Alerting System Agreement Page 1 of 7
COOPERATIVE AGREEMENT
BETWEEN
TH
E CITY OF ALAMEDA
AND
AL
AMEDA COUNTY FIRE DEPARTMENT
__________________________________
Fire Station Alerting System
Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A Alerting System Agreement Page 2 of 7
This Cooperative Agreement (Agreement) is entered into this _____ day of ____________________, 2025, by and between the Alameda County Fire Department (“ACFD”), a dependent fire district governed by the Alameda County Board of Supervisors as its Board of Directors and the City of Alameda, hereinafter referred to as “City,” collectively hereinafter referred to as “Parties,” for the Installation of the Phoenix G2 Station Alerting System by Honeywell (Alerting System) at the City’s fire stations, hereinafter referred to as “Project.”
RECITALS
This Agreement is made with reference to the following facts and objectives:
A. WHEREAS, the Parties have entered into an agreement for the provision of dispatching services (Services Contract), pursuant to which ACFD provides contract fire and emergency dispatching services within the incorporated limits of the City, at City cost; and B. WHEREAS, under the Services Contract, the City provides ACFD the use of City- owned fire stations at no cost to ACFD; and
C. WHEREAS, the Parties wish to enter into this Agreement for the installation of an upgraded fire station alerting system to all City fire stations (the Project); and D. WHEREAS, the Project consists of all aspects of the procurement and installation of the Alerting System, at each City fire station location (see Attachment A: list of components broken out by station) including receiving manufacturer certification of the Alerting System; and E. WHEREAS, the Project involves pulling ethernet cables (with labels) within each of the City’s fire stations (see Attachment B: floor plan layout for each station), accompanying electrical work as required by the system manufacturer, installation of the alerting system speakers and lights, wall/ceiling patchwork, and other associated work as needed; and F. WHEREAS, the Project, including the Project budget, has been reviewed and approved by the City’s representative under the Services Contract; and G. WHEREAS, the ACFD has entered into a contract for the Project and will provide an ACFD Project Manager to oversee and coordinate the work with the City; and H. WHEREAS, City provided ACFD with recommendations and direction for the Project; and
I. WHEREAS, the Parties have identified efficiencies to be gained from using ACFD’s contractor to complete the Project; and
Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A Alerting System Agreement Page 3 of 7
J. WHEREAS, the Parties agree that FIVE HUNDRED SIXTY THOUSAND FOUR HUNDRED TWENTY FIVE DOLLARS AND FORTY-SEVEN CENTS ($560,425.47) represents the Project cost without contingency, as detailed in Attachment A. The Project covers installation work to be performed at the following City Fire Stations:
Alameda Fire Station 1 — 2401 Encinal Ave., Alameda, CA 94501 Alameda Fire Station 2 — 635 Pacific Ave., Alameda, CA 94501 Alameda Fire Station 3 — 1625 Buena Vista Ave, Alameda, CA 94501 Alameda Fire Station 4 — 2595 Mecartney Rd, Alameda, CA 94502 The wiring diagrams for the project are detailed in Attachment B; and K. WHEREAS, the Parties agree that a ten percent (10%) contingency of FIFTY SIX THOUSAND FORTY-TWO DOLLARS AND FIFTY-FIVE CENTS ($56,042.55) is reasonable and appropriate, bringing the total Project cost covered by this agreement to SIX HUNDRED
SIXTEEN THOUSAND FOUR HUNDRED SIXTY-EIGHT DOLLARS AND TWO CENTS ($616,468.02) (the “Not-to-Exceed Amount”); and,
L. WHEREAS, City will reimburse ACFD for all of the actual costs ACFD incurs for the Project; and
M. WHEREAS, the City acknowledges that successful completion of the Project will require City cooperation, including timely responses; and N. WHEREAS, the City Council of the City of Alameda can authorize the City Manager to enter into Agreements with governmental entities pursuant to Alameda Municipal Code Section 2-59 et seq. and the City of Alameda’s Purchasing Policy.
NOW THEREFORE, THE PARTIES TO THIS AGREEMENT COVENANT AND AGREE AS FOLLOWS:
TERMS
ACFD agrees that it shall:
1. Contract for completion of the Project.
2. Track costs incurred due to the Project (“Costs”).
3. Send itemized invoices to the City in a timely manner for the Costs incurred. If Costs are anticipated to exceed the Not-to-Exceed Amount, ACFD will inform the City, and ACFD may place the Project on hold until additional funding is approved by the City. Any costs that result from placing the Project on hold shall be Costs to Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A Alerting System Agreement Page 4 of 7
be borne by the City, however, ACFD shall take reasonable steps to mitigate such costs.
City agrees that it shall:
1. Identify a Project Manager who will coordinate the Project who has sufficient authority to act on behalf of the City with respect to the Project.
2. Provide timely support to ACFD in implementing the recommendations and directions provided by the City for the Project. Such support shall include, but not be limited to:
a. Providing and facilitating unobstructed access to each City fire station; b. Coordinating the participation of any needed City staff as required to respond to Project needs;
c. Providing review and responses to any requests for information, change orders, or notices within five business days or on a mutually-agreeable timeline; d. Participating in meetings, including any walk-throughs, and identifying items needed for project closeout, including any punch list items; e. Securing any required City approvals needed to complete the Project, including, but not limited to, approvals by planning staff, environmental staff, building official, public works director, construction manager, City Council, or City Manager.
3. Reimburse ACFD within forty-five (45) calendar days of receipt of ACFD’s invoice for Costs incurred, up to the Not-to-Exceed Amount.
4. Upon completion of the Project, assume ownership and responsibility for the components of the Alerting System, including maintenance, provided, however, that the Parties may separately agree that ACFD will maintain the Alerting System, such as through the Services Contract.
If Costs are anticipated to exceed the Not-to-Exceed-Amount, seek any needed approval for allocation of additional funding in a timely manner to avoid additional costs and timely complete the Project. If additional funding is not available to complete the project, ACFD may Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A Alerting System Agreement Page 5 of 7
put the Project on hold. City shall be responsible for any costs that result from placing the Project on hold, however, ACFD shall take reasonable steps to mitigate such costs.
LEGAL STATUS OF THIS AGREEMENT
Nothing in this Agreement shall be considered to establish a partnership or any other joint venture between the Parties, or a joint powers agreement under the California Government Code.
NO THIRD-PARTY BENEFICIARY
This Agreement shall not be construed or deemed to be an agreement for the benefit of any third party or parties, and no third party or parties shall have any claim or right of action hereunder for any causes whatsoever.
NOTICES
Notices regarding proposed changes to this Agreement are to be sent as follows:
TO CITY:
Alameda Fire Department
1300 Park St
Alameda CA, 94501
Attn: Nick Luby, Fire Chief
TO ACFD:
Alameda County Fire Department
6363 Clark Ave
Dublin, CA 94568
Attn: Eric Moore, Deputy Chief
WAIVER
The parties’ waiver of any term, condition or covenant, or breach of any term, condition or covenant shall not be construed as a waiver of any subsequent breach or violation of the same or any other term, condition or covenant.
AMENDMENTS
No alterations or changes to the terms of this Agreement shall be valid unless made in writing and signed by all parties hereto.
Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A Alerting System Agreement Page 6 of 7
SEVERABILITY CLAUSE
In any case one or more of the provisions contained herein shall, for any reason, be held invalid, illegal, or unenforceable in any respect, it shall not affect the validity of the other provisions, which shall remain in full force and effect.
INDEMNIFICATION
ACFD agrees to indemnify, defend, and hold harmless the City, its City Council, boards, commissions, officials, employees, and volunteers (“Indemnitees”) from and against loss, damages, liability, claims, suits, costs and expenses, arising from or in any manner connected solely to ACFD’s negligent or willful misconduct regarding performance of services or work conducted or performed pursuant to this Agreement.
The City agrees to defend, indemnify, and hold harmless the Alameda County Fire Department, the County of Alameda, their governing bodies, their predecessors, successors, assignees, agents, departments, officials, representatives, employees and all persons acting by, through, under or in concert with any of them, and each of them (collectively “ACFD Indemnitees”) from and against loss, damages, liability, claims, suits, costs and expenses, arising from or in any manner connected solely to the City’s negligent or willful misconduct regarding performance of services or work conducted or performed pursuant to this Agreement.
TERM
The term of this Agreement shall be effective when this Agreement is fully executed by all parties, and this Agreement shall terminate when all the obligations for each party have been fulfilled.
MODIFICATION
This Agreement constitutes the entire Agreement, supersedes all prior written or oral understandings, and may only be changed by a written amendment executed by both parties.
COUNTERPARTS
This Agreement may be executed in multiple counterparts, each of which shall be deemed an original and all of which together shall constitute one instrument.
SIGNATURE PAGE FOLLOWS
Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A Alerting System Agreement Page 7 of 7
IN WITNESS WHEREOF, the Parties hereto have executed this agreement as of the effective date, which is the date first written above.
ALAMEDA COUNTY FIRE
DEPARTMENT
By:
__________________________
CITY OF ALAMEDA
By:
__________________________________
David Haubert
President, Board of Directors
Date: __________________________
Approved as to form:
Donna R. Ziegler, County Counsel
By: __________________________
Kathy Lee
Deputy County Counsel
Jennifer Ott
City Manager
Date:_________________________________
______________________________________
Nicohlas Luby
Fire Chief
Date:_________________________________
Approved as to form and legality:
Yibin Chen, City Attorney
By: __________________________________
Douglas W. McManaway
Assistant City Attorney
Date: ________________________________
Attest:
By: __________________________________
By signing above, the signatory warrants and represents that he/she executed this Agreement in his/her authorized capacity and that by his/her signature on this Agreement, he/she or the entity upon behalf of which he/she acted, executed this Agreement
Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A 4/2/2025
4/2/2025
Exhibit A
List of Components Broken Out by Station
Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A
US DIGITAL DESIGNS QUOTE
1150 W Grove Pkwy St #110
Tempe, Arizona 85283
877-551-8733 tel 480-290-7892 fax DATE: 3/6/2025
Expires: 6/4/2025
Quote SUBMITTED TO:
ALAMEDA COUNTY, CA
Alameda County Fire Departments
REF PROPOSAL
Item Unit Mfr Qty Description Part No. US List Unit QUOTE UNIT QUOTE EXT SL1 Ea USDD 1 G2 VOICEALERT - Single Station License. VA $ 1,102.50 $ 992.25 $ 992.25 SL2 Ea/Yr USDD 24 G2 MOBILE FSAS APP - Single Device License. Up to 24 Licenses-Per-ATX G2-APP-DLI $ 124.50 $ 112.05 No Charge Item Unit Mfr Qty Description Part No. US List Unit QUOTE UNIT QUOTE EXT SC1 Kit USDD 1
G2 ATX STATION CONTROLLER -
Power/Signal/Control up to 8 peripheral Remote
Options. 4 Unique Amps/Zones available.
ATX $ 23,272.50 $ 20,945.25 $ 20,945.25 SC2 Kit USDD 1
G2 EXPANSION KIT - Allows ability to
Power/Signal/Control up to 12 more peripheral
Remote options per EXP.
EXP $ 7,838.00 $ 7,054.20 $ 7,054.20 SC4a Ea TBD 2 ATX UPS, Standard UPS-STD $ 988.00 $ 889.20 $ 1,778.40 SC4b Ea TBD 2 Shelf/Bracket, Wall-Mount for UPS UPS-WMB $ 75.00 $ 67.50 $ 135.00 Item Unit Mfr Qty Description Part No. US List Unit QUOTE UNIT QUOTE EXT SP2 Ea USDD 6 G2 COLOR INDICATOR REMOTE Module - Up to
8 unique colors CIR $ 949.00 $ 854.10 $ 5,124.60 Ea USDD 6 G2 COLOR INDICATOR REMOTE BACK BOX CIR-SMB $ 165.10 $ 148.59 $ 891.54 SP5 Ea USDD 5 Push Button, Standard (Black) PB-B $ 126.50 $ 113.85 $ 569.25 SP7 Ea USDD 5 G2 MESSAGE REMOTE 2 Module MR2 $ 1,525.00 $ 1,372.50 $ 6,862.50 Ea USDD 3 G2 LCD MESSAGE SIGN / 28" Active Screen
width / Configurable display USDD-LCD-SIGN $ 3,000.00 $ 2,700.00 $ 8,100.00 SP9d Ea TBD 3 MS Mount - Articulating, Long reach MS-MNT-ART-L $ 390.00 $ 351.00 $ 1,053.00 SP10a Ea USDD 1 G2 ROOM REMOTE 2 Module RR2 $ 2,167.00 $ 1,950.30 $ 1,950.30 Ea USDD 2
G2 REMOTE USER INTERFACE Module –
Extends ATX’s TouchScreen User Interface into
alternative area of same building.
RUI $ 2,167.00 $ 1,950.30 $ 3,900.60 SP11a Ea USDD 20 G2 SPEAKER - LED Illuminated - FLUSH Mount, 70v SPK-LED-FM $ 374.00 $ 336.60 $ 6,732.00 SP11b Ea USDD 1 G2 SPEAKER - LED Illuminated - SURFACE
Mount (Metal Box), 70v SPK-LED-SM $ 374.00 $ 336.60 $ 336.60 SP12a Ea USDD 1 G2 SPEAKER - OmniAlertStrobe SPK-OAS $ 1,050.00 $ 945.00 $ 945.00 SP13a Ea USDD 6 SPEAKER - STANDARD, FLUSH Mount, 70v SPK-STD-FM $ 126.00 $ 113.40 $ 680.40 SP13b Ea USDD 3 SPEAKER - STANDARD, SURFACE Mount (Metal Box), 70v SPK-STD-SM $ 126.00 $ 113.40 $ 340.20 SP14 Ea USDD 1 SPEAKER - APP BAY/OUTDOOR - Weatherized, Surface Mount, 70v SPK-W-SM $ 373.75 $ 336.38 $ 336.38 SP15 Ea USDD 1 G2 Strobe Light / Red LED STR $ 661.50 $ 595.35 $ 595.35 ALAMEDA FS01
Based from USDD G2 Fire Station Alerting System Design DrawingUSDD.AMDA.ALL_STATIONS.FSA.2025.02.24
STATION SYSTEM LICENSES
STATION SYSTEM CONTROLLER
STATION SYSTEM PERIPHERAL COMPONENTS
CA_ALCO010 v4 STATION-LEVEL
PROPRIETARY and CONFIDENTIAL ALAMEDA 01 SYSTEM Page 4 of 65 Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A Item Unit Mfr Qty Description Part No. US List Unit QUOTE UNIT QUOTE EXT SS1 Ea USDD 1 Station Installation by: Tech Electric, Bob McCabe; [email protected] ST-INST $ 90,671.35 $ 81,604.22 $ 81,604.22 SS3 Ea USDD 1 Station Configuration & Start-Up ST-SU $ 1,666.67 $ 1,500.00 $ 1,500.00 SS4 Ea USDD 1 Station Project Management ST-PM $ 1,111.11 $ 1,000.00 $ 1,000.00 SS5 Ea USDD 1 Station Engineering / Design Services ST-ES $ 333.33 $ 300.00 $ 300.00 SS6 Ea USDD 1 Station Documentation ST-DM $ 44.44 $ 40.00 $ 40.00 Item Unit Mfr Qty Description Part No. US List Unit QUOTE UNIT QUOTE EXT SW1 YR USDD 1.0
[STANDARD] 1st YEAR WARRANTY &
SUPPORT FOR THIS STATION SYSTEM (or
component): Telephone / Remote Access Support
(8:00 AM - 5:00 PM MST)
RS-1YR-STD $ 7,702.54 $ 6,932.28 No Charge SW2 YR USDD 1.0
[STANDARD] EACH ADDITIONAL YEAR (12-
Months) WARRANTY & SUPPORT FOR THIS
STATION SYSTEM (or Component): Telephone /
Remote Access Support (8:00 AM - 5:00 PM MST)
RS-AYR-STD $ 7,702.54 $ 6,932.28 $ 6,932.28 153,767.03$
1,606.00$
6,932.28$
7,105.59$
169,410.90$ STATION SUBTOTAL:
STATION SYSTEM WARRANTY & OPTIONAL RECURRING ANNUAL SUPPORT Warranty & Support:
Estimated Taxes:
STATION SYSTEM SERVICES
Shipping:
ALAMEDA FS01 System:
PROPRIETARY and CONFIDENTIAL ALAMEDA 01 SYSTEM Page 5 of 65 Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A
US DIGITAL DESIGNS QUOTE
1150 W Grove Pkwy St #110
Tempe, Arizona 85283
877-551-8733 tel 480-290-7892 fax DATE: 3/6/2025
Expires: 6/4/2025
Quote SUBMITTED TO:
ALAMEDA COUNTY, CA
Alameda County Fire Departments
REF PROPOSAL
Item Unit Mfr Qty Description Part No. US List Unit QUOTE UNIT QUOTE EXT SL1 Ea USDD 1 G2 VOICEALERT - Single Station License. VA $ 1,102.50 $ 992.25 $ 992.25 SL2 Ea/Yr USDD 24 G2 MOBILE FSAS APP - Single Device License. Up to 24 Licenses-Per-ATX G2-APP-DLI $ 124.50 $ 112.05 No Charge Item Unit Mfr Qty Description Part No. US List Unit QUOTE UNIT QUOTE EXT SC1 Kit USDD 1
G2 ATX STATION CONTROLLER -
Power/Signal/Control up to 8 peripheral Remote
Options. 4 Unique Amps/Zones available.
ATX $ 23,272.50 $ 20,945.25 $ 20,945.25 SC4a Ea TBD 1 ATX UPS, Standard UPS-STD $ 988.00 $ 889.20 $ 889.20 SC4b Ea TBD 1 Shelf/Bracket, Wall-Mount for UPS UPS-WMB $ 75.00 $ 67.50 $ 67.50 Item Unit Mfr Qty Description Part No. US List Unit QUOTE UNIT QUOTE EXT SP2 Ea USDD 3 G2 COLOR INDICATOR REMOTE Module - Up to
8 unique colors CIR $ 949.00 $ 854.10 $ 2,562.30 Ea USDD 3 G2 COLOR INDICATOR REMOTE BACK BOX CIR-SMB $ 165.10 $ 148.59 $ 445.77 SP5 Ea USDD 4 Push Button, Standard (Black) PB-B $ 126.50 $ 113.85 $ 455.40 SP7 Ea USDD 4 G2 MESSAGE REMOTE 2 Module MR2 $ 1,525.00 $ 1,372.50 $ 5,490.00 Ea USDD 1 G2 LCD MESSAGE SIGN / 28" Active Screen
width / Configurable display USDD-LCD-SIGN $ 3,000.00 $ 2,700.00 $ 2,700.00 SP9d Ea TBD 1 MS Mount - Articulating, Long reach MS-MNT-ART-L $ 390.00 $ 351.00 $ 351.00 Ea USDD 1
G2 REMOTE USER INTERFACE Module –
Extends ATX’s TouchScreen User Interface into
alternative area of same building.
RUI $ 2,167.00 $ 1,950.30 $ 1,950.30 SP11a Ea USDD 14 G2 SPEAKER - LED Illuminated - FLUSH Mount, 70v SPK-LED-FM $ 374.00 $ 336.60 $ 4,712.40 SP12a Ea USDD 1 G2 SPEAKER - OmniAlertStrobe SPK-OAS $ 1,050.00 $ 945.00 $ 945.00 SP13a Ea USDD 5 SPEAKER - STANDARD, FLUSH Mount, 70v SPK-STD-FM $ 121.00 $ 108.90 $ 544.50 SP14 Ea USDD 1 SPEAKER - APP BAY/OUTDOOR - Weatherized, Surface Mount, 70v SPK-W-SM $ 373.75 $ 336.38 $ 336.38 SP15 Ea USDD 1 G2 Strobe Light / Red LED STR $ 661.50 $ 595.35 $ 595.35
STATION SYSTEM LICENSES
STATION SYSTEM CONTROLLER
STATION SYSTEM PERIPHERAL COMPONENTS
CA_ALCO010 v4 STATION-LEVEL
ALAMEDA FS02
Based from USDD G2 Fire Station Alerting System Design Drawing # USDD.AMDA.ALL_STATIONS.FSA.2025.02.24 PROPRIETARY and CONFIDENTIAL ALAMEDA 02 SYSTEM Page 6 of 65 Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A Item Unit Mfr Qty Description Part No. US List Unit QUOTE UNIT QUOTE EXT SS1 Ea USDD 1 Station Installation by: Tech Electric, Bob McCabe; [email protected] ST-INST $ 57,527.40 $ 51,774.66 $ 51,774.66 SS3 Ea USDD 1 Station Configuration & Start-Up ST-SU $ 1,666.67 $ 1,500.00 $ 1,500.00 SS4 Ea USDD 1 Station Project Management ST-PM $ 1,111.11 $ 1,000.00 $ 1,000.00 SS5 Ea USDD 1 Station Engineering / Design Services ST-ES $ 333.33 $ 300.00 $ 300.00 SS6 Ea USDD 1 Station Documentation ST-DM $ 44.44 $ 40.00 $ 40.00 Item Unit Mfr Qty Description Part No. US List Unit QUOTE UNIT QUOTE EXT SW1 YR USDD 1.0
[STANDARD] 1st YEAR WARRANTY & SUPPORT
FOR THIS STATION SYSTEM (or component):
Telephone / Remote Access Support (8:00 AM -
5:00 PM MST)
RS-1YR-STD $ 4,886.96 $ 4,398.26 No Charge SW2 YR USDD 1.0
[STANDARD] EACH ADDITIONAL YEAR (12-
Months) WARRANTY & SUPPORT FOR THIS
STATION SYSTEM (or Component): Telephone /
Remote Access Support (8:00 AM - 5:00 PM MST)
RS-AYR-STD $ 4,886.96 $ 4,398.26 $ 4,398.26 98,597.26$
949.00$
4,398.26$
4,508.22$
108,452.73$
Estimated Taxes:
STATION SYSTEM SERVICES
STATION SUBTOTAL:
STATION SYSTEM WARRANTY & OPTIONAL RECURRING ANNUAL SUPPORT ALAMEDA FS02 System:
Shipping:
Warranty & Support:
PROPRIETARY and CONFIDENTIAL ALAMEDA 02 SYSTEM Page 7 of 65 Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A
US DIGITAL DESIGNS QUOTE
1150 W Grove Pkwy St #110
Tempe, Arizona 85283
877-551-8733 tel 480-290-7892 fax DATE: 3/6/2025
Expires: 6/4/2025
Quote SUBMITTED TO:
ALAMEDA COUNTY, CA
Alameda County Fire Departments
REF PROPOSAL
Item Unit Mfr Qty Description Part No. US List Unit QUOTE UNIT QUOTE EXT SL1 Ea USDD 1 G2 VOICEALERT - Single Station License. VA $ 1,102.50 $ 992.25 $ 992.25 SL2 Ea/Yr USDD 24 G2 MOBILE FSAS APP - Single Device License. Up to 24 Licenses-Per-ATX G2-APP-DLI $ 124.50 $ 112.05 No Charge Item Unit Mfr Qty Description Part No. US List Unit QUOTE UNIT QUOTE EXT SC1 Kit USDD 1
G2 ATX STATION CONTROLLER -
Power/Signal/Control up to 8 peripheral Remote
Options. 4 Unique Amps/Zones available.
ATX $ 23,272.50 $ 20,945.25 $ 20,945.25 SC2 Kit USDD 1
G2 EXPANSION KIT - Allows ability to
Power/Signal/Control up to 12 more peripheral
Remote options per EXP.
EXP $ 7,838.00 $ 7,054.20 $ 7,054.20 SC4a Ea TBD 2 ATX UPS, Standard UPS-STD $ 988.00 $ 889.20 $ 1,778.40 SC4b Ea TBD 2 Shelf/Bracket, Wall-Mount for UPS UPS-WMB $ 75.00 $ 67.50 $ 135.00 Item Unit Mfr Qty Description Part No. US List Unit QUOTE UNIT QUOTE EXT SP2 Ea USDD 4 G2 COLOR INDICATOR REMOTE Module - Up to
8 unique colors CIR $ 949.00 $ 854.10 $ 3,416.40 Ea USDD 4 G2 COLOR INDICATOR REMOTE BACK BOX CIR-SMB $ 165.10 $ 148.59 $ 594.36 SP5 Ea USDD 4 Push Button, Standard (Black) PB-B $ 126.50 $ 113.85 $ 455.40 SP7 Ea USDD 4 G2 MESSAGE REMOTE 2 Module MR2 $ 1,525.00 $ 1,372.50 $ 5,490.00 Ea USDD 2 G2 LCD MESSAGE SIGN / 28" Active Screen
width / Configurable display USDD-LCD-SIGN $ 3,000.00 $ 2,700.00 $ 5,400.00 SP9d Ea TBD 2 MS Mount - Articulating, Long reach MS-MNT-ART-L $ 390.00 $ 351.00 $ 702.00 SP10a Ea USDD 1 G2 ROOM REMOTE 2 Module RR2 $ 2,167.00 $ 1,950.30 $ 1,950.30 Ea USDD 1
G2 REMOTE USER INTERFACE Module –
Extends ATX’s TouchScreen User Interface into
alternative area of same building.
RUI $ 2,167.00 $ 1,950.30 $ 1,950.30 SP11a Ea USDD 14 G2 SPEAKER - LED Illuminated - FLUSH Mount, 70v SPK-LED-FM $ 374.00 $ 336.60 $ 4,712.40 SP11b Ea USDD 1 G2 SPEAKER - LED Illuminated - SURFACE
Mount (Metal Box), 70v SPK-LED-SM $ 374.00 $ 336.60 $ 336.60 SP12a Ea USDD 1 G2 SPEAKER - OmniAlertStrobe SPK-OAS $ 1,050.00 $ 945.00 $ 945.00 SP13a Ea USDD 6 SPEAKER - STANDARD, FLUSH Mount, 70v SPK-STD-FM $ 121.00 $ 108.90 $ 653.40 SP14 Ea USDD 1 SPEAKER - APP BAY/OUTDOOR - Weatherized, Surface Mount, 70v SPK-W-SM $ 373.75 $ 336.38 $ 336.38 SP15 Ea USDD 1 G2 Strobe Light / Red LED STR $ 661.50 $ 595.35 $ 595.35
STATION SYSTEM LICENSES
STATION SYSTEM CONTROLLER
STATION SYSTEM PERIPHERAL COMPONENTS
CA_ALCO010 v4 STATION-LEVEL
ALAMEDA FS03
Based from USDD G2 Fire Station Alerting System Design Drawing #USDD.AMDA.ALL_STATIONS.FSA.2025.02.24 PROPRIETARY and CONFIDENTIAL ALAMEDA 03 SYSTEM Page 8 of 65 Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A Item Unit Mfr Qty Description Part No. US List Unit QUOTE UNIT QUOTE EXT SS1 Ea USDD 1 Station Installation by: Tech Electric, Bob McCabe; [email protected] ST-INST $ 76,440.99 $ 68,796.89 $ 68,796.89 SS3 Ea USDD 1 Station Configuration & Start-Up ST-SU $ 1,666.67 $ 1,500.00 $ 1,500.00 SS4 Ea USDD 1 Station Project Management ST-PM $ 1,111.11 $ 1,000.00 $ 1,000.00 SS5 Ea USDD 1 Station Engineering / Design Services ST-ES $ 333.33 $ 300.00 $ 300.00 SS6 Ea USDD 1 Station Documentation ST-DM $ 44.44 $ 40.00 $ 40.00 Item Unit Mfr Qty Description Part No. US List Unit QUOTE UNIT QUOTE EXT SW1 YR USDD 1.0
[STANDARD] 1st YEAR WARRANTY &
SUPPORT FOR THIS STATION SYSTEM (or
component): Telephone / Remote Access Support
(8:00 AM - 5:00 PM MST)
RS-1YR-STD $ 6,493.67 $ 5,844.30 No Charge SW2 YR USDD 1.0
[STANDARD] EACH ADDITIONAL YEAR (12-
Months) WARRANTY & SUPPORT FOR THIS
STATION SYSTEM (or Component): Telephone /
Remote Access Support (8:00 AM - 5:00 PM MST)
RS-AYR-STD $ 6,493.67 $ 5,844.30 $ 5,844.30 130,079.88$
1,314.00$
5,844.30$
5,990.41$
143,228.58$
Estimated Taxes:
STATION SYSTEM SERVICES
STATION SUBTOTAL:
STATION SYSTEM WARRANTY & OPTIONAL RECURRING ANNUAL SUPPORT ALAMEDA FS03 System:
Shipping:
Warranty & Support:
PROPRIETARY and CONFIDENTIAL ALAMEDA 03 SYSTEM Page 9 of 65 Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A
US DIGITAL DESIGNS QUOTE
1150 W Grove Pkwy St #110
Tempe, Arizona 85283
877-551-8733 tel 480-290-7892 fax DATE: 3/6/2025
Expires: 6/4/2025
Quote SUBMITTED TO:
ALAMEDA COUNTY, CA
Alameda County Fire Departments
REF PROPOSAL
Item Unit Mfr Qty Description Part No. US List Unit QUOTE UNIT QUOTE EXT SL1 Ea USDD 1 G2 VOICEALERT - Single Station License. VA $ 1,102.50 $ 992.25 $ 992.25 SL2 Ea/Yr USDD 24 G2 MOBILE FSAS APP - Single Device License. Up to 24 Licenses-Per-ATX G2-APP-DLI $ 124.50 $ 112.05 No Charge Item Unit Mfr Qty Description Part No. US List Unit QUOTE UNIT QUOTE EXT SC1 Kit USDD 1
G2 ATX STATION CONTROLLER -
Power/Signal/Control up to 8 peripheral Remote
Options. 4 Unique Amps/Zones available.
ATX $ 23,272.50 $ 20,945.25 $ 20,945.25 SC2 Kit USDD 1
G2 EXPANSION KIT - Allows ability to
Power/Signal/Control up to 12 more peripheral
Remote options per EXP.
EXP $ 7,838.00 $ 7,054.20 $ 7,054.20 SC4a Ea TBD 2 ATX UPS, Standard UPS-STD $ 988.00 $ 889.20 $ 1,778.40 SC4b Ea TBD 2 Shelf/Bracket, Wall-Mount for UPS UPS-WMB $ 75.00 $ 67.50 $ 135.00 Item Unit Mfr Qty Description Part No. US List Unit QUOTE UNIT QUOTE EXT SP2 Ea USDD 2 G2 COLOR INDICATOR REMOTE Module - Up to
8 unique colors CIR $ 949.00 $ 854.10 $ 1,708.20 Ea USDD 2 G2 COLOR INDICATOR REMOTE BACK BOX CIR-SMB $ 165.10 $ 148.59 $ 297.18 SP5 Ea USDD 3 Push Button, Standard (Black) PB-B $ 126.50 $ 113.85 $ 341.55 SP7 Ea USDD 6 G2 MESSAGE REMOTE 2 Module MR2 $ 1,525.00 $ 1,372.50 $ 8,235.00 Ea USDD 1 G2 LCD MESSAGE SIGN / 28" Active Screen
width / Configurable display USDD-LCD-SIGN $ 3,000.00 $ 2,700.00 $ 2,700.00 SP9d Ea TBD 1 MS Mount - Articulating, Long reach MS-MNT-ART-L $ 390.00 $ 351.00 $ 351.00 Ea USDD 1
G2 REMOTE USER INTERFACE Module –
Extends ATX’s TouchScreen User Interface into
alternative area of same building.
RUI $ 2,167.00 $ 1,950.30 $ 1,950.30 SP11a Ea USDD 22 G2 SPEAKER - LED Illuminated - FLUSH Mount, 70v SPK-LED-FM $ 374.00 $ 336.60 $ 7,405.20 SP11b Ea USDD 1 G2 SPEAKER - LED Illuminated - SURFACE
Mount (Metal Box), 70v SPK-LED-SM $ 374.00 $ 336.60 $ 336.60 SP12a Ea USDD 1 G2 SPEAKER - OmniAlertStrobe SPK-OAS $ 1,050.00 $ 945.00 $ 945.00 SP13a Ea USDD 1 SPEAKER - STANDARD, FLUSH Mount, 70v SPK-STD-FM $ 121.00 $ 108.90 $ 108.90 SP14 Ea USDD 1 SPEAKER - APP BAY/OUTDOOR - Weatherized, Surface Mount, 70v SPK-W-SM $ 373.75 $ 336.38 $ 336.38 SP15 Ea USDD 2 G2 Strobe Light / Red LED STR $ 661.50 $ 595.35 $ 1,190.70
STATION SYSTEM LICENSES
STATION SYSTEM CONTROLLER
STATION SYSTEM PERIPHERAL COMPONENTS
CA_ALCO010 v4 STATION-LEVEL
ALAMEDA FS04
Based from USDD G2 Fire Station Alerting System Design Drawing #USDD.AMDA.ALL_STATIONS.FSA.2025.02.24 PROPRIETARY and CONFIDENTIAL ALAMEDA 04 SYSTEM Page 10 of 65 Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A Item Unit Mfr Qty Description Part No. US List Unit QUOTE UNIT QUOTE EXT SS1 Ea USDD 1 Station Installation by: Tech Electric, Bob McCabe; [email protected] ST-INST $ 50,215.99 $ 45,194.39 $ 45,194.39 SS3 Ea USDD 1 Station Configuration & Start-Up ST-SU $ 1,666.67 $ 1,500.00 $ 1,500.00 SS4 Ea USDD 1 Station Project Management ST-PM $ 1,111.11 $ 1,000.00 $ 1,000.00 SS5 Ea USDD 1 Station Engineering / Design Services ST-ES $ 333.33 $ 300.00 $ 300.00 SS6 Ea USDD 1 Station Documentation ST-DM $ 44.44 $ 40.00 $ 40.00 Item Unit Mfr Qty Description Part No. US List Unit QUOTE UNIT QUOTE EXT SW1 YR USDD 1.0
[STANDARD] 1st YEAR WARRANTY &
SUPPORT FOR THIS STATION SYSTEM (or
component): Telephone / Remote Access Support
(8:00 AM - 5:00 PM MST)
RS-1YR-STD $ 4,265.85 $ 3,839.27 No Charge SW2 YR USDD 1.0
[STANDARD] EACH ADDITIONAL YEAR (12-
Months) WARRANTY & SUPPORT FOR THIS
STATION SYSTEM (or Component): Telephone /
Remote Access Support (8:00 AM - 5:00 PM MST)
RS-AYR-STD $ 4,265.85 $ 3,839.27 $ 3,839.27 86,427.04$
757.00$
3,839.27$
3,935.25$
94,958.55$
Estimated Taxes:
STATION SYSTEM SERVICES
STATION SUBTOTAL:
STATION SYSTEM WARRANTY & OPTIONAL RECURRING ANNUAL SUPPORT CASTRO VALLEY FS06 System:
Shipping:
Warranty & Support:
PROPRIETARY and CONFIDENTIAL CASTRO VALLEY 06 SYSTEM Page 13 of 65 Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A Exhibit B
Layouts for City of Alameda Fire Stations G2 Alerting System Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A USDD.CA_ALME.FS01.FSA.DWGdesign by
A B C D
4 3
2 1
4 2
1 A B C D
3projectbuildingfilenamedate
THIS DOCUMENTCONTAINS CONFIDENTIALAND PROPRIETARYINFORMATION WHICH ISTHE EXCLUSIVE PROPERTYOF US DIGITAL DESIGNS,INC. REPRODUCTION,DISTRIBUTION OR USE BYOTHERS, IN WHOLE OR INPART, IS NOT PERMITTEDWITHOUT THE WRITTENAUTHORIZATION FROM USDIGITAL DESIGNS, INC.
PoE = G2 ATX Power-over-Ethernet (PoE) ports 1...8 and G2 Expansion Module ports 1...12A.n = G2 ATX Amplifier 1...4 EA.n = G2 External Amplifier 1...n CH.n = G2 Message Remote 2 Channel 1 or 2 2/20/2025 - 6:14PM
SYMBOLDESCRIPTIONG2 I/O REMOTE
PUSH BUTTON - RED
G2 STROBE LIGHT
SPEAKER,WEATHER-PROOFSPEAKER, FLUSHMOUNTSPEAKER, METALBOX G2 LED SPEAKER,FLUSH MOUNTG2 LED SPEAKER,METAL BOX
OEM TRANSFORMER
G2 HDTV REMOTEG2 COLORINDICATOR REMOTE
OEM FLAT PANELMONITOR, XX", WITHMOUNT
G2 MESSAGE SIGN(STANDARD 24")
VOLUME CONTROL(CUSTOMER SUPPLIED)
G2 ROOM REMOTE 2
ARTICULATING ARMMOUNT - LONG
ADAPTER PLATEDOUBLE
PUSH BUTTON - BLACK
G2 OMNIALERTSTROBE SPEAKER
G2 MESSAGE SIGN(MINI 12")
G2 MESSAGE SIGN(EXTENDED 36")
ADAPTER PLATESINGLE
G2 MESSAGEREMOTE 2
G2 ATXSTATION CONTROLLERG2 EXPANSIONMODULEG2-UNINTERRUPTIBLEPOWER SUPPLYOEM AMPLIFIER
SYMBOLDESCRIPTION
TVR
PBBLACK
PBRED
CIR
STR
ATX
I/O
T
UPSAMP
MR2
EXP
RR2
SS
S
ADS
MSE
MSML
MSSMSM
VC
SS
ADP
MSML
S
LARG2 LOCAL AREAREMOTE
FPD MOUNT
FPM - XX"
address
END-USER APPROVES STATIONDESIGN FOR PURPOSES OFOBTAINING QUOTE.INSTALLER CONFIRMS DESIGNALIGNS WITH SITE CONDITIONS.(SPEAKER MOUNTING TYPE, ATXLOCATION ETC.)
SIGNATURE REQUIRED
G2 VIDEO DOORSTATIONVDS
ALAMEDA FD, CA (ALAMEDA COUNTY)FIRE STATION 1 FIRST FLOOR2401 ENCINAL AVE, ALAMEDA, CADMG, JA NOTES:1. SEE ARCHITECTURAL SPECIFICATIONS FOR ALL ROUGH-IN AND INSTALLATION DETAILS.2. US DIGITAL DESIGNS DOES NOT SUPPLY BACK BOXES, CONDUITS, OR MOUNTING FASTENERS.3. PHOENIX G2 SYSTEM IS ABLE TO SIGNAL OWNER-FURBISHED SYSTEMS, (EXHAUST, LIGHT, GASSHUT OFF, ETC.) BUT USDD DOES NOT SUPPLY THESE SYSTEMS AND CANNOT WARRANT ORSUPPORT ANY OF THEIR PERFORMANCE BEYOND THE TRANSMISSION OF RELAY SIGNAL TO THEM.4. US DIGITAL DESIGNS FIRE STATION ALERTING PLANS ARE DIAGRAMMATIC AND FOR QUOTINGPURPOSES ONLY. DRAWING MAY NOT BE TO SCALE.
INSTALLER NOTES:1. INSTALLER TO VERIFY WALL AND CEILING TYPE TO DETERMINE NEED FOR FLUSH OR SURFACE MOUNTINSTALLATION OF EQUIPMENT SPECIFIED.2. INSTALLER TO COORDINATE CONNECTION BETWEEN ATX STATION CONTROLLER’S LINE-LEVEL AUDIOOUTPUT AND (EXISTING) OWNER-FURBISHED HOUSE AUDIO SYSTEM (AMP). (IF APPLICABLE)3. INSTALLER TO PROVIDE CAT6 & 18/4 CABLES FROM ATX CONTROLLER TO CUSTOMER'S STATION RADIOFOR BACKUP.4. INSTALLER TO PROVIDE CAT6 CABLE FROM ATX CONTROLLER WAN OUTPUT TO CUSTOMER'S IN-STATIONNETWORK.5. INSTALLER TO COORDINATE CONNECTION BETWEEN EXISTING STATION LIGHTING CONTROL SYSTEMAND RELAY OUTPUT FROM ATX STATION CONTROLLER OR I/O REMOTE WITH OWNER. (IF APPLICABLE)6. VOLUME CONTROL TO BE PROVIDED BY OWNER OR INSTALLER IF SHOWN ON DRAWING.7. INSTALLER TO VERIFY AND CONSIDER LOCATION(S) OF NETWORK AND RADIO CONNECTIONS.
S
S
TO MR2-A BY ATXACK x4
PoE
A.1
A.1S S
SS
SS
S
S S
SS S
SA.4
STR
A.2
MR2MR2-A PoE
MR2MR2-B PoE
MR2MR2-C PoE
MR2MR2-D PoE
MS-LCD
MSML
PBBLACK
DOORBELL
ATXUPSMR2MR2-E PoE
MR2-E CH.1
MR2-E CH.2
S S
CIRSM-CIR-BBSM-CIR-BB
CIRSM-CIR-BBSM-CIR-BB
CIRSM-CIR-BBSM-CIR-BB
EXPUPS
PoEMS-LCD
MSML
CIRSM-CIR-BBSM-CIR-BB
PoE
PoE PoE
PoE
US DIGITAL DESIGNSCountName1 G2 ATX STATION CONTROLLER (ATX)6G2 CIR BACK BOX - SURFACE MOUNT (CIR-SMB)6 G2 COLOR INDICATOR REMOTE (CIR)1 G2 EXPANSION UNIT (G2-EXP)20G2 LED SPEAKER (G2-LVL-HC-70)1 G2 LED SPEAKER-BOX5 G2 MESSAGE REMOTE 23 G2 MESSAGE SIGN LCD (USDD-LCD-SIGN)1 G2 OMNISTROBE SPEAKER2 G2 REMOTE USER INTERFACE MODULE1 G2 ROOM REMOTE 2 (RR-2)1 G2 STROBE LIGHT3 MS MOUNT ARTICULATING (MS-MNT)5 PUSH BUTTON (PB-B)6 SPEAKER FLUSH MOUNT1 SPEAKER WEATHER-PROOF3 SPEAKER-METAL BOX2 UPS (UPS-STD)US DIGITAL DESIGNSCountName17 G2 PoE PORT REQUIRED
PBBLACKPBBLACKPBBLACKPBBLACK
RR2
PoERUI
PoE
EQUIPMENT IN IT ROOM
STAIRSIT ROOM
Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A USDD.CA_ALME.FS01.FSA.DWG
design by
A B C D
4 3
2 1
4 2
1 A B C D
3 project
building
filename
date
T H I S D O C U M E N T
CONTAINS CONFIDENTIAL
A N D P R O P R I E T A R Y
INFORMATION WHICH IS
THE EXCLUSIVE PROPERTY
OF US DIGITAL DESIGNS,
I N C . R E P R O D U C T I O N ,
DISTRIBUTION OR USE BY
OTHERS, IN WHOLE OR IN
PART, IS NOT PERMITTED
WITHOUT THE WRITTEN
AUTHORIZATION FROM US
DI GIT AL D ESI GNS, I NC.
PoE = G2 ATX Power-over-Ethernet (PoE) ports 1...8 and G2 Expansion Module ports 1...12 A.n = G2 ATX Amplifier 1...4 EA.n = G2 External Amplifier 1...n CH.n = G2 Message Remote 2 Channel 1 or 2 2/20/2025 - 6:14PM
SYMBOL DESCRIPTION
G2 I/O REMOTE
PUSH BUTTON - RED
G2 STROBE LIGHT
SPEAKER,
WEATHER-PROOF
SPEAKER, FLUSH
MOUNT
SPEAKER, METAL
BOX
G2 LED SPEAKER,
FLUSH MOUNT
G2 LED SPEAKER,
METAL BOX
OEM TRANSFORMER
G2 HDTV REMOTE
G2 COLOR
INDICATOR REMOTE
OEM FLAT PANEL
MONITOR, XX", WITH
MOUNT
G2 MESSAGE SIGN
(STANDARD 24")
VOLUME CONTROL
(CUSTOMER SUPPLIED)
G2 ROOM REMOTE 2
ARTICULATING ARM
MOUNT - LONG
ADAPTER PLATE
DOUBLE
PUSH BUTTON - BLACK
G2 OMNIALERT
STROBE SPEAKER
G2 MESSAGE SIGN
(MINI 12")
G2 MESSAGE SIGN
(EXTENDED 36")
ADAPTER PLATE
SINGLE
G2 MESSAGE
REMOTE 2
G2 ATX
STATION CONTROLLER
G2 EXPANSION
MODULE
G2-UNINTERRUPTIBLE
POWER SUPPLY
OEM AMPLIFIER
SYMBOL DESCRIPTION
TVR
PB
BLACK
PB
RED
CIR
STR
ATX
I/O
T
UPS
AMP
MR2
EXP
RR2
S
S
S
ADS
MSE
MSML
MSS
MSM
VC
S
S
ADP
MSML
S
LAR G2 LOCAL AREA
REMOTE
FPD MOUNT
FPM - XX"
address
END-USER APPROVES STATION
DESIGN FOR PURPOSES OF
OBTAINING QUOTE.
INSTALLER CONFIRMS DESIGN
ALIGNS WITH SITE CONDITIONS.
(SPEAKER MOUNTING TYPE, ATX
LOCATION ETC.)
SIGNATURE REQUIRED
G2 VIDEO DOOR
STATION
VDS
ALAMEDA FD, CA (ALAMEDA COUNTY)
FIRE STATION 1 SECOND FLOOR
2401 ENCINAL AVE, ALAMEDA, CA
DMG, JA
NOTES:
1. SEE ARCHITECTURAL SPECIFICATIONS FOR ALL ROUGH-IN AND INSTALLATION DETAILS.
2. US DIGITAL DESIGNS DOES NOT SUPPLY BACK BOXES, CONDUITS, OR MOUNTING FASTENERS.
3. PHOENIX G2 SYSTEM IS ABLE TO SIGNAL OWNER-FURBISHED SYSTEMS, (EXHAUST, LIGHT, GAS SHUT OFF, ETC.) BUT USDD DOES NOT SUPPLY THESE SYSTEMS AND CANNOT WARRANT OR SUPPORT ANY OF THEIR PERFORMANCE BEYOND THE TRANSMISSION OF RELAY SIGNAL TO THEM.
4. US DIGITAL DESIGNS FIRE STATION ALERTING PLANS ARE DIAGRAMMATIC AND FOR QUOTING PURPOSES ONLY. DRAWING MAY NOT BE TO SCALE.
INSTALLER NOTES:
1. INSTALLER TO VERIFY WALL AND CEILING TYPE TO DETERMINE NEED FOR FLUSH OR SURFACE MOUNT INSTALLATION OF EQUIPMENT SPECIFIED.
2. INSTALLER TO COORDINATE CONNECTION BETWEEN ATX STATION CONTROLLER’S LINE-LEVEL AUDIO OUTPUT AND (EXISTING) OWNER-FURBISHED HOUSE AUDIO SYSTEM (AMP). (IF APPLICABLE)
3. INSTALLER TO PROVIDE CAT6 & 18/4 CABLES FROM ATX CONTROLLER TO CUSTOMER'S STATION RADIO FOR BACKUP.
4. INSTALLER TO PROVIDE CAT6 CABLE FROM ATX CONTROLLER WAN OUTPUT TO CUSTOMER'S IN-STATION NETWORK.
5. INSTALLER TO COORDINATE CONNECTION BETWEEN EXISTING STATION LIGHTING CONTROL SYSTEM AND RELAY OUTPUT FROM ATX STATION CONTROLLER OR I/O REMOTE WITH OWNER. (IF APPLICABLE)
6. VOLUME CONTROL TO BE PROVIDED BY OWNER OR INSTALLER IF SHOWN ON DRAWING.
7. INSTALLER TO VERIFY AND CONSIDER LOCATION(S) OF NETWORK AND RADIO CONNECTIONS.
S
S
S
S
A.2
A.1
S
S
PoE
MR2-B CH.1
MR2-B CH.2
MR2-C CH.1
MR2-C CH.2
MR2-D CH.1
MR2-D CH.1
A.3
MS-LCD
PoE
MSML
CIR
SM-CIR-BBSM-CIR-BB
CIR
SM-CIR-BBSM-CIR-BB
S
RUI
PoE
PoE
S
STAIRS
S
S
S
S
S
S
S
Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A USDD.CA_ALME.FS02.FSA.DWG
design by
A B C D
4 3
2 1
4 2
1 A B C D
3 project
building
filename
date
T H I S D O C U M E N T
CONTAINS CONFIDENTIAL
A N D P R O P R I E T A R Y
INFORMATION WHICH IS
THE EXCLUSIVE PROPERTY
OF US DIGITAL DESIGNS,
I N C . R E P R O D U C T I O N ,
DISTRIBUTION OR USE BY
OTHERS, IN WHOLE OR IN
PART, IS NOT PERMITTED
WITHOUT THE WRITTEN
AUTHORIZATION FROM US
DI GIT AL D ESI GNS, I NC.
PoE = G2 ATX Power-over-Ethernet (PoE) ports 1...8 and G2 Expansion Module ports 1...12 A.n = G2 ATX Amplifier 1...4 EA.n = G2 External Amplifier 1...n CH.n = G2 Message Remote 2 Channel 1 or 2 2/20/2025 - 6:14PM
SYMBOL DESCRIPTION
G2 I/O REMOTE
PUSH BUTTON - RED
G2 STROBE LIGHT
SPEAKER,
WEATHER-PROOF
SPEAKER, FLUSH
MOUNT
SPEAKER, METAL
BOX
G2 LED SPEAKER,
FLUSH MOUNT
G2 LED SPEAKER,
METAL BOX
OEM TRANSFORMER
G2 HDTV REMOTE
G2 COLOR
INDICATOR REMOTE
OEM FLAT PANEL
MONITOR, XX", WITH
MOUNT
G2 MESSAGE SIGN
(STANDARD 24")
VOLUME CONTROL
(CUSTOMER SUPPLIED)
G2 ROOM REMOTE 2
ARTICULATING ARM
MOUNT - LONG
ADAPTER PLATE
DOUBLE
PUSH BUTTON - BLACK
G2 OMNIALERT
STROBE SPEAKER
G2 MESSAGE SIGN
(MINI 12")
G2 MESSAGE SIGN
(EXTENDED 36")
ADAPTER PLATE
SINGLE
G2 MESSAGE
REMOTE 2
G2 ATX
STATION CONTROLLER
G2 EXPANSION
MODULE
G2-UNINTERRUPTIBLE
POWER SUPPLY
OEM AMPLIFIER
SYMBOL DESCRIPTION
TVR
PB
BLACK
PB
RED
CIR
STR
ATX
I/O
T
UPS
AMP
MR2
EXP
RR2
S
S
S
ADS
MSE
MSML
MSS
MSM
VC
S
S
ADP
MSML
S
LAR G2 LOCAL AREA
REMOTE
FPD MOUNT
FPM - XX"
address
END-USER APPROVES STATION
DESIGN FOR PURPOSES OF
OBTAINING QUOTE.
INSTALLER CONFIRMS DESIGN
ALIGNS WITH SITE CONDITIONS.
(SPEAKER MOUNTING TYPE, ATX
LOCATION ETC.)
SIGNATURE REQUIRED
G2 VIDEO DOOR
STATION
VDS
ALAMEDA FD, CA (ALAMEDA COUNTY)
FIRE STATION 2
635 PACIFIC AVE, ALAMEDA, CA 94501
DMG, JA
NOTES:
1. SEE ARCHITECTURAL SPECIFICATIONS FOR ALL ROUGH-IN AND INSTALLATION DETAILS.
2. US DIGITAL DESIGNS DOES NOT SUPPLY BACK BOXES, CONDUITS, OR MOUNTING FASTENERS.
3. PHOENIX G2 SYSTEM IS ABLE TO SIGNAL OWNER-FURBISHED SYSTEMS, (EXHAUST, LIGHT, GAS SHUT OFF, ETC.) BUT USDD DOES NOT SUPPLY THESE SYSTEMS AND CANNOT WARRANT OR SUPPORT ANY OF THEIR PERFORMANCE BEYOND THE TRANSMISSION OF RELAY SIGNAL TO THEM.
4. US DIGITAL DESIGNS FIRE STATION ALERTING PLANS ARE DIAGRAMMATIC AND FOR QUOTING PURPOSES ONLY. DRAWING MAY NOT BE TO SCALE.
INSTALLER NOTES:
1. INSTALLER TO VERIFY WALL AND CEILING TYPE TO DETERMINE NEED FOR FLUSH OR SURFACE MOUNT INSTALLATION OF EQUIPMENT SPECIFIED.
2. INSTALLER TO COORDINATE CONNECTION BETWEEN ATX STATION CONTROLLER’S LINE-LEVEL AUDIO OUTPUT AND (EXISTING) OWNER-FURBISHED HOUSE AUDIO SYSTEM (AMP). (IF APPLICABLE)
3. INSTALLER TO PROVIDE CAT6 & 18/4 CABLES FROM ATX CONTROLLER TO CUSTOMER'S STATION RADIO FOR BACKUP.
4. INSTALLER TO PROVIDE CAT6 CABLE FROM ATX CONTROLLER WAN OUTPUT TO CUSTOMER'S IN-STATION NETWORK.
5. INSTALLER TO COORDINATE CONNECTION BETWEEN EXISTING STATION LIGHTING CONTROL SYSTEM AND RELAY OUTPUT FROM ATX STATION CONTROLLER OR I/O REMOTE WITH OWNER. (IF APPLICABLE)
6. VOLUME CONTROL TO BE PROVIDED BY OWNER OR INSTALLER IF SHOWN ON DRAWING.
7. INSTALLER TO VERIFY AND CONSIDER LOCATION(S) OF NETWORK AND RADIO CONNECTIONS.
STR
S
S
A.4
ATX
UPS
MR2-A PoE
MR2
A.3
A.1
A.1
SSSSS
PoE
A.2
MR2-B PoE
MR2
MR2-C PoE
MR2
MR2-D PoE
MR2
MR2-B CH.1
PoEMS-LCD
MSML
PB
BLACK
DOORBELL
CIR
SM-CIR-BBSM-CIR-BB
RUI
PB
BLACK
PB
BLACK
PB
BLACK
ACK x3
CIRSM-CIR-BBSM-CIR-BB
US DIGITAL DESIGNS
Count Name
1 G2 ATX STATION CONTROLLER
3 G2 CIR BACK BOX - SURFACE MOUNT (CIR-SMB)
3 G2 COLOR INDICATOR REMOTE (CIR)
14 G2 LED SPEAKER (G2-LVL-HC-70)
4 G2 MESSAGE REMOTE 2
1 G2 MESSAGE SIGN LCD (USDD-LCD-SIGN)
1 G2 OMNISTROBE SPEAKER
1 G2 REMOTE USER INTERFACE MODULE
1 G2 STROBE LIGHT
1 G2 UPS (G2-UPS)
1 MS MOUNT ARTICULATING (MS-MNT)
4 PUSH BUTTON (PB-B)
5 SPEAKER FLUSH MOUNT
1 SPEAKER WEATHER-PROOF
US DIGITAL DESIGNS
Count Name
8 G2 PoE PORT REQUIREDWOMEN'S
CIR
SM-CIR-BBSM-CIR-BB
PoE
MR2-A CH.1
MR2-A CH.2
MR2-B CH.2 MR2-C CH.1 MR2-C CH.2 MR2-D CH.1 MR2-D CH.2
PoE
S S SS
SS
S
S
S
S
S S S
S
Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A USDD.CA_ALME.FS03.FSA.DWGdesign by
A B C D
4 3
2 1
4 2
1 A B C D
3projectbuildingfilenamedate
THIS DOCUMENTCONTAINS CONFIDENTIALAND PROPRIETARYINFORMATION WHICH ISTHE EXCLUSIVE PROPERTYOF US DIGITAL DESIGNS,INC. REPRODUCTION,DISTRIBUTION OR USE BYOTHERS, IN WHOLE OR INPART, IS NOT PERMITTEDWITHOUT THE WRITTENAUTHORIZATION FROM USDIGITAL DESIGNS, INC.
PoE = G2 ATX Power-over-Ethernet (PoE) ports 1...8 and G2 Expansion Module ports 1...12A.n = G2 ATX Amplifier 1...4 EA.n = G2 External Amplifier 1...n CH.n = G2 Message Remote 2 Channel 1 or 2 2/20/2025 - 6:14PM
SYMBOLDESCRIPTIONG2 I/O REMOTE
PUSH BUTTON - RED
G2 STROBE LIGHT
SPEAKER,WEATHER-PROOFSPEAKER, FLUSHMOUNTSPEAKER, METALBOX G2 LED SPEAKER,FLUSH MOUNTG2 LED SPEAKER,METAL BOX
OEM TRANSFORMER
G2 HDTV REMOTEG2 COLORINDICATOR REMOTE
OEM FLAT PANELMONITOR, XX", WITHMOUNT
G2 MESSAGE SIGN(STANDARD 24")
VOLUME CONTROL(CUSTOMER SUPPLIED)
G2 ROOM REMOTE 2
ARTICULATING ARMMOUNT - LONG
ADAPTER PLATEDOUBLE
PUSH BUTTON - BLACK
G2 OMNIALERTSTROBE SPEAKER
G2 MESSAGE SIGN(MINI 12")
G2 MESSAGE SIGN(EXTENDED 36")
ADAPTER PLATESINGLE
G2 MESSAGEREMOTE 2
G2 ATXSTATION CONTROLLERG2 EXPANSIONMODULEG2-UNINTERRUPTIBLEPOWER SUPPLYOEM AMPLIFIER
SYMBOLDESCRIPTION
TVR
PBBLACK
PBRED
CIR
STR
ATX
I/O
T
UPSAMP
MR2
EXP
RR2
SS
S
ADS
MSE
MSML
MSSMSM
VC
SS
ADP
MSML
S
LARG2 LOCAL AREAREMOTE
FPD MOUNT
FPM - XX"
address
END-USER APPROVES STATIONDESIGN FOR PURPOSES OFOBTAINING QUOTE.INSTALLER CONFIRMS DESIGNALIGNS WITH SITE CONDITIONS.(SPEAKER MOUNTING TYPE, ATXLOCATION ETC.)
SIGNATURE REQUIRED
G2 VIDEO DOORSTATIONVDS
ALAMEDA FD, CA (ALAMEDA COUNTY)FIRE STATION 3 FIRST FLOOR1625 BUENA VISTA AVE, ALAMEDA, CA 94501DMG, JA NOTES:1. SEE ARCHITECTURAL SPECIFICATIONS FOR ALL ROUGH-IN AND INSTALLATION DETAILS.2. US DIGITAL DESIGNS DOES NOT SUPPLY BACK BOXES, CONDUITS, OR MOUNTING FASTENERS.3. PHOENIX G2 SYSTEM IS ABLE TO SIGNAL OWNER-FURBISHED SYSTEMS, (EXHAUST, LIGHT, GASSHUT OFF, ETC.) BUT USDD DOES NOT SUPPLY THESE SYSTEMS AND CANNOT WARRANT ORSUPPORT ANY OF THEIR PERFORMANCE BEYOND THE TRANSMISSION OF RELAY SIGNAL TO THEM.4. US DIGITAL DESIGNS FIRE STATION ALERTING PLANS ARE DIAGRAMMATIC AND FOR QUOTINGPURPOSES ONLY. DRAWING MAY NOT BE TO SCALE.
INSTALLER NOTES:1. INSTALLER TO VERIFY WALL AND CEILING TYPE TO DETERMINE NEED FOR FLUSH OR SURFACE MOUNTINSTALLATION OF EQUIPMENT SPECIFIED.2. INSTALLER TO COORDINATE CONNECTION BETWEEN ATX STATION CONTROLLER’S LINE-LEVEL AUDIOOUTPUT AND (EXISTING) OWNER-FURBISHED HOUSE AUDIO SYSTEM (AMP). (IF APPLICABLE)3. INSTALLER TO PROVIDE CAT6 & 18/4 CABLES FROM ATX CONTROLLER TO CUSTOMER'S STATION RADIOFOR BACKUP.4. INSTALLER TO PROVIDE CAT6 CABLE FROM ATX CONTROLLER WAN OUTPUT TO CUSTOMER'S IN-STATIONNETWORK.5. INSTALLER TO COORDINATE CONNECTION BETWEEN EXISTING STATION LIGHTING CONTROL SYSTEMAND RELAY OUTPUT FROM ATX STATION CONTROLLER OR I/O REMOTE WITH OWNER. (IF APPLICABLE)6. VOLUME CONTROL TO BE PROVIDED BY OWNER OR INSTALLER IF SHOWN ON DRAWING.7. INSTALLER TO VERIFY AND CONSIDER LOCATION(S) OF NETWORK AND RADIO CONNECTIONS.
STR
S
TO MR2 BY ATX
ACK x3
SA.4
SS
S A.2
A.1
MR2MR2-A PoE
MR2MR2-B PoE
MR2MR2-C PoE
PBBLACKDOORBELL
PBBLACKPBBLACKPBBLACK
CIRPoESM-CIR-BBSM-CIR-BB
MS-LCDPoE
MSML
MS-LCDPoEMSML
MR2MR2-D PoE
US DIGITAL DESIGNSCountName12 G2 PoE PORT REQUIRED
ATXUPSUPSEXP
US DIGITAL DESIGNSCountName1 G2 ATX STATION CONTROLLER (ATX)4G2 CIR BACK BOX - SURFACE MOUNT (CIR-SMB)4 G2 COLOR INDICATOR REMOTE (CIR)1 G2 EXPANSION UNIT (G2-EXP)14G2 LED SPEAKER (G2-LVL-HC-70)1 G2 LED SPEAKER-BOX4 G2 MESSAGE REMOTE 22 G2 MESSAGE SIGN LCD (USDD-LCD-SIGN)1 G2 OMNISTROBE SPEAKER1 G2 REMOTE USER INTERFACE MODULE1 G2 ROOM REMOTE 2 (RR-2)1 G2 STROBE LIGHT2 MS MOUNT ARTICULATING (MS-MNT)4 PUSH BUTTON (PB-B)6 SPEAKER FLUSH MOUNT1 SPEAKER WEATHER-PROOF2 UPS (UPS-STD) PoERR2
S
SS
S S S
S
S
Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A USDD.CA_ALME.FS03.FSA.DWGdesign by
A B C D
4 3
2 1
4 2
1 A B C D
3projectbuildingfilenamedate
THIS DOCUMENTCONTAINS CONFIDENTIALAND PROPRIETARYINFORMATION WHICH ISTHE EXCLUSIVE PROPERTYOF US DIGITAL DESIGNS,INC. REPRODUCTION,DISTRIBUTION OR USE BYOTHERS, IN WHOLE OR INPART, IS NOT PERMITTEDWITHOUT THE WRITTENAUTHORIZATION FROM USDIGITAL DESIGNS, INC.
PoE = G2 ATX Power-over-Ethernet (PoE) ports 1...8 and G2 Expansion Module ports 1...12A.n = G2 ATX Amplifier 1...4 EA.n = G2 External Amplifier 1...n CH.n = G2 Message Remote 2 Channel 1 or 2 2/20/2025 - 6:14PM
SYMBOLDESCRIPTIONG2 I/O REMOTE
PUSH BUTTON - RED
G2 STROBE LIGHT
SPEAKER,WEATHER-PROOFSPEAKER, FLUSHMOUNTSPEAKER, METALBOX G2 LED SPEAKER,FLUSH MOUNTG2 LED SPEAKER,METAL BOX
OEM TRANSFORMER
G2 HDTV REMOTEG2 COLORINDICATOR REMOTE
OEM FLAT PANELMONITOR, XX", WITHMOUNT
G2 MESSAGE SIGN(STANDARD 24")
VOLUME CONTROL(CUSTOMER SUPPLIED)
G2 ROOM REMOTE 2
ARTICULATING ARMMOUNT - LONG
ADAPTER PLATEDOUBLE
PUSH BUTTON - BLACK
G2 OMNIALERTSTROBE SPEAKER
G2 MESSAGE SIGN(MINI 12")
G2 MESSAGE SIGN(EXTENDED 36")
ADAPTER PLATESINGLE
G2 MESSAGEREMOTE 2
G2 ATXSTATION CONTROLLERG2 EXPANSIONMODULEG2-UNINTERRUPTIBLEPOWER SUPPLYOEM AMPLIFIER
SYMBOLDESCRIPTION
TVR
PBBLACK
PBRED
CIR
STR
ATX
I/O
T
UPSAMP
MR2
EXP
RR2
SS
S
ADS
MSE
MSML
MSSMSM
VC
SS
ADP
MSML
S
LARG2 LOCAL AREAREMOTE
FPD MOUNT
FPM - XX"
address
END-USER APPROVES STATIONDESIGN FOR PURPOSES OFOBTAINING QUOTE.INSTALLER CONFIRMS DESIGNALIGNS WITH SITE CONDITIONS.(SPEAKER MOUNTING TYPE, ATXLOCATION ETC.)
SIGNATURE REQUIRED
G2 VIDEO DOORSTATIONVDS
ALAMEDA FD, CA (ALAMEDA COUNTY)FIRE STATION 3 SECOND FLOOR1625 BUENA VISTA AVE, ALAMEDA, CA 94501DMG, JA NOTES:1. SEE ARCHITECTURAL SPECIFICATIONS FOR ALL ROUGH-IN AND INSTALLATION DETAILS.2. US DIGITAL DESIGNS DOES NOT SUPPLY BACK BOXES, CONDUITS, OR MOUNTING FASTENERS.3. PHOENIX G2 SYSTEM IS ABLE TO SIGNAL OWNER-FURBISHED SYSTEMS, (EXHAUST, LIGHT, GASSHUT OFF, ETC.) BUT USDD DOES NOT SUPPLY THESE SYSTEMS AND CANNOT WARRANT ORSUPPORT ANY OF THEIR PERFORMANCE BEYOND THE TRANSMISSION OF RELAY SIGNAL TO THEM.4. US DIGITAL DESIGNS FIRE STATION ALERTING PLANS ARE DIAGRAMMATIC AND FOR QUOTINGPURPOSES ONLY. DRAWING MAY NOT BE TO SCALE.
INSTALLER NOTES:1. INSTALLER TO VERIFY WALL AND CEILING TYPE TO DETERMINE NEED FOR FLUSH OR SURFACE MOUNTINSTALLATION OF EQUIPMENT SPECIFIED.2. INSTALLER TO COORDINATE CONNECTION BETWEEN ATX STATION CONTROLLER’S LINE-LEVEL AUDIOOUTPUT AND (EXISTING) OWNER-FURBISHED HOUSE AUDIO SYSTEM (AMP). (IF APPLICABLE)3. INSTALLER TO PROVIDE CAT6 & 18/4 CABLES FROM ATX CONTROLLER TO CUSTOMER'S STATION RADIOFOR BACKUP.4. INSTALLER TO PROVIDE CAT6 CABLE FROM ATX CONTROLLER WAN OUTPUT TO CUSTOMER'S IN-STATIONNETWORK.5. INSTALLER TO COORDINATE CONNECTION BETWEEN EXISTING STATION LIGHTING CONTROL SYSTEMAND RELAY OUTPUT FROM ATX STATION CONTROLLER OR I/O REMOTE WITH OWNER. (IF APPLICABLE)6. VOLUME CONTROL TO BE PROVIDED BY OWNER OR INSTALLER IF SHOWN ON DRAWING.7. INSTALLER TO VERIFY AND CONSIDER LOCATION(S) OF NETWORK AND RADIO CONNECTIONS.
S S S
A.2
A.1
MR2-B CH.1 MR2-C CH.1MR2-B CH.2 MR2-C CH.2
PoERUI
MR2-D CH.1
MR2-D CH.2CIRPoESM-CIR-BBSM-CIR-BB CIRPoESM-CIR-BBSM-CIR-BB CIRPoESM-CIR-BBSM-CIR-BB S S
S
S S S
S
Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A USDD.CA_ALME.FS04.FSA.DWGdesign by
A B C D
4 3
2 1
4 2
1 A B C D
3projectbuildingfilenamedate
THIS DOCUMENTCONTAINS CONFIDENTIALAND PROPRIETARYINFORMATION WHICH ISTHE EXCLUSIVE PROPERTYOF US DIGITAL DESIGNS,INC. REPRODUCTION,DISTRIBUTION OR USE BYOTHERS, IN WHOLE OR INPART, IS NOT PERMITTEDWITHOUT THE WRITTENAUTHORIZATION FROM USDIGITAL DESIGNS, INC.
PoE = G2 ATX Power-over-Ethernet (PoE) ports 1...8 and G2 Expansion Module ports 1...12A.n = G2 ATX Amplifier 1...4 EA.n = G2 External Amplifier 1...n CH.n = G2 Message Remote 2 Channel 1 or 2 2/20/2025 - 6:14PM
SYMBOLDESCRIPTIONG2 I/O REMOTE
PUSH BUTTON - RED
G2 STROBE LIGHT
SPEAKER,WEATHER-PROOFSPEAKER, FLUSHMOUNTSPEAKER, METALBOX G2 LED SPEAKER,FLUSH MOUNTG2 LED SPEAKER,METAL BOX
OEM TRANSFORMER
G2 HDTV REMOTEG2 COLORINDICATOR REMOTE
OEM FLAT PANELMONITOR, XX", WITHMOUNT
G2 MESSAGE SIGN(STANDARD 24")
VOLUME CONTROL(CUSTOMER SUPPLIED)
G2 ROOM REMOTE 2
ARTICULATING ARMMOUNT - LONG
ADAPTER PLATEDOUBLE
PUSH BUTTON - BLACK
G2 OMNIALERTSTROBE SPEAKER
G2 MESSAGE SIGN(MINI 12")
G2 MESSAGE SIGN(EXTENDED 36")
ADAPTER PLATESINGLE
G2 MESSAGEREMOTE 2
G2 ATXSTATION CONTROLLERG2 EXPANSIONMODULEG2-UNINTERRUPTIBLEPOWER SUPPLYOEM AMPLIFIER
SYMBOLDESCRIPTION
TVR
PBBLACK
PBRED
CIR
STR
ATX
I/O
T
UPSAMP
MR2
EXP
RR2
SS
S
ADS
MSE
MSML
MSSMSM
VC
SS
ADP
MSML
S
LARG2 LOCAL AREAREMOTE
FPD MOUNT
FPM - XX"
address
END-USER APPROVES STATIONDESIGN FOR PURPOSES OFOBTAINING QUOTE.INSTALLER CONFIRMS DESIGNALIGNS WITH SITE CONDITIONS.(SPEAKER MOUNTING TYPE, ATXLOCATION ETC.)
SIGNATURE REQUIRED
G2 VIDEO DOORSTATIONVDS
ALAMEDA FD, CA (ALAMEDA COUNTY)FIRE STATION 42595 MECARTNEY RD, ALAMEDA, CA 94502DMG, JA NOTES:1. SEE ARCHITECTURAL SPECIFICATIONS FOR ALL ROUGH-IN AND INSTALLATION DETAILS.2. US DIGITAL DESIGNS DOES NOT SUPPLY BACK BOXES, CONDUITS, OR MOUNTING FASTENERS.3. PHOENIX G2 SYSTEM IS ABLE TO SIGNAL OWNER-FURBISHED SYSTEMS, (EXHAUST, LIGHT, GASSHUT OFF, ETC.) BUT USDD DOES NOT SUPPLY THESE SYSTEMS AND CANNOT WARRANT ORSUPPORT ANY OF THEIR PERFORMANCE BEYOND THE TRANSMISSION OF RELAY SIGNAL TO THEM.4. US DIGITAL DESIGNS FIRE STATION ALERTING PLANS ARE DIAGRAMMATIC AND FOR QUOTINGPURPOSES ONLY. DRAWING MAY NOT BE TO SCALE.
INSTALLER NOTES:1. INSTALLER TO VERIFY WALL AND CEILING TYPE TO DETERMINE NEED FOR FLUSH OR SURFACE MOUNTINSTALLATION OF EQUIPMENT SPECIFIED.2. INSTALLER TO COORDINATE CONNECTION BETWEEN ATX STATION CONTROLLER’S LINE-LEVEL AUDIOOUTPUT AND (EXISTING) OWNER-FURBISHED HOUSE AUDIO SYSTEM (AMP). (IF APPLICABLE)3. INSTALLER TO PROVIDE CAT6 & 18/4 CABLES FROM ATX CONTROLLER TO CUSTOMER'S STATION RADIOFOR BACKUP.4. INSTALLER TO PROVIDE CAT6 CABLE FROM ATX CONTROLLER WAN OUTPUT TO CUSTOMER'S IN-STATIONNETWORK.5. INSTALLER TO COORDINATE CONNECTION BETWEEN EXISTING STATION LIGHTING CONTROL SYSTEMAND RELAY OUTPUT FROM ATX STATION CONTROLLER OR I/O REMOTE WITH OWNER. (IF APPLICABLE)6. VOLUME CONTROL TO BE PROVIDED BY OWNER OR INSTALLER IF SHOWN ON DRAWING.7. INSTALLER TO VERIFY AND CONSIDER LOCATION(S) OF NETWORK AND RADIO CONNECTIONS.
S
TO MR2 BY ATX
A.2
A.1S
S
PoE
MR2-A PoEMR2MR2-B PoEMR2MR2-C PoEMR2MR2-D PoEMR2
MR2-B CH.1
MR2-B CH.2
MR2-C CH.1
MR2-C CH.2
MR2-D CH.1MR2-D CH.2
MR2-E CH.1
MR2-E CH.2
MR2-E PoEMR2
PBBLACKDOORBELL
PBBLACK
SA.4
MR2-F PoEMR2
MR2-F CH.1
MR2-F CH.1MS-LCDPoEMSML
RUI
PBBLACK
ACK x2
US DIGITAL DESIGNSCountName10G2 PoE PORT REQUIRED
STR
STR
ATXUPSUPSEXP
US DIGITAL DESIGNSCountName1G2 ATX STATION CONTROLLER (ATX)2G2 CIR BACK BOX - SURFACE MOUNT(CIR-SMB)2G2 COLOR INDICATOR REMOTE (CIR)1 G2 EXPANSION UNIT (G2-EXP)22G2 LED SPEAKER (G2-LVL-HC-70)1 G2 LED SPEAKER-BOX6 G2 MESSAGE REMOTE 21G2 MESSAGE SIGN LCD (USDD-LCD-SIGN)1 G2 OMNISTROBE SPEAKER1G2 REMOTE USER INTERFACE MODULE2 G2 STROBE LIGHT1MS MOUNT ARTICULATING (MS-MNT)3 PUSH BUTTON (PB-B)1 SPEAKER FLUSH MOUNT1 SPEAKER WEATHER-PROOF2 UPS (UPS-STD) CIRPoESM-CIR-BBSM-CIR-BB
CIRPoE
SM-CIR-BBSM-CIR-BB
S S S
S
S SSSS
SSS
S
S
S
SS
S
S
S
S
S
Docusign Envelope ID: 0F9A7EA8-11B7-49AA-8C4A-7A1AA4F08E7A