ALIGN
OWNER:
LENNAR HOMES OF CALIFORNIA, LLC
2000 FIVEPOINT 3RD FOOR
IRVINE, CA 92618
CONTACT: DENNIS HARDGRAVE
ARCHITECT:
PAGE & TURNBULL
523 W 6TH ST SUITE 1013,
LOS ANGELES, CA 90014
CONTACT: HEATHER MANGRUM
STRUCTURAL:
HOLMES
523 W 6TH ST #1122,
LOS ANGELES, CA 90014
CONTACT: JUSTIN SHARKEY
MECHANICAL, ELECTRICAL, & PLUMBING:
BUDLONG
633 W 5TH ST 26TH FLOOR,
LOS ANGELES, CA 90071
CONTACT: FELIX GOMEZ
PROJECT DIRECTORY
PROJECT INFORMATION
PROJECT NAME
ADDRESS
OWNER
EXISTING
OCCUPANCIES
PROPOSED
POCCUPANCIES
CONSTR TYPE
FIRE PROTECTION
NUMBER OF STORIES
BUILDING HEIGHT
PARKING
FIRE RATING REQUIREMENTS
BLDG ELEMENT
PRIMARY STRUCT FRAME
EXTERIOR BEARING WALLS
INTERIOR BEARING WALLS
INTERIOR NONBEARING WALLS
FLOOR CONSTRUCTION
ROOF CONSTRUCTION
CONSTRUCTION
TYPE VB
0 0
0 0
0 0
SCHOLLE HOUSE RESTORATION
W PONDEROSA DRIVE AT
SPRINGVILLE DRIVE; CAMARILLO, CA
LENNAR HOMES OF CALIFORNIA,
LLC
R-3
R-3
(E) TYPE V -B
SMOKE DETECTORS
1 20 FT
DETAHCED GARAGE
THE PROPOSED PROJECT FOR THE SCHOLLE FARM
HOUSE IS TO REHABILITATE THE BUILDING FOR
CONTINUED USE AS A SINGLE -FAMILY RESIDENCE.
A DETACHED GARAGE WILL BE PART OF THE PROJECT.
THE SCHOLLE FARM HOUSE WILL UNDERGO EXTERIOR
REPAIRS AND RESTORATION, INCLUDING THE WOOD
SIDING, WINDOWS, AND ROOF EAVE WITH DECORATIVE
BRACKETS. THE FRONT PORCH WILL BE REOPENED BY
REMOVING THE ENCLOSED STRUCTURE AND RE -ROOFED
WITH NEW ASPHALT SHINGLES. A NEW CONCRETE
FOUNDATION WALL WILL MATCH THE ORIGINAL
FOUNDATION'S HEIGHT. ALTERATIONS INCLUDE
REMOVING THE SOUTH FAÇADE'S GABLED VESTIBULE AND
CONVERTING THE EAST PORCH TO AN OPEN DESIGN.
INTERIOR SPACES WILL MOSTLY REMAIN, WITH A LIVING
ROOM EXPANSION, RECONFIGURATION OF BEDROOMS TO
ADD AN ENSUITE BATHROOM FOR THE PRIMARY
BEDROOM, AND AN ENLARGED, RENOVATED BATHROOM.
THE KITCHEN WILL BE UPDATED AND OPENED TO THE
DINING ROOM. NEW PLUMBING, MECHANICAL, AND
ELECTRICAL UPGRADES WILL BE INSTALLED. A DETACHED
TWO -CAR GARAGE WILL BE ADDED SOUTHWEST OF THE
HOUSE.
THE DRAWING SET IS PREPARED BY PAGE&TURNBULL. IT
ALSO INCLUDES STRUCTURAL PLANS BY HOLMES
ENGINEERING, MECHANICAL, ELECTRICAL AND PLUMBING
PLANS BY BUDLONG ENGINEERS.
PROJECT DESCRIPTION
APPLICABLE CODES
SECRETARY OF INTERIOR STANDARDS
2022 CALIFORNIA BUILDING STANDARDS CODE
(CALIFORNIA CODE REGULATIONS, TITLE 24)
AS AMENDED BY THE CITY OF SAN FRANCISCO:
• PART 01 - CALIFORNIA ADMINISTRATIVE CODE
• PART 02 - CALIFORNIA BUILDING CODE (CBC)
• PART 03 - CALIFORNIA ELECTRICAL CODE (CEC)
• PART 04 - CALIFORNIA MECHANICAL CODE (CMC)
• PART 05 - CALIFORNIA PLUMBING CODE (CPC)
• PART 06 - CALIFORNIA ENERGY CODE
• PART 08 - CALIFORNIA HISTORICAL BLDG CODE (CHBC )
• PART 09 - CALIFORNIA FIRE CODE (CFC)
• PART 11 - CALIFORNIA GREEN BLDG STANDARDS CODE
• PART 12 - CALIFORNIA REFERENCED STANDARDS
GENERAL NOTES
1. 1. PROVIDE WORK AND MATERIALS IN ACCORDANCE WITH THE LATEST
RULES AND REGULATIONS OF APPLICABLE STATE AND LOCAL CODES, LAWS, AND STATUTES. NOTHING IN THE CONTRACT DOCUMENTS IS TO
BE CONSTRUED AS REQUIRING OR PERMITTING WORK CONTRARY TO THESE CODES, LAWS, AND STATUTES.
2. EXAMINATION OF THE SITE WHICH WILL AFFECT THIS W ORK SHALL BE
MADE IMMEDIATELY BY THE CONTRACTOR, WHO SHALL COMPARE IT
WITH THE CONTRACT DOCUMENTS AND SATISFY THEMSELVES AS TO CONDITIONS UNDER WHICH WORK IS TO BE PERFORMED. TH EY
SHALL, AT SUCH TIME, CHECK LOCATIONS OF THE EXISTING
STRUCTURES AND EQUIPMENT WHICH MAY AFFECT THEIR WORK. NO
ALLOWANCE SHALL BE MADE FOR ANY EXTRA EXPENSE TO WHICH
THEY MAY BE PUT DUE TO FAILURE OR NEGLECT ON THEIR PART TO MAKE SUCH EXAMINATION. ANY DISCREPANCIES SHALL BE REPORTED TO ARCHITECT BEFORE PROCEEDING WITH ANY WORK.
3. DIMENSIONS ON CONSTRUCTION DRAWINGS ARE TO FACE OF
FRAMING UNLESS OTHERWISE NOTED. CONTRACTOR SHALL NOT
SCALE DRAWINGS. DIMENSIONS NOTED EXISTING (E), ARE TO BE FIELD VERIFIED PRIOR TO LAYING OUT WORK.
4. THE CONSTRUCTION DOCUMENTS ARE PROVIDED TO ILLUS TRATE THE
DESIGN AND GENERAL TYPE OF CONSTRUCTION, MATERIALS, AND WORKMANSHIP THROUGHOUT. THE DOCUMENTS DO NOT ILLUSTRATE EVERY CONDITION. THE CONTRACTOR, IN ASSUMING RESPONSIBILITY
FOR THE WORK INDICATED, SHALL COMPLY WITH THE SPIRI T AS WELL AS THE LETTER IN WHICH THEY WERE PREPARED.
5. WORK LISTED, SHOWN, OR IMPLIED ON ANY CONSTRUCTI ON
DOCUMENT SHALL BE PROVIDED BY THE CONTRACTOR, EXCEPT
WHERE NOTED OTHERWISE. THE GENERAL CONTRACTOR SHAL L
CLOSELY COORDINATE THEIR WORK WITH THAT OF OTHER
CONTRACTORS OR VENDORS AND OWNER TO ASSURE THAT
SCHEDULES ARE MET AND THAT WORK IS DONE IN CONFORMANCE
WITH MANUFACTURERS' REQUIREMENTS.
6. WORK IS ASSUMED NEW UNLESS NOTED AS EXISTING (E) .
7. THE USE OF THE WORD "PROVIDE" IN CONNECTION WITH ANY ITEM
SPECIFIED IS INTENDED TO MEAN THAT SUCH ITEM SHALL BE
FURNISHED, INSTALLED, AND CONNECTED, UNLESS OTHERWISE
NOTED.
8. CONTRACTOR SHALL PROTECT AREA AND NEW OR EXISTIN G
MATERIALS AND FINISHES FROM DAMAGE WHICH MAY OCCUR FROM CONSTRUCTION, DEMOLITION, DUST, WATER, ETC. AND SHALL
PROVIDE AND MAINTAIN TEMPORARY BARRICADES OR ENCLOSURES
AS REQUIRED TO PROTECT THE PUBLIC DURING THE PERIOD OF
CONSTRUCTION. AT NO ADDITIONAL EXPENSE TO THE OWNER, THE
CONTRACTOR SHALL REPAIR OR REPLACE DAMAGE TO NEW AND
EXISTING MATERIALS, FINISHES, STRUCTURES, AND EQUIPMENT TO THE SATISFACTION OF THE OWNER.
9. CONTRACTORS SHALL REMOVE RUBBISH AND WASTE MATER IALS ON A
REGULAR BASIS, AND SHALL EXERCISE STRICT CONTROL OVER JOB
CLEANING TO PREVENT ANY DIRT, DEBRIS, OR DUST FROM AFFECTING,
IN ANY WAY, FINISHED WORK OR EXISTING TO REMAIN WOR K OR CREATING A SAFETY HAZARD IN OR OUTSIDE JOBSITE.
10. CONTRACTOR SHALL LEAVE JOBSITE AND AFFECTED AREAS CLEAN AND IN AN ORDERLY MANNER READY FOR MOVE IN; THIS IS TO
INCLUDE CLEANING THE INTERIOR AND EXTERIOR FACES OF NEW AND EXISTING GLASS.
11. HAZARDOUS MATERIALS ABATEMENT IS NOT PART OF THE
ARCHITECTURAL WORK AND IS THE SOLE RESPONSIBILITY O F THE BUILDING OWNER.
1. THE SCHOLLE FARMHOUSE HAS BEEN DETERMINED ELIGIBLE FOR
LISTING IN THE NATIONAL REGISTER OF HISTORIC PLACES
(NATIONAL REGISTER) AND THE CALIFORNIA REGISTER OF
HISTORICAL RESOURCES (CALIFORNIA REGISTER) AS A HISTORIC DISTRICT.
2. THE SCHOLLE HOUSE IS A QUALIFIED HISTORICAL BUILDING OR
PROPERTY AS DEFINED BY THE CALIFORNIA HISTORICAL
BUILDING CODE (CHBC). THE CHBC ALLOWS FOR SOLUTIONS
THAT ARE REASONABLY EQUIVALENT TO THE REGULAR CODE TO
PROMOTE THE PRESERVATION OF THE HISTORICAL RESOURCE
(8 -101.2 PURPOSE).
3. THE WORK OF THIS PROJECT SHALL COMPLY WITH THE
SECRETARY OF THE INTERIOR ’S STANDARDS FOR
REHABILITATION (SOI STANDARDS) AND ASSOCIATED GUIDELINES FOR REHABILITATING HISTORIC BUILDINGS (SOI GUIDELINES).
4. THE REPORT "SCHOLLE HOUSE HSR" & "SCHOLLE HOUSE
PRESERVATION PLAN ”, PREPARED BY PAGE & TURNBULL AND
DATED OCTOBER 2024, CONTAINS THE FOLLOWING INFORMATION.
1. LISTING OF BUILDINGS AND SITE FEATURES THAT
CONTRIBUTE TO THE HISTORIC DISTRICT.
2. DOCUMENTATION OF HISTORIC MATERIALS, CHARACTER -
DEFINING FEATURES, AND SIGNIFICANT SPACES THAT ARE
TO BE PROTECTED AND PRESERVED AS PART OF THE
PROJECT.
3. GUIDANCE FOR APPLYING THE SOI STANDARDS AND SOI
GUIDELINES TO THE WORK.
HISTORIC PRESERVATION NOTES
ELEVATION
DATUM
NAME
0' - 0"
PROJECT
NORTH
N
(E) WALL
DEMO WALL
PROPOSED
WALL
ALIGN
REVISION
CLOUD
INTERIOR ELEVATION A201
11 1
1 1
1 A3.00
_______________ BUILDING
SECTION
1 A3.00
_______________
SECTION
DETAIL
PROPERTY
LINE
CENTER
LINE
1 A3.00
_______________
EXTERIOR ELEVATION
1 A3.00
_______________
PLAN DETAIL
1 A3.00
_______________ WALL
SECTION
101
ROOM NAME
100 SF
ROOM TAG
GRID LINE
1 A
03.01 KEYNOTE
A
1 WALL TYPE
1 DOOR TAG
1 WINDOW TAG
DETAIL NUMBER
SHEET
SHEET
DETAIL NUMBER
REVISION NUMBER 1
FLOOR DRAIN FD
ROOF DRAIN RD
OVERFLOW
DRAIN
OD
+/-, ± PLUS OR MINUS
' FOOT
" INCH
< LESS THAN
> GREATER THAN
° DEGREES
ABV ABOVE
A.C. ASPHALT CONCRETE
ACC ACCESSIBLE
A.C.P. ACOUSTICAL CEILING PANEL
A.C.T. ACOUSTICAL CEILING TILE
AD AREA DRAIN
A.F.F. ABOVE FINISH FLOOR
AL. ALUMINUM
ANC. ANCHOR
APPROX. APPROXIMATE
ARCH. ARCHITECTURAL
BD. BOARD
BLDG. BUILDING
B.O. BOTTOM OF
BRKT. BRACKET
CAB. CABINET
CEM. CEMENTITIOUS
C.I.P. CAST IN PLACE
C.J. CONTROL JOINT
C.L. CENTERLINE
CLG. CEILING
CLR. CLEAR, CLEARANCE
CLST. CLOSET
CMU. CONCRETE MASONRY UNIT
CNTR. COUNTER
CONC. CONCRETE
CONT. CONTINUOUS
CONTR. CONTRACTOR
CORR. CORRIDOR
CPT. CARPET
CTR. CENTER
CTSK. COUNTERSUNK
DBL. DOUBLE
DEMO. DEMOLISH, DEMOLITION
DET. DETAIL
DIA. DIAMETER
DIAG. DIAGONAL
DIM. DIMENSION
DN. DOWN
D.S. DOWNSPOUT
DWG. DRAWING
(E) EXISTING
EA. EACH
ELEV. ELEVATION
E.O.S. EDGE OF SLAB
EQ. EQUAL
EQUIP. EQUIPMENT
F.A. FIRE ALARM
F.D. FLOOR DRAIN
F.D.C. FIRE DEPARTMENT CONNECTION
FDN. FOUNDATION
F.H.C. FIRE HOSE CABINET
F.H.V. FIRE HOSE VALVE
FIN. FINISH
FIXT. FIXTURE
FLR. FLOOR
F.O. FACE OF
FT. FOOT, FEET
FTG. FOOTING
FUR. FURRING
FURN. FURNITURE
G.B. GRAB BAR
G.C. GENERAL CONTRACTOR
GL. GLASS
GLZ. GLAZING
GND. GROUND
GR. GRADE
G.W.B. GYPSUM WALL BOARD
GYP. GYPSUM
H.M. HOLLOW METAL
H.O. HOLD OPEN
HORZ. HORIZONTAL
HRAIL. HANDRAIL
HTR. HEATER
H.V.A.C. HEATING, VENTILATING AND
AIR CONDITIONING
INCL. INCLUDE,
JAN. JANITOR
JST. JOIST
KIT. KITCHEN
K.P. KICK PLATE
L. LONG, LENGTH
LAM. LAMINATE,
MAT. MATERIAL
MAX. MAXIMUM
MCAB. MEDICINE CABINET
MECH. MECHANICAL
M.E.P. MECHANICAL / ELECTRICAL /
PLUMBING
MEZZ. MEZZANINE
MIN. MINIMUM
MISC. MISCELLANEOUS
M.M.R. MOLD & MOISTURE
RESISTANT
M.O. MASONRY OPENING
MTD. MOUNTED
MTL. METAL
N. NORTH
N/A NOT APPLICABLE
N.I.C. NOT IN CONTRACT
NO. NUMBER
N.R. NON-RATED
N.T.S. NOT TO SCALE
O/ OVER
OFD. OVERFLOW DRAIN
OH. OVERHEAD
OPNG. OPENING
PERF. PERFORATED
PERP. PERPENDICULAR
PL. PROPERTY LINE
PLAS. PLASTER
PLMB. PLUMBING
PLWD. PLYWOOD
PNL. PANEL
PNLG. PANELING
P.O.C. POINT OF CONNECTION
POL. POLISHED
PR. PAIR
PRTR. PRESERVATIVE TREATED
P.T. PRESSURE TREATED
PTD. PAINTED
PTN. PARTITION
QTY. QUANTITY
R. RISER
RAD. RADIUS
R.C.P. REFLECTED CEILING PLAN
R.D. ROOF DRAIN
REF. REFRIGERATOR
REFL. REFLECTED
REQD. REQUIRED
REV. REVISION
RM. ROOM
R.O. ROUGH OPENING
RTD. RATED
RWL RAIN WATER LEADER
S SOUTH
SAN. SANITARY
S.F. SQUARE FOOT
SH. SHELF
SHTG. SHEATHING
SIM. SIMILAR
SEAL. SEALANT
SOF. SOFFIT
S.O.G. SLAB ON GRADE
SPEC. SPECIFICATION
SQ. SQUARE
S.S. STAINLESS STEEL
STD. STANDARD
STOR. STORAGE
STRUCT. STRUCTURAL
SUSP. SUSPENDED
T TREAD
TERR. TERRAZZO
THK. THICK
T.O. TOP OF
TYP. TYPICAL
V.I.F. VERIFY IN FIELD
W. WEST, WIDTH
W/ WITH
W/O WITHOUT
WD. WOOD
WDW. WINDOW
WSCT. WAINSCOT
WT. WEIGHT
CLIENT
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
523 W 6TH ST SUITE 1013,
LOS ANGELES, CA,90014
TEL 916.930.9903
WWW.PAGE-TURNBULL.COM
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
SCHEMATIC DESIGN SET 10.28.2024
As indicated
10/29/2024 12:42:15 PM
Autodesk Docs://24162 Scholle House HSR/2162_ScholleHouse Rehabilitation_R23.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camarillo, CA, 93010
G0.01
COVER SHEET
ND
HM
24162
10.28.2024
SCHEMATIC DESIGN
SCHOLLE HOUSE REHABILITATION
SCHOLLE FARMHOUSE, CAMARILLO, CA, 93010
SHEET LIST
G - GENERAL
G0.01 COVER SHEET
G3.04 AHJ DOCUMENTATION
G4.01 TITLE 24 DOCUMENTATION
G5.01 CAL GREEN DOCUMENTATION
AD - DEMOLITION
AD2.01 FIRST FLOOR DEMOLITION PLAN
AD2.02 REFLECTED CEILING DEMOLITION PLAN
AD2.03 ROOF DEMOLITION AND PROTECTION PLAN
AD3.01 NORTH AND WEST EXTERIOR ELEVATIONS
AD3.02 SOUTH AND EAST EXTERIOR ELEVATIONS
AP2.01 FIRST FLOOR PROTECTION PLAN
A - ARCHITECTURAL
A1.01 SITE PLAN
A2.01 FIRST FLOOR PLAN
A2.02 REFLECTED CEILING PLAN
A2.03 ROOF PLAN AND DETAILS
A3.01 EXTERIOR ELEVATIONS -I
A3.02 EXTERIOR ELEVATIONS- II
A3.11 ENLARGED ELEVATIONS
A3.21 BUILDING SECTIONS
A4.01 ENLARGED KITCHEN FLOOR PLANS AND ELEVATIONS
A4.02 ENLARGED BATHROOM PLANS AND ELEVATIONS
A6.11 DOOR, WINDOW AND FINISH SCHEDULES, TYPES
A7.11 DOOR WINDOW DETAILS
A7.41 EXTERIOR DETAILS - ROOF, SITE AND WALLS
S- STRUCTURAL
SSK-01 FOUNDATION FRAMING PLAN
SSK-02 CEILING FRAMING PLAN
SSK-03 ROOF FRAMING PLAN
M- MECHNICAL
M0.01 MECHANICAL FRONT SHEET
M0.02 MECHANICAL NOTES
M0.03 MECHANICAL SYMBOLS AND ABBREVIATIONS
M0.04 MECHANICAL SCHEDULES
M2.01 MECHNAICAL FIRST FLOOR PLAN
M2.02 MECHANICAL ROOF PLAN
MD2.01 MECHANICAL FIRST FLOOR DEMOLITION PLAN
MD2.02 MECHANICAL ROOF DEMOLITION PLAN
E- ELECTRICAL
E0.01 ELECTRICAL FRONT SHEET
E0.02 ELECTRICAL SINGLE LINE DIAGRAM
E1.01 ELECTRICAL SITE PLAN
E2.01 ELECTRICAL FIRST FLOOR POWER PLAN- MAIN HOUSE
E2.02 ELECTRICAL FIRST FLOOR LIGHTING PLAN- MAIN HOU SE E2.03 ELECTRICAL FIRST FLOOR PLAN- DETACHED GARAGE
E7.01 ELECTRICAL DETAILS
E7.02 ELECTRICAL DETAILS
P- PLUMBING
P0.01 PLUMBING FRONT SHEET
P2.01 PLUMBING FIRST FLOOR WASTE AND GAS PLAN
P2.02 PLUMBING FIRST FLOOR WASTE AND VENT PLAN
P2.03 PLUMBING ROOF PLAN
P7.01 PLUMBING DETAILS
PD2.01 PLUMBING FIRST FLOOR DEMOLITION PLAN
PD2.02 PLUMBING ROOF DEMOLITION PLAN
LOCATION MAP SYMBOLS VICINITY MAP
SCHOLLE
FARMHOUSE
PROJECT SITE
ABBREVIATIONS
(E) WALL TO REMAIN
(E) WALL TO BE DEMOLISHED
(E) DOOR TO BE DEMOLISHED
ROOF OVERHANG
LIVING ROOM
DINING ROOM
HALLWAY
KITCHEN
LAUNDRY/
PANTRY BATH-1
NORTH PORCH
AD3.01
1 AD3.01
2 AD3.02
2 AD3.02
1 E103
E101
E102
S104 S103 S101
W103
W102
W101
N104 N103 N102 N101
E106
E105
E104
E107
E108
E109
102
101
118
108
120
121
107
119
122
BEDROOM - 1
BEDROOM - 2
BEDROOM - 3
1' - 8" 2' - 10" 6' - 10"
REMOVE WINDOW AND
WINDOW FRAME, TYP.
REMOVE DOOR & INT. WALL
PARTIALLY REMOVE WALL TO
ACCOMODATE NEW DOOR
REMOVE CHIMNEY
FROM FIRST FLOOR TO
UNDERSIDE OF ROOF
PROTECT WD WAINSCOATING AND
MOLDINGS, TYP. REFER TO AP2.01
REMOVE (E) DOOR, THE TRANSOM
ABOVE AND DOOR FRAME, TYP.
REMOVE (E) REMAINING GLAZING,
MULLIONS AND STOREFRONT
SYSTEM
REMOVE THE BACK PORCH AND
THE GABLE ROOF WITH WD POSTS
ROOF OVERHANG
REMOVE ALL PLUMBING FIXTURES.
CUT/CAP PIPES, TYP.
REMOVE PARTITION CLOSET
WALL AND BUILT-INS
REMOVE PARTITION
CLOSET WALL AND
BUILT-INS
REMOVE BUILT-IN
CABINETS
REMOVE ELECTRIC PANELS
REMOVE BUILT-IN &
OVERHEAD CABINETS, TYP.
REMOVE SINK AND
PLUMBING FIXTURES.
REMOVE CABINET,
COUNTERTOP AND
BACKSPLASH.
PROTECT WD
WAINSCOATING AND
MOLDINGS, TYP. WHEREVER
EXIST
REMOVE FLOORING DOWN TO
WOOD FLOOR. REVIEW EXISTING
CONDITION WITH ARHCITECT.
REMOVE DOOR AND
DOOR FRAME
REMOVE
CHIMNEY
FROM FIRST
FLOOR TO
UNDERSIDE OF
ROOF
REMOVE PLASTER AND
LATH DOWN TO STUDS
THROUGHOUT, TYP.
112
SIDE PORCH
10' - 2"
REMOVE EXT. WALL
ASSEMBLY AT PORCH
ENCLOSURE
REMOVE FLOORING DOWN TO SHEATIHNG
124
PARTIALLY REMOVE WALL FOR DOOR
OPENING. REFER TO A2.01
SHEET NOTES (DEMOLITION)
1. THIS SHEET SHOWS ONLY (E) CONDITIONS. VERIFY CON DITION OF ALL FRAMING MEMBERS WITH ARCHITECT. REMOVE
DAMAGED MEMBERS AND PROVISIONALLY SHORE AS REQUIRED.
SEE STRUCTURAL DWGS.
2. REFER TO STRUCTURAL DWGS. FOR TEMPORARY SHORING
REQUIRED.
3. REMOVE ALL INTERIOR PLASTER FROM WALLS DOWN TO W OOD FRAMING.
4. ALL WINDOWS TO REMAIN U.N.O. PROTECT SASHES, HEA D,
JAMB, SILL AND FRAME IN PLACE.
5. REMOVE ALL BROKEN GLAZING FROM WINDOWS.
6. REMOVE ALL PLUMBING FIXTURES AND PIPING U.N.O.
7. REMOVE ALL MECHANICAL EQUIPMENT AND DUCTS U.N.O.
8. REMOVE ALL ELECTRICAL EQUIPMENT, SWITCHES, RECEP TICALS AND JUNCTION BOXES ON WALLS AND BASEBOARDS.
9. REMOVE ALL FLOORING MATERIAL DOWN TO FLOOR SHEAT HING.
10. THE SCOPE OF WORK WILL INVOLVE THE REMOVAL AND/ OR
ABATEMENT OF SURFACES THAT MIGHT CONTAIN LEAD. A
HAZARDOUS MATERIAL SURVEY WAS NOT CONDUCTED FOR
THIS PROJECT. THE CONTRACTOR SHALL FURNISH ALL LABOR,
MATERIALS, SERVICES, INSURANCE, EQUIPMENT AND
DECONTAMINATION FACILITIES TO CARRY OUT THE COMPLETE
REMOVAL AND DISPOSAL OF LCS.
CLIENT
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
523 W 6TH ST SUITE 1013,
LOS ANGELES, CA,90014
TEL 916.930.9903
WWW.PAGE-TURNBULL.COM
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
SCHEMATIC DESIGN SET 10.28.2024
As indicated
10/29/2024 12:42:18 PM
Autodesk Docs://24162 Scholle House HSR/2162_ScholleHouse Rehabilitation_R23.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camarillo, CA, 93010
AD2.01
FIRST FLOOR
DEMOLITION PLAN
ND
HM
24162
10.28.2024
SCHEMATIC DESIGN
PLAN LEGEND
N0 2' 4' 8'
SCALE: 1/4" = 1'-0"
1/4" = 1'-0" 1 FIRST FLOOR DEMO PLAN
KEY NOTES
REMOVE LATH & PLASTER
CEILING
REMOVE CEILING, TYP.
REMOVE LATH &
PLASTER CEILING
REMOVE LATH &
PLASTER CEILING
PROTECT INPLACE THE BEADBOARD CEILING @ ROOF EAVES, TYP.
PROTECT FASCIA BOARD IN PLACE, TYP.
REMOVE BEADBOARD CEILING
REMOVE LATH AND
PLASTER CEILING
(E) WALL TO REMAIN
(E) WALL TO BE DEMOLISHED
(E) DOOR TO BE DEMOLISHED
ROOF OVERHANG
CLIENT
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
523 W 6TH ST SUITE 1013,
LOS ANGELES, CA,90014
TEL 916.930.9903
WWW.PAGE-TURNBULL.COM
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
SCHEMATIC DESIGN SET 10.28.2024
As indicated
10/29/2024 12:42:18 PM
Autodesk Docs://24162 Scholle House HSR/2162_ScholleHouse Rehabilitation_R23.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camarillo, CA, 93010
AD2.02
REFLECTED CEILING
DEMOLITION PLAN
ND
HM
24162
10.28.2024
SCHEMATIC DESIGN
N
0 4' 8' 16'
PLAN LEGEND
1/4" = 1'-0" 1 FIRST FLOOR REFLECTED CEILING PLAN
N
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
PLAN LEGEND
KEY NOTES
DEMOLITION REFLECTED CEILING PLAN NOTES
1. ALL (E) CEILING TO BE REMOVED U.N.O.
2. ALL CEILING FIXTURES AND JUNCTION BOXES TO BE REM OVED.
3. THE SCOPE OF WORK WILL INVOLVE THE REMOVAL AND/OR
ABATEMENT OF SURFACES THAT MIGHT CONTAIN LEAD. A
HAZARDOUS MATERIAL SURVEY WAS NOT CONDUCTED FOR THIS
PROJECT. THE CONTRACTOR SHALL FURNISH ALL LABOR,
MATERIALS, SERVICES, INSURANCE, EQUIPMENT AND
DECONTAMINATION FACILITIES TO CARRY OUT THE COMPLETE
REMOVAL AND DISPOSAL OF LCS.
AD3.01
1 AD3.01
2 AD3.02
2 AD3.02
1 REMOVE ROOFING MATERIAL
AND SHEATHING TO WOOD
FRAMING THROUGHOUT
REMOVE THE GABLE ROOF FRAMING,
SHEATHING AND THE ROOF MATERIAL
REMOVE THE EXHAUST
VENT FIXTURE.
EXISTING OPENINGS IN ROOF
AT FORMER CHIMNEY
LOCATION
REMOVE AND REINSTALL THE CORNICE
AND FASCIA BD. STORE IN A SAFE
LOCATION.
ROOF SHEET NOTES (DEMOLITION)
1. THIS SHEET SHOWS ONLY (E) CONDITIONS. VERIFY CON DITION OF ALL FRAMING MEMBERS WITH ARCHITECT. REMOVE
DAMAGED MEMBERS AND PROVISIONALLY SHORE AS REQUIRED.
SEE STRUCTURAL DWGS.
2. REFER TO STRUCTURAL DWGS. FOR TEMPORARY SHORING
REQUIRED.
3. THE SCOPE OF WORK WILL INVOLVE THE REMOVAL AND/O R
ABATEMENT OF SURFACES THAT MIGHT CONTAIN LEAD. A
HAZARDOUS MATERIAL SURVEY WAS NOT CONDUCTED FOR
THIS PROJECT. THE CONTRACTOR SHALL FURNISH ALL LABOR,
MATERIALS, SERVICES, INSURANCE, EQUIPMENT AND
DECONTAMINATION FACILITIES TO CARRY OUT THE COMPLETE
REMOVAL AND DISPOSAL OF LCS.
CLIENT
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
523 W 6TH ST SUITE 1013,
LOS ANGELES, CA,90014
TEL 916.930.9903
WWW.PAGE-TURNBULL.COM
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
SCHEMATIC DESIGN SET 10.28.2024
As indicated
10/29/2024 12:42:19 PM
Autodesk Docs://24162 Scholle House HSR/2162_ScholleHouse Rehabilitation_R23.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camarillo, CA, 93010
AD2.03
ROOF DEMOLITION
AND PROTECTION
PLAN
ND
HM
24162
10.28.2024
SCHEMATIC DESIGN
PLAN LEGEND
N
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
KEY NOTES
1/4" = 1'-0" 1 ROOF LEVEL
FIRST FLOOR LEVEL
96' - 0"
TOP OF WALL
106' - 0"
ROOF LEVEL
116' - 0"
N101 N104
101
REMOVE EXISTING ROOF TO RAFTERS
REMOVE AND REINSTALL THE CORNICE
AND FASCIA BD. STORE IN A SAFE
LOCATION.
PROTECT THE DECORATIVE BRACKETS IN-
PLACE
DEMO THE STOREFRNT
SYSTEM. REMOVE THE
MULLIONS AND GLAZING.
DECORATIVE BALUSTERS
TO REMAIN IN-PLACE
PROTECT THE EXTERIOR WD SIDING.
FIRST FLOOR LEVEL
96' - 0"
TOP OF WALL
106' - 0"
ROOF LEVEL
116' - 0"
W101 W102 W103
REMOVE ROOFING MATERIAL AND SHEATHING
TO WOOD RAFTER
REMOVE AND REINSTALL THE
CORNICE AND FASCIA BD. STORE IN
A SAFE LOCATION.
PROTECT THE DECORATIVE BRACKETS IN-
PLACE
DEMO THE STOREFRONT
SYSTEM. REMOVE THE
MULLIONS AND GLAZING.
DECORATIVE BALUSTERS
TO REMAIN IN-PLACE
REMOVE THE GABLE
ROOF MEMBRANE,
SHEATHING AND THE
STRUCTURE, TYP.
REMOVE THE WD POSTS
EXISTING OPENINGS IN ROOF
AT FORMER CHIMNEY
LOCATION
(E) WALL TO REMAIN
(E) WALL TO BE DEMOLISHED
(E) DOOR TO BE DEMOLISHED
ROOF OVERHANG
1/4" = 1'-0" 2 WEST ELEVATION
CLIENT
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c1 2 3 4
1 2 3 4
A
B
C
523 W 6TH ST SUITE 1013,
LOS ANGELES, CA,90014
TEL 916.930.9903
WWW.PAGE-TURNBULL.COM
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
NOT FOR CONSTRUCTION
ISSUANCE TITLE ISSUANCE DATE
SCHEMATIC DESIGN SET 10.28.2024
As indicated
10/29/2024 12:42:26 PM
Autodesk Docs://24162 Scholle House HSR/2162_ScholleHouse Rehabilitation_R23.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camarillo, CA, 93010
AD3.01
NORTH AND WEST
EXTERIOR
ELEVATIONS
ND
HM
24162
10.28.2024
SCHEMATIC DESIGN
1/4" = 1'-0" 1 NORTH ELEVATION
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
GRAPHICS LEGEND
DEMOLITION NOTES
1. VERIFY CONDIITON OF ALL FRAMING MEMBERS WITH ARH CITECTS. REMOVE DAMAGED MEMEBRS AS REQUIRED. SEE STRUCTURAL DWGS.
2. REFER TO STRUCTURAL DWGS FO RTEMPORARY SHORING R EQUIRED.
3. ALL WINDOWS TO REMAIN U.N.O. SASH, JAMBS, HEAD, TRIMS TO REMAIN IN- PLACE.
4. CAREFULLY REMOVE THE DOORS AND DOOR FRAMES AS ME NTIONED.
5. REMOVE ALL BROKEN GLAZING FROM WINDOWS.
6. REMOVE ALL PLUMBING FIXTURES- CUT/CAP PIPES U.N.O .
7. REMOVE ALL MECHANICAL EQUIPEMENT AND DUCTS U.N.O .
8. REMOVE ALL ELECTRICAL EQUIPEMENTS U.N.O.
9. REMOVE ALL CARPET PATCH AND REPAIR FLOOR SHEATHI NG AND PLANS AS REQD.
10. THE SCOPE OF WORK WILL INVOLVE THE REMOVAL AND ABADEMENT OF SURFACES THAT MIGHT CONTAIN LEAD. HAZARDOUS MATERIAL SURVEY IS NOT CONDUCTED FOR THIS PROJECT. THE CONTRACTOR SHALL FURBISH ALL
LABOR, MATERIALS, SERVICES, INSURANCE, EQUIPEMENT AND
DECONTAMINATION FACLITIES TO CARRY OUT THE COMPLETE REMOVAL AND DISPOSAL OF LCS.
FIRST FLOOR LEVEL
96' - 0"
TOP OF WALL
106' - 0"
ROOF LEVEL
116' - 0"
REMOVE EXISTING ROOFING MATERIAL AND
SHEATHING TO WOOD RAFTER
REMOVE AND REINSTALL THE
CORNICE AND FASCIA BD. STORE
IN A SAFE LOCATION.
REMOVE THE GABLE ROOF
MEMBRANE, SHEATHING AND THE
STRUCTURE
REMOVE THE WD POSTS
PROTECT THE DECORATIVE BRACKETS IN-PLACE
S101 S103 S104
124
EXISTING OPENINGS IN ROOF
AT FORMER CHIMNEY
LOCATION
PROTECT THE EXTERIOR WD SIDING.
REPAIR AS REQD.
FIRST FLOOR LEVEL
96' - 0"
TOP OF WALL
106' - 0"
ROOF LEVEL
116' - 0"
3' - 0"
13' - 0"
23' - 0"
REMOVE WALL ASSEMBLY, DOOR
AND WINDOWS AT PORCH
ENCLOSURE
DEMO THE STOREFRONT
SYSTEM. REMOVE THE
MULLIONS AND GLAZING.
REMOVE ROOFING MATERIAL AND SHEATHING
TO WOOD FRAMING
REMOVE AND REINSTALL THE
CORNICE AND FASCIA BD, TYP.
STORE IN A SAFE LOCATION.
REMOVE THE GABLE
ROOF MEMBRANE,
SHEATHING AND THE
STRUCTURE
REMOVE THE WD POSTS
REMOVE WD WINDOWS
REMOVE DOOR AND
TRANSOM ABOVE
E109 E108 E107
122
E104 E105 E106
PROTECT THE DECORATIVE
BRACKETS IN-PLACE
DECORATIVE BALUSTERS
TO REMAIN IN-PLACE
PROTECT THE
EXTERIOR WD SIDING.
REPAIR AS REQD.
(E) WALL TO REMAIN
(E) WALL TO BE DEMOLISHED
(E) DOOR TO BE DEMOLISHED
ROOF OVERHANG
CLIENT
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c1 2 3 4
1 2 3 4
A
B
C
523 W 6TH ST SUITE 1013,
LOS ANGELES, CA,90014
TEL 916.930.9903
WWW.PAGE-TURNBULL.COM
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
NOT FOR CONSTRUCTION
ISSUANCE TITLE ISSUANCE DATE
SCHEMATIC DESIGN SET 10.28.2024
As indicated
10/29/2024 12:42:30 PM
Autodesk Docs://24162 Scholle House HSR/2162_ScholleHouse Rehabilitation_R23.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camarillo, CA, 93010
AD3.02
SOUTH AND EAST
EXTERIOR
ELEVATIONS
ND
HM
24162
10.28.2024
SCHEMATIC DESIGN
1/4" = 1'-0" 1 SOUTH ELEVATION
1/4" = 1'-0" 2 EAST ELEVATION
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
SHEET NOTES
1. AS-BUILD DRAWING MEASUREMENTS WERE TAKEN
IN FIELD ON SITE VISIT (07/09/2024).
2. CONTRACTOR SHOULD CONFIRM ALL
MEASUREMENTS PRIOR TO CONSTRUCTION.
3. THE HOUSE CURRENTLY SITS ON CRIBBING.
GRAPHICS LEGEND
DEMOLITION NOTES
1. VERIFY CONDIITON OF ALL FRAMING MEMBERS WITH ARH CITECTS. REMOVE DAMAGED MEMEBRS AS REQUIRED. SEE STRUCTURAL DWGS.
2. REFER TO STRUCTURAL DWGS FO RTEMPORARY SHORING R EQUIRED.
3. ALL WINDOWS TO REMAIN U.N.O. SASH, JAMBS, HEAD, TRIMS TO REMAIN IN- PLACE.
4. CAREFULLY REMOVE THE DOORS AND DOOR FRAMES AS ME NTIONED.
5. REMOVE ALL BROKEN GLAZING FROM WINDOWS.
6. REMOVE ALL PLUMBING FIXTURES- CUT/CAP PIPES U.N.O .
7. REMOVE ALL MECHANICAL EQUIPEMENT AND DUCTS U.N.O .
8. REMOVE ALL ELECTRICAL EQUIPEMENTS U.N.O.
9. REMOVE ALL CARPET PATCH AND REPAIR FLOOR SHEATHI NG AND PLANS AS REQD.
10. THE SCOPE OF WORK WILL INVOLVE THE REMOVAL AND ABADEMENT OF SURFACES THAT MIGHT CONTAIN LEAD. HAZARDOUS MATERIAL SURVEY IS NOT CONDUCTED FOR THIS PROJECT. THE CONTRACTOR SHALL FURBISH ALL
LABOR, MATERIALS, SERVICES, INSURANCE, EQUIPEMENT AND
DECONTAMINATION FACLITIES TO CARRY OUT THE COMPLETE REMOVAL AND DISPOSAL OF LCS.
LIVING ROOM
DINING ROOM
HALLWAY
KITCHEN
LAUNDRY/
PANTRY BATH-1
NORTH PORCH
E103
E101
E102
S104 S103 S101
W103
W102
W101
N104 N103 N102 N101
E106
E105
E104
E107
E108
E109
102
101
118
108
120
121
107
119
122
BEDROOM - 1
BEDROOM - 2
BEDROOM - 3
112
REMOVE (E) BEADBOARD
WAINSCOATING
1 4
3 2
REMOVE (E) WD
SKIRTBOARD
REMOVE (E) BEADBOARD
WAINSCOATING
ROOF OVERHANG
1- (E) BEADBOARD WAINSCOATING TO
REMAIN-PLACE
1- REMOVE (E) BEADBOARD
WAINSCOATING
2 - (E) SKIRT BOARD TO REMAIN IN-
PLACE
2- REMOVE (E) SKIRT-BOARD
3 - WD WINDOW TRIMS TO REMAIN IN-
PLACE
4 - DOOR TRIMS TO REMAIN IN-PLACE
WAINSCOATING
SKIRTBOARD
INTERIOR EXTERIOR
SILL
HEAD
SASH
DOOR TRIM
AND CASING
CLIENT
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
523 W 6TH ST SUITE 1013,
LOS ANGELES, CA,90014
TEL 916.930.9903
WWW.PAGE-TURNBULL.COM
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
SCHEMATIC DESIGN SET 10.28.2024
As indicated
10/29/2024 12:42:34 PM
Autodesk Docs://24162 Scholle House HSR/2162_ScholleHouse Rehabilitation_R23.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camarillo, CA, 93010
AP2.01
FIRST FLOOR
PROTECTION PLAN
ND
HM
24162
10.28.2024
SCHEMATIC DESIGN
PLAN LEGEND
N0 2' 4' 8'
SCALE: 1/4" = 1'-0"
1/4" = 1'-0" 1 FIRST FLOOR PROTECTION PLAN
TEMPORARY PROTECTION
PLAN NOTES
GENERAL:
1. IN GENERAL, THE HISTORIC MATERIALS AND CHARACTER-DEFINING
FEATURES WITHIN THE AREAS OF WORK AND THROUGHOUT THE CAMPUS
SHALL BE PROTECTED IN PLACE DURING CONSTRUCTION OR-
REMOVED,STORED, AND REINSTALLED FOLLOWING THE INSTALLATION OF NEW SYSTEMS.
2. THE PURPOSE OF TEMPORARY PROTECTION MEASURES IS TO PREVENT AND AVOID DAMAGE TO HISTORIC STRUCTURES, ARTIFACTS, AND MATERIALS.
TEMPORARY PROTECTION MEASURES SHALL BE INSTALLED RIOR TO
CONSTRUCTION AND REMOVED AFTER CONSTRUCTION HAS BEEN
COMPLETED.PROTECT IN PLACE
• ACCEPTABLE PROTECTION MATERIALS INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING.
a. PLYWOOD: PLYWOOD CONFORMING THE REQUIREMENTS OF US
DEPARTMENT OF COMMERCE PRODUCT STANDARDS PS 1-19; CLEAN AND FREE OF MOLD, ALGAE, MILDEW, OR OTHER BIOLOGICAL GROWTH. b. DIMENSIONAL LUMBER: NOMINAL 2X, NOMINAL 1X1 NAILERS, FIRE- RETARDANT-TREATED; CLEAN AND FREE OF MOLD, ALGAE, MIL-DEW, OR OTHER BIOLOGICAL GROWTH.
c. BUILDING PAPER: NON-ASPHALTIC ROSIN PAPER, FABRIC OR EQUAL, COMPATIBLE WITH FLOORING, WALL, OR CASEWORK SURFACE.
d. POLYETHYLENE SHEET: REINFORCED, FIRE-RESISTIVE SHEET, 10-MIL MINIMUM THICKNESS, WITH FLAME-SPREAD RATING OF 15 OR LESS IN ACCORDANCE WITH ASTM E84 AND PASSING NFPA 701 TEST METHOD 2. e. NEOPRENE PADS, NON-STAINING, MINIMUM THICKNESS 1/4”. f. FOAM WRAP: ACID-FREE, LOW-DENSITY POLYETHYLENE CLOSED- CELL FOAM.
g. FOAM SANDWICH BOARD: POLYSTYRENE FOAM SANDWICHED
BETWEEN VARIOUS LINERS,
IN ACID-FREE FORM: FOME-COR, INTERNA-TIONALPAPER CO OR EQUAL. h. POLYESTER FILM: MYLAR D, E.I. DUPONT DE NEMOURS CO OR EQUAL. i. FIBERBOARD: FIRE-TREATED, UNFACED PANELS, 1/2”THICK.
ACCEPTABLE PRODUCT: HOMASOTE NFCR OR EQUAL.
j. FASTENERS: WOOD SCREWS, TYPE 302 STAINLESS STEEL
k. DUST-CONTROL ADHESIVE-SURFACE WALK-OFF MATS: PROVIDE MATS, MINIMUM 36 BY 60 INCHES.
• SUBMIT A WRITTEN, DETAILED DESCRIPTION OF MATERIALS, METHODS,
EQUIPMENT, AND SEQUENCE OF OPERATIONS TO BE USED FOR
PROTECTION OF HISTORIC MATERIALS AND FEATURES TO REMAIN PROTECTED IN PLACE.
a. INCLUDE PRODUCT DATA INFORMATION FOR MATERIALS USED IN PROTECTING, PACKAGING, AND CRATING ITEMS.
• EXTERIOR & SITE
a. CARE SHALL BE TAKEN TO AVOID DAMAGE TO EXTERIOR WALLS,
DOORS, WINDOWS, AND GLAZING, TRIM, CANOPIES, FIXTURES, AND
DECORATIVE ELEMENTS ON EXTERIOR WALLS AND IN HISTORIC
LANDCAPED AREAS.
b. PROTECT ITEMS IN HIGH TRAFFIC AREAS AND ADJACENT TO
WHERE DEMOLITION WORK IS OCCURING.
c. PROTECT CONCRETE PAVING, WALKWAYS, CURBS AND STEPS,
AND CANOPIES AND WALKWAY COVERINGS AROUND
CONTRIBUTING HISTORIC BUILDINGS AND ASSOCIATED
HISTORIC LANDSCAPED AREAS.
d. SEE XXXX FOR THE EXISTING TREE AND PLANTING PROTECTION. e. PROTECT -OR-REMOVE AND REINSTALL EXTERIOR DOORS AT
HISTORIC BUILDINGS AS APPROPRIATE.
f. PROTECT ANY (E) GLAZING USING PLYWOOD PRIOR TO
REHABILITATION. FOLLOWING WORK, REMOVE PLYWOOD AND
REVIEW WINDOW CONDITIONS WITH ARCHITECT. PATCH
ANY HOLES FROM PLYWOOD INSTALLATION.
• INTERIOR
a. PROTECT ORIGINAL BUILT-IN BOOKCASES, CABINETS, AND
CASEWORK TO LIMIT DAMAGE DURING CONSTRUCTION.
b. MAKE SURE ANY DOORS ARE IN THE LOCKED POSITION.
c. SECURE ANY DRAWERS IN THE CLOSED POSITION.
d. WRAP CASEWORK IN QUILTED PADDING, PROPERLY SECURING
PADDING. DO NOT DAMAGE WOOD SURFACES.
1- BEADBOARD WAINSCOATING
2- SKIRTBOARD
3- WINDOW
4- DOORS
UP
UP
UP
ADJACENT HOUSING DEVELOPMENT
SCEHEME (NOT IN SCOPE)
ADJACENT HOUSING
DEVELOPMENT SCEHEME
(NOT IN SCOPE)
ADJACENT HOUSING
DEVELOPMENT SCEHEME
(NOT IN SCOPE)
PROPERTY LINE
CONCRETE PATHWAY. SEE
CIVIL DWGS
SIDWALK
PROPERTY LINE
PROPERTY LINE
PROPERTY LINE
20' - 7"
5' - 0"
45' - 5"
16' - 0"
5' - 4"
92' - 2"
32' - 9"
49' - 7"
29' - 3"
SCHOLLE HOUSE RELOCTAED
TO THE CURRENT LOCATION
ON SITE.
FINISH FACE OF THE
BUILDING
W PONDEROSA DRIVE AT SPRINGVILLE DRIVE
GRAVEL PATHWAY TO THE
HOUSE
GARAGE
DOUBLE CAR PARKING
DOUBLE CAR
DRIVEWAY,
CONCRETE.
5' - 8"
4' - 0"
CLIENT
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
523 W 6TH ST SUITE 1013,
LOS ANGELES, CA,90014
TEL 916.930.9903
WWW.PAGE-TURNBULL.COM
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
SCHEMATIC DESIGN SET 10.28.2024
1" = 10'-0"
10/29/2024 12:42:35 PM
Autodesk Docs://24162 Scholle House HSR/2162_ScholleHouse Rehabilitation_R23.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camarillo, CA, 93010
A1.01
SITE PLAN
ND
HM
24162
10.28.2024
SCHEMATIC DESIGN
KEY NOTES
N
0 4' 8' 16'
SCALE: 1' = 10'-0" 1" = 10'-0" 1 SITE PLAN
SITE PLAN NOTES
1. ALL DIMENSIONS TO BE FIELD VERIFIED. BRING ANY
DISCRIPENCIES TO THE ARHCITECT'S ATTENTION.
2. LANDSCAPE DESIGN IS NOT UNDER P&T SCOPE.
3. SEE CIVIL DWGS FOR ADDITIONAL UTILITIES AND SITE
INFORMATION.
UP
UP
UP
SHEET NOTES (PLANS)
1. PLACE SHEET NOTE TEXT HERE
A3.01
2 A3.02
2 A3.02
1 A3.01
1 NORTH PORCH
42' - 2"
38' - 5"
REF
W
D
KITCHEN
LAUNDRY/
PANTRY BATH-1
BEDROOM- 1
DINING ROOM
OFFICE/
BEDROOM -3
BEDROOM-2
CABINET CL
CL
CL
CL
CL
BUILT-IN
CABINET
HALLWAY
2 A3.21
_______________
2 A3.21
_______________
1 A3.21
_______________ 1
A3.21
_______________
9' - 6" 11' - 9" 5' - 0" 10' - 4"
16' - 3" 10' - 5"
5' - 5"
9' - 7" 10' - 2"
5' - 2" 2' - 2" 4' - 3" 2' - 2"
N101 N102 N103 N104
E106
E105
E104
E103
E102
E101
S104 S103 S101
W103
W102
W101
101
102
105
109 110
111
112
114
110
104
107
103
LIVING ROOM
MEDIA WALL
________
A4.01
1 ________
A4.02
2 ________
A4.02
1 ALIGN
HARDWOOD FLOORING HARDWOOD FLOORING
HARDWOOD FLOORING
HARDWOOD FLOORING
HARDWOOD FLOORING
WOOD DECK
WOOD DECK
ROOF OVERHANG
WD POSTS, PAINTED.
4' - 7" 4' - 7" 4' - 8"
5' - 0" 9' - 6"
WD RAILING, PAINTED.
2' - 10" 10' - 2"
WD STAIRS, PAINTED
EAST PORCH
CL
CL
126
127
116
130
DW TC
WF
CONCRETE STEPS
WD RAILING, PAINTED, TYP.
133
117
ACCESS
HATCH
ABOVE
2' - 10" 10"
1' - 11"
2' - 10"
2' - 7"
WATER HEATER
17' - 0" 8' - 1" 17' - 0"
5' - 8"
11' - 4"
8' - 6"
8' - 10"
2' - 0"
2' - 0" 4' - 7"
2' - 5"
139
(E) WALL TO REMAIN
WALL TO BE CONSTRUCTED
CLIENT
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c1 2 3 4
1 2 3 4
A
B
C
523 W 6TH ST SUITE 1013,
LOS ANGELES, CA,90014
TEL 916.930.9903
WWW.PAGE-TURNBULL.COM
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
NOT FOR CONSTRUCTION
ISSUANCE TITLE ISSUANCE DATE
SCHEMATIC DESIGN SET 10.28.2024
As indicated
10/29/2024 12:42:37 PM
Autodesk Docs://24162 Scholle House HSR/2162_ScholleHouse Rehabilitation_R23.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camarillo, CA, 93010
A2.01
FIRST FLOOR PLAN
ND
HM
24162
10.28.2024
SCHEMATIC DESIGN
N
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
PLAN LEGEND
KEY NOTES
1/4" = 1'-0" 1 FIRST LEVEL FLOOR PLAN
2 A3.21
_______________
2 A3.21
_______________
1 A3.21
_______________ 1
A3.21
_______________
REFURBISH (E) BRACKET, PAINT., TYP.
106' - 0"
106' - 0" 106' - 0"
106' - 0"
106' - 0"
106' - 0"
106' - 0"
(E) BEADBOARD CEILING, REPIR AS
NEEDED. PAINTED
BEADBOARD CEILING,
TYP. PAINTED
GYP. BOARD CEILING, TYP.
PROTECT IN-PLACE BEADBOARD
CEILING AT ROOF EAVES, PAINTED.
REPAIR AS NEEDED.
LIVING ROOM DINING ROOM BEDROOM- 1
NORTH PORCH
BATH-2 WALKIN CL
BEDROOM-2 KITCHEN HALLWAY
LAUNDRY/
PANTRY BATH-1
OFFICE/
BEDROOM -3
ACCESS
HATCH
SHEET NOTES (PLANS)
1. PLACE SHEET NOTE TEXT HERE
(E) WALL TO REMAIN
WALL TO BE CONSTRUCTED
CEILING MOUNTED FIXTURE
PENDANTS
RECESSED LIGHT FIXTURES
WALL SCONCE (EXTERIOR/
INTERIOR)
UNDERCABINET LED
CLIENT
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
523 W 6TH ST SUITE 1013,
LOS ANGELES, CA,90014
TEL 916.930.9903
WWW.PAGE-TURNBULL.COM
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
SCHEMATIC DESIGN SET 10.28.2024
As indicated
10/29/2024 12:42:42 PM
Autodesk Docs://24162 Scholle House HSR/2162_ScholleHouse Rehabilitation_R23.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camarillo, CA, 93010
A2.02
REFLECTED CEILING
PLAN
ND
HM
24162
10.28.2024
SCHEMATIC DESIGN
N
0 4' 8' 16'
SCALE: 1/8" = 1'-0"
PLAN LEGEND
1/4" = 1'-0" 1 GROUND LEVEL REFLECTED CEILING PLAN
N
0 4' 8' 16'
SCALE: 1/8" = 1'-0"
PLAN LEGEND
KEY NOTES
UP
UP
UP
SHEET NOTES (PLANS)
1. PLACE SHEET NOTE TEXT HERE
2 A3.21
_______________
2 A3.21
_______________
1 A3.21
_______________ 1
A3.21
_______________
FINISH FACE OF THE BUILDING
5" GUTTER, MTL, TYP.
NEW ASPHALT ROOF SHINGLES, TYP.
5" RWL, TYP.
FLAT
RIDGE
VALL
EY VALL
EY
RIDGE
RIDGE
RIDGE
RIDG
E
CLIENT
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
523 W 6TH ST SUITE 1013,
LOS ANGELES, CA,90014
TEL 916.930.9903
WWW.PAGE-TURNBULL.COM
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
SCHEMATIC DESIGN SET 10.28.2024
As indicated
10/29/2024 12:42:43 PM
Autodesk Docs://24162 Scholle House HSR/2162_ScholleHouse Rehabilitation_R23.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camarillo, CA, 93010
A2.03
ROOF PLAN AND
DETAILS
ND
HM
24162
10.28.2024
SCHEMATIC DESIGN
N
0 4' 8' 16'
SCALE: 1/8" = 1'-0"
PLAN LEGEND
KEY NOTES
1/4" = 1'-0" 1 ROOF LEVEL PLAN
FIRST FLOOR LEVEL
96' - 0"
TOP OF WALL
106' - 0"
ROOF LEVEL
116' - 0"
2 A3.21
_______________
2 A3.21
_______________
N101 N102 N103 N104 101
GRADE LEVEL
91' - 6"
ASPHALT SHINGLE ROOF
(E) DECORATIVE
BRACKETS. REPAIR AS
REQD. PAINT. TYP.
REPAIR AND PATCH WOOD
SIDING AS REQD ACC TO SPECS.
SPECIES, PROFILES, AND SIZE
TO MATCH (E)
CONC. FOUNDATION WALL, WITH
PAINTED PLASTER.
WD LOUVERED
WNDW. PAINTED.
(E) EXT. SIDING. REPAIR AS
REQD. PAINTED
CONC. STOOP.
WITH PAINTED
PLASTER.
WD RAILING, PAINTED.
(E) DECORATIVE BALUSTERS,
REPAIR AS REQD. PAINTED.
(E) COLUMNS WOOD.
REPAIR AS REQD.
PAINTED
(E) WD TRIM. REPAIR
AND REPAINT.
WD RAILINGS, PAINTED.
WD STRINGER, PAINTED.
DECORATIVE CORNICE
BEHIND GUTTER, PAINTED.
REPAIR (E) ENTABLATURE
AS REQD. PAINTED
REPAIR THE CORNER
BOARD BEHIND LEADER AS
REQD. PAINTED, TYP.
6' - 2" 8' - 1" 6' - 3"
5" ROUND GUTTER. METAL, TYP.
5" DIA RWL, METAL, TYP.
SHEET NOTES (ELEVATIONS)
1. SCHOLLE HOUSE CURRENTLY SITS ON ITS CORRECT LOCATION ON THE SITE. THE FIRST FLOOR FINISH LEVEL WILL BE
COORDINATED WITH THE CIVIL DRAWINGS BEFORE
CONSTRUCTION.
2. ALL EXISTING DIMENSIONS TO BE FIELD VERIFIED. BRING ANY DISCRIPENCY TO THE ARHCITECTS ATTENTION.
3. ALL EXTERIOR SIDING TO REMAIN U.N.O. REPAIR AS REQUIRED.
PATCH AND REPLACE MISSING ANF HEAVILY DAMAGED MEMBERS
AS PER SPECIFICATION SECTION XX.XXX
4. ALL EXTERIOR WALLS TO BE PAINTED, TYP.
5. REPAIR/ RESTORE ALL THE WINDOWS AS NEEDED. SILL, JAMBS AND HEAD TO REMAIN U.N.O.
6. REPAIR (E) WOOD TRIM. PAINT.
7. REPAIR ALL THE ROOF EAVES AS REQD. REPLACE DAMGED
MEMEBERS TO MATCH (E) PAINT.
FIRST FLOOR LEVEL
96' - 0"
TOP OF WALL
106' - 0"
ROOF LEVEL
116' - 0"
1 A3.21
_______________
1 A3.21
_______________
W101 W102 W103
GRADE LEVEL
91' - 6"
CONC. STOOP, PAINTED
PLASTER
WD RAILINGS, PAINTED.
CONC. FOUNDATION
ASPHALT SHINGLE ROOF
REPAIR AND PATCH WOOD
SIDING AS REQD ACC TO SPECS.
SPECIES, PROFILES, AND SIZE
TO MATCH (E)
(E) COLUMNS WOOD. REPAIR
AS REQD. PAINTED
REPAIR (E) ENTABLATURE
AS REQD. PAINTED
(E) DECORATIVE BALUSTERS,
REPAIR AS REQD. PAINTED.
(E) DECORATIVE BRACKETS.
REPAIR AS REQD. PAINT. TYP.
DECORATIVE CORNICE
BEHIND GUTTER, PAINTED. REPAIR THE CORNER BOARD AS
REQD. PAINTED, TYP.
5" GUTTERS. METAL, TYP.
5' - 2" 16' - 6"
4"
5" RWL, MTL, TYP.
1/4" = 1'-0" 1 WEST ELEVATION
TITLE
ISSUE
SEAL & SIGNATURE
ISSUE DATE
PAGE & TURNBULL, INC. 2021 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
NOT FOR CONSTRUCTION
CLIENT
CONSULTANT
ARCHITECT
PROJECT
417 SOUTH HILL STREET, SUITE 211
LOS ANGELES, CA 90013
TEL 213.221.1200
WWW.PAGE-TURNBULL.COM
As indicated
10/29/2024 12:42:45 PM
Autodesk Docs://24162 Scholle House HSR/2162_ScholleHouse Rehabilitation_R23.rvt
EXTERIOR
ELEVATIONS -I
ND
HM
24162
10.28.2024
SCHEMATIC
DESIGN
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camarillo, CA, 93010
A3.01
1/4" = 1'-0" 2 NORTH ELEVATION
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
KEY NOTES
SHEET NOTES (ELEVATIONS)
1. SCHOLLE HOUSE CURRENTLY SITS ON ITS CORRECT LOCATION ON THE SITE. THE FIRST FLOOR FINISH LEVEL WILL BE
COORDINATED WITH THE CIVIL DRAWINGS BEFORE
CONSTRUCTION.
2. ALL EXISTING DIMENSIONS TO BE FIELD VERIFIED. BRING ANY DISCRIPENCY TO THE ARHCITECTS ATTENTION.
3. ALL EXTERIOR SIDING TO REMAIN U.N.O. REPAIR AS REQUIRED.
PATCH AND REPLACE MISSING ANF HEAVILY DAMAGED MEMBERS
AS PER SPECIFICATION SECTION XX.XXX
4. ALL EXTERIOR WALLS TO BE PAINTED, TYP.
5. REPAIR/ RESTORE ALL THE WINDOWS AS NEEDED. SILL, JAMBS AND HEAD TO REMAIN U.N.O.
6. REPAIR (E) WOOD TRIM. PAINT.
7. REPAIR ALL THE ROOF EAVES AS REQD. REPLACE DAMGED
MEMEBERS TO MATCH (E) PAINT.
FIRST FLOOR LEVEL
96' - 0"
TOP OF WALL
106' - 0"
ROOF LEVEL
116' - 0"
S101 S103 S104
GRADE LEVEL
91' - 6"
ASPHALT SHINGLE ROOF
(E) DECORATIVE BRACKETS.
REPAIR AS REQD. PAINT. TYP.
REPAIR AND PATCH WOOD
SIDING AS REQD ACC TO SPECS.
SPECIES, PROFILES, AND SIZE
TO MATCH (E)
CONC. FOUNDATION
WALLS WITH PAINTED
PLASTER.
WD RAILINGS, PAINTED.
DECORATIVE CORNICE BEHING GUTTERS, PAINTED.
WD COLUMNS, PAINTED.
REPAIR THE CORNER
BOARD AS REQD.
PAINTED, TYP.
WD STAIRS, PAINTED.
5" GUTTERS METAL, TYP.
124
5" RWL, METAL, TYP.
FIRST FLOOR LEVEL
96' - 0"
TOP OF WALL
106' - 0"
ROOF LEVEL
116' - 0"
1 A3.21
_______________
1 A3.21
_______________
E104 E105 E106
E101 E102 E103
107
GRADE LEVEL
91' - 6"
REPAIR THE CORNER
BOARD BEHIND THE
GUTTER. PAINTED, TYP.
ASPHALT SHINGLE ROOF
(E) DECORATIVE BRACKETS.
REPAIR AS REQD. PAINT. TYP.
REPAIR AND PATCH WOOD
SIDING AS REQD ACC TO SPECS.
SPECIES, PROFILES, AND SIZE
TO MATCH (E)
CONC. FOUNDATION
WALLS WITH
PAINTED PLASTER.
DECORATIVE CORNICE BEHIND GUTTER, PAINTED.
WD POSTS, PAINTED.
WD STAIRS, PAINTED.
CONC. STOOP, WITH PAINTED PLASTER
REPAIR (E) ENTABLATURE AS REQD.
PAINTED
(E) WOOD COLUMNS. REPAIR AS
REQD. PAINTED
5" ROUND GUTTERS. METAL, TYP.
CLIENT
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
523 W 6TH ST SUITE 1013,
LOS ANGELES, CA,90014
TEL 916.930.9903
WWW.PAGE-TURNBULL.COM
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
SCHEMATIC DESIGN SET 10.28.2024
As indicated
10/29/2024 12:42:46 PM
Autodesk Docs://24162 Scholle House HSR/2162_ScholleHouse Rehabilitation_R23.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camarillo, CA, 93010
A3.02
EXTERIOR
ELEVATIONS- II
ND
HM
24162
10.28.2024
SCHEMATIC DESIGN
1/4" = 1'-0" 1 SOUTH ELEVATION
0 4' 8' 16'
SCALE: 1/8" = 1'-0"
KEY NOTES
1/4" = 1'-0" 2 EAST ELEVATION
SHEET NOTES (SECTIONS)
1. PLACE SHEET NOTE TEXT HERE
FIRST FLOOR LEVEL
96' - 0"
TOP OF WALL
106' - 0"
ROOF LEVEL
116' - 0"
1 A3.21
_______________
1 A3.21
_______________
GRADE LEVEL
91' - 6"
254 SF
LIVING ROOM
112 SF
HALLWAY
111 SF
NORTH PORCH
103 116 114
5" RWL, MTL, TYP.
5" ROUND GUTTER, MTL, TYP.
CONC.
STAIRS
WD RIALINGS,
PAINTED, TYP.
GYP BD, CEILING, PAINTED, TYP.
REPAIR, PATCH AND REPAINT (E) BEADBOARD CEILING AT ROOF EAVES, TYP.
REPAIR (E) ROOF RAFTERS AS
REQD. SEE STRUCTURAL DWGS,
TYP.
ASPHALT ROOF SHINGLES, TYP.
SHEATHING FOR ADDITIONAL SUPPORT,
SEE STRUCTURAL DWGS, TYP.
WD STAIRS, PAINTED, TYP.
FIRST FLOOR LEVEL
96' - 0"
TOP OF WALL
106' - 0"
ROOF LEVEL
116' - 0"
2 A3.21
_______________
2 A3.21
_______________
178 SF
BEDROOM-2
112 SF
HALLWAY
GRADE LEVEL
91' - 6"
199 SF
KITCHEN
109 110 105 104
5" RWL, MTL, TYP.
BEADBOARD CEILING AT THE SIDE PORCH
68 SF
SIDE PORCH
REPAIR ROOF RAFTER AS NEEDED,
SEE STRUCTURAL DWGS, TYP.
SHEATHING FOR ADDITIONAL SUPPORT,
SEE STRUCTURAL DWGS, TYP.
FOUNDATION
WALL, CONC,
PAINTED, TYP.
WD RAILING, PAINTED, TYP.
WD STAIRS, PAINTED, TYP.
INFILL OPENING WITH WOOD SIDING AS REQD ACC TO
SPECS. SPECIES, PROFILES, AND SIZE TO MATCH (E)
5" GUTTER, MTL, TYP.
ASPHALT SHINGLE ROOF MEMBRANE
CLIENT
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
523 W 6TH ST SUITE 1013,
LOS ANGELES, CA,90014
TEL 916.930.9903
WWW.PAGE-TURNBULL.COM
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
SCHEMATIC DESIGN SET 10.28.2024
As indicated
10/29/2024 12:42:47 PM
Autodesk Docs://24162 Scholle House HSR/2162_ScholleHouse Rehabilitation_R23.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camarillo, CA, 93010
A3.21
BUILDING SECTIONS
ND
HM
24162
10.28.2024
SCHEMATIC DESIGN
KEY NOTES
0 4' 8' 16'
SCALE: 1/8" = 1'-0"
1/4" = 1'-0" 2 SECTION THROUGH HALLWAY LOOKING EAST
1/4" = 1'-0" 1 SECTION THROUGH KITCHEN LOOKING NORTH
GENERAL NOTES
1. PRIOR TO SUBMITTING BID, MECHANICAL CONTRACTOR SHALL
BECOME FULLY ACQUAINTED WITH THE CONDITIONS OF THE
PROJECT. REVIEW THE GENERAL NOTES, SPECIFICATIONS AND
OTHER DRAWINGS FOR ADDITIONAL REQUIREMENTS WHICH MAY
NOT BE SPECIFICALLY CALLED OUT IN THIS PORTION OF THE
CONSTRUCTION DOCUMENTS. NOTIFY ARCHITECT, ENGINEER
AND/OR OWNER OF CONFLICTS OR DISCREPANCIES PRIOR TO
SUBMISSION OF BID.
2. COORDINATE THE INSTALLATION OF THE MECHANICAL SYSTEMS
WITH OTHER TRADES TO ENSURE A NEAT AND ORDERLY
INSTALLATION. INSTALL DUCTWORK AS TIGHT TO STRUCTURE AS POSSIBLE. COORDINATE WITH OTHER TRADES TO AVOID
CONFLICTS. COORDINATE INSTALLATION OF DUCTWORK TO
AVOID CONFLICTS WITH ELECTRICAL PANELS, LIGHTING
FIXTURES, ETC. ANY MODIFICATIONS REQUIRED DUE TO LACK OF
COORDINATION WILL BE THE RESPONSIBILITY OF THE
MECHANICAL CONTRACTOR AT NO EXTRA COST TO THE OWNER.
3. AVOID DAMAGING SURFACES AND EQUIPMENT DURING WORK.
REPAIR DAMAGE CAUSED DURING CONSTRUCTION AT NO EXTRA
COST TO THE OWNER.
4. ALL MECHANICAL EQUIPMENT SHOWN ON THE MECHANICAL
PLANS SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR
UNLESS OTHERWISE NOTED. TEMPERATURE SENSORS, HUMIDITY
SENSORS AND CARBON DIOXIDE SENSORS SHALL BE FURNISHED
BY THE OWNER AND INSTALLED BY BMS CONTRACTOR, UNLESS
NOTED OTHERWISE ON DRAWINGS. THERMOSTATS SHALL BE
PROVIDED AND INSTALLED BY THE MECHANICAL CONTRACTOR.
5. MECHANICAL EQUIPMENT AND DUCTWORK ARE SHOWN AT
APPROXIMATE LOCATIONS. FIELD MEASURE FINAL DUCTWORK
LOCATIONS PRIOR TO FABRICATION AND MAKE ADJUSTMENTS AS
REQUIRED TO FIT THE DUCTWORK WITHIN THE AVAILABLE
SPACE. VERIFY THAT FINAL EQUIPMENT LOCATIONS MEET
MANUFACTURER'S RECOMMENDATIONS REGARDING SERVICE
CLEARANCE AND PROPER AIRFLOW CLEARANCE AROUND
EQUIPMENT.
6. INDOOR AIR QUALITY MEASURES: PROTECT INSIDE OF
(INSTALLED AND DELIVERED) DUCTWORK AND HVAC UNITS FROM
EXPOSURE TO DUST, DIRT, PAINT AND MOISTURE. REPLACE
INSULATION THAT HAS GOTTEN WET AT ANY TIME DURING
CONSTRUCTION, DRYING THE INSULATION IS NOT ACCEPTABLE.
SEAL ANY TEARS OR JOINTS OF INTERNAL FIBERGLASS
INSULATION. REMOVE DEBRIS FROM CEILING/RETURN AIR
PLENUM INCLUDING DUST. AN INDEPENDENT, PROFESSIONAL
DUCT CLEANING COMPANY SHALL VACUUM CLEAN ANY
DUCTWORK CONNECTED TO HVAC UNITS THAT WERE OPERATED
DURING THE CONSTRUCTION PERIOD BEFORE NEW FILTERS ARE
INSTALLED AND PRIOR TO TURNING SYSTEM OVER TO THE
OWNER.
7. INSTALL DUCTWORK PARALLEL TO BUILDING COLUMN LINES
UNLESS OTHERWISE NOTED.
8. OVERHEAD HANGERS AND SUPPORTS FOR EQUIPMENT,
DUCTWORK SHALL BE FASTENED TO BUILDING JOISTS OR
BEAMS. DO NOT ATTACH HANGERS AND SUPPORTS TO THE
ABOVE FLOOR SLAB OR ROOF.
9. COORDINATE LOCATION OF EQUIPMENT SUPPORTS WITH
LOCATION OF EQUIPMENT ACCESS PANELS/DOORS TO ENABLE
SERVICE OF EQUIPMENT AND/OR FILTER REPLACEMENT.
10. SEAL PENETRATIONS THROUGH THE BUILDING COMPONENTS IN ACCORDANCE WITH THE CONTRACT SPECIFICATIONS.
11. COORDINATE THE EXACT MOUNTING SIZE AND FRAME TYPE OF
DIFFUSERS, REGISTERS AND GRILLES WITH THE SUPPLIER TO
MEET THE CEILING, WALL AND DUCT INSTALLATION
REQUIREMENTS.
12. ADJUST LOCATION OF CEILING DIFFUSERS, REGISTERS AND
GRILLES AS REQUIRED TO ACCOMMODATE FINAL CEILING GRID
AND LIGHTING LOCATIONS.
13. LOCATE AND SET TEMPERATURE SENSORS AT LOCATIONS
SHOWN ON PLANS. VERIFY EXACT LOCATIONS WITH ARCHITECT
PRIOR TO INSTALLATION. INSTALL DEVICES 48" AFF TO MEET ADA REQUIREMENTS UNLESS NOTED OTHERWISE ON DWGS.
PROVIDE INSULATED BACKING FOR THERMOSTATS MOUNTED ON
EXTERIOR BUILDING WALLS. INSTALL WIRING IN CONDUIT
PROVIDED BY DIVISION 26.
14. COORDINATE THE LOCATION AND ELEVATION OF WALL -MOUNTED
DEVICES WITH PRESENTATION BOARDS, DISPLAY CABINETS,
SHELVES OR OTHER COMPONENTS SHOWN ON THE
ARCHITECTURAL DRAWINGS THAT ARE TO BE INSTALLED UNDER
OTHER DIVISIONS. CONTRACTOR WILL NOT BE REIMBURSED FOR
RELOCATION OF WALL -MOUNTED DEVICES CAUSED BY A LACK OF COORDINATION.
15. PROVIDE A MANUAL BALANCING DAMPER IN EACH BRANCH DUCT
TAKEOFF FROM MAIN SUPPLY, RETURN, OUTDOOR AND EXHAUST
AIR DUCTS.
16. PROVIDE A PREFABRICATED 45 DEGREE, HIGH EFFICIENCY,
RECTANGULAR/ROUND BRANCH DUCT TAKEOFF FITTING WITH
MANUAL BALANCING DAMPER AND LOCKING QUADRANT FOR
BRANCH DUCT CONNECTIONS AND TAKE -OFFS TO INDIVIDUAL
DIFFUSERS, REGISTERS AND GRILLES.
17. BRANCH DUCTWORK TO AIR OUTLETS SHALL BE SAME SIZE AS OUTLET NECK SIZE UNLESS OTHERWISE NOTED.
18. RIGID DUCTWORK INSULATION: PROVIDE 3/4 LB DENSITY, 3" (R -8)
THICK, INSULATION WRAP ON RIGID ROUND, CONCEALED (NON -
CONDITIONED SPACE), SUPPLY AND RETURN AIR DUCTS AND ON
OUTSIDE AIR DUCTS.DUCT SIZES ON MECHANICAL PLANS
INDICATE CLEAR INSIDE AIRFLOW DIMENSIONS, INCREASE SHEET METAL SIZES ACCORDINGLY.
19. PROVIDE EQUIPMENT VENTS PER EQUIPMENT MANUFACTURER'S RECOMMENDATIONS AND EQUIPMENT SPECIFICATIONS. KEEP
PENETRATIONS THROUGH ROOF A MINIMUM OF 10' -0" FROM HVAC EQUIPMENT FRESH AIR INLETS AND 2' -0" FROM ROOF PARAPETS.
20. PROVIDE A NEW SET OF AIR FILTERS IN UNITS PRIOR TO
TESTING, ADJUSTING AND BALANCING. AND BEFORE TURNING
SYSTEM(S) OVER TO OWNER.
21. PLACEMENT, DUCTING AND STARTUP OF THE MECHANICAL UNITS SHALL BE BY THE MECHANICAL CONTRACTOR.
22. EITHER WHEN STORED OR MOVED INTO ROUGH FRAME, HVAC
EQUIPMENT OPENINGS AND DUCTS SHALL BE PROTECTED AND
PROTECTION MAINTAINED UNTIL FINAL STARTUP OF THE SYSTEM.
23. ALL HVAC UNITS INSTALLED AND OPERATIONAL DURING
CONSTRUCTION AND UP TO THE POINT OF OCCUPANCY SHALL BE
INSTALLED WITH MERV -13 FILTERS.
24. JOINTS, PENETRATIONS AND OTHER OPENINGS IN THE BUILDING
ENVELOPE THAT ARE POTENTIAL SOURCES OF AIR LEAKAGE
SHALL BE CAULKED, GASKETED, WEATHER STRIPPED, OR
OTHERWISE SEALED TO LIMIT INFILTRATION AND EXFILTRATION.
SEC. 110.7
25. THE LESSER OF THE MINIMUM RATE OF OUTDOOR AIR REQUIRED BY SEC. 120.1 (C), OR THREE COMPLETE AIR CHANGES SHALL BE
SUPPLIED TO THE ENTIRE BUILDING DURING THE ONE -HOUR
PERIOD IMMEDIATELY BEFORE THE BUILDING IS NORMALLY
OCCUPIED. SEC. 120.1 (D) 2.
26. NON -CENTRALIZED ENERGY MANAGEMENT SYSTEMS SHALL
HAVE SETBACK THERMOSTATS; CAPABLE TO PROGRAM
TEMPERATURE SETPOINTS FOR AT LEAST FOUR PERIODS WITHIN
A 24 -HR. PERIOD. SEC 110.2 (C)
27. THE THERMOSTATIC CONTROLS FOR HVAC SYSTEMS SHALL BE
CAPABLE OF BEING SET LOCALLY OR REMOTELY BY TO CONTROL
COMFORT HEATING DOWN TO 55 °F OR LOWER AND COOLING UP
TO 85°F OR HIGHER. THE THERMOSTATIC CONTROLS SHALL BE
CAPABLE OF PROVIDING A DEAD BAND RANGE OF AT LEAST 5°F
WITHIN WHICH HEATING AND COOLING ENERGY TO THE ZONE IS
SHUT OFF OR REDUCED TO A MINIMUM. SEC. 120.2 (A) (B)
28. OUTDOOR AIR SUPPLY AND EXHAUST EQUIPMENT SHALL BE
INSTALLED WITH DAMPERS THAT AUTOMATICALLY CLOSE UPON
FAN SHUTDOWN. SEC. 120.2 (F)
29. THE PIPING FOR ALL SPACE CONDITIONING SHALL BE INSULATED IN ACCORDANCE WITH TABLE 120.3 -A.
30. SERVICE WATER HEATING SYSTEMS AND EQUIPMENT SHALL
MEET THE APPLICABLE REQUIREMENTS OF THE APPLIANCE
EFFICIENCY REGULATIONS AS REQUIRED BY SEC. 110.1. SEC.
110.3 (B)
31. ALL MECHANICAL VENTILATION AND SPACE -CONDITIONING
SYSTEMS SHALL BE DESIGNED WITH DUCTWORK, DAMPERS, AND
CONTROLS WHICH ALLOWS OUTSIDE AIR RATES TO BE
OPERATED AT THE LARGER OF
1. THE MINIMUM LEVELS SPECIFIED IN SECTION 120.1(C)3 OR
2. THE RATE REQUIRED FOR MAKE -UP OF EXHAUST SYSTEMS
THAT ARE REQUIRED FOR AN EXEMPT OR COVERED
PROCESS, FOR CONTROL OF ODORS, OR FOR THE
REMOVAL OF CONTAMINANTS WITHIN THE SPACE SEC
120.1(F)1.
32. OUTDOOR AIR SUPPLY AND EXHAUST EQUIPMENT SHALL BE
INSTALLED WITH DAMPERS THAT AUTOMATICALLY CLOSE UPON
FAN SHUTDOWN. SEC. 120.2 (F).
33. HVAC SYSTEM SHALL SHUT DOWN UPON AUTOMATIC ACTIVATION OF SMOKE DAMPERS OR COMBINATION SMOKE -FIRE DAMPERS.
34. DUCTS, PLENUMS, OR FITTINGS OF METAL SHALL COMPLY WITH
SMACNA DUCT CONSTRUCTION STANDARDS - METAL AND
FLEXIBLE. SEC 602.3
35. DUCTWORK SHALL BE LEAK -TESTED IN ACCORDANCE WITH
SMACNA HVAC AIR DUCT LEAKAGE TEST MANUAL. SEC. 603.10.1
36. AIR -MOVING SYSTEMS SUPPLYING AIR IN EXCESS OF 2000 CFM
SHALL BE EQUIPPED WITH AN AUTOMATIC SHUTOFF ACTIVATED
BY A SMOKE DETECTOR LOCATED IN THE MAIN SUPPLY -AIR DUCT.
A SYSTEM MAY INCLUDE MORE THAN ONE PIECE OF AC UNIT
WHICH SERVES A COMMON SPACE WITH AGGREGATE SUPPLY
AIR OF MORE THAN 2000 CFM.
37. WHEN FIRE DETECTION OR ALARM SYSTEMS ARE PROVIDED FOR
THE BUILDING, ANY REQUIRED SMOKE DETECTORS SHALL BE
SUPERVISED BY SUCH SYSTEMS AND SHALL BE CAPABLE OF
ACTIVATING THE FIRE ALARM SYSTEM. SEC 608.1
38. ALLAPPLIANCES DESIGNED TO BE FIXED IN POSITION SHALL BE
SECURELY FASTENED IN PLACE IN ACCORDANCE WITH
MANUFACTURER INSTALLATION REQUIREMENTS AND THE
BUILDING CODE. SEC 303.4
39. EACH SPACE -CONDITIONING SYSTEM SHALL BE INSTALLED WITH CONTROLS.
1. CAPABLE OF AUTOMATICALLY SHUTTING OFF THE
SYSTEM DURING PERIODS OF NON -USE AND SHALL
HAVE
A. 4-HR TIMER OR;
B. OCCUPANCY SENSORS OR;
C. AUTO TIME SWITCH CONTROLS AND
ACCESSIBLE MANUAL OVERRIDE FOR UP TO 4 -
HRS.
2. AUTOMATICALLY RESTART AND TEMPORARILY
OPERATE THE SYSTEM TO MAINTAIN SETBACK
THERMOSTAT SETPOINTS FOR MECHANICAL HEATING
AND COOLING.
3. MULTIPURPOSE, CLASSROOMS CONFERENCE,
CONVENTION, AUDITORIUM AND MEETING CENTER
ROOMS OF CERTAIN SIZE WHICH DO NOT HAVE
PROCESSES OR OPERATIONS THAT GENERATE
DUSTS, FUMES, VAPORS OR GASSES SHALL BE
EQUIPPED WITH OCCUPANT SENSOR(S) TO
ACCOMPLISH THE FOLLOWING DURING UNOCCUPIED
PERIODS
A. AUTOMATICALLY SETUP THE OPERATING
COOLING TEMPERATURE SET POINT BY 2°F OR
MORE AND SETBACK THE OPERATING HEATING
TEMPERATURE SET POINT BY 2°F OR MORE
AND;
B. AUTOMATICALLY RESET THE MINIMUM
REQUIRED VENTILATION RATE WITH AN
OCCUPANT SENSOR VENTILATION CONTROL
DEVICE ACCORDING TO SECTION 120.1(C)5..
SEC. 120.2 (E) (1 -3)
40. AIR CONDITIONING REFRIGERANT CIRCUIT ACCESS PORTS
LOCATED OUTDOORS SHALL BE PROTECTED FROM
UNAUTHORIZED ACCESS. SEC 1105.11
41. ENVIRONMENTAL AIR DUCTS SHALL TERMINATE A MINIMUM OF THREE (3) FEET FROM PROPERTY LINE AND OPENINGS INTO THE BUILDING, TEN (10) FEET FROM FORCED AIR INLETS.
42. ENVIRONMENTAL AIR DUCT EXHAUST SHALL NOT DISCHARGE
ONTO A PUBLIC WALKWAY PER SECTION 502.2.1 OF THE
CALIFORNIA MECHANICAL CODE.
43. EXHAUST AIR OPENINGS SHALL BE COVERED WITH A SCREEN HAVING NOT LESS THAN 1/4 -INCH OPENINGS AND NOT MORE
THAN ½ -INCH OPENINGS. SEC 502.1
44. OUTDOOR AIR INTAKE OPENINGS SHALL BE COVERED WITH A SCREEN HAVING NOT LESS THAN 1/4 -INCH OPENINGS AND NOT
MORE THAN ½ -INCH OPENINGS. SEC 402.4
45. OVERFLOW DRAINS FROM A/C UNITS LOCATED IN AN ATTIC OR
FURRED SPACE SHALL DISCHARGE AT A POINT THAT IS READILY OBSERVED. SEC 310.2
46. AT THE TIME OF ROUGH INSTALLATION, OR DURING STORAGE ON
THE CONSTRUCTION SITE AND UNTIL FINAL STARTUP OF THE
HEATING, COOLING, AND VENTILATING EQUIPMENT, ALL DUCT
AND OTHER RELATED AIR DISTRIBUTION COMPONENT OPENINGS
SHALL BE COVERED WITH TAPE, PLASTIC, SHEET METAL, OR
OTHER ACCEPTABLE METHODS TO REDUCE THE AMOUNT OR
DUST, WATER, AND DEBRIS WHICH MAY ENTER THE SYSTEM.
GREEN BUILDING CODE SEC 5.504.3
47. PRIOR TO PERMIT BEING FINALED, A COMPLETE REPORT OF THE
TESTING AND ADJUSTING SHALL BE PROVIDED TO THE OWNER
OR OWNER ’S REPRESENTATIVE AND FORM 5.410 – TESTING AND
ADJUSTING SHALL BE COMPLETED AND PROVIDED TO THE
INSPECTOR.
48. THE PERSON WITH OVERALL RESPONSIBILITY FOR
CONSTRUCTION OR THE PERSON RESPONSIBLE FOR THE
INSTALLATION OF REGULATED FEATURES, MATERIALS,
COMPONENTS, OR MANUFACTURED DEVICES SHALL POST, OR
MAKE AVAILABLE WITH THE BUILDING PERMIT(S) ISSUED FOR THE
BUILDING, THE REQUIRED INSTALLATION CERTIFICATE(S) FOR
FEATURES, MATERIALS, COMPONENTS, OR MANUFACTURED
DEVICES REGULATED BY THE APPLIANCE EFFICIENCY
REGULATIONS OR PART 6. SUCH INSTALLATION CERTIFICATE(S)
SHALL BE MADE AVAILABLE TO THE ENFORCEMENT AGENCY FOR
ALL APPROPRIATE INSPECTIONS. THESE CERTIFICATES SHALL:
1. IDENTIFY FEATURES, MATERIALS, COMPONENTS, OR
MANUFACTURED DEVICES REQUIRED TO VERIFY
COMPLIANCE WITH THE APPLIANCE EFFICIENCY
REGULATIONS AND PART 6.
2. INCLUDE A STATEMENT INDICATING THAT THE FEATURES,
MATERIALS, COMPONENTS, OR MANUFACTURED DEVISE
CONFORM TO THE APPLIANCE EFFICIENCY REGULATIONS
AND PART 6 AND THE REQUIREMENTS FOR SUCH
FEATURES,MATERIALS, COMPONENTS, OR MANUFACTURED
DEVICES GIVEN IN THE PLANS AND SPECIFICATIONS
APPROVED BY THE LOCAL ENFORCEMENT AGENCY.
3. STATE THE NUMBER OF THE BUILDING PERMIT UNDER
WHICH THE CONSTRUCTION OR INSTALLATION WAS
PERFORMED. SEC. 10 -103 (A,B)
49. THE BUILDER SHALL PROVIDE THE BUILDING OWNER OR THE PERSON(S) RESPONSIBLE FOR
BUILDING MAINTENANCE (IN CASE OF MULTI -TENANT OR CENTRALLY OPERATED BUILDINGS) AT OCCUPANCY THE FOLLOWING:
1. OPERATING INFORMATION: THE APPROPRIATE CERTIFICATE(S) OF COMPLIANCE
AND A LIST OF THE FEATURES, MATERIALS, COMPONENTS, AND MECHANICAL
DEVICES INSTALLED IN THE BUILDING AND INSTRUCTIONS ON HOW TO OPERATE THEM EFFICIENTLY.
2. MAINTENANCE INFORMATION: REQUIRED ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY STATED AND INCORPORATED ON A READILY ACCESSIBLE LABEL. THE
LABEL MAY BE LIMITED TO IDENTIFYING THE OPERATION AND MAINTENANCE MANUAL
3. VENTILATION INFORMATION: A DESCRIPTION OF THE QUANTITIES OF OUTDOOR
AND RECIRCULATED AIR THAT THE VENTILATION SYSTEMS ARE DESIGNED TO PROVIDE TO EACH AREA. SEC. 10 -103 (B) 2 -4
CODES AND STANDARDS
CONSTRUCTION SHALL COMPLY WITH THE FOLLOWING PARTS OF TITLE 24, CALIFORNIA CODE OF REGULATIONS (CCR):
PART 1 2022 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE PART 2 2022 CALIFORNIA BUILDING CODE (CBC) VOLUME 1 AND 2 PART 3 2022 CALIFORNIA ELECTRICAL CODE (CEC)
PART 4 2022 CALIFORNIA MECHANICAL CODE (CMC)
PART 5 2022 CALIFORNIA PLUMBING CODE (CPC)
PART 6 2022 CALIFORNIA ENERGY CODE (CEC)
PART 7 CURRENTLY VACANT
PART 8 2022 CALIFORNIA HISTORICAL BUILDING CODE
PART 9 2022 CALIFORNIA FIRE CODE (CFC)
PART 10 2022 CALIFORNIA EXISTING BUILDING CODE
PART 11 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE
PART 12 2022 CALIFORNIA REFERENCED STANDARDS
U.S. DEPARTMENT OF THE INTERIOR - STANDARD FOR THE TREATMENT OF HISTORIC
PROPERTIES
PARTIAL LIST OF APPLICABLE STANDARDS:
2013 CALIFORNIA BUILDING CODE (FOR SFM) REFERENCED STANDARDS CHAPTERS 35 AND 45.
NFPA 13, AUTOMATIC SPRINKLER SYSTEMS (CALIFORNIA AMENDED) 2016 EDITION NFPA 14, STANDPIPE SYSTEMS (CALIFORNIA AMENDED) 2016 EDITION NFPA 17, DRY CHEMICAL EXTINGUISHING SYSTEM 2017 EDITION NFPA 17A, WET CHEMICAL SYSTEMS 2017 EDITION NFPA 20, STATIONARY PUMPS 2016 ED ITION NFPA 24, PRIVATE FIRE MAINS (CALIFORNIA AMENDED) 2016 EDITION NFPA 72, NATIONAL FIRE ALARM CODE (CALIFORNIA AMENDED) 2016 EDITION (NOTE: SEE UL STANDARD 1971 FOR "VISUAL DEVICES")
NFPA 80, FIRE DOOR AND OTHER OPENING PROTECTIVES 2016 EDITION NFPA 253, CRITICAL RADIANT FLUX OF FLOOR COVERING SYSTEMS 2015 EDITION NFPA 2001 CLEAN AGENT FIRE EXTINGUISHING SYSTEMS 2015 EDITION REFERENCE CODE SECTION FOR NFPA STANDARDS -2001 CBC (SFM) 3504.1 Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE-TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 -126
12" = 1'-0"
28-10-2024 15:21:54
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
M0.01
MECHANICAL FRONT
SHEET
Author
Checker
24162
07.24.24 AS-BUILT DRAWINGS
MECHANICAL SHEET INDEX
SHEET NUMBER SHEET NAME
M0.01 MECHANICAL FRONT SHEET
M0.02 MECHANICAL NOTES
M0.03 MECHANICAL SYMBOLS AND ABBREVIATIONS
M0.04 MECHANICAL SCHEDULES
MD2.01 MECHANICAL FIRST FLOOR DEMOLITION PLAN
MD2.02 MECHANICAL ROOF DEMOLITION PLAN
M2.01 MECHANICAL FIRST FLOOR PLAN
M2.02 MECHANICAL ROOF PLAN
100% SD 10/28/2024
REFRIGERANT PIPING NOTES
1. REFRIGERANT PIPING MATERIALS AND SIZES SHALL BE PER
MANUFACTURER'S RECOMMENDATIONS.VENT ALL ENTRAINED AIR
FROM PIPING SYSTEM.
2. REFRIGERANT PIPES PENETRATING FRAMING MEMBERS SHALL BE PROTECTED BY STEEL NAIL PLATES NOT LESS THAN NO. 18 GAUGE (0.0478 INCH) IN THICKNESS. THE NAIL PLATE SHALL EXTEND ALONG THE WALL NOT LESS THAN 1 -1/2" BEYOND THE OUTSIDE DIAMETER OF THE PIPE.
COMMISSIONING NOTES
1. A COMMISSIONING PLAN AND REPORT WHICH MEETS THE
REQUIREMENTS OF THE CURRENT CEnC CODE SHALL BE
PROVIDED FOR ALL NEW MECHANICAL SYSTEMS UNLESS EXEMPT
BY CODE EXCEPTIONS.
2. A COMMISSIONING PLAN SHALL BE DEVELOPED BY A CERTIFIED
COMMISSIONING PROFESSIONAL (CCP) AND SHALL INCLUDE THE
FOLLOWING ITEMS:
2.1. A NARRATIVE DESCRIPTION OF THE ACTIVITIES THAT WILL BE
ACCOMPLISHED DURING EACH PHASE OF COMMISSIONING,
INCLUDING THE PERSONNEL INTENDED TO ACCOMPLISH
EACH OF THE ACTIVITIES.
2.2. A LISTING OF THE SPECIFIC EQUIPMENT, APPLIANCES OR
SYSTEMS TO BE TESTED AND A DESCRIPTION OF THE TESTS
TO BE PERFORMED.
2.3. FUNCTIONS TO BE TESTED, INCLUDING, BUT NOT LIMITED TO CALIBRATIONS AND ECONOMIZER CONTROLS.
2.4. CONDITIONS UNDER WHICH THE TEST WILL BE PERFORMED.
AT A MINIMUM, TESTING SHALL AFFIRM WINTER AND SUMMER
DESIGN CONDITIONS AND FULL OUTSIDE AIR CONDITIONS.
2.5. MEASURABLE CRITERIA FOR PERFORMANCE.
3. PROVIDE A "PRELIMINARY COMMISSIONING REPORT" AND A "FINAL COMMISSIONING REPORT" TO THE OWNER AND MAKE AVAILABLE
TO THE CODE OFFICIAL UPON REQUEST.
AIR BALANCING
HEATING, VENTILATION AND AIR CONDITIONING SYSTEMS (INCLUDING)
HYDRONIC SYSTEMS SHALL BE BALANCED IN ACCORDANCE WITH ONE OF THE FOLLOWING METHODS.
1. AABC NATIONAL STANDARDS FOR TOTAL SYSTEM BALANCE.
2. ACCA MANUAL B.
3. ASHRAE 111.
4. NEBB PROCEDURAL STANDARDS FOR TESTING ADJUSTING
BALANCING OF ENVIRONMENTAL SYSTEMS.
5. SMACNA HVAC SYSTEMS TESTING, ADJUSTING, AND BALANCING.
LIFE SAFETY CONTROL NOTES
COORDINATE WITH LIFE SAFETY CONTRACTOR FOR THE
INTERCONNECTING OF HVAC EQUIPMENT WITH THE BUILDING FIRE
ALARM SYSTEM FOR SHUT DOWN UPON A SIGNAL FROM THE FIRE
ALARM SYSTEM.
DUCT INSULATION
1. PORTIONS OF SUPPLY -AIR AND RETURN -AIR DUCTS CONVEYING
HEATED OR COOLED AIR LOCATED IN ONE OR MORE OF THE
FOLLOWING SPACES SHALL BE INSULATED TO A MINIMUM
INSTALLED LEVEL OF R -8:
1. OUTDOORS; OR
2. IN A SPACE BETWEEN THE ROOF AND AN INSULATED
CEILING; OR
3. IN A SPACE DIRECTLY UNDER A ROOF WITH FIXED VENTS OR OPENINGS TO THE OUTSIDE OR UNCONDITIONED SPACES;OR
4. IN AN UNCONDITIONED CRAWLSPACE; OR
5. IN OTHER UNCONDITIONED SPACES.
2. PORTIONS OF SUPPLY -AIR DUCTS THAT ARE NOT IN ONE OF THESE
SPACES, INCLUDING DUCTS BURIED IN CONCRETE SLAB, SHALL BE INSULATED TO A MINIMUM INSTALLED LEVEL OF R -4.2 OR BE
ENCLOSED IN DIRECTLY CONDITIONED SPACE.
3. OUTSIDE AIR DUCTS LOCATED INSIDE THE BUILDING SHALL BE INSULATED WITH MINIMUM OF 1".
BUILDING FLUSHOUT
AFTER ALL INTERIOR FINISHES HAVE BEEN INSTALLED, FLUSH OUT THE
BUILDING BY SUPPLYING CONTINUOUS VENTILATION WITH ALL AIR
HANDLING UNITS AT THEIR MAXIMUM OUTDOOR AIR RATE AND ALL SUPPLY FANS AT THEIR MAXIMUM POSITION AND RATE FOR AT LEAST 14 DAYS.
1. DURING THIS TIME, MAINTAIN AN INTERNAL TEMPERATURE
OF AT LEAST 60°F AND RELATIVE HUMIDITY NO HIGHER THAN
60 PERCENT. IF EXTENUATING CIRCUMSTANCES MAKE THESE
TEMPERATURE AND HUMIDITY LIMITS UNACHIEVABLE, THE
FLUSHOUT MAY BE CONDUCTED UNDER CONDITIONS AS
CLOSE AS POSSIBLE TO THESE LIMITS, PROVIDED THAT
DOCUMENTATION OF THE EXTENUATING CIRCUMSTANCES IS
PROVIDED IN WRITING.
2. OCCUPANCY MAY START AFTER 4 DAYS, PROVIDED FLUSH -
OUT CONTINUES FOR THE FULL 14 DAYS. DURING OCCUPIED
TIMES, THE THERMAL COMFORT CONDITIONS OF TITLE 24
MUST BE MET.
MECHANICAL NOTES
SCOPE OF WORK
1. THE WORK INCLUDED UNDER THIS SECTION CONSISTS OF FURNISHING ALL
MATERIALS, EQUIPMENT AND LABOR, AND THE PERFORMING OF ALL
FUNCTIONS, EXCEPT AS OTHERWISE SPECIFIED HEREIN OR SHOWN ON THE
DRAWINGS TO BE PERFORMED BY OTHERS, AND FOR THE INSTALLATION OF ALL
HEATING AND COOLING EQUIPMENT, PIPING AND ALL DUCTWORK, GRILLES, REGISTERS, ETC., INCLUDING ALL CONNECTIONS TO EACH SYSTEM AS SPECIFIED HEREIN AND SHOWN ON THE DRAWINGS. IT SHALL FURTHER
INCLUDE FURNISHING AND INSTALLING ALL MISCELLANEOUS ITEMS REQUIRED
FOR THE OPERATION OF THE SYSTEM, WHETHER SPECIFICALLY CALLED OUT OR NOT.
2. SPECIAL INSPECTIONS: WHERE THE PLANS INDICATE SPECIAL INSPECTIONS
AND REPORT, OR AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION (AHJ), THE CONTRACTOR SHALL, AT HIS OWN EXPENSE, HIRE AN INDEPENDENT
THIRD PARTY INSPECTOR OR TESTING AGENCY TO PERFORM THE REQUIRED
INSPECTIONS FOR THE TYPES OF WORK REQUIRED OR IDENTIFIED ON THE SPECIAL INSPECTION FORM. THE SPECIAL INSPECTOR SHALL SUBMIT A FINAL
SIGNED REPORT TO THE REGISTERED DESIGN PROFESSIONAL ENGINEER,
PROVIDING TEST RESULTS AND STATING WHETHER THE ITEMS REQUIRING
SPECIAL INSPECTION WERE IN COMPLIANCE WITH THE INSPECTION REQUIREMENTS. PROVIDE ADDITIONAL COST FOR ENGINEER'S SEALED LETTER OF APPROVAL.
COORDINATION
1. CONTRACT DRAWINGS ARE DIAGRAMMATIC AND INTENDED TO SHOW APPROXIMATE LOCATIONS. COORDINATE WORK WITH ALL TRADES TO AVOID INTERFERENCE. INSTALLED HVAC WORK WHICH INTERFERES WITH THE WORK
OF OTHER TRADES DUE TO LACK OF COORDINATION SHALL BE RE -INSTALLED AT NO ADDITIONAL COST TO THE OWNER.
2. REFER TO THE ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF EQUIPMENT, PARTITIONS, WALLS, AND GENERAL CONSTRUCTION.
3. ALL CONTRACTORS SHALL BE RESPONSIBLE FOR COORDINATING WORK WITH OTHER TRADES AFFECTED BY EACH OTHERS WORK.
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL FIELD CONDITIONS WHICH MAY AFFECT HIS WORK BEFORE SUBMITTING BIDS.
5. PERFORMANCE OF ALL WORK SHALL BE SCHEDULED AS APPROVED BY THE OWNER. AVOID INTERFERENCE WITH FUNCTIONS IN OTHER PARTS OF THE FACILITY, AND COORDINATE WITH THE WORK OF OTHER TRADES. SERVICES
SHALL NOT BE INTERRUPTED WITHOUT WRITTEN PRIOR APPROVAL OF THE OWNER.
6. NO STRUCTURAL MEMBER SHALL BE CUT WITHOUT PERMISSION FROM THE ARCHITECT AND THE STRUCTURAL ENGINEER.
7. PROTECT EXISTING BUILDING STRUCTURE AND GROUNDS FROM DAMAGE WHICH MAY OCCUR DURING DEMOLITION WORK. ANY DAMAGE TO THE EXISTING
FACILITIES SHALL BE REPAIRED, REPLACED, OR RESTORED TO THE ORIGINAL
CONDITION AT NO ADDITIONAL COST AND TO THE SATISFACTION OF THE OWNER.
8. SPACE ABOVE CEILINGS IS CRITICAL - THE CONTRACTOR SHALL VERIFY SPACE
ABOVE CEILING & COORDINATE WITH PLUMBING, ELECTRICAL, STRUCTURAL,
FIRE PROTECTION, ARCHITECTURAL, AND ALL OTHER TRADES INVOLVED BEFORE COMMENCEMENT OF WORK.
CODES AND PERMITS
1. ALL MATERIALS, EQUIPMENT AND INSTALLATION MUST COMPLY WITH ALL
APPLICABLE LAWS, CODES, RULES AND REGULATIONS, REQUIRED BY CITY, COUNTY AND STATE, AS WELL AS FEDERAL REQUIREMENTS.
2. COMBUSTIBLE MATERIALS SHALL NOT BE USED IN A NON -COMBUSTIBLE BUILDING AS DEFINED BY THE BUILDING CODE. COMBUSTIBLE MATERIALS MAY BE PROTECTED AS SPECIFIED BY THE ENGINEER AND ARCHITECT OF RECORD.
3. PERMITS: OBTAIN AND PAY FOR ALL REQUIRED PERMITS, LICENSES AND FEES.
4. INSPECTIONS: FURNISH OWNER WITH CERTIFICATE OF INSPECTION AND
APPROVAL BY LOCAL AUTHORITIES PRIOR TO FINAL ACCEPTANCE OF THE PROJECT BY THE OWNER. ALL WORK MUST BE INSPECTED.
PRODUCTS
1. ALL PRODUCTS SHALL BE NEW AND UNUSED OF ESTABLISHED AND REPUTABLE AMERICAN MANUFACTURERS. ITEMS OF EQUIPMENT USED FOR THE SAME PURPOSE SHALL BE OF THE SAME MANUFACTURER.
2. SYSTEMS SHALL BE COMPLETE AND OPERABLE. ANY ACCESSORIES REQUIRED
FOR THE OPERATION OF THE SYSTEM SHALL BE INCLUDED AS THOUGH SPECIFICALLY INDICATED TO BE PROVIDED. SUCH ACCESSORIES INCLUDE BUT
ARE NOT LIMITED TO FILTERS, CONDENSATE DRAINS, RELIEF VALVES, SERVICE VALVES, THERMOSTATS, VIBRATION ISOLATORS, ETC. MOTOR STARTERS FOR
PREWIRED EQUIPMENT (AND OTHER PROTECTION AND CONTROL DEVICES) ARE ALSO INCLUDED IN THIS SPECIFICATION.
3. SPECIFIC REFERENCE TO A MANUFACTURER'S PRODUCT IS ONLY TO ESTABLISH TYPE, QUALITY, AND PERFORMANCE REQUIRED. THESE QUALIFICATIONS ARE IN
ADDITION TO THE REQUIREMENTS SHOWN ON THE DRAWINGS AND
SPECIFICATIONS. LISTING OF ALTERNATE EQUIPMENT MANUFACTURERS SHALL
NOT BE CONSTRUED AS AN UNCONDITIONAL APPROVAL OF THE PRODUCTS OF THOSE MANUFACTURERS.
4. ACCEPTABLE HVAC EQUIPMENT MANUFACTURERS: AS SPECIFIED ELSEWHERE IN THESE DOCUMENTS.
5. PROVIDE CLEARANCES AS PER MANUFACTURERS RECOMMENDATIONS.
SUBSTITUTIONS
1. SUBSTITUTIONS OF MATERIALS OR PRODUCTS SHOWN HEREIN SHALL BE BY OWNER'S, ARCHITECTS, OR ENGINEER'S WRITTEN APPROVAL. ANY DEVIATION FROM THESE DRAWINGS WILL NOT BE ALLOWED.
2. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF
ANY SUBSTITUTIONS AND COSTS OF CHANGES INCURRED BY OTHER TRADES DUE TO THE SUBSTITUTIONS. OTHER TRADES INCLUDE: ELECTRICAL,
PLUMBING, STRUCTURAL, ROOFING, OR ANY TRADE EFFECTED BY THE SUBSTITUTION.
ACOUSTICAL LINER
1. SUPPLY, RETURN AND PLENUM DUCTS SHALL BE ACOUSTICALLY LINED FOR THE FIRST 15' -0" MINIMUM FROM UNIT CONNECTION POINTS.
2. ALL SHEET METAL SUPPLY, RETURN AND PLENUM DUCTWORK REQUIRING ACOUSTICAL LINER SHALL BE LINED WITH 1" THICK LINER.
CLEANUP
1. REMOVE AS MUCH DIRT, SCRAP MATERIAL AND DEBRIS AS POSSIBLE, AT THE
END OF EACH WORKING DAY TO PREVENT HAZARDOUS CONDITIONS AND EXCESS DUST.
RELIEF VENTS
1. ALL RELIEF VENT EXTERIOR PENETRATIONS SHALL BE PROVIDED WITH COUNTERBALANCED BAROMETRIC BACKDRAFT DAMPERS.
GENERAL REQUIREMENTS FOR CONTROLS AND CONTROL WIRING
1. ALL CONTROL EQUIPMENT, INTEGRAL STARTERS, INTERLOCKING STARTERS,
SMOKE DETECTORS, RELAYS, TRANSFORMERS, PANELS AND OTHER DEVICES
SHOWN, SPECIFIED OR NEEDED FOR A COMPLETE CONTROL SYSTEM ARE TO BE PROVIDED AND INSTALLED UNDER THIS MECHANICAL DIVISION. COMPONENTS AND
WIRING NOT SHOWN, BUT REQUIRED FOR THE PROPER OPERATION OF EQUIPMENT
OR CONTROL SYSTEMS, SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE PROJECT.
2. POWER WIRING, LOW VOLTAGE WIRING AND RACEWAYS RELAT ED TO CONTROLS
SYSTEMS ARE TO BE PROVIDED AND INSTALLED UNDER THIS MECHANICAL DIVISION.
3. INSTALLATION OF ALL EQUIPMENT, DEVICES AND WIRING SHALL CONFORM TO THE NATIONAL ELECTRIC CODE. ALL CONTROLS SHALL BE FURNISHED AND PROPERLY IDENTIFIED WITH INSTRUCTIONS FOR PROPER CONNECTIONS. RESPONSIBILITY FOR
PROPER CONNECTIONS AND OPERATION IS INCLUDED UNDER THE MECHANICAL CONTRACTORS RESPONSIBILITY. VERIFY ALL VOLTAGES, PHASES AND ELECTRICAL
CONNECTIONS WITH THE ELECTRICAL CONTRACTOR BEFORE ORDERING ANY
EQUIPMENT, AND IF DISCREPANCIES OCCUR, THEY SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT BEFORE PROCEEDING WITH ANY WORK.
4. ALL TEMPERATURE CONTROLS ARE TO BE TESTED, ADJUSTED, AND CALIBRATED FOR PROPER OPERATION.
5. COORDINATE EXACT THERMOSTAT AND/OR MOUNTING HEIGHT ABOVE FINISHED FLOOR AND FINAL LOCATION WITH THE ARCHITECT.
6. THERMOSTATS LOCATED ON EXTERIOR WALLS SHALL HAVE AN INSULATED SUB - BASE.
DUCT SMOKE DETECTORS
1. MECHANICAL CONTRACTOR TO PROVIDE AND INSTALL ALL DUCT SMOKE
DETECTORS WHERE INDICATED ON THE DRAWINGS AND AS REQUIRED BY LOCAL ADOPTED CODES, LOCAL AMENDMENTS, THE BUILDING OFFICIAL.
2. SMOKE DETECTORS SHALL BE POWERED BY 24 VOLT POWER. POWER MAY BE
TAKEN FROM UNIT CONTROL TRANSFORMER IF APPROVED BY MANUFACTURER WITHOUT VOIDING WARRANTY. IF MANUFACTURER WILL NOT ALLOW ADDITIONAL CONTROL CIRCUIT LOAD, PROVIDE AND INSTALL A SECONDARY 24 VOLT
TRANSFORMER POWERED FROM EQUIPMENT POWER SUPPLY TO CONTROL SMOKE DETECTOR. ALTERNATIVE 120 VOLT POWER PROVISIONS ARE ACCEPTABLE. THE
MECHANICAL CONTRACTOR IS RESPONSIBLE FOR ALL COSTS RELATED TO PROVIDING POWER TO SMOKE DETECTORS.
3. UPON ACTIVATION, SMOKE DETECTOR SHALL SHUT DOWN 24 VOLT CONTROL
POWER CIRCUIT AND ALL OPERATIONAL CAPABILITIES OF THE AIR DISTRIBUTION SYSTEMS FOR THE CONNECTED UNIT.
4. INTERFACE DETECTORS TO SUPERVISORY CIRCUIT OF FIRE ALARM SYSTEM/FIRE SPRINKLER MONITORING PANEL. IN OCCUPANCIES NOT REQUIRED TO BE EQUIPPED
WITH A FIRE ALARM SYSTEM, PROVIDE DUCT DETECTOR WITH A REMOTE LED INDICATOR LIGHT MOUNTED BELOW UNIT IN CEILING PER NFPA 72 -5-10.6.08 OR AN APPROVED LOCATION. COORDINATE WITH ELECTRICAL/FIRE ALARM CONTRACTOR PRIOR TO ROUGH -IN.
EQUIPMENT
1. ALL MECHANICAL EQUIPMENT SHALL BE PROPERLY LISTED AND LABELED BY AN APPROVED AGENCY.
2. ALL EQUIPMENT SHALL BE LABELED WITH STEEL TAGS EMBOSSED WITH 1/4" HIGH LETTERS, PERMANENTLY ATTACHED. TAG SHALL CLEARLY INDICATE THE AREA SERVED BY THE EQUIPMENT.
3. MAINTAIN MANUFACTURER'S RECOMMENDATIONS FOR ALL REQUIRED SERVICE CLEARANCES AND INSTALLATION OF EQUIPMENT.
4. REFER TO ARCHITECTURAL DRAWINGS FOR ACCESS TO ROOF INSTALLED MECHANICAL EQUIPMENT. ROOF ACCESS TO COMPLY WITH THE MECHANICAL CODE ADOPTED BY THE AUTHORITY HAVING JURISDICTION.
5. DUCT SYSTEMS USED WITH BLOWER TYPE EQUIPMENT WHICH ARE PORTIONS OF A
HEATING, COOLING, ABSORPTION, EVAPORATIVE COOLING OR OUTDOOR AIR VENTILATION SYSTEM SHALL BE SIZED IN ACCORDANCE WITH CHAPTER 17 OF THE CALIFORNIA MECHANICAL CODE.
FINAL TESTS
1. AN INDEPENDENT AABC, NEBB OR TABB LIFE SAFETY LEVEL 2 CERTIFIED
CONTRACTOR SHALL BALANCE AIR DISTRIBUTION TO VALUES LISTED ON DRAWINGS. A FINAL COPY OF THE TEST AND BALANCE REPORT SHALL BE PROVIDED TO THE ENGINEER UPON COMPLETION OF THE REPORT. A PROJECT
SHALL NOT BE CONSIDERED IN COMPLIANCE WITH THE PLANS AND SPECIFICATIONS UNTIL SUCH A REPORT HAS BEEN PROVIDED TO THE ENGINEER.
2. BEFORE ACCEPTANCE AND FINAL PAYMENT, IT SHALL BE DEMONSTRATED THAT ALL APPARATUS IS FUNCTIONING PROPERLY AND EFFICIENTLY. THE CONTRACTOR
SHALL MAKE A THOROUGH TEST OF EACH SUPPLY, RETURN, AND EXHAUST
SYSTEMS TO ASSURE THAT EACH DIFFUSER AND REGISTER HAS THE PROPER QUANTITY OF AIR IN ACCORDANCE WITH AABC OR NEBB. PROVIDE ADDITIONAL
COMFORT BALANCE ADJUSTMENTS PER OWNER/TENANT REQUIREMENTS TO ADDRESS ANY NEEDED VARIATIONS IN DESIGN AIR FLOWS.
3. THE TEST AND BALANCE CONTRACTOR HAS THE RIGHT TO COMMUNICATE ANY INFORMATION TO THE MECHANICAL ENGINEER.
GUARANTEE
1. THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS, EQUIPMENT AND
WORKMANSHIP FROM DEFECT OF WORKMANSHIP, AND SHALL REPLACE OR REPAIR
WITHOUT ADDITIONAL COST TO THE OWNER ALL DEFECTIVE MATERIAL AND WORKMANSHIP, FOR A PERIOD OF (1) YEAR AFTER COMPLETION AND ACCEPTANCE.
CLOSEOUT
1. SUBMIT THE SPECIFIED NUMBER OF COPIES OF SHOP DRAWINGS FOR MATERIALS, FIXTURES AND EQUIPMENT. INDICATE MANUFACTURERS, TRADE NAMES, SPECIFIC
MODEL NUMBERS, AND TECHNICAL INFORMATION FOR EACH ITEM BEING FURNISHED.
2. ASSEMBLE OPERATION MANUALS FOR EACH ITEM INSTALLED FURNISH EQUIPMENT CUT SHEET AND CONTROL WIRING DIAGRAMS. SUBMIT COPIES AS DEFINED UNDER GENERAL CONDITIONS.
3. ALL SYSTEMS SHALL BE COMPLETE AND FULLY OPERATIONAL. ACCEPTANCE BY THE OWNER SHALL BE A CONDITION OF THE CONTRACT.
4. ALL MATERIALS, WORKMANSHIP, AND EQUIPMENT SHALL BE GUARANTEED FOR A MINIMUM OF ONE YEAR AFTER SYSTEM ACCEPTANCE.
5. PROVIDE TYPE WRITTEN OPERATING INSTRUCTIONS AND EQUIPMENT WARRANTIES TO THE OWNERS REPRESENTATIVES.
6. CONTRACTOR SHALL FURNISH RECORD SET DRAWINGS CONSISTING OF REPRODUCIBLE CAD FILES UPON COMPLETION OF WORK FOR OWNER'S USE.
MINIMUM SCALE SHALL BE 1/8"= 1' -0". THE COMPLETE SET OF RECORD DOCUMENTS IN SHALL BE IN AN AUTOCAD FORMAT AS REQUIRED BY OWNER, ON COMPACT DISC.
7. CONTRACTOR SHALL MAKE FINAL INSPECTION AND TESTS IN THE PRESENCE OF
THE OWNER AND SHALL SUPPLY ALL LABOR, MATERIALS, INSTRUMENTS, AND EQUIPMENT REQUIRED FOR TESTING.
POLLUTANT CONTROL
INDOOR AIR QUALITY DURING CONSTRUCTION
TEMPORARY VENTILATION DURING CONSTRUCTION SHALL BE
PROVIDED IN ACCORDANCE WITH THE FOLLOWING:
1. VENTILATION DURING CONSTRUCTION SHALL BE ACHIEVED
THROUGH OPENINGS IN THE BUILDING SHELL USING FANS
TO PRODUCE NOT LESS THAN THREE AIR CHANGES PER
HOUR.
2. THE SUPPLY AND RETURN HVAC SYSTEM OPENINGS SHALL
BE COVERED WITH TAPE, PLASTIC SHEET METAL OR OTHER
METHODS ACCEPTABLE TO THE ENFORCING AGENCY TO
REDUCE THE AMOUNT OF DUST OR DEBRIS THAT CAN
COLLECT IN THE SYSTEM.
3. THE BUILDING WILL BE OCCUPIED DURING DEMOLITION AND
CONSTRUCTION, VENTILATION SHALL BE PROVIDED IN
ACCORDANCE WITH THE CONTROL MEASURES OF THE
SMACNA IAQ GUIDELINES FOR OCCUPIED BUILDINGS DURING
CONSTRUCTION.
4. THE PERMANENT HVAC SYSTEM SHALL NO BE USED DURING
CONSTRUCTION TO CONDITION AND VENTILATE THE
BUILDING WITHIN THE REQUIRED TEMPERATURE RANGE FOR
MATERIAL AND EQUIPMENT INSTALLATION. WHERE
REQUIRED, A SUPPLEMENTAL HVAC SYSTEM SHALL BE USED
DURING CONSTRUCTION.
Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE-TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 -126
12" = 1'-0"
28-10-2024 15:21:54
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
M0.02
MECHANICAL NOTES
Author
Checker
24162
07.24.24 AS-BUILT DRAWINGS
100% SD 10/28/2024
DESCRIPTION
AIR CONDITIONING UNIT
ACCESS DOOR
ABOVE FINISHED FLOOR
AIR HANDLING
BACK DRAFT DAMPER (WEIGHTED)
BACKFLOW PREVENTER
BYPASS TIMER
BRITISH THERMAL UNITS PER HOUR
COOLING COIL
CEILING DIFFUSER
CUBIC FEET PER MINUTE
CEILING
CONDENSING UNIT
CONSTANT VOLUME,
CONTINUES
COMBINATION FIRE/SMOKE DAMPER
DISCHARGE AIR LOUVER
DECIBELS
DRY BULB TEMPERATURE
DIRECT DIGITAL CONTROL
DIAMETER
DOWN
DOWN THROUGH ROOF
EXHAUST AIR
ENTERING AIR TEMPERATURE
ENRGY EFFICIENCY RATIO
EXHAUST FAN
EXHAUST GRILLE
EFFICIENCY
ENERGY MANAGEMENT CONTROL SYSTEM
ENERGY MANAGEMENT SYSTEM
EXHAUST REGISTER
EXTERNAL STATIC PRESSURE
DEGREES, FAHRENHEIT
FORCED AIR UNIT
FLEX CONNECTION
FAN COIL UNIT
FIRE DAMPER
FLOOR
FULL LOAD AMPS
FEET PER MINUTE
FEET
FACE VELOCITY
HERTZ
HEAT PUMP UNIT
HORSE POWER
HEATING SEASONAL PERFORMANCE FACTOR
HOT WATER
HOT WATER RETURN
HOT WATER SUPPLY
INCHES
INCHES OF WATER COLUMN
INDOOR FAN MOTOR
LEAVING AIR TEMPERATURE
POUNDS
LOCKED ROTOR AMPS
MAXIMUM
ONE THOUSAND BTUH
MINIMUM CIRCUIT AMPS
MAXIMUM CIRCUIT AMPS
MOTORIZED DAMPER
MINIMUM
MAXIMUM FUSE SIZE
MANUAL VOLUME DAMPER
NOT APPLICABLE
NOISE CRITERIA
NOT IN CONTRACT
NECK
NUMBER
NOT TO SCALE
OUTSIDE AIR INTAKE
OUTSIDE AIR LOUVER
OPPOSED BLADE DAMPER
OUTDOOR FAN MOTOR
OUTSIDE AIR
OUTSIDE AIR GRILLE
RETURN AIR
RETURN AIR GRILLE
RETURN FAN
RETURN GRILLE
RELATIVE HUMIDITY
RATED LOAD AMPS
ROOM
REVOLUTIONS PER MINUTE
RETURN REGISTER
SUPPLY AIR
SUPPLY AIR REGISTER
SUPPLY DIFFUSER
SEASONAL ENRGY EFFICIENCY RATIO
SUPPLY AIR FAN
STATIC PRESSURE
SPECIFICATIONS
SUPPLY REGISTER
ABBREVIATION
AC
AD
AFF
AH
BDD
BFP
BT
BTUh
CC
CD
CFM
CLG
CU
CV
CONT.
CFSD
DAL
DB
DBT
DDC
DIA
DN
DTR
EA
EAT
EER
EF
EG
EFF
EMCS
EMS
ER
ESP
°F
FAU
FC
FCU
FD
FLR
FLA
FPM
FT
FV
HZ
HPU
HP
HSPF
HW
HWR
HWS
IN
IN. W.C.
IFM
LAT
LBS
LRA
MAX
MBH
MCA
MCOP
MD
MIN
MFS
MVD
N/A
NC
NIC
NK
NO
NTS
OAI
OAL
OBD
OFM
OSA
OAG
RA
RAG
RF
RG
RH
RLA
RM
RPM
RR
SA
SAR
SD
SEER
SF
SP
SPEC
SR
SUPPLY DUCT RISER IN PLAN
RETURN DUCT RISER IN PLAN
EXHAUST DUCT RISER IN PLAN
RECTANGULAR DUCTWORK (WIDTH x DEPTH)
RECTANGULAR DUCTWORK (WIDTH x DEPTH)
FLAT OVAL DUCTWORK
ROUND DUCTWORK (SIZE, DIAMETER)
1" ACOUSTICALLY LINED DUCTWORK
SQUARE -THROATED ELBOW W/TURNING VANES
RADIUS ELBOW
RADIUS TEE
SQUARE -THROATED TEE
CHANGE IN ELEVATION WITH RELATION TO
AIR FLOW
VOLUME DAMPER
TRANSITION WITH FLAT SIDE
TRANSITION ON CENTER
RECTANGULAR -TO -ROUND TRANSITION
TAKE -OFF TAP TO RECTANGULAR DUCT
AND VOLUME DAMPER
CONICAL TAP TO RECTANGULAR DUCT
AND VOLUME DAMPER
COMBINATION FIRE SMOKE DAMPER (CFSD)
FIRE DAMPER (FD)
FLEXIBLE CONNECTOR
EXISTING DUCTWORK TO REMAIN (DASHED)
EXISTING TO BE REMOVED (HATCHED)
NEW DUCTWORK (SOLID)
(L) NEW LINED DUCTWORK (SOLID)
(DWL) NEW DOUBLE WALL LINED DUCTWORK
(SOLID)
NEW FLEXIBLE DUCT (MAXIMUM LENGTH 5' -0")
ACCESS REQUIRED FOR EQUIPMENT SERVICE
SIDE WALL REGISTER/GRILLE
RETURN GRILLE WITH ACOUSTICALLY LINED
BOOT
CEILING DIFFUSER 4 -WAY THROW
CEILING DIFFUSER 3 -WAY THROW
CEILING DIFFUSER 2 -WAY THROW
CEILING DIFFUSER 2 -WAY THROW
CEILING DIFFUSER 1 -WAY THROW
RETURN AIR GRILLE
EXHAUST GRILLE
LINEAR CEILING DIFFUSER
THERMOSTAT (MAX. 48" A.F.F.)
TEMPERATURE SENSOR (MAX. 48" A.F.F.)
CARBON DIOXIDE SENSOR (MAX. 48" A.F.F.)
BYPASS TIMER (MAX. 48" A.F.F.)
DESCRIPTION ABBREVIATION
10x8
10x8ø
8ø
(L)
NK= NK=
NK= NK=
R/D R/D
CFSD CFSD
FD
X(L) X(L)
X(DWL) X(DWL)
T
TS
CO ₂
BT
DESCRIPTION ABBREVIATION
PUMP
WYE STRAINER (BALL VALVE & HOSE CAP)
FLEXIBLE CONNECTION
ISOLATION BALL VALVE
2-WAY MODULATING CONTROL VALVE
DRAIN VALVE W/ HOSE CAP
CIRCUIT SETTER BALANCE VALVE
MANUAL BUTTERFLY VALVE
RISE IN PIPE
DIRECTION OF FLOW
DROP IN PIPE
CAPPED PIPE
STEAM PIPING
CONDENSATE DRAIN PIPING
EXISTING CHILLED WATER SUPPLY PIPING
EXISTING CHILLED WATER RETURN PIPING
CHILLED WATER SUPPLY PIPING
CHILLED WATER RETURN PIPING
HEATING HOT WATER SUPPLY PIPING
HEATING HOT WATER RETURN PIPING
STM
CD
ECHWS
ECHWR
CHWS
CHWR
HWS
HWR
FD
DESCRIPTION
TEMPERATURE DIFFERENCE
TEMPERATURE
THERMOSTAT
TYPICAL
TOTAL STATIC PRESSURE
UNIT HEATER
UNLESS NOTED OTHERWISE
UP THROUGH ROOF
VOLT
VENTILATION VENT
VERTICAL
VENT THROUGH ROOF
WITH
WATT
WET BULB TEMPERATURE
WIRE MESH SCREEN
ZONE DAMPER
EXISTING TO REMAIN
EXISTING
NEW
REMOVE
RELOCATED
REMOVE & SAVE FOR RELOCATION
DEMAND CONTROL VENTILATION (CO2)
ABBREVIATION
TD
TEMP
TSTAT
TYP
TSP
UH
UNO
UTR
V
VENT
VERT
VTR
W/
W
WBT
WMS
ZD
(ETR)
(E)
(N)
(R)
(RL)
(RS)
(DCV)
HVAC ABBREVATIONS LEGNEDS AND SYMBOLS
MANUAL VOLUME DAMPER
WEIGHTED BAROMETRIC DAMPER
EQUIPMENT TAG, DESCRIPTION FC ROOM.
NUMBER D80, UNIT NUMBER 1
DETAIL REFERENCE, DETAIL 1,
SHEET NUMBER M -1
DOOR LOUVER MIN. 12"x12"
DOOR UNDERCUT MAX. 1"
SECTION REFERENCE, SECTION 1 SHEET M -1
DUCT MOUNTED SMOKE DETECTOR
CONSTRUCTION NOTE #1
DEMOLITION NOTE #1
POINT OF DISCONNECT
POINT OF CONNECTION BETWEEN NEW AND
EXISTING
FC
D80-1
1 M-1
DL
DU
1 M-1
1 1
SD
Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE-TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 -126
12" = 1'-0"
28-10-2024 15:21:54
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
M0.03
MECHANICAL
SYMBOLS AND
ABBREVIATIONS
Author
Checker
24162
07.24.24 AS-BUILT DRAWINGS
100% SD 10/28/2024
TAG
COIL SCHEDULE
MANUFACTURER
AND MODEL NO.
OUTDOOR
UNIT TYPE SERVING MAX.
CFM
ESP (")
W.G.
REFRIGERANT
OPERATING
WEIGHT
(LBS)
MOUNTING
DETAIL REMARKS
FC -1 DAIKIN
CHPTA4830C3 CU -1 DUCTED LEVEL -1 1550 0.38 R-32 78 - -
TYPE LIQUID
SIZE
SUCTION
SIZE
3/8" 7/8"
TAG
FURNACE SCHEDULE
MANUFACTURER
AND MODEL NO. AREA SERVED
MAX. CFM ESP (")
W.G.
FAN DATA MAX HEATING
CAPACITIES
MCA MOCP
ELECTRICAL
POWER
VOLTS PHASE Hz
OPERATING
WEIGHT
(LBS)
MOUNTING
DETAIL REMARKS
F-1 DAIKIN
DM80SC0805CU LEVEL -1 1550 0.5 80000 64000 11.6 15 115 1 60 127 - - INPUT
(Btu/hr)
OUTPUT
(Btu/hr)
NOTES:
NOTES:
1. PROVIDE DRAIN PAN. (KIT NUMBER: HHCMK01)
2. PROVIDE DRAIN PAN INSULATION KITS (KIT NUMBER: DPICX -CB)
3. PROVIDE ZONING ACCESSORY KIT. (KIT NUMBER: 0230K00007) SYMBOL
MANUFACTURER
AND MODEL NO. LOCATION TONNAGE
MCA MOCP
ELECTRICAL
POWER
VOLTS PHASE Hz
TYPE LIQUID
SIZE
REFRIGERANT
SUCTION
SIZE
OPERATING
WEIGHT
(LBS)
MOUNTING
DETAIL REMARKS
HEAT PUMP SCHEDULE
CU -1 DAIKIN
DC4SEA4810 4 40 208/240 1 60 R-32 3/8" 7/8" 72 - -25.18 SEER2 EER2
11.70 13.80 -
COOLING
CAPACITY
(Btu/hr)
46000
SYMBOL
EXHAUST FAN SCHEDULE
MANUFACTURER
AND MODEL NO. LOCATION ESP (")
W.G.
MOTOR
HP FAN
RPM VOLTS PHASE Hz
ELECTRICAL
WEIGHT
(LBS)
AIR FLOW
(CFM) DRIVE MOUNTING
DETAIL REMARKS
EF -1 GREENHECK
SQ -70 -VG BATH -1 75 DIRECT 1/15 1410 115 60 1 27 -0.3 - EF -2 GREENHECK
SQ -70 -VG
BATH -2
MCA MOCP
1.6 15
75 DIRECT 1/15 1410 115 60 1 27 -0.3 -1.6 15
Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE-TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 -126
12" = 1'-0"
28-10-2024 15:21:55
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
M0.04
MECHANICAL
SCHEDULES
Author
Checker
24162
07.24.24 AS-BUILT DRAWINGS
100% SD 10/28/2024
Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE-TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 -126
1/4" = 1'-0"
28-10-2024 15:21:55
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
MD2.01
MECHANICAL FIRST
FLOOR DEMOLITION
PLAN
Author
Checker
24162
07.24.24 AS-BUILT DRAWINGS
1/4" = 1'-0" 1 MECHANICAL FIRST FLOOR DEMOLITION PLAN
N
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
100% SD 10/28/2024
Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE-TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 -126
1/4" = 1'-0"
28-10-2024 15:21:55
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
MD2.02
MECHANICAL ROOF
DEMOLITION PLAN
Author
Checker
24162
07.24.24 AS-BUILT DRAWINGS
1/4" = 1'-0" 1 MECHANICAL ROOF DEMOLITION PLAN
N
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
100% SD 10/28/2024
T
NRD
NRD
NORTH PORCH
1014
LIVING ROOM
1004
DINING ROOM
1005
HALLWAY
1008
KITCHEN
1009
LAUNDRY/
PANTRY
1011
BATH-1
1012
BATH-2
1021
BEDROOM- 1
1036
CL
1037
OFFICE/
BEDROOM -3
1069
BEDROOM-2
1084
SG
150 CFM
DRYER
EXHAUST DUCT
UP TO ROOF
KITCHEN
EXHAUST DUCT
UP TO ROOF
RESTROOM
EXHAUST DUCT
UP TO ROOF
NON RETURN
BACK DRAUGHT
DAMPER
CU
1 F
1 OSA INTAKE
DUCT UP TO
ROOF
EF
1 EF
2 FURNACE
EXHAUST DUCT
UP TO ROOF
RESTROOM
EXHAUST DUCT
UP TO ROOF
FC
1 60 CFM
NON RETURN
BACK DRAUGHT
DAMPER
PLENUM
BOX
SG
130 CFM
SG
130 CFM
(TYP.2)
SG
180 CFM
SG
50 CFM
THERMOSTAT
SG
180 CFM
SG
200 CFM
Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE-TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 -126
1/4" = 1'-0"
28-10-2024 15:21:56
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
M2.01
MECHANICAL FIRST
FLOOR PLAN
Author
Checker
24162
07.24.24 AS-BUILT DRAWINGS
1/4" = 1'-0" 1 MECHANICAL FIRST FLOOR PLAN
N
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
100% SD 10/28/2024
DRYER EXHAUST DUCT
FROM THE BELOW
FLOOR CONNECT TO
ROOF CAP
KITCHEN EXHAUST DUCT
FROM THE BELOW
FLOOR CONNECT TO
ROOF CAP
RESTROOM EXHAUST
DUCT FROM THE BELOW
FLOOR CONNECT TO
ROOF CAP
RESTROOM EXHAUST
DUCT FROM THE BELOW
FLOOR CONNECT TO
ROOF CAP
OSA INTAKE DUCT
FROM THE BELOW
FLOOR CONNECT
TO ROOF CAP
FURNACE EXHAUST
DUCT FROM THE BELOW
FLOOR CONNECT TO
ROOF CAP
Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE-TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 -126
1/4" = 1'-0"
28-10-2024 15:21:56
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
M2.02
MECHANICAL ROOF
PLAN
Author
Checker
24162
07.24.24 AS-BUILT DRAWINGS
1/4" = 1'-0" 1 MECHANICAL ROOF PLAN
N
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
100% SD 10/28/2024
SHEET INDEX
20A/1P
20A/2P
20A/3P
30A/1P
30A/2P
30A/3P
40A/1P
40A/2P
40A/3P
50A/1P
50A/2P
50A/3P
60A/1P
60A/2P
60A/3P
70A/1P
70A/2P
70A/3P
80A/1P
80A/2P
80A/3P
2#12+1#12G CU 3/4"
2#12+1#12G CU 3/4"
3#12+1#12G CU 3/4"
2#10+1#10G CU 3/4"
2#10+1#10G CU 3/4"
3#10+1#10G CU 3/4"
2#8+1#10G CU 3/4"
2#8+1#10G CU 3/4"
3#8+1#10G CU 3/4"
2#6+1#8G CU 3/4"
2#6+1#8G CU 3/4"
3#6+1#8G CU 3/4"
2#4+1#8G CU 1"
2#4+1#8G CU 1"
3#4+1#8G CU 1"
2#4+1#8G CU 1"
2#4+1#8G CU 1"
3#4+1#8G CU 1"
2#3+1#8G CU 1"
2#3+1#8G CU 1"
3#3+1#8G CU 1.25"
54 FT
95 FT
109 FT
58 FT
100 FT
116 FT
80 FT
120 FT
139 FT
88 FT
152 FT
176 FT
101 FT
176 FT
204 FT
86 FT
149 FT
172 FT
94 FT
163 FT
189 FT
BRANCH CIRCUIT CONDUCTOR
SIZES
BRKR
AMPS
WIRE & COND. SIZE MAX
LENGTH
SEE PANEL SCHEDULES FOR BREAKER SIZES
NOTES:
1. CONTRACTOR TO FIELD MEASURE THE LENGTH FOR EACH
BRANCH CIRCUIT CONDUCTOR WIRING, UPSIZE THE CONDUCTOR
IS DISTANCE IS MORE THAN MAX ALLOWED. UPSIZE CONDUCTORS AS NEEDED TO KEEP THE TOTAL VOLTAGE DROP TO 5% OR LESS
2. TOTAL VOLTAGE DROP IS VOLTAGE DROP FROM SERVICE EQ TO
FURTHEST OUTLET
CONDUIT LINETYPES
ELECTRICAL CONDUIT ABOVE GROUND
ELECTRICAL CONDUIT BELOW GROUND , MINIMUM
COVER DEPTH PER CEC 300.5
CONDUIT/CABLE LINETYPES
1. ALL CONDUITS FOR SERVING UTILITY COMPANY SHALL BE PER
THEIR STANDARDS
2. USE EMT CONDUIT FOR FEEDERS AND BRANCH CIRCUIT
CONDUCTORS FOR CONCEALED WORK(NOT SUBJECT TO
PHYSICAL DAMAGE OR WET LOCATIONS)
3. CONTRACTOR MAY USE MC CABLES FOR FEEDERS IN LIEU OF
EMT CONDUITS, ONLY CONCEALED WORK. CABLES NOT ALLOWED
IN CONCRETE. CONTRACTOR MUST FOLLOW 2020NEC ARTICLE
334 FOR CABLE INSTALLATION
4. CONTRACTOR MAY USE TYPE NM,NMC CABLES FOR BRANCH
CIRCUIT CONDUCTORS, ONLY CONCEALED WORK. CABLES NOT
ALLOWED IN CONCRETE. CONTRACTOR MUST FOLLOW 2020NEC
ARTICLE 334 FOR CABLE INSTALLATION
5. USE PVC SCH 40 FOR UNDERGROUND CONDUITS
6. USE RIGID GALVANIZED STEEL(RGS) CONDUIT FOR EXTERIOR
EXPOSED CONDUITS
7. USE LIQUID TIGHT FLEX CONDUIT FOR CONNECTION BETWEEN A DISCONNECT SWITCH AND MEP EQUIPMENT. MAX 6FT DISTANCE
ALLOWED
SYMBOLS LEGEND(NOT ALL SYMBOLS ARE USED
RECEPTACLE SYMBOLS
120Vac, 20AMP SIMPLEX RECEPTACLE
120Vac, 20AMP DUPLEX RECEPTACLE
120Vac, 20AMP DUPLEX RECEPTACLE w/GROUND
FAULT CIRCUIT INTERRUPTER
120Vac, 20AMP WEATHER PROOF DUPLEX
RECEPTACLE
120Vac, 20AMP WEATHER PROOF DUPLEX
RECEPTACLE w/GROUND FAULT CIRCUIT
INTERRUPTER
120Vac, 20AMP DUPLEX RECEPTACLE w/DUAL USB
CHARGERS
120Vac, 20AMP SPLIT WIRED DUPLEX
CONTROLLED RECEPTACLE. BOTTOM
RECEPTACLE IS TO BE SWITCH CONTROLLED,
USE GRAY COLORED RECEPTACLE TO INDICATE
SWITCHED RECEPTACLE.
SPECIAL RECEPTACLE 'X - XXR' DESCRIBES NEMA
TYPE OF THE RECEPTACLE, REFER TO SPECIAL
RECEPTACLE SCHEDULE
FLOOR CLNG WALL
WP
WP
USB
SWITCHING SYMBOLS
MANUAL ON - OFF TOGGLE SWITCH
MANUAL ON - OFF 3 - WAY TOGGLE SWITCH
DIMMER SWITCH w/MANUAL OVERRIDE
3 - WAY DIMMER SWITCH w/MANUAL OVERRIDE
OCCUPANCY SENSOR SWITCH w/MANUAL
OVERRIDE
3 - WAY OCCUPANCY SENSOR SWITCH w/MANUAL
OVERRIDE
OCCUPANCY SENSOR+DIMMER SWITCH
w/MANUAL OVERRIDE
VACANCY SENSOR SWITCH w/MANUAL OVERRIDE
3 - WAY VACANCY SENSOR SWITCH w/MANUAL
OVERRIDE
HUMIDITY SENSOR SWITCH w/MANUAL OVERRIDE
HUMIDITY+OCCUPANCY SENSOR SWITCH
w/MANUAL OVERRIDE
MANUAL MOTOR STARTER/RATED SWITCH,
w/THERMAL OVERLOAD PROTECTION. NUMBER
OF POLES AS REQUIRED , RATING PER THE LOAD
IT SERVES
2 - SINGLE POLE SWITCHES GROUPED TOGETHER.
'a','b' DESIGNATES THE LOADS BEING SERVED
PILOT LIGHT SWTICH
KEYED SWITCH
COUNTER TOP GARBAGE DISPOSAL AIR SWITCH
S
S 3
S D
S 3D
S O
S 3O
S OD
S V
S 3V
S H
S HO
S M
S ab
S P
S K
WALL
COUNTER TOP
LIGHTING CONTROL SYMBOLS
WALL CEILING
OCCUPANCY + DAYLIGHT PHOTO SENSOR COMBO
OCCUPANCY SENSOR
DAYLIGHT PHOTO SENSOR
RELAY POWER PACK
OS
PS
OS
PS
OS OS
PS PS
RP RP
DATA/TELECOMM SYMBOLS
2 PORT DATA(LAN) OUTLET, RJ - 45 JACK
2 PORT TELEPHONE OUTLET, RJ - 14 JACK
1 PORT DATA+1 PORT TELEPHONE OUTLET
COMBO
1 PORT TV(TELEVISION COAXIAL CABLE OUTLET)
'F' TYPE CONNECTER
1 PORT DATA+1 PORT TV OUTLET
1 PORT PHONE+1 PORT TV OUTLET
DATA+PHONE+TV OUTLET(1 PORT EACH)
WALL
TV
TV
TV
TV
FIRE/SMOKE SYMBOLS
SMOKE DETECTOR
CARBON MONOXIDE DETECTOR
SMOKE + CARBON MONOXIDE DETECTOR COMBO
DUCT SMOKE DETECTOR
HEAT DETECTOR
CEILING
SD
CO
SD
DSD
HD
CO
ELECTRICAL EQUIPMENT SYMBOLS
FLUSH MOUNTED/ WALL RECESSED
PANELBOARD
SURFACE MOUNTED/ WALL RECESSED
PANELBOARD
LIGHTING CONTROL PANEL FLUSH MOUNTED
FLOOR
STANDING SWITCHBOARD
PAD MOUNTED TRANSFORMER T
1. THE CONTRACTOR SHALL USE SUFFICIENT BARRICADES AND TEMPORARY PROTECTION
DEVICES TO PREVENT PEDESTRIANS OR NON - AUTHORIZED PERSONNEL ACCESS TO ANY OPEN TRENCHES OR CONSTRUCTION ACTIVITY. THE CONTRACTOR SHALL ERECT A SAFETY
BARRICADE AT ALL OPEN TRENCHES, DITCHES, PITS, SUMPS, ETC FOR THE PROTECTION AND SAFETY OF THE PUBLIC. ALL TRENCHES OUTSIDE OF THE BARRICADE LIMITS SHALL BE BACKFILLED AND PAVED NOT LATER THAN 72 HOURS AFTER BEING OPENED. DURING THE TIME
THE TRENCHES ARE OPEN IN TRAFFIC AREAS, THE CONTRACTOR SHALL PROVIDE TRAFFIC PLATES. SAFETY BARRICADES SHALL BE PANELIZED CHAIN LINK FENCE. EACH FENCE PANEL SHALL BE 6FT TALL X 10FT WIDE WITH STAND AND TIED TOGETHER END TO END WITH A MINIMUM 8 - GAUGE WIRE. NO TRENCHES SHALL BE LOCATED OUTSIDE BARRICADES.
2. ALL FEEDERS AND BRANCH CIRCUITS SHALL CARRY A GROUND WIRE, SIZED AS PER C.E.C.
ARTICLE 250.
3. PRIOR TO PULLING ANY CONDUCTORS, CLEAN AND MANDREL ALL CONDUITS.
4. CONTRACTOR SHALL INSTALL EQUIPMENTS PER ADA (AMERICAN DISABILITIES ACT)
REQUIREMENTS, WHERE APPLICABLE
5. ALL EXTERIOR,OUTDOOR ELECTRICAL EQUIPMENT SHALL BE OF NEMA - 3R TYPE, SHALL BE PROVIDED WITH WEATHERPROOF COVER, AND SHALL BE VANDAL PROOF/RESISTANT.
6. THE ENGINEER HAS PREPARED THESE DOCUMENTS ONLY FOR IMPROVEMENTS SPECIFIED,
DETAILED OR SHOWN AS NEW WORK, AND ASSUMES NO RESPONSIBILITY FOR OTHER CONSTRUCTION, MATERIAL OR EQUIPMENT NOTED AS "PROVIDED BY OTHERS".
7. DEMOLITION AND/OR REMOVAL OF ELECTRICAL EQUIPMENT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. ALL REMOVED EQUIPMENT NOT TO BE REUSED SHALL BE RETURNED TO OWNER OR AS DIRECTED BY THE OWNER INSPECTOR.
8. ALL JUNCTION BOX COVER PLATES FOR BRANCH CIRCUIT SYSTEM SHALL BE CLEARLY MARKED
WITH PERMANENT INK FELT PEN IDENTIFYING THE BRANCH CIRCUIT (BOTH PANEL NUMBER AND CIRCUIT NUMBER) CONTAINED IN THE BOX.
9. THE CONTRACTOR SHALL MAINTAIN THE UNIFORMITY AND CONTINUITY OF THE GROUNDING SYSTEM IN ALL CONDUITS/RACEWAYS.
10. TEST AND TURN ON THE ENTIRE SYSTEM TO DEMONSTRATE TO THE OWNER THAT THE ELECTRICAL COMPONENTS AND SPECIAL SYSTEMS ARE COMPLETE AND FUNCTION PROPERLY.
MAKE NECESSARY CORRECTIONS AND LEAVE SYSTEMS READY FOR OPERATION.
11. DRAWINGS ARE PROVIDED FOR GENERAL COMPLIANCE OF LOCAL, STATE CODES AND ARE ESSENTIALLY DIAGRAMMATIC. DRAWINGS ARE NOT TO BE USED AS SHOP DRAWINGS, AS THEY DO NOT SHOW EVERY REQUIRED COMPONENT. CONTRACTOR MUST FOLLOW MANUFACTURER
INSTALLATION MANUAL AND PROVIDE ALL REQUIRED ITEMS FOR A FULLY OPERATIONAL SYSTEM. ENGINEER DOES NOT TAKE ANY RESPONSIBILITIES FOR SYSTEM FAILURES AND ADDED FOR ITEMS THAT WERE NOT INCORPORATED AS REQUIRED BY MANUFACTURER.
12. PROVIDE HANGERS, SUPPORTS, SEISMIC RESTRAINTS AND/ OR BRACING FOR ALL EQUIPMENT,
CONDUIT, AND LIGHTING FIXTURES TO SUSTAIN VERTICAL LOADS AND RESIST HORIZONTAL FORCES IN ANY DIRECTION TO COMPLY WITH 2016 EDITION OF TITLE 24, PART 2, CALIFORNIA BUILDING CODE, CHAPTER 16, TABLE 16A AND ASSOCIATED NOTES.
13. PER CEC 300 - 21, "OPENINGS AROUND ELECTRICAL PENETRATIONS THROUGH FIRE - RESISTANT -
RATED WALLS, PARTITIONS, FLOORS, CEILINGS SHALL BE FIRESTOPPED USING APPROVED METHODS TO MAINTAIN THE FIRE RESISTANCE RATING."
14. ALL CONDUCTORS FOR FEEDERS AND BRANCH CIRCUITS SHALL BE COPPER, TYPE THWN/THHN, RATED FOR 75°C. SIZES #12 AWG MAY BE SOLID OR STRANDED, #10 AND LARGER SHALL BE STRANDED. PROVIDE 75°C RATED AND APPROVED TERMINATION FOR ALL CONDUCTORS.
15. ALL ELECTRICAL WORK SHALL BE PER THE APPLICABLE CEC CODE. CONTRACTOR SHALL
INCLUDE IN HIS BID ALL REQUIRED LABOR, MATERIAL, EXPERTISE AND QUALIFIED PERSONNEL TO COMPLETELY INSTALL IN A CODE COMPLIANT MANNER, ALL WORK SHOWN ON THE PLANS.
16. WHEN THERE ARE DISCREPANCIES BETWEEN CONTRACT DOCUMENTS (DRAWINGS), OBTAIN CLARIFICATION FROM THE ENGINEER PRIOR TO BID. FOR BIDDING PURPOSES THE MORE STRINGENT OR MORE EXPENSIVE REQUIREMENT(S) SHALL APPLY.
17. DURING CONSTRUCTION, THE CONTRACTOR SHALL MAINTAIN A DAILY RECORD OF ALL DEVIATIONS FROM THE BID DRAWINGS. ALL DIMENSIONS AND OTHER INFORMATION
NECESSARY TO COMPLETELY EXPLAIN AND LOCATE ALL ELEMENTS OF THESE DEVIATIONS SHALL BE RECORDED. UPON COMPLETION OF WORK, THE CONTRACTOR SHALL SUBMIT TO THE OWNER, ONE COMPLETE SET OF REPRODUCIBLE DRAWINGS CORRECTED TO REFLECT "AS - BUILT" CONDITIONS OF THE WORK.
18. ANY SUBMITTALS FOR EQUIPMENT DIFFERENT FROM THE SPECIFIED ITEMS SHOWN ON THE PLANS SHALL BE ACCOMPANIED BY CUT SHEETS FOR THE ORIGINAL SPECIFIED ITEM(S).
SUBMITTALS WITHOUT THE SPECIFIED CUT SHEETS WILL BE REJECTED AS INCOMPLETE.
19. "PROVIDE" SHALL BE DEFINED AS: FURNISH AND INSTALL.
20. ALL DIMENSIONS AND ELEVATIONS SHALL BE CHECKED AND VERIFIED ON THE SITE BY THE GENERAL CONTRACTOR AND EACH SUBCONTRACTOR BEFORE THE WORK BEGINS. ALL
PERCEIVED ERRORS, OMISSIONS AND DISCREPANCIES SHALL BE BROUGHT TO THE ENGINEER'S ATTENTION BEFORE CONSTRUCTION BEGINS.
OVAL MUST BE OBTAINED FROM THE OWNER PRIOR TO THE STARTING OF THE WORK
GENERAL NOTES
21. PROVIDE ELECTRICAL PANELS WITH TYPEWRITTEN "AS - BUILT" PANEL SCHEDULE. PANEL SCHEDULE SHALL INCLUDE LOCATION, QUANTITY AND TYPE OF DEVICES SERVED. PANEL
SCHEDULE SHALL BE REVISED AS REQUIRED TO REFLECT REMOVED OR DEMOLISHED CIRCUITS.
22. THE SEISMIC ANCHORAGE OF ELECTRICAL EQUIPMENT SHALL CONFORM TO C.C.R. 2007 CHAPTER 16 AND ASCE 7 - 05 CHAPTER 13.
23. CONTRACTOR SHALL SUBMIT A CALCULATIONS AND DETAILS FOR APPROVAL WHEN USING AN
INSTALLATION METHOD NOT COVERED UNDER ANY OF THE STRUCTURAL DRAWINGS STANDARD DETAILS.
24. WIRING FOR ALL LOW VOLTAGE SYSTEMS SHALL BE ENCLOSED IN CONDUIT AND/OR RACEWAY.
25. ALL RACEWAYS INSIDE OF BUILDING SHALL BE CONCEALED. INCLUDE ALL REQUIRED
DEMOLITION, CUTTING, PATCHING AND FINISH TO MATCH EXISTING INSTALLATION AS REQUIRED TO INSTALL NEW CONDUIT AND RACEWAYS IN EXISTING BUILDING.
26. EXPOSED AND CONDUITS ABOVE T - BAR CEILINGS SHALL BE INSTALLED PARALLEL TO OR AT RIGHT ANGLES TO EXISTING BEAMS OR WALLS. EXPOSED CONDUITS UP TO 7' - 0" ABOVE FINISH FLOOR SHALL BE RIGID GALVANIZED STEEL AND ABOVE 7' - 0" MAY BE EMT.
27. PROVIDE ELECTRICAL PANELS WITH ENGRAVED NAMEPLATE ON OUTSIDE OF PANEL ABOVE DOOR OPENING.
28. SUPPORT CONDUIT 2 - 1/2 INCH TRADE SIZE OR SMALLER WITH U.L. LISTED CLAMPS AND HANGERS IN ACCORDANCE WITH SMACNA STANDARDS.
29. EQUIPMENT SPECIFIED ON THESE DRAWING ARE BASIS OF DESIGN
30. CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR ALL ADDITIONAL DESIGN AND
CONSTRUCTION COSTS INCURRED BY THE USE OF ANY PRODUCT OTHER THAN THE BASIS OF DESIGN.
31. PROVIDE BREAKERS TIES TO BREAKERS FEEDING MULTI WIRE RUNS.
32. THESE PLANS ARE DIAGRAMMATIC, CONDUIT EXACT ROUTING, BOXES, FASTENERS, ETC. ARE
CONSIDERED AS PART OF THE MEANS AND METHODS THAT THE CONTRACTOR IS USING TO
PROVIDE AN OPERABLE AND APPROVED INSTALLATION
33. 110.2 APPROVAL: ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED OR CERTIFIED BY A
NATIONALLY RECOGNIZED TESTING LABORATORY ACCREDITED BY THE UNITED STATES
OCCUPATIONAL SAFETY HEALTH ADMINISTRATION
34. 130.5(c) VOLTAGE DROP: THE MAXIMUM COMBINED VOLTAGE DROP ON BOTH INSTALLED
FEEDER CONDUCTORS AND BRANCH CIRCUIT CONDUCTORS TO THE FARTHEST CONNECTED LOAD OR OUTLET SHALL NOT EXCEED 5 PERCENT. CONTRACTOR TO UPSIZE WIRING AS
NEEDED TO MEET THIS REQUIREMENT
35. CONTRACTOR MUST REVIEW DRAWINGS FOR ALL TRADES IN ADDITION TO ELECTRICAL DRAWINGS AND PROVIDE ELECTRICAL WORK AS REQUIRED PER DRAWINGS. ENGINEER DOES
NOT ASSUME ANY LIABILITY FOR ADDED COSTS FOR ELECTRICAL WORK THAT WAS MISSED/NOT
CONSIDERED BY CONTRACTOR DURING THE BIDDING FROM ANY OTHER TRADE DRAWINGS
36. EXTREME CAUTION IN EXCAVATING AND TRENCHING ON THIS SITE TO AVOID EXISTING DUCTS, PIPING OR CONDUITS, ETC., AND TO PREVENT HAZARD TO PERSONNEL AND/OR DAMAGE TO
EXISTING UNDERGROUND UTILITIES OR STRUCTURES WHETHER OR NOT SHOWN AND INSTALLED BY ANY OTHER CONTRACTS. THE ENGINEER IS NOT RESPONSIBLE FOR THE
LOCATION OF UNDERGROUND UTILITIES OR STRUCTURES WHETHER OR NOT SHOWN OR DETAILED AND INSTALLED BY ANY OTHER CONTRACTS. THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ENGINEER SHOULD SUCH UNIDENTIFIED CONDITIONS BE DISCOVERED.
37. PROVIDE PROTECTION FROM PHYSICAL DAMAGE FOR SWITCHBOARDS, PANEL BOARDS AND ALL
OTHER FREESTANDING ELECTRICAL EQUIPMENT USING BOLLARDS OR OTHER APPROVED
MEANS, WHERE THEY ARE INSTALLED OUTDOORS OR IN VEHICULAR AREAS
38. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO INSTALL ALL EQUIPMENT WITH CLEARANCES AS REQUIRED PER CODE CEC 110.26.
39. ANY CHANGES REQUIRED IN FIELD OR ANY CHANGES PROPOSED BY CONTRACTORS MUST BE REVIEWED AND APPROVED IN WRITING FROM THE ENGINEER OR RECORD. ENGINEER HOLDS
NO RESPONSIBILITY OR LIABILITY FOR ANY CHANGES OCCURRED INFIELD WITHOUT REVIEW AND APPROVAL. COST APPROVAL MUST BE OBTAINED FROM THE OWNER PRIOR TO THE
STARTING OF THE WORK
40. GENERAL ABBREVIATIONS
AFF ABOVE FINISHED FLOOR
A OR AMP AMPERES
AF AMPERE FUSE/FRAME
AHJ AUTHORITY HAVING JURISDICTION
AS AMPERE SWITCH
AT AMPERE TRIP
AIC AMPERE INTERRUPTING CAPACITY
ATS AUTOMATIC TRANSFER SWITCH
BKR BREAKER
BRKR BRAEKER
BLDG BUILDING
C CONDUIT
CKT CIRCUIT
CB CIRCUIT BREAKER
CATV CABLE TELEVISION
CLG CEILING
CLNG CEILING
COMM COMMUNICATION
CONT. CONTINUE/CONTINUOUS
CT CURRENT TRANSFORMER
CU COPPER
DB DIRECTLY BURIED
DISC DISCONNECT
DIST DISTRIBUTION
(E) EXISTING
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
FLA FULL LOAD AMPS
FACP FIRE ALARM CONTROL PANEL
FATC FIRE ALARM TERMINAL CABINET
FV FIELD VERIFY
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GRD/GND/G GROUND
HP HORSEPOWER/HEAT PUMP
IG ISOLATED GROUND
IDF INTERMEDIATE DISTRIBUTION FRAME
J/JB/J - BOX JUNCTION BOX
KA KILO AMPS
LCL LONG CONTINUOUS LOAD
LRA LOCKED ROTOR AMPS
LTG LIGHTING
LDF LOCAL DISTRIBUTION FRAME
MDF MAIN DISTRIBUTION FRAME
MH MOUNTING HEIGHT
MC METAL CLAD CABLE
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCCB MOLDED CASE CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MLO MAIN LUG ONLY
MOCP MAXIMUM OVER CURRENT PROTECTION
MTS MANUAL TRANSFER SWITCH
MTG MOUNTING
(N) NEW
PH OR ∅ PHASE
PNL PANEL
PRI PRIMARY
PT POTENTIAL TRANSFORMER
PV PHOTOVOLTAIC
REV REVISION/REVISED
RECP RECEPTACLE
RGS RIGID GALVANIZED STEEL CONDUIT
RLA RATED LOAD AMPS
SCA SHORT CIRCUIT AMPS
SFD SMOKE FIRE DAMPER
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SW SWITCH
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSER
TEMP TEMPORARY
TYP. TYPICAL
UFER UFER GROUND
UG UNDERGROUND
UON UNLESS OTHERWISE NOTES
VF VERIFY IN FIELD
MISC SYMBOLS
SURFACE MOUNTED PUSH BUTTON DOOR BELL
SWITCH
DOOR BELL CHIME+24V TRANSFORMER
COMBINATION
EXHAUST FAN, FAN SPECS, DIMENSIONS AND ALL
OTHER REQUIREMENTS PER MECHANICAL PLAN
THERMOSTAT, PROVIDE 3/4"C FROM THERMOSTAT
TO EACH RESPECTIVE INDOOR/OUT DOOR UNIT
DB
T
NOTES/TAGS SYMBOL
A - 3
A - 3,5
A - 3,5,7
HOMERUN TO ELECTRICAL, 'A' INDICATES PANEL
AND '3' INDICATES SINGLE POLE CIRCUIT, '3,5'
INDICATES TWO POLE CIRCUIT, '3,5,7' INDICATES
THREE POLE CIRCUIT, SEE PANEL SCHEDULE AND
FLOOR PLANS EXACT CIRCUIT NUMBERS
PROVIDE WIRE AND CONDUIT SIZING PER BRANCH
CIRCUIT CONDUCTOR SCHEDULES PROVIDED ON
THE SAME SHEET
DESIGN PLANS KEYNOTE TAG
#
SCOPE OF WORK:
1. PROVIDE 3/4" CONDUIT FOR EACH OUTLET, TERMINATE CONDUIT BACK
TO CATV/TELECOMM CABINET
2. ELECTRICAL DRAWINGS ONLY INDICATE DATA OUTLETS AND CONDUIT REQUIREMENTS. ALL OTHER HEAD END EQ., CABLING SHALL BE BY OTHERS
Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE - TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 - 126
12" = 1' - 0"
10/28/2024 4:27:50 PM
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
E0.01
ELECTRICAL FRONT
SHEET
Author
Checker
24162
07.24.24 AS - BUILT DRAWINGS
E2.03 ELECTRICAL FIRST FLOOR PLAN-DETACHED
GARAGE
E0.01 ELECTRICAL FRONT SHEET
E0.02 ELECTRICAL SINGLE LINE DIAGRAM
E1.01 ELECTRICAL SITE PLAN
E2.01 ELECTRICAL FIRST FLOOR POWER
PLAN-MAIN HOUSE
E2.02 ELECTRICAL FIRST FLOOR LIGHTING
PLAN-MAIN HOUSE
E7.01 ELECTRICAL DETAILS
E7.02 ELECTRICAL DETAILS
SOUTHERN
CALIFORNIA
TRANSFORMER PAD
WITH SLAB BOX
M
METER
SECTION
UG PULL
SECTION
2P
200A
22KA
2P
40A
2P
80A
DISTRIBUTION BREAKERS
SEE PANEL SCHEDULE
N
G
BUSBAR
OR IBT
CA
TV
TE
LE
GRD
ELECTRODES
200A, 120,240V, 1PH, 3W
UG/OH METER PANEL COMBO
NEMA - 3R, 22KAIC, SERIES RATED
(1)4"UGC
SECONDARY
SERVICE CONDUIT
FIELD VERIFY
EXACT LOCATION
OF THE
TRANSFORMER
3/4"C - 3/0 CU
3/4" - 3/0CU
3/0CU
1 BUSSED CONNECTION
I f =
10,000A(UTILITY
FAULT CURRENT)
2 3
PANEL B
120/240V,
1PH, 3W
1.5"UGC- w/3#1AL LINE+
1#6AL GRD
ELECTRICAL LOAD CALCULATION (CEC 220 PART 3)
FLOOR AREA(LARGEST UNIT) 2500 SQFT
GENERAL LOAD
GENERAL LTG & RECP. (@ 3VA PER SQFT)(CONT. LOAD) 9375 VA 2xSMALL APPLIANCE(@1500 VA EACH) 3000 VA
LAUNDRY CIRCUIT 1500 VA
SUBTOTAL GENERAL LOAD VA(CEC 220.52 & 220.42) 13875 VA
APPLIANCE LOAD
GARBAGE DISPOSAL 1000 VA
DISHWASHER 1000 VA
MICROWAVE+HOOD 1000 VA
ELECTRIC RANGE 8000 VA
ELECTRIC DRYER 5000 VA
ELECTRIC WATER HEATER 9600 VA
EV CHARGER(@7680VAx1.25)(CONT. LOAD) 9600 VA
SUBTOTAL APPLIANCE LOAD (CEC 220.53) 35200 VA
SUBTOAL LOAD FIRST 10KVA@100% 10000 VA
REMAINDER @40% 15630 VA
HEAT PUMP 9600 VA
EX FANS 100 VA
TOTAL UNIT FEEDER DEMAND LOAD 35430 VA
UNIT FEEDER DEMAND AMPS @ 240V,1PH,3W 147.625 AMP
REQUIRED SERVICE - 200A, 120/240, 1PH, 3W
Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE - TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 - 126
12" = 1' - 0"
10/28/2024 4:27:50 PM
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
E0.02
ELECTRICAL SINGLE
LINE DIAGRAM
Author
Checker
24162
07.24.24 AS - BUILT DRAWINGS
12" = 1' - 0" 1 ELECTRICAL SINGLE LINE DIAGRAM
12" = 1' - 0" 2 ELECTRICAL SERVICE LOAD CALCULATION
1 CONTRACTOR TO VERIFY THE CONDUIT REQUIREMENTS WITH
UTILITY COMPANY PRIOR TO BEGGINING OF WORK
2 FAULT CURRENT IS PROVIDED PER SOUTHERN CALIFORNIA
EDISON ELECTRICAL SERVICE REQUIREMENTS BOOK
SECTION 13-13.1
3 PROVIDE PV BACKFEED BREAKER AT THE OPPOSITE END OF
THE UTILITY FEED, MAXIMUM SIZE TO BE 40A/2P,
COORDINATE THE EXACT SIZE OF THE BREAKER WITH PV
CONTRACTOR IN FIELD
GENERAL NOTES
1. ALL ITEMS SHOWN HERE ARE NEW(N) UNLESS OTHERWISE
SHOWN AS EXISTING (E)
2. LENGTH OF FEEDERS SHOWN ON SINGLE LINE DIAGRAM
ARE NOT TO BE USED FOR CONSTRUCTION OR BIDDING
PURPOSE, CONTRACTOR TO VERIFY ACTUAL LENGTH
REQUIRED.
3. ALL EQUIPMENT SHALL BE LISTED AND LABELED BY A
NATIONALLY RECOGNIZED TESTING LABORATORY AND
SHALL BE INSTALLED AS PER LISTING OR LABELING.
4. ALL DEVICES AND TERMINALS SHALL BE RATED FOR 75°C
AND SHALL BE TORQUED TO MANUFACTURERS LISTED
SPECIFICATIONS.
5. ALL RACEWAYS SHALL CONTAIN A CODE - SIZED
(CEC - 250.122), INSULATED, GREEN, COPPER EQUIPMENT
GROUNDING CONDUCTOR AND SHALL BE BONDED TO THE
METALLIC COMPONENTS OF THE RACEWAY SYSTEM.
6. ALL CONDUCTORS TO BE COPPER OR ALUMINUM, AS
NOTED, TYPE THWN/THHN, ASSUME COPPER
CONDUCTORS IF MATERIAL TYPE IS NOT FOUND ON PLANS
OR PROVIDE A WRITTEN RFI/RFC PRIOR TO BIDDING. 'CU'
FOR COPPER AND 'AL' FOR ALUMINIUM
7. ALL CONDUCTORS FOR FEEDERS AND BRANCH CIRCUITS
SHALL BE COPPER OR ALUMINUM AS NOTED, TYPE
THWN/THHN, RATED FOR 75°C. SIZES #12 AWG MAY BE
SOLID OR STRANDED, #10 AND LARGER SHALL BE
STRANDED. PROVIDE 75°C RATED AND APPROVED
TERMINATION FOR ALL CONDUCTORS.
8. EQUIPMENT/ DEVICES AND TERMINATIONS ARE RATED
FOR 75°C AND FOR USE WITH 75° RATED CONDUCTORS.
9. BREAKER LUGS SHALL BE LARGE ENOUGH TO
ACCOMMODATE CONDUCTORS. IN THE EVENT WHERE
CONDUCTORS ARE LARGER THAN BREAKER LUGS
CONTRACTOR MAY ALSO USE A 5FT SECTION OF SMALL
SIZE CONDUCTORS TO CONNECT TO BREAKERS. IN NO
CASE CONDUCTORS SHALL BE SMALLER THAN THE
AMPACITIES ALLOWED IN CEC TABLE 310.15(B)(16).
PROVIDE ADDITIONAL J - BOX FOR THE SPLICES
10. CEC - 110.22(C) EQUIPMENT ENCLOSURES FOR CIRCUIT
BREAKERS AND FUSES APPLIED IN COMPLIANCE WITH THE
SERIES RATINGS MARKED BY MFR. SHALL BE LEGIBLY
MARKED IN THE FIELD TO INDICATE THE EQUIPMENT HAS
BEEN APPLIED WITH SERIES RATING. THE MARKING SHALL
MEET THE REQUIREMENTS OF CE 110.21(B) AND SHALL BE
READILY VISIBLE AND STATE FOLLOWING :
11. CAUTION SERIES COMBINATION SYSTEM RATED ----
AMPERES. IDENTIFIED REPLACEMENT COMPONENTS
REQUIRED
12. LUGS/TERMINALS SHALL BE RATED FOR BOTH COPPER
AND ALUMINUM
13. CONTRACTOR MUST OBTAIN FINAL DESIGN DRAWINGS
FROM UTILITY CONPANIES(POWER, TELECOMM, CATV,
INTERNET SERVICE PROVIDERS) AND COORDINATE ALL
THE INSTALLATION WORK RELATED TO UTILITY
COMPANIES INCLUDING BUT NOT LIMITED TO CONDUITS,
CONDUIT ROUTING, MATERIAL, EQUIPMENT STRUCTURES,
CONCRETE PADs ETC WITH UTILITY COMPANIES AND
INSTALL PER UTILITY FINAL DESIGN DRAWINGS
KEYNOTES #
4 - PROVIDE SURGE PROTECTION DEVICE FOR THE PANEL
3 - PANEL SIZING IS DONE PER UNIT FEEDER LOAD CALCS, PROVIDED ON SINGLE LINE DIAGRAM AND LOAD CALCULATION SHEET 2 - BREAKER FEEDING SMOKE+CARBON MONOXIDE DET. TO BE PROVIDED WITH RED LOCKON DEVICE 1 - PROVIDE AFCI BREAKER+1ST OUTLET IN THE BRANCH CIRCUIT TO HAVE AFCI PROTECTION, MARK THE FIRST OUTLET BOX TO INDICATE THAT IT IS THE FIRST OUTLET IN THE BRANCH CIRCUIT PER CEC210.12(A)(2)
CIRCUIT KEYNOTES(NOT ALL NOTES ARE USED) :
TOTAL DEMAND CURRENT: 138.8 A
TOTAL CURRENT: 138.8 A
TOTAL DEMAND LOAD: 33300 VA
TOTAL LOAD: 33300 VA
LONG CONT. LOAD 1.25 0 VA
DEMAND LOADS DEMAND FACTOR DEMAND VA TOTALS
LOAD SUMMARY
Total Amps: 136.7 A 140.8 A
Total Load: 16.40 kVA 16.90 kVA
41 -- -- -- 42 -- -- --
39 -- 2 -- SURGE PROTECTIVE DEVICE(NOTE 4) 40 --
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
-- -- -- 17 -- -- -- 3600 18
15 PANEL B 80 A 2 5600 16
-- -- -- 13 -- -- -- 4000 2500 -- -- -- 14 -- -- --
● 11 KITCHEN RANGE 50 A 2 4000 2500 2 30 A ELECTRIC DRYER 12 ● ● 1 1 ● ● 9 GARBAGE DISPOSAL 20 A 1 1000 1000 1 20 A MICROWAVE+HOOD 10 ● 1 ● ● 7 LAUNDRY CIRCUIT(WASHER) 20 A 1 1500 900 1 20 A BED-3/OFFICE RECP.+LTG 8 ● 1 1 ● ● 5 DISHWASHER 20 A 1 1000 900 1 20 A BED-2 RECP.+LTG 6 ● 1 1 ● 3 SMALL APPLIANCES-2(KITCHEN+REF.) 20 A 1 1500 900 1 20 A BED-1 RECP.+LTG 4 ● 1 1 ● 1 SMALL APPLIANCES-1(KITCHEN+DINNING) 20 A 1 1500 900 1 20 A LIVING RM RECP.+LTG 2 ● 1 K
E
Y
A
F
C
I
G
F
C
I
C
K
T
LOAD DESCRIPTION BRKR
AMPS
BRKR
P A B BRKR
P
BRKR
AMPS LOAD DESCRIPTION
C
K
T
G
F
C
I
A
F
C
I
K
E
Y
PLUG IN BREAKERS SCCR/KAIC :
FEED : SERIES RATED PANEL TO 22KA BUS :
LOCATION : DWELLING UNIT BRANCH BREAKER AIC RATING 10KA WIRE : 3 FED FROM : UTILITY PHASE : 1
ENCLOSURE : VOLTS : 120/240 Single
MOUNTING : MAIN :
PANEL A
4 - PROVIDE SURGE PROTECTION DEVICE FOR THE PANEL
3 - PANEL SIZING IS DONE PER UNIT FEEDER LOAD CALCS, PROVIDED ON SINGLE LINE DIAGRAM AND LOAD CALCULATION SHEET 2 - BREAKER FEEDING SMOKE+CARBON MONOXIDE DET. TO BE PROVIDED WITH RED LOCKON DEVICE 1 - PROVIDE AFCI BREAKER+1ST OUTLET IN THE BRANCH CIRCUIT TO HAVE AFCI PROTECTION, MARK THE FIRST OUTLET BOX TO INDICATE THAT IT IS THE FIRST OUTLET IN THE BRANCH CIRCUIT PER CEC210.12(A)(2)
CIRCUIT KEYNOTES(NOT ALL NOTES ARE USED) :
TOTAL DEMAND CURRENT: 45.8 A
TOTAL CURRENT: 38.3 A
TOTAL DEMAND LOAD: 11000 VA
TOTAL LOAD: 9200 VA
LONG CONT. LOAD 1.25 1800 VA
DEMAND LOADS DEMAND FACTOR DEMAND VA TOTALS
LOAD SUMMARY
Total Amps: 46.7 A 30 A
Total Load: 5.60 kVA 3.60 kVA
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
-- -- -- 5 -- -- -- 3600 6
3 EV CAPABLE 40 A 2 3600 4
1 GARAGE DOOR OPENER-1 20 A 1 1000 1000 1 20 A GARAGE DOOR OPENER-2 2 K
E
Y
A
F
C
I
G
F
C
I
C
K
T
LOAD DESCRIPTION BRKR
AMPS
BRKR
P A B BRKR
P
BRKR
AMPS LOAD DESCRIPTION
C
K
T
G
F
C
I
A
F
C
I
K
E
Y
PLUG IN BREAKERS SCCR/KAIC :
FEED : SERIES RATED PANEL TO 22KA BUS :
LOCATION : DWELLING UNIT BRANCH BREAKER AIC RATING 10KA WIRE : 3 FED FROM : UTILITY PHASE : 1
ENCLOSURE : VOLTS : 120/240 Single
MOUNTING : MAIN :
PANEL B
S
DB
WP
NORTH PORCH
1014
LIVING ROOM
1004
DINING ROOM
1005
HALLWAY
1008
KITCHEN
1009
PORCH
1010
LAUNDRY/
PANTRY
1011
BATH - 1
1012
BATH - 2
1021
BEDROOM - 1
1036
CL
1037
OFFICE/
BEDROOM - 3
1069
BEDROOM - 2
1084
PANEL A
TELECOMM/CATV CABINET
NEMA - 3R, WEATHERPROOF
SIZE PER LV UTILITY COMPANY
Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE - TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 - 126
1/4" = 1' - 0"
10/28/2024 4:27:51 PM
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
E2.01
ELECTRICAL FIRST
FLOOR POWER
PLAN - MAIN HOUSE
Author
Checker
24162
07.24.24 AS - BUILT DRAWINGS
1/4" = 1' - 0" 1 ELECTRICAL FIRST FLOOR POWER PLAN - MAIN HOUSE N
0 2' 4' 8'
SCALE: 1/4" = 1' - 0"
GENERAL NOTES
1. MARK ALL EXPOSED JUNCTION BOXES, RECEPTACLES
WITH PANEL AND CIRCUIT NUMBERS
2. PROVIDE 3/4" C FROM FAN COIL TO ASSOCIATED
THERMOSTATS AND OUTDOOR UNITS FOR CONTROLS
PURPOSE
3. ALL J - BOXES, CONTROLLERS AND OTHER ELECT. EQ.
LOCATED IN CEILING OR CAVITIES SHALL BE ACCESSIBLE
BY AN ACCESS PANEL OR OTHER APPROVED MEANS.
FIELD VERIFY THE REQUIRED SIZE OF THE ACCESS
PANELS
4. ALL OUTDOOR RECEPTACLES SHALL BE GFCI TYPE AND
SHALL BE PROVIDED WITH WEATHER PROTECTIVE
COVERS
5. ALL GENERAL PURPOSE RECEPTACLES SHALL BE PLACED
AT +18" AFF AND SWITCHES SHALL BE PLACED AT +48" AFF
U.O.N. CONTRACTOR SHALL MOUNT RECEPTACLES ABOVE
FURNITURE WHEREVER REQUIRED
6. REFER TO MECHANICAL PLANS FOR THE EXACT LOCATION
OF EXHAUST FANS. FAN COIL UNITS, THERMOSTATS AND
ALL OTHER MECHANICAL EQ
7. PROVIDE GFCI RECEPTACLES FOR FOLLOWING
LOCATIONS :
BATHROOMS, GARAGES, OUTDOORS, CRAWL - SPACES,
UNFINISHED PARTITIONS AND ALL LOCATIONS THAT HAVE
A FLOOR LOCATED AT OR BELOW GRADE LEVEL NOT
INTENDED AS HABITABLE ROOMS AND LIMITED TO
STORAGE AREAS, WORK AREAS, ALL KITCHEN
COUNTERTOPS, WITHIN 6FT. OF LAUNDRY AND BAR SINKS
AND AREAS OF SIMILAR USE, DISHWASHERS
8. RECEPTACLES AT KITCHEN COUNTERTOPS SHALL BE
PLACED SO THAT NO PORTION OF THE COUNTERTOP IS
FURTHER THAN 24" FROM AN OUTLET
9. WALL OUTLETS IN HABITABLE ROOMS SHALL BE SPACED
SO THAT NO POINT ALONG THE FLOOR LINE IN ANY WALL
SPACES IS MORE THAN 6' FROM AN OUTLET
10. ALL 120 - VOLT, 15 OR 20 AMP RECEPTACLES TO BE LISTED AS TAMPER - RESISTANT PER CEC SECTION 210.52 AND
406.11
11. LAYOUT OF THE HVAC AND PLUMBING EQUIPMENT IS
SHOWN FOR REFERENCE AND FOR POWER
REQUIREMENTS, EXACT EQUIPMENT LAYOUT SHALL BE BY
EACH INDIVIDUAL DISPLINE CONTRACTOR/ENGINEER,
ELECTRICAL CONTRACTOR TO FIELD COORDINATE EXACT
LOCATIONS AND RELOCATE ANY ELECTRICAL EQ. AS
NEEDED
12. REFER TO FRONT SHEET FOR BRANCH CIRCUIT
CONDUCTOR AND CONDUIT SIZING WHEREVER NOT
PROVIDED ON THE RESPECTIVE PLAN SHEET
13. WIRING FOR POWER PLANS IS SHOWN FOR
DIAGRAMMATIC PURPOSE AND ONLY INDICATES
CIRCUITING , CONTRACTOR MUST FIELD DETERMINE THE
MOST APPROPRIATE MEANS AND METHOD OF WIRING AND
PROVIDE ALL REQUIRED ACCESSORIES FOR A FULLY
OPERATIONAL SYSTEM
KEYNOTES #
WP
WP WP
WP
NORTH PORCH
1014
BEDROOM - 1
1036
LIVING ROOM
1004
DINING ROOM
1005
CL
1037
BATH - 2
1021
BEDROOM - 2
1084
HALLWAY
1008
KITCHEN
1009
OFFICE/
BEDROOM - 3
1069
BATH - 1
1012
LAUNDRY/
PANTRY
1011
LIGHT FIXTURE LEGEND
LED - SUFACE MOUNT DOWNLIGHT - 120VAC - 3000K - DAMP
LISTED
LED - PENDANT LIGHT - 120VAC - 3000K - DAMP LISTED
LED - RECESSED DOWNLIGHT - 120VAC - 3000K - WET
LISTED IN BATHROOMS AND DAMP LISTED IN THE
REST OF THE AREAS
LED - BATH VANITY WALL SCONCE - 120VAC - 3000K - DAMP
LISTED
LED - EXTERIOR WALL SCONCE - 3000K - 120VAC - WET
LISTED
NOTES :
1. ALL PERANENTLY INSTALLED LIGHT FOR DWELLING UNITS
MUST BE HIGH EFFICACY AS SPECIFIED IN TABLE 150.0(K)
2. FIELD VERIFY THE EXACT MOUNTING HEIGHT OF FIXTURES
3. DIMMER SWITCHES SHALL BE COMPATIBLE WITH LIGHT
FIXTURES
Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE - TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 - 126
1/4" = 1' - 0"
10/28/2024 4:27:52 PM
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
E2.02
ELECTRICAL FIRST
FLOOR LIGHTING
PLAN - MAIN HOUSE
Author
Checker
24162
07.24.24 AS - BUILT DRAWINGS
1/4" = 1' - 0" 1 ELECTRICAL FIRST FLOOR LIGHTING PLAN
N
0 2' 4' 8'
SCALE: 1/4" = 1' - 0"
GENERAL NOTES
1. MARK ALL EXPOSED JUNCTION BOXES, LIGHTING DEVICES
WITH PANEL AND CIRCUIT NUMBERS
2. CONTRACTOR SHALL INSTALL OCCUPANCY SENSORS 4 TO
6 FEET AWAY FROM SUPPLY AIR DIFFUSERS
3. ALL J - BOXES, CONTROLLERS AND OTHER ELECT. EQ.
LOCATED IN CEILING OR CAVITIES SHALL BE ACCESSIBLE
BY AN ACCESS PANEL OR OTHER APPROVED MEANS.
FIELD VERIFY THE REQUIRES SIZE OF THE ACCESS
PANELS
4. ALL GENERAL SWITCHES SHALL BE PLACED AT +48" AFF
U.O.N. CONTRACTOR, COTRACTOR SHALL MOUNT THE
SWITCHES ABOVE COUNTER WHEREVER REQUIRED
5. ALL LUMINARIES INSTALLED IN DWELLING UNITS SHALL BE
HIGH EFFICACY, JA - 8 COMPLIANT AND SHALL SATISFY
CONDITIONS GIVEN IN CALIFORNIA ENERGY STANDARD
TABLE 150.0 - A
6. UNDER CABINET LUMINARIES SHALL BE SWITCHED
SEPARATELY FROM THE REST OF THE LIGHTING
7. LIGHTING IN BATHROOMS SHALL BE SWITCHED
SEPARATELY FROM THE EXHAUST FANS, THIS APPLIES TO
EXHAUST FAN COMBOS AS WELL
8. ALL LIGHT FIXTURES INTEGRATED WITH BATTERY BACK UP
SHALL BE PROVIDED WITH A SEPARATE UNSWITCHED
HOT/LINE WIRE FOR BATTERY CHARGING
9. ALL EXIT SIGNS SHALL BE WIRED INFRONT OF ALL
LIGHTING CONTROLS OR SWITCHES SO THEY ARE ON 24x7
AND NOT CONTROLLED BY ANY SWITCHES, PROVIDE
ADDITIONAL UNSWITCHED HOT/LINE WIRE FOR BATTERY
CHARGING
10. WIRING FOR LIGHTING PLANS IS SHOWN FOR
DIAGRAMMATIC PURPOSE AND ONLY INDICATES
CIRCUITING , CONTRACTOR MUST FIELD DETERMINE THE
MOST APPROPRIATE MEANS AND METHOD OF WIRING AND
PROVIDE ALL REQUIRED ACCESSORIES FOR A FULLY
OPERATIONAL SYSTEM
11. PROVIDE FIRE RATED J - BOXES/HOUSINGS WHERE LIGHT
FIXTURES ARE INSTALLED IN FIRE RATED ASSEMBLIES.
WHERE LIGHT FIXTURES ARE INSTALLED IN CONCRETE
ASSEMBLIES PROVIDE CONCRETE COMPATIBLE J -
BOXES/HOUSINGS
12. PROVIDE SEPARATE 1"C BETWEEN LIGHTING DEVICES
INCLUDING BUT NOT LIMITED TO OCCUPANCY SENSORS,
DAYLIGHT SENSORS, SWITCHES, POWER PACK ETC.
PROVIDE CONTROL WIRING PER MFR REQUIREMENTS
13. PROVIDE SEPARATE 3/4"C - w/0 - 10V WIRING WHEREVER
0 - 10V DIMMING IS REQUIRED
14. REFER TO FRONT SHEET FOR BRANCH CIRCUIT
CONDUCTOR AND CONDUIT SIZING WHEREVER NOT
PROVIDED ON THE RESPECTIVE PLAN SHEET
KEYNOTES #
J
1 1
PANEL B
B - 1
B - 2
1" CONDUIT
J - BOX FOR
FUTURE EV
CHARGER
2 2
Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE - TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 - 126
1/4" = 1' - 0"
10/28/2024 4:27:52 PM
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
E2.03
ELECTRICAL FIRST
FLOOR
PLAN - DETACHED
GARAGE
Author
Checker
24162
07.24.24 AS - BUILT DRAWINGS
1/4" = 1' - 0" 1 ELECTRICAL FIRST FLOOR POWER PLAN - DETACHED GARAGE 1 CEILING MOUNT RECEPTACLE FOR GARAGE DOOR OPENER,
INSTALL PER MFG REQUIREMENTS AND PROVIDE ALL
REQUIRED ACCESSORIES FOR A FULLY OPERATIONAL
SYSTEM
2 PROVIDE 1"C FROM PANEL B TO THE EV CHARGING J-BOX AS
NOTED. MARK THE J-BOX 'EV CAPABLE' AS REQUIRED PER
CGBSC 4.106.4.1.1
GENERAL NOTES
1. MARK ALL EXPOSED JUNCTION BOXES, RECEPTACLES
WITH PANEL AND CIRCUIT NUMBERS
2. PROVIDE 3/4" C FROM FAN COIL TO ASSOCIATED
THERMOSTATS AND OUTDOOR UNITS FOR CONTROLS
PURPOSE
3. ALL J - BOXES, CONTROLLERS AND OTHER ELECT. EQ.
LOCATED IN CEILING OR CAVITIES SHALL BE ACCESSIBLE
BY AN ACCESS PANEL OR OTHER APPROVED MEANS.
FIELD VERIFY THE REQUIRED SIZE OF THE ACCESS
PANELS
4. ALL OUTDOOR RECEPTACLES SHALL BE GFCI TYPE AND
SHALL BE PROVIDED WITH WEATHER PROTECTIVE
COVERS
5. ALL GENERAL PURPOSE RECEPTACLES SHALL BE PLACED
AT +18" AFF AND SWITCHES SHALL BE PLACED AT +48" AFF
U.O.N. CONTRACTOR SHALL MOUNT RECEPTACLES ABOVE
FURNITURE WHEREVER REQUIRED
6. REFER TO MECHANICAL PLANS FOR THE EXACT LOCATION
OF EXHAUST FANS. FAN COIL UNITS, THERMOSTATS AND
ALL OTHER MECHANICAL EQ
7. PROVIDE GFCI RECEPTACLES FOR FOLLOWING
LOCATIONS :
BATHROOMS, GARAGES, OUTDOORS, CRAWL - SPACES,
UNFINISHED PARTITIONS AND ALL LOCATIONS THAT HAVE
A FLOOR LOCATED AT OR BELOW GRADE LEVEL NOT
INTENDED AS HABITABLE ROOMS AND LIMITED TO
STORAGE AREAS, WORK AREAS, ALL KITCHEN
COUNTERTOPS, WITHIN 6FT. OF LAUNDRY AND BAR SINKS
AND AREAS OF SIMILAR USE, DISHWASHERS
8. RECEPTACLES AT KITCHEN COUNTERTOPS SHALL BE
PLACED SO THAT NO PORTION OF THE COUNTERTOP IS
FURTHER THAN 24" FROM AN OUTLET
9. WALL OUTLETS IN HABITABLE ROOMS SHALL BE SPACED
SO THAT NO POINT ALONG THE FLOOR LINE IN ANY WALL
SPACES IS MORE THAN 6' FROM AN OUTLET
10. ALL 120 - VOLT, 15 OR 20 AMP RECEPTACLES TO BE LISTED AS TAMPER - RESISTANT PER CEC SECTION 210.52 AND
406.11
11. LAYOUT OF THE HVAC AND PLUMBING EQUIPMENT IS
SHOWN FOR REFERENCE AND FOR POWER
REQUIREMENTS, EXACT EQUIPMENT LAYOUT SHALL BE BY
EACH INDIVIDUAL DISPLINE CONTRACTOR/ENGINEER,
ELECTRICAL CONTRACTOR TO FIELD COORDINATE EXACT
LOCATIONS AND RELOCATE ANY ELECTRICAL EQ. AS
NEEDED
12. REFER TO FRONT SHEET FOR BRANCH CIRCUIT
CONDUCTOR AND CONDUIT SIZING WHEREVER NOT
PROVIDED ON THE RESPECTIVE PLAN SHEET
13. WIRING FOR POWER PLANS IS SHOWN FOR
DIAGRAMMATIC PURPOSE AND ONLY INDICATES
CIRCUITING , CONTRACTOR MUST FIELD DETERMINE THE
MOST APPROPRIATE MEANS AND METHOD OF WIRING AND
PROVIDE ALL REQUIRED ACCESSORIES FOR A FULLY
OPERATIONAL SYSTEM
KEYNOTES #
MAIN
PANEL
GROUNDING ELECTRODE
CONDUCTOR SIZE PER
PLANS PROTCTED BY
CONDUIT
BOLTED TYPE
CONNECTION
CONCRETE FOUNDATION
OR FOOTING
4 AWG OR LARGER BARE CU.
OR REBAR OR ROD NOT LESS THAN
1/2" DIAMETER
NOT MORE THAN
3" OR LESS THAN 2"
WHERE IN DIRECT
CONTACT WITH EARTH
20" MIN
.
SCALE
1 UFER GROUNDING NTS
EQUIPMENT
GROUNDING
CONDUCTOR
UFER
GROUNDING
3/4"x10'
SUPPLEMENTAL
COPPER BONDED
GROUNDING ROD
COLD WATER PIPE
BLDG
STEELE
TELECOM - CATV EQ.
GROUNDING BUS
IBT(INTERSYST
EM BONDING
TERMINATION)
SERVICE EQUIPMENT
NEUTRAL BUS
GROUND BUS
LEGEND:
KEYNOTES :
EXOTHERMIC WELD CONNECTION SUCH AS CADWELD, COMPATIBLE WITH JOINTS BEING
MECHANICAL/BOLTD CONNECTION
GROUNDING ELECTRODE CONDUCTOR SIZE PER PLAN
MAIN BONDING JUMPER SIZE PER PLAN
SYSTEM BONDING JUMPER SIZE PER PLAN
ALL GROUNDING ELECTRODES AS SHOWS THAT ARE PRESENT AT EACH BUILDING OR
STRUCTURE SERVED SHALL BE BONDED TOGETHER TO FORM THE GROUNDING
SYSTEM, WHERE NONE OF THESE GROUNDING ELECTRODE EXIST, ONE OR MORE OF THE GROUNDING ELECTRODES SPECIFIED IN 250.52(A)(4) THROUGH 250.52(A)(8) SHALL BE INSTALLED AND USED PER CEC250.50 SIZE PER PLAN
CONTRACTOR TO USE INTERSYSTEM BONDING TERMINATION DEVICE PER CEC 800.1.
DEVICE MUST COMPLY WITH THE REQUIREMENTS OF CEC 250.94
BONDING OF METALLIC GAS OR OTHER PIPES THAT ARE LIKELY TO BE ENERGIZED,
SIZE PER PLANS
IF MULTIPLE RODS ARE USED, THEY SHALL NOT BE LESS THAN 6FT. APART 2 3
4 TYP
1 6
5 7
1 2
3 4
5 6
7 SCALE
2 SERVICE EQ. GROUNDING NTS
2"MIN
72 "TYP
MICROWAVE
OVEN RANGE
SWITCH
DOOR BELL
PUSHBUTTON 48" TYP
12" TYP
RECP.
CEILING LINE
DOORBELL
CHIME
NOTE : SEE ADA MOUNTING
HEIGHT REQUIREMENTS DETAIL
FOR ADA COMPLIANT UNIT
MOUNTING HEIGHTS
SCALE
4 TYPICAL MTG. HEIGHTS FOR SWITCHES AND RECP NTS
INTERIOR FINISH
FIRE RATED
GYPSUM
BOARD PER
ARCHITECT
WRAP OUTLET BOX WITH
PUTTY PAD, USE 3M TYPE
MPP+ MOLDABLE PUTTY
PADS(FOLLOW
MANUFACTURER
INSTALLATION
INSTRUCTION)
FILL 1/4" GAP WITH
ACOUSTICAL SEALANT
AROUND PERIMETER
OUTLET COVER
INSULATION PER TITLE - 24
SCALE
6 OUTLET BOXES IN FIRE RATED WALL NTS
DOOR BELL CHIME
REAR TRANS FRONT
REAR
DOOR
BELL
FRONT
DOOR
BELL
TRANSFORMER
HOT
NEUTRAL
GROUND
TO ELECT
PANEL
TRANSFORMER
WIRE
FRONT DOOR BELL
WIRE
REAR DOOR BELL WIRE
(WHERE REQ'D)
SCALE
5 DOOR BELL CHIME WIRING NTS
A
A
CAST METAL 'WHILE -
IN - USE' WP COVER &
RECEPTACLE
RIGID STEEL CONDUIT FOR
SUPPORT & WIRING PER NEC
ART 314
SECURE CONDUITS TO ROOF /FLOOR
JOISTS/CONCRETE SLAB
FLASHING PER ROOF MFR REQUIREMENTS
CAST METAL, 2 -
GANG,NEMA - 3R
JUNCTION BOX
WITH THREADED
HUBS
SCALE
7 INDEPENDENTLY SUPPORTED WP RECEPTACLE NTS
24" TYP.
Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE - TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 - 126
12" = 1' - 0"
10/28/2024 4:27:53 PM
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
E7.01
ELECTRICAL DETAILS
Author
Checker
24162
07.24.24 AS - BUILT DRAWINGS
PLUMBING GENERAL NOTES
1. ALL WORK SHALL BE IN STRICT ACCORDANCE WITH 2022
CPC/CMC/CBC ALL LOCAL CODES AND AUTHORITIES HAVING
JURISDICTION UNLESS NOTED WITH SPECIFIC YEAR
ADDITION.
2. ARCHITECTURAL AND STRUCTURAL PLANS ARE
CONSIDERED A PART OF THE DESIGN DRAWINGS AND ARE
TO BE USED TO DEFINE DETAIL CONFIGURATIONS
INCLUDING, BUT NOT LIMITED TO RELATIVE LOCATION OF
MEMBERS, ELEVATION, LOCATION OF ALL OPENINGS, ETC.
3. BEFORE STARTING ANY WORK, VERIFY THE ADEQUACY,
LOCATION, SIZE, AND AVAILABILITY OF ALL UTILITIES
CONCERNED, INCLUDING SEWER INVERT ELEVATIONS, AND
WATER PRESSURE.
4. ALL VENTS THROUGH ROOF AND ROOF DECKS SHALL BE
MINIMUM OF THREE FEET VERTICALLY OR TEN FEET
HORIZONTALLY FROM ANY FRESH AIR INTAKES.
5. CLEANOUTS SHALL BE REQUIRED AS INDICATED ON THE
PLANS AND INSTALLED PER SECTION 707.0 AND 719.0 OF THE
PLUMBING CODE.
6. ALL DOMESTIC WATER FIXTURES, PIPING VALVES, ETC. FOR
HUMAN CONSUMPTION SHALL COMPLY WITH CALIFORNIA
HEALTH AND SAFETY CODE 116875.
7. NEW OR REPAIRED POTABLE WATER SYSTEM SHALL BE
DISINFECTED PRIOR TO USE ACCORDING TO THE METHOD
SET IN SECTION 609.10 OF THE PLUMBING CODE.
8. INSULATE ALL HOT WATER, HOT WATER RETURN,
CONDENSATE DRAIN PIPING AND OUTDOOR PIPING.
9. THE "ENGINEER OF RECORD" IS RESPONSIBLE FOR THE
SYSTEM DESIGN AND THE INTERPRETATION OF THAT
DESIGN FOR THIS PROJECT.
10. PIPES PASSING THROUGH FIRE RATED WALLS OR FLOORS
SHALL BE SEALED ALL AROUND WITH FIRE RATED SEALANT.
11. PROVIDE FLASHING AND/OR COUNTER FLASHING OF ALL
EXTERIOR PENETRATIONS.
12. ALL EQUIPMENT SHALL BE INSTALLED IN STRICT
ACCORDANCE WITH THE EQUIPMENT MANUFACTURERS
RECOMMENDATIONS.
13. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE
WORKABLE INSTALLATION.
14. ALL APPLIANCES DESIGNED TO BE FIXED IN POSITION SHALL
BE SECURELY FASTEN IN PLACE PER BUILDING CODE
REQUIREMENTS OR APPLICABLE MANUFACTURER
INSTALLATION REQUIREMENTS.
15. ALL EXPOSED GAS PIPING SHALL BE PROTECTED AGAINST
CORROSION BY COATING OR WRAPPING WITH AN INERT
MATERIAL APPROVED FOR SUCH APPLICATIONS.
16. ALL COMBUSTIBLE PIPING SHALL BE INSTALLED PER
CHAPTER 14 OF THE CALIFORNIA PLUMBING CODE FOR
"FIRESTOP PROTECTION".
17. PROVIDE METALLIC WATER LINE CONNECTORS FROM SHUT -
OFF TO PLUMBING FIXTURES. RUBBER AND PLASTICS ARE
NOT PERMITTED.
18. ALL FIXTURES, EQUIPMENT, PIPING, AND MATERIALS SHALL BE LISTED.
19. ALL PLUMBING FIXTURES SHALL MEET THE FLOW
REQUIREMENTS SPECIFIED IN THE CALIFORNIA PLUMBING
CODE.
20. ALL PLUMBING FIXTURES THAT PROVIDE WATER FOR HUMAN
CONSUMPTION SHALL COMPLY WITH THE CALIFORNIA LEAD
FREE LAW (PER SECTION 116875 OF THE CALIFORNIA
HEALTH AND SAFETY CODE) - LESS THAN 0.25% WEIGHTED
AVERAGE OF LEAD CONTENT.
PLUMBING LEGEND
SYMBOL ABBREVIATION DESCRIPTION
CW CW
HW
HWR
HW
HWR
COLD WATER PIPING
HOT WATER PIPING
HOT WATER RETURN PIPING
DN DROP IN PIPE
UP RISE IN PIPE
- DIRECTION IN PIPE
HB HOSE BIBB
WCO WALL CLEANOUT
U UNION
BV BALL VALVE
FCO FLOOR CLEANOUT
POC POINT OF CONNECTION
POD POINT OF DEMOLITION
FU FIXTURE UNIT
GPM GALLONS PER MINUTE
I.E. INVERT ELEVATION
NTS NOT TO SCALE
TDL TOTAL DEVELOPED LENGTH
TYP. TYPICAL
NOTE: ALL FINAL SELECTION OF PLUMBING FIXTURES SHALL BE MADE BY OWNER OR OWNER'S REPRESENTATIVE.
PLUMBING EQUIPMENT SCHEDULE
EQUIP.
TAG EQUIPMENT GAS
CFH
G G LOW PRESSURE GAS PIPING
W WASTE PIPING ABOVE FLOOR W
W WASTE PIPING BELOW FLOOR W
V VENT PIPING V
WH -1
ET -1
HOLD
(GAL.)
WATER HEATER
EXPANSION TANK
BFP -1 REDUCED PRESSURE
BACKFLOW PREVENTER - -
ELECTRICAL
kW V ∅
SIZE MAKE MODEL REMARKS
- 1-1/2" ZURN NR3XL - -
- - 1-1/2" ZURN 975XL2 - -
192 0.17 - RINNAI RXP199i 120 3
- - 1/2" AMTROL ST -1- -
SCOPE OF WORK
THE SCOPE OF WORK FOCUSES ON PROVIDING THE PLUMBING
SYSTEMS FOR REHABILITATION OF SCHOLLE HOUSE. THE
PLUMBING SYSTEMS INCLUDE THE COLD, HOT WATER, HOT
WATER RETURN, CONDENSATE, AND THE WASTE AND VENT
SYSTEM.
FIXTURE UNIT COUNT
TYPE OF FIXTURE QTY. TOTAL CW FU F.U.
FUTURE LOAD
TOTAL F.U.
TOTAL FLOW RATE
WATER CALCULATIONS
WATER INFORMATION: 110 PSI HIGH AND 100 PSI LOW
METER SIZE: 1 -1/2"
EQUIVALENT LENGTH (DEVELOPED LENGTH 88 FT + 25% FITTING ALLOWANCES) = 110 FT
PIPING MATERIAL: COPPER TYPE L
BACKFLOW PREVENTION ASSEMBLY: SIZE 1 -1/2" ZURN 975XL2
HYDRAULIC CALCULATION
A.
B.
C.
E.
F.
MINIMUM PRESSURE AT CITY MAIN
PRESSURE LOSS THROUGH 1 -1/2" METER
PRESSURE LOSS THROUGH OTHER EQUIPMENT
RESIDUAL PRESSURE REQUIRED (MOST REMOTE OUTLET)
STATIC HEAD LOSS H.
100 PSI
0.9 PSI
31 PSI
20 PSI
2.6 PSI
J.
UNIFORM FRICTION HEAD LOSS = (8.402 X 100)/110 = 7.6 PSI/100 FT
KITCHEN SINK
BATHTUB
11.5 WATER CLOSET
LAVATORY
22.5 21
SHOWER
4 2
1 1
TOTAL HW FU
WASHING MACHINE
DISHWASHER
4 1
11.5 5 0
2 2
4 4
2 2
4 4
1.5 1.5
1.5 5.5 0
30 15
HOSE BIBB 12.5 2.5 0
ADD. HOSE BIBB 2 2 01
20 GPM 11 GPM
PLUMBING PIPE AND FITTING SCHEDULE
TYPE
CW, HW
AND
HWR
WASTE
AND VENT
GAS
SIZE
ALL SIZES
MATERIAL
NO -HUB
CAST IRON,
ABS SCH X0
SCHEDULE 40
BLACK STEEL
(NOTE: WARDFLEX
WILL NOT BE
ACCEPTABLE)
FITTINGS
WROUGHT
COPPER
WROUGHT
COPPER
SILVER BRAZED
NO -HUB
CAST IRON,
ABS SCH X0
THREADED
FITTINGS ANSI
B16.3, BLACK
MALLEABLE IRON
150 LBS OR ANSI
B16.11 FORGED
STEEL
POLYETHYLENE POLYETHYLENE
LOCATION
ABOVE GRADE
BELOW GRADE
ABOVE GRADE
BELOW GRADE
ABOVE AND
BELOW GRADE
FIXTURE FLOW RATES
FIXTURE TYPE
GRAVITY TANK TYPE WATER
CLOSETS
LAVATORY FAUCETS,
RESIDENTIAL
BATHTUB/SHOWER
HEADS
KITCHEN FAUCETS
MAX. ALLOWABLE FLOW RATE
1.28 GALLONS/FLUSH
DISH WASHER
CLOTH WASHER
METERING FAUCETS
1.5 GPM AT 60 PSI
ENERGY -STAR CERTIFIED
ENERGY -STAR CERTIFIED
0.2 GALLONS/CYCLE
1.8 GPM AT 80 PSI
1.2 GPM AT 60 PSI
PIPE SIZE SCHEDULE
PIPE MATERIAL : COPPER L
ALLOW FIXTURE UNITS PSI/100FT: 5
FLUSH TANK FLUSH VALVE
1/2
3/4
1 1-1/2
2 1
7 16
46 119
1 7
18 66
245
0 20
124
0 5
I.
15 PSI
PLUMBING FIXTURE SCHEDULE
FIXTURE
TAG FIXTURE
KITCHEN SINK
BATHTUB
WATER CLOSET
LAVATORY
SHOWER
CLOTHE WASHER
DISHWASHER
ICE MAKER WALL
BOX
WC -1
L-1
BT -1
SH -1
WM -1
KS -1
DW -1
IM -1
GAS RANGE GR -1
W V T CW HW REMARKS
3" 2" INT 3/4" -
2" 1-1/2"
- 1/2"
3/4"
- 3/4" INDIRECT DRAIN
INTO KITCHEN SINK
1-1/4'
1-1/2" X
-
-
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
2"
2"
2"
2"
2"
2"
2"
2"
WATER HEATER CALCULATION
WH -1
KITCHEN SINK
BATHTUB
LAVATORY
SHOWER
CLOTHE WASHER
DISHWASHER
1.5 PRESSURE LOSS THROUGH 1 -1/2" BACKFLOW PREVENTER
K.
L.
TOTAL PRESSURE LOSS AFTER PRV 61.6 PSI
TOTAL PRESSURE LOSS UP TO PRV 15.9 PSI
SET PRESSURE AT PRESSURE REDUCING VALVE 70.0 PSI
PRESSURE LOSS THROUGH WATER SUBMETER 0 PSI
M.
C FACTOR: 140
COLD WATER
LOCATION: EAST EXTERIOR WALL
FIXTURE TYPE 3/4TH OF FU TOTAL
TOTAL GPM (HUNTER'S CURVE)
EQ -1 EARTHQUAKE VALVE
QTY.
2 2
1 1
1 1
FU
1 1
4 1.5
1.5 4
TOTAL FU
0.75 3
0.75 3
1.125
1.125
1.5 3
3 1.125
1.125
1.5 11.6
9.00 HOSE BIBB HB -1
- -
PRV -1 PRESSURE REDUCING VALVE INSTALL PER MANUFACTURER'S R ECOMMENDATIONS PROVIDE OUTDOOR VENT CAP #RXOVC AND ISOLATION
VALVE KIT#MIVK-T-LW. INSTALL PER MANUFACTURER'S
RECOMMENDATIONS.
INSTALL PER MANUFACTURER'S RECOMMENDATIONS
DRYER DR -1 - -
- - 1" PSP 301 - -
INSTALL PER MANUFACTURER'S RECOMMENDATIONS
REFER TO ARCHITECTURAL DRAWINGS FOR SPECS. INSTALL PER MANUFACTURER RECOMMENDATION.
RECESSED IN WALL. ACORN #8151 WITH KEY OPERATED AND VACUUM BREAKER.
COLD WATER HOT WATER
PRESSURE AVAILABLE TO OVERCOME PIPE FRICTION (J -K) 8.4 PSI G.
ALL SIZES
ALL SIZES
ALL SIZES
ALL SIZES
TYPE "K"
HARD COPPER
TYPE "L"
HARD COPPER
-
-
-
- -
- -
- -
- -
FLUSH TANK TYPE FLOOR MOUNTED - 1.28 GPF TOTO MODEL MS614114CUF(G) ELONGATED FRONT BOWL CARLYLE II. ONE-PIECE WITH SEAT.
MAX. DESIGN VELOCITY: 8 FPS FOR COLD WATER AND 5 FPS FOR HOT WATER
SIZE (INCHES)
WALL MOUNTED LAVATORY TOTO MODEL LT307(A). PROVIDE DRAIN WITH ALL RELATED ACCESSORIES. TOTO FAUCET (TEL105-C20E) STANDARD ECO POWER 0.5GPM REFER TO ARCHITECTURAL DRAWINGS FOR SPECS. INSTALL PER MANUFACTURER RECOMMENDATION.
ENERGY STAR CERTIFIED. OWNER TO PROVIDE SPECIFICATION. INSTALL PER MANUFACTURER RECOMMENDATIONS.
REFER TO ARCHITECTURAL DRAWINGS FOR SPECS. INSTALL PER MANUFACTURER RECOMMENDATIONS. INSTALL WITH HOLE FOR DISHWASHER AIR GAP.
ENERGY STAR CERTIFIED. OWNER TO PROVIDE SPECIFICATION. INSTALL PER MANUFACTURER RECOMMENDATIONS.
ENERGY STAR CERTIFIED. OWNER TO PROVIDE SPECIFICATION. INSTALL PER MANUFACTURER RECOMMENDATIONS.
PROVIDE GAS CONNECTION. 45,000 BTU/h. OWNER TO PROVIDE SPECIFICATION. SEE RISER DIAGRAM FOR PIPE SIZE. INSTALL PER MANUFACTURER RECOMMENDATIONS.
PROVIDE GAS CONNECTION. 20,000 BTU/h. OWNER TO PROVIDE SPECIFICATION. SEE RISER DIAGRAM FOR PIPE SIZE. INSTALL PER MANUFACTURER RECOMMENDATIONS.
PRESSURE LOSS THROUGH 1-1/2" PRESSURE REDUCING
VALVE
D. 8 PSI
-
-
-
-
INSTALL PER MANUFACTURER'S RECOMMENDATIONS
DEMAND FACTOR 1
DEMAND WATER HEATER SELECTION IS RINNAI #RXP199i
AT 44° F TEMPERATURE DIFFERENCE MAXIMUM FLOW RATE OF
WATER HEATER.
9 GPM
NUMBER OF WATER HEATER REQUIRED (9/9) 1
INLET WATER TEMP = 60° F, OUTLET WATER TEMP = 104° F ΔT=44° F Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE-TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 -126
12" = 1'-0"
28-10-2024 16:55:51
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
P0.01
PLUMBING FRONT
SHEET
Author
Checker
24162
07.24.24 AS-BUILT DRAWINGS
PLUMBING SHEET INDEX
SHEET NUMBER SHEET NAME
P0.01 PLUMBING FRONT SHEET
PD2.01 PLUMBING FIRST FLOOR DEMOLITION PLAN
PD2.02 PLUMBING ROOF DEMOLITION PLAN
P2.01 PLUMBING FIRST FLOOR WATER AND GAS PLAN
P2.02 PLUMBING FIRST FLOOR WASTE AND VENT PLAN
P2.03 PLUMBING ROOF PLAN
P7.01 PLUMBING DETAILS
100% SD 10/28/2024
B
B
A
B
Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE-TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 -126
1/4" = 1'-0"
28-10-2024 16:55:56
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
PD2.01
PLUMBING FIRST
FLOOR DEMOLITION
PLAN
Author
Checker
24162
07.24.24 AS-BUILT DRAWINGS
1/4" = 1'-0" 1 PLUMBING FIRST FLOOR DEMOLITION PLAN
N
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
100% SD 10/28/2024
DEMOLITION GENERAL NOTES
1. ALL THE EXISTING PLUMBING FIXTURES AND RELATED
ACCESSORIES, WATER, WASTE AND VENT PIPING TO BE
REMOVED INSIDE THIS BUILDING.
2. PRIOR TO COMMENCING WORK CONTRACTOR SHALL VERIFY
EXACT DEPTH AND LOCATION OF EXISTING SEWER LINES AT
THE FIELD.
3. REPAIR THE WALLS, FLOORS OR CEILINGS AFTER
INSTALLATION AND INSPECTION OF UTILITIES INSTALLED.
PATCH AND PAINT TO MATCH PREVIOUS CONDITIONS.
DEMOLITION NOTES
EXISTING PLUMBING FIXTURES WITH ALL RELATED
ACCESSORIES TO BE REMOVED.
ALL THE EXISTING WATER, WASTE AND VENT PIPING TO BE
REMOVED INSIDE THIS AREA.
A.
B.
AA
Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE-TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 -126
1/4" = 1'-0"
28-10-2024 16:55:57
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
PD2.02
PLUMBING ROOF
DEMOLITION PLAN
Author
Checker
24162
07.24.24 AS-BUILT DRAWINGS
1/4" = 1'-0" 1 PLUMBING ROOF DEMOLITION PLAN
N
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
100% SD 10/28/2024
DEMOLITION GENERAL NOTES
1. ALL THE EXISTING PLUMBING FIXTURES AND RELATED
ACCESSORIES, WATER, WASTE AND VENT PIPING TO BE
REMOVED INSIDE THIS BUILDING.
2. PRIOR TO COMMENCING WORK CONTRACTOR SHALL VERIFY
EXACT DEPTH AND LOCATION OF EXISTING SEWER LINES AT
THE FIELD.
3. REPAIR THE WALLS, FLOORS OR CEILINGS AFTER
INSTALLATION AND INSPECTION OF UTILITIES INSTALLED.
PATCH AND PAINT TO MATCH PREVIOUS CONDITIONS.
DEMOLITION NOTES
ALL THE EXISTING VENT THROUGH ROOF PIPING TO BE
REMOVED INSIDE THIS AREA.
A.
NORTH PORCH
1014
LIVING ROOM
1004
DINING ROOM
1005
HALLWAY
1008
KITCHEN
1009
LAUNDRY/
PANTRY
1011
BATH-1
1012
BATH-2
1021
BEDROOM- 1
1036
CL
1037
OFFICE/
BEDROOM -3
1069
BEDROOM-2
1084
WC -1
L-1
SH -1
BT -1
L-1
WC -1
KS -1
WM -1
1 2
3 4
1 2
5 6
1-1/2" DOMESTIC COLD WATER POINT
OF CONNECTION
5 FEET AWAY FROM THE BUILDING.
REFER TO CIVIL PLANS FOR
CONTINUATION.
7 DW -1
1" LOW PRESSURE GAS POINT OF
CONNECTION 5 FEET AWAY FROM THE
BUILDING. REFER TO CIVIL PLANS FOR
CONTINUATION.
8 IM -1
GGG
GR -1
BFP -1
PRV -1
WH -1
9 9
10 DR -1
Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE-TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 -126
1/4" = 1'-0"
28-10-2024 16:55:53
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
P2.01
PLUMBING FIRST
FLOOR WATER AND
GAS PLAN
Author
Checker
24162
07.24.24 AS-BUILT DRAWINGS
1/4" = 1'-0" 1 PLUMBING FIRST FLOOR WATER AND GAS PLAN
N
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
GENERAL NOTES
A. ALL PIPING ON THIS PLAN SHALL BE CONCEALED INSIDE THE WALL, FLOOR OR CEILING UNLESS NOTED OTHERWISE.
B. REFER TO RISER DIAGRAMS FOR PIPE SIZES.
C. PROVIDE INSULATION FOR ALL HOT WATER SUPPLY, HOT
WATER RETURN, CONDENSATE DRAINAGE AND OUTDOOR
PIPING.
D. ALL PIPE PENETRATION AT THE FLOOR OR ROOF SHALL BE
PROPERLY SEALED BY THE INSTALLING CONTRACTOR.
CONSTRUCTION NOTES
1 INSTALL WATER CLOSET (FT) WITH ALL RELATED
ACCESSORIES. RUN 3/4" CW (2.5 FU) DOWN TO WATER
CLOSET.
2 INSTALL LAVATORY WITH ALL RELATED ACCESSORIES. RUN
3/4" CW (1 FU) AND 3/4" HW (1 FU) DOWN TO FAUCET.
3 INSTALL BATHTUB WITH ALL RELATED ACCESSORIES. RUN 3/4" CW (4 FU) AND 3/4" HW (4 FU) DOWN TO BATHTUB.
4 INSTALL SHOWER WITH ALL RELATED ACCESSORIES. RUN 3/4" CW (2 FU) AND 3/4" HW (2 FU) DOWN TO SHOWER HEAD.
5 INSTALL WASHING MACHINE WITH ALL RELATED ACCESSORIES.
RUN 3/4" CW (4 FU) AND 3/4" HW (4 FU) DOWN TO WASHER.
PROVIDE WASHER BOX WITH WATER HAMMER ARRESTOR FOR
WATER CONNECTIONS.
6 INSTALL KITCHEN SINK WITH ALL RELATED ACCESSORIES. RUN 3/4" CW (1.5 FU) AND 3/4" HW (1.5 FU) DOWN TO FAUCET.
7 INSTALL DISHWASHER WITH ALL RELATED ACCESSORIES.
EXTEND 3/4" HW (4 FU) FROM KITCHEN SINK TO DISHWASHER
AND PROVIDE WATER HAMMER ARRESTOR. CW CONNECTION
IS NOT REQUIRED
8 RUN 1/2" CW DOWN TO ICE MACHINE. INSTALL WALL BOX FOR WATER CONNECTION.
#
100% SD 10/28/2024
INSTALL GAS RANGE WITH ALL RELATED ACCESSORIES. RUN
3/4" G (45 CFH) DOWN.
9 INSTALL DRYER WITH ALL RELATED ACCESSORIES. RUN 3/4" G (20 CFH) DOWN.
10 NORTH PORCH
1014
LIVING ROOM
1004
DINING ROOM
1005
HALLWAY
1008
KITCHEN
1009
LAUNDRY/
PANTRY
1011
BATH-1
1012
BATH-2
1021
BEDROOM- 1
1036
CL
1037
OFFICE/
BEDROOM -3
1069
BEDROOM-2
1084
WC -1
L-1
SH -1
BT -1
L-1
WC -1
KS -1
WM -1
1 2
3 4
1 2
5 6
7 DW -1
4" SEWER POINT OF
CONNECTION 5 FEET
AWAY FROM THE
BUILDING. REFER TO
CIVIL PLANS FOR
CONTINUATION.
4" VTR
4" VTR
3" COTG
4" COTG
1/8" / 12" 1/8" / 12"
Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE-TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 -126
1/4" = 1'-0"
28-10-2024 16:55:54
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
P2.02
PLUMBING FIRST
FLOOR WASTE AND
VENT PLAN
Author
Checker
24162
07.24.24 AS-BUILT DRAWINGS
1/4" = 1'-0" 1 PLUMBING FIRST FLOOR WASTE AND VENT PLAN N
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
GENERAL NOTES
A. ALL PIPING ON THIS PLAN SHALL BE CONCEALED INSIDE THE WALL, FLOOR OR CEILING UNLESS NOTED OTHERWISE.
B. REFER TO RISER DIAGRAMS FOR PIPE SIZES.
C. PROVIDE INSULATION FOR ALL HOT WATER SUPPLY, HOT
WATER RETURN, CONDENSATE DRAINAGE AND OUTDOOR
PIPING.
D. ALL PIPE PENETRATION AT THE FLOOR OR ROOF SHALL BE
PROPERLY SEALED BY THE INSTALLING CONTRACTOR.
# CONSTRUCTION NOTES
1 INSTALL WATER CLOSET (FT) WITH ALL RELATED
ACCESSORIES. RUN 3" W (3 FU) DOWN AND 2" V UP FROM
WATER CLOSET.
2 INSTALL LAVATORY WITH ALL RELATED ACCESSORIES. RUN
2" W (1 FU) DOWN AND 1-1/2" V UP FROM LAVATORY.
3 INSTALL BATHTUB WITH ALL RELATED ACCESSORIES. RUN
2" W (2 FU) DOWN AND 1-1/2" V UP FROM BATHTUB DRAIN.
4 INSTALL SHOWER WITH ALL RELATED ACCESSORIES. RUN 2 "
W (2 FU) DOWN AND 1-1/2" V UP FROM SHOWER DRAIN.
5 INSTALL WASHING MACHINE WITH ALL RELATED
ACCESSORIES. RUN 2" W (3 FU) DOWN AND 1-1/2" V UP FROM
WASHER BOX.
6 INSTALL KITCHEN SINK WITH ALL RELATED ACCESSORIES.
RUN 2" W (2 FU) DOWN AND 1-1/2" V UP FROM SINK.
7 INSTALL DISHWASHER WITH ALL RELATED ACCESSORIES.
CONNECT DRAIN INTO KITCHEN SINK TAILPIECE.
100% SD 10/28/2024
4" VTR
4" VTR
Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE-TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 -126
1/4" = 1'-0"
28-10-2024 16:55:55
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
P2.03
PLUMBING ROOF PLAN
Author
Checker
24162
07.24.24 AS-BUILT DRAWINGS
1/4" = 1'-0" 1 PLUMBING ROOF PLAN
N
0 2' 4' 8'
SCALE: 1/4" = 1'-0"
100% SD 10/28/2024
GENERAL NOTES
A. ALL PIPE PENETRATION AT THE FLOOR OR ROOF SHALL BE
PROPERLY SEALED BY THE INSTALLING CONTRACTOR.
B. REFER TO RISER DIAGRAMS FOR PIPE SIZES.
1 TANKLESS WATER HEATER DETAIL
NTS
2 HOSE BIBB DETAIL
NTS
3 CONDENSATE DRAIN DISCHARGE DETAIL
NTS
4 DISHWASHER DRAIN CONNECTION DETAIL
NTS
GAS SUPPLY
HOT WATER SUPPLY
COLD WATER SUPPLY
SRV
GAS SUPPLY LINE
CW SUPPLY LINE
HW SUPPLY LINE
CONDENSATE DISCHARGE
EXPANSION TANK
AMTROL #ST-1
WH-1
DRAIN CONDENSATE
TO FLOOR SINK
3/4" PRESSURE TEMPERATURE
RELIEF VALVE DISCHARGE TO
FLOOR SINK
PROVIDE OUTDOOR VENT KIT
BUILT-IN CIRCULATION PUMP
HOT WATER RETURN
HW RETURN LINE
WALL SECTION
FRONT ELEVATION
FINISHED
WALL (TYP.)
3/4" CW CONNECT
TO HOSE BIBB
LOOSE KEY
WITH VACUUM
BREAKER
3/4" CW CONNECT
TO HOSE BIBB
MAINTAIN
WATERTIGHT SEAL
BETWEEN BIBB AND
BOX
WALL BOX
HOSE BIBB
CONDENSATE
DRAINAGE FROM
MECHANICAL
EQUIPMENT
2"
NEARBY WALL
FLOOR SINK/FLOOR DRAIN
P-TRAP TO WASTE
SYSTEM
VENT LINE
FLOOR
MOUNT PIPE
SUPPORT
CONDENSATE DRAINAGE
INDIRECT WASTE TO
FLOOR SINK
814.5 POINT OF DISCHARGE
AIR-CONDITIONING CONDENSATE WASTE PIPES SHALL CONNECT
INDIRECTLY, EXCEPT WHERE PERMITTED IN SECTION 814.6, TO
THE DRAINAGE SYSTEM THROUGH AN AIR GAP OR AIR BREAK TO
TRAPPED AND VENTED RECEPTORS, DRY WELLS, LEACH PITS, OR THE TAILPIECE OF PLUMBING FIXTURES. A CONDENSATE DRAIN
SHALL BE TRAPPED IN ACCORDANCE WITH THE APPLIANCE
MANUFACTURER'S INSTRUCTIONS OR AS APPROVED.
CONDENSATE DRAIN
DOWN IN
WALL.DISCHARGE IN THE
TAILPIECE OF THE
LAVATORY
WALL
LAVATORY OR
SERVICE SINK
NEW SLIP-JOINT
FITTING
P-TRAP
FINISHED
FLOOR
CD
RUN 3/4" CD
ALONG INTERIOR
WALL
814.6 CONDENSATE WASTE FROM AIR-CONDITIONING COILS
WHERE THE CONDENSATE WASTE FROM AIR-CONDITIONING
COILS DISCHARGES BY DIRECT CONNECTION TO A LAVATORY
TAILPIECE OR TO AN APPROVED ACCESSIBLE INLET ON A
BATHTUB OVERFLOW, THE CONNECTION SHALL BE LOCATED IN
THE AREA CONTROLLED BY THE SAME PERSON CONTROLLING
THE AIR-CONDITIONED SPACE.
INDIRECT DRAIN TO RECEPTOR DIRECT DRAIN TO LAVATORY TAILPIECE
FINISHED
FLOOR
LOCKABLE ACCESS
PANEL IN WALL
2" WASTE DOWN
NEW 1-1/2" VENT UP 2" DRAIN
FINISHED FLOOR
COUNTER TOP
FLOOD LEVEL RIM
MINIMUM 6" ABOVE
DISHWASHER
2" WASTE DOWN
DRAIN CONNECTION
DISHWASHER
AIR GAP FITTING
Budlong
An MBE|SBE|DBE|LSBE Firm
Glendale|Downtown LA|Camarillo
W W W . B U D L O N G . C O M
CLIENT
170 MAIDEN LANE, 5TH FLOOR
SAN FRANCISCO, CA 94108
TEL 415.362.5154
WWW.PAGE-TURNBULL.COM
TITLE
ISSUE
SEAL & SIGNATURE
CONSULTANT
ARCHITECT
PROJECT
ISSUE DATE
PAGE & TURNBULL, INC. 2023 c
SCALE
DRAWN BY
CHECKED BY
JOB NUMBER
ISSUANCE TITLE ISSUANCE DATE
Job No. 24 -126
12" = 1'-0"
28-10-2024 16:55:56
Autodesk Docs://24162 Scholle House HSR/MEP23_24-126_ScholleHouse Rehabilitation.rvt
LAND PLANNING/ ENTITLEMENT
CONSULTING
434 PARK COTTAGE PLACE
CAMARILLO, CA 93012
SCHOLLE HOUSE
REHABILITATION
Scholle Farmhouse
Camrillo, CA, 93010
P7.01
PLUMBING DETAILS
Author
Checker
24162
07.24.24 AS-BUILT DRAWINGS
100% SD 10/28/2024