B. Related Requirements:

1. Section 260526 "Grounding and Bonding for Electrical Systems" specifies grounding and bonding referenced by this Section.

1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.

1.3 INFORMATIONAL SUBMITTALS
A. Manufacturer's published instructions.

1.4 QUALIFICATIONS
A. Electrical Power Testing (EPT) Technician III: Possessing active NICET EPT Level III certification. Able to manage switching procedures; conduct tests of complex equipment; analyze test and equipment data; plan a job; and lead a team. Has experience performing NFPA 70B, IEEE, and NETA electrical tests.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS
A. Regulatory Requirements: Products or components listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.

2.2 SURFACE METAL RACEWAYS AND FITTINGS
A. Source Quality Control:

1. Samples:

SURFACE RACEWAYS FOR ELECTRICAL SYSTEMS
26 05 33.23 - 2
Carlsbad Police and Fire HQ – Chiller Replacement
a. Surface Metallic Raceway Nonmetallic Cover Samples for Initial Selection:

Manufacturer's standard color sheets, showing full range of available colors for each type, [12 inch] <Insert dimension> long.

B. UL RJBT - Surface Metal Raceways and Fittings with Metal Covers:

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
a. Hubbell Wiring Device-Kellems; brand of Hubbell Electrical Solutions; Hubbell Incorporated.
b. MonoSystems, Inc.
c. Wiremold; Legrand North America, LLC.

2. Listing Criteria: Investigated, labeled, and marked by qualified electrical testing laboratory in accordance with guide information and standards specified for the following UL product categories:
a. UL CCN RJBT; including UL 5.

3. Standard Features:
a. Galvanized steel base with snap-on covers.
b. Manufacturer's standard enamel finish in color selected by Architect. c. Wiring Channels: Single. Multiple channels must be capable of housing a standard 20 to 30 A device flush within the raceway.

2.3 STRUT-TYPE CHANNEL RACEWAYS AND FITTINGS
A. Source Quality Control:

1. Samples:
a. Strut-Type Channel Raceway Nonmetallic Covers for Initial Selection:

Manufacturer's standard color sheets, showing full range of available colors for each type.

B. UL RIUU - Strut-Type Channel Raceways and Fittings with Metallic Covers:

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
a. Atkore Unistrut.
b. Cooper B-line; brand of Eaton, Electrical Sector.
c. Power-Strut; Atkore International.

2. Listing Criteria: Investigated, labeled, and marked by qualified electrical testing laboratory in accordance with guide information and standards specified for the following UL product categories:
a. UL CCN RIUU; including UL 5B.

SURFACE RACEWAYS FOR ELECTRICAL SYSTEMS
26 05 33.23 - 3
Carlsbad Police and Fire HQ – Chiller Replacement

3. Standard Features:
a. Prime coated, ready for field painting.

2.4 WIREWAYS AND AUXILIARY GUTTERS
A. UL ZOYX - Metal Wireways and Auxiliary Gutters:

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
a. Cooper B-line; brand of Eaton, Electrical Sector.
b. Hoffman; brand of nVent Electrical plc.
c. Square D; Schneider Electric USA.

2. Listing Criteria: Investigated, labeled, and marked by qualified electrical testing laboratory in accordance with guide information and standards specified for the following UL product categories:
a. UL CCN ZOYX; including UL 870.

3. Standard Features:
a. Fittings and Accessories: Include covers, couplings, offsets, elbows, expansion joints, adapters, hold-down straps, end caps, and other fittings to match and mate with wireways as required for complete system.
b. Finish: Manufacturer's standard enamel finish.
c. Wireway Covers: Screw-cover type unless otherwise indicated.

4. Other Available Features Required by the Project:
a. Degree of Protection: Type 3R unless otherwise indicated.

PART 3 - EXECUTION

3.1 INSTALLATION OF SURFACE RACEWAYS FOR ELECTRICAL SYSTEMS A. Comply with manufacturer's published instructions.

B. Reference Standards for Installation: Unless more stringent installation requirements are specified in Contract Documents or manufacturers' published instructions, comply with the following:

1. Electrical Construction: ICC IBC, ICC IFC, NFPA 1, NFPA 70, and NECA NEIS 1.

2. Electrical Safety: NFPA 70E.

3. Grounding and Bonding: NECA NEIS 331 and Article 250 of NFPA 70.

4. Communications Work: BICSI N1.

5. Work in Confined Spaces: NFPA 350.

6. Work in Basements and Other Developed Subterranean Spaces: NFPA 520.

7. Auxiliary Gutters: Article 366 of NFPA 70.

8. Surface Metal Raceway: Article 386 of NFPA 70.

SURFACE RACEWAYS FOR ELECTRICAL SYSTEMS
26 05 33.23 - 4
Carlsbad Police and Fire HQ – Chiller Replacement

9. Surface Nonmetallic Raceway: Article 388 of NFPA 70.

10. Consult Architect for resolution of conflicting requirements.

C. Special Installation Techniques:

1. Install surface raceways only where indicated on Drawings.

2. Install surface raceway with a minimum 2 inch radius control at bend points.

3. Secure surface raceway with screws or other anchor-type devices at intervals not exceeding 48 inch and with no less than two supports per straight raceway section.

Support surface raceway in accordance with manufacturer's published instructions. Tape and glue are unacceptable support methods.

D. Interfaces with Other Work:

1. Identification: Provide labels for surface raceways and associated electrical equipment. a. Identify field-installed conductors, interconnecting wiring, and components. b. Provide warning signs.

3.2 FIELD QUALITY CONTROL OF SURFACE RACEWAYS
A. Administrant for Electrical Power Tests and Inspections:

1. Administer and perform tests and inspections.

B. Tests and Inspections:

1. Perform manufacturer's recommended tests and inspections.

C. Nonconforming Work:

1. Boxes and covers will be considered defective if they do not pass tests and inspections.

2. Remove and replace defective units and retest.

D. Field Quality-Control Reports: Collect, assemble, and submit test and inspection reports.

3.3 CLEANING
A. Remove construction dust and debris from surface raceways before installing covers.

3.4 PROTECTION
A. After installation, protect surface raceways from construction activities. Remove and replace items that are contaminated, defaced, damaged, or otherwise caused to be unfit for use prior to acceptance by Owner.

END OF SECTION 26 05 33.23

IDENTIFICATION FOR ELECTRICAL SYSTEMS
26 05 53 - 1
Carlsbad Police and Fire HQ – Chiller Replacement
SECTION 26 05 53

IDENTIFICATION FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL

1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY
A. Section Includes:

1. Color and legend requirements for raceways, conductors, and warning labels and signs.

2. Labels.

3. Bands and tubes.

4. Tapes and stencils.

5. Tags.

6. Signs.

7. Cable ties.

8. Paint for identification.

9. Fasteners for labels and signs.

1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.

1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for electrical identification products.

B. Identification Schedule: For each piece of electrical equipment and electrical system components to be an index of nomenclature for electrical equipment and system components used in identification signs and labels. Use same designations indicated on Drawings.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS
A. Comply with ASME A13.1 and IEEE C2.

B. Comply with NFPA 70.

C. Comply with 29 CFR 1910.144 and 29 CFR 1910.145.

D. Comply with ANSI Z535.4 for safety signs and labels.

E. Comply with NFPA 70E requirements for arc-flash warning labels.

IDENTIFICATION FOR ELECTRICAL SYSTEMS
26 05 53 - 2
Carlsbad Police and Fire HQ – Chiller Replacement
F. Adhesive-attached labeling materials, including label stocks, laminating adhesives, and inks used by label printers, shall comply with UL 969.

G. Thermal Movements: Allow for thermal movements from ambient and surface temperature changes.

1. Temperature Change: 120 deg F (67 deg C), ambient; 180 deg F (100 deg C), material surfaces.

2.2 COLOR AND LEGEND REQUIREMENTS
A. Raceways and Cables Carrying Circuits at 600 V or Less:

1. Black letters on an orange field.

2. Legend: Indicate voltage and system or service type.

B. Color-Coding for Phase- and Voltage-Level Identification, 600 V or Less: Use colors listed below for ungrounded service feeder and branch-circuit conductors.

1. Color shall be factory applied or field applied for sizes larger than No. 8 AWG if authorities having jurisdiction permit.

2. Colors for 4160V Circuits:
a. Phase L1: Brown.
b. Phase L2 Red.
c. Phase L3: Blue.

3. Color for Neutral: White.

4. Color for Equipment Grounds: Green.

5. Colors for Isolated Grounds: Green with white stripe.

C. Raceways and Cables Carrying Circuits at More Than 600 V:

1. Black letters on an orange field.

2. Legend: "DANGER - CONCEALED HIGH VOLTAGE WIRING."
D. Warning Label Colors:

1. Identify system voltage with black letters on an orange background.

E. Warning labels and signs shall include, but are not limited to, the following legends:

1. Multiple Power Source Warning: "DANGER - ELECTRICAL SHOCK HAZARD - EQUIPMENT HAS MULTIPLE POWER SOURCES."

2. Workspace Clearance Warning: "WARNING - OSHA REGULATION - AREA IN FRONT OF ELECTRICAL EQUIPMENT MUST BE KEPT CLEAR FOR 36 INCHES (915 MM)." F. Equipment Identification Labels:

1. Black letters on a white-field.

2. Black letters on a green-field for equipment fed from UPS System.

2.3 LABELS
A. Vinyl Wraparound Labels: Preprinted, flexible labels laminated with a clear, weather- and chemical-resistant coating and matching wraparound clear adhesive tape for securing label ends.

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Brady Corporation.
b. Champion America.
c. Panduit Corp.

IDENTIFICATION FOR ELECTRICAL SYSTEMS
26 05 53 - 3
Carlsbad Police and Fire HQ – Chiller Replacement

d. Seton Identification Products.

B. Snap-around Labels: Slit, pretensioned, flexible, preprinted, color-coded acrylic sleeves, with diameters sized to suit diameters and that stay in place by gripping action.

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Brady Corporation.
b. Marking Services, Inc.
c. Panduit Corp.
d. Seton Identification Products.

C. Self-Adhesive Wraparound Labels: Preprinted, 3-mil- (0.08-mm-) thick, vinyl flexible label with acrylic pressure-sensitive adhesive.

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Brady Corporation.
b. Ideal Industries, Inc.
c. Panduit Corp.
d. Seton Identification Products.

2. Self-Lamination: Clear; UV-, weather- and chemical-resistant; self-laminating, protective shield over the legend. Labels sized such that the clear shield overlaps the entire printed legend.

3. Marker for Labels: Machine-printed, permanent, waterproof, black ink recommended by printer manufacturer.

D. Self-Adhesive Labels: Vinyl, thermal, transfer-printed, 3-mil- (0.08-mm-) thick, multicolor, weather- and UV-resistant, pressure-sensitive adhesive labels, configured for intended use and location.

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Brady Corporation.
b. Ideal Industries, Inc.
c. Panduit Corp.
d. Seton Identification Products.

2. Minimum Nominal Size:
a. 1-1/2 by 6 inches (37 by 150 mm) for raceway and conductors. b. 3-1/2 by 5 inches (76 by 127 mm) for equipment.
c. As required by authorities having jurisdiction.

2.4 BANDS AND TUBES
A. Snap-around, Color-Coding Bands: Slit, pretensioned, flexible, solid-colored acrylic sleeves, 2 inches (50 mm) long, with diameters sized to suit diameters and that stay in place by gripping action.

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Brady Corporation.
b. HellermannTyton.
c. Marking Services, Inc.
d. Panduit Corp.

IDENTIFICATION FOR ELECTRICAL SYSTEMS
26 05 53 - 4
Carlsbad Police and Fire HQ – Chiller Replacement
B. Heat-Shrink Preprinted Tubes: Flame-retardant polyolefin tubes with machine-printed identification labels, sized to suit diameter and shrunk to fit firmly. Full shrink recovery occurs at a maximum of 200 deg F (93 deg C). Comply with UL 224.

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Brady Corporation.
b. Panduit Corp.

2.5 TAPES AND STENCILS
A. Marker Tapes: Vinyl or vinyl-cloth, self-adhesive wraparound type, with circuit identification legend machine printed by thermal transfer or equivalent process.

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Carlton Industries, LP.
b. Ideal Industries, Inc.
c. Panduit Corp.

B. Self-Adhesive Vinyl Tape: Colored, heavy duty, waterproof, fade resistant; not less than 3 mils (0.08 mm) thick by 1 to 2 inches (25 to 50 mm) wide; compounded for outdoor use.

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Brady Corporation.
b. Carlton Industries, LP.
c. Marking Services, Inc.

C. Tape and Stencil: 4-inch- (100-mm-) wide black stripes on 10-inch (250-mm) centers placed diagonally over orange background and are 12 inches (300 mm) wide. Stop stripes at legends.

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. HellermannTyton.
b. LEM Products Inc.
c. Marking Services, Inc.
d. Seton Identification Products.

D. Floor Marking Tape: 2-inch- (50-mm-) wide, 5-mil (0.125-mm) pressure-sensitive vinyl tape, with yellow and black stripes and clear vinyl overlay.

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Carlton Industries, LP.
b. Seton Identification Products.

E. Underground-Line Warning Tape:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Brady Corporation.
b. Ideal Industries, Inc.
c. Marking Services, Inc.
d. Seton Identification Products.

2. Tape:
a. Recommended by manufacturer for the method of installation and suitable to identify and locate underground electrical and communications utility lines. b. Printing on tape shall be permanent and shall not be damaged by burial operations.

IDENTIFICATION FOR ELECTRICAL SYSTEMS
26 05 53 - 5
Carlsbad Police and Fire HQ – Chiller Replacement

c. Tape material and ink shall be chemically inert and not subject to degradation when exposed to acids, alkalis, and other destructive substances commonly found in soils.

3. Color and Printing:
a. Comply with ANSI Z535.1, ANSI Z535.2, ANSI Z535.3, ANSI Z535.4, and ANSI Z535.5.
b. Inscriptions for Red-Colored Tapes: "ELECTRIC LINE, HIGH VOLTAGE".

4. Tag: Type I:
a. Pigmented polyolefin, bright colored, continuous-printed on one side with the inscription of the utility, compounded for direct-burial service. b. Width: 3 inches (75 mm).
c. Thickness: 4 mils (0.1 mm).
d. Weight: 18.5 lb/1000 sq. ft. (9.0 kg/100 sq. m).
e. Tensile according to ASTM D 882: 30 lbf (133.4 N) and 2500 psi (17.2 MPa).

5. Tag: Type II:
a. Multilayer laminate, consisting of high-density polyethylene scrim coated with pigmented polyolefin; bright colored, continuous-printed on one side with the inscription of the utility, compounded for direct-burial service. b. Width: 3 inches (75 mm).
c. Thickness: 12 mils (0.3 mm).
d. Weight: 36.1 lb/1000 sq. ft. (17.6 kg/100 sq. m).
e. Tensile according to ASTM D 882: 400 lbf (1780 N) and 11,500 psi (79.2 MPa).

6. Tag: Type ID:
a. Detectable three-layer laminate, consisting of a printed pigmented polyolefin film, a solid aluminum-foil core, and a clear protective film that allows inspection of the continuity of the conductive core; bright colored, continuous-printed on one side with the inscription of the utility, compounded for direct-burial service. b. Width: 3 inches (75 mm).
c. Overall Thickness: 5 mils (0.125 mm).
d. Foil Core Thickness: 0.35 mil (0.00889 mm).
e. Weight: 28 lb/1000 sq. ft. (13.7 kg/100 sq. m).
f. Tensile according to ASTM D 882: 70 lbf (311.3 N) and 4600 psi (31.7 MPa).

7. Tag: Type IID:
a. Reinforced, detectable three-layer laminate, consisting of a printed pigmented woven scrim, a solid aluminum-foil core, and a clear protective film that allows inspection of the continuity of the conductive core; bright-colored, continuous- printed on one side with the inscription of the utility, compounded for direct-burial service.
b. Width: 3 inches (75 mm).
c. Overall Thickness: 8 mils (0.2 mm).
d. Foil Core Thickness: 0.35 mil (0.00889 mm).
e. Weight: 34 lb/1000 sq. ft. (16.6 kg/100 sq. m).
f. Tensile according to ASTM D 882: 300 lbf (1334 N) and 12,500 psi (86.1 MPa).

F. Stenciled Legend: In nonfading, waterproof, black ink or paint. Minimum letter height shall be 1 inch (25 mm).

2.6 TAGS
A. Metal Tags: Brass or aluminum, 2 by 2 by 0.05 inch (50 by 50 by 1.3 mm), with stamped legend, punched for use with self-locking cable tie fastener.

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

IDENTIFICATION FOR ELECTRICAL SYSTEMS
26 05 53 - 6
Carlsbad Police and Fire HQ – Chiller Replacement
a. Brady Corporation.
b. Carlton Industries, LP.
c. Marking Services, Inc.
d. Seton Identification Products.

B. Nonmetallic Preprinted Tags: Polyethylene tags, 0.023 inch (0.58 mm) thick, color-coded for phase and voltage level, with factory printed permanent designations; punched for use with self- locking cable tie fastener.

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Brady Corporation.
b. Carlton Industries, LP.
c. Marking Services, Inc.
d. Panduit Corp.
e. Seton Identification Products.

C. Write-on Tags:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Carlton Industries, LP.
b. LEM Products Inc.
c. Seton Identification Products.

2. Polyester Tags: 0.015 inch (0.38 mm) thick, with corrosion-resistant grommet and cable tie for attachment.

3. Marker for Tags: Machine-printed, permanent, waterproof, black ink marker recommended by printer manufacturer.

2.7 SIGNS
A. Baked-Enamel Signs:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Carlton Industries, LP.
b. Champion America.
c. Marking Services, Inc.

2. Preprinted aluminum signs, punched or drilled for fasteners, with colors, legend, and size required for application.

3. 1/4-inch (6.4-mm) grommets in corners for mounting.

4. Nominal Size: 7 by 10 inches (180 by 250 mm).

B. Metal-Backed Butyrate Signs:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Brady Corporation.
b. Champion America.
c. Marking Services, Inc.

2. Weather-resistant, nonfading, preprinted, cellulose-acetate butyrate signs, with 0.0396- inch (1-mm) galvanized-steel backing, punched and drilled for fasteners, and with colors, legend, and size required for application.

3. 1/4-inch (6.4-mm) grommets in corners for mounting.

4. Nominal Size: 10 by 14 inches (250 by 360 mm).

C. Laminated Acrylic or Melamine Plastic Signs:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

IDENTIFICATION FOR ELECTRICAL SYSTEMS
26 05 53 - 7
Carlsbad Police and Fire HQ – Chiller Replacement

a. Brady Corporation.
b. Carlton Industries, LP.
c. Marking Services, Inc.

2. Engraved legend.

3. Thickness:
a. For signs up to 20 sq. in. (129 sq. cm), minimum 1/16 inch (1.6 mm) thick. b. For signs larger than 20 sq. in. (129 sq. cm), 1/8 inch (3.2 mm) thick. c. Engraved legend with white letters on a dark gray background. d. Self-adhesive.
e. Framed with mitered acrylic molding and arranged for attachment at applicable equipment.

2.8 CABLE TIES
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. HellermannTyton.

2. Ideal Industries, Inc.

3. Marking Services, Inc.

4. Panduit Corp.

B. General-Purpose Cable Ties: Fungus inert, self-extinguishing, one piece, self-locking, and Type 6/6 nylon.

1. Minimum Width: 3/16 inch (5 mm).

2. Tensile Strength at 73 Deg F (23 Deg C) according to ASTM D 638: 12,000 psi (82.7 MPa).

3. Temperature Range: Minus 40 to plus 185 deg F (Minus 40 to plus 85 deg C).

4. Color: Black, except where used for color-coding.

C. UV-Stabilized Cable Ties: Fungus inert, designed for continuous exposure to exterior sunlight, self-extinguishing, one piece, self-locking, and Type 6/6 nylon.

1. Minimum Width: 3/16 inch (5 mm).

2. Tensile Strength at 73 Deg F (23 Deg C) according to ASTM D 638: 12,000 psi (82.7 MPa).

3. Temperature Range: Minus 40 to plus 185 deg F (Minus 40 to plus 85 deg C).

4. Color: Black.

D. Plenum-Rated Cable Ties: Self-extinguishing, UV stabilized, one piece, and self-locking.

1. Minimum Width: 3/16 inch (5 mm).

2. Tensile Strength at 73 Deg F (23 Deg C) according to ASTM D 638: 7000 psi (48.2 MPa).

3. UL 94 Flame Rating: 94V-0.

4. Temperature Range: Minus 50 to plus 284 deg F (Minus 46 to plus 140 deg C).

5. Color: Black.

2.9 MISCELLANEOUS IDENTIFICATION PRODUCTS
A. Paint: Comply with requirements in painting Sections for paint materials and application requirements. Retain paint system applicable for surface material and location (exterior or interior).

B. Fasteners for Labels and Signs: Self-tapping, stainless-steel screws or stainless-steel machine screws with nuts and flat and lock washers.

IDENTIFICATION FOR ELECTRICAL SYSTEMS
26 05 53 - 8
Carlsbad Police and Fire HQ – Chiller Replacement
PART 3 - EXECUTION

3.1 PREPARATION
A. Self-Adhesive Identification Products: Before applying electrical identification products, clean substrates of substances that could impair bond, using materials and methods recommended by manufacturer of identification product.

3.2 INSTALLATION
A. Verify and coordinate identification names, abbreviations, colors, and other features with requirements in other Sections requiring identification applications, Drawings, Shop Drawings, manufacturer's wiring diagrams, and operation and maintenance manual. Use consistent designations throughout Project.

B. Install identifying devices before installing acoustical ceilings and similar concealment.

C. Verify identity of each item before installing identification products.

D. Coordinate identification with Project Drawings, manufacturer's wiring diagrams, and operation and maintenance manual.

E. Apply identification devices to surfaces that require finish after completing finish work.

F. Install signs with approved legend to facilitate proper identification, operation, and maintenance of electrical systems and connected items.

G. System Identification for Raceways and Cables under 600 V: Identification shall completely encircle cable or conduit. Place identification of two-color markings in contact, side by side.

1. Secure tight to surface of conductor, cable, or raceway.

H. Auxiliary Electrical Systems Conductor Identification: Identify field-installed alarm, control, and signal connections.

I. Emergency Operating Instruction Signs: Install instruction signs with white legend on a red background with minimum 3/8-inch- (10-mm-) high letters for emergency instructions at equipment used for power transfer.

J. Elevated Components: Increase sizes of labels, signs, and letters to those appropriate for viewing from the floor.

K. Accessible Fittings for Raceways: Identify the covers of each junction and pull box of the following systems with the wiring system legend and system voltage. System legends shall be as follows:

1. "EMERGENCY POWER."

2. "POWER."

3. "UPS."
L. Vinyl Wraparound Labels:

1. Secure tight to surface of raceway or cable at a location with high visibility and accessibility.

2. Attach labels that are not self-adhesive type with clear vinyl tape, with adhesive appropriate to the location and substrate.

IDENTIFICATION FOR ELECTRICAL SYSTEMS
26 05 53 - 9
Carlsbad Police and Fire HQ – Chiller Replacement

M. Snap-around Labels: Secure tight to surface at a location with high visibility and accessibility.

N. Self-Adhesive Wraparound Labels: Secure tight to surface at a location with high visibility and accessibility.

O. Self-Adhesive Labels:

1. On each item, install unique designation label that is consistent with wiring diagrams, schedules, and operation and maintenance manual.

2. Unless otherwise indicated, provide a single line of text with 1/2-inch- (13-mm-) high letters on 1-1/2-inch- (38-mm-) high label; where two lines of text are required, use labels 2 inches (50 mm) high.

P. Snap-around Color-Coding Bands: Secure tight to surface at a location with high visibility and accessibility.

Q. Heat-Shrink, Preprinted Tubes: Secure tight to surface at a location with high visibility and accessibility.

R. Marker Tapes: Secure tight to surface at a location with high visibility and accessibility.

S. Self-Adhesive Vinyl Tape: Secure tight to surface at a location with high visibility and accessibility.

1. Field-Applied, Color-Coding Conductor Tape: Apply in half-lapped turns for a minimum distance of 6 inches (150 mm) where splices or taps are made. Apply last two turns of tape with no tension to prevent possible unwinding.

T. Tape and Stencil: Comply with requirements in painting Sections for surface preparation and paint application.

U. Floor Marking Tape: Apply stripes to finished surfaces following manufacturer's written instructions.

V. Underground Line Warning Tape:

1. During backfilling of trenches, install continuous underground-line warning tape directly above cable or raceway at 6 to 8 inches (150 to 200 mm) below finished grade. Use multiple tapes where width of multiple lines installed in a common trench or concrete envelope exceeds 16 inches (400 mm) overall.

2. Install underground-line warning tape for direct-buried cables and cables in raceways.

W. Metal Tags:

1. Place in a location with high visibility and accessibility.

2. Secure using UV-stabilized cable ties.

X. Nonmetallic Preprinted Tags:

1. Place in a location with high visibility and accessibility.

2. Secure using UV-stabilized cable ties.

Y. Write-on Tags:

1. Place in a location with high visibility and accessibility.

2. Secure using UV-stabilized cable ties.

Z. Baked-Enamel Signs:

IDENTIFICATION FOR ELECTRICAL SYSTEMS
26 05 53 - 10
Carlsbad Police and Fire HQ – Chiller Replacement

1. Attach signs that are not self-adhesive type with mechanical fasteners appropriate to the location and substrate.

2. Unless otherwise indicated, provide a single line of text with 1/2-inch- (13-mm-) high letters on minimum 1-1/2-inch- (38-mm-) high sign; where two lines of text are required, use signs minimum 2 inches (50 mm) high.

AA. Metal-Backed Butyrate Signs:

1. Attach signs that are not self-adhesive type with mechanical fasteners appropriate to the location and substrate.

2. Unless otherwise indicated, provide a single line of text with 1/2-inch- (13-mm-) high letters on 1-1/2-inch- (38-mm-) high sign; where two lines of text are required, use labels 2 inches (50 mm) high.

BB. Laminated Acrylic or Melamine Plastic Signs:

1. Attach signs that are not self-adhesive type with mechanical fasteners appropriate to the location and substrate.

2. Unless otherwise indicated, provide a single line of text with 1/2-inch- (13-mm-) high letters on 1-1/2-inch- (38-mm-) high sign; where two lines of text are required, use labels 2 inches (50 mm) high.

CC. Cable Ties: General purpose, for attaching tags, except as listed below:

1. Outdoors: UV-stabilized nylon.

2. In Spaces Handling Environmental Air: Plenum rated.

3.3 IDENTIFICATION SCHEDULE
A. Install identification materials and devices at locations for most convenient viewing without interference with operation and maintenance of equipment. Install access doors or panels to provide view of identifying devices.

B. Identify conductors, cables, and terminals in enclosures and at junctions, terminals, pull points, and locations of high visibility. Identify by system and circuit designation.

C. Accessible Raceways, Armored and Metal-Clad Cables, More Than 600 V: Vinyl wraparound labels.

1. Locate identification at changes in direction, at penetrations of walls and floors, at 50-foot (15-m) maximum intervals in straight runs, and at 25-foot (7.6-m) maximum intervals in congested areas.

D. Accessible Raceways and Metal-Clad Cables, 600 V or Less, for Service, Feeder, and Branch Circuits, More Than 30 A and 120 V to Ground: Identify with self-adhesive raceway labels.

1. Locate identification at changes in direction, at penetrations of walls and floors, at 50-foot (15-m) maximum intervals in straight runs, and at 25-foot (7.6-m) maximum intervals in congested areas.

E. Accessible Fittings for Raceways and Cables within Buildings: Identify the covers of each junction and pull box of the following systems with self-adhesive labels containing the wiring system legend and system voltage. System legends shall be as follows:

1. "EMERGENCY POWER."

2. "POWER."

3. "UPS."
F. Power-Circuit Conductor Identification, 600 V or Less: For conductors in vaults, pull and junction boxes, manholes, and handholes, use vinyl wraparound labels to identify the phase.

IDENTIFICATION FOR ELECTRICAL SYSTEMS
26 05 53 - 11
Carlsbad Police and Fire HQ – Chiller Replacement

1. Locate identification at changes in direction, at penetrations of walls and floors, at 50-foot (15-m) maximum intervals in straight runs, and at 25-foot (7.6-m) maximum intervals in congested areas.

G. Control-Circuit Conductor Identification: For conductors and cables in pull and junction boxes, manholes, and handholes, use self-adhesive label] with the conductor or cable designation, origin, and destination.

H. Control-Circuit Conductor Termination Identification: For identification at terminations, provide self-adhesive labels with the conductor designation.

I. Conductors to Be Extended in the Future: Attach marker tape to conductors and list source.

J. Auxiliary Electrical Systems Conductor Identification: Self-adhesive vinyl tape that is uniform and consistent with system used by manufacturer for factory-installed connections.

1. Identify conductors, cables, and terminals in enclosures and at junctions, terminals, and pull points. Identify by system and circuit designation.

K. Locations of Underground Lines: Underground-line warning tape for power, lighting, communication, and control wiring and optical-fiber cable.

L. Workspace Indication: Apply floor marking tape or tape and stencil to finished surfaces. Show working clearances in the direction of access to live parts. Workspace shall comply with NFPA 70 and 29 CFR 1926.403 unless otherwise indicated. Do not install at flush-mounted panelboards and similar equipment in finished spaces.

M. Instructional Signs: Self-adhesive labels, including the color code for grounded and ungrounded conductors.

N. Warning Labels for Indoor Cabinets, Boxes, and Enclosures for Power and Lighting: Self- adhesive labels.

1. Apply to exterior of door, cover, or other access.

2. For equipment with multiple power or control sources, apply to door or cover of equipment, including, but not limited to, the following:
a. Power-transfer switches.
b. Controls with external control power connections.

O. Arc Flash Warning Labeling: Self-adhesive labels.

P. Operating Instruction Signs: Baked-enamel warning signs.

Q. Emergency Operating Instruction Signs: Baked-enamel warning signs with white legend on a red background with minimum 3/8-inch- (10-mm-) high letters for emergency instructions at equipment used for power transfer.

R. Equipment Identification Labels:

1. Indoor Equipment: Baked-enamel signs.

2. Outdoor Equipment: Laminated acrylic or melamine sign.

3. Equipment to Be Labeled:
a. Panelboards: Typewritten directory of circuits in the location provided by panelboard manufacturer. Panelboard identification shall be in the form of a engraved, laminated acrylic or melamine label.
b. Enclosures and electrical cabinets.

IDENTIFICATION FOR ELECTRICAL SYSTEMS
26 05 53 - 12
Carlsbad Police and Fire HQ – Chiller Replacement
c. Access doors and panels for concealed electrical items. d. Switchgear.
e. Switchboards.
f. Transformers: Label that includes tag designation indicated on Drawings for the transformer, feeder, and panelboards or equipment supplied by the secondary. g. Substations.
h. Emergency system boxes and enclosures.
i. Motor-control centers.
j. Enclosed switches.
k. Enclosed circuit breakers.
l. Enclosed controllers.
m. Variable-speed controllers.
n. Push-button stations.
o. Power-transfer equipment.
p. Contactors.
q. Remote-controlled switches, dimmer modules, and control devices. r. Battery-inverter units.
s. Battery racks.
t. Power-generating units.
u. Monitoring and control equipment.
v. UPS equipment.

END OF SECTION 26 05 53

LOW-VOLTAGE SWITCHGEAR
26 23 00 - 1
Carlsbad Police and Fire HQ – Chiller Replacement
SECTION 26 23 00

LOW-VOLTAGE SWITCHGEAR
PART 1 - GENERAL

1.1 SUMMARY
A. The Work of This Section Includes:

1. Metal-enclosed, low-voltage switchgear, with power circuit breakers and metering and control accessories.

1. Switchgear structure.

2. Additional requirements for outdoor switchgear.

3. Circuit breakers.

1.2 PREINSTALLATION MEETINGS
A. Preinstallation Conference: Conduct conference at Project site.

B. Preinstallation Coordination Meeting(s): For switchgear. Conduct meeting(s) at Project site before.

1. Attendees: Installers, fabricators, representatives of manufacturers, and administrants for field tests and inspections. Notify Architect, and Owner's Commissioning Authority of scheduled meeting dates.

1.3 ACTION SUBMITTALS
A. Product Data:

1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for switchgear.

2. Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories.

B. Shop Drawings:

1. For low-voltage switchgear.

1. System Power One-Line Diagrams: Depict power sources, feeders, distribution components, and major loads. Include as-built data for low-voltage power switchgear and connections as follows:
1) Frame size of circuit breakers.
2) Trip rating for circuit breakers.
3) Conduit and wire size for feeders.

LOW-VOLTAGE SWITCHGEAR
26 23 00 - 2
Carlsbad Police and Fire HQ – Chiller Replacement

2. Include plans, elevations, sections, shipping splits, and mounting details.

3. Include details of equipment assemblies. Indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of field connections.

4. Wire Termination Diagrams and Schedules: Include diagrams for power, signal, and control wiring. Identify terminals and wiring designations and color-codes to facilitate installation, operation, and maintenance. Indicate recommended types, wire sizes, and circuiting arrangements for field-installed wiring, and show circuit protection features. Differentiate between manufacturer-installed and field-installed wiring.

5. Block Diagram: Show interconnections between components specified in this Section and devices furnished with power distribution system components.

Indicate data communication paths and identify networks, data buses, data gateways, concentrators, and other devices used. Describe characteristics of network and other data communication lines.

6. Indicate short-time and short-circuit current rating of switchgear assembly.

7. Include features, characteristics, ratings, and factory settings of individual overcurrent protective devices and auxiliary components.

8. Include mimic-bus diagram.

1.4 INFORMATIONAL SUBMITTALS

1.5 CLOSEOUT SUBMITTALS
A. System Power Riser Diagram: For switchgear, using non-fugitive ink on high-quality paper. Post on wall at switchgear location.

1.6 DELIVERY, STORAGE, AND HANDLING
A. Indoor Switchgear Storage: Store in dry, clean location, placed on level surface to prevent strain and possible distortion. During construction period, provide protection against dust, dirt, falling objects, dripping water, water, excessive moisture, and other possible causes of damage to equipment. Temporary covering may not restrict ventilation and may not be removed until equipment is ready for installation. Take special precaution to keep equipment sufficiently warm with adequate ventilation to prevent condensation during storage period. Install temporary heating if necessary.

B. When provisions for temporary power connection are provided as part of switchgear assembly, provisions must be included to prevent energization of primary buses.

C. Ventilation openings must be left open to permit proper air circulation.

PART 2 - PRODUCTS

2.1 LOW-VOLTAGE SWITCHGEAR
A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:

1. Eaton.

LOW-VOLTAGE SWITCHGEAR
26 23 00 - 3
Carlsbad Police and Fire HQ – Chiller Replacement

2. Siemens Industry, Inc., Energy Management Division.

3. Square D; Schneider Electric USA.

2.2 SYSTEM DESCRIPTION
A. Description: Metal-enclosed, low-voltage switchgear with power circuit breakers, with accessories and metering components.

1. Electrical Components, Devices, and Accessories: Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.

2. Comply with IEEE C37.20.1.

3. Listed and labeled as complying with UL 1558.

4. Listed and labeled for use as service entrance equipment.

2.3 PERFORMANCE REQUIREMENTS
A. Capacities and Characteristics:

1. Nominal System Voltage: 480V, 3-phase, four wire, 60 Hz.

2. Rated Maximum Voltage: 600V.

3. Rated Power Frequency: 60 Hz.

4. Rated Insulation Level: Power frequency withstand must be not less than 2.2 kV(rms).

5. Rated Continuous Current:

1. Main-Bus Continuous: 400 A.

2. Vertical Section Bus Riser: Equal to frame size of low-voltage power circuit breaker connected to that riser.

6. Rated Short-Circuit Withstand Current: 42 000 A(sym).

7. Short-Time and Short-Circuit Current: Match rating of integrated short-circuit current rating.

2.4 SWITCHGEAR STRUCTURE
A. Bus isolation barriers must be arranged to isolate line bus from load bus at main and tie circuit breaker. Extend section barriers between main and tie circuit breakers to rear of section.

B. Allow the following circuit-breaker functions to be performed when compartment door is closed:

1. Operate manual charging system.

2. Open and close circuit breaker.

3. Examine and adjust trip unit.

4. Read breaker nameplate.

C. Install instrument compartments when additional space is required for metering and instrumentation. Allow for routing of instrumentation, control and communications wires, and cables.

D. Switchgear Bus:

1. Use bus bars to connect compartments and vertical sections. Cable connections are not permitted.

LOW-VOLTAGE SWITCHGEAR
26 23 00 - 4
Carlsbad Police and Fire HQ – Chiller Replacement

2. Main Phase Bus: Uniform capacity entire length of assembly.

3. Neutral Bus: 100 percent of phase-bus ampacity unless otherwise indicated. Equip bus with pressure-connector terminations for outgoing circuit neutral conductors. Include braces for neutral-bus extensions for busway feeders.

4. Ground Bus: Uniform capacity entire length of assembly, with pressure connector terminations for feeder and branch-circuit ground conductors, minimum size 1/4 by 2 inch.

5. Vertical Section Bus Size: Fully rated to system continuous current, equal to horizontal bus.

6. Bus Material and Connections:

1. Phase- and Neutral-Bus Material:
1) Hard-drawn copper of 98 percent minimum conductivity, with copper feeder circuit-breaker line connections.
2) Silver- or tin-plated, high-strength, electrical-grade aluminum alloy, with copper or tin-plated aluminum circuit-breaker line connections. 3) Hard-drawn copper of 98 percent minimum conductivity or tin-plated, high- strength, electrical-grade aluminum alloy.

2. Use copper for connecting circuit-breaker line to copper bus.

7. Neutral Disconnect Link: Bolted, uninsulated, bus, arranged to connect neutral bus to ground bus.

E. Circuit-Breaker Compartment:

1. Primary Disconnect: Mount on stationary part of compartment. Disconnect must consist of set of contacts extending to rear through insulating support barrier, and of corresponding moving finger contacts on power circuit-breaker studs, which engage in only connected position. Assembly must provide multiple silver-to-silver full floating, spring-loaded, high-pressure-point contacts with uniform pressure on fingers. Load studs must connect to bus extensions that terminate in solderless terminals in rear cable compartment.

F. Auxiliary Compartments: Match and align with basic switchgear assembly. Include the following:

1. Utility metering compartment that complies with utility-company requirements.

2. Incoming-line pull sections.

3. Hinged front panels for access to metering, accessory, and blank compartments.

2.5 CIRCUIT BREAKERS
A. Drawout type, unfused, power operated, with electromechanical or electronic trip devices.

Comply with IEEE C37.13, IEEE C37.13a, and UL 1066.

B. Ratings: For continuous, interrupting, and short-time current ratings for circuit breakers; voltage and frequency ratings same as switchgear. Comply with IEEE C37.16.

1. Circuit breakers must have 30-cycle short-time withstand ratings equal to their symmetrical interrupting ratings through 85 000 A, whether or not equipped with instantaneous trip protection.

C. Operator Display: Located on face of circuit breaker.

LOW-VOLTAGE SWITCHGEAR
26 23 00 - 5
Carlsbad Police and Fire HQ – Chiller Replacement

1. Electrical operation buttons to open and close circuit breaker. Provide clear lockable cover over buttons.

2. Indicator to show position of circuit-breaker contacts, status of closing springs, and circuit-breaker position in its compartment.

D. Padlocking Provisions: For installing at least three padlocks on circuit breakers to secure its enclosure.

E. Mechanical Interlocking of Circuit Breakers: Uses mechanical tripping lever or equivalent design and electrical interlocks.

2.6 SOURCE QUALITY CONTROL
A. Factory Tests and Inspections: Test and inspect low-voltage switchgear, by, or under supervision of, qualified electrical testing laboratory recognized by authorities having jurisdiction, in accordance with IEEE C37.20.1 before delivering to site. Affix label with name and date of manufacturer's certification of system compliance on control units.

1. Dielectric Tests: Perform power-frequency withstand tests to demonstrate ability of insulation system to withstand voltages listed in IEEE C37.20.1. Voltage must be increased gradually from zero to the required test value within 5 to 10 seconds and must be held at that value for one minute.

2. Perform mechanical operation tests to ensure proper functioning of operating mechanism, mechanical interlocks, and interchangeability of removable elements that are designed to be interchangeable.

3. Test effectiveness of grounding of metal-case instrument transformer frame or case.

4. Verify that control wiring is correct by verifying continuity. Perform electrical operation of component devices to ensure that they function properly and in intended sequence.

5. Perform control wiring insulation tests.

6. Verify correct polarity of connections between instrument transformers and meters and relays.

B. Nonconforming Work:

1. Low-voltage switchgear assembly will be considered defective if it does not pass tests and inspections.

C. Prepare test and inspection reports.

PART 3 - EXECUTION

3.1 EXAMINATION
A. Examine areas and space conditions for compliance with requirements for secondary unit substations and other conditions affecting performance of the Work.

B. Examine roughing-in of conduits and grounding systems to verify the following:

1. Wiring entries comply with layout requirements.

2. Entries are within conduit-entry tolerances specified by manufacturer, and no feeders will have to cross section barriers to reach load or line lugs.

LOW-VOLTAGE SWITCHGEAR
26 23 00 - 6
Carlsbad Police and Fire HQ – Chiller Replacement
C. Examine walls, floors, roofs, and concrete bases for suitable conditions where switchgear will be installed.

D. Verify that ground connections are in place and that requirements in Section 260526 "Grounding and Bonding for Electrical Systems" have been met. Maximum ground resistance must be 10 Ω at switchgear location.

E. On delivery of switchgear and prior to unloading, inspect equipment for damage.

1. Verify that tie rods and chains are undamaged and tight, and that blocking and bracing are tight.

2. Verify that there is no evidence of load shifting in transit, and that readings from transportation shock recorders, if equipped, are within manufacturer's published instructions.

3. Examine switchgear for external damage, including dents or scratches in doors and sill, and termination provisions.

4. Compare switchgear and accessories received with bill of materials to verify that shipment is complete. Verify that switchgear and accessories comply with manufacturer's published instructions and Shop Drawings. If shipment is incomplete or does not comply with Project requirements, notify manufacturer in writing immediately.

5. Unload switchgear, observing packing label warnings and handling instructions.

6. Open compartment doors and inspect components for damage or displaced parts, loose or broken connections, cracked or chipped insulators, bent mounting flanges, dirt or foreign material, and water or moisture.

F. Handling:

1. Handle switchgear, in accordance with manufacturer's published instructions; avoid damage to enclosure, termination compartments, base, frame, tank, and internal components. Do not subject switchgear to impact, jolting, jarring, or rough handling.

2. Protect switchgear compartments against entrance of dust, rain, and snow.

3. Transport switchgear upright, to avoid internal stresses on equipment mounting assemblies. Do not tilt or tip switchgear.

4. Use spreaders or lifting beam to obtain vertical lift and to protect switchgear from straps bearing against enclosure. Lifting cable pull angles may not be greater than 15 degrees from vertical.

5. Do not damage structure when handling switchgear.

G. Proceed with installation only after examinations are complete and unsatisfactory conditions have been corrected.

3.2 INSTALLATION
A. Maintain minimum clearances and workspace at equipment in accordance with manufacturer's published instructions and NFPA 70.

3.3 CONNECTIONS
A. Ground equipment in accordance with Section 260526 "Grounding and Bonding for Electrical Systems."
B. Grounding Connections at Exterior Locations:

LOW-VOLTAGE SWITCHGEAR
26 23 00 - 7
Carlsbad Police and Fire HQ – Chiller Replacement

1. Install tinned bare copper conductors not smaller than 4/0 AWG, for ground conductors buried not less than 30 inch below grade interconnecting grounding electrodes.

2. Bond surge arrester and neutrals directly to switchgear enclosure and then to grounding electrode system with bare copper conductors, sized as indicated.

3. Keep lead lengths as short as practicable with no kinks or sharp bends.

4. Make joints in grounding conductors and loops by exothermic weld or compression connector.

C. Terminate grounding and bonding conductors on common equipment grounding terminal on switchgear enclosure. Install supplemental terminal bars, lugs, and bonding jumpers as required to accommodate number of conductors for termination.

3.4 IDENTIFICATION
A. Install warning signs as required to comply with OSHA 29 CFR 1910.269.

B. Compartment Nameplates: Engraved, melamine plastic for compartments, mounted with corrosion-resistant screws.

C. Arc-Flash Warning Labels:

1. Label must have orange header with wording, "WARNING, ARC-FLASH HAZARD," and must include the following information taken directly from arc-flash hazard analysis:
1) Location designation.
2) Nominal voltage.
3) Flash protection boundary.
4) Hazard risk category.
5) Incident energy.
6) Working distance.
7) Engineering report number, revision number, and issue date.

2. Labels must be machine printed, with no field-applied markings.

3.5 FIELD QUALITY CONTROL
A. Tests and Inspections:

1. Comply with provisions of "Testing and Test Methods" Chapter in NFPA 70B and NETA ATS.

2. After installing switchgear and after electrical circuitry has been energized, test for compliance with requirements.

3. Perform visual and mechanical inspections and electrical tests stated in NETA ATS.

Certify compliance with test parameters.

4. Visual and Mechanical Inspection:

1. Verify that fuse and circuit-breaker sizes and types correspond to Drawings and coordination study.

2. Verify that current and voltage transformer ratios correspond to Drawings.

3. Inspect bolted electrical connections for high resistance using one of the following two methods:

LOW-VOLTAGE SWITCHGEAR
26 23 00 - 8
Carlsbad Police and Fire HQ – Chiller Replacement
1) Use low-resistance ohmmeter to compare bolted-connection resistance values to values of similar connections. Investigate values that deviate from those of similar bolted connections by more than 50 percent of lowest value. 2) Verify tightness of accessible bolted electrical connections by calibrated torque-wrench method in accordance with manufacturer's published data or NETA ATS, Table 100.12. Bolt-torque levels must be in accordance with manufacturer's published data. In absence of manufacturer's published data, use NETA ATS, Table 100.12.

4. Confirm correct operation and sequencing of electrical and mechanical interlock systems.
1) Attempt closure on locked-open devices. Attempt to open locked-closed devices.
2) Make key exchange with devices operated in off-normal positions.

5. Verify appropriate lubrication on moving current-carrying parts and on moving and sliding surfaces.

6. Inspect insulators for evidence of physical damage or contaminated surfaces.

7. Verify correct barrier and shutter installation and operation.

8. Exercise active components.

9. Inspect mechanical indicating devices for correct operation.

10. Verify that filters are in place and that vents are clear.

11. Perform visual and mechanical inspection of instrument transformers in accordance with "Instrument Transformer Field Tests" Paragraph.

12. Inspect control power transformers.
1) Inspect for physical damage, cracked insulation, broken leads, tightness of connections, defective wiring, and overall general condition. 2) Verify that primary and secondary fuse or circuit-breaker ratings match Drawings.
3) Verify correct functioning of drawout disconnecting and grounding contacts and interlocks.

B. Circuit-Breaker Field Tests:

1. Visual and Mechanical Inspection:

1. Inspect physical and mechanical condition.

2. Inspect anchorage, alignment, and grounding.

3. Verify that maintenance devices are available for servicing and operating breaker.

4. Verify unit is clean.

5. Verify that arc chutes are intact.

6. Inspect moving and stationary contacts for condition and alignment.

7. Verify that primary and secondary contact wipe and other dimensions vital to satisfactory operation of breaker are correct.

8. Perform mechanical operator and contact alignment tests on both breaker and its operating mechanism in accordance with manufacturer's published data.

9. Verify cell fit and element alignment.

10. Verify racking mechanism operation.

11. Verify appropriate lubrication on moving current-carrying parts and on moving and sliding surfaces.

12. Perform adjustments for final protective-device settings in accordance with coordination study provided by Owner.

13. Record as-found and as-left operation counter readings.

LOW-VOLTAGE SWITCHGEAR
26 23 00 - 9
Carlsbad Police and Fire HQ – Chiller Replacement

2. Electrical Tests:

1. Perform insulation-resistance tests for one minute on each pole, phase-to-phase and phase-to ground with switch closed, and across open poles. Apply voltage in accordance with manufacturer's published data. In absence of manufacturer's published data, use NETA ATS, Table 100.1. Insulation-resistance values must be in accordance with manufacturer's published data. In absence of manufacturer's published data, comply with NETA ATS, Table 100.1. Values of insulation resistance less than Table 100.1 or manufacturer's published instructions must be investigated.

2. Measure contact resistance across power contacts of circuit breakers. Drop values for µΩ or mV(dc) may not exceed high levels of normal range as indicated in manufacturer's published data. In absence of manufacturer's published data, investigate values that deviate from adjacent poles or similar switches by more than 50 percent of lowest value.

3. Determine long-time pickup and delay by primary current injection. Long-time pickup values must be as specified, and trip characteristic may not exceed manufacturer's published time-current characteristic tolerance band, including adjustment factors. If manufacturer's curves are unavailable, trip times may not exceed value shown in NETA ATS, Table 100.7.

4. Determine short-time pickup and delay by primary current injection. Short-time pickup values must be as specified, and trip characteristic may not exceed manufacturer's published time-current tolerance band.

5. Determine ground-fault pickup and delay by primary current injection. Ground-fault pickup values must be as specified, and trip characteristic may not exceed manufacturer's published time-current tolerance band.

6. Determine instantaneous pickup value by primary current injection. Instantaneous pickup values must be as specified and within manufacturer's published tolerances. In absence of manufacturer's published data, comply with NETA ATS, Table 100.8.

7. Test functions of trip unit by means of secondary injection. Pickup values and trip characteristic must be as specified and within manufacturer's published tolerances.

8. Perform minimum pickup voltage tests on shunt trip and close coils in accordance with manufacturer's published data. Minimum pickup voltage of shunt trip and close coils must comply with manufacturer's published data. In absence of manufacturer's published data, comply with NETA ATS, Table 100.20.

9. Measure fuse resistance. Investigate fuse-resistance values that deviate from each other by more than 15 percent.

10. Verify correct operation of auxiliary features, such as trip and pickup indicators, zone interlocking, electrical close and trip operation, trip-free operation, antipump function, and trip-unit battery condition. Reset trip logs and indicators. Auxiliary features must operate in accordance with manufacturer's published data.

11. Verify operation of charging mechanism. Charging mechanism must operate in accordance with manufacturer's published data.

12. Perform polarity test on current transformers in accordance with IEEE C57.13.1.

Polarity results must agree with transformer markings.

C. Ground-Resistance Test:

1. Visual and Mechanical Inspection:

1. Verify that ground system complies with Contract Documents and with Article 250, "Grounding and Bonding," in NFPA 70.

2. Inspect physical and mechanical condition. Grounding system electrical and mechanical connections must be free of corrosion.

LOW-VOLTAGE SWITCHGEAR
26 23 00 - 10
Carlsbad Police and Fire HQ – Chiller Replacement

3. Inspect bolted electrical connections for high resistance using one of the following two methods:
1) Use low-resistance ohmmeter to compare bolted-connection resistance values to values of similar connections. Investigate values that deviate from those of similar bolted connections by more than 50 percent of lowest value. 2) Verify tightness of accessible bolted electrical connections by calibrated torque-wrench method in accordance with manufacturer's published data or NETA ATS, Table 100.12. Bolt-torque levels must be in accordance with manufacturer's published data. In absence of manufacturer's published data, use NETA ATS, Table 100.12.

4. Inspect anchorage.

2. Electrical Tests:

1. Perform fall-of-potential or alternative test in accordance with IEEE 81 on main grounding electrode or system. Resistance between main grounding electrode and ground must be no more than 10 Ω.

2. Perform point-to-point tests to determine resistance between main grounding system and major electrical equipment frames, system neutral, and derived neutral points. Investigate point-to-point resistance values that exceed 0.5 Ω. Compare equipment nameplate data with the Contract Documents.

3. Inspect physical and mechanical condition.

4. Inspect bolted electrical connections for high resistance using one of the following two methods:
1) Use low-resistance ohmmeter to compare bolted-connection resistance values to values of similar connections. Investigate values that deviate from those of similar bolted connections by more than 50 percent of lowest value. 2) Verify tightness of accessible bolted electrical connections by calibrated torque-wrench method in accordance with manufacturer's published data or NETA ATS, Table 100.12. Bolt-torque levels must be in accordance with manufacturer's published data. In absence of manufacturer's published data, use NETA ATS, Table 100.12.

D. System Function Tests: Perform system function tests after other field quality-control tests have been completed and components have passed specified tests. Verify correct interaction of sensing, processing, and action devices.

1. Develop test parameters and perform tests for purpose of evaluating performance of integral components and their functioning as complete unit within design requirements and manufacturer's published data.

2. Verify correct operation of interlock safety devices for fail-safe functions in addition to design function.

3. Verify correct operation of sensing devices, alarms, and indicating devices.

E. Nonconforming Work:

1. Switchgear components will be considered defective if they do not pass tests and inspections.

2. Remove and replace defective units and retest.

END OF SECTION 26 23 00
Appendix A

FLEET COMPLIANCE CERTIFICATION
Bidder hereby acknowledges that they have reviewed the California Air Resources Board’s policies, rules and regulations and are familiar with the requirements of Title 13, California Code of Regulations, Division 3, Chapter 9, effective on January 1, 2024 (the “Regulation”). Bidder hereby certifies, subject to penalty for perjury, that the option checked below relating to the Bidder’s fleet, and/or that of their subcontractor(s) (“Fleet”) is true and correct:
□ The Fleet is subject to the requirements of the Regulation, and the appropriate Certificate(s) of Reported Compliance have been attached hereto. □ The Fleet is exempt from the Regulation under section 2449.1(f)(2), and a signed description of the subject vehicles, and reasoning for exemption has been attached hereto. □ Bidder and/or their subcontractor is unable to procure R99 or R100 renewable diesel fuel as defined in the Regulation pursuant to section 2449.1(f)(3). Bidder shall keep detailed records describing the normal refueling methods, their attempts to procure renewable diesel fuel and proof that shows they were not able to procure renewable diesel (i.e. third party correspondence or vendor bids).
□ The Fleet is exempt from the requirements of the Regulation pursuant to section 2449(i)(4) because this Project has been deemed an Emergency, as defined under section 2449(c)(18). Bidder shall only operate the exempted vehicles in the emergency situation and records of the exempted vehicles must be maintained, pursuant to section 2449(i)(4). □ The Fleet does not fall under the Regulation or is otherwise exempted, and a detailed reasoning is attached hereto.

Name of Bidder:

Signature:

Name:

Title:

Date:

PWS25-3807FAC

SCOPE OF WORK

APPLICABLE CODES

PROJECT DIRECTORY
OWNER:

ARCHITECT OF RECORD: IDS Group
Irvine, California 92606
John Silber
[email protected]
949.387.8500
John Silber - Principal Architect
Tel:

Email:

Contact:

MECHANICAL ENGINEER:

ELECTRICAL ENGINEER:

Tel:

Email:

Contact:

IDS Group
1 Peters Canyon Road, Suite 130
Irvine, California 92606
949.387.8500
PLUMBING:

Tel:

Email:

Contact:

IDS Group
1 Peters Canyon Road, Suite 130
Irvine, California 92606
Darren Smith
[email protected]
949.387.8500
Darren Smith
Darren Smith
[email protected]
Darren Smith
1 Peters Canyon Road, Suite 130
STRUCTURAL ENGINEER:

Tel:

Email:

Contact:

IDS Group
1 Peters Canyon Road, Suite 130
Irvine, California 92606
949.387.8500
Rami Elhassan
[email protected]
Rami Elhassan
· 2022 CALIFORNIA REFERENCED STANDARDS CODE, PART 1, TITLE 24 C.C.R. · 2022 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 C.C.R. · 2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3.
· TITLE 24 C.C.R. (2022 NEC)
· 2022 CALIFORNIA FIRE CODE, PART 9, TITLE 24 C.C.R.
· 2022 TITLE 19 C.C.R. PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS. · 2022 CALIFORNIA GREEN STANDARD CODE.
· 2022 CALIFORNIA ENERGY CODE. CBC 107.2.1
· 2022 CALIFORNIA MECHANICAL CODE (CMC)
· 2022 CALIFORNIA PLUMBING CODE (CPC)
· 2010 AMERICANS WITH DISABILITIES ACT.

IDS Group
1 Peters Canyon Road, Suite 130
Irvine, California 92606
Tel: 949.387.8500
Email:

Contact:
[email protected]
Steven Collins
Steven Collins
City of Carlsbad Public Works
Contracts Administration
1635 FARADAY AVE.

CARLSBAD, CA 92008
Contact: Brian Bacardi
Public Works Superintendent
Tel: 442-339-2944
Email: [email protected]

CITY OF CARLSBAD

CARLSBAD POLICE AND FIRE HQ CHILLER REPLACEMENT
2560 ORION WAY, CARLSBAD, CA 92010

FACILITY MAP

VICINITY MAP SHEET INDEX

SHEET NAME

PROJECT

LOCATION
M-001 NOTES, LEGEND AND ABBREVIATIONS
M-002 SCHEDULES
M-100 OVERALL SITE PLAN
M-101 CHILLER YARD DEMOLITION PLAN
M-201 CHILLER YARD PROPOSED PLAN
M-501 DETAILS
M-601 CONTROLS LEGEND AND ABBREVIATION
M-602 CONTROLS RISER DIAGRAM AND SEQUENCE OF OPERATION M-603 CHILLED WATER SYSTEM P&ID
M-701 TITLE 24 DOCUMENTATION

ARCHITECTURAL

ELECTRICAL

MECHANICAL
E-001 GENERAL NOTE, SYMBOLS LIST & SHEET INDEX
E-002 SINGLE LINE DIAGRAM - DEMOLITION & NEW
E-100 OVERALL ELECTRICAL SITE PLAN
E-200 ENLARGED ELECTRICAL PLAN - DEMOLITION & NEW E-300 ELECTRICAL DETAILS
N
N

STRUCTURAL
S-001 GENERAL NOTE
S-002 GENERAL NOTE
S-201 FOUNDATION PLAN
S-501 SECTION AND DETAILS
DEFERRED SUBMITTAL:

NA
P-001 NOTES, LEGEND, ABBREVIATIONS AND SCHEDULES
P-201 PLUMBING PLAN

PLUMBING
G-001 COVER SHEET

DRAWING
No.

REPLACE THE EXISTING 99.4 TON AIR-COOLED CHILLER WITH NEW TWO 50 TON AIR

COOLED CHILLERS, UPGRADE CONTROLS AND TIE INTO EXISTING BMS AND UPGRADE FRONT END GRAPHICS TO NEW CONFIGURATION. REVISE SEQUENCE OF OPERATIONS AS SHOWN TO SUPPORT TWO 50 TON AIR COOLED CHILLERS.

ELECTRICAL UPGRADES AS PART OF THIS PROJECT ARE SHOWN ON THE ELECTRICAL DRAWINGS.

PROVIDE (N) TRENCH DRAIN AND ASSOCIATED CONCRETE WORK FOR CHILLER YARD. 02 03
04 05
06 07
08 09
10 11
12 13
14 15
16 19
20 21
22 17
18 01
SHEET
No.

OCCUPANCY GROUP
SAFETY CENTER - A3, B2, I3/ TYPE II; SPRINKLERED/ 2-STOREY EQUIPMENT ENCLOSURE: B2/ TYPE V; NOT SPRINKLERED
SERVICE CENTER: H4/TYPE II; NOT SPRINKLERED
VEHICLE WASH: B2/TYOE V; NOT SPRINKLERED
TYPE OF CONSTRUCTION/ NO. OF STOREY
SAFETY CENTER: TYPE II; SPRINKLERED/ 2-STOREY
EQUIPMENT ENCLOSURE: TYPE V; NOT SPRINKLERED
SERVICE CENTER: TYPE II; NOT SPRINKLERED
VEHICLE WASH: TYPE V; NOT SPRINKLERED

TOTAL BUILDING AREA
SAFETY CENTER: 53,207 SF
EQUIPMENT ENCLOSURE:1,820 SF
SERVICE CENTER: 10,540 SF
VEHICLE WASH: 3,560 SF

OCCUPANCY AND BUILDING SUMMARY
NOTE:

THESE INFORMATION ARE FROM THE ORIGINAL DATA OF THE BUILDING 1 1

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.08 50% CONSTRUCTION DOCUMENTS06/21/24 -- 90% CONSTRUCTION DOCUMENTS07/23/24 --
PLAN CHECK SUBMITTAL10/02/24 --
PLAN CHECK CORRECTIONS04/01/25 1

COVER SHEET
G-001
5-15-25
5 DIAL
BEFORE

YOU DIG

TWO WORKING

DAYS BEFORE

YOU DIG
2560 ORION WAY _____ .:,.._
CARLSBAD, CA 92010
' .-·.:.-= oft ~ ,.

Q .. ~
. • r
,..:, u -
,... \
..,,

FARADAY AVE
J
;ti
Q'.
0 z
~
J
w
fsREml
~
E==3~~~t===================~~==~==3~==t=~ ~APFPP~ROJVIVE~D:~~~~~~~~~;::;:::::::;::= JOHN MAASHOFF RCE 61909 EXP 9/30/ 25
CITY OF CARLSBAD rp, • PUBLIC WORKS MANAGER DAlE

DA TE INITIAL DA TE INITIAL
ENGINEER OF WORK REVISION DESCRIPTION OlHER APPROVAL

DA TE INITIAL

CITY APPROVAL
DWN BY:

CHKD BY:

RVWD BY:

PROJECT NO.

A. GENERAL:

1. SCOPE OF WORK INCLUDES WORK SHOWN ON THE DRAWINGS AND DESCRIBED IN THE SPECIFICATIONS, WHETHER SHOWN ON THE DRAWINGS OR NOT. DRAWINGS AND SPECIFICATIONS ARE INTENDED TO COVER THE ENTIRE INSTALLATION OF A COMPLETE AND FUNCTIONAL SYSTEM TO OPERATE AS DESCRIBED.

2. THE CONTRACT DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED WORK. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK AND SHALL BE RESPONSIBLE FOR ALL CONSTRUCTION MEANS AND METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES.

3. THESE DRAWINGS ARE DIAGRAMMATIC. ALL TURNS, BENDS, AND ELEVATION CHANGES ARE NOT SHOWN ON THESE DRAWINGS.

THE CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY OF COORDINATION WITH VARIOUS TRADES AND INCLUDE ALL TURNS, BENDS, ADDITIONAL LENGTHS OF DUCTS, AND TRANSITIONS WITHOUT ADDITIONAL COST TO THE OWNER.

4. THE CONTRACTOR MUST EXAMINE ALL CONSTRAINTS AND THE AVAILABLE SPACE AT THE SITE THAT MAY REQUIRE CUSTOM FABRICATION. DISASSEMBLY AND RE-ASSEMBLY OF CERTAIN EQUIPMENT AT THE FINAL LOCATION OF THE JOB SITE. NO CHANGE ORDER WILL BE GRANTED TO MECHANICAL CONTRACTOR AFTER COMMENCING WORK DUE TO EXISTING CONDITION.

5. PROTECT ALL MATERIALS INCLUDING DUCTS AND PIPES FROM DUST AND DEBRIS AND KEEP OPEN END OF PIPES AND DUCTS COVERED AT ALL TIMES UNTIL READY FOR INSTALLATION OF NEXT SEGMENT OF WORK.

6. WORK DAMAGED OR CUT INTO DURING CONSTRUCTION SHALL BE PATCHED, REPAIRED, PAINTED AND FINISHED TO MATCH EXISTING ADJACENT SURFACES IN TEXTURE, COLOR, AND FINISH.

7. ALL MECHANICAL EQUIPMENT, MATERIALS, AND INSTALLATION SHALL BE IN ACCORDANCE WITH THE LATEST CALIFORNIA MECHANICAL CODE.

8. ALL INSULATION SHALL COMPLY WITH THE REQUIREMENTS OF TITLE 24 CALIFORNIA CODE OF REGULATIONS IN ADDITION TO THE REQUIREMENTS OF SPECIFICATIONS.

9. INSTALL EQUIPMENT IN ACCESSIBLE LOCATION AND PROVIDE ADEQUATE SERVICE CLEARANCE FOR NORMAL MAINTENANCE WITHOUT REQUIRING REMOVAL OF ARCHITECTURAL, ELECTRICAL OR STRUCTURAL ELEMENTS.

10. FOR EQUIPMENT LOCATED ABOVE CEILING, INSTALL SUCH EQUIPMENT CLOSE ENOUGH TO THE CEILING ELEVATION TO FACILITATE READY ACCESS FOR MAINTENANCE AND SERVICING.

11. CUTTING, BORING, SAWCUTTING OR DRILLING THROUGH STRUCTURAL ELEMENTS TO BE DONE ONLY WHEN SO DETAILED ON THE DRAWINGS OR ACCEPTED BY THE STRUCTURAL ENGINEER.

12. VERIFY ELECTRICAL CHARACTERISTICS PRIOR TO BID AND MATERIAL PURCHASE.

13. COORDINATE TEMPERATURE SENSOR AND THERMOSTAT LOCATION WITH FLOOR PLANS AND ELEVATION WITH LIGHT SWITCH/FIRE ALARM DEVICES. TEMPERATURE SENSOR AND THERMOSTAT ELEVATION SHALL BE SAME ELEVATION AS LIGHT SWITCH/FIRE ALARM DEVICES.

A, AMPS AMPERES

ABV ABOVE

AD ACCESS DOOR

AFF ABOVE FINISHED FLOOR

AMB AMBIENT

AP ACCESS PANEL

ARCH ARCHITECTURAL

AUTO AUTOMATIC

BD BACK DRAFT DAMPER

BDD BACK DRAFT DAMPER

BEL BELOW

BHP BRAKE HORSEPOWER

BTUH BRITISH THERMAL UNITS PER HOUR

CAP CAPACITY

CD CEILING DIFFUSER

CDP CONDENSATE DRAIN PIPE

CFM CUBIC FEET PER MINUTE

CFSD COMBINATION FIRE SMOKE DAMPER

CLG CEILING

COMP COMPRESSOR

COND CONDITION

COP COEFFICIENT OF PERFORMANCE
dB DECIBEL

DB DRY BULB TEMPERATURE

DDC DIRECT DIGITAL CONTROL

DEFL DEFLECTION

DL DOOR LOUVER

DN DOWN

DPSW DIFFERENTIAL PRESSURE SWITCH

DSW DISCONNECT SWITCH

DWGS DRAWINGS

E EXISTING

EA EACH

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EFF EFFICIENCY

EG EXHAUST GRILLE

ELECT ELECTRICAL

ELEV ELEVATION

ENCL ENCLOSURE

ENT ENTERING

ESP EXTERNAL STATIC PRESSURE

EVAP EVAPORATOR, EVAPORATIVE

EXH EXHAUST
°F DEGREES FAHRENHEIT

FA FRESH AIR OR OUTSIDE AIR

FC FAN COIL

FLA FULL LOAD AMPS

FLEX FLEXIBLE

FS FLOOR SINK

FSW FLOW SWITCH

H HEIGHT

HP HORSEPOWER

HR HOUR

HTG HEATING

HVAC HEATING, VENTILATING AND AIR CONDITIONING

HZ HERTZ

IN WG INCHES WATER GAUGE

ABBREVIATION IDENTIFICATION

DROP IN DUCTWORK
CEILING SUPPLY, TYPECD-2
200FLOW (CFM)
(IN DIRECTION OF AIR FLOW)
RG-1
300

FIRE DAMPER AND ACCESS DOOR

COMBINATION FIRE AND SMOKE DAMPER

RISE IN DUCTWORK

TERMINAL AIR UNIT W/ REHEAT COIL
D
UP

SMOKE DAMPER
(IN DIRECTION OF AIR FLOW)
FD
SD

DUCT FLEXIBLE CONNECTION

BACK DRAFT DAMPER
TV

DUCT FITTING

RADIUS ELBOW

DUCT TRANSITION

OUTSIDE AIR DUCT

VANED ELBOW
(SUPPLY AIR OR FAN DISCHARGE)

DUCT UNDER POSITIVE PRESSURE

DUCT UNDER NEGATIVE PRESSURE

DUCTWORK WITH ACOUSTIC LINING

EXHAUST DUCT

RETURN DUCT

SINGLE LINE DUCTWORK, NEW

SYMBOLDESCRIPTION
BDD
300
EG-1

MANUAL VOLUME DAMPER

CEILING RETURN, TYPE

FLOW (CFM)

CEILING EXHAUST, TYPE

FLOW (CFM)

GENERAL NOTESMECHANICAL SYMBOLS - DUCTWORK MECHANICAL SYMBOLS - PIPING

KW KILOWATT

L LENGTH

LBS POUNDS

LRA LOCKED ROTOR AMPERES

LVG LEAVING

MAX MAXIMUM

MBH THOUSAND BRITISH THERMAL UNITS PER HOUR

MCA MINIMUM CIRCUIT AMPACITY

MCC MOTOR CONTROL CENTER

MD MOTORIZED DAMPER

MFGR MANUFACTURER

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

N NEW

NC NOISE CRITERIA

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

OBD OPPOSED BLADE DAMPER

OC ON CENTER

OPER OPERATING

OPNG OPENING

OP WT OPERATING WEIGHT

PD PRESSURE DROP

PH PHASE

POC POINT OF CONNECTION

PR PRESSURE

PSI POUND PER SQUARE INCH

QTY QUANTITY

RA RETURN AIR

REFR REFRIGERANT

RH RELATIVE HUMIDITY

RLA RATED LOAD AMPERES

REL RELOCATED

SA SUPPLY AIR

SC SENSIBLE CAPACITY

SCOP SENSIBLE COEFFICIENT OF PERFORMANCE

SD SMOKE DETECTOR

SF SQUARE FEET

SHT SHEET

SS STAINLESS STEEL

SW SWITCH

TAD TRANSFER DUCT

TC TOTAL CAPACITY

TEMP TEMPERATURE

TSP TOTAL STATIC PRESSURE

TYP TYPICAL

UC UNDER CUT

UL UNDERWRITER'S LABORATORY

UON UNLESS OTHERWISE NOTED

UTR UP THRU ROOF

V VOLTS

W WIDTH

W/ WITH

WB WET BULB TEMPERATURE

WT WEIGHT

ABBREVIATION IDENTIFICATION
SUSPENDED UTILITY SYSTEMS WHICH INCLUDE:
· ELECTRICAL, MECHANICAL, AND PLUMBING EQUIPMENT AND ASSOCIATED CONDUIT, DUCTWORK, AND PIPING ARE

REQUIRED TO HAVE SEISMIC RESTRAINT ATTACHMENTS DESIGNED TO RESIST THE TOTAL DESIGN SEISMIC FORCES PRESCRIBED IN SECTION 1613A. PROVIDE TYPICAL SEISMIC RESTRAINT DETAILS. DOCUMENTATION SUBSTANTIATING COMPLIANCE WITH SECTION 1613A OF THE 2022 INTERNATIONAL BUILDING CODE (2022 CALIFORNIA BUILDING CODE) TO INCLUDE SEISMIC RESTRAINT ASSEMBLY DETAILS. ANCHORAGE TO OVERHEAD STRUCTURES WITH SUPPORTING ENGINEERING STAMP BY A LICENSED CIVIL OR STRUCTURAL ENGINEER IS REQUIRED AT TIME OF INSPECTION.

NONSTRUCTURAL COMPONENTS AND EQUIPMENT SUPPORTS AND ATTACHMENTS · PROVIDE DETAILS ON THE CONSTRUCTION DOCUMENTS AND SUBSTANTIATING CALCULATIONS (WHEN NECESSARY)

FOR THE SUPPORTS AND ATTACHMENTS OF NONSTRUCTURAL COMPONENTS AND EQUIPMENT UNLESS THEY ARE EXEMPTED FROM PLAN REVIEW BY 2022 CBC SECTIONS 1616A.1.18. THE SUPPORTS AND ATTACHMENTS DETAILS SHALL BE COORDINATED WITH THE CALCULATIONS AND THE MANUFACTURE'S LITERATURE. SKETCHES SHOWN IN THE CALCULATIONS FOR THE PURPOSE OF ILLUSTRATING THE ANALYTICAL METHOD ARE NOT ADEQUATE.

EQUIPMENT SUPPORTS AND ATTACHMENTS
· SUPPORTS AND ATTACHMENTS OF ALL EQUIPMENT TO BE INSTALLED AS A PART OF THIS PROJECT SHALL BE DETAILED ON CONSTRUCTION DOCUMENTS, EXCEPT THOSE EXEMPT BY THE 2022 CBC SECTION 1616A.1.18. · EQUIPMENT SUPPORTS AND ATTACHMENTS SHALL BE APPROVED BY THE APPROPRIATE DESIGN PROFESSIONAL OF RECORD AS A PART OF FIELD REVIEW/OBSERVATIONS. THE INSPECTOR OF RECORD (IOR) SHALL ASSURE THAT THE ABOVE REQUIREMENTS ARE ENFORCED. (2022 CBC SECTIONS 107 AND 1616A)

PIPES, DUCTS, AND CONDUITS SUPPORTS, ATTACHMENTS, AND BRACING · PROVIDE CALCULATIONS AND DETAILS FOR SUPPORTS, ATTACHMENTS, AND BRACING OF ALL PIPES, DUCTS, AND CONDUITS. IF A PRE-APPROVED SYSTEM IS SPECIFIED (THE OPM NUMBERS FOR THE ACCEPTABLE ALTERNATIVES

SHALL BE SPECIFIED ON THE DRAWINGS) CERTAIN CALCULATIONS AND DETAILS FOR THE SUPPORTING STRUCTURE ARE STILL REQUIRED.
· (2022 CAC SECTIONS 7-115, 7-126, AND CBC 2022 SECTION 107)

PRE-APPROVED PIPES, DUCTS, AND CONDUITS SEISMIC BRACING A. LAYOUT DRAWINGS OF THE SUPPORTS, ATTACHMENTS, AND BRACING SYSTEMS IN ACCORDANCE WITH THE

PRE-APPROVED SHALL BE SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL (RDP) IN RESPONSIBLE CHARGE OF THE PROJECT FOR REVIEW TO VERIFY THAT THE DETAILS ARE IN CONFORMANCE WITH THE CODE REQUIREMENTS. THE LAYOUT DRAWINGS SHALL AS MINIMUM SATISFY THE REQUIREMENTS OF ASCE 7 SECTION 13.6 AS MODIFIED BY THE CBC 2022 SECTION 1616A.

1. THE STRUCTURAL ENGINEER OF RECORD (SEOR) SHALL VERIFY THAT THE SUPPORTING STRUCTURE IS ADEQUATE

FOR THE FORCES IMPOSED ON IT BY THE SUPPORTS, ATTACHMENTS, AND BRACES INSTALLED IN ACCORDANCE WITH THE PRE-APPROVAL IN ADDITION TO ALL OTHER LOADS.

2. THE SEOR SHALL FORWARD THE SUPPORTS, ATTACHMENTS, AND BRACING DRAWINGS (INCLUDED APPROVED

AMENDED CONSTRUCTION DOCUMENTS FOR SUPPLEMENTARY FRAMING WHERE REQUIRED) TO THE DISCIPLINE IN

RESPONSIBLE CHARGE WITH A NOTATION INDICATING THAT THE DRAWINGS HAVE BEEN REVIEWED AND ARE IN GENERAL CONFORMANCE WITH THE PRE-APPROVAL IN ADDITION TO ALL OTHER LOADS.

3. A “SHOP DRAWING STAMP” MAY BE USED TO INDICATE COMPLIANCE WITH THIS REQUIREMENT.

4. THE REGISTERED DESIGN PROFESSIONAL (RDP), OTHER THAN SEOR, MAY PROVIDE THE SHOP DRAWING.

B. THE SEOR SHALL DESIGN ANY SUPPLEMENTARY FRAMING THAT IS NEEDED TO RESIST THE LOADS, MAINTAIN STABILITY AND/OR IS REQUIRED FOR INSTALLATION OF PRE-APPROVED SYSTEM. · THE SUPPLEMENTARY FRAMING SHALL BE SUBMITTED AS AN AMENDED CONSTRUCTION DOCUMENTS (ACD).

C.THE LAYOUT DRAWINGS (WITH THE SHOP DRAWING STAMP) SHALL BE SUBMITTED FOR REVIEW:

1. STRUCTURE SUPPORTING THE DISTRIBUTION SYSTEM HAS ADEQUATE CAPACITY,

2. SEISMIC DESIGN FORCES (FP) ARE IN ACCORDANCE WITH THE CBC 2022 D. THE LAYOUT DRAWINGS (WITH THE SHOP DRAWING STAMP) SHALL BE KEPT ON THE JOBSITE AND CAN THEN BE USED FOR INSTALLATION OF THE SUPPORT AND BRACING.

E. A COPY OF THE CHOSEN BRACING SYSTEM(S) INSTALLATION GUIDE/OPM MANUAL SHALL BE ON THE JOBSITE PRIOR TO STARTING THE INSTALLATION OF HANGERS AND/OR BRACES.
· IT IS THE CONTRACTOR'S RESPONSIBILITY TO OBTAIN COPIES OF OPM AND FURNISH THE IOR WITH ONE COPY EACH.

F. COMPONENTS OF TWO OR MORE PRE-APPROVED BRACING SYSTEMS SHALL NOT BE MIXED. · ONLY ONE PRE-APPROVED BRACING SYSTEM MAY BE USED FOR A RUN OF PIPE, DUCT, OR CONDUIT. · ANY SUBSTITUTION OF COMPONENT OF AN OPM SYSTEM SHALL REQUIRE REVIEW AND APPROVAL. (2022 CAC SECTIONS 7-115, 7-126, 7-153, AND CBC 2022 SECTION 107)

1. MINIMUM OF 50% OF NON HAZARDOUS CONSTRUCTION WASTE IS TO BE RECYCLE. CGC 5.713.8.1.

2. TESTING AND ADJUSTING OF NEW SYSTEMS SHALL COMPLY AS OUTLINED IN CGC SECTION 5.713.10.4.2.

3. OPERATIONS AND MAINTENANCE SCHEDULE (O&M) AS LISTED IN CGC SECTION 5.713.10.4.5 SHALL BE DELIVERED TO THE BUILDING OWNER OR REPRESENTATIVE AND THE FACILITIES OPERATOR.

4. DURING CONSTRUCTION, ENDS OF DUCT OPENING SHALL BE SEALED, AND MECHANICAL EQUIPMENT SHALL BE COVERED.

CGC 5.714.4.3.

5. VOC'S MUST COMPLY WITH THE LIMITATIONS LISTED IN SECTION 5.504.4 AND TABLES 4.504.1, 5.504.4.1, 5.504.4.2, 5.504.4.3 AND 5.504.4.5 FOR: ADHESIVES, SEALANTS, PAINTS, AND COATINGS, CARPET AND COMPOSITION WOOD PRODUCTS. CGC

5.714.4.4 .

6. PRIOR TO FINAL APPROVAL OF THE BUILDING THE LICENSED CONTRACTOR, ARCHITECT OR ENGINEER IN RESPONSIBLE

CHARGE OF THE OVERALL CONSTRUCTION MUST COMPLETE AND SIGN THE COUNTY APPROVED GREEN BUILDING

STANDARDS CERTIFICATION FORM OR OTHER DOCUMENTATION REQUIRED BY THE COUNTY AND GIVEN TO THE BUILDING DEPARTMENT OFFICIAL PRIOR TO BUILDING FINAL APPROVAL TO BE FILED WITH THE APPROVED PLANS.

SEISMIC BRACING

CALGREEN BUILDING STANDARD NOTES
POINT OF DISCONNECTP.O.D.

POINT OF CONNECTIONP.O.C.

FS
XX

YYEQUIPMENT TAG

U/G UNDER GROUND

THERMOSTAT / TEMPERATURE SENSORT
CARBON DIOXIDE SENSORCO2

APPLICABLE CODES
2022 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE, (TITLE 24 PART 1) 2022 CALIFORNIA BUILDING CODE (CBC), (TITLE 24 PART 2)
2022 CALIFORNIA ELECTRICAL CODE (CEC), (TITLE 24 PART 3) 2022 CALIFORNIA MECHANICAL CODE (CMC), (TITLE 24 PART4) 2022 CALIFORNIA PLUMBING CODE (CPC), (TITLE 24 PART 5)
2022 CALIFORNIA ENERGY CODE, (TITLE 24 PART 6)
2022 CALIFORNIA FIRE CODE (TITLE 24 PART 9)
2022 CALIFORNIA GREEN BUILDING CODE (CGBC), (TITLE 24 11)

SCOPE OF WORK

MBTUH THOUSAND BRITISH THERMAL UNITS PER HOUR

PRESS PRESSURE

SQ FT SQUARE FEET
REPLACE THE EXISTING 99.4 TON AIR-COOLED CHILLER WITH NEW TWO 50 TON AIR COOLED CHILLERS, UPGRADE CONTROLS AND TIE INTO EXISTING BMS AND UPGRADE FRONT END GRAPHICS TO NEW CONFIGURATION. REVISE SEQUENCE OF OPERATIONS AS SHOWN TO SUPPORT TWO 50% CHILLERS.

ELECTRICAL UPGRADES AS PART OF THIS PROJECT ARE SHOWN ON THE ELECTRICAL DRAWINGS.

SHEET INDEX
M-001 1
SCHEDULES M-002
S.No.SHEET TITLE
M-101 CHILLER YARD DEMOLITION PLAN
M-201 CHILLER YARD PROPOSED PLAN
M-501 DETAILS

NOTES, LEGEND AND ABBREVIATIONS
SHEET
NUMBER
2 3
4 5
6 SCALE

NO SCALE

NO SCALE
M-601 CONTROLS LEGEND AND ABBREVIATIONNO SCALE
7 1/4" = 1'-0"
1/4" = 1'-0"

NO SCALE
OVERALL SITE PLANM-1001" = 30'-0"

CHWS CHILLED WATER SUPPLY

CHWR CHILLED WATER RETURN
M-701 TITLE 24 DOCUMENTATIONNO SCALE
8 M-602 CONTROLS RISER DIAGRAM AND SEQUENCE OF OPERATOINNO SCALE 9 ABBREVIATIONS

MANUAL AIR VENT

TEST PLUG

THERMOMETER AND WELL

PRESSURE GAUGE

VIBRATION ISOLATOR IN HANGER

PRIMARY CHILLED WATER SUPPLY

REFRIGERANT SUCTION

REFRIGERANT LIQUIDRL
RS
PCWS

THREE-WAY AUTOMATIC

TWO-WAY AUTOMATIC

SAFETY VALVE

AUTOMATIC AIR VENT

PRESSURE REDUCING VALVE

PLUG VALVE

CHILLED WATER RETURN

CHILLED WATER SUPPLY

CONDENSATE DRAIN
DRAIN

HEATING HOT WATER RETURN

HEATING HOT WATER SUPPLY
CHWR
D
HHWS
HHWR
CHWS
CD

SYMBOLDESCRIPTION

CONTROL VALVE

WITH NEEDLE VALVE

CONTROL VALVE

EXISTING DUCT/PIPING TO REMAIN

EXISTING EQUIPMENT TO REMAIN

EXISTING EQUIPMENT TO BE REMOVED

EXISTING DUCT/PIPING TO BE REMOVED

NEW PIPE WITH DIRECTION OF FLOW

PIPE RISE

PIPE DROP

CONCENTRIC REDUCER

FLANGED CONNECTION

PITCH DOWN IN DIRECTION OF FLOW

PITCH UP IN DIRECTION OF FLOW

PIPE IN UNDERGROUND CONDUIT

EXPANSION LOOP

BALL JOINT

PIPE EXPANSION JOINT

GATE VALVE

PIPE ANCHOR

ANGLE GATE VALVE

PIPE ALIGNMENT GUIDE

ANGLE VALVE

DEAD END, SCREWED CAP

CHECK VALVE
U
D
UNION
"Y" TYPE STRAINER

VACUUM BREAKER

SYMBOLDESCRIPTION

ECCENTRIC REDUCER

ACTUATED BUTTERFLY VALVE
M-603 CHILLED WATER SYSTEM P&IDNO SCALE
10 RJ
SS
DS

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.0850% CONSTRUCTION DOCUMENTS06/21/24 -- 90% CONSTRUCTION DOCUMENTS07/23/24 --
PLAN CHECK SUBMITTAL10/02/24 --
No. 30841REM
SATTE

ETER SIG
ER
P
D
LO A
C N
F HO C
A
AL I
F C
ANR
I
O
EFO
ISS

NER ENI GELANI
DARREN
B
. SMITH
Exp. 12/31/26PLAN CHECK CORRECTIONS04/01/251

NOTES LEGEND AND ABBREVIATIONS
M-001
0 :,:
i5
0 .c
"' {;
(/J
-,:,~"""""""'-----
! JDEJ~I.loIBTh\T
·o =i ~
.c
~
1/1
lo',
m
,,
:!
0 a:

DIAL
BEFORE

YOU DIG

TWO WORKING

DAYS BEFORE

YOU DIG
TOLL FREE llllllliil 1-800-227-2600

A PUBLIC SERVICE BY

UNDERGROUND SERVICE ALERT
,----7
L ____ J
1/// ///h
~
:_) l
-1:
----111
------cJ--
[:--­
_____f""""l__
----E3--
-----QI---
---I><)--
~
~
------t----..J-
C?-
g
-....l\91---
----w-
__£_
4 ----[]
----[]
----[]
~­
[2]-
0-
0 0
~
qi
e
..___ _________ _JE::I::=1::::::::=~=====-=--=--=--=--=-=-=t=-~..____ ______ __J * *
/'I,
[====J~~=~j===============================f====~====l====jt===j APPROVED: JOHN MAASHOFF RCE 61909 EXP. 9/30/25

PUBLIC WORKS MANAGER CITY OF CARLSBAD DATE

DA TE INITIAL

ENGINEER OF WORK REVISION DESCRIPTION

DATE INITIAL
OlHER APPROVAL

DATE INITIAL

CITY APPROVAL
DWN BY: ---1 CHKD BY: ___ PROJECT NO.

RVWD BY: _

TAG STATUSMAKEMODELTYPELOCATION
NOTES:

CHILLER SCHEDULE

SERVICE
NOTES:

CAP
EFF

KW/TON EER
TONS

WATER TEMP GPM

EWT LWTMAX MIN
PRESS.

DROP

MCAFUSE V / PH / HZ

PHYSICAL

OPERATING

REFRIGLWH

ANCHORAGE
DETAIL
MOCP
(IN.) (IN.) (IN.)
WEIGHT
(LBS)
REFRIG
CHARGE
(LBS)
FT H2O

12 S-501
(E) AH-1 FIRST FLOOR
(E) AH-2, AH-3 SECOND FLOOR
POLICE & FIRE HQ BLDG.

YORK DEMOYCAL0104EB46XCASB (E) CH-1
CH
1ANEW

AIR COOLED
SCROLL

CHILLER
8378 ON GRADE460 / 3 / 60

UNIT POWER SUPPLY

MCAFUSE V / PH / HZ
MOCP

UNIT CONTROL SUPPLY
203 225 115 / 1 / 60 20 30 407C-

ELECTRICAL CONDENSER
TOTAL
FAN
KW
FAN

QTY CFM EAT
DEG F
99 EVAPORATOR PERFORMANCE
159 88.25 9698 --- - - - - - - - --
CARRIER 30RC-0506620--003

AIR COOLED

DIGITAL
SCROLL

CHILLER

ON GRADE
(E) AH-1 FIRST FLOOR
(E) AH-2, AH-3 SECOND FLOOR
POLICE & FIRE HQ BLDG.
5010.53 1.145444 119.4 43.92 4.392350 460 / 3 / 60 108.8 125.0 - - - R-3295 88 78 25 9533,7343 3.975 52.92

COMPRESSORS
TOTAL
KW
CH
1B

1. ENERGY MANAGEMENT MODULE.

2. EVAPORATIVE HEATER (FREEZE PROTECTION)

3. 10 kA SCCR

4. SUCTION LINE INSULATION.

5. DIGITAL SCROLL COMPRESSOR (INCLUDES SOUND BLANKETS).

6. MICRO CHANNEL CONDENSER COIL WITH E-COAT.

7. GREENSPEED INTELLIGENCE : HIGH EFFICIENCY VARIABLE CONDENSER FANS.

8. NON FUSED DISCONNECT SWITCH.

9. BRAZED PLATE HEAT EXCHANGER.

10. SINGLE POINT POWER.

11. FULL HAIL GUARDS.

12. LOW SOUND - INCLUDE AERO-ACOUSTIC FANS.

13. CONNECT TO EXISTING CARRIER I-VU CONTROLS
1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13

12 S-501
NEW CARRIER 30RC-0506620--003

AIR COOLED

DIGITAL
SCROLL

CHILLER

ON GRADE
(E) AH-1 FIRST FLOOR
(E) AH-2, AH-3 SECOND FLOOR
POLICE & FIRE HQ BLDG.
5010.53 1.145444119.4 43.92 4.392350 460 / 3 / 60108.8 125.0- - -R-3295 88 78 25 9533,7343 3.975 52.921, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13

TAG STATUSMAKEMODELTYPELOCATION

PERFORMANCE

GPMFTNPSH

EXISTING ARMSTRONG

EXISTING PUMP SCHEDULE (FOR REFERENCE ONLY)

ELECTRICALPHYSICAL

SERVICESUCTION
NOTES:

RPMBHPEFF
%

HPVPH TYPE FRAMEDISCHIMP
DIA.LWH WEIGHT
4302 0410 005.0
BOILER
ROOMCHILLED232 48.0 10.2 1672 4.23 62.13 5 460 3184TC 4" 4" 8.31" 30 33.01 36.54INVERTER DUTY888

VERTICAL
INLINE

DUALARM
PUMP
WATER

BUILDING DESIGN ENVELOPE
(E)P
1 (E)P
2 EXISTING TO REMAIN AND RE-USED.

RJ
SS
DS

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.0850% CONSTRUCTION DOCUMENTS06/21/24 -- 90% CONSTRUCTION DOCUMENTS07/23/24 --
PLAN CHECK SUBMITTAL10/02/24 --
No. 30841REM
SATTE

ETER SIG
ER
P
D
LO A
C N
F HO C
A
AL I
F C
ANR
I
O
EFO
ISS

NER ENI GELANI
DARREN
B
. SMITH
Exp. 12/31/26PLAN CHECK CORRECTIONS04/01/251

SCHEDULES
M-002
~
6 I
0 :,:
~ ..,
C
0 G
,2
0 a. ..,
0 i1
'C
8 OJ
0 ui
0 0
X
~ ..,
~
0 .s= ,.
~
0 € "' cl
"' ~
]
0 .s= ,.
~
J,
C
;;:::
8 0
.s=
"' {;
(/J
-.,~"""""""'-----
! JDEJ~I.loIBTh\T
·o =i ~
.s=
~
1/1
lo',
m ..,
:!
0 a:

DIAL
BEFORE

YOU DIG

TWO WORKING

DAYS BEFORE

YOU DIG
TOLL FREE llllllliil 1-800-227-2600

A PUBLIC SERVICE BY

UNDERGROUND SERVICE ALERT
e
e
* *
8 8
~=t~===---==+=+=t==±~ fSHml CITY OF CARLSBAD fsHEET5l
t-1-==t=jt======------====t==+=~==i=~ ;::~~
3 ~~~~P~U~BL=:IC=:::::W::::O::::R:=KS~D~E~PA~R~TM~E~NT!:::==~l___E_J~~ 2 =:! f-I IMPROVEMENT PLANS FOR:
/'I,
~==~t~~t====================~===E===i===t=~ fAAFFPPiR(RO~VEEDD~: JnJO~HN~M~A~S~~~~======= I-A HOFF RCE 61909 EXP. 9/30/25

PUBLIC WORKS MANAGER CITY OF CARLSBAD DATE

DA TE INITIAL

ENGINEER OF WORK REVISION DESCRIPTION

DATE INITIAL
OlHER APPROVAL

DATE INITIAL

CITY APPROVAL
DWN BY: ---1 CHKD BY: ___ ~ROJECT NO.

RVWD BY:
(E)
50'-0"
20'-0"
20'-0"
150'-0"
R15'-0"
R15'-0"
1 M-201
1 M-101
(E)POLICE & FIRE SAFETY

BUILDING
RJ
SS
DS

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.0850% CONSTRUCTION DOCUMENTS06/21/24 -- 90% CONSTRUCTION DOCUMENTS07/23/24 --
PLAN CHECK SUBMITTAL10/02/24 --
No. 30841REM
SATTE

ETER SIG
ER
P
D
LO A
C N
F HO C
A
AL I
F C
ANR
I
O
EFO
ISS

NER ENI GELANI
DARREN
B
. SMITH
Exp. 12/31/26PLAN CHECK CORRECTIONS04/01/251
1 1" = 30'-0" OVERALL SITE PLAN

OVERALL SITE PLAN
M-100
TRUE
NORTH
N
0 I
"' "' 0
"'
0 8 -I :::;
.;;
[
C
...J
DIAL
BEFORE

YOU DIG

TWO WORKING

DAYS BEFORE

YOU DIG
D
0 /JiillJ
~
C ID
D
0 □
0 ~==3E~~t====================~===E==l===t=~ fAAJ3FppiR(Ro~VEEDD~: ~JO~HN~M~A~AS~~~============:::;:===::! I-HOFF RCE 61909 EXP. 9/30/25

PUBLIC WORKS MANAGER CITY OF CARLSBAD DATE

DA TE INITIAL

ENGINEER OF WORK

DATE INITIAL
REVISION DESCRIPTION OlHER APPROVAL

DATE INITIAL

CITY APPROVAL
DWN BY:

CHKD BY:

RVWD BY:

PROJECT NO. 11 DRAWING NO.I

DEMOLITION KEYNOTES
(E) BOILER TO REMAIN AND REUSED.
(E) PIPING AND PIPING APPURTENANCES TO REMAIN
AND REUSED.

DEMOLISH AND REMOVE (E) CHILLER INCLUDING
ALL APPURTENANCE.
(E) CHW PUMPS TO REMAIN AND REUSED.
(E) HHW PUMPS TO REMAIN AND REUSED.
(E) 8" FLUE UP THROUGH ROOF TO REMAIN AND
REUSED.
(E) EXPANSION TANK TO REMAIN AND REUSED.
(E) CHW AIR SEPARATOR TO REMAIN AND REUSED .
(E) CHEMICAL FEEDERS TO REMAIN AND REUSED.
(E) MCC (MOTOR CONTROL CENTER). REFER TO
ELECTRICAL DRAWINGS.
(E) HHW AIR SEPARATOR TO REMAIN AND REUSED.
(E) FLOOR SINK TO REMAIN AND REUSED.
(E) (2) COMBUSTION AIR LOUVERS TO REMAIN AND
REUSED. HI AND LOW.
(E) DISCONNECT SWITCH FOR CHILLER. REFER TO
ELECTRICAL DRAWINGS.
(E) CONCRETE PAD TO REMAIN AND REUSED.
(E) ±1" DIA WALL OPENING FOR DRAIN.

DEMOLISH AND REMOVE (E) CHWS AND CHWR
PIPES.
1 (E) 2" HHWR
(E) 4" CHWR
(E) 4" CHWS
(E) 4" CHWR
(E) 4" CHWS
(E) 2"HHWS
4" CHWS
4" CHWR
2 3
4 5
6 7
8 9
10 11
12 13
1 8 (E) AS-1
(E) B-1
6 7 (E) ET-2
7 (E) ET-1
4 (E) P-1
(E) P-2
2 2
12 (E) FD
9 (E) CPF-2
2 11 (E) AS-2
5 (E) P-3
(E) P-4
13 10
9(E) CPF-1
3(E) CH-1
(E) 4" CHWS&R

TO BUILDING
(E) 2" HHWS&R

TO BUILDING
14 14
15 15
2POD
(E) ELECTRICAL

TRANSFORMER(E) GENERATOR ROOM
(E) BOILER ROOM
(E) TRASH
(E) CHILLER YARD
(E) GENERATOR SET
16 16
16 16
16 16
16 17
17 RJ
SS
DS

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.0850% CONSTRUCTION DOCUMENTS06/21/24 -- 90% CONSTRUCTION DOCUMENTS07/23/24 --
PLAN CHECK SUBMITTAL10/02/24 --
No. 30841REM
SATTE

ETER SIG
ER
P
D
LO A
C N
F HO C
A
AL I
F C
ANR
I
O
EFO
ISS

NER ENI GELANI
DARREN
B
. SMITH
Exp. 12/31/26PLAN CHECK CORRECTIONS04/01/251
1 1/4"=1'-0" CHILLER YARD DEMOLITION PLAN
TRUE
NORTHN

CHILLER YARD DEMOLITION PLAN
M-101
L
.!!
,:
<J
0 :,:
"' "' 0
"' a
a -I :::;
-"
~
0 ...J
0 ,:
"' ~
'C
~
0 a:

DIAL
BEFORE

YOU DIG

TWO WORKING

DAYS BEFORE

YOU DIG
-
(_ -
I : :--,,,.ir,!Y l::. -• • -.d
11 11
11 11
11 11
11 11
11 I I
11 11
11 11
11 11
11 11
11 11
I I 11
11 I I
11 11
11 11
11 11
I I 11
11 11
11 11
11 ,Y
//
II II 1111
II II I 111
II II f-lH
11 ~ l;fi
II A ffff
I I I I f I If
I I 11 / / f I
I I 11 / f f I
I I 11 ff f I
~~f;ff
l!f!f/f/
ffff/ff/
f/ f/ If f /
f/ f; f; f /
I/ if I; f /
I f;
-;r--,'L..,.

I/ f/ I I
I/ if I I I I
I; if I I f I
f/f;lfl/
i/f;l;f;
I/ I/ I; I/
I/ If I I I I
i/f;lff/
1/f;lff/
I/ f/ I; I/
~)L)Jjj_r
I I
,-------------
1 I
I
I
7 I
I
I
I
I I
L _____________ _J
o~--------------
0 ◊
◊
◊
◊
◊
◊
◊
◊
◊
◊
◊
◊
◊
◊
◊
◊
◊
[sHms]
LE_J
[====J~~=~j===============================f====~====l====jt===j APPROVED: JOHN MAASHOFF RCE 61909 EXP. 9/30/25

PUBLIC WORKS MANAGER CITY OF CARLSBAD DATE

DA TE INITIAL
ENGINEER Of WORK
DWN BY: PROJECT NO.

REVISION DESCRIPTION

DATE INITIAL
OlHER APPROVAL

DA TE INITIAL

CITY APPROVAL
CHKD BY:

RVWD BY:

II DRAWING NO.I

KEYNOTES
1 (E) 2" HHWR
(E) 4" CHWR
(E) 4" CHWS
(E) 4" CHWR
(E) 4" CHWS
(E) 2"HHWS
4" CHWS
4" CHWR
(E) AS-1
(E) B-1
(E) ET-2
(E) ET-1
(E) P-1
(E) P-2
(E) FD
(E) CPF-2
(E) AS-2
(E) P-3
(E) P-4
(E) CPF-1
(E) 4" CHWS&R

TO BUILDING
(E) 2" HHWS&R

TO BUILDING
(E) BOILER TO REMAIN AND REUSED.
(E) PIPING AND PIPING APPURTENANCES TO REMAIN
AND REUSED.

PROVIDE (N) CHILLER. SEE SCHEDULE ON SHEET
M-002.
(E) CHW PUMPS TO REMAIN AND REUSED.
(E) HHW PUMPS TO REMAIN AND REUSED.
(E) 8" FLUE UP THROUGH ROOF TO REMAIN AND
REUSED.
(E) EXPANSION TANK TO REMAIN AND REUSED.
(E) CHW AIR SEPARATOR TO REMAIN AND REUSED .
(E) CHEMICAL FEEDERS TO REMAIN AND REUSED.

SEE DETAIL 1 / M-501 FOR CHILLER DIMENSIONS
AND SERVICE CLEARANCES.
(E) HHW AIR SEPARATOR TO REMAIN AND REUSED.
(E) FLOOR SINK TO REMAIN AND REUSED.
(E) (2) COMBUSTION AIR LOUVERS TO REMAIN AND
REUSED. HI AND LOW.
(N) 3" BUTTERFLY ISOLATION VALVE WITH
ACTUATOR. INSTALL ON CHILLED WATER RETURN
PIPE.
(E) CONCRETE PAD TO REMAIN AND REUSED.
(N) CONCRETE PAD EXTENSION TO (E) CONCRETE
PAD. SEE STRUCTURAL DRAWINGS FOR DETAIL.

PROVIDE FLEXIBLE CONNECTIONS AT CHILLER
2 3
4 5
6 7
8 9
10 11
13 12
14 15
1 2
3 4
5 6
7 7
8 9
11 12
13 15
9 2
2 2
CH
1A
POC
3" CHWR ABOVE
3" CHWS BELOW
3CH
1B
16 16
17 10
(E) ELECTRICAL

TRANSFORMER(E) GENERATOR ROOM
(E) BOILER ROOM
(E) TRASH
(E) CHILLER YARD
(E) GENERATOR SET
1010
(TYP.)
3 M-501
(TYP.)
6 M-501
(E) ±1" DIA WALL OPENING
FOR DRAIN. (TYP.6)

INSULATED PIPE WITH

ALUMINUM JACKET PER
SPECIFICATIONS.
3" CHWR ABOVE
3" CHWS BELOW
16 1414
(N) 4" CHWR
(N) 4" CHWS
15 17
17 RJ
SS
DS

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.0850% CONSTRUCTION DOCUMENTS06/21/24 -- 90% CONSTRUCTION DOCUMENTS07/23/24 --
PLAN CHECK SUBMITTAL10/02/24 --
No. 30841REM
SATTE

ETER SIG
ER
P
D
LO A
C N
F HO C
A
AL I
F C
ANR
I
O
EFO
ISS

NER ENI GELANI
DARREN
B
. SMITH
Exp. 12/31/26PLAN CHECK CORRECTIONS04/01/251
1 1/4"=1'-0" CHILLER YARD NEW PLAN
TRUE
NORTHN

CHILLER YARD NEW PLAN
M-201
C>
3 ,, ,.

G
'i
0 "' I
~
~
u:i
0 0
X
"' 5J-.s= u
G
:::;
~
~ u
"' 0
~
ii
E
~
C
a.

G
"'
0 :,:
"' "' 0
"'
0 ~
0 "' I :::;
-"
~
C
...J
,:,~"""""""'-----
! na~~IBiT
·a =i ~
.s=
~
1/1
lo'. m
DIAL
BEFORE

YOU DIG

TWO WORKING

DAYS BEFORE

YOU DIG
TOLL FREE 111111111 1-800-227-2600

A PUBLIC SERVICE BY

UNDERGROUND SERVICE ALERT
~
-

II I I I I
II 1111
II II I 111
II II f-lH
11 ~ l;fi
II A ffff
I I I I f I If
I I 11 / / f I
I I 11 / f f I
I I 11 ff f I
~~f;ff
l!f!f/f/
ffff/ff/
f/ f/ If f /
f/ f; f; f /
I/ if I; f /
I f;
-wc"--7.,.

I/ f/ I I
I/ if I I I I
I; if I I f I
lif;if//
i/f;l;f;
I/ I/ I; I/
I/ If I I I I
i/f;lff/
1/f;lff/
I/ f/ I; I/
~JLJJ}}r
-
-
I I rY"I-· /\~
J_ _ _J_
I
7 I
I
I
I
I
I
I
I
I
eccc
C-
Ccc
-\ _J
~========-----~ \_jlccc
\ ~-------_J
,-----------------1 --------7
I I
I I
I I
I I
L____________ I _____________ _J
o~--------------
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
~=t~===---==+=+=t==±~f"SHml CITY OF CARLSBAD~ t-1-==t=jt======------====t==+=~==i=~ ~ PUBLIC WORKS DEPARTMENT l____E_j f-IMPRO\IEMENT PLANS FOR:
* *
/\
[====J~~=~j===============================f====~====l====jt===j APPROVED: JOHN MAASHOFF RCE 61909 EXP. 9/30/25

PUBLIC WORKS MANAGER CITY OF CARLSBAD DA TE

DA TE INITIAL
ENGINEER Of WORK REVISION DESCRIPTION

DATE INITIAL
OlHER APPROVAL

DA TE INITIAL

CITY APPROVAL
DWN BY: I PROJECT NO. II CHKD BY DRAWING NO~I
RVWD BY; ---.. _
6 NO SCALE PIPE SUPPOR AT SLAB 9 NO SCALE DETAIL
10 NO SCALE DETAIL
11 NO SCALE DETAIL
3 NO SCALE STAKED PIPE SUPPORT

1.131.7 44.01.111.2 44.0 35.8 47.0 28.6
CH
1A
CH
1B
CGy
CGx

PLAN VIEW

COIL SIDE
SEE NOTE #4

COIL SIDE
SEE NOTE #4

PANEL SIDE
SEE NOTE #4

SERVICE CLEARANCE
BORDER

AIR FLOW

AIR FLOW

42.00 MIN

42.00 MIN

48.00 MIN

48.00 MIN

SEE DETAILA

1.00 TYP. SEE
NOTE #4

0.99 TYP. SEE NOTE #4
Ø2.25
TYP.

2.68 TYP.

3.50 TYP.

1.00 TYP.

1.5 TYP.

FRONT VIEW

CONTROL BOX

HINGED ACCESS

MAIN POWER SHUT OFF

DISCONNECT

FORK TRUCK

POCKETS

CIRCUIT B

COMPRESSOR
ACCESS

CIRCUIT A

COMPRESSOR
ACCESS

DETAIL A

DETAIL A

BOTTOM VIEW

MOUNTING HOLE
TYP. SEE NOTE #4

AIR FLOWAIR FLOW

87.99 78.43
LWz
EWz
EWy & LWy

REAR VIEW

WATER-OUT
SEE NOTE #8

WATER-IN
SEE NOTE #8

AIR FLOWAIR FLOW
3X4.61

27.9823.9821.98

4.13 1.48
TYP. SEE
NOTE #4

1.50 TYP. SEE NOTE #4

94.80 33.98

92.01 78.43
CGz
EWx & LWx
SEE NOTE #8

97.76 RIGHT SIDE VIEWLEFT SIDE VIEW
VFD
ACCESS
GRILL
2-1/2" GROOVED

MACHINE OPTIONS
PUMP GREENSPEED COIL TYPE CGx CGy CGz

CENTER OF GRAVITY
INCH

ENTERING WATER (EW)
INCH

LEAVING WATER (LW)
INCH

X Y Z X Y Z
CONNECTION TYPE:

MCHX
±.25 ±.25 ±.25 ±.25 ±.25 ±.25
1 NO SCALE CHILLER DETAIL
7/8 DIA. KNOCK-OUT

FIELD POWER ENTRY
SEE NOTE #2
7/8 DIA. KNOCK-OUT FIELD

CONTROL WIRING ENTRY
-
NOTES:

1. DIMENSIONS SHOWN ARE IN INCHES.

2. DO NOT CAP OR OTHERWISE OBSTRUCT THE LIQUID LINE TEMPERATURE RELIEF.

3. 7/8 DIAM. PILOT HOLE PROVIDED FOR LOCATION FIELD POWER WIRING ACTUAL HOLE REQUIRED DEPENDS ON FIELD WIRING SIZING.

4. Ø 0.5 HOLE AND 0.8 X 0.4 SLOT USED FOR MOUNTING UNIT ON FRONT AND REAR BASE RAIL.

5. UNIT MUST HAVE SERVICE CLEARANCES AS FOLLOWS: TOP - DO NOT RESTRICT. COIL SIDE - 42 FROM SOLID SURFACE. PANEL SIDE - 48 PER NEC.

6. CARRIER DOES NOT RECOMMEND INSTALLATION IN A PIT.

7. UNIT CAN BE HANDLED USING THE FORK TRUCK LIFT POCKETS (MINIMUM OF 60 FORK LENGTH).

8. WATER CONNECTIONS RECESSED INSIDE UNIT. ALL WATER DRAIN AND VENTING HOLES ARE 1/4" NPT.

EQ EQ
EQ

SECTION A-A A A
EQ
(4)3/8" DIA. HILTI KB-TZ2
SS304 PER MFGR.
(ICC ESR 4266)
(2-3/4" NOMINAL EMBED)
HSS 2-1/2 x 2-1/2 x 1/4
TYP. @ 4'-0" O.C.

MAX. SPACING
1/4TYP.
1/4" CAP PLATE (TYP.)
1-1/2"
TYP
9"
9"
3/8" PLATE
(E) 4" CONCRETE SLAB
48"MAX.

L 2x2x1/4

INSULATED PIPE WITH ALUMINUM
JACKET AND "U" BOLTS

SEE PLAN FOR SIZE
3/8" DIA. HILTI KB-TZ2
SS304 PER MFGR.
(ICC ESR 4266)
(2-3/4" NOMINAL EMBED)
UNISTRUT P1000
(E) 4" CONCRETE SLAB
3/16

INSULATED PIPE WITH
ALUMINUM JACKET. SEE

PLAN FOR SIZE
NOTE: MAX. PIPE SUPPORT SPACING 4'-0" O.C.

RJ
SS
DS

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.0850% CONSTRUCTION DOCUMENTS06/21/24 -- 90% CONSTRUCTION DOCUMENTS07/23/24 --
PLAN CHECK SUBMITTAL10/02/24 --
No. 30841REM
SATTE

ETER SIG
ER
P
D
LO A
C N
F HO C
A
AL I
F C
ANR
I
O
EFO
ISS

NER ENI GELANI
DARREN
B
. SMITH
Exp. 12/31/26PLAN CHECK CORRECTIONS04/01/251

DETAILS
M-501
0 :,:
"' "' ::al
i5
,,
:!
0 a:

DIAL
BEFORE

YOU DIG

TWO WORKING

DAYS BEFORE

YOU DIG
•
•
J'H----....1..1_1
' " '
7 ..
<
..

I I t
' '
i--I I
I I
I--
I--
I/
~
. .. . . . . . . . ·--.
• •
=
I I
I I I
. . . . . . . . . . . . . . .

I..
--I I-
l~L
u
• •
= .
• .
·c;
. ..
• =
/
~,.__ . . .
00 I-/
I I
I I
I I
I I
I I
I I
I I
I I
I
I
I
I
I
I
I
I
• ' '
I I
I I
~
. ·--. . . . .
u
I
• : 1§1 . ' • . • . . :·rn:i· . . . .. • =
. . . .
~ L,=l
~_\_
0 0
7 . . .
' •
-• . -
. .
.
□
b
....

I..
'
. . .
00 -I
0 ~
7 J
I--
i
I
I
I
L ___ l
✓
7 7
_J
00 ~=3==t==============~==t==E==1=~ ~ CITY OF CARLSBAD fsHErnl t-1-==t=jt======------====t==+=~==i=~ ~ PUBLIC WORKS DEPARTMENT L___E_j f-~==t==t====---------===+==+==t==t=j ~IM~P~RO~VE~M~EN~T~PLA~N~S~F~OR~:=::::::::::=:::=:~~~~~=~_!::::~~~ ~====jt~=~j===============================i====]====j=====t===j ~AAfP~PiRR:00VJVEfcD>:': ==sJ~OH~N~MfjA~A~S~HO~F=;:F:=R;;;C;;;E:=';;'61;=;:9:=:::0=:::=9=:E==x=P=.9::::;/3=0=;=2=5

PUBLIC WORKS MANAGER CITY OF CARLSBAD DATE

DA TE INITIAL

ENGINEER OF WORK REVISION DESCRIPTION

DATE INITIAL
OlHER APPROVAL

DATE INITIAL

CITY APPROVAL
DWN BY: CHKD BY: ___ PROJECT NO.

RVWD BY:

II DRAWING NO.I

USED WITH NUMBERS AS WIRING

REFERENCE POINTS TO SIMPLIFY WIRING

DIAGRAM

LINE VOLTAGE WIRING
LINE VOLTAGE (120 VOLT) WIRING
LOW VOLTAGE (30 VOLT AND LESS)
A.C. WIRING
LOW VOLTAGE (30 VOLT AND LESS)
D.C. WIRING

INDICATES CONTROL PANEL TERMINAL

CONTACTS
NC

NONO - NORMALLY OPEN

NOHC - NORMALLY OPEN

NC - NORMALLY CLOSED

NCHO - NORMALLY CLOSED

CONTROL RELAY
CR

HAS CLOSED

HAS OPENED
120 VAC, 1PH, 60Hz 120V
480VAC, 3PH, 60Hz 480V, 3PH

IINTERLOCK

POWER SUPPLY FOR DC DEVICESPS
ABBR. / SYMBOLDESCRIPTION

4. 5.

3. 2.

V
M
E
CONTROL PANELS REQUIRE 120VAC POWER. SEE THE CONTROL

CONTRACTOR'S CONTROL SUBMITTAL DRAWINGS FOR QUANTITY
AND LOCATION OF 120V POWER & DISCONNECT.

FIRE SMOKE DAMPERS ARE ELECTRICALLY OPERATED. OPERATION

AND MONITORING MUST BE COORDINATED WITH THE LIFE SAFETY CONTRACTOR. SEE THE MECHANICAL DRAWINGS.

WIRING DIAGRAMS ARE SHOWN FOR CONTROL SEQUENCE AND
FUNCTION ONLY. THE ELECTRICAL CONTRACTOR TO INSURE THAT THE ELECTRICAL PORTION OF THIS WORK IS INSTALLED PER CODE.

LOW VOLTAGE CONDUIT & WIRE FURNISHED AND INSTALLED BY
MECHANICAL CONTRACTOR. LINE VOLTAGE CONDUIT & WIRE
FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR. REFER

TO ELECTRICAL PLANS FOR COMMUNICATION PATHWAYS IDENTIFIED

ON DRAWING COMMUNICATION CABLE IS BY CONTROL
CONTRACTOR.

FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR.

FURNISHED, INSTALLED & TERMINATED BY ELECTRICAL
CONTRACTOR.

FURNISHED BY MECHANICAL CONTRACTOR WIRED AND
TERMINATED BY ELECTRICAL CONTRACTOR.

FURNISHED BY ELECTRICAL CONTRACTOR WIRED AND
TERMINATED BY MECHANICAL CONTRACTOR.

FURNISHED BY EQUIPMENT VENDOR.

ME
EM
FFIRE ALARM CONTRACTOR.

CFURNISHED, INSTALLED AND WIRED BY CONTROL CONTRACTOR.

I
ANALOG
BINARY

INTERLOCK

FIRST LETTERSECOND LETTER

MEASURED OR

INITIATING VARIABLE

MODIFIERREADOUT OR

PASSIVE FUNCTION

OUTPUT FUNCTIONMODIFIER
A
B
C
D
E

ANALYSIS

BURNER COMBUSTION

CARBON DIOXIDE

USER CHOICE

VOLTAGE
-ALARM--

USER CHOICE USER CHOICE USER CHOICE -

CLOSED CONTROL - -
- - - DIFFERENTIAL
(PRIMARY ELEMENT)

SENSOR -- -

FFLOW RATERATIO (FRACTION)---

USER CHOICEG-GLASS VIEWING DEVICE--

HAND H---HIGH

ELECTRICAL CURRENTI-INDICATE--

POWER JSCAN---

TIME, TIME SCHEDULEKTIME, RATE OF CHANGE-CONTROL STATION-

LEVEL L-LIGHT-LOW

USER CHOICEMMOMENTARY--MIDDLE

USER CHOICEN-USER CHOICEUSER CHOICEINTERMEDIATE

OCCUPANCYO-ORIFICE, RESTRICTION-OPEN

PRESSURE, VACUUMPPOINT
(TEST CONNECTION)
---

QUANTITY QINTEGRATE, TOTALIZE---

RADIATION R-RECORD--

SPEED, FREQUENCYSSAFETY-SWITCHSTOP

TEMPERATURET-MULTIFUNCTIONTRANSMIT-

MULTIVARIABLEU--MULTIFUNCTIONMULTIFUNCTION

VIBRATION V-POINT
(TEST CONNECTION)
--

MECHANICAL ANALYSIS

WWEIGHT, FORCE-WELL--

STATUS XX-AXISUNCLASSIFIED

EVENT STATE OR

PRESENCEYY-AXIS--

POSITION, DIMENSIONZZ-AXIS-DRIVER ACTUATOR,-

UNCLASSIFIEDUNCLASSIFIED

RELAY COMPUTE,

CONVERT

UNCLASSIFIED FINAL

CONTROL ELEMENT

PRIMARY

LOCATION
***NORMALLY

ACCESSIBLE TO

OPERATOR
FIELD

MOUNTED

AUXILIARY

LOCATION
***NORMALLY

ACCESSIBLE TO

OPERATOR

DISCRETE

INSTRUMENT

SHARED DISPLAY,

SHARED CONTROL

COMPUTER FUNCTION

PROGRAMMABLE LOGIC

CONTROLLER
***NORMALLY INACCESSIBLE OR BEHIND-THE-PANEL DEVICES

OR FUNCTIONS MAY BE DEPICTED BY USING THE SAME
SYMBOL BUT WITH DASHED HORIZONTAL BARS, I.E.

DESCRIPTION

LOW VOLTAGE ELECTRICAL

ANALOG SIGNAL

LOW VOLTAGE ELECTRICAL

BINARY SIGNAL OR POWER

HYDRAULIC OR

PNEUMATIC SIGNAL

ELECTRICAL POWER

NETWORK

COMMUNICATION CABLE
480V, 3Ø

SOLENOID

CONTROL RELAY
XXCR
XXMS

MOTOR STARTER/CONTACTOR
XXTR

TIMER RELAY
XXESCR

ESTOP CONTROL RELAY

PILOT LIGHT X

A-AMBER
B-BLUE

C-CLEAR

G-GREEN
R-RED
W-WHT

Y-YELLOW

XPILOT LIGHT PUSH TO TEST
M

PANEL WIRING

FIELD WIRING

FILED ENCLOSURE

CONNECTION
XXX

NO CONNECTION

XWIRE CONTINUATION

X-DRAWING SECTION

XXX-LINE NUMBER

SLIP RING

DETACHABLE CONNECTOR

FUSED TERMINAL BLOCK

EARTH GROUND

CHASSIS GROUND

MCC/FIELD TERMINAL

GENERAL PURPOSE TERMINAL

DIN TERMINAL BLOCK

DEVICE SPECIFIC TERMINAL BLOCK

DISCONNECT

CIRCUIT BREAKER

FUSIBLE DISCONNECT

THERMAL OVERLOAD

MAGNETIC OVERLOAD
3 PHASE MOTORM

CONTROL POWER TRANSFORMER

1.CONTROL'S CONSTRUCTOR TO COORDINATE WITH CITY OF CARLSBAD

AND SAFETY CENTER BUILDING MANAGEMENT FOR SELECTION OF

FIELD, EQUIPMENT CONTROLLERS AND INTEGRATION WITH EXISTING BAS.

ABBREVIATIONSSYSTEM SCHEMATIC IDENTIFICATION LETTERS WIRING SYMBOLS

POWER SYMBOLS

PROCESS DEVICES

WIRING DIAGRAM SYMBOLS

GENERAL NOTES

INSTRUMENT LINE SYMBOL

BAI BACNET ANALOG INPUT

BAO BACNET ANALOG OUTPUT

BBI BACNET BINARY INPUT

BBO BACNET BINARY OUTPUT

BI BINARY INPUT

BO BINARY OUTPUT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

DA DISCHARGE AIR

DI DIGITAL INPUT

DO DIGITAL OUTPUT

EA EXHAUST AIR

EF EXHAUST FAN

EVAP EVAPORATOR

F FAHRENHEIT

FCU FAN COIL UNIT

HP HEAT PUMP

HRU HEAT RECOVERY UNIT

HTEX HEAT EXCHANGER

MAX MAXIMUM

MIN MINIMUM

MISC MISCELLANEOUS

OA OUTDOOR AIR

RA RETURN AIR

RF RETURN FAN

RH RELATIVE HUMIDITY

RTU ROOFTOP UNIT

SA SUPPLY AIR

SF SUPPLY FAN

SP STATIC PRESSURE

TEMP TEMPERATURE

VAV VARIABLE AIR VOLUME

VAVTU VARIABLE AIR VOLUME TERMINAL UNIT

VVT VARIABLE VOLUME & TEMPERATURE

W/ WITH

W/O WITHOUT

DUCT TEMP
SENSOR

HEATING COOLING

SUPPLY FAN RETURN FAN
STATIC

PRESSURE
SENSOR
DIFF.

PRESSURE
SENSOR

ENTHALPY OR

HUMIDITY
SPACE
SENSOR

FILTER MANUAL
DAMPER

BAROMETRIC
RELIEF
DOOR

CONTACT

CEILING
MOUNT
MOTION

SENSORWIRE NUT

HORIZONTAL

ECONOMIZER

VERTICAL

ECONOMIZER

WELL TEMP
SENSOR

LIQUID FLOW
METER

LIQUID DIFF

PRESSURE
SENSOR
2-WAY VALVE3-WAY VALVE

COMMUNICATION BUS SPECIFICATION

1. A 24 AWG 2-CONDUCTOR-SHIELDED-STRANDED CABLE (PLENUM RATED AS REQUIRED) MUST BE DAISY CHAINED FROM CONTROLLER TO CONTROLLER.

IT SHOULD BE COLOR CODED (RED, BLACK, WHITE).

2. THE COMMUNICATION CABLE OPERATES AT UP TO 5 VDC. VERIFY WITH THE LOCAL CODE AUTHORITY AND SPECS REGARDING CONDUIT REQUIREMENTS.

3. NO "T" TAP OR "STAR" TYPE CONNECTIONS ARE PERMITTED.

4. TERMINATE THE SHIELDS ON THE DESIGNATED TERMINAL AT EACH DEVICE.

5. 30 CONTROLLER’S MAXIMUM PER COMMUNICATION BUS SEGMENT. 60 CONTROLLER’S MAXIMUM PER NETWORK ROUTER.

6. A REPEATER IS REQUIRED EVERY 2000 FT. OR 30 DEVICES. MAXIMUM OF 4 REPEATERS PER BUS FOR A TOTAL OF 10,000 FT.

GENERAL NOTES

1. THE 2 CONDUCTOR COMMUNICATION CABLE AND SENSOR CABLES MUST ALWAYS BE IN A SEPARATE JACKET FROM ONE ANOTHER. NEVER RUN THESE CABLES IN THE SAME CONDUIT AS, OR BUNDLE THEM WITH, AC POWER WIRING OF ANY VOLTAGE. DO NOT STRAP THESE CABLES ALONG ANY CONDUITS THAT CONTAIN AC POWER WIRING OF ANY VOLTAGE. DO NOT RUN THESE

CABLES IN RINGS OR CONDUIT WITH FIRE, LIFE, SAFETY, SECURITY, NETWORK, TELEPHONE, POWER, OR OTHER WIRING. WHEN RUNNING COMMUNICATION AND SENSOR WIRING PARALLEL TO OTHER CABLING OR CONDUIT MAINTAIN A 12 IN. DISTANCE.

2. ETHERNET AND/OR INTERNET CONNECTION TO I-VU ARE SUPPLIED AND MAINTAINED BY BUILDING OWNER/OPERATOR.

INSTALLATION COORDINATION NOTES

1. INSTALLER SHALL COORDINATE ALL POWER AND DATA CONNECTION REQUIREMENTS WITH THE GC ONSITE.

2. INSTALL ALL COMPONENTS IN ACCORDANCE WITH THE SPECIFICATION, APPLICABLE CODES AND MANUFACTURER’S LITERATURE
PUMP

ALTERNATING CURRENT

ACKNOWLEDGE

ANALOG INPUT
ALARM

AUTO-MANUAL

ANALOG OUTPUT

AID SUPPLY

BUILDING AUTOMATION SYSTEM
CLOSE

COMMON ALARM
CATEGORY 5 CABLING

CONTROL RELAY

CENTRAL ENERGY PLANT

CONSTANT SPEED PUMP

CARRIER COMFORT NETWORK

DIRECT CURRENT

DISTRIBUTED CONTROL SYSTEM

END OF LINE

ELECTRIC SUPPLY

ELAPSED TIME METER

FLOW METER

GAS SUPPLY

HAND-AUTO

HIGH-LOW

HIGH-LOW-OFF-REMOTE

HUMAN MACHINE INTERFACE

HAND-OFF-AUTO

HYDRAULIC SUPPLY

HARDWIRED INPUT/OUTPUT

INSTRUMENT AIR
INSTRUMENT S.O.A.

INSTRUMENTATION & CONTROL

INPUT/OUTPUT

JAVA APPLICATION CONTROL ENGINE

LOCAL CONTROL PANEL

LOCAL-OFF-REMOTE

LOCK-OUT-STOP

MOTOR CONTROL CENTER

NETWORK POINT

NORMALLY OPEN

NORMALLY CLOSED

NITROGEN SUPPLY

PLANT AIR

POWER SUPPLY

PROPORTIONAL INTEGRAL DERIVATIVE

PROCESS & INSTRUMENT DIAGRAM

PROGRAMMABLE LOGIC CONTROLLER

PRESSURE REDUCING VALVE

REGIONAL ENERGY EFFICIENCY

PROJECT FACILITY

REMOTE I/O

START-STOP

STEAM SUPPLY

TRANSFER CONTROL

PROTOCOL/INTERNET PROTOCOL

TOTALIZATION

TIME PROPORTIONAL CONTROL

TWISTED SHIELDED PAIR

UNINTERRUPTIBLE POWER SUPPLY

VARIABLE FREQUENCY DRIVE

WATER SUPPLY

DATAHIWAY

DATAHIWAY PLUS
MODBUS

MODBUS PLUS

PANEL VIEW
AC
ACK
AI
AL
AM
AO
AS
BAS
C
CA
CAT5
CR
CEP
CSP
CNN
DC
DCS
EOL
ES
ETM
FM
GS
HA
HL
HLOR
HMI
HOA
HS
HW
IA
ISA
I&C
I/O
JACE
LCP
LOR
LOS
MCC
NET
N.O.

N.C.

NS
PA
PS
PID
P&ID
PLC
PRV
REEP
RIO
S/S
SS
TCP/IP
TOT
TPC
TSP
UPS
VFD
WS
DH
DH+
MB
MB+
PV

GENERAL INFORMATION

SYMBOL LEGEND
RJ
SS
DS

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.0850% CONSTRUCTION DOCUMENTS06/21/24 -- 90% CONSTRUCTION DOCUMENTS07/23/24 --
PLAN CHECK SUBMITTAL10/02/24 --
No. 30841REM
SATTE

ETER SIG
ER
P
D
LO A
C N
F HO C
A
AL I
F C
ANR
I
O
EFO
ISS

NER ENI GELANI
DARREN
B
. SMITH
Exp. 12/31/26PLAN CHECK CORRECTIONS04/01/251

CONTROLS LEGEND AND ABBREVIATION
M-601
0 I
~ i,_
,,
C
C
~
'-0
a.

C
u
CXJ
a
"' a a
~ ,,
"' "' a
"'
0 0
<O
I
::;
..;
[
C
...J
C
.c
"' ~
~
~
= =
@+-
~ Jm
~ w ~I~
[!]\ /\ /\ ,r,r,
g;J
t!l ...... ,..,. ...... ,..,.
la w !
c::::J
GiJ
\"j\7\ ,r,r,
,..,.,
...... ,..,. ...... ,..,.
□
D
0 0
0 0
0 0
0 ------
---
-·-- - - - - -
0 □
□
o-0--o
.
'
l (
I-
I--
'
+
o-0--o
----
o-0--o t
o-0--o ~
o-0--o .. ..
o--Q-o
--
181
o--Q-o
II ' r:: -----o-r 0---
' -----o--<o-
' hf' ,~ ) ( ____,,;.--0---
----I ,-( ---0: 0---
' ,..,.,_ ---0: 0--- ------1 ' r-..
8 --0 0---
8 0
' r:: -----o-r o---[I]]-
'
□ 8
t> -----o--< o---[I])-
a
' ____,,;.--o---[I])-
►
e 0 e
----o(X'o--
----o(X'o--
----o(X'o--
B □ B
----o"-,o---
----o"-,o---
----o"-,o---
3) 8 ~ e
§
fSHml CITY OF CARLSBAD ~ 1-----1--+---------------t----t--+----i----t ~ PUBLIC WORKS DEPARTMENT L.E_j t=====t====t================================t====~~====t====~====~ IMPRO\IEMENT PLANS FOR:
* *
/\.
] DIAL TWO WORKING PUBLIC WORKS MANAGER CITY OF CARLSBAD DA TE ! ,:;;:, • .:::: M~ '""~ RE~SION DESCRIPSON M~ ,.,_ :; ... ==~ !~ '~-=--=-=== I PROJECT NO, II DRAWING NO.I APPROVED: JOHN MAASHOFF RCE 61909 EXP. 9/30/25
~a:Go l.::;~~t&~~J~~=j __________________________________________________________ JL _______________________ J.::EN:G:IN~EE~R~OF~WO=Rl,K __ _:~.:=~=:::._:::, ___ _J~o:TH!E:.R_:A:::PP:::R::;ov:AL:.J~~,:::::;::::,~:;:::;:::;::::::::::::::::!.!:· ========;!!::====:J ~ A PUBLIC SERVICE BY

UNDERGROUND SERVICE ALERT
1 NO SCALE CONTROLS RISER DIAGRAM

ADMIN BLDG

EXISTING PC OR INTERNET DEVICE WITH

STANDARD WEB BROWSER SOFTWARE AND

LAN ACCESS, SUPPLIED BY OTHERS
1 PC

CUSTOMER LOCAL AREA NETWORK

ON GRADE
1 WS

EXISTING I-VU

APPLIANCE
WEB
SERVER
1A
CH

CHILLER
BACNET

INTERFACE
1B
CH

CHILLER
BACNET

INTERFACE
1 1
CP

CHILLER
PLANT

CONTROL

LOCAL AREA NETWORK
042007DB

WIRE LEGEND

BACNET MS/TP NETWORK WIRING

BURIAL BACNET MS/TP NETWORK WIRING
042002-S

PROVIDED AND INSTALLED BY OTHERS
24 AWG 2 COND SHIELDED, PLENUM, ORANGE
24 AWG 2 COND SHIELDED, BURIAL, BLACK

LINE STYLE WIRE TYPEPART NUMBERDESCRIPTION
I/O NETWORK WIRING043009AL22 AWG 2 COND SHIELDED, PLENUM, BLUE VRF NETWORK WIRING001320-S16 AWG 2 COND SHIELDED, PLENUM, WHITE BACNET MSTP NETWORK GUIDELINES:

A MSTP NETWORK SHALL NOT EXCEED 10,000 FEET OVERALL LENGTH, CONSISTING OF UP TO FIVE 2000 FOOT SEGMENTS WITH NO GREATER THAN 30 DEVICES PER SEGMENT.

EACH 2000 FOOT SEGMENT SHALL BE JOINED TO THE NEXT SEGMENT USING A BACNET REPEATER WITH APPROPRIATE TERMINATION. NO MORE THAN 4 REPEATERS CAN BE USED ON A SINGLE BACNET MSTP NETWORK. EACH SEGMENT WILL HAVE TERMINATION AT THE BEGINNING AND END OF THE SEGMENT.

EXISTING CARRIER EQUIPMENT INSTALLED IN PHASE 1 OF PROJECT ON CARRIER BACNET MS/ TP NETWORK. NOT INCLUDED IN CURRENT PROJECT SCOPE OF WORK. 1 NOTES:

1. NETWORK TOPOLOGY MAY VARY BASED UPON FIELD CONDITIONS

2. CONTROLS ROVIDED AND INSTALLED BY RUSSELL SIGLER INC CONTROLS GROUP

SEQUENCE OF OPERATION
CHILLED WATER SYSTEM - RUN CONDITIONS:

THE EQUIPMENT WILL RUN ACCORDING TO THE FOLLOWING USER SELECTABLE MODES:
·OFF: THE EQUIPMENT WILL NOT RUN AND ALL OUTPUTS WILL REMAIN IN THEIR OFF POSITION. ·REMOTE OR MANUAL START/STOP: THE EQUIPMENT WILL RUN WHENEVER THE "REMOTE" BINARY INPUT OR "MANUAL" START/STOP IS ENABLED.
·OUTSIDE AIR TEMPERATURE: THE EQUIPMENT WILL RUN WHENEVER THE OUTSIDE AIR TEMPERATURE IS GREATER THAN ITS USER DEFINABLE SETPOINT (ADJ.)
·SCHEDULE: THE EQUIPMENT WILL RUN WHENEVER SCHEDULED.
·COOLING REQUESTS & OUTSIDE AIR TEMPERATURE:

O THE EQUIPMENT WILL RUN WHENEVER A DEFINABLE NUMBER OF CHILLED WATER COILS NEED COOLING; AND THE OUTSIDE AIR TEMPERATURE IS GREATER THAN ITS USER DEFINABLE SETPOINT (ADJ.).

O OUTSIDE AIR TEMPERATURE AND SCHEDULE OR MANUAL START/STOP: THE EQUIPMENT WILL RUN WHENEVER THE OUTSIDE TEMPERATURE IS ABOVE ITS USER DEFINABLE SETPOINT (ADJ.) AND WHENEVER IT IS SCHEDULED.

BOTH CONDITIONS MUST BE TRUE FOR THE UNIT TO RUN. THE EQUIPMENT WILL ALSO RUN IF THE "REMOTE" BINARY INPUT OR "MANUAL" START/STOP IS ENABLED.

POWER-UP START-UP DELAY:

THERE WILL BE A 60 SECOND (ADJ.) DELAY IN ENABLING THE EQUIPMENT ON INITIAL START-UP OR AFTER A POWER LOSS.

FREEZE PROTECTION:

THE CHILLED WATER PUMPS WILL ALSO RUN FOR FREEZE PROTECTION WHENEVER OUTSIDE AIR TEMPERATURE IS LESS THAN 38 °F (ADJ.).

CHILLED WATER PUMPS - LEAD/STANDBY OPERATION:

ONE OF THE TWO CHILLED WATER PUMPS WILL RUN ANYTIME A CHILLER IS CALLED TO RUN.

THE LEAD PUMP WILL START PRIOR TO THE CHILLER BEING ENABLED AND WILL STOP ONLY AFTER THE CHILLER IS DISABLED.

THE PUMPS WILL THEREFORE HAVE:
·A USER ADJUSTABLE DELAY ON START.
·AND A USER ADJUSTABLE DELAY ON STOP.

THE DELAY TIMES WILL BE SET APPROPRIATELY TO ALLOW FOR ORDERLY CHILLED WATER SYSTEM START-UP, SHUTDOWN, AND SEQUENCING.

THE TWO PUMPS WILL OPERATE IN A LEAD/STANDBY FASHION.
·THE LEAD PUMP WILL RUN FIRST.
·ON FAILURE OF THE LEAD PUMP, THE STANDBY PUMP WILL RUN AND THE LEAD PUMP WILL TURN OFF.

THE DESIGNATED LEAD PUMP WILL ROTATE UPON ONE OF THE FOLLOWING CONDITIONS (USER SELECTABLE):
·MANUALLY THROUGH A SOFTWARE SWITCH
·IF PUMP RUNTIME (ADJ.) IS EXCEEDED
·DAILY
·WEEKLY
·MONTHLY
ALARMS WILL BE PROVIDED AS FOLLOWS:
·CHILLED WATER PUMP 1
O FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

O RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

O RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT.

O VFD FAULT.
·CHILLED WATER PUMP 2
O FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

O RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

O RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT.

O VFD FAULT.

CHILLED WATER DIFFERENTIAL PRESSURE CONTROL:

THE CONTROLLER WILL MEASURE CHILLED WATER DIFFERENTIAL PRESSURE AND MODULATE THE CHILLED WATER PUMP VFD TO MAINTAIN THE CHILLED WATER DIFFERENTIAL PRESSURE SETPOINT. THE FOLLOWING SETPOINTS ARE RECOMMENDED VALUES. ALL SETPOINTS WILL BE FIELD ADJUSTED DURING THE COMMISSIONING PERIOD TO MEET THE REQUIREMENTS OF ACTUAL FIELD CONDITIONS.

THE CONTROLLER WILL MODULATE CHILLED WATER PUMP SPEEDS TO MAINTAIN A CHILLED WATER DIFFERENTIAL PRESSURE OF 10 PSID (ADJ.). THE VFDS MINIMUM SPEED WILL NOT DROP BELOW 20% (ADJ.).

ALARMS WILL BE PROVIDED AS FOLLOWS:
·HIGH CHILLED WATER DIFFERENTIAL PRESSURE: IF THE CHILLED WATER DIFFERENTIAL PRESSURE IS 25% (ADJ.) GREATER THAN SETPOINT.
·LOW CHILLED WATER DIFFERENTIAL PRESSURE: IF THE CHILLED WATER DIFFERENTIAL PRESSURE IS 25% (ADJ.) LESS THAN SETPOINT.

CHILLED WATER BYPASS VALVE -VARIABLE PRIMARY FLOW CONTROL:

THE CONTROLLER WILL MEASURE SYSTEM CHILLED WATER FLOW AND MODULATE THE CHILLED WATER BYPASS VALVE OPEN TO MAINTAIN THE SYSTEM CHILLED WATER FLOW MINIMUM SETPOINT OF 45 GPM (ADJ.) FOR SINGLE CHILLER OPERATION AND 90 GPM (ADJ.) FOR DUAL CHILLER OPERATION. ONCE THE MINIMUM FLOW SETPOINT IS EXCEEDED BY 10% THE BYPASS SHOULD BE FULLY CLOSED.

ALARMS WILL BE PROVIDED AS FOLLOWS:
·LOW CHILLED WATER FLOW: IF THE CHILLED WATER FLOW IS 25% (ADJ.) LESS THAN SETPOINT.

CHILLERS - LEAD/LAG OPERATION:

THE TWO CHILLERS WILL OPERATE IN A LEAD/LAG FASHION.

THE FOLLOWING SETPOINTS ARE RECOMMENDED VALUES. ALL SETPOINTS WILL BE FIELD ADJUSTED DURING THE COMMISSIONING PERIOD TO MEET THE REQUIREMENTS OF ACTUAL FIELD CONDITIONS.

THE CHILLERS WILL BE STAGED AS FOLLOWS:
·THE LEAD CHILLER WILL RUN FIRST.
·ON FAILURE OF THE LEAD CHILLER, THE LAG PUMP WILL RUN AND THE LEAD PUMP WILL TURN OFF. ·THE LAG CHILLER WILL STAGE ON WHEN THE CHILLER DEMAND LOAD REACHES 85% (ADJ.) OF THE LEAD CHILLER CAPACITY FOR 10 MINUTES (ADJ.) OR IF THE MAIN CHILLED WATER SUPPLY TEMPERATURE RISES 2°F (ADJ.) ABOVE SETPOINT FOR 5 MINUTES (ADJ.). THE LEAD AND LAG CHILLERS WILL RUN IN UNISON MAINTAIN CHILLED WATER SUPPLY TEMPERATURE SETPOINT.
·THE LAG CHILLER WILL STAGE OFF WHEN THE CHILLER DEMAND LOAD FOR BOTH CHILLERS REACHES 30% (ADJ.) OF CHILLER CAPACITY FOR 10 MINUTES (ADJ.) OR IF THE MAIN CHILLED WATER SUPPLY TEMPERATURE DROPS 2°F (ADJ.) BELOW SETPOINT FOR 5 MINUTES (ADJ.). THE LEAD CHILLER WILL CONTINUE TO RUN TO MAINTAIN CHILLED WATER SUPPLY TEMPERATURE SETPOINT.

TO PREVENT SHORT CYCLING, THERE WILL BE A USER DEFINABLE DELAY (ADJ.) BETWEEN STAGING UP OR DOWN, UNLESS SHUTDOWN ON SAFETIES OR FAILURE. EACH CHILLER WILL RUN SUBJECT TO ITS OWN INTERNAL SAFETIES AND CONTROLS.

THE DESIGNATED LEAD PUMP WILL ROTATE UPON ONE OF THE FOLLOWING CONDITIONS (USER SELECTABLE):
·MANUALLY THROUGH A SOFTWARE SWITCH
·IF PUMP RUNTIME (ADJ.) IS EXCEEDED
·DAILY
·WEEKLY
·MONTHLY
ALARMS WILL BE PROVIDED AS FOLLOWS:
·CHILLER 1
O FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

O RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

O RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT. ·CHILLER 2
O FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.

O RUNNING IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.

O RUNTIME EXCEEDED: STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT. ·LEAD CHILLER FAILURE: THE LEAD CHILLER IS IN FAILURE AND THE LAG CHILLER IS ON. ·HIGH MAIN CHILLED WATER SUPPLY TEMP: IF THE MAIN CHILLED WATER SUPPLY TEMPERATURE IS GREATER THAN 65 °F (ADJ.).
·LOW MAIN CHILLED WATER SUPPLY TEMP: IF THE MAIN CHILLED WATER SUPPLY TEMPERATURE IS LESS THAN 38 °F (ADJ.).

CHILLER ISOLATION VALVES:

THE CHILLER ISOLATION VALVE WILL OPEN ANYTIME THE CHILLER IS CALLED TO RUN AND SHALL CLOSE ONLY AFTER THE CHILLER IS DISABLED.

THE CHILLER ISOLATION VALVE WILL THEREFORE HAVE:
·A USER ADJUSTABLE DELAY FOR THE CHILLER UPON ENABLE.
·AND A USER ADJUSTABLE DELAY ON CLOSE.

THE DELAY TIMES SHALL BE SET APPROPRIATELY TO ALLOW FOR ORDERLY CHILLED WATER SYSTEM START-UP, SHUTDOWN, AND SEQUENCING.

ALARMS WILL BE PROVIDED AS FOLLOWS:
·CHILLER 1 ISOLATION VALVE
O FAILURE: COMMANDED OPEN, BUT THE STATUS IS CLOSED.

O OPEN IN HAND: COMMANDED CLOSED, BUT THE STATUS IS OPEN. ·CHILLER 2 ISOLATION VALVE
O FAILURE: COMMANDED OPEN, BUT THE STATUS IS CLOSED.

O OPEN IN HAND: COMMANDED CLOSED, BUT THE STATUS IS OPEN. 2 NO SCALE SEQUENCE OF OPERATION
RJ
SS
DS

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.0850% CONSTRUCTION DOCUMENTS06/21/24 -- 90% CONSTRUCTION DOCUMENTS07/23/24 --
PLAN CHECK SUBMITTAL10/02/24 --
No. 30841REM
SATTE

ETER SIG
ER
P
D
LO A
C N
F HO C
A
AL I
F C
ANR
I
O
EFO
ISS

NER ENI GELANI
DARREN
B
. SMITH
Exp. 12/31/26PLAN CHECK CORRECTIONS04/01/251

CONTROLS RISER DIAGRAM AND SEQUENCE OF

OPERATION
M-602
~
G
.s= u
I
0 I
~
"tJ
C
C
-~ 0 a.
"tJ
C
-" w -;:

C
u
CXJ
a .,;
g
~
"tJ
~
C
.s=
'.!),
"' "' ~
~
~
0 "' ~
"tJ
~
C
.s=
'.!),
1ii "­
I
(/)
0 ~
~
<O
I ::;
..;
[
C
...J
C
.s=
"' ti
(/)
"tJ t:"':"""""""' ______ _
i JDJIO~rloIBiT
·a c= ~
.s=
Jl
l',
a,
DIAL
BEFORE

YOU DIG

TWO WORKING

DAYS BEFORE

YOU DIG
TOLL FREE 1-800-227-2600

A PUBLIC SERVICE BY

UNDERGROUND SERVICE ALERT
('(
I
,__ ___ ---
0 * *
7 _)

B B B B
/ / / / / /
9 ,
J l

I I I I I
l
I
! )
~=t=j====---===+=+=t==t~fSHml CITY OF CARLSBAD ~
t"l-==t=jt=======-----====t==+==l==i=~ ;::~~
9 ~~~~P~U~BL::IC::::::::W:::O::::R:::KS::::::D:::E:::PA~R~TM~E~NT!::::=!JLE._j~~ 2 ::::! I-I IMPROVEMENT PLANS FOR:
/'I,
~==~E~~t====================~===E==l===t=~ fAAPFPPiR(Ro~VEEDD~: ~JO~HN~M~A~AS~~~==============;:===::! I-HOFF RCE 61909 EXP. 9/30/25

PUBLIC WORKS MANAGER CITY OF CARLSBAD DATE

DA TE INITIAL

ENGINEER OF WORK REVISION DESCRIPTION

DATE INITIAL

OTHER APPROVAL

DA TE INITIAL

CITY APPROVAL
DWN BY: ---I PROJECT NO.

RCVHWKDD BY: __ _
BY: .
1 NO SCALE CHILLED WATER SYSTEM P&ID - EXISTING / DEMOLITION KEYNOTES:

DRAIN
PI
AAV
DRAIN
CHWR
CHWS
AHU-1CHW COIL
TT
FCZT
AAV
DRAIN
DCWWM
PRV

DRAINDRAIN
PI
FILL
QUICK
PRV
FQ
RPB1" CW
VFD
PI
FSTIT
FLEX
CP
TIT
FLEX

DI DO AOPULSE

MAKE UP WATER

CONSUMPTION
CH-1 ALARM
CH-1 TEMP. SET POINT
CH-1 START / STOP
NETWORK CON.

DO CHWP-2 START / STOP
XCSC
AOPHWP-2 SPEED
SIGNAL
460V/3p
PDT

AI CHW DIF PRESSURE
AHU-2
TT
FCZT

CHW COIL
1 CH
(D) CHILLERFCZT
AI

VALVE SIGNAL

VALVE POSITION
AO
RS485 BACNET
MS/TP
FIT

AI CHW WATER FLOW
M M
VFD
XCSC 460V/3p
DO CHWP-1 START / STOP
AOPHWP-1 SPEED
SIGNAL
P
2 P
1 4"
3"
3"
2-1/2"
2-1/2"

EXTERNAL CONTROLLER
TIT
TIT
AI CHWR TEMP.

AI CHWS TEMP.
4"
4"
ET
1 AS
1 4"
4"
3"
4"

6.3 GAL
AHU-3
TT
FCZT

CHW COIL
1"
1"
1-1/2"
3" 4"
4"
1-1/2"
CPF
1 DRAIN
PI
AAV
DRAIN
CHWR
CHWS
AHU-1CHW COIL
TT
FCZT
AAV
DRAIN
DCWWM
PRV

DRAINDRAIN
PI
FILL
QUICK
PRV
FQ
RPB1" CW
VFD
PI
FS
TIT
TIT
PULSE

MAKE UP WATER

CONSUMPTION
NETWORK CON.

DO CHWP-2 START / STOP
XCSC
AOPHWP-2 SPEED
SIGNAL
460V/3p
PDT

AI CHW DIF PRESSURE
AHU-2
TT
FCZT

CHW COIL
FCZT
AI

VALVE SIGNAL

VALVE POSITION
AO
RS485 BACNET
MS/TP
5 FIT

AI CHW WATER FLOW
M M
VFD
XCSC 460V/3p
DO CHWP-1 START / STOP
AOPHWP-1 SPEED
SIGNAL
P
2 P
1 4"CHWS
3"
3"
2-1/2"
2-1/2"
2 2
1 EXTERNAL CONTROLLER
6 TIT
TIT
AI CHWR TEMP.

AI CHWS TEMP.
4 4
4"
4"
3 7
ET
1 AS
1 9 9
55 4"
4"CHWR
3"
4"

6.3 GAL
AHU-3
TT
FCZT

CHW COIL
1"
1"
2 1-1/2"
3" 4"
4"
1-1/2"
CPF
1 2 NO SCALE CHILLED WATER SYSTEM P&ID - NEW
3 4
2 1
5 6
7 8
9 1
2 3
4 5
6 7
8 9
2 2 2
4 1
5 4
3 9
5 5
6 8
6 9
7 DEMOLISH AND REMOVE (E) CARRIER i VU COMPATIBLE CONTROLLER (E) 2-WAY VALVE CONTROLLED FROM AHU CONTROLLER
(E) SETRA 230 0-100 PSID, 3 VALVE MANIFOLD, 4-20 mA, CALIBRATION CERTIFICATE AH5. CONNECT LOW PRESSURE TO UPSTREAM SIDE OF PUMP. BI-DIRECTIONAL ± 25 PSID.
(E) TEMPERATURE TRANSMITTER NEMA 4. 4.20 mA, PROBE LENGTH TO CENTER OF PIPE. STAINLESS STEEL WELL WITH 2" EXTENSION FOR INSULATION.
(E) NETWORK CONNECTION
(E) SENSORS TO BE REPLACED.
(E) ONICON F 4600 INLINE FLOW METER. 4", 1.5 PSIG @ 110 GPM. 0.5 GPM MINIMUM FLOW. FLANGE CONNECTION. 4.20 mA. USED FOR BYPASS

VALVE CONTROL AND ENERGY TRENDING
(E) FLOW SWITCH TO BE REMOVED.
(E) VARIABLE FREQUENCY DRIVE PROVIDED BY PUMP MANUFACTURER ORDER WITH BACnet MS/TP NETWORK PROTOCOL
DEMOLISH AND REMOVE (E) CHILLER.

KEYNOTES:
(N) CARRIER i VU COMPATIBLE CONTROL PANEL.

CONTROL PANEL SHALL CONFORM TO UL 508A STANDARDS.
(E) 2-WAY VALVE CONTROLLED FROM AHU CONTROLLER
(E) SETRA 230 0-100 PSID, 3 VALVE MANIFOLD, 4-20 mA, CALIBRATION CERTIFICATE AH5. CONNECT LOW PRESSURE TO UPSTREAM SIDE OF PUMP. BI-DIRECTIONAL ± 25 PSID.
(E) TEMPERATURE TRANSMITTER NEMA 4. 4.20 mA, PROBE LENGTH TO CENTER OF PIPE. STAINLESS STEEL WELL WITH 2" EXTENSION FOR INSULATION.
(E) NETWORK CONNECTION
NEW SENSORS .
(E) ONICON F 4600 INLINE FLOW METER. 4", 1.5 PSIG @ 110 GPM. 0.5 GPM MINIMUM FLOW. FLANGE CONNECTION. 4.20 mA. USED FOR BYPASS

VALVE CONTROL AND ENERGY TRENDING
TRANSMITTER WITH LOCAL DISPLAY.
(E) VARIABLE FREQUENCY DRIVE PROVIDED BY PUMP MANUFACTURER ORDER WITH BACnet MS/TP NETWORK PROTOCOL
3" BUTTERFLY ISOLATION VALVE WITH ACTUATOR.
10 10
1A
CH
POC
POD
POD
POC
FLEX
FLEX
4"
4"
3"CHWS
3"CHWS
3" CHWR
24 VAC
AI CHWS TEMP.

AI CHWR TEMP.

PDT
1B
CH
FLEX
FLEX
PDT

TIT TIT
FS
AI CH-1B CHWS TEMP.

AI DI AI AI CH-1B CHW DIF PRESSURE
3"CHWS
3"CHWR
3"CHWR
10 10 10
119 GPM 119 GPM
8 8
8 8
240 GPM MAX.
44 GPM MIN.
45 GPM MAX. SINGLE CHILLER
90 GPM MAX. DUAL CHILLERS
DI CH-1B STATUS
CH-1B ISO POS
AO
6 AOCH-1A CHWST SETPOINT
DI CH-1A ALARM
CH-1A S/S
DO
CH-1A CHWS TEMP.

CH-1A CHW DIF PRESSURE
CH-1A STATUS
AOCH-1B CHWST SETPOINT
DI CH-1B ALARM
CH-1B S/S
DO
CH-1B ISO FB
AI
CH-1A ISO POS
AO
CH-1A ISO FB
AI
RJ
SS
DS

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.0850% CONSTRUCTION DOCUMENTS06/21/24 -- 90% CONSTRUCTION DOCUMENTS07/23/24 --
PLAN CHECK SUBMITTAL10/02/24 --
No. 30841REM
SATTE

ETER SIG
ER
P
D
LO A
C N
F HO C
A
AL I
F C
ANR
I
O
EFO
ISS

NER ENI GELANI
DARREN
B
. SMITH
Exp. 12/31/26PLAN CHECK CORRECTIONS04/01/251

CHILLED WATER SYSTEM P&ID
M-603
"' ~ ,,
e -C
0 ~ co
I
~
CX)
0 ~
~
"' ~ .s:: u m
"' §,
0 < u
"' ~
ij
~ u
0 a. m
"' ~
m
.s:: u
0 I
~ ,,
C
0 -~ 0 a.
,,
0 -" w -;:
0 u
CX)
0 .,;
g
~ ,,
~
0 .s::
'.!),
"' "' ~
~
~
0 "' ~ ,,
~
0 .s::
'.!),
1ii "­I
(/)
0 ~
;;]
co
I
"' ..;
[
0 ...J
0 .s::
"' ~
·a
.s:: DIAL
Jl BEFORE
l'. YOU DIG a,
I
I
I
I
I I
I I L 7
I I \ I I
I~ \
I µ.t::::==::::1..1::::::==:::L. \ l 00
b?O 0
e

TWO WORKING

DAYS BEFORE

YOU DIG
" TOLL FREE 1-800-227-2600
:/! A PUBLIC SERVICE BY
ff. UNDERGROUND SERVICE ALERT
1 L 7
e
T I
I
I
/----,a~
~r
0 T I
I
I
I
0 0
0 0
e l
oe-------I
~ ~ ~ 1 ( ) - -_J
0 e
I
QI
0 __________ _J
I
◊
◊
Pt l
oe-------I
~o~-~, s;) __ _J
e
0 I
QI
0 __________ _J
0 ◊
0 0
T
0 T
co
co
0 0
0 ◊
0 0
l
l
0 l
◊
l
l
◊
l
=
0 0
l
l
0 0
l
l
◊ ◊
l
l
l
l
0 0
0 0
0 0
0 0
0 0
◊
◊
◊
◊
◊
◊
◊
◊
◊
◊
fSHml CITY OF CARLSBAD ~
1---+---+--------------+---+---+---+----1 ~ PUBLIC WORKS DEPARTMENT L..E_j l---+---+--------------+---+---+---+----1
1---+---+--------------+---+---+---+----t IMPRO\IEMENT PLANS FOR:
1---4-< ........ +--------------+---+---+---+----1 APPROVED: JOHN MAASHOFF RCE 61909 EXP. 9/30/25 1---+---+--------------+---+---+---+----1 PUBLIC WORKS MANAGER CITY OF CARLSBAD DATE t---=-:-=--+=,=.,,.-+--------------+---+---+---+----t DWN BY: __ DATE INITIAL >--DA_TE~I_Nlll_AL---+-_DA_TE~I_Nlll_A__,L CHKD BY: __ ENGINEER OF WORK REVISION DESCRIPTION OTHER APPROVAL CITY APPROVAL RVWD BY:

PROJECT NO. II DRAWING NO.I

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.0850% CONSTRUCTION DOCUMENTS06/21/24 -- 90% CONSTRUCTION DOCUMENTS07/23/24 --
PLAN CHECK SUBMITTAL10/02/24 --
No. 30841REM
SATTE

ETER SIG
ER
P
D
LO A
C N
F HO C
A
AL I
F C
ANR
I
O
EFO
ISS

NER ENI GELANI
DARREN
B
. SMITH
Exp. 12/31/26PLAN CHECK CORRECTIONS04/01/251
TITLE 24 DOCUMENTATION
M-701

CONDUIT CAP-OFF
MIN. 3/4"C- HOMERUN TO PANELBOARD
RACEWAY TURNED DOWN 1/2"C, 2#12 AND 1#12 GND -
TYPICAL U.N.O.

RACEWAY TURNED UP 1/2"C, 2#12 AND 1#12 GND -
TYPICAL U.N.O.

RACEWAY CONCEALED IN WALL OR CEILING 1/2"C,
2#12 AND 1#12 GND - TYPICAL U.N.O.

CONDUIT ROUTED EXPOSED

AAMPERE

AB ABOVE BACK SPLASH

ADA AMERICANS W/DISABILITIES ACT
A.F.F. ABOVE FINISHED FLOOR

AF ARC FAULT

AHU AIR HANDLING UNIT

AMP FUSE

AFG ABOVE FINISHED GRADE

AIC AMPERE INTERRUPTING CAPACITY

AL ALUMINUM

ARCH'L ARCHITECTURAL AS AMP SWITCH

ATS AUTOMATIC TRANSFER SWITCH

AWG AMERICAN WIRE GAUGE

BC BARE COPPER

BLDG BUILDING BLDG

CCONDUIT

CAB CABINET

CAT CATALOG/CATEGORY

CB CIRCUIT BREAKER

CKT CIRCUIT

CLG CEILING

CO CONDUIT ONLY

CC COMM COMMUNICATION

CU COPPER

CTEP CALIFORNIA TYPE EVALUATION

PROGRAM

DEMO,(D) DEMOLITION/DEMOLISH
DISC. DISCONNECT

DN DOWN

DWG DRAWING

EA EACH

EF EXHAUST FAN

EG EQUIPMENT GROUND
ELEC. ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

EQUIP EQUIPMENT
(E) EXISTING TO REMAIN

EVCS ELECTRICAL VEHICLE

CHARGING STATION

FACP FIRE ALARM CONTROL PANEL

FBO FURNISHED BY OTHERS

FF FINISHED FLOOR

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT (STEEL)

FT FEET OR FOOT

GFA GROUND FAULT ALARM

GFCI GROUND FAULT CIRCUIT

INTERRUPTER

GND GROUND

HP HORSEPOWER

HVAC HEATING, VENTILATING &

AIR CONDITIONING

IBC INTERNATIONAL BUILDING CODE

IMC INTERMEDIATE METAL CONDUIT

IN INCH(ES)

IRC INTERNATIONAL RESIDENTIAL
CODE

ISC SHORT CIRCUIT AMPERES

JB, J-BOX JUNCTION BOX
KCMIL&

MCM THOUSAND CIRCULAR MILS

KVA KILOVOLT AMPERE

KW KILOWATT

LCP LIGHTING CONTROL PANEL

LRA LOCK RUNNING AMPS

LOTO LOCK OUT TAG OUT

LTG LIGHTING
MAX. MAXIMUM

MCA MAXIMUM CIRCUIT AMP

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER
MECH. MECHANICAL
MIN. MINIMUM

MLO MAIN LUGS ONLY

MTD MOUNTED

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NECA NATIONAL ELECTRICAL

CONTRACTOR'S

ASSOCIATION

NEMA NATIONAL ELECTRICAL

MANUFACTURERS

ASSOCIATION

NEUT NEUTRAL

NFC NATIONAL FIRE CODE

NF NON-FUSIBLE

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

OCPD OVER CURRENT PROTECTION
DEVICE
PPOLE

PH PHASE

PNL PANEL

PV PHOTOVOLTAIC

PVC POLYVINYL CHLORIDE

PWR POWER

QTY QUANTITY
(R) RELOCATE

RECEP RECEPTACLE

REQ'D REQUIRED

RGS RIGID GALVANIZED STEEL

RSC RIGID STEEL CONDUIT

SCHED SCHEDULE

SECT SECTION

SP SINGLE POLE

SN SOLID NEUTRAL

SPEC SPECIFICATION

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCH GEAR

SYS SYSTEM

TEMP TEMPORARY

TELE TELEPHONE

T-STAT THERMOSTAT

TTB TELEPHONE TERMINAL

BACKBOARD

TTC TELEPHONE TERMINAL

CABINET
TYP. TYPICAL

UBC UNIFORM BUILDING CODE

UL UNDERWRITERS LABORATORY
U.N.O. UNLESS NOTED OTHERWISE

VVOLT OR VOLTAGE

VA VOLT AMPERE

VD VOLTAGE DROP

VFD VARIABLE FREQUENCY DRIVE

VP VAPOR PROOF

W WATT, WIRE
WP WEATHERPROOF, NEMA 3R

XFMR TRANSFORMER
- A -
- B -
- C -
- D -
- E -
- F -
- G -
- H -
- I -
- J -
- K -
- L -
- M -
- N -
- O -
- P -
- Q -
- R -
- S -
- T -
- U -
- V -
- W -
- X -
WIRING

MISCELLANEOUS

SIGNAL POWER
2022 CALIFORNIA ELECTRICAL CODE (CEC)
PART 3, TITLE 24, CALIFORNIA CODE OF REGULATIONS (CCR)
2020 NATIONAL ELECTRICAL CODE (NEC) NFPA 70
2022 CALIFORNIA ADMINISTRATIVE CODE (CAC)
PART 1, TITLE 24, CALIFORNIA CODE OF REGULATIONS (CCR) 2022 CALIFORNIA BUILDING CODE (CBC)
PART 2, TITLE 24, CALIFORNIA CODE OF REGULATIONS (CCR)
2022 CALIFORNIA MECHANICAL CODE (CMC)
PART 4, TITLE 24, CALIFORNIA CODE OF REGULATIONS (CCR)
2022 CALIFORNIA PLUMBING CODE (CPC)
PART 5, TITLE 24, CALIFORNIA CODE OF REGULATIONS (CCR)
2022 CALIFORNIA ENERGY CODE (CEC)
PART 6, TITLE 24, CALIFORNIA CODE OF REGULATIONS (CCR)
2022 CALIFORNIA FIRE CODE (CFC)
PART 9, TITLE 24, CALIFORNIA CODE OF REGULATIONS (CCR)
2022 CALIFORNIA GREEN BUILDING CODE (CGBC)
PART 11, TITLE 24, CALIFORNIA CODE OF REGULATIONS (CCR)

APPLICABLE CODES

REVISION SYMBOL

FEEDER SCHEDULED EQUIPMENT

KEYNOTE PLAN SYMBOL
#
SHEET
UNIT
#
1 MECHANICAL EQUIPMENT TAG

DIAGRAM TAG
1 1

CONDUIT ROUTED UNDER FLOOR/UNDERGROUND

DEMOLITION KEYNOTE PLAN SYMBOL

ELECTRICAL SYMBOL LISTSTANDARD ABBREVIATIONS

PUSH BUTTON CONTROL STATION

DUAL CHANNEL RACEWAY WITH COVER, DUPLEX AND

DATA RECEPTACLES AS NOTED

JUNCTION BOX

JUNCTION BOX - FLUSH FLOOR MOUNT

AUTOMATIC TRANSFER SWITCH

NON-FUSED DISCONNECT SWITCH
(WITH SEALTITE RACEWAY CONNECTION

FUSED DISCONNECT SWITCH

MOTOR CONTROLLER OR STARTER

METER SERVICE PEDESTAL

SWITCHBOARD OR DISTRIBUTION BOARD

LIGHTING AND APPLIANCE PANELBOARD - FLUSH MOUNT

LIGHTING AND APPLIANCE PANELBOARD - SURFACE MOUNT

PULLBOX - EXTERIOR OR INTERIOR AS INDICATED

POWER FLOOR OUTLET WITH DEVICE AS INDICATED
DUPLEX RECEPTACLE NEMA 5-20R, 15A, 125V -

FLUSH MOUNT CEILING
DEDICATED DUPLEX RECEPTACLE, NEMA 5-20R, 20A, 125V
RATED MOUNT CENTER OF OUTLET AT 18" AFF UON
DUPLEX RECEPTACLE / HALF-SWITCHED "C" INDICATES

CONTROLLED VIA MOTION SENSOR/TIME CLOCK, MOUNT
CENTER OF OUTLET AT 18" AFF UON
QUADPLEX RECEPTACLE, NEMA 5-15R, 20A, 125V, MOUNT
CENTER OF OUTLET AT 18" AFF UON
DUPLEX RECEPTACLE, NEMA 5-15R, 20A, 125V RATED,
MOUNT CENTER OF OUTLET AT 18" AFF UON
SINGLE RECEPTACLE, NEMA 5-15R, 20A, 125V, MOUNT
CENTER OF OUTLET AT 18" AFF UON
PB
J
J
ATS
F

JJUNCTION BOX - WALL MOUNT
SPECIAL RECEPTACLE 480V RATED w/GROUND AS NOTED
DUPLEX RECEPTACLE NEMA 5-20R, 15A, 125V GFCI TYPE,
MOUNTED 6" ABOVE COUNTER SPLASH
C

VARIABLE FREQUENCY DRIVE
VFD
COMBINATION USB/DUPLEX NEMA 5-15R, 125V, MOUNTED
18" AFF UON
DUPLEX RECEPTACLE NEMA 5-15R 125V RATED MOUNTED 6"

ABOVE COUNTER SPLASH
MSINGLE MANUAL MOTOR RATED SWITCH (1HP)
COMBINATION USB/DUPLEX NEMA 5-15R, 125V, MOUNTED
6" ABOVE COUNTER
DEDICATED DUPLEX RECEPTACLE, NEMA 5-20R, 20A, 125V,
GFCI TYPE, RATED MOUNT CENTER OF OUTLET AT 18" AFF
UON G
DUPLEX RECEPTACLE NEMA 5-20R, 15A, 125V -

FLUSH MOUNT CEILING

COMBINATION POWER / DATA FLOOR OUTLET NOTED

SUITABLE FOR CONCRETE FLOORS NOTED SUITABLE FOR
TYPE 5 CONSTRUCTION

UTILITY COMPANY SERVICE CABLE

TERMINATION

CIRCUIT BREAKER
FUSE

FUSED DISCONNECT SWITCH
SWITCH

TRANSIENT VOLTAGE SURGE SUPPRESSOR

CURRENT TRANSFORMER (CT)

POTENTIAL TRANSFORMER

GROUNDING ELECTRODE

UTILITY COMPANY POWER METER
MOTOR (# INDICATED HP)

GENERATOR MOTOR

GROUND FAULT PROTECTION DEVICE

TRANSFER SWITCH ATS OR MTS AND

NUMBER OF POLES AS NOTED

ENCLOSED CIRCUIT BREAKER
RELAY

CONTACTOR (NORMALLY OPEN)

CONTACTOR (NORMALLY CLOSED)

CONTROL SWITCH

PUSH BUTTON
R
N EM
L
M
G
TVSS
#

MCUSTOMER OWNED POWER METER
TAC-1
GFPD
THERMOSTAT OUTLET AT +54" (HVAC

UNIT DESIGNATION)
F05

1. SYMBOLS ARE NOT NECESSARILY USED IN THIS PROJECT.

2. IT IS THE INTENT OF THESE DRAWINGS AND SPECIFICATIONS TO ESTABLISH A STANDARD OF QUALITY. THE ENGINEER RESERVES THE RIGHT TO ALLOW OTHER METHODS AND MATERIALS NOT REFLECTED HEREIN. THE CONTRACTOR

SHALL BE RESPONSIBLE TO REQUEST THE ENGINEER WAIVE THE STANDARDS

TO ALLOW ALTERNATE MEANS AND METHODS PRIOR TO BEGINNING THE PROJECT. CONTRACT DOCUMENT REVISIONS TO ACCOMMODATE INSTALLED

CONDITIONS, WITHOUT PRIOR APPROVAL, WILL RESULT IN ADDITIONAL DESIGN CHARGES TO THE CONTRACTOR.

3. ELECTRICAL WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER IN

ACCORDANCE WITH THE NECA INSTALLATION STANDARDS TO THE
SATISFACTION OF THE ARCHITECT AND ENGINEER.

4. WORK, MATERIALS AND EQUIPMENT SHALL CONFORM TO THE CURRENTLY

ACCEPTED EDITION OF APPLICABLE NATIONAL, STATE AND CITY CODES AND ORDINANCES.

5. ELECTRICAL SYSTEM COMPONENTS SHALL BE LISTED OR LABELED BY UL OR

OTHER RECOGNIZED TESTING FACILITY AS ALLOWED BY AUTHORITY HAVING JURISDICTION.

6. WHERE AN APPARENT DISCREPANCY EXISTS BETWEEN THE REQUIREMENTS

OF THE GENERAL NOTES AND INFORMATION PORTRAYED IN THE ELECTRICAL

DRAWINGS, THE CONTRACTOR SHALL INCLUDE IN HIS BID THE COST OF THE GREATER QUALITY OR QUANTITY.

7. CONTRACTOR SHALL VISIT JOB SITE PRIOR TO BID AND VERIFY EXISTING CONDITIONS. CONTRACTOR SHALL INCLUDE IN BASE BID COSTS REQUIRED FOR PERMITS AND INSPECTIONS.

8. CONTRACTOR SHALL VERIFY, WITH OWNER'S REPRESENTATIVE PRIOR TO

SUBMITTING BID, ALLOWABLE WORKING HOURS, EMPLOYEE PARKING AREAS,

MATERIAL DELIVERY, STORAGE REQUIREMENTS, DEMOLITION AND REMOVAL OF CONSTRUCTION DEBRIS, AS WELL AS DAILY CLEAN UP REQUIREMENTS.

INCLUDE COSTS IN BID FOR DUST BARRIERS, DUMPSTERS ETC. AS REQUIRED FOR THE DURATION OF THE PROJECT. PERFORM WORK AS DIRECTED BY OWNER'S REPRESENTATIVE AND ARCHITECT.

9. ELECTRICAL SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. IF TESTS

SHOW THAT WORK IS DEFECTIVE, CONTRACTOR SHALL MAKE NECESSARY CORRECTIONS.

10. CONTRACTOR SHALL GUARANTEE WORK AGAINST DEFECTS IN MATERIALS AND

WORKMANSHIP WHICH MAY OCCUR UNDER NORMAL USE FOR A PERIOD OF ONE YEAR AFTER OWNER'S ACCEPTANCE. DEFECTS SHALL BE PROMPTLY CORRECTED BY CONTRACTOR WITHOUT ADDITIONAL CHARGE TO OWNER.

11. DO NOT SCALE ELECTRICAL DRAWINGS. VERIFY EXACT LOCATION OF ALL

DEVICES, JUNCTION BOXES, LIGHTING FIXTURES, WITH ARCHITECTURAL AND INTERIOR DESIGN DRAWINGS PRIOR TO INSTALLATION. CONTRACTOR SHALL

VERIFY THE EXACT LOCATION OF MECHANICAL EQUIPMENT AND OTHER EQUIPMENT REQUIRING ELECTRICAL CONNECTION PRIOR TO ROUGH-IN. EVERY

OUTLET HEIGHT SHALL BE VERIFIED ON EACH WALL WITH THE INTERIOR PLANNING AND DESIGN DRAWINGS. COORDINATE WITH CABINET SHOP

DRAWINGS TO ENSURE PROPER HEIGHT AND LOCATION WITH RESPECT TO MILLWORK, EQUIPMENT.

12. RACEWAY SYSTEMS ARE SHOWN DIAGRAMMATICALLY. ACTUAL LOCATION AND ROUTING SHALL BE DETERMINED BY CONTRACTOR TO SUIT FIELD CONDITIONS.

13. MINIMUM RACEWAY SIZE SHALL BE 3/4"". MINIMUM HOMERUN SIZE SHALL BE 3/4". MINIMUM CONDUCTOR SIZE SHALL BE #12 AWG U.N.O. TYPICAL. POWER

RELATED CONDUITS SHALL HAVE A CODE SIZE GROUND WIRE INSTALLED IN EACH RUN.

14. CONTRACTOR SHALL PROVIDE RACEWAY SYSTEMS INDICATED ON THE DRAWING PER CEC REQUIREMENTS AND GENERAL NOTES. ANY DEVIATION

FROM THE WIRING METHODS INDICATED SHALL BE ALLOWED ONLY BY

SPECIFIC WRITTEN APPROVAL FROM EITHER THE ARCHITECT, ENGINEER OR OWNER. CONTRACTOR'S BID SHALL INCLUDE COSTS FOR RACEWAY SYSTEMS

AS SPECIFIED UNLESS SPECIFIC WRITTEN APPROVAL FOR AN ALTERNATIVE

WIRING METHOD IS OBTAINED FROM EITHER THE ARCHITECT, ENGINEER OR

OWNER AND IS SUBMITTED AS PART OF CONTRACTOR'S FORMAL BID PROPOSAL.

15. PRIOR TO INSTALLATION, CONTRACTOR SHALL REVIEW THE COMPLETE SET OF CONSTRUCTION DOCUMENTS FOR CONFLICTS WITH OTHER TRADES.

CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WORK WITH OTHER TRADES TO AVOID CONFLICT DURING INSTALLATION. CONTRACTOR SHALL

MAKE MINOR ADJUSTMENTS IN EQUIPMENT LOCATION AND ROUTING AS NECESSARY.

16. CONTRACTOR SHALL BE RESPONSIBLE TO PROPERLY CUT AND PATCH

EXISTING CONSTRUCTION AS REQUIRED TO INSTALL NEW ELECTRICAL WORK

PATCHING SHALL BE OF THE SAME MATERIALS, WORKMANSHIP AND FINISH AS

THE EXISTING WORK AND SHALL ACCURATELY MATCH SURROUNDING WORK TO THE SATISFACTION OF THE ARCHITECT.

17. ELECTRICAL EQUIPMENT SHALL HAVE SUFFICIENT GUTTER SPACE AND LUGS TO ACCOMMODATE QUANTITY AND SIZE OF CONDUCTORS REQUIRED.

CONTRACTORS SHALL PROVIDE EQUIPMENT WITH OVERSIZED ENCLOSURES WHERE REQUIRED.

18. NEW PANELBOARDS SHALL HAVE LOCKING DOORS AND BE KEYED THE SAME U.N.O.

19. PROVIDE TYPE WRITTEN UPDATED PANEL DIRECTORY TO BE MOUNTED ON INSIDE OF PANEL DOOR COVERS. DIRECTORY SHALL REFLECT ADDITIONS OR MODIFICATIONS TO EXISTING PANELS AND SHALL REFLECT ACTUAL "AS-BUILT" CONDITIONS.

20. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS TO ARCHITECT FOR REVIEW OF THE FOLLOWING EQUIPMENT:
a. ELECTRICAL SWITCHGEAR: SWITCHBOARDS, WITH PANELS, MOTOR

CONTROL
b. OVERCURRENT DEVICES: CIRCUIT BREAKERS AND FUSES INCLUDING c. TIME/CURRENT TRIP CURVES.
d. LIGHT FIXTURES, WIRE DEVICES, CONDUIT & CONDUCTORS.
e. MOTOR DISCONNECT SWITCHES AND ASSOCIATED STARTERS.

34. EQUIPMENT ELECTRICAL TERMINATIONS TO UNDERGO A TORQUE TEST.

ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR MANUFACTURER'S

RECOMMENDED TORQUE DOCUMENTATION AND TOOLS TO PERFORM TORQUE TEST.

35. ELECTRICAL EQUIPMENT SHALL BE MOUNTED ON A 6" HIGH CONCRETE PAD.

36. ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED, OR CERTIFIED BY A

NATIONALLY RECOGNIZED TESTING LABORATORY ACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFETY HEALTH ADMINISTRATION.

37. CONTRACTOR SHALL REPAIR ANY DAMAGED IRRIGATION LINES TO MATCH EXISTING CONDITIONS. FIELD VERIFY AND COORDINATE PRIOR ANY EXCAVATION WORK.

GENERAL ELECTRICAL NOTES
E-001

GENERAL NOTES, SYMBOL LIST & SHEET
INDEX

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.0850% CONSTRUCTION DOCUMENTS06/21/24 -- 90% CONSTRUCTION DOCUMENTS07/23/24 --
PLAN CHECK SUBMITTAL10/02/24 --
PLAN CHECK CORRECTIONS04/01/251

SHEET INDEX
Sheet
NumberSheet Title
E-001GENERAL NOTES, SYMBOL LIST & SHEET INDEX
E-002SINGLE LINE DIAGRAM - DEMOLITION & NEW
E-100OVERALL ELECTRICAL SITE PLAN
E-200ENLARGED ELECTRICAL PLAN - DEMOLITION & NEW
E-300ELECTRICAL DETAILS
SPECIAL RECEPTACLE. 250V RATED WITH GROUND AS
NOTED

COMBINATION POWER / DATA FLOOR OUTLET AS

INDICATED

1. WORK INCLUDED: LABOR, MATERIAL, APPLIANCES, TOOLS, EQUIPMENT,

FACILITIES, TRANSPORTATION AND SERVICES NECESSARY AND INCIDENTAL TO

PERFORMING OPERATIONS IN CONNECTION WITH THE DEMOLITION, DISPOSAL,

TRANSPORTATION AND RECONNECTION OF EXISTING REMAINING
EQUIPMENT/DEVICES. COMPLETE AS INDICATED IN THE CONTRACT DOCUMENTS AS SPECIFIED HEREIN.

2. THE FOLLOWING IS INTENDED TO COVER THE COMPLETE DEMOLITION,

DISPOSAL, TRANSPORTATION AND RECONNECTION OF EXISTING ELECTRICAL EQUIPMENT. THE OMISSION OF EXPRESSED REFERENCE TO ANY ITEM OF

LABOR OR MATERIAL FOR THE PROPER EXECUTION OF THE WORK IN

ACCORDANCE WITH PRESENT PRACTICE OF THE TRADE SHALL NOT RELIEVE THE CONTRACTOR FROM PROVIDING SUCH ADDITIONAL LABOR AND MATERIALS.

3. REFER TO THE CONTRACT DOCUMENTS FOR ADDITIONAL DEMOLITION REQUIREMENTS WHICH AFFECT THE PROPER EXECUTION OF THIS WORK.

DIAGRAMS AND SYMBOLS SHOWING ELECTRICAL CONNECTIONS ARE DIAGRAMMATIC ONLY. WIRING DIAGRAMS DO NOT NECESSARILY SHOW THE EXACT PHYSICAL ARRANGEMENT OF THE EQUIPMENT.

4. IT IS THE CONTRACTOR'S RESPONSIBILITY TO VISIT THE SITE AND BECOME

THOROUGHLY FAMILIAR WITH FEATURES OF THE BUILDING AND SITE WHICH MAY AFFECT THE PROPER PERFORMANCE OF THIS WORK.

5. PORTIONS OF THESE PLANS HAVE BEEN DERIVED FROM INFORMATION TAKEN FROM ORIGINAL ELECTRICAL PLANS. THE INTENT OF THE DRAWINGS AND

SPECIFICATIONS IS TO PROVIDE FOR THE REMOVAL AND DISPOSAL OF

ELECTRICAL EQUIPMENT, LIGHTING FIXTURES, DEVICES, OUTLET BOXES,

CONDUIT, WIRING AS DEFINED HEREIN AND AS INDICATED ELSEWHERE IN THE CONTRACT DOCUMENTS.

6. IT IS UNDERSTOOD AND AGREED THAT THIS CONTRACT DOES NOT

CONTEMPLATE THE HANDLING OF ASBESTOS, PCB OR ANY HAZARDOUS WASTE MATERIAL. IF ASBESTOS, PCB OR ANY HAZARDOUS WASTE MATERIAL IS ENCOUNTERED, NOTIFY THE ARCHITECT IMMEDIATELY. DO NOT DISTURB, HANDLE OR ATTEMPT TO REMOVE.

7. THE SCOPE OF DEMOLITION WORK SHALL INCLUDE, BUT IS NOT LIMITED TO THE FOLLOWING:
a. SUBMIT PROPOSED OUTAGE SCHEDULE. PROVIDE A SEQUENCE OF

DEMOLITION TO INSURE THE UNINTERRUPTED USE OF OCCUPIED

PORTIONS OF THE FACILITY WHICH ARE TO REMAIN OPERATIONAL DURING THE CONTRACT PERIOD.
b. SYSTEM OUTAGES SHALL BE PERMITTED ONLY AT TIMES APPROVED BY OWNER, IN WRITING. WORK WHICH COULD RESULT IN A ACCIDENTAL

OUTAGE (BEYOND BRANCH CIRCUITS) SHALL BE PERFORMED WITH THE OWNER'S MAINTENANCE PERSONNEL ADVISED OF SUCH WORK.
c. COORDINATE WITH THE OWNER AND DESIGNATE A PORTION OF THE FACILITY FOR SAFELY STORING REMOVED AND SALVAGED MATERIALS. d. REMOVED MATERIALS AND EQUIPMENT WHICH IN THE OPINION OF THE

OWNER/ARCHITECT ARE SALVAGEABLE, SHALL REMAIN THE PROPERTY OF THE OWNER. DELIVER SUCH SALVAGED MATERIALS AND EQUIPMENT ON

PREMISES AS DIRECTED, NEATLY PILE OR STORE THEM AND PROTECT FROM DAMAGE. DO NOT REUSE MATERIALS AND EQUIPMENT UNLESS SPECIFICALLY INDICATED ON PLANS OR SPECIFIED. REMOVE FROM

PREMISES AND DISPOSE OF MATERIALS CONSIDERED BY THE
OWNER/ARCHITECT TO BE SCRAP.
e. PERFORM CUTTING AND PATCHING OF THE CONSTRUCTION WORK WHICH

MAY BE REQUIRED FOR THE PROPER DEMOLITION OF THE ELECTRICAL WORK. PATCHING SHALL BE OF THE SAME MATERIAL, THICKNESS,

WORKMANSHIP AND FINISH AS EXISTING AND ACCURATELY MATCH SURROUNDING WORK TO THE SATISFACTION OF THE ARCHITECT. CUTTING

OF STRUCTURAL MEMBERS SHALL NOT BE DONE WITHOUT FIRST

OBTAINING APPROVAL FROM THE ARCHITECT AND/OR STRUCTURAL ENGINEER OF RECORD.
f. PATCHING OF OPENINGS IN RATED PARTITIONS, BARRIERS, FLOORS,

CEILINGS SHALL BE EXECUTED USING UL AND NFPA FIRE STOP MATERIAL EQUAL TO THE FIRE RATINGS OF THE PENETRATED SURFACE.
g. WHERE MATERIALS AND EQUIPMENT HAVE BEEN REMOVED AND NOT

REPLACED THE EXPOSED SURFACE SHALL BE PAINTED TO MATCH
SURROUNDING SURFACE COLOR.
h. AS INDICATED, DISCONNECT AND REMOVE EXISTING ELECTRICAL

EQUIPMENT, DISCONNECT SWITCHES, RECEPTACLES, MOUNTING

HARDWARE AND ASSOCIATED RACEWAYS, CONDUCTORS AND OUTLET BOXES. WHERE OUTLET BOXES ARE FLUSH AND CONDUITS ARE

CONCEALED IN EXISTING REMAINING WALLS, REMOVE WIRING AND ABANDON CONDUIT IN PLACE.
i. PANEL BATTERIES ARE FUNCTIONAL AND FULLY CHARGED

8. THE CONTRACTOR SHALL FIELD VERIFY EXISTING EQUIPMENT, DEVICES, AND/OR CIRCUITS THAT ARE REMAINING. CIRCUITS SHALL BE RECONNECTED TO

NEW OR EXISTING POWER DISTRIBUTION EQUIPMENT AND FUNCTION IN THE MANNER THEY WERE ORIGINALLY DESIGNED. PROVIDE ADDITIONAL EQUIPMENT,

DEVICES, OUTLET BOXES, CONDUIT, WIRING AS REQUIRED TO RESTORE CONTINUITY TO THESE CIRCUITS.

9. WHERE FIXTURES, EQUIPMENT, DEVICES ARE SPECIFIED BY THE CONTRACT

DOCUMENTS FOR REMOVAL, THE CONTRACTOR SHALL REMOVE CIRCUIT

CONDUCTORS/CABLING BACK TO THE NEAREST REMAINING JUNCTION BOX AND/OR POINT OF TERMINATION.

10. RELOCATE EXISTING CONDUITS AND/OR CONDUCTORS/CABLING ROUTING

THROUGH AREAS WHERE NEW PLENUMS AND/OR ROOF OPENINGS ARE SPECIFIED.

11. PROVIDE ADDITIONAL CONDUIT, CONDUCTORS, CABLING, OUTLET BOXES AS REQUIRED FOR THE RELOCATION OF ELECTRICAL APPARATUS.

12. RELOCATION AND/OR REMOVAL OF EXISTING EQUIPMENT, DEVICES, OUTLET

BOXES, CONDUIT, WIRING MAY AFFECT THE OPERATION OF EXISTING, REMAINING ELECTRICAL EQUIPMENT/DEVICES. THE CONTRACTOR SHALL

PROVIDE ADDITIONAL MATERIALS AS REQUIRED TO MAINTAIN AND/OR RESTORE CONTINUITY OF SERVICE TO EXISTING, REMAINING ELECTRICAL/DEVICES.

13. PROVIDE NECESSARY DEMOLITION TO REMOVE EXISTING UNUSED RACEWAYS,

CONDUCTORS, CABLING, OUTLET BOXES, RECEPTACLES, SWITCHES, EQUIPMENT.

14. WHERE IT IS NOT FEASIBLE TO REMOVE UNUSED FLUSH MOUNTED OUTLET

BOXES AND CONCEALED RACEWAYS IN EXISTING, REMAINING WALLS AND/OR

CEILINGS REMOVE WIRING AND PROVIDE BLANK COVER PLATES OVER OUTLET BOXES.

15. COVER UNUSED AND/OR ABANDONED OUTLETS WITH BLANK COVER PLATES.

16. SEAL ABANDONED FLOOR PENETRATIONS IN A MANNER ACCEPTABLE TO THE ARCHITECT.

17. DISCONNECT ABANDONED CIRCUITS AT EXISTING PANELBOARDS AND REMOVE WIRE TO LAST REMAINING DEVICE. LABEL ABANDONED CIRCUIT BREAKERS "SPARE".

18. PROVIDE NEW TYPEWRITTEN DIRECTORIES FOR RE-USED PANELBOARDS THAT ARE ALTERED AS PART OF THE DEMOLITION.

19. EXISTING CIRCUITS THAT ARE REMOVED AND ARE NOT RE-USED SHALL BE IDENTIFIED ON THE PANEL DIRECTORY AS 'SPARE'.

20. THE CONTRACTOR SHALL PROVIDE CIRCUIT NUMBERS AND LOADS FOR ALL EXISTING REMAINING EQUIPMENT. PRIOR TO RECONNECTION, REASSIGN CIRCUITS AS REQUIRED. TO BALANCE LOADS EVENLY ACROSS PHASES WHEN RECONNECTED. PROVIDE COMPLETE 'AS-BUILT' DRAWINGS.

DEMOLITION GENERAL NOTES
AL
BK
SC

SCOPE OF WORK

PROJECT WILL REPLACE AN EXISTING MOTOR CONTROL CENTER WITH A NEW POWER PANEL. EXISTING FEEDER WILL BE SPLICED IN A NEW PULL AND AND EXTENDED TO NEW ELECTRICAL EQUIPMENT.

PROVIDE UPDATED CIRCUITRY FOR TWO NEW 50 TON OUTDOOR CHILLERS.

INTERCEPT EXISTING CHILLER PUMPS AND EXTEND TO NEW POWER PANEL.

UPDATE BUILDING GROUNDING ELECTRODE SYSTEM TO ACCOMMODATED NEW POWER PANEL.

REPLACE CHILLER OUTDOOR RECEPTACLE WITH A NEW GROUND FAULT CIRCUIT INTERRUPTING TYPE.
12 DIAL
BEFORE

YOU DIG

TWO WORKING

DAYS BEFORE

YOU DIG
TOLL FREE 1-800-227-2600

A PUBLIC SERVICE BY

UNDERGROUND SERVICE ALERT
-e
=@
fl
0 f()
[Q]
■ ■ ■ ■ I
□
-----
~
□
□
II""]
H_o]
QJ
[2<J
-
-----4'o--
----l I<~
---=--
__c-0 0---
I
-FA-
0_)
rr
_L
0 ;(Ji
□
;(Ji
I
M
-H-
-+-
•
•
•
•
•
•
•
•
•
_L
0 1-"'d
□
e
8 0
0 6
CJ
DATE INlllAL

ENGINEER OF WORK

DATE INITIAL DATE INITIAL

REVISION DESCRIPTION OTHER APPROVAL CITY APPROVAL
APPROVED: JOHN MAASHOFF RCE 61909 EXP. 9/30/25

PUBLIC WORKS MANAGER
DWN BY: ---I 1
CHKD BY: ---I
RVWD BY: _

CITY OF CARLSBAD
PROJECT NO.

DATE
II DRAWING NO.I

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.0850% CONSTRUCTION DOCUMENTS06/21/24 -- 90% CONSTRUCTION DOCUMENTS07/23/24 --
PLAN CHECK SUBMITTAL10/02/24 --
PLAN CHECK CORRECTIONS04/01/251

DEMOLITION KEYNOTES

SINGLE LINE DIAGRAM NOTES

1. OVER-CURRENT DEVICES IN AN INDIVIDUAL PIECE OF EQUIPMENT SHALL HAVE AN A.I.C RATING EQUAL TO THE OVERALL RATING OF THE EQUIPMENT. SERIES RATING IS PROHIBITED.

2. TERMINATIONS AND ENCLOSURES SHALL BE RATED FOR USE WITH 75 DEGREE CELSIUS CONDUCTORS.

3. SERVICE ENTRANCE EQUIPMENT METERED SWITCHBOARDS SHALL BE

PROVIDED WITH A MAIN OVER-CURRENT DEVICE AND CONTINUOUS BUSSING IN ACCORDANCE WITH SDGE STANDARDS.

4. MAIN, FEEDER OR BRANCH CIRCUIT BREAKERS SHALL BE 100% RATED.

5. BUSSING:
a. BUSSING SHALL BE TINNED COPPER CLAD CONSTRUCTION.

HORIZONTAL AND VERTICAL BUSSING SHALL BE FULL CAPACITY IN SWITCHBOARD SECTIONS.
b. HORIZONTAL AND VERTICAL BUSSING SHALL BE FULL LENGTH.

BUSSING SHALL HAVE A MINIMUM WITHSTAND RATING EQUAL TO THE

AVAILABLE FAULT CURRENT INDICATED, BUT IN NO CASE SHALL THE RATING BE LESS THAN 65,000 AMPS, SYMMETRICAL.

7. UNDERGROUND AND ABOVE GROUND CONDUCTORS IN EXPOSED CONDUIT SHALL BE THWN-2, TEMPERATURE RATING OF 90 DEGREES.

8. PROVIDE EXOTHERMIC WELD CONNECTIONS FOR SERVICE GROUND ELECTRODE CONNECTION IN ACCORDANCE WITH PUBLIC WORK STANDARDS.

9. CONTRACTOR SHALL INSTALL SERVICE ENTRANCE CONDUITS IN ACCORDANCE WITH UTILITY COMPANY APPROVED PLANS.
(E) UTILITY
XFMR #1
M
(E) COMB. PULL

METER SECTION
AV
ASVS
1600A
3P
(E)
350A
3P
(E)
(E) MAIN SERVICE
BOARD "MSDA"
1600A, 480/277V,
3Ø, 4W, 30KAIC
(D)
(D) MCC
600A, 480V, 3Ø, 3W
(D)

CHILLER
F (D)
E-002

SINGLE LINE DIAGRAM - DEMOLITION & NEW
1 NO SCALE PARTIAL SINGLE LINE DIAGRAM - DEMOLITION
60A
3P
(E)
100A
3P
(E)
400A
3P
(E)
50A
3P
(E)
175A
3P
(E)
50A
3P
(E)
2 NO SCALE PARTIAL SINGLE LINE DIAGRAM - NEW
(D)(D)
(E) SDGE

PAD MOUNTED

TRANSFORMER
M
(E) SDGE WALL

MOUNTED

METER SECTION
AV
ASVS
1600A
3P
(E)
350A
3P
(E)
(E) MAIN SWITCHBOARD "MSDA"
1600A, 480/277V, 3Ø, 4W, 30KAIC
60A
3P
(E)
100A
3P
(E)
400A
3P
(E)
50A
3P
(E)
175A
3P
(E)
50A
3P
(E)

TO (E) LOAD
(E)
CHWP-1
(E)
HHWP-2
F (N)

TO (E) LOADTO (E) LOADTO (E) LOADTO (E) LOAD TO (E) LOADTO (E) LOADTO (E) LOADTO (E) LOADTO (E) LOADREFER TO 2/E-002
(D)
(D) (D)
15A
3P
(N) 15A
3P
(N)
200A
3P
(N)
(N) (N) (N)
F06 F05 F04
(N)
(N)
(N)
F (N)
200A
3P
(N)
(N)
F03
1 E-300
400A BUS
(N) POWER PANEL 'PP'
400A, 480V, 3Ø, 3W, 30KAIC
F02
(N) PULL BOX 'PP'
NEMA 1 ENCLOSURE,

SCREW COVER TYPE
30" X 30" X 8"
(FEEDER SPLICE)

SCOPE OF WORK
4 E-300
400A
3P
(N)
MCB
G

REMOVE FEEDER AND RACEWAY BACK TO NEW JUNCTION/PULL BOX AND SAFE OFF. REFER TO REMODEL SLD FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
1 1
(D)
AL
BK
SC
CH
1A
(N)CH
1B
3 E-300
F (N) F (N) 200AS
175AF
3P
200AS
175AF
3PVFDVFD(E) (E)

VFDVFD(E) (E)
30AS
15AF
3P
30AS
15AF
3P
PB (D)
(E)
CHWP-1
(E)
HHWP-2
(E) 3 1/2" C. WITH (3)
#500 MCM & (1) #2 GND.F01
(E) XFMR ETB
120/208V~277/480V
9KVA
PANEL
EPB
(E)
(E)
PANEL
EL1A
(E)
(E)
175A
3P
(E)150A
3P
(E)
(E)
(E)
LOAD
60A
3P
(E)
(E)
LOAD
70A
3P
(E)
(E)
LOAD
N EM
L
(E)(E)(E)
(E)
(E)
400A
3P
(E)
450A
3P
(E)
(E)
G
(E)
30A
3P
(E)
(E) DISTRIBUTION SWITCHBOARD "EDBA"
400A, 480/277V, 3Ø, 4W
(E) ATS1 600A,
4P, 480V, 3Ø
(E) 400A BUS
(E)
(E) 300KW GENERATOR
277/480V, 3Ø, 4W
(E) DISTRIBUTION SWITCHBOARD "EDBB"
600A, 480/277V, 3Ø, 4W
(E) 600A BUS

HACR HACR HACR HACR
(E)TO
ATS#2
(1))#6 THWN-3/4"C.
(E)GROUND BAR
(E) UFER
108.8 MCA 108.8 MCA
13 A104
5 A103
1 A303
1 (E)
A102
4 A102
3 50'-0"
20'-0"
20'-0"
150'-0"
R15'-0"
R15'-0"
A102
1 A102
2 (E)MAIN SWITCHBOARD 'MSDA'
LOCATED IN MAIN ELEC. ROOM
(E)GEN SET
(E)POLICE & FIRE SAFETY

BUILDING
(E)
F01 (E)

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.0850% CONSTRUCTION DOCUMENTS06/21/24 -- 90% CONSTRUCTION DOCUMENTS07/23/24 --
PLAN CHECK SUBMITTAL10/02/24 --
PLAN CHECK CORRECTIONS04/01/251

GENERAL NOTES
1 1" = 30'-0" OVERALL ELECTRICAL SITE PLAN
E-100

OVERALL ELECTRICAL SITE PLAN
TRUE
NORTH
N
1 E-200
2 E-200
AL
BK
SC

1. CONTRACTOR SHALL COORDINATE ALL ELECTRICAL OUTAGES TWO WEEKS PRIOR TO DE-ENERGIZING THE ELECTRICAL SYSTEM.

2. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING PORTABLE TEMPORARY POWER TO SUSTAIN BUILDING OPERATIONS. FIELD
COORDINATE STAGING REQUIRED EQUIPMENT AND POWER OUTAGES.

3. THE EXISTING UNDERGROUND ELECTRICAL CONDUIT AND FEEDER SHALL REMAIN AND PROTECTED IN PLACE.
14 DIAL
BEFORE

YOU DIG

TWO WORKING

DAYS BEFORE

YOU DIG
TOLL FREE 1-800-227-2600

A PUBLIC SERVICE BY

UNDERGROUND SERVICE ALERT
0 +
D
□
~
0 ID
rnrnrn
D
'
□
-. '/ {· -'
ofESS;
'i,\\ M. C
--z. "' No. E22808 rn
~ m
cP
l~=~==t=============~==f=~==t==l ~I SH~EE~T I ~C~IT~Y=O~F~CA~R~LS~B~A=D ~I ~I f-PUBLIC WORKS DEPARTMENT 2
lt.lPROVEMENT PLANS FOR:

APPROVED: JOHN MAASHOFF RCE 61909 EXP. 9/30/25

PUBLIC WORKS MANAGER CITY OF CARLSBAD DATE

DATE INITIAL

ENGINEER OF WORK REVISION DESCRIPTION

DATE INITIAL DATE INITIAL
DWN BY:

CHKD BY:

RVWD BY:

PROJECT NO.

OlHER APPROVAL CITY APPROVAL
II DRA\\1NG NO.I
TWP
(E) OLD GEN. SET

T (E) XFMR 'ETB'
(E)
PANEL
'EPB'
(D) CHILLER

DISCONNECT
SWITCH
T
(D) 1KVA
480-208/120V
CP
(D)
(D)
(E) METER
VFD
VFD
VFD
VFD
(E) (E)
(D) MCC
PB
(D)
J
(E)
1 (D)
(D)
2 (E)
3 (E) TEMP.

POWER
DISC. SW.
(E) TEMP.

POWER

PULL BOX

INCOMING
FROM
'MSDA'
(E) (E)
(E)
(E)
(D)
(E)

GENERATOR
ROOM
(E) BOILER
ROOM
(E) TRASH
(E) CHILLER
YARD
(E) GENERATOR
SET
4 6
E-200
TYP5
E-200
4 E-200
(D) PULLBOX
(E)
(E)
(E)
(E)
(E)
(E)
PANEL
'EPB'
(E) BOILER 'B-1'
SM
(E) GROUND ROD
(E)

ELECTRICAL

TRANSFORMER
(E) IRRIGATION

CONTROLLER
TWP
(E) OLD GEN. SET
T
(E)
PANEL
'EPB'
VFD
VFD
WP
(N)
CP
(E) IRRIGATION

CONTROLLER
(E) METER
VFD
VFD
(E)
(E)
(N) POWER PANEL 'PP'

INCOMING
FROM
'MSDA'
F01
1 CP CP
J
F05
F06
(E) TEMP.

POWER

PULL BOX
(E) TEMP.

POWER
DISC. SW.
1 E-300
2 E-300
CH
1B
CH
1A
(E)

ELECTRICAL

TRANSFORMER
(E)

GENERATOR
ROOM
(E) BOILER
ROOM
(E) TRASH
(E)

CHILLER
YARD
(E)

GENERATOR
SET
3 E-200
(N) PULL BOX
'PP'30x30x8"D

PULL BOX
1 E-300
F
F
F F
F03
F04
J
SM
(E)
F02
(N)
(E)
(E)
(E)
(E)
(N) (N)
J
F04
6 E-200
TYP
(E) XFMR 'ETB'
(E) GROUND BAR
4 E-300
(N)
5 E-300

GROUND BOND

WATER PIPE
6 E-300
6 E-300

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.0850% CONSTRUCTION DOCUMENTS06/21/24 -- 90% CONSTRUCTION DOCUMENTS07/23/24 --
PLAN CHECK SUBMITTAL10/02/24 --
PLAN CHECK CORRECTIONS04/01/251

GENERAL NOTES
1 1/8" = 1'-0" ENLARGED ELECTRICAL PLAN - DEMOLITION
2 1/8" = 1'-0" ENLARGED ELECTRICAL PLAN - NEW
TRUE
NORTHN
TRUE
NORTHN
E-200

ENLARGED ELECTRICAL PLAN - DEMOLITION
& NEW

DEMOLITION KEYNOTES
DISCONNECT & REMOVE EXISTING RECEPTACLE. EXISTING BRANCH CIRCUIT

WIRING TO BE JUNCTIONED / SAFED OFF FOR FUTURE CONNECTION TO NEW RECEPTACLE. REFER TO REMODEL PLAN FOR REQUIREMENTS.

DISCONNECT, REMOVE, TRANSPORT AND DISPOSE EXISTING MOTOR CONTROL.

CONTRACTOR SHALL PRESERVE EXISTING CONDUCTORS FOR EXISTING CIRCUIT TO REMAIN.

DISCONNECT, REMOVE, TRANSPORT, AND DISPOSE EXISTING OUTDOOR DISCONNECT SWITCH AND ASSOCIATED CONDUIT TO EXISTING CHILLER.

DISCONNECT EXISTING MECHANICAL EQUIPMENT AND PREPARE TO CIRCUIT TO BE ROUTED TO NEW DISTRIBUTION BOARD.
1 KEYNOTE
1PROVIDE A NEW GFCI, 125V, 20A WEATHERPROOF RECEPTACLE WITH AN 'IN-USE' COVER.
2 3
4 1. REFER TO GENERAL DEMOLITION NOTES ON SHEET E-001 FOR ADDITIONAL INFORMATION.

2. REFER TO FEEDER SCHEDULE ON E-002 FOR ADDITIONAL INFORMATION.

3. REFER TO SINGLE LINE DIAGRAM SHEET E-002 FOR ADDITIONAL INFORMATION.

AL
BK
SC
3 NO SCALE PHOTO DETAIL
4 NO SCALE PHOTO DETAIL
5 NO SCALE PHOTO DETAIL
6 NO SCALE PHOTO DETAIL

DISCONNECT, REMOVE, TRANSPORT, AND

DISPOSE EXISTING OUTDOOR

DISCONNECT SWITCH AND ASSOCIATED
CONDUIT TO EXISTING CHILLER.

DISCONNECT,

REMOVE, TRANSPORT

AND DISPOSE

EXISTING MOTOR
CONTROL CONTROL.

CONTRACTOR SHALL

PRESERVE EXISTING

CONDUCTORS FOR

EXISTING CIRCUIT TO
REMAIN.

EXISTING VFD'S TO REMAIN

AND BE DISCONNECTED

AND RECIRCUITED TO NEW
DISCONNECT SWICTH (TYP).

NEW POWER PANEL
'PP' LOCATION
15 POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.0850% CONSTRUCTION DOCUMENTS06/21/24 -- 90% CONSTRUCTION DOCUMENTS07/23/24 --
PLAN CHECK SUBMITTAL10/02/24 --
PLAN CHECK CORRECTIONS04/01/251
E-300

ELECTRICAL DETAILS
2 NO SCALE CONDUIT SUPPORT TO CMU WALL DETAIL
3 NO SCALE COLD SHRINK SPLICE KIT DETAIL
4 NO SCALE GROUNDING DETAIL
1 NO SCALE EQUIPMENT MOUNTING DTAIL
5 NO SCALE GROUND WELL DETAIL
6 NO SCALE CONDUIT PENETRATION DETAIL
6'-0"
MAX.
3"
4"
MIN.

ELECTRICAL PANEL
MAX WT. = 175 LBS.

MAX SIZE = 72"H X 20"W X 5.75D
P-1000 ASTM A1011 UNISTRUT

FULL PANEL LENGTH TOP AND
BOTTOM
12"Ø HILTI KB-TZ2 (ICC ESR
1917) @ 16" O.C., TYP.
(E) BLOCK WALL

FINISHED FLOOR

METALLIC COLD WATER SERVICE ENTRANCE
(PROVIDE SIMILAR CONNECTION TO FIRE

PROTECTION WATER SERVICE ENTRANCE),
(CEC 252-52(A)(1) (IF AVAILABLE)
BOND WITHIN 5 FEET OF COLD WATER PIPE
EXITING UNDERGROUND ENTRANCE.
(1) #3/0 THWN GREEN GROUND

TO POWER PANEL 'PP'
(E) BUILDING STRUCTURAL
STEEL CEC 250-52(A)(2)
NOTES:

1. ALL GROUNDING ELECTRODE CONDUCTORS SHALL SIZED PER CEC TABLE 250.66

2. ALL GROUNDING SHALL BE INSTALLED WITH ACCORDANCE WITH CEC ARTICLE 250 OF THE NATIONAL ELECTRICAL CODE.
(E) CADWELD
SUPPLY

SIDECADWELD
AL
BK
SC
2 E-200
A

PLAN VIEW OF GROUND

CLAMP TO RIDGED CONDUIT

PROVIDE ADDITIONAL GROUND RODS IN
CONCRETE BOXES 72" O.C. AS NEEDED
TO MEET 25 OHM REQUIREMENT

EXTENDING SAME CONDUIT AND WIRE
AND USING SAME CLAMPS. 25 OHM

RESISTANCE TO GROUND MAXIMUM

SHALL BE PROVIDED USING SAME
GROUND RODS ONLY. PRIOR TO THE

CONNECTION OF CONDUIT AT ROD OR
PANEL OR OTHER GROUND PATH.
8" DIA. CLAY SOIL PIPE FILL WITH

BENDENITE CLAY
3/4"P.V.C-1 3/0 COPPER GND TO
(E) GROUND BAR

CAST IRON LOCKING COVER
3/4" X 10'-0" COPPER CLAD

GROUND ROD

COPPER ALLOY GROUND CLAMPS

BY BURNDY OR EQUAL GROUND ROD

RIGID CONDUIT

GROUND CONNECTOR BURNDY

TYPE GKP

COPPER WIRE SIZE AS REQUIRED

GROUND CONNECTOR CONDUIT

TO ROD WITH FEED THRU
PRE CAST CONCRETE BOX (19" X
14") BROOKS #3600 OR EQUAL
GROUND

CLAMP, SEE

DETAIL A

FINISH GRADE

CAST IRON FRAME

CAST IRON BOLT DOWN
COVER

GROUND WIRE
A
2'-0" MIN.
4 E-300
2"
EMT SHALL BE SECURELY FASTENED IN PLACE AT LEAST EVERY 3 m (10 FT).

TABLE 344.30(B) (2) SUPPORT FOR RIGID METAL CONDUIT

CONDUIT SIZEMAXIMUM DISTANCE BETWEEN RIGID METAL CONDUIT

SUPPORTS

METRIC DESIGNER TRADE SIZEMETERSFEET
16-211/2-3/4310
2713.712
35-411 1/4 - 1 1/24.314
53-632 - 2 1/24.916

CONDUIT TRADE
SIZE

SIZE AND EMBEDMENT

OF ANCHOR BOLTS
12"C - 2 12"C14" X 1 38
3"C - 4"C516" X 1 12"

HEX NUT &
BOLT
UNISTRUT P1000 S.S.

ASTM A101
(E) 8" CMU BLOCK WALL
(E) GROUND BAR
(E)
(N) 3/4"x10' GROUND ROD
(CEC 250-52(A)(5))

CADWELL

TO (E) TRANSFORMER 'ETB'
(E) (1) #6 THWN-3/4"C
(1) #3/0-3/4"C
(1) #3/0-3/4"C
(N) #3/0 THWN GREEN GROUND

TO POWER PANEL 'PP'
THIS MATERIAL WAS EXTRACTED AND DRAWN BY 3M FIRE PROTECTION PRODUCTS FROM THE 2007 EDITION OF THE UL FIRE RESISTANCE DIRECTORY.

System No. W-L-1001
F Ratings – 1, 2, 3 and 4 Hr (See Items 2 and 3)
T Ratings – 0, 1, 2, 3, and 4 Hr (See Item 3)
L Rating At Ambient – less than 1 CFM/sq ft
L Rating At 400 F – less than 1 CFM/sq ft

OMEGA FLEX INC

TITEFLEX CORP

A BUNDY CO

WARD MFG INC
+When copper pipe is used, T Rating is 0 hr.
3M COMPANY – CP 25WB+ caulk or FB-3000 WT sealant,
Max Pipe or ConduitF Rating T Rating
Diam In. (mm)HrHr
1 (25)1 or 20+, 1 or 2
1 (25)3 or 4 3 or 4
4 (102)1 or 20
6 (152)3 or 40
12 (305)1 or 20

1. WALL ASSEMBLY – THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL

ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

A. STUDS – WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 HR FIRE RATED ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER SPACED 16 IN. (406 MM) OC WITH NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. (92 MM) WIDE BY 1-3/8 IN. (35 MM) DEEP CHANNELS SPACED MAX 24 IN. (610 MM) OC.

B. GYPSUM BOARD* – NOM 1/2 OR 5/8 IN. (13 OR 16 MM) THICK, 4 FT. (122 CM) WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF

LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF OPENING IS 26 IN. (660 MM).

2. THROUGH PENETRANT – ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN OF 0 IN. (0 MM) (POINT CONTACT) TO MAX 2 IN. (51 MM). PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:

A. Steel Pipe – Nom 24 in. (610 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.

B. Iron Pipe – Nom 24 in. (610 mm) diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 12 in. (305 mm) diam (or smaller) or Class 50 (or heavier) ductile iron pressure pipe.

C. Conduit – Nom 6 in. (152 mm) diam (or smaller) steel conduit or nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing
D. Copper Tubing – Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing E. Copper Pipe – Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.

F. Through Penetrating Product* – Flexible Metal Piping – The following types of steel flexible metal gas piping may be used:

1. NOM 2 IN. (51 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC

COVERING ON PIPING MAY OR MAY NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.

2. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC

COVERING ON PIPING MAY OR MAY NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.

3. NOM 1 IN. (25 MM) DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC

COVERING ON PIPING MAY OR MAY NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY.

3. FILL, VOID OR CAVITY MATERIAL* – CAULK OR SEALANT – MIN 5/8. 1-1/4,1-7/8 AND 2-1/2 IN. (16, 32, 48 AND 64 MM) THICKNESS OF CAULK FOR 1, 2, 3 AND 4 HR RATED ASSEMBLIES, RESPECTIVELY, APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. MIN 1/4 IN. (6 MM) DIAM

BEAD OF CAULK APPLIED TO GYPSUM BOARD/PENETRANT INTERFACE AT POINT CONTACT LOCATION ON BOTH SIDES OF WALL. THE HOURLY F

RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY

FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE. THE HOURLY T RATING OF THE

FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE PIPE

OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS TABULATED BELOW:
*Bearing the UL Classification Marking
This material was extracted and drawn by 3M Fire Protection Products from the 2007 edition of the UL Fire Resistance Directory. 16 DIAL
BEFDRE

YOU DIG

TWO WORKING

DAYS BEFORE

YOU DIG
TOLL FREE 1-800-227-2600

A PUBLIC SERVICE BY

UNDERGROUND SERVICE ALERT
3 0
1 • .,-----.._
3 r
0 r 8
8 ,­
L)­
(
t2:::22::~7t:1
3M™ Cold Shrink Quick Splice Low Voltage
QSL V-M Series
Data Sheet July 2018
~ s .... 1ng Maslic
Con~tor
SealingMaslic ~
3M"' Quick Splice Low Vottage QSLV-M
C1m1;rCorQ
Product Series Cable Size Range
AWG or kcmil *
Cable Insulation 0.0. Range
Inches mm
Max Connector O.D.

Inches mm
Max Connector Length
Inches mm
QSLV-M-8-2/0 8 -2/0 0 20 -0 75 5 -19 0 687 17 25 63
QSLV-M-2-500 2 -500 0.40-1.60 10-41 1.500 38 4.25 108
~Insulator may be used on cable sizes outside of the recommended range, provided both cables are within the insulation 0.0. range and the connector meets the dimensional requirements shown above.

Description
Agency Approvals
& Self Certifications
3M™ Cold Shrink Quick Splice Low Voltage QSLV-M are open-ended tubular rubber sleeves with sealing mastic on each end which are factory expanded and assembled onto a unique three-core system. Two cores, one on each end, are removed after the 3M QSLV-M insulator has been centered over an inline connector, allowing the ends of the tube to shrink and form a water-resistant seal. The third, center segment of the core remains inside the cold shrink tube, acting as a support structure. Sizing of the cores and tube, along with the sealing mastic on each end, is designed to accommodate the variance in connectors and connector crimping techniques and final dimensions without degrading the seal and insulating characteristics of the EPDM rubber tube, while making core removal easy. Two diameter sizes will cover a range of 1000 volt or less cable from 8 AWG through 500 kcmil, copper and aluminum conductors with crimped connectors.

In aerial applications where intense UV radiation will be common and visual inspection is not possible, it is recommended to overwrap the tubing with Scotch® Super 33+ TM Vinyl Electrical Tape or Scotch® Self-Fusing Silicone Rubber Electrical Tape 70 • Simple hand installation, no tools required
• No heat source, eg. heat guns or torches
• Accommodates wide range of cable sizes, including street lighting • Excellent wet electrical properties
• Good thermal stability during storage and shipping
• Seals tight, retains resiliency and pressure, even after years of aging and exposure • Resists acids and alkalies
• Water resistant. Meets water seal requirements of ANSI C119.1 RoHS
2011/65/EU
"RoHS 2011/65/EU" means that the product or part does not contain any of the substances in excess of the maximum concentration values ("MCVs") in EU Ro HS Directive 2011 /65/EU.

The MCVs are by weight in homogeneous materials. This information represents 3M's knowledge and belief, which may be based in whole or in part on information provided by third party suppliers to 3M.
1 of 3
-
rESS/
1" M. C
3NI
Y} No. E22808 ~
(t'. ,:J
F CA

I I I I
I I
I
l-----+---+------------+---+--+---1-----11 SHEET I CITY OF CARLSBAD ~2 PUBLIC WORKS DEPARTMENT ~
~IM=P=R=o=VE=M=EN~T=P=L=A=Ns==Fo=R=, ============-=====:

APPROVED: JOHN MAASHOFF RCE 61909 EXP-9/30/25

PUBUC WORKS MANAGER CITY OF CARLSBAD DATE

DATE INITIAL

ENGINEER OF WORK REVISION DESCRIPTION

DATE INITIAL DATE INITIAL

OTHER APPROVAL CITY APPROVAL
DWN BY:

CHKD BY: __ _
RVWD BY:

PROJECT NO. DRAWING NO.

APPLICABLE CODES

SCOPE OF WORK
REPLACE THE EXISTING 99.4 TON AIR-COOLED CHILLER WITH NEW.

PROVIDE (N) TRENCH DRAIN FOR CHILLER YARD.

SHEET INDEX
P-001 1
S.No.SHEET TITLE
P-201 PLUMBING PLAN

NOTES, LEGEND AND ABBREVIATIONS, AND SCHEDULES
SHEET
NUMBER
2 A. OMISSIONS AND OR CONFLICTS BETWEEN THE VARIOUS ELEMENTS OF THE

CONSTRUCTION DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF AND

RESOLVED WITH THE ARCHITECT PRIOR TO PROCEEDING WITH ANY OF THE AFFECTED WORK.

B. MATERIALS AND WORKMANSHIP SHALL CONFORM TO THE REQUIREMENTS OF CBC AND CPC.

C. THE PLUMBING CONSTRUCTION DOCUMENTS REPRESENT THE INTENT OF PLUMBING AND PIPING SYSTEMS, NOT THE METHOD OF CONSTRUCTION. THE CONTRACTOR

SHALL BE RESPONSIBLE FOR ALL LABOR, MATERIALS, EQUIPMENT AND ACCESSORIES NECESSARY TO ACHIEVE THE FINISHED SYSTEMS.

D. FIELD VERIFY AND COORDINATE WITH ELECTRICAL SYSTEMS INSTALLER EXACT ELECTRICAL REQUIREMENTS OF PLUMBING PRODUCTS REQUIRING POWER.

E. ELECTRICAL POWER CONNECTIONS SHALL BE MADE BY ELECTRICAL SYSTEMS INSTALLER UNDER PROVISIONS OF DIVISION 26.

PROJECT NOTES
YB

CFHCUBIC FEET PER HOUR

YARD BOX
HWR
(E)W

SOV IN YB
S OR W
S OR W

ABBREVIATION
DN
BEL
ABV
W/
CLG
FLR
CONN
I.E.

AP
POC
VTR
COTG
GC
CV
SOV
COYB
WCO
(E) G
G
HWR
(E) G
G
FCO
HW
CD
CW
CD
V
SYMBOL
DOWN
BELOW
ABOVE
WITH

CEILING
FLOOR

VENT THRU ROOF

POINT OF CONNECTION

CONNECTION

INVERT ELEVATION

ACCESS PANEL

CLEANOUT TO GRADE

WALL CLEANOUT

CLEANOUT IN YARDBOX

SHUT-OFF VALVE IN YARD BOX

CHECK VALVE

SHUT-OFF VALVE

GAS COCK

HOT WATER RETURN

GAS (LOW PRESSURE)

EXISTING GAS

HOT WATER

FLOOR CLEANOUT

EXISTING SOIL OR WASTE

SANITARY VENT

COLD WATER

CONDENSATE DRAIN

SOIL OR WASTE (BELOW GRADE)

DESCRIPTION

SOIL OR WASTE (ABOVE GRADE)
LEGEND
(E) CW(E) CWEXISTING COLD WATER
(E) HW(E) HWEXISTING HOT WATER
(E) HWR(E) HWREXISTING HOT WATER RETURN
(E) CD(E) CDEXISTING CONDENSATE DRAIN
(E) V(E) VEXISTING VENT
(E) W(E) WEXISTING WASTE

PODPOINT OF DISCONNECTION

UPUP PIPING

DOWNDOWN PIPING

GPMGALLON PER MINUTE
MEP

AHJAUTHORITY HAVING JURISDICTION

MECHANICAL

ELECTRICAL

PLUMBING

WHAWATER HAMMER ARESTOR

TPTRAP PRIMER

DEMODEMOLITION

BVBALL VALVE

ESWEMERGENCY SHOWER EYEWASH

FFFIRE SPRINKLER LINE
2022 CALIFORNIA HISTORICAL BUILDING CODE, PART 8, CBSC
2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, CBSC
2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, CBSC
2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, CBSC
2022 CALIFORNIA FIRE CODE, PART 9, CBSC
2022 CALIFORNIA ENERGY CODE, PART 6, CBSC
2022 CALIFORNIA BUILDING CODE (CBC), PART 2, CBSC
2022 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1, CBSC 2022 CALIFORNIA REFERENCED STANDARDS, PART 12, CBSC
2022 CALIFORNIA GREEN BUILDING CODE.

SCHEDULE
TRENCH

GRATE &
FRAME
NEENAH MODEL 4996-A1, TYPE M TRENCH FRAME WITH GRATED COVER CAST IRON 12" WIDE x 84 " LONG .

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.08
RPM
SS
DS
50% CONSTRUCTION DOCUMENTS06/21/24 --
90% CONSTRUCTION DOCUMENTS07/23/24 --
PLAN CHECK SUBMITTAL10/02/24 --
No. 30841REM
SATTE

ETER SIG
ER
P
D
LO A
C N
F HO C
A
AL I
F C
ANR
I
O
EFO
ISS

NER ENI GELANI
DARREN
B
. SMITH
Exp. 12/31/26PLAN CHECK CORRECTIONS04/01/251

NOTES, LEGEND AND ABBREVIATIONS, AND

SCHEDULES
P-001
ij
= _,:
u
I
0 I
~ ,,
C
C
~
.2
0 n.
,,
C
.a
0 8
OJ
0 ~
X
"' ~ ,,
~
C
g.

I
!!J
0 "' ~
~
C _,:
~
~
J,
Cl
::::
0 8
d.
.;;
[
C
...J
-
,:,~"""""""'-------
! mo~~IBIR:T ·a c:::I ~
_,:

Jl
l',
"'
DIAL
BEFORE

YOU DIG

TWO WORKING

DAYS BEFORE

YOU DIG
il TOLL FREE 1111111111 1-800-227-2600
15 A PUBLIC SERVICE BY
ii: UNDERGROUND SERVICE ALERT
* *
'
~=t=j====---===+=+=t==t~fSHml CITY OF CARLSBAD ~
t"l-==t=jt=======-----====t==+==l==i=~ ;::~~
7 ~~~~P~U~BL::IC::::::::W:::O::::R:::KS::::::D:::E:::PA~R~TM~E~NT!::::=!JLE._j~~ 2 ::::! I-I IMPROVEMENT PLANS FOR:
/'I,
~==3E~~t====================~===E==l===t=~ fAAPFPPiR(Ro~VEEDD~: ~JO~HN~M~A~AS~~~==============;:===::! I-HOFF RCE 61909 EXP. 9/30/25

PUBLIC WORKS MANAGER CITY OF CARLSBAD DATE

DA TE INITIAL

ENGINEER OF WORK REVISION DESCRIPTION

DATE INITIAL DA TE INITIAL

OTHER APPROVAL CITY APPROVAL
DWN BY: ---I PROJECT NO.

RCVHWKDD BY: __ _
BY: .
3"W SCHEDULE 40 PVC PIPE
BELOW GRADE.

FLOOR SAWCUT

REFER TO

STRUCTURAL DETAIL

TRENCH SEE
7 S-501
7'-0"
1'-0"

CONTRACTOR TO CORE THE

CURB AND TERMINATE PIPE AT

CENTER OF THE CURB
(E) GRADE
(E) ELECTRICAL

TRANSFORMER(E) GENERATOR ROOM
(E) BOILER ROOM
(E) TRASH
(E) CHILLER YARD
(E) GENERATOR SET
2% SLOPE
(E) FINISH ASPHALT PAVING
(E) CONCRETE GUTTER
(E) CURB
SLOPE

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.08
RPM
SS
DS
50% CONSTRUCTION DOCUMENTS06/21/24 --
90% CONSTRUCTION DOCUMENTS07/23/24 --
PLAN CHECK SUBMITTAL10/02/24 --
No. 30841REM
SATTE

ETER SIG
ER
P
D
LO A
C N
F HO C
A
AL I
F C
ANR
I
O
EFO
ISS

NER ENI GELANI
DARREN
B
. SMITH
Exp. 12/31/26PLAN CHECK CORRECTIONS04/01/251
1 1/4"=1'-0" CHILLER YARD PLUMBING PLAN
TRUE
NORTHN

PLUMBING PLAN
P-201
~ ,,
i
'i
0 "' I
"l
~
ui
0 0
X
"' ;:!,
-"
E
~
a:
~
Cl
~
!
C
G
E
G
u
0 e-"' Ii
= _,::
u
I
0 I
~ ,,
C
0 G
.2
0 "­
,,
0 -"
~
1i u
CXl
0 ~
X
"' ;:!, ,,
~
0 g,
I
!'l
0 "' ~
~
0 _,::
~
~
J,
Cl
:;:;
"' g:
"'
0 .:,
i
0 ...J
-
,,~~-------! mo~~IBiT
·a c= ~
_,::

Jl
:,:,
ID
DIAL
BEFORE

YOU DIG

TWO WORKING

DAYS BEFORE

YOU DIG
il TOLL FREE 111111111 1-800-227-2600
1i A PUBLIC SERVICE BY
ii: UNDERGROUND SERVICE ALERT
,,---_-_-_-_-_JI--------~
-.,____I., 1
It ~)l L. ~j
1~ _.=....:_,j
()
'-,,_
C't
-
8 IT 7l !
., ':' :;c:,
~
" ....
b
b
~======== _____ __Jb ~------_J
' .

I!/
I~
I
11 11
-~
0 0
-----------
-
~
_/
* *
-
~=t=j====---===+=+=t==t~ fSHml CITY OF CARLSBAD ~
t"l-==t=jt=======-----====t==+=~==i=~ ;::~~B~~~~P~U~BL::IC::::::::W:::O:::R:::KS::::::D:::E:::PA~R~TM~E~NT!::::=~LE._j~~ 2 ::::! I-I IMPRO'IEMENT PLANS FOR:
/'\
~==~E~~t====================~===E===i===t=~ fAAPFPPiR(Ro~VEEDD~: ~JO~HN~M~A~AS~~~=====:;;::::::=::==:::;:= I-HOFF RCE 61909 EXP. 9/30/25
PUBLIC WORKS MANAGER CllY OF CARLSBAD DATE

DA TE INITIAL

ENGINEER OF WORK REVISION DESCRIPTION

DATE INITIAL DATE INITIAL
OlHER APPROVAL CITY APPROVAL
DWN BY: ---I PROJECT NO.

CHKD BY: __ _
RVWD BY: .

GENERAL

SCOPE OF WORK

TOLERANCE

1. PERMITTED TOLERANCE SHALL BE ACCORDING TO THE CBC.

DESIGN CRITERIA
DESIGN CONFORMS TO THE 2022 CALIFORNIA BUILDING CODE.

1. SEISMIC ANALYSIS: EQUIVALENT LATERAL FORCE PROCEDURE ·SITE CLASS = D - DEFAULT
·SEISMIC DESIGN CATEGORY = D
·RISK OCCUPANCY CATEGORY = IV
·Ie= 1.5
·Ss= 0.948
·S1 = 0.348
·Fa = 1.2
·Sds =

0.759

FOR CHILLER UNIT
·Ap = 1.00
·Rp = 2.50
·Ω = 2.00
·Fp = 0.342

2. WIND ANALYSIS: WIND LOADS ARE BASED ON CBC WITH THE FOLLOWING FACTORS:
·EXPOSURE CATEGORY = C
·V = 107 MPH
·Vasd = 82.88 MPH
·KZ = 0.85
·Kzt = 1.0
·KE = 1.0
·RISK CATEGORY IV

CAST-IN-PLACE CONCRETE
THE SCOPE OF WORK FOR THIS PROJECT ARE:
- REPLACE THE EXISTING CHILLER AND ANCHORAGE
- REMOVE AND REPLACE PORTION OF THE EXISTING SLAB ON GRADE AND ADJUST THE SLOPE FOR

DRAINAGE

NON-SHRINK GROUT

1. NON- SHRINK GROUT SHALL BE SIKA SIKAGROUT 212, OR APPROVED EQUAL.

2. SURFACE PREPARATION AND INSTALLATION SHALL FOLLOW MANUFACTURER'S SPECIFICATIONS.

PROPER SURFACE CLEANING AND MOIST CURING ARE ESSNTIAL.

3. FOR POURABLE GROUT, CONSTRUCT FORMS TO RETAIN GROUT WITHOUT LEAKAGE. FORMS SHALL BE LINED OR COATED WITH BOND-BREAKER FOR EASY REMOVAL.

4. NON-SHRINK GROUT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 7,000 PSI AT 28 DAYS.

5. GROUT SHAL BE NON-SHRINK GROUT UNLESS OTHERWISE NOTED..

6. REPAIR UNUSED CORED OR DRILLED HOLES BY FILLING WITH NON-SHRINK GROUT AT CONCRETE AND MASONRY, FINISH SURFACE TO MATCH THE ADJACENT CONDITION.

1. PORTLAND CEMENT SHALL BE ASTM C150 TYPE V UNLESS OTHERWISE NOTED.

2. ALL CONCRETE SHALL BE NORMAL WEIGHT (145 PCF) HARD ROCK TYPE ASTM C33.

3. CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH (f'c) AT 28 DAYS AS FOLLOWS, UNLESS OTHERWISE NOTED:

A. EQUIPMENT PAD FOOTING FOOTING: 4,000 PSI UNLESS OTHERWISE NOTED.

B. SLAB-ON-GRADE: 4,000 PSI UNLESS OTHERWISE NOTED.

4. CONCRETE MIXES SHALL BE DESIGNED BY A QUALIFIED TESTING LABORATORY, BEARING A

REGISTERED CALIFORNIA CIVIL ENGINEER'S STAMP, AND REVIEWED AND APPROVED BY THE SEOR PRIOR TO USE.

5. MAXIMUM RATIO OF WATER TO CEMENTITIOUS MATERIALS, BY WEIGHT, SHALL BE 0.45 UNLESS OTHERWISE NOTED. USE MINIMUM 6 SACKS OF CEMENT PER CUBIC YARD OF CONCRETE.

6. ALL CONSTRUCTION JOINTS SHALL BE KEYED AND SHALL BE THOROUGHLY CLEANED. SEE CAST-IN-PLACE CONCRETE NOTE 10.

7. THE CONTRACTOR SHALL SUBMIT THE PROPOSED LOCATION OF ALL CONSTRUCTION JOINTS TO THE ENGINEER FOR REVIEW PRIOR PLACING OF CONCRETE. POUR JOINTS SHALL BE LOCATED TO MINIMIZE EFFECTS OF SHRINKAGE AS WELL AS PLACED AT POINTS OF LOW STRESS. REFER TO ACI 318, SEC.

26.5.6. 8. CONCRETE COVERAGE OF REINFORCING STEEL SHALL BE AS FOLLOWS, UNLESS OTHERWISE NOTED:

A. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3" B. CONCRETE EXPOSED TO EARTH OR WEATHER:
·#6 THROUGH #18 REBAR: 2”
·#5 REBAR, W31 OR D31 WIRE, AND SMALLER: 1 1/2"
C. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND:
·SLABS, WALLS AND JOISTS (#11 REBAR AND SMALLER): 1"
·BEAMS AND COLUMNS: 1-1/2"
D. SLABS-ON-GRADE: MID-DEPTH

9. ALL EXPOSED CONCRETE EDGES SHALL BE FORMED WITH A 3/4" CHAMFER UNLESS OTHERWISE NOTED.

10. ALL NEW CONCRETE PLACED AGAINST HARDENED CONCRETE SHALL BE PREPARED PER THE FOLLOWING PROCEDURE:

A. ROUGHEN HARDENED SURFACE TO AN AMPLITUDE OF 1/4" WITH BUSH HAMMER, SAND BLASTING, OR OTHER APPROVED METHOD.

B. CLEAN SURFACES OF DUST AND DEBRIS USING CLEAN COMPRESSED AIR AND WATER.

C. THE SURFACE OF ALL HORIZONTAL CONSTRUCTION JOINTS SHALL BE CLEANED AND ROUGHED BY EXPOSING CLEAN AGGREGATE SOLIDLY EMBEDDED IN MORTAR MATRIX. IN THE EVENT THAT THE CONTACT SURFACE BECOMES COATED WITH EARTH, SAWDUST, ETC., AFTER BEING CLEANED, THE ENTIRE SURFACE SO COATED SHALL BE RECLEANED.

D. REFER TO OTHER NOTES FOR DUST CONTROL DURING CONSTRUCTION.

E. BONDING AGENTS ARE NOT ACCEPTABLE OR A SUBSTITUTE FOR PROCEDURES A, B. AND C.

11. BONDING AGENT WHEN SPECIFIED SHALL BE CHEMREX CONCRESIVE LIQUID LPL, OR SIKA ARMATEC 110

EPOCEM, OR APPROVED EQUAL AND SHALL BE APPLIED FOLLOWING THE MANUFACTURER'S RECOMMENDATIONS.

12. THE NOMINAL MAXIMUM SIZE OF COARSE AGGREGATES SHALL BE 1" UNLESS OTHERWISE NOTED.

13. ALL CRACKS WIDER THAN 1/64" IN NEW CONCRETE APPEARING WITHIN 6 MONTHS OF CONCRETE

PLACEMENT SHALL BE REPAIRED USING EPOXY ADHESIVE INJECTION BY THE CONTRACTOR AT NO COST TO THE OWNER.

14. CONCRETE SHALL BE MIXED, PLACED AND CURED PER ACI 318, LATEST EDITION AND PROJECT SPECIFICATION.

1. ALL CONCRETE AND MASONRY SHALL BE REINFORCED. REINFORCING STEEL SHALL BE NEW DEFORMED STEEL BARS CONFORMING TO ASTM A615, GRADE 60 UNLESS OTHERWISE NOTED.

2. REINFORCING STEEL SHALL BE ACCURATELY PLACED AND FIRMLY SUPPORTED DURING CONCRETE POUR.

3. COMPLETE REINFORCING STEEL PLACEMENT DRAWINGS SHALL BE PREPARED IN ACCORDANCE WITH ACI 315 BY THE CONTRACTOR AND REVIEWED BY THE SEOR AND SHALL BE AVAILABLE ON THE JOB SITE PRIOR TO INSPECTION AND THE PLACING OF CONCRETE.

4. ANCHOR BOLTS, DOWELS AND OTHER EMBEDDED ITEMS SHALL BE SECURELY ANCHORED AND/OR TIED IN PLACE BEFORE CONCRETE IS PLACED.

5. ALL REINFORCING STEEL TO BE WELDED SHALL CONFORM TO ASTM A706, GRADE 60. DEFORMATIONS SHALL BE IN ACCORDANCE WITH ASTM A615.

6. ALL WELDING OF REINFORCING STEEL SHALL CONFORM TO AWS D1.4 AND SHALL BE PERFORMED BY CERTIFIED WELDERS USING AWS A5.5 E80XX FOR ASTM A706 GRADE 60 (TABLE 7.1 AWS D1.4) LOW HYDROGEN MOISTURE RESISTING ELECTRODES UNLESS OTHERWISE NOTED.

7. NO HEATING SHALL BE ALLOWED FOR BENDING OF REINFORCING STEEL UNLESS APPROVED BY THE ENGINEER.

8. ALL MECHANICAL SPLICES SHALL BE APPROVED BY THE SEOR AND INSPECTED DURING CONSTRUCTION AND SHALL HAVE AN ICC-ES/IAPMO NUMBER.

9. ALL HEADED BAR SYSTEMS (TERMINATORS) SHALL BE APPROVED BY THE SEOR AND INSPECTED DURING CONSTRUCTION AND SHALL HAVE AN ICC-ES/IAPMO NUMBER.

10. ALL REINFORCING STEEL INTERRUPTED BY STRUCTURAL STEEL SHALL TERMINATE WITHIN 1" OF STEEL SURFACE WITH A 90° STANDARD HOOK UNLESS OTHERWISE NOTED.

11. ALL REINFORCING BEND SHALL BE MADE COLD. RE-BENDING OR PREVIOUSLY BENT REINFORCING IS NOT PERMITTED.

REINFORCING STEEL

ADHESIVE ANCHOR SYSTEM FOR THREADED ROD OR REBAR IN CONCRETE

MINIMUM EMBEDMENT
DEPTH (U.N.O.)
#5

THREAD ROD
DIAMETER (Ø)
#4
9,300 LB 6"
412"
5,600 LB

TESTING FORCE

AN EQUIVALENT PRODUCT ACCEPTABLE TO ENGINEER
HILTI HIT - RE 500 V3

SIMPSON - SET-XP

ACCEPTABLE PRODUCTS
ESR-3814
ESR-2508

ICC-ES EVALUATION REPORT

REBAR SIZE

ACCEPTABLE PRODUCTS
HILTI - KWIK BOLT TZ2
SIMPSON - STRONG-BOLT 2
DEPTH (U.N.O.)
212"

AN EQUIVALENT PRODUCT ACCEPTABLE TO ENGINEER

ICC-ES EVALUATION REPORT
ESR-4266
ESR-3037
HILTI KWIK BOLT TZ2
338"
BOLT DIAMETER (Ø)EFFECTIVE MIN.

DEPTH , U.N.O.
38"30
12"50 314"

INSTALLATION TORQUE (FT-LB)
*
SIMPSON STRONG-TIE STRONG-BOLT 2
ANCHORS MUST ATTAIN SPECIFIED TORQUE WITHIN 1/2 TURN OF THE NUT. INSTALLATION TORQUE APPLIES TO CARBON STEEL ANCHORS. REFER TO ICC REPORT FOR INSTALLATION TORQUE REQUIRED FOR STAINLESS STEEL ANCHORS.

ANCHORS MUST ATTAIN SPECIFIED TORQUE WITHIN 1/2 TURN OF THE NUT. INSTALLATION TORQUE APPLIES TO CARBON STEEL ANCHORS. REFER TO ICC REPORT FOR INSTALLATION TORQUE REQUIRED FOR STAINLESS STEEL ANCHORS.
312"
7"
8"
9"
#3
#6
#7
#8
3,400 LB
13,450 LB
16,800 LB
22,600 LB
412"
5"
58"
34"
4"
434"
40 110
2"
BOLT DIAMETER (Ø)
38"
12"
58"
34"
38" DIA
12" DIA
58" DIA
34" DIA
78" DIA
1" DIA

1. REFER TO PROJECT SPECIFICATIONS FOR PROJECT REQUIREMENTS.

2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SAFETY OF WORK AREA DURING CONSTRUCTION PERIOD. THE CONTRCTOR SHALL PROTECT ADJACENT PROPERTY AND UTILITIES IN ACCORDANCE WITH ALL NATIONAL, STATE, AND LOCAL SAFETY ORDINANCES.

3. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRACTION. WHERE CONDITIONS ARE

NOT SPECIFICALLY INDICATED BUT ARE OF SIMILAR CHARACTER TO DETAILS SHOW, SIMILAR DETAILS OF CONSTRACTION SHALL BE USED SUBJECT TO PRIOR REVIEW BY THE SEOR.

4. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK, AND SHALL BE SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES. THE

SUPPORTING SERVICES BY THE SEOR, WHETHER PERFORMED PRIOR TO, DURING, OR AFTER

CONSTRUCTION, ARE PERFORMED SOLELY FOR THE PURPOSE OF ASSISTING IN QUALITY CONTROL AND IN ACHIEVING CONFORMANCE WITH CONTRACT DRAWINGS AND PROJECT SPECIFICATIONS; BUT

THEY DO NOT GUARANTEE THE CONTRACTOR'S PERFORMANCE AND SHALL NOT BE CONSIDERED AS SUPERVISION OF CONSTRUCTION.

5. SHOP DRAWINGS REQUIRED BY THE PROJECT SPECIFICATIONS SHALL BE SUBMITTED TO THE SEOR FOR REVIEW PRIOR TO FABRICATION. DRAWINGS ARE REVIEWED BY THE SEOR FOR GENERAL CONFORMANCE TO THE DESIGN. REGARDLESS OF THE SEOR'S REVIEW, THE CONTRACTOR IS FULLY

AND SOLELY RESPONSIBLE FOR COMPLETE AND SATISFACTORY SUBMITTAL AND CONFORMANCE TO THE CONTRACT DOCUMENTS. SHOP DRAWINGS WILL BE REJECTED FOR INCOMPLETENESS, LACK OF CALCULATIONS (IF REQUIRED) OR CHANGES WITHOUT PRE-APPROVAL. ALL STRUCTURAL

CALCULATIONS AND DRAWINGS AS PART OF THE SHOP DRAWINGS SUBMITTAL SHALL BE SIGNED AND STAMPED BY A CALIFORNIA REGISTERED STRUCTURAL ENGINEER.

6. ANY PARTS OF WORK AREA WHICH ARE TO BE BARRRICATED OR SEALED TO NON-CONSTRUCTION

INDIVIDUALS MUST BE COORDINATED WITH AND APPROVED BY THE OWNER BEFORE PROCEEDING WITH THE WORK.

7. THE CONTRACTOR SHALL EXERT EVERY EFFORT TO PREVENT DUST AND CONSTRUCTION DEBRIS FROM CONTAMINATING THE WORK AREA. THESE EFFORTS SHALL INCLUDE BUT NOT BE LIMITED TO PROVIDING A DAILY CLEANUP OF THE CONSTRUCTION AREA. THE CONTRACTOR SHALL REFER TO THE PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

8. THE CONTRACTOR SHALL BE RESPONSIBLE TO SECURE THE CONSTRUCTION SITE.

9. CUTTING, BORING, SAW-CUTTING OR DRILLING THROUGH NEW STRUCTURAL MEMBERS OTHER THAN

THOSE DETAILED ON STRUCTURAL DRAWINGS SHALL NOT BE DONE WITHOUT THE SEOR'S APPROVAL.

10. THE CONTRACTOR SHALL:
- CHECK DIMENSIONS.
- BE RESPONSIBLE FOR COORDINATING THE WORK OF ALL TRADES ALL DISCREPANCIES SHALL BE

CALLED TO THE ATTENTION OF THE SEOR AND SHALL BE RESOLVED BEFORE PROCEEDING WITH THE WORK.

11. ALL MATERIALS, FEATURES OR CONDITION NOT IDENTIFIED AS (E) WHICH MEANS "EXISTING, SHALLBE BE CONSIDERED AS NEW AND PART OF THE PROJECT SCOPE OF WORK.

12. THE CONTRACTOR IS FULLY AND SOLELY RESPONSIBLE FOR ALL SHORING REQUIRED IN ORDER TO SAFELY ACHIEVE THE FINAL CONSTRUCTION SHOWN ON THE DRAWINGS. THIS INCLUDES, BUT IS NOT LIMITED TO, ANY TYPES OF SHORING REQUIRED FOR SOILS EXCAVATION AND BACKFILL WORK;

SUPPORT OF STRUCTURAL ELEMENTS UNTIL THEY HAVE ACHIEVED THE NECESSARY STRENGTH TO PERFORM IN THE FINAL POSITION AND MANNER SHOWN ON THE DRAWINGS; AND SUPPORT OF

STRUCTURAL ELEMENTS THAT ARE MODIFIED AND THEREBY REDUCED IN STRENGTH IN ANY WAY

DURING CONSTRUCTION AS REQUIRED TO ACHIEVE THE FINAL CONSTRUCTION AS SHOWN ON THE DRAWINGS. ALL SHORING CALCULATIONS AND DRAWINGS SHALL BE STAMPED BY A CALIFORNIA REGISTERED ENGINEER AND SUBMITTED FOR REVIEW PRIOR TO PERFORMING THE WORK.

13. WHERE NOT INDICATED OTHERWISE, THE LATEST EDITION OF ALL CITED DOCUMENTS SHALL GOVERN.

14. THE TERM CBC IN THESE DRAWINGS MEANS 2022 CALIFORNIA BUILDING CODE. CALIFORNIA CODE OF REGULATIONS, TITLE PARTS AND VOLUMES AND ALL CITY OF CARLSBAD AMMENDMENTS.

15. ALL CONTRUCTIONS AND WORKMANSHIP, INCLUDING MATERIALS, SHALL CONFORM TO THE DRAWINGS, PROJECT SPECIFICATIONS, AND THE CBC.

16. PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE AND ADJACENT STRUCTURE(S),AND THEIR FINISHES AND UTILITIES, DURING CONSTRUCTION.

17. THE CONTRACTOR SHALL COORDINATE ALL UTILITY LOCATIONS WITH OTHER DRAWINGS AND SHALL

CONDUCT A DETAILED SURVEY OF EXISTING UTILITIES TO IDENTIFY INTERFERENCES WITH THE NEW CONSTRUCTION. PROMPTLY NOTIFY THE SEOR OF ANY INTERFERENCES PRIOR TO PERFORMING THE WORK.

18. CORING, TRENCHING & EXCAVATIONS:
- PRIOR TO CORING, TRENCHING, AND EXCAVATIONS, THE CONTRACOR ARE RESPONSIBLE FOR AND

IS REQUIRED TO USE AN INDEPENDENT UTILITY LOCATING SERVICE TO LOCATION ALL UTILITIES

WITHIN THE IMPACTED AREA(S) THE INDEPENDENT UTILITY LOCATING SERVICE SHALL PROVIDE

CERTIFICATION THAT IT HAS LOCATED ALL UTILITIES IN THE IMPACTED AREA(S) AND THE

CONTRACTOR MUST DEPICT ALL DISCOVERED UTILITIES ACCURATELY ON REDLINES/AS-BUILT

PLANS FOR SUBMISSION TO THE CITY OF CARLSBAD FOR REVIEW AND APPROVAL PRIOR TO

COMMENCEMENT OF CORING, TRENCHING, OR EXCAVATIONS, IN ADDITION, FOR UTILITIES

REQUIRING EXTERNAL AGENCY NOTIFICATION, COORDINATION AND APPROVALS, THE

CONTRACTOR MUST PROVIDE PROOF OF NOTIFICATION, COORDINATION AND REVIEWS BY EXTERNAL AGENCIES.

19. ALL SPECIAL/DEPUTY INSPECTION REPORTS AND TEST SHALL INCLUDE: JOB NAME AND JOB NUMBER, SITE LOCATION PLAN PAGE AND DETAILS ANY RFI AND REFERENCES.

AS-BUILT CONDITIONS

1. CONTRACTOR MUST FULLY MEASURE THE (E) STRUCTURE BEFORE FABRICATING/CUTTING ANY NEW STEEL OR WOOD MEMBERS TO BE INSTALLED INTO STRUCTURE PER THESE DRAWINGS.

2. ALL NEW STEEL AND WOOD MEMBERS MUST BE FABRICATED/CUT TO THE ACTUAL AS-BUILT

STRUCTURE DIMENSIONS IN ORDER TO ASSURE PROPER FIT-UP AND INSTALLATION AS SHOWN IN THE CONNECTION, SUPPORT AND OTHER DETAILS SHOWN ON THE DRAWINGS.

3. MODIFICATION OF THE DESIGN OR DETAILS SHOWN ON THE DRAWINGS IN ORDER TO ACCOMODATE

IMPROPER FIT-UP DUE TO LACK OF AS-BUILT MEASUREMENTS AND/OR FABRICATION ERRORS WILL NOT BE ALLOWED AND WILL BE THE BASIS FOR REJECTION OF THE INSTALLATION.

4. CONDITIONS SHOWN OR NOTES AS EXISTING ARE BASES ON THE INFORMATION AVAILABLE AT THE TIME OF THE PREPARATION OF THESE DRAWINGS. NO WARRANTY IS IMPLIED AS TO ACCURACY OF EXISTING CONDITIONS. THE CONTRACTOR SHALL REFER TO THE ORIGINAL CONSTRUCTION

DOCUMENTS (IF ANY) FOR INFORMATION REGARDING EXISTING CONSTRUCTION AND SHALL FIELD VERIFY ALL CONDITIONS. IF CONDITIONS BECOME APPARENT WHICH DIFFER FROM THE CONDITIONS

SHOWN HEREIN, THEY SHALL BE BROUGHT THE IMMEDIATE ATTENTION OF THE STRUCTURAL ENGINEER. DIMENSIONS TAKE PRECEDENCE OVER SCALE OF DRAWING, HOWEVER, SIGNIFICANT CONFLICTS SHALL BE RESOLVED AS NOTED.
30 40
60 125

CARBON STEELSTAINLESS STEEL
30 50
40 110
30 40
60 125

INSTALLATION TORQUE (FT-LB)

CARBON STEELSTAINLESS STEEL

INSTALLATION TORQUE (FT-LB)
*

POST-INSTALLED ANCHORAGE INTO CONCRETE

1. ANCHORAGE SHALL BE INSTALLED PER MANUFACTURER'S WRITTEN INSTRUCTIONS, AND SHALL COMPLY WITH ACI 318 CHAPTER 17 AND CBC.

2. ADHESIVE ANCHOR INSTALLERS SHALL BE CERTIFIED IN ACCORDANCE WITH THE ACI-CRSI ADHESIVE ANCHOR INSTALLER CERTIFICATION PROGRAM.

3. THE CONTRACTOR SHALL PREPARE A WRITTEN PROCEDURE PRIOR TO CONSTRUCTION FOR AN

INSTALLATION METHOD TO AVOID DRILLING INTO OR CONTACTING IN ANY WAY REINFORCING STEEL AND OTHER EMBEDDED ITEMS. APPROVED METHODS COULD INCLUDE PLASTIC MARKINGS FORMED

INTO THE CONCRETE SURFACE, OR USE OF GROUND PENETRATING RADAR EQUIPMENT SUCH AS HILTI FERROSCAN PS300. ANCHORS SHALL CLEAR EXISTING REBAR BY 1" MIN.

4. CONFORM WITH ICC RECOMMENDED VALUES FOR ANCHOR SPACING AND EDGE DISTANCE TO DEVELOP FULL (100%) ALLOWABLE TENSION/SHEAR LOADS LISTED IN ICC REPORTS. DO NOT USE

REDUCED SPACING AND EDGE DISTANCE UNLESS SPECIFICALLY NOTED OTHERWISE BY THE DETAILS.

5. ANCHORS SHALL BE INSTALLED ACCORDING TO THE ANCHORING SYSTEM'S SPECIFICATIONS. DO NOT DAMAGE REINFORCING STEEL OR OTHER EMBEDDED ITEMS. FILL UNUSED HOLES WITH NON-SHRINK GROUT.

6. DRILLED HOLE SHALL BE CLEANED WITH A BRUSH AND CLEAN COMPRESSED AIR IN COMPLIANCE WITH ICC ESR REQUIREMENTS.

7. CONTRACTOR SHALL DETERMINE LOCATION OF EXISTING REINFORCING STEEL PRIOR TO DRILLING

FOR ANCHORS, AND DRILL THE ANCHOR HOLES TO CLEAR THE REINFORCING STEEL PER THESE NOTES. NO REINFORCING STEEL SHALL BE NICKED, CUT OR DAMAGED IN ANY WAY. DAMAGED REINFORCING WILL BE REPLACED BY THE CONTRACTOR AT NO ADDITIONAL COST. IF THE LOCATION

OF ANCHORS MUST BE MOVED SLIGHTLY TO ACCOMMODATE THE LOCATION OF EXISTING

REINFORCING STEEL, THE CONTRACTOR SHALL PREPARED A SLIGHTLY MODIFIED DESIGN OF THE ITEM TO BE ANCHORED AND SUBMIT TO THE ENGINEER FOR APPROVAL PRIOR TO FABRICATION. THE

MODIFIED DESIGN SUGGESTED BY THE CONTRACTOR SHALL INVOLVE THE ABSOLUTE MINIMUM

RELOCATION OF ANCHORS TO MEET THE DETAILS AND REQUIREMENTS HEREIN, AND SHALL BE

BASED ON A TEMPLATE BY THE CONTRACTOR WHICH ACCURATELY PORTRAYS THE POSITION OF THE ANCHORS.

8. WHILE ANCHORING STEEL MEMBERS AGAINST CONCRETE, PROVIDE LOCK-WASHER AND NUT AT EACH ANCHOR ROD.

9. CONCRETE SCREW ANCHORS MAY BE HILTI KH-EZ S.S. 316 (ICC ESR-3027), SIMPSON TITEN HD S.S. 316 SCREW ANCHORS (ICC ESR-2713), RED HEAD TAPCON+ SCREW ANCHOR (ICC ESR-3699), OR AN EQUIVALENT PRODUCT ACCEPTABLE TO ENGINEER. AT ENDS OF LATERAL SEISMIC BRACING, USE EXPANSION BOLTS IN LIEU OF SCREW ANCHORS.

10. TEST POST-INSTALLED ANCHORS IN CONCRETE PER CBC. TENSION-TEST BOLTS TO TWICE THE

ALLOWABLE TENSION VALUE LISTED IN THE APPLICABLE ICC REPORT FOR BOLTS OF THE SAME DIAMETER. TEST 100-PERCENT OF BOLTS USED FOR STRUCTURAL APPLICATIONS. TEST 50-PERCENT

OF BOLTS USED FOR NON-STRUCTURAL APPLICATIONS SUCH AS EQUIPMENT ANCHORAGE, INCLUDING HALF OF THE BOLTS IN EACH GROUP. TEST 10-PERCENT OF BOLTS USED FOR SILL-PLATE BOLTING APPLICATIONS.

11. ALL BOLTS AND ANCHORS (INCLUDING NUTS AND WASHERS) EXPOSED TO WEATHER SHALL BE STAINLESS STEEL..

12. THE EMBEDMENT DEPTH OF POST-INSTALLED ANCHORS SPECIFIED IN THE INDIVIDUAL DRAWING DETAILS SHALL GOVERN OVER THE MINIMUM EMBEDMENTS SHOWN IN THE TABLES ABOVE. WHERE

THE INDIVIDUAL DRAWING DETAIL SPECIFIES A CERTAIN PRODUCT AND THE CONTRACTOR WISHES

TO USE AN ACCEPTABLE ALTERNATIVE PRODUCT, THE EMBEDMENT DEPTH FOR THAT ALTERNATIVE

PRODUCT SHALL BE INCREASED AS REQUIRED BEYOND THE EMBEDMENT DEPTH SHOWN FOR THE

SPECIFIED PRODUCT IN ORDER TO ACHIEVE THE SAME CAPACITIES IN SHEAR AND TENSION AS

PUBLISHED IN THE ICC-ESR REPORT FOR THE PRODUCT AND EMBEDMENT DEPTH SPECIFIED IN THE DETAIL. IF THE EMBEDMENT DEPTH OF THE ALTERNATIVE PRODUCT MUST BE INCREASED TO MATCH

THE CAPACITIES OF THE PRODUCT SPECIFIED IN THE DETAIL, THE LIMITATION ON CONCRETE

THICKNESS SPECIFIED IN THE ICC-ESR REPORT FOR THE ALTERNATIVE PRODUCT MAY NOT BE VIOLATED. THE EMBEDMENT DEPTH FOR THE ALTERNATIVE PRODUCT MAY NOT BE LESSENED BELOW THE VALUE SHOWN IN THE DETAIL..

SOILS AND FOUNDATIONS

1. ALLOWABLE FOUNDATION AND LATERAL PRESSURE TAKEN FROM 2022 CALIFORNIA BUILDING CODE TABLE 1806.2 (NO SOILS REPORT).

2. SOIL BEARING CAPACITIES AND RECOMMENDATIONS:

A. ALLOWABLE SOIL BEARING PRESSURES: 1,500 PSF

3. EXCAVATION AND COMPACTION SHALL BE APPROVED PRIOR TO PLACING ANY REINFORCING STEEL AND CONCRETE BY A SPECIAL INSPECTOR APPROVED BY CITY OF CARLSBAD. THE IOR TO SUBMIT A LETTER OF COMPLIANCE TO OWNER.

4. ALL ABANDONED FOOTINGS, UTILITIES, ETC., THAT INTERFERE WITH NEW CONSTRUCTION SHALL BE REMOVED.

DRAWING INDEX
S-001GENERAL NOTES
S-002GENERAL NOTES
S-201FOUNDATION PLAN
S-501SECTION AND DETAILS

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 50% CONSTRUCTION DOCUMENTS6/21/24-
2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.08
CK
EL
VM
NAS
NGI
AL
ON
SI
EL
E
RP
O
EFM.

TRE
DE
S
EER
S
IA
OR
FI
AL
L
RA
UT
N
R
GER I
TE
OF C
RTS
U
SAT
C
No. 3930
S
N
AH
AMI
90% CONSTRUCTION DOCUMENTS7/23/24
DATE SIGNED: 04-01-2025
PLAN CHECK SUBMITTAL10/02/24
PLAN CHECK CORRECTIONS04/01/25
-
-
1 GENERAL NOTE
S-001
I
~
!
I I
!
I I
I
a :c
E
'D
&
J
l
I s
8 '
I ..
" 5
I
5 i
!
I
D
2 3i
! ~~-------1 ma~~ IB i T
!DIAL = ~ if BEFORE TWO WORKING
11, YOU DIG DAYS BEFORE 11-,, YOU DIG
I
TOLL FREE ---1-800-227-2600

A PUBLIC SERVICE BY

UNDERGROUND SERVICE ALERT
I
I
I
I
I
I
I I
I
I I
I I
I I
I I
I
I
I
i--==+~=+~============-_-_-_=::=::7=+::~=+::~=+::~t~:::j(siiffill CITY OF CARI.SHAD IISILE,JI I-L.!!...J ! PUBLIC WORKS DEPARTMENT _ 22 E==t==i==================~==l==t==:l=::j lll'RIMIIEtlT PUNS FIii:
''-
~===t~~~t:::::::::==============~::::E::3E:::t::j I APPROVED: JOHN MAASHOFF RCE 81909 EXP. 9/J0/251 DA1E N1W. = MlRKS MANAGER. aTY OF CARLSBAD DAlE=!
EN!ll FR a, IIDRIC REVISION DESCRIPTION :: AFF= ~ AFF= = 13 ~ --I PRO.ECT NO. II DRAWING NO.I
CBC 2022 TABLE 1705.3: REQUIRED SPECIAL INSPECTIONS AND TESTS OF CONCRETE CONSTRUCTION

4. INSPECT ANCHORS POST-INSTALLED IN HARDENED
CONCRETE MEMBERSb.
a. ADHESIVE ANCHORS INSTALLED IN HORIZONTAL OR

UPWARDLY INCLINED ORIENTATIONS TO RESIST
SUSTAINED TENSION LOADSc.
b. MECHANICAL ANCHORS AND ADHESIVE NOT DEFINED IN

4.a.

6. PRIOR TO AND DURING CONCRETE PLACEMENT, FABRICATE

SPECIMENS FOR STRENGTH TESTS, PERFORM SLUMP AND

AIR CONTENT TESTS, AND DETERMINE THE TEMPERATURE
OF THE CONCRETE.

7. INSPECT CONCRETE FOR PROPER APPLICATION
TECHNIQUES.

8. VERIFY MAINTENANCE OF SPECIFIED CURING
TEMPERATURE AND TECHNIQUES.
-X
-X
- X
- X
X
X
AWS D1.4,
ACI 318: Ch. 19,

26.4, 26.13.3.2
ACI 318: 26. 3, 26.13,
ACI 506: 3.4
ACI 318: 26.5.3-26.5.5,

26.13.3.3 TYPE

CONTINUOUS

SPECIAL

INSPECTION

PERIODIC

SPECIAL

INSPECTION

REFERENCE
STANDARD a
CBC

REFERENCE

10.INSPECT ERECTION OF PRECAST CONCRETE MEMBERS.

X
X
-
-
ACI 318: 26.10.2,

26.13.1, 26.13.3.21705A.3.4
-

3. INSPECT ANCHORS CAST IN CONCRETE.

9. INSPECT PRESTRESSED CONCRETE FOR:
a. APPLICATION OF PRESTRESSING FORCES, AND
b. GROUTING OF BONDED PRESTRESSING TENDONDS.

X -
X
X
X - 5. VERIFY USE OF REQUIRED DESIGN MIX.

ACI 318: Ch. 26.9,

26.13.1, 26.13.3.3X
--
X

14. INSPECT FORMWORK FOR SHAPE, LOCATION AND
DIMENSIONS OF THE CONCRETE MEMBER BEING FORMED.
a. WHERE APPLICABLE, SEE ALSO CBC SECTION 1705.13.
b. SPECIFIC REQUIREMENTS FOR SPECIAL INSPECTION SHALL BE INCLUDED IN THE RESEARCH REPORT FOR THE ANCHOR ISSUED BY AN APPROVED SOURCE IN ACCORDANCE WITH 17.8.2. IN ACI318 OR OTHER QUALIFICATIONS PROCEDURES. WHERE SPECIFIC REQUIREMENTS ARE

NOT PROVIDED, SPECIAL INSPECTION REQUIREMENTS SHALL BE SPECIFIED BY THE REGISTERED DESIGN PROFESSIONAL AND SHALL BE APPROVED BY THE BUILDING OFFICIAL PRIOR TO THE COMMENCEMENT OF THE WORK. c. INSTALLATION OF ALL ADHESIVE ANCHORS IN HORIZONTAL AND UPWARDLY INCLINED POSITION SHALL BE PERFORMED BY AN ACI/CRSI CERTIFIED ADHESIVE ANCHOR INSTALLER, EXCEPT WHERE THE FACTORED DESIGN TENSION ON THE ANCHORS IS LESS THAN 100 POUNDS

AND THOSE ANCHORS ARE CLEARLY NOTED ON THE APPROVED CONSTRUCTION DOCUMENTS OR WHERE THE ANCHORS ARE SHEAR DOWELS ACROSS COLD JOINTS IN SLAB ON GRADE WHERE THE SLAB IS NOT A PART OF THE LATERAL FORCE-RESISTING SYSTEM.

X -
-
ACI 318: 26.13.1.3
ACI 318: 26.13.1.3X
-
-

1. INSPECT AND TEST REINFORCEMENT, INCLUDING
PRESTRESSING TENDONS, AND VERIFY PLACEMENT.
a. REINFORCEMENT IN SPECIAL MOMENT FRAMES,

BOUNDARY ELEMENTS OF SPECIAL STRUCTURAL WALLS
AND COUPLING BEAMS.
b. ALL OTHER REINFORCEMENT
ACI 318: Ch. 20, 25.2,

25.3, 25.5.1,

26.6.1–26.6.3, 26.13.1,

26.13.3.2, 26.13.3.3
X
1705A.3.9, 1908A.1,
1910A.2, 1910A.3;
[DSA-SS/CC] 1909.2.4,
1909.2.5, 1909.4.1

2. REINFORCING BAR WELDING:
a. VERIFY WELDABILITY OF REINFORCING BARS OTHER THAN ASTM A706;
b. INSPECT SINGLE-PASS FILLET WELDS, MAXIMUM 516"; NOT DEFINED IN 2.d OR 2.e.
c. INSPECT ALL OTHER WELDS.
d. REINFORCING STEEL RESISTING FLEXURAL AND AXIAL FORCES IN

INTERMEDIATE AND SPECIAL MOMENT FRAMES, AND BOUNDARY

ELEMENTS AND COUPLING BEAMS OF SPECIAL STRUCTURAL WALLS OF CONCRETE AND SHEAR REINFORCEMENT.
e. SHEAR REINFORCEMENT.

X
-
-
X
-
-
ACI 318: 18.2.8,

25.5.7, 26.6.4,

26.13.1.4, 26.13.3.2,

26.13.3.3 1705A.3.1,
1903A.8
ACI 318: 17.8.2,

26.7.2, 26.8.2,

26.13.1, 26.13.3.3
-
-
ACI 318: 17.8.2.4

26.7.2, 26.13.1,

26.13.3.2 ACI 318: 17.8.2 26.7.2,

26.13.1, 26.13.3.3
1705A.3.8, 1910A.5,
[DSA-SS/CC] 1909.2.7
1705A.3.8, 1910A.5,
[DSA-SS/CC] 1909.2.7
1903A.5, 1903A.6,
1903A.7, 1904A.1,
1904A.2, 1910A.1,
[OSHPD 1 & 4] 1908A.1,
[DSA-SS/CC] 1909.2.1,
1909.2.2, 1909.2.3
ASTM C31,
ASTM C172,
ACI 318: 26.4, 26.5,

26.12 1705A.3.5, 1705A.3.6,
1705A.3.9, 1905A.1.17,
[DSA-SS/CC] 1909.3.9
1705A.3.9, 1905A.1.15,
1905A.1.16,
[DSA-SS/CC] 1909.3.7,
1909.3.8

11.FOR PRECAST CONCRETE DIAPHRAGM CONNECTIONS OR

REINFORCEMENT AT JOINTS CLASSIFIED AS MODERATE OR

HIGH DEFORMABILITY ELEMENTS (MDE OR HDE) IN

STRUCTURES ASSIGNED TO SEISMIC DESIGN CATE-GORY D,

E OR F, INSPECT SUCH CONNECTIONS AND REINFORCEMENT
IN THE FIELD FOR:
a. INSTALLATION OF THE EMBEDDED PARTS
b. COMPLETION OF THE CONTINUITY OF REINFORCEMENT
ACROSS JOINTS.
c. COMPLETION OF CONNECTIONS IN THE FIELD.

12. INSPECT INSTALLATION TOLERANCES OF PRECAST

CONCRETE DIAPHRAGM CONNECTIONS FOR COMPLIANCE
WITH ACI 550.5.

13. VERIFY IN-SITU CONCRETE STRENGTH, PRIOR TO STRESSING OF

TENDONS IN POST-TENSIONED CONCRETE AND PRIOR TO REMOVAL OF SHORES AND FORMS FROM BEAMS AND STRUCTURAL SLABS.

ACI 318: 26.10.2,

26.11.2, 26.13.3.3 -
-
X
XACI 318: 26.11.1.2(b),

26.13.3.3 ACI 550.5
1908A.3,
[DSA-SS/CC] 1909.4.3
FOR SI: 1 inch = 25.4 mm.
-
X
X
X
-
-
-
-
-

ABBREVIATIONS
@AT
&AND
A.B.ANCHOR BOLT
ABV.ABOVE
ADD'L. (ADDL.) ADDITIONAL
ADJ.ADJACENT
ALT.ALTERNATE
ALUM.ALUMINUM
APPRX. (APPROX.) APPROXIMATE(LY)
ARCH.ARCHITECT(URAL)
BLDG.BUILDING
BLKG.BLOCKING
BLW.BELOW
BM.BEAM
B.N.BOUNDARY NAILING
BNDRY.BOUNDARY
B.O.C.BOTTOM OF CONCRETE
B.O.F.BOTTOM OF FOOTING
BOT. (B)BOTTOM
BRCG.BRACING
BRDG.BRIDGE (ING)
BRG.BEARING
BTWN.BETWEEN
CAMB. (C)CAMBER(ED)

CBCCALIFORNIA BUILDING CODE
CANT.CANTILEVER(ED)
C.F.CUBIC FEET (FOOT)
C.I.P.CAST-IN-PLACE
C.I.D.H.CAST-IN-DRILLED HOLE
C.J.CONTROL JOINT;

CONSTRUCTION JOINT
C.L. (
℄)CENTER LINE
CLG.CEILING
CLR.CLEAR
COL.COLUMN
CONC.CONCRETE
CONN.CONNECTION
CONST.CONSTRUCTION
CONT.CONTINUOUS
C.P.COMPLETE-

PENETRATION
CTSK.COUNTERSINK
CTR.CENTER(ED)
C.P.CUBIC YARD
dd PENNY NAIL

DBADEFORMED BAR ANCHOR
DBL.DOUBLE
DEPT.DEPARTMENT
D.F.DOUGLAS FIR
DIA. (Ø)DIAMETER
DIAG.DIAGONAL
DIAPH.DIAPHRAGM
DIM.DIMENSION
DN.DOWN

DODITTO (REPEAT)
DWG. (DWGS.) DRAWING(S)
DWL.DOWEL
EA.EACH
E.F.EACH FACE
E.J.EXPANSION JOINT
EL.ELEVATION
ELEC.ELECTRICAL
ELEV.ELEVATOR
EMB.EMBED(MENT)
E.N.EDGE NAIL
ENG.ENGINEER
EQ.EQUAL
EQPT.EQUIPMENT
EQUIV.EQUIVALENT
EXP.EXPANSION
EXIST. (E)EXISTING
EXT.EXTERIOR
FDN.FOUNDATION
FIN.FINISH(ED)
FLR.FLOOR
F.N.FIELD NAIL; FACE NAIL
F.O.C.FACE OF CONCRETE
F.O.M.FACE OF MASONRY
F.O.S.FACE OF STUD
F.O.W.FACE OF WALL
F.P.FULL PENETRATION

FRPFIBER REINFORCED POLYMER
F.S.FAR SIDE
FT. (')FOOT (FEET)
FTG.FOOTING
F.V.FIELD VERIFY
GA.GAUGE
GALV.GALVANIZE(D)
GLB.GLUED LAMINATED BEAM
(GLU-LAM)
GRD.GRADE
GYP.GYPSUM
HD.HOLDOWN; HAND
HDR.HEADER
HGR.HANGER
HORIZ.(H) HORIZONTAL
H.S.HEADED STUD
H.S.B.HIGH STRENGTH BOLT
HT.HEIGHT
I.D.INSIDE DIAMETER
IN.(") INCH(ES)
INFO.INFORMATION
JST.JOIST
JT.JOINT
KKIPS; 1000
K.P.KING POST
LAT.LATERAL
L.B.LAG BOLT
LB (#)POUND
L.F.LINEAL FEET (FOOT)

LLHLONG LEG HORIZONTAL

LLVLONG LEG VERTICAL
LT.WT.LIGHT WEIGHT
MAX.MAXIMUM
M.B.MACHINE BOLT
MECH.MECHANICAL
M.E.P.MECHANICAL, ELECTRICAL

AND PLUMBING
MEZZ.MEZZANINE
MFR.MANUFACTURER
MIN.MINIMUM
MISC.MISCELLANEOUS
MTL.METAL
(N)NEW
N.O.(#) NUMBER
N.S.NEAR SIDE
N.T.S.NOT TO SCALE
O/C (O.C.)ON CENTER
O.D.OUTSIDE DIAMETER
O.H.OPPOSITE HAND
OPNG.OPENING
OPP.OPPOSITE
ORTH.ORTHOGONAL
O.W.J.OPEN WEB JOIST

PCPILE CAP
PCFPOUNDS PER CU.FT.

PL.PLATE
PLYWD.PLYWOOD
P.P.PARTIAL-

PENETRATION
P.S.F.POUNDS PER SQUARE FOOT
P.S.I.POUNDS PER SQUARE INCH

PTPRETENSIONED
P.T.PRESSURE TREATED
QTY.QUANTITY
RAD.(R) RADIUS

RBSREDUCED BEAM SECTION
REF.REFERENCE
REINF.REINFORCEMENT (ING)
REQ'D. (REQD.) REQUIRED
RF.ROOF
R.O.ROUGH OPENING
S.A.D.SEE ARCHITECTURAL

DRAWINGS

SCSLIP-CRITICAL
S.C.D.SEE CIVIL DRAWINGS
SCH.SCHEDULE
SEP.SEPARATION
SHT.SHEET
SIM.SIMILAR
SKW.SKEW(ED)
S..G.SLAB-ON-GRADE
SPEC.SPECIFICATION
SQ.SQUARE

STSNUG-TIGHTENED
STD.STANDARD
STAGG.STAGGER(ED)
STIFF.STIFFENER
STIR.STIRRUP
STL.STEEL
STRUC(T).STRUCTURAL
SUSP.SUSPENDED
SYMM.SYMMETRICAL

T&BTOP AND BOTTOM

T&GTONGUE AND GROOVE
TEMP.TEMPORARY
THK.THICK(NESS)
T.N.TOE NAIL
T.O.TOP OF
T.O.C.TOP OF CONCRETE
T.O.S.TOP OF STEEL;

TOP OF SHEATHING
T.O.W.TOP OF WALL
TRANS.TRANSVERSE
T.S.G.TAPERED STEEL GIRDER
TYP.TYPICAL
U.N.O.UNLESS OTHERWISE NOTED
UTL.UTILITY
VERT. (V) VERTICAL
V.I.F.VERIFY IN FIELD
W/WITH
(W)WIDE; WIDTH
WD.WOOD
W.P.WORK POINT
WT.WEIGHT
W.W.F.WELDED WIRE FABRIC

X-STGEXTRA STRONG

XX-STGDOUBLE EXTRA STRONG

STRUCTURAL OBSERVATION PROGRAM

1. 2.

3. 4.

5. 6.

7. 8.

9. 10.

STRUCTURAL OBSERVATION IS REQUIRED FOR THE STRUCTURAL SYSTEM IN ACCORDANCE WITH THE CBC 2022, SECTION 1704.6. STRUCTURAL OBSERVATION IS THE VISUAL OBSERVATION AT THE

CONSTRUCTION SITE OF THE ELEMENTS AND CONNECTIONS OF THE STRUCTURAL SYSTEM AT

SIGNIFICANT CONSTRUCTION STAGES, AND THE COMPLETE STRUCTURE FOR GENERAL CONFORMANCE TO THE APPROVED PLANS AND SPECIFICATIONS. STRUCTURAL OBSERVATION DOES NOT INCLUDE OR WAIVE THE RESPONSIBILITY FOR THE INSPECTIONS IN SECTION 110 OR THE SPECIAL INSPECTIONS IN 1705 OR OTHER SECTIONS OF THIS CODE.

THE OWNER SHALL EMPLOY A STATE OF CALIFORNIA REGISTERED CIVIL OR STRUCTURAL ENGINEER OR LICENSED ARCHITECT TO PERFORM THE STRUCTURAL OBSERVATION. THE CITY OF

CARLSBAD DEPARTMENT OF BUILDING AND SAFETY REQUIRES THE USE OF THE ENGINEER

OR ARCHITECT, OR HIS/HER DESIGNEE RESPONSIBLE FOR THE STRUCTURAL DESIGN WHO ARE INDEPENDENT OF THE CONTRACTOR.

NAME OF SE: RAMI ELHASAN

THE STRUCTURAL OBSERVER SHALL PROVIDE EVIDENCE OF EMPLOYMENT BY THE OWNER OR THE OWNER'S REPRESENTATIVE. A LETTER FROM THE OWNER, THE OWNER'S REPRESENTATIVE,

OR A COPY OF THE AGREEMENT FOR SERVICES SHALL BE SENT TO THE BUILDING INSPECTOR BEFORE THE FIRST SITE VISIT.

THE OWNER OR OWNER'S REPRESENTATIVE SHALL COORDINATE AND CALL FOR A MEETING

BETWEEN THE ENGINEER OR ARCHITECT RESPONSIBLE FOR THE STRUCTURAL DESIGN,

STRUCTURAL OBSERVER, CONTRACTOR, AFFECTED SUBCONTRACTORS AND DEPUTY INSPECTORS. THE PURPOSE OF THE MEETING SHALL BE TO IDENTIFY THE MAJOR STRUCTURAL

ELEMENTS AND CONNECTIONS THAT AFFECT THE VERTICAL AND LATERAL LOAD SYSTEMS OF THE STRUCTURE AND TO REVIEW SCHEDULING OF THE REQUIRED OBSERVATIONS. A RECORD OF THE

MEETING SHALL BE INCLUDED IN THE FIRST OBSERVATION REPORT SUBMITTED TO THE BUILDING INSPECTOR.

THE STRUCTURAL OBSERVER SHALL PERFORM SITE VISITS AT THOSE STEPS IN THE PROGRESS

OF THE WORK THAT ALLOW FOR CORRECTION OF DEFICIENCIES WITHOUT SUBSTANTIAL EFFORT OR UNCOVERING OF THE WORK INVOLVED. AT A MINIMUM, THE LISTED SIGNIFICANT CONSTRUCTION STAGES ON THE "STRUCTURAL OBSERVATION/SIGNIFICANT CONSTRUCTION STAGES" FORM REQUIRE A SITE VISIT AND AN OBSERVATION REPORT FROM THE STRUCTURAL OBSERVER.

THE STRUCTURAL OBSERVER SHALL PREPARE A REPORT OF THE "STRUCTURAL OBSERVATION REPORT FORM" FOR EACH SIGNIFICANT STAGE OF CONSTRUCTION OBSERVED. THE ORIGINAL OF

THE STRUCTURAL OBSERVATION REPORT SHALL BE SENT TO THE BUILDING INSPECTOR'S OFFICE

AND SHALL BE SIGNED AND SEALED (WET STAMP) BY THE RESPONSIBLE STRUCTURAL OBSERVER OF RECORD. ONE COPY OF THE OBSERVATION REPORT SHALL BE ATTACHED TO THE APPROVED PLANS. THE COPY ATTACHED TO THE PLANS SHALL BE SIGNED AND SEALED (WET STAMP) BY THE RESPONSIBLE STRUCTURAL OBSERVER OR THEIR DESIGNEE. COPIES OF THE REPORT SHALL ALSO BE GIVEN TO THE OWNER, CONTRACTOR, AND DEPUTY INSPECTOR. ANY DEFICIENCY

NOTED ON THE OBSERVATION REPORT WILL BECOME THE RESPONSIBILITY OF THE STRUCTURAL

ENGINEER OR ARCHITECT OF RECORD TO VERIFY ITS COMPLETION BY THE STRUCTURAL OBSERVER.

A FINAL OBSERVATION REPORT MUST BE SUBMITTED WHICH SHOWS THAT ALL OBSERVED

DEFICIENCIES WERE RESOLVED AND STRUCTURAL SYSTEM GENERALLY CONFORMS WITH THE APPROVED PLANS AND SPECIFICATIONS. THE CITY OF CARLSBAD DEPARTMENT OF

BUILDING SAFETY WILL NOT ACCEPT THE STRUCTURAL WORK WITHOUT THE FINAL OBSERVATION

REPORT AND THE CORRECTION OF SPECIFIC DEFICIENCIES NOTED DURING NORMAL BUILDING INSPECTION.

THE STRUCTURAL OBSERVER OF RECORD SHALL PROVIDE THE ORIGINAL STAMPED AND SIGNED "STRUCTURAL OBSERVATION REPORT FORM" TO THE THE CITY OF CARLSBAD DEPARTMENT OF BUILDING AND SAFETY BUILDING INSPECTOR.

THE ENGINEER OR ARCHITECT OF RECORD SHALL DEVELOP ALL CHANGES RELATING TO THE STRUCTURAL SYSTEMS. THE BUILDING DEPARTMENT SHALL REVIEW AND APPROVE ALL CHANGES

TO THE APPROVED PLANS AND APPROVE ALL CHANGES TO THE APPROVED PLANS AND SPECIFICATIONS.

AT THE CONCLUSION OF THE WORK INCLUDED IN THE PERMIT, THE STRUCTURAL OBSERVER OF

RECORD SHALL SUBMIT TO THE BUILDING OFFICIAL A WRITTEN STATEMENT THAT THE SITE VISITS

HAVE BEEN MADE AND IDENTIFY ANY REPORTED DEFICIENCIES THAT, TO THE BEST OF THE STRUCTURAL OBSERVER'S KNOWLEDGE HAVE NOT BEEN RESOLVED.

CONSTRUCTION STAGE ELEMENTS / CONNECTIONS TO BE OBSERVED; A. SLAB ON GRADE: DEPTH OF SLAB ON GRADE; REINFORCING PLACEMENT, SIZE AND GRADE OF REINFORCING STEEL.

NOTE:

1. THE SPECIAL INSPECTION SHALL BE PERFORMED BY CERTIFIED DEPUTY INSPECTORS.

2. THE TEST OF SOIL AND CONCRETE SHALL BE PERPORMED BY AN APPROVED LABORATORY.

3. THE CERTIFIED DEPUTY INSPECTORS AND THE APPROVED LABORATORY SHALL BE HIRED BY THE OWNER OR THE PROJECT CONSULTANT AND NOT THE CONTRACTOR.

1. STRUCTURAL TESTS AND INSPECTIONS SHALL BE ACCORDING TO 2022 CALIFORNIA BUILDING CODE AND, PROJECT SPECIFICATIONS.

2. THE CONTRACTOR SHALL COORDINATE THE WORK AND SCHEDULE WITH THE OWNERS

INSPECTOR TO ASSURE THAT ADEQUATE NOTICE IS GIVEN FOR INSPECTION TO OCCUR WHILE MAINTAINING PROJECT SCHEDULE.

3. CONTINUOUS OR PERIODIC INSPECTION BY THE PROJECT OR SPECIAL INSPECTOR HIRED BY THE OWNER ARE REQUIRED FOR THE FOLLOWING TYPES OF WORK WHERE OCCURS:

A. POST-INSTALLED ANCHOR IN CONCRETE
B. EPOXY ANCHOR IN CONCRETE

4. THE TESTING TORQUES FOR POST-INSTALLED ANCHORS SHALL BE BASED ON THE

MANUFACTURER'S RECOMMENDED INSTALLATION TORQUE AS APPROVED IN AN ICC-ES EVALUATION REPORT UNLESS OTHERWISE NOTED. (CONFORM TO REQUIREMENTS OF CBC 2022, SECTION 1901.3.4.4).

5. THE TESTING FORCES FOR POST-INSTALLED ADHESIVE ANCHORS SHALL BE BASED ON ONE AND A QUARTER (1¼) TIMES THE MAXIMUM DESIGN STRENGTH OF ANCHORS AS PROVIDED IN

AN APPROVED TEST REPORT USING CRITERIA ADOPTED IN THIS CODE OR DETERMINED IN ACCORDANCE WITH APPENDIX D OF ACI 318. TENSION TEST LOAD NEED NOT EXCEED 80 PERCENT OF THE NOMINAL YIELD STRENGTH OF THE ANCHOR ELEMENT (=0.8Asefya). (CONFORM TO REQUIREMENTS OF CBC 2022, SECTION 1901.3.4.4)

6. ACCEPTANCE CRITERIA FOR POST INSTALLED ANCHORS SHALL BE BASED ON ICC-ESR OR MANUFACTURER'S WRITTEN INSTRUCTION. FIELD TEST SHALL SATISFY THE MINIMUM REQUIREMENTS PER CBC 2022, SECTION 1901.3.4.3 AND 1901.3.4.5.

7. ALL SPECIAL/DEPUTY INSPECTION REPORTS AND TESTS SHALL INCLUDE: JOB NAME AND JOB NUMBER, SITE LOCATION, PLAN PAGE AND DETAILS, ANY RFI, AND CODE REFERENCES.

STRUCTURAL TEST AND INSPECTION

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 50% CONSTRUCTION DOCUMENTS6/21/24-
2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.08
CK
EL
VM
NAS
NGI
AL
ON
SI
EL
E
RP
O
EFM.

TRE
DE
S
EER
S
IA
OR
FI
AL
L
RA
UT
N
R
GER I
TE
OF C
RTS
U
SAT
C
No. 3930
S
N
AH
AMI
90% CONSTRUCTION DOCUMENTS7/23/24
DATE SIGNED: 04-01-2025
PLAN CHECK SUBMITTAL10/02/24
PLAN CHECK CORRECTIONS04/01/25
-
-
1 GENERAL NOTE
S-002
I
r
I
I
I I
J
s
I
I
I
I
a :i::

E ...
&
.I l
I :
'
',
OI
i i ..
6 I
• 6
i
§
J,
1 ..
... [:;:] I CITY OF CARLSBAD II SHEElS I
, PUBLIC WORKS DEPARTMENT 22
M'IIIMIIENTPUNSFIII:

IDJIO~llDIBiT ~
= ~

DIAL TWO WORKING

BEFORE DAYS BEFORE

YOU DIG YOU DIG
*
!I\
*
TO LL FREE 1-800-227-2600
'"

A PUBLIC SERVICE BY
!APPROVED: JOHN MMSHOFF RCE 81909 EXP. 9/30/251

UNDERGROUND SERVICE ALERT
DA1E N1IAL
PIIIIJC WllRKS MANAGER. a1Y CF CARLSBAD DAlE
D• FF r, MRC REVISION DESCRIPTION
DA1E N1IAL DA1E N1IAL 1=~ II ~CT NO. 11DRA•G NO.I
01IER ll'fWNIL CIIY APPROVAL
1 1/2"= 1'-0" CHILLER YARD NEW PLAN
(E) WALL
12 S-501
CHILLER CH-1B MAX

OPERATED WEIGHT
3,000 LBS SEE
(E) WALL
(E) WALL
15'-4"36'-0"
DCB
1 1
21'-0"
8 S-501
3"
(E) 8" CMU WALL W/
#5 @ 24" O.C. EA.

WAY TO REMAIN TYP.
7 S-501
(E) PUMP TO REMAIN
(E) CHEMICAL FEEDERS

TO REMAIN
(E) BOILER TO REMAIN
(E) EXPANSION TANK

TO REMAIN
(E) PUMP TO
REMAIN
(E) CHILLER YARD
(E) 4" CONCRETE PAD W/ #4
@ 18" O.C. EA WAY
9 1/2"
NOTE:
- CONTRACTOR TO VERIFY ALL
DIMENSIONS W/ MEP & ARCH. DWG.

PRIOR TO ANY CONSTRUCTION.
1B
S-501
(E) 4" S.O.G. W/ #4 @
18" O.C. EA WAY
(E) WEEP HOLE TO
REMAIN TYP.
12 S-501
TYP
1A
S-501
9 1/2"
10 S-501

DEEP TRENCH PER PLUMBING

DRAWING
3"Ø DRAIN PIPE. SEE MEP/CIVIL

FOR LOCATION
(E) 14" WIDE CONT'
FOOTING. TYP.

SIM'
10 S-501
(E) DRIVE WAY
5 S-501
11 S-501
4 S-501
12 S-501
CHILLER CH-1A MAX

OPERATED WEIGHT
3,000 LBS SEE
(E) GENERATOR SET
11"±7'-5"
8"8"
8"

SEE MEP DWG
4"
4"Ø CHWR AND ANCHOR PER MEP DWG.
4"Ø CHWS AND ANCHOR PER MEP DWG.

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 50% CONSTRUCTION DOCUMENTS6/21/24-
2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.08
CK
EL
VM
NAS
NGI
AL
ON
SI
EL
E
RP
O
EFM.

TRE
DE
S
EER
S
IA
OR
FI
AL
L
RA
UT
N
R
GER I
TE
OF C
RTS
U
SAT
C
No. 3930
S
N
AH
AMI
90% CONSTRUCTION DOCUMENTS7/23/24
DATE SIGNED: 04-01-2025
PLAN CHECK SUBMITTAL10/02/24
PLAN CHECK CORRECTIONS04/01/25
-
-
1 FOUNDATION PLAN
S-201
TRUE
NORTHN
2 N.T.S. TYP. BENDS AT REINF.

DDDD
12d
D
D
135°
6d
(3" MIN.)
4d
(212" MIN.)
135° STD. HOOK
6 1
180° STD.

HOOK
LEGEND:
d - BAR DIAMETER
D - 6d FOR #3 THROUGH #8
D - 8d FOR #9 THROUGH #11
90° STD.

HOOK
(E) CONC.

SLAB-ON-GRADE
CONC.

SLAB-ON-GRADE

PER PLAN
4" TYP
EQ.EQ.

HILTI HIT-RE 500 V3
TYP. (ICC ESR-3814)
4 N.T.S. TYP. CONC. S.O.G. TO (E) CONC. S.O.G.
#4 DOWEL @ 18" O.C. TYP.2'-0"

PRESATURATION TO
110% OF OPTIMUM

MOISTURE CONTENT
4" THK. (MIN.) BASE OF
12" CLEAN AGGREGATE
15 MIL VAPOR BARRIER W/

JOINTS LAPPED NOT LESS
THAN 6" & SEALED W/ MFR.

SEAM TAPE
(3) #4 REBAR
24" MIN.

STAGGER

LAP SPLICE
SEE SCH.

LAP SPLICE
SEE SCH.

B
db
B

DIAGRAM AT STAGGERED SPLICES

BAR SPACING DIAGRAM

SPLICE OR

LAPPING BAR
A
NOTES:

1. THE SCHEDULED LAP SPLICE LENGTHS ARE FOR EITHER OF THE FOLLOWING CASES:

1.1 CLEAR SPACING OF BARS BEING DEVELOPED OR SPLICED NOT LESS THAN (2db), AND CLEAR COVER NOT LESS THAN (db).

1.2 CLEAR SPACING OF BARS BEING DEVELOPED OR SPLICED SHALL NOT BE LESS THAN (db), CLEAR COVER NOT LESS THAN (db), AND STIRRUPS/TIES THROUGHOUT LAP SPLICE NOT LESS THAN CODE PRESCRIBED MAXIMUM.

2. MULTIPLY LAP SPLICE LENGTHS BY 1.5 FOR CASES NOT MEETING THE CONDITIONS AS DESCRIBED IN NOTE 1.

3. USE CLASS "B" SPLICES FOR VERTICAL & HORIZONTAL BARS TYP. U.O.N.

4. TOP BARS ARE HORIZONTAL BARS PLACED SO THAT 12-INCHES OR MORE OF CONCRETE IS CAST IN THE MEMBER BELOW THE BAR.

5. VALUES SHOWN ARE FOR NORMAL WEIGHT CONCRETE. IF LIGHTWEIGHT CONCRETE, MULTIPY LAP SPLICE LENGTHS BY 1.3.
(REFER TO NOTE 2 FOR ANY ADDITIONAL INCREASES IN LAP SPLICE LENGTHS).

6. VALUES SHOWN ARE FOR UNCOATED GRADE 60 REINFORCEMENT. 3 N.T.S. TYP. BENDS AT REINF.

A A
#10
#5
#9
#8
#7
#6

BAR SIZE
#3
#4
TOP

BAR BASICBASIC

CLASS OF
LAP SPLICECLASS "B"
fc' = 4,000 PSI
fy = 60,000 PSI
CLASS "A"
TOP
BAR

STRENGTH
15"
19"
24"
29"
42"
48"
54"
61"
20"
25"
31"
38"
55"
62"
70"
79"
20"
25"
31"
38"
55"
62"
70"
79"
26"
33"
41"
50"
71"
81"
91"
103"
8"
MIN.
6"
3"
CLR.
3"
CLR.

CONC.

SLAB-ON-GRADE
1 1 TYP. REINF.
#4 CONT.

FINISH GRADE

SUBGRADE
5 1"=1'-0" TYP. EDGE OF CONC. SLAB-ON-GRADE

DRAINAGE PIPE

PER PLAN

ROUGHEN SURFACE TO
1/4" AMPLITUDE AND

PROVIDE BONDING
AGENT. TYP.
1 N.T.S. CONCRETE PAD EXTENSION
2" EFF. EMBED
#4 HORIZ. DOWEL W/ 90° HOOK @ 18"
O.C. W/ HILTI HIT RE 500 V3 EPOXY
INSTALL PER ICC ESR 3814
2" CLR
TYP
(E) DOWEL

WHERE OCCURS
(E) SLAB ON GRADE PER PLAN
(E) CONC. PAD

PER PLAN
2"
±6" F.V.

A - A
(E) REBAR TO REMAIN
#4 HOR. DOWEL W/ 90° HOOK
W/ HILTI HIT RE 500 V3
INSTALL PER ICC ESR 3814
#4 "U" DOWEL @ 18" O.C. W/
HILTI HIT RE 500 V3 INSTALL
PER ICC ESR 3814
(E) DAMAGE AREA
(E) CONC. PAD

PER PLAN
7 N.T.S. NEW S.O.G. TO (E) FOOTING
14" F.V.
(E) 8" CMU WALL TO REMAIN
(E) #5 @ 24" O.C. EA. WAY
S.O.G. PER PLAN
(E) CONC. FOOTING PER ELEV.

NOTE:
·CONTRACTOR TO LOCATE

EXISTING REBAR/DOWEL THAT

NEED TO BE PROTECTED IN

PLACE PRIOR TO ANY
DEMOLITION.
8 N.T.S. NEW S.O.G. TO (E) FOOTING
14" F.V.

SLOPE PER ARCH'L.S.O.G. PER PLAN

SLAB EDGE PER
5 - (E) FOOTING

TO REMAIN
NOTE:
·CONTRACTOR TO LOCATE EXISTING REBAR/DOWEL THAT NEED
TO BE PROTECTED IN PLACE PRIOR TO ANY DEMOLITION.
(E) 8" CMU WALL

TO REMAIN
(E) #5 @ 24" O.C.

EA. WAY
RE-SURFACE T.O. FOOTING TO
MATCH NEW SLOPE (14" MAX.)
(E) #4 DOWEL @ 24" O.C.

TO REMAIN
12"
24"
PORTION OF (E) #4 SLAB

REBAR TO BE REMOVED
3" MIN.
4" MAX.
5'-0"
12" MIN6"
6" MIN3" MIN. (E) #4 DOWEL
@18" O.C. EA WAY
(E) #4 DOWEL
@18" O.C. EA WAY
(E) 4" S.O.G.

PER PLAN
B - B
HILTI HIT RE 500 V3 EPOXY
INSTALL PER ICC ESR 3814
2 3 4" EFF
EMBED
#4 DOWEL @ 18" O.C. EA
WAY W/ 90° HOOD W/ HILTI
HIT RE 500 V3 EPOXY.

INSTALL PER ICC ESR 3814
#4 @ 18" O.C. EA WAY
4" CONC. EXTENSION
PAD PER PLAN (E) CONC. PAD PER PLAN
SLOPE PERCIVIL/ARCH'L.
8"
RE-SURFACE T.O. FOOTING TO
MATCH NEW SLOPE (14" MAX.)
2" MIN.
4" MAX.
1'-0"1'-2"#4 REBAR AS SHOWN W/
90º HOOK AT CORNER
#4 @ 18" O.C.
3" CLR.

TYP.

EPOXY DOWEL PER4
-
3"Ø DRAINAGE PIPE

PER PLAN
L2X2X316" (SS316) W/ 12"X4"

NELSON WELDED HEADED
STUD @ 16" O.C. AND 4" MAX
FROM EA. END. TYP.

DEEP TRENCH PER
1 P-001
1 12" THK. DEEP TRENCH

COVER PER SCHEDULE ON
P-001

DRAINAGE PIPE PER PLAN
#4 @ 18" O.C.

EPOXY PER
4 -
24" MIN.
2" CLR
TYP.
2" CLR TYP
2" CLR TYP.

ROUGHEN SURFACE TO 1/4"

AMPLITUDE AND PROVIDE
BONDING AGENT TYP.

ROUGHEN SURFACE TO 1/4"

AMPLITUDE AND PROVIDE
BONDING AGENT TYP.
4" EMBED
ROUGHEN SURFACE TO 1/4"

AMPLITUDE AND PROVIDE
BONDING AGENT TYP.

HILTI HIT RE 500 V3 EPOXY
INSTALL PER ICC ESR 3814
(2) #4 ADDITIONAL REBAR
(E) #4 DOWEL @ 24" O.C. TO REMAIN
#4 DOWEL @ 18" O.C. W/HILTI
HIT RE 500 V3 EPOXY INSTALL
PER ICC ESR 3814 W/ 4" EMEBD

WHERE THE DOWEL HAS BEEN
CUT
(4) #4 AS SHOWN
SLOPE PERCIVIL/ARCH'L.

EPOXY DOWEL PER7
-

DRAIN PIPE PER PLAN

REBAR/DOWEL PER
7 -

DEEP TRENCH PER
1 P-001
NOTE:
- FOR INFORMATION NOT SHOWN SEE DETAIL7
-
10 N.T.S. DRAINAGE PIPE PENETRATION
11 N.T.S. NEW S.O.G. TO (E) FOOTING
14" F.V.

SLOPE PER ARCH'L.S.O.G. PER PLAN

SLAB EDGE PER
5 -
(E) FOOTING

TO REMAIN
NOTE:
·CONTRACTOR TO LOCATE EXISTING REBAR/DOWEL THAT NEED
TO BE PROTECTED IN PLACE PRIOR TO ANY DEMOLITION.
5'-0"

DRAINAGE PIPE PER PLAN
24" MIN.
(E) #4 DOWEL @ 24" O.C. TO REMAIN
DRIVE WAY S.O.G THICKNESS

AND REINFORCING TO MATCH

THE EXISTING
CORE DRILL 5"Ø FOR
DRAINAGE PIPE. (DO NOT

DAMAGE (E) REBAR)
REBAR PER8
-

SLAB EDGE TO MATCH (E)

IF OCCURS
#4 DOWEL @ 18" O.C. W/HILTI HIT
RE 500 V3 EPOXY INSTALL PER ICC
ESR 3814 W/ 4" EMEBD WHERE THE

DOWEL HAS BEEN CUT

PROVIDE METAL SLEEVES W/
I.D. 2" LARGER THAN THE
O.D. OF THE PIPE.
10"
12 N.T.S. CHILLER ANCHOR DETAIL
4" MIN.
(E) S.O.G.

PER PLAN

CHILLER UNIT

PER PLAN
(E) CONC. PAD

PER PLAN
38"Ø HILTI KB TZ2 SS316 W/ 2" EFF.

EMBED, @ 24" O.C. (MIN. 4 EA.

SIDES TOTAL 8" ANCHORS MIN.)
INSTALL PER ICC ESR 4266

PAD EXTENSION
PER1A
-
11" CLR.9 1/2"
CLR TYP.

POLICE AND FIRE HQ - CHILLER REPLACEMENT

DRAFT IMPROVEMENT PLANS - CITY OF CARLSBAD - POLICE AND FIRE HQ - CHILLER REPLACEMENT 50% CONSTRUCTION DOCUMENTS6/21/24-
2560 ORION WAY, CARLSBAD, CA 92010
1 PETERS CANYON ROAD, SUITE 130
IRVINE, CA. 92606
TEL: 949-387-8500, FAX: 949-387-0800
IDS

IDS GROUP
Project # 22X005.08
CK
EL
VM
NAS
NGI
AL
ON
SI
EL
E
RP
O
EFM.

TRE
DE
S
EER
S
IA
OR
FI
AL
L
RA
UT
N
R
GER I
TE
OF C
RTS
U
SAT
C
No. 3930
S
N
AH
AMI
90% CONSTRUCTION DOCUMENTS7/23/24
DATE SIGNED: 04-01-2025
PLAN CHECK SUBMITTAL10/02/24
PLAN CHECK CORRECTIONS04/01/25
-
-
1 SECTION AND DETAILS
S-501
Exhibit 3
June 10, 2025
Item #9 Page 7 of 7