9. RINCON ROOSEVELT MIXED-USE (CT 2024-0008/SDP 2024-0022, DEV2023-0105) – 1) Hold a public hearing; and
2) A doption of a resolution denying a Tentative Tract Map and Site Development Plan to demolish an existing eight-unit residential apartment building and commercial structures and construct a four -story mixed -use building consisting of 3,419 square feet of commercial space, 33 residential condominium units and 42 covered parking spaces on a 0.69 -acre property located at 2747 and 2775 Roosevelt Street in the northwest quadrant of the city, the Village & Barrio Master Plan area and Local Facilities Management Zone 1 (C ase Name:
Rincon Roosevelt; Case No.: CT 2024-0008/SDP 2024-0022 (DEV2023-0105)); or 3) A doption of a resolution approving a California Environmental Quality Act exemption determination and approving a Tentative Tract Map and Site Development Plan to demolish an existing eight-unit residential apartment building and commercial structures and construct a f our-story mixed -use building consisting of 3,419 square feet of commercial space, 33 residential condominium units and 42 covered parking spaces on a 0.69-acre property located at 2747 and 2775 Roosevelt Street in the northwest quadrant of the city, the Village & Barrio Master Plan area and Local Facilities Management Zone 1 (C ase Name: Rincon Roosevelt; Case No .: CT 2024 -0008/SDP 2024-0022 (DEV2023-0105)). (Staff contact: Shannon Harker, Community Services)
City Manager’s Recommendation: Take public input, close the public hearing, and adopt a resolution.
This item was withdrawn at the request of the applicant via letter dated Sept. 29, 2026.
CA Review CDS
Meeting Date: Sept. 29, 2026
To: Mayor and City Council
From: Geoff Patnoe, City Manager
Staff Contact: Shannon Harker, Senior Planner
[email protected], 442-339-2621
Subject: Rincon Roosevelt Mixed-Use
(CT 2024-0008/SDP 2024-0022, DEV2023-0105)
District: 1
Rec
ommended Action
1) Hold a public hearing; and
2) Adopt a resolution denying a Tentative Tract Map and Site Development Plan to demolish an existing eight-unit residential apartment building and commercial structures and construct a four-story mixed-use building consisting of 3,419 square feet of commercial space, 33 residential condominium units and 42 covered parking spaces on a 0.69-acre property located at 2747 and 2775 Roosevelt Street in the northwest quadrant of the city, the Village & Barrio Master Plan area and Local Facilities Management Zone 1; or 3) Adopt a resolution approving a California Environmental Quality Act exemption determination and approving a Tentative Tract Map and Site Development Plan to demolish an existing eight-unit residential apartment building and commercial structures and construct a four-story mixed-use building consisting of 3,419 square feet of commercial space, 33 residential condominium units and 42 covered parking spaces on a 0.69-acre property located at 2747 and 2775 Roosevelt Street in the northwest quadrant of the city, the Village & Barrio Master Plan area and Local Facilities Management Zone 1.
Executive Summary
A private development project, known as the Rincon Roosevelt, proposes to redevelop the properties at 2747 and 2775 Roosevelt Street, which currently contain a real estate office and an eight-unit apartment building. The 0.69-acre site would be redeveloped with a four-story, mixed- use building containing 33 condominium units, including five affordable housing units, 3,419 square feet of commercial space and 42 parking spaces within a gated garage.
In exchange for the construction of four lower income units, the applicant is requesting a 29% increase in residential density above the maximum density otherwise permitted under the Village & Barrio Master Plan, under California Density Bonus Law. To accommodate the increased density, the applicant is also requesting 11 waivers from applicable city development standards and objective design standards. Carlsbad's objective design standards are measurable, non- subjective building rules for multifamily housing and mixed-use developments designed to comply with state housing laws while preserving local community character.
Sept. 29, 2026
Item #9 Page 1 of 195
Following the Planning Commission’s recommendation on Feb. 18, 2026, that the City Council approve the project, city staff identified violations of certain state-mandated tenant protections by the property owner. Although the applicant has agreed to incorporate conditions intended to address these compliance issues, the Housing Crisis Act of 2019, specifically Government Code Section 66300.6(b), prohibits the city from approving the project unless the applicable tenant protection requirements have been satisfied.
Ultimately, the decision to approve, conditionally approve, or deny the Rincon Roosevelt project rests with the City Council. To facilitate the City Council’s consideration of the project and provide clear alternatives, staff have prepared two complete resolutions: one recommending approval of the project and one recommending denial. The project is before the City Council because the property is subject to the Village & Barrio Master Plan, which requires City Council review and approval of proposed structures exceeding 5,000 square feet or projects containing more than four dwelling units.
Explanation & Analysis
Project Site and Proposed Development
The project site consists of three parcels totaling approximately 0.69 acres on the west side of Roosevelt Street, just south of Beech Avenue. The site is currently developed with three structures, all of which are vacant: an eight-unit apartment building, a commercial office building with an associated accessory structure and a surface parking lot.
The site is surrounded by a mix of commercial and residential uses, including restaurants, commercial and professional offices and an auto repair shop. The United States Post Office is located on the north side of Roosevelt Street, across the steet from the site.
The developer is requesting Tentative Tract Map and Site Development Plan approvals to demolish existing structures and construct a four-story mixed-use development consisting of:
• 3,419 square feet of ground-floor commercial space, divided among three tenant spaces • 33 residential condominium units on the second, third and fourth floors, including five affordable housing units
• 42 parking spaces within an at-grade parking garage accessed from Roosevelt Street; four spaces would be designated for the commercial uses, with the remaining 38 spaces designated for the residential units
Density Bonus and Development Standard Waivers
Under the Village Center District of the Village & Barrio Master Plan, residential development is permitted at a density of 28 to 35 dwelling units per acre. Based on the site's 0.69-acre area, the maximum base density is 25 dwelling units. To construct the proposed 33 units, the developer is using the California Density Bonus Law to obtain a 29% density bonus, resulting in eight additional units and a proposed density of 47.8 dwelling units per acre. 1 1 Base density unit yields are calculated based on provisions in Carlsbad Municipal Code Chapter
21.53, under which dwelling units may be rounded up or down to the next whole number.
However, in the California Density Bonus Law, fractional units for base density and total density are rounded up to the next whole number.
Sept. 29, 2026
Item #9 Page 2 of 195
To qualify for the requested density bonus, the developer is designating at least 16% of the 25- unit base density, or four units, as affordable to low-income households.2 In addition, the developer is required to provide one extremely low-income unit to satisfy replacement protected unit requirements of the state's Housing Crisis Act. Accordingly, the project includes a total of five deed-restricted affordable housing units, which satisfy the applicable requirements of California Density Bonus Law (Government Code sections 65915-65918) and the city's Inclusionary Housing Ordinance.
California Density Bonus Law also allows a developer to request incentives, concessions and waivers of development standards when necessary to reduce the cost of the affordable housing or to avoid precluding or physically hindering the construction of the density bonus project. In connection with the proposed project, the developer is requesting 11 waivers from development standards contained in the Village & Bario Master Plan and the Carlsbad Municipal Code.
A complete description of the proposed development; applicable General Plan, zoning and master plan requirements; and staff's analysis of the project are provided in the Planning Commission staff report in Exhibit 3.
Planning Commission Meeting and Post Meeting
The Planning Commission considered the project on Feb. 18, 2026. Three members of the public spoke at the hearing. One speaker expressed general support for the project, while the other two raised concerns regarding the building design, landscape maintenance, screening of air- conditioning units and parking stall dimensions. Commissioner Lafferty also expressed safety concerns regarding the increased setbacks between the proposed building and adjacent property lines as well as the lack of fencing to limit access to the sides and rear of the building. Following staff responses to those issues, which are summarized in Exhibit 7, the Planning Commission recommended that the City Councill approve the project. Please refer to the minutes to the Planning Commission hearing in Exhibit 4.
Following the Planning Commission’s recommendation for approval on Feb. 18, 2026, two critical actions took place: 1) discovery of tenant displacements, and 2) applicant initiated project revisions.
Tenant Protections under the Housing Crisis Act
The Housing Crisis Act, specifically Government Code Section 66300.6(b), prohibits the city from approving a housing development project, like the Rincon Roosevelt project, that will require the demolition of occupied or vacant protected units
3 unless certain requirements are satisfied.
Protected units include housing units rented by low- or very low-income tenants in the past five
2 The U.S. Department of Housing and Urban Development defines a low-income household family as one whose income does not exceed 80% of the average area median income for the region. In 2026, the department reported that the average area median income for the San Diego County region is $130,900. Based on the department’s adjustment factors for high-cost areas, a low-income family of four makes no more than $139,400 annually. 3 Protected units include residential units that are rented by lower income households within five years, subject to legally required rental restrictions, subject to rent or price control ordinances, or withdrawn from rent or lease within ten years under what is commonly known as the Ellis Act.
Sept. 29, 2026
Item #9 Page 3 of 195
years. When there is a protected unit, the occupants of both the protected units and non- protected units have rights that the applicant is required to comply with.
Among these rights, all existing occupants must be allowed to occupy their units until six months prior to the start of construction activities. The applicant must provide occupants with written notice of the planned demolition, the date they must vacate and their tenant protection rights.
The notice must be provided at least six months before the date that existing occupants must vacate. The occupants that are required to leave their units must be allowed to return at their prior rental rate if the demolition does not proceed and the property is returned to the rental market.
Separately, the applicant must provide the existing occupants of any protected units with certain relocation benefits and a right of first refusal for a comparable unit in the new housing development at an affordable rent or cost.
Project Background and Review Timeline
The applicant submitted a preliminary application for the Rincon Roosevelt project on Aug. 29, 2024. The application gave the applicant vested rights for the project to be reviewed under the local ordinances, policies, standards and fees in effect at the time of the preliminary application.
On Sept. 23, 2023, almost a year before the preliminary application’s submittal, Carlsbad Housing & Homeless Services staff provided the applicant with comments informing the applicant of the Housing Crisis Act’s tenant protection requirements.
As part of the application process, the applicant was required to submit several forms. One form, the Housing Declarations Form (P-38 Form), applies to development projects, like the Rincon Roosevelt project, that propose to demolish existing residential units. The form required the Applicant to verify income and/or occupancy of tenants within the five years prior to the application’s submission. The form also required the applicant to acknowledge certain tenant protections may apply to the project.
Housing & Homeless Services staff received income verification information for five of the eight existing units, which indicated that three units were occupied by lower-income households. The income verification forms were signed by the tenants at different times between June 2024 and August 2024. Housing & Homeless Services prepared a memo on March 31, 2025, informing the applicant that state-mandated affordability assumptions for the other households required two more of the existing units would be assumed to be occupied by lower income households. The city and applicant mutually agreed that five of the eight existing units qualify as “protected units” – one for an extremely low-income household and four for low-income households. The project application was determined to be complete for further processing on Sept. 3, 2025.
Discovery of Tenant Displacement and Applicant’s Response While processing the application, city staff were led to believe that the existing units were occupied and the applicant intended to implement and fulfill all the Housing Crisis Act tenant protection requirements following project approval. In February 2026, a representative of the applicant informed the project planner that the existing units were vacant. The conversation happened in person during the representative’s submission of a final set of plans for distribution to the Planning Commission.
Sept. 29, 2026
Item #9 Page 4 of 195
The Planning Commission considered the project at a public hearing on Feb. 18, 2026. At the hearing, planning staff indicated the units were vacant, but the significance of the vacancies was not then known. The Planning Commission recommended approval of the project to the City Council.
Shortly after the Planning Commission hearing, Housing & Homeless Services staff learned that the former tenants of the protected units were displaced. After further investigation, it became clear then that the property owner required the tenants to move out of the existing units without the notice and relocation assistance required by the Housing Crisis Act.
In April 2026, the applicant contacted seven of the eight former tenants. The applicant proposed notifying the tenants of their rights under the Housing Crisis Act, offering them the right to return to their units at the prior rental rate and to remain until six months before construction. City staff initially took no position on the applicant’s proposal and expressed concern about the city’s ability to recommend and approve the project when the Housing Crisis Act tenant protection requirements were not satisfied.
Housing Crisis Act Technical Assistance Request
On May 27, 2026, the city sought technical assistance from the California Department of Housing and Community Development on how to proceed given the applicant’s failure to satisfy the Housing Crisis Act’s tenant protection requirements. On July 14, 2026, after clarifying information with city staff and the applicant, a representative with the Department of Housing and Community Development left a voicemail message for city staff indicating that the applicant’s proposed remedy was satisfactory, approval of the project would not violate the Housing Crisis Act or at least the California Department of Housing and Community Development would not go after the city for approving the project. After hearing from the California Department of Housing and Community Development, the applicant notified seven of the eight former tenants as described above. Of the five former tenants that responded, only one accepted the offer to move back to the property.
City staff were concerned that the California Department of Housing and Community Development did not answer the city’s question about whether the city could approve a project that failed to fully comply with the Housing Crisis Act’s tenant protection requirements. City staff followed up with the California Department of Housing and Community Development and asked for a written response to the city’s request for technical assistance or city staff would need to recommend the City Council deny the project. The California Department of Housing and Community Development expressly declined to provide the requested technical assistance.
A written response would have established an official record of guidance from the California Department of Housing and Community Development that the city could provide in response to any challenge to the city’s decision on the project. The department’s voicemail response does not provide the same level of protection for the city and failed to address the Housing Crisis Act’s apparent requirement that the city deny the project.
Applicant Proposed Project Revisions
Following the public hearing, the developer revised the project plans to add storage closets to a select number of units, including the inclusionary units, and remove the proposed roof decks.
Removal of the roof decks also eliminates one of the two stairway towers and the elevator access Sept. 29, 2026
Item #9 Page 5 of 195
tower. As a result, the maximum height of the proposed projections is reduced from 64 feet, 3 inches to 59 feet, 3 inches.
Minor revisions to approved discretionary projects are common and may occur during plan check or in response to updated building code requirements. Following discretionary approval, the City Planner may approve minor changes during the construction drawing phase when the changes are determined to be in “substantial conformance” with the original project description, findings, and conditions of approval.
Rather than defer the proposed revisions until the construction drawing or building permit phase, the developer has requested that the changes be incorporated into the project plans now.
This allows the revisions to be considered as part of the discretionary action before the City Council, including the requested approval of Tentative Tract Map (CT 2024-0008) and Site Development Plan (SDP 2024-0022). The proposed modification is limited to:
• Adding storage closets to a select number of units, including the inclusionary units • Removing the proposed roof decks
• Removing the elevator access tower
• Removing one of the two stairway towers
The roof drains and mechanical equipment have also been reconfigured to accommodate these changes and maintain compliance with applicable engineering, building and zoning regulations.
The revisions do not change the approved residential unit count, commercial floor area, building footprint, project density, parking supply or overall site design.
Staff evaluated the proposed modification using the same criteria applied to determine whether changes to an approved project are minor or major. Based on that evaluation, staff determined that the modification is minor in nature and does not affect the Planning Commission’s findings or recommendation for approval.
The modified project remains consistent with the design, proposed uses and applicable development standards presented to the Planning Commission on Feb. 18, 2026. The revised plans incorporating these modifications are provided as Exhibit 6.
Options
Staff provide the following options for the City Council’s consideration:
• Resolution 1: Denial of the application
Despite the California Department of Housing and Community Development’s verbal support, since the applicant cannot demonstrate full compliance with the Housing Crisis Act’s tenant protection requirements, the Housing Crisis Act requires the city to deny the project. Per city code, the applicant must wait a year to submit a new application for the project. However, the applicant would still have to provide five replacement units for the five existing protected units. The project would also be subject to current ordinances, policies, standards and fees. Additionally, a denial may result in the Attorney General taking an enforcement action against the city under Housing Element Law. City staff believe there is sufficient evidence in the record to substantiate and support denial of the proposed Rincon Roosevelt project under state housing laws.
Sept. 29, 2026
Item #9 Page 6 of 195
• Resolution 2: Approval of the application
While the California Department of Housing and Community Development did not provide their opinions in writing, they did verbally indicate that they would not go after the city for approving the project in violation of the Housing Crisis Act, with the applicant’s added conditions and offer to remedy the tenant protection violations.
Further, the project would provide new housing, which closes the gap between projected housing needs and actual supply. The city would benefit from the addition of 33 condominium units, including five affordable housing units. Should the City Council approve this option, the tenant relocation conditions and post planning commission project changes have been made as part of the resolution.
Fiscal Analysis
There is no direct fiscal impact associated with the proposed project.
Next Steps
Should the proposed project be denied, in terms of land development, the developer could submit a new land use development application on the same property or any other property in the city. The city has developed a good track record for facilitating new housing development projects to respond to the important statewide housing need. City staff are available to assist the developer with processing future land use development projects.
If the proposed project is approved, staff will continue to process and work with the developer with the requirements to demolish the existing structures and develop the project.
Environmental Evaluation
The California Environmental Quality Act, or CEQA, requires agencies to be aware of the environmental effects of their proposed actions, to give the public an opportunity to comment on environmental issues, and to avoid or reduce significant environmental impacts when it’s feasible to do so. Prior to final action on the project, an environmental determination shall be made by the City Council as part of the approval action to ensure agency compliance with CEQA.
The CEQA Guidelines (California Code of Regulations Title 14, Division 6, Chapter 3) establish certain project types as being exempt from CEQA.
To further streamline and accelerate the development of housing in California, Assembly Bill 130 was signed into law by the Governor on June 30, 2025. The bill, codified in Public Resources Code section 21080.66, was effective immediately and established a new statutory exemption from CEQA for “housing development projects” in urban areas that meet a list of qualifying criteria.
When presented to the Planning Commission, it was believed that the proposed Rincon Roosevelt project would be the first housing development project to be considered by the City Council for the Assembly Bill 130 statutory exemption. Please refer to Exhibit 10 for the requisite Assembly Bill 130 analysis, included as part of the CEQA Notice of Exemption, as was presented to and accepted by the Planning Commission. This CEQA exemption, findings and analysis, would be utilized if there is a City Council decision to approve the proposed project.
As noted previously, city staff’s recommendation to the City Council is different than the Feb. 18, 2026, recommendation of the Planning Commission. This is based on the information that was learned after the Planning Commission public hearing. Projects that are rejected, disapproved or Sept. 29, 2026
Item #9 Page 7 of 195
denied by a public agency are excluded from CEQA review requirements. Therefore, no further environmental review is required if the proposed project is denied.
Exhibits
1. City Council resolution (denial)
2. City Council resolution (approval)
3. Staff Report from February 18, 2026, Planning Commission Meeting (on file in the Office of the City Clerk)
4. Minutes from February 18, 2026, Planning Commission Meeting (on file in the Office of the City Clerk)
5. Planning Commission Resolution No. 7567 (on file in the Office of the City Clerk)
6. Updated Plans Including Minor Modifications
7. Response to Planning Commission Comments at February 18, 2026 Hearing
8. Project-Related Compliance Analysis of Statewide Tenant Protection Requirements
9. Project Processing Timeline and HCD and Developer Correspondences
10. California Environmental Quality Act AB 130 Analysis and Notice of Exemption
11. Location Map
Sept. 29, 2026
Item #9 Page 8 of 195
Exhibit 1
RESOLUTION NO. .
A RESOLUTION OF THE CITY COUNCIL OF THE CITY OF CARLSBAD,
CALIFORNIA, DENYING A TENTATIVE TRACT MAP AND SITE DEVELOPMENT
PLAN TO DEMOLISH AN EXISTING EIGHT -UNIT RESIDENTIAL APARTMENT
BUILDING AND COMMERCIAL STRUCTURES AND CONSTRUCT A FOUR - STORY MIXED -USE BUILDING CONSISTING OF 3,419 SQUARE FEET OF COMMERCIAL SPACE, 33 RESIDENTIAL CONDOMINIUM UNITS AND 42 COVERED PARKING SPACES ON A 0.69 -ACRE PROPERTY LOCATED AT 2747 AND 2775 ROOSEVELT STREET IN THE NORTHWEST QUADRANT OF THE
CITY, THE VILLAGE & BARRIO MASTER PLAN AREA AND LOCAL FACILITIES MANAGEMENT ZONE 1
CASE NAME: RINCON ROOSEVELT
CASE NO.: CT 2024-0008/SDP 2024-0022 (DEV2023-0105)
WHEREAS, the City Council of the City of Carlsbad, California has determined that pursuant to the provisions of the Municipal Code, the Planning Commission did, on Feb. 18, 202 6, hold a duly noticed public hearing as prescribed by law to consider Tentative Tract Map CT 2024 -0008 and Site Development Plan SDP 2024- 0022, as referenced in Planning Commission Resolution No. 75 67 recommending to the City Council that it be approved; and WHEREAS, the Housing Crisis Act of 2019 (California Senate Bill 330) declared a statewide crisis in order to address California’s affordable housing shortage, strengthen tenant protections and preserve existing affordable housing; and
WHEREAS, t he Housing Crisis Act does not prohibit a local government from exercising its authority to disapprove a housing development project, but rather provides limitations and conditions for exercising that authority; and
WHEREAS, the Housing Crisis Act requires, under Government Code section 66300.6(b), the city to no approve a development project that will require the demolition of occupied or vacant protected units unless certain requirements are satisfied, including but not limited to: (1) Any existing occupants will be allowed to occupy their units until six months before the start of construction activities; (2) the project proponent shall provide existing occupants with written notice of the planned demolition, the date they must vacate, and their rights under Government Code section 66300.6; (3) notice to existing occupants shall be provided at least six months in advance of the date that existing occupants must vacate; (4) a ny existing occupants that are required to leave their units shall be allowed to return at their prior rental rate if the demolition does not proceed and the property is returned to the rental market; (5) t he developer agrees to provide both of the following to the existing occupants of any Sept. 29, 2026
Item #9 Page 9 of 195
protected units that are lower income households: (A) Relocation benefits that are equivalent to the relocation benefits required to be paid by public entities pursuant to Chapter 16 (commencing with Section 7260) of Division 7 of Title 1 and any implementing regulations ; and (B) A right of first refusal for a comparable unit available in the new housing development, or in any required replacement units associated with a new development that is not a housing development, affordable to the household at an affordable rent or an affordable housing cost; and
WHEREAS, the city must comply with various state housing laws that are designed to prevent displacement of existing tenants when housing is demolished or replaced; and WHEREAS, the City Council of the City of Carlsbad held a duly noticed public hearing to consider Tentative Tract Map CT 2024-0008 and Site Development Plan SDP 2024-0022 (“Project”); and WHEREAS, at said public hearing, upon hearing and considering all testimony, public comment and arguments, if any, of all persons desiring to be heard, the City Council considered all evidence and factors relating to the Project; and
WHEREAS, the City Council has reviewed the proposed Project and considered all relevant reports, public comments, and findings.
NOW, THEREFORE, BE IT RESOLVED by the City Council of the City of Carlsbad, California, as follows:
1. That the above recitations are true and correct.
2. Compliance with California Environmental Quality Act . Projects that are rejected, disapproved, or denied by a public agency are excluded from CEQA review requirements. Therefore, no further environmental review is required.
3. The City Council finds and determines that the proposed Project includes the demolition of protected units does not comply with the tenant protection requirements of the Housing Crisis Act, Government Code section 66300.6(b), in that the existing occupants of all units and the existing occupants of the protected units at the time of the application were not provided, notified, or offered the rights as required under California law . City Council determines that the State Legislature’s passage of the narrowly tailored prohibition reads as mandatory and absolute obligation on the city relating to this Project , and leaves little to no room for interpretation or discretion.
Sept. 29, 2026
Item #9 Page 10 of 195
Therefore, the proposed Project , Tentative Tract Map CT 2024 -0008 and Site Development Plan SDP 2024-0022, is denied.
4. The City Council, after considering all evidence and testimony presented during the hearing, conclude that there is insufficient evidence and information provided to the city to demonstrate that the landlord or developer either cured or remedied the violation of the tenants rights under the Housing Crisis Act, specifically Government Code section 66300.6(b)(3)-(4).
5. According to the Housing Accountability Act, Government Code sections 65589.5(d), the Project includes low-income households and finds, based on a preponderance of the evidence in the record, that the denial of the housing development project is required in order to comply with the Housing Crisis Act, specifically the tenant protection requirements found in Government Code section 66300.6(b)(3) -(4), and there is no feasible method to comply without rendering the development unaffordable to low - income households or financially infeasible. The evidence in the record demonstrate that the tenant protection requirements under state law were not capable of being accomplished in a successful manner within a reasonable period of time, taking into account economic, environmental, social, and technological factors.
6. The City Council acknowledges the need for housing, including affordable housing, while also acknowledging the importance of property owners, landlords and developers to be familiar with statewide tenant protection requirements to prevent violations of state law. The city stands ready to assist the landlord/developer or successor in interest find suitable housing development opportunities to supply much- needed housing at all income levels for Californians.
7. This action is final the date this resolution is adopted by the City Council. The Provisions of Chapter 1.16 of the Carlsbad Municipal Code, “Time Limits for Judicial Review” shall apply:
Sept. 29, 2026
Item #9 Page 11 of 195
“NOTICE”
The time within which judicial review of this decision must be sought is governed by Code of Civil Procedure, Section 1094.6, which has been made applicable in the City of Carlsbad by Carlsbad Municipal Code Chapter 1.16. Any petition or other paper seeking review must be filed in the appropriate court not later than the ninetieth day following the date on which this decision becomes final; however, if within ten days after the decision becomes final a request for the record is filed with a deposit in an amount sufficient to cover the estimated cost or preparation of such record, the time within which such petition may be filed in court is extended to not later than the thirtieth day following the date on which the record is either personally delivered or mailed to the party, or his attorney of record, if he has one. A written request for the preparation of the record of the proceedings shall be filed with the City Clerk, City of Carlsbad, 1200 Carlsbad Village Drive, Carlsbad, CA 92008.
PASSED, APPROVED AND ADOPTED at a Regular Meeting of the City Council of the City of Carlsbad on the __ day of ________, 2026, by the following vote, to wit:
AYES:
N AYS:
ABSTAIN:
ABSENT:
______________________________________
KEITH BLACKBURN, Mayor
______________________________________
SHERRY FREISINGER, City Clerk
(SEAL)
Sept. 29, 2026
Item #9 Page 12 of 195
Exhibit 2
RESOLUTION NO. .
A RESOLUTION OF THE CITY COUNCIL OF THE CITY OF CARLSBAD,
CALIFORNIA, APPROVING A CALIFORNIA ENVIRONMENTAL QUALITY ACT
EXEMPTION DETERMINATION AND APPROVING A TENTATIVE TRACT MAP
AND SITE DEVELOPMENT PLAN TO DEMOLISH AN EXISTING EIGHT -UNIT
RESIDENTIAL APARTMENT BUILDING AND COMMERCIAL STRUCTURES AND CONSTRUCT A FOUR -STORY MIXED -USE BUILDING CONSISTING OF 3,419 SQUARE FEET OF COMMERCIAL SPACE, 33 RESIDENTIAL CONDOMINIUM UNITS AND 42 COVERED PARKING SPACES ON A 0.69 -ACRE PROPERTY LOCATED AT 2747 AND 2775 ROOSEVELT STREET IN THE NORTHWEST
QUADRANT OF THE CITY, THE VILLAGE & BARRIO MASTER PLAN AREA AND LOCAL FACILITIES MANAGEMENT ZONE 1
CASE NAME: RINCON ROOSEVELT
CASE NO.: CT 2024-0008/SDP 2024-0022 (DEV2023-0105)
WHEREAS, the City Council of the City of Carlsbad, California has determined that pursuant to the provisions of the Municipal Code, the Planning Commission did, on Feb. 18, 202 6, hold a duly noticed public hearing as prescribed by law to consider Tentative Tract Map CT 2024 -0008 and Site Development Plan SDP 2024-0022 (“Project”), as referenced in Planning Commission adopted Resolution No. 7567 recommending to the City Council that it be approved; and WHEREAS, after the Planning Commission public hearing, the Project underwent a number of revisions to its project description as further described in the Sept. 29, 2026, City Council Staff Report and presented within this resolution. The Project that is the subject of this resolution, includes the revisions made to the project description by the applicants as presented in the record of evidence; and WHEREAS, the City Council of the City of Carlsbad held a duly noticed public hearing to consider the Project; and
WHEREAS, at said public hearing, upon hearing and considering all testimony, public comment and arguments, if any, of all persons desiring to be heard, the City Council considered all factors relating to the Project.
NOW, THEREFORE, BE IT RESOLVED by the City Council of the City of Carlsbad, California, as follows:
1. That the above recitations are true and correct.
2. Compliance with California Environmental Quality Act. The proposed action to demolish an existing apartment building and commercial structure s and construct a four -story mixed-use structure is statutorily exempt from environmental review pursuant to Public Sept. 29, 2026
Item #9 Page 13 of 195
Resources Code Section 65589.5(h)(2) since it qualifies as a “housing development project.” Specifically:
a. It is a mixed-use development consisting of residential and nonresidential uses and at least two-thirds of the square footage is designated for residential use and due to the location outside of the Coastal Zone, short term rental of the housing units is prohibited by the Carlsbad Municipal Code b. The proposed density exceeds 15 dwelling units per acre c. The site is not more than 20 acres and is surrounded by urban uses d. The project is consistent with the General Plan, Zoning Ordinance and the Village & Barrio Master Plan
e. There are no other environmental or site-specific constraints outlined in the statute that would render this property ineligible for the exemption f. The structures proposed to be demolished are not historic structures that have been placed on a national, state or local historic register g. The tribal consultation process has been completed within the requisite timelines of Assembly Bill (AB) 130.
The notice of exemption will be filed with the Recorder/County Clerk and the State Clearinghouse within five days after project approval by the decision-making body.
3. That the recommendation of the Planning Commission for the approval of Tentative Tract Map CT 2024 -0008 and Site Development Plan , SDP 2024-0022, is adopted and approved, and that the findings and conditions of the Planning Commission contained in the Planning Commission adopted Resolution No. 7567 on file with the City Clerk and incorporated herein by reference, are the findings and conditions of the City Council , with the following exceptions:
a. Condition No. 20 of Planning Commission Resolution No. 7567 is hereby superseded and replaced with the following condition:
Prior to the approval of the final map for any phase of this project, or where a map is not being processed, prior to the issuance of building permits for any lots or units, the developer shall enter into an Affordable Housing Agreement with the city. The Agreement shall satisfy the following criteria:
Sept. 29, 2026
Item #9 Page 14 of 195
a. To provide and deed restrict one (1) dwelling unit as affordable to an extremely low-income household for 55 years, earning up to 30% of the area median income (AMI), and four (4) dwelling units as affordable to low -income households for 55 years, earning up to 80% of the Area Median Income (AMI). b. The agreement shall be in accordance with the requirements and process set forth in Chapters 21.85 and 21.86 of the Carlsbad Municipal Code. The draft Affordable Housing Agreement shall be submitted to the City Planner no later than 60 days prior to the request to final the map and shall be recorded prior to approval of the final map, or prior to the issuance of any building permit or grading permit for any lots or units where a map is not being processed. The recorded Affordable Housing Agreement shall be binding on all future owners and successors in interest
b. Condition No. 22 of Planning Commission Resolution No. 7567 is hereby superseded and replaced with the following condition:
Project must comply with occupant noticing requirements and protections defined in Government Code Section 66300.6.
a. Noticing per Government Code Section 66300.6(b)(3)(A), that all existing occupants must be allowed to remain in their units until six (6) months before the start of construction activities. Additionally, existing occupants that are required to vacate their units, must be allowed to return at the prior rental rate should the demolition not proceed and the property is returned to the rental market. Documentation demonstrating compliance with this requirement, or alternative remedy acceptable to HCD, shall be submitted to the Housing & Homeless Services Director no later than 60 days prior to the request for final map.
b. Evidence of appropriate relocation benefits were paid to eligible occupants in accordance with Government Code Section 7260, per Government Code Section 66300.6(b)(4), and first right of refusal for a comparable unit, affordable to household at an affordable housing cost, pursuant to Health and Safety Code Section 50052.5 in the proposed new housing development. Documentation Sept. 29, 2026
Item #9 Page 15 of 195
demonstrating compliance with this requirement shall be submitted to the Housing & Homeless Services Director no later than 60 days prior to issuance of first building permit.
c. Condition 23 of Planning Commission Resolution No. 7567 is hereby superseded and replaced with the following condition:
The owners of the five (5) lower -income units shall have equal access to project amenities, including the residential parking spaces in the parking garage, pursuant to Health and Safety Code Section 17929 to the satisfaction of the City Planner and the Housing & Homeless Services Director. Such access shall be included in the affordable price and no additional cost shall be assessed to the owners of the affordable units for use.
4. This action is final the date this resolution is adopted by the City Council. The Provisions of Chapter 1.16 of the Carlsbad Municipal Code, “Time Limits for Judicial Review” shall apply:
“NOTICE”
The time within which judicial review of this decision must be sought is governed by Code of Civil Procedure, Section 1094.6, which has been made applicable in the City of Carlsbad by Carlsbad Municipal Code Chapter 1.16. Any petition or other paper seeking review must be filed in the appropriate court not later than the ninetieth day following the date on which this decision becomes final; however, if within ten days after the decision becomes final a request for the record is filed with a deposit in an amount sufficient to cover the estimated cost or preparation of such record, the time within which such petition may be filed in court is extended to not later than the thirtieth day following the date on which the record is either personally delivered or ma iled to the party, or his attorney of record, if he has one. A written request for the preparation of the record of the proceedings shall be filed with the City Clerk, City of Carlsbad, 1200 Carlsbad Village Drive, Carlsbad, CA 92008.
Sept. 29, 2026
Item #9 Page 16 of 195
PASSED, APPROVED AND ADOPTED at a Regular Meeting of the City Council of the City of Carlsbad on the __ day of ________, 2026, by the following vote, to wit:
AYES:
N AYS:
ABSTAIN:
ABSENT:
______________________________________
KEITH BLACKBURN, Mayor
______________________________________
SHERRY FREISINGER, City Clerk
(SEAL)
Sept. 29, 2026
Item #9 Page 17 of 195
Exhibit 3
Sta
ff Report from February 18, 2026,
Planning Commission Meeting
(on file in the Office of the City Clerk)
Sept. 29, 2026
Item #9 Page 18 of 195
Exhibit 4
Mi
nutes from February 18, 2026,
Planning Commission Meeting
(on file in the Office of the City Clerk)
Sept. 29, 2026
Item #9 Page 19 of 195
Exhibit 5
Plan
ning Commission Resolution No. 7567
(on file in the Office of the City Clerk)
Sept. 29, 2026
Item #9 Page 20 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 - 2775 ROOSEVELT STREET - CARLSBAD, CA 92008
2317
sheet
TITLE SHEET
A001
Stephen Dalton Architects
444 S. CEDROS. STUDIO 185
SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916 CT 2024-0008 / SDP 2024-0002
PROJECT DATA
OWNER 2747 ROOSEVELT, LLC
DEVELOPER 2747 ROOSEVELT, LLC
5315 AVENIDA ENCINAS SUITE 200
CARLSBAD, CA 92008
(949) 637-3254
APPLICATION TYPES
SITE DEVELOPMENT PLAN (SDP)
TENTATIVE MAP (CT)
PROJECT NAME RINCON ROOSEVELT
PROJECT ADDRESS 2747 - 2775, ROOSEVELT STREET
CARLSBAD CA, 92008
A.P.N. 203-101-12
203-181-16
203-181-10
LEGAL DESCRIPTION
A SUBDIVISION OF THE SELY 1/2 OF
LOT 29 & LOT 30 OF SEASIDE
LANDS, CARLSBAD, MAP No.1722
SITE AREA 30,116 SF (0.69 ACRE)
GENERAL PLAN VILLAGE-BARRIO (V-B)
ZONING VILLAGE CENTER (VC)
EXISTING LAND USE COMMERCIAL
PROPOSED LAND USE RESIDENTIAL
OCCUPANCY TYPE(S) R2 - RESIDENTIAL
A2 - COMMERCIAL
ALLOWED DENSITY 28-35 DU/ACRE
PROPOSED DENSITY 47.8 DU/ACRE
PROPOSED UNITS 33
ALLOWED COVERAGE N/A
PROPOSED COVERAGE 24,643 SF (82%)
CONSTRUCTION TYPE III A @ LEVELS 2-4
I A @ LEVEL 1
SETBACKS REQ'D PROPOSED
FRONT/CORNER: 0'-0" MIN/5'-0" MAX 10'-1"
SIDE: 0'-0" 11'-6"
REAR: 0'-0" 11'-5"
MAX BUILDING HEIGHT 53'-5"
APPLICABLE CODES 2022 CBC, CFC, CMC, CPC, CEC.
PHOTOVOLTAIC REQ'D: YES
KW-DC (ROOF): 3,654 SF PROVIDED
REQUIRED PARKING: 0 SPACES PURSUANT TO AB 2097
PROVIDED PARKING: 42 SPACES
EV SPACES REQUIRED: YES
EV CHARGERS: 3 REQUIRED
3 PROVIDED
EV READY: 9 SPACES REQUIRED
9 SPACES PROVIDED
EV CAPABLE: 4 SPACES REQUIRED
4 SPACES PROVIDED
REQ'D REC SPACE PRIVATE: 60 SF / UNIT
COMMON: 15 SF / UNIT
PROP'D REC SPACE PRIVATE: 6,858 SF
COMMON: 1,658 SF
SEWER DISTRICT CITY OF CARLSBAD WASTEWATER
DIVISION
WATER DISTRICT CITY OF CARLSBAD MUNICIPAL
WATER DISTRICT
SCHOOL DISTRICT
CARLSBAD UNIFIED SCHOOL
DISTRICT
6"
EL 99.99
A 8-1
1 A8-1
1 2
3 4 A6-1
10 1
A4-1
1 A4-1
1 0
0 N
RI
01.01 F01
DRAWING TITLE
GRID LINES
BUILDING SECTION
WALL OR DETAIL
SECTION
DETAIL
CALLOUT
EXT/INT ELEVATIONS
NORTH ARROW
ABOVE, BELOW, OR HIDDEN
CUTLINE
DOOR IDENTIFIER
WINDOW IDENTIFIER
MATERIAL IDENTIFIER
FIXTURE IDENTIFIER
KEYNOTE
REVISION CLOUD/CALLOUT
DATUM POINT
ELEVATION
SLAB STEP
DRAFTING SYMBOLS
PROJECT TEAM
DEVELOPER 2747 ROOSEVELT LLC
5315 AVENIDA ENCINAS, SUITE 200
CARLSBAD, CA 92008
949.637.3254
ARCHITECT STEPHEN DALTON ARCHITECTS
444 S CEDROS AVE, STUDIO 185
SOLANA BEACH, CA 92075
858.792.5906
CIVIL PASCO, LARET, SUITER & ASSOCIATES
535 NORTH HIGHWAY 101 SUITE A
SOLANA BEACH, CA 92075
858.259.8212
LANDSCAPE GILLESPIE MOODY PATTERSON (GMP), INC
3176 LIONSHEAD AVENUE, SUITE 102
CARLSBAD, CA 92010
858.558.8977
SMEP GOUVIS ENGINEERING
15 STUDEBAKER
IRVINE, CA 92618
949.752.1612
DEMOLITION OF EXISTING:
ONE-STORY COMMERCIAL STRUCTURE: 1,347 SF
ONE-STORY COMMERCIAL STRUCTURE: 696 SF
TWO-STORY RESIDENTIAL STRUCTURE: 3,973 SF
CONSTRUCTION OF NEW
:
4-STORY RESIDENTIAL BUILDING W/ 33 RESIDENTIAL UNITS, 3
GROUND-LEVEL COMMERCIAL UNITS, SURFACE PARKING,
UTILITY SPACES, ASSOCIATED HARDSCAPE AND LANDSCAPE
SCOPE OF WORK
PROJECT
LOCATION
VICINITY MAP
GRAND AVE
STATE
ST
BEECH ST
ROOSEVELT
ST
N
SHEET INDEX
ELECTRICAL
EN-0.0 SPECIFICATIONS NOTES & SHEET INDEX
EN-0.1A GENERAL NOTES
EN-0.1B MANDATORY MEASURES NOTES
EN-0.2 ABBREVIATIONS & SYMBOLS LIST
EN-0.3 SINGLE LINE DIAGRAM - 'MS1' RESIDENTIAL SERVICE EN-0.4 SINGLE LINE DIAGRAM - RESIDENTIAL METER BANK
EN-0.5 SINGLE LINE DIAGRAM - 'MS2' COMMERCIAL SERVICE
EN-0.5A FEEDER SCHEDULES
EN-0.6 LOAD CALCULATIONS & EQUIPMENT SCHEDULES
EN-0.7 PANEL SCHEDULES
EN-0.8 PANEL SCHEDULES
EN-0.9 PANEL SCHEDULES
EN-0.10 LIGHTING CONTROL
ED-1 DETAILS
ED-2 DETAILS
ED-3 DETAILS
ED-4 DETAILS
E-1.0 SITE LIGHTING NOTES
E-1.1 SITE UTILITY PLAN
E-1.2 SITE LIGHTING PLAN
E-1.3 PHOTOMETRIC SITE PLAN
E-1.4 LIGHTING SPECIFICATIONS
E-2.1 1ST FLOOR LIGHTING PLAN
E-2.2 2ND FLOOR LIGHTING PLAN
E-2.3 3RD FLOOR LIGHTING PLAN
E-2.4 4TH FLOOR LIGHTING PLAN
E-2.5 ROOF LIGHTING PLAN
E-2.6 1ST FLOOR POWER PLAN
E-2.6A ORANGE EV SPECSHEET, ELEVATOR MACHINE RM, ELEVATOR
SHAFT & NOTE
E-2.7 2ND FLOOR POWER PLAN
E-2.8 3RD FLOOR POWER PLAN
E-2.9 4TH FLOOR POWER PLAN
E-2.10 ROOF POWER PLAN
E-3.1 UNIT A1 & A2
E-3.2 UNIT A3 & B1
E-3.3 UNIT B2
E-3.4 UNIT C1
E-3.5 UNIT C2
E-3.6 UNIT D1
E-4.1 NORMAL PHOTOMETRIC FIRST FLOOR
E-4.2 NORMAL PHOTOMETRIC SECOND FLOOR
E-4.3 NORMAL PHOTOMETRIC THIRD FLOOR
E-4.4 NORMAL PHOTOMETRIC FOURTH FLOOR
E-4.5 NORMAL PHOTOMETRIC ROOF FLOOR
E-4.6 EGRESS PHOTOMETRIC FIRST FLOOR
E-4.7 EGRESS PHOTOMETRIC SECOND FLOOR
E-4.8 EGRESS PHOTOMETRIC THIRD FLOOR
E-4.9 EGRESS PHOTOMETRIC FOURTH FLOOR
E-4.10 EGRESS PHOTOMETRIC ROOF FLOOR
E-4.11 LIGHTING SPECIFICATIONS
E-5.1 TITLE 24 LTO OUTDOOR FORMS
E-5.2 TITLE 24 LTI INDOOR FORMS
E-5.3 TITLE 24 ELC ELECTRICAL POWER DISTRIBUTION FORMS
PLUMBING
P-0.1 GENERAL NOTES & SHEET INDEX
P-0.2 MATERIAL AND FIXTURE SCHEDULES
P-0.3 CALCULATIONS
P-0.4 FIXTURE SCHEDULES & CALCULATIONS
P-0.5 SPECIFICATIONS
P-1.1 SITE PLAN
P-2.1A 1ST FLOOR PLAN - COLD/HOT WATER
P-2.2A 2ND FLOOR PLAN - COLD/HOT WATER
P-2.3A 3RD FLOOR PLAN - COLD/HOT WATER
P-2.4A 4TH FLOOR PLAN - COLD/HOT WATER
P-2.5A ROOF PLAN - COLD/HOT WATER
P-2.1B 1ST FLOOR PLAN - NATURAL GAS
P-2.2B 2ND FLOOR PLAN - NATURAL GAS
P-2.3B 3RD FLOOR PLAN - NATURAL GAS
P-2.4B 4TH FLOOR PLAN - NATURAL GAS
P-2.5B ROOF PLAN - NATURAL GAS
P-2.1C 1ST FLOOR PLAN - WASTE/VENT PIPING AND FC CONDENSATE P-2.2C 2ND FLOOR PLAN - WASTE/VENT PIPING AND FC CONDENSATE P-2.3C 3RD FLOOR PLAN - WASTE/VENT PIPING AND FC CONDENSATE P-2.4C 4TH FLOOR PLAN - WASTE/VENT PIPING AND FC CONDENSATE P-2.5C ROOF PLAN - VENT THRU ROOF
P-2.1D 1ST FLOOR PLAN - STORM DRAIN
P-2.2D 2ND FLOOR PLAN - STORM DRAIN
P-2.3D 3RD FLOOR PLAN - STORM DRAIN
P-2.4D 4TH FLOOR PLAN - STORM DRAIN
P-2.5D ROOF PLAN - STORM DRAIN
P-3.1A UNIT PLAN - COLD/HOT WATER AND FC CONDENSATE
P-3.2A UNIT PLAN - COLD/HOT WATER AND FC CONDENSATE
P-3.3A UNIT PLAN - COLD/HOT WATER AND FC CONDENSATE
P-3.4A UNIT PLAN - COLD/HOT WATER AND FC CONDENSATE
P-3.1B UNIT PLAN - NATURAL GAS
P-3.2B UNIT PLAN - NATURAL GAS
P-3.3B UNIT PLAN - NATURAL GAS
P-3.4B UNIT PLAN - NATURAL GAS
P-3.5B UNIT PLAN - NATURAL GAS
P-4.1 DIAGRAMS
P-4.2 DIAGRAMS
P-4.3 DIAGRAMS
P-4.4 DIAGRAMS
P-4.5 DIAGRAMS
P-4.6 DIAGRAMS
P-4.7 DIAGRAMS
P-4.8 DIAGRAMS
P-4.9 DIAGRAMS
P-4.10 DIAGRAMS
P-4.11 DIAGRAMS
P-4.12 DIAGRAMS
P-4.13 DIAGRAMS
P-4.14 DIAGRAMS
P-4.15 DIAGRAMS
P-4.16 DIAGRAMS
P-D.1 DETAILS
P-D.2 DETAILS
TITLE 24
T24-MM TITLE 24 FORMS MANDATORY MEASURES
T24-1 TITLE 24 ENERGY COMPLIANCE FORMS APARTMENT
T24-2 TITLE 24 ENERGY COMPLIANCE FORMS APARTMENT CONT.
T24-3 TITLE 24 ENERGY COMPLIANCE FORMS APARTMENT CONT.
LANDSCAPE
TS-01 TITLE SHEET
LC-01 CONSTRUCTION PLAN
LC-02 CONSTRUCTION PLAN
LC-02 CONSTRUCTION DETAILS
LC-03 CONSTRUCTION NOTES & SPECIFICATIONS
LI-01 IRRIGATION PLAN
LI-02 IRRIGATION PLAN
LI-03 IRRIGATION DETAILS
LI-04 IRRIGATION DETAILS
LI-05 IRRIGATION DETAILS
LI-06 IRRIGATION SPECIFICATIONS
LP-01 PLANTING PLAN
LP-02 PLANTING PLAN
LP-02 PLANTING DETAILS & NOTES
LP-03 PLANTING SPECIFICATIONS
GENERAL
A001 TITLE SHEET
A002 CLIMATE ACTION PLAN CHECKLIST
CIVIL
C-1 TENTATIVE TRACT MAP TITLE SHEET
C-2 PRELIMINARY GRADING PLAN
C-3 SECTIONS AND DETAILS
C-4 DMA EXHIBIT / ROOF PLAN
ARCHITECTURAL
A101 ARCHITECTURAL SITE PLAN
A102 PLAN DIAGRAMS
A103 ELEVATION DIAGRAMS
A104 ELEVATION DIAGRAMS
A201 1ST FLOOR PLAN
A202 2ND FLOOR PLAN
A203 3RD FLOOR PLAN
A204 4TH FLOOR PLAN
A205 ROOF PLAN
A301 EXTERIOR ELEVATIONS
A302 EXTERIOR ELEVATIONS
A303 EXTERIOR PERSPECTIVES
A401 BUILDING SECTIONS
A402 BUILDING SECTIONS
A601 UNIT PLANS - UNIT A1
A602 UNIT PLANS - UNIT A2
A603 UNIT PLANS - UNIT A3
A604 UNIT PLANS - UNIT B1
A605 UNIT PLANS - UNIT B2
A606 UNIT PLANS - UNIT C1
A607 UNIT PLANS - UNIT C2
A608 UNIT PLANS - UNIT D1
LANDSCAPE
LC-01 SITE LANDSCAPE PLAN
LC-02 2ND FLOOR AMENITY DECK
LC-03 WATER CONSERVATION AND USE DIAGRAMS
LC-04 WATER CALCULATIONS AND DETAILS
LC-05 CONCEPTUAL LIGHTING PLAN - GROUND LEVEL
LC-06 CONCEPTUAL LIGHTING PLAN - 2ND FLOOR
SHEET INDEX
(E) EXISTING
ABV ABOVE
AC ACOUSTICAL
ACC ACCESSIBLE
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
ADA AMERICANS W/ DISABILITIES ACT
ADD'L ADDITIONAL
ADJ ADJUSTABLE
AFF ABOVE FINISH FLOOR
ALUM ALUMINUM
AN ANODIZED
AP ACCESS PANEL
APPROX APPROXIMATE
ASYM ASYMMETRICAL
BATT BATTING
BD BOARD
BLDG BUILDING
BLW BELOW
BM BEAM
BO BOTTOM OF
BTWN BETWEEN
BUR BUILT-UP ROOFING
BYD BEYOND
CAB CABINET
CEMT CEMENTITIOUS
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CMU CONCRETE MASONRY UNIT
CNTR COUNTER
CONC CONCRETE
CONT CONTINUOUS
CORR CORRIDOR
CPT CARPET
CTR CENTER
DBL DOUBLE
DF DRINKING FOUNTAIN
DIA DIAMETER
DS DOWNSPOUT
DTL DETAIL
DWG DRAWING
EA EACH
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
EMER EMERGENCY
EP ELECTRICAL PANEL
EQ EQUAL
EQPT EQUIPMENT
EX EXISTING
EXT EXTERIOR
FA FIRE ALARM
FAC FIN FACTORY FINISH
FAU FORCED AIR UNIT
FC FIBER CEMENT
FD FLOOR DRAIN
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FG FINISH GRADE
FIN FINISH
FL FLUORESCENT
FLR FLOOR
FLR SNK FLOOR SINK
FLSH'G FLASHING
FO FACE OF
FR FRENCH DOOR
FRP FIBER REINFORCED PLASTIC
FS FINISH SURFACE
FT FOOT OR FEET
FTG FOOTING
FURR FURRING
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GL GLASS
GYP GYPSUM
HB HOSE BIBB
HC HOLLOW CORE
HD HOT DIPPED
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HOUR
HT HEIGHT
ID INSIDE DIAMETER
IN INCHES
INSUL INSULATION
INT INTERIOR
JST JOIST
LAV LAVATORY SINK
MANUF MANUFACTURER
MAX MAXIMUM
MDF MEDIUM DENSITY FIBERBOARD
MECH MECHANICAL
MIN MINIMUM
MIR MIRROR
MNT MOUNTED
MO MASONRY OPENING
MS MOP SINK
MTL METAL
MTR METER
MTRL MATERIAL
MUL MULLION
NIC NOT IN CONTRACT
NOM NOMINAL
NTS NOT TO SCALE
O/ OVER
O/FL OVERFLOW DRAIN
OC ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
OPP OPPOSITE
OSCI OWNER SUPPLIED CONTRACTOR INSTALLED
OVHD OVERHEAD
PART PARTITION
P-LAM PLASTIC LAMINATE
PLSTR PLASTER
PLT PLATE
PLYWD PLYWOOD
PNT PAINT(ED)
PR PAIR
PREFIN PRE-FINISHED
PV PHOTOVOLTAIC
PWDR POWDER
R RADIUS
RAG RETURN AIR GRILLE
RB RESILIENT BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RE/S RE-SAWN
RECSS'D RECESSED
REF REFERENCE
REFL REFLECTED
REFRIG
REFRIGERATOR
REQ'D REQUIRED
RES RESILIENT
RF'G ROOFING
RM ROOM
RMC RECESSED MEDICINE CABINET
RO ROUGH OPENING
RP RAISED PANEL
RR RESTROOM
SC SOLID CORE
SCHED SCHEDULE
SECT SECTION
SH SHELF
SHT SHEET
SHT'G SHEATHING
SHWR SHOWER
SIM SIMILAR
SIP STRUCTURAL INSULATED PANEL
SMF SHEET METAl FLASHING
SPEC SPECIFICATION
SS STAINLESS STEEL
SSG STRUCTURAL SILICONE GLAZED
STD STANDARD
STL STEEL
STRUCT STRUCTURAL
SUSP SUSPENDED
SWM SELF-ADHERING WATERPROOF MEMBRANE
T&G TONGUE & GROOVE
TB TOWEL BAR
TEL TELEPHONE
THRESH THRESHOLD
TO TOP OF
TPH TOILET PAPE HOLDER
TS TUBE STEEL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VAV VARIABLE AIR VOLUME
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VIF VERIFY IN FIELD
W WIDTH
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WH WATER HEATER
WR WATER RESISTANT
ABBREVIATIONS
NOTE: AB 2097
1. PURSUANT TO CALIFORNIA ASSEMBLY BILL 2097, THE
CITY IS PROHIBITED FROM REQUIRING PARKING FOR
PROJECTS LOCATED WITHIN ONE-HALF MILE OF A MAJOR
TRANSIT STOP. THE INTENT OF THIS LEGISLATION IS TO
PROVIDE FLEXIBILITY FOR PROJECT DESIGN,
CONCURRENT WITH PLANNING STUDIES THAT HAVE
SHOWN THAT PARKING SHOULD BE MARKET DRIVEN.
DEVELOPERS COULD STILL VOLUNTARILY PROVIDE
ONSITE PARKING, BUT THE NUMBER OF PARKING SPACES
PROVIDED WILL BE BASED ON BUILDER PREFERENCE
AND MARKET DEMAND, NOT BY CITY-ESTABLISHED
MINIMUM PARKING STANDARDS.
PROJECT INFORMATION
ADDRESS: 2747 - 2775 ROOSEVELT STREET LOT AREA ACRE SF
CARLSBAD, CA .69 AC 30,116 SF
APNs: 203-101-12
203-181-16
203-181-10
DEVELOPMENT REGULATIONS
BASE ZONE VILLAGE CENTER DISTRICT MIN MAX
DENSITY 28 DU / AC 35 DU / AC
COMMUNITY PLAN V-B (VILLAGE BARRIO)
HEIGHT LIMIT 45 FT
SETBACKS FRONT MIN. 0 FT 4 STORIES
MAX 5 FT
GROUND FLOOR HEIGHT 14 FT
SIDE MIN: 0 FT
OPT: 0 FT PRIVATE OPEN SPACE MIN. DIM. 6 FT
MIN. AREA 60 SF/DU
REAR MIN: 10 FT
OPT: 0 FT COMMON OPEN SPACE MIN. DIM. 10 FT
MIN. AREA 15 SF/DU
SIDE STREET MAX: 0 FT
DENSITY BONUS
BASE DENSITY .69 AC x 35 DU / AC
= 24.2 DU 25 DU
SET ASIDE UNITS (DB) 3% = .75 DU 1 DU
15% = 3.75 DU 4 DU
5 DU
DENSITY BONUS
29% =
7.25 DU 8 DU
8 DU
TOTAL UNITS ALLOWED 33 DU
CARLSBAD INCLUSIONARY (15% MIN): 5. DU / 33. DU = 15.2%
INCENTIVES / WAIVERS
INCENTIVES AVAILABLE: 2
INCENTIVES PROPOSED: 1 TBD
2 TBD
WAIVER
HEIGHT LIMIT (ROOFTOP STRUCTURES) VBMP 2.6.2(C)(3)
WAIVER HEIGHT LIMIT (MAX BUILDING HEIGHT) VBMP 2.7-1(G)(1) WAIVER 30% MAX OF 4TH FLOOR FAÇADE (0 FT SETBACK) VBMP 2.7-1(G)(3)(a) WAIVER 80% 4TH FLOOR TO 3RD FLOOR AREA VBMP 2.7-1(G)(3)(b) WAIVER 40-FT LENGTH FAÇADE W/ 5-FT VARIATION VBMP 2.7-1(H)(1) WAIVER 80% GROUND FLOOR USE ALONG ROOSEVELT VBMP 2.7-1(I)(1) WAIVER UTILITIES / EQUIPMENT SCREENING VBMP ODS 2.6(A)(1) WAIVER UPPER STORIES TO OCCUPY FULL GROUND FLOOR FOOTPRINT VBMP ODS 4.8(C)(2) WAIVER MINIMUM VERTICAL CLEARANCE TO CANTILEVER AT SHOPFRONT VBMP ODS 6.3(D)(4) WAIVER 10 FT STEPBACK AT 3RD AND 4TH FLOOR FOR 25 FT VBMP ODS 7.2(B) WAIVER STANDARD STALL SIZE AT ENCLOSED PARKING GARAGE CMC 21.44.060(A)(3)
UNIT TABULATION
UNIT # DU SF / DU NRSF
A1 6 756 SF 4,536 SF
A2 6 1,701 SF 10,206 SF
A3 3 1,121 SF 3,363 SF
SUB-TOTAL 15 18,105 SF
B1 3
1,560 SF 4,680 SF
B2 3 1,665 SF 4,995 SF
SUB-TOTAL 6 9,675 SF
C1 3 1,956 SF 5,868 SF
C2 3 2,131 SF 6,393 SF
SUB-TOTAL 6 12,261 SF
D1 6 2,586 SF 15,516 SF
SUB-TOTAL 6 15,516 SF
TOTAL DU 33 55,557 SF
AVERAGE UNIT SIZE: 1,684 SF
BUILDING AREA
NRSF / SALES SF 59,577 SF
RESIDENTIAL 55,557 SF
COMMERCIAL #1 1,069 SF
COMMERCIAL #2 1,167 SF
COMMERCIAL #3 1,183 SF
STORAGE (GARAGE) 295 SF
STORAGE (TYP) 3 FLR X 102 SF/FLR 306 SF
HABITABLE AREA 446 SF
LOBBY 446 SF
ACCESSORY AREA 2,247 SF
FIRE RISER CLOSET (1ST) 64 SF
PARCEL ROOM (1ST) 66 SF
BOILER ROOM (ROOF) 218 SF
ELECTRICAL ROOM (1ST) 345 SF
LOW VOLTAGE (1ST) 180 SF
IDF (COMBINED) 3 FLR
X 38 SF/FLR 114 SF
TRASH ROOM (1ST) 336 SF
TRASH CHUTES 3 FLR X 112 SF/FLR 336 SF
BIKES (1ST) 295 SF
ELEV INVERT ROOM (1ST) 111 SF
ELEV MACH ROOM (1ST) 182 SF
CIRCULATION 6,600 SF
ELEVATORS 84 SF X 5 FLR 420 SF
STAIR 1 (TYP) 193 SF X 4 FLR 772 SF
STAIR 1 (1ST) 259 SF X 1 FLR 259 SF
STAIR 2 (TYP) 192 SF X 4 FLR 768 SF
STAIR 2 (1ST) 241 SF X 1 FLR 241 SF
HALL (TYP) 1,380 SF X 2 FLR 2,760 SF
HALL (2ND) 1,380 SF X 1 FLR 1,380 SF
TOTAL GROSS FLOOR AREA (GFA) 68,870 SF
EFFICIENCY (EXCLUDES GARAGE) 87.2%
GARAGE 16,682 SF
F.A.R. PROPOSED 2.3
PARKING (MINIMUM REQUIREMENTS)
ADA EV
CBC 11B CGC CHAPTER 5
RATIO 1:170 # RATIO # TABLE 11B.208.2 TABLE 5.106.5.3.1 COMMERCIAL 1 1,069 SF 0 0
COMMERCIAL 2 1,167 SF 0 0
COMMERCIAL 3 1,183 SF 0 0
TOTAL 3,419 SF 170 20.1 0
(RANGE 10-25)
REQUIRED 21 0 1 4 "EV CAPABLE"
PROVIDED 21 2 4 "EV CAPABLE"
(1 VAN, 3 STANDARD)
ADA EV
CBC 1109A.4 CGC CHAPTER 4
RATIO # RATIO #
ASSIGNED (2%) 4.106.4.2.2
1 BR 15 DU 1 15 0 0
2 BR 6 DU 1 6 0 0
3 BR 6 DU 1.5 9 0 0
4 BR 6 DU 1.5 9 0 0
TOTAL 33 DU 39.0 0
(EV-READY 40% & 10%)
REQUIRED 39 0 1 READY (40%) = 9
READY W/ CHG (10%) = 3
PROVIDED 21 1 9 "READY"
(STANDARD) &
3 "READY W/ CHG"
(1 ADA/VAN, 2 STANDARD)
TOTAL PARKING PROVIDED 42
PARKING NOTES 1 SITE IS WITHIN 1/2 MILE OF A MAJOR TRANSIT STOP 2 AB 2097 EXEMPTS PROJECT FROM ANY PARKING MINIMUMS
SHORT-TERM LONG-TERM
PUBLIC 6
SUPPLEMENTAL RESIDENTIAL REGULATIONS
PRIVATE EXTERIOR OPEN SPACE
REQUIRED: 33 DU x 60 SF/DU 1,980 SF
PROPOSED: 6,321 SF
A1 6 DU x 65 SF/DU 390 SF
A2 6 DU x 158 SF/DU 948 SF
A3 3 DU x 81 SF/DU 243 SF
B1 3 DU x 161 SF/DU 483 SF
B2 3 DU x 218 SF/DU 654 SF
C1 3 DU x 240 SF/DU 720 SF
C2 3 DU x 207 SF/DU 621 SF
D1 6 DU x 377 SF/DU 2,262 SF
COMMON OPEN SPACE
REQUIRED: 33 DU x 15 SF/DU 495 SF
PROPOSED: 590 SF
COURTYARD (MEETING MINIMUM DIMENSION) 590 SF
TRASH TRASH RECYCLE GREEN
RESIDENTIAL: 288 SF 288 SF 288 SF 864 SF
PROPOSED: 336 SF
TRASH SUMMARY TABLE
15 1BR 15
6 2BR 12 1/3 LANDFILL = 3.9 CY
6 3BR 18 1/3 RECYCLE = 3.9 CY
6 4BR 24 1/3 ORGANIC = 3.9 CY
TOTAL OCCUPANTS 69 4.9 LBS 200 LBS CY
PROPOSED 350 SF ROOM W/ (3) 4 CY CAPACITY DUMPSTERS TO BE EMPTIED OUT TWICE PER WEEK (3) TRASH & (3) RECYCLING 65 GALLON BINS HAVE BEEN PROVIDED FOR COMMERCIAL EXISTING 58 SF TRASH ENCLOSURE W/ (2) 65 & (2) 35 GALLON CART BINS
TRASH NOTES
1 PER ENVIRONMENTAL PROTECTION AGENCY, THIS IS THE AVERAGE TRASH BY PERSON PER POUND PER DAY 2 AVERAGE WEIGHT IN POUNDS OF HOUSEHOLD TRASH IN 1 CUBIC YARD 18%
18%
18% 3 BR
2 BR
4 BR
CALIF AB 2097
45% 1 BR
COMMERCIAL GROSS AREA CITY (REFERENCE ONLY)
RESIDENTIAL QNTY CITY (REFERENCE ONLY)
69 x 4.9 / 200 x 7 DAYS = 11.8 CY
RESIDENTIAL DWELLING UNITS TOTAL #
BEDROOMS
PER EPA
AVG TRASH (1*)
TRASH
WEIGHT IN 1
CUBIC YARD
(2*)
BICYCLE
PARKING
CITY
EXTREMELY LOW
LOW
CALIF AB 2097
TOTAL RESIDENTIAL SOLID WASTE IN CUBIC YARDS PER WEEK
LOW
1 PROJECT INFORMATION
ADDRESS: 2747 - 2775 ROOSEVELT STREET LOT AREA ACRE SF
CARLSBAD, CA .69 AC 30,116 SF
APNs: 203-101-12
203-181-16
203-181-10
DEVELOPMENT REGULATIONS
BASE ZONE VILLAGE CENTER DISTRICT MIN MAX
DENSITY 28 DU / AC 35 DU / AC
COMMUNITY PLAN V-B (VILLAGE BARRIO)
HEIGHT LIMIT 45 FT
SETBACKS FRONT MIN. 0 FT 4 STORIES
MAX 5 FT
GROUND FLOOR HEIGHT 14 FT
SIDE MIN: 0 FT
OPT: 0 FT PRIVATE OPEN SPACE MIN. DIM. 6 FT
MIN. AREA 60 SF/DU
REAR MIN: 10 FT
OPT: 0 FT COMMON OPEN SPACE MIN. DIM. 10 FT
MIN. AREA 15 SF/DU
SIDE STREET MAX: 0 FT
DENSITY BONUS
BASE DENSITY .69 AC x 35 DU / AC
= 24.2 DU 25 DU
SET ASIDE UNITS (DB) 3% = .75 DU 1 DU
15% = 3.75 DU 4 DU
5 DU
DENSITY BONUS
29% =
7.25 DU 8 DU
8 DU
TOTAL UNITS ALLOWED 33 DU
CARLSBAD INCLUSIONARY (15% MIN): 5. DU / 33. DU = 15.2%
INCENTIVES / WAIVERS
INCENTIVES AVAILABLE: 2
INCENTIVES PROPOSED: 1 TBD
2 TBD
WAIVER
HEIGHT LIMIT (ROOFTOP STRUCTURES) VBMP 2.6.2(C)(3)
WAIVER HEIGHT LIMIT (MAX BUILDING HEIGHT) VBMP 2.7-1(G)(1) WAIVER 30% MAX OF 4TH FLOOR FAÇADE (0 FT SETBACK) VBMP 2.7-1(G)(3)(a) WAIVER 80% 4TH FLOOR TO 3RD FLOOR AREA VBMP 2.7-1(G)(3)(b) WAIVER 40-FT LENGTH FAÇADE W/ 5-FT VARIATION VBMP 2.7-1(H)(1) WAIVER 80% GROUND FLOOR USE ALONG ROOSEVELT VBMP 2.7-1(I)(1) WAIVER UTILITIES / EQUIPMENT SCREENING VBMP ODS 2.6(A)(1) WAIVER UPPER STORIES TO OCCUPY FULL GROUND FLOOR FOOTPRINT VBMP ODS 4.8(C)(2) WAIVER MINIMUM VERTICAL CLEARANCE TO CANTILEVER AT SHOPFRONT VBMP ODS 6.3(D)(4) WAIVER 10 FT STEPBACK AT 3RD AND 4TH FLOOR FOR 25 FT VBMP ODS 7.2(B) WAIVER STANDARD STALL SIZE AT ENCLOSED PARKING GARAGE CMC 21.44.060(A)(3)
UNIT TABULATION
UNIT # DU SF / DU NRSF
A1 6 756 SF 4,536 SF
A2 6 1,701 SF 10,206 SF
A3 3 1,121 SF 3,363 SF
SUB-TOTAL 15 18,105 SF
B1 3
1,560 SF 4,680 SF
B2 3 1,665 SF 4,995 SF
SUB-TOTAL 6 9,675 SF
C1 3 1,956 SF 5,868 SF
C2 3 2,131 SF 6,393 SF
SUB-TOTAL 6 12,261 SF
D1 6 2,586 SF 15,516 SF
SUB-TOTAL 6 15,516 SF
TOTAL DU 33 55,557 SF
AVERAGE UNIT SIZE: 1,684 SF
BUILDING AREA
NRSF / SALES SF 59,577 SF
RESIDENTIAL 55,557 SF
COMMERCIAL #1 1,069 SF
COMMERCIAL #2 1,167 SF
COMMERCIAL #3 1,183 SF
STORAGE (GARAGE) 295 SF
STORAGE (TYP) 3 FLR X 102 SF/FLR 306 SF
HABITABLE AREA 446 SF
LOBBY 446 SF
ACCESSORY AREA 2,247 SF
FIRE RISER CLOSET (1ST) 64 SF
PARCEL ROOM (1ST) 66 SF
BOILER ROOM (ROOF) 218 SF
ELECTRICAL ROOM (1ST) 345 SF
LOW VOLTAGE (1ST) 180 SF
IDF (COMBINED) 3 FLR
X 38 SF/FLR 114 SF
TRASH ROOM (1ST) 336 SF
TRASH CHUTES 3 FLR X 112 SF/FLR 336 SF
BIKES (1ST) 295 SF
ELEV INVERT ROOM (1ST) 111 SF
ELEV MACH ROOM (1ST) 182 SF
CIRCULATION 6,600 SF
ELEVATORS 84 SF X 5 FLR 420 SF
STAIR 1 (TYP) 193 SF X 4 FLR 772 SF
STAIR 1 (1ST) 259 SF X 1 FLR 259 SF
STAIR 2 (TYP) 192 SF X 4 FLR 768 SF
STAIR 2 (1ST) 241 SF X 1 FLR 241 SF
HALL (TYP) 1,380 SF X 2 FLR 2,760 SF
HALL (2ND) 1,380 SF X 1 FLR 1,380 SF
TOTAL GROSS FLOOR AREA (GFA) 68,870 SF
EFFICIENCY (EXCLUDES GARAGE) 87.2%
GARAGE 16,682 SF
F.A.R. PROPOSED 2.3
PARKING (MINIMUM REQUIREMENTS)
ADA EV
CBC 11B CGC CHAPTER 5
RATIO 1:170 # RATIO # TABLE 11B.208.2 TABLE 5.106.5.3.1 COMMERCIAL 1 1,069 SF 0 0
COMMERCIAL 2 1,167 SF 0 0
COMMERCIAL 3 1,183 SF 0 0
TOTAL 3,419 SF 170 20.1 0
(RANGE 10-25)
REQUIRED 21 0 1 4 "EV CAPABLE"
PROVIDED 21 2 4 "EV CAPABLE"
(1 VAN, 3 STANDARD)
ADA EV
CBC 1109A.4 CGC CHAPTER 4
RATIO # RATIO #
ASSIGNED (2%) 4.106.4.2.2
1 BR 15 DU 1 15 0 0
2 BR 6 DU 1 6 0 0
3 BR 6 DU 1.5 9 0 0
4 BR 6 DU 1.5 9 0 0
TOTAL 33 DU 39.0 0
(EV-READY 40% & 10%)
REQUIRED 39 0 1 READY (40%) = 9
READY W/ CHG (10%) = 3
PROVIDED 21 1 9 "READY"
(STANDARD) &
3 "READY W/ CHG"
(1 ADA/VAN, 2 STANDARD)
TOTAL PARKING PROVIDED 42
PARKING NOTES 1 SITE IS WITHIN 1/2 MILE OF A MAJOR TRANSIT STOP 2 AB 2097 EXEMPTS PROJECT FROM ANY PARKING MINIMUMS
SHORT-TERM LONG-TERM
PUBLIC 6
SUPPLEMENTAL RESIDENTIAL REGULATIONS
PRIVATE EXTERIOR OPEN SPACE
REQUIRED: 33 DU x 60 SF/DU 1,980 SF
PROPOSED: 6,321 SF
A1 6 DU x 65 SF/DU 390 SF
A2 6 DU x 158 SF/DU 948 SF
A3 3 DU x 81 SF/DU 243 SF
B1 3 DU x 161 SF/DU 483 SF
B2 3 DU x 218 SF/DU 654 SF
C1 3 DU x 240 SF/DU 720 SF
C2 3 DU x 207 SF/DU 621 SF
D1 6 DU x 377 SF/DU 2,262 SF
COMMON OPEN SPACE
REQUIRED: 33 DU x 15 SF/DU 495 SF
PROPOSED: 590 SF
COURTYARD (MEETING MINIMUM DIMENSION) 590 SF
TRASH TRASH RECYCLE GREEN
RESIDENTIAL: 288 SF 288 SF 288 SF 864 SF
PROPOSED: 336 SF
TRASH SUMMARY TABLE
15 1BR 15
6 2BR 12 1/3 LANDFILL = 3.9 CY
6 3BR 18 1/3 RECYCLE = 3.9 CY
6 4BR 24 1/3 ORGANIC = 3.9 CY
TOTAL OCCUPANTS 69 4.9 LBS 200 LBS CY
PROPOSED 350 SF ROOM W/ (3) 4 CY CAPACITY DUMPSTERS TO BE EMPTIED OUT TWICE PER WEEK (3) TRASH & (3) RECYCLING 65 GALLON BINS HAVE BEEN PROVIDED FOR COMMERCIAL EXISTING 58 SF TRASH ENCLOSURE W/ (2) 65 & (2) 35 GALLON CART BINS
TRASH NOTES
1 PER ENVIRONMENTAL PROTECTION AGENCY, THIS IS THE AVERAGE TRASH BY PERSON PER POUND PER DAY 2 AVERAGE WEIGHT IN POUNDS OF HOUSEHOLD TRASH IN 1 CUBIC YARD 18%
18%
18% 3 BR
2 BR
4 BR
CALIF AB 2097
45% 1 BR
COMMERCIAL GROSS AREA CITY (REFERENCE ONLY)
RESIDENTIAL QNTY CITY (REFERENCE ONLY)
69 x 4.9 / 200 x 7 DAYS = 11.8 CY
RESIDENTIAL DWELLING UNITS TOTAL #
BEDROOMS
PER EPA
AVG TRASH (1*)
TRASH
WEIGHT IN 1
CUBIC YARD
(2*)
BICYCLE
PARKING
CITY
EXTREMELY LOW
LOW
CALIF AB 2097
TOTAL RESIDENTIAL SOLID WASTE IN CUBIC YARDS PER WEEK
LOW
1 PROJECT INFORMATION
ADDRESS: 2747 - 2775 ROOSEVELT STREET LOT AREA ACRE SF
CARLSBAD, CA .69 AC 30,116 SF
APNs: 203-101-12
203-181-16
203-181-10
DEVELOPMENT REGULATIONS
BASE ZONE VILLAGE CENTER DISTRICT MIN MAX
DENSITY 28 DU / AC 35 DU / AC
COMMUNITY PLAN V-B (VILLAGE BARRIO)
HEIGHT LIMIT 45 FT
SETBACKS FRONT MIN. 0 FT 4 STORIES
MAX 5 FT
GROUND FLOOR HEIGHT 14 FT
SIDE MIN: 0 FT
OPT: 0 FT PRIVATE OPEN SPACE MIN. DIM. 6 FT
MIN. AREA 60 SF/DU
REAR MIN: 10 FT
OPT: 0 FT COMMON OPEN SPACE MIN. DIM. 10 FT
MIN. AREA 15 SF/DU
SIDE STREET MAX: 0 FT
DENSITY BONUS
BASE DENSITY .69 AC x 35 DU / AC
= 24.2 DU 25 DU
SET ASIDE UNITS (DB) 3% = .75 DU 1 DU
15% = 3.75 DU 4 DU
5 DU
DENSITY BONUS
29% =
7.25 DU 8 DU
8 DU
TOTAL UNITS ALLOWED 33 DU
CARLSBAD INCLUSIONARY (15% MIN): 5. DU / 33. DU = 15.2%
INCENTIVES / WAIVERS
INCENTIVES AVAILABLE: 2
INCENTIVES PROPOSED: 1 TBD
2 TBD
WAIVER
HEIGHT LIMIT (ROOFTOP STRUCTURES) VBMP 2.6.2(C)(3)
WAIVER HEIGHT LIMIT (MAX BUILDING HEIGHT) VBMP 2.7-1(G)(1) WAIVER 30% MAX OF 4TH FLOOR FAÇADE (0 FT SETBACK) VBMP 2.7-1(G)(3)(a) WAIVER 80% 4TH FLOOR TO 3RD FLOOR AREA VBMP 2.7-1(G)(3)(b) WAIVER 40-FT LENGTH FAÇADE W/ 5-FT VARIATION VBMP 2.7-1(H)(1) WAIVER 80% GROUND FLOOR USE ALONG ROOSEVELT VBMP 2.7-1(I)(1) WAIVER UTILITIES / EQUIPMENT SCREENING VBMP ODS 2.6(A)(1) WAIVER UPPER STORIES TO OCCUPY FULL GROUND FLOOR FOOTPRINT VBMP ODS 4.8(C)(2) WAIVER MINIMUM VERTICAL CLEARANCE TO CANTILEVER AT SHOPFRONT VBMP ODS 6.3(D)(4) WAIVER 10 FT STEPBACK AT 3RD AND 4TH FLOOR FOR 25 FT VBMP ODS 7.2(B) WAIVER STANDARD STALL SIZE AT ENCLOSED PARKING GARAGE CMC 21.44.060(A)(3)
UNIT TABULATION
UNIT # DU SF / DU NRSF
A1 6 756 SF 4,536 SF
A2 6 1,701 SF 10,206 SF
A3 3 1,121 SF 3,363 SF
SUB-TOTAL 15 18,105 SF
B1 3
1,560 SF 4,680 SF
B2 3 1,665 SF 4,995 SF
SUB-TOTAL 6 9,675 SF
C1 3 1,956 SF 5,868 SF
C2 3 2,131 SF 6,393 SF
SUB-TOTAL 6 12,261 SF
D1 6 2,586 SF 15,516 SF
SUB-TOTAL 6 15,516 SF
TOTAL DU 33 55,557 SF
AVERAGE UNIT SIZE: 1,684 SF
BUILDING AREA
NRSF / SALES SF 59,577 SF
RESIDENTIAL 55,557 SF
COMMERCIAL #1 1,069 SF
COMMERCIAL #2 1,167 SF
COMMERCIAL #3 1,183 SF
STORAGE (GARAGE) 295 SF
STORAGE (TYP) 3 FLR X 102 SF/FLR 306 SF
HABITABLE AREA 446 SF
LOBBY 446 SF
ACCESSORY AREA 2,247 SF
FIRE RISER CLOSET (1ST) 64 SF
PARCEL ROOM (1ST) 66 SF
BOILER ROOM (ROOF) 218 SF
ELECTRICAL ROOM (1ST) 345 SF
LOW VOLTAGE (1ST) 180 SF
IDF (COMBINED) 3 FLR
X 38 SF/FLR 114 SF
TRASH ROOM (1ST) 336 SF
TRASH CHUTES 3 FLR X 112 SF/FLR 336 SF
BIKES (1ST) 295 SF
ELEV INVERT ROOM (1ST) 111 SF
ELEV MACH ROOM (1ST) 182 SF
CIRCULATION 6,600 SF
ELEVATORS 84 SF X 5 FLR 420 SF
STAIR 1 (TYP) 193 SF X 4 FLR 772 SF
STAIR 1 (1ST) 259 SF X 1 FLR 259 SF
STAIR 2 (TYP) 192 SF X 4 FLR 768 SF
STAIR 2 (1ST) 241 SF X 1 FLR 241 SF
HALL (TYP) 1,380 SF X 2 FLR 2,760 SF
HALL (2ND) 1,380 SF X 1 FLR 1,380 SF
TOTAL GROSS FLOOR AREA (GFA) 68,870 SF
EFFICIENCY (EXCLUDES GARAGE) 87.2%
GARAGE 16,682 SF
F.A.R. PROPOSED 2.3
PARKING (MINIMUM REQUIREMENTS)
ADA EV
CBC 11B CGC CHAPTER 5
RATIO 1:170 # RATIO # TABLE 11B.208.2 TABLE 5.106.5.3.1 COMMERCIAL 1 1,069 SF 0 0
COMMERCIAL 2 1,167 SF 0 0
COMMERCIAL 3 1,183 SF 0 0
TOTAL 3,419 SF 170 20.1 0
(RANGE 10-25)
REQUIRED 21 0 1 4 "EV CAPABLE"
PROVIDED 21 2 4 "EV CAPABLE"
(1 VAN, 3 STANDARD)
ADA EV
CBC 1109A.4 CGC CHAPTER 4
RATIO # RATIO #
ASSIGNED (2%) 4.106.4.2.2
1 BR 15 DU 1 15 0 0
2 BR 6 DU 1 6 0 0
3 BR 6 DU 1.5 9 0 0
4 BR 6 DU 1.5 9 0 0
TOTAL 33 DU 39.0 0
(EV-READY 40% & 10%)
REQUIRED 39 0 1 READY (40%) = 9
READY W/ CHG (10%) = 3
PROVIDED 21 1 9 "READY"
(STANDARD) &
3 "READY W/ CHG"
(1 ADA/VAN, 2 STANDARD)
TOTAL PARKING PROVIDED 42
PARKING NOTES 1 SITE IS WITHIN 1/2 MILE OF A MAJOR TRANSIT STOP 2 AB 2097 EXEMPTS PROJECT FROM ANY PARKING MINIMUMS
SHORT-TERM LONG-TERM
PUBLIC 6
SUPPLEMENTAL RESIDENTIAL REGULATIONS
PRIVATE EXTERIOR OPEN SPACE
REQUIRED: 33 DU x 60 SF/DU 1,980 SF
PROPOSED: 6,321 SF
A1 6 DU x 65 SF/DU 390 SF
A2 6 DU x 158 SF/DU 948 SF
A3 3 DU x 81 SF/DU 243 SF
B1 3 DU x 161 SF/DU 483 SF
B2 3 DU x 218 SF/DU 654 SF
C1 3 DU x 240 SF/DU 720 SF
C2 3 DU x 207 SF/DU 621 SF
D1 6 DU x 377 SF/DU 2,262 SF
COMMON OPEN SPACE
REQUIRED: 33 DU x 15 SF/DU 495 SF
PROPOSED: 590 SF
COURTYARD (MEETING MINIMUM DIMENSION) 590 SF
TRASH TRASH RECYCLE GREEN
RESIDENTIAL: 288 SF 288 SF 288 SF 864 SF
PROPOSED: 336 SF
TRASH SUMMARY TABLE
15 1BR 15
6 2BR 12 1/3 LANDFILL = 3.9 CY
6 3BR 18 1/3 RECYCLE = 3.9 CY
6 4BR 24 1/3 ORGANIC = 3.9 CY
TOTAL OCCUPANTS 69 4.9 LBS 200 LBS CY
PROPOSED 350 SF ROOM W/ (3) 4 CY CAPACITY DUMPSTERS TO BE EMPTIED OUT TWICE PER WEEK (3) TRASH & (3) RECYCLING 65 GALLON BINS HAVE BEEN PROVIDED FOR COMMERCIAL EXISTING 58 SF TRASH ENCLOSURE W/ (2) 65 & (2) 35 GALLON CART BINS
TRASH NOTES
1 PER ENVIRONMENTAL PROTECTION AGENCY, THIS IS THE AVERAGE TRASH BY PERSON PER POUND PER DAY 2 AVERAGE WEIGHT IN POUNDS OF HOUSEHOLD TRASH IN 1 CUBIC YARD 18%
18%
18% 3 BR
2 BR
4 BR
CALIF AB 2097
45% 1 BR
COMMERCIAL GROSS AREA CITY (REFERENCE ONLY)
RESIDENTIAL QNTY CITY (REFERENCE ONLY)
69 x 4.9 / 200 x 7 DAYS = 11.8 CY
RESIDENTIAL DWELLING UNITS TOTAL #
BEDROOMS
PER EPA
AVG TRASH (1*)
TRASH
WEIGHT IN 1
CUBIC YARD
(2*)
BICYCLE
PARKING
CITY
EXTREMELY LOW
LOW
CALIF AB 2097
TOTAL RESIDENTIAL SOLID WASTE IN CUBIC YARDS PER WEEK
LOW
1 DEVELOPMENT SUMMARY DEVELOPMENT SUMMARY
RINCON ROOSEVELT
2747 - 2775 ROOSEVELT STREET - CARLSBAD, CA 92008
date
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Exhibit 6
Sept. 29, 2026
Item #9 Page 21 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 - 2775 ROOSEVELT STREET - CARLSBAD, CA 92008
2317
sheet
CLIMATE ACTION PLAN CHECKLIST
A002
Stephen Dalton Architects
444 S. CEDROS. STUDIO 185
SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916 CT 2024-0008 / SDP 2024-0002
P-30 Page 1 of 8 Revised 6/22
Development Services
Planning Division
1635 Faraday Avenue
(442) 339-2610
www.carlsbadca.gov
CLIMATE ACTION PLAN
CONSISTENCY CHECKLIST
P-30
PURPOSE
In September 2015, the City of Carlsbad adopted a Climate Action Plan (CAP) that outlines actions that the city will undertake to achieve its proportional share of state greenhouse gas (GHG) emissions reductions. This checklist contains measures that are required to be implemented on a project-by-project basis to ensure that the specified emissions targets identified in the Climate Action Plan (CAP) are achieved. Implementation of these measures will ensure that new dev elopment is consistent with the CAP’s assumption for relevant CAP strategies toward achieving the identified greenhouse gas (GHG) reduction targets. In this manner, a project’s incremental contribution to a cumulative GHG emissions effect may be determined not to be cumulatively considerable if it complies with the requirements of the CAP, in accordance with CEQA Guidelines Sections 15064(h)(3), 15130(d), and 15183(b).* *City staff are currently not assessing the greenhouse gas impacts of California Environmental Quality Act projects by using the Climate Action Plan as a qualified GHG reduction plan under CEQA section 15183.5(b). Please consult with the Planning Department for further guidance. Additional information may be found on the Climate Action Plan Update and Vehicle Miles Traveled calculations staff report.
This checklist is intended to assist project applicants in identifying CAP ordinance requirements and demonstrate how their project fulfills those requirements. This checklist is to be completed and included in applications for new development projects that require discretionary review. The specific applicable requirements outlined in the checklist shall be re quired as conditions of project approval for CAP compliant projects with streamlined GHG emissions assessments. This checklist (i.e. Form P -30) is complementary to the checklist provided in Form B-50, which is specific to building permits and required for building permit applications.
APPLICATION SUBMITTAL REQUIREMENTS
• The completed checklist must be included in the project submittal package or building permit application. Application submittal procedures can be found on the City of Carlsbad website. This checklist is designed to assist the applicant in identifying the minimum CAP-related requirements specific to their project. However, it may be necessary to supplement the completed checklist with supporting materials, calculations or certifications, to demonstrate full compliance with CAP requirements. For example, projects that propose or require a performance approach to comply with energy-related measures will need to attach to this checklist separate calculations and documentation as specified by the ordinances.
• If an item in the checklist is deemed to be not applicable to a project, or is less than the minimum required by ordinance, an explanation must be provided to the satisfaction of the Planning Division or building official.
• The requirements in the checklist will be included in the project’s conditions of approval or issuance of building permit.
• Details on CAP ordinance requirements are available on the city’s website.
City of Carlsbad Climate Action Plan Consistency Checklist P-30 Page 2 of 8 Revised 06/22
STEP 1: LAND USE CONSISTENCY
The first step in determining CAP consistency for discretionary development is to assess the project’s consistency with the growth projections used in the development of the CAP. This section allows the city to determine a project’s consistency with the land use assumptions used in the CAP. Projects found not to be consistent with the CAP’s land use assumptions and that are projected to emit at or above the CAP screening threshold of 900 metric tons of CO2 equivalent (MTCO2e) GHG will be subject to a project-specific analysis of GHG emissions’ impact on the environment in accordance with the requirements of the California Environmental Quality Act (CEQA) . This may result in GHG-reducing mitigation measures applied as a condition of project approval in addition to compliance with the CAP ordinance requirements identified in Step 2 of this checklist.
STEP 1 Land Use Consistency
Checklist Item
(Check the appropriate box and provide an explanation and supporting documentation for your answer) Yes No A. Is the proposed project consistent with the existing General Plan land use and specific/master plan or zoning designations? OR,
If the proposed project is not consistent with the existing land use plan and zoning designations, does the project include a land use plan and/or specific plan, master plan or zoning designation amendment that would result in an equivalent or less GHG-intensive project when compared to the existing designations? If “Yes”, proceed to Step 2 of the checklist. For the second option under Question A above, provide estimated project-related GHG emissions under both existing and proposed designation(s) for comparison. GHG emissions must be estimated in accordance with the City of Carlsbad Guidance to Demonstrating Consistency with the Climate Action Plan.
If “No”, proceed to Question B.
B. The CAP established a screening threshold of 900 MTCO2e/year for new development projects to assist in determining consistency with the CAP. The types and sizes of typical projects listed below have been determined to correspond to the CAP screening threshold. Will the proposed land use change result in the construction of less than any one of the following? • Single-Family Housing: 50 dwelling units
• Multi-Family Housing: 70 dwelling units
• Office: 35,000 square feet
• Retail Store: 11,000 square feet
• Grocery Store: 6,300 square feet
• Other: If the proposed project is not one of the above types, provide a project-specific GHG emissions analysis to determine whether it is below the 900 MTCO2e/year screening threshold.
If “Yes”, proceed to Step 2 of the checklist.
If “No”, the project’s GHG impact is potentially significant and must be analyzed in accordance with CEQA. Applicant must prepare a Self-developed GHG emissions reduction program in accordance with the City of Carlsbad Guidance to Demonstrating Consistency with the Climate Action Plan to demonstrate how it would offset the increase in emissions over the existing designations. The project must incorporate each of the applicable measures identified in Step 2 to mitigate cumulative GHG emissions impacts unless the decision maker finds that a measure is infeasible in accordance with California Environmental Quality Act Guidelines Section 15091. Mitigation in lieu of or in addition to the measures in Step 2 may be required, depending on the results of the project-specific GHG impact analysis. Proceed and complete a project-specific Self-developed GHG emissions reduction program and Step 2 of the Checklist.
City of Carlsbad Climate Action Plan Consistency Checklist P-30 Page 3 of 8 Revised 06/22
STEP 2: CAP ORDINANCE COMPLIANCE REQUIREMENTS
Completion of this checklist will document a project’s compliance with CAP ordinances, and in turn, demonstrate consistency with the applicable measures and actions of the CAP. The compliance requirements in this Step 2 apply to development projects that require a building permit . All other development projects shall implement all emissions-related mitigation measures from the General Plan Update EIR.
Use the table below to determine which sections of the Ordinance Compliance checklist are applicable to your project. If your project includes alterations or additions to an existing building, please contact the Carlsbad Building Division for assistance in estimating building permit valuation, by phone at 760-602-2719 or by email at [email protected].
Estimated Building Permit Valuation (BPV): $ __________________________ Construction Type Complete Section(s) Notes:
Residential
☐ New construction 2A, 3A and 4A
☐ Alterations:
☐ BPV < $60,000 N/A All residential alterations
☐ BPV ≥ $60,000
☐ Electrical service panel upgrade
1A and 4A
4A
1-2 family dwellings and townhouses with attached
garages only
☐ BPV ≥ $200,000 1A and 4A
2B
Multi-family dwellings only where interior finishes are removed and significant site work and upgrades to
structural and mechanical, electrical, and/or plumbing
systems are proposed
BPV ≥ $1,000,000 Multi-family dwellings only where ≥$1,000,000 BPV AND affecting ≥75% existing floor area
Nonresidential
☐ New construction 1B, 2B, 3B, 4B and
5 Application Information
Project No./Name:
Property
Address/APN:
Applicant Name/Co.:
Applicant Address:
Contact Phone: Contact Email:
Contact information of person completing this checklist (if different than above):
Name: Contact Phone:
Company
name/address: Contact Email:
Rincon Roosevelt
2747 - 2775 Roosevelt Street
5315 Avenida Encinas, Suite 200 Carlsbad, CA 92008
925-708-3638
[email protected]
Jonathan Frankel / 2747 Roosevelt LLC
City of Carlsbad Climate Action Plan Consistency Checklist P-30 Page 4 of 8 Revised 06/22
☐ Alterations:
☐ BPV ≥ $200,000 or additions ≥
1,000 square feet 1B, 5
☐ BPV ≥ $1,000,000 1B, 2B and 5 Building alterations of ≥ 75% existing gross floor area ☐ ≥ 2,000 sq. ft. new roof addition 2B and 5 1B also applies if BPV ≥ $200,000 CAP Ordinance Compliance
Checklist Item
Check the appropriate boxes, explain all not applicable and exception items, and provide supporting calculations and documentation as necessary.
1. Energy Efficiency
Please refer to Carlsbad Ordinance No. CS-437 for more information when completing this section.
A. Residential addition or alteration ≥ $60,000 building permit valuation.
See Ord. CS-437.
☐ N/A ____________________________________
☐ Exception: Home energy score ≥ 7
(attach certification)
Year Built Single-family Requirements Multi-family Requirements ☐ Before 1978 Select one:
☐ Duct sealing ☐ Attic insulation ☐ Cool roof ☐ Attic insulation ☐ 1978 and later Select one:
☐ Lighting package ☐ Water heating package
☐ Between 1978 and 1990 Select one:
☐ Attic insulation ☐ Duct Sealing ☐ Cool roof
☐ 1991 and later Select one:
☐ Lighting package ☐ Water heating package
B. Nonresidential* new construction or alterations ≥ $200,000 building permit valuation, or additions ≥ 1,000 square feet.
See CALGreen Appendix A5, as amended in CS-437.
☐ N/A ____________________________________
A5.203.1.1.1
☐ Outdoor lighting: .90 Allowed Outdoor Lighting Power ☐ N/A ____________________________________ A5.203.1.1.2
☐ Restaurant service water heating (comply with California Energy Code Section 140.5, as amended) ☐ N/A ____________________________________ A5.203.1.2.1
Choose one as applicable: ☐ .95 Energy budget ☐ .90 Energy budget ☐ N/A ____________________________________ A5.211.1.**
☐ On-site renewable energy ☐ N/A ____________________________________ A5.211.3**
☐ Green power (if offered by local utility provider, 50% minimum renewable sources) ☐ N/A ____________________________________ A5.212.1
☐ Elevators and escalators ☐ N/A __________________________________ City of Carlsbad Climate Action Plan Consistency Checklist P-30 Page 5 of 8 Revised 06/22
* New CEC standards also require battery storage systems meeting the requirements if Reference Joint Appendix JA12 of the CEC.
A5.213.1
☐ Steel framing ☐ N/A __________________________________ * Includes hotels/motels and high-rise residential buildings ** For alterations ≥ $1,000,000 BPV and affecting > 75% existing gross floor area, or alterations that add 2,000 square feet of new roof addition: comply with California Energy Code section 120.10 instead.
2. Photovoltaic Systems
A. Residential new construction. Refer to Carlsbad Ordinance No. CS-437 for requirements, which amends Section 150.1(c) of the CEC for single-family residential; and Section 170.2(d) of the CEC for multi-family requirements. Note: if project includes installation of an electric heat pump water heater pursuant to Carlsbad ordinance CS-447, increase system size by .3kWdc if PV offset option is selected.
Floor Plan ID (use additional
sheets if necessary)
CFA #d.u. Calculated kWdc* Exception
☐ ________________________________________
☐ ________________________________________
☐ ________________________________________
☐ ________________________________________
Total System Size: kWdc
kWdc = (CFAx.572) / 1,000 + (1.15 x #d.u.)
*Formula calculation where CFA = conditional floor area, #du = number of dwellings per plan type If proposed system size is less than calculated size, please explain.
B. Nonresidential and hotel/motel new construction; or major alterations to nonresidential, hotel/motels, and multi-family residential ≥$1,000,000 BPV and affecting ≥75% existing floor area, or addition that increases roof area by ≥2,000 square feet. Please refer to Carlsbad Ordinance CS-437 when completing this section.*
Choose one of the following methods:
☐ Gross Floor Area (GFA) Method
GFA: ______________________ Min. System Size: ________ kWdc ☐ If < 10,000s.f. Enter: 5 kWdc
☐ If ≥ 10,000s.f. calculate: 15 kWdc x (GFA/10,000) **
**Round building size factor to nearest tenth, and round system size to nearest whole number. ☐ Time- Dependent Valuation Method
Annual TDV Energy use:*** ________________ x .80= Min. system size: __________ kWdc ***Attach calculation documentation using modeling software approved by the California Energy Commission. 756
1,724
1,559
1,683
A1
6 A2
A3
1,098
B1
B2
6 3
3 45.44
See worksheet
See worksheet
See worksheet
See worksheet
3 3,468
5 C1 1,936 CFA 3DU
C2 2,131 CFA 3 DU
D1 2,571 CFA 6 DU
City of Carlsbad Climate Action Plan Consistency Checklist P-30 Page 6 of 8 Revised 06/22
3. Water Heating
A. Residential new construction
Please refer to Carlsbad Ordinance CS-437 when completing this section. ☐ For systems serving individual dwelling units and achieving 60% of energy needed from on-site solar or recovered energy, choose one:
☐ Single 240-volt heat pump water heater AND compact hot water distribution AND Drain water heat recovery (low - rise residential only)
☐ Single 240-volt heat pump water heater AND PV system .3 kWdc larger than required. ☐ Heat pump water heater meeting NEEA Advanced Water Heating Specification Tier 3 or higher. ☐ Solar water heating system with electric backup that is either .60 solar savings fraction of 40 s.f. solar collectors. ☐ Gas or propane system with a solar water heating system and recirculation system ☐ Exception: _________________________________________________________________________________________ ☐ For systems serving multiple dwelling units and achieving 60% of energy needed from on -site solar or recovered energy, install a central water-heating system with all of the following:
☐ Recirculation system
☐ Solar water heating system that is either:
☐ .20 solar savings fraction
☐ .15 solar savings fraction, plus drain water heat recovery ☐ Exception:
B. Nonresidential new construction
Please refer to Carlsbad Ordinance CS-437 when completing this section. ☐ Water heating system derives at least 40% of its energy from one of the following (attach documentation):
☐ Solar-thermal ☐ Photovoltaics ☐ Recovered energy
☐ Water heating system is (choose one):
☐ Heat pump water heater
☐ Electric resistance water heater(s)
☐ Solar water heating system with .40 solar savings fraction ☐ Exception: _____________________________________________________________________________________________________ City of Carlsbad Climate Action Plan Consistency Checklist P-30 Page 7 of 8 Revised 06/22
Calculations: Total EVSE spaces = .10 x Total parking (rounded up to nearest whole number) EVSE Installed = Total EVSE Spaces x .50 (rounded up to nearest whole number) EVSE other= Total EVSE spaces – EVSE Installed
(EVSE other may be “Capable,” “Ready” or “Installed.”)
*Major alterations are: (1) for one and two-family dwellings and townhouses with attached garages, alterations have a building permit valuation ≥ $60,000 or include an electrical service panel upgrade; (2) for multifamily dwellings (three units or more without attached garages), alterations have a building permit valuation ≥ $200,000, interior finishes are removed and significant site work and upgrades to structural and mechanical, electrical, and/or plumbing systems are proposed.
**When new parking facilities are added, or electrical systems or lighting to existing parking facilities are added or altered and the work requires a building permit, 10% of the total number of parking spaces or altered shall be EV Capable. This is NOT a CAP checklist requirement, but is included to coordinate CEC compliance early in the planning process
B. Nonresidential new construction (includes hotels/motels) ☐ Exception : ________________________________ Total Parking Spaces
Proposed
EVSE Spaces
Capable Ready Installed Total
Calculation: Refer to the table below:
Total Number of Parking Spaces provided Number of required EV Spaces (Capable) Number of required EVSE Installed Spaces ☐ 0-9 1 1
☐ 10-25 4 1
☐ 26-50 8 2
☐ 51-75 13 3
☐ 76-100 17 5
☐ 101-150 25 6
☐ 151-200 35 9
☐ 201 and over 20 percent of total 25 percent of EV Capable
4. Electric Vehicle Charging
A. Residential - New construction and major alterations* Please refer to Carlsbad Ordinance CS-437 when completing this section. ☐ One and two-family residential dwelling alterations with no electrical panel upgrade (No EV space required) ☐ ADU (no EV space required when no additional parking facilities are added) ☐ One and two-family residential dwelling or townhouse with attached garage:
☐ One EVSE ready parking space required ☐ Exception :____________________________________ ☐ Multi-family residential: ☐ Exception :___________________________________ Total Parking Spaces
Proposed for New
Construction
EVSE Spaces
Capable
(10% of proposed)
Ready
(25% of proposed)
Installed
(5% of proposed)
Total
Total Proposed or Altered
Spaces (Major
Alterations)**
Capable
(10% of proposed)
--- --- Total
42 5
11 3
19 0
0 1
1 2
City of Carlsbad Climate Action Plan Consistency Checklist P-30 Page 8 of 8 Revised 06/22
A. List each proposed nonresidential use and gross floor area (GFA) allocated to each use.
B. Employee ADT/1,000 square feet is selected from the City of Carlsbad Employee ADT Table.
Use GFA Employee ADT/1,000 S.F. Total Employee ADT
Total ___________________
If total employee ADT is greater than or equal to 110 employee ADT, a TDM plan is required. *NOTE: Notwithstanding the 110 employee ADT threshold above, General Plan Mobility Element Policy 3-P.11 requires new development that adds vehicle traffic to vehicle LOS-exempt street facilities to implement TDM and transportation system management strategies. Please consult with City of Carlsbad Land Development Engineering (LDE) staff to determine whether this policy applies to your project.
TDM plan required: Yes ☐ No ☐
LDE Staff Verification: ☐________________ (staff initials)
5. Transportation Demand Management (TDM)
Specialty Retail
3,500
36 8 first 1k / 11 per 1k after
36 date
date
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Sept. 29, 2026
Item #9 Page 22 of 195
ROOSEVELT STREET
KENT R. PATERSON
2727 ROOSEVELT ST
PTN OF LOT 28
PM 1722
APN: 203-101-34-00
PTN OF LOT 30
MAP NO. 1722
APN: 204-070-28-00
SUBJECT PROPERTY
GROSS AREA = 30,116 SF
(0.691 AC)
PARCEL 2
PM 1339
APN: 203-181-16-00
25.0' 33.0'
58.0'
33.0'
S55°57'26"W 8.00'
N34°00'03"W 62.12'
S55°55'53"W 8.00'
N34°00'03"W
64.07'
S55°57'31"W 162.55'
N34°00'41"W 188.32'
N55°59'03"E 162.67'
N34°00'03"W
62.06'
25.0'
NE 1/2 OF NW 1/2
OF LOT 29
PM 1722
APN: 203-101-12-00
PTN OF LOT 30
MAP NO. 1722
APN: 203-181-10-00
OSTRIE FAMILY INC
2742 STATE ST
PARCEL 1
PM 1339
APN: 203-181-19-00
RALPH A STRAESSER
& CJ FIELDS
REVOCABLE TRUST
2730 STATE ST
PTN OF LOT 29
PM 1722
APN: 203-101-11-00
OSTRIE FAMILY INC
2742 STATE ST
PTN OF LOT 30
PM 1722
APN: 203-181-19-00
EISLER FAMILY
2700 STATE ST
PTN OF LOT 28
PM 1722
APN: 203-101-16-00
OSTRIE FAMILY INC
2742 STATE ST
PTN OF LOT 30
PM 1722
APN: 203-181-19-00
BEECH AVENUE
1 1ROW
ROW
2 N34°00'03"W
188.24'
11.0'
3.0'
11.0'
I5 FREEWAY
SITE
ROOSEVELT ST
MADISON ST
LAGUNA DR
CARLSBAD VILLAGE DR
GRAND AVE
OAK AVE
PINE AVE
JEFFERSON ST
HARDING ST
STATE ST
TENTATIVE TRACT MAP TITLE SHEET FOR:
40 80
120
GRAPHIC SCALE 1" = 40'
0 40
OWNER INFORMATION
DEVELOPER INFORMATION
LEGAL DESCRIPTION
SITE ADDRESS
TOPOGRAPHY
BENCHMARK
SITE ACREAGE EARTHWORK / PROJECT GRADING
ACCESS
ENGINEER OF WORK
PREPARED BY
2747 ROOSEVELT, LLC
5315 AVENIDA ENCINAS, SUITE 200
CARLSBAD, CA 92008
PH: (858) 259-8212
2747 / 2775 ROOSEVELT STREET
CARLSBAD, CA 92008
APN: 203-101-12-00, 203-181-10-00, 203-181-16-00
THE BOUNDARIES AND DIMENSIONS OF THE SURVEYED PARCEL(S) SHOWN HEREON ARE BASED ON A FIELD SURVEY. RECORD DIMENSIONS MAY VARY. THE BOUNDARIES OF ADJOINING PARCELS WERE COMPILED FROM RECORDED OR FILED DATA, AND ARE TO BE USED FOR PLANNING PURPOSES ONLY. FULL PROCEDURE OF SURVEY NOT SHOWN HEREON.
THE LOCATIONS OF UNDERGROUND UTILITIES AS SHOWN HEREON ARE BASED ON ABOVEGROUND STRUCTURES AND RECORDED DRAWINGS PROVIDED TO THE SURVEYOR. LOCATIONS OF UNDERGROUND UTILITIES/STRUCTURES MAY VARY FROM LOCATIONS SHOWN HEREON. ADDITIONAL BURIED UTILITIES/STRUCTURES MAY BE ENCOUNTERED. NO EXCAVATIONS WERE MADE DURING THE PROGRESS OF THE SURVEY. TO LOCATE ANY BURIED UTILITIES/STRUCTURES. BEFORE ANY EXCAVATIONS ARE
STARTED, THE FOLLOWING SHOULD BE CONTACTED FOR VERIFICATION OF UTILITY TYPE AND FOR FIELD LOCATIONS.
UNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA 1-800-422-4133 AERIAL MAPPING FLOWN DECEMBER 19, 2018
PREPARED BY: BHA INC.
BRYAN A. KNAPP, PE #86542DATE
PARCEL 1: (APN: 203-101-12-00)
THE NORTHEASTERLY HALF OF THE NORTHWESTERLY HALF OF LOT 29 OF SEASIDE LANDS, IN
THE CITY OF CARLSBAD, COUNTY OF SAN DIEGO, STATE OF CALIFORNIA, ACCORDING TO THE MAP THEREOF NO. 1722, FILED IN THE OFFICE OF THE COUNTY RECORDER OF SAN DIEGO COUNTY, JULY 28, 1921, THE SOUTHEASTERLY LINE OF SAID NORTHWESTERLY HALF BEING PARALLEL WITH THE NORTHWESTERLY LINE OF SAID LOT.
PARCEL 5: (APN: 203-181-10-00)
THAT PORTION OF LOT 30 OF SEASIDE LANDS, IN THE CITY OF CARLSBAD, COUNTY OF SAN DIEGO, STATE OF CALIFORNIA, ACCORDING TO MAP THEREOF NO. 1722, FILED IN THE OFFICE OF THE COUNTY RECORDER OF SAN DIEGO COUNTY, JULY 28, 1921, LYING NORTHEASTERLY OF THE NORTHEASTERLY LINE OF THE SOUTHWESTERLY 162.7 FEET OF SAID LOT 30.
EXCEPTING THEREFROM THE SOUTHEASTERLY 60.3 FEET THEREOF.
PARCEL 6: (APN: 203-181-16-00)
PARCEL 2 OF PARCEL MAP NO. 1339, IN THE CITY OF CARLSBAD, COUNTY OF SAN DIEGO, STATE
OF CALIFORNIA, FILED IN THE OFFICE OF THE COUNTY RECORDER OF SAN DIEGO COUNTY, FEBRUARY 23, 1973 AS FILE NO. 73-048297 OF OFFICIAL RECORDS.
GROSS:30,116 SF (0.691 AC)
NET DEVELOPABLE:27,600 SF (0.634 AC)
EXISTING IMPERVIOUS AREA (ONSITE):14,000 SF (0.321 AC)
PROPOSED IMPERVIOUS AREA (ONSITE):25,879 SF (0.594 AC)
INCREASE IN IMPERVIOUS AREA:11,879 SF (0.273 AC)
DISTURBED AREA (INCLUDES OFFSITE):32,022 SF (0.735 AC)
PROPOSED IMPERVIOUS AREA (INCLUDES OFFSITE): 27,997 SF (0.643 AC) EXISTING LIVABLE AREA :0 SF (0.000 AC)
(SINGLE-FAMILY DETACHED OR DUPLEX DWELLINGS ONLY)
CUT: 100 CYMAX CUT HEIGHT: 2.0 FT
FILL: 1,120 CYMAX FILL HEIGHT: 3.0 FT
IMPORT: 1,020 CY
REMEDIAL: 5,580 CY (5-FEET BELOW EXISTING GRADE)
THESE QUANTITIES ARE APPROXIMATE AND ARE SUBJECT TO CHANGE BASED ON FINAL ENGINEERING
DESIGN AND DETAILING
ROOSEVELT STREET, A PUBLIC ROAD
PREPARED BY:
PASCO, LARET, SUITER & ASSOCIATES
1911 SAN DIEGO AVE, SUITE 100
SAN DIEGO, CA 92110
PH: (858) 259-8212
THE BENCHMARK FOR THIS SURVEY IS THE CITY OF CARLSBAD SURVEY CONTROL POINT #130, AS SHOWN ON RECORD OF SURVEY 17271. A 2.5-INCH BRASS DISC IN THE SOUTHEASTERLY CORNER OF A STORM DRAIN CURB INLET AT THE NORTHEASTERLY RETURN OF GRAND AVE. AND WASHINGTON ST.
ELEVATION: 40.91 (NGVD29)
DONNA DOYLE, DAVID R. DEWHURST & DOUGLAS G. DEWHURST AS TRUSTEES UNDER TRUST DATED MARCH 13, 1990
2747 / 2775 ROOSEVELT STREET
CARLSBAD, CA 92008
GENERAL NOTES
SHEET INDEX
REFERENCED DRAWINGS
VICINITY MAP
SCALE: NTS
DENSITY CALCULATIONS
CONDOMINIUM NOTE
CT 2024-0008 / SDP 2024-0022
TENTATIVE TRACT MAP
RINCON ROOSEVELT
LAND USEMIXED-USE
NUMBER OF LOTS1 LOT
SEWER DISTRICT CITY OF CARLSBAD WASTEWATER DIVISION
WATER DISTRICTCARLSBAD MUNICIPAL WATER DISTRICT
SCHOOL DISTRICTCARLSBAD UNIFIED SCHOOL DISTRICT
ELECTRICSAN DIEGO GAS & ELECTRIC
TELEPHONEAT&T
CATVTIME WARNER CABLE
DRAINAGE BASIN / HYDROLOGIC AREACARLSBAD / BUENA VISTA CREEK
FIRECITY OF CARLSBAD
PROPOSED DENSITY33.3 DU / AC (RESIDENTIAL)
PROPOSED # OF UNITS36 UNITS (33 RESIDENTIAL + 3 COMMERCIAL)
EXISTING ZONINGVILLAGE-BARRIO (V-B)
PROPOSED ZONINGVILLAGE-BARRIO (V-B)
EXISTING MASTER PLAN DESIGNATIONVILLAGE CENTER (VC) 28-35 DU/AC PROPOSED MASTER PLAN DESIGNATIONVILLAGE CENTER (VC) 28-35 DU/AC SEWER GENERATION FIGURE1 EDU / DU (RESIDENTIAL - MULTI-FAMILY) 1 EDU / 1,800 SF (COMMERCIAL)
TOTAL SEWER GENERATION35 EDU (1 EDU * 33 DU + 1 EDU / 1,800 SF * 3,596 SF) PDF = 17,500 GDP (35 EDU * 200 GDP * 2.5)
POTABLE WATER FIGURE185 GPD / DU (RESIDENTIAL - MULTI-FAMILY) 1,500 GDP / ACRE (COMMERCIAL)
TOTAL POTABLE WATER 6,229 GDP (185 GPU * 33 DU + 1,500 GDP / 43560 SF * 3,596 SF) PRE-DEVELOPMENT PEAK DISCHARGE (Q100) 2.08 CFS (TOTAL FOR SITE) POST-DEVELOPMENT PEAK DISCHARGE (Q100) 3.58 CFS (TOTAL FOR SITE; UNMITIGATED)
2.00 CFS (TOTAL FOR SITE; MITIGATED)
TENTATIVE MAP TITLE SHEET1
PRELIMINARY GRADING PLAN2
SECTIONS AND DETAILS3
BMP EXHIBIT / ROOF PLAN4
MAP 1722
PM 1339
ROS 9164
ROS 14504
THIS IS A MAP OF AN AIRSPACE CONDOMINIUM SUBDIVISION PROJECT AS DEFINED IN SECTION 4125 OF THE CIVIL CODE OF THE STATE OF CALIFORNIA, AND IS PURSUANT TO THE SUBDIVISION MAP ACT. THIS PROJECT IS
COMPRISED OF A ONE LOT CONDOMINIUM SUBDIVISION AND CONTAINS A MAXIMUM OF 33 AIRSPACE CONDOMINIUM RESIDENTIAL UNITS AND 36 UNITS TOTAL (3X COMMERCIAL UNITS AND 33 RESIDENTIAL UNITS)
GROSS ACREAGE= 30,116 SF / 0.691 ACRES
LESS BEACHES= 0 SF / 0 ACRES
LESS PERMANENT BODIES OF WATER= 0 SF / 0 ACRES
LESS FLOODWAYS= 0 SF / 0 ACRES
LESS SIGNIFICANT WETLANDS= 0 SF / 0 ACRES
LESS SIGNIFICANT WOODLAND HABITATS= 0 SF / 0 ACRES
LESS LAND SUBJECT TO MAJOR POWER TRANSMISSION EASEMENTS = 0 SF / 0 ACRES LESS RAILROAD TRACK BEDS= 0 SF / 0 ACRES
NET ACRES= 30,116 SF / 0.691 ACRES
SLOPESAREA (SF / ACRES)DENSITY (DU)*DWELLING UNITS
0% - 25%30,116 SF / 0.691 ACRES 28-35 19.3 - 24.2 25% - 40% 0 SF / 0 ACRES 28-35 0
40% +0 SF / 0 ACRES 28-35 0
*PER THE LAND USE ELEMENT - VILLAGE CENTER (VC): 28-35 DWELLING UNITS PER ACRE TOTAL = 19.3-24.2
PLAN VIEW - SITE LAYOUT
SCALE: 1" = 40'
LEGEND
PROPERTY BOUNDARY
CENTERLINE OF ROAD
EXISTING LOT LINE
PUBLIC RIGHT-OF-WAY
EXISTING EASEMENTS
SETBACK LINE
EXISTING CONTOUR LINE
PROPOSED CONTOUR LINE
PROPOSED FLOWLINE
PROPOSED DIRECTION OF FLOW
PROPOSED 6" PCC CURB PER SDRSD G-02*
PROPOSED SAWCUT OF EXISTING PAVEMENT
PROPOSED PCC PAVEMENT*
PROPOSED TRENCH RESURFACING PER CITY OF
CARLSBAD STANDARD GS-26, GS-27, GS-28
3" AC GRIND AND OVERLAY
EXISTING FENCE
EXISTING WATER MAIN (SIZE PER PLAN)
EXISTING SEWER MAIN (SIZE PER PLAN)
EXISTING GAS MAIN (SIZE PER PLAN)
PROPOSED 1" IRRIGATION WATER SERVICE, METER,
AND BACKFLOW PER CMWD STANDARD W-3, W-6
PROPOSED DOMESTIC WATER SERVICE, METER,
AND BACKFLOW PER CMWD STANDARD W-4, W-6
(SIZE PER PLAN)
PROPOSED PVC PRIVATE STORM DRAIN PIPING
(SIZE PER PLAN)
PROPOSED 6" FIRE WATER SERVICE AND 6" DDCVA
BACKFLOW PER CMWD STANDARD W-9
PROPOSED PVC SEWER LATERAL AND CLEANOUT
WITH 12" CAST IRON LID PER CITY OF CARLSBAD
STANDARD S-6 (SIZE PER PLAN)
PROPOSED PCC DRIVEWAY APRON PER SDRSD
G-14A* (WIDTH PER PLAN)
PROPOSED RETAINING MASONRY WALL
PROPOSED RAISED PLANTER BIOFILTRATION BMP
*AS MODIFIED BY CITY OF CARLSBAD STANDARDS
XX
WW
SS
GG
W
64 64
SS
SS
N
W
WW
SDSD
EASEMENT / DEDICATION NOTES
PROPOSED 11.0' AND 3.0' WIDE PUBLIC UTILITY EASEMENT AND PUBLIC
STREET EASEMENT TO THE CITY OF CARLSBAD
PROPOSED 5.0' WIDE SEWER EASEMENT TO THE CITY OF CARLSBAD 1 J:\ACTIVE JOBS\4183 RINCON ROOSEVELT\CIVIL\DRAWING\DISCRETIONARY PLANS 14 BASIS OF BEARINGS
THE BASIS OF BEARINGS FOR THIS SURVEY IS THE CALIFORNIA COORDINATE SYSTEM, NAD 83 (CCS83) [EPOCH 1991.35], ZONE 6, AS DETERMINED LOCALLY BY A LINE BETWEEN FIRST ORDER CONTROL STATIONS 122 AND 130 BEING A GRID BEARING OF S 63°33'34" W AS DERIVED FROM GEODETIC VALUES SHOWN ON RECORD OF SURVEY 17271 (CITY OF CARLSBAD SURVEY CONTROL), FILED ON FEBRUARY 8, 2002 AS FILE NUMBER 2002-0112862 IN THE OFFICE OF THE COUNTY RECORDER OF SAN DIEGO COUNTY.
C
EXISTING EASEMENTS NOTES
ITEMS 1 THROUGH 9 ARE NON MAPPING ITEMS AND HAVE BEEN
OMITTED HEREON.
RINCON ROOSEVELT
2747/2775 ROOSEVELT STREET
CT 2024-0008 / SDP 2024-0022 / PUD 2024-0008
LOT LINE NOTE
PORTIONS OF EXISTING LOTS 29 & 30 AS SHOWN ON MAP 1722 AND EXISTING PARCEL 2 AS SHOWN ON MAP 1339 WILL BE CONSOLIDATED INTO ONE LOT TO CREATE 23 AIRSPACE CONDOMINIUM RESIDENTIAL UNITS AND 26 UNITS TOTAL (3X COMMERCIAL UNITS AND 23 RESIDENTIAL UNITS)
2 TRAFFIC NOTES
EXISTING:
AVERAGE DAILY TRAFFIC GENERATED 117 TRIPS / DAY
(8 DU * 6 TRIPS / DU + 1,735 SF * 40 TRIPS / 1000 SF)*** AM PEAK HOUR (RESIDENTIAL)4 PEAK HOUR (1 INBOUND / 3 OUTBOUND) PM PEAK HOUR (RESIDENTIAL)4 PEAK HOUR (3 INBOUND / 1 OUTBOUND) AM PEAK HOUR (COMMERCIAL)2 PEAK HOUR (1 INBOUND / 1 OUTBOUND) PM PEAK HOUR (COMMERCIAL)6 PEAK HOUR (3 INBOUND / 3 OUTBOUND) PROPOSED:
AVERAGE DAILY TRAFFIC GENERATED (PROPOSED) 344 TRIPS / DAY (33 DU * 6 TRIPS / DU + 3,662 SF * 40 TRIPS / 1,000 SF)*** AM PEAK HOUR (RESIDENTIAL)16 PEAK HOUR (3 INBOUND / 13 OUTBOUND) PM PEAK HOUR (RESIDENTIAL)17 PEAK HOUR (12 INBOUND / 5 OUTBOUND) AM PEAK HOUR (COMMERCIAL)5 PEAK HOUR (3 INBOUND / 2 OUTBOUND) PM PEAK HOUR (COMMERCIAL)14 PEAK HOUR (7 INBOUND / 7 OUTBOUND) AVERAGE DAILY TRAFFIC GENERATED (NET) 227 TRIPS / DAY INCREASE ***PER "BRIEF GUIDE OF VEHICULAR TRAFFIC GENERATION RATES FOR THE SAN DIEGO REGION" BY SANDAG DATED APRIL 2002:
SPECIALTY RETAIL/STRIP COMMERCIAL (40 TRIPS / 1,000 SF) CONDOMINIUM OR ANY MULTI-FAMILY >20 DU/AC (6 TRIPS / 1 DU) ROS 17188
PM 21084
ROS 22811
Sept. 29, 2026
Item #9 Page 23 of 195
Sept. 29, 2026
Item #9 Page 24 of 195
PL
APN: 203-101-34-00FF = 43.5
5.7'
4.0'
11.5'
0.33'
(41.1 FG)
47.8 TW
43.9 BW@FG
BMP #3
46.8 FG
EXISTING GRADE
PROPOSED RETAINING MASONRY WALL
PER STRUCTURAL DESIGN WITH
42" CABLE RAIL FENCE PER LS PLANS
PROPOSED RAISED PLANTER
BIOFILTRATION BMP (TYP.);
SEE DETAIL THIS SHEET
PROPOSED SWALE
43.6 FG
4.5'
PLAPN: 203-181-09-00
FF = 43.5
6.1'
4.0'
11.7'
0.33'
(43.2 FG)
50.0 TW
45.7 BW@FG
BMP #2
49.0 FG
PROPOSED RETAINING MASONRY WALL
PER STRUCTURAL DESIGN WITH
42" CABLE RAIL FENCE PER LS PLANS
PROPOSED RAISED PLANTER
BIOFILTRATION BMP (TYP.);
SEE DETAIL THIS SHEET
PROPOSED SWALE
45.4 FG
4.5'
**REMEDIAL
GRADING CUT
5.0'APPROX. EX. BUILDING FOOTING;
CONFIGURATION UNKNOWN
EX. BUILDING ~42.0 FF
APPROX. EX. BUILDING FOOTING;
CONFIGURATION UNKNOWN
PROPOSED STEM WALL
PROPOSED STEM WALL
REMEDIAL GRADING "ABC" SLOT CUT
1:1 INFLUENCE LINE
REMEDIAL GRADING
"ABC" SLOT CUT
1:1 INFLUENCE LINE 1:1 REMEDIAL
CONFORM TRANSITION
1:1 REMEDIAL
CONFORM TRANSITION
X
X
12"/14"
PONDING DEPTH
PER BMP TABLE
12"/14"
11" LAYER OF 3/4"
CLEAN CRUSHED ROCK
4" THICK CHOKER COURSE
OF 3/8" PEA GRAVEL
18" THICK LAYER OF
ENGINEERED SOIL; *SEE
NOTE BELOW
STRUCTURALLY
DESIGNED RAISED
PLANTER BOX; DESIGN
BY OTHERS
PLANTER WATERPROOFING;
IMPERVIOUS LINER ALONG THE
SIDES AND BOTTOM OF THE BASIN
ROOF DOWNSPOUT PIPE
DEEP ROOTED, DENSE,
DROUGHT TOLERANT
PLANTING SUITABLE FOR
WELL-DRAINED SOIL
CATCH BASIN BY BROOKS PRODUCTS
OR APPROVED EQUAL FOR EMERGENCY
OVERFLOW; SIZE PER PLANS
PVC OUTLET
PIPE; SIZE PER
PLAN (TYP.)
3"
6" DIAMETER
PERFORATE
UNDERDRAIN PIPE
PLANTER WATER
PROOFING
IMPERVIOUS LINER
FS ELEV.
PER PLAN
TW ELEV. =
BMP FG + 12"
3" HARDWOOD
MULCH
CLEANOUT /
INSPECTION PORTFREEBOARD PER
BMP TABLE
*BIOFILTRATION "ENGINEERED SOIL" LAYER SHALL BE EVENLY MIXED COMPOSITION OF WASHED SAND, SANDY LOAM TOPSOIL, AND HUMIC COMPOST. THE MIX SHALL CONTAIN 65% SAND, 20% TOPSOIL, AND 15% COMPOST OR HARDWOOD MULCH IN ACCORDANCE WITH COUNTY OF SAN DIEGO LID BIOSWALE MEDIA BIO65 CUT SHEET.
GUTTERLINE
SAWCUT LINE
3.0' MIN
2.0' MIN
6" PCC CURB & GUTTER
PER SDRSD G-02
STRUCTURAL SECTION 4" AC
OVER 6" CLASS II AB OVER NATIVE
SUBGRADE COMPACTED TO 95%
REL. COMP.
COLD PLAN AND OVERLAY (3" MIN.
DEPTH) TO PROVIDE SMOOTH
TRANSITION
EXISTING AC PAVEMENT
XXX
X
EV CAPABLE EV CAPABLE EV CAPABLEADA VAN
EV CAPABLE
EV READYEV READY EV READY
EV READY
EV READY EV READYEV READYEV READY
EV READY
ADA VAN
EV READY
W/ CHARGER
EV READY
W/ CHARGER
EV READY
W/ CHARGER
COMPACTCOMPACTCOMPACT
COMPACT COMPACT COMPACT
COMPACT
COMPACTCOMPACT
COMPACTCOMPACT COMPACT COMPACTCOMPACTCOMPACT
COMPACT COMPACT COMPACT COMPACT COMPACT
COMPACT COMPACT COMPACT COMPACT COMPACT COMPACT COMPACT B
A
A
B
ROOSEVELT STREET
C
C
PL
3.0'
11.0'
14.0' PKWY
22.0' TO TC
22.0' TO TC
69.0'
VARIES
(3-5%)
PROPOSED AC
PAVEMENT SAWCUT
EX. CURB AND
GUTTER
PROP. 6" PCC CURB AND
GUTTER PER SDRSD G-02
EX. SIDEWALK
EX. 6" ACP WATER MAIN
EX. 8" VCP SEWER MAIN
CL
(3-5%)
ROW
2.0%
EX. 1.5" GAS MAIN
PROP. 4" PCC SIDEWALK
PER SDRSD G-07
SUBJECT
PROPERTY
2.5'
8.5'
PROP./EX. TREE
36.0'
PL
EX.
3.0' / 11.0'
DEDICATION
PL
COMMERCIAL #1
FF = 44.0
3.3'
17.5'
43.9 TC
(43.4 FL)
48.5 TW
44.0 BW@FG
BMP #1
47.5 FG
EXISTING GRADE
PROPOSED RAISED PLANTER
BIOFILTRATION BMP (TYP.);
SEE DETAIL THIS SHEET
3.5'
PLAPN: 203-181-19-00
FF = 43.5
7.1'
(40.8 FG)
41.3 FG
14.0'
1.5%
ROOSEVELT
STREET
PROPOSED 4" PCC SIDEWALK
PER SDRSD G-7
PROPOSED 6" CURB AND
GUTTER PER SDRSD G-02
SAWCUT EXISTING AC PAVEMENT
PER DETAIL THIS SHEET**REMEDIAL
GRADING CUT
EXISTING 6" VCP SEWER
~32.7 IE
5.0'
PROPOSED DEEPENED
FOOTING
5.0'
SEWER ESMT
1:1 INFLUENCE LINE
1:1 INFLUENCE LINE REMEDIAL GRADING
"ABC" SLOT CUT
11.0'3.0'
1:1 REMEDIAL
CONFORM TRANSITION
REMEDIAL GRADING
"ABC" SLOT CUT
1:1 REMEDIAL
CONFORM TRANSITION
4" ATRIUM GRATE
WALL DRAINAGE
(CRUSHED
AGGREGATE, TYP.)
4" FRENCH DRAIN TO
OUTLET THROUGH
WALL FACE OR
CONNECT TO PVT S.D.
LEVEL OR SLOPED
BACKFILL PER PLAN
WATERPROOFING
H = EXPOSED
HEIGHT OF WALL
TW = TOP OF WALL
AT FINISHED
SURFACE
BW = BOTTOM OF
WALL AT
FINISHED GRADE
PCC CURB &
GUTTER (SIZE
PER PLAN)
PCC CURB &
GUTTER (SIZE
PER PLAN)
BB
A
A
18" WIDE CURB CUT
CENTERED ON TREE
WELL (SEE DETAIL D-D)
SPLASH PAD
PER GS-5.06
LIMITS OF STRUCTURAL SOIL
BELOW (4' DEEP X 10' X 9')
15' DIAMETER CANOPY STREET
TREE WITH 360 CF MIN
STRUCTURAL SOIL
LIMITS OF 30 MIL PLASTIC
IMPERMEABLE LINER ALONG
SIDES OF STRUCTURAL SOIL
6" THICK, 18" DEEPENED
EDGE SIDEWALK TREATMENT,
SEE SECTION B-B BELOW
TREE WELL GRATE COVER 4' X 4'
CONSTRUCT CONTIGUOUS
PCC SIDEWALK
ROOT
BALL
10.0' LIMITS OF STRUCTURAL SOIL
6" SAND FILTER
LAYER
ROOT BARRIER
PER SDRSD L-6
30 MIL PLASTIC
IMPERMEABLE LINER
*48" DEEP STRUCTURAL
SOIL; STRUCTURAL PER
A-1 STRUCTURAL SOIL OR
APPROVED EQUAL
DEEP ROOT TREE
BUBBLER PER
SDRSD DWG I-4
UNCOMPACTED SUBGRADE 8"
ROOT BARRIER
PER SDRSD L-6
30 MIL PLASTIC
IMPERMEABLE LINER
3"
MULCH
5.0'
4.0' TREE GRATE FRAME
9" X 30" TREE
GRATE SUPPORT
4" X 8 SMOOTH DOWELS
@ 18" OC, GREASED ON
ONE END, TYP. ALL SIDES
PER SDC GS DS GS-1.02
#4 @ 18" O.C. BOTH WAYS
PER SDC GS DS GS-1.02
INSTALL 30 MIL PLASTIC IMPERMEABLE
LINER WHERE CONCRETE IS POURED OVER
ENGINEERED SOIL (TYP.)
4' X 4' CASCADE TREE GATE FRAME WITH
COATED IRON IN MATT BLACK FINISH BY
URBAN ACCESSORIES; INSTALL GRATE
PER MANUFACTER'S SPECIFICATIONS
3"
6" PCC C&G
PER SDRSD G-2
STREET FLOW
COMPACTED
SUBGRADE
9.0' LIMITS OF STRUCTURAL SOIL
ROOT BARRIER
PER SDRSD L-6
30 MIL PLASTIC
IMPERMEABLE LINER
48" DEEP STRUCTURAL
SOIL; STRUCTURAL PER
A-1 STRUCTURAL SOIL
OR APPROVED EQUAL
DEEP ROOT TREE
BUBBLER PER
SDRSD DWG I-4
UNCOMPACTED SUBGRADE
3" MIN MULCH
LAYER
4" OPENING FOR
DRAINAGE
30 MIL PLASTIC
IMPERMEABLE LINER
SPLASH
PAD PER SDC GS
DS GS-5.06
6"8"
PCC SIDEWALK PER
SDRSD G-7
4.0' TREE GRATE FRAME
4" X 8" SMOOTH DOWELS
@ 18" OC, GREASED ON
ONE END, TYP. ALL SIDES
PER SDC GS DS GS-1.00
CURB CUT PER
DETAIL THIS
SHEET
4' X 4' CASCADE TREE GATE FRAME
BY URBAN ACCESSORIES; INSTALL
GRATE PER MANUFACTER'S
SPECIFICATIONS
6" SAND
FILTER LAYER
COMPACTED
SUBGRAED
ROOT BARRIER
PER SDRSD L-6
9" X 30" TREE
GRATE SUPPORT
3"
ROOT
BALL
4.0'
PL
#4 @ 18" O.C. BOTH WAYS
PER SDC GS DS GS 1-.00
TOP OF 6" PCC C>OP OF 6" PCC C&G
4.5'
FLOWLINE
(PER PLAN)
FLOWLINE
(PER PLAN)1" GUTTER DEPRESSION
@ TREE WELL
1" VERTICAL GUTTER TRANSITION OVER 1'
HORIZONTAL
1.5' CURB CUT
OPENING 1.0' 1.0'
7"
1"
2.5'
6" PCC C&G PER
SDRSD G-2
STREET FLOW
COMPACTED
SUBGRADE
CURB CUT PER
DETAIL THIS
SHEET
30 MIL PLASTIC
IMPERMEABLE LINER
AND ROOT BARRIER
9" X 30" PCC TREE
GRATE SUPPORT PER
SDRSD L-4
SPLASH PAD PER
GS-5.06
12"
12"
9" x 30" x 12" DEEP TYPE 1 SPLASH PAD PER
SDC DS GS-5.06 (NO. 2 COARSE
AGGREGATE ROCK)
R=6" (TYP.)
6" PCC C&G PER SDRSD G-02 GUTTER LIP
2.5' 1.0' 1.0'
AA
B
B
18" CURB CUT OPENING CENTERED AT
TREE WELL LOCATION AS SHOWN ON
SHEET 4
GUTTER LIP
4.5' GUTTER DEPRESSION
6" PCC C&G PER SDRSD G-02
EXISTING GRADE
PLAPN: 203-181-09-00
FF = 43.5
6.1'
4.0'
11.7'
0.33'
(42.3 FG)
50.0 TW
45.0 BW@FG
BMP #2
49.0 FG
PROPOSED RAISED PLANTER
BIOFILTRATION BMP (TYP.);
SEE DETAIL THIS SHEET
PROPOSED SWALE
44.7 FG
4.5'
**REMEDIAL
GRADING CUT
EXISTING FREESTANDING WALL
TO BE PROTECTED IN PLACE
PROPOSED STEM WALL
RETAINING WALL DRAINAGE
PER DETAIL THIS SHEET
REMEDIAL GRADING
"ABC" SLOT CUT
1:1 REMEDIAL
CONFORM TRANSITION
PROPOSED RETAINING MASONRY WALL
PER STRUCTURAL DESIGN WITH
42" CABLE RAIL FENCE PER LS PLANS
X
STORM DRAIN PIPE
(SIZE PER PLAN)
520-C-2500 PCC
CONCRETE
PCC HEADWALL
THICKNESS=8"
J:\ACTIVE JOBS\4183 RINCON ROOSEVELT\CIVIL\DRAWING\DISCRETIONARY PLANS 34 SECTIONS AND DETAILS FOR:
SECTION B-B
NOT TO SCALE
SECTION A-A
NOT TO SCALE
TYPICAL DETAIL - AC PAVEMENT SAWCUT
NOT TO SCALE
TYPICAL DETAIL - RAISED PLANTER
NOT TO SCALE
PLAN VIEW - SECTION KEY MAP
SCALE: 1" = 60'
TYPICAL SECTION - ROOSEVELT STREET
NOT TO SCALE
RINCON ROOSEVELT
2747/2775 ROOSEVELT STREET
CT 2024-0008 / SDP 2024-0022 / PUD 2024-0008
TYPICAL DETAIL - RETAINING
WALL DRAINAGE
NOT TO SCALE
PLAN VIEW - TREE WELL W/ GRATE
MODIFIED SDC GS DS GS-1.00, GS-1.02, GS-1.05
NOT TO SCALE
SECTION A-A - TREE WELL W/ GRATE
MODIFIED SDC GS 1.02
NOT TO SCALE
SECTION B-B - TREE WELL W/ GRATE
MODIFIED SDC GS 1.02
NOT TO SCALE
PLAN VIEW - CURB CUT @ TREE WELL
MODIFIED SDC GS DS GS-5.01
NOT TO SCALE
SECTION A-A - CURB CUT @ TREE WELL
MODIFIED SDC GS DS GS-5.01
NOT TO SCALE
SECTION B-B - CURB CUT @ TREE WELL
MODIFIED SDC GS DS GS-5.01
NOT TO SCALE
SECTION C-C
NOT TO SCALEBMP TABLE
PONDING
BMP 1
6"
BMP 2
6"
BMP 3
6"
BMP 4
8"
FREEBOARD6" 6" 6" 6"
BMP 5
8"
6"
SCALE: NOT TO SCALE
TYPICAL DETAIL - MODIFIED CUTOFF WALL
**REMEDIAL GRADING NOTE: ANTICIPATED LIMITS OF REMEDIAL GRADING SHOWN HEREON PER GOETECHNICAL ENGINEER RECOMMENDATIONS. NO OFFSITE GRADING IS PROPOSED. SLOT
CUTTING IS ANTICIPATED IN ACCORDANCE WITH THE RECOMMENDATIONS IN THE LETTER FROM GEOTEK, INC. TITLED TEMPORARY EXCAVATION RECOMMENDATIONS DATED APRIL 30, 2025 Sept. 29, 2026
Item #9 Page 25 of 195
X X X X X X
X X X X X X X X X X X X X X X X X
X
X
X X
X
X X
X
X
X
XXXXXXXXXXXXXXXXXXXXXXXXXXX
X
X X
X X X X
X
X
X
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X XXXX
XXX X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
GGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGGG
W
W W W
S
S
S
S S
S S
S
S
S
S S
S
S
S
S S
S
S
S
S S
S
S
S
S S
X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X X XX X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
W W WS S S S S S S S S S S S S
S
S S S S S S S S S S S S S
W
W
W
W
W
WW
W
W
W
W
WW
W
W
W
W
WW
W
W
W
W
WW
W
WW E
C
E
45 45
45 44
44 44
44 44
44 44
44 43
43 43
43 43
43 43
43 42
42 42
42 42
42 41
41 41
41 4040
1 STORY
BLDG
1 STORY
BLDG
2 STORY
BLDG
1 STORY
BLDG
STAIRS
X
XXXXXXXXXXXXX
XXXXXXXXXXXXX
X
EV CAPABLE EV CAPABLE EV CAPABLEADA VAN
EV CAPABLE
EV READYEV READY EV READY
EV READY
EV READY EV READYEV READY EV READY
EV READY
ADA VAN
EV READY
W/ CHARGER
EV READY
W/ CHARGER
EV READY
W/ CHARGER
COMPACTCOMPACTCOMPACT
COMPACT COMPACT COMPACT
COMPACT
COMPACTCOMPACT
COMPACTCOMPACT COMPACT COMPACTCOMPACTCOMPACT
COMPACT COMPACT COMPACT COMPACT COMPACT
COMPACT COMPACT COMPACT COMPACT COMPACT COMPACT COMPACT
F F F F F
S S S S
S S S S
CC
W W W W W
WV
WV
WV
WM
SD SD SD
SD
SD
SD SD SD SD SD SD
W W W W W
W W W W W
W W W W WWM
WM
WM
SD SD SD SD
WW
WWW
W
W
W
WWW
W
W
W
WWW
W
W
W
W
S55°57'26"W
8.00'
N34°00'03"W 62.12'
S55°55'53"W
8.00'
N34°00'03"W 64.07'
S55°57'46"W 162.64'
N34°00'41"W 188.32'
S55°59'03"W 162.67'
N34°00'03"W 62.06'
ROOSEVELT STREET
APN: 203-181-09-00
APN: 203-101-11-00
APN: 203-181-19-00
BMP #1
A = 49 SF
BMP #2
A = 272 SF
BMP #3
A = 324 SF
BMP #5
A = 219 SF
BMP #4
A = 144 SF
POINT OF
DISCHARGE #3
POINT OF
DISCHARGE #1
POINT OF
DISCHARGE #2
(184 SF) DE MINIMIS
DMA PER BMP DESIGN
MANUAL 5.2.2
(2,269 SF) SELF-MITIGATING
AREA PER BMP DESIGN
MANUAL 5.2.1
APN: 203-101-34-00
2ND FLOOR
AMENITY COURTYARD
DMA 1
AREA = 1,344 SF
(0.031 AC)
DMA 2
AREA = 5,553 SF
(0.127 AC)
DMA 3
AREA = 11,409 SF
(0.262 AC)
DMA 5
AREA = 4,329 SF
(0.099 AC)
DMA 4
AREA = 3,456 SF
(0.079 AC)
PROPOSED
TREE WELL
DMA 6
AREA = 10,639 SF
(0.244 AC)
X
X
XX
X
X X
X
X X
X
X
X
X
GGGGGGGGGGGGG
S S S S
S
S S S S
W
WW
W
W
W
W
W
W
WWWW E
C
E
46 46
46 46
46 45
45 45
45 45
45 44
44 44
44 44
44 44
43 43
43 43
42 42
42 F
SS
CC
W
WV
WV
WV
WM
SD
W
W
W
WM
WM
WM
SD
W
WW
W
DY
H
ROOSEVELT STREET
HIGH POINT
~(47.0 TC)
~(46.5 FL)
PROPOSED
TREE WELL
DMA 6
AREA = 10,639 SF
(0.244 AC)
GRAPHIC SCALE: 1" = 10'
010'20'30'
J:\ACTIVE JOBS\4183 RINCON ROOSEVELT\CIVIL\DRAWING\DISCRETIONARY PLANS
SITE PLAN
SCALE : 1" = 10'
RINCON ROOSEVELT
2747/2775 ROOSEVELT STREET
CT 2024-0008 / SDP 2024-0022 / PUD 2024-0008
44 DMA EXHIBIT / ROOF PLAN FOR:
BMP / PLANTER OUTLET SCHEMATIC
DMADRAINS TO OUTLET PIPE
DRAINS TO
ULTIMATE
POINT OF
DISCHARGE
1BMP 1
(SURFACE)
2 SIDEWALK UNDERDRAIN
1 BMP 2
(SURFACE)
3 4
BMP 3
(SURFACE)
BMP 4
(SURFACE)
CURB OUTLET PER
SDRSD D-25
BMP 5
(SURFACE)
2 3
1 5SIDEWALK UNDERDRAIN1
WATER QUALITY CALCULATIONS - ROOF PLAN
DMAAREA (SF)IMPERVIOUS
(SF)
MINIMUM
BIOFILTRATION
REQUIRED (SF)
PLANTER AREA
PROVIDED (SF)
11,3441,2433449
25,5535,531150272
311,409 11,355307324
43,4563,31790144
54,3294,249115219
DMA
LOCATION
2ND FLR
BMP
LOCATION
1ST FLR
1ST FLR
1ST FLR
ROOF
2ND FLR
2ND FLR
SIDEWALK UNDERDRAIN
SIDEWALK UNDERDRAIN ROOF
ROOF
ROOF
SEE DETAIL A FOR CONTINUATION
DETAIL A
SCALE : 1" = 40'
LEGEND
PROPERTY BOUNDARY
CENTERLINE OF ROAD
ADJACENT PROPERTY LINE / RIGHT-OF-WAY
EXISTING CONTOUR LINE
PROPOSED CONTOUR LINE
LIMIT OF AREA DISTURBED
DMA DRAINAGE BASIN BOUNDARY
PROPOSED / REMOVED AND REPLACED IMPERVIOUS
AREA WITHIN DISTURBED AREA OF SITE
PROPOSED PLANTER / BMP AREA
SELF-MITIGATING AREA PER CITY OF CARLSBAD BMP
DESIGN MANUAL SECTION 5.2.1
DE MINIMIS AREA PER CITY OF CARLSBAD BMP
DESIGN MANUAL SECTION 5.2.2
ROUTINE MAINTENANCE AREA PER BMP DESIGN
MANUAL SECTION 1.3
EQUIVALENT AREA SWAP TAKEN (1,076 SF)
(EXISTING AND NEW / REPLACED IMPERVIOUS AREA
BYPASSING TREATMENT)
EQUIVALENT AREA SWAP GIVEN (1,076 SF)
OFFSITE TRIBUTARY AREA TO TREE WELL NOT
SUBJECT TO POLLUTANT REQUIREMENTS
64 64
GROUNDWATER INFORMATION
SOIL TYPE INFORMATION
SOIL: TYPE B SOILS PER WEB SOIL SURVEY APPLICATION AVAILABLE
THROUGH UNITED STATES DEPARTMENT OF AGRICULTURE
TREATMENT CONTROL BMPS
BIOFILTRATION BASIN BF-1
COARSE SEDIMENT YIELD
NO CRITICAL COARSE SEDIMENT YIELD AREAS TO BE PROTECTED.
REFER TO PRIORITY DEVELOPMENT PROJECT SWQMP PREPARED
BY PASCO, LARET, SUITER & ASSOCIATES
TOTAL GROSS SITE AREA29,107 SF (0.67 AC)
EXISTING IMPERVIOUS AREA14,000 SF (0.32 AC)
EXISTING PERVIOUS AREA15,107 SF (0.35 AC)
TOTAL AREA DISTURBED BY PROJECT (ONSITE)28,544 SF (0.66 AC) TOTAL PROPOSED / REPLACED IMPERVIOUS AREA (ONSITE) 25,879 SF (0.59 AC) TOTAL AREA DISTURBED BY PROJECT (TOTAL)32,022 SF (0.74 AC) TOTAL PROPOSED / REPLACED IMPERVIOUS AREA (TOTAL) 27,997 SF (0.64 AC)
PROJECT SITE - AREA CALCULATIONS
GROUNDWATER ENCOUNTERED AT DEPTHS BETWEEN 9' AND 13.5' PER
PRELIMINARY GEOTECHNICAL INVESTIGATION PERFORMED BY
ADVANCED GEOTECHNICAL SOLUTIONS, INC.
Sept. 29, 2026
Item #9 Page 26 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 - 2775 ROOSEVELT STREET - CARLSBAD, CA 92008
2317
sheet
ARCHITECTURAL SITE PLAN
A101
Stephen Dalton Architects
444 S. CEDROS. STUDIO 185
SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916 CT 2024-0008 / SDP 2024-0002 Grass
5003
42.62 WV
5007
42.05 SDGE HH
5008
42.17 COR VAULT
5009
42.21 COR VAULT
5010
42.13 COR VAULT
5011
42.12 COR VAULT
5012
42.03 CATV BOX
5013
42.11 WM
5014
39.94 EOC
5015
40.12 EOC
5016
40.21 EOC
5017
40.03 EOC
5018
45.33 FW
5019
45.10 FW/END
5020
44.99 FENCE/INTERSECTION
5021
45.63 FENCE
5022
45.58 FENCE
5023
45.88 FENCE
5024
46.36 FENCE/END
5025
46.15 BLDG/COR
5026
47.96 BLDG/COR
5027
46.45 BLDG/FACE
5028
48.90 BLDG/COR
5029
48.64 BLDG/OVERHANG
5030
54.54 BLDG/COR
5031
42.13 EOC
5032
42.38 EOC
5033
42.82 EOC
5034
43.26 EOC
5035
42.86 EOC
5036
42.97 EOC
5037
43.02 EOC
5038
42.88 EOC
5039
43.00 12IN/TREE
5040
43.81 19IN/TREE
5042
43.58 EOC
5043
43.88 EOC
5044
43.98 EOC
5045
44.42 EOC
5046
44.75 EOC
5047
44.89 EOC
5048
45.29 EOC
5049
43.55 EOC
5050
43.66 EOC
5051
43.73 EOC
5052
43.59 EOC
5053
44.26 EOC
5054
44.41 EOC
5055
44.50 EOC
5056
44.38 EOC
5057
44.37 22IN/TREE 5058
44.38 WM
5059
45.10 ST/LT
5060
45.01 SDG&EHH
5061
45.05 ATT/VAULT
5062
45.17 ATT/VAULT
5063
45.22 ATT/VAULT
5064
45.12 ATT/VAULT
5065
45.28 IRON/FENCE
5066
45.19 IRON/FENCE
5159
1FT O/S TO WD FENCE POL
5160
42.17 1FT O/S TO WD FENCE POL
5161
42.27 2FT O/S TO 8IN BLOCK WALL END
5162
43.71 2FT O/S TO 8IN BLOCK WALL POL
5163
42.86 TFC END
45 45
45 44
44 44
44 44
44 43
43 43
43 43
43 43
42 42
42 42
42 41
41 41
41 41
40 40
40 1 STORY
BLDG
1 STORY
BLDG
2 STORY
BLDG
1 STORY
BLDG
STAIRS
C C
WV
WVWV
WM WM WMWM
1 1
6 6
A FB C D E
5 5
4 4
3 3
2 2
EV CAPABLE EV CAPABLE EV CAPABLE ADA VAN
EV CAPABLE
EV READY EV READYEV READY
EV READY
EV READY EV READY EV READY EV READY
EV READY
ADA VAN
EV READY
W/ CHARGER
EV READY
W/ CHARGER
EV READY
W/ CHARGER
8.49' 122.50' 20.68'
8.00'ROW
DEDICATION
25.00' TO CENTERLINE
7.02'
STBK
11.50'
STBK
11.50'
STBK
20.00'
DRIVEWAY
44.00'
10.00'
10.00'
24.00'
28.52'
25.02'
28.99'
5.00'
MAX
FRONT
SETBACK
7.50'
7.50'
7.50'
7.50'
6.00' 6.00' 6.00'
18.49'
3.00'
PUBLIC STREET AND
UTILITY EASEMENT
8.00'
ROW
DEDICATION
5.50'
4.50'
3.50'
4.50'
20.50'
4.50'
6.13'5.37'
5.17'
3.35'
7.00'
2.25'
3.35'
5.17'
3.27'
3.80'
3.37'
5.17'
6.13' 5.61'
6.50' 5.24'
4.50' 8.25'
188.25'
01.34 32.04
05.19 01.34
33.05 01.04
01.01 10.01
02.04 12.02
02.0402.04
01.27 01.27
01.27 01.27
01.34 32.04
01.34 01.34
01.34 03.13
03.13 01.11
01.21 33.0933.09
21.01 21.01
ROOSEVELT ST
N 33° 59' 42" W 64.06'
N 34° 00' 28" W 124.20'
N 55° 57' 20" E 162.67'
N 33° 59' 38" W 62.06'
N 33° 59' 42" W 62.12'
N 55° 57' 31" E 162.55'
N
16.50'
16.50'
26.00'
DRIVE AISLE
24.00'
DRIVE AISLE
N 55° 57' 26" E 8.00' N 55° 57' 00" E 8.00'
FIRE TRUCK
10FT FROM CURB
<150' HOSE PULL
<150' HOSE PULL
STAND
PIPE
STAND
PIPE
<150' HOSE PULL<150' HOSE PULL
EXISTING FIRE
HYDRANT
STANDPIPE
@ STAIR
STANDPIPE
@ STAIR
STAIR TO ROOF
STAIR TO ROOF 32.24
32.07 32.07 32.07
02.05 33.07
33.08 33.02 33.08
33.02 PROPOSED 4-STORY
MIX-USE BUILDING
COMMERCIAL #1COMMERCIAL #2COMMERCIAL #3
LOBBY
SITE PLAN LEGEND
PROPOSED BUILDING FOOTPRINT
PROPOSED BMP BASIN: REF. CIVIL PLANS
TBD
TBD
TBD
TBD
TBD
TBD
PROJECT TEAM
DEVELOPER 2747 ROOSEVELT LLC
5315 AVENIDA ENCINAS, SUITE 200
CARLSBAD, CA 92008
949.637.3254
ARCHITECT STEPHEN DALTON ARCHITECTS
444 S CEDROS AVE, STUDIO 185
SOLANA BEACH, CA 92075
858.792.5906
CIVIL PASCO, LARET, SUITER & ASSOCIATES
535 NORTH HIGHWAY 101 SUITE A
SOLANA BEACH, CA 92075
858.259.8212
LANDSCAPE GILLESPIE MOODY PATTERSON (GMP), INC
3176 LIONSHEAD AVENUE, SUITE 102
CARLSBAD, CA 92010
858.558.8977
SMEP GOUVIS ENGINEERING
15 STUDEBAKER
IRVINE, CA 92618
949.752.1612
PROJECT
LOCATION
VICINITY MAP
GRAND AVE
STATE
ST
BEECH ST
ROOSEVELT
ST
N
FIRE NOTES
CONSTRUCTION TYPE SHALL BE IIIA
HORIZONTAL EXIT W/ MAG-HOLD DOOR SYSTEM SHALL
BE PROVIDED AT LEVELS 2, 3, AND 4.
EXTERIOR BEARING WALLS SHALL BE 2-HR RATED.
PROJECT SHALL COMPLY WITH NFPA 13 & 14
STANDARDS.
SPRINKLER DENSITY: 15/2000 SF.
STANDPIPES SHALL BE PROVIDED AT EXTERIOR AND
STAIRS 1 & 2.
STAIRS 1 SHALL EXTEND TO ROOF.
COMPLETE PLANS AND SPECIFICATIONS FOR ALL FIRE
EXTINGUISHING SYSTEMS, INCLUDING AUTOMATIC
SPRINKLER AND STANDPIPE SYSTEMS AND OTHER
SPECIAL FIRE EXTINGUISHING SYSTEMS AND RELATED
APPURTENANCE’S SHALL BE SUBMITTED TO THE CITY
OF SAN DIEGO FOR REVIEW AND APPROVAL PRIOR TO
INSTALLATION.
COMPLETE PLANS AND SPECIFICATIONS FOR FIRE
ALARM SYSTEMS SHALL BE SUBMITTED TO THE CITY OF
SAN DIEGO DEVELOPMENT SERVICES FOR REVIEW AND
APPROVAL PRIOR TO INSTALLATION. CFC 907.1.1
LOCATIONS AND CLASSIFICATIONS OF EXTINGUISHERS
SHALL BE IN ACCORDANCE WITH CFC 906 AND
CALIFORNIA CODE OF REGULATIONS (CCR), TITLE 19.
DURING CONSTRUCTION AT LEAST ONE EXTINGUISHER
SHALL BE PROVIDED ON EACH FLOOR LEVEL AT EACH
STAIRWAY, IN ALL STORAGE AND CONSTRUCTION
SHEDS, IN LOCATIONS WHERE FLAMMABLE OR
COMBUSTIBLE LIQUIDS ARE STORED OR USED, AND
WHERE OTHER SPECIAL HAZARDS ARE PRESENT PER
CFC SECTION3315.1
IN BUILDINGS THAT REQUIRE STANDPIPES, STANDPIPES
SHALL BE PROVIDED DURING CONSTRUCTION WHEN
THE HEIGHT REACHES 40 FEET ABOVE THE LOWEST
LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS. A FIRE
DEPARTMENT CONNECTION SHALL BE NO MORE THAN
100 FEET FROM THE AVAILABLE FIRE DEPARTMENT
VEHICLE ACCESS ROADWAYS. CFC SECTIONS 3310,
3313.
BUILDINGS UNDERGOING CONSTRUCTION,
ALTERATION, OR DEMOLITION SHALL CONFORM TO CFC
CHAPTER 33. WELDING, CUTTING, AND OTHER HOT
WORK SHALL BE IN CONFORMANCE WITH CFC
CHAPTER 35.
WALL, FLOOR AND CEILING FINISHES AND MATERIALS
SHALL NOT EXCEED THE INTERIOR FINISH
CLASSIFICATION IN CBC TABLE 803.9 AND SHALL MEET
THE FLAME PROPAGATION PERFORMANCE CRITERIA OF
THE CALIFORNIA CODE OF REGULATIONS, TITLE 19,
DIVISION 1. DECORATIVE MATERIALS SHALL BE
PROPERLY TREATED BY A PRODUCT OF PROCESS
APPROVED BY THE STATE FIRE MARSHAL WITH
APPROPRIATE DOCUMENTATION PROVIDED TO THE
CITY OF SAN DIEGO.
KEY BOXES SHALL BE PROVIDED FOR ALL HIGH-RISE
BUILDINGS, POOL ENCLOSURES, GATES IN THE PATH
OF FIREFIGHTER TRAVEL TO STRUCTURES, SECURED
PARKING LEVELS, DOORS GIVING TO ALARM PANELS
AND/OR ANNUNCIATORS, AND ANY OTHER
STRUCTURES OR AREAS WHERE ACCESS TO AN AREA
IS RESTRICTED.
DUMPSTERS AND TRASH CONTAINERS EXCEEDING 1.5
CUBIC YARDS SHALL NOT BE STORED IN BUILDINGS OR
PLACED WITHIN 5 FEET OF COMBUSTIBLE WALLS,
OPENINGS OR COMBUSTIBLE ROOF EAVE LINES
UNLESS PROTECTED BY AN APPROVED SPRINKLER
SYSTEM OR LOCATED IN A TYPE I OR IIA
STRUCTURE SEPARATED BY 10 FEET FROM OTHER
STRUCTURES. CONTAINERS LARGER THAN I CUBIC
YARD SHALL BE OF NON - OR LIMITED-COMBUSTIBLE
MATERIALS OR SIMILARLY PROTECTED OR SEPARATED.
CFC 304.3.
EXITS, EXIT SIGNS, FIRE ALARM PANELS, HOSE
CABINETS, FIRE EXTINGUISHER LOCATIONS, AND
STANDPIPE CONNECTIONS SHALL NOT BE CONCEALED
BY CURTAINS, MIRRORS, OR ANY OTHER DECORATIVE
MATERIAL
OPEN FLAMES, FIRE AND BURNING ON ALL PREMISES IS
PROHIBITED EXCEPT AS SPECIFICALLY PERMITTED BY
THE CITY OF SAN DIEGO AND CFC 308.
THE EGRESS PATH SHALL REMAIN FREE AND CLEAR OF
ALL OBSTRUCTIONS AT ALL TIMES. NO STORAGE IS
PERMITTED IN ANY EGRESS PATHS.
ADDRESS IDENTIFICATION SHALL BE PROVIDED FOR ALL
NEW AND EXISTING BUILDINGS IN A LOCATION THAT IS
PLAINLY VISIBLE AND LEGIBLE FROM THE STREET OR
ROAD FRONTING THE PROPERTY. WHERE ACCESS IS BY
WAY OF A PRIVATE ROAD AND THE BUILDING ADDRESS
CANNOT BE VIEWED FROM THE PUBLIC WAY, AN
APPROVED SIGN OR MEANS SHALL BE USED TO
IDENTIFY THE STRUCTURE. PREMISES IDENTIFICATION
SHALL CONFORM TO CBC SECTION 501.2.
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
11. 12.
13. 14.
15. 16.
17. 18.
19. 20.
1. REFER TO CIVIL DRAWINGS FOR LOCATION AND HEIGHTS
OF PROPERTY LINE WALLS AND FENCES
2. COMMERCIAL USES WITH RESIDENTIAL UNITS ATTACHED
SHALL PROVIDE VENTILATION SYSTEMS TO PREVENT
ODORS FROM ADVERSELY AFFECTING RESIDENTIAL
UNITS.
GENERAL NOTES
PROJECT DATA
OWNER 2747 ROOSEVELT, LLC
DEVELOPER 2747 ROOSEVELT, LLC
5315 AVENIDA ENCINAS SUITE 200
CARLSBAD, CA 92008
(949) 637-3254
APPLICATION TYPES SITE DEVELOPMENT PLAN (SDP)
TENTATIVE MAP (CT)
PROJECT NAME RINCON ROOSEVELT
PROJECT ADDRESS 2747 - 2775, ROOSEVELT STREET
CARLSBAD CA, 92008
A.P.N. 203-101-12
203-181-16
203-181-10
LEGAL DESCRIPTION A SUBDIVISION OF THE SELY 1/2 OF
LOT 29 & LOT 30 OF SEASIDE
LANDS, CARLSBAD, MAP No.1722
SITE AREA
30,116 SF (0.69 ACRE)
GENERAL PLAN VILLAGE-BARRIO (V-B)
ZONING VILLAGE CENTER (VC)
EXISTING LAND USE COMMERCIAL
PROPOSED LAND USE RESIDENTIAL
OCCUPANCY TYPE(S) R2 - RESIDENTIAL
A2 - COMMERCIAL
ALLOWED DENSITY 28-35 DU/ACRE
PROPOSED DENSITY 47.8 DU/ACRE
PROPOSED UNITS 33
ALLOWED COVERAGE N/A
PROPOSED COVERAGE 24,643 SF (82%)
CONSTRUCTION TYPE III A @ LEVELS 2-4
I A @ LEVEL 1
SETBACKS REQ'D PROPOSED
FRONT/CORNER: 0'-0" MIN/5'-0" MAX 10'-1"
SIDE: 0'-0" 11'-6"
REAR: 0'-0" 11'-5"
MAX BUILDING HEIGHT 53'-5"
APPLICABLE CODES 2022 CBC, CFC, CMC, CPC, CEC.
PHOTOVOLTAIC REQ'D: YES
KW-DC (ROOF): 3,654 SF PROVIDED
REQUIRED PARKING: 0 SPACES PURSUANT TO AB 2097
PROVIDED PARKING: 42 SPACES
EV SPACES REQUIRED: YES
EV CHARGERS: 3 REQUIRED
3 PROVIDED
EV READY: 9 SPACES REQUIRED
9 SPACES PROVIDED
EV CAPABLE: 4 SPACES REQUIRED
4 SPACES PROVIDED
REQ'D REC SPACE PRIVATE: 60 SF / UNIT
COMMON: 15 SF / UNIT
PROP'D REC SPACE PRIVATE: 6,858 SF
COMMON: 1,658 SF
SEWER DISTRICT CITY OF CARLSBAD WASTEWATER
DIVISION
WATER DISTRICT CITY OF CARLSBAD MUNICIPAL
WATER DISTRICT
SCHOOL DISTRICT
CARLSBAD UNIFIED SCHOOL
DISTRICT
SCALE: 1" = 10'1 ARCHITECTURAL SITE PLAN & FIRE ACCESS PLAN date
date
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Sept. 29, 2026
Item #9 Page 27 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
AREA DIAGRAMS
A102
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
336 sq ft
1 2
3 4
5 6
7 8
9 10
11 12
13 14 15
16 17
18 19
20 21
22 23
UP
1 2
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18 19
20 21
22 23
24 25
26 27
28 UP
295 sq ft 295 sq ft
164'-0"
FRONTAGE
15'-6"
LOBBY
24'-0"
24'-0"
26'-0"
9.4% OF FRONTAGE
1,159 sq ft
84 sq ft
259 sq ft
1,064 sq ft
1,167 sq ft
345 sq ft
64 sq ft
16,767 sq ft
66 sq ft
446 sq ft
111 sq ft 182 sq ft
180 sq ft
56 sq ft
BIKE ROOM
S-2STORAGE
S-2
ELECTRICAL
ROOM
S-2
LOBBY
R-2
COMMERCIAL #2
A-2
COMMERCIAL #1
A-2
COMMERCIAL #3
A-2
FIRE RISER
S-2
ELEV EQ
S-2
ELEV INVERT
S-2
TRASH ROOM
S-2
LOW VOLTAGE
S-2
PARCEL ROOM
R-2
ELEV EQELEV INVERT
590 sq ft
DN
1 2
3 4
5 6
7 UP
1 2
3 4
5 6
7 UP 89'-7 1/8"
10'-1"
18'-4"
8'-1"
10'-1"
6'-10"
13'-10"
3'-3"
13'-10"
6'-10"
9'-10"
8'-10"
15'-4"
8'-4"
27'-4" 29'-3"
15'-6"
38'-5"
22'-10"
22'-10" 38'-8"
50'-8" BTWN CANTILEVERS
(NO CANTILEVER CONDITION)
6'-0"
4'-6"
5'-4"
3'-4" 3'-4"
3'-6"
32'-4" CANTILEVERED
5'-0"
18'-0" 49'-3"
CANTILEVER
11'-9"
55'-6"
CANTILEVER
14'-6" 20'-0"
CANTILEVER
10'-0" 25'-9"
CANTILEVER
10'-5 1/2"
22'-9" 10'-5" 19'-1"
CANTILEVER
17'-0" 38'-8"
CANTILEVER
DN
ACCESSIBLE PATH
LINE OF 1ST FLOOR TYP
FIRE SEPARATION
DISTANCE, TYP
D1a
R-2
C1
R-2
C2
R-2A3
R-2
B2
R-2
B1
R-2
D1
R-2
A2
R-2
A1
R-2
A2
R-2
A1
R-2
DN
DN
1 2
3 4
5 6
7 UP
1 2
3 4
5 6
7 UP
15'-5 1/8"
(10FT MIN)
11'-9"
(6 FT MIN)
19'-2" 8'-10"
10'-5"
(10 FT MIN)
10'-2"
(6 FT MIN)
COMBINED PLANES
(19'-2")+(8'-10")+(17'-0") = 45 FT
ACCESSIBLE PATH
D1a
R-2
C1
R-2
C2
R-2A3
R-2
B2
R-2
B1
R-2
D1
R-2
A2
R-2
A1
R-2
A2
R-2
A1
R-2
UP DN
218 sq ft
ROOFTOP STRUCTURE AREA CALCS
ELEVATOR OVERRUN: 95 SF
STAIR 1 OVERRUN: 193 SF
BOILER ROOM: 218 SF
= 506 SF
506 SF / 23,917 SF = 2.12%
ELEVATOR
OVERRUN
STAIR 1
OVERRUN
BOILER ROOM
AREA BREAKDOWN BY FLOOR
4TH FLOOR = 19,216 SF
3RD FLOOR = 19,216 SF
2ND FLOOR = 19,216 SF
1ST FLOOR = 23,025 SF
19,216 SF / 23,025 SF = 83.45% (RATIO 2ND TO 1ST FLOOR)
AREA CALCULATIONS
GENERAL NOTES GENERAL NOTES
1. ALL FLASHING, SHEET METAL VENTS, EXHAUST FANS,
VENTILATORS, DOWNSPOUTS AND PIPE STACKS
SHALL BE PAINTED TO MATCH THE ADJACENT ROOF
OR WALL MATERIAL AND/OR COLOR.
2. ALL WINDOWS ARE RECESSED A MINIMUM OF 2".
SCALE: 1/16" = 1'-0"1 PLAN DIAGRAM - 1ST FLOOR
SCALE: 1/16" = 1'-0"2 PLAN DIAGRAM - 2ND FLOOR
SCALE: 1/16" = 1'-0"3 PLAN DIAGRAM - 3RD AND 4TH FLOORS SCALE: 1/16" = 1'-0"4 PLAN DIAGRAM - ROOF
KEYNOTES
date
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Sept. 29, 2026
Item #9 Page 28 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
ELEVATION DIAGRAMS
A103
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
28 sq ft
358 sq ft 284 sq ft
196 sq ft 541 sq ft
9 sq ft 27 sq ft 27 sq ft
128 sq ft 27 sq ft 9 sq ft
9 sq ft 30 sq ft
FSD = 38'-8"
NO LIMIT
FSD = 10'-1"
45% MAX
FSD = 8'-1"
25% MAX
FSD = 19'-3"
75% MAX
FSD = 10'-1"
45% MAX
FSD = 29'-3"
NO LIMIT
358 sq ft
284 sq ft
196 sq ft
541 sq ft
128 sq ft 27 sq ft 9 sq ft 9 sq ft
30 sq ft
358 sq ft
284 sq ft
196 sq ft
541 sq ft27 sq ft 27 sq ft 128 sq ft 27 sq ft 9 sq ft 9 sq ft 18 sq ft 27 sq ft 27 sq ft
13'-10 3/4" (10'-0" MIN)
AT CANTILEVER
(NON-SHOPFRONT)
28 sq ft 9 sq ft
17 sq ft 9 sq ft
AREA OF WALL
AREA OF OPENING(S)
PROPOSED % OF OPENINGS
10.3%
19.0% 65.3% 13.9%
10.3%
7.3%
19.0%
19.0%
65.3%
65.3% 13.9%
13.9%
GROUND FLOOR GLAZING FACADE TRANSPARENCY PER STORY
GROUND FLOOR COMMERCIAL FACADE = 1,553 sq ft
REQUIRED = 1,398 sq ft (90%)
PROVIDED = 1,407 sq ft (91%)
* GLAZING SHALL BE TRANSPARENT / TRANSLUCENT
482 sq ft 755 sq ft143 sq ft
COMMERCIAL #3
FF = 43.0'
COMMERCIAL #1
FF = 44.0'
COMMERCIAL #2
FF = 43.4'
627 sq ft90 sq ft
612 sq ft
90 sq ft
627 sq ft90 sq ft
725 sq ft
68 sq ft
725 sq ft
68 sq ft
725 sq ft 68 sq ft
15'-2" (15'-0" MIN)
AT CANTILEVER
(SHOPFRONT)
13'-0" (10'-0" MIN)
AT CANTILEVER
(NON-SHOPFRONT)
13'-6"
SHOPFRONT HEIGHT
(WAIVER)
15'-1"
SHOPFRONT HEIGHT
23 sq ft23 sq ft68 sq ft70 sq ft56 sq ft
56 sq ft
56 sq ft
70 sq ft
70 sq ft
23 sq ft23 sq ft68 sq ft
23 sq ft23 sq ft68 sq ft
27 sq ft 27 sq ft 27 sq ft 27 sq ft 27 sq ft 27 sq ft
27 sq ft 27 sq ft 27 sq ft 27 sq ft 27 sq ft 27 sq ft
3'-9"
27 sq ft 27 sq ft 27 sq ft 27 sq ft 27 sq ft 27 sq ft
AREA OF WALLAREA OF OPENING(S)
PROPOSED % OF OPENINGS
40% MINIMUM
40.2%
41.2%
40.2% 42.5%
42.5%
42.5%
GENERAL NOTES GENERAL NOTES
1. ALL FLASHING, SHEET METAL VENTS, EXHAUST FANS,
VENTILATORS, DOWNSPOUTS AND PIPE STACKS
SHALL BE PAINTED TO MATCH THE ADJACENT ROOF
OR WALL MATERIAL AND/OR COLOR.
2. ALL WINDOWS ARE RECESSED A MINIMUM OF 2".
SCALE: 1/8" = 1'-0"2 EAST / SIDE ELEVATION
SCALE: 1/8" = 1'-0"1 NORTH / FRONT ELEVATION
KEYNOTES
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Sept. 29, 2026
Item #9 Page 29 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
ELEVATION DIAGRAMS
A104
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
GENERAL NOTES GENERAL NOTES
1. ALL FLASHING, SHEET METAL VENTS, EXHAUST FANS,
VENTILATORS, DOWNSPOUTS AND PIPE STACKS
SHALL BE PAINTED TO MATCH THE ADJACENT ROOF
OR WALL MATERIAL AND/OR COLOR.
2. ALL WINDOWS ARE RECESSED A MINIMUM OF 2".
72 sq ft
247 sq ft 253 sq ft 144 sq ft
419 sq ft
144 sq ft 253 sq ft 247 sq ft
FSD = 10'-4"
45% MAX
FSD = 22'-10"
NO LIMIT
FSD = 6'-10"
25% MAX
FSD = 13'-10"
45% MAX
FSD = 3'-3"
15% MAX
FSD = 13'-10"
45% MAX
FSD = 6'-10"
25% MAX
FSD = 22'-10"
NO LIMIT
FSD = 10'-4"
45% MAX
14 sq ft14 sq ft14 sq ft14 sq ft 14 sq ft40 sq ft
72 sq ft
72 sq ft
247 sq ft 253 sq ft 144 sq ft
419 sq ft
144 sq ft 253 sq ft 247 sq ft
14 sq ft14 sq ft14 sq ft14 sq ft
72 sq ft
72 sq ft
247 sq ft 253 sq ft
144 sq ft
419 sq ft
253 sq ft
247 sq ft
14 sq ft14 sq ft14 sq ft14 sq ft
72 sq ft
15'-4" (10'-0" MIN)
AT CANTILEVER
(NON-SHOPFRONT)
144 sq ft
24 sq ft
24 sq ft
24 sq ft
24 sq ft
24 sq ft
24 sq ft
14 sq ft
14 sq ft14 sq ft
14 sq ft14 sq ft
14 sq ft
14 sq ft14 sq ft
14 sq ft14 sq ft
14 sq ft
40 sq ft
40 sq ft
40 sq ft
40 sq ft
40 sq ft
AREA OF WALL
AREA OF OPENING(S)
PROPOSED % OF OPENINGS
13.3%
13.3%
13.3%
27.8% 11.1%
11.1%
11.1%
38.9%
38.9%
38.9%
38.9%
38.9%
38.9%
11.1%
11.1%
11.1%
27.8%
27.8%
27.8%
27.8%
27.8%
42.1'
40.6'39.9'39.7'
9 sq ft
284 sq ft
9 sq ft
30 sq ft
284 sq ft
9 sq ft
30 sq ft
284 sq ft 27 sq ft
613 sq ft
153 sq ft
220 sq ft
FSD = 27'-4"
NO LIMIT
FSD = 38'-5"
NO LIMIT
FSD = 8'-4"
25% MAX
FSD = 15'-6"
75% MAX
FSD = 8'-10"
25% MAX
FSD = 15'-4"
75% MAX
FSD = 9'-10"
25% MAX
96 sq ft 27 sq ft 27 sq ft 9 sq ft
30 sq ft
27 sq ft
613 sq ft
153 sq ft
220 sq ft 96 sq ft 27 sq ft 27 sq ft
27 sq ft
613 sq ft
153 sq ft
220 sq ft 96 sq ft 27 sq ft 27 sq ft
15'-3" (10'-0" MIN)
AT CANTILEVER
(NON-SHOPFRONT)
14'-3" (10'-0" MIN)
AT CANTILEVER
(NON-SHOPFRONT)
30 sq ft
9 sq ft
30 sq ft
9 sq ft 18 sq ft
AREA OF WALL
AREA OF OPENING(S)
PROPOSED % OF OPENINGS
13.7% 12.3%
62.7%
15.2%
13.7%
13.7%
12.3%
12.3%
62.7%
62.7%
15.2%
13.2%
SCALE: 1/8" = 1'-0"1 SOUTH / REAR ELEVATION
SCALE: 1/8" = 1'-0"2 WEST / SIDE ELEVATION
KEYNOTES
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Sept. 29, 2026
Item #9 Page 30 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
1ST FLOOR PLAN
A201
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
1 1
10 10
A
A
L
L
B
B
C
C
J
J
K
K
9 9
8 8
5 5
4 4
336 sq ft
UP
UP
04'8'16'
1 A611
1 A612
1 A613
1 A614
2 A010
2 A401
2 A401
2 A402
2 A402
1 A402
1 A402
1 A010
2 A011
1 A011
1 A401
1 A401
1 A403
1 A403
2 A403
2 A403
1 A404
1 A404
2 A404
2 A404
141'-0"
165'-0"
24'-0"
1'-2"
26'-0"
1'-2"
26'-0"
1'-2"
26'-0"
1'-2"
24'-0"
18'-8" 24'-0" 18'-0" 24'-0"
165'-0"
1'-0"121'-10" 26'-0" 16'-2"
9'-0" 9'-0" 8'-0"
56'-4"
1'-6" 1'-0" 2'-6"
92'-0" 9'-10" 36'-8"
17'-2" 5'-4" 18'-8" 26'-0"
1'-2"
26'-0" 18'-8" 5'-4"
1'-2" 1'-2"
26'-0"
1'-2"
17'-2"
32'-0" 16'-4" 5'-0" 9'-8" 5'-0" 37'-6" 8'-0"
1'-6"1'-6"
5'-4"
6'-0" 9'-0" 9'-0"
1'-2"
9'-0" 4'-0"9'-0" 18'-0" 9'-0" 32'-6"
1'-6"
17'-0"
1'-2"
26'-0"
1'-2"
20'-8"17'-2" 26'-0"
1'-2"
27'-8" 1'-6"
295 sq ft 295 sq ft
3'-0"
8'-2"
7'-8"
9'-0" 8'-0" 9'-0"
9'-0" 8'-0" 9'-0"
18'-0"
9'-0" 8'-0" 9'-0"
24'-0"
BACKUP DISTANCE
18'-0"
6'-0"6'-0"
22'-6" 120'-0" 22'-6"
24'-0"
BACKUP DISTANCE
18'-0"
16'-6" 16'-6"
9'-0" 9'-0"
9'-0" 8'-0" 9'-0" 9'-0" 8'-0"
18'-0"
9'-0" 8'-0" 9'-0" 9'-0" 8'-0" 9'-0"
9'-0" 9'-0"9'-0" 9'-0"
9'-0" 9'-0" 9'-0"8'-0"9'-0"9'-0" 8'-0" 9'-0"
143'-6"
1'-4"
4'-10"23'-2"
7'-9"
(4" MIN RECESS)
18'-0" 15'-2" 14'-2" 9'-0"22'-10"
DISTANCE BETWEEN ENTRIES
19'-10"
DISTANCE BETWEEN ENTRIES
17'-2" 26'-0"
1'-2"
18'-0"
1'-2"
18'-0" 10'-6"
1'-8"
D1-01
D1-04
D1-06
D1-07
D1-08
D1-12
D1-09
D1-11
D1-10
D1-13
D1-14 D1-15
D1-16
SF1-01 SF1-02
SF1-03 SF1-04
SF1-05
SF1-06
D1-02
D1-03
10.01 33.05
01.11 32.05
03.07 32.08
14.01 32.03
01.01 32.13
32.07 05.09
32.06 01.27
14.07 12.01
01.03 21.03
32.24 02.03
05.1801.27
01.27 01.27
01.11 21.03
05.18 11.12
SF1-07
D1-05
10.14 32.26 32.26
21.01 21.01
ELECTRICAL
ROOM
LOBBY
TRASHLOW
VOLTAGE
COMMERCIAL #1COMMERCIAL #2COMMERCIAL #3
STORAGE BIKES
FR
TOTAL PARKING = 42 SPACES
ADA = 3 SPACES
EV = 16 SPACES
ELEV
ELEV
EQ
ELEV
INVERT
STAIR 1
1ST FLOOR AREA: 23,065 SF
ADA VAN
EV CAPABLE
ADA VAN
EV READY
W/ CHARGER
42 41 40 39 38 37 36 35 34 33
32 31 30 29 28 27 26 25 24 23 22 21 20 19
18 17 16 15 14 13 12
4 5 6 7 8 9 10 11
321
EV CAPABLE
N
1,159 sq ft
84 sq ft
259 sq ft
1,064 sq ft1,167 sq ft 345 sq ft
64 sq ft
16,767 sq ft
66 sq ft
446 sq ft
111 sq ft 182 sq ft180 sq ft
56 sq ft
PARCEL
ROOM GAS
METERS
COMP.
4 CY
TRASH
4 CY
REC
4 CY
T
R
T
R
T
R
33.08 33.02
21.02 21.02
21.02 STAIR 2
EV CAPABLE EV CAPABLE
EV READY
EV READYEV READY
EV READY
EV READY EV READY EV READY EV READY
EV READY
EV READY
W/ CHARGER
EV READY
W/ CHARGER
PARKING CALCULATIONS
CALCULATIONS PER CBC CH11 REQ'S
COMMERCIAL
3,465 SF / 170 SF = 21 SPACES REQ'D
CBC TABLE 11B-208.2 REQUIRES 1 ACCESSIBLE SPACE
CBC SECTION 11B-208.2.4 REQUIRES 1:6 FOR VAN SPACES
PROVIDED:
1X ADA VAN SPACE REQ'D FOR COMMERCIAL
RESIDENTIAL
42 TOTAL - 21 COMMERCIAL = 21 SPACES LEFT
CBC SECTION 1109A.3 REQUIRES 2% ACCESSIBLE
21 X 0.02 = 0.42 = 1 ACCESSIBLE SPACE
CBC 1109A.6 REQUIRES 1:8 FOR VAN SPACES
PROVIDED
:
1X ADA VAN SPACE REQ'D FOR RESIDENTIAL
----------------------------------------------------------------------------------------------
CALCULATIONS PER GREEN BUILDING REQ'S
*ALL EV SPACES MUST BE 9X18 MINIMUM*
COMMERCIAL
21 COMMERCIAL SPACES PER AREA CALCS
CGC TABLE 5.106.5.3.1 REQUIRES 4 "EV CAPABLE" ONLY
PROVIDED:
1X EV-CAPABLE VAN SPACE
3X EV-CAPABLE STANDARD SPACE
RESIDENTIAL
21 RESIDENTIAL SPACES REMAIN
40% = 8.4 = 9 SPACES "EV READY RECEPTACLES"
10% = 2.1 = 3 SPACES "EV READY W/ CHARGERS"
12 TOTAL EV-READY SPACES
CGC 4.106.4.2.2.1.1 REQUIRES 1:25 BE VAN ACCESSIBLE
PROVIDED
:
1X EV READY W/ CHARGER VAN SPACE
2X EV READY W/ CHARGER STANDARD SPACES
9X EV READY RECEPTACLE STANDARD SPACES
---------------------------------------------------------------------------------------------
TOTAL REQUIRED PARKING PROVIDED BY TYPE
COMMERCIAL
1X ADA VAN SPACE
1X ADA VAN SPACE (EV CAPABLE)
3X STANDARD SPACES (EV CAPABLE)
RESIDENTIAL
1X ADA VAN SPACE (EV READY W/ CHARGER)
2X STANDARD SPACES (EV READY W/ CHARGER)
9X STANDARD SPACES (EV READY RECEPTACLE)
WALL LEGEND WALL LEGEND
CIP CONCRETE COLUMN PER STRUCTURAL
(REFERENCE SLAB PLANS FOR COLUMN SIZE)
12" CONCRETE WALL
8" CONCRETE WALL
8" CMU WALL
2 HR 6" METAL STUD
1 HR 6" METAL STUD
NON-RATED 6" METAL STUD
SOFFIT / FLOOR ABOVE
GENERAL NOTES GENERAL NOTES
1. ALL FLASHING, SHEET METAL VENTS, EXHAUST FANS,
VENTILATORS, DOWNSPOUTS AND PIPE STACKS
SHALL BE PAINTED TO MATCH THE ADJACENT ROOF
OR WALL MATERIAL AND/OR COLOR.
2. ALL WINDOWS ARE RECESSED A MINIMUM OF 2".
01.01 01.03
01.11 01.27
02.03 03.07
05.09 05.18
10.01 10.14
11.12 12.01
14.01 14.07
21.01 21.02
21.03 32.03
32.05 32.06
32.07 32.08
32.13 32.24
32.26 33.02
33.05 33.08
PROPERTY LINE
PROPERTY LINE AFTER DEDICATION
LINE OF WALL / FLOOR ABOVE
LINE OF AWNING ABOVE
FULL HEIGHT ENCLOSURE WALL
CONCRETE COLUMN: REF. STRUCUTRAL DWGS
GARAGE GATE
INTERIOR PARTITION WALL
MAILBOXES: OPERABLE PARTS OF MAILBOXES TO BE 48" A.F.F. MAX.
PER CBC 1138A.3, ADA & USPS REGULATIONS
MAIL COUNTER
TELEPHONE ENTRY SYSTEM ACCESS CONTROL
BIKE RACKS
TRASH CHUTE
GREASE SHAFT
KNOX BOX: FIRE DEPARTMENT ACCESS
FIRE EXTINGUISHER
FIRE STANDPIPE: REF. FIRE SPRINKLER DRAWINGS
BIO FILTER PLANTER/BMP AREA: REF. CIVIL DRAWINGS &
LANDSCAPE DWGS
4" PARKING STRIPING, WHITE
4" PARKING STRIPING, ACCESSIBLE, BLUE
ACCESSIBLE LOADING AISLE
ACCESSIBLE PARKING SPACE: REF. DETAIL 18/A898
EV CAPABLE SPACE
ACCESSIBLE PATH
DETECTABLE WARNING SURFACE
FIRE BACKFLOW PREVENTER: REF. CIVIL DWGS
TRANSFORMER
WATER METER: REF. CIVIL DWGS
SCALE: 1/8" = 1'-0"1 1ST FLOOR PLAN
KEYNOTES
date
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Sept. 29, 2026
Item #9 Page 31 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
2ND FLOOR PLAN
A202
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
1 1
10 10
A
A
L
L
I
I
D
D
E
E
F
F
2 2
3 3
6 6
7 7
11 11
REF
W D
DW
REF
REF
DW
REF
DW
DW
REF
DW
REF
DW
REF
DW
REF
REF
DW
REF
DW
DW
DW
REF
WD
DNUP
UP
04'8'16'
FAU
MICRO
WINE
W/D
FAU
TRSH
MICRO
W/D
MICRO
FAU
TRSH
WINE
MICRO
FAU
W/D
TRSH
W/D
FAU
TRSH
W/D
FAU
TRSH
W/D
FAU
TRSH
MW
W/D
FAU
TRSH
MW
W/D
MICRO
FAU
TRSH
MICRO
W/DFAU
TRSH
FAU WINE
TRSH
TRSH
MICRO
62'-8 1/2" 44'-5" 39'-6 1/2"
52'-3 1/2" 36'-3 1/2" 36'-3 1/2" 52'-3 1/2"
146'-8"
177'-2"
2 A611
2 A612
2 A614
3 A303
2 A010
2 A401
2 A401
2 A402
2 A402
1 A402
1 A402
1 A010
2 A011
1 A011
1 A401
1 A401
1 A403
1 A403
1 A303
2 A303
2 A403
2 A403
1 A404
1 A404
2 A404
2 A404
19'-0" 31'-6 1/2" 22'-2" 67'-6"
2'-0"
29'-3 1/2"
144'-8"
62'-8 1/2" 10'-0"
2'-0"
34'-5 1/2" 37'-6"
10'-0"
11'-0"
13'-0"
10'-8" 15'-4"
169'-6"
54 sq ft 38 sq ft
18'-0"
5 1/2"
1/A607
201
1/A606
202
3/A609
203
1/A602
204
1/A601
205
1/A601
207
1/A602
206
1/A609
208
1/A604
209
1/A605
211
1/A603
210
D2-01
D2-03
D2-04
D2-05
D2-06
D2-02
32.03 03.04
07.08 D2-07
21.08 01.01
05.16 06.03
21.03 21.03
21.02 05.04
D2-09 D2-08
D2-10
ELEV
IDFSTO.
2ND FLOOR AREA: 19,472 SF
CL
CL CL
CL
CL
CL
CL
TR
DN
STO. STO.
STO.
H
H
G
G
N
WS
P
WS
WS
P
P
WS
WS
MW
WS
MW
P
WS
P
WS
P
WS
WS
P
P P
WS
2 A613
30'-4" 30'-4"
590 sq ft
29'-0"
COMMON
OPEN SPACE
MIN.
DIMENSION
14.07 14.01
21.02 AMENITY
COURT
STAIR 2 STAIR 1
C2
C1
D1.2
A2
A1A1
A2
D1
B1
B2
A3
FIRE NOTES
CONSTRUCTION TYPE SHALL BE IIIA
HORIZONTAL EXIT W/ MAG-HOLD DOOR SYSTEM SHALL
BE PROVIDED AT LEVELS 2, 3, AND 4.
EXTERIOR BEARING WALLS SHALL BE 2-HR RATED.
PROJECT SHALL COMPLY WITH NFPA 13 & 14
STANDARDS.
SPRINKLER DENSITY: 15/2000 SF.
STANDPIPES SHALL BE PROVIDED AT EXTERIOR AND
STAIRS 1 & 2.
STAIRS 1 SHALL EXTEND TO ROOF.
COMPLETE PLANS AND SPECIFICATIONS FOR ALL FIRE
EXTINGUISHING SYSTEMS, INCLUDING AUTOMATIC
SPRINKLER AND STANDPIPE SYSTEMS AND OTHER
SPECIAL FIRE EXTINGUISHING SYSTEMS AND RELATED
APPURTENANCE’S SHALL BE SUBMITTED TO THE CITY
OF SAN DIEGO FOR REVIEW AND APPROVAL PRIOR TO
INSTALLATION.
COMPLETE PLANS AND SPECIFICATIONS FOR FIRE
ALARM SYSTEMS SHALL BE SUBMITTED TO THE CITY OF
SAN DIEGO DEVELOPMENT SERVICES FOR REVIEW AND
APPROVAL PRIOR TO INSTALLATION. CFC 907.1.1
LOCATIONS AND CLASSIFICATIONS OF EXTINGUISHERS
SHALL BE IN ACCORDANCE WITH CFC 906 AND
CALIFORNIA CODE OF REGULATIONS (CCR), TITLE 19.
DURING CONSTRUCTION AT LEAST ONE EXTINGUISHER
SHALL BE PROVIDED ON EACH FLOOR LEVEL AT EACH
STAIRWAY, IN ALL STORAGE AND CONSTRUCTION
SHEDS, IN LOCATIONS WHERE FLAMMABLE OR
COMBUSTIBLE LIQUIDS ARE STORED OR USED, AND
WHERE OTHER SPECIAL HAZARDS ARE PRESENT PER
CFC SECTION3315.1
IN BUILDINGS THAT REQUIRE STANDPIPES, STANDPIPES
SHALL BE PROVIDED DURING CONSTRUCTION WHEN
THE HEIGHT REACHES 40 FEET ABOVE THE LOWEST
LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS. A FIRE
DEPARTMENT CONNECTION SHALL BE NO MORE THAN
100 FEET FROM THE AVAILABLE FIRE DEPARTMENT
VEHICLE ACCESS ROADWAYS. CFC SECTIONS 3310,
3313.
BUILDINGS UNDERGOING CONSTRUCTION,
ALTERATION, OR DEMOLITION SHALL CONFORM TO CFC
CHAPTER 33. WELDING, CUTTING, AND OTHER HOT
WORK SHALL BE IN CONFORMANCE WITH CFC
CHAPTER 35.
WALL, FLOOR AND CEILING FINISHES AND MATERIALS
SHALL NOT EXCEED THE INTERIOR FINISH
CLASSIFICATION IN CBC TABLE 803.9 AND SHALL MEET
THE FLAME PROPAGATION PERFORMANCE CRITERIA OF
THE CALIFORNIA CODE OF REGULATIONS, TITLE 19,
DIVISION 1. DECORATIVE MATERIALS SHALL BE
PROPERLY TREATED BY A PRODUCT OF PROCESS
APPROVED BY THE STATE FIRE MARSHAL WITH
APPROPRIATE DOCUMENTATION PROVIDED TO THE
CITY OF SAN DIEGO.
KEY BOXES SHALL BE PROVIDED FOR ALL HIGH-RISE
BUILDINGS, POOL ENCLOSURES, GATES IN THE PATH
OF FIREFIGHTER TRAVEL TO STRUCTURES, SECURED
PARKING LEVELS, DOORS GIVING TO ALARM PANELS
AND/OR ANNUNCIATORS, AND ANY OTHER
STRUCTURES OR AREAS WHERE ACCESS TO AN AREA
IS RESTRICTED.
DUMPSTERS AND TRASH CONTAINERS EXCEEDING 1.5
CUBIC YARDS SHALL NOT BE STORED IN BUILDINGS OR
PLACED WITHIN 5 FEET OF COMBUSTIBLE WALLS,
OPENINGS OR COMBUSTIBLE ROOF EAVE LINES
UNLESS PROTECTED BY AN APPROVED SPRINKLER
SYSTEM OR LOCATED IN A TYPE I OR IIA
STRUCTURE SEPARATED BY 10 FEET FROM OTHER
STRUCTURES. CONTAINERS LARGER THAN I CUBIC
YARD SHALL BE OF NON - OR LIMITED-COMBUSTIBLE
MATERIALS OR SIMILARLY PROTECTED OR SEPARATED.
CFC 304.3.
EXITS, EXIT SIGNS, FIRE ALARM PANELS, HOSE
CABINETS, FIRE EXTINGUISHER LOCATIONS, AND
STANDPIPE CONNECTIONS SHALL NOT BE CONCEALED
BY CURTAINS, MIRRORS, OR ANY OTHER DECORATIVE
MATERIAL
OPEN FLAMES, FIRE AND BURNING ON ALL PREMISES IS
PROHIBITED EXCEPT AS SPECIFICALLY PERMITTED BY
THE CITY OF SAN DIEGO AND CFC 308.
THE EGRESS PATH SHALL REMAIN FREE AND CLEAR OF
ALL OBSTRUCTIONS AT ALL TIMES. NO STORAGE IS
PERMITTED IN ANY EGRESS PATHS.
ADDRESS IDENTIFICATION SHALL BE PROVIDED FOR ALL
NEW AND EXISTING BUILDINGS IN A LOCATION THAT IS
PLAINLY VISIBLE AND LEGIBLE FROM THE STREET OR
ROAD FRONTING THE PROPERTY. WHERE ACCESS IS BY
WAY OF A PRIVATE ROAD AND THE BUILDING ADDRESS
CANNOT BE VIEWED FROM THE PUBLIC WAY, AN
APPROVED SIGN OR MEANS SHALL BE USED TO
IDENTIFY THE STRUCTURE. PREMISES IDENTIFICATION
SHALL CONFORM TO CBC SECTION 501.2.
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
11. 12.
13. 14.
15. 16.
17. 18.
19. 20.
WALL LEGEND
2 HR 2X6 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X4 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X6 FIRE BARRIER W/ FIRE-RETARDANT
TREATED STUD
2 HR 2X6 FIRE BARRIER
2 HR 2X4 FIRE BARRIER
2 HR 2X6 WOOD STUD
2 HR 2X4 WOOD STUD
1 HR 2X6 WOOD STUD
1 HR 2X4 WOOD STUD
1 HR PARTY WALL (2) 2X6 WOOD STUD WALLS
W/ 2" GAP BETWEEN FRAMING
NON-RATED 2X6 STANDARD WOOD WALL
NON-RATED 2X4 STANDARD WOOD WALL
SOFFIT / FLOOR ABOVE
WALL LEGEND
CIP CONCRETE COLUMN PER STRUCTURAL
(REFERENCE SLAB PLANS FOR COLUMN SIZE)
12" CONCRETE WALL
8" CONCRETE WALL
8" CMU WALL
2 HR 6" METAL STUD
1 HR 6" METAL STUD
NON-RATED 6" METAL STUD
SOFFIT / FLOOR ABOVE
GENERAL NOTES GENERAL NOTES
1. ALL FLASHING, SHEET METAL VENTS, EXHAUST FANS,
VENTILATORS, DOWNSPOUTS AND PIPE STACKS
SHALL BE PAINTED TO MATCH THE ADJACENT ROOF
OR WALL MATERIAL AND/OR COLOR.
2. ALL WINDOWS ARE RECESSED A MINIMUM OF 2".
01.01 03.04
05.04 05.16
06.03 07.08
14.01 14.07
21.02 21.03
21.08 32.03
PROPERTY LINE
CONCRETE SLAB (DEPRESSED): W/ 2" MIN. TOPPING SLAB: SLOPE
1.5-2% TO DRAIN OR EXTERIOR PER PLAN, REF. STRUCTURAL DWGS
METAL SCREEN, HEIGHT PER ELEVATIONS
EXTERIOR GUARDRAIL: 42" MIN. ABOVE ADJACENT FINISHED FLOOR BALCONY FRAMING: REFER TO STRUCTURAL DWGS. W/
ELASTOMERIC DECK COATING OVER OVERFRAMING, SLOPE 1.5-2%
TO DRAIN OR EXTERIOR PER PLAN
DRAIN: REF. PLUMBING DWGS
TRASH CHUTE
GREASE SHAFT
FIRE EXTINGUISHER
FIRE STANDPIPE: REF. FIRE SPRINKLER DRAWINGS
HORIZONTAL FIRE EXIT
BIO FILTER PLANTER/BMP AREA: REF. CIVIL DRAWINGS &
LANDSCAPE DWGS
SCALE: 1/8" = 1'-0"1 2ND FLOOR PLAN
KEYNOTES
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Sept. 29, 2026
Item #9 Page 32 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
3RD FLOOR PLAN
A203
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
1 1
10 10
A
A
L
L
I
I
D
D
E
E
F
F
2 2
3 3
6 6
7 7
11 11
DW
REF
REF
DW
DW
REF
DW
REF
DW
REF
DW
REF
REF
DW
REF
DW
REF
DW
DW
DW
REFREF
W D WD
DN
DN
UP
UP
04'8'16'
W/D
FAU
TRSH
MICRO
W/D
MICRO
FAU
TRSH
WINE
W/D
FAU
TRSH
W/D
FAU
TRSH
W/D
FAU
TRSH
MW
W/D
FAU
TRSH
MW
W/D
MICRO
FAU
TRSH
MICRO
W/DFAU
TRSH
MICRO
FAU
W/D
FAU
WINE
FAU WINE
TRSH
TRSH
TRSH
MICROMICRO
2 A611
2 A612
2 A614
3 A303
2 A010
2 A401
2 A401
2 A402
2 A402
1 A402
1 A402
1 A010
2 A011
1 A011
1 A401
1 A401
1 A403
1 A403
1 A303
2 A303
2 A403
2 A403
1 A404
1 A404
2 A404
2 A404
30'-4" 30'-4"
2'-0"
50'-6 1/2" 22'-2" 67'-6"
2'-0"
29'-3 1/2"
39'-6 1/2"62'-8 1/2" 44'-5"
52'-3 1/2" 52'-3 1/2"36'-3 1/2"36'-3 1/2"
62'-8 1/2"
2'-0"
34'-5 1/2" 10'-0" 37'-6"
146'-8"
169'-6"
144'-8"
177'-2"
38 sq ft54 sq ft
1/A607
301
1/A606
302
4/A609
303
1/A602
304
1/A601
305
1/A601
307
1/A602
306
2/A609
308
1/A604
309
1/A605
311
1/A603
310
D3-01
D3-03
D3-04
D3-05
D3-06
D3-02
21.03 D3-07
21.08 14.07
14.01 01.01
05.16 06.03
21.03 06.02
21.02 21.02
05.04 D3-08 D3-09
21.03 D3-10
3RD FLOOR AREA: 19,472 SF
IDF
ELEV
CL
CL CL CL
CL
CL
CL
TR
STO. STO.
STO.STO.
P
WS
H
H
G
G
N
P
WS
WS
P
WS
MW
WS
MW
P
WS
P
WS
P
WS
WS
P
P P
WS
WS
2 A613
STAIR 2 STAIR 1
C2.1
C1
D1.3
A2
A1A1
A2
D1.1
B1
B2
A3
FIRE NOTES
CONSTRUCTION TYPE SHALL BE IIIA
HORIZONTAL EXIT W/ MAG-HOLD DOOR SYSTEM SHALL
BE PROVIDED AT LEVELS 2, 3, AND 4.
EXTERIOR BEARING WALLS SHALL BE 2-HR RATED.
PROJECT SHALL COMPLY WITH NFPA 13 & 14
STANDARDS.
SPRINKLER DENSITY: 15/2000 SF.
STANDPIPES SHALL BE PROVIDED AT EXTERIOR AND
STAIRS 1 & 2.
STAIRS 1 SHALL EXTEND TO ROOF.
COMPLETE PLANS AND SPECIFICATIONS FOR ALL FIRE
EXTINGUISHING SYSTEMS, INCLUDING AUTOMATIC
SPRINKLER AND STANDPIPE SYSTEMS AND OTHER
SPECIAL FIRE EXTINGUISHING SYSTEMS AND RELATED
APPURTENANCE’S SHALL BE SUBMITTED TO THE CITY
OF SAN DIEGO FOR REVIEW AND APPROVAL PRIOR TO
INSTALLATION.
COMPLETE PLANS AND SPECIFICATIONS FOR FIRE
ALARM SYSTEMS SHALL BE SUBMITTED TO THE CITY OF
SAN DIEGO DEVELOPMENT SERVICES FOR REVIEW AND
APPROVAL PRIOR TO INSTALLATION. CFC 907.1.1
LOCATIONS AND CLASSIFICATIONS OF EXTINGUISHERS
SHALL BE IN ACCORDANCE WITH CFC 906 AND
CALIFORNIA CODE OF REGULATIONS (CCR), TITLE 19.
DURING CONSTRUCTION AT LEAST ONE EXTINGUISHER
SHALL BE PROVIDED ON EACH FLOOR LEVEL AT EACH
STAIRWAY, IN ALL STORAGE AND CONSTRUCTION
SHEDS, IN LOCATIONS WHERE FLAMMABLE OR
COMBUSTIBLE LIQUIDS ARE STORED OR USED, AND
WHERE OTHER SPECIAL HAZARDS ARE PRESENT PER
CFC SECTION3315.1
IN BUILDINGS THAT REQUIRE STANDPIPES, STANDPIPES
SHALL BE PROVIDED DURING CONSTRUCTION WHEN
THE HEIGHT REACHES 40 FEET ABOVE THE LOWEST
LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS. A FIRE
DEPARTMENT CONNECTION SHALL BE NO MORE THAN
100 FEET FROM THE AVAILABLE FIRE DEPARTMENT
VEHICLE ACCESS ROADWAYS. CFC SECTIONS 3310,
3313.
BUILDINGS UNDERGOING CONSTRUCTION,
ALTERATION, OR DEMOLITION SHALL CONFORM TO CFC
CHAPTER 33. WELDING, CUTTING, AND OTHER HOT
WORK SHALL BE IN CONFORMANCE WITH CFC
CHAPTER 35.
WALL, FLOOR AND CEILING FINISHES AND MATERIALS
SHALL NOT EXCEED THE INTERIOR FINISH
CLASSIFICATION IN CBC TABLE 803.9 AND SHALL MEET
THE FLAME PROPAGATION PERFORMANCE CRITERIA OF
THE CALIFORNIA CODE OF REGULATIONS, TITLE 19,
DIVISION 1. DECORATIVE MATERIALS SHALL BE
PROPERLY TREATED BY A PRODUCT OF PROCESS
APPROVED BY THE STATE FIRE MARSHAL WITH
APPROPRIATE DOCUMENTATION PROVIDED TO THE
CITY OF SAN DIEGO.
KEY BOXES SHALL BE PROVIDED FOR ALL HIGH-RISE
BUILDINGS, POOL ENCLOSURES, GATES IN THE PATH
OF FIREFIGHTER TRAVEL TO STRUCTURES, SECURED
PARKING LEVELS, DOORS GIVING TO ALARM PANELS
AND/OR ANNUNCIATORS, AND ANY OTHER
STRUCTURES OR AREAS WHERE ACCESS TO AN AREA
IS RESTRICTED.
DUMPSTERS AND TRASH CONTAINERS EXCEEDING 1.5
CUBIC YARDS SHALL NOT BE STORED IN BUILDINGS OR
PLACED WITHIN 5 FEET OF COMBUSTIBLE WALLS,
OPENINGS OR COMBUSTIBLE ROOF EAVE LINES
UNLESS PROTECTED BY AN APPROVED SPRINKLER
SYSTEM OR LOCATED IN A TYPE I OR IIA
STRUCTURE SEPARATED BY 10 FEET FROM OTHER
STRUCTURES. CONTAINERS LARGER THAN I CUBIC
YARD SHALL BE OF NON - OR LIMITED-COMBUSTIBLE
MATERIALS OR SIMILARLY PROTECTED OR SEPARATED.
CFC 304.3.
EXITS, EXIT SIGNS, FIRE ALARM PANELS, HOSE
CABINETS, FIRE EXTINGUISHER LOCATIONS, AND
STANDPIPE CONNECTIONS SHALL NOT BE CONCEALED
BY CURTAINS, MIRRORS, OR ANY OTHER DECORATIVE
MATERIAL
OPEN FLAMES, FIRE AND BURNING ON ALL PREMISES IS
PROHIBITED EXCEPT AS SPECIFICALLY PERMITTED BY
THE CITY OF SAN DIEGO AND CFC 308.
THE EGRESS PATH SHALL REMAIN FREE AND CLEAR OF
ALL OBSTRUCTIONS AT ALL TIMES. NO STORAGE IS
PERMITTED IN ANY EGRESS PATHS.
ADDRESS IDENTIFICATION SHALL BE PROVIDED FOR ALL
NEW AND EXISTING BUILDINGS IN A LOCATION THAT IS
PLAINLY VISIBLE AND LEGIBLE FROM THE STREET OR
ROAD FRONTING THE PROPERTY. WHERE ACCESS IS BY
WAY OF A PRIVATE ROAD AND THE BUILDING ADDRESS
CANNOT BE VIEWED FROM THE PUBLIC WAY, AN
APPROVED SIGN OR MEANS SHALL BE USED TO
IDENTIFY THE STRUCTURE. PREMISES IDENTIFICATION
SHALL CONFORM TO CBC SECTION 501.2.
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
11. 12.
13. 14.
15. 16.
17. 18.
19. 20.
WALL LEGEND
2 HR 2X6 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X4 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X6 FIRE BARRIER W/ FIRE-RETARDANT
TREATED STUD
2 HR 2X6 FIRE BARRIER
2 HR 2X4 FIRE BARRIER
2 HR 2X6 WOOD STUD
2 HR 2X4 WOOD STUD
1 HR 2X6 WOOD STUD
1 HR 2X4 WOOD STUD
1 HR PARTY WALL (2) 2X6 WOOD STUD WALLS
W/ 2" GAP BETWEEN FRAMING
NON-RATED 2X6 STANDARD WOOD WALL
NON-RATED 2X4 STANDARD WOOD WALL
SOFFIT / FLOOR ABOVE
WALL LEGEND
CIP CONCRETE COLUMN PER STRUCTURAL
(REFERENCE SLAB PLANS FOR COLUMN SIZE)
12" CONCRETE WALL
8" CONCRETE WALL
8" CMU WALL
2 HR 6" METAL STUD
1 HR 6" METAL STUD
NON-RATED 6" METAL STUD
SOFFIT / FLOOR ABOVE
GENERAL NOTES GENERAL NOTES
1. ALL FLASHING, SHEET METAL VENTS, EXHAUST FANS,
VENTILATORS, DOWNSPOUTS AND PIPE STACKS
SHALL BE PAINTED TO MATCH THE ADJACENT ROOF
OR WALL MATERIAL AND/OR COLOR.
2. ALL WINDOWS ARE RECESSED A MINIMUM OF 2".
01.01 05.04
05.16 06.02
06.03 14.01
14.07 21.02
21.03 21.08
PROPERTY LINE
METAL SCREEN, HEIGHT PER ELEVATIONS
EXTERIOR GUARDRAIL: 42" MIN. ABOVE ADJACENT FINISHED FLOOR CORRIDOR / DECK FRAMING: REFER TO STRUCTURAL DWGS. W/ 2" MIN. TOPPING SLAB OVER OVERFRAMING, SLOPE 1.5-2% TO DRAIN
OR EXTERIOR PER PLAN
BALCONY FRAMING: REFER TO STRUCTURAL DWGS. W/
ELASTOMERIC DECK COATING OVER OVERFRAMING, SLOPE 1.5-2%
TO DRAIN OR EXTERIOR PER PLAN
TRASH CHUTE
GREASE SHAFT
FIRE EXTINGUISHER
FIRE STANDPIPE: REF. FIRE SPRINKLER DRAWINGS
HORIZONTAL FIRE EXIT
SCALE: 1/8" = 1'-0"1 3RD FLOOR PLAN
KEYNOTES
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Sept. 29, 2026
Item #9 Page 33 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
4TH FLOOR PLAN
A204
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
1 1
10 10
A
A
L
L
I
I
D
D
E
E
F
F
2 2
3 3
6 6
7 7
11 11
DW
REF
REF
DW
DW
REF
DW
REF
REF
DW
REF
DW
REF
DW
DW
DW
DW
REF
DW
REF
REF REF
W D WD
DNUP
04'8'16'
W/D
FAU
TRSH
MICRO
W/D
MICRO
FAU
TRSH
WINE
W/D
FAU
TRSH
W/D
FAU
TRSH
W/D
MICRO
FAU
TRSH
MICRO
W/DFAU
TRSH
MICRO
FAU
W/D
FAU
WINE
FAU WINE
W/D
FAU
W/D
FAU
TRSH
TRSH
TRSHTRSH
MW
TRSH
MW
MICRO MICRO
2 A611
2 A612
2 A614
3 A303
2 A010
2 A401
2 A401
2 A402
2 A402
1 A402
1 A402
1 A010
2 A011
1 A011
1 A401
1 A401
1 A403
1 A403
1 A303
2 A303
2 A403
2 A403
1 A404
1 A404
2 A404
2 A404
30'-4" 30'-4"
2'-0"
50'-6 1/2" 22'-2" 67'-6"29'-3 1/2"
62'-8 1/2" 44'-5" 39'-6 1/2"
62'-8 1/2" 37'-6"
2'-0"
34'-5 1/2" 10'-0"
146'-8"
52'-3 1/2"52'-3 1/2" 36'-3 1/2" 36'-3 1/2"
169'-6"
144'-8"
177'-2"
38 sq ft54 sq ft
2/A607
401
1/A606
402
1/A602
404
1/A601
405
1/A601
407
1/A602
406
1/A604
409
1/A605
411
1/A603
410
4/A609
403
2/A609
408
D4-01
D4-03
D4-04
D4-05
D4-06
D4-02
21.08 14.07
14.01 01.01
D4-07
05.16 06.03
21.03 06.02
21.02 21.02
05.04 D4-09 D4-08
21.03 D4-10
4TH FLOOR AREA: 19,417 SF
IDF
ELEV
CL
CL CL CL
CL
CL
CL
TR
STO. STO.
STO.STO.
P
WS
H
H
G
G
N
P
WS
WS
P
WS
MW
WS
MW
P
WS
WS
P
P P
P
WS
P
WS
WS
WS
2 A613
1/A604
409
STAIR 1
C2.2
C1
A2
A1A1
A2
B1
B2
A3
D1.5D1.4
STAIR 2
FIRE NOTES
CONSTRUCTION TYPE SHALL BE IIIA
HORIZONTAL EXIT W/ MAG-HOLD DOOR SYSTEM SHALL
BE PROVIDED AT LEVELS 2, 3, AND 4.
EXTERIOR BEARING WALLS SHALL BE 2-HR RATED.
PROJECT SHALL COMPLY WITH NFPA 13 & 14
STANDARDS.
SPRINKLER DENSITY: 15/2000 SF.
STANDPIPES SHALL BE PROVIDED AT EXTERIOR AND
STAIRS 1 & 2.
STAIRS 1 SHALL EXTEND TO ROOF.
COMPLETE PLANS AND SPECIFICATIONS FOR ALL FIRE
EXTINGUISHING SYSTEMS, INCLUDING AUTOMATIC
SPRINKLER AND STANDPIPE SYSTEMS AND OTHER
SPECIAL FIRE EXTINGUISHING SYSTEMS AND RELATED
APPURTENANCE’S SHALL BE SUBMITTED TO THE CITY
OF SAN DIEGO FOR REVIEW AND APPROVAL PRIOR TO
INSTALLATION.
COMPLETE PLANS AND SPECIFICATIONS FOR FIRE
ALARM SYSTEMS SHALL BE SUBMITTED TO THE CITY OF
SAN DIEGO DEVELOPMENT SERVICES FOR REVIEW AND
APPROVAL PRIOR TO INSTALLATION. CFC 907.1.1
LOCATIONS AND CLASSIFICATIONS OF EXTINGUISHERS
SHALL BE IN ACCORDANCE WITH CFC 906 AND
CALIFORNIA CODE OF REGULATIONS (CCR), TITLE 19.
DURING CONSTRUCTION AT LEAST ONE EXTINGUISHER
SHALL BE PROVIDED ON EACH FLOOR LEVEL AT EACH
STAIRWAY, IN ALL STORAGE AND CONSTRUCTION
SHEDS, IN LOCATIONS WHERE FLAMMABLE OR
COMBUSTIBLE LIQUIDS ARE STORED OR USED, AND
WHERE OTHER SPECIAL HAZARDS ARE PRESENT PER
CFC SECTION3315.1
IN BUILDINGS THAT REQUIRE STANDPIPES, STANDPIPES
SHALL BE PROVIDED DURING CONSTRUCTION WHEN
THE HEIGHT REACHES 40 FEET ABOVE THE LOWEST
LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS. A FIRE
DEPARTMENT CONNECTION SHALL BE NO MORE THAN
100 FEET FROM THE AVAILABLE FIRE DEPARTMENT
VEHICLE ACCESS ROADWAYS. CFC SECTIONS 3310,
3313.
BUILDINGS UNDERGOING CONSTRUCTION,
ALTERATION, OR DEMOLITION SHALL CONFORM TO CFC
CHAPTER 33. WELDING, CUTTING, AND OTHER HOT
WORK SHALL BE IN CONFORMANCE WITH CFC
CHAPTER 35.
WALL, FLOOR AND CEILING FINISHES AND MATERIALS
SHALL NOT EXCEED THE INTERIOR FINISH
CLASSIFICATION IN CBC TABLE 803.9 AND SHALL MEET
THE FLAME PROPAGATION PERFORMANCE CRITERIA OF
THE CALIFORNIA CODE OF REGULATIONS, TITLE 19,
DIVISION 1. DECORATIVE MATERIALS SHALL BE
PROPERLY TREATED BY A PRODUCT OF PROCESS
APPROVED BY THE STATE FIRE MARSHAL WITH
APPROPRIATE DOCUMENTATION PROVIDED TO THE
CITY OF SAN DIEGO.
KEY BOXES SHALL BE PROVIDED FOR ALL HIGH-RISE
BUILDINGS, POOL ENCLOSURES, GATES IN THE PATH
OF FIREFIGHTER TRAVEL TO STRUCTURES, SECURED
PARKING LEVELS, DOORS GIVING TO ALARM PANELS
AND/OR ANNUNCIATORS, AND ANY OTHER
STRUCTURES OR AREAS WHERE ACCESS TO AN AREA
IS RESTRICTED.
DUMPSTERS AND TRASH CONTAINERS EXCEEDING 1.5
CUBIC YARDS SHALL NOT BE STORED IN BUILDINGS OR
PLACED WITHIN 5 FEET OF COMBUSTIBLE WALLS,
OPENINGS OR COMBUSTIBLE ROOF EAVE LINES
UNLESS PROTECTED BY AN APPROVED SPRINKLER
SYSTEM OR LOCATED IN A TYPE I OR IIA
STRUCTURE SEPARATED BY 10 FEET FROM OTHER
STRUCTURES. CONTAINERS LARGER THAN I CUBIC
YARD SHALL BE OF NON - OR LIMITED-COMBUSTIBLE
MATERIALS OR SIMILARLY PROTECTED OR SEPARATED.
CFC 304.3.
EXITS, EXIT SIGNS, FIRE ALARM PANELS, HOSE
CABINETS, FIRE EXTINGUISHER LOCATIONS, AND
STANDPIPE CONNECTIONS SHALL NOT BE CONCEALED
BY CURTAINS, MIRRORS, OR ANY OTHER DECORATIVE
MATERIAL
OPEN FLAMES, FIRE AND BURNING ON ALL PREMISES IS
PROHIBITED EXCEPT AS SPECIFICALLY PERMITTED BY
THE CITY OF SAN DIEGO AND CFC 308.
THE EGRESS PATH SHALL REMAIN FREE AND CLEAR OF
ALL OBSTRUCTIONS AT ALL TIMES. NO STORAGE IS
PERMITTED IN ANY EGRESS PATHS.
ADDRESS IDENTIFICATION SHALL BE PROVIDED FOR ALL
NEW AND EXISTING BUILDINGS IN A LOCATION THAT IS
PLAINLY VISIBLE AND LEGIBLE FROM THE STREET OR
ROAD FRONTING THE PROPERTY. WHERE ACCESS IS BY
WAY OF A PRIVATE ROAD AND THE BUILDING ADDRESS
CANNOT BE VIEWED FROM THE PUBLIC WAY, AN
APPROVED SIGN OR MEANS SHALL BE USED TO
IDENTIFY THE STRUCTURE. PREMISES IDENTIFICATION
SHALL CONFORM TO CBC SECTION 501.2.
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
11. 12.
13. 14.
15. 16.
17. 18.
19. 20.
WALL LEGEND
2 HR 2X6 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X4 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X6 FIRE BARRIER W/ FIRE-RETARDANT
TREATED STUD
2 HR 2X6 FIRE BARRIER
2 HR 2X4 FIRE BARRIER
2 HR 2X6 WOOD STUD
2 HR 2X4 WOOD STUD
1 HR 2X6 WOOD STUD
1 HR 2X4 WOOD STUD
1 HR PARTY WALL (2) 2X6 WOOD STUD WALLS
W/ 2" GAP BETWEEN FRAMING
NON-RATED 2X6 STANDARD WOOD WALL
NON-RATED 2X4 STANDARD WOOD WALL
SOFFIT / FLOOR ABOVE
WALL LEGEND
CIP CONCRETE COLUMN PER STRUCTURAL
(REFERENCE SLAB PLANS FOR COLUMN SIZE)
12" CONCRETE WALL
8" CONCRETE WALL
8" CMU WALL
2 HR 6" METAL STUD
1 HR 6" METAL STUD
NON-RATED 6" METAL STUD
SOFFIT / FLOOR ABOVE
GENERAL NOTES GENERAL NOTES
1. ALL FLASHING, SHEET METAL VENTS, EXHAUST FANS,
VENTILATORS, DOWNSPOUTS AND PIPE STACKS
SHALL BE PAINTED TO MATCH THE ADJACENT ROOF
OR WALL MATERIAL AND/OR COLOR.
2. ALL WINDOWS ARE RECESSED A MINIMUM OF 2".
01.01 05.04
05.16 06.02
06.03 14.01
14.07 21.02
21.03 21.08
PROPERTY LINE
METAL SCREEN, HEIGHT PER ELEVATIONS
EXTERIOR GUARDRAIL: 42" MIN. ABOVE ADJACENT FINISHED FLOOR CORRIDOR / DECK FRAMING: REFER TO STRUCTURAL DWGS. W/ 2" MIN. TOPPING SLAB OVER OVERFRAMING, SLOPE 1.5-2% TO DRAIN
OR EXTERIOR PER PLAN
BALCONY FRAMING: REFER TO STRUCTURAL DWGS. W/
ELASTOMERIC DECK COATING OVER OVERFRAMING, SLOPE 1.5-2%
TO DRAIN OR EXTERIOR PER PLAN
TRASH CHUTE
GREASE SHAFT
FIRE EXTINGUISHER
FIRE STANDPIPE: REF. FIRE SPRINKLER DRAWINGS
HORIZONTAL FIRE EXIT
SCALE: 1/8" = 1'-0"1 4TH FLOOR PLAN
KEYNOTES
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Sept. 29, 2026
Item #9 Page 34 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
ROOF PLAN
A205
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
1 1
10 10
A
A
L
L
I
I
D
D
E
E
F
F
2 2
3 3
6 6
7 7
11 11
04'8'16'
3 A611
2 A401
2 A401
2 A402
2 A402
1 A402
1 A402
1 A401
1 A401
1 A403
1 A403
2 A403
2 A403
1 A404
1 A404
2 A404
2 A404
218 sq ft
6'-6"
26'-0"
42'-7"
70'-11"
20'-4"
42'-6"
26'-0"
18'-2"33'-7 1/2" 73'-7" 18'-2" 33'-7 1/2"
78'-11 1/2" 19'-6 1/2" 10'-0" 41'-0"
55'-3 1/2" 68'-6"18'-9" 12'-9 1/2" 16'-2" 4'-11"
25'-4 1/2" 62'-6"41'-7 1/2" 16'-6"
2'-6"
149'-6"
177'-2"
148'-6"
176'-5"
D5-01
D5-02
06.23 21.03
06.23 06.23
06.23 06.23
06.23 48.01
14.02 01.2801.28
01.28 01.28
03.12 23.02
07.18 23.02
23.02 07.18
23.02 07.18
BOILER
ROOF AREA = 24,238 SF
H
H
G
G
N
3 A613
3,654 sq ft
STAIR 1
FIRE NOTES
CONSTRUCTION TYPE SHALL BE IIIA
HORIZONTAL EXIT W/ MAG-HOLD DOOR SYSTEM SHALL
BE PROVIDED AT LEVELS 2, 3, AND 4.
EXTERIOR BEARING WALLS SHALL BE 2-HR RATED.
PROJECT SHALL COMPLY WITH NFPA 13 & 14
STANDARDS.
SPRINKLER DENSITY: 15/2000 SF.
STANDPIPES SHALL BE PROVIDED AT EXTERIOR AND
STAIRS 1 & 2.
STAIRS 1 SHALL EXTEND TO ROOF.
COMPLETE PLANS AND SPECIFICATIONS FOR ALL FIRE
EXTINGUISHING SYSTEMS, INCLUDING AUTOMATIC
SPRINKLER AND STANDPIPE SYSTEMS AND OTHER
SPECIAL FIRE EXTINGUISHING SYSTEMS AND RELATED
APPURTENANCE’S SHALL BE SUBMITTED TO THE CITY
OF SAN DIEGO FOR REVIEW AND APPROVAL PRIOR TO
INSTALLATION.
COMPLETE PLANS AND SPECIFICATIONS FOR FIRE
ALARM SYSTEMS SHALL BE SUBMITTED TO THE CITY OF
SAN DIEGO DEVELOPMENT SERVICES FOR REVIEW AND
APPROVAL PRIOR TO INSTALLATION. CFC 907.1.1
LOCATIONS AND CLASSIFICATIONS OF EXTINGUISHERS
SHALL BE IN ACCORDANCE WITH CFC 906 AND
CALIFORNIA CODE OF REGULATIONS (CCR), TITLE 19.
DURING CONSTRUCTION AT LEAST ONE EXTINGUISHER
SHALL BE PROVIDED ON EACH FLOOR LEVEL AT EACH
STAIRWAY, IN ALL STORAGE AND CONSTRUCTION
SHEDS, IN LOCATIONS WHERE FLAMMABLE OR
COMBUSTIBLE LIQUIDS ARE STORED OR USED, AND
WHERE OTHER SPECIAL HAZARDS ARE PRESENT PER
CFC SECTION3315.1
IN BUILDINGS THAT REQUIRE STANDPIPES, STANDPIPES
SHALL BE PROVIDED DURING CONSTRUCTION WHEN
THE HEIGHT REACHES 40 FEET ABOVE THE LOWEST
LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS. A FIRE
DEPARTMENT CONNECTION SHALL BE NO MORE THAN
100 FEET FROM THE AVAILABLE FIRE DEPARTMENT
VEHICLE ACCESS ROADWAYS. CFC SECTIONS 3310,
3313.
BUILDINGS UNDERGOING CONSTRUCTION,
ALTERATION, OR DEMOLITION SHALL CONFORM TO CFC
CHAPTER 33. WELDING, CUTTING, AND OTHER HOT
WORK SHALL BE IN CONFORMANCE WITH CFC
CHAPTER 35.
WALL, FLOOR AND CEILING FINISHES AND MATERIALS
SHALL NOT EXCEED THE INTERIOR FINISH
CLASSIFICATION IN CBC TABLE 803.9 AND SHALL MEET
THE FLAME PROPAGATION PERFORMANCE CRITERIA OF
THE CALIFORNIA CODE OF REGULATIONS, TITLE 19,
DIVISION 1. DECORATIVE MATERIALS SHALL BE
PROPERLY TREATED BY A PRODUCT OF PROCESS
APPROVED BY THE STATE FIRE MARSHAL WITH
APPROPRIATE DOCUMENTATION PROVIDED TO THE
CITY OF SAN DIEGO.
KEY BOXES SHALL BE PROVIDED FOR ALL HIGH-RISE
BUILDINGS, POOL ENCLOSURES, GATES IN THE PATH
OF FIREFIGHTER TRAVEL TO STRUCTURES, SECURED
PARKING LEVELS, DOORS GIVING TO ALARM PANELS
AND/OR ANNUNCIATORS, AND ANY OTHER
STRUCTURES OR AREAS WHERE ACCESS TO AN AREA
IS RESTRICTED.
DUMPSTERS AND TRASH CONTAINERS EXCEEDING 1.5
CUBIC YARDS SHALL NOT BE STORED IN BUILDINGS OR
PLACED WITHIN 5 FEET OF COMBUSTIBLE WALLS,
OPENINGS OR COMBUSTIBLE ROOF EAVE LINES
UNLESS PROTECTED BY AN APPROVED SPRINKLER
SYSTEM OR LOCATED IN A TYPE I OR IIA
STRUCTURE SEPARATED BY 10 FEET FROM OTHER
STRUCTURES. CONTAINERS LARGER THAN I CUBIC
YARD SHALL BE OF NON - OR LIMITED-COMBUSTIBLE
MATERIALS OR SIMILARLY PROTECTED OR SEPARATED.
CFC 304.3.
EXITS, EXIT SIGNS, FIRE ALARM PANELS, HOSE
CABINETS, FIRE EXTINGUISHER LOCATIONS, AND
STANDPIPE CONNECTIONS SHALL NOT BE CONCEALED
BY CURTAINS, MIRRORS, OR ANY OTHER DECORATIVE
MATERIAL
OPEN FLAMES, FIRE AND BURNING ON ALL PREMISES IS
PROHIBITED EXCEPT AS SPECIFICALLY PERMITTED BY
THE CITY OF SAN DIEGO AND CFC 308.
THE EGRESS PATH SHALL REMAIN FREE AND CLEAR OF
ALL OBSTRUCTIONS AT ALL TIMES. NO STORAGE IS
PERMITTED IN ANY EGRESS PATHS.
ADDRESS IDENTIFICATION SHALL BE PROVIDED FOR ALL
NEW AND EXISTING BUILDINGS IN A LOCATION THAT IS
PLAINLY VISIBLE AND LEGIBLE FROM THE STREET OR
ROAD FRONTING THE PROPERTY. WHERE ACCESS IS BY
WAY OF A PRIVATE ROAD AND THE BUILDING ADDRESS
CANNOT BE VIEWED FROM THE PUBLIC WAY, AN
APPROVED SIGN OR MEANS SHALL BE USED TO
IDENTIFY THE STRUCTURE. PREMISES IDENTIFICATION
SHALL CONFORM TO CBC SECTION 501.2.
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
11. 12.
13. 14.
15. 16.
17. 18.
19. 20.
GENERAL NOTES GENERAL NOTES
1. ALL FLASHING, SHEET METAL VENTS, EXHAUST FANS,
VENTILATORS, DOWNSPOUTS AND PIPE STACKS
SHALL BE PAINTED TO MATCH THE ADJACENT ROOF
OR WALL MATERIAL AND/OR COLOR.
2. ALL WINDOWS ARE RECESSED A MINIMUM OF 2".
01.28 03.12
06.23 07.18
14.02 21.03
23.02 48.01
LINE OF BALCONY BELOW
CURB @ ROOF EDGE, TYP
2x FRAMED PARAPET WALL / CURB: HEIGHT & FINISH PER
ELEVATION
MECHANICAL SCREEN, HEIGHT PER ELEVATIONS
ROOFTOP MECHANICAL TRASH CHUTE EXHAUST: REF. DETAIL 11/ A834, REF. MECHANICAL DWGS
FIRE STANDPIPE: REF. FIRE SPRINKLER DRAWINGS
MECH EQUIPMENT: REF. MECHANICAL DWGS
PROPOSED LOCATION OF PV PANELS: REF. SOLAR DWGS
SCALE: 1/8" = 1'-0"1 ROOF PLAN
KEYNOTES
date
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Sept. 29, 2026
Item #9 Page 35 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
EXTERIOR ELEVATIONS
A301
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
52'-9"
59'-3"
5'-0"
3'-6"
55'-3"
10'-0"
3'-6"
3'-6"
10'-0"
3'-6"
PROPERTY LINE
SDG-1 SDG-3
GRD-1
ECP-1
ECP-3
ECP-4 PARAPET WALLGL-1 MECHANICAL EQUIPMENT
(SCREENED FROM VIEW)
PARAPET WALL
PARAPET WALL
BOILER ROOMSTAIR PROJECTION
ELEVATOR PROJECTION
TOP OF FLOOR,TYP
BOTTOM OF FLOOR, TYP
ECP-2
FF:44.50'
FF:60.83'
FF:71.75'
FF:82.67'
FF:93.58'
TRANSOM
DOOR
TRANSOM
DOOR
TRANSOM
DOOR
TRANSOM
DOOR
45'-0" HEIGHT LIMIT
51'-1"
3'-6" 3'-6"3'-6"
8'-0"8'-0"
48'-7"
8'-0"
14'-0" 1'-10" 9'-1" 1'-10" 9'-1" 1'-10" 9'-1" 1'-10"
BRK-1 MTL-3 TLE-1 DR-1 DR-2
DR-3
GL-2 MTL-2
SIGNAGE UNDER
SEPARATE PERMIT
MTL-2
MTL-4 MAILBOXES
MATERIAL: ALUMINUM
COLOR: DARK BRONZE
SIGNAGE UNDER
SEPARATE PERMIT
PLANE CHANGE
(SEE 1ST FLOOR PLAN)EXISTING GRADE
FINISHED GRADE
55'-7"
62'-1"
52'-9"
59'-3"
3'-6"3'-6"3'-6"
3'-6"
10'-0"
3'-6"
3'-6"
5'-0"
PROPERTY LINE
ECP-1
ECP-2
ECP-3
ECP-4
SDG-1
SDG-2
SDG-3
GRD-1 MECHANICAL EQUIPMENT
(SCREENED FROM VIEW)
PARAPET WALLPARAPET
WALL
BOILER ROOM PROJECTION
STAIR PROJECTION
ELEVATOR PROJECTION
PARAPET WALL
TOP OF FLOOR,TYP
BOTTOM OF FLOOR, TYP
FF:44.50'
@ MAIN LOBBY (BEYOND)
FF:60.83'
FF:71.75'
FF:82.67'
FF:93.58'
13'-11 3/8" 1'-10" 9'-1" 1'-10" 9'-1" 1'-10" 9'-1" 1'-10" 51'-5"
45'-0" HEIGHT LIMIT
8'-0"8'-0" 8'-0"
48'-7"
ECP-2
DR-3
BRK-1
GL-1
GAS METERS
EXISTING GRADE
FINISHED GRADE
MARK DESCRIPTION
EXTERIOR CEMENT PLASTER
MANUF: -
STYLE: 20/30 SAND FINISH
COLOR: INTEGRAL COLOR, MATCH DUNN EDWARDS
DE6225/ FOSSIL
EXTERIOR CEMENT PLASTER
MANUF: -
STYLE: 20/30 SAND FINISH
COLOR: INTEGRAL COLOR, MATCH DUNN EDWARDS
DE6305/ GALWAY BAY
EXTERIOR CEMENT PLASTER
MANUF: -
STYLE: 20/30 SAND FINISH
COLOR: INTEGRAL COLOR, MATCH DUNN EDWARDS
DE6333/ HAMILTON BLUE
EXTERIOR CEMENT PLASTER
MANUF: -
STYLE: 20/30 SAND FINISH
COLOR: INTEGRAL COLOR, MATCH DUNN EDWARDS
DE6370/ CHARCOAL SMUDGE
FIBER CEMENT SIDING
MANUF: JAMES HARDIE
STYLE: ARTISAN SIDING
COLOR: MATCH "ECP-1"
FIBER CEMENT SIDING
MANUF: JAMES HARDIE
STYLE: ARTISAN SIDING
COLOR: MATCH "ECP-2"
VERTICAL FIBER CEMENT SIDING
MANUF: NICHIHA
STYLE: VINTAGEWOOD
COLOR: CEDAR
CONCRETE MASONRY UNIT
MANUF: RCP BLOCK & BRICK
STYLE: SMOOTH FINISH, 8X8X16, STACKED BOND
COLOR: SAND
CONCRETE MASONRY UNIT
MANUF: RCP BLOCK & BRICK
STYLE: SMOOTH FINISH, 8X8X16, STACKED BOND
COLOR: MISSION
BRICK VENEER
MANUF: BELDEN BRICK
STYLE: -
COLOR: 8521 COARSE VELOUR
BRAKE METAL
MANUF: -
STYLE: 22 GAUGE ALUMINUM
COLOR: MATCH "ECP-4"
METAL AWNING
MANUF: -
STYLE: -
COLOR: MATCH "ECP-4"
METAL SCREEN
STYLE: 2" STEEL ANGLE FRAME W/ WIRE MESH
INFILL PANELS
COLOR: TBD
METAL AWNING
MANUF: -
STYLE: -
COLOR: MATCH "ECP-3"
TILE
MANUF: TILEBAR
STYLE: LOFT SEAFOAM 3X6 POLISHED GLASS
SUBWAY TILE
COLOR: SEAFOAM
GUARDRAIL SYSTEM
MANUF: VIVA RAILINGS
STYLE: STRUC PANEL SYSTEM
COLOR: CLEAR
GUARDRAIL SYSTEM
MANUF: VIVA RAILINGS
STYLE: STRUC PANEL SYSTEM
COLOR: TBD
GARAGE ROLLING DOOR
MANUF: WAYNE DALTON
STYLE: MODEL 600
COLOR: MATCH "ECP-4"
STOREFRONT DOOR
MANUF: ARCADIA
STYLE: -
COLOR: MATCH "ECP-4"
MULTI-SLIDE POCKET DOOR
MANUF: PER SCHEDULE AND SPECIFICATIONS
STYLE: ALUMINUM
COLOR: MATCH "ECP-4"
UTILITY SERVICE DOOR
MANUF: PER SCHEDULE AND SPECIFICATIONS
STYLE: HOLLOW METAL
COLOR: MATCH "ECP-2"
WINDOWS
MANUF: PER SCHEDULE AND SPECIFICATIONS
STYLE: VINYL
COLOR: MATCH "ECP-4"
STOREFRONT SYSTEM
MANUF: PER SCHEDULE AND SPECIFICATIONS
STYLE: ALUMINUM
COLOR: MATCH "ECP-4" (FRAME)
GLASS: TRANSPARENT / TRANSLUCENT
ECP-1
ECP-2
ECP-3
ECP-4
SDG-1
SDG-2
SDG-3
CMU-1
CMU-2
BRK-1
MTL-1
MTL-2
MTL-3
MTL-4
TLE-1
GRD-1
GRD-2
DR-1
DR-2
DR-3
DR-4
WIN-1
SF-1
EXT. FINISH SCHEDULE
GENERAL NOTES GENERAL NOTES
1. ALL FLASHING, SHEET METAL VENTS, EXHAUST FANS,
VENTILATORS, DOWNSPOUTS AND PIPE STACKS
SHALL BE PAINTED TO MATCH THE ADJACENT ROOF
OR WALL MATERIAL AND/OR COLOR.
2. ALL WINDOWS ARE RECESSED A MINIMUM OF 2".
SCALE: 1/8" = 1'-0"1 EAST / FRONT ELEVATION
SCALE: 1/8" = 1'-0"2 SOUTH / SIDE ELEVATION
KEYNOTES
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
BRK-1
Sept. 29, 2026
Item #9 Page 36 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
EXTERIOR ELEVATIONS
A302
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
3'-6"
3'-6"
51'-5"
55'-7"
62'-1"
57'-7"
64'-1"
3'-6"
15'-0"
10'-0"
3'-6"
PROPERTY LINE
ECP-1
ECP-4
SDG-1
SDG-3
GRD-1
GRD-2
SDG-2
PARAPET WALL PARAPET WALLPARAPET WALL
PARAPET WALL
PARAPET WALL
BOILER ROOM STAIR PROJECTION
BOTTOM OF
FLOOR, TYP
TOP OF
FLOOR,TYP
FF:44.50'
@ MAIN LOBBY (BEYOND)
FF:60.83'
FF:71.75'
FF:82.67'
FF:93.58'
1'-10"
9'-1"
1'-10"
9'-1"
1'-10"
9'-1"
1'-10"
16'-10"
53'-5" (MAX BUILDING HEIGHT)
45'-0" HEIGHT LIMIT
8'-0"8'-0" 8'-0"
3'-6" 3'-6"
3'-6"
42.1'
40.6'39.9'39.7'
ECP-2
DR-3
GL-1
FINISHED GRADE TO
MATCH EXISTING GRADE
3'-6"
3'-6"
53'-5" (MAX BUILDING HEIGHT)
57'-7"
64'-1"
61'-9"
45'-0" HEIGHT LIMIT
5'-0"
10'-0"
3'-6"
10'-0"
PROPERTY LINE
ECP-1
ECP-2
ECP-3
ECP-4 SDG-1
SDG-3
SDG-2
GRD-1
MECHANICAL EQUIPMENT
(SCREENED FROM VIEW)
PARAPET WALL
PARAPET WALL
BOILER ROOM
STAIR PROJECTION
ELEVATOR PROJECTION
TOP OF FLOOR,TYP
BOTTOM OF FLOOR, TYP
FF:44.50'
@ MAIN LOBBY (BEYOND)
FF:60.83'
FF:71.75'
FF:82.67'
FF:93.58'
51'-1"
8'-0"
3'-6"
8'-0"
3'-6"
8'-0"
3'-6"
18'-10"
1'-10"
9'-1"
1'-10"
9'-1"
1'-10"
9'-1"
1'-10"
55'-3"
DR-4
MTL-1
MTL-2 ECP-2
DR-3
GL-1
GL-2
BRK-1 ECP-4
EXISTING GRADE
FINISHED GRADE
MARK DESCRIPTION
EXTERIOR CEMENT PLASTER
MANUF: -
STYLE: 20/30 SAND FINISH
COLOR: INTEGRAL COLOR, MATCH DUNN EDWARDS
DE6225/ FOSSIL
EXTERIOR CEMENT PLASTER
MANUF: -
STYLE: 20/30 SAND FINISH
COLOR: INTEGRAL COLOR, MATCH DUNN EDWARDS
DE6305/ GALWAY BAY
EXTERIOR CEMENT PLASTER
MANUF: -
STYLE: 20/30 SAND FINISH
COLOR: INTEGRAL COLOR, MATCH DUNN EDWARDS
DE6333/ HAMILTON BLUE
EXTERIOR CEMENT PLASTER
MANUF: -
STYLE: 20/30 SAND FINISH
COLOR: INTEGRAL COLOR, MATCH DUNN EDWARDS
DE6370/ CHARCOAL SMUDGE
FIBER CEMENT SIDING
MANUF: JAMES HARDIE
STYLE: ARTISAN SIDING
COLOR: MATCH "ECP-1"
FIBER CEMENT SIDING
MANUF: JAMES HARDIE
STYLE: ARTISAN SIDING
COLOR: MATCH "ECP-2"
VERTICAL FIBER CEMENT SIDING
MANUF: NICHIHA
STYLE: VINTAGEWOOD
COLOR: CEDAR
CONCRETE MASONRY UNIT
MANUF: RCP BLOCK & BRICK
STYLE: SMOOTH FINISH, 8X8X16, STACKED BOND
COLOR: SAND
CONCRETE MASONRY UNIT
MANUF: RCP BLOCK & BRICK
STYLE: SMOOTH FINISH, 8X8X16, STACKED BOND
COLOR: MISSION
BRICK VENEER
MANUF: BELDEN BRICK
STYLE: -
COLOR: 8521 COARSE VELOUR
BRAKE METAL
MANUF: -
STYLE: 22 GAUGE ALUMINUM
COLOR: MATCH "ECP-4"
METAL AWNING
MANUF: -
STYLE: -
COLOR: MATCH "ECP-4"
METAL SCREEN
STYLE: 2" STEEL ANGLE FRAME W/ WIRE MESH
INFILL PANELS
COLOR: TBD
METAL AWNING
MANUF: -
STYLE: -
COLOR: MATCH "ECP-3"
TILE
MANUF: TILEBAR
STYLE: LOFT SEAFOAM 3X6 POLISHED GLASS
SUBWAY TILE
COLOR: SEAFOAM
GUARDRAIL SYSTEM
MANUF: VIVA RAILINGS
STYLE: STRUC PANEL SYSTEM
COLOR: CLEAR
GUARDRAIL SYSTEM
MANUF: VIVA RAILINGS
STYLE: STRUC PANEL SYSTEM
COLOR: TBD
GARAGE ROLLING DOOR
MANUF: WAYNE DALTON
STYLE: MODEL 600
COLOR: MATCH "ECP-4"
STOREFRONT DOOR
MANUF: ARCADIA
STYLE: -
COLOR: MATCH "ECP-4"
MULTI-SLIDE POCKET DOOR
MANUF: PER SCHEDULE AND SPECIFICATIONS
STYLE: ALUMINUM
COLOR: MATCH "ECP-4"
UTILITY SERVICE DOOR
MANUF: PER SCHEDULE AND SPECIFICATIONS
STYLE: HOLLOW METAL
COLOR: MATCH "ECP-2"
WINDOWS
MANUF: PER SCHEDULE AND SPECIFICATIONS
STYLE: VINYL
COLOR: MATCH "ECP-4"
STOREFRONT SYSTEM
MANUF: PER SCHEDULE AND SPECIFICATIONS
STYLE: ALUMINUM
COLOR: MATCH "ECP-4" (FRAME)
GLASS: TRANSPARENT / TRANSLUCENT
ECP-1
ECP-2
ECP-3
ECP-4
SDG-1
SDG-2
SDG-3
CMU-1
CMU-2
BRK-1
MTL-1
MTL-2
MTL-3
MTL-4
TLE-1
GRD-1
GRD-2
DR-1
DR-2
DR-3
DR-4
WIN-1
SF-1
EXT. FINISH SCHEDULE
GENERAL NOTES GENERAL NOTES
1. ALL FLASHING, SHEET METAL VENTS, EXHAUST FANS,
VENTILATORS, DOWNSPOUTS AND PIPE STACKS
SHALL BE PAINTED TO MATCH THE ADJACENT ROOF
OR WALL MATERIAL AND/OR COLOR.
2. ALL WINDOWS ARE RECESSED A MINIMUM OF 2".
SCALE: 1/8" = 1'-0"1 WEST / REAR ELEVATION
SCALE: 1/8" = 1'-0"2 NORTH / SIDE ELEVATION
KEYNOTES
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
BRK-1
BRK-1
Sept. 29, 2026
Item #9 Page 37 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
EXTERIOR PERSPECTIVES
A303
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
1 S/E PERSPECTIVE 2 N/E PERSPECTIVE
4 S/W PERSPECTIVE3 N/W PERSPECTIVE
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Sept. 29, 2026
Item #9 Page 38 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
BUILDING SECTIONS
A401
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
A B C J K LD E F G H I
44.50'
1ST FLOOR
60.83'
2ND FLOOR
71.75'
3RD FLOOR
82.67'
4TH FLOOR
93.58'
ROOF
15'-8" GROUND FLOOR HT
61'-11"
63'-9"
61'-3"
61'-3"
50'-7"
50'-7"
16'-10" 10'-11" 10'-11" 10'-11"
17'-10" 10'-11" 10'-11" 10'-11"
2'-6"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
01.01 01.01
01.0801.07
32.03 07.04 03.12
01.07 32.03
4/A609
403
4/A609
303
3/A609
203
1/A602
404
1/A602
304
1/A602
204
1/A602
406
1/A602
306
1/A602
206
2/A609
408
2/A609
308
1/A609
208
PARKING
BOILER
D1.5
D1.3
D1.2
SHOWERCLOSETKITCHEN TOILET
SHOWERCLOSETKITCHEN TOILET
SHOWERCLOSETKITCHEN TOILET
A2
A2
A2
BATHHALLKITCHEN TOILET
BATHHALLKITCHEN TOILET
BATHHALLKITCHEN TOILET
SHOWER
SHOWER
SHOWER
A2
A2
A2
BATH HALL KITCHENTOILET
BATH HALL KITCHENTOILET
BATH HALL KITCHENTOILET
SHOWER
SHOWER
SHOWER
D1.4
D1.1
D1
CLOSET KITCHENTOILET
CLOSET KITCHENTOILET
CLOSET KITCHENTOILET
SHOWER
SHOWER
SHOWER
4 A820
5 A820
2 A820
3 A820
8 A820
5 A855
A B C J K LD E F G H I
44.50'
1ST FLOOR
60.83'
2ND FLOOR
71.75'
3RD FLOOR
82.67'
4TH FLOOR
93.58'
ROOF
15'-10" 10'-11" 10'-11" 10'-11"
50'-7"
48'-7"
50'-3"
60'-9"
3'-6"
16'-8" GROUND FLOOR HT
17'-10" 10'-11"10'-11" 10'-11"
43.0'
4'-2"
8'-6" 8'-6" 8'-6"
9'-10 1/2" 9'-8 1/4"9'-10 1/2"
8'-6" 8'-6" 8'-6"
9'-10 1/2" 9'-10 1/2" 9'-8 1/4"
8'-0"
8'-0"
51'-3"
52'-9"
07.04 01.01
32.25 01.0701.08
01.07 06.23
01.01 03.12
1/A603
410
1/A603
310
1/A603
210
1/A606
402
1/A606
302
1/A606
202
32.03 STAIR 2
TRASHPARKING
TC
TC
TCWALKWAY
STAIR 1
PARKING PARKING
WALKWAY
WALKWAY W
W
W
A3
KITCHEN
A3
KITCHEN
A3
KITCHEN
C1
BATHCLOSETDEN HALL
C1
BATH
C1
BATH
CLOSETDEN HALL
CLOSETDEN HALL
AMENITY
COURTYARD
4 A820
5 A820
2 A820
3 A820
8 A820
5 A855
1 A820
14'-8" GROUND FLOOR HT
16'-8"
16'-2"
16'-8"
15'-2"
14.01 A805
-
A825
6 A810
-
A852
-
A850
-
A890
1 A825
-
A840
7 A840
8 A840
9 A840
11 A840
4 A840
13 A840
5 A840
6 A840
10 A840
12 A890
2 A841
2 A841
3 A855
-
A840
2 A840
3 A840
1 A841
-
A841
-
A842
-
A861
-
A862
-
A860
-
A870
-
A871
-
A872
-
A873
-
A500s
-
A885
-
A881
-
A890
-
A891
-
A892
-
1. 2.
3. 4.
5. 7.
6. GENERAL NOTESGENERAL NOTES
1. 2. FOR TYPICAL METAL STUD WALLS FROM LEVEL 1
FOR TYPICAL PARTY WALL SECTION
3. FOR TYPICAL WOOD STUD WALLS FROM
LEVELS 2-5
4. FOR TYPICAL WOOD FRAMED EXT. BALCONIES/
WALKWAYS5.
7. FOR ACOUSTIC JOINTS @ WALLS
6. FOR GENERAL ASSEMBLY, ACOUSTIC SEALANT
AND RESILIENT NOTES
FOR TYPICAL WOOD FRAMED EXT. CONCRETE
BALCONIES/WALKWAYS
8. FOR CONTINUATION OF RATING
AT DROP CEILINGS & SOFFITS9.
10. FOR PENETRATION OF 1-HR
ASSEMBLIES @ RECESSED FIXTURES11.
FOR PENETRATION OF 1-HR FLOOR/CEILING
ASSEMBLIES @ DUCT CHASE12.
13. 14.
FOR CONTINUATION OF RATING
AT WALL OUTLETS & TUBS
FOR PLUMBING PENETRATIONS OF 1-HR
INTERIOR WALL ASSEMBLIES
FOR PLUMBING PENETRATIONS OF 2-HR
EXTERIOR WALL ASSEMBLIES
FOR TYPICAL ROOF DETAILS
15. FOR GENERAL PENETRATION NOTES16.
FOR GENERAL PENETRATION DETAILS17.
18. 19.
20. 21.
FOR EXHAUST PENETRATIONS AT
EXTERIOR WALL ASSEMBLIES
FOR TYPICAL EXTERIOR FINISH
DETAILS
FOR TYPICAL WINDOW DETAILS
FOR TYPICAL STOREFRONT DETAILS
FOR TYPICAL DOOR DETAILS
DETAIL REFERENCES ARE CONSIDERED "TYPICAL"
(U.N.O.)
ALL DIMENSIONS ARE TO FACE OF STUD OR GRID LINE
U.N.O.
27. FOR TYPICAL ELEVATOR DETAILS
FOR TYPICAL STAIR DETAILS
FOR INTERIOR DETAILS
FOR ACCESSIBILIY AND SIGNAGE DETAILS
22. FOR ADDITIONAL INFORMATION ON DOORS
& WINDOWS
23. 24.
25. 26.
28. 01.01
01.07 01.08
03.12 06.23
07.04 14.01
32.03 32.25
PROPERTY LINE
PROPOSED GRADE
EXISTING GRADE
CURB @ ROOF EDGE, TYP
2x FRAMED PARAPET WALL / CURB: HEIGHT & FINISH PER
ELEVATION
DRAINAGE VALLEY/CRICKET: SLOPE TO DRAIN
TRASH CHUTE
BIO FILTER PLANTER/BMP AREA: REF. CIVIL DRAWINGS &
LANDSCAPE DWGS
EXTERIOR WALKWAY
SCALE: 1/8" = 1'-0"2 BUILDING SECTION
SCALE: 1/8" = 1'-0"1 BUILDING SECTION
KEYNOTES
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Sept. 29, 2026
Item #9 Page 39 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
BUILDING SECTIONS
A402
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
110 9 8 5 411 7 6 3 2
44.50'
1ST FLOOR
60.83'
2ND FLOOR
71.75'
3RD FLOOR
82.67'
4TH FLOOR
93.58'
ROOF
55'-9"
15'-8" GROUND FLOOR HT
16'-10" 10'-11" 10'-11" 10'-11"
13'-1"
10 FT MIN CLEARANCE
(NON-STOREFRONT)
50'-3"
1'-8"
14'-8" GROUND FLOOR HT
11'-0"
16'-4" 10'-11" 10'-11" 10'-11"
49'-7"
51'-7"
8'-0"
8'-0"
8'-0"
8'-0"
3'-6" 3'-6"
4'-2"
01.01 01.01
03.12 01.07
07.04 23.02
06.23 01.08
01.07 01.30
1/A607
401
1/A607
301
1/A607
201
1/A607
401
1/A607
301
1/A607
201
4/A609
403
4/A609
303
3/A609
203
PARKING
C2
C2
C2
KITCHEN DINING
KITCHEN DINING
KITCHEN DININGCLO
C1
C1
C1
FAUHALLDINING
FAUHALLDINING
FAUHALLDINING
D1.5
D1.3
D1.2
LAUNDRYHALLKITCHEN
LAUNDRYHALLKITCHEN
LAUNDRYHALLKITCHEN
DINING
DINING
DINING
LIVING
LIVING
LIVING CLO
CLO CLO
CLO CLO
4 A820
5 A820
2 A820
3 A820
8 A820
5 A855
13 A855
4 A860
8 A860
110 9 8 5 411 7 6 3 2
44.50'
1ST FLOOR
60.83'
2ND FLOOR
71.75'
3RD FLOOR
82.67'
4TH FLOOR
93.58'
ROOF
54'-9"
16'-8" GROUND FLOOR HT
54'-5"
50'-3"
17'-10" 10'-11" 10'-11" 10'-11"
50'-7"
53'-3"
9'-0"
10'-0"
43.6'
16'-3/4" GROUND FLOOR HT
4'-2"
16'-4" 10'-11" 10'-11" 10'-11"
8'-6" 8'-6" 8'-6"
9'-10 1/2" 9'-10 1/2" 9'-8 1/4"
8'-0"
8'-0"
8'-0"
3'-6"
MIN.
3'-6"
MIN.
3'-6"
MIN.
3'-6"
MIN.
3'-6"
MIN.
3'-6"
MIN.
4'-2"
01.07 32.25
01.01 01.01
03.12 14.07
06.23 14.07
07.04 01.07
06.26 06.26
1/A603
410
1/A603
310
1/A603
210
1/A601
407
1/A601
307
1/A601
207
1/A602
406
1/A602
306
1/A602
206
PARKING
TRASH ROOM
COMMERCIAL #2
TC
TC
W
W
W
A3
A3
A3
W/D HALL BEDROOMSHOWER
W/D HALL BEDROOMSHOWER
W/D HALL BEDROOMSHOWER
HALL
HALL
HALL
FAU
FAU
FAU
A1
A1
A1
LIVINGKITCHEN
LIVINGKITCHEN
LIVINGKITCHEN
A2
A2
A2
BATHBEDROOM
BATHBEDROOM
BATHBEDROOM
FAU
FAU
FAU
W/D
W/D
W/D
TOILET
TOILET
TOILET
CLOSET
CLOSET
CLOSET
4 A820
5 A820
2 A820
3 A820
8 A820
11 A820
12 A820
5 A855
13 A855
16'-2"
01.08 14.01
TC
A805
-
A825
6 A810
-
A852
-
A850
-
A890
1 A825
-
A840
7 A840
8 A840
9 A840
11 A840
4 A840
13 A840
5 A840
6 A840
10 A840
12 A890
2 A841
2 A841
3 A855
-
A840
2 A840
3 A840
1 A841
-
A841
-
A842
-
A861
-
A862
-
A860
-
A870
-
A871
-
A872
-
A873
-
A500s
-
A885
-
A881
-
A890
-
A891
-
A892
-
1. 2.
3. 4.
5. 7.
6. GENERAL NOTESGENERAL NOTES
1. 2. FOR TYPICAL METAL STUD WALLS FROM LEVEL 1
FOR TYPICAL PARTY WALL SECTION
3. FOR TYPICAL WOOD STUD WALLS FROM
LEVELS 2-5
4. FOR TYPICAL WOOD FRAMED EXT. BALCONIES/
WALKWAYS5.
7. FOR ACOUSTIC JOINTS @ WALLS
6. FOR GENERAL ASSEMBLY, ACOUSTIC SEALANT
AND RESILIENT NOTES
FOR TYPICAL WOOD FRAMED EXT. CONCRETE
BALCONIES/WALKWAYS
8. FOR CONTINUATION OF RATING
AT DROP CEILINGS & SOFFITS9.
10. FOR PENETRATION OF 1-HR
ASSEMBLIES @ RECESSED FIXTURES11.
FOR PENETRATION OF 1-HR FLOOR/CEILING
ASSEMBLIES @ DUCT CHASE12.
13. 14.
FOR CONTINUATION OF RATING
AT WALL OUTLETS & TUBS
FOR PLUMBING PENETRATIONS OF 1-HR
INTERIOR WALL ASSEMBLIES
FOR PLUMBING PENETRATIONS OF 2-HR
EXTERIOR WALL ASSEMBLIES
FOR TYPICAL ROOF DETAILS
15. FOR GENERAL PENETRATION NOTES16.
FOR GENERAL PENETRATION DETAILS17.
18. 19.
20. 21.
FOR EXHAUST PENETRATIONS AT
EXTERIOR WALL ASSEMBLIES
FOR TYPICAL EXTERIOR FINISH
DETAILS
FOR TYPICAL WINDOW DETAILS
FOR TYPICAL STOREFRONT DETAILS
FOR TYPICAL DOOR DETAILS
DETAIL REFERENCES ARE CONSIDERED "TYPICAL"
(U.N.O.)
ALL DIMENSIONS ARE TO FACE OF STUD OR GRID LINE
U.N.O.
27. FOR TYPICAL ELEVATOR DETAILS
FOR TYPICAL STAIR DETAILS
FOR INTERIOR DETAILS
FOR ACCESSIBILIY AND SIGNAGE DETAILS
22. FOR ADDITIONAL INFORMATION ON DOORS
& WINDOWS
23. 24.
25. 26.
28. 01.01
01.07 01.08
01.30 03.12
06.23 06.26
07.04 14.01
14.07 23.02
32.25 PROPERTY LINE
PROPOSED GRADE
EXISTING GRADE
RECESSED VEHICULAR DOOR
CURB @ ROOF EDGE, TYP
2x FRAMED PARAPET WALL / CURB: HEIGHT & FINISH PER
ELEVATION
UNIT BALCONY, TYP.
DRAINAGE VALLEY/CRICKET: SLOPE TO DRAIN
TRASH CHUTE
GREASE SHAFT
MECH EQUIPMENT: REF. MECHANICAL DWGS
EXTERIOR WALKWAY
SCALE: 1/8" = 1'-0"2 BUILDING SECTION
SCALE: 1/8" = 1'-0"1 BUILDING SECTION
KEYNOTES
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Sept. 29, 2026
Item #9 Page 40 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
A1 UNIT PLAN
A601
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
DW
REF
W/D
FAU
TRSH
12'-6" 12'-6"
15'-8" 14'-7" 1"
25'-0"
30'-4"
1'-6"
MIN
1'-6"
MIN
6'-2" 6'-8" 7'-11"9'-6"
3'-9" 8'-9"
5'-0" 4'-4" 5'-2" 1"13'-0" 2'-9"
3'-2" 1'-10"
4'-6" 3'-2" 4'-10"
5'-6" 9'-11"4'-8" 5'-6" 4'-8"
3'-8" 10'-0"
30'-4"
1/A701
A
9/A704
A
D-01
D-11
D-03 D-06
D-02
D-14 W-02
W-01
01.10 05.16
06.03 06.11
07.04 07.1909.04
10.08 06.27
CL
WS
MW P
BEDROOM
KITCHEN
FIN: A
FIN: A
BATH
FIN: B
LIVING
FIN: A
FIN: A
A890
11 A501
-
A891
2 A502
-
A503
-
A891
1 A891
3 A891
6 A891
14 A891
15 A891
18 GENERAL NOTES
1. 2. FOR 1 HOUR WALL AT BATHTUB / SHOWER
FOR ADDITIONAL INFORMATION ON
DOORS & WINDOW REFERENCES &
NOTES
3. DETAIL REFERENCES ARE CONSIDERED
"TYPICAL" (U.N.O.) AND ARE TO BE APPLIED TO
SIMILAR ITEMS WHETHER REFERENCED OR NOT.
SHOWER COMPARTMENTS AND BATHTUBS WITH
INSTALLED SHOWER HEADS SHALL BE FINISHED
WITH A NONABSORBENT SURFACE THAT
EXTENDS TO THE HEIGHT OF NOT LESS THAN 6
FEET ABOVE THE FLOOR.
4. FOR BATHTUB CLEARANCES AND GRAB
BAR BLOCKING LOCATIONS
FOR TOILET CLEARANCES AND GRAB BAR
BLOCKING LOCATIONS
5. 6.
FOR LAVATORY CLEARANCES AND
BATH ACCESSORY MOUNTING
HEIGHTS
FOR KITCHEN SINK CLEARANCES
8. 9.
7. FOR SHOWER CLEARANCES
TYPE FLOOR WALL
A
B
CEILING
-
-
-
-
-
-
-
-
-
-
-
-
INT. FINISH SCHEDULE
WALL LEGEND
2 HR 2X6 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X4 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X6 FIRE BARRIER W/ FIRE-RETARDANT
TREATED STUD
2 HR 2X6 FIRE BARRIER
2 HR 2X4 FIRE BARRIER
2 HR 2X6 WOOD STUD
2 HR 2X4 WOOD STUD
1 HR 2X6 WOOD STUD
1 HR 2X4 WOOD STUD
1 HR PARTY WALL (2) 2X6 WOOD STUD WALLS
W/ 2" GAP BETWEEN FRAMING
NON-RATED 2X6 STANDARD WOOD WALL
NON-RATED 2X4 STANDARD WOOD WALL
SOFFIT / FLOOR ABOVE
WALL LEGEND
CIP CONCRETE COLUMN PER STRUCTURAL
(REFERENCE SLAB PLANS FOR COLUMN SIZE)
12" CONCRETE WALL
8" CONCRETE WALL
8" CMU WALL
2 HR 6" METAL STUD
1 HR 6" METAL STUD
NON-RATED 6" METAL STUD
SOFFIT / FLOOR ABOVE
JJ
4'-8" 6'-6" 4'-4"
EQ. EQ.
EQ. EQ.
EQ.EQ.
EQ. EQ.
EQ. EQ. EQ. EQ.
EQ. EQ.
EQ. 6'-6" EQ.EQ. 6'-6" EQ.
EQ. 7'-0" EQ.
5'-0" 5'-0" 7'-0" 2'-6"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
EQ. EQ.
EQ. EQ.
LED DOWNLIGHT
NOTE:
FOR LIGHT/FIXTURE SPECIFICATIONS, SWITCHING, AND
OTHER ELECTRICAL ITEMS REFER TO ELECTRICAL DWGS
WALL SCONCE CENTERED ON SINK
JUNCTION BOX
CEILING FAN
COMBINATION CARBON MONOXIDE/
SMOKE DETECTOR
SMOKE DETECTOR
EXHAUST FAN CENTERED ON TOILET
GYPSUM BOARD SOFFIT
J
RCP LEGEND
01.10 05.16
06.03 06.11
06.27 07.04
07.19 09.04
10.08 LINE OF WALL / FLOOR BELOW
EXTERIOR GUARDRAIL: 42" MIN. ABOVE ADJACENT FINISHED FLOOR BALCONY FRAMING: REFER TO STRUCTURAL DWGS. W/
ELASTOMERIC DECK COATING OVER OVERFRAMING, SLOPE 1.5-2%
TO DRAIN OR EXTERIOR PER PLAN
WIRE SHELF & POLE: +66" A.F.F. @ TYP. UNITS
6' X 6' MINIMUM PRIVATE OPEN SPACE AT BALCONY
DRAINAGE VALLEY/CRICKET: SLOPE TO DRAIN
W/D DRAINAGE PAN: FOR DRAIN REF. PLUMBING DWGS
SOFFIT: REF. RCPS
DOOR SWING MANEUVERING CLEARANCE
SCALE: 1/4" = 1'-0"1 A1 UNIT PLANSCALE: 1/4" = 1'-0"2 A1 RCP
KEYNOTES
756 SF
UNIT QUANTITY: 6
UNIT ORIENTATION
207, 307, 407 = STANDARD
205, 305, 405 = MIRRORED
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Sept. 29, 2026
Item #9 Page 41 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
A2 UNIT PLAN
A602
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
DW
REF
W/D
FAU
TRSH
MW
52'-8"
7'-10"34'-2"10'-8"
52'-8"
30'-3"5'-11"
1"36'-2"1/2"
1"36'-3"
19'-3"17'-0"
3'-9" 7'-5" 5'-10" 2'-6" 10'-9"
13'-7" 8'-9" 5'-3" 2'-7"11'-10"
24'-4" 14'-0" 14'-4"
1'-6"
MIN
1'-10"
36'-3 1/2"
4'-6"
24'-3" 5'-4" 7'-1" 4'-0" 4'-0" 8'-0"
7'-11" 4'-0" 5'-2"
3'-7" 2'-3" 3'-9" 7'-0"
4'-0" 2'-0"4'-8"
4'-0" 5'-9" 4'-7"
1'-6"
MIN
6'-0" 3'-6" 12'-3" 3'-6"
5/A701
B
14/A704
B
1/A705
C
D-01
D-06
D-03
D-02
D-12
D-03
D-02
D-06
D-14
W-04
W-03
W-05 W-05
W-01
07.08 01.10
05.16 06.03
06.11 07.19
09.04 10.08
06.27 D-16
07.04 CLCL
CL
BENCH
P
WS
ADJACENT
UNIT WALL:
SEE BLDG.
PLANS
DINING
FIN: A
KITCHEN
FIN: A
BEDROOM
FIN: A
BATH
FIN: B
LIVING
FIN: A
BATH
FIN: B
FIN: B
FIN: A
OFFICE/DEN
FIN: A
J
J
J
J
JJ
EQ. EQ. 5'-2"
7'-9" 7'-6" 7'-6" 4'-0"
EQ. EQ.
EQ. EQ.
EQ.EQ.
EQ. EQ.
EQ.EQ.
2'-3"EQ. EQ.
EQ. EQ.
EQ. EQ.
EQ. EQ.
EQ. 7'-0" EQ.
EQ. EQ.
3'-0" EQ. EQ.
EQ. EQ.
3'-4"
EQ. EQ.
EQ. EQ.
EQ. EQ.
EQ. EQ.
EQ. EQ.8'-0"
EQ. EQ.
EQ. 6'-0" EQ.6'-0"
EQ. EQ.3'-0" EQ.
EQ. EQ.8'-0"
3'-4"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
ADJACENT
UNIT WALL:
SEE BLDG.
PLANS
A890
11 A501
-
A891
2 A502
-
A503
-
A891
1 A891
3 A891
6 A891
14 A891
15 A891
18 GENERAL NOTES
1. 2. FOR 1 HOUR WALL AT BATHTUB / SHOWER
FOR ADDITIONAL INFORMATION ON
DOORS & WINDOW REFERENCES &
NOTES
3. DETAIL REFERENCES ARE CONSIDERED
"TYPICAL" (U.N.O.) AND ARE TO BE APPLIED TO
SIMILAR ITEMS WHETHER REFERENCED OR NOT.
SHOWER COMPARTMENTS AND BATHTUBS WITH
INSTALLED SHOWER HEADS SHALL BE FINISHED
WITH A NONABSORBENT SURFACE THAT
EXTENDS TO THE HEIGHT OF NOT LESS THAN 6
FEET ABOVE THE FLOOR.
4. FOR BATHTUB CLEARANCES AND GRAB
BAR BLOCKING LOCATIONS
FOR TOILET CLEARANCES AND GRAB BAR
BLOCKING LOCATIONS
5. 6.
FOR LAVATORY CLEARANCES AND
BATH ACCESSORY MOUNTING
HEIGHTS
FOR KITCHEN SINK CLEARANCES
8. 9.
7. FOR SHOWER CLEARANCES
TYPE FLOOR WALL
A
B
CEILING
-
-
-
-
-
-
-
-
-
-
-
-
INT. FINISH SCHEDULE
WALL LEGEND
2 HR 2X6 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X4 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X6 FIRE BARRIER W/ FIRE-RETARDANT
TREATED STUD
2 HR 2X6 FIRE BARRIER
2 HR 2X4 FIRE BARRIER
2 HR 2X6 WOOD STUD
2 HR 2X4 WOOD STUD
1 HR 2X6 WOOD STUD
1 HR 2X4 WOOD STUD
1 HR PARTY WALL (2) 2X6 WOOD STUD WALLS
W/ 2" GAP BETWEEN FRAMING
NON-RATED 2X6 STANDARD WOOD WALL
NON-RATED 2X4 STANDARD WOOD WALL
SOFFIT / FLOOR ABOVE
WALL LEGEND
CIP CONCRETE COLUMN PER STRUCTURAL
(REFERENCE SLAB PLANS FOR COLUMN SIZE)
12" CONCRETE WALL
8" CONCRETE WALL
8" CMU WALL
2 HR 6" METAL STUD
1 HR 6" METAL STUD
NON-RATED 6" METAL STUD
SOFFIT / FLOOR ABOVE
LED DOWNLIGHT
NOTE:
FOR LIGHT/FIXTURE SPECIFICATIONS, SWITCHING, AND
OTHER ELECTRICAL ITEMS REFER TO ELECTRICAL DWGS
WALL SCONCE CENTERED ON SINK
JUNCTION BOX
CEILING FAN
COMBINATION CARBON MONOXIDE/
SMOKE DETECTOR
SMOKE DETECTOR
EXHAUST FAN CENTERED ON TOILET
GYPSUM BOARD SOFFIT
J
RCP LEGEND
01.10 05.16
06.03 06.11
06.27 07.04
07.08 07.19
09.04 10.08
LINE OF WALL / FLOOR BELOW
EXTERIOR GUARDRAIL: 42" MIN. ABOVE ADJACENT FINISHED FLOOR BALCONY FRAMING: REFER TO STRUCTURAL DWGS. W/
ELASTOMERIC DECK COATING OVER OVERFRAMING, SLOPE 1.5-2%
TO DRAIN OR EXTERIOR PER PLAN
WIRE SHELF & POLE: +66" A.F.F. @ TYP. UNITS
6' X 6' MINIMUM PRIVATE OPEN SPACE AT BALCONY
DRAINAGE VALLEY/CRICKET: SLOPE TO DRAIN
DRAIN: REF. PLUMBING DWGS
W/D DRAINAGE PAN: FOR DRAIN REF. PLUMBING DWGS
SOFFIT: REF. RCPS
DOOR SWING MANEUVERING CLEARANCE
SCALE: 1/4" = 1'-0"1 A2 UNIT PLANSCALE: 1/4" = 1'-0"2 A2 RCP
KEYNOTES
1,701 SF
UNIT QUANTITY: 6
UNIT ORIENTATION
206, 306, 406 = STANDARD
204, 304, 404 = MIRRORED
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Sept. 29, 2026
Item #9 Page 42 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
A3 UNIT PLAN
A603
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
REF
DW
W/D
MICRO
FAU
TRSH
36'-10" 10'-2"
7'-5 1/2" 4'-9 1/2" 32'-3" 2'-6"
14'-9" 15'-6"
30'-3"
9"
5'-0" 9'-8" 5'-0" 8'-10"
47'-0"
47'-0"
1/2" 29'-3"
4'-5" 8'-9" 6'-6" 12'-7"
1'-6"
MIN
29'-3 1/2"
3'-2" 3'-2" 1'-8"1'-8"
2'-4"
10'-8" 4'-1"
3'-1" 4'-0" 2'-9" 5'-9"
2'-0" 2'-0"
5'-0" 4'-8" 3'-10"
4'-10 1/2" 4'-0" 7'-7"4'-9" 3'-10"
4'-3 1/2"
3'-9" 3'-4" 8'-3" 9'-6"
8"
21'-6"
4'-8" 12'-0" 4'-10"1'-8" 1'-8"
1/A704
A
9/A701
C
5/A705
D
D-14
D-02
D-07
D-07
D-12 D-03
D-01
W-05
W-02
W-02
W-01
W-07 W-06 W-07
W-05
D-16
D-06
07.08 01.10
06.11 07.19
09.04 10.08
05.16 06.03
07.04 06.27
CL
BENCH
P
WS
POWDER
FIN: B
DINING
FIN: A
KITCHEN
FIN: A
BEDROOM
FIN: A
BATH
FIN: B
LIVING
FIN: A
J
J
J
J
J
EQ. EQ.
5'-6"3'-0" 5'-6"
5'-2" 8'-0"
5'-2"8'-0"
EQ. EQ.EQ. EQ.
EQ. EQ. EQ.EQ.
EQ. EQ.
EQ. EQ.
2'-0" EQ. EQ.
EQ. EQ. EQ.EQ.
8'-0" 8'-0" 3'-0"EQ. EQ.
EQ. EQ.8'-0"
5'-4" EQ. EQ.
EQ. 6'-0" EQ.
EQ. 9'-0" EQ.
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
A890
11 A501
-
A891
2 A502
-
A503
-
A891
1 A891
3 A891
6 A891
14 A891
15 A891
18 GENERAL NOTES
1. 2. FOR 1 HOUR WALL AT BATHTUB / SHOWER
FOR ADDITIONAL INFORMATION ON
DOORS & WINDOW REFERENCES &
NOTES
3. DETAIL REFERENCES ARE CONSIDERED
"TYPICAL" (U.N.O.) AND ARE TO BE APPLIED TO
SIMILAR ITEMS WHETHER REFERENCED OR NOT.
SHOWER COMPARTMENTS AND BATHTUBS WITH
INSTALLED SHOWER HEADS SHALL BE FINISHED
WITH A NONABSORBENT SURFACE THAT
EXTENDS TO THE HEIGHT OF NOT LESS THAN 6
FEET ABOVE THE FLOOR.
4. FOR BATHTUB CLEARANCES AND GRAB
BAR BLOCKING LOCATIONS
FOR TOILET CLEARANCES AND GRAB BAR
BLOCKING LOCATIONS
5. 6.
FOR LAVATORY CLEARANCES AND
BATH ACCESSORY MOUNTING
HEIGHTS
FOR KITCHEN SINK CLEARANCES
8. 9.
7. FOR SHOWER CLEARANCES
TYPE FLOOR WALL
A
B
CEILING
-
-
-
-
-
-
-
-
-
-
-
-
INT. FINISH SCHEDULE
WALL LEGEND
2 HR 2X6 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X4 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X6 FIRE BARRIER W/ FIRE-RETARDANT
TREATED STUD
2 HR 2X6 FIRE BARRIER
2 HR 2X4 FIRE BARRIER
2 HR 2X6 WOOD STUD
2 HR 2X4 WOOD STUD
1 HR 2X6 WOOD STUD
1 HR 2X4 WOOD STUD
1 HR PARTY WALL (2) 2X6 WOOD STUD WALLS
W/ 2" GAP BETWEEN FRAMING
NON-RATED 2X6 STANDARD WOOD WALL
NON-RATED 2X4 STANDARD WOOD WALL
SOFFIT / FLOOR ABOVE
WALL LEGEND
CIP CONCRETE COLUMN PER STRUCTURAL
(REFERENCE SLAB PLANS FOR COLUMN SIZE)
12" CONCRETE WALL
8" CONCRETE WALL
8" CMU WALL
2 HR 6" METAL STUD
1 HR 6" METAL STUD
NON-RATED 6" METAL STUD
SOFFIT / FLOOR ABOVE
LED DOWNLIGHT
NOTE:
FOR LIGHT/FIXTURE SPECIFICATIONS, SWITCHING, AND
OTHER ELECTRICAL ITEMS REFER TO ELECTRICAL DWGS
WALL SCONCE CENTERED ON SINK
JUNCTION BOX
CEILING FAN
COMBINATION CARBON MONOXIDE/
SMOKE DETECTOR
SMOKE DETECTOR
EXHAUST FAN CENTERED ON TOILET
GYPSUM BOARD SOFFIT
J
RCP LEGEND
29'-3 1/2"
1/2" 29'-3"
9'-8" 5'-0" 8'-10"
9"
5'-0"
6'-8" 3'-6"
10'-2"
07.08 06.03
07.04 06.27
CL
REF
W/D
MICRO
FAU
DW TRSH
P
WS
01.10 05.16
06.03 06.11
06.27 07.04
07.08 07.19
09.04 10.08
LINE OF WALL / FLOOR BELOW
EXTERIOR GUARDRAIL: 42" MIN. ABOVE ADJACENT FINISHED FLOOR BALCONY FRAMING: REFER TO STRUCTURAL DWGS. W/
ELASTOMERIC DECK COATING OVER OVERFRAMING, SLOPE 1.5-2%
TO DRAIN OR EXTERIOR PER PLAN
WIRE SHELF & POLE: +66" A.F.F. @ TYP. UNITS
6' X 6' MINIMUM PRIVATE OPEN SPACE AT BALCONY
DRAINAGE VALLEY/CRICKET: SLOPE TO DRAIN
DRAIN: REF. PLUMBING DWGS
W/D DRAINAGE PAN: FOR DRAIN REF. PLUMBING DWGS
SOFFIT: REF. RCPS
DOOR SWING MANEUVERING CLEARANCE
SCALE: 1/4" = 1'-0"1 A3 UNIT PLAN
SCALE: 1/4" = 1'-0"3 A3 RCP
SCALE: 1/4" = 1'-0"2 A3 - ALT BALCONY
SCALE: 1/4" = 1'-0"3 A3 - ALT KITCHEN LAYOUT
KEYNOTES
1,121 SF
UNIT QUANTITY: 1
UNIT ORIENTATION
310& 410 = STANDARD
1,121 SF
UNIT QUANTITY: 1
UNIT ORIENTATION
210 = STANDARD
1,121 SF
UNIT QUANTITY: 2
UNIT ORIENTATION
210 & 310 = STANDARD
SEE 1/607 FOR ADDITIONAL
DIMENSIONS AND CALLOUTS
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Sept. 29, 2026
Item #9 Page 43 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
B1 UNIT PLAN
A604
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
DW
REF
W/D
FAU
TRSH
MICRO
1/2" 14'-7" 5'-3" 2'-6" 12'-1"
10'-6"7'-1"3'-3"4'-5"10'-5"13'-0"
14'-5" 4'-10" 6'-4" 1'-8" 7'-2"
11'-0" 27'-8" 14'-6"
53'-2"
34'-5 1/2"
48'-8"
1'-6"
MIN
3'-1" 2'-2"
4'-6" 1'-9" 4'-9" 12'-10" 4'-5" 4'-1" 6'-3" 4'-1" 3'-9" 6'-9" 2'-10" 2'-3"4'-8" 4'-8"
2'-9"
1'-10"
5'-9" 6'-4"
1/2" 34'-5"
3'-2" 3'-2"
4'-6" 4'-0"
6"
7'-2"
4'-4" 6'-8"
15'-5"
1'-6"
MIN
1'-6"
MIN
34'-5 1/2"
1/A702
D
9/A705
E
14/A705
F
D-01
D-05
D-02
D-07
D-03
D-06
D-04
D-06
D-03
D-14
W-02
W-01
W-01
W-03
D-02
07.08 01.10
05.16 06.03
06.11 07.04
07.19 09.04
10.08 06.27
BENCH
CL CL
4 P
WSDINING
FIN: A
KITCHEN
FIN: A
BEDROOM
FIN: A
BATH
FIN: B
LIVING
FIN: A
BEDROOM
FIN: A FIN: A
FIN: A
FIN: B
BATH
FIN: B
J
J
J
J
J J
EQ. EQ.EQ. EQ.EQ. EQ.5'-0" 3'-0"
5'-2" 6'-5" 5'-7" EQ. EQ.EQ. EQ.
5'-2"5'-9"
EQ.EQ.
EQ.EQ. EQ. EQ.
EQ. EQ.
EQ. EQ.
EQ. EQ. EQ. EQ.
4'-0"
5'-0" EQ.EQ.
EQ. EQ. EQ. EQ.
3'-0"
EQ. EQ.
3'-0"
EQ. 10'-0" EQ.
EQ. EQ.6'-0"
3'-0" 6'-6" 6'-6" 6'-0"
EQ.3'-0" EQ. 3'-0"
EQ. EQ.
EQ. EQ.
4 8'-0"
8'-0"
8'-0"
8'-0" 8'-0"
8'-0" 8'-0"8'-0"
8'-0"
8'-0"
8'-0"
A890
11 A501
-
A891
2 A502
-
A503
-
A891
1 A891
3 A891
6 A891
14 A891
15 A891
18 GENERAL NOTES
1. 2. FOR 1 HOUR WALL AT BATHTUB / SHOWER
FOR ADDITIONAL INFORMATION ON
DOORS & WINDOW REFERENCES &
NOTES
3. DETAIL REFERENCES ARE CONSIDERED
"TYPICAL" (U.N.O.) AND ARE TO BE APPLIED TO
SIMILAR ITEMS WHETHER REFERENCED OR NOT.
SHOWER COMPARTMENTS AND BATHTUBS WITH
INSTALLED SHOWER HEADS SHALL BE FINISHED
WITH A NONABSORBENT SURFACE THAT
EXTENDS TO THE HEIGHT OF NOT LESS THAN 6
FEET ABOVE THE FLOOR.
4. FOR BATHTUB CLEARANCES AND GRAB
BAR BLOCKING LOCATIONS
FOR TOILET CLEARANCES AND GRAB BAR
BLOCKING LOCATIONS
5. 6.
FOR LAVATORY CLEARANCES AND
BATH ACCESSORY MOUNTING
HEIGHTS
FOR KITCHEN SINK CLEARANCES
8. 9.
7. FOR SHOWER CLEARANCES
TYPE FLOOR WALL
A
B
CEILING
-
-
-
-
-
-
-
-
-
-
-
-
INT. FINISH SCHEDULE
WALL LEGEND
2 HR 2X6 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X4 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X6 FIRE BARRIER W/ FIRE-RETARDANT
TREATED STUD
2 HR 2X6 FIRE BARRIER
2 HR 2X4 FIRE BARRIER
2 HR 2X6 WOOD STUD
2 HR 2X4 WOOD STUD
1 HR 2X6 WOOD STUD
1 HR 2X4 WOOD STUD
1 HR PARTY WALL (2) 2X6 WOOD STUD WALLS
W/ 2" GAP BETWEEN FRAMING
NON-RATED 2X6 STANDARD WOOD WALL
NON-RATED 2X4 STANDARD WOOD WALL
SOFFIT / FLOOR ABOVE
WALL LEGEND
CIP CONCRETE COLUMN PER STRUCTURAL
(REFERENCE SLAB PLANS FOR COLUMN SIZE)
12" CONCRETE WALL
8" CONCRETE WALL
8" CMU WALL
2 HR 6" METAL STUD
1 HR 6" METAL STUD
NON-RATED 6" METAL STUD
SOFFIT / FLOOR ABOVE
LED DOWNLIGHT
NOTE:
FOR LIGHT/FIXTURE SPECIFICATIONS, SWITCHING, AND
OTHER ELECTRICAL ITEMS REFER TO ELECTRICAL DWGS
WALL SCONCE CENTERED ON SINK
JUNCTION BOX
CEILING FAN
COMBINATION CARBON MONOXIDE/
SMOKE DETECTOR
SMOKE DETECTOR
EXHAUST FAN CENTERED ON TOILET
GYPSUM BOARD SOFFIT
J
RCP LEGEND
01.10 05.16
06.03 06.11
06.27 07.04
07.08 07.19
09.04 10.08
LINE OF WALL / FLOOR BELOW
EXTERIOR GUARDRAIL: 42" MIN. ABOVE ADJACENT FINISHED FLOOR BALCONY FRAMING: REFER TO STRUCTURAL DWGS. W/
ELASTOMERIC DECK COATING OVER OVERFRAMING, SLOPE 1.5-2%
TO DRAIN OR EXTERIOR PER PLAN
WIRE SHELF & POLE: +66" A.F.F. @ TYP. UNITS
6' X 6' MINIMUM PRIVATE OPEN SPACE AT BALCONY
DRAINAGE VALLEY/CRICKET: SLOPE TO DRAIN
DRAIN: REF. PLUMBING DWGS
W/D DRAINAGE PAN: FOR DRAIN REF. PLUMBING DWGS
SOFFIT: REF. RCPS
DOOR SWING MANEUVERING CLEARANCE
SCALE: 1/4" = 1'-0"1 B1 UNIT PLAN
SCALE: 1/4" = 1'-0"2 B1 RCP
KEYNOTES
1,560 SF
UNIT QUANTITY: 3
UNIT ORIENTATION
209, 309, 409 = STANDARD
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Sept. 29, 2026
Item #9 Page 44 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
B2 UNIT PLAN
A605
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
REF
DW
MICRO
W/DFAU
TRSH
50'-6 1/2"
1'-6" 19'-0" 31'-6"
37'-6"
25'-9" 11'-9"
50'-6" 1/2"
17'-8" 13'-10"
8'-0" 10'-0" 14'-2"
10'-5" 10'-9" 4'-10" 4'-0" 5'-4" 7'-2"
1'-0" 1/2"7'-0"
10'-9"
1'-0"
12'-6" 13'-3"
1'-6"
MIN
7'-2" 10'-9"5'-4" 2'-6"
4'-1" 4'-8" 3'-0"
6'-8" 3'-2" 3'-2" 6'-0" 2'-5" 2'-0" 4'-0" 3'-2" 3'-2"13'-3" 3'-6" 6'-9" 4'-9"
6'-0" 4'-9" 3'-1"
4'-6" 4'-2" 8'-6" 4'-9"3'-10"
2'-6"
50'-6 1/2"
37'-6"
5'-4" 32'-2"
4/A704
B
5/A702
E
5/A706
H
1/A706
G
D-01
D-11
D-03
D-03
D-09
D-02
D-14
D-02
D-03
D-03
D-06 W-09
W-08
W-01
W-07 W-07 W-07 W-06 W-07
W-07 W-06 W-07
01.10 06.11
07.19 09.04
10.08 06.27
07.08 05.16
06.03 07.04
BENCH
CL
CL
WS
P
POWDER
FIN: B
DINING
FIN: A
KITCHEN
FIN: A
BEDROOM
FIN: A
BATH
FIN: B
LIVING
FIN: A
BEDROOM
FIN: A
FIN: B
FIN: A
BATH
FIN: B
FIN: B
J
J
J
J
J
J
EQ. EQ.EQ. EQ. EQ. EQ.
EQ. EQ.
EQ. EQ.
5'-4" 4'-10" EQ. EQ.
EQ. EQ.
EQ. EQ.
EQ. EQ. EQ. EQ. EQ. EQ.
5'-6" 6'-6" 6'-6"
EQ.EQ.
EQ. EQ. EQ.EQ.
EQ. EQ.
EQ. EQ.
EQ. EQ.2'-4"
EQ. EQ.
EQ. EQ.
5'-0"
EQ. EQ.
11'-0"EQ. EQ. EQ. 7'-0" EQ.
EQ. 7'-6" EQ.
EQ. EQ.6'-0"
6'-0" 7'-0"
EQ. EQ.7'-0"
EQ. 11'-0" EQ.
EQ. EQ.
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
A890
11 A501
-
A891
2 A502
-
A503
-
A891
1 A891
3 A891
6 A891
14 A891
15 A891
18 GENERAL NOTES
1. 2. FOR 1 HOUR WALL AT BATHTUB / SHOWER
FOR ADDITIONAL INFORMATION ON
DOORS & WINDOW REFERENCES &
NOTES
3. DETAIL REFERENCES ARE CONSIDERED
"TYPICAL" (U.N.O.) AND ARE TO BE APPLIED TO
SIMILAR ITEMS WHETHER REFERENCED OR NOT.
SHOWER COMPARTMENTS AND BATHTUBS WITH
INSTALLED SHOWER HEADS SHALL BE FINISHED
WITH A NONABSORBENT SURFACE THAT
EXTENDS TO THE HEIGHT OF NOT LESS THAN 6
FEET ABOVE THE FLOOR.
4. FOR BATHTUB CLEARANCES AND GRAB
BAR BLOCKING LOCATIONS
FOR TOILET CLEARANCES AND GRAB BAR
BLOCKING LOCATIONS
5. 6.
FOR LAVATORY CLEARANCES AND
BATH ACCESSORY MOUNTING
HEIGHTS
FOR KITCHEN SINK CLEARANCES
8. 9.
7. FOR SHOWER CLEARANCES
TYPE FLOOR WALL
A
B
CEILING
-
-
-
-
-
-
-
-
-
-
-
-
INT. FINISH SCHEDULE
WALL LEGEND
2 HR 2X6 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X4 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X6 FIRE BARRIER W/ FIRE-RETARDANT
TREATED STUD
2 HR 2X6 FIRE BARRIER
2 HR 2X4 FIRE BARRIER
2 HR 2X6 WOOD STUD
2 HR 2X4 WOOD STUD
1 HR 2X6 WOOD STUD
1 HR 2X4 WOOD STUD
1 HR PARTY WALL (2) 2X6 WOOD STUD WALLS
W/ 2" GAP BETWEEN FRAMING
NON-RATED 2X6 STANDARD WOOD WALL
NON-RATED 2X4 STANDARD WOOD WALL
SOFFIT / FLOOR ABOVE
WALL LEGEND
CIP CONCRETE COLUMN PER STRUCTURAL
(REFERENCE SLAB PLANS FOR COLUMN SIZE)
12" CONCRETE WALL
8" CONCRETE WALL
8" CMU WALL
2 HR 6" METAL STUD
1 HR 6" METAL STUD
NON-RATED 6" METAL STUD
SOFFIT / FLOOR ABOVE
LED DOWNLIGHT
NOTE:
FOR LIGHT/FIXTURE SPECIFICATIONS, SWITCHING, AND
OTHER ELECTRICAL ITEMS REFER TO ELECTRICAL DWGS
WALL SCONCE CENTERED ON SINK
JUNCTION BOX
CEILING FAN
COMBINATION CARBON MONOXIDE/
SMOKE DETECTOR
SMOKE DETECTOR
EXHAUST FAN CENTERED ON TOILET
GYPSUM BOARD SOFFIT
J
RCP LEGEND
01.10 05.16
06.03 06.11
06.27 07.04
07.08 07.19
09.04 10.08
LINE OF WALL / FLOOR BELOW
EXTERIOR GUARDRAIL: 42" MIN. ABOVE ADJACENT FINISHED FLOOR BALCONY FRAMING: REFER TO STRUCTURAL DWGS. W/
ELASTOMERIC DECK COATING OVER OVERFRAMING, SLOPE 1.5-2%
TO DRAIN OR EXTERIOR PER PLAN
WIRE SHELF & POLE: +66" A.F.F. @ TYP. UNITS
6' X 6' MINIMUM PRIVATE OPEN SPACE AT BALCONY
DRAINAGE VALLEY/CRICKET: SLOPE TO DRAIN
DRAIN: REF. PLUMBING DWGS
W/D DRAINAGE PAN: FOR DRAIN REF. PLUMBING DWGS
SOFFIT: REF. RCPS
DOOR SWING MANEUVERING CLEARANCE
SCALE: 1/4" = 1'-0"1 B2 UNIT PLAN
SCALE: 1/4" = 1'-0"2 B2 RCP
KEYNOTES
1,665 SF
UNIT QUANTITY: 3
UNIT ORIENTATION
211, 311 411 = STANDARD
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Sept. 29, 2026
Item #9 Page 45 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
C1 UNIT PLAN
A606
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
REF
DW
W/D
MICRO
FAU
TRSH
WINE
13'-3" 4'-1" 13'-1" 9'-11" 7'-4"
44'-5"
1/2"
15'-8" 5'-3"
1/2"
23'-5"
39'-6" 8'-2" 2'-0"
49'-8"
1/2" 1/2"
44'-4"
2'-11" 18'-0" 12'-1" 4'-8" 6'-8"
47'-8"
11'-7" 2'-6" 9'-4"
1'-6"
MIN
1'-6"
MIN
4'-8" 4'-8"
4'-0" 4'-2"
4'-6"8'-9"
8'-2" 7'-5" 3'-4" 4'-4"
4'-9" 5'-7" 1'-7" 5'-10" 5'-6"
4'-4" 4'-8" 4'-8" 4'-4"
6'-0" 5'-7"
9'-1" 4'-5" 9'-6"
3'-8" 3'-2 1/2" 4'-5" 8'-8"2'-6"
44'-5"
6'-1" 6'-0" 2'-2" 2'-6"
3'-10" 4'-4"
9/A702
F
10/A706
J
1/A707
K
D-01
D-14
D-18
D-02
D-08
D-02
D-06
D-03
D-06
D-06 D-02
D-03
D-03
W-01
W-01
W-02
W-09
W-03
W-03
W-02
06.11 07.19
10.08 01.10
09.04 07.08
07.04 05.16
06.03 06.27
BENCH
CL
CL
CL
CL
WS
P
DINING
FIN: A
KITCHEN
FIN: A
BEDROOM
FIN: A
BATH
FIN: B
LIVING
FIN: A
BEDROOM
FIN: A
DEN
FIN: A
FIN: A
FIN: A
BATH
FIN: B
J J
JJ
J
J
EQ. 6'-6" EQ. EQ. EQ. EQ. EQ. EQ. EQ. EQ.EQ.
EQ. EQ. EQ. EQ.
EQ. EQ.
EQ. EQ.
EQ. EQ. EQ. EQ.
EQ. EQ.
EQ. EQ.
EQ. EQ.
EQ. EQ.
EQ. EQ.
EQ. EQ.
EQ. EQ.
EQ. EQ.
EQ. EQ.
5'-2" 6'-0" 6'-0" EQ. EQ.
5'-1/2" 7'-0" 7'-0" 10'-0"7'-0"
EQ. EQ.
EQ. EQ.
EQ. EQ.7'-0"
EQ. 8'-0" EQ.
EQ. EQ.10'-0"
EQ. EQ.6'-0"
EQ. EQ.
EQ.EQ.
EQ EQ
EQ. EQ.
4'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
8'-0"
J
A890
11 A501
-
A891
2 A502
-
A503
-
A891
1 A891
3 A891
6 A891
14 A891
15 A891
18 GENERAL NOTES
1. 2. FOR 1 HOUR WALL AT BATHTUB / SHOWER
FOR ADDITIONAL INFORMATION ON
DOORS & WINDOW REFERENCES &
NOTES
3. DETAIL REFERENCES ARE CONSIDERED
"TYPICAL" (U.N.O.) AND ARE TO BE APPLIED TO
SIMILAR ITEMS WHETHER REFERENCED OR NOT.
SHOWER COMPARTMENTS AND BATHTUBS WITH
INSTALLED SHOWER HEADS SHALL BE FINISHED
WITH A NONABSORBENT SURFACE THAT
EXTENDS TO THE HEIGHT OF NOT LESS THAN 6
FEET ABOVE THE FLOOR.
4. FOR BATHTUB CLEARANCES AND GRAB
BAR BLOCKING LOCATIONS
FOR TOILET CLEARANCES AND GRAB BAR
BLOCKING LOCATIONS
5. 6.
FOR LAVATORY CLEARANCES AND
BATH ACCESSORY MOUNTING
HEIGHTS
FOR KITCHEN SINK CLEARANCES
8. 9.
7. FOR SHOWER CLEARANCES
TYPE FLOOR WALL
A
B
CEILING
-
-
-
-
-
-
-
-
-
-
-
-
INT. FINISH SCHEDULE
WALL LEGEND
2 HR 2X6 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X4 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X6 FIRE BARRIER W/ FIRE-RETARDANT
TREATED STUD
2 HR 2X6 FIRE BARRIER
2 HR 2X4 FIRE BARRIER
2 HR 2X6 WOOD STUD
2 HR 2X4 WOOD STUD
1 HR 2X6 WOOD STUD
1 HR 2X4 WOOD STUD
1 HR PARTY WALL (2) 2X6 WOOD STUD WALLS
W/ 2" GAP BETWEEN FRAMING
NON-RATED 2X6 STANDARD WOOD WALL
NON-RATED 2X4 STANDARD WOOD WALL
SOFFIT / FLOOR ABOVE
WALL LEGEND
CIP CONCRETE COLUMN PER STRUCTURAL
(REFERENCE SLAB PLANS FOR COLUMN SIZE)
12" CONCRETE WALL
8" CONCRETE WALL
8" CMU WALL
2 HR 6" METAL STUD
1 HR 6" METAL STUD
NON-RATED 6" METAL STUD
SOFFIT / FLOOR ABOVE
LED DOWNLIGHT
NOTE:
FOR LIGHT/FIXTURE SPECIFICATIONS, SWITCHING, AND
OTHER ELECTRICAL ITEMS REFER TO ELECTRICAL DWGS
WALL SCONCE CENTERED ON SINK
JUNCTION BOX
CEILING FAN
COMBINATION CARBON MONOXIDE/
SMOKE DETECTOR
SMOKE DETECTOR
EXHAUST FAN CENTERED ON TOILET
GYPSUM BOARD SOFFIT
J
RCP LEGEND
01.10 05.16
06.03 06.11
06.27 07.04
07.08 07.19
09.04 10.08
LINE OF WALL / FLOOR BELOW
EXTERIOR GUARDRAIL: 42" MIN. ABOVE ADJACENT FINISHED FLOOR BALCONY FRAMING: REFER TO STRUCTURAL DWGS. W/
ELASTOMERIC DECK COATING OVER OVERFRAMING, SLOPE 1.5-2%
TO DRAIN OR EXTERIOR PER PLAN
WIRE SHELF & POLE: +66" A.F.F. @ TYP. UNITS
6' X 6' MINIMUM PRIVATE OPEN SPACE AT BALCONY
DRAINAGE VALLEY/CRICKET: SLOPE TO DRAIN
DRAIN: REF. PLUMBING DWGS
W/D DRAINAGE PAN: FOR DRAIN REF. PLUMBING DWGS
SOFFIT: REF. RCPS
DOOR SWING MANEUVERING CLEARANCE
SCALE: 1/4" = 1'-0"1 C1 UNIT PLAN
SCALE: 1/4" = 1'-0"2 C1 RCP
KEYNOTES
1,956 SF
UNIT QUANTITY: 3
UNIT ORIENTATION
202, 302, 402 = STANDARD
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Sept. 29, 2026
Item #9 Page 46 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
C2 UNIT PLAN
A607
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
REF
DW
MICRO
FAU
W/D
TRSH
67'-6"
19'-10" 47'-8"
25'-9" 13'-9"
1/2"
39'-6"
50'-6" 17'-0"
9'-10" 29'-8"
39'-6"
1'-2"
2'-6" 2'-8"
11"
2'-11" 2'-6"
1'-0"
12'-8" 6'-2" 8'-6" 6'-10" 15'-0" 9'-11" 7'-5"
7'-6" 4'-6" 12'-9"
1'-0"
13'-9"
67'-6"
16'-8"
1'-6"
MIN
1'-6"
MIN
2'-2"2'-2" 2'-2"2'-2"
3'-4"3'-4" 6'-6"
2'-0" 3'-0"4'-1" 4'-8"
11'-2"
5'-1" 9'-6"
8"
5'-5" 5'-6" 4'-5"
3'-4" 6'-6" 6'-7" 6'-5" 3'-4"
6'-2"5'-9" 7'-3"
1'-0" 10" 13'-2" 6'-4" 26'-2"
10"
2'-2" 14'-6" 2'-6"
3'-9" 4'-10"
1'-3"
4'-4" 4'-4" 6'-4" 4'-4" 9'-4"
1'-0"
7'-6" 10'-2" 2'-4" 4'-0"
2'-2" 2'-4" 2'-7" 11'-2"
39'-6 1/2"
1/A703
G
11/A707
M6/A707
L
D-01
D-06
D-02
D-09
D-02
D-08
D-03
D-03
D-06
D-03
D-03
D-02
D-14
W-09
W-08
W-01
W-11 W-12 W-12 W-11 W-11 W-12
W-10
W-10
W-13 W-13
D-06
07.08 07.04
01.10 06.11
07.19 09.04
10.08 05.16
06.03 06.27
BENCH
LINEN
P
WS
DINING
FIN: A
KITCHEN
FIN: A
BEDROOM
FIN: A
BATH
FIN: B
LIVING
FIN: A
BEDROOM
FIN: A
FIN: A FIN: A
BEDROOM
FIN: A
FIN: B
BATH
FIN: B
A890
11 A501
-
A891
2 A502
-
A503
-
A891
1 A891
3 A891
6 A891
14 A891
15 A891
18 GENERAL NOTES
1. 2. FOR 1 HOUR WALL AT BATHTUB / SHOWER
FOR ADDITIONAL INFORMATION ON
DOORS & WINDOW REFERENCES &
NOTES
3. DETAIL REFERENCES ARE CONSIDERED
"TYPICAL" (U.N.O.) AND ARE TO BE APPLIED TO
SIMILAR ITEMS WHETHER REFERENCED OR NOT.
SHOWER COMPARTMENTS AND BATHTUBS WITH
INSTALLED SHOWER HEADS SHALL BE FINISHED
WITH A NONABSORBENT SURFACE THAT
EXTENDS TO THE HEIGHT OF NOT LESS THAN 6
FEET ABOVE THE FLOOR.
4. FOR BATHTUB CLEARANCES AND GRAB
BAR BLOCKING LOCATIONS
FOR TOILET CLEARANCES AND GRAB BAR
BLOCKING LOCATIONS
5. 6.
FOR LAVATORY CLEARANCES AND
BATH ACCESSORY MOUNTING
HEIGHTS
FOR KITCHEN SINK CLEARANCES
8. 9.
7. FOR SHOWER CLEARANCES
TYPE FLOOR WALL
A
B
CEILING
-
-
-
-
-
-
-
-
-
-
-
-
INT. FINISH SCHEDULE
WALL LEGEND
2 HR 2X6 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X4 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X6 FIRE BARRIER W/ FIRE-RETARDANT
TREATED STUD
2 HR 2X6 FIRE BARRIER
2 HR 2X4 FIRE BARRIER
2 HR 2X6 WOOD STUD
2 HR 2X4 WOOD STUD
1 HR 2X6 WOOD STUD
1 HR 2X4 WOOD STUD
1 HR PARTY WALL (2) 2X6 WOOD STUD WALLS
W/ 2" GAP BETWEEN FRAMING
NON-RATED 2X6 STANDARD WOOD WALL
NON-RATED 2X4 STANDARD WOOD WALL
SOFFIT / FLOOR ABOVE
WALL LEGEND
CIP CONCRETE COLUMN PER STRUCTURAL
(REFERENCE SLAB PLANS FOR COLUMN SIZE)
12" CONCRETE WALL
8" CONCRETE WALL
8" CMU WALL
2 HR 6" METAL STUD
1 HR 6" METAL STUD
NON-RATED 6" METAL STUD
SOFFIT / FLOOR ABOVE
LED DOWNLIGHT
NOTE:
FOR LIGHT/FIXTURE SPECIFICATIONS, SWITCHING, AND
OTHER ELECTRICAL ITEMS REFER TO ELECTRICAL DWGS
WALL SCONCE CENTERED ON SINK
JUNCTION BOX
CEILING FAN
COMBINATION CARBON MONOXIDE/
SMOKE DETECTOR
SMOKE DETECTOR
EXHAUST FAN CENTERED ON TOILET
GYPSUM BOARD SOFFIT
J
RCP LEGEND
REF
DW
MICRO
FAU
TRSH
67'-6"
17'-0"
1'-0"
50'-6"
1'-0"
47'-4" 2'-2"
11'-9" 2'-0"
13'-9"
10'-9" 3'-0"
28'-8"
1'-0"
W-14
07.08 07.04
05.16 06.03
06.27 P
WS
W-14
BENCH
01.10 05.16
06.03 06.11
06.27 07.04
07.08 07.19
09.04 10.08
LINE OF WALL / FLOOR BELOW
EXTERIOR GUARDRAIL: 42" MIN. ABOVE ADJACENT FINISHED FLOOR BALCONY FRAMING: REFER TO STRUCTURAL DWGS. W/
ELASTOMERIC DECK COATING OVER OVERFRAMING, SLOPE 1.5-2%
TO DRAIN OR EXTERIOR PER PLAN
WIRE SHELF & POLE: +66" A.F.F. @ TYP. UNITS
6' X 6' MINIMUM PRIVATE OPEN SPACE AT BALCONY
DRAINAGE VALLEY/CRICKET: SLOPE TO DRAIN
DRAIN: REF. PLUMBING DWGS
W/D DRAINAGE PAN: FOR DRAIN REF. PLUMBING DWGS
SOFFIT: REF. RCPS
DOOR SWING MANEUVERING CLEARANCE
SCALE: 1/4" = 1'-0"1 C2 UNIT PLAN
SCALE: 1/4" = 1'-0"3 C2.2 UNIT PLAN
SCALE: 1/4" = 1'-0"2 C2.1 UNIT PLAN
KEYNOTES
2,131 SF
UNIT QUANTITY: 1
UNIT ORIENTATION
201 = STANDARD
2,131 SF
UNIT QUANTITY: 1
UNIT ORIENTATION
401 = STANDARD
SEE 1/607 FOR ADDITIONAL DIMENSIONS AND CALLOUTS
2,131 SF
UNIT QUANTITY: 1
UNIT ORIENTATION
301 = STANDARD
SEE 1/607 FOR ADDITIONAL
DIMENSIONS AND CALLOUTS
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
Sept. 29, 2026
Item #9 Page 47 of 195
stamp
sheet
date
job no. project title
RINCON ROOSEVELT
2747 / 2775 / 2801 ROOSEVELT STREET - CARLSBAD, CA 92008 2317
sheet
D1 UNIT PLAN
Stephen Dalton Architects
444 S. CEDROS. STUDIO 190SOLANA BEACH. CA 92075
t: 858.792.5906 / f: 858.792.5916
LICENSED ARCHITECT
STEPHEN E. DALTON
STATE OF CAL I FORNIAO ONo. C25166
01/31/21
REF
W D
DW
FAU
MICRO
WINE
TRSH
16'-7" 4'-4" 5'-5" 2'-0" 5'-10" 2'-6" 11'-0"
23'-8" 17'-6" 5'-10" 12'-0"
59'-0"
6'-10 1/2" 5'-9 1/2" 50'-0"
52'-3"
1/2"
4'-7" 18'-2" 10'-5" 19'-1"
62'-8"
1/2"47'-8"
1'-6"
MIN
1'-6"
MIN
1'-6"
MIN
3'-6" 12'-1" 3'-6"
8'-4" 4'-3" 6'-9" 5'-1"
2'-4" 2'-3" 6'-5" 4'-8" 7'-1"
8'-0" 2'-2" 5'-7"8'-0"
7'-4" 7'-3"
7'-9 1/2" 4'-7" 6'-10" 5'-0" 4'-5"
6'-0" 6'-0"
3'-2" 1'-10"
4'-5" 8'-3" 5'-5"
2'-6" 12'-0"
7'-0"
47'-8 1/2"
1'-6"
MIN
1'-6"
MIN
9'-11" 9'-8" 6'-0" 12'-7" 11'-10"
7'-3" 2'-8" 4'-8" 5'-0"
52'-3 1/2"
5/A703
H
1/A708
N
6/A708
P
11/A708
Q
D-01
D-02
D-06
D-06
D-03
D-02
D-07
D-02
D-08
D-03
D-15
D-02
D-06
D-03
D-03
D-17
W-03
W-02
W-02
W-15
W-08
W-05 W-05
D-14 W-01
07.08 05.16
06.03 06.11
07.04 07.19
09.04 10.08
06.27 01.10
D-16
PANTRY
BENCH
LINEN
CL
CL
WS
DINING
FIN: A
KITCHEN
FIN: A
BEDROOM
FIN: A
BATH
FIN: B
LIVING
FIN: A
BEDROOM
FIN: A
BEDROOM
FIN: A
OFFICE
FIN: A
FIN: A
FIN: A FIN: B
FIN: A
BATH
FIN: B
BATH
FIN: B
A890
11 A501
-
A891
2 A502
-
A503
-
A891
1 A891
3 A891
6 A891
14 A891
15 A891
18 GENERAL NOTES
1. 2. FOR 1 HOUR WALL AT BATHTUB / SHOWER
FOR ADDITIONAL INFORMATION ON
DOORS & WINDOW REFERENCES &
NOTES
3. DETAIL REFERENCES ARE CONSIDERED
"TYPICAL" (U.N.O.) AND ARE TO BE APPLIED TO
SIMILAR ITEMS WHETHER REFERENCED OR NOT.
SHOWER COMPARTMENTS AND BATHTUBS WITH
INSTALLED SHOWER HEADS SHALL BE FINISHED
WITH A NONABSORBENT SURFACE THAT
EXTENDS TO THE HEIGHT OF NOT LESS THAN 6
FEET ABOVE THE FLOOR.
4. FOR BATHTUB CLEARANCES AND GRAB
BAR BLOCKING LOCATIONS
FOR TOILET CLEARANCES AND GRAB BAR
BLOCKING LOCATIONS
5. 6.
FOR LAVATORY CLEARANCES AND
BATH ACCESSORY MOUNTING
HEIGHTS
FOR KITCHEN SINK CLEARANCES
8. 9.
7. FOR SHOWER CLEARANCES
TYPE FLOOR WALL
A
B
CEILING
-
-
-
-
-
-
-
-
-
-
-
-
INT. FINISH SCHEDULE
WALL LEGEND
2 HR 2X6 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X4 FIRE-RETARDANT-TREATED WOOD STUD
2 HR 2X6 FIRE BARRIER W/ FIRE-RETARDANT
TREATED STUD
2 HR 2X6 FIRE BARRIER
2 HR 2X4 FIRE BARRIER
2 HR 2X6 WOOD STUD
2 HR 2X4 WOOD STUD
1 HR 2X6 WOOD STUD
1 HR 2X4 WOOD STUD
1 HR PARTY WALL (2) 2X6 WOOD STUD WALLS
W/ 2" GAP BETWEEN FRAMING
NON-RATED 2X6 STANDARD WOOD WALL
NON-RATED 2X4 STANDARD WOOD WALL
SOFFIT / FLOOR ABOVE
WALL LEGEND
CIP CONCRETE COLUMN PER STRUCTURAL
(REFERENCE SLAB PLANS FOR COLUMN SIZE)
12" CONCRETE WALL
8" CONCRETE WALL
8" CMU WALL
2 HR 6" METAL STUD
1 HR 6" METAL STUD
NON-RATED 6" METAL STUD
SOFFIT / FLOOR ABOVE
LED DOWNLIGHT
NOTE:
FOR LIGHT/FIXTURE SPECIFICATIONS, SWITCHING, AND
OTHER ELECTRICAL ITEMS REFER TO ELECTRICAL DWGS
WALL SCONCE CENTERED ON SINK
JUNCTION BOX
CEILING FAN
COMBINATION CARBON MONOXIDE/
SMOKE DETECTOR
SMOKE DETECTOR
EXHAUST FAN CENTERED ON TOILET
GYPSUM BOARD SOFFIT
J
RCP LEGEND
W-14
BENCH
6'-10 1/2" 5'-9 1/2" 50'-0"
27'-2" 4'-8" 6'-4" 3'-10" 6'-4" 1'-8"
BENCH
6'-8 1/2" 5'-9 1/2" 50'-0"
27'-2" 4'-8" 6'-4" 3'-10" 6'-4" 1'-8"
W-14
BENCH
01.10 05.16
06.03 06.11
06.27 07.04
07.08 07.19
09.04 10.08
LINE OF WALL / FLOOR BELOW
EXTERIOR GUARDRAIL: 42" MIN. ABOVE ADJACENT FINISHED FLOOR BALCONY FRAMING: REFER TO STRUCTURAL DWGS. W/
ELASTOMERIC DECK COATING OVER OVERFRAMING, SLOPE 1.5-2%
TO DRAIN OR EXTERIOR PER PLAN
WIRE SHELF & POLE: +66" A.F.F. @ TYP. UNITS
6' X 6' MINIMUM PRIVATE OPEN SPACE AT BALCONY
DRAINAGE VALLEY/CRICKET: SLOPE TO DRAIN
DRAIN: REF. PLUMBING DWGS
W/D DRAINAGE PAN: FOR DRAIN REF. PLUMBING DWGS
SOFFIT: REF. RCPS
DOOR SWING MANEUVERING CLEARANCE
SCALE: 1/4" = 1'-0"1 D1 UNIT PLAN
SCALE: 1/4" = 1'-0"2 D1.1 UNIT PLAN
SCALE: 1/4" = 1'-0"3 D1.2 UNIT PLAN
SCALE: 1/4" = 1'-0"4 D1.3 UNIT PLAN
KEYNOTES
2,586 SF
UNIT QUANTITY: 1
UNIT ORIENTATION
208 = STANDARD
SEE 1/609 FOR ADDITIONAL
DIMENSIONS AND CALLOUTS
2,586 SF
UNIT QUANTITY: 2
UNIT ORIENTATION
308 & 408 = STANDARD
2,586 SF
UNIT QUANTITY: 1
UNIT ORIENTATION
203 = MIRRORED
2,586 SF
UNIT QUANTITY: 2
UNIT ORIENTATION
303 & 403 = MIRRORED
SEE 1/609 FOR ADDITIONAL
DIMENSIONS AND CALLOUTS
SEE 1/609 FOR ADDITIONAL
DIMENSIONS AND CALLOUTS
07/16/26 - 100% SD
PLANNING DEPT SUB 08
02/03/26 - 100% SD
PLANNING DEPT SUB 07
11/17/25 - 100% SD
PLANNING DEPT SUB 06
A608
Sept. 29, 2026
Item #9 Page 48 of 195
XXXXXXXXXXXXXX
G G
EV CAPABLEEV CAPABLE
ADA VAN
EV CAPABLE
EV READY
EV READY EV READY
EV READY
EV READY EV READYEV READY EV READY
EV READY
ADA VAN
EV READY
W/ CHARGER
EV READY
W/ CHARGER
EV READY
W/ CHARGER
F F
S SS S
CC
W W
WM
W W
W W
W W
WM
WM
WM
X X X
X X X X X X X X
X
X
X
X
X
XXXXXXXXXXXX
X X X
X
X
X X X X X X X X X X X X X X X X X X X X X X XXXX
XXX X X X X X X X X X X X X X X X X X X
GGGGGGGGGGGGGGGGGGG
W
S
S
S
S
S
S
S
S
S
S
S
S
S
S
X X X X X X X X X X X X X X X XX X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X
W
S S S S S S S S
S
S S S S S
WW E
C
E
45 45
45 44
44 44
44 44
43 43
43 43
43 43
43 42
42 42
42 42
41 41
41 41
41 4040
40 1 STORY
BLDG
1 STORY
BLDG
2 STORY
BLDG
1 STORY
BLDG
STAIRS
ELECTRICAL
ROOM
LOBBY
TRASH
LOW
VOLTAGE
COMMERCIAL
#1
COMMERCIAL
#2
COMMERCIAL
#3
STORAGEBIKES
FR
TOTAL PARKING = 42 SPACES
ADA = 3 SPACES
EV = 16 SPACES
ELEV
STAIR 2
ELEV
EQ
ELEV
INVERT
STAIR 1
1ST FLOOR AREA: 23,065 SF
EV CAPABLEEV CAPABLE
ADA VAN
EV CAPABLE
EV READY
EV READY EV READY
EV READY
EV READY EV READYEV READY EV READY
EV READY
ADA VAN
EV READY
W/ CHARGER
EV READY
W/ CHARGER
EV READY
W/ CHARGER
42 41 40 39 38 37 36 35 34 33
32 31 30 29 28 27 26 25 24 23 22 21 20 19
18 17 16 15 14 13 12
4 5 6 7 8 9 10 11
3 2 1
PARCEL
ROOM
FULL HEIGHT
ENCLOSURE WALL
DOUBLE DETECTOR
CHECK VALVE
TRANSFORMER PAD
GAS
METERS
LINE OF FLOOR ABOVE
ACCESSIBLE PATH
GREASE SHAFT
MAILBOXES
VEHICULAR GATE
(VENTED)
INTERIOR
PARTITION WALL
INTERIOR
PARTITION WALL
SHORT
TERM BIKE
PARKING
AWNING ABOVEAWNING ABOVE AWNING
ABOVE AWNING ABOVE
LINE OF FLOOR ABOVE
EV SPACE PER
REQUIREMENT
CATEGORY
PLANE CHANGE
@ COMMERCIAL SPACES
CHUTES
ABOVE
NUMBERED PARKING
SPACES FOR REFERENCE
APN: 203-101-34-00
APN: 203-181-09-00
APN: 203-101-11-00
APN: 203-181-19-00
COMMERCIAL #3
FF = 43.0
COMMERCIAL #2
FF = 43.6
COMMERCIAL #1
FF = 44.0
LOBBYFF = 44.5
(2.2%) (2.0%)(1.3%)
(1.1%)
ELEC.FF = 45.0
TRASHFF = 43.5
FF = 43.0
FRFF =44.5
ELEV
STAIRS
ELEVEQUIP
STAIRSFF = 43.0
BIKE STORAGE
FF = 43.5
1.0%
1.0%
1.0%
STORAGEFF = 43.5
FG = 46.9
FG = 49.0
25.0'
11.5' SETBACK
6.1'
5.2'
7.2'
APN: 203-181-19-00
4.0'
5.0'
1.0' 0.5'
1.0'0.5'
4.3%
2.3%
4.0% 1.5%
1.5%
1.5%
2.0%
2.7%
1.5%
4.9%
2.5%
(0.3%)
2.0% 9.7%
ELEVINVERT
14.0' PKWY 22.0' TO TC
14 A
11.0' R/W
DEDICATION
11.0' R/W
DEDICATION
SUBJECTPROPERTY
COVERED PARKINGUNDER PODIUM
COVERED PARKINGUNDER PODIUM
COVERED PARKINGUNDER PODIUM
1.0%
1.5%
3.4%3.5%
4.5%
2.0%
APN: 203-101-16-00
2.0%
1.0% 1.0%
1.5% 1.5% 1.5%
42 41
40 43
44 7.1'
11.6'
8.6'
11.5'
0.9% 0.9%
5.0%
5.0%
5.0%
5.0%
5.0%
43 42 43 44
41 40
40 41 42
41 42
43 44
1.0%
1.8%
2.0%
1.0%
2.8%
3.3%
1.0%
4.5%
1.0%
3.1%
1.4%
1.7% 1.1%
0.9%
2.0%
1.0%
2.0% 2.0%2.0% 2.0%2.0%
11.5' SETBACK
5.0' SEWER
ESMT
0.9%
0.6%
3.0' R/W
DEDICATION
1.8%
0.9%
0.0%
2.0%
1.2%
24.0'
DRIVE AISLE 8.5'
0.5%
3.5%
27 5.0'5.0'
4.2'
ROOSEVELT ST
10 51020 0
SCALE: 1"=10'-0"
30 TWO WORKING DAYS BEFORE YOU DIG
Call:
Underground Service Alert
"CAUTION": Remember that the USA Center notifies
only those utilities belonging to the center. There
could be other utilities present at the work site. The
center will inform you of whom they will notify.
02-25
«
«
G:\23-PROJECTS\23-061-00\Landarch\Concept\23-061 Concept.dwg[23-061-00 Roosevelt Concept]Sep-19-2025:09:08 VKHHW
GaWH
MRE QR.
9 RINCON ROOSEVELT
23061
VKHHW
LANDSCAPE CONCEPT PLAN
GMP
3176 LIONSHEAD AVE.
CARLSBAD, CA 92010
t: 858-558-8977
09/12/25 - 100% SD
PLANNING DEPT SUB 05
PERMIT NUMBER / PERMIT NUMBER / PERMIT NUMBER
LANDSCAPE
ARCHITECTURE
& PLANNING
gmplandarch.com
T 858 558 8977
4010 Sorrento Valley Blvd.
Suite 200
San Diego, CA 92121
PLANTER AREA, TYP.
SITE LANDSCAPE PLAN
ENTRY DRIVE PER
CIVIL ENGINEER
BMP PLANTER 2, SEE
DETAIL A/LC-04
BMP PLANTER 3, SEE
DETAIL A/LC-04
SIDEWALK PER
CIVIL ENGINEER
+NOTE: A ROOT BARRIER SHALL BE OVER OR ADJACENT
TO ANY UNDERGROUND DRAIN LINES AS A MEANS OF
PROTECTION AGAINST ROOT INTRUSION. FINAL LOCATION
OF ROOT BARRIER(S) SHALL BE DETERMINED DURING
CONSTRUCTION
I AM FAMILIAR WITH THE REQUIREMENTS FOR LANDSCAPE AND IRRIGATION PLANS CONTAINED IN THE CITY OF CARLSBAD'S WATER EFFICIENT LANDSCAPE REGULATIONS. I UNDERSTAND THAT
CONSTRUCTION DRAWINGS ARE TO BE PREPARED IN COMPLIANCE WITH THOSE REGULATIONS AND THE LANDSCAPE MANUAL. I CERTIFY THAT THE PLANS WILL BE PREPARED IMPLEMENTING THOSE REGULATIONS TO PROVIDE EFFICIENT USE OF WATER.
05-10-24
NAMEDATE
GRAND AVE.
CARLSBAD BLVD.
INTERSTATE 5
VICINITY MAP (NTS)
PROJECT
SITE
CABLE RAIL FENCING
ATOP RETAINING WALL
B/LC-04
LC-01
DENOTES 2ND FLOOR AMENITY DECK
ENLARGEMENT - SEE SHEET LC-02
ROOSEVELT ST.
* SEE SHEET LC-02 FOR PLANT SCHEDULE *
IRRIGATION METER
AND BACKFLOW
ELEC. ROOM
NOTE: ALL LANDSCAPE AREAS SHALL
HAVE POSITIVE DRAINAGE (2% GRADE
IN PLANTING AREAS) AWAY FROM ALL
STRUCTURES AND TERMINATING IN
AN APPROVED DRAINAGE SYSTEM
50% OF SHRUBS (EXCEPT ON SLOPES
3:1 OR STEEPER) SHALL BE A MINIMUM
5 GALLON SIZE.
BMP PLANTER 1, SEE
DETAIL A/LC-04
STREET TREES SHALL BE LOCATED:
A MINIMUM OF SEVEN (7) FEET FROM ANY SEWER LINE.
B.IN AREAS THAT DO NOT CONFLICT WITH PUBLIC UTILITIES.
C.OUTSIDE OF SIGHT DISTANCE AREAS.
D.WITHIN THE STREET RIGHT-OF-WAY.
1. IRRIGATION CIRCUITS SHALL BE ORGANIZED INTO HYDROZONES.
2. ALL IRRIGATION SYSTEMS WILL BE PERMANENT AND SHALL UTILIZE SPRINKLER/ROTOR HEADS ON SLOPES, AND LOW PRECIPITATION RATE DRIP IN OTHER PLANTED AREAS.
3. CONTROLLER SHALL BE CAPABLE OF MULTIPLE PROGRAMMING AND SHALL BE CONNECTED TO A RAIN SHUT-OFF DEVICE.
4. THE OVERALL IRRIGATION SYSTEM SHALL BE DESIGNED WITH WATER EFFICIENCY AND
CONSERVATION IN MIND, THROUGH GOOD DESIGN, SPECIFICATION OF EFFICIENT MATERIALS, AND PROPER LANDSCAPE MAINTENANCE AND MANAGEMENT.
5. THE IRRIGATION SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH THE CITY OF CARLSBAD LANDSCAPE MANUAL.
6. ONLY SUBSURFACE IRRIGATION SHALL BE USED TO IRRIGATE PLANT MATERIAL WITHIN 24" OF AN
IMPERMEABLE SURFACE UNLESS THE ADJACENT IMPERMEABLE SURFACES ARE DESIGNED AND CONSTRUCTED TO DRAIN ENTIRELY INTO LANDSCAPED AREAS.
IRRIGATION NOTES
BMP TREE WELL PER
CIVIL ENGINEER
PLANTER AREA, TYP.
EXISTING 36" DBH
LOPHOSTEMON SPP. TO REMAIN
-SEE DETAIL C/LC-04 FOR TREE
PROTECTION FENCING
EXISTING 30" DBH
AFROCARPUS SPP. TO REMAIN
-SEE DETAIL C/LC-04 FOR TREE
PROTECTION FENCING
EXISTING 34" DBH
SCHINUS SPP. TO REMAIN
-SEE DETAIL C/LC-04 FOR TREE
PROTECTION FENCING
NOTE:ALL TREES TO REMAIN TO BE
PROTECTED IN PLACE AND TO
ADHERE TO ALL CITY OF CARLSBAD
PROTECTION STANDARDS. SEE
DETAIL C/LC-04 FOR TREE
PROTECTION FENCING
BIKE PARKING
CABLE RAIL FENCING
ATOP RETAINING WALL
B/LC-04
EXISTING PLANTING TO BE REMOVED
EXISTING PLANTING TO BE REMOVED
SEWER EASEMENT
SCREEN PLANTING TO
SOFTEN ARCHITECTURE
Sept. 29, 2026
Item #9 Page 49 of 195
ELEV
IDF
AMENITYCOURT
STAIR 2
STAIR 1
UNIT C2
UNIT C1
UNIT D1a
UNIT D1
UNIT B1
UNIT A1
UNIT A1
UNIT A3
UNIT B2
UNIT A2
UNIT A2
STO.
TR
GREASE SHAFT
6' x 6' MINIMUM PRIVATE OPEN
SPACE AT ALL BALCONIES
HORIZONTAL EXITW/ MAG-HOLD DOOR
LINE OF GROUND
FLOOR BELOW
FULL
HEIGHTSCREEN
LINE OF GROUND
FLOOR BELOW
SECOND FLOOR PLAN
SHRUBS
AGAVE AMERICANA / CENTURY PLANT5 GAL, L
AGAVE ATTENUATA / FOXTAIL AGAVE5 GAL, L
AGAVE VILMORINIANA / OCTOPUS AGAVE1 GAL, L
ALOE STRIATA / CORAL ALOE1 GAL, L
BOUTELOUA GRACILIS / BLUE GRAMA GRASS1 GAL, L
CALLISTEMON VIMINALIS 'LITTLE JOHN' / LITTLE JOHN WEEPING BOTTLEBRUSH5 GAL, L CUPRESSUS SEMPERVIRENS 'MONSHEL' / TINY TOWER ITALIAN CYPRESS15 GAL, L DIETES BICOLOR / FORTNIGHT LILY5 GAL, L
DODONAEA VISCOSA 'PURPUREA' / PURPLE HOPSEED BUSH5 GAL, L LANTANA X 'NEW GOLD' / NEW GOLD LANTANA5 GAL, L
LAVANDULA DENTATA 'PARIS BLUE' / PARIS BLUE FRENCH LAVENDER5 GAL, L LEUCOPHYLLUM FRUTESCENS 'COMPACTA' / COMPACT TEXAS SAGE5 GAL, L LIGUSTRUM JAPONICUM 'TEXANUM' / TEXAS JAPANESE PRIVET5 GAL, M MUHLENBERGIA CAPILLARIS / PINK MUHLY GRASS5 GAL, L
MUHLENBERGIA RIGENS / DEER GRASS5 GAL, L
PHORMIUM TENAX / NEW ZEALAND FLAX5 GAL, L
PITTOSPORUM TENUIFOLIUM ' SILVER SHEEN' / SILVER SHEEN KOHUHU15 GAL, L RHAPHIOLEPIS INDICA 'SPRINGTIME' TM / SPRINGTIME INDIAN HAWTHORN5 GAL, L ROSA X 'NOZOMI' / NOZOMI MINIATURE CLIMBING ROSE5 GAL, M ROSMARINUS OFFICINALIS 'PROSTRATUS' / DWARF ROSEMARY5 GAL, L SALVIA LEUCANTHA / MEXICAN BUSH SAGE5 GAL, L
WESTRINGIA FRUTICOSA / COAST ROSEMARY5 GAL, L
GROUNDCOVER
BACCHARIS PILULARIS 'PIGEON POINT' / PIGEON POINT COYOTE BRUSHFLAT, 24" O.C.
SENECIO MANDRALISCAE 'BLUE CHALK STICKS' / SENECIOFLAT, 24" O.C.
BASIN GROUNDCOVER
JUNCAS PATENS / CALIFORNIA GREY RUSHLINERS @ 24" O.C., L SHRUBS
AGAVE AMERICANA / CENTURY PLANT5 GAL, L
AGAVE ATTENUATA / FOXTAIL AGAVE5 GAL, L
AGAVE VILMORINIANA / OCTOPUS AGAVE1 GAL, L
ALOE STRIATA / CORAL ALOE1 GAL, L
BOUTELOUA GRACILIS / BLUE GRAMA GRASS1 GAL, L
CALLISTEMON VIMINALIS 'LITTLE JOHN' / LITTLE JOHN WEEPING BOTTLEBRUSH5 GAL, L CUPRESSUS SEMPERVIRENS 'MONSHEL' / TINY TOWER ITALIAN CYPRESS15 GAL, L DIETES BICOLOR / FORTNIGHT LILY5 GAL, L
DODONAEA VISCOSA 'PURPUREA' / PURPLE HOPSEED BUSH5 GAL, L LANTANA X 'NEW GOLD' / NEW GOLD LANTANA5 GAL, L
LAVANDULA DENTATA 'PARIS BLUE' / PARIS BLUE FRENCH LAVENDER5 GAL, L LEUCOPHYLLUM FRUTESCENS 'COMPACTA' / COMPACT TEXAS SAGE5 GAL, L LIGUSTRUM JAPONICUM 'TEXANUM' / TEXAS JAPANESE PRIVET5 GAL, M MUHLENBERGIA CAPILLARIS / PINK MUHLY GRASS5 GAL, L
MUHLENBERGIA RIGENS / DEER GRASS5 GAL, L
PHORMIUM TENAX / NEW ZEALAND FLAX5 GAL, L
PITTOSPORUM TENUIFOLIUM ' SILVER SHEEN' / SILVER SHEEN KOHUHU15 GAL, L RHAPHIOLEPIS INDICA 'SPRINGTIME' TM / SPRINGTIME INDIAN HAWTHORN5 GAL, L ROSA X 'NOZOMI' / NOZOMI MINIATURE CLIMBING ROSE5 GAL, M ROSMARINUS OFFICINALIS 'PROSTRATUS' / DWARF ROSEMARY5 GAL, L SALVIA LEUCANTHA / MEXICAN BUSH SAGE5 GAL, L
WESTRINGIA FRUTICOSA / COAST ROSEMARY5 GAL, L
GROUNDCOVER
BACCHARIS PILULARIS 'PIGEON POINT' / PIGEON POINT COYOTE BRUSHFLAT, 24" O.C.
SENECIO MANDRALISCAE 'BLUE CHALK STICKS' / SENECIOFLAT, 24" O.C.
BASIN GROUNDCOVER
JUNCAS PATENS / CALIFORNIA GREY RUSHLINERS @ 24" O.C., L
INDICATES LARGE SHRUB
INDICATES MEDIUM SHRUB
INDICATES SMALL SHRUB
SHRUB CATEGORIES
*
INDICATES BMP SHRUBS
*
*
*
INDICATES SCREENING SHRUBS+
+
+
SITE TREES
7 LOPHOSTEMON CONFERTUS / BRISBANE BOX24" BOX, M
MAGNOLIA GRANDIFLORA / SOUTHERN MAGNOLIA24" BOX, M
OLEA EUROPAEA `SWAN HILL` / SWAN HILL OLIVE24"BOX, L
BMP TREES
2 ARBUTUS X 'MARINA' / MARINA STRAWBERRY TREE STANDARD24" BOX, L CERCIS OCCIDENTALIS / WESTERN REDBUD24" BOX, L
STREET TREES
2 MAGNOLIA GRANDIFLORA 'LITTLE GEM' / LITTLE GEM MAGNOLIA * BMP SELECTION24" BOX, L PISTACIA CHINENSIS / CHINESE PISTACHE24"BOX, M
CONCEPT PLANT SCHEDULECONCEPT PLANT SCHEDULE
10 51020 0
SCALE: 1"=10'-0"
30 TWO WORKING DAYS BEFORE YOU DIG
Call:
Underground Service Alert
"CAUTION": Remember that the USA Center notifies
only those utilities belonging to the center. There
could be other utilities present at the work site. The
center will inform you of whom they will notify.
02-25
«
«
G:\23-PROJECTS\23-061-00\Landarch\Concept\23-061 Concept.dwg[23-061-00 Roosevelt Concept]Sep-19-2025:09:08 VKHHW
GaWH
MRE QR.
9 RINCON ROOSEVELT
23061
VKHHW
LANDSCAPE CONCEPT PLAN
GMP
3176 LIONSHEAD AVE.
CARLSBAD, CA 92010
t: 858-558-8977
09/12/25 - 100% SD
PLANNING DEPT SUB 05
PERMIT NUMBER / PERMIT NUMBER / PERMIT NUMBER
LANDSCAPE
ARCHITECTURE
& PLANNING
gmplandarch.com
T 858 558 8977
4010 Sorrento Valley Blvd.
Suite 200
San Diego, CA 92121
BBQ COUNTER
WITH DINING AND
LOUNGE AREA
TURF FLEX SPACE AREA
2ND FLOOR AMENITY DECKLC-02
BMP PLANTER #4, SEE
DETAIL A/LC-04
LOW MODULAR
SELF-WATERING
PLANTER, TYP.
1. MAINTENANCE WITHIN THE RIGHT OF WAY SHALL BE MAINTAINED BY THE PROPERTY OWNER FOR THE FIRST 12 MONTHS ONCE
THIS PERIOD HAS BEEN COMPLETED AND THE TREES ARE IN
HEALTHY CONDITION, THE CITY WILL ASSUME MAINTENANCE.
2. ALL ON-SITE LANDSCAPING SHALL BE MAINTAINED BY THE
PROPERTY OWNER.
3. BMP PLANTERS IN RIGHT OF WAY TO BE MAINTAINED BY OWNER
MAINTENANCE NOTES
NOTES:
+ A ROOT BARRIER SHALL BE OVER OR ADJACENT TO
ANY UNDERGROUND DRAIN LINES AS A MEANS OF
PROTECTION AGAINST ROOT INTRUSION. FINAL
LOCATION OF ROOT BARRIER(S) SHALL BE DETERMINED
DURING CONSTRUCTION
+ ALL UTILITIES ARE TO BE SCREENED
NOTE:
STREET TREES SHALL BE LOCATED: A.
A MINIMUM OF SEVEN (7) FEET FROM ANY SEWER LINE.
B.IN AREAS THAT DO NOT CONFLICT WITH PUBLIC UTILITIES.
C.OUTSIDE OF SIGHT DISTANCE AREAS.
D.WITHIN THE STREET RIGHT-OF-WAY.
NOTE:
PER THE LANDSCAPE MANUAL 50% OF THE SHRUBS (EXCEPT
ON SLOPES 3:1 OR STEEPER) SHALL BE A MINIMUM 5-GALLON
SIZE.
NOTE:
PLANTING WILL INCLUDE LARGE SHRUBS AND/OR SMALL
TREES TO HELP SCREEN AND SOFTEN THE BUILDING.
BMP PLANTER #5, SEE
DETAIL A/LC-04
Sept. 29, 2026
Item #9 Page 50 of 195
XXXXXXXXXXXXX
X
G G
EV CAPABLEEV CAPABLE
EV READY
EV READY EV READY
EV READY
EV READY EV READYEV READY EV READY
EV READY
ADA VAN
EV READY
W/ CHARGER
EV READY
W/ CHARGER
EV READY
W/ CHARGER
F F
S SS S
CC
W W
WV
WM
W W
W W
W W
WM
WM
WM
WW
W
WW
W
WW
W
X X
X
X
X
XXXXXXXXXXXXXX
XXXXXXXXXXXXX
X X X X X X X X X
GGGGGGGGGGGGGGGGG
W
S S
S
S
S
S S S S
S
S
X X X X X X X X X X X X X X X XX X
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X W
S S S S
S
S S S S S S S S
W
W
W
WW
W
W
W
WW
W
W
W
E
C
45 45
44 44
43 43
43 41
41 41
4040
40 40
40 40
40 39
1 STORY
BLDG
ELEV
AMENITYCOURT
STAIR 1
UNIT A3
TR
GREASE SHAFT
DENOTES 2ND FLOOR
AMENITY DECK
ROOSEVELT ST
XXXXXXXXXXXXX
X
G G
EV CAPABLEEV CAPABLE
EV READY
EV READY EV READY
EV READY
EV READY EV READYEV READY EV READY
EV READY
ADA VAN
EV READY
W/ CHARGER
EV READY
W/ CHARGER
EV READY
W/ CHARGER
F F
S SS S
CC
W W
WV
WM
W W
W W
W W
WM
WM
WM
WW
W
WW
W
WW
W
X X
X
X
X
XXXXXXXXXXXXXX
XXXXXXXXXXXXX
X X X X X X X X X
GGGGGGGGGGGGGGGGG
W
S S
S
S
S
S S S S
S
S
X X X X X X X X X X X X X X X XX X
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X W
S S S S
S
S S S S S S S S
W
W
W
WW
W
W
W
WW
W
W
W
E
C
45 45
44 44
43 43
43 41
41 41
4040
40 40
40 40
40 39
1 STORY
BLDG
ELEV
AMENITYCOURT
STAIR 1
UNIT A3
TR
GREASE SHAFT
DENOTES 2ND FLOOR
AMENITY DECK
ROOSEVELT ST
XXXXXXXXXXXXX
X
G G
EV CAPABLEEV CAPABLE
EV READY
EV READY EV READY
EV READY
EV READY EV READYEV READY EV READY
EV READY
ADA VAN
EV READY
W/ CHARGER
EV READY
W/ CHARGER
EV READY
W/ CHARGER
F F
S SS S
CC
W W
WV
WM
W W
W W
W W
WM
WM
WM
WW
W
WW
W
WW
W
X X
X
X
X
XXXXXXXXXXXXXX
XXXXXXXXXXXXX
X X X X X X X X X
GGGGGGGGGGGGGGGGG
W
S S
S
S
S
S S S S
S
S
X X X X X X X X X X X X X X X XX X
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X W
S S S S
S
S S S S S S S S
W
W
W
WW
W
W
W
WW
W
W
W
E
C
45 45
44 44
43 43
43 41
41 41
4040
40 40
40 40
40 39
1 STORY
BLDG
ELEV
AMENITYCOURT
STAIR 1
UNIT A3
TR
GREASE SHAFT
DENOTES 2ND FLOOR
AMENITY DECK
ROOSEVELT ST
MAINTENANCE EXHIBITWATER USE PLAN WATER CONSERVATION PLAN LANDSCAPED AREAS TO BE MAINTAINED BY HOA.POTABLE WATER USE NOTE: NO AREAS SHALL UTILIZE RECYCLED OR
GREY WATER OF ANY KIND ON SITE.
MODERATE WATER USE - 722 S.F.
LOW WATER USE - 4,300 S.F.
NOTE: ONLY LOW VOLUME OR SUBSURFACE IRRIGATION SHALL
BE USED TO IRRIGATE ANY VEGETATION WITHIN 24" OF AN
IMPERMEABLE SURFACE UNLESS THE ADJACENT IMPERMEABLE
SURFACES ARE DESIGNED AND CONSTRUCTED TO TO CAUSE
WATER TO DRAIN ENTIRELY INTO A LANDSCAPED AREA.
ALL LANDSCAPE AREAS ARE PLANTED WITH EXCLUSIVELY LOW AND MODERATE WATER USE PLANT MATERIAL AND THEREFORE CONSIDERED OF THE SAME HYDROZONE. IRRIGATION CIRCUITS WILL BE DESIGNED ACCORDINGLY AS WELL AS BEING SEPARATED BY SOLAR ORIENTATION. NO TURF AREAS ARE PROPOSED ++NOTE:
(1). 15 GAL. TREE SHALL BE PROVIDED PER 500 S.F. OF SLOPE GREATER THAN 5' VERTICAL AND (1) 15 GAL.
TREE PER 500 S.F. PLUS (1) ADDITIONAL 5 GAL. TREE PER 1000 S.F. FOR SLOPES GREATER THAN 8' VERTICAL. (2). ALL TREES WITH 10' OF ANY WALK, CURB, DRIVE, BUILDING, UTILITY OR HARDSCAPE ELEMENT SHALL RECEIVE 10' OF 48" DEEP ROOT BARRIER UNLESS OTHERWISE INDICATED ON THE PLANS. (3). ALL SHRUB AREAS SHALL RECIEVE 3" LAYER OF BARK MULCH EXCLUDING SLOPES 3:1 AND STEEPER HYDROZONE NOTE:
10 51020 0
SCALE: 1"=10'-0"
30 TWO WORKING DAYS BEFORE YOU DIG
Call:
Underground Service Alert
"CAUTION": Remember that the USA Center notifies
only those utilities belonging to the center. There
could be other utilities present at the work site. The
center will inform you of whom they will notify.
02-25
«
«
G:\23-PROJECTS\23-061-00\Landarch\Concept\23-061 Concept.dwg[23-061-00 Roosevelt Concept]Sep-19-2025:09:08 VKHHW
GaWH
MRE QR.
9 RINCON ROOSEVELT
23061
VKHHW
LANDSCAPE CONCEPT PLAN
GMP
3176 LIONSHEAD AVE.
CARLSBAD, CA 92010
t: 858-558-8977
09/12/25 - 100% SD
PLANNING DEPT SUB 05
PERMIT NUMBER / PERMIT NUMBER / PERMIT NUMBER
LANDSCAPE
ARCHITECTURE
& PLANNING
gmplandarch.com
T 858 558 8977
4010 Sorrento Valley Blvd.
Suite 200
San Diego, CA 92121
LC-03
NTSNTSNTS
TREES TO BE MAINTENANCE TO BE ASSUMED BY CITY AFTER 12
MONTH PERIOD - TO EXCLUDE BMP TREE PLANTER
Sept. 29, 2026
Item #9 Page 51 of 195
TWO WORKING DAYS BEFORE YOU DIG
Call:
Underground Service Alert
"CAUTION": Remember that the USA Center notifies
only those utilities belonging to the center. There
could be other utilities present at the work site. The
center will inform you of whom they will notify.
02-25
«
«
G:\23-PROJECTS\23-061-00\Landarch\Concept\23-061 Concept.dwg[23-061-00 Roosevelt Concept]Sep-19-2025:09:08 VKHHW
GaWH
MRE QR.
9 RINCON ROOSEVELT
23061
VKHHW
LANDSCAPE CONCEPT PLAN
GMP
3176 LIONSHEAD AVE.
CARLSBAD, CA 92010
t: 858-558-8977
09/12/25 - 100% SD
PLANNING DEPT SUB 05
PERMIT NUMBER / PERMIT NUMBER / PERMIT NUMBER
LANDSCAPE
ARCHITECTURE
& PLANNING
gmplandarch.com
T 858 558 8977
4010 Sorrento Valley Blvd.
Suite 200
San Diego, CA 92121
= (40)(.62)[(.55 X 5,022) + (.45 X SLA)]
= (24.8)(2,762.1)
= 68,500
75,350
40 24.8
.3.5
4,300 125
1,46967.5
.8.75
1,837 90
2,301
57,065
B
FOR REFERENCE ONLY - SEE CIVIL ENGINEER PLANS
LC-04
PLANTING CONCEPT:
1. ALL PLANTING AND IRRIGATION DESIGN SHALL BE IN CONFORMANCE WITH THE CITY OF CARLSBAD LANDSCAPE MANUAL.
2. ALL LANDSCAPING SHALL BE DEVELOPED IN CONFORMANCE WITH ALL STANDARDS SET FORTH BY THE CITY OF CARLSBAD LAND DEVELOPMENT CODE, CITY OF CARLSBAD LANDSCAPE REGULATIONS AND ALL OTHER STANDARDS FOR LANDSCAPE INSTALLATION.
3. EXISTING QUALITY TREES AND PALMS SHALL BE SALVAGED WHENEVER FEASIBLE.
4. ALL STREET TREES SHALL BE LOCATED OUTSIDE ALL UTILITY, GAS, AND WATER EASEMENTS, UNLESS OTHERWISE APPROVED BY A CITY OF CARLSBAD UTILITY AGENCY.
5. ANY TREES WITHIN 5' FROM PAVING SHALL RECEIVE ROOT BARRIERS IN ACCORDANCE WITH CITY OF CARLSBAD GUIDELINES.
6. SLOPES REQUIRING EROSION CONTROL MEASURES AS SPECIFIED HEREIN SHALL BE TREATED WITH ONE OR MORE OF THE FOLLOWING PLANTING STANDARDS:
A. STANDARD #1 - COVER CROPS/REINFORCED STRAW MAT
COVER CROP SHALL BE A SEED MIX TYPICALLY MADE UP OF QUICK GERMINATING AND FAST COVERING GRASSES, CLOVERS, AND /OR WILD FLOWERS. SUBMIT THE SPECIFIC SEED MIX FOR CITY APPROVAL PRIOR TO APPLICATION. THE COVER CROP SHALL BE APPLIED AT A RATE AND MANNER SUFFICIENT TO PROVIDE 90% COVERAGE WITHIN THIRTY (30) DAYS. TYPE OF
REINFORCED STRAW MAT SHALL BE AS APPROVED BY THE CITY AND STAKED TO THE SLOPE AS RECOMMENDED BY THE MANUFACTURER. REINFORCED STRAW MAT SHALL BE REQUIRED WHEN PLANTING OCCURS BETWEEN AUGUST 15 AND APRIL 15.
DURING THE REMAINDER OF THE YEAR, THE COVER CROP AND/OR REINFORCED STRAW MAT MAY BE USED.
B. STANDARD #2 - GROUND COVER
ONE HUNDRED (100%) PERCENT OF THE AREA SHALL BE PLANTED WITH A GROUND COVER KNOWN TO HAVE EXCELLENT SOIL
BINDING CHARACTERISTIC (PLANTED FROM A MINIMUM SIZE OF FLATTED MATERIAL AND SPACED TO PROVIDE FULL COVERAGE WITHIN ONE YEAR).
C. STANDARD #3 - LOW SHRUBS
LOW SPREADING WOODY SHRUBS (PLANTED FROM A MINIMUM OF 1 GALLON CONTAINERS) SHALL COVER A MINIMUM OF SEVENTY (70%) PERCENT OF THE SLOPE FACE (AT MATURE SIZE).
D. STANDARD #4 - TREES AND/OR LARGE SHRUBS
TREES AND/OR LARGE SHRUBS SHALL BE (PLANTED FROM A MINIMUM OF 1 GALLON CONTAINERS) AT A MINIMUM RATE OF ONE (1) PLANT PER TWO HUNDRED (200) SQUARE FEET.
E. AREAS OF APPLICATION (PLANTING)
SLOPES - 6:1 OR STEEPER AND:
I. 3 FEET OR LESS IN VERTICAL HEIGHT AND ARE ADJACENT TO PUBLIC WALKS OR STREETS REQUIRE AT MINIMUM STANDARD #1.
II. 3 FEET TO 8 FEET IN VERTICAL HEIGHT REQUIRE STANDARDS #1 (EROSION CONTROL MATTING SHALL BE INSTALLED IN LIEU OF A COVER CROP), #2 AND #3.
III. IN EXCESS OF 8 FEET IN VERTICAL HEIGHT REQUIRE STANDARDS #1(EROSION CONTROL MATTING SHALL BE INSTALLED IN LIEU OF A COVER CROP), #2, #3 AND #4.
SPECIAL CONDITIONS
AREAS GRADED FLATTER THAN 6:1 REQUIRE STANDARD #1 (EROSION CONTROL MATTING) WHEN THEY HAVE ONE OR MORE OF THE FOLLOWING CONDITIONS:
F. SHEET GRADED PADS NOT SCHEDULED FOR IMPROVEMENTS WITHIN 6 MONTHS OF COMPLETION OF ROUGH GRADING.
II. A POTENTIAL EROSION PROBLEM AS DETERMINED BY THE CITY.
III. IDENTIFIED BY THE CITY AS HIGHLY VISIBLE AREAS TO THE PUBLIC OR HAVE SPECIAL CONDITIONS THAT WARRANT IMMEDIATE TREATMENT.
7. ALL PLANT MATERIAL SELECTED FOR USE WILL BE OF A TYPE KNOWN TO BE SUCCESSFUL IN THE AREA OR IN SIMILAR CLIMATIC AND SOIL CONDITIONS.
8. COLOR FROM PLANT FOLIAGE, BARK AND FLOWERS WILL BE UTILIZED IN DEVELOPING A WARM, FRIENDLY AND VISUALLY APPEALING PROJECT IDENTITY IN CONFORMANCE WITH THE CITY OF CARLSBAD LANDSCAPE MANUAL.
9. PRIMARY VEHICULAR ENTRANCES WILL BE IDENTIFIED AND ACCENTED WITH SPECIAL GROUPINGS OF TREES, PALMS, FLOWERING SHRUBS, GROUNDCOVERS, SIGNAGE, LIGHTING, AND DECORATIVE PAVING.
10. LANDSCAPE FINISH GRADING OBJECTIVES WILL INCLUDE POSITIVE SURFACE DRAINAGE OF PLANTED AREAS AND "HARDSCAPE" AWAY FROM ALL STRUCTURES, TERMINATING IN AN APPROVED DRAINAGE SYSTEM.
11. ALL SOILS WILL BE AMENDED AND TILLED TO CONFORM TO RECOMMENDATIONS MADE BY A SOILS TESTING LABORATORY TO PROMOTE HEALTHY AND VIGOROUS PLANT GROWTH.
12. ALL PLANTING AREAS WILL BE MAINTAINED IN A WEED AND DEBRIS FREE CONDITION.
13. ALL AREAS SHALL BE MAINTAINED FREE OF DEBRIS AND LITTER AND ALL PLANT MATERIAL SHALL BE MAINTAINED IN A HEALTHY GROWING CONDITION. DISEASED OR DEAD PLANT MATERIAL SHALL BE SATISFACTORILY TREATED OR REPLACED WITHIN 30 DAYS WITH MATERIAL OF EQUAL KIND AND SIZE.
14. ALL SHRUB AREAS SHALL RECEIVE 3" FIRBARK MULCH.
15. ALL TREES SHALL BE STAKED IN ACCORDANCE WITH THE CITY OF CARLSBAD LANDSCAPE MANUAL.
CONCEPTUAL LANDSCAPE DEVELOPMENT NOTES:
CROWN DRIP LINE
4'-0"
MAINTAIN EXISTING GRADE WITH
THE TREE PROTECTION FENCE
UNLESS OTHERWISE INDICATED
ON THE PLANS.
2" X 6' STEEL POSTS OR
APPROVED EQUAL.
5" THICK LAYER OF MULCH.
NOTES:
1- SEE SPECIFICATIONS FOR ADDITIONAL TREE
PROTECTION REQUIREMENTS.
2- IF THERE IS NO EXISTING IRRIGATION, SEE
SPECIFICATIONS FOR WATERING
REQUIREMENTS.
3- NO PRUNING SHALL BE PERFORMED EXCEPT
BY APPROVED ARBORIST.
4- NO EQUIPMENT SHALL OPERATE INSIDE THE
PROTECTIVE FENCING INCLUDING DURING
FENCE
INSTALLATION AND REMOVAL.
SECTION VIEW
KEEP OUT
TREE PROTECTION
AREA
8.5" X 11" SIGN
LAMINATED IN
PLASTIC SPACED
EVERY 50' ALONG
THE FENCE.
TO ADHERE TO ALL CITY OF
CARLSBAD STANDARDS
TREE PROTECTION FENCE: HIGH
DENSITY POLYETHYLENE FENCING
WITH 3.5" X 1.5" OPENINGS;
COLOR- ORANGE. STEEL POSTS
INSTALLED AT 8' O.C.
TREE PROTECTION
3/16" = 1'-0"C
.5
597
298.5
.8
374
CABLE GUARDRAIL ATOP RETAINING WALL
GALVANIZED STEEL
ROUND END POST WITH
CABLE ENDERD
GALVANIZED STEEL
SQUARE POST WITH
CABLE HOLDERS
GALVANIZED STEEL CABLE
TENSIONER ADJUSTABLE
GALVANIZED STEEL CABLE
WIRE ROPE
RETAINING WALL PER
CIVIL ENGINEER'S PLANS
A
Sept. 29, 2026
Item #9 Page 52 of 195
XXXXXXXXXXXXXX
G G
F F
S SS S
CC
W W
WM
W W
W W
W W
WM
WM
WM
X X X
X X X X X X X X
X
X
X
X
X
XXXXXXXXXXXX
X X X
X
X
X X X X X X X X X X X X X X X X X X X X X X XXXX
XXX X X X X X X X X X X X X X X X X X X
GGGGGGGGGGGGGGGGGGG
W
S
S
S
S
S
S
S
S
S
S
S
S
S
S
X X X X X X X X X X X X X X X XX X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X
W
S S S S S S S S
S
S S S S S
WW E
C
E
45 45
45 44
44 44
44 44
43 43
43 43
43 43
43 42
42 42
42 42
41 41
41 41
41 4040
40 1 STORY
BLDG
1 STORY
BLDG
2 STORY
BLDG
1 STORY
BLDG
STAIRS
4' 8' 16'0
ELECTRICAL
ROOM
LOBBY
TRASH
LOW
VOLTAGE
COMMERCIAL
#1
COMMERCIAL
#2
COMMERCIAL
#3
STORAGEBIKES
FR
TOTAL PARKING = 42 SPACES
ADA = 3 SPACES
EV = 16 SPACES
ELEV
STAIR 2
ELEV
EQ
ELEV
INVERT
STAIR 1
1ST FLOOR AREA: 23,065 SF
EV CAPABLEEV CAPABLE
ADA VAN
EV CAPABLE
EV READY
EV READY EV READY
EV READY
EV READY EV READYEV READY EV READY
EV READY
ADA VAN
EV READY
W/ CHARGER
EV READY
W/ CHARGER
EV READY
W/ CHARGER
42 41 40 39 38 37 36 35 34 33
32 31 30 29 28 27 26 25 24 23 22 21 20 19
18 17 16 15 14 13 12
4 5 6 7 8 9 10 11
3 2 1
N
PARCEL
ROOM
FULL HEIGHT
ENCLOSURE WALL
DOUBLE DETECTOR
CHECK VALVE
TRANSFORMER PAD
GAS
METERS
LINE OF FLOOR ABOVE
ACCESSIBLE PATH
GREASE SHAFT
MAILBOXES
VEHICULAR GATE
(VENTED)
INTERIOR
PARTITION WALL
INTERIOR
PARTITION WALL
SHORT
TERM BIKE
PARKING
AWNING ABOVEAWNING ABOVE AWNING
ABOVE AWNING ABOVE
LINE OF FLOOR ABOVE
EV SPACE PER
REQUIREMENT
CATEGORY
PLANE CHANGE
@ COMMERCIAL SPACES
CHUTES
ABOVE
NUMBERED PARKING
SPACES FOR REFERENCE
APN: 203-101-34-00
APN: 203-181-09-00
APN: 203-101-11-00
APN: 203-181-19-00
COMMERCIAL #3
FF = 43.0
COMMERCIAL #2
FF = 43.6
COMMERCIAL #1
FF = 44.0
LOBBYFF = 44.5
(2.2%) (2.0%)(1.3%)
(1.1%)
ELEC.FF = 45.0
TRASHFF = 43.5
FF = 43.0
FRFF =44.5
ELEV
STAIRS
ELEVEQUIP
STAIRSFF = 43.0
BIKE STORAGE
FF = 43.5
1.0%
1.0%
1.0%
STORAGEFF = 43.5
FG = 46.9
FG = 49.0
25.0'
11.5' SETBACK
6.1'
5.2'
7.2'
APN: 203-181-19-00
4.0'
5.0'
1.0' 0.5'
1.0'0.5'
4.3%
2.3%
4.0% 1.5%
1.5%
1.5%
2.0%
2.7%
1.5%
4.9%
2.5%
(0.3%)
2.0% 9.7%
ELEVINVERT
14.0' PKWY 22.0' TO TC
14 A
11.0' R/W
DEDICATION
11.0' R/W
DEDICATION
SUBJECTPROPERTY
COVERED PARKINGUNDER PODIUM
COVERED PARKINGUNDER PODIUM
COVERED PARKINGUNDER PODIUM
1.0%
1.5%
3.4%3.5%
4.5%
2.0%
APN: 203-101-16-00
2.0%
1.0% 1.0%
1.5% 1.5% 1.5%
42 41
40 43
44 7.1'
11.6'
8.6'
11.5'
0.9% 0.9%
5.0%
5.0%
5.0%
5.0%
5.0%
43 42 43 44
41 40
40 41 42
41 42
43 44
1.0%
1.8%
2.0%
1.0%
2.8%
3.3%
1.0%
4.5%
1.0%
3.1%
1.4%
1.7% 1.1%
0.9%
2.0%
1.0%
2.0% 2.0%2.0% 2.0%2.0%
11.5' SETBACK
5.0' SEWER
ESMT
0.9%
0.6%
3.0' R/W
DEDICATION
1.8%
0.9%
0.0%
2.0%
1.2%
24.0'
DRIVE AISLE 8.5'
0.5%
3.5%
27 5.0'5.0'
4.2'
ROOSEVELT ST
EXISTING STREET/ PED LIGHTBBQ/WALL LIGHTSCONCE LIGHTTREE LIGHT
CONCEPT LIGHTING LEGEND
10 51020 0
SCALE: 1"=10'-0"
30 TWO WORKING DAYS BEFORE YOU DIG
Call:
Underground Service Alert
"CAUTION": Remember that the USA Center notifies
only those utilities belonging to the center. There
could be other utilities present at the work site. The
center will inform you of whom they will notify.
02-25
«
«
G:\23-PROJECTS\23-061-00\Landarch\Concept\23-061 Concept Lighting Plan.dwg[23-061-00 Roosevelt Concept]Sep-19-2025:09:09 VKHHW
GaWH
MRE QR.
9 RINCON ROOSEVELT
23061
VKHHW
LANDSCAPE CONCEPT PLAN
GMP
3176 LIONSHEAD AVE.
CARLSBAD, CA 92010
t: 858-558-8977
09/12/25 - 100% SD
PLANNING DEPT SUB 05
PERMIT NUMBER / PERMIT NUMBER / PERMIT NUMBER
LANDSCAPE
ARCHITECTURE
& PLANNING
gmplandarch.com
T 858 558 8977
4010 Sorrento Valley Blvd.
Suite 200
San Diego, CA 92121
CONCEPTUAL LIGHTING PLANLC-05
1. ALL LIGHTING SHOWN IS CONCEPTUAL. FINAL LIGHTING PLAN
CONSTRUCTION DOCUMENTS TO ADHERE TO ALL APPLICABLE
CODES.
LIGHTING NOTES
LIGHTING NOTES:
ALL LIGHTING SHALL BE PERMANENT FIXTURES THAT ARE
UL TESTED AND APPROVED. THE DESIGN OF THE
LIGHTING SHALL BE DONE SO THAT MAIN ENTRANCES,
FOCAL POINTS AND GATHERING AREAS ARE ILLUMINATED
TO ENHANCE EACH SPACE. FIXTURES LOCATED ON THE
BUILDINGS AND WITHIN THE LANDSCAPE ARE INTENDED
TO ILLUMINATE EMERGENCY EGRESS PATHWAYS TO
MEET ALL LOCATE CODES AND REQUIREMENTS. LIGHT
POLLUTION IS A MAJOR CONCERN AND APPROPRIATE
WATTAGES AND ACCESSORIES SUCH AS CUT-OFF
SHIELDS WILL BE UTILIZED TO MINIMIZE LIGHT TRESPASS
INTO UNWANTED AREAS. ALL LIGHTING SHALL COMPLY
WITH THE CITY OF CARLSBAD LAND DEVELOPMENT CODE
AND OTHER APPLICABLE GUIDELINES.
BBQ / PLANTER WALL LIGHTS
BUILDING SCONCE
TREE UPLIGHT
GROUND LEVEL
Sept. 29, 2026
Item #9 Page 53 of 195
ELEV
IDF
AMENITYCOURT
STAIR 2
STAIR 1
UNIT C2
UNIT C1
UNIT D1a
UNIT D1
UNIT B1
UNIT A1
UNIT A1
UNIT A3
UNIT B2
UNIT A2
UNIT A2
STO.
TR
GREASE SHAFT
HORIZONTAL EXITW/ MAG-HOLD DOOR
FULL
HEIGHTSCREEN
LINE OF GROUND
FLOOR BELOW
SECOND FLOOR PLAN
EXISTING STREET/ PED LIGHTBBQ/WALL LIGHTSCONCE LIGHTTREE LIGHT
CONCEPT LIGHTING LEGEND
10 51020 0
SCALE: 1"=10'-0"
30 TWO WORKING DAYS BEFORE YOU DIG
Call:
Underground Service Alert
"CAUTION": Remember that the USA Center notifies
only those utilities belonging to the center. There
could be other utilities present at the work site. The
center will inform you of whom they will notify.
02-25
«
«
G:\23-PROJECTS\23-061-00\Landarch\Concept\23-061 Concept Lighting Plan.dwg[23-061-00 Roosevelt Concept]Sep-19-2025:09:09 VKHHW
GaWH
MRE QR.
9 RINCON ROOSEVELT
23061
VKHHW
LANDSCAPE CONCEPT PLAN
GMP
3176 LIONSHEAD AVE.
CARLSBAD, CA 92010
t: 858-558-8977
09/12/25 - 100% SD
PLANNING DEPT SUB 05
PERMIT NUMBER / PERMIT NUMBER / PERMIT NUMBER
LANDSCAPE
ARCHITECTURE
& PLANNING
gmplandarch.com
T 858 558 8977
4010 Sorrento Valley Blvd.
Suite 200
San Diego, CA 92121
CONCEPTUAL LIGHTING
LC-06
1. ALL LIGHTING SHOWN IS CONCEPTUAL. FINAL LIGHTING PLAN
CONSTRUCTION DOCUMENTS TO ADHERE TO ALL APPLICABLE
CODES.
LIGHTING NOTES
LIGHTING NOTES:
ALL LIGHTING SHALL BE PERMANENT FIXTURES THAT ARE
UL TESTED AND APPROVED. THE DESIGN OF THE
LIGHTING SHALL BE DONE SO THAT MAIN ENTRANCES,
FOCAL POINTS AND GATHERING AREAS ARE ILLUMINATED
TO ENHANCE EACH SPACE. FIXTURES LOCATED ON THE
BUILDINGS AND WITHIN THE LANDSCAPE ARE INTENDED
TO ILLUMINATE EMERGENCY EGRESS PATHWAYS TO
MEET ALL LOCATE CODES AND REQUIREMENTS. LIGHT
POLLUTION IS A MAJOR CONCERN AND APPROPRIATE
WATTAGES AND ACCESSORIES SUCH AS CUT-OFF
SHIELDS WILL BE UTILIZED TO MINIMIZE LIGHT TRESPASS
INTO UNWANTED AREAS. ALL LIGHTING SHALL COMPLY
WITH THE CITY OF CARLSBAD LAND DEVELOPMENT CODE
AND OTHER APPLICABLE GUIDELINES.
BBQ / PLANTER WALL LIGHTS
BUILDING SCONCE
TREE UPLIGHT
2ND FLOOR AMENITY DECK
Sept. 29, 2026
Item #9 Page 54 of 195
Exhibit 7
Response to Planning Commission Comments
at February 18, 2026 Hearing
Pla
nning Commission
The Planning Commission considered the project on February 18, 2026. Three speakers provided comments at the hearing. One expressed overall support for the project. The remaining two speakers had concerns regarding the design, maintenance of landscaping, screening of the air conditioning units and size of the parking stalls. In addition, Commissioner Lafferty expressed safety concerns due to the expanded setback between the building and the property lines and the lack of fence to limit access to the sides and rear of the building. The following is a summary of these concerns, and the responses provided.
Design
A member of the public expressed concern regarding the design, indicating it looked like a commercial structure. The project is designed to comply with a majority of the district- specific, area-wide and the California Contemporary and mixed use objective design standards of the Village & Barrio Master Plan. A wide variety of materials and architectural projections are proposed around all sides of the building. A common amenity courtyard on the second floor, which is open to the sky above, helps break up the mass of the building as viewed from the street. A total of 11 waivers to development standards are proposed. An unlimited number of waivers to development standards can be requested pursuant to State Density Bonus Law if the requisite findings can be made.
Landscaping
A member of the public expressed concern regarding whether the landscaping would be maintained. The landscaping around the perimeter of the building is part of a required landscape plan and stormwater quality management plan included with the development proposal. The landscaped areas are required to be maintained in perpetuity by the owners of the development.
Scre
ening of Air Conditioning Units
A member of the public expressed concern about the visibility of the air conditioning units. City staff indicated the project is designed to screen all air conditioning units from the street either from parapets or rooftop screening.
Size
of Parking Stalls
A member of the public expressed concern regarding the reduced size of the parking stalls. The minimum dimensions for a standard parking stall size are 8.5’ wide by 20’ long, exclusive of columns or posts. The minimum dimensions for a compact parking stall are 8’ wide by 15’ long. The project proposes parking stalls with minimum dimensions of 8’ wide by 16.6’ long, exclusive of the required accessible parking spaces.
The developer requests a density bonus waiver to allow for the reduction in the size of the standard parking spaces.
Sept. 29, 2026
Item #9 Page 55 of 195
Setbacks Along the Property Lines
Commissioner Lafferty expressed safety concern regarding the setback between the proposed building and the structures located on the adjacent properties. The increased side and rear yard setbacks are required for Fire Department access around the perimeter of the building and for the stormwater treatment facilities, which are in raised planters. The stormwater planters are four feet-wide and require access for maintenance. At the Planning Commission February 18, 2026, public hearing, the developer indicated that they were open to installing a gate to limit public access to the sides of the building; however, no condition of approval was added to the project. There are no objective standards in the city requiring access-controlled gates. Under the HAA, while the city can’t force arbitrary conditions on a housing development project, the developer may voluntarily agree to a specific condition to settle neighborhood disputes.
If the City Council decides to move forward and approve the housing development project and wishes to require an access gate be added to the property, city staff recommends that the developer be given the option to voluntarily agree to the condition.
Sept. 29, 2026
Item #9 Page 56 of 195
Exhibit 8
Project-Related Compliance Analysis
of Statewide Tenant Protection Requirements
Th
e Housing Crisis Act (Government Code sections 66300-66300.6.5)1 created new state laws regarding the production and preservation of housing development. The Housing Crisis Act aims to increase certainty in the development process, prevent certain zoning actions that reduce the availability of housing, and preserves existing affordable housing. The Housing Crisis Act also protects households facing evictions and provides other additional benefits to lower- income households residing in protected units2 who will be displaced by development of a new housing project.
First, existing tenants of demolished or replaced “protected units” are entitled to certain statewide tenant protections. Pursuant to Government Code section 66300.6(b)(3), an existing tenant shall be allowed to occupy their unit until six months before the start of construction activities and must be given six-months’ notice prior to the date they must vacate regarding the planned timeline for demolition, the date they must vacate, and their rights under California Government Code section 66300.6, including a right to return to their unit at the prior rental rate if the demolition does not occur. Second, developers must agree to provide a lower- income household in a protected unit with both relocation benefits3 and a right of first refusal4 for a comparable unit in the new housing development at an affordable rent or an affordable housing cost. The goal of the notice requirement, relocation benefit, and right of first refusal requirement are to provide or sustain housing opportunities to the lower income households who are being or scheduled to be displaced due to the housing development project.
Another key component of the Housing Crisis Act is that a developer must commit to replacing all “protected units” in the new housing development project.5 Replacement requirements 1 The Housing Crisis Act of 2019 (SB 330, 2019) was signed by Governor Newsom on October 9, 2019, and became effective on January 1, 2020. It was amended by SB 8 in 2021.
2 “Protected units” as a term defined by statute include: (1) units with low-income deed restrictions in the past 5 years; (2) units subject to local rent control in the past 5 years; (3) units occupied by low-income tenants in the past 5 years; and (4) units removed via the Ellis Act in the past 10 years. (Government Code section 66300.5(h).) 3 The Housing Crisis Act includes provisions for relocation assistance, primarily for lower-income tenants who are displaced when a housing development project demolishes or replaces existing “protected units.” The Housing Crisis Act mandates that tenants who are displaced due to certain housing development projects, including those forced to move out due to demolition, conversion, or substantial rehabilitation, must receive relocation assistance. (Government Code section 66300.6(b)(4)(A).) This is in addition to other no fault eviction rules, and supplemented by other statewide requirements, such as the Tenant Protection Act of 2019 (AB 1482), and California Health and Safety sections 17975-17975.10. 4 A right of first refusal is a legal mechanism that gives certain entities the opportunity to purchase an affordable housing unit before it can be sold to others. It gives the existing lower-income tenant priority over other potential buyers. It is a key tool under the Housing Crisis Act and related statutes to preserve affordability. (Government Code section 66300.6(b)(4)(B).) 5 The Housing Crisis Act requires housing development projects to create at least as many units as will be demolished during construction of the project in an affected jurisdiction. It also requires the same level of affordability by ensuring that the housing development project begins with the same number of affordable units. (Government Code section 66300.6(b)(1).) Sept. 29, 2026
Item #9 Page 57 of 195
largely mirror those under the State Density Bonus Law (Government Code section 65915- 65918) and replacement units may be used towards meeting density bonus requirements or a local inclusionary housing requirement. The statute uses the term “replace” and “replacement,” suggesting that a unit currently or previously subject to affordable restrictions or actually occupied by persons with lower-income is being demolished or removed from affordability due to conversion into a new or different residential use or other nonresidential use.
In short, the “replacement” requirements address housing units, while the “tenant protection” requirement address people.
In the case of the proposed project, five of the eight-unit apartments in question are protected because they are rented by income-qualifying households. One household qualifies in the extremely low-income category and four households qualify in the low-income category. (The housing units were also withdrawn from the rental market, which could also be construed as a qualifying event for replacement requirements and tenant protection requirements.) A timeline of the city’s review of the subject application and discovery of facts are provided in Exhibit 9.
Both the city and developer mutually agree that some of the existing housing units qualify as “protected units” – one for an extremely low-income household and four for low-income households, which is reflected in the developer’s submitted materials (i.e. Project Description and details of the request). Since the units qualify as “protected units,” any tenants living in designated "protected units" are legally entitled to robust displacement protections if a landlord or developer intends to develop or redevelop the property.
The disagreement between the city and the developer is regarding the area of state law that addresses the strict noticing and procedural requirements, and whether the developer has the ability to cure or remedy a violation of any one of the statewide tenant protection requirements. The developer stated it was unaware of the property owner’s actions and proposed to remedy the tenant protection violations by contacting the former tenants and offering them the opportunity to move back into the property. The developer contends that offering each tenant an opportunity to return to their unit cures or remedies the violation(s).
On the other hand, city staff believe the city is required by state law to recommend denial of the project. The property owner and developer are unable to meet the strict noticing requirements and unfairly terminated tenancy to lower income households, leading to their displacement. Although the violations of the Housing Crisis Act’s tenant protections requirements were committed by the property owner, the property owner and the developer are treated as one applicant for the purpose of the city’s approval process.
It is acknowledged that the Housing Crisis Act was designed to encourage the expeditious processing and approval of housing development projects. The State Legislature specifically found, for instance, that the State of California is experiencing a housing supply shortage of crisis proportions and declared a statewide housing emergency, suspending certain restrictions on development of new housing during that period. However, the State of California also has some of the strongest tenant protections in the nation, with laws that make it harder for landlords to evict without cause and require strict procedures before eviction can occur. These Sept. 29, 2026
Item #9 Page 58 of 195
areas of law often conflict when an older, occupied residential building is scheduled to replaced or converted into a new residential building. The Housing Crisis Act expressively states that “…an affected city or an affected county shall not approve a development project that will require the demolition of occupied or vacant protected units, or that is located on a site where protected units were demolished in the previous five years, unless all [statewide occupant protections] … are satisfied …” That is, if a household lives in a “protected unit” and their home is going to be demolished or replaced for a new housing development, they are entitled to specific noticing, relocation assistance, a right of first refusal and other protections. It seems unlikely that the State Legislature would use the term “shall not approve” if it merely meant that developer could avoid these requirements and/or find alternative means of compliance if found in violation of the statute, otherwise the statute would have language allowing such remedy.
State law protects applicants from arbitrary denials. But there is also a clear effort to balance housing production and housing preservation in the statute itself.
In most cases, before the city or county can deny a land use development project it must make findings or determinations based on “substantial evidence.” However, under the Housing Crisis Act, a housing development project must not only comply with the “protected unit” provisions (preserving affordability when replacing an outdated structure with a new residential structure), but landlords/developers must also create legally valid notices pursuant to Government Code section 66300.6(b)(3), provide relocation assistance pursuant to Government Code section 66300.6(b)(4)(A), and offer a right of first refusal pursuant to Government Code section 66300.6(b)(4)(B). If the landlord or developer skips these steps, the law prohibits affected cities or counties from approving any development project, not just housing development projects. The state law reads as mandatory and absolute, and leaves little to no room for interpretation or discretion. This creates a bright-line standard, where all parties know exactly what is legal or illegal beforehand.
City staff believe facts in this case substantiate and support the recommended denial of the proposed project.
Sept. 29, 2026
Item #9 Page 59 of 195
Project Processing Timeline and HCD and Developer Correspondences On August 3, 2023, Stephen Dalton Architects, acting on behalf of the property owner, filed a preliminary review application (PRE 2023-0043) for a housing development project, called Rincon Roosevelt, at the subject site.
On September 21, 2023, the city is sued a city re view letter providing c omments on the preliminary application. Staff comment letter (Attachment A) reference the Housing Crisis Act and robust displacement protections if a landlord or developer intends to develop or redevelop the property. This information was provided before a formal application was received and before tenants were displaced.
On
August 29, 2024, Rincon Homes filed a preliminary application for housing development pro
ject seeking vesting rights pursuant to SB 330.
On September 18, 2024, Rincon Homes submitted a formal land use development application for a housing development project, called Rincon Roosevelt. As part of the application process, the Rincon Homes was required to submit several intake forms to complete their application, including a Disclosure Statement Form (P-1A Form, Attachment B) and a Housing Declarations Form (P-38 Form, Attachment C). A P-38B Form (Attachment D) requires the applicant to verify income and/or occupancy of tenants. The P-38B Form also requires the applicant to make several acknowledgements, including that certain “tenant protections” may apply to the project.
From June 2024 to August 2024, five (5) of the (8) tenants completed the income verification forms.
On October 18, 2024, city’s first discretionary review letter issued; Government Code requirements related to noticing, replacement, and relocation requirements included in scope of letter.
On March 31, 2025, Housing and Homeless Services staff determined that five (5) protected units are required, per completed Income Certification Forms (P-38 Form) from existing residents and application of the CHAS data percentage for the units in which the tenant’s incomes were unknown.
On April 11, 2025, city’s second discretionary review letter issued; Government Code requirements related to noticing, replacement, and relocation requirements included in scope of letter.
Exhibit 9
Sept. 29, 2026
Item #9 Page 60 of 195
On June 3, 2025, Rincon Homes submitted draft notice to Housing and Homeless Services staff and asked for any input. Applicant stated notice will be sent to existing tenants (Attachment E).
On J
uly 3, 2025, city’s third discretionary review letter issued; Government Code requirements related to noticing, replacement, and relocation requirements included in scope of letter.
On A
ugust 12, 2025, Housing and Homeless Services provided emailed comments to Rincon Homes and included same language as the email provided on March 31, 2025, including providing comments on a general information notice that Rincon Homes prepares regarding tenant protections (Attachment E).
On Aug
ust 21, 2025, Rincon Homes indicates that they were told by the owner that several tenants are intending to move out and that they do not have forwarding addresses (Attachment E).
On Sep
tember 3, 2025, the proposed project was determined to be complete for further processing. At this point, staff were led to believe that the units were occupied and the Rincon Homes intended to implement and fulfill all statewide tenant protection requirements following project approval (as required by the Housing Crisis Act).
A rep
resentative of Rincon Homes informed the project planner in the first week in February 2026 that the apartment building was vacant. The conversation happened in-person when submitting a final set of plans for distribution to the Planning Commission.
On February 18, 2026, the Planning Commission considered the project at a public hearing. At the hearing, planning staff indicated the units were vacant, but its significance at the time was not known. The Planning Commission voted 6-1 (Lafferty voting No) to recommend approval of the project to the City Council.
However, shortly after the Planning Commission hearing staff learned that the former tenants that lived in the qualified “protected units” were displaced.
On Ma
rch 17, 2026, Housing and Homeless Services staff and Planning staff met with Rincon Homes to discuss the issues.
Rin
con Homes, after acknowledging the potential effect of violating existing tenants' rights, proposed to notify all prior tenants that they would offer their return to their unit at the prior rental rate and be allowed to stay until six months prior to demolition.
On M
arch 24, 2026, Rincon Homes sent correspondences to seven (7) of the eight (8) former tenants to inform them of certain rights that former tenants may have under state law (Attachment F). The applicant sent record of this effort to Housing and Homeless Services staff on April 20, 2026. Notice summarized tenants’ rights under the Housing Crisis Act (even though Sept. 29, 2026
Item #9 Page 61 of 195
they were no longer living in the apartment building). Six (6) of the former tenants confirmed receipt of the applicant notice.
Ho
using and Homeless Services staff spoke to one of the former tenants in April 2026. The tenant verbally confirmed that their tenancy was not permitted beyond a certain date and did not receive any kind of information about the proposed project or their rights and eligibility for benefits.
On May 6
, 2026, city staff and Rincon Homes discuss situation at length, including their proposal to send the notice for a Right to Return at Prior Rental Rate (Attachment G). Rincon Homes informs the city that they now own the property. Applicant shared that they contacted six (6) of the eight (8) former tenants and is working to contact the other two (2) tenants.
Ci
ty staff initially took no position on the applicant’s proposal and expressed concern about the city’s ability to recommend and approve the project when there was a violation of state law. On May 27, 2026, the city submitted an inquiry to the State Department of Housing and Community Development (HCD) seeking technical assistance (Attachment H).
HC
D reviewed the information and had follow-up conversations with both city staff and the applicant.
On Jul
y 9, 2026, HCD staff verbally told city staff in a virtual meeting that the applicant’s proposal sounded reasonable, given the circumstances.
Ho
using and Homeless Services receive communications between applicant and former tenants (Attachment I). Based on this record, one tenant “would have been happy to stay longer.” Another former tenant indicated an interest in benefits (implying they had not been received prior to moving). Another former tenant indicated that they moved in April 2025.
Ho
using and Homeless Services had conversations with another former tenant and they indicated that they moved out in September 2025 (Attachment I).
Ba
sed on HCD’s verbal opinion, the applicant (Rincon) sent the notices to seven (7) of the eight (8) former tenants via certified mail on July 13, 2026, and via email on July 14, 2026, requesting response by August 1, 2026. The applicant provided an option to return to their respective apartment unit and the same rental rate. (Attachment J) Fi
ve (5) responses were received. One former tenant accepted the offer to return to the apartment. The other four (4) former tenants declined.
Sinc
e city staff was concerned that HCD did not adequately answer the city’s question, city staff followed up again with HCD in an email dated August 12, 2026 (Attachment K). The email sought clarification on the city’s role and jurisdiction to approve, conditionally approve, or deny Sept. 29, 2026
Item #9 Page 62 of 195
the proposed project. The email indicated that if HCD is unwilling to provide a formal written response that the city staff would end up recommending the city council deny the project.
Des
pite the city’s straightforward request to HCD, on August 25, 2026, HCD staff responded by email that they declined to formally respond to the request in writing. Even though HCD staff reiterated that the developer’s proposed remedy seemed reasonable, HCD was and, as of this writing, is unwilling or unable to make a formal determination and put it in writing (Attachment L).
Att
achment A - PRE 2023-0043 City Comment Letter
Attachment B - Disclosure Statement Form
Attachment C - Housing Declarations Form
Attachment D – Income Verification Forms
Attachment E – Various Emails Between City and Rincon Homes Attachment F – Rincon Letter to Former Tenants with Notice of Rights Attachment G – Rincon Letter to Former Tenants with Right to Return Attachment H – Technical Assistance Inquiry Letter to HCD Attachment I – Rincon and City Communications with Former Tenants Attachment J – Rincon Letter to Former Tenants in Attempt to Cure Violation Attachment K – City Clarification Email to HCD to Request to Formal Determination Attachment L - HCD Response
Sept. 29, 2026
Item #9 Page 63 of 195
September 21, 2023
Stephen Dalton Architects
444 South Cedros Avenue, Studio 185
Solano Beach, CA 92075
SUBJECT: PRE 2023-0043 (DEV2023-0105}- RINCON ROOSEVELT APNs 203-181-10-00, 203-181-16-00, AND 203-101-12-00
{"Cityof
Carlsbad
8FILE COPY
Thank you for submitting a preliminary review for a residential project proposed on assessor's parcel numbers (APNs) 203-181-10-00, 203-181-16-00, and 203-101-12-00 in the Village Center District of the Village and Barrio Master Plan. The project site, consisting of three lots combining for approximately 29,000-square-feet, currently is developed with an existing 8-unit apartment building, small commercial building, and a parking lot. Vehicular access to the site is provided off Roosevelt Street.
The preliminary review exhibit(s) propose:
• Demolition of the existing apartment building with eight existing residential apartment units and a commercial building.
• Construction of a new mixed-use building containing 52,560 square-feet of residential space for 36 condominium units, 5,015 square-feet of commercial retail space, a 1,483-square-foot lobby, and 51 parking spaces.
In response to your application, the Planning Division has prepared this comment letter. Please note that the purpose of a preliminary review is to provide you with direction and comments on the overall concept of your project. This preliminary review does not represent an in-depth analysis of your project. It is intended to give you feedback on critical issues based upon the information provided in your submittal.
This review is based upon the plans, policies, and standards in effect as of the date of this review. Please be aware that at the time of a formal application submittal, new plans, policies, and standards may be in effect and additional issues of concern may be raised through a more specific and detailed review.
Planning:
General
1. General Plan and zoning designations for the property are as follows:
a. General Plan: Village - Barrio (V-B).
b. Zoning: Village- Barrio (V-B).
c. Master Plan: Village and Barrio Master Plan (VBMP}, Village Center (VC) District
2. The project requires the following permits:
a. Site Development Plan (SDP)
b. Planned Unit Development Permit (PUD)
Community Development Department
Planning Division I 1635 Faraday Avenue Carlsbad, CA 92008-7314 I 442-339-2600 www.carlsbadca.gov Attachment A
Sept. 29, 2026
Item #9 Page 64 of 195
PRE 2023-0043 (DEV2023-0105) RINCON ROOSEVELT
September 21, 2023