2. Wireless Modules:
a. Provide wireless communication inputs for:
1) Occupancy sensors.
2) Daylight sensors.
3) Wireless controller.
b. RF Range: 30 feet (9 m) between sensor and compatible RF receiving devices.
c. RF Frequency: 434 MHz; operates in FCC governed frequency spectrum for periodic operation; continuous transmission spectrum is not permitted.

3. Communicate sensor information to wired low-voltage digital link for use by compatible devices.

2.6 WIRED SENSORS
ATTACHMENT B ITEM 6
260926 - 17 City of Ceres
Water Division
A. Wired Occupancy Sensors:

1. General Requirements:
a. Connects directly to compatible ballasts and modules without the need of a power pack or other interface.
b. Turns off or reduces lighting automatically after reasonable time delay when a room or area is vacated by the last person to occupy the space. c. Accommodates all conditions of space utilization and all irregular work hours and habits.
d. Comply with UL 94.
e. Self-Adaptive Sensors: Continually adjusts sensitivity and timing to ensure optimal lighting control for any use of the space; furnished with field-adjustable controls for time delay and sensitivity to override any adaptive features. f. Provide capability to:
1) Add additional timeout system-wide without need to make local adjustment on sensor.
2) Group multiple sensors.
g. Power Failure Memory: Settings and learned parameters to be saved in nonvolatile memory and not lost should power be interrupted and subsequently restored.
h. Furnished with all necessary mounting hardware and instructions. i. Class 2 devices.
j. Ceiling-Mounted Sensors: Indicate viewing directions on mounting bracket. k. Wall-Mounted Sensors: Provide swivel-mount base.
l. Color: White.

2. Wired Passive Infrared Sensors:
a. Utilize multiple segmented lens, with internal grooves to eliminate dust and residue build-up.
b. Ceiling-Mounted Sensors: Provide customizable mask to block off unwanted viewing areas.
1) timeout; customizable mask for aisle and end of aisle applications.

3. Wired Ultrasonic Sensors:
a. Utilize an operating frequency of 32 kHz or 40 kHz, crystal-controlled to operate within plus/minus 0.005 percent tolerance.

4. Wired Dual Technology Sensors:
a. Passive Infrared: Utilize multiple segmented lens, with internal grooves to eliminate dust and residue build-up.
b. Ultrasonic: Utilize an operating frequency of 32 kHz or 40 kHz, crystalcontrolled to operate within plus/minus 0.005 percent tolerance. c. Ceiling-Mounted Sensors: Provide customizable mask to block off unwanted viewing areas.

ATTACHMENT B ITEM 6
260926 - 18 City of Ceres
Water Division
d. Isolated Relay: Provide an internal additional isolated relay with Normally Open, Normally Closed, and Common outputs for use with HVAC control, Data Logging and other control options where indicated. e. Integral Photocell: Provide an integral photocell with adjustable sensitivity to prevent lights from turning on when there is sufficient natural light where indicated.

B. Sensor Power Packs:

1. Provide sensor power packs where required for power connection to sensors.

2. For ease of mounting, installation and future service, power pack(s) to be able to mount through a 1/2 inch knockout in a standard electrical enclosure and be an integrated, self-contained unit consisting internally of an isolated load switching control relay and a transformer to provide low-voltage power. Transformer to provide power to a minimum of three sensors.

3. Plenum-rated.

4. Control Wiring Between Sensors and Control Units: Class 2, 18-24 AWG, stranded UL Classified, PVC insulated or TEFLON jacketed cable suitable for use in plenums, where applicable.

C. Infrared Receivers:

1. Use Class 2 wiring for low voltage communication.

2. Can be replaced without reprogramming.

3. 360 degree reception of wireless infrared remote controls.

4. Immediate local LED response upon reception of handheld transmitter communication.

5. Mountable on lighting fixtures or recessed acoustical ceiling tiles.

6. Constructed via sonic welding.

7. Color: White.

D. Wired Daylight Sensors:

1. Digital Interior Daylight Sensor:
a. Use Class 2 wiring for low voltage communication.
b. Can be replaced without reprogramming.
c. Open-loop basis for daylight sensor control scheme.
d. Stable output over temperature from 32 degrees F (0 degrees C) to 104 degrees F (40 degrees C).
e. Partially shielded for accurate detection of available daylight to prevent fixture lighting and horizontal light component from skewing sensor detection. f. Provide linear response from 0 to 500 footcandles.
g. Integral IR receiver for personal control.
h. Mountable on lighting fixtures or recessed acoustical ceiling tiles. i. Constructed via sonic welding.
j. Color: White.

2. Daylight Control Package:
a. Controller:

ATTACHMENT B ITEM 6
260926 - 19 City of Ceres
Water Division
1) Automatically switches a dry contact according to changes in ambient light levels.
2) Fully adjustable separate high and low setpoints, with an adjustable dead band between set points to prevent unwanted cycling. 3) Input time delay to prevent unwanted cycling due to intermittent light level fluctuations.
4) Signal/setpoint and relay status indication.
5) Sensor calibration input.
b. Sensors:
1) Class 2, three-wire analog devices.
2) Provision for zero or offset based signal.

E. Infrared Partition Sensors:

1. Provide contact closure based on status of the partition wall (open/close) enabling automatic linking of controls.

2.7 WIRELESS SENSORS
A. General Requirements:

1. Operational life of 10 years without the need to replace batteries when installed per manufacturer's instructions.

2. Communicates directly to compatible RF receiving devices through use of a radio frequency communications link.

3. Does not require external power packs, power wiring, or communication wiring.

4. Capable of being placed in test mode to verify correct operation from the face of the unit.

5. RF Range: 30 feet (9 m) between sensor and compatible RF receiving device(s).

6. Electromagnetic Interference/Radio Frequency Interference (EMI/RFI) Limits:

Comply with FCC requirements of 47 CFR 15, for Class B application.

B. Wireless Occupancy/Vacancy Sensors:

1. General Requirements:
a. Provides a clearly visible method of indication to verify that motion is being detected during testing and that the unit is communicating to compatible RF receiving devices.
b. Utilize multiple segmented lens, with internal grooves to eliminate dust and residue build-up.
c. Sensing Mechanism: Passive infrared coupled with technology for sensing fine motions; Lutron XCT Technology. Signal processing technology detects fine-motion passive infrared (PIR) signals without the need to change the sensor's sensitivity threshold.
d. Provide optional, readily accessible, user-adjustable controls for timeout, automatic/manual-on, and sensitivity.

ATTACHMENT B ITEM 6
260926 - 20 City of Ceres
Water Division
e. Turns off lighting after reasonable and adjustable time delay once the last person to occupy the space vacates a room or area. Provide adjustable timeout settings of 1, 5, 15, and 30 minutes.
f. Capable of turning dimmer's lighting load on to an optional locked preset level selectable by the user. Locked preset range to be selectable on the dimmer from 1 percent to 100 percent.
g. Color: White.
h. Provide all necessary mounting hardware and instructions for both temporary and permanent mounting.
i. Provide temporary mounting means to allow user to check proper performance and relocate as needed before permanently mounting sensor.

Temporary mounting method to be design for easy, damage-free removal. j. Sensor lens to illuminate during test mode when motion is detected to allow installer to verify coverage prior to permanent mounting. k. Ceiling-Mounted Sensors:
1) Provide surface mounting bracket compatible with drywall, plaster, wood, concrete, and compressed fiber ceilings.
2) Provide recessed mounting bracket compatible with drywall and compressed fiber ceilings.
3) Provide customizable mask to block off unwanted viewing areas. l. Wall-Mounted Sensors: Provide wall or corner mounting brackets compatible with drywall and plaster walls.

2. Wireless Combination Occupancy/Vacancy Sensors:
a. Ceiling-Mounted Sensors: Programmable to operate as an occupancy sensor (automatic-on and automatic-off), an occupancy sensor with low light feature (automatic-on when less than one footcandle of ambient light available and automatic-off), or a vacancy sensor (manual-on and automatic-off). b. Wall-Mounted Sensors: Programmable to operate as an occupancy sensor (automatic-on and automatic-off), or a vacancy sensor (manual-on and automatic-off).

C. Wireless Daylight Sensors:

1. Open-loop basis for daylight sensor control scheme.

2. Stable output over temperature from 32 degrees F (0 degrees C) to 104 degrees F (40 degrees C).

3. Partially shielded for accurate detection of available daylight to prevent fixture lighting and horizontal light component from skewing sensor detection.

4. Provide linear response from 0 to 10,000 footcandles.

5. Color: White.

6. Mounting:
a. Provide surface mounting bracket compatible with drywall, plaster, wood, concrete, and compressed fiber ceilings.
b. Provide all necessary mounting hardware and instructions for both temporary and permanent mounting.

ATTACHMENT B ITEM 6
260926 - 21 City of Ceres
Water Division
c. Provide temporary mounting means to allow user to check proper performance and relocate as needed before permanently mounting sensor.

Temporary mounting method to be design for easy, damage-free removal.

7. Meets CAL TITLE 24 P6 requirements.

2.8 ACCESSORIES
A. Emergency Lighting Interface:

1. Provides total system listing to UL 924 when used with lighting control system.

2. Senses all three phases of building power.

3. Accepts a contact closure input from a fire alarm control panel.

B. Provide power supplies as indicated or as required to power system devices and accessories.

1. Product(s):
a. Junction box-mounted power supply for shades, keypads, and accessories, and for providing additional low voltage power to communication link with miswire and thermal protection.
b. Plug-in power supply for shades, drapery drive units, keypads, and accessories, and for providing additional low voltage power to communication linkwith miswire protection; powered from standard receptacle using cord 6 feet (1.8 m) in length; complies with DOE Level VI regulation. c. Ten output power supply panel for shades, drapery drive units, keypads and accessories, and for providing additional low voltage power to communication link no replaceable fuses required for overload/miswire protection; contains DOE Level VI Compliant power supplies.
d. Power supply for keypads and accessories (not for shades/window treatments), and for providing additional low voltage power to communication link
C. Provide locking covers for controls where indicated.

1. Reversible to allow lock to be located on either side of control.

2. Compatible with IR controls.

3. Does not reduce specified IR range by more than 50 percent of its original specification.

2.9 SOURCE QUALITY CONTROL
A. See Section 01 4000 - Quality Requirements, for additional requirements.

B. Factory Testing; Lutron Standard Factory Testing:

1. Perform full-function factory testing on all completed assemblies. Statistical sampling is not acceptable.

ATTACHMENT B ITEM 6
260926 - 22 City of Ceres
Water Division

2. Perform full-function factory testing on 100 percent of all ballasts and LED drivers.

3. Perform factory audit burn-in of all dimming assemblies and panels at 104 degrees F (40 degrees C) at full load for two hours.

4. Perform factory burn-in of 100 percent of all ballasts at 104 degrees F (40 degrees C).

PART 3 - EXECUTION

3.1 EXAMINATION
A. Verify that field measurements are as shown on the drawings.

B. Verify that ratings and configurations of system components are consistent with the indicated requirements.

C. Verify that mounting surfaces are ready to receive system components.

D. Verify that conditions are satisfactory for installation prior to starting work.

3.2 INSTALLATION
A. Perform work in a neat and workmanlike manner in accordance with NECA 1 and, where applicable, NECA 130.

B. Install products in accordance with manufacturer's instructions.

C. Define each dimmer/relay load type, assign each load to a zone, and set control functions.

D. Sensor Locations:

1. Where Lighting Control Manufacturer Sensor Layout and Tuning service is specified in Part 2 under "LIGHTING CONTROL SYSTEM - GENERAL REQUIREMENTS", locate sensors in accordance with layout provided by Lighting Control Manufacturer.

Lighting Control Manufacturer may direct Contractor regarding sensor relocation should conditions require a deviation from locations indicated. Where Lighting Control Manufacturer Sensor Layout and Tuning service is not specified, locate sensors in accordance with Drawings.

2. Sensor locations indicated are diagrammatic. Within the design intent, reasonably minor adjustments to locations may be made in order to optimize coverage and avoid conflicts or problems affecting coverage, in accordance with manufacturer's recommendations.

E. Mount exterior daylight sensors to point due north with constant view of daylight.

F. Ensure that daylight sensor placement minimizes sensor view of electric light sources.

Locate ceiling-mounted and luminaire-mounted daylight sensors to avoid direct view of luminaires.

ATTACHMENT B ITEM 6
260926 - 23 City of Ceres
Water Division
G. Lamp Burn-In: Operate lamps at full output for prescribed period per manufacturer's recommendations prior to use with any dimming controls. Replace lamps that fail prematurely due to improper lamp burn-in.

H. Lamp Lead Lengths: Do not exceed 3 feet (0.9 m) for T4 4-pin compact and T5 BIAX lamps and 7 feet (2.1 m) for T5, T5-HO, T8 U-bend, and T8 linear fluorescent lamps.

I. LED Light Engine/Array Lead Length: Do not exceed 100 feet (31 m).

3.3 FIELD QUALITY CONTROL
A. Manufacturer's Startup Services; Lutron Standard Startup Services:

1. Manufacturer's authorized Service Representative to conduct minimum of two site visits to ensure proper system installation and operation.

2. Conduct Pre-Installation visit to review requirements with installer as specified in Part 1 under "Administrative Requirements".

3. Conduct second site visit upon completion of lighting control system to perform system startup and verify proper operation:
a. Where Lighting Control Manufacturer Sensor Layout and Tuning service is specified in Part 2 under “LIGHTING CONTROL SYSTEM – GENERAL REQUIREMENTS”, authorized Service Representative to verify sensor locations, in accordance with layout provided by Lighting Control Manufacturer; Lighting Control Manufacturer may direct Contractor regarding sensor relocation should conditions require a deviation from locations indicated.
b. Verify connection of power wiring and load circuits. c. Verify connection and location of controls.
d. Address devices.
e. Verify system operation control by control.
f. Verify proper operation of manufacturer's interfacing equipment. g. Configure initial groupings of ballast for wall controls, daylight sensors and occupancy sensors.
h. Provide initial rough calibration of sensors; fine-tuning of sensors is responsibility of Contractor unless provided by Lighting Control Manufacturer as part of Sensor Layout and Tuning service where specified in Part 2 under "LIGHTING CONTROL SYSTEM - GENERAL REQUIREMENTS".
i. Train Owner's representative on system capabilities, operation, and maintenance, as specified in Part 3 under "Closeout Activities". j. Obtain sign-off on system functions.

B. Correct defective work, adjust for proper operation, and retest until entire system complies with contract documents.

3.4 ADJUSTING
A. On-Site Scene and Level Tuning; Lutron LSC-AF-VISIT: Include additional costs for Lighting Control Manufacturer to visit site to conduct meeting with Owner's representative ATTACHMENT B ITEM 6
260926 - 24 City of Ceres
Water Division
to make required lighting adjustments to the system for conformance with original design intent.

B. Sensor Fine-Tuning: Where Lighting Control Manufacturer Sensor Layout and Tuning service is specified in Part 2 under “LIGHTING CONTROL SYSTEM – GENERAL REQUIREMENTS”, Lighting Control Manufacturer to provide up to two additional poststartup on-site service visits for fine-tuning of sensor calibration. Where Lighting Control Manufacturer Sensor Layout and Tuning service is not specified, Contractor to provide fine-tuning of sensor calibration.

3.5 CLEANING
A. Clean exposed surfaces to remove dirt, paint, or other foreign material and restore to match original factory finish.

3.6 COMMISSIONING
A. Title 24 Acceptance Testing Service; Lutron LSC-SPV-DOC-T24: Include additional costs for Lighting Control Manufacturer to perform lighting control acceptance testing in accordance with CAL TITLE 24 P6. Submit required documentation.

3.7 CLOSEOUT ACTIVITIES
A. Demonstration:

1. On-Site Performance-Verification Walkthrough; Lutron LSC-WALK: Include additional costs for lighting control manufacturer to provide on-site demonstration of system functionality to facility representative.

B. Training:

1. Include services of manufacturer's authorized Service Representative to perform onsite training of Owner's personnel on operation, adjustment, and maintenance of lighting control system as part of standard system start-up services.

3.8 PROTECTION
A. Protect installed products from subsequent construction operations.

END OF SECTION
ATTACHMENT B ITEM 6
262416 - 1 City of Ceres
Water Division
SECTION 26 24 16

PANELBOARDS
PART 1 - GENERAL

1.1 SUMMARY
A. Section includes

1. Provide all labor, materials and equipment necessary to complete the installation required for the items specified under this Section, including but not limited to panelboards.

B. Related sections

1. Where items specified in other Division 26 sections conflict with the requirements of this Section, the most stringent requirement shall govern. a. 26 05 26 – Grounding and Bonding for Electrical Systems b. 26 28 11 – Overcurrent Protection Devices

2. The requirements of this Section apply to all Division 26 work, as applicable.

3. Consult all other sections, determine the extent and character of related work and properly coordinate work specified herein with that specified elsewhere to produce a complete installation.

1.2 REFERENCES
A. Comply with the latest edition of the following applicable specifications and standards except as otherwise shown or specified:

1. CCR –California Code of Regulations, Title 24
a. Part 3 -California Electrical Code(CEC); NFPA 70 National Electrical Code (NEC) with California amendments

2. Federal Specification
a. W-C-375; Circuit Breakers, Molded Case, Branch Circuit and Service

3. NECA –National Electrical Contractors Association
a. 407, Recommended Practice for Installing and Maintaining Panelboards

4. NEMA –National Electrical Manufacturer’s Association a. AB 1; Molded Case Circuit Breakers
b. PB 1; Panelboards
ATTACHMENT B ITEM 6
262416 - 2 City of Ceres
Water Division
c. PB 1.1; Instructions for Safe Installation, Operation and Maintenance of Panelboards Rated 600 Volts or Less

5. UL -Underwriters Laboratories, Inc.
a. 50; Cabinets and Boxes
b. 67; Panelboards
c. 98; Enclosed and Dead Front Switches
d. 489; Molded-Case Circuit Breakers and Circuit Breaker Enclosures e. 891; Dead-Front Switchboards
f. 943; Ground Fault Circuit Interrupters
g. 977; Fused Power Circuit Devices50; Enclosures for Electrical Equipment

1.3 SUBMITTALS
A. Submit manufacturer’s data for materials specified within this Section in accordance to Section 26 05 00.

B. Submittal shall show the following information: circuit breaker numbering, circuit breaker type and short circuit rating, provisions for future circuit breakers, bussing, including neutral and ground, ratings and enclosure dimensions and trims.

1.4 QUALITY ASSURANCE
A. All materials, equipment and parts comprising the materials specified herein shall be new and unused, bearing UL labels where applicable.

1.5 DELIVERY, STORAGE AND HANDLING
A. Handle carefully to avoid damage to internal components, enclosure and finish.

B. Store in a clean, dry environment. Maintain factory packaging and, if required, provide an additional cover to protect enclosure in harsh environments.

PART 2 - PRODUCTS

2.1 MANUFACTURERS
A. Square D, Cutler-Hammer or approved equal.

2.2 MATERIALS
A. Panelboards

1. Interior
ATTACHMENT B ITEM 6
262416 - 3 City of Ceres
Water Division
a. Shall be factory-assembled with voltage, ampacity, and short circuit rating as shown in Drawings.
b. Provide 1 continuous copper bus bar per phase. Each bus bar shall have sequentially phase branch circuit connectors suitable for plug-on or bolt-on branch circuit breakers. The bussing shall be fully rated. Panelboard bus current rating shall be determined by heat-rise tests conducted in accordance with UL 67. Panelboards shall be suitable for use as Service Equipment when application requirements comply with UL 67 and CEC/NEC 230.F and 230.G.
c. All current-carrying parts shall be insulated from ground and phase-to-phase by high dielectric strength material.
d. Interior trim shall be of dead-front construction to shield user from energized parts. Dead-front trims shall have pre-formed twist-out covering unused mounting spaces.
e. Nameplates shall contain system information and catalog number or factory order number. Interior wiring diagram, neutral wiring diagram, UL Listed label and short circuit current rating shall be displayed on the interior. f. Main and sub-feed circuit breakers shall be vertical mounted. Interior leveling provisions shall be provided for flush mounted applications.

2. Main Circuit Breaker
a. Circuit breaker shall be of type, rating and poles shown on Drawings per Section 26 28 11 – Overcurrent Protection Devices.

3. Branch Circuit Breakers
a. Circuit breakers shall be of type, rating and poles shown on Drawings per Section 26 28 11 – Overcurrent Protection Devices.

4. Enclosures
a. Type NEMA 1 Boxes
i. Boxes shall be galvanized steel constructed in accordance with UL 50 requirements. Galvanealed steel will not be acceptable. ii. Boxes shall have removable endwalls with knockouts located on one end.

Boxes shall have welded interior mounting studs. Interior mounting brackets are not required.
iii. Box width shall be 20 in wide.
b. Type NEMA 1 Fronts
iv. Front shall meet strength and rigidity requirements per UL 50 standards.

Front shall have ANSI 49 gray enamel electrodeposited over cleaned phosphatized steel.
v. Fronts shall be hinged 1-piece with door. Mounting shall be as indicated in Drawings.
vi. Panelboards rated 225 amperes and below shall flat fronts with concealed door hinges and trim screws. Front shall not be removable with the door locked. Panelboards rated above 225 amperes shall have fronts with trim ATTACHMENT B ITEM 6
262416 - 4 City of Ceres
Water Division
clamps and concealed door hinges. Front doors shall have rounded corners and edges shall be free of burrs.
vii. Front shall have cylindrical tumbler type lock with catch and spring-loaded stainless steel door pull. All lock assemblies shall be keyed alike. Two (2) keys shall be provided with each lock. A clear plastic directory cardholder shall be mounted on the inside of door.
c. Type NEMA 3R, 5, and 12
viii. Enclosures shall be constructed in accordance with UL 50 requirements.

Enclosures shall be painted with ANSI 49 gray enamel electrodeposited over cleaned phosphatized steel.
ix. All doors shall be gasketed and equipped with a tumbler type vault lock. All lock assemblies shall be keyed alike. 2 keys shall be provided with each lock. A clear plastic directory cardholder shall be mounted on the inside of door.
x. Maximum enclosure dimensions shall not exceed 20 in wide and 6.5 in deep.

PART 3 - EXECUTION

3.1 INSTALLATION
A. Install in accordance with manufacturer’s written instructions and NEMA PB 1.1.

B. Installation shall conform to NECA 407 where not specified under this Division.

C. Anchor panelboards to structural members and as shown on Drawings. Provide additional support as required. Anchor freestanding distribution panels to concrete pad.

D. Mount panelboards level and plumb.

E. Install flush mounted panel backbox front edges flush with finished wall. Where flush panel backbox is deeper than wall depth, install closing trim of wood or metal to provide a finished trim.

F. Where panelboard is flush in wall, provide one ¾” conduit stub into accessible ceiling above for every 5 spare circuit breaker or available space.

G. After installation, make all feeder connections to circuit breaker load side lugs and incoming secondary feeders.

3.2 FIELD QUALITY CONTROL
A. Inspect complete installation prior to energizing for physical damage, proper alignment, anchorage and grounding.

B. Check tightness of bolted connections and circuit breaker connections using a calibrated torque wrench or torque screwdriver per manufacturer’s written specifications.

ATTACHMENT B ITEM 6
262416 - 5 City of Ceres
Water Division

3.3 ADJUSTING
A. Measure steady state load line currents at each panelboard feeder; rearrange panelboard circuits to balance the phase loads with 20% of each other. Maintain proper phasing for multi-wire branch circuits.

3.4 SCHEDULES
A. Fill out panelboard circuit identification card, typewritten, with list of circuits in use.

Identification shall be specific with room designation and other information as necessary.

For distribution panels, use engraved laminated phenolic plates showing load served.

END OF SECTION
ATTACHMENT B ITEM 6
262726 - 1 City of Ceres
Water Division
SECTION 26 27 26

WIRING DEVICES
PART 1 - GENERAL

1.1 SUMMARY
A. Section includes

1. Provide all labor, materials and equipment necessary to complete the installation required for the items specified under this Section, including but not limited to wiring devices.

B. Related sections

1. Where items specified in other Division 26 sections conflict with the requirements of this Section, the most stringent requirement shall govern. a. 26 05 26 – Grounding and Bonding for Electrical Systems

2. The requirements of this Section apply to all Division 26 work, as applicable.

3. Consult all other sections, determine the extent and character of related work and properly coordinate work specified herein with that specified elsewhere to produce a complete installation.

1.2 REFERENCES
Comply with the latest edition of the following applicable specifications and standards except as otherwise shown or specified:

1. Federal Specification
a. W-C-596; Connector, Electrical, Power, General Specification for b. W-S-896; Switches, Toggle (Toggle and Lock), Flush Mounted (General Specification)

2. NEMA –National Electrical Manufacturer’s Association a. WD 1; General Color Requirements for Wiring Devices
b. WD 6; Wiring Devices-Dimensional Requirements

3. UL -Underwriters Laboratories, Inc.
a. 20; General-Use Snap Switches
b. 498; Standard for Attachment Plugs and Receptacles
c. 943; Standard for Ground-Fault Circuit-Interrupters
ATTACHMENT B ITEM 6
262726 - 2 City of Ceres
Water Division
d. 1449; Standard for Transient Voltage Surge Suppressors

1.3 SUBMITTALS
Submit manufacturer’s data for materials specified within this Section in accordance to Section 26 05 00.

QUALITY ASSURANCE
All materials, equipment and parts comprising the materials specified herein shall be new and unused, bearing UL labels where applicable.

PART 2 - PRODUCTS

2.1 SWITCHES
A. Wall switches

1. Specification grade, quiet, AC rated, mechanical, snap type with silver alloy contacts, and shall comply with NEMA WD-1 and Fed. Spec W-S-896.

2. Rating shall be 20A at 120/277Vac, unless otherwise shown.

3. Handles shall be nylon; color shall be compatible with adjacent wall finish.

4. Manufacturers and types
a. Single pole, single throw
xi. Cooper Wiring Devices #CSB120, Hubbell #CSB120, or equal. b. Double pole, single throw
xii. Cooper Wiring Devices #CSB220, Hubbell #CSB220, or equal. c. Three way
xiii. Cooper Wiring Devices #CSB320, Hubbell #CSB320, or equal.

B. Wall dimmer switches

1. Linear slide type dimmer with smooth and continuous square law dimming curve that complies with UL 20 and is UL listed for the specified load.

2. Dimmers shall have power failure memory to bring lights back on at same level prior to power interruption.

3. Dimmers shall incorporate air-gap switch accessible with wall plate installed.

4. Furnish dimmer switch of rating to connected loads; de-rate as required by manufacturer’s information for ganged installations.

5. Coverplate shall be snap-on type with no visible attachments or fins. Color shall be compatible with adjacent wall finish.

ATTACHMENT B ITEM 6
262726 - 3 City of Ceres
Water Division

6. Manufacturer and type
a. Lutron Nova series or approved equal.

2.2 RECEPTACLES
Standards

1. Specification grade, NEMA 5-15R configuration grounding type, rated 15A at 125/250Vac that conform to NEMA WD-6 and Fed. Spec W-C-596.

2. At dedicated receptacle locations and as otherwise noted, use specification grade, NEMA 5-20R configuration grounding type, rated 20A at 125/250Vac that conform to NEMA WD-6 and when possible Fed. Spec W-C-596.

3. Specialty receptacles shall conform to NEMA WD-6 and UL standards as applicable.

B. Color

1. General purpose receptacle face shall be nylon; color shall be compatible with adjacent wall finish, unless otherwise indicated.

C. Receptacle types

1. General purpose single
a. Provide self-grounding back and side wired with binding head staked terminal screw.
b. Use Cooper Wiring Devices #5261, Hubbell #5261, or equal for NEMA 5- 15R.
c. Use Cooper Wiring Devices #5361, Hubbell #5361, or equal for NEMA 5- 20R.

2. General purpose duplex
a. Provide self-grounding back and side wired with binding head staked terminal screws and break-off strip for two circuit wiring. b. Use Cooper Wiring Devices #5262, Hubbell #5262, or equal for NEMA 5- 15R.
c. Use Cooper Wiring Devices #5362, Hubbell #5362, or equal for NEMA 5- 20R.

3. Transient voltage surge suppressor (TVSS) duplex
a. Provide 20A, 125Vac receptacle consisting of NEMA 5-20R duplex device with integral TVSS protection circuit.
b. Provide LED indicator to verify surge protection and ground, and audible alarm to notify bad ground connection or surge protection expiration. c. TVSS characteristics:

ATTACHMENT B ITEM 6
262726 - 4 City of Ceres
Water Division
xiv. 400V clamping voltage.
xv. 280J energy rating.
xvi. 150Vac RMS MOV rating
xvii. 18kA maximum surge current in all modes (L-N, L-G and N-G) d. Use Cooper Wiring Devices #5362_S, no known equal.

4. Isolated ground
a. Provide receptacle specified within this Section with equipment grounding contacts connected only to the green grounding screw terminal of the device and with inherent electrical isolation from mounting strap.

5. Ground fault circuit interrupter (GFCI) duplex
a. Provide 20A, 125Vac receptacle consisting of NEMA 5-20R duplex device with integral solid state sensing and signaling circuitry capable of detecting and interrupting a maximum 5mA line-to-ground fault current in approximately 1/40th of a second per UL 943.
b. Provide visual device with trip indication, manual reset and test mechanisms per UL 943.
c. Device shall be capable of point of use and multi-outlet protection. d. Use Cooper Wiring Devices #XGF20, Hubbell #GF53, or equal.

6. Hospital grade and tamper resistant
a. Provide receptacle specified within this Section that conforms to UL 498 “Hospital Grade” requirements.
b. Tamper resistance receptacle shall have integral protection mechanism to prevent accidental shock from foreign object contacting energized blades.

7. Special purpose
a. Provide specification grade devices with NEMA configuration, voltage, ampacity, poles and ground provisions as noted on Drawings.

2.3 WALL PLATES
Interior locations

1. Finished Areas: 0.032” stainless steel, brushed or satin finish with required number of openings for location.

2. Exposed Areas: galvanized, raised type.

B. Exterior: die-cast copper-free aluminum, gasketed, raintight cover UL listed for exterior and wet locations while in use. Use Hubbell #WP8M (duplex), #WP26M (GFCI) or equal.

C. Screws shall match plate.

D. Tamper resistance receptacles shall have exposed screws of temper resistant type.

ATTACHMENT B ITEM 6
262726 - 5 City of Ceres
Water Division
E. Individual, gangable wall plates are not acceptable where two or more devices are installed at one location.

PART 3 - EXECUTION

3.1 PREPARATION
A. Coordinate device heights with architectural drawings and details.

B. Locate switches on latch side of door, unless otherwise indicated.

3.2 INSTALLATION
Mount and align device and wall plates level and plumb. Insure wall plates fit flat against wall and tight against device without strain on plate.

A. Comply with manufacturer’s instructions regarding termination of conductors to wiring device.

B. Derate ganged dimmer switches as instructed by manufacturer and use dedicated neutrals within all dimmer circuits.

C. Provide wall plates for all outlet boxes with devices.

D. Install blank wall plates on all outlet boxes in which no device is present or installed.

END OF SECTION
ATTACHMENT B ITEM 6
262811 - 1 City of Ceres
Water Division
SECTION 26 28 11

OVERCURRENT PROTECTION DEVICES
PART 1 - GENERAL

1.1 SUMMARY
A. Section includes

1. Provide all labor, materials and equipment necessary to complete the installation required for the items specified under this Section, including but not limited to overcurrent protection devices.

B. Related sections

1. Where items specified in other Division 26 sections conflict with the requirements of this Section, the most stringent requirement shall govern.

2. The requirements of this Section apply to all Division 26 work, as applicable.

3. Consult all other sections, determine the extent and character of related work and properly coordinate work specified herein with that specified elsewhere to produce a complete installation.

1.2 REFERENCES
A. Comply with the latest edition of the following applicable specifications and standards except as otherwise shown or specified:

1. CCR –California Code of Regulations, Title 24
a. Part 3 -California Electrical Code(CEC); NFPA 70 National Electrical Code (NEC) with California amendments

2. Federal Specification
a. W-C-375; Circuit Breakers, Molded Case, Branch Circuit and Service

3. NEMA –National Electrical Manufacturer’s Association a. AB 1; Molded-Case Circuit Breakers, Molded Case Switches, and CircuitBreaker Enclosures b. PB 2.2; Application Guide for Ground Fault Protective Devices for Equipment

4. UL -Underwriters Laboratories, Inc.
a. 248; Low Voltage Fuses
b. 468; Wire Connectors
c. 508E; IEC Type "2" Coordination Short Circuit Tests
ATTACHMENT B ITEM 6
262811 - 2 City of Ceres
Water Division
d. 489; Molded-Case Circuit Breakers and Circuit Breaker Enclosures e. 943; Standard for Ground-Fault Circuit-Interrupters

1.3 SUBMITTALS
A. Submit manufacturer’s data for materials specified within this Section in accordance to Section 26 05 00.

B. Production test of circuit breakers upon request of Engineer.

C. Submittal shall show the following information: circuit breaker numbering, circuit breaker type and short circuit rating, provisions for future circuit breakers, bussing, including neutral and ground, ratings and enclosure dimensions and trims.

1.4 QUALITY ASSURANCE
A. All materials, equipment and parts comprising the materials specified herein shall be new and unused, bearing UL labels where applicable.

B. The manufacturing facility shall be registered by Underwriters Laboratories Inc. to the International Organization for Standardization ISO 9002 Series Standards for quality.

1.5 DELIVERY, STORAGE AND HANDLING
A. Handle carefully to avoid damage to internal components, enclosure and finish.

B. Store in a clean, dry environment. Maintain factory packaging and, if required, provide an additional cover to protect enclosure in harsh environments.

PART 2 - PRODUCTS

2.1 FUSES
A. All power distribution fuses shall be time-delay, high interrupting (200kAIC minimum) and current limiting type, unless otherwise indicated. All fuses shall be of same manufacturer and model.

1. Motor branch circuit fuses (0 – 600A): UL Class RK5 dual element, time delay type shall be size for UL 508E “Type 2” coordination for the motor controller.

Coordinate fuse selection with motor starter overload relay heaters as required.

2. General purpose feeder fuses (0 – 600A): UL Class RK1 dual element, time delay type shall be size per Drawings.

B. Control and instrumentation fuses shall of type and rating as recommended by equipment manufacturer, suitable for fuse blocks or holders installation.

ATTACHMENT B ITEM 6
262811 - 3 City of Ceres
Water Division

2.2 MOLDED CASE CIRCUIT BREAKERS
A. General

1. Circuit breakers shall be constructed using glass reinforced insulating material.

Current carrying components shall be completely isolated from the handle and the accessory mounting area.

2. Circuit breakers shall have an over center, trip free, toggle operating mechanism which will provide quick-make, quick-break contact action. The circuit breaker shall have common tripping of all poles.

3. The circuit breaker handle shall reside in a tripped position between ON and OFF to provide local trip indication.

4. The maximum ampere rating and UL, IEC, or other certification standards with applicable voltage systems and corresponding interrupting ratings shall be clearly marked on face of circuit breaker after installation.

5. Circuit breakers shall have an RMS interrupting capacity not less than shown on Drawings, or if not shown shall not be less than:
a. 25kA for 480V systems
b. 22kA for 240V (or less) systems

6. Each circuit breaker shall be equipped with a push-to-trip button, located on the face of the circuit breaker to mechanically operate the circuit breaker tripping mechanism for maintenance and testing purposes.

7. Circuit breakers shall be equipped with UL Listed electrical accessories as noted on Drawing. Circuit breaker handle accessories shall provide provisions for locking handle in the ON and OFF position.

8. All circuit breakers shall be UL Listed for reverse connection without restrictive line and load markings and be suitable for mounting in any position.

9. Circuit breakers shall be constructed with factory installed mechanical lugs. All circuit breakers shall be UL Listed to accept field installable/removable mechanical type lugs. Lug body shall be bolted in place; snap in design not acceptable. All lugs shall be UL Listed to accept solid (not larger than #8 AWG) and/or stranded copper and aluminum conductors. Lugs shall be suitable for 90°C rated wire, sized according to the 75°C temperature rating in the CEC.

10. All circuit breakers shall be capable of accepting bus connections.

B. Thermal-Magnetic Circuit Breakers

1. Circuit breakers shall have a permanent trip unit containing individual thermal and magnetic trip elements in each pole.

2. Thermal trip elements shall be factory preset and sealed. Circuit breakers shall be true RMS sensing and thermally responsive to protect circuit conductor(s) in a 40°C ambient temperature.

3. Circuit breaker frame sizes above 100 amperes shall have a single magnetic trip adjustment located on the front of the circuit breaker.

4. Provide equipment ground fault protection where shown on Drawing with the following features.
a. Ground fault sensing system shall be modified zero sequence sensing type and not require any external power to trip the circuit breaker.

ATTACHMENT B ITEM 6
262811 - 4 City of Ceres
Water Division
b. The ground fault sensing system shall be suitable for use on grounded systems. The ground fault sensing system shall be suitable for use on threephase, three-wire circuits where the system neutral is grounded but not carried through the system or on three-phase, four-wire systems. c. Ground fault pickup current setting and time delay shall be field adjustable.

A switch shall be provided for setting ground fault pickup point. A means to seal the pickup and delay adjustments shall be provided. d. The ground fault sensing system shall include a ground fault memory circuit to sum the time increments of intermittent arcing ground faults above the pickup point.
e. A means of testing the ground fault system to meet the on-site testing requirements of CEC/NEC 230-95(c) shall be provided.
f. Local visual ground fault trip indication shall be provided. g. The ground fault sensing system shall be provided with Zone Selective Interlocking (ZSI) communication capabilities compatible with other thermal magnetic circuit breakers equipped with ground fault sensing, electronic trip circuit breakers with integral ground fault sensing and external ground fault sensing systems as noted on Drawings.

C. Electronic Trip Circuit Breakers

1. Circuit breaker trip system shall be a microprocessor-based true RMS sensing design with sensing accuracy through the thirteenth (13th) harmonic. Sensor ampere ratings shall be as indicated on Drawings.

2. The integral trip system shall be independent of any external power source and shall contain no less than industrial grade electronic components.

3. The ampere rating of the circuit breaker shall be determined by the combination of an interchangeable rating plug, the sensor size and the long-time pickup adjustment on the circuit breaker. The sensor size, rating plug and adjustment positions shall be clearly marked on the face of the circuit breaker. Circuit breakers shall be UL Listed to carry 80% (or 100% where noted on Drawings) of their ampere rating continuously.

4. The following time/current response adjustments shall be provided. Each adjustment shall have discrete settings and shall be independent of all other adjustments.
a. Instantaneous Pickup
b. Long Time Pickup
c. Long Time Delay
d. Short Time Pickup
e. Short Time Delay
f. Ground Fault Pickup (when specified with ground fault protection) g. Ground Fault Delay (when specified with ground fault protection)

5. A means to seal the trip unit adjustments in accordance with CEC/NEC 240-6(b) shall be provided.

6. Local visual trip indication for overload, short circuit and ground fault trip occurrences shall be provided.

7. An ammeter to individually display all phase currents flowing through the circuit breaker shall be provided. All current values shall be displayed in true RMS with 2% accuracy.

ATTACHMENT B ITEM 6
262811 - 5 City of Ceres
Water Division

8. Long Time Pickup indication to signal when loading approaches or exceeds the adjusted ampere rating of the circuit breaker shall be provided.

9. The trip system shall include a Long Time memory circuit to sum the time increments of intermittent overcurrent conditions above the pickup point. Means shall be provided to reset Long Time memory circuit during primary injection testing.

10. An ammeter to individually display all phase currents flowing through the circuit breaker shall be provided. Indication of inherent ground fault current flowing in the system shall be provided on circuit breakers with integral ground fault protection.

All current values shall be displayed in true RMS with 2% accuracy.

11. Circuit breakers shall be equipped with back-up thermal and magnetic trip system.

12. Equipment Ground Fault Protection shall be provided where noted on Drawings. a. Circuit breakers shall be provided with integral equipment ground fault protection for grounded systems. The circuit breaker shall be suitable for use on three-phase, three-wire circuits where the system neutral is grounded but not carried through the system or on three-phase, four-wire systems. b. A separate neutral current transformer shall be provided for three-phase, four-wire systems.
c. Ground fault sensing system shall be residual sensing type. d. The trip system shall include a ground fault memory circuit to sum the time increments of intermittent ground faults above the pickup point. e. A means of testing the ground fault system to meet the on-site testing requirements of CEC/NEC 230-95(c) shall be provided.
f. Local visual trip indication for a ground fault trip occurrence shall be provided.
g. The ground fault sensing system shall be provided with Zone Selective Interlocking (ZSI) communication capabilities compatible with other thermal magnetic circuit breakers equipped with ground fault sensing, electronic trip circuit breakers with integral ground fault sensing and external ground fault sensing systems as noted on Drawings.

13. Circuit breaker trip system shall be equipped with an externally accessible test port. Disassembly of the circuit breaker shall not be required for testing. Test set shall be capable of verifying the operation of all trip functions with or without tripping the circuit breaker.

2.3 INSULATED CASE CIRCUIT BREAKERS
A. Circuit breaker trip system shall be a microprocessor-based true RMS sensing design with sensing accuracy through the thirteenth (13th) harmonic. Sensor ampere ratings shall be as indicated on Drawings.

B. The integral trip system shall be independent of any external power source and shall contain no less than industrial grade electronic components.

C. Circuit breakers shall be equipped with back-up thermal and magnetic trip system.

D. Circuit breakers shall have an RMS interrupting capacity not less than shown on Drawings, or if not shown shall not be less than:

ATTACHMENT B ITEM 6
262811 - 6 City of Ceres
Water Division

1. 100kA for all frame sizes at 208V

2. 65kA for all 800A - 2,000A frames at 480V

3. 100kA for all 3,000A - 4,000A frames at 480V
E. The ampere rating of the circuit breaker shall be determined by the combination of an interchangeable rating plug, the sensor size and the long-time pickup adjustment on the circuit breaker. The sensor size, rating plug and switch adjustments shall be clearly marked on the face of the circuit breaker. Circuit breakers shall be UL Listed to carry 100% of their ampere rating continuously.

F. The following time/current response adjustments shall be provided. Each adjustment shall have discrete settings and shall be independent from all other adjustments. a. Instantaneous Pickup
b. Long Time Pickup
c. Long Time Delay
d. Short Time Pickup
e. Short Time Delay
f. Ground Fault Pickup (when specified with ground fault protection) g. Ground Fault Delay (when specified with ground fault protection) G. Circuit breakers with adjustable short-time function shall be provided with defeatable instantaneous adjustment and 30 cycle short-time withstand ratings. Short-time withstand ratings shall be specified in RMS symmetrical amperes, as shown on the [drawings] [schedules].

H. A means to seal the rating plug and trip unit adjustments in accordance with CEC/NEC 240-6(b) shall be provided.

I. Local visual trip indication for overload, short circuit and ground fault trip occurrences shall be provided.

J. An ammeter to individually display all phase currents flowing through the circuit breaker shall be provided. [Indication of inherent ground fault current flowing in the system shall be provided on circuit breakers with integral ground fault protection]. All current values shall be displayed in True RMS with 2% accuracy.

K. Long Time Pickup indication to signal when loading approaches or exceeds the adjusted ampere rating of the circuit breaker shall be provided.

L. The trip system shall include a Long Time memory circuit to protect against intermittent overcurrent conditions above the long time pickup point. Means shall be provided to reset Long Time memory circuit during primary injection testing.

M. True two-step stored energy mechanism with five (5) cycle closing time shall be provided.

All circuit breakers shall have multiple CHARGE/CLOSE provisions allowing the following sequence: CHARGE, CLOSE, RECHARGE, OPEN/CLOSE/OPEN N. Local control pushbuttons to OPEN and CLOSE circuit breaker shall be provided. Color coded visual indication of contact position (OPEN or CLOSED) shall be provided on the face of the circuit breaker. Local manual charging following CLOSE operation shall be ATTACHMENT B ITEM 6
262811 - 7 City of Ceres
Water Division
provided. Color coded visual indication of mechanism CHARGED and DISCHARGED position shall be provided on the face of the circuit breaker. Visual indicator shall indicate CHARGED only when closing springs are completely charged.

O. Each circuit breaker shall be electrically operated to permit remote CHARGE, CLOSE, and OPEN capabilities. Electrically operated circuit breaker shall be equipped with charge contact switch for remote indication of mechanism charge status.

P. An ammeter to individually display all phase currents flowing through the circuit breaker shall be provided. [Indication of inherent ground fault current flowing in the system shall be provided on circuit breakers with integral ground fault protection]. All current values shall be displayed in True RMS with 2% accuracy.

Q. All circuit breakers shall be equipped with electrical accessories as noted on Drawings.

R. Provide the following interlocking capabilities:

1. cell door interlock

2. key interlock for main-tie-main

3. lock off
S. Circuit breaker trip system shall be equipped with an externally accessible test port.

Disassembly of the circuit breaker shall not be required for testing. Test set shall be capable of verifying the operation of all trip functions with or without tripping the circuit breaker.

T. Equipment Ground Fault Protection shall be provided where noted on Drawings.

1. Circuit breakers shall be provided with integral equipment ground fault protection for grounded systems. The circuit breaker shall be suitable for use on three-phase, three-wire circuits where the system neutral is grounded but not carried through the system or on three-phase, four-wire systems.

2. A separate neutral current transformer shall be provided for three-phase, four-wire systems.

3. Ground fault sensing system shall be residual sensing type.

4. The trip system shall include a ground fault memory circuit to sum the time increments of intermittent ground faults above the pickup point.

5. A means of testing the ground fault system to meet the on-site testing requirements of CEC/NEC 230-95(c) shall be provided.

6. Local visual trip indication for a ground fault trip occurrence shall be provided.

7. The ground fault sensing system shall be provided with Zone Selective Interlocking (ZSI) communication capabilities compatible with other thermal magnetic circuit breakers equipped with ground fault sensing, electronic trip circuit breakers with integral ground fault sensing and external ground fault sensing systems as noted on Drawings.

2.4 DRAWOUT INSULATED CASE CIRCUIT BREAKERS
ATTACHMENT B ITEM 6
262811 - 8 City of Ceres
Water Division
A. Main circuit breaker shall meet the same requirements of insulated case circuit breakers and be individually drawout mounted where shown on Drawings.

B. Sturdy drawout rails shall be permanently attached to the sides of the breaker compartment and retract into the compartment when not in use.

C. When fully withdrawn, the circuit breaker shall permit access for inspection and testing.

Circuit breaker(s) shall also be removable from the rails completely.

D. When the circuit breaker is in the Connected, Test, or Disconnected positions, or when the circuit breaker is removed from the compartment, the compartment door shall be able to be fully closed and secured.

E. A removable crank shall be supplied for racking the circuit breaker between the Connected, Test, or Disconnected positions.

PART 3 - EXECUTION

3.1 PREPARATION
A. Notify Engineer no later than 10 working days for adjustable circuit breaker settings not shown within Drawings. Submit to Engineer the following information:

1. Panel, switchboard name/ID

2. Circuit breaker identifier (i.e., main circuit breaker, load served, etc.)

3. List of necessary settings (i.e., trip settings, time delays, etc.)

3.2 INSTALLATION
A. Install equipment and their accessories in to manufacturer’s instructions, pertinent Codes, and with recognized industry practices to insure device operates properly.

B. Tighten electrical connectors and terminals in accordance to manufacturer’s requirements. Where the manufacturer does not have published torque tightening values, comply with the requirements of UL 468.

3.3 FIELD QUALITY CONTROL
A. Check tightness of circuit breaker connections using a calibrated torque wrench or torque screwdriver per manufacturer’s written specifications.

B. Obtain the services of an independent testing company who shall provide quality control and adjustments as well as tests for

1. Check each circuit breaker above 100A on a 225A frame for long-time and shorttime delay pickup and instantaneous pickup.

ATTACHMENT B ITEM 6
262811 - 9 City of Ceres
Water Division
a. Instantaneous pickup current shall be determined by 4 cycles or less. b. Perform timing test with 300% of breaker trip unit rated current. c. Adjust unit if required, so that the tripping characteristics are within the limits of the published time-current characteristic curves for that particular trip unit.

2. Test and calibrate ground fault protection trip and pickup time on 225A frame breakers and larger.

C. Physically test key interlock systems to check for proper functionality.

D. Check and set where required all protective device settings in accordance with approved coordination study settings and conduct ground fault acceptance tests.

3.4 ADJUSTING
A. Adjust all operating mechanisms for free mechanical movement per manufacturer’s specifications.

B. Adjust circuit breaker trip and time delay settings to values indicated as instructed by Engineer.

1. Check each circuit breaker above 100A, long-time and short-time delay pickup and instantaneous pickup. Instantaneous pickup current shall be determined by 4 cycles or less. Perform timing test with 300% of breaker trip unit rated current.

Adjust unit if required, so that the tripping characteristics are within the limits of the published time-current characteristic curves for that particular trip unit.

2. Main circuit breaker ground fault setting shall be per CEC/NEC 230-95(a) or as directed by Engineer.

3.5 PROTECTION
A. When directed by Engineer provide physical means to “permanently fix” settings for rotary and DIP type switches with a thin coat of clear lacquer.

3.6 CLEANING
A. Remove marks, dirt and debris from installed equipment surfaces for “new like” appearance.

END OF SECTION
ATTACHMENT B ITEM 6
262816 - 1 City of Ceres
Water Division
SECTION 26 28 16

SAFETY SWITCHES AND INDIVIDUAL MOUNTED CIRCUIT BREAKERS PART 1 - GENERAL

1.1 SUMMARY
A. Section includes

1. Provide all labor, materials and equipment necessary to complete the installation required for the items specified under this Section, including but not limited to heavy duty fusible, non-fusible and double throw safety switches.

B. Related sections

1. Where items specified in other Division 26 sections conflict with the requirements of this Section, the most stringent requirement shall govern. a. 26 05 26 – Grounding and Bonding for Electrical Systems b. 26 28 11 – Overcurrent Protection Devices

2. The requirements of this Section apply to all Division 26 work, as applicable.

3. Consult all other sections, determine the extent and character of related work and properly coordinate work specified herein with that specified elsewhere to produce a complete installation.

1.2 REFERENCES
A. Comply with the latest edition of the following applicable specifications and standards except as otherwise shown or specified:

1. CCR –California Code of Regulations, Title 24
a. Part 3 -California Electrical Code(CEC); NFPA 70 National Electrical Code (NEC) with California amendments

2. NEMA –National Electrical Manufacturer’s Association a. KS 1; Enclosed Switches
b. 250; Enclosures for Electrical Equipment

3. UL -Underwriters Laboratories, Inc.
a. 98; Enclosed and Dead Front Switches
b. 489; Molded-Case Circuit Breakers and Circuit Breaker Enclosures ATTACHMENT B ITEM 6
262816 - 2 City of Ceres
Water Division

1.3 SUBMITTALS
A. Submit manufacturer’s data for materials specified within this Section in accordance to Section 26 05 00.

1.4 QUALITY ASSURANCE
A. All materials, equipment and parts comprising the materials specified herein shall be new and unused, bearing UL labels where applicable.

1.5 DELIVERY, STORAGE AND HANDLING
A. Handle carefully to avoid damage to internal components, enclosure and finish.

B. Store in a clean, dry environment. Maintain factory packaging and, if required, provide an additional cover to protect enclosure in harsh environments.

PART 2 - PRODUCTS

2.1 MANUFACTURERS
A. Square D, Cutler Hammer or approved equal.

2.2 MATERIALS
A. Heavy-duty safety switches

1. Switch interior
a. All switches shall have switch blades which are visible when the switch is OFF and the cover is open.
b. Lugs shall be front removable and UL Listed for 75C conductors, aluminum or copper.
c. 30A through 100A switches shall be equipped with factory or field installed fuse pullers.
d. Switches required for Type 12, 12K or Type 4-4X-5 stainless steel applications shall have all copper current carrying parts. e. All current carrying parts shall be plated to resist corrosion. f. Switches shall have removable arc suppressors to facilitate easy access to line side lugs.
g. Switches shall have provisions for a field installable electrical interlock.

2. Switch mechanism
a. Switch operating mechanism shall be quick-make, quick-break such that, during normal operation of the switch, the operation of the contacts shall not ATTACHMENT B ITEM 6
262816 - 3 City of Ceres
Water Division
be capable of being restrained by the operating handle after the closing or opening action of the contacts has started.
b. The operating handle shall be an integral part of the box, not the cover. c. Provisions for padlocking the switch in the OFF position with at least three padlocks shall be provided.
d. The handle position shall travel at least 90° between OFF and ON positions to clearly distinguish and indicate handle.
e. All switches shall have a dual cover interlock mechanism to prevent unintentional opening of the switch cover when the switch is ON and prevent turning the switch ON when the cover is open. The cover interlock mechanism shall have an externally operated override but the override shall not permanently disable the interlock mechanism. The tool used to override the cover interlock mechanism shall not be required to enter the enclosure in order to override the interlock.

3. Switch enclosures
a. All enclosures shall be NEMA 1 general purpose unless otherwise noted. b. Switch covers shall be attached:
1) with welded pin-type hinges (Type 1, 12, 12K, 4-4X-5 stainless steel). 2) top hinged, attached with removable screws and securable in the open position (Type 3R).
3) by molded hinges and type 316 stainless steel hinge pins (Type 4X polyester).
4) by type 316 stainless steel bolts (Type 7/9).
c. The enclosure shall be finished with:
1) gray baked enamel paint which is electrodeposited on cleaned, phosphate pre-treated steel (Type 1).
2) gray baked enamel paint which is electrodeposited on cleaned, phosphate pre-treated galvannealed steel (Type 3R, 12, 12K).
3) a brush finish on type 304 stainless steel (Type 4-4X-5 stainless steel). 4) Gray baked enamel on copper free cast aluminum alloy (Type 7/9). d. The enclosure shall have ON and OFF markings:
1) stamped into the cover (Type 1, 3R, 4-4X-5 stainless steel, 12, 12K). 2) cast into the cover (Type 7/9).
3) inked on a adhesive label (Type 4X polyester).
e. The operating handle shall be provided with a dual colored, red/black position indication.
f. All switches shall have provisions to accept up to three 3/8” hasp padlocks to lock the operating handle in the OFF position.

4. Switch ratings
a. Switches shall be horsepower rated for ac and/or dc as indicated on Drawings.

ATTACHMENT B ITEM 6
262816 - 4 City of Ceres
Water Division
b. The UL Listed short circuit current rating of the switches shall be:
1) 10,000 rms symmetrical amperes when used with or protected by Class H or K fuses (30-600A).
2) 200,000 rms symmetrical amperes when used with or protected by Class R or Class J fuses (30-600A switches employing appropriate fuse rejection schemes).
3) 200,000 rms symmetrical amperes when used with or protected by Class L fuses (800-1200A)
B. Double throw switches

1. Shall have the same characteristics as heavy-duty safety switches above for switch interior, mechanism, enclosure and rating.

2. Additional switch operating mechanism characteristics shall be:
a. quick-make, quick-break for 60A through 200A, 2 pole and 3 pole devices. b. Slow-make, slow-break for
1) 30A and greater than 200A, 2 pole and 3 pole devices. 2) 60A through 200A, 4 pole devices.

C. Individual Mounted Circuit Breakers

1. Circuit Breaker
a. Circuit breakers shall be of type, rating and poles shown on Drawings per Section 26 28 11 – Overcurrent Protection Devices.

2. Enclosure
a. Enclosure shall be galvanized steel constructed in accordance with UL 50 requirements, and be NEMA 1, unless specifically shown or specified otherwise.

PART 3 - EXECUTION

3.1 INSTALLATION
A. The equipment shall be installed per the manufacturer's recommendations.

B. Anchor safety switches to structural members and as shown on Drawings. Provide additional support as required.

C. Mount safety switches level and plumb.

ATTACHMENT B ITEM 6
262816 - 5 City of Ceres
Water Division

3.2 FIELD QUALITY CONTROL
A. Inspect complete installation prior to energizing for physical damage, proper alignment, anchorage and grounding.

B. Check tightness of bolted connections per manufacturer’s written specifications.

END OF SECTION
ATTACHMENT B ITEM 6
265000 - 1 City of Ceres
Water Division
SECTION 26 50 00

LIGHTING
PART 1 - GENERAL

1.1 SUMMARY
A. Section includes

1. Provide all labor, materials and equipment necessary to complete the installation required for the items specified under this Section, including but not limited to fixtures, lamps, standards, bases, hangers, supports, reflectors, glassware, lenses, auxiliary equipment, ballasts and sockets.

B. Related work under this section

1. Where items specified in other Division 26 sections conflict with the requirements of this Section, the most stringent requirement shall govern.

2. The requirements of this Section apply to all Division 26 work, as applicable.

3. Consult all other sections, determine the extent and character of related work and properly coordinate work specified herein with that specified elsewhere to produce a complete installation.

1.2 REFERENCES
A. Comply with the latest edition of the following applicable specifications and standards except as otherwise shown or specified:

1. ANSI -American National Standards Institute
a. C78; American National Standard for Electric Lamps
b. C81; American National Standard for Electric Lampholders c. C82; American National Standard for Lamp Ballasts
d. C136; American National Standard for Roadway and Area Lighting Equipment

2. California Codes of Regulations
a. Part 3 -California Electrical Code(CEC); NFPA 70 National Electrical Code (NEC) with California amendments
b. Part 6 -California Energy Code

3. IESNA –Illuminating Engineering Society of North America a. RP-16; Nomenclature and Definitions for Illuminating Engineering

4. NECA –National Electrical Contractors Association
ATTACHMENT B ITEM 6
265000 - 2 City of Ceres
Water Division
a. NECA/IESNA 500, Recommended Practice for Installing Indoor Commercial Lighting Systems
b. NECA/IESNA 501, Recommended Practice for Installing Exterior Lighting Systems
c. NECA/IESNA 502, Recommended Practice for Installing Industrial Lighting Systems

5. UL -Underwriter’s Laboratories, Inc.
a. 935; Standard for Fluorescent-Lamp Ballasts
b. 1029; Standard for High-Intensity-Discharge Lamp Ballasts c. 1574; Standard for Track Lighting Systems

1.3 SUBMITTALS
A. Submit manufacturer’s data for materials specified within this Section in accordance to Section 26 05 00.

B. Substituted fixtures shall be submitted with manufacturer’s specification sheet and published photometric reports, verified by testing to IES and NEMA standards under controlled laboratory conditions.

1.4 QUALITY ASSURANCE
A. All materials, equipment and parts comprising the materials specified herein shall be new and unused, bearing UL labels where applicable.

B. Installation shall conform to the following standards:

1. NECA/IESNA 500, Recommended Practice for Installing Indoor Commercial Lighting Systems

2. NECA/IESNA 501, Recommended Practice for Installing Exterior Lighting Systems

3. NECA/IESNA 502, Recommended Practice for Installing Industrial Lighting Systems

1.5 DELIVERY, STORAGE AND HANDLING
A. Handle carefully to avoid damage to internal components, enclosure and finish.

B. Store in a clean, dry environment. Maintain factory packaging and, if required, provide an additional cover to protect enclosure in harsh environments.

1.6 WARRANTY
A. Furnish one-year guarantee in accordance with and in form required under Section 26 05 00.

ATTACHMENT B ITEM 6
265000 - 3 City of Ceres
Water Division
PART 2 - PRODUCTS

2.1 GENERAL
A. Fixtures shall be of the types, wattages and voltages shown on Drawings.

B. Fixtures shall be UL listed as an entire assembly and for the installed location.

C. Fixtures’ mounting trim shall be compatible with ceiling material, coordinate with Architect Drawings for each location. Fixtures delivered which are not compatible shall be returned and replaced at Contractor’s expense.

D. Luminaire recessed in fire rated ceiling shall conform to UL Standards, equipped with yoke where in tee ceiling and field fabricated fire protection box in accordance with latest UL Fire Resistance Directory.

E. Fluorescent luminaire lenses shall be Pattern 12 of 100% virgin acrylic with 0.125” thickness except shown or specified otherwise.

F. Equip exposed fluorescent lamps with safety lamp holders or wire guard.

G. Deliver fixtures and other lighting equipment complete with suspension accessories, canopies, castings, sockets, holders, reflectors, ballasts, diffusing material, louvers, frames, and recessing boxes all wired and assembled.

H. Hangers: Swivel-type to allow for free movement of 45 degrees from vertical at canopy and at luminaire housing. Steel tube hangers shall include a 1/16-inch diameter galvanized wire cord or equivalent (100-pound break strength) in stem assembly attached to luminaire housing and building structure. Attach loop with C-type tool applied compression splice.

I. All metal halide lamp luminaires shall be the enclosed type with diffuser or lens to withstand an arc tube rupture.

J. Louvers for fluorescent luminaires which are removable for re-lamping but not hinged shall be securely fastened near each end between the fixture housing and louvers using No. 16 jack chain.

2.2 BALLASTS
A. Ballast(s) in luminaire recessed in fire rated ceiling shall be approved for such use.

B. Ballast installed indoors shall be of encapsulated type for noise control.

C. Use appropriate rated ballast in high or low temperature applications.

D. Compact fluorescent and fluorescent lamp ballasts

1. Ballasts shall be programmed rapid start.

ATTACHMENT B ITEM 6
265000 - 4 City of Ceres
Water Division

2. Ballasts shall be UL 935 listed, Class P, Type 1 Outdoor, CSA Certified where applicable.

3. The ballast shall meet or exceed ANSI C82.11, where applicable.

4. The ballast shall withstand transients specified within ANSI C62.41 Cat. A.

5. THD (Total Harmonic Distortion) shall be less than 10%.

6. Ballast power factor shall be greater than 98%.

7. The ballast shall have an audible noise rating of Class A or better.

E. High intensity discharge (HID) lamp ballasts

1. Ballasts shall be premium constant wattage (regulator stabilized) type, designed in accordance with all applicable ANSI specifications including ANSI C82.4 and UL 1029.

2. Power factor shall be greater than 90%.

3. Provide protective fusing with HID ballasts or HID fixtures.

F. Lamps

1. Provide lamps in all lighting fixtures shown.

2. Type as noted on the plans, T8 unless noted otherwise.

3. Approved manufacturers are General Electric, Osram Sylvania or equal.

PART 3 - EXECUTION

3.1 EXAMINATION
A. Locate all lighting fixtures by reference to Drawings, both electrical and architectural.

B. Report proposed changes for luminaire locations found necessary due to interference with structure, pipes, ducts, and other items to Owner’s representative for direction before installation. Luminaires specified with overall lengths are subject to change.

Adjust as directed by Owner’s representative.

C. Contractor shall be responsible to coordinate with ceiling installation trade. This will assure that proper fixture type will be furnished to match ceiling system specified.

3.2 INSTALLATION
A. Luminaires shall be properly grounded per CEC Article 410, Parts 17 through 21.

ATTACHMENT B ITEM 6
265000 - 5 City of Ceres
Water Division
B. Luminaires recessed in fire rated ceilings shall be in accordance with UL Fire Resistance Directory.

C. Install all luminaires true and plumb. Support and mount in accordance manufacturer’s instructions and with CEC Article 410, Parts 16 and 76.

D. Install recessed luminaires with separate junction box, flexible conduit, and heat-resisting wire as required by CEC. Set junction box in furred space facing luminaire for maximum accessibility. Furnish and install metal ceiling frame so luminaire can be removed without damaging finish.

E. Suspended ceiling mounting

1. Attach all light fixtures to ceiling grid runners to resist a horizontal force equal to the weight of the fixtures. Use a #10 Tek-screw or approved fastener.

2. Flush or recessed light fixtures weighing less than 56lbs. May be supported directly on runners of a heavy duty grid system, but in addition, they must have a minimum of (2) 12ga slack safety wires attached to the fixtures at diagonal corners and anchored to the structure above in the same fashion as the grid system. All 4'x4' light fixtures must have slack safety wires at each corner.

3. All flush or recessed light fixtures 56lbs. Or greater must be independently supported by not less than (4) taut 12ga wires each attached to the fixture and the structure above regardless of the grid system used. The 4 taut 12ga wires including their attachment to the structure above must be capable of supporting 4 times the fixture weight.

4. All light fixtures supported on intermediate grid system must be independently supported by not less than (4) taut 12ga wires each attached to the fixture and the structure above.

5. Support surface mounted light fixtures by at least 2 positive devices which surround the ceiling runner and which are each supported from the structure above by a 12ga wire. Spring clips or clamps that connect only to the runner are not acceptable. Provide additional supports for 8' or longer fixtures.

6. Support pendant mounted light fixtures directly from the structure above with hanger wires of cables passing through each pendant hanger & capable of supporting 4 times the fixture weight.

3.3 ADJUSTING
A. Particular care shall be used to eliminate light leaks around edge of recessed fixture trims.

ATTACHMENT B ITEM 6
265000 - 6 City of Ceres
Water Division

3.4 CLEANING
A. Clean all glass and plastic and polish all visible metal parts before submitting job to Owner’s representative for final acceptance. Remove all fingerprints and dirt from exposed surfaces. Replace scratched or damaged components.

END OF SECTION
ATTACHMENT B ITEM 6
270526 - 1 City of Ceres
Water Division
SECTION 27 05 26

GROUNDING AND BONDING FOR COMMUNICATIONS
PART 1 - GENERAL

1.1 SUMMARY
A. Section includes
a. Provide all labor, materials and equipment necessary to complete the installation required for the item specified under this Section, including but not limited to telecommunication system grounding.

B. Related sections

1. Where items specified in other Division 27 sections conflict with the requirements of this Section, the most stringent requirement shall govern.

2. The requirements of this Section apply to all Division 27 work, as applicable.

3. Consult all other sections, determine the extent and character of related work and properly coordinate work specified herein with that specified elsewhere to produce a complete installation.

1.2 REFERENCES
A. Comply with the latest edition of the following applicable specifications and standards except as otherwise shown or specified:

1. CCR –California Code of Regulations, Title 24
a. Part 3 -California Electrical Code(CEC); NFPA 70 National Electrical Code (NEC) with California amendments

2. IEEE –Institute of Electrical and Electronic Engineers a. 1100; Recommended Practices Powering and Grounding Electronic Equipment

3. NFPA –National Fire Protection Association
a. 780; Lightning Protection Code

4. TIA/EIA – Telecommunications Industry Association/Electronic Industries Alliance a. 607; Commercial Building Grounding and Bonding Requirements for Telecommunications

5. UL -Underwriters Laboratories, Inc.

ATTACHMENT B ITEM 6
270526 - 2 City of Ceres
Water Division
a. 467; Grounding and Bonding Equipment

1.3 SYSTEM DESCRIPTION
A. This Section provides for the grounding and bonding of all electrical and communication apparatus, appliances, components, fittings and accessories where required to provide a permanent, continuous, low impedance, grounded electrical system.

B. Except as otherwise indicated, the complete electrical installation including equipment and metallic raceways, boxes and cabinets shall be completely and effectively grounded in accordance with all Code requirements, whether or not such connections are specifically shown or specified.

C. Provide telecommunication system ground bus bars with each building main telecommunications equipment room or cabinet/rack location. Provide connection between the bus bar and main building reference ground bus, the ground bus of the panelboard serving power to telecommunication equipment, and all telecommunication conduit, cable trays, cable ladders and boxes.

1.4 SUBMITTALS
A. Submit manufacturer’s data for equipment and materials specified within this Section in accordance to Section 26 05 00.

1.5 QUALITY ASSURANCE
A. All materials, equipment and parts comprising the materials specified herein shall be new and unused, bearing UL labels where applicable.

PART 2 - PRODUCTS

2.1 INSULATED GROUNDING BUSHINGS
A. Plated malleable iron body with 150C molded plastic insulated throat and lay-in ground lug; OZ/Gedney BLG, Thomas & Betts #TIGB series or equal.

2.2 CONNECTIONS TO STRUCTURAL STEEL, GROUND RODS OR SPICES A. Where required by the Drawings, grounding conductors shall be spliced together, connected to ground rods or connected to structural steel using exothermic welds, Cadweld or equal, or high pressure compression type connectors, Cadweld, Thomas & Betts or equal.

2.3 BONDING JUMPERS
A. OZ/Gedney Type BJ, Thomas & Betts #3840 series or equal.

ATTACHMENT B ITEM 6
270526 - 3 City of Ceres
Water Division

2.4 GROUND CONDUCTOR
A. Ground conductor shall be #6 AWG UL labeled, Type THWN insulated copper wire, green in color.

2.5 TELECOMMUNICATION MAIN GROUNDING BUS BAR (TMGB)
A. Provide grounding bus bar at telecommunication backboards, racks and cabinets of the following type:

1. Backboards 4’X8’ and greater, floor mounted telecommunication equipment racks/cabinets larger than 60” height or wall mounted cabinets greater than 36”Wx36”H
a. Provide 1 13.5”x2”x1/4” TK copper bus bar mounted on wall with insulating stand-offs at +96” AFF. Furnish complete with cast copper alloy body Thomas Betts Series 310 or equal lugs for connecting grounding conductors.

Attach lugs to bus with appropriate size bronze bolt, flat washer and Belleville washer. All connections shall be torque, and all holes shall be drilled and tapped for single hole lugs. Provide 4 spare lugs with respective spaces.

2. Backboards less than 4’X8’, floor/wall mounted telecommunication equipment racks/cabinet less than 60” or wall mounted cabinets less than 36”Wx36”H a. Provide an aluminum loadcenter ground kit with 14 terminals minimum, General Electric TGL2 or equal. A minimum of 3 terminals shall accommodate #6 AWG. Mount within enclosure or on backboard at +96” AFF.

PART 3 - EXECUTION

3.1 INSTALLATION
A. Telecommunication system grounding

1. Bond all telecommunication conduit, cable tray, ladder rack, equipment racks and all other metallic telecommunication infrastructure components to the nearest TMGB using a #6 AWG conductor.

2. Provide #6 AWG ground within ¾” conduit from each secondary backboard, cabinet, rack, etc. to the BGB.

3. Install #6 AWG grounding conductor in nonmetallic underground raceways containing only fiber optic cable.

4. Provide an engraved nameplate mechanically fastened to wall or enclosure adjacent to each TMGB. Nameplate shall be blue with ¼” high white lettering to read “TMGB-(name of enclosure or building)”.

ATTACHMENT B ITEM 6
270526 - 4 City of Ceres
Water Division

3.2 FIELD QUALITY CONTROL
A. Contractor using test equipment expressly designed for that purpose shall perform all ground resistance tests in conformance with IEEE Standard 1100. Contractor shall submit typewritten records of measured resistance values to Engineer for review and approval prior to energizing the system.

B. Obtain and record ground resistance measurements both from electrical equipment ground bus to the ground electrode and from the ground electrode to earth. Furnish and install additional bonding and add grounding electrodes as required to comply with the following resistance limits:

1. Resistance from ground bus to ground electrode and to earth shall not exceed 5 ohms unless otherwise noted.

2. Resistance from the farthest panelboard, loadcenter, switchboard or motor control center ground bus to the ground electrode and to earth shall not exceed 20 ohms maximum.

C. Obtain and record ground resistance measurements (DC, 60Hz, 10MHz, 20MHz, 33 MHz, 66MHz and 100MHz) both from each TMGB to the ground electrode and from the ground electrode to earth.

D. Inspection

1. The Engineer or Inspector prior to encasement, burial or concealment thereto shall review the grounding electrode and connections.

END OF SECTION
ATTACHMENT B ITEM 6
270528 - 1 City of Ceres
Water Division
SECTION 27 05 28

PATHWAYS FOR COMMUNICATION SYSTEMS
PART 1 - GENERAL

1.1 SUMMARY
A. Section includes

1. Provide all labor, materials and equipment necessary to complete the installation required for the items specified under this Section, including but not limited to electrical conduits; outlet, junction and pull boxes; and related supports.

B. Related sections

1. Where items specified in other Division 27 sections conflict with the requirements of this Section, the most stringent requirement shall govern. a. 27 05 26 – Grounding and Bonding for Electrical Systems

2. The requirements of this Section apply to all Division 27 work, as applicable.

3. Consult all other sections, determine the extent and character of related work and properly coordinate work specified herein with that specified elsewhere to produce a complete installation.

1.2 REFERENCES
A. Comply with the latest edition of the following applicable specifications and standards except as otherwise shown or specified:

1. ANSI –American National Standards Institute
a. C33.91; Specification for Rigid PVC Conduit
b. C80.1; Specification Rigid Steel Conduit, Zinc-Coated c. C80.3; Specification for Electrical Metallic Tubing, Zinc-Coated d. C80.6; Intermediate Metal Conduit (IMC), Zinc-Coated

2. CCR –California Code of Regulations, Title 24
a. Part 2 -California Building Code (CBC); International Building Code (IBC) with California amendments
b. Part 3 -California Electrical Code(CEC); NFPA 70 National Electrical Code (NEC) with California amendments

3. NECA –National Electrical Contractors Association
ATTACHMENT B ITEM 6
270528 - 2 City of Ceres
Water Division
a. 101, Standard for Installing Steel Conduit (Rigid, IMC, EMT) b. 111, Standard for Installing Nonmetallic Raceways (RNC, ENT, LFNC) (ANSI)

4. NEMA –National Electrical Manufacturer’s Association a. FB 1; Fittings, Cast Metal Boxes, and Conduit Bodies for Conduit, Electrical Metallic Tubing, and Cable
b. FB 2.10; Selection and Installation Guidelines for Fittings for Use with Nonflexible Electrical Metal Conduit or Tubing (Rigid Metal Conduit, Intermediate Metal Conduit, and Electrical Metallic Tubing)
c. FB 2.20; Selection and Installation Guidelines for Fittings for Use with Flexible Electrical Conduit and Cable
d. OS 1; Sheet-Steel Outlet Boxes, Device Boxes, Covers, and Box Supports e. OS 3; Selection and Installation Guidelines for Electrical Outlet Boxes f. RN 1; Polyvinyl-Chloride Externally Coated Galvanized Rigid Steel Conduit and Electrical Metallic Tubing.
g. TC 2; Electrical Plastic Tubing and Conduit
h. TC 3; PVC Fittings for Use with Rigid PVC Conduit and Tubing i. TC 14; Reinforced Thermosetting Resin Conduit (RTRC) and Fittings

5. OSHPD Anchorage Pre-approvals
a. OPA-0003; Superstrut Seismic Restraint System
b. OPA-0114; B-Line Seismic Restraints
c. OPA-0120; Unistrut Seismic Bracing System
d. OPA-0242; Power-Strut Seismic Bracing System

6. UL –Underwriter’s Laboratories, Inc.
a. 1; Standard for Flexible Metal Conduit
b. 6; Rigid Metal Electrical Conduit
c. 360; Standard for Liquid-Tight Flexible Steel Conduit d. 514A; Metallic Outlet Boxes, Electrical
e. 514B; Fittings for Conduit and Outlet Boxes
f. 651; Schedule 40 & 80 PVC Conduit
g. 797; Electrical Metallic Tubing
h. 1242; Intermediate Metal Conduit
i. 1684; Reinforced Thermosetting Resin Conduit (RTRC) and Fittings

1.3 SYSTEM DESCRIPTION
A. Furnish, assemble, erect, install, connect and test all electrical conduits and related raceway apparatus required and specified to form a complete installation.

1.4 SUBMITTALS
ATTACHMENT B ITEM 6
270528 - 3 City of Ceres
Water Division
A. Submit manufacturer’s data for materials specified within this Section in accordance to Section 26 05 00.

1.5 QUALITY ASSURANCE
A. All materials, equipment and parts comprising the materials specified herein shall be new and unused, bearing UL labels where applicable.

B. Installation shall conform to the NECA installation guidelines unless otherwise indicated within this Section
PART 2 - PRODUCTS

2.1 MATERIALS
A. Conduits and Fittings

1. Rigid steel conduit (RMC)
a. Conduit: Standard weight, mild steel pipe, and zinc coated on both inside and outside by a hot dipping or shearardizing process manufactured in accordance with UL 6 and ANSI C80.1 specifications.
b. Fittings (couplings, elbows, bends, etc.)
1) Shall be steel or malleable iron.
2) Coupling and unions shall be threaded type, assembled with anti-corrosion, conductive and anti-seize compound at joints made absolutely tight to exclude water.
c. Bushings
1) Insulating bushings: Threaded polypropylene or thermosetting phenolic rated at 150C minimum.
2) Insulating grounding bushing: Threaded cast body with insulating throat and steel “lay-in” ground lug.
3) Insulating metallic bushing: Threaded cast body with plastic insulated throat rated at 150C minimum.

2. Coated rigid steel conduit (CRMC)
a. Conduit: Equivalent to RMC with a Polyvinyl chloride (PVC) coated bonded to the galvanized outer surface of the conduit. The bonding between the PVC coating and conduit surface shall be ETL PVC-001 compliant. The coating thickness shall be a minimum of 40mil.

ATTACHMENT B ITEM 6
270528 - 4 City of Ceres
Water Division
b. Fittings (couplings, elbows, bends, etc.)
1) Equivalent to RMC above with bonded coating same as conduit. 2) The PVC sleeve over fittings shall extend beyond hub or coupling approximately one diameter or 1 1/2” whichever is smaller. c. Bushing equivalent to RMC above.

3. Intermediate metallic conduit(IMC)
a. Conduit: Intermediate weight, mild steel pipe, meeting the same requirements for finish and material as rigid steel conduit manufactured in accordance with UL 1242 and ANSI C80.6 specifications.
b. Fittings (couplings, elbows, bends, etc.) equivalent to RMC above. c. Bushing equivalent to RMC above.

4. Electrical metallic tubing (EMT)
a. Conduit: Cold rolled steel tubing with zinc coating on outside and protective enamel on inside manufactured in accordance with UL 797 and ANSI C80.3 specifications.
b. Couplings: Steel or malleable iron with compression type fastener via a nut. c. Connectors: Steel or malleable iron with compression type fastener via a nut with plastic insulated throat rated at 150C minimum.

5. Rigid non-metallic conduit (PVC)
a. Conduit: PVC composed Schedule 40, 90C manufactured in accordance with NEMA TC 2 and UL 651 specifications.
b. Fittings: Molded PVC, slip on solvent welded type in accordance to NEMA TC 3.

6. Reinforced thermosetting resin conduit (RTRC)
a. Conduit: Fiber impregnated with a cured thermosetting resin compound in accordance with NEMA TC 14 and UL1684.
b. Fittings: Molded resin with glass reinforcement manufactured in the same process as the conduit bonded with an epoxy adhesive.

7. Flexible metallic conduit (FMC)
a. Conduit: Continuous, flexible steel spirally wound with zinc coating on both inside and outside in accordance with UL 1.
b. Connectors: Steel or malleable iron with compression type fastener via a nut with plastic insulated throat rated at 150C minimum.

8. Liquidtight flexible metallic conduit (LFMC)
a. Conduit: PVC coated, continuous, flexible steel spirally wound with zinc coating on both inside and outside in accordance with UL 360.

ATTACHMENT B ITEM 6
270528 - 5 City of Ceres
Water Division
b. Connectors: Steel or malleable iron with compression type fastener via a nut with plastic insulated throat rated at 150C minimum.

9. Miscellaneous Fittings and Products
a. Conduit sealing bushings: Steel or cast malleable iron body and pressure clamps with PVC sleeve, neoprene sealing grommets and PVC coated steel pressure rings. Supplied with neoprene sealing rings between body and PVC sleeve.
b. Watertight cable terminators: One piece, compression molded sealing ring with PVC coated steel pressure disks, stainless steel screws and zinc plated cast iron locking collar.
c. Watertight cable/cord connectors: Liquidtight steel or cast malleable iron body with sealing neoprene bushing and stainless steel retaining ring. d. Expansion fittings: Multi-piece unit of hot dip galvanized malleable iron or steel body and outside pressure bussing design to allow a maximum of 4” movement (2” in either direction). Furnish with external braid tinned copper bonding jumper. UL listed for both wet and dry locations. e. Expansion/deflection couplings: Multi-piece unit comprised of a neoprene sleeve, internal flexible tinned copper braid attached to bronze end couplings with stainless steel bands. Coupling to provide minimum of 3/4” movement and 30 degrees deflection from normal. UL listed for both wet and dry locations.
f. Conduit bodies: Raintight, malleable iron, hot-dip galvanized body with threaded hubs, stamped steel cover, stainless steel screws and neoprene gasket.
g. Other couplings, connectors and fittings shall be equal in quality, material and construction to items specified herein.

B. Boxes

1. Outlet boxes
a. Standard: Galvanized one-piece of welded pressed steel type in accordance with NEMA OS 1 and UL 514. Boxes shall not be less than 4” square and at least 1 1/2” deep.
b. Concrete: Galvanized steel, 4” octagon ring with mounting lug, backplate and adapter ring type in accordance with NEMA OS 1 and UL 514. Depth as required by application.
c. Masonry: Galvanized steel, 3.75” high gang box in accordance with NEMA OS 1 and UL 514.
d. Surface cast metal: Cast malleable iron body, surface mounted box with threaded hubs and mounting lugs as required in accordance with NEMA OS 1 and UL 514. Furnish with ground flange, steel cover and neoprene gasket.

2. Pull and junction boxes
a. Sheet metal boxes: Standard or concrete outlet box wherever possible; otherwise use 16 gauge galvanized sheet metal, NEMA 1 box sized per CEC with machine screwed cover.

ATTACHMENT B ITEM 6
270528 - 6 City of Ceres
Water Division
b. Cast metal boxes: Install standard cast malleable iron outlet or device box when possible.
c. Flush mounted boxes: Install overlapping cover with flush head screws. d. In-ground mounted pull holes/boxes: Install pre-cast concrete box, sized per Drawing or CEC with pre-cast or traffic rated lid.

3. Floor boxes
a. Floor boxes shall be adjustable, cast metal body with threaded conduit openings, adjustable rings, brass flange or Lexan ring and cover plate with threaded plug. Include provisions to accommodate surface mounted telephone or receptacle outlet, or flush floor mounted telephone or receptacle outlet where shown on Drawings.

C. Pull line/cord

1. Polypropylene braided line or Let-line #232 or equal of 1/8” diameter with a minimum break strength of 200 pounds.

PART 3 - EXECUTION

3.1 EXAMINATION
A. Thoroughly examine site conditions for acceptance of wire and cable installation to verify conformance with manufacturer and specification tolerances. Do not commence with work until all conditions are made satisfactory.

3.2 PREPARATION
A. Conduit

1. Provide all necessary conduit fittings, connectors, bushings, etc. required to complete conduit installation to meet the CEC/NEC and intended application whether noted, shown or specified within.

2. Location of conduit runs shall be planned in advance of the installation and coordinated with other trades.

3. Where practical, install conduits in groups in parallel vertical or horizontal runs that avoid unnecessary offsets.

4. All conduits shall be parallel or at right angles to columns, beams and walls whether exposed or concealed.

5. Conduits shall not be placed closer than 12” to a flue, parallel to hot water, steam line or other heat sources; or 3” when crossing perpendicular to the above said lines when possible.

6. Install exposed conduit as high as practical to maintain adequate headroom. Notify Engineer if headroom will be less than 102”.

7. Do not obstruct spaces required by Code in front of electrical equipment, access doors, etc.

ATTACHMENT B ITEM 6
270528 - 7 City of Ceres
Water Division

8. The largest trade size conduit in concrete floors and walls shall not exceed 1/3 thickness or be spaced a less than three conduit diameters apart unless permitted by Engineer. All conduits shall be installed in the center of slab or wall, and never between reinforcing steel and bottom of floor slab.

9. Install additional pull boxes, not shown on Drawings, in sufficient quantities to facilitate pulling of conductors and cables such that total spacing does not exceed 150 feet or 270 degrees, total; and maximum pulling tension will not be exceeded.

10. When installing underground conduits to specified depth; depth shall be taken from finished grade as it will be at project completion. Should finish grade be above existing grade by an amount equal to or greater than specified depth, conduit shall be installed not less than 6” below existing grade.

11. Verify that information concerning finish grade is accurate, for should the underground run be less than the specified depth, Contractor may be required to re-install conduit to meet the required depth.

12. Unless otherwise specified, underground conduits shall be installed with top side not less than 24” below finished grade; this depth applies to all conduits outside of building foundations including those under walks, open corridors or paved areas.

13. Utility company service conduits installation depth shall be as directed by their respective specifications and requirements.

B. Boxes

1. Before locating outlet boxes, check Construction Documents for type of construction and make sure that there is no conflict with other equipment. Locate outlet boxes as shown and locate so as not to interfere with other Work or equipment.

2. Install all outlet boxes flush within walls, ceiling and floors except where installed within non-finished rooms, cabinetry, attic spaces or as indicated on Drawings.

3. Locate pull boxes and junction boxes within concealed, accessible locations where possible.

4. Do not install outlet boxes back-to-back with same stud space. Where shown back-to-back, offset as required, and fill void with sound dampening material where requested by Owner.

5. In fire rated walls separate boxes by 24” minimum and with stud member.

6. Adjust position of outlet boxes within masonry wall to accommodate course lines.

3.3 INSTALLATION
A. Conduit

1. Minimum conduit size shall be 3/4” unless otherwise indicated.

2. All conduit work shall be concealed unless otherwise indicated. Exposed conduits shall be permitted within unfinished rooms/spaces to facilitate installation.

3. Install conduit in complete runs prior to installing conductors or cables.

4. Make long radius conduits bends free from kink, indentations or flattened surfaces.

Make bends carefully to avoid injury or flattening. Bends 1 1/4” size and larger shall be factory made ells, or be made with a manufactured mechanical bender.

Heating of steel conduit to facilitate bending or that damage galvanized coating will not be permitted.

ATTACHMENT B ITEM 6
270528 - 8 City of Ceres
Water Division

5. Remove burrs and sharp edges at end of conduit with tapered reamer.

6. Protect and cover conduits during construction with metallic bushings and bushing “pennies” to seal exposed openings.

7. Assemble conduit threads with anti-corrosion, conductive, anti-seize compound and tighten securely.

8. Install conduits shall that no traps to collect condensation exist.

9. Fasten conduit securely to boxes with locknuts and bushings to provide good grounding continuity.

10. Install pull cords/line within any spare or unused conduits of sufficient length to facilitate future cable installation.

11. Penetrations
a. Locate penetrations within structural members as shown on Drawings and as directed by Architect or Engineer. Should it be necessary to notch any framing member, make such notching only at locations and in a manner as approved by Engineer.
b. Do not chase concrete or masonry to install conduit unless specifically approved by Engineer.
c. Cutting or holes
1) Install sleeves for cast-in-place concrete floors and walls. After installing conduit through penetration, seal using dry-pack grouting compound (noniron bearing, chloride free and non-shrinking) or fire rated assembly if rated floor or wall. Use escutcheon plate on floor underside to contain compound as necessary.
2) Cut holes with a hole saw for penetrations through non-concrete or nonmasonry members. 3) Provide chrome plated escutcheon plates at all publicly exposed wall, ceiling and floor penetrations.
d. Sealing
1) Non-rated penetration openings shall be packed with non-flammable insulating material and sealed with gypsum wallboard taping compound. 2) Fire rated penetration shall be sealed using a UL classified fire stop assembly suitable to maintain the equivalent fire rating prior to the penetration.
3) Use escutcheon plates to hold sealing or fire rated compound as necessary.
e. Waterproofing
1) Make penetrations through any damp-proofed/waterproofed surfaces within damp/wet locations as such as to maintain integrity of surface. 2) Install specified watertight conduit entrance seals at all below grade wall and floor penetrations.
3) At roof penetrations furnish roof flashing, counter flashing and pitchpockets compatible to roof assembly. 4) Where possible conduits that horizontally penetrate a waterproof membrane shall fall away from and below the penetration’s exterior side.

ATTACHMENT B ITEM 6
270528 - 9 City of Ceres
Water Division
5) Make penetrations through floors watertight with mastic, even when concealed within walls or furred spaces.

12. Supports
a. Conduits shall be support and braced per OSHPD pre-approved anchorage systems when those methods are implemented and installed. b. Sizes of rods and cross channels shall be capable of supporting 4 times and 5 times actual load, respectively. Anchorage shall support the combined weight of conduit, hanger and conductors.
c. Support individual horizontal conduit 1 1/2” and smaller by means of 2 hole straps or individual hangers.
d. Galvanized iron hanger rods sizes 1/4” diameter and larger with spring steel fasteners, clips or clamps specifically design for that purpose for 1 1/2” conduits and larger.
e. Support multi-parallel horizontal conduits runs with trapeze type hangers consisting of 2 or more steel hanger rods, preformed cross channels, ‘J’ bolts, clamps, etc.
f. Support conduit to wood structures by means of bolts or lag screws in shear, to concrete by means of insert or expansion bolts and to brickwork by means of expansion bolts.
g. Support multi-parallel vertical conduits runs with galvanized Unistrut, PowerStrut or approved equal type supports anchored to wall. Where multi-floored conduits pass through floors, install riser clamps at each floor. h. Maximum conduit support spacing shall be in accordance with NECA Standard of Installation:
1) Horizontal runs:
a) 3/4” and smaller at 60” on centers, unless building construction prohibits otherwise, then 84” on centers.
b) 1” and larger at 72” on centers, unless building construction prohibits otherwise or any other condition, then 120” on centers. 2) Vertical runs:
a) 3/4” and smaller @ 84” on centers.
b) 1” and 1 1/4” @ 96” on centers.
c) 1 1/2” and larger @ 120” on centers.
d) Any vertical condition such as shaftways and concealed locations for any sized conduit, 120” on centers.
i. Anchorage for RMC/IMC supports unless otherwise specified:
1) < 1” IMC/RMC = #10 bolt/screw.
2) 1” IMC/RMC = 1/4” bolt/screw.
3) 1 1/2” and 2” IMC/RMC = 3/8” bolt/screw.
4) 3” IMC/RMC, 4” EMT = 1/2” bolt/screw.
5) > 3” IMC/RMC = 5/8” bolt/screw.

ATTACHMENT B ITEM 6
270528 - 10 City of Ceres
Water Division
j. Anchorage for EMT supports unless otherwise specified:
1) < 1 1/2” EMT = #10 bolt/screw.
2) 1 1/2” EMT = 1/4” bolt/screw.
3) 2, 2 1/2” and 3” EMT = 3/8” bolt/screw.
4) 4” EMT = 1/2” bolt/screw.
5) > 4” EMT = 5/8” bolt/screw.

B. Boxes

1. Install boxes as shown on Drawings and as required for splices, taps, wire pulling, equipment connections and Code compliance.

2. Install additional pull boxes, not shown on Drawings, in sufficient quantities to facilitate pulling of conductors and cables such that total spacing does not exceed 150 feet or 270 degrees, total; and maximum pulling tension will not be exceeded.

3. Install plaster rings on all outlet boxes in stud walls or in furred, suspended or exposed ceilings. Covers shall be of a depth suited for installation.

4. Provide gasketed cast metal cover plates where boxes are exposed in damp or wet locations

5. Install access door for boxes installed within concealed locations without access.

6. Install approved factory made knockout seal where knockouts are not present.

7. Refer to Architectural interior elevations and details shown for exact mounting heights of all electrical outlets. In general, locate outlets as shown or specific and complies with Americans with Disabilities Act:
a. Convenience outlets: +18”AFF or +6” above counter or splash. b. Local switches: +48”AFF or +6” above counter or splash. c. Telecommunication outlets: +18”AFF or +48”AFF for wall telephone or intercom device.
d. Verify all mounting heights with Architectural Drawings, and where heights are not suited for construction or finish please consult Engineer or Architect.

8. Use conduit bodies to facilitate pulling of conductor or cables or change conduit direction. Do not splice within conduit bodies.

9. Enclose pull box with additional rated gypsum board as necessary to maintain wall’s original fire rating.

10. Install galvanized steel coverplates on all open boxes within dry listed areas.

11. Install in-ground pull holes/boxes flush to grade finish at finished areas or 1” above finished landscaped grade. Seal all conduits terminating in pull hole/box watertight. Install and grout around bell ends where shown. Cover and lids shall be removable without damage to adjacent finish surfaces.

12. Support
a. Accurately place boxes for finish, independently and securely supported by adequate blocking or manufacturer channel type heavy-duty box hangers for stud walls. Do not use nails to support boxes.
b. Support boxes independent of conduit system.
c. Mount boxes installed within ceilings to 16 gauge metal channel bars attached to main runners or joists.

ATTACHMENT B ITEM 6
270528 - 11 City of Ceres
Water Division
d. Support boxes within suspended acoustical tile ceilings directly from structure above when light fixture are to be installed from box. e. Use auxiliary plates, bar or clips and grouted in place for masonry, block or pour-in-place concrete construction.

3.4 APPLICATION
A. Conduit

1. RMC/IMC suitable for all damp, dry and wet locations except when in contact with earth. IMC not suitable for hazardous locations as stated within CEC/NEC.

2. CRMC suitable for damp or wet locations, concealed within concrete or in contact with earth.

3. EMT suitable for exposed or concealed dry, interior locations.

4. PVC/RTRC suitable for beneath ground floor slab, except when penetrating, and direct earth burial. Do not run exposed within concrete walls or in floor slab unless indicated on Drawings or per Engineer’s permission.

5. FMC suitable for dry locations only for connections to motors, transformers, vibrating equipment/machinery, controllers, valves, switches and light fixtures in less than 6 foot lengths.

6. LFMC application same as FMC above but for damp or wet locations.

B. Termination and joints

1. Use raceway fittings compatible with associated raceway and suitable for the location.

2. Raceways shall be joined using specified couplings or transitions where dissimilar raceway systems are joined.

3. Conduits shall be securely fastened to cabinets, boxes and gutters using (2) two locknuts and insulating bushing or specified insulated connector. Where joints cannot be made tight and terminations are subject to vibration, use bonding jumpers, bonding bushings or wedges to provide electrical continuity of the raceway system. Use insulating bushings to protect conductors where subjected to vibration or dampness. Install grounding bushings or bonding jumpers on all conduits terminating at concentric or eccentric knockouts.

4. Terminations exposed at weatherproof enclosures and cast outlet boxes shall be made watertight using specified connectors and hubs.

5. Stub freestanding equipment conduits through concrete floors for connections with top of coupling set flush with finished floor. Install plugs to protect threads and entrance of debris.

6. Install specified cable sealing bushings on all conduits originating outside the building walls and terminating within interior switchboard, panel, cabinet or gutters.

Install cable sealing bushings or raceway seal for conduit terminations in all grade level or below grade exterior pull, junction or outlet boxes.

7. Where conduits enter building from below grade inject into filled raceways preformulated rigid 2 lbs. density polyurethane foam suitable for sealing against water, moisture, insects and rodents.

ATTACHMENT B ITEM 6
270528 - 12 City of Ceres
Water Division

8. Install expansion fitting or expansion/deflection couplings per manufacturer’s recommendations where:
a. Any conduit that crosses a building structure expansion joint; secure conduit on both sides to building structure and install expansion fitting at joint. b. Any conduit that crosses a concrete expansion joint; install expansion/deflection at joint.
c. Any conduit greater than 1-1/4” is routed along roof top in runs greater than 100 feet; install expansion fittings every 100 feet.
d. Engineer may allow FMC or LFMC in lieu of expansion fitting or expansion/deflection couplings on conduits 2” and smaller within accessible locations upon further review and written consent.

C. Boxes

1. Standard type suitable for all flush installations and all dry concealed locations.

2. Concrete type suitable for all flush concrete installations.

3. Masonry type suitable for all flush concrete and block installations.

4. Surface cast meta type suitable for all exposed damp and wet surface mounted locations, and dry surface mounted locations less than 96” from finished floor

END OF SECTION
ATTACHMENT B ITEM 6
271116 - 1 City of Ceres
Water Division
SECTION 27 11 16

DATA RACKS AND ENCLOSURES
PART 1 - GENERAL

1.1 SUMMARY
A. Section includes

1. Provide all labor, materials and equipment necessary to complete the installation required for the items specified under this Section, including but not limited to telecommunication cabinets, racks and enclosures.

B. Related sections

1. Where items specified in other Division 27 sections conflict with the requirements of this Section, the most stringent requirement shall govern. a. 27 05 26 – Grounding and Bonding for Communications

2. The requirements of this Section apply to all Division 27 work, as applicable.

3. Consult all other sections, determine the extent and character of related work and properly coordinate work specified herein with that specified elsewhere to produce a complete installation.

1.2 REFERENCES
A. Comply with the latest edition of the following applicable specifications and standards except as otherwise shown or specified:

1. CCR –California Code of Regulations, Title 24
a. Part 2 -California Building Code (CBC); International Building Code (IBC) with California amendments

2. EIA –Electronic Industries Alliance
a. 310; Cabinets, Racks, Panels, and Associated Equipment

3. UL -Underwriters Laboratories, Inc.
a. 1863; Standard for Communications-Circuit Accessories ATTACHMENT B ITEM 6
271116 - 2 City of Ceres
Water Division

1.3 SUBMITTALS
A. Submit manufacturer’s data for grounding materials specified within this Section in accordance to Section 26 05 00.

1.4 QUALITY ASSURANCE
A. All materials, equipment and parts comprising the materials specified herein shall be new and unused, bearing UL labels where applicable.

PART 2 - PRODUCTS

2.1 EQUIPMENT ENCLOSURE SYSTEMS
A. General:

1. Provide type, size and quantity as shown on Drawings. Unless otherwise noted, completely enclose interior of enclosure, or ensembles of enclosures with equipment, blank or vent panels, including sides and top. Provide rear access door except at enclosures flush with the wall behind or enclosures which are portable.

2. Provide enclosure systems conforming to the latest CBC requirements for seismic design.

3. The drawings show a scheme of heat management based on generic conventionally packaged components to convey design intent. Coordinate fans, blank panels, vent panels and related heat management provisions with products provided.

4. Equipment Enclosures: Provide each bay with basic frame and pairs of adjustable mounting angles located at front and rear of each bay, angles tapped #10-32, EIA 310-D universally spaced. At each bay, provide pontoon base, solid top panel and with fan where noted or scheduled and locking rear door. Except where otherwise indicated, at each ensemble of bays, provide end (side) panels to provide complete enclosure.

B. Intermediate Distribution Enclosure

1. Drawing Reference: WE##, where ## indicates minimum quantity of rack unit spaces.

2. Construction
a. Wall mounted, three part sectional, with:
1) Fixed mount wall terminal section.
2) Double hinge design for independent opening/motion of front door and main body.
3) Plexiglas locking front door with 16 gauge steel wall or as shown on Drawings.

ATTACHMENT B ITEM 6
271116 - 3 City of Ceres
Water Division
b. Fully-adjustable 19” rails.
c. Combined depth of swing-away center section and fixed rear section to be not less than 24”.
d. Provide lockable hasp to secure rack sections. Owner will supply padlock. e. Enclosure shall be phosphate pre-treated and finished in a durable black powder coat finish.
f. Opening, 4” minimum for exhaust fan mounting on main body section.

Provide fan and thermostat as described within this Section. g. Manufacturers
1) Rittal EL Series, B-Line E2 Series or approved equal.

C. Intermediate Distribution Cabinet

1. Drawing Reference: WC##, where ## indicates minimum quantity of rack unit spaces.

2. Construction
a. Wall mounted, two piece design, with:
1) Fixed mount wall terminal section.
2) Solid locking front door with 16 gauge steel construction. b. Provision for enclosed, integrated duplex receptacle when shown on Drawings.
c. Enclosure shall be phosphate pre-treated and finished in a durable black powder coat finish.
d. Opening, 4” minimum for exhaust fan mounting. Provide fan and thermostat as described within this Section.
e. Manufacturers
1) Hubbell Rebox series, Chatsworth ThinLine II or approved equal.

D. Full Height Equipment Relay Rack, Two Post System

1. Drawing Reference: 2RR##, where ## indicates minimum quantity of rack unit spaces.

2. Construction
a. Channels shall be 12 gauge steel minimum with #10-32 mounting holes. b. Rack shall be phosphate pre-treated and finished in a durable black powder coat finish.

3. Manufacturers
a. Hubbell, Chatsworth, B-Line or approved equal.

E. Full Height Equipment Relay Rack, Four Post System

1. Drawing Reference: 4RR##, where ## indicates minimum quantity of rack unit spaces.

ATTACHMENT B ITEM 6
271116 - 4 City of Ceres
Water Division

2. Construction
a. Channels shall be 12 gauge steel minimum with #10-32 mounting holes. b. Rack shall be phosphate pre-treated and finished in a durable black powder coat finish.

3. Manufacturers
a. Hubbell, Chatsworth, B-Line or approved equal.

F. Full Height Equipment Enclosure

1. Drawing Reference: FE##, where ## indicates minimum quantity of rack unit spaces.

2. Construction
a. Channels shall be 12 gauge steel minimum with #10-32 mounting holes. All steel panels and door shall be 16 gauge CRS minimum.
b. Enclosure shall be phosphate pre-treated and finished in a durable black powder coat finish.
c. Removable front and rear locking doors with universal swing capability.

Provide front Plexiglas door and rear steel, vented unless noted otherwise on Drawings.
d. Field removable steel side panels.
e. Install top panel with 2 openings minimum for exhaust fan mounting. Provide 2 fans and thermostat as described within this Section. Install wire guards over unused openings.
f. Adjustable feet for leveling.
g. Capable, with proper option, to comply with CBC Zone 4 seismic requirements.
h. EIA 310-D compliant and UL listed.

3. Manufacturers
a. Hubbell, Chatsworth, B-Line or approved equal.

2.2 RACK PANELS AND ACCESSORIES:

A. Rack Mounting Screws:

1. Screws 10-32; length as required for at least ¼” excess when fully seated; oval head with black plastic non marring cup washer or equivalent ornamental head; nickel, cadmium or black plated; Phillips, Allen Hex, Square-Tip or Torx drive.

Slotted screws are not acceptable.

B. Vertical Wire Management Section:

1. All Steel construction with black finish.

2. Total cross-sectional area of vertical tray shall be greater than 26 square-inches.

3. Universal hole pattern to bolt to rack channel.

ATTACHMENT B ITEM 6
271116 - 5 City of Ceres
Water Division

4. Provide matching de-attachable front covers.

5. Manufacturers
a. Panduit, Hubbell or approved equal.

C. Horizontal Wire Management Panel (1 or 2 Rack Unit(s)):

1. All Steel construction with black finish.

2. Panel without cover will not be accepted.

3. Manufacturers
a. Panduit, Hubbell or approved equal.

D. Blank Panels:

1. Flanged steel construction with black finish.

2. Manufacturers
a. Middle Atlantic Products, Atlas/Soundolier or approved equal.

E. Vent Panels:

1. Flanged steel construction with black finish.

2. Manufacturers
a. Middle Atlantic Products, Atlas/Soundolier or approved equal.

2.3 EQUIPMENT ENCLOSURE VENTILATION:

A. Enclosure exhaust fan

1. Characteristics
a. UL labeled 4 ½” diameter fan of smooth ball bearing design. b. Electrical: 115Vac, 60Hz
c. Air flow: approximately 50CFM
d. Sound level: <40dBA

2. Supply metal wire guard where exposed.

3. Manufacturers
a. Comair Rotron, Rittal or approved equal.

B. Enclosure thermostat

1. Characteristics
a. UL labeled device with bi-metal temperature sensitive element. b. Temperature control range from +10C to +60C
c. Electrical
ATTACHMENT B ITEM 6
271116 - 6 City of Ceres
Water Division
1) Requirements: 115Vac, 60Hz
2) Output Contact: 1A minimum at 120Vac

2. Manufacturers
a. Rittal, Honeywell or approved equal.

2.4 EQUIPMENT ENCLOSURE POWER, PROTECTION AND SIGNAL GROUNDING A. Receptacle Strip, One (1) Circuit.

1. Features/Construction:
a. Receptacles
1) Outlets shall be NEMA 5-15R with isolated ground.
2) Provide 1 duplex receptacle for every 12” of rack height with no fewer than 2 and no greater than 7 duplex receptacles for any one rack/enclosure. b. Power strip shall be ready for hardwire installation with junction box or 36” minimum flexible whip connection.
c. All steel construction with durable powder coat finish. d. UL labeled.
e. Provide mounting hardware as necessary to rack chassis.

2. Acceptable
a. Middle Atlantic Products, Wiremold or approved equal.

PART 3 - EXECUTION

3.1 INSTALLATION
A. Combustible material, other than incidental trim of indicated equipment, is prohibited within equipment racks.

B. Access shall not require de-mounting or de-energizing of equipment. Install access covers, hinged panels or pull-out drawers as required to insure complete access to terminals and interior components.

C. Provide adequate work room clearances per CEC Article 110.

D. Provide permanent labels for all equipment devices installed within rack(s)/enclosure(s).

E. Ventilation System

1. Connect thermostat and exhaust fans to enclosure’s receptacle/branch circuit, and comply with CEC for wiring and overcurrent protection.

ATTACHMENT B ITEM 6
271116 - 7 City of Ceres
Water Division

2. Mount thermostat at rear of enclosure, closest to top of either one third the distance from enclosure top or highest mounted active hardware component.

3. Set thermostat at +32C (+90F).

F. Anchorage wall and floor mounted racks/enclosures to structural members to withstand seismic forces based upon rack/enclosure’s maximum load capacity.

END OF SECTION
ATTACHMENT B ITEM 6
271513 - 1 City of Ceres
Water Division
SECTION 27 15 13

COPPER TELECOMMUNICATIONS/DATA CABLING AND DEVICES
PART 1 - GENERAL

1.1 SUMMARY
A. Section includes

1. Provide all labor, materials and equipment necessary to complete the installation required for the items specified under this Section, including but not limited to copper data communication cabling systems and copper based telecommunication, which include.
a. Category 6 cabling
1) Provide scheduled station plates at each indicated location. Provide labeled Category 6 modules in the plates, and document per Specifications.
2) Homerun all station cabling from each universal Category 6 data jack to the indicated MDF or IDF.
3) Provide Category 6 patch panels where indicated. Terminate and test Category 6 cabling as detailed within the Specifications. 4) Terminate, test and document Category 5E cabling as detailed within the Specifications.
b. Category 3, RUS (REA) and USOC telephone cabling
1) Provide scheduled station plates at each indicated location. 2) Homerun all station cabling from each telephone jack to indicated cabinet/telephone backboard.
3) Provide punch blocks as necessary; terminate and test as detailed within the Specifications.

B. Related sections

1. Where items specified in other Division 27 sections conflict with the requirements of this Section, the most stringent requirement shall govern. a. 27 05 26 – Grounding and Bonding for Communications
b. 27 11 16 – Data Racks and Enclosures
c. 27 05 28 – Pathways for Communication System

2. The requirements of this Section apply to all Division 27 work, as applicable.

3. Consult all other sections, determine the extent and character of related work and properly coordinate work specified herein with that specified elsewhere to produce a complete installation.

ATTACHMENT B ITEM 6
271513 - 2 City of Ceres
Water Division

1.2 REFERENCES
A. Comply with the latest edition of the following applicable specifications and standards except as otherwise shown or specified:

1. ANSI –American National Standards Institute
a. ISO/IEC 11801; Information technology - Generic cabling for customer premises

2. CCR –California Code of Regulations, Title 24
a. Part 3 -California Electrical Code(CEC); NFPA 70 National Electrical Code (NEC) with California amendments

3. CFR –Code of Federal Regulations
a. Title 7 –Agriculture, Part 1755 – Telecommunications Standards and Specifications for Materials, Equipment and Construction b. Title 47 –Telecommunication, Part 68 – Connection of Terminal Equipment to the Telephone Network.

4. TIA/EIA – Telecommunications Industry Association/Electronic Industries Alliance a. Wiring/Cabling Standards
1) TIA/EIA-568-B.1; Commercial Building Telecommunications Cabling Standard - Part 1: General Requirements
2) TIA/EIA-568-B.2; Commercial Building Telecommunications Cabling Standard - Part 2: Balanced Twisted Pair Cabling Components 3) TIA/EIA-569-A; Commercial Building Standards for Telecommunications Pathways and Spaces
4) TIA/EIA-606; Administration Standard for the Telecommunications Infrastructure of Commercial Buildings
5) TIA/EIA/IS-729; Technical Specifications for 100 Ohm Screened TwistedPair Cabling 6) TIA/EIA-758; Customer Owned Outside Plant Telecommunications Cabling Standard
7) TSB67; Transmission Performance Specifications for Field Testing of Unshielded Twisted-Pair Cabling Systems
8) TSB95; Additional Transmission Performance Guidelines for 4-Pair 100 Category 5 Cabling

5. ICEA –Insulated Cable Engineers Association
a. S-56-434; Polyolefin Insulated Communications Cables for Outdoor Use b. S-80-576; Category 1 & 2 Individually Unshielded Twisted Pair Indoor Cables for Use in Communications Wiring Systems
c. S-90-661; Category 3, 5, & 5e Individually Unshielded Twisted Pair Indoor Cable for Use in General Purpose and LAN Communication Wiring Systems ATTACHMENT B ITEM 6
271513 - 3 City of Ceres
Water Division
d. S-101-699; Standard for Category 3 Individually Unshielded Twisted Pair Indoor Cable for Use in General Purpose Non-Lan Telecommunication Wiring Systems

6. IEEE –Institute of Electrical and Electronic Engineers a. C2; National Electrical Safety Code (NESC)
b. 802.3; Information Technology -Local and Metropolitan Area Networks c. 820; Standard Telephone Loop Performance Characteristics

7. NECA –National Electrical Contractors Association
a. NECA/BICSI 568; Standard for Installing Commercial Building Telecommunications Systems

8. UL –Underwriters Laboratories, Inc.
a. 444; Communications Cables
b. 497; Standard for Protectors for Paired-Conductor Communications Circuits c. 1581; Reference Standard for Electrical Wires, Cables, and Flexible Cords d. 1666; Standard Test for Flame Propagation Height of Electrical and OpticalFiber Cables Installed Vertically in Shafts e. 1685; Standard for Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables
f. 1863; Standard for Communications-Circuit Accessories

9. U.S. Department of Agriculture, Rural Utilities Service (RUS), formerly Rural Electrification Administration (REA) Standards
a. PC-2; Splicing Plastic Insulated Cables
b. PC-4; Acceptance Tests and Measurements of Telephone Plant c. PE-22; Aerial and Underground Telephone Cable
d. PE-33; Shield Bonding Connectors
e. PE-39; Filled Telephone Cables
f. PE-52; Telephone Cable Splicing Connectors
g. PE-60; Trunk Carrier Systems
h. PE-74; Filled Splice Closures
i. PE-87; Terminating (TIP) Cable
j. PE-89; Filled Telephone Cable with Expanded Insulation k. TE&CM Section 644; Design and Construction of Underground Cable

1.3 SYSTEM PERFORMANCE STANRDARDS
A. Voice copper plant

1. To Universal Service Ordering Code (USOC) Standards (CFR Title 47, Part 68, Subpart F, Section 68.502) and other appropriate authorities.

2. Where voice plant cabling is specified for connection to RJ-11 or RJ-14 jacks conform to USOC and Category 3 standards as demonstrated using the appropriate test equipment.

ATTACHMENT B ITEM 6
271513 - 4 City of Ceres
Water Division
B. Category 6 copper cabling plant:

1. To applicable EIA/TIA standards using a digital cable analyzer as specified herein.

1.4 SUBMITTALS
A. Submit manufacturer’s data for materials specified within this Section in accordance to Section 26 05 00.

1.5 QUALITY ASSURANCE
A. All materials, equipment and parts comprising the materials specified herein shall be new and unused, bearing UL labels where applicable.

B. Installer Qualifications

1. The work performed under this Section shall be certified by the manufacturer of the equipment and components being furnished and be authorized by the manufacturer to install and convey the product warranty and performance guarantee to the Owner upon completion of Contract.

2. Installing Contractor must have a minimum of three years previous experience in data communications and/or telecommunication systems installation. All Contractors and/or Vendors supplying all or parts of the work described herein shall supply three project references within the Submittal package at the Engineer’s request, which substantiate the Contractor/Vendors’ previous experience as noted herein.

C. Testing Equipment

1. Furnish in conformance with the applicable requirements of this Section.

2. Test systems using at least one each of the following test measurement devices or approved functional equivalents:
a. Digital cable analyzer with applicable copper and/or fiber testing standards required within this Section.
b. Cabling plant tester capable of detecting shorts, opens, reversals and miswires.
c. Tone test set capable of analyzing line condition of voice lines. d. Any other items of equipment or materials required to demonstrate conformance with the Contract Documents.

1.6 DELIVERY, STORAGE AND HANDLING
A. Wire shall be in original unbroken package. Obtain approval of Inspector or Engineer before installation of wires.

B. Handle carefully to avoid damage to internal components, enclosure and finish.

ATTACHMENT B ITEM 6
271513 - 5 City of Ceres
Water Division
C. Store in a clean, dry environment. Maintain factory packaging and, if required, provide an additional cover to protect enclosure in harsh environments.

1.7 WARRANTY
A. Furnish guarantee in accordance with and in form required under Section 26 05 00.

B. Provide 15 year manufacturer’s warranty covering application assurance, product, cable, and labor for installations performed by a certified installer using the manufacturer’s connecting hardware and qualified cables.

PART 2 - PRODUCTS

2.1 DATA/VOICE CATEGORY-6 RATED COPPER CABLES
A. General

1. Exceeds EIA/TIA-568 Category 6 requirements and tested to 300Mhz.

2. Conductors shall be no small than 24AWG solid annealed bare copper.

3. Outdoor, underground cables must be UL listed for wet applications.

4. Cabling construction and use shall comply with CEC Article 800.

B. Indoor, General (Type CM/CMG/CMR/CMP)

1. Drawing Reference: UTP6-4

2. Cables installed within vertical shafts or risers shall be Type CMR or CMP listed.

3. Construction: Thermoplastic insulated 8 conductor (4 pair) assembly with flame retardant PVC jacket.

4. Manufacturer: Commscope UltraMedia, Mohawk AdvanceNet, Superior Essex NetGain or approved equal.

C. Indoor, Plenum (Type CMP)

1. Drawing Reference: UTP6-4P

2. Construction: FEP/PE insulated 8 conductor (4 pair) assembly with low smoke PVC/FEP jacket.

3. Manufacturer: Commscope UltraMedia, Mohawk AdvanceNet, Superior Essex NetGain or approved equal.

D. Outdoor, Underground

1. Drawing Reference: UTP6-4OP

2. Construction: FEP/PE insulated 8 conductor (4 pair) assembly with floodant compound and PE jacket.

3. Manufacturer: Mohawk AdvanceNet or approved equal.

E. Indoor, Shielded (Type CM/CMG/CMR/CMP)
ATTACHMENT B ITEM 6
271513 - 6 City of Ceres
Water Division

1. Drawing Reference: STP6-4

2. Construction: FEP/PE insulated 8 conductor (4 pair) with an overall tape/drain shield and flame retardant PVC or low smoke PVC/FEP jacket.

3. Manufacturer: Mohawk AdvanceNet or approved equal.

F. Outdoor, Underground Shielded

1. Drawing Reference: STP6-4OP

2. Construction: PE/PVC insulated 8 conductor (4 pair) with an overall tape/drain shield, floodant compound and PE/PVC jacket.

3. Manufacturer: Mohawk AdvanceNet or approved equal.

2.2 TELEPHONE PLANT COPPER CABLES
A. General

1. Cables which interconnect interior distribution centers and terminate at station jacks shall conform to ICEA S-80-576, Category 1 or Category 3 standards.

2. Conductors shall be 22AWG solid annealed bare copper with minimum pair counts indicated on the plans.

3. Outdoor, underground cables must be UL listed for wet applications.

4. Cabling construction and use shall comply with CEC Article 800.

B. Indoor, General (Type CM/CMG/CMR/CMP)

1. Drawing Reference: UTP-##, where ## refers to required pair count

2. Cables installed within vertical shafts or risers shall be Type CMR or CMP listed.

3. Construction: Thermoplastic insulated conductors situated as paired assemblies with a flame retardant PVC jacket.

4. Manufacturer: Belden, Mohawk or approved equal.

C. Indoor, Plenum (Type CMP)

1. Drawing Reference: UTP-##P, where ## refers to required pair count

2. Construction: FEP/PE insulated conductors situated as paired assemblies with a low smoke PVC/FEP jacket

3. Manufacturer: Belden, Mohawk or approved equal.

D. Outdoor, Underground Within Duct

1. Less than (<) 4 pair trunk cables
a. Drawing Reference: STP-##OP, where ## refers to required pair count b. Construction: Polyolefin, PE or PVC insulated conductors situated as paired assemblies with a foil shield, floodant compound and PE jacket. c. Manufacturer: Belden, Westpenn Aquaseal or approved equal.

2. Greater than (>) 4 pair trunk cables
a. Drawing Reference: STP-##OP, where ## refers to required pair count ATTACHMENT B ITEM 6
271513 - 7 City of Ceres
Water Division
b. Construction:
1) Shall be RUS (REA) PE-89 listed, and suitable for direct burial. 2) PE jacket with aluminum tape shield and flooded core assembly. 3) The core assembly shall consist of twisted pair cables with polyolefin insulation.
c. Manufacturer: General Cable, Superior Essex SEALPIC-FSF or approved equal.

2.3 DATA/VOICE STATION JACKS & MODULES
A. General Jack and Module Requirements

1. Meets or exceeds the following configuration and performance standards where applicable:
a. EIA/TIA 568B
b. ISO/IEC 11801, Class E
c. UL1863
d. CEC/NEC Article 800
e. FCC Part 68

2. High impact, flame retardant thermoplastic.

3. Integral locking mechanism upon insertion of a modular plug.

B. Voice jack USOC grade

1. Six (6) position, RJ25 configuration jack conforming to USOC requirements.

2. Manufacturers
a. Leviton, Siemon or approved equal.

C. Voice and/or data jack, Category 3

1. Eight (8) position, RJ45 configuration jack conforming to EIA/TIA 568B and USOC requirements.

2. Manufacturers
a. Leviton, Siemon or approved equal.

D. Data jack Category 6

1. Eight (8) position, RJ45 configuration jack conforming to EIA/TIA 568B requirements.

2. Manufacturers
a. Leviton eXetreme, Siemon Ultra Max or approved equal.

ATTACHMENT B ITEM 6
271513 - 8 City of Ceres
Water Division

2.4 TELECOMMUNICATION STATION PLATES
A. Modular plates

1. Construction
a. Modular, with snap-in receptacle options as scheduled. b. Single gang plate size and mounting.
c. Options for 1 to 6 modular jacks per plate.
d. Plate face shall be nylon; color shall be compatible with adjacent wall finish, unless otherwise indicated.
e. Integral labeling provided for plate identifier and identifier for each receptacle on the plate. Provide as follows:
1) Plate nominally 1-½” by ½” recessed slot with clear plastic cover over paper label. See labeling requirements in Part 3 of this Section. 2) Receptacle identifier(s) shall be iconic or literal descriptions of each receptacle type.
f. System shall provide at minimum the following receptacle options:
1) RJ45 Category 3 or RJ25 voice
2) RJ45 Category 6 data
3) 75 BNC
4) 75F
5) Phono (RCA) type
6) ST fiber adapter
7) SC fiber adapter
8) S video
9) Blank plate fillers as required to fill unused area.

2. Manufacturers
a. Leviton QuickPort MOS, Siemons CT or approved equal
B. Wall phones plates (non-VOIP or Category-6 jack type)

1. Construction
a. Single gang plate size and mounting.
b. Plate face shall be stainless steel with 2 mounting stud type screws for mounting of telephone handset; unless otherwise indicated. c. Jack shall be USOC voice grade as described above.

2.5 CABLE TERMINATION EQUIPMENT AND RELATED, CATEGORY RATED A. Data Patch Panels, Category 6 Rated, Rack Mounted

1. Drawing Reference: ##C6PP, where ## refers to port count.

2. Functions/Features
ATTACHMENT B ITEM 6
271513 - 9 City of Ceres
Water Division
a. 19” EIA rack mountable.
b. 24 ports per one (1) EIA rack unit (1.75”) minimum, unless otherwise noted on Drawings.
c. Keyed, block form RJ-45/Category 6 jacks and 110 terminations meeting specifications elsewhere herein.
1) Arranged in rows on steel panel.
2) Jacks on front and terminations on rear.
d. Port identifier label space on front.
e. Provide wire management rings in a ratio of at least 4 rings for every 24 ports.

3. Manufacturers
a. Leviton, Siemon or approved equal.

B. Category 3 Terminal Block with Pre-Wired RJ21C Connector

1. Drawing reference: 110PWTB##, where ## refers to pair count.

2. Features/Functions
a. Type 110 terminal block with pre-wired RJ21C 50 pin connector on block or on end of pigtail stub cable.
b. Meets Category 3 specifications.

3. Manufacturers
a. Siemon S110A series, Siemon S700 or approved equal.

C. Category 3 Rack Mount Patch Panels with Pre-Wired RJ21C Connector

1. Drawing reference: ##110PWC3PP, where ## designates port count.

2. Features/Functions/Construction
a. 19” EIA rack mount panel.
b. Front face: RJ45 jacks
c. Rear face: Pre-wired RJ21C 50 pin connector(s).
d. Printed Circuit board linking RJ45’s to RJ21C – all four pairs wired straight through.
e. Meets Category 3.
f. At least 24 Jacks per rack unit (RU).

3. Manufacturers
a. Siemon, Signamax or approved equal.

2.6 MISCELLANOUS DEVICES
A. Shield Connectors
ATTACHMENT B ITEM 6
271513 - 10 City of Ceres
Water Division

1. Shield connectors shall make a stable, low-impedance electrical connection between the shield of the communications cable and a conductor such as a strap, bar or wire.

2. The connector shall be made of tin-plated tempered brass.

3. RUS PE-33 compliant.

4. Manufacturers
a. Preformed Line Products Servi-Bond or approved equal.

B. Grounding Braid

1. Ground braid shall provide low electrical impedance connections for dependable shield bonding.

2. The braid shall be made from 1/2” wide flat tin-plated copper, length as required.

3. Provide eyelets as necessary for bonding purposes.

4. Manufacturers
a. Thomas Betts, 3M or approved equal.

PART 3 - EXECUTION

3.1 EXAMINATION
A. Verify that all raceways have been de-burred and properly joined, coupled, and terminated prior to installation of cables. Verify that all raceways are clear of foreign matter and substances prior to installation of wire or cable.

B. Inspect all conduit bends to verify proper radius. Comply with Code and cable manufacturer requirements for minimum permissible radius and maximum permissible deformation.

3.2 INSTALLATION
A. Separation of Wires: Comply with EIA/TIA-569 rules and CEC/NEC 800-52 for separation of unshielded copper voice and data system cables from potential EMI sources, including electrical power lines and equipment.

B. All necessary interconnections, services, and adjustments required for a complete and operable system shall be provided. All installation work must be done in accordance with the safety requirements set forth in the general requirements of IEEE C2 and CEC/NEC 800.

C. Unless otherwise noted, all trunk and backbone cables and conductors shall have surge and ground protection installed at each end which meets RUS PE-60 requirements.

Refer to requirements herein and within the referencing Section as to the acceptable products in each application.

D. Wire and cable installation:

ATTACHMENT B ITEM 6
271513 - 11 City of Ceres
Water Division

1. All wire and cable shall be continuous and splice-free for the entire length of run between designated connections or terminations.

2. At designated splices, maintain conductor color code across all splices.

3. Copper conductor voice cable outside plant splicing shall be accomplished in accordance with RUS PC-2.

4. All shielded cables shall be insulated. Do not permit shields to contact conduit, raceway, boxes, panels or equipment enclosures.

5. Within buildings, make splices only in designated terminal cabinets and/or on designated equipment backboards.

6. Outdoor splices shall not be permitted except where specifically noted or where required by the run length. Where run lengths require outdoor splices not noted on the drawings, notify Engineer in writing for direction before proceeding.

7. Do not subject wire and cable to tension greater than that recommended by the cable manufacturer. Use multi-spool rollers where cable is pulled in place around bends. Do not pull reverse bends.

8. Provide a box loop for all wire and cable routed through junction boxes or distribution panels. Provide tool formed thermal expansion loops at cable at manholes, handholes and at both sides of all fixed mounted equipment. Cable loops and bends shall not be bent at a radius greater than that recommended by the manufacturer.

9. Secure all wire and cable run vertically for continuous distances greater than thirty (30) feet. Secure robust non-coaxial cables with screw-flange nylon cable ties, kellem grip or similar approved devices appropriate to weight of cable. For all other cables, provide symmetrical conforming nonmetallic bushings or woven cable grips appropriate to weight of cable.

10. Where drawings specifically permit use of exposed cable installation in Plenum and/or Suspended Ceiling voids, conform to the following:
a. Conform to EIA/TIA 569 with respect to separation from power and radio frequency (RF) sources. Provide at least twice the listed separation at fluorescent light fixtures, ballasts and similar high intensity EMF sources (including but not limited to motors, transformers and copiers). b. Support: Provide support for all cabling. Do not place or attach directly to T-bar grid, concealed spline grid, flexible or rigid ductwork, HVAC registers, sprinkler piping or fixtures, light fixtures.
1) Provide supports at least 48” on center, with cables installed with slight sag to ensure conformance with EIA TSB40 tensioning and stress limits. c. Placement: Do not obscure access to access doors, hatches, air dampers, valves, cable trays, junction boxes, pull boxes or similar areas of access. d. Place EMT pipe sleeves at all wall penetrations. Fire stop sleeves and cables where penetrating a rated wall with an approved UL assembly.

11. Wiring practices
a. Land all non-coaxial field wiring entering each equipment rack at specified terminal devices prior to connection to any equipment or devices within racks. At Contractor’s option and at no additional costs to Owner, such terminals may be located in the equipment racks or in the terminal cabinets provided.

ATTACHMENT B ITEM 6
271513 - 12 City of Ceres
Water Division
b. Apply all crimp connectors only with manufacturer’s recommended ratchet type tooling and correct crimp dies for connector and wire size; pliers type crimp tooling shall not be acceptable.
c. Coordinate insulation displacement (quick connect) terminal devices with wire size and type. Comply with manufacturer’s recommendations, and make connections with automatic impact type tooling set to a recommended force.
d. Make all connections to screw-type barrier blocks with insulated cirmp-type spade lugs. Lugs are not required at captive compression terminal type blocks. Provide permanent designation strips designed for use with the terminal blocks provided. Make neat, intelligible markings with indelible markers equivalent to “Sharpie”.
e. Tin terminated shield drain wires and insulate with heat shrinkable tubing. f. Use only rosin core 60/40 tin/lead solder for all solder connections. g. Dress, lace or harness all wire and cable to prevent mechanical stress on electrical connections. No wire or cable shall be supported by a connection point. Provide service loops where harness of different classes cross or where hinged panels are to be interconnected.
h. Termination and build-out resistors and related circuit correction components shall be visible. Do not install in connector shells or internally modify equipment. Show locations on Record Drawings.
i. Correct any and all of the following unacceptable wiring conditions:
1) Deformed, brittle or cracked insulation.
2) Torn or worn cable jacket.
3) Excessively scored cable jackets
4) Insulation shrunken or stripped further than 1/8” away from the actual point of connection within a connector, or on a punch block.
5) Cold solder joints.
6) Flux joints.
7) Solder splatter.
8) Ungrommeted, unbushed, or uninsulated wire or cable entries. 9) Deformation or improper radius of wire or cable.

12. Data cabling wiring practice (For copper cabling used in circuits of >1.0 Mbps conform to the following, in addition to the general requirements above.) a. Limit cable bends to a minimum radius of eight (8) times cable diameter except where otherwise noted herein.
b. At junction boxes, form circular radius bends of eight times cable diameter minimum. Up to two (2) flat bends of 90 or less are permitted in any single cable run where necessary to accommodate field wiring conditions. Flat bends exceeding 90 will not be accepted.
c. At the receptacle, a single bend of 90 or less and a 1 inch radius shall be permitted subject to the cable manufacturer certification of such an installation meeting Category 5E requirements. Contractor to field verify the performance of the proposed installation in a mockup using the proposed cabling, jacks, raceway and listed test equipment prior to proceeding. d. Tie wraps to be hand (not tool) tightened.

ATTACHMENT B ITEM 6
271513 - 13 City of Ceres
Water Division
e. Total run not to exceed 92 meters (300 feet). If condition exists report exceeded requirements to Engineer.

13. Labeling
a. Provide permanent identification of run destination at all raceway terminations. Identify at each manhole, vault, handhole, terminal cabinet, pull box, equipment rack and receptacle/outlet.
b. Unless otherwise noted, conform to the standards and methods of EIA/TIA 606.
c. Identify all wire and cable clearly with permanent labels rapped about the full circumference within one (1) inch of each connection. Provide any of the following:
1) Continuous permanent imprint; equivalent to Clifford of Vermont, Inc. “Quick-Pull”.
2) Direct hot stamp.
3) Heat shrinkable factory hot stamped; equivalent to Bradysleeve Heatshrink.
4) Adhesive strip printed labels wrapped the full circumference of the wire and sealed with clear heat shrink tubing; equivalent to Thomas Betts or Panduit Insta-code with clear heat-shrunk tubing equivalent to Alpha. 5) Outside Plant, in Manholes or Pull Boxes. Panduit Fiber Optic Cable Marker Tags (Type PST-FO) or Lead tags, 2” square, drilled for cable attachment. Use cable ties or THWN #12 or 2 #14 wrapped twice around the cable bundle and secure to tag using a crimp fastener. d. Indicate:
1) Indicate the number designated on the associated field or shop drawing or run sheet, as applies. Assign wire or cable designations consistently throughout a given system. Each wire or cable shall carry the same labeled designation over its entire run, regardless of intermediate terminations. 2) Indicate installation date.
e. Terminal cabinet, pull box and manhole, handhole, vault or similar locations subject to abuse, label in accordance to Section 26 05 00. 1) Patching Bays and Jacks and Receptacles containing six or fewer jacks/outlets: Provide designation strip holders with clear plastic covers to retain replaceable designation strips. Provide designation strips with block lettering on permanent background in contrasting color. Use photographic print, laser print on acid free paper, plotting ink on Mylar, or equivalent nonfading process. Alternatively, provide black on white adhesive labels equivalent to those produced by Brother brand P-Touch Letter Machine.

Embossed plastic (Dymo) labels shall not be acceptable. The presence of manufacturer provided silk screen iconic identification labels shall not relieve the contractor from the requirement to identify the receptacle with its associated cabling and circuit.

14. Signal grounding procedures
ATTACHMENT B ITEM 6
271513 - 14 City of Ceres
Water Division
a. Where items specified in Section 28 05 26 conflict with the requirements of this Section, the most stringent requirement shall govern. b. Equipment enclosures shall not be permitted to touch each other unless bolted together and electrically bonded.
c. Ground and bond equipment racks and similar equipment enclosures containing powered equipment exclusively to a telecommunication grounding bus bar.
d. At each rack, provide a lug bonded to the rack frame with a #10 Cu THWN stranded wire to the rack isolated ground bus.
e. Equipment signal ground shall be to racks isolated ground bus via the green wire of the equipment power cord. Where equipment uses an ungrounded power cord, provide #12 green bond wire to rack isolated ground bus bar.

At equipment housing, provide crimp lug and suitable hardware for bonding. f. Shielded cables of this section shall be grounded exclusively to a telecommunication grounding bus bar by a single path. Shield shall be tied to ground bar at one end only, i.e., at the low potential (receiving) end of run, unless otherwise noted.

3.3 FIELD QUALITY CONTROL
A. General

1. Test and report on each intermediate cabling segment separately, including station cabling, horizontal distribution (each segment, if multiple) and telecommunications closet wiring.

2. Test each end to end cable link.

3. Submit copy of final results on paper and in machine readable form, organized by circuit number, consistent with circuit numbering scheme used in preparing submittal drawings and in labeling receptacles and terminations. a. Submit machine-generated documentation and raw data of all test results on Contractor-provided, Owner approved forms; and in electronic format approved by the Owner.
b. Where the machine-generated documentation requires use of a proprietary computer program to view the data, provide the Owner with 1 licensed copy of the software.
c. Provide registered testing software used for the actual tests to the Owner/Engineer for review of test data as may be required.

B. Station Wiring, General

1. Test station wire only after all pairs of station wire in a work area have been terminated at both ends, and no work of this Section or other Sections may cause physical disturbance to the wiring.

2. Correct any and all transpositions found, and retest.

3. If any conductor in a station wire tests either open or short, then the entire station wire is to be removed, replaced and retested.

C. Inside Cabling
ATTACHMENT B ITEM 6
271513 - 15 City of Ceres
Water Division

1. Using a listed Category 6 cable test set, test and submit report on the parameters specified. Report whether tested link passes or fails the Category 5E standards outline within EIA/TIA-568.

2. Note exceptions to required Category standards. Remedy and retest.

D. Telephone: Outside Plant, Inside Riser Wire, Voice Station Wire (where not Category rated):

1. General
a. A new cable shall be tested only after all wires within the cable have been terminated at both ends.
b. For unshielded cable, “measurements to ground” means an electrical connection to the Telecommunications Ground Bus, building steel, electrical metallic conduit or a water pipe.
c. The Contractor shall correct all defects possible.
d. If the maximum number of un-repairable defective pairs exceeds 4% of the cable’s pair count, the cable shall be deemed unacceptable and shall be replaced. Replace, re-terminate and retest new cable at no additional cost to the Owner.

2. Test procedures
a. Test #1 – Continuity:
1) Meter set for 20 full scale ohm reading. Each pair shall be shorted at one end and the loop resistance value read at the other.
2) The difference between the largest and the smallest resistance reading from each pair in the cable shall be no more than 10 percent of the largest reading.
b. Test #2 – Balance, Polarity and Conductor Transpositions:
1) Upon passing Test #1, the tester at one end of cable shall ground tip side of each pair in turn. The tester at other end of cable reads resistance to building ground of same conductor.
2) Reading for each tip conductor in pair of approximately on-half of loop resistance value from Test #1.

3. Test Report
a. Submit Test Report. Documentation shall include loop resistance regarding any opens, shorts, transpositions as well as corrective actions.

END OF SECTION
ATTACHMENT B ITEM 6
271513 - 1 City of Ceres
Water Division
SECTION 28 05 26

GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL

1.1 SUMMARY
A. Section includes

1. Provide all labor, materials and equipment necessary to complete the installation required for the item specified under this Section, including but not limited to telecommunication system grounding.

B. Related sections

1. Where items specified in other Division 26 sections conflict with the requirements of this Section, the most stringent requirement shall govern.

2. The requirements of this Section apply to all Division 26 work, as applicable.

3. Consult all other sections, determine the extent and character of related work and properly coordinate work specified herein with that specified elsewhere to produce a complete installation.

1.2 REFERENCES
A. Comply with the latest edition of the following applicable specifications and standards except as otherwise shown or specified:

1. CCR –California Code of Regulations, Title 24
a. Part 3 -California Electrical Code(CEC); NFPA 70 National Electrical Code (NEC) with California amendments

2. IEEE –Institute of Electrical and Electronic Engineers a. 1100; Recommended Practices Powering and Grounding Electronic Equipment

3. NFPA –National Fire Protection Association
a. 780; Lightning Protection Code

4. TIA/EIA – Telecommunications Industry Association/Electronic Industries Alliance a. 607; Commercial Building Grounding and Bonding Requirements for Telecommunications

5. UL -Underwriters Laboratories, Inc.

ATTACHMENT B ITEM 6
271513 - 2 City of Ceres
Water Division
a. 467; Grounding and Bonding Equipment

1.3 SYSTEM DESCRIPTION
A. This Section provides for the grounding and bonding of all electrical and communication apparatus, appliances, components, fittings and accessories where required to provide a permanent, continuous, low impedance, grounded electrical system.

B. Except as otherwise indicated, the complete electrical installation including equipment and metallic raceways, boxes and cabinets shall be completely and effectively grounded in accordance with all Code requirements, whether or not such connections are specifically shown or specified.

C. Provide telecommunication system ground bus bars with each building main telecommunications equipment room or cabinet/rack location. Provide connection between the bus bar and main building reference ground bus, the ground bus of the panelboard serving power to telecommunication equipment, and all telecommunication conduit, cable trays, cable ladders and boxes.

1.4 SUBMITTALS
A. Submit manufacturer’s data for equipment and materials specified within this Section in accordance to Section 26 05 00.

1.5 QUALITY ASSURANCE
A. All materials, equipment and parts comprising the materials specified herein shall be new and unused, bearing UL labels where applicable.

PART 2 - PRODUCTS

2.1 INSULATED GROUNDING BUSHINGS
A. Plated malleable iron body with 150C molded plastic insulated throat and lay-in ground lug; OZ/Gedney BLG, Thomas & Betts #TIGB series or equal.

2.2 CONNECTIONS TO STRUCTURAL STEEL, GROUND RODS OR SPICES A. Where required by the Drawings, grounding conductors shall be spliced together, connected to ground rods or connected to structural steel using exothermic welds, Cadweld or equal, or high pressure compression type connectors, Cadweld, Thomas & Betts or equal.

2.3 BONDING JUMPERS
ATTACHMENT B ITEM 6
271513 - 3 City of Ceres
Water Division
A. OZ/Gedney Type BJ, Thomas & Betts #3840 series or equal.

2.4 GROUND CONDUCTOR
A. Ground conductor shall be #6 AWG UL labeled, Type THWN insulated copper wire, green in color.

2.5 TELECOMMUNICATION MAIN GROUNDING BUS BAR (TMGB)
A. Provide grounding bus bar at telecommunication backboards, racks and cabinets of the following type:

1. Backboards 4’X8’ and greater, floor mounted telecommunication equipment racks/cabinets larger than 60” height or wall mounted cabinets greater than 36”Wx36”H
a. Provide 1 13.5”x2”x1/4” TK copper bus bar mounted on wall with insulating stand-offs at +96” AFF. Furnish complete with cast copper alloy body Thomas Betts Series 310 or equal lugs for connecting grounding conductors.

Attach lugs to bus with appropriate size bronze bolt, flat washer and Belleville washer. All connections shall be torque, and all holes shall be drilled and tapped for single hole lugs. Provide 4 spare lugs with respective spaces.

2. Backboards less than 4’X8’, floor/wall mounted telecommunication equipment racks/cabinet less than 60” or wall mounted cabinets less than 36”Wx36”H a. Provide an aluminum loadcenter ground kit with 14 terminals minimum, General Electric TGL2 or equal. A minimum of 3 terminals shall accommodate #6 AWG. Mount within enclosure or on backboard at +96” AFF.

PART 3 - EXECUTION

3.1 INSTALLATION
A. Telecommunication system grounding

1. Bond all telecommunication conduit, cable tray, ladder rack, equipment racks and all other metallic telecommunication infrastructure components to the nearest TMGB using a #6 AWG conductor.

2. Provide #6 AWG ground within ¾” conduit from each secondary backboard, cabinet, rack, etc. to the BGB.

3. Install #6 AWG grounding conductor in nonmetallic underground raceways containing only fiber optic cable.

4. Provide an engraved nameplate mechanically fastened to wall or enclosure adjacent to each TMGB. Nameplate shall be blue with ¼” high white lettering to read “TMGB-(name of enclosure or building)”.

ATTACHMENT B ITEM 6
271513 - 4 City of Ceres
Water Division

3.2 FIELD QUALITY CONTROL
A. Contractor using test equipment expressly designed for that purpose shall perform all ground resistance tests in conformance with IEEE Standard 1100. Contractor shall submit typewritten records of measured resistance values to Engineer for review and approval prior to energizing the system.

B. Obtain and record ground resistance measurements both from electrical equipment ground bus to the ground electrode and from the ground electrode to earth. Furnish and install additional bonding and add grounding electrodes as required to comply with the following resistance limits:

1. Resistance from ground bus to ground electrode and to earth shall not exceed 5 ohms unless otherwise noted.

2. Resistance from the farthest panelboard, loadcenter, switchboard or motor control center ground bus to the ground electrode and to earth shall not exceed 20 ohms maximum.

C. Obtain and record ground resistance measurements (DC, 60Hz, 10MHz, 20MHz, 33 MHz, 66MHz and 100MHz) both from each TMGB to the ground electrode and from the ground electrode to earth.

D. Inspection

1. The Engineer or Inspector prior to encasement, burial or concealment thereto shall review the grounding electrode and connections.

END OF SECTION
ATTACHMENT B ITEM 6
271513 - 1 City of Ceres
Water Division
SECTION 28 05 33

PATHWAY FOR ELECTRONIC SAFETY AND SECURITY
PART 1 - GENERAL

1.1 SUMMARY
A. Section includes

1. Provide all labor, materials and equipment necessary to complete the installation required for the items specified under this Section, including but not limited to electrical conduits; outlet, junction and pull boxes; and related supports.

B. Related sections

1. Where items specified in other Division 26 sections conflict with the requirements of this Section, the most stringent requirement shall govern. a. 26 05 26 – Grounding and Bonding for Electrical Systems

2. The requirements of this Section apply to all Division 26 work, as applicable.

3. Consult all other sections, determine the extent and character of related work and properly coordinate work specified herein with that specified elsewhere to produce a complete installation.

1.2 REFERENCES
A. Comply with the latest edition of the following applicable specifications and standards except as otherwise shown or specified:

1. ANSI –American National Standards Institute
a. C33.91; Specification for Rigid PVC Conduit
b. C80.1; Specification Rigid Steel Conduit, Zinc-Coated c. C80.3; Specification for Electrical Metallic Tubing, Zinc-Coated d. C80.6; Intermediate Metal Conduit (IMC), Zinc-Coated

2. CCR –California Code of Regulations, Title 24
a. Part 2 -California Building Code (CBC); International Building Code (IBC) with California amendments
b. Part 3 -California Electrical Code(CEC); NFPA 70 National Electrical Code (NEC) with California amendments

3. NECA –National Electrical Contractors Association
a. 101, Standard for Installing Steel Conduit (Rigid, IMC, EMT) ATTACHMENT B ITEM 6
271513 - 2 City of Ceres
Water Division
b. 111, Standard for Installing Nonmetallic Raceways (RNC, ENT, LFNC) (ANSI)

4. NEMA –National Electrical Manufacturer’s Association a. FB 1; Fittings, Cast Metal Boxes, and Conduit Bodies for Conduit, Electrical Metallic Tubing, and Cable
b. FB 2.10; Selection and Installation Guidelines for Fittings for Use with Nonflexible Electrical Metal Conduit or Tubing (Rigid Metal Conduit, Intermediate Metal Conduit, and Electrical Metallic Tubing)
c. FB 2.20; Selection and Installation Guidelines for Fittings for Use with Flexible Electrical Conduit and Cable
d. OS 1; Sheet-Steel Outlet Boxes, Device Boxes, Covers, and Box Supports e. OS 3; Selection and Installation Guidelines for Electrical Outlet Boxes f. RN 1; Polyvinyl-Chloride Externally Coated Galvanized Rigid Steel Conduit and Electrical Metallic Tubing
g. TC 2; Electrical Plastic Tubing and Conduit
h. TC 3; PVC Fittings for Use with Rigid PVC Conduit and Tubing i. TC 14; Reinforced Thermosetting Resin Conduit (RTRC) and Fittings

5. OSHPD Anchorage Pre-approvals
a. OPA-0003; Superstrut Seismic Restraint System
b. OPA-0114; B-Line Seismic Restraints
c. OPA-0120; Unistrut Seismic Bracing System
d. OPA-0242; Power-Strut Seismic Bracing System

6. UL –Underwriter’s Laboratories, Inc.
a. 1; Standard for Flexible Metal Conduit
b. 6; Rigid Metal Electrical Conduit
c. 360; Standard for Liquid-Tight Flexible Steel Conduit d. 514A; Metallic Outlet Boxes, Electrical
e. 514B; Fittings for Conduit and Outlet Boxes
f. 651; Schedule 40 & 80 PVC Conduit
g. 797; Electrical Metallic Tubing
h. 1242; Intermediate Metal Conduit
i. 1684; Reinforced Thermosetting Resin Conduit (RTRC) and Fittings

1.3 SYSTEM DESCRIPTION
A. Furnish, assemble, erect, install, connect and test all electrical conduits and related raceway apparatus required and specified to form a complete installation.

1.4 SUBMITTALS
A. Submit manufacturer’s data for materials specified within this Section in accordance to Section 26 05 00.

ATTACHMENT B ITEM 6
271513 - 3 City of Ceres
Water Division

1.5 QUALITY ASSURANCE
A. All materials, equipment and parts comprising the materials specified herein shall be new and unused, bearing UL labels where applicable.

B. Installation shall conform to the NECA installation guidelines unless otherwise indicated within this Section
PART 2 - PRODUCTS

2.1 MATERIALS
A. Conduits and Fittings

1. Rigid steel conduit (RMC)
a. Conduit: Standard weight, mild steel pipe, and zinc coated on both inside and outside by a hot dipping or shearardizing process manufactured in accordance with UL 6 and ANSI C80.1 specifications.
b. Fittings (couplings, elbows, bends, etc.)
1) Shall be steel or malleable iron.
2) Coupling and unions shall be threaded type, assembled with anticorrosion, conductive and anti-seize compound at joints made absolutely tight to exclude water.
c. Bushings
1) Insulating bushings: Threaded polypropylene or thermosetting phenolic rated at 150C minimum.
2) Insulating grounding bushing: Threaded cast body with insulating throat and steel “lay-in” ground lug.
3) Insulating metallic bushing: Threaded cast body with plastic insulated throat rated at 150C minimum.

2. Coated rigid steel conduit (CRMC)
a. Conduit: Equivalent to RMC with a Polyvinyl chloride (PVC) coated bonded to the galvanized outer surface of the conduit. The bonding between the PVC coating and conduit surface shall be ETL PVC-001 compliant. The coating thickness shall be a minimum of 40mil.
b. Fittings (couplings, elbows, bends, etc.)
1) Equivalent to RMC above with bonded coating same as conduit. 2) The PVC sleeve over fittings shall extend beyond hub or coupling approximately one diameter or 1 1/2” whichever is smaller. c. Bushing equivalent to RMC above.

ATTACHMENT B ITEM 6
271513 - 4 City of Ceres
Water Division

3. Intermediate metallic conduit(IMC)
a. Conduit: Intermediate weight, mild steel pipe, meeting the same requirements for finish and material as rigid steel conduit manufactured in accordance with UL 1242 and ANSI C80.6 specifications.
b. Fittings (couplings, elbows, bends, etc.) equivalent to RMC above. c. Bushing equivalent to RMC above.

4. Electrical metallic tubing (EMT)
a. Conduit: Cold rolled steel tubing with zinc coating on outside and protective enamel on inside manufactured in accordance with UL 797 and ANSI C80.3 specifications.
b. Couplings: Steel or malleable iron with compression type fastener via a nut. c. Connectors: Steel or malleable iron with compression type fastener via a nut with plastic insulated throat rated at 150C minimum.

5. Rigid non-metallic conduit (PVC)
a. Conduit: PVC composed Schedule 40, 90C manufactured in accordance with NEMA TC 2 and UL 651 specifications.
b. Fittings: Molded PVC, slip on solvent welded type in accordance to NEMA TC 3.

6. Reinforced thermosetting resin conduit (RTRC)
a. Conduit: Fiber impregnated with a cured thermosetting resin compound in accordance with NEMA TC 14 and UL1684.
b. Fittings: Molded resin with glass reinforcement manufactured in the same process as the conduit bonded with an epoxy adhesive.

7. Flexible metallic conduit (FMC)
a. Conduit: Continuous, flexible steel spirally wound with zinc coating on both inside and outside in accordance with UL 1.
b. Connectors: Steel or malleable iron with compression type fastener via a nut with plastic insulated throat rated at 150C minimum.

8. Liquidtight flexible metallic conduit (LFMC)
a. Conduit: PVC coated, continuous, flexible steel spirally wound with zinc coating on both inside and outside in accordance with UL 360. b. Connectors: Steel or malleable iron with compression type fastener via a nut with plastic insulated throat rated at 150C minimum.

9. Miscellaneous Fittings and Products
a. Conduit sealing bushings: Steel or cast malleable iron body and pressure clamps with PVC sleeve, neoprene sealing grommets and PVC coated steel pressure rings. Supplied with neoprene sealing rings between body and PVC sleeve.

ATTACHMENT B ITEM 6
271513 - 5 City of Ceres
Water Division
b. Watertight cable terminators: One piece, compression molded sealing ring with PVC coated steel pressure disks, stainless steel screws and zinc plated cast iron locking collar.
c. Watertight cable/cord connectors: Liquidtight steel or cast malleable iron body with sealing neoprene bushing and stainless steel retaining ring. d. Expansion fittings: Multi-piece unit of hot dip galvanized malleable iron or steel body and outside pressure bussing design to allow a maximum of 4” movement (2” in either direction). Furnish with external braid tinned copper bonding jumper. UL listed for both wet and dry locations. e. Expansion/deflection couplings: Multi-piece unit comprised of a neoprene sleeve, internal flexible tinned copper braid attached to bronze end couplings with stainless steel bands. Coupling to provide minimum of 3/4” movement and 30 degrees deflection from normal. UL listed for both wet and dry locations.
f. Conduit bodies: Raintight, malleable iron, hot-dip galvanized body with threaded hubs, stamped steel cover, stainless steel screws and neoprene gasket.
g. Other couplings, connectors and fittings shall be equal in quality, material and construction to items specified herein.

B. Boxes

1. Outlet boxes
a. Standard: Galvanized one-piece of welded pressed steel type in accordance with NEMA OS 1 and UL 514. Boxes shall not be less than 4” square and at least 1 1/2” deep.
b. Concrete: Galvanized steel, 4” octagon ring with mounting lug, backplate and adapter ring type in accordance with NEMA OS 1 and UL 514. Depth as required by application.
c. Masonry: Galvanized steel, 3.75” high gang box in accordance with NEMA OS 1 and UL 514.
d. Surface cast metal: Cast malleable iron body, surface mounted box with threaded hubs and mounting lugs as required in accordance with NEMA OS 1 and UL 514. Furnish with ground flange, steel cover and neoprene gasket.

2. Pull and junction boxes
a. Sheet metal boxes: Standard or concrete outlet box wherever possible; otherwise use 16 gauge galvanized sheet metal, NEMA 1 box sized per CEC with machine screwed cover.
b. Cast metal boxes: Install standard cast malleable iron outlet or device box when possible.
c. Flush mounted boxes: Install overlapping cover with flush head screws. d. In-ground mounted pull holes/boxes: Install pre-cast concrete box, sized per Drawing or CEC with pre-cast or traffic rated lid.

3. Floor boxes
a. Floor boxes shall be adjustable, cast metal body with threaded conduit openings, adjustable rings, brass flange or Lexan ring and cover plate with ATTACHMENT B ITEM 6
271513 - 6 City of Ceres
Water Division
threaded plug. Include provisions to accommodate surface mounted telephone or receptacle outlet, or flush floor mounted telephone or receptacle outlet where shown on Drawings.

C. Pull line/cord

1. Polypropylene braided line or Let-line #232 or equal of 1/8” diameter with a minimum break strength of 200 pounds.

PART 3 - EXECUTION

3.1 EXAMINATION
A. Thoroughly examine site conditions for acceptance of wire and cable installation to verify conformance with manufacturer and specification tolerances. Do not commence with work until all conditions are made satisfactory.

3.2 PREPARATION
A. Conduit

1. Provide all necessary conduit fittings, connectors, bushings, etc. required to complete conduit installation to meet the CEC/NEC and intended application whether noted, shown or specified within.

2. Location of conduit runs shall be planned in advance of the installation and coordinated with other trades.

3. Where practical, install conduits in groups in parallel vertical or horizontal runs that avoid unnecessary offsets.

4. All conduits shall be parallel or at right angles to columns, beams and walls whether exposed or concealed.

5. Conduits shall not be placed closer than 12” to a flue, parallel to hot water, steam line or other heat sources; or 3” when crossing perpendicular to the above said lines when possible.

6. Install exposed conduit as high as practical to maintain adequate headroom. Notify Engineer if headroom will be less than 102”.

7. Do not obstruct spaces required by Code in front of electrical equipment, access doors, etc.

8. The largest trade size conduit in concrete floors and walls shall not exceed 1/3 thickness or be spaced a less than three conduit diameters apart unless permitted by Engineer. All conduits shall be installed in the center of slab or wall, and never between reinforcing steel and bottom of floor slab.

9. Install additional pull boxes, not shown on Drawings, in sufficient quantities to facilitate pulling of conductors and cables such that total spacing does not exceed 150 feet or 270 degrees, total; and maximum pulling tension will not be exceeded.

10. When installing underground conduits to specified depth; depth shall be taken from finished grade as it will be at project completion. Should finish grade be above existing grade by an amount equal to or greater than specified depth, conduit shall be installed not less than 6” below existing grade.

ATTACHMENT B ITEM 6
271513 - 7 City of Ceres
Water Division

11. Verify that information concerning finish grade is accurate, for should the underground run be less than the specified depth, Contractor may be required to re-install conduit to meet the required depth.

12. Unless otherwise specified, underground conduits shall be installed with top side not less than 24” below finished grade; this depth applies to all conduits outside of building foundations including those under walks, open corridors or paved areas.

13. Utility company service conduits installation depth shall be as directed by their respective specifications and requirements.

B. Boxes

1. Before locating outlet boxes, check Construction Documents for type of construction and make sure that there is no conflict with other equipment. Locate outlet boxes as shown and locate so as not to interfere with other Work or equipment.

2. Install all outlet boxes flush within walls, ceiling and floors except where installed within non-finished rooms, cabinetry, attic spaces or as indicated on Drawings.

3. Locate pull boxes and junction boxes within concealed, accessible locations where possible.

4. Do not install outlet boxes back-to-back with same stud space. Where shown back-to-back, offset as required, and fill void with sound dampening material where requested by Owner.

5. In fire rated walls separate boxes by 24” minimum and with stud member.

6. Adjust position of outlet boxes within masonry wall to accommodate course lines.

3.3 INSTALLATION
A. Conduit

1. Minimum conduit size shall be 3/4” unless otherwise indicated.

2. All conduit work shall be concealed unless otherwise indicated. Exposed conduits shall be permitted within unfinished rooms/spaces to facilitate installation.

3. Install conduit in complete runs prior to installing conductors or cables.

4. Make long radius conduits bends free from kink, indentations or flattened surfaces.

Make bends carefully to avoid injury or flattening. Bends 1 1/4” size and larger shall be factory made ells, or be made with a manufactured mechanical bender.

Heating of steel conduit to facilitate bending or that damage galvanized coating will not be permitted.

5. Remove burrs and sharp edges at end of conduit with tapered reamer.

6. Protect and cover conduits during construction with metallic bushings and bushing “pennies” to seal exposed openings.

7. Assemble conduit threads with anti-corrosion, conductive, anti-seize compound and tighten securely.

8. Install conduits shall that no traps to collect condensation exist.

9. Fasten conduit securely to boxes with locknuts and bushings to provide good grounding continuity.

10. Install pull cords/line within any spare or unused conduits of sufficient length to facilitate future cable installation.

11. Penetrations
ATTACHMENT B ITEM 6
271513 - 8 City of Ceres
Water Division
a. Locate penetrations within structural members as shown on Drawings and as directed by Architect or Engineer. Should it be necessary to notch any framing member, make such notching only at locations and in a manner as approved by Engineer.
b. Do not chase concrete or masonry to install conduit unless specifically approved by Engineer.
c. Cutting or holes
1) Install sleeves for cast-in-place concrete floors and walls. After installing conduit through penetration, seal using dry-pack grouting compound (non-iron bearing, chloride free and non-shrinking) or fire rated assembly if rated floor or wall. Use escutcheon plate on floor underside to contain compound as necessary.
2) Cut holes with a hole saw for penetrations through non-concrete or nonmasonry members. 3) Provide chrome plated escutcheon plates at all publicly exposed wall, ceiling and floor penetrations.
d. Sealing
1) Non-rated penetration openings shall be packed with non-flammable insulating material and sealed with gypsum wallboard taping compound. 2) Fire rated penetration shall be sealed using a UL classified fire stop assembly suitable to maintain the equivalent fire rating prior to the penetration.
3) Use escutcheon plates to hold sealing or fire rated compound as necessary.
e. Waterproofing
1) Make penetrations through any damp-proofed/waterproofed surfaces within damp/wet locations as such as to maintain integrity of surface. 2) Install specified watertight conduit entrance seals at all below grade wall and floor penetrations.
3) At roof penetrations furnish roof flashing, counter flashing and pitchpockets compatible to roof assembly. 4) Where possible conduits that horizontally penetrate a waterproof membrane shall fall away from and below the penetration’s exterior side. 5) Make penetrations through floors watertight with mastic, even when concealed within walls or furred spaces.

12. Supports
a. Conduits shall be support and braced per OSHPD pre-approved anchorage systems when those methods are implemented and installed. b. Sizes of rods and cross channels shall be capable of supporting 4 times and 5 times actual load, respectively. Anchorage shall support the combined weight of conduit, hanger and conductors.
c. Support individual horizontal conduit 1 1/2” and smaller by means of 2 hole straps or individual hangers.

ATTACHMENT B ITEM 6
271513 - 9 City of Ceres
Water Division
d. Galvanized iron hanger rods sizes 1/4” diameter and larger with spring steel fasteners, clips or clamps specifically design for that purpose for 1 1/2” conduits and larger.
e. Support multi-parallel horizontal conduits runs with trapeze type hangers consisting of 2 or more steel hanger rods, preformed cross channels, ‘J’ bolts, clamps, etc.
f. Support conduit to wood structures by means of bolts or lag screws in shear, to concrete by means of insert or expansion bolts and to brickwork by means of expansion bolts.
g. Support multi-parallel vertical conduits runs with galvanized Unistrut, PowerStrut or approved equal type supports anchored to wall. Where multi-floored conduits pass through floors, install riser clamps at each floor. h. Maximum conduit support spacing shall be in accordance with NECA Standard of Installation:
1) Horizontal runs:
a) 3/4” and smaller at 60” on centers, unless building construction prohibits otherwise, then 84” on centers.
b) 1” and larger at 72” on centers, unless building construction prohibits otherwise or any other condition, then 120” on centers. 2) Vertical runs:
a) 3/4” and smaller @ 84” on centers.
b) 1” and 1 1/4” @ 96” on centers.
c) 1 1/2” and larger @ 120” on centers.
d) Any vertical condition such as shaftways and concealed locations for any sized conduit, 120” on centers.
i. Anchorage for RMC/IMC supports unless otherwise specified:
1) < 1” IMC/RMC = #10 bolt/screw.
2) 1” IMC/RMC = 1/4” bolt/screw.
3) 1 1/2” and 2” IMC/RMC = 3/8” bolt/screw.
4) 3” IMC/RMC, 4” EMT = 1/2” bolt/screw.
5) > 3” IMC/RMC = 5/8” bolt/screw.
j. Anchorage for EMT supports unless otherwise specified:
1) < 1 1/2” EMT = #10 bolt/screw.
2) 1 1/2” EMT = 1/4” bolt/screw.
3) 2, 2 1/2” and 3” EMT = 3/8” bolt/screw.
4) 4” EMT = 1/2” bolt/screw.
5) > 4” EMT = 5/8” bolt/screw.

B. Boxes

1. Install boxes as shown on Drawings and as required for splices, taps, wire pulling, equipment connections and Code compliance.

ATTACHMENT B ITEM 6
271513 - 10 City of Ceres
Water Division

2. Install additional pull boxes, not shown on Drawings, in sufficient quantities to facilitate pulling of conductors and cables such that total spacing does not exceed 150 feet or 270 degrees, total; and maximum pulling tension will not be exceeded.

3. Install plaster rings on all outlet boxes in stud walls or in furred, suspended or exposed ceilings. Covers shall be of a depth suited for installation.

4. Provide gasketed cast metal cover plates where boxes are exposed in damp or wet locations

5. Install access door for boxes installed within concealed locations without access.

6. Install approved factory made knockout seal where knockouts are not present.

7. Refer to Architectural interior elevations and details shown for exact mounting heights of all electrical outlets. In general, locate outlets as shown or specific and complies with Americans with Disabilities Act:
a. Convenience outlets: +18”AFF or +6” above counter or splash. b. Local switches: +48”AFF or +6” above counter or splash. c. Telecommunication outlets: +18”AFF or +48”AFF for wall telephone or intercom device.
d. Verify all mounting heights with Architectural Drawings, and where heights are not suited for construction or finish please consult Engineer or Architect.

8. Use conduit bodies to facilitate pulling of conductor or cables or change conduit direction. Do not splice within conduit bodies.

9. Enclose pull box with additional rated gypsum board as necessary to maintain wall’s original fire rating.

10. Install galvanized steel coverplates on all open boxes within dry listed areas.

11. Install in-ground pull holes/boxes flush to grade finish at finished areas or 1” above finished landscaped grade. Seal all conduits terminating in pull hole/box watertight. Install and grout around bell ends where shown. Cover and lids shall be removable without damage to adjacent finish surfaces.

12. Support
a. Accurately place boxes for finish, independently and securely supported by adequate blocking or manufacturer channel type heavy-duty box hangers for stud walls. Do not use nails to support boxes.
b. Support boxes independent of conduit system.
c. Mount boxes installed within ceilings to 16 gauge metal channel bars attached to main runners or joists.
d. Support boxes within suspended acoustical tile ceilings directly from structure above when light fixture are to be installed from box. e. Use auxiliary plates, bar or clips and grouted in place for masonry, block or pour-in-place concrete construction.

3.4 APPLICATION
A. Conduit

1. RMC/IMC suitable for all damp, dry and wet locations except when in contact with earth. IMC not suitable for hazardous locations as stated within CEC/NEC.

ATTACHMENT B ITEM 6
271513 - 11 City of Ceres
Water Division

2. CRMC suitable for damp or wet locations, concealed within concrete or in contact with earth.

3. EMT suitable for exposed or concealed dry, interior locations.

4. PVC/RTRC suitable for beneath ground floor slab, except when penetrating, and direct earth burial. Do not run exposed within concrete walls or in floor slab unless indicated on Drawings or per Engineer’s permission.

5. FMC suitable for dry locations only for connections to motors, transformers, vibrating equipment/machinery, controllers, valves, switches and light fixtures in less than 6 foot lengths.

6. LFMC application same as FMC above but for damp or wet locations.

B. Termination and joints

1. Use raceway fittings compatible with associated raceway and suitable for the location.

2. Raceways shall be joined using specified couplings or transitions where dissimilar raceway systems are joined.

3. Conduits shall be securely fastened to cabinets, boxes and gutters using (2) two locknuts and insulating bushing or specified insulated connector. Where joints cannot be made tight and terminations are subject to vibration, use bonding jumpers, bonding bushings or wedges to provide electrical continuity of the raceway system. Use insulating bushings to protect conductors where subjected to vibration or dampness. Install grounding bushings or bonding jumpers on all conduits terminating at concentric or eccentric knockouts.

4. Terminations exposed at weatherproof enclosures and cast outlet boxes shall be made watertight using specified connectors and hubs.

5. Stub freestanding equipment conduits through concrete floors for connections with top of coupling set flush with finished floor. Install plugs to protect threads and entrance of debris.

6. Install specified cable sealing bushings on all conduits originating outside the building walls and terminating within interior switchboard, panel, cabinet or gutters.

Install cable sealing bushings or raceway seal for conduit terminations in all grade level or below grade exterior pull, junction or outlet boxes.

7. Where conduits enter building from below grade inject into filled raceways preformulated rigid 2 lbs. density polyurethane foam suitable for sealing against water, moisture, insects and rodents.

8. Install expansion fitting or expansion/deflection couplings per manufacturer’s recommendations where:
a. Any conduit that crosses a building structure expansion joint; secure conduit on both sides to building structure and install expansion fitting at joint. b. Any conduit that crosses a concrete expansion joint; install expansion/deflection at joint.
c. Any conduit greater than 1-1/4” is routed along roof top in runs greater than 100 feet; install expansion fittings every 100 feet.
d. Engineer may allow FMC or LFMC in lieu of expansion fitting or expansion/deflection couplings on conduits 2” and smaller within accessible locations upon further review and written consent.

C. Boxes
ATTACHMENT B ITEM 6
271513 - 12 City of Ceres
Water Division

1. Standard type suitable for all flush installations and all dry concealed locations.

2. Concrete type suitable for all flush concrete installations.

3. Masonry type suitable for all flush concrete and block installations.

4. Surface cast meta type suitable for all exposed damp and wet surface mounted locations, and dry surface mounted locations less than 96” from finished floor

END OF SECTION
ATTACHMENT B ITEM 6
280526 - 1 City of Ceres
Water Division
SECTION 28 05 26

GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL

1.1 SUMMARY
A. Section includes

1. Provide all labor, materials and equipment necessary to complete the installation required for the item specified under this Section, including but not limited to telecommunication system grounding.

B. Related sections

1. Where items specified in other Division 26 sections conflict with the requirements of this Section, the most stringent requirement shall govern.

2. The requirements of this Section apply to all Division 26 work, as applicable.

3. Consult all other sections, determine the extent and character of related work and properly coordinate work specified herein with that specified elsewhere to produce a complete installation.

1.2 REFERENCES
A. Comply with the latest edition of the following applicable specifications and standards except as otherwise shown or specified:

1. CCR –California Code of Regulations, Title 24
a. Part 3 -California Electrical Code(CEC); NFPA 70 National Electrical Code (NEC) with California amendments

2. IEEE –Institute of Electrical and Electronic Engineers a. 1100; Recommended Practices Powering and Grounding Electronic Equipment

3. NFPA –National Fire Protection Association
a. 780; Lightning Protection Code

4. TIA/EIA – Telecommunications Industry Association/Electronic Industries Alliance a. 607; Commercial Building Grounding and Bonding Requirements for Telecommunications
ATTACHMENT B ITEM 6
280526 - 2 City of Ceres
Water Division

5. UL -Underwriters Laboratories, Inc.
a. 467; Grounding and Bonding Equipment

1.3 SYSTEM DESCRIPTION
A. This Section provides for the grounding and bonding of all electrical and communication apparatus, appliances, components, fittings and accessories where required to provide a permanent, continuous, low impedance, grounded electrical system.

B. Except as otherwise indicated, the complete electrical installation including equipment and metallic raceways, boxes and cabinets shall be completely and effectively grounded in accordance with all Code requirements, whether or not such connections are specifically shown or specified.

C. Provide telecommunication system ground bus bars with each building main telecommunications equipment room or cabinet/rack location. Provide connection between the bus bar and main building reference ground bus, the ground bus of the panelboard serving power to telecommunication equipment, and all telecommunication conduit, cable trays, cable ladders and boxes.

1.4 SUBMITTALS
A. Submit manufacturer’s data for equipment and materials specified within this Section in accordance to Section 26 05 00.

1.5 QUALITY ASSURANCE
A. All materials, equipment and parts comprising the materials specified herein shall be new and unused, bearing UL labels where applicable.

PART 2 - PRODUCTS

2.1 INSULATED GROUNDING BUSHINGS
A. Plated malleable iron body with 150C molded plastic insulated throat and lay-in ground lug; OZ/Gedney BLG, Thomas & Betts #TIGB series or equal.

2.2 CONNECTIONS TO STRUCTURAL STEEL, GROUND RODS OR SPICES A. Where required by the Drawings, grounding conductors shall be spliced together, connected to ground rods or connected to structural steel using exothermic welds, Cadweld or equal, or high pressure compression type connectors, Cadweld, Thomas & Betts or equal.

ATTACHMENT B ITEM 6
280526 - 3 City of Ceres
Water Division

2.3 BONDING JUMPERS
A. OZ/Gedney Type BJ, Thomas & Betts #3840 series or equal.

2.4 GROUND CONDUCTOR
A. Ground conductor shall be #6 AWG UL labeled, Type THWN insulated copper wire, green in color.

2.5 TELECOMMUNICATION MAIN GROUNDING BUS BAR (TMGB)
A. Provide grounding bus bar at telecommunication backboards, racks and cabinets of the following type:

1. Backboards 4’X8’ and greater, floor mounted telecommunication equipment racks/cabinets larger than 60” height or wall mounted cabinets greater than 36”Wx36”H
a. Provide 1 13.5”x2”x1/4” TK copper bus bar mounted on wall with insulating stand-offs at +96” AFF. Furnish complete with cast copper alloy body Thomas Betts Series 310 or equal lugs for connecting grounding conductors.

Attach lugs to bus with appropriate size bronze bolt, flat washer and Belleville washer. All connections shall be torque, and all holes shall be drilled and tapped for single hole lugs. Provide 4 spare lugs with respective spaces.

2. Backboards less than 4’X8’, floor/wall mounted telecommunication equipment racks/cabinet less than 60” or wall mounted cabinets less than 36”Wx36”H a. Provide an aluminum loadcenter ground kit with 14 terminals minimum, General Electric TGL2 or equal. A minimum of 3 terminals shall accommodate #6 AWG. Mount within enclosure or on backboard at +96” AFF.

PART 3 - EXECUTION

3.1 INSTALLATION
A. Telecommunication system grounding

1. Bond all telecommunication conduit, cable tray, ladder rack, equipment racks and all other metallic telecommunication infrastructure components to the nearest TMGB using a #6 AWG conductor.

2. Provide #6 AWG ground within ¾” conduit from each secondary backboard, cabinet, rack, etc. to the BGB.

3. Install #6 AWG grounding conductor in nonmetallic underground raceways containing only fiber optic cable.

ATTACHMENT B ITEM 6
280526 - 4 City of Ceres
Water Division

4. Provide an engraved nameplate mechanically fastened to wall or enclosure adjacent to each TMGB. Nameplate shall be blue with ¼” high white lettering to read “TMGB-(name of enclosure or building)”.

3.2 FIELD QUALITY CONTROL
A. Contractor using test equipment expressly designed for that purpose shall perform all ground resistance tests in conformance with IEEE Standard 1100. Contractor shall submit typewritten records of measured resistance values to Engineer for review and approval prior to energizing the system.

B. Obtain and record ground resistance measurements both from electrical equipment ground bus to the ground electrode and from the ground electrode to earth. Furnish and install additional bonding and add grounding electrodes as required to comply with the following resistance limits:

1. Resistance from ground bus to ground electrode and to earth shall not exceed 5 ohms unless otherwise noted.

2. Resistance from the farthest panelboard, loadcenter, switchboard or motor control center ground bus to the ground electrode and to earth shall not exceed 20 ohms maximum.

C. Obtain and record ground resistance measurements (DC, 60Hz, 10MHz, 20MHz, 33 MHz, 66MHz and 100MHz) both from each TMGB to the ground electrode and from the ground electrode to earth.

D. Inspection

1. The Engineer or Inspector prior to encasement, burial or concealment thereto shall review the grounding electrode and connections.

END OF SECTION
ATTACHMENT B ITEM 6
280526 - 1 City of Ceres
Water Division
SECTION 28 05 33

PATHWAY FOR ELECTRONIC SAFETY AND SECURITY
PART 1 - GENERAL

1.1 SUMMARY
A. Section includes

1. Provide all labor, materials and equipment necessary to complete the installation required for the items specified under this Section, including but not limited to electrical conduits; outlet, junction and pull boxes; and related supports.

B. Related sections

1. Where items specified in other Division 26 sections conflict with the requirements of this Section, the most stringent requirement shall govern. a. 26 05 26 – Grounding and Bonding for Electrical Systems

2. The requirements of this Section apply to all Division 26 work, as applicable.

3. Consult all other sections, determine the extent and character of related work and properly coordinate work specified herein with that specified elsewhere to produce a complete installation.

1.2 REFERENCES
A. Comply with the latest edition of the following applicable specifications and standards except as otherwise shown or specified:

1. ANSI –American National Standards Institute
a. C33.91; Specification for Rigid PVC Conduit
b. C80.1; Specification Rigid Steel Conduit, Zinc-Coated c. C80.3; Specification for Electrical Metallic Tubing, Zinc-Coated d. C80.6; Intermediate Metal Conduit (IMC), Zinc-Coated

2. CCR –California Code of Regulations, Title 24
a. Part 2 -California Building Code (CBC); International Building Code (IBC) with California amendments
b. Part 3 -California Electrical Code(CEC); NFPA 70 National Electrical Code (NEC) with California amendments

3. NECA –National Electrical Contractors Association
ATTACHMENT B ITEM 6
280526 - 2 City of Ceres
Water Division
a. 101, Standard for Installing Steel Conduit (Rigid, IMC, EMT) b. 111, Standard for Installing Nonmetallic Raceways (RNC, ENT, LFNC) (ANSI)

4. NEMA –National Electrical Manufacturer’s Association a. FB 1; Fittings, Cast Metal Boxes, and Conduit Bodies for Conduit, Electrical Metallic Tubing, and Cable
b. FB 2.10; Selection and Installation Guidelines for Fittings for Use with Nonflexible Electrical Metal Conduit or Tubing (Rigid Metal Conduit, Intermediate Metal Conduit, and Electrical Metallic Tubing)
c. FB 2.20; Selection and Installation Guidelines for Fittings for Use with Flexible Electrical Conduit and Cable
d. OS 1; Sheet-Steel Outlet Boxes, Device Boxes, Covers, and Box Supports e. OS 3; Selection and Installation Guidelines for Electrical Outlet Boxes f. RN 1; Polyvinyl-Chloride Externally Coated Galvanized Rigid Steel Conduit and Electrical Metallic Tubing
g. TC 2; Electrical Plastic Tubing and Conduit
h. TC 3; PVC Fittings for Use with Rigid PVC Conduit and Tubing i. TC 14; Reinforced Thermosetting Resin Conduit (RTRC) and Fittings

5. OSHPD Anchorage Pre-approvals
a. OPA-0003; Superstrut Seismic Restraint System
b. OPA-0114; B-Line Seismic Restraints
c. OPA-0120; Unistrut Seismic Bracing System
d. OPA-0242; Power-Strut Seismic Bracing System

6. UL –Underwriter’s Laboratories, Inc.
a. 1; Standard for Flexible Metal Conduit
b. 6; Rigid Metal Electrical Conduit
c. 360; Standard for Liquid-Tight Flexible Steel Conduit d. 514A; Metallic Outlet Boxes, Electrical
e. 514B; Fittings for Conduit and Outlet Boxes
f. 651; Schedule 40 & 80 PVC Conduit
g. 797; Electrical Metallic Tubing
h. 1242; Intermediate Metal Conduit
i. 1684; Reinforced Thermosetting Resin Conduit (RTRC) and Fittings

1.3 SYSTEM DESCRIPTION
A. Furnish, assemble, erect, install, connect and test all electrical conduits and related raceway apparatus required and specified to form a complete installation.

1.4 SUBMITTALS
ATTACHMENT B ITEM 6
280526 - 3 City of Ceres
Water Division
A. Submit manufacturer’s data for materials specified within this Section in accordance to Section 26 05 00.

1.5 QUALITY ASSURANCE
A. All materials, equipment and parts comprising the materials specified herein shall be new and unused, bearing UL labels where applicable.

B. Installation shall conform to the NECA installation guidelines unless otherwise indicated within this Section
PART 2 - PRODUCTS

2.1 MATERIALS
A. Conduits and Fittings

1. Rigid steel conduit (RMC)
a. Conduit: Standard weight, mild steel pipe, and zinc coated on both inside and outside by a hot dipping or shearardizing process manufactured in accordance with UL 6 and ANSI C80.1 specifications.
b. Fittings (couplings, elbows, bends, etc.)
1) Shall be steel or malleable iron.
2) Coupling and unions shall be threaded type, assembled with anticorrosion, conductive and anti-seize compound at joints made absolutely tight to exclude water.
c. Bushings
1) Insulating bushings: Threaded polypropylene or thermosetting phenolic rated at 150C minimum.
2) Insulating grounding bushing: Threaded cast body with insulating throat and steel “lay-in” ground lug.
3) Insulating metallic bushing: Threaded cast body with plastic insulated throat rated at 150C minimum.

2. Coated rigid steel conduit (CRMC)
a. Conduit: Equivalent to RMC with a Polyvinyl chloride (PVC) coated bonded to the galvanized outer surface of the conduit. The bonding between the PVC coating and conduit surface shall be ETL PVC-001 compliant. The coating thickness shall be a minimum of 40mil.
b. Fittings (couplings, elbows, bends, etc.)
1) Equivalent to RMC above with bonded coating same as conduit.

ATTACHMENT B ITEM 6
280526 - 4 City of Ceres
Water Division
2) The PVC sleeve over fittings shall extend beyond hub or coupling approximately one diameter or 1 1/2” whichever is smaller. c. Bushing equivalent to RMC above.

3. Intermediate metallic conduit(IMC)
a. Conduit: Intermediate weight, mild steel pipe, meeting the same requirements for finish and material as rigid steel conduit manufactured in accordance with UL 1242 and ANSI C80.6 specifications.
b. Fittings (couplings, elbows, bends, etc.) equivalent to RMC above. c. Bushing equivalent to RMC above.

4. Electrical metallic tubing (EMT)
a. Conduit: Cold rolled steel tubing with zinc coating on outside and protective enamel on inside manufactured in accordance with UL 797 and ANSI C80.3 specifications.
b. Couplings: Steel or malleable iron with compression type fastener via a nut. c. Connectors: Steel or malleable iron with compression type fastener via a nut with plastic insulated throat rated at 150C minimum.

5. Rigid non-metallic conduit (PVC)
a. Conduit: PVC composed Schedule 40, 90C manufactured in accordance with NEMA TC 2 and UL 651 specifications.
b. Fittings: Molded PVC, slip on solvent welded type in accordance to NEMA TC 3.

6. Reinforced thermosetting resin conduit (RTRC)
a. Conduit: Fiber impregnated with a cured thermosetting resin compound in accordance with NEMA TC 14 and UL1684.
b. Fittings: Molded resin with glass reinforcement manufactured in the same process as the conduit bonded with an epoxy adhesive.

7. Flexible metallic conduit (FMC)
a. Conduit: Continuous, flexible steel spirally wound with zinc coating on both inside and outside in accordance with UL 1.
b. Connectors: Steel or malleable iron with compression type fastener via a nut with plastic insulated throat rated at 150C minimum.

8. Liquidtight flexible metallic conduit (LFMC)
a. Conduit: PVC coated, continuous, flexible steel spirally wound with zinc coating on both inside and outside in accordance with UL 360. b. Connectors: Steel or malleable iron with compression type fastener via a nut with plastic insulated throat rated at 150C minimum.

ATTACHMENT B ITEM 6
280526 - 5 City of Ceres
Water Division

9. Miscellaneous Fittings and Products
a. Conduit sealing bushings: Steel or cast malleable iron body and pressure clamps with PVC sleeve, neoprene sealing grommets and PVC coated steel pressure rings. Supplied with neoprene sealing rings between body and PVC sleeve.
b. Watertight cable terminators: One piece, compression molded sealing ring with PVC coated steel pressure disks, stainless steel screws and zinc plated cast iron locking collar.
c. Watertight cable/cord connectors: Liquidtight steel or cast malleable iron body with sealing neoprene bushing and stainless steel retaining ring. d. Expansion fittings: Multi-piece unit of hot dip galvanized malleable iron or steel body and outside pressure bussing design to allow a maximum of 4” movement (2” in either direction). Furnish with external braid tinned copper bonding jumper. UL listed for both wet and dry locations. e. Expansion/deflection couplings: Multi-piece unit comprised of a neoprene sleeve, internal flexible tinned copper braid attached to bronze end couplings with stainless steel bands. Coupling to provide minimum of 3/4” movement and 30 degrees deflection from normal. UL listed for both wet and dry locations.
f. Conduit bodies: Raintight, malleable iron, hot-dip galvanized body with threaded hubs, stamped steel cover, stainless steel screws and neoprene gasket.
g. Other couplings, connectors and fittings shall be equal in quality, material and construction to items specified herein.

B. Boxes

1. Outlet boxes
a. Standard: Galvanized one-piece of welded pressed steel type in accordance with NEMA OS 1 and UL 514. Boxes shall not be less than 4” square and at least 1 1/2” deep.
b. Concrete: Galvanized steel, 4” octagon ring with mounting lug, backplate and adapter ring type in accordance with NEMA OS 1 and UL 514. Depth as required by application.
c. Masonry: Galvanized steel, 3.75” high gang box in accordance with NEMA OS 1 and UL 514.
d. Surface cast metal: Cast malleable iron body, surface mounted box with threaded hubs and mounting lugs as required in accordance with NEMA OS 1 and UL 514. Furnish with ground flange, steel cover and neoprene gasket.

2. Pull and junction boxes
a. Sheet metal boxes: Standard or concrete outlet box wherever possible; otherwise use 16 gauge galvanized sheet metal, NEMA 1 box sized per CEC with machine screwed cover.
b. Cast metal boxes: Install standard cast malleable iron outlet or device box when possible.
c. Flush mounted boxes: Install overlapping cover with flush head screws.

ATTACHMENT B ITEM 6
280526 - 6 City of Ceres
Water Division
d. In-ground mounted pull holes/boxes: Install pre-cast concrete box, sized per Drawing or CEC with pre-cast or traffic rated lid.

3. Floor boxes
a. Floor boxes shall be adjustable, cast metal body with threaded conduit openings, adjustable rings, brass flange or Lexan ring and cover plate with threaded plug. Include provisions to accommodate surface mounted telephone or receptacle outlet, or flush floor mounted telephone or receptacle outlet where shown on Drawings.

C. Pull line/cord

1. Polypropylene braided line or Let-line #232 or equal of 1/8” diameter with a minimum break strength of 200 pounds.

PART 3 - EXECUTION

3.1 EXAMINATION
A. Thoroughly examine site conditions for acceptance of wire and cable installation to verify conformance with manufacturer and specification tolerances. Do not commence with work until all conditions are made satisfactory.

3.2 PREPARATION
A. Conduit

1. Provide all necessary conduit fittings, connectors, bushings, etc. required to complete conduit installation to meet the CEC/NEC and intended application whether noted, shown or specified within.

2. Location of conduit runs shall be planned in advance of the installation and coordinated with other trades.

3. Where practical, install conduits in groups in parallel vertical or horizontal runs that avoid unnecessary offsets.

4. All conduits shall be parallel or at right angles to columns, beams and walls whether exposed or concealed.

5. Conduits shall not be placed closer than 12” to a flue, parallel to hot water, steam line or other heat sources; or 3” when crossing perpendicular to the above said lines when possible.

6. Install exposed conduit as high as practical to maintain adequate headroom. Notify Engineer if headroom will be less than 102”.

7. Do not obstruct spaces required by Code in front of electrical equipment, access doors, etc.

8. The largest trade size conduit in concrete floors and walls shall not exceed 1/3 thickness or be spaced a less than three conduit diameters apart unless permitted ATTACHMENT B ITEM 6
280526 - 7 City of Ceres
Water Division
by Engineer. All conduits shall be installed in the center of slab or wall, and never between reinforcing steel and bottom of floor slab.

9. Install additional pull boxes, not shown on Drawings, in sufficient quantities to facilitate pulling of conductors and cables such that total spacing does not exceed 150 feet or 270 degrees, total; and maximum pulling tension will not be exceeded.

10. When installing underground conduits to specified depth; depth shall be taken from finished grade as it will be at project completion. Should finish grade be above existing grade by an amount equal to or greater than specified depth, conduit shall be installed not less than 6” below existing grade.

11. Verify that information concerning finish grade is accurate, for should the underground run be less than the specified depth, Contractor may be required to re-install conduit to meet the required depth.

12. Unless otherwise specified, underground conduits shall be installed with top side not less than 24” below finished grade; this depth applies to all conduits outside of building foundations including those under walks, open corridors or paved areas.

13. Utility company service conduits installation depth shall be as directed by their respective specifications and requirements.

B. Boxes

1. Before locating outlet boxes, check Construction Documents for type of construction and make sure that there is no conflict with other equipment. Locate outlet boxes as shown and locate so as not to interfere with other Work or equipment.

2. Install all outlet boxes flush within walls, ceiling and floors except where installed within non-finished rooms, cabinetry, attic spaces or as indicated on Drawings.

3. Locate pull boxes and junction boxes within concealed, accessible locations where possible.

4. Do not install outlet boxes back-to-back with same stud space. Where shown back-to-back, offset as required, and fill void with sound dampening material where requested by Owner.

5. In fire rated walls separate boxes by 24” minimum and with stud member.

6. Adjust position of outlet boxes within masonry wall to accommodate course lines.

3.3 INSTALLATION
A. Conduit

1. Minimum conduit size shall be 3/4” unless otherwise indicated.

2. All conduit work shall be concealed unless otherwise indicated. Exposed conduits shall be permitted within unfinished rooms/spaces to facilitate installation.

3. Install conduit in complete runs prior to installing conductors or cables.

4. Make long radius conduits bends free from kink, indentations or flattened surfaces.

Make bends carefully to avoid injury or flattening. Bends 1 1/4” size and larger shall be factory made ells, or be made with a manufactured mechanical bender.

Heating of steel conduit to facilitate bending or that damage galvanized coating will not be permitted.

5. Remove burrs and sharp edges at end of conduit with tapered reamer.

ATTACHMENT B ITEM 6
280526 - 8 City of Ceres
Water Division

6. Protect and cover conduits during construction with metallic bushings and bushing “pennies” to seal exposed openings.

7. Assemble conduit threads with anti-corrosion, conductive, anti-seize compound and tighten securely.

8. Install conduits shall that no traps to collect condensation exist.

9. Fasten conduit securely to boxes with locknuts and bushings to provide good grounding continuity.

10. Install pull cords/line within any spare or unused conduits of sufficient length to facilitate future cable installation.

11. Penetrations
a. Locate penetrations within structural members as shown on Drawings and as directed by Architect or Engineer. Should it be necessary to notch any framing member, make such notching only at locations and in a manner as approved by Engineer.
b. Do not chase concrete or masonry to install conduit unless specifically approved by Engineer.
c. Cutting or holes
1) Install sleeves for cast-in-place concrete floors and walls. After installing conduit through penetration, seal using dry-pack grouting compound (non-iron bearing, chloride free and non-shrinking) or fire rated assembly if rated floor or wall. Use escutcheon plate on floor underside to contain compound as necessary.
2) Cut holes with a hole saw for penetrations through non-concrete or nonmasonry members. 3) Provide chrome plated escutcheon plates at all publicly exposed wall, ceiling and floor penetrations.
d. Sealing
1) Non-rated penetration openings shall be packed with non-flammable insulating material and sealed with gypsum wallboard taping compound. 2) Fire rated penetration shall be sealed using a UL classified fire stop assembly suitable to maintain the equivalent fire rating prior to the penetration.
3) Use escutcheon plates to hold sealing or fire rated compound as necessary.
e. Waterproofing
1) Make penetrations through any damp-proofed/waterproofed surfaces within damp/wet locations as such as to maintain integrity of surface. 2) Install specified watertight conduit entrance seals at all below grade wall and floor penetrations.
3) At roof penetrations furnish roof flashing, counter flashing and pitchpockets compatible to roof assembly. 4) Where possible conduits that horizontally penetrate a waterproof membrane shall fall away from and below the penetration’s exterior side.

ATTACHMENT B ITEM 6
280526 - 9 City of Ceres
Water Division
5) Make penetrations through floors watertight with mastic, even when concealed within walls or furred spaces.

12. Supports
a. Conduits shall be support and braced per OSHPD pre-approved anchorage systems when those methods are implemented and installed. b. Sizes of rods and cross channels shall be capable of supporting 4 times and 5 times actual load, respectively. Anchorage shall support the combined weight of conduit, hanger and conductors.
c. Support individual horizontal conduit 1 1/2” and smaller by means of 2 hole straps or individual hangers.
d. Galvanized iron hanger rods sizes 1/4” diameter and larger with spring steel fasteners, clips or clamps specifically design for that purpose for 1 1/2” conduits and larger.
e. Support multi-parallel horizontal conduits runs with trapeze type hangers consisting of 2 or more steel hanger rods, preformed cross channels, ‘J’ bolts, clamps, etc.
f. Support conduit to wood structures by means of bolts or lag screws in shear, to concrete by means of insert or expansion bolts and to brickwork by means of expansion bolts.
g. Support multi-parallel vertical conduits runs with galvanized Unistrut, PowerStrut or approved equal type supports anchored to wall. Where multi-floored conduits pass through floors, install riser clamps at each floor. h. Maximum conduit support spacing shall be in accordance with NECA Standard of Installation:
1) Horizontal runs:
a) 3/4” and smaller at 60” on centers, unless building construction prohibits otherwise, then 84” on centers.
b) 1” and larger at 72” on centers, unless building construction prohibits otherwise or any other condition, then 120” on centers. 2) Vertical runs:
a) 3/4” and smaller @ 84” on centers.
b) 1” and 1 1/4” @ 96” on centers.
c) 1 1/2” and larger @ 120” on centers.
d) Any vertical condition such as shaftways and concealed locations for any sized conduit, 120” on centers.
i. Anchorage for RMC/IMC supports unless otherwise specified:
1) < 1” IMC/RMC = #10 bolt/screw.
2) 1” IMC/RMC = 1/4” bolt/screw.
3) 1 1/2” and 2” IMC/RMC = 3/8” bolt/screw.
4) 3” IMC/RMC, 4” EMT = 1/2” bolt/screw.
5) > 3” IMC/RMC = 5/8” bolt/screw.

ATTACHMENT B ITEM 6
280526 - 10 City of Ceres
Water Division
j. Anchorage for EMT supports unless otherwise specified:
1) < 1 1/2” EMT = #10 bolt/screw.
2) 1 1/2” EMT = 1/4” bolt/screw.
3) 2, 2 1/2” and 3” EMT = 3/8” bolt/screw.
4) 4” EMT = 1/2” bolt/screw.
5) > 4” EMT = 5/8” bolt/screw.

B. Boxes

1. Install boxes as shown on Drawings and as required for splices, taps, wire pulling, equipment connections and Code compliance.

2. Install additional pull boxes, not shown on Drawings, in sufficient quantities to facilitate pulling of conductors and cables such that total spacing does not exceed 150 feet or 270 degrees, total; and maximum pulling tension will not be exceeded.

3. Install plaster rings on all outlet boxes in stud walls or in furred, suspended or exposed ceilings. Covers shall be of a depth suited for installation.

4. Provide gasketed cast metal cover plates where boxes are exposed in damp or wet locations

5. Install access door for boxes installed within concealed locations without access.

6. Install approved factory made knockout seal where knockouts are not present.

7. Refer to Architectural interior elevations and details shown for exact mounting heights of all electrical outlets. In general, locate outlets as shown or specific and complies with Americans with Disabilities Act:
a. Convenience outlets: +18”AFF or +6” above counter or splash. b. Local switches: +48”AFF or +6” above counter or splash. c. Telecommunication outlets: +18”AFF or +48”AFF for wall telephone or intercom device.
d. Verify all mounting heights with Architectural Drawings, and where heights are not suited for construction or finish please consult Engineer or Architect.

8. Use conduit bodies to facilitate pulling of conductor or cables or change conduit direction. Do not splice within conduit bodies.

9. Enclose pull box with additional rated gypsum board as necessary to maintain wall’s original fire rating.

10. Install galvanized steel coverplates on all open boxes within dry listed areas.

11. Install in-ground pull holes/boxes flush to grade finish at finished areas or 1” above finished landscaped grade. Seal all conduits terminating in pull hole/box watertight. Install and grout around bell ends where shown. Cover and lids shall be removable without damage to adjacent finish surfaces.

12. Support
a. Accurately place boxes for finish, independently and securely supported by adequate blocking or manufacturer channel type heavy-duty box hangers for stud walls. Do not use nails to support boxes.
b. Support boxes independent of conduit system.
c. Mount boxes installed within ceilings to 16 gauge metal channel bars attached to main runners or joists.

ATTACHMENT B ITEM 6
280526 - 11 City of Ceres
Water Division
d. Support boxes within suspended acoustical tile ceilings directly from structure above when light fixture are to be installed from box. e. Use auxiliary plates, bar or clips and grouted in place for masonry, block or pour-in-place concrete construction.

3.4 APPLICATION
A. Conduit

1. RMC/IMC suitable for all damp, dry and wet locations except when in contact with earth. IMC not suitable for hazardous locations as stated within CEC/NEC.

2. CRMC suitable for damp or wet locations, concealed within concrete or in contact with earth.

3. EMT suitable for exposed or concealed dry, interior locations.

4. PVC/RTRC suitable for beneath ground floor slab, except when penetrating, and direct earth burial. Do not run exposed within concrete walls or in floor slab unless indicated on Drawings or per Engineer’s permission.

5. FMC suitable for dry locations only for connections to motors, transformers, vibrating equipment/machinery, controllers, valves, switches and light fixtures in less than 6 foot lengths.

6. LFMC application same as FMC above but for damp or wet locations.

B. Termination and joints

1. Use raceway fittings compatible with associated raceway and suitable for the location.

2. Raceways shall be joined using specified couplings or transitions where dissimilar raceway systems are joined.

3. Conduits shall be securely fastened to cabinets, boxes and gutters using (2) two locknuts and insulating bushing or specified insulated connector. Where joints cannot be made tight and terminations are subject to vibration, use bonding jumpers, bonding bushings or wedges to provide electrical continuity of the raceway system. Use insulating bushings to protect conductors where subjected to vibration or dampness. Install grounding bushings or bonding jumpers on all conduits terminating at concentric or eccentric knockouts.

4. Terminations exposed at weatherproof enclosures and cast outlet boxes shall be made watertight using specified connectors and hubs.

5. Stub freestanding equipment conduits through concrete floors for connections with top of coupling set flush with finished floor. Install plugs to protect threads and entrance of debris.

6. Install specified cable sealing bushings on all conduits originating outside the building walls and terminating within interior switchboard, panel, cabinet or gutters.

Install cable sealing bushings or raceway seal for conduit terminations in all grade level or below grade exterior pull, junction or outlet boxes.

7. Where conduits enter building from below grade inject into filled raceways preformulated rigid 2 lbs. density polyurethane foam suitable for sealing against water, moisture, insects and rodents.

ATTACHMENT B ITEM 6
280526 - 12 City of Ceres
Water Division

8. Install expansion fitting or expansion/deflection couplings per manufacturer’s recommendations where:
a. Any conduit that crosses a building structure expansion joint; secure conduit on both sides to building structure and install expansion fitting at joint. b. Any conduit that crosses a concrete expansion joint; install expansion/deflection at joint.
c. Any conduit greater than 1-1/4” is routed along roof top in runs greater than 100 feet; install expansion fittings every 100 feet.
d. Engineer may allow FMC or LFMC in lieu of expansion fitting or expansion/deflection couplings on conduits 2” and smaller within accessible locations upon further review and written consent.

C. Boxes

1. Standard type suitable for all flush installations and all dry concealed locations.

2. Concrete type suitable for all flush concrete installations.

3. Masonry type suitable for all flush concrete and block installations.

4. Surface cast meta type suitable for all exposed damp and wet surface mounted locations, and dry surface mounted locations less than 96” from finished floor

END OF SECTION
ATTACHMENT B ITEM 6
362
EXHIBIT “C”

SPECIAL CONDITIONS
ATTACHMENT B ITEM 6
363
EXHIBIT “D”

CERTIFICATION
LABOR CODE - SECTION 1861
I, the undersigned Contractor, am aware of the provisions of Section 3700, et seq., of the California Labor Code which require every employer to be insured against liability for Worker’s Compensation or to undertake self-insurance in accordance with the provisions of the Code, and I, the undersigned Contractor, agree to and will comply with such provisions before commencing the performance of the Work on this Contract.
_______________________________
[INSERT CONTRACTOR NAME]
By: _________________________
Signature
_________________________
Name (Print)
_________________________
Title (Print)
ATTACHMENT B ITEM 6
364
EXHIBIT “E”

PUBLIC WORKS CONTRACTOR REGISTRATION CERTIFICATION
Pursuant to Labor Code sections 1725.5 and 1771.1, all contractors and subcontractors that wish to bid on, be listed in a bid proposal, or enter into a contract to perform public work must be registered with the Department of Industrial Relations. See http://www.dir.ca.gov/PublicWorks/PublicWorks.html for additional information.

No bid will be accepted nor any contract entered into without proof of the contractor’s and subcontractors’ current registration with the Department of Industrial Relations to perform public work.

Contractor hereby certifies that it is aware of the registration requirements set forth in Labor Code sections 1725.5 and 1771.1 and is currently registered as a contractor with the Department of Industrial Relations.1
Name of Contractor:

DIR Registration Number:

DIR Registration Expiration:

Small Project Exemption: _____ Yes or _____ No
Unless Contractor is exempt pursuant to the small project exemption, Contractor further acknowledges:
• Failure to submit this form or comply with any of the above requirements may result in a finding that the bid is non-responsive.
• Contractor shall maintain a current DIR registration for the duration of the project. • Contractor shall include the requirements of Labor Code sections 1725.5 and 1771.1 in its contract with subcontractors and ensure that all subcontractors are registered at the time of bid opening and maintain registration status for the duration of the project.

Name of Contractor
Signature
Name and Title
Dated
1 If the Project is exempt from the contractor registration requirements pursuant to the small project exemption under Labor Code Sections 1725.5 and 1771.1, please mark “Yes” in response to “Small Project Exemption.”
ATTACHMENT B ITEM 6
365
EXHIBIT “F”

PAYMENT AND PERFORMANCE BONDS
ATTACHMENT B ITEM 6
366

PERFORMANCE BOND
KNOW ALL PERSONS BY THESE PRESENTS:

THAT WHEREAS, the City of Ceres (hereinafter referred to as “City”) has awarded to (hereinafter referred to as the “Contractor”) an agreement for (hereinafter referred to as the “Project”).

WHEREAS, the work to be performed by the Contractor is more particularly set forth in the Contract Documents for the Project dated , (hereinafter referred to as “Contract Documents”), the terms and conditions of which are expressly incorporated herein by reference; and
WHEREAS, the Contractor is required by said Contract Documents to perform the terms thereof and to furnish a bond for the faithful performance of said Contract Documents.

NOW, THEREFORE, we, , the undersigned
Contractor and _____________________________________________ as Surety, a corporation organized and duly authorized to transact business under the laws of the State of California, are held and firmly bound unto the City in the sum of
DOLLARS, ($ ), said sum being not less than one hundred percent (100%) of the total amount of the Contract, for which amount well and truly to be made, we bind ourselves, our heirs, executors and administrators, successors and assigns, jointly and severally, firmly by these presents.

THE CONDITION OF THIS OBLIGATION IS SUCH, that, if the Contractor, his or its heirs, executors, administrators, successors or assigns, shall in all things stand to and abide by, and well and truly keep and perform the covenants, conditions and agreements in the Contract Documents and any alteration thereof made as therein provided, on its part, to be kept and performed at the time and in the manner therein specified, and in all respects according to their intent and meaning; and shall faithfully fulfill all obligations including the one-year guarantee of all materials and workmanship; and shall indemnify and save harmless the City, its officers and agents, as stipulated in said Contract Documents, then this obligation shall become null and void; otherwise it shall be and remain in full force and effect.

As a condition precedent to the satisfactory completion of the Contract Documents, unless otherwise provided for in the Contract Documents, the above obligation shall hold good for a period of one (1) year after the acceptance of the work by City, during which time if Contractor shall fail to make full, complete, and satisfactory repair and replacements and totally protect the City from loss or damage resulting from or caused by defective materials or faulty workmanship, Surety shall undertake and faithfully fulfill all such obligations. The obligations of Surety hereunder shall continue so long as any obligation of Contractor remains. Nothing herein shall limit the City’s rights or the Contractor or Surety’s obligations under the Contract, law or equity, including, but not limited to, California Code of Civil Procedure section 337.15.

Whenever Contractor shall be, and is declared by the City to be, in default under the Contract Documents, the Surety shall remedy the default pursuant to the Contract Documents, or shall promptly, at the City’s option:

ATTACHMENT B ITEM 6
367
(1) Take over and complete the Project in accordance with all terms and conditions in the Contract Documents; or
(2) Obtain a bid or bids for completing the Project in accordance with all terms and conditions in the Contract Documents and upon determination by Surety of the lowest responsive and responsible bidder, arrange for a Contract between such bidder, the Surety and the City, and make available as work progresses sufficient funds to pay the cost of completion of the Project, less the balance of the contract price, including other costs and damages for which Surety may be liable. The term “balance of the contract price” as used in this paragraph shall mean the total amount payable to Contractor by the City under the Contract and any modification thereto, less any amount previously paid by the City to the Contractor and any other set offs pursuant to the Contract Documents.
(3) Permit the City to complete the Project in any manner consistent with local, California and federal law and make available as work progresses sufficient funds to pay the cost of completion of the Project, less the balance of the contract price, including other costs and damages for which Surety may be liable. The term “balance of the contract price” as used in this paragraph shall mean the total amount payable to Contractor by the City under the Contract and any modification thereto, less any amount previously paid by the City to the Contractor and any other set offs pursuant to the Contract Documents.

Surety expressly agrees that the City may reject any contractor or subcontractor which may be proposed by Surety in fulfillment of its obligations in the event of default by the Contractor.

Surety shall not utilize Contractor in completing the Project nor shall Surety accept a bid from Contractor for completion of the Project if the City, when declaring the Contractor in default, notifies Surety of the City’s objection to Contractor’s further participation in the completion of the Project.

The Surety, for value received, hereby stipulates and agrees that no change, extension of time, alteration or addition to the terms of the Contract Documents or to the Project to be performed thereunder shall in any way affect its obligations on this bond, and it does hereby waive notice of any such change, extension of time, alteration or addition to the terms of the Contract Documents or to the Project, including but not limited to the provisions of sections 2819 and 2845 of the California Civil Code.

ATTACHMENT B ITEM 6
368
IN WITNESS WHEREOF, we have hereunto set our hands and seals this _______ day of ______________, 20__).
(Corporate Seal)
Contractor/ Principal
By
Title
(Corporate Seal) Surety
By
Attorney-in-Fact
Signatures of those signing for the Contractor and Surety must be notarized and evidence of corporate authority attached.
(Attach Attorney-in-Fact Certificate) Title
The rate of premium on this bond is ____________ per thousand. The total amount of premium charges, $_______________________________.
(The above must be filled in by corporate attorney.)

THIS IS A REQUIRED FORM
Any claims under this bond may be addressed to:
(Name and Address of Surety) ___________________________________________ ___________________________________________
___________________________________________
(Name and Address of Agent or ___________________________________________ Representative for service of
process in California, if different ___________________________________________ from above)
___________________________________________
(Telephone number of Surety and ___________________________________________ Agent or Representative for service
of process in California)
NOTE: A copy of the Power-of-Attorney authorizing the person signing on behalf of the Surety to do so must be attached hereto.

ATTACHMENT B ITEM 6
369
Notary Acknowledgment
A notary public or other officer completing this certificate verifies only the identity of the individual who signed the document to which this certificate is attached, and not the truthfulness, accuracy, or validity of that document.

STATE OF CALIFORNIA
COUNTY OF ______________
On , 20___, before me, _______________________________, Notary Public, personally appeared , who proved to me on the basis of satisfactory evidence to be the person(s) whose name(s) is/are subscribed to the within instrument and acknowledged to me that he/she/they executed the same in his/her/their authorized capacity(ies), and that by his/her/their signature(s) on the instrument the person(s), or the entity upon behalf of which the person(s) acted, executed the instrument.

I certify under PENALTY OF PERJURY under the laws of the State of California that the foregoing paragraph is true and correct.

WITNESS my hand and official seal.

Signature of Notary Public

OPTIONAL
Though the information below is not required by law, it may prove valuable to persons relying on the document and could prevent fraudulent removal and reattachment of this form to another document.

CAPACITY CLAIMED BY SIGNER DESCRIPTION OF ATTACHED DOCUMENT  Individual
 Corporate Officer
Title(s) Title or Type of Document
 Partner(s)  Limited
 General Number of Pages
 Attorney-In-Fact
 Trustee(s)
 Guardian/Conservator Date of Document
 Other:

Signer is representing:

Name Of Person(s) Or Entity(ies)
Signer(s) Other Than Named Above
ATTACHMENT B ITEM 6
370

PAYMENT BOND
KNOW ALL MEN BY THESE PRESENTS That
WHEREAS, the City of Ceres (hereinafter designated as the “City”), by action taken or a resolution passed on has awarded to
, Inc. hereinafter designated as the “Principal,” a contract for the work described as follows:

Rockefeller Water Building Improvements (the “Project”); and WHEREAS, the work to be performed by the Principal is more particularly set forth in the Contract Documents for the Project dated , 20 (“Contract Documents”), the terms and conditions of which are expressly incorporated by reference; and WHEREAS, said Principal is required to furnish a bond in connection with said contract; providing that if said Principal or any of its Subcontractors shall fail to pay for any materials, provisions, provender, equipment, or other supplies used in, upon, for or about the performance of the work contracted to be done, or for any work or labor done thereon of any kind, or for amounts due under the Unemployment Insurance Code or for any amounts required to be deducted, withheld, and paid over to the Employment Development Department from the wages of employees of said Principal and its Subcontractors with respect to such work or labor the Surety on this bond will pay for the same to the extent hereinafter set forth.

NOW THEREFORE, we, the Principal and __________________________ as Surety, are held and firmly bound unto the City in the penal sum of Dollars ($ ) lawful money of the United States of
America, for the payment of which sum well and truly to be made, we bind ourselves, our heirs, executors, administrators, successors and assigns, jointly and severally, firmly by these presents.

THE CONDITION OF THIS OBLIGATION IS SUCH that if said Principal, his or its subcontractors, heirs, executors, administrators, successors or assigns, shall fail to pay any of the persons named in Section 9100 of the Civil Code, fail to pay for any materials, provisions or other supplies, used in, upon, for or about the performance of the work contracted to be done, or for any work or labor thereon of any kind, or amounts due under the Unemployment Insurance Code with respect to work or labor performed under the contract, or for any amounts required to be deducted, withheld, and paid over to the Employment Development Department or Franchise Tax Board from the wages of employees of the contractor and his subcontractors pursuant to Section 18663 of the Revenue and Taxation Code, with respect to such work and labor the Surety or Sureties will pay for the same, in an amount not exceeding the sum herein above specified.

This bond shall inure to the benefit of any of the persons named in Section 9100 of the Civil Code so as to give a right of action to such persons or their assigns in any suit brought upon this bond.

It is further stipulated and agreed that the Surety on this bond shall not be exonerated or released from the obligation of this bond by any change, extension of time for performance, addition, alteration or modification in, to, or of any contract, plans, specifications, or agreement pertaining or relating to any scheme or work of improvement herein above described, or pertaining or relating to the furnishing of labor, materials, or equipment therefore, nor by any change or modification of any terms of payment or extension of the time for any payment pertaining or relating to any scheme or work of improvement herein above described, nor by any rescission or attempted rescission of the contract, agreement or bond, nor by any conditions precedent or subsequent in the bond attempting ATTACHMENT B ITEM 6
371
to limit the right of recovery of claimants otherwise entitled to recover under any such contract or agreement or under the bond, nor by any fraud practiced by any person other than the claimant seeking to recover on the bond and that this bond be construed most strongly against the Surety and in favor of all persons for whose benefit such bond is given, and under no circumstances shall Surety be released from liability to those for whose benefit such bond has been given, by reason of any breach of contract between the owner or City and original contractor or on the part of any obligee named in such bond, but the sole conditions of recovery shall be that claimant is a person described in Section 9100 of the Civil Code, and has not been paid the full amount of his claim and that Surety does hereby waive notice of any such change, extension of time, addition, alteration or modification herein mentioned and the provisions of sections 2819 and 2845 of the California Civil Code.

IN WITNESS WHEREOF, we have hereunto set our hands and seals this _______ day of ______________, 20__.
(Corporate Seal)
Contractor/ Principal
By
Title
(Corporate Seal) Surety
By
Attorney-in-Fact
Title
Signatures of those signing for the Contractor and Surety must be notarized and evidence of corporate authority attached. A Power-of-Attorney authorizing the person signing on behalf of the Surety to do so much be attached hereto.

NOTE: A copy of the Power-of-Attorney authorizing the person signing on behalf of the Surety to do so must be attached hereto.

ATTACHMENT B ITEM 6
372
Notary Acknowledgment
A notary public or other officer completing this certificate verifies only the identity of the individual who signed the document to which this certificate is attached, and not the truthfulness, accuracy, or validity of that document.

STATE OF CALIFORNIA
COUNTY OF ______________
On , 20___, before me, _______________________________, Notary Public, personally appeared , who proved to me on the basis of satisfactory evidence to be the person(s) whose name(s) is/are subscribed to the within instrument and acknowledged to me that he/she/they executed the same in his/her/their authorized capacity(ies), and that by his/her/their signature(s) on the instrument the person(s), or the entity upon behalf of which the person(s) acted, executed the instrument.

I certify under PENALTY OF PERJURY under the laws of the State of California that the foregoing paragraph is true and correct.

WITNESS my hand and official seal.

Signature of Notary Public

OPTIONAL
Though the information below is not required by law, it may prove valuable to persons relying on the document and could prevent fraudulent removal and reattachment of this form to another document.

CAPACITY CLAIMED BY SIGNER DESCRIPTION OF ATTACHED DOCUMENT  Individual
 Corporate Officer
Title(s) Title or Type of Document
 Partner(s)  Limited
 General Number of Pages
 Attorney-In-Fact
 Trustee(s)
 Guardian/Conservator Date of Document
 Other:

Signer is representing:

Name Of Person(s) Or Entity(ies)
Signer(s) Other Than Named Above
ATTACHMENT B ITEM 6
373

APPENDIX
ATTACHMENT B ITEM 6
374

CITY OF CERES STANDARD DESIGNS

THE FOLLOWING STANDARDS ARE FOR REFERENCE ONLY

REFER TO THE CITY OF CERES WEBSITE FOR THE COMPLETE LISTING OF STANDARD

DETAILS
https://www.ci.ceres.ca.us/DocumentCenter/View/2214/Approved-2018-Standard-Specificationsand-Design ATTACHMENT B ITEM 6
375

STATE GENERAL PREVAILING WAGE RATES
General prevailing wage determination
Made by the Director of Industrial Relations
Pursuant to California Labor Code part 7,
Chapter 1, article 2, sections 1770, 1773, and 1773.1
__________________________________________________
State of California Department of Industrial Relations Website:
http://www.dir.ca.gov/OPRL/PWD/index.htm
ATTACHMENT B ITEM 6
376
REGULATION VIII – FUGITIVE PM10 PROHIBITIONS
ATTACHMENT B ITEM 6
377
ATTACHMENT B ITEM 6
378
ATTACHMENT B ITEM 6
379
ATTACHMENT B ITEM 6
Budget Amendment No.

Fiscal Year
Reference Resolution No . , dated authorizing appropriations for as follows:

Appropriations:

Fund Name Org. Object Project
(if appl.)
Appropriation
Amount
Requested Appropriation
Current Appropriation
Total Appropriation
Estimated Revenues:

Fund Name Org. Object Project
(if appl.)
Appropriation
Amount
Estimated Revenue
Current Estimated Revenue
Total Estimated Revenue
Fiscal Impact:

ATTACHMENT C
ITEM 6
ITEM 6
ITEM 6

COUNCIL AGENDA REPORT

CITY COUNCIL
Javier Lopez, Mayor
James Casey, Dist.1
Rosalinda L. Vierra, Dist. 2
Cerina Otero, Dist. 3
Daniel A. Martinez, Dist. 4
MEETING DATE: April 13, 2026
TO: Mayor and City Council
FROM: Trenton Johnson, Acting City Manager
CONTACT: Michael R. Beltran II, PE, Director of Engineering [email protected], (209) 538-5775
SUBJECT:

Resolution No. 2026-XXX, Approving Project Agreement No. 5 to the Master Agreement for Professional Consultant Services with Westwood Professional Services for Design Services for the Building on Active Transportation and Connectivity within the City (New Project String) Project in the Amount of $301,600; Approving the Project to be Added to the Capital Improvement Program; Approving the New Project String; Accepting Active
Transportation Program Grant Funding in the Amount of $256,000; Approving a Budget Amendment in the Amount of $256,000; Approving a Budget Transfer from Measure L Project 2408 in the Amount of $19,352.42 and Project 2522 in the Amount of
$64,228.33 for a Total of $83,580.75 for Matching Funds ($45,600) and Staff Time ($37,980.75); and Authorizing the City Manager to Execute Project Agreement No. 5
RECOMMENDED COUNCIL ACTION:

Staff recommends the City Council adopt a resolution; 1) approving Project Agreement No. 5 to the Master Agreement for Professional Consultant Services with Westwood Professional Services for design services for the Building on Active Transportation Connectivity and Access within the City (New Project String) Project (the “Project”) in the amount of $301,600; 2) approving the Project to be added to the Capital Improvement Program; 3) approving a new Project String; 4) accepting Active Transportation Program (ATP) grant funding in the amount of $256,000; 5) approving a budget amendment in the amount of $256,000; 6) approving budget transfers from Measure L Project 2408 in the amount of $19,352.42 and Project 2522 in the amount of $64,228.33, for a total project budget of $403,280.75 to cover local match and staff time, and 7) authorizing the City Manager to execute Project Agreement No. 5.

I. BACKGROUND:

The Building on Active Transportation Connectivity and Access within the City Project (the “Project”) is intended to expand and improve the City of Ceres (“City”) network of ITEM 7
bicycle and pedestrian facilities in order to enhance safety, accessibility, and connectivity throughout the community. The Project supports the City’s efforts to provide safe and convenient active transportation routes that connect residents to key destinations such as schools, parks, transit facilities, community services, and commercial areas.

The Project includes improvements along several corridors within the City, including Ninth Street, Lawrence Street, Moffett Road, Moore Road, Eastgate Boulevard, Roeding Road, Whitmore Avenue, Fowler Road, Hatch Road, and River Bluff Regional Park.

Proposed improvements include installation of approximately 4.39 miles of bicycle lanes/routes and approximately 2,800 linear feet of pedestrian improvements, along with other safety and accessibility enhancements such as crosswalk improvements, curb ramps, wayfinding signage, lighting, and bicycle amenities.

These improvements are intended to create a more connected network for bicyclists and pedestrians, allowing residents, students, families, and recreational users to safely access destinations throughout the City while encouraging walking and bicycling as alternative modes of transportation.

The City applied for and was awarded $256,000 in Active Transportation Program (ATP) grant funding for the design phase of the Project. The ATP , administered by the California Transportation Commission and Caltrans, supports projects that improve safety and mobility for non-motorized users while encouraging active transportation and reducing greenhouse gas emissions.

To advance the Project toward construction, the City requires professional engineering design services including preparation of plans, specifications, and cost estimates, coordination with regulatory agencies, and compliance with state and federal funding requirements.

Westwood Professional Services currently maintains a Master Agreement for Professional Consultant Services with the City and has extensive experience in transportation design, grant-funded infrastructure projects, and coordination with Caltrans Local Assistance requirements. The proposed Project Agreement No. 5 will authorize Westwood Professional Services to perform the necessary design services for the Project and prepare the Project for future funding and construction.

II. REASONS FOR RECOMMENDATION:

Approval of the proposed resolution is recommended for the following reasons:

1. Improving Bicycle and Pedestrian Safety - The Project will improve safety for bicyclists and pedestrians by providing dedicated facilities, improved crossings, and ADA-compliant infrastructure along key corridors within the City.

2. Expanding Active Transportation Connectivity - The proposed improvements will create a connected network of bicycle and pedestrian routes that provide access to schools, parks, downtown destinations, transit facilities, and other community resources.

3. Utilization of State Grant Funding - The City has been awarded $256,000 in Active Transportation Program grant funding for the design phase of the ITEM 7
project. Accepting these funds allows the City to leverage state funding to advance important infrastructure improvements.

4. Supporting Community Health and Mobility - Expanding active transportation infrastructure promotes healthier lifestyles, reduces vehicle dependency, and improves air quality while providing equitable transportation options for residents of all ages and abilities.

5. Consultant Qualifications and Project Readiness - Westwood Professional Services has the technical expertise and experience necessary to complete the design phase and ensure compliance with Caltrans Local Assistance procedures and grant funding requirements.

6. Fiscal Responsibility and Budget Alignment - The project is funded through a combination of ATP grant funding and Measure L local matching funds. The project does not require the use of General Fund resources.

7. Capital Improvement Program Planning - Adding the project to the City’s Capital Improvement Program ensures appropriate financial tracking, project oversight, and long-term infrastructure planning
III. FISCAL IMPACTS:

Upon approval this Project will be added to the City’s 5-Year Capital Improvement Program. Funding will be appropriated to the following project account as it was not in the FY26 budget:
• 26895.800500 (New Project String) - $256,000.00
To fully fund the design contract and staff time, the following budget transfers are recommended:
• Transfer funds from 27195.800500 (2408) - $19,352.42
• Transfer funds from 27195.800500 (2522) - $64,228.33
This Project does not utilize any General Fund resources.

IV. EXISTING POLICY / RELATIONSHIP TO THE STRATEGIC PLAN:

This Project is in conformance with the First Goal of the Strategic Plan:

Infrastructure: Ensure that the community has adequate, well-maintained infrastructure that fosters a quality community and supports a strong economy.

V. POLICY ALTERNATIVES:

The City Council may consider the following alternatives:

1. Do Not Approve the Resolution
If the City Council chooses not to approve the resolution, the design phase of the project would not proceed. This could result in the potential loss of ATP grant funding and delay improvements intended to enhance pedestrian and bicycle safety and connectivity.

2. Delay Action Pending Further Review
The City Council may direct staff to return with additional information or ITEM 7
alternative approaches. This action could delay the project schedule and potentially impact grant funding timelines.

VI. INTERDEPARTMENTAL COORDINATION:

N/A
VII. PUBLIC PARTICIPATION:

Public outreach and community input were conducted during development of the City’s Active Transportation Plan and ATP grant application process.

Community surveys indicated strong support for improvements that provide safer walking and bicycling routes and better connectivity between destinations within the City VIII. ENVIRONMENTAL REVIEW:

N/A
IX. STEPS FOLLOWING APPROVAL:

Upon Council approval, the City Manager will execute the task order with Westwood Professional Services, and staff will proceed with design.

Approved by: __________________________
Trenton Johnson,
Acting City Manager
Attachments:

1. Attachment A – Resolution

2. Attachment B – Westwood Professional Services Project Agreement

3. Attachment C – Budget Transfer

4. Attachment D – Budget Amendment
ITEM 7

ATTACHMENT A
RESOLUTION NO. 2025-XXX
APPROVING PROJECT AGREEMENT NO. 5 TO THE MASTER

AGREEMENT FOR PROFESSIONAL CONSULTANT SERVICES WITH

WESTWOOD PROFESSIONAL SERVICES, FOR DESIGN SERVICES FOR

THE BUILDING ON ACTIVE TRANSPORTATION AND CONNECTIVITY

WITHIN THE CITY (NEW PROJECT STRING) PROJECT IN THE AMOUNT OF $301,600; APPROVING THE PROJECT TO BE ADDED TO THE
CAPITAL IMPROVEMENT PROGRAM; APPROVING A NEW PROJECT
STRING; ACCEPTING ACTIVE TRANSPORTATION PROGRAM GRANT
FUNDING IN THE AMOUNT OF $256,000; APPROVING A BUDGET
AMENDMENT IN THE AMOUNT OF $256,000; APPROVING A BUDGET TRANSFER FROM MEASURE L PROJECT 2408 IN THE AMOUNT OF
$19,352.42 AND PROJECT 2522 IN THE AMOUNT OF $64,228.33 FOR A TOTAL OF $83,580.75 FOR MATCHING FUNDS ($45,600) AND STAFF TIME ($37,980.75); AND AUTHORIZING THE CITY MANAGER TO
EXECUTE PROJECT AGREEMENT NO. 5

THE CITY COUNCIL
City of Ceres
WHEREAS, the Building on Active Transportation Connectivity and Access within the City Project (the “Project”) will improve bicycle and pedestrian connectivity and safety throughout the community; and
WHEREAS, the Project will include improvements such as bicycle lanes, pedestrian improvements, crosswalk enhancements, and other safety improvements along multiple corridors within the City of Ceres (“City”); and
WHEREAS, the City has been awarded $256,000 in Active Transportation Program grant funding for the design phase of the Project; and
WHEREAS, a new Project String will be established, and the Project will be added to the City’s Capital Improvement Program; and
WHEREAS, the Project requires professional engineering design services to prepare plans, specifications, cost estimates, and complete coordination required for future construction funding; and
WHEREAS, Westwood Professional Services is a qualified firm under the City’s Master Agreement for Professional Consultant Services and has submitted a proposal to provide the required design services; and
WHEREAS, the City accepts the Active Transportation Program Grant funds, and a budget amendment appropriating from 26895.800500 in the amount of $256,000 is necessary and appropriate to cover the Project scope; and
WHEREAS, staff recommends approving a Project Agreement with Westwood Professional Services in the amount of $301,600; and
ITEM 7

ATTACHMENT A
WHEREAS, the Active Transportation Program grant funding will be received on a reimbursable basis; and
WHEREAS, budget transfers from 27195.800500 (2408) in the amount of $19,352.42, and 27195.800500 (2522) in the amount of $64,228.33 are necessary and appropriate to cover the matching funds for the Active Transportation Program Grant and staff time; and WHEREAS, this project does not require the use of General Fund resources.

NOW, THEREFORE, BE IT RESOLVED that the City Council of the City of Ceres does hereby:
1) approve Project Agreement No. 5 to the Master Agreement for Professional Consultant Services with Westwood Professional Services, for design services for the Building on Active Transportation and Connectivity within the City (New Project String) Project (the “Project”) in the amount of $301,600; 2) approve the Project to be added to the Capital Improvement Program; 3) approve a new Project String;
4) accept Active Transportation Program grant funding in the amount of $256,000; 5) approve a budget amendment in the amount of $256,000; 6) approve a budget transfer from Measure L Project 2408 in the amount of $19,352.42 and Project 2522 in the amount of $64,228.33 for a total of $83,580.75 for matching funds ($45,600) and staff time ($37,980.75); 7) , and authorize the City Manager to execute Project Agreement No. 5.

BE IT FURTHER RESOLVED that the City of Ceres Finance Director is hereby authorized and directed to record the appropriate accounting entries PASSED AND ADOPTED by the Ceres City Council at a regular meeting thereof held on the 13th day of April 2026, by the following vote:

AYES: Councilmembers:

NOES: Councilmembers:

ABSENT: Councilmembers:

ABSTAIN: Councilmembers:
_________________________________
Javier Lopez, Mayor
ATTEST:
_________________________________
Fallon Martin, City Clerk
ITEM 7
PROJECT AGREEMENT No. 5

TO THE MASTER AGREEMENT FOR PROFESSIONAL CONSULTANT SERVICES

FOR CAPITAL PROJECTS
Providing: Design Services described in
Exhibit A
Professional Consultant Services for
City of Ceres Engineering Department
Project – Building on Active Transportation and Connectivity within the City (NEW) This Project Agreement is made this 27th day of April 2026, by and between the City of Ceres, a municipal corporation, hereinafter referred to as “CITY”, and Westwood Professional Services, a professional consulting firm, hereinafter referred to as “CONSULTANT”. CITY and CONSULTANT may collectively be referred to as “Parties” or individually as “Party”. There are no other Parties to this Project Agreement.

RECITALS
A. Following a Request for Qualifications (“RFQ”) process to select qualified professional consulting firms to perform services for the City on an as needed basis for various engineering specialties, the Parties entered into a Master Agreement for Professional Consultant Services for Capital Projects (“Master Agreement”) on July 14, 2025.

B. City seeks to hire an independent contractor to perform design services to assist the City with the Building on Active Transportation and Connectivity within the City (the “Project”).

C. Consultant has made a proposal to the City to provide such professional engineering services for the Project. A description of the services Consultant proposes to provide is included in the Scope of Services in Exhibit A (“Services”). City desires to retain Consultant to perform the Services, subject to the terms and conditions set forth in this Agreement, the Master Agreement, and the Amendment.

D. The Parties have outlined the schedule or timeline for providing the Services (“Performance Schedule”), which shall be included in Scope of Services in Exhibit A. The final schedule shall be adjusted for a start date no sooner than the Effective Date of this Agreement.

E. The Parties have outlined the rates and method of payment to consultant for its performance of the Services under the Master Agreement.

ATTACHMENT B ITEM 7

PROJECT AGREEMENT NO. 5

BETWEEN CITY OF CERES AND

WESWOOD PS

Page 2 ends

NOW, THEREFORE, in consideration of the promises and covenants set forth below, the Parties agree as follows:

AGREEMENT
Section 1. Recitals. The recitals set forth above (“Recitals”) are true and correct and are hereby incorporated into and made part of this Agreement by this reference. In the event of any inconsistency between the Recitals and Section 1 through 14 of this Agreement, Sections 1 through 14 shall prevail.

Section 2. Term. The term of this Agreement shall stay in effect until the satisfactory completion of the Services as further described in Exhibit A, but in no case more than one (1) year.

Section 3. Effective Date. This Agreement shall only become effective once all the Parties have executed the Agreement.

Section 4. Incorporation of Master Agreement. The Parties hereby incorporate all terms, conditions, and exhibits contained in the Master Agreement and the Amendment, subject to the limitation that if there are any inconsistencies between the terms of this Agreement and those contained in the Master Agreement and the Amendment, the terms of this Agreement shall prevail.

Section 5. Services. Subject to the terms and conditions set forth in this Agreement, Consultant shall provide City the Services described in Exhibit A. Any request for Services not included in Exhibit A will be considered a request for additional or modified Services (“Modification” or “Modifications”). Consultant shall not perform a Modification nor receive additional compensation for any Modification of the Services unless the Parties agree otherwise in a writing executed by both Parties.

Section 6. Compensation. City shall pay Consultant according to the rates and timing set forth in the Master Agreement. City’s total compensation to Consultant shall be on a time and materials, not to exceed sum of three hundred one thousand six hundred dollars ($301,600.00) (“Maximum Payment”) unless the Parties mutually agree to a Modification in writing otherwise.

Section 7. Notice to Proceed. Consultant shall not commence the performance of the Services until it has been given notice by City in accordance with Section 9 of the Master Agreement (“Notice to Proceed”). The Performance Schedule shall be adjusted for a start ATTACHMENT B ITEM 7

PROJECT AGREEMENT NO. 5

BETWEEN CITY OF CERES AND

WESWOOD PS

Page 3 ends

date no sooner than the Notice to Proceed or execution of this Agreement, whichever comes later.

Section 8. Time of Performance. Consultant warrants that it will commence performance of the Services within thirty (30) calendar days of the Notice to Proceed and shall conform to the Performance Schedule. The time of performance is a material term of this Agreement relied on by City in entering into this Agreement.

Section 9. Assurance of Performance. If, at any time, City believes Consultant may not be adequately performing its obligations under this Agreement or may fail to complete the Services as required by this Agreement, City may submit a written request to Consultant for written assurances of performance and a plan to correct observed deficiencies in Consultant's performance. Failure to provide written assurances subsequent to such written request, constitutes grounds to declare a breach under this Agreement.

Section 10. Liability of City. Notwithstanding any other provision of this Agreement, in no event shall City be liable, regardless of whether any claim is based on contract or tort, for any special, consequential, indirect or incidental damages, including, but not limited to, lost profits or revenue, arising out of or in connection with this Agreement or the Services performed in connection with this Agreement.

Section 11. Exhibits. All “Exhibits” referred to below or attached to herein are by this reference incorporated into this Agreement.

Exhibit Designation Exhibit Title
Exhibit A: Scope of Services
Section 12. Notices. Any notice or communication required hereunder between City and Consultant must be in writing, and may be given either personally, by electronic mail (“email”) (with original forwarded by regular U.S. Mail), by registered or certified mail (return receipt requested), or by Federal Express, UPS or other similar couriers providing overnight delivery. If personally delivered, a notice or communication shall be deemed to have been given when delivered to the Party to whom it is addressed. If given by email transmission, a notice or communication shall be deemed to have been given and received upon actual receipt of the entire document by the receiving Party’s email server. Notices transmitted by email after 5:00 p.m. on a normal business day, or on a Saturday, Sunday or holiday, shall be deemed to have been given and received on the next normal business day. If given by registered or certified mail, such notice or communication shall be deemed to have been given and received on the first to occur of (i) actual receipt by any of the addressees designated below as the party to whom notices are to be sent, or (ii) five (5) days after a registered or certified letter containing such notice, properly addressed, with ATTACHMENT B ITEM 7

PROJECT AGREEMENT NO. 5

BETWEEN CITY OF CERES AND

WESWOOD PS

Page 4 ends

postage prepaid, is deposited in the United States mail. If given by Federal Express or similar courier, a notice or communication shall be deemed to have been given and received on the date delivered as shown on a receipt issued by the courier. Any Party hereto may at any time, by giving ten (10) days written notice to the other Party hereto, designate any other address in substitution of the address to which such notice or communication shall be given. Such notices or communications shall be given to the Parties at their addresses set forth below:

If to City: City of Ceres
2220 Magnolia Street
Ceres, California, 95307
Attention: City Clerk
Tel: (209) 538-5611
[email protected]
With courtesy copies to: City of Ceres
2220 Magnolia Street
Ceres, California, 95307
Attention: City Engineer
Tel: (209) 538-5792
[email protected]
and White Brenner LLP
1414 K Street, 3rd Floor
Sacramento, California 95814
Attention: Nubia I. Goldstein, Esq.

Tel: (916) 468-0950
[email protected]
If to Consultant: Westwood Professional Services
1165 Scenic Dr. Ste A
Modesto, California, 95350
Attention: Scott Roberts, P.L.S., Director
Tel: (559) 668-0009
[email protected]
Section 13. Modification/Termination. No alteration, amendment, modification, or termination of this Agreement shall be valid unless made in writing and executed by all of the Parties to this Agreement subject to the requirements set forth in the Master Agreement.

ATTACHMENT B ITEM 7

PROJECT AGREEMENT NO. 5

BETWEEN CITY OF CERES AND

WESWOOD PS

Page 5 ends

Section 14. General Provisions

14.1. Waiver. No covenant, term, or condition or the breach thereof shall be deemed waived, except by written consent of the Party against whom the waiver is claimed, and any waiver of the breach of any covenant, term, or condition shall not be deemed to be a waiver of any preceding or succeeding breach of the same or any other covenant, term, or condition.

14.2. Assignment. No Party to this Agreement shall assign, transfer, or otherwise dispose of this Agreement in whole or in part to any individual, firm, or corporation without the prior written consent of the other Party. Subject to the forgoing provisions, this Agreement shall be binding upon, and inure to the benefit of, the respective successors and assigns of the Parties hereto.

14.3. Authority. All Parties to this Agreement warrant and represent that they have the power and authority to enter into this Agreement and the names, titles, and capacities herein stated on behalf of any entities, persons, states, or firms represented or purported to be represented by such entities, persons, states or firms and that all former requirements necessary or required by the state or federal law in order to enter into the Agreement have been fully complied with. Further, by entering into this Agreement, neither Party hereto shall have breached the terms or conditions of any other contract or agreement to which such Party is obligated, which such breach would have a material effect hereon.

14.4 Drafting and Ambiguities. Each Party acknowledges that it has reviewed this Agreement with its own legal counsel, and based upon the advice of that counsel, freely entered into this Agreement. Each Party has participated fully in the review and revision of this Agreement. Any rule of construction that ambiguities are to be resolved against the drafting party does not apply in interpreting this Agreement.

14.5. Severability. If this Agreement in its entirety is determined by a court to be invalid or unenforceable, this Agreement shall automatically terminate as of the date of final entry of judgment. If any provision of this Agreement shall be determined by a court to be invalid and unenforceable, or if any provision of this Agreement is rendered invalid or unenforceable according to the terms of any federal or state statute, which becomes effective after the Effective Date of this Agreement, the remaining provisions shall continue in full force and effect and shall be construed to give effect to the intent of this Agreement.

14.5. Counterparts. This Agreement may be executed simultaneously and in several counterparts, each of which shall be deemed an original, but which together shall constitute one and the same instrument.

13.6. Entire Agreement. This Agreement, together with its specific references, attachments and exhibits, constitutes the entire agreement of the Parties with respect to ATTACHMENT B ITEM 7

PROJECT AGREEMENT NO. 5

BETWEEN CITY OF CERES AND

WESWOOD PS

Page 6 ends

the subject matters hereof, and supersedes any and all prior negotiations, understanding and agreements with respect hereto, whether oral or written.

14.7. Supersedes Prior Agreement. It is the intention of the Parties hereto that this Agreement shall supersede any prior agreements, discussions, commitments, or representations, whether written, electronic or oral, between the Parties with respect to the subject matter of this Agreement.

14.8. Mandatory and Permissive. “Shall” and “will” and “agrees” are mandatory. “May” and “can” are permissive.

14.9. Successors and Assigns. All representations, covenants, and warranties specifically set forth in this Agreement, by or on behalf of, or for the benefit of, any or all of the Parties hereto, shall be binding upon and inure to the benefit of such Party, its successors and assigns.

14.10. Headings. Headings used in this Agreement are for reference purposes only and shall not be considered in construing this Agreement.

14.11. Attorney’s Fees and Costs. If any action at law or in equity not resolved pursuant to Section 24 of this Agreement, including action for declaratory relief, is brought to enforce or interpret provisions of this Agreement, the prevailing Party shall be entitled to reasonable attorney's fees and costs, which may be set by the court in the same action or in a separate action brought for that purpose, in addition to any other relief to which such Party may be entitled.

14.12. Necessary Acts and Further Assurances. The Parties shall at their own cost and expense execute and deliver such further documents and instruments and shall take such other actions as may be reasonably required or appropriate to evidence or carry out the intent and purposes of this Agreement.

14.13. Time is of the Essence. Time is of the essence in this Agreement for each covenant and term of a condition herein.
[SIGNATURES ON FOLLOWING PAGE.]
ATTACHMENT B ITEM 7
PROJECT AGREEMENT NO. 5

BETWEEN CITY OF CERES AND

WESWOOD PS

Page 7 ends

IN WITNESS WHEREOF, the Parties have executed this Agreement on the dates indicated below.

Dated: ______________________, 2026 Dated: ______________________, 2026
CITY OF CERES, a municipal corporation
By____________________________
Signature
Douglas Dunford, City Manager
Name and Title

CONSULTANT
By_____________________________
Signature
Scott Roberts, Director
Name and Title

APPROVED AS TO FORM
_______________________________
Nubia I. Goldstein, City Attorney
ATTACHMENT B ITEM 7
ITEM 7
Budget Amendment No.

Fiscal Year
Reference Resolution No . , dated authorizing appropriations for as follows:

Appropriations:

Fund Name Org. Object Project
(if appl.)
Appropriation
Amount
Requested Appropriation
Current Appropriation
Total Appropriation
Estimated Revenues:

Fund Name Org. Object Project
(if appl.)
Appropriation
Amount
Estimated Revenue
Current Estimated Revenue
Total Estimated Revenue
Fiscal Impact:

ITEM 7
ITEM 7

ADMINISTRATIVE BUDGET AMENDMENT

TRANSFER OF FUNDS

FROM ONE ACCOUNT TO ANOTHER
BA #
DATE: ___________
TO: Finance Department
FROM:

Transfer appropriations from:

Fund Name Org. Object Project
(if appl.)
Appropriation
Amount
Total
Transfer appropriations to:

Fund Name Org. Object Project
(if appl.)
Appropriation
Amount
Total
JUSTIFICATION: This administrative budget transfer ______________________________________ Department Head Date ______________________________________ Finance Director Date City Manager Date
ITEM 7
ITEM 7

COUNCIL AGENDA REPORT

CITY COUNCIL
Javier Lopez, Mayor
James Casey, Dist.1
Rosalinda L. Vierra, Dist. 2
Cerina Otero, Dist. 3
Daniel A. Martinez, Dist. 4
MEETING DATE: April 13, 2026
TO: Mayor and City Council
FROM: Douglas D. Dunford, City Manager
CONTACT:

Trenton Johnson, Chief of Police
[email protected], (209) 538-5726
David McCann, Community Service Officer
[email protected], (209) 538-5700, ext. 1010
SUBJECT:

Waiver of Second Reading and Adoption of Ordinance 2026-XXX, An Ordinance of the City Council of the City of Ceres Amending Title 5, Business Licenses and Regulation, Chapter 20, Fireworks Sales of the Ceres Municipal Code
RECOMMENDED COUNCIL ACTION:

Staff recommends the City Council waive the second reading and adopt Ordinance No. 2026- XXX, amending Title 5, Business Licenses and Regulation, Chapter 20, Fireworks Sales of the Ceres Municipal Code.

I. BACKGROUND:

The City of Ceres currently permits the seasonal sale of State Fire Marshal-approved “safe and sane” fireworks pursuant to Title 5, Chapter 20 of the Ceres Municipal Code.

Over recent years, staff have identified recurring issues during the fireworks sales period, including:
• Increased illegal fireworks activity
• Fire hazards and property damage
• Enforcement challenges
• Neighborhood complaints related to noise, debris and safety In response, staff reviewed the existing ordinance to develop recommended revisions.

After introduction and first reading, staff identified and corrected a typographical error in the definition of “Nonprofit,” revising the reference from Section 501(c)(3) to Section 501(c) as a clerical change.

ITEM 8
4914-9324-6621, v. 1
II. REASONS FOR RECOMMENDATION:

Staff is recommending these revisions to the existing ordinance to accomplish the following:
• Broaden the definition of dangerous fireworks
• Address Point of Sale safety requirements
• Strengthen the requirements for the storage of fireworks • Provide updated standards for Safety Training
• Augment the fines imposed for violations
III. FISCAL IMPACTS:

Depending on the fines issued during the fireworks season, these revisions could result in improved cost recovery to the city.

IV. EXISTING POLICY / RELATIONSHIP TO THE STRATEGIC PLAN:

N/A
V. POLICY ALTERNATIVES:

Should Council decide not to approve the revisions to the ordinance, the Police Department will continue to attempt to regulate fireworks sales using the existing municipal code.

VI. INTERDEPARTMENTAL COORDINATION:

N/A
VII. PUBLIC PARTICIPATION:

N/A
VIII. ENVIRONMENTAL REVIEW:

N/A
IX. STEPS FOLLOWING APPROVAL:

The City Council will consider a second reading and adoption of the Ordinance at a later meeting of the City Council.

Approved by: _________________________
Trenton Johnson,
Acting City Manager
Attachments:

1. Attachment A – Ordinance

2. Attachment B – Redline Changes

3. Attachment C – Public Hearing Notice
ITEM 8

ATTACHMENT A
4917-7170-8829, v. 1
ORDINANCE NO. 2026-XXXX

AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF CERES AMENDING TITLE 5, BUSINESS LICENSES AND REGULATION, CHAPTER 20, FIREWORKS

SALES OF THE CERES MUNICIPAL CODE
WHEREAS, the City of Ceres currently permits the seasonal sale of State Fire Marshal-approved “safe and sane” fireworks; and
WHEREAS, staff has identified recurring issues during the fireworks sales period to include increased illegal fireworks activity, fire hazards and property damage, enforcement challenges and neighborhood complaints; and WHEREAS, staff is recommending revisions to address dangerous fireworks, Point of Sale safety requirements, the storage of fireworks, Safety Training, and fines imposed for violations.

NOW, THEREFORE, THE CITY COUNCIL OF THE CITY OF CERES DOES ORDAIN AS FOLLOWS:

SECTION 1. Section 5.20.010, Definitions, of Chapter 20, Fireworks Sales, of Title 5, Business Licenses and Regulations, shall be amended to read as follows:

5.20.010 Definitions.

For the purpose of this chapter, and except where otherwise expressly defined in another section of this chapter, the following words and phrases shall have the meanings provided in this section. Where words and phrases are not expressly defined under this chapter, they shall be construed as their ordinary meaning within the context which they are used:
“Applicant” means the person that files an application for a permit. “Dangerous fireworks” has the same meaning as that term is defined by Health and Safety Code section 12505. Dangerous fireworks may also be defined as illegal fireworks, those fireworks not having the California State Fire Marshal seal for safe and sane fireworks. “Fire Chief” means the Fire Chief or designated representative. “Fireworks sales booth” means the booth, stand, or other approved temporary structure used for the purpose of selling safe and sane fireworks. “Local nonprofit organization” means a nonprofit organization that:

1. Has a primary meeting place within the official sphere of influence of the City of Ceres, as approved by the Local Agency Formation Commission;

2. Has been organized and established within the City of Ceres' sphere of influence for a minimum of one continuous year preceding the filing of the application for a permit; and
ITEM 8

ATTACHMENT A
4917-7170-8829, v. 1

3. Has a bona fide membership of at least ten members who reside in the City of Ceres.
“Nonprofit organization” means any nonprofit association or corporation organized primarily for veteran, patriotic, welfare, religious, civic betterment or charitable purposes that has been approved by the Internal Revenue Service as a tax-exempt organization under Section 501(c) of the Internal Revenue Code. Groups that are integral part of a recognized national organization must also operate under the organization’s IRSrecognized 501(c) tax-exempt status. “Owner-occupant” means the record owner of real property as listed in the most current equalized assessment roll as maintained by the Stanislaus County Assessor. “Permit” means a permit for the sale of safe and sane fireworks issued pursuant to section

5.20.030.
“Permittee” means a local nonprofit organization that has received a permit for the sale of safe and sane fireworks.
“Responsible party” means any person with an ownership interest or right of possession of the real property where unpermitted fireworks are possessed, sold, used, manufactured or discharged, including, but not limited to:

1. Any owner-occupant.

2. Any lessee, subtenant, licensee, or other person having possessory control over a property, structure, or parcel of land.

3. Any person that organizes, supervises, officiates, conducts, or controls the gathering or any other person accepting responsibility for such a gathering. “Safe and sane fireworks” has the same meaning as that term is defined by California Health and Safety Code section 12529. All safe and sane fireworks shall be approved by the California Fire Marshal and labeled as safe and sane.

SECTION 2. Section 5.20.030, Permit applications, of Chapter 20, Fireworks Sales, of Title 5, Business Licenses and Regulations, shall be amended to read as follows:

5.20.030 Permit applications.

A. The Fire Chief shall cause a standard application to be prepared for a permit. In addition to the requirements of section 5.02.010 the permit application shall include all of the following:

1. Proper identification and signature of the applicant.

2. A proposed location of the fireworks sales booth that includes the nine digit accessor's parcel number of the Stanislaus County Assessor.

3. Proof of safety training.

4. A site plan for the fireworks sales booth.

5. The written consent of the owner of the property upon which the proposed fireworks sales booth will be located.

ITEM 8

ATTACHMENT A
4917-7170-8829, v. 1

6. A nonrefundable applicable fee as established by resolution of the City Council pursuant to Section 9.30.120.

7. Any other reasonable information that the Fire Chief may deem necessary to properly implement and administer the provisions of this chapter.

B. Applications shall be submitted during normal business hours from April 15 through June 15 of the same year.

C. All applications shall be submitted to the Fire Chief on or before June 15 of each year. Each application must be complete and contain all required information. Any application that is not properly completed and submitted to the office of the Fire Chief by 5:00 p.m. on June 15 will not be considered.

D. The Fire Chief or his or her designee shall review all submitted applications, and may consult with the Departments of Public Works, Engineering Services, and Community Development to ensure that the proposed location meets existing zoning regulations and does not create pedestrian or vehicular traffic hazards.

SECTION 3. Section 5.20.060, Firework sales, of Chapter 20, Fireworks Sales, of Title 5, Business Licenses and Regulations, shall be amended to read as follows:

5.20.060 Fireworks sales.

A. Safe and sane fireworks may only be sold or offered for sale from 12:00 noon to 10:00 p.m. on June 28 and from 9:00 a.m. to 10:00 p.m. from June 29 through July

6. B. Each of the following are mandatory point-of-sale safety requirements:

1. No person under the age of 18 shall sell, or handle for sale, any fireworks.

2. No person under the age of 18 shall purchase or be allowed to purchase any fireworks.

3. Smoking, open flame, or spark-producing equipment shall be prohibited for a distance of 100 feet in all directions of a fireworks sale booth.

4. Dry grass, weeds, trash, and all other combustible material shall be removed for a distance of 20 feet if the booth is on concrete or asphalt or 100 feet when on an open, unimproved lot in all directions of a fireworks sale booth.

5. Fireworks shall not be discharged within 150 feet in all directions of a fireworks sale booth.

C. Merchandise may be displayed in an approved glass-enclosed counter or showcase, or displayed in fireworks sale booths constructed in the following manner:

1. Walls and roof shall be of plywood at least one-third-inch thickness or of an approved noncombustible material.

2. The fireworks sale booth shall have a roof.

3. Notwithstanding an exit door, walls shall extend to a minimum height of six feet, eight inches on at least three sides. These three sides shall not have any openings.

ITEM 8

ATTACHMENT A
4917-7170-8829, v. 1

4. Two exit doors shall be provided in each fireworks sale booth, with a minimum size of 24 inches in width and six feet in height. Exits shall be maintained clear and unobstructed at all times while open to the public.

5. The front wall of the fireworks sale booth shall provide a physical barrier not less than 18 inches in height between the public and the merchandise on display.

6. Approved "NO SMOKING" signs shall be securely fastened to the fireworks sale booth and prominently displayed in and on the exterior of the stand.

7. Approved "NO SALES TO PERSONS UNDER THE AGE OF 18" signs shall be securely fastened to the fireworks sale booth and prominently displayed in and on the exterior of the booth.

8. An approved fire extinguisher having a minimum U.L. classification of 2A shall be located in the fireworks sale booth near the exit and be readily accessible.

SECTION 4. Section 5.20.070, Storage of fireworks, of Chapter 20, Fireworks Sales, of Title 5, Business Licenses and Regulations, shall be amended to read as follows:

5.20.070 Storage of fireworks.

A. Permittees may only store safe and sane fireworks within the City solely during the period of June 22 through July 15 of each year.

B. Safe and sane fireworks that are not being sold or displayed with the intent to sell shall be stored in the following manners:

1. Within the permitted fireworks sale booth with a responsible adult on the premises at all times.

2. In a completely enclosed and locked utility type trailer constructed of onequarter-inch plywood or other approved noncombustible material.

3. In a completely detached garage on residential property with a minimum of tenfoot clearance to other structures or property lines and 100 feet from any place of habitation. There shall be no open flame or spark producing equipment, or class 1 flammable liquids stored or used within the garage.

4. Fireworks shall not be stored within 100 feet of any building classified or used as a public or private school, day care facility, residential care facility, hospital, place of detention, public oil/gas station, or public garage, or any place of public assembly that can accommodate 50 or more persons.

5. The following information shall be submitted to and approved by the Fire Chief:
a. Storage location.
b. Description of storage facility.

SECTION 5. Section 5.20.080, Permittee safety training, of Chapter 20, Fireworks Sales, of Title 5, Business Licenses and Regulations, shall be amended to read as follows:

5.20.080 Permittee safety training.

Each calendar year one or more representatives from each permittee shall attend a fireworks sales booth safety seminar conducted by the Fire Department. Failure to attend the seminar shall result in the revocation of the permittee's permit for that calendar year.

ITEM 8

ATTACHMENT A
4917-7170-8829, v. 1
SECTION 6. Section 5.20.100, Dangerous fireworks prohibited, of Chapter 20, Fireworks Sales, of Title 5, Business Licenses and Regulations, shall be amended to read as follows:

5.20.100 Dangerous fireworks prohibited.

A person shall not sell, use, possess, manufacture, or discharge dangerous fireworks within the City as defined by section 5.20.010.

SECTION 7. Section 5.20.110, Penalties, of Chapter 20, Fireworks Sales, of Title 5, Business Licenses and Regulations, shall be amended to read as follows:

5.20.110 Penalties.

A. In addition to any other remedies set forth in this title, administrative penalties may be imposed against any responsible party for violations of this chapter. The administrative penalty for violations of this chapter shall be as follows within a 36- month period:

1. First violation: $2,500.00 fine.

2. Second violation: $3,500.00 fine.

3. Third violation and any thereafter: $4,500.00 fine.

Any violation of this section shall constitute a misdemeanor, which may result in imprisonment for a period not exceeding six (6) months. Any person who possesses less than 25 pounds of dangerous fireworks is also in violation of 12700 of the California Health and Safety Code and the City may refer the violation to the District Attorney’s Office for criminal prosecution.

B. Any person who engages in the sales, manufacture, or distribution of dangerous fireworks shall be guilty of a misdemeanor and may be subject to an administrative penalty of $10,000.00 per occurrence or imprisonment for a period not exceeding six (6) months. Any person who sales, manufactures, or transports dangerous fireworks is also in violation of 12676 of the California Health and Safety Code and can have the violation referred to the District Attorney’s Office for criminal prosecution.

C. Every owner, occupant, lessee, tenant, or holder of any possessory interest of a residence or other private property within the City is required to maintain, manage and supervise property and all persons thereon in a manner so as not to violate the provisions of this chapter. A responsible party need not be present at the time dangerous fireworks are possessed, manufactured, sold, used, or discharged in order for the City to issue an administrative citation under this section.

D. For the purposes of this section, the term “responsible party” means any person with an ownership interest or right of possession of the real property where unpermitted fireworks are possessed, sold, used, manufactured or discharged, including but not limited to:

ITEM 8

ATTACHMENT A
4917-7170-8829, v. 1

1. Any owner-occupant

2. Any lessee, subtenant, licensee, or other person having possessory control over a property, structure or parcel of land.

3. Any person that organizes, supervises, officiates, conducts or controls the gathering or any other person accepting responsibility for such a gathering.

4. Every parent, guardian or other person, having the legal care, custody or control of any person under the age of eighteen (18) years old may be issued a citation in accordance with the provisions of this article, in addition to any citation that may be issued to the offending minor.

E. Nothing in this section shall be intended to limit any of the penalties provided for under the Health and Safety Code or Penal Code.

SECTION 2. SEVERABILITY. If any section, subdivision, sentence, clause, phrase, or portion of this Ordinance is, for any reason, held invalid or unconstitutional by any court of competent jurisdiction, such portion shall be deemed a separate, distinct, and independent provision, and such holding shall not affect the validity of the remaining portions thereof.

SECTION 3. PUBLICATION AND EFFECTIVE DATE. This ordinance shall become effective thirty (30) days from and after its final passage and adoption, provided it is published in a newspaper of a general circulation at least within fifteen (15) days after its passage or a summary of the Ordinance is published in a newspaper of general circulation at least five (5) days prior to adoption and again at least fifteen (15) days after its passage.

SECTION 4. CERTIFICATION OF COUNCIL ADOPTION AND APPROVAL. This Ordinance was introduced at a regular meeting of the City Council held on the 23rd day of March 2026, and passed and adopted as Ordinance No. 2026-XXXX at a regular meeting of the City Council held on the 13th day of April 2026, by the following vote:

AYES: Councilmembers:

NOES: Councilmembers:

ABSENT: Councilmembers:

ABSTAIN: Councilmembers:

APPROVED:
___________________________________
Javier Lopez, Mayor
ATTEST:
________________________________
Fallon Martin, City Clerk
APPROVED AS TO FORM:
________________________________
Nubia I. Goldstein, City Attorney
ITEM 8
Title 5 – Business Licenses and Regulations
Chapter 20 - Fireworks Sales Amended

5.20.010 Definitions.

For the purpose of this chapter, and except where otherwise expressly defined in another section of this chapter, the following words and phrases shall have the meanings provided in this section. Where words and phrases are not expressly defined under this chapter, they shall be construed as their ordinary meaning within the context which they are used:
“Applicant” means the person that files an application for a permit. “Dangerous fireworks” has the same meaning as that term is defined by Health and Safety Code section 12505. Dangerous fireworks may also be defined as illegal fireworks, those fireworks not having the California State Fire Marshal seal for safe and sane fireworks. “Fire Chief” means the Fire Chief or designated representative. “Fireworks sales booth” means the booth, stand, or other approved temporary structure used for the purpose of selling safe and sane fireworks. “Local nonprofit organization” means a nonprofit organization that:

1. Has a primary meeting place within the official sphere of influence of the City of Ceres, as approved by the Local Agency Formation Commission;

2. Has been organized and established within the City of Ceres' sphere of influence for a minimum of one continuous year preceding the filing of the application for a permit; and

3. Has a bona fide membership of at least ten members who reside in the City of Ceres.
“Nonprofit organization” means any nonprofit association or corporation organized primarily for veteran, patriotic, welfare, religious, civic betterment or charitable purposes, that has been approved by the Internal Revenue Service as a tax-exempt organization under Section 501(c)(3) of the Internal Revenue Code. Groups that are integral part of a recognized national organization must also operate under the organization’s IRSrecognized 501(c)(3) tax-exempt status.which has been issued a tax exempt certificate as required under the California Revenue and Taxation Code or a group that is an integral part of of a recognized national organization having a tax exempt status. “Owner-occupant” means the record owner of real property as listed in the most current equalized assessment roll as maintained by the Stanislaus County Assessor. “Permit” means a permit for the sale of safe and sane fireworks issued pursuant to section

5.20.030.
“Permittee” means a local nonprofit organization that has received a permit for the sale of safe and sane fireworks.
“Responsible party” means any person with an ownership interest or right of possession of the real property where unpermitted fireworks are possessed, sold, used, manufactured or discharged, including, but not limited to:

ATTACHMENT B ITEM 8
4931-9816-5405, v. 1

1. Any owner-occupant.

2. Any lessee, subtenant, licensee, or other person having possessory control over a property, structure, or parcel of land.

3. Any person that organizes, supervises, officiates, conducts, or controls the gathering or any other person accepting responsibility for such a gathering. “Safe and sane fireworks” has the same meaning as that term is defined by California Health and Safety Code section 12529. All safe and sane fireworks shall be approved by the California Fire Marshal and labeled as safe and sane.

5.20.030 Permit applications.

A. The Fire Chief shall cause a standard application to be prepared a standard application for a permit. In addition to the requirements of section 5.02.010 the permit application shall include all of the following:

1. Proper identification and signature of the applicant.

2. A proposed location of the fireworks sales booth that includes the nine digit accessor's parcel number of the Stanislaus County Assessor.

3. Proof of safety training.

4. A site plan for the fireworks sales booth.

5. The written consent of the owner of the property upon which the proposed fireworks sales booth will be located.

6. A nonrefundable applicable fee as established by resolution of the City Council pursuant to Section 9.30.120.

7. Any other reasonable information that the Fire Chief may deem necessary to properly implement and administer the provisions of this chapter.

B. Applications shall be submitted during normal business hours from April 15 through June 15 of the same year.

C. All applications shall be submitted to the Fire Chief on or before June 15 of each year. Each application must be complete and contain all required information. Any application that is not properly completed and submitted to the office of the Fire Chief by 5:00 p.m. on June 15 will not be considered.

D. The Fire Chief or his or her designee shall review all submitted applications, and may consult with the Departments of Public Works, Engineering Services, and Community Development to ensure that the proposed location meets existing zoning regulations and does not create pedestrian or vehicular traffic hazards.

5.20.060 Fireworks sales.

A. Safe and sane fireworks may only be sold or offered for sale from 12:00 noon to 10:00 p.m. on June 28 and from 9:00 a.m. to 10:00 p.m. from June 29 through July

6. B. Each of the following are mandatory point-of-sale safety requirements:

ATTACHMENT B ITEM 8
4931-9816-5405, v. 1

1. No person under the age of 18 shall sell, or handle for sale, any fireworks.

2. No person under the age of 18 shall purchase or be allowed to purchase any fireworks.

3. Smoking, open flame, or spark-producing equipment shall be prohibited for a distance of 100 feet in all directions of a fireworks sale booth.

4. Dry grass, weeds, trash, and all other combustible material shall be removed for a distance of 20 feet if the booth is on concrete or asphalt or 100 feet when on an open, unimproved lot in all directions of a fireworks sale booth.

5. Fireworks shall not be discharged within 150 feet in all directions of a fireworks sale booth.

C. Merchandise may be displayed in an approved glass-enclosed counter or showcase, or displayed in fireworks sale booths constructed in the following manner:

1. Walls and roof shall be of plywood at least one-third-inch thickness or of an approved noncombustible material.

2. The fireworks sale booth shall have a roof.

3. Notwithstanding an exit door, walls shall extend to a minimum height of six feet, eight inches on at least three sides. These three sides shall not have any openings.

4. Two exit doors shall be provided in each fireworks sale booth, with a minimum size of 24 inches in width and six feet in height. Exits shall be maintained clear and unobstructed at all times while open to the public.

5. The front wall of the fireworks sale booth shall provide a physical barrier not less than 18 inches in height between the public and the merchandise on display.

6. Approved "NO SMOKING" signs shall be securely fastened to the fireworks sale booth and prominently displayed in and on the exterior of the stand.

7. Approved "NO SALES TO PERSONS UNDER THE AGE OF 18" signs shall be securely fastened to the fireworks sale booth and prominently displayed in and on the exterior of the booth.

8. An approved fire extinguisher having a minimum U.L. classification of 2A shall be located in the fireworks sale booth near the exit and be readily accessible.

5.20.070 Storage of fireworks.

A. Permittees may only store safe and sane fireworks within the City solely during the period of June 22 through July 15 of each year.

B. Safe and sane fireworks that are not being sold or displayed with the intent to sell shall be stored in the following manners:

1. Within the permitted fireworks sale booth with a responsible adult on the premises at all times.

ATTACHMENT B ITEM 8
4931-9816-5405, v. 1

2. In a completely enclosed and locked utility type trailer constructed of onequarter-inch plywood or other approved noncombustible material.

3. In a completely detached garage on residential property with a minimum of tenfoot clearance to other structures or property lines and 100 feet from any place of habitation. There shall be no open flame or spark producing equipment, or class 1 flammable liquids stored or used within the garage.

4. Fireworks shall not be stored within 100 feet of any building classified or used as a public or private school, day care facility, residential care facility, hospital, place of detention, public oil/gas station, or public garage, or any place of public assembly that can accommodate 50 or more persons.

5. The following information shall be submitted to and approved by the Fire Chief will be required:
a. Storage location.
b. Description of storage facility.

5.20.080 Permittee safety training.

Each calendar year one or more representatives from each permittee shall attend a fireworks sales booth safety seminar conducted by the Fire Department or the fireworks industry. Failure to attend the seminar shall result in the revocation of the permittee's permit for that calendar year.

5.20.100 Dangerous fireworks prohibited.

A person shall not sell, use, possess, manufacture, or discharge dangerous fireworks within the City as defined by section 5.20.010.

5.20.110 Penalties.

A. In addition to any other remedies set forth in this title, administrative penalties may be imposed against any responsible party for violations of this chapter. The administrative penalty for violations of this chapter shall be $2,500.000 or imprisonment for a period not exceeding six months. as follows within a 36-month period:

1. First violation: $2,500.00 fine.

2. Second violation: $3,500.00 fine.

3. Third violation and any thereafter: $4,500.00 fine.

Any violation of this section shall constitute a misdemeanor, which may result in imprisonment for a period not exceeding six (6) months. Any person who possesses less than 25 pounds of dangerous fireworks is also in violation of 12700 of the California Health and Safety Code and the City may refer the violation to the District Attorney’s Office for criminal prosecution.

B. Any person who engages in the sales, manufacture, or distribution of dangerous fireworks shall be guilty of a misdemeanor and may be subject to an administrative ATTACHMENT B ITEM 8
4931-9816-5405, v. 1
penalty of $10,000.00 per occurrence or imprisonment for a period not exceeding six (6) months. Any person who sales, manufactures, or transports dangerous fireworks is also in violation of 12676 of the California Health and Safety Code and can have the violation referred to the District Attorney’s Office for criminal prosecution.

B.C.Every owner, occupant, lessee, tenant, or holder of any possessory interest of a residence or other private property within the City is required to maintain, manage and supervise property and all persons thereon in a manner so as not to violate the provisions of this chapter. A responsible party need not be present at the time dangerous fireworks are possessed, manufactured, sold, used, or discharged in order for the City to issue an administrative citation under this section.

D. For the purposes of this section, the term “responsible party” means any person with an ownership interest or right of possession of the real property where unpermitted fireworks are possessed, sold, used, manufactured or discharged, including but not limited to:

1. Any owner-occupant

2. Any lessee, subtenant, licensee, or other person having possessory control over a property, structure or parcel of land.

3. Any person that organizes, supervises, officiates, conducts or controls the gathering or any other person accepting responsibility for such a gathering.

4. Every parent, guardian or other person, having the legal care, custody or control of any person under the age of eighteen (18) years old may be issued a citation in accordance with the provisions of this article, in addition to any citation that may be issued to the offending minor.

C.E.Nothing in this section shall be intended to limit any of the penalties provided for under the Health and Safety Code or Penal Code.

ATTACHMENT B ITEM 8
ITEM 8

ATTACHMENT C
City of Ceres

NOTICE OF PUBLIC HEARING
NOTICE IS HEREBY GIVEN THAT THE CERES CITY COUNCIL will hold a public hearing in the Council Chambers at 2701 Fourth Street, Ceres, CA on March 23, 2026, at 6:00 p.m. or as soon as possible thereafter, to receive and consider all evidence and reports relative to adoption of the following: An Ordinance of the City Council of the City of Ceres amending and adding to Title 5 – Business Licenses and Regulations, Chapter 20 – Fireworks Sales, amending Section 5.20.010 – Definitions, amending Section

5.20.060 – Fireworks Sales, amending Section 5.20.070 – Storage of Fireworks, amending Section 5.20.080 – Permittee Safety Training, amending Section 5.20.100 – Dangerous Fireworks Prohibited, and amending Section 5.20.110 – Penalties, of the City of Ceres Municipal Code.

The Ceres City Council will consider an amendment to the Ceres Municipal Code to broaden the definition of dangerous fireworks, address Point of Sale safety requirements, strengthen the requirements for the storage of fireworks, provide updated standards for safety training and augment the fines imposed for violations. This amendment is being proposed in response to staff identifying the following recurring issues during the fireworks sales period: increased illegal fireworks activity, fire hazards and property damage, enforcement challenges and neighborhood complaints.

All interested parties are invited to attend said hearing and express opinions or submit evidence for or against proposal as outlined above.

Further information on the above hearing may be obtained or viewed at the office of the City Clerk, City Hall, 2220 Magnolia Street Ceres, CA 95307 or by telephone at (209) 538-5731.

If a citizen wishes to challenge the nature of the above actions in court, they may be limited to raising only those issues they or someone else raised at the public hearing described in the notice, or in written correspondence delivered to the City of Ceres, at, or prior to the public hearing.
/s/ Fallon Martin, City Clerk
Date Notice Posted: March 11, 2026
ITEM 8
ITEM 8

COUNCIL AGENDA REPORT

CITY COUNCIL
Javier Lopez, Mayor
James Casey, Dist.1
Rosalinda L. Vierra, Dist. 2
Cerina Otero, Dist. 3
Daniel A. Martinez, Dist. 4
MEETING DATE: April 13, 2026
TO: Mayor and City Council
FROM: Nubia I. Goldstein, City Attorney
CONTACT: Nubia I. Goldstein, City Attorney
SUBJECT:

Waiver of Second Reading and Adoption of Ordinance No. 2026- XXXX, An Ordinance of the City Council of the City of Ceres Amending Title 5, Business Licenses and Regulations, Chapter 3, General Permit Procedure, Section 010, General and Title 5, Business Licenses and Regulation, Chapter 22, Cannabis Pilot Program, of the Ceres Municipal Code
Waiver of Second Reading and Adoption of Ordinance No. 2026- XXXX, A Zoning Ordinance Text Amendment of the City Council of the City of Ceres Adding Chapter 44, Cannabis Conditional Use Permits, to Title 18, Zoning, and Amending Sections 18.02.010,

18.13.020, 18.16.040, 18.17.040, 18.18.040, 18.19.040, and 18.20.040, of Title 18, Zoning, of the Ceres Municipal Code
RECOMMENDED COUNCIL ACTION:

Staff recommends Council take the following actions to revise the City of Ceres’ Cannabis Business Regulations in the Ceres Municipal Code:

1. Approve the second reading, read by title only, and adopt Ordinance No. 2026-XXX (Attachment A), reading by title only, waiving further reading, an Ordinance of the City of Ceres amending Section 5.03.010, General, of Chapter 5.03, General Permit Procedure, and amending Chapter 5.22, Cannabis Pilot Program, of Title 5, Business License and Regulation, of the Ceres Municipal Code.

2. Approve the second reading, read by title only, and adopt Zoning Ordinance Text Amendment No. 2026-XXX (Attachment B), reading by title only, waiving further reading, a Zoning Ordinance Text Amendment of the Ceres City Council adding Chapter 18.44, Cannabis Conditional Use Permits, to Title 18, Zoning, and amending Sections

18.02.010, 18.13.020, 18.16.040, 18.17.040, 18.18.040, 18.19.040, and 18.20.040, of Title 18, Zoning of the Ceres Municipal Code.

ITEM 9a & 9b
4928-9510-1595, v. 3
I. BACKGROUND:

The Medical and Adult-Use Cannabis Regulation and Safety Act (“MAUCRSA”), codified in Business and Professions Code section 26000 et seq., established the comprehensive state regulatory framework for commercial medicinal and adult-use cannabis activity.

MAUCRSA expressly preserves the authority of local jurisdiction to regulate or prohibit cannabis operations within their boundaries.

The City of Ceres (“City”) has permitted and regulated medical and adult use cannabis businesses under the Cannabis Pilot Program codified in Chapter 5.22 (“Pilot Program”), of the Ceres Municipal Code (“CMC”), established on May 29, 2018. Since the establishment of the Pilot Program, the City has gained a better understanding of the commercial cannabis industry and its impact to public health, safety, and welfare. Based on this experience, staff and the Ceres City Council (“City Council”) have identified the need to update the Pilot Program to a permanent regulatory structure to strengthen the City’s enforcement authority and ensure consistent compliance with local and state regulations.

II. DISCUSSION:

The City Council has held multiple public discussions and heard from staff, City cannabis operators, and the public regarding potential changes to the City’s regulation of cannabis businesses. Based on these discussions, staff has prepared substantial amendments to the CMC to implement the City Council’s direction regarding updates to the City’s cannabis regulations.

The updates to cannabis business regulations are contained in two separate ordinances.

The first Ordinance proposes amendments to section 5.03.010, General, of Chapter 5.03, General Permit Procedure, and amends Chapter 5.22, Cannabis Pilot Program. The second Ordinance, is a zoning ordinance text amendment that adds Chapter 18.44, Cannabis Conditional Use Permits to the City’s Zoning Ordinance and amends related zoning provisions to authorize cannabis businesses within specified zoning districts.

The revisions to the CMC will result in cannabis businesses being subject to three entitlements: (1) a City business license, (2) a development agreement, and (3) a cannabis conditional use permit. Although each entitlement is governed by a separate chapter of the CMC, they are intended to operate collectively to ensure compliance with applicable state and local laws. Together, these entitlements create an integrated and cohesive regulatory framework governing cannabis businesses within the City.

On March 23, 2026, the City Council, by unanimous vote, approved the first reading and introduced both Ordinances, with revisions to the first Ordinance to implement a cap of two cannabis retail dispensaries in the City and have the Chief of Police be responsible for enforcement of cannabis regulations. Those revisions have been made to the Ordinance for the second reading.

1. Proposed Changes to Section 5.03.010 General, of Chapter 5.03, General Permit Procedure.

Section 5.03.010, subdivision (A), currently requires commercial cannabis businesses to obtain a separate permit issued by the City. The City Council has directed staff to ITEM 9a & 9b
4928-9510-1595, v. 3
eliminate this standalone permit requirement and instead rely on development agreements and cannabis conditional use permits as the primary regulatory mechanisms for commercial cannabis businesses.

The proposed amendment to section 5.03.010 aligns the CMC accordingly by removing the redundant cannabis business permit requirement. Cannabis businesses will remain subject to the requirement to obtain and maintain a general City business license pursuant to Title 5.

2. Proposed Changes to Chapter 5.22, Cannabis Business Regulations.

Chapter 5.22, Cannabis Pilot Program, currently contains the City’s cannabis business regulations. The proposed ordinance would repeal Chapter 5.22 in its entirety and replace it with a revised Chapter 5.22, Cannabis Business Regulations.

The proposed Chapter 5.22 contains general requirements on cannabis businesses, provides the procedure for cannabis businesses to obtain a development agreement, and establishes the City’s enforcement mechanisms.

The City Council has expressed interest in establishing a limit on the number of cannabis dispensaries permitted within the City. The Council was presented with two alternatives and ultimately selected a cap of two dispensaries. This cap was incorporated into the Ordinance for second reading.

The revised Chapter 5.22 clarifies and formalizes the procedures for cannabis business development agreements. The Chapter establishes defined application requirements and approval procedures, including fingerprinting and police-conducted background checks for all cannabis business owners.

The proposed amendments to Chapter 5.22 expand the City’s enforcement authority by expressly authorizing inspections, establishing administrative fines for minor violations, incorporating nuisance abatement procedures for code violations, and providing a costrecovery mechanism to reimburse the City for expenses incurred in connection with enforcement actions. The City Council directed staff to specify that the Chief of Police is responsible for enforcement of this chapter. Staff has incorporated this revision into the Ordinance for second reading.

3. Proposed Addition of Chapter 18.44, Cannabis Conditional Use Permits.

Adding Chapter 18.44, Cannabis Conditional Use Permits, is an amendment to the City’s Zoning Ordinance. On February 2, 2026, the Ceres Planning Commission passed a resolution recommending the City Council adopt the Zoning Ordinance Text Amendment to add Chapter 18.44 to the CMC as required by state law.

The addition of Chapter 18.44 to the CMC requires all cannabis businesses operating within the City to obtain and maintain a Cannabis Conditional Use Permit. Each permit establishes property-specific conditions of approval that govern the operation of the cannabis business and with which the business must continuously comply.

ITEM 9a & 9b
4928-9510-1595, v. 3
Cannabis conditional use permits start with the same cannabis business application used for development agreements. The cannabis conditional use permit then follows the existing procedure for conditional use permits which are approved by the Planning Commission.

Chapter 18.44 provides the minimum conditions of approval for each cannabis business.

The Planning commission may impose more stringent conditions based on an applicants circumstances. The conditions of approval include but are not limited to:
• Premises Conditions;
• Security Conditions;
• Cannabis Waste Conditions;
• Cannabis Odor Conditions;
• Cannabis Cultivation Conditions;
• Cannabis Manufacturing Conditions;
The City’s enforcement options for cannabis conditional use permits include administrative citations and revocation. Specific circumstances under which a cannabis conditional use permit may be revoked are also provided by the Chapter. Revocation proceedings follow the same procedures applicable to the revocation of traditional conditional use permits under Chapter 18.30.

In addition to adding chapter 18.44, the ZOTA amends multiple sections of Title 18 to identify where cannabis businesses are permitted as conditional uses. The City’s current cannabis businesses are located in Planned Community and Industrial zones. Staff has proposed that cannabis businesses may be conditional uses in the following zones:
• Planned Community - CMC Chapter 18.13
• Community Commercial – CMC Chapter 18.16
• Wholesale Commercial - CMC Chapter 18.17
• Highway Commercial - CMC Chapter 18.18
• Light Industrial - CMC Chapter 18.19
• General Industrial - CMC Chapter 18.20
III. FISCAL IMPACTS:

The proposed amendments clarify and strengthen the City’s enforcement authority over cannabis businesses. By establishing clearer compliance mechanisms and enforcement tools, the amendments are expected to reduce the administrative and legal costs associated with pursuing violations and to enhance the City’s ability to recover fines, fees, and other revenues owed by cannabis businesses.

V. POLICY ALTERNATIVES:

1. Introduce the ordinances for first reading with the City Council’s preference related to the limit on cannabis businesses permitted in the City; or

2. Provide direction to staff related to the ordinances; or

3. Deny the ordinances.

ITEM 9a & 9b
4928-9510-1595, v. 3
VI. INTERDEPARTMENTAL COORDINATION:

N/A.

VII. PUBLIC PARTICIPATION:

The public is encouraged to provide input at the City Council meeting.

VIII. ENVIRONMENTAL REVIEW:

The proposed Ordinances are a general policy change that does not result in a direct or reasonably foreseeable indirect physical change in the environment and, therefore, does not meet the definition of a “project” under the California Environmental Quality Act (“CEQA”) pursuant to Section 21065 of the Public Resources Code and Section 15378 of the CEQA Guidelines (Title 14, California Code of Regulations).

IX. STEPS FOLLOWING APPROVAL:

The City Council will consider approval of the second reading and adoption of the Ordinance at a later meeting of the City Council.

Approved by: _________________________
Trenton Johnson,
Acting City Manager
Attachments:

1. Attachment A – Cannabis Pilot Program Ordinance Amendment

2. Attachment B – Zoning Ordinance Text Amendment

3. Attachment C – Redline Changes to Cannabis Pilot Program Ordinance

4. Attachment D – Redline Changes to Zoning Ordinance Text Amendment

5. Attachment E – Public Hearing Notice
ITEM 9a & 9b
ITEM 9a & 9b

ATTACHMENT A
ORDINANCE NO. 2026-XXXX

AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF CERES AMENDING TITLE 5, BUSINESS LICENSES AND REGULATIONS, CHAPTER 3, GENERAL PERMIT PROCEDURE, SECTION 010, GENERAL AND TITLE 5, BUSINESS LICENSES AND REGULATION, CHAPTER 22, CANNABIS PILOT PROGRAM, OF

THE CERES MUNICIPAL CODE
WHEREAS, the Medicinal and Adult-Use Cannabis Regulation and Safety Act (“MAUCRSA”), codified in Business and Professions Code section 26000 et seq., establishes the comprehensive state regulatory framework for commercial medicinal and adult-use cannabis activity, and expressly preserves the authority of local jurisdictions to regulate or prohibit such operations within their boundaries; and WHEREAS, on May 29, 2018, the City Council adopted Ordinance No. 2018-1045, establishing a Cannabis Business Pilot Program (“Pilot Program”) regulating the operation of cannabis businesses within the City which is now codified in Chapter 5.22 of the Ceres Municipal Code (“CMC”); and
WHEREAS, on November 8, 2018, Ceres voters approved Measure W, which authorized the City Council to impose a business license tax of up to fifteen percent (15%) of the gross receipts of any marijuana-related business (“Cannabis Business Tax”); and WHEREAS, since the establishment of the Pilot Program, the City has gained a better understanding of the cannabis industry, which has informed how the City intends to regulate cannabis businesses going forward; and
WHEREAS, the City Council finds that updating the Pilot Program to establish a permanent regulatory structure for cannabis businesses is necessary to protect the public health, safety, and welfare; and
WHEREAS, as part of these permanent regulations, the City Council has determined to update the Pilot Program to implement the Cannabis Business Tax, clarify procedural requirements for cannabis business entitlements, and strengthen the City’s enforcement authority to further protect the public health, safety, and welfare of the community; and
WHEREAS, prior to implementing the Cannabis Business Tax, the City must make minor adjustments to the general business license procedure for City business licenses section to ensure consistency with revisions to the Pilot Program and to provide for proper administration, collection, and enforcement of the Cannabis Business Tax; and WHEREAS, the City Council now wishes to update Chapter 5.22, Cannabis Business Pilot program to implement a permanent regulatory structure for cannabis businesses within the City; and
ITEM 9a & 9b

ATTACHMENT A
4923-0061-3531, v. 3
WHEREAS, the proposed Ordinance constitutes a general policy change that does not result in a direct or reasonably foreseeable indirect physical change in the environment and, therefore, does not meet the definition of a “project” under the California Environmental Quality Act (“CEQA”) pursuant to Section 21065 of the Public Resources Code and Section 15378 of the CEQA Guidelines (Title 14, California Code of Regulations).

NOW, THEREFORE, THE CITY COUNCIL OF THE CITY OF CERES ORDAINS AS FOLLOWS:

SECTION 1. Section 5.03.010, General, of Chapter 3, General Permit Procedure, of Title 5, Business Licenses and Regulations, of the Ceres Municipal Code shall be amended to remove subsection 16, Commercial cannabis businesses, and move 17, Sidewalk vending, to 16 of Paragraph (A) as follows:

5.03.010 – General.

A. Certain activities in the City require permits issued by the City Manager or designee.

The following activities require a permit issued by the City:

1. Patrol services;

2. Motion picture and television production;

3. Alcoholic beverages;

4. Junk dealers and scrap metal recyclers;

5. Special events and temporary street closures;

6. Public dances, dancing places, and concerts;

7. Fortunetelling;

8. Taxicabs;

9. Adult entertainment businesses;

10. Garage sales;

11. Massage establishments;

12. Mobile food vendor;

13. Bingo;

14. Firework sales;

15. Ambulances;

16. Sidewalk vending.

B. All requirements of this chapter are in addition to the requirements of chapters 5.06 through 5.24.

ITEM 9a & 9b

ATTACHMENT A
4923-0061-3531, v. 3
SECTION 2. Chapter 5.22, Cannabis Pilot Program, of Title 5, Business Licenses and Regulations, of the Ceres Municipal Code shall be repealed in its entirety and replaced with a new Chapter 5.22, Cannabis Business Regulations, which shall read as follows:

Chapter 5.22

CANNABIS BUSINESS REGULATIONS
Sections:

5.22.010 Declaration of purpose.

5.22.020 Definitions.

5.22.030 State requirements.

5.22.040 Required local approvals.

5.22.050 Cannabis business application.

5.22.060 Investigation and fingerprinting of applicant.

5.22.070 Development agreement.

5.22.080 Revocation of development agreement.

5.22.090 Cannabis business tax.

5.22.100 Operational requirements.

5.22.110 Limit on number of cannabis dispensaries.

5.22.120 Inspections.

5.22.130 Enforcement.

5.22.140 Public nuisance.

5.22.150 Cost recovery.

5.22.160 Nonconforming use.

5.22.170 Relationship to other laws.

5.22.180 Severability.

5.22.010 Declaration of Purpose.

A. The City finds and declares that the purpose of this chapter is to regulate all commercial cannabis activity in the City of Ceres, to the extent authorized by state law and in a manner designed to minimize negative impacts on the City, and to promote the health, safety, morals, and general welfare of residents and businesses within the City.

B. It is the purpose and intent of the City Council to implement state law by regulating cannabis businesses and to ensure that commercial cannabis activity does not result in the diversion of cannabis for illicit purposes.

C. Cannabis businesses shall comply with all provisions of the Ceres Municipal Code, state law, and all other applicable local and state regulations. It is neither the intent nor the effect of this chapter to condone or legitimize the illegal use, consumption, or cultivation of cannabis under federal, state, or local law.

D. The regulations in this chapter do not interfere with a qualified patient's right to obtain and use cannabis as authorized under state law, nor do they criminalize the ITEM 9a & 9b

ATTACHMENT A
4923-0061-3531, v. 3
possession or cultivation of cannabis by qualified patients or their primary caregivers.

5.22.020 Definitions.

Abatement costs shall include the actual and reasonable costs incurred by the City to abate a public nuisance. These costs include all direct and indirect costs to the City that result from the total abatement action, including, but not limited to, investigation costs, costs to enforce the Ceres Municipal Code and any applicable State, County or local law, clerical and administrative costs to process paperwork, costs incurred to provide notices and prepare for and conduct administrative appeal hearings, and costs to conduct actual abatement of the nuisance. Costs include personnel costs, administrative overhead, costs for equipment such as cameras and vehicles, staff time to hire a contractor, and reasonable attorneys’ fees incurred by City.

Applicant shall mean a person that files an application to operate a cannabis business pursuant to this code.

Business means a profession, trade, occupation, gainful activity, and all and every kind of calling whether or not carried on for profit.

Cannabis shall mean all parts of the plant Cannabis sativa Linnaeus, Cannabis indica, or Cannabis ruderalis, whether growing or not; the seeds thereof; the resin, whether crude or purified, extracted from any part of the plant; and every compound, manufacture, salt, derivative, mixture, or preparation of the plant, its seeds, or resin. “Cannabis” also means the separated resin, whether crude or purified, obtained from cannabis. “Cannabis” does not include the mature stalks of the plant, fiber produced from the stalks, oil or cake made from the seeds of the plant, any other compound, manufacture, salt, derivative, mixture, or preparation of the mature stalks (except the resin extracted therefrom), fiber, oil, or cake, or the sterilized seed of the plant which is incapable of germination. “Cannabis” does not mean “industrial hemp” as defined by Cal. Health & Safety Code § 11018.5.

Commercial cannabis activity includes the cultivation, manufacture, distribution, processing, storing, laboratory testing, packaging, labeling, transportation, delivery, or sale of cannabis or cannabis products that requires a state license, including medicinal cannabis or medicinal cannabis product as defined in section 26001 of the Business and Professions Code.

Cannabis business shall mean any person or business that engages in commercial cannabis activity.

Cannabis Business Tax shall mean the tax imposed on all commercial cannabis businesses pursuant to Ceres Municipal Code chapter 3.26.

Cannabis conditional use permit shall mean a conditional use permit issued to a cannabis business pursuant to Ceres Municipal Code chapter 18.44.

ITEM 9a & 9b

ATTACHMENT A
4923-0061-3531, v. 3
Cannabis delivery or cannabis deliveries shall mean the sale of cannabis and cannabis products by delivery to a customer pursuant to a Type 10 State cannabis license. “Cannabis delivery” does not mean the transfer or sale of cannabis or cannabis products between two cannabis businesses.

Cannabis dispensary shall mean a business at a particular location or real property involving the distribution of cannabis to qualified patients, primary caregivers, persons with identification cards, or customers pursuant to a Type 10 State cannabis license that is consistent with State law and this chapter.

Cannabis manufacturing business shall mean any cannabis business that, pursuant to a Type 6, Type 7, or Type 12 State cannabis license, manufactures cannabis or cannabis products.

Cannabis product shall mean cannabis that has undergone a process whereby the plant material has been transformed into a concentrate, including, but not limited to, concentrated cannabis, or an edible or topical product containing cannabis or concentrated cannabis and other ingredients.

City business license shall mean a business license issued by the City pursuant to Ceres Municipal Code Title 5.

City Manager shall mean the Ceres City Manager or their designee.

Cultivation shall mean any activity involving the planting, growing, harvesting, drying, curing, grading, or trimming of cannabis.

Customer shall mean natural person 21 years of age or older or a natural person 18 years of age or older who possesses a physician's recommendation, or a primary caregiver who purchases or otherwise lawfully obtains cannabis or cannabis products from a licensed cannabis business for personal use, whether for medicinal or adult-use purposes, and not for resale.

Medicinal and Adult-Use Cannabis Regulation and Safety Act or MAUCRSA has the same meaning as chapter 1 (commencing with section 26000) of division 10 of the California Business and Professions Code, and any applicable rules and regulations promulgated thereafter.

Permittee shall mean any person or entity who has been granted a cannabis conditional use permit by the City authorizing the operation of a cannabis business, and who is operating or intends to operate such business in accordance with the terms and conditions of that permit.

Person shall mean an individual, firm, partnership, joint venture, association, corporation, limited liability company, estate, trust, business trust, receiver, syndicate, or any other group or combination acting as a unit and includes the plural as well as the singular number.

ITEM 9a & 9b

ATTACHMENT A
4923-0061-3531, v. 3
Primary caregiver shall have the same meaning as set forth in California Health and Safety Code section 11362.7(d).

Responsible party shall mean a person or entity responsible for creating, causing, committing, or maintaining any violation of this code or State, County, or local law.

Subject property shall mean the real property that is the subject of any abatement or enforcement action by the City for which the City incurred costs and seeks recovery under this code.

Qualified patient shall have the same meaning as set forth in California Health and Safety Code section 11362.7(f).

5.22 030 State requirements.

A. Any cannabis business that does not have the applicable state license is prohibited within the City.

B. Every cannabis business operating within the City shall:

1. Obtain and maintain all required licenses, permits, and approvals issued by the State of California or any applicable state regulatory agency, including, without limitation, licenses under the Medicinal and Adult-Use Cannabis Regulation and Safety Act (MAUCRSA).

2. Operate in full compliance with all applicable state laws, regulations, and guidelines governing cannabis businesses, including but not limited to cultivation, manufacturing, distribution, testing, and retail sales.

3. Immediately notify the City of any suspension, revocation, or other enforcement action taken by a state agency against the business’s license(s).

4. Cease operations if any required state license is suspended or revoked until such time as the license is reinstated.

C. This chapter, and the provisions herein, shall be read consistent with any statewide regulation of cannabis that is promulgated by the legislature or by voter approval.

5.22.040 Required local approvals.

A. No person or entity shall establish, operate, or continue to operate any cannabis business within the City without first obtaining and thereafter maintain in good standing each of the following approvals:

1. A valid development agreement.

2. A valid cannabis conditional use permit.

3. A valid City business license.

B. Each cannabis business shall continuously maintain all required approvals listed in subsection (A). The expiration, suspension, or revocation of any one of these approvals shall constitute grounds for suspension or revocation of the others and shall immediately require the cessation of all cannabis operations until such approvals are reinstated or reissued.

ITEM 9a & 9b

ATTACHMENT A
4923-0061-3531, v. 3
C. The issuance of any approval under this Chapter does not create a vested right to continue operating a cannabis business and shall not limit the City’s authority to amend, suspend, or terminate such approvals as provided by law or the terms of the applicable approval.

5.22.050 Cannabis business application.

A. A person may apply to operate a cannabis business by filing a cannabis business application with the City Manager on a form provided by the City.

B. No cannabis business application shall be processed unless applicant pays the application fee in an amount to be established by resolution of the City Council.

C. No cannabis business application shall be processed unless applicant has entered into a funding agreement with the City to cover application processing costs and all other established costs payable to the City in connection with a cannabis business application.

D. No cannabis business application shall be processed unless applicant has executed an indemnification agreement approved by the City Attorney.

E. Any proposed transfer of ownership of a cannabis business shall be submitted through a cannabis business application, together with all required fees and documentation. The transferee shall meet all eligibility requirements for a cannabis business under this chapter.

5.22.060 Investigation and fingerprinting of applicant.

A. Prior to the acceptance of applications for a license, transfer of ownership, or other approval as provided in this chapter, the following individuals shall authorize the Chief of Police to perform criminal background investigation by providing verified fingerprint information to the Ceres Police Department:

1. If the applicant is a natural person, that person.

2. If the applicant is a partnership, all of the partners.

3. If the applicant is a corporation, both the officers and directors, together with any person with an ownership interest of ten percent (10%) or more.

B. No cannabis business shall be permitted to operate in the City if the background investigation indicates disqualifying criminal history.

5.22.070 Development agreement.

A. No cannabis business shall commence or continue operations in the City without obtaining and maintaining a valid development agreement in full force and effect.

B. An applicant shall be eligible to enter into a development agreement upon completion of background investigation of all applicable individuals.

C. Development agreements shall be issued pursuant to Ceres Municipal Code chapter 18.37.

D. A development agreement may be approved prior to an applicant having received all required state licenses and local permits; however, no cannabis business shall ITEM 9a & 9b

ATTACHMENT A
4923-0061-3531, v. 3
receive a certificate of occupancy nor operate in the City prior to possessing the required state and local licenses and approvals.

E. Development agreements may not be transferred, sold, assigned or bequeathed expressly or by operation of law. Any attempt to directly or indirectly transfer a development agreement shall be unlawful and void and shall automatically revoke the permit.

F. Development agreements shall be periodically reviewed pursuant to Ceres Municipal Code section 18.37.180.

5.22.080 Termination of development agreement.

A. Termination of development agreements shall follow procedures provided by Ceres Municipal Code chapter 18.37.

B. Upon termination a development agreement, an operator’s cannabis conditional use permit and City business license shall be subject to revocation.

5.22.090 Cannabis business tax.

A. All cannabis businesses within the City are subject to the Cannabis Business Tax established by Ceres Municipal Code chapter 3.26.

B. A cannabis business’ failure to pay the Cannabis Business Tax constitutes grounds for revocation of its development agreement, cannabis conditional use permit or City business license.

5.22.100 Operational requirements.

A. Cannabis business operations shall comply with all applicable state and local laws and regulations.

B. Cannabis business operations shall comply with the conditions of approval of their cannabis conditional use permit.

C. A cannabis business shall immediately cease operations upon revocation of its development agreement, cannabis conditional use permit, or City business license and operator shall comply with all closure and inventory disposal requirements under this code and state and local law and regulations.

5.22.110 Limit on number of cannabis dispensaries.

A. The total number of licensed cannabis dispensaries operating within the city shall not exceed two (2) at any given time.

B. If the maximum number of cannabis dispensaries is reached, no additional cannabis dispensaries shall be issued a development agreement or cannabis conditional use permit until an existing cannabis dispensary’s development agreement and cannabis conditional use permit is voluntarily surrendered, revoked, or otherwise terminated.

5.22.120 Inspections.

ITEM 9a & 9b

ATTACHMENT A
4923-0061-3531, v. 3
A. The City Manager and any authorized City official shall have the right to enter the premises of any cannabis business, during regular business hours or at any other reasonable time, to inspect the premises and business records to ensure compliance with this code, any conditions of approval, and state and local law and regulations.

5.22.130 Enforcement.

A. The Chief of Police or their designee shall be responsible for enforcement of this chapter.

B. Violation of any condition of approval of a cannabis conditional use permit shall constitute a violation of this chapter.

C. Violations of this chapter are subject to administrative remedies provided by Ceres Municipal Code chapter 19.10.

D. The amount of fine imposed for violation of this chapter shall not exceed:
a. Schedule 1. Five Hundred Dollars ($500) for a first violation. b. Schedule 2. Seven hundred and Fifty Dollars ($750) for a second violation of the same code section within one (1) year.
c. Schedule 3. One Thousand Dollars ($1,000) for each additional violation of the same code section within one (1) year.

E. Each violation of this chapter, or of any condition of approval of a cannabis conditional use permit, shall constitute a separate offense.

F. Any permittee whose cannabis conditional use permit, development agreement, or City business license is revoked shall immediately cease all cannabis-related operations within the City.

G. In addition to any other remedy, the City may seek injunctive relief and may recover costs of enforcement, including attorneys’ fees.

H. The remedies provided herein are cumulative and in addition to any other remedies available under law.

5.22.140 Public nuisance.

A. Any commercial cannabis use or activity caused or permitted to exist in the City in violation of any provision of this chapter shall be and is hereby declared a public nuisance and may be abated by the City pursuant to the procedures provided by Ceres Municipal Code chapter 19.07.

B. The remedies provided in this section are cumulative and do not limit the City’s authority to pursue all other remedies available under law.

5.22.150 Cost recovery.

A. The City shall be entitled to recover its abatement and enforcement costs incurred in obtaining compliance with this code. Costs incurred by the City are recoverable even if a public nuisance or violation of this code, the Ceres Municipal Code, or ITEM 9a & 9b

ATTACHMENT A
4923-0061-3531, v. 3
state law or regulation is corrected by the property owner or other responsible party.

B. The cost of abating a public nuisance or enforcing this code shall either be a special assessment and lien on the subject property or the personal obligation of the owner of the subject property or the responsible party. If there is more than one (1) responsible party, each party shall be jointly and severally liable for the costs.

5.22.160 Nonconforming use.

Any cannabis business established or operating in the City in violation of this chapter shall not be considered a lawful or permitted nonconforming use, and no such cannabis business shall be eligible for issuance of any permits or approvals under the Ceres Municipal Code. Further, any such unlawfully established cannabis business shall constitute a public nuisance subject to abatement by the City.

5.22.170 Relationship to other laws.

Except as otherwise specifically provided herein, this chapter incorporates the requirements and procedures set forth in chapter 1 (commencing with section 26000) of division 10 of the California Business and Professions Code, or its successors. In the event of any conflict between the provisions of this chapter and the provisions of that chapter or any other applicable state or local law, the more restrictive provision shall control.

5.22.180 Severability.

Should any provision of this chapter, or its application to any person or circumstance, be determined by a court of competent jurisdiction to be unlawful, unenforceable or otherwise void, that determination shall have no effect on any other provision of this chapter or the application of this chapter to any other person or circumstance and, to that end, the provisions hereof are severable.

SECTION 3. SEVERABILITY. If any section, subdivision, sentence, clause, phrase or portion of this ordinance is, for any reason, held invalid or unconstitutional by any court of competent jurisdiction, such portion shall be deemed a separate, distinct and independent provision, and such holding shall not affect the validity of the remaining portions thereof and shall continue to be in full force and effect.

SECTION 4. EFFECTIVE DATE AND PUBLICATION. This Ordinance shall become effective thirty (30) days from and after its final passage and adoption, provided it is published in a newspaper of general circulation at least within fifteen (15) days after its passage or a summary of the Ordinance is published in a newspaper of general circulation at least five (5) days prior to adoption and again at least within fifteen (15) days after its passage.

SECTION 5. CERTIFICATION OF COUNCIL ADOPTION AND APPROVAL. This Ordinance was introduced at a regular meeting of the City Council held on the 23rd day ITEM 9a & 9b

ATTACHMENT A
4923-0061-3531, v. 3
of March 2026, and passed and adopted as Ordinance No. 2026-XXXX at a regular meeting of City Council held on the 13th day of April 2026, by the following vote:

AYES: Councilmembers:

NOES: Councilmembers:

ABSENT: Councilmembers:

ABSTAIN: Councilmembers:

APPROVED:
________________________________
Javier Lopez, Mayor
ATTEST:
______________________________
Fallon Martin, City Clerk
APPROVED AS TO FORM:
______________________________
Nubia I. Goldstein, City Attorney
ITEM 9a & 9b
ITEM 9a & 9b

ATTACHMENT B
ORDINANCE NO. 2026-XXXX

A ZONING ORDINANCE TEXT AMENDMENT OF THE CERES CITY COUNCIL ADDING CHAPTER 44, CANNABIS CONDITIONAL USE PERMITS TO TITLE 18, ZONING, AND AMENDING SECTIONS 18.02.010, 18.13.020, 18.16.040, 18.17.040,

18.18.040, 18.19.040, AND 18.20.040, OF TITLE 18, ZONING, OF THE CERES

MUNICIPAL CODE
WHEREAS, the Medicinal and Adult-Use Cannabis Regulation and Safety Act (“MAUCRSA”), codified in Business and Professions Code section 26000 et seq., establishes the comprehensive state regulatory framework for commercial medicinal and adult-use cannabis activity, and expressly preserves the authority of local jurisdictions to regulate or prohibit such operations within their boundaries; and WHEREAS, on May 29, 2018, the Ceres City Council (“City Council”) adopted Ordinance No. 2018-1045, establishing a Cannabis Pilot Program (“Pilot Program”) regulating the operation of cannabis businesses within the City which is now codified in Chapter 5.22 of the Ceres Municipal Code; and
WHEREAS, since the establishment of the Pilot Program, the City has gained a better understanding of the cannabis industry, which has informed how the City intends to regulate cannabis businesses going forward; and
WHEREAS, the City Council finds that updating the Pilot Program to establish a permanent regulatory structure for cannabis businesses is necessary to protect the public health, safety, and welfare; and
WHEREAS, as part of these permanent regulations, the City Council has determined that all cannabis businesses operating within the City shall be required to obtain a cannabis conditional use permit; and
WHEREAS, the addition of Chapter 18.44, Cannabis Conditional Use Permits, implements the City Council’s determination and establishes procedures, operational standards, and enforcement authority for the City related to cannabis conditional use permits; and
WHEREAS, to ensure consistency within Title 18, Zoning, corresponding amendments have been made to designate cannabis businesses as conditional uses in the Community Commercial, Wholesale Commercial, Highway Commercial, Light Industrial, General Industrial, and Planned Community zones; and WHEREAS, on February 2, 2026, the Planning Commission of the City of Ceres held a duly noticed public hearing and adopted a resolution recommending that the City Council approve this zoning ordinance text amendment.

ITEM 9a & 9b

ATTACHMENT B
4932-8960-9881, v. 2

NOW, THEREFORE, THE COUNCIL OF THE CITY OF CERES DOES ORDAIN AS FOLLOWS:

SECTION 1. Chapter 44, Cannabis Conditional Use Permits, shall be added to of Title 18, Zoning, of the Ceres Municipal Code which shall read as follows:

Chapter 18.44 - CANNABIS CONDITIONAL USE PERMITS
Sections:

18.44.010 Definitions.

18.44.020 Cannabis conditional use permit required.

18.44.030 Cannabis conditional use permit application.

18.44.040 Cannabis conditional use permit procedure.

18.44.050 Revocation of cannabis conditional use permit.

18.44.060 Conditions of approval for cannabis conditional use permit.

18.44.070 General conditions.

18.44.080 Premises conditions.

18.44.090 Security conditions.

18.44.100 Signage conditions.

18.44.110 Cannabis waste conditions.

18.44.120 Odor control conditions.

18.44.130 Cultivation conditions.

18.44.140 Manufacturing conditions.

18.44.150 Cannabis delivery conditions.

18.44.160 Insurance conditions.

18.44.170 Severability.

18.44.010 Definitions.

Applicant: a person that files an application for a cannabis conditional use pursuant to this chapter.

Cannabis: all parts of the plant Cannabis sativa Linnaeus, Cannabis indica, or Cannabis ruderalis, whether growing or not; the seeds thereof; the resin, whether crude or purified, extracted from any part of the plant; and every compound, manufacture, salt, derivative, mixture, or preparation of the plant, its seeds, or resin. “Cannabis” also means the separated resin, whether crude or purified, obtained from cannabis. “Cannabis” does not include the mature stalks of the plant, fiber produced from the stalks, oil or cake made from the seeds of the plant, any other compound, manufacture, salt, derivative, mixture, or preparation of the mature stalks (except the resin extracted therefrom), fiber, oil, or cake, or the sterilized seed of the plant which is incapable of germination. “Cannabis” does not mean “industrial hemp” as defined by Cal. Health & Safety Code § 11018.5.

Cannabis business: any person or entity that engages in commercial cannabis activity.

ITEM 9a & 9b

ATTACHMENT B
4932-8960-9881, v. 2
Cannabis business tax: the tax imposed by the City on persons engaged in a cannabis business pursuant to Ceres Municipal Code chapter 3.26.

Cannabis conditional use permit: a conditional use permit issued to a cannabis business pursuant to this chapter.

Cannabis cultivation business: any business engaged in commercial cannabis activity involving the planting, growing, harvesting, drying, curing, grading, or trimming of cannabis.

Cannabis delivery: the sale of cannabis and cannabis products by delivery to a customer pursuant to a Type 10 State cannabis license. “Cannabis delivery” does not mean the transfer or sale of cannabis or cannabis products between two cannabis businesses.

Cannabis dispensary: a business at a particular location involving the distribution of cannabis to customers pursuant to a Type 10 State cannabis license that is consistent with State law and this chapter.

Cannabis manufacturing business: a business engaged in commercial cannabis activity involving compounding, blending, extracting, infusing, packaging, labeling, or otherwise making or preparing a cannabis product.

Cannabis product: cannabis that has undergone a process whereby the plant material has been transformed into a concentrate, including, but not limited to, concentrated cannabis, or an edible or topical product containing cannabis or concentrated cannabis and other ingredients.

Cannabis waste: waste that is cannabis or cannabis product that has been discarded, destroyed, or is no longer usable or saleable, including plant material, trimmings, extracts, infused products, packaging containing cannabis residue, or other materials contaminated with cannabis.

City Manager: the Ceres City manager or their designee.

City business License: a business license issued by the City pursuant to Ceres Municipal Code chapter 5.02.

Commercial cannabis activity: the cultivation, manufacture, distribution, processing, storing, laboratory testing, packaging, labeling, transportation, delivery, or sale of cannabis or cannabis products that requires a state license, including medicinal cannabis or medicinal cannabis product as defined in section 26001 of the Business and Professions Code.

Customer: natural person 21 years of age or older or a natural person 18 years of age or older who possesses a physician's recommendation, or a primary caregiver who purchases or otherwise lawfully obtains cannabis or cannabis products from a licensed cannabis business for personal use, whether for medicinal or adult-use purposes, and not for resale.

ITEM 9a & 9b

ATTACHMENT B
4932-8960-9881, v. 2
Permittee: any person, business, or entity that has been issued a cannabis conditional use permit by the City under this chapter, and includes the permit holder’s agents, employees, successors, and assigns acting within the scope of the permit.

Premises: the land, buildings, structures, and any other improvements or facilities occupied, used, or intended to be used by a permittee for the operation of a cannabis business.

Person: an individual, firm, partnership, joint venture, association, corporation, limited liability company, estate, trust, business trust, receiver, syndicate, or any other group or combination acting as a unit and includes the plural as well as the singular number.

Temporary structure shall mean a structure that is erected or placed on a lot for a limited and specified period, not intended for permanent occupancy, and removed upon expiration of the approved time period.

18.44.020 Cannabis conditional use permit required.

A. No cannabis business shall operate in the City unless it has first obtained and continues to maintain compliance with all of the following:

1. All applicable state licenses and permits.

2. A cannabis conditional use permit.

3. A validly executed development agreement.

4. A City business license.

B. Any cannabis business that fails to satisfy any of the requirements in subsection (A) shall immediately cease operations and shall not resume operations until that cannabis business is in full compliance with all applicable requirements.

18.44.030 Cannabis conditional use permit application.

A. An applicant shall file the following information with the City at the time of application for a cannabis conditional use permit:

1. A completed cannabis business application.

2. Completed background checks of all applicable individuals pursuant to Ceres Municipal Code section 5.22.060.

3. Any additional information required by the City Manager.

B. No cannabis conditional use permit application shall be processed unless the applicant pays the application fee in an amount to be established by resolution of the City Council.

18.44.040 Cannabis conditional use permit procedure.

A. A cannabis conditional use permit shall be processed in accordance with the procedures set forth in Ceres Municipal Code chapter 18.30.

B. A permittee seeking to amend the conditions of approval of its cannabis conditional use permit shall submit a written request to the City Manager and pay applicable processing fees. Amendments that do not substantially change the type or scope ITEM 9a & 9b

ATTACHMENT B
4932-8960-9881, v. 2
of use may be approved by the City Manager. All other amendments shall require a public hearing and Planning Commission approval.

18.44.050 Revocation of cannabis conditional use permit.

A. A cannabis conditional use permit may be revoked based on certain findings, including but not limited to if any of the following:

1. That the permittee has violated any condition of approval of its cannabis conditional use permit.

2. That the permittee has violated any term or condition of its development agreement.

3. That the permittee’s development agreement has been revoked, terminated, or otherwise rendered invalid.

4. That the permittee’s City business license has been revoked, suspended, or otherwise rendered invalid.

5. That the permittee has failed to pay any applicable cannabis business tax.

6. That the permittee’s applicable state license has been revoked, suspended, or otherwise rendered invalid.

7. That the permittee has violated any provision of the Ceres Municipal Code.

8. That the permittee has violated any applicable state or local law or regulation.

9. That the use is being exercised in such a way as to be detrimental to the public health, safety, or welfare, or in such a manner as to constitute a nuisance.

10.That the use for which approval was granted has ceased to exist or has been suspended for a period in excess of six months.

B. Revocation of a cannabis conditional use permit shall be processed in accordance with the procedures set forth in Ceres Municipal Code chapter 18.30.

C. Upon revocation of a cannabis conditional use permit, all cannabis operations on the premises shall immediately cease, and the permittee shall comply with all closure and inventory disposal requirements under this code and state law and regulations.

18.44.060 Conditions of approval for cannabis conditional use permit.

Upon approval of a cannabis conditional use permit, the Planning Commission may impose conditions in excess of the requirements set forth in this chapter.

18.44.070 General conditions.

A. Permittee shall not operate without a valid cannabis conditional use permit, nor shall a permittee operate if its cannabis conditional use permit has been revoked, suspended, or otherwise rendered invalid.

B. Permittee shall not operate in violation of the conditions of its cannabis conditional use permit.

ITEM 9a & 9b

ATTACHMENT B
4932-8960-9881, v. 2
C. Permittee shall obtain and maintain a valid development agreement. Any breach or default of permittee’s development agreement or revocation of the development agreement shall be grounds for revocation of a cannabis conditional use permit.

D. Permittee shall obtain and maintain a valid City business license.

E. Permittee shall comply with all state and local laws and regulations.

F. Permittee shall timely pay the applicable taxes pursuant to state and local laws.

G. Permittee shall not make any operational changes to its cannabis business operations without an approved amendment to its conditional use permit.

H. A cannabis conditional use permit may be issued prior to an applicant having received all required state licenses; however, no cannabis business shall receive a certificate of occupancy nor operate in the City prior to possessing the required state and local licenses and permits.

18.44.080 Premises conditions.

A. The premises must be fully compliant with all applicable federal, state, and local laws and regulations.

B. Permittee’s operations shall be conducted within fully enclosed buildings.

Operations, including storage and cultivation of cannabis, shall not be visible from the exterior of any building.

C. The premises shall not be located within a 1000-foot radius of any park, day care center, youth center or public or private school providing instruction to prekindergarten, kindergarten, or grades 1-12. The distance specified in this subsection shall be the horizontal distance measured in a straight line without regard to intervening structures, from the property line of the lot on which the cannabis business is located to the nearest property line of those uses described in this subsection.

D. Permittee shall not establish, operate, or maintain any cannabis business within a temporary structure on the premises.

E. No person shall sell, dispense, or consume alcoholic beverages or tobacco products on the premises.

F. No person shall consume cannabis or cannabis products on the premises.

G. Permittee shall take all necessary and reasonable steps to discourage and prevent unlawful or disorderly conduct, including loitering, from occurring on the premises and in the immediate area surrounding the premises during business hours and after closing.

H. The premises shall comply with a site plan approved or conditionally approved as part of its cannabis conditional use permit. Permittee’s noncompliance with its approved or conditionally approved site plan constitutes a violation of its cannabis conditional use permit.

ITEM 9a & 9b

ATTACHMENT B
4932-8960-9881, v. 2

18.44.090 Security conditions.

A. All entrances and exits to buildings on the premises shall be secured with commercial locks or similar measures to prevent unauthorized entry.

B. Permittee’s shall have a digital video surveillance system monitoring all entrances, exits, cannabis cultivation and processing rooms, cannabis point of sale rooms, limited access rooms and security rooms on the premises.

1. Surveillance cameras shall record continuously, 24 hours a day.

2. Surveillance cameras must provide sufficient resolution and color fidelity to identify individuals on the premises.

3. Surveillance recordings shall be maintained for a minimum of ninety (90) days, stored in such a way that protects the recordings from tampering or theft, and be made available to the City upon request.

C. Permittees shall ensure a licensed alarm company operator installs, maintains, monitors, and responds to the alarm system.

1. Upon request, permittee shall make available to the City all information related to the alarm system, monitoring, and alarm activity.

D. Permittee must store all cannabis, cannabis products, and cannabis waste in locked and secure areas.

E. The City may impose additional site-specific security conditions on permittee as necessary to protect public health and safety or to address unique risks associated with the location or type of cannabis operation.

F. Permittee shall comply with the security plan approved or conditionally approved as part of its Cannabis Conditional Use Permit. Permittee’s noncompliance with its approved or conditionally approved security plan constitutes a violation of its cannabis conditional use permit.

G. The City Manager, Chief of Police or other designated City official may require updates or revisions to a Permittee’s Security Plan at any time based on operational changes, observed risks, or complaints.

18.44.100 Signage conditions.

A. Permittee’s signage shall comply with the sign standards set forth by state law and regulation and by this Code.

B. Offsite and temporary signs are prohibited.

C. Permittee’s signs shall be approved by the Director of Community Development prior to installation. Changes or modifications to signage require prior written approval from the Director of Community Development.

18.44.110 Cannabis waste conditions.

A. Permittee shall secure all cannabis waste in locked designated areas within the premises until properly disposed of in compliance with state law.

ITEM 9a & 9b

ATTACHMENT B
4932-8960-9881, v. 2
B. Permittee shall maintain records of all cannabis waste disposal activities, including quantities, dates, and responsible parties. Records shall be made available to the City upon request.

C. Permittee shall comply with the cannabis waste plan approved or conditionally approved as part of its cannabis conditional use permit. Permittee’s noncompliance with its approved or conditionally approved cannabis waste plan constitutes a violation of its cannabis conditional use permit.

18.44.120 Odor control conditions.

A. Permittee shall install and maintain an odor control system designed to prevent cannabis odors from escaping the interior of the facility. Cannabis odors shall not be detectable at the exterior of the premises or within adjacent properties.

B. Odors from Permittee’s premises may not unreasonably impact adjacent properties or public areas, consistent with state law and regulation and local nuisance standards.

C. Permittee shall comply with the odor control plan approved or conditionally approved as part of its cannabis conditional use permit. Permittee’s noncompliance with its approved or conditionally approved odor control plan constitutes a violation of its cannabis conditional use permit.

18.44.130 Cultivation conditions.

A. This section is only applicable to permittees granted a cannabis conditional use permit for a cannabis cultivation business.

B. Outdoor commercial cannabis cultivation is prohibited.

C. Permittee shall only perform cultivation methods authorized by its cannabis conditional use permit. Any additional cultivation methods may only be conducted with an amendment to a cannabis conditional use permit.

D. Permittee shall obtain and maintain a valid Industrial Waste Discharge Permit issued by the City pursuant to chapter 13.19 of this Code. Permittee shall comply with all requirements of its Industrial Sewage Permit.

E. If applicable, Permittee shall register with the Stanislaus County Department of Hazardous Materials Division. Permittee shall comply with all requirements imposed by the Stanislaus County Department of Hazardous Materials Division.

F. Permittee shall comply with all fire, building, and electrical codes, including specific requirements for flammable solvents, pressurized gases, and chemical storage.

G. Permittee must obtain and maintain fire safety approval from the City Fire Chief.

H. Operations shall not create a public or private nuisance, including, but not limited to, noise, odor, lighting, or pest management impacts on neighboring properties.

I. Permittee shall comply with the cannabis cultivation plan approved or conditionally approved as part of its cannabis conditional use permit. Permittee’s noncompliance with its approved or conditionally approved cannabis cultivation plan constitutes a violation of its cannabis conditional use permit.

ITEM 9a & 9b

ATTACHMENT B
4932-8960-9881, v. 2

18.44.140 Manufacturing conditions.

A. This section is only applicable to permittees granted a cannabis conditional use permit for a cannabis manufacturing business.

B. Permittee shall only perform manufacturing methods authorized by its cannabis conditional use permit. Any additional manufacturing methods may only be conducted with an amendment to a cannabis conditional use permit.

C. Permittee shall obtain and maintain a valid Industrial Waste Discharge Permit issued by the City pursuant to Chapter 13.19 of this Code. Permittee shall comply with all requirements of its Industrial Sewage Permit.

D. If applicable, Permittee shall register with the Stanislaus County Department of Hazardous Materials Division. Permittee shall comply with all requirements imposed by the Stanislaus County Department of Hazardous Materials Division.

E. Permittee shall comply with all fire, building, and electrical codes, including specific requirements for flammable solvents, pressurized gases, and chemical storage.

F. Permittee must obtain and maintain fire safety approval from the City Fire Chief.

G. Permittee shall obtain and maintain any required clearance from the County Department of Health prior to commencing operations.

H. Permittee shall comply with the cannabis manufacturing plan approved or conditionally approved as part of its cannabis conditional use permit. Permittee’s noncompliance with its approved or conditionally approved cannabis manufacturing plan constitutes a violation of its cannabis conditional use permit.

18.44.150 Cannabis delivery.

A. Cannabis delivery is permitted only as an accessory use to a permitted cannabis dispensary, subject to approval of a cannabis conditional use permit issued pursuant to this chapter.

B. All cannabis delivery shall originate and be dispatched from the premises identified and approved under a cannabis conditional use permit.

C. Prior to providing cannabis or cannabis products to a delivery customer, the Permittee shall confirm the identity and age of the delivery customer as required under State law and shall secure a written or electronic signature of the delivery customer before completing the sale.

18.44.160 Insurance conditions.

Permittee shall maintain insurance in the amounts and of the types that are acceptable to the City Manager. The City shall be named as additional insured on all City-required insurance policies.

18.44.170 Severability.

Should any provision of this chapter, or its application to any person or circumstance, be determined by a court of competent jurisdiction to be unlawful, unenforceable or otherwise void, that determination shall have no effect on any other provision of this chapter or the ITEM 9a & 9b

ATTACHMENT B
4932-8960-9881, v. 2
application of this chapter to any other person or circumstance and, to that end, the provisions hereof are severable.

SECTION 2. Section 18.02.010, Definitions and interpretive provisions, of Chapter 2, Definitions, of Title 18, Zoning, of the Ceres Municipal Code shall be amended to add the definition of “Cannabis business” as follows:

18.02.010 - Definitions and interpretive provisions.

For the purpose of carrying out the provisions and intent of this title, words, phrases, and terms shall be deemed to have the meanings ascribed to them and shall be interpreted to have the standards and include the parts, elements and the features set forth in this chapter. When not inconsistent with the context, words used in the present tense include the future; words in the singular number include the plural; words in the plural number include the singular. The word "shall" is mandatory, and the word "may" is permissive. …
Cannabis business: any person or entity that engages in the cultivation, manufacture, distribution, processing, storing, laboratory testing, packaging, labeling, transportation, delivery, or sale of cannabis or cannabis products that requires a state license, including medicinal cannabis or medicinal cannabis product as defined in section 26001 of the Business and Professions Code.

SECTION 3. Section 18.13.020, General Provision, of Chapter 13 - P-C, Planned Community Zone, of Title 18, Zoning, of the Ceres Municipal Code shall be amended to add subdivision (L) as follows:

The following general provisions shall apply to all P-C zones:
…
L. Cannabis businesses shall be permitted in any P-C zone subject to a cannabis conditional use permit as provided for in chapter 18.44 of this title.

SECTION 4. Section 18.16.040, Conditional uses, of Chapter 16 - C-2, Community Commercial Zone, of Title 18, Zoning, of the Ceres Municipal Code shall be amended to revise the introductory paragraph and add subdivision (M) as follows:

18.16.040 – Conditional Uses
The following uses may be permitted in the C-2 zone subject to a conditional use permit as provided for in chapter 18.30 or 18.44 of this title. …
M. Cannabis businesses
SECTION 5. Section 18.17.040, Conditional uses, of Chapter 17 - C-3, Wholesale Commercial Zone, of Title 18, Zoning, of the Ceres Municipal Code shall be amended to revise the introductory paragraph and add subdivision (L) as follows:

ITEM 9a & 9b

ATTACHMENT B
4932-8960-9881, v. 2

18.17.040 – Conditional Uses
The following uses may be permitted in the C-3 zone subject to a conditional use permit as provided for in chapter 18.30 or 18.44 of this title. …
L. Cannabis businesses
SECTION 6. Section 18.18.040, Conditional uses, of Chapter 18 - H-1, Highway Commercial Zone, of Title 18, Zoning, of the Ceres Municipal Code shall be amended to revise the introductory paragraph and add subdivision (E) as follows:

18.18.040 – Conditional Uses
The following uses may be permitted in the H-3 zone subject to a conditional use permit as provided for in chapter 18.30 or 18.44 of this title. …
E. Cannabis businesses
SECTION 7. Section 18.19.040, Conditional uses, of Chapter 19 - M-1, Light Industrial Zone, of Title 18, Zoning, of the Ceres Municipal Code shall be amended to revise the introductory paragraph and add subdivision (L) as follows:

18.19.040 – Conditional Uses
The following uses may be permitted in the M-1 zone subject to a conditional use permit as provided for in chapter 18.30 or 18.44 of this title. …
L. Cannabis businesses
SECTION 8. Section 18.20.040, Conditional uses, of Chapter 20 - M-2, General Industrial Zone, of Title 18, Zoning, of the Ceres Municipal Code shall be amended to revise the introductory paragraph and add subdivision (T) as follows:

18.20.040 – Conditional Uses
The following uses may be permitted in the M-2 zone subject to a conditional use permit as provided for in chapter 18.30 or 18.44 of this title. …
T. Cannabis businesses
SECTION 9. Severability. If any section, subdivision, sentence, clause, phrase or portion of this ordinance is, for any reason, held invalid or unconstitutional by any court of competent jurisdiction, such portion shall be deemed a separate, distinct and independent provision, and such holding shall not affect the validity of the remaining portions thereof and shall continue to be in full force and effect.

ITEM 9a & 9b

ATTACHMENT B
4932-8960-9881, v. 2
SECTION 10. Effective Date and Publication. This Ordinance shall become effective thirty (30) days from and after its final passage and adoption, provided it is published in a newspaper of general circulation at least within fifteen (15) days after its passage or a summary of the Ordinance is published in a newspaper of general circulation at least five (5) days prior to adoption and again at least within fifteen (15) days after its passage.

This Ordinance was introduced at a regular meeting of the City Council held on the 23rd day of March 2026, and passed and adopted as Ordinance No. 2026-XXXX at a regular meeting of City Council held on the 13th of April 2026, by the following vote:

AYES: Councilmembers:

NOES: Councilmembers:

ABSENT: Councilmembers:

ABSTAIN: Councilmembers:

APPROVED:
________________________________
Javier Lopez, Mayor
ATTEST:
______________________________
Fallon Martin, City Clerk
APPROVED AS TO FORM:
______________________________
Nubia I. Goldstein, City Attorney
ITEM 9a & 9b

ATTACHMENT C
Section 5.03.010, General, of Chapter 3, General Permit Procedure, of Title 5, Business Licenses and Regulations, of the Ceres Municipal Code shall be amended to remove subsection 16, Commercial cannabis businesses, and move 17, Sidewalk vending, to 16 of Paragraph (A) as follows:

5.03.010 – General.

A. Certain activities in the City require permits issued by the City Manager or designee.

The following activities require a permit issued by the City:

1. Patrol services;

2. Motion picture and television production;

3. Alcoholic beverages;

4. Junk dealers and scrap metal recyclers;

5. Special events and temporary street closures;

6. Public dances, dancing places, and concerts;

7. Fortunetelling;

8. Taxicabs;

9. Adult entertainment businesses;

10.Garage sales;

11. Massage establishments;

12.Mobile food vendor;

13.Bingo;

14.Firework sales;

15.Ambulances;

16.Commercial cannabis businesses.
1716. Sidewalk vending
B. All requirements of this chapter are in addition to the requirements of chapters 5.06 through 5.24.

Chapter 5.22, Cannabis Pilot Program, of Title 5, Business Licenses and Regulations, of the Ceres Municipal Code shall be repealed in its entirety and replaced with a new Chapter 5.22, Cannabis Business Regulations, which shall read as follows:

5.22.010 - Declaration of purpose.

A. The City finds and declares that the purpose of this chapter is to regulate all commercial cannabis activity in the City of Ceres, to the extent authorized by state law and in a manner designed to minimize negative impacts on the City, and to promote the health, safety, morals, and general welfare of residents and businesses within the City.

ITEM 9a & 9b

ATTACHMENT C
4906-8613-4427, v. 3
B. It is the purpose and intent of the City Council to implement state law by regulating cannabis businesses and to ensure that commercial cannabis activity does not result in the diversion of cannabis for illicit purposes.

C. The regulations in this chapter do not interfere with a qualified patient's right to obtain and use cannabis as authorized under state law, nor do they criminalize the possession or cultivation of cannabis by qualified patients or their primary caregivers. Cannabis businesses shall comply with all provisions of the Ceres Municipal Code, state law, and all other applicable local and state regulations. It is neither the intent nor the effect of this chapter to condone or legitimize the illegal use, consumption, or cultivation of cannabis under federal, state, or local law.

5.22.020 - Definitions.

Adult Use of Marijuana Act or AUMA has the same meaning as Proposition 64, the Control, Regulate, and Tax Adult Use of Marijuana Act approved by California voters at the November 8, 2016, election, and any applicable rules and regulations promulgated thereafter.

Business means a profession, trade, occupation, gainful activity, and all and every kind of calling whether or not carried on for profit.

City Manager shall mean the Ceres City Manager or designee.

Commercial cannabis activity includes the cultivation, manufacture, distribution, processing, storing, laboratory testing, packaging, labeling, transportation, delivery, or sale of cannabis or cannabis products that requires a state license, including medicinal cannabis or medicinal cannabis product as defined in section 26001 of the Business and Professions Code.

Cannabis business shall mean any person or business that engages in commercial cannabis activity.

Cannabis business permit shall mean any permit issued to a cannabis business pursuant to the provisions of this chapter.

Cannabis Business Pilot Program shall mean the City's permitting process and procedures pursuant to the provisions of this chapter for the purpose of determining and evaluating the feasibility and desirability of regulating multiple cannabis businesses within City limits.

Cultivation means any activity involving the planting, growing, harvesting, drying, curing, grading, or trimming of cannabis.

Medicinal and Adult-Use Cannabis Regulation and Safety Act or MAUCRSA has the same meaning as chapter 1 (commencing with section 26000) of division 10 of the California Business and Professions Code, and any applicable rules and regulations promulgated thereafter.

Primary caregiver shall have the same meaning as set forth in California Health and Safety Code section 11362.7(d).

ITEM 9a & 9b

ATTACHMENT C
4906-8613-4427, v. 3
Qualified patient shall have the same meaning as set forth in California Health and Safety Code section 11362.7(f).

5.22.030 - Cannabis business pilot program.

A. Cannabis businesses shall only be permitted to operate in the City following application, investigation, verification, approval, and issuance of a development agreement approved by the City Council, and a cannabis business permit issued by the City in accordance with the criteria and procedures set forth in this chapter.

No land use entitlement, permit (including building permit) approval, site plan, certificate of occupancy, zoning clearance, or other land use authorization for a cannabis business shall be granted or permitted unless it complies with the provisions of the Ceres Municipal Code.

B. All persons who are engaged in or who are attempting to engage in commercial cannabis activity in any form shall do so only in strict compliance with the terms, conditions, limitations and restrictions of this chapter, AUMA, and MAUCRSA, as it applies, the provisions of the Ceres Municipal Code, as may be amended from time to time, and all other applicable state and local laws and regulations.

C. The City Manager is authorized to make policies and procedures consistent with the intent of this chapter concerning the applications, the application process, the information required of an applicant, the application procedures, and the administration and procedures to be used and followed in the application and hearing process.

5.22.040 - All state and local licenses and permits required.

A. No cannabis business shall operate unless it is in possession of all applicable state and local licenses and permits.

B. Every cannabis business shall submit to the City Manager a copy of any and all of its state and local licenses and permits required for its operation.

C. If any other applicable state or local license or permit required for a cannabis business' operation is denied, suspended, modified, revoked, or expired, the cannabis business shall notify the City Manager in writing within ten days of such denial, suspension, modification, revocation, or expiration.

5.22.050 - Permits not transferable.

Cannabis business permits issued pursuant to this chapter are not property and have no value. Cannabis business permits may not be transferred, sold, assigned or bequeathed expressly or by operation of law. Any attempt to directly or indirectly transfer a cannabis business permit shall be unlawful and void, and shall automatically revoke the permit. • 5.22.060 - Development agreement.

A. Prior to operating in the City, and as a condition of issuance of any applicable permits, including, but not limited to, a cannabis business permit, the applicant seeking to operate a cannabis business shall enter into a development agreement ITEM 9a & 9b

ATTACHMENT C
4906-8613-4427, v. 3
with the City setting forth the terms and conditions under which the cannabis business will operate. Such development agreement shall be in addition to the requirements of this chapter, including, but not limited to, public outreach and education, community service, payment of fees and other charges as mutually agreed upon, approval of architectural plans (including site plan, floor plan, and elevation), and such other terms and conditions that will protect and promote the public health, safety, and welfare of all persons in the City.

B. Every development agreement approved by the City pursuant to this chapter shall be subject to an annual review by the City Council to determine compliance with the terms of the development agreement, applicable local and state laws and regulations, this chapter, and the Ceres Municipal Code. The City Council may from time to time determine whether to allow additional cannabis businesses as part of the Cannabis Business Pilot Program.

5.22.070 - Nonconforming use.

Any cannabis business established or operating in the City in violation of this chapter shall not be considered a lawful or permitted nonconforming use, and no such cannabis business shall be eligible for issuance of any permits or approvals under the Ceres Municipal Code. Further, any such unlawfully established cannabis business shall constitute a public nuisance subject to abatement by the City.

5.22.080 - Outdoor cultivation of cannabis prohibited.

A. A cannabis business shall only be allowed to cultivate cannabis within a fully enclosed building.

B. A cannabis business shall not cultivate cannabis outdoors.

C. The outdoor cultivation of cannabis, as defined in California Business and Professions Code section 26001, is strictly prohibited on all agricultural, residential, commercial, and industrial zoned properties.

5.22.090 - Relationship to other laws.

Except as otherwise specifically provided herein, this chapter incorporates the requirements and procedures set forth in chapter 1 (commencing with section 26000) of division 10 of the California Business and Professions Code, or its successors. In the event of any conflict between the provisions of this chapter and the provisions of that chapter or any other applicable state or local law, the more restrictive provision shall control.

5.22.100 - Statewide regulation.

This chapter, and the provisions herein, shall be read consistent with any statewide regulation of cannabis that is promulgated by the legislature or by voter approval.

5.22.110 - Severability.

Should any provision of this chapter, or its application to any person or circumstance, be determined by a court of competent jurisdiction to be unlawful, unenforceable or otherwise ITEM 9a & 9b

ATTACHMENT C
4906-8613-4427, v. 3
void, that determination shall have no effect on any other provision of this chapter or the application of this chapter to any other person or circumstance and, to that end, the provisions hereof are severable.

Chapter 5.22

CANNABIS BUSINESS REGULATIONS
Sections:

5.22.010 Declaration of purpose.

5.22.020 Definitions.

5.22.030 State requirements.

5.22.040 Required local approvals.

5.22.050 Cannabis business application.

5.22.060 Investigation and fingerprinting of applicant.

5.22.070 Development agreement.

5.22.080 Revocation of development agreement.

5.22.090 Cannabis business tax.

5.22.100 Operational requirements.

5.22.110 Limit on number of cannabis dispensaries.

5.22.120 Inspections.

5.22.130 Enforcement.

5.22.140 Public nuisance.

5.22.150 Cost recovery.

5.22.160 Nonconforming use.

5.22.170 Relationship to other laws.

5.22.180 Severability.

5.22.010 Declaration of Purpose.

A. The City finds and declares that the purpose of this chapter is to regulate all commercial cannabis activity in the City of Ceres, to the extent authorized by state law and in a manner designed to minimize negative impacts on the City, and to promote the health, safety, morals, and general welfare of residents and businesses within the City.

B. It is the purpose and intent of the City Council to implement state law by regulating cannabis businesses and to ensure that commercial cannabis activity does not result in the diversion of cannabis for illicit purposes.

C. Cannabis businesses shall comply with all provisions of the Ceres Municipal Code, state law, and all other applicable local and state regulations. It is neither the intent nor the effect of this chapter to condone or legitimize the illegal use, consumption, or cultivation of cannabis under federal, state, or local law.

D. The regulations in this chapter do not interfere with a qualified patient's right to obtain and use cannabis as authorized under state law, nor do they criminalize the ITEM 9a & 9b

ATTACHMENT C
4906-8613-4427, v. 3
possession or cultivation of cannabis by qualified patients or their primary caregivers.

5.22.020 Definitions.

Abatement costs shall include the actual and reasonable costs incurred by the City to abate a public nuisance. These costs include all direct and indirect costs to the City that result from the total abatement action, including, but not limited to, investigation costs, costs to enforce the Ceres Municipal Code and any applicable State, County or local law, clerical and administrative costs to process paperwork, costs incurred to provide notices and prepare for and conduct administrative appeal hearings, and costs to conduct actual abatement of the nuisance. Costs include personnel costs, administrative overhead, costs for equipment such as cameras and vehicles, staff time to hire a contractor, and reasonable attorneys’ fees incurred by City.

Applicant shall mean a person that files an application to operate a cannabis business pursuant to this code.

Business means a profession, trade, occupation, gainful activity, and all and every kind of calling whether or not carried on for profit.

Cannabis shall mean all parts of the plant Cannabis sativa Linnaeus, Cannabis indica, or Cannabis ruderalis, whether growing or not; the seeds thereof; the resin, whether crude or purified, extracted from any part of the plant; and every compound, manufacture, salt, derivative, mixture, or preparation of the plant, its seeds, or resin. “Cannabis” also means the separated resin, whether crude or purified, obtained from cannabis. “Cannabis” does not include the mature stalks of the plant, fiber produced from the stalks, oil or cake made from the seeds of the plant, any other compound, manufacture, salt, derivative, mixture, or preparation of the mature stalks (except the resin extracted therefrom), fiber, oil, or cake, or the sterilized seed of the plant which is incapable of germination. “Cannabis” does not mean “industrial hemp” as defined by Cal. Health & Safety Code § 11018.5.

Commercial cannabis activity includes the cultivation, manufacture, distribution, processing, storing, laboratory testing, packaging, labeling, transportation, delivery, or sale of cannabis or cannabis products that requires a state license, including medicinal cannabis or medicinal cannabis product as defined in section 26001 of the Business and Professions Code.

Cannabis business shall mean any person or business that engages in commercial cannabis activity.

Cannabis Business Tax shall mean the tax imposed on all commercial cannabis businesses pursuant to Ceres Municipal Code chapter 3.26.

Cannabis conditional use permit shall mean a conditional use permit issued to a cannabis business pursuant to Ceres Municipal Code chapter 18.44.

ITEM 9a & 9b

ATTACHMENT C
4906-8613-4427, v. 3
Cannabis delivery or cannabis deliveries shall mean the sale of cannabis and cannabis products by delivery to a customer pursuant to a Type 10 State cannabis license. “Cannabis delivery” does not mean the transfer or sale of cannabis or cannabis products between two cannabis businesses.

Cannabis dispensary shall mean a business at a particular location or real property involving the distribution of cannabis to qualified patients, primary caregivers, persons with identification cards, or customers pursuant to a Type 10 State cannabis license that is consistent with State law and this chapter.

Cannabis manufacturing business shall mean any cannabis business that, pursuant to a Type 6, Type 7, or Type 12 State cannabis license, manufactures cannabis or cannabis products.

Cannabis product shall mean cannabis that has undergone a process whereby the plant material has been transformed into a concentrate, including, but not limited to, concentrated cannabis, or an edible or topical product containing cannabis or concentrated cannabis and other ingredients.

City business license shall mean a business license issued by the City pursuant to Ceres Municipal Code Title 5.

City Manager shall mean the Ceres City Manager or their designee.

Cultivation shall mean any activity involving the planting, growing, harvesting, drying, curing, grading, or trimming of cannabis.

Customer shall mean natural person 21 years of age or older or a natural person 18 years of age or older who possesses a physician's recommendation, or a primary caregiver who purchases or otherwise lawfully obtains cannabis or cannabis products from a licensed cannabis business for personal use, whether for medicinal or adult-use purposes, and not for resale.

Medicinal and Adult-Use Cannabis Regulation and Safety Act or MAUCRSA has the same meaning as chapter 1 (commencing with section 26000) of division 10 of the California Business and Professions Code, and any applicable rules and regulations promulgated thereafter.

Permittee shall mean any person or entity who has been granted a cannabis conditional use permit by the City authorizing the operation of a cannabis business, and who is operating or intends to operate such business in accordance with the terms and conditions of that permit.

Person shall mean an individual, firm, partnership, joint venture, association, corporation, limited liability company, estate, trust, business trust, receiver, syndicate, or any other group or combination acting as a unit and includes the plural as well as the singular number.

ITEM 9a & 9b

ATTACHMENT C
4906-8613-4427, v. 3
Primary caregiver shall have the same meaning as set forth in California Health and Safety Code section 11362.7(d).

Responsible party shall mean a person or entity responsible for creating, causing, committing, or maintaining any violation of this code or State, County, or local law.

Subject property shall mean the real property that is the subject of any abatement or enforcement action by the City for which the City incurred costs and seeks recovery under this code.

Qualified patient shall have the same meaning as set forth in California Health and Safety Code section 11362.7(f).

5.22 030 State requirements.

A. Any cannabis business that does not have the applicable state license is prohibited within the City.

B. Every cannabis business operating within the City shall:

1. Obtain and maintain all required licenses, permits, and approvals issued by the State of California or any applicable state regulatory agency, including, without limitation, licenses under the Medicinal and Adult-Use Cannabis Regulation and Safety Act (MAUCRSA).

2. Operate in full compliance with all applicable state laws, regulations, and guidelines governing cannabis businesses, including but not limited to cultivation, manufacturing, distribution, testing, and retail sales.

3. Immediately notify the City of any suspension, revocation, or other enforcement action taken by a state agency against the business’s license(s).

4. Cease operations if any required state license is suspended or revoked until such time as the license is reinstated.

C. This chapter, and the provisions herein, shall be read consistent with any statewide regulation of cannabis that is promulgated by the legislature or by voter approval.

5.22.040 Required local approvals.

A. No person or entity shall establish, operate, or continue to operate any cannabis business within the City without first obtaining and thereafter maintain in good standing each of the following approvals:

1. A valid development agreement.

2. A valid cannabis conditional use permit.

3. A valid City business license.

B. Each cannabis business shall continuously maintain all required approvals listed in subsection (A). The expiration, suspension, or revocation of any one of these approvals shall constitute grounds for suspension or revocation of the others and shall immediately require the cessation of all cannabis operations until such approvals are reinstated or reissued.

ITEM 9a & 9b

ATTACHMENT C
4906-8613-4427, v. 3
C. The issuance of any approval under this Chapter does not create a vested right to continue operating a cannabis business and shall not limit the City’s authority to amend, suspend, or terminate such approvals as provided by law or the terms of the applicable approval.

5.22.050 Cannabis business application.

A. A person may apply to operate a cannabis business by filing a cannabis business application with the City Manager on a form provided by the City.

B. No cannabis business application shall be processed unless applicant pays the application fee in an amount to be established by resolution of the City Council.

C. No cannabis business application shall be processed unless applicant has entered into a funding agreement with the City to cover application processing costs and all other established costs payable to the City in connection with a cannabis business application.

D. No cannabis business application shall be processed unless applicant has executed an indemnification agreement approved by the City Attorney.

E. Any proposed transfer of ownership of a cannabis business shall be submitted through a cannabis business application, together with all required fees and documentation. The transferee shall meet all eligibility requirements for a cannabis business under this chapter.

5.22.060 Investigation and fingerprinting of applicant.

A. Prior to the acceptance of applications for a license, transfer of ownership, or other approval as provided in this chapter, the following individuals shall authorize the Chief of Police to perform criminal background investigation by providing verified fingerprint information to the Ceres Police Department:

1. If the applicant is a natural person, that person.

2. If the applicant is a partnership, all of the partners.

3. If the applicant is a corporation, both the officers and directors, together with any person with an ownership interest of ten percent (10%) or more.

B. No cannabis business shall be permitted to operate in the City if the background investigation indicates disqualifying criminal history.

5.22.070 Development agreement.

A. No cannabis business shall commence or continue operations in the City without obtaining and maintaining a valid development agreement in full force and effect.

B. An applicant shall be eligible to enter into a development agreement upon completion of background investigation of all applicable individuals.

C. Development agreements shall be issued pursuant to Ceres Municipal Code chapter 18.37.

D. A development agreement may be approved prior to an applicant having received all required state licenses and local permits; however, no cannabis business shall ITEM 9a & 9b

ATTACHMENT C
4906-8613-4427, v. 3
receive a certificate of occupancy nor operate in the City prior to possessing the required state and local licenses and approvals.

E. Development agreements may not be transferred, sold, assigned or bequeathed expressly or by operation of law. Any attempt to directly or indirectly transfer a development agreement shall be unlawful and void and shall automatically revoke the permit.

F. Development agreements shall be periodically reviewed pursuant to Ceres Municipal Code section 18.37.180.

5.22.080 Termination of development agreement.

A. Termination of development agreements shall follow procedures provided by Ceres Municipal Code chapter 18.37.

B. Upon termination a development agreement, an operator’s cannabis conditional use permit and City business license shall be subject to revocation.

5.22.090 Cannabis business tax.

A. All cannabis businesses within the City are subject to the Cannabis Business Tax established by Ceres Municipal Code chapter 3.26.

B. A cannabis business’ failure to pay the Cannabis Business Tax constitutes grounds for revocation of its development agreement, cannabis conditional use permit or City business license.

5.22.100 Operational requirements.

A. Cannabis business operations shall comply with all applicable state and local laws and regulations.

B. Cannabis business operations shall comply with the conditions of approval of their cannabis conditional use permit.

C. A cannabis business shall immediately cease operations upon revocation of its development agreement, cannabis conditional use permit, or City business license and operator shall comply with all closure and inventory disposal requirements under this code and state and local law and regulations.

5.22.110 Limit on number of cannabis dispensaries.

A. The total number of licensed cannabis dispensaries operating within the city shall not exceed two (2) at any given time.

B. If the maximum number of cannabis dispensaries is reached, no additional cannabis dispensaries shall be issued a development agreement or cannabis conditional use permit until an existing cannabis dispensary’s development agreement and cannabis conditional use permit is voluntarily surrendered, revoked, or otherwise terminated.

5.22.120 Inspections.

ITEM 9a & 9b

ATTACHMENT C
4906-8613-4427, v. 3
A. The City Manager and any authorized City official shall have the right to enter the premises of any cannabis business, during regular business hours or at any other reasonable time, to inspect the premises and business records to ensure compliance with this code, any conditions of approval, and state and local law and regulations.

5.22.130 Enforcement.

A. The Chief of Police or their designee shall be responsible for enforcement of this chapter.

B. Violation of any condition of approval of a cannabis conditional use permit shall constitute a violation of this chapter.

C. Violations of this chapter are subject to administrative remedies provided by Ceres Municipal Code chapter 19.10.

D. The amount of fine imposed for violation of this chapter shall not exceed:
a. Schedule 1. Five Hundred Dollars ($500) for a first violation. b. Schedule 2. Seven hundred and Fifty Dollars ($750) for a second violation of the same code section within one (1) year.
c. Schedule 3. One Thousand Dollars ($1,000) for each additional violation of the same code section within one (1) year.

E. Each violation of this chapter, or of any condition of approval of a cannabis conditional use permit, shall constitute a separate offense.

F. Any permittee whose cannabis conditional use permit, development agreement, or City business license is revoked shall immediately cease all cannabis-related operations within the City.

G. In addition to any other remedy, the City may seek injunctive relief and may recover costs of enforcement, including attorneys’ fees.

H. The remedies provided herein are cumulative and in addition to any other remedies available under law.

5.22.140 Public nuisance.

A. Any commercial cannabis use or activity caused or permitted to exist in the City in violation of any provision of this chapter shall be and is hereby declared a public nuisance and may be abated by the City pursuant to the procedures provided by Ceres Municipal Code chapter 19.07.

B. The remedies provided in this section are cumulative and do not limit the City’s authority to pursue all other remedies available under law.

5.22.150 Cost recovery.

A. The City shall be entitled to recover its abatement and enforcement costs incurred in obtaining compliance with this code. Costs incurred by the City are recoverable even if a public nuisance or violation of this code, the Ceres Municipal Code, or ITEM 9a & 9b

ATTACHMENT C
4906-8613-4427, v. 3
state law or regulation is corrected by the property owner or other responsible party.

B. The cost of abating a public nuisance or enforcing this code shall either be a special assessment and lien on the subject property or the personal obligation of the owner of the subject property or the responsible party. If there is more than one (1) responsible party, each party shall be jointly and severally liable for the costs.

5.22.160 Nonconforming use.

Any cannabis business established or operating in the City in violation of this chapter shall not be considered a lawful or permitted nonconforming use, and no such cannabis business shall be eligible for issuance of any permits or approvals under the Ceres Municipal Code. Further, any such unlawfully established cannabis business shall constitute a public nuisance subject to abatement by the City.

5.22.170 Relationship to other laws.

Except as otherwise specifically provided herein, this chapter incorporates the requirements and procedures set forth in chapter 1 (commencing with section 26000) of division 10 of the California Business and Professions Code, or its successors. In the event of any conflict between the provisions of this chapter and the provisions of that chapter or any other applicable state or local law, the more restrictive provision shall control.

5.22.180 Severability.

Should any provision of this chapter, or its application to any person or circumstance, be determined by a court of competent jurisdiction to be unlawful, unenforceable or otherwise void, that determination shall have no effect on any other provision of this chapter or the application of this chapter to any other person or circumstance and, to that end, the provisions hereof are severable.

ITEM 9a & 9b

ATTACHMENT D
Chapter 44, Cannabis Conditional Use Permits, shall be added to of Title 18, Zoning, of the Ceres Municipal Code which shall read as follows:

Chapter 18.44 - CANNABIS CONDITIONAL USE PERMITS
Sections:

18.44.010 Definitions.

18.44.020 Cannabis conditional use permit required.

18.44.030 Cannabis conditional use permit application.

18.44.040 Cannabis conditional use permit procedure.

18.44.050 Revocation of cannabis conditional use permit.

18.44.060 Conditions of approval for cannabis conditional use permit.

18.44.070 General conditions.

18.44.080 Premises conditions.

18.44.090 Security conditions.

18.44.100 Signage conditions.

18.44.110 Cannabis waste conditions.

18.44.120 Odor control conditions.

18.44.130 Cultivation conditions.

18.44.140 Manufacturing conditions.

18.44.150 Cannabis delivery conditions.

18.44.160 Insurance conditions.

18.44.170 Severability.

18.44.010 Definitions.

Applicant: a person that files an application for a cannabis conditional use pursuant to this chapter.

Cannabis: all parts of the plant Cannabis sativa Linnaeus, Cannabis indica, or Cannabis ruderalis, whether growing or not; the seeds thereof; the resin, whether crude or purified, extracted from any part of the plant; and every compound, manufacture, salt, derivative, mixture, or preparation of the plant, its seeds, or resin. “Cannabis” also means the separated resin, whether crude or purified, obtained from cannabis. “Cannabis” does not include the mature stalks of the plant, fiber produced from the stalks, oil or cake made from the seeds of the plant, any other compound, manufacture, salt, derivative, mixture, or preparation of the mature stalks (except the resin extracted therefrom), fiber, oil, or cake, or the sterilized seed of the plant which is incapable of germination. “Cannabis” does not mean “industrial hemp” as defined by Cal. Health & Safety Code § 11018.5.

Cannabis business: any person or entity that engages in commercial cannabis activity.

ITEM 9a & 9b

ATTACHMENT D
4901-9532-7641, v. 1
Cannabis business tax: the tax imposed by the City on persons engaged in a cannabis business pursuant to Ceres Municipal Code chapter 3.26.

Cannabis conditional use permit: a conditional use permit issued to a cannabis business pursuant to this chapter.

Cannabis cultivation business: any business engaged in commercial cannabis activity involving the planting, growing, harvesting, drying, curing, grading, or trimming of cannabis.

Cannabis delivery: the sale of cannabis and cannabis products by delivery to a customer pursuant to a Type 10 State cannabis license. “Cannabis delivery” does not mean the transfer or sale of cannabis or cannabis products between two cannabis businesses.

Cannabis dispensary: a business at a particular location involving the distribution of cannabis to customers pursuant to a Type 10 State cannabis license that is consistent with State law and this chapter.

Cannabis manufacturing business: a business engaged in commercial cannabis activity involving compounding, blending, extracting, infusing, packaging, labeling, or otherwise making or preparing a cannabis product.

Cannabis product: cannabis that has undergone a process whereby the plant material has been transformed into a concentrate, including, but not limited to, concentrated cannabis, or an edible or topical product containing cannabis or concentrated cannabis and other ingredients.

Cannabis waste: waste that is cannabis or cannabis product that has been discarded, destroyed, or is no longer usable or saleable, including plant material, trimmings, extracts, infused products, packaging containing cannabis residue, or other materials contaminated with cannabis.

City Manager: the Ceres City manager or their designee.

City business License: a business license issued by the City pursuant to Ceres Municipal Code chapter 5.02.

Commercial cannabis activity: the cultivation, manufacture, distribution, processing, storing, laboratory testing, packaging, labeling, transportation, delivery, or sale of cannabis or cannabis products that requires a state license, including medicinal cannabis or medicinal cannabis product as defined in section 26001 of the Business and Professions Code.

Customer: natural person 21 years of age or older or a natural person 18 years of age or older who possesses a physician's recommendation, or a primary caregiver who purchases or otherwise lawfully obtains cannabis or cannabis products from a licensed ITEM 9a & 9b

ATTACHMENT D
4901-9532-7641, v. 1
cannabis business for personal use, whether for medicinal or adult-use purposes, and not for resale.

Permittee: any person, business, or entity that has been issued a cannabis conditional use permit by the City under this chapter, and includes the permit holder’s agents, employees, successors, and assigns acting within the scope of the permit.

Premises: the land, buildings, structures, and any other improvements or facilities occupied, used, or intended to be used by a permittee for the operation of a cannabis business.

Person: an individual, firm, partnership, joint venture, association, corporation, limited liability company, estate, trust, business trust, receiver, syndicate, or any other group or combination acting as a unit and includes the plural as well as the singular number.

Temporary structure shall mean a structure that is erected or placed on a lot for a limited and specified period, not intended for permanent occupancy, and removed upon expiration of the approved time period.

18.44.020 Cannabis conditional use permit required.

A. No cannabis business shall operate in the City unless it has first obtained and continues to maintain compliance with all of the following:

1. All applicable state licenses and permits.

2. A cannabis conditional use permit.

3. A validly executed development agreement.

4. A City business license.

B. Any cannabis business that fails to satisfy any of the requirements in subsection (A) shall immediately cease operations and shall not resume operations until that cannabis business is in full compliance with all applicable requirements.

18.44.030 Cannabis conditional use permit application.

A. An applicant shall file the following information with the City at the time of application for a cannabis conditional use permit:

1. A completed cannabis business application.

2. Completed background checks of all applicable individuals pursuant to Ceres Municipal Code section 5.22.060.

3. Any additional information required by the City Manager.

B. No cannabis conditional use permit application shall be processed unless the applicant pays the application fee in an amount to be established by resolution of the City Council.

18.44.040 Cannabis conditional use permit procedure.

ITEM 9a & 9b

ATTACHMENT D
4901-9532-7641, v. 1
A. A cannabis conditional use permit shall be processed in accordance with the procedures set forth in Ceres Municipal Code chapter 18.30.

B. A permittee seeking to amend the conditions of approval of its cannabis conditional use permit shall submit a written request to the City Manager and pay applicable processing fees. Amendments that do not substantially change the type or scope of use may be approved by the City Manager. All other amendments shall require a public hearing and Planning Commission approval.

18.44.050 Revocation of cannabis conditional use permit.

A. A cannabis conditional use permit may be revoked based on certain findings, including but not limited to if any of the following:

1. That the permittee has violated any condition of approval of its cannabis conditional use permit.

2. That the permittee has violated any term or condition of its development agreement.

3. That the permittee’s development agreement has been revoked, terminated, or otherwise rendered invalid.

4. That the permittee’s City business license has been revoked, suspended, or otherwise rendered invalid.

5. That the permittee has failed to pay any applicable cannabis business tax.

6. That the permittee’s applicable state license has been revoked, suspended, or otherwise rendered invalid.

7. That the permittee has violated any provision of the Ceres Municipal Code.

8. That the permittee has violated any applicable state or local law or regulation.

9. That the use is being exercised in such a way as to be detrimental to the public health, safety, or welfare, or in such a manner as to constitute a nuisance.

10.That the use for which approval was granted has ceased to exist or has been suspended for a period in excess of six months.

B. Revocation of a cannabis conditional use permit shall be processed in accordance with the procedures set forth in Ceres Municipal Code chapter 18.30.

C. Upon revocation of a cannabis conditional use permit, all cannabis operations on the premises shall immediately cease, and the permittee shall comply with all closure and inventory disposal requirements under this code and state law and regulations.

18.44.060 Conditions of approval for cannabis conditional use permit.

Upon approval of a cannabis conditional use permit, the Planning Commission may impose conditions in excess of the requirements set forth in this chapter.

ITEM 9a & 9b

ATTACHMENT D
4901-9532-7641, v. 1

18.44.070 General conditions.

A. Permittee shall not operate without a valid cannabis conditional use permit, nor shall a permittee operate if its cannabis conditional use permit has been revoked, suspended, or otherwise rendered invalid.

B. Permittee shall not operate in violation of the conditions of its cannabis conditional use permit.

C. Permittee shall obtain and maintain a valid development agreement. Any breach or default of permittee’s development agreement or revocation of the development agreement shall be grounds for revocation of a cannabis conditional use permit.

D. Permittee shall obtain and maintain a valid City business license.

E. Permittee shall comply with all state and local laws and regulations.

F. Permittee shall timely pay the applicable taxes pursuant to state and local laws.

G. Permittee shall not make any operational changes to its cannabis business operations without an approved amendment to its conditional use permit.

H. A cannabis conditional use permit may be issued prior to an applicant having received all required state licenses; however, no cannabis business shall receive a certificate of occupancy nor operate in the City prior to possessing the required state and local licenses and permits.

18.44.080 Premises conditions.

A. The premises must be fully compliant with all applicable federal, state, and local laws and regulations.

B. Permittee’s operations shall be conducted within fully enclosed buildings.

Operations, including storage and cultivation of cannabis, shall not be visible from the exterior of any building.

C. The premises shall not be located within a 1000-foot radius of any park, day care center, youth center or public or private school providing instruction to prekindergarten, kindergarten, or grades 1-12. The distance specified in this subsection shall be the horizontal distance measured in a straight line without regard to intervening structures, from the property line of the lot on which the cannabis business is located to the nearest property line of those uses described in this subsection.

D. Permittee shall not establish, operate, or maintain any cannabis business within a temporary structure on the premises.

E. No person shall sell, dispense, or consume alcoholic beverages or tobacco products on the premises.

F. No person shall consume cannabis or cannabis products on the premises.

G. Permittee shall take all necessary and reasonable steps to discourage and prevent unlawful or disorderly conduct, including loitering, from occurring on the premises ITEM 9a & 9b

ATTACHMENT D
4901-9532-7641, v. 1
and in the immediate area surrounding the premises during business hours and after closing.

H. The premises shall comply with a site plan approved or conditionally approved as part of its cannabis conditional use permit. Permittee’s noncompliance with its approved or conditionally approved site plan constitutes a violation of its cannabis conditional use permit.

18.44.090 Security conditions.

A. All entrances and exits to buildings on the premises shall be secured with commercial locks or similar measures to prevent unauthorized entry.

B. Permittee’s shall have a digital video surveillance system monitoring all entrances, exits, cannabis cultivation and processing rooms, cannabis point of sale rooms, limited access rooms and security rooms on the premises.

1. Surveillance cameras shall record continuously, 24 hours a day.

2. Surveillance cameras must provide sufficient resolution and color fidelity to identify individuals on the premises.

3. Surveillance recordings shall be maintained for a minimum of ninety (90) days, stored in such a way that protects the recordings from tampering or theft, and be made available to the City upon request.

C. Permittees shall ensure a licensed alarm company operator installs, maintains, monitors, and responds to the alarm system.

1. Upon request, permittee shall make available to the City all information related to the alarm system, monitoring, and alarm activity.

D. Permittee must store all cannabis, cannabis products, and cannabis waste in locked and secure areas.

E. The City may impose additional site-specific security conditions on permittee as necessary to protect public health and safety or to address unique risks associated with the location or type of cannabis operation.

F. Permittee shall comply with the security plan approved or conditionally approved as part of its Cannabis Conditional Use Permit. Permittee’s noncompliance with its approved or conditionally approved security plan constitutes a violation of its cannabis conditional use permit.

G. The City Manager, Chief of Police or other designated City official may require updates or revisions to a Permittee’s Security Plan at any time based on operational changes, observed risks, or complaints.

18.44.100 Signage conditions.

A. Permittee’s signage shall comply with the sign standards set forth by state law and regulation and by this Code.

B. Offsite and temporary signs are prohibited.

ITEM 9a & 9b

ATTACHMENT D
4901-9532-7641, v. 1
C. Permittee’s signs shall be approved by the Director of Community Development prior to installation. Changes or modifications to signage require prior written approval from the Director of Community Development.

18.44.110 Cannabis waste conditions.

A. Permittee shall secure all cannabis waste in locked designated areas within the premises until properly disposed of in compliance with state law.

B. Permittee shall maintain records of all cannabis waste disposal activities, including quantities, dates, and responsible parties. Records shall be made available to the City upon request.

C. Permittee shall comply with the cannabis waste plan approved or conditionally approved as part of its cannabis conditional use permit. Permittee’s noncompliance with its approved or conditionally approved cannabis waste plan constitutes a violation of its cannabis conditional use permit.

18.44.120 Odor control conditions.

A. Permittee shall install and maintain an odor control system designed to prevent cannabis odors from escaping the interior of the facility. Cannabis odors shall not be detectable at the exterior of the premises or within adjacent properties.

B. Odors from Permittee’s premises may not unreasonably impact adjacent properties or public areas, consistent with state law and regulation and local nuisance standards.

C. Permittee shall comply with the odor control plan approved or conditionally approved as part of its cannabis conditional use permit. Permittee’s noncompliance with its approved or conditionally approved odor control plan constitutes a violation of its cannabis conditional use permit.

18.44.130 Cultivation conditions.

A. This section is only applicable to permittees granted a cannabis conditional use permit for a cannabis cultivation business.

B. Outdoor commercial cannabis cultivation is prohibited.

C. Permittee shall only perform cultivation methods authorized by its cannabis conditional use permit. Any additional cultivation methods may only be conducted with an amendment to a cannabis conditional use permit.

D. Permittee shall obtain and maintain a valid Industrial Waste Discharge Permit issued by the City pursuant to chapter 13.19 of this Code. Permittee shall comply with all requirements of its Industrial Sewage Permit.

E. If applicable, Permittee shall register with the Stanislaus County Department of Hazardous Materials Division. Permittee shall comply with all requirements imposed by the Stanislaus County Department of Hazardous Materials Division.

ITEM 9a & 9b

ATTACHMENT D
4901-9532-7641, v. 1
F. Permittee shall comply with all fire, building, and electrical codes, including specific requirements for flammable solvents, pressurized gases, and chemical storage.

G. Permittee must obtain and maintain fire safety approval from the City Fire Chief.

H. Operations shall not create a public or private nuisance, including, but not limited to, noise, odor, lighting, or pest management impacts on neighboring properties.

I. Permittee shall comply with the cannabis cultivation plan approved or conditionally approved as part of its cannabis conditional use permit. Permittee’s noncompliance with its approved or conditionally approved cannabis cultivation plan constitutes a violation of its cannabis conditional use permit.

18.44.140 Manufacturing conditions.

A. This section is only applicable to permittees granted a cannabis conditional use permit for a cannabis manufacturing business.

B. Permittee shall only perform manufacturing methods authorized by its cannabis conditional use permit. Any additional manufacturing methods may only be conducted with an amendment to a cannabis conditional use permit.

C. Permittee shall obtain and maintain a valid Industrial Waste Discharge Permit issued by the City pursuant to Chapter 13.19 of this Code. Permittee shall comply with all requirements of its Industrial Sewage Permit.

D. If applicable, Permittee shall register with the Stanislaus County Department of Hazardous Materials Division. Permittee shall comply with all requirements imposed by the Stanislaus County Department of Hazardous Materials Division.

E. Permittee shall comply with all fire, building, and electrical codes, including specific requirements for flammable solvents, pressurized gases, and chemical storage.

F. Permittee must obtain and maintain fire safety approval from the City Fire Chief.

G. Permittee shall obtain and maintain any required clearance from the County Department of Health prior to commencing operations.

H. Permittee shall comply with the cannabis manufacturing plan approved or conditionally approved as part of its cannabis conditional use permit. Permittee’s noncompliance with its approved or conditionally approved cannabis manufacturing plan constitutes a violation of its cannabis conditional use permit.

18.44.150 Cannabis delivery.

A. Cannabis delivery is permitted only as an accessory use to a permitted cannabis dispensary, subject to approval of a cannabis conditional use permit issued pursuant to this chapter.

B. All cannabis delivery shall originate and be dispatched from the premises identified and approved under a cannabis conditional use permit.

C. Prior to providing cannabis or cannabis products to a delivery customer, the Permittee shall confirm the identity and age of the delivery customer as required ITEM 9a & 9b

ATTACHMENT D
4901-9532-7641, v. 1
under State law and shall secure a written or electronic signature of the delivery customer before completing the sale.

18.44.160 Insurance conditions.

Permittee shall maintain insurance in the amounts and of the types that are acceptable to the City Manager. The City shall be named as additional insured on all City-required insurance policies.

18.44.170 Severability.

Should any provision of this chapter, or its application to any person or circumstance, be determined by a court of competent jurisdiction to be unlawful, unenforceable or otherwise void, that determination shall have no effect on any other provision of this chapter or the application of this chapter to any other person or circumstance and, to that end, the provisions hereof are severable.

Section 18.02.010, Definitions and interpretive provisions, of Chapter 2, Definitions, of Title 18, Zoning, of the Ceres Municipal Code shall be amended to add the definition of “Cannabis business” as follows:

18.02.010 - Definitions and interpretive provisions.

For the purpose of carrying out the provisions and intent of this title, words, phrases, and terms shall be deemed to have the meanings ascribed to them and shall be interpreted to have the standards and include the parts, elements and the features set forth in this chapter. When not inconsistent with the context, words used in the present tense include the future; words in the singular number include the plural; words in the plural number include the singular. The word "shall" is mandatory, and the word "may" is permissive. …
Cannabis business: any person or entity that engages in the cultivation, manufacture, distribution, processing, storing, laboratory testing, packaging, labeling, transportation, delivery, or sale of cannabis or cannabis products that requires a state license, including medicinal cannabis or medicinal cannabis product as defined in section 26001 of the Business and Professions Code.

Section 18.13.020, General Provision, of Chapter 13 - P-C, Planned Community Zone, of Title 18, Zoning, of the Ceres Municipal Code shall be amended to add subdivision (L) as follows:

The following general provisions shall apply to all P-C zones:
…
L. Cannabis businesses shall be permitted in any P-C zone subject to a cannabis conditional use permit as provided for in chapter 18.44 of this title.

ITEM 9a & 9b

ATTACHMENT D
4901-9532-7641, v. 1
Section 18.16.040, Conditional uses, of Chapter 16 - C-2, Community Commercial Zone, of Title 18, Zoning, of the Ceres Municipal Code shall be amended to revise the introductory paragraph and add subdivision (M) as follows:

18.16.040 – Conditional Uses
The following uses may be permitted in the C-2 zone subject to a conditional use permit as provided for in chapter 18.3050 or 18.44 of this title. …
M. Cannabis businesses
Section 18.17.040, Conditional uses, of Chapter 17 - C-3, Wholesale Commercial Zone, of Title 18, Zoning, of the Ceres Municipal Code shall be amended to revise the introductory paragraph and add subdivision (L) as follows:

18.17.040 – Conditional Uses
The following uses may be permitted in the C-3 zone subject to a conditional use permit as provided for in chapter 18.30 or 18.44 of this title. …
L. Cannabis businesses
Section 18.18.040, Conditional uses, of Chapter 18 - H-1, Highway Commercial Zone, of Title 18, Zoning, of the Ceres Municipal Code shall be amended to revise the introductory paragraph and add subdivision (E) as follows:

18.18.040 – Conditional Uses
The following uses may be permitted in the H-3 zone subject to a conditional use permit as provided for in chapter 18.30 or 18.44 of this title. …
E. Cannabis businesses
Section 18.19.040, Conditional uses, of Chapter 19 - M-1, Light Industrial Zone, of Title 18, Zoning, of the Ceres Municipal Code shall be amended to revise the introductory paragraph and add subdivision (L) as follows:

18.19.040 – Conditional Uses
The following uses may be permitted in the M-1 zone subject to a conditional use permit as provided for in chapter 18.30 or 18.44 of this title. …
L. Cannabis businesses
ITEM 9a & 9b

ATTACHMENT D
4901-9532-7641, v. 1
Section 18.20.040, Conditional uses, of Chapter 20 - M-2, General Industrial Zone, of Title 18, Zoning, of the Ceres Municipal Code shall be amended to revise the introductory paragraph and add subdivision (T) as follows:

18.20.040 – Conditional Uses
The following uses may be permitted in the M-2 zone subject to a conditional use permit as provided for in chapter 18.30 or 18.44 of this title. …
T. Cannabis businesses
ITEM 9a & 9b
ITEM 9a & 9b

ATTACHMENT E

CITY OF CERES

NOTICE OF PUBLIC HEARING
NOTICE IS HEREBY GIVEN that the City Council of the City of Ceres will conduct public hearings to receive and consider all evidence, reports, and testimony on Monday, March 23, 2026, at 6:00 p.m., or as soon thereafter as the matters may be heard, in the City Council Chambers located at 2701 Fourth Street, Ceres, CA on the following:

1. The approval of a Resolution establishing the Cannabis Business Tax rates pursuant to Chapter 3.26, Cannabis Business Tax, of Title 3, Revenue and Finance of the Ceres Municipal Code;

2. The adoption of an Ordinance amending Section 5.03.010, General, of Chapter

5.03, General Permit Procedure, and Chapter 22, Cannabis Pilot Program, of Title 5, Business Licenses and Regulations, of the Ceres Municipal Code; and

3. The adoption of a Zoning Ordinance Text Amendment adding Chapter 43, Cannabis Conditional Use Permits, and Amending Applicable Chapters of Title 18, Zoning, of the Ceres Municipal Code.

The purpose of the public hearings is to receive public comments on the proposed actions to revise the City’s cannabis business regulations. The proposed Resolution sets the Cannabis Business Tax rates. The proposed Ordinance amends the City’s commercial cannabis regulations to implement the adopted tax rates, clarify application and operational procedures for cannabis businesses, and expand the City’s enforcement authority related to cannabis business regulation. The proposed Zoning Ordinance Text Amendment requires all cannabis businesses to obtain and maintain a Cannabis Conditional Use Permit and identifies the zoning districts in which cannabis businesses are permitted as conditional uses.

All Interested parties are invited to attend the public hearing and provide comments on the proposed Ordinance. Public comments may be submitted by emailing [email protected] by 4:00 p.m. on the date of the hearing or verbally at the hearing.

Further information on the above hearing may be obtained or viewed at the office of the City Clerk, City Hall, 2220 Magnolia Street, Ceres, CA 95307 during regular business hours or by telephone at (209) 538-5731.

If a citizen wishes to challenge the nature of the above actions in court, they may be limited to raising only those issues they or someone else raised at the public hearing described in the notice, or in written correspondence delivered to the City of Ceres at, or prior to, the public hearing.
/s/ Fallon Martin, City Clerk
Date Notice Posted: March 11, 2026
ITEM 9a & 9b
ITEM 9a & 9b

COUNCIL AGENDA REPORT

CITY COUNCIL
Javier Lopez, Mayor
James Casey, Dist.1
Rosalinda L. Vierra, Dist. 2
Cerina Otero, Dist. 3
Daniel A. Martinez, Dist. 4
Meeting Date: April 13, 2026
To: Mayor and City Council
From: Trenton Johnson, Acting City Manager
Contact:

Trenton Johnson, Police Chief
[email protected], (209) 538-5725
Travis Hudson, Lieutenant
[email protected], (209) 538-5607
SUBJECT:

Resolution No. 2026-XXX, Approving a Budget Amendment in the Amount of $89,991.52 for Fiscal Year 2025-26 to Appropriate Abandoned Vehicle Abatement Funds to Purchase a New Vehicle from Downtown Ford Sacramento Center and Upfitting of Said Vehicle
RECOMMENDED COUNCIL ACTION:

Staff recommends that the City Council authorize the City Manager to approve a budget amendment in the amount of $89,991.52 for Fiscal year 2025-26 to appropriate Abandoned Vehicle Abatement (AVA) Funds to purchase a new vehicle from Downtown Ford Sacramento Center and upfitting of said vehicle.

I. BACKGROUND:

The AVA (Abandoned Vehicle Abatement) unit has needed a replacement vehicle for several years. The unit is currently operating a 2013 Ford F-150 with approximately 100,000 miles. The vehicle has exceeded its optimal service life and has become increasingly expensive to maintain, with repair costs expected to continue to rise.

Additionally, it lacks modern vehicle safety features such as a backup camera and lanedeparture or lane-assist indicators.

The in-vehicle CAD computer and police radio are outdated and in need of replacement.

Portions of the vehicle are beginning to show signs of rust, and it is not fuel-efficient. The existing emergency lightbar is worn and no longer provides the level of visibility offered by newer systems. Furthermore, the vehicle is not equipped with Parking Enforcement License Plate Reader (LPR) equipment, limiting the unit’s operational efficiency.

ITEM 10
II. REASONS FOR RECOMMENDATION:

The current 2013 Ford F-150 AVA vehicle has exceeded its useful lifespan within the fleet and has become increasingly expensive to maintain, with ongoing repair costs expected to continue. The proposed replacement vehicle has been identified as a Ford Ranger pickup, which is smaller and more versatile than the Ford F-150 and offers improved fuel efficiency.

The new vehicle will be equipped with an updated police radio and a laptop-based CAD computer. It will also be outfitted with a License Plate Reader (LPR) system specifically designed for parking enforcement. This LPR system will allow AVA officers to track and geolocate vehicles and will automatically scan license plates to notify officers when a vehicle’s registration is expired.

Overall, the new vehicle will utilize modern technology to improve enforcement efficiency, accuracy, and officer safety and with the new vehicle graphics it will proudly display our department Core Values of Pride, Integrity and Excellence.

III. FISCAL IMPACTS:

The total cost for the purchase and upfitting of the new AVA vehicle is $89,991.52.

Funding for this vehicle will be provided through the AVA Fund which is restricted to expenditures related to Abandoned Vehicle Abatement operations. A Fiscal Year 2025- 2026 budget amendment is required for the purchase and upfitting to account number 29509.051100. This budget amendment will have no General Fund impact. $40,183.60 Ford Ranger Pickup (See Attachment C)
$10,387.54 - Vehicle upfitting to including emergency lights, console, computer mount, toolbox (See Attachment D)
$24,912.88 - LPR (license plate reader) installation and 1year service contract. (See Attachment E)
$8,673.63 - Police radio (See Attachment E)
$5,311.24 - CAD computer (See Attachment G)
$522.63 - Vehicle graphics (See Attachment H)
IV. EXISTING POLICY / RELATIONSHIP TO THE STRATEGIC PLAN:

Approval of this AVA Vehicle purchase and upfitting fulfills the strategic plan for Government Operations to “Provide quality services to meet community needs, assuring that the City has…properly equipped…staff.”
V. POLICY ALTERNATIVES:

Council could choose not to approve this service agreement. AVA Officers will continue to use their assigned vehicle but will experience significant down time due to repairs and maintenance.

ITEM 10
VII. PUBLIC PARTICIPATION:

N/A
VIII. ENVIRONMENTAL REVIEW:

N/A
IX. STEPS FOLLOWING APPROVAL:

Following Council approval, the Motorola Radio Quote will be routed through the City Clerk’s office for the appropriate signatures, and the Finance Director will implement the Budget Amendment.

Approved by: ________________________
Trenton Johnson,
Acting City Manager
Attachments:

1. Attachment A – Resolution

2. Attachment B – Budget Amendment

3. Attachment C – Vehicle Quote

4. Attachment D – BWE 209/Jay’s Tires Outfitting Quote

5. Attachment E – Motorola LPR Quote

6. Attachment F – Radio Quote

7. Attachment G – Computer Quote

8. Attachment H – Decals

9. Attachment I – Jay’s Tires Agreement
ITEM 10
ITEM 10

ATTACHMENT A
RESOLUTION NO. 2026-XXX
APPROVING A BUDGET AMENDMENT IN THE AMOUNT OF $89,991.52 FOR FISCAL YEAR 2025-26 TO APPROPRIATE ABANDONED VEHICLE ABATEMENT FUNDS TO

PURCHASE A NEW VEHICLE FROM DOWNTOWN FORD SACRAMENTO CENTER

AND UPFITTING SAID VEHICLE

THE CITY COUNCIL
City of Ceres
WHEREAS, the Police Department’s Abandoned Vehicle Abatement (“AVA”) Unit currently drives a 2013 Ford F-150 that has exceeded its optimal service life and has become increasingly expensive to maintain; and
WHEREAS, the cost to purchase and upfit a new AVA vehicle will be $89,991.52 and can be fully funded using Abandoned Vehicle Abatement funds, and WHEREAS, a Fiscal Year 2025–26 budget amendment is necessary to appropriate $89,991.52 to account number 29509.051100 for this expenditure.

NOW, THEREFORE, BE IT RESOLVED that the City Council of the City of Ceres hereby approves a budget amendment in the amount of $89,991.52 for Fiscal Year 2025-26 to appropriate Abandoned Vehicle Abatement funds to purchase a new vehicle from Downtown Ford Sacramento Center and upfitting of said vehicle.

BE IT FURTHER RESOLVED that the City of Ceres Finance Director is hereby authorized and directed to record the appropriate accounting entries.

PASSED AND ADOPTED by the Ceres City Council at a regular meeting thereof held on 13
th day of April 2026, by the following vote:

AYES: Councilmembers:

NOES: Councilmembers:

ABSENT: Councilmembers:

ABSTAIN: Councilmembers:
________________________________
Javier Lopez, Mayor
ATTEST:
_______________________________
Fallon Martin, City Clerk
ITEM 10
ITEM 10
Budget Amendment No.

Fiscal Year
Reference Resolution No . , dated authorizing appropriations for as follows:

Appropriations:

Fund Name Org. Object Project
(if appl.)
Appropriation
Amount
Requested Appropriation
Current Appropriation
Total Appropriation
Estimated Revenues:

Fund Name Org. Object Project
(if appl.)
Appropriation
Amount
Estimated Revenue
Current Estimated Revenue
Total Estimated Revenue
Fiscal Impact:

ITEM 10
ITEM 10
ASW-010826-1635
Name DATE 1/8/2026
Address SALES REP AARON
City CERES State CA Zip 95307 PHONE 916-929-0577
Phone FOB SACRAMENTO
Qty Unit Price TOTAL
1 $42,132.00 $42,132.00
CLIN:

OPTIONS
-1 $9,608.00 ($9,608.00)
1 $1,558.86 $1,558.86
1 $299.00 $299.00
1 $2,142.00 $2,142.00
1 $85.00 $85.00
SubTotal $36,608.86
DELIVERY $500.00
Cash SALES TAX $3,065.99
Check CA Tire Tax $8.75
Credit Card TOTAL $40,183.60
Name
CC #
Expires

PRICING BELOW SUBJECT TO CHANGE

BASED ON REGISTRATION ADDRESS

8.375%

DOC FEE
EXTRA CARE - 5 YR / 100K MI / $0 DEDUCT

CKE - EXTRA KEY
R4B - CHANGE TO FORD RANGER XL CREWCAB 4X2
Description
2026 FORD F150 CREWCAB PICKUP 4X2
$500 DISCOUNT WITH PAYMENT IN 20 DAYS
Office Use Only
ULTRA QUOTE # 64693 - WEATHER GUARD TOOLBOX
SALES TAX CALCULATED AT:

EXTERIOR COLOR:

SCOTT KEYS - CITY OF CERES
2220 MAGNOLIA ST
209-538-5796 X: 7135

YZ - OXFORD WHITE
STATE OF CALIFORNIA CONTRACT: 1-22-23-20A
24 525 N16TH STREET, SACRAMENTO, CA 95811
PHONE: 916-299-3529
QUOTE
Payment Details
Customer

ATTACHMENT C
ITEM 10
ITEM 10
WO # 1-19723
Date 01 /15/26

Page 1 of 1 ends