NOTES:

1. TYPICAL CONSTRUCTION:

CABINET TO BE CONSTRUCTED OF 12 GA. COLD ROLLED SHEET METAL. —3-PDINT HANDLE VITH PADLECK • CABINET TO BE FREE STANDING ON A 3 INCH C-CHANNEL BASE.

AND PENTA-BOLT SCREV • 3 INCH C-CHANNEL BASE TO BE HOT-DIP GALVANIZED AFTER FABRICATION.

SEE NOTE #3
• ALL JOINTS TO BE TAMPER RESISTANT.
• MIG WELDING THROUGHOUT.
• ALL EXTERIOR WELDS TO BE GROUND SMOOTH.
• ROOF IS CROSS-KINKED FOR STRENGTH AND DRAINAGE.

CLOSE FLOOR

2. FINISH:
• CABINET TO BE ABRASIVE BLASTED PRIOR TO APPLICATION OF PPG EPOXY 58 SPRAYED ONTO A 3 MIL THICKNESS.
• FINISH COAT TO BE PPG PSX 700 POLYSILOXANE COLORED MUNSELL GREEN SPRAYED ONTO A 3 MIL THICKNESS.
• TOTAL AVERAGE PAINT THICKNESS 6 MIL.
• MEETS ANSI C57.12.28.

CABLE ENTRY (OPEN FLODR).

3. DOORS:
-3-POINT HANDLE WITH PADLOCK - 5/8* THRU (4 PLCS) • DOOR TO BE PROVIDED WITH PAD-LOCKABLE HANDLE WITH THREE POINT 58- AND PENTA-BELT SCREW -58 LATCHING CONSTRUCTED SO THAT CAPTIVE PENTA HEAD BOLT MUST BE SEE NDTE #3
THREADED INTO POSITION BEFORE PADLOCK CAN BE INSERTED.
• MINIMUM DOOR OPENING 105*.

TOP VIEW BASE DETAIL • MEETS ANSI C57.12.28.
• DOORS LIFT OFF OPEN POSITION.
• ALL HINGES TO BE STAINLESS STEEL.

ISOMETRIC VIEW 4. TAMPER RESISTANT GUARD INSIDE ALL LOUVERS.

5. RATINGS:

NOMINAL. ..12 KY
BIL.…...... ...95 KV
CONTINIOUS..... ...200 AMPS
TOTAL REACTIVE POWER.. ... 1800 KVAR
APROX. WEIGHT... ...1700 LBS
-DECAL: "CENTREL INSIDE' - DECAL: "CONTROL INSIDE
88 88
-TECAL: "DANGER HIGH VILTAGE" -JECAL: "DANGER HIGH VOLTNE" 55 55 -POINT HANDLE VI

ADLOCK AND PENTA-BE
SCREW
SEE NDTE #3 SO DE AH, TE NGR
8 8 8 8 8 888 DIA ZINC OR GALVANIZED WITH IN CHANNEL

FLAT WASHER, LOCK WASHER MED CHAN
AND NUT (4 PLCS).
-58 -58- GRADE 5 RECOMMENDED HOE SUPPLIED
— RED CHANEL BASE ON THE CORNER
GUSSET (4 PLCS:

LEFT SIDE VIEW FRONT VIEW RIGHT SIDE VIEW REAR VIEW MIN PROTRUS -CONCRETE

IDE CONCRE PAD BY
DTHER
TITLE: ELEVATION EXTERIOR VIEWS DRAWING RAWING NUMBE
1800KVAR, 12KV, 3PH, 95KV BIL, UNGROUNDED WYE PADMOUNTED CAPACITOR BANI 31057- CUSTOMER: RCMU SPEEWAY COMMERCE CENTER DWN BY: GV Scott manufacturing sourions
REVISIONS DATE APP DRI NOT REVISIONS DATE APP DRN DATE: 3-20-22

BILL OF MATERIAL
ITEM PART NUMBER MANUFACTURER DESCRIPTION ATY.

NO.

U-UBW95 REUEL 200A, 15KV, 95KV BIL BUSHING WELL
LBI215 COOPER 200A, 15KY, 95KY BIL LOADBREAK
2 BUSHING INSERT
PS25-1AMBC-21515 200A, 25KV, 150KV, 120V AC CONTROL 2
ABB

VACUUM SWITH
PA-7181 s&c 13.8KV NOMINAL, 95KV BIL, 6.25" 12

INDOOR INSULATOR
612125 s&c 125E, SMU-20 FUSE REFILL 3
7525A67G08 1500YA, 12KY:120V, 110KV BIL, TYPE VIZ-11
ABB 2 FUSES INDOOR VOLTAGE TRANSFORMER
s&c SM-20 END FITTING
s&c SM-20 FUSE HOLDER LIVE PARTS
COOPER 600 KVAR, 7200V, 110KV BIL DOUBL
5-7/16 -6-7/16 BUSHING CAPACITOI
6 17-1316 462-318-
-58- IPEX USA 4 JAW METER SOCKET

MAXRAD LOW PROFILE ANTENA -

TOP VIEW REAR VIEW WIRE GUARD
SYSTEMS, INC 6"X8"X4" JUNCTION BOX
MARATHON 6 POSITION TERMINAL BLOCK
SMS LABEL ADHESIVE, CONTROL INSIDE 3-7/16X2"
HOOK TO REMUVE REMUVABLE ACRILIC REMDVABLE GPD-3

TRANSFORMER - BARRIER -HANGING BARRIERS

VACUUM SW VACUUM SW
200 AMP 200 AMP
V 600 KVAR . 600 KVAR 600 KVAR
S 125E FUSE S125E FUSE S 12SE FUSE
CPT
13 FUSE 12000/120V
- TIP-OUT ERACKET
9 CARRIN STANDS FUSE 3E von
1-/ 1.50 JPL SAMO NUTS 13 - 0
-13- 58-

BUSHING BUSHING BUSHING
WELL1 WELL 2 WELL 3

FRONT VIEW FRONT VIEW
12KV SOURCE

THREE LINE DIAGRAM
TITLE: ELEVATION INTERIOR VIEWS DRAWING DRAWING NUMBER
1800KVAR, 12KV, 3PH, 95KV BIL, UNGROUNDED WYE PADMOUNTWD CAPACITOR BANK 131057-2 CUSTOMER: WESCO DWN BY: GV Scott
RCMU SPEEDWAY COMMERCE CENTER manucaczuring sauurons
REVISIONS DATE APP DRMI HOT REVISIONS DATE APP DRW DATE: 3-20-22

I END BUS IS WHITE
- 4 CLIP METER SOCKET
49 BLACK/ORANGE T.W.

BLACK COMMON CLOSE
- #6 AWG
#12 JUMPER
WHITE T.W. NEUTRAL * #12 BLACK/ORANGE

PLUG IN CONNECTOR

ON DIL INSULATED

TRANSFORMER

A CONTROL POWER

TRANSFORMER
12KV120V 0000
C B 1500VA € 30°C
FUSES
55 COMMON CLOSE WHITE COMMON
12KV SDURCE
NOTE: CONTROLCABLE #16 3/C T.W.

CONTROL SCHEMATIC DRAWING RAWING NUMBE
IT 1300OKVAR, 12KY, 3PH, SKY BIL, UNGROUED WIE PAOHOUNTED CAPACTOR BANK 31057- CUSTOMER: REMU SPEEDWAY COMMERCE CENTER BAT A 3-20-22 Scott manufacturing socurions
REVISIONS DATE APP DR NOT REVISIONS DATE APP DRW DATE:

FULL PART # 240120-J40P0R66S1
IntelliCap® 2000 Automatic Capacitor Control
Specifications
Conditions of Sale Line voltage, current, kWs, kVAs, kvars, power factor, STANDARD: The seller's standard conditions of sale temperature, and harmonics can all be accessed in real set forth in Price Sheet 150 apply, except as modified time. The IntelliCap 2000 Automatic Capacitor Control by the "Special Warranty Provisions" and "Warranty calculates total harmonic distortion as well as the third Qualifications" sections on page 2. through 15th harmonics every 15 minutes.

The IntelliCap 2000 Automatic Capacitor Control
SPECIAL TO THIS PRODUCT:
provides true RMS voltage and current readings. Over
INCLUSIONS: The microprocessor-based IntelliCap 2000 the operating temperature range of -40° F (-40° C) to Automatic Capacitor Control is specifically designed for 158° F (70° C), temperature readings are accurate to +2° F the control of pole-mounted and pad-mounted switched (+1° C); current readings are accurate to =0.15% full scale, capacitor banks, both in stand-alone and SCADA with a resolution of 1 ampere RMS; and voltage readings applications. Automatic control strategies are software are accurate to +0.15% full scale, with a resolution of selectable. 0.1 Vac. Phase-angle readings are accurate to +1° at 10% The IntelliCap 2000 Automatic Capacitor Control can of full-scale current, with a resolution of ⅛°. be set up locally with a computer through a local USB The IntelliCap 2000 Automatic Capacitor Control connection or through an optional Wi-Fi connection. includes extensive data-logging capabilities. The following Monitoring and troubleshooting are easy to perform using parameters are logged and can be downloaded as tables the faceplate tactile-feedback switches and liquid-crystal display, which shows real-time data and key setpoints. A PC using the Windows® 7 or later operating system can • Temperature, voltage, current, power factor, kvar, kW, and neutral current/voltage (if applicable) (Logging
be connected via a USB faceplate connector. IntelliLink® intervals can be adjusted from 1 minute to 120 minutes, Setup Software is used to view real-time data, manage set in 1-minute intervals [15 minutes is default], for two days points, troubleshoot, and download historical data for
to 120 days of voltage and temperature data.)
reports. The faceplate includes a manual override switch and test points for sensor inputs. An operation counter • Up to 10,000 Historic Log entries—includes switching is provided as a software function. The data logging and events and the date and time of power cycles perpetual calendar are implemented with non-volatile • Daily minimum and maximum voltages, temperatures, memory. current, kWs, kvars, power factor, and neutral current/ The IntelliCap 2000 Automatic Capacitor Control pro- voltage (if applicable), and number of switching cycles vides a full range of automatic functions: in the last month and since installation • Voltage, time, temperature, time-biased voltage, and The IntelliCap 2000 Automatic Capacitor Control supports both one-way and two-way communication.
time-biased temperature control strategies
Distributed Network Protocol (DNP) 3.0 is the standard
• Optional var and current control strategies protocol. A variety of communication devices may be fur- • Optional neutral-current or voltage sensing to detect nished and installed by S&C in the IntelliCap 2000 control blown fuses and stuck switches enclosure. A variety of customer-furnished communication • Voltage/temperature override devices may be accommodated as well. Refer to Table 2 on pages 5 through 7. A pole-mounted single-antenna bracket • Automatic calculation of voltage change caused by
is available to improve radio performance.
capacitor bank switching
• Daily limit on the number of automatic switching Communication equipment may be factory-installed operations inside the control enclosure. SpeedNet™ and MDS Adap- tive Broadband radios can be accommodated as can fiber- • Automatic adjustments for daylight savings time and optic transceivers. For further information, contact your holidays nearest S&C Sales Office.
• SCADA-override strategy, which allows the master EXCLUSIONS: The IntelliCap 2000 Automatic Capacitor station to issue a command and returns the control to Control does not include a neutral sensing input, its regular programmed strategy after a user-selected communication device, antenna, antenna connections, period of time sensors, or cables.

February 20, 2023
Specification Bulletin 1024-31
© S&C Electric Company 2013-2023, all rights reserved
IntelliCap® 2000 Automatic Capacitor Control
Conditions of Sale-Continued of necessary replacement parts. The seller's war- S&C may be able to furnish and install in the Intel- ranty does not apply to any equipment that has been liCap 2000 control enclosure, or make provision for, a disassembled, repaired, or altered by anyone other customer-specified communication device not listed in than the seller. This limited warranty is granted only Table 2 on pages 5 through 7. S&C will need to evaluate to the immediate purchaser or, if the equipment is the physical and electrical requirements of the commu- purchased by a third party for installation in third- nication device and its performance characteristics, and party equipment, the end user of the equipment. The conduct qualification testing to verify its suitability for the seller's duty to perform under any warranty may be desired application. delayed, at the seller's sole option, until the seller has been paid in full for all goods purchased by the
Refer to the nearest S&C Sales Office for scheduling immediate purchaser. No such delay shall extend the information. S&C cannot furnish or install any communi- cation device for which the supplier requires S&C to offer Tier 1 (i.e., "help desk") support. Replacement parts provided by the seller or repairs performed by the seller under the warranty
SPECIFICATION DEVIATIONS: Refer to Table 2 on for the original equipment will be covered by the pages 5 through 7. above special warranty provision for its duration.

SPECIAL WARRANTY PROVISIONS: The standard Replacement parts purchased separately will be cov- warranty contained in the seller's standard conditions of ered by the above special warranty provision. sale, as set forth in Price Sheet 150, applies to IntelliCap WARRANTY QUALIFICATIONS: Warranty of IntelliCap 2000 Automatic Capacitor Controls, except the first 2000 Automatic Capacitor Controls is contingent upon paragraph of said warranty is replaced by the following: the installation, configuration, and use of the control or General: The seller warrants to the immediate pur- software in accordance with S&C's applicable instruction chaser or end user for a period of 10 years from the sheets. This warranty does not apply to major components date of shipment that the equipment delivered will not of S&C manufacture, such as batteries, communication be of the kind and quality specified in the contract devices, and remote terminal units. However, S&C description and will be free of defects of workman- will assign to the immediate purchaser or end user all ship and material. Should any failure to conform to manufacturers' warranties that apply to such major this warranty appear under proper and normal use
within 10 years after the date of shipment, the seller END USER LICENSE AGREEMENT: The end user is agrees, upon prompt notification thereof and confir- granted a nontransferable, non-sublicensable, nonexclusive mation that the equipment has been stored, installed, license to use the IntelliLink® Setup Software and/or operated, inspected, and maintained in accordance other software furnished with IntelliCap 2000 Automatic with recommendations of the seller and standard
Capacitor Controls only upon acceptance of all the terms industry practice, to correct the nonconformity and conditions of the seller's end user license agreement either by repairing any damaged or defective parts of
set forth in Price Sheet 155.
the equipment or (at the seller's option) by shipment
S&C Specification Bulletin 1024-31
IntelliCap® 2000 Automatic Capacitor Control
How to Order STEP 5. (Optional) Choose the catalog number for the Complete the following steps to build an IntelliCap 2000 desired power cables from Table 6 on page 10.

Automatic Capacitor Control catalog number. Included 00700123602 Catalog Number:
with the steps are fill-in boxes to help keep track of the various components of the final catalog number. STEP 6. (Optional) Choose the appropriate catalog Note: Pay strict attention to the various table footnotes, number for sensor cables from Table 7 on page which identify constraints and considerations regarding 10 and Tables 8 and 9 on page 11. the selection of the various options. Catatog Number: 007001138-01 STEP 1. Choose the capacitor control catalog number
STEP 7. (Optional) Choose the catalog number for the
from Table 1 on page 4.
applicable meter box from Table 10 on page 11.
2 4 012 0
Catalog Number:

Catalog Number: 90400000500
STEP 2. (Optional) Choose the suffixes for any desired Example: The catalog number for an IntelliCap 2000 options from Table 2 on pages 5 through 7. control with a USB connector for local communication A 3 and a padlockable Lexan® NEMA 3R enclosure; control Suffix:
strategies that include time, temperature, and voltage; STEP 3. Choose the mounting type suffix from Table 4 single-phase voltage sensing provided by a customer- on page 9. furnished voltage transformer; a pole-mounting bracket; Sup J 40 and a GPS module with a door-mounted N-Type 900-MHz 5-dB GPS antenna is 240120-JB1A4T2S1.

Note: If the mounting type is not selected, an M-option 240120 JB1A4T2S1
from Step 2 must be specified.

STEP 4. (Optional) Choose the catalog numbers for any
accessories from Table 5 on page 10.

Catalog Number: 903002344 01
S&C Specification Bulletin 1024-31 3
IntelliCap@ 2000 Automatic Capacitor Control
Table 1. IntelliCap 2000 Automatic Capacitor Controls
Page
Control- Output Relay Catalog Reference Net Wt.

Device Source Control Strategies for Lbs.

Voltage Contacts Number Dimensional (Kg.)
Information
Standard: time, temperature, and voltage,
with single-phase voltage sensing provided 240120 8¼
oper Transformer-furnished vollage (3.74)
close
100 to Standard plus var and current with single-
135 Vac, rated 20 A at phase current sensing provided by a 10 8¼ 240160• (3.74)
50 or EV Line Post Sensor ac-turnished CS or
60 Hz
a digita inputs Standard ales varan series pride. ingle phasi 2401644 10 8¼
to 5-A surent transitord - 10 1-A or 0- (3.74)
• and co Line Post Sensors, Cates argued at to Tate 7 • Customer-furnished sensors must be high-impedance, low output energy sensors, to avoid damaging the sensor input and voiding th on page 10 and Tables 8 and 9 on page 11 for ordering information. warranty. A burdened current transformer of any kind cannot be used.

A Customer to provide shorting block.
4 S&C Specification Bulletin 1024-31
IntelliCap®@ 2000 Automatic Capacitor Control
Table 2. Options
Suffix to Be Added
Item to IntelliCap 2000
Catalog Number
Wi-Fi module with antenna, for wireless setup (Not available outside the United States and Canada. Contact S&C for -A3 options in other countries
GPS module (requires GPS antenna. See Table 5 on page 9. Antenna is included with Wi-Fi module with -A4 antenna, suffix "-A3
/i-Fi/GPS module with antenna, for wireless setup (Not available outside the United States and Canad -A5 ontact S&C for options in other countrie
Terminal block cover -c
Door switch, provides "Cabinet Door Open" indication when connected to User Status Input -D Neutral alarm LED indicator -E
Control for 50-Hz system frequency -H
Voltage Input Sensing
Voltage Input, 0- to 10-V from S&C CSV Line Post Current/Voltage Sensor -K1 Reversed colors for OPEN/CLOSE indicators (green = closed, red = open) -L1 Spanish -L51
Portuguese - L520
Foreign language labels, front panel, and screens@ French -L53 Chinese -L54
Arabic -L55
Connectors (multiple types may be specified; standard is terminal strip; option is for bracket mounting, pole, or wall) Neutral sensor cable entry, opening blocked with shipping plug -MO Five-pin mil spec for bracket-mounted control -M10
Seven-pin mil spec for bracket-mounted control -M30
Three-pin mil spec for phase current input
Three-pin mil spec for neutral current/voltage input -M7U Five-pin mil spec for user definable digital inputs -M110 Neutral Input Sensing
Current input, 0-10 V® -N1•
Potential transformer voltage sensor input, 0-144 Vac -N2 S&c Voltage Sensor Input, 0-144 Vac - N3
Lindsey Voltage Sensor Input, 0-5 Vac -N4
Fisher-Pierce AT 929 Sensor Input -N5
Communication Protocol
DNP 3.0 -PO
Labels will add four weeks to lead time. Spanish front panels are • Portuguese labels and front panels are available at standard lead available. Contact the nearest S&C Sales Office for French, Chinese, times. and Arabic front panel availability, and screen availability. • Multiple connectors may be specified. See Table 3 on page 8. 4 May also be used with a four-jaw socket mount control. • Refer to Specification Bulletin 1062-31 for ordering information on neutral current sensors.

TABLE CONTINUED •
S&C Specification Bulletin 1024-31 5
IntelliCap@ 2000 Automatic Capacitor Control
Table 2. Options-Continued
Suffix to Be Added to
Item IntelliCap 2000 Catalog
Number
Communication Device and Mounting (furnished by S&C, requires suffix "-R98") MDS TransNET 900 Transceiver -R18
Multi-Mode Dymec 5843HRT Fiber-Optic Modem -R45
SpeedNet™M Radio -R80
Telemetric DNP-RTMII-FLX for FlexNet system -R148
MDS SD9 Remote Radio •
SpeedNett ME Mesh End-Point Radio -R240
SpeNT Cell Edge Gateway 4G LTE cellular modem for AT&T Cellular Network (With embedded -R320 SpeedNet™ Cell Edge Gateway 4G LTE cellular modem with removable SIM card for USA and Canada@ -R352 Specify the appropriate catalog number suffix based on the frequenc One pication Bulletin 107-31 for Speed Net Cel Edge Gateway and range and application for the radio from the following table. Fo apacation, spely a 90g nur or sure a CLErnet and serial. TABLE CONTINUED • vansmith pited to ply or a makin of providing 12- W average continuous power to the radio. Peak Frequency Band Range, MHZ Application Suffix to be Added to Catalog Number 820 to 870 -R216AK
928 to 960 -R216CK
928 to 960, 50-kHz channel -R216DK
880 to 915 Serial -R216EK
880 to 915, 50-kHz channel -R216FK
850 to 860 / 926 to 936, transmit low -R216GK
850 to 860 / 926 to 936, transmit high -R216HK
820 to 870 -R216AL
928 to 960 -R216CL
928 to 960, 50-kHz channel -R216DL
880 to 915 Ethernet and - R216EL
Serial
880 to 915, 50-kHz channel -R216FL
850 to 860 / 926 to 936, transmit low -R216GL
850 to 860 / 926 to 936, transmit high -R216HL
820 to 870 -R216AM
928 to 960 -R216CM
928 to 960, 50-kHz channel -R216DM
880 to 915 9710 -R216EM
Emulation
880 to 915, 50-kHz channel -R216FM
850 to 860 / 926 to 936, transmit low -R216GM
850 to 860 / 926 to 936, transmit high -R216HM
6 S&C Specification Bulletin 1024-31
IntelliCap®@ 2000 Automatic Capacitor Control
Table 2. Options-Continued
Suffix to Be Added
Item to IntelliCap 2000
Catalog Number
Communication Device Ready for (communication device furnished by customer) MDS 9810 Radio -R02
MDS TransNet 900 Radio -RO7
Silver Spring Networks eBridge Radio -R125
Telemetric DNP-RTMII-FLX for FlexNet system -R147
MDS Mercury 3650 HGR3 Remote Radio -R151
MDS SD9 Remote Radio -R188
SpeedNeft ME Mesh End-Point Radio -R241
Cradlepoint COR IBR600 Series integrated broadband routers -R266 Ready for Tantalus DA Bridge Modem -R273
Sierra Wireless RV50 LTE cellular modem -R316
GE MDS Orbit ECR wireless router with single WAN radio -R328 Cisco IR807 Integrated Services Router with 4G LTE cellular modem -R330 Installation of Communication Device
Furnished by S&C -R98
Furnished by customer -R99
Antenna Connections
N-Type connector, door top mounted (for mounting whip antenna) - S1 N-Type connector, bottom mounted (for remote antenna installation) -S2 PolyPhaser® Surge Suppressor, N-type connector, bottom mounted (for remote antenna installation) -S3 NMO-type mounting for Antenex Phantom Antenna, door top -S4 Dual-band cellular antenna connection -S5
PolyPhaser® Surge Suppressor, N-type connector, 800-2300 MHz, for dual band cellular antenna -S6 Antenna
900-MHz 5-dB gain antenna, door mounted -12
Antenex Spread-Spectrum Antenna -T3
Antenex Phantom Antenna, model TRAB821/18503P, dual band (821-896 and 1850-1990 MHz), 3 dB-MEG - 74 Dual Band LoPro® Cellular Antenna (824-896 and 1850-1990 MHz), 3 dBi -T7 Permanent Phantom Antenna 3G-4G multi-band (698-960, 1700-2700 MHZ) N-type female, black -T18 Note: More radios will be added to the list in the future. physical and electrical requirements of the communica- For other radios not yet in the table, contact S&C. tion device and its performance characteristics and con- Exclusions: S&C may be able to furnish and install duct qualification testing to verify its suitability for the in the IntelliCap 2000 control, or make provision for, a desired application. S&C cannot furnish or install any customer-specified communication device not listed in communication device for which the supplier requires Table 2 on pages 6 and 7. S&C will need to evaluate the S&C to offer Tier I (i.e., "help desk") support.

S&C Specification Bulletin 1024-31 7
IntelliCap® 2000 Automatic Capacitor Control
Table 3. Connector Combinations
Valid Combinations
Numbers in () = Connector Positions Mounting Restrictions Catalog Restrictions M1 (5) JB1 and JB2 only None
M3 (7) JB1 and JB2 only None
M5 (3) Not allowed with J60, J61, J62, J63, J64, J69, and J70 Not allowed with 240120 M7 (3) Not allowed with J60, J68, and J70 None
M11 (5) None None
M1 (5), M5 (3) JB1 and JB2 only Not allowed with 240120 M1 (5), M7 (3) JB1 and JB2 only None
M1 (5), M11 (5) JB1 and JB2 only None
M1 (5), M5 (3), M7 (3) JB1 and JB2 only Not allowed with 240120 M5 (3), M7 (3) Not allowed with J60, J61, J62, J63, J64, J68, J69, and J70 Not allowed with 240120 M3 (7), M11 (5) JB1 and JB2 only None
M5 (3), 11(5) Not allowed with J60, J61, J62, J63, J64, J69, and J70 Not allowed with 240120 M7 (3), M11 (5) Not allowed with J60, J68, and J70 None M5 (3), M7 (3), M11 (5) Not allowed with J60, J61, J62, J63, J64, J68, J69, and J70 Not allowed with 240120 K1 (3) None None
K1 (3), M1 (5) JB1 and JB2 only None
K1 (3), M3 (7) JB1 and JB2 only None
K1 (3), M5 (3) Not allowed with J60, J61, J62, J63, J64, J69, and J70 Not allowed with 240120 K1 (3), M7 (3) Not allowed with J60, J68, and J70 None
K1, M11 (5) None None
K1, M1 (5), M5 (3) JB1 and JB2 only Not allowed with 240120 K1, M1 (5), M7 (3) JB1 and JB2 only None
K1, M1 (5), M11 (5) JB1 and JB2 only None
K1, M5 (3), M7 (3) Not allowed with J60, J61, J62, J63, J64, J68, J69, and J70 Not allowed with 240120 K1, M3 (7), M11 (5) JB1 and JB2 only None
K1, M5 (3), M11 (5) Not allowed with J60, J61, J62, J63, J64, J69, and J70 Not allowed with 240120 K1, M7 (3), M11 (5) Not allowed with J60, J68, and J70 None 8 S&C Specification Bulletin 1024-31
IntelliCap®@ 2000 Automatic Capacitor Control
Table 4. Mounting Type-Must Be Specified
Suffix to Be Added
Item to IntelliCap 2000
Catalog Number
Four-jaw electric meter base DO -J40
Four-jaw electric meter baseD® -J41
Four-jaw electric meter baseD® -J42
Six-jaw electric meter base 13A -J60
Six-jaw electric meter base@3 -J61
Six-jaw electric meter base@3 -J62
Six-jaw electric meter base@S -J63
Six-jaw electric meter base@® -J64
Six-jaw electric meter base@® -J65
Pole-mounting bracket® -JB1
Wall-mounting bracket@S -JB2
Demonstration stand -JB9
Wall-mounting bracket with 3-foot (91-cm) cable, standard wiring® -J67 Six-jaw electric meter base@ -J68
Mounting: Wall-mounting bracket with 3-foot (91-cm) cable. standard wiring with var for current transformer® -J69 transforme all-mounting bracket with 3-f00t (91-cm) cable, standard wiring with var plus neutral, for current -J7O • Sol avail 2n for lap z meter to a win nu cons ain. ) Only available on IntelliCap 2000 control catalog number 2401€ ith neutral input sensing (options "-N1," "-N2," "-N3," or "-N4 and 240164. ® See page 13 for connector configurations. 3 Not available on IntelliCap 2000 control catalog number 240120. © Only available on IntelliCap 2000 control catalog number 240164.

S&C Specification Bulletin 1024-31
IntelliCap@ 2000 Automatic Capacitor Control
Table 5. Accessories
Item Catalog Number
le-mount antenna kit for GPS, includes 25-foot (7.62 meter) cable, mounting bracket, and antenna. Custo 903-002344-01 ble length can be quoted. Requires surge suppressor catalog number 005-001471- Description Model Catalog Number
coaxial cable with MA-30-PM 903-002132-02
connectors on both end
Nith 50-foot (15.2-m
coaxial cable wit MA-50-PM 903-002132-03
anGate Pole-Mount Bracket, includes 40-foot (12.2-m) communications cabl 903-002174-01 der with catalog number suffix "-RO
Table 6. S&C Power Cables-Control to Junction Box
2000 Catalog NumBer (enih, fers) End One Connector End Two Connector Catalog Number 30 (914) 5-pin 5-pin 007-001236-02
35(1067) 5-pin None 007-000262-04
35 (1067) 5-pin 5-pin 007-001236-01
240120 5-pin
40(1219) None 007-000262-01
40(1219) 5-pin 5-pin 007-001236-03
50(1524) 5-pin None 007-000262-03
Table 7. S&C Sensor Cables-Control to Junction Box
For Use with IntelliCap ength, Fee End One Connector End Two Connector Catalog Number 2000 Catalog Number: Centimeters
35 (1067) 7-pin None 007-001138-01
240120 and 24016 35(1067) 7-pin 7-pin 007-001139-01
40(1219) 7-pin None 007-001138-02
10 S&C Specification Bulletin 1024-31
IntelliCap®@ 2000 Automatic Capacitor Control
Table 8. S&C Sensor Cables-Junction Box to Current Sensor For Use with IntelliCap End Two Connector Catalog Number 2000 Catalog Number (engineers) End One Connector
20(610) None 007-000973-04
20(610) 2-pin 007-000767-03
30 (914) 2-pin 007-000767-04
35 (1067) None 007-000973-03
240160 35(1067) None 2-pin 007-000767-05
40(1219) None 007-000973-01
40(1219) 2-pin 007-000767-01
50(1524) None 007-000973-02
50(1524) 2-pin 007-000767-02
Table 9. S&C Sensor Cables—Control to Current Sensor
For Use with IntelliCap Length, Feet End One Connector End Two Connector Catalog Number 2000 Catalog Number (Centimeters)
20(610) 007-000261-04
35(1067) 007-000261-05
40 (1219) 007-000261-01
240160 3-pin 2-pin
50(1524) 007-000261-03
60(1829) 007-000261-02
65 (1981) 007-000261-07
Table 10. Meter Base-Includes Mounting Bracket and Meter Ring [For Use with IntelliCap 2000 Catalog Number Type Catalog Number 240120 4-jaw 904-000005-00
240120, 240160, 240164 6-jaw 904-000005-01
S&C Specification Bulletin 1024-31 11
IntelliCap@ 2000 Automatic Capacitor Control
Electric Meter Base Wiring Configurations

AC LINE - AC NEUTRAL CURRENT SENSOR - AC NEUTRAL
AC LINE — OPEN

OPEN CLOSE CURRENT SENSOR - CLOSE
Four-Jaw Electric Meter Base, Six-Jaw Electric Meter Base, Catalog Number Suffix"-J40" Catalog Number Suffix "-J63" open and close
AC NEUTRAL 8
AC LINE• -AC / SENSOR NEUTRALS CURRENT SENSOR - CURRENT SENSOF Lal NEUTRAL
NEUTRAL SENSOR _ CURRENT SENSOR AC LINE- - OPEN

HOT 'HOT

URRENT SENSOR

OPEN - CLOSE HOT (ALTERNATE - CLOSE
Six-Jaw Electric Meter Base, Six-Jaw Electric Meter Base, Catalog Number Suffix "-J60" Catalog Number Suffix "-J64"

CURRENT SENSOR
HOT — AC NEUTRAL NOT CONNECTED - - AC NEUTRAL

AC LINE - OPEN AC LINE - - OPEN

CURRENT SENSOR - CLOSE NOT CONNECTED - CLOSE
JEUTRA
Six-Jaw Electric Meter Base, Six-Jaw Electric Meter Base, Catalog Number Suffix "-J61" Catalog Number Suffix "-J65"

AC LINE - -AC NEUTRAL AC LINE - - AC NEUTRAL

CURRENT SENSOR - HURRENT SENSOR NEUTRAL SETURN - HOUTRAL SENSOR

OPEN - CLOSE OPEN - CLOSE
Six-Jaw Electric Meter Base, Six-Jaw Electric Meter Base.

Catalog Number Suffix"-J62" Catalog Number Suffix "-J68" 12 S&C Specification Bulletin 1024-31
IntelliCap®@ 2000 Automatic Capacitor Control
Connector Configurations-For Wall or Pole-Mounting Bracket AC neutral and shield ground
Line current
Not connected sensor hot Ac line
Neutral current/
Open - Ac line voltage sensor hot Open
Return for line &
Close - Ac neutral neutral sensors Close
Connector Configuration-M1 Connector Configuration—M3
Bracket-Mounted Control Bracket-Mounted Control
C
Shield Sensor Shield Sensor
return return
Sensor Sensor
hot hot
Connector Configuration—M5 Connector Configuration-M7
Phase Current Input Neutral Current/Voltage Input
E
Not connected
Shield Sensor
Return - Digital input 1 return
Sensor
Digital input 3 Digital input 2 hot
Connector Configuration—M11 Connector Configuration-K1
User-Definable Digital Inputs Line Post Current Voltage Sensor Terminal Strip Configuration-For Wall or Pole Mounting Bracket

INPUT TERMINALS TEST POINTS
1 Ac neutral (connected to terminal 12)
Phase Current Ac-Neutral and
Sensor Hot (+) Sensor Return(s) (-)
Load Ac-Line
oro o
FUSE.
8 Open
9 Close

INPUT TERMINAL BLOCK
transformer of any kind cannot be used.

S&C Specification Bulletin 1024-31 13
IntelliCap@ 2000 Automatic Capacitor Control
Typical Installation of IntelliCap 2000 Automatic Capacitor Control 000000 M
Single-phase voltage transformer Capacitor bank switch
Voltage-transformer
sensing/power cable box Switch close/open cable
Cap bank connection
to common neutral
Neutral sensor
Common neutral
Neutral sensor connection to
junction box
Junction box connection to
control
IntelliCap 2000 Automatic Capacitor Control
• Ground lug
NOTE: Neutral sensor is optional and includes the cable. 14 S&C Specification Bulletin 1024-31
IntelliCap®@ 2000 Automatic Capacitor Control
Typical Installation of IntelliCap 2000 Automatic Capacitor Control Catalog Numbers 240160 and 240164
Single-phase current sensor
Current sensor connection to Current sensor
common neutral connection to junction
box
Single-phase voltage transformer Capacitor bank switch
Voltage-transformer Junction
sensing/power cable box Switch close/open cable
Cap bank connection
to common neutral
Neutral sensor
Common neutral
Neutral sensor connection
to junction box
Junction box connection to
control
IntelliCap 2000 Automatic Capacitor Control
- Ground lug
NOTE: Neutral sensor is optional and includes the cable.

S&C Specification Bulletin 1024-31 15
IntelliCap@ 2000 Automatic Capacitor Control
IntelliCap 2000 Automatic Capacitor Control
Meter-Base Mounted
Dimensions in inches (millimeters)

9.85 (250)
IntelliCap® 2000
Automatic

15.13 Capacitor Control
(384)

14.75 14.75
(375) (375)

11.25 (286)

8.56 (217)

7.75 (197)

8.50 (216)

10.25 (260)
16 S&C Specification Bulletin 1024-31
IntelliCap®@ 2000 Automatic Capacitor Control
IntelliCap 2000 Automatic Capacitor Control
Pole-Mounted
Dimensions in inches (millimeters)

2.50 (64)

0.56 (14)
-10.25 (260) - 9.85 (250)
Ø 1.13 (29)
.84 (21)-
25000 14500
IntelliCap® 200(
Automatic
Capacitor Control
13,00
(38)
156(1) 1)
+.25 (6) -.75 (19)
= 5.00 (127) →
- 11.35 (288)
S&C Specification Bulletin 1024-31 17
IntelliCap@ 2000 Automatic Capacitor Control
IntelliCap 2000 Automatic Capacitor Control
Wall-Mounted
Dimensions in inches (millimeters)
- 9.85 (250)
- 9.00 (229) + 6.00 (152)
Ø.44 (11) - 3.00 (76) - -63 (16)
-.63 (16)
Ø.81 (21)-
- 7.75 (197) -
C
IntelliCap® 2000

14.75 Automatic

18.75 (375) Capacitor Control 17.25
(476) (438)
195)
•44 (11)
* +.125 (3) - 75(19)
- 11.35 (288)
18 S&C Specification Bulletin 1024-31