Spot Repair Schedule of Descriptions
The numbers indicate the Item of Work per Part C of the Specifications. Coordinate these Work Item numbers with the Project Plans on Attachment A. 20 Shellmound St
MAP GRID C4
Repair Length
??
Pipe Diameter
8”
Pipe Material
VCP
Pipe Reach
24.000.04–24.000.03
Rim to Invert
15.9 FT
Distance from Upstream MH:
182.0 FT
Price
Defect
Heavy Mineral Deposits (Concrete)
Repair
Chip away deposits accessible through Maintenance Hole. dig up and replace one length of pipe. $
Description
Replace pipe from Manhole to next upstream joint, approximately 7’-0” of pipe. Open cut/trench required. Remove debris within manhole at joint with Pipe to ensure free flow of wastewater into manhole. 21 53rd St at Hollis St
MAP GRID D4
Repair Length
??
Pipe Diameter
15”
Pipe Material
VCP
Pipe Reach
22.002.16-22.000.21
Rim to Invert
9.1 FT
Distance from Upstream MH:
327.8 FT
Price
Defect
Joint Offset Medium
Repair
Replace (2) segments of Sewer Main starting from downstream maintenance hole towards the upstream direction. $
Description
The length of sewer from joint to joint is assumed to be 7’-0” per segment. 22 53rd St at Emery Bay Dr
MAP GRID D4
Repair Length
??
Pipe Diameter
6”
Pipe Material
VCP
Pipe Reach
22.002.07A-22.002.09D
Rim to Invert
3.2 FT
Distance from Upstream MH:
15.0 FT
Price
Defect
Joint Separated Large
Repair
Open Cut and replace full segment with HDPE SD 17.
$
Description
22 53rd St at Emery Bay Dr
MAP GRID D4
Repair Length
??
Pipe Diameter
6”
Pipe Material
VCP
Pipe Reach
22.002.09D-22.002.07A
Rim to Invert
5.1 FT
Distance from Upstream MH:
47.2 FT
Price
Defect
Tap Break-in Intruding
Repair
Open Cut and replace full segment with HDPE SD 17.
$
Description
23 65th St near Lacoste and Ashby
MAP GRID C1
Repair Length
??
Pipe Diameter
12”
Pipe Material
VCP
Pipe Reach
20.001.04-20.001.03
Rim to Invert
6.0 FT
Distance from Upstream MH:
27.9 FT
Price
Defect
Roots Tap Joint, Broken Pipe, and Roots Medium
Repair
Open Cut and replace full segment with HDPE SD 17.
$
Description
Approximately 40’ in roadway, remainder in unpaved/landscaping area. 24 West MacArthur Blvd near Emery ST
MAP GRID D5
Repair Length
??
Pipe Diameter
12”
Pipe Material
VCP
Pipe Reach
50.001.52-50.001.57
Rim to Invert
10 FT
Distance from Upstream MH:
94.2 FT
Price
Defect
Broken – Soil Visible, Fracture Longitudinal (Continuous) Repair
CIPP liner for full segment
$
Description
25 UPRR near Bay St Complex
MAP GRID C4
Repair Length
??
Pipe Diameter
24”
Pipe Material
VCP
Pipe Reach
22.000.09-22.000.07
Rim to Invert
14.9 FT
Distance from Upstream MH:
49.8 FT
Price
Defect
Fracture Spiral, Deposit Encrustation, Infiltration Gusher Repair
Grout Injection at infiltration location.
$
Description
Trenchless repair
26 Bay St Complex
2 MAP GRID C4
Repair Length
??
Pipe Diameter
24”
Pipe Material
Steel
Pipe Reach
22.000.06A-22.000.06
Rim to Invert
14.8 FT
Distance from Upstream MH:
160.7 FT
Price
Defect
Infiltration Gusher Joint
Repair
Grout Injection at infiltration location.
$
Description
Trenchless repair
Emeryville Sanitary Sewer Main Repairs – Summer 2023
City of Emeryville
INCORPORATED 1896
1333 Park Avenue. Emeryville, CA 94608-3517