ORDINANCE NO. _____
AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF HERCULES AMENDING PROVISIONS OF THE HERCULES MUNICIPAL CODE TITLE 9, CHAPTERS 1–18, ADOPTING BY REFERENCE THE NEW 2022 EDITION OF THE CALIFORNIA CODE OF REGULATIONS TITLE 24 OF THE CALIFORNIA BUILDING STANDARDS CODE WITH AMENDMENTS DEVELOPED BY THE CITY OF HERCULES, CONTRA COSTA COUNTY AND THE RODEO–HERCULES FIRE PROTECTION DISTRICT.

WHEREAS, every three years the State of California adopts new construction codes; and WHEREAS, the City of Hercules desires to adopt the new construction codes with amendments developed and adopted by the City of Hercules through its Ordinance No. 539, Contra Costa County through its Ordinance No. 2022-35 and by the Rodeo–Hercules Fire Protection District through its Ordinance No. 2022-01; and WHEREAS, the findings in support of County and Fire District changes, additions, and deletions to Statewide Building Standards Code are attached to the January 10, 2023 City Council staff report and were reviewed and adopted by the Contra Costa County Board of Supervisors and by the Rodeo–Hercules Fire Protection District Board of Directors; and WHEREAS, adoption of County and Fire District amendments is authorized in Sections 50020-50022.9 of the California Government Code without adopting separate filing of findings and therefore findings are not attached herein nor are they required to be forwarded to the California Building Standards Commission; and WHEREAS, on May 24, 2022, the City of Hercules adopted Ordinance No. 539 “All-Electric Ordinance” amending Chapter 5 of Title 9 of the Hercules Municipal Code to require all newly constructed and rebuilt residential, detached accessory dwelling unit, hotel, and office type buildings be all-electric buildings, with exemptions; NOW, THEREFORE, THE CITY COUNCIL OF THE CITY OF HERCULES DOES HEREBY ORDAIN AS FOLLOWS:

SECTION 1. RECITALS. The City Council hereby incorporates the above recitals into this Ordinance by this reference.

SECTION 2. AMENDMENTS TO ADMINISTRATIVE CODE. Hercules Municipal Code, Title 9, Chapter 1, is hereby repealed and replaced in its entirety to read as follows:

Chapter 1. Building Regulations Administrative Code
Sec. 9-1.01 Administration.

These regulations shall be known as the “California Administrative Code,” and may be so cited, and will be referred to herein as “this Chapter.” This Code is one of the technical codes of Building Regulations and is administered under Title 9, Chapter 1 of the Hercules Municipal Code.

Sec. 9-1.02 Adoption by Reference.

The California Administrative Code, 2022 Edition, published by the International Code Council, as modified by the State of California and published in the “California Code of Regulations, Title 24, Part 1,” is adopted by reference and made a part of this Chapter as though fully set forth herein.

Sec. 9-1.03 Copies on File.

One (1) copy of the 2022 Edition of the California Administrative Code, as adopted by Section 9-1.02, and all amendments thereto, is on file in the office of the Chief Building Official for inspection by the public.

Sec. 9-1.04 Amendments, Additions, and Deletions. The following portion of the Ordinance Code of Contra Costa County, California, is adopted by reference under the authority of Sections HYPERLINK "http://leginfo.legislature.ca.gov/faces/codes_displaySection.xhtml?lawCode=GOV&sectionNum=50020" \t "_blank" 50020 through HYPERLINK "http://leginfo.legislature.ca.gov/faces/codes_displaySection.xhtml?lawCode=GOV&sectionNum=50022.9" \t "_blank" 50022.9 of the California Government Code: Amending the 2022 California Administrative Code by the changes, additions, and deletions set forth in Contra Costa County Ordinance No. 2022-35, Section III, Section 74-4.002 Section numbers used below are those of the 2022 California Building Code.

Expiration of permit.

A permit issued by the county building official becomes void if either of the following occur:

The work authorized by the permit is not commenced within 12 months after the permit issuance date. Evidence that work has commenced consists of at least one approved inspection.

The work authorized by the permit is suspended or abandoned for a period of 12 consecutive months after the work is commenced. Work is deemed suspended or abandoned for a period of 12 consecutive months if no approved inspection occurs during that time.

A permittee holding an unexpired permit may apply to the county building official for a permit extension. Upon written request by the permittee demonstrating justifiable cause for the delay, the county building official may extend the time of the permit for a period not exceeding 180 days. A permit may not be extended more than once.

Once a permit becomes void, a new permit must be obtained before any work is commenced or recommenced, and a new permit fee must be paid.

SECTION 3. AMENDMENTS TO BUILDING CODE. Hercules Municipal Code, Title 9, Chapter 2, Sections 9-2.02, 9-2.03, and 9-2.04 are hereby repealed and replaced in their entirety to read as follows.

Sec. 9-2.02 Adoption by Reference.

The California Building Code, 2022 Edition, (California Code of Regulations, Title 24, Part 2, Volumes 1 and 2), as published by the International Code Council (ICC) and adopted and amended by the California Building Standards Commission in the California Building Standards Code, Title 24 of the California Code of Regulations, is adopted by reference and made a part of this Chapter as though fully set forth herein, subject to the changes, additions, and deletions set forth in this Chapter.

Sec. 9-2.03 Copies on File.

One (1) copy of the 2022 Edition of the California Building Code, as adopted by Section 9-2.02, and all amendments thereto, is on file in the office of the Chief Building Official for inspection by the public.

Sec. 9-2.04 Amendments, Additions, and Deletions. The following portion of the Ordinance Code of Contra Costa County, California, is adopted by reference under the authority of Sections HYPERLINK "http://leginfo.legislature.ca.gov/faces/codes_displaySection.xhtml?lawCode=GOV&sectionNum=50020" \t "_blank" 50020 through HYPERLINK "http://leginfo.legislature.ca.gov/faces/codes_displaySection.xhtml?lawCode=GOV&sectionNum=50022.9" \t "_blank" 50022.9 of the California Government Code:

Amending the 2022 California Building Code (CBC) by the changes, additions, and deletions set forth in Contra Costa County Ordinance No. 2022-35, Chapter 74-4, “MODIFICATIONS” Section 74-4.002 Amendments to CBC as stated below. Section numbers used below are those of the 2022 California Building Code.

CBC Chapter 1 (Scope and Administration) is amended by the provisions of Division 72 of this code and as follows:

Sections 103 and 113 of CBC Chapter 1 are deleted.

Section 105.2 (Work exempt from permit) of CBC Chapter 1, subsection 4 is amended to read:

4. Retaining walls that are not more than 3 feet in height measured from the top of the footing to the top of the wall and that have a downward ground slope at the bottom of the retaining wall not exceeding 1(vertical):10(horizontal), unless supporting a surcharge or ground slope exceeding 1(vertical):2(horizontal) or impounding Class I, II, or III-a liquids.

Section 107.2.1 (Information on construction documents) of CBC Chapter 1 is amended to read:
107.2.1 Information on Construction Documents. Construction documents shall include dimensions and shall be drawn to scale on suitable material. Electronic media documents may be submitted when approved in advance by the building official. Construction documents shall be of sufficient clarity to indicate the location, nature, and extent of the work proposed and to show in detail that it will conform to this code and all relevant laws, ordinances, rules, and regulations. The first sheet of each set of plans shall include contact information for the owner and the person or persons who prepared the plans. Plans shall include a plot plan showing all existing property lines labeled and fully dimensioned, the elevations of the top and toe of cuts and fills, and the location of the proposed building with distances to all property lines and to every existing building on the property. Instead of detailed specifications, the county building official may approve references on the plans to a specific section or part of this code or other ordinances or laws.

Section 110.1 (Inspections - General) of CBC Chapter 1 is amended by adding the following to the end of that section:

At the time of first inspection by the county building official, a California licensed Land Surveyor or Civil Engineer shall certify in writing that the structure is placed according to the approved set of plans. The written certification must include the site address and permit number. This requirement does not apply to alterations or repairs to existing structures that do not affect the exterior limits of the existing structures.

Section 420.13 [HCD] (Electric vehicle (EV) charging for new construction) of CBC Chapter 4 (Special Detailed Requirements Based on Occupancy and Use) is amended to read:
420.14 Electric vehicle (EV) charging for new construction. Newly constructed Group R-1, R-2, and R-3 buildings shall be provided with infrastructure to facilitate future installation and use of electric vehicle (EV) chargers, and, where required, newly constructed Group R-2 buildings shall be provided with electric vehicle charging spaces equipped with fully-operational EV chargers, in accordance with the California Green Building Standards Code (CALGreen), Chapter 4, Division 4.1.

Section 907.2.11.2.5.1 is added to Section 907.2.11.2.5 (Existing Group R occupancies) of CBC Chapter 9 (Fire Protection Systems), to read:
907.2.11.2.5.1 Existing flat roof buildings. In existing flat roof buildings, the installation of a smoke detector that complies with California Residential Code Section R314.6 shall be required when a pitched roof is added on top of the existing flat roof and the solid sheathing of the flat roof is not removed.

Section 1405.2 is added to Section 1405 (Combustible materials on the exterior side of exterior walls) of CBC Chapter 14 (Exterior Walls), to read:
1405.2 Wood shakes or shingles. Wood shakes or shingles used for exterior wall covering shall be fire treated unless there is a minimum of 10 feet from the exterior wall (including shakes or shingles) to the property line or the exterior wall faces a street.

In Section 1705.3 (Concrete construction) of CBC Chapter 17 (Special Inspections and Tests), Exception 1 is amended to read:

Isolated spread concrete footings of buildings three stories or less above grade plane that are fully supported on earth or rock, where the structural design of the footing is based on a specified compressive strength of no greater than 2,500 pound per square inch (psi) (17.2 Mpa).

Section 1809.8 (Plain concrete footings) of CBC Chapter 18 (Soils and Foundations) is deleted.

Section 1810.3.9.3 (Placement of reinforcement) of CBC Chapter 18 (Soils and Foundations) is amended by deleting Exception 3.

Section 1905.1.7 (ACI 318, Section 14.1.4) of CBC Chapter 19 (Concrete) is amended to read:
1905.1.7 ACI 318, Section 14.1.4. Delete ACI 318, Section 14.1.4, and replace with the following:

14.1.4 - Plain concrete in structures assigned to Seismic Design Category C, D, E, or F.

14.1.4.1- Structures assigned to Seismic Design Category C, D, E, or F shall not have elements of structural plain concrete, except as follows:

Reserved.

Isolated footings of plain concrete supporting pedestals or columns are permitted, provided the projection of the footing beyond the face of the supported member does not exceed the footing thickness.

Plain concrete footings supporting walls are permitted, provided the footings have at least two continuous longitudinal reinforcing bars. Bars shall not be smaller than No. 4 and shall have a total area of not less than 0.002 times the gross cross-sectional area of the footing. A minimum of one bar shall be provided at the top and bottom of the footing. Continuity of reinforcement shall be provided at corners and intersections.

Section 1906 (Footings for light-frame construction) of CBC Chapter 19 (Concrete) is deleted.

Section 1907.l (Minimum Slab Provisions - General) of CBC Chapter 19 (Concrete) is amended by adding the following sentence to that section:

Slabs shall have a minimum reinforcement of 6-inch by 6-inch by 10-gauge wire mesh or equal at mid-height.

Appendix C and Appendix I of the CBC are incorporated into the City building code. Appendix A, Appendix B, Appendix D, Appendix E, Appendix F, Appendix G, Appendix H, Appendix J, Appendix K, Appendix L, and Appendix M of the CBC are excluded from the City building code.

SECTION 4. AMENDMENTS TO PLUMBING CODE. Hercules Municipal Code, Title 9, Chapter 3, Sections 9-3.02 and 9-3.03 are hereby repealed and replaced in their entirety to read as set forth below:

Sec. 9-3.02 Adoption by Reference.

The California Plumbing Code, 2022 Edition, (California Code of Regulations, Title 24, Part 5) including the standards based on the 2021 Uniform Plumbing Code of the International Association of Plumbing and Mechanical Officials, as modified by the State of California and as published in the “California Code of Regulations,” is adopted by reference and made part of this Chapter as though fully set forth herein, subject to the additions and deletions as set forth in this Chapter.

Sec. 9-3.03 Copies on File.

One (1) copy of the 2022 California Plumbing Code as adopted by Section HYPERLINK "https://www.codepublishing.com/CA/Hercules/" \l "!/Hercules09/Hercules095.html#9-5.02" 9-3.02 is on file in the office of the Chief Building Official for inspection by the public.

SECTION 5. AMENDMENTS TO MECHANICAL CODE. Hercules Municipal Code, Title 9, Chapter 4, Sections 9-4.02 and 9-4.03 are hereby repealed and replaced in their entirety to read as set forth below:

Sec. 9-4.02 Adoption by Reference.

The California Mechanical Code, 2022 Edition, (California Code of Regulations, Title 24, Part 4) including the appendices, based on the 2021 Uniform Mechanical Code of the International Association of Plumbing and Mechanical Officials, as modified by the State of California and as published in the “California Code of Regulations,” is adopted by reference and made part of this Chapter as though fully set forth herein, subject to the additions and deletions as set forth in this Chapter.

Sec. 9-4.03 Copies on File.

One (1) copy of the 2022 California Mechanical Code as adopted by Section HYPERLINK "https://www.codepublishing.com/CA/Hercules/" \l "!/Hercules09/Hercules094.html#9-4.02" 9‑4.02 is on file in the office of the Chief Building Official for inspection by the public.

SECTION 6. AMENDMENTS TO ELECTRICAL CODE. Hercules Municipal Code, Title 9, Chapter 5 Sections 9-5.02, 9-5.03 and 9-5.04 are hereby repealed and replaced in their entirety to read as set forth below:

Sec. 9-5.02 Adoption by Reference.

The California Electrical Code, 2022 Edition, (California Code of Regulations, Title 24 Part 3) based on the 2017 Edition of the National Electrical Code, as published by the National Fire Protection Association, as modified by the State of California and published in the “California Code of Regulations,” is adopted by reference and made a part of this Chapter as though fully set forth herein, subject to the additions and deletions set forth in this Chapter.

Sec. 9-5.03 Copies on File.

One (1) copy of the 2022 California Electrical Code as adopted by Section HYPERLINK "https://www.codepublishing.com/CA/Hercules/" \l "!/Hercules09/Hercules095.html#9-5.02" 9-5.02 is on file in the office of the Chief Building Official for inspection by the public.

Sec. 9-5.04 Amendments, Additions and Deletions.
(a) Addition to Chapter 1, Section 101, Scope, to read as an additional paragraph as follows:
(1) The Administrative part of this chapter is in addition to the City of Hercules Building Regulations Administrative Code, Title 9, Chapter 1 of the Hercules Municipal Code. Where conflicts occur between this chapter and Title 9, Chapter 1 of the Hercules Municipal Code, the provisions of Title 9, Chapter 1 of the Hercules Municipal Code shall govern. (b) The 2022 California Energy Code (“CEnC”) is amended by the changes, additions, and deletions set forth in this Chapter. Section numbers used below are those of the 2022 California Energy Code. (1) Section 100.0(e)(2)(A) of CEnC Subchapter 1 (All Occupancies – General Provisions) is amended to read:

A. All newly constructed buildings.
(i) Sections 110.0 through 110.12 apply to all newly constructed buildings and rebuilt buildings within the scope of Section 100.0(a), where rebuilt involves demolition and reconstruction of a building or structure involving the repair or replacement of fifty (50) percent or more of the exterior walls or involving work that exceeds one-half (1/2) of the appraised value of the structure. In addition, newly constructed buildings shall meet the requirements of Subsection B, C, D, or E, as applicable. (ii) A newly constructed building that is any of the following building types shall be an all-electric building:
a. Residential
b. Detached Accessory Dwelling Units
c. Hotel
d. Office
Exceptions to Section 100.0(e)(2)(A)(ii):
• Laboratory- and research-specific functions within laboratories and medical buildings (general heating and appliance purposes within laboratories and medical facilities are not exempt). • Emergency facilities and emergency generators;
• Development projects that have obtained vested rights before the effective date of this subsection pursuant to a development agreement in accordance with Government Code section 65866, a vesting tentative map in accordance with Government Code section 66998.1, or other applicable law. (2) Section 100.1(b) (Definitions) of CEnC Subchapter 1 (All Occupancies – General Provisions) is amended by adding the following definition:

ALL-ELECTRIC BUILDING means a building that has no natural gas or propane plumbing installed within the building, and that uses electricity as the sole source of energy for its space heating (including heating of all indoor and outdoor spaces of the building), water heating (including heating of indoor and outdoor pools and spas), cooking appliances, and clothes drying appliances. An all-electric building may utilize natural gas for emergency generators.

SECTION 7. HOUSING CODE. No changes proposed in Hercules Municipal Code, Title 9, Chapter 6.

SECTION 8. BUILDING SECURITY CODE. No changes proposed in Hercules Municipal Code, Title 9, Chapter 7.

SECTION 9. ABATEMENT OF DANGEROUS BUILDINGS. No changes proposed in Hercules Municipal Code, Title 9, Chapter 8.

SECTION 10. BOARD OF APPEALS. No changes proposed in Hercules Municipal Code, Title 9, Chapter 9.

SECTION 11. PENALTIES. No changes proposed in Hercules Municipal Code, Title 9, Chapter 10.

SECTION 12. AMENDMENTS TO ENERGY CODE. Hercules Municipal Code, Title 9, Chapter 11, Sections 9-11.02 and 9-11.03 are hereby repealed and replaced in their entirety to read as set forth below:

Sec. 9-11.02 Adoption by Reference.

The California Energy Code, 2022 Edition, (California Code of Regulations, Title 24, Part 6), including appendices, as published by the International Code Council as modified by the State of California is adopted by reference and made a part of this Chapter as though fully set forth herein, subject to the additions and deletions set forth in this Chapter.

Sec. 9-11.03 Copies on File.

One (1) copy of the 2022 California Energy Code, including appendices, as adopted by Section HYPERLINK "https://www.codepublishing.com/CA/Hercules/" \l "!/Hercules09/Hercules0911.html#9-11.02" 9-11.02, is on file in the office of the Chief Building Official for inspection by the public.

SECTION 13. AMENDMENTS TO HISTORICAL BUILDING CODE. Hercules Municipal Code, Title 9, Chapter 12, Sections 9-12.01, 9-12.02 and 9-12.03 are hereby repealed and replaced in their entirety to read as set forth below:

Sec. 9-12.01 Administration.

These regulations shall be known as the “Historical Code” and may be so cited, and will be referred to herein as “this Chapter.” This Code is one (1) of the technical codes of building regulations and is administered under Title 9, Chapter 1 of the Hercules Municipal Code.

Sec. 9-12.02 Adoption by Reference.

The California Historical Building Code, 2022 Edition, (California Code of Regulations, Title 24, Part 8) including appendices, as published by the International Code Council as modified by the State of California is adopted by reference and made a part of this Chapter as though fully set forth herein, subject to the additions and deletions set forth in this Chapter.

Sec. 9-12.03 Copies on File.

One (1) copy of the 2022 California Historical Building Code, including appendices, as adopted by Section HYPERLINK "https://www.codepublishing.com/CA/Hercules/" \l "!/Hercules09/Hercules0912.html#9-12.02" 9-12.02 is on file in the office of the Chief Building Official for inspection by the public.

SECTION 14. AMENDMENTS TO EXISTING BUILDING CODE. Hercules Municipal Code, Title 9, Chapter 13 is hereby repealed and replaced in its entirety to read as set forth below.

Sec. 9-13.01 Administration.

These regulations shall be known as the “Existing Building Code” and may be so cited, and will be referred to herein as “this Chapter.” This Code is one (1) of the technical codes of building regulations and is administered under Title 9, Chapter 1 of the Hercules Municipal Code Sec. 9-13.02 Adoption by Reference.

The California Existing Building Code (“CEBC”), 2022 Edition, (California Code of Regulations, Title 24, Part 10) including appendices, as published by the International Code Council as modified by the State of California and is adopted by reference and made a part of this Chapter as though fully set forth herein, subject to the changes, additions and deletions set forth in this Chapter.

Sec. 9-13.03 Copies on File.

One (1) copy of the 2022 California Existing Building Code, including appendices, as adopted by Section HYPERLINK "https://www.codepublishing.com/CA/Hercules/" \l "!/Hercules09/Hercules0913.html#9-13.02" 9-13.02 is on file in the office of the Chief Building Official for inspection by the public.

Sec. 9-13.04 Amendments, Additions, and Deletions. The following portion of the Ordinance Code of Contra Costa County, California, is adopted by reference under the authority of Sections 50020 through 50022.9 of the California Government Code:

Adopting the amendments to the California Existing Building Code ("CEBC") by the changes, additions, and deletions set forth below as set forth in the Contra Costa County Ordinance No. 2022-35, Chapter 74-4, “Amendments to CEBC” Section 74-4.008 with Section numbers used below being those of the 2022 California Existing Building Code.

CEBC Chapter 1 (Scope and Administration) is amended by the provisions of Division 72 of this code and as follows:

Sections 103 and 112 of CEBC Chapter 1 are deleted.

Section 106.1 (Construction Documents - General) of CEBC Chapter 1 is amended by deleting the exception.

Section 106.2.1 (Construction documents) of CEBC Chapter 1 is amended to read:
106.2.1 Construction documents. Construction documents shall include dimensions and shall be drawn to scale on suitable material. Electronic media documents may be submitted when approved in advance by the building official. Construction documents shall be of sufficient clarity to indicate the location, nature, and extent of the work proposed and to show in detail that it will conform to this code and all relevant laws, ordinances, rules, and regulations. The first sheet of each set of plans shall include contact information for the owner and the person or persons who prepared the plans. Plans shall include a plot plan showing all existing property lines labeled and fully dimensioned, the elevations of the top and toe of cuts and fills, and the location of the proposed building with distances to all property lines and to every existing building on the property. Instead of detailed specifications, the county building official may approve references on the plans to a specific section or part of this code or other ordinances or laws.

SECTION 15. AMENDMENTS TO REFERENCED STANDARDS CODE. Hercules Municipal Code, Title 9, Chapter 14, Sections 9-14.01, 9-14.02 and 9-14.03 are hereby repealed and replaced in their entirety to read as set forth below.

Sec. 9-14.01 Administration.

These regulations shall be known as the “Referenced Standards Code,” and may be so cited, and will be referred to herein as “this Chapter.” This Code is one (1) of the technical codes of building regulations and is administered under Title 9, Chapter 1 of the Hercules Municipal Code.

Sec. 9-14.02 Adoption by Reference.

The California Referenced Standards Code, 2022 Edition (California Code of Regulations, Title 24, Part 12) including appendices, as published by the International Code Council, as modified by the State of California is adopted by reference and made a part of this Chapter as though fully set forth herein, subject to the additions and deletions as set forth in this Chapter.

Sec. 9-14.03 Copies on File.

One (1) copy of the 2022 Edition of the California Referenced Standards Code, as adopted by Section HYPERLINK "https://www.codepublishing.com/CA/Hercules/" \l "!/Hercules09/Hercules0914.html#9-14.02" 9-14.02, is on file in the office of the Chief Building Official for inspection by the public.

SECTION 161. AMENDMENTS TO FIRE CODE. Title 9, Chapter 15 of the City of Hercules Municipal Code is appealed and replaced in its entirety to read:

Sec. 9-15.01 Administration.

These regulations shall be known as the “2022 California Fire Code” and may be so cited, and will be referred to herein as “this Chapter.” This Code is one (1) of the technical codes of building regulations and is administered under Title 9, Chapter 1 of the Hercules Municipal Code.

Sec. 9-15.02 Adoption by Reference.

The 2022 California Fire Code, ((California Code of Regulations, Title 24, Part, 9 [based on the 2021 International Fire Code published by the International Code Council]), including appendices, as published by the International Code Council, as modified by the State of California and is adopted by reference and made a part of this Chapter as though fully set forth herein, subject to the additions and deletions as set forth in this Chapter.

Sec. 9-15.03 Copies on File.

One (1) copy of the 2022 California Fire Code, as adopted by Section 9-15.02, is on file in the office of the Chief Building Official for inspection by the public.

Sec. 9-15.04 Amendments, Additions, and Deletions.

The following portion of the Ordinance Code of Rodeo-Hercules Fire District, California, is adopted by reference under the authority of Sections 50020 through 50022.9 of the California Government Code:

Amending the 2022 California Fire Code by the changes, additions, and deletions set forth below as set forth as set in the Rodeo-Hercules Fire District Ordinance No. 2022-01. Chapter and Section numbers used below are those of the 2022 California Fire Code.

Chapter 1. Scope and Administration.

Section 101.1 is amended to read:
101.1 Title. These regulations shall be known as the Fire Code of the Rodeo-Hercules Fire Protection District, hereinafter referred to as "this code." Section 102.1 is amended to add item 5, to read:

5. Where not otherwise limited by law, the provisions of this code shall apply to vehicles, ships, and boats that are permanently affixed to a specific location within the boundaries of this jurisdiction.

Section 105.5 is amended to read:
105.5 Required operational permits. The fire code official is authorized to issue operational permits for the operations set forth in Chapter 1, Sections 105.5.1 through 105.5.63.

Section 105.5.33 is amended to read:
105.5.33 Motor Fuel Dispensing Facilities. An operational permit is required for the operation of automotive, marine, and fleet motor fuel dispensing facilities, including for sites that allow mobile fueling from a service provider to the general public , fueling of motor vehicles at approved locations from a tank vehicle and limited or temporary fueling operations for special events (fueling of watercraft from shore, piers, floats, or barges).

Section 105.5.40 is amended to read:

Section 105.5.40 Cannabis/Plant Extraction Related System(s)/Operations. An operational permit is required for any of the following cannabis/plant extraction related systems operations.

Cultivation
Plant Extraction Systems
Testing/Lab
Manufacturing
Distribution
Carbon Dioxide Systems or volatile solvent Section
105.5.52 is amended to read:
105.5.52 Wood products. An operational permit is required to store chips, hogged material, wood or other combustible pallets, lumber or plywood in excess of 200 cubic feet (6 m3).

Section 105.5 is amended by adding Subsections 105.5.55 through 105.5.63 to read:
105.5.55 Asbestos removal. A permit is required to conduct asbestos-removal operations regulated by Section 3319 105.5.56 Automobile Wrecking or Dismantling Yard. An operation permit is, required for all automobile wrecking yards, automobile dismantling operations, and similar operations. 105.5.57 Christmas tree sales. A permit is required to use a property for the purpose of selling cut Christmas trees 105.5.58 Firework aerial display. A permit is required to conduct a firework display regulated by California Code of Regulations, Title 19 and Chapter 56 of this code 105.5.59 Model rockets. A permit is required to sell model rocket motors or launch model rockets pursuant to California Code of Regulations, Title 19, Division 1, Article 17. Permits issued in accordance with this section are for the site and are effective as long as site conditions have not changed. 105.5.60 Temporary Occupancy. A permit is required for any temporary occupancy. 105.5.61 Temporary water supply. A permit is required to use a temporary water supply for construction of residential projects or subdivisions pursuant to Section 3313.1. 105.5.62 Tire storage. A permit is required to store more than 1,000 cubic feet (28.3m3) of tires inside buildings pursuant to Chapter 34. 105.5.63 Indoor Growing Operation. A permit is required to operate an indoor growing operation.

Exception: Agricultural Greenhouses in an agricultural zone.

Section 105.6 is amended to read:
105.6 Required construction permits. The fire code official is authorized to issue construction permits for the operations set forth in Chapter 1, Sections 105.6.1 through 105.6.29.

Section 105.6 is amended by adding Sections 105.6.25 through 105.6.29 to read:
105.6.25 Access for fire apparatus. Plans shall be submitted and a permit is required to install, improve, modify, or remove public or private roadways, driveways, and bridges for which Fire District access is required by the Fire Code. 105.6.26 Construction, Substantial Alteration, Additions of a building for which a building permit is required. Plans shall be submitted to the fire code official for all land developments or for the construction, substantial alteration, additions or renovation of a building within the jurisdiction where a building permit is required.

Exception: Non-sprinklered Group R-3 Occupancies where work does not involve a substantial addition or substantial alteration. 105.6.27 Land Development, Subdivisions. Plans shall be submitted to the fire code official for all land developments or improvements proposed within the jurisdiction that involve the subdivision of land. 105.6.28 Water supply for fire protection. Plans shall be submitted to the fire code official for the purpose of determining whether adequate water supplies, fire hydrants, and associated systems are provided for all facilities, buildings, or portions of buildings either constructed or moved into the District pursuant to Section 507. 105.6.29 Land Development, Subdivisions. Plans shall be submitted to the fire code official for all land developments or improvements proposed within the jurisdiction that involve the subdivision of land.

Section 105.7 is added, to read:
105.7 Responsibility of permitee. Construction permits shall be presumed by the Fire District to incorporate all the work that the applicant or the applicant's agent, employees, or contractors shall carry out. Work performed shall be in accordance with the approved plans and with all requirements of this code and any other laws or regulations applicable thereto. No Fire District approval shall relieve or exonerate any person from the responsibility of complying with the provisions of this code nor shall any vested rights be created for any work performed in violation of this code.

Section 112.4 is amended to read:
112.4 Violation penalties. Every person who violates any provision of this fire code is guilty of an infraction or misdemeanor in accordance with Health and Safety Code Section 13871 and Government Code Section 53069.4. The imposition of one penalty for any violation shall not excuse the violation or permit it to continue; and all such persons shall be required to correct or remedy such violations or defects within a reasonable time; and when not otherwise specified, each ten (10) days that prohibited conditions are maintained shall constitute a separate offense. The application of the aforesaid penalty shall not be held to prevent the enforced removal of prohibited conditions.

Chapter 2. Definitions.

Section 202 is amended by adding the following definitions to that section:

Administrator. Shall mean the Fire Chief.

Aerial Pre-Plans. An overhead layout of a parcel that contains structure(s) that identifies specific first responder related items to assist in effectively managing incidents and events for the protection of occupants, responding personnel, property, and the environment. The preplan shall be developed in accordance with a format approved by the AHJ. Preplan symbols shall comply with AHJ or the latest edition of NFPA 170 (Standard for Fire Safety and Emergency Symbols), and NFPA 1620 (Standard for Pre-Incident Planning).

All-Weather Driving Surface. A roadway with a minimum surface finish that is designed to carry the imposed weight loads of fire apparatus.

Automobile Dismantling or Wrecking Yard. The operation of dismantling or removing parts from salvaged vehicles including engines or engine parts.

Automobile Wrecking Yard. An area that stores or dismantles salvaged vehicles.

Board of Directors. The Rodeo-Hercules Fire Protection District.

Board of Fire Commissioners. An advisory commission appointed by the Board of Directors to act as set forth in this ordinance and by resolutions of the Board of Directors.

Combustible Material. Rubbish, litter or material of any kind other than hazardous vegetation that is combustible and endangers the public safety by creating a fire hazard as determined by the fire code official.

Defensible Space. The area adjacent to a structure or dwelling as determined by the fire code official where wildfire prevention or protection practices are implemented to provide the key point of defense from an approaching wildfire or to minimize the spread of a structure fire to wildlands or surrounding areas.

Driveway. A private roadway that provides access to no more than two (2) single-family dwellings.

Fire Apparatus Access Road. A road that provides fire apparatus access from a fire station to a facility, building or portion thereof. This is a general term that includes, but is not limited to a fire lane, public street, private street, driveway, parking lot lane, and access roadway.

Fire Code Official. The Fire Chief or a duly authorized representative, or other person as may be designated by law, appointment or delegation and charged with the administration and enforcement of this code.

Firebreak. A continuous strip of land upon and from which all combustible material hazardous vegetation or other growth has been removed to bare mineral soil to stop or prevent the extension of fire from one area to another.

Fire Trail. A graded firebreak of sufficient width, surface, and design to provide access for personnel and equipment to suppress and to assist in preventing a surface extension of fires. Must be able to support the safe travel of a Type 3 Fire Apparatus.

Fuel Break. A strategically located block or strip, on which a cover of dense, heavy, or combustible vegetation has been changed to one of lower fuel volume or reduced combustibility, as an aid to fire control. Fuel breaks require annual and recurring maintenance.

Hazardous Vegetation. Vegetation that is combustible and endangers the public safety by creating a fire hazard including but not limited to seasonal and recurrent grasses, weeds, stubble, brush, dry leaves, dry needles, dead, dying or diseased trees and any other vegetation as determined by the fire code official.

Key Box or Knox Box. (Underwriters Laboratory) UL "Listed" box size and style, approved by the Fire Code Official or designee, that meets the requirements and uses the same security key code adopted by the Fire District.

Ladder Fuel. Fuel that provides vertical continuity between surface fuel and canopy fuel strata, increasing the likelihood that fire will carry from surface fuel into the crowns of shrubs and trees.

Nuisance Fire Alarm. The activation of any fire protection or alarm system which results in the response of the Fire District and is caused by malfunction, improper maintenance, negligence, or misuse of the system by an owner, occupant, employee, or agent, or any other activation not caused by excessive heat, smoke, fire, or similar activating event.

Ornamental Landscaping. Decorative plants growing within a tended garden or yard which are appropriately irrigated, maintained, and located to provide aesthetic decoration and functional utility, such as privacy screening, shade, weed suppression and erosion control. The use of fire- resistant plants and the removal of fire hazardous vegetation will enhance fire safety.

Person. Includes any agency of the county, city, district or other local public agency and any individual, firm, association, partnership, business trust, corporations, limited liability company, or company.

Public Nuisance. A declaration by the fire code official that the presence of combustible materials on any parcel creates a fire hazard or threat to public safety (Health and Safety Code 14875 and 14876) or any violation of this code.

Priority Hazard Zone. An area where the threat from wildfire is severe due to proximity to open space, topography, degree of space, density of homes and/or amount of vegetation (native and ornamental), and/or other conditions favorable to fast moving fires.

Response Time. The elapsed time from receipt of call to the arrival of the first unit on scene.

Rubbish. Waste matter, litter, trash, refuse, debris, and dirt on streets or private property in the jurisdiction which is, or when dry may become, a fire hazard. See combustible material.

Rural Area. An area generally designated for agricultural or open space uses with parcels more than 10 acres (4.046873ha) in size.

Rural Residential Area. An area generally designated for single family residential use with parcels between three (1.2140619 ha) and 10 (4.046873 ha) acres in size.

Sprinkler Alarm and Supervisory System (SASS). A Dedicated Function Fire Alarm System located at the protected premise installed specifically to monitor sprinkler water- flow alarm, valve supervisory, and general trouble conditions where a Building Fire Alarm is not required.

Streets. Includes alleys, parkways, driveways, sidewalks, and areas between sidewalks and curbs, highways, public rights of way, private road, paper street and easements.

Substantial Addition. The addition of new gross floor area exceeds fifty percent of the existing gross floor area and the total new gross floor area is 5,000 square feet or greater. (CCFPD, SRVFPD, RHFPD,) Substantial Alteration. Where fifty percent or greater of the linear length of the wall of the building (exterior and interior) and fifty percent of the roof are removed or replaced within a one-year period.

Temporary Fire Department Access Road for Construction. An approved temporary roadway for emergency vehicle use during construction of residential subdivision projects.

Temporary Fire Department Access Road for Construction Of One (1) Residential (R3) Unit. A temporary roadway for emergency vehicle use during construction of an individual residential (R3) structure where a fire department access road is required as part of the project.

Temporary Water Supply. Water stored for firefighting purposes in an approved aboveground tank during combustible construction.

Tree Litter. Any limbs, bark, branches, and/or leaves in contact with other vegetation or left to gather on the ground.

Weeds. All weeds growing upon streets or private property in the jurisdiction, including any of the following:

Weeds that bear seeds of a fluffy nature or are subject to flight.

Sagebrush, chaparral (including Chamise, Coyote Brush/Greasewood, Brooms, and Buckwheat), and any other brush or weeds that attain such large growth as to become, when dry, a fire menace to adjacent improved property.

Weeds that are otherwise noxious or dangerous;
Poison oak and poison sumac when the conditions of growth constitute a menace to public health.

Dry grass, brush, tree litter, litter, or other flammable materials that endanger the public safety by creating a fire hazard.

Chapter 3. General Requirements.

Section 304.3.5 is added, to read:
304.3.5 Clothes Dryers. Clothes dryers shall be frequently cleaned to maintain the lint trap, mechanical and heating components, vent duct, and associated equipment free from accumulations of lint and combustible materials.

Section 308.1.4, Exception 1 is amended to read:

Exception 1. Residential Occupancies.

Section 324 is added to Chapter 3, to read:

SECTION 324 Exterior Fire Hazard Control.
324.1 Subsurface Fires.
324.1.1 Peat Fire. It is the duty of each person, firm, corporation, or association not to permit a peat fire or a fire involving combustible vegetable matters under the surface of the natural ground to remain upon the property. It is hereby declared that it is the duty of any person as herein defined to take all necessary precautions to extinguish any subsurface fire involving peat or vegetable material at the owner’s own cost and expense. 324.1.2 Fire Suppression Costs. If there exists upon the lands or property of any person as herein defined a subsurface fire involving the burning or combustion of peat, vegetable matter, or vegetation, and the owner or occupant thereof has not taken reasonable precautions within a reasonable time to extinguish or minimize such fire or combustion, the Fire District may, in addition to its regular duties to extinguish or minimize such fire or combustion, go upon the lands of any person as herein defined and extinguish such fire or combustion. Any costs incurred by the Fire District in fighting the fire and for the cost of proving rescue or emergency medical services shall be a charge against the property owner. The charge shall constitute a debt of the property owner and is collectable by the jurisdiction incurring those costs in the same manner as in the case of an obligation under a contract, express or implied. (See Health and Safety Code, §13009.)
Section 325 is added to Chapter 3, to read:

SECTION 325 Automobile Wrecking Yards.
325.1 General. The operation of automobile wrecking yards shall be in accordance with this section. 325.2 Definitions. The following terms are defined in Chapter 2:

Automobile Dismantling
Automobile Wrecking Yard
325.3 Requirements.
325.3.1 Permits. An operational fire code permit is required as in Section 105.6.53. 325.3.2 Fire Apparatus Access Roads. Fire apparatus access roads shall be constructed throughout the site in accordance with this code and shall be maintained clear of all vehicles and stored items. 325.3.3 Welding and cutting. Welding and cutting operations shall be conducted in an approved location, clear of all flammable liquids and combustible materials, including weeds, tires, and all other debris. 325.3.4 Housekeeping. Combustible rubbish accumulated on site shall be collected and stored in approved containers, rooms, or vaults of noncombustible materials. Combustible vegetation, cut or uncut, shall be removed when determined by the fire code official to be a fire hazard. 325.3.5 Fire Protection. Offices, storage buildings, and vehicles used for site operations shall each be provided with at least one portable fire extinguisher with not less than a 4-A: 40-B-C rating. When required by the fire code official, additional fire extinguishers shall be provided. 325.3.6 Tire storage. Tires shall be stored in racks or in a manner as approved by the fire code official. 325.3.6.1 Distance from Water Supply. Tire storage shall be located on-site and no further than 500 feet from a fire hydrant or an approved water supply as determined by the fire code official. 325.3.7 Storage Piles. Storage piles shall be located a minimum of 20 feet from property lines and shall have an unobstructed access road on all sides of not less than 20 feet. 325.3.8 Burning operations. The burning of salvaged vehicles and salvaged or waste materials is prohibited. 325.3.9 Motor vehicle fluids. Motor vehicle fluid shall be drained from salvaged vehicles when such liquids are leaking onto the ground and prior to dismantling or removing engine/motor parts. 325.3.9.1 Mitigation of leaking fluids. Precautions shall be taken to prevent fluids from salvaged vehicles from leaking onto the ground. Supplies or equipment capable of mitigating leaks from fuel tanks, crankcases, brake systems, and transmissions shall be kept available on site. Single-use plugs, diking, and absorbent materials shall be disposed of as hazardous waste and removed from the site in a manner in accordance with federal, state, and local requirements. 325.3.10 Fuel tanks. Fuel tanks of salvaged vehicles shall be emptied of all flammable (gasoline, diesel) fuels in an approved manner and stored in approved tanks. 325.3.10.1 Repair of vehicle fuel tanks. The repair of fuel tanks, including cutting, welding, or drilling of any kind, is prohibited. 325.3.11 Lead acid batteries. Lead acid batteries shall be removed from all salvaged vehicles and stored in an approved manner in a location approved by the fire code official.

Chapter 4. Emergency Planning and Preparedness.

Section 401.5.1 is added to read:
401.5.1 Nuisance Fire Alarm. A fee may be charged for false and/or nuisance fire alarms in accordance with the fee schedule adopted by the Board of Directors.

Section 401.10 is added to read:
401.10 Aerial Pre-Plans. For all new construction the fire official is authorized to require a fire aerial pre-plan to be prepared by an approved vendor at the cost of the developer.

Section 403.11.1 is amended to read:
403.11.1 Standby Personnel. Where, in the opinion of the fire code official or Fire Chief, it is essential for public safety in a place of assembly, or any other place where people congregate, because of the number of persons, or the nature of the performance, exhibition, display, contest, or activity, the owner, agent, or lessee shall provide standby personnel as required and approved by the fire code official or Fire Chief. If the activity requires fire watch, fire watch shall be provided in accordance with Sections 403.11.1.1 and 403.11.1.2. Standby personnel needed for EMS standby shall be provided in accordance with Contra Costa County EMS Protocols.

Chapter 5. Fire Service Features.

Section 503.1.4 is added to read:
503.1.4 Access to open spaces. When access to open land/space or fire trail systems maintained for public or private use is obstructed by new development of any kind, the developer shall provide alternate acceptable access into the area that is sufficient to allow access for fire personnel and apparatus. The alternate means of access requires the approval of the fire code official.

Section 503.1.5 is added to read:
503.1.5 Existing fire trail systems shall be maintained. When conditions make maintenance of existing trails impractical, alternate means of access shall be provided and requires approval by fire code official.

Section 503.2.1 is amended by adding the following exception:

Exception: A driveway with a minimum width of 16 feet is acceptable for access to one or two single- family dwellings.

Section 505.3 is added, to read:
505.3 Street names and addressing. Street names and addressing shall be submitted for review and approval to the fire code official, whose approval will not be unreasonably withheld. The purpose of the review is to verify that new street names and addressing will not duplicate existing street names and addressing.

Chapter 6. Building Services and Systems.

Section 605.3.1 is added to read:
605.3.1 Spark Arrestors. All Chimneys attached to any appliance or fireplace that burns solid fuel shall be equipped with an approved spark arrestor per CBC 2113.9.2.

Chapter 9. Fire Protection and Life Safety Systems.

Section 901.6.3 is amended to read:
901.6.3 Records. Records of all system inspections, tests, and maintenance required by the reference standards shall be submitted to a third party electronic record keeping service as chosen by the fire district.

Section 902.1 is amended to add:

SUBSTANTIAL ADDITION. The addition of new gross floor area exceeds fifty percent of the existing gross floor area and the total new gross floor area is 5,000 square feet or greater.

SUBSTANTIAL ALTERATION. Where fifty percent or greater of the linear length of the wall of the building (exterior and interior) and fifty percent of the roof are removed or replaced within a one-year period.

Section 903.2.1.1 is amended to read:
903.2.1.1 Group A-1. An automatic sprinkler system shall be provided throughout stories containing Group A-1 occupancies and throughout all stories from the Group A-1 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists:

The fire area exceeds 5,000 square feet.

The fire area has an occupant load of 300 or more.

The fire area is located on a floor other than a level of exit discharge serving such occupancies.

The fire area contains a multi-theater complex.

Section 903.2.1.3 is amended to read:
903.2.1.3 Group A-3. An automatic sprinkler system shall be provided throughout stories containing Group A-3 occupancies and throughout all stories from the Group A-3 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists:

The fire area exceeds 5,000 square feet.

The fire area has an occupant load of 300 or more.

The fire area is located on a floor other than a level of exit discharge serving such occupancies.

The structure exceeds 10,000 square feet, contains more than one fire area containing exhibition and display rooms, and is separated into two or more buildings by fire walls of less than 4-hour fire resistance rating without openings.

Section 903.2.1.4 is amended to read:
903.2.1.4 Group A-4. An automatic sprinkler system shall be provided throughout stories containing Group A-4 occupancies and throughout all stories from the Group A-4 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists:

The fire area exceeds 5,000 square feet
The fire area has an occupant load of 300 or more.

The fire area is located on a floor other than a level of exit discharge serving such occupancies.

Section 903.2.2 is amended in its entirety, to read:

Section 903.2.2 Group B. An automatic sprinkler system shall be provided for Group B occupancies and intervening floors of the building where the fire area exceeds 5,000 square feet.

Section 903.2.2.1 Ambulatory care facilities. An automatic sprinkler system shall be installed throughout the entire floor containing an ambulatory care facility where either of the following conditions exist at any time:

Four or more care recipients are incapable of self-preservation.

One or more care recipients that are incapable of self-preservation are located at other than the level of exit discharge serving such a facility.

In buildings where ambulatory care is provided on levels other than the level of exit discharge, an automatic sprinkler system shall be installed throughout the entire floor as well as all floors below where such care is provided, and all floors between the level of ambulatory care and the nearest level of exit discharge, the level of exit discharge, and all floors below the level of exit discharge.

Exception: Floors classified as an open parking garage are not required to be sprinklered.

Section 903.2.3 is amended to read:
903.2.3 Group E. An automatic sprinkler system shall be provided for new Group E occupancies as follows:

Throughout all Group E fire areas greater than 2,000 square feet in area.

Exception: An automatic sprinkler system is not required in any Group E Day Care Facility less than 5,000 square feet.

The Group E fire area is located on a floor other than a level of exit discharge serving such occupancies.

Exception: In buildings where every classroom has not fewer than one exterior exit door at ground level, an automatic sprinkler system is not required in any area below the lowest level of exit discharge serving that area.

The Group E fire area has an occupant load of 300 or more.

In rooms or areas with special hazards such as laboratories, vocational shops, and. other such areas where hazardous materials in quantities not exceeding the maximum allowable quantity are used or stored.

Throughout any Group E structure greater than 4,000 square feet in area, which contains more than one fire area, and which is separated into two or more buildings by fire walls of less than 4•hour fire resistance rating without openings.

For public school state-funded construction projects, see Section 903.2.19.

For public school campuses, Kindergarten through 12th grade, see Section 903.2.20.

Section 903.2.4. is amended in its entirety, to read:
903.2.4 Group F-1. An automatic sprinkler system shall be provided throughout all buildings containing a Group F-1 occupancy where one of the following conditions exists:

A Group F-1 fire area exceeds 5,000 square feet.

A Group F-1 fire area is located more than three stories above grade plane.

The combined area of all Group F-1 fire areas on all floors, including any mezzanines, exceeds 10,000 square feet.

A Group F-1 occupancy used for the manufacture of upholstered furniture or mattresses exceeding 2,500 square feet (232 m2) .

Section 903.2.4.4 is added to read:
903.2.4.4 Group F-2. An automatic sprinkler system shall be provided throughout all buildings containing a Group F-2 occupancy greater than 5,000 square feet.

Section 903.2.7 is amended to read
903.2.7 Group M. An automatic sprinkler system shall be provided throughout buildings containing a Group M occupancy where one of the following conditions exists:

A Group M fire area exceeds 5,000 square feet.

A Group M fire area is located more than three stories above grade plane.

The combined area of all Group M fire areas on all floors, including any mezzanines, exceeds 10,000 square feet.

A Group M occupancy (is) used for the display and sale of upholstered furniture or mattresses exceeds 5,000 square feet.

The structure exceeds 10,000 square feet, contains more than one fire area containing a Group M occupancy, and is separated into two or more buildings by fire walls of less than 4-hour fire•resistance rating without openings.

Section 903.2.8 is amended to read:
903.2.8 Group R. An automatic sprinkler system installed in accordance with Section 903.3 shall be provided throughout all Group R occupancies. An automatic sprinkler system shall be installed in new manufactured homes, new mobile homes, and multifamily manufactured homes with two dwelling units, including those located in mobile home parks, in accordance with Title 25 of the California Code of Regulations.

Section 903.2.8.1.1 is added, to read:
903.2.8.1.1 Group R-3 Substantial Addition or Alteration. An automatic sprinkler system shall be provided throughout all existing Group R-3 dwellings where either of the following occurs:

Substantial Addition. The addition of new gross floor area exceeds fifty percent of the existing gross floor area and the total new gross floor area is 3,600 square feet or greater.

Substantial Alteration. Where fifty percent or greater of the linear length of the wall of the building (exterior and interior) and fifty percent of the roof are removed or replaced within a one- year period.

Section 903.2.9 is amended to read:
903.2.9 Group S-1. An automatic sprinkler system shall be provided throughout all buildings containing a Group S-1 occupancy where one of the following conditions exists:

A Group S-1 fire area exceeds 5,000 square feet.

A Group S-1 fire area is located more than three stories above grade plane.

The combined area of all Group S-1 fire areas on all floors, including any mezzanines, exceeds 10,000 square feet.

A Group S-1 occupancy used for the storage of commercial motor vehicles where the fire area exceeds 5,000 square feet.

Section 903.2.9.1 is amended to read:
903.2.9.1 Repair garages. An automatic sprinkler system shall be provided throughout all buildings used as repair garages in accordance with Section 406.8 of the California Building Code, as shown:

Buildings having two or more stories above grade plane, including basements, with a fire area containing a repair garage exceeding 5,000 square feet.

Buildings not more than one story above grade plane, with a fire area containing a repair garage exceeding 5,000 square feet.

Buildings with repair garages servicing vehicles parked in basements.

A Group S-1 fire area used for the repair of commercial motor vehicles where the fire area exceeds 5,000 square feet or any tenant improvement to the structure exceeds 49% of the S- 1 area.

Section 903.2.10 is amended to read:
903.2.10 Group S-2 parking garages. An automatic sprinkler system shall be provided throughout buildings classified as parking garages where any of the following conditions exists:

Where the fire area of the enclosed parking garage, in accordance with Section 406.6 of the California Building Code, exceeds 5,000 square feet.

Where the enclosed parking garage, in accordance with Section 406.6 of the California Building Code, is located beneath other groups.

Exception: Enclosed parking garages located beneath Group R-3 occupancies.

Where the fire area of the open parking garage, in accordance with Section 406.5 of the California Building Code, exceeds 48,000 square feet.

Section 903.2.10.3 is added to read:
903.2.10.3 Group S-2 low hazard storage. An automatic sprinkler system shall be provided throughout all buildings containing a Group S-2 occupancy exceeding 5,000 square feet.

Section 903.2.11.7 is added to read:
903.2.11.7 High-piled storage. An automatic sprinkler system shall be provided throughout buildings containing high-pile combustible storage.

Exception: An automatic sprinkler system is not required for 500 square feet or less, including aisles, of high-piled storage.

Section 903.2.22 is added, to read:

Section 903.2.22 Fire department delivery capability. An automatic fire sprinkler shall be installed in all new buildings and occupancies or in existing buildings or structures that change occupancy classification or use, when the required fire flow exceeds 2,000 gallons per minute Section 903.3.1.1.4 is added, to read:
903.3.1.1.4 Undeclared Use. In buildings of undeclared use with floor to structure height greater than 14 feet, the fire sprinkler system shall be designed to conform to Extra Hazard Group I design density. In buildings of undeclared use with floor to structure height less than .14 feet, the fire sprinkler system shall be designed to conform to Ordinary Group II design density. Where a subsequent occupancy requires a system with greater capability, it shall be the responsibility of the owner and/or the occupant to upgrade the system.

Section 903.3.1.3.1 is added to read:
903.3.1.3.1 Pipe limitations. Where CPVC pipe is installed above the insulation or is otherwise located in an unconditioned space, such as in an attic space, or a garage without conditioned living space above, CPVC pipe shall be adequately insulated to a minimum R-19 value, or equivalent, or pipe shall be limited to Type K or L copper, or ferrous piping.

Section 903.3.5.3 is added, to read:
903.3.5.3 Non-permissible water supply storage. Swimming pools and ponds shall not be considered water storage for the purposes of Section 903.3.5.

Section 903.3.9 is amended to read:
903.3.9. Floor control valves. Individual floor control valves and water flow detection assemblies shall be provided for each floor in multi-floor buildings at an approved location.

Exception: Group R-3 and R-3.1 Occupancies.

Section 903.4.2 is amended to read:
903.4.2 Alarms. One approved audible and visual device shall be connected to every automatic sprinkler system at an approved location. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Audible and visual alarm devices shall be provided on the exterior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system.

Section 903.6.1 is added, to read:
903.6.1 Substantial addition or expansion. An automatic sprinkler system shall be provided throughout all existing R-3 Occupancy buildings where a substantial addition occurs and the total new gross floor area of the structure exceeds 5,000 square feet. Group R-3 substantial additions or alterations shall comply with Section 903.2.8.1.1.

Section 903.6.2 is added, to read:
903.6.2 Change of occupancy classification. Any existing building that undergoes a change of occupancy classification into a higher hazard category shall comply with the requirements of Section 903.2. Relative hazard categories of occupancy groups shall be established based upon the Heights and Areas Hazard Categories of Table 1011.5 of the current edition of the International Existing Building Code, as published by the International Code Council. The requirements of Section 903.2 shall not be required when a change of occupancy classification is made to an equal or lesser hazard category. Group L occupancies shall be considered a relative hazard of 1 (highest hazard).

Section 907.4.4 is added, to read:
907.4.4 Monitoring of other fire systems. In buildings equipped with a fire alarm system or sprinkler alarm and supervisory service (SASS) system, where other fire suppression or extinguishing systems are installed in the building (including, but not limited to commercial kitchen suppression systems, pre-action fire suppression systems, dry chemical systems, and clean agent systems), these other suppression systems shall be monitored by the SASS dedicated function fire alarm system and transmitted as a specific signal to the Central Station. The system shall be monitored in compliance with Section 907.6.6.

Section 907.5.2.3.1 is amended to read:
907.5.2.3.1 Public and common areas. Visible alarm notification appliances shall be provided in public use areas and common use areas, including but not limited to:

Sanitary facilities including restrooms, bathrooms, shower rooms, and locker rooms.

Corridors, hallways, and aisles with shelving and/or fixtures obstructing the required light intensity for that area.

Music practice rooms.

Band rooms.

Gymnasiums.

Multipurpose rooms.

Occupational shops.

Occupied rooms where ambient noise impairs hearing of the fire alarm.

Lobbies.

Meeting/Conference rooms.

Classrooms.

Medical exam rooms.

Open office areas.

Sales floor areas.

Break or lunch rooms
Copy or work rooms.

Computer server rooms exceeding 200 sq. ft.

File or Storage rooms exceeding 200 sq. ft.

Section 907.6.6 is amended to read:
907.6.6 Monitoring of fire alarm systems. A fire alarm system required by this chapter, or by the California Building Code, shall be monitored by a UL-listed Central Station service in accordance with NFPA 72 and this code.

Exception: Monitoring by a UL-listed central station is not required for:

Single- and multiple-station smoke alarms required by Section 907.2.10.

Group 1-3 occupancies shall be monitored in accordance with Section 907.2.6.3.

Residential Day Care Facilities (occupancy load of 14 or less).

One- and two-family dwellings.

Residential Care Facilities licensed by the state with an occupant load of 6 or less.

Occupancies with local fire alarm system that will give an audible and visible signal at a constantly attended location, as approved by the Fire Code Official.

Section 907.6.7 is added, to read:
907.6.7 Certification. New fire alarm systems shall be UL-Certified. A Certificate of Completion and other documentation as listed in NFPA 72 shall be provided for all new fire alarm system installations. It is the responsibility of the building owner or owner's representative to obtain and maintain a current and valid Certificate.

Section 907.6.7.1 is added, to read:
907.6.7.1 Posting of Certificate. The UL Certificate shall be posted in a durable transparent cover within three feet of the fire alarm control panel within 45 days of the final acceptance test/inspection.

Chapter 10. Means of Egress.

Section 1028.5.1 is added, to read:
1028.5.1 Exit discharge surface. Exterior exit pathway surfaces shall be suitable for pedestrian use in inclement weather, and shall terminate at a public way as defined in the California Building Code.

Chapter 33. Fire Safety During Construction and Demolition.

Section 3303.1.2 is added to read:

Amendments. Amendments may be required to an approved site safety plan if deemed necessary by both the building official and fire official, based on previous fires or hazards that occurred on site or within the jurisdiction.

Section 3303.1.3 is added to read:

Site Security requirements. Site security requirements hall include the following if deemed necessary by both the building official and fire official:

Controlled access points
Site fencing, up to 12 feet in height with tamper sensors and security wires on top Security guards, full-time 24/7 presence on-site, to perform fire watch and patrols Detection check points located throughout the buildings for fire watch and patrol verification Security camera coverage throughout the site with motion detection notifications Identify measures taken to prevent tampering with security cameras and motion sensors Necessary lighting throughout the project site
Section 3319 Asbestos Removal is added to read as follows:

General. Operations involving removal of asbestos or asbestos-containing materials from buildings shall be in accordance with Section 3319.

Exception: Section 3319 does not apply to the removal of asbestos from:

Pumps, valves, gaskets, and similar equipment.

Pipes, ducts, girders, or beams that have a length less than 21 linear feet (6400 mm).

Wall or ceiling panels that have an area of less than 10 square feet (0.93 m2) or a dimension of less than 10 linear feet (3048 mm).

Floor tiles when their removal can be completed in less than four hours.

Group R-3 occupancies.

Notification. The fire code official shall be notified 24 hours prior to the commencement and closure of asbestos-removal operations. The permit applicant shall notify the building official when asbestos abatement involves the removal of materials that were used as a feature of the building's fire resistance.

Plastic Film. Plastic film that is installed on building elements shall be flame resistant as required for combustible decorative material, in accordance with Section 807.

Signs. Approved signs shall be posted at the entrance, exit and exit-access door, decontamination areas and waste disposal areas for asbestos-removal operations. The signs shall state that asbestos is being removed from the area, that asbestos is a suspected carcinogen, and that proper respiratory protection is required. Signs shall have a reflective surface. Lettering shall be a minimum of2 inches (51 mm) high.

Chapter 50. Hazardous Materials - General Provisions.

Section 5001.5.1 is amended to add items numbered 10 & 11 to read as follows:

Fire Department related safety equipment
Fire alarm control panel (FACP)
Sprinkler riser
Fire department connection (FDC)
Knox Box location
Gas valve shutoff
Electrical main shutoff
Water shutoff
Elevator equipment room
A Site Fire/Explosion/Hazardous Material Release Analysis Assessment. A Fire Protection Engineer (FPE) stamped risk assessment is required for each possible hazard risk associated with fire, explosion, smoke, and toxicity associated with the possible incident at a facility that is identified as a bulk transfer/process/storage facility. Refer to NFPA 550 & 551 for references.

Section 5001.5.3 is added to read:
5001.5.3 Emergency response support information. Floor plans, material safety data sheets, Hazardous Materials Management Plans (HMMP), Hazardous Material Inventory Statements (HMIS), and other information must be stored at a readily accessible location; as determined by the fire code official. This location may be in cabinets. located outside of facilities or buildings. Information may be required to be maintained in a specific electronic media format to facilitate computer aided dispatching.

Section 5003.9.1.2 is added to read:
5003.9.1.2 Documentation. Evidence of compliance with provisions of this chapter as well as with state and federal hazardous material regulations shall be maintained on site and available for inspection by fire department personnel.

Chapter 56. Explosives and Fireworks.

Section 5601.1.3 is amended to read as follows:

Fireworks. The possession, manufacture, storage, sale, handling and use of fireworks are prohibited within the jurisdiction of the District.

Exceptions:

Storage and handling of fireworks by a Public Safety Agency.

The use of fireworks for fireworks displays pyrotechnics before a proximate audience and pyrotechnic special effects in motion pictures, television, theatrical or group entertainment productions as allowed in Title 19, Division 1, Chapter 6 Fireworks reprinted in Section 5608 and Health and Safety Code Division 11.

Snap Caps and Party Poppers classified by the State Fire Marshal as pyrotechnic devices.

Section 5601.2.2 is amended to read as follows:
5601.2.2 Sale and retail display. No person shall construct a retail display or offer for sale any explosives, explosive materials, or fireworks within the jurisdiction. Exception: Snap Caps and Party Poppers classified by the State Fire Marshal as pyrotechnic devices.

Section 5601.2.4 is amended to read as follows:
5601.2.4 Financial responsibility. Before a permit is issued pursuant to Section 5601.2, the applicant shall file with the jurisdiction a corporate surety bond in the principal sum of $2,000,000 or a public liability insurance policy for the same amount, for the purpose of the payment of all damages to persons or property which arise from, or are caused by, the conduct of any act authorized by the permit upon which any judicial judgment results. The fire code official is authorized to specify a greater or lesser amount when, in his or her opinion, conditions at the location of use indicate a greater or lesser amount is required. Government entities shall be exempt from this bond requirement.

Exception: Fireworks in accordance with California Code of Regulations, Title 19, Division 1, Chapter 6. See Section 5608.

Chapter 57. Flammable and Combustible Liquids.

Section 5703.3.1 is added to read:
5703.3.1 Facility site Fire/Explosion/Hazardous Material Release Analysis Assessment. A Fire Protection Engineer (FPE) stamped risk assessment is required for each possible hazard risk associated with fire, explosion, smoke, and toxicity associated with the possible incident at a facility that is identified as a bulk transfer/process/storage facility when required by the fire official. Refer to NFPA 550 & 551 for references.

Section 5704.2.9.6.1 is amended to read as follows:

Section 5704.2.9.6.1 Locations where above-ground tanks are prohibited. The storage of Class I and II liquids in above-ground tanks outside of buildings is prohibited in all zoning districts except districts zoned for commercial, industrial, or agricultural uses.

Exception: Protected above-ground tanks for the purpose of emergency power generator installations in areas zoned commercial, industrial, agricultural, business district, rural or rural residential, and for facilities on an individual basis consistent with the intent of this provision. Tank size shall not exceed 1,000 gallons for any class of liquids.

Section 5706.2.4.4 is amended to read:

Section 5706.2.4.4 Locations where above-ground tanks are prohibited. Storage of Class I and II liquids in above-ground tanks is prohibited in all zoning districts except district zoned for commercial, industrial, or agricultural uses.

Exception: Protected above-ground tanks for the purpose of emergency power generator installations in areas zoned commercial, industrial, agricultural, business district, rural or rural residential, and for facilities on an individual basis consistent with the intent of this provision. Tank size shall not exceed 1,000 gallons for any class liquids.

Chapter 58. Flammable Gasses and Flammable Cryogenic Fluids Section 5806.2 is amended to read as follows:

Limitations. The storage of flammable cryogenic fluids in stationary containers outside of buildings is prohibited in any area which is zoned for other than industrial use.

Exception: Liquid hydrogen fuel systems in compliance with Section 5806.3 or 5806.4.

Chapter 61. Liquefied Petroleum Gases.

Section 6103.2.1.7 is amended to read:
6103.2.1.7 Use for food preparation. Individual portable L-P containers used, stored, or handled inside a building classified as a Group A, Group B, or Group M occupancy for the purposes of cooking, food display, or a similar use, shall be limited in size to one quart capacity and shall be of an approved type. The number of portable containers permitted will be at the discretion of the fire code official. LP-gas appliances used for food preparation shall be listed for such use in accordance with the California Mechanical Code and NFPA 58.

Section 6104.2 is amended to read:
6104.2 Maximum capacity within established limits. The storage of liquefied petroleum gas is prohibited in any central business district and in all zoning districts except districts zoned for commercial, industrial, rural, or agricultural uses. The aggregate capacity of any one installation used for the storage of liquefied petroleum gas shall not exceed a water capacity of 2,000 gallons (7570 L).

Chapter 80. Referenced Standards.

Chapter 80 is amended by adding the following referenced standards:

NFPA 3 (2021): Recommended Practice for Commissioning of Fire Protection and Life Safety Systems NFPA 850 (2020): Recommended Practice for Fire Protection for Electric Generating Plants and High Voltage Direct Current Converter Stations.

Chapter 80 is further amended by amending the NFPA 13D (2022) (Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes) standard as follows:

Section 7.7.1 is added, to read:

7.7.1 Where CPVC pipe is installed above the normal insulation in an unconditioned space, such as in an attic space, or a garage without conditioned living space above, CPVC pipe shall be adequately insulated to a minimum R-19 value, or equivalent, or pipe shall be limited to Type K or L copper, or ferrous piping.

Section 8.3.5.1.2 is amended to read:

8.3.5.1.2 Where fuel-fired equipment is below or on the same level as occupied areas of the dwelling unit, at least one quick-response intermediate temperature sprinkler shall be installed above the equipment or at the wall separating the space with the fuel-fired equipment from the occupied space. In unconditioned spaces, CPVC pipe shall be adequately insulated to a minimum R-19 value, or equivalent, or pipe shall be limited to Type K or L copper, or ferrous piping.

Appendix B. Fire-Flow Requirements for Buildings.

Table B105.2 is amended to read:

TABLE B105.2

REQUIRED FIRE-FLOW FOR BUILDINGS OTHER THAN ONE- AND
TWO-FAMILY DWELLINGS, GROUP R-3 AND R-4 BUILDINGS AND TOWNHOUSES

AUTOMATIC SPRINKLER SYSTEM (DESIGN STANDARD)

MINIMUM FIRE-FLOW (GALLONS PER MINUTE)

FLOW DURATION (HOURS)
No automatic sprinkler system
Value in Table B105.1(2)
Duration in Table B105.1(2)
Section 903.3.1.1 of the California Fire Code
50% of the value in Table B105.1(2)a
Duration in Table B105.1(2) at the reduced flow rate
Section 903.3.1.2 of the California Fire Code
50% of the value in Table B105.1(2)a
Duration in Table B105.1(2) at the reduced flow rate
For SI: 1 gallon per minute= 3.785 Lim
The reduced fire-flow shall be not less than 1,500 gallons per minute.

Appendix C. Fire Hydrant Locations and Distribution.

Table C102.1 is amended as follows:

The title of Table C102.1 is amended to read: TABLE C102.1 REQUIRED NUMBER AND SPACING OF FIRE HYDRANTS (footnotes h and j) The heading of the fourth column of Table C102.1 is amended to read:

MAXIMUM DISTANCE FROM ANY POINT ON STREET OR ROAD FRONTAGE TO A HYDRANT (d, f, g, i) Footnotes "i" and "j" are added to Table C102.1, to read:
i. A fire hydrant shall be provided within 250 feet of a fire trail access point off a public or private street. j. For infill projects within existing single-family residential developments, Section 507.5.1 applies.

Appendix D. Fire Apparatus Access Roads.

Section D102.1 is amended to read:

D102.1 Access and loading. Facilities, buildings or portions of buildings hereafter constructed shall be accessible to fire department apparatus by way of an approved fire apparatus access road with an asphalt, concrete, or other approved all-weather driving surface capable of supporting the imposed load of fire apparatus weighing at least 74,000 pounds (34,473 kg) in accordance with Caltrans Design Standard HS- 20-44.

Exception: Driveways serving one or two single-family dwellings may be constructed of an alternate surface material, providing the imposed weight load design minimums are met and the grade does not exceed 10 percent.

Section D103.2 is amended to read:

D103.2 Grade. Fire department access roadways having a grade of between 16 percent and 20 percent shall be designed to have a finished surface of grooved concrete sufficient to hold a 44,000 pound (19 958 kg) traction load. The grooves in the concrete surface shall be ½ inch (13 mm) wide by ½ inch (13 mm) deep and 1 ½ inch (38 mm) on center and set at a 30 to 45 degree angle across the width of the roadway surface. No grade shall exceed 20 percent, nor shall the cross slope exceed 8%, unless authorized in writing by the fire code official.

Section D103.2.1 is added, to read:

D103.2.1 Angles of approach and departure. The angles of approach and departure for any means of access shall not exceed 10 percent at 10 feet of the grade break.

Section D103.3 is amended to read:

D103.3 Turning radius. Based on a minimum unobstructed width of 20 feet, a fire apparatus access roadway shall be capable of providing a minimum standard turning radius of 25 feet (7620 mm) inside and 45 feet (13 716 mm) outside.

Figure D103.l is amended to read:

Table D103.4 is amended to read:

TABLE D103.4 REQUIREMENTS FOR DEAD-END FIRE APPARATUS ROADS LENGTH
(feet)

MINIMUM WIDTH
(feet)
. TURNAROUNDS REQUIRED
0-150
20a
20 None required
151 -
750
20a
20 100-foot Hammerhead, 50-foot "Y", 75-foot Shunt or 90-foot- diameter cul-de-sac in accordance with figure D103.1 Over 750
Special approval requiredb
A driveway with a minimum width of 16 feet is acceptable for access to no more than two single-family dwellings.

Any fire apparatus access roadway or driveway that is approved to be less than 20 feet wide and to exceed 750 feet in length shall have outsets or turnouts every 300 feet along the length of the road or driveway, or at locations approved by the fire code official. Each outset or turnout shall be of the following dimensions: an 8-foot-wide turnout that extends at least 40 feet in length.

Section D103.5 is amended as follows:

Criteria 1 of Section D103.5 is amended to read:

The minimum clear width shall be 20 feet (6096mm).

Exception: For access to one or two single-family dwellings, 16 feet clear width is acceptable.

Criteria 9 is added to Section D103.5, to read:

9. All gates shall be installed and located a minimum of 30 feet off the street.

Section D103.6.1 is amended to read:

D103.6.1 Roads less than 28 feet in width. Fire apparatus access roads less than 28 feet wide shall be posted on both sides as a fire lane.

Section D103.6.2 is amended to read:

D103.6.2 Roads 28 feet in width or greater, but less than 36 feet in width. Fire apparatus access roads 28 feet wide or greater, but less than 36 feet wide, shall be posted on one side of the road as a fire lane.

Section D106.1 is amended by deleting the exception and to read:

D106.1 Projects having more than 100 dwelling units. Multiple-family residential projects having more than 100 dwelling units shall be provided with two separate and approved fire apparatus access roads and shall meet the requirements of Section D104.3.

Section D106.2 is deleted in its entirety.

SECTION 16. AMENDMENTS TO GREEN BUILDING STANDARDS CODE. Hercules Municipal Code, Title 9, Chapter 16, Sections 9-16.02, 9-16.03, and 9-16.04 are hereby repealed and replaced in their entirety to read as set forth below.

Sec. 9-16.02 Adoption by Reference.

The California Green Building Standards Code, 2022 Edition, as adopted by the State of California and published in the “California Code of Regulations,” Title 24, Part 11 is adopted by reference and made a part of this Chapter as though fully set forth herein, subject to the additions and deletions as set forth in this Chapter.

Sec. 9-16.03 Copies on File.

One (1) copy of the 2022 Edition of the California Green Building Standards Code, as adopted by Section HYPERLINK "https://www.codepublishing.com/CA/Hercules/" \l "!/Hercules09/Hercules0916.html#9-16.02" 9-16.02, is on file in the office of the Chief Building Official for inspection by the public.

Sec. 9-16.04 Amendments, Additions, and Deletions
The following portion of the Ordinance Code of Contra Costa County, California, is adopted by reference under the authority of Sections 50020 through 50022.9 of the California Government Code:

Adopting the amendments to the 2022 California Green Building Standards Code by the changes, additions, and deletions set forth below as set forth in the Contra Costa County Ordinance No. 2019-31, Chapter 74-4, “Amendments to CGBSC” Section 74-4.006 with Section numbers used below being those of the 2022 California Green Building Standards Code.

Section 202 (Definitions) of CGBSC Chapter 2 (Definitions) is amended by replacing the definition of Electric Vehicle Charging Space (EV Space) with the following:

ELECTRIC VEHICLE CHARGING SPACE (EV SPACE). A space intended for current or future installation of EV charging equipment and charging of electric vehicles.

Section 301.1.1 (Additions and alterations) of CGBSC Chapter 3 (Green Building) is amended to read:

Section 301.1.1 Additions and alterations. The mandatory provisions of Chapter 4 shall apply to additions or alterations of existing residential buildings where the addition or alteration increases the building's conditioned area, volume, or size. The requirements shall apply only to and within the specific area of the addition or alteration.

The mandatory provisions of Section 4.106.4.2 may apply to additions or alterations of existing parking facilities or the addition of new parking facilities serving existing multifamily buildings. See Section 4.106.4.3 for application.

NOTE: Repairs including, but not limited to, resurfacing, restriping, and repairing or maintaining existing lighting fixtures are not considered alterations for the purpose of this section.

The mandatory provisions of Section 4.408 shall apply to the following types of construction or demolition projects for existing residential buildings:

Projects that increase the total combined conditioned and unconditioned building area by 5,000 square feet or more.

Alterations to existing structures impacting 5,000 square feet or more of total combined conditioned and unconditioned building area.

3. Demolition projects when a demolition permit is required.

Exception: Demolition projects undertaken because the enforcing agency has determined that the demolition is necessary to abate a public nuisance or otherwise protect public health and safety.

For the purposes of determining whether a project meets the 5,000 square-foot threshold, the enforcing agency may deem all phases of a project and all related projects taking place on a single or adjoining parcel(s) as a single project.

Section 301.3.2 (Waste diversion) of CGBSC Chapter 3 (Green Building) is amended to read:

Section 301.3.2 Waste diversion. The requirements of Section 5.408 shall apply to additions, alterations, and demolition whenever a permit is required for work.

Exception: Demolition projects undertaken because the enforcing agency has determined that the demolition is necessary to abate a public nuisance or otherwise protect public health and safety.

Section 4.106.4.2.1 (Multifamily development projects with less than 20 dwelling units; and hotels and motels with less than 20 sleeping units or guest rooms) of CGBSC Chapter 4 (Residential Mandatory Measures) is amended by adding the following Item 3 to the end of the section:

3. EV Chargers. Ten (10) percent of the total number of parking spaces shall be equipped with fully-operational Level 2 EVSE. Where common use parking is provided, at least one EV charger shall be located in the common use parking area and shall be available for use by all residents or guests.

When low power Level 2 EV charging receptacles or Level 2 EVSE are installed beyond the minimum required, an automatic load management system (ALMS) may be used to reduce the maximum required electrical capacity to each space served by the ALMS. The electrical system and any on-site distribution transformers shall have sufficient capacity to deliver at least 3.3 kW simultaneously to each EV charging station (EVCS) served by the ALMS. The branch circuit shall have a minimum capacity of 40 amperes, and installed EVSE shall have a capacity of not less than 30 amperes. ALMS shall not be used to reduce the minimum required electrical capacity to the required EV capable spaces Section 4.106.4.2.1.1 is added to Section 4.106.4.2.1 (Multifamily development projects with less than 20 dwelling units; and hotels and motels with less than 20 sleeping units or guest rooms) of CGBSC Chapter 4 (Residential Mandatory Measures), to read:

Section 4.106.4.2.1.1 Electric vehicle charging stations (EVCS). Electric vehicle charging stations required by Section 4.106.4.2.1, Item 3, shall comply with Section 4.106.4.2.1.1.

Exception: Electric vehicle charging stations serving public accommodations, public housing, motels and hotels shall not be required to comply with this section. See California Building Code, Chapter 11B, for applicable requirements.

Section 4.106.4.2.1.1.1 Location. EVCS shall comply with at least one of the following options:

The charging space shall be located adjacent to an accessible parking space meeting the requirements of the California Building Code, Chapter 11A, to allow use of the EV charger from the accessible parking space.

The charging space shall be located on an accessible route, as defined in the California Building Code, Chapter 2, to the building.

Exception: Electric vehicle charging stations designed and constructed in compliance with the California Building Code, Chapter 11B, are not required to comply with Section 4.106.4.2.1.1.1 and Section 4.106.4.2.1.1.2, Item 3.

Section 4.106.4.2.1.1.2 Electric Vehicle Charging Stations (EVCS) Dimensions. The charging spaces shall be designed to comply with the following:

The minimum length of each EV space shall be 18 feet (5486 mm).

The minimum width of each EV space shall be 9 feet (2743 mm).

One in every 25 charging spaces, but not less than one, shall also have an 8-foot (2438 mm) wide minimum aisle. A 5-foot (1524 mm) wide minimum aisle shall be permitted provided the minimum width of the EV space is 12 feet (3658 mm).

Surface slope for this EV space and the aisle shall not exceed 1 unit vertical in 48 units horizontal (2.083 percent slope) in any direction.

Section 4.106.4.2.1.1.3 Accessible EV Spaces. In addition to the requirements in Sections 4.106.4.2.1.1.1 and 4.106.4.2.1.1.2, all EVSE, when installed, shall comply with the accessibility provisions for EV chargers in the California Building Code, Chapter 11B. EV ready spaces and EVCS in multifamily developments shall comply with California Building Code, Chapter 11A, Section 1109A.

Section 4.106.4.2.2 (Multifamily development projects with 20 or more dwelling units; and hotels and motels with 20 or more sleeping units or guest rooms) of CGBSC Chapter 4 (Residential Mandatory Measures) is amended by revising Item 3 to read:

3. EV Chargers. Ten (10) percent of the total number of parking spaces shall be equipped with fully-operational Level 2 EVSE. Where common use parking is provided, at least one EV charger shall be located in the common use parking area and shall be available for use by all residents or guests.

When low power Level 2 EV charging receptacles or Level 2 EVSE are installed beyond the minimum required, an automatic load management system (ALMS) may be used to reduce the maximum required electrical capacity to each space served by the ALMS. The electrical system and any on-site distribution transformers shall have sufficient capacity to deliver at least 3.3 kW simultaneously to each EV charging station (EVCS) served by the ALMS. The branch circuit shall have a minimum capacity of 40 amperes, and installed EVSE shall have a capacity of not less than 30 amperes. ALMS shall not be used to reduce the minimum required electrical capacity to the required EV capable spaces Section 4.408.1 (Construction waste management) of CGBSC Chapter 4 (Residential Mandatory Measures) is amended to read:

Section 4.408.1 Construction waste management. Recycle and/or salvage for reuse a minimum of 65 percent of the nonhazardous construction and demolition waste in accordance with Section 4.408.2.

Exceptions:

1. Excavated soil and land-clearing debris.

2. The enforcing agency may identify alternate waste reduction requirements if the agency determines that an owner or contractor has adequately demonstrated that diversion facilities necessary for the owner to comply with this section do not exist or are not located within a reasonable distance from the jobsite.

Section 4.408.2 (Construction waste management plan) of CGBSC Chapter 4 (Residential Mandatory Measures) is amended to read:

Section 4.408.2 Construction waste management plan. Submit a construction waste management plan for the project, signed by the owner, in conformance with Items 1 through 5 prior to issuance of building permit. The construction waste management plan shall be updated as necessary upon approval by the enforcing agency and shall be available during construction for examination by the enforcing agency. The plan must do all of the following:

1. Identify the construction and demolition waste materials to be diverted from disposal by recycling, reuse on the project, or salvage for future use or sale.

2. Specify if construction and demolition waste materials will be sorted on-site (source-separated) or bulk mixed (single stream).

3. Identify diversion and disposal facilities where the construction and demolition waste material will be taken and identify the waste management companies, if any, that will be utilized to haul the construction and demolition waste material. A waste management company utilized to haul construction and demolition waste material must have all applicable County approvals.

4. Identify construction methods employed to reduce the amount of construction and demolition waste generated.

5. Specify that the amount of construction and demolition debris shall be calculated consistent with the enforcing agency’s requirements for the weighing of debris. The owner shall ensure that all construction and demolition debris diverted or disposed are measured and recorded by weight or volume using the most accurate method of measurement available. To the extent practicable, all construction and demolition debris shall be weighed using scales. Scales shall be in compliance with all regulatory requirements for accuracy and maintenance. For construction and demolition debris for which weighing is not possible due to lack of scales or not practical due to materials being reused on-site or elsewhere or other considerations, a volumetric measurement shall be used. The owner shall convert volumetric measurements to weight using the standardized conversion factors approved by the enforcing agency for this purpose.

Section 4.408.3 (Waste management company) of CGBSC Chapter 4 (Residential Mandatory Measures) is deleted.

Section 4.408.5 (Documentation) of CGBSC Chapter 4 (Residential Mandatory Measures) is amended to read:

Section 4.408.5 Documentation. A construction waste management final report containing information and supporting documentation that demonstrates compliance with Section 4.408.1, Section 4.408.2, Items 1 through 5, and, when applicable, Section 4.408.4 or Section 4.408.4.1, shall be provided to the enforcing agency before the final inspection. The required documentation shall include, but is not necessarily limited to, the following:

1. Documentation of the quantity by weight of each material type diverted or disposed, consistent with the requirements of Section 4.408.2, Item 5, and receipts or written certification from all receiving facilities utilized to divert or dispose waste generated by the project that substantiate the amounts specified on the construction waste management final report; or

2. For projects that satisfy the waste stream reduction alternative specified in Section 4.408.4 or Section 4.408.4.1, documentation of the quantity by weight of each material type disposed and the total combined weight of construction and demolition waste disposed in landfills as a result of the project, the corresponding pounds disposed per square foot of the building area, and receipts or written certification from all receiving facilities utilized to dispose waste generated by the project that substantiate the amounts specified on the construction waste management final report.

Section 5.106.5.3.1 (EV capable spaces) of CGBSC Chapter 5 (Nonresidential Mandatory Measures) is amended to read:

Section 5.106.5.3.1 EV Capable Spaces. [N] EV capable spaces shall be provided in accordance with Table 5.106.5.3.1 and the following requirements:

Raceways complying with the California Electrical Code and no less than 1-inch (25 mm) diameter shall be provided and shall originate at a service panel or a subpanel(s) serving the area, and shall terminate in close proximity to the proposed location of the EV capable space and into a suitable listed cabinet, box, enclosure or equivalent. A common raceway may be used to serve multiple EV capable spaces.

A service panel or subpanel(s) shall be provided with panel space and electrical load capacity for a dedicated 208/240 volt, 40-ampere minimum branch circuit for each EV capable space, with delivery of 30-ampere minimum to an installed EVSE at each EVCS.

The electrical system and any on-site distribution transformers shall have sufficient capacity to supply full rated amperage at each EV capable space.

The service panel or subpanel circuit directory shall identify the reserved overcurrent protective device space(s) as "EV CAPABLE". The raceway termination location shall be permanently and visibly marked as "EV CAPABLE." Note: A parking space served by electric vehicle supply equipment or designed as a future EV charging space shall count as at least one standard automobile parking space only for the purpose of complying with any applicable minimum parking space requirements established by an enforcement agency. See Vehicle Code Section 22511.2 for further details.

TABLE 5.106.5.3.1

TOTAL NUMBER OF ACTUAL PARKING SPACES

NUMBER OF REQUIRED EV CAPABLE SPACES
NUMBER OF EVCS (EV CAPABLE SPACES PROVIDED WITH EVSE)2
1-9
0 0
10-25
4 3
26-50
8 5
51-75
13 8
76-100
17 10
101-150
25 15
151-200
35 20
201 and over
20 percent of total1
10 percent of total1

1. Calculation for spaces shall be rounded up to the nearest whole number

2. The number of required EVCS (EV capable spaces provided with EVSE) in column 3 count toward the total number of required EV capable spaces shown in column 2.

Section 5.106.5.3.2 (Electric vehicle charging stations (EVCS)) of CGBSC Chapter 5 (Nonresidential Mandatory Measures) is amended to read:

Section 5.106.5.3.2 Electric Vehicle Charging Stations (EVCS). EV capable spaces shall be provided with fully-operational EVSE to create EVCS in the number indicated in Table 5.106.5.3.1. The EVCS required by Table 5.106.5.3.1 may be provided with EVSE in any combination of Level 2 and Direct Current Fast Charging (DCFC), except that at least one Level 2 EVSE shall be provided.

One EV charger with multiple connectors capable of charging multiple EVs simultaneously shall be permitted if the electrical load capacity required by Section 5.106.5.3.1 for each EV capable space is accumulatively supplied to the EV charger.

The installation of each DCFC EVSE shall be permitted to reduce the minimum number of required EV capable spaces without EVSE by five and reduce proportionally the required electrical load capacity to the service panel or subpanel.

Section 5.408.1 (Construction waste management) of CGBSC Chapter 5 Nonresidential Mandatory Measures) is amended to read:

Section 5.408.1 Construction waste management. Recycle and/or salvage for reuse a minimum of 65 percent of the nonhazardous construction and demolition waste in accordance with Section 5.408.1.1.

Exceptions:

1. Excavated soil and land-clearing debris.

2. The enforcing agency may identify alternate waste reduction requirements if the agency determines that an owner or contractor has adequately demonstrated that diversion facilities necessary for the owner to comply with this section do not exist or are not located within a reasonable distance from the jobsite.

Section 5.408.1.1 (Construction waste management plan) of CGBSC Chapter 5 Nonresidential Mandatory Measures) is amended to read:

Section 5.408.1.1 Construction waste management plan. Submit a construction waste management plan for the project, signed by the owner, in conformance with Items 1 through 5 prior to issuance of building permit. The construction waste management plan shall be updated as necessary upon approval by the enforcing agency and shall be available during construction for examination by the enforcing agency. The plan must do all of the following:

1. Identify the construction and demolition waste materials to be diverted from disposal by recycling, reuse on the project, or salvage for future use or sale.

2. Specify if construction and demolition waste materials will be sorted on-site (source-separated) or bulk mixed (single stream).

3. Identify diversion and disposal facilities where the construction and demolition waste material will be taken and identify the waste management companies, if any, that will be utilized to haul the construction and demolition waste material. A waste management company utilized to haul construction and demolition waste material must have all applicable County approvals.

4. Identify construction methods employed to reduce the amount of construction and demolition waste generated.

5. Specify that the amount of construction and demolition debris shall be calculated consistent with the enforcing agency’s requirements for the weighing of debris. The owner shall ensure that all construction and demolition debris diverted or disposed are measured and recorded by weight or volume using the most accurate method of measurement available. To the extent practicable, all construction and demolition debris shall be weighed using scales. Scales shall be in compliance with all regulatory requirements for accuracy and maintenance. For construction and demolition debris for which weighing is not possible due to lack of scales or not practical due to material being reused on-site or elsewhere or other considerations, a volumetric measurement shall be used. The owner shall convert volumetric measurements to weight using the standardized conversion factors approved by the enforcing agency for this purpose.

Section 5.408.1.2 (Waste management company) of CGBSC Chapter 5 (Nonresidential Mandatory Measures) is deleted.

Section 5.408.1.4 (Documentation) of CGBSC Chapter 5 (Nonresidential Mandatory Measures) is amended to read:

Section 5.408.1.4 Documentation. A construction waste management final report containing information and supporting documentation that demonstrates compliance with Section 5.408.1, Section 5.408.1.1, Items 1 through 5, and, when applicable, Section 5.408.1.3, shall be provided to the enforcing agency before the final inspection. The required documentation shall include, but is not necessarily limited to, the following:

1. Documentation of the quantity by weight of each material type diverted or disposed, consistent with the requirements of Section 5.408.1.1, Item 5, and receipts or written certification from all receiving facilities utilized to divert or dispose waste generated by the project that substantiate the amounts specified on the construction waste management final report; or For projects that satisfy the waste stream reduction alternative specified in Section 5.408.1.3, documentation of the quantity by weight of each new construction material type disposed and the total combined weight of new construction waste disposed as a result of the project, the corresponding pounds of new construction disposal per square foot of the building area, and receipts or written certification from all receiving facilities utilized to dispose waste generated by the project that substantiate the amounts specified on the construction waste management final report SECTION 17. AMENDMENTS TO RESIDENTIAL CODE. Hercules Municipal Code, Title 9, Chapter 17, Sections 9-17.02, 9-17.03, and 9-17.04 are hereby repealed and replaced in their entirety to read as set forth below.

Sec. 9-17.02 Adoption by Reference.

The California Residential Code, 2022 Edition, including appendices, as published by the International Code Council, as modified by the State of California and published in the “California Code of Regulations, Title 24, Part 2.5” is adopted by reference and made a part of this Chapter as though fully set forth herein, subject to the changes, additions and deletions as set forth in this Chapter.

Sec. 9-17.03 Copies on File.

One (1) copy of the 2022 Edition of the California Residential Code, as adopted by Section HYPERLINK "https://www.codepublishing.com/CA/Hercules/" \l "!/Hercules09/Hercules0917.html#9-17.02" 9-17.02, is on file in the office of the Chief Building Official for inspection by the public.

Sec. 9-17.04 Amendments, Additions, and Deletions. The following portion of the Ordinance Code of Contra Costa County, California, is adopted by reference under the authority of Sections HYPERLINK "http://leginfo.legislature.ca.gov/faces/codes_displaySection.xhtml?lawCode=GOV&sectionNum=50020" \t "_blank" 50020 through HYPERLINK "http://leginfo.legislature.ca.gov/faces/codes_displaySection.xhtml?lawCode=GOV&sectionNum=50022.9" \t "_blank" 50022.9 of the California Government Code:

Adopting the amendments to the 2022 California Residential Code by the changes, additions, and deletions set forth below as set forth in Contra Costa County Ordinance No. 2022-35, Chapter 74-4 and Division 72, “Amendments to CRC” to read as follows, with Section numbers used below are those of the 2022 California Residential Code.:

Sections R103 and R112 of CRC Chapter 1 (Scope and Application) are deleted.

In Section Rl05.2 (Work exempt from permit) of CRC Chapter 1 (Scope and Application), subsection 3 is amended to read:

3. Retaining walls that are not more than 3 feet in height measured from the top of the footing to the top of the wall and that have a downward ground slope at the bottom of the retaining wall not exceeding 1(vertical):10(horizontal), unless supporting a surcharge or ground slope exceeding 1(vertical):2(horizontal) or impounding Class I, II, or III-a liquids.

Section R314.8.1.1 is added to Section R314.8 (Existing Group R-3 occupancies) of CRC Chapter 3 (Building Planning), to read:

R314.8.1.1 Existing flat roof buildings. In existing flat roof buildings, the installation of a smoke detector that complies with Section R314.6 shall be required when a pitched roof is added on top of the existing flat roof and the solid sheathing of the flat roof is not removed.

Section R602.10.3(3) (Bracing Requirements Based on Seismic Design Category) of CRC Chapter 6 (Wall Construction) is amended as follows:

The title of Table R602.10.3(3) is amended to read:

TABLE R602.10.3(3)i
Footnote "i" is added to Table R602.10.3(3), to read:
i. In Seismic Design Categories D0, D1, and D2, Method GB is not permitted and the use of Method PCP is limited to one-story dwellings and accessory structures.

Section R602.10.4.5 is added to Section R602.10.4 (Construction methods for braced wall panels) of CRC Chapter 6 (Wall Construction), to read:

R602.10.4.5 Limits on methods GB and PCP. In Seismic Design Categories D0, D1, and D2, Method GB is not permitted, but gypsum board is permitted to be installed on the opposite side of the studs from other types of braced wall panel sheathing. In Seismic Design Categories D0, D1, and D2, the use of Method PCP is limited to one-story dwellings and accessory structures.

Appendix AH and Appendix AX of the CRC is incorporated into the County building code. Appendix AA, Appendix AB, Appendix AC, Appendix AD, Appendix AE, Appendix AF, Appendix AG, Appendix AI, Appendix AJ, Appendix AK, Appendix AL, Appendix AM, Appendix AN, Appendix AO, Appendix AP, Appendix AQ, Appendix AR, Appendix AS, Appendix AT, Appendix AU, Appendix AV, Appendix AW, Appendix AY, and Appendix AZ of the CRC are excluded from the County building Footnote "g" is added to Table R602.10.3(3), to read:
g. In Seismic Design Categories D0, D1, and D2, Method GB is not permitted and the use of Method PCP is limited to one-story dwellings and accessory structures.

Section R602.10.4.5 is added to Section R602.10.4 (Construction methods for braced wall panels) of CRC Chapter 6 (Wall Construction), to read:

R602.10.4.5 Limits on methods GB and PCP. In Seismic Design Categories D0, D1, and D2, Method GB is not permitted, but gypsum board is permitted to be installed on the opposite side of the studs from other types of braced wall panel sheathing. In Seismic Design Categories D0, D1, and D2, the use of Method PCP is limited to one-story dwellings and accessory structures.

Appendix H of the CRC is incorporated into the City building code. Appendix A, Appendix B, Appendix C, Appendix D, Appendix E, Appendix F, Appendix G, Appendix I, Appendix J, Appendix K, Appendix L, Appendix M, Appendix N, Appendix O, Appendix P, Appendix Q, Appendix R, Appendix S, Appendix T, Appendix U, Appendix V, and Appendix W of the CRC are excluded from the City building code.

SECTION 19. PROPERTY MAINTENANCE CODE. Hercules Municipal Code, Title 9, Chapter 18 Sections 9-18.01, 9-18.02 and 9-18.03 are hereby repealed and replaced as follows:

Sec. 9-18.01 Administration.

These regulations shall be known as the “International Property Maintenance Code,” and may be so cited, and will be referred to herein as “this Chapter.” This Code is one (1) of the technical codes of building regulations and is administered under Title 9, Chapter 1 of the Hercules Municipal Code.

Sec. 9-18.02 Adoption by Reference.

The International Property Maintenance Code, 2021 Edition, including appendices, as published by the International Code Council is adopted by reference and made a part of this Chapter as though fully set forth herein, subject to the additions and deletions as set forth in this Chapter Sec. 9-18.03 Copies on File.

One (1) copy of the 2021 Edition of the International Property Maintenance Code, as adopted by Section HYPERLINK "https://www.codepublishing.com/CA/Hercules/" \l "!/Hercules09/Hercules0918.html#9-18.02" 9-18.02, is on file in the office of the Chief Building Official for inspection by the public.

SECTION 20. SEVERABILITY. If any section, subsection, sentence, clause, or phrase of this Ordinance is for any reason held to be invalid, such decisions shall not affect the validity of the remaining portions of this Ordinance. The Council hereby declares that it would have adopted the Ordinance, and each section, subsection, sentence, clause, or phrase thereof, irrespective of the fact that any one or more sections, subsections, sentences, clauses or phrases be deleted.

SECTION 21. EFFECTIVE DATE AND PUBLICATION. The City Clerk shall certify to the adoption of this Ordinance and shall publish or post the Ordinance as required by law. This Ordinance shall be effective thirty (30) days from date of final adoption.

THE FOREGOING ORDINANCE was first read at a regular meeting of the Hercules City Council on the 10th day of January, 2023, and was passed and adopted at a regular meeting of the Hercules City Council on the _____ day of _____________, 2022, by the following vote:

AYES:

NOES:

ABSENT:

ABSTAIN:

Alex Walker-Griffin, Mayor
__________________________________________
Eibleis Melendez
Acting City Clerk
Ordinance No. ___
Page PAGE 3 of NUMPAGES 44

← All documents from this meeting