PROJECT DIRECTORY
UNDERGROUND SERVICE ALERT
APPLICABLE CODESALL WORK SHALL COMPLY WITH THE FOLLOWING APPLICABLE CODES:2017 NATIONAL ELECTRICAL CODE2019 CALIFORNIA ELECTRICAL CODE2019 CALIFORNIA BUILDING CODE2019 CALIFORNIA GREEN BUILDING CODE2019 CALIFORNIA MECHANICAL CODE2019 CALIFORNIA PLUMBING CODESCOPE OF WORK EROSION CONTROL NOTES:-EROSION AND SEDIMENT CONTROL BEST MANAGEMENT PRACTICES (BMPS) SHALL BE IMPLEMENTED ANDMAINTAINED TO MINIMIZE AND/OR PREVENT THE TRANSPORT OF SOIL FROM THE CONSTRUCTION SITE.-APPROPRIATE BMPS FOR CONSTRUCTION RELATED MATERIALS, WASTES, SPILLS, PR RESIDUES SHALL BEIMPLEMENTED TO ELIMINATE OR REDUCE TRANSPORT FROM THE SITE TO STREETS, DRAINAGE FACILITIES,OR ADJOINING PROPERTIES BY WIND OR RUNOFF.
SHEET INDEX
SOUTHERN CALIFORNIA EDISON CHARGE READY PROGRAMHUNTINGTON BEACH PUBLIC WORKS17371 GOTHARD STHUNTINGTON BEACH, CA 92647SCE PROJECT ID: 00001424207ADDRESS:HUNTINGTON BEACH PUBLIC WORKS NORTH17371 GOTHARD STHUNTINGTON BEACH, CA 92647ENGINEER OF RECORD:BRYTEMOVE ENERGYRAOUL L. WOOD, P.E., LEED AP, CEM(909) [email protected] DESCRIPTIONAPN:11103235 SHEET NUMBERSHEET TITLEDATE:SCALE:CHECKED BY:DRAWN BY:
REVISIONMARKDATEDESCRIPTION
PROJECT DEVELOPER
PROJECT SITE
BRYTEMOVE ENERGY1690 SCENIC AVE.COSTA MESA, CA 92626TEL: (714) 908-5266www.brytemove.com V103-02-22CD30
NOT FOR CONSTRUCTION
AS SHOWN3/30/22
G-0
KTSL
HUNTINGTON BEACH PUBLIC WORKS17371 GOTHARD STHUNTINGTON BEACH, CA 92647SCE PROJECT ID: 00001424207 DWG: E:\brytemove energy\Engineering - Documents\Customer Files\Southern California Edison\Projects\HuntingtonBeach - Public Works (N) 4207\Engineering\CAD\SCE HUNTINGTON BEACH Public_Works-20220310.dwg BY: ovillamar Mar 30, 2022 - 4:57:44pmPROJ:P- SOUTHERN CALIFORNIA EDISON CO.CHARGE READY PROGRAM2244 WALNUT GROVE AVENUEROSEMEAD, CA 91770TEL:(800) 655-4555
TITLE PAGE
AREA OF WORK
VICINITY MAP
SITE MAP
SITE LOCATION
UNDERGROUND SERVICE ALERTUTILITY NOTIFICATION CENTER OF CALIFORNIA811 OR (800) 422-41333 WORKING DAYS UTILITY NOTIFICATION PRIOR TO CONSTRUCTIONCONTRACTOR SHALL VERIFY ALL PLANS & EXISTING LOCATIONS,CONDITIONS ON THE JOB SITE & SHALL IMMEDIATELY NOTIFY THEENGINEER IN WRITING OF ANY DISCREPANCIES BEFOREPROCEEDING WITH THE WORK OR BE RESPONSIBLE FOR SAME SITE DEVELOPER:SANDY BAKERTRANSPORTATION ELECTRIFICATION PROJECT MANAGEMENTSOUTHERN CALIFORNIA EDISION (SCE)3 INNOVATION WAYPOMONA, CA [email protected](951) 816-0137PROJECT COORDINATOR:BRYTEMOVE ENERGYKEN TAKADA P.E.PROJECT [email protected] COMPANY:SOUTHERN CALIFORNIA EDISON (SCE)PROPERTY OWNER:CITY OF HUNTINGTON BEACH C/OREAL ESTATE SERVICES DIVPO BOX 190HUNTINGTON BEACH, CA 92648 -INSTALL ONE (1) NEW 200A, 277/480V, 3PH, 4W METER PEDESTAL, WITH A 400A, 120/208, 3-PH, 4WDISTRIBUTION SECTION, WITH NEW FOUNDATION.-INSTALL ONE (1) NEW 3 PHASE 112.5KVA STEP DOWN TRANSFORMER 480V - 208/120V WITH NEW FOUNDATION.-INSTALL EIGHT (8) NEW TEMPORARY DUAL TERMINAL BLOCKS WITH FOUNDATIONS FOR FUTURE L2 EVCHARGER.
SHEET #TITLEG-0TITLE PAGEE-1.1SITE PLANE-3LAYOUT DETAILE-5SINGLE LINE DIAGRAM AND CONDUIT & WIRE SCHEDULE
E VS EE VS EE VS EE VS E
E VS EE VS EE VS EE VS E
UEUEUEUEUEUEUET
T
UTILITY INCOMINGLOADS
SHEET NUMBERSHEET TITLEDATE:SCALE:CHECKED BY:DRAWN BY:
REVISIONMARKDATEDESCRIPTION
PROJECT DEVELOPER
PROJECT SITE
BRYTEMOVE ENERGY1690 SCENIC AVE.COSTA MESA, CA 92626TEL: (714) 908-5266www.brytemove.com V103-02-22CD30
NOT FOR CONSTRUCTION
AS SHOWN3/30/22
E-1.1
KTSL
HUNTINGTON BEACH PUBLIC WORKS17371 GOTHARD STHUNTINGTON BEACH, CA 92647SCE PROJECT ID: 00001424207 DWG: E:\brytemove energy\Engineering - Documents\Customer Files\Southern California Edison\Projects\HuntingtonBeach - Public Works (N) 4207\Engineering\CAD\SCE HUNTINGTON BEACH Public_Works-20220310.dwg BY: ovillamar Mar 30, 2022 - 4:57:45pmPROJ:P- SOUTHERN CALIFORNIA EDISON CO.CHARGE READY PROGRAM2244 WALNUT GROVE AVENUEROSEMEAD, CA 91770TEL:(800) 655-4555 SITE PLAN 1SITE PLAN
(E) SCE UTILITYTRANSFORMER277/480V 3P
SCE ELECTRICAL SERVICESUPPLY TO METER, BY T&DUEPROPOSED NON EXPOSEDELECTRICAL CONDUITPROPOSED DUAL PORTTERMINAL BLOCKE VS E NOTES:1.UTILITY DISTRIBUTION INFRASTRUCTURE TO BE BUILTBY OTHERS AND SHOWN ONLY FOR PROJECTCLARITY AND COORDINATION.2.IMPACTED EXISTING PARKING = 16 TOTAL SPACES.3.PROPOSED CHARGING = 16 TOTAL.4.EVSE LAYOUT BASED ON USE OF DUAL PORT5.ALL PARKING SPACES ARE EXISTING. FIELD TOVERIFY EXACT DIMENSION PRIOR TO CONSTRUCTION.6.FIELD VERIFY ALL EQUIPMENT LOCATION TO MAKESURE APPROPRIATE SPACE IS AVAILABLE.7.FIELD VERIFY ALL EXISTING UTILITY LOCATIONS FOREASEMENT REQUIREMENT.
PROPOSED BOLLARD(E) UTILITY TRANSFORMER
LEGEND:PROPOSED DUAL PORTTERMINAL BLOCKE VS E (N) 200A, 277/480V,3PH, 4WMETER PEDESTAL"EV MSB"WITH 400A,120/208, 3-PH, 4WDISTRIBUTIONSECTION(N) 3PH 112.5kVA,480V-208Y/120VSTEP-DOWNTRANSFORMER E-31
E-32
(E) TREE(N) METER PEDESTAL
77'-3"
(E) STRUCTURAL COLUMN
(E) COLUMNTO REMAIN
(N) STEP-DOWN TRANSFORMER
(N) DUAL TERMINALBLOCK #4(N) DUAL TERMINALBLOCK #3(N) DUAL TERMINALBLOCK #2(N) DUAL TERMINALBLOCK #1 (N) DUAL TERMINALBLOCK #8(N) DUAL TERMINALBLOCK #7(N) DUAL TERMINALBLOCK #6(N) DUAL TERMINALBLOCK #5
PROPOSED REMOVABLE BOLLARD
(E) TREETO REMAIN(TYP)
Feet01020
3'
24'-8"