Resolution No. PC-2022-06 August 3, 2022
(C) The use is consistent with the general plan.
The proposed use is consistent with the General Plan designation of Regional Serving Commercial. The Regional Serving Commercial designation is intended for areas that allow more intense urban activities, such as high volume retail sales, and other sales and services which are expected to draw local and Regional customers. Entertainment uses such as movie theaters and nightclubs may be conditionally permitted within the Regional Serving Commercial land use designation.
NOW, THEREFORE, BE IT RESOLVED BY THE PLANNING COMMISSION OF THE CITY OF LA MESA AS FOLLOWS:
1. The foregoing findings of fact and determinations are true and hereby made a part hereof.
2. The foregoing findings of fact and determinations are supported by the staff, report, plans, and exhibits, all of which are herein incorporated by reference.
3. The Planning Commission approves Project No. 2021-26 subject to the conditions of approval in Exhibit A.
PASSED AND ADOPTED at a regular meeting of the Planning Commission of the City of La Mesa, California, held the 3rd day of August 2022, by the following vote, to wit:
AYES: Chair Torpey and Commissioners Jones, Coston, Cooper, and Alvarado NOES: None
ABSENT: None
I, Kerry Kusiak, Secretary of the City of La Mesa Planning Commission, do hereby certify the foregoing to be a true and exact copy of Resolution PC-2022-06, duly passed and adopted by the Planning Commission.
__________________________
Kerry Kusiak, Secretary
La Mesa Planning Commission
Exhibit A
PC Resolution PC-2022-xx
Project 2021-26
Conditions of Approval
A. GENERAL CONDITIONS
1. The project is conditionally approved as set forth on the application, Charcoal House Business Plan, and project drawings received electronically by the City on July 20, 2022, consisting of three (3) sheets total, including A-1 – Site Plan; A-2 – Floor Plan and Roof Plan; A-3 – Elevations; all designated as approved by the Planning Commission on August 3, 2022, and shall not be altered without express authorization by the Community Development Department.
2. This approval shall not waive compliance with any section of the La Mesa Municipal Code or any other applicable City regulations in effect unless specifically waived herein.
3. Performance entertainment shall not occur prior to operating hours as identified in the Charcoal House Business Plan and shall cease by 12:00 a.m. Sunday through Thursday and 1:00 a.m. on Friday, Saturday, and New Year’s Eve.
4. No concurrent use of the banquet hall and general dining area shall be allowed at any time.
5. At all times, building occupancy shall be maintained, and not exceeded, in accordance with all applicable laws, including but not limited to Building Code and Fire Code. The room labeled “banquet hall” is limited to a maximum of 150 guests, and the room labeled “general dining area” is limited to a maximum of 200 guests. The number of occupants and guests shall be continuously monitored by security and/or management personnel.
Appropriate action, including but not limited to removing guests, refusing entry to guests, or temporarily ceasing business operations, shall be taken to ensure that building occupancy or the maximum guest capacity are not exceeded at any time.
6. No open containers of alcoholic beverages shall be allowed outside the premises, including but not limited to the parking lot and adjacent yard area.
7. Security and/or management personnel shall not permit loitering on the premises of the site or within the public right-of-way within or immediately adjacent to the premises. For purposes of this section, the term "loitering" shall mean remaining or lingering in or around the premises with no apparent purpose or reason related to the business located thereon.
8. At all times performance entertainment occurs on-site, the facility shall provide security personnel licensed by the State of California and in possession of a valid Department of Consumer Affairs “security guard card” and a valid City of La Mesa Business License. The applicant shall provide copies of security contracts and security guard cards.
9. All performance entertainment on site must maintain compliance at all times with all applicable noise laws.
10. Doors must remain closed at all times performance entertainment occurs on-site except as needed momentarily for entry to and exit from the building. Signs stating “DOORS TO BE CLOSED DURING ENTERTAINMENT” shall be placed on the interior and the exterior and in close proximity to entry doors to the specification of the Director of Community Development. The lettering of the sign shall be in a font that is clearly legible, all capitals, and not less than 2” in letter height.
11. The Director of Community Development (“Director”) shall provide written notice to the business owner and/or property owner of any substantiated parking and/or vehicular traffic complaints. The notice shall prescribe that performance entertainment operations shall be suspended entirely or in part as determined by the Director in consultation with the City Manager and the Chief of Police. A parking and/or traffic analysis shall be provided to the specification of the Director, whom shall prepare and present a report regarding the complaint(s) and the analysis to the Planning Commission in a noticed public hearing.
Based on the evidence presented and testimony received in the public hearing, the Planning Commission may impose additional restrictions and conditions of approval or may revoke the Conditional Use Permit.
12. The Director of Community Development (“Director”) shall provide written notice to the business owner and/or property owner of any substantiated loitering complaints, noise complaints, nuisance complaints, non-compliance with the Conditional Use Permit, and/or non-compliance with other applicable state or local regulations. The notice shall prescribe that performance entertainment operations shall be suspended entirely or in part as determined by the Director in consultation with the City Manager and the Chief of Police.
In the instance of noise-related complaints, an acoustical analysis shall be performed to the specification of the Director. The Director shall prepare and present a report regarding the complaint(s) and any analysis prepared to the Planning Commission in a noticed public hearing. Based on the evidence presented and testimony received in the public hearing, the Planning Commission may impose additional restrictions and conditions of approval or may revoke the Conditional Use Permit.
13. As soon as possible following one year from the issuance of a certificate of occupancy, the Director of Community Development shall provide a report to the Planning Commission on the operational performance of the use in a duly noticed public hearing.
The Planning Commission shall consider the matter and may modify, add to, remove, and/or reduce conditions of approval based on the report, evidence presented, and testimony received. The use permit shall expire at the conclusion of the public hearing unless the Planning Commission acts to extend the life of the permit for a specified time frame or in perpetuity.
B. THE FOLLOWING CONDITIONS MUST BE SATISFIED PRIOR TO THE ISSUANCE OF THE FINAL OCCUPANCY PERMIT:
Building
1. The applicant shall obtain approvals from all departments for all issued permits: building, fire, planning, grading, SD County ACPD, SD County HazMat, Encroachment, or other permits for the proposed improvements prior to the issuance of a certificate of occupancy.
E:\cp2022\Resolutions\PC\PC-2022-xx (2021-26) CUP.docx
ATTACHMENT B
ATTACHMENT C
Heartland Fire & Rescue
8054 Allison Ave
La Mesa, CA 91942
Friday, 13 October, 2023
Attn: Chris Mittia
,
Property Address:
Charcoal House
9566 Murray Dr
La Mesa, CA 91942
Re: Initial - Routine Fire Inspection on October 13 2023 Notice of Life & Fire Safety Violations: Youare hereby notified that a life and fire safety inspection of your property and/or premises located at the above address has disclosed the following life and fire safety violations; as such, Compliance is required immediately.
Order to Comply:
As such violations are contrary to law, you are hereby required to correct these conditions immediately upon receipt of this notice. An inspection to determine whether you have complied will be conducted on or before the re-inspection date indicated above. Failure to comply with the foregoing order before the date of the re-inspection may subject you to further enforcement action and/or penalties as provided by law and may include administrative fines, civil penalties and/ or a criminal complaint.
Thank you,
Inspector: Property Representative:
Deputy Fire Marshal Rachel Clarke Chris Mittia
[email protected]
619-667-1470
CA-37055 / 2099326 / 266276
Charcoal House
Routine Fire Inspection
Inspection on October 13 2023
Violations repaired / total: 1 / 7
Violation/Information Page(s)
Inspection Violations
Hood cleaning service required.
Hoods, grease-removal devices, fans, ducts and other appurtenances shall be inspected at intervals specified in Table 606.3.3.1 or as approved by the fire code official. Inspections shall be completed by qualified individuals. 606.3.3.1
Inspector Notes: All the kitchen hoods must be cleaned by a professional in accordance with ANSI/IKECA C10 every three months. Provide proof of service immediately.
Violation found on
10/13/2023
Repaired on
10/13/2023
Repaint the faded fire lanes. NO PARKING FIRE LANE
Where required by the fire code official, approved signs or other approved notices or markings that include the words “NO PARKING—FIRE LANE” shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. The means by which fire lanes are designated shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility.
503.3
Inspector Notes: Signage and markings required to indicate fire lane. The signage must state the vehicle code reference.
Will be rechecked on or after
11/12/2023
Violation found on
10/13/2023
Violation Not
Repaired
CA-37055 / 2099326 / 266276
Provide documentation of annual service of the fire alarm system.
The building owner shall be responsible to maintain the fire and life safety systems in an operable condition at all times. Service personnel shall meet the qualification requirements of NFPA 72 for inspection, testing and maintenance of such systems.
Records of inspection, testing and maintenance shall be maintained. 907.8.4
Inspector Notes: Fire alarm systems must serviced annually. Provide proof of service immediately.
Will be rechecked on or after
11/12/2023
Violation found on
10/13/2023
Violation Not
Repaired
Inspection, testing, and maintenance required.
Fire protection and life safety systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection and life safety systems and equipment shall be inspected, tested and maintained or removed in accordance with Section 901.8.
All fire alarm systems, fire detection systems, automatic sprinkler or extinguishing systems, communication systems, and all other equipment, material or systems required by these regulations shall be maintained in an operable condition at all times in accordance with this code and California Code of Regulations, Title 19, Division 1. Upon disruption or diminishment of the fire protective qualities of such equipment, material or systems, immediate action shall be instituted to affect a reestablishment of such equipment, material or systems to their original normal and operational condition.
[California Code of Regulations, Title 19, Division 1, §1.14] Maintenance.
Every fire alarm system or device, sprinkler system, fire extinguisher, fire hose, fireresistive assembly or any other fire safety assembly, device, material or equipment installed and retained in service in any building or structure subject to California Code of Regulations, Title 19, Division 1 regulations shall be maintained in an operable condition at all times in accordance with California Code of Regulations, Title 19, Division 1 regulations and with their intended use. [California Code of Regulations, Title 19, Division 1, §3.24] Maintenance of Equipment.
All fire alarm systems, fire detection systems, automatic sprinkler or extinguishing systems, communication systems, and all other equipment, material or systems 901.6
CA-37055 / 2099326 / 266276
required by California Code of Regulations, Title 19, Division 1 shall be maintained in an operable condition at all times. Upon disruption or diminishment of the fire protective qualities of such equipment, material or systems, immediate action shall be instituted to affect a reestablishment of such equipment material or systems to their original normal and operational condition.
[California Code of Regulations, Title 19, Division 1, §904(a)] Required Inspection, Testing and Maintenance Frequencies.
1. (a) All automatic fire extinguishing systems, including systems installed as an alternate to other building requirements, shall be inspected, tested and maintained in accordance with the following frequencies. Local authorities may require more frequent inspection, testing and maintenance and additional procedures.
[California Code of Regulations, Title 19, Division 1, §904(a)(1)] Required Inspection, Testing and Maintenance Frequencies.
1. (1) Water-based fire protection systems shall be inspected, tested and maintained in accordance with the frequencies required by NFPA 25 (2011 edition) including Annexes A, B, C, D, E, F and G as amended by the State of California. (Published as NFPA 25, 2013 California Edition.) [California Code of Regulations, Title 19, Division 1, §904(b)] Required Inspection, Testing and Maintenance Frequencies.
1. (b) When proof of the installation date of standpipe systems or automatic fire sprinkler systems cannot be furnished, such systems shall receive initial testing and maintenance by July 1, 1985.
[California Code of Regulations, Title 19, Division 1, §904.2(a)] Testing and Maintenance Requirements.
1. (a) All testing and maintenance on automatic fire extinguishing systems in accordance with Health & Safety Code Section 13195 shall be performed by those licensed in accordance with Health and Safety Code Section 13196.5.
Exceptions:
1. (1) The State Fire Marshal may waive, in writing, licensing of fire departments which conduct fire sprinkler and standpipe system testing and maintenance.
2. (2) Service on fire alarm systems and industrial systems as specified in Health and Safety Code Sections 13196.5(b) and (c) may be conducted without a license.
3. (3) Testing and maintenance on automatic fire extinguishing systems exempted in writing by the State Fire Marshal, when the building owner or occupant has the staff and equipment to conduct testing and maintenance.
[California Code of Regulations, Title 19, Division 1, §904.2(b)] Testing and Maintenance Requirements.
CA-37055 / 2099326 / 266276
1. (b) Any testing and maintenance of automatic fire extinguishing systems shall be performed in accordance with these requirements.
Exceptions:
1. (1) The State Fire Marshal may waive, in writing, the requirement that testing and maintenance be performed in accordance with these requirements when a licensee can demonstrate that a system cannot functionally be tested and maintained in accordance with the California Code of Regulations, Title 19, Division 1, Chapter 5.
2. (2) If at any time a licensee encounters a specialized or modified system which cannot be tested and maintained in accordance with California Code of Regulations, Title 19, Division 1, Chapter 5, the licensee shall contact the State Fire Marshal and test and maintain the system as directed.
1. (A) The intent of this section is to cover automatic fire extinguishing systems as originally designed, installed and approved by the Authority Having Jurisdiction. It is not, however, intended to require that such systems be upgraded to current adopted standards.
[California Code of Regulations, Title 19, Division 1, §904.2(h)] Testing and Maintenance Requirements.
1. (h) At the time of testing and maintenance, building management shall be consulted to avoid unnecessary disturbance of normal building operation. [California Code of Regulations, Title 19, Division 1, §904.2(i)] Testing and Maintenance Requirements.
1. (i) The licensee shall contact the local fire authority having jurisdiction prior to testing and maintenance of a system when required by the local fire authority having jurisdiction to do so.
Inspector Notes: Fire sprinkler systems require annual service. Provide proof of service immediately.
Will be rechecked on or after
11/12/2023
Violation found on
10/13/2023
Violation Not
Repaired
CA-37055 / 2099326 / 266276
Ceiling and walls shall maintain fire integrity without holes or breaches.
Materials and firestop systems used to protect membrane and through penetrations in fire-resistance-rated construction and construction installed to resist the passage of smoke shall be maintained. The materials and firestop systems shall be securely attached to or bonded to the construction being penetrated with no openings visible through or into the cavity of the construction. Where the system design number is known, the system shall be inspected to the listing criteria and manufacturer’s installation instructions.
703.1
Inspector Notes: The penetration in the wall must be repaired immediately.
Will be rechecked on or after
11/12/2023
Violation found on
10/13/2023
Violation Not
Repaired
Secure and identify contents of compressed cylinders.
Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgement and against access by unauthorized personnel in accordance with Sections 5303.5.1 through 5303.5.3.
5303.5
Inspector Notes: Secure the compressed gas tank immediately for seismic reasons.
Will be rechecked on or after
11/12/2023
Violation found on
10/13/2023
Violation Not
Repaired
CA-37055 / 2099326 / 266276
LP-gas containers stored in buildings in accordance with Sections 6109.9 and 6109.11 shall not be located near exit access doors, exits, stairways or in areas normally used, or intended to be used, as a means of egress. 6109.4
Inspector Notes: LP-gas tanks shall not be stored near an exit. Remove the LP-gas tanks immediately. For outside storage, provide at least 5ft from a door or opening to a building, and at least 10ft from combustible materials.
Will be rechecked on or after
11/12/2023
Violation found on
10/13/2023
Violation Not
Repaired
CA-37055 / 2099326 / 266276
8130 ALLISON AVENUE LA MESA, CA 91942 TEL: 619.667.1177 FAX: 619.667.1380 Certificate of Occupancy Completion Items
In order to issue the final Certificate of Occupancy, the Charcoal House Restaurant completed the following remaining items to ensure they met all of the Building Division requirements in compliance with the California Building Code:
• Removed unauthorized vehicle signage at the entrance
• Provided maximum occupancy signs in the banquet hall and general dining area • Replaced electrical in the junction box located in the attic • Posted and stenciled no parking in the fire lane as per Heartland Fire • Removed the temporary storage container and construction material located at the rear of the building
The Charcoal House Restaurant worked with the Planning Division to meet all of the requirements of the building permit and CUP. To address all remaining Planning items, the applicant completed the following:
• Updated and removed parking lot signage for accuracy with the CUP • Painted the parapet wall addition to match the rest of the building • Removed the unpermitted roof sign
• Provided the façade detailing’s for the building, including the cornices and pilaster moldings and the lattices as noted on the South, East, and West Elevations
• Replaced and refreshed the approved landscaped areas
• Provided copies of security contracts and security guard cards, as required by Resolution No. PC 2022-06
• Provided a copy of the Western Towing Agreement
• Provided a copy of the Professional Valet Services Agreement
ATTACHMENT L
Heartland Fire & Rescue
8054 Allison Ave
La Mesa, CA 91942
Wednesday, 18 October, 2023
Attn: Chris Mittia
,
Property Address:
Charcoal House
9566 Murray Dr
La Mesa, CA 91942
Re: Re-inspection - Routine Fire Inspection on October 18 2023 You are hereby notified that a life and fire safety inspection of your property and/or premises located at the address listed above and has determined that no life or fire safety violations exist at this time.
On behalf of the Fire Chief , we would like to thank you for being fire safe in our community. It is everyone’s job to prevent fires and you have taken the first steps and/or actions to ensure we are protected from these potential hazards.
Thank you,
Inspector: Property Representative:
Deputy Fire Marshal Rachel Clarke
[email protected]
619-667-1470
CA-37055 / 2099839 / 266276
Charcoal House
Routine Fire Inspection
Inspection on October 18 2023
Violations repaired / total: 7 / 7
Violation/Information Page(s)
Inspection Violations
Hood cleaning service required.
Hoods, grease-removal devices, fans, ducts and other appurtenances shall be inspected at intervals specified in Table 606.3.3.1 or as approved by the fire code official. Inspections shall be completed by qualified individuals. 606.3.3.1
Inspector Notes: All the kitchen hoods must be cleaned by a professional in accordance with ANSI/IKECA C10 every three months. Provide proof of service immediately.
Violation found on
10/13/2023
Repaired on
10/13/2023
Repaint the faded fire lanes. NO PARKING FIRE LANE
Where required by the fire code official, approved signs or other approved notices or markings that include the words “NO PARKING—FIRE LANE” shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. The means by which fire lanes are designated shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility.
503.3
Inspector Notes: Signage and markings required to indicate fire lane. The signage must state the vehicle code reference.
Will be rechecked on or after
11/12/2023
Violation found on
10/13/2023
Repaired on
10/18/2023
CA-37055 / 2099839 / 266276
Provide documentation of annual service of the fire alarm system.
The building owner shall be responsible to maintain the fire and life safety systems in an operable condition at all times. Service personnel shall meet the qualification requirements of NFPA 72 for inspection, testing and maintenance of such systems.
Records of inspection, testing and maintenance shall be maintained. 907.8.4
Inspector Notes: Fire alarm systems must serviced annually. Provide proof of service immediately.
Will be rechecked on or after
11/12/2023
Violation found on
10/13/2023
Repaired on
10/18/2023
Inspection, testing, and maintenance required.
Fire protection and life safety systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection and life safety systems and equipment shall be inspected, tested and maintained or removed in accordance with Section 901.8.
All fire alarm systems, fire detection systems, automatic sprinkler or extinguishing systems, communication systems, and all other equipment, material or systems required by these regulations shall be maintained in an operable condition at all times in accordance with this code and California Code of Regulations, Title 19, Division 1. Upon disruption or diminishment of the fire protective qualities of such equipment, material or systems, immediate action shall be instituted to affect a reestablishment of such equipment, material or systems to their original normal and operational condition.
[California Code of Regulations, Title 19, Division 1, §1.14] Maintenance.
Every fire alarm system or device, sprinkler system, fire extinguisher, fire hose, fireresistive assembly or any other fire safety assembly, device, material or equipment installed and retained in service in any building or structure subject to California Code of Regulations, Title 19, Division 1 regulations shall be maintained in an operable condition at all times in accordance with California Code of Regulations, Title 19, Division 1 regulations and with their intended use. [California Code of Regulations, Title 19, Division 1, §3.24] Maintenance of Equipment.
All fire alarm systems, fire detection systems, automatic sprinkler or extinguishing systems, communication systems, and all other equipment, material or systems 901.6
CA-37055 / 2099839 / 266276
required by California Code of Regulations, Title 19, Division 1 shall be maintained in an operable condition at all times. Upon disruption or diminishment of the fire protective qualities of such equipment, material or systems, immediate action shall be instituted to affect a reestablishment of such equipment material or systems to their original normal and operational condition.
[California Code of Regulations, Title 19, Division 1, §904(a)] Required Inspection, Testing and Maintenance Frequencies.
1. (a) All automatic fire extinguishing systems, including systems installed as an alternate to other building requirements, shall be inspected, tested and maintained in accordance with the following frequencies. Local authorities may require more frequent inspection, testing and maintenance and additional procedures.
[California Code of Regulations, Title 19, Division 1, §904(a)(1)] Required Inspection, Testing and Maintenance Frequencies.
1. (1) Water-based fire protection systems shall be inspected, tested and maintained in accordance with the frequencies required by NFPA 25 (2011 edition) including Annexes A, B, C, D, E, F and G as amended by the State of California. (Published as NFPA 25, 2013 California Edition.) [California Code of Regulations, Title 19, Division 1, §904(b)] Required Inspection, Testing and Maintenance Frequencies.
1. (b) When proof of the installation date of standpipe systems or automatic fire sprinkler systems cannot be furnished, such systems shall receive initial testing and maintenance by July 1, 1985.
[California Code of Regulations, Title 19, Division 1, §904.2(a)] Testing and Maintenance Requirements.
1. (a) All testing and maintenance on automatic fire extinguishing systems in accordance with Health & Safety Code Section 13195 shall be performed by those licensed in accordance with Health and Safety Code Section 13196.5.
Exceptions:
1. (1) The State Fire Marshal may waive, in writing, licensing of fire departments which conduct fire sprinkler and standpipe system testing and maintenance.
2. (2) Service on fire alarm systems and industrial systems as specified in Health and Safety Code Sections 13196.5(b) and (c) may be conducted without a license.
3. (3) Testing and maintenance on automatic fire extinguishing systems exempted in writing by the State Fire Marshal, when the building owner or occupant has the staff and equipment to conduct testing and maintenance.
[California Code of Regulations, Title 19, Division 1, §904.2(b)] Testing and Maintenance Requirements.
CA-37055 / 2099839 / 266276
1. (b) Any testing and maintenance of automatic fire extinguishing systems shall be performed in accordance with these requirements.
Exceptions:
1. (1) The State Fire Marshal may waive, in writing, the requirement that testing and maintenance be performed in accordance with these requirements when a licensee can demonstrate that a system cannot functionally be tested and maintained in accordance with the California Code of Regulations, Title 19, Division 1, Chapter 5.
2. (2) If at any time a licensee encounters a specialized or modified system which cannot be tested and maintained in accordance with California Code of Regulations, Title 19, Division 1, Chapter 5, the licensee shall contact the State Fire Marshal and test and maintain the system as directed.
1. (A) The intent of this section is to cover automatic fire extinguishing systems as originally designed, installed and approved by the Authority Having Jurisdiction. It is not, however, intended to require that such systems be upgraded to current adopted standards.
[California Code of Regulations, Title 19, Division 1, §904.2(h)] Testing and Maintenance Requirements.
1. (h) At the time of testing and maintenance, building management shall be consulted to avoid unnecessary disturbance of normal building operation. [California Code of Regulations, Title 19, Division 1, §904.2(i)] Testing and Maintenance Requirements.
1. (i) The licensee shall contact the local fire authority having jurisdiction prior to testing and maintenance of a system when required by the local fire authority having jurisdiction to do so.
Inspector Notes: Fire sprinkler systems require annual service. Provide proof of service immediately.
Will be rechecked on or after
11/12/2023
Violation found on
10/13/2023
Repaired on
10/18/2023
CA-37055 / 2099839 / 266276
Ceiling and walls shall maintain fire integrity without holes or breaches.
Materials and firestop systems used to protect membrane and through penetrations in fire-resistance-rated construction and construction installed to resist the passage of smoke shall be maintained. The materials and firestop systems shall be securely attached to or bonded to the construction being penetrated with no openings visible through or into the cavity of the construction. Where the system design number is known, the system shall be inspected to the listing criteria and manufacturer’s installation instructions.
703.1
Inspector Notes: The penetration in the wall must be repaired immediately.
Will be rechecked on or after
11/12/2023
Violation found on
10/13/2023
Repaired on
10/18/2023
Secure and identify contents of compressed cylinders.
Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgement and against access by unauthorized personnel in accordance with Sections 5303.5.1 through 5303.5.3.
5303.5
Inspector Notes: Secure the compressed gas tank immediately for seismic reasons.
Will be rechecked on or after
11/12/2023
Violation found on
10/13/2023
Repaired on
10/18/2023
CA-37055 / 2099839 / 266276
LP-gas containers stored in buildings in accordance with Sections 6109.9 and 6109.11 shall not be located near exit access doors, exits, stairways or in areas normally used, or intended to be used, as a means of egress. 6109.4
Inspector Notes: LP-gas tanks shall not be stored near an exit. Remove the LP-gas tanks immediately. For outside storage, provide at least 5ft from a door or opening to a building, and at least 10ft from combustible materials.
Will be rechecked on or after
11/12/2023
Violation found on
10/13/2023
Repaired on
10/18/2023
CA-37055 / 2099839 / 266276