EXHIBIT B
Proposal Document
City of Norco
Bid Results for Project Norco Fire Station 47 HVAC Replacement (54303.15)Issued on 01/10/2026Bid Due on February 10, 2026 10:00 AM (PST)Exported on 02/17/2026Line Totals (Unit Price * Quantity)Item Num Description Unit of Measure Quantity
Allison Mechanical, Inc. - Unit Price
Allison Mechanical, Inc. - Line Total
Pacific West Industries Inc. - Unit Price
Pacific West Industries Inc. - Line Total
GK LUX GROUP HVAC INC -
Unit Price
GK LUX GROUP HVAC INC -
Line Total MEP Fusion - Unit Price MEP Fusion - Line Total 1 General: Mobilization LS 1 $10,000.00 $10,000.00 $5,000.00 $5,000.00 $5,000.00 $5,000.00 $3,500.00 $3,500.002 General: Provision and Administration of City of Norco Building Permits, Business License, Demolition Deposit, Disposal Fees, Inspections, Utility LS 1 $5,600.00 $5,600.00 $10,000.00 $10,000.00 $20,000.00 $20,000.00 $7,500.00 $7,500.00 3 General: Testing, Adjusting, and Balancing of air and Hydronic Systems, Verification of Final HVAC Operating Conditions, BIM Modelling for Clash Detection, and Commissioning Activities to Ensure Proper Functionality and LS 1 $35,000.00 $35,000.00 $30,000.00 $30,000.00 $10,000.00 $10,000.00 $87,000.00 $87,000.00 4 Remove Existing Roofing System to Install Beam from Roof as per Approved SF 120 $83.33 $9,999.60 $41.66 $4,999.20 $166.67 $20,000.40 $450.00 $54,000.00 5 Miscellaneous Minor Demolition LS 1 $5,000.00 $5,000.00 $2,500.00 $2,500.00 $5,000.00 $5,000.00 $7,800.00 $7,800.00 6 Install New Wood Beam, 4" x 12" Including Hoisting as per Approved LF 54 $138.89 $7,500.06 $185.18 $9,999.72 $185.19 $10,000.26 $550.00 $29,700.00 7 Infill/reframe Roof opening after Installation of Beam Including (E) Roof SF 135 $55.56 $7,500.60 $74.07 $9,999.45 $74.07 $9,999.45 $150.00 $20,250.00 8 Install Equipment Platform SF 24 $41.67 $1,000.08 $416.66 $9,999.84 $416.67 $10,000.08 $1,750.00 $42,000.00 9 Patch and Repair Refrigerant Piping thru Roof Penetration EA 2 $50.00 $100.00 $2,500.00 $5,000.00 $5,000.00 $10,000.00 $2,000.00 $4,000.00 10 Roofing System infill to Match Existing, LS 1 $100.00 $100.00 $2,500.00 $2,500.00 $10,000.00 $10,000.00 $5,750.00 $5,750.0011 Miscellaneous Caulking and Sealants LS 1 $500.00 $500.00 $2,500.00 $2,500.00 $5,000.00 $5,000.00 $5,000.00 $5,000.0012 Patch and Repair Wall Finishes where new Thermostat and Wiring is Installed EA 2 $250.00 $500.00 $2,500.00 $5,000.00 $2,500.00 $5,000.00 $750.00 $1,500.00 13 Demolition Work - Remove Existing Condensate Pipe Distribution LS 1 $500.00 $500.00 $2,500.00 $2,500.00 $5,000.00 $5,000.00 $2,500.00 $2,500.00 14 Demolition Work - Remove Existing Gas Pipe Distribution and Pipe Cap LS 1 $5,000.00 $5,000.00 $2,500.00 $2,500.00 $5,000.00 $5,000.00 $2,500.00 $2,500.00 15 Condensate Pipe Distribution - Install Condensate Drainpipe 3/4" LF 40 $125.00 $5,000.00 $250.00 $10,000.00 $250.00 $10,000.00 $875.00 $35,000.00 16 Valves - Install Shut Off Valve for Gas Pipe EA 7 $714.29 $5,000.03 $500.00 $3,500.00 $714.29 $5,000.03 $2,750.00 $19,250.00 17 Miscellaneous - Install Noise and Vibration Control, Firestopping, and Seismic Supports LS 1 $5,000.00 $5,000.00 $2,500.00 $2,500.00 $10,000.00 $10,000.00 $7,500.00 $7,500.00 18 Demolition Work - Demo of Existing AC Units LS 1 $5,000.00 $5,000.00 $2,500.00 $2,500.00 $20,000.00 $20,000.00 $8,500.00 $8,500.00 19 Demolition Work - Demo of Existing Fan Coil Units LS 1 $5,000.00 $5,000.00 $2,500.00 $2,500.00 $5,000.00 $5,000.00 $3,500.00 $3,500.00 20 Demolition Work - Demo of Existing Condensate Units LS 1 $5,000.00 $5,000.00 $2,500.00 $2,500.00 $10,000.00 $10,000.00 $2,500.00 $2,500.00 21 Demolition Work - Demo of Existing Duct Connections LS 1 $5,000.00 $5,000.00 $2,500.00 $2,500.00 $10,000.00 $10,000.00 $2,950.00 $2,950.00 22 Demolition Work - Demo of Existing Thermostats and Wiring LS 1 $5,000.00 $5,000.00 $2,500.00 $2,500.00 $5,000.00 $5,000.00 $2,500.00 $2,500.00 23 Demolition Work - Demo of Existing Refrigerant Pipes LS 1 $5,000.00 $5,000.00 $2,500.00 $2,500.00 $5,000.00 $5,000.00 $4,500.00 $4,500.00 24 Demolition Work - Demo of Existing AC curbs LS 1 $5,000.00 $5,000.00 $2,500.00 $2,500.00 $5,000.00 $5,000.00 $1,750.00 $1,750.00 25 Equipment - Procure and Install Packaged Heat Pump Unit - Heat Pump 3000 cfm EA 1 $15,000.00 $15,000.00 $25,000.00 $25,000.00 $25,000.00 $25,000.00 $18,500.00 $18,500.00 26 Equipment - Procure and Install Packaged Heat Pump Unit - Heat Pump 2000 cfm EA 2 $7,500.00 $15,000.00 $20,000.00 $40,000.00 $25,000.00 $50,000.00 $18,500.00 $37,000.00
27 Equipment - Procure and Install Packaged Heat Pump Unit - Heat Pump 1200 cfm EA 2 $7,500.00 $15,000.00 $15,000.00 $30,000.00 $25,000.00 $50,000.00 $18,500.00 $37,000.00 28 Equipment - Procure and Install Packaged Heat Pump Unit - Heat Pump 800 cfm EA 2 $7,500.00 $15,000.00 $13,000.00 $26,000.00 $25,000.00 $50,000.00 $18,500.00 $37,000.00 29 Equipment - Procure and Install 2 Ton Split System Outdoor Unit EA 2 $7,500.00 $15,000.00 $5,000.00 $10,000.00 $17,500.00 $35,000.00 $18,500.00 $37,000.00 30 Equipment - Procure and Install 2 Ton Split System Indoor Unit EA 2 $6,500.00 $13,000.00 $5,000.00 $10,000.00 $17,500.00 $35,000.00 $18,500.00 $37,000.00 31 Air Distribution - Procure and Install Ductwork, Galvanized Steel LB 388 $30.93 $12,000.84 $77.32 $30,000.16 $103.10 $40,002.80 $110.00 $42,680.00 32 Air Distribution - Duct Insulation, Wrap SF 171 $29.24 $5,000.04 $29.24 $5,000.04 $58.48 $10,000.08 $90.00 $15,390.0033 Air Distribution - Install Existing Duct Connection for New Heat Pump Units EA 7 $714.29 $5,000.03 $1,000.00 $7,000.00 $714.29 $5,000.03 $1,750.00 $12,250.00 34 Air Distribution - Procure and Install Refrigerant Pipe LF 70 $71.43 $5,000.10 $35.71 $2,499.70 $285.72 $20,000.40 $100.00 $7,000.00 35 Air Distribution - Procure and Install Duct Silencers LS 1 $100.00 $100.00 $2,500.00 $2,500.00 $5,000.00 $5,000.00 $7,500.00 $7,500.00 36 HVAC Controls - Procure and Install Head end Equipment/Software/Programing/Controls Distribution LS 1 $100.00 $100.00 $20,000.00 $20,000.00 $5,000.00 $5,000.00 $18,500.00 $18,500.00 37 HVAC Controls - Procure and Install CO2 Sensors LS 1 $5,000.00 $5,000.00 $2,500.00 $2,500.00 $5,000.00 $5,000.00 $1,850.00 $1,850.00 38 Procure and Install Rigging LS 1 $5,000.00 $5,000.00 $28,000.00 $28,000.00 $5,000.00 $5,000.00 $3,500.00 $3,500.0039 Procure and Install Seismic Bracing LS 1 $1,000.00 $1,000.00 $2,500.00 $2,500.00 $2,500.00 $2,500.00 $4,500.00 $4,500.00 40 Procure and Install Zone Dampers EA 2 $2,500.00 $5,000.00 $5,000.00 $10,000.00 $1,250.00 $2,500.00 $1,950.00 $3,900.0041 Procure and Install Bypass Damper EA 1 $1,000.00 $1,000.00 $5,000.00 $5,000.00 $5,000.00 $5,000.00 $750.00 $750.0042 Procure and Install Room Sensors EA 2 $2,500.00 $5,000.00 $2,500.00 $5,000.00 $2,500.00 $5,000.00 $850.00 $1,700.0043 Procure and Install Penetrations and Fire Stopping LS 1 $1,000.00 $1,000.00 $2,500.00 $2,500.00 $5,000.00 $5,000.00 $850.00 $850.00 44 Demolition Work- Safe-off/ Misc. Systems Identification/ Labelling LS 1 $1,000.00 $1,000.00 $5,000.00 $5,000.00 $5,000.00 $5,000.00 $2,500.00 $2,500.00 45 Service & Distribution Equipment - Procure and Install 400 amps circuit breaker EA 1 $7,500.00 $7,500.00 $5,000.00 $5,000.00 $5,000.00 $5,000.00 $2,950.00 $2,950.00 46 Service & Distribution Equipment - Procure and Install 400 amps panel board, 208Y/120V, 3Ph, 4W EA 1 $9,000.00 $9,000.00 $10,000.00 $10,000.00 $5,000.00 $5,000.00 $2,950.00 $2,950.00 47 Service & Distribution Equipment - Procure and Install 400 amps Feeder LF 50 $150.00 $7,500.00 $100.00 $5,000.00 $120.00 $6,000.00 $50.00 $2,500.00 48 HVAC and Equipment Connections - Procure and Install Heat Pump Unit Connection EA 7 $785.71 $5,499.97 $2,000.00 $14,000.00 $571.43 $4,000.01 $1,100.00 $7,700.00 49 HVAC and Equipment Connections - Procure and Install Condensing Unit Connection EA 2 $2,750.00 $5,500.00 $2,500.00 $5,000.00 $2,250.00 $4,500.00 $950.00 $1,900.00 50 HVAC and Equipment Connections - Procure and Install Fan Coil Unit Connection EA 2 $2,750.00 $5,500.00 $2,500.00 $5,000.00 $2,750.00 $5,500.00 $1,100.00 $2,200.00 51 HVAC and Equipment Connections - Disconnect switch, 100/3 fused EA 1 $5,500.00 $5,500.00 $5,000.00 $5,000.00 $7,000.00 $7,000.00 $850.00 $850.00 52 HVAC and Equipment Connections - Disconnect switch, 60/3 fused EA 6 $916.67 $5,500.02 $2,500.00 $15,000.00 $500.00 $3,000.00 $500.00 $3,000.00 53 HVAC and Equipment Connections - Disconnect switch, 30/3 fused EA 7 $785.71 $5,499.97 $2,500.00 $17,500.00 $428.57 $2,999.99 $750.00 $5,250.00 54 HVAC and Equipment Connections - Procure and Install 100 amps feeder LF 184 $29.89 $5,499.76 $54.35 $10,000.40 $38.04 $6,999.36 $50.00 $9,200.00 55 HVAC and Equipment Connections - Procure and Install 60 amps feeder LF 735 $7.48 $5,497.80 $40.82 $30,002.70 $8.16 $5,997.60 $75.00 $55,125.00 56 HVAC and Equipment Connections - Procure and Install 30 amps feeder LF 890 $6.18 $5,500.20 $33.71 $30,001.90 $5.00 $4,450.00 $60.00 $53,400.00 57 HVAC and Equipment Connections - Procure and Install 25 amps feeder reconnection LF 60 $91.67 $5,500.20 $166.66 $9,999.60 $66.67 $4,000.20 $50.00 $3,000.00
58 Procure and Install Firestopping, Seismic Bracing/Miscellaneous Supports LS 1 $2,000.70 $2,000.70 $5,000.00 $5,000.00 $4,000.00 $4,000.00 $5,500.00 $5,500.00 59 Electrical Temporary Power/Lighting LS 1 $2,000.00 $2,000.00 $60,000.00 $60,000.00 $6,000.00 $6,000.00 $8,500.00 $8,500.00 Subtotal $360,500.00 $631,002.71 $654,450.69 $851,345.00Total $360,500.00 $631,002.71 $654,450.69 $851,345.00
PROJECT SCOPE
PROJECT DIRECTORY
REGIONAL MAP N.T.S.
REPLACEMENT OF 7 ROOFTOP AC UNITS AND 2 DUCTLESS SPLIT SYSTEMS.
OWNER - REPRESENTATIVE
CITY OF NORCO
PHONE: (951) 270-5633
PROJECT CONTACT: AMANDA HAMILTONEMAIL: [email protected] 2870 CLARK AVE
NORCO, CA 92860
PROJECT ADDRESS:
3902 HILLSIDE AVENUE, NORCO, CA 92860
APPLICABLE CODES
1. 2022 BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1, TITLE 24 C.C.R.
2. 2022 CALIFORNIA BUILDING CODE (CBC),PART 2, TITLE 24 C.C.R. (IBC WITH AMENDMENTS)
3. 2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R. (NEC WITH AMENDMENTS)
4. 2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R. (UMC WITH AMENDMENTS)
5. 2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R. (UPC WITH AMENDMENTS)
6. 2022 CALIFORNIA FIRE CODE, PART 9, TITLE 24 C.C.R. (IFC WITH AMENDMENTS)
7. 2022 CALIFORNIA REFERENCED STANDARDS, PART 12, TITLE 24 C.C.R.
8. TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS.9. 2022 CALIFORNIA ENERGY CODE (PART 6, TITLE 24 C.C.R.)
10. 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CGBSG), PART 11, TITLE 24 C.C.R.11. 2021 INTERNATIONAL BUILDING CODE (IBC)12. 2021 INTERNATIONAL MECHANICAL CODE (IMC)13. 2021 INTERNATIONAL PLUMBING CODE (IPC) NORCO FIRE STATION 47
HVAC REPLACEMENT
NORTH
PLUMBING ENGINEER
DESIGN WEST ENGINEERING412 E. VANDERBILT WAY
SAN BERNARDINO, CA 92408
(909) 890-3700 FAX (909) 890-3770
PROJECT CONTACT: RUDY PARAMOEMAIL: [email protected]
MECHANICAL ENGINEER
DESIGN WEST ENGINEERING412 E. VANDERBILT WAY
SAN BERNARDINO, CA 92408
(909) 890-3700 FAX (909) 890-3770
PROJECT CONTACT: RUDY PARAMOEMAIL: [email protected]
ELECTRICAL ENGINEER
DESIGN WEST ENGINEERING412 E. VANDERBILT WAY
SAN BERNARDINO, CA 92408
(909) 890-3700 FAX (909) 890-3770
PROJECT CONTACT: ARCADIO NUNGARAY
EMAIL: - SITE MAP N.T.S.
NORTH
EMAIL: [email protected]
SITE SITE
STRUCTURAL ENGINEER
T&B ENGINEERING, INC4344 LATHAM ST., SUITE 210
RIVERSIDE, CA 92501
(951) 684-6200 FAX (951) 684-6226
PROJECT CONTACT: RAYMUNDO LOZANOEMAIL: [email protected] DESIGNED BYDRAWN BYCHECKED BYDATESCALEJOB NO.
SHEET NO.
DATE BY ISSUE FOR
SM/ACSM/AC
RP
07.26.2024
24-146
ISSUE DATE:REVISION:
NUM. DATE BY REVISION FOR
CONSULTANT
3902 HILLSIDE AVENUE
NORCO, CA 92860
STAMP
San Bernardino, CA 92408
412 E. Vanderbilt Way Phone: 909-890-3700
Fax: 909-890-3770
Email: [email protected]
SHEET TITLEPROJECT TITLE
AS NOTED
R:\_PROJECT\2024\24-146 NORCO FIRE STATION 47 HVAC REPLACEMENT\_CAD\COVER TEMPLATE - 2025-07-26 - RUDY PARAMO NORCO FIRE STATION 47 HVAC
REPLACEMENT
ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED TO BE USED IN
CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYINGSPECIFICATIONS WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING. 1234567
07-17-2025 DWE PC CORRECTIONS
TITLE SHEET
T-0.1
PROJECT SHEET INDEX
SHEET NUMBER SHEET TITLE
T-0.1 TITLE SHEET
MP-0.1 MECHANICAL PLUMBING LEGENDS NOTES & SCHEDULES
MP-0.2 MECHANICAL PLUMBING SCHEDULES CONT.MP-0.3 ENERGY COMPLIANT DOCUMENTSMP-0.4 ENERGY COMPLIANT DOCUMENTS MP-1.1 MECHANICAL PLUMBING DEMO PLAN
MP-1.2 MECHANICAL PLUMBING DEMOLITION ROOF PLAN
MP-2.1 MECHANICAL PLUMBING PLANMP-3.1 MECHANICAL PLUMBING ROOF PLANMP-4.1 MECHANICAL PLUMBING DETAILS E-0.1 ELECTRICAL LEGENDS & NOTES
E-0.2 SINGLE LINE DIAGRAM & PANEL SCHEDULES
E-1.1 ELECTRICAL DEMOLITION PLAN
E-1.2 ELECTRICAL DEMOLITION ROOF PLAN
E-2.1 ELECTRICAL POWER PLANE-3.1 ELECTRICAL ROOF PLANE-4.1 ELECTRICAL DETAILS S0.1 GENERAL NOTES & DETAILSS2.1 ROOF FRAMING PLAN
SIGNED:07/26/2025
REVIEWED FOR CODE COMPLIANCE BY:
WILLDAN ENGINEERING
1:59:38 PM Jul 31, 2025
Approval of these plans & specifications shallnot be construed to be a permit for, or anapproval of any violation of any Federal, State,County or City laws or ordinances. One set ofapproved plans must be kept on the job untilcompletion.
MECHANICAL BASIS OF DESIGN MECHANICAL GENERAL NOTES
A. OUTDOOR DESIGN CONDITIONS:
1. SUMMER: 105°F DB/69°F WB
2. WINTER: 29°F
B. DESIGN CONDITIONS:
C. HVAC CONTROL METHOD:
1. (E) PROGRAMMABLE WIFI ENABLED STAND ALONG THERMOSTAT
2. PROGRAMMABLE WIFI ENABLED STAND ALONG THERMOSTAT
D. CALIFORNIA VENTILATION CRITERIA:
1. COMPLY WITH CALIFORNIA BUILDING ENERGY EFFICIENCY STANDARD.
A. GREATER OF 15 CFM/PERSON OR 0.15 CFM/SF
E. EXHAUST TO OUTDOORS (MINIMUM RATES)
1. RESTROOMS: 75 CFM/(WC or U)
F. BUILDING ENVELOPE:
1. REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR ENVELOPE REQUIREMENTS
2. ALL ENVELOPE COMPONENTS SHALL MEET CALIFORNIA ENERGY CODE MINIMUM PRESCRIPTIVE CRITERIA.
G. DUCTWORK DESIGN CRITERIA (MAXIMUM ALLOWABLE AIR PRESSURE DROPS AND AIR VELOCITIES) TO MEET HIGH EFFICIENCY OPERATION WITH MINIMAL ACOUSTICAL NOISE. DUCT STATIC PRESSURE FRICTION LOSS SHALL NOT EXCEED 0.2” PER 100 FEET IN MECHANICAL ROOMS AND SHAFTS. LOW PRESSURE SUPPLY AND EXHAUST DUCT STATIC PRESSURE FRICTION LOSS BASED ON A MAXIMUM OF 0.08” PER 100 FEET. LOW PRESSURE RETURN DUCT STATIC PRESSURE FRICTION LOSS BASED ON AMAXIMUM OF 0.05” PER 100 FEET. MEDIUM PRESSURE DUCTWORK SHALL NOT EXCEED MAXIMUM VELOCITY AS LISTED BELOW.
1. IN ADDITION, MAXIMUM SUPPLY, RETURN AND EXHAUST DUCT AIR FLOW VELOCITIES, REGARDLESS OF PRESSURE DROP, SHALL NOT EXCEED THE FOLLOWING CRITERIA:
A. MAINS ABOVE CEILING: 1750 FPM
B. MAINS ABOVE OPEN OCCUPIED SPACES: 1450 FPM
C. BRANCHES ABOVE CEILING: 1400 FPM
D. BRANCHES ABOVE OPEN OCCUPIED SPACES: 1150 FPME. RUN-OUTS TO DIFFUSERS: 725 FPMF. IN SHAFTS: 2500 FPM G. IN MECHANICAL ROOMS: 3000 FPM
H. ACOUSTICAL
1. THE FOLLOWING NOISE NC/RC CRITERIA LEVELS WILL BE DESIGNED AS DEFINED IN THE ASHRAE HVAC APPLICATIONS HANDBOOK. THESE LEVELS ADDRESS THE MECHANICAL SYSTEMS ONLY. ACTUAL SOUND PERFORMANCEREQUIREMENTS FOR EACH SPACE MUST BE VERIFIED WITH ACOUSTICAL CONSULTANT.
A. CORRIDORS AND LOBBIES: 40
B. OFFICES: 30
I. SEISMIC:
1. ANCHORAGE AND RESTRAINTS ARE A DEFERRED SUBMITTAL BY THE CONTRACTOR AND MUST BE COORDINATED WITH STRUCTURAL ENGINEER AND AUTHORITY HAVING JURISDICTION.
15 SF/OCC
N/A
100 SF/OCC
N/A
0.85 W/SF
0.7 W/SF 74°F +/- 2°F
74°F +/- 2°F
N/A N/A
50%
50%
70°F +/- 2°F
70°F +/- 2°F
N/A 90°F MAX N/A N/A N/A
OFFICE
LOBBY
ELECTRICAL
ROOM
DATA/
TELECOM
OCC
DENSITY
LIGHTING
DENSITY
COOLING
TEMPERATURE
HEATING
TEMPERATURE
RELATIVE
HUMIDITY
OCCUPANT
SPACE
VENTILATION
PER
OCCUPANT
78°F MAX N/A
15 CFM/OCC
15 CFM/OCC
N/A
ANCHORAGE AND BRACING NOTES
PIPES, DUCTS AND CONDUITS SHALL BE SUPPORTED AND BRACED PER THE 2008 SMACNA "GUIDELINES FOR SEISMIC RESTRAINTS OF MECHANICAL SYSTEMS AND PLUMBING SYSTEMS", THE "SUPERSTRUT SEISMIC RESTRAINT SYSTEM" FOR PIPES AND CONDUITS ONLY.
1. COND
A
P-1
SHEET No.
STACK/RISER
DETAIL No.
ID. No.EQUIPMENTID. No.
COND
UP
DN
FU
IE
NO
NC
GR
H.C.
FLR.BEL.
CONN
CONT
CLG.
ABV.
W/
V.T.R.
TYP.
CFMS
CFM
CFMR
(N)
CFME
30X10
(E) OR EXIST.
M
10Ø
SECTION REFERENCEDETAIL REFERENCEEQUIPMENT REFERENCEPLUMBING STACK OR RISER REFERENCE
CONDENSATE DRAIN
PIPE DOWNPIPE UP
CAP ON END OF PIPE
PIPE RISER (UP AND DOWN)BELOWCONTINUATIONCONNECTIONCEILINGABOVEINVERT ELEVATIONNORMALLY CLOSEDNORMALLY OPENGRADEHANDICAPPEDFLOORVENT THROUGH ROOF
WITHTYPICALPLUMBING FIXTURE UNITCFM EXHAUSTCFM RETURNCFM SUPPLYEXISTINGINDICATES SQUARE DUCT (INCHES)CUBIC FEET OF AIR PER MINUTENEWMOTORIZED DAMPERINDICATES ROUND DUCT (INCHES)
HVAC AND PLUMBING LEGEND
SYMBOL ABBREVIATIONS
CDCR
MVD
T'STAT
SFD
T
P.O.C
P.O.D.
DESCRIPTION
FLEXIBLE DUCTSECTION THROUGH DUCTCEILING DIFFUSER, SUPPLYEXIST. DUCT OR EQUIP. TO REMAINCEILING REGISTER, RETURN & EXHAUSTEXIST. DUCT OR EQUIP. TO BE REMOVEDSQ., RECT. OR ROUND DUCT AS NOTEDDUCT DOWNTHERMOSTATDUCT WITH TURNING VANESDUCT ACCESS DOORCOMBINATION SMOKE/FIRE DAMPERMANUAL VOLUME DAMPERSQUARE TO ROUND TRANSITIONPOINT OF DEMOLITIONPOINT OF CONNECTIONREFRIGERANT LINES DX DX
PLUMBING GENERAL NOTES
PIPE MATERIAL SCHEDULE
CONDENSATE COPPER L TUBE SOLDERED BRONZE 125 N/A
PIPE MATERIAL
& WEIGHT
TYPE OF
JOINTS
PRESSURE
FITTINGS
MATERIAL
SHUT-OFF
RATINGS PSI
- SwP
SERVICE VALVE
PIPE INSULATION SCHEDULE
INSULATION
MEAN RATING
TEMPERATURE
(°F)
< 1 1 to < 1.5 1.5 to < 4 4 to < 8 8 and larger
CONDUCTIVITY
RANGE
(IN BTU-IN/HR
PER SQFT/°F)
FLUID
TEMPERATURE
RANGE
(°F)
SPACE HEATING, HOT WATER SYSTEMS (STEAM, STEAM CONDENSATE AND HOT WATER) AND SERVICE WATER HEATING SYSTEMS 150°
2.5 2.5 3.0 3.0
201° - 250° 0.27 - 0.30
125°
1.5 2.0 2.0 2.0
141° - 200° 0.25 - 0.29
100°
1.0 105° - 140° 0.22 - 0.28
Space cooling systems (chilled water, refrigerant and brine) 40° - 60° 0.21 - 0.27 75° 1.0 1.0 1.0
BELOW 40° 0.20 - 0.26 50° R-8.5 R-12 R-10 R-9
NOTE: WHERE INSULATED PIPING IS EXPOSED OUTDOORS, IT SHALL BE COVERED. COVER OUTDOOR EXPOSED INSULATED PIPING WITH
0.016 INCH THICK CORRUGATED ALUMINUM JACKET. PROVIDE VALVE STEM EXTENSIONS SUCH THAT INSULATION IS NOT DAMAGED
WHEN VALVE IS CYCLED
NONRES
0.5 RES
0.75 NONRES
0.5 RES
0.75 REQUIRED INSULATION THICKNESS (IN.)
PIPE SIZE (IN. DIA.)
INCHES
R-VALUE
INCHES
R-VALUE
INCHES
R-VALUE
1.51.5 2.5
R-21 R-20 R-17.5 R-17 R-14.5
R-11.5 R-11 R-14 R-11 R-10
R-7.7 R-12.5 R-11 R-9 R-8
INCHES
R-VALUE
INCHES
R-VALUE R-14
1.0 1.5 1.5 1.5 1.5
NONRES
R-3
RES
R-6
NONRES
R-3
RES
R-5
R-7 R-6 R-5
2.0 2.0 2.0
1. THE TOTAL INSTALLATION SHALL COMPLY WITH ANY REQUIREMENTS OF THE LEGALLY CONSTITUTED AUTHORITIES HAVING JURISDICTION INCLUDING 2022 CBC (CALIFORNIA BUILDING CODE), 2022 CAL GREEN REQUIREMENTS AND 2022 CMC/CPC (CALIFORNIA MECHANICAL AND PLUMBING CODE).
2. VISIT THE SITE PRIOR TO BID AND SHALL THOROUGHLY FAMILIARIZE THEMSELVES WITH THE EXISTING CONDITIONS UNDER WHICH THEY WILL BE REQUIRED TO WORK. INDICATED DIMENSIONS ARE APPROXIMATE AND ARE GIVEN FOR ESTIMATE PURPOSES ONLY.
3. BEFORE PROCEEDING WITH THE WORK CAREFULLY CHECK AND VERIFY DIMENSIONS, SIZES, REQUIRED CLEARANCES AND
SHALL ASSUME FULL RESPONSIBILITY FOR THE FITTING OF EQUIPMENT AND MATERIALS HEREIN REQUIRED TO OTHER PARTS OF THE WORK OF OTHER TRADES.
4. THE DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC TO THE EXTENT THAT OFFSETS, BENDS, SPECIAL FITTINGS AND LOCATIONS ARE NOT EXACTLY LOCATED. IN THE PREPARATION OF THESE DOCUMENTS, CERTAIN ASSUMPTIONS ARE MADEREGARDING EXISTING CONDITIONS. SOME OF THESE ASSUMPTIONS MAY NOT BE VERIFIABLE WITHOUT EXPENDING
ADDITIONAL SUMS OF MONEY OR DESTROYING OTHERWISE ADEQUATE OR SERVICEABLE PORTIONS OF EXISTING BUILDINGS AND/OR EQUIPMENT. THEREFORE, THE ENGINEER SHALL NOT BE HELD RESPONSIBLE FOR ANY CHANGES OR ADDITIONAL COSTS INCURRED DUE TO EXISTING CONDITIONS.
5. ITEMS RELATED TO PLUMBING UTILITIES AND/OR OTHER SERVICE(S); MATERIALS, LABOR, PERMITS, FEES, ETC., SHALL BE VERIFIED WITH THE RESPECTIVE SERVING UTILITY COMPANY PRIOR TO SUBMISSION OF A BID. THE ACT OF SUBMITTING A
BID SHALL CONSTITUTE FULL RESPONSIBILITY TO INSTALL SERVICE(S) IN COMPLIANCE WITH THE REQUIREMENTS OF THE SERVING UTILITY COMPANY AND THE MECHANICAL ENGINEER. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CHARGES LEVIED BY THE SERVING UTILITY COMPANY EXCEPTING THE FIRST BILLING DEPOSIT.
6. COMPLY WITH CONTRACT DOCUMENTS IN LAYING OUT THEIR WORK AND EQUIPMENT. THEY SHALL COORDINATE THE WORK OF THIS SECTION WITH THE WORK OF OTHER TRADES AND JOB CONDITIONS.
7. THE INSTALLATION OF ACCESS PANELS OR OTHER INDICATING EQUIPMENT OR SPECIALTIES REQUIRING READING,
ADJUSTMENT, INSPECTION, REPAIRS, REMOVAL OR REPLACEMENT SHALL BE CONVENIENTLY LOCATED WITH REFERENCE TO THE FINISHED BUILDING.
8. EQUIPMENT AND FIXTURES INSTALLED UNDER THIS CONTRACT SHALL BE HUNG OR ANCHORED IN ACCORDANCE WITH 2022 CPC/CBC.
9. THE INTENT OF THE DRAWINGS AND SPECIFICATIONS IS TO CONSTRUCT THE PROJECT IN ACCORDANCE WITH TITLE 24, CALIFORNIA CODE OF REGULATIONS.
10. WHERE MATERIAL IS SHOWN ON THE DRAWINGS BUT NOT SPECIFIED, IT SHALL BE OF THE SAME TYPE AND QUALITY AS EXISTING MATERIAL.
11. TEST SYSTEM(S) IN ACCORDANCE WITH REQUIREMENTS OF THE GOVERNING AUTHORITIES.12. PAVED AREAS WHICH ARE EXCAVATED AND/OR DAMAGED BY OPERATIONS SHALL BE PATCHED AND REPAIRED. IN ADDITION, RESTORE TO ORIGINAL CONDITION PLANTED AREAS DAMAGED BY OPERATIONS.
13. CONNECTIONS TO EXISTING SERVICES SHALL BE MADE SUCH THAT INTERRUPTION TIME WILL BE AS SHORT AS POSSIBLE.
THE CONTRACTOR SHALL GIVE THE OWNERS REPRESENTATIVE SUFFICIENT NOTICE OF SUCH INTERRUPTIONS AND THE ACTUAL SHUT-DOWN TIME SHALL BE AT A TIME DESIGNATED BY THE OWNERS REPRESENTATIVE.
14. PLUMBING PIPE, FITTINGS AND FIXTURES USED TO CONVEY OR DISPENSE WATER FOR HUMAN CONSUMPTION SHALL COMPLY WITH AB 1953.
15. ANY SUBSTITUTION MADE BY THAT IS DIFFERENT FROM WHAT IS SPECIFIED ON THE DRAWINGS SHALL BE CLEARLY INDICATED ON THE SUBMITTAL AS TO THAT IS BEING SUBSTITUTED.
1. THE TOTAL INSTALLATION SHALL COMPLY WITH ANY REQUIREMENTS OF THE LEGALLY CONSTITUTED AUTHORITIES HAVING JURISDICTION INCLUDING 2022 CBC (CALIFORNIA BUILDING CODE), 2022 CMC/CPC (CALIFORNIA MECHANICAL AND PLUMBING CODE), 2022 CAL GREEN REQUIREMENTS AND THE 2022 TITLE 24 ENERGY CODE.
2. CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID AND SHALL THOROUGHLY FAMILIARIZE THEMSELVES WITH THE EXISTING CONDITIONS UNDER WHICH HE WILL BE REQUIRED TO WORK.
3. INDICATED DIMENSIONS ARE APPROXIMATE AND ARE GIVEN FOR ESTIMATE PURPOSES ONLY. BEFORE PROCEEDING WITH
THE WORK CAREFULLY CHECK AND VERIFY DIMENSIONS, SIZES, REQUIRED CLEARANCES AND SHALL ASSUME FULL
RESPONSIBILITY FOR THE FITTING OF EQUIPMENT AND MATERIALS HEREIN REQUIRED TO OTHER PARTS OF THE WORK OF OTHER TRADES. DUCT DIMENSIONS SHOWN ON PLANS ARE NET INSIDE CLEAR.
4. THE DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC TO THE EXTENT THAT OFFSETS, BENDS, SPECIAL FITTINGS AND LOCATIONS ARE NOT EXACTLY LOCATED. DUCTWORK DIMENSIONS SHOWN ON THE DRAWINGS ARE NET INSIDE DIMENSIONS.DO NOT FABRICATE DUCTWORK FROM THESE DRAWINGS. THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR SUPPLYING SHOP DRAWINGS WHICH REFLECT THE PROPOSED INSTALLATION. THE SHOP DRAWINGS MUST BE APPROVED BY THE ENGINEER PRIOR TO ANY SHEET METAL FABRICATION. THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING
ACCURATE AS-BUILT DRAWINGS AT THE COMPLETION OF THE PROJECT AND SUBMITTING THEM TO THE ENGINEER AND OWNER.
5. IN THE PREPARATION OF THESE DOCUMENTS, CERTAIN ASSUMPTIONS ARE MADE REGARDING EXISTING CONDITIONS. SOME OF THESE ASSUMPTIONS MAY NOT BE VERIFIABLE WITHOUT EXPENDING ADDITIONAL SUMS OF MONEY OR DESTROYINGOTHERWISE ADEQUATE OR SERVICEABLE PORTIONS OF EXISTING BUILDINGS AND/OR EQUIPMENT. THEREFORE, THE
ENGINEER SHALL NOT BE HELD RESPONSIBLE FOR ANY CHANGES OR ADDITIONAL COSTS INCURRED DUE TO EXISTING CONDITIONS.
6. CONTRACTOR SHALL COMPLY WITH CONTRACT DOCUMENTS IN LAYING OUT THEIR WORK AND EQUIPMENT. THEY SHALL COORDINATE THE WORK OF THIS SECTION WITH THE WORK OF OTHER TRADES AND JOB CONDITIONS.
7. THE INSTALLATION OF ACCESS PANELS OR OTHER INDICATING EQUIPMENT OR SPECIALTIES REQUIRING READING,
ADJUSTMENT, INSPECTION, REPAIRS, REMOVAL OR REPLACEMENT SHALL BE CONVENIENTLY LOCATED WITH REFERENCE TO THE FINISHED BUILDING.
8. WHERE MATERIAL IS SHOWN ON THE DRAWINGS BUT NOT SPECIFIED, IT SHALL BE OF THE SAME TYPE AND QUALITY AS EXISTING MATERIAL.
9. PROVIDE MANUAL VOLUME DAMPERS AT UPSTREAM PORTION OF TERMINAL AIR BRANCHES. THESE SHALL BE OF THE LOCKING QUADRANT TYPE. WHERE LOCATED OVER SLOPED OR HARD CEILINGS, PROVIDE DURO-DYNE ANGLE GEAR DRIVE OR BOWDEN CABLE CONTROL SYSTEM OR PROVIDE UNITED ENERTECH POWER/BALANCE SYSTEM. REMOTE PLATE LOCATIONS TO BE LOCATED AS DETERMINED BY ARCHITECT.
10. PROVIDE MINIMUM 1" ACOUSTICAL LINING IN DUCTWORK WITHIN 10 FEET OF AIR MOVING EQUIPMENT. PROVIDE DURO-DYNE FLEXIBLE CONNECTION AT DUCT AT EQUIPMENT LOCATIONS.
11. DUCTS IN AN UNCONDITIONED SPACE OR EXTERIOR DUCT WORK SHALL HAVE A MIN. OF R-8 INSULATION. DUCTS WITHIN THE CONDITIONED ENVELOPE ABOVE A CEILING SHALL HAVE A MIN. OF R-4.2 INSULATION. EXTERIOR DUCTWORK SHALL NOT HAVE INSULATION EXPOSED TO THE ENVIRONMENT.
12. WHERE NOT SPECIFICALLY INDICATED OTHERWISE, DUCTWORK AND EQUIPMENT SHALL BE SUPPORTED PER THE SMACNA GUIDELINES FOR SEISMIC RESTRAINT AND CURRENT APPLICABLE UNIFORM MECHANICAL CODE.
13. WHEN A FIRE ALARM SYSTEM WITH FULL COVERAGE SMOKE DETECTORS ARE PROVIDED, DUCT SMOKE DETECTORS MAY BE ELIMINATED. FIRE ALARM CONTRACTOR SHALL WIRE SMOKE/FIRE DAMPER ACTIVATORS TO AREA SMOKE DETECTORS.
14. TESTING, ADJUSTING, AND BALANCING (TAB) OF THE AIR CONDITIONING SYSTEMS AND RELATED ANCILLARY EQUIPMENT WILL BE PERFORMED BY A CERTIFIED, INDEPENDENT THIRD PARTY, AABC AGENCY PROCURED BY THE MECHANICAL CONTRACTOR.
A COMPLETE AIR BALANCE REPORT TO BE SUBMITTED TO THE ADMINISTRATIVE AUTHORITY AND TO THE MECHANICAL ENGINEER AND APPROVED PRIOR TO FINAL PAYMENT.
AFTER COMPLETION OF WORK, TESTS ON THE HVAC SYSTEMS, INCLUDING A DUCT LEAKAGE TEST AND AN AIR BALANCE PERFORMANCE TEST, SHALL BE PERFORMED IN ACCORDANCE WITH AN APPROVED METHOD PER CMC 314.1.
15. AIR HANDLING DUCT SYSTEMS SHALL BE CONSTRUCTED, INSTALLED AND INSULATED AS PROVIDED IN CHAPTER 6 OF 2019 CMC.
16. MATERIALS EXPOSED WITHIN DUCTS OR PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL HAVE FLAME SPREAD INDEX NOT GREATER THAN 25 AND A SMOKE DEVELOPED INDEX NOT GREATER THAN 50 (2019 CMC SECTION 602.2).
17. DUCTWORK SHALL BE HARD DUCT. FLEXIBLE AIR DUCTS AND CONNECTORS SHALL BE NOT MORE THAN 5' IN LENGTH AND SHALL NOT BE USED IN LIEU OF RIDGED ELBOWS OR FITTINGS. FLEXIBLE AIR DUCTS SHALL BE PERMITTED TO BE USED AS AN ELBOW AT A TERMINAL DEVICE (SEC 603.4.1 CMC).
18. ANY SUBSTITUTION MADE THAT IS DIFFERENT FROM WHAT IS SPECIFIED ON THE DRAWINGS SHALL BE CLEARLY INDICATED ON THE SUBMITTAL AS TO THAT IS BEING SUBSTITUTED.
19. THERMOSTATS SHALL COMPLY WITH THE 2022 ENERGY COMMISSION AND SHALL BE WIFI ENABLED.
20. AT THE TIME OF ROUGH INSTALLATION, OR DURING STORAGE ON THE CONSTRUCTION SITE AND UNTIL FINAL STARTUP OF
THE HEATING AND COOLING EQUIPMENT, DUCT AND OTHER RELATED AIR DISTRIBUTION COMPONENT OPENINGS SHALL BE
COVERED WITH TAPE, PLASTIC, SHEET METAL OR OTHER METHODS ACCEPTABLE TO THE ENFORCING AGENCY TO REDUCE THE AMOUNT OF DUST OR DEBRIS WHICH MAY COLLECT IN THE SYSTEM.
21. WHERE MORE THAN ONE HEATING, COOLING, VENTILATING, OR REFRIGERATING SYSTEM IS INSTALLED ON THE ROOF OF A
BUILDING OR WITHIN A BUILDING, IT SHALL BE PERMANENTLY IDENTIFIED AS TO THE AREA OR SPACE SERVED BY THE EQUIPMENT. (CMC 303.6) PROVIDE PERMANENT LABELING AND IDENTIFICATION FOR HVAC UNIT (SINGLE SYSTEM OR MULTIPLE) AND THERMOSTATS. IDENTIFICATION FOR THE THERMOSTATS SHALL CORRELATE TO THE HVAC UNIT THAT IT SERVES.
22. AIR CONDITIONING REFRIGERATION SERVICE PORTS LOCATED OUTDOORS SHALL BE FITTED WITH LOCKING TYPE TAMPER
RESISTANT CAP OR SHALL BE PROTECTED FROM UNAUTHORIZED ACCESS BY A MEANS ACCEPTABLE TO THE BUILDING DEPARTMENT PER CMC SECTION 1105.11.
APPLICABLE CODES
1. 2022 BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1, TITLE 24 C.C.R.
2. 2022 CALIFORNIA BUILDING CODE (CBC),PART 2, TITLE 24 C.C.R. (IBC WITH AMENDMENTS)
3. 2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R. (NEC WITH AMENDMENTS)
4. 2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R. (UMC WITH AMENDMENTS)
5. 2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R. (UPC WITH AMENDMENTS)6. 2022 CALIFORNIA FIRE CODE, PART 9, TITLE 24 C.C.R. (IFC WITH AMENDMENTS)
7. 2022 CALIFORNIA REFERENCED STANDARDS, PART 12, TITLE 24 C.C.R.
8. 2022 TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS.9. 2022 CALIFORNIA ENERGY CODE (PART 6, TITLE 24 C.C.R.)
10. 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CGBSG), PART 11, TITLE 24 C.C.R.
CAL GREEN GENERAL NOTES
1. AT THE TIME OF ROUGH INSTALLATION, OR DURING STORAGE ON THE CONSTRUCTION SITE AND UNTIL FINAL
STARTUP OF THE HEATING AND COOLING EQUIPMENT, ALL DUCT AND OTHER RELATED AIR DISTRIBUTION
COMPONENT OPENINGS SHALL BE COVERED WITH TAPE, PLASTIC, SHEET METAL OR OTHER METHODS
ACCEPTABLE TO THE ENFORCING AGENCY TO REDUCE THE AMOUNT OF DUCT OR DEBRIS WHICH MAY COLLECT IN THE SYSTEM.
2. ADHESIVES, SEALANTS, AND CAULKS USED ON THE PROJECT SHALL MEET THE REQUIREMENTS OF THE FOLLOWING STANDARDS:
A. ADHESIVES, ADHESIVE BONDING PRIMERS, ADHESIVE PRIMERS, SEALANTS, SEALANTS PRIMERS AND
CAULKS SHALL COMPLY WITH LOCAL OR REGIONAL AIR POLLUTION CONTROL OR AIR QUALITY MANAGEMENT DISTRICT RULES WHERE APPLICABLE, OR SCAQMD RULE 1168 VOC LIMITS, AS SHOWN IN TABLES 5.504.4.1 AND 5.504.4.2. SUCH PRODUCTS ALSO SHALL COMPLY WITH THE RULE 1168 PROHIBITION
ON THE USE OF CERTAIN TOXIC COMPOUNDS (CHLOROFORM, ETHYLENE, DICHLORIDE, ETHYLENECHLORIDE, PERCHLOROETHYLENE, AND TRICHLOROETHYLENE), EXCEPT FOR AEROSOL PRODUCTS AS SPECIFIED IN SUBSECTION 2 BELOW.
B. AEROSOL ADHESIVE, AND SMALLER UNIT SIZES OF ADHESIVES, AND SEALANT OR CAULKING COMPOUNDS (IN UNITS OF PRODUCT, LESS PACKAGING, WHICH DO NOT WEIGH MORE THAN ONE POUND AND DO NOT CONSIST OF MORE THAN 16 FLUID OUNCES) SHALL COMPLY WITH STATEWIDE VOC STANDARDS ANDOTHER REQUIREMENTS, INCLUDING PROHIBITIONS ON USE OF CERTAIN TOXIC COMPOUNDS, OFCALIFORNIA CODE OF REGULATIONS, TITLE 17 COMMENCING WITH SECTION 94507.
3. IN MECHANICALLY VENTILATED BUILDINGS, PROVIDE REGULARLY OCCUPIED AREAS OF THE BUILDING WITH AIR
FILTRATION MEDIA FOR OUTSIDE AND RETURN AIR THAT PROVIDES AT LEAST A MINIMUM EFFICIENCY REPORTING VALUE (MERV) OF 13. MERV 13 FILTERS SHALL BE INSTALLED PRIOR TO OCCUPANCY, ANDRECOMMENDATIONS FOR MAINTENANCE WITH FILTERS OF THE SAME VALUE SHALL BE INCLUDED IN THE OPERATIONS AND MAINTENANCE MANUAL.
EXCEPTIONS:
C. AN ASHRAE 10-PERCENT TO 15-PERCENT EFFICIENCY FILTER SHALL BE PERMITTED FOR AN HVAC UNIT MEETING THE 2022 CALIFORNIA ENERGY CODE HAVING 60,000 BTU/H OR LESS CAPACITY PER FAN COIL, IF THE ENERGY USE OF THE AIR DELIVERY SYSTEM IS 0.4 W/CFM OR LESS AT DESIGN AIR FLOW.
D. EXISTING MECHANICAL EQUIPMENT.
5.504.5.3.1 LABELING, INSTALLED FILTERS SHALL BE CLEARLY LABELED BY THE MANUFACTURER INDICATING MERV RATING.
4. BUILDINGS SHALL MEET OR EXCEED THE PROVISIONS OF CALIFORNIA BUILDING CODE, CCR, TITLE 24, PART 2, SECTIONS 1203 (VENTILATION) AND CHAPTER 14 (EXTERIOR WALLS). FOR CONDITIONAL MEASURES NOT APPLICABLE TO LOW RISE RESIDENTIAL OCCUPANCIES, SEE SECTION 5.407.2 OF THIS CODE.
5. FOR MECHANICALLY OR NATURALLY VENTILATED SPACES IN BUILDINGS, MEET THE MINIMUM REQUIREMENTS OF SECTION 120.1 (REQUIREMENTS FOR VENTILATION) OF THE 2022 CALIFORNIA ENERGY CODE, OR THE APPLICABLE LOCAL CODE, WHICHEVER IS MORE STRINGENT, AND THE DIVISION 1, CHAPTER 4 OF CCR, TITLE 8.
6. INSTALLATIONS OF HVAC, REFRIGERATION EQUIPMENT SHALL COMPLY WITH 5.508.1.1 AND 5.508.1.2, ADDRESSING THAT ALL REFRIGERATION IN HVAC EQUIPMENT SHALL NOT CONTAIN CFCS AND/OR HALONS.
REFRIGERANT PIPE MATERIAL SCHEDULE
REFRIGERATION PIPE
SIZES 1/4"
TO 3/4" (OD)
SERVICE
NITROGENIZED
ACR-ANNEALED COPPER
TYPE "K"
BRAZED
FLARE
COPPER TYPE "K"
BRASS 700 PSI
BALL
SOLENOID
TXV
REFRIGERATION PIPE
SIZES 7/8"
TO 1-5/8" (OD)
NITROGENIZED
ACR-DRAWN TEMPER
COPPER TYPE "K"
BRAZED
FLARE
COPPER TYPE "K"
BRASS 700 PSI
BALL
SOLENOID
TXV
PIPE MATERIAL JOINT TYPES FITTINGS MATERIAL VALVE TYPES PRESSURE RATING
1. THE CALIFORNIA ENERGY CODE SECTION 10-103 REQUIRES ACCEPTANCE TESTING ON ALL NEWLY INSTALLED LIGHTING CONTROLS, MECHANICAL SYSTEMS, ENVELOPES, AND PROCESS EQUIPMENT AFTER INSTALLATION AND BEFORE PROJECT COMPLETION. AN ACCEPTANCE
TEST IS A FUNCTIONAL PERFORMANCE TEST TO HELP ENSURE THAT THE NEWLY INSTALLED EQUIPMENT IS OPERATING AND IN COMPLIANCE WITH THE ENERGY CODE.
2. LIGHTING CONTROLS ACCPETANCE TESTS MUST BE PERFOMED BY A CERTIFIED LIGHTING CONTROLS ACCEPTANCE TEST TECHNICIAN (ATT).
3. MECHANCIAL SYSTEM ACCEPTANCE TESTS MUST BE PERFORMED BY A CERTIFIED MECHANICAL ATT FOR PROJECTS SUBMITTED ON OR AFTER OCTOBER 1, 2021.
4. ENVELOPE AND PROCESS EQUIPMENT ACCEPTANCE TESTS SHALL BE PERFORMED BY THE INSTALLING CONTRACTOR, ENGINEER/ARCHITECT OR RECORD OF THE OWNER'S AGENT.
5. A LISTING OF CERTIFIED ATT CAN BE FOUND AT:
HTTPS://WWW.ENERGY.CA.GOV/PROGRAMS-AND-TOPICS/PROGRAMS/ACCEPTANCE-TEST-TECHNICIAN-CERTIFICATION-PROVIDERPROGRAM/ACCEPTANCE
6. THE ACCEPTANCE TESTING PROCEDURES MUST BE REPLACED, AND DEFICIENCIES MUST BE CORRECTED BY THE BUILDER OR INSTALLING CONTRACTOR UNTIL THE CONSTRUCTION/INSTALLATION OF THE SPECIFIC SYSTEM CONFORM AND PASS THE REQUIRED ACCEPTANCECRITERIA. PROJECT INSPECTORS WILL COLLECT THE FORMS TO CONFIRM THAT THE REQUIRED ACCEPTANCE TESTS HAVE BEEN COMPLETED.
TITLE 24 PERFORMANCE TESTING NOTES
DD DUCT SMOKE DETECTOR
UP TO 12"
19" TO 30"13" TO 18"
DUCT SIZE GAUGE TRANSVERSE JOINTDUCT SIZE TRANSVERSE JOINT
PER SMACNA
UP TO 9"
14" TO 18"10" TO 14"
2" SLIP
BRACINGBRACING
31" TO 42"43" TO 54"
GAUGE
282628
18" TO 24" 26
NOTE:
LOW PRESSURE DUCT CONSTRUCTION: GAUGES, TRANSVERSE JOINTS, SPACING OF JOINTS AND INTERMEDIATEBRACING SHALL BE AS TABULATED ABOVE, IN WHICH TRANSVERSE JOINTS ARE SHOWN SS FOR S-STOP, DS FOR DRIVE SLIP, PS FOR POCKET SLIP, AND BS FOR BAR SLIP, PS AND BS LAPPED AND RIVETED AT CORNERS. INTERMEDIATE BRACING WHERE SHOWN MAY BE OMITTED IF DUCT SECTIONS OF FOUR FEET (4'-0") OR LESS ARE USED. MAXIMUM SPACING OF BRACING - FOUR FEET (4'-0")
PER SMACNAPER SMACNAPER SMACNAPER SMACNA
PER SMACNAPER SMACNAPER SMACNAPER SMACNAPER SMACNA
PER SMACNAPER SMACNAPER SMACNAPER SMACNAPER SMACNA
2" SLIP2" SLIP2" SLIP
RECTANGULAR DUCT
ROUND
DUCT GAUGE SCHEDULE
PER SMACNAPER SMACNAPER SMACNAPER SMACNA
DESIGNED BYDRAWN BYCHECKED BYDATESCALEJOB NO.
SHEET NO.
DATE BY ISSUE FOR
SM/ACSM/AC
RP
07.26.2024
24-146
ISSUE DATE:REVISION:
NUM. DATE BY REVISION FOR
CONSULTANT
3902 HILLSIDE AVENUE
NORCO, CA 92860
STAMP
San Bernardino, CA 92408
412 E. Vanderbilt Way Phone: 909-890-3700
Fax: 909-890-3770
Email: [email protected]
SHEET TITLEPROJECT TITLE
AS NOTED
R:\_PROJECT\2024\24-146 NORCO FIRE STATION 47 HVAC REPLACEMENT\_CAD\24-146 MP-FRONT - 2025-07-26 - RUDY PARAMO NORCO FIRE STATION 47 HVAC
REPLACEMENT
ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED TO BE USED IN
CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYINGSPECIFICATIONS WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING. 1234567
07-17-2025 DWE PC CORRECTIONS
MECHANICAL PLUMBING
LEGENDS NOTES &
SCHEDULES
MP-0.1
MECHANICAL SHEET INDEX
SHEET NUMBER SHEET TITLE
MP-0.1 MECHANICAL PLUMBING LEGENDS NOTES & SCHEDULES
MP-0.2 MECHANICAL PLUMBING SCHEDULES CONT.MP-0.3 ENERGY COMPLIANT DOCUMENTSMP-0.4 ENERGY COMPLIANT DOCUMENTS MP-1.1 MECHANICAL PLUMBING DEMO PLAN
MP-1.2 MECHANICAL PLUMBING DEMOLITION ROOF PLAN
MP-2.1 MECHANICAL PLUMBING PLANMP-3.1 MECHANICAL PLUMBING ROOF PLANMP-4.1 MECHANICAL PLUMBING DETAILS 1 1
SIGNED:07/26/2025
REVIEWED FOR CODE COMPLIANCE BY:
WILLDAN ENGINEERING
1:59:42 PM Jul 31, 2025
Approval of these plans & specifications shallnot be construed to be a permit for, or anapproval of any violation of any Federal, State,County or City laws or ordinances. One set ofapproved plans must be kept on the job untilcompletion.
YES
PACKAGE HEAT PUMP UNIT SCHEDULE
208-3-60 MERV 13 R-454B
VERTICAL
SUPPLY &
RETURN
ECON/PE 191
UNIT: 606
CURB: N/A
TOTAL: 797
AC
1 CARRIER
50GEQM06A2A5-0A0A0 ROOM 146 THRU 154 2,288 DIRECT 1 MP-4.1 1.22 285 450 82.5 65.2 56.8 55.8 52.55 56.37 16.0 SEER2 60.8 18.8 38.45 7.2 HSPF2 4.9 KW 7.7 16.7 208-3-60 1 NOTES:
SECONDARY HEAT AMPS INCLUDED IN UNIT ELECTRICAL
ECONOMIZER OUTSIDE AIR TEMPERATURE SENSOR TO BE LOCATED AWAY FROM DIRECT SUNLIGHT.ECONOMIZER TO BE CONTROLLED BY DIFFERENTIAL OUTSIDE AIRPOWER EXHAUST TO RECEIVE SEPARATE POWERMICROMETL MODULATING ECONOMIZER AND MODULATING POWER EXHAUST 234
HINGED ACCESS DOORSMICROMETL 14" TALL RIGID CURB
56 YES MERV 13 SUPPLY &
RETURN
ECON/PE 259
UNIT: 836
CURB: N/A
TOTAL: 1,095
AC
2 CARRIER
50GEQM08A2A5-0A0A0
ROOM 136, 138,
139,141,142,143,145 1.14 1,630 DIRECT 1.48 250 600
81.8 65.1
54.8 54.7 82.85 92.21 12.2 EER 17.0 IEER 61.8 20.9 64.11 3.6 HIGH COP 2.3 LOW COP 8.2 26.6 NO MERV 13 R-454B SUPPLY &
RETURN
ECON 50PE 75
UNIT: 382
CURB: 16
TOTAL: 523
AC
3 ROOM 137 & 140 800 DIRECT 0.39 70 150
81.4 65.0
60.0 57.3 17.90 19.11 62.3 17.4 14.51 14.6 12.9
MERV 13 R-454B SUPPLY &
RETURN
ECON/PE 191
UNIT: 606
CURB: N/A
TOTAL: 797
AC
4 ROOM 101 THRU 105,
129, 169 DIRECT 195 400
81.8 65.1
56.7 55.6 51.25 56.27 61.8 18.7 38.29 7.7 16.7
MERV 13 R-454B SUPPLY &
RETURN
ECON/PE 191
UNIT: 577
CURB: N/A
TOTAL:
AC
5 ROOM 106, 107, 108,
110,113,115,119 0.84 1,920 DIRECT 0.49 165 250
82.0 65.1
58.1 56.0 29.31 32.82 61.5 17.8 21.90 12.9 16.7 768
YES MERV 13 R-454B SUPPLY &
RETURN
ECON 50PE 75
UNIT: 382
ADAP CURB: 16
TOTAL:
AC
6 ROOM 111, 112, 121
THRU 125 0.74 800 DIRECT 0.39 90 200
83.3 65.3
60.0 57.5 19.40 19.40 59.8 17.4 14.57 14.6 12.9 523
YES MERV 13 R-454B SUPPLY &
RETURN
ECON/PE 225
UNIT: 577
CURB: 98
TOTAL:
AC
7 ROOM 114, 116, 117,
118, 120, 122 DIRECT 145 275
82.6 65.2
58.2 56.1 29.95 32.88 60.6 17.9 21.98 12.9 16.7 900
CARRIER
50NR-B24---3
CARRIER
50GEQM04A2A5-0A0A0 1,200
818
1,200
2,0002,000
818
3,000
HORIZONTAL DISCHARGE
VERTICAL DISCHARGE
7 VERTICALVERTICALVERTICALVERTICALVERTICAL
HORIZONTAL
1.14 7.8 KW
3.8 KW 4.9 KW 4.9 KW 3.8 KW
4.9 KW
0.74 15.2 SEER2 7.2 HSPF2
0.84 2,114 0.96 16.0 SEER2 7.2 HSPF2
16.0 SEER2 6.7 HSPF2 15.2 SEER2 7.2 HSPF2
208-3-60208-1-60208-3-60208-3-60208-1-60
0.9 1,936 0.50 6.7 HSPF2 208-3-60
8 COMPLETE WITH LOW AMBIENT ACCESSORIES.
DUCTLESS MINI-SPLIT SCHEDULE
INDOOR UNIT
OUTDOOR UNIT
ROOM 109 N/A NO
24.0 29.0 208-1-60 10.4 HSPF2 22.7 SEER2 11.8 EER2 105.0 69.0 155 3/8"
5/8" 705 35
INDOOR UNIT POWERED THRU OUTDOOR UNIT.
COMPLETE WITH 24V INTERFACE KIT (KSAIC0301230)
FC
1 FC
1 CU
1 12
3 1
2 CARRIER TOSHIBA
RAV-HB241KRTP-UL
NOTES:
4 MP-4.1
3 4 PROVIDE CONDENSATE PUMP, HMAX TATTOO 16
4 27.0
5 PROVIDE HARD-WIRED T-24 COMPLIANT T-STAT.
5 ROOM 130 N/A NO 35 705 FC
2 5
MP-4.1 3 4 5
24.0 29.0 208-1-60
105.0
69.0 FC
2 CU
2 27.0 1
208-3-60
1.0 2,000
3,000
208-1-60 0.5 800
0.5 1,200 YES
YES
3 MP-4.1
2 MP-4.1
1 MP-4.1
1 MP-4.1
2 MP-4.1
11 MP-4.1
CARRIER
50GEQM06A2A5-0A0A0
CARRIER
50NR-B24---3
CARRIER
50GEQM04A2A5-0A0A0 16.0 SEER2
CARRIER TOSHIBA
RAV-BP241AT2P-UL
3/8"
5/8"
2 22
22.7 SEER2
11.8 EER2 10.4 HSPF2 155 4 MP-4.1
5 MP-4.1
208-3-60 1.0 2,000
1.0 208-1-60 0.5 800208-3-60208-3-60 0.5 1,200
REUSING EXISTING CURBREUSING EXISTING T-STATMICROMETL ADAPTER KIT
THE EXISTING DUCT SMOKE DETECTOR (DD) IN THE EXISTING MAIN SUPPLY AIR DUCT IS TO REMAIN IN PLACE. INTERLOCK WITH THE NEW UNIT FOR AUTOMATIC SHUTDOWN.
9 10
1 3
1 2 3 4 5 8 9 10
11 1 2 3 4 5 8 9 10
1 2 3 4 5 8 9 10 111 2 3 4 5 8 9 10 111 2 3 4 5 8 9 101 2 3 4 5 8 9 101 2 3 4 5 6 7 9 10 MIN.
CFM SETTINGS
ZONE DAMPER & BYPASS SCHEDULE
ZD
1-1
MODEL NO.
MFR. & REMARKS
AC-1 10" 575
AREA SERVED
ZD
1-2
BP
1 SERVED BY
CARRIER
35JN10
MAX.
165
TAG
450 1,425
OPR.WT (LBS)
ANCHORAGE
DETAIL
REFERENCE
1,0541,021
16 x 14 2,000 METALAIRE SR-502D 615 1,400
INLET
SIZE (IN)
AIR SPEED
(FPM)
PROVIDE CARRIER SPACE SENSOR
ROOM 146 & 147
ROOM 149, 150,
151, 146
N/A
16"
20 AC1
AC-1
13 MP-4.1
36 N/A
PROVIDE CARRIER SPACE SENSOR
CARRIER
35JN16
13 MP-4.1
13 MP-4.1
12 12
12 1212
1212
N/A
R-454B
CARRIER TOSHIBA
RAV-BP241AT2P-UL
CARRIER TOSHIBA
RAV-HB241KRTP-UL
R454BR454BR454BR454B
47.0 MCA
50.0 MOCP
40.0 MCA
40.0 MOCP
40.0 MCA
40.0 MOCP
39.0 MCA
45.0 MOCP
39.0 MCA
45.0 MOCP
47.0 MCA
50.0 MOCP
8.0 MCA
14.4 MOCP
70.0 MCA
70.0 MOCP
8.0 MCA
14.4 MOCP
8.0 MCA
14.4 MOCP
7.1 MCA
12.8 MOCP
7.1 MCA
12.8 MOCP
4.9 MCA
8.8 MOCP
4.9 MCA
8.8 MOCP
33.7756.32
13.58 33.63
19.27 13.81
19.34 17.0 MCA
25.0 MOCP
17.0 MCA
25.0 MOCP
DESIGNED BYDRAWN BYCHECKED BYDATESCALEJOB NO.
SHEET NO.
DATE BY ISSUE FOR
SM/ACSM/AC
RP
07.26.2024
24-146
ISSUE DATE:REVISION:
NUM. DATE BY REVISION FOR
CONSULTANT
3902 HILLSIDE AVENUE
NORCO, CA 92860
STAMP
San Bernardino, CA 92408
412 E. Vanderbilt Way Phone: 909-890-3700
Fax: 909-890-3770
Email: [email protected]
SHEET TITLEPROJECT TITLE
AS NOTED
R:\_PROJECT\2024\24-146 NORCO FIRE STATION 47 HVAC REPLACEMENT\_CAD\24-146 MP-FRONT - 2025-07-26 - RUDY PARAMO NORCO FIRE STATION 47 HVAC
REPLACEMENT
ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED TO BE USED IN
CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYINGSPECIFICATIONS WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING. 1234567
07-17-2025 DWE PC CORRECTIONS
MECHANICAL PLUMBING
SCHEDULES CONT.
MP-0.2
1 1
1 1
1 1
1 1 1 1 1 1 1 1
1 1 1
1 1
SIGNED:07/26/2025
REVIEWED FOR CODE COMPLIANCE BY:
WILLDAN ENGINEERING
1:59:42 PM Jul 31, 2025
Approval of these plans & specifications shallnot be construed to be a permit for, or anapproval of any violation of any Federal, State,County or City laws or ordinances. One set ofapproved plans must be kept on the job untilcompletion.
DESIGNED BY
DRAWN BYCHECKED BYDATESCALEJOB NO.
SHEET NO.
DATE BY ISSUE FOR
SM/ACSM/AC
RP
07.26.2024
24-146
ISSUE DATE:REVISION:
NUM. DATE BY REVISION FOR
CONSULTANT
3902 HILLSIDE AVENUE
NORCO, CA 92860
STAMP
San Bernardino, CA 92408
412 E. Vanderbilt Way Phone: 909-890-3700
Fax: 909-890-3770
Email: [email protected]
SHEET TITLEPROJECT TITLE
AS NOTED
R:\_PROJECT\2024\24-146 NORCO FIRE STATION 47 HVAC REPLACEMENT\_CAD\24-146 MP-FRONT - 2025-07-26 - RUDY PARAMO NORCO FIRE STATION 47 HVAC
REPLACEMENT
ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED TO BE USED IN
CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYINGSPECIFICATIONS WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING. 1234567
07-17-2025 DWE PC CORRECTIONS
ENERGY COMPLIANT
DOCUMENTS
MP-0.3
SIGNED:07/26/2025
REVIEWED FOR CODE COMPLIANCE BY:
WILLDAN ENGINEERING
1:59:42 PM Jul 31, 2025
Approval of these plans & specifications shallnot be construed to be a permit for, or anapproval of any violation of any Federal, State,County or City laws or ordinances. One set ofapproved plans must be kept on the job untilcompletion.
DESIGNED BY
DRAWN BYCHECKED BYDATESCALEJOB NO.
SHEET NO.
DATE BY ISSUE FOR
SM/ACSM/AC
RP
07.26.2024
24-146
ISSUE DATE:REVISION:
NUM. DATE BY REVISION FOR
CONSULTANT
3902 HILLSIDE AVENUE
NORCO, CA 92860
STAMP
San Bernardino, CA 92408
412 E. Vanderbilt Way Phone: 909-890-3700
Fax: 909-890-3770
Email: [email protected]
SHEET TITLEPROJECT TITLE
AS NOTED
R:\_PROJECT\2024\24-146 NORCO FIRE STATION 47 HVAC REPLACEMENT\_CAD\24-146 MP-FRONT - 2025-07-26 - RUDY PARAMO NORCO FIRE STATION 47 HVAC
REPLACEMENT
ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED TO BE USED IN
CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYINGSPECIFICATIONS WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING. 1234567
07-17-2025 DWE PC CORRECTIONS
ENERGY COMPLIANT
DOCUMENTS
MP-0.4
SIGNED:07/26/2025
REVIEWED FOR CODE COMPLIANCE BY:
WILLDAN ENGINEERING
1:59:42 PM Jul 31, 2025
Approval of these plans & specifications shallnot be construed to be a permit for, or anapproval of any violation of any Federal, State,County or City laws or ordinances. One set ofapproved plans must be kept on the job untilcompletion.
DEMO EXISTING FAN COIL. REPLACE EXISTING REFRIGERANT PIPING WITH NEW. REUSE EXISTING CONDENSATE PUMP. DISCONNECT ANDRECONNECT CONDENSATE PIPING.
DEMO EXISTING THERMOSTAT AND REPLACE WITH NEED. REPLACE EXISTING WIRING.
DEMO EXISTING DUCTWORK UP TO P.O.D.EXISTING DUCT DETECTOR TO REMAIN. SEE ELECTRICAL PLANS FOR RE-CONNECTION TO NEW HVAC UNITS.
1234
156 157
155
152 153 154
147
148
145
149 150 151
146
140 137
135
134
138 133
143
142
139
141
136
132
131
127
128
101
130
129
169
102
104 103
105
106
107
108
109
110
111
112
124
123
125
122
121
120
119 118
113 117
114
115
116
126
T
(E) AC-7
T
(E) AC-5
T
(E) AC-6
(E) FC-1 T
(E) FC-1
T
(E) AC-4
(E) FC-2
T
(E) FC-2
T
(E) AC-1
T
(E) AC-2
T
(E) AC-3
T
(E) EF-24
S
(E) DD
(E) DD
(E) DD
(E) DD
(E) DD
(E) DD
(E) EF-15
(E) EF-17
(E) EF-16
(E) EF-24
(E) EF-10
(E) EF-11
(E) EF-7
(E) EF-8
(E) EF-9
(E) EF-18(E) EF-19
(E) EF-20
(E) EF-21
(E) EF-22
(E) EF-6
(E) EF-23
(E) EG
(E) EG (E) EG
(E) EG
(E) EF-13
(E) EF-12
(E) EG
(E) EF-14
T
(E) EF-14
1 1
(E) 6" Ø
(E) 12" Ø
(E) 8" Ø
(E) 7" Ø
(E) 12" Ø
(E) 6" Ø
(E) 8x8 CD
75 CFM
(E) 8x8 CD
100 CFM
(E) 8x8 CD
75 CFM
(E) 8x8 CD
75 CFM
(E) 24x24 CR
325 CFM
2 2 (E) 16" Ø
(E) 14" Ø
(E) 18" Ø
3 3
3 4
4 4
4 4
MECHANICAL PLUMBING DEMOLITION PLAN 1
DESIGNED BYDRAWN BYCHECKED BYDATESCALEJOB NO.
SHEET NO.
DATE BY ISSUE FOR
SM/ACSM/AC
RP
07.26.2024
24-146
ISSUE DATE:REVISION:
NUM. DATE BY REVISION FOR
CONSULTANT
3902 HILLSIDE AVENUE
NORCO, CA 92860
STAMP
San Bernardino, CA 92408
412 E. Vanderbilt Way Phone: 909-890-3700
Fax: 909-890-3770
Email: [email protected]
SHEET TITLEPROJECT TITLE
AS NOTED
R:\_PROJECT\2024\24-146 NORCO FIRE STATION 47 HVAC REPLACEMENT\_CAD\24-146 MP-FLRPLN - 2025-07-26 - RUDY PARAMO NORCO FIRE STATION 47 HVAC
REPLACEMENT
ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED TO BE USED IN
CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYINGSPECIFICATIONS WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING. 1234567
07-17-2025 DWE PC CORRECTIONS
GENERAL NOTES
DEMOLITION NOTES
MECHANICAL PLUMBING
DEMO PLAN
MP-1.1
SCALE: 1/8" = 1'-0"
1 1
1 1
1 1
SIGNED:07/26/2025
REVIEWED FOR CODE COMPLIANCE BY:
WILLDAN ENGINEERING
1:59:42 PM Jul 31, 2025
Approval of these plans & specifications shallnot be construed to be a permit for, or anapproval of any violation of any Federal, State,County or City laws or ordinances. One set ofapproved plans must be kept on the job untilcompletion.
DEMO EXISTING AC UNIT. EXISTING ROOF CURB TO REMAIN AND REUSE.
DEMO EXISTING GAS PIPING UP TO P.O.D. AND CAP. PROVIDE SHUT-OFF VALVE UPSTREAM OF CAP.
DEMO EXISTING CONDENSATE PIPING UP TO P.O.D. PREPARE EXISTINGPIPING TO CONNECT WITH NEW UNIT.DEMO EXISTING AC UNIT AND ROOF CURB. EXISTING PENETRATION TOREMAIN AND REUSE.
EXISTING TO REMAIN.
DEMO EXISTING CONDENSING UNIT. REPLACE EXISTING REFRIGERANTPIPING WITH NEW. REUSE EXISTING PENETRATION ON ROOF. EXISTINGPLATFORM TO REMAIN AND REUSE. 123456
(E) AC-2
(E) AC-1
(E) AC-3 (E) EF-2
(E) AC-6
(E) AC-7
(E) AC-5
(E) AC-4
(E) CU-2
(E) CU-1
(E) EF-4(E) EF-5
(E) EF-1
(E) EF-3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
1 2 3
2 3 4
5 5
5 5
5 6
6 (E) VENT
(E) VENT
(E) VENT
(E) VENT
(E) FLUE
(E) VENT
(E) VENT
(E) VENT
(E) FLUE
(E) VENT
(E) VENT
(E) GAS
(E) COND
(E) COND
(E) COND
(E) GAS
(E) GAS
(E) GAS
(E) COND
(E) COND
(E) COND
(E) GAS
(E) GAS
(E) GAS
(E) ROOF ACCESS
HATCH 30"x36"
(E) ROOF ACCESS
HATCH 30"x36"
5 5
MECHANICAL PLUMBING DEMOLITION ROOF PLAN 1
DESIGNED BYDRAWN BYCHECKED BYDATESCALEJOB NO.
SHEET NO.
DATE BY ISSUE FOR
SM/ACSM/AC
RP
07.26.2024
24-146
ISSUE DATE:REVISION:
NUM. DATE BY REVISION FOR
CONSULTANT
3902 HILLSIDE AVENUE
NORCO, CA 92860
STAMP
San Bernardino, CA 92408
412 E. Vanderbilt Way Phone: 909-890-3700
Fax: 909-890-3770
Email: [email protected]
SHEET TITLEPROJECT TITLE
AS NOTED
R:\_PROJECT\2024\24-146 NORCO FIRE STATION 47 HVAC REPLACEMENT\_CAD\24-146 MP-ROOF - 2025-07-26 - RUDY PARAMO NORCO FIRE STATION 47 HVAC
REPLACEMENT
ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED TO BE USED IN
CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYINGSPECIFICATIONS WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING. 1234567
07-17-2025 DWE PC CORRECTIONS
GENERAL NOTES
DEMOLITION NOTES
MECHANICAL PLUMBING
DEMOLITION ROOF PLAN
MP-1.2
SCALE: 1/8" = 1'-0"
1 1
SIGNED:07/26/2025
REVIEWED FOR CODE COMPLIANCE BY:
WILLDAN ENGINEERING
1:59:42 PM Jul 31, 2025
Approval of these plans & specifications shallnot be construed to be a permit for, or anapproval of any violation of any Federal, State,County or City laws or ordinances. One set ofapproved plans must be kept on the job untilcompletion.
9 MP-4.1
1 REVISE CFM PER PLAN.
3/8" & 5/8" REFRIGERANT UP THRU ROOF
PROVIDE NEW THERMOSTAT AND WIRING.
CONNECT NEW DUCTWORK TO EXISTING. REWORK EXISTING DUCT AS REQUIRED TO MAKE THE NEW CONNECTION. VERIFY EXISTING SIZE AND LOCATION IN FIELD.
234
157 156
155
152 153 154
147
148
145
149 150 151
146
140 137
135
134
138 133
143
142
139
141
136
132
131
127
128
101
130
129
169
102
104 103
105
106
107
108
109
110
111
112
124
123 125
122
121
120
119 118
113 117
114
115
116
126
T
(E) AC-7
T
(E) AC-5
T
(E) AC-6
T
FC-1
T
(E) AC-4
T
FC-2
T
(E) AC-1
T
(E) AC-2
T
(E) AC-3
T
(E) EF-24
S
FC
1 FC
2 (E) DD
(E) DD
(E) DD
(E) DD
(E) DD
(E) DD
(E) EF-15
(E) EF-17
(E) EF-16
(E) EF-24
(E) EF-10
(E) EF-11
(E) EF-7
(E) EF-8
(E) EF-9
(E) EF-18(E) EF-19
(E) EF-20
(E) EF-21
(E) EF-22
(E) EF-6
(E) EF-23
(E) EG
(E) EG (E) EG
(E) EG
(E) EF-13
(E) EF-12
(E) EG
(E) EF-14
T
(E) EF-14
(E) 6" Ø
(E) 12" Ø
(E) 8" Ø
(E) 7" Ø
(E) 6" Ø
(E) 8x8 CD
50 CFM
(E) 8x8 CD
75 CFM
(E) 8x8 CD
100 CFM
(E) 8x8 CD
100 CFM
1 1
1 1
(E) 24x24 CR
375 CFM 1
2 2
3 3
(E) 8x8 CD
150 CFM
(E) 8x8 CD
150 CFM
(E) 8x8 CD
100 CFM
(E) 8x8 CD
75 CFM
(E) 24x24 CR
425 CFM
(E) 8x8 CD
150 CFM
(E) 8x8 CD
150 CFM
(E) 14x14 CD
400 CFM
(E) 14x14 CD
400 CFM
(E) 10x10 CD
400 CFM
(E) 8x8 CD
125 CFM
(E) 8x8 CD
125 CFM
(E) 8x8 CD
125 CFM
(E) 24x24 CR
400 CFM (E) 24x24 CR 400 CFM
(E) 8x8 CD
125 CFM
(E) 8x8 CD
75 CFM
(E) 12x12 CD
400 CFM
(E) 12x12 CD
325 CFM
(E) 10x10 CD
250 CFM
(E) 14x14 CR
375 CFM
(E) 18x18 CR
900 CFM
(E) 10x10 CD
250 CFM
(E) 10x10 CD
200 CFM
(E) 8x8 CD
150 CFM
(E) 10x10 CD
200 CFM
(E) 8x8 CD
100 CFM
(E) 10x10 CD
250 CFM
(E) 18x18 CR
900 CFM
(E) 14x14 CR
450 CFM
(E) 14x14 CR
450 CFM
(E) 24x24 CR
200 CFM
(E) 14x14 CD
400 CFM
(E) 14x14 CD
400 CFM
(E) 12x12 CD
375 CFM
(E) 12x12 CD
375 CFM
(E) 18x18 CR
725 CFM
(E) 18x18 CR
725 CFM
(E) 8x8 CD
150 CFM
(E) 8x8 CR
150 CFM
(E) 8x8 CD
100 CFM
(E) 8x8 CD
100 CFM
(E) 8x8 CD
125 CFM
(E) 14x14 CD
400 CFM
(E) 12x12 CD
300 CFM
(E) 10x10 CD
200 CFM
(E) 10x10 CD
200 CFM
(E) 8x8 CD
100 CFM
(E) 10x10 CD
250 CFM
(E) 14x14 CR
400 CFM
(E) 14x14 CR
400 CFM
(E) 14x14 CD
400 CFM
(E) 8x8 CD
50 CFM
(E) 8x8 CD
75 CFM
(E) 24x24 CR
25 CFM
(E) 24x24 CR
275 CFM
(E) 24x24 CR
175 CFM
(E) 24x24 CR
175 CFM
(E) 24x24 CR
300 CFM (E) 8x8 CD 150 CFM
(E) 8x8 CD
75 CFM
(E) 14x14 CD
450 CFM
(E) 24x24 CR
250 CFM
(E) 10x10 CD
200 CFM
(E) 12x12 CR
350 CFM
ZD
1-1
ZD
BP 1-2
1 10" Ø
16" Ø
(E) 16" Ø
16"x14"
(E) 18" Ø
(E) 14" Ø
4 4
4 4 S ZD-1-1
S
ZD-1-2
20"x14"
4 MECHANICAL PLUMBING REMODEL PLAN 1
DESIGNED BYDRAWN BYCHECKED BYDATESCALEJOB NO.
SHEET NO.
DATE BY ISSUE FOR
SM/ACSM/AC
RP
07.26.2024
24-146
ISSUE DATE:REVISION:
NUM. DATE BY REVISION FOR
CONSULTANT
3902 HILLSIDE AVENUE
NORCO, CA 92860
STAMP
San Bernardino, CA 92408
412 E. Vanderbilt Way Phone: 909-890-3700
Fax: 909-890-3770
Email: [email protected]
SHEET TITLEPROJECT TITLE
AS NOTED
R:\_PROJECT\2024\24-146 NORCO FIRE STATION 47 HVAC REPLACEMENT\_CAD\24-146 MP-FLRPLN - 2025-07-26 - RUDY PARAMO NORCO FIRE STATION 47 HVAC
REPLACEMENT
ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED TO BE USED IN
CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYINGSPECIFICATIONS WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING. 1234567
07-17-2025 DWE PC CORRECTIONS
GENERAL NOTES
CONSTRUCTION NOTES
MECHANICAL PLUMBING
PLAN
MP-2.1
SCALE: 1/8" = 1'-0"
SIGNED:07/26/2025
REVIEWED FOR CODE COMPLIANCE BY:
WILLDAN ENGINEERING
1:59:42 PM Jul 31, 2025
Approval of these plans & specifications shallnot be construed to be a permit for, or anapproval of any violation of any Federal, State,County or City laws or ordinances. One set ofapproved plans must be kept on the job untilcompletion.
AC
7 AC
6 AC
5 AC
4 AC
3 AC
2 AC
1 CU
2 (E) EF-2
(E) EF-4(E) EF-5
(E) EF-1
(E) EF-3
1 2
1 2
1 2
1 2
1 2
1 2
CU
1 2
3 (E) VENT
(E) VENT
(E) VENT
(E) VENT
(E) FLUE
(E) VENT
(E) VENT
(E) VENT
(E) FLUE
(E) VENT
(E) VENT
DUCT
MOUNTED
POWER
EXHAUST
POWER
EXHAUST
POWER
EXHAUST
3/4" COND
3/4" COND
3/4" COND
3/4" COND
3/4" COND
3/4" COND
3/4" COND
CAPPED GAS
CAPPED GAS
CAPPED GAS
CAPPED GAS
CAPPED GAS
CAPPED
GAS
4 4
4 (E) VENT
4 4
(E) ROOF ACCESS HATCH
30"x36"
(E) ROOF ACCESS HATCH
30"x36"
18x12
10x26 6 MP-4.1
7 MP-4.1
8 MP-4.1
10 MP-4.1
12 MP-4.1
1 CONNECT NEW UNIT TO EXISTING SUPPLY AND RETURN DUCTS. REWORK EXISTING DUCT AS NEEDED TO MAKE THE CONNECTION.
CONNECT NEW CONDENSATE PIPING AT P.O.C. REWORK PIPING AS NEEDED TO MAKE THE CONNECTION. VERIFY SIZE AND LOCATION OF EXISTING PIPING IN FIELD.
CONNECT NEW SUPPLY AND RETURN DUCT TO EXISTING. REWORK
EXISTING DUCT AS NEEDED.
EXTEND VENT TO BE AT LEAST 10 FT AWAY FROM THE FRESH AIR INTAKE OF AC UNIT.
234
DESIGNED BYDRAWN BYCHECKED BYDATESCALEJOB NO.
SHEET NO.
DATE BY ISSUE FOR
SM/ACSM/AC
RP
07.26.2024
24-146
ISSUE DATE:REVISION:
NUM. DATE BY REVISION FOR
CONSULTANT
3902 HILLSIDE AVENUE
NORCO, CA 92860
STAMP
San Bernardino, CA 92408
412 E. Vanderbilt Way Phone: 909-890-3700
Fax: 909-890-3770
Email: [email protected]
SHEET TITLEPROJECT TITLE
AS NOTED
R:\_PROJECT\2024\24-146 NORCO FIRE STATION 47 HVAC REPLACEMENT\_CAD\24-146 MP-ROOF - 2025-07-26 - RUDY PARAMO NORCO FIRE STATION 47 HVAC
REPLACEMENT
ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED TO BE USED IN
CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYINGSPECIFICATIONS WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING. 1234567
07-17-2025 DWE PC CORRECTIONS
GENERAL NOTES
CONSTRUCTION NOTES
MECHANICAL PLUMBING
ROOF PLAN
MP-3.1
MECHANICAL PLUMBING REMODEL ROOF PLAN SCALE: 1/8" = 1'-0" 1 1 1
SIGNED:07/26/2025
REVIEWED FOR CODE COMPLIANCE BY:
WILLDAN ENGINEERING
1:59:42 PM Jul 31, 2025
Approval of these plans & specifications shallnot be construed to be a permit for, or anapproval of any violation of any Federal, State,County or City laws or ordinances. One set ofapproved plans must be kept on the job untilcompletion.
1 24
FC MOUNTING 5
68 REFRIGERANT PIPE SUPPORT 9
PIPE SUPPORT ON ROOF 10
DUCT THRU ROOF 12
13 14
- 16
- 15 NEW AC UNIT MOUNTED ON NEW CURB 11 AC CONDENSATE CONNECTION 7 3 (E) ROOF
RIGID INSULATION,
CANTSTRIP AND ROOFING
BY ROOFING CONTRACTOR
SECURE TO EQUIPMENT PAD W/ 3/8"Ø
LAG SCREW W/ 4" MIN. EMBEDMENT
AT EACH CORNER (TYP.4)
"CALDYN" TYPE VT
MOUNTING PAD. TYP. (4)
SHEET METAL
ADDITIONAL BLOCKING AS REQUIRED
FOR ATTACHMENT OF ISOLATOR TO
EQUIPMENT PLATFORM.
CONTRACTOR TO COORDINATE
EXACT LOCATIONS.
CU
-
12" MIN.
FC
-
MOUNTING BRACKETBY EQUIP. MFR.
(4) EACH UNIT. HOLES
SET BY MANUFACTURER
SECURE UNISTRUT TO WALL BLOCKING WITH
1/2"Ø LAG BOLT W/ MIN 4" EMBEDMENT. ADD
ADDITIONAL BLOCKING AS REQUIRED.
6" 12"
3" MIN.
1% SLOPE
8"
RIGID INSULATION,
CANTSTRIP AND ROOFING
BY ROOFING CONTRACTOR
20 GA. G.I. FLASHING BY
MECH. CONTR.
22 GA SHEET METAL CAP
(SOLDERED SEAMS)
REFRIGERANT SUCTION &
LIQUID LINES
PACK OPENING WITH
INSULATION
COMPLETELY SEAL ALL
OPENINGS WITH MASTIC
2X BASE
"B-LINE" B2000SERIES PIPECLAMP. (TYP.)
SIZE AND QTY.SEE PLANS FORTYPICAL PIPE.
"B-LINE" B22 CHANNELLENGTH AS REQUIRED.8'-0" O/C.
"B-LINE" DURABLOK ROOFTOP SUPPORT
STEEL PIPE PIPE
SUPPORT SPACING
PIPE SIZE SPACING OF SUPPORTS (FT.)
1/2" 6
3/4" OR 1" 8
1 1/4" OR LARGER 10
CU MOUNTING
NEW AC UNIT MOUNTED ON EXISTING CURB
NEW AC UNIT MOUNTED ON NEW ADAPTER CURB
NEW AC UNIT MOUNTED ON EXISTING CURB
(E) ROOF
NEW A/C UNIT
14 GA MICROHOLD BY EQUIPMENT
MANUFACTURER. SECURE TO
ADAPTER CURB WITH (3) #12x1/2"
TEK SCREWS EQUALLY SPACED.TYPICAL EACH MICROHOLD.
(E) RIGID INSULATION, CANTSTRIP
AND ROOFING
(E) PLYWOOD SHEATHING
(E) EQUIP CURB
NEW UNIT BASE RAIL
SECURE MICROHOLD TO NEW UNIT BASE
RAIL WITH (3) #12x1-1/2" TEK SCREWS
EQUALLY SPACED. TYPICAL EACH
MICROHOLD.
ADAPTER CURB
AC-3 & 6
PLAN VIEW
SECURE ADAPTER CURB TO (E) CURB
WITH #10 WOOD SCREWS WITH 1-1/2"
PENETRATION, TYP. (3) PER SIDE
LOCATION OF
MICROHOLD, TYP
MICROHOLD
1.018"
1.018"
0.938"
7.0"
3.125"
(E) ROOF
NEW A/C UNIT
NEOPRENE GASKETBY EQUIPMENT MFR.
#14 x 2" MIN SELF TAPPING
SCREWS W/ FENDER WASHER;
MIN. 2 EACH SIDE (E) RIGID INSULATION, CANTSTRIP
AND ROOFING
(E) PLYWOOD SHEATHING
(E) 2x NAILER
(E) FLASHING
(E) EQUIP CURB
SECURE NEW UNIT TO EXISTING CURB
W/ (2) #14x2" LONG SELF TAPPING SCREWSW/ FENDER WASHER. MIN. 2 EACH SIDE.
EXISTING UNIT HOLD DOWN SEISMIC CLIP.
3/4" MIN EDGE DISTANCE & SPACING
BETWEEN SCREWS.
MIN. 2"
(TYP)
EQEQ
NOTE:EXISTING CURB AND/OR EXISTING PLATFORM ONLYUSED WHEN NEW REPLACEMENT UNIT WEIGHT DIDNOT EXCEED EXISTING PREVIOUS UNIT WEIGHT BY GREATER THAN 5%, PER CAC 4-309(A)
3" MINIMUM
EQUIPMENT
DRAIN PAN
DI-ELECTRIC COUPLING
UNION (IF REQUIRED)
UNIT TYPE
DRAW THRU
BLOW THRU
A
SPx1.5+2"
B
DIMENSION "B" SHALL NOT BE LESS THAN 3"
SP = EXTERNAL STATIC PRESSURE
OF A/C UNIT
DRAIN LINE SHALL BE
SIZED AS FOLLOWS:
0-10 TONS
* NOT LESS THAN FULL SIZE OF
UNIT CONNECTION
SPx1.5+2"
SPx1.0+1"SPx1.5+2"
3/4"
11-20 TONS 1"
21-45 TONS 1-1/4"
46-65 TONS 1-1/2"
66-250 TONS 2"
A B
UNION (TYP)
(E) ROOF
NEW A/C UNIT
FLEX DUCT
CONNECTION
(E) CONTINUOUS
WOOD NAILER
DUCT - SEEPLANS
FASTEN DUCT TO ANGLE
W/ #10 SMS @ 6" O.C. ON
(2) SIDES OF DUCT MIN.
(E) PRE-LEVELED
EQUIPMENT ISOLATION
CURB
(E) RIGID INSULATION,
CANTSTRIP AND ROOFING
NEW A/C UNIT
& BASE
NEW ADAPTER
CURB
(E) ISO CURB
(10) 1/4" x 12" WIDE x 18"
TALL GR.50 STEEL PLATE
(7) 1/4" TEK SCREWS PER
ROW EQUALLY SPACED
18"
(8) 1/4" TEK SCREWS PER
ROW EQUALLY SPACED
1 1/2" X 1 1/2" X 3/16" THICK ANGLE
NEOPRENE GASKET
SECURE NEW UNIT BENT PLATE W/
(2) ROWS OF (8) 1/4" TEKS SCREWS
AC-2
PLAN VIEW
EQ EQ EQ
STEEL PLATES (E) EQUIPMENT CURB
(5) EA PER
LONG SIDE
(E) 2" ADJUSTABLE ISOLATION SPRINGS
(2) ROWS OF (8) 1/4"
TEKS SCREWS
(E) EQUIPMENT CURB(E) 20 GA. G.I. FLASHING
12"
(1) ROW OF (8) 1/4" TEKS SCREWS
1/4" BENT PL
EQ
3/8" LAG BOLT,
2 EACH SIDE
22 GA G.I. FLASHING. (TYP.)
ROOFING UP ALL SIDES
SEE ARCHITECTURAL
DRAWING
3" EMB. (TYP.)
(E) WOOD ROOF
CANT STRIP
3X10
TYP.
#10 S.M.S. @ 6" 0.C. MAX
#10 S.M.S. @ 6" O.C. MAX
PROVIDE SEALANT FOR
WATER TIGHT INSTALLATION
DUCTWORK. SEEPLANS FOR SIZE
AND LOCATION.
4X8 BLKG ALL SIDES W/
SIMPSON (2) A35 EA. END
TO BLKG OR (E) ROOF
RAFTER
DUCT SUPPORT ON ROOF
AC-1, 4, 5, 7
DX PIPING THU ROOF
DURABLOCK DUCT
SUPPORT, SIZE PER DUCT
SIZE & WEIGHT
(E) ROOF
DUCT W/ EXTERNAL
INSULATION
20 GA. SHEET METAL
DUCT COVER, PITCH 1/4"
PER FOOT
1/2"Ø STUD
NUT (TYP.)
B22 UNISTRUT ANGLE BRACKET
(TYP.)
NOTE: PROVIDE SUPPORTS AT 8'-0" O.C., AS WELL AS, AT ALL TURNS AND OFFSETS NOTES:
1. HANG TRAPEZE AT 6'-0" ON CENTER
2. REFRIGERANT PIPING UNDER 2 1/2"
DOES NOT NEED SEISMIC BRACING
12" MAX
B-LINE
B-LINE FIG. B3380 THRU B22SHB3384
B-LINE B200 SERIES
PIPE INSULATION
FOR CONNECTION TO
STRUCTURE - REFER TO
2008 SMACNA SEISMIC
RESTRAINT MANUAL
ZONE OR BYPASS DAMPER MOUNTING
A/C UNIT
NEOPRENE GASKET BY
EQUIPMENT MFR.
SECURE UNIT TO CURB W/ 3/16"x3"
LONG SELF TAPPING SCREWS W/
FENDER WASHER. MIN. 2 EACH SIDE.
UNIT HOLD DOWN SEISMIC
CLIP (TYP. OF 4 LOCATIONS)
20 GA. G.I. FLASHING BY
MECH. CONTR.
RIGID INSULATION,
CANTSTRIP AND ROOFING
BY ROOFING CONTRACTOR
(E) ROOF
FOR CONNECTION TO
STRUCTURE SEE STRUCTURAL
DRAWINGS
14" HIGH PRE LEVELED
EQUIPMENT CURB FACTORY BY
UNIT MFR. TOP SET LEVEL
DUCT - SEE PLANS
2 x NAILER BY EQUIPMENT MFR.
FOR ROD CONN. TO STRUCTURE
- REFER TO 2008 SMACNA
SEISMIC RESTRAINT MANUAL
1-1/2"x1" 1/2"x1/8" ANGLE SECURE
TO BOX W/ #10 SMS AT 6" O.C.
LINED SUPPLY DUCT. SEE PLANS
FOR SIZE
1/2"ø HANGER ROD. DOUBLE NUT
TO ANGLE EACH SIDE.
LOCATION OF RODS
(TOTAL OF 4)
TYP. ZONE & BYPASS
DAMPER. SEE PLANS
FOR LOCATION
DIAGONAL BRACING
(TOTAL 4)
RIGID DUCT CONN. SEEPLANS FOR SIZE
FOR BRACING CONN. TO
STRUCTURE - REFER TO
2008 SMACNA SEISMIC
RESTRAINT MANUAL
DIAGONAL BRACING
(TOTAL 4)
TOP VIEW
45° (TYP)
MAX WEIGHT: 40 LBS
ZD
-
BP
-
FOR CONNECTION TO
STRUCTURE SEE STRUCTURAL
DRAWINGS
FOR CONNECTION TO
STRUCTURE SEE STRUCTURAL
DRAWINGS
FOR CONNECTION TO
STRUCTURE SEE STRUCTURAL
DRAWINGS
-
DESIGNED BYDRAWN BYCHECKED BYDATESCALEJOB NO.
SHEET NO.
DATE BY ISSUE FOR
SM/ACSM/AC
RP
07.26.2024
24-146
ISSUE DATE:REVISION:
NUM. DATE BY REVISION FOR
CONSULTANT
3902 HILLSIDE AVENUE
NORCO, CA 92860
STAMP
San Bernardino, CA 92408
412 E. Vanderbilt Way Phone: 909-890-3700
Fax: 909-890-3770
Email: [email protected]
SHEET TITLEPROJECT TITLE
AS NOTED
R:\_PROJECT\2024\24-146 NORCO FIRE STATION 47 HVAC REPLACEMENT\_CAD\24-146 MP-DETAILS - 2025-07-26 - RUDY PARAMO NORCO FIRE STATION 47 HVAC
REPLACEMENT
ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED TO BE USED IN
CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYINGSPECIFICATIONS WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING. 1234567
07-17-2025 DWE PC CORRECTIONS
MECHANICAL PLUMBING
DETAILS
MP-4.1
SIGNED:07/26/2025
REVIEWED FOR CODE COMPLIANCE BY:
WILLDAN ENGINEERING
1:59:42 PM Jul 31, 2025
Approval of these plans & specifications shallnot be construed to be a permit for, or anapproval of any violation of any Federal, State,County or City laws or ordinances. One set ofapproved plans must be kept on the job untilcompletion.
POWER LEGEND AND SYMBOLS
SYMBOL DESCRIPTION
NOTE TO CONTRACTOR
CONTRACTOR SHALL VERIFY PLANS AND EXISTING DIMENSIONS AND CONDITIONS ON THE JOB SITE AND SHALL
IMMEDIATELY NOTIFY THE ARCHITECT IN WRITING OF ANY DISCREPANCIES BEFORE PROCEEDING WITH THE WORK OR BE RESPONSIBLE FOR THE SAME.
DO NOT SCALE DRAWINGS
1. ALL MATERIALS AND WORKMANSHIP SHALL CONFORM TO THE LATEST CODE OF FEDERAL REGULATIONS (CFR), NATIONAL ELECTRICAL CODE EDITION AND ALL APPLICABLE LOCAL CODES AND REGULATIONS.
2. ALL WORK IS NEW UNLESS NOTED OTHERWISE.
3. ALL PANELS, SWITCHES, ETC. SHALL HAVE SUFFICIENT GUTTER SPACE AND LUGS IN COMPLIANCE TO UL REQUIREMENTS TO ACCOMMODATE CONDUCTORS SHOWN.
4. WHERE WIRE SIZES ARE INDICATED ON PLANS, FOR INDIVIDUAL CIRCUITS, THE WIRE SIZE INDICATED SHALL APPLY TO THE COMPLETE CIRCUIT, UNLESS OTHERWISE NOTED.
5. WHERE EXISTING CIRCUITS OR DEVICES ARE DEMOLISHED, MODIFIED, OR REUSED, ENSURE ALL EXISTING ELECTRICAL UTILIZATION DEVICES TO REMAIN ARE ENERGIZED UPON COMPLETION OF WORK.
6. CONTRACTOR SHALL VERIFY THE EXACT LOCATION OF MECHANICAL, PLUMBING AND OTHER EQUIPMENT REQUIRING ELECTRICAL CONNECTION PRIOR TO ANY WORK.
7. CONTRACTOR SHALL EXTEND WIRING FROM ALL JUNCTION BOXES, SWITCHES, ETC. AND MAKE FINAL CONNECTION AS REQUIRED TO ALL BUILDING EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS.
8. LOCATION OF LOCAL WALL SWITCHES ARE SUBJECT TO MODIFICATIONS. AT OR NEAR DOORS, INSTALL SWITCHES ON SIDE OPPOSITE TO DOOR HINGE. VERIFY FINAL HINGE LOCATION IN FIELD PRIOR TO ANY WORK.
9. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEMS AND WORK INCLUDED. FOLLOW
DRAWINGS IN LAYING OUT WORK AND CHECK DRAWINGS OR OTHER TRADES RELATING TO WORK TO VERIFY SPACE IN WHICH WORK WILL BE INSTALLED. MAINTAIN HEADROOM AND MINIMUM CODE REQUIRED WORKING CLEARANCES AT ALL TIMES.
10. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL WALL OUTLET BOXES FOR SWITCHES, BELL/STROBES, FIRE ALARM PULL STATIONS. RECEPTACLES ETC. WITH CABINETS, FURNITURE, EQUIPMENT ETC., TO AVOID CONFLICT.
11. FURNISH APPROVED EXPANSION FITTINGS WHERE RACEWAY CROSSES BUILDING EXPANSION JOINTS.12. FURNISH PULL STRING IN EACH RACEWAY RUN OVER 10' IN LENGTH, IN WHICH PERMANENT WIRING IS NOT INSTALLED.13. PROVIDE PULL BOXES WHEREVER NECESSARY TO FACILITATE PULLING OF CONDUCTORS. COORDINATE LOCATIONS OF BOXES WITH OTHER TRADES TO AVOID CONFLICT. PULL BOXES SHALL BE ACCESSIBLE. THE SIZE OF PULL BOX SHALL COMPLY WITH N.E.C. REQUIREMENTS.
14. SEE MECHANICAL AND PLUMBING DRAWINGS AND SPECIFICATION FOR ADDITIONAL CONNECTION REQUIREMENTS TO
CONTROL PANELS, CONTROL TRANSFORMERS, POWER FOR CONTROL SYSTEM EP AND PE SWITCHES, TIME CLOCKS, VALVES, STATS, RELAYS, DUCT SMOKE DETECTOR LOCATIONS, ETC. INDICATED ON CONTROL WIRING DIAGRAMS.
ELECTRICAL CONTRACTOR SHALL VERIFY FINAL CONTROL WIRING REQUIREMENTS WITH MECHANICAL AND PLUMBING CONTRACTORS PRIOR TO ANY WORK AND PROVIDE ALL NECESSARY DEVICES AND CONNECTIONS AS REQUIRED.
15. ALL EXTERIOR ELECTRICAL DEVICES AND EQUIPMENT INCLUDING THOSE THAT ARE EXPOSED TO OUTSIDE ENVIRONMENT SHALL BE WEATHERPROOF TYPE, NEMA 3R.
16. NO CONDUIT RUNS SHALL BE ALLOWED IN CONCRETE SLABS. ALL CONDUITS WILL BE PLACED ABOVE ACCESSIBLE CEILING SPACES UNLESS SPECIFICALLY INDICATED TO BE UNDERGROUND.
17. DISCONNECT SWITCHES SHALL BE MOUNTED ON INDIVIDUAL SUPPORTS, OR OTHERWISE DIRECTLY ON EQUIPMENT, PROVIDED NO MODIFICATION TO EQUIPMENT IS NECESSARY.
18. ALL ELECTRICAL POWER, LIGHTING, TELEPHONE OR SIGNAL WIRING IN FIRE RATED WALL IS TO BE INSTALLED IN A METALLIC CONDUIT SYSTEM.
19. ALL ELECTRIC MATERIAL SHALL BE LISTED BY "UL" FOR THE TYPE OF APPLICATION AND "UL" LABEL SHALL APPEAR ON ALL ELECTRICAL EQUIPMENT.
20. ALL DISTRIBUTION AND CONTROL EQUIPMENT (SUCH AS CB's, SWITCHES, CONTACTORS, ETC.), TERMINATIONS SHALL BE FULLY RATED PER UL AS FOLLOWS:
a. 100A OR LESS : 60°C OR MORE;
b. MORE THAN 100A : 75°C OR MORE.
21. ANY ERRORS, OMISSIONS, OR DESIGN DISCREPANCIES ON PLANS OR SPECIFICATIONS SHALL BE BROUGHT TO THE
ATTENTION OF THE ELECTRICAL ENGINEER FOR CLARIFICATION OR CORRECTION PRIOR TO CONSTRUCTION AND PREPARATION OF SUBMITTAL PACKAGES.
22. CONDUCTORS SHALL HAVE UNDERWRITER'S LABORATORIES, INC.(UL) LISTED, 600 VOLT INSULATION OF TYPE SPECIFIED BELOW OR ELSEWHERE IN THE SPECIFICATIONS. CONDUCTORS SHALL BE COPPER AND LISTED FOR 90 DEGREE APPLICATIONS.
1. BRANCH CIRCUITS - LIGHTING AND POWER.
a. #10 AWG AND SMALLER, SOLID WIRE TYPE THW OR THHN/THWN-2, THHW(THHN FOR DRY LOCATION ONLY). b. #8 AWG TO #2 AWG, STRANDED TYPE THW OR THHN/THHW.
c. #1 AWG AND LARGER, STRANDED TYPE XHHW-2.
2. FEEDERS : TYPE THW OR THHN/THWN-2, OR XHHW-2.
23. PROVIDE GREEN INSULATED GROUNDING CONDUCTOR IN EACH RACEWAY INCLUDING CONDUITS, PLUG STRIPS, WIREMOLD. SIZE OF GROUNDING SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE ARTICLE 250.
24. WIRING METHOD SHALL BE EMT ABOVE GROUND AND MOUNTED IN CONCEALED SPACES AND SCHEDULE-40 PVC FOR UNDERGROUND INSTALLATION. USE RIGID WHEN ENCASED IN CONCRETE OR SUSCEPTIBLE TO DAMAGE.
25. ALL SWITCH LOCATIONS ARE REQUIRED TO HAVE A NEUTRAL CONDUCTOR PROVIDED AT THE SWITCH LOCATION PER NEC 404.2(C).
26. UNLESS OTHERWISE INDICATED, SHARING OF NEUTRAL/GROUNDED CONDUCTORS AMONG SINGLE PHASE BRANCH CIRCUITS OF DIFFERENT PHASES INSTALLED IN THE SAME RACEWAY IS NOT PERMITTED. PROVIDE DEDICATED NEUTRAL/GROUNDED CONDUCTOR FOR EACH INDIVIDUAL BRANCH CIRCUIT.
27. BASIS OF ELECTRICAL DESIGN LIMITS VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUITS. ANY CHANGES MADE IN THE FIELD SHALL LIMIT VOLTAGE DROP TO THESE PERCENTAGES.
28. BRANCH CIRCUIT CONDUITS SHALL BE CONCEALED IN WALL OR CEILING SPACES. EXPOSED CONDUITS ARE NOT ALLOWED WHERE CONCEALED METHODS ARE AVAILABLE.
29. CONTRACTOR SHALL PROVIDE CONDUCTORS AND CONDUITS REQUIRED FOR ALL BRANCH CIRCUITS AND FEEDERS. FOR CIRCUIT SIZES NOT SHOWN, REFER TO PANEL SCHEDULES FOR CONDUCTOR AND CONDUIT SIZES.
30. THE CONTRACTOR SHALL COORDINATE THE WORK WITH OTHER TRADES. ANY COSTS TO INSTALL WORK TO
ACCOMPLISH SAID COORDINATION, WHICH DIFFERS FROM THE WORK AS SHOWN ON THE CONTRACT DOCUMENTS, SHALL BE INCURRED BY THE CONTRACTOR. ANY DISCREPANCIES, AMBIGUITIES OR CONFLICTS SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER'S REPRESENTATIVE DURING BID TIME FOR CLARIFICATION. ANY SUCH CONFLICTS NOT
CLARIFIED PRIOR TO BID SHALL BE SUBJECT TO THE INTERRUPTION OF THE OWNER'S REPRESENTATIVE AT NO ADDITIONAL COST TO THE OWNER.
31. EXACT ROUTING METHOD AND LOCATION OF CONDUIT PENETRATION AND OPENINGS IN WOOD ROOF DECKS, WALL, FLOORS OR STRUCTURAL STEEL MEMBERS SHALL BE DETERMINED BY THE CONTRACTOR IN FIELD. PERFORM CORING,
SAWCUTTING, PATCHING AND REFINISHING OF EXISTING WALLS AND SURFACES WHEREVER IT IS NECESSARY TO PENETRATE. OPENINGS SHALL BE SEALED IN AN APPROVED METHOD TO MEET THE FIRE RATING AND WATER PROOFINGREQUIREMENTS OF THE PARTICULAR WALL, FLOOR OR CEILING. ALL FIRE SEALS SHALL BE UL APPROVED. CONTRACTOR SHALL SCAN ALL CONCRETE WALLS AND SLABS FOR THE PRESENCE OF REBAR AND/OR UTILITIES PRIOR TO DRILLING ORCUTTING IF CONCRETE WORK IS INVOLVED. CONTRACTOR SHALL PROVIDE CERTIFICATION OF CALIBRATION OFCONCRETE SCANNING EQUIPMENT PRIOR TO PERFORMING WORK.
APPLICABLE CODES
GENERAL DEMOLITION NOTES
1. THE CONTRACTOR SHALL VISIT THE PROJECT SITE AND MAKE THEMSELVES COMPLETELY FAMILIAR WITH THE EXISTING INSTALLED CONDITIONS. A FIELD SURVEY VERIFICATION IS MANDATORY IN ORDER TO SUBMIT AN ELECTRICAL BID, FAILURE TO DO SO SHALL NOT RELIEVE THIS CONTRACTOR FROM PERFORMING THE WORK OF THIS CONTRACT.
2. ALL EQUIPMENT OR WORK REQUIRED TO CARRY OUT THE DEMOLITION SCOPE OF WORK IS CONSIDERED TO BE PART OF THE CONTRACTOR SCOPE OF WORK. NO EXTRAS WILL BE CONSIDERED TO PERFORM THE REQUIRED WORK.
3. THE CONTRACTOR SHALL OBTAIN WRITTEN PERMISSION FROM THE FACILITY DIRECTOR PRIOR TO THE SCHEDULING OF ANY POWER OUTAGE. SUCH PERMISSION MUST BE OBTAINED IN WRITING AND BE GRANTED AT LEAST 7 DAYS PRIOR TOANY SCHEDULE SHUT DOWN. THE SHUT DOWN SHALL NOT EXCEED A DURATION OF 4 HOURS.
4. THE CONTRACTOR SHALL NOT STORE ON SITE ANY ITEMS THAT WERE DEMOLISHED FOR ANY EXTENDED PERIOD OF TIME, WITHOUT THE WRITTEN PERMISSION OF THE CAMPUS FACILITY DIRECTOR.
5. ALL ELECTRICAL ITEMS DESIGNATED AS EXISTING TO REMAIN SHALL AS PART OF THIS SCOPE OF WORK BE CLEANED AND TESTED, TO INSURE PROPER OPERATION. ANY ITEMS THAT FAIL TO PASS THE TEST SHALL BE BROUGHT TO THEATTENTION OF THE FIELD INSPECTOR AND THE ENGINEER OF RECORD FOR RESOLUTION.
6. THE CONTRACTOR SHALL REMOVE ALL EXISTING SWITCHBOARDS, DISTRIBUTION BOARDS, PANEL BOARDS, LIGHTING FIXTURES, CONDUITS, WIRES AND OTHER ELECTRICAL APPARATUS DESIGNATED AS EXISTING TO BE REMOVED.
DEMOLITION ITEMS, IF NOT REQUIRED TO BE SALVAGED BY OWNER, BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE DISPOSED OF IN AN APPROPRIATE MANNER.
7. THE CONTRACTOR SHALL REMOVE ALL CONDUITS SERVING DEVICES WHICH ARE DESIGNATED AS EXISTING TO BE REMOVED, BACK TO THE SOURCE.
8. DEMOLITION AND/OR REMOVAL OF ELECTRICAL EQUIPMENT IN AREAS TO BE REMODELED SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
9. WHERE OUTLETS ARE REMOVED IN EXISTING WALL, REMOVE DEVICES, OUTLETS AND WIRING BACK TO PANELBOARD OR BACK TO NEAREST OUTLET WITH OTHER EXISTING LOAD TO REMAIN.
10. WHERE EXISTING CONDUIT AND CONDUCTORS ARE TO BE REMOVED AND CONDUIT IS INSTALLED IN GROUND OR
EMBEDDED IN CONCRETE, REMOVE WIRE AND CUT CONDUIT TO BELOW FLOOR, PLUG CONDUIT, PATCH FLOOR AND ABANDON CONDUIT.
11. WHERE ELECTRICAL DEVICES ARE TO BE REMOVED, REMOVE ALL CONDUIT AND CONDUCTORS BACK TO SOURCE, TERMINAL CABINETS AND RACKS, PROVIDE BLANK COVER PLATE FOR ABANDONED JUNCTION BOXES.
12. REMOVE ALL CONTROL PANELS, EQUIPMENT RACKS, PULL-BOXES, TERMINAL CABINETS, ETC. FOR SYSTEMS TO BE DEMOLISHED EXCEPT WHERE ANY OF THE EXISTING DEVICES, SYSTEMS, CONSOLES, ETC. ARE TO BE REUSED FORUPGRADE.
13. PROVIDE BLANK COVER PLATE FOR ALL EMPTY OUTLET BOXES WHERE DEVICES AND/OR CONDUCTORS HAVE BEEN REMOVED AS PART OF THIS CONTRACT.
14. AFTER REMOVAL OF WIREMOLD AND ASSOCIATED FITTINGS, PATCH, REPAIR AND PAINT AFFECTED SURFACES TO MATCH EXISTING.
15. EXISTING CONDUIT CAN BE REUSED PROVIDING IT IS CODE COMPLIANT, IS CHECKED FOR CONTINUITY OF GROUND, CLEAN AND MANDREL, AND DOES NOT INTERFERE WITH NEW CONSTRUCTION.
16. REMOVALS AND REPAIRS TO EXISTING ELECTRICAL WORK REQUIRED TO AVOID CONFLICTS WITH NEW CONSTRUCTION TO MEET MINIMUM CODE REQUIREMENTS.
GENERAL NOTES ABBREVIATIONS
1. 2022 BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1, TITLE 24 C.C.R.
2. 2022 CALIFORNIA BUILDING CODE (CBC),PART 2, TITLE 24 C.C.R. (IBC WITH AMENDMENTS)
3. 2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R. (NEC WITH AMENDMENTS)
4. 2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R. (UMC WITH AMENDMENTS)
5. 2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R. (UPC WITH AMENDMENTS)6. 2022 CALIFORNIA FIRE CODE, PART 9, TITLE 24 C.C.R. (IFC WITH AMENDMENTS)
7. 2022 CALIFORNIA REFERENCED STANDARDS, PART 12, TITLE 24 C.C.R.
8. TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS.9. 2022 CALIFORNIA ENERGY CODE (PART 6, TITLE 24 C.C.R.)
10. 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CGBSG), PART 11, TITLE 24 C.C.R. +96" OR 7'-6" AFF
MOUNTING HEIGHT FROM FINISHED FLOOR TO BOTTOM LINE OF OUTLET OR EQUIPMENT. FORLIGHT FIXTURES, IT IS TO BOTTOM OF FIXTURE.
MAIN SWITCHBOARD, POWER OR LIGHT, FLOOR STANDING ENCLOSURE, (SEE SINGLE LINEDIAGRAM AND LOAD SUMMARY)BRANCH PANELBOARD, WALL MOUNTED, SEE PLANS AND SCHEDULE. (RECESSED MOUNTED)BRANCH PANELBOARD, WALL MOUNTED, SEE PLANS AND SCHEDULE. (SURFACE MOUNTED) CONDUIT STUBBED AND CAPPED, SIZE AND QUANTITIES PER PLANS.CONDUIT CONCEALED IN OR UNDER FLOOR, 3/4" UON, COORDINATE WITH G.C.: OR, BURIALCONDUIT UNDERGROUND. REFER TO PLANS, DETAILS AND SPECIFICATIONS.
HEAVY DUTY SAFETY SWITCH H.P. AND 600 VOLTS RATED. "F" INDICATES FUSE TYPE. FUSESPER APPROVED EQUIPMENT MANUFACTURERS SHOP DRAWINGS. SUBSCRIPT INDICATES SWITCH AMPERE RATING. # OF POLES TO MATCH SUPPLY CIRCUIT.
MAGNETIC MOTOR STARTER H.P. RATED (NUMBER INDICATES NEMA SIZE) #2 OR
200-Y CONDUIT WIRING DESCRIPTION PER FEEDER SCHEDULE ON OTHER PLAN
ELECTRICAL UTILITY PRIMARY
ELECTRICAL UTILITY SECONDARYUTILITY TELEPHONE
TEMPORARY OVERHEAD CABLING
CONCRETE ELECTRICAL PULL BOX WITH LID APPROPRIATE FOR INSTALLATION LOCATION. LID SHALL BE LABELED "ELECTRICAL" OR "COMM" ACCORDING TO USE.
EQUIPMENTID. No.
SHEET No.DETAIL No.
EQUIPMENT REFERENCEDETAIL REFERENCE
ABOVE CEILING, CONCEALED, JUNCTION BOX, WITH COVER, PER NATIONAL ELECTRICAL CODE (NEC) TABLE 314.16(A)/(B), 4" SQUARE DEEP, WITH PLASTER RING.
RECESSED WALL MOUNTED JUNCTION BOX, WITH COVER, PER NATIONAL ELECTRICAL CODE (NEC) TABLE 314.16(A)/(B), 4" SQUARE DEEP, WITH PLASTER RING.
DUPLEX RECEPTACLE OUTLET, CONVENIENCE. (20 AMPS, 125 VOLTS, GFCI TYPE) MOUNTED +15" A.F.F. TO BOTTOM OF DEVICE U.O.N.
MOLDED CASE CIRCUIT BREAKER
SWITCH AND FUSE ASSEMBLY
GROUNDING CONNECTION AT SWITCHGEAR/DISTRIBUTION BOARD WITH NEUTRAL BONDING.
UTILITY COMPANY PULL SECTION LUGS
G
N
GROUNDING CONNECTION TO MAIN BUILDING GROUND SYSTEM U.O.N.
EXISTING (DASH INDICATES) ELECTRICAL EQUIPMENT
TELEPHONE BACKBOARD 2'X4'X3/4" PLYWOOD. PROVIDE 2" CONDUIT TO TELEPHONE POC.
HOMERUN TO CIRCUITS #1 AND #3 IN PANEL "A". REFER TO PANEL SCHEDULE FOR CONDUIT AND CONDUCTOR SIZES. QTY AS REQUIRED.
A-1,3
SMOKE FIRE DAMPER
DUCT MOUNTED SMOKE DETECTOR.
IN-LINE UTILITY COMPANY METER
UTILITY METER WITH CIRCUIT TRANSFORMERS (CT'S) METER
SOLID STATE DEVICE CONNECTED TO THE POWER DISTRIBUTION SYSTEM TRANSFORMER WITH SECONDARY GROUND. REFER TO SINGLE LINE DIAGRAM FOR KVA RATING AND GROUNDING REQUIREMENTS. T
GROUND FAULT PROTECTION DEVICE CONNECTED TO THE POWER DISTRIBUTION SYSTEM THERMOSTAT SUPPLIED BY MECHANICAL CONTRACTOR, ELECTRICAL CONTRACTOR SHALL STUB 3/4" C.O. 6" ABOVE CEILING SPACE, PROVIDE BUSHING AND PULL WIRE. IF INSTALLED IN AREA WITH EXPOSED STRUCTURE ABOVE OR HARDLID CEILING, PROVIDE 3/4" C.O. BACK TO ASSOCIATED HVAC UNIT. REFER TO MECHANICAL DETAILS FOR T-STAT MOUNTING HEIGHT REQUIREMENTS. VERIFYLOCATIONS WITH HVAC CONTRACTOR PRIOR TO ROUGH IN.
CARBON MONOXIDE SENSOR SUPPLIED BY MECHANICAL CONTRACTOR. ELECTRICAL CONTRACTOR SHALL PROVIDE 3/4" GALVANIZED RIGID CONDUIT WITH PULL STRING BACK TO HEAD END CARBON MONOXIDE PANEL. REFER TO MECHANICAL DRAWINGS FOR EXACT EQUIPMENT LOCATIONS AND WIRING DETAILS.
CEILING MOUNTED PLUG LOAD CONTROLLER.
GROUND WELL
CONTACT SENSOR FOR HVAC SHUTDOWN. 4S BOX, MOUNTED ABOVE DOOR OR WINDOW, U.O.N.
STUB 3/4" C.O. 6" ABOVE CEILING SPACE. PROVIDE BUSHING AND PULL WIRE. IF INSTALLED IN AREA WITH EXPOSED STRUCTURE ABOVE OR HARD LID CEILING, PROVIDE 3/4" C.O. BACK TO LOCATION OF ASSOCIATED HVAC THERMOSTAT.
A AMPEREAF AMPERE FRAME RATING (CIRCUIT BREAKER)AFC AVAILABLE FAULT CURRENTAFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEAFU AMPERE FUSE RATING (FUSE)AIC AMPERE INTERRUPTING CAPACITYAS AMPERE SWITCH RATING (FUSE)AT AMPERE TRIP RATING (CIRCUIT BREAKER)AWG AMERICAN WIRE GAUGE
BCG BARE COPPER GROUNDBKBD BACKBOARDBLDG BUILDINGBKR BREAKER
C CONDUITCB CIRCUIT BREAKERCKT CIRCUITCFSD COMBINATION FIRE SMOKE DAMPERCO CONDUIT ONLYCT CURRENT TRANSFORMERCU COPPERCL CENTERLINE
DISC DISCONNECTDSBN DISTRIBUTION SECTIONDN DOWNDWG DRAWINGEA EACHEC ELECTRICAL CONTRACTOREGC EQUIPMENT GROUNDING CONDUCTOREM EMERGENCYEMT ELECTRICAL METALLIC TUBINGEPO EMERGENCY POWER OFFEXIST, (E) EXISTINGEXO EXTERNAL OPERABLE DISCONNECT
F FUSEFA FIRE ALARMFACP FIRE ALARM CONTROL PANELFF FINISHED FLOORFG FINISHED GRADEFLA FULL LOAD CURRENT
GEC GROUNDING ELECTRODE CONDUCTORGEN GENERATORGFCI GROUND FAULT CIRCUIT INTERRUPTERGFP GROUND FAULT PROTECTIONGND GROUNDGRC GALVANIZED RIGID CONDUIT
HD HEAVY DUTYHOA HAND-OFF-AUTOMATICHP HORSE POWERHV HIGH VOLTAGE
IDF INTERMEDIATE DISTRIBUTION FRAMEIG ISOLATED/INSULATED GROUNDISC SHORT CIRCUIT CURRENT AVAILABLE IN RMS
SYMMETRICAL AMPERES
J-BOX JUNCTION BOX
KCMIL THOUSAND CIRCULAR MILSKW KILOWATTKV KILO VOLTKVA KILO VOLT-AMPERE
LDC LOCAL DISTRIBUTION CABINETLDF LOCAL DISTRIBUTION FRAMELCL LONG CONTINUOUS LOADLFMC LIQUID TIGHT FLEXIBLE METAL CONDUITLSIG LONG, SHORT, INSTANTANEOUS, GROUNDLTG LIGHTINGLV LOW VOLTAGE
MFR MANUFACTURERMAX MAXIMUMMCC MOTOR CONTROL CENTERMIN MINIMUMMH MANHOLE / METAL HALIDE
MLO MAIN LUGS ONLYM/M METER AND MAIN SECTIONMV MEDIUM VOLTAGENC NORMALLY CLOSEDNEC NATIONAL ELECTRICAL CODENEMA NATIONAL ELECTRICAL MANUFACTURER'S
ASSOCIATION
NEW (N) NEW, TO BE FURNISHED AND INSTALLED BY
CONTRACTOR
NF NON-FUSEDNIC NOT IN CONTRACTN/L NIGHT LIGHTNO NUMBER, NORMALLY OPENNTS NOT TO SCALE
OC ON CENTEROD OUTSIDE DIAMETER
P POLEPB PULL BOXPF POWER FACTORPH PHASEPNL PANELPOC POINT OF CONNECTIONPP POWER POLEPWR POWERPVC POLYVINYL CHLORIDE
QUAD QUADRUPLEXQTY QUANTITY
RGS RIGID GALVANIZED STEELRMC RIGID METALLIC CONDUITRM ROOMRNC RIGID NONMETALLIC CONDUIT
SHT SHEETSN SOLID NEUTRALSPEC SPECIFICATIONSSW SWITCHSWBD SWITCHBOARD
TC TIME CLOCKTEL TELEPHONETERM TERMINALTP TEMPORARY POLETYP TYPICAL
UGPS UNDERGROUND PULL SECTIONUL UNDERWRITERS LABORATORYUPS UNINTERRUPTIBLE POWER SUPPLYUON UNLESS OTHERWISE NOTED
V VOLT, VOLTAGEVA VOLT-AMPEREVD VOLTAGE DROPVFC VARIABLE FREQUENCY CONTROLLERVFD VARIABLE FREQUENCY DRIVE
W WATTWH WATT-HOURWP WEATHERPROOFWW WIREWAY
XP EXPLOSION PROOF
Z IMPEDANCE
4W FOUR-WIRE
3W THREE-WIRE5S JUNCTION BOX
(4 11/16" SQUARED X2 1/8" DEEP)
Ø DIAMETER, PHASE
# NUMBER
°C DEGREE CELSIUS
(E) EXISTING DEVICE TO REMAIN(R) REMOVE EXISTING DEVICE AND ASSOCIATED
CONDUIT AND WIRE
(RL) REMOVE EXISTING DEVICE AND RELOCATE AS
SHOWN ON PLAN
(NL) NEW LOCATION OF RELOCATED DEVICE
MOLDED CASE SHUNT TRIP CIRCUIT BREAKERMOLDED CASE DRAW OUT TYPE CIRCUIT BREAKER
REMOTE CONTROLLED, ELECTRONICALLY OPERATED CIRCUIT BREAKER E
SURGE PROTECTION DEVICESUBSCRIPT "A-1" REFERS TO PANEL DESIGNATION WITH CIRCUIT NUMBER. TYPICAL OF ALL RECEPTACLE OUTLETS. A-1
100AS
DESIGNED BYDRAWN BYCHECKED BYDATESCALEJOB NO.
SHEET NO.
DATE BY ISSUE FOR
07.26.2024
24-146
ISSUE DATE:REVISION:
NUM. DATE BY REVISION FOR
CONSULTANT
3902 HILLSIDE AVENUE
NORCO, CA 92860
STAMP
San Bernardino, CA 92408
412 E. Vanderbilt Way Phone: 909-890-3700
Fax: 909-890-3770
Email: [email protected]
SHEET TITLEPROJECT TITLE
AS NOTED
R:\_PROJECT\2024\24-146 NORCO FIRE STATION 47 HVAC REPLACEMENT\_CAD\24-146 E-FRONT - 2025-07-17 - MIGUEL AGUILAR MAMAAN NORCO FIRE STATION 47 HVAC
REPLACEMENT
ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED TO BE USED IN
CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYINGSPECIFICATIONS WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING. 1234567
07-17-2025 DWE PC CORRECTIONS
ELECTRICAL LEGENDS &
NOTES
E-0.1
ELECTRICAL SHEET INDEX
SHEET NUMBER SHEET NAME
E-0.1 ELECTRICAL LEGENDS & NOTES
E-0.2 SINGLE LINE DIAGRAM & PANEL SCHEDULES
E-1.1 ELECTRICAL DEMOLITION PLAN
E-1.2 ELECTRICAL DEMOLITION ROOF PLAN
E-2.1 ELECTRICAL POWER PLANE-3.1 ELECTRICAL ROOF PLANE-4.1 ELECTRICAL DETAILS SIGNED:07/17/2025
REVIEWED FOR CODE COMPLIANCE BY:
WILLDAN ENGINEERING
1:59:43 PM Jul 31, 2025
Approval of these plans & specifications shallnot be construed to be a permit for, or anapproval of any violation of any Federal, State,County or City laws or ordinances. One set ofapproved plans must be kept on the job untilcompletion.
GENERAL NOTES
DEMOLITION NOTES
800AUGPS
EXISTING SERVICE GROUND
EXISTING INCOMING
POWER UTILITY SERVICE
1 (E)90A3P
G
N
800AT800AF
3P
1234
150A3P
2 345 7
(E)80A
3P
(E)40A
3P
3P600A
(E)
(E) SWITCHBOARD 'MSB-1'
800A 208Y/120V 3Ø 4W 42KAIC
(E) DISTRIBUTION BOARD 'DP-1'
600A 208Y/120V 3Ø 4W 25KAIC
(E)
40A3P
(E)
20A3P
60AS
35AT
3P
EXISTING
AC-1
EXISTING
60AS
45AT
3P
EXISTING
AC-2
EXISTING
30AS
20AT
3P
EXISTING
AC-3
EXISTING
30AS
25AT
3P
EXISTING
AC-5
EXISTING
30AS
25AT
3P
EXISTING
AC-6
EXISTING
30AS
25AT
3P
EXISTING
AC-7
EXISTING
EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING
60AS
35AT
3P
EXISTING
AC-4
EXISTINGEXISTING
60AS
3P
EXISTING
AIR COMP.
EXISTINGEXISTING
EXISTING
WASHING MACHINE
EXISTING
6 8
(E)
600A3P
L
N E
G 3P
600A
EXISTING 180KW
120/208V 3Ø 4W
EXISTING ATS 600A 4P
EXISTING EXISTING EXISTING
EXISTING
EXISTING
PANEL
1A
EXISTING
150A3P
250A3P
80A3P
EXISTING
PANEL
1B
EXISTING
EXISTING
PANEL
2B
EXISTING
EXISTING
PANEL
3A
EXISTING
EXISTING
PANEL
2A
EXISTING
800AUGPS
EXISTING SERVICE GROUND
EXISTING INCOMING
POWER UTILITY SERVICE
1 (E)90A3P
G
N
800AT800AF
3P
2 345 7
(E)80A3P
(E)
40A3P
(E) SWITCHBOARD 'MSB-1'
800A 208Y/120V 3Ø 4W 42KAIC
(E)
40A3P
(E)
20A3P
60AS
3P
EXISTING
AIR COMP.
EXISTINGEXISTING
EXISTING
WASHING MACHINE
EXISTING
6 8
(E)
600A3P
L
N E
G 3P
600A
EXISTING 180KW
120/208V 3Ø 4W
EXISTING ATS 600A 4P
EXISTING
1234
150A3P
3P600A(E) (E) DISTRIBUTION BOARD 'DP-1'
600A 208Y/120V 3Ø 4W 25KAIC
EXISTING
EXISTING
PANEL
1A
EXISTING
150A
3P
250A
3P
80A
3P
EXISTING
PANEL
1B
EXISTING
EXISTING
PANEL
2B
EXISTING
EXISTING
PANEL
3A
EXISTING
EXISTING
PANEL
2A
EXISTING
AFC:
AIC:
PANEL
1AC
21,162
42,000
400A3P
L=
V.D.=
40'0.51%
400-Y
1. REFER TO 'GENERAL NOTES' ON ELECTRICAL LEGENDS AND NOTES SHEET FOR WIRING METHODS, MATERIALS, AND REQUIREMENTS.
2. ALL NEW CIRCUIT BREAKERS, PANELBOARDS AND TRANSFORMERS SHALL BE OF THE SAME MANUFACTURER.
3. ALL NEW SWITCHBOARDS DISTRIBUTION SECTIONS SHALL BE EQUIPPED
WITH FULL HEIGHT VERTICAL BUSSING TO ACCOMMODATE MAXIMUM UTILIZATION OF SPACE FOR DEVICES.
4. AVAILABLE FAULT AT SERVICE POINT SHALL BE CONSIDERED AT 65,000 RMS SYM.
5. ALL PANELBOARDS SHALL BE FULLY RATED FOR THE AVAILABLE FAULT UNLESS OTHERWISE NOTED.
6. THE FEEDER LENGTHS SHOWN ON THESE DRAWINGS ARE FOR CALCULATION PURPOSES ONLY AND ARE NOT VALID FOR BIDDING.
7. CONTRACTOR SHALL UPDATE ALL MODIFIED PANEL DIRECTORIES OR
CREATE A NEW TYPED DIRECTORY, IF ONE DOES NOT EXIST, IDENTIFYING
EACH CIRCUIT AND INSTALLED CIRCUIT LOADS, MOUNTED IN GLASS OR PLASTIC INSIDE DOOR. THE CONTRACTOR SHALL BE RESPONSIBLE FORUPDATING DIRECTORIES TO INDICATE ALL NEW CIRCUITS AND ACTUAL AREA
SERVED WHICH IS NOT NECESSARILY THE DESCRIPTION INDICATED ON THE BID DOCUMENTS. USE A COMPUTER OR TYPEWRITER TO CREATEDIRECTORY; HANDWRITTEN DIRECTORIES ARE NOT ACCEPTABLE.
8. ALL SWITCHBOARDS, SWITCHGEAR AND PANELBOARDS AT OTHER THAN DWELLING UNITS SHALL BE LEGIBLY MARKED IN THE FIELD WITH THEMAXIMUM AVAILABLE FAULT CURRENT PER CEC 110.24. THE FIELDMARKING(S) SHALL INCLUDE THE DATE THE FAULT-CURRENT CALCULATION
WAS PERFORMED AND BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. THE CALCULATION SHALL BE DOCUMENTED AND MADE AVAILABLE TO THOSE AUTHORIZED TO DESIGN, INSTALL, INSPECT,MAINTAIN, OR OPERATE THE SYSTEM. WHEN MODIFICATIONS TO THE
ELECTRICAL INSTALLATION OCCUR THAT AFFECT THE MAXIMUM AVAILABLEFAULT CURRENT AT THE SERVICE, THE MAXIMUM AVAILABLE FAULT
CURRENT SHALL BE VERIFIED OR RECALCULATED AS NECESSARY TO
ENSURE THE SERVICE EQUIPMENT RATINGS ARE SUFFICIENT FOR THE
MAXIMUM AVAILABLE FAULT CURRENT AT THE LINE TERMINALS OF THE EQUIPMENT. THE REQUIRED FIELD MARKING(S) IN 110.24(A) SHALL BE
ADJUSTED TO REFLECT THE NEW LEVEL OF MAXIMUM AVAILABLE FAULT CURRENT.
9. EQUIPMENT DATA AND CONFIGURATIONS SHOWN ON THE SINGLE LINE DIAGRAM PROVIDE GENERAL EQUIPMENT INFORMATION. CONTRACTOR
SHALL REVIEW ELECTRICAL PLANS AND SPECIFICATIONS TO VERIFY ALL EQUIPMENT ASSOCIATED DESIGN INFORMATION. THE CONTRACTOR IS
RESPONSIBLE FOR PROVIDING ALL NECESSARY COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION. ANY DISCREPANCIES
BETWEEN DESCRIPTIONS, SPECIFICATIONS, AND EXISTING CONDITIONS ARE TO BE PRESENTED TO THE ENGINEER OF RECORD PRIOR TO COMPLETION OFTHE BID PROCESS FOR CLARIFICATION. NO EQUIPMENT SHALL BE ORDERED UNTIL DISCREPANCIES ARE RESOLVED THROUGH A FORMAL RFI PROCESS.
10. ELECTRICAL EQUIPMENT SUBMITTALS SHALL BE ACCOMPANIED BY A ¼"=1'-0"
SCALE DRAWING WHICH REFERENCES ALL ELECTRICAL EQUIPMENT ROOMS AND EQUIPMENT. DRAWING SHALL CLEARLY IDENTIFY ADEQUATE SPACE IS
PROVIDED IN ELECTRICAL ROOMS TO ACCOMMODATE THE INSTALLATION OF
ELECTRICAL EQUIPMENT WHILE MAINTAINING ALL REQUIRED CODE CLEARANCES. ALL SUBMITTALS NOT ACCOMPANIED BY SCALED DRAWING WILL BE REJECTED AS INCOMPLETE.
11. GROUND ALL ELECTRICAL EQUIPMENT, BRANCH CIRCUITS, FEEDERS, PANEL AND DISTRIBUTION BOARDS, ELECTRICAL SERVICES, ETC. PER ADOPTED NECARTICLES 250.
12. ALL ELECTRICAL EQUIPMENT (I.E. SWITCHGEAR, TRANSFORMERS, DISTRIBUTION BOARDS, PANELBOARDS, DISCONNECT SWITCHES, ETC.)
SHALL BE PROVIDED WITH A PHENOLIC NAMEPLATE WITH ENGRAVED LETTERS PER SPECIFICATIONS. ALL NAMEPLATES SHALL BE
FASTENED WITH A MINIMUM OF TWO (2) MACHINE SCREWS. NO SELF ADHESIVE NAMEPLATES ARE ALLOWED.
13. ANY FLOOR-STANDING ELECTRICAL EQUIPMENT (I.E. INVERTERS,
DISTRIBUTION BOARDS, SWITCHBOARDS, ATS SWITCHES, MOTOR CONTROL CENTERS, ETC.) WHICH ARE MOUNTED AT/BELOW GRADE AND/OR
SUSCEPTIBLE TO WATER DAMAGE SHALL BE MOUNTED ON A MINIMUM 4" HIGH HOUSEKEEPING PAD WHICH EXTENDS 4" BEYOND EQUIPMENT IN ALLDIRECTIONS.
14. ELECTRICAL CONTRACTOR TO INCLUDE IN BID ALL ASSOCIATED COSTS FOR
THIRD PARTY TESTING OF ELECTRICAL EQUIPMENT, GROUND FAULT, CONDUCTORS, ETC.
15. CONTRACTOR SHALL FURNISH AND INSTALL MISSING FILLER PLATES IN PANELBOARD/SWITCHBOARD THAT IS BEING REUSED.
16. ALL CONDUCTOR TERMINATIONS SHALL BE TIGHTENED TO MANUFACTURER RECOMMENDATIONS USING AN APPROVED MEANS.
17. ALL ELECTRICAL EQUIPMENT SHALL BE IDENTIFIED WITH NAMEPLATES, REFER. TO SPECIFICATIONS. IN ADDITION, EACH DISCONNECT MUST BEMARKED TO IDENTIFY ITS PURPOSE AND INCLUDE IDENTIFICATION OF CIRCUIT SOURCE THAT SUPPLIES DISCONNECTING MEANS. (110.22)
EXISTING FEEDERS AND CONDUIT TO BE REMOVED FROM SWITCHBOARD 'MSB-1'. EXISTING CIRCUIT BREAKERS TO BE RELABELED AS SPARE.
PANEL SCHEDULE & LOAD SUMMARY 1
FEEDER SCHEDULE 2
LABEL PHASE GROUND CONDUIT TYPE SETS
400-Y 400A-4W 2 1 # 2
NEUTRAL
600V FEEDER SCHEDULE 3Ø 4W
NOTE:
ALL CONDUCTOR SIZES ARE BASED ON TYPE THHN COPPER CONDUCTOR UNLESS OTHERWISE NOTED. THEAMPACITY OF CONDUCTORS SHALL BE BASED ON THE TERMINALS NOT TO EXCEED 60°C FOR CONDUCTOR SIZE #14 THROUGH #1 AWG OR 75°C FOR CONDUCTOR SIZE OVER #1 AWG AS PER NEC 110.14(C). 3 # 3/0 1 # 3/0 3"
1 EXISTING SINGLE LINE DIAGRAM 3
CONSTRUCTION NOTES
1 PROVIDE NEW CIRCUIT BREAKER IN EXISTING DISTRIBUTION PANEL BOARD. TYPE TO MATCH EXISTING. AIC RATING TO BE GREATER THAN AVAILABLE FAULT CURRENT. UPDATE PANELBOARD DIRECTORY PER GENERAL NOTE REQUIREMENTS.
1 1
PROPOSED SINGLE LINE DIAGRAM 4
DESIGNED BYDRAWN BYCHECKED BYDATESCALEJOB NO.
SHEET NO.
DATE BY ISSUE FOR
07.26.2024
24-146
ISSUE DATE:REVISION:
NUM. DATE BY REVISION FOR
CONSULTANT
3902 HILLSIDE AVENUE
NORCO, CA 92860
STAMP
San Bernardino, CA 92408
412 E. Vanderbilt Way Phone: 909-890-3700
Fax: 909-890-3770
Email: [email protected]
SHEET TITLEPROJECT TITLE
AS NOTED
R:\_PROJECT\2024\24-146 NORCO FIRE STATION 47 HVAC REPLACEMENT\_CAD\24-146 E-SLD - 2025-07-17 - MIGUEL AGUILAR MAMAAN NORCO FIRE STATION 47 HVAC
REPLACEMENT
ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED TO BE USED IN
CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYINGSPECIFICATIONS WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING. 1234567
07-17-2025 DWE PC CORRECTIONS
SINGLE LINE DIAGRAM &
PANEL SCHEDULES
E-0.2
SIGNED:07/17/2025
REVIEWED FOR CODE COMPLIANCE BY:
WILLDAN ENGINEERING
1:59:43 PM Jul 31, 2025
Approval of these plans & specifications shallnot be construed to be a permit for, or anapproval of any violation of any Federal, State,County or City laws or ordinances. One set ofapproved plans must be kept on the job untilcompletion.
1. REFER TO ELECTRICAL LEGENDS AND NOTES SHEET FOR ADDITIONAL DEMOLITION NOTES.
156 157
155
152 153 154
147
148
145
149 150 151
146
140 137
135
134
138 133
143
142
139
141
136 132
131
127
128
101
130129169
102
103
104
105
106107108
109
110
111
112
124
123 125 122
121
120
118
119
113 117
114
115
116
126
T
(E) AC-7
T
(E) AC-5
T
(E) AC-6
T
(E) FC-1
T
(E) AC-4
T
(E) FC-2
T
(E) AC-1
T
(E) AC-2
T
(E) AC-3
T
(E) EF-24
ST
(E) EF-14
(R) FC-1
(R) FC-2
1 1
(E)
2 1 EXISTING INDOOR UNIT TO BE REMOVED AND REPLACED WITH NEW INDOOR UNIT. REMOVE CONDUIT AND CONDUCTORS BACK TO SOURCE.
EXISTING CONDENSATION OUTLET TO REMAIN FOR NEW CONDENSATIONPUMP. 2 ELECTRICAL DEMOLITION PLAN 1
DESIGNED BYDRAWN BYCHECKED BYDATESCALEJOB NO.
SHEET NO.
DATE BY ISSUE FOR
07.26.2024
24-146
ISSUE DATE:REVISION:
NUM. DATE BY REVISION FOR
CONSULTANT
3902 HILLSIDE AVENUE
NORCO, CA 92860
STAMP
San Bernardino, CA 92408
412 E. Vanderbilt Way Phone: 909-890-3700
Fax: 909-890-3770
Email: [email protected]
SHEET TITLEPROJECT TITLE
AS NOTED
R:\_PROJECT\2024\24-146 NORCO FIRE STATION 47 HVAC REPLACEMENT\_CAD\24-146 E-PWRPLN - 2025-07-17 - MIGUEL AGUILAR MAMAAN NORCO FIRE STATION 47 HVAC
REPLACEMENT
ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED TO BE USED IN
CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYINGSPECIFICATIONS WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING. 1234567
07-17-2025 DWE PC CORRECTIONS
GENERAL NOTES
DEMOLITION NOTES
ELECTRICAL
DEMOLITION PLAN
E-1.1
SCALE: 1/8" = 1'-0"
SIGNED:07/17/2025
REVIEWED FOR CODE COMPLIANCE BY:
WILLDAN ENGINEERING
1:59:43 PM Jul 31, 2025
Approval of these plans & specifications shallnot be construed to be a permit for, or anapproval of any violation of any Federal, State,County or City laws or ordinances. One set ofapproved plans must be kept on the job untilcompletion.
(E)
(E)
(E)
(E)
(E)
(E) EF-3
(E) EF-2
(E) EF-1
(E) EF-4(E) EF-5
(R) CU-2
(R) AC-4
(R) CU-1 (R) AC-5
(R) AC-6
(R) AC-7
(R) AC-1
(R) AC-2
(E) AC-3
1 1
2 3
3 (R)
(R)
1. REFER TO ELECTRICAL LEGENDS AND NOTES SHEET FOR ADDITIONAL DEMOLITION NOTES.
12 CONTRACTOR IS TO DEMO EXISTING DISCONNECT SWITCHES AND GUTTER BOX AS SHOWN. REMOVE CONDUIT AND CONDUCTORS BACK TO SOURCE.
CONTRACTOR IS TO DEMO EXISTING DISCONNECT SWITCH AS SHOWN.
REMOVE CONDUIT AND CONDUCTORS BACK TO SOURCE.
EXISTING CONDENSING UNIT AND DISCONNECT SWITCH TO BE REMOVED AND REPLACED WITH NEW CONDENSING UNIT AND DISCONNECT SWITCH.
EXISTING CONDUIT AND CONDUCTORS TO REMAIN & REWORKED FOR CONNECTION TO NEW CONDENSING UNIT.
3 DESIGNED BYDRAWN BYCHECKED BYDATESCALEJOB NO.
SHEET NO.
DATE BY ISSUE FOR
07.26.2024
24-146
ISSUE DATE:REVISION:
NUM. DATE BY REVISION FOR
CONSULTANT
3902 HILLSIDE AVENUE
NORCO, CA 92860
STAMP
San Bernardino, CA 92408
412 E. Vanderbilt Way Phone: 909-890-3700
Fax: 909-890-3770
Email: [email protected]
SHEET TITLEPROJECT TITLE
AS NOTED
R:\_PROJECT\2024\24-146 NORCO FIRE STATION 47 HVAC REPLACEMENT\_CAD\24-146 E-ROOF - 2025-07-17 - MIGUEL AGUILAR MAMAAN NORCO FIRE STATION 47 HVAC
REPLACEMENT
ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED TO BE USED IN
CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYINGSPECIFICATIONS WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING. 1234567
07-17-2025 DWE PC CORRECTIONS
GENERAL NOTES
DEMOLITION NOTES
ELECTRICAL
DEMOLITION ROOF PLAN
E-1.2
ELECTRICAL DEMOLITION ROOF PLAN SCALE: 1/8" = 1'-0" 1
SIGNED:07/17/2025
REVIEWED FOR CODE COMPLIANCE BY:
WILLDAN ENGINEERING
1:59:43 PM Jul 31, 2025
Approval of these plans & specifications shallnot be construed to be a permit for, or anapproval of any violation of any Federal, State,County or City laws or ordinances. One set ofapproved plans must be kept on the job untilcompletion.
156 157
155
152 153 154
147
148
145
149 150 151
146
140 137
135
134
138 133
143
142
139
141
136 132
131
127
128
101
130129169
102
103
104
105
106107108
109
110
111
112
124
123 125 122
121
120
118
119
113 117
114
115
116
126
T
(E) AC-7
T
(E) AC-5
T
(E) AC-6
T
(E) FC-1
T
(E) AC-4
T
T
(E) AC-1
T
(E) AC-2
T
(E) AC-3
T
(E) EF-24
ST
(E) EF-14
(E) ATS
(E) DP1
(E) PANEL '1A'(E) PANEL '1B' (E)SWITCHBOARD 'MSB-1'
FC
1 FC
2 ZD
1-1
ZD
1-2
BP
1 1 PANEL '1AC'
1AC-40
1AC-40
1AC-40
2 2 2
3 4 6
4 S
ZD-1-1
S
ZD-1-2
5 5
(E)
(E) FC-2
3 DD (E)
7 DD (E)
7 DD (E)
7 DD (E)
7 DD (E)
7 DD
(E)
7 1. COORDINATE POWER DEVICE LOCATIONS, AND DEVICE PLATE COLOR WITH ARCHITECT.
2. NO PIPING, DUCTS OR EQUIPMENT FOREIGN TO ELECTRICAL EQUIPMENT
SHALL BE PERMITTED TO BE LOCATED WITHIN A SPACE EXTENDING FROM FLOOR TO A HEIGHT OF 6' ABOVE THE EQUIPMENT. CEC 110.26(E)1. 12 PROVIDE MINIMUM 3'-0" LEVEL CLEARANCE IN FRONT OF ELECTRICAL EQUIPMENT, PER NEC 110.26.
PROVIDE AND INSTALL NEMA 1 MOTOR RATED SNAP SWITCH.
FAN COIL TO BE POWERED BY CONDENSING UNIT (ON ROOF). PROVIDE (2)#12, (1)#12GND. IN 3/4" CONDUIT.REFER TO MECHANICAL PLANS TO
ACHIEVE INTERLOCK CONTROL AS INDICATED ON MECHANICAL
EQUIPMENT SCHEDULE.
PROVIDE AND INSTALL 208V, 2 POLE NEMA 1 MOTOR RATED SNAP SWITCH.
SPACE SENSOR SUPPLIED BY MECHANICAL CONTRACTOR, ELECTRICAL CONTRACTOR SHALL STUB 3/4" C.O. 6" ABOVE CEILING SPACE, PROVIDE BUSHING AND PULL WIRE. IF INSTALLED IN AREA WITH EXPOSED STRUCTURE ABOVE OR HARDLID CEILING, PROVIDE 3/4" C.O. BACK TO ASSOCIATED ZONE DAMPER. REFER TO MECHANICAL DETAILS FOR SPACE SENSOR MOUNTING HEIGHT REQUIREMENTS. VERIFY LOCATIONS WITH HVAC CONTRACTOR PRIOR TO ROUGH IN.PROVIDE 3/4" C. FROM CONDENSING UNIT TO FAN COIL FOR EQUIPMENT
CONTROL INTERLOCK AS INDICATED ON MECHANICAL EQUIPMENT
SCHEDULE.
RECONNECT EXISTING DUCT DETECTOR TO NEW SERVING HVAC UNIT. 34567
DESIGNED BYDRAWN BYCHECKED BYDATESCALEJOB NO.
SHEET NO.
DATE BY ISSUE FOR
07.26.2024
24-146
ISSUE DATE:REVISION:
NUM. DATE BY REVISION FOR
CONSULTANT
3902 HILLSIDE AVENUE
NORCO, CA 92860
STAMP
San Bernardino, CA 92408
412 E. Vanderbilt Way Phone: 909-890-3700
Fax: 909-890-3770
Email: [email protected]
SHEET TITLEPROJECT TITLE
AS NOTED
R:\_PROJECT\2024\24-146 NORCO FIRE STATION 47 HVAC REPLACEMENT\_CAD\24-146 E-PWRPLN - 2025-07-17 - MIGUEL AGUILAR MAMAAN NORCO FIRE STATION 47 HVAC
REPLACEMENT
ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED TO BE USED IN
CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYINGSPECIFICATIONS WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING. 1234567
07-17-2025 DWE PC CORRECTIONS
GENERAL NOTES
CONSTRUCTION NOTES
ELECTRICAL POWER
PLAN
E-2.1
ELECTRICAL POWER PLAN SCALE: 1/8" = 1'-0" 1
SIGNED:07/17/2025
REVIEWED FOR CODE COMPLIANCE BY:
WILLDAN ENGINEERING
1:59:43 PM Jul 31, 2025
Approval of these plans & specifications shallnot be construed to be a permit for, or anapproval of any violation of any Federal, State,County or City laws or ordinances. One set ofapproved plans must be kept on the job untilcompletion.
1. ALL CONDUITS SHALL BE INSTALLED IN THE CEILING BELOW U.O.N.
2. REFER TO MECHANICAL AND PLUMBING PLANS FOR THE EXACT LOCATION OF HVAC EQUIPMENT AND ADDITIONAL WIRING REQUIREMENTS.
3. PROVIDE FLEXIBLE SEAL TYPE CONDUIT FOR CONNECTION TO ALL HVAC EQUIPMENT.
4. ALL EXTERIOR ELECTRICAL EQUIPMENT SHALL BE NEMA 3R.
5. PROVIDE HEAVY DUTY DISCONNECT SWITCHES WITH DUAL ELEMENT FUSES TO MATCH MOTOR H.P. RATING.
AC
4 AC
3 AC
2 AC
1 CU
2 CU
1 (E)
(E)
(E)
(E)
(E)
(E) EF-3
(E) EF-2
(E) EF-1
(E) EF-4(E) EF-5
60AS30AS
100AS
30AS
60AS 30AS
60AS30AS
60AS30AS
AC
5 AC
7 60AS 30AS
60AS
30AS
1AC-2,4,6
1AC-14,16,18
AC
6 30AS
30AS
1 1
1AC-20,22,24
1AC-34,36,38
1AC-33,35,37 1AC-27,29,31
1AC-21,23,25
1AC-26,28 1AC-30,32
1AC-8,10,12
1AC-2,4,6
1AC-13,15 1AC-17,19
1AC-7,9,11
1AC-1,3,5 1 USE EXISTING CIRCUIT FOR NEW CONDENSING UNIT AS SHOWN. INSPECT EACH CONDUCTOR FOR CORRECT IDENTIFICATION AND INSPECT CABLE JACKET AND CONDITION. CONTRACTOR SHALL REPLACE ANY CONDUCTORS THAT DO NOT PASS INSPECTION.
ELECTRICAL ROOF PLAN 1
DESIGNED BYDRAWN BYCHECKED BYDATESCALEJOB NO.
SHEET NO.
DATE BY ISSUE FOR
07.26.2024
24-146
ISSUE DATE:REVISION:
NUM. DATE BY REVISION FOR
CONSULTANT
3902 HILLSIDE AVENUE
NORCO, CA 92860
STAMP
San Bernardino, CA 92408
412 E. Vanderbilt Way Phone: 909-890-3700
Fax: 909-890-3770
Email: [email protected]
SHEET TITLEPROJECT TITLE
AS NOTED
R:\_PROJECT\2024\24-146 NORCO FIRE STATION 47 HVAC REPLACEMENT\_CAD\24-146 E-ROOF - 2025-07-17 - MIGUEL AGUILAR MAMAAN NORCO FIRE STATION 47 HVAC
REPLACEMENT
ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED TO BE USED IN
CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYINGSPECIFICATIONS WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING. 1234567
07-17-2025 DWE PC CORRECTIONS
GENERAL NOTES
CONSTRUCTION NOTES
ELECTRICAL ROOF PLAN
E-3.1
SCALE: 1/8" = 1'-0"
SIGNED:07/17/2025
REVIEWED FOR CODE COMPLIANCE BY:
WILLDAN ENGINEERING
1:59:43 PM Jul 31, 2025
Approval of these plans & specifications shallnot be construed to be a permit for, or anapproval of any violation of any Federal, State,County or City laws or ordinances. One set ofapproved plans must be kept on the job untilcompletion.
MECHANICAL UNIT DISCONNECT 1
SURFACE MNTD. PANEL CONC. FRAMING 2
-4
-5
-6-8
-9
- 10- 12
- 13
- 14- 16- 15 - 11 -7 -3
MECHANICAL UNIT.ROOF STRUCTURE AND FLASHING PER
ARCHITECTURAL PLANS.
VERIFY STRUCTURAL ATTACHMENT WITH
STRUCTURAL ENGINEER.
RECEPTACLE CIRCUIT
CONSTRUCTION NOTES:
1. ALL ROOF PENETRATIONS SHALL
HAVE FLASHING PER THE
ARCHITECTURAL DETAIL.
GENERAL NOTES:
2 123
PROVIDE AND INSTALL
WEATHERPROOF NEMA 3R
DISCONNECT SIZED PER PLAN.
VERIFY REQUIREMENTS WITH
MECHANICAL CONTRACTOR FOR
UNIT LOCATION AND EXACTELECTRICAL REQUIREMENTSPROVIDE EQUIPMENT PERELECTRICAL SPECIFICATIONS.
HVAC UNIT POWER SUPPLY
CONTROL CIRCUIT
HVAC UNIT POWER CIRCUITRECEPTACLE CIRCUIT 3
1 3/8" BOLT SPRING NUT
AND WASHERS (TYPICAL
FOR EACH CORNER)
PANEL (MAX. SIZE:
12"W X 14"H X 6"D
MAX. WEIGHT: 150 LBS.)
P-1000 UNISTRUT,LENGTH AS REQUIRED
3/8" Ø HILTI KB-TZ (ICC #ESR-3785)
MINIMUM 1 1/2" EMBEDMENT AT
EACH OF 4 HOLE LOCATIONS
(E) CONCRETE WALL
FASTEN UNISTRUT TO BUILDING
WALL STUD 4 PLACES
(1 EACH CORNER)
DESIGNED BYDRAWN BYCHECKED BYDATESCALEJOB NO.
SHEET NO.
DATE BY ISSUE FOR
07.26.2024
24-146
ISSUE DATE:REVISION:
NUM. DATE BY REVISION FOR
CONSULTANT
3902 HILLSIDE AVENUE
NORCO, CA 92860
STAMP
San Bernardino, CA 92408
412 E. Vanderbilt Way Phone: 909-890-3700
Fax: 909-890-3770
Email: [email protected]
SHEET TITLEPROJECT TITLE
AS NOTED
R:\_PROJECT\2024\24-146 NORCO FIRE STATION 47 HVAC REPLACEMENT\_CAD\24-146 E-DETAILS - 2025-07-17 - MIGUEL AGUILAR MAMAAN NORCO FIRE STATION 47 HVAC
REPLACEMENT
ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED TO BE USED IN
CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYINGSPECIFICATIONS WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING. 1234567
07-17-2025 DWE PC CORRECTIONS
ELECTRICAL DETAILS
E-4.1
SIGNED:07/17/2025
REVIEWED FOR CODE COMPLIANCE BY:
WILLDAN ENGINEERING
1:59:43 PM Jul 31, 2025
Approval of these plans & specifications shallnot be construed to be a permit for, or anapproval of any violation of any Federal, State,County or City laws or ordinances. One set ofapproved plans must be kept on the job untilcompletion.
DESIGNED BY
DRAWN BYCHECKED BYDATESCALEJOB NO.
SHEET NO.
DATE BY ISSUE FOR
RIL
MAE
RIL
07.26.2024
95-24-10
ISSUE DATE:REVISION:
NUM. DATE BY REVISION FOR
CONSULTANT
3902 HILLSIDE AVENUE
NORCO, CA 92860
STAMP
San Bernardino, CA 92408
412 E. Vanderbilt Way Phone: 909-890-3700
Fax: 909-890-3770
Email: [email protected]
DESIGN WEST ENGINEERING
MECHANICAL ELECTRICAL ENERGY CONSULTANTS
SHEET TITLEPROJECT TITLE
AS NOTED
\\TBSERVER\DROPBOX (T & B ENGINEERING)\T & B ENGINEERING INC\DRAFT AND ENG\JOBS\95-24-10-CITY OF NORCO-NORCO F.S. #47-HVAC REPLACEMENT\_CAD\S0.1 - 2024-08-15 - MARK ERLENDSON NORCO FIRE STATION 47 HVAC
REPLACEMENT
ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED TO BE USED IN
CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYINGSPECIFICATIONS WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING. 1234567
4344 Latham St., Suite 210
Riverside, CA. 92501-1773
P: 951.684.6200
F: 951.684.6226
Job no.
CONSULTING STRUCTURAL ENGINEERS
Engineering, Inc.
95-24-10
GENERAL NOTES
& DETAILS
S0.1
1 07-17-2025 DWE PC CORRECTIONS
REVIEWED FOR CODE COMPLIANCE BY:
WILLDAN ENGINEERING
1:59:43 PM Jul 31, 2025
Approval of these plans & specifications shallnot be construed to be a permit for, or anapproval of any violation of any Federal, State,County or City laws or ordinances. One set ofapproved plans must be kept on the job untilcompletion.
DESIGNED BY
DRAWN BYCHECKED BYDATESCALEJOB NO.
SHEET NO.
DATE BY ISSUE FOR
RIL
MAE
RIL
07.26.2024
95-24-10
ISSUE DATE:REVISION:
NUM. DATE BY REVISION FOR
CONSULTANT
3902 HILLSIDE AVENUE
NORCO, CA 92860
STAMP
San Bernardino, CA 92408
412 E. Vanderbilt Way Phone: 909-890-3700
Fax: 909-890-3770
Email: [email protected]
DESIGN WEST ENGINEERING
MECHANICAL ELECTRICAL ENERGY CONSULTANTS
SHEET TITLEPROJECT TITLE
AS NOTED
\\TBSERVER1\T & B ENGINEERING INC\DRAFT AND ENG\JOBS\95-24-10-CITY OF NORCO-NORCO F.S. #47-HVAC REPLACEMENT\_CAD\S2.1 - 2025-07-16 - MARK ERLENDSON NORCO FIRE STATION 47 HVAC
REPLACEMENT
ALL IDEAS, DESIGNS AND ARRANGEMENTS INDICATED ON THESE DRAWINGS ARE THE PROPERTY OF DESIGN WEST ENGINEERING, INC. AND ARE INTENDED TO BE USED IN
CONNECTION WITH THIS SPECIFIC PROJECT ONLY AND SHALL NOT OTHERWISE BE USED FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. THERE SHALL BE NO CHANGES OR DEVIATIONS FROM THESE DRAWINGS OR ACCOMPANYINGSPECIFICATIONS WITHOUT THE WRITTEN CONSENT OF DESIGN WEST ENGINEERING. 1234567
4344 Latham St., Suite 210
Riverside, CA. 92501-1773
P: 951.684.6200
F: 951.684.6226
Job no.
CONSULTING STRUCTURAL ENGINEERS
Engineering, Inc.
95-24-10
06-10-2025 DWE PC CORRECTIONS
ROOF FRAMING
PLAN
S2.1
1 07-17-2025 DWE PC CORRECTIONS
REVIEWED FOR CODE COMPLIANCE BY:
WILLDAN ENGINEERING
1:59:43 PM Jul 31, 2025
Approval of these plans & specifications shallnot be construed to be a permit for, or anapproval of any violation of any Federal, State,County or City laws or ordinances. One set ofapproved plans must be kept on the job untilcompletion.
City Council
STAFF REPORT
Date: March 18, 2026 Agenda Item:
3.I.
To: Honorable Mayor and City Council Members
From: Amanda Hamilton, Deputy City Manager /
Community Operations Director
Prepared By: Amanda Hamilton, Deputy City Manager /
Community Operations Director
Department: Community Operations
SUBJECT:
Consideration of Resolutions Authorizing the Preparation of the Fiscal Year 2026-2027 Engineer's Reports for Landscape Maintenance Districts 1-5 RECOMMENDATION:
Adopt Resolution No. 2026-13 - A Resolution of the City Council of the City of Norco, California, Ordering the Preparation of the Engineer’s Report for Landscape Maintenance District No. 1 (Beazer, Tract 28765) to Establish Annual Assessments for Fiscal Year 2026-2027.
Adopt Resolution No. 2026-14 - A Resolution of the City Council of the City of Norco, California, Ordering the Preparation of the Engineer’s Report for Landscape Maintenance District No. 2 (Western Pacific, Tract 25779) to Establish Annual Assessments for Fiscal Year 2026-2027.
Adopt Resolution No. 2026-15 - A Resolution of the City Council of the City of Norco, California, Ordering the Preparation of the Engineer’s Report for Landscape Maintenance District No. 3 (Centex, Tract 28626) to Establish Annual Assessments for Fiscal Year 2026-2027.
Adopt Resolution No. 2026-16 - A Resolution of the City Council of the City of Norco, California, Ordering the Preparation of the Engineer’s Report for Landscape Maintenance District No. 4 (Norco Ridge Ranch, Tracts 29588 and 29589) to Establish Annual Assessments for Fiscal Year 2026-2027.
Adopt Resolution No. 2026-17 - A Resolution of the City Council of the City of Norco, California, Ordering the Preparation of the Engineer’s Report for Landscape Maintenance District No. 5 (Hawks Crest – Tract 30230) to Establish Annual Assessments for Fiscal Year 2026-2027.
SUMMARY:
The City of Norco has engaged Webb Municipal Finance, LLC, to assist with the Annual Levy process for all five Landscape Maintenance Districts (LMDs), including preparing and filing Engineer’s Reports with the City Clerk and Riverside County AuditorController. To continue the levy, the City Council must adopt the necessary resolutions, order and approve the preliminary Engineer’s Reports, set and conduct a public hearing, and levy assessments with provisions for annual increases. The reports will comply with Proposition 218 and include descriptions of improvements, cost estimates, apportionment methods, and assessment rolls. The City Council may authorize Webb Municipal Finance, LLC, to prepare and file the Engineer’s Reports for Fiscal Year 2026-2027.
BACKGROUND:
Pursuant to the provisions of California Streets and Highways Code sections 22500- 22679 (the "Act"), the City of Norco has retained Webb Municipal Finance, LLC, for the third consecutive year to assist with the Annual Levy process for all five LMDs within the City. This engagement encompasses the preparation and filing of the Engineer's Reports with the City Clerk, as well as the submission of the annual levy to the Riverside County Auditor-Controller for the purposes of assessment collection.
The Act authorizes the County of Riverside to levy and collect assessments on behalf of the City of Norco to fund the maintenance and servicing of improvements related to landscaping, parks, and recreational facilities. The assessments are applied to the following established Landscape Maintenance Districts:
Landscape Maintenance District No. 1 (Beazer)
Landscape Maintenance District No. 2 (Western Pacific) Landscape Maintenance District No. 3 (Centex)
Landscape Maintenance District No. 4 (Norco Ridge Ranch) Landscape Maintenance District No. 5 (Hawks Crest)
The funds generated through these assessments are dedicated to the installation, construction, and ongoing maintenance of the improvements within each district, ensuring the continued upkeep of the City’s landscape and recreational facilities.
Annual Assessment Process
In order to continue the levy of assessments for the aforementioned Landscape Maintenance Districts, the City Council must, in accordance with the Act and the Assessment Law, undertake the following proceedings each year:
1. Resolution Initiating the Preparation of the Engineer's Reports
2. Preparation of Engineer’s Reports
3. Adoption of Resolution of Intention Approving the Preliminary Engineer's Reports
4. Adoption of Resolution Setting the Public Hearing
5. Hold the Public Hearing
6. Adoption of Resolution Levying the Assessments
The Landscape Maintenance Districts are established with provisions that permit annual increases in assessments. Furthermore, the Engineer’s Reports shall comply with the requirements of Article XIIID of the California Constitution, as enacted by Proposition 218, the "Right to Vote on Taxes Act" (approved by California voters on November 5, 1996).
Engineer’s Report Requirements
In compliance with the Act, an Engineer’s Reports will be prepared for each of the five districts. Each report shall include the following:
A description of the improvements or services to be financed; An estimate of the cost associated with each improvement or service; An assessment diagram depicting the boundaries of each district and the parcels within such boundaries;
A description of the methodology employed to apportion assessments to properties within each district;
An assessment roll listing the parcels to be assessed and the proposed assessment for each parcel.
The completed Engineer’s Reports will be presented to the City Council for review and approval in May.
It is hereby recommended that the City Council adopt the five resolutions necessary to initiate the proceedings for the preparation of the Engineer’s Annual Levy Reports for the fiscal year commencing July 1, 2026, and ending June 30, 2027. The City Council is further requested to authorize Webb Municipal Finance, LLC, to prepare and file the required Engineer’s Reports concerning the levy and collection of assessments for the five districts in accordance with Chapter 3, Section 22622 of the Act. A proposal outlining the scope of work to be performed by Webb Municipal Finance, LLC, is attached hereto for the Council’s consideration.
FISCAL IMPACT:
The cost of professional services required to initiate proceedings for the levy and collection of assessments for the Fiscal Year 2026-2027 Districts' Annual Levy authorization, in the amount of $20,288, is allocated within the Fiscal Year 2025-2026 budget for the administration of the Districts. This cost will be apportioned and paid by each individual District.
RELATIONSHIP TO STRATEGIC PLAN:
This item is consistent with Strategic Direction No. 3, "Economic Development and Financial Stability."
REVIEWED AND APPROVED BY:
Certified as to Availability of Funds: Joshua Calhoun, Finance Director Approved by: Lisette Free, City Manager
Approved as to Form: Harper and Burns, LLP, City Attorney ATTACHMENT(S):
Resolution 2026-13 LMD No. 1 Initiating Proceedings FY 26_27 Resolution 2026-14 LMD No. 2 Initiating Proceedings FY 26_27 Resolution 2026-15 LMD No. 3 Initiating Proceedings FY 26_27 Resolution 2026-16 LMD No. 4 Initiating Proceedings FY 26_27 Resolution 2026-17 LMD No. 5 Initiating Proceedings FY 26_27 Proposal - FY 26-27 LMD Annual Administration
RESOLUTION NO. 2026-13
A RESOLUTION OF THE CITY COUNCIL OF THE CITY OF NORCO,
CALIFORNIA, ORDERING THE PREPARATION OF THE ENGINEER’S
REPORT FOR LANDSCAPE MAINTENANCE DISTRICT NO. 1
(BEAZER, TRACT 28765) TO ESTABLISH ANNUAL ASSESSMENTS
FOR FISCAL YEAR 2026-2027.
WHEREAS, the City Council of the City of Norco, California, (hereinafter the “City Council”), has by previous Resolution established the Landscape Maintenance District No. 1, pursuant to the provisions of the Landscaping and Light Act of 1972, Part 2 of Division 15 of the Streets and Highways Code of the State of California, beginning with §22500 (hereafter referred to as the “Act”), that provides for the levy and collection of assessments by the City of Norco to pay for the maintenance and services of improvements and all appurtenant facilities and operations related thereto; and
WHEREAS, §22566 and §22622 of the Act requires the preparation of an Engineer’s Report to determine and adjust the annual assessment rates for Landscape Maintenance District No. 1;
NOW, THEREFORE BE IT RESOLVED, DETERMINED, AND ORDERED BY THE CITY COUNCIL, AS FOLLOWS:
Section 1: Webb Municipal Finance, LLC is hereby ordered to prepare and appropriately file the Engineer’s Report required to determine and adjust the Landscape Maintenance District No. 1 assessments for Fiscal Year 2026-2027 in accordance with §22566 and §22622 of the Act. The Engineer’s Report shall be filed with the City Clerk for submission to the City Council.
Section 2. The improvements to be operated and maintained by Landscape Maintenance District No. 1 generally include the operation, administration, maintenance, and servicing of improvements, and appurtenant facilities and expenses associated with Landscape Maintenance District No. 1 that will be maintained by the City of Norco through annual assessments.
Section 3. The improvements to be maintained by the City of Norco for Fiscal Year 2026-2027 are substantially the same as the improvements provided and maintained in the previous Fiscal Year and the Engineer’s Report for Landscape Maintenance District No. 1 prepared in connection therewith shall describe the improvements as required by the Act.
Section 4. The Engineer’s Report for Landscape Maintenance District No. 1 shall reflect provisions and related assessments in accordance with the requirements of Article XIIID of the California Constitution as enacted by the passage of
Proposition 218, also referred to as “The Right to Vote on Taxes Act,” as approved by the voters of the State of California on November 5, 1996.
Section 5. The Engineer’s Report for Landscape Maintenance District No. 1 shall be titled: “City of Norco, Landscape Maintenance District No. 1, Engineer’s Report, Fiscal Year 2026-2027.”
Section 6. The City Clerk shall certify to the adoption of this Resolution.
PASSED AND ADOPTED by the City Council of the City of Norco, California, at a regular meeting held on March 18, 2026.
____________________________________
Robin Grundmeyer, Mayor
City of Norco, California
____________________________________
Janet Martinez, Interim City Clerk
City of Norco, California
I, Janet Martinez, Interim City Clerk of the City of Norco, California, do hereby certify that the foregoing Resolution was adopted by the City Council of the City of Norco, California, at a regular meeting thereof held on March 18, 2026, by the following vote of the City Council:
AYES:
NOES:
ABSENT:
ABSTAIN:
IN WITNESS WHEREOF, I have hereunto set my hand affixed the official seal of the City of Norco, California, held on March 18, 2026.
____________________________________
Janet Martinez, Interim City Clerk
City of Norco, California
RESOLUTION NO. 2026-14
A RESOLUTION OF THE CITY COUNCIL OF THE CITY OF NORCO,
CALIFORNIA, ORDERING THE PREPARATION OF THE ENGINEER’S
REPORT FOR LANDSCAPE MAINTENANCE DISTRICT NO. 2
(WESTERN PACIFIC, TRACT 25779) TO ESTABLISH ANNUAL
ASSESSMENTS FOR FISCAL YEAR 2026-2027.
WHEREAS, the City Council of the City of Norco, California, (hereinafter the “City Council”), has by previous Resolution established the Landscape Maintenance District No. 2, pursuant to the provisions of the Landscaping and Light Act of 1972, Part 2 of Division 15 of the Streets and Highways Code of the State of California, beginning with §22500 (hereafter referred to as the “Act”), that provides for the levy and collection of assessments by the City of Norco to pay for the maintenance and services of improvements and all appurtenant facilities and operations related thereto; and
WHEREAS, §22566 and §22622 of the Act requires the preparation of an Engineer’s Report to determine and adjust the annual assessment rates for Landscape Maintenance District No. 2;
NOW, THEREFORE BE IT RESOLVED, DETERMINED, AND ORDERED BY THE CITY COUNCIL, AS FOLLOWS:
Section 1: Webb Municipal Finance, LLC is hereby ordered to prepare and appropriately file the Engineer’s Report required to determine and adjust the Landscape Maintenance District No. 2 assessments for Fiscal Year 2026-2027 in accordance with §22566 and §22622 of the Act. The Engineer’s Report shall be filed with the City Clerk for submission to the City Council.
Section 2. The improvements to be operated and maintained by Landscape Maintenance District No. 2 generally include the operation, administration, maintenance, and servicing of improvements, and appurtenant facilities and expenses associated with Landscape Maintenance District No. 2 that will be maintained by the City of Norco through annual assessments.
Section 3. The improvements to be maintained by the City of Norco for Fiscal Year 2026-2027 are substantially the same as the improvements provided in the previous Fiscal Year and the Engineer’s Report for Landscape Maintenance District No. 2 prepared in connection therewith shall describe the improvements as required by the Act.”
Section 4. The Engineer’s Report for Landscape Maintenance District No. 2 shall reflect provisions and related assessments in accordance with the requirements of Article XIIID of the California Constitution as enacted by the passage of Proposition 218, also referred to as “The Right to Vote on Taxes Act,” as approved by the voters of the State of California on November 5, 1996.
Section 5. The Engineer’s Report for Landscape Maintenance District No. 2 shall be titled: “City of Norco, Landscape Maintenance District No. 2, Engineer’s Report, Fiscal Year 2026-2027.”
Section 6. The City Clerk shall certify to the adoption of this Resolution.
PASSED AND ADOPTED by the City Council of the City of Norco, California, at a regular meeting held on March 18, 2026.
____________________________________
Robin Grundmeyer, Mayor
City of Norco, California
____________________________________
Janet Martinez, Interim City Clerk
City of Norco, California
I, Janet Martinez, Interim City Clerk of the City of Norco, California, do hereby certify that the foregoing Resolution was adopted by the City Council of the City of Norco, California, at a regular meeting thereof held on March 18, 2026, by the following vote of the City Council:
AYES:
NOES:
ABSENT:
ABSTAIN:
IN WITNESS WHEREOF, I have hereunto set my hand affixed the official seal of the City of Norco, California, held on March 18, 2026.
____________________________________
Janet Martinez, Interim City Clerk
City of Norco, California
RESOLUTION NO. 2026-15
A RESOLUTION OF THE CITY COUNCIL OF THE CITY OF NORCO,
CALIFORNIA, ORDERING THE PREPARATION OF THE ENGINEER’S
REPORT FOR LANDSCAPE MAINTENANCE DISTRICT NO. 3
(CENTEX, TRACT 28626) TO ESTABLISH ANNUAL ASSESSMENTS
FOR FISCAL YEAR 2026-2027.
WHEREAS, the City Council of the City of Norco, California, (hereinafter the “City Council”), has by previous Resolution established the Landscape Maintenance District No. 3, pursuant to the provisions of the Landscaping and Light Act of 1972, Part 2 of Division 15 of the Streets and Highways Code of the State of California, beginning with §22500 (hereafter referred to as the “Act”), that provides for the levy and collection of assessments by the City of Norco to pay for the maintenance and services of improvements and all appurtenant facilities and operations related thereto; and
WHEREAS, §22566 and §22622 of the Act requires the preparation of an Engineer’s Report to determine and adjust the annual assessment rates for Landscape Maintenance District No. 3;
NOW, THEREFORE BE IT RESOLVED, DETERMINED, AND ORDERED BY THE CITY COUNCIL, AS FOLLOWS:
Section 1: Webb Municipal Finance, LLC is hereby ordered to prepare and appropriately file the Engineer’s Report required to determine and adjust the Landscape Maintenance District No. 3 assessments for Fiscal Year 2026-2027 in accordance with §22566 and §22622 of the Act. The Engineer’s Report shall be filed with the City Clerk for submission to the City Council.
Section 2. The improvements to be operated and maintained by Landscape Maintenance District No. 3 generally include the operation, administration, maintenance, and servicing of improvements, and appurtenant facilities and expenses associated with Landscape Maintenance District No. 3 that will be maintained by the City of Norco through annual assessments.
Section 3. The improvements to be maintained by the City of Norco for Fiscal Year 2026-2027 are substantially the same as the improvements provided in the previous Fiscal Year and the Engineer’s Report for Landscape Maintenance District No. 3 prepared in connection therewith shall describe the improvements as required by the Act.”
Section 4. The Engineer’s Report for Landscape Maintenance District No. 3 shall reflect provisions and related assessments in accordance with the requirements of Article XIIID of the California Constitution as enacted by the passage of
Proposition 218, also referred to as “The Right to Vote on Taxes Act,” as approved by the voters of the State of California on November 5, 1996.
Section 5. The Engineer’s Report for Landscape Maintenance District No. 3 shall be titled: “City of Norco, Landscape Maintenance District No. 3, Engineer’s Report, Fiscal Year 2026-2027.”
Section 6. The City Clerk shall certify to the adoption of this Resolution.
PASSED AND ADOPTED by the City Council of the City of Norco, California, at a regular meeting held on March 18, 2026.
____________________________________
Robin Grundmeyer, Mayor
City of Norco, California
____________________________________
Janet Martinez, Interim City Clerk
City of Norco, California
I, Janet Martinez, Interim City Clerk of the City of Norco, California, do hereby certify that the foregoing Resolution was adopted by the City Council of the City of Norco, California, at a regular meeting thereof held on March 18, 2026, by the following vote of the City Council:
AYES:
NOES:
ABSENT:
ABSTAIN:
IN WITNESS WHEREOF, I have hereunto set my hand affixed the official seal of the City of Norco, California, held on March 18, 2026.
____________________________________
Janet Martinez, Interim City Clerk
City of Norco, California
RESOLUTION NO. 2026-16
A RESOLUTION OF THE CITY COUNCIL OF THE CITY OF NORCO,
CALIFORNIA, ORDERING THE PREPARATION OF THE ENGINEER’S
REPORT FOR LANDSCAPE MAINTENANCE DISTRICT NO. 4 (NORCO
RIDGE RANCH, TRACTS 29588 AND 29589) TO ESTABLISH ANNUAL ASSESSMENTS FOR FISCAL YEAR 2026-2027.
WHEREAS, the City Council of the City of Norco, California, (hereinafter the “City Council”), has by previous Resolution established the Landscape Maintenance District No. 4, pursuant to the provisions of the Landscaping and Light Act of 1972, Part 2 of Division 15 of the Streets and Highways Code of the State of California, beginning with §22500 (hereafter referred to as the “Act”), that provides for the levy and collection of assessments by the City of Norco to pay for the maintenance and services of improvements and all appurtenant facilities and operations related thereto; and
WHEREAS, §22566 and §22622 of the Act requires the preparation of an Engineer’s Report to determine and adjust the annual assessment rates for Landscape Maintenance District No. 4;
NOW, THEREFORE BE IT RESOLVED, DETERMINED, AND ORDERED BY THE CITY COUNCIL, AS FOLLOWS:
Section 1: Webb Municipal Finance, LLC is hereby ordered to prepare and appropriately file the Engineer’s Report required to determine and adjust the Landscape Maintenance District No. 4 assessments for Fiscal Year 2026-2027 in accordance with §22566 and §22622 of the Act. The Engineer’s Report shall be filed with the City Clerk for submission to the City Council.
Section 2. The improvements to be operated and maintained by Landscape Maintenance District No. 4 generally include the operation, administration, maintenance, and servicing of improvements, and appurtenant facilities and expenses associated with Landscape Maintenance District No. 4 that will be maintained by the City of Norco through annual assessments.
Section 3. The improvements to be maintained by the City of Norco for Fiscal Year 2026-2027 are substantially the same as the improvements provided and maintained in the previous Fiscal Year and the Engineer’s Report for Landscape Maintenance District No. 4 prepared in connection therewith shall describe the improvements as required by the Act.
Section 4. The Engineer’s Report for Landscape Maintenance District No. 4 shall reflect provisions and related assessments in accordance with the requirements of Article XIIID of the California Constitution as enacted by the passage of
Proposition 218, also referred to as “The Right to Vote on Taxes Act,” as approved by the voters of the State of California on November 5, 1996.
Section 5. The Engineer’s Report for Landscape Maintenance District No. 4 shall be titled: “City of Norco, Landscape Maintenance District No. 4, Engineer’s Report, Fiscal Year 2026-2027.”
Section 6. The City Clerk shall certify to the adoption of this Resolution.
PASSED AND ADOPTED by the City Council of the City of Norco, California, at a regular meeting held on March 18, 2026.
____________________________________
Robin Grundmeyer, Mayor
City of Norco, California
____________________________________
Janet Martinez, Interim City Clerk
City of Norco, California
I, Janet Martinez, Interim City Clerk of the City of Norco, California, do hereby certify that the foregoing Resolution was adopted by the City Council of the City of Norco, California, at a regular meeting thereof held on March 18, 2026, by the following vote of the City Council:
AYES:
NOES:
ABSENT:
ABSTAIN:
IN WITNESS WHEREOF, I have hereunto set my hand affixed the official seal of the City of Norco, California, held on March 18, 2026.
____________________________________
Janet Martinez, Interim City Clerk
City of Norco, California
RESOLUTION NO. 2026-17
A RESOLUTION OF THE CITY COUNCIL OF THE CITY OF NORCO,
CALIFORNIA, ORDERING THE PREPARATION OF THE ENGINEER’S
REPORT FOR LANDSCAPE MAINTENANCE DISTRICT NO. 5 (HAWKS
CREST, TRACT 30230) TO ESTABLISH ANNUAL ASSESSMENTS FOR FISCAL YEAR 2026-2027.
WHEREAS, the City Council of the City of Norco, California, (hereinafter the “City Council”), has by previous Resolution established the Landscape Maintenance District No. 5, pursuant to the provisions of the Landscaping and Light Act of 1972, Part 2 of Division 15 of the Streets and Highways Code of the State of California, beginning with §22500 (hereafter referred to as the “Act”), that provides for the levy and collection of assessments by the City of Norco to pay for the maintenance and services of improvements and all appurtenant facilities and operations related thereto; and
WHEREAS, §22566 and §22622 of the Act requires the preparation of an Engineer’s Report to determine and adjust the annual assessment rates for Landscape Maintenance District No. 5;
NOW, THEREFORE BE IT RESOLVED, DETERMINED, AND ORDERED BY THE CITY COUNCIL, AS FOLLOWS:
Section 1: Webb Municipal Finance, LLC is hereby ordered to prepare and appropriately file the Engineer’s Report required to determine and adjust the Landscape Maintenance District No. 5 assessments for Fiscal Year 2026-2027 in accordance with §22566 and §22622 of the Act. The Engineer’s Report shall be filed with the City Clerk for submission to the City Council.
Section 2. The improvements to be operated and maintained by Landscape Maintenance District No. 5 generally include the operation, administration, maintenance, and servicing of improvements, and appurtenant facilities and expenses associated with Landscape Maintenance District No. 5 that will be maintained by the City of Norco through annual assessments.
Section 3. The improvements to be maintained by the City of Norco for Fiscal Year 2026-2027 are substantially the same as the improvements provided and maintained in the previous Fiscal Year and the Engineer’s Report for Landscape Maintenance District No. 5 prepared in connection therewith shall describe the improvements as required by the Act.
Section 4. The Engineer’s Report for Landscape Maintenance District No. 5 shall reflect provisions and related assessments in accordance with the requirements of Article XIIID of the California Constitution as enacted by the passage of
Proposition 218, also referred to as “The Right to Vote on Taxes Act,” as approved by the voters of the State of California on November 5, 1996.
Section 5. The Engineer’s Report for Landscape Maintenance District No. 5 shall be titled: “City of Norco, Landscape Maintenance District No. 5, Engineer’s Report, Fiscal Year 2026-2027.”
Section 6. The City Clerk shall certify to the adoption of this Resolution.
PASSED AND ADOPTED by the City Council of the City of Norco, California, at a regular meeting held on March 18, 2026.
____________________________________
Robin Grundmeyer, Mayor
City of Norco, California
____________________________________
Janet Martinez, Interim City Clerk
City of Norco, California
I, Janet Martinez, Interim City Clerk of the City of Norco, California, do hereby certify that the foregoing Resolution was adopted by the City Council of the City of Norco, California, at a regular meeting thereof held on March 18, 2026, by the following vote of the City Council:
AYES:
NOES:
ABSENT:
ABSTAIN:
IN WITNESS WHEREOF, I have hereunto set my hand affixed the official seal of the City of Norco, California, held on March 18, 2026.
____________________________________
Janet Martinez, Interim City Clerk
City of Norco, California
3788 McCray Street
Riverside, CA 92506
951.200.8600
January 29, 2026
City of Norco
Amanda Hamilton
Facilities & Maintenance Director
2870 Clark Avenue
Norco, CA 92860
RE: Landscape Maintenance Districts FY 26-27 Annual Administration Services Dear Ms. Hamilton:
Webb Municipal Finance, LLC (WMF) is grateful to have the opportunity to continue to work with the City of Norco (the “City”) providing annual administration of Landscape Maintenance District Nos. 1, 2, 3, 4, and 5 (“LMDs”).
We are confident that our project team has the technical expertise, resources, knowledge, relationships and most importantly, the commitment to complete your administration projects on time and within budget. We will tailor solutions to meet your needs.
Our Scope of Services for the LMDs’ annual administration is as shown below:
Kickoff Meeting: The purpose of this meeting is to coordinate with the City to gain an understanding of the specific goals, components and criteria to meet the City’s needs. To that end, WMF will meet with the City staff to confirm the schedule of events, procedural considerations and discuss the City’s preferred method of communication.
Budget Review and Preparation: WMF will review and prepare a budget for each LMD based on the cost estimates for maintenance of all improvements, landscaping, capital improvements and incidental costs, as well as operating and capital improvement reserves. For the LMDs where costs exceed the maximum allowable assessments, WMF will factor into the budget the necessary cuts to bring the expenses in line with the assessments.
Annual District Engineering and Engineer’s Report Preparation: Prior to the annual public hearing confirming the LMDs assessments, WMF will file the Engineer’s Reports with the City Clerk. The Engineer’s Reports will include the fiscal year’s budget information, the listing of improvements to be maintained by the collection of the special assessments, the benefit spread methodology, a copy of plans and specifications, estimates of the costs, assessment diagrams, and complete listings of parcels to be assessed and their total assessments. The reports will be prepared in accordance with California Code. WMF’s Engineer’s Reports will include a statement of engineer signed by a Professional Engineer verifying the accuracy of the report. The original copy of the Engineer’s Report will be provided to the City.
Preparation of Resolutions: WMF, in coordination with the City Attorney and City Staff, will assist in the preparation of all resolutions and staff reports needed for the annual administration process.
Meeting Attendance: For each item requiring City Council action, WMF will attend all City Council Meetings pertaining to the LMDs. WMF will provide a PowerPoint presentation for City Staff to present at the Council Meetings and be available to answer any questions posed by City Staff, City Council Members, or the public. As requested by City Staff, WMF will be available to attend all Property Owner Meetings regarding the LMDs’ annual assessments and answer questions.
Annual Special Assessment Submittal: WMF will calculate and submit the annual levy for the LMDsto the Riverside County Auditor-Controller. Included with the annual levy submittal is the preparation of direct invoices (handbills) to all public agencies whose properties are determined to receive a direct benefit from the public improvements.
WMF will submit the annual levies for the LMDs in the media format, and configuration acceptable for direct submission to the Riverside County Auditor-Controller’s Office prior to the statutory deadline and shall perform adjustments and corrections to the levies on the property tax rolls as necessary.
District Mapping: WMF will obtain the latest assessor’s parcel maps and secured tax roll information from the Riverside County Assessor’s Office for the parcels within the LMDsto identify parcel changes each year. Each year, WMF will provide updated GIS maps and audit maps for the City’s use.
Annual Special Assessment Calculation: As requested by the City, WMF will audit the assessment calculations which include (but are not limited to) the review of EDU computations, parcel acreage, development status, and the taxability status of each parcel.
Property Owner Letters: WMF will assist City Staff with the preparation of property owner letters for applicable LMDs. WMF will generate a mailing list for each applicable district to include current property owner names and mailing addresses using the latest assessor’s parcel maps and Riverside County Assessor’s data as well as our inhouse GIS platform.
Property Owner Services: WMF will serve as the initial and primary contact to City Staff, property owners, title companies, and other interested parties for inquiries regarding the LMDs administration and annual special assessment installments. A toll-free telephone number, of WMF designation, will appear on the regular property tax bill next to each LMD’s line item to facilitate contact with the public.
Roll Changes and Adjusted Property Tax Bills: If any changes to the secured tax roll necessitate corrections/revisions after the deadline are determined necessary, WMF will research, recalculate and, with City approval, rectify the issue. We notify the City of the assessor’s parcel numbers that were rejected by the County and therefore will not be assessed.
COMPENSATION
We propose to be compensated a fixed fee for services performed according to the schedule outlined as follows:
FIXED FEE SCHEDULE
Annual Administrative Services Fee (1)
Landscape Maintenance District No. 1 $1,560.60
Landscape Maintenance District No. 2 $5,202.00
Landscape Maintenance District No. 3 $4,161.60
Landscape Maintenance District No. 4 $5,722.20
Landscape Maintenance District No. 5 $3,641.40
Total $20,287.80
(1) Our proposed fees escalate by 2% annually.
For services performed related to the projects which are not listed herein, compensation shall be at the hourly rates set forth on Attachment A, together with reimbursement, at cost, for incidental expenses incurred in connection with such services, together with reimbursement for outside services at cost plus 15%.
We look forward to continuing to build a strong relationship with the City. If you have any questions or require additional information, please feel free to call me at (951) 320-6069.
Sincerely,
WMF MUNICIPAL FINANCE, LLC
Charmaine McCarvel
Assessment Manager
CONCURRENCE OF THE CITY OF NORCO
This authorizes WMF Municipal Finance, LLC to proceed with the administration for FY 2026-2027 and bill a total of $20,287.80 for the annual administration of the City’s Landscape Maintenance Districts. _________________________________________
City of Norco
Amanda Hamilton
Facilities & Maintenance Director
City Council
STAFF REPORT
Date: March 18, 2026 Agenda Item:
3.J.
To: Honorable Mayor and City Council Members
From: Colby Cataldi, Community Development Director
Prepared By: Erika Woods-Diaz, Associate Planner
Department: Community Development
SUBJECT:
Adopt Resolution No. 2026-18 denying Accessory Building Use Permit 2025-04 (Ursu) request to allow a 1,000 square foot Large Vehicle Parking Building with an attached 392 square foot shop area located at 4077 Temescal Avenue within the A-1-20 Zone (APN: 133-101-004).
RECOMMENDATION:
Adopt Resolution No. 2026-18 denying Accessory Building Use Permit 2025-04 (Ursu).
SUMMARY:
Resolution No. 2026-18 upholds City Council’s March 4, 2026 approval to appeal Planning Commission’s January 14, 2026 approval and hereby denies Accessory Building Use Permit No. 2025-04.
BACKGROUND:
The Planning Commission considered Accessory Building Use Permit No. 2025-04 on January 14, 2026, for the construction of a 1,000-square-foot large vehicle garage with an additional 392-square-foot shop area, and approved the request.
On January 21, 2026, the City Council appealed the Planning Commission’s determination, citing concerns regarding the justification of the findings required to approve the permit.
On March 4, 2026, the City Council reviewed the project information associated with Accessory Building Use Permit No. 2025-04 and considered all written and oral evidence in the record, including the Planning Commission’s action date January 21, 2026. Based on its independent review of the application and required findings, the City Council determined that findings could not be made to support the project.
Therefore, City Council voted to uphold the appeal of Planning Commission's determination and are taking action to adopt Resolution No. 2026-18, denying Accessory Building Use Permit No. 2025-04.
FISCAL IMPACT:
This agenda item will not result in a fiscal impact.
RELATIONSHIP TO STRATEGIC PLAN:
This item is consistent with Strategic No. 3 - "Economic Development and Financial Stability".
REVIEWED AND APPROVED BY:
Certified as to Availability of Funds: Joshua Calhoun, Finance Director Approved by: Lisette Free, City Manager
Approved as to Form: Harper and Burns, LLP, City Attorney ATTACHMENT(S):
RESOLUTION 2026-18 Accessory Building Use Permit 2025-04
RESOLUTION 2026-18
A RESOLUTION OF THE CITY COUNCIL OF THE CITY OF NORCO,
CALIFORNIA DENYING AN ACCESSORY BUILDING USE PERMIT TO
ALLOW A 1,000 SQUARE FOOT LARGE VEHICLE PARKING BUILDING WITH AN ATTACHED 392 SQUARE FOOT SHOP AREA AT 4077
TEMESCAL AVENUE LOCATED WITHIN THE A-1-20 ZONE.
ACCESSORY BUILDING USE PERMIT 2025-04. (APN 133-101-004) WHEREAS, Sam and Katie Ursu submitted an application for an Accessory Building Use Permit to the City of Norco, California under the provisions of Chapter 18.68, Title 18 of the Norco Municipal Code, on property located at 4077 Temescal Avenue (APN 133-101-004); and
WHEREAS, on January 14, 2026, within the Council Chambers at 2820 Clark Avenue, Norco, California, 92860, said application was heard by the Planning Commission for the City of Norco; and
WHEREAS, at said time and place set, said Planning Commission considered the aforesaid application and received both oral and written testimony pertaining to said application; and
WHEREAS, after consideration of all written and oral public testimony, said Accessory Building Use Permit 2025-04 was approved by the Planning Commission; and WHEREAS, said approval of Accessory Building Use Permit 2025-04 was appealed by the City Council;
WHEREAS, said appeal was duly submitted to said City’s City Council for decision at a public hearing for which proper notice was given; and WHEREAS, said appeal of Accessory Building Use Permit 2025-04 was scheduled for a public hearing on March 4, 2026, on or about 7:00 p.m. in the Council Chambers at 2820 Clark Avenue, Norco, California 92860; and
WHEREAS, at the time set, the City Council held a public hearing and received both oral and written testimony pertaining to Accessory Building Use Permit 2025-04; and WHEREAS, the City of Norco, acting as the Lead Agency, has determined that the proposed project is exempt from environmental assessment.
NOW, THEREFORE, the City Council of the City of Norco does hereby find as follows:
Resolution 2026-18 Accessory Building Use Permit 2025-04
March 18, 2026
FINDINGS:
A. The requested accessory building use permit is not consistent with the General Plan and zoning requirements of the zone in which the property is located, including the protection of adequate open animal areas on lots where the keeping of large animals is permitted. Further, the property is being used as a business, and not in a manner that is compatible with the general plan and zoning of the zone in which the property is located.
B. The requested accessory building use permit will have an adverse effect on the public convenience or general welfare of persons residing or working in the neighborhood and will adversely affect adjoining land uses, including runoff and drainage impacts and architectural compatibility.
NOW, THEREFORE, the City Council of the City of Norco, hereby resolves as follows:
SECTION 1: The City Council of the City of Norco, California, in session assembled on March 4, 2026, overturned the Planning Commission’s determination approving the aforesaid application for an Accessory Building Use Permit and denies said application.
SECTION 2: EFFECTIVE DATE. This resolution shall become effective upon approval by the City Council of the City of Norco.
SECTION 3: NOTICE IS HEREBY GIVEN that this decision is final. The time within which judicial review must be sought is governed by California Code of Civil Procedure section1094.6.
SECTION 4: This notice triggers the running of the 90-day SOL and should be provided on any "final" administrative hearing decision (i.e., a due process hearing where evidence is taken and decision rendered). A decision is "final" when there are no additional options for appeal at the City level.
Resolution 2026-18 Accessory Building Use Permit 2025-04
March 18, 2026
PASSED AND ADOPTED by the City Council of the City of Norco, California, at a regular meeting held on March 18, 2026.
__________________________
Robin Grundmeyer, Mayor
City of Norco, California
ATTEST:
________________________
Janet Martinez, Interim City Clerk
City of Norco, California
I, Janet Martinez, Interim City Clerk of the City of Norco, California, do hereby certify that the foregoing resolution was adopted at a regular meeting of the City Council of the City of Norco, California, duly held on March 18, 2026, by the following roll call vote of the City Council:
AYES:
NOES:
ABSENT:
ABSTAIN:
IN WITNESS THEREOF, I have hereunto set my hand and affixed the official seal of the City of Norco, California, on March 18, 2026. _______________________
Janet Martinez, Interim City Clerk
City of Norco, California
City Council
STAFF REPORT
Date: March 18, 2026 Agenda Item:
3.K.
To: Honorable Mayor and City Council Members
From: Colby Cataldi, Community Development Director
Prepared By: Lacey David, Senior Community Development
Specialist
Department: Community Development
SUBJECT:
Recap of Actions Taken by the Planning Commission at its Meeting Held on March 11, 2026
RECOMMENDATION:
Receive and file the recap of actions taken by the Planning Commission at its meeting held on March 11, 2026.
REVIEWED AND APPROVED BY:
Approved by: Lisette Free, City Manager
ATTACHMENT(S):
DRAFT Planning Commission Minutes - Mar 11 2026
DRAFT MINUTES
Planning Commission
Wednesday, March 11, 2026
City Council Chamber – Norco City Hall
2820 Clark Avenue, Norco, CA 92860
CALL TO ORDER 7:00 PM
ROLL CALL Patricia Hedges, Chair
Jeff Shyu, Vice Chair
Shannon Chudzicki, Member
Catherine Fiore, Member
Dennis Hutnik, Member
PLEDGE OF ALLEGIANCE by Member Hutnik
1. PUBLIC COMMENTS
There were no speakers present.
2. CONSENT CALENDAR
2.A. Planning Commission Meeting Minutes for February 11, 2026 M/S SHYU/HUTNIK to approve the Planning Commission Meeting Minutes of February 11, 2026. The Motion was carried by the following roll call vote:
AYES: HEDGES, SHYU, CHUDZICKI, AND HUTNIK
NOES: NONE
ABSENT: FIORE
ABSTAIN: NONE
4. DISCUSSION / ACTION ITEM(S)
Planning Commissioner Fiore arrived at 7:07 p.m.
4.A. Accessory Building Use Permit 2025-13 (Barber): A request to allow a 1,000 square-foot Large Vehicle Parking Building with an attached 400 square-foot shop area located at 2313 Hillside Avenue (APN: 123-210-012), within the A-1- 20 zone.
Planning Commission Minutes - March 11, 2026
Assistant Planner Martin presented the staff report on file, and a presentation was available.
Vice Chair Shyu noted that the plans show an option for a bathtub, Assistant Planner Martin noted that the bathtub was removed and a tub is not allowed.
Member Hutnik questioned notes on the site plan, Assistant Planner Martin noted that it's an easement. Director Cataldi explained that it would be reviewed in plan check. Member Hutnik questioned about the sewer connection, Director Cataldi noted those items would be reviewed in plan check by staff.
Applicant present, explained the building meets all the requirements.
Vice Chair Shyu asked the applicant if he would reduce the bathroom size to 5x5, applicant agreed.
Bill Naylor noted the issue with the easement.
Vice Chair Shyu requested the bathroom be reduced, all agreed.
M/S SHYU/FIORE to approve Accessory Building Use Permit 2025-13 (Barber) subject to the attached Conditions of Approval on Resolution 2026-08 with the added condition that the bathroom be reduced to a 5x5. The Motion was carried by the following roll call vote:
AYES: HEDGES, SHYU, CHUDZICKI, FIORE, AND HUTNIK
NOES: NONE
ABSENT: NONE
ABSTAIN: NONE
4.B. Accessory Building Use Permit 2025-19 (Lopez): A request to allow a 1,000 square foot large vehicle garage with an additional 400 square-foot workshop located on 3192 Sunset Court within the A-E zone (APN 130-330-008).
Associate Planner Diaz presented the staff report on file and a presentation was available.
Vice Chair Shyu noted that the elevations call out a 1:12 slope, Associate Planner Diaz noted that there was a clerical error. Vice Chair Shyu requested that the elevations go back to ARC, Director Cataldi explained that there is no concern, and will allow for a secondary review by ARC.
Planning Commission Minutes - March 11, 2026
Bill Naylor noted the access path is not 15 feet and the issue with the eave of the building causing access issues.
Member Fiore noted there is no real issue with access.
Deputy City Attorney Brennan noted that the secondary ARC review is being done as a courtesy, however, will not amend the current resolution.
M/S SHYU/HUTNIK to approve Accessory Building Use Permit 2025-19 subject to the attached Conditions of Approval in Resolution 2026-10, with a clerical review of the elevation plans to be completed by ARC for the roof pitch. The Motion was carried by the following roll call vote:
AYES: HEDGES, SHYU, CHUDZICKI, FIORE, AND HUTNIK
NOES: NONE
ABSENT: NONE
ABSTAIN: NONE
4.C. Accessory Building Use Permit 2025-20 (Arredondo): A request to allow a 988 square-foot large vehicle garage located on 3834 Hillside Avenue within the A1-20 zone (APN 133-182-014).
Associate Planner Diaz presented the staff report on file and a presentation was available.
Vice Chair Shyu questioned staff about the color called out in the plans, Associate Planner Diaz noted the color. Vice Chair Shyu noted the ribbing direction.
Applicant present. Vice Chair Shyu asked the applicant to confirm the color, the applicant noted it will be tan and a reddish roof. Vice Chair Shyu noted the ribbing direction, the applicant requested that the ribbing stay the same as the proposed.
Member Hutnik questioned the process of the kit building, Director Cataldi explained the process of plan check by staff.
Bill Naylor questioned if the building was built already, noted the drive access at 12'4".
M/S SHYU/CHUDZICKI to approve Accessory Building Use Permit 2025-20 subject to the attached Conditions of Approval in Resolution 2026-09. The Motion was carried by the following roll call vote:
Planning Commission Minutes - March 11, 2026
AYES: HEDGES, SHYU, CHUDZICKI, FIORE, AND HUTNIK
NOES: NONE
ABSENT: NONE
ABSTAIN: NONE
4.D. Accessory Building Use Permit 2025-07 (Oliver): A request to allow a 1,350 square-foot barn located on 5677 Bluff Street within the A-1-20 zone (APN 121-071-016).
Associate Planner Diaz presented the staff report on file and a presentation was available.
Vice Chair Shyu stated there is no color noted in the plans, Associate Planner Diaz explained the colors.
Applicant present, explained he would like to return the property to an animal keeping property, the structure will match the home in color.
Bill Naylor expressed his like for project, noted the elevations.
M/S SHYU/CHUDZICKI to approve Accessory Building Use Permit 2025-07 subject to the attached Conditions of Approval on Resolution 2026-12. The Motion was carried by the following roll call vote:
AYES: HEDGES, SHYU, CHUDZICKI, FIORE, AND HUTNIK
NOES: NONE
ABSENT: NONE
ABSTAIN: NONE
5. PUBLIC HEARING(S)
5.A. Conditional Use Permit 2025-07 (Ji): A proposal to allow consignment sales of refurbished and used firearms at an existing specialized retail gun shop located at 2027 River Road within the Commercial General (CG) Zone (APN 121-250- 033).
Associate Planner Diaz presented the staff report on file and a presentation was available.
Member Hutnik is in favor of this type of consignment store.
Vice Chair Shyu noted there are no operating hours noted, Associate Planner
Planning Commission Minutes - March 11, 2026
Diaz noted the hours will not change from the existing hours. Vice Chair Shyu asked Attorney Brennan if there are any laws with the storage of guns, Attorney Brennan noted she will do research and report back.
Applicant present, explained that he was approached by locals to sell their guns and noted this would a great benefit to the community. Chair Hedges asked if there is a large request for sales, applicant stated yes. Member Hutnik asked about the process of taking in the firearm and the sales, Applicant explained in detail the process for buying and selling guns.
M/S CHUDZICKI/HUTNIK to approve Conditional Use Permit (CUP) 2025-07 subject to the attached Conditions of Approval on Resolution 2026-11. The Motion was carried by the following roll call vote:
AYES: HEDGES, SHYU, CHUDZICKI, FIORE, AND HUTNIK
NOES: NONE
ABSENT: NONE
ABSTAIN: NONE
6. COMMISSION / STAFF COMMUNICATIONS
Vice Chair Shyu requested staff to create a presentation in regard to water meters on empty lots.
7. ADJOURNMENT
Chair Hedges adjourned the meeting at 7:52 p.m.