City of Oakland
Facility Assessment Checklist
BUILDING NAME 1/12/2022
1 of 23
# Oakland Facility Assessment Checklist Instructions
1 City of Oakland tab: Existing Documentation section items are requested to be provided to Consultant before site assessment. 2 City of Oakland tab: Facilities and User Questions section is to be completed by Public Works and building user groups. 3 Summary tab is meant to be a quick review of major building systems. See Systems tab for more detail. 4 Accessibility tab: initial accessibility review items provided as indicators for items requiring further investigation. Accessibility review is not CASP level review or inspection.
5 Systems tab: provide unique 3-digit number in first column labeled ### for identification. Numbers to be added at end of assessment process.
6 Systems tab: delete unused rows in spreadsheet and add new rows as needed for building components. 7 Systems tab: maintain 1 letter + 4-digit numbering system when removing and adding new rows. If items in group exceed ten items group can expand to the next tenth grouping. Adjust overall numbering scheme as needed. 8 See additional associated reviews and reports for structural and specific building types provided under separate cover. 9 Cost columns highlighted red are reserved for future use.
ATTACHMENT C
City of Oakland
Facility Assessment Checklist
BUILDING NAME 1/12/2022
2 of 23
# SYSTEM ITEM
YES/
NO DESCRIPTION COMMENT
1 Existing Documentation
2 Existing drawings Yes Uploaded to consultant FTP site 3 Major renovations
4 Geotechnical reports None available
5 Energy audits and/or utility records See folder
6 Hazardous material reports See folder
7 Other reports (assessments)
Facilities and User Questions
11 Are there any major building components frequently out of order or that require consistent maintenance? i.e. elevator
12 Are there any roof leaks?
13 Are there any major plumbing backup issues?
14 Any plumbing fixture leaks or issues?
15 Does the mechanical system need frequent adjustment? 16 Are any electrical breakers tripped consistently?
17 Are utility costs abnormally high for this building? 18 Are there complaints from building users about thermal comfort? 19 Any reported issues with or concerns about indoor air quality? 20 Are there any other notable issues with the building? City of Oakland
Facility Assessment Checklist
Fire Station 13, 1225 Derby Avenue 1/12/2022
### SYSTEM ITEM DESCRIPTION COMMENT
T Building Summary
T10 Overall
100 T1010 Year constructed 1960
101 T1011 Number of stories One
102 T1012 Building setting Urban
103 T1013 Approximate building height 17-feet
104 T1014 Estimated building area 5430 SF
105 T1015 Occupancy Group and Use
S2 App Bay, R3 Dorms and B
Kitchen and Day Room/offices
106 T1016 Superstructure system
Untopped metal deck spanning to
concrete beams supported on
pockets in concrete tilt-up walls
107 T1017 Roof type Rolled asphalt low-slope
108 T1018 Approximate number of parking spaces (if applicable) Room for approx. five vehicles, no
striping
109 T1019 Elevator or lift None, one story
110 T1020 Number of stairs Exterior only
111 T1021 Number of exits 3
112 T1021.01 Exit configuration
Dormitory 12, Locker room 13,
Toilet Rm 14 exit thru App Bay Non conforming
113 T1022 Exit signage none Non conforming
114 T1023 Accessory structures on site none
115 T1024 Openings between sleeping rooms and App Bay
Dorm 12 has door to App Bay; no
openings directly between motor
vehic related occ and room for
sleeping Non conforming
116 T0125 Occupancy Separations R2 (dwelling rooms)
None - doors not rated; 30 min
(sprinkler) or 60 min (no sprinkler)
required Non conforming
117 T0126
Occupancy Separations if required between R2-S2
(dwelling rooms/app bay
None- doors not rated ; 1 hr
required
Possibly Non
conforming
T50 Systems General
118 T5010 Total number of toilet fixtures 4
119 T5011 Total number of addtl. plumbing fixtures incl. showers (1) urinal, (1) shower stall, (3)
shower heads
120 T5012 Fire sprinkler system None Non conforming
121 T5013 Mechanical system
Original boiler and radiant floor/
and baseboard radiator system;
Numerous space heaters;
No AC cooling
122 T5013 Electrical system: ECAP readiness
200A 120/240 Single phase,
original Pemco panel that has no
available replacement parts
City of Oakland
Facility Assessment Checklist
FIRE STATION 13
1225 Derby Avenue 94601
1/12/2022
### SYSTEM ITEM LOCATION DESCRIPTION COMMENT COST
M Accessibility
M10 Exterior
200 M1010 Exterior path of travel to entry Front door to ROW Concrete path from ROW to front door in
compliance, less than 5% slope in direction of travel
and less than 2% cross-slope
201 M1011 Interior path of travel from entry to all required spaces Non-conforming - see specifics below 202 M1012 Accessible parking space, van, and/or drop-off zone No accessible parking on site or at street observed 203 M1013 Accessible parking signage No accessible parking on site or at street observed 204 M1014 Curb ramps No curb ramps
205 M1015 Entrance
No exterior level landing provided outside of front
entry door; flush transition at front door threshold;
existing exterior entry mat could be tripping hazard
M20 Interior General
206 M2010 Elevator and lifts; accessible controls None required - one story building 207 M2011 High-low drinking fountain w/CFA App Bay 15 Non accessible drinking fountain Non-conforming 208 M2012 Visual and audible alarms Further review needed 209 M2013 Tactile signage All None at building interior nor exterior 210 M2014 Door hardware
Doors 3,4,6,8,11A, 11B,12,13, 15,
15A, 17B, 17C, 18, No lever hardware (existing knobs)
211 M2014.01 Closet hardware Officer's Rm 2 and 3 No lever hardware on closets (knobs) 212 M2014.02
Door Hardware - 10" high smooth surface from floor on
bottom of door at push side Doors 3, 4, 9,14
Kick stop installed on bottom 10" of door on push
side
213 M2014.03 Door Hardware - pull mtg height Doors 2, 7, 9, 10, 17 Pull mounted >44" 214 M2014.04 Door Hardware - closer Door 9 - Day Rm 8 Missing closer 215 M2014.05 Door condition Door 17B Door damaged
216 M2015.01 Pull side latch clearance and pull mtg height Door 2 - Public Space 5 Door has <18" pull side latch clearance, located in
alcove, pull located >44" AFF Non-conforming
217 M2015.02 Push side latch clearance Door 3 - Off Rm 3 Door has <12" push side latch clearance, at closets Non-conforming 218 M2015.03 Door opening width and Pull side Latch clearance Door 5 - Kitchen Door is <36" and <18" pull side latch clearance at
counter in office Non-conforming
M2015.04 Pull side latch clearance Door 7 - Kitchen
Door has <18" pull side latch clearance, located in
alcove Non-conforming
219 M2015.05 Push side latch clearance Door 9 - Day Rm 8 Door has <12" push side latch clearance, at counter Non-conforming 220 M2015.06 Pull and push side latch clearance Dooor 11A - Toilet Rm 4 Door has <18" pull side latch clearance and <12"
push side latch clearance, located in alcove Non-conforming 221 M2015.07 Pull and push side latch clearance Dooor 11B - Toilet Rm 4 Door has <18" pull side latch clearance and <12"
push side latch clearance, located in alcove Non-conforming 222 M2015.08 Pull and push side latch clearance Door 18 - Lockers Door has <18" pull side latch clearance and <12"
push side latch clearance, located at lockers Non-conforming City of Oakland
Facility Assessment Checklist
FIRE STATION 13
1225 Derby Avenue 94601
1/12/2022
223 M2015.09
Pull side clearance and spacing between doors in
sequence Doors 19 and 20
Doors have <18" pull side latch clearance and doors
have less than 48" between them in sequence Non-conforming 224 M2016 Door Threshold Doors 9, 10 - Day Rm 8
Threshold >.5" non-beveled transition to vinyl
flooring Non-conforming
M30 Restrooms
225 M3010.01 Toilet Room 4 clearances Toilet Rm 4 (officers') Clearances not provided at shower, toilet or lav, nor
accessories (very small space). Lav faucet has
knobs, not levers. (see floor plan attached) Non-conforming 226 M3010.02 All Gender Toilet and Shower Room clearances All Gender Toilet and Shower Clearances not provided include: Toilet wall to wall clear dimension <60" min (59")
Toilet is not 17"-18" from wall (existing 19")
Grab Bar is not 54"min from corner (existing 52")
48x52 Shower configuration non-complying
Soap Disp at sink mtd >40" AFF Non-conforming
227 M3010.03 Toilet Room and Shower 14 clearances Toilet Rm and Shower 14 Clearances not provided include: Urinal and privacy screens are not accessible
(2) Toilet stalls are not accessible
Open (3) head shower config non-complying
Mirrors and accessories mtd >40" AFF
Non-conforming
M50 Special Accessible Conditions
228 M5010 Service counter with employee knee space
Public Space 5/Off and Signal
Room 6
Counter too high and no knee space on employee
side; >34". Non-conforming
229 M5010.01 Kitchen counter Kitchen 7 Counter too high ; >36" Non-conforming 230 M5010.02 Kitchen sink Kitchen 7 No knee space provided, ht >34 Non-conforming 231 M5010.03 Kitchen worksurface next to oven Kitchen 7 No work surface provided adjacent to bottom hinged
oven door (11B-804.6.5.2) Non-conforming
232 M5010.04 Kitchen worksurface with knee space Kitchen 7 None provided at fixed counter Non-conforming 233 M5011 Electrical Light Switches Rms 5, 6 Located too high ; >48" ; total count (18) Non-conforming 234 M5012 Electrical Outlets Kitchen 7 (3) Outlets over counter >48"; 235 M5013 Benches Locker 14 No accessible bench provided Non-conforming City of Oakland
Facility Assessment Checklist
Fire Station 13, 1225 Derby Avenue 1/12/2022
### SYSTEM ITEM LOCATION DESCRIPTION / YEAR QTY UNIT PRIORITY COST A Substructure
A10 Foundations
A1010 Standard Foundations
A1011 Wall Foundations
Continuous shallow footings 20" wide min 18"
thick
A1012 Column Foundations
A40 Slab On Grade
A4010 Standard Slabs-on-Grade
A4011
6" concrete slab on grade in truck bays, 4" conc
slab on grade in others
B Shell
B10 Superstructure
B1010 Floor Construction
B1012 Floor Decks, Slabs, & Toppings all
Concrete slab on grade; concrete floors have
numerous cracks
B1020 Roof Construction
B1021 Roof Structural Frame
B1022 Roof Decks, Slabs, & Sheathing
Untopped metal deck spanning to concrete beams
supported on pockets in concrete tilt-up walls
B1025
Roof Construction Supplementary Components
(fascia and flashing)
Break metal angled coping at roof edge; some
locations show peeling paint like NE corner of
bldg.; Soffits painted exposed steel deck
B20 Exterior Vertical Enclosures
B2010 Exterior Walls
B2011 Exterior Bearing Walls 8" thick concrete tilt-up walls B2012 Exterior Wall Veneer
Exposed painted conc. walls at window bays,
hand-place river rock in cement plaster, wood
detailing, in good condition generally uon
B2013 Exterior Wall Interior Skin
B2014 Fabricated Exterior Wall Assemblies North elev.
Wood fin damaged and missing stones in cement
plaster four locations
B2015 Parapets No parapets, angled metal edge at roof B2016 Equipment Screens Diesel tank SE site
CMU wall and chain-link fence onsite at diesel
tank
B2017 Equipment Screens Emerg. Generator NW site
Chain-link fence enclosure at emergency
generator
B2020 Exterior Windows
B2021 Exterior Windows
Single-pane awning style windows, mtl. Frame,
typical half the lites per bay are operable. At
sleeping rooms windows cannot be used for
ventilation because there is too much traffic noise
and pollution airborne particulates
City of Oakland
Facility Assessment Checklist
Fire Station 13, 1225 Derby Avenue 1/12/2022
B2021.01 Exterior Windows at Sleeping Rooms Emergency Egress Dorm 17B and 17C Window sill height >44" and clear area less than
minimum 20" W x 24" H
B2021.02 Exterior Windows at Sleeping Rooms Emergency Egress Rm 2 and 3 Emerg exit clear area less than minimum 20" W x
24" H
B2050 Exterior Doors
B2051 Exterior Doors Door 1 - Front door
Mtl. door/frame w/ two lites vertical; no exterior
level landing
B2052 Exterior Doors Door 8 - Side door
Mtl. door/frame w/ full upper lite & mtl. grill; no
exterior level landing
B2053 Exterior Doors Door 14 - Rear door
Mtl. door/frame w/full upper lite, small non-
compliant exterior landing; planter in area of strike-
side clearance
B2054 Exterior Doors Mech. Rm. Door Mtl. Door w/louver B2057 Exterior Overhead Doors Three OH doors
Pair of OH door at south w/one row of lites and
one at north side of Apparatus Bay w/one row of
lites; steel frame at north side door is rusted
B2070 Exterior Louvers & Vents
B2071 Exterior Louvers & Vents
West elevation south of OH
door Louver at damaged missing portion of blade
B2072 Exterior Louvers & Vents
South elevation above mech.
door Louver at no rodent screen
B2073 Exterior Louvers & Vents Exterior windows Some vents added at exterior window lites B2080 Exterior Wall Appurtenances
B2085 Exterior Walls & Railings Perimeter of site
Exterior concrete wall at approx. 4-feet high;
substantial cracking at wall observed at terminus
near SW corner of building; entire wall needs
paint
B30 Exterior Horizontal Enclosures
B3010 Roofing
B3015 Low-Slope Roofing
One high and two low low-slope roofs, rolled
asphalt roofing, standing water at all three roofs;
roofs generally have less than 1% slope
B3020 Roof Appurtenances
B3025 Roof and Overflow Drains At each roof Roof drains w/ screens and overflow drains B3060 Horizontal Openings
B3061 Roof Skylights
Unit skylights at each low roof; skylights at north
side of building were tarped and leaks reported
(Kitchen 7 and Toilet Rm 4 have tarps)
B3065 Vents & Hatches
Generally vent pipes in need of patching at roof
penetration; leak reported at former vent location
(no longer used) over Appartus Bay
B3080 Overhead Exterior Enclosures
B3081 Exterior Ceilings
City of Oakland
Facility Assessment Checklist
Fire Station 13, 1225 Derby Avenue 1/12/2022
B3082 Exterior Soffits At each roof edge
Break metal angled coping; some locations show
peeling paint like NE corner of bldg.
Soffits painted exposed steel deck
C Interiors
C10 Interior Construction
C1010 Interior Partitions
See Summary page for additional fire rating
comments
C1011 Interior Partitions Dorm 12
Room partitions are temporary partial height and
not fire-rated, acoustically or mechanically
separated. Lighting spans across top of wall. Non-conforming C1020 Interior Windows
C1030 Interior Doors See summary page for fire rating comments C1031.00 Interior Door Frame Toilet Rm 14 Rust on HM door frames C2031.01 Closet wood door refinishing
Kitchen 7, Officer's Rm 2,
Officer's Rm 3 Closet doors are scuffed, need refinishing C2031.02 Louver in All Gender Restroom Door All Gender Door 16A Door is not providing acoustic separation - Louver
in door allows toilet room sounds to be heard in
Locker Room
C1070 Suspended Ceiling Construction
C1071 Acoustical Suspended Ceilings All Gender
ACT ceiling in All Gender Shower/toilet room - not
recommended for a moist environment
C1090 Interior Specialties
C1096 Toilet, Bath, & Laundry Accessories See accessibility summary page C1096.01 Toilet Partition condition Toilet Rm 4 Rust on Toilet Partition C1099 Other Interior Specialties
C1099.01 Window Treatments all
Window mini blinds make it difficult to open the
windows since they cover the operating hardware.
C20 Interior Finishes
C2010 Wall Finishes
C2017 Wall Painting & Coating Day Rm 8 Scuff marks on wall, repaint C2020 Interior Fabrications
C2030 Flooring
C2032.00 Concrete Floor all
Stained concrete floor is cracked, no repair
required u.o.n.
C2032.01 Concrete Floor Public Space 5
uneven floor at 3" wide divet in the concrete needs
to be patched.
C2032.02 Concrete Floor Locker 13
Patched and cracked concrete floor, where radiant
flooring leaked. Stain patched areas to match.
C2035 Terrazzo Flooring Shower Rm 14 and 4
Terrazzo flooring at shower stall and shared
shower has deteriorated.See accessibility
checklist for non conforming conditions this area
C2040 Resilient Floor Base Rms 1, 5, 6 No floor base installed (6") City of Oakland
Facility Assessment Checklist
Fire Station 13, 1225 Derby Avenue 1/12/2022
C2041 Resilient Floor Base Locker 13 Rubber base is worn C2050 Ceiling Finishes
C2057 Ceiling Painting & Coating all
Exposed metal painted deck has rust spots
throughout the fire station. App Bay ceiling has
peeling paint.
D Services
D20 Plumbing
D2010 Domestic Water Distribution
D2012 Domestic Water Heater and/or boilers Exterior water heater room 20+ years old, no energy rating on heater 1 D2014 Domestic Water Piping Entire building
mostly original, exposed pipe in water heater room
is copper, original concealed could be galvanized.
D2016 Plumbing Fixtures Restrooms
Older 1.6GPF flush valve toilets. Lavatories are
1GPM
D2020 Sanitary Drainage
D2023 Sanitary Sewer Piping Main
Reported that main to street has been cleaned out
and repalced recently.
D2030 Building Support Plumbing Systems
D2032 Stormwater Drainage Piping Exposed rain water leaders from gutters.
D2050 General Service Compressed-Air
D2051 Compressed-Air Systems
D30
Heating, Ventilation, & Air Conditioning
(HVAC)
D3010 Facility Fuel Systems
D3011 Fuel Piping Existing piping is in good condition D3013 Fuel Pumps
D3015 Fuel Storage Tanks
D3020 Heating Systems
D3021 Heat Generation
Original boiler and radiant floor/ and baseboard
radiator system. Floor has been sawcut several
times for repairs to leaking pipes.
D3025 Decentralized Heating Equipment Electric space heaters throuhgout building.
D3030 Cooling Systems All
Building has no cooling system (except for a few
individual window air conditioners) and is
uncomfortably hot on warm days and nights.
Windows are not opened at night due to poor
outdoor air quality (adjacent street) and noise.
D3031 Air filtration Day Rm 8, Rms 2 and 3
Filtration machine installed with vent through
window patch/glass removed
D3033 Evaporative Air-Cooling
Move n Cools and portable AC located throughout
property.
D3060 Ventilation
D3061 Supply Air & Grilles
D3062 Return Air & Grilles
D3063 Exhaust Air & Grilles
Located in restrooms. Loud. Moves air well, but
motor is most likely oversized due to age.
City of Oakland
Facility Assessment Checklist
Fire Station 13, 1225 Derby Avenue 1/12/2022
D3063.01 Restroom Exhaust Toilet Rm 4 Loud exhaust fan
Restroom Exhaust Toilet Rm 14 Loud exhaust fan
D3064 Outside Air Operable windows
D40 Fire Protection
D4010 Fire Suppression
D4011 Fire Sprinklers None in building
D4030 Fire Suppression Specialties
D4031 Fire Extinguisher Cabinets
D4033 Fire Extinguishers
D4035 Commercial Kitchen Fire Suppression Systems
D50 Electrical
D5010 Facility Power Generation
D5011 Emergency Generator for Standby Power 15kVA 120/240 single phase generator D5014 UPS System Small unit located at station data rack.
D5017 Transfer Switches
D5020 Electrical Service & Distribution
D5021 Electrical Service
200A 120/240 Single phase, original Pemco panel
that has no available replacement parts.
D5022 Electrical Panels
App Bay adjacent to transfer
switch Panel E in good condition
D5023 Power Distribution Conduit exposed and underground D5027 Electrical Grounding Fair condition
D5031 Branch Wiring System Fair condition
D5035 Wiring Devices
Mounted below ADA heights in most locations.
Mix of Orange devices, red devices, and white
devices that are most likely not properly connected
to isolated ground systems and/or emergency
systems
D5040 Lighting
D5041 Lighting Controls Single wall switches mounted above ADA heights D5042 Branch Wiring for Lighting
D5045 Lighting Fixtures Exterior Building (working condition y/n) D5046 Lighting Fixtures Interior (working condition y/n) D5046.01 Light Fixture condition Office 6 Cracked fixture diffuser (approx 17" x 48") D5046.02 Light Fixture condition Day Rm 8 Cracked fixture diffuser (approx 17" x 48") Light Fixture condition All Gender Light over sink does not turn on Light Fixture condition Locker 17A Broken fixture housing D5047 Illuminated Exit Signage None provided Non-conforming D5048 Exit Emergency Lighting
D5049 Lighting Sensors
D60 Communications
D6010 Data Communications
D6011 Data Communications Network Equipment Fair condition and located in comms room D6012 Data Communications Hardware Fair condition and located in comms room City of Oakland
Facility Assessment Checklist
Fire Station 13, 1225 Derby Avenue 1/12/2022
D6020 Voice Communications
D6022.01 Telephone cabling Day Rm 8
Telephone cabling draped over doorway to phone
location, needs to be organized in conduit
D70 Electronic Safety & Security
D7010 Access Control & Intrusion Detection
D7011 Access Control Fair condition and located in app bay D7050 Detection & Alarm
D7051 Fire Detection & Alarm
D7053 Line Voltage Smoke Alarm
E Equipment & Furnishings
E10 Equipment
E1030 Equipment
E1033.01 Laundry Dry Rm 9 Dryer is lifted up on wood plinth, max reach >48:
E1033.02 Dryer vent Dry Rm 9
Vent installed through exterior air vent - the mesh
is cut and frame broken
E1034 Lockers Locker 13 Rusty lockers and no accessible locker E1035 Bench Locker 13 See accessibility checklist
E1038.01 Kitchen sink garbage disposal Kitchen No garbage disposal provided (preferred by FD) E1038.02 SS counter top Kitchen Good condition, scratched E0138.03 Wood counter top Kitchen
Wood counter installed over dishwasher only.
Wood is an absorbant material and not
recommended for a high use kitchen.
E1061 Residential Appliances Kitchen
Three residential style refrigerators provided,
located in apparatus bay, not kitchen
E20 Furnishings
E2010 Fixed Furnishings
E2012 Window Treatments See windows above
E2013 Casework Kitchen
Cabinets and their interiors need cleaning and
refinishing
E2019 Other Fixed Furnishings Exterior rear west side of bldg. Wood bench damaged, needs repair G20 Site Improvements
G2020 Parking Lots
G2021 Parking Lot Pavement North and west site
Recent AC paving w/ 2x wood edging at planted
areas, no striping
G2021 Parking Lot Pavement South site Recent AC concrete paving w/control joints G2030 Pedestrian Plazas & Walkways
G2031 Pedestrian Pavement From ROW to front door Recent conc. walkway , see accessibility tab G2060 Site Development
City of Oakland
Facility Assessment Checklist
Fire Station 13, 1225 Derby Avenue 1/12/2022
G2062 Fences & Gates
Chain-link fence around north and west perimeter
of site. Ivy-covered, approx. 5-feet high, not high
enough for privacy from adjacent residential
according to OFD
G2062 Site Furnishings
Chairs an bbq grill observed; two dumpsters &
two recycling bins north side of site
G2063 Exterior Signage None observed
G2063 Flagpoles South of bldg. Good condition, needs paint G2080 Landscaping
G2081 Planting Irrigation None observed
G2083 Plants
Large shrubs at building south elevation; trees at
west side of site, small plants adjacent to OH
doors at south side of building; planters along
north and west next to bldg. bare in need of plants
G40 Electrical Site Improvements
G4050 Site Lighting
Fire Station 13 1/12/2022
SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Public Space Lobby secure to Watch Office
Lobby is open to watch office
Photo: Watch Office to Lobby
Add Pass through window
at opening. Low
Space for Well Checks There is space for a chair for well checks. None Accessible Public Restroom
No dedicated public restroom, no restrooms
are accessible
Photo: Captain's Restroom adjacent to
Lobby
Create accessible restroom
to share with Station
Captain
Required if
renovated
Fire Station 13 1/12/2022
SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Apparatus
Bays Apparatus Bay Door Operation/condition Good Condition, newly replaced. N/A N/A Floor Drains in Bay Yes N/A N/A
Vehicle Tailpipe Extraction System
Non-Operational, Currently the Department
uses WARDS No Smoke for exhaust
control.
Photo: Tail-pipe System to be removed Remove obsolete system Low Hand washing/medical clean-up in bay No medical clean up area in station.
Station lacks a dedicated
space for general
handwashing and
decontamination after
returning from a call that is
convenient and on the
pathway to the living
quarters.
High -
Recommended
adding this space if
station is renovated
Shore power and Compressed Air
Shore power at engine bay and portable
compressed air systems are adequate. N/A N/A
Alerting System Status/Acoustics
New System in place
Photo: Alerting System N/A N/A
Fire Station 13 1/12/2022
SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Apparatus
Support
Dedicated Turn out Storage Room with two lockers for
assigned fire fighter Turnouts stored in bay
Add dryer and modify
existing laundry to hold
turnout lockers. Provide
continuous exhaust.
High - Recommend
adding this space.
Extractor and Dryer for apparatus and hose Station has an extractor Add dryer
modifying this space
so that it is
Medical Supply Storage Medical Supply storage in Watch Office Area adequate Workshop Workshop area in apparatus bay Area adequate
Hose Storage No backup hose storage at this location N/A
Fire Station 13 1/12/2022
SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Dedicated janitors room
Janitor room not large enough for supply
and equipment storage. Only one in
bathroom area.
Photo: Janitor equipment outside
Expand or add a second for
apparatus bays
Medium -
Recommended if
station is renovated
Dedicated Fitness Room
Fitness equipment is in the apparatus bay
Photo: Fitness Equipment in Apparatus Bay
Expand station for
dedicated fitness room Highest
Fire Station 13 1/12/2022
SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Office Space Dedicate Watch Office with at least two work stations Watch office is adequate
Photo: Watch Office Desk N/A
Dedicated Comm. Room with air-conditioning
Comm equipment is in a close off the
apparatus bay and is not conditioned.
Photo: Data closet off apparatus bay
Create dedicated Comm
Room.
Medium -
Recommended if
station is renovated
Public Meeting room Not required at this location N/A
Fire Station 13 1/12/2022
SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Kitchen Casework Condition
Recently refinished by the Firefighters
Photo: Kitchen N/A
Stainless Steel Counters Good Condition
Adequate shift storage and house storage Adequate Storage for dry goods Three refrigerators
All refrigerators are in the apparatus bay
Photo: Refrigerators in apparatus bay
Expand kitchen area to
accommodate all food
storage systems. High
Accessible work area and sink No accessible work area or sinks address in Kitchen
expansion
Range Ventilation Status Good Condition N/A
Fire Station 13 1/12/2022
SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Dining Room Sized to accommodate shift change meeting
Adequate size for shift change meeting with
staff standing.
Photo: Dining Area N/A
Dayroom Sized to accommodate on duty shift
Adequate size for on-duty firefighters
Photo: Dayroom N/A
Laundry
room Washer dryer
Washing facilities are included in extractor
and drying room. Mop sink provided for
house.
Photo: Extractor/Washer/Dry and TO drying
racks
Provide TO Dryer.
Separate the house hold
laundry/janitor facilities
from the apparatus
bay/gear cleaning and
drying facilities. Provided a
dedicate laundry facility for
the living quarters
High - Address with
Station Renovation
mop sink for house
adequate storage
Fire Station 13 1/12/2022
SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Sleeping Privatized Living Quarters
Private sleeping rooms have been provided
although they are partially open to the
hallway and do not isolate sound. They do
not meet current fire code separations.
Photo: Typical Sleeping Room open to
hallway
The size of the rooms are
generous.
Medium -
Reconfigure and
upgrade sleeping
rooms.
Emergency egress from sleeping room windows
Windows do not meet code for egress.
Photo: Sleeping Room with egress windows
Lowering windows will be
required as a part of a
renovation
Medium - Address
with Station
Renovation
Fire Station 13 1/12/2022
SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Dressing
Locker placement to accommodate dynamic staffing
models
Some lockers are located in areas to
accommodate dynamic staffing
Photo: Locker dressing Area
Eliimate this space and
create a gender neutral
personnel locker area that
responds to dynamic
staffing goals.
Medium - Address
with Station
Renovation
Gender neutral Restrooms with showers
Accommodations have been made for a
private restroom/dressing area.
Photo: Door to private dressing area
Renovate existing restroom
and locker area to provide
gender quality and privacy
Medium - Address
with Station
Renovation
Fire Station 13 1/12/2022
SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Restrooms/S
howers
Adequate number of restrooms for staffing (.75 per
staff Member) The number of restrooms is adequate.
Shower number is not
adequate.
Medium - Address
with Station
Renovation
Accessible Staff Shower and restroom
None of the restrooms are accessible
Photo: Firefighter restroom
Accessibility will be met
through a renovation.
Medium - Address
with Station
Renovation
Fire Station 13 1/12/2022
SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO General
Storage Storage for Special Duty operations (USAR, ETC.) Not required at this location. N/A Fire Alert Fire Station Dispatch Alert System Status New System at this location N/A Gas Shut off at Stove Yes
Gas shut off at BBQ No
Site Exterior paved surfaces: aprons, parking lot, driveway All surfaces have been recently paved N/A Operation of fuel pumps , fuel pump hoses, and
nozzles Fueling systems are operational N/A
Inspection of above ground tanks by Environmental
Services Unknown N/A
Adequate parking for shift change
Adequate parking for on duty staff, street
used for shift change N/A
Increased site storm water containment requirements
to meet Water Quality Act Requirements and allow
apparatus washing.
Not implemented in recent paving
renovation. N/A