City of Oakland
Facility Assessment Checklist
BUILDING NAME 1/12/2022
1 of 27
# Oakland Facility Assessment Checklist Instructions
1 City of Oakland tab: Existing Documentation section items are requested to be provided to Consultant before site assessment. 2 City of Oakland tab: Facilities and User Questions section is to be completed by Public Works and building user groups. 3 Summary tab is meant to be a quick review of major building systems. See Systems tab for more detail. 4 Accessibility tab: initial accessibility review items provided as indicators for items requiring further investigation. Accessibility review is not CASP level review or inspection.
5 Systems tab: provide unique 3-digit number in first column labeled ### for identification. Numbers to be added at end of assessment process.
6 Systems tab: delete unused rows in spreadsheet and add new rows as needed for building components. 7 Systems tab: maintain 1 letter + 4-digit numbering system when removing and adding new rows. If items in group exceed ten items group can expand to the next tenth grouping. Adjust overall numbering scheme as needed. 8 See additional associated reviews and reports for structural and specific building types provided under separate cover. 9 Cost columns highlighted red are reserved for future use.

ATTACHMENT D
City of Oakland
Facility Assessment Checklist
BUILDING NAME 1/12/2022
2 of 27
# SYSTEM ITEM
YES/

NO DESCRIPTION COMMENT
1 Existing Documentation
2 Existing drawings Yes Uploaded to consultant FTP site 3 Major renovations
4 Geotechnical reports None available
5 Energy audits and/or utility records See folder
6 Hazardous material reports See Appendix
7 Other reports (assessments)
Facilities and User Questions
11 Are there any major building components frequently out of order or that require consistent maintenance? i.e. elevator
12 Are there any roof leaks?
13 Are there any major plumbing backup issues?
14 Any plumbing fixture leaks or issues?
15 Does the mechanical system need frequent adjustment? 16 Are any electrical breakers tripped consistently?
17 Are utility costs abnormally high for this building? 18 Are there complaints from building users about thermal comfort? 19 Any reported issues with or concerns about indoor air quality? 20 Are there any other notable issues with the building? City of Oakland
Facility Assessment Checklist
FIRE STATION 25

SUMMARY
11/3/2021
3 of 27
### SYSTEM ITEM NUMBER DESCRIPTION COMMENT
T Building Summary
T10 Overall
100
T1010 Year constructed Circa 1960's but no known date;
Seismic Retrofit and Other
Improvements 1995
101 T1011 Number of stories One
102 T1012 Building setting Suburban
103 T1013 Approximate building height 16-feet (not including tower) 104 T1014 Estimated building area ~5500 SF
105
T1015 Occupancy Group and Use Fire Station: R3 (residential) and S2 (Storage)
106
T1016 Superstructure system Wood-framed with steel moment frame retrofit
107
T1017 Roof type Asphalt shingle steep-slope and
asphalt roll low-slope
108 T1018 Approximate number of parking spaces (if applicable) Large parking lot, no striping 109 T1019 Elevator or lift None, one story
110 T1020 Number of stairs Exterior only
111 T1021 Number of exits 4
T1021.01 Exit configuration
Dormitory 11,12,13, All Gender 7
and Toilet 9 exit thru App Bay Non conforming
112 T1022 Exit signage none
113
T1023 Accessory structures on site one shed, used for Fitness Facility
T1024 Openings between sleeping rooms and App Bay
Officers Room 1 has door to App
Bay with transom; no openings
should be provided directly
between motor vehic related occ
and room for sleeping Non conforming
T0125 Occupancy Separations R3 (dwelling rooms)
None - doors not rated; 1 hr
required Non conforming
T0126
Occupancy Separations R3-S2 (dwelling rooms/app
bay
None- doors not rated ; 2 hr
required Non conforming
City of Oakland
Facility Assessment Checklist
FIRE STATION 25

SUMMARY
11/3/2021
4 of 27
T50 Systems General
114 T5010 Total number of toilet fixtures 4
115
T5011 Total number of addtl. plumbing fixtures incl. showers (1) urinal, (4) shower stall, (5) lavs, (1) mop sink, (1) kitchen
sink
116 T5012 Fire sprinkler system None Non conforming
117
T5013 Mechanical system Central Furnace mounted high in app bay provides heating to both
sides of the FH. One year old.

Great condition
117
T5013 Electrical system: ECAP readiness 150A 120/240 single phase service. Service installed in
1997. Good condition
City of Oakland
Facility Assessment Checklist
FIRE STATION 25

ACCESSIBILITY
11/3/2021
5 of 27
### SYSTEM ITEM LOCATION DESCRIPTION COMMENT COST
M Accessibility
M10 Exterior
200 M1010 Exterior path of travel to entry No POT from ROW or parking lot Non-conforming 201 M1011 Interior path of travel from entry to all required spaces See issues listed under section M20 Interior General Non-conforming 202 M1012 Accessible parking space, van, and/or drop-off zone No parking lot striping or accessible parking spaces Non-conforming 203 M1013 Accessible parking signage No parking signage Non-conforming 204 M1014 Curb ramps na
205 M1015
Entrance
Front door entrance
No clear and level landing or signage at front door;
threshold is not flush and is non-compliant Non-conforming M20 Interior General
210 M2010 Elevator and lifts; accessible controls None required; one story building 211 M2011 High-low drinking fountain w/CFA None provided 212 M2012 Visual and audible alarms Check with MEP
213 M2013 Tactile signage None at building interior nor exterior 214
M2014 Door hardware Doors 1,3,4,7,8, 13,
14, 15, 16, 17, 18 No lever hardware (existing knobs) Non-conforming M2014.01 Closet hardware Doors 2A, 2B No lever hardware (existing knobs) Non-conforming M2014.02
Door Hardware - 10" high smooth surface from floor on
bottom of door at push side
Door 7, 14
Door has kick stop on push side, which obstructs smooth surface Non-conforming
M2015.01 Pull side latch clearance Door 12 Door has <18" pull side latch clearance, located in alcove Non-conforming M2015.02 Pull and push side latch clearance Door 13
Door has <18" pull side latch clearance and <12" push side latch clearance, located in alcove Non-conforming
M2015.03 Door width Door 15,16,17 Dorm doors are 32"; 36" required. Non-conforming 216 M2016 Flush transitions and door thresholds Door 19 Threshold >.5" with .25" max vertical rise Non-conforming 217 M2017 Ramps (measure w/ level) No ramps in building M2019 Accessories mounting heights
Kitchen 3
Soap and paper towel dispenser at kitchen mounted higher than 40" to operable parts Non-conforming
M30 Restrooms
220 M3010.01 Toilet Room 1A (officers') clearances
Toilet Rm 1A
(officers')
Required clearances not provided at door 3, toilet or lav, nor accessories (very small space). (see floor plan
attached) Non-conforming
221 M3010.02 Toilet Room and Shower 9 clearances Toilet Rm 9 Clearances not provided include:

Urinal and its stall; non complying
Toilet stalls too small; non complying
(3) shower stalls too small; non-complying
Paper towel dispenser mtd >40" AFF (40" max req) Non-conforming City of Oakland
Facility Assessment Checklist
FIRE STATION 25

ACCESSIBILITY
11/3/2021
6 of 27
M3010.03 All Gender Toilet and Shower 7 clearances All Gender 7 Clearances not provided include:

28.5" clear under sink at skirt ; 29" required
Sink knee clearance <8" required to bowl
Toilet stall is 48" wide (60" required)
Toilet stall <48" clear in front of toilet (48" required) Stall door not self closing (self closing required)
Shower stall 42x54 w/bench opp controls non complying
Soap and paper towel mtd >40" AFF (40" max req) Non-conforming M50 Special Accessible Conditions
230 M5010 Service counter none
Kitchen counter
Kitchen 3 Quartz counter in good shape, but counter too high ; >36" Non-conforming Kitchen worksurface next to oven Kitchen 7
No work surface provided adjacent to bottom hinged oven door (11B-804.6.5.2) Non-conforming
Kitchen worksurface with knee space Kitchen 7 None provided at fixed counter Non-conforming Electrical Switches Rms 2 Located too high ; >48" ; approximately (10) Non-conforming Electrical Outlets Mounting Heights all
Outlets - over counter too high >48"; Most low outlets in building located too close to floor <15" AFF Approximately ( 15) Non-conforming
233 M5013 Benches NA/no locker room
234 M5014 Washer clear space Laundry 6 no clear floor space provided Non-conforming City of Oakland
Facility Assessment Checklist
FIRE STATION 25

SYSTEMS
11/3/2021
7 of 27
### SYSTEM ITEM LOCATION DESCRIPTION MAINTENANCE QTY UNIT PRIORITY COST A Substructure
A10 Foundations
A1010 Standard Foundations
A1011 Wall Foundations
Continuous shallow footings (sizes
unknown) under bearing walls, 4 foot
square pad footings under moment frame
A40 Slab On Grade
A4010 Standard Slabs-on-Grade
A4011 Slab On Grade 6" concrete slab on grade
B Shell
B10 Superstructure
B1010 Floor Construction
B1012 Floor Decks, Slabs, & Toppings 6" concrete slab on grade B1020 Roof Construction
B1021 Roof Structural Frame Steel moment frame at App Bay as part of retrofit
B1022 Roof Decks, Slabs, & Sheathing 1x8 T&G spanning to purlins supported on built up wood trusses
B1025 Roof Construction Supplementary Components
(fascia and flashing)
Mtl. Flashing needed at roof valley
intersections, see B3010 section for
addtl. Info.

B1080 Stairs and Ladders
B1088 Ladders Hose-drying
tower Ladder appears to be compliant
B20 Exterior Vertical Enclosures
B2010 Exterior Walls
B2011 Exterior Wall Structure Wood stud walls, cement plaster and some walls with added structural
sheathing done as part of retrofit; exterior
cement plaster does not have required
code separation from grade
B2012 Exterior Wall Veneer Cement plaster, no separation from grade, needs patch and paint
Crack repaired near back stair from
restroom leak, still soft; repair of sink not
confirmed
B2016 Equipment Screens
CMU wall screen at diesel tank, needs
paint; chain link fence cage at emergency
generator, some organic growth on slats
B2020 Exterior Windows
B2021 Exterior Windows Windows new in 2021
City of Oakland
Facility Assessment Checklist
FIRE STATION 25

SYSTEMS
11/3/2021
8 of 27

B2021.01 Exterior Windows at Sleeping Rooms Emergency Exit Officers' Rm
1 and Dorms
11,12, 13
Window sill height 45" and 45 1/2" which
is >44"; non conforming per exiting
requirements
B2050 Exterior Doors
B2051 Exterior Doors Front door Mtl. Door/frame w/ lever hardware B2052 Exterior Doors Side door at
parking lot
Wd. Door/frame w/ lever hardware, needs
paint, no landing
B2053 Exterior Doors
Rear door
Wd. panel door repaired w/ sealant, knob
hardware, needs replacement
B2054 Exterior Doors Side door at
sidewalk
Wd. Door/frame w/ knob, screen door
broken handle
B2057 Exterior Overhead Doors
Two roll-up overhead doors into app bay
B2070 Exterior Louvers & Vents
B2071 Exterior Louvers & Vents Soffit vents approx. 15-feet on center B30 Exterior Horizontal Enclosures
B3010 Roofing
B3011 Steep Slope Roofing
Main roof
Main roof is 5:12 asphalt shingle good
condition, some organic growth north
side; Mtl. Flashing needed at valley
intersections
B3015 Low-Slope Roofing Rear of bldg.
south at each
corner
Low slope roof is rolled asphalt, cracked
and needs replacement
B3018 Insulation at Roof App Bay and
above clg. on
north and
south wings No insulation at roof envelope observed
B3020 Roof Appurtenances
B3027 Gutters & Downspouts Alum. gutters, downspouts in good condition, need to be cleaned out;
downspout termination is blocked in some
cases
B3060 Horizontal Openings
B3065 Vents & Hatches Interior
ceiling one in
closet one in
hall
Interior ceiling hatches need paint
B3080 Overhead Exterior Enclosures
B3082 Exterior Soffits All Wood w/ peeling paint
C Interiors
C10 Interior Construction
City of Oakland
Facility Assessment Checklist
FIRE STATION 25

SYSTEMS
11/3/2021
9 of 27
C1020 Interior Windows
C1021 Interior Windows
Dining 2
Non rated window between dining room
and App Bay 8 - non conforming
C1030 Interior Doors See Summary page for fire rating and Accessibility page for comments
C1031 Interior Doors Door 14 Wood door is damaged at latch C1040 Interior Grilles & Gates
C1070 Suspended Ceiling Construction
C1072 Plaster & Gypsum Board Ceilings Hall 10 Plaster is bubbled and cracked - repair C1090 Interior Specialties
C1096 Toilet, Bath, & Laundry Accessories See Accessibility page C1096.01 Toilet Partition condition Toilet Rm 9 Very rusty toilet partitions C1097 Storage Specialties
Kitchen 3
Existing kitchen storage under counter is
open shelving, hard to keep
clean/sanitary without doors
C20 Interior Finishes
C2010 Wall Finishes
C2011 Tile Wall Finish
Toilet Rm 9
Damaged wall tile, base and wall board
behind custodial sink
C2015 Stone Facing Paint is damaged, repainting required C2017 Wall Painting & Coating
All
Interiors have old damaged paint, should
be repainted (1)
C2020 Interior Fabrications
C2030 Flooring
C2031 Tile Flooring Toilet Rm 9 Tile is in good shape C2032 Masonry Flooring
Laundry 6
Painted concrete floor paint is worn,
needs repainting
C2034 Resilient Flooring Kitchen 3 Resilient tile flooring damaged - replace Resilient Flooring Hall 10 Resilient tile flooring damaged - replace C2040 Resilient Floor Base Office 4 No floor base installed C2050 Ceiling Finishes
C2051 Plaster & Gypsum Board Finish Hall 10 Plaster is bubbled and cracked - repair C2057 Ceiling Painting & Coating
all
Interiors have old damaged paint, should
be repainted (1)
C2059 Attic Space Condition (insulated envelope) all See roofing item above D Services
D20 Plumbing
D2010 Domestic Water Distribution
D2012 Domestic Water Heater and/or boilers Manufactured in 2019. In good condition.

D2014 Domestic Water Piping Hot water piping is not insulated for large sections.

City of Oakland
Facility Assessment Checklist
FIRE STATION 25

SYSTEMS
11/3/2021
10 of 27
D2016 Plumbing Fixtures
Kitchen 3
and other
One compartment sink in Kitchen 3;
Older 1.6GPF water closets. Lavatories
have controls that requiring grasping and
twisting, not ADA compliant.

D2020 Sanitary Drainage
D2023 Sanitary Sewer Piping
No reports from staff that there are issues
D2030 Building Support Plumbing Systems
D2032 Stormwater Drainage Piping Rain water leaders from roof to runoff D2033 Stormwater Drains Steel trench drain at grade in front of OH door in good condition
D30 Heating, Ventilation, & Air Conditioning
(HVAC)
D3010 Facility Fuel Systems
D3011 Fuel Piping
D3013 Fuel Pumps
D3015 Fuel Storage Tanks Diesel tank outer conc. shell has cracks, needs patch and paint
D3020 Heating Systems
D3021 Heat Generation Central Furnace mounted high in app bay provides heating to both sides of the FH.

One year old. Great condition
D3023 Thermal Heat Storage
D3025 Decentralized Heating Equipment A few electric heaters were found throughout the property. Most were not
plugged in.

D3027 Heating System Supplementary Components Unit heater is located in app bay D3029 Electric Heating System
D3030 Cooling Systems
D3031 Central Cooling Outdoor 5-Ton Condensing unit
connected to central furnace. One year
old
D3037 Decentralized Cooling A few move n cools located throughout building. Does not appear that they are in
use. Workout studio has a move n cool
that is in use
D3060 Ventilation
D3061 Supply Air & Grilles Located throughout FH. Typical 12"x6" residential type grilles
D3062 Return Air & Grilles Located throughout FH. Typical 12"x6" residential type grilles
D3063 Exhaust Air & Grilles Located in restrooms and kitchen D3064 Outside Air Operable windows
D40 Fire Protection
City of Oakland
Facility Assessment Checklist
FIRE STATION 25

SYSTEMS
11/3/2021
11 of 27
D4010 Fire Suppression
D4011 Fire Sprinklers No fire sprinkler system
D4030 Fire Suppression Specialties
D4031 Fire Extinguisher Cabinets
D4033 Fire Extinguishers
D4035 Commercial Kitchen Fire Suppression Systems
D50 Electrical
D5010 Facility Power Generation
D5011 Emergency Generator for Standby Power
Kohler emergency generator with transfer
swith located inside fence enclosure
D5012 Battery Equipment
D5014 UPS System
D5017 Transfer Switches
D5020 Electrical Service & Distribution
D5021 Electrical Service 150A 120/240 single phase service.

Service installed in 1997. Good condition
D5022 Electrical Panels Two zinsco panels located in App Bay.

Should be replaced and relocated to
somwehere outside the app bay
D5023 Power Distribution Exposed conduit throughout app bay D5031 Branch Wiring System Appears to be in good condition D5040 Lighting
D5041 Lighting Controls
Dorms
11,12,13 and
other
Light switches in Dorms 11, 12, 13 are
controlled outside of the rooms in oddly
configured circuiting; wall switches are
used, no occupancy sensors
D5042 Branch Wiring for Lighting Within conduit and in fair condition G4051 Area Lighting Rear parking
lot LED post-mounted exterior led floodlight
D5046 Lighting Fixtures Interior (working condition y/n) App Bay 8
(3) light fixtures are missing protective
cage; Overall mixture of T8 4', 8',
compact fluorescent, surface mounted
fixtures throughout. Due for LED upgrade
D5047 Illuminated Exit Signage All None provided
D5048 Exit Emergency Lighting
D60 Communications
D6010 Data Communications
D6011 Data Communications Network Equipment In Fair condition. Located in Comm room that is connected to dining room.

D6020 Voice Communications
D6021 Voice Communications Switch & Routing Equip. Located in closet through captain's quarters.

City of Oakland
Facility Assessment Checklist
FIRE STATION 25

SYSTEMS
11/3/2021
12 of 27
D6022 Voice Communications Terminal Equipment Located in closet through captain's quarters.

D70 Electronic Safety & Security
D7010 Access Control & Intrusion Detection
D7011 Access Control Card reader at pedestrian door
D7050 Detection & Alarm
D7051 Fire Detection & Alarm Local 120V devices in dorm rooms D7053 Line Voltage Smoke Alarm
D7053 Outdoor Warning Siren Pole-
mounted rear
parking lot Operation not verified
E Equipment & Furnishings
E10 Equipment
E1030 Equipment
E1033 Laundry & Dry Cleaning Equipment Washer and dryer - residential grade E1037 Office Equipment Not reviewed
E1038 Foodservice Equipment Not reviewed
E1061 Residential Appliances Dishwasher and refridgerators are residential grade
E1067 Residential Ceiling Fans Yes, provided in dorms E20 Furnishings
E2010 Fixed Furnishings
E2012 Window Treatments Existing louvered shades
E2013 Casework At kitchen only
G Sitework
G20 Site Improvements
G2020 Parking Lots
G2021 Parking Lot Pavement Lot at west
and south of
building
Asphalt with many patches and cracks,
needs replacement, no striping
G2030 Pedestrian Plazas & Walkways
G2033 Exterior Steps & Ramps Exterior into
rear SE
corner of App
Bay
Non-compliant handrails and guard, no
landing at exterior door; no striping at
treads; door does not appear to be in use
G2034 Exterior Steps & Ramps Exterior into
rear SW
corner of App
Bay
Non-compliant handrails and guard, no
striping at treads, no landing at exterior
door
G2035 Exterior Steps & Ramps East side of
building from
Dining Room
Non-compliant handrails and guard, no
striping at treads, no landing at exterior
door
G2060 Site Development
City of Oakland
Facility Assessment Checklist
FIRE STATION 25

SYSTEMS
11/3/2021
13 of 27
G2062 Site Furnishings
South of
main building
at rear lot
Shipping container onsite for storage;
small outbuilding used for fitness room;
Mop and tool hangers on outbuilding
north side
G2063 Exterior Signage No accessible signage; wayfinding signage including FS 25 and front door;
Safe Surrender
G2063 Flagpoles Exterior north
side of
property
Good condition
G2066 Retaining Walls
Around base
of diesel tank
Small stone wall, gravel spilling onto
sidewalk
G2080 Landscaping
FIRE STATION NO. 25

STATION EVALUATION
1/12/2022

SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Public Space Lobby
This station does not have a lobby space.

The public is greeted at a apparatus bay
door. Add public lobby. High Door to Apparatus bay
Space for Well Checks
There is not an appropriate space for well
checks.

Add public lobby with
space for well checks
Medium -
Recommended if
station is renovated
Accessible Public Restroom No dedicated public restroom There is an accessible
restroom off of the
apparatus bay that can
meet the requirement for
accessibility. However,
there is no accessible route
to the station. If that station
is renovated, we
recommend creating a
dedicated accessible
restroom as a part of a new
lobby.

Required if
renovated Restroom entrance from Captain's Office

Page 14 of 27 ends

FIRE STATION NO. 25

STATION EVALUATION
1/12/2022

SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Apparatus
Bays Apparatus Bay Door Operation/condition.

Fair Condition, newly replaced. However,
door opening is too narrow for newer
apparatus.

Remove center support and
install door that extends
across the full opening.

Required if
renovated View of doors from the apparatus bay
Floor Drains in Bay No Continue to use drain pans. N/A
Vehicle Tailpipe Extraction System
Non-Operational, Currently the Department
uses WARDS No Smoke for exhaust control. Remove obsolete system Low Tail-pipe System to be removed Hand washing/medical clean-up in bay There is not a dedicate clean up sink.

Add medical clean up sink
if renovated
Recommended if
station is renovated

Page 15 of 27 ends

FIRE STATION NO. 25

STATION EVALUATION
1/12/2022

SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Shore power and Compressed Air
Shore power at engine bay and portable
compressed air systems are adequate. N/A N/A
Alerting System Status/Acoustics
New head end equipment has been
provided.

Replace obsolete speaking
system with upgraded
speakers and notification
devises.

Medium -
Recommended if
station is renovated Alerting System
Apparatus
Support
Dedicated Turn out Storage Room with two lockers for
assigned fire fighter Turnouts stored in bay
Add on to the fire station to
provide this necessary
dedicate storage. High Existing turn out storage

Page 16 of 27 ends

FIRE STATION NO. 25

STATION EVALUATION
1/12/2022

SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Extractor and Dryer for apparatus and hose Station only has residential units Expand station to add a
room for dedicated turnout
storage and washer
extractor/equipment dryer. High Existing laundry room
Medical Supply Storage
Medical supply storage location was not
identified N/A
Workshop Workshop area in apparatus bay
Shop work area used for
multiple functions.

Modification of the obsolete
hose tower is
recommended for a more
efficient layout.

Page 17 of 27 ends

FIRE STATION NO. 25

STATION EVALUATION
1/12/2022

SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Hose Storage and Drying Tower No backup hose storage at this location Re-purpose tower area for
an expansion of the shop
and added storage.

Medium -
Recommended if
station is renovated Tower at floor level
Dedicated janitors room
There is a janitors space in the fire fighter
restroom.

This space is adequate for
the use, however, if the
station was renovated this
would be moved to the
laundry room and a second
janitors space would be
added for just the
apparatus bay and support
areas.

Medium -
Recommended if
station is renovated Janitor Room in restroom

Page 18 of 27 ends

FIRE STATION NO. 25

STATION EVALUATION
1/12/2022

SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Dedicated Fitness Room
A shed at the rear of the property has been
converted to a fitness room.

The shed lacks sufficient
space for required
equipment and the
construction is sub-
standard. Recommend that
a fitness space is added to
the fire station if renovated.

Medium -
Recommended if
station is renovated Fitness Equipment in Shed
Office Space Dedicate Watch Office with at least two work stations A former bunk room has been converted to
an office for use by the station crew. It also
provides space for a refrigerator and medical
supply storage.

A watch office is typically off
of a secure lobby. We
recommend adding a lobby
and converting the
Captains office/bedroom to
a functional office area for
all fire fighters to use.

Medium -
Recommended if
station is renovated Office space with other storage

Page 19 of 27 ends

FIRE STATION NO. 25

STATION EVALUATION
1/12/2022

SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Dedicated Comm. Room with air-conditioning
Comm equipment is in a closet off the
Captains room and is not conditioned.

Create dedicated Comm
Room. with space for rack
mounting of equipment and
a dedicated conditioning
system.

Medium -
Recommended if
station is renovated Data closet off Captains Office/bedroom Public Meeting room Not required at this location N/A
Kitchen Casework Condition
Currently being refurbished by the Fire
Fighters assigned to this station. N/A Kitchen
Stainless Steel Counters
Counters are not stainless but are new and
appropriate for the use. N/A
Adequate shift storage and house storage Adequate Storage for dry goods N/A

Page 20 of 27 ends

FIRE STATION NO. 25

STATION EVALUATION
1/12/2022

SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Three refrigerators
The kitchen has a single refrigerator and a
second is located in the former bunk room.

Expand kitchen area to
accommodate all food
storage systems.

Medium -
Recommended if
station is renovated Refrigerator in kitchen
Accessible work area and sink No accessible work area or sinks Address in Kitchen
expansion
Required if
renovated
Range Ventilation Status Good Condition N/A
Dining Room Sized to accommodate shift change meeting
The dining room is also the day room and
provides space for a computer work station.

It is adequately size for the intended use as
a dining room only.

Recommend relocating the
dayroom function out of the
dining room through a
station expansion.

Medium -
Recommended if
station is renovated Dining Area

Page 21 of 27 ends

FIRE STATION NO. 25

STATION EVALUATION
1/12/2022

SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Dayroom Sized to accommodate on duty shift
There is not a dedicated dayroom in this
station.

Recommend adding a day
room.

Medium -
Recommended if
station is renovated Recliners in Dining Room
Laundry room Washer dryer
A mechanical room was converted to a
laundry room.

Renovate space to add
casework for storage.

Enclose water heater.

Medium - Address
with Station
Renovation Extractor/Washer/Dry and TO drying racks
mop sink for house Located in bathroom
Add mop sink to laundry
room.
adequate storage No
Replace lockers with
casework and folding
counters/supply storage
shelving.

Page 22 of 27 ends

FIRE STATION NO. 25

STATION EVALUATION
1/12/2022

SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Sleeping Privatized Living Quarters
The station has been renovated to provide
private sleeping quarters.

The size of the rooms are
generous. N/A Typical Sleeping Room open to hallway
Emergency egress from sleeping room windows
The windows in the sleeping rooms appear
to provide egress N/A N/A Sleeping Room with egress windows

Page 23 of 27 ends

FIRE STATION NO. 25

STATION EVALUATION
1/12/2022

SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Dressing
Locker placement to accommodate dynamic staffing
models
The living quarters wing of the facility has
been modified to provide private sleeping
rooms and a gender neutral personnel locker
area.

N/A Personnel Lockers
Gender neutral Restrooms with showers
Accommodations have been made for a
gender neutral shower and dressing area. It
was design as an accessible space when
constructed.

Relocate if the station is
renovated to be grouped
with the other all gender
restrooms. Reduce in size
and relocate lockers.

Medium - Address
with Station
Renovation Private Restroom

Page 24 of 27 ends

FIRE STATION NO. 25

STATION EVALUATION
1/12/2022

SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Restrooms/Sh
owers
Adequate number of restrooms for staffing (.75 per staff Member)
The number of fixtures exceeds the number
normally associated with this level of
staffing. There is a group bathroom.

Renovate restroom space
to provide private all gender
facilities.

Medium - Address
with Station
Renovation Partial restroom view. Shower behind view.

Accessible Staff Shower and restroom
An accessible, all gender restroom have
been added to the station. N/A N/A Firefighter restroom

Page 25 of 27 ends

FIRE STATION NO. 25

STATION EVALUATION
1/12/2022

SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO General
Storage Storage for Special Duty operations (USAR, ETC.) Not required at this location. N/A Site Security Site perimeter secured. The site is not secured. Fence site.

Medium - Address
with Station
Renovation View of rear yard property line.

Fire Alert Fire Station Dispatch Alert System Status New System at this location N/A Gas Shut off at Stove Yes
Gas shut off at BBQ No
Site Exterior paved surfaces: aprons, parking lot, driveway All surfaces are worn and are recommended
to be replaced
Replace paving if facility is
renovated.

Medium - Address
with Station
Renovation Front Apron

Page 26 of 27 ends

FIRE STATION NO. 25

STATION EVALUATION
1/12/2022

SPACE ITEM OPERATIONAL REVIEW MODIFICATION PRIORITY PHOTO Operation of fuel pumps , fuel pump hoses, and
nozzles Fueling systems are operational
Would recommend
relocating these systems to
the rear of the station site. Existing fueling system with generator behind.

Inspection of above ground tanks by Environmental
Services Unknown N/A
Adequate parking for shift change
Adequate parking for on duty staff, street
used for shift change N/A
Increased site storm water containment requirements
to meet Water Quality Act Requirements and allow
apparatus washing.

Would be included in a paving replacement
project.

Add to paving scope of
work if facility is
renovated.

Page 27 of 27 ends