TITLE 4. - PUBLIC SAFETY
CHAPTER 3. FIRE PROTECTION
Pacifica, California, Code of Ordinances

Page 1 of 14 ends

CHAPTER 3. FIRE PROTECTION
Article 1. Fire Code1
Sec. 4-3.101. Adoption of the California Fire Code.

For the purpose of regulating the erection, construction, enlargement, alteration, repair, removal, demolition, conversion, occupancy, equipment, use, height, area, and maintenance of all buildings and structures and grading in the City of Pacifica, Chapters 1 through 67, including Appendix B ("Fire-Flow Requirements for Buildings"), Appendix C ("Fire Hydrant Locations and Distribution"), Appendix D ("Fire Apparatus Access Roads"), and Appendix F ("Hazard Ranking"), Appendix L ("Requirements for Fire Fighter Air Replenishment Systems") of that certain code designated as the California Fire Code, 2025 Edition [CCR Title 24, Part 9], published by the International Code Council, amended by the State of California and as adopted and/or amended by the Office of the State Fire Marshal, which is on file in the Office of the City Clerk for public record and inspection, is hereby adopted by reference and made a part of this chapter as though set forth in this chapter in full, subject, however, to the amendments, additions, and deletions set forth in this chapter, and said code shall be known as Fire Code for the City of Pacifica. All other previously adopted ordinances not modified by this article and amendments shall remain.

Sec. 4-3.102. Establishment and duties of the Bureau of Fire Prevention.

The California Fire Code shall be enforced by the Fire Prevention Services Bureau in the Fire Department of the City, which Bureau is hereby established and which shall be operated under the supervision of the Fire Chief.

The Fire Marshal in charge of the Fire Prevention Services Bureau shall be appointed in accordance with the provisions of Article 4 of Chapter 5 of Title 2 of this Code and Council Resolution No. 82-69.

The Fire Chief may detail such members of the Fire Department as shall from time to time be necessary.

Sec. 4-3.103. Amendments: Section 105.1.1 ("Permits required").

Section 105.1.1 is amended by adding the following paragraph at the end of the section:

The city council of the City of Pacifica may if it so desires, establish by resolution permit fees in connection with any permit required or authorized to be issued by the fire chief or any other authorized representative of the fire department.

Sec. 4-3.104. Amendments: Section 105.5 ("Required operational permits").

Section 105.5 is amended by adding the following at the end of the section:
105.5.60 Institutions and day care. An operational permit is required to operate any and all occupancies that are set forth under Group I Occupancies, and Group E Occupancy of Title 24 of the California Code of Regulations, each accommodating more than six people.

Page 2 of 14 ends

105.5.61 Residential care facility. An operational permit is required to operate a residential care/assisted living facility as set forth under Group R, Division 4 Occupancies.

Sec. 4-3.105. Amendments: Section 202 ("General Definitions").

Section 202 is added to read as follows:
202 Definitions.
(a) Wherever the word "jurisdiction" is used in said California Fire Code, it shall be held to mean the City of Pacifica.
(b) Wherever the term "Corporation Counsel" is used in said California Fire Code, it shall be held to mean the City Attorney.
(c) Wherever the words "Fire Code Official" are used in said California Fire Code, they shall be held to mean the Fire Marshal.

Sec. 4-3.106. Amendments: Section 505.1 (“Address Identification”).

Section 505.1 of the California Fire Code is amended by adding the following at the end of the section:

Said numbers shall be internally or externally illuminated in all new construction, or when alterations or repairs of existing construction occur.

The size and location of address numbers for multi-family dwellings and all other occupancies shall be as designated by the Fire Marshal.

Sec. 4-3.107.-Amendments: Section 507 (“Fire Protection Water Supplies”).

Section 507.5.7 is added to the California Fire Code read as follows:
507.5.7 Hydrants. All new fire hydrants shall be UL listed, or equivalent, wet barrel type having a minimum of two 2 ½” and one 4 ½” outlets, all equipped with national standard threads (Clow 860, or approved equivalent). The minimum fire service main size permitted is six inch (6”).

Sec. 4-3.108.-Amendments: Section 509 (“Fire Protection and Utility Equipment Identification and Access”).

Section 509.1.2 is added to the California Fire Code read as follows:
509.1.2 Utility Identification in Multi-Family Tenant Buildings. Utility markings of all gas and electric utility services in multi-family tenant buildings shall be visibly and legibly marked with the unit identification.

Sec. 4-3.109. Amendments: Section 903.2 ("Automatic sprinkler systems. Where required").

Section 903.2 of the California Fire Code is hereby amended to read as follows:
903.2 Required Installations.

A. Newly Constructed Buildings and Structures. An automatic fire sprinkler system shall be installed in all new occupancies and locations.

Page 3 of 14 ends

Exception. Detached U occupancies not exceeding 1,000 square feet in size, when accessory to an R-3 dwelling.

B. Existing Buildings and Structures. An automatic fire sprinkler system shall be installed throughout all buildings when an addition is added to the building.

Exceptions:

1. When an addition to a R-3 occupancy is less than 1,000 square feet in size and when an addition to all other occupancies is less than 500 square feet in size, no sprinklers are required in either the addition or the existing building.

2. The construction of an assessor dwelling unit shall not trigger a requirement for fire sprinklers to be installed in an existing dwelling, including any addition solely for purposes of accessory dwelling unit construction.

3. When specifically exempted by the Fire Code Official.

C. 903.2.21 Car Stackers. Parking garage areas containing car stackers shall be protected by an automatic wet-pipe sprinkler system designed to the current edition of NFPA 13. In addition, non-extended coverage standard sidewall sprinklers listed for Ordinary Hazard shall be provided under each parking level, including the bottom level if the stacker is provided with a pit. Each sidewall sprinkler shall cover an area of 80 sq. ft. or less.

The area of application may be reduced from the required 2,500 sq. ft. to as low as 1,500 sq. ft. if:

1. 1-hour fire rated walls are provided to separate the car stacker areas from the standard parking stalls,

2. The car stacker areas are divided up into 1,500 sq. ft. areas via 1-hour fire rated walls, and

3. One-hour fire rated walls are provided to separate the car stacker areas from any other areas in the garage.

One-hour fired rated walls are not required in the driveway areas. For the hydraulic calculation, flow from all sprinklers, upright or pendent sprinklers at ceiling and all sidewall sprinklers at all levels, located in the area of application shall be included in the calculation.

Sec. 4-3.110. Amendments: Section 903.4.3 ("Alarms").

Section 903.4.3 is amended by adding the following to the end of the paragraph:

In addition to the audible device(s) required by this section, an approved strobe light shall be located on the exterior of the building in an approved location.

Sec. 4-3.111. Amendments: Section 904.2.2 ("Commercial hood and duct systems").

Section 904.2.2 is amended by adding the following to the end of the paragraph:

The location(s) of all cooking appliances that are protected by an approved automatic fire extinguishing system shall be permanently identified either by a wall mounted "approved" appliance floor plan or marked on the floor in a manner approved by the Fire Marshal.

Sec. 4-3.112. Amendments: Section 907.7.3 ("Instructions").

Section 907.7.3 of the California Fire Code is amended by adding the following paragraph:

Page 4 of 14 ends

Each fire alarm system shall have posted at the main control panel instructions for silencing and resetting the system, the day and night phone numbers of the person responsible for the property, and the company or individual providing maintenance services for the alarm system.

Sec. 4-3.113. Amendments: Section 907.8.1 ("Maintenance required").

Section 907.8.1 of the California Fire Code is amended by adding the following paragraph:

Owners and operators of group R-1 occupancies shall provide documentation to the Fire Department, such as annual inspection forms, which confirm that all smoke detection devices and equipment within apartment units are installed and are in good operating condition.

Sec. 4-3.114. Amendments: Section 914.3.9 ("High Rise Buildings").

Section 914.3.9 is added to read as follows:

Section 914.3.9 Firefighter Breathing Air Replenishment. All Group B and Group R occupancies, each having floors used for human occupancy located more than seventy-five feet (75') above the lowest level of fire department vehicular access, shall be equipped with an approved Firefighter Breathing Air Replenishment System as outlined in Appendix L. Such a system shall provide an adequate pressurized fresh air supply through a permanent piping system for the replenishment of portable life sustaining air equipment carried by fire department, rescue, and other personnel in the performance of their duties. Location and specifications of access stations to, and the installation of, such air replenishment systems shall be made in accordance with the requirements of the Fire Chief.

Sec. 4-3.115. Amendments: Section 5608.1 ("Fireworks display").

Section 5608.1 is amended by adding the following paragraph:

The sale and discharge of safe and sane fireworks is permitted only as provided in the Pacifica Municipal Code.

Section 5608.1.2 is hereby added to read as follows:
5608.1.2 Dangerous Fireworks Prohibited. Except as hereinafter provided, it shall be unlawful for any person to possess, store, offer for sale, expose for sale, sell at retail, or use or explode any fireworks, except those designated as "safe and sane" and approved by the State Fire Marshal. No person under the age of eighteen (18) shall be permitted to purchase or sell "safe and sane" fireworks. The Fire Chief shall have the power to adopt reasonable rules and regulations for the granting of permits for supervised public displays of fireworks by a jurisdiction, fair association, amusement park, or other organization or for the use of fireworks by artisans in the pursuit of their trade. Every such use or display shall be handled by a competent operator approved by the Fire Chief and shall be of such character and so located, discharged, or fired so as, in the opinion of the Fire Chief after proper investigation, not to be hazardous to property or endanger any person, and shall be in accordance with Chapter 56 of said California Fire Code.

Sec. 4-3.116. Amendments: Section 5706.2.4.4 ("Locations where above-ground tanks are prohibited").

Section 5706.2.4.4 is amended by adding the following paragraph at the end of the section:

The storage of flammable or combustible liquids in above-ground outside storage tanks is prohibited in all areas of the City except for those areas with the zoning designation of Public Facilities District.

Notwithstanding the foregoing, the Fire Chief may grant a permit for such storage in other areas of the City if

Page 5 of 14 ends

the Chief determines, in each case, that the storage is required for the conduct of a lawful use upon the property, will not constitute a safety hazard, and will otherwise comply with all applicable provisions of this Code and all other ordinances, rules and regulations of the City. The Chief may impose such conditions and requirements upon the issuance of the permit, as the Chief deems necessary or appropriate.

Sec. 4-3.117. Amendments: Section 6104.2 ("Maximum capacity within established limits").

Section 6104.2 is amended by adding the following paragraph at the end of the first paragraph:

The aggregate storage of liquefied petroleum gas at any one installation in excess of two thousand (2,000) gallons (7,570 L) is prohibited in all areas of the City except for those areas with the zoning designation of Public Facilities District. Notwithstanding the foregoing, the Fire Chief may grant a permit for such storage in other areas of the City if the Chief determines, in each case, that the storage is required for the conduct of a lawful use upon the property, will not constitute a safety hazard, and will otherwise comply with all applicable provisions of this Code and all other ordinances, rules and regulations of the City. The Chief may impose such conditions and requirements upon the issuance of the permit, as the Chief deems necessary or appropriate.

Sec. 4-3.118. Amendment Appendix D, Section D101 ("General").

Section D101.2 is added to read as follows:

D101.2 - Definition. Fire Apparatus Access Road. A road that provides fire apparatus access from a fire station to at facility, building or portion thereof. This is a general term inclusive of all other terms such as but not limited to fire lane, public street, private street, parking lot lane, access roadway and driveway.

Sec. 4-3.119. Amendments: Appendix D, Section D102 ("Required access").

1. Section D102.2 is added to Appendix D of the California Fire Code to read as follows:

Section D102.2. Fire department access shall extend to within 50 feet (15 m) of at least one exterior door that can be opened from the outside and that provides access to the interior of the building.

Exception: one- or two-family dwellings or townhouses protected with 13D or 13R may be permitted to be increased to 150 ft. (46 m).

2. Section 102.3 is added to Appendix D of the California Fire Code to read as follows:

Large Buildings. Fire department access roads shall be provided such that any portion of the facility or any portion of an exterior wall of the first story of the building is located not more than 150 ft. (46 m) from fire department access roads as measured by an approved route around the exterior of the building or facility.

3. Section 102.4 is added to the California Fire Code to read as follows:

Fire apparatus access roads shall have an unobstructed vertical clearance of not less than 13 ft. 6 in. (4.1 m).

4. Section D102.5 is added to the California Fire Code to read as follows:

Exception: When fire department access roads cannot be installed due to location on the property, topography, waterways, nonnegotiable grades, or other similar conditions the Fire Marshal shall be authorized to require fire protection features in addition to those already required.

Created: 2022-08-12 09:49:03 [EST]
(Supp. No. 52)

Page 6 of 14 ends

Sec. 4-3.120. Appendix D, Section D103 ("Minimum specifications").

Section D103.7 is added to Appendix D of the California Fire Code to read:

D103.7 - Marking where fire lanes on private property have been designated by the Fire Marshal, curbs shall be painted red on the side or sides of the street or access route where parking is prohibited and no parking signs or other appropriate notice prohibiting obstructions, as approved by the Fire Marshal, shall be provided and maintained by the owner.

Below this line, NCFA has not altered language or sections from previous adoptions. No changes made.

Article 2. Fireworks2
Sec. 4-3.201. Definitions.

The most current adopted definitions set forth in the State Fireworks Law (California Health and Safety Code Sections 12500 et seq.) will define the terms used in this article unless otherwise modified herein. (a) "City" means the City of Pacifica.
(b) "Dangerous fireworks" means any fireworks specified as such in Section 12505 of the California Health and Safety Code, including any safe and sane fireworks altered in a manner such that they fall within the definition of dangerous fireworks.
(c) "Eligible organization" means an organization which has met all of the following criteria and which continues to meet the criteria for the duration of any permit to sell issued by the City pursuant to this article:
(1) For a continuous period of not less than one full year preceding submittal of an application for a permit to sell (as defined herein):
(i) The organization shall be at least one of the following:
(A) A non-profit organization pursuant to Internal Revenue Code Sections 501(c)3, 4, 6, 7, 8, 10, 19, 23, or 26; Section 501(d); or Section 501(e); (B) A group which is associated with an organization meeting the requirements of Section 4-3.201(c)(1)(i)(A);
(C) An organization affiliated with and officially recognized by an elementary school, junior high school, high school, or school district that serves, in whole or in part, the residents of Pacifica;
(ii) The organization shall be organized primarily for veterans, patriotic, welfare, civic betterment, or charitable purposes;
(iii) The organization must have its principal and permanent meeting place within the City;
2Editor's note(s)—Ord. No. 815 C.S, effective June 21, 2017, amended Art. 2 in its entirety to read as set out herein.

Former Art. 2, §§ 4-3.201—4-3.211, pertained to similar subject matter and derived from § 2, Ord. 762-C.S., effective July 9, 2008; and Ord. 797-C.S., effective July 24, 2013.

Created: 2022-08-12 09:49:04 [EST]
(Supp. No. 52)

Page 7 of 14 ends

(iv) The organization must be one which provides direct and regular community services and benefits to the residents of the City; (v) The organization must have a minimum bona fide membership of at least twenty (20) members who either reside in the City, are employed in the City, or are owners or operators of a business, or other establishment located in the City;
(2) The organization must not have been cited for or found by any court of competent jurisdiction or City Administrative Hearing Officer to be in violation of any civil or criminal local, state, or federal law relating to fireworks within twenty-four (24) calendar months prior to the organization's submittal of an application for a permit to sell;
(3) The organization must not have had a permit to sell revoked within twenty-four (24) months prior to the organization's submittal of an application for a permit to sell. (d) "Fireworks stand" means any building, counter, or other structure of a temporary nature used in the sale, offering for sale, or display for sale of safe and sane fireworks. (e) "Minor" shall mean a person under the age of eighteen (18) years. (f) "Permit to sell" means a permit required by Section 4-3.204(a). (g) "Public display of fireworks" is defined in Section 12524 of the California Health and Safety Code. (h) "Social host" shall mean any of the following:
(1) Any owner of private property as listed on the most recent assessment roll; (2) Any person who has the right to use, possess, or occupy a public or private property under a lease, permit, license, rental agreement, or contract;
(3) Any person who hosts, organizes, supervises, officiates, conducts, or accepts responsibility for a gathering on public or private property.
(i) "Safe and sane fireworks" means any fireworks specified as such in the State Fireworks Law, Section 12529 of the California Health and Safety Code.
(j) "Special effects" is defined in Section 12532 of the California Health and Safety Code. (k) "Strictly liable" means liability for a wrongful act irrespective of such person's intent, knowledge, negligence, or lack thereof in committing the wrongful act. (§ 3(Exh.A), Ord. 815 C.S, eff. June 21, 2017)
Sec. 4-3.202. General prohibition against ignition, use, discharge, possession, sale, offer for sale, or display of dangerous fireworks.
(a) No person shall ignite, use, discharge, sell, offer for sale, or display for sale any dangerous fireworks, or take any action requiring a permit under Section 12640 of the California Health and Safety Code, without a permit from the Fire Chief.
(b) No person shall possess dangerous fireworks in the amount of twenty-five (25) pounds or less (gross weight including packaging) within City limits without a permit from the Fire Chief. (c) The Fire Chief shall have authority to adopt reasonable rules and regulations for the granting of permits for those activities listed in Section 12640 of the California Health and Safety Code, including public displays of dangerous fireworks and special effects.

Created: 2022-08-12 09:49:04 [EST]
(Supp. No. 52)

Page 8 of 14 ends

(d) Each use or display of dangerous fireworks or special effects shall be handled by a licensed pyrotechnic operator (as defined by Section 12527 of the California Health and Safety Code) in accordance with a Cityissued permit, and shall be ignited, used, or discharged in a manner and location that, in the opinion of the Fire Chief or his or her designee, will not be hazardous to any person. (§ 3(Exh.A), Ord. 815 C.S, eff. June 21, 2017)
Sec. 4-3.203. Ignition, use, or discharge of safe and sane fireworks. (a) Permissible hours of discharge: It shall be unlawful for any person to ignite, use, or discharge any safe and sane fireworks within City limits except between the hours of 12:00 p.m. (noon) to 11:00 p.m. on June 28, and 9:00 a.m. to 11:00 p.m. of each day from June 29 through July 5, inclusive, of the same year. (b) Location limitations of discharge: No person shall ignite, use, or discharge any safe and sane fireworks in any of the locations set forth below:
(1) Upon, over, or onto any property without the consent of the owner. (2) Within ten (10') feet of any residence, dwelling, or other structure used as a place of habitation by human beings.
(3) Within any City park, mini-park, or tot lot.
(4) Within fifty (50') feet of any fireworks stand.
(5) Upon, over, or onto any beach within the City except for that designated portion of beach immediately west of the north Pacifica State Beach/Linda Mar Parking Lot located at 5150 Coast Highway, to approximately ten (10') feet east of the tide line and immediately north of the property located at 5200 Coast Highway to the prolongation of the north end of the north Pacifica State Beach/Linda Mar Parking Lot.
(c) Discharge by unsupervised minors prohibited: It shall be unlawful for any minor to ignite, use, or discharge any safe and sane fireworks unless under the direct supervision and in the immediate presence of a parent, legal guardian, or other custodial adult eighteen (18) years of age or older. (§ 3(Exh.A), Ord. 815 C.S, eff. June 21, 2017)
Sec. 4-3.204. Sale, offer for sale, or display of safe and sane fireworks. (a) Permit required. It shall be unlawful for any person to sell, offer for sale, or display for sale any safe and sane fireworks within the City limits without having first procured a valid permit to sell in accordance with the provisions of this article and Administrative Policy #68, as amended from time to time. The maximum number of permits to sell that may be issued during any calendar year shall not exceed fifteen (15). (b) Approved fireworks stand required. It shall be unlawful for any person to sell, offer for sale, or display for sale safe and sane fireworks except from within an approved fireworks stand in accordance with the provisions of this article and Administrative Policy #68, as amended from time to time. (c) Hours of sale. It shall be unlawful to sell, offer for sale, or display for sale any safe and sane fireworks within the City limits except between the hours of 12:00 p.m. (noon) to 10:00 p.m. on June 28, and 9:00 a.m. to 10:00 p.m. of each day from June 29 through July 4, inclusive, of the same year. (d) Sale to minors prohibited. It shall be unlawful for any person to cause, permit, allow, aid, abet, or suffer the sale of any safe and sane fireworks to a minor at any time. (§ 3(Exh.A), Ord. 815 C.S, eff. June 21, 2017)
Created: 2022-08-12 09:49:04 [EST]
(Supp. No. 52)

Page 9 of 14 ends

Sec. 4-3.205. Application for permits to sell, offer for sale, or display safe and sane fireworks.

Any eligible organization, as defined by this article, desiring to sell, offer for sale, or display for sale any safe and sane fireworks shall submit a complete application for a permit to sell to the City Manager, on a City-approved form, after the first Monday of January and before the first Monday of February. All applications for a permit to sell shall contain the following:
(a) The full name and address of the applicant and, if incorporated, the names and addresses of the officers thereof;
(b) The proposed location of the fireworks stand;
(c) An assurance that, if granted a preliminary permit to sell, the applicant, not later than June 15, shall deliver to the Finance Department a certificate evidencing a policy of insurance for public liability and property damages with a minimum of one million and no/100ths ($1,000.000.00) dollars combined single limit with an endorsement attached thereto designating the City of Pacifica as an additional insured hereunder. The endorsement shall be executed by a company authorized to carry on an insurance business in the State of California, and having an A.M. Best's Rating of at least A:VIII; (d) An agreement to hold harmless, indemnify, and defend the City of Pacifica, its officials, officers, employees, and agents, against any and all claims arising from the applicant's sale of fireworks. (e) An agreement stating that, if granted a permit to sell, the applicant will perform not less than twenty (20) hours of cleanup-related community service prior to August 31 at the times and locations designated by the City.
(f) Any other information deemed necessary by the City Manager. (§ 3(Exh.A), Ord. 815 C.S, eff. June 21, 2017)
Sec. 4-3.206. Notice of approval for permits to sell, offer for sale, or display safe and sane fireworks.

The City Manager shall notify successful applicants of their selection, and issue to each successful applicant a preliminary permit to sell on or before the first Monday in March of each year. The preliminary permit shall not become final until the applicant has timely complied with Section 4-3.207(a), Section 4-3.208(c)(1), and Section 4-

3.208(a)(3) of this article.
(§ 3(Exh.A), Ord. 815 C.S, eff. June 21, 2017)
Sec. 4-3.207. Fees for permits to sell, offer for sale, or display safe and sane fireworks.

Each permittee shall tender a permit fee to the Pacifica Finance Department in two (2) parts. The amount of each part of the fee shall be as stated in the City's Master Fee and Charges Schedule, as amended from time to time.
(a) The permittee shall pay Part 1 of the fee on or before March 31 of the year authorized pursuant to the permit to sell.
(b) The permittee shall pay Part 2 of the fee on or before September 1 of the year authorized pursuant to the permit to sell.
(§ 3(Exh.A), Ord. 815 C.S, eff. June 21, 2017)
Created: 2022-08-12 09:49:04 [EST]
(Supp. No. 52)

Page 10 of 14 ends

Sec. 4-3.208. Fireworks stands; construction, location, operating, cleanup, and reporting requirements.
(a) Construction requirements. It shall be unlawful for any person to erect, install, use, operate, or maintain a fireworks stand unless the stand complies with the following:
(1) Fireworks stands shall not be erected on any property sooner than June 21 of the year in which fireworks sales have been authorized pursuant to a permit to sell. (2) The erection of a fireworks stand need not comply with the provisions of the Pacifica Building Code; however, the installation, use, and maintenance of any utilities therein shall comply with the Pacifica Municipal Code and/or codes adopted therein.
(3) All fireworks stands shall be inspected by the Fire Department to ensure that the stand is constructed in a manner which will reasonably ensure the safety of attendants and patrons and that the fireworks stand meets the requirements of this article.
(4) No fireworks stand shall have a floor area in excess of seven hundred fifty (750) square feet. (5) Each fireworks stand in excess of twenty-four (24') feet in length shall have at least three (3) exits spaced approximately an equal distance apart; provided, however, in no event shall the distance between exits exceed twenty-four (24') feet.
(6) Exit doors shall swing in the direction of egress.
(7) Except for openings to permit the delivery of merchandise to the prospective customer, which openings shall not be larger than twelve (12") inches by eighteen (18") inches in size, the front of each fireworks stands shall be completely enclosed from the counter to the roof with:
(i) Hardwire cloth, the openings of which shall not exceed one-fourth (¼") inch in size; or (ii) Plexiglas.
(8) Each fireworks stand shall have at least two (2) fire extinguishers with minimum 2A-10B:C capacity, mounted, recently serviced, in good working order, and easily accessible for use in case of fire. (9) "No smoking" signs prohibiting smoking within twenty-five (25') feet of the stand shall be prominently displayed on the exterior of each fireworks stand.
(10) A sign with letter size of at least one inch high on contrasting background stating "NO PERSON UNDER THE AGE OF 18 YEARS SHALL BE PERMITTED TO PURCHASE FIREWORKS" shall be posted on the outside of the fireworks stand in a conspicuous location.
(11) A sign with letter size of at least one inch high on contrasting background stating "NO PERSON UNDER THE AGE OF 18 YEARS SHALL SELL, OR HANDLE FOR SALE, ANY CLASSIFICATION OF FIREWORKS" shall be posted on the inside of the fireworks stand in a conspicuous location. (b) Location requirements. It shall be unlawful for any person to erect, install, use, operate, or maintain a fireworks stand unless the stand complies with the following:
(1) No fireworks stand shall be located within twenty-five (25') feet of any other building. (2) No fireworks stand shall be located within fifty (50') feet of any gasoline storage tank or dispensing unit.
(c) Operating requirements. It shall be unlawful for any person to use, operate, or maintain a fireworks stand without complying with all of the following:

Created: 2022-08-12 09:49:04 [EST]
(Supp. No. 52)

Page 11 of 14 ends

(1) On or before June 15 of any year authorized pursuant to a permit to sell, each permittee shall obtain each of the following and submit copies of the same to the Pacifica Finance Department:
(i) State Fire Marshal's retail fireworks license;
(ii) Temporary sales tax permit from the California State Board of Equalization; (iii) Insurance in the amount and manner described in Section 4-3.205 of this article; and (iv) Written consent from the owner of record of the real property which is the proposed location of the fireworks stand to the placement of the fireworks stand and conduct of fireworks sales on the real property.
(2) No person other than an adult member of the eligible organization, spouse of a member, adult child of a member, or parent of a member who is a minor shall operate the fireworks stand. Only eligible organizations shall share or otherwise participate in the profits of the operation of such stand. (3) No person under the age of eighteen (18) years shall sell or handle for sale fireworks from a fireworks stand.
(4) During the hours of sale, no person shall be allowed in the interior of a fireworks stand, except those directly engaging in the sale of fireworks.
(5) Each fireworks stand shall have an adult over the age of eighteen (18) years in attendance and in charge thereof when fireworks are stored therein (including during hours when fireworks are not being actively sold, offered for sale, or displayed for sale). (6) Each permittee shall post its City of Pacifica permit to sell, temporary sales tax permit from the California State Board of Equalization, State Fire Marshal's retail fireworks license, and proof of insurance (as required pursuant to the provisions of this article) in a prominent place inside of the fireworks stand.
(7) No permittee shall permit or suffer smoking within twenty-five (25') feet of the fireworks stand. (8) No permittee shall permit or suffer the use or discharge of fireworks within fifty (50') feet of the fireworks stand.
(9) All weeds, litter, trash, and combustible materials shall be cleared from the location of fireworks stands, including a distance of at least twenty (20') feet surrounding the stand, and each permittee shall maintain the location of the fireworks stand in a neat, clean, and sanitary condition at all times. (10) Approved rubbish and/or recycling containers in accordance with City standards shall be provided at each fireworks stand location.
(d) Cleanup and reporting requirements. All permittees shall comply with all of the following:
(1) All unsold stock and accompanying litter shall be removed from the location of the fireworks stand, and from related storage containers, by 12:00 p.m. (noon) on July 6 of the year authorized pursuant to the permit to sell.
(2) Fireworks stands and related storage containers shall be removed from their temporary locations by 12:00 p.m. (noon) on July 18 of the year authorized pursuant to the permit to sell. (3) On or before August 31, the permittee shall perform twenty (20) hours of cleanup-related community service according to the agreement signed pursuant to Section 4-3.205(e) at the times and locations determined by the City. Each permittee shall perform ten (10) hours of cleanup-related community service on July 5, and an additional ten (10) hours prior to August 31. (4) On or before September 1 of any year authorized pursuant to a permit to sell, the permittee shall submit to the Finance Department a financial statement by the treasurer or financial officer of the Created: 2022-08-12 09:49:04 [EST]
(Supp. No. 52)

Page 12 of 14 ends

permittee setting forth the total gross receipts from each fireworks stand operated by the permittee, all expenses incurred and paid in connection with the purchase of fireworks and the sale thereof, and to whom and for what purpose the net proceeds were disbursed, along with the most recent report filed by the permittee to the State Board of Equalization. (§ 3(Exh.A), Ord. 815 C.S, eff. June 21, 2017)
Sec. 4-3.209. Strict liability for unlawful ignition, use, or discharge of fireworks by another person.
(a) Ignition, use, or discharge by minors. Any person having the care, custody, or control of a minor shall be strictly liable for any unlawful ignition, use, or discharge of dangerous fireworks or safe and sane fireworks in violation of Section 4-3.202 or Section 4-3.203 by such minor. (b) Social host liability. Any social host shall be strictly liable for any unlawful ignition, use, or discharge of any dangerous fireworks or safe and sane fireworks in violation of Section 4-3.202 or Section 4-3.203 at his or her property or gathering; except that:
(1) No owner of private property shall be liable under this subsection (b) for a violation of Section 4-3.202 or Section 4-3.203 on that property if that owner can demonstrate that at the time of such violation he or she
(i) Had rented or leased the property to another;
(ii) Was not present; and
(iii) Had no prior knowledge of the violation.
(2) No person who has the right to use, possess, or occupy a unit in a multifamily residential property under a lease, rental agreement, or contract shall be liable under this subsection (b) for violations of Section 4-3.202 or Section 4-3.203 occurring in the common areas of such property. (3) Nothing in this subsection (b) shall limit the liability of any social host for a violation of Section 4-3.202 or Section 4-3.203 of this article by the social host.
(§ 3(Exh.A), Ord. 815 C.S, eff. June 21, 2017)
Sec. 4-3.210. Penalties for violations.
(a) Except for violations of Section 4-3.202 for which a penalty is prescribed in Section 12700 et seq. of the California Health and Safety Code, each violation of this article, including the rules and regulations promulgated by the Fire Chief under Section 4-3.202(c), shall be a misdemeanor and shall be punishable by a fine not exceeding one thousand and no/100ths ($1,000.00) dollars and/or six (6) months in jail. (b) Each violation of this article, including the rules and regulations promulgated by the Fire Chief under Section 4-3.202(c), shall also be punishable by a civil fine in accordance with Title 1, Chapter 6 of this Code, and subject to appeal through the procedures stated therein. (1) Notwithstanding Section 1-6.04(b), no warning is required prior to the issuance of an administrative citation for the violation of this article.
(2) Any civil fine assessed and collected for a violation of Section 4-3.202(b) of this article shall include the actual costs associated with the collection, transportation and disposal of any seized fireworks, in accordance with regulations duly adopted by the State Fire Marshal, which costs shall be forwarded to Created: 2022-08-12 09:49:04 [EST]
(Supp. No. 52)

Page 13 of 14 ends

the State Fire Marshal. Moreover, civil fines assessed and collected for a violation of Section 4-3.202(b) of this article shall not be subject to California Health and Safety Code Section 12706. (c) Failure to comply with the requirements of Section 4-3.208 shall constitute grounds for revocation of a permit to sell.
(1) An enforcement officer revoking a permit to sell shall provide the permittee with a notice of revocation containing the following information:
(i) The name of the permittee;
(ii) The address or description of the location of the violation(s); (iii) The date and approximate time of commission of the violation(s); (iv) The code section(s) violated;
(v) A description of the violation(s);
(vi) A description of the appeal process for revocation of permits; (vii) The name and signature of the officer.
(2) Any permittee whose permit to sell has been revoked shall be entitled to a copy of the evidence supporting the revocation upon request to the Police Department within twenty-four (24) hours of the receipt of the request.
(3) Before July 2, any permittee whose permit has been revoked is entitled to contest the revocation by filing a request for an expedited appeal with the Police Department. A permittee's failure to file a complete request for an expedited appeal prior to July 2 shall constitute a waiver of the right to an expedited appeal.
(4) A request for an expedited appeal must contain the following:
(i) The name, address, telephone, and any facsimile numbers, of the permittee contesting the revocation;
(ii) A statement of the reason(s) why the revocation is being contested; (iii) Any evidence in support of the permittee's argument; (iv) The date and signature of an officer of the permittee. (5) Upon receipt of a request for an expedited appeal, the City Manager, or his or her designee, shall issue a written decision based on evidence upholding or overturning the revocation of the permit and shall state the reasons therefor. The City Manager, or his or her designee, shall serve the decision on the permittee by first-class mail, postmarked not less than two (2) business days after the receipt of the expedited appeal. The decision of the City Manager, or his or her designee, on an expedited appeal of a revocation shall be final.
(6) Any permittee whose permit to sell has been revoked, and who has not filed an expedited appeal, may contest the revocation in accordance with the appeal procedures set out in Section 1-6.07 et seq. of this Code. A permittee who has not filed a complete expedited appeal prior to July 2, and who has not filed a complete timely appeal pursuant to this section shall be deemed to have waived its right to an appeal of the revocation of the permit to sell.
(d) Any violations of Sections 4-3.202, 4-3.203, 4-3.204, 4-3.208, or 4-3.209 of this article are hereby declared to be public nuisances and subject to abatement in accordance with Title 5, Chapter 25 of this Code or emergency abatement in accordance with Section 1-2.08 of this Code. All such violations are further declared to be an immediate or imminent hazard or threat to life, limb, health, property, safety or welfare such that it Created: 2022-08-12 09:49:04 [EST]
(Supp. No. 52)

Page 14 of 14 ends

would be unreasonable and dangerous to persons or property to expend the time necessary to seek City Manager approval and allow for voluntary abatement prior to emergency abatement. Any actions to recover costs of abating violations of this article shall be subject to the procedures in Section 5-25.13 et seq. and may include the actual costs associated with the collection, transportation, and disposal of any seized fireworks.

Appeals of the City's determination of nuisance, determination to use emergency abatement procedures, or amount of recoverable costs shall be subject to appeal pursuant to Title 5, Chapter 25, Article 2 of this Code.

Appeals of the amount of recoverable costs must be filed within ten (10) days of the responsible party's receipt of the City's statement of costs pursuant to Section 5-25.13. (e) Causing, permitting, aiding, abetting or concealing a violation of any provision of this article shall also constitute a violation.
(f) The remedies provided by this article are cumulative and in addition to any other remedy available at law or in equity.
(§ 3(Exh.A), Ord. 815 C.S, eff. June 21, 2017)
Sec. 4-3.211. Concurrent authorities.

This article is not the exclusive regulation for fireworks within the City of Pacifica. This article shall supplement and be in addition to the other regulatory codes, statues, regulations, and ordinances heretofore and hereinafter enacted by the City of Pacifica, the State of California, or any other legal entity or agency having jurisdiction.

Where allowed by law, this article supersedes any conflicting provisions of the California Fire Code and Building Code.
(§ 3(Exh.A), Ord. 815 C.S, eff. June 21, 2017)