Placentia Planning Commission
AGENDA STAFF REPORT
TO: PLANNING COMMISSION
FROM: ANDREW A. GONZALES, PLANNING MANAGER
DATE: NOVEMBER 14, 2023
SUBJECT: TENTATIVE PARCEL MAP NO. TPM 2020-124, USE PERMIT NO. UP 2023-10, AND SITE PLAN REVIEW NO. SPR 2023-02; 803 W. LA JOLLA
STREET (CHD INTERNATIONAL)
RECOMMENDATION
It is recommended that the Planning Commission take the following actions:
1) Open Public Hearing, concerning Tentative Parcel Map No. TPM 2020-124, Use Permit No. UP 2023-10, and Site Plan Review No. SPR 2023-02; and 2) Receive the staff report and consider all public testimony; and 3) Close the public hearing; and
4) Adopt Resolution No. PC -2023-16, a Resolution of the Planning Commission of the City of Placentia, approving UP 2023-10 and SPR 2023-02, and making findings to permit the development of an improved approximately 0.19 -gross acre lot for the construction of a two-story, multi -family building consisting of three attached residential townhome units and associated hardscape and landscape improvements within the High Density Residential (R-3) Zoning District on property located at 803 W. La Jolla Street; and making findings that the project is categorically exempt pursuant to the California Environmental Quality Act (CEQA) set forth in Title 14 CCR § 15332 (Class 32 — In -Fill Development Projects) and the City of Placentia Environmental Guidelines; and 5) Adopt Resolution No. PC -2023-17, a Resolution of the Planning Commission of the City of Placentia, recommending that the City Council of the City of Placentia approve TPM 2020-124 to permit the subdivision of three townhome units for residential condominium purposes requested via UP 2023-10 and SPR 2023-02 subject to the Conditions of Approval and Standard Development Requirements; and making findings that the project is categorically exempt pursuant to the California Environmental Quality Act (CEQA) set forth in Title 14 CCR § 15332 (Class 32 — In -Fill Development Projects) and the City of Placentia Environmental Guidelines.
Planning Commission Meeting
November 14, 2023
TPM 2020-124, UP 2023-10, and SPR 2023-02
REQUEST:
The applicant, CHD International, requests approval of a Use Permit, Site Plan Review, and Tentative Parcel Map to develop an existing 0.19 -gross acre site containing an existing single-family residence with a two-story townhome development resulting in three attached condominium townhome units. The three units will be contained within a single building.
The proposed development will have a residential density of 16 dwelling units per acre.
Three floor plans are proposed which are noted on the development plans as "Unit A", "Unit B", and "Unit C". The plan types will measure between 2,135 square feet and 2,288 square feet in overall floor area and contain an attached two -car garage per unit. Each unit will have three bedrooms and 2.5 baths. The building will be two stories at a height of approximately 27 feet. A total of 7 parking spaces will be provided, comprised of 6 garage spaces, and 1 guest parking space.
Vehicular access to the project will be provided by a 9 -foot -wide driveway connection to W.
La Jolla Street. The narrow driveway has been determined by Planning and Engineering staff to be an appropriate width due to the anticipated low usage the driveway will experience resulting from the small number of units onsite. A vehicle courtyard will provide direct access to each individual garage. The Vehicle courtyard will be articulated with decorative paving to create a dual use area for both passive and active usage. Decorative landscaping will be provided throughout the site.
PROJECT CHARACTERISTICS
Applicable Code Section — Placentia Municipal Code
The project is located within the R-3 Zoning District. The project will be required to comply with the development standards and use requirements set forth in the Placentia Municipal Code (PMC) for projects located within the R-3 Zoning District. Pursuant to PMC Section
23.75.010(b), construction of four or less dwelling units in a residential zone are exempt from processing a Development Plan Review (DPR) but are instead required to file a Site Plan Review (SPR) for review and final action by the Development Services Department.
In accordance with PMC Section 23.21.030 the establishment of a condominium or townhome requires a UP to be reviewed and approved at a noticed public hearing before the Planning Commission. The TPM requires a recommendation by the Planning Commission to be forwarded to the City Council pursuant to PMC Section 22.80.060. The concurrent processing of entitlement applications necessitates all applicable requests to adhere to the most restrictive process, which due to the UP request requires the SPR to be reviewed and acted on by the Planning Commission. Only the TPM will be acted upon by the City Council in the absence of an appeal.
Subiect Site and Surrounding Land Uses
The table below illustrates the site and surrounding existing land uses, General Plan Land Use designation and zoning:
Planning Commission Meeting
November 14, 2023
TPM 2020-124, UP 2023-10, and SPR 2023-02
Location Existing Land Use
Detached, Single -
Existing Family Residential
Attached, Multi -Family
Proposed Residential
Multi -Family
North Residential
South (across
W. La Jolla
Street)
East (across
Lawrence
Street)
West
Attached, Multi -Family
Residential
Attached, Multi -Family
Residential
Multi -Family
Residential
ZONING COMPLIANCE ANALYSIS
Site Development Standards
Land Use Element
General Plan
Designation
High Density
Residential
High Density
Residential
High Density
Residential
High Density
Residential
High Density
Residential
High Density
Residential
Zoning Map
Designation
High Density Residential
(R-3)
R-3
R-3
R-3
R-3
R-3
The project is located within the R-3 Zoning District. The proposed residential townhome development project is permitted with a UP and SPR subject to review and approval by the Planning Commission. The proposed development and use comply with the base zoning district in terms of the maximum height limit, minimum setbacks, minimum onsite parking, and maximum lot coverage requirements. No impacts to nearby sensitive land use receptors (e.g., residential) is anticipated because the project will be similar in nature as the existing multi -family developments abutting the subject site. The following matrix provides a summary of the development's compliance with the identified development standards:
STANDARD PROJECT
Height
35 ft. max.
26 ft 11 in.
Setbacks
Front Yard Setback — 15 ft. min. Front: 15 ft. (W. La Jolla Street)
Planning Commission Meeting
November 14, 2023
TPM 2020-124, UP 2023-10, and SPR 2023-02
Street Side Yard Setback — 10 ft. min. Lawrence Street Side Yard — 10 ft.
Interior Side Yard Setback — 5 ft. min. West Side Yard: 9 ft.
Rear Yard Setback - 10 ft. min. Rear Yard: 10 ft.
Building Separation
20 ft. min. Not Applicable
Lot Coverage
60% max. (4,943 sq. ft.) 38.7% (3,165 sq. ft.)
Parking
Two spaces per dwelling: 6 spaces min. 6 spaces
Additional 15% min. of total parking
required for guest parking: 1 spaces min. 1 space
Total Parking Required: 7 spaces min. 7 spaces
Lot Area and Dimensions
Minimum Lot Area: 9,000 sq. ft. Lot Area: 8,238 sq. ft. (0.19 -gross acres)* Minimum Lot Width: 90 linear ft. Approx. 75 linear ft.* Exception*: Any lot or parcel of land under one (1)
ownership and of record thirty (30) days before the
effective date of the ordinance codified in this chapter, and where no adjoining land is owned by the same person,
may be used as a building site even when of less area or width than that required by the regulations for the district in which it is located (PMC Sect. 23.81.110)
Other Departments Concerns and Requirements
The Divisions of Planning and Building, Public Works Department, as well as the Orange County Fire Authority have reviewed the application and submitted comments but had no major concerns with the proposal. All applicable code requirements and conditions of approval have been incorporated into draft resolutions for consideration and approval by the Planning Commission for UP 2023-10 and SPR 2023-02, and consideration and recommendation by the Planning Commission to the City Council for TPM 2020-124.
Planning Commission Meeting
November 14, 2023
TPM 2020-124, UP 2023-10, and SPR 2023-02
ISSUES ANALYSIS:
Consistency with the General Plan
The General Plan features policies that promotes the reinvestment of underutilized properties while being sensitive to the suburban atmosphere and requires new developments to provide adequate improvements and pay impact fees to offset the demand costs on city services and facilities. The proposed development and subdivision is consistent with the following Land Use policies of the General Plan:
Policy LU -1.2 — Allow for a variety of residential infill opportunities including single family, multi -family, mixed-use, manufactured housing, and mobile homes, in designated areas to satisfy regional housing needs.
Policy LU -2.4 — Large, contiguous vacant or underutilized parcels should be comprehensively planned for development to be compatible with adjacent neighborhoods.
Development of vacant property will promote further compatibility with existing developments within the surrounding area. The proposed project will be consistent with the General Plan and will result in a compatible continuation to existing land uses and development within the surrounding area, including adding to the city's housing inventory and assisting to satisfying the regional housing demand.
Land Use Compatibility
The project will be compatible with the surrounding area as the development will revitalize an underutilized and undeveloped property with the development of a two-story multi -family building consisting of three attached residential townhome units. The development project will be located within a developed and established area that aims to create and foster a symbiotic relationship with nearby land uses. The development will provide a compatible transition between nearby land uses that complements the residential densities of housing developments to the north, south, and east. Based upon the land use, overall site layout, and building design, the proposed development is not anticipated to result in any significant adverse impacts to the surrounding area.
Architecture
The proposed project will include a townhome building consisting of three units. There are three floor plans proposed ("Unit A", "Unit B", "Unit 0"). The residential buildings will utilize craftsman bungalow style architectural features such as a low-pitched roof with a hip and gable roof system, horizontal lap siding, partial width porches with elephantine base columns, river rock base cladding, simulated divided light windows, earth tone colors, window shutters, and exposed rafter tails. The overall building mass is appropriately broken up into different building volumes utilizing design techniques as contrasting building colors, building plain projections, variable roof styles, and doorway/window insets which all assist in minimizing the potential for the building to appear monolithic. The project employs
Planning Commission Meeting
November 14, 2023
TPM 2020-124, UP 2023-10, and SPR 2023-02
four-sided architecture by using the same material on all four sides of a structure so that, no matter what vantage point it is viewed from, the design is never interrupted, and all the parts are perceived as part of a unified whole.
CEQA
The proposed application was reviewed by staff in accordance with the requirements of the California Environmental Quality Act ("CEQA"), Public Resources Code §§ 21000 et seq., the State CEQA Guidelines, 14 C.C.R. §§ 15000 et seq., and the Environmental Guidelines of the City of Placentia. Staff recommends that the Planning Commission exercise its independent judgment and find that UP 2023-10, SPR 2023-02, and TPM 2020-124 is exempt from CEQA pursuant to State CEQA Guidelines § 15332 (Class 32 — Infill Development Projects).
PUBLIC NOTIFICATION
Legal notice was published in the Placentia News -Times on November 2, 2023. Notices were sent to property owners of record within a 300 -foot radius of the subject property, posted at the Civic Center, and on the City website on November 2, 2023. As of November 8, 2023, staff has received no communication in support or opposition to the requested development project.
CONCLUSION
The proposed project is consistent with the City's General Plan and meets the minimum development standards of the PMC. With the recommended conditions of approval, it is the determination of city staff that the proposed development will be compatible with adjacent land uses and will not result in any adverse impacts onto the surrounding neighborhood.
RECOMMENDATION
Staff recommends that the Planning Commission of the City of Placentia adopt Resolution PC -2023-16 approving UP 2023-10 and SPR 2023-02, and that the Planning Commission
Planning Commission Meeting
November 14, 2023
TPM 2020-124, UP 2023-10, and SPR 2023-02
recommend to the City Council of the City of Placentia adoption of Resolution PC -2023-17 recommending approval of TPM 2020-124.
Prepared and submitted by:
Andrew A. Gonzales
Planning Manager
Reviewed and approved by:
eph . Lambert
Director of Development Services
ATTACHMENTS:
1. Resolution No. PC -2023-16
2. Resolution No. PC -2020-17
3. Vicinity Map
4. Project Plans including the Site Plan, Floor Plans, Building Elevations, Preliminary Landscape Plan, colored renderings, Tentative Parcel Map (TPM 2020-124) and Colors and Materials Palette Received and Dated October 3, 2023
5. Affidavit of Mailing, Legal Hearing Notice, Radius Map, and Address List
T1P
HA C]ER ANK • LAP SONG
HEATF MOSS
T'rP
CCUCR a.NV ECyNAFc6
I1.•a18 ..99E J •J
WAG'S 3J\ CO\9O -
AC_\
803 W LA JOLLA ST. PLACENTIA, CA 92870
'TP
PEW FS-A.L -1'04 ❑F PO3FNJG M. TEF 4L
SAXCNY9X SHAD G.? 'ET @CFTC
DC-EM1 1617 .arO OAR( BR3A14 FEfl DRAY
MLLTCCILCF1 CCLOR
T'ieP
LA RABR4 ST...CC3
666 SOU-KRY A/CE6
aa'
TYP
TUSCANY DCF
int Eli T
T'IP
EL.eyCO���RpA��DOeTTy
5C . Rtaffi RGOC
C 1ORACO �c
GENERAL I N EORMATI ON
1. PROJECT ADDRESS:
803 W LA JOLLA ST. PLACENTIA, CA 92870
T•R
CCL. CR 0.1d1 ANDS
Fi448 ft i1. EPE `1
2. SCOPE OF WORK:
1. DEMO EXISTING RESIDENCE
2. CONSTRUCTING 3 NEW TWO-STORY CONDO W/ 2 -CAR GARAGE
FOR EACH UNIT
3. NUMBER OF STORY: 2
4. BUILDING HEIGHT: 27'-02"
5. ZONGING: R-3 HIGH DENSITY RESIDENTIAL
AREAS FOR BUILDING DEPARTMENT USE:
UNIT
FIRST FLOOR
SECOND FLOOR
TOTAL LIVING AREA
GARAGE
TOTAL AREA
LOT AREA
A
620
1058
1678
424
2102
8237.5 SF.
B C
650
1269
1919
417
2336
LOT COVERAGE: 3180 SF.
3 180 / 8237.5 = 38.6%
LEGAL JURISDICTION:
CITY OF PLACENTIA, CALIFORNIA
645
1052
1697
424
2121
TPP.
MIGKC IAA ROENGL SS WNDyh'
• P4I19C14 WANE COLOR MAa POUT "•P
CCL 3R WW1 EOWA¢as
FPC= CM BROWN
- ExTERN:s cuAAE COL.CA . BLA34 MAN
• U -+-ACTOR C29
• 9GC 021
-WE3a.AE6
G. GROUP OCCUPANCY: R-3 $ U
7. CONSTRUCTION TYPE: V -B
8. FIRE ZONE: NONE
9. PUBLIC SEWER: YES
1 0. FIRE SPRINKLER: NO
TlP
MLR Gu'vd EE]W TFDE
FIC -15 OAK BRGM4
NOTE:
ENTIRE LOT TO BE DEMOLITION AND REBUILD NEW. SEE BELOW FOR DETAILS.
THESE CALCULATIONS ARE FOR ARCHITECTS USE ONLY AND ARE NOT INTENDED FOR
USE BY OTHERS
APPLICABLE CODES:
2022 CALII-OKNIA BUILDING CODE (CBC)
2022 CALII-OKNIA RESIDENTIAL CODE (CKC)
2022 CALIFOKNIA ELECTRICAL CODE (CEC)
2022 CALIFORNIA MECHANICAL CODE (CMC)
2022 CALIFORNIA PLUMBING CODE (CPC)
2022 CALII-OKNIA FIKE CODE (CFC)
2022 CALII-OKNIA GREEN BUILDING STANDARD CODE (GBC)
2022 BUILDING ENERGY EFFICIENCY STANDARDS
2022 CALIFOKNIA ENERGY CODE (TITLE 24, PART 6
PLACENTIA MUNICIPAL CODE)
PUBLIC SAFETY, TITLE 19, CALIFORNIA CODE OF
REGULATIONS, STATE MKE MARSHAL REGULATIONS.
VICINITY MAP
MU, n5 nae.el. n Om.
krufM r.
04 ASA.. soaref W ,12
IIS ARUIICI Na ISSuaS Nr 1.1.+1(1;,
u prxrAr
aS. NM IcrIKINa tte.
C �'alPN P.aS(a cuar.SvS5 2
IIIRCN H71
GOLDEN STATE
(al
LA JOLLA -
03 GOLDEN srAr( TR.
TRACT 4V 350
PARCEL MAP
a
BLAJ. 9
Le,
0 TRACT
1!4 I
M. M. a -66
M. M. IS -20
P. At 119-37
VICINITY MAP
12 MOTE - AS5E5501r'5 BLOCK 4
PARCEL NMBE5$
SNOAN IN CIRCLES
0 0
O
14. 0
NO 558
0,8
STREET 1 -
ASSE550r'5 ANP
806. 344 PAGE 13
COLWTT Or 01ANCE
344-13
- 1/
OU -Hain of Placenlie
OReartecn Allc o
OArgas Stora
Holy land Olive Wood
0 M.vrry Lk•k Drst•dn.::n
Pat's Paltering
EBagw.
nt8
l -U Truck t Auto Papaw
Placentia Wroe-s0
OCty Service Paring
OP•ra Placentia
AW,rle,rl.
0 Hactetda 13 Jolla
Peewees Market
FI Addle Apartments
Mils Le Jolla Apart Os
LOT COVERAGE
PL
FL
7,„e7
FL
LOT COVERAGE
3181 SQ.FT
3 1 81 / 8237.5 = 38.6%
LOT AREA
8237.5 SQ.FT.
FL
OWNER'S I N EO
STEVEN WANG
CELL: 626-688-8787
EMAIL: [email protected]
17746 NEAKBANK DR.
ROWLAND HEIGHTS, CA 91748
FL
SHEET INDEX
ID SKEET TITLE
A-1.0 GENERAL INFORMATION
A-2.0 PROPOSED SITE PLAN
A-3.0 GRADING PLAN
A-4.0 EROSION CONTROL PLAN
A-5.0 LANDSCAPING PLAN
A-6.0 PROPOSED 1ST FLOOR PLAN
A-7.0 PROPOSED 2ND FLOOR PLAN
A-8.0 PROPOSED ROOF PLAN
A-9.0 WINDOWS $ DOORS SCHEDULE
A-10 ELEVATION VIEW 1
A- 1 1 ELEVATION VIEW 2
A-12 SECTION VIEWS 1
A-13 SECTION VIEWS 2
A-14 COLORED ELEVATION VIEW 1
A-15 COLORED ELEVATION 2
A-16 MATERIAL BOARD 1
A-17 MATERIAL BOARD 2
LEGAL DESCRIPTION
APN : 344- 1 3 1- 1 1
TPM: 2020-124
TRACT: 16705 LOT: 9
ADDRESS: 803 W LA JOLLA ST.
PLACENTIA, CA 92870
PROJECT TEAM INFORMATION
ARCHITECTURAL:
STEVEN Z. WANG
C: 626-688-8787
E-MAIL: [email protected]
17746 NEARBANK DR.
ROWLAND HEIGHTS, CA 91748
STRUCTURAL:
Z.Y.NI ENGINEERING STRUCTURAL
CONSULTANT
TEL: 626-298-1828
8232 GARVEY AVE.
ROSEMEAD, CA 91770
T-24:
PERFECT DESIGN $ INVESTMENT, INC.
TEL: 626-289-8808
E-MAIL: [email protected]
24 16 W. VALLEY BLVD.
ALh AM B RA, CA 91803
REVISION DATE
z
J
5 0
z
0 U
z
m
z
1Q
z
W
U
0 . 0
co
Q_1 0--)
0 <
� U
Q
Q
0 0<
3_
STREET ADDRESS
803 W LA JOLLA ST.
PLACENTIA, CA 92870
if
WANG'S 3 -UNIT
CONDO - PLACENTIA
0 DRAWN BY:
STEVEN Z. WANG
DATE:
09. 18.2023
z TITLE:
@ GENERAL INFORMATION
A-I.O
TYPE
(SEQUENCE
FILE NAME:
LEGEND:
14 a NEW CONCRETE PAVING
+ + + + + +
+ + + + + +
NEW GRASS / PLANTER
NEW RED CONCRETE PAVER
NEW METAL FENCE
NOTE:
1 . CONDENSOK UNITS NEED TO BE SCREENED WITH DECORATIVE SCREEN. SCREENING SHOULD BE DURABLE $ CAPABLE TO
WITHSTAND ALL WEATHER-RELATED ELEMENTS.
r);
(N) REMOTE C )NTROL
METAL SLIDING GATE
(E) LIGhT POLE
301-011
(N) METAL FEI~CE
(E) SCE HIGH
VOLTAGE
(N) 5/8" WATER
METER
(N) 5/8" WATER
METER
(E) 5/8" WATER
METER
4 /
/
/
(N) RED
CONCRETE PAVER
2% =
U
+
+ +
+ + + + +
I 'JO+ + + -
+ + + + +
1- + + + _ —
( Z + + + +1 +
Q ��+ + + N-
+ + + + +
rn o - 1 50
/
+ + +
+ + + +
+ +
+ `+
(— O+ + +
+_ 2-10 +
OQ + + +
r
EXISTING BUILDING
NOT IN SCOPE OF
WORK
(N) RED S 16° 16'00"E 114.00'
CONCRETE PAVER
4 4
(N) CONCRETE P.,/\\/ NG
•
0 0
(N) 36" META
DOOR
(N) METAL FENCE
(E) PEDESTRIAN
SIGN
(E) STOP SIGN
(N) UNIT 'A 125
AMP ELECT. PANEL
//A
,ai-li A Ni li- i �. r-li-
4.','1_y-'�1�r .i1r�y—'y-'��, a ,��i1'1_yrri
t1Fril‘ :4II.
,
rl
jTr
rl1
1 11!i..1i 'rti-1ii''''111%'''1'1�iT1'11!1�!�11-
�-� .r1
_i11 .11 .11 = .11 111 111-N 1 111 .11 1
!' ��!ir-1ii!ii j:ilriT h
1 .11-111�. !!: .1'�1''-ii'1 R.i .r.'
_A''';''�1: ;":.!1� ;1' ;1';1' 1` --11
1- 1
1- 1 i 11-11'
iAr P' J'r .!i I;' I'.J
.i_'_11.�' '1--1'_.. .P ''11-11
1111,i'i1'119-1ii _111P1''=�i-''�!!i'11'1
1 'i -4-1i - .-1i-1i ' 1"A
��14,4'1.i. __-___i'_'0._.
1 -1i .1 1 M.
=m1!11
UNIT A
LIVING AREA: 1 682 SF.
GARAGE: 42I SF.
+ + 4
+ + + + + +
+ + + + + ±
+
-t-N) VtIdYL + + + t
+ + DEOR FIVE-fCRE-N I + +
I I I I I I
41 AC
1 1 1 1
+ + + + + + + + +
+ + + +
+ + + 4° +
+ + + 1, +
+ + +
+ J
SIDEWALK
+ + + +
+ + +
+ + + +
+ + +
+ +�
(N) 36" META
DOOR
a
O
0 co
A
(N) UNIT '5' 125
AMP ELECT. PANEL
UNIT B
LIVING AREA: 1 886 SF.
GARAGE: 4 17 SF.
4T
AC
+
+ + -+ +
+891+01 +
1 1 1 1
+ + + + +
+ +
Q + + +
4T
AC
+ +
+ + I1+ + - N) 36" METAL
+
+ + + + + DOOR+ -Th
+ + + + + + +
S 16° 16'00"E 114.00'
—(E) TRANSFORMER
(E) 8FT BLOCK
WALL TO REMAIN
2% a
a a a
(N) GUEST PARKING a
(N) UNIT 'C' 125
UNIT C
LIVING AREA: 1 744 SF.
GARAGE: 42I SF.
a
+ + + +
+ + +
a + + + +
4\ +
/
/
/
/
/
EXISTING BUILDING
NOT IN SCOPE OF
WORK
+ + + + 1- +10l-bu +
1 - 1 1 1 1` 1 1 1 A
+,, + + + + + + +
+ f + + + + +
+ + + + + +° + +
°. + 4 + + + + II+ +
+ + + + + + +
t 6 +
(N) METAL FENCE
4 (41!.- 0
LAWRENCE ST.
SITE PLAN
SCALE: 1/8" = I '-0"
A3
REVISION
DATE
0 •0
Q
0 Q N
UQ65
--) U
z u� Q
`` J • 1-
a_ z
W
U
z 0 <
STREET ADDRESS
0 803 W LA JOLLA ST.
5 m
PLACENTIA, CA 92870
if
WANG'S 3 -UNIT
CONDO - PLACENTIA
DRAWN BY:
STEVEN Z. WANG
DATE:
09. 18.2023
TITLE:
PROPOSED SITE FLAN
A-2.0
TYPE
(SEQUENCE
FILE NAME:
N
TC(198.70)
(198.37) FL(198.21)
LAWRENCE
TC(198.73)
FL(1 98.211
(198 80) (198 78)
(199.10)
U TEL
(199.99) °
7' H C FENCE
ON TOP OF 2' H CBW
\\\\\\\1\ ,
\\\EX. HODS
199.12
199.18
TC(198.67)
/FL(198 18)
(198 77)
N16°52'20"W 89.00'
FL
199.1-2 m
m m Im
\ ] m m m m
m m m m
h" m m m
m m 199.88
199:74)/- FG
.4
�
199:79 m m
Om m m
O1 m m
mm
N- 'm5%
'1994
200.13) m
„FLm
m m m
m m
(200.43) 199.5Q m
200.43
FL
PRECISE GRADING PLAN
SCALE 1"=10'
a •.5m2m'mmm21�0�m" 4
m2
FSm 4'Nm41 mE ° o ( 99 . 2 )` \lF 99 .4d° 2mWmm
F
•ENm
Cm
m€
m,mm
/m
mmmm m m mmmmmmmm m m v p mmmmm m m mm
mm
mm m 4 4
mm m m m m n m 4 mm m TmmC° , v;(10,5 -J%
m m
m m ,(199Z4).m m®mrv2 mmJo mmm -LANDFiCAPEm
4\12" 201.05,
DF FS
FF =201'55
PAD = 200.63
(199.47)
SI
\200.18
FG
GFF = 201.05
200.38
m m /FG 200.72
m 4! .V FS
4 (198.97)
m v
m m ° ° v o 10
mmm 11-449
.35) 16°52' 0" W
201.88 TC"
200.55 FL
° 1
J
w
H
(200.34)
m
m m
m m
m�
m c
m m L
199.88
m T rGN\
12 /
DF
1 TC(198
FL(198.
MEET
98.67)
(198 74) (19867) {19871)
(198.73) \ 0198.73)
199.FS34 98. 72) -89--:0
TC(198.57)
// FL(198.05)
1 U
GFF=201.05
(199.10)
GARAGE
(199.14)
\\\\V
/' / /m
/ /� °/ �m T m m
/54/N
200.05,%/m//m
�FS\7 //�
0m
(199.
m
U
(198 68)
(198.69)
(198.74)
TC(198.62)
FL(108.08)
(198.62)
^^N28°07'40'
C�o
o
LF SCA''
4 201.05/
FS
FF=201.55
PAG = c iat
(199.11
/m 1/99'$y5)
/ m m
12"
DF (199.
G/
m m
m m m
m
m m m
8.56)
198.65)
5.36'
ti
m m
98.44)
FF = 201.55
PAD = 200.63
200.80 \\
)FS 1 ) EX. HOL 5E 200.30 ' I
I. GFF=2•s� a (� 99.14 FS
�i�i�i�i iiiVMS
� i#i$i$i�tit4
�v1�i�i�i�i�,i
y
iiv,�� \�
*44*.#4**
,i i',*4 `#4i�'• w)�1x.35)CONG
iji�i�r�i�� ��i ►ij ' \200.30
200.27
4t#A$t#A$VVA
����� ij���►jo�i�i /FS
svi
ys#*
�•
jij4#S#
SSPS#ijS•vs,t•v tv-ijijijppAes- it p
201.05
FS
.4'0)/ m
199 00 FG
20" DF 9$.35)
./4/'
m / /
TC(198.45)
FL(197.95)
(197.90)
(197.84)
8.40 ST. SIGN
(198.53)
(198.32)(198.45)
(1 •:
(19
.41)
.27)
1 (198.24)
0 OSI
g o (198.3
ti
Z
TiP(198.37)
' (197.83)
F
TC(198.27)
FL(197.78)
(197.90)
ISON
23)
C(198.22)
FL(197.71)
(p
GARAG o
199.34) c` j'
(200.00) \- N16°52'20"W 114.00'
7'HCB
\\\\\\\\\\\\\\\ \\\\\\\\\\
HOUSE
F
199.29) E.1
°o
199.41)
DF
v
C p
F ` [Ni=.70m
m m m i$m
mmmm m
(1
200.21 T
199.87 FL
(198.92)
199.30 TC
198.97 FL
(199.52)
U
1 (198.60)
U
(198.96)
D/W
(19'
(198.72)
FS
(19
(19
(198.14)
TC(198.16)
FL(197.63)
7.61)
7.57)
TC(198.09)
FL(197.58)
197.73)
TC(198.09)
FL(197.54)
co4
4, LA JOLLA STREET
,-197.57)
REVISION
DATE
O0
o
z n co
0 QU <
N
--) U
z y_71
Q •
0_z
W
(NoU
z 0<
STREET ADDRESS
z
803 W LA JOLLA ST.
PLACENTIA, CA 92870
5 if
w WANG'S 3 -UNIT
O
o_
DRAWN BY:
CONDO - PLACENTIA
STEVEN Z. WANG
DATE:
09. 18.2023
z TITLE:
< GRADING PLAN
A-3 .0
TYPE
(SEQUENCE
FILE NAME:
TC(198.70) TC(198.73)
FL(198.21)_ _ FLII98.21L
(19880) (198.78)
(1-99.1=4}
Fu TEL
... E
CBW
LAWRENCE STREET
m
N 1E1'5220"
ro_As),a4,
•
19979)
triN
r
▪ ;199:74)
w
co 3
"199.40 )
,
(200.43)
1 u94,11_,
(260,35)
4 ,.
1 TC(198.67)
FL(1.98_-38) -
•
(198 77).
N16°5220"W 89.00'
▪ . b s
T •
199.'62).
(199.47)
'LAN D 1CAP
o❑
99.42)
b
TC(198
.F1..(1 98,
SE -5
0 3
fi', I'W FENCE
•
(109.02)
.20)
V98.67)
I
(148.4)
TC(198,57L
--FL(198.-05)-
U
Y (19867)(..i .82 )
(
198.73}
- -- _ (198.72 )$9.aar
.7,-1271
ofi �.-
(199..39)
4. k
'(199.06)
(198.97)
(199.10)
(199 14
a?a) '
tititittsi
l
itsestei
ifvt#44"#44% 4-074.0
#444"
44s
sAivpik
s
r•
(19.8_668)
TC(198:62)
--FL(198
`-ST.=S1G N
1098.62)
(198.69)
(198.74)
(19ff:-85)
`19897)
LAP DSCAP.=
(199.14) (199.111
EX. HOL SE
10)•.
(198.56)
(198.65)
N28°0740"W 35.36'
/17
<r.7`1,
■
-5
• (198.52)
�V I
(19® 24)..
• / n.
(199.0
LAN DSC
(199.1
IG/Mi
(19
(201.55)
LANDSCAPE
s ,
�9�,:
N 16052'20" W
IL"
(200.34)
EROSION CONTROL PLAN
SCALE 1"-1 0'
V
7'HCBW
SE -5
(200.00)
7 co
co
TC(198.45)
FL(197.95)
(197.90)
a.
CCI
rn
(197.84 )
(198.40)
ST. SIGN
(198,45)
(198,53)
(198_32)
U
(198.41)
199.35)
9,8:44)
(199.30)
-
!:(:n tous }
(199.29)
(199.34)
CONC
(199.41)
1IAr. •nl
-37) .,. vC ass." j V ..
P.
o -t
N16°52'20"W 114,00'
' i CBW
EX. HOUSE
CIS
(198,40).]
;199.00)
c9
crl
TC(198.37)
FL(197.83)
TC(198.27)
FL(197. 8)
▪ (197.90)
(196-27)
EDISON
(198123)i
1 (198.24)
b
E '198 3(g
() _l
6'iCFENCE �_.
z
FC(198.22)
FL(197.71)
SE -5
30'
30'
TC(198.16)
FL(197.63)
U
(199,52) j (198,96)
(1 97.57)
(198.14) •
1t
'(198.14)
TC(198.09)
FL(197.58)
197.73)
TC(198.09)
FL(197.54)
1-
w
CI)
4_ LA JOLLA STREET
SMH
(197.76)
_(197.57)
REVISION
z
0 J
5 DATE
O ■0
o z (s-)�
O Q cv
UQ65
Z--) U
Z u� Q
a_ z
W
MU
z 0 <
Q
STREET ADDRESS
803 W LA JOLLA ST.
PLACENTIA, CA 92870
if
w WANG'S 3 -UNIT
CONDO - PLACENTIA
0 DRAWN BY:
STEVEN Z. WANG
DATE:
09. 18.2023
TITLE:
EROSION CONTROL PLAN
A-4.0
TYPE
(SEQUENCE
FILE NAME:
IG VilOr Vi
7 < 1
1,VM]OPG
A
25 A
D<ISTING BUILDING
NOT IN SCOPE OF
WORK
7/
GARAGE
4 5 16° 1000"E I 14.00'
�,.ftal14'la ...,,...If'a 1144 4414.4 14„1.,,..„„14,,11„1414„..„„4114..„,. , $$ 11 14 11 11 11 14 11 41 11 1.11 11 11 19 9, 1,111a11...• 4.1 14 ,,. , UNIT A
▪ (N) GIJESr FARKJNG
"co4
.0c
c
00 00
TYP.
UNIT B
11 GARAGE
ID
GARAGE
UNIT C
TYP.
4 21-8s1
■
0 T61 ///
11 „Y.
U1-0„
„
� d
AC
A
LANDSCAPE PLAN �N
1 /8"= 1 '-On 11
0 4, 8'
TYP
SIDEWALK
LAWRENCE ST.
7 TYP
41 TYP
88888888888888888888888818888818881888888888
X X X X XX X% X% X% X X% X% X X X%
X X%%% 8888888188888 X 1[ X 1C X X 1[ X X X X
FJfI51ING BUILDING
NOT IN SCOPE OF won.
%
REVISION
z
0 J
5 DATE
O .0
Q
z (s-)�
O Q cv
UQ65
�z0<
--) U
Z u1
cL z
W
U
z 0 <
< co
D_
STREET ADDRESS
803 W LA JOLLA ST.
PLACENTIA, CA 92870
if
w WANG'S 3 -UNIT
CONDO - PLACENTIA
0 DRAWN BY:
STEVEN Z. WANG
DATE:
09. 18.2023
TITLE:
LANDSCAPING PLAN
A-5.0
TYPE
(SEQUENCE
FILE NAME:
LEGEND:
1 1 (N) 2x STUD WALL
(N) DOUBLE I -HR FIRE RATED STUD
WALL / SEPARATION WALLS BETWEEN
DIFFERENT UNITS
SWINGING DOORS
1. .., WINDOWS
11 DOUBLE SLIDING DOORS
C
•
/ 41-I"
-
i
Eo 14
20'-8"
UNIT A
2 -CAR GARAGE
5'- 1 0"
UNIT A
LAUNDRY ROOM
51-411 5'- I "
511 RECYCLE
BIN BIN
UNIT A
LIVING AREA
28'-7"
UNIT A
DINNING AREA
cs%
2'-I 1"
KITCHEN ISLAND
m
0 UNIT A
KITCHEN
00 �e 3'-4"
0 0
'/////-%
- ;r
UN A / UNI B
Oz) PI. DER %POWD
ROOM 2 ROOM --�
I- I II
Ln
0 89'-011
47'-8"20'-8"
/
B
10'-I I" 1
m
0 RF
UNIT B
KITCHEN
`
KITCHEN ISLAND
LIVING AREA 494 SF
NATURAL LIGhT= 10% x 194 SF = 49.4 SF
WINDOWS: 4'x6' = 24 SF'
3.5'x8' = 28 5F
TOTAL NATURAL LIGhT PR:DVIDED = 24 +
28 = 52SF>49.4SF
UNIT B
DINNING AREA
i. i.� i/I—V ii
13 •
ii iii
13 UNIT B
FRONT DOOR
51-8"
0 18'-I I"
UNIT B
LIVING AREA
n /Li
1r
20'-41
UNIT B
2 -CAR GARAGE
UNIT C
2 -CAR GARAGE
// 174 51-3" )( 5'-2"
) �l RA511 RECYCLE
UP h BIN BIN
3'-4" I -
IJII/
1 _!
O
cv7
Co
N /4
UNIT C
jLIVING AREA
y
20'-4"
4'-8" 5'-4" ih 10'-4"
.///'7////1�/7i,
IT
1 1-11 � UF) TAN -1 RECYCLE / O ODER
1 6 m �. I� I RO• .�
—i_ /
101-9"
V/ // // :
LANDING
77 — 77
1 31-0"de 51-4" �� 10'- I 1"
B
UNIT B
LAUNDRY ROOM
10'-0"
0 UNIT C
FRONT DOOR
3L—G" 51-811
OI
LANDING -
7T1
17-.
24-5"
k51M' 0"
UNIT C
_ LAUNDRY ROOM
c9
co
20'-4"
KITCHEN ISLAND
UNIT C
DINNING AREA
15'-2"
de
ee
4'- I "
/
RF
ID
:3'-4" O
DW
cn
LNIT C
KITCHEN
0 0
10'-0" G'-3" / 3'-8" / 5'-4" / 15'-6"
70'-1"
FKOFOSED 1ST FLOOR FLAN
SCALE: 1/4" = I '-0"
14 1
•
A
0 •
•
C
REVISION DATE
•0
Q
0 Q cv
Q
z0<
U
C)) :!;
D— z
W
U COU
z 0 <
Q
STREET ADDRESS
z
0 803 W LA JOLLA ST.
PLACENTIA, CA 92870
if
WANG'S 3 -UNIT
CONDO - PLACENTIA
0 DRAWN BY:
STEVEN Z. WANG
DATE:
09. 18.2023
TITLE:
PROPOSED 1ST
FLOOR PLAN
A-6.0
TYPE
(SEQUENCE
FILE NAME:
LEGEND:
1 1 (N) 2x STUD WALL
(N) DOUBLE 1 -HR FIRE RATED STUD
WALL / SEPARATION WALLS BETWEEN
DIFFERENT UNITS
SWINGING DOORS
i r"""". WINDOWS
11 DOUBLE SLIDING DOORS
A
C
12'-0"
16 . ,
i
0 24'-0"
12'-0"
UNIT A UNIT A -
BEDROOM 2 BEDROOM 1
7-4" 4'-6"
0 CLOSET 2
4'-6"
C()
0 4-5"
UNIT A
HALLWAY
DO\VN
20'-3"
0 i
O
CLOSET 1 t /
N
1 UNIT A N
MASTER BEDROOM `I? 9 -0
Ln / *%//////////////�i
9'-0"
/
WALK-IN
_ CLOSET
/
89'-0"
41'-0" 24'-0"
i
B — , 12'-0"
i
/
i
i
i
5'-5" 15'-2" 1 �� 13'-9" 7'-0"
WALK-IN
CLOSET
,
aN
/(//////////
x[
UNIT A C OI
MASTER BATH J
7'- 1 1 "
13 r
„/
0 15 15 15 15
15'-2"
UNIT B
MASTER BEDROOM
UNIT B
MASTER BATH
171-7"
Y/ // // " //
l
N
1.'1' /, /, /, // 1
5'-I 1"
v ,1 /, // // -A',
o
N
•
•
4—8"x4'—G"
LANDING
131-9"
UNIT B
BEDROOM 1
DOWN
// ) N // // // // // .I
ce, / //
0'4"
O UNIT C
BATHROOM
c9
n UNIT B
ATHROOM 1
7'-4" II ° �1
0 ��
U1 �n JNIT B
CLOSET N BATHROOM
1�
0 co
N
UNIT B
BEDROOM 2
1 5'-G"
4'-1 1 " 5'-8" 7'-0" 13'-9" 9'-10"
B
70'-1"
121-0"
UNIT C UNIT C
BEDROOM 2 BEDROOM 1
7'-4" 4'-G"
9 Fr,
•
•
C()
•
•
i
5'-2"
WALK -I N
CI nSET
//////7'///7/
y
PROPOSED 2ND ELOOK FLAN
SCALE: 1/4" = l'-0"
4-5"
0 - 0
5'-8"
10-0"
DOWN
1 1 5'-2"
ee
ee
ee
/
/
/
/
0/
/0
N / In
N / N
t
4' 2" 14
'f '1-
/ O
/
i
'
0 -4-
UNIT C
MASTER BEDROOM
UNIT C
MASTER BATH
>0( n
5'-4"
.
•
62,
,
•
A
C
REVISION DATE
STREET ADDRESS
z
0 803 W LA JOLLA ST.
PLACENTIA, CA 92870
if
WANG'S 3 -UNIT
CONDO - PLACENTIA
DRAWN BY:
STEVEN Z. WANG
DATE:
09. 18.2023
z TITLE:
IST FLOOR PLAN
0 A-7.0
TYPE
(SEQUENCE
FILE NAME:
•
•
r
0 0
27-0"
5:12 5:12
a a
24'-5"
8' -1 I"
L-
4:12
4: 1 2
92'-0"
38'-0" 27'-0"
1 I '-5" 241-10"
7 1 '-0"
5:12 5:12
No -
4:12
4: 1 2
Paw -
1 1'-8" / 1 3'- I I"
/
PROPOSED ROOF( NG FLAN
SCALE: 1/4" = 11-0"
(1\
KA5
REVISION DATE
O H: 0
Q
O Q cv
Q
z0<
zW.‹CQ
c� i • I ---
D-
W
U CU
z 0 <
STREET ADDRESS
z
0 803 W LA JOLLA ST.
PLACENTIA, CA 92570
if
WANG'S 3 -UNIT
CONDO - PLACENTIA
0 0
0 DRAWN BY:
STEVEN Z. WANG
DATE:
09. 18.2023
TITLE:
PROPOSED ROOF PLAN
A-8.0
TYPE
(SEQUENCE
FILE NAME:
15 0
WINDOWS
SIZE (WXN) SLIDER
24" X 42" XO
32" X 24" XO
18" X 12" XO
32"X42" XO
48"X42" XO
48" X 48" XO
32" X 84"
72" X 48" XO
9G" X 42" XOX
0 0
0 0
SCHEDULE
MATERIAL
VINYL
VINYL
VINYL
VINYL
VINYL
VINYL
VINYL
VINYL
VINYL
0 0
0 0
a b
GLASS TYPE TYPE
CLR/LE3
CLR/LE3
CLR/LE3
CLR/LE3
CLR/LE3 a
CLR/LE3
CLR/LE3
CLR/LE3
CLR/LE3
NOTE
b TEMPERED SAFETY GLAZED
a TEMPERED SAFETY GLAZED
TEMPERED SAFETY GLAZED
b TEMPERED SAFETY GLAZED
TEMPERED SAFETY GLAZED /
RESCUE OPENING: 7 SF.
0 0
a TEMPERED SAFETY GLAZED
c TEMPERED SAFETY GLAZED
a TEMPERED SAFETY GLAZED
TEMPERED SAFETY GLAZED
0 0
c e
WINDOWS SCHEDULE
NOTE:
I . ALL GLASS GLAZING IN DOOR MUST BE TEMPERED.
2. SHOWER GLASS DOOR MUST BE TEMPERED.
3.5110WER DOORS SHALL SWING OUT. NET AREA OF SHOWER RECEPTOR SHALL BE NOT LESS THAN I ,024 SQ.IN. OF FLOOR AREA, AND ENCOMPASS 30 -IN.
DIAMETER CIRCLE. (PC 408.6)
4. U -FACTOR = 0.30, SHGC = 0.23 FOR DOOR AND WINDOW GLAZING (NEW)
5. HOUSE WILL BE CONNECTED TO PUBLIC SEWER
6. SILL HEIGHT: MAX 44"
7. EFFECTIVE JAN I , 2020 GAS WATER HEATER SHALL HAVE ALL THE FOLLOWING AS PER 20 19 CALIFORNIA ENERGY CODE 150.0(n) I :
A. A DEDICATED 1 25V, 20 -AMP ELECTRICAL RECEPTACLE THAT IS CONNECTED TO THE ELECTRICAL PANEL WITH A 1 20/240 -VOLT 3 CONDUCTOR, I 0 AWG COPPER BRANCH CIRCUIT, WITHIN 3 FEET FROM THE WATER HEATER AND ACCESSIBLE WITH NO OBSTRUCTIONS. BOTH ENDS OF THE UNUSED CONDUCTOR SHALL BE LABELED WITH THE WORD "SPARE" AND ELECTRICALLY
ISOLATED AND MUST HAVE A RESERVED SINGLE -POLE CIRCUIT BREAKER SPACE ADJACENT TO HIS CIRCUIT BREAKER LABELED "FUTURE 240V USE" B. A CATEGORY III OR IV VENT, OR A TYPE B VENT WITH STRAIGHT PIPE BETWEEN OUTSIDE AND WATER HEATER.
C. A CONDENSATE DRAIN NO MORE THAN 2 INCHES HIGHER THAN THE BASE ON WATER HEATER FOR NATURAL DRAINING.
D. A GAS SUPPLY LINE WITH CAPACITY OF AT LEAST 200,000 BTU/HR.
B.EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL BE CLEAR OF ANY
OBSTRUCTION AND OPERATIONAL FROM THE INSIDE OF THE ROOM WITHOUT THE USE OF KEYS, TOOLS OR SPECIAL KNOWLEDGE.
9. DOORS AND WINDOWS SHALL BE SAFETY GLAZING PER SECTION 2406 SAFETY GLAZING.
0 SIZE (WXN)
GO" X91"
30" X 80"
32" X 80"
GO" X 80"
48" X 80"
1 92" X 84"
GO" X 80"
32" X 80"
DOOR SCHEDULE
POSITION
EXTERIOR
INTERIOR
INTERIOR
INTERIOR
INTERIOR
EXTERIOR
INTERIOR
INTERIOR
MATERIAL
WOOD
WOOD
WOOD
TYPE
D
A
A
LOCATION
FRONT DOOR
METAL/ GLASS B CLOSET SLIDING DOOR
WOOD C BI -FOLDED DOOR
WOOD
WOOD
DOORS SCHEDULE
GARAGE DOOR
CLOSET DOUBLE
SWING DOOR
A GARAGE TO
RESIDENCE DOOR
NOTE
SHALL BE I -3/8"
SOLID DOOR WITH
SELF -CLOSURE.
(2
A-5.0
o �
A
n
n
n
D
n
0 0 0
> o
0 0
14 F
B
00 E
REVISION
DATE
. O
Q
z oz)
< (3U
Z u� fiC UQ
06 <z
W
(Y)U
z 0
STREET ADDRESS
0 803 W LA JOLLA ST.
PLACENTIA, CA 92870
if
WANG'S 3 -UNIT
CONDO - PLACENTIA
DRAWN BY:
STEVEN Z. WANG
DATE:
09. 18.2023
z TITLE:
WINDOWS $ DOORS
cZ SCHEDULE
A-9.0
TYPE
(SEQUENCE
FILE NAME:
2 3
5 6
TYP . TYP. TYP. TYP. TYP. TYP.
I I I I I I I I I I I I I I 1 1 1 Y I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 11.1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 d 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 IIIIIIIIIIIIIIII lllllllllllllllllllllllll 111111111111111111111111,�IIIIIIIIIIIIIIIIIIIIIIIIII� I I 11Jii �� 1 1 1 1 1 1121 1 1 1 1 1 1 1 1(N I I I I I 1► 1 1 1 1 1 1 I I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1( 11 I, 1111 111111 11111111111 y� 11111 1111111111111111 1111111111111111111 1111 1111111111111111111111 1 111 IIIIIIII Jai �� 11511111 1111 I I I 1111 II 1111 1111
111111 J��'FIIIIIIIIIIIIIIIIIIIIIIII111111IIIIIIIIIIIIIIIIIIIIIIIIIIIIr111111II IIIIJyi ���IIIII11111111111111111�1111111111111111111111111111111��II1II I \ 1\ 11111111111111111111111111111111111I�I1111111111111111111111111111111111111111111111111111111111111111111111111� '1 1 1 1 1 1 1 1 1 1 y �l 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I I I I I I I I) '/\tel 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 (I I I 1>1...--l->"' �� 1 1 1 1 1 1 1 1 1 1 1 1 1 1
I I I I . 1 1 1 1 1 1 1 1 1 1 1
1),..1„..j...-1_-_-":----
1 I 1 1 1 IJJi -111 1 I I I 11111
)�'J y-/ \111111111
u
u u u
0 0
�.�.�.�.�.I�.o�.o�.o�.o�.o�.o�.o�.o
I I I I I I I I I I I I
elpOolp_olp0o00.1.0e00e00e00e00e00 -e0,e. elp
%moo /moo _ /moo _ /moo_ n nn
5 TYP.
6 TYP.
TYP.
u
/,
0 0
/, 0
TIP. TYP.
TYP.
0 0
0 TYP.
TYP.
TYP.
0 0
0 I Tr
1C -
i ,-".o .o ,-".o .12 .12 1 1
.2 .2 /�� _ /�� _ /�� _ /1� _ /-1(Z_
TYP.
5 MT. NORTH VIEW (SIDE)
SCALE: 1/4" = l'-0"
TYP.
TYP. TYP.
( 1 1 1 1 1
„te ll1 I1II1I1I1I1I1I1I111111III1I1III1I1I1I1I1II1I1I11 I1I1I1I1I1 IIIIIII1I1I1I1I1IIIII1I1I1I (IIIIIIIIII1I1 1 -I1I1I1I1I1I1I1II1I1I1I1I1I1I1I1I1I1I1I1I1II1I1I1II1I11111 m IIIIIIII I 1 I( y I I I I I 1 ivI I (I I I I I I I I 1 1 I I I I I I I Irl I I I I I I/ \1 1 1 1 1 1 1 I I I I I I I I I I I I I M _� 1111111111111. 11111111111111111111111111111111111 1111111111111111111 111111111111111111111111111111111111111111111111111111I IIIIIIIIIIII II N11111
IIIIIIIII IIIIIIIIIII IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII II ��IIIIIIIIIIIIIIIIIIIlllllllllllllllllllllll 1111111 IIIIIIIIIIIIIIIII''ll IIIIIIIIIIIIIIIIIIIIIIIII IIIIIIIIIIIIIII11"11 IIIIIIIIII 1 1 1 1 1 1J,,, I I1I 1 I II II II II II IUI IIII IJ- -'-' 1 1 ( 1I 1 I 1 I 1 I 1 I 1 I 1 I 1 I 1 1 1 ,i1111111111111111111111111 11 111111NL I 5.63 S.F.
INTAKE VENTS:
PROVIDE HALF -ROUND DORMER VENT x 9PC =
900 S.I. / 144 = 6.25 S.F. > 5.63 S.F.
n
111
111
n
n
111
111
TYP.
WEST VIEW (SIDE)
SCALE: 1/4" = I '-0"
0 0
0 0
NOTE:
1. NEW EXTERIOR WALLS NEED 2 LAYERS OF GRADE D PAPER
UNDER STUCCO WHEN OVER WOOD SHEATHING. (CRC 703.7.3)
2. WHERE A WINDOW IS PROVIDED AS THE EMERGENCY ESCAPE
AND RESCUE OPENING, IT SHALL HAVE THE BOTTOM OF THE
CLEAR OPENING NOT GREATER THAN 44 INCHES MEASURED
FROM THE FLOOR (I 030.3)
STRUCTURE hEIGFIT
TOP SFIEAThING
2ND FLOOR CEILING
UDR.
1,
1 1••`
I ST CEILING hEIGFIT
hDR.
11 •
•
STRUCTURE YIEIGHT
TOP SUEATUING
2ND FLOOR CEILING
UDR.
♦`
IST CEILING FIEGFIT
4�
0 cP
•
•
N
N
•
•
N
N
REVISION DATE
STREET ADDRESS
z
0 803 W LA JOLLA ST.
PLACENTIA, CA 92870
if
WANG'S 3 -UNIT
CONDO - PLACENTIA
DRAWN BY:
STEVEN Z. WANG
DATE:
09. 18.2023
TITLE:
ELEVATION VIEWS I
A- I 0
TYPE
(SEQUENCE
FILE NAME:
NOTE: NEW EXTERIOR WALLS NEED 2 LAYERS OF GRADE D PAPER UNDER STUCCO WHEN OVER WOOD SHEAThING. (CRC 703.7.3)
2 5
6 EXTERIOR FINISH SCHEDULE
MATERIAL
ROOF CLAY TILE
EXTERIOR STUCCO
24"x 1 2" GALVANIZED STEEL
HALF -ROUND DORMER VENT
EXTERIOR BOARD AND
BATTEN
EXTERIOR PRE -CAST STONE
VENEER
DECK COATING
TYP.
TYP.
TYP.
I
TYP.
TYP.
I I I I I I I I I 1 1 1 I I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I 1 I 1 1 1 1 1 11111 I 1
IIIIIIIIIIIII IIIIIIIIIIIIIIIIIII IIIIIIIIt►►►tllllttlll1111 ItIT 11111111111( 11111111111111111111111111111111111111111 Xflllllll 1� 1111111111111111111111
11111111IIIItII1111111111111111111 1111111111111
II IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII I11 11 r IIIIIIIIIIII1111 1 111111IIIIIIIIIIIIIIIIIIIIIIIIIII►►IIIIIIIIIIII► IIIIIIIIIIIIIIIIIIIIIIII !IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIiiIIJXftlllllllllllllllllllll►tllll� I 1I1111111IIIII1111111111111111I111'111111llll1111'1111111111111111111111111111111111111111111111 1111111111111111111111111111111111111 IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIJ�I'I111111111111111111111111111111111111111� 0 7'P
L_TJ
1 17
C ] Q
C ] E
1 /� - I I 1 /�
9L4Ld94WWW 9'444'9 44LdLd 9WWW 9WWL4'4WWW 9WWW
0 0
0 0
L -TJ
C
44404 0 0 0 0 400040000000044;
0 0;4040404wAA �A�A�A�A�A�A�A�A PA�A'�A101111�
• /��
TYP.
I I I I1 I I I I Jyi
I I I I I I I
1 1 1 1 JJ!�
0 TYP.
0 0
0 TYP.
u
0 •
TYP.
TYP. TYP. TYP.
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 ���IIIIIIII �IIIIJ�I111111.1IIIIIIIIIIII IIIIIIII
1 1 1 1 1 1 lI" I I I I l'-11 1 1 1 1 1 1 I I I I I I I I I I I II11IIIIIIIIIIIIIIIIIIIIIIIII IIIIIIII
1111IIIIIIIIIIIIIIIIIIIIIIIIIIII
IIIIII1 I 1 II1 I 1 I 1 IIIIIIIIIII►►►IIIIIIII
1 1 1 1 1 1 I ISI 1 1 1 1 1 1 1
1111111111111111111111111111
IIIIIIIIIIIIIIIIIIIIIIII11
I 4 I /
' TH.
0 0 _
0 0
0 ASOSOSOSOSOSOSOJOSOSOJOSOSOSOSOJOSOSOSOSOSOSOSOSO
OAOAOAOAOP•OPAOAOPAOPAOAOAOAOAOAOAOAOAOAOP OAOAOAOAOAOPt _ /--No / �o /--No / �o _ �o _ .�� /moo �o \o \o \o \o \o \o \o \o \o \o \o �o
FINISH COLOR MANUFACTURE NOTE
PRE -CAST OLD SEDONA BLEND REDLAND CLAY TILE ICC -ES ESR -4395
SAND FINISH TOFFEE CRUNCH LAHABRA
GIBRALTAR BUILDING
PRE -CAST SILVER
PRODUCTS
FIBER CEMENT VERTICAL
PRE -CAST GREEN JAMES HARDIE SIDING OR APPROVED EQUAL
PRE -CAST VOLTERRA CORONADO ITALIAN VILLA STYLE OR
STONE PRODUCTS APPROVED EQUAL
PRE -CAST DEX-O-TEX ICC -ES ESR -5036
TYP.
TYP.
STRUCTURE HEIGHT
TOP SHEATHING
2ND FLOOR CEILING
0 I
N
N
15T CEILING HEIGHT •
•
HDR.
NORTH VIEW (SIDE)
SCALE: 1/4" = I '-0"
STRUCTURE HEIGHT
2 REVISION DATE
o • 0
o z n�
O Q N
U
1___z0<
TOP SHEATHING %
2ND FLOOR CEILING L. W
./ I I- 'DR. N` D / \ `
I Q .<(`
oQ- z
n W
m 0 MU
N z 0<
I ST CEILING HEIGHT
HDR.
WEST VIEW (SIDE)
SCALE: I /4" = 1 '-0"
STREET ADDRESS
0 803 W LA JOLLA ST.
PLACENTIA, CA 92570
m
4� if
�A 5� w WANG'S 3 -UNIT
CONDO - PLACENTIA
0 DRAWN BY:
STEVEN Z. WANG
DATE:
09. 18.2023
TITLE:
ELEVATION VIEWS 2
AHI
TYPE
(SEQUENCE
FILE NAME:
co
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 J/
111111111111IIII�
11111111111111111 )�
111111
R-21 i
2x RIDGE BOARD
----.l 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I I I I I I I I I I I I I I 1 1 1 1 I I I I I I I I I I I I 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1/1 1 1 1 1 1 1 1 1 1 III 11_ 111111111..11111111111111111111111111111111.x.111111111111111111111111111 • �`"� 111111111( �1111111111111111111111111111111( 111111111111111111111111111 L1,11111)II 11111111111111111111111111111111 1111111111111111111111111111111 -----1...--1----1-1111111 1111 I 1111 11111 IIIIIIIIIIIII IIII1111 '-----1..--1-111111111111111111111111111111111111111111111111111111111111111111 X1,1111 1111 lllllllll11711111111111111111111111111111117-11111 I 11111111111111111111111'1111111111 11111111111111111111111'1111I ------1-.....___ LII
--LIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII IIIrfI UNIT A
ATTIC SPACE
1/2" GYP. ON R-30
CEILING
X6 STUD
�E XTIOR NA}
V / 5/8" ;YP. /
1 -IR FIRE I;ATED
R-21 i
0 0
O
0 0 I J IT
2 -CAR GP RAC E
2x CEILING JOINTS
2X6 SUI
-EXTERIO WALL WALL =
1HRGYP.
NSFI E RAT
• ; I
NEW CONCRETE
FOOTING
SECTION VIEW B—B
SCALE: 1/4" = l'-0"
2x
O
CEILING JOINTS
1 '2"PROPR
( G .ASS MAT
R-19
UNIT A
2 -CAR GARAGE
0 R-21 J
2X6 TU,
EXTEF IOR WALL
W/ 5, '8" GYP.
1HR F RE RAT5 )
#
ETARY T DE X
GYP. PA 1EL
5/8" GYP. Oh
CEILING
NEW CONCRETE
FOOTING
0 0 0
�o �o /\o �o �o �o �o �o �o �o �o �o �o �o �o �o ,p/-
111111
1 111111)y
IIIIIH
fly
2x RIDGE BOARD
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
�IIIIIII111111111
l2xI R1 T t 1 1 1 1 1 1 I
I 1 1 1 1 1 1 1 1 1 I
111111111
L L 1 1 1 1 1 I
1 1 1I
UNIT A
ATTIC SPACE
2x CEILING LINTS
R-21
X6 STUD
�E KTERIOR NALL
SECTION VIEW A—A
SCALE: 1/4" = l'-0"
1 I I I I I I I I I I I I I I I I 1 I I I I I I I I I I I I I I I I I I I I I I I I I I I 111111111111111111111111111111111111111111
IIIIIIIIIIIIIIIIIIIIIIIIIIIII1IIIIIIIIIIIV
IIIIIIIIIIIIIIIIIIIIIIIIIIIIII IIIIIIII y-
11111111111111111 IIIIIIIIIIIIIIIIIIIII111111111111111111111111111111111 1'" y,
1111111 1 IIIIIIIIIIIIIII111111Jy-
1111111111111111111111111111JJ�
IIIIIIIIIIIIIIIIIIIIIIIIIIJyli__46
L_1
1 '-6"
L_1 u
L_1
L_1
2 A-9.0
R-21
1111VA
11y�
1/2" GYP. ON R-30
CEILING
2X6 STUD
EXTERIOR WALL
W/ 5/8" GYP. /
1HR FIRE RATED
XNN
NEW CONCRETE -'
FOOTING
- 2X6
EXTERIO
1N1HR 5 IRE
1014
U)
WALL
GYP. /
RATED
2x RIDGE BOARD
UNIT A
ATTIC SPACE
2x CEILING JOINTS
UNIT B
MASTER BEDROOM
2x RAFTER
/414/4
R-30
\�- WOOD STUD
WALL 2x4
16" O.C.
0 O
/.1
NEW CONCRETE -/
FOOTING
1 1 1 1 1 1 1 1 1 1
11111111
IIIII
\ UNIT B
MASTER BATHROOM
2X6 STUD �1�
EXTERIOR WALL
W/ 5/8" GYP. /)
1/2"PROPRIETARY TYPE X 1HR FIRE RATED
GLASS MAT GYP. PANELR-19
NOINNNNNUINCINN X
R-19 2x CEILING JOINTS 5/8' GYP. BOARD 2x CEILING JOIN -S 1 -HR FIRE RATED
R-21
UNIT B
LIVING AREA
4• . .
UP
NEW CONCRETE
FOOTING
R-21
2X6 STL4D
EXTER101 t WALL
W/ 5/8".GYP. /
1HR FIRE: RATED
- 5/8" GYP. ON
CEILING
R-19
R-30 - 1/2" GYP. ON
CEILING
O
0 TUD
EXTEF IOR WALL
W/ 5 /8" GYP. /
1HR f IRE RATED
(1 /2 'PROF'RIE1 ARY TYPE X
GLASS MAT C,YP. PANEL
UNIT C
2 -CAR GARAGE
2x CEILING JOINTS
R-21
2X6 STUD
EXTE IOR ' ALL R-21
W/ ` /8" GYP. -y
1HR "E RATED
-=-=-
Q
NEW CONCRETE <
FOOTING
co
REVISION
DATE
0 •O
Q
z oz)
O QN
H O <
U
Z uLI fiC UQ
06 <z
W
(U
z 0
Q 11__
STREET ADDRESS
z
0 803 W LA JOLLA ST.
PLACENTIA, CA 92570
f -
w WANG'S 3 -UNIT
CONDO - PLACENTIA
0 DRAWN BY:
STEVEN Z. WANG
DATE:
09. 18.2023
z TITLE:
< SECTION VIEWS
A- 1 2
TYPE
(SEQUENCE
FILE NAME:
R-21 J
R-21
1/2" GYP. ON R-30
CEILING
2X6 ST>J[
-EXTERIOR WALL
W/ 5/ GYP. /
1HR RE RATED
ATTIC SFACE
2x CEILING JOINTS
2X STUD WALL W/--"
5/8" GYP. ON EA,
SIDE / 1HR FIRE
RATED WALL
UNIT C
MASTER BEDROOM
1])1 N N/NNNNNN
0 0 R-19
0 0
\2X5 STUD
EXTERIOR WALL
W/ 5/8" GYP. /
Y I I,I1 DIE f11TEq
.,I
NEW CONCRETE
FOOTING
i� 0
UNIT C
DINNING AREA
_N
D
n
n
1i/i/4
R-30
0 UNIT 5
BEDROOM 2
1 /2"PROPRIETARY TYP = X
GLASS MAT GYP. PANE .
0 1i/i/4
R-30
2X STUD WALL W/
1/2" GYP. ON EA,
SIDE
UNIT 5
HALLWAY
NXNNNNNNflNNNN
5/8" GYP. ON 8 2x CEILING JOINTS R-19
CEILING
❑ II
D
NEW CONCRETE
FOOTING
IUNIT BC
-[ 2X STUD WALL W/ 2 CAR GARAGE
5/8" GYP. ON EA,
SIDE / 1HR FIRE
RATED WALL
SECTION VIEW C -C
SCALE: 1/4" = l'-0"
R-30
2X STUD WALL W/
1' GYP. ON EA,
UNIT B
MASTER BEDRI )OM
A -TIC 5P/E
1/2"PROPRIETARY TYPE X
GLASS MAT GYP. PANEL
NNNNNNN MN
2x CEILING JOINTS
2X STUD WALL W/
1/2" GYP. ON EA,
SIDE
UNIT 5
LIVING AREA
LW
R-19
n
n
NEW CONCRETE 2
FOOTING
2x CEILING JOINTS
2X STUD WALL W/
1/2" GYP. ON EA,
SIDE
WALK-IN
CLOSET
R-30
1/2" GYP. ON
CEILING
2X STUD WALL W/
5/8" GYP. ON EA,
SIDE / 1HR FIRE
RATED WALL / UNIT A
PLY WOOD
MASTER BEDROOM
2X6 STUD R-21
EXTERIOR WALLW
/ 5/8" GYP. /_}
1HR FIRE RATED
NNNNNWXN
5/8" GYP. ON
CEILING
UNIT A
KITCHEN
2X STUD WALL W/
5/8" GYP. ON EA,
SIDE / 1HR FIRE
RATED WALL
NNN,NNNNN]R-19 2x CEILING JOINTS
2X6 STUD
EXTERIOR WALLW
/ 5/8" GYP.
1HR FIRE RATED
UNIT A
DINING AREA
1. •
NEW CONCRETE
FOOTING
R-21
00 REVISION
DATE
O •O
Q
z nco
0 Q Cv
HzO<
U
Z uLI fiC UQ
06 -
z
W
(U
z 0 <
STREET ADDRESS
z
0 803 W LA JOLLA ST.
PLACENTIA, CA 92870
if
WANG'S 3 -UNIT
CONDO - PLACENTIA
0 DRAWN BY:
STEVEN Z. WANG
DATE:
09. 18.2023
z TITLE:
SECTION VIEWS
A- 1 3
TYPE
(SEQUENCE
FILE NAME:
mi\i i cu: UJ-71-LUZU
TYP.
COLOR: DUNN EDWAFRDS
RH4B- ASPEN GREEN
TYP.
ELDORADO STONE , RIVER ROCK
COLORADO COLOR
TYP.
NEW INSTALLATION OF ROOFING MATERIAL .
SAXONY' 900 SHAKE GARNET BLEND
ICC -ESR -1647 AND DARK BROWN, RED, GRAY
MULTICOLOR COLOR
i
i
TYP.
- MILGARD ULTRA FIBERGLASS WINDOW
TYP.
COLOR: DUNN EDWARDS
RH4B- ASPEN GREEN
il--10,41.e.:,..711111:17.1:411411:11".6705.1g•-moVilit.-,..1110, 11111111 IKKAIrial" OR
itgn:aripilliirdper-:41.41'4.,111114441.pilltiMis7.414124t04,11Miribte0., "Art* at" dirowelp4.4.$111111
• 1101,41800 5"1% 41INF
lil:;'
- INTERIOR FRAME COLOR _ HARMONY
- EXTERIOR FRAME COLOR : BLACK BEAN
- U -FACTOR 0.29
- SHGC 0.21
- LCE 3 GLASS
TYP.
NEWINSTALLATION OF ROOFING MATERIAL
SAXONY' 900 SHAKE GARNET BLEND]
ECC -ESR -1647 AND DARK BROWN, FED, GRAY
MULTICOLOR COLOR
TOTAL HEIGHT
TOP PLATE
HDR.
TYP.
HARDEPLANK , LAP SIDING r
HEATHERD MOSS
TOP PLATE
TOP SHEATHING
HDR.
TYP.
LA HABRA STUCCO
696 SOUTHERN MOSS
BASE 200
ti
NORTH ELEVATION - PROPOSED
SCALE: 1/4" = 1'-0'
TOTAL HEIGHT
TYP.
HARDIEPLANK , LAP SIDING
HEATHERD MOSS
TYP.
LA HABRA STUCCO
696 SOUTHERN MOSS
BASE 200
1 II1
■L
LJ
TYP.
ELDORADO STONE , RIVER ROCK
COLORADO COLOR
1 Offfn
Tir
. f i�re �r , aka
` /01111114lIkrn 01®r� a'=('
TYP.
- MILGARD ULTRA FIBERGLASS WINDOW
- INTERIOR FRAME COLOR : HARMONY
- EXTERIOR FRAME COLOR : BLACK BEAN
- U -FACTOR 0.29
- SHGC 0.21
- LOE 3 GLASS
:fr
TOP PLATE
HDR.
TOP PLATE
TOP SHEATHING
HDR.
0 CD
IU
Lib
SOUTH ELEVATION -- PROPOSED
SCALE: 1/4" = 1'-0"
REVISION
DATE
STREET ADDRESS
z
0 803 W LA JOLLA ST.
PLACENTIA, CA 92570
if
WANG'S 3 -UNIT
CONDO - PLACENTIA
IL
DRAWN BY:
STEVEN Z. WANG
DATE:
09. 18.2023
z TITLE:
< COLORED ELEVATION I
A- 1 4
TYPE
(SEQUENCE
FILE NAME:
IH
TYP.
COLOR: DUNN EDWARDS
RH46- ASPEN GREEN
TYP.
HARDIEPLANK , LAP SIDING
HEATHERD MOSS
TYP.
NEW INSTALLATION OF ROOFING MATERIAL
SAXONY' 900 SHAKE GARNET BLEND
ICC -ESR -1847 AND DARK BROWN, RED, GRAY
MULTICOLOR COLOR
•
--'r•'�':^'
-....-rte--� -.r-._ .�-....�-rte..- �,�,..- ���,,.�--+.-..- r' -...-.mow _--•�-t ...moi.-��.,;,,,,,,..:r,,.w�-.-�.� - 'r"-w-`.'yy_�___,�"""..-..war--.fes-+''-'�---' •
._,_�...,,.w
•
Ell
a
L✓
1_1
TOTAL HEIGHT
TOP PLATE
HDR.
TOP PLATE
TOP SHEATHING
HDR.
TYP.
LA HABRA STUCCO
696 SOUTHERN MOSS
BASE 200
1 TYP.
HARDIEPLANK , LAP SIDING
HEATHERD MOSS
TYP,
COLOR DUNN EDWARDS
RH48- ASPEN GREEN
TYP.
ELDORADO STONE , RIVER ROCK
COLORADO COLOR
TYP.
NEW INSTALLATION CF ROOFING MATERIAL .
SAXONY' 900 SHAKE GARNET BLEND
ICC -ESR -1647 AND DARK BROWN, RED, GRAY
MULTICOLOR COLOR
TYP.
- MILGARD ULTRA FIBERGLASS WINDOW
- INTERIOR FRAME COLOR : HARMONY
- EXTERIOR FRAME COLOR : BLACK BEAN
- U -FACTOR 0.29
- SHGC 0.21
- LOE 3 GLASS
- _ �- �� =►
�_....r.. -_.. .�-� •.--.y.�-----�
TYP.
LA HABRA STUCCO
696 SOUTHERN MOSS
BASE 200
TYP.
TUSCANY DOOR
TOL 6LT
TYP_
ELDORADO STONE , RIVER ROCK
COLORADO COLOR
TYP_
COLOR: DUNN EDWARDS
RH48 - ASPEN GREEN
L-.
L
•
•
O
07 I'.
•
C11
WEST ELEVATION - PROPOSED
SCALE: 1/4" = 1'-0"
f
TYP.
- MILGARD ULTRA FIBERGLASS WINDOW
- INTERIOR FRAME COLOR : HARMONY
- EXTERIOR FRAME COLOR : BLACK BEAN
- U -FACTOR 0.29
- SHGC 0.21
- LOE 3 GLASS
TYP.
COLOR: DUNN EDWARDS
RH35- OAK BROWN
1 TYP.
COLOR: DUNN EDWARDS
RH35- OAK BROWN
TOTAL HEIGHT
TOP PLATE
0 th
TOP PLATE
TOP SHEATHING
0 EAST ELEVATION - PROPOSED
SCALE: 1 /4" =
-w
CU
•
REVISION
DATE
0 .0
z n�
0 ic N
CO • H
W
U (Y)U
z 0<
STREET ADDRESS
z
0 803 W LA JOLLA ST.
PLACENTIA, CA 92570
if
w WANG'S 3 -UNIT
CONDO - PLACENTIA
DRAWN BY:
STEVEN Z. WANG
DATE:
09. 18.2023
TITLE:
COLORED ELEVATION 2
A-15
TYPE
(SEQUENCE
FILE NAME:
Boral Roofing
Build something greatTM
ROOFING MATERIAL
N.T.S.
Uk I rrlNV i tu: V.S i L-LULU
4A‘tut-Eclicatiti
PAINTS
Profile
Color Name:
SKU Number:
Product Type:
Color:
FRONTIER LAND DE6074
Saxony® 900 Shake
Garnet Blend
1 FBCJ3182
Standard Weight
Dark Brown, Red, Grey Multicolor
Tile Specification
Size:
Coverage:
Approx. Installed Weight:
Pieces per Pallet:
Squares per Pallet:
Approx. Weight per Pallet:
OAK BROWN
ASPEN GREEN
TRIM/FASCIA BOARD/GARAGE DOOR/ COLUMN COLOR
N.T.S.
17" x 13"
85 930 Ibs
288
3.39 3405 Ibs
LaHabra
Fine
696SOUTHERN MOSS
05 STUCCO WALL MATERIAL
N.T.S.
JamesHardie
HARDIEPLANK
LAP SIDING
lowmanniMilPoilOMEMPOIliwnwarinor
•
_ .rw rte.. - — •10M1///7I
HEATHERD MOSS
04 SIDING WALL MATERIAL
N.T.S.
ELDORA1](W
STONE
River Rock
02 COLORADO COLOR
03 ENTRANCE COLUMN FOOTING MATERIAL
N.T.S.
REVISION
DATE
O •O
z oz)
O QN
U
Z uL1 fiC UQ
06 <z
W
�U
z 0
STREET ADDRESS
z
0 803 W LA JOLLA ST.
PLACENTIA, CA 92870
if
WANG'S 3 -UNIT
CONDO - PLACENTIA
0 DRAWN BY:
STEVEN Z. WANG
DATE:
09. 18.2023
TITLE:
MATERIAL BOARD I
A- 1 6
TYPE
(SEQUENCE
01 FILE NAME:
Pavestone
8 in. x 4 in. x 60 mm Red Concrete Paver
11 CONCRETE PAVER
N.T.S.
GAMA SON/C°
SOLAR LIGHTING
Model #: 21751
Sku #: 442209
09 Post/3"Fitter Mount
For optimum light duration throughout the night, it is very important to place your solar lamp in a spot where it will receive the maximum amount of direct sunlight throughout the day.
Note: For best results, the solar lamp post must be charged for two sunny days on the "ON" position.
Open your package and remove the contents. Check to
make sure all pieces are present and accounted for.
• You will need to follow these two steps to
disassemble the unit completely
BAYTOWN 11 BULB
SOLAR LAMP
Model: GS-105B-FPW
US Patent #9458970 4r7172307
10 SOLAR LIGHTING
N.T.S.
Note if you're
not going to use
the 3" fitter base.
disassemble the
nut and part (H)
from part (E).
.411
A. Finial
B. Top
C. Window
Frame
D. Fixture
6.011.
E. 3" Fitter
F. Wall bracket
G. Pier Mount
I. G5 LED Bulb
WARNING: GAMA SON1C® Light bulbs are built and
designed for Gama Sonic products only. They are not
designed to be used in other electrical sockets.
H. Base For the same reason, regular AC and/or low Voltage bulbs cannot be used in Gama Sonic products.
UltraTM Series Fiberglass Windows & Patio Doors
Architectural Manual
Horizontal Sliding Window
2-114" Setback with Contour Z -Bar
CAD File Scale
NTS
View
Horizontal & Vertical
File Name
3110U-05 HS
More Technical Documents can be found at milgard.cam/professionals oue to continual research and development, details may be changed at any time. 02013 Miigard Mfg.
HEAD & SILL
WINDOW DETAILS
NTS.
76:1,
M • I
WINDOWS &DOORS
ega,1,171-/t& Ae4t
Series
on
WINDOW COLOR
N.T.S.
HORIZONTAL SLIDER
SERIES3110
4, "
FP4Mt
YIMTH
Units
Inch
JAMBS
07 Exterior Frame Colors - White interior only
Black Bean
Interior Frame Colors
ESPRESSO
EXTERIOR ONLY
06 REVISION
DATE
O -O
U
Z u� Q
UIQ
06 <z
W
(U
z 0<
STREET ADDRESS
0 803 W LA JOLLA ST.
PLACENTIA, CA 92870
I—
w WANG'S 3 -UNIT
CONDO - PLACENTIA
0 z
DRAWN BY:
STEVEN Z. WANG
DATE:
09. 18.2023
TITLE:
MATERIAL BOARD 2
A- 1 7
TYPE
(SEQUENCE
FILE NAME:
AFFIDAVIT OF MAILING NOTICE OF PUBLIC HEARING
STATE OF CALIFORNIA )
County of Orange
ss
I, N A.• wells'say that on the 2"° day of NovEM(!, 2o-3 a copy of the notice attached hereto was mailed to each of the persons whose name and address appears on the attached list. Said mailings was done at the City of Placentia City Hall, Planning Division, located at 401 E. Chapman Avenue, Placentia, California
Project Address: Sct3 w• 1 - OL( -R STPt E t-
usr ?Feutr Na. up 2°Z3 -to; 'TtNrerltE 1AucFL Mkf NO. TPM 2070- (74) Case No.: sib pcAN TtevsW NG. sPR Z02.3-- OZ
Meeting Date: niwE�ngew- N l i Z 0z-31 A -r 6 ' -3°rM
I declare, under penalty of perjury, that the foregoing is true and correct.
Executed at Placentia, California on this 2'1° day of NO`e^"iSe2 ZuZ 3
NOTICE OF PUBLIC HEARING
NOTICE IS HEREBY GIVEN that the Planning Commission of the City of Placentia will hold a public hearing in the Council Chambers of the Placentia City Hall, 401 E. Chapman Avenue on Tuesday, November 14, 2023, at 6:30 p.m., or as soon thereafter as the matter may be heard, to consider the following items:
APPLICANT:
PROJECT LOCATION:
CASE NOS.:
REQUEST:
CHD International, c/o Eric Lin
803 W. La Jolla Street (northside of W. La
Jolla Street, westside of Lawrence Street)
APN 344-131-11
USE PERMIT NO. UP 2023-10, TENTATIVE
PARCEL MAP NO. TPM 2020-124, & SITE
PLAN REVIEW NO. SPR 2023-02
UP: To permit the development of a two-story
townhome development consisting of three
attached condominium units and associated
landscape and hardscape improvements on
an improved 0.19 -acre lot. TPM: To permit a
condominium subdivision of three townhome
units. SPR: To permit the development of
three townhome condominium units within the
High Density Residential (R-3) Zoning District.
ENVIRONMENTAL DETERMINATION (CEQA).: The proposed development is not expected to create a negative impact on the physical environment and, therefore, staff is recommending a categorical exemption pursuant to the California Environmental Quality Act (CEQA) Guideline § 15332 (Class 32- In -Fill Development Projects) and City Environmental Guidelines.
ALL INTERESTED PERSONS are invited to attend this hearing and express opinions upon the items listed above.
ANY WRITTEN MATERIALS to be submitted to the Planning Commission should be submitted to the Planning Division at least twenty-four (24) hours prior to the hearing. Ten (10) copies are requested.
IF YOU CHALLENGE this proposal in court, you may be limited to raising only those issues you or someone else raised at the public hearings described in this notice or written correspondence delivered to the Planning Commission.
FURTHER INFORMATION on these items may be obtained at the Development Services Department, Planning Division, or by telephone: (714) 993-8124.
Tomah, La vwbe,Yt
SECRETARY TO THE PLACENTIA PLANNING COMMISSION
PUBLISHED:
MAILED:
POSTED:
November 2, 2023
November 2, 2023
November 2, 2023
PARA INFORMACION EN ESPANOL, LLAME AL (714) 993-8124
NOTICE OF PUBLIC HEARING
NOTICE IS HEREBY GIVEN that the Planning Commission of the City of Placentia will hold a public hearing in the Council Chambers of the Placentia City Hall, 401 E. Chapman Avenue on Tuesday, November 14, 2023, at 6:30 p.m., or as soon thereafter as the matter may be heard, to consider the following items:
APPLICANT:
PROJECT LOCATION:
CASE NOS.:
REQUEST:
CHD International, c/o Eric Lin
803 W. La Jolla Street (northside of W. La
Jolla Street, westside of Lawrence Street)
APN 344-131-11
USE PERMIT NO. UP 2023-10, TENTATIVE
PARCEL MAP NO. TPM 2020-124, & SITE
PLAN REVIEW NO. SPR 2023-02
UP: To permit the development of a two-story
townhome development consisting of three
attached condominium units and associated
landscape and hardscape improvements on
an improved 0.19 -acre lot. TPM: To permit a
condominium subdivision of three townhome
units. SPR: To permit the development of
three townhome condominium units within the
High Density Residential (R-3) Zoning District.
ENVIRONMENTAL DETERMINATION (CEQA): The proposed development is not expected to create a negative impact on the physical environment and, therefore, staff is recommending a categorical exemption pursuant to the California Environmental Quality Act (CEQA) Guideline § 15332 (Class 32- In -Fill Development Projects) and City Environmental Guidelines.
ALL INTERESTED PERSONS are invited to attend this hearing and express opinions upon the items listed above.
ANY WRITTEN MATERIALS to be submitted to the Planning Commission should be submitted to the Planning Division at least twenty-four (24) hours prior to the hearing. Ten (10) copies are requested.
IF YOU CHALLENGE this proposal in court, you may be limited to raising only those issues you or someone else raised at the public hearings described in this notice or written correspondence delivered to the Planning Commission.
FURTHER INFORMATION on these items may be obtained at the Development Services Department, Planning Division, or by telephone: (714) 993-8124.
Toxeblti La.v i be -r t
SECRETARY TO THE PLACENTIA PLANNING COMMISSION
PUBLISHED:
MAILED:
POSTED:
November 2, 2023
November 2, 2023
November 2, 2023
PARA INFORMACION EN ESPANOL, LLAME AL (714) 993-8124
Advanced Listing Services Inc
Ownership Listings & Radius Maps
P.O. Box 2593 • Dana Point, CA • 92624
Office: (949) 361-3921 •Cell (949) 310-6869
www.Advancedlistino.com [email protected]
I, Denise Kaspar, hereby certify that the attached list contains the names, addresses and assessor's parcel numbers of all persons to whom all property is assessed as they appear on the latest available assessment roll of the County of Orange within the area described by the required 300 foot radius measured from the exterior boundaries of the property legally described as:
Subject: APN: 344-131-11
Subject Address: 803 W LA JOLLA ST
PLACENTIA CA 92870
f�f
October 31, 2023 Denise Kaspar /
Subject APN: 344-131-11
300' RADIUS
l
PAR. /
/.94 AC.
-44r. xa'
PAR. 2
BLK.9
LOT 5
{4
2.69 AC.
.Tia./r' it
y.-
13. 3.028 AC.
eras.
LA JOLLA
110' 6s'
GOLDEN STATE
r r
25 0 O
1 � R.S. /7-50
POR. LOT 9
65'
r /7'
1-/ a
26-38
RS.
.
o
45' 127'
STREET h
1 43' { /27' -
7Advanced Listing Services Inc
Ownership Listings & Radius Maps
P.O. Box 2593 • Dana Point, CA • 92624
A Office: (949) 361-3921 •Cell: (949) 310-6869
www.Advancedlistina.com [email protected]
11. 50'
1-
LLJ
R. M. 119-37
TRA
•
T
Address: 803 W LA JOLLA ST
PLACENTIA CA 92870
W
Q
P.M.208- 38 t7
RM. /87- 99
0 A
Y
0 8.
O 9.
300.,4• -
le
.0 225/4'
REET 4— L A JOLLA
t2
O
se'
9 240.21'
\7
15. /. 61AC
16. GOLDEN STE 4.
PAR. 1.
3.472 AC.
3. 1.
LO
0 2.73 AC.
BL K. 9
0-431
AC.
Na
215 2/
40 7
4-
REE.T
132'
2. P.M 117-27
PAR. 1
2.908 AC.
#12038
10/31/2023
300' OWNERSHIP LISTING
300' OCCUPANT LISTING
PREPARED FOR:
344-131-11
STEVEN ZHIYU WANG
803 W LA JOLLA ST
PLACENTIA CA 92870
1 344-011-07
HACIENDA LA JOLLA I KOYL
752 W LA JOLLA ST
PLACENTIA CA 92870
4 344-011-12
CALVISTA INVESTMENTS
1841 AVENIDA DEL NORTE
FULLERTON CA 92833
7 344-131-06
ALBERT HOWELL PATTON
5040 MARSHBURN CIR
YORBA LINDA CA 92886
10 344-131-11
STEVEN ZHIYU WANG
17746 NEARBANK DR
ROWLAND HEIGHTS CA 91748
13 344-131-17
LEATRICE L MOISI
35107 ROAD 180
VISALIA CA 93292
16 344-132-08
JUNO APARTMENTS
752 W LA JOLLA ST
PLACENTIA CA 92870
1 344-011-07
OCCUPANT
752 W LA JOLLA ST APT 11B
PLACENTIA CA 92870
1 344-011-07
OCCUPANT
752 W LA JOLLA ST APT 11E
PLACENTIA CA 92870
Advanced Listing Services Inc
Ownership Listings & Radius Maps
P.O. Box 2593 • Dana Point, CA • 92624
A Office: (949) 361-3921 • Cell: (949) 310-6869
www.Advancedljtinq.com [email protected]
2 344-011-10
LMTD DABOYS
6330 VARIEL AVE 201
WOOLAND HILLS CA 91367
5 344-032-01
MAXIMIANO RAZON
884 W LA JOLLA ST
PLACENTIA CA 92870
8 344-131-07
LARRY A PATTON
925 LAWRENCE ST
PLACENTIA CA 92870
11 344-131-14
COUNTY INVESTMENTS
27286 VIA INDUSTRIA B
TEMECULA CA 92590
14 344-132-02
BEACH INDUSTRIES OWEN
1006 N RIDGELINE RD
3 344-011-11
HACIENDA LA JOLLA KOYL
752 W LA JOLLA ST
PLACENTIA CA 92870
6 344-032-02
BERNARDO LOZA
870 W LA JOLLA ST
PLACENTIA CA 92870
9 344-131-08
KENNETH C DEPPE
933 LAWRENCE ST
PLACENTIA CA 92870
12 344-131-16
LWP LLC
1841 AVENIDA DEL NORTE
FULLERTON CA 92833
15 344-132-03
DUPER DUOS SUPER
18701 WINDY KNOLL DR
ORANGE CA 92869 YORBA LINDA CA 92886
1 344-011-07
OCCUPANT
752 W LA JOLLA ST OFC
PLACENTIA CA 92870
1 344-011-07
OCCUPANT
752 W LA JOLLA ST APT 1 IC
PLACENTIA CA 92870
1 344-011-07
OCCUPANT
752 W LA JOLLA ST APT 11F
PLACENTIA CA 92870
1 344-011-07
OCCUPANT
752 W LA JOLLA ST APT 11A
PLACENTIA CA 92870
1 344-011-07
OCCUPANT
752 W LA JOLLA ST APT I ID
PLACENTIA CA 92870
1 344-011-07
OCCUPANT
752 W LA JOLLA ST APT 12A
PLACENTIA CA 92870
1 344-011-07 1 344-011-07 1 344-011-07
OCCUPANT OCCUPANT OCCUPANT
752 W LA JOLLA ST APT 12B 752 W LA JOLLA ST APT 12C 752 W LA JOLLA ST APT 12D PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-07 1 344-011-07 1 344-011-07
OCCUPANT OCCUPANT OCCUPANT
752 W LA JOLLA ST APT 12E 752 W LA JOLLA ST APT 12F 752 W LA JOLLA ST APT 21A PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-07 1 344-011-07 1 344-011-07
OCCUPANT OCCUPANT OCCUPANT
752 W LA JOLLA ST APT 21B 752 W LA JOLLA ST APT 21C 752 W LA JOLLA ST APT 22A PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-07 1 344-011-07 1 344-011-07
OCCUPANT OCCUPANT OCCUPANT
752 W LA JOLLA ST APT 22B 752 W LA JOLLA ST APT 22C 752 W LA JOLLA ST APT 31A PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-07 1 344-011-07 1 344-011-07
OCCUPANT OCCUPANT OCCUPANT
752 W LA JOLLA ST APT 31B 752 W LA JOLLA ST APT 32A 752 W LA JOLLA ST APT 32B PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-07 1 344-011-07 1 344-011-07
OCCUPANT OCCUPANT OCCUPANT
752 W LA JOLLA ST APT 41A 752 W LA JOLLA ST APT 41B 752 W LA JOLLA ST APT 41C PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-07 1 344-011-07 1 344-011-07
OCCUPANT OCCUPANT OCCUPANT
752 W LA JOLLA ST APT 41D 752 W LA JOLLA ST APT 42A 752 W LA JOLLA ST APT 42B PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-07 1 344-011-07 1 344-011-07
OCCUPANT OCCUPANT OCCUPANT
752 W LA JOLLA ST APT 42C 752 W LA JOLLA ST APT 42D 752 W LA JOLLA ST APT 51A PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-07 1 344-011-07 1 344-011-07
OCCUPANT OCCUPANT OCCUPANT
752 W LA JOLLA ST APT 51B 752 W LA JOLLA ST APT 52A 752 W LA JOLLA ST APT 52B PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-07 1 344-011-07 1 344-011-07
OCCUPANT OCCUPANT OCCUPANT
752 W LA JOLLA ST APT 61A 752 W LA JOLLA ST APT 61B 752 W LA JOLLA ST APT 61C PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870
1 344-011-07 1 344-011-07 1 344-011-07
OCCUPANT OCCUPANT OCCUPANT
752 W LA JOLLA ST APT 61D 752 W LA JOLLA ST APT 62A 752 W LA JOLLA ST APT 62B PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-07 1 344-011-07 1 344-011-07
OCCUPANT OCCUPANT OCCUPANT
752 W LA JOLLA ST APT 62C 752 W LA JOLLA ST APT 62D 752 W LA JOLLA ST APT 71A PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 I 344-011-07 1 344-011-07 1 344-011-07
OCCUPANT OCCUPANT OCCUPANT
752 W LA JOLLA ST APT 71B 752 W LA JOLLA ST APT 71C 752 W LA JOLLA ST APT 71D PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-07 1 344-011-07 1 344-011-07
OCCUPANT OCCUPANT OCCUPANT
752 W LA JOLLA ST APT 72A 752 W LA JOLLA ST APT 72B 752 W LA JOLLA ST APT 72C PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-07 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
752 W LA JOLLA ST APT 72D 840 W LA JOLLA ST APT 1A 840 W LA JOLLA ST APT 1B PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT IC 840 W LA JOLLA ST APT ID 840 W LA JOLLA ST APT IE PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 1F 840 W LA JOLLA ST APT 1G 840 W LA JOLLA ST APT 1H PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 2A 840 W LA JOLLA ST APT 2B 840 W LA JOLLA ST APT 2C PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 2D 840 W LA JOLLA ST APT 2E 840 W LA JOLLA ST APT 2F PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 2G 840 W LA JOLLA ST APT 2H 840 W LA JOLLA ST APT 3A PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870
1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 3B 840 W LA JOLLA ST APT 3C 840 W LA JOLLA ST APT 3D PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 3E 840 W LA JOLLA ST APT 3F 840 W LA JOLLA ST APT 3G PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 3H 840 W LA JOLLA ST APT 4A 840 W LA JOLLA ST APT 4B PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 4C 840 W LA JOLLA ST APT 4D 840 W LA JOLLA ST APT 4E PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 4F 840 W LA JOLLA ST APT 4G 840 W LA JOLLA ST APT 4H PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 I 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 5A 840 W LA JOLLA ST APT 5B 840 W LA JOLLA ST APT 5C PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 5D 840 W LA JOLLA ST APT 5E 840 W LA JOLLA ST APT 5F PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 5G 840 W LA JOLLA ST APT 5H 840 W LA JOLLA ST APT 6A PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 6B 840 W LA JOLLA ST APT 6C 840 W LA JOLLA ST APT 6D PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 6E 840 W LA JOLLA ST APT 6F 840 W LA JOLLA ST APT 6G PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870
1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 611 840 W LA JOLLA ST APT 7A 840 W LA JOLLA ST APT 7B PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 7C 840 W LA JOLLA ST APT 7D 840 W LA JOLLA ST APT 7E PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 7F 840 W LA JOLLA ST APT 7G 840 W LA JOLLA ST APT 7H PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 8A 840 W LA JOLLA ST APT 8B 840 W LA JOLLA ST APT 8C PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT - OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 8D 840 W LA JOLLA ST APT 8E 840 W LA JOLLA ST APT 8F PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-0I1-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 8G 840 W LA JOLLA ST APT 8H 840 W LA JOLLA ST APT 9A PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 9B 840 W LA JOLLA ST APT 9C 840 W LA JOLLA ST APT 9D PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 9E 840 W LA JOLLA ST APT 9F 840 W LA JOLLA ST APT 9G PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 9H 840 W LA JOLLA ST APT 10A 840 W LA JOLLA ST APT 10B PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT IOC 840 W LA JOLLA ST APT 10D 840 W LA JOLLA ST APT 10E PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870
1 344-011-11 1 344-011-11 1 344-011-11
OCCUPANT OCCUPANT OCCUPANT
840 W LA JOLLA ST APT 1OF 840 W LA JOLLA ST APT 10G 840 W LA JOLLA ST APT 10H PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 2 344-011-10 2 344-011-10 2 344-011-10
OCCUPANT OCCUPANT OCCUPANT
734 W LA JOLLA ST 734 W LA JOLLA ST APT 101 734 W LA JOLLA ST APT 102 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 2 344-011-10 2 344-011-10 2 344-011-10
OCCUPANT OCCUPANT OCCUPANT
734 W LA JOLLA ST APT 103 734 W LA JOLLA ST APT 104 734 W LA JOLLA ST APT 105 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 2 344-011-10 2 344-011-10 2 344-011-10
OCCUPANT OCCUPANT OCCUPANT
734 W LA JOLLA ST APT 106 734 W LA JOLLA ST APT 107 734 W LA JOLLA ST APT 108 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 2 344-011-10 2 344-011-10 2 344-011-10
OCCUPANT OCCUPANT OCCUPANT
734 W LA JOLLA ST APT 109 734 W LA JOLLA ST APT 110 734 W LA JOLLA ST APT 111 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 2 344-011-10 2 344-011-10 2 344-011-10
OCCUPANT OCCUPANT OCCUPANT
734 W LA JOLLA ST APT 112 734 W LA JOLLA ST APT 113 734 W LA JOLLA ST APT 114 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 2 344-011-10 2 344-011-10 2 344-011-10
OCCUPANT OCCUPANT OCCUPANT
734 W LA JOLLA ST APT 115 734 W LA JOLLA ST APT 116 734 W LA JOLLA ST APT 117 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 2 344-011-10 2 344-011-10 2 344-011-10
OCCUPANT OCCUPANT OCCUPANT
734 W LA JOLLA ST APT 118 734 W LA JOLLA ST APT 119 734 W LA JOLLA ST APT 120 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 2 344-011-10 2 344-011-10 2 344-011-10
OCCUPANT OCCUPANT OCCUPANT
734 W LA JOLLA ST APT 121 734 W LA JOLLA ST APT 122 734 W LA JOLLA ST APT 123 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 2 344-011-10 2 344-011-10 2 344-011-10
OCCUPANT OCCUPANT OCCUPANT
734 W LA JOLLA ST APT 124 734 W LA JOLLA ST APT 125 734 W LA JOLLA ST APT 126 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870
2 344-011-10 2 344-011-10 2 344-011-10
OCCUPANT OCCUPANT OCCUPANT
734 W LA JOLLA ST APT 127 734 W LA JOLLA ST APT 128 734 W LA JOLLA ST APT 129 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 2 344-011-10 2 344-011-10 2 344-011-10
OCCUPANT OCCUPANT OCCUPANT
734 W LA JOLLA ST APT 130 734 W LA JOLLA ST APT 201 734 W LA JOLLA ST APT 202 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 2 344-011-10 2 344-011-10 2 344-011-10
OCCUPANT OCCUPANT OCCUPANT
734 W LA JOLLA ST APT 203 734 W LA JOLLA ST APT 204 734 W LA JOLLA ST APT 205 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 2 344-011-10 2 344-011-10 2 344-011-10
OCCUPANT OCCUPANT OCCUPANT
734 W LA JOLLA ST APT 206 734 W LA JOLLA ST APT 207 734 W LA JOLLA ST APT 208 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 2 344-011-10 2 344-011-10 2 344-011-10
OCCUPANT OCCUPANT OCCUPANT
734 W LA JOLLA ST APT 209 734 W LA JOLLA ST APT 2I0 734 W LA JOLLA ST APT 211 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 2 344-011-10 2 344-011-10 2 344-011-10
OCCUPANT OCCUPANT OCCUPANT
734 W LA JOLLA ST APT 212 734 W LA JOLLA ST APT 213 734 W LA JOLLA ST APT 214 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 2 344-011-10 2 344-011-10 2 344-011-10
OCCUPANT OCCUPANT OCCUPANT
734 W LA JOLLA ST APT 215 734 W LA JOLLA ST APT 216 734 W LA JOLLA ST APT 217 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 2 344-011-10 2 344-011-10 2 344-011-10
OCCUPANT OCCUPANT OCCUPANT
734 W LA JOLLA ST APT 223 734 W LA JOLLA ST APT 224 734 W LA JOLLA ST APT 225 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 2 344-011-10 2 344-011-10 2 344-011-10
OCCUPANT OCCUPANT OCCUPANT
734 W LA JOLLA ST APT 226 734 W LA JOLLA ST APT 227 734 W LA JOLLA ST APT 228 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 2 344-011-10 2 344-011-10 4 344-011-12
OCCUPANT OCCUPANT OCCUPANT
734 W LA JOLLA ST APT 229 734 W LA JOLLA ST APT 230 738 W LA JOLLA ST APT 1 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870
4 344-011-12 4 344-011-12 4 344-011-12
OCCUPANT OCCUPANT OCCUPANT
738 W LA JOLLA ST APT 2 738 W LA JOLLA ST APT 3 738 W LA JOLLA ST APT 4 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 4 344-011-12 4 344-011-12 4 344-011-12
OCCUPANT OCCUPANT OCCUPANT
738 W LA JOLLA ST APT 5 738 W LA JOLLA ST APT 6 738 W LA JOLLA ST APT 7 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 4 344-011-12 4 344-011-12 4 344-011-12
OCCUPANT OCCUPANT OCCUPANT
738 W LA JOLLA ST APT 8 738 W LA JOLLA ST APT 9 738 W LA JOLLA ST APT 10 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 4 344-011-12 4 344-011-12 6 344-032-02
OCCUPANT OCCUPANT OCCUPANT
738 W LA JOLLA ST APT 11 738 W LA JOLLA ST APT 12 870 W LA JOLLA ST APT A PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 6 344-032-02 7 344-131-06 10 344-131-11
OCCUPANT OCCUPANT OCCUPANT
870 W LA JOLLA ST APT B 919 LAWRENCE ST 803 W LA JOLLA ST PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 11 344-131-14 11 344-131-14 11 344-131-14
OCCUPANT OCCUPANT OCCUPANT
940 S PLACENTIA AVE STE A 940 S PLACENTIA AVE STE B 940 S PLACENTIA AVE STE C PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 11 344-131-14 11 344-131-14 11 344-131-14
OCCUPANT OCCUPANT OCCUPANT
940 S PLACENTIA AVE STE D 940 S PLACENTIA AVE STE E 940 S PLACENTIA AVE STE F PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 11 344-131-14 11 344-131-14 11 344-131-14
OCCUPANT OCCUPANT OCCUPANT
940 S PLACENTIA AVE STE G 940 S PLACENTIA AVE STE H 940 S PLACENTIA AVE STE I PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 11 344-131-14 11 344-131-14 11 344-131-14
OCCUPANT OCCUPANT OCCUPANT
940 S PLACENTIA AVE STE J 940 S PLACENTIA AVE STE K 940 S PLACENTIA AVE STE L PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 11 344-131-14 11 344-131-14 11 344-131-14
OCCUPANT OCCUPANT OCCUPANT
940 S PLACENTIA AVE STE M 940 S PLACENTIA AVE STE N 940 S PLACENTIA AVE STE 0 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870
11 344-131-14 11 344-131-14 11 344-131-14
OCCUPANT OCCUPANT OCCUPANT
940 S PLACENTIA AVE STE P 940 S PLACENTIA AVE STE Q 940 S PLACENTIA AVE STE R PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 11 344-131-14 11 344-131-14 11 344-131-14
OCCUPANT OCCUPANT OCCUPANT
940 S PLACENTIA AVE STE S 940 S PLACENTIA AVE STE T 940 S PLACENTIA AVE STE U PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 11 344-131-14 11 344-131-14 11 344-131-14
OCCUPANT OCCUPANT OCCUPANT
940 S PLACENTIA AVE STE V 940 S PLACENTIA AVE STE W 940 S PLACENTIA AVE STE X PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 11 344-131-14 11 344-131-14 11 344-131-14
OCCUPANT OCCUPANT OCCUPANT
940 S PLACENTIA AVE STE Y 940 S PLACENTIA AVE STE Z 940 S PLACENTIA AVE STE Al PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 11 344-131-14 11 344-131-14 11 344-131-14
OCCUPANT OCCUPANT OCCUPANT
940 S PLACENTIA AVE STE B1 930 S PLACENTIA AVE STE A 930 S PLACENTIA AVE STE B PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 11 344-131-14 11 344-131-14 11 344-131-14
OCCUPANT OCCUPANT OCCUPANT
930 S PLACENTIA AVE STE C 930 S PLACENTIA AVE STE D 930 S PLACENTIA AVE STE E PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 11 344-131-14 11 344-131-14 11 344-131-14
OCCUPANT OCCUPANT OCCUPANT
930 S PLACENTIA AVE STE F 930 S PLACENTIA AVE STE G 930 S PLACENTIA AVE STE H PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 12 344-131-16 12 344-131-16 12 344-131-16
OCCUPANT OCCUPANT OCCUPANT
821 W LA JOLLA ST OFC 821 W LA JOLLA ST APT 10IA 821 W LA JOLLA ST APT 101B PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 12 344-131-16 12 344-131-16 12 344-131-16
OCCUPANT OCCUPANT OCCUPANT
821 W LA JOLLA ST APT 101C 821 W LA JOLLA ST APT 101D 821 W LA JOLLA ST APT 102A PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 12 344-131-16 12 344-131-16 12 344-131-16
OCCUPANT OCCUPANT OCCUPANT
821 W LA JOLLA ST APT 102B 821 W LA JOLLA ST APT 102C 821 W LA JOLLA ST APT 102D PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870
12 344-131-16 12 344-131-16 12 344-131-16
OCCUPANT OCCUPANT OCCUPANT
821 W LA JOLLA ST APT 103A 821 W LA JOLLA ST APT 103B 821 W LA JOLLA ST APT 103C PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 12 344-131-16 12 344-131-16 12 344-131-16
OCCUPANT OCCUPANT OCCUPANT
821 W LA JOLLA ST APT 104A 821 W LA JOLLA ST APT 104C 821 W LA JOLLA ST APT 201A PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 12 344-131-16 12 344-131-16 12 344-131-16
OCCUPANT OCCUPANT OCCUPANT
821 W LA JOLLA ST APT 201B 821 W LA JOLLA ST APT 201C 821 W LA JOLLA ST APT 201D PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 12 344-131-16 12 344-131-16 12 344-131-16
OCCUPANT OCCUPANT OCCUPANT
821 W LA JOLLA ST APT 202A 821 W LA JOLLA ST APT 202B 821 W LA JOLLA ST APT 202C PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 12 344-131-16 12 344-131-16 12 344-131-16
OCCUPANT OCCUPANT OCCUPANT
821 W LA JOLLA ST APT 202D 821 W LA JOLLA ST APT 203A 821 W LA JOLLA ST APT 203B PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 12 344-131-16 12 344-131-16 12 344-131-16
OCCUPANT OCCUPANT OCCUPANT
821 W LA JOLLA ST APT 203C 821 W LA JOLLA ST APT 203D 821 W LA JOLLA ST APT 204A PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 12 344-131-16 12 344-131-16 12 344-131-16
OCCUPANT OCCUPANT OCCUPANT
821 W LA JOLLA ST APT 204B 821 W LA JOLLA ST APT 204C 821 W LA JOLLA ST APT 204D PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 12 344-131-16 12 344-131-16 12 344-131-16
OCCUPANT OCCUPANT OCCUPANT
821 W LA JOLLA ST APT 301B 821 W LA JOLLA ST APT 301C 821 W LA JOLLA ST APT 301D PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 12 344-131-16 12 344-131-16 12 344-131-16
OCCUPANT OCCUPANT OCCUPANT
821 W LA JOLLA ST APT 302B 821 W LA JOLLA ST APT 302C 821 W LA JOLLA ST APT 302D PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 13 344-131-17 14 344-132-02 15 344-132-03
OCCUPANT OCCUPANT OCCUPANT
990 S PLACENTIA AVE 920 LAWRENCE ST 930 LAWRENCE ST
PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870
16 344-132-08 16 344-132-08 16 344-132-08
OCCUPANT OCCUPANT OCCUPANT
747 W LA JOLLA ST APT 101 747 W LA JOLLA ST APT 102 747 W LA JOLLA ST APT 103 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 16 344-132-08 16 344-132-08 16 344-132-08
OCCUPANT OCCUPANT OCCUPANT
747 W LA JOLLA ST APT 104 747 W LA JOLLA ST APT 105 747 W LA JOLLA ST APT 106 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 16 344-132-08 16 344-132-08 16 344-132-08
OCCUPANT OCCUPANT OCCUPANT
747 W LA JOLLA ST APT 107 747 W LA JOLLA ST APT 108 747 W LA JOLLA ST APT 109 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 16 344-132-08 16 344-132-08 16 344-132-08
OCCUPANT OCCUPANT OCCUPANT
747 W LA JOLLA ST APT 110 747 W LA JOLLA ST APT 111 747 W LA JOLLA ST APT 112 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 16 344-132-08 I6 344-132-08 16 344-132-08
OCCUPANT OCCUPANT OCCUPANT
747 W LA JOLLA ST APT 113 747 W LA JOLLA ST APT 114 747 W LA JOLLA ST APT 115 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 16 344-132-08 16 344-132-08 16 344-132-08
OCCUPANT OCCUPANT OCCUPANT
747 W LA JOLLA ST APT 116 747 W LA JOLLA ST APT 201 747 W LA JOLLA ST APT 202 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 16 344-132-08 16 344-132-08 16 344-132-08
OCCUPANT OCCUPANT OCCUPANT
747 W LA JOLLA ST APT 203 747 W LA JOLLA ST APT 204 747 W LA JOLLA ST APT 205 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 16 344-132-08 16 344-132-08 16 344-132-08
OCCUPANT OCCUPANT OCCUPANT
747 W LA JOLLA ST APT 206 747 W LA JOLLA ST APT 207 747 W LA JOLLA ST APT 208 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 16 344-132-08 16 344-132-08 16 344-132-08
OCCUPANT OCCUPANT OCCUPANT
747 W LA JOLLA ST APT 301 747 W LA JOLLA ST APT 302 747 W LA JOLLA ST APT 303 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 16 344-132-08 16 344-132-08 16 344-132-08
OCCUPANT OCCUPANT OCCUPANT
747 W LA JOLLA ST APT 304 747 W LA JOLLA ST APT 305 747 W LA JOLLA ST APT 306 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870
16 344-132-08 16 344-132-08 16 344-132-08
OCCUPANT OCCUPANT OCCUPANT
747 W LA JOLLA ST APT 307 747 W LA JOLLA ST APT 308 747 W LA JOLLA ST APT 401 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 16 344-132-08 16 344-132-08 16 344-132-08
OCCUPANT OCCUPANT OCCUPANT
747 W LA JOLLA ST APT 402 747 W LA JOLLA ST APT 403 747 W LA JOLLA ST APT 404 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 16 344-132-08 16 344-132-08 16 344-132-08
OCCUPANT OCCUPANT OCCUPANT
747 W LA JOLLA ST APT 405 747 W LA JOLLA ST APT 406 747 W LA JOLLA ST APT 407 PLACENTIA CA 92870 PLACENTIA CA 92870 PLACENTIA CA 92870 16 344-132-08
OCCUPANT
747 W LA JOLLA ST APT 408
PLACENTIA CA 92870