City of Sacramento
City Council - 5PM Report
915 I Street Sacramento, CA 95814
www.cityofsacramento.org
File ID: 2023-00043 3/7/2023 Consent Item 17.
Agreement: Ballroom B HVAC and Lighting Systems Project (M17101900) [Published for 10- Day Review on 2/23/2023]
File ID: 2023-00043
Location: District 4, Represented by Councilmember Valenzuela Recommendation: Adopt a Resolution: 1) awarding a Construction Contract for the Ballroom B HVAC and Lighting Systems Project at the SAFE Credit Union Convention Center to Mesa Energy Systems, Inc. in an amount not to exceed $2,991,182; 2) authorizing the City Manager or City Manager’s designee to execute the Construction Contract with Mesa Energy Systems, Inc.; 3) establishing the Ballroom B HVAC and Lighting Systems Project (M17101900) as a new Capital Improvement Project; 4) approving the Plans and Specifications for the Ballroom B HVAC and Lighting Systems Project; and 5) authorizing the City Manager or City Manager’s designee to transfer $4,500,000 (Community Center Fund, Fund 6010) from the expenditure budget of various capital improvement projects to the expenditure budget of the Ballroom B HVAC and Lighting Systems Project (M17101900).
Contact: Sabrina Tefft, Project Manager, (916) 808-3789, [email protected], Office of Innovation and Economic Development; Mack Smith, Engineering Manager, (916) 808-5445, [email protected]; and Steven Sakakihara, Administrative Officer, (916) 808-7146, [email protected], Convention and Cultural Services Department Presenter: None.
Attachments:
1-Description/Analysis
2-Resolution
3-Construction Contract with Mesa Energy Systems, Inc.
4-Plans
5-Specifications
Description/Analysis
Issue Detail: The SAFE Credit Union Convention Center Ballroom B (1400 J Street, Sacramento, CA 95814) has lighting fixtures and controls that are over 27 years old and are outdated. As a result, the replacement fixtures are becoming obsolete and difficult to source. There is also a need to relocate
File ID: 2023-00043 3/7/2023 Consent Item 17.
the HVAC system, which is currently placed in a location that makes it extremely difficult to access for maintenance. The relocation of the HVAC system was included as part of the Convention Center Complex Renovation Project, but due to the overlapping scopes of work in Ballroom B, the two scopes were designed as an independent project, which created an opportunity for cost savings, while allowing the work to be performed around programmed events at the SAFE Credit Union Convention Center.
Coordination efforts with Visit Sacramento and the Hotel Association have allowed for these improvements to be completed between June and October of 2023. These improvements will allow the facility to run efficiently, while staying competitive and keeping up with industry standards.
On November 22, 2022, Invitation for Bid (IFB) No. B23171131006 was released via the City’s bid portal (Planet Bids) to solicit bids for the Ballroom B HVAC and Lighting Systems Project at the SAFE Credit Union Convention Center. Following this IFB process, staff recommends awarding a construction contract to Mesa Energy Systems, Inc. in an amount of $2,991,182.
Policy Considerations: The recommendations in this report are consistent with the provisions of Sacramento City Code chapter 3.60: Contracts for Public Projects. Per Sacramento City Code section 3.60.090, all contracts for public projects involving an expenditure of $250,000 or more require award by the city council.
The Sacramento City Code Section 4.04.020 and Council Rules of Procedure (Chapter 7, Section E.2.d) mandate that unless waived by a 2/3 vote of the City Council, all labor agreements and all agreements greater than $1,000,000 shall be made available to the public at least ten (10) days prior to council action. This item was published for 10-day review on February 23, 2023, in compliance with the City Code.
Economic Impacts: The recommended contract is expected to create 22.13 jobs (14.06 direct jobs and 8.08 jobs through indirect and induced activities) and create $2,920,955 in total economic output ($1,872,408 of direct output and $1,048,547 of indirect and induced activities).
The indicated economic impacts are estimates calculated using a calculation tool developed by the Center for Strategic Economic Research (CSER). CSER utilized the IMPLAN input-output model (2009 coefficients) to quantify the economic impacts of a hypothetical $1 million of spending in various construction categories within the City of Sacramento in an average one-year period. Actual impacts could differ significantly from the estimates and neither the City of Sacramento nor CSER shall be held responsible for consequences resulting from such differences.
Additionally, this contract requires compliance with the approved Community Workforce and Training Agreement (CWTA), which requires local hiring and allow for targeted employment opportunities for Sacramento residents.
File ID: 2023-00043 3/7/2023 Consent Item 17.
Environmental Considerations: Under the California Environmental Quality Act (CEQA), continuing administrative activities, such as what is recommended in this report, does not constitute a “project”. [CEQA Guidelines section 15378(b)(2).]
Sustainability: This project is designed utilizing energy efficient standards and will reduce the carbon footprint contribution, therefore helping meet the City of Sacramento’s sustainability goal.
Commission/Committee Action: Not applicable.
Rationale for Recommendation: There were two bids submitted prior to the deadline of the IFB of 2pm on December 21, 2022. Both bids submitted were considered responsive, Mesa Energy Systems, Inc. was the lowest responsive and responsible bidder as summarized below:
Contractor Total Bid Amount LBE Participation Requirement Satisfied?
Mesa Energy Systems, Inc. $2,991,182 Yes
PRIDE Industries One, Inc. $3,199,600 Yes
Financial Considerations: The total estimated cost for the Ballroom B HVAC and Lighting Systems Project (M17101900) is $4,500,000. This total cost includes the construction contract, construction management, commissioning services and contingency.
The funding required for the Ballroom B HVAC and Lighting Systems Project (M17101900) will be transferred from existing CIPs as shown in the table below:
Project Description CIP # Fund - Fund Name Amount
Convention Center Improvements M17100000 6010 - Community Center
$1,100,000
Convention Center Audio-Visual
Improvements
M17100300 6010 - Community
Center
$140,000
Convention Center Chiller Upgrade M17100500 6010 - Community Center
$50,000
Memorial Auditorium Improvements M17101000 6010 - Community Center
$955,000
Convention Center Durable
Equipment Replacement
M17101600 6010 - Community
Center
$145,000
Convention Center Production
Equipment Upgrades
M17101700 6010 - Community
Center
$2,110,000
TOTAL $4,500,000
TOTAL $4,500,000
File ID: 2023-00043 3/7/2023 Consent Item 17.
Project Description CIP # Fund - Fund Name Amount
Convention Center Improvements M17100000 6010 - Community Center
$1,100,000
Convention Center Audio-Visual
Improvements
M17100300 6010 - Community
Center
$140,000
Convention Center Chiller Upgrade M17100500 6010 - Community Center
$50,000
Memorial Auditorium Improvements M17101000 6010 - Community Center
$955,000
Convention Center Durable
Equipment Replacement
M17101600 6010 - Community
Center
$145,000
Convention Center Production
Equipment Upgrades
M17101700 6010 - Community
Center
$2,110,000
Local Business Enterprise (LBE): Mesa Energy Systems, Inc. is a LBE vendor and met the 5% LBE participation requirement.
RESOLUTION NO. 2023-XXXX
Adopted by the Sacramento City Council
Agreement: Ballroom B HVAC and Lighting Systems Project (M17101900)
BACKGROUND
A. The SAFE Credit Union Convention Center Ballroom B (1400 J Street, Sacramento, CA 95814) has lighting fixtures and controls that are over 27 years old and are outdated. As a result, the replacement fixtures are becoming obsolete and difficult to source. There is also a need to relocate the HVAC system, which is currently placed in a location that makes it extremely difficult to access for maintenance. The project combines the two scopes, creating an opportunity for cost savings, while allowing the work to be performed around programmed events at the SAFE Credit Union Convention Center.
B. On November 22, 2022, Invitation for Bid (IFB) No. B23171131006 was released via the City’s bid portal (Planet Bids) to solicit bids for the Ballroom B HVAC and Lighting Systems Project at the SAFE Credit Union Convention Center.
C. Mesa Energy System, Inc. was the successful low bidder.
D. The total estimated cost for the Ballroom B HVAC and Lighting Systems Project (M17101900) is $4,500,000, which includes costs for the construction contract, construction management, commissioning services and contingency.
E. There are sufficient funds in existing capital improvement programs (CIPs) that can be transferred to the Ballroom B HVAC and Lighting Systems Project (M17101900).
BASED ON THE FACTS SET FORTH IN THE BACKGROUND, THE CITY COUNCIL RESOLVES AS FOLLOWS:
Section 1. A Construction Contract in an amount not to exceed $2,991,182 is awarded to Mesa Energy Systems, Inc. to complete the Ballroom B HVAC and Lighting Systems Project at the SAFE Credit Union Convention Center.
Section 2. The City Manager or City Manager’s designee is authorized to execute the Construction Contract with Mesa Energy Systems, Inc.
Section 3. The Ballroom B HVAC and Lighting Systems Project (M17101900) is established as a new Capital Improvement Project.
Section 4. The Plans and Specifications for the Ballroom B HVAC and Lighting Systems Project are approved.
Section 5. The City Manager or City Manager’s designee is authorized to transfer $4,500,000 (Community Center Fund, Fund 6010) from the expenditure budgets of the following capital improvement projects to the expenditure budget of the Ballroom B HVAC and Lightings Systems Project (M17101900):
Project Description CIP # Fund – Fund Name Amount
Community Center Improvements M17100000 6010 – Community Center
$1,100,000
Convention Center Audio-Visual
Improvements
M17100300 6010 – Community
Center
$140,000
Convention Center Chiller
Upgrade
M17100500 6010 – Community
Center
$50,000
Memorial Auditorium
Improvements
M17101000 6010 – Community
Center
$955,000
Convention Center Durable
Equipment Replacement
M17101600 6010 – Community
Center
$145,000
Convention Center Production
Equipment Upgrades
M17101700 6010 – Community
Center
$2,110,000
TOTAL $4,500,000
/0/1/2/3/4/5/0/3/i255
/4/1/7/3/8/2/9/i255/10/11/12/12/3/i255
/13/14/15/16/17/18/19/16/i255/13/14/21/22/17/23/24/14/25/16/26/15/27/i255/28/14/17/29/30/i255/31/25/32/16/i255/33/19/19/14/29/34/18/15/35/i255/33/36/36/i255/13/14/15/16/17/18/19/16/32/37/i255/38/14/39/22/21/22/17/40/i255/26/16/i255/26/32/i255/41/42/43/i255/34/18/17/16/i255/14/44/i255/16/38/22/i255/19/14/15/16/17/18/19/16/45/i255 /9/46/47/46/48/49/50/i255/8/47/51/52/48/53/49/54/55/52/47/i255/56/4/46/57/58/55/48/46/59/60/i255 /61/62/63/64/63/65/66/67/i255/69/70/65/71/62/66/72/71/i255/73/i255/74/75/76/77/77/67/78/79/78/65/71/75/i255/70/65/67/80/81/82/i255/83/83/83/83/83/83/83/83/i255/i255/i255/84/76/77/77/67/78/79/78/65/71/85/86/87/87/78/65/87/76/79/i255/73/82/i255/i255/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/i255 /86/75/75/78/75/75/70/62/88/75/i255/89/66/62/72/78/67/i255/90/76/79/91/78/62/74/75/81/82/i255/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83 /69/70/65/71/62/66/72/71/i255/92/93/93/78/72/71/63/94/78/i255/95/66/71/78/82/i255/83/83/83/83/83/83/83/83/83/i255/i255/i255/i255/69 /70/65/71/62/66/72/71/i255/92/96/77/63/62/66/71/63/70/65/i255/95/66/71/78/i255/74/63/93/i255/66/77/77/67/63/72/66/91/67/78/81/82/i255/83/83/83/83/83/83/83/83/83/i255 /97/i255/86/79/70/76/65/71/i255/74/90/70/71/i255/71/70/i255/92/96/72/78/78/87/81/82/i255/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/i255/86/87/98/76/75/71/78/87/i255/97/i255/86/79/70/76/65/71/i255/74/99/85/100/81/82/i255/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/i255 /61/71/101/78/62/i255/89/66/62/71/80/82/i255/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/i255 /89/62/70/98/78/72/71/i255/102/63/71/67/78/82/i255/i255/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/i255 /89/62/70/98/78/72/71/i255/73/82/i255/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/i255/103/63/87/85/104/105/106/85/104/105/89/i255/73/82/i255/i255/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/i255 /69/63/71/80/i255/69/70/76/65/72/63/67/i255/86/77/77/62/70/94/66/67/82/i255/63 /93/i255/107/92/84/108/i255/69/70/76/65/72/63/67/i255/105/63/67/78/i255/109/95/73/82/i255/83/83/83/83/83/83/83/83/83/83/i255 /0/52/47/54/48/49/111/54/i255/112/48/52/111/46/113/113/55/47/114/i255/0/52/47/54/49/111/54/113/i255 /95/78/77/66/62/71/79/78/65/71/82/i255/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/i255 /69/70/65/71/62/66/72/71/i255/69/70/70/62/87/63/65/66/71/70/62/82/i255/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/i255 /89/62/70/98/78/72/71/i255/115/66/65/66/64/78/62/82/i255/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83 /116/117/118/119/120/121/i255/123/123/123/123/123/123/123/123/123/123/123/123/123/123/123/123/123/123/123/123/123/123/123/123/83/83/83/83/83/83/i255 /124/46/125/49/48/54/53/46/47/54/i255/4/46/126/55/46/127/i255/49/47/59/i255/4/52/58/54/55/47/114/i255 /74/84/63/64/65/66/71/76/62/78/81/i255 /74/95/66/71/78/81/i255 /74/84/63/64/65/66/71/76/62/78/81/i255 /74/95/66/71/78/81/i255 /74/84/63/64/65/66/71/76/62/78/81/i255 /74/95/66/71/78/81/i255 /128/129/129/130/131/132/133/134/132/135/136/i255
/138/131/139/140/141/142/134/143/130/141/136/i255/i255
/144/134/142/134/143/134/130/132/i255/145/146/132/146/135/140/141/136/i255/i255 /147/133/148/140/141/136/i255
/74/84/63/64/65/66/71/76/62/78/81/i255 /74/95/66/71/78/81/i255 /10/125/46/111/55/49/50/i255/8/47/113/54/48/58/111/54/55/52/47/149/0/52/53/53/46/47/54/113/i255/56/55/150/46/150/i255/48/46/111/52/48/59/55/47/114/i255/48/46/57/58/46/113/54/46/59/151/i255/52/54/152/46/48/i255/49/114/46/47/111/153/i255/113/55/114/47/49/54/58/48/46/113/i255/48/46/57/58/55/48/46/59/151/i255/46/54/111/150/60/i255 /83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/83/i255 /155/155/155/155/155/155/155/155/155/155/155/155/155/155/155/155/155/155/28/42/24/i255/13/36/156/24/157/i255/158/i255/159/43/i255/160/156/161/33/24/43/31/156/41/43/162/i255/42/41/36/163/i255/164/i255/160/42/i255/41/42/43/i255/165/24/159/43/156/i255/166/156/36/42/165 /i255/43/167/159/162/i255/36/159/41/156/155/155/155/155/155/155/155/155/155/155/155/155/155/155/155/155/155/155/i255 /168/168/i255/170/171/172/173/i255/174/175/176/174/177/173/178/179/180/181/i255 /183/184/185/186/187/188/189/190/191/i255/183/184/193/194/184/195/196/184/188 /197/196/198/184/187/i255/199/200/187/196/201/i255/202/189/191/190/200/196/194/187/184/i255/183/184/193/194/189/187/184/188 /203/204/205/203/206/205/207/203/207/204
/208/i255/207/210/211/211/212/210/212/213/207/214/203/203 /215/216/217/218/i255/219/220/216/221/222/223/i255/224/223/217/225/216/226/217/210/i255/227/220/228/214 /229/218/230/230/221/231/231/226/i255/229/i255/232/233/234/235/i255/218/220/236/i255/237/238/222/239/225/238/220/222/i255/224/223/217/225/216/226/217 /215/212/206/212/203/212/211/203/203 /229/207/204/212/206/212/212/204/212/203/203/240 /207/203/207/204/241/203/203/203/242/204
/215/218/228/243/i255/224/226/238/225/239
/224/225/216/244/216/220/i255/224/218/243/218/243/238/239/218/221/218 /217/239/217/218/243/218/243/238/239/218/221/218/245/228/238/225/223/231/246/217/218/228/221/218/226/216/220/225/231/214/231/221/222 /247/219/224
/235/231/220/244/216/220/225/238/231/220/i255/248/i255/235/249/230/225/249/221/218/230/i255/224/216/221/244/238/228/216/217
CALIFORNIA
STATE CAPITOL
SACRAMENTO
CONVENTION CENTER
(THIS PROJECT)
K ST.
J ST.
L ST.
13 TH
14 TH
15 THTHEATRE
AUDITORIUM
VICINITY MAP
TRUE NORTH PROJECT NORTH
PROJECT NO.
Copyright C
ISSUED BY:
ISSUED DATE:
SHEET TITLE:
DISCIPLINE - CATEGORY - SUB CATEGORY - SHEET
REVISIONS
®
TM
®
®
ARCHITECT OF RECORD
POPULOUS
4800 Main Street Suite 300
Kansas City, MO 64112
816-221-1500
HVAC and LIGHTING ENGINEER
HENDERSON ENGINEERS
8345 Lenexa Drive
Lenexa, KS 66214
913-742-5000
Sacramento Convention Center Ballroom B Upgrades
September 8, 2021
9/7/2021 11:22:11 AM
1400 J St, Sacramento, CA 95814
CONSTRUCTION
DOCUMENTS
COVER SHEET
X1-1
17.4465
09/08/21
2019
CONVENTION CENTER BALLROOM B UPGRADES
SACRAMENTO, CALIFORNIA
CONSTRUCTION DOCUMENTS
SEPTEMBER 8, 2021
Sheet Index
GENERAL INFORMATION
X1-1 COVER SHEET
ARCHITECTURE
A1-1 PROJECT INFORMATION
A1-2 BALLROOM B RCP
MECHANICAL
M0-0 MECHANICAL GENERAL NOTES AND LEGENDS
M0-1 TITLE 24 COMPLIANCE
MD1-2 HVAC DEMO BALLROOM B
M1-2 HVAC PLAN BALLROOM B
M2-1 MECHANICAL ENLARGED PLANS
M3-1 MECHANICAL DETAILS, SCHEDULES AND CONTROLS
MPD1-2 PIPING DEMO BALLROOM B
MP1-2 PIPING PLAN BALLROOM B
ELECTRICAL LIGHTING
E0-0 ELECTRICAL NOTES, SYMBOLS & ABBREVIATIONS
E0-1 TITLE 24 COMPLIANCE FORMS
E0-2 TITLE 24 COMPLIANCE FORMS
E0-3 TITLE 24 COMPLIANCE FORMS
ED1-1 LIGHTING DEMO PLAN BALLROOM B
E1-1 ELECTRICAL SCHEDULES, CONTROLS AND DETAILS
E1-2 LIGHTING PLAN BALLROOM B
E2-1 LIGHTING DETAILS
NO. DATE DESCRIPTION
UP
UP UP
J
MC
JMC
J
J
J
S
S
VITREOUS CHINA C_URINALSDEXTER
K-5016-ET
GE NERAL NOTES
1.T H ESE AS-BUILT RESTROOMS A RE CREATED FROM ON-SITEMEASUREMENTS OF EXISTING CONDITIONS.
2.D I MENSIONS SHOW N ARE TO FACE OF FINISHES (F.F.), UNLESSOTHER WISE NOTED.
SACRAME NTO CONVENTION CENTER
1400 J St, Sacram ento, CA 95814
SACRAME NTO CONVENTION CENTER
1400 J St, Sacram ento, CA 95814
```
VITREOUS CHINAC_URINALSDEXTERK-5016-ETVITREOUS CHINAC_URINALSDEXTERK-5016-ET VITREOUS CHINAC_URINALSDEXTERK-5016-ET VITREOUS CHINAC_URINALSDEXTERK-5016-ET VITREOUS CHINAC_URINALSDEXTERK-5016-ET VITREOUS CHINAC_URINALSDEXTERK-5016-ETVITREOUS CHINAC_URINALSDEXTERK-5016-ET VITREOUS CHINAC_URINALSDEXTERK-5016-ET
FD
FD
UP
GE NERAL NOTES
1.T H ESE AS-BUILT RESTROOMS A RE CREATED FROM ON-SITEMEASUREMENTS OF EXISTING CONDITIONS.
2.D I MENSIONS SHOW N ARE TO FACE OF FINISHES (F.F.), UNLESSOTHER WISE NOTED.
SACRAME NTO CONVENTION CENTER
1400 J St, Sacram ento, CA 95814
ACOUST ACOUSTICAL
ADJ ADJUSTABLE
AFF ABOVE FINISH FLOOR
AP ACCESS PANEL
APPROX APPROXIMATE
ARCH ARCHITECTURAL
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BM BEAM
CJ CONTROL JOINT
CLG CEILING
COL COLUMN
CONT CONTINUOUS
CONTR CONTRACTOR
DIM DIMENSION
DN DOWN
DR DOOR
DTL DETAIL
DWG(S) DRAWING(S)
EE A S T
EA EACH
EE L E V A T I O N
ELEC ELECTRICAL
EQ EQUAL
EQUIP EQUIPMENT
ETR EXISTING TO REMAIN
EXP EXPANSION
EXIST EXISTING
FIN FINISH
FURR FURRING
FV FIELD VERIFY
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GYP BD GYPSUM BOARD
HM HOLLOW METAL
HORIZ HORIZONTAL
HT HEIGHT
ID INSIDE DIAMETER / DIMENSION
IN INCH
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
JST JOIST
MAX MAXIMUM
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED
NN O R T H
N / A NOT APPLICABLE
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER / DIMENSION
OH OPPOSITE HAND
OVHD OVERHEAD
PLYWD PLYWOOD
PTD PAINTED
QTY QUANTITY
R RISER OR RADIUS
RCP REFLECTED CEILING PLAN
REQ'D REQUIRED
REV REVISION
RM ROOM
RO ROUGH OPENING
SS O U T H
SC SOLID CORE
SCHED SCHEDULE
SECT SECTION
SF SQUARE FOOT (FEET)
SP SPACING
SPEC SPECIFICATION
SPHD SPRINKLER HEAD
SPKR SPEAKER
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STL STEEL
STOR STORAGE
SY (SQ YD) SQUARE YARD(S)
T&G TONGUE AND GROOVE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
W / WITH
W / I WITHIN
W / O WITHOUT
WD WOOD
DIMENSIONING CRITERIA
PARTITION
All drawings are intended to be complementary. Notify the architect of any dimensioning discrepancy prior to proceeding.
Dimensions are to outside face of gypsum board/stud walls.
Dimensions are as identified on the documents or as established by criteria as follows:
1. DIMENSIONS WILL NOT BE SHOWN FOR THE FOLLOWING CONDITIONS:
-When partition is centered on grid line.
-When partition is shown flush with column face.
-When partition is shown flush with grid line.
-when partition is centered on glazing mullion.
2. MASONRY/METAL STUD WALLS ARE DIMENSIONED FROM FINISHED FACE. 4" TYPICAL FOR STUD PARTITIONS
-When one jamb is located adjacent to a column, the following diagram applies:
8" TYPICAL - FOR MASONRY PARTITIONS
4" TYPICAL - FOR STUD PARTITIONS
PARTITION
COLUMN
(UNLESS NOTED OTHERWISE)
(UNLESS NOTED OTHERWISE)
& CONCRETE
(UNLESS NOTED OTHERWISE)
3. FOR OPENINGS IN PARTITIONS OR WALLS: (OPENINGS, DOOR, WINDOW, LOUVER) -When an opening occurs at gridline, no dimensions will be shown, Width will be established by either criteria or schedules.
-When neither jamb occurs at a partition intersection, at a column or at a gridline; one jamb will be located dimensionally by the detail. -When one jamb is located adjacent to a partition intersection, the following diagram applies:
INTERSECTING PARTITION
DOOR AS SCHEDULED
X
X
DETAIL REFERENCE SYMBOLS
GRAPHIC SYMBOL STANDARDS
BUILDING/WALL SECTION REFERENCE SYMBOL
INTERIOR ELEVATION/DETAIL SYMBOL
DETAIL SYMBOL
4 1A6-3
A8-1
1 NOTE
A7-3
1 NOTE
A8-2
1 NOTE
AREA TO BE DETAILED
Detail Number (Detail 1) On Sheet A8-1
Discipline (Architecture)
Sheet Number
Detail Number (Drawing 1 On Sheet A7-3)
Discipline (Architecture)
Drawing Category
Sheet Number
Detail Number (Drawing 4 On Sheet A6-3)
Discipline (Architecture)
Drawing Category
Sequential Sheet Number
3 4
1 2
A6-3
NOTE
Detail Number (Detail 1) On Sheet A8-2
Discipline (Architecture)
Drawing Category (Details = 8)
Sequential Sheet Number
COLUMN AND / OR GRID LINES
A
1 16'0 32'8'
NORTH
0' - 0"
Level 1
0' - 0"
8" TYPICAL FOR MASONRY PARTITIONS
1 FLOOR ELEVATION LEVEL SYMBOL
CENTERLINE SYBMOL / GRID LINE
GRAPHIC SCALE SYMBOL
NORTH ARROW SYMBOL
SPOT ELEVATION SYMBOL
Drawing Category
REVISION SYMBOL
Area Revised
Revision Number
ROOM / SPACE IDENTIFICATION SYMBOL
1B.02
ROOM NAME
Building Level
Room Number
Area / Sector
ABBREVIATIONS
1 EW EZ
9 9
18 18
50 50
59 59
77 Q AZ BR ED EK EQ
5 1
34 34
J ST.
13TH ST.
14TH ST.
K ST.
15TH
ST.
12345 6 7 89 1 0 1 1 1 2
CHURCH
AA
SJSA
SW5
SD
UPUP
SXEZ.1
SW2.5
COMMUNITY CENTER
THEATER
EXHIBIT HALL DEXHIBIT HALL CEXHIBIT HALL BEXHIBIT HALL A
NORTH LOBBY
EAST
LOBBY
WEST
LOBBY
NOTE: There is no scope of work on
this level. Shown for reference only.
EW
EW EZ
9 9
18 18
50 50
59 59
65 Q AZ BR
ED
ED
EK
EK
EQ
EQ
5 1
34 34
CHURCH
OPEN TO
BELOW
OPEN TO BELOW
AA
SJSASW5 SD
EAST
TERRACE
OPEN TO
BELOW
DN
DNDN
SXEZ.1
SW2.5
BALLROOM BBALLROOM A
Legend:
Extent of Work
Extent of Work for Ballroom B:
1) Lay-in acoustical ceiling replacement - Refer to A1-2. 2) Gypsum board ceiling selective demolition and replacement - Refer to A1-2. 3) Terminal air unit upgrades - Refer to Mechancial.
4) Lighting upgrades - Refer to Electrical.
MEETING ROOMS 1-4
MTG ROOMS 5-8
MTG ROOMS 9-11
MTG ROOMS 12-16
A1-2
1 PROJECT NO.
Copyright C
ISSUED BY:
ISSUED DATE:
SHEET TITLE:
DISCIPLINE - CATEGORY - SUB CATEGORY - SHEET
REVISIONS
PROJECT NORTH
®
TM
®
®
ARCHITECT OF RECORD
POPULOUS
4800 Main Street Suite 300
Kansas City, MO 64112
816-221-1500
HVAC and LIGHTING ENGINEER
HENDERSON ENGINEERS
8345 Lenexa Drive
Lenexa, KS 66214
913-742-5000
Sacramento Convention Center Ballroom B Upgrades
September 8, 2021
9/8/2021 10:20:26 AM
1400 J St, Sacramento, CA 95814
CONSTRUCTION
DOCUMENTS
PROJECT
INFORMATION
A1-1
17.4465
09/08/21
2019
1/2" = 1'-0"A1-1
1 ABBREVIATIONS, LEGENDS, AND GENERAL
NOTES
1" = 50'-0"A1-1
2 01 - GROUND LEVEL REFERENCE PLAN
1" = 50'-0"A1-1
3 02 - UPPER LEVEL REFERENCE PLAN
NO. DATE DESCRIPTION
18 25
43 50
ED EF EG EH EK EM EN EO EQ
34 MEN
E2E27
STAIR 13
E2FST13
JAN
E2F50OPERABLE WALL STORAGE
303
E2F32
PREFUNCTION
E2D01
OPERABLE WALL STORAGE
306
E2F30
OPERABLE WALL STORAGE
304
E2F31
OPERABLE WALL STORAGE
308
E2F29
OPERABLE WALL STORAGE
311
E2F28
SERVICE CORRIDOR
E2F37
OPERABLE WALL STORAGE
321
E2C09
OPERABLE WALL STORAGE
323
E2C10
OPERABLE WALL STORAGE
326
E2C11
OPERABLE WALL STORAGE
330
E2C12
OPERABLE WALL STORAGE
331
E2C13 JAN
E2C47
WOMEN
E2C21
PREFUNCTION
E2D01
BALLROOM B
E2C4625' - 0" FV
25' - 1" FV 25' - 11" FV 26' - 8" FV 26' - 10" FV DIFFUSER ETR
DIFFUSER ETR
DIFFUSER ETRDIFFUSER ETR
DIFFUSER ETR DIFFUSER ETR
DIFFUSER ETR DIFFUSER ETR
DIFFUSER ETR
25' - 1" FV26' - 8" FV25' - 11" FV26' - 10" FV
28' - 6" FV
28' - 6" FV
25' - 6" FV
31' - 6" FV
25' - 6" FV 25' - 6" FV 25' - 6" FV 25' - 6" FV
31' - 6" FV31' - 6" FV
31' - 6" FV
25' - 6" FV
SSSSSSSS
SS S S SS SS
S S SS SS S S
S S SS SS S S
SS S S SS SS
SSSSSSSS
OPERABLE PARTITION ETR
OPERABLE PARTITION ETR
SLOPE DOWN
SLOPE DOWN
SLOPE DOWN
SLOPE DOWN
SLOPE DOWN
SLOPE DOWN
SLOPE DOWN
SLOPE DOWN
31' - 6" FV31' - 6" FV
2'-0" FULL TILE
AS REQUIRED
CUT TILE
HALF TILE
1' - 0"
FULL TILE
2' - 0"
HALF TILE
1' - 0"
FULL TILE
2' - 0"
HALF TILE
1' - 0"
HALF TILE
1' - 0"
FULL TILE
2' - 0"
FULL TILE
2' - 0"
1'-0" HALF TILE TO ALIGN WITH
GYPSUM BOARD CEILING, TYP.
ALIGN
ALIGN
2'-0" FULL TILE
AS REQUIRED
CUT TILE
GYPSUM BOARD CEILING ETR
REPLACE LAY-IN CEILING SYSTEM, TYP.
NEW LAYOUT TO MATCH EXISTING.
NEW CEILING SYSTEM TO MATCH
EXISTING, CONTRACTOR TO VERIFY
PRODUCT WITH OWNER. REINSTALL
CEILING DEVICES AS REQUIRED.
HALF TILE
1' - 0"
FULL TILE
2' - 0"
HALF TILE
1' - 0"
31' - 6" FV 31' - 6" FV
REMOVE EXISTING GYPSUM BOARD
CEILING AS REQUIRED FOR TAU
WORK ABOVE CEILING. PROVIDE
NEW GYPSUM BOARD AT SAME
ELEVATION AS EXISTING PAINTED TO
MATCH EXISTING. REINSTALL
CEILING DEVICES AS REQUIRED.
PREFUNCTION
E2D01
GYPSUM BOARD CEILING ETR
LIGHT BOX TO BE REMOVED AND
REINSTALLED, TYP. RE: 2/A1-2
-
---
3 A1-2
EXISTING
LIGHT COVE
ACOUSTICAL CEILING TILE
GYPSUM BOARD - EXISTING TO REMAIN
2' X 2' LAY-IN-GRID
1' X 2' LAY-IN-GRID
CEILING SPEAKER - EXISTING TO REMAIN
LIGHT FIXTURE - TO BE REPLACED, REFER TO ELECTRICAL
FIRE SPRINKLER HEAD - EXISTING TO REMAIN
RIGGING POINT - EXISTING TO REMAIN
SUPPLY DIFFUSER - EXISTING TO REMAIN
RETURN AIR GRILLE OR EXHAUST - EXISTING TO REMAIN
OPERABLE PARTITION & TRACK - EXISTING TO REMAIN
S
GYPSUM BOARD
PROJECT NO.
Copyright C
ISSUED BY:
ISSUED DATE:
SHEET TITLE:
DISCIPLINE - CATEGORY - SUB CATEGORY - SHEET
REVISIONS
PROJECT NORTH
®
TM
®
®
ARCHITECT OF RECORD
POPULOUS
4800 Main Street Suite 300
Kansas City, MO 64112
816-221-1500
HVAC and LIGHTING ENGINEER
HENDERSON ENGINEERS
8345 Lenexa Drive
Lenexa, KS 66214
913-742-5000
Sacramento Convention Center Ballroom B Upgrades
September 8, 2021
9/8/2021 10:25:24 AM
1400 J St, Sacramento, CA 95814
CONSTRUCTION
DOCUMENTS
BALLROOM B RCP
A1-2
17.4465
09/08/21
2019
1/8" = 1'-0"A1-2
1 BALLROOM B RCP
GENERAL NOTES:
RCP LEGEND:
SCOPE OF WORK IS TO REPLACE THE EXISTING LAY-IN CEILING SYSTEM IN BALLROOM B. THIS INCLUDES NEW CEILING TILE, GRID AND ANY REQUIRED SEISMIC BRACING. THE NEW CEILING SYSTEM IS TO BE INSTALLED TO MATCH EXISTING LAYOUT AND ELEVATIONS. CEILING LAYOUT AND ELEVATIONS SHOWN ARE BASED ON AS-BUILT DRAWINGS. CONTRACTOR IS RESPONSEBLE FOR FIELD VERIFIYING EXISTING CONDITIONS.
THERE IS SELECTIVE DEMOLITION OF EXISTING GYPSUM BOARD CEILING AREAS REQUIRED IN ORDER TO WORK ABOVE CEILING, REFER TO RCP FOR LOCATIONS.
NEW GYPSUM BOARD CEILING IS TO BE INSTALLED TO MATCH EXISTING LAYOUT AND ELEVATIONS. PAINT TO MATCH EXISTING. THE EXTENT OF GYPSUM BOARD
CEILING TO REMAIN IN PLACE, SHADED AS GRAY, IS BASED ON AS-
BUILT DRAWINGS
AND SHOULD BE FIELD VERIFIED BY CONTRACTOR.
CEILING DEVICE LOCATIONS ARE BASED ON AS-BUILT DRAWINGS. CONTRACTOR IS
RESPONSIBLE FOR FIELD VERIFYING EXISTING LOCATIONS AND TO REINSTALL ALL EXISTING DEVICES AS REQUIRED WHERE CEILING SYSTEM IS REPLACED.
BALLROOM B CEILING EXISTING CEILING - VIEW LOOKING WEST BAL LROOM B CEILING EXISTING CEILING - VIEW LOOKING NORTH
LAY-IN CEILING SYSTEM
TO BE REPLACED
THROUGHOUT BALLROOM
GYPSUM BOARD CEILING AND
BULKHEAD TO REMAIN, TYP.
GYPSUM BOARD CEILING AND
BULKHEAD TO REMAIN, TYP.
FOR REFERENCE ONLY FOR REFERENCE ONLY
REINSTALL EXISTING CEILING
DEVICES AS REQUIRED, TYP.
OPERABLE PARTITION
AND TRACK TO REMAIN
LAY-IN CEILING SYSTEM TO BE
REPLACED THROUGHOUT BALLROOM
GYPSUM BOARD CEILING AND
BULKHEAD TO REMAIN, TYP.
EN 4343
EK
REMOVE AND REPLACE
GYPSUM BOARD CEILING
REMOVE AND REPLACE
GYPSUM BOARD CEILING
LIGHT BOX TO BE REMOVED FOR LIGHT
REPLACEMENT AND REINSTALLED, TYP.
REFER TO ELECTRICAL FOR
LIGHT REMOVAL AND
REPLACEMENT
EXISTING LIGHT BOX
FOR REFERENCE ONLY
2 A1-2
EXISTING LIGHT COVE
FOR REFERENCE ONLY
3 A1-2
REMOVE ACRYLIC
LENS COVER FOR
LIGHT REPLACEMENT
AND REINSTALL, TYP.
NO. DATE DESCRIPTION
PIPING LINETYPES
THERMOSTATS (USER ADJUSTABLE)
CONTROLS
46"
46"
PIPING SYMBOLSSTANDARD MOUNTING HEIGHT
MECHANICAL SYMBOLS
THIS IS A MASTER LEGEND AND NOT ALL SYMBOLS OR ABBREVIATIONS ARE USED. V2.07
HVAC DUCTWORK AND ACCESSORIES
1 ANNOTATION
MECHANICAL PLAN NOTE CALLOUT
MECHANICAL EQUIPMENT DESIGNATION (CONTRACTOR
FURNISHED AND INSTALLED UNLESS NOTED OTHERWISE)
CONNECTION POINT OF NEW WORK TO EXISTING
DETAIL REFERENCE. UPPER NUMBER INDICATES DETAIL
NUMBER LOWER NUMBER INDICATES SHEET NUMBER
SECTION CUT DESIGNATION
DEDICATED EQUIPMENT ACCESS TILE
ACCESS PANEL
INSTALL DEVICES AT THE MOUNTING HEIGHTS SHOWN ABOVE UNO IN THE CONSTRUCTION DOCUMENTS. MOUNTING HEIGHTS LISTED ABOVE OR
ELSEWHERE IN THE CONSTRUCTION DOCUMENTS ARE AFF OR AFG TO TOP OF THE DEVICE UNO. ALL DEVICES SHALL BE INSTALLED IN COMPLIANCE WITH CURRENT ADA AND LOCAL REQUIREMENTS.
ABBREVIATIONS
A/C
ACC
ACCU
AFC
AFF
AFG
AHJ
AHU
AI
AO
AP
APD
AWG
B
BAS
BB
BD
BD
BFC
BFF
BFG
BFP
BHP
BI
BO
BOD
BOS
BTU
CFM
CH
CLG
CP
CPT
CRAC
CRU
CT
CV
CWP
CU
CHWP
DB
DBA
DDC
DI
DISC
DN
DS
DX
(E)
EA
EAT
ED
EDB
EF
EFF
EMS
ESP
ETR
EWB
EWT
FCU
FFA
FFB
FF
FPI
FPM
GC
GPM
HOA
HP
HTG
AIR CONDITIONING
AIR COOLED CHILLER
AIR COOLED CONDENSING
UNIT
ABOVE FINISHED CEILING
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AUTHORITY HAVING
JURISDICTION
AIR HANDLING UNIT
ANALOG INPUT
ANALOG OUTPUT
ACCESS PANEL
AIR PRESSURE DROP
AMERICAN WIRE GAUGE
BOILER
BUILDING AUTOMATION
SYSTEM
BACKBONE
BACKDRAFT DAMPER
BLOWDOWN
BELOW FINISHED CEILING
BELOW FINISHED FLOOR
BELOW FINISHED GRADE
BOILER FEED PUMP
BRAKE HORSEPOWER
BINARY INPUT
BINARY OUTPUT
BOTTOM OF DUCT
BOTTOM OF STRUCTURE
BRITISH THERMAL UNIT
CUBIC FEET PER MINUTE
CHILLER
COOLING
CONDENSATE PUMP
CONTROL POWER
TRANSFORMER
COMPUTER ROOM AIR
CONDITIONING UNIT
COMPUTER ROOM UNIT
COOLING TOWER
CONTROL VALVE
CONDENSER
WATER PUMP
CONDENSING UNIT
CHILLED WATER PUMP
DECIBELS
DECIBEL AVERAGE
DIRECT DIGITAL CONTROL
DIGITAL INPUT
DISCONNECT
DOWN
DUCT SILENCER
DIRECT EXPANSION
EXISTING
EXHAUST AIR
ENTERING
AIR TEMPERATURE
EXHAUST DUCT
ENTERING DRY BULB
EXHAUST FAN
EFFICIENCY
ENERGY MANAGEMENT
SYSTEM
EXTERNAL STATIC
PRESSURE
EXISTING TO REMAIN
ENTERING WET BULB
ENTERING WATER
TEMPERATURE
FAN COIL UNIT
FROM FLOOR ABOVE
FROM FLOOR BELOW
FINISHED FLOOR
FINS PER INCH
FEET PER MINUTE
GENERAL CONTRACTOR
GALLONS PER MINUTE
HAND-OFF-AUTOMATIC
HORSEPOWER
HEATING
HWP
IN WC
L
LAT
LDB
LP
LWB
LWT
MAU
MAX
MBH
MD
MFR
MIN
N/A
N/C
N/O
NOM
NC
NF
NIC
OA
PICV
PROVIDE
QTY
RA
RC
RD
REA
RF
RFR
RH
RH
RPM
RTU
SA
SCP
SD
SD
SF
SH
SOW
SP
ST
STM
TBD
TC/C
TCP
TF
TFA
TFB
TH
TSP
TT
TYP
U/F
U/G
U/S
UH
UNO
VAV
VEL
VFD
VRF
VRV
W/
W/O
WB
WC
WPD
XP
HEATING WATER PUMP
INCHES OF WATER
COLUMN
LOUVER
LEAVING AIR
TEMPERATURE
LEAVING DRY BULB
LOW PRESSURE
LEAVING WET BULB
LEAVING WATER
TEMPERATURE
MAKE-UP AIR UNIT
MAXIMUM
1000 BTU PER HOUR
MOTORIZED DAMPER
MANUFACTURER
MINIMUM
NOT APPLICABLE
NORMALLY CLOSED
NORMALLY OPEN
NOMINAL
NOISE CRITERIA
NON-FUSED
NOT IN CONTRACT
OUTSIDE AIR
PRESSURE INDEP.
CONTROL VALVE
FURNISH AND INSTALL
QUANTITY
RETURN AIR
ROOM CRITERIA
RETURN DUCT
RELIEF AIR
RETURN FAN
REFRIGERANT
RELATIVE HUMIDITY
ROOF HOOD
REVOLUTIONS PER MINUTE
ROOFTOP UNIT
SUPPLY AIR
STEAM CONDENSATE PUMP
SMOKE DUCT DETECTOR
SUPPLY DUCT
SUPPLY FAN
SENSIBLE HEAT CAPACITY
SCOPE OF WORK
STATIC PRESSURE
STEAM TRAP
STEAM
TO BE DETERMINED
TEMPERATURE CONTROLS
CONTRACTOR
TEMPERATURE CONTROL
PANEL
TRANSFER FAN
TO FLOOR ABOVE
TO FLOOR BELOW
TOTAL HEAT CAPACITY
TOTAL STATIC PRESSURE
TEMPERATURE
TRANSMITTAL
TYPICAL
UNDERFLOOR
UNDERGROUND
UNDERSLAB
UNIT HEATER
UNLESS NOTED OTHERWISE
VARIABLE AIR VOLUME
VELOCITY
VARIABLE FREQUENCY
DRIVE
VARIABLE REFRIGERANT
FLOW
VARIABLE REFRIGERANT
VOLUME
WITH
WITHOUT
WET BULB
WATER COLUMN
WATER PRESSURE DROP
EXPLOSION PROOF
1 M1
1 M1
CU
1 NPW
RL
CWR
CWS
HCR
HCS
CHWR
CHWS
HWR
HWS
LPC
LPS
HPC
FOV
FOR
FOS
BFW
HPS
LPG
G
MPG
G
MPG
CD
ACD
CPD
RD
RDB
RV
RS
AV
MV
DIRECTION OF FLOW
CONTROL VALVE
THREE-WAY CONTROL VALVE
SHUTOFF VALVE
CHECK VALVE
BALANCING VALVE WITH PRESSURE PORTS
TRIPLE DUTY VALVE WITH PRESSURE PORTS
STRAINER
STRAINER WITH BLOWDOWN VALVE
RELIEF / SAFETY VALVE
SOLENOID VALVE
PRESSURE REDUCING VALVE
GAS PRESSURE REGULATOR
THERMOSTATIC MIXING VALVE
PIPE ANCHOR
EXPANSION JOINT
PIPE GUIDE
PIPING SUPPORT
F & T TRAP
BUCKET TRAP
THERMOSTATIC TRAP
BACKFLOW PREVENTER
PRESSURE GAUGE
THERMOMETER
PRESSURE AND TEMPERATURE TEST PLUG
UNION
FLANGE CONNECTION
VACUUM RELIEF VALVE
AUTOMATIC AIR VENT
MANUAL AIR VENT
PRESSURE / VACUUM SWITCH
CLEANOUT
CAP
ELBOW UP
ELBOW DOWN
TEE UP
TEE DOWN
ELBOW UP WITH SHUT-OFF VALVE (SOV)
ELBOW DOWN WITH SHUT-OFF VALVE (SOV)
TEE UP WITH SHUT-OFF VALVE (SOV)
TEE DOWN WITH SHUT-OFF VALVE (SOV)
REDUCER
RECIRCULATION PUMP
P-TRAP
GAS COCK
TOP BEAM CLAMP
TRAPEZE HANGER
FLEXIBLE CONNECTION
PA
HUMIDISTAT
THERMOSTAT
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
DIFFERENTIAL PRESSURE SENSOR
FLOW SWITCH
HUMIDITY SENSOR
PULL STATION
REMOTE TESTING STATION WITH INDICATING LIGHT
STATIC PRESSURE
TEMPERATURE SENSOR
T
H
CO
FS
PS
DP
CO2
HVAC CONTROL DEVICES
HS
LINETYPE LEGEND
THROUGHOUT THE DRAWINGS DIFFERENT LINETYPES ARE USED IN
COMBINATION WITH THE SYMBOLS TO INDICATE THE STATUS OF ITEMS AS
EXISTING, TO BE DEMOLISHED, TO BE INCLUDED AS PART OF NEW WORK AND/OR ITEMS WHICH ARE ANTICIPATED TO BE PROVIDED IN THE FUTURE.
THE STATUS OF ITEMS USING THESE LINETYPES ARE RELATIVE TO THE VIEW IN WHICH THEY APPEAR. PHASING SHOWN IN DRAWINGS IS NOT
INTENDED TO FULLY DESCRIBE ALL NECESSARY CONSTRUCTION PHASING,
WHICH IS DETERMINED BY THE CONTRACTOR AS PART OF THEIR
RESPONSIBILITIES. ANY SUCH PHASES DESCRIBED IN THE CONSTRUCTION
DOCUMENTS ARE GENERAL AND ONLY INTENDED TO INDICATE A BROAD ORDER FOR THE SAKE OF DESCRIBING THE PROJECT. THE FOLLOWING
LINETYPES MAY BE USED ON ANY DEVICE, EQUIPMENT, NOTE, LINE, SHAPE, ETC.
EXISTING
DEMOLISH
NEW
FUTURE
RT
TS
SP
EXISTING PIPING TO BE REMOVED OR RELOCATED
EXISTING PIPING TO REMAIN
CONDENSATE DRAIN (CD)
AUXILIARY CONDENSATE DRAIN (ACD)
NON-POTABLE WATER (NPW)
NATURAL GAS (G)
NATURAL GAS ON ROOF (G)
MEDIUM PRESSURE NATURAL GAS (MPG)
MEDIUM PRESSURE NATURAL GAS ON ROOF (MGP)
FUEL OIL SUPPLY (FOS)
FUEL OIL RETURN (FOR)
FUEL OIL VENT (FOV)
LIQUEFIED PETROLEUM GAS (LPG)
BOILER FEED WATER (BFW)
HIGH PRESSURE STEAM SUPPLY (HPS)
HIGH PRESSURE STEAM CONDENSATE (HPC)
LOW PRESSURE STEAM SUPPLY (LPS)
LOW PRESSURE STEAM CONDENSATE (LPC)
CONDENSATE PUMP DISCHARGE (CPD)
HEATING HOT WATER SUPPLY (HWS)
HEATING HOT WATER RETURN (HWR)
CHILLED WATER SUPPLY (CHWS)
CHILLED WATER RETURN (CHWR)
HOT / CHILLED WATER SUPPLY (HCS)
HOT / CHILLED WATER SUPPLY (HCR)
CONDENSER WATER SUPPLY (CWS)
CONDENSER WATER RETURN (CWR)
REFRIGERANT LIQUID (RL)
REFRIGERANT DISCHARGE (HOT GAS) (RD)
REFRIGERANT SUCTION (RS)
REFRIGERANT DISCHARGE BYPASS (RDB)
REFRIGERANT VENT (RV)
LINEAR SLOT DIFFUSER
INSULATED FLEXIBLE DUCT (MAX. 5'-0" LONG)
BRANCH DUCT WITH 45° RECTANGLE-ROUND
BRANCH FITTING AND MANUAL VOLUME DAMPER
ELBOW WITH TURNING VANES
BRANCH DUCT WITH BELL-MOUTH FITTING &
MANUAL VOLUME CONTROL DAMPER
DUCT UP
DUCT DOWN
EXHAUST AIR
EXHAUST AIR - GREASE
OUTSIDE AIR
RELIEF AIR
RETURN AIR
SPECIAL EXHAUST
SUPPLY AIR
EQUIPMENT WITH FLEXIBLE DUCT CONNECTION
10" (NECK SIZE)
CSD-1 (TYPE)
300 CFM (CFM OF SUPPLY DIFFUSER OR REGISTER)
24x24 (NECK SIZE)
CEG-1 (TYPE)
800 CFM (CFM OF EXHAUST GRILLE)
EQUIPMENT ACCESS TILE (IN ACT CEILINGS)
ACCESS PANEL (IN GYPSUM)
MANUAL VOLUME DAMPER
SQUARE TO ROUND TRANSITION
DUCT MOUNTED SMOKE DETECTOR
(SD=SUPPLY/RD=RETURN)
ROUND DUCT TAG INDICATING DIAMETER
RECTANGULAR DUCT TAG INDICATING INTERNAL
DUCT DIMENSIONS.
FLAT OVAL DUCT TAG INDICATING INTERNAL DUCT
DIMENSIONS
RISER DESIGNATION
FIRE DAMPER
FIRE SMOKE DAMPER
SMOKE DAMPER
VOLUME DAMPER
MOTORIZED DAMPER
BACKDRAFT DAMPER
FSD
SD
FD
VD
MD
BD
#
RD
ALL DUCT DIMENSIONS SHOWN ON DRAWINGS ARE INSIDE DIMENSIONS.
REFER TO DUCTWORK SPECIFICATIONS FOR DUCTWORK INSULATION AND LINER INFORMATION.
XX" Ø
XX" x XX"
XX' / XX"
EA
GEA
OA
REA
EA
XEA
SA
CALL OUTS
ENLARGED PLAN CALLOUT
NOT IN SCOPE
1. THE EXISTING CEILING PLENUM IS VERY CONGESTED WITH CEILING SUPPORT FRAMING THROUGHOUT THE CENTER SECTION OF THE BALLROOM. THE CONTRACTOR SHALL MAKE PROVISIONS TO INSPECT THE CEILING PLENUM PRIOR TO PROJECT BID. DUCT AND PIPE
ROUTING SHOWN ON THE DRAWINGS IS DIAGRAMATIC AND THE CONTRACTOR SHALL INCLUDE ALLOWANCE TO MAKE ROUTING
MODIFICATIONS TO AVOID CONCEALED FRAMING OTHER OBSTRUCTIONS WHICH MAY ONLY BECOME EVIDENT ONCE THE LAY-IN PORTIONS OF THE CEILING CAN BE REMOVED, ALLOWING FULL VIEW OF EXISTING CONDITIONS.
2. PRIOR TO SUBMITTING BID, VISIT THE JOB SITE AND BECOME FULLY ACQUAINTED WITH THE EXISTING CONDITIONS OF THE PROJECT.
REVIEW THE GENERAL NOTES, SPECIFICATIONS AND OTHER DRAWINGS FOR ADDITIONAL REQUIREMENTS WHICH MAY NOT BE SPECIFICALLY CALLED OUT IN THIS PORTION OF THE CONSTRUCTION DOCUMENTS. NOTIFY ARCHITECT, ENGINEER AND/OR OWNER OF CONFLICTS OR DISCREPANCIES PRIOR TO SUBMISSION OF BID.
3. EXISTING CONDITIONS WERE TAKEN FROM ORIGINAL DRAWINGS AND SITE VISITS AND MAY NOT REFLECT EXACT “AS-BUILT” CONDITIONS.
FIELD VERIFY EXISTING CONDITIONS PRIOR TO SUBMITTING FINAL BIDS. COORDINATE NEW WORK AND DEMOLITION WITH OTHER DISCIPLINES AND EXISTING CONDITIONS PRIOR TO CONSTRUCTION.
4. COORDINATE THE INSTALLATION OF THE MECHANICAL SYSTEMS WITH OTHER TRADES TO ENSURE A NEAT AND ORDERLY INSTALLATION.
INSTALL DUCTWORK AND PIPING AS TIGHT TO STRUCTURE AS POSSIBLE. COORDINATE WITH OTHER TRADES TO AVOID CONFLICTS.
COORDINATE INSTALLATION OF DUCTWORK AND PIPING TO AVOID CONFLICTS WITH ELECTRICAL PANELS, LIGHTING FIXTURES, ETC. ANY
MODIFICATIONS REQUIRED DUE TO LACK OF COORDINATION WILL BE THE RESPONSIBILITY OF THE CONTRACTOR AT NO EXTRA COST TO THE OWNER.
5. WHERE SHUTDOWN OF EXISTING SYSTEMS IS REQUIRED DURING NEW WORK, COORDINATE SHUTDOWN TIME AND DURATION WITH THE OWNER TO MINIMIZE DOWNTIME. NOTIFY OWNER SEVEN (7) DAYS PRIOR TO INTERRUPTION OF SERVICE.
6. DURING INSTALLATION OF NEW WORK, AVOID DAMAGING EXISTING SURFACES AND EQUIPMENT TO REMAIN. REPAIR DAMAGE CAUSED DURING CONSTRUCTION AT NO EXTRA COST TO THE OWNER.
7. PROVIDE TEMPORARY BARRIERS TO CONTAIN DUST AND DEBRIS RESULTING FROM THE PERFORMANCE OF THE WORK TO THE AREA WHERE WORK IS BEING PERFORMED.
8. ALL MECHANICAL EQUIPMENT SHOWN ON THE MECHANICAL PLANS SHALL BE PROVIDED BY DIVISION 23 UNLESS OTHERWISE NOTED.
9. NEW MECHANICAL EQUIPMENT, DUCTWORK AND PIPING ARE SHOWN AT APPROXIMATE LOCATIONS. FIELD MEASURE FINAL DUCTWORK AND
PIPING LOCATIONS PRIOR TO FABRICATION AND MAKE ADJUSTMENTS AS REQUIRED TO FIT THE DUCTWORK AND PIPING WITHIN THE AVAILABLE SPACE. VERIFY THAT FINAL EQUIPMENT LOCATIONS MEET MANUFACTURER’S RECOMMENDATIONS REGARDING SERVICE CLEARANCE AND PROPER AIRFLOW CLEARANCE AROUND EQUIPMENT.
10. REFER TO ARCHITECTURAL DRAWINGS FOR RELATED CONSTRUCTION DETAILS AS APPLICABLE TO THE HVAC SYSTEM.
11. INDOOR AIR QUALITY MEASURES: PROTECT INSIDE OF (INSTALLED AND DELIVERED) DUCTWORK AND HVAC UNITS FROM EXPOSURE TO DUST, DIRT, PAINT AND MOISTURE. REPLACE INSULATION THAT HAS BECOME WET AT ANY TIME DURING CONSTRUCTION, DRYING THE INSULATION IS NOT ACCEPTABLE. SEAL ANY TEARS OR JOINTS OF INTERNAL FIBERGLASS INSULATION. REMOVE DEBRIS FROM CEILING/RETURN AIR PLENUM INCLUDING DUST.
12. INSTALL DUCTWORK AND PIPING PARALLEL TO BUILDING COLUMN LINES UNLESS OTHERWISE SHOWN OR NOTED.
13. OVERHEAD HANGERS AND SUPPORTS FOR EQUIPMENT, DUCTWORK AND PIPING SHALL BE FASTENED TO BUILDING JOISTS OR BEAMS. DO NOT ATTACH HANGERS AND SUPPORTS TO THE ABOVE ROOF.
14. COORDINATE LOCATION OF EQUIPMENT SUPPORTS WITH LOCATION OF EQUIPMENT ACCESS PANELS/DOORS TO ENABLE SERVICE OF EQUIPMENT.
15. SEAL PENETRATIONS THROUGH THE BUILDING COMPONENTS IN ACCORDANCE WITH THE CONTRACT SPECIFICATIONS.
16. FOR HYDRONIC PIPING TO EQUIPMENT, MINIMUM ACCEPTABLE SIZE FOR STEEL AND COPPER PIPE IS 3/4 INCH. USE THIS CRITERIA WHERE PIPE SIZES ARE NOT SHOWN ON PLAN.
17. DRAIN, FLUSH, AND REFILL ALL PIPING SYSTEMS NECESSARY TO PERFORM THE WORK. REFERENCE SPECIFICATIONS FOR FLUSHING PERFORMANCE REQUIREMENTS AND SUBMIT FLUSHING PLAN TO ENGINEER FOR REVIEW. PROVIDE CHEMICAL TREATMENT FOR ALL PIPING SYSTEMS AFTER FLUSHING AND REFILLING THE SYSTEM.
18. PROVIDE A PREFABRICATED 45 DEGREE, HIGH EFFICIENCY, RECTANGULAR/ROUND BRANCH DUCT TAKEOFF FITTING FOR BRANCH DUCT CONNECTIONS AND TAKE-OFFS TO INDIVIDUAL DIFFUSERS, REGISTERS AND GRILLES. PROVIDE WITH INTEGRAL MANUAL BALANCING DAMPER AND LOCKING QUADRANT WHERE INDICATED ON PLANS.
19. BRANCH DUCTWORK TO AIR OUTLETS SHALL BE SAME SIZE AS OUTLET NECK SIZE UNLESS OTHERWISE NOTED.
20. REFER TO SPECIFICATIONS FOR DUCTWORK AND PIPING INSULATION REQUIREMENTS. DUCT SIZES ON MECHANICAL PLANS INDICATE CLEAR INSIDE AIRFLOW DIMENSIONS, INCREASE SHEET METAL SIZES ACCORDINGLY TO ACCOUNT FOR THICKNESS OF DUCT LINER.
21. FLEXIBLE DUCTWORK SHALL NOT EXCEED 5’-0” IN LENGTH AND SHALL BE INSTALLED AND SUPPORTED TO AVOID SHARP BENDS AND SAGGING. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
22. FIELD VERIFY THAT THE EXISTING EQUIPMENT INCLUDING ACCESSORIES BEING REUSED FOR THIS PROJECT IS NOT DAMAGED AND IS IN GOOD WORKING ORDER. REPORT ANY DEFICIENCIES TO THE OWNER OR ARCHITECT.
GENERAL NEW NOTES:
1. COORDINATE ALL DEMOLITION WITH WHAT IS SHOWN ON ARCHITECTURAL PLANS. NOTIFY ARCHITECT OF ANY DISCREPANCIES.
2. PRIOR TO SUBMITTING BID, VISIT THE JOB SITE AND BECOME FULLY ACQUAINTED WITH THE EXISTING CONDITIONS OF THE PROJECT.
REVIEW GENERAL NOTES, SPECIFICATIONS AND OTHER DRAWINGS FOR ADDITIONAL REQUIREMENTS THAT MAY NOT BE SPECIFICALLY CALLED OUT IN THIS PORTION OF THE CONSTRUCTION DOCUMENTS. NOTIFY ARCHITECT, ENGINEER OR OWNER, AS DEFINED IN BID DOCUMENTS, OF CONFLICTS OR DISCREPANCIES PRIOR TO SUBMISSION OF BID.
3. REMOVE ITEMS SHOWN HEAVY-LINED DASHED, AND/OR NOTED TO BE REMOVED.
4. AVOID DAMAGING EXISTING SURFACES AND EQUIPMENT TO REMAIN FOR NEW INSTALLATION. REPAIR DAMAGE CAUSED DURING WORK AT NO EXTRA COST TO THE OWNER.
5. SEAL PENETRATIONS THROUGH FLOORS AND WALLS WHERE MECHANICAL COMPONENTS ARE REMOVED AND WHERE THE EXISTING PENETRATION IS NOT USED FOR THE NEW INSTALLATION. REPAIR DAMAGED SURFACES TO MATCH ADJACENT AREAS OR AS INDICATED ON THE ARCHITECTURAL DRAWINGS.
6. REMOVE HANGERS AND SUPPORTS WHERE DUCTWORK, PIPING AND/OR EQUIPMENT ARE REMOVED AND THE EXISTING HANGERS AND SUPPORTS ARE NOT USED FOR THE NEW INSTALLATION.
7. INSTALL PERMANENT CAPS WHERE DUCTWORK AND PIPING IS REMOVED AND THE EXISTING TAPS ARE NOT USED FOR THE NEW INSTALLATION. WHERE DUCTWORK AND PIPING ARE REMOVED AND THE EXISTING TAPS WILL BE USED FOR THE NEW INSTALLATION, INSTALL TEMPORARY CAPS TO PROTECT THE INTERIOR SURFACES UNTIL NEW DUCTWORK AND PIPING ARE INSTALLED.
8. INSPECT EXISTING EQUIPMENT TO REMAIN TO VERIFY THAT EQUIPMENT IS OPERATING PROPERLY. NOTIFY OWNER OF DAMAGED AND/OR MALFUNCTIONING COMPONENTS.
9. WHERE SHUTDOWN OF EXISTING SYSTEMS IS REQUIRED DURING DEMOLITION, COORDINATE SHUTDOWN TIME AND DURATION WITH OWNER TO MINIMIZE DOWNTIME. NOTIFY OWNER SEVEN (7) DAYS PRIOR TO INTERRUPTION OF SERVICE.
GENERAL DEMOLITION NOTES:
FAXTEL
PROJECT NO.
Copyright C
ISSUED BY:
ISSUED DATE:
SHEET TITLE:
DISCIPLINE - CATEGORY - SUB CATEGORY - SHEET
REVISIONS
PROJECT NORTH
®
(913) 742-5000 (913) 742-5001
LENEXA, KS 66214
8345 LENEXA DRIVE, SUITE 300
WWW.HENDERSONENGINEERS.COM
®
®
ARCHITECT OF RECORD
POPULOUS
4800 Main Street Suite 300
Kansas City, MO 64112
816-221-1500
HVAC and LIGHTING ENGINEER
HENDERSON ENGINEERS
8345 Lenexa Drive
Lenexa, KS 66214
913-742-5000
Sacramento Convention Center Ballroom B Upgrades
9/8/2021 9:19:00 AM
CONSTRUCTION
DOCUMENTS
September 8, 2021
MECHANICAL
GENERAL NOTES
AND LEGENDS
M0-0
17.4465
09/08/2021
2019
ERIC C. TAYLOR
1650002727
1400 J St, Sacramento, CA 95814
NO. DATE DESCRIPTION
09/08/2021
10/7/2021
10/11/2021
37 43
49 50
51 EF EG EH EK EM EN EO EQ
34 VAV
11-9
VAV
11-10
(ETR)
VAV 8-14
(ETR)
VAV 8-15
(ETR)
VAV 8-16
(ETR)
VAV 8-17
(ETR)
VAV 9-15
(ETR)
VAV 9-16
(ETR)
VAV 9-17
(ETR)
VAV 9-18
VAV
9-2
VAV
9-3
VAV
9-4
VAV
9-5
VAV
9-6
VAV
9-7
VAV
9-8
VAV
9-9
VAV
9-10
VAV
9-11
VAV
9-13
VAV
9-12
VAV
9-14
VAV
9-1
VAV
12-8
VAV
12-9
(ETR)
VAV 8-18
VAV
8-1
VAV
8-2
VAV
8-3
VAV
8-4
VAV
8-5
VAV
8-6 VAV
8-7
VAV
8-8
VAV
8-9
VAV
8-11
VAV
8-12
VAV
8-10
VAV
8-13
38"Ø SA (ETR) 30"Ø SA (ETR) 22"Ø SA (ETR)
60"x60" RA (ETR)
60"x52" SA (ETR) 60"x42" SA (ETR) 60"x30" SA (ETR) 42"x24" SA (ETR) 60"x54" SA (ETR) 60"x52" SA (ETR) 60"x42" SA (ETR) 60"x30" SA (ETR) 42"x24" SA (ETR) 46"Ø SA (ETR) 44"Ø SA (ETR) 44"x36" SA (ETR)
30"Ø RA (ETR)42"Ø RA (ETR)50"Ø RA (ETR)
60"x56" RA (ETR)
28"Ø28"x14"
20"x18"
24"x14"
18"x14" 18"x14"
24"x14"
28"Ø
18"x14" 18"x14"
20"x18"
24"x14"
18"x14" 18"x14"
28"Ø
24"x18"
24"x14"
24"x14"
18"Ø
16"x14"
16"x14"
16"x14" 18"Ø
16"x14"
28"Ø
28"x14"
24"x14"
20"x18"
18"x14"18"x14"
24"x14"
28"Ø
20"x18"
18"x14"18"x14"
24"x14"
18"x14"
24"x18"
18"x14"
28"Ø 24"x14"
24"x14"
18"Ø
18"Ø
16"x14"
16"x14"
16"x14"
16"x14"
22"Ø SA (ETR)
22"Ø SA (ETR)
30"Ø RA (ETR)
30"Ø RA (ETR)
30"Ø RA (ETR)
22"Ø SA (ETR)22"Ø SA (ETR)
(TYP)
1 (TYP)
2 (TYP)
3 10"Ø SA (ETR) 12"Ø SA14"Ø SA 10"Ø SA(ETR) (ETR) (ETR) ETR (TYP 4)
ALL WORK ABOVE AREA WITHIN DASHED
BOX WAS NOT ABLE TO BE FIELD VERIFIED
DUE TO LACK OF ABOVE CEILING ACCESS
DURING DESIGN PHASE. DEMOLITION
PLANS ARE BASED ON ORIGINAL DESIGN
DRAWINGS. CONTRACTOR SHALL FIELD
VERIFY EXISTING CONDITIONS AND
COORDINATE ALL DEMOLITION WORK WITH
NEW WORK PLANS. CONTRACTOR SHALL
NOTIFY ARCHITECT AND ENGINEER OF ANY
EXISTING CONDITIONS THAT DO NOT
ALLOW FOR DEMOLITION AND/OR NEW
WORK TO BE PERFORMED AS INDICATED.
FAXTEL
PROJECT NO.
Copyright C
ISSUED BY:
ISSUED DATE:
SHEET TITLE:
DISCIPLINE - CATEGORY - SUB CATEGORY - SHEET
REVISIONS
PROJECT NORTH
®
(913) 742-5000 (913) 742-5001
LENEXA, KS 66214
8345 LENEXA DRIVE, SUITE 300
WWW.HENDERSONENGINEERS.COM
®
®
ARCHITECT OF RECORD
POPULOUS
4800 Main Street Suite 300
Kansas City, MO 64112
816-221-1500
HVAC and LIGHTING ENGINEER
HENDERSON ENGINEERS
8345 Lenexa Drive
Lenexa, KS 66214
913-742-5000
Sacramento Convention Center Ballroom B Upgrades
9/8/2021 9:19:18 AM
CONSTRUCTION
DOCUMENTS
September 8, 2021
HVAC DEMO
BALLROOM B
MD1-2
17.4465
09/08/2021
2019
ERIC C. TAYLOR
1650002727
1400 J St, Sacramento, CA 95814
1/8" = 1'-0"1 HVAC DEMO PLAN BALLROOM B
1 AT CONTRACTOR'S OPTION, EXISTING BRANCH DUCTWORK A ND FLEX DUCTS SERVING DIFFUSERS MAY REMAIN IN PLACE TO BE REUSED. INSPECT ALL
SEAMS AND CONNECTIONS AND REPAIR ANY LEAKAGE AND DAMAGED INSULATION.
2 ALL SLOT DIFFUSERS AND ASSOCIATED SUPPLY PLENUMS S HALL REMAIN FOR REUSE.
3 REMOVE VAV TERMINAL UNITS AS INDICATED INCLUDING S UPPORTS AND HANGERS. ALL PRIMARY AIR CONNECTIONS MUST BE REMOVED AND SEALED. ALL CONTROL POWER WIRING MUST BE DISCONNECTED AT ITS SOURCE.
MECHANICAL DEMOLITION PLAN NOTES
NO. DATE DESCRIPTION
09/08/2021
17 18
19 25
31 37
43 49
50 51
EE EF EG EH EJ EK EL EM EN EO EP EQ ER
34 37.5
43.5 50"Ø RA (ETR) 42"Ø RA (ETR) 30"Ø RA (ETR)
30"Ø RA (ETR)
30"Ø RA (ETR)
30"Ø RA (ETR)
46"Ø SA (ETR) 44"Ø SA (ETR) 44"x36" SA (ETR)
60"x54" SA (ETR)
60"x52" SA (ETR)
60"x30" SA (ETR)
42"x24" SA (ETR)
60"x42" SA (ETR)
60"x30" SA (ETR)
42"x24" SA (ETR)
38"Ø SA (ETR) 30"Ø SA (ETR) 22"Ø SA (ETR)
16"x16" SA (ETR)
14"Ø SA10"Ø SA 12"Ø SA 10"Ø SA
10"Ø SA(TYP 4)
42"Ø RA (ETR) 38"Ø RA (ETR) 34"Ø RA (ETR)
32"Ø SA
60"x60" RA (ETR)
60"x56" RA (ETR)
60"x42" SA (ETR)
20"Ø SA
VAV
8-11
VAV
8-10
VAV
8-12
VAV
8-13
20"x14" SA 20"x14" SA
20"x14" SA
20"x14" SA
20"x18" SA
32"Ø SA
VAV
8-7
VAV
8-8
VAV
8-9
28"x14" SA
18"x14" SA
24"x18" SA
32"Ø SA16"Ø SA30"Ø SA
VAV
8-1
VAV
8-2
VAV
8-3 VAV
8-4
VAV
8-5
VAV
8-6
20"x18" SA 18"x14" SA18"x14" SA
18"x14" SA
18"x14" SA18"x14" SA18"x14" SA
18"x14" SA 18"x14" SA 18"x14" SA
20"Ø SA
32"Ø SA
20"Ø SA
24"Ø SA
24"x18" SA
28"x14" SA
14"x14" SA
24"x14" SA 20"x18" SA
VAV
9-2
VAV
9-3 VAV
9-4
VAV
9-1
16"x16" SA
18"x14" SA 18"x14" SA 24"x18" SA
24"x18" SA
28"x14" SA
18"x14" SA
18"x14" SA
28"x14" SA
20"x18" SA18"x14" SA
22"Ø SA
VAV
12-9
VAV
9-8
VAV
9-9
VAV
9-10
VAV
9-11
VAV
9-12
VAV
9-13
VAV
9-14
VAV
9-5
VAV
9-6 VAV
9-7
20"x14" SA
20"x14" SA20"x14" SA
20"x14" SA
VAV
12-8
22"Ø SA
22"Ø SA (ETR) 22"Ø SA (ETR)
24"x18" SA
18"x14" SA
28"x14" SA
14"x14" SA
28"x14" SA
24"x18" SA 24"x14" SA
20"Ø SA
VAV
11-9
22"Ø SA (ETR)
22"Ø SA
22"Ø SA (ETR)
22"Ø SA VAV
11-10
20"Ø SA20"Ø SA30"Ø RA (ETR)
30"Ø RA (ETR)
30"Ø RA (ETR)
1 1
11 20"Ø SA
60"x54" SA (ETR)
B8
E2E18
1294 SF
B6
E2C17
3043 SF
B4
E2C16
3043 SF
B2
E2C15
2974 SF
BALLROOM
B
E2C46
1318 SF
B1
E2F22
2932 SF
B3
E2F23
3000 SF
B5
E2F24
3000 SF
B9
E2F26
1269 SF
PREFUNCTION
E2D01
22058 SF
B1
E2F22
2932 SF
B3
E2F23
3000 SF
B5
E2F24
3000 SF
B7
E2F25
1269 SF
PREFUNCTION
E2D01
22058 SF
B10
E2C19
1297 SF
B6
E2C17
3043 SF
B4
E2C16
3043 SF
B2
E2C15
2974 SF
PREFUNCTION
E2D01
22058 SF
WOMEN
E2C21
993 SF
MEN
E2E27
884 SF
(TYP)
2 3
(TYP)
4 4
M3-1
(TYP)
5 M3-1
(TYP)
6 M3-1
(TYP)
7 M3-1
(TYP)
(ETR)
VAV 8-14
(ETR)
VAV 8-15
(ETR)
VAV 8-18
(ETR)
VAV 8-16
(ETR)
VAV 8-17
(ETR)
VAV 9-15
(ETR)
VAV 9-16
(ETR)
VAV 9-17
(ETR)
VAV 9-18
3 3 3
(TYP 116)
5 ALL WORK ABOVE AREA WITHIN DASHED
BOX WAS NOT ABLE TO BE FIELD VERIFIED
DUE TO LACK OF ABOVE CEILING ACCESS
DURING DESIGN PHASE. DEMOLITION
PLANS ARE BASED ON ORIGINAL DESIGN
DRAWINGS. CONTRACTOR SHALL FIELD
VERIFY EXISTING CONDITIONS AND
COORDINATE ALL DEMOLITION WORK WITH
NEW WORK PLANS. CONTRACTOR SHALL
NOTIFY ARCHITECT AND ENGINEER OF ANY
EXISTING CONDITIONS THAT DO NOT
ALLOW FOR DEMOLITION AND/OR NEW
WORK TO BE PERFORMED AS INDICATED.
FAXTEL
PROJECT NO.
Copyright C
ISSUED BY:
ISSUED DATE:
SHEET TITLE:
DISCIPLINE - CATEGORY - SUB CATEGORY - SHEET
REVISIONS
PROJECT NORTH
®
(913) 742-5000 (913) 742-5001
LENEXA, KS 66214
8345 LENEXA DRIVE, SUITE 300
WWW.HENDERSONENGINEERS.COM
®
®
ARCHITECT OF RECORD
POPULOUS
4800 Main Street Suite 300
Kansas City, MO 64112
816-221-1500
HVAC and LIGHTING ENGINEER
HENDERSON ENGINEERS
8345 Lenexa Drive
Lenexa, KS 66214
913-742-5000
Sacramento Convention Center Ballroom B Upgrades
9/8/2021 9:19:34 AM
CONSTRUCTION
DOCUMENTS
September 8, 2021
HVAC PLAN
BALLROOM B
M1-2
17.4465
09/08/2021
2019
ERIC C. TAYLOR
1650002727
1400 J St, Sacramento, CA 95814
1 FIELD VERIFY EXACT LOCATION OF EXISTING DUCTWORK
FOR NEW CONNECTION.
2 AT CONTRACTOR'S OPTION, PROVIDE INDIVIDUAL
PRIMARY AIR DUCT TAPS, 2" GREATER THAN TERMINAL
UNIT INLET SIZE, FROM DUCT MAIN TO VAV BOX IN LIEU OF
MANIFOLD DUCT SHOWN.
3 PROVIDE ACOUSTICAL PENETRATION TREATMENT AT
DUCT PENETRATION THROUGH ABOVE CEILING BULKHEAD
LOCATED ABOVE EACH OPERABLE PARTITION WALL.
4 ALL SLOT DIFFUSERS AND ASSOCIATED SUPPLY PLENUMS
ARE EXISTING TO REMAIN. PROVIDE NEW 12"Ø DUCT
CONNECTION TO SUPPLY PLENUMS. FIELD VERIFY
EXISTING BRANCH DUCT CONNECTION ARRANGEMENT.
5 TOTAL SCHEDULED CFM OF EACH VAV BOX SHALL BE
EVENLY SPLIT THROUGH CONNECTED DIFFUSERS.
PROVIDE CABLE OPERATED BALANCING DAMPERS AS
REQUIRED. TERMINATE CABLE OPERATORS IN
ACCESSIBLE LOCATION ABOVE CEILING. CLEARLY LABEL
DAMPER OPERATOR WITH VAV TAG AND DIFFUSER #
CORRELATING TO PLAN MARKUP BY INSTALLING
CONTRACTOR.
MECHANICAL PLAN NOTES
1/8" = 1'-0"1 HVAC PLAN BALLROOM B
NO. DATE DESCRIPTION
09/08/2021
31 37
EA EB EC ED
34 37.5
60"x60" RA (ETR)
(ETR)
AHU 8
(ETR)
AHU 13
(ETR)
AHU 4
10" CHWR (ETR)
6" HWS (ETR)
10" CHWS (ETR)
6" HWR (ETR) 6" HWR (ETR)
10" CHWS (ETR)
10" CHWR (ETR)
6" HWS (ETR)
2" HWS (ETR)
2" HWR (ETR)
2" HWR (ETR)
2" HWS (ETR)
1 2" HWR
2" HWS
22 22
3 4
FAXTEL
PROJECT NO.
Copyright C
ISSUED BY:
ISSUED DATE:
SHEET TITLE:
DISCIPLINE - CATEGORY - SUB CATEGORY - SHEET
REVISIONS
PROJECT NORTH
®
(913) 742-5000 (913) 742-5001
LENEXA, KS 66214
8345 LENEXA DRIVE, SUITE 300
WWW.HENDERSONENGINEERS.COM
®
®
ARCHITECT OF RECORD
POPULOUS
4800 Main Street Suite 300
Kansas City, MO 64112
816-221-1500
HVAC and LIGHTING ENGINEER
HENDERSON ENGINEERS
8345 Lenexa Drive
Lenexa, KS 66214
913-742-5000
Sacramento Convention Center Ballroom B Upgrades
9/8/2021 9:19:52 AM
CONSTRUCTION
DOCUMENTS
September 8, 2021
MECHANICAL
ENLARGED PLANS
M2-1
17.4465
09/08/2021
2019
ERIC C. TAYLOR
1650002727
1400 J St, Sacramento, CA 95814
1/4" = 1'-0"1 EXISTING MECHANICAL MEZZANINE PLAN - ENLARGED
MECHANICAL PLAN NOTES
1 FACILITY EXPLORER FX80 SUPERVISORY CONTROLLER TO B E RECONFIGURED FOR INTERFACE TO NEW VAV TERMINAL UNIT CONTROLLERS.
2 PROVIDE ISOLATION VALVE IN HWS BRANCH AND BALANCIN G VALVE IN HWR BRANCH TO ALLOW FOR ISOLATION AND BALANCING OF MODIFIED BRANCH PIPING. PROVIDE 1" VALVED CONNECTIONS TO ALLOW FOR SYSTEM FILL, FLUSHING, AND CHEMICAL TREATMENT. 3 EXISTING BALLROOM VAV TERMINAL UNIT CONTROL POWER IS SUPPLIED FROM TRANSFORMERS IN PANEL WTCP1. CONTRACTOR SHALL VERIFY EXACT CONFIGURATION AND MODIFY AS REQUIRED TO SERVE NEW TERMINAL UNITS. VERIFY THAT CONTROL POWER IS MAINTAINED AT EXISTING TO REMAIN VAV TERMINAL UNITS.
4 EXISTING BALLROOM VAV TERMINAL UNIT CONTROL POWER IS SUPPLIED FROM TRANSFORMERS IN PANEL WTCP3. CONTRACTOR SHALL VERIFY EXACT CONFIGURATION AND MODIFY AS REQUIRED TO SERVE NEW TERMINAL UNITS. VERIFY THAT CONTROL POWER IS MAINTAINED AT EXISTING TO REMAIN VAV TERMINAL UNITS.
NO. DATE DESCRIPTION
09/08/2021
10/11/2021
T
T T T T T T T T T
T
T TTSHS
T TT T
T T T T T T T
T
T T
T
T T
T
CO2
CO2
37 43
49 50
51 EF EG EH EK EM EN EO EQ
34 VAV
11-9
VAV
11-10
(ETR)
VAV 8-14
(ETR)
VAV 8-15
(ETR)
VAV 8-16
(ETR)
VAV 8-17
(ETR)
VAV 9-15
(ETR)
VAV 9-16
(ETR)
VAV 9-17
(ETR)
VAV 9-18
VAV
9-2
VAV
9-3
VAV
9-4 VAV
9-5
VAV
9-6
VAV
9-7
VAV
9-8
VAV
9-9
VAV
9-10
VAV
9-11
VAV
9-13
VAV
9-12
VAV
9-14
VAV
9-1
VAV
12-8
VAV
12-9
(ETR)
VAV 8-18
VAV
8-1
VAV
8-2
VAV
8-3
VAV
8-4
VAV
8-5
VAV
8-6
VAV
8-7
VAV
8-8
VAV
8-9
VAV
8-11
VAV
8-12
VAV
8-10
VAV
8-13
2"2" 1 1/2"1 1/2" 1 1/4"1 1/4" 1"1"
3/4" HWS/R
TYP ALL VAV BOX
CONNECTIONS
2"2"
1 1/2"
1 1/2" 1 1/2"1 1/2"
1 1/4"1 1/4"
2" HWS (ETR)
2" HWR (ETR)
2" HWS (ETR)
2" HWR (ETR)
1" HWS (ETR)
1" HWR (ETR)
1" HWR (ETR)
1" HWS (ETR)
1"1"
VAV
8-3
VAV
8-4
VAV
8-5
VAV
8-6
VAV
8-8
VAV
8-9
VAV
8-7
VAV
8-10
VAV
8-13
VAV
8-11
VAV
8-12
VAV
8-1
VAV
8-2
VAV
9-2
VAV
9-3
VAV
9-4
VAV
9-5
VAV
9-6
VAV
9-7
VAV
9-9
VAV
9-10
VAV
9-8
VAV
12-9
VAV
9-12
VAV
9-14
VAV
12-8
VAV
9-13
VAV
9-11
VAV
9-1
EMCS
EMCS
VAV
11-9 VAV
11-10
1(TYP ALL DEMO VAV BOXES)
ALL WORK ABOVE AREA WITHIN DASHED
BOX WAS NOT ABLE TO BE FIELD VERIFIED
DUE TO LACK OF ABOVE CEILING ACCESS
DURING DESIGN PHASE. DEMOLITION
PLANS ARE BASED ON ORIGINAL DESIGN
DRAWINGS. CONTRACTOR SHALL FIELD
VERIFY EXISTING CONDITIONS AND
COORDINATE ALL DEMOLITION WORK WITH
NEW WORK PLANS. CONTRACTOR SHALL
NOTIFY ARCHITECT AND ENGINEER OF ANY
EXISTING CONDITIONS THAT DO NOT
ALLOW FOR DEMOLITION AND/OR NEW
WORK TO BE PERFORMED AS INDICATED.
FAXTEL
PROJECT NO.
Copyright C
ISSUED BY:
ISSUED DATE:
SHEET TITLE:
DISCIPLINE - CATEGORY - SUB CATEGORY - SHEET
REVISIONS
PROJECT NORTH
®
(913) 742-5000 (913) 742-5001
LENEXA, KS 66214
8345 LENEXA DRIVE, SUITE 300
WWW.HENDERSONENGINEERS.COM
®
®
ARCHITECT OF RECORD
POPULOUS
4800 Main Street Suite 300
Kansas City, MO 64112
816-221-1500
HVAC and LIGHTING ENGINEER
HENDERSON ENGINEERS
8345 Lenexa Drive
Lenexa, KS 66214
913-742-5000
Sacramento Convention Center Ballroom B Upgrades
9/8/2021 9:19:28 AM
CONSTRUCTION
DOCUMENTS
September 8, 2021
PIPING DEMO
BALROOM B
MPD1-2
17.4465
09/08/2021
2019
ERIC C. TAYLOR
1650002727
1400 J St, Sacramento, CA 95814
1 REMOVE EXISTING TEMPERATURE SENSORS AND CONTROL WI RING AS INDICATED. TEMPERATURE SENSOR ROUGH-IN SHALL BE USED FOR NEW SENSOR INSTALLATION. REMOVE ANY ADDITIONAL CONTROL DEVICES SUCH AS HUMIDITY OR CO2 SENSORS ASSOCIATED WITH DEMOLISHED VAV TERMINAL UNITS. PATCH
AND SEAL WALL PENETRATIONS THAT WILL NOT BE USED FOR NEW SENSOR INSTALLATION AND PAINT TO MATCH ADJACENT FINISH.
MECHANICAL PLAN NOTES
1/8" = 1'-0"1 PIPING DEMO PLAN BALLROOM B
NO. DATE DESCRIPTION
09/08/2021
TS TS
TS TS TS
TS
TS TS TS TS TS TS
TS
TSTSTSTS
TSTS
TS
TSTSTSTSTSTSTS
TS
TS TS TS
17 18
19 25
31 37
43 49
50 51
EE EF EG EH EJ EK EL EM EN EO EP EQ ER
34 37.5
43.5 1" HWR (ETR)
1" HWS (ETR)
(ETR)
VAV 8-14
(ETR)
VAV 8-15
(ETR)
VAV 8-16
(ETR)
VAV 8-17
(ETR)
VAV 9-15
(ETR)
VAV 9-16
(ETR)
VAV 9-17
(ETR)
VAV 9-18
(ETR)
VAV 8-18
VAV
9-2
VAV
9-3
VAV
9-4
VAV
9-1
VAV
9-5
VAV
9-6
VAV
9-7
VAV
12-8
VAV
12-9
VAV
9-8
VAV
9-9
VAV
9-10
VAV
9-11
VAV
9-13
VAV
9-12
VAV
9-14
VAV
8-1
VAV
8-2
VAV
8-3
VAV
8-4
VAV
8-5
VAV
8-6
VAV
8-7
VAV
8-8 VAV
8-9
VAV
8-11
VAV
8-12
VAV
8-10
VAV
8-13
VAV
11-9
VAV
11-10
1 1/2" HWR
2" HWR
2" HWR 1 1/4" HWR 1" HWR
2" HWR
2" HWS
2" HWS
VAV
8-3
VAV
8-4
VAV
8-5
VAV
11-9
VAV
8-2
VAV
8-1
VAV
8-6
VAV
8-8
VAV
8-7
VAV
8-9
VAV
8-10
VAV
8-13
VAV
11-10
VAV
8-11
VAV
8-12
VAV
9-13
VAV
9-11
VAV
9-14
VAV
9-12
VAV
12-9
VAV
9-10
VAV
9-9
VAV
9-8
VAV
9-7
VAV
9-6
VAV
9-5
VAV
9-4
VAV
12-8
VAV
9-2
VAV
9-3
VAV
9-1
(TYP)
1(TYP ALL REPLACED VAV BOXES)
2" HWS
3/4" HWS/R
TYP ALL
BRANCH PIPING
TO VAV BOXES
2" HWR2" HWS 1 1/2" HWR 1 1/2" HWS
1 1/2" HWS
1 1/2" HWR
1 1/4" HWR 1 1/4" HWS
1" HWS
1" HWR
1" HWS
1" HWS (ETR)
1" HWR (ETR)
1 1/4" HWS
1 1/2" HWS
1 1/2" HWR
1 1/2" HWS
2" HWS (ETR)
2" HWR (ETR)
2" HWR (ETR)
2" HWS (ETR)
7.3 GPM
DOWNSTREAM OF
NEW CONNECTION
9.2 GPM
DOWNSTREAM OF
NEW CONNECTION
BRANCH TOTAL
FLOW = 31.6 GPM
BRANCH TOTAL
FLOW = 29.7 GPM
ROUTE NEW BRANCH PIPING
OVER ACCESSIBLE PORTION
OF CEILING. TYP.
2 2
2 8
M3-1
(TYP)
1 M3-1
3 M3-1
2 M3-1
(TYP)(TYP)(TYP)
FAXTEL
PROJECT NO.
Copyright C
ISSUED BY:
ISSUED DATE:
SHEET TITLE:
DISCIPLINE - CATEGORY - SUB CATEGORY - SHEET
REVISIONS
PROJECT NORTH
®
(913) 742-5000 (913) 742-5001
LENEXA, KS 66214
8345 LENEXA DRIVE, SUITE 300
WWW.HENDERSONENGINEERS.COM
®
®
ARCHITECT OF RECORD
POPULOUS
4800 Main Street Suite 300
Kansas City, MO 64112
816-221-1500
HVAC and LIGHTING ENGINEER
HENDERSON ENGINEERS
8345 Lenexa Drive
Lenexa, KS 66214
913-742-5000
Sacramento Convention Center Ballroom B Upgrades
9/8/2021 9:19:45 AM
CONSTRUCTION
DOCUMENTS
September 8, 2021
PIPING PLAN
BALLROOM B
MP1-2
17.4465
09/08/2021
2019
ERIC C. TAYLOR
1650002727
1400 J St, Sacramento, CA 95814
MECHANICAL PLAN NOTES
1/8" = 1'-0"1 PIPING PLAN BALLROOM B
1 PROVIDE NEW TEMPERATURE SENSOR AT EXISTING ROUGH-I N LOCATION.
REPAIR/PAINT SURROUNDING WALL AS REQUIRED FOR A CLEAN INSTALLATION. 2 PROVIDE ACOUSTICAL PENETRATION TREATMENT AT PIPE P ENETRATIONS
THROUGH ABOVE CEILING BULKHEAD LOCATED ABOVE EACH OPERABLE PARTITION WALL.
NO. DATE DESCRIPTION
09/08/2021
1. CONTRACTOR'S BID SHALL INCLUDE PROVISIONS TO
PROVIDE ALL SERVICES RELATED TO THE CODE REQUIRED
BUILDING SYSTEMS COMMISSIONING, FUNCTIONAL
PERFORMANCE AND ACCEPTANCE TESTING, RELATED
DOCUMENTATION, REPORTS, AND OWNER TRAINING. THIS
INCLUDES RETAINING THE SERVICES OF A 3RD PARTY
ENGINEER AND CERTIFIED LIGHTING CONTROLS
ACCEPTANCE TEST TECHNICIAN (CLCATT) AS REQUIRED.
REFER TO THE LATEST ADOPTED EDITION OF THE
CALIFORNIA TITLE 24 PART 6 AND PART 11 FOR MORE
INFORMATION.
2. ALL APPLICABLE LIGHT FIXTURES, EXIT SIGNS AND
LIGHTING CONTROL DEVICES AS INSTALLED SHALL
COMPLY WITH THE LATEST ADOPTED EDITION OF
CALIFORNIA TITLE 24 PART 6 SECTION 110.0, AND ANY
OTHER STATE AND LOCAL REQUIREMENTS.
3. EXISTING CONDITIONS WERE TAKEN FROM ORIGINAL
DRAWINGS AND SITE VISITS AND MAY NOT REFLECT
ACTUAL "AS-BUILT" CONDITIONS. VERIFY EXISTING
CONDITIONS PRIOR TO SUBMITTING FINAL BID.
COORDINATE NEW AND DEMOLITION WORK WITH ALL
OTHER TRADES AND EXISTING CONDITIONS.
4. NOTIFY ARCHITECT, ENGINEER AND OWNER, AS
APPLICABLE, IF ANY DANGEROUS CONDITIONS EXIST ON
JOB SITE BEFORE ANY DEMOLITION OR REMODEL WORK
BEGINS.
5. COORDINATE ANY NECESSARY POWER OUTAGES WITH
THE LANDLORD AND OWNER AND MAKE EVERY ATTEMPT
TO SCHEDULE DURING NON-BUSINESS OR OFF-PEAK
BUSINESS HOURS TO MINIMIZE DISRUPTION TO BUSINESS
OPERATIONS. REQUESTS FOR ELECTRICAL SHUTDOWNS
OF THE LANDLORD'S EQUIPMENT SHALL BE BROUGHT IN
WRITING TO THE ATTENTION OF THE LANDLORD AT LEAST
7 DAYS IN ADVANCE. SHUTDOWNS SHALL NOT BE
PERFORMED WITHOUT WRITTEN APPROVAL FROM THE
LANDLORD.
6. ALL ROOF PENETRATIONS, FLOOR CHASING OR CORE
DRILLING SHALL REQUIRE THE SPECIFIC APPROVAL OF THE
LANDLORD AND OWNER. ALL WORK IN COMMON AREAS,
SHAFTS OR OTHER OWNER SPACES MUST BE
SPECIFICALLY REVIEWED AND APPROVED BY THE
LANDLORD PRIOR TO ANY WORK BEING PERFORMED.
MINIMIZE DISTURBANCE TO OTHER BUILDING TENANTS.
7. FOR AREAS AND EQUIPMENT WITHIN THE SCOPE OF THIS
REMODEL: EXISTING ELECTRICAL EQUIPMENT AND
CIRCUITRY MAY BE REUSED IF IN GOOD CONDITION AND
NEW DESIGN REQUIREMENTS CAN BE MET; OTHERWISE
REPLACE
8. FOR AREAS AND EQUIPMENT WITHIN THE SCOPE OF THIS
REMODEL: REPAIR OR REPLACE ANY EXISTING DAMAGED
OR RECALLED ELECTRICAL EQUIPMENT, LIGHT FIXTURES,
WIRING DEVICES AND RELATED CIRCUITRY AND RESTORE
ALL ELECTRICAL SYSTEMS TO PROPER WORKING ORDER.
THE FINAL ELECTRICAL INSTALLATION SHALL BE FREE
FROM ELECTRICAL DEFECTS TO THE SATISFACTION OF
THE AHJ, OWNER, ARCHITECT AND ENGINEER.
9. FOR AREAS AND EQUIPMENT WITHIN THE SCOPE OF THIS
REMODEL: VERIFY CONDITION AND AGE OF EXISTING
REUSED ELECTRICAL EQUIPMENT, LIGHT FIXTURES,
CIRCUIT BREAKERS, FUSES, CONDUIT, SWITCHES AND
RELATED WIRING. NOTIFY OWNER OF ANY ELECTRICAL
EQUIPMENT, LIGHT FIXTURES AND WIRING AGED BEYOND
ITS USEFUL LIFE AND REPLACE AS DIRECTED. THE
MAXIMUM EXPECTED USEFUL LIFE SHALL NOT EXCEED THE
FOLLOWING, (AS DATED FROM THE POINT OF
MANUFACTURE), UNLESS APPROVED BY THE ENGINEER,
MANUFACTURER AND OWNER: 20 YEARS FOR CIRCUIT
BREAKERS, GENERATOR/UPS SYSTEMS AND LIGHT
FIXTURES, 30 YEARS FOR TRANSFORMERS AND
PANELBOARDS, 40 YEARS FOR SWITCHBOARDS AND
OTHER ELECTRICAL EQUIPMENT.
10. FOR AREAS AND EQUIPMENT WITHIN THE SCOPE OF THIS
REMODEL: ELECTRICAL EQUIPMENT SHALL BE LOCATED
SO THAT THE CODE REQUIRED MINIMUM WORKING
CLEARANCE AND DEDICATED ELECTRICAL SPACE ARE
MAINTAINED. EXISTING EQUIPMENT NOT MEETING
CURRENT CODE CLEARANCE REQUIREMENTS MAY REMAIN
IF ALLOWED TO REMAIN BY THE AHJ, ENGINEER AND
OWNER.
ELECTRICAL GENERAL NOTES:
1. PRIOR TO SUBMITTING BID, VISIT THE JOB SITE AND BECOME FULLY ACQUAINTED WITH THE EXISTING CONDITIONS. AS
APPLICABLE, REVIEW THE LANDLORD CRITERIA, GENERAL
NOTES, OTHER TRADE DRAWINGS AND SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS THAT MAY NOT BE CALLED OUT IN
THIS PORTION OF THE CONSTRUCTION DOCUMENTS. NOTIFY
ARCHITECT AND ENGINEER OF ANY CONFLICTS OR
DISCREPANCIES PRIOR TO SUBMITTING BID.
2. ALL WORK SHALL CONFORM TO ALL LOCAL CODES AND
ORDINANCES AS WELL AS APPLICABLE INDUSTRY STANDARDS.
ALL EQUIPMENT SHALL BEAR LABELS FOR THE USE INTENDED
BY AN AHJ ACCEPTED NATIONALLY RECOGNIZED TESTING
LABORATORY (NRTL), SUCH AS UL OR ETL. THE FINAL
ELECTRICAL INSTALLATION OF THE FACILITY OCCUPIED BY
OWNER SHALL BE FREE FROM ELECTRICAL DEFECTS TO THE
SATISFACTION OF THE AHJ, OWNER, ARCHITECT AND
ENGINEER.
3. COORDINATE FINAL LOCATION AND INSTALLATION
REQUIREMENTS OF ALL LIGHT FIXTURES, ELECTRICAL
EQUIPMENT AND ELECTRICAL DEVICES WITH ARCHITECTURAL
DRAWINGS, EXISTING CONDITIONS AND OTHER TRADES PRIOR
TO ROUGH-IN. PROVIDE ALL NECESSARY DEVICES, CORDS,
PLUGS, DISCONNECTS AND FINAL CONNECTIONS TO
ELECTRICAL EQUIPMENT FOR PROPER OPERATION IN
ACCORDANCE WITH CODE, OWNER AND MANUFACTURER
REQUIREMENTS.
4. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC/SCHEMATIC IN
NATURE AND REPRESENT THE GENERAL SCOPE OF WORK. IT IS
NOT WITHIN THE SCOPE OF THE ELECTRICAL DRAWINGS TO
SHOW ALL NECESSARY RACEWAY ROUTING, BENDS, OFFSETS,
PULL BOXES AND OBSTRUCTIONS. CONTRACTOR SHALL
COORDINATE THE FINAL LOCATION OF EQUIPMENT AND WIRING
DEVICES WITH OTHER TRADES PRIOR TO INSTALLATION AND
INSTALL ALL WORK TO CONFORM TO THE OWNER
REQUIREMENTS.
5. ALL CONDUCTOR AND CONDUIT LENGTHS SHOWN IN THESE
DESIGN DOCUMENTS ARE INTENDED SOLELY FOR USE IN THE
DESIGN CALCULATIONS BY THE DESIGN PROFESSIONAL,
UNLESS NOTED OTHERWISE. LENGTHS SHOWN SHALL NOT BE
USED TO ASSIST IN THE BIDDING TAKEOFF PROCESS. THE
CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MATERIAL
QUANTITIES REQUIRED TO BID AND CONSTRUCT THE
COMPLETE PROJECT.
6. PROVIDE PROPER FIRE PROOFING AND SEALANT FOR
PENETRATIONS THROUGH FIRE RATED ASSEMBLIES. THE FIRE
STOPPING METHOD, MATERIAL AND ITS APPLICATION SHALL BE
NRTL LISTED, CODE COMPLIANT AND APPROVED BY AHJ.
7. ALL APPLICABLE SWITCHES, RECEPTACLES, OUTLETS, AND
CONTROLS SHALL BE PLACED AT HEIGHTS THAT ARE IN
ACCORDANCE WITH ADA ACCESSIBILITY GUIDELINES.
8. WIRING DEVICES ADJACENT TO EACH OTHER SHALL BE
INSTALLED UNDER A SINGLE COVER PLATE, UNO.
9. WIRING DEVICES SHOWN BACK-TO-BACK ON A COMMON WALL
SHALL BE OFFSET A MINIMUM OF 12” HORIZONTALLY TO
REDUCE SOUND TRANSMISSION BETWEEN ROOMS, UNO.
10. FLEXIBLE CONDUIT IS ONLY PERMITTED WHERE SPECIFICALLY
ALLOWED IN THE CONSTRUCTION DOCUMENTS, WHERE
CONCEALED FROM VIEW OR EXPOSED FINAL CONNECTIONS TO
LIGHT FIXTURES AND EQUIPMENT IN LENGTHS OF 6'-0" OR LESS.
11. ALL EMPTY CONDUIT/RACEWAY SHALL BE INSTALLED WITH
PULL STRINGS. TERMINATE CONDUIT STUB-UP WITH A NYLON
BUSHING.
12. EXPOSED CONDUIT/RACEWAY SHALL BE PAINTED TO MATCH
ADJACENT SURFACE, UNLESS NOTED OTHERWISE.
COORDINATE REQUIREMENTS WITH ARCHITECT AND OWNER
PRIOR TO INSTALLATION.
13. CONDUITS/RACEWAYS SHALL BE CONCEALED FROM VIEW
WHEREVER PRACTICABLE, UNLESS NOTED OTHERWISE. ROUTE
CONDUITS SERVING ROOFTOP EQUIPMENT CONCEALED INSIDE
EQUIPMENT CURB AND MINIMIZE ROOF PENETRATIONS AND
EXTERIOR CONDUIT RUNS WHERE PRACTICABLE. SUPPORT
RACEWAY FROM STRUCTURE, NOT ROOF DECK. MAINTAIN 2"
MIN SPACING FROM BOTTOM OF ROOF DECK TO PREVENT
ROOFING SCREWS FROM PENETRATING RACEWAY. DO NOT
ROUTE CONDUITS ACROSS SKYLIGHTS, ACCESS PANELS,
HATCHED TILES, HVAC DIFFUSERS, OR EQUIPMENT WORKING
CLEARANCE SPACE. ROUTE ALL EXPOSED NON-FLEXIBLE
CONDUITS TIGHT TO STRUCTURE, PARALLEL TO BUILDING
LINES AND IN STRUT OR CABLE/PIPE TRAY WHERE
PRACTICABLE. INSTALL CONDUITS PLUMB/ LEVEL WHERE
EXPOSED TO VIEW. COORDINATE RACEWAY ROUTING AND
INSTALLATION WITH OTHER TRADES PRIOR TO ROUGH-IN.
14. MULTIWIRE BRANCH CIRCUITS ARE NOT ALLOWED, UNLESS
NOTED OTHERWISE.
15. PROVIDE INSULATED EQUIPMENT GROUNDING CONDUCTOR
FOR ALL CIRCUITS, UNLESS NOTED OTHERWISE.
ELECTRICAL SUPPLEMENTAL SPECIFICATIONS:
NOTE: PROJECT IS DESIGNED IN COMPLIANCE WITH THE FOLLOWING CODES. THIS IS NOT AN EXHAUSTIVE LIST. PROJECT SHALL COMPLY
WITH ALL APPLICABLE CODES, STANDARDS AND LOCAL
REQUIREMENTS. REFER TO THE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
ELECTRICAL CODE: 2019 CALIFORNIA ELECTRICAL CODE
BUILDING CODE: 2019 CALIFORNIA BUILDING CODE
ENERGY CODE: 2019 CALIFORNIA ENERGY CONSERVATION CODE
APPLICABLE ELECTRICAL CODES:
MCC
MFR
MIN
MLO
MLV
MOCP
MTD
N/A
NF
NL
NRTL
NTS
OS
P
PART
PH/Ø
PNL
PNLBD
PROVIDE
PT
QTY
R/REL
RCPT
RLA
RTU
SCCR
SD
SF
SPDT
SPST
SSBJ
ST
SWBD
SWGR
TBB
TBD
TGB
TL
TMGB
TX/XFMR
TYP
U/F
U/G
U/S
UH
UNO
UPS
VD
VFD
VS
W
W/
WP
WR
WT
XP
MOTOR CONTROL CENTER
MANUFACTURER
MINIMUM
MAIN LUGS ONLY
MAGNETIC LOW-VOLTAGE
MAXIMUM OVERCURRENT
PROTECTION
MOUNTED
NOT APPLICABLE
NON-FUSED
NIGHT LIGHT (24HR ON)
NATIONALLY RECOGNIZED
TESTING LABORATORY
(CSA, ETL, NSF, UL)
NOT TO SCALE
OCCUPANCY SENSOR
POLE
PARTIAL CIRCUIT
PHASE
PANEL
PANELBOARD
FURNISH AND INSTALL
POTENTIAL TRANSFORMER
QUANTITY
RELOCATE
RECEPTACLE
RUNNING LOAD AMPS
ROOFTOP UNIT
SHORT-CIRCUIT CURRENT
RATING
SMOKE DUCT DETECTOR
SQUARE FEET
SINGLE-POLE,
DOUBLE-THROW
SINGLE-POLE,
SINGLE-THROW
SUPPLY-SIDE BONDING
JUMPER
SHUNT TRIP
SWITCHBOARD
SWITCHGEAR
TELECOMMUNICATIONS
BONDING BACKBONE
TO BE DETERMINED
TELECOMMUNICATIONS
GROUND BUS BAR
TWISTLOCK
TELECOMMUNICATIONS
MAIN GROUND BUS BAR
TRANSFORMER
TYPICAL
UNDERFLOOR
UNDERGROUND
UNDERSLAB
UNIT HEATER
UNLESS NOTED OTHERWISE
UNINTERRUPTIBLE POWER
SUPPLY
VOLTAGE DROP
VARIABLE FREQUENCY
DRIVE
VACANCY SENSOR
WIRE
WITH
WEATHER PROOF
WEATHER RESISTANT
WATERTIGHT
EXPLOSION PROOF
AF
AFC
AFF
AFG
AHJ
AHU
AIC
AS
AT
ATS
AV
BAS
BKR
C
CAT
CATV
CCTV
CD
CKT
CODE
CT
CTR
CVD
D/DEMO
DPDT
DPST
E/ETR/EX
EC
EF
EM
EMS
ELV
EWC
FAAP
FACP
FCA
FCU
FF
FLA
FLR
GC
GEC
GES
GFR
G
IG
ISC
JB/J-BOX
LF
LRA
LTG/LTS
MAU
MAX
MCA
MCB
AMPERE FUSE SIZE
ABOVE FINISHED CEILING
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AUTHORITY HAVING
JURISDICTION
AIR HANDLING UNIT
AMPERE INTERRUPTING
CAPACITY
AMPERE SWITCH SIZE
AMPERE TRIP SETTING
AUTOMATIC TRANSFER
SWITCH
AUDIO VISUAL
BUILDING AUTOMATION
SYSTEM
BREAKER
CONDUIT
CATEGORY
CABLE TELEVISION SYSTEM
CLOSED CIRCUIT TELEVISION
CANDELA
CIRCUIT
APPLICABLE CODE
ADOPTED BY JURISDICTION
CURRENT TRANSFORMER
CENTER
CUMULATIVE VOLTAGE DROP
DEMOLITION
DOUBLE-POLE,
DOUBLE-THROW
DOUBLE-POLE,
SINGLE-THROW
EXISTING TO REMAIN
ELECTRICAL CONTRACTOR
EXHAUST FAN
EMERGENCY
ENERGY MANAGEMENT
SYSTEM
ELECTRONIC LOW-VOLTAGE
ELECTRIC WATER COOLER
FIRE ALARM ANNUNCIATOR
PANEL
FIRE ALARM CONTROL PANEL
FAULT CURRENT AMPS
AVAILABLE
FAN COIL UNIT
FINISHED FLOOR
FULL LOAD AMPS
FLOOR
GENERAL CONTRACTOR
GROUNDING ELECTRODE
CONDUCTOR
GROUNDING ELECTRODE
SYSTEM
GROUND FAULT RELAY
GROUND
ISOLATED GROUND
SHORT CIRCUIT CURRENT
JUNCTION BOX
LINEAR FEET
LOCKED ROTOR AMPS
LIGHTING/LIGHTS
MAKE-UP AIR UNIT
MAXIMUM
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
STANDARD MOUNTING HEIGHTS
AUDIBLE APPLIANCES (CENTERLINE)
ALARMS
ANNUNCIATOR PANELS (DISPLAY)
CONTROLS (TOP OF DEVICE)
FIRE ALARM ANNUNCIATOR PANEL (DISPLAY)
FIRE ALARM BELL (EXTERIOR) (CENTERLINE)
FIRE ALARM CONTROL PANEL/UNIT (DISPLAY)
INTERCOM (AFEA ONLY)
INTERCOMS (TOP OF DEVICE)
PULL STATIONS (TOP OF DEVICE)
PHOTOCELLS
RECEPTACLES
RECEPTACLES (EXTERIOR)
RECEPTACLES (GARAGES)
RECEPTACLES (POOLS)
RECEPTACLES (ABOVE COUNTER)
RECEPTACLES IN EQUIPMENT ROOMS
REMOTE INDICATING LIGHT (EQUIPMENT ROOMS)
REMOTE INDICATING LIGHT (FINISHED AREAS)
SAFETY SWITCHES (TOP OF DEVICE)
STARTERS (TOP OF DEVICE)
SWITCHES (TOP OF DEVICE)
TELEPHONE, DATA OUTLETS
TELEPHONE TERMINAL BOARD (BOTTOM)
TELEVISION OUTLETS
VISIBLE APPLIANCES (CENTERLINE)
INSTALL OUTLET BOXES AT THE MOUNTING HEIGHTS SHOWN ABOVE UNO IN THE CONSTRUCTION DOCUMENTS. MOUNTING HEIGHTS LISTED ABOVE, OR
ELSEWHERE IN THE CONSTRUCTION DOCUMENTS, ARE AFF OR AFG TO BOTTOM OF OUTLET BOX, UNO. ALL DEVICES SHALL BE INSTALLED IN COMPLIANCE WITH CURRENT ADA AND LOCAL REQUIREMENTS.
1 CU
1 1
E1
1 1
1 1
1 1
E1
ANNOTATION
MECHANICAL OR FIRE PROTECTION PLAN NOTE CALLOUT
PLUMBING PLAN NOTE CALLOUT
ELECTRICAL OR FIRE ALARM PLAN NOTE CALLOUT
TECHNOLOGY PLAN CALLOUT
PLUMBING EQUIPMENT DESIGNATION. (CONTRACTOR
FURNISHED AND INSTALLED). REFER TO PLUMBING FIXTURE
OR EQUIPMENT SCHEDULES
EQUIPMENT DESIGNATION (OWNER FURNISHED,
CONTRACTOR INSTALLED)
MECHANICAL EQUIPMENT DESIGNATION (CONTRACTOR
FURNISHED AND INSTALLED UNLESS NOTED OTHERWISE)
CONNECTION POINT OF NEW WORK TO EXISTING
DETAIL REFERENCE UPPER NUMBER INDICATES DETAIL
NUMBER LOWER NUMBER INDICATES SHEET NUMBER
SECTION CUT DESIGNATION
DEDICATED EQUIPMENT ACCESS TILE
ACCESS PANEL
CIRCUITING & WIRING
57 P1-3,5,7
OR
3 HOMERUN TO PANELBOARD. INFORMATION AT ARROWS
ARE CIRCUIT NUMBERS AND PANELBOARD FOR
TERMINATION. REFER TO PANELBOARD SCHEDULES FOR
BRANCH CIRCUIT CONDUCTOR SIZES.
INDICATES RELAY NUMBER
CIRCUIT CONTINUATION OR PARTIAL CIRCUIT
CONDUIT CONCEALED
CONDUIT CONCEALED (EMERGENCY)
CONDUIT IN/UNDER FLOOR/GROUND CONSTRUCTION
EXPOSED CONDUIT
EXPOSED CONDUIT (EMERGENCY)
FLEXIBLE CONDUIT
LOW VOLTAGE CABLE (NOT ROUTED IN CONDUIT)
CONDUIT TURNING DOWN
CONDUIT TURNING UP
CONNECTION POINT OR EQUIPMENT TERMINATION
EQUIPMENT TERMINATION
POWER EQUIPMENT & DEVICES
VFD
200/3/150/3R
30/3/15/1/3R
2 ELECTRICAL PANELBOARD (SURFACE OR FLUSH
MOUNT)
ELECTRICAL CABINET (SURFACE OR FLUSH MOUNT),
TYPE AS NOTED
PLYWOOD TERMINAL BOARD FOR TELEPHONE
SYSTEM, UNO. SIZE AS NOTED
SWITCHBOARD OR MOTOR CONTROL CENTER ON
HOUSEKEEPING PAD
ELECTRICAL DISTRIBUTION PANELBOARD
TRANSFORMER
DISCONNECT SWITCH - "200/3/150/3R" DENOTES
AMPERES/POLE/FUSE/NEMA ENCLOSURE RATING,
NF= NON-FUSED, CB= CIRCUIT BREAKER (200/3/CB),
NO VALUE (200/3/150) FOR NEMA ENCLOSURE MEANS
STANDARD NEMA 1 RATING
COMBINATION DISCONNECT (SAFETY) SWITCH AND
MOTOR STARTER "30/3/15/1/3R" DENOTES
AMPERES/POLE/FUSE/NEMA STARTER SIZE/NEMA
ENCLOSURE RATING. NF= NON-FUSED, CB= CIRCUIT
BREAKER (30/3/CB/1), NO VALUE (200/3/150/1) FOR
NEMA ENCLOSURE MEANS STANDARD NEMA 1
ENCLOSURE RATING
MAGNETIC MOTOR STARTER, NEMA SIZE AS NOTED.
3-POLE, UNO
VARIABLE FREQUENCY DRIVE
INDICATING LIGHT
EMERGENCY POWER OFF BUTTON
STOP-START PUSH BUTTON CONTROL STATION
HAND-OFF-AUTO PUSH BUTTON CONTROL STATION
MUSHROOM-TYPE PUSH BUTTON
OVERHEAD PADDLE FAN
A a
LIGHTING
LIGHT FIXTURE
a = LOWER CASE LETTER IS SWITCH IDENTIFIER
A = UPPER CASE LETTER INDICATES LIGHT FIXTURE
TYPE
= WALL MOUNT
= ARROW INDICATED AIMING DIRECTION
LIGHT FIXTURE CIRCUITED AS A NIGHT LIGHT (NL)
EMERGENCY LIGHT FIXTURE WITH EMERGENCY LIGHTING
BATTERY PACK OR CONNECTED TO EMERGENCY SOURCE
NIGHT LIGHT/EMERGENCY LIGHT FIXTURE WITH EMERGENCY
BATTERY PACK OR CONNECTED TO EMERGENCY SOURCE
LIGHT FIXTURE WITH DUAL BALLASTS CIRCUITED
SEPARATELY (SHADING IMPLIES EMERGENCY LIGHT
FIXTURE)
LIGHTING TRACK (# INDICATES RELAY NUMBER)
MIRROR LIGHTS
EXTERIOR PARKING LOT LIGHT FIXTURE
EXTERIOR PEDESTRIAN POST TOP LIGHT FIXTURE
EXTERIOR LIT BOLLARD LIGHT
EXIT SIGN - CEILING / WALL MOUNTED, ARROWS AS
INDICATED, FACE HATCHED
EMERGENCY LIGHTING UNIT EQUIPMENT WITH BATTERY
PACK - CEILING/WALL MOUNTED
AFEA (AREA FOR EVACUATION ASSISTANCE) SIGN -
CEILING/WALL MOUNTED, ARROWS AS INDICATED
BOXES, LIGHTING CONTROL & WIRING DEVICES
SWITCH LETTER DESIGNATIONS AS FOLLOWS:
BLANK = SINGLE
2 = TWO POLE
3 = THREE-WAY
4 = FOUR-WAY
D = DIMMER
F = FAN SPEED CONTROL
FH = FRACTIONAL HORSEPOWER MANUAL
CONTROLLER
IH = INTEGRAL HORSEPOWER MANUAL
CONTROLLER
K = KEYED
LV# = LOW VOLTAGE / DIGITAL
M = MANUAL MOTOR STARTER DISCONNECT
OS# = OCCUPANCY SENSOR
P = SPST PILOT LIGHT
WP = WEATHER PROOF
# = REFER TO LIGHTING CONTROL DEVICE
SCHEDULE
AUTOMATIC LOAD CONTROL RELAY
BRANCH CIRCUIT TRANSFER SWITCH
CEILING / WALL MOUNTED OCCUPANCY SENSOR
(# INDICATES TYPE PER SCHEDULE)
CORNER 90 DEGREE SENSING
ONE-DIRECTION SENSING, CEILING/WALL MOUNT
CEILING MOUNT, TWO DIRECTION SENSING
CEILING MOUNT, FOUR DIRECTION SENSING
CONTACTOR (SIZE, COIL VOLTAGE AND NUMBER OF
POLES AS INDICATED)
TRACK-MOUNTED CURRENT LIMITER (## INDICATES
AMPERAGE)
DAYLIGHT SENSOR (# INDICATES TYPE PER SCHEDULE)
LIGHTING CONTROLS PROCESSOR AND/OR EQUIPMENT
POWER PACK (# INDICATES TYPE PER SCHEDULE)
PHOTOELECTRIC SWITCH
ROOM CONTROLLER (# INDICATES TYPE PER SCHEDULE)
TIME SWITCH
SIMPLEX RECEPTACLE - NEMA 5-20R, UNO
DUPLEX RECEPTACLE - NEMA 5-20R, UNO
DOUBLE DUPLEX RECEPTACLE - NEMA 5-20R, UNO
SPECIAL RECEPTACLE - NEMA TYPE AS NOTED
TWIST-LOCK TYPE RECEPTACLE
BLANK FACE GFCI FEED THROUGH DEVICE
GFCI TYPE RECEPTACLE*
ISOLATED GROUND TYPE RECEPTACLE*
EMERGENCY RECEPTACLE*
RECEPTACLE INSTALLED ABOVE COUNTER OR
BACKSPLASH*
RECEPTACLE INSTALLED IN CEILING*
RECEPTACLE INSTALLED IN FLOOR*
RECEPTACLE INSTALLED VIA DROP CORD*
RECEPTACLE LETTER DESIGNATIONS AS FOLLOWS:
C = AUTOMATICALLY CONTROLLED
CH = CLOCK HANGER TYPE
G=RCPT PROTECTED BY GFCI CIRCUIT
BREAKER OR UPSTREAM
GFCI DEVICE
H = HORIZONTALLY MOUNTED
S = MANUALLY CONTROLLED
SP / TVSS = SURGE PROTECTION
TR = TAMPER RESISTANT
TV = TELEVISION
USB = USB/DUPLEX
WP = WEATHER PROOF COVER
WR = WEATHER RESISTANT
MULTI-OUTLET ASSEMBLY
TELEPHONE OUTLET
DATA OUTLET
MULTI-SERVICE OUTLET; TELEPHONE AND DATA
ABOVE COUNTER, TYP
WALL, TYP
FLOOR, TYP
MULTI-SERVICE POWER POLE WITH TELEPHONE, DATA
AND POWER OUTLETS A = TYPE, REFER TO PLANS,
SCHEDULES AND SPECIFICATIONS
MULTI-SERVICE FLOOR BOX WITH TELEPHONE, DATA AND
POWER OUTLETS A = TYPE, REFER TO PLANS, SCHEDULES
AND SPECIFICATIONS
POKE THROUGH, A = TYPE, REFER TO PLANS, SCHEDULES
AND SPECIFICATIONS
THERMOSTAT
CEILING/FLOOR MOUNT JUNCTION/OUTLET BOX
WALL MOUNT JUNCTION/OUTLET BOX
#
GFCI
EM
ALC
BTS
OR
OR
#
###A 3P
###AS 3P
###AF FRS
###A 3P
###AS 3P
###AF
FRS NEMA #
ELECTRICAL ONE-LINE & RISER DIAGRAM
SWITCH (RATING AS INDICATED)
DRAWOUT CIRCUIT BREAKER (RATINGS AS INDICATED)
FUSED SWITCH (RATING, POLES AND FUSE TYPE AS
INDICATED)
COMBINATION FUSED SWITCH/STARTER AND STARTER SIZE
CIRCUIT BREAKER (RATINGS AS INDICATED)
COMBINATION CIRCUIT BREAKER/STARTER AND STARTER
SIZE
PANELBOARD, SINGLE OR MULTI-SECTION (REFER TO
SCHEDULES)
ISOLATED POWER PANELBOARD W/ INTEGRAL
TRANSFORMER (REFER TO SCHEDULES)
TRANSFORMER (TYPE AND RATINGS AS INDICATED)
SHIELDED TRANSFORMER (TYPE AND RATINGS AS INDICATED)
AUTOMATIC TRANSFER SWITCH (RATINGS AS INDICATED)
AUTOMATIC TRANSFER SWITCH WITH BYPASS (RATINGS AS
INDICATED)
GENERATOR (RATINGS AS INDICATED)
NON-SEPARATELY DERIVED SOURCE
OR
SEPARATELY DERIVED SOURCE
SWITCHGEAR, SWITCHBOARD AND/OR
DISTRIBUTION PANELBOARD (TYPE, RATING, DEVICES
AND ACCESSORIES AS
INDICATED)
COMBINATION DIGITAL VOLT METER/AMMETER
CIRCUIT IDENTIFICATION (REFER TO CIRCUIT SCHEDULE)
GROUND FAULT RELAY
PHASE FAILURE RELAY
KIRK-KEY INTERLOCK (# INDICATES KEY PAIR)
SHUNT TRIP
AMMETER (RANGE AS SPECIFIED OR REQUIRED)
VOLTMETER (RANGE AS SPECIFIED OR REQUIRED)
UTILITY METER (AS REQUIRED BY UTILITY)
AMMETER SWITCH
VOLTMETER SWITCH
WATT-HOUR METER, "D" DENOTES DEMAND REGISTER, "15"
DENOTES MINUTES OF DEMAND INTERVAL
CURRENT TRANSFORMER RATING AS SPECIFIED OR
REQUIRED
POTENTIAL TRANSFORMER RATING AS SPECIFIED OR
REQUIRED
SURGE-PROTECTIVE DEVICE
GROUND CONNECTION
GROUND CONNECTION WITH TEST WELL
GROUND ROD
LIGHTNING ARRESTER
CAPACITOR
CONTACT (OPEN OR CLOSED)
HEATER
MOTOR
BLOCK LOAD KW OR KVA
FAULT POINT REFERENCED IN SHORT CIRCUIT CURRENT AND
VOLTAGE DROP SPREADSHEET
###A
3P
NEMA #
###AS 3P
FRS NEMA #
ELECTRICAL SYMBOLS
THIS IS A MASTER LEGEND AND NOT ALL SYMBOLS OR ABBREVIATIONS ARE USED. V3.00
ABBREVIATIONS
A
A
A
T
JJ
84"
48"
60"
48"
60"
120"
60"
36"
48"
48"
144"
16"
24"
24"
27"
+6" ABOVE BACKSPLASH/COUNTER, 40" MAX
44"
48"
CEILING
48"
48"
44"
SAME AS ADJACENT DEVICE, UNO
6"
REFER TO ARCH DRAWINGS
84"
MDP SWITCHBOARD ELEC ROOM
HP
FP#
WH
SPD
15 UTILITY
METER
D
M
VS
AS
###
VM AM
DIGITAL
### AMPS
F#
TX##
TX##
###A
ATS#
ATS# (W/BYPASS)
###A
480Y/277V, 3Ø, 4W
###A, 3P M/G
##KW GENERATOR
ATS# (W/BYPASS)
480Y/277V 3Ø 4W
GFR
KK#
ST
PFR
AM
VM
##
LINETYPE LEGEND
THROUGHOUT THE DRAWINGS DIFFERENT LINETYPES ARE USED IN
COMBINATION WITH THE SYMBOLS TO INDICATE THE STATUS OF ITEMS AS
EXISTING, TO BE DEMOLISHED, TO BE INCLUDED AS PART OF NEW WORK AND/OR ITEMS WHICH ARE ANTICIPATED TO BE PROVIDED IN THE FUTURE.
THE STATUS OF ITEMS USING THESE LINETYPES ARE RELATIVE TO THE VIEW IN WHICH THEY APPEAR. PHASING SHOWN IN DRAWINGS IS NOT
INTENDED TO FULLY DESCRIBE ALL NECESSARY CONSTRUCTION PHASING,
WHICH IS DETERMINED BY THE CONTRACTOR AS PART OF THEIR
RESPONSIBILITIES. ANY SUCH PHASES DESCRIBED IN THE CONSTRUCTION
DOCUMENTS ARE GENERAL AND ONLY INTENDED TO INDICATE A BROAD ORDER FOR THE SAKE OF DESCRIBING THE PROJECT. THE FOLLOWING
LINETYPES MAY BE USED ON ANY DEVICE, EQUIPMENT, NOTE, LINE, SHAPE, ETC.
EXISTING
DEMOLISH
NEW
FUTURE
ARTICLE 700 OR
LIFE SAFETY
ARTICLE 701 OR
CRITICAL / EQUIPMENT BRANCH
ARTICLE 702 OR
OPTIONAL
BRANCH CIRCUIT CONDUCTOR TABLE
PROVIDE ADDITIONAL CONDUCTORS THROUGH ENTIRE CIRCUIT
(SWITCHED, UNSWITCHED/EM, ETC.) AS INDICATED
THROUGHOUT CONSTRUCTION DOCUMENTS AND AS REQUIRED
FOR A COMPLETE AND WORKING SYSTEM.
REFER TO SPECIFICATIONS FOR LIMITATIONS ON SHARING
NEUTRAL (GROUNDED) CONDUCTORS. DO NOT CIRCUIT AS A
MULTI-WIRE BRANCH CIRCUIT, UNO.
PROVIDE ADDITIONAL ISOLATED GROUNDING CONDUCTORS
WHERE INDICATED.
REFER TO SPECIFICATIONS, PLANS, NOTES, WIRING AND
CONTROL DIAGRAMS FOR ADDITIONAL CIRCUITING
REQUIREMENTS.
WHERE TICK MARKS ARE NOT SHOWN, THE FOLLOWING SHALL GOVERN:
# OF POLES
1P
2P
3P
HOT (PHASE)*
(1)
(2)
(3)
*
**
***
CONDUCTOR TICK MARK LEGEND
GROUNDING***
NEUTRAL
(GROUNDED)**
(1) UNO
(1) UNO
(1) UNO
(1)
(1)
(1)
SWITCHED HOT (PHASE) CONDUCTORS (SHOWN
TRAILING NEUTRAL)
NEUTRAL (GROUNDED) CONDUCTOR
UNSWITCHED HOT (PHASE) CONDUCTORS (SHOWN
LEADING NEUTRAL)
NOTE: HASH MARKS INDICATE QUANTITY OF
CONDUCTORS
EQUIPMENT GROUNDING CONDUCTOR IN CONDUIT
(GREEN INSULATION OR BARE)
ISOLATED GROUNDING CONDUCTOR IN CONDUIT
(GREEN INSULATION WITH YELLOW TRACER)
WHERE TICK MARKS ARE SHOWN, THE FOLLOWING SHALL GOVERN:
EM
EM
[R#] P1
# # # #
CL##
C#
D#
P#
LC
PS#
R##
TS#
JJ
* SYMBOL DEMONSTRATED WITH DUPLEX RECEPTACLE, WHEN USED IN
COMBINATION WITH OTHER DEVICES MEANING IS SIMILAR FOR THOSE DEVICE TYPES.
REFER TO LIGHTING CONTROL DEVICE SCHEDULE FOR MORE
INFORMATION.
[#]
G
OR
IG
REFER TO LIGHT FIXTURE SCHEDULE FOR MORE INFORMATION
CALL OUTS
ENLARGED PLAN CALLOUT
NOT IN SCOPE
FAXTEL
PROJECT NO.
Copyright C
ISSUED BY:
ISSUED DATE:
SHEET TITLE:
DISCIPLINE - CATEGORY - SUB CATEGORY - SHEET
REVISIONS
PROJECT NORTH
®
(913) 742-5000 (913) 742-5001
LENEXA, KS 66214
8345 LENEXA DRIVE, SUITE 300
WWW.HENDERSONENGINEERS.COM
®
®
ARCHITECT OF RECORD
POPULOUS
4800 Main Street Suite 300
Kansas City, MO 64112
816-221-1500
HVAC and LIGHTING ENGINEER
HENDERSON ENGINEERS
8345 Lenexa Drive
Lenexa, KS 66214
913-742-5000
Sacramento Convention Center Ballroom B Upgrades
9/7/2021 10:19:36 AM
CONSTRUCTION
DOCUMENTS
September 8, 2021
ELECTRICAL
NOTES, SYMBOLS,
& ABBREVIATIONS
E0-0
17.4465
09/08/2021
2019
RUSSELL J. MURDOCK
1650002727
1400 J St, Sacramento, CA 95814
NO. DATE DESCRIPTION
09/08/2021
FAXTEL
PROJECT NO.
Copyright C
ISSUED BY:
ISSUED DATE:
SHEET TITLE:
DISCIPLINE - CATEGORY - SUB CATEGORY - SHEET
REVISIONS
PROJECT NORTH
®
(913) 742-5000 (913) 742-5001
LENEXA, KS 66214
8345 LENEXA DRIVE, SUITE 300
WWW.HENDERSONENGINEERS.COM
®
®
ARCHITECT OF RECORD
POPULOUS
4800 Main Street Suite 300
Kansas City, MO 64112
816-221-1500
HVAC and LIGHTING ENGINEER
HENDERSON ENGINEERS
8345 Lenexa Drive
Lenexa, KS 66214
913-742-5000
Sacramento Convention Center Ballroom B Upgrades
9/7/2021 10:19:39 AM
CONSTRUCTION
DOCUMENTS
September 8, 2021
TITLE 24
COMPLIANCE
FORMS
E0-1
17.4465
09/08/2021
2019
RUSSELL J. MURDOCK
1650002727
1400 J St, Sacramento, CA 95814
NO. DATE DESCRIPTION
09/08/2021
FAXTEL
PROJECT NO.
Copyright C
ISSUED BY:
ISSUED DATE:
SHEET TITLE:
DISCIPLINE - CATEGORY - SUB CATEGORY - SHEET
REVISIONS
PROJECT NORTH
®
(913) 742-5000 (913) 742-5001
LENEXA, KS 66214
8345 LENEXA DRIVE, SUITE 300
WWW.HENDERSONENGINEERS.COM
®
®
ARCHITECT OF RECORD
POPULOUS
4800 Main Street Suite 300
Kansas City, MO 64112
816-221-1500
HVAC and LIGHTING ENGINEER
HENDERSON ENGINEERS
8345 Lenexa Drive
Lenexa, KS 66214
913-742-5000
Sacramento Convention Center Ballroom B Upgrades
9/7/2021 10:19:42 AM
CONSTRUCTION
DOCUMENTS
September 8, 2021
TITLE 24
COMPLIANCE
FORMS
E0-2
17.4465
09/08/2021
2019
RUSSELL J. MURDOCK
1650002727
1400 J St, Sacramento, CA 95814
NO. DATE DESCRIPTION
09/08/2021
10/07/2021
QTM
37 43
49 50
EB ED EF EG EH EK EM EN EO EQ
34 'D' 'D' 'D'
'D' 'E' 'D'
'D' 'D' 'D'
'D' 'D' 'D'
'C''C''C''C'
'C'
'C''C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'E'
'D' 'D' 'D'
'D' 'D'
'D' 'D' 'D'
'D' 'D' 'D'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C' 'C''E''C' 'E' 'C''C' 'C' 'E' 'C''C' 'C' 'E''C' 'C'
'D' 'D' 'D' 'D'
'D' 'D' 'D' 'D'
'D' 'D' 'D' 'D'
'C' 'C' 'C' 'C' 'C'
'C' 'C' 'E' 'C' 'C'
'C' 'C' 'C' 'C' 'C'
'D' 'D' 'D' 'D'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'D' 'D' 'D' 'D'
'D' 'D' 'D' 'D'
'D' 'D' 'D' 'D'
'C' 'C' 'C' 'C' 'C'
'C' 'C' 'E' 'C' 'C'
'C' 'C' 'C' 'C' 'C'
'D' 'D' 'D' 'D'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'E'
'D' 'D' 'D'
'D' 'D'
'D' 'D' 'D'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'D'
'D' 'D'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'E'
'D' 'D' 'D'
'D' 'D'
'D' 'D' 'D'
'D' 'D' 'D'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'E'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'D' 'D' 'D' 'D'
'D' 'D' 'D' 'D'
'D' 'D' 'D' 'D'
'D' 'D' 'D' 'D'
'C' 'C' 'C' 'C' 'C'
'C' 'C' 'E' 'C' 'C'
'C' 'C' 'C' 'C' 'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'D' 'D' 'D' 'D'
'D' 'D' 'D' 'D'
'D' 'D' 'D' 'D'
'D' 'D' 'D' 'D'
'C' 'C' 'C' 'C' 'C'
'C' 'E' 'C' 'C'
'C' 'C' 'C' 'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
'C'
(TYP)
1 (TYP)
2 (TYP)
3 4 4 4 4
4 4
4 5
6 6 6 6
4 4
4 7
4 4 4 4
6 6 6 6
8 (TYP)
5 (TYP)
5 MS
(TYP)
9 MS
MS
MS
MSMS
MS
MS
FAXTEL
PROJECT NO.
Copyright C
ISSUED BY:
ISSUED DATE:
SHEET TITLE:
DISCIPLINE - CATEGORY - SUB CATEGORY - SHEET
REVISIONS
PROJECT NORTH
®
(913) 742-5000 (913) 742-5001
LENEXA, KS 66214
8345 LENEXA DRIVE, SUITE 300
WWW.HENDERSONENGINEERS.COM
®
®
ARCHITECT OF RECORD
POPULOUS
4800 Main Street Suite 300
Kansas City, MO 64112
816-221-1500
HVAC and LIGHTING ENGINEER
HENDERSON ENGINEERS
8345 Lenexa Drive
Lenexa, KS 66214
913-742-5000
Sacramento Convention Center Ballroom B Upgrades
9/7/2021 10:20:09 AM
CONSTRUCTION
DOCUMENTS
September 8, 2021
LIGHTING DEMO
PLAN BALLROOM B
ED1-1
17.4465
09/08/2021
2019
RUSSELL J. MURDOCK
1650002727
1400 J St, Sacramento, CA 95814
1/8" = 1'-0"1 LIGHTING DEMO PLAN BALLROOM B
ELECTRICAL PLAN NOTES:
1 REMOVE EXISTING DOWNLIGHT AND ALL ASSOCIATED
EQUIPMENT BACK TO SOURCE OR NEAREST DEVICE TO
REMAIN. TYPICAL OF ALL TYPE 'D'.
2 REMOVE EXISTING DOWNLIGHT AND ALL ASSOCIATED
EQUIPMENT. CIRCUITING TO FIXTURE LOCATION TO REMAIN
FOR NEW INSTALLATION IN SAME LOCATION. TYPICAL OF
ALL TYPE 'C'.
3 REMOVE EXISTING DOWNLIGHT AND ALL ASSOCIATED
EQUIPMENT. EMERGENCY PANEL CIRCUITING TO REMAIN
FOR NEW INSTALLATION IN SAME LOCATION. TYPICAL OF
ALL TYPE 'E'.
4 REMOVE EXISTING NEON AND ALL ASSOCIATED EQUIPMENT.
CIRCUIT TO FIXTURE LOCATION TO REMAIN FOR NEW
INSTALLATION IN SAME LOCATION.
5 REMOVE EXISTING FLUORESCENT STRIP LIGHT FIXTURE
AND ALL ASSOCIATED EQUIPMENT. CIRCUIT TO FIXTURE
LOCATION TO REMAIN FOR NEW INSTALLATION IN SAME
LOCATION.
6 REMOVE EXISTING TRACK HEAD LIGHT FIXTURES. TRACK
TO REMAIN.
7 EXISTING LUTRON QUANTUM EQUIPMENT TO REMAIN.
RELOCATE AS PART OF NEW WORK.
8 EXISTING LUTRON GP-72 DIMMING PANELS, 1D-U AND 2D- U, NO CHANGE INTENDED. CONTRACTOR TO COORDINATE
WHERE RE-WIRING IS REQUIRED BASED ON EXISTING
CONDITIONS AND LIGHT FIXTURE DEMO WORK.
9 EXISTING LIGHTING CONTROL SYSTEM WALL STATION TO
REMAIN. LOCATIONS SHOWN ARE DIAGRAMMATIC. VERIFY
QUANTITY WITH ONSITE CONDITIONS.
NO. DATE DESCRIPTION
09/08/2021
LIGHTING
CONTROLS
PROCESSOR
NOTES:
1. REFER TO LIGHTING CONTROL DEVICE SCHEDULE FOR DEVICE AND EQUIPMENT SPECIFICATIONS.
2. DETAIL IS DIAGRAMMATIC AND IS BASED ON PHAROS . THIS REPRESENTS THE GENERAL SCOPE OF WORK AND LOCATION OF DEVICES IN RELATION TO EACH OTHER ALONG THE POWER CIRCUIT. DIAGRAMS MAY BE DIFFERENT FOR ALLOWED EQUIVALENT MANUFACTURERS. ELECTRICAL CONTRACTOR SHALL COORDINATE FULL SYSTEM REQUIREMENTS WITH SELECTED MANUFACTURER.
PROVIDE ALL PARTS AND PIECES REQUIRED FOR A FULLY FUNCTIONAL SYSTEM. REFER TO FINAL APPROVED MANUFACTURER'S INSTALLATION INSTRUCTIONS AND WIRING DIAGRAMS FOR INSTALLATION.
3. CIRCUITING SHOWN ON PLAN(S) CORRESPONDS TO LIGHTING CONTROL INTENT. IF CIRCUITING IS FIELD-MODIFIED, ENSURE THAT SYSTEM PROGRAMMING WITH REVISED CIRCUITING MEETS ORIGINAL LIGHTING CONTROL INTENT.
4. INTEGRAL TIMECLOCK SHALL BR PROGRAMMABLE WITH 7 DAY / HOLIDAY SCHEDULING, AND HAVE 24 HOUR BATTERY BACK-UP. LIGHTING CONTROL SYSTEM SHALL COMPLY WITH ALL LOCAL AND STATE ENERGY CODES.
5. COORDINATE WITH OWNER TIMECLOCK SCHEDULES. PROVIDE GENERAL CONTRACTOR WITH OPERATIONS MANUALS FOR ALL COMPONENTS OF LIGHTING CONTROL SYSTEM.
7. PROVIDE SYSTEM PROGRAMMING AS REQUIRED FOR SYSTEM TO OPERATE PER THESE CONTRACT DOCUMENTS. PROGRAMMING SHALL BE BY PHAROS FEILD TECHNICIAN PROVIDING COLOR SCENES AND MACROS FOR EACH PARTITIONED AND COMBINED SPACE. • STATIC COLOR SCENES
1. RED
2. HOT PINK
3. DARK ORANGE
4. GOLD
5. GREEN
6. AQUA
7. BLUE
8. PURPLE
• MACRO SCENES
1. RAINBOW FADE
2. COOL FADE
3. WARM FADE
REFER TO BALLROOM A SETTINGS TO MATCH IN A SIMILAR MANNER.
SCENES ARE TO ESTABLISH INITIAL SET-UP. OWNER TO REVIEW, PROVIDE ADJUSTMENT COMMENTS, AND APPROVAL UPON FINAL REVIEW.
9. PROVIDE SYSTEM COMMISSIONING AS REQUIRED PER ENERGY CODE.
10. IF CONSTRUCTION IS COMPLETED IN PHASES, MANUFACTURER SHALL DEDICATE A SINGLE TECHNICIAN TO PROGRAM INSTALLED DEVICES AFTER EACH PHASE AND SHALL NOTIFY CONTRACTOR IMMEDIATELY OF ANY ISSUES. THE SAME TECHNICIAN SHALL ALSO
PERFORM THE FUNCTIONAL LIGHTING CONTROL TESTING AFTER ALL CONSTRUCTION PHASES ARE COMPLETE AND ENSURE THE SYSTEM IS FULLY FUNCTIONAL.
TO COMPUTER (FOR
COMMISSIONING
ONLY)
SITE VISITS:
1. CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL SITE VISITS WITH MANUFACTURER PER MANUFACTURER'S REQUIRED TIME FRAME.
2. MANUFACTURER SHALL PROVIDE PRE-CONSTRUCTION SERVICES TO ASSIST CONTRACTOR IN UNDERSTANDING SYSTEM REQUIREMENTS AND COMPONENTS PRIOR TO INSTALLING SYSTEM. MANUFACTURER SHALL VISIT THE SITE WHEN THE CONTRACTOR IS BEGINNING TO ROUGH-IN AND BEFORE INSTALLING THE SYSTEM. INCLUDE A MINIMUM OF 1 SITE VISIT(S).
3. MANUFACTURER SHALL PROVIDE FUNCTIONAL LIGHTING CONTROL TESTING (COMMISSIONING). INCLUDE A MINIMUM OF 1 SITE VISIT(S). ALL VISITS SHALL OCCUR AFTER NORMAL BUSINESS HOURS. VISIT SHALL INCLUDE AN ADEQUATE NUMBER OF DAYS ON SITE PER COMPLEXITY OF SYSTEMS AND PROGRAMMING REQUIREMENTS.
4. MANUFACTURER SHALL PROVIDE ON-SITE TRAINING(S)FOR EMPLOYEES AFTER THE SYSTEM HAS BEEN COMMISSIONED AND FINAL ADJUSTMENTS TO SCENES COMPLETED PER OWNER REVIEW CO MMENTS. INCLUDE A MINIMUM OF 1 SITE VISIT(S).
LINE VOLTAGE WIRING
DIN RAIL MOUNT ENCLOSURE
CONTAINING PROCESSOR,
POWER SUPPLY, AND ANY
OTHER ASSOCIATED
EQUIPMENT AS REQUIRED.
LOCATE IN EXISTING
CORRIDOR E2F37.
LAN FOR INTERNET INTERFACE.
COORDINATE IP ON BUILDING
INFRASTRUCTURE NETWORK
WITH OWNER, IF REQUESTED.
CONNECTION TO ETHERNET NOT
REQUIRED, UNLESS AT THE
REQUEST OF THE OWNER.
LOW VOLTAGE WIRING (CONFIRM
TYPE WITH MANUFACTURER)
RDMEXT
PSU
TPC
SURFACE MOUNT TOUCH
SCREEN CONTROL PANEL
LOCATE IN EXISTING
SERVICE CORRIDOR E2F37
D
BALLROOM B1
TO RGBW LIGHT FIXTURES
BACKLIGHT: DMX CHANNELS 1-4
COVE: DMX CHANNELS 5-8
D D D
T
LED POWER SUPPLY(S)
QUANITY IS GENERIC
T T T
T T T T
D D D D
BALLROOM B3
TO RGBW LIGHT FIXTURES
BACKLIGHT: DMX CHANNELS 9-12
COVE: DMX CHANNELS 13-16
BALLROOM B5
TO RGBW LIGHT FIXTURES
BACKLIGHT: DMX CHANNELS 17-20
COVE: DMX CHANNELS 21-24
BALLROOM B7
TO RGBW LIGHT FIXTURES
BACKLIGHT : DMX CHANNELS 25-28
COVE: DMX CHANNELS 29-32
BALLROOM B2
TO RGBW LIGHT FIXTURES
BACKLIGHT: DMX CHANNELS 33-36
COVE: DMX CHANNELS 37-40
BALLROOM B4
TO RGBW LIGHT FIXTURES
BACKLIGHT: DMX CHANNELS 41-44
COVE: DMX CHANNELS 45-48
BALLROOM B6
TO RGBW LIGHT FIXTURES
BACKLIGHT: DMX CHANNELS 49-52
COVE: DMX CHANNELS 53-56
BALLROOM B8
TO RGBW LIGHT FIXTURES
BACKLIGHT : DMX CHANNELS 57-60
COVE: DMX CHANNELS 61-64
FULL
BALLROOM
NORTH
BALLROOM
SOUTH
BALLROOM
B1 & B3
BALLROOM
B5 & B7
BALLROOM
B2 & B4
BALLROOM
B6 & B8
BALLROOM
B1
BALLROOM
B3
BALLROOM
B5
BALLROOM
B7
BALLROOM
ROOM SELECTION PAGE
B4
BALLROOM
B6
BALLROOM
B8
BALLROOM
ALL
OFF
B2
BALLROOM
RED HOT PINK DARK
ORANGE
GOLD GREEN AQUA
SCENE SELECTION PAGE
BLUE PURPLE RAINBOW
FADE
WARM
FADE
ALL
OFF
COOL
FADE
FULL BALLROOMBACK COLOR PICKER
SIMILAR FOR EACH ROOM SELECTION
COLOR SELECTION PAGE
FULL BALLROOMBACK HOME
SIMILAR FOR EACH ROOM SELECTION
6. PERIMETER WALL DMX CHANNEL ZONING: EACH OF THE (8) PERIMETER BALLROOM ENTRY DETAIL SHALL BE ZONED TO HAVE (2) 4- CHANNEL DMX ZONES, (16) DMX ZONES. (1) 4-CHANNEL ZONE FOR THE TOP BACK-LIT WALL DETAIL PORTION. AND, (1) ZONE 4- CHANNEL ZONE FOR THE UPLIGHT COVE PORTION, (64) DMX CHANNELS.
AT EACH DETAIL THE TOP AND BOTTOM ZONES SHALL BE INDEPENDANTLY CONTROLLED FOR PROGRAMMING SCENE PURPOSES.
THOUGH EACH ZONE IS COMPRISED OF MULTIPLE FIXTURE UNITS, IT IS THE INTENT THAT THE ALL THE BACK-LIT LIGHT FIXTURES OR UPLIGHT COVE LIGHT FIXTURES OF A SPECIFIC ZONE BE PROGRAMMED TO THE ASSIGNED (4) DMX CHANNELS.
8. LUTRON LIGHTING SYSTEM SHALL NOT BE ABLE TO RECALL OR "TRIGGER" DMX LIGHTING SCENES. ALL PROGRAMMING AND CONTROL INTERFACE ACCESS OF THE DMX SYSTEM WILL BE THROUGH THE TOUCHSCREEN (TPC) AND SHOW CONTROLLER (EXT).
FAXTEL
PROJECT NO.
Copyright C
ISSUED BY:
ISSUED DATE:
SHEET TITLE:
DISCIPLINE - CATEGORY - SUB CATEGORY - SHEET
REVISIONS
PROJECT NORTH
®
(913) 742-5000 (913) 742-5001
LENEXA, KS 66214
8345 LENEXA DRIVE, SUITE 300
WWW.HENDERSONENGINEERS.COM
®
®
ARCHITECT OF RECORD
POPULOUS
4800 Main Street Suite 300
Kansas City, MO 64112
816-221-1500
HVAC and LIGHTING ENGINEER
HENDERSON ENGINEERS
8345 Lenexa Drive
Lenexa, KS 66214
913-742-5000
Sacramento Convention Center Ballroom B Upgrades
9/7/2021 10:19:52 AM
CONSTRUCTION
DOCUMENTS
September 8, 2021
ELECTRICAL
SCHEDULES,
CONTROLS AND
DETAILS
E1-1
17.4465
09/08/2021
2019
RUSSELL J. MURDOCK
1650002727
1400 J St, Sacramento, CA 95814
REQUIRED TO COMPLY WITH THE SYSTEM'S DESIGN REQUIREMENTS.
AND/ OR ENGINEERING PLAN FOR CORRECT NUMBER OF FIXTURES WITH AND RELATIVE LOCATION OF TRACK HEADS. QUANTITIES INDICATED PER TRACK. CONTRACTOR SHALL ALSO ORDER ALL NECESSARY MISCELLANEOUS EQUIPMENT AS 8 CONTRACTOR SHALL CONFRIM EXISTING TRACK SYSTEM EQUIPMENT FOR PRIOR TO FINAL ORDER FOR MANUFACTURER TO PROVIDE COMPATIBLE TRACK ADAPTOR TYPE FITTING. CONTRACTOR TO REFER TO REFLECTED CEILING PLAN WITH SYSTEM INCLUDING JUMPER CABLES WHEN FIXTURES ARE NOT ABLE TO BE PHYSICALLY ABUTTED NEXT TO EACH OTHER. REFER TO SPECIFIC FIXTURE SPECIFICATION REGARDING OPTICS.
AND WATTAGE PER LINEAL FOOT AS NOTED PER EACH FIXTURE TYPE REFERENCED ON THE SCHEDULE. MANUFACTURER TO COORDINATE WITH CONTRACTOR TO ENSURE ALL MISCELLANEOUS ELECTRICAL COMPONENTS ARE FURNISHED 7 CONTRACTOR TO PROVIDE A COMPLETE AND OPERATIONAL LINE VOLTAGE LED SYSTEM INCLUDING LEADER CABLE, SPECIFIC MOUNTING HARDWARE TO PROVIDE STRAIGHT RUNS WITHIN COVES, WIRING COMPARTMENT AT START OF RUN TRIAC OR AS OTHERWISE INDICATED FOR COORDINATION WITH EXISTING LUTRON QUANTUM EQUIPMENT AND DIMMING LOW RANGES VALUE AS INDICATED. 6 COORDINATE LED FIXTURE'S INTEGRAL DIMMING REQUIREMENTS WITH DIMMING SYSTEM. AS PER BASIS OF DESIGN, LED MANUFACTURERS TO FURNISH DOWNLIGHT FIXTURES AND LINEAR COVE LED SYSTEMS WITH 2-WIRE HI-LUME DIMMING, A COMPLETE AND OPERATIONAL SYSTEM AS PER DESIGN INTENT AND SHALL COORDINATE WITH WINDOW MULLION DETAILS WHERE REQUIRED.
IP20 MALE/FEMALE CONNECTORS. NO FIELD SOLDERING CONNECTIONS SHALL BE ALLOWED. MANUFACTURER TO COORDINATE WITH CONTRACTOR REGARDING OTHER MISCELLANEOUS MOUNTING OR ELECTRICAL EQUIPMENT FOR DROP. INDICATED LOCATIONS ON PLANS ARE FOR REFERENCE ONLY. LENGTH OF LED RUN TO BE COORDINATED WITH DETAILS. FOR LOW VOLTAGE LED SYSTEMS MANUFACTURER TO FURNISH END OF RUN WITH 2-WIRE QUICK-DISCONNECT OF LINEAR RUN INDICATED PER PLANS. REMOTE TRANSFORMER/ DRIVER TO BE LOCATED IN ACCESSIBLE, WELL VENTILATED AREA VERIFIED BY FIELD CONDITIONS PRIOR TO INSTALLATION TO REDUCE VOLTAGE 5 CONTRACTOR TO PROVIDE A COMPLETE AND OPERATIONAL LOW VOLTAGE LED SYSTEM INCLUDING SPECIFIED EXTRUSION, REMOTE 24 VOLT TRANSFORMER/ DRIVER APPROPRIATELY SIZED FOR GIVEN LOAD 4 FIXTURE TO BE SECURED TO STRUCTURE ABOVE AND NOT TO ACOUSTIC CEILING. CONTRACTOR RESPONSIBLE FOR PROVIDING MISCELLANEOUS MOUNTING MATERIAL AT STRUCTURAL CEILING TO COMPLY WITH SEISMIC REQUIREMENTS.
MANUFACTURER TO FURNISH LED ARRAY WITH HIGH CRI CHIP OF 90 OR BETTER. IF NOT INDICATED, STANDARD 80+ CRI ACCEPTABLE. 3 REFER TO SPECIFIC COLOR TEMPERATURE OR COLOR OF LED CHIPS OR DIODES AS INDICATED. PROVIDE ONLY THAT COLOR TEMPERATURE OF LED ARRAY. FOR COLOR LED, VERIFY WITH ARCHITECT AND/ OR OWNER. WHERE INDICATED, TESTING INFORMATION. FURTHERMORE, ALTERNATE MANUFACTURERS TO COMPLY WITH OPTICAL SYSTEM REQUIREMENTS DEFINED IN BASIS OF DESIGN FIXTURE. 2 MANUFACTURER TO FURNISH FIXTURE WITH LED PHOTOMETRIC INFORMATION DEFINING LUMEN OUTPUT AND COMPLYING WITH IES LM-79 AND LM-80 TESTING PROCEDURES. ALTERNATE MANUFACTURERS WILL NOT BE ACCEPTED WITHOUT WELL-VENTILATED LOCATIONS.
INDICATED LOCATIONS OF REMOTE DRIVERS ON DOCUMENTS IS FOR REFERENCE AND INTENT ONLY. CONTRACTOR TO RE-LOCATE AS NEEDED BASED ON FIELD CONDITIONS, HOWEVER, TRANSFORMERS TO BE LOCATED IN ACCESSIBLE, MISCELLANEOUS ELECTRICAL COMPONENTS TO COMPLY WITH DESIGN INTENT. FOR LOW VOLTAGE COVE SYSTEMS, REMOTE DIMMING DRIVERS NOT TO EXCEED LENGTH FROM END OF RUN AS PER MANUFACTURER'S REQUIREMENTS.
COORDINATE WITH LIGHTING MANUFACTURER'S REPRESENTATIVE TO DETERMINE COMPONENT PARTS. FEEDS TO START AT END OF RUN OR MIDDLE OF RUN AS REQUIRED. MANUFACTURER SHALL FURNISH TO CONTRACTOR ALL DETERMINED IN FIELD FROM LINEAL FOOTAGE DIMENSIONS TO MAXIMIZE EXTENT OF LENGTH STARTING IN CENTER OF COVE AND MOVING TOWARD ENDS, USING LONGEST AVAILABLE LED SECTION TO MAXIMIZE LIGHTED SECTION OF COVE. 1 REFER TO SHEET E2.1 AND EXISTING CONDITIONS. WHERE DETAILED, TOP OF COVE FIXTURE'S LENS TO BE FLUSH WITH TOP LIP OF COVE DETAIL FOR MAXIMUM EFFICIENCY OF FIXTURE. IN COVE CONDITIONS, EXACT LENGTHS TO BE LIGHT FIXTURE NOTES:
IS TAKEN FROM THE LATEST EDITION OF THE CALIFORNIA BUILDING ENERGY EFFICIENCY STANDARDS NONRESIDENTIAL COMPLIANCE MANUAL, (APPENDIX NA8 - ILLUMINANCE CATEGORIES AND LUMINAIRE POWER).
N. THE LIGHT FIXTURES WATTAGE VALUES LISTED ABOVE ARE THE TOTAL INPUT WATTS PER LIGHT FIXTURE INCLUDING ALL LOSSES AND BALLAST FACTORS AND WHEN AVAILABLE EFFICIENCY REGULATIONS.
LOCAL REQUIREMENTS. ADDITIONALLY, ALL LIGHT FIXTURES, EXIT SIGNS AND LIGHTING CONTROLS AND SHALL COMPLY WITH THE LATEST ADOPTED EDITION OF THE CALIFORNIA APPLIANCE COMMISION AND SHALL COMPLY WITH THE LATEST ADOPTED EDITION OF THE CALIFORNIA BUILDING ENERGY EFFICIENCY STANDARDS NONRESIDENTIAL COMPLIANCE MANUAL, (TITLE 20, 24) AND ANY OTHER STATE AND M. ALL AUTOMATIC LIGHTING CONTROL DEVICES AND APPLICABLE FLUORESCENT LUMINAIRES (INCLUDING LAMPS AND BALLASTS) SHALL BE CERTIFIED TO THE CALIFORNIA ENERGY L. VERIFY QUANTITIES, MODEL NUMBERS AND DESCRIPTIONS WITH MANUFACTURER PRIOR TO PLACING ORDER.
K. FIXTURES DESIGNATED AS HIGH CRI LED FIXTURES TO BE FURNISHED WITH A MINIMUM OF 90 CRI WITH MODULES FURNISHED BY XICATO, CREE, PHILIPS, OR BRIDGELUX WITH NO MORE THAN 2- MCADAMS ELLIPSES.
J. REFER TO DIVISION 26 SPECIFICATIONS FOR ACCEPTABLE LAMP AND BALLAST MANUFACTURERS AND ADDITIONAL INFORMATION.
I. CONTRACTOR SHALL PROVIDE ALL LIGHT FIXTURES UNLESS NOTED OTHERWISE.
AND SPECIFICATIONS IN CONJUNCTION WITH THE CATALOG NUMBER TO DETERMINE THE EXACT MATERIAL AND ACCESSORIES TO BE ORDERED. THE MANUFACTURERS LISTED ARE THE BASIS FOR THE DESIGN.
H. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER AND CATALOG NUMBERS ONLY. FIRST READ THE COMPLETE DESCRIPTION, NOTES BETWEEN THE ARCHITECTURAL AND ELECTRICAL LIGHTING PLANS.
G. REFER TO ARCHITECTURAL DRAWINGS AND DETAILS FOR EXACT LOCATIONS, MOUNTING HEIGHTS AND ADDITIONAL MOUNTING INFORMATION. CONTACT ARCHITECT IMMEDIATELY IF THERE ARE DISCREPANCIES SCREEN, UNIVERSE SHOW CONTROLLER AND DATA CONVERTER BOXES.
F. ALL RGBW/ RGB- LINEAR SERIES COLOR CHANGING LIGHT FIXTURES TO BE FURNISHED BY SAME MANUFACTURER TO ENSURE CONSISTENT ETHERNET DMX/RDM COMMUNICATION AND COORDINATION WITH PHAROS TPC AND EXT SERIES CONTROL E. VERIFY FINISH AND COLOR WITH ARCHITECT PRIOR TO PLACING ORDER.
D. VERIFY CEILING CONDITIONS AND COORDINATE LIGHT FIXTURE MOUNTING HARDWARE AND TRIMS NEEDED TO SUIT CEILING CONDITIONS PRIOR TO ORDERING.
C. FOR DIMMABLE LIGHT FIXTURES, REFER TO DIVISION 26 SPECIFICATIONS FOR MORE INFORMATION REGARDING CONTROL WIRING AND COMPATIBILITY.
B. PACKAGING OF LIGHT FIXTURES WILL NOT BE CONSIDERED OR APPROVED.
A. REPRESENTATIVE AGENTS SHALL BE ALLOWED TO OFFER MINI-LOT PRICING (MLP) FOR LIGHT FIXTURES SPECIFIED IN 265100 ONLY. REFER TO SPECIFICATION 265100 FOR DEFINITION, TERMS AND LIMITATIONS OF MLP.
GENERAL NOTES:
MANUFACTURER FIXTURE ALSO EQUIPPED WITH SNOOT AND CROSS-BLADE BAFFLE. FINSH SHALL BE WHITE.
BY DRIVER SUITABLE FOR TRAILING EDGE TRIAC/ELV DIMMER THAT IS CAPABLE OF PROVIDING 5% OF FULL OUTPUT. 4,375 LUMEN INTEGRAL ON/OFF SWITCH, OPTICAL SYSTEM YIELDING NOMINAL 12 DEGREE BEAM FOR NOMINAL 55,180MBCP, AND INTERNAL SPEQ-L-A17 48 WT TN1 120 SP 279 LE/TE SN CB 90 CRI, 2700K LOCKING YOKE CONFIGURATION. TRACK FIXTURE EQUIPPED WITH ADAPTOR FOR 1-CIRCUIT/ H-STYLE GLOBAL TRACK WITH 8 T1 AMERLUX - SPEQ TRACKHEAD SERIES LED LED 120 48 53 NOMINA L 5.125" DIAMETER X 11.128" DEEP TRACK MOUNTED LED TRACK FIXTURE WITH ALUMINUM HOUSING AND 2,3 JUMPER/ QUICK CONNECT CABLES. NO SOLDERING OF SECTIONS ALLOWED.
MANUFACTURER SIZED ACCORDINGLY PER COVE CONDITION. SYSTEM TO BE FIELD CUTTABLE AND SECTIONS TOGETHER VIA STANDARD IP20 STYLE BY SECOND BEAM SPREAD. SYSTEM TO INCLUDE REMOTE MLV TR IAC DIMMING 120/24V MAGNETIC TRANSFORMER POWER SUPPLY CONNECTED DRVWDIM24 60 170LM/ FOOT 24V FOOT FOOT LENS FOR STRAIGHT COVE RUNS W ITHIN CEILING DETAILS. CHANNEL AND LENS SHALL PRODUCE A NOMINAL 120DEGREE CHAS3 C WH RB 90 SWS220 1.5 30 1 90 CRI, 3000K PRIMARY PER PER LINEAR LED TAPE LIGHT SYS TEM WITHIN ALUMINUM HOUSING, MOUNTING CLIPS AND CLEAR 5 L4 ACOLYTE LED LED 120V 1.5 2 NOMINAL 1" WIDE X 5/8" HIGH X VARYING LENGTH SURFACE MOUNTED DRY LOCATION IP20 RATED LOW VOLTAGE LED 1,2,3 LIGHT FIXTURE IS NON-DIMMING. FIXTURE FINISH WHITE.
MANUFACTURER BALLROOM PREFUNCTION ENTRY. FIXTURE EQUIPPED WITH INTEGRAL 10 FOOT LONG STARTING CABLE.
BY ADJUSTABLE WALL MOUNTING 2-IN ARM BRACKET TO ALLOW FIXTURE TO BE AIMED UPWARD TO GRAZE CURVE WALL DETAIL AT 250LM/ FOOT FOOT FOOT STEEL HARDWARE AND INTEGRAL OPTI CAL SYSTEM YIELDING NOMINAL 30 VERTICAL X 60 DEGREE BEAM WITH INTEGRAL LOGIASHRAE 120 36 30K 30X60 WAM2 WH NO 90 CRI, 3000K PER PER SYSTEM WITH FACTORY PROVIDED HIG H 90+ CRI ARRAY, LOW COPPER CONTENT EXTRUDED ALUMINUM HOUSING, STAINLESS 6,7 L3 LUMENPULSE - LUMENFACADE SERIES LED LED 120 5 6 NOMINAL 2-3/16" WIDE X 2-3/4" HIGH X 3 FOOT LONG SURFACE MOUNTED LINE VOLTAGE LINEAR LED NARROW DISTRIBUTION 1 ,2,3 JUMPER/ QUICK CONNECT CABLES. NO SOLDERING OF SECTIONS ALLOWED.
MANUFACTURER SIZED ACCORDINGLY PER COVE CONDITION. SYSTEM TO BE FIELD CUTTABLE AND SECTIONS TOGETHER VIA STANDARD IP20 STYLE BY SECOND BEAM SPREAD. SYSTEM TO INCLUDE REMOTE MLV TR IAC DIMMING 120/24V MAGNETIC TRANSFORMER POWER SUPPLY CONNECTED DRVWDIM24 60 330LM/ FOOT 24V FOOT FOOT LENS FOR STRAIGHT COVE RUNS A ND SEGMENTED WALL DETAIL. CHANNEL AND LENS SHALL PRODUCE A NOMINAL 72DEGREE CHAS6 F WH RB 90 SWS220 3.0 30 1 90 CRI, 3000K PRIMARY PER PER LINEAR LED TAPE LIGHT SYS TEM WITHIN ALUMINUM HOUSING, MOUNTING CLIPS AND 85% COEFFICIENT TRANSMISSION FROSTED 5 L2 ACOLYTE LED LED 120V 3 3 NOMINAL 1" WIDE X 5/8" HIGH X VARYING LE NGTH SURFACE MOUNTED DRY LOCATION IP20 RATED LOW VOLTAGE LED 1,2,3 TOGETHER VIA STANDARD IP20 STYLE JUMPER/ QUICK CONNECT CABLES. NO SOLDERING OF SECTIONS ALLOWED.
MANUFACTURER ACCORDINGLY PER COVE CONDITION AND 5-CHANNEL DMX DECORDER. SYSTEM TO BE FIELD CUTTABLE AND SECTIONS DMXINFLCD5 BY SECOND 120DEGREE BEAM SPREAD. SYSTEM TO INCLUDE R EMOTE NON-DIMMING 120/ 24V POWER SUPPLYCONNECTED SIZED DRVW24 96 200LM/ FOOT 24V FOOT FOOT FROSTED LENS FOR STRAIGHT COV E RUNS AND SEGMENTED WALL DETAIL. CHANNEL AND LENS SHALL PRODUCE A NOMINAL CHAS3 M WH RB RGBWA20 5.5 RGB30 1 RGB+3000K PRIMARY PER PER CHIP LINEAR LED TAPE LIGHT SYS TEM WITHIN ALUMINUM HOUSING, MOUNTING CLIPS AND 70% COEFFICIENT TRANSMISSION MILK 5 L1 ACOLYTE LED LED 120V 5.5 6 NOMINAL 1" WIDE X 1/2" HIGH X VARYING LENGTH SURFACE MOUNTED DRY LOCATION IP20 RATED LOW VOLTAGE 4-1 RGBW LED 1,2,3
MANUFACTURER
BY
8,000 LUMEN
RS6N 80 279 UNV LTE 60 WHT SCA610 90 CRI, 2700K CEILING CONDITIONS. 6 D2 METEOR - REV6 SERIES LED LED 120 80 89 SAME AS TYPE D1, EXCEPT FIXTURE EQUIPPE D WITHOUT SLOPE CEILING ADAPTER. MOUNTING TYPE SHALL BE FOR DRYWALL 2,3,4, INSULATION KEPT MORE THAN 1-FT AWAY FROM HOUSING.
MANUFACTURER REMOVABLE THROUGH APERTURE. LIGHT FIXTURE TRIM UTILIZES 6.7" DIAMETER CEILING CUT-OUT. IC-HOUSING MUST HAVE BY FIXTURE FURNISHED WITH INTEGRAL 2-WIRE LUTRON HI-LUME DIMMING DRIVER SUITABLE FOR 1% OF FULL OUTPUT WITH DRIVER 8,000 LUMEN FIXTURE EQUIPPED WITH INTEGRAL 60 DEGREE BEAM SPREAD DOWNLIGHT WITH HIGH 90+ CRI SINGLE CHIP LED MODULE.
RS6N 80 279 UNV LTE 60 WHT SCA610 90 CRI, 2700K FOR ACOUSTIC TILE CEILING CONDITIONS, CLEAR ALZAK SEMI-SPECULAR REFLECTOR AND OVERLAPPING WHITE FLANGE. 6 D1 METEOR - REV6 SERIES LED LED 120 80 89 NOMINAL 6" DIAMETER APERTURE X 7.75" T ALL RECESSED FIXED LED DOWNLIGHT FIXTURE WITH NEW CONSTRUCTION HOUSING 2,3,4, NO. TYPE VOLT WATTS VA
TYPE MANUFACTURER/MODEL # LAMPS INPUT INPUT DESCRIPTION NOTES LIGHT FIXTURE SCHEDULE (1 of 1)
NTS1 BALLROOM B - DMX LIGHTING CONTROL SYSTEM DIAGRAM
VERSION: 4.04
J. ALL LIGHTING CONTROL DEVICES SHALL MEET CALIFORNIA ENERGY COMMISSION TITLE 24 REQUIREMENTS.
H. DO NOT SHARE NEUTRAL CONDUCTOR ON LOAD SIDE OF DIMMERS.
G. PROVIDE A NEUTRAL CONDUCTOR TO ALL WALL SWITCH LOCATIONS PER NEC REQUIREMENTS.
F. PROVIDE COPIES OF OPERATION AND MAINTENANCE INSTRUCTIONS FOR ALL DEVICES TO OWNER.
SEQUENCE OF OPERATIONS AND OWNER PRIOR TO SYSTEM COMMISSIONING.
E. ALL WALL SWITCH AND CEILING SENSORS SHALL HAVE AN ADJUSTABLE TIME DELAY RANGE OF 0-30 MIN, UNO. CONFIRM SENSOR SETTINGS WITH D. VERIFY COLOR(S) FOR ALL WALL AND CEILING MOUNTED DEVICES WITH THE ARCHITECT.
C. LIGHTING CONTROLS PRICING SHALL BE COMPLETELY SEPARATE OF ANY LIGHT FIXTURE PRICING.
CEILING MOUNTED DEVICES). ALSO PROVIDE SCHEMATICS AND SCHEDULES WHEN APPLICABLE.
DEVICES SUCH AS SPEAKERS, SECURITY CAMERAS, PROJECTORS, ETC. (SENSORS MAY BE ADVERSELY AFFECTED IF LOCATED TOO CLOSE TO OTHER
INCLUDING BUT NOT LIMITED TO HVAC SUPPLY AND RETURN GRILLES, SPRINKLERS, LIGHT FIXTURES, AND OTHER OWNER-PROVIDED CEILING MOUNTED MUST INCLUDE SENSOR LOCATIONS, HEIGHTS, ORIENTATION, AND COVERAGE AREAS. SHOW COORDINATION WITH ALL OTHER CEILING DEVICES B. PROVIDE SHOP DRAWINGS FOR ENGINEER AND ARCHITECT REVIEW THAT INCLUDE PRODUCT CUTSHEETS AND PROJECT-SPECIFIC LAYOUTS. LAYOUTS COLUMN, ADJUST SENSOR QUANTITIES AND LOCATIONS PER MANUFACTURER-SPECIFIC SPACING CRITERIA.
A. OCCUPANCY SENSOR LAYOUT DESIGNED FROM BASIS-OF-DESIGN COVERAGE PATTERNS. IF SUBMITTING ALTERNATE PER 'EQUIVALENT MANUFACTURER' GENERAL NOTES:
LUT-ELI-3PH OR BYPASS PER EMERGENCY SEQUENCE.
LUT LUTRON LUTRON EMERGENCY TRANSFER DEVICE. UL924 LISTED. OPERATES AS CONTROL DEVICE 24 CGP12-120-4-FT
CGP12 LUTRON LUTRON 12 CIRCUIT FEED-THRU DIMMING PANEL FOR EMERGENCY LIGHT FIXTURE ZONE(S) 120
TAG MODEL/SERIES MANUFACTURER DEVICE DESCRIPTION VOLTAGE NOTES
SYMBOL MANUFACTURER ALTERNATE
AUXILIARY EQUIPMENT
EXT
EXT PHAROS EXTENSION EQUIPMENT FOR TPC TO PROVIDE STANDARD DMX512 OUTPUT CAPABILITY. 120 EXT RJ45 ETHERNET CONNECTION. PROVIDE WITH SRUFACE MOUNT BACK BOX.
PTC SBB ASTRONIMICAL TIMECLOCK SCHEDULING. PROGAMMED THROUGH PHAROS DESIGNER.
TPC WW 1-UNIVERSE (512) DMX CONTROLLER WITH TRIGGER RECALL, TIMECLOCK, AND TPC PHAROS 4.3" TOUCH PANEL CONTROLLER WITH CUSTOMIZABLE CAPACTIVE TOUCH SCREEN. POE 9-48V DRAWNG 4W, 120V MAINS INPUT
RDM 1-PORT THRU, AND 4 PORTS OUT. DIN RAIL MOUNT. REQUIRES REMOTE POWER SUPPLY, RDM PHAROS REMOTE DEVICE MANAGEMENT DEVICE PROVIDING 4 PORT DMX512 SPLITTER. 1-PORT IN, 9-48VDC SCHEDULE CONTROLLERS. DMX TERMINATOR REQUIRED. USE BELDEN 9829, 9824 OR CAT5.
LIGHT FIXTURE REQUIRED TO BE USED IN TANDEM WITH LED DRIVER. DMX THROUGH TO ADDITIONAL REFER TO CONTROL RED, GREEN, BLUE, WHITE AND POWER P ER FIXTURE RUN.
D ACCOLYTE 5-CHANNEL DMX INTERFACE USED TO CONTROL L1 LIGHT FIXTURES PROVIDING CHANNEL 12-24VDC
TAG MODEL/SERIES MANUFACTURER DEVICE DESCRIPTION VOLTAGE NOTES
SYMBOL MANUFACTURER ALTERNATE
NETWORK AUXILIARY LIGHTING EQUIPMENT
LIGHTING CONTROL DEVICE SCHEDULE
DURING NORMAL OPERATION. WHEN NORMAL SENSING POWER IS LOST, LIGHT FIXTURES SHALL BE SIGNALED TO FULL BRIGHTNESS.
QUANTUM NAMING PROTOCOL. LIGHT FIXTURES FED BY EMERGENCY PANEL SHALL MATCH ON/OFF/DIMMED SCENE SETTINGS
1. CONTRACTOR TO CONFIRM ZONE NAME WITH EXISTING SYSTEMS AND COORDINATE AS REQUIRED WITH EXISTING LUTRON
LIGHTING CONTROL PANEL NOTES
CONFIGURATION WITH LIGHTING CONTROL VENDOR AND FIELD CONDITIONS.
INFORMATIONAL PURPOSES ONLY. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING FINAL RELAY NOTE: RELAY NUMBERING ON SCHEDULE IS INTENDED TO COMMUNICATE DESIGN INTENT AND IS FOR 12 SPARE
11 SPARE
10 1ELP-U-8 CENTER CORRIDOR 2-WIRE LUTRON 160 E-10
9 1ELP-U-6 CENTER CORRIDOR 2-WIRE LUTRON 160 E-9
8 1ELP-U-4 BALLROOM B8 2-WIRE LUTRON 80 E-8
7 1ELP-U-4 BALLROOM B7 2-WIRE LUTRON 80 E-7
6 1ELP-U-4 BALLROOM B6 2-WIRE LUTRON 80 E-6
5 1ELP-U-4 BALLROOM B5 2-WIRE LUTRON 80 E-5
4 1ELP-U-2 BALLROOM B4 2-WIRE LUTRON 80 E-4
3 1ELP-U-2 BALLROOM B3 2-WIRE LUTRON 80 E-3
2 1ELP-U-2 BALLROOM B2 2-WIRE LUTRON 80 E-2
1 1ELP-U-2 BALLROOM B1 2-WIRE LUTRON 80 E-1
TYPE (WATTS)
RELAY CIRCUIT LOAD CONTROLLED MODULE LOAD ZONE
LOCATION: CORR E2F37 VOLTAGE: 120
PANEL NAME: ELCP MOUNTING: SURFACE
LIGHTING CONTROL PANEL SCHEDULE
NO. DATE DESCRIPTION
09/08/2021
T D T D T D T D
T D T D T D T D
T
T
T
T
T
T
TPC
EXTRDMCPG12LUT
TPC
EXTRDMCPG12LUT
TPC
EXTRDMLUTQTM
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
ES
17 18
19 25
31 37
43 49
50 EB EC ED EE EF EG EH EJ EK EL EM EN EO EP EQ ER
34 37.5
43.5 D1 D1 D1 D1 D1
D1 D1 D1E D1 D1
D1 D1 D1 D1 D1
D1
D1
D1
D1
D1
D1
D1E
D1
D1
D1
D1
D1 D1 D1 D1 D1 D1
D1 D1 D1E D1 D1
D1 D1 D1 D1 D1
D1
D1
D1
D1
D1
D1
D1
D1E
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D2 D2D2ED2
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D2E D2D2 D2
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D2E D2D2 D2 D2ED2 D2
D1 D1 D1 D1 D1
D1 D1 D1E D1 D1
D1 D1 D1 D1 D1
D1
D1
D1
D1
D1
D1
D1E
D1
D1
D1
D1
D1 D1 D1 D1 D1 D1
D1 D1 D1E D1 D1
D1 D1 D1 D1 D1
D1
D1
D1
D1
D1
D1
D1
D1E
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1
TRACK
(ETR)
TRACK
(ETR)
TRACK
(ETR)
TRACK
(ETR)
TRACK
(ETR)
TRACK
(ETR)
TRACK
(ETR)
TRACK
(ETR)
T1 T1 T1 T1 T1 T1 T1 T1
T1 T1 T1 T1 T1 T1 T1 T1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L2
L2
L2
L3-4
L2
L2
L2
1 (TYP)
2 (TYP)
3 1
1 (TYP)
2 (TYP)
4 (TYP)
4 (TYP)
5 (TYP)
6(TYP)
7 B1
E2F22
B3
E2F23
B5
E2F24
B7
E2F25
B10
E2C19
B6
E2C17
B4
E2C16
B2
E2C15
8 9
10 1
E2-1 TYP
5 E2-1
NOT IN
SCOPE
1 1
ETR ETR ETR ETR ETR ETR ETR ETR
ETR
ETR
ETR
1 1
ETR
ETR
ETR
L3-4
L3-4
L3-4
L3-4
L3-2
11 ETR ETR
1 ETR ETR
1 ETR ETRETR ETR
3 E2-1 TYP
1 1
1 12 12
1212
BALLROOM
B
E2C46
13 L4 L4 L4 L4 L4 L4 L4
6 E2-1
(TYP)
14 L4L4 L4 L4 L4 L4 L4 L4 L4L4L4 L4 L4 L4 L4 L4 L4 L4L4 L4 L4 L4 L4 L4 L4 L4 L4 L4 L4 L4 L4 L4 L4L4L4 L4 L4 L4 L4 L4 L4 L4L4L4 L4 L4 L4 L4 L4 L4 L4L4 L4 L4 L4 L4 L4 L4 L4 CPG12
(TYP)
14 (3)96W (3)96W (3)96W (3)96W
(3)96W (3)96W (3)96W (3)96W
60W
60W
60W
60W
60W
60W
60W60W
60W
L4 L4 L4 L4 L4 L4 L4 L4L4
60W
L4 L4 L4 L4 L4 L4 L4 L4 L4
60W
L4 L4 L4 L4 L4 L4 L4 L4 L4 L4 L4 L4 L4 L4 L4 L4
E2-1
2 60W
60W
60W 60W
7 E2-1
MS
ETR ETR ETR ETR ETR ETR ETR ETR
ETR
ETR
ETR ETR ETR ETR ETR ETRETRETR
ETR
ETR
MS
MS
MS
MS MS
MS
MS
(TYP)
15 60W
60W
60W
60W
60W
60W
60W
FAXTEL
PROJECT NO.
Copyright C
ISSUED BY:
ISSUED DATE:
SHEET TITLE:
DISCIPLINE - CATEGORY - SUB CATEGORY - SHEET
REVISIONS
PROJECT NORTH
®
(913) 742-5000 (913) 742-5001
LENEXA, KS 66214
8345 LENEXA DRIVE, SUITE 300
WWW.HENDERSONENGINEERS.COM
®
®
ARCHITECT OF RECORD
POPULOUS
4800 Main Street Suite 300
Kansas City, MO 64112
816-221-1500
HVAC and LIGHTING ENGINEER
HENDERSON ENGINEERS
8345 Lenexa Drive
Lenexa, KS 66214
913-742-5000
Sacramento Convention Center Ballroom B Upgrades
9/7/2021 10:19:56 AM
CONSTRUCTION
DOCUMENTS
September 8, 2021
LIGHTING PLAN
BALLROOM B
E1-2
17.4465
09/08/2021
2019
RUSSELL J. MURDOCK
1650002727
1400 J St, Sacramento, CA 95814
1/8" = 1'-0"1 LIGHTING PLAN BALLROOM B
ELECTRICAL PLAN NOTES:
1 DESIGNATED EMERGENCY LIGHT FIXTURES/CIRCUITS TO BE
CONNECTED TO EXISTING LUTRON SYSTEM THROUGH NEW
DIMMING PANEL WITH UL924 LISTED LUT-ELI TRANSFER
DEVICE. DEVICE TO ALLOW THESE FIXTURES TO DIM AND
PROVIDE EMERGENCY POWER. WHEN NORMAL SENSING
POWER IS LOST, LIGHT FIXTURES SHALL BE SIGNALED TO
FULL BRIGHTNESS.
2 INSTALL NEW CONSTRUCTION 6" RECESSED LED
DOWNLIGHT CENTERED WITHIN NEW CEILING TILE. UTILIZE
EXISTING CIRCUIT AND RE-CONNECT LIGHT FIXTURE TO
EXISTING LUTRON PANEL. NEW LIGHT FIXTURES SHALL BE
2-WIRE DIMMING SIGNAL TYPE.
3 INSTALL NEW TRACK HEAD ON EXISTING TRACK.
CONTRACTOR TO CONFIRM EXISTING TRACK TYPE FOR
TRACK HEAD CONNECTOR COMPATIBILITY PRIOR TO
PURCHASE. REPLACE 1-FOR-1.
4 INSTALL NEW LED RGBW LIGHT FIXTURE USING SIMILAR
LOCATION OF PREVIOUS NEON FIXTURE INSTALLATION.
INSTALL REMOTE POWER SUPPLY AND DMX DECODER
EQUIPMENT ON FLOOR BASE OF WALL DETAIL. REFER TO
ELEVATIONS AND SECTIONS ON SHEET E2-1 FOR
ADDITIONAL INFORMATION. UTILIZE EXISTING CIRCUIT AND
RE-CONNECT LIGHT FIXTURE TO EXISTING LUTRON PANEL.
5 INSTALL NEW LED LIGHT FIXTURE USING SIMILAR LOCAT ION OF PREVIOUS NEON FIXTURE INSTALLATION. LIGHT
FIXTURES SHALL BE CENTERED WITHIN COVE, RUN
CONTINUOUSLY FROM WALL-TO-WALL, AND BE NOT MORE
THAN 1" FROM WALL. INSTALL REMOTE POWER SUPPLY ON
FLOOR BASE OR WALL DETAIL. REFER TO ELEVATIONS AND
SECTIONS ON SHEET E2-1 FOR ADDITIONAL INFORMATION.
UTILIZE EXISTING CIRCUIT AND RE-CONNECT LIGHT FIXTURE
TO EXISTING LUTRON PANEL.
6 INSTALL NEW LED LIGHT FIXTURE MOUNTED TO INTERIOR
COVE VALANCE AND AIMED UPWARD TO GRAZE CURVED
WALL. REFER TO ELEVATIONS AND SECTIONS ON SHEET
E2-1 FOR ADDITIONAL INFORMATION. UTILIZE EXISTING
CIRCUIT AND RE-CONNECT LIGHT FIXTURE TO EXISTING
PREFUNCTION AREA PANEL.
7 INSTALL LED LIGHT FIXTURE WITHIN WALL COVE ABOVE
DOORS AND MOUNTED SUCH THAT TOP OF FIXTURE IS
ALIGNED WITH TOP OF VALANCE. ELECTRICAL
CONTRACTOR TO PROVIDE L-BRACKET FOR MOUNTING.
LIGHT FIXTURES SHALL BE CENTERED WITHIN COVE, RUN
CONTINUOUSLY FROM WALL-TO-WALL, AND BE NOT MORE
THAN 1" FROM WALL. REFER TO ELEVATIONS AND
SECTIONS ON SHEET E2-1 FOR ADDITIONAL INFORMATION.
INSTALL REMOTE POWER SUPPLY WITHIN SERVICE
CORRIDOR, COORDINATE LOCATIONS WITH EXISTING
CEILING ACCESS PANELS. UTILIZE EXISTING CIRCUIT AND
RE-CONNECT LIGHT FIXTURE TO EXISTING LUTRON PANEL.
8 INSTALL TOUCH SCREEN PANEL CONTROLLER FOR NEW
DMX LIGHT FIXTURE CONTROL WITHIN EXISTING BALLROOM.
COORDINATE FINAL LOCATION WITH OWNER AND EXISTING
SERVICE CORRIDOR EQUIPMENT.
9 INSTALL DIN RAIL MOUNT DMX ON WALL WITHIN SERVICE
CORRIDOR. COORDINATION LOCATION WITH EXISTING
EQUIPMENT AND MANUFACTURER REQUIRED CLEARANCES.
10 INSTALL NEW LUTRON 12-CIRCUIT FEED THRU DIMMING
PANEL AND EMERGENCY INTERFACE EQUIPMENT WITHIN
SERVICE CORRIDOR NEXT TO EXISTING 1ELP-U ON EXISTING
UNISTRUT (REFER TO DETAIL 3 ON THIS SHEET).
COORDINATE LOCATION WITH EXISTING EQUIPMENT AND
MANUFACTURER CLEARANCES. ELECTRICAL CONTRACTOR
TO VERIFY 3PHASE 4WIRE CONDITION OF EXISTING 1ELP-U
PANEL TO ENSURE NEW DIMMING PANEL SPECIFICATION.
LOCATE LUTRON EMERGENCY INTERFACE EQUIPMENT
ABOVE NEW 12-CIRCUIT DIMMING PANEL AS PER TYPICAL
MANUFACTURER DETAIL.
11 EXISTING NEON LIGHT FIXTURE TO REMAIN UNLESS
FURTHER REQUESTED BY OWNER.
12 EXTEND LIGHTING CIRCUIT WIRING FROM PREVIOUS LIGH T
FIXTURE LOCATION TO NEW INSTALLATION.
13 RELOCATE QUANTUM PROCESSOR AS REQUIRED TO
NEAR-BY CLEAR WALL SPACE WITHIN SERVICE CORRIDOR
PROVIDE UNISTRUT AS REQUIRED FOR MOUNTING (REFER
TO DETAIL 3 ON THIS SHEET). RE-WIRE CONNECTIONS TO
EXISTING LIGHTING PANEL 1D-U AND 2D-U AS REQUIRED.
CONNECT NEW DIMMING PANEL TO QUANTUM SYSTEM.
UPGRADE SOFTWARE AS REQUIRED. SYSTEM SHALL BE
COMMISSIONED BY LUTRON FIELD AGENT TO MAINTAIN
ZONE SETTING INTENT AS PER EXISTING CONDITIONS
UNLESS OTHERWISE DIRECTED BY OWNER.
14 INSTALL NEW LED LIGHT FIXTURE IN SAME LOCATION AS
THE PREVIOUS LIGHT FIXTURES BEHIND THE ACRYLIC
PANEL CEILING DETAIL. LIGHT FIXTURES SHALL BE
CENTERED WITHIN COVE, RUN CONTINUOUSLY FROM
WALL-TO-WALL, AND BE NOT MORE THAN 1" FROM WALL.
INSTALL REMOTE POWER SECURED TO STRUCTURE ABOVE
ACCESSIBLE CEILING TILES. UTILIZE EXISTING CIRCUIT AND RE-CONNECT TO EXISTING LUTRON PANEL.
15 EXISTING LIGHTING CONTROL SYSTEM WALL STATION TO
REMAIN. LOCATIONS SHOWN ARE DIAGRAMMATIC. VERIFY
QUANTITY WITH ONSITE CONDITIONS.
LIGHTING GENERAL NOTES
1 REFER TO SHEET E0-0 FOR ADDITIONAL
GENERAL NOTES.
2 REFER TO SHEETS E1-1 FOR LIGHT FIXTURE
SCHEDULE.
3 REFER TO SHEET E1-1 FOR LIGHTING
CONTROL DEVICE SCHEDULE AND LIGHTING
CONTROL ONE-LINE AND CONTROL SEQUENCE OF
OPERATIONS FOR PERFORMANCE INTENT.
NO. DATE DESCRIPTION
09/08/2021
L2
REMOVE NEON LIGHT
FIXTURE AND INSTALL NEW
LED LIGHT FIXTURE. LOCATE
REMOTE POWER SUPPLY
WITHIN SERVICE CORRIDOR
UTILIZING EXISTING ACCESS
PANEL.
INSTALL LED LIGHT FIXTURE
SECURED TO SIDE OF
EXISTING COVE. MOUNT LED
STRIP FIXURE ON TOP OF L-
BRACKET TO THAT TOP OF
FIXTURE LENS IS FLUSH
WITH TOP OF COVE LIP.
ELECTRICAL CONTRACTOR
SHALL PROVIDE L-BRACKET.
EXISTING EXIT SIGN TO REMAIN
RELOCATE LUTRON QUANTUM EQUIPMENT TO
NEW WALL LOCATION.
PROVIDE UNISTRUT FOR MOUNTING AS
REQUIRED. RE-WORK WIRING AS NEEDED TO
MAINTAIN CONNECTION TO EXISTING LIGHTING
PANELS.
INSTALL NEW 12-CIRCUIT FEED-THRU
DIMMING PANEL AND EMERGENCY
TRANSFER DEVICE (LUT-ELI) IN THIS
LOCATION . CONNECT NEW
EQUIPMENT TO QUANTUM PANEL.
L3
INSTALL LED LIGHT
FIXTURE MOUNTED TO
SIDE OF VALNCE AND
PLACED SUCH THAT TOP
OF FIXTURE IS ALIGNED
WITH TOP OF VALANCE.
REMOVE FLUORESCENT
STRIP LIGHT
L2
REMOVE NEON LIGHT
FIXTURE AND INSTALL NEW
LED LIGHT FIXTURE.
LOCATE REMOTE POWER
SUPPLY WITHIN COVE.
PREFUNCTION AREA BALLROOM
L1
L1
REMOVE NEON LIGHT
FIXTURE AND INSTALL NEW
LED LIGHT FIXTURE. LOCATE
REMOTE POWER SUPPLY
AND DMX INTERFACE
EQUIPMENT WITHIN COVE.
L1
L1 (TYP)
FOLLOW CURVE OF WALL
DETAIL BY USING 2-FT
SEGMENT LED FIXTURE
LENGTHS
REMOVE NEON LIGHT FIXTURE
AND INSTALL NEW LED LIGHT
FIXTURE. LOCATE REMOTE
POWER SUPPLY AND DMX
INTERFACE EQUIPMENT
WITHIN COVE.
ROUTE NEW LOW-VOLTAGE
AND DMX WIRING THROUGH
WALL TO REMOTE EQUIPMENT
LOCATED IN BASE OF WALL
DETAIL.
4 E2-1
EXITEXIT
(ETR) (ETR)
L4
REMOVE FLUORESCENT LIGHT
FIXTURE AND INSTALL NEW LED LIGHT
FIXTURE. PROVIDE BLOCK TO ALIGN
TOP OF LIGHT FIXTURE WITH BOTTOM
OF ACRYLIC PANEL. SECURE REMOTE
POWER SUPPLY TO STRUCTURE
ABOVE ACCESSIBLE TILE CEILING.
ALIGN
L4
REMOVE FLUORESCENT LIGHT
FIXTURES AND INSTALL NEW LED LIGHT
FIXTURE. MOUNT LED LIGHT FIXTURE
TO SIDE OF CEILING SOFFIT BEHIND
TRANSLUCENT PANELS. OREINT LIGHT
FIXTURE TO AIM OUT, INTO, BALLROOM
AS SHOWN. SECURE REMOTE POWER
SUPPLY TO STRUCTURE ABOVE
ACCESSIBLE TILE CEILING.
FAXTEL
PROJECT NO.
Copyright C
ISSUED BY:
ISSUED DATE:
SHEET TITLE:
DISCIPLINE - CATEGORY - SUB CATEGORY - SHEET
REVISIONS
PROJECT NORTH
®
(913) 742-5000 (913) 742-5001
LENEXA, KS 66214
8345 LENEXA DRIVE, SUITE 300
WWW.HENDERSONENGINEERS.COM
®
®
ARCHITECT OF RECORD
POPULOUS
4800 Main Street Suite 300
Kansas City, MO 64112
816-221-1500
HVAC and LIGHTING ENGINEER
HENDERSON ENGINEERS
8345 Lenexa Drive
Lenexa, KS 66214
913-742-5000
Sacramento Convention Center Ballroom B Upgrades
9/7/2021 10:20:02 AM
CONSTRUCTION
DOCUMENTS
September 8, 2021
LIGHTING DETAILS
E2-1
17.4465
09/08/2021
2019
RUSSELL J. MURDOCK
1650002727
1400 J St, Sacramento, CA 95814
NTS1 BALLROOM B - EXISTING SECTION @ WEST ENTRY/EXT DOORS NTS2 LIGHTING CONTROL SYSTEMS - EXISTING LUTRON QUANTUM RELOCATION NTS5 BALLROOM B - EXISTING SECTION @ VESTIBULE 337 CEILING LIGHT COVE NTS4 BALLROOM B - EXISTING WALL SECTION @ BALLROOM DOORS NTS3 BALLROOM B - EXISTING PARTIAL WALL ELEVATION @ BALLROOM DOORS NTS6 BALLROOM B - EXISTING DETAIL @ CEILING LIGHT ALCOVE NTS7 BALLROOM B - EXISTING DETAIL @ CEILING CUSTOM LIGHT FIXTURE NO. DATE DESCRIPTION
09/08/2021
SAFE CREDIT UNION CONVENTION CENTER
BALLROOM B HVAC & LIGHTING SYSTEMS
CONSTRUCTION DOCUMENTS
PROJECT MANUAL
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 ARCHITECTURAL CERTIFICATION
00 01
05.1 - 1
ARCHITECTURAL CERTIFICATION
1.1 CERTIFICATION
A. I hereby certify that these Specifications have been prepared by me, or under my supervision. I further certify that to the best of my knowledge these Specifications are as required by and in compliance with Building Codes of the State of California.
B. I hereby specify that the documents intended to be authenticated by my seal are limited to:
00 01 05 ARCHITECTURAL CERTIFICATION
00 01
10 TABLE OF CONTENTS
01 10 00 SUMMARY
01 25 00 SUBSTITUTION PROCEDURES
01 26 00 CONTRACT MODIFICATION PROCEDURES
01 29 00 PAYMENT PROCEDURES
01 31 00 PROJECT MANAGEMENT AND COORDINATION
01 32 00 CONSTRUCTION PROGRESS DOCUMENTATION
01 32 33 PHOTOGRAPHIC DOCUMENTATION
01 33 00 SUBMITTAL PROCEDURES
01 35 16 ALTERATION PROJECT PROCEDURES
01 40 00 QUALITY REQUIREMENTS
01 42 00 REFERENCES
01 50 00 TEMPORARY FACILITIES AND CONTROLS
01 60 00 PRODUCT REQUIREMENTS
01 73 00 EXECUTION
01 74 19 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
01 77 00 CLOSEOUT PROCEDURES
01 78 23 OPERATION AND MAINTENANCE DATA
01 78 39 PROJECT RECORD DOCUMENTS
02 41 19 SELECTIVE DEMOLITION
06 10 53 MISCELLANEOUS ROUGH CARPENTRY
07 92 00 JOINT SEALANTS
09 22 16 NON-STRUCTURAL METAL FRAMING
09 29 00 GYPSUM BOARD
09 51 13 ACOUSTICAL PANEL CEILINGS
09 91 23 INTERIOR PAINTING
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 ARCHITECTURAL CERTIFICATION
00 01
05.1 - 2
1.2 PROFESSIONAL SEAL
A. Signature: Date: 9/8/21
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© POPULOUS 2021 MECHANICAL CERTIFICATION
00 01
05.5 - 1
MECHANICAL CERTIFICATION
1.1 CERTIFICATION
A. I hereby certify that these Specifications have been prepared by me, or under my supervision. I further certify that to the best of my knowledge these Specifications are as required by and in compliance with Building Codes of the State of California.
B. I hereby specify that the documents intended to be authenticated by my seal are limited to:
230010 GENERAL MECHANICAL REQUIREMENTS
2300
15 ELECTRICAL COORDINATION FOR MECHANICAL EQUIPMENT
230500 COMMON WORK RESULTS FOR HVAC
230510 BASIC PIPING MATERIALS AND METHODS
230523 GENERAL-DUTY VALVES FOR HVAC PIPING
230529 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230548 SEISMIC CONTROLS FOR MECHANICAL SYSTEMS
230553 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT
230593 TESTING, ADJUSTING, AND BALANCING FOR HVAC
230700 HVAC INSULATION
230913 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC
230923 DIRECT-DIGITAL CONTROL FOR HVAC
232113 HYDRONIC PIPING
232114 HYDRONIC SPECIALTIES
233113 METAL DUCTS
233300 AIR DUCT ACCESSORIES
233600 AIR TERMINAL UNITS
1.2 P
ROFESSIONAL SEAL
A. Signature: __________________________ Date: _____________ 09/08/2021
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© POPULOUS 2021 MECHANICAL CERTIFICATION
00 01
05.5 - 2
THIS IS INTENTIONALLY LEFT BLANK
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© POPULOUS 2021 ELECTRICAL CERTIFICATION
00 01
06.5 - 1
ELECTRICAL CERTIFICATION
1.1 CERTIFICATION
A. I hereby certify that these Specifications have been prepared by me, or under my supervision. I further certify that to the best of my knowledge these Specifications are as required by and in compliance with Building Codes of the State of California.
B. I hereby specify that the documents intended to be authenticated by my seal are limited to:
260010 GENERAL ELECTRICAL REQUIREMENTS
2605
00 COMMON WORK RESULTS FOR ELECTRICAL
260519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260526 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
260529 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
260533 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
260548 SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS
260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS
265100 INTERIOR LIGHTING
1.2 P
ROFESSIONAL SEAL
A. Signature: __________________________ Date: _____________ 09/08/2021
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© POPULOUS 2021 ELECTRICAL CERTIFICATION
00 01
06.5 - 2
THIS IS INTENTIONALLY LEFT BLANK
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© POPULOUS 2021 SEISMIC CERTIFICATION
00 01
05.7- 1
SEISMIC CERTIFICATION
1.1 CERTIFICATION
A. I hereby certify that these Specifications have been prepared by me, or under my supervision. I further certify that to the best of my knowledge these Specifications are as required by and in compliance with Building Codes of the State of California.
B. I hereby specify that the documents intended to be authenticated by my seal are limited to:
200548 SEISMIC CONTROLS FOR MEP/F/T SYSTEMS
1.2 P
ROFESSIONAL SEAL
A. Signature: __________________________ Date: _____________ 09/08/2021
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© POPULOUS 2021 SEISMIC CERTIFICATION
00 01 0
5.7- 2
THIS IS INTENTIONALLY LEFT BLANK
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 TABLE OF CONTENTS
00 01 10 - 1
DOCUMENT 00 01 10 – TABLE OF CONTENTS
PROCUREMENT AND CONTRACTING DOCUMENTS GROUP
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
00 01 05 ARCHITECTURAL CERTIFICATION
00 01 05 MECHANICAL CERTIFICATION
00 01 05 ELECTRICAL CERTIFICATION
00 01 05 SEISMIC CERTIFICATION
00 01 10 TABLE OF CONTENTS
SPECIFICATIONS GROUP
General Requirements Subgroup
DIVISION 01 - GENERAL REQUIREMENTS
01 10 00 SUMMARY
01 25 00 SUBSTITUTION PROCEDURES
01 26 00 CONTRACT MODIFICATION PROCEDURES
01 29 00 PAYMENT PROCEDURES
01 31 00 PROJECT MANAGEMENT AND COORDINATION
01 32 00 CONSTRUCTION PROGRESS DOCUMENTATION
01 32 33 PHOTOGRAPHIC DOCUMENTATION
01 33 00 SUBMITTAL PROCEDURES
01 35 16 ALTERATION PROJECT PROCEDURES
01 40 00 QUALITY REQUIREMENTS
01 42 00 REFERENCES
01 50 00 TEMPORARY FACILITIES AND CONTROLS
01 60 00 PRODUCT REQUIREMENTS
01 73 00 EXECUTION
01 74 19 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
01 77 00 CLOSEOUT PROCEDURES
01 78 23 OPERATION AND MAINTENANCE DATA
01 78 39 PROJECT RECORD DOCUMENTS
Facility Construction Subgroup
DIVISION 02 - EXISTING CONDITIONS
02 41 19 SELECTIVE DEMOLITION
DIVISION 03 - CONCRETE
NO SECTIONS
DIVISION 04 - MASONRY
NO SECTIONS
DIVISION 05 - METALS
NO SECTIONS
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 TABLE OF CONTENTS
00 01 10 - 2
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 53 MISCELLANEOUS ROUGH CARPENTRY
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 92 00 JOINT SEALANTS
DIVISION 08 - OPENINGS
NO SECTIONS
DIVISION 09 - FINISHES
09 22 16 NON-STRUCTURAL METAL FRAMING
09 29 00 GYPSUM BOARD
09 51 13 ACOUSTICAL PANEL CEILINGS
09 91 23 INTERIOR PAINTING
DIVISION 10 - SPECIALTIES
NO SECTIONS
DIVISION 11 - EQUIPMENT
NO SECTIONS
DIVISION 12 - FURNISHINGS
NO SECTIONS
DIVISION 13 - SPECIAL CONSTRUCTION
NO SECTIONS
DIVISION 14 - CONVEYING EQUIPMENT
NO SECTIONS
DIVISION 15 - RESERVED
NO SECTIONS
DIVISION 16 - RESERVED
NO SECTIONS
DIVISION 17 - RESERVED
NO SECTIONS
DIVISION 18 - RESERVED
NO SECTIONS
DIVISION 19 - RESERVED
NO SECTIONS
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 TABLE OF CONTENTS
00 01 10 - 3
Facility Services Subgroup
DIVISION 20 - RESERVED
200548 SEISMIC CONTROLS FOR MEP/F/T SYSTEMS
DIVISION 21 - FIRE SUPPRESSION
NO SECTIONS
DIVISION 22 - PLUMBING
NO SECTIONS
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) 230010 GENERAL MECHANICAL REQUIREMENTS
230015 ELECTRICAL COORDINATION FOR MECHANICAL EQUIPMENT 230500 COMMON WORK RESULTS FOR HVAC
230510 BASIC PIPING MATERIALS AND METHODS
230523 GENERAL-DUTY VALVES FOR HVAC PIPING
230529 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230548 SEISMIC CONTROLS FOR MECHANICAL SYSTEMS
230553 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT
230593 TESTING, ADJUSTING, AND BALANCING FOR HVAC
230700 HVAC INSULATION
230913 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC
230923 DIRECT-DIGITAL CONTROL FOR HVAC
232113 HYDRONIC PIPING
232114 HYDRONIC SPECIALTIES
232500 HVAC WATER TREATMENT
233113 METAL DUCTS
233300 AIR DUCT ACCESSORIES
233600 AIR TERMINAL UNITS
DIVISION 24 - RESERVED
NO SECTIONS
DIVISION 25 - INTEGRATED AUTOMATION
NO SECTIONS
DIVISION 26 - ELECTRICAL
260010 GENERAL ELECTRICAL REQUIREMENTS
260500 COMMON WORK RESULTS FOR ELECTRICAL
260519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260526 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
260529 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
260533 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS
260548 SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS
260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS
265100 INTERIOR LIGHTING
DIVISION 27 - COMMUNICATIONS
NO SECTIONS
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 TABLE OF CONTENTS
00 01 10 - 4
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
NO SECTIONS
DIVISION 29 - RESERVED
NO SECTIONS
Site and Infrastructure Subgroup
DIVISION 30 - RESERVED
NO SECTIONS
DIVISION 31 - EARTHWORK
NO SECTIONS
DIVISION 32 - EXTERIOR IMPROVEMENTS
NO SECTIONS
DIVISION 33 - UTILITIES
NO SECTIONS
DIVISION 34 - TRANSPORTATION
NO SECTIONS
DIVISION 35 - WATERWAY AND MARINE CONSTRUCTION
NO SECTIONS
DIVISION 36 - RESERVED
NO SECTIONS
DIVISION 37 - RESERVED
NO SECTIONS
DIVISION 38 - RESERVED
NO SECTIONS
DIVISION 39 - RESERVED
NO SECTIONS
Process Equipment Subgroup
DIVISION 40 - PROCESS INTERCONNECTIONS
NO SECTIONS
DIVISION 41 - MATERIAL PROCESSING AND HANDLING EQUIPMENT
NO SECTIONS
DIVISION 42 - PROCESS HEATING, COOLING, AND DRYING EQUIPMENT
NO SECTIONS
DIVISION 43 - PROCESS GAS AND LIQUID HANDLING, PURIFICATION AND STORAGE EQUIPMENT
NO SECTIONS
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 TABLE OF CONTENTS
00 01 10 - 5
DIVISION 44 - POLLUTION AND WASTE CONTROL EQUIPMENT
NO SECTIONS
DIVISION 45 - INDUSTRY-SPECIFIC MANUFACTURING EQUIPMENT
NO SECTIONS
DIVISION 46 - WATER AND WASTEWATER EQUIPMENT
NO SECTIONS
DIVISION 47 - RESERVED
NO SECTIONS
DIVISION 48 - ELECTRICAL POWER GENERATION
NO SECTIONS
DIVISION 49 - RESERVED
NO SECTIONS
END OF TABLE OF CONTENTS
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 SUMMARY
01 10 00 - 1
SECTION 011000 - SUMMARY
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Project information.
2. Work covered by Contract Documents.
3. Access to site.
4. Coordination with occupants.
5. Work restrictions.
6. Specification and Drawing conventions.
7. Miscellaneous provisions.
B. Related Requirements:
1. Section 015000 "Temporary Facilities and Controls" for limitati ons and procedures governing temporary use of Owner's facilities.
1.3 PROJECT INFORMATION
A. Project Identification: SAFE Credit Union Convention Center Ballroom B HVAC & Lighting Systems.
1. Project Location: 1400 J Street, Sacramento, CA 95814.
B. Owner: City of Sacramento, 915 I St. Sacramento, CA 95814.
1. Owner's Representative: Mr. Mack Smith; [email protected]; 916-808-5445 (work); 916-960-9214 (mobile).
C. Architect: Populous Architects; Ms. Danielle May; [email protected]; 816- 329-4532.
D. Architect's Consultants: Architect has retained the following design professionals who have prepared designated portions of the Contract Documents:
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 SUMMARY
01 10 00 - 2
1. MEP Engineer: Henderson Enginee rs; Mr. Don Clark ;
[email protected]; 913 -742-5526 (work); 816 -804-4313 (mobile).
E. Web-Based Project Software: Project software administered by Contractor will be used for purposes of managing communication and documents during the construction stage.
1. See Section 013100 "Project Management and Coordination." for requirements for using web-based Project software.
1.4 WORK COVERED BY CONTRACT DOCUMENTS
A. The Work of Project is defined by the Contract D ocuments and generally consists of the following:
1. Replacement of existing suspended acoustical panel system.
2. Existing lighting replacement.
3. Existing terminal air unit relocation.
4. Other Work indicated in the Contract Documents.
B. Type of Contract:
1. Project will be constructed under a single prime contract.
1.5 ACCESS TO SITE
A. General: Contractor shall have limited use of Project site for construction operations as indicated on Dr awings by the Contract limits and as indicated by requirements of this Section.
B. Use of Site: Limit use of Project site to Work in areas indicated. Do not disturb portions of Project site beyond areas in which the Work is indicated.
1. Limits: Confine construction operations to Ballroom B.
2. Driveways, W alkways and Entrances: Keep driveways loading areas, and entrances serving premises clear and available to Owner, Owner's employees, and emergency vehicles at all times. Do not use these areas for parking or for storage of materials.
a. Schedule deliveries to minimize use of driveways and entrances by construction operations.
b. Schedule deliveries to minimize space and time requirements for storage of materials and equipment on-site.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 SUMMARY
01 10 00 - 3
C. Condition of Existing Building: Maintain portions of exi sting building affected by construction operations in a weathertight condition throughout construction period.
Repair damage caused by construction operations.
D. Condition of Existing Grounds: Maintain portions of existing grounds, landscaping, and hardscaping affected by construction operations throughout construction period. Repair damage caused by construction operations.
1.6 COORDINATION WITH OCCUPANTS
A. Partial Owner Occupancy: Owner will occupy the premises during entire construction period, with the exception of areas under c onstruction. Cooperate with Owner during construction operations to minimize conflicts and facilitate Owner usage. Perform the Work so as not to interfere with Owner's operations. Maintain existing exits unless otherwise indicated.
1. Maintain access to exist ing walkways, corridors, and other adjacent occupied or used facilities. Do not close or obstruct walkways, corridors, or other occupied or used facilities without written permission from Owner and authorities having jurisdiction.
2. Provide not less than 72 hours' notice to Owner of activities that will affect Owner's operations.
B. Owner Limited Occupancy of Completed Areas of Construction: Owner reserves the right to occupy and to place and install equipment in completed portions of the Work, prior to Substantial Completion of the Work, provided such occupancy does not interfere with completion of the Work. Such placement of equipment and limited occupancy shall not constitute acceptance of the total Work.
1. Architect will prepare a Certificate of Substantial Completion for each specific portion of the Work to be occupied prior to Owner acceptance of the completed Work.
2. Obtain a Certificate of Occupancy from authorities having jurisdiction before limited Owner occupancy.
3. Before limited Owner occupancy, mechanical and electrical systems shall be fully operational, and required tests and inspections shall be successfully completed.
On occupancy, O wner will operate and maintain mechanical and electrical systems serving occupied portions of Work.
4. On occupancy, Owner will assume responsibility for maintenance and custodial service for occupied portions of Work.
1.7 WORK RESTRICTIONS
A. Work Restrictions, General: Comply with restrictions on construction operations.
1. Comply with limitations on use of public streets and with other requirements of authorities having jurisdiction.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 SUMMARY
01 10 00 - 4
B. On-Site Work Hours: Limit work in the existing building to normal business working hours of 8:00 a.m. to 5:00 p.m., Monday through Friday, unless otherwise indicated.
C. Existing Utility Interruptions: Do not interrupt utilities serving facilities occupied by Owner or others unless permitted under the following conditions and then only after providing temporary utility services according to requirements indicated:
1. Notify Owner not less than seven days in advance of proposed utility interruptions.
2. Obtain Owner's written permission before proceeding with utility interruptions.
D. Noise, Vibration, and Odors: Coordinate operations that may result in high levels of noise and vibration, odors, or other disruption to Owner occupancy with Owner.
1. Notify Owner not less than two days in advance of proposed disruptive operations.
2. Obtain Owner's written permission before proceeding with disruptive operations.
E. Restricted Substances: Use of tobacco products and other controlled substances on Project site is not permitted.
F. Employee Identification: Owner will provide identification tags for Contractor personnel working on Project site. Require personnel to use identification tags at all times.
G. Employee Screening: Comply with Owner's requirements for background screening of Contractor personnel working on Project site.
1. Maintain list of approved screened personnel with Owner's representative.
1.8 SPECIFICATION AND DRAWING CONVENTIONS
A. Specification Content: The Specifications use certain conventions for the style of language and the intended meaning of certain terms, words, and phrases when used in particular situations. These conventions are as follows:
1. Imperative mood and streamlined language are generally used in the Specifications. The words "shall," "shall be," or "shall comply with," depending on the context, are implied where a colon (:) is used within a sentence or phrase.
2. Specification requirements are to be performed by Contrac tor unless specifically stated otherwise.
B. Division 01 General Requirements: Requirements of Sections in Division 01 apply to the Work of all Sections in the Specifications.
C. Drawing Coordination: Requirements for materials and products identified on Drawings are described in detail in the Specifications. One or more of the following are used on Drawings to identify materials and products:
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 SUMMARY
01 10 00 - 5
1. Terminology: Materials and products are identified by the typical generic terms used in the individual Specifications Sections.
2. Abbreviations: Materials and products are identified by abbreviations published as part of the U.S. National CAD Standard and scheduled on Drawings.
3. Keynoting: Materials and products are identified by reference keynotes referencing Specification Section numbers found in this Project Manual.
PART 2 - PRODUCTS (Not Used)
PART 3 - EXECUTION (Not Used)
END OF SECTION 011000
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 SUBSTITUTION PROCEDURES
01 25 00 - 1
SECTION 01 25 00 - SUBSTITUTION PROCEDURES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, inc luding General and Supplementary Conditions and other Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes administrative and procedural requirements for substitutions and Value Engineering.
B. Related Requirements:
1. Section 01 60 00 "Product Requirements" for requirements for submitting comparable product submittals for products by listed manufacturers.
1.3 DEFINITIONS
A. Substitutions: Changes in products, materials, equipment, and methods of construction from those required by the Contract Documents and proposed by Contractor.
1. Substitutions for Cause: Changes proposed by Contractor that are requ ired due to changed Project conditions, such as unavailability of product, regulatory changes, or unavailability of required warranty terms.
2. Substitutions for Convenience: Changes proposed by Contractor or Owner that are not required in order to meet other Project requirements but may offer advantage to Contractor or Owner.
1.4 ACTION SUBMITTALS
A. Substitution Requests: Submit three copies of each request for consideration. Identify product or fabrication or installation method to be replaced. Include Specification Section number and title and Drawing numbers and titles.
1. Substitution Request Form: Use facsimile of form provided in Project Manual.
2. Documentation: Show compliance with requirements for substitutions and the following, as applicable:
a. Statement indicating why specified product or fabrication or installation method cannot be provided, if applicable.
b. Coordination of information, including a list of changes or revisions needed to other parts of the Work and to constru ction performed by Owner and
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 SUBSTITUTION PROCEDURES
01 25 00 - 2
separate contractors that will be necessary to accommodate proposed substitution.
c. Detailed comparison of significant qualities of proposed substitutions with those of the Work specified. Include annotated copy of applicable Specification Section. Significant qualities may include attributes, such as performance, weight, size, durability, visual effect, sustainable design characteristics, warranties, and specific features and requirements indicated. Indicate deviations, if any, from the Work specified. d. Product Data, including drawings and descriptions of products and fabrication and installation procedures.
e. Samples, where applicable or requested.
f. Certificates and qualification data, where applicable or requested. g. List of similar i nstallations for completed projects, with project names and addresses as well as names and addresses of architects and owners. h. Material test reports from a qualified testing agency, indicating and interpreting test results for compliance with requirements indicated. i. Research reports evidencing compliance with building code in effect for Project, from ICC-ES.
j. Detailed comparison of Contractor's construction schedule using proposed substitutions with products specified for the Work, including effect on the overall Contract Time. If specified product or method of construction cannot be provided within the Contract Time, include letter from manufacturer, on manufacturer's letterhead, stating date of receipt of purchase order, lack of availability, or delays in delivery.
k. Cost information, including a proposal of change, if any, in the Contract Sum.
l. Contractor's certification that proposed substitution complies with requirements in the Contract Documents, except as indicated in substitution request, is compatible with related materials and is appropriate for applications indicated.
m. Contractor's waiver of rights to additional payment or time that may subsequently become necessary because of failure of proposed substitution to produce indicated results.
3. Architect's Action: If necessary, Architect will request additional information or documentation for evaluation within seven days of receipt of a request for substitution. Architect will notify Contractor through Construction Manager of acceptance or rejec tion of proposed substitution within 15 days of receipt of request, or seven days of receipt of additional information or documentation, whichever is later.
a. Forms of Acceptan ce: Change Order, Construction Change Directive, or Architect's Supplemental Instructions for minor changes in the Work. b. Use product specified if Architect does not issue a decision on use of a proposed substitution within time allocated.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 SUBSTITUTION PROCEDURES
01 25 00 - 3
1.5 QUALITY ASSURANCE
A. Compatibility of Substitutions: Investigate and document compatibility of proposed substitution with related products and materials. Engage a qualified testing agency to perform compatibility tests recommended by manufacturers.
1.6 PROCEDURES
A. Coordination: Re vise or adjust affected work as necessary to integrate work of the approved substitutions.
1.7 SUBSTITUTIONS
A. Substitutions for Cause: Submit requests for substitution immediately on discovery of need for change, but not later than 15 days prior to time req uired for preparation and review of related submittals.
1. Conditions: Architect will consider Contractor's request for substitution when the following conditions are satisfied. If the following conditions are not satisfied, Architect will return requests without action, except to record noncompliance with these requirements:
a. Requested substitution is consistent with the C ontract Documents and will produce indicated results.
b. Substitution request is fully documented and properly submitted. c. Requested substitution will not adversely affect Contractor's construction schedule.
d. Requested substitution has received necessary approv als of authorities having jurisdiction.
e. Requested substitution is compatible with other portions of the Work. f. Requested substitution has been coordinated with other portions of the Work.
g. Requested substitution provides specified warranty.
h. If requested subs titution involves more than one contractor, requested substitution has been coordinated with other portions of the Work, is uniform and consistent, is compatible with other products, and is acceptable to all contractors involved.
B. Substitutions for Convenience: Not allowed unless otherwise indicated.
C. Substitutions for Convenience: Architect will consider requests for substitution if received within 30 days after the Notice to Proceed. Requests received after that time may be considered or rejected at discretion of Architect.
1. Conditions: Architect will consider Contractor's request for substitution when the following conditions are satisfied. If the following conditions are not satisfied, Architect will return requests without action, except to record n oncompliance with these requirements:
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 SUBSTITUTION PROCEDURES
01 25 00 - 4
a. Requested substitution offers Owner a substantial advantage in cost, time, energy conservation, or other considerations, after deducting additional responsibilities Owner must assume. Owner's additional responsibilities may include compensation to Architect for redesign and evaluation services, increased cost of other construction b y Owner, and similar considerations.
b. Requested substitution does not require extensive revisions to the Contract Documents.
c. Requested substitution is consistent with the Contract Documents and will produce indicated results.
d. Substitution request is fully documented and properly submitted. e. Requested substitution will not adversely affect Contractor's construction schedule.
f. Requested substitution has received necessary approvals of authorities having jurisdiction.
g. Requested substitution is compatible with other portions of the Work. h. Requested substitution has been coordinated with other portions of the Work.
i. Requested substitution provides specified warranty.
j. If requested substitution involves more than one contractor, requested substitution has been co ordinated with other portions of the Work, is uniform and consistent, is compatible with other products, and is acceptable to all contractors involved.
1.8 VALUE ENGINEERING
A. The Owner encourages voluntary development, preparation, and submittal of Value Engineering proposals (VEP's). Proposals may be submitted to the Owner for modifying the plans, specifications, or other requirements of the contract for the purpose of reducing the total cost of construction without impairing in any manner the essential functions or characteristics of the project. All aspects of the proposed change will be evaluated in determining the value of the proposed change to the project, for example: service life, economy of operations, ease of maintenance, appearance, and design and safety standards.
B. Value Engineering Proposals may be initiated by the Contractor including subcontractors, the Owner, and the Owner's designer including subconsultants.
C. Upon receipt of a Value Engineering Proposal (VEP), the Owner will assemble a preliminary review team to evaluate all aspects of the VEP, for example: construction cost savings, contractor costs to develop and implement the VEP, Owner costs to develop and implement the VEP, required design changes, and functional considerations.
D. If the preli minary review results in agreement on the merits of further action on the VEP, the review team will recommend full development of the VEP. The Owner will estimate development, life cycle, and redesign costs, and the contractor will estimate and propose construction costs savings.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 SUBSTITUTION PROCEDURES
01 25 00 - 5
1.9 VEP FORMAT
A. The Contractor's Value Engineering Proposal will contain the following:
1. A description of the proposed change and of the existing contract requirements affected by the proposed change.
2. A detailed estimate of the costs of performing the work as originally designed and of the costs of performing in accordance with the proposed change.
3. Advantages and disadvantages of the existing design and the proposed change.
4. A statement as to the effect that the proposed change will have on the time required for completion of the project.
B. The City shall prepare the following:
1. A list of contract document changes required by acceptance of the proposed change.
2. A detailed estimate of Owner development and redesign costs required by acceptance of the proposed change.
3. An estimate of time duration for redesign effort required by acceptance of the proposed change.
4. An estimate of the effect of the proposed change on life cycle costs.
1.10 ANALYSIS FOR ACCEPTANCE
A. The review team will analyze th e fully developed proposal for functional equivalence, characteristics, development costs, construction cost savings, and life cycle costs, and recommend acceptance or rejection by the Owner.
B. The Owner will be the sole judge of acceptability of the proposal.
1.11 MODIFICATION OF CONTRACT FOR VEP
A. Upon acceptance of a VEP, the Owner and Contractor will agree on the scope and price adjustments required. The contract price will be reduced by the following amount:
(Construction cost savings less contractor development costs less Owner development costs) multiplied by 0.50.
B. Upon agreement as to changes in scope and price, the necessary change order will be issued, specifically stating that it is issued under the provision Section: VALUE ENGINEERING of this contract, a nd fully describing the required changes in the plans and specifications.
C. During submittal, analysis, review, and negotiation of any VEP, the Contractor shall continue to perform the work in accordance with the original requirements of the contract unless otherwise directed in writing by the Owner.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 SUBSTITUTION PROCEDURES
01 25 00 - 6
PART 2 - EXECUTION (Not Used)
END OF SECTION 01 25 00
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 CONTRACT MODIFICATION PROCEDURES
01 26 00 - 1
SECTION 01 26 00 - CONTRACT MODIFICATION PROCEDURES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, inc luding General and Supplementary Conditions and other Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes administrative and procedural requirements for handling and processing Contract modifications.
B. Related Requirements:
1. Section 01 25 00 "Substitution Procedures" for administrative procedures for handling requests for substitutions made after the Contract award.
1.3 MINOR CHANGES IN THE WORK
A. Owner will issue through Construction Manager supplemental instructions authorizing minor changes in the Work, not involving adjustment to the Contract Sum or the Contract Time,
1.4 PROPOSAL REQUESTS
A. Owner-Initiated Proposal Requests: Construction Manager will issue a detailed description of proposed changes in the Work that may require adjustment to the Contract Sum or the Contract Time. If necessary, the description will include supplemental or revised Drawings and Specifications.
1. Work Chang e Proposal Requests issued by Construction Manager are not instructions either to stop work in progress or to execute the proposed change.
2. Within time specified in Proposal Request after receipt of Proposal Request, submit a quotation estimating cost adjustments to the Contract Sum and the Contract Time necessary to execute the change.
a. Include a list of quantities of products required or eliminated and unit costs, with total amount of purchases and credits to be made. If requested, furnish survey data to substantiate quantities.
b. Indicate applicable taxes, delivery charges, equipment rental, and amounts of trade discounts.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 CONTRACT MODIFICATION PROCEDURES
01 26 00 - 2
c. Include costs of labor and supervision directly attributable to the change. d. Include an updated Contractor's construction schedule that indicates the effect of the change, including, but not limited to, changes in activity duration, start and finish times, and activity relationship. Use available total float before requesting an extension of the Contract Time. e. Quotation Form: Use EZ-PCO form provided by Owner. Sample copies are included in this section.
B. Contractor-Initiated Proposals: If latent or changed condi tions require modifications to the Contract, Contractor may initiate a claim by submitting a request for a change to Construction Manager.
1. Include a statement outlining reasons for the change and the effect of the change on the Work. Provide a complete des cription of the proposed change. Indicate the effect of the proposed change on the Contract Sum and the Contract Time.
2. Include a list of quantities of products required or eliminated and unit costs, with total amount of purchases and credits to be made. If requested, furnish survey data to substantiate quantities.
3. Indicate applicable taxes, delivery charges, equipment rental, and amounts of trade discounts.
4. Include costs of labor and supervision directly attributable to the change.
5. Include an updated Contractor's construction schedule that indicates the effect of the change, including, but not limited to, changes in activity duration, start and finish times, and activity relationship. Use available total float before requesting an extension of the Contract Time.
6. Comply with requirements in Section 01 25 00 "Substitution Procedures" if the proposed change requires substitution of one product or system for product or system specified.
7. Proposal Request Form: Use EZ-PCO form provided by Owner . Sample copy is included in this section.
1.5 ADMINISTRATIVE CHANGE ORDERS
A. Allowance Adjustment: See Section 01 21 00 "Allowances" for administrative procedures for preparation of Change Order Proposal for adjusting the Contract Sum to reflect actual costs of allowances.
B. Unit-Price Adjustment: See Section 01 22 00 "Unit Prices" for administrative procedures for preparation of Change Order Proposal for adjusting the Contract Sum to reflect measured scope of unit-price work.
1.6 CHANGE ORDER PROCEDURES
A. On Owner's approval of a Work Change Proposal Request, Construction Manager will issue a Change Order for signatures of Owner and Contractor.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 CONTRACT MODIFICATION PROCEDURES
01 26 00 - 3
1.7 CONSTRUCTION CHANGE DIRECTIVE
A. Construction Change Directive: Construction Manager may issue a Construction Change Directive on form included in Project Manual. Construction Change Directive instructs Contractor to proceed with a change in the Work, for subsequent inclusion in a Change Order.
1. Construction Change Directive contains a complete description of change in the Work. It also designates method to be followed to determine change in the Contract Sum or the Contract Time.
B. Documentation: Maintain detailed records on a time and material basis of work required by the Construction Change Directive.
1. After completion of change, submit an itemized account an d supporting data necessary to substantiate cost and time adjustments to the Contract.
PART 2 - PRODUCTS (Not Used)
PART 3 - EXECUTION (Not Used)
END OF SECTION 01 26 00
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 PAYMENT PROCEDURES
01 29 00 - 1
SECTION 01 29 00 - PAYMENT PROCEDURES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes administrative and procedural requirements necessary to prepare and process Applications for Payment.
B. Related Requirements:
1. Section 01 26 00 "Contract Modification Procedures " for administrative procedures for handling changes to the Contract.
2. Section 01 32 00 "Construction Prog ress Documentation " for administrative requirements governing the preparation and submittal of the Contractor's construction schedule.
1.3 DEFINITIONS
A. Schedule of Values: A statement furnished by Contractor allocating portions of the Contract Sum to various po rtions of the Work and used as the basis for reviewing Contractor's Applications for Payment.
1.4 SCHEDULE OF VALUES
A. Coordination: Coordinate preparation of the schedule of values with preparation of Contractor's construction schedule.
1. Coordinate line items in the schedule of values with items required to be indicated as separate activities in Contractor's construction schedule.
2. Submit the schedule of values to City’s Project Manager at earliest possible date, but no later than 14 days before the date scheduled for submittal of initial Applications for Payment.
3. Subschedules for Separate Elements of Work: Where the Contractor's construction schedule defines separate elements of the Wo rk, provide subschedules showing values coordinated with each element.
4. Subschedules for Separate Design Contracts: Where the Owner has retained design professionals under separate contracts who will each provide certification of payment requests, provide subschedules showing values coordinated with the
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 PAYMENT PROCEDURES
01 29 00 - 2
scope of each design services contract , as described in Section 01 10 00 "Summary."
B. Format and Content: Use Project Manual table of contents as a guide to establish line items for the schedule of values. Provide at least one line item for each Specification Section.
1. Identification: Include the following Project identification on the schedule of values:
a. Project name and location.
b. City's Project number.
c. Contractor's name, address and phone number.
d. Date of submittal.
2. Arrange schedule of values consistent with format of City provided Schedule of Values form.
3. Provide a breakdown of the Contract Sum in enough detail to facilitate continued evaluation of Applications for Payment and progress reports. Provide multiple line items for principal subcontract amounts in excess of five percent of the Contract Sum.
4. Provide a separate line item in the schedule of values for each part of the Work where Applications for Payment may include materials or equipment purchased or fabricated and stored, but not yet installed.
5. Differentiate between items stored on-site and items stored off-site.
6. Overhead Costs: Include total cost and proportionate share of general overhead and profit for each line item.
7. Overhead Costs: Show cost of temporary facilities and other major cost items that are not direct cost of actual work-in-place as separate line items.
8. Closeout Costs. Include separate line items under Contractor and principal subcontracts for Project closeout requirements in an amount totaling equal or greater than five percent of the Contract Sum and subcontract amount.
9. Schedule of Values Revisions : Revise the schedule of values when Change Orders or Construction Change Directives result in a change in the Contract Sum. Include at least one separate line item for each Change Order and Construction Change Directive.
1.5 APPLICATIONS FOR PAYMENT
A. Each Application for Payment following the initial Application for Payment shall be consistent with previous applications and payments as certified by City’s Project Manager and paid for by Owner.
B. Payment Application Times: The date for each progress payment is indicated in the Agreement between Owner and Contractor. The period of construction work covered by each Application for Payment is the period indicated in the Agreement.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 PAYMENT PROCEDURES
01 29 00 - 3
1. Submit draft copy of Application for Payment ten days prior to due date for review by City Labor Compliance, Inspector, Project & Construction Manager.
C. Application for Payment Forms: Use City provided form for Applications for Payment.
D. Application Preparation: Complete every entry on form. Execute by a person authorized to sign legal documents on behalf of Contractor. City will return incomplete applications without action.
1. Entries shall match data on the schedule of values and Contractor's construction schedule. Use updated schedules if revisions were made.
2. Include amounts for work completed following previous Application for Payment, whether or not payment has b een received. Include only amounts for work completed at time of Application for Payment.
3. Include amounts of Change Orders and Construction Change Directives issued before last day of construction period covered by application.
4. Indicate separate amounts fo r work being carried out under Owner -requested project acceleration.
E. Stored Materials: Include in Application for Payment amounts applied for materials or equipment purchased or fabricated and stored, but not yet installed. Differentiate between items stored on-site and items stored off-site.
1. Provide address of warehouse facility, certificate of insurance, evidence of transfer of title to Owner, and consent of surety to payment for stored materials.
2. Provide supporting documentation that verifies amount requ ested, such as paid invoices. Match amount requested with amounts indicated on documentation; do not include overhead and profit on stored materials.
3. Provide summary documentation for stored materials indicating the following:
a. Value of materials previously stored and remaining stored as of date of previous Applications for Payment.
b. Value of previously stored materials put in place after date of previous Application for Payment and on or before date of current Application for Payment.
c. Value of materials stored since date of previous Application for Payment and remaining stored as of date of current Application for Payment.
F. Transmittal: Submit one signed original cop y of each Application for Payment to Construction Manager by a method ensuring receipt.Include waivers of lien and similar attachments as required.
1. Transmit each copy with a transmittal f orm listing attachments and recording appropriate information about application.
G. Waivers of Mechanic's Lien: With each Application for Payment, submit waivers of mechanic's lien from subcontractors, sub-subcontractors, and suppliers for construction period covered by the previous application.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 PAYMENT PROCEDURES
01 29 00 - 4
1. Submit partial waivers on each item for amount requested in previous application, after deduction for retainage, on each item.
2. When an application shows completion of an item, submit conditional final or full waivers.
3. Owner reserves the right t o designate which entities involved in the Work must submit waivers.
4. Submit final Application for Payment with or preceded by conditional final waivers from every entity involved with performance of the Work covered by the application who is lawfully entitled to a lien.
5. Waiver Forms: Submit executed waivers of lien on forms acceptable to Owner.
H. Initial Application for Payment: Administrative actions and submittals that must precede or coincide with submittal of first Application for Payment include the following:
1. List of subcontractors.
2. Schedule of values.
3. Contractor's construction schedule (preliminary if not final).
4. Combined Contractor's construction schedule (preliminary if not final) incorporating Work of multiple contracts, with indication of acceptance of schedule by each Contractor.
5. Products list (preliminary if not final).
6. Sustainable design action plans, including preliminary project materials cost data.
7. Schedule of unit prices.
8. Submittal schedule (preliminary if not final).
9. List of Contractor's staff assignments.
10. List of Contractor's principal consultants.
11. Copies of building permits.
12. Copies of authorizations and licenses from authorities having jurisdiction for performance of the Work.
13. Initial progress report.
14. Report of preconstruction conference.
I. Application for Payment at Substantial Completion: After City issues the Certificate of Substantial Completion, submit an Application for Payment showing 100 percent completion for portion of the Work claimed as substantially complete.
1. Include documentation supporting claim that the Work is substantially complete and a statement showing an accounting of changes to the Contract Sum.
2. This application shall reflect Certificate(s) of Substantial Completion issued previously for Owner occupancy of designated portions of the Work.
J. Final Payment Application: After completing Project closeout requirements, submit final Application for Payment with releases and supporting documentation not previously submitted and accepted, including, but not limited, to the following:
1. Evidence of completion of Project closeout requirements.
2. Insurance certificates for products and completed operations where required and proof that taxes, fees, and similar obligations were paid.
3. Updated final statement, accounting for final changes to the Contract Sum.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 PAYMENT PROCEDURES
01 29 00 - 5
4. Evidence that claims have been settled.
5. Final meter readings for utilities, a measured record of stored fuel, and similar data as of date of Substantial Completion or when Owner took possession of and assumed responsibility for corresponding elements of the Work.
6. Final liquidated damages settlement statement.
PART 2 - PRODUCTS (Not Used)
PART 3 - EXECUTION (Not Used)
END OF SECTION 01 29 00
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 PROJECT MANAGEMENT AND COORDINATION
01 31 00 - 1
SECTION 01 31 00 - PROJECT MANAGEMENT AND COORDINATION
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provi sions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes administrative provisions for coordinating construction operations on Project including, but not limited to, the following:
1. General coordination procedures.
2. Coordination drawings.
3. RFIs.
4. Digital project management procedures.
5. Project meetings.
B. Related Requirements:
1. Section 01 32 00 "Construction Progress Documentation" for preparing a nd submitting Contractor's construction schedule.
2. Section 01 73 00 "Execution" for procedures for coordinating general installation and field -engineering services, including establishment of benchmarks and control points.
3. Section 01 77 00 "Closeout Procedu res" for coordinating closeout of the Contract.
1.3 DEFINITIONS
A. BIM: Building Information Modeling.
B. RFI: Request for Information. Request from Owner, Architect, or Contractor seeking information required by or clarifications of the Contract Documents.
1.4 INFORMATIONAL SUBMITTALS
A. Subcontract List: Prepare a written summary identifying indi viduals or firms proposed for each portion of the Work, including those who are to furnish products or equipment fabricated to a special design. Include the following information in tabular form:
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 PROJECT MANAGEMENT AND COORDINATION
01 31 00 - 2
1. Name, address, telephone number, and email address of entity performing subcontract or supplying products.
2. Number and title of related Specification Section(s) covered by subcontract.
3. Drawing number and detail references, as appropriate, covered by subcontract.
B. Key Personnel Names: Within 5 days of starting construction operations, submit a list of key personnel assignments, including superintendent and other personnel in attendance at Project site. Identify individuals and their duties and responsibilities; list addresses and cellular telep hone numbers and e -mail addresses. Provide names, addresses, and telephone numbers of individuals assigned as alternates in the absence of individuals assigned to Project.
1. Post copies of list in project meeting room, in temporary field office, in web-based Project software directory, and in prominent location in each built facility. Keep list current at all times.
1.5 GENERAL COORDINATION PROCEDURES
A. Coordination: Coordinate construction operations included in different Sections of th e Specifications to ensure efficient and orderly installation of each part of the Work.
Coordinate construction operations included in different Sections that depend on each other for proper installation, connection, and operation.
1. Schedule construction operations in sequence required to obtain the best results where installation of one part of the Work depends on installation of other components, before or after its own installation.
2. Coordinate installation of different components to ensure maximum performance and accessibility for required maintenance, service, and repair.
3. Make adequate provisions to accommodate items scheduled for later installation.
B. Prepare memoranda for distribution to each party involved, outlining special procedures required for coordinati on. Include such items as required notices, reports, and list of attendees at meetings.
1. Prepare similar memoranda for Owner and separate contractors if coordination of their Work is required.
C. Administrative Procedures: Coordinate scheduling and timing of required administrative procedures with other construction activities to avoid conflicts and to ensure orderly progress of the Work. Such administra tive activities include, but are not limited to, the following:
1. Preparation of Contractor's construction schedule.
2. Preparation of the schedule of values.
3. Installation and removal of temporary facilities and controls.
4. Delivery and processing of submittals.
5. Progress meetings.
6. Preinstallation conferences.
7. Project closeout activities.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 PROJECT MANAGEMENT AND COORDINATION
01 31 00 - 3
8. Startup and adjustment of systems.
1.6 COORDINATION DRAWINGS
A. Coordination Drawings, General: Prepare coordination drawings according to requirements in individual Sections, and additional ly where installation is not completely indicated on Shop Drawings, where limited space availability necessitates coordination, or if coordination is required to facilitate integration of products and materials fabricated or installed by more than one entity.
1. Content: Project-specific information, drawn accurately to a scale large enough to indicate and resolve conflicts. Do not base coordination drawings on standard printed data. Include the following information, as applicable:
a. Use applicable Drawings as a basis for preparation of coordination drawings. Prepare sections, elevations, and details as needed to describe relationship of various systems and components.
b. Indicate functional and spatial relationships of components of architectural, structural, civil, mechanical, and electrical systems.
c. Indicate space requirements for routine maintenance and for anticipated replacement of components during the life of the installation. d. Show location and size of access doors required for access to concealed dampers, valves, and other controls.
e. Indicate required installation sequences.
f. Indicate dimensions shown on Drawings. Specifically note dimensions that appear to be in conflict with submitted equipment and minimum clearance requirements. Provide alternative sketches to Architect indicating proposed resolution of such conflicts. Minor dimension changes and difficult installations will not be considered changes to the Contract.
B. Coordination Drawing Organization: Organize coordination drawings as follows:
1. Floor Plans and Reflected Ceiling Plans: Show architectural and structural elements, and mechanical, plumbing, fire -protection, fire -alarm, and electrical Work. Show locations of visible ceiling -mounted devices relative to acoustical ceiling grid. Supplement plan drawings with section drawings where required to adequately represent the Work.
2. Plenum Space: Indicate sub -framing for support of ce iling, and wall systems, mechanical and electrical equipment, and related Work. Locate components within plenums to accommodate layout of light fixtures and other components indicated on Drawings. Indicate areas of conflict between light fixtures and other components.
3. Mechanical Rooms: Provide coordination drawings for mechanical rooms showing plans and elevations of mechanical, plumbing, fire-protection, fire-alarm, and electrical equipment.
4. Structural Penetrations: Indicate penetrations and openings requi red for all disciplines.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 PROJECT MANAGEMENT AND COORDINATION
01 31 00 - 4
5. Slab Edge and Embedded Items: Indicate slab edge locations and sizes and locations of embedded items for metal fabrications, sleeves, anchor bolts, bearing plates, angles, door floor closers, slab depressions for floor finishes, curbs and housekeeping pads, and similar items.
6. Mechanical and Plumbing Work: Show the following:
a. Sizes and bottom elevations of ductwork, piping, and conduit runs, including insulation, bracing, flanges, and support systems. b. Dimensions of major components, such as dampers, valves, diffusers, access doors, cleanouts and electrical distribution equipment. c. Fire-rated enclosures around ductwork.
7. Electrical Work: Show the following:
a. Runs of vertical and horizontal conduit 1-1/4 inchesin diameter and larger. b. Light fixture, exit light, emergency battery pack, smoke detector, and other fire-alarm locations.
c. Panel board, switch board, switchgear, transformer, busway, generator, and motor-control center locations.
d. Location of pull boxes and junction boxes, dimensioned from column center lines.
8. Fire-Protection System: Show the following:
a. Locations of standpipes, mains piping, branch lines, pipe drops, and sprinkler heads.
9. Review: Owner will review coordination drawings to confirm that in general the Work is being coordi nated, but not for the details of the coordination, which are Contractor's responsibility. If Owner determines that coordination drawings are not being prepared in sufficient scope or detail, or are otherwise deficient, Owner will so inform Contractor, who shall make suitable modifications and resubmit.
10. Coordination Drawing Prints: Prepare coordination drawing prints according to requirements in Section 01 33 00 "Submittal Procedures." C. Coordination Digital Data Files: Prepare coordination digital data files according to the following requirements:
1. File Preparation Format: Same digital data software program, version, and operating system as original Drawings.
2. BIM File Incorporation: Develop and incorporate coordination drawing files into BIM established for Project.
a. Perform three-dimensional component conflict analysis as part of preparation of coordination drawings. Resolve component conflicts prior to submittal. Indicate where conflict resolution requires modification of design requirements by Architect.
3. Architect will furnish Contractor one set of digital data files of Drawings for use in preparing coordination digital data files.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 PROJECT MANAGEMENT AND COORDINATION
01 31 00 - 5
a. Architect makes no representations as to the accuracy or completeness of digital data files as they relate to Drawings.
b. Digital Data Software Program: Drawings are available in Architect’s program and version in effect for the Project
c. Contractor shall execute a data licensing agreement in the form of the Agreement included in this Project Manual, or if not included, as acceptable to Architect and Owner.
1.7 REQUEST FOR INFORMATION (RFI)
A. General: Immediately on discovery of the need for additional information, clarification, or interpretation of the Contract Documents, Contractor shall prepare and submit an RFI in the form specified.
1. Owner will return without response those RFIs submitted to Owner by other entities controlled by Contractor.
2. Coordinate and submit RFIs in a prompt manner so as to avoid delays in Contractor's work or work of subcontractors.
B. Content of the RFI: Include a detailed, legible description of i tem needing information or interpretation and the following:
1. Project name.
2. Project number.
3. Date.
4. Name of Contractor.
5. Name of Architect and Owner
6. RFI number, numbered sequentially.
7. RFI subject.
8. Specification Section number and title and related paragraphs, as appropriate.
9. Drawing number and detail references, as appropriate.
10. Field dimensions and conditions, as appropriate.
11. Contractor's suggested resolution. If Contractor's suggested resolution impacts the Contract Time or the Contract Sum, Contractor shall state impact in the RFI.
12. Contractor's signature.
13. Attachments: Include sketches, descriptions, measurements, photos, Product Data, Shop Drawings, coordination drawings, and other information necessary to fully describe items needing interpretation.
a. Include dimensions, thicknesses, structural grid references, and details of affected materials, assemblies, and attachments on attached sketches.
C. RFI Forms: Form bound in Project Manual or Software-generated form with substantially the same content as indicated above, acceptable to Owner.
1. Attachments shall be electronic files in PDF format.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 PROJECT MANAGEMENT AND COORDINATION
01 31 00 - 6
D. Owner's Action: Owner will review each RFI, determine action required, and respond.
Allow five working days for Owner's response for each RFI. RFIs receiv ed by Owner after 1:00 p.m. will be considered as received the following working day.
1. The following Contractor-generated RFIs will be returned without action:
a. Requests for approval of submittals.
b. Requests for approval of substitutions.
c. Requests for approval of Contractor's means and methods. d. Requests for coordination information already indicated in the Contract Documents.
e. Requests for adjustments in the Contract Time or the Contract Sum. f. Requests for interpretation of Architect's actions on submittals. g. Incomplete RFIs or inaccurately prepared RFIs.
2. Owner's action may include a request for additional information, in which case Owner's time for response will date from time of receipt by Owner of additional information.
3. Owner's action on RFIs that may result i n a change to the Contract Time or the Contract Sum may be eligible for Contractor to submit Change Proposal according to Section 01 26 00 "Contract Modification Procedures." a. If Contractor believes the RFI response warrants change in the Contract Time or t he Contract Sum, notify Owner in writing within 5 days of receipt of the RFI response.
E. RFI Log: Prepare, maintain, and submit a tabular log of RFIs organized by the RFI number. Submit log weekly. Software log with not less than the following:
1. Project name.
2. Name and address of Contractor.
3. Name and address of Architect.
4. RFI number including RFIs that were returned without action or withdrawn.
5. RFI description.
6. Date the RFI was submitted.
7. Date Owner's response was received.
8. Identification of related Minor Change in the Work, Construction Change Directive, and Proposal Request, as appropriate.
F. On receipt of Owner's action, update the RFI log and immediately distribute the RFI response to affected parties. Review response and notify Owner within five days if Contractor disagrees with response.
1.8 DIGITAL PROJECT MANAGEMENT PROCEDURES
A. Use of Architect's Digital Data Files: Digital data files of Architect's CAD drawings will be provided by Architect for Contractor's use during construction.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 PROJECT MANAGEMENT AND COORDINATION
01 31 00 - 7
1. Digital data files may be used by Contractor in preparing coordination drawings, Shop Drawings, and Project record Drawings.
2. Architect makes no representations as to the accuracy or completeness of digital data files as they relate to Contract Drawings.
3. Digital Data Software Pr ogram: Drawings are available in Architect’s program and version in effect for the Project
4. Contractor shall execute a data licensing agreement in the form of the Agreement included in this Project Manual , or if not included, as acceptable to Architect and Owner.
a. Subcontractors, and other parties grante d access by Contractor to Architect's digital data files shall execute a data licensing agreement in the form of Agreement included in this Project Manual.
5. AutoCAD background drawings will be made available for Owner’s use.
6. The following digital data files will be furnished for each appropriate discipline:
a. Site plans.
b. Floor plans.
c. Reflected ceiling plans.
B. Web-Based Project Software: Provide, administer, and use web-based Project software site f or purposes of hosting and managing Project communication and documentation until Final Completion.
1. Web-based Project software site includes, at a minimum, the following features:
a. Compilation of Project data, including Contractor, subcontractors, Architect, architect's consultants, Owner, and other entities involved in Project.
Include names of individuals and contact information.
b. Access control for each entity for each workflow process, to determine entity's digital rights to create, modify, view, and print documents. c. Document workflow planning, allowing customization of workflow between project entities.
d. Creation, logging, tracking, and notification for Project communications required in other Specification Sections, including, but not limited to, RFIs, submittals, Minor Changes in the Work, Construction Change Directives, and Change Orders.
e. Track status of each Project communication in real time, and log time and date when responses are provided.
f. Procedures for handling PDFs or similar file formats , allowing markups by each entity. Provide security features to lock markups against changes once submitted.
g. Processing and tracking of payment applications.
h. Processing and tracking of contract modifications.
i. Creating and distributing meeting minutes.
j. Document management for Drawings, Specifications, and coordination drawings, including revision control.
k. Management of construction progress photographs.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 PROJECT MANAGEMENT AND COORDINATION
01 31 00 - 8
l. Mobile device compatibility, including smartphones and tablets.
2. Provide up to seven web-based Project sof tware user licenses for use of Owner, , Architect, and Architect's consultants. Upon request, provide four hours of software training at Owner's office for web-based Project software users.
3. At completion of Project, provide digital archive in format that is readable by common desktop software applications in format acceptable to Architect. Provide data in locked format to prevent further changes.
4. Provide one of the following web -based Project software packages under their current published licensing agreements:
a. Autodesk;
b. Corecon Technologies, Inc.
c. Meridian Systems; Prolog.
d. Newforma, Inc.
e. Procore Technologies, Inc.
f. Viewpoint, Inc.; Viewpoint for Project Collaboration.
C. PDF Document Preparation: Where PDFs are required to be submitted to Architect, prepare as follows:
1. Assemble complete submittal package into a single inde xed file incorporating submittal requirements of a single Specification Section and transmittal form with links enabling navigation to each item.
2. Name file with submittal number or other unique identifier, including revision identifier.
3. Certifications: Whe re digitally submitted certificates and certifications are required, provide a digital signature with digital certificate on where indicated.
1.9 PROJECT MEETINGS
A. General: Schedule and conduct meetings and conferences at Project site unless otherwise indicated.
1. Attendees: Inform participants and others involved, and individuals whose presence is required, of date and time of each meeting. Notify Owner and Architect of scheduled meeting dates an d times a minimum of 10 working days prior to meeting.
2. Agenda: Prepare the meeting agenda. Distribute the agenda to all invited attendees.
3. Minutes: Entity responsible for conducting meeting will record significant discussions and agreements achieved. Distr ibute the meeting minutes to everyone concerned, including Owner and Architect, within three days of the meeting.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 PROJECT MANAGEMENT AND COORDINATION
01 31 00 - 9
B. Preconstruction Conference: Owner will schedule and conduct ] a preconstruction conference before starting construct ion, at a time convenient to Owner and Architect, but no later than 15days after execution of the Agreement.
1. Attendees: Authorized representatives of Owner, Architect, and their consultants; Contractor and its superintendent; major subcontractors; suppliers; and other concerned parties shall attend the conference. Participants at the conference shall be familiar with Project and authorized to conclude matters relating to the Work.
2. Agenda: Discuss items of significance that could affect progress, including the following:
a. Responsibilities and personnel assignments.
b. Tentative construction schedule.
c. Phasing.
d. Critical work sequencing and long lead items.
e. Designation of key personnel and their duties.
f. Lines of communications.
g. Use of web-based Project software.
h. Procedures for processing field decisions and Change Orders. i. Procedures for RFIs.
j. Procedures for testing and inspecting.
k. Procedures for processing Applications for Payment.
l. Distribution of the Contract Documents.
m. Submittal procedures.
n. Sustainable design requirements.
o. Preparation of Record Documents.
p. Use of the premises.
q. Work restrictions.
r. Working hours.
s. Owner's occupancy requirements.
t. Responsibility for temporary facilities and controls. u. Procedures for moisture and mold control.
v. Procedures for disruptions and shutdowns.
w. Construction waste management and recycling.
x. Parking availability.
y. Office, work, and storage areas.
z. Equipment deliveries and priorities.
aa. First aid.
bb. Security.
cc. Progress cleaning.
3. Minutes: Entity responsible for conducting meeting will record and d istribute meeting minutes.
C. Sustainable Design Requirements Coordination Conference: Owner will schedule and conduct a sustainable design coordination conference before starting construction, at a time convenient to Owner, Architect, and Contractor.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 PROJECT MANAGEMENT AND COORDINATION
01 31 00 - 10
1. Attendees: Authorized representatives of Owner, Architect, and their consultants; Contractor and its superintendent and sustainable design coordinator; major subcontractors; suppliers; and other concerned parties shall attend the conference. Participants at the conference shall be familiar with Project and authorized to conclude matters relating to the Work.
2. Agenda: Discuss items of significance that could affect meeting sustainable design requirements, including the following:
a. General requirements for sustainable design -related procurement and documentation.
b. Project closeout requirements and sustainable design certification procedures.
c. Construction waste management.
d. Construction operations and restrictions.
3. Minutes: Entity responsible for conducting meeting will record and distribute meeting minutes.
D. Preinstallation Conferences: Conduct a preinstallation conference at Project site before each construction activity when required by other sections and when required for coordination with other construction.
1. Attendees: Installer and representatives of manufacturers and fabricators involved in or affected by the installation and its c oordination or integration with other materials and installations that have preceded or will follow, shall attend the meeting. Advise Owner of scheduled meeting dates.
2. Agenda: Review progress of other construction activities and preparations for the particular activity under consideration, including requirements for the following:
a. Contract Documents.
b. Options.
c. Related RFIs.
d. Related Change Orders.
e. Purchases.
f. Deliveries.
g. Submittals.
h. Sustainable design requirements.
i. Review of mockups.
j. Possible conflicts.
k. Compatibility requirements.
l. Time schedules.
m. Weather limitations.
n. Manufacturer's written instructions.
o. Warranty requirements.
p. Compatibility of materials.
q. Acceptability of substrates.
r. Temporary facilities and controls.
s. Space and access limitations.
t. Regulations of authorities having jurisdiction.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 PROJECT MANAGEMENT AND COORDINATION
01 31 00 - 11
u. Testing and inspecting requirements.
v. Installation procedures.
w. Coordination with other work.
x. Required performance results.
y. Protection of adjacent work.
z. Protection of construction and personnel.
3. Record significant conference discussions, agreements, and disagreements, including required corrective measures and actions.
4. Reporting: Distribute minutes of the meeting to each party present and to other parties requiring information.
5. Do not proceed with installation if the conference cannot be successfully concluded. Initiate whatever actions are necessary to resolve impedime nts to performance of the Work and reconvene the conference at earliest feasible date.
E. Project Closeout Conference: Schedule and conduct a project closeout conference, at a time convenient to Owner and Architect, but no later than 30 days prior to the scheduled date of Substantial Completion.
1. Conduct the conference to review requirements and responsibilities related to Project closeout.
2. Attendees: Authorized representatives of Owner, Architect, and their consultants; Contractor and its superintendent; major subcontractors; suppliers; and other concerned parties shall attend the meeting. Participants at the meeting shall be familiar with Project and authorized to conclude matters relating to the Work.
3. Agenda: Discuss items of significance that could affect or delay Project closeout, including the following:
a. Preparation of Record Documents.
b. Procedures required prior to inspection for Substantial Completion and for final inspection for acceptance.
c. Procedures for completing and archiving web -based Project software site data files.
d. Submittal of written warranties.
e. Requirements for preparing operations and maintenance data. f. Requirements for delivery of material samples, attic stock, and spare parts. g. Requirements for demonstration and training.
h. Preparation of Contractor's punch list.
i. Procedures for processing Applications for Payment at Substantial Completion and for final payment.
j. Submittal procedures.
k. Coordination of separate contracts.
l. Owner's partial occupancy requirements.
m. Installation of Owner's furniture, fixtures, and equipment. n. Responsibility for removing temporary facilities and controls.
4. Minutes: Entity conducting meeting will record and distribute meeting minutes.
F. Progress Meetings: Conduct progress meetings at regular intervals.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 PROJECT MANAGEMENT AND COORDINATION
01 31 00 - 12
1. Coordinate dates of meetings with preparation of payment requests.
2. Attendees: In addition to representatives of Owner , and Architect, each contractor, sub contractor, supplier, and other entity concerned with current progress or involved in planning, coordination, or performance of future activities shall be represented at these meetings. All participants at the meeting shall be familiar with Project and authorized to conclude matters relating to the Work.
3. Agenda: Review and correct or approve minutes of previous progress meeting.
Review other items of significance that could affect progress. Include topics for discussion as appropriate to status of Project.
a. Contractor's Construction Schedule: Review progress since the last meeting. Determine whether each activity is on time, ahead of schedule, or behind schedule, in relation to Contractor's construction sche dule.
Determine how construction behind schedule will be expedited; secure commitments from parties involved to do so. Discuss whether schedule revisions are required to ensure that current and subsequent activities will be completed within the Contract Time.
1) Review schedule for next period.
b. Review present and future needs of each entity present, including the following:
1) Interface requirements.
2) Sequence of operations.
3) Resolution of BIM component conflicts.
4) Status of submittals.
5) Deliveries.
6) Off-site fabrication.
7) Access.
8) Site use.
9) Temporary facilities and controls.
10) Progress cleaning.
11) Quality and work standards.
12) Status of correction of deficient items.
13) Field observations.
14) Status of RFIs.
15) Status of Proposal Requests.
16) Pending changes.
17) Status of Change Orders.
18) Pending claims and disputes.
19) Documentation of information for payment requests.
4. Minutes: Entity responsible for conducting the meeting will record and distribute the meeting minutes to each party present and to parties requiring information. a. Schedule Updating: Revise Contractor's c onstruction schedule after each progress meeting where revisions to the schedule have been made or
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 PROJECT MANAGEMENT AND COORDINATION
01 31 00 - 13
recognized. Issue revised schedule concurrently with the report of each meeting.
G. Coordination Meetings: Conduct Project coordination meetings at regular intervals.
Project coordination meetings are in addition to specific meeting s held for other purposes, such as progress meetings and preinstallation conferences.
1. Attendees: In addition to representatives of Owner and Archi tect, each contractor, subcontractor, supplier, and other entity concerned with current progress or involved in planning, coordination, or performance of future activities shall be represented at these meetings. All participants at the meetings shall be familiar with Project and authorized to conclude matters relating to the Work.
2. Agenda: Review and correct or approve minutes of the previous coordination meeting. Review other items of significance that cou ld affect progress. Include topics for discussion as appropriate to status of Project. a. Combined Contractor's Construction Schedule: Review progress since the last coordination meeting. Determine whether each contract is on time, ahead of schedule, or behin d schedule, in relation to combined Contractor's construction schedule. Determine how construction behind schedule will be expedited; secure commitments from parties involved to do so. Discuss whether schedule revisions are required to ensure that current and subsequent activities will be completed within the Contract Time.
b. Schedule Updating: Revise combined Contractor's construction schedule after each coordination meeting where revisions to the schedule have been made or recognized. Issue revised schedule concurrently with report of each meeting.
c. Review present and future needs of each contractor present, including the following:
1) Interface requirements.
2) Sequence of operations.
3) Resolution of BIM component conflicts.
4) Status of submittals.
5) Deliveries.
6) Off-site fabrication.
7) Access.
8) Site use.
9) Temporary facilities and controls.
10) Work hours.
11) Hazards and risks.
12) Progress cleaning.
13) Quality and work standards.
14) Status of RFIs.
15) Proposal Requests.
16) Change Orders.
17) Pending changes.
SAFE CREDIT UNION CONVENTION CENTER
POPULOUS 17.4465
SEPTEMBER 8, 2021
BALLROOM B HVAC & LIGHTING SYSTEMS
© Populous 2021 PROJECT MANAGEMENT AND COORDINATION
01 31 00 - 14
3. Reporting: Record meeting results and distribute copies to everyone in attendance and to others affected by decisions or actions resulting from each meeting.
PART 2 - PRODUCTS (Not Used)
PART 3 - EXECUTION (Not Used)
END OF SECTION 01 31 00
REQUEST FOR INFORMATION / INTERPRETATION
Project: City of Sacramento R.F.I. Number:_________
Ballroom B HVAC & Lighting Systems
From:________________
To: ____________________ Date: ________ ________
Fax: ____________
City Project Number:
Specification Section: Paragr aph: Drawing Reference: Detail
Request/Recommendation:
* Requested Date/Time for Response:
Signed by:
Response: