R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
E0.4-1
PANEL SCHEDULES
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
CIRCUIT KEY NOTES: G - PROVIDE GFCI CIRCUIT BREAKER
F - PROVIDE 'LOCK-ON' DEVICE TO BREAKER AND RED LABEL INDICATING 'FIRE ALARM' TO CIRCUIT ID. *TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
TOTAL ESTIMATED DEMAND AMPS: 59.5 A
TOTAL CONNECTED AMPS: 66.22 A
Receptacles 14.82 kVA 83.74% 12.41 kVA TOTAL ESTIMATED DEMAND LOAD: 21.446 kVA Power 9.036 kVA 100.00% 9.036 kVA TOTAL CONNECTED LOAD: 23.86 kVA Lighting 0 kVA 0.00% 0 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND TOTALS*
LOAD SUMMARY
Total Amps: 63.46 68.82 67.65
Total Load: 7.61 kVA 8.19 kVA 8.05 kVA
-- 41 SPACE -- 1 -- -- -- -- -- -- -- -- 1 -- SPACE 42 -- -- 39 SPACE -- 1 -- -- -- -- -- -- -- -- 1 -- SPACE 40 -- -- 37 SPACE -- 1 -- -- -- -- -- -- -- -- 1 -- SPACE 38 -- -- 35 SPACE -- 1 -- -- -- -- -- -- -- -- 1 -- SPACE 36 -- 33 TP-2 15 A 1 12 12 12 2.25 0.6 -- -- -- -- 1 -- SPACE 34 -- 31 OVERHEAD DOOR 15 A 1 12 12 12 0.53 0.36 1.09 1.12 12 12 12 1 15 A HAND DRYER 32 29 46, 102 RECEPTACLES 20 A 1 12 12 12 0.52 0.9 1.09 1.61 12 12 12 1 15 A HAND DRYER 30 27 115 RECEPTACLES 20 A 1 10 10 10 2.29 0.9 1.09 1.94 12 12 12 1 15 A HAND DRYER 28 25 104, 105 RECEPTACLES 20 A 1 12 12 12 0.57 0.72 0.9 2.31 12 12 12 1 20 A 10, 110 RECEPTACLES 26 23 112, 113 RECEPTACLES 20 A 1 12 12 12 1.67 0.54 0.72 0.78 12 12 12 1 20 A TV RECEPTACLES 24 21 108 RECEPTACLES 20 A 1 12 12 12 1.3 0.72 0.72 0.86 12 12 12 1 20 A 105, 107 RECEPTACLES 22 19 113 RECEPTACLES 20 A 1 12 12 12 1.92 0.54 0.54 1 12 12 12 1 20 A 101, 102 RECEPTACLES 20 17 R33 AV RACK 20 A 1 12 12 12 0.4 0.36 0.72 1.91 12 12 12 1 20 A 110, 117 RECEPTACLES 18 15 R33 AV RACK 20 A 1 12 12 12 0.2 0.36 0.54 1.93 12 12 12 1 20 A 114 RECEPTACLES 16 13 102 RECPTACLES 20 A 1 12 12 12 0.26 0.18 0.36 0.18 12 12 12 1 20 A DEDICATED QUAD FOR IT CLOSET 14 G 11 REFRIGERATOR 20 A 1 12 12 12 0.94 1.5 0.18 0.73 12 12 12 1 20 A 114 RECEPTACLES 12 9 103 RECEPTACLES 20 A 1 12 12 12 0.14 1.68 0.18 0.69 12 12 12 1 20 A 112 RECEPTACLES 10 F 7 FIRE ALARM BELL 15 A 1 12 12 12 0.52 0.5 1.94 9 12 12 12 1 20 A MECHOSHADES 8 5 RR SENSORS 20 A 1 12 12 12 0.85 0.96 1.08 2.12 12 12 12 1 20 A 110, 112 RECEPTACLES 6 3 OPEN SIGN 15 A 1 12 12 12 1.02 0.5 0.9 1.15 12 12 12 1 20 A 102, 106, 109 RECEPTACLES 4 1 DRINKING WATER FOUNTAIN 15 A 1 12 12 12 0.14 0.12 0.36 1.24 12 12 12 1 20 A 112 RECEPTACLES 2 K
E
Y
CKT
NO. LOAD DESCRIPTION
OCPD
AMPS P
WIRE
SIZE
H N G
VD
%
A B C VD
%
WIRE
SIZE
G N H
OCPD
P AMPS LOAD DESCRIPTION
CKT
NO.
K
E
Y
NOTES:
ISC: 8.59 kA
SCCR: 10 kA
LOCATION: KITCHENETTE 103 WIRE: 4
FED FROM: 225 A/3P @ SB-MAIN GROUND BUS PHASE: 3
ENCLOSURE: NEMA 1 SOLID NEUTRAL VOLTS: 120/208 Wye
MOUNTING: RECESSED SINGLE TUB MAIN: 225 A MCB
PANEL A
CIRCUIT KEY NOTES: *H - HACR RATED BREAKER
*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
TOTAL ESTIMATED DEMAND AMPS: 573 A
TOTAL CONNECTED AMPS: 603.35 A
Receptacles 31.904 kVA 65.67% 20.952 kVA TOTAL ESTIMATED DEMAND LOAD: 206.415 kVA Power 174.202 kVA 100.00% 174.202 kVA TOTAL CONNECTED LOAD: 217.37 kVA Lighting 11.261 kVA 100.00% 11.261 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND TOTALS*
LOAD SUMMARY (INCLUDES ALL TUBS IN THIS PANEL)
12 SPACE -- 3 -- -- -- -- -- --
11 SERVICE RECEPTACLES 0.36 kVA 1 20 A 20 A 2#12 & 1#12 EGC IN 1" C. -- 10 CU-3 3.54 kVA 2 30 A 30 A 2#10 & 1#10 EGC IN 1" C. *H 9 CU-2 42.87 kVA 3 200 A 200 A 3#1/0 & 1#6 EGC IN 1 1/2" C. *H 8 CU-1 13.69 kVA 3 50 A 50 A 3#6 & 1#10 EGC IN 1" C. *H 7 OU-1B 31.7 kVA 3 150 A 150 A 3#1/0 & 1#6 EGC IN 1 1/4" C. *H 6 OU-1A 31.7 kVA 3 150 A 150 A 3#1/0 & 1#6 EGC IN 1 1/4" C. *H 5 PANEL M1 39.68 kVA 3 225 A 225 A 4#4/0 & 1#4 EGC IN 2 1/2" C. -- 4 PANEL C 11.26 kVA 3 100 A 100 A 4#3 & 1#8 EGC IN 1 1/4" C. -- 3 PANEL B 18.9 kVA 3 225 A 225 A 4#4/0 & 1#4 EGC IN 2 1/2" C. -- 2 PANEL A 23.86 kVA 3 225 A 225 A 4#4/0 & 1#4 EGC IN 2 1/2" C. -- 1 SPD 0 kVA 3 30 A 30 A 4#10 & 1#10 EGC IN 3/4" C. --
CKT LOAD DESCRIPTION Load POLES FRAME TRIP TYPE ACC. WIRE AND RACEWAY
CIRCUIT
KEY
NOTES:
ISC: 40.00 kA
SCCR: 65 kA
LOCATION: OUTDOOR WIRE: 4
FED FROM: SMUD TRANSFORMER GROUND BUS PHASE: 3
ENCLOSURE: NEMA 3R SOLID NEUTRAL VOLTS: 120/208 Wye
MAIN: 800 A MCCB
SWITCHBOARD SB-MAIN
CIRCUIT KEY NOTES:
*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
TOTAL ESTIMATED DEMAND AMPS: 110.1 A
TOTAL CONNECTED AMPS: 110.14 A
TOTAL ESTIMATED DEMAND LOAD: 39.681 kVA
Receptacles 0.72 kVA 100.00% 0.72 kVA TOTAL CONNECTED LOAD: 39.68 kVA Power 38.961 kVA 100.00% 38.961 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND TOTALS*
LOAD SUMMARY
Total Amps: 104.19 121.52 105.24
Total Load: 12.50 kVA 14.57 kVA 12.61 kVA
-- 59 SPACE -- 1 -- -- -- -- -- -- -- -- 1 -- SPACE 60 -- -- 57 SPACE -- 1 -- -- -- -- 0.04 -- -- -- -- -- -- -- 58 -- -- 55 SPARE 20 A 1 -- -- -- 0 0.04 0.02 12 -- 12 2 20 A FAN COIL CONTROL PANELS 56 -- 53 SPARE 20 A 1 -- -- -- 0 0.36 0.32 12 12 12 1 20 A CONDENSATE PUMPS 54 51 MOTOR OPERATED DAMPERS 20 A 1 12 12 12 0.26 0.24 0.19 -- -- -- -- -- -- -- 52 -- -- 49 -- -- -- -- -- -- -- 0.1 0.19 0.12 12 -- 12 2 20 A BC-2 50 47 SS-1 20 A 2 12 -- 12 0.08 0.1 0.08 0.05 12 12 12 1 20 A CP-1 48 45 DED. BMS & COMPUTER 20 A 1 12 12 12 1.3 0.86 0.19 -- -- -- -- -- -- -- 46 -- 43 EF-2 & ROOF RECEPT 20 A 1 12 12 12 0.35 0.34 0.19 0.14 12 -- 12 2 20 A BC-1 44 -- 41 -- -- -- -- -- -- -- 0.03 0.52 1.7 12 12 12 1 20 A EF-1 & ROOF RECEPT 42 39 FC-1-10 20 A 2 12 -- 12 0.09 0.03 1 -- -- -- -- -- -- -- 40 -- -- 37 -- -- -- -- -- -- -- 0.03 1 0.64 12 -- 12 2 20 A FC-1-7 38 35 FC-1-11 20 A 2 12 -- 12 0.09 0.03 1 -- -- -- -- -- -- -- 36 -- -- 33 -- -- -- -- -- -- -- 2.45 1 0.8 12 -- 12 2 20 A FC-1-3 34 31 WH-1 40 A 2 8 -- 10 0.46 2.45 0.55 -- -- -- -- -- -- -- 32 -- -- 29 -- -- -- -- -- -- -- 1 0.55 0.3 12 -- 12 2 20 A FC-1-6 30 27 FC-1-2 20 A 2 12 -- 12 0.49 1 0.55 -- -- -- -- -- -- -- 28 -- -- 25 -- -- -- -- -- -- -- 0.05 0.55 0.21 12 -- 12 2 20 A FC-1-5 26 23 FC-1-12 20 A 2 12 -- 12 0.13 0.05 1 -- -- -- -- -- -- -- 24 -- -- 21 -- -- -- -- -- -- -- 0.03 1 0.76 12 -- 12 2 20 A FC-1-1 22 19 FC-1-9 20 A 2 12 -- 12 0.03 0.03 1 -- -- -- -- -- -- -- 20 -- 17 SP-1 20 A 1 12 12 12 0.75 0.96 1 0.33 12 -- 12 2 20 A FC-1-4 18 -- 15 -- -- -- -- -- -- -- 0.03 0.02 -- -- -- -- -- -- -- 16 -- 13 FC-1-8 20 A 2 12 -- 12 0.02 0.03 0.02 0.02 12 -- 12 2 20 A FC-1-13 14 -- 11 -- -- -- -- -- -- -- 0.79 0.79 -- -- -- -- -- -- -- 12 -- -- 9 -- -- -- -- -- -- -- 0.79 0.79 -- -- -- -- -- -- -- 10 -- 7 RF-2 20 A 3 12 -- 12 0.43 0.79 0.79 0.47 12 -- 12 3 20 A RF-1 8 -- 5 -- -- -- -- -- -- -- 0.6 3.72 -- -- -- -- -- -- -- 6 -- -- 3 -- -- -- -- -- -- -- 0.6 3.72 -- -- -- -- -- -- -- 4 -- 1 AHU-1 20 A 3 12 -- 12 0.41 0.6 3.72 0.6 10 -- 8 3 40 A DOAS-1 2 K
E
Y
CKT
NO. LOAD DESCRIPTION
OCPD
AMPS P
WIRE
SIZE
H N G
VD
%
A B C VD
%
WIRE
SIZE
G N H
OCPD
P AMPS LOAD DESCRIPTION
CKT
NO.
K
E
Y
NOTES:
ISC: 27.29 kA
SCCR: 42 kA
LOCATION: MECHANICAL 001 WIRE: 4
FED FROM: 225 A/3P @ SB-MAIN GROUND BUS PHASE: 3
ENCLOSURE: NEMA 1 SOLID NEUTRAL VOLTS: 120/208 Wye
MOUNTING: SURFACE SINGLE TUB MAIN: 225 A MCB
PANEL M1
GENERAL NOTES:
1. CONTRACTOR SHALL PROVIDE COMPLETE, TYPED AS-BUILT PANEL DIRECTORIES IN
EACH PANEL WITHIN THE MANUFACTURER- PROVIDED DIRECTORY HOLDER AS REQUIRED THAT DISTINGUISH EACH CIRCUIT PER NEC ART. 408.1 AND 408.4.
HANDWRITTEN DIRECTORIES ARE UNACCEPTABLE. COMPLETED DIRECTORIES
SHALL BE SUBMITTED TO THE ELECTRICAL INSPECTOR PRIOR TO FINAL ELECTRICAL INSPECTION.
ADDENDUM C 11/01/2024
ADDENDUM D 12/09/2024
KEYNOTES:
1. SWITCHBOARD 'SB-MAIN' TO BE PRE-PURCHASED BY THE OWNER AND INSTALLED BY THE ELECTRICAL CONTRACTOR.
2. PROVIDE AND INSTALL LOCKOUT AND TAG FOR CIRCUIT BREAKER. #
1 2
D
D
CIRCUIT KEY NOTES: G - PROVIDE GFCI CIRCUIT BREAKER
F - PROVIDE 'LOCK-ON' DEVICE TO BREAKER AND RED LABEL INDICATING 'FIRE ALARM' TO CIRCUIT ID *TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
TOTAL ESTIMATED DEMAND AMPS: 43.6 A
TOTAL CONNECTED AMPS: 51.92 A
TOTAL ESTIMATED DEMAND LOAD: 15.702 kVA
Receptacles 16.004 kVA 81.24% 13.002 kVA TOTAL CONNECTED LOAD: 18.70 kVA Power 2.7 kVA 100.00% 2.7 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND TOTALS*
LOAD SUMMARY
Total Amps: 52.47 53.61 51.67
Total Load: 6.28 kVA 6.42 kVA 6.20 kVA
-- 41 SPACE -- 1 -- -- -- -- -- -- -- -- 1 -- SPACE 42 -- 39 ECM (HEAT TRACE) 15 A 1 12 12 12 0.12 0.2 -- -- -- -- 1 -- SPACE 40 -- 37 LIGHTING CONTROLLER 20 A 1 12 12 12 0.56 0.5 0.36 0.45 12 12 12 1 20 A DED. MECHOSHADE CONTROLLER 38 35 122, 125 RECEPTACLES 20 A 1 12 12 12 0.56 0.54 0.2 12 12 12 1 20 A FACP 36 F 33 125 RECEPTACLES 20 A 1 12 12 12 0.27 0.72 0.72 0.48 12 12 12 1 20 A 121, 123, 169 RECEPTACLES 34 31 124, 125 RCPT 20 A 1 12 12 12 0.3 0.36 0.72 0.83 12 12 12 1 20 A 119 RECEPTACLES 32 29 121 RECEPTACLES 20 A 1 12 12 12 0.36 0.54 0.72 1.27 12 12 12 1 20 A BASEMENT RECEPTACLES 30 27 113 RECEPTACLES 20 A 1 12 12 12 1.18 0.36 0.54 1.27 12 12 12 1 20 A 118 RECEPTACLES 28 25 112 RECEPTACLES 20 A 1 12 12 12 1.37 0.36 0.54 1.45 12 12 12 1 20 A 117 RECEPTACLES 26 23 117, OUTDOOR RECEPTACLES 20 A 1 12 12 12 2.02 0.72 0.36 0.91 12 12 12 1 20 A 115 RECEPTACLES 24 21 118 RECEPTACLES 20 A 1 12 12 12 0.72 0.36 0.36 0.64 12 12 12 1 20 A 116, 118 RECEPTACLES 22 19 118, OUTDOOR RECEPTACLES 20 A 1 12 12 12 0.65 0.54 0.36 1 12 12 12 1 20 A 116 RECEPTACLES 20 17 ACCESS CONTROL PANEL 20 A 1 12 12 12 0.16 0.18 0.36 0.43 12 12 12 1 20 A 118 RECEPTACLES 18 -- 15 -- -- -- -- -- -- -- 0 0.18 0.17 12 12 12 1 20 A ACCESS CONTROL PANEL 16 13 FOUR POST CABINET 30 A 2 10 -- 10 0 0.18 0.16 12 12 12 1 20 A 121 RECEPTACLES 14 G 11 REFRIGERATOR 20 A 1 12 12 12 1.34 1.5 0 -- -- -- -- -- -- -- 12 -- 9 122, 125 RECEPTACLES 20 A 1 12 12 12 1.8 1.44 0 10 -- 10 2 30 A FOUR POST CABINET 10 7 115, 116 RECEPTACLES 20 A 1 12 12 12 2.11 0.72 0.9 0.68 12 12 12 1 20 A 125 RECEPTACLES 8 5 116 RECEPTACLES 20 A 1 12 12 12 0.8 0.54 0.54 1.18 12 12 12 1 20 A 116 RECEPTACLES 6 3 HAND DRYER 15 A 1 12 12 12 0.24 1 0.54 0.67 12 12 12 1 20 A 116 RECEPTACLES 4 1 STAFF RR 123 SENSORS 15 A 1 12 12 12 0.01 0.02 0.72 1.93 12 12 12 1 20 A 115 RECEPTACLES 2 K
E
Y
CKT
NO. LOAD DESCRIPTION
OCPD
AMPS P
WIRE
SIZE
H N G
VD
%
A B C VD
%
WIRE
SIZE
G N H
OCPD
P AMPS LOAD DESCRIPTION
CKT
NO.
K
E
Y
NOTES:
ISC: 18.69 kA
SCCR: 22 kA
LOCATION: IT 124 WIRE: 4
FED FROM: 225 A/3P @ SB-MAIN GROUND BUS PHASE: 3
ENCLOSURE: NEMA 1 SOLID NEUTRAL VOLTS: 120/208 Wye
MOUNTING: RECESSED SINGLE TUB MAIN: 225 A MCB
PANEL B
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
E0.4-2
PANEL SCHEDULES
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
CIRCUIT KEY NOTES:
*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
TOTAL ESTIMATED DEMAND AMPS: 31.3 A
TOTAL CONNECTED AMPS: 31.26 A
TOTAL ESTIMATED DEMAND LOAD: 11.261 kVA
TOTAL CONNECTED LOAD: 11.26 kVA
Lighting 11.261 kVA 100.00% 11.261 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND TOTALS*
LOAD SUMMARY
Total Amps: 36.47 31.66 26.96
Total Load: 4.30 kVA 3.72 kVA 3.24 kVA
-- 41 SPACE -- 1 -- -- -- -- -- -- -- -- 1 -- SPACE 42 -- -- 39 SPACE -- 1 -- -- -- -- -- -- -- -- 1 -- SPACE 40 -- -- 37 SPACE -- 1 -- -- -- -- -- -- -- -- 1 -- SPACE 38 -- -- 35 SPACE -- 1 -- -- -- -- -- -- -- -- 1 -- SPACE 36 -- -- 33 SPACE -- 1 -- -- -- -- -- -- -- -- 1 -- SPACE 34 -- -- 31 SPACE -- 1 -- -- -- -- -- -- -- -- 1 -- SPACE 32 -- -- 29 SPACE -- 1 -- -- -- -- -- -- -- -- 1 -- SPACE 30 -- -- 27 SPACE -- 1 -- -- -- -- -- -- -- -- 1 -- SPACE 28 -- -- 25 SPACE -- 1 -- -- -- -- -- -- -- -- 1 -- SPACE 26 -- -- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 -- 21 116 LIGHTING 20 A 1 10 10 12 1.14 0.87 0 -- -- -- 1 20 A SPARE 22 -- 19 116 LIGHTING 20 A 1 10 10 12 1.13 0.87 0.87 1.2 12 10 10 1 20 A 116 LIGHTING 20 17 001 LIGHTING 20 A 1 12 12 12 1.79 1.09 1.09 1.3 12 12 12 1 20 A 001 LIGHTING 18 15 119, 121, 125 LIGHTING 20 A 1 12 12 12 1 0.58 0.87 1.2 12 10 10 1 20 A 116 LIGHTING 16 13 124, 125, 169 LIGHTING 20 A 1 12 12 12 1.51 0.74 0.84 1.67 12 12 12 1 20 A 116 LIGHTING 14 11 103, 104, 105 LIGHTING 20 A 1 12 12 12 1.14 0.28 0.45 0.81 12 12 12 1 20 A 122, 125 LIGHTING 12 9 102 LIGHTING 20 A 1 12 12 12 1.53 0.35 0.61 2.19 10 10 10 1 20 A 112 LIGHTING 10 7 107, 108, 109, 110 LIGHTING 20 A 1 12 12 12 1.08 0.27 0.38 1.55 12 12 12 1 20 A 105, 106 LIGHTING 8 5 EXTERIOR LIGHTING 20 A 1 12 12 12 0.44 0.1 0.21 0.57 12 12 12 1 20 A 101, 102 LIGHTING 6 3 112, 115, 116 LIGHTING 20 A 1 12 12 12 0.61 0.21 0.23 1.1 12 12 12 1 20 A 113, 114, 115, 117 LIGHTING 4 1 115, 116, 118 LIGHTING 20 A 1 12 12 12 1 0.16 0.17 1.04 12 12 12 1 20 A EXTERIOR LIGHTING 2 K
E
Y
CKT
NO. LOAD DESCRIPTION
OCPD
AMPS P
WIRE
SIZE
H N G
VD
%
A B C VD
%
WIRE
SIZE
G N H
OCPD
P AMPS LOAD DESCRIPTION
CKT
NO.
K
E
Y
NOTES:
ISC: 8.41 kA
SCCR: 10 kA
LOCATION: STAFF BREAKROOM 121 WIRE: 4
FED FROM: 100 A/3P @ SB-MAIN GROUND BUS PHASE: 3
ENCLOSURE: NEMA 1 SOLID NEUTRAL VOLTS: 120/208 Wye
MOUNTING: RECESSED SINGLE TUB MAIN: 100 A MCB
PANEL C
GENERAL NOTES:
1. CONTRACTOR SHALL PROVIDE COMPLETE, TYPED AS-BUILT PANEL DIRECTORIES IN
EACH PANEL WITHIN THE MANUFACTURER- PROVIDED DIRECTORY HOLDER AS REQUIRED THAT DISTINGUISH EACH CIRCUIT PER NEC ART. 408.1 AND 408.4.
HANDWRITTEN DIRECTORIES ARE UNACCEPTABLE. COMPLETED DIRECTORIES
SHALL BE SUBMITTED TO THE ELECTRICAL INSPECTOR PRIOR TO FINAL ELECTRICAL INSPECTION.
ADDENDUM C 11/01/2024
1 KEYNOTES:
1. PROVIDE AND INSTALL LOCKOUT AND TAG FOR CIRCUIT BREAKER. #
UP
UP
24TH STREET
24TH STREET BYPASS
2101
0643
2102
E1.1-3
2 FOR ENLARGED
PLAN, REFER TO
E1.1-3
1 PANEL B
PANEL C
PANEL A
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
E1.1-1
OVERALL SITE
PLAN - ELECTRICAL
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
N O R
H T
1 1/16" = 1'-0"
OVERALL SITE PLAN - ELECTRICAL
GENERAL NOTES:
KEYNOTES: #
1. CONTRACTOR TO VERIFY ALL EXISTING WIRES, CONDUITS, CIRCUITS, CONNECTIONS AND TERMINATIONS ON SITE.
2. REFER TO DISCONNECT SWITCH SCHEDULE, SINGLE-LINE DIAGRAM, ELECTRICAL CONNECTION SCHEDULE AND PANEL SCHEDULE FOR SIZES, FUSES, FEEDERS, ETC.
3. REFER TO SHEET E1.1-2 FOR ENLARGED EQUIPMENT YARD PLAN.
ADDENDUM C 11/01/2024
UP
E
E
E
E
E
OU-1B
SB-MAIN-7
OU-1A
SB-MAIN-6
CU-2
SB-MAIN-9
CU-1
SB-MAIN-8
CU-3
SB-MAIN-10
FDS-CU-1
60A
FDS-OU-1A
200A
FDS-OU-1B
200A
FDS-CU-2
200A
FDS-CU-3
30A
1 1
3 EXISTING SMUD
TRANSFORMER
TO REMAIN
NEW PULL
SECTION
NEW MAIN
BREAKER AND
METER SECTION
NEW DISTRIBUTION
SECTION
NEW CONCRETE
PAD
4 2
W
SB-MAIN-11
W
SB-MAIN-11
1 1
5 MAIN SWITCHBOARD "SB-MAIN"
6 EXISTING SMUD
TRANSFORMER
TO REMAIN
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
E1.1-3
EQUIPMENT YARD
PLAN - ELECTRICAL
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
N O
PROJECT #23008651.00
R
H T
2 3/16" = 1'-0"
EQUIPMENT YARD REMODEL PLAN - ELECTRICAL
GENERAL NOTES:
KEYNOTES: #
1. CONTRACTOR TO VERIFY ALL EXISTING WIRES, CONDUITS, CIRCUITS, CONNECTIONS AND TERMINATIONS ON SITE.
2. REFER TO DISCONNECT SWITCH SCHEDULE, SINGLE-LINE DIAGRAM, ELECTRICAL CONNECTION SCHEDULE AND PANEL SCHEDULE FOR SIZES, FUSES, FEEDERS, ETC.
1. PROVIDE AND INSTALL NEW NEMA 3R DISCONNECT SWITCH MOUNTED ON UNISTRUT STAND. REFER TO DETAIL 4/E5.0-3 FOR MOUNTING INFORMATION. REFER TO DISCONNECT SWITCH SCHEDULE ON SHEET E4.0-3 FOR DISCONNECT SWITCH AND CIRCUITING INFORMATION.
2. LOCATION OF NEW MAIN METER PANEL, MAIN BREAKER AND PULL SECTION ON 6" CONCRETE PAD.
3. PROVIDE AND INSTALL NEW MAIN SWITCHBOARD ON 6" CONCRETE PAD. REFER TO REMODEL SINGLE LINE DIAGRAM ON E4.0-2 AND STRUCTURAL DRAWINGS FOR MOUNTING DETAILS.
4. INSTALL NEW UNDERGROUND SECONDARY FEEDERS(3) SETS OF 4#500 IN 4" C TO SMUD TRANSFORMER IN A DUCT BANK. REFER TO REMODEL SINGLE LINE DIAGRAM ON E4.0-2 AND DETAIL 5/E5.0-3.
5. COORDINATE WITH THE UTILITY COMPANY FOR POWER SHUTDOWN AND WIRE TERMINATIONS.
6. PROVIDE GROUND ROD AND WELL FOR NEW SWITCHBOARD. REFER TO DETAIL 2/E5.0-2.
N O R
H T
1 3/16" = 1'-0"
EQUIPMENT YARD DEMOLITION PLAN - ELECTRICAL
ADDENDUM C 11/01/2024
PLAN CHECK
COMMENTS
11/01/2024
JJ
J J
J
J
J
J
1 A
2 B
C
E
5 F
3 D
PANEL-C-(R)
PANEL-A-(R)
PANEL-B-(R)
WP
WP
WP
WP
W
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
E2.0-3
FIRST FLOOR
DEMOLITION PLAN
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
N O R
H T
1 1/8" = 1'-0"
FIRST FLOOR DEMOLITION PLAN
GENERAL NOTES:
1. CONTRACTOR TO VERIFY ALL EXISTING WIRES, CONDUITS, CIRCUITS, CONNECTIONS AND TERMINATIONS ON SITE.
2. DISCONNECT AND REMOVE ALL EXISTING ELECTRICAL DEVICES INCLUDING BUT
NOT LIMITED TO PANELBOARDS, DISCONNECT SWITCHES, RECEPTACLES, FLOOR
BOXES, EQUIPMENT CONNECTIONS TO MECHANICAL EQUIPMENT, LIGHT FIXTURES, CONTROLLERS, CONDUITS AND WIRES.
ADDENDUM C 11/01/2024
J J
M
1 A
2 B
C
E
5 F
3 D
MAIN SWITCHBOARD-(R)
MOTOR STARTER PANELBOARD-MSP-(R)
SMART METER-(R)
FIRE ALARM MASTER-(R)
REFER TO FIRE ALARM
SHEETS
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
E2.0-4
BASEMENT
DEMOLITION PLAN
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
N O R
H T
1 1/8" = 1'-0"
BASEMENT DEMOLITION PLAN
GENERAL NOTES:
1. CONTRACTOR TO VERIFY ALL EXISTING WIRES, CONDUITS, CIRCUITS, CONNECTIONS AND TERMINATIONS ON SITE.
2. DISCONNECT AND REMOVE ALL EXISTING ELECTRICAL DEVICES INCLUDING BUT NOT
LIMITED TO PANELBOARDS, DISCONNECT SWITCHES, RECEPTACLES, FLOOR BOXES,
EQUIPMENT CONNECTIONS TO MECHANICAL EQUIPMENT, LIGHT FIXTURES, CONTROLLERS, CONDUITS AND WIRES.
ADDENDUM C 11/01/2024
{LC2}
{LC1}
{LC1D}
{LC1D}
{LC1D}
{LC1}
{LS1}
{LC1} {LD1}
{LS1}
{LC1}
{LS2}
{LD1}
LCS
4B
4B
4B
{LC2}
{LC2}
{LC2}
{LD1}
{LS1} {LS1}
{LD1}
{LS1}
{LC1}
{LC1D}
{LD1}
{LD1}
{LC1D}
1B
1B
1B
O2
{LS2}
1B
1B
1B
1B DO
DO
DO
{LC1}
{LC1}
{LSE1} {LSE1}
{LSE1}
{LSE1}
{LSE1}
{LSE1}
{LSE1}
{LSE1}
{LSE1}
{LSE1}
{LC2}
{LC1}
{LC1D}
{LC1D}
{LC1D}
{LC1}
{LS1}
{LC1} {LD1}
{LS1}
{LC1}
{LS2}
{LD1}
LCS
OC
4B
OCOC
4B
4B
{LC2}
{LC2}
{LC2}
{LD1}
{LS1} {LS1}
{LD1}
{LS1}
{LC1}
{LC1D}
{LD1}
{LD1}
{LC1D}
1B
1B
1B
O2
{LS2}
OC
OC
OC
1B
1B
1B
1B DO
DO
DO
{LC1}
{LR1}
{LC1}
OC
{LSE1}
OC
OC
OC
{LSE1}
{LSE1}
{LSE1}
{LSE1}
{LSE1}
{LSE1}
{LSE1}
{LSE1}
{LSE1}
1 A
2 B
C
E
5 F
3 D
GROUP STUDY
117
CHILDREN
112
TEEN
115
MARKETPLACE
116
ADULT
118
STAFF WORKROOM
125
STUDY
114
STUDY
113
IT
124
STAFF BREAKROOM
121
AMH/SORTING
122
STAFF RR
123
OFFICE
119
FOL
112
COMMUNITY MEETING
102
THE STUDIO
110
PATIO
10 ENTRY
101
STORAGE
104
FAMILY RESTROOM
109
WELLNESS
108
PATIO
46 ALL GENDER RESTROOM
105
HALL
106
KITCHENETTE
103
JANITOR
107
STAIR TO BASEMENT
002
O
O O D
D D
PANEL C
PANEL B
L15A/C-4/zs01
L15B/C-4/zs03
L10/C-10/zc01
L10/C-10/zc01
L10/C-10/zc01
L10/C-10/zc01
L10/C-10/zc01
L11/C-10/zc02
L12E/C-10/zc02 L13/C-10/zc02
L12E/C-10/zc02
L13/C-10/zc02 L13/C-10/zc02
L11/C-10/zc02 L12E/C-10/zc02
L11/C-10/zc02
L13/C-10/zc02
L12E/C-10/zc02
L13/C-10/zc02
L12E/C-10/zc02
L11/C-10/zc02
L11/C-10/zc02
L11/C-10/zc02
L14E/C-3/zb02
L14/C-3/zb02
L14/C-3/zb02
L14E/C-3/zb02
L14/C-3/zb02
L14E/C-1/zb02
L14/C-1/zb02
L14/C-1/zb02
L14/C-1/zb02
L1A/C-1/zb04
L14/C-3/zb02
L14/C-3/zb02
L14E/C-3/zb02
L14E/C-1/zb02
L16/C-14/zb05
L16/C-14/zb05
L16/C-16/zb01
L16/C-21/zb01
L5/C-15
F2/C-15
F1/C-12
F3/C-13
L1/C-6/za01
L6/C-6
L1E/C-9
L1/C-9 L1E/C-9
L9/C-9
L8/C-9
L7/C-9
L8/C-9
L7/C-9
L9/C-9
L4E/C-11/zk01
F3A/C-11
L5/C-11/zk03
L3/C-11
L1A/C-8
L3/C-8
L1A/C-8/za02
L3/C-7
L3/C-7
F3A/C-7
F3A/C-13
L2/C-13
L1A/C-4/zb04
L1A/C-4/zb04
L1AE/C-4/zb04
L18/C-3/zb07/zb08
L19
L19
L19
L22/C-1/zb06
L20/C-1/zb06
L22/C-1/zb06
L23/C-1/zb06
L20/C-1/zb06
L23/C-1/zb06
L20/C-1/zb06
F3E/C-13
L17A/C-4/zb03
L15B/C-4/zs02
L15A/C-7/zs04 L15AE/C L15AE -7/zs04
F1/C-15 F1/C-15
F1E/C-15 F1/C-15
F1E/C-15 F1/C-15
L4/C-8/zr01
O
L2/C-9
D
D
D
L1E/C-13
O
O
L17A/C-4/zb03
L17A/C-4/zb03
L1E/C-6/za01
TYPICAL NONLIT
SUSPENDED
ACOUSTIC
CLOUD AT
TEEN AREA.
L10E/C-10/zc01
L10E/C-10/zc01
L10E/C-10/zc01
L10E/C-10/zc01
L1AE/C-8/za02
L4/C-8/zr01
L1/C-9 L1/C-9
F1/C-15
E1/C-2/ze01
E1/C-2/ze01
E1E/C-2/ze01
E1/C-2/ze01
E1/C-2/ze01
E1/C-5/ze01
E1/C-2/ze01
E1/C-5/ze01
E1/C-5/ze01
E1/C-5/ze01 E1/C-5/ze01 E1/C-5/ze01 E1/C-5/ze01
E1/C-5/ze01
E1/C-2/ze01
E1/C-2/ze01
E2E/C-2/ze02
E1/C-2/ze01
E1/C-2/ze01
E1/C-2/ze01
E1/C-2/ze01 E1E/C-2/ze01
E1/C-2/ze01
E1/C-2/ze01
E2E/C-5/ze02
E2E/C-5/ze02
L21/C-3
EX#/C-7
PRIMARY DAYLIGHT ZONE NORTH
PRIMARY
DAYLIGHT
ZONE WEST
PRIMARY DAYLIGHT ZONE SOUTH
PRIMARY DAYLIGHT
ZONE EAST
SECONDARY DAYLIGHT ZONE
EX#/C-4
EX#/C-8
EX#/C-6
EX#/C-6
EX#/C-10
EX#/C-9
COORDINATE
LOCATION OF
LIGHTING
CONTROL
GATEWAY/HUB
WITHIN I.T
CLOSET.
PROVIDE
RECEPTACLE
FOR POWER AS
NEEDED.
L1/C-9 L1/C-9 L1/C-9
F2/C-12 F2/C-12
L1E/C-7
L1E/C-7
U
L14E/C-1/zb02 L14E/C-1/zb04
L14/C-1/zb02
L14E/C-3/zb02
L14/C-3/zb02
PANEL A
B-37
L1AE/C-1/zb04 L1AE/C-1/zb04
F2E/C-15
F2/C-15
F1E/C-12
F1E/C-15
L1A/C-8 L1AE/C-8
L14/C-3/zb02
L14/C-3/zb02
L1/C-9 L1/C-9
L1E/C-9
L4/C-11/zk02
D
D
D
F1E/C-12
D
1. REFER TO LIGHTING SEQUENCE OF OPERATIONS AS WELL AS SPECIFICATION SECTION 26 09 33 FOR CONTROL INFORMATION AND REQUIREMENTS.
2. STANDARD LIGHTING CONTROL START-UP SERVICES SHALL INCLUDE PRE-WIRE
SITE VISIT, ON-SITE PROGRAMMING, TESTING, TRAINING, COMMISSIONING, AND SCENE SETTINGS.
3. WHERE LUMINAIRE QUANTITIES OR LAYOUT DIFFER BETWEEN ELECTRICAL
LIGHTING PLANS AND ARCHITECTURAL REFLECTED CEILING PLANS, HIGHER QUANTITY SHALL TAKE PRECEDENCE. CONTRACTOR SHALL CONFIRM QUANTITY AND LAYOUT WITH DESIGN TEAM.
4. VACANCY/OCCUPANCY SENSOR LAYOUT: SENSORS ARE SHOWN ON THE PLANS FOR DESIGN INTENT AND MAY NOT REPRESENT EVERY DEVICE. PROVIDE
MANUFACTURER SPECIFIC FLOOR PLAN LAYOUTS SHOWING LOCATION,
ORIENTATION, AND COVERAGE AREA OF EACH CONTROL DEVICE, SENSOR, AND CONTROLLER/INTERFACE. AREAS REQUIRING MULTIPLE SENSOR DEVICES FOR
APPROPRIATE COVERAGE, SUBMIT SPECIFIC MANUFACTURER-APPROVED SENSOR
LAYOUT AS AN OVERLAY DIRECTLY ON THE PROJECT DRAWINGS, EITHER IN PRINT OR APPROVED ELECTRONIC FORM.
5. COORDINATE DISTRIBUTED LIGHTING CONTROL DEVICE LOCATIONS WITH ACCESSIBLE CEILINGS. VIF WITH ARCHITECT PRIOR TO ROUGH IN. NOT ALL ACT CEILINGS ARE ACCESSIBLE.
LIGHTING GENERAL NOTES:
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
E2.4-1
FIRST FLOOR
REMODEL PLAN -
LIGHTING
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
N O R
H T
1 1/8" = 1'-0"
FIRST FLOOR REMODEL PLAN - LIGHTING
ADDENDUM C 11/01/2024
PLAN CHECK
COMMENTS
11/01/2024
KEYNOTES: #
1. SUSPEND LIGHTS AT 11 FEET TO THE BOTTOM.
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
{LS2}
{LS3}
OC
1 A
2 B
C
E
5 F
3 D
MECHANICAL
001
PANEL M1
F3A/C-13 F3E/C-13
F3E/C-17
F3/C-18
F3E/C-18
F3/C-17
F3/C-17
2 2
2 1 U
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
E2.4-2
BASEMENT
REMODEL PLAN -
LIGHTING
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
N O R
H T
1 1/8" = 1'-0"
BASEMENT REMODEL PLAN - LIGHTING
PLAN CHECK
COMMENTS
11/01/2024
KEYNOTES: #
1. MOUNT LIGHTS AT 8 FEET TO THE BOTTOM.
2. SUSPEND LIGHTS AT 9 FEET TO THE BOTTOM
E
E
EE
E
E
E E
E
E
E E E E E
E
E
E
E
E
E
E
E
E
E
E
E
E E
EE
E
E
E
E
1 A
2 B
C
E
5 F
3 D
GROUP STUDY
117
CHILDREN
112
TEEN
115
MARKETPLACE
116
ADULT
118
STAFF WORKROOM
125
STUDY
114
STUDY
113
IT
124
STAFF BREAKROOM
121
AMH/SORTING
122
STAFF RR
123
OFFICE
119
FOL
112
COMMUNITY MEETING
102
THE STUDIO
110
PATIO
10 ENTRY
101
STORAGE
104
FAMILY RESTROOM
109
WELLNESS
108
PATIO
46 ALL GENDER RESTROOM
105
HALL
106
KITCHENETTE
103
JANITOR
107
STAIR TO BASEMENT
002
STORAGE
104
ALL GENDER RESTROOM
105
ALL GENDER RESTROOM
105
PANEL A
PANEL C
PANEL B
FC-1-8
M1-13,15
MX-FC-1-8
20A
HD
A-32
HD
A-30
2 3
3 NEW PULL SECTION NEW MAIN BREAKER AND
METER SECTION
NEW DISTRIBUTION SECTION
NEW CONCRETE
PAD
B-36
FAB
A-7
4 5
1 HD
A-28
DF-1
A-1
WC-2
A-5
WC-2
A-5
WC-2
A-5
WC-2
A-5
SK-1
A-5
WC-1
A-5
WC-2
A-5
HD
B-3
FC-1-13
M1-14,16
MX-FC-1-13
20A
FACP/VECP
FADC
FATC-1
AMP-1
MS-5
A-8 MS-5
A-8
MS-2
A-8
MS-2
A-8
MS-2
A-8
MS-3
A-8
MS-1
A-8
7 7
7 7
7 7
7 7
MS-4
A-8
8 FC-1-9
M1-19,21
FC-1-12
M1-23,25
FC-1-11
M1-35,37
FC-1-10
M1-39,41
MS-1 SWITCH
A-8
MS-2 SWITCH
A-8
MS-3 SWITCH
A-8
MS-4 SWITCH
MS-5 SWITCH
A-8
SS-1
M1-47,49
MX-SS-1
20A
MX-FC-1-10
20A
MX-FC-1-11
20A
MX-FC-1-9
20A 9
9 9
9 9
9 9
OVERHEAD DOOR
A-31
6 MX-ECM
ECM
B-39
TP-2
A-33
MX-FC-1-12
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
E2.4-3
FIRST FLOOR
REMODEL PLAN -
POWER
EQUIPMENT
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
N O R
H T
1 1/8" = 1'-0"
FIRST FLOOR REMODEL PLAN - POWER EQUIPMENT
GENERAL NOTES:
KEYNOTES: #
1. REFER TO DISCONNECT SWITCH SCHEDULE, SINGLE-LINE DIAGRAM, ELECTRICAL CONNECTION SCHEDULE AND PANEL SCHEDULE FOR SIZES, FUSES, FEEDERS, ETC.
2. ALL CIRCUIT OR FEEDER WIRING RUN IN A RACEWAY SHALL INCLUDE A SEPARATE WIRE-TYPE EQUIPMENT GROUNDING CONDUCTOR. A METALLIC RACEWAY SHALL NOT SERVE AS THE SOLE EQUIPMENT GROUNDING CONDUCTOR.
3. PER NEC 300.5, ALL UNDERGROUND CONDUITS MUST MEET THE COVER REQUIREMENTS OF THIS TABLE. ALL UNDERGROUND CONDUIT RUNS MUST BE INSPECTED PRIOR TO BURIAL.
4. REFER TO 3/E5.0-1 FOR CONDUIT PENETRATION DETAIL.
5. REFER TO 2/E5.0-1 FOR CONDUIT FIRE BARRIER PENETRATION DETAIL.
6. REFER TO ABBREVIATIONS KEY ON THE ELECTRICAL COVERSHEET, SHEET E0.0.
7. REFER TO MECHANICAL AND PLUMBING SCHEDULES FOR EQUIPMENT RATINGS.
REFER TO ELECTRICAL CONNECTION SCHEDULE FOR ELECTRICAL INFORMATION.
8. DISCONNECT SWITCHES ABOVE CEILING SPACES SHALL BE PROVIDED WITH ACCESS PANELS WHERE GYPSUM BOARD CEILING OCCURS.
1. LOW VOLTAGE TRANSFORMER FOR SOAP DISPENSERS, PAPER TOWEL
DISPENSERS, WATER CLOSETS AND FAUCETS TO BE PROVIDED BY PLUMBING CONTRACTOR. ELECTRICAL CONTRACTOR TO INSTALL TRANSFORMER(S) BEHIND PLUMBING CHASE OR ABOVE ACCESSIBLE CEILING AND HARDWIRE 120V CONNECTIONS AS REQUIRED. ELECTRICAL CONTRACTOR TO EXTEND LOW VOLTAGE CONNECTIONS TO INDIVIDUAL SENSORS. COORDINATE INSTALLATION AND QUANTITY OF SENSORS WITH PLUMBING CONTRACTOR PRIOR TO INSTALLATION.
REFER TO 4/E5.0-2 FOR WIRING DETAILS.
2. PROVIDE POWER FOR NEW BOTTLE FILLER, REFER TO PANEL SCHEDULES FOR CIRCUITING INFORMATION.
3. PROVIDE AND INSTALL RECESS MOUNTED PANELBOARD. REFER TO PANEL SCHEDULES AND SINGLE LINE DIAGRAM FOR PANEL SIZE. REFER TO DETAIL 5/E5.0-1 AND 2/E5.0-3 FOR MOUNTING INFORMATION. REFER TO ARCHITECTURAL DRAWINGS FOR WALL TYPE.
4. PROVIDE DEDICATED CIRCUIT FOR ELECTRIC FIRE ALARM BELL. PROVIDE 'LOCK-ON'
DEVICE TO CIRCUIT BREAKER AND RED LABEL INDICATING 'FIRE ALARM' TO CIRCUIT ID. COORDINATE WITH FIRE PROTECTION CONTRACTOR FOR ELEVATION AND FINAL CONNECTIONS.
5. PROVIDE DEDICATED CIRCUIT FOR FIRE ALARM PANEL. PROVIDE 'LOCK-ON' DEVICE TO CIRCUIT BREAKER AND RED LABEL INDICATING 'FIRE ALARM' TO CIRCUIT ID.
6. PROVIDE POWER FOR NEW HEAT TRACE ELECTRONIC CONTROL MODULE (ECM).
REFER TO ELECTRICAL CONNECTION SCHEDULE FOR ELECTRICAL INFORMATION.
PROVIDE AND INSTALL NEW MANUAL SWITCH FOR THE ECM, REFER TO DISCONNECT AND STARTER SCHEDULE ON SHEET E4.0-3 FOR ELECTRICAL INFORMATION. REFER TO SHEET FP2.4-1 FOR HEAT TRACE LOCATION. TO PROVIDE POWER TO HEAT TRACE ELEMENT; COORDINATE WITH FIRE PROTECTION CONTRACTOR FOR INTERNAL WIRING AND TERMINATIONS.
7. PROVIDE POWER FOR THE NEW MECHOSHADES, ENSURING THE SHADE CONTROL SWITCHES ARE GANGED WITH THE EXISTING LIGHT SWITCHES IN EACH ROOM.
REFER TO THE PRODUCT SPECIFICATIONS FOR FINAL CONNECTION DETAILS AND COORDINATE THE LOCATIONS WITH THE ARCHITECTURAL DRAWINGS.
8. PROVIDE NEW CONCRETE PAD FOR SWITCHBOARD, REFER TO STRUCTURAL DRAWINGS FOR MOUNTING DETAILS.
9. PROVIDE AND INSTALL NEW MANUAL SWITCH ABOVE CEILING FOR FC-1-8, 9, 10, 11, 12, 13 AND SS-1. COORDINATE WITH MECHANICAL CONTRACTOR FOR EXACT MOUNTING LOCATION. REFER TO DISCONNECT SWITCH AND ELECTRICAL CONNECTION SCHEDULES ON SHEET E4.0-3 FOR CIRCUITING INFORMATION.
ADDENDUM C 11/01/2024
ADDENDUM D 12/09/2024
D
D
D
D
D
D
E
E
E
E
E E E E
E
E
E
E
E
E
E
E
EE
E
E
E E E E E
E
E
E
1 A
2 B
C
E
5 F
3 D
MECHANICAL
001
PANEL M1
FC-1-4
FC-1-1
FC-1-5
AHU-1
FC-1-6
FC-1-2
FC-1-3
MX-FC-1-3 FDS-AHU-1
FDS-DOAS-1
5 1
1 FC-1-7
WH-1 FDS-WH-1
TCP
2 RF-2
RF-1
VFD-RF-1
VFD-RF-2
DOAS-1
BC-2
MX-BC-1
CP-1
MX-CP-1
MX-BC-2
BC-1
4 MOD-2 MOD-1
COP-2
COP-1
1 MX-FC-1-1
MX-FC-1-7
MX-FC-1-6
MX-FC-1-2
MX-FC-1-5
MX-FC-1-4
5 5
5 5
5 CP FC-1-3
CP FC-1-1
CP FC-1-7
CP FC-1-6
CP FC-1-2
CP FC-1-5
CP FC-1-4
3 6
6 6
6 6
6 SP-1
5 MX-SP-1
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
E2.4-4
BASEMENT
REMODEL PLAN -
POWER
EQUIPMENT
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
N O R
H T
1 1/8" = 1'-0"
BASEMENT REMODEL PLAN - POWER EQUIPMENT
GENERAL NOTES:
KEYNOTES: #
1. REFER TO DISCONNECT SWITCH SCHEDULE, SINGLE-LINE DIAGRAM, ELECTRICAL CONNECTION SCHEDULE AND PANEL SCHEDULE FOR SIZES, FUSES, FEEDERS, ETC.
2. REFER TO 3/E5.0-1 FOR CONDUIT PENETRATION DETAIL.
3. REFER TO 2/E5.0-1 FOR CONDUIT FIRE BARRIER PENETRATION DETAIL.
4. ALL CIRCUIT OR FEEDER WIRING RUN IN A RACEWAY SHALL INCLUDE A SEPARATE WIRE-TYPE EQUIPMENT GROUNDING CONDUCTOR. A METALLIC RACEWAY SHALL NOT SERVE AS THE SOLE EQUIPMENT GROUNDING CONDUCTOR.
5. REFER TO ABBREVIATIONS KEY ON THE ELECTRICAL COVERSHEET, SHEET E0.0.
6. REFER TO MECHANICAL AND PLUMBING SCHEDULES FOR EQUIPMENT RATINGS.
REFER TO ELECTRICAL CONNECTION SCHEDULE FOR ELECTRICAL INFORMATION.
1. PROVIDE AND INSTALL NEW DISCONNECT SWITCH. REFER DISCONNECT SWITCH SCHEDULE ON SHEET E4.0-3 FOR DISCONNECT SWITCH AND CIRCUITING INFORMATION. REFER TO DETAIL 1/E5.0-2 FOR MOUNTING INFORMATION.
2. PROVIDE AND INSTALL NEW SURFACE MOUNTED PANEL. EC SHALL ROUTE
UNDERGROUND CONDUIT FROM SB-MAIN AND TRANSITION IN CEILING SPACE OF BASEMENT. PROVIDE JUNCTION BOX AT TRANSITION. REFER TO PANEL SCHEDULES AND SINGLE LINE DIAGRAM FOR PANEL SIZE. REFER TO DETAIL 1/E5.0-3 FOR MOUNTING INFORMATION.
3. PROVIDE POWER FOR TEMPERATURE CONTROL PANEL. REFER TO ELECTRICAL CONNECTION SCHEDULE ON SHEET E4.0-3 FOR ELECTRICAL INFORMATION.
4. PROVIDE AND INSTALL NEW VARIABLE FREQUENCY DRIVE FOR EACH RETURN FAN UNIT. REFER TO VFD SCHEDULE ON SHEET E4.0-3 FOR VFD AND CIRCUITING INFORMATION. REFER TO DETAIL 1/E5.0-3 FOR MOUNTING INFORMATION.
5. PROVIDE AND INSTALL NEW MANUAL SWITCH FOR EACH FAN COIL UNIT, BRANCH SELECTOR UNIT AND SUMP PUMP. REFER TO DISCONNECT AND STARTER SCHEDULE ON SHEET E4.0-3 FOR ELECTRICAL INFORMATION. REFER TO SECTION 1/M8.0-3 FOR THE LOCATION OF THE MANUAL SWITCHES.
6. PROVIDE POWER TO THE CONTROL PANELS SERVING EACH FAN COIL UNIT. REFER TO ELECTRICAL CONNECTION SCHEDULE ON SHEET E4.0-3 FOR ELECTRICAL INFORMATION. REFER TO SECTION 1/M8.0-3 FOR THE LOCATION OF THE CONTROL PANELS.
ADDENDUM C 11/01/2024
ADDENDUM D 12/09/2024
D
D
D
D
D
D
D
D
D
D
J
1 A
2 B
C
E
5 F
3 D
GROUP STUDY
117
CHILDREN
112
TEEN
115
MARKETPLACE
116
ADULT
118
STAFF WORKROOM
125
STUDY
114
STUDY
113
IT
124
STAFF BREAKROOM
121
AMH/SORTING
122
STAFF RR
123
OFFICE
119
FOL
112
COMMUNITY MEETING
102
THE STUDIO
110
PATIO
10 ENTRY
101
STORAGE
104
FAMILY RESTROOM
109
WELLNESS
108
PATIO
46 ALL GENDER RESTROOM
105
HALL
106
KITCHENETTE
103
JANITOR
107
STAIR TO BASEMENT
002
B-13,15
O
B-9
O
B-9
O
B-35
O
B-9
O
B-9
O
B-35
O
B-35
B-34
O
B-34 O
B-34
O
B-29
O
A
B-29
B-11
O
B-29
O
B-33
O
B-33
O
B-8
O
B-8
O
B-32
O
B-32
O
B-32
O
B-19
O
B-26
O
B-23
O
B-23
+62"AFF
B-26
B-2
O
A-12
+62"AFF
A-16
O
A-16
+62"AFF
A-19
O
A-19
O
A-23
O
A-23
O
A-23
A-6
O
A-6
A-6
W
A-26
W
A-26
W
A-26
A-22
A-22
A-21
A-21
A
A-21
A-4
A-4
A-4
O
A-4
A-22 A-22
A-25 A-25
A-25
O
A-29
O
A-29
O
A-29
+62"AFF
A-24
+62"AFF
A-24
+62"AFF
A-20
O
A-20
A-20
B-34
W
A-29
+90"AFF
A-15 +90"AFF
A-17
A-11
O
A
A-9
B-8
O
A
B-14
O
A
B-27
O
A-9
PT-2
B- 24
PT-2
PT-1
B- 6
PT-1
PT-2
B- 24
PT-2
A-25
PT-1
B- 21
PT-1
PT-1
B- 21
PT-1
PT-2
B- 18
PT-2
PT-2
B- 20
PT-2
PT-2
B- 20
PT-2
PT-2
B- 7
PT-2
PT-2
B- 25
PT-2
PT-2
B- 25
PT-2
PT-2
B- 18
PT-2
PT-2
B- 22
PT-2
PT-1
B- 6
PT-1
PT-1
B- 22
PT-1
PT-1
B- 7
PT-1
PT-1
A- 18
PT-1
PT-1
A- 2
PT-1
PT-1
A- 2
PT-1
PT-1
A- 18
PT-1
PT-1
A- 10
PT-1
PT-2
A- 13
PT-2
B-16
B-31 B-17
PT-1
B- 28
PT-1
PT-2
B- 7
PT-2
PT-1
B- 7
PT-1
PT-1
A- 27
PT-1
PT-1
A- 27
PT-1
+18"AFF
A-14
+62"AFF
B-2
PT-1
A- 18
PT-1
A-6
PT-1
A- 27
PT-1
PT-1
A- 27
PT-1
PT-1
A- 27
PT-1
PT-1
B- 6
PT-1
PT-1
B- 28
PT-1
PT-1
B- 28
PT-1
A-26
PT-1
B- 5
PT-1
PT-1
B- 5
PT-1
PT-1
B- 4
PT-1
O
B-4
(TYP.)
4 2
1 5
3 (TYP.)
B-38 6
W
B-19
W
B-23
L-1
A-5
L-1
A-5
7 7
PT-1
A- 18
PT-1
8 B-9
9 B-37
L-2
A-21
7 O
B-5
O
A-4
O
B-23
L-3
B-1
7 Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
E2.4-5
FIRST FLOOR
REMODEL PLAN -
RECEPTACLES
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
N O R
H T
1 1/8" = 1'-0"
FIRST FLOOR REMODEL PLAN - RECEPTACLES
GENERAL NOTES:
KEYNOTES: #
1. ANY GFCI PROTECTION DEVICE SHOULD BE READILY ACCESSIBLE FOR TEST/RESET FUNCTIONS. IF APPLICABLE, PROVIDE GFCI CIRCUIT BREAKER AT PANEL INSTEAD OF GFCI RECEPTACLE TO MEET THIS REQUIRED.
2. ALL CIRCUIT OR FEEDER WIRING RUN IN A RACEWAY SHALL INCLUDE A SEPARATE WIRE-TYPE EQUIPMENT GROUNDING CONDUCTOR. A METALLIC RACEWAY SHALL NOT SERVE AS THE SOLE EQUIPMENT GROUNDING CONDUCTOR.
3. PER NEC 300.5, ALL UNDERGROUND CONDUITS MUST MEET THE COVER REQUIREMENTS OF THIS TABLE. ALL UNDERGROUND CONDUIT RUNS MUST BE INSPECTED PRIOR TO BURIAL.
4. REFER TO 3/E5.0-1 FOR CONDUIT PENETRATION DETAIL.
5. REFER TO 2/E5.0-1 FOR CONDUIT FIRE BARRIER PENETRATION DETAIL.
6. PER TITLE24, 130.5(D), 50% OF RECEPTACLES ON THE POWER PLANS ARE OCCUPANCY CONTROLLED (TAGGED 'O') IN EACH SPACE. REFER TO 1/E5.0-1 FOR CONTROLLED RECEPTACLE WIRING DETAIL.
7. WHERE POKE THROUGH OUTLETS OCCUR, PROVIDE CONDUIT RUNS AT FLOOR BELOW WITHIN THE CRAWL SPACES.
8. COORDINATE WITH STRUCTURAL ENGINEER FOR THE PROPOSED LOCATIONS OF FLOOR CORING FOR THE POKE THROUGH DEVICE BOXES.
9. COORDINATE WITH ARCHITECT THE DIMENSIONS OF THE FLOOR OUTLETS IN REFERENCE TO WALLS PRIOR TO FLOOR CORING AND ROUGH-INS.
1. PROVIDE TWO L6-30R AT THE FOUR POST CABINET. REFER TO TECHNOLOGY DRAWINGS FOR ELEVATIONS AND MORE DETAILS.
2. PROVIDE TWO DEDICATED RECEPTACLES FOR ACCESS CONTROL PANEL. REFER TO TECHNOLOGY DRAWINGS FOR ELEVATIONS AND MORE DETAILS.
3. PROVIDE POKE THRU METAL FLUSH QUAD RECEPTACLES.
4. PROVIDE POKE THRU METAL FLUSH QUAD RECEPTACLES WITH EMPTY GANG BOXES FOR TECHNOLOGY. REFER TECHNOLOGY PLANS FOR NUMBER OF EMPTY GANGS REQUIRED.
5. PROVIDE DEDICATED RECEPTACLES FOR REFRIGERATOR. PROVIDE GFCI CIRCUIT BREAKER AT PANEL. REFER TO PANEL SCHEDULES FOR CIRCUITING INFORMATION.
6. PROVIDE DEDICATED QUAD RECEPTACLE FOR MECHOSHADE HUB/GATEWAY,
COORDINATE ELEVATIONS AND FINAL LOCATION WITH ARCHITECT/TECHNOLOGY CONTRACTOR.
7. LOW VOLTAGE TRANSFORMER FOR FAUCETS TO BE PROVIDED BY PLUMBING CONTRACTOR. ELECTRICAL CONTRACTOR TO INSTALL NEW RECEPTACLE UNDER THE SINK. COORDINATE INSTALLATION AND LOCATION OF RECEPTACLE WITH PLUMBING CONTRACTOR PRIOR TO INSTALLATION. REFER TO 4/E5.0-2 FOR WIRING DETAILS.
8. PROVIDE POWER TO NEW SURFACE-MOUNTED JUNCTION BOX AT THE WALL FOR RECEPTACLES UNDER THE DESK. COORDINATE THE RECEPTACLE LOCATION AND CONDUIT ROUTING WITH FURNITURE MANUFACTURER.
9. PROVIDE DEDICATED RECEPTACLE FOR NEW LIGHTING CONTROL GATEWAY/HUB WITHIN THE IT CLOSET. REFER TO ELECTRICAL SCHEDULES FOR ELECTRICAL INFORMATION.
ADDENDUM C 11/01/2024
ADDENDUM D 12/09/2024
D
D
1 A
2 B
C
E
5 F
3 D
MECHANICAL
001
B-30
B-30
B-30
B-30
BMS COMPUTER
M1-45
1 PANEL M1
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
E2.4-6
BASEMENT
REMODEL PLAN -
RECEPTACLES
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
N O R
H T
1 1/8" = 1'-0"
BASEMENT REMODEL PLAN - RECEPTACLES
GENERAL NOTES:
KEYNOTES: #
1. REFER TO DISCONNECT SWITCH SCHEDULE, SINGLE-LINE DIAGRAM, ELECTRICAL CONNECTION SCHEDULE AND PANEL SCHEDULE FOR SIZES, FUSES, FEEDERS, ETC.
2. REFER TO 3/E5.0-1 FOR CONDUIT PENETRATION DETAIL.
3. REFER TO 2/E5.0-1 FOR CONDUIT FIRE BARRIER PENETRATION DETAIL.
4. ALL CIRCUIT OR FEEDER WIRING RUN IN A RACEWAY SHALL INCLUDE A SEPARATE WIRE-TYPE EQUIPMENT GROUNDING CONDUCTOR. A METALLIC RACEWAY SHALL NOT SERVE AS THE SOLE EQUIPMENT GROUNDING CONDUCTOR.
1. PROVIDE DEDICATED QUAD RECEPTACLE FOR BMS AND COMPUTER. COORDINATE
WITH TEMPERATURE CONTROLS CONTRACTOR AND TECHNOLOGY CONTRACTOR FOR EXACT LOCATION AND ELEVATIONS.
PLAN CHECK
COMMENTS
11/01/2024
E
E
1 A
2 B
E
5 F
3 D
EF-2
M1-43
EF-1
M1-42
2 W
M1-43
1 W
M1-42
1 2
MX-EF-1
20A
MX-EF-2
20A
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
E2.4-7
LOW ROOF
REMODEL PLAN -
ELECTRICAL
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
N O R
H T
1 1/8" = 1'-0"
LOW ROOF REMODEL PLAN - ELECTRICAL
GENERAL NOTES:
KEYNOTES: #
1. REFER TO DISCONNECT SWITCH SCHEDULE, SINGLE-LINE DIAGRAM, ELECTRICAL CONNECTION SCHEDULE AND PANEL SCHEDULE FOR SIZES, FUSES, FEEDERS, ETC.
2. ALL CIRCUIT OR FEEDER WIRING RUN IN A RACEWAY SHALL INCLUDE A SEPARATE WIRE-TYPE EQUIPMENT GROUNDING CONDUCTOR. A METALLIC RACEWAY SHALL NOT SERVE AS THE SOLE EQUIPMENT GROUNDING CONDUCTOR.
3. PER NEC 300.5, ALL UNDERGROUND CONDUITS MUST MEET THE COVER REQUIREMENTS OF THIS TABLE. ALL UNDERGROUND CONDUIT RUNS MUST BE INSPECTED PRIOR TO BURIAL.
4. REFER TO 3/E5.0-1 FOR CONDUIT PENETRATION DETAIL.
5. REFER TO 2/E5.0-1 FOR CONDUIT FIRE BARRIER PENETRATION DETAIL.
6. REFER TO ABBREVIATIONS KEY ON THE ELECTRICAL COVERSHEET, SHEET E0.0.
7. REFER TO MECHANICAL AND PLUMBING SCHEDULES FOR EQUIPMENT RATINGS.
REFER TO ELECTRICAL CONNECTION SCHEDULE FOR ELECTRICAL INFORMATION.
8. DISCONNECT SWITCHES ABOVE CEILING SPACES SHALL BE PROVIDED WITH ACCESS PANELS WHERE GYPSUM BOARD CEILING OCCURS.
1. PROVIDE AND INSTALL NEW MANUAL SWITCH FOR NEW FAN, MOUNT ADJACENT TO EXHAUST FAN'S POWER POINT OF CONNECTION ON THE CURB. COORDINATE WITH MECHANICAL DRAWINGS FOR LOCATION AND CONTROLS OF EXHAUST FAN.
PROVIDE 120V, 20A RATED ELECTRICALLY HELD RELAY FOR CONNECTION TO CONTROLS. REFER TO DETAIL 3/E5.0-3 FOR CONTROL RELAY INFORMATION. REFER TO ELECTRICAL AND PANEL SCHEDULES FOR ELECTRICAL INFORMATION.
2. PROVIDE AND INSTALL NEW RECEPTACLE WITH WEATHERPROOF IN-USE COVER.
MOUNT RECEPTACLE ON THE CURB, COORDINATE FINAL LOCATION AND TERMINATIONS WITH MECHANICAL CONTRACTOR. REFER TO PANEL SCHEDULES FOR ELECTRICAL INFORMATION.
ADDENDUM C 11/01/2024
M
120/208V,3Ø4W
225A MCB
A
120/208V,3Ø4W
100A MCB
C
120/208V,3Ø4W
225A MCB
B
120/208V,3Ø4W
225A MCB
MSP
120/208V,3Ø4W
800A MCCB
SB-MAIN
800AT
800AF
4 3 2 1
NEUTRAL
800 AMP BUS
GROUND
UTILITY SMUD SERVICE
C.T. COMPARTMENT AND
METERING PER UTILITY
COMPANY REQUIREMENTS.
150A/3P 100A/3P 150A/3P 225A/3P
8 7 6 5
SPACE EXISTING LOADS
150A/3P 50A/3P
MAIN SWITCHBOARD "SB-MAIN'
800A,120/208V, 3⌀4W
LOCATION: BASEMENT 1
2 EXISTING SMUD
TRANSFORMER TO REMAIN
3 Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
E4.0-1
DEMOLITION
SINGLE LINE
DIAGRAM
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
1 NO SCALE
DEMOLITION SINGLE LINE DIAGRAM
GENERAL NOTES:
1. CONTRACTOR TO VERIFY ALL EXISTING WIRES, CONDUITS, CIRCUITS, CONNECTIONS AND TERMINATIONS ON SITE.
KEY NOTES:
1. DEMOLISH EXISTING SWITCHBOARD "SB-MAIN."
2. CONDUIT TO BE ABANDONED IN PLACE, CUT AND CAP STUBOUTS FLUSH TO FLOOR.
3. UTILITY PRIMARY SERVICE TO REMAIN AND PROTECTED IN PLACE. #
ADDENDUM C 11/01/2024
PLAN CHECK
COMMENTS
11/01/2024
M
120/208V,3Ø4W
800A MCCB
SCCR 65 kA
SB-MAIN
120/208V,3Ø4W
225A MCB
SCCR 42 kA
M1
120/208V,3Ø4W
225A MCB
SCCR 10 kA
A
120/208V,3Ø4W
100A MCB
SCCR 10 kA
C
120/208V,3Ø4W
225A MCB
SCCR 22 kA
B
E
OU-1A
ISC 7.01 kA
31.70 kVA E
OU-1B
ISC 7.40 kA
31.70 kVA E
CU-1
ISC 2.66 kA
13.69 kVA E
CU-2
ISC 8.71 kA
42.87 kVA E
CU-3
ISC 1.15 kA
3.54 kVA
800AT
800AF
DPM
5 4 3 2
C.T.'S
NEUTRAL
800 AMP BUS
GROUND
SECONDARY
FEEDER TO SMUD
TRANSFORMER
C.T. COMPARTMENT AND
METERING PER UTILITY
COMPANY REQUIREMENTS.
4#4/0 & 1#4 EGC IN 2 1/2" C.FROM 225A/3P @ SB-MAIN4#4/0 & 1#4 EGC IN 2 1/2" C.FROM 225A/3P @ SB-MAIN4#3 & 1#8 EGC IN 1 1/4" C.FROM 100A/3P @ SB-MAIN4#4/0 & 1#4 EGC IN 2 1/2" C.FROM 225A/3P @ SB-MAIN 225A/3P 100A/3P 225A/3P 225A/3P
11 SPACE
MAIN SWITCHBOARD "SB-MAIN'
800A,120/208V, 3⌀4W
LOCATION: OUTDOOR
PULL
SECTION
6 150A/3P
7 150A/3P
8 50A/3P
9 200A/3P
10 30A/2P
DISTRIBUTION SECTION
2#10 & 1#10 EGC IN 1" C.FROM 30A/2P3#1/0 & 1#6 EGC IN 1 1/2" C.FROM 200A/3P3#6 & 1#10 EGC IN 1" C.FROM 50A/3P3#1/0 & 1#6 EGC IN 1 1/4" C.FROM 150A/3P3#1/0 & 1#6 EGC IN 1 1/4" C.FROM 150A/3P CT
#3/0 GROUNDING ELECTRODE
CONDUCTOR
#1/0 GROUNDING
ELECTRODE
CONDUCTOR
3/4" DIA. x 10'-0" COPPER
GROUND ROD. TOP OF ROD
SHALL BE 12" BELOW GRADE.
(TYP.). SEE DETAIL 2/E5.0-2 AND
EQUIPMENT YARD PLAN FOR
GROUND WELL AND ROD
LOCATION.
20'-0"
CT CT CT CT CT CT CT CT
20A/1P
SERVICE
RECEPTACLES 2#12 & 1#12 EGC IN 1"C. FROM 20A/1P
1 12
CONNECT TO METALLIC
WATER MAIN, WITHIN
5'-0" OF WATER SERVICE
ENTRANCE
WM
PROVIDE JUMPER
ACROSS WATER METER
EFFECTIVELY
GROUNDED BUILDING
STEEL
EXISTING SMUD
TRANSFORMER
TO REMAIN
2 3
4#10 & 1#10 EGC IN 3/4" C. MAXIMUM 5'-0" LENGTH
SPD
30A/3P
1 INTERSYSTEM BONDING TERMINATION, REFER TO DETAIL
6/TN906 IN TECHNOLOGY DRAWINGS FOR TECHNOLOGY
GROUND BUS BAR. COORDINATE EXACT LOCATION WITH
TECHNOLOGY CONTRACTOR.
IBT
#4 INSULATED COPPER GROUNDING
CONDUCTOR. PER NEC 250.94. MAXIMUM 20'-0"
LENGTH.
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
E4.0-2
REMODEL SINGLE
LINE DIAGRAM
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
GENERAL NOTES:
1. ALL CIRCUIT OR FEEDER WIRING RUN IN A RACEWAY SHALL INCLUDE A SEPARATE WIRE-TYPE EQUIPMENT GROUNDING CONDUCTOR. A METALLIC RACEWAY SHALL NOT SERVE AS THE SOLE EQUIPMENT GROUNDING CONDUCTOR.
2. CONTRACTOR TO PERFORM ELECTRICAL LOAD STUDY, INCLUDING SHORT CIRCUIT
ANALYSIS, VOLTAGE DROP, SELECTIVE COORDINATION, ARC FLASH ASSESSMENT AND APPLY THE ARC FLASH LABELS TO ALL PANELS.
KEYNOTES:
1. SWITCHBOARD 'SB-MAIN' IS PRE-PURCHASED BY OWNER. EC TO INSTALL AND OWNER FURNISHED SWITCHBOARD. ALL OTHER EQUIPMENT INCLUDING BUT NOT
LIMITED TO PANELS, WIRING, CONDUITS, GROUNDING TO BE FURNISHED AND INSTALLED BY EC.
2. PROVIDE AND INSTALL NEW (3) SETS OF 4#500 IN 4" C.
3. UTILITY PRIMARY SERVICE TO REMAIN.
#
1 NO SCALE
REMODEL SINGLE LINE DIAGRAM
ADDENDUM C 11/01/2024
ADDENDUM D 12/09/2024
BACK CHECK 2 12/09/2024
2 D
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
E4.0-3
ELECTRICAL
SCHEDULES
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
VOLTAGE DROP SCHEDULE
ITEM
FEEDER
CIRCUIT
LENGTH
VOLTAGE DROP
UPSTREAM OCPD OR TERMINATION WIRE AND RACEWAY
FEEDERS BRANCH CIRCUITS
FEEDER
VOLTAGE
DROP
UPSTREAM
FEEDERS
VOLTAGE
DROP
TOTAL
FEEDER
VOLTAGE
DROP
MAX
BRANCH
VOLTAGE
DROP
TOTAL
VOLTAGE
DROP AT MAX
BRANCH
SB-MAIN 800 A (2) SETS OF 4#600 & 1#1/0 EGC EACH IN 3 1/2" C. 1.33% ╠►A 225 A 4#4/0 & 1#4 EGC IN 2 1/2" C. 135'-5 7/16" 1.60% 1.60% 9.00% 10.60% ╠►B 225 A 4#4/0 & 1#4 EGC IN 2 1/2" C. 42'-2 9/16" 0.50% 0.50% 2.11% 2.61% ╠►C 100 A 4#3 & 1#8 EGC IN 1 1/4" C. 43'-10 9/16" 0.73% 0.73% 2.19% 2.92% ╚►M1 225 A 4#4/0 & 1#4 EGC IN 2 1/2" C. 17'-6 3/8" 0.21% 0.21% 1.70% 1.91%
ELECTRICAL CONNECTION SCHEDULE
ITEM VOLTAGE
LOAD
CLASS.
APPARENT
LOAD MCA MOCP OCPD
CIRCUIT
NUMBER WIRE AND RACEWAY
DISCONNECT
BY TYPE COMMENTS
A
HD 120 V, 1Ø Power 1.09 kVA 5.4 A 15 A 15 A 32 2#12 & 1#12 EGC IN 3/4" C. EC CB HAND DRYER HD 120 V, 1Ø Power 1.09 kVA 5.4 A 15 A 15 A 30 2#12 & 1#12 EGC IN 3/4" C. EC CB HAND DRYER HD 120 V, 1Ø Power 1.09 kVA 5.4 A 15 A 15 A 28 2#12 & 1#12 EGC IN 3/4" C. EC CB HAND DRYER TP-2 120 V, 1Ø Power 0.60 kVA 7.3 A 9.1 A 15 A 33 2#12 & 1#12 EGC IN 3/4" C. EC CB TRAP PRIMER WC-1 120 V, 1Ø Power 0.02 kVA 0.3 A 0.3 A 20 A 5 2#12 & 1#12 EGC IN 3/4" C. EC CB WATER CLOSET WC-2 120 V, 1Ø Power 0.02 kVA 0.3 A 0.3 A 20 A 5 2#12 & 1#12 EGC IN 3/4" C. EC CB WATER CLOSET WC-2 120 V, 1Ø Power 0.02 kVA 0.3 A 0.3 A 20 A 5 2#12 & 1#12 EGC IN 3/4" C. EC CB WATER CLOSET WC-2 120 V, 1Ø Power 0.02 kVA 0.3 A 0.3 A 20 A 5 2#12 & 1#12 EGC IN 3/4" C. EC CB WATER CLOSET WC-2 120 V, 1Ø Power 0.02 kVA 0.3 A 0.3 A 20 A 5 2#12 & 1#12 EGC IN 3/4" C. EC CB WATER CLOSET WC-2 120 V, 1Ø Power 0.02 kVA 0.3 A 0.3 A 20 A 5 2#12 & 1#12 EGC IN 3/4" C. EC CB WATER CLOSET WC-2 120 V, 1Ø Power 0.02 kVA 0.3 A 0.3 A 20 A 5 2#12 & 1#12 EGC IN 3/4" C. EC CB WATER CLOSET WC-2 120 V, 1Ø Power 0.02 kVA 0.3 A 0.3 A 20 A 5 2#12 & 1#12 EGC IN 3/4" C. EC CB WATER CLOSET B
ECM 120 V, 1Ø Power 0.20 kVA 2.1 A 15 A 15 A 39 2#12 & 1#12 EGC IN 3/4" C. EC NF ELECTRONIC CONTROL MODULE HD 120 V, 1Ø Power 1.00 kVA 5.4 A 15 A 15 A 3 2#12 & 1#12 EGC IN 3/4" C. EC CB HAND DRYER M1
AHU-1 208 V, 3Ø Power 1.80 kVA 6 A 15 A 20 A 1,3,5 3#12 & 1#12 EGC IN 3/4" C. EC FU AIR HANDLING UNIT BC-1 208 V, 1Ø Power 0.37 kVA 1.8 A 20 A 20 A 44,46 2#12 & 1#12 EGC IN 3/4" C. EC NF BRANCH SELECTOR UNIT BC-2 208 V, 1Ø Power 0.37 kVA 1.8 A 20 A 20 A 50,52 2#12 & 1#12 EGC IN 3/4" C. EC NF BRANCH SELECTOR UNIT COP-1 120 V, 1Ø Power 0.18 kVA 1.9 A 15 A 20 A 54 2#12 & 1#12 EGC IN 3/4" C. EC CB CONDENSATE PUMP COP-2 120 V, 1Ø Power 0.18 kVA 1.9 A 15 A 20 A 54 2#12 & 1#12 EGC IN 3/4" C. EC CB CONDENSATE PUMP CP FC-1-1 208 V, 1Ø Power 0.01 kVA 0.1 A 15 A 20 A 56,58 2#12 & 1#12 EGC IN 3/4" C. EC CB CONTROL PANEL FOR FAN COIL UNIT CP FC-1-2 208 V, 1Ø Power 0.01 kVA 0.1 A 15 A 20 A 56,58 2#12 & 1#12 EGC IN 3/4" C. EC CB CONTROL PANEL FOR FAN COIL UNIT CP FC-1-3 208 V, 1Ø Power 0.01 kVA 0.1 A 15 A 20 A 56,58 2#12 & 1#12 EGC IN 3/4" C. EC CB CONTROL PANEL FOR FAN COIL UNIT CP FC-1-4 208 V, 1Ø Power 0.01 kVA 0.1 A 15 A 20 A 56,58 2#12 & 1#12 EGC IN 3/4" C. EC CB CONTROL PANEL FOR FAN COIL UNIT CP FC-1-5 208 V, 1Ø Power 0.01 kVA 0.1 A 15 A 20 A 56,58 2#12 & 1#12 EGC IN 3/4" C. EC CB CONTROL PANEL FOR FAN COIL UNIT CP FC-1-6 208 V, 1Ø Power 0.01 kVA 0.1 A 15 A 20 A 56,58 2#12 & 1#12 EGC IN 3/4" C. EC CB CONTROL PANEL FOR FAN COIL UNIT CP FC-1-7 208 V, 1Ø Power 0.01 kVA 0.1 A 15 A 20 A 56,58 2#12 & 1#12 EGC IN 3/4" C. EC CB CONTROL PANEL FOR FAN COIL UNIT CP-1 120 V, 1Ø Power 0.08 kVA 0.7 A 15 A 20 A 48 2#12 & 1#12 EGC IN 3/4" C. EC NF CIRCULATION PUMP DOAS-1 208 V, 3Ø Power 11.17 kVA 33 A 40 A 40 A 2,4,6 3#8 & 1#10 EGC IN 3/4" C. EC FU DEDICATED OUTDOOR AIR UNIT EF-1 120 V, 1Ø Power 0.34 kVA 3.5 A 15 A 20 A 42 2#12 & 1#12 EGC IN 3/4" C. EC NF EXHAUST FAN UNIT EF-2 120 V, 1Ø Power 0.16 kVA 1.6 A 15 A 20 A 43 2#12 & 1#12 EGC IN 3/4" C. EC NF EXHAUST FAN UNIT FC-1-1 208 V, 1Ø Power 2.01 kVA 9.7 A 15 A 20 A 22,24 2#12 & 1#12 EGC IN 3/4" C. EC NF FAN COIL UNIT FC-1-2 208 V, 1Ø Power 2.01 kVA 9.7 A 15 A 20 A 27,29 2#12 & 1#12 EGC IN 3/4" C. EC NF FAN COIL UNIT FC-1-3 208 V, 1Ø Power 2.01 kVA 9.7 A 15 A 20 A 34,36 2#12 & 1#12 EGC IN 3/4" C. EC NF FAN COIL UNIT FC-1-4 208 V, 1Ø Power 2.01 kVA 9.7 A 15 A 20 A 18,20 2#12 & 1#12 EGC IN 3/4" C. EC NF FAN COIL UNIT FC-1-5 208 V, 1Ø Power 1.11 kVA 5.3 A 15 A 20 A 26,28 2#12 & 1#12 EGC IN 3/4" C. EC NF FAN COIL UNIT FC-1-6 208 V, 1Ø Power 1.11 kVA 5.3 A 15 A 20 A 30,32 2#12 & 1#12 EGC IN 3/4" C. EC NF FAN COIL UNIT FC-1-7 208 V, 1Ø Power 2.01 kVA 9.7 A 15 A 20 A 38,40 2#12 & 1#12 EGC IN 3/4" C. EC NF FAN COIL UNIT FC-1-8 208 V, 1Ø Power 0.07 kVA 0.3 A 15 A 20 A 13,15 2#12 & 1#12 EGC IN 3/4" C. EC NF FAN COIL UNIT FC-1-9 208 V, 1Ø Power 0.06 kVA 0.3 A 15 A 20 A 19,21 2#12 & 1#12 EGC IN 3/4" C. EC NF FAN COIL UNIT FC-1-10 208 V, 1Ø Power 0.06 kVA 0.3 A 15 A 20 A 39,41 2#12 & 1#12 EGC IN 3/4" C. EC NF FAN COIL UNIT FC-1-11 208 V, 1Ø Power 0.06 kVA 0.3 A 15 A 20 A 35,37 2#12 & 1#12 EGC IN 3/4" C. EC NF FAN COIL UNIT FC-1-12 208 V, 1Ø Power 0.10 kVA 0.5 A 15 A 20 A 23,25 2#12 & 1#12 EGC IN 3/4" C. EC NF FAN COIL UNIT FC-1-13 208 V, 1Ø Power 0.04 kVA 0.2 A 15 A 20 A 14,16 2#12 & 1#12 EGC IN 3/4" C. EC NF FAN COIL UNIT MOD-1 120 V, 1Ø Power 0.12 kVA 15 A 1.3 A 20 A 51 2#12 & 1#12 EGC IN 3/4" C. EC CB MOTOR OPERATED DAMPER MOD-2 120 V, 1Ø Power 0.12 kVA 15 A 1.3 A 20 A 51 2#12 & 1#12 EGC IN 3/4" C. EC CB MOTOR OPERATED DAMPER RF-1 208 V, 3Ø Power 2.38 kVA 8.2 A 20 A 20 A 8,10,12 3#12 & 1#12 EGC IN 3/4" C. EC FU RETURN FAN UNIT RF-2 208 V, 3Ø Power 2.38 kVA 8.2 A 20 A 20 A 7,9,11 3#12 & 1#12 EGC IN 3/4" C. EC FU RETURN FAN UNIT SP-1 120 V, 1Ø Power 0.96 kVA 10 A 12.5 A 20 A 17 2#12 & 1#12 EGC IN 3/4" C. EC NF SUMP PUMP SS-1 208 V, 1Ø Power 0.21 kVA 10 A 15 A 20 A 47,49 2#12 & 1#12 EGC IN 3/4" C. EC NF SPLIT SYSTEM INDOOR UNIT TCP 120 V, 1Ø Power 0.50 kVA 4.2 A 15 A 20 A 45 2#12 & 1#12 EGC IN 3/4" C. EC CB TEMPERATURE CONTROL PANEL WH-1 208 V, 1Ø Power 4.91 kVA 33.3 A 35 A 40 A 31,33 2#8 & 1#10 EGC IN 3/4" C. EC FU WATER HEATER
SB-MAIN
CU-1 208 V, 3Ø Power 13.69 kVA 42 A 50 A 50 A 8 3#6 & 1#10 EGC IN 1" C. EC FU CONDENSING UNIT CU-2 208 V, 3Ø Power 42.87 kVA 131 A 175 A 200 A 9 3#1/0 & 1#6 EGC IN 1 1/2" C. EC FU CONDENSING UNIT CU-3 208 V, 1Ø Power 3.54 kVA 17 A 30 A 30 A 10 2#10 & 1#10 EGC IN 1" C. EC FU SPLIT SYSTEM OUTDOOR UNIT OU-1A 208 V, 3Ø Power 31.70 kVA 88 A 150 A 150 A 6 3#1/0 & 1#6 EGC IN 1 1/4" C. EC FU CONDENSING UNIT OU-1B 208 V, 3Ø Power 31.70 kVA 88 A 150 A 150 A 7 3#1/0 & 1#6 EGC IN 1 1/4" C. EC FU CONDENSING UNIT
AMS-ASSEMBLED MOTOR STARTER
FS - FUSED SWITCH
MX - MANUAL SWITCH
MS - MANUAL STARTER
SS - SOLID STATE
RV - REDUCED VOLTAGE AUTOXFMR
SW - 2 SPEED, 1 WINDING
TW - 2 SPEED, 2 WINDING
RE - REVERSING HL - HANDLE PADLOCK HASP
YD - WYE - DELTA S/N - INSULATED NEUTRAL ASSEMBLY SS - START-STOP PUSHBUTTON IN DOOR FV - FULL VOLTAGE *TA - TWO CONVERTIBLE AUXILIARY CONTACTS EI - ELECTRICAL INTERLOCK (2)-N.O. & (2)-N.C.
STARTER TYPE: *RP - RED (RUN) PILOT LIGHT IN DOOR FA - 4-CONVERTIBLE AUXILIARY CONTACTS *HA - HAND-OFF-AUTO IN DOOR GP - GREEN (OFF) PILOT LIGHT IN DOOR CB - CIRCUIT BREAKER *EO - ELECTRONIC OVERLOAD (3 PHASE MOTORS) TS - 2 SPEED SELECTOR SWITCH IN DOOR NF - NON-FUSED *CT - CONTROL TRANSFORMER, FUSED 120V TO - MELTING THERMAL OVERLOADS (1 PHASE) FU - FUSED SA - STANDARD ACCESSORIES (INCLUDES * ITEMS) PF - PHASE LOSS PROTECTION (5 HP OR GREATER, 3 PHASE
MOTOR)
DISCONNECT TYPE: ACCESSORIES & OPTIONS
NOTE: ALL DISCONNECTS (EXCEPT MANUAL STARTERS) SHALL BE HEAVY DUTY TYPE.
DISCONNECT AND STARTER SCHEDULE
ITEM
DISCONNECT TYPE &
RATING
VOLTAGE POLES ENCLOSURE
REQUIRED
ACCESSORIES
TYPE RATING & OPTIONS COMMENTS
TRIP
RATING
FDS-AHU-1 FU 30 A 20 A 208 V 3 NEMA 12 SA SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
FDS-CU-3 FU 30 A 30 A 208 V 3 NEMA 3R SA SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
FDS-DOAS-1 FU 60 A 40 A 208 V 3 NEMA 1 SA SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
FDS-CU-1 FU 60 A 50 A 208 V 3 NEMA 3R SA SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
FDS-WH-1 FU 60 A 40 A 208 V 2 NEMA 12 SA SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
FDS-OU-1A FU 200 A 150 A 208 V 3 NEMA 3R SA SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
FDS-OU-1B FU 200 A 150 A 208 V 3 NEMA 3R SA SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
FDS-CU-2 FU 200 A 175 A 208 V 3 NEMA 3R SA SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-FC-1-3 NF 20 A 208 V 2 NEMA 12 SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-FC-1-8 NF 20 A 208 V 2 NEMA 12 SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-FC-1-9 NF 20 A 208 V 2 NEMA 12 SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-FC-1-13 NF 20 A 208 V 2 NEMA 12 SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-FC-1-11 NF 20 A 208 V 2 NEMA 12 SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-FC-1-10 NF 20 A 208 V 2 NEMA 12 SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-SS-1 NF 20 A 208 V 2 NEMA 12 SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-BC-1 NF 20 A 208 V 2 NEMA 12 SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-CP-1 NF 20 A 120 V 1 NEMA 12 SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-EF-1 NF 20 A 120 V 1 NEMA 4X SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-EF-2 NF 20 A 120 V 1 NEMA 4X SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-BC-2 NF 20 A 208 V 2 NEMA 12 SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-ECM NF 20 A 120 V 1 NEMA 12 SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-FC-1-1 NF 20 A 208 V 2 NEMA 12 SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-FC-1-7 NF 20 A 208 V 2 NEMA 12 SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-FC-1-6 NF 20 A 208 V 2 NEMA 12 SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-FC-1-2 NF 20 A 208 V 2 NEMA 12 SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-FC-1-5 NF 20 A 208 V 2 NEMA 12 SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-FC-1-4 NF 20 A 208 V 2 NEMA 12 SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-FC-1-12 NF 20 A 208 V 2 NEMA 12 SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
MX-SP-1 NF 20 A 120 V 1 NEMA 12 SA, HL SQUARE D, SIEMENS, EATON OR
APPROVED EQUAL
ADDENDUM C 11/01/2024
ADDENDUM D 12/09/2024
REFER TO SPECIFICATIONS
FCH - FORCED COOLING / HEATING * HARMONIC DISTORTION PERFORMANCE CRITERIA CB - CIRCUIT BREAKER MMO - MULTIPLE MOTOR OVERLOADS * SKIP FREQUENCY CAPABILITY FDS - FUSED DISCONNECT SWITCH TO - MELTING THERMAL OVERLOADS * HAND-OFF-AUTO DOOR SWITCH DS - DISCONNECT SWITCH CA - TWO CONVERTIBLE AUXILIARY CONTACTS * CONTROL TRANSFORMER, FUSED, 120V LINE DISCONNECT: AHF - ACTIVE HARMONIC FILTER * ELECTRONIC THERMAL OVERLOADS LOW HARMONIC (REQUIRED) PHF - PASSIVE HARMONIC FILTER * MANUAL SPEED ADJUSTMENT AFE - ACTIVE FRONT END / ULTRA DB - DYNAMIC BRAKING (INCLUDES * ITEMS) (6,12,18 PULSE PWM REQUIRED) LPF - LEADING POWER FACTOR MANAGEMENT SA - STANDARD ACCESSORIES FOR ALL DRIVES
PWM - PULSE WIDTH MODULATED SC - SHIELDED VFD CABLE RSS - REMOTE START-STOP, DRIVE RUN, FAULT TRIP STARTER TYPE: ACCESSORIES & OPTIONS (REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION):
VARIABLE FREQUENCY DRIVE SCHEDULE
ITEM
LINE
DISC.
DRIVE
BYPASS SCCR
CIRCUIT
VOLTAGE POLES
DRIVE
ENCLOSURE
REQUIRED ACCESSORIES
& OPTIONS COMMENTS
HP
RATING TYPE
TORQUE
TYPE
VFD-RF-1 DS 3
CONTACT
100 kA 208 V 3 3 PWM VARIABLE NEMA 12 SA SQUARE D, SIEMENS, EATON
OR APPROVED EQUAL
VFD-RF-2 DS 3
CONTACT
100 kA 208 V 3 3 PWM VARIABLE NEMA 12 SA SQUARE D, SIEMENS, EATON
OR APPROVED EQUAL
D
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
E4.0-4
ELECTRICAL
SCHEDULES
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
NOTES:
1. {L##} DENOTES THE LIGHTING SEQUENCE OF OPERATIONS FOR THIS SPACE.
2. [#B] PUSH BUTTON REFERS TO SCENE QUANTITY. CONTROL STATION SHALL BE CAPABLE OF [RAISE/LOWER AND] SWITCHING ON/OFF FOR MULTIPLE SCENES AS INDICATED ON SHEETS AND THE LIGHTING SEQUENCE OF OPERATIONS {L##}. COORDINATE QUANTITIES OF BUTTONS FOR CONTROL STATIONS WITH LIGHTING CONTROL MANUFACTURER.
3. [Z#] DENOTES LIGHTING CONTROL ZONE. PROVIDE SEPARATE CONTROL OF EACH CONTROLLED ZONE. LUMINAIRES ASSOCIATED WITH THE SAME ZONE SHALL OPERATE TOGETHER WITHIN THE SAME PROGRAMMED SCENE.
4. a = SWITCH DESIGNATION FOR LIGHTING CONTROL
5. VERIFY AND COORDINATE ALL TIME CLOCK SETTINGS WITH OWNER PRIOR TO FINAL PROGRAMMING.
6. VERIFY AND COORDINATE ALL PUSH BUTTON WALL DEVICES AND QUANTITIES OF INDIVIDUAL BUTTONS WITH SCENES AND ZONES PER LOCATION.
7. VERIFY AND COORDINATE ALL PUSH BUTTON QUANTITIES AND SCENE NAMES WITH OWNER PRIOR TO SUBMITTING ENGRAVING TEMPLATE TO MANUFACTURER.
LIGHTING SEQUENCE OF OPERATION
PLAN ID LIGHTING SWITCHED
{LC1D} Sequence: Lighting is controlled by timeclock.
ON: Lights turn on automatically to 100% with timeclock.
ADJUST: Lighting may be manually raised/lowered via master lighting control station, accessible to only authorized users. Lighting shall continually adjust to interior daylight to maintain 30 footcandles at 30" AFF. When lighting has reached 150% of design illuminance, dim level shall be no greater than 10%.
OFF: Lights turn off using master lighting control station. Lights turn off automatically with timeclock. {LC1} Sequence: Lighting is controlled by timeclock.
ON: Lights turn on automatically to 100% with timeclock.
ADJUST: Lighting may be manually raised/lowered via master lighting control station, accessible to only authorized users.
OFF: Lights turn off using master lighting control station. Lights turn off automatically with timeclock. {LC2} Sequence: Lighting is controlled by timeclock.
ON: Lights turn on automatically to 100% with timeclock.
ADJUST: Lighting may be manually raised/lowered via master lighting control station, accessible to only authorized users. Lights are lowered to 20% after the space has been vacant for 15 minutes.
OFF: Lights turn off using master lighting control station. Lights turn off automatically with timeclock. {LD1} Sequence: Lighting is vacancy controled in this space.
ON: Lights turn on automatically to 50% output.
ADJUST: Lighting may be manually raised/lowered via master lighting control station, accessible to only authorized users.
OFF: Lights turn off using master lighting control station. Lights turn off automatically with timeclock. {LR1} Sequence: 50% of receptacles tagged "O" on the power plans are occupancy controlled in this space.
ON: The lights turn on using the wall controller(s).
ADJUST: The dimming luminaires are raised/lowered using the controller(s).
OFF: The lights turn off manually using the wall controller(s). After the space has been vacant for 20 minutes, the lights will automatically turn off via occupancy sensor. {LS1} Sequence: Lighting control provides occupancy control in this space.
ON: Lights turn on automatically when room is occupied.
OFF: Lights turn off using a wall controller. Lights automatically turn off after the space has been vacant for 15 minutes. {LS2} Sequence: Lighting control provides vacancy control in this space.
ON: Lights turn on manually.
OFF: Lights turn off using a wall controller. Lights automatically turn off after the space has been vacant for 15 minutes. {LS3} Sequence: Lighting control provides occupancy control and emergency lighting control in this space.
ON: Lights turn on to 100% maximum output
ADJUST: Lights are lowered to 50% after the space has been vacant for 15 minutes. {LSE1} Sequence: Lighting control provides manual override and emergency lighting control in this space.
ON: Site building mounted lighting turn on using astronomical timeclock ADJUST: Building mounted lights adjust to 50% maximum output between midnight and 6AM local time OFF: Lights are turned off using astronomical time clock and photocell.
REFER TO SPECIFICATION SECTIONS LED LIGHTING 26 51 19 FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
INTERIOR CORRELATED COLOR TEMPERATURE 3500K, COLOR RENDERING INDEX (CRI) AT OR ABOVE 80, UNLESS NOTED OTHERWISE.
EXTERIOR CORRELATED COLOR TEMPERATURE 3000K, COLOR RENDERING INDEX (CRI) AT OR ABOVE 80, UNLESS NOTED OTHERWISE.
CATALOG NUMBER SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. THE COMPLETE DESCRIPTION AND THE SPECIFICATION SHALL BE COORDINATED WITH THE CATALOG NUMBER TO DETERMINE THE EXACT MATERIAL AND ACCESSORIES TO BE ORDERED. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.
VERIFY AND COORDINATE ALL CEILING TYPES WITH LUMINAIRE MOUNTING AND TRIM REQUIREMENTS PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.
CONFIRM ALL COLORS AND FINISHES OF ALL LUMINAIRE COMPONENTS WITH ARCHITECT AND INTERIOR DESIGNER PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.
UNLESS INDICATED ON LIGHTING PLANS OR BELOW, REFER TO ARCHITECTURAL AND INTERIOR DESIGN ELEVATIONS, SECTIONS AND DETAILS FOR ALL SUSPENDED AND WALL MOUNTED LUMINAIRE MOUNTING HEIGHTS.
DMX - DIGITAL MULTIPLEX EM - EMERGENCY BATTERY ML - MULTI-LEVEL SWITCHING O - OTHER (SEE DESCRIPTION)
DALI - DIGITAL ADDRESSABLE ELV - ELECTRONIC LOW VOLTAGE LINE - LINE VOLTAGE DIMMING REM - REMOTE 0-10V - 0-10V DIMMING EB - ELECTRONIC HL - HIGH/LOW (100%/50%) STEP DIM MV - MULTI-VOLTAGE ELECTRONIC (TYPE) DRIVER:
PL - POLE O - OTHER (SEE DESCRIPTION) DLED - DYNAMIC TUNABLE LED WLED - WARM DIM LED
P - PERIMETER WL - WALL OLED - ORGANIC LED RLED - RETROFIT LED FR - FLANGED RECESSED UC - UNDER CABINET TLED - TUBULAR LED LAMP RGBA - COLOR CHANGING + AMBER CV - COVE SU - SURFACE LED - LIGHT EMITTING DIODE RGBW - COLOR CHANGING + WHITE
CL - CEILING SURFACE SP - SUSPENDED (TYPE) LED RGB - COLOR CHANGING LED (MTG) MOUNTING: RE - RECESSED (WATT) PER: FIX - FIXTURE, FT - FOOT, LAMP CFSA - COLOR-FINISH SELECTION BY ARCHITECT [DESIGN SPECIFIC BLANKS] PAF - PAINT AFTER FABRICATION WW - WALL WASH K - KSH12 .125" ACRYLIC O - OTHER (SEE DESCRIPTION) FINISH: VWD - VERY WIDE G - TEMPERED GLASS SS - SEMI-SPECULAR CLEAR RS - REGRESSED STEEL V - ANSI/IES TYPE 5 DISTRIBUTION WD - WIDE F - FROSTED ACRYLIC R - HIGH IMPACT DR ACRYLIC RA - REGRESSED ALUMINUM IV - ANSI/IES TYPE 4 DISTRIBUTION MD - MEDIUM C - CLEAR ALZAK P - POLYCARBONATE FS - FLAT STEEL III - ANSI/IES TYPE 3 DISTRIBUTION SP - SPOT B - BAFFLE/LOUVER N - NONE FA - FLAT ALUMINUM II - ANSI/IES TYPE 2 DISTRIBUTION NSP - VERY NARROW SPOT A - .125" ACRYLIC M - MATTE DIFFUSE CLEAR (DESC) DOOR: DISTRIBUTION: BEAMWIDTH: (L/L) LENS/LOUVER: K19 - KSH19 .156" ACRYLIC
LED LUMINAIRE SCHEDULE
ITEM DESCRIPTION L/L MTG
DIMENSIONS WATT LED DRIVER
L W H DIA. MANUFACTURER AND MODEL
ANSI
WATTS PER TYPE QTY
DELIVERED
LUMENS
(MIN) VOLTS TYPE
E1 LOW PROFILE CANOPY LIGHT, FLAT
FROSTED LENS, ALUMINUM EXSTRUTION
FINISH BY ARCHITECT.
O SU 11 1/2" 11 1/2" 4
85/256"
0" 10 W FIX LED 1 1900 120 V 0-10V RAB VANLED10YFFR
VANLED10YFRR
E1E LOW PROFILE CANOPY LIGHT, FLAT
FROSTED LENS, ALUMINUM EXSTRUTION
FINISH BY ARCHITECT. INCLUDE EMERGENCY
BATTERY
O SU 11 1/2" 11 1/2" 4
85/256"
0" 10 W FIX LED 1 1900 120 V 0-10V RAB VANLED10YFFR
VANLED10YFRRFINISH/E2
E2E SQAURE AREA LIGHT, ALUMINUM
EXTRUSION, FINISH BY ARCHITECT, INCLUDE
BODINE 50 WATT REMOTE MINI INVERTER.
O SU 5 1/2" 9" 8" 0" 7 W FIX LED 1 750 120 V 0-10V LITHONIA WDGE1 WDGE1 LED P0 30K 80CRI VW MVOLT
SRM FINISH
EX# SINGLE-FACE EXIT SIGN, WHITE
THERMOPLASTIC BODY, GREEN LETTERS,
EMERGENCY NI-CAD BATTERY INSIDE OF
SIGN, UNIVERSAL ARROWS/MOUNTING. SELF
TEST & DIAGNOSTICS OF INVERTER. VERIFY
RECESSED END, BACK OR CEILING
MOUNTING AND ARROWS WITH PLANS.
O CL/SP/
WL
1'-0" 1 1/2" 10" 0" 3 W FIX LED 1 na 120 V EM ACUITY LITHONIA LQMS
SIGNIFY CHLORIDE CLX
COOPER SURELITES APX
F1 RECESSED FLAT PANEL, ALUMINUM
FRAME, SATIN WHITE LENS, EDGE LIT.
O RE 2'-0" 4'-0" 2" 0" 41 W FIX LED 1 4600 120 V 0-10V ACUITY LITHONIA EPANL
COOPER METALUX FPANEL
CURRENT HLI COLUMBIA CFP
F1E RECESSED FLAT PANEL, ALUMINUM
FRAME, SATIN WHITE LENS, EDGE LIT,
INCLUDE A 10 WATT EMERGENCY BATTERY.
O RE 2'-0" 4'-0" 2" 0" 41 W FIX LED 1 4600 120 V 0-10V ACUITY LITHONIA EPANL
COOPER METALUX FPANEL
CURRENT HLI COLUMBIA CFP
F2 RECESSED FLAT PANEL, ALUMINUM
FRAME, SATIN WHITE LENS, EDGE LIT.
O RE 2'-0" 2'-0" 2" 0" 20 W FIX LED 1 2200 120 V 0-10V ACUITY LITHONIA EPANL
COOPER METALUX FPANEL
CURRENT HLI COLUMBIA CFP
F2E RECESSED FLAT PANEL, ALUMINUM
FRAME, SATIN WHITE LENS, EDGE LIT,
INCLUDE A 10 WATT EMERGENCY BATTERY.
O RE 2'-0" 2'-0" 2" 0" 20 W FIX LED 1 2200 120 V 0-10V ACUITY LITHONIA EPANL
COOPER METALUX FPANEL
CURRENT HLI COLUMBIA CFP
F3 LED LENSED STRIP LIGHT, DIE-FORMED
COLD-ROLLED STEEL HOUSING, ROUND,
FULL FROST LENS. PROVIDE MOUNTING
HARDWARE ARE REQUIRED BASED ON
FIELD-COORDINATED CONDITIONS.
O SP/CL 4'-0" 3" 4" 0" 41 W FT LED 1 4400 120 V 0-10V COOPER METALUX SNLED H.E. WILLIAMS 75 LED SERIES
ACUITY LITHONIA ZL1D
F3A LED LENSED STRIP LIGHT, DIE-FORMED
COLD-ROLLED STEEL HOUSING, ROUND,
FULL FROST LENS. PROVIDE MOUNTING
HARDWARE ARE REQUIRED BASED ON
FIELD-COORDINATED CONDITIONS.
O SP/CL 4'-0" 3" 4" 0" 16 W FT LED 1 2100 120 V 0-10V COOPER METALUX SNLED H.E. WILLIAMS 75 LED SERIES
ACUITY LITHONIA ZL1D
F3E LED LENSED STRIP LIGHT, DIE-FORMED
COLD-ROLLED STEEL HOUSING, ROUND,
FULL FROST LENS. PROVIDE MOUNTING
HARDWARE ARE REQUIRED BASED ON
FIELD-COORDINATED CONDITIONS., INCLUDE
A 10 WATT EMERGENCY BATTERY.
O SP/CL 4'-0" 3" 4" 0" 41 W FT LED 1 4400 120 V 0-10V COOPER METALUX SNLED H.E. WILLIAMS 75 LED SERIES
ACUITY LITHONIA ZL1D
L1 ROUND DOWNLIGHT, VERIFY CEILING
THICKNESS. 1.5" REGRESSED TRIM WITH
SOFT FOCUS LENS, SELF-FLANGED, FINISH
BY ARCHITECT. 36 DEG BEAM
G RE 0" 0" 1'-0 1/2" 4" 10 W FIX LED 1 850 120 V 0-10V INTENSE 3.5" MXG2DRTD LENSED
DOWNLIGHT
MXG2DRTR-NC-CEILING-L0-D101-EM7
MXTG2-RTRD302-FINISH-L0-35-36-SL
L1A ROUND DOWNLIGHT, VERIFY CEILING
THICKNESS. 1.5" REGRESSED TRIM WITH
SOFT FOCUS LENS, SELF-FLANGED, FINISH
BY ARCHITECT. 50 DEG BEAM
G RE 0" 0" 1'-0 1/2" 4" 10 W FIX LED 1 770 120 V 0-10V INTENSE 3.5" MXG2DRTD LENSED
DOWNLIGHT
MXG2DRTR-NC-CEILING-L0-D101-EM7
MXTG2-RTRD302-FINISH-L0-35-50-SL
L1AE ROUND DOWNLIGHT, VERIFY CEILING
THICKNESS. 1.5" REGRESSED TRIM WITH
SOFT FOCUS LENS, SELF-FLANGED, FINISH
BY ARCHITECT. 50 DEG BEAM, INCLUDE
EMERGENCY BATTERY.
G RE 0" 0" 1'-0 1/2" 4" 10 W FIX LED 1 770 120 V 0-10V INTENSE 3.5" MXG2DRTD LENSED
DOWNLIGHT
MXG2DRTR-NC-CEILING-L0-D101-EM7
,
MXTG2-RTRD302-FINISH-L0-35-50-SL
L1E ROUND DOWNLIGHT, VERIFY CEILING
THICKNESS. 1.5" REGRESSED TRIM WITH
SOFT FOCUS LENS, SELF-FLANGED, FINISH
BY ARCHITECT. 36 DEG BEAM. INCLUDE
EMERGENCY BATTERY
G RE 0" 0" 1'-0 1/2" 4" 10 W FIX LED 1 850 120 V 0-10V INTENSE 3.5" MXG2DRTD LENSED
DOWNLIGHT
MXG2DRTR-NC-CEILING-L0-D101-EM7
,
MXTG2-RTRD302-FINISH-L0-35-36-SL
L2 CONCEALED CONTINOUS COVE LIGHT,
EXTRUDED ALUMINUM, SEE PLANS FOR
LENGTH, INCLUDE ALL COMPONENTS FOR A
FUNCTIONING SYSTEM.
F CV <varies
>
3 7/8" 1 13/16" 0" 4 W FT LED 1 550 lm/ft 120 V 0-10V LUMENWERX ALCOVE LED ALC-APO-LED-80-550-35-LENGTH-120-
D1-1-COVH-W
L3 CONTINOUS LINEAR, SATIN LENS, ALUMINIUM
EXTRUSION, SEE PLANS FOR LENGTH,
CONFIRM CEILING TYPE
O RE <varies
>
3 1/4" 4 7/64" 0" 7 W FT LED 1 750 lm/ft 120 V 0-10V LUMENWERX VIA 3 RECESSED VIA3R-D-HLO-RG-SW-80-750LMF-LEN
GTH-120V-D1-1C-MOUNTING-FINISH
L4 LINEAR WRAPAROUND, ALUMINUM
EXTRUSION, FINISH BY ARCHITECT, SEE
PLANS FOR LENGTH.
O SU <varies
>
2 1/4" 3 1/2" 0" 10 W FT LED 1 940 120 V 0-10V LUMENWERX QUAD WIDE QUAWS-HLO-SW-80-550-35-4FT-120-D
1-1-DRC-FINISH
L4E LINEAR WRAPAROUND, ALUMINUM
EXTRUSION, FINISH BY ARCHITECT, SEE
PLANS FOR LENGTH, INLCUDE EMERGENCY
BATTERY.
O SU 4'-0" 2 1/4" 3 1/2" 0" 10 W FT LED 1 940 120 V 0-10V LUMENWERX QUAD WIDE QUAWS-HLO-SW-80-550-35-4FT-120-D
1-1+EB-DRC-FINISH,
L5 UNDERCABINET TASK LIGHT, COORDINATE
LENGTH WITH CASEWORK, PROVIDE
JUMPERCABLES AND ACCESSORIES AS
REQUIRED., FINISH BY ARCHITECT.
O CV <varies
>
115/128
"
85/256" 0" 3 W FT LED 1 170 120 V 0-10V HALO COMMERCIAL HU30M-SCTD-LENGTH-FINISH
L6 ROUND WALL WASH, VERIFY CEILING
THICKNESS. 1" REGRESSED TRIM,
SELF-FLANGED, FINISH BY ARCHITECT.
O RE 0" 0" 1" 4" 20 W FIX LED 1 800 120 V 0-10V INTENSE 3.5" MXG2WRTR WALL
WASH WOOD CEILING
MXG2WRTR-NC-CEILING-L2-D101,
MXG2-RWLW300-FINISH-L2-35
LED LUMINAIRE SCHEDULE (CONTINUED)
ITEM DESCRIPTION L/L MTG
DIMENSIONS WATT LED DRIVER
L W H DIA. MANUFACTURER AND MODEL
ANSI
WATTS PER TYPE QTY
DELIVERED
LUMENS
(MIN) VOLTS TYPE
L7 DECORATIVE RING, ALUMINUM EXTRUSION, DIFFUSED
ACRYLIC LENS. FINISH BY ARCHITECT
O SU 0" 0" 1 3/4" 4'-0" 73 W LED 1 4500 120 V 0-10V ALW MOONRING 1.5 MR1.5-D4-SS-LOW-CM-LOW803500K-V01-
LENS
L8 DECORATIVE RING, ALUMINUM EXTRUSION, DIFFUSED
ACRYLIC LENS. FINISH BY ARCHITECT
O SU 0" 0" 2 3/4" 6'-0" 110 W LED 1 6745 120 V 0-10V ALW MOONRING 1.5 MR1.5-D6-SS-LOW-CM-LOW803500K-V01-
LENS
L9 DECORATIVE RING, ALUMINUM EXTRUSION, DIFFUSED
ACRYKUC LENS, FINISH BY ARCHITECT
O SU 0" 0" 3 3/4" 8'-0" 147 W LED 1 9000 120 V 0-10V ALW MOONRING 1.5 MR1.5-D8-SS-LOW-CM-LOW803500K-V01-
LENS
L10 CYLINDER DOWNLIGHT, DECORATIVE LENS,DIE-CAST
ALUMINUM TRIM, FINISH BY ARCHITECT, 50 DEG BEAM.
O SU 0" 0" 6 3/16" 4 5/16" 20 W FIX LED 1 1500 120 V 0-10V DMF M SERIES CYLINDER DC4-SM-S-S-D-15-GA-0-0-35-FINISH-O-EM
-D
L10E CYLINDER DOWNLIGHT, DECORATIVE LENS,DIE-CAST
ALUMINUM TRIM, FINISH BY ARCHITECT, 50 DEG BEAM,
INCLUDE WITH EMERGENCY BATTERY PACK
O SU 0" 0" 6 3/16" 4 5/16" 20 W FIX LED 1 1500 120 V 0-10V DMF M SERIES CYLINDER DC4-SM-S-S-D-15-GA-0-0-35-FINISH-O-EM
-D
L11 ROUND FROSTED GLOBE, ALUMINUM EXTRUSION,
WHITE DIFFUSER.
O SU 0" 0" 6 3/4" 8" 10 W LED 1 1000 120 V 0-10V EUREKA MIKA 3230 3230-8-LED-35-80-120V-DV-WH-39831EA
L12E ROUND FROSTED GLOBE, ALUMINUM EXTRUSION,
WHITE DIFFUSER, INCLUDE BIODINE 50 WATT REMOTE
MINI INVERTER.
O SU 0" 0" 11
13/128
"
1'-0" 10 W LED 1 1040 120 V 0-10V EUREKA MIKA 3230
3230-12-LED-35-80-120V-DV-WH-39831EA
L13 ROUND FROSTED GLOBE, ALUMINUM EXTRUSION,
WHITE DIFFUSER.
O SU 0" 0" 1'-3" 1'-4" 14 W LED 1 1500 120 V 0-10V EUREKA MIKA 3230 3230-16-LED-35-80-120V-DV-WH-39831EA
L14 CYLINDER PENDANT, ALUMINUM EXTRUSION, FINISH BY
ARCHITECT, 40 DEG BEAM.
A SP 0" 0" 1'-1" <varies
>
14 W LED 1 1200 120 V 0-10V LUMENWERX VOILA
VO2CYP-6-FINISH-FLUSH-FINISH-SDL-SW
-40-2-80-35-120-14W-D1
L14E CYLINDER PENDANT, ALUMINUM EXTRUSION, FINISH BY
ARCHITECT, 40 DEG BEAM, INCLUDE EMERGENCY
BATTERY
A SP 0" 0" 1'-1" 6" 14 W LED 1 1200 120 V 0-10V LUMENWERX VOILA VO2CYP-6-FINISH-FLUSH-FINISH-SDL-SW
-40-2-80-35-120-14W-D1+EB
L15A SIZE A CAPSULE SHAPE SURFACE MOUNT LINEAR. 3.5"
DEPTH. HIGH EFFICIENCY LAMBERTIAN OPTIC. SEE
PLANS FOR LENGTHS. FINISH BY ARCHITECT
A,P SU <varies
>
3" 3 1/2" 0" 4 W FT LED 1 500 lm/ft 120 V 0-10V LUMENWERX CURVIA 3 SHAPES CURV3CAS-D-SIZE-CORNER
RADIUS-HLO-NA-SW-90CRI-500LMF-NA-3
5K-120V-D1-1C-DRC-FINISH
L15AE SIZE A CAPSULE SHAPE SURFACE MOUNT LINEAR. 3.5"
DEPTH. HIGH EFFICIENCY LAMBERTIAN OPTIC. SEE
PLANS FOR LENGTHS. FINISH BY ARCHITECT. INCLUDE
WITH EMERGENCY BATTERY
A,P SU <varies
>
3" 3 1/2" 0" 4 W FT LED 1 500 lm/ft 120 V 0-10V LUMENWERX CURVIA 3 SHAPES CURV3CAS-D-SIZE-CORNER
RADIUS-HLO-NA-SW-90CRI-500LMF-NA-3
5K-120V-D1+EB-1C-DRC-FINISH
L15B SIZE B CAPSULE SHAPE SURFACE MOUNT LINEAR. 3.5"
DEPTH. HIGH EFFICIENCY LAMBERTIAN OPTIC. SEE
PLANS FOR LENGTHS. FINISH BY ARCHITECT
A,P SU <varies
>
3" 3 1/2" 0" 4 W FT LED 1 500 lm/ft 120 V 0-10V LUMENWERX CURVIA 3 SHAPES CURV3CAS-D-SIZE-CORNER
RADIUS-HLO-NA-SW-90CRI-500LMF-NA-3
5K-120V-D1-1C-DRC-FINISH
L16 CONCEALED CONTINOUS COVE LIGHT, EXTRUDED
ALUMINUM, SEE PLANS FOR LENGTH, INCLUDE ALL
COMPONENTS FOR A FUNCTIONING SYSTEM.
F CV <varies
>
3 7/8" 1
13/16"
0" 10 W FT LED 1 1200 lm/ft 120 V 0-10V LUMENWERX ALCOVE LED ALC-APO-LED-80-1200-35-LENGTH-120-D1
-1-COVH-W
L17A ACOUSTIC LIT PENDANT, FINISH BY ARCHITECT, HEIGHT
BY ARCHITECT, COLOR BY ARCHITECT.
O SP 0" 3'-0" 4" <varies
>
43 W LED 1 3800 120 V 0-10V LUMENWERX TOGO
TOGOACOP-36-ULO-SW-90-L3800LM-35-D
1-1-FINISH FELT COLOR
L18 CURVED MULTI SYSTEM TRACK, LUMENWERX PIVOT
WITH WALL WASH AND PIVOT DOT, FINISH BY
ARCHITECT
O SP <varies
>
2" 2" 0" 2 W FT LED 1 120 V 0-10V LUMENWERX PIVOT TRACK PENDANT PIVP
-PAT-LENGTH-NA-CORNER-120V-D1-CHA
NNEL-CONTROL-NA-ACC-FINISH-FINISH
L19 TRACK HEAD, 35 DEG BEAM, FINISH BY ARCHITECT,
MOUNTED ON LUMENWERX PIVOT TRACK.
O SP 2" 2" 0" 2" 11 W FIX LED 1 750 120 V 0-10V LUMENWERX PIVOT DOT PIV2DT-2.65IN-SW-FLD-90CRI-750LM-35KSDB-FINISH-FH-FINISH-FINISH-CAHNNEL L20 DECORATIVE CYLINDER PENDANTS, LENS ECHES WHITE
ACRYLIC BUTTOM, WHITE ACRYLIC INNER TOP LENS,
WASHABLE DIFFUSE, WELDED STEEL/ALUMINUM
EXTRUSION
O SP 1'-0" 1'-0" 2'-3" <varies
>
21 W LED 1 1085 120 V 0-10V LUMETTA SHADOW CYLINDER PENDANT CORDCOLORF2CHROME-D921TRANSCOOL-D44PERIW
INKLE-L411-CCT3500KCRI90-120V
L21 LINEAR WALL WASH, FINISH BY ARCHITECT, MOUNTED
ON LUMENWERX PIVOT TRACK.
O SP 8'-0" 1 1/4" 1" 0" 6 W FT LED 1 350 lm/ft 120 V 0-10V LUMENWERX PIVOT MODULE PIVWW-8FT-SW-80CRI-350LMF-25K-FINIS
H
L22 DECORATIVE CYLINDER PENDANTS, LENS ECHES WHITE
ACRYLIC BUTTOM, WHITE ACRYLIC INNER TOP LENS,
WASHABLE DIFFUSE, WELDED STEEL/ALUMINUM
EXTRUSION
O SP 1'-0" 1'-0" 2'-3" <varies
>
21 W LED 1 1085 120 V 0-10V LUMETTA SHADOW CYLINDER PENDANT CORDCOLORF2CHROME-D921TRANSCOOL-D43GRAP
EFRESH-L411-CCT3500KCRI90-120V
L23 DECORATIVE CYLINDER PENDANTS, LENS ECHES WHITE
ACRYLIC BUTTOM, WHITE ACRYLIC INNER TOP LENS,
WASHABLE DIFFUSE, WELDED STEEL/ALUMINUM
EXTRUSION
O SP 1'-0" 1'-0" 2'-3" <varies
>
21 W LED 1 1085 120 V 0-10V LUMETTA SHADOW CYLINDER PENDANT CORDCOLORF2CHROME-D921TRANSCOOL-SPICEFRE
SH-L411-CCT3500KCRI90-120V
ADDENDUM C 11/01/2024
PLAN CHECK
COMMENTS
11/01/2024
DUPLEX RECEPTACLE IS SPLIT
WIRED WITH UPPER (OR LEFT
HALF CONTROLLED OR
HORIZONTAL MOUNT)
QUAD RECEPTACLE IS SPLIT WIRED
WITH UPPER HALF CONTROLLED
CONTROLLED
CONCEALED RACEWAY WITH NONCONTROLLED PHASE,
CONTROLLED (SWITCHED PHASE),
NEUTRAL, AND EQUIPMENT
GROUND CONDUCTOR (TYP)
ONE PIECE COVERPLATE WITH
CONTROLLED DEVICE MARKING.
INCLUDE PANEL-CIRCUIT
IDENTIFICATION WHEN SPECIFIED.
QUAD RECEPTACLE IS
CONFIGURED AS ONE CONTROLLED
AND ONE NON-CONTROLLED
WIRING DEVICE
NOTES:
1. FIELD OR FACTORY REMOVE BREAK-OFF TAB ON WIRING DEVICES TO
SUPPORT CONTROLLED AND NON-CONTROLLED RECEPT ON EACH
COMMON WIRING DEVICE YOKE.
2. RELAY FOR CONTROLLED (SWITCHED) RECEPT SHALL BE FULLY RATED FOR THE BRANCH CIRCUIT LOAD (16-20 AMPS)
CONTROLLED CONTROLLED CONTROLLED
CONTROLLED
RATED WALL
(CONSTRUCTION VARIES)
FIRE SEALANT
FIRE SEALANT
PENETRATING ITEM
PENETRATING ITEM
RATED FLOOR
(CONSTRUCTION
VARIES)
NOTES:
1. THIS GENERAL DETAIL APPLIES TO ALL ITEMS PENETRATING FIRE RATED WALLS OR FLOORS. THE INTENT IS TO MAINTAIN THE FIRE RATING AND TO ALLOW LONGITUDINAL MOVEMENT. REFER TO SPECIFICATION FOR ADDITIONAL INFORMATION.
KEYNOTES:
1. SCHEDULE 5 PIPE SLEEVE EMBEDDED IN WALL OR FLOOR, OR SMOOTH CORE DRILL. EACH CONTRACTOR FURNISHES SLEEVE TO G.C.,
COORDINATES SLEEVE LOCATIONS AND DEBURS SLEEVE. G.C. BUILDS SLEEVE INTO WALL OR FLOOR ALLOWING NO GAP AROUND SLEEVE. IF
SLEEVE IS NOT PROVIDED WHEN WALL OR FLOOR IS BUILT,
CONTRACTOR SHALL INSTALL SLEEVE. SLEEVE SIZE SHALL ALLOW ANNULAR SPACE REQUIRED BY THE SELECTED FIRE STOP SYSTEM.
2. INSTALL BACKING MATERIAL, SUCH AS MINERAL WOOL SAFING, AS REQUIRED FOR FIRE STOP SYSTEM. INSTALL IN ACCORDANCE WITH FIRE STOP SYSTEM APPLICATION LISTING. SECURE TO WALL OR FLOOR TO
ALLOW LONGITUDINAL MOVEMENT OF PENETRATING ITEM WITHOUT MOVEMENT OF FIRE BARRIER.
3. WATER-TIGHT WELDED 1"x1" 20 GAUGE MINIMUM GALVANIZED SHEET
METAL ANGLE FRAME, BY CONTRACTOR IN EQUIPMENT ROOMS FOR WATER STOP. PLACE A BEAD OF WATERPROOF SEALANT BETWEEN
FLOOR AND BOTTOM OF ANGLE FRAME. SECURE TO FLOOR WITH
MASONRY ANCHORS IN CORNERS AND ON 12" MAXIMUM CENTERS.
MULTIPLE PENETRATING ITEMS MAY BE ENCLOSED IN ONE FRAME. 2 3
1 2
3 1
2 12"
WALL WITH INSULATION
FLANGES ON EACH SIDE
OF WALL. CAULK AT
WALL AND SLEEVE.
CONDUIT
SHEET METAL SLEEVE, 2"
LARGER THAN CONDUIT
OVERALL DIAMETER
PACK AROUND CONDUIT WITH
FIBERGLASS INSULATION
ESCUTCHEON PLATES
ON BOTH SIDES
GALVANIZED STEEL CONDUIT CLAMPS
GALVANIZED STEEL CHANNEL ANCHORED
TO WALL. ANCHORS SHALL BE 1/2"Ø HLC
SLEEVE ANCHOR WITH 1 1/2" EMBEDMENT.
FRONT SIDE
#12x1" FLAT HEAD WOOD
SCREW TYP. FOR
12 TOTAL, 3 IN EACH SIDE
ELECTRICAL PANELBOARD
OR CABINET, MAXIMUM
WEIGTH 150 LBS
#10x3" FLT HD WD SCREW.
PRE-DRILL TYPICAL 2 EA. SIDE
2x6 STUD MINIMUM COORDINATE
WITH DEPTH OF ENCLOSURE
2x4 BLOCKING
TOP & BOTTOM
MOUNT ENCLOSURE TO BE
FLUSH WITH WALL FINISH,
GYP., PLASTER, TILE, ETC.
RECESS MOUNTED PANELBOARD - WOOD FRAMING
DO NOT INSTALL IN FIRE
RATED WALL
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
E5.0-1
DETAILS
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
1 NO SCALE
CONTROLLED RECEPTACLE
WIRING
2 NO SCALE
FIRE BARRIER PENETRATION
3 NO SCALE
CONDUIT WALL PENETRATION 4 NO SCALECONDUIT WALL SUPPORT 5 NO SCALE
RECESSED PANEL WOOD FRAMING MOUNTING DETAIL
SYSTEM FURNITURE
CONNECTIONS TO
SYSTEM FURNITURE
1/2" FLEX CONDUIT
(TYP OF 3)
POKE-THRU FLOOR
BOX, STEEL CITY
#PT-7006 (TYP OF 2)
FLOOR SLAB
JUNCTION BOX FOR
POWER CONNECTION
JUNCTION BOX FOR
COMPUTER AND TELEPHONE
CONDUIT AS INDICATED
ON DRAWINGS
TR
LOW VOLTAGE CABLE TO
SOLENOID VALVE, BY P.C.
LOW VOLTAGE CABLE
TO SENSOR, BY P.C.
CLASS II LOW VOLTAGE TRANSFORMER, WITH
PRIMARY AND SECONDARY FUSING. MOUNT IN
NEMA 1 ENCLOSURE ABOVE ACCESSIBLE CEILING.
H
GND
2#14 & 1#14 GND IN 1/2" FLEX FOR LOW VOLTAGE
CLASS II WIRING TO CONTROL MODULES.
MOUNTED UNDER
COUNTER OF
LAVATORY
MOUNTED ON WALL,
LEFT OF URINAL
FLUSH VALVE.
MOUNTED ON
WALL, BEHIND
WATER CLOSET
MAXIMUM OF SIX MODULES
PER TRANSFORMER. MAXIMUM
50' WIRING LENGTH.
LOW VOLTAGE
SOLENOID VALVE
WATER CLOSET LOW
VOLTAGE SENSOR /
CONTROL
LAVATORY LOW
VOLTAGE CONTROL
MODULE
URINAL LOW
VOLTAGE SENSOR
/ CONTROL
N
NOTES:
1. PROVIDE DOUBLE GANG BACKBOXES AND PLASTER RINGS AT LOCATIONS COORDINATED WITH PLUMBING CONTRACTOR (P.C.)
2. E.C. SHALL FIELD VERIFY EXACT SENSOR LOCATION WITH P.C. PRIOR TO ROUGH-IN.
DISTRIBUTION SECTION
SFL
OR
MCB
SFL KIT OR
BACK-FEED
MAIN BREAKER
3'-0"
7'-6"
NEMA 3R ENCLOSURE FOR
MAIN BREAKER SECTION
PULL SECTION MAIN BREAKER SECTION
3'-0"
7'-6"
2'-2"
7'-6"
3'-0"
7'-6"
NOTES:
1. SHOWN FOR REFERENCE ONLY, ACTUAL DIMENSIONS WILL BE DETERMINED BY THE MANUFACTURER, AND SMUD REQUIREMENTS
2. SWITCHBOARD IS MADE UP OF THREE SECTIONS, NEMA 3R ENCLOSURE HOUSES MAIN BREAKER SECTION.
ONE SECTION, REFER NOTE 2
RIGID STEEL
OR IMC CONDUITS MASONRY WALL
WEATHERPROOF
DISCONNECT (27 LBS MAX).
PER PLANS.
"SEALTITE" FLEX
TO UNIT.
22"
10"
TYPICAL. 3/8" DIA. THREADED ROD
x 3 1/2" EMBED W/ SIMPSON
SET-3G EPOXY IN SOLID GROUTED
CMU. PROVIDE 3 1/2" EMBED
WITH 3GW OPTIMESH SCREEN
TUBE AT
HOLLOW CMU CELLS.
GROUND
"E"
12"
MIN.
12"
DIAMETER
12"
"9"
APPROX
FINISHED GRADE
ENSEN PRECAST 1-RD BODY
SERIES WITH 1-R 30-30
SERIES COVER OR EQUAL
STEEL TRAFIC TYPE
COVER WITH HOOK HOLE
AND ETCHED WORDS
"GROUND"
COMPACTED CLEAN EARTH
3/4" X 10'-0" COPPERCLAD
STEEL GROUND ROD
[SCHEDULE 80 PVC]
[SCHEDULE 40PVC] [RGS]
CONDUIT WITH BARE
COPPER GROUNDING WIRE
GROUDING CONNECTOR ON
CALDWELD
GALVAINIZED RIGID STEEL CONDUIT
WRAPPED AROUND WITH 40 MIL
BLACK ELECTRICAL PLASTIC TAPE TO
6" ABOVE FINISHED GRADE
BARE COPPER GROUNDING CONDUCTOR
SIZED PER CODE. SEE SINGLE LINE DIAGRAM
FOR GROUNDING CONDUCTOR SIZE
REFER TO SINGLE LINE DIAGRAM FOR
CONTINUATION
BUILDING EXTERIOR
NOTES:
1. INTERCONNECTION BETWEEN ADDITIONAL GROUND WELLS NOT
SHOWN. PROVIDE INTERCONNECTION BETWEEN GROUND WELLS
AS REQUIRED TO SATISFY SPECIFIED OHM PERFORMANCE.
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
E5.0-2
DETAILS
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
3 NO SCALE
POKE-THRU FLOOR OUTLET
4 NO SCALE
ELECTRONIC SENSOR WIRING
5 NO SCALE
SWITCHBOARD ELEVATION VIEW
1 NO SCALE
DS ON MASONRY WALL
2 NO SCALE
GROUND WELL DETAIL
ADDENDUM C 11/01/2024
ELECTRICAL PANEL / VFD
150 LBS. MAXIMUM
3/8" DIA. THREADED ROD x 3 1/2"
EMBED W/ SIMPSON SET-3G
EPOXY IN SOLID GROUTED CMU.
PROVIDE 3 1/2" EMBED WITH 3GW
OPTIMESH SCREEN TUBE AT
HOLLOW CMU CELLS.
2-10-16x3/4" SELF
TAPPING TEK
SCREWS
MINIMUM OF 8 #12-14
X1" SELF TAPPING
TEK SCREWS.
LOCATEON ON EACH
SIDE OF ENCLOSURE
2-TO 6x16g
3-#10-16x3/4" SELF
TAPPING TEK SCREWS
(TYP. EACH SIDE)
W6x16gauge JAMB
AT 16" O.C.
W6x16gauge @ 16" TYPICAL
ELECTRICAL PANELBOARD OR
CABINET. MAXIMUM WEIGHT 150 LBS.
DO NOT INSTALL IN FIRE RATED WALL
FRONT SIDE
RECESS MOUNTED PANELBOARD - STEEL
FRAMING
DS DS
50" MIN
UNISTRUT #P1008 FLAT
WITH 3/8"Ø HHCS BOLT
(TYP. FOR 4)
6'-0" MIN
ELECTRICAL
CONDUIT SEE PLAN
FOR SIZE & QUANTITY
24"
NOTES:
1. PROVIDE/INSTALL P2072A POST BASE, FOR MOUNTING
OF VERTICAL UNISTRUT.
2. PROVIDE/INSTALL (4) 5/8"Ø X 3" MIN. HILTI KWIK BOLT
TZ2 (ICC-ESR-4266).
3. PROVIDE/INSTALL ALL UNISTRUT NUTS, STUD NUTS,
SCREWS, WASHERS, LOCK WASHERS, ETC., AS
REQUIRED FOR MOUNTING OF ALL UNISTRUT
CHANNELS AND PLATES.
CONCRETE PAD
SEE NOTE 1, BELOW
ELECTRICAL
CONDUIT CLAMP(TYP)
WEATHERPROOF
DUPLEX RECEPTACLE
SEE NOTE 2, BELOW
UNISTRUT #P1000T CHANNEL
(TYP FOR VERTICAL AND
HORIZONTAL MEMBERS)
UNISTRUT #P1065 FLAT
PLATE FITTING(TYP OF 2)
UNISTRUT #P1036 FLAT
PLATE FITTING(TYP OF 2)
UNISTRUT #P1031 FLAT
PLATE FITTING(TYP OF 2)
28"
MAX
O.L.'S
SO
120 VOLT CIRCUIT
LUMINAIRE
POWER RELAY 30 AMP SPST, MOUNTED
IN N.E.M.A. 1 ENCLOSURE ABOVE CEILING,
SQUARE "D" 8501 C06 V04, 9991 TYPE UE1
EXHAUST FAN
NEMA 4X
MANUAL SWITCH
120 VOLT CIRCUIT
H
ØA
N
H N
C
4" MINIMUM COMPACTED
AGGREGATE BASE.
CONDUIT NONMETALLIC SPACER,
MAXIMUM 5' ON CENTER.
MARKER TAPE WITH
METALLIC TRACER, 12"
ABOVE DUCT BANK.
#4 TIE BARS AT
3'-0" ON CENTER
2500 PSI CONCRETE
4" (5") SCHEDULE 40 PVC
(4) #4 BARS CONTINUOUS
ON TOP AND BOTTOM
3" MIN. 7 1/2"
5 1/4"
3" MIN.
24" MIN, 30" MAX
7 1/2"
NONMETALLIC REDUCER
SPACER.
CLEAN EARTH FINISHED GRADE
BACKFILL PLACED PER
SPECIFICATIONS
NOTES:
1. INSTALL 2000 lb TENSILE STRENGTH BRAIDED
POLYPROPYLENE PULL CORD IN ALL CONDUITS.
2. TRENCHING AND BACKFILL ACCORDING TO SPECIFICATIONS.
3. MINIMUM OF 4'-0" CLEAR BETWEEN ADJACENT DUCTBANKS.
4. DOWEL ENDS OF DUCTBANK TO FOUNDATION OR MANHOLE
WITH A MINIMUM OF (4) #4 DOWELS.
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
E5.0-3
DETAILS
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
1 NO SCALE
PANEL / VFD ON MASONRY WALL MOUNTING DETAIL
2 NO SCALE
RECESSED PANEL STEEL FRAMING MOUNTING DETAIL
4 NO SCALE
DISCONNECT SWITCH UNISTRUT MOUNTING DETAIL
3 NO SCALE
EXHAUST FAN EF-2 CONTROL RELAY
5 NO SCALE
DUCT BANK DETAIL (3x1)
ADDENDUM C 11/01/2024
FIRE ALARM SYMBOL LIST
SYMBOL: MAF. MODEL NO. DESCRIPTION:
COMMON AND
SEQUENCE OF
OPERATION
SUBSCRIPTS
SUBSCRIPTS: TYPE / PROGRAMMING
WP = WEATHERPROOF
# = 15, 30, 75, 110, 177 CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
SILENT KNIGHT 6820EVS FIRE ALARM CONTROL PANEL WITH VOICE
EVACUATION CONTROL PANEL
FIRE ALARM ANNUNCIATOR
REMOTE POWER SUPPLY
SPACE AGE TC2-32 FIRE ALARM TERMINAL CABINET
S
# SILENT KNIGHT SK-PHOTO-W FIRE ALARM SMOKE DETECTOR,
CEILING OR WALL MOUNT
BLANK - PHOTOELECTRIC
S
#
F FIRE ALARM MANUAL PULL STATION
#
#
SYSTEM
SENSOR
SCR FIRE ALARM VISUAL ALARM DEVICE, CEILING
OR WALL MOUNT
# = CANDELA RATING.
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
S S COMBINATION AUDIO (VOICE) AND VISUAL
ALARM DEVICE CEILING MOUNTED
# = CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
FIRE ALARM END OF LINE DEVICE,
DRAWINGS ONLY
EOL
H
#
AUDIO (SPEAKER) ALARM DEVICE, CEILING
OR WALL MOUNTED-WP
CSFM LISTING NO.
SILENT KNIGHT 6860
SILENT
KNIGHT
SK-PULL-SA
SYSTEM
SENSOR
SYSTEM
SENSOR
SPRK
SPSR
SPSCR
7320-1653:0201
7125-1653:0186
7320-1653:0201
7150-0559:0161
SYSTEM
SENSOR
B300-6
7272-0559:0512
7300-1653:0109
7300-0553:0110
7165-0559:0500
7165-0559:0500
S SILENT KNIGHT - DUCT DETECTOR -PHOTOELECTRIC -
SILENT FIRE ALARM MONITOR MODULE
KNIGHT
SK-MONITOR 7300-0559:0155 MM
FIRE ALARM TAMPER SWITCH
PIV = POST INDICATOR VALVE
POTTER PCVS-1 7770-0328:0010 TS
POTTER VSR FIRE ALARM FLOW SWITCH 7770-0328:0001 FS
SYSTEM FIRE ALARM BELL
SENSOR
SSV120-6 7135-1653:0217 F
MULTI VOLTAGE RELAY
(24VDC,24VAC,120VAC)
APOLLO MR-101/C/R 7300-1004:0101 R
5496
EVS-50W DISTRIBUTED AUDIO AMPLIFIER
7300-0559:0171
7165-0559:0500
SILENT KNIGHT
SILENT KNIGHT
SPACE AGE FIRE ALARM DOCUMENT CABINET
OSYSU-2
SYMBOL
TWISTED PAIR
TWO
NUMBER OF CONDUCTORS
SIGNALING LINE CIRCUIT (SLC) - ABOVE GRADE
NOTIFICATION APPLIANCE CIRCUIT
DESCRIPTION
D
N
SIZE
#16
#12 THHN/THWN
TYPE
UD SIGNALING LINE CIRCUIT (SLC) - BELOW GRADE TWISTED PAIR #16 WEST PENN #AQC225 WEST PENN #D990
(CSFM #7161-0859:0101)
NOTE:
1. SYMBOL INDICATES QTY & I.D. OF CIRCUIT. I.E. 2N2, INDICATES (2) 2#12 CI CABLE FOR N CIRCUIT.
2. ALL CONDUIT USED FOR FIRE ALARM SHALL BE 3/4" MINIMUM ABOVE GRADE AND 1" MINIMUM BELOW GRADE UNLESS NOTED OTHERWISE.
3. ALL WIRING USED IN UNDERGROUND CONDUITS SHALL BE LISTED FOR WET AREA APPLICATION, IN ACCORDANCE WITH CEC 760.
FIRE ALARM WIRE DESIGNATION CHART
S VOICE EVACUATION CIRCUIT - ABOVE GRADE TWISTED PAIR #16 WEST PENN #D990 (CSFM #7161-0859:0101)
AQUA SEAL 65MM
FIBER OPTIC CABLE
US VOICE EVACUATION CIRCUIT - BELOW GRADE FIBER OPTIC CABLE 2022 CALIFORNIA ADMINISTRATIVE CODE (CAC), PART 1, TITLE 24 CCR 2022 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 CCR 2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 CCR 2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 CCR 2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 CCR 2022 CALIFORNICA ENERGY CODE, PART 6, TITLE 24 CCR
2022 CALIFORNIA FIRE CODE (CFC), PART 9, TITLE 24 CCR
2022 CALIFORNIA EXISTING BUILDING CODE, (CEBC), PART 10, TITLE 24 CCR 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE, (CAL GREEN), PART 11, TITLE 24 CCR
2022 CALIFORNIA REFERENCED STANDARDS CODE, PART 12, TITLE 24 CCR TITLE 19 CCR, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS LIST OF APPLICABLE CODES:
APPLICABLE STANDARDS:
FOR A LIST OF APPLICABLE STANDARDS, INCLUDING CALIFORNIA AMENDMENTS TO THE NFPA STANDARDS, REFER TO CBC CHAPTER 35 AND CFC CHAPTER 80.
SEQUENCE OF OPERATION
REPORT TO CENTRAL STATION YES NO
ACTIVATE AUDIBLE ALARM SIGNALS (UNTIL SILENCE)
ACTIVATE VISUAL ALARM SIGNALS (UNTIL RESET)
SOUND CONTROL PANEL TROUBLE BUZZER
NO
NO
YES
YES
ANNUNCIATE AT FIRE CONTROL PANEL (ALARM)
BUILDING
FAILURE
POWER
NO
SMOKE
YES
DETECTOR OR GROUND
OPEN SHORT
NO
NO
YES
YES
YES YES
ANNUNCIATE AT REMOTE ANNUNCIATOR PANEL
(ADMIN)
SHUTDOWN HVAC UNIT NO YES NO
ACTIVATE EMERGENCY VOICE SYSTEM SIGNALS
(UNTIL RESET)
NO YES NO
YES
YES
YES
MANUAL
YES
PULL STN
YES
YES
YES
YES
YES
DUCT
YES
DETECTOR
YES
YES
YES
YES
TAMPER
SWITCH
YES
YES
YES
YES
NO
YES
YES
FLOW
SWITCH
ANNUNCIATE AT FIRE CONTROL PANEL (SUPERVISION)
ANNUNCIATE AT FIRE CONTROL PANEL (TROUBLE) YES
NO
YES YES NO
NO
NO
NO
NO
ANNUNCIATE AT REMOTE ANNUNCIATOR PANEL
(SUPERVISION)
YES
YES
ANNUNCIATE AT REMOTE ANNUNCIATOR PANEL
(TROUBLE) NO
NO
NO
NO NO
NO
NO NO
NO NO
NO
NO
ACTIVATE SPRINKLER BELL NO NO NO YES NO
YES
NO NO
NO
YES
YES
YES
YES
YES YES YES YES YES YES YES
YES
YES YES YES YES YES YES
ACTIVATE ROLL-DOWN DOOR YES NO YES YES NO NO NO
FIRE ALARM NOTES
1. THIS IS A COMPLETE MANUAL SYSTEM WITH SUPPLEMENTAL AUTOMATIC DETECTING DEVICES SYSTEM PLAN SUBMITTAL PER 2022 CFC 907.2.3 AND 2022 CBC 907.2.3.
2. THE CONTRACTOR SHALL COORDINATE CONSTRUCTION PHASING WITH THE OWNER
AND PROVIDE ALL COST ASSOCIATED WITH CONSTRUCTION PHASING INCLUDING TEMPORARY CONNECTS. FIRE WATCHS AND PROGRAMMING OF EXISTING AND NEW FIRE ALARM SYSTEM.
3. THE FIRE ALARM SYSTEM INDICATED ON THESE DRAWINGS IS APPROVED BY
CALIFORNIA STATE FIRE MARSHAL AND SHALL BE INSTALLED AS DESCRIBED ON THESE DRAWINGS AND AS NOTED IN THE SPECIFICATIONS. ANY CHANGES TO THESE PLANS, I.E., DELETION, RELOCATION OR ADDING OF DEVICES SHALL BE RESUBMITTED TO THE STATE FIRE MARSHAL FOR APPROVAL.
4. ALL WIRING AND INITIATING DEVICES SHALL BE SUPERVISED TO THE PRINCIPAL POINT OF ANNUNCIATION (F/A PANEL TO SUPERVISE ALL CIRCUITS AND INITIATING DEVICES).
5. WIRING SHALL NOT BE LOOPED THROUGH DEVICES; WIRE MUST BE CUT FOR IN AND FOR OUT.
6. FIRE ALARM SYSTEM DEMOLITION AND CONSTRUCTION SHALL COMPLY WITH 2022 CBC CHAPTER 33 AND 2.19 CFC. FIRE PROTECTION DURING DEMOLITION AND CONSTRUCTION SHALL BE IN ACCORDANCE TO 2022 CBC AND CFC.
7. ALL TERMINATIONS IN JUNCTION BOXES, PULL BOXES AND TERMINAL CABINETS SHALL BE ON BOX MOUNTED TERMINAL BLOCKS. DO NOT USE WIRE NUTS FOR SPLICING. DO NOT SPLICE WIRES IN ANY BOXES.
8. ALL CONDUIT SIZES INDICATED IN DRAWINGS ARE MINIMUM. CONTRACTOR TO ADJUST SIZE FOR FIELD CONDITIONS BUT SHALL NOT BE SMALLER THAN 3/4 INCH.
9. ALL FIRE ALARM WIRING MUST TEST FREE OF OPENS, SHORTS AND GROUNDS.
10. FIRE ALARM DRAWINGS ARE SCHEMATIC IN NATURE ONLY. CONTRACTOR TO ROUTE WIRING AS FIELD CONDITIONS INDICATE.
11. CONDUIT AND JUNCTION/BACK BOXES ARE NOT TO BE USED FOR UNRELATED WIRING.
12. THE SYSTEM SHALL CONFORM TO TITLES 19 AND 24 AS APPLICABLE TO THIS PROJECT.
13. UPON COMPLETION OF SYSTEM INSTALLATION, THE SYSTEM SHALL BE TESTED IN THE PRESENCE OF, AND IN A MANNER ACCEPTABLE TO, THE ENFORCING AGENCY.
14. THE CONTRACTOR SHALL REPROGRAM AND CERTIFY ADDRESSABLE FIRE ALARM CONTROL PANEL TO ACCOMMODATE ADDITIONAL DEVICES.
15. FIRE ALARM SYSTEM SHALL BE INSTALLED BY FACTORY AUTHORIZED REPRESENTATIVE.
16. CONDUCTOR LENGTHS AND DEVICE QUANTITIES ARE SHOWN SOLELY FOR CALCULATION PURPOSES ONLY, AND SHALL NOT BE USED FOR BID TAKE-OFF.
17. THE FIRE ALARM SYSTEM SHALL CONFORM TO ARTICLE 760 OF CALIFORNIA ELECTRICAL CODE. INSTALLATION OF THE FIRE ALARM SYSTEM SHALL NOT BE STARTED UNTIL
DETAILED PLANS AND SPECIFICATIONS, INCLUDING CALIFORNIA STATE FIRE MARSHAL
LISTING NUMBERS FOR EACH COMPONENT OF THE SYSTEM HAVE BEEN APPROVED BY CITY OF SACRAMENTO. UPON COMPLETION OF THE INSTALLATION OF THE FIRE ALARM
SYSTEM A SATISFACTORY TEST OF THE ENTIRE SYSTEM SHALL BE MADE IN THE PRESENCE OF THE FIRE AUTHORITY HAVING JURISDICTION.
18. PENETRATIONS OF PIPES, CONDUITS, ETC., IN WALLS REQUIRING PROTECTED OPENINGS SHALL BE FIRE STOPPED. FIRE STOP MATERIAL SHALL BE A TEST ASSEMBLY ACCEPTABLE TO CITY OF SACRAMENTO.
19. ALL FIRE ALARM AND COMMUNICATIONS WIRES AND CABLES SHALL BE ONE
CONTINUOUS LENGTH FROM A BUILDING TERMINAL CABINET TO ANOTHER BUILDING TERMINAL CABINET OR JUNCTION BOX. ABSOLUTELY NO SUBGRADE SPLICES WILL BE PERMITTED! PROVIDE TERMINAL BLOCKS WITH MOUNTING IN TERMINAL CABINETS ONLY AS REQUIRED.
20. EVERY ALARM SIGNALING DEVICE INSTALLED SHALL BE OF THE SAME BASIC TYPE (BELLS, HORNS, CHIMES, SPEAKERS, ETC.) AS ALL OTHER SIGNALING DEVICES IN THE FACILITY, (EXCEPTION: ANY SIGNALING DEVICES REQUIRED FOR THE DEAF OR HEARING IMPAIRED PER 2022 NFPA-72.
21. INSULATED CONDUCTORS USED IN WET LOCATIONS SHALL BE (1) LEAD-COVERED, (2) TYPES RHW,TW, THW, THHW, THWN, XHHW; OR (3) OF A TYPE LISTED FOR USE IN WET LOCATIONS. CABLES OF ONE OR MORE CONDUCTORS USED IN WET LOCATIONS SHALL BE OF A TYPE LISTED FOR USE IN WET LOCATIONS. CONDUCTORS USED FOR DIRECT BURIAL APPLICATIONS SHALL BE OF A TYPE LISTED FOR SUCH USE (PER 2022 CEC ARTICLE 310).
22. THE FIRE ALARM DEVICE SUPPLIER SHALL FURNISH ALL SURFACE MOUNT ENCLOSURES
FOR PULLSTATIONS AND SKIRTS FOR ALL VISUAL AND AUDIO VISUAL DEVICES TO CONCEAL 4S BACK BOXES.
23. AFTER THE SYSTEM IS COMPLETED, ALL ADDRESSABLE DEVICES SHALL BE PROGRAMMED AT THE FACP ACCORDING TO THE ACTUAL BUILDING ROOM NUMBER. THE
CONTRACTOR IS RESPONSIBLE TO COORDINATE WITH THE SCHOOL DISTRICT TO OBTAIN ACCURATE ROOM NUMBER INFORMATION.
24. POWER SERVICES SHALL BE ON A DEDICATED BRANCH CIRCUIT WITH A RED MARKING & LOCKING DEVICE AND IDENTIFIED AS "FIRE ALARM CIRCUIT CONTROL".
25. PROVIDE CALIFORNIA TEMPORAL-THREE TONE DISTINCTIVE FIRE ALARM SOUND. (2022 CFC SEC. 907.6.2.1.3 & 2019 NFPA 72 SEC. 18.4.2.1)
26. AUDIBLE FIRE ALARM SOUND LEVEL SHALL BE AT LEAST 15 dBA ABOVE THE AVERAGE AMBIENT SOUND LEVEL IN ALL OCCUPIABLE AREAS (2022 NFPA 72 SEC. 18.4.3.1) (i.e.
CLASSROOM AVERAGE AMBIENT ROOM NOISE IS45dBA PLUS 15dBA EQUAL = 60dBA
MINIMUM ALARM TONE REQUIRED)
27. STROBES SHALL FLASH AT A RATE NOT EXCEEDING TWO FLASHES PER SECOND NOR BE LESS THAN ONE FLASH EVERY SECOND. (2022 NFPA 72 SEC. 18.5.3.1)
28. FINAL FIRE ALARM TEST SHALL BE MADE WITH THE CITY OF SACRAMENTO INSPECTOR OF RECORD (IOR). LOCAL FIRE AUTHORITY SHALL BE NOTIFIED OF DATE AND TIME OF FINAL ALARM TESTING AND SHALL ASSIST/WITNESS SUCH TESTING WHEN ABLE.
29. FIRE ALARM CONTRACTOR SHALL PROVIDE A "RECORD OF COMPLETION" TO THE
INSPECTOR OF RECORD (IOR)/CITY OF SACRAMENTO AFTER COMPLETION OF OPERATION ACCEPTANCE TEST. (2022 NFPA 72 SEC. 7.5.6. & 2022 CFC 901.6.2)
30. UNLESS SPECIFICALLY SHOWN ON THESE PLANS NO STRUCTURAL MEMBER SHALL BE
CUT, DRILLED, NOR NOTCHED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM THE
STRUCTURAL ENGINEER AND DISTRICT STRUCTURAL ENGINEER FROM THE DIVISION OF THE STATE ARCHITECT.
31. THE INSTALLING CONTRACTOR SHALL PROVIDE A STATEMENT OF COMPLIANCE ALONG WITH THE REQUEST FOR ACCEPTANCE TESTING PER 2022 NFPA-72.
32. OCCUPANCY OF THE BUILDINGS IS PROHIBITED UNTIL THE FIRE ALARM SYSTEM IS COMPLETED, TESTED, AND APPROVED PER 2022 NFPA 72.
33. SMOKE DETECTORS SHALL BE TESTED PER THE METHOD SHOWN IN 2022 CFC.
34. REACCEPTANCE TESTING SHALL BE PERFORMED AS REQUIRED BY 2022 NFPA 72.
35. ALL BACKUP BATTERIES FOR FIRE ALARM SYSTEM EQUIPMENT SHALL BE VISUALLY CHECKED FOR DATE OF INSTALLATION. ALL BATTERIES OVER 5 YEARS OLD SHALL BE REPLACED WITH NEW BATTERIES OF THE SAME MANUFACTURER, TYPE, AND AMPHOUR RATING.
36. FIRE ALARM SYSTEMS SHALL BE SUPERVISED BY AN APPROVED UL LISTED CENTRAL STATION, OR REMOTE STATION (UUFX) MONITORING COMPANY (UUJS) (2022 CFC, 907.2.3.5, 907.6.5.3.)
37. A SINGLE FAULT ON A PATHWAY CONNECTED TO THE ADDRESSABLE DEVICES SHALL NOT CAUSE THE LOSS OF MORE THAN 50 ADDRESSABLE DEVICES (2022 NFPA 72 SECTION
23.6.1)
38. PROVIDE FIRE ALARM DOCUMENT CABINET PER 2022 NEPA 72,7.7.2.1.
39. FIRE ALARM CONTROL PANEL MICROPHONE SHALL HAVE POSTED OPERATING INSTRUCTION PER 2022 NFPA 72, 24.3.2.
40. THE DISTRICT SHALL RETAIN RECORD DRAWINGS ON THE PREMISES IN A DEDICATED FIRE ALARM RECORD DOCUMENT CABINET IN ACCORDANCE WITH 2022 NFPA 72, 7.7.2.
EVERY NEW FIRE ALARM SYSTEM SHALL PROVIDE A DOCUMENTATION CABINET, INSTALLED AT THE SYSTEM CONTROL PANEL OR OTHER APPROVED LOCATION.
THE DOCUMENTATION CABINET SHALL BE PROMINENTLY LABELED,"SYSTEM RECORD DOCUMENTS".
ALL RECORED AND TESTING DOCUMENTATION SHALL BE STORED IN THE CABINET.
CONTENTS SHALL BE ACCESSIBLE BY AUTHORIZED PERSONNEL ONLY.
WHERE CABINET IS INSTALLED IN A LOCATION OTHER THAN THE SYSTEM CONTROL UNIT, ITS LOCATION SHALL BE IDENTIFIED AT THE SYSTEM CONTROL UNIT.
SYSTEM DOCUMENTS AS APPLICABLE:
RECORD DRAWINGS/AS-BUILTS
EQUIPMENT CUT SHEETS & CA SFM LISTINGS
ALTERNATIVE MEANS AND METHODS
PERFORMANCE BASED DESIGN DOCUMENTATION (NFPA 72, 7.3.7)
SYSTEM RECORED OF COMPLETION & ANY SUPPLEMENTAL INSPECTION AND TESTING DOCUMENTATION (NFPA 72, 7.8.2)
EMERGENCY RESPONSE PLAN (NFPA 72, 7.3.8)
EVALUATION DOCUMENTATION (NFPA 72, 7.3.9)
SOFTWARE & FIRMWARE CONTROL DOCUMENTATION (NFPA 72, 23.2.2)
41. EXTRA DEVICES
DUE TO UNFORESEEN CONDITION, THE FOLLOWING EXTRA DEVICES SHALL BE INCLUDED IN THE CONTRACTORS BID:
a. SMOKE DETECTORS 2 EACH
b. MANUAL PULL STATION 2 EACH
c. DUCT DETECTORS 2 EACH
d. SPEAKER-EXTERIOR 2 EACH
e. SPEAKER/STROBE 2 EACH
f. STROBE 2 EACH
g. MONITOR/CONTROL MODULES 2 EACH
h. 20A/120V DEDICATED CIRCUIT WITH 50' OF 3/4"C-2#12 2 EACH & 1#12 GND. AND 20A/1P MATCHING BREAKER WITH
RED HANDLE.
FOR BID PURPOSES, ALLOW TWENTY (30) FEET OF CONDUIT WITH WIRING AND ITS
SUPPORT SYSTEM TO INCLUDE FITTINGS, WIRES AND LABOR FOR EACH OF THE DEVICES LISTED ABOVE INCLUDE PROGRAMMING OF DEVICCES.
42. ALL UNDERGROUNDS AND EXTERIOR CONDUITS SHALL BE PROVIDED WITH WATERTIGHT FITTINGS AND WIRES SHALL BE APPROVED FOR WET LOCATIONS.
43. A SINGLE FAULT ON A PATHWAY CONNECTS TO THE ADDRESSABLE DEVICES SHALL NOT CAUSE THE LOSS OF THE DEVICES IN MORE THAN ONE ZONE PER 2022 NFPA# 72 SECTIONE 23.6.1.
44. FIRE ALARM SYSTEM SHALL BE SUPERVISED BY AN APPROVED UL LISTED CENTRAL STATION OR REMOTE STATION (UUFX) MONITORING COMPANY (UUJS) PER CFC 907.2.3.5 AND 907.6.6.3.
45. FIRE ALARM INSTALLATION SHALL COMPLY WITH CFC CHAPTER 33 - FIRE SAFETY DURING CONSTRUCATION AND DEMOLITION.
46. THE CONTRACTOR OPERATIONS SHALL NOT BLOCK, HINDER, IMPEDE OR OTHERWISE INHIBIT THE USE OF REQUIRED EXITS AT ANY TIME. THE CONTRACTOR SHALL MAINTAIN
UNOB STRUCTED ACCESS TO FIRE EXHUGUISHERS, FIRE HYDRANTS, TEMPORARAY FIRE
PROTECTION FACILITIES, STAIREWIS AND OTHER ACCESS ROUTES FOR FIRE FIGHTING EQUIPMENT AND OR PERSONER.
47. 2022 NFPA 72, 10.6.7 THE SECONDARY POWER SUPPLY SHALL HAVE SUFFICENT CAPACITY TO OPERATE THE SYSTEM UNDER QUIESCENT LOAD (SYSTEM OPERATING IN A NONALARM CONDITION) FOR A MINIMUM OF 24 HOURS AND AT THE END OF THAT PERIOD,
SHALL BE CAPABLE OF OPERATING ALL ALARM NOTIFICATION APPLIANCES USED FOR EVACUATION OR TO DIRECT AID TO THE LOCATION OF AN EMERGENCY FOR 5 MINUTES, UNLESS OTHERWISE PERMITTED OR REQUIRED BY THE FOLLOWING:
1. BATTERY CALCULATIONS SHALL INCLDUE A 20 PERCENT SAFETY MARGIN TO THE CALCULATED AMP-HOUR RATING.
2. THE SECONDARY POWER SUPPLY FOR IN-BUILDING EMERGENCY VOICE/ALARM
COMMUNICATIONS SERVICE SHALL BE CAPABLE OF OPERATING THE SYSTEM UNDER QUIESCENT LOAD FOR A MINIMUM OF 24 HOURS AND THEN SHALL BE CAPABLE OF
OPERATING THE SYSTEM DURING A FIRE OR OTHER EMERGENCY CONDITION FOR A PERIOD OF 15 MINUTES AT MAXIMUM CONNECTED LOAD.
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
FA0.0
FIRE ALARM
COVER SHEET
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
FIRE ALARM SHEET INDEX
FA0.0 FIRE ALARM COVER SHEET
FA0.1-1 FIRE ALARM SCHEDULES AND RISER DIAGRAM
FA1.1-1 OVERALL SITE PLAN - FIRE ALARM
FA2.0-1 BASEMENT DEMOLITION PLAN - FIRE ALARM
FA2.0-2 FIRST FLOOR DEMOLITION PLAN - FIRE ALARM
FA2.0-3 BASEMENT REMODEL PLAN -FIRE ALARM
FA2.0-4 FIRST FLOOR REMODEL PLAN - FIRE ALARM
FA3.0-1 FIRE ALARM DETAILS
FA3.0-2 FIRE ALARM DETAILS
GRAND TOTAL: 9
ADDENDUM C 11/01/2024
PLAN CHECK
COMMENTS
11/01/2024
BUILDING-LIBRARY
FADC FAA
FATC-1
S
001-1
S
001-2
S
122-1
S
120-1
S
124-1
S
123-1
S
120-2
S
121-1
S
120-3
S
120-4
S
116-1
S
S
S
S
S
115-1
S
117-1
S
S
S
S
118-1
S
116-2
118-2
118-3
118-4
115-2
116-3
112-1
114-1
S S
S
S
S
S
S
S
S
S
S
113-1 112-2
112-3
112-4
112-5
112-6
112-7
110-1
116-4
116-5
109-1
S
S
S
S
S
S
S
S
S S
101-1
105-1
108-1 107-1
106-1
104-1
103-1
102-1
102-2
102-3
2D
D
D
D D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D D
F
101-2
S
H
N1,S1
N1-1
S1-1
30cd
0.5W
S1-2
2.0W
WP
N1,S1
N1-2
15cd
N1,S1
S
N1-5
S1-3
30cd
0.5W
N1,S1
N1-3
30cd
H
N1,S1
S1-5
2.0W
WP
N1,S1
N1-9
15cd
EOL
EOL-N1
L=510'-0"
N2-1
15cd
N2,S2
S
N2-2
S2-1
75cd
0.5W
N2,S2
H
S2-2
2.0W
WP
N2,S2
N2-3
15cd
N2,S2
N2-4
30cd
N2-5
15cd
N2,S2
H
S2-3
2.0W
WP
N2,S2
N2-6
15cd
N2,S2
N2-7
15cd
N2,S2
N2,S2
S
N2-9
S2-4
75cd
0.5W
N1,S1
D
N2,S2
FACP/VECP
1 D,N,S
N1,S1
N1-4
15cd
N1,S1
N1-6
15cd
N1,S1
S
N1-7
S1-4
110cd
2.0W
N1,S1
S
N1-8
S1-6
30cd
0.5W
H
N1
S1-8
2.0W
WP
N1,S1
S
N1-10
S1-7
30cd
0.5W
N1,S1
N1-11
15cd
N1-12
15cd
EOL
EOL-S1
L=490'-0"
N2-8
15cd
N2,S2
N2,S2
S
N2-10
S2-5
110cd
2.0W
N2-11
75cd
N2,S2
N2,S2
N2
S
N2-12
S2-6
75cd
0.5W
N2-13
75cd
EOL
EOL-N2
L=400'-0"
EOL
EOL-S2
L=380'-0"
S
119-1
D
D
S
001-1A
2D
TO AHU-1
3 2D
F
S
001-2A
2D
TO DOAS-1
3 001-2B
MM MM
TS FS
R F
AMP-1
2S
D,P
N1,S1
WP
2 2D
TO CIRCUIT
B-36
TO CIRCUIT
A-7
2D
F
120-1A
2D
F
116-1A
2D
F
115-2A
2D
2D
F
112-4A
2D
MM MM
TS TS
DCDA
7 2D
F
116-5A
2D
CM
TO OVERHEAD
DOOR 106
2D
F
103-1A
MM
TS
PIV
8 9
2D
5 6
D
4 TELEPHONE
CABLE
WP WP
WP
N1-13
S1-9
75cd
0.5W
S
2N1,2S1
S
N1-14
S1-10
110cd
2.0W
N1,S1
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
FA0.1-1
FIRE ALARM
SCHEDULES AND
RISER DIAGRAM
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
21.846 AH, SPARE CAPACITY
28 AH, BATTERY CAPACITY
6.154 TOTAL
IT SHALL NOT BE USED FOR BID QUANTITY TAKEOFFS. 1.026 (20% SAFETY FACTOR) SOLELY FOR ENGINEERING CALCULATIONS. 5.128 AH, SUB TOTAL FIRE ALARM DEVICE QUANTITIES ARE SHOWN 0.724 AH, ALARM
4.405 AH, STANDBY
4.405 AH 0.724 AH
x 24 H x 0.25 H
0.184 A 2.894 A
TOTAL 0.184 2.894
EXTERIOR SPEAKER- WEATHERPROOF 5 0.09000 0.45000
SPEAKER/STROBECOMBO (110cd) 3 0.20300 0.60900
SPEAKER/STROBE COMBO (75cd) 4 0.15900 0.63600
SPEAKER/STROBE COMBO (30cd) 4 0.08600 0.34400
SPEAKER/STROBE COMBO (15cd) 0 0.06500 0.00000
STROBE (75cd) - CEILING 2 0.07200 0.14400
STROBE (30cd) - CEILING 2 0.03500 0.07000
STROBE (15cd) - CEILING 12 0.03000 0.36000
CONTROL MODULE 1 0.00530 0.005300 0.00530 0.00530
RELAY MODULE 1 0.00530 0.005300 0.00530 0.00530
FA BELL 1 0.00530 0.005300 0.00530 0.00530
TAMPER SWITCH WITH MONITOR MODULE 3 0.00040 0.00119 0.00068 0.00204 TAMPER & FLOW SWITCH WITH DUAL MONITOR MODULE 1 0.00040 0.00040 0.00068 0.00068 DUCT DETECTOR 2 0.00030 0.00060 0.00030 0.00060
SMOKE DETECTOR 44 0.00030 0.01320 0.00030 0.01320
MANUAL PULL STATION 9 0.00025 0.00225 0.00040 0.00360
REMOTE POWER SUPPLY 0 0.00000 0.00000
FIRE ALARM ANNUNCIATOR 1 0.02000 0.02000 0.02500 0.02500 FACP/VECP 1 0.13000 0.13000 0.22000 0.22000
QTY UNIT TOTAL UNIT TOTAL
DESCRIPTION SUPERVISORY CURRENT ALARM CURRENT
FACP
BATTERY CALCULATION FOR FIRE ALARM CONTROL PANEL
BLDG FACP/VECP N4 0 0.000 0 0.000 0 0.000 0 0.000 0 0.000 0 0.000 0 0.000 0.000 12 6530 0 0.00 SPARE BLDG FACP/VECP N3 0 0.000 0 0.000 0 0.000 0 0.000 0 0.000 0 0.000 0 0.000 0.000 12 6530 0 0.00 SPARE BLDG FACP/VECP N2 6 0.168 1 0.094 2 0.316 0 0.000 0 0.000 3 0.477 1 0.203 1.258 12 6530 400 6.93 BLDG FACP/VECP N1 6 0.168 1 0.094 0 0.000 0 0.000 4 0.344 1 0.159 2 0.406 1.171 12 6530 510 8.23 NO. AMPS NO. AMPS NO. AMPS NO. AMPS NO. AMPS NO. AMPS NO. AMPS AMPS # MILLS (FROM PANEL TO EOL) DROP (%) REMARKS NO. NO. NO. 0.028 AMPS 0.094 AMPS 0.158 AMPS 0.065 AMPS 0.086 AMPS 0.159 AMPS 0.203 AMPS CIRCUIT CIRC. FEEDER LENGTH IN FT. VOLTAGE BLDG. PANEL CIRCUIT 15cd STROBE 30cd STROBE 75cd STROBE 15cd SPEAKER/STROBE 30cd SPEAKER/STROBE 75cd SPEAKER/STROBE 110cd SPEAKER/STROBE TOTAL WIRE SIZE (CU)
STROBE SIGNAL CIRCUIT SCHEDULE
KEYNOTES:
1. PROVIDE 20A/120V DEDICATED CIRCUIT TO NEW FIRE ALARM EQUIPMENT FROM EXISTING PANEL. PROVIDE LOCK-ON DEVICE TO BREAKER HANDEL AND RED LABEL TO CIRCUIT IDENTIFICATION.
2. PROVIDE 20A/120V DEDICATED CIRCUIT TO FIRE ALARM BELL. PROVIDE LOCK-ON DEVICE TO BREAKER HANDEL AND RED LABEL TO CIRCUIT IDENTIFICATION.
3. TO HVAC UNIT FOR SHUT DOWN.
4. (1) 2-PAIR #22 EACH TELEPHONE LINE TO CENTRAL MONITOR STATION.
5. FIRE CONTROL COMMUNICATOR, SILENT KNIGHT #6820EVS.
6. TELEPHONE OUTLETS TYPE RJ-31 FOR OUTPUT TO CENTRAL MONITOR STATION.
7. ROUTE 1" UNDER GROUND CONDUIT FROM MONITOR MODULE TO DOUBLE DETECTOR CHECK VALVE (DCDA), TAMPER SWITCH LOCATED IN SITE. REFER TO SITE PLAN FOR MORE INFORMATION. COORDINATE WITH FIRE PROTECTION CONTRACTOR FOR EXACT LOCATIONS.
8. ROUTE 1" UNDER GROUND CONDUIT FROM MONITOR MODULE TO PIV TAMPER SWITCH LOCATED IN SITE. REFER TO SITE PLAN FOR MORE INFORMATION.
COORDINATE WITH FIRE PROTECTION CONTRACTOR FOR EXACT LOCATIONS.
9. INSTALL NEW TAMPER SWITCH AND FLOW SWITCH IN FIRE RISER ROOM ON FIRST FLOOR. COORDINATE WITH FIRE PROTECTION CONTRACTOR FOR EXACT LOCATIONS.
#
AMP-1 50 20.00 30.00 60.00%
Amplifier Total (Watts) Total Load (Watts) Spare Load (Watts) Spare Percentage 0 8 0 8 20.00
Appliance Summary Total Load (Watts)
AMP-1 S4(SPARE) 16 70 vrms 0 0 0 0 . Watts ft. . db ft. . Ohms AMP-1 S3(SPARE) 16 70 vrms 0 0 0 0 . Watts ft. . db ft. . Ohms AMP-1 S2 16 70 vrms 0 3 0 3 7.5 Watts 380 ft. -.05 db 30086 ft. 3.416 Ohms AMP-1 S1 16 70 vrms 0 5 0 5 12.5 Watts 490 ft. -.1 db 18052 ft. 4.405 Ohms NUMBER 14, 12) 70 VRMS) .25 Watt .5 Watt 1. Watt 2. Watt (WATTS) (FEET) (dB) (FEET) (OHMS) CIRCUIT (18, 16, (25 OR TAP TAP TAP TAP LOAD LENGTH WIRE/LOSS CKT. LENGTH RESISTANCE
PANEL GAUGE VOLTAGE SPEAKER SPEAKER SPEAKER SPEAKER CIRCUIT CIRCUIT ACTUAL ALLOWABLE CIRCUIT
SPEAKER CIRCUIT DESCRIPTION
WIRE CIRCUIT APPLIANCES QUANTITIES / TAP VALUES TOTAL ESTIMATED MAXIMUM TOTAL SPEAKER CIRCUIT LOAD CALCULATION MAXIMUM -3 dB DROP PER CIRCUIT 1 NO SCALE
FIRE ALARM RISER
ADDENDUM C 11/01/2024
PLAN CHECK
COMMENTS
11/01/2024
UP
UP
H
H
H
H
H
TS
TS
TS
24TH STREET
24TH STREET BYPASS
2101
0643
2102
WP
WP
WP
WP
WP
FAA
FACP/VECP
FADC
FATC-1
AMP-1
PIV
WP
WP WP
1 2
REFER TO STORAGE
104 ROOM FOR
CONTINUATION
2 DCDA
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
FA1.1-1
OVERALL SITE
PLAN - FIRE ALARM
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
N O R
H T
1 1/16" = 1'-0"
OVERALL SITE PLAN - FIRE ALARM
KEYNOTES:
1. ROUTE 1" UNDER GROUND CONDUIT FROM PIV TAMPER
SWITCH TO MONITOR MODULE LOCATED IN STORAGE 104
ROOM. REFER TO SHEET FA2.0-4 FOR MORE
INFORMATION.
2. ROUTE 1" UNDER GROUND CONDUIT FROM DOUBLE
DETECTOR CHECK VALCE (DCDA), TAMPER SWITCH TO
MONITOR MODULE LOCATED IN CHILDERN 112 ROOM.
REFER TO SHEET FA2.0-4 FOR MORE INFORMATION.
#
ADDENDUM C 11/01/2024
S
1 A
2 B
C
E
5 F
3 D
FIRE ALARM MASTER (FACP)
R
R
1 2
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
FA2.0-1
BASEMENT
DEMOLITION PLAN
- FIRE ALARM
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
N O R
H T
1 1/8" = 1'-0"
BASEMENT DEMOLITION PLAN - FIRE ALARM
KEYNOTES:
1. DEMOLISH EXISTING FACP WITH ALL CONDUITS WITH
WIRES AND ASSOCIATED DEVICES.
2. DEMOLISH ALL EXISTING FIRE ALARM DEVICES WITH
CONDUITS AND WIRES.
#
ADDENDUM C 11/01/2024
F
S
S
H
F
S
1 A
2 B
C
E
5 F
3 D
R
R
R
R
R
R
1 1
1 1
1 1
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
FA2.0-2
FIRST FLOOR
DEMOLITION PLAN
- FIRE ALARM
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
N
PROJECT #23008651.00
O R
H T
1 1/8" = 1'-0"
FIRST FLOOR DEMOLITION PLAN - FIRE ALARM
KEYNOTES:
1. DEMOLISH EXISTING FIRE ALARM DEVICE WITH CONDUITS
AND WIRES.
#
ADDENDUM C 11/01/2024
S
S
S
S
F
S
1 A
2 B
C
E
5 F
3 D
MECHANICAL
001
2D
001-2
001-1
2D,2N1,2S1 FROM
1st FLOOR 001-1A
TO AHU-1
1 001-2A
TO DOAS-1
1 2D
2D
2D
001-2B
2D,2N1,2S1
N1-13
S1-9
75cd
0.5W
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
FA2.0-3
BASEMENT
REMODEL PLAN
-FIRE ALARM
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
N O
PROJECT #23008651.00
R
H T
1 1/8" = 1'-0"
BASEMENT REMODEL PLAN -FIRE ALARM
KEYNOTES:
1. TO HVAC UNIT FOR SHUT DOWN.
#
ADDENDUM C 11/01/2024
H
H
H
H
H
S S S S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
F
S S S
S
S
S
S
S
S
S
S S
S
S
S
S
S
S
S
S S
S
S
EOL
S
EOL
EOL
EOL
S
S
S
S
S
S
S
S
S
F
F
F
F
F
F
F
S
MM
MM MM
CM
F
TSFS
MM MM
R
1 A
2 B
C
E
5 F
3 D
GROUP STUDY
117
CHILDREN
112
TEEN
115
MARKETPLACE
116
ADULT
118
STAFF WORKROOM
125
STUDY
114
STUDY
113
IT
124
STAFF BREAKROOM
121
AMH/SORTING
122
STAFF RR
123
OFFICE
119
FOL
112
COMMUNITY MEETING
102
THE STUDIO
110
PATIO
10 ENTRY
101
STORAGE
104
FAMILY RESTROOM
109
WELLNESS
108
PATIO
46 ALL GENDER RESTROOM
105
HALL
106
KITCHENETTE
103
JANITOR
107
STAIR TO BASEMENT
002
FAA
1 N2-4
30cd
N2-6
15cd
N2-9
S2-4
75cd
0.5W
N2-3
15cd
N2-7
15cd
N2-8
15cd
N2-2
S2-1
75cd
0.5W
N1-12
15cd
N1-11
15cd
N1-9
15cd
N1-3
30cd
N1-2
15cd
N2-1
15cd
N1-4
15cd
N1-5
S1-3
30cd
0.5W
N1-1
S1-1
30cd
0.5W
N2-12
S2-6
75cd
0.5W
N2-11
75cd
S2-2
2.0W
WP
S2-3
2.0W
WP
S1-8
2.0W
WP
S1-5
2.0W
WP
S1-2
2.0W
WP
N2-5
15cd
D
D
D
D
D
D
D
D
D
D
D D D
D
D D D
D
D
D
D
D
D D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
122-1
120-1
120-2 124-1
123-1
121-1
120-3
120-4
101-1
101-2 116-1
116-2
116-3
118-1 118-2 118-3 118-4
116-5 116-4
117-1
115-1
115-2
112-1
114-1
113-1
112-2
112-3
112-5 112-4
112-6
112-7
110-1
109-1
107-1 108-1
106-1
105-1
104-1
103-1
102-1 102-2 102-3
N1,S1
N1,S1
N1,S1
N1,S1
N1,S1
N2,S2
N2,S2
N2,S2
N2,S2
N2,S2
N2,S2
N2,S2
N2,S2
N2,S2 N2,S2
EOL-N2
L=400'-0"
FACP/VECP
FADC
2 FATC-1
D
D
N1-6
15cd
119-1
N1-7
S1-4
110cd
2.0W 2D,2N1,2S1
TO BASEMENT
N1,S1
N1,S1
N1-8
S1-6
30cd
0.5W
N1,S1
N2,S2
N2-10
S2-5
110cd
2.0W
N1-10
S1-7
30cd
0.5W
N2,S2
N2,S2
N2-13
75cd
EOL-S2
L=380'-0"
N2
N1,S1
N1,S1
N1,S1
N2,S2 EOL-N1
L=510'-0"
N1
EOL-S1
L=490'-0"
N1,S1
N1,S1
AMP-1
D
FA2.0-4
2 FOR CONTINUES
SEE DETAIL #2
ON SHEET FA2.04
103-1A
2D
120-1A 2D
112-4A
2D
108-1A
WP
2D
2D
115-2A
2D
116-1A
2D
116-5A
TO CIRCUIT
B-36
N1-14
S1-10
110cd
2.0W
N1,S1
2D
2D
5 6
REFER TO SITE PLAN
FOR CONTINUATION
6 CHILDREN
112
TO OVERHEAD
DOOR 106
2D
5 3
WP
FOR CONTINUES
SEE STORAGE 104
ROOM IN DETAIL #1
ON SHEET FA2.04
TO CIRCUIT
A-7
4 Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
FA2.0-4
FIRST FLOOR
REMODEL PLAN -
FIRE ALARM
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
N
PROJECT #23008651.00 O R
H T
1 1/8" = 1'-0"
FIRST FLOOR REMODEL PLAN - FIRE ALARM
KEYNOTES:
1. FLUSH WALL MOUNTED. ROUTE 2#16 AWG IN 1" CONDUIT
FORM FACP/VECP TO FAA.
2. PROVIDE 20A/120V DEDICATED CIRCUIT TO NEW FIRE
ALARM EQUIPMENT FROM EXISTING PANEL. PROVIDE
LOCK-ON DEVICE TO BREAKER HANDLE AND RED LABEL
TO CIRCUIT IDENTIFICATION.
3. PROVIDE 20A/120V DEDICATED CIRCUIT TO FIRE ALARM
BELL. PROVIDE LOCK-ON DEVICE TO BREAKER HANDLE
AND RED LABEL TO CIRCUIT IDENTIFICATION.
4. INSTALL NEW TAMPER SWITCH AND FLOW SWITCH IN FIRE
RISER ROOM ON FIRST FLOOR. COORDINATE WITH FIRE
PROTECTION CONTRACTOR FOR EXACT LOCATIONS.
5. ROUTE 1" UNDER GROUND CONDUIT FROM MONITOR
MODULE TO PIV TAMPER SWITCH LOCATED IN SITE.
REFER TO SITE PLAN FOR MORE INFORMATION.
COORDINATE WITH FIRE PROTECTION CONTRACTOR FOR
EXACT LOCATIONS.
6. ROUTE 1" UNDER GROUND CONDUIT FROM MONITOR
MODULE TO DOUBLE DETECTOR CHECK VALVE (DCDA),
TAMPER SWITCH LOCATED IN SITE. REFER TO SITE PLAN
FOR MORE INFORMATION. COORDINATE WITH FIRE
PROTECTION CONTRACTOR FOR EXACT LOCATIONS.
#
N O R
H T
2 1/4" = 1'-0"
ENLARGED FIRE RISER ROOM
ADDENDUM C 11/01/2024
-------
TERMINAL CABINET
FIRE ALARM
18"x18"x6" MIN.
FIRE ALARM DEVICES
TO SECOND
NAC PANEL
(WHEN APPLICABLE)
TO FACP OR NAC PANEL
FACP/VECP
60"
TO 12OV
FINISHED FLOOR
4S
BOX
AMPLIFIER
DIM: 18"x18"x6"
MAX WT: 30LBS
SEE
DIM: 15"x15"x4"
MAX WT: 40LBS
SEE
DIM: 15"x15"x4"
MAX WT: 40LBS
SEE
FA-303
8 FA-303
8 FA-303
8 -------
STROBE
DUCT
SUPPLY AIR
MINIMUM
3FT
SMOKE DETECTOR
FIRE
PULL STATION
SPEAKER-STROBE OUTDOOR
SPEAKER
48" MAX
90"
FINISHED FLOOR GRADE
OR LANDSCAPE
CEILING SPACE
JUNCTION BOX
MOUNTED IN
CEILING.
FINISH CEILING
REMOTE
ANNUNCIATOR
96" MAX
BOTTOM OF LENS NOT LESS
THAN 80" AFF AND NOT GREATER
THAN 96" AFF TO TOP OF LENS
80" MIN
CONTRACTOR TOEXTEND
THE CONDUIT STUBBED
INTO THE CEILING SPACE.
F I R E
F I R E
4S STANDARD
EXTENSION BOX
4S DEEP BOX
4S STANDARD
EXTENSION BOX
4S DEEP BOX
4S DEEP BOX
4S STANDARD
EXTENSION BOX
4S DEEP BOX
4S STANDARD
EXTENSION BOX
ADDRESSABLE SMOKE DETECTOR OR
ADDRESSABLE HEAT DETECTOR
-
+
+
-
-
+
0 1
2 3
4 ADDRESS LOOP
5 6
7 8
9 (-)
(+)
TO NEXT
ADDRESSABLE
DEVICE
DATA
OUT(+)
DATA
OUT(-)
DATA
IN
(-)
DAT
A
IN (+)
OR PREVIOUS
ADDRESSABLE
DEVICE
RETURN (-)
RETURN (+)
ZONE (-)
ZONE (+)
UNUSED
COMBINATION FIRE/SMOKE DAMPER
CFSD
MULTI
VOLTAG
E
RELAY
UNUSED
OUTPUT RELAY
CONTROL MODULE
-
+
+
-
-
+
0 1
2 3
4 ADDRESS ONES
TENS
0 1
2 3
4 5
6 7 8 9
6 7 8 9
5 4
3 2
1 10
11 12
13 14
0 15
LOOP
5 6
7 8
9 UNUSED
UNUSED
TO 24VDC
POWER
-
- +
TERMINAL 2
DATA IN (-)
DATA IN (+)
TERMINAL 1
2(+)
1(-)
3 OUT (-)
ADDRESSABLE
DEVICE
DATA
TO NEXT
INITIATING
OUT (+)
DATA
OUTPUT RELAY CONTROL MODULE
120V
POWER
R
C
UNIT SHUT-DOWN
TO AC
C
FROM FIRE
ALARM PANEL
OR PREVIOUS
ADDRESSABLE
DEVICE
9 0
6 3
5 4
7 8
2 1
3 1
2 0
4 11
8 6
4 5
7 9
1 0
3 2
15 14
13 12
8 6
5 7
10 9
-
+
NOTIFIER #FMM-1
MONITOR MODULE
FROM
PREVIOUS
ADDRESSABLE
DEVICE
TO NEXT
ADDRESSABLE
DEVICE
NC
NO
COM
EOL
TYPICAL TAMPER
SWITCH
9 0
6 3
5 4
7 8
2 1
3 1
2 0
114
8 6
4 5
7 9
1 0
3 2
15 14
13 12
8 6
5 7
10 9
-
+
NOTIFIER #FMM-1
MONITOR MODULE
FROM
PREVIOUS
ADDRESSABLE
DEVICE
TO NEXT
ADDRESSABLE
DEVICE
CONNECT TO
#FCPS-24S6 IN1(+)
CONNECT TO
#FCPS-24S6 IN1(-)
EOL
COM
COM
A BB A
9 0
6 3
5 4
7 8
2 1
3 1
2 0
114
8 6
4 5
7 9
1 0
3 2
15 14
13 12
8 6
5 7
10 9
-
+
TYPICAL WATER FLOW
SWITCH
NOTIFIER #FMM-1
MONITOR MODULE
NOTE: WATERFLOW
SWITCH CONTACTS
SHALL BE N.O. WHEN
RISER IS CHARGED WITH
WATER.
FROM
PREVIOUS
ADDRESSABLE
DEVICE
TO NEXT
ADDRESSABLE
DEVICE
MIN. CLEAR
30" X 48"
SIDE APPROACH
OR
PULL STATION
MIN. CLEAR
30" X 48"
FRONT
APPROACH
PULL STATION
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
FA3.0-1
FIRE ALARM
DETAILS
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
1 NO SCALE
TYPICAL POWER SUPPLY LAYOUT
2 NO SCALE
FIRE ALARM DEVICE ELEVATION
3 NO SCALE
CEILING MOUNT AUDIO/VISUAL DEVICE DETAIL
4 NO SCALE
WALL MOUNT AUDIO/VISUAL DEVICE DETAIL
5 NO SCALE
TYPICAL FIRE ALARM DEVICE WIRING DIAGRAM
6 NO SCALE
TAMPER SWITCH DETAIL
7 NO SCALE
SYNC CONTROL MODULE
8 NO SCALE
WATER FLOW SWITCH DETAIL
9 NO SCALE
FIRE ALARM PULL STATIONS DETAIL
ADDENDUM C 11/01/2024
MOUNT SMOKE/HEAT
DETECTOR BASE TO 4S
BOX WITH FACTORY
PROVIDED (2)
MOUNTING
SCREWS.
BASE
DETECTOR
3-O GANG
RING
DETECTOR HEAD
DATA IN (+)
TERMINAL 1
2(+)
1(-)
3 TO NEXT
ADDRESSABLE
INITIATING
DEVICE
REMOTE LED
(OPTIONAL)
DATA
OUT (+)
4S DEEP BOX
FROM FIRE
ALARM PANEL
OR PREVIOUS
ADDRESSABLE
DEVICE
DATA
OUT (-)
DATA IN (-)
TERMINAL 2
ADDRESSABLE DEVICE
OR PREVIOUS
SLC LOOP (IN)
FROM MAIN FACP
5 5 4
MONITOR MODULE
FDM-1
1 2
3 4
ADDRESSABLE DEVICE
SLC LOOP (OUT)
TO NEXT
DATA OUT (+)
12 13
14 150
DATA OUT (-)
7 9 7
7 3
6 2
1 6
4 5
6 8
0 13 2
10 11
8 9
14 150
3 8 9 10
11 12 1
DATA IN (+)
DATA IN (-)
(TAMPER SWITCH)
RESISTOR
47K EOL
RESISTOR
47K EOL
N/O CONTACT DEVICE
(WATER FLOW SWITCH)
N/O CONTACT DEVICE
(EVEN ADDRESS)
(ODD ADDRESS)
4S Deep Box
4S Extension
Module Cover
Plate
(+)
(-)
(+)
(-)
RM CM
REFER TO MANUFACTURERS'
INSTRUCTIONS FOR DETAILS
OF WIRE TERMINATIONS
SSU-RIC-1
120VAC COIL
CONTROL
RELAY MODULE
120VAC
FROM PANEL
SLC
LOOP
FOR ACTIVATION OF FIRE SPRINKLER
ALARM BELL UPON ACTIVATION OF
FIRE RISER FLOW SWITCH
FIRE SPRINKLER
BELL
APPLY TO INTERFACE WITH WALL SURFACE.
FIRE STOP SYSTEM - ONE HOUR - CAULK.
5/8" X GYPSUM BOARD PER ARCHITECTURAL.
STEEL STUDS PER ARCHITECTURAL/STRUCTURAL.
CONDUIT SIZE PER DRAWINGS.
WALL CONSTRUCTION:
KEY NOTES:
SECTION A-A
EMT OR ELECTRICAL
4" DIA. OR SMALLER
CONDUIT
MAX. DIA. OF OPENING IS 13 1/2"
BEAD IS REQUIRED.
ANNULAR SPACE OF MIN. 1/4" DIA.
U.L. SYSTEM NO. WL 1001
NOTE:
2 3.
2. B.
1-HR. FIRE RATED
GYPSUM WALL
ASSEMBLY
A
1. A.
FRONT VIEW
3 A
AT ITS EGGRESS FROM
OF FIRE STOP SEALANT
(CAULK) APPLIED TO
PERIMETER OF CONDUIT
MIN. 1/4" DIA. BEAD
WALL
1B
2 1A
3 REFER TO RESPECTIVE FLOOR PLAN
FOR
EXISTING FIRE RATED WALL LOCATION
USE THIS DETAIL WHERE OCCURS.
TEKS/3 OVER 20" OF WIDTH
USE 3 SCREWS
TOP & BOTTOM 2 #12-14x1 7/8
SOLID WASHER BETWEEN
PANEL BACK & TD.
METAL STUD BACKUP TAB
16"G METAL STUD
16"G METAL STUD
16"G METAL STUD
TEKS/3
3-#10-18x1"
A
DETAIL "A" A
WALL FINISH, GYP. BD.,
PLASTER, TILE, ETC.
PANEL OR TERMINAL CABINET
MAX WT: 150LBS
PANEL OR TERMINAL CABINET
MAX WT: 150LBS
EXISTING CONCRETE OR CMU WALL
3/8"ø x3" LONG HILTI "KB-TZ2 STAINLESS STEEL" EXPANTION ACHORS (ICC ESR 4266) AND (ICC ESR 4561 FOR MASONARY
WALL) 2 1/2" EFFECTIVE EMBEDMENT WITH FENDER WASHER
(4 TOTAL) FOR CONCRETE WALL. USE THROUGH OR TOGGLE
BOLTS IN UNGROUTED MASONRY BLOCK
B METAL STUD WALL
C CONCRETE STUD WALL
S
UNIT SHUTDOWN
1. UPON ACTIVATION OF THE NOTED AREA SMOKE DETECTOR
a) THE AREA SMOKE DETECTOR INITIATES AN ALARM CONDITION AT THE FACP b) WIRING FROM THE OUTPUT TERMINALS OF THE FACP ENERGIZES THE CONTROL MODULE ASSOCIATED WITH THE HVAC UNIT SERVING THE AREA.
UNIT SHUTDOWN TERMINALS.
c) CONTACTS IN THE CONTROL MODULE CLOSE TO ALLOW VOLTAGE TO THE HVAC
TO AC UNIT FOR SHUT-DOWN
24VDC DATA LOOP IN
24VDC DATA LOOP OUT
REFER TO MANUFACTURERS'
INSTRUCTIONS FOR DETAILS
OF WIRE TERMINATIONS
ADDRESSABLE
OUTPUT
RELAY
CONTROL
MODULE
Exp. 6-30-2025
E
L A
CTR I C
L E
Lic. E16934
ET AT S
R FO L I
OF CA
N
AI
F
D PRO ESS IONA L ENGI N
EER
REGISTERE
NESTOR C. IGNACIO, JR.
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
RC
NDEN VA
,N I N G
CRAE
EI T C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
FA3.0-2
FIRE ALARM
DETAILS
23604-01
160 PINE STREET
SUITE 350
SAN FRANCISCO, CA 94111
P: 415.541.9477
www.imegcorp.com
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #23008651.00
1 NO SCALE
SMOKE/HEAT DETECTOR BASE WIRING DETAIL
2 NO SCALE
MONITOR MODULE WIRING DETAIL
3 NO SCALE
FIRE SPRINKLER BELL WIRING
4 NO SCALE
PENETRATION THRU 1HR FIRE RATED WALL
5 NO SCALE
SURFACE MOUNTED PANEL / TERMINAL CABINET DETAILS
6 NO SCALE
HVAC SHUTDOWN
KEYNOTE REFERENCES
SCOPE OF KEYNOTES USED. **** IS A 4 DIGIT NUMBER FOLLOWING
THE PREFIX
KEYNOTE REFERENCE
AKN****
ARCHITECTURAL. CONFORM WITH WITH THE
REQUIREMENTS OF DIVISIONS 3-14. SEE
ARCHITECTURAL AND INTERIOR DRAWINGS FOR
ADDITIONAL DETAILS.
MKN****
MECHANICAL/PLUMBING. CONFORM WITH WITH THE
REQUIREMENTS OF DIVISIONS 22-23. SEE
MECHANICAL AND PLUMBING DRAWINGS FOR
ADDITIONAL INFORMATION.
EKN****
ELECTRICAL. CONFORM WITH WITH THE
REQUIREMENTS OF SPECIFICATION DIVISION 26 AND
THE FIRE ALARM SECTIONS OF DIVISION 28. SEE
ELECTRICAL AND FIRE ALARM DRAWINGS FOR
ADDITIONAL INFORMATION.
TKN****
COMMUNICATIONS AND ELECTRONIC SECURITY
SYSTEMS. CONFORM WITH WITH THE
REQUIREMENTS OF SPECIFICATION DIVISION 27 AND
THE ELECTRONIC SECURITY SECTIONS OF DIVISION
28. SEE TA, TN AND TY DRAWINGS FOR ADDITIONAL
INFORMATION.
REFER TO SPECIFICATIONS FOR COMPLETE REQUIREMENTS.
PROVIDE CONDUIT, BOXES AND FITTINGS SHOWN ON AUDIO VISUAL SYSTEMS (AV) DRAWINGS UNDER THE WORK OF SECTION 27 05 33 COMMUNICATIONS RACEWAYS, BOXES AND FITTINGS. UNLESS OTHERWISE INDICATED, PROVIDE 1 INCH TRADE SIZE MINIMUM . PROVIDE RACEWAY SIZE AS REQUIRED FOR A MAXIMUM OF 30 PERCENT WIRE FILL.
PROVIDE FIRESTOPPING UNDER THE WORK OF SECTION 27 05 33.
LOCATIONS SHOWN ON THE ARCHITECTURAL DRAWINGS TAKE PRECEDENCE OVER LOCATIONS SHOWN ON THE COMMUNICATIONS SYSTEMS DRAWINGS.
DEVICE QUANTITIES SHOWN ON FLOOR PLANS AND REFLECTED CEILING PLANS TAKE PRECEDENCE OVER DEVICE QUANTITIES SHOWN ON FUNCTIONAL DIAGRAMS.
QUANTITIES SHOWN ON FUNCTIONAL DIAGRAMS TAKE PRECEDENCE OVER QUANTITIES SHOWN ON RACK ELEVATIONS.
QUANTITIES SHOWN ON DEVICE SCHEDULES TAKE PRECEDENCE OVER QUANTITIES SHOWN ON FUNCTIONAL DIAGRAMS, FLOOR PLANS AND REFLECTED CEILING PLANS.
LOCATIONS SHOWN ON LARGE SCALE DRAWINGS TAKE PRECEDENCE OVER LOCATIONS SHOWN ON SMALL SCALE DRAWINGS.
NOT USED.
WIRING FOR THE WORK OF AUDIO VISUAL SYSTEMS IS NOT PERMITTED TO SHARE
CONDUIT, SLEEVES OR J-HOOKS WITH WIRING FOR WORK OF COMMUNICATIONS WIRES, CABLES AND RELATED. MAINTAIN AT LEAST 2 INCHES SEPARATION IF RUNNING PARALLEL. MAINTAIN AT LEAST 3 INCHES OF SEPARATION VERTICALLY IF CROSSING AT RIGHT ANGLES.
AUDIO VISUAL SYSTEMS GENERAL NOTES
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
OPP. OPPOSITE
SIM. SIMILAR
ON CENTER
NOT TO SCALE
PANEL
PROJECT
OUTSIDE DIAMETER
OWNER FURNISHED EQUIPMENT
NATIONAL ELECTRICAL CODE
NOT IN CONTRACT
REFER TO
REFERENCE
SPECIFICATION
SHEET NOTE
SURFACE RACEWAY
SINGLE MODE OPTICAL FIBER
SHIELDED PAIR - SEE SPECIFICATIONS
TELEPHONE
TYPICAL
TWISTED PAIR
TELECOMMUNICATIONS
TELECOMMUNICATIONS CLOSET
SHIELDED TWISTED PAIR
WITH
WEATHERPROOF
UNLESS OTHERWISE NOTED
TELECOMMUNICATIONS INDUSTRY ASSOCIATION
STANDARD
NEC
N.I.C.
O.D.
O.C.
NTS
O.F.E.
PROJ.
PNL.
RE:
P.S.S.H.
REF.
SP
SN
S.R.
SPEC
SMF
P.S.R.H
STP
TEL
TELCOM
T.C.
TIA
TYP.
TP
W/
WP
U.O.N.
STD
EA. EACH
C.L. CENTERLINE
ALTERNATE
AMERICANS WITH DISABILITIES ACT
ABOVE MEZZANINE FINISHED FLOOR
ABOVE FINISHED CEILING
ABOVE FINISHED FLOOR
BACK OF HOUSE
BUILDING
COMMUNICATIONS
CATEGORY
CONDUIT
BUILDING DISTRIBUTION FACILITY
BELOW FINISHED CEILING
CALIFORNIA ELECTRICAL CODE
CALIFORNIA BUILDING CODE
CONDUIT ONLY
CONTINUATION
DIVISION
EXISTING
DIAMETER
DEDUCTIVE
DEMOLISH EXISTING
COMMUNICATIONS SYSTEM
EQUIPMENT
FINISHED
ELEVATION
END OF LINE
ELECTRONIC INDUSTRIES ASSOCIATION
A.D.A.
A.F.C.
ALT
A.M.F.F.
A.F.F.
BDF
B.F.C.
B.O.H.
BLDG.
CAT.
CBC
COMM.
CEC
C.
C.O.
CONT.
CS
(D)
DIA.
(E)
EIA
DIV
DED
ELEV.
E.O.L.
FIN
EQPT.
ABBREVIATIONS
FUTURE
HOME RUN
HEIGHT
JUNCTION BOX
LOCAL AREA NETWORK
MAXIMUM
MODULAR
MINIMUM
NEW
H.R.
FUT
HT.
LAN
J, JBOX
MAX.
MOD.
MIN.
(N)
IDF INTERMEDIATE DISTRIBUTION FACILITY
MDF MAIN DISTRIBUTION FACILITY
MMF MULTI MODE OPTICAL FIBER
MPOE MINIMUM POINT OF ENTRY
OSP OUTSIDE PLANT
S.A.D. SEE ARCHITECTURAL DRAWINGS
S.E.D. SEE ELECTRICAL DRAWINGS
S.I.D. SEE INTERIORS DRAWINGS
S.M.D. SEE MECHANICAL DRAWINGS
ALL JUNCTION BOXES TO BE HINGED TYPE, PROVIDED
WITHOUT PRE-PUNCHED KNOCKOUTS. PENETRATIONS
AS REQUIRED FOR INSTALLATION. PAINT ALL INTERIOR
WITH ARCH. PLANS.
BOXES TO MATCH WALL FINISH. COORDINATE FINISH
D
4 4
(INCHES)
W
8 6
H
(INCHES)
8 6
(INCHES)
6 8
4 8
6 6
8 6
8 6
8 8
8 12
12 12
18 16
16 12
12 12
12 18
20 20
16 20
20 20
24 20
24 20
24 20
24 24
30 36 30 8
30 30 8
NOTE
IN JUNCTION BOXES SHALL BE CUT OR PUNCHED
J2
J1
SYMBOL
J3
J5
J4
J7
J8
J9
J6
J10
J12
J11
J14
J13
J15
J17
J16
SUFFIX:
JUNCTION BOX SCHEDULE
D - NEMA 4X
C - NEMA 4
B - NEMA 3R
NONE - NEMA 1
A - NEMA 12
PROJECT STANDARD RECEPTACLE HEIGHT +18" ATT, U.O.N.
PROJECT STANDARD SWITCH HEIGHT +48" AFF TO U.O.N.
NORMALLY CLOSED CONTACT
NORMALLY OPEN CONTACT
REPEAT RELAY
1/4" PHONE CONNECTOR
TYPE "F" CONNECTOR
DIN CONNECTOR, MIDI STANDARD
TRIPLE FIVE WAY BINDING POSTS
WIRING CONTINUES AS INDICATED
BNC CONNECTOR, 75 OHMS IMPEDANCE
RESISTIVE TERMINATION AT CIRCUIT
XLR CONNECTOR, 3 PIN, FEMALE; MALE
XLR CONNECTOR, 4 PIN, FEMALE; MALE
S-VIDEO CONNECTOR, MALE; FEMALE
WIRING HOME RUN AS INDICATED
SECTION QUANTITY AS REQUIRED BY CIRCUIT
FLY-ON OR FLY-OFF POINT
SCREW TERMINAL
TYPE RCA AUDIO OR VIDEO CONNECTOR, FEMALE; MALE
TUBULAR CLAMP BARRIER BLOCK, SWITCH BLOCK
TRS MINI STEREO AUDIO CONNECTOR, FEMALE; MALE.
Loudspeaker quantity
70V power tap
PRIORITY MUTE RECEIVING, ADJUSTABLE MUTE LEVEL
TRANSFORMER BALANCED, LINE INPUT MODULE,
RELAY COIL
PRIORITY MUTE GENERATING
PRIORITY MUTE GENERATING
TRANSFORMER BALANCED, LINE INPUT MODULE,
TRANSFORMER BALANCED, MIC INPUT MODULE,
Loudspeaker reference number
Loudspeaker type (See Plans
and Specifications)
SWITCH
SWITCH
NOTES: X DENOTES SEQUENCE NUMBER
MOMENTARY PUSH
PUSH BUTTON SWITCH
BUTTON SWITCH
70 WATT PRIORITY ATTENUATOR, RACK MOUNTED
AV FUNCTIONALS LEGEND
AUDIO SPEAKER CONNECTOR, FEMALE; MALE
CHARACTERISTIC IMPEDANCE
J18 36 36 8
3.7W TAP
x2
SHEET NUMBER
WALL SECTION KEY
SHEET NUMBER
DRAWING NUMBER
ELEVATION KEY
DRAWING NUMBER
SHEET NUMBER
DRAWING NUMBER
DETAIL SYMBOL
SHEET NUMBER
REVISION NUMBER
REVISION SYMBOL
BUILDING LABEL
COLUMN GRID
GRID LINES
DRAWING MATCH LINE
SHEET NUMBER
DRAWING NUMBER
ROOM NAME
ROOM NUMBER
ROOM KEY
BLDG. SECTION KEY
DRAWING NUMBER
GENERAL SYMBOLS
FOR COMMUNICATIONS AND POWER SYSTEM
NEW WIRE AND/OR CABLE INSIDE NEW CONDUIT WALLS OR IN CEILING .
PROVIDED UNDER DIV. 27.
CABLE/RACEWAY TURNS UP
CABLE/RACEWAY TURNS DOWN
AND SPECIFICATIONS.
NEW WIRE AND/OR CABLE IN EXPOSED CONDUIT
OR RACEWAY. FILL PER SCHEDULE, PLANS
MARK INDICATES RACEWAY DROP FROM CEILING.
COORDINATE EXACT LOCATION WITH DIV. 27 PLANS.
SURFACE RACEWAY.
HOME RUN
KEYNOTES
WIRING NOTES
LEGEND
SVM SVF
XM
4M
RR
XF
B
4F
D
P
*
RF RM
MF MM
M
VC-R
K
VBI
MBI
BM
ASF ASM
1 1
1 1
1 1
1 1
1 A1
1 XXXX
XXXX
1 1
1 1
701
TKN
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TA001
AV - GENERAL
NOTES, LEGEND,
SYMBOLS, ABBR
AND JBOX
SCHEDULE
Project Number
SYMBOL DEVICE FUNCTION OR SERVICE LOCATION WORK OF ROUGH-IN RACEWAY ELEVATION
CABLE FILL &
HOMERUN
DESTINATION, U.O.N.
FINISH
WEIGHT,
LB
DETAIL
SHEET(S)
WALL SLEEVE/CONDUIT PATHWAY INDICATED 27 05 33 N/A R11
ASSISTIVE LISTENING
TRANSMITTER AUDIO-VISUAL SYSTEMS CEILING 27 41 16 FLUSH 4S BOX, 1 G. RING. LRI11 R6
ANTENNA IS SURFACE
MTD TO CLG.
PER FUNCTIONAL WHITE
AV CONTROL TOUCHPANEL, WALL
MOUNTED AUDIO-VISUAL SYSTEMS INDICATED 27 41 16
PROPRIETARY MANUFACTURER
BACKBOX.
R7 +45" A.F.F. PER FUNCTIONAL WHITE N/A
AUDIOVISUAL TOUCHSCREEN
CONTROL PANEL, TOPSET AUDIO-VISUAL SYSTEMS TABLE TOP 27 41 16 USE GROMMETS FOR CABLE FEED R6 WORK SURFACE PER FUNCTIONAL WHITE 4
HIGH-CAPACITY AUDIOVISUAL
FLOORBOX AUDIO VISUAL SYSTEMS FLOOR 27 05 33
MANUFACTURER'S PROPRIETARY
BACKBOX.
R4 FLOOR
PER FUNCTIONAL
AND AS NOTED.
COORD. FLOOR
FINISH/LID W/
ARCHITECT
N/A
FLAT PANEL ROUGH-IN BOX AUDIO VISUAL SYSTEMS FLUSH IN WALL 27 05 33 FPWB (2) 1" C. FROM EACH OF
(2) LOW VOLTAGE
BACKBOXES TO
ACCESSIBLE CEILING
+62" AFF TO CL, U.O.N. WHITE 5
VIDEO TELECONFERENCE HUB:
CAMERA, MIC, SPEAKER
SOUNDBAR
AUDIO VISUAL SYSTEMS DISPLAY MTD 27 41 16 N/A N/A N/A
PER FUNCTIONAL
AND AS NOTED.
BLACK 20
FLAT DISPLAY PANEL, 55"
DIAGONAL, 16:9 ASPECT RATIO AUDIO-VISUAL SYSTEMS
FPWB IS FLUSH MTD
WALL, PANEL IS
SURFACE MOUNTED.
27 41 16 FPWB (SEE FPWB) +60" AFF TO CL, U.O.N. AS SCHEDULED BLACK 70 FLAT DISPLAY PANEL, 65"
DIAGONAL, 16:9 ASPECT RATIO AUDIO-VISUAL SYSTEMS
FPWB IS FLUSH MTD
WALL, PANEL IS
SURFACE MOUNTED.
27 41 16 FPWB (SEE FPWB) +63" AFF TO CL, U.O.N. AS SCHEDULED BLACK 125 FLAT DISPLAY PANEL, 75"
DIAGONAL, 16:9 ASPECT RATIO AUDIO-VISUAL SYSTEMS
FPWB IS FLUSH MTD
WALL, PANEL IS
SURFACE MOUNTED.
27 41 16 FPWB (SEE FPWB) +66" AFF TO CL, U.O.N. AS SCHEDULED BLACK 175 FLAT DISPLAY PANEL, 90"
DIAGONAL, 16:9 ASPECT RATIO AUDIO-VISUAL SYSTEMS
FPWB IS FLUSH MTD
WALL, PANEL IS
SURFACE MOUNTED.
27 41 16 FPWB (SEE FPWB) +69" AFF TO CL, U.O.N. AS SCHEDULED BLACK 225
WALL PLATE PRESENTER INPUT AUDIO-VISUAL SYSTEMS
INDICATED, FLUSH
MOUNTED TO WALL OR
TO FLOORBOX INTERIOR.
27 41 16
AT WALL, 4-11/16 S WITH 1 GANG
RING, 2-1/8" DEEP.
R7 +45" A.F.F. PER FUNCTIONAL WHITE N/A
AUDIOVISUAL EQUIPMENT RACK,
SLIDE-OUT, FULL HEIGHT AUDIO-VISUAL SYSTEMS INDICATED 27 11 16 J3 (SEE TA0.1-0) R2 FLOOR
PER FUNCTIONAL
AND AS NOTED.
BLACK 500
LOUDSPEAKER, CEILING, HARD
LID AUDIO-VISUAL SYSTEMS CEILING 27 41 16
1G BOX W/ 1G RING AT
UNDERSIDE OF DECK
R5 FLUSH IN CEILING PER FUNCTIONAL WHITE 10
LOUDSPEAKER, PENDANT AUDIO-VISUAL SYSTEMS CEILING 27 41 16 1G BOX W/ 1G RING AT
UNDERSIDE OF DECK
R5 CEILING PER FUNCTIONAL WHITE 14
LOUDSPEAKER, CEILING, LAY-IN AUDIO-VISUAL SYSTEMS CEILING 27 41 16 1G BOX W/ 1G RING AT
UNDERSIDE OF DECK
R5 FLUSH IN CEILING PER FUNCTIONAL WHITE 10
WALL PLATE, USB AUDIO-VISUAL SYSTEMS
INDICATED, FLUSH
MOUNTED TO WALL OR
TO FLOORBOX INTERIOR.
27 41 16
AT WALL, 4-11/16 S WITH 1 GANG
RING, 2-1/8" DEEP.
R7 +45" A.F.F. PER FUNCTIONAL WHITE N/A
WIRELESS MIC RECEIVER AUDIO-VISUAL SYSTEMS CEILING 27 41 16 FLUSH 4S BOX, 1 G. RING. LRI11 R5 SURFACE MTD TO CLG. PER FUNCTIONAL WHITE 1 SA
A
CTW
CTP
SP
SC
HUB
FC6
.
FPNL90
.
FPNL75
.
FPNL65
.
FPNL55
FPWB
.
W
MP1
R35
USB
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TA002
AV - SYMBOL
SCHEDULE
Project Number
NOTE NO. DEVICE NOTES
DN1
FIRE ALERT LIGHTING ROUGH-IN PROVIDES DAISY
CHAINED UTP6-4P BETWEEN OFE CONTROLLER AND
THE WALL PLATES IN EACH LIGHTING ZONE. ZONE
INDICATED BY SINGLE NUMBER SUBSCRIPT., L1
INDICATES END-OF-LINE AND WAO HAS 1 JACK AND 1
UTP6-4P; L2 INDICATES WAO IS PART OF DAISY CHAIN
CKT AND HAS 2 JACKS AND ONE ENTERING AND ONE
EXITING UTP4-4P – REFER TO SINGLE LINE DIAGRAM.
WORK OF NOTES
WO1
PROVIDE CABLING AND ROUGH-IN UNDER WORK OF
PROJECT – LIGHTING FIXTURE PROVIDED BY OWNER’S
CONTRACTOR (N.I.C}..
LOCATION & ROUGH-IN NOTES
LRI1
INSTALLED ASSEMBLY, INCLUDING MONITOR SHALL NOT
PROJECT MORE THAN 4" FROM FACE OF WALL. IF
LEADING EDGE 27" TO 80" AFF
LRI2 MATCH PROJECT SWITCH HEIGHT
LRI3 4S BOX W/ 1 GANG RING BLANK COVER PLATE
LRI4
WHERE COVER PLATES OCCUR IN GYPSUM BOARD
PARTITIONS, COVER PLATE TO BE WHITE PLASTIC.
WHERE COVER PLATES OCCUR IN WOOD, SOLID
SURFACE, OR FABRIC-PANEL FINISHES, COVER PLATE IS
TO BE BRUSHED STAINLESS STEEL.
LRI5 NOT USED
LRI6 NOT USED
LRI7 MANUFACTURER'S VENTED BACKBOX .
LRI8 NOT USED
LRI9
4S BOX, 2-1/8" DEEP MIN., W/ 1 GANG RING WITH LOCKING
HINGED COVER PLATE (FSR WB-MR2G OR EQUAL).
LRI10 NOT USED
LRI11 PROVIDE BACKING AND SUPPORT FOR 5 POUND DEVICE.
LRI12
PROVIDE DEVICE COMPLETE WITH BACKBOX, TILE
SUPPORT RAILS AND CEILING CUTOUT TEMPLATE.
COMPLY WITH SECTION 09 50 11 ACOUSTICAL PANEL
CEILINGS.
LRI13
PROVIDE BACKING IN WALL SUITABLE TO SUPPORT A 20
POUND DEVICE WITH A LOAD CENTROID 18 INCHES
FROM THE FACE OF THE WALL.
LRI14
PROVIDE BACKING IN WALL SUITABLE TO SUPPORT A 200
POUND DEVICE WITH A LOAD CENTROID 8 INCHES FROM
THE FACE OF THE WALL.
LRI15
AS DETAILED AND/OR SCHEDULED ON THE
ARCHITECTURAL DRAWINGS.
RACEWAY NOTES
R1 NOT USED
R2 NOT USED
R3 NOT USED
R4 AS DETAILED AND/OR SCHEDULED
R5
3/4" C. H.R. TO ACCESSIBLE CEILING OR FLOOR, OR TO
SERVING BDF, IDF OR EQUIPMENT ROOM, U.O.N.
R6
1" C. H.R. TO ACCESSIBLE CEILING OR FLOOR, OR TO
SERVING BDF, IDF OR EQUIPMENT ROOM, U.O.N.
R7
1-1/4" C. H.R. TO ACCESSIBLE CEILING OR FLOOR, OR TO
SERVING BDF, IDF OR EQUIPMENT ROOM, U.O.N.
R8 NOT USED
R9
AT ACCESSIBLE CEILING, PROVIDE ABOVE CEILNG
PATHWAY USING CABLE HOOKS. WHERE MOUNTED IN
GYP CEILING, EXTEND 3/4" C. TO ACCESSIBLE CEILING.
R10
2 1-1/4" C TO 4 GANG COMPARTMENT, 1 - 1" TO 1 GANG
COMPARTMENT, STUBBED TO ACCESSIBLE CEILING OR
FLOOR EXTEND TO SERVER ROOM USING BASKET TRAY.
SEE ELECTRICAL DRAWINGS FOR ELECTRICAL ROUGH-IN.
R11
UNLESS OTHERWISE SHOWN, PROVIDE 1.5" EMT SLEEVE,
WITH INSULATED THROAT BUSHING AT EACH END,
STUBBED OUT 4 INCHES FROM FACE OF WALL, AT
ELEVATION APPROXIMATELY 6 INCHES ABOVE
ACCESSIBLE CEILING. INSTALL SLEEVE IN AN
ACCESSIBLE LOCATION AS DEFINED IN CALIFORNIA
ELECTRICAL CODE, ARTICLE 100 DEFINITIONS. PROVIDE
FIRESTOPPING UNDER WORK OF SECTION 27 05 33.
BOND TO GROUND. COMPLY WITH DIVISION 26 AND
SECTION 27 05 26 GROUNDING.
R12
4 1-1/4" C TO 6 GANG COMPARTMENT, 1 - 1.25" TO EA. 1
GANG COMPARTMENT, STUBBED TO ACCESSIBLE
CEILING OR FLOOR, EXTEND TO SERVER ROOM IN
BASKET TRAY. SEE ELECTRICAL DRAWINGS FOR
ELECTRICAL ROUGH-IN TO 3 GANG COMPARTMENT.
ACCESSIBLE CEILING IS A T-BAR OR SIMILAR GRID
BASED, PANELIZED REMOVEABLE CEILING MEETING THE
DEFINITION FOR ACCESSIBLE WIRING METHODS IN
ARTICLE 100 OF THE CALIFORNIA ELECTRICAL CODE.
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TA003
AV - SYMBOL
SCHEDULE NOTES
Project Number
UP
UP
JLD JLD
JLD JLD
JLD JLD
JLD JLD
JLD
YLD YLD
ALD ALD
AANEW NEW
AANEW NEW
AADVD DVD
AAAAUDIO UDIO
AADVD DVD
JJDVD DVD
JAUDIO
ALD ALD
DVOICE DVOICE
FC3
FC3
FC3
FC3
FC3
FC6
FPNL55
MP1USB
HUB
FPNL55
USBMP1
HUB
FPNL75
MP1
FPNL65
HUB
FPNL55
FPNL90 FPNL90
MP1
CTP
CTW
MP1
FC3
FC3
FC3
MP1
USB
FC3FC3
USB
11 AA
22 BB
CC
EE
5 FF
33 DD
OPEN TO
BELOW
STORAGE
104
HALL
106
ALL GENDER
RESTROOM
105
FOL
112
PATIO
10 CHILDREN
112
STUDY
113
STUDY
114
GROUP
STUDY
117
TEEN
115
MARKETPLACE
116
ADULT
118
STAFF
WORKROOM
125
OFFICE
119
STAFF
BREAKROOM
121
STAFF RR
123
IT
124
AMH/SORTING
122
ENTRY
101
119
STAFF
WORKROOM
125
PATIO
46 121
101B
007
113
114
117
005
004
101
COMMUNITY
MEETING
102
THE STUDIO
110
WELLNESS
108
FAMILY
RESTROOM
109
JANITOR
107
109
108
107
44 002
105
104
102B
102
102A
006
LINE OF SOFFIT ABOVE
LINE OF SOFFIT ABOVE
LINE OF SOFFIT ABOVE
106
120
124
123
116B
116A
103
KITCHENETTE
103
101A
003
2307 WHISPER
ROOM (E)
1043
1043
009
008
STOWABLE
PRESENTATION
LECTERN
R35
FPWB FPWB
FPWB
FPWB
FPWB
FPWB FPWB B IUEI HU 9
AS.OAFRANCN
4 0 8 0
HINS
L11
ALER C
NDE N VA
,N I N G
CRAE
I T
E
C
T
SCSNN
G R O U P
7 S
5 06C
07 18
2PRA
O
90 A
EUC+
ER 4
SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
N
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TA201
AV - FIRST FLOOR
PLAN
Project Number
1/8" = 1'-0"
1 AV - FIRST FLOOR PLAN
BID RFI 09/24/2024
SC
SC
SC
SC
SA SA SA SA
SA SA SA SA
A W
SA
SA
SP SP SP SP
SP SP
SA
SA
SA
SA
SA
SA
SA
SP SP
SC
SA
SA
1 1
A
2 2
B
C
E
5 5
F
3 3
D
OPEN TO ABOVE
9' - 0"
8' - 8 1/8"
8' - 8 1/8"
8' - 8 1/8"
9' - 0"
8' - 11 7/8"
8' - 6 3/4"
8' - 11 7/8"
8' - 11 7/8"
COMMUNITY
MEETING
CHILDREN
THE STUDIO
STUDY
STUDY
GROUP
STUDY
STORAGE
WELLNESS
FAMILY
RESTROOM
ALL GENDER
RESTROOM HALL
FOL
MARKETPLACE
TEEN
ADULT
STAFF
BREAKROOM
STAFF RR
IT
AMH/SORTING
STAFF
WORKROOM
STAFF
WORKROOM
OFFICE
ENTRY
JANITOR
KITCHENETTE
4 4
0939
9' - 1 3/8"
7' - 6"
9' - 1 3/8"
9' - 1 3/8"
9' - 0"
9' - 1"
0123
ACT-1
ACT-1
ACT-1
T-1
T-1
T-1
G-1
G-1
G-1
W-1
W-1
W-1
W-1
T-1
G-1
G-1
ACT-1
ACT-1
ACT-1
ACT-1
ACC-2
?
?
ACC-2
?
?
8' - 0"
8' - 0"
7' - 6" 8' - 0"
7' - 6"
G-1
G-1
G-1
G-1
G-1
ACT-1
9' - 0 3/8"
9' - 1 3/8"
9' - 1 3/8"
G-1
2602
2602
2602 2602
2602
2602
2602
2602
2602
1058 2602
2602
2602
2602
2602
2602
2602
2602
2602
2602
2304
2602
2304
2304
2602
2304
2304
2304
2602
2602
ACC-2
G-1
8' - 8 1/8"
8' - 6 3/4"
8' - 6 3/4"
8' - 6 3/4"
0560
8' - 0" 8' - 0" 8' - 0" 7' - 0" 7' - 10 1/2" 7' - 8 5/8" 8' - 0" 8' - 0" 6' - 10" 8' - 0" 8' - 0" 8' - 0" 6' - 10"
8' - 0" 7' - 0"
8' - 0" 8' - 0" 8' - 0" 8' - 0"
8' - 0" 8' - 0"
5' - 8 1/2" 8' - 0" 8' - 0" 8' - 0" 8' - 0" 6' - 7 1/2" 10' - 0" 8' - 0" 8' - 0"
8' - 0"
8' - 0" 8' - 0" 8' - 0" 8' - 0" 8' - 0" 7' - 0"
6' - 6" 8' - 0"
ALT. D-03: ACT-1 @ MARKETPLACE,
TEEN, AND ADULT SOFFT
W-1
W-1
W-1
G-1
8' - 0"
0560
0560
0560
0560
0560
0560
0560
C
NEW ENLARGED
DRAWING DRAWING
C
NEW ENLARGED
DRAWING DRAWING
7' - 6"
2602
TKN3001
TKN3001 TKN3001
TKN3002
TKN3002
TKN3002
TKN3002
TKN3002
TKN3002
ZONE 3
ZONE 2
ZONE 1
ZONE 4
ZONE 1
ZONE 5
B
B
B
B
B
B
PTZ TKN0907
PTZ B
B
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
R C
NDE N VA
,N I N G
CRAE
I T E C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
N
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TA601
AV - FIRST FLOOR
RCP
Project Number
1/8" = 1'-0" 1
AV - FIRST FLOOR RCP
KEYNOTES
TKN0907 BID ALT ONLY: SECOND PTZ CAMERA FOR BROWN
ACT.
TKN3001 H.R. TO RACK R33
TKN3002 ZONED PUBLIC ADDRESS LOUDSPEAKER, H.R.TO
PA AMPLIFIER, RACK R33, TYP.
BID RFI 09/24/2024
B
HDMI IN 1
AUDIO
OUT
WALL FPWB WALL
HDMI IN 2
HDMI IN HDMI
OUT
O.F.C.I. SIGNAGE
APPLIANCE
IP IN
LCD (SIZE VARIES, SEE
PLANS)
COORDINATE FINAL
CONNECTION TO
NETWORK WITH
LIBRARY I.T.
REPRESENTATIVE
CAT6 HDMI
LCD (SIZE VARIES, SEE PLANS)
WPS
HDMI
HUB
AUDIO IN
2SP
USB
FPWB WALL
USB
(COORDINATE CONNECTION TO
NETWORK AND CONFIGURATION
OF WIRED SUBNET AND CABLE
SCHEDULE W/ LIBRARY IT
REPRESENTATIVES) CAT.6
BEHIND DISPLAY CEILING
RDL ALS-TX ALS ANT
RG6
HDMI IN
HDMI
OUT
DMRX
DM IN
LCD (SIZE VARIES, SEE PLAN)
DM HDMI
WALL FPWB WALL
MP1
HDMI
MP1
HDMI
USB
USB-X
1 TYPICAL DIGITAL SIGNAGE
FUNCTIONAL DIAGRAM
NTS
2 TYPICAL GROUP STUDY
AUDIOVISUAL FUNCTIONAL DIAGRAM
NTS
3 TEEN
AUDIOVISUAL FUNCTIONAL DIAGRAM
NTS
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
R C
NDE N VA
,N I N G
CRAE
I T E C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TA701
DIGITAL SIGNAGE
AND GROUP
STUDY AV
FUNCTIONAL
DIAGRAMS
Project Number
BID RFI 09/24/2024
B
STOWABLE LECTERN (BY OTHERS) RACK R35
AVSW 16x16
DM IN
1 1 DM OUT
2 CONTROL
HDMI
IN
RS232
HDMI
OUT
RS232
DM IN
DMRX
LCD90
HDMI
IN
RS232
HDMI
OUT
RS232
DM IN
DMRX
CAT 6
HDMI
RS232
HDMI
2 1
2 AUDIO OUT
FPWB
FPWB
WMIC (HANDHELD &
LAVALIER)
STOWABLE (x2 EA)
CEILING
STOWABLE
H1
A11
HDMI IN AUDIO IN
A12
AV LAN
RS232
NSW
WALL
DMRX
RS232
LCD90
A9
A10
(TO DSP
SEE TA708)
AV
LAN
PROVIDE CONTROL CONNECTION
TO MUTE PA IN EVENT OF FIRE
ALARM. PROVIDE CONTROL WIRING
FROM AV CONTROL PROCESSOR TO
FIRE ALARM CONTROL PANEL. FINAL
CONNECTION TO FA PANEL BY FA
CONTRACTOR
SP
1 WALL (TYP. FOR 2 LOCATIONS)
HDMI IN
HDDA2
HDMI
HDMI
HDSDI
HDC1
HDMI
HDMI USB
HDC2
U1
USB
HDSDI H1
PTZ
CTL
AV
LAN
CAT6
RG6
WALL
HDMI HDMI
AV
LAN
U1
FC6
CTP
MP1
HDMI
USB
RJ45
HDMI
USB
USB HDMI
CAT6
USB-X
WALL
CTW
AV
LAN
USB
MP1
HDMI
WMIC ANT. (W)
WMIC ANT
DIST. WMIC REC 1 A1
WMIC REC 1 A2
RG6 RG6 2SP
CAT 6
CAT 6
CAT 6
1 2
2SP
1 2
AUDIO OUT
AUDIO IN
1 2
3 4
DSP
A1
A2
5 6
7 8
9 10
A9
A10
400
PA70
#14 AWG
ALS
ANT (A)
ALS-TX
RG6
3 A11
4 A12
CEILING
CONTROL
AV
LAN
2SP
1 COMMUNITY ROOM AUDIOVISUAL
FUNCTIONAL DIAGRAM
NTS
(AS OCCUR, SEE RCP)
SA/SC SA/SC
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
R C
NDE N VA
,N I N G
CRAE
I T E C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TA702
MEETING ROOM
AUDIOVISUAL
FUNCTIONAL
DIAGRAM
Project Number
BID RFI 09/24/2024
STOWABLE LECTERN (BY OTHERS) RACK R35
AVSW 16x16
DM IN
1 1 DM OUT
2 CONTROL
HDMI
IN
RS232
HDMI
OUT
RS232
DM IN
DMRX
LCD90
HDMI
IN
RS232
HDMI
OUT
RS232
DM IN
DMRX
CAT 6
HDMI
RS232
HDMI
2 1
2 AUDIO OUT
FPWB
FPWB
STOWABLE
WMIC (HANDHELD &
LAVALIER)
STOWABLE
CEILING
STOWABLE
WGMIC (x6)
H2 (FROM RECORDER,
SEE BELOW)
A11
HDMI IN AUDIO IN
A12
AV LAN
NVR
C1
HDMI OUT H2
NSW
RS232
H1 HDMI IN
WALL
DMRX
RS232
LCD90
1 H1
HDMI OUT
(TO RECORDER,
SEE BELOW)
A9
A10
AV
LAN
PROVIDE CONTROL CONNECTION
TO MUTE PA IN EVENT OF FIRE
ALARM. PROVIDE CONTROL WIRING
FROM AV CONTROL PROCESSOR TO
FIRE ALARM CONTROL PANEL. FINAL
CONNECTION TO FA PANEL BY FA
CONTRACTOR
SP
H3
H4
1 2
3 WALL (TYP FOR 2 LOCATIONS)
HDMI IN
HDDA2
HDMI
HDMI
HDSDI
HDC1
HDMI
HDMI USB
HDC2
U2
USB
HDSDI H4
PTZ
CTL
AV
LAN
CAT6
RG6
WALL
USB
OFE CPU
USB
RJ45
USB-X
USB
U1
CAT6
USB
H3
HDMI HDMI
HDMI
AV
LAN
U1
FC6
CTP
MP1
HDMI
USB
RJ45
HDMI
USB
USB HDMI
CAT6
USB-X
WALL
CTW
AV
LAN
USB
MP1
HDMI
(FROM CPU, SEE
BELOW)
H5 4
1 2
CAT 6
CAT 6
CAT 6
WMIC ANT. (W)
WMIC ANT
DIST. WMIC REC 1 A1
WMIC REC 2 A2
WMIC REC 3 A3
WMIC REC 4 A4
WMIC REC 5 A5
WMIC REC 6 A6
WMIC REC 7 A7
WMIC REC 8 A8
U2
U3
RG6 RG6 2SP
2SP
1 2
AUDIO OUT
AUDIO IN
1 2
3 4
DSP
A1
A2
A3
A4
5 6
A5
A6
7 8
A7
A8
9 10
A9
A10
400
PA70
#14 AWG
ALS
ANT (A)
ALS-TX
RG6
2SP
3 A11
4 A12
CEILING
CONTROL
AV
LAN
(x2) (x2)
H5
U3
1 COMMUNITY ROOM W/ BROWN ACT (BID ALT)
AUDIOVISUAL FUNCTIONAL DIAGRAM
NTS
(AS OCCUR, SEE RCP)
SA/SC SA/SC
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
R C
NDE N VA
,N I N G
CRAE
I T E C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TA703
COMMUNITY ROOM
W/ BROWN ACT
(BID ALT) AV
FUNCTIONAL
DIAGRAM
Project Number
BID RFI 09/24/2024
B
BLDG
LAN
1 PUBLIC ADDRESS
FUNCTIONAL DIAGRAM
NTS
(AS OCCUR, SEE RCP)
ZONE 1
ZONE 2
ZONE 3
PA-AMP8
IP
70V OUT
#12AWG
PA-AMP8
IP
LINE OUT
NSW
2SP
UTP6-4
PA-VOIP
H.R. TO NEAREST IDF,
COORDINATE
CONNECTION TO O.F.
VOIP SYSTEM W/
LIBRARY I.T.
REPRESENTATIVE
RACK R35
UTP6-4
UTP6-4
PA-MIR
1 2 3
(AS OCCUR, SEE RCP)
(AS OCCUR, SEE RCP)
COMMUNITY ROOM DSP, RACK R35
SA/SC/SP
SA/SC/SP
SA/SC/SP
UTP6-4
CEILING
ZONE 5
ZONE 4
#12AWG
4 5
(AS OCCUR, SEE RCP)
(AS OCCUR, SEE RCP)
SA/SC/SP
SA/SC/SP
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
R C
NDE N VA
,N I N G
CRAE
I T E C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TA704
PUBLIC ADDRESS
FUNCTIONAL
DIAGRAM
Project Number
BID RFI 09/24/2024
B
TKN6
AKN1
EKN1
AKN2
TKN5
AKN3
AKN4 AKN4
AREA
CABLE SERVICE
KO CENTER DIMENSIONS ARE TYPICAL FOR SIDE AND BOTTOM UNLESS OTHERWISE NOTED 1C PLAN VIEW
NTS
1C
-
1B
-
1B SIDE VIEW
NTS
1A SIDE VIEW
NTS
1 FC6 FLOOR BOX -
SLAB ON GRADE CONDITION
NTS
1 15/16"
1 3/4"
DOOR OPENING
1 1/4" - 1"
CONDUIT KNOCKOUT TYPICAL FOR 2 SIDES
1"
4 3/8"
135°
3 3/4"
3 3/4"
CL
KO
C
KO
L
KO
ONLY
CL
SIDE
ONLY
KO
CL
SIDE
CL
KO
KO
CL
KO
CL
DIVIDER PLATE
DIVIDER PLATE
2 1/8"
3"
3"
13 1/2"
CL
KO
KOCL
1 3/4"
2 7/8"
6" 3 1/2"
2 7/16"
3 1/8"
2 7/16"
1 1/8"
11 3/4"
DOOR
OPENING
4 1/2"
CL
KO
4 1/2"
2 1/4"
11 1/2"
2 7/8"
12"
1 3/4"
KO CL
6 1/4"
FRONT OF BOX
CONDUIT KNOCKOUT
TYP. FOR 10
1 1/4" - 1"
X
1/8"
2 1/2"
2 3/4"
CONDUIT KNOCKOUT
3/4" - 1/2"
TYP. FOR 4
11 3/4"
14" 6 3/4"
12 1/2"
NOTE: FLOOR BOX HAS
FOUR KO'S ON BOTTOM.
3 1/4"
X = 4 OR 6 INCH
DEEP BASE
COMMUNICATIONS SYSTEMS: CONFORM WITH DIVISION 27
AND 28.
NOT USED.
NOT USED.
NOT USED.
NOT USED.
BOX ACCEPTS 2-1/8" DEEP MIN. DEVICES.
CLASS 1/CLASS 2 BARRIER.
ARCHITECTURAL: DIVISIONS 3 THROUGH 14.
SLAB - SEE ARCHITECTURAL AND STRUCTURAL DRAWINGS.
SAND BASE - SEE ARCHITECTURAL AND STRUCTURAL
DRAWINGS.
MOISTURE BARRIER - SEE ARCHITECTURAL AND
STRUCTURAL DRAWINGS.
CARPET OR SCHEDULED FOOR FINISH. SEE ARCHITECTURAL
DRAWINGS - EXTEND OVER FLOOR BOX INTO INSERTS.
ELECTRICAL: DIVISION 26.
QUAD ELECTRICAL POWER - SEE ELECTRICAL DRAWINGS.
CONTRACTOR TO CONTACT FLOOR BOX MANUFACTURER
FOR INSTALLATION INSTRUCTIONS PRIOR TO ROUGH-IN.
1. AKN
AKN1
AKN2
AKN3
AKN4
EKN
EKN1
TKN
TKN1
TKN2
TKN3
TKN4
TKN5
TKN6
KEYNOTES
SHEET NOTES
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TA901
DETAILS - FLOOR
BOX
Project Number
(4) 3/8"X3" DIA LAG
SCREWS INTO BLOCKING
(E) POLYWOOD FLOOR
ADD 3X BLOCKING AT
ANCHORS
BLOCKING TO MATCH
GAUGE OF WALL STUDS
16GA BENT PL X 6" LONG
METAL STUD WALL BEYOND
(2) #10 SMS TYP
(2) #10 SMS TYP
47.5 [1207] TO 48.5 [1232]
FRAME ROLL OUT "F"
83.125 [2111]
OVERALL HEIGHT
HOST CABINET
USEABLE RACKING
MRK-4426AXS-Z4
MODEL NO
41 x 1.75 = 71.75
HEIGHT "URH"
OVERALL DEPTH
22 [559] *
OVERALL WIDTH
HOST CABINET
"A" "B"
26.4 [671]
HOST CABINET
"C"
20 [508]
FRAME DEPTH "D"
1.5 [38]
SETBACK "E" **
MINIMUM RAIL
** MINIMUM RAIL SETBACK SHOWN. MAXIMUM RAIL SETBACK IS 2.5 [64] * SIDE PANELS ADD .625 [15,9] TO EACH SIDE WHERE APPLICABLE
SEE DETAIL
TKN6
TKN2
TKN1
3B
_
TKN12
TKN12
TKN6
TKN8
TKN9
TKN2
TKN7
5A
_
TKN5 TKN4
TKN3
TKN1
TKN1 TKN2
TKN2
TKN1
TKN2
_
1A
TYP AT 4 CORNERS
400#
TKN13 TKN13
TKN3
TKN4
TKN1
TKN2
1 11/16"
[42.35]
"URH"
"A"
"F"
150°
MAX
"B"
"D"
"C"
19.125
[486]
2'-0 3/8"
[619.77]
1'-8 13/16"
[528.33]
"E"
2'-0 5/16"
[616.87]
8X 7/16"
[11.10]
1'-5 1/8"
[434.98]
1'-7 7/8"
[504.83]
1'-9 1/2"
[546.26]
TKN11
TKN10
TKN10
TKN14
4 RACK ANCHORAGE DETAILS
NTS
3 MOVEABLE STORAGE FRAME RESTRAINT
NTS
3A PICTORIAL, REAR VIEW
NTS
1A FRONT VIEW
NTS 1B SIDE - FULLY EXTENDEDNTS
1C TOP - OPEN POSITION SHOWN
NTS
1D BOTTOM - CLOSED POSITION SHOWN
NTS
1 SLIDING RACK SYSTEM, FIXED ENCLOSURE
NTS
NTS
2 SLIDING RACK SYSTEM - PICTORIAL
NTS
2A
CLOSED
(OPERATING) POSITION
NTS 2B
OPEN
(SERVICE) POSITION
NTS 3B
FASTENING DETAIL
NTS
5 SEISMIC BRACKET INSTALLATION
NTS
5B
RACK INSIDE CORNER
TYP 4 CORNERS
NTS
5A
PLAN VIEW
TYP 4 CORNERS
NTS
KEYNOTES
TKN TELECOMMUNICATIONS SYSTEMS: WORK OF DIV 27.
FIXED STEEL HOST ENCLOSURE.
MOVEABLE EQUIPMENT RACK FRAME (MOVEABLE
STORAGE SHELF). THE MOVEABLE EQUIPMENT FRAME
SHALL BE IN THE CLOSED AND FASTENED POSITION
WHEN THE ADJACENT SPACE IS OPEN FOR PUBLIC USE.
THE MOVEABLE FRAME SHALL BE OPENED, CLOSED AND
FASTENED ONLY BY QUALIFIED PERSONS FOLLOWING
THE MANUFACTURER'S INSTRUCTIONS.
ARTICULATING CABLE CARRIERS.
PORTABLE SERVICE TRACK FOR USE ONLY BY
QUALIFIED PERSON TO MOVE THE MOVEABLE STORAGE
FRAME TO THE OPEN POSITION.
PORTABLE SERVICE TRACK LEVELER FOR USE ONLY BY
QUALIFIED PERSON TO MOVE THE MOVEABLE STORAGE
FRAME TO THE OPEN POSITION.
RACK RAIL BRACKET OF HOST ENCLOSURE, 4 PER SIDE,
8 TOTAL
BRACKET, PART NUMBER PMRKSLS(HH), WHERE "HH"
SUFFIX IS THE HEIGHT OF THE STEEL HOST ENCLOSURE
IN INCHES.
BRACKET PART NUMBER PMRKSLS(HH) IS SECURED TO
THE STEEL HOST ENCLOSURE USING 4 EACH 1/4-20X5/8
BOLTS, ASTM 307 AND 4 EACH 1/4-20 CLIP NUTS PER
SIDE, 8 BOLTS AND 8 NUTS TOTAL.
IN THE CLOSED (OPERATING) POSITION, THE MOVEABLE
EQUIPMENT RACK FRAME (MOVEABLE STORAGE SHELF)
IS FASTENED TO THE BRACKET, PART NUMBER
PMRKSLS(HH) USING 3 EACH 1/4-20X5/8 BOLTS, ASTM 307
AND 3 EACH 1/4-20 CLIP NUTS PER SIDE, 6 BOLTS AND 6
NUTS TOTAL. THE LOCATIONS FOR THE CLIP NUTS ON
THE BRACKETS ARE THE 3RD AND 18 HOLE DOWN FROM
THE TOP AND THE 4TH HOLE UP FROM THE BOTTOM.
PROVIDE SEISMIC BRACKET MRK-Z4 SERIES INSTALLED
TIGHT AT EACH CORNER OF THE STEEL HOST
ENCLOSURE FRAME. THE LEVELING FOOT RIV-NUT IN
THE CORNER OF THE FRAME SHALL NOT BE REMOVED.
TIGHTEN THE FLOOR ANCHOR TO THE
MANUFACTURER'S SPECIFIED TORQUE. DEFLECTION
WILL OCCUR AROUND THE RIV-NUT, THIS IS REQUIRED;
IT PRE-LOADS THE CORNER IN COMPRESSION.
KNOCKOUT PLATES SHALL NOT BE REMOVED.
ASSUMED LOAD CENTROID FOR COMMUNICATIONS
SYSTEM AND AUDIO VISUAL SYSTEM ELECTRONICS,
ALLOW 400 POUNDS TOTAL LOAD FASTENED TO THE
MOVEABLE EQUIPMENT RACK FRAME. DEVICES WITH
WEIGHT OF LESS THAN 10 POUNDS PER RACK UNIT (1
RACK UNIT = 1.75 INCHES VERTICAL PANEL HEIGHT)
SHALL BE FASTENED TO THE MOVEABLE EQUIPMENT
RACK FRAME FRONT RAIL WITH 4 EACH 10-32 MACHINE
SCREWS. DEVICES WITH WEIGHT OF 10 POUNDS PER
RACK UNIT OR MORE SHALL BE FASTENED TO THE
MOVEABLE EQUIPMENT RACK FRAME AT BOTH FRONT
AND REAR RACK RAILS WITH AT LEAST 8 EACH 10-32
MACHINE SCREWS.
CONTRACTOR TO PROVIDE AND SUBMIT RACK SUPPORT
DETAILS. REFER TO SPECIFICATION SECTION 27 05 29
AND 27 41 16.
SEE DETAIL 4 FOR FASTENER TYPE AND QTY.
TKN1
TKN2
TKN3
TKN4
TKN5
TKN6
TKN7
TKN8
TKN9
TKN2
TKN10
TKN11
TKN12
TKN13
TKN14
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TA902
DETAILS - RACK
R35
Project Number
BLOCK-OFF PANEL (3 INCLUDED)
WITH GROMMET (1 INCLUDED)
AC OUTLET BOX
(1 INCLUDED)
LOW-VOLTAGE ENTRY
BOX (1 INCLUDED)
CL
(8) 1/2" KNOCKOUTS
1" & 1-1/4"
KNOCKOUT
1/2" & 3/4"
KNOCKOUT
1/2" & 3/4"
KNOCKOUT
AC OUTLET
OPENING
IPS INSERT
OPENING
1" x 2" OVAL KNOCKOUT CENTERED ON
BLOCK-OFF PANEL
DIAMOND & NOTCH
OF MOUNT
CL
3.72 1.58 2.92
15.10 30.00" [762mm] MAX
3.94" [100mm] MIN
12.00" MINIMUM SPACING
WALL PLATES SLIDE FREELY ON RAILS
ALIGN WITH VERTICAL
10.94 0.58 1.42
7.02 5.23
7.39 A1
TNK1
TKN3
TKN4
TKN2
TKN2
TNK1
TKN3
KEYNOTES
TELECOMMUNICATIONS SYSTEMS: COMPLY WITH DIVISION 27.
FLAT PANEL DISPLAY/LCD - NET WEIGHT NOT TO EXCEED 135
LBS.
FLAT PANEL MOUNT - NET WEIGHT NOT TO EXCEED 40 LBS.
FLAT PANEL WALL BOX, FPWB1, RECESSED FLUSH IN WALL.
IN-WALL CONDUIT RACEWAY.
ARCHITECTURAL: COMPLY WITH DIVISIONS 2-14.
WALL CTKNITY WITH MINIMUM 200 LB. BACKING.
TKN
A
A1
TNK1
TKN2
TKN3
TKN4
1 FLAT PANEL MOUNT ASSEMBLY
NTS
1A FRONT VIEW 1B SIDE VIEW 1C
FRONT VIEW 1DSIDE VIEW
2 FLAT PANEL WALL BOX - FPWB
NTS
2A FRONT VIEW 2B TOP VIEW
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TA903
DETAILS - FLAT
PANEL WALL BOX
AND FLAT PANEL
MOUNT
Project Number
KEYNOTE REFERENCES
SCOPE OF KEYNOTES USED. **** IS A 4 DIGIT NUMBER FOLLOWING
THE PREFIX
KEYNOTE REFERENCE
AKN****
ARCHITECTURAL. CONFORM WITH WITH THE
REQUIREMENTS OF DIVISIONS 3-14. SEE
ARCHITECTURAL AND INTERIOR DRAWINGS FOR
ADDITIONAL DETAILS.
MKN****
MECHANICAL/PLUMBING. CONFORM WITH WITH THE
REQUIREMENTS OF DIVISIONS 22-23. SEE
MECHANICAL AND PLUMBING DRAWINGS FOR
ADDITIONAL INFORMATION.
EKN****
ELECTRICAL. CONFORM WITH WITH THE
REQUIREMENTS OF SPECIFICATION DIVISION 26 AND
THE FIRE ALARM SECTIONS OF DIVISION 28. SEE
ELECTRICAL AND FIRE ALARM DRAWINGS FOR
ADDITIONAL INFORMATION.
TKN****
COMMUNICATIONS AND ELECTRONIC SECURITY
SYSTEMS. CONFORM WITH WITH THE
REQUIREMENTS OF SPECIFICATION DIVISION 27 AND
THE ELECTRONIC SECURITY SECTIONS OF DIVISION
28. SEE TA, TN AND TY DRAWINGS FOR ADDITIONAL
INFORMATION.
FOH-P FIBER OPTIC CABLE HYBRID, PLENUM RATED
1IDP 1" INNERDUCT, PLENUM RATED
2IDP 2" INNERDUCT, PLENUM RATED
SEE SPECIFICATION SECTIONS FOR REFERENCE DESCRIPTIONS
AND REQUIREMENTS. FOR OTHER MATERIAL AND EQUIPMENT
NOTE:
UTP5e-4P UNSHIELDED TWISTED PAIR, CAT. 5e PLENUM
TB15 TERMINAL BLOCK WITH 15 AMP SWITCH BLADE.
CAT.3 PATCH PANEL
XX- NO OF PAIRS
110 TERMINAL BLOCK, PRE-WIRED W/50 PIN CONNECTOR,
110TBXX 110 TERMINAL BLOCK, CAT.5, XX-NO OF PAIRS
110PWTBXX
PWC3PP PRE-WIRED, 50 PIN CONNECTOR (REAR) & RJ45 (FRONT) CATEGORY 5e PATCH PANEL
FIBER SPLICE PANEL
FIBER SPLICE CLOSURE
FIBER PATCH PANEL
FIBER TERMINAL BOX
OUTSIDE PLANT
MULTIMEDIA PLATE
UNSHIELDED TWISTED PAIR, CAT. 5e
MULTI MODE OPTICAL FIBER
MINIMUM POINT OF ENTRY
SINGLE MODE OPTICAL FIBER
TELECOMMUNICATIONS CLOSET
MAIN DISTRIBUTION FACILITY.
FIBER OPTIC CABLE HYBRID, OUTSIDE PLANT RISER RATED
FIBER OPTIC CABLE, SINGLE MODE OUTSIDE PLANT RISER RATED
FIBER OPTIC CABLE, MULTI MODE OUTSIDE PLANT RISER RATED
INTERMEDIATE DISTRIBUTION FACILITY
TELEPHONE CABLE, OUTSIDE PLANT, DUCTWAY
UNSHIELDED TWISTED PAIR, CAT. 5e OUTSIDE PLANT
C5ePP
FOH-OPR
FOM-OPR
FOS-OPR
FPP
MDF
IDF
FTB
FSP
FSC
MM
MMP
OSP
MPOE
T.C.
UTP5e-4
T-OPD
SM
MATERIAL & EQUIPMENT LEGEND
UTP5e-4OP
OPP. OPPOSITE
SIM. SIMILAR
ON CENTER
NOT TO SCALE
PANEL
PROJECT
OUTSIDE DIAMETER
OWNER FURNISHED EQUIPMENT
NATIONAL ELECTRICAL CODE
NOT IN CONTRACT
REFER TO
REFERENCE
SPECIFICATION
SHEET NOTE
SURFACE RACEWAY
SINGLE MODE OPTICAL FIBER
SHIELDED PAIR - SEE SPECIFICATIONS
PROJECT STANDARD RECEPTACLE HEIGHT +18" AFF, U.O.N.
PROJECT STANDARD SWITCH HEIGHT +48" AFF TO , U.O.N.
TELEPHONE
TYPICAL
TWISTED PAIR
TELECOMMUNICATIONS
TELECOMMUNICATIONS CLOSET
SHIELDED TWISTED PAIR
WITH
WEATHERPROOF
UNLESS OTHERWISE NOTED
TELEPHONE CABLE, OUTSIDE PLANT, DUCTWAY
TELECOMMUNICATIONS INDUSTRY ASSOCIATION
STANDARD
NEC
N.I.C.
O.D.
O.C.
NTS
O.F.E.
PROJ.
PNL.
RE:
P.S.S.H.
REF.
SP
SN
S.R.
SPEC
SM
P.S.R.H
STP
TEL
TELCOM
T.C.
TIA
T-OPD
TYP.
TP
W/
WP
U.O.N.
STD
CABLE RUNWAY OR CABLE TRAY. TYPE & SIZE AS INDICATED ON
FOR COMMUNICATIONS AND POWER SYSTEM
NEW WIRE AND/OR CABLE INSIDE NEW CONDUIT WALLS OR IN CEILING .
PLANS AND SPECIFICATIONS SECTION 27 05 36.
PROVIDED UNDER DIV. 27.
CABLE/RACEWAY TURNS UP
CABLE/RACEWAY TURNS DOWN
AND SPECIFICATION SECTION 27 05 33.
NEW WIRE AND/OR CABLE IN EXPOSED CONDUIT
OR RACEWAY. FILL PER SCHEDULE, PLANS
MARK INDICATES RACEWAY DROP FROM CEILING.
COORDINATE EXACT LOCATION WITH DIV. 27 PLANS.
SURFACE RACEWAY.
HOME RUN
KEYNOTES
WIRING NOTES
EXPOSED CABLE UNDER CEILING SUPPORTED BY CLIPS
CONDUIT TO CABLE TRANSITION POINT
OR STAPLES @ 1'-0" O.C.
LEGEND
EA. EACH
C.L. CENTERLINE
ALTERNATE
AMERICANS WITH DISABILITIES ACT
ABOVE MEZZANINE FINISHED FLOOR
ABOVE FINISHED CEILING
ABOVE FINISHED FLOOR
AREA DISTRIBUTION FACILITY
BACK OF HOUSE
BUILDING
COMMUNICATIONS
CATEGORY
CONDUIT
BUILDING DISTRIBUTION FACILITY
BELOW FINISHED CEILING
CALIFORNIA ELECTRICAL CODE
CALIFORNIA BUILDING CODE
SINGLE CHAMBER SURFACE RACEWAY
THREE CHAMBER SURFACE RACEWAY
CONDUIT ONLY
CONTINUATION
DIVISION
EXISTING
DIAMETER
DEDUCTIVE
DEMOLISH EXISTING
COMMUNICATIONS SYSTEM
EQUIPMENT
FINISHED
ELEVATION
END OF LINE
ELECTRONIC INDUSTRIES ASSOCIATION
3SR-2.5
A.D.A.
1SR-1
ADF
A.F.C.
ALT
A.M.F.F.
A.F.F.
BDF
B.F.C.
B.O.H.
BLDG.
CAT.
CBC
COMM.
CEC
C.
C.O.
CONT.
CS
(D)
, DIA.
(E)
EIA
DIV
DED
ELEV.
E.O.L.
FIN
EQPT.
ABBREVIATIONS
FUTURE
HOME RUN
HEIGHT
JUNCTION BOX
MASTER ANTENNA TELEVISION
LOCAL AREA NETWORK
MONUMENT
MAXIMUM
MODULAR
MINIMUM
NEW
H.R.
FUT
HT.
LAN
MATV
J, JBOX
MAX.
MON.
MOD.
MIN.
(N)
REFER TO SPECIFICATIONS FOR COMPLETE REQUIREMENTS.
PROVIDE CONDUIT, BOXES AND FITTINGS SHOWN ON COMMUNICATIONS SYSTEMS (TN) SYSTEM DRAWINGS UNDER THE WORK OF SECTION 27 05 33 COMMUNICATIONS RACEWAYS, BOXES AND FITTINGS. UNLESS OTHERWISE INDICATED, PROVIDE 1 INCH TRADE SIZE MINIMUM . PROVIDE RACEWAY SIZE AS REQUIRED FOR A MAXIMUM OF 30 PERCENT WIRE FILL.
PROVIDE FIRESTOPPING UNDER THE WORK OF SECTION 27 05 33 COMMUNICATIONS RACEWAYS, BOXES AND FITTINGS.
LOCATIONS SHOWN ON THE ARCHITECTURAL DRAWINGS TAKE PRECEDENCE OVER LOCATIONS SHOWN ON THE COMMUNICATIONS SYSTEMS DRAWINGS.
DEVICE QUANTITIES SHOWN ON FLOOR PLANS AND REFLECTED CEILING PLANS TAKE PRECEDENCE OVER DEVICE QUANTITIES SHOWN ON FUNCTIONAL DIAGRAMS.
QUANTITIES SHOWN ON FUNCTIONAL DIAGRAMS TAKE PRECEDENCE OVER QUANTITIES SHOWN ON RACK ELEVATIONS.
QUANTITIES SHOWN ON DEVICE SCHEDULES TAKE PRECEDENCE OVER QUANTITIES SHOWN ON FUNCTIONAL DIAGRAMS, FLOOR PLANS AND REFLECTED CEILING PLANS.
LOCATIONS SHOWN ON LARGE SCALE DRAWINGS TAKE PRECEDENCE OVER LOCATIONS SHOWN ON SMALL SCALE DRAWINGS.
3 5
4 6
8 7
COMMUNICATIONS SYSTEMS GENERAL NOTES
1 2
C6PP CATEGORY 6 PATCH PANEL.
UTP6-4P UNSHIELDED TWISTED PAIR, CAT. 6 PLENUM
UNSHIELDED TWISTED PAIR, CAT. 6
UNSHIELDED TWISTED PAIR, CAT. 6 OUTSIDE PLANT
UTP6-4
UTP6-4OP
TYPES REFER TO SPECIFICATIONS.
EXAMPLE: J16C= 30"H X 30"W X 8"D HINGED NEMA 4 JBOX.
ALL JUNCTION BOXES TO BE HINGED TYPE, PROVIDED
(INCHES)
AS REQUIRED FOR INSTALLATION. PAINT ALL INTERIOR
IN JUNCTION BOXES SHALL BE CUT OR PUNCHED
WITHOUT PRE-PUNCHED KNOCKOUTS. PENETRATIONS
BOXES TO MATCH WALL FINISH. COORDINATE FINISH
WITH ARCH. PLANS.
A - NEMA 12
NONE - NEMA 1
B - NEMA 3R
NOTE 1
SUFFIX:
J16
J17
J15
J13
J14
J12
C - NEMA 4
D - NEMA 4X
30 36
30 24
24 24
30 30
24 20
24 20
J8
J11
J10
J9
J6
J7
J5
J1
J4
J3
J2
SYMBOL
20 20
20 20
16 18
12 20
20 16
16 12
18 12
(INCHES)
6 12
12 8
H
6 12
12 8
W
JUNCTION BOX SCHEDULE
(INCHES)
J18 36 36
4 4
4 6
8 6
8 6
8 6
8 6
8 8
8 8
8 8
SHEET NUMBER
WALL SECTION KEY
SHEET NUMBER
DRAWING NUMBER
ELEVATION KEY
DRAWING NUMBER
SHEET NUMBER
DRAWING NUMBER
DETAIL SYMBOL
SHEET NUMBER
REVISION NUMBER
REVISION SYMBOL
BUILDING LABEL
COLUMN GRID
GRID LINES
DRAWING MATCH LINE
SHEET NUMBER
DRAWING NUMBER
ROOM NAME
ROOM NUMBER
ROOM KEY
BLDG. SECTION KEY
DRAWING NUMBER
GENERAL SYMBOLS
TRAFFIC RATED LID. DEPTH PER
PEDESTRIAN LID. DEPTH PER
SPECIFIED TRENCH DEPTH AND
TRAFFIC RATED LID. DEPTH PER
SPECIFIED TRENCH DEPTH AND
SPECIFIED TRENCH DEPTH AND
PEDESTRIAN LID. DEPTH PER
TRAFFIC RATED LID. DEPTH PER
SPECIFIED TRENCH DEPTH AND
SPECIFIED TRENCH DEPTH AND
SET TO GRADE
SET TO GRADE
MOUNTING
SET TO GRADE
DETAILS.
DETAILS.
DETAILS.
NOTES
SET TO GRADE
SYMBOL
UNDERGROUND
UNDERGROUND
24" x 36"
DEVICE/FUNCTION
12" x 22"
UNDERGROUND
12" x 22"
UNDERGROUND VAULT SCHEDULE
24" x 36"
CONCRETE PULL BOX
CONCRETE PULL BOX
CONCRETE PULL BOX
2. INSTALL U.G. CONDUITS TO THE BODY OF THE PULL BOX AND PROVIDE
CONCRETE PULL BOX
36" x 60"
UNDERGROUND
DETAILS.
SET TO GRADE
CONCRETE PULL BOX DETAILS.
GENERAL PULL BOX NOTES
END BELLS. CONDUITS RISING UP INSIDE THE PULL BOX WILL NOT BE ACCEPTED.
UNDERGROUND
1. LIDS SHALL BE MARKED WITH "COMMUNICATIONS".
ACJ
ECT
701
1 1
1 1
1 1
1 1
1 A1
1 XXXX
XXXX
1 1
1 1
TKN1
PB2P
PB1T
PB1P
PB2T
PB3T
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TN001
COMM - GENERAL
NOTES, LEGEND,
SYMBOLS, ABBR
AND JBOX
SCHEDULE
Project Number
SYMBOL DEVICE FUNCTION OR
SERVICE LOCATION WORK OF ROUGH-IN RACEWAY ELEVATION
CABLE FILL &
HOMERUN
DESTINATION,
U.O.N.
FINISH
WEIGHT,
LB
DETAIL
SHEET(S)
WALL SLEEVE/CONDUIT PATHWAY INDICATED 27 05 33 N/A R11
FLOOR BOX, RECESSED DEVICE COMPARTMENT,
CONCRETE SLAB, AT LEAST FOUR 1 GANG
OPENINGS, EACH AT LEAST 2-1/8" DEEP.
COMMUNICATIONS
PATHWAY
DEVICE ARE
RECESSED BELOW
FLOOR
27 05 33 FLOOR BOX FC3 - PROVIDE CAST IRON
TYPE AT SLAB ON GRADE CONDITIONS
2 EA. R6 U.O.N. FLUSH IN FLOOR AS SCHEDULED
ALUMINUM/SS TRIM OR
AS SELECTED BY CITY’S
REPRESENTATIVE.
3 6,7/TN905
FLOOR BOX, CONCRETE SLAB, AT LEAST 1-6 GANG,
2-1 GANG AND 1-3 GANG OPENING, EACH AT LEAST
2-1/8" DEEP. 6" MIN. DEPTH OVERALL. LID ACCEPTS
CARPET INSERTS.
COMMUNICATIONS &
AUDIO-VISUAL
FLUSH IN FLOOR,
INDICATED AND/OR
SCHEDULED
27 05 33
FLOOR BOX FC6 WITH MANUFACTURERS
SLAB ON GRADE TREATMENT AT GRADE
CONDITIONS.
R12 FLUSH IN FLOOR AS SCHEDULED
ALUMINUM/SS TRIM OR
AS SELECTED BY CITY’S
REPRESENTATIVE.
TA901
FURNITURE TRANSITION COMMUNICATIONS
PATHWAY AS DETAILED 27 05 33,
WO1 AS DETAILED
2 EA. R7, MIN,
AS AS RQD.
FOR FILL
AS DETAILED 4/TN905
J-BOX WITH BLANK FACE PLATE COMMUNICATIONS
PATHWAY INDICATED 27 05 33
4S BOX, 2-1/8" DEEP MIN., U.O.N. AT CMU
WALLS, PROVIDE 3-1/2” DEEP 2 GANG
MASONRY BOX.
R4 INDICATED STEEL 2
MULTIMEDIA DEVICE PLATE. DN1 COMMUNICATIONS INDICATED AND/OR
SCHEDULED
27 05 33,
27 15 00
FLUSH 4-11/16"S BOX, 2-7/8" DEEP MIN., W/ 1
GANG RING, U.O.N. AT CMU WALLS,
PROVIDE FLUSH 3-1/2” DEEP 2 GANG
MASONRY BOX.
R7 +18" AFF TO CL, U.O.N. AS SCHEDULED
MATCH ADJ.
ELECTRICAL U.O.N.
1,2,3,4/TN906
MULTIMEDIA DEVICE PLATE MOUNTED INSIDE FLAT
PANEL WALL BOX. DN1. COMMUNICATIONS AS DETAILED 27 05 33, 27 15 00 AS DETAILED R6 INDICATED AS SCHEDULED
MATCH ADJ.
ELECTRICAL U.O.N.
MULTIMEDIA DEVICE PLATE MOUNTED IN
CASEWORK. DN1. COMMUNICATIONS INDICATED AND/OR
SCHEDULED
27 05 33,
27 15 00 CUSTOM R7 +18" AFF TO CL, U.O.N. AS SCHEDULED
MATCH ADJ.
ELECTRICAL U.O.N.
MULTIMEDIA DEVICE PLATE ABOVE COUNTER. DN1. COMMUNICATIONS INDICATED 27 05 33, 27 15 00
FLUSH 4-11/16"S BOX, 2-7/8" DEEP MIN., W/ 1
GANG RING, U.O.N. AT CMU WALLS,
PROVIDE FLUSH 3-1/2” DEEP 2 GANG
MASONRY BOX.
R7 +6" ABOVE COUNTER TO CL AS SCHEDULED
MATCH ADJ.
ELECTRICAL U.O.N.
MULTIMEDIA DEVICE PLATE IN OPEN PLAN
FURNITURE. DN1. COMMUNICATIONS LRI4 27 05 33,27 15 00 LRI4 R8 LRI4 AS SCHEDULED MATCH ADJ.
ELECTRICAL U.O.N.
MULTIMEDIA SURFACE MOUNT BUSCUIT BOX
MOUNTED INSIDE BACKBOX FOR OWNER
FURNISHED IP CAMERA. DN1.
COMMUNICATIONS AS DETAILED 27 05 33,
27 15 00 AS DETAILED R6 INDICATED AS SCHEDULED
PROVIDE BLANK COVER
PLATE TO MATCH ADJ.
ELECTRICAL
MULTIMEDIA PLATE, WALL TELEPHONE PLATE. DN1. COMMUNICATIONS INDICATED 27 05 33, 27 15 00
FLUSH 4-11/16"S BOX, 2-7/8" DEEP MIN., W/ 1
GANG RING, U.O.N. AT CMU WALLS,
PROVIDE FLUSH 3-1/2” DEEP 1 GANG
MASONRY BOX.
R5
+48" AFF TO CL, 9" ABOVE
COUNTERS WHERE
INDICATED
1 UTP6-4P STAINLESS STEEL 5/TN906
MULTIMEDIA DEVICE PLATE CEILING, FOR WIFI
APPLICATION. DN1 COMMUNICATIONS INDICATED 27 05 33,
27 15 00
4-11/16"S BOX, 2-7/8" DEEP MIN., W/ 1 GANG
RING FLUSH IN CEILING.
R7 FLUSH IN FINISHED CEILING. 2 UTP6-4P
VARIES BY LOCATION.
FINISH PER CITY’S
REPRESENTATIVE.
FLOOR MOUNTED MEDIUM DEPTH NETWORK
EQUIPMENT CABINET W/ VERTICAL WIRE
MANAGEMENT, 44 RU, 42" DEEP, 4 POST, SEISMIC
RATED.
COMMUNICATIONS FLOOR 27 11 16
BOLT TO SLAB PER
CONTRACTORS
STRUCTURAL ENGINEERING
DESIGN.
BLACK 1100 TN903
R28
F
XXX-YY
N
XXX-YY
O
XXX-YY
T
XXX-YY
W
XXX-YY
A
XXX-YY
XXX-YY
FC3
J
FC6
FT
S
XXX-YY
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TN002
COMM - SYMBOL
SCHEDULE
Project Number
NOTE NO. DEVICE NOTES
DN1
SUBSCRIPT INDICATES QUANTITY OF CATEGORY AND COAX CABLES PROVIDED AT WAO AND DESTINATION. (D)ATA/VOICE CABLING IS CATEGORY 6, (B)ROADBAND VIDEO CABLING IS RG-6.
EXAMPLES:
2D REPRESENTS 2 CATEGORY 6 CABLES AND JACKS TERMINATED AT THE INDICATED WAO AND SERVING TR.
1B IS 1 RG-6 TERMINATED AT THE INDICATED WAO AND SERVING TR.
WORK OF NOTES
WO1 NOT USED
LOCATION & ROUGH-IN NOTES
LRI1 FLUSH 4S BOX IN WALL ADJ. TO INDICATED LOCATION. FISH CABLE THROUGH FURNITURE TO CITY SELECTED MOUNTING LOCATION.
LRI2 NOT USED
LRI3 4S BOX W/ 1 GANG RING BLANK COVER PLATE
LRI4 ABOVE DESK IN ELECTRIFIED BELT OR AT BASE IN ELECTRIFIED BASE PER CITY'S REP.
LRI5
AT SUSPENDED CLG CONDITIONS, SM 4S BOX, BLNK COVER & FLEX C TO DEVICE. ELSEWHERE MOUNTED IN CEILING ADJ TO DEVICE OR MNT DEVICE TO COVER PLATE.
LRI6
SURFACE MTD 4S BOX WITH BLANK COVER PLATE INSTALLED ADJACENT TO TRACK AND WITHIN 6" OF FLOOR. PROVIDE ONE DEVICE AT OPPOSITE SIDES OF EACH OPENING. INSTALL DEVICE TO TRACK PER
MANUFACTURER'S INSTRUCTIONS.
LRI7 NOT USED
LRI8
4S BOX W/ BLANK COVER PLATE W/ GROMMET OPENING MTD WITHIN 6" OF LATCH AT UNDERSIDE OF ROOF. EXTEND HS TO HATCH FRAME AND INSTALL IN ACCORDANCE WITH MANUFACTURER INSTRUCTIONS.
LRI9 4S BOX, 2-1/8" DEEP MIN., W/ 1 GANG RING WITH LOCKING HINGED COVER PLATE (FSR WB-MR2G OR EQUAL).
LRI10 OUTLETS SHALL BE PLACED SO THEY WILL NOT BE COVERED BY AN UNDER-COUNTER CABINET.
LRI11 PROVIDE BACKING AND SUPPORT FOR 5 POUND DEVICE.
LRI12 NOT USED
LRI13 PROVIDE BACKING IN WALL SUITABLE TO SUPPORT A 20 POUND DEVICE WITH A LOAD CENTROID 18 INCHES FROM THE FACE OF THE WALL.
LRI14 PROVIDE BACKING IN WALL SUITABLE TO SUPPORT A 200 POUND DEVICE WITH A LOAD CENTROID 8 INCHES FROM THE FACE OF THE WALL.
LRI15 AS DETAILED AND/OR SCHEDULED ON THE ARCHITECTURAL DRAWINGS.
RACEWAY NOTES
R1
AS REQUIRED AND CONSTRUCTED IN CONFORMANCE WITH NFPA 72, ARTICLE 12.4.4. RACEWAY SIZES SHOWN ON PLANS ARE MIN.
R2 NOT USED
R3 NOT USED
R4 AS DETAILED AND/OR SCHEDULED
R5
3/4" C. H.R. TO ACCESSIBLE CEILING OR FLOOR, OR TO SERVING BDF, IDF OR EQUIPMENT ROOM, U.O.N.
R6
1" C. H.R. TO ACCESSIBLE CEILING OR FLOOR, OR TO SERVING BDF, IDF OR EQUIPMENT ROOM, U.O.N.
R7
1-1/4" C. H.R. TO ACCESSIBLE CEILING OR FLOOR, OR TO SERVING BDF, IDF OR EQUIPMENT ROOM, U.O.N.
R8
LIQUIDTITE TO SERVING EFM, EFM-R OR FMP, AS APPLIES. SIZE TO MATCH FILL AT 40% FILL MAXIMUM.
R9
AT ACCESSIBLE CEILING, EXTEND TO BASKET TRAY AT CENTER OF ROOM.
WHERE MOUNTED IN GYP CEILING, EXTEND 3/4" C. TO BASKET TRAY AT
CENTER OF ROOM
R10
2 1-1/4" C TO 4 GANG COMPARTMENT, 1 - 1" TO 1 GANG COMPARTMENT,
STUBBED TO ACCESSIBLE CEILING OR FLOOR EXTEND TO TR ROOM USING BASKET TRAY. SEE ELECTRICAL DRAWINGS FOR ELECTRICAL ROUGH-IN.
R11
UNLESS OTHERWISE SHOWN, PROVIDE 1.5" EMT SLEEVE, WITH INSULATED THROAT BUSHING AT EACH END, STUBBED OUT 4 INCHES FROM FACE OF WALL, AT ELEVATION APPROXIMATELY 6 INCHES ABOVE ACCESSIBLE CEILING. INSTALL SLEEVE IN AN ACCESSIBLE LOCATION AS DEFINED IN CALIFORNIA ELECTRICAL CODE, ARTICLE 100 DEFINITIONS. PROVIDE FIRESTOPPING UNDER WORK OF SECTION 27 05 33. BOND TO GROUND.
COMPLY WITH DIVISION 26 AND SECTION 27 05 26 GROUNDING.
R12
4 1-1/4" C TO 6 GANG COMPARTMENT, 1 - 1.25" TO EA. 1 GANG
COMPARTMENT, STUBBED TO ACCESSIBLE CEILING OR FLOOR, EXTEND TO TR ROOM IN BASKET TRAY. SEE ELECTRICAL DRAWINGS FOR ELECTRICAL ROUGH-IN TO 3 GANG COMPARTMENT.
ACCESSIBLE CEILING IS A T-BAR OR SIMILAR GRID BASED, PANELIZED
REMOVEABLE CEILING MEETING THE DEFINITION FOR ACCESSIBLE WIRING METHODS IN ARTICLE 100 OF THE CALIFORNIA ELECTRICAL CODE.
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TN003
COMM - SYMBOL
SCHEDULE NOTES
Project Number
UP
UP
24TH STREET
24TH STREET BYPASS
2101
0643
2102
TKN1001
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
R C
NDE N VA
,N I N G
CRAE
I T E C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
N
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TN100
COMM - SITE PLAN
Project Number
1/16" = 1'-0" 1
COMM - SITE PLAN
1. WORK OF THE PROJECT PROTECTS IN PLACE EXISTING
UNDERGROUND CARRIER ENTRANCE DUCTS TO IT ROOM 116
SHEET NOTE
KEYNOTES
TKN1001 PROTECT IN PLACE EXISTING (2) 1.25 C AT&T MPOE
ENTRY DUCTS FROM THE PUBLIC RIGHT OF WAY
TO MECHANICAL EQUIPMENT ROOM POINT OF
ENTRY TO THE BUILDING. PATH SHOWN
REPRODUCED FROM ORIGINAL CONSTRUCTION
PLANS - VERIFY LOCATION IN FIELD.
1 1
A A
2 2
B B
C C
E E
5 5
F F
3 3
D D
MECHANICAL
001
4' HIGH CRAWLSPACE
4' HIGH CRAWLSPACE
4 4
001
SMD + SED FOR
EQUIPMENT LAYOUT
AND INFORMATION
SMD + SED FOR DUCT
AND CONDUIT ROUTING
AND INFORMATION
SMD + SED FOR DUCT
AND CONDUIT ROUTING
AND INFORMATION
SMD + SED FOR DUCT
AND CONDUIT ROUTING
AND INFORMATION
001-DA
4D
001-DB
1D
TKN1208
TKN1210
001-BA
4D
TKN1214
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
R C
NDE N VA
,N I N G
CRAE
I T E C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
N
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TN200
COMM - BASEMENT
FLOOR PLAN
Project Number
1/8" = 1'-0" 1
COMM - BASEMENT FLOOR PLAN
KEYNOTES
TKN1208 COORDINATE WITH THE REQUIREMENTS OF
DIVISION 25 AND THE LOCATION OF THE BMS
PANEL INTERFACE.
TKN1210 WAO FOR FIRE ALARM CONTROL PANEL -
COORDINATE WITH LOCATION OF FACP AND WORK
OF DIVISION 28. CONTRACTOR TO PROVIDE 1" EMT
C. PATHWAY MINIMUM FROM IT ROOM 116. REFER
TO THE SINGLE LINE DIAGRAM FOR THE
ADDITIONAL CABLING TO BE PROVIDED TO THIS
LOCATION TO SUPPORT ANALOG ALARM LINES, IF
USED.
TKN1214 WAO TO SUPPORT HVAC AND BMS FUNCTIONS.
COORDINATE LOCATION WITH WORK OF DIVISIONS
23 AND 25.
FC3
FC3
FC3
FC3
FC3
FC6
FC3
FC3
FC3
FT
FC3 FC3
1 1
A A
2 2
B B
C C
E E
5 F F
3 3
D D
OPEN TO
BELOW
STORAGE
104
HALL
106
ALL GENDER
RESTROOM
105
FOL
112
PATIO
10 CHILDREN
112
STUDY
113
STUDY
114
GROUP
STUDY
117
TEEN
115
MARKETPLACE
116
ADULT
118
STAFF
WORKROOM
125
OFFICE
119
STAFF
BREAKROOM
121
STAFF RR
123
IT
124
AMH/SORTING
122
ENTRY
101
119
STAFF
WORKROOM
125
PATIO
46 121
101B
007
113
114
117
005
004
101
COMMUNITY
MEETING
102
THE STUDIO
110
WELLNESS
108
FAMILY
RESTROOM
109
JANITOR
107
109
108
107
4 4
002
105
104
102B
102
102A
006
LINE OF SOFFIT ABOVE
LINE OF SOFFIT ABOVE
LINE OF SOFFIT ABOVE
106
120
124
123
116B
116A
103
KITCHENETTE
103
101A
003
WHISPER
ROOM (E)
009
008
103-CA
6D
116-AA
A
1D 116-BA
2D
119-BA
2D
119-DA
2D
125-EA
O
2D
112-CA
2D
112-AA
2D
121-DA
T
124-BB
2D
124-BA
2D
116-CA
2D
117-CA
2D
117-CB
A
1D
115-AA
A
2D
118-EC
4D
115-EA
6D
116-FA
4D
116-FB
4D
116-GA
2D
102-EA
4D
114-BA
2D
114-BB
A
1D
113-DA
2D
113-DB
A
1D
TN401
1 102-AB
N
2D
N
102-AA
2D
102-CA
2D
102-CD
2D
125-ED
O
2D
125-EC
O
2D 125-BB
2D
125-BA
2D
125-DA
2D
125-DB
2D
110-BA
2D
110-CA
2D
110-DA
2D
118-EB
4D
118-EA
4D
116-EC
F
4D
116-EB
F
4D
116-EA
F
4D
125-EB
O
2D
122-DA
1D 122-EA
4D
122-AA
4D
102-CC
A
1D
102-CB
A
1D
TYP.
FPWB
118-CA
2D
118-CB
2D
112-EB
4D
112-EA
4D
TKN1202
TKN1213
TKN1212
TKN1003
D
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
R C
NDE N VA
,N I N G
CRAE
I T E C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
N
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TN201
COMM - FIRST
FLOOR PLAN
Project Number
1/8" = 1'-0" 1
COMM - FIRST FLOOR PLAN
KEYNOTES
TKN1003 EXTEND TWO 1.25" C TO POINT OF ENTRY OF AT&T
SERVICE ENTRY AT BASEMENT LEVEL. REFER TO
TN100 - LOCATE POINT OF ENTRY IN FIELD AND
PROVIDE J15 NEMA 1 PULLBOX AT BASEMENT AT
POINT OF TRANSITION.
TKN1202 LOCATE AT INTERIOR OF A/V RACK - COORDINATE
WITH THE WORK OF SECTION 27 41 16.
TKN1212 WAO FOR ACCESS CONTROL AND IDS PANELS -
COORDINATE LOCATION WITH WORK OF DIVISION
28. TKN1213 LOCATE FURNITURE TRANSITION AS DIRECTED BY
CITY'S REPRESENTATIVE AND THE FINAL OPEN
PLAN FURNITURE PLANS AND ITS ELECTRIFIED
BASE ASSEMBLY.
ADDENDUM D 12/06/2024
D
IT
124
004
124
R28
36" MIN.
30" MIN.
26" MIN.
FRONT
4 TN401
3 6
5 AKN0001
AKN0001
AKN0001
TKN2013
EKN0008
EKN0008
TKN2001
TKN2001
D
TKN1003
D
TKN0446
EKN0018
EKN0013
EKN0014
D
D
TKN1003
D
D
D
TKN2012
TKN2013
EKN0008
TKN2019
TKN2013
TKN2011
TKN2010
TKN2012
TKN2015
EKN0008
TKN2014
EKN0008
TYP.
TKN2011 D
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
R C
NDE N VA
,N I N G
CRAE
I T E C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TN401
COMM - IT 124
ROOM - ENLARGED
PLAN, RCP,
ELEVATIONS
Project Number
1/2" = 1'-0" 1
COMM - IT 124 ROOM ENLARGED PLAN
N
1/2" = 1'-0" 2
COMM - IT 124 ROOM ENLARGED RCP
N
1/2" = 1'-0" 3
IT 124 ROOM SOUTH ELEVATION
1/2" = 1'-0" 4
IT 124 ROOM WEST ELEVATION
1/2" = 1'-0"
5 IT 124 ROOM NORTH ELEVATION
1/2" = 1'-0"
6 IT 124 ROOM EAST ELEVATION
ADDENDUM D 12/06/2024
KEYNOTES
AKN0001 3/4" FIRE TREATED PLY FROM 18" AFF TO 9'-6".
EKN0008 SURFACE MOUNTED 120VAC CIRCUIT FOR ESS
USE INSTALLED AT BACKBOARD.
EKN0013 GROUND RACK AND CABLE TRAY PER NEX
ARTICLE 250.
EKN0014 GROUND BUS BAR.
EKN0018 L6-30 POWER RECEPTACLE MOUNTED TO THE
VERTICAL FACE OF THE CABLE TRAY USING A
CONSTRUCTION CHANNEL SPACER TO PROTECT
TRAY INTERIOR. MIN OF TWO EACH CABINET. SEE
ELECTRICAL DRAWINGS FOR ADDITIONAL DETAILS.
TKN0446 18-4 CT SUPPORTED FROM DECK
TKN1003 EXTEND TWO 1.25" C TO POINT OF ENTRY OF AT&T
SERVICE ENTRY AT BASEMENT LEVEL. REFER TO
TN100 - LOCATE POINT OF ENTRY IN FIELD AND
PROVIDE J15 NEMA 1 PULLBOX AT BASEMENT AT
POINT OF TRANSITION.
TKN2001 ACCESS CONTROL PANELS AND DOOR LOCK
POWER SUPPLIES
TKN2010 4"x4" MIN. STEEL GUTTER AS SPECIFIED IN
SECTION 28 05 28.
TKN2011 ELECTRONIC SECURITY SYSTEM FIELD DEVICE
CONDUITS STUB INTO GUTTER.
TKN2012 ACCESS CONTROL DATA GATHERING PANEL (DGP)
AS SPECIFIED IN SECTION 28 13 00. PROVIDE QTY
AS REQUIRED.
TKN2013 WORK AREA OUTLET BY WORK OF SECTION 27 15
00 FOR USE WITH ACCESS CONTROL DATA
GATHERING PANEL.
TKN2014 DOOR LOCK POWER SUPPLY AS SPECIFIED IN
SECTION 28 05 28. PROVIDE QTY AS REQUIRED.
TKN2015 PROVIDE PATHWAY/CHASE NIPPLES BETWEEN
PANELS AND TO GUTTER AS REQUIRED.
TKN2019 INTRUSION DETECTION PANEL.
D
D
1 1
A
2 2
B
C
E
5 5
F
3 3
D
OPEN TO ABOVE
9' - 0"
8' - 8 1/8"
8' - 8 1/8"
8' - 8 1/8"
9' - 0"
8' - 11 7/8"
8' - 6 3/4"
8' - 11 7/8"
8' - 11 7/8"
COMMUNITY
MEETING
CHILDREN
THE STUDIO
STUDY
STUDY
GROUP
STUDY
STORAGE
WELLNESS
FAMILY
RESTROOM
ALL GENDER
RESTROOM HALL
FOL
MARKETPLACE
TEEN
ADULT
STAFF
BREAKROOM
STAFF RR
IT
AMH/SORTING
STAFF
WORKROOM
STAFF
WORKROOM
OFFICE
ENTRY
JANITOR
KITCHENETTE
4 4
9' - 1 3/8"
7' - 6"
9' - 1 3/8"
9' - 1 3/8"
9' - 0"
9' - 1"
8' - 0"
8' - 0"
7' - 6" 8' - 0"
7' - 6"
9' - 0 3/8"
9' - 1 3/8"
9' - 1 3/8"
8' - 8 1/8"
8' - 6 3/4"
8' - 6 3/4"
8' - 6 3/4"
ALT. D-03: ACT-1 @ MARKETPLACE,
TEEN, AND ADULT SOFFT
8' - 0"
7' - 6"
TN401
2 125-ZA
W
1D
112-ZA
W
2D
118-YA
W
2D
102-ZA
W
1D
116-ZA
W
2D
EXT-YA
1D
TKN1221
112-YB
1D
112-YA TKN1221
1D
TKN1221
EXT-YI
1D
TKN1221
110-YA
1D
TKN1221
116-YD
TKN1221 1D
116-YC
1D TKN1221
EXT-YH
1D
TKN1221
EXT-YG
1D
TKN1221
116-YB
1D
TKN1221
101-YA
1D
TKN1221
EXT-YE
1D
TKN1221
EXT-YD
1D
TKN1221
EXT-YF
TKN1221 1D
116-YA
1D TKN1221
115-YB
TKN1221 1D
115-YA
1D
TKN1221
EXT-YB
TKN1221 1D
EXT-YC
1D
TKN1221
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
R C
NDE N VA
,N I N G
CRAE
I T E C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
N
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TN601
COMM - FIRST
FLOOR RCP
Project Number
1/8" = 1'-0" 1
COMM - FIRST FLOOR RCP
KEYNOTES
TKN1221 WAO FOR SECURITY CAMERA. SEE DRAWING
TY601 FOR EXACT LOCATION.
TKN
TELECOMMUNICATIONS SYSTEMS: COMPLY WITH
DIVISION 27.
TKN1
NETWORK ELECTRONICS, PATCH CORDS, PATCHING,
AND CROSS-CONNECTIONS ARE SACRAMENTO PUBLIC
LIBRARY FURNISHED AND INSTALLED.
TKN2
PROVIDE WAO QUANTITY AS INDICATED ON THE PLANS
AND SCHEDULES.
TKN3 NOT USED
TKN4 BY SACRAMENTO PUBLIC LIBRARY.
TKN5
REFER TO THE QUANTITY OF 24 PORT AND 48 PORT
PATCH PANELS INDICATED IN THE DEVICE SCHEDULE.
TKN6
IP CAMERAS AND PATCH CORDS ARE PROVIDED UNDER
THE WORK OF DIVISION 28. REFER TO TY SHEETS.
TKN7
AT CAMERAS PROVIDE BISCUIT BOX MOUNTED
INTERNAL TO CAMERA BACKBOX AS WAO.
TKN8
PROVIDE AT LEAST 2 PAIR (USOC INS 3,4,5,6)
TERMINATED THROUGH FOR EACH JACK.
TKN9
SACRAMENTO PUBLIC LIBRARY TO FURNISH AND
INSTALL THE WIRELESS ACCESS POINTS (WAPS) AND
PATCH CORDS.
TKN10
PROVIDE UTP6-4OP FOR WAO’S AT CAMERA LOCATIONS
WITHIN 295 CABLED FEET OF MDF PATCH PANEL.
CAMERAS LOCATED BEYOND THIS DISTANCE TO BE
PROVIDED WITH ALTERNATIVE MEDIA UNDER THE WORK
OF SECTION 28 23 00.
TKN11 BY FRONTIER/AT&T (N.I.C.).
TKN12 NOT USED
TKN13
PROVIDE UTP6-4 INSTALLED IN A 1.25" C. EMT CONDUIT
MIN. PATHWAY.
MMP6
MMP6
MMP6
MMP6
KEYNOTES
110TB100
25 PRT-IDW
2 UTP6-4P
UTP6-4P
*-48 C6PP
24 C6PP
TKN9
TKN7
TKN6
TKN2
TKN1
TKN5 TKN10
TKN5
TKN13
TKN13
TKN2
1 STRUCTURED CABLING SINGLE LINE DIAGRAM
NTS
IT ROOM 116
RACK MTD - R28
AT FACP - SEE
ELECTRICAL DWGS.
MECHANICAL ROOM - 001
BASEMENT
TKN1
WAP
TKN11
NET EQUIP
MPOE
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TN701
STRUCTURED
CABING SINGLE
LINE RISER
DIAGRAM
Project Number
Plate Station No.
Room No.
Room Name
"F" Type Connector
Cat. 6 Jack Count
UTP6-4
TOTAL Ct. 6 FILL
Cat6 Ckt #1 LabelingCat6 Ckt #2 LabelingCat6 Ckt #3 LabelingCat6 Ckt #4 LabelingCat6 Ckt #5 LabelingCat6 Ckt #6 Labeling "F" Connector Ckt
Labeling
UTP6-4 FILL
RG-6M FILL
Home Run Location
Notes
BASEMENT
001-BA 001 MECHANICAL 0 4 4 0001 0002 0003 0004 4 IT 124 001-DA 0 4 4 0005 0006 0007 0008 4 IT 124
001-DB 0 1 1 0009 1 IT 124
TOTAL FOR BASEMENT 0 9 9 0 9 0
Min. 48 port patch panel req. 1 1
Plate Station No.
Room No.
Room Name
"F" Type Connector
Cat. 6 Jack Count
UTP6-4
TOTAL Cat. 6 FILL
Cat6 Ckt #1 LabelingCat6 Ckt #2 LabelingCat6 Ckt #3 LabelingCat6 Ckt #4 LabelingCat6 Ckt #5 LabelingCat6 Ckt #6 Labeling "F" Connector Ckt
Labeling
UTP6-4 FILL
RG-6M FILL
Home Run Location
Notes
FIRST FLOOR
101-YA 101 ENTRY 0 1 1 0001 1 IT 124
102-AA 102 COMMUNITY MEETING 0 2 2 0002 0003 2 IT 124
102-AB 0 2 2 0004 0005 2 IT 124
102-CA 0 2 2 0006 0007 2 IT 124
102-CB 0 1 1 0008 1 IT 124
102-CC 0 1 1 0009 1 IT 124
102-CD 0 2 2 0010 0011 2 IT 124
102-EA 0 4 4 0012 0013 0014 0015 4 IT 124
102-ZA 0 2 2 0016 0017 2 IT 124
103-CA 103 KITCHENETTE 0 6 6 0018 0019 0020 0021 0022 0023 6 IT 124 110-BA 110 THE STUDIO 0 2 2 0024 0025 2 IT 124
110-CA 0 2 2 0026 0027 2 IT 124
110-DA 0 2 2 0028 0029 2 IT 124
110-YA 0 1 1 0030 1 IT 124
112-EA 0 4 4 0031 0032 0033 0034 4 IT 124
112-EB 0 4 4 0035 0036 0037 0038 4 IT 124
112-AA 112 CHILDREN 0 2 2 0039 0040 2 IT 124
112-CA 0 2 2 0041 0042 2 IT 124
112-YA 0 1 1 0043 1 IT 124
112-YB 0 1 1 0044 1 IT 124
112-ZA 0 2 2 0045 0046 2 IT 124
113-DA 113 STUDY 0 2 2 0047 0048 2 IT 124
113-DB 0 1 1 0049 1 IT 124
114-BA 114 STUDY 0 2 2 0050 0051 2 IT 124
114-BB 0 1 1 0052 1 IT 124
115-EA 115 TEEN 0 6 6 0053 0054 0055 0056 0057 0058 6 IT 124 115-YA 0 1 1 0059 1 IT 124
115-YB 0 1 1 0060 1 IT 124
116-AA 116 MARKETPLACE 0 1 1 0061 1 IT 124
116-AB 0 2 2 0062 0063 2 IT 124
116-CA 0 2 2 0064 0065 2 IT 124
116-EA 0 4 4 0066 0067 0068 0069 4 IT 124
116-EB 0 4 4 0070 0071 0072 0073 4 IT 124
116-EC 0 4 4 0074 0075 0076 0077 4 IT 124
116-FA 0 4 4 0078 0079 0080 0081 4 IT 124
116-FB 0 4 4 0082 0083 0084 0085 4 IT 124
116-GA 0 2 2 0086 0087 2 IT 124
116-YA 0 1 1 0088 1 IT 124
116-YB 0 1 1 0089 1 IT 124
116-YC 0 1 1 0090 1 IT 124
116-YD 0 1 1 0091 1 IT 124
116-ZA 0 2 2 0092 0093 2 IT 124
117-CA 117 GROUP STUDY 0 2 2 0094 0095 2 IT 124
117-CB 0 1 1 0096 1 IT 124
118-CA 118 ADULT 0 2 2 0097 0098 2 IT 124
118-CB 0 2 2 0099 0100 2 IT 124
118-EA 0 4 4 0101 0102 0103 0104 4 IT 124
118-EB 0 4 4 0105 0106 0107 0108 4 IT 124
118-EC 0 4 4 0109 0110 0111 0112 4 IT 124
118-YA 0 1 1 0113 1 IT 124
119-BA 119 OFFICE 0 2 2 0114 0115 2 IT 124
119-DA 0 2 2 0116 0117 2 IT 124
121-DA 121 STAFF BREAKROOM 0 1 1 0118 1 IT 124
122-AA 122 AMH/STORING 0 4 4 0119 0120 0121 0122 4 IT 124 122-DA 0 1 1 0123 1 IT 124
122-EA 0 4 4 0124 0125 0126 0127 4 IT 124
124-BA 124 IT 0 2 2 0128 0129 2 IT 124
124-BB 0 2 2 0130 0131 2 IT 124
125-BA 125 STAFF WORKROOM 0 2 2 0132 0133 2 IT 124
125-BB 0 2 2 0134 0135 2 IT 124
125-DA 0 2 2 0136 0137 2 IT 124
125-DB 0 2 2 0138 0139 2 IT 124
125-EA 0 2 2 0140 0141 2 IT 124
125-EB 0 2 2 0142 0143 2 IT 124
125-EC 0 2 2 0144 0145 2 IT 124
125-ED 0 2 2 0146 0147 2 IT 124
125-ZA 0 2 2 0148 0149 2 IT 124
EXT-YA EXT EXT 0 1 1 0150 1 IT 124
EXT-YB EXT EXT 0 1 1 0151 1 IT 124
EXT-YC EXT EXT 0 1 1 0152 1 IT 124
EXT-YD EXT EXT 0 1 1 0153 1 IT 124
EXT-YE EXT EXT 0 1 1 0154 1 IT 124
EXT-YF EXT EXT 0 1 1 0155 1 IT 124
EXT-YG EXT EXT 0 1 1 0156 1 IT 124
EXT-YH EXT EXT 0 1 1 0157 1 IT 124
EXT-YI EXT EXT 0 1 1 0158 1 IT 124
TOTAL FOR FIRST FLOOR 0 158 158 0 158 0
Min. 48 port patch panel req. 4 4
TOTAL FROM BASEMENT 9 9 9
Min. 48 port patch panel req. 1 1
TOTAL FOR BOTH FLOORS 0 167 167 0 167 0
Min. 48 port patch panel req. 4 4
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TN801
COMM - DEVICE
SCHEDULE
Project Number
(4) #10 SMS TYP
(E) POLYWOOD FLOOR
ADD 3X BLOCKING AT
ANCHORS
BLOCKING TO
MATCH GAUGE
OF WALL STUDS
16GA BENT PL
X 6" LONG
METAL STUD
WALL BEYOND
(4) 3/8"X3" DIA LAG
SCREWS INTO BLOCKING
BLOCKING TO MATCH
GAUGE OF WALL STUDS
16GA BENT PL X 6" LONG
BLOCKING TO MATCH
GAUGE OF WALL STUDS
16GA BENT PL X 6" LONG
(4) 3/8"X3" DIA LAG
SCREWS INTO BLOCKING
ADD 3X BLOCKING AT
ANCHORS
(E) POLYWOOD FLOOR
(E) POLYWOOD FLOOR
(4) #10 SMS TYP
ADD 3X BLOCKING AT
ANCHORS
(4) #10 SMS TYP
METAL STUD
WALL BEYOND
ADD 3X BLOCKING AT
ANCHORS
(4) 3/8"X3" DIA
LAG SCREWS
INTO BLOCKING
METAL STUD
WALL BEYOND
(E) POLYWOOD FLOOR
8X.437
76.750
USABLE DEPTH
22.8 75
19.5 00
34. 85
42. 00
30.00 83.485
OVERALL
1/FAN TOP
77.125
44 USEABLE
RACK SPACES
4.13 O V E R A LL WI D T H ( 3. 25 O P E N I N G WI D T H )
4.25 26.51/31.11
31.125 33.875
29.29/
33.89 .720
2.375 1.473
32.875
27.26/
31.86 2.000
BOTTOM VIEW
REAR DOOR REMOVED
VIEWS SHOWN WITH
FLOOR MOUNTING
LOCATIONS
REMOVABLE SERVICE PLATE
2 RACKSPACE
WITH FAN TOP REMOVED
TOP OPENING DIMENSIONS
19"
WIDTH
PANEL
SCALE .070
DETAIL A
(FAN NOT INCLUDED)
GRILL FOR 10" FAN
TOP VIEW
(DOOR OPEN)
FRONT VIEW
(21X THIS SIDE 17X OTHER SIDE)
CABLE DUCT
VIEW
REAR
VIEW
SIDE
SOLID HINGED
DOOR WITH
CLOSURE
MAGNETIC
4 POINT
REMOVABLE
TOP OPENING
TOP VIEW
1/2" & 3/4"
1" & 1-1/2" KNOCKOUTS
_
D
_
B
FRONT
_
C
OPENING (8X)
.875 X 4.875
A
OPENING 2.250 X 3.000
OPENING (8X)
.875 X 4.875
EKO PLATES
KNOCKOUTS
RACK LOADING DETAIL
2 SHOWN WITHOUT THE DOOR. 1" = 1'-0"
AS NEAR TO THE TOP
(UNINTERUPTED POWER
NEAR TO THE BOTTOM OF
AMPLIFIERS, ETC.) AS
LOAD HEAVY EQUIPMENT
SUPPLIES, POWER
THE RACK AS POSSIBLE
AS POSSIBLE
OF THE RACK
EXCEPT AS OTHERWISE
ANY BLANK PANELS
DIRECTED, PLACE
RACK R28 DETAILS AND ELEVATIONS 1 N.T.S.
D
REAR VIEW C
SIDE VIEW BFRONT VIEW
TKN1
TKN2
TKN1
TKN2
E
KEYNOTES
TKN
TKN1
TKN2
E1 R28 84" 44 EIA RACK UNITS 19" 30" 42"
VPO=VERTICAL PANEL OPENING PANEL WIDTH FRAME WIDTH
DIMENSIONS
TYPE OVERALL HEIGHT NOT TO EXCEED FRAME DEPTH ELECTRICAL: WORK OF DIV. 26. 5-20R DEDICATED QUAD RECEPTACLE IN 4S BOX WITH
UTILITY COVER.
TELECOMMUNICATIONS SYSTEMS: WORK OF DIVISION 27.
RACK RAILS, COMPLY WITH ANSI/EIA-310-D. POSITION
ADJUSTABLE FRONT TO REAR.
LOCKING FRONT AND REAR FULL MESH DOORS. I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TN903
DETAILS - RACK
R28
Project Number
SHEET NOTES
1. REFER TO THE PLAN KEYNOTES AND SPECIFICATION
SECTION 27 05 36 FOR THE TYPE AND SIZE OF TRAY
SPECIFIED IN EA CONDITION CT, CR AND CTW.
INSTALLATION OF TRAY TYPE CONTRARY TO THESE
REQUIREMENTS WILL BE REMOVED AND REPLACED AT NO
COST TO THE CITY AND LIBRARY.
2. BOND ADJACENT TRAY SECTIONS TO EACH OTHER AND
GROUND THE TRAY TO THE GROUND BUS BAR IN EA.
TELECOMMUNICATIONS ROOM IN ACCORDANCE WITH THE
CEC, SPECIFICATION SECTIONS 27 05 26 AND 27 05 36 AND
THE MANUFACTURER'S INSTRUCTIONS.
3. AT EACH TRAY TYPE, PASSING ABOVE COPPER AND FIBER
PATCH PANELS, PROVIDE RADIUSSED DROP OUT FITTINGS
OVER ENTRANCE RACK AND CABINET ENTRANCE INTENDED
FOR VERTICAL CABLE TRANSITION.
4. CONTRACTOR TO USE PRE-MANUFACTURED FITTINGS FOR
ALL JUNCTIONS AND JOINTS IN TYPE CT TRAY.
5. PROVIDE SPLICE KIT FITTINGS AT EACH CR TYPE TRAY
JUNCTION.
6. WHERE TYPE CTW BASKET TRAY IS INDICATED TO BE
SHARED BY STRUCTURED CABLING AND ANOTHER CLASS 2
OR CLASS 3 MEDIA TYPE, PROVIDE A CONTINUOUS
PREMANUFACTURED VERTICAL DIVIDER.
1 CABLE TRAY, WIRE BASKET TYPE CTW
NTS 2
CABLE TRAY, WIRE BASKET
TYPE CTW DIVIDER
NTS 3
CABLE TRAY, WIRE BASKET
TYPE CTW CONDUIT CONNECTOR
NTS
4 CABLE TRAY, WIRE BASKET TYPE CTW
DROP-OUT FITTINGS
NTS 5
CABLE TRAY, WIRE BASKET TYPE CTW
RADIUSSED INSIDE CORNER SHIELD
NTS
8 CABLE RUNWAY,
TYPE CR, SPLICE KIT
7 NTS
CABLE RUNWAY, TYPE CR 6 NTS
CABLE RUNWAY,
TYPE CR, RADIUS DROP
NTS
9 CABLE TRAY, TYPE CT
HORIZONTAL TEE
NTS 10
CABLE TRAY, TYPE CT
HORIZONTAL CROSS
NTS 11
CABLE TRAY, TYPE CT
HORIZONTAL 90
RADIUSED BEND NTS
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TN904
DETAILS - CABLE
TRAYS
Project Number
Legrand®
SYSTEM: Fire Classified Floor Boxes
Catalog Number: RFB4S-FC
11/05/13
20"
16 5/8"
3 7/16
"
RECESSED COVER OPTION
ACCEPTS CARPET AND TILE
INSERTS
FLAT COVER OPTION
CAST IRON BOX SUITABLE FOR
SLAB ON GRADE MOUNTING
CONDITIONS
SHEET METAL CONCRETE
PAN. PROVIDE ADJUSTABLE
DEPTH ASSEMBLY WHERE
REQUIRED TO MATCH FLOOR
DECK.
1-1/4" INTUMESCENT
STEM ASSEMBLIES AT 2
HOUR ASSEMBLIES, 1-1/4 AND
2" AT 3 HOUR ASSEMBLIES
CONDUIT
CEW
A2
A2
A1 TKN2
TKN4
TKN3
TKN1
TYPICAL CONDUIT
SUPPORT
FLEXIBLE CONDUIT
PROVIDE 12" OF SLACK
#4 BARE COPPER LEAVE
12" OF SLACK
RIGID STEEL CONDUIT
RIGID STEEL
CONDUIT
TYPICAL GROUNDING
BUSHING
EXTEND DATA OUTLETS IN MODULAR
FURNITURES RACEWAY. PROVIDE
MODULAR FURNITURE FACEPLATES.
REFER TO PLANS AND SCHEDULES FOR
DEVICES.
DISTRICT FURNISHED
MODULAR FURNITURE
PARTITION RACEWAY
(LOW VOLTAGE SECTION)
2" LIQUIDTIGHT
MODULAR
DESKTOP
FIN. FLOOR
FURNITURE
PARTITION
FLEX CONDUIT
+0"
5C
-
5C
-
ELECTRIFIED
PARTITION
ELECTRIFIED
PARTITION
KEYNOTES
TKN COMMUNICATIONS SYSTEMS: CONFORM WITH DIVISION 27 AND
28. TKN1
TKN2
TKN3
TKN4
ARCHITECTURAL: DIVISIONS 3 THROUGH 14.
MODULAR OPEN PLAN FURNITURE SYSTEM.
ELECTRIFIED OPEN PLAN FURNITURE.
TKN
A1
A2
2 FLOOR BOX TO MODULAR
FURNITURE CONNECTION
NTS 4
FT - TRANSITION FROM WALL
TO ELECTRIFIED PARTITION
NTS
4A
SIDE ELEVATION
4B
FRONT ELEVATION
5 FF4 FURNITURE FEED FLOOR BOX DETAIL
NTS
5C SIDE VIEW
5B PLAN VIEW WITH COVER
5A FF4 ISOMETRIC
1 TYPICAL CONDUIT CROSSING
SEISMIC JOINTS
NTS
FLOOR BOX TYPE FF4. AT FLOORS ABOVE GRADE, AT
CONTRACTOR'S OPTIONS CAN SUBSTITUTE POKE-THRU TYPE FP2.
ONE 1.25" C. TO ACCESSIBLE CEILING LINE, U.O.N.
5S BACKBOX, OR AS REQUIRED TO ACCOMMODATE
INDICATED FILL AND RISER CONDUITS. SET IN
WALL AT P.S.R.H. COORDINATE LOCATION WITH
OWNER'S REPRESENTATIVE TO PROVIDE MINIMUM
VISUAL APPEARANCE AFTER INSTALLATION.
PROVIDE 1-1.25" FLEXIBLE METALLIC CONDUIT.
3 CEW - CONDUIT END WATERFALL
PROVIDE AT HORIZONTAL CONDUIT ENDS 18" OR
MORE ABOVE THE NEXT MEANS OF CABLE SUPPORT.
NTS
6 FC3 FLOORBOX
SLAB ON GRADE CONDITION
SUBMIT COVER OPTIONS FOR SELECTION BY CITY'S REPRESENTATIVE. NTS 7 FC3 FLOOR BOX
ABOVE GRADE CONDITION
ASSEMBLY IS 2 AND 3 HOUR FIRE RATING PER UL 263.
SUBMIT COVER OPTIONS FOR SELECTION BY CITY'S
REPRESENTATIVE.
NTS
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TN905
DETAILS -
COMMUNICATIONS
FLOOR BOXES &
PATHWAYS
Project Number
w-x.y-z
w-x.y-z
w-x.y-z
1001
1025
1002
1026
1004
1027
1005
1028
TKN
TELECOMMUNICATIONS SYSTEMS COMPLY WITH
DIVISION 27.
TKN1
REFER TO THE TEMPLATE DETAIL 1 FOR THE
REQUIREMENT TO INSERT SEQUENTIAL CIRCUIT
NUMBERS IN THE JACK LABEL FIELD.
TKN2
REFER TO THE TEMPLATE DETAIL 1 FOR THE
REQUIREMENT TO INSERT ROOM NUMBER LABELS IN
THE OVERALL WAO LABEL FIELD.
XXXXX
LABEL EACH CABLE WITH THE
SAME DEVICE NUMBER THAT IT IS
CONNECTED TO. PROVIDE
MACHINE PRINTED LABELS, TEXT
HEIGHT OF 0.120 TO 0.125.
PROVIDE BLANK
INSERTS ON ALL
UNUSED OPENINGS,
TYP.
WALL MOUNTED TEL.
MOUNTING STUDS
PROVIDE RJ-45
KEYSTONE
CAT6 JACK
RECESSED
JACK INSERT
REAR FACE
FRONT FACE
SEQUENCE # SEQUENCE #
SEQUENCE # SEQUENCE #
1001 1002
1003 1004
48 46 44 42 40 38 36 34 32
20 43
22 45
24 47
23 21 19
14 37
18 41
16 39
8 31
10 33
12 35
17 15 13 11 9 7
30 28 26
2 25
6 29
4 27
5 3 1
TKN1 TKN1 TKN1
TKN1
TKN2
TKN2
TKN2 TKN2 TKN2
SHEET NOTES KEYNOTES
1. WORK AREA OUTLET (WAO) ELEVATIONS ARE PROVIDED
AS A CONVENIENCE FOR THE CONTRACTOR ONLY. WAO
ELEVATIONS GENERALLY REFLECT DESIGN BASIS
ALTERNATE. CONTRACTOR TO COORDINATE REQUIRED
ARRANGEMENTS AND LABELING REQUIREMENT WITH
CITY AND LIBRARY’S REPRESENTATIVE FOR ANY WAO
ALTERNATE SUBMITTED.
2. WAO ELEVATIONS PROVIDED MAY BE INCOMPLETE,
REFER TO SYMBOL SCHEDULE, PLANS AND DEVICE
SCHEDULES FOR COMPLETE LIST OF ALL WAO COUNTS
AND ARRANGEMENTS REQUIRED. WHERE
ARRANGEMENT AND LABELING REQUIREMENT IS
UNCLEAR, OBTAIN DIRECTION OF CITY AND LIBRARY’S
REPRESENTATIVE BEFORE PROCEEDING.
3. WHERE WAO ELEVATIONS AND DEVICE SCHEDULE
CONFLICT, DEVICE SCHEDULE TAKES PRECEDENCE
OVER WAO ELEVATIONS.
4. ALL LABELING TO BE MACHINE GENERATED – HAND
WRITTEN LABELING UNACCEPTABLE.
5. WAO AND PATCH PANEL LABELING TO BE BLACK
LETTER/NUMBERS ON WHITE BACKGROUND.
6. WAO LABELING TO BE 12 POINT ARIAL FONT, UNLESS
OTHERWISE DIRECTED BY THE CITY AND LIBRARY’S
REPRESENTATIVE.
7. REFER TO SPECIFICATION SECTION 27 05 53 FOR
COMPLETE LABELING REQUIREMENTS.
4 MMP6 - 3 CAT. 6 JACKS 3 NTSMMP6 - 2 CAT. 6 JACKS 2 NTSMMP6 - 1 CAT. 6 JACK NTS
5 630A WALL TEL. PLATE
NTS 6
2 HOLE COMPRESSION LUG
TELECOMMUNICATIONS GROUNDING BUSBAR
REFER TO SECTION 270526 FOR COMPLETE REQUIREMENTS.
WORK OF THIS PROJECT BONDS AND GROUNDS WORK INSTALLED UNDER THE WORK OF THIS PACKAGE TO THE TMGB IN ACCORDANCE WITH SECTION 27 05 26.
NTS
7 COPPER PATCH PANEL/ CABLE LABELING
HALF SIZE
1A WAO LABELING TEMPLATE
NTS 1B
EXAMPLE WAO
LABELED PER TEMPLATE
NTS
1 WAO LABELING STANDARD
NTS
EACH PORT IS LABELED WITH THE SEQUENTIAL NUMBER.
THE NUMBER WILL BE A FOUR DIGIT NUMBER. THE FIRST
NUMBER BEING ASSOCIATED WITH THE FLOOR.
0XXX = BASEMENT
1XXX = FIRST FLOOR
THE TOP LEFT PORT WILL BE FIRST NUMBER IN SEQUENCE.
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TN906
DETAILS -
STRUCTURED
CABLING
Project Number
Created or Revised:
Reproduced courtesy of Underwriters Laboratories, Inc.
R
STI
Specified Technologies Inc. 2 10 Evans Way Somerville, NJ 08876 (800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com PAGE OF Created or Revised:
Reproduced courtesy of Underwriters Laboratories, Inc.
R
STI
Specified Technologies Inc. 2 10 Evans Way Somerville, NJ 08876 (800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com PAGE OF Created or Revised:
Reproduced courtesy of Underwriters Laboratories, Inc.
R
STI
Specified Technologies Inc. 2 10 Evans Way Somerville, NJ 08876 (800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com PAGE OF Created or Revised:
Reproduced courtesy of Underwriters Laboratories, Inc.
R
STI
Specified Technologies Inc. 2 10 Evans Way Somerville, NJ 08876 (800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com PAGE OF Created or Revised:
Reproduced courtesy of Underwriters Laboratories, Inc.
R
STI
Specified Technologies Inc. 2 10 Evans Way Somerville, NJ 08876 (800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com PAGE OF
SHEET NOTES
1. REFER TO SECTION 27 05 33 OF THE SPECIFICATIONS. FOR
QUALITY CONTROL REQUIREMENTS, REFER TO THE QUALITY
CONTROL PORTION OF THE SPECIFICATION.
2. DETAILS SHOWN ARE TYPICAL DETAILS. IF FIELD CONDITIONS
DO NOT MATCH REQUIREMENTS OF TYPICAL DETAILS,
APPROVED ALTERNATE DETAILS SHALL BE UTILIZED. FIELD
CONDITIONS AND DIMENSIONS NEED TO BE VERIFIED FOR
COMPLIANCE WITH THE DETAILS, INCLUDING BUT NOT LIMITED
TO THE FOLLOWING:
TYPE AND THICKNESS OF FIRE-RATED CONSTRUCTION. THE
MINIMUM ASSEMBLY RATING OF THE FIRESTOP ASSEMBLY
SHALL MEET OR EXCEED THE HIGHEST RATING OF THE
ADJACENT CONSTRUCTION.
IF ALTERNATE DETAILS MATCHING THE FIELD CONDITIONS
ARE NOT AVAILABLE, MANUFACTURER'S ENGINEERING
JUDGMENT DRAWINGS ARE ACCEPTABLE. ENGINEERING
JUDGMENTS SHALL FOLLOW THE INTERNATIONAL FIRESTOP
COUNCIL (IFC) GUIDELINES FOR EVALUATING FIRESTOP SYSTEMS ENGINEERING JUDGMENTS.
REFERENCES:
UL FIRE RESISTANCE DIRECTORY, CURRENT EDITION.
NFPA 101 LIFE SAFETY CODE
ALL GOVERNING LOCAL AND REGIONAL BUILDING CODES
FIRESTOP SYSTEM INSTALLATION MUST MEET REQUIREMENTS
OF ASTM E814 (UL 1479) TESTED ASSEMBLIES THAT PROVIDE A
FIRE RATING EQUAL TO THAT OF THE SURROUNDING
CONSTRUCTION.
3. 4.
5. 3
3 4
1 2
4 A
A
3 4
2 1
A
A
3 4
4 3
2 2
3 4
1 3 2
3 1
A
A
A
A
2 EZP133CA
EZP133CA
3 4
3 2
1 A
A
System No. C-AJ-3260
F Rating - 2 Hr
T Ratings - 0 and 1/2 Hr (See Item 4)
L Rating At Ambient - Less Than 1, 2.3, 6.2, 6.7 or 7.4 CFM/Device Module (See Item 4) L Rating At 400F - Less Than 1, 2.3, 4.5, 5 or 6.7 CFM/Device Module (See Item 4)
1. Floor or Wall Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Floor may also be constructed of any UL Classified hollow-core Precast Concrete Units*. Diam of opening to be 6 in. (152 mm).
See Concrete Blocks (CAZT) or Precast Concrete Units (CFTV) category in the Fire Resistance Directory for names of manufacturers.
2. Steel Sleeve - (Optional) - Nom 6 in. (152 mm) diam Schedule 10 to Schedule 40 steel pipe or rigid steel conduit cast or grouted into concrete floor or wall flush with floor or wall surfaces.
3. Firestop Device* - One firestop device module centered within the opening. The firestop device module consists of a 4 by 4-5/8 by 14 in. (102 by 118 by 356 mm) long galv steel tube with an intumescent material lining. Series 44 device modules have spring-loaded steel retainer plates. Firestop device module to be installed in accordance with the accompanying installation instructions. The space between the firestop device module and the periphery of the opening shall be min 0 in. (0 mm, point contact) to max 1 in. (25 mm).
Firestop device module secured in place by means of steel restraint plates sized to accommodate the firestop device module. Steel restraint plates each provided with an intumescent gasket and sized to lap onto floor or wall surfaces. Steel restraint plate installed on both sides of floor or wall and secured to firestop device module with steel set screws. The firestop device module is to be installed with its ends projecting an equal distance beyond each surface of the floor or wall assembly. As an option, firestop device may be cast or grouted into floor wall assembly. When device is cast or grouted in place, the steel restraint plates are optional. To achieve air leakage ratings with the Series 44 device module only, integral hook and eye window attachment locations on right and left side of single installed pathways and ganged pathway groups must be sealed using the stickers provided with device module.
SPECIFIED TECHNOLOGIES INC - EZ PATH Series 44 or Series 44+ Fire Rated Pathway 3A. Firestop Device* - Extension Module - (Optional, Not Shown) - Extension module attached to ends of firestop device (Item 3) to increase its length to facilitate installation in thicker floors or walls. Each module consists of a 4 by 4-5/8 by 6 in. (102 by 118 by 152 mm) long galv steel tube with an intumescent material lining. Extension module to be installed in accordance with the accompanying installation instructions. When module is used, firestop device (Item 3) and extension module(s) secured in place by means of steel plates installed with gasketing material supplied with product. Steel plates installed on both sides of floor or wall and secured to device or extension module by means of steel set screws provided with plates. Firestop device and extension module(s) assembly to be installed with ends projecting an equal distance beyond each surface of the floor or wall assembly.
SPECIFIED TECHNOLOGIES INC - EZ PATH Series 44+ Extension January 26, 2011
1 2
C-AJ-3260
Section A-A
System No. F-A-3026
F Rating - 2 Hr
T Rating - 1 Hr
1. Floor Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Floor may also be constructed of any min 6 in. (152 mm) thick hollow-core Precast Concrete Units* .
See Precast Concrete Units category (CFTV) in the Fire Resistance Directory for names of manufacturers.
2. Steel Sleeve - Nom 4 in. (102 mm) diam steel electrical metallic tubing (EMT), steel conduit, Schedule 5 (or heavier) steel pipe or rigid steel conduit cast or grouted into concrete floor. Sleeve to extend min 3/4 in. (19 mm) to max 2 in. (51 mm) from top surface of floor and installed flush with the bottom surface of the floor.
3. Firestop Device* - One firestop device module centered within the steel sleeve. The firestop device module consists of a 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long galv steel tube with an intumescent material lining. Firestop device module to be installed in accordance with the accompanying installation instructions. Firestop device module secured in place by means of split steel restraint plate sized to accommodate the firestop device module. Steel restraint plate provided with an intumescent gasket and sized to cover the space between the firestop device module and the steel sleeve. Steel restraint plate installed on top end of steel sleeve and secured to firestop device module and steel sleeve with steel set screws. The firestop device module is to be installed with its ends projecting an equal distance beyond each edge of the steel sleeve.
SPECIFIED TECHNOLOGIES INC - EZ PATH Series 33 Fire Rated Pathway
4. Cables - Within the loading area for each firestop device module, the cables may represent a 0 to 100 percent visual fill.
Cable fill to be distributed at a uniform height across the width of the firestop device module. Cables to be rigidly supported on both sides of the floor assembly. Any combination of the following types of cables may be used:
A. Max 400 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) jacketing and insulation or with plenum rated jacketing and insulation.
B. Max 350 kcmil single copper conductor power cable with XLPE jacket and insulation.
C. Max 7/C No. 12 AWG copper conductor control cable with PVC or XLPE jacket and insulation.
D. Max 3/C No. 10 AWG metal clad or armored cable with steel or aluminum jacket.
E. Max 3/C No. 8 AWG NM cable (Romex) with PVC insulation and jacket.
F. Max four pair No. 22 AWG (or smaller) copper conductor data cable with PVC or plenum rated jacketing and insulation.
G. Max four pair No. 22 AWG (or smaller) copper conductor data cable with PVC or plenum rated jacketing and insulation.
H. Max RG/U coaxial cable with fluorinated ethylene insulation and jacketing.
I. Fiber optic cable with PVC or polyethylene (PE) jacket and insulation having a max diam of 5/8 in. (16 mm).
J. Aluminum or steel armored optical fiber cables jacketed with polyvinyl chloride (PVC) or polyethylene (PE) jacket and insulation having a max diam of 5/8 in. (16 mm).
K. Optical Fiber Raceway+ - Max 1-1/2 in. (38 mm) diam (or smaller) optical fiber raceway ("innerduct") formed of either PVC or polyvinylidene fluoride (PVDF) with optical fiber cable fill. Raceways installed in accordance with the National Electrical Code (NFPA 70).
+Bearing the UL Listing Mark
*Bearing the UL Classification Mark
April 06, 2007
1 1
F-A-3026
Section A-A
SYSTEM NO. W-J-3099
F RATING - 2 HR (SEE ITEM 1)
T RATINGS - 3/4 AND 1 HR (SEE ITEM 2)
L RATING AT AMBIENT - LESS THAN 1, 1.3, 4 OR 7 CFM/DEVICE (SEE ITEM 3) L RATING AT 400 F - LESS THAN 1, 2 OR 3 CFM/DEVICE (SEE ITEM 3)
1. WALL ASSEMBLY - MIN 6 IN. (152 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3 ) CONCRETE WALL. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. WHEN ITEM 4 IS USED, OPENING TO BE MAX 14 SQ IN. (90 CM2) WITH A MAX DIM OF 4 IN. (102 MM) OR NOMINAL 4 IN. (102 MM) DIAMETER.
SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
2. CABLES - WITHIN THE LOADING AREA FOR EACH FIRESTOP DEVICE MODULE, THE CABLES MAY REPRESENT A 0 TO 100 PERCENT VISUAL FILL. CABLE FILL TO BE DISTRIBUTED AT A UNIFORM HEIGHT ACROSS THE WIDTH OF THE FIRESTOP DEVICE MODULE. CABLES TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE WALL ASSEMBLY. ANY COMBINATION OF THE FOLLOWING TYPES OF CABLES MAY BE USED:
A. MAX 100 NO. 24 AWG (OR SMALLER) COPPER CONDUCTOR TELECOMMUNICATION CABLE WITH POLYVINYL CHLORIDE (PVC) JACKETING AND INSULATION.
B. MAX 350 KCMIL SINGLE COPPER CONDUCTOR POWER CABLE WITH XLPE JACKET AND INSULATION C. MAX 7/C NO. 12 AWG COPPER CONDUCTOR CONTROL CABLE WITH PVC OR XLPE JACKET AND INSULATION.
D. MAX 3/C NO. 10 AWG METAL CLAD OR ARMORED CABLE WITH STEEL OR ALUMINUM JACKET.
E. MAX 3/C NO. 8 AWG NM CABLE (ROMEX) WITH PVC INSULATION AND JACKET.
F. MAX FOUR PAIR NO. 22 AWG (OR SMALLER) COPPER CONDUCTOR DATA CABLE WITH POLYVINYL CHLORIDE (PVC) OR PLENUM RATED JACKETING AND INSULATION.
G. MAX RG/U COAXIAL CABLE WITH FLUORINATED ETHYLENE INSULATION AND JACKETING.
H. FIBER OPTIC CABLE WITH POLYVINYL CHLORIDE (PVC) OR POLYETHYLENE (PE) JACKET AND INSULATION HAVING A MAX DIAM OF 5/8 IN. (16 MM).
February 17, 2010
1 2
W-J-3099
Section A-A
System No. W-J-3138
F Ratings - 2 and 4 Hr (See Item 3)
T Ratings - 3/4, 1 and 1-1/2 Hr (See Item 3)
L Rating At Ambient - Less than 1, 1.3, 4 or 7 CFM (See Item 3) L Rating At 400 F - Less than 1, 2 or 3 CFM (See Item 3)
1. Wall Assembly - Min 6 in. (152 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3 ) concrete wall. Wall may also be constructed of any UL Classified Concrete Blocks*. Opening to be max 1/4 in. (6 mm) larger than width and height dimensions of firestop device.
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. 1A. Steel Sleeve - (Optional, Not Shown) - Nom 4 in. diam Schedule 10 (or heavier) steel pipe, rigid steel conduit, or EMT sleeve cast or grouted into concrete wall flush with wall surfaces.
2. Firestop Device* - Single firestop device module consisting of a 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long galv steel tube with an intumescent material lining. Firestop device to be installed in accordance with the accompanying installation instructions. The space between the firestop device and the periphery of the opening shall be min 0 in. ( 0 mm, point contact) to max 1/2 in. (13 mm). Firestop device secured in place by means of circular steel wall plates installed with gasketing material supplied with product. Circular steel wall plates installed on both sides of wall and secured to device by means of steel set screws provided with device. Firestop device is to be installed with ends projecting an equal distance beyond each surface of the wall assembly.
SPECIFIED TECHNOLOGIES INC - EZ PATH Series 33 Fire Rated Pathway 2A. Firestop Device* - Extension Module - (Optional, Not Shown) - Module attached to ends of 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long firestop device (Item 3) to increase its length to facilitate installation in thicker walls. Each module consists of a 3 by 3 by 6 in. (76 by 76 by 152 mm) long galv steel tube with an intumescent material lining. Extension module to be installed in accordance with the accompanying installation instructions. When module is used, firestop device (Item 2) and extension module(s) secured in place by means of steel wall plates installed with gasketing material supplied with product.
Steel wall plates installed on both sides of wall and secured to device or extension module(s) by means of steel set screws provided with wall plates. Firestop device and extension module(s) assembly to be installed with ends projecting an equal distance beyond each surface of the wall assembly.
SPECIFIED TECHNOLOGIES INC - EZ PATH Extension
February 17, 2010
1 2
W-J-3138
System No. W-J-3150
F Rating - 2 Hr
T Rating - 1 Hr
1. Wall Assembly - Min 5 in. (127 mm) thick reinforced lightweight or normal weight (100-150 pcf) concrete. Wall assembly may also be constructed of any UL Classified Concrete Blocks *. Max diam of opening is 4-1/2 in. (114 mm).
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Steel Sleeve/Conduit - Nom 4 in. (102 mm) diam steel electrical metallic tubing (EMT), steel conduit or Schedule 5 (or heavier) steel pipe cast or grouted into wall assembly. Conduit to run continuously on one side of the wall and extend min 3/4 in. (19 mm) to max 6 in. (152 mm) beyond second wall surface. Sleeve to extend min 3/4 in. (19 mm) to max 6 in. (152 mm) beyond one or both wall surfaces.
3. Firestop Device * - One firestop device module centered within the steel sleeve. The firestop device module consists of a 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long galv steel tube with an intumescent material lining. Firestop device module to be installed in accordance with the accompanying installation instructions. Firestop device module secured in place by means of split steel restraint plate(s) sized to accommodate the firestop device module. Steel restraint plate(s) each provided with an intumescent gasket and sized to cover the space between the firestop device module and the steel sleeve. Steel restraint plate/module assembly installed on open end of steel conduits and on both ends of steel sleeves that are shorter than 8-1/2 in. (216 mm) in total length. Steel restraint plates secured to firestop device module and to steel sleeve or conduit with steel set screws.
SPECIFIED TECHNOLOGIES INC - EZ PATH
4. Cables - The cable fill within the loading area of the firestop device module may represent a 0 to 100 percent visual fill. Cable fill to be distributed at a uniform height across the width of the firestop device module. Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types of cables may be used:
A. Max 400 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) jacketing and insulation or with plenum rated jacketing and insulation.
B. Max 350 kcmil single copper conductor power cable with XLPE jacket and insulation C. Max 7/C No. 12 AWG copper conductor control cable with PVC or XLPE jacket and insulation.
D. Max 3/C No. 10 AWG metal clad or armored cable with steel or aluminum jacket.
E. Max 3/C No. 8 AWG NM cable (Romex) with PVC insulation and jacket.
F. Max four pair No. 22 AWG (or smaller) copper conductor data cable with PVC or plenum rated jacketing and insulation.
G. Max four pair No. 22 AWG (or smaller) copper conductor data cable with PVC or plenum rated jacketing and insulation.
H. Max RG/U coaxial cable with fluorinated ethylene insulation and jacketing.
I. Fiber optic cable with PVC or polyethylene (PE) jacket and insulation having a max diam of 5/8 in. (16 mm).
J. Aluminum or steel armored optical fiber cables jacketed with polyvinyl chloride (PVC) or polyethylene (PE) jacket and insulation having a max diam of 5/8 in. (16 mm).
K. Optical Fiber Raceway + - Max 1-1/2 in. (38 mm) diam (or smaller) optical fiber raceway (“innerduct”) formed of either PVC or polyvinylidene fluoride (PVDF) with optical fiber cable fill. Raceways installed in accordance with the National Electrical Code (NFPA 70).
5. Fill, Void or Cavity Material * - Putty - (Not Shown) - When sleeves are longer than 8-1/2 in. (216 mm) in length, SpecSeal Putty applied to a min 1 in. (25 mm) thickness within steel sleeve around device or cables, flush with edge of steel sleeve on side of opening opposite split steel restraint plate.
SPECIFIED TECHNOLOGIES INC - SpecSeal Putty
+Bearing the UL Listing Mark
*Bearing the UL Classification Mark
April 6, 2007
1 1
W-J-3150
Section A-A
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TN907
DETAILS - SEALANT
RE-ENTERABLE
THROUGH
PENETRATION
Project Number
Created or Revised:
Reproduced courtesy of Underwriters Laboratories, Inc.
Created or Revised:
Reproduced courtesy of Underwriters Laboratories, Inc.
Created or Revised:
Reproduced courtesy of Underwriters Laboratories, Inc.
SHEET NOTES
1. REFER TO SECTION 27 05 33 OF THE SPECIFICATIONS. FOR
QUALITY CONTROL REQUIREMENTS, REFER TO THE QUALITY
CONTROL PORTION OF THE SPECIFICATION.
2. DETAILS SHOWN ARE TYPICAL DETAILS. IF FIELD CONDITIONS
DO NOT MATCH REQUIREMENTS OF TYPICAL DETAILS,
APPROVED ALTERNATE DETAILS SHALL BE UTILIZED. FIELD
CONDITIONS AND DIMENSIONS NEED TO BE VERIFIED FOR
COMPLIANCE WITH THE DETAILS, INCLUDING BUT NOT LIMITED
TO THE FOLLOWING:
TYPE AND THICKNESS OF FIRE-RATED CONSTRUCTION. THE
MINIMUM ASSEMBLY RATING OF THE FIRESTOP ASSEMBLY
SHALL MEET OR EXCEED THE HIGHEST RATING OF THE
ADJACENT CONSTRUCTION.
IF ALTERNATE DETAILS MATCHING THE FIELD CONDITIONS
ARE NOT AVAILABLE, MANUFACTURER'S ENGINEERING
JUDGMENT DRAWINGS ARE ACCEPTABLE. ENGINEERING
JUDGMENTS SHALL FOLLOW THE INTERNATIONAL FIRESTOP
COUNCIL (IFC) GUIDELINES FOR EVALUATING FIRESTOP SYSTEMS ENGINEERING JUDGMENTS.
REFERENCES:
UL FIRE RESISTANCE DIRECTORY, CURRENT EDITION.
NFPA 101 LIFE SAFETY CODE
ALL GOVERNING LOCAL AND REGIONAL BUILDING CODES
FIRESTOP SYSTEM INSTALLATION MUST MEET REQUIREMENTS
OF ASTM E814 (UL 1479) TESTED ASSEMBLIES THAT PROVIDE A
FIRE RATING EQUAL TO THAT OF THE SURROUNDING
CONSTRUCTION.
3. 4.
5. AA
32 3
2 1A 1B
2 3
4 4
1B
1A
1B
3 1A
3 2
2 AA
3 4
3 5
2 1B
1A
AA
AA
EZP133CA
Section A-A
System No. W-L-3248
F Ratings - 1 and 2 Hr (See Item 1)
T Ratings - 3/4 and 1 Hr (See Item 2)
1. Wall Assembly - The 1 or 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described within the individual U300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall incorporate the following construction features:
A. Studs - Wall framing shall consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Opening in gypsum board to accommodate firestop device may be square or rectangular.
Min distance between periphery of through opening and edge of two-piece steel plate (Item 3) is 1 in. (25 mm).
The hourly F Rating of the firestop system is dependent upon the hourly rating of the wall in which it is installed.
2. Cables - Within the loading area for each firestop device module, the cables may represent a 0 to 100 percent visual fill. Cable fill to be distributed at a uniform height across the width of the firestop device module. Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types of cables may be used:
A. Max 100 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) jacketing and insulation.
B. Max 350 kcmil single copper conductor power cable with XLPE jacket and insulation C. Max 7/C No. 12 AWG copper conductor control cable with PVC or XLPE jacket and insulation.
D. Max 3/C No. 10 AWG metal clad or armored cable with steel or aluminum jacket.
E. Max 3/C No. 8 AWG NM cable (Romex) with PVC insulation and jacket.
F. Max four pair No. 22 AWG (or smaller) copper conductor data cable with polyvinyl chloride (PVC) jacketing and insulation.
G. Max RG/U coaxial cable with fluorinated ethylene insulation and jacketing.
R
STI
Specified Technologies Inc. 2
10 Evans Way Somerville, NJ 08876
(800)992-1180
(908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com Section A-A
System No. W-L-3256
F Ratings - 1 and 2 Hr (See Item 1)
T Ratings - 1, 1-1/4 and 1-3/4 Hr (See Item 2)
L Rating At Ambient - Less Than 1 or 1.4 CFM (See Item 3) L Rating At 400 F - Less Than 1 or 1.4 CFM (See Item 3)
1. Wall Assembly - The 1 or 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described within the individual U300, U400 or V400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall incorporate the following construction features:
A. Studs - Wall framing shall consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design.
Opening in gypsum board to accommodate firestop device to be max 3 in. (76 mm) wide by max 2-1/2 in. (64 mm) high. or nom 2 in. (51 mm) diameter.
The hourly F Rating of the firestop system is dependent upon the hourly rating of the wall in which it is installed.
2. Cables - Within the loading area for each firestop device module, the cables may represent a 0 to 100 percent visual fill. Cable fill to be distributed at a uniform height across the width of the firestop device module. Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types of cables may be used:
A. Max four pair No. 22 AWG (or smaller) copper conductor data cable with polyvinyl chloride (PVC) or plenum rated jacketing and insulation.
B. Max RG/U coaxial cable with fluorinated ethylene insulation and jacketing.
C. Fiber optic cable with polyvinyl chloride (PVC) or polyethylene (PE) jacket and insulation having a max diam of 1/4 in. (6 mm).
The T Rating is 1 hr and 1-3/4 hr in 1 hr and 2 hr rated walls, respectively, when no cables are installed in firestop device. The T Rating is 1 hr and 1-1/4 hr in 1 hr and 2 hr rated walls, respectively, when cables are installed in firestop device.
The L Rating for the empty firestop device is less than 1.4 cfm at ambient and at 400F. When Item 3A is used, the L Rating with 100 percent visual fill of cable is less than 1 CFM at ambient and at 400F.
R
STI
Specified Technologies Inc. 2
10 Evans Way Somerville, NJ 08876
(800)992-1180
(908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com Section A-A
System No. W-L-3265
F Ratings - 1, 2, 3 and 4 Hr (See Items 1 and 3)
T Ratings - 3/4, 1 and 1-1/2 Hr (See Item 3)
L Rating At Ambient - Less than 1, 1.3, 4 or 7 CFM (See Item 3) L Rating At 400 F - Less than 1, 2 or 3 CFM (See Item 3)
1. Wall Assembly - The 1, 2, 3 or 4 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described within the individual U300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall incorporate the following construction features:
A. Studs - Wall framing shall consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Max diam of opening to be 4 in. (102 mm).
The hourly F Rating of the firestop system is dependent upon the hourly rating of the wall in which it is installed.
2. Firestop Device* - Single firestop device module consisting of a 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long galv steel tube with an intumescent material lining. Firestop device module to be installed in accordance with the accompanying installation instructions. The space between the firestop device module(s) and the periphery of the opening shall be min 0 in. ( 0 mm, point contact) to max 1/2 in. (13 mm). Firestop device module(s) secured in place by means of circular steel wall plates installed with gasketing material supplied with product. Circular steel wall plates installed on both sides of wall and secured to each device by means of steel set screws provided with device. Firestop device module is to be installed with ends projecting an equal distance beyond each surface of the wall assembly.
SPECIFIED TECHNOLOGIES INC - EZ PATH Series 33 Fire Rated Pathway 2A. Firestop Device* - Extension Module - (Optional, Not Shown) - Module attached to ends of 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long firestop device (Item 3) to increase its length to facilitate installation in thicker walls. Each module consists of a 3 by 3 by 6 in. (76 by 76 by 152 mm) long galv steel tube with an intumescent material lining. Extension module to be installed in accordance with the accompanying installation instructions. When module is used, firestop device (Item 2) and extension module(s) secured in place by means of steel wall plates installed with gasketing material supplied with product.
Steel wall plates installed on both sides of wall and secured to each device or extension module(s) by means of steel set screws provided with wall plates. Firestop device and extension module(s) assembly to be installed with ends projecting an equal distance beyond each surface of the wall assembly.
SPECIFIED TECHNOLOGIES INC - EZ PATH Extension
R
STI
Specified Technologies Inc. 2
10 Evans Way Somerville, NJ 08876
(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com System No. W-L-3287
F Ratings - 1 and 2 Hr (See Item 1)
T Rating - 1 Hr
1. Wall Assembly - The 1 or 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described within the individual U300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall incorporate the following construction features:
A. Studs - Wall framing shall consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum Board * - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design.
Opening in gypsum board to be 4-1/2 in. (114 mm) diameter.
The hourly F Rating of the firestop system is dependent upon the hourly rating of the wall in which it is installed.
2. Steel Sleeve/Conduit - Nom 4 in. (102 mm) diam steel electrical metallic tubing (EMT), steel conduit or Schedule 5 (or heavier) steel pipe friction-fitted into 4-1/2 in. (114 mm) diam cutouts in gypsum board. Conduit to run continuously on one side of the wall and extend min 3/4 in. (19 mm) to max 6 in. (152 mm) beyond second wall surface. Sleeve to extend min 3/4 in. (19 mm) to max 6 in. (152 mm) beyond one or both wall surfaces.
3. Firestop Device * - One firestop device module centered within the steel sleeve. The firestop device module consists of a 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long galv steel tube with an intumescent material lining. Firestop device module to be installed in accordance with the accompanying installation instructions. Firestop device module secured in place by means of split steel restraint plate(s) sized to accommodate the firestop device module. Steel restraint plate(s) each provided with an intumescent gasket sized to cover the space between the firestop device module and the steel sleeve. Steel restraint plate/module assembly installed on open end of steel conduit and on both ends of steel sleeve that is shorter than 8-1/2 in. (216 mm) in total length. Steel restraint plates secured to firestop device module and to steel sleeve or conduit with steel set screws.
SPECIFIED TECHNOLOGIES INC - EZ PATH
4. Cables - The cable fill within the loading area of the firestop device module may represent a 0 to 100 percent visual fill. Cable fill to be distributed at a uniform height across the width of the firestop device module. Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types of cables may be used:
A. Max 400 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) jacketing and insulation or with plenum rated jacketing and insulation.
B. Max 350 kcmil single copper conductor power cable with XLPE jacket and insulation Section A-A
R
STI Created or Revised:
Reproduced courtesy of Underwriters Laboratories, Inc.
Specified Technologies Inc. 2
10 Evans Way Somerville, NJ 08876
(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com Created or Revised:
Reproduced courtesy of Underwriters Laboratories, Inc.
Created or Revised:
Reproduced courtesy of Underwriters Laboratories, Inc.
Created or Revised:
Reproduced courtesy of Underwriters Laboratories, Inc.
SHEET NOTES
1. REFER TO SECTION 27 05 33 OF THE SPECIFICATIONS. FOR
QUALITY CONTROL REQUIREMENTS, REFER TO THE QUALITY
CONTROL PORTION OF THE SPECIFICATION.
2. DETAILS SHOWN ARE TYPICAL DETAILS. IF FIELD CONDITIONS
DO NOT MATCH REQUIREMENTS OF TYPICAL DETAILS,
APPROVED ALTERNATE DETAILS SHALL BE UTILIZED. FIELD
CONDITIONS AND DIMENSIONS NEED TO BE VERIFIED FOR
COMPLIANCE WITH THE DETAILS, INCLUDING BUT NOT LIMITED
TO THE FOLLOWING:
TYPE AND THICKNESS OF FIRE-RATED CONSTRUCTION. THE
MINIMUM ASSEMBLY RATING OF THE FIRESTOP ASSEMBLY
SHALL MEET OR EXCEED THE HIGHEST RATING OF THE
ADJACENT CONSTRUCTION.
IF ALTERNATE DETAILS MATCHING THE FIELD CONDITIONS
ARE NOT AVAILABLE, MANUFACTURER'S ENGINEERING
JUDGMENT DRAWINGS ARE ACCEPTABLE. ENGINEERING
JUDGMENTS SHALL FOLLOW THE INTERNATIONAL FIRESTOP
COUNCIL (IFC) GUIDELINES FOR EVALUATING FIRESTOP SYSTEMS ENGINEERING JUDGMENTS.
REFERENCES:
UL FIRE RESISTANCE DIRECTORY, CURRENT EDITION.
NFPA 101 LIFE SAFETY CODE
ALL GOVERNING LOCAL AND REGIONAL BUILDING CODES
FIRESTOP SYSTEM INSTALLATION MUST MEET REQUIREMENTS
OF ASTM E814 (UL 1479) TESTED ASSEMBLIES THAT PROVIDE A
FIRE RATING EQUAL TO THAT OF THE SURROUNDING
CONSTRUCTION.
3. 4.
5. AA
32 3
2 1A 1B
2 3
4 4
1B
1A
1B
3 1A
3 2
2 AA
3 4
3 5
2 1B
1A
AA
AA
EZP133CA
Section A-A
System No. W-L-3248
F Ratings - 1 and 2 Hr (See Item 1)
T Ratings - 3/4 and 1 Hr (See Item 2)
1. Wall Assembly - The 1 or 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described within the individual U300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall incorporate the following construction features:
A. Studs - Wall framing shall consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Opening in gypsum board to accommodate firestop device may be square or rectangular.
Min distance between periphery of through opening and edge of two-piece steel plate (Item 3) is 1 in. (25 mm).
The hourly F Rating of the firestop system is dependent upon the hourly rating of the wall in which it is installed.
2. Cables - Within the loading area for each firestop device module, the cables may represent a 0 to 100 percent visual fill. Cable fill to be distributed at a uniform height across the width of the firestop device module. Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types of cables may be used:
A. Max 100 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) jacketing and insulation.
B. Max 350 kcmil single copper conductor power cable with XLPE jacket and insulation C. Max 7/C No. 12 AWG copper conductor control cable with PVC or XLPE jacket and insulation.
D. Max 3/C No. 10 AWG metal clad or armored cable with steel or aluminum jacket.
E. Max 3/C No. 8 AWG NM cable (Romex) with PVC insulation and jacket.
F. Max four pair No. 22 AWG (or smaller) copper conductor data cable with polyvinyl chloride (PVC) jacketing and insulation.
G. Max RG/U coaxial cable with fluorinated ethylene insulation and jacketing.
R
STI
Specified Technologies Inc. 2
10 Evans Way Somerville, NJ 08876
(800)992-1180
(908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com Section A-A
System No. W-L-3256
F Ratings - 1 and 2 Hr (See Item 1)
T Ratings - 1, 1-1/4 and 1-3/4 Hr (See Item 2)
L Rating At Ambient - Less Than 1 or 1.4 CFM (See Item 3) L Rating At 400 F - Less Than 1 or 1.4 CFM (See Item 3)
1. Wall Assembly - The 1 or 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described within the individual U300, U400 or V400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall incorporate the following construction features:
A. Studs - Wall framing shall consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design.
Opening in gypsum board to accommodate firestop device to be max 3 in. (76 mm) wide by max 2-1/2 in. (64 mm) high. or nom 2 in. (51 mm) diameter.
The hourly F Rating of the firestop system is dependent upon the hourly rating of the wall in which it is installed.
2. Cables - Within the loading area for each firestop device module, the cables may represent a 0 to 100 percent visual fill. Cable fill to be distributed at a uniform height across the width of the firestop device module. Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types of cables may be used:
A. Max four pair No. 22 AWG (or smaller) copper conductor data cable with polyvinyl chloride (PVC) or plenum rated jacketing and insulation.
B. Max RG/U coaxial cable with fluorinated ethylene insulation and jacketing.
C. Fiber optic cable with polyvinyl chloride (PVC) or polyethylene (PE) jacket and insulation having a max diam of 1/4 in. (6 mm).
The T Rating is 1 hr and 1-3/4 hr in 1 hr and 2 hr rated walls, respectively, when no cables are installed in firestop device. The T Rating is 1 hr and 1-1/4 hr in 1 hr and 2 hr rated walls, respectively, when cables are installed in firestop device.
The L Rating for the empty firestop device is less than 1.4 cfm at ambient and at 400F. When Item 3A is used, the L Rating with 100 percent visual fill of cable is less than 1 CFM at ambient and at 400F.
R
STI
Specified Technologies Inc. 2
10 Evans Way Somerville, NJ 08876
(800)992-1180
(908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com Section A-A
System No. W-L-3265
F Ratings - 1, 2, 3 and 4 Hr (See Items 1 and 3)
T Ratings - 3/4, 1 and 1-1/2 Hr (See Item 3)
L Rating At Ambient - Less than 1, 1.3, 4 or 7 CFM (See Item 3) L Rating At 400 F - Less than 1, 2 or 3 CFM (See Item 3)
1. Wall Assembly - The 1, 2, 3 or 4 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described within the individual U300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall incorporate the following construction features:
A. Studs - Wall framing shall consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Max diam of opening to be 4 in. (102 mm).
The hourly F Rating of the firestop system is dependent upon the hourly rating of the wall in which it is installed.
2. Firestop Device* - Single firestop device module consisting of a 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long galv steel tube with an intumescent material lining. Firestop device module to be installed in accordance with the accompanying installation instructions. The space between the firestop device module(s) and the periphery of the opening shall be min 0 in. ( 0 mm, point contact) to max 1/2 in. (13 mm). Firestop device module(s) secured in place by means of circular steel wall plates installed with gasketing material supplied with product. Circular steel wall plates installed on both sides of wall and secured to each device by means of steel set screws provided with device. Firestop device module is to be installed with ends projecting an equal distance beyond each surface of the wall assembly.
SPECIFIED TECHNOLOGIES INC - EZ PATH Series 33 Fire Rated Pathway 2A. Firestop Device* - Extension Module - (Optional, Not Shown) - Module attached to ends of 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long firestop device (Item 3) to increase its length to facilitate installation in thicker walls. Each module consists of a 3 by 3 by 6 in. (76 by 76 by 152 mm) long galv steel tube with an intumescent material lining. Extension module to be installed in accordance with the accompanying installation instructions. When module is used, firestop device (Item 2) and extension module(s) secured in place by means of steel wall plates installed with gasketing material supplied with product.
Steel wall plates installed on both sides of wall and secured to each device or extension module(s) by means of steel set screws provided with wall plates. Firestop device and extension module(s) assembly to be installed with ends projecting an equal distance beyond each surface of the wall assembly.
SPECIFIED TECHNOLOGIES INC - EZ PATH Extension
R
STI
Specified Technologies Inc. 2
10 Evans Way Somerville, NJ 08876
(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com System No. W-L-3287
F Ratings - 1 and 2 Hr (See Item 1)
T Rating - 1 Hr
1. Wall Assembly - The 1 or 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described within the individual U300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall incorporate the following construction features:
A. Studs - Wall framing shall consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum Board * - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design.
Opening in gypsum board to be 4-1/2 in. (114 mm) diameter.
The hourly F Rating of the firestop system is dependent upon the hourly rating of the wall in which it is installed.
2. Steel Sleeve/Conduit - Nom 4 in. (102 mm) diam steel electrical metallic tubing (EMT), steel conduit or Schedule 5 (or heavier) steel pipe friction-fitted into 4-1/2 in. (114 mm) diam cutouts in gypsum board. Conduit to run continuously on one side of the wall and extend min 3/4 in. (19 mm) to max 6 in. (152 mm) beyond second wall surface. Sleeve to extend min 3/4 in. (19 mm) to max 6 in. (152 mm) beyond one or both wall surfaces.
3. Firestop Device * - One firestop device module centered within the steel sleeve. The firestop device module consists of a 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long galv steel tube with an intumescent material lining. Firestop device module to be installed in accordance with the accompanying installation instructions. Firestop device module secured in place by means of split steel restraint plate(s) sized to accommodate the firestop device module. Steel restraint plate(s) each provided with an intumescent gasket sized to cover the space between the firestop device module and the steel sleeve. Steel restraint plate/module assembly installed on open end of steel conduit and on both ends of steel sleeve that is shorter than 8-1/2 in. (216 mm) in total length. Steel restraint plates secured to firestop device module and to steel sleeve or conduit with steel set screws.
SPECIFIED TECHNOLOGIES INC - EZ PATH
4. Cables - The cable fill within the loading area of the firestop device module may represent a 0 to 100 percent visual fill. Cable fill to be distributed at a uniform height across the width of the firestop device module. Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types of cables may be used:
A. Max 400 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) jacketing and insulation or with plenum rated jacketing and insulation.
B. Max 350 kcmil single copper conductor power cable with XLPE jacket and insulation Section A-A
R
STI Created or Revised:
Reproduced courtesy of Underwriters Laboratories, Inc.
Specified Technologies Inc. 2
10 Evans Way Somerville, NJ 08876
(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com IUEI HU 9 AS.OAN FRANC
4080
HINS
L11
ALERC
NDEN VA
NING,
CRAE
ITE
C
T
SCSNN
G R O U P
7 S
5 06C
8 710
2PRA
O
90 A
EUC+
ER4
SHEET TITLE AND NO. ISSUE DAT
E
PROJECT: CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD-PLAN CHECK 08/29/2024
-MO/DA/YEAR
TN908
DETAILS - SEALANT
RE-ENTERABLE
THROUGH
PENETRATION
Project Number
KEYNOTE REFERENCES
SCOPE OF KEYNOTES USED. **** IS A 4 DIGIT NUMBER FOLLOWING
THE PREFIX
KEYNOTE REFERENCE
AKN****
ARCHITECTURAL. CONFORM WITH WITH THE
REQUIREMENTS OF DIVISIONS 3-14. SEE
ARCHITECTURAL AND INTERIOR DRAWINGS FOR
ADDITIONAL DETAILS.
MKN****
MECHANICAL/PLUMBING. CONFORM WITH WITH THE
REQUIREMENTS OF DIVISIONS 22-23. SEE
MECHANICAL AND PLUMBING DRAWINGS FOR
ADDITIONAL INFORMATION.
EKN****
ELECTRICAL. CONFORM WITH WITH THE
REQUIREMENTS OF SPECIFICATION DIVISION 26 AND
THE FIRE ALARM SECTIONS OF DIVISION 28. SEE
ELECTRICAL AND FIRE ALARM DRAWINGS FOR
ADDITIONAL INFORMATION.
TKN****
COMMUNICATIONS AND ELECTRONIC SECURITY
SYSTEMS. CONFORM WITH WITH THE
REQUIREMENTS OF SPECIFICATION DIVISION 27 AND
THE ELECTRONIC SECURITY SECTIONS OF DIVISION
28. SEE TA, TN AND TY DRAWINGS FOR ADDITIONAL
INFORMATION.
FOH-P FIBER OPTIC CABLE HYBRID, PLENUM RATED
1IDP 1" INNERDUCT, PLENUM RATED
2IDP 2" INNERDUCT, PLENUM RATED
SEE SPECIFICATION SECTIONS FOR REFERENCE DESCRIPTIONS
AND REQUIREMENTS. FOR OTHER MATERIAL AND EQUIPMENT
NOTE:
UTP5e-4P UNSHIELDED TWISTED PAIR, CAT. 5e PLENUM
TB15 TERMINAL BLOCK WITH 15 AMP SWITCH BLADE.
XX- NO OF PAIRS
110 TERMINAL BLOCK, PRE-WIRED W/50 PIN CONNECTOR,
110TBXX 110 TERMINAL BLOCK, CAT.5, XX-NO OF PAIRS
110PWTBXX
CATEGORY 5e PATCH PANEL
FIBER SPLICE PANEL
FIBER SPLICE CLOSURE
FIBER PATCH PANEL
FIBER TERMINAL BOX
OUTSIDE PLANT
MULTIMEDIA PLATE
UNSHIELDED TWISTED PAIR, CAT. 5e
MULTI MODE OPTICAL FIBER
SINGLE MODE OPTICAL FIBER
MAIN DISTRIBUTION FACILITY.
FIBER OPTIC CABLE HYBRID, OUTSIDE PLANT RISER RATED
FIBER OPTIC CABLE, SINGLE MODE OUTSIDE PLANT RISER RATED
FIBER OPTIC CABLE, MULTI MODE OUTSIDE PLANT RISER RATED
INTERMEDIATE DISTRIBUTION FACILITY
UNSHIELDED TWISTED PAIR, CAT. 5e OUTSIDE PLANT
C5ePP
FOH-OPR
FOM-OPR
FOS-OPR
FPP
MDF
IDF
FTB
FSP
FSC
MM
MMP
OSP
UTP5e-4
SM
MATERIAL & EQUIPMENT LEGEND
UTP5e-4OP
OPP. OPPOSITE
SIM. SIMILAR
ON CENTER
NOT TO SCALE
PANEL
PROJECT
OUTSIDE DIAMETER
OWNER FURNISHED EQUIPMENT
NATIONAL ELECTRICAL CODE
NOT IN CONTRACT
REFER TO
REFERENCE
SPECIFICATION
SHEET NOTE
SURFACE RACEWAY
SINGLE MODE OPTICAL FIBER
SHIELDED PAIR - SEE SPECIFICATIONS
PROJECT STANDARD RECEPTACLE HEIGHT +18" AFF, U.O.N.
PROJECT STANDARD SWITCH HEIGHT +48" AFF TO , U.O.N.
TELEPHONE
TYPICAL
TWISTED PAIR
TELECOMMUNICATIONS
TELECOMMUNICATIONS CLOSET
SHIELDED TWISTED PAIR
WITH
WEATHERPROOF
UNLESS OTHERWISE NOTED
TELECOMMUNICATIONS INDUSTRY ASSOCIATION
STANDARD
NEC
N.I.C.
O.D.
O.C.
NTS
O.F.E.
PROJ.
PNL.
RE:
P.S.S.H.
REF.
SP
SN
S.R.
SPEC
SM
P.S.R.H
STP
TEL
TELCOM
T.C.
TIA
TYP.
TP
W/
WP
U.O.N.
STD
FOR COMMUNICATIONS AND POWER SYSTEM
NEW WIRE AND/OR CABLE INSIDE NEW CONDUIT WALLS OR IN CEILING .
PROVIDED UNDER DIV. 26.
CABLE/RACEWAY TURNS UP
CONDUIT. FILL PER SCHEDULE, PLANS
CABLE/RACEWAY TURNS DOWN
NEW WIRE AND/OR CABLE IN (N) UNDERGROUND
AND SPECIFICATION SECTION 28 05 13.
AND SPECIFICATION SECTION 28 05 13.
NEW WIRE AND/OR CABLE IN EXPOSED CONDUIT
OR RACEWAY. FILL PER SCHEDULE, PLANS
MARK INDICATES RACEWAY DROP FROM CEILING.
COORDINATE EXACT LOCATION WITH DIV. 26 PLANS.
SURFACE RACEWAY.
HOME RUN
KEYNOTES
CONDUIT TO CABLE TRANSITION POINT
LEGEND
EA. EACH
C.L. CENTERLINE
ALTERNATE
AMERICANS WITH DISABILITIES ACT
ABOVE MEZZANINE FINISHED FLOOR
ABOVE FINISHED CEILING
ABOVE FINISHED FLOOR
AREA DISTRIBUTION FACILITY
BACK OF HOUSE
BUILDING
COMMUNICATIONS
CATEGORY
CONDUIT
BUILDING DISTRIBUTION FACILITY
BELOW FINISHED CEILING
CALIFORNIA ELECTRICAL CODE
CALIFORNIA BUILDING CODE
SINGLE CHAMBER SURFACE RACEWAY
THREE CHAMBER SURFACE RACEWAY
CONDUIT ONLY
CONTINUATION
DIVISION
EXISTING
DIAMETER
DEDUCTIVE
DEMOLISH EXISTING
COMMUNICATIONS SYSTEM
EQUIPMENT
FINISHED
ELEVATION
END OF LINE
ELECTRONIC INDUSTRIES ASSOCIATION
3SR-2.5
A.D.A.
1SR-1
ADF
A.F.C.
ALT
A.M.F.F.
A.F.F.
BDF
B.F.C.
B.O.H.
BLDG.
CAT.
CBC
COMM.
CEC
C.
C.O.
CONT.
CS
(D)
(E)
EIA
DIV
DED
ELEV.
E.O.L.
FIN
EQPT.
ABBREVIATIONS
FUTURE
HOME RUN
HEIGHT
JUNCTION BOX
MASTER ANTENNA TELEVISION
LOCAL AREA NETWORK
MONUMENT
MAXIMUM
MODULAR
MINIMUM
NEW
H.R.
FUT
HT.
LAN
MATV
J, JBOX
MAX.
MON.
MOD.
MIN.
(N)
REFER TO SPECIFICATIONS FOR COMPLETE REQUIREMENTS.
PROVIDE CONDUIT, BOXES AND FITTINGS SHOWN ON ELECTRONIC SECURITY SYSTEMS (TY) SYSTEM DRAWINGS UNDER THE WORK OF SECTION 28 05 28 PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY. UNLESS OTHERWISE INDICATED, PROVIDE 1 INCH TRADE SIZE MINIMUM . PROVIDE RACEWAY SIZE AS REQUIRED FOR A MAXIMUM OF 30 PERCENT WIRE FILL.
PROVIDE FIRESTOPPING UNDER THE WORK OF SECTION 28 05 28 PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY.
LOCATIONS SHOWN ON THE ARCHITECTURAL DRAWINGS TAKE PRECEDENCE OVER LOCATIONS SHOWN ON THE COMMUNICATIONS SYSTEMS DRAWINGS.
DEVICE QUANTITIES SHOWN ON FLOOR PLANS AND REFLECTED CEILING PLANS TAKE PRECEDENCE OVER DEVICE QUANTITIES SHOWN ON FUNCTIONAL DIAGRAMS.
QUANTITIES SHOWN ON FUNCTIONAL DIAGRAMS TAKE PRECEDENCE OVER QUANTITIES SHOWN ON RACK ELEVATIONS.
QUANTITIES SHOWN ON DEVICE SCHEDULES TAKE PRECEDENCE OVER QUANTITIES SHOWN ON FUNCTIONAL DIAGRAMS, FLOOR PLANS AND REFLECTED CEILING PLANS.
LOCATIONS SHOWN ON LARGE SCALE DRAWINGS TAKE PRECEDENCE OVER LOCATIONS SHOWN ON SMALL SCALE DRAWINGS.
NOT USED.
WIRING FOR THE WORK OF ELECTRONIC SECURITY SYSTEMS IS NOT PERMITTED TO SHARE CONDUIT, SLEEVES OR J-HOOKS WITH WIRING FOR WORK OF DIVISION 27. MAINTAIN AT LEAST 2 INCHES SEPARATION IF RUNNING PARALLEL. MAINTAIN AT LEAST 3 INCHES OF SEPARATION VERTICALLY IF CROSSING AT RIGHT ANGLES.
3 5
4 6
8 9
10 7
ELECTRONIC SECURITY SYSTEMS GENERAL NOTES
1 2
C6PP CATEGORY 6 PATCH PANEL.
UTP6-4P UNSHIELDED TWISTED PAIR, CAT. 6 PLENUM
UNSHIELDED TWISTED PAIR, CAT. 6
UNSHIELDED TWISTED PAIR, CAT. 6 OUTSIDE PLANT
UTP6-4
UTP6-4OP
TYPES REFER TO SPECIFICATIONS.
EXAMPLE: J16C= 30"H X 30"W X 8"D HINGED NEMA 4 JBOX.
ALL JUNCTION BOXES TO BE HINGED TYPE, PROVIDED
(INCHES)
AS REQUIRED FOR INSTALLATION. PAINT ALL INTERIOR
IN JUNCTION BOXES SHALL BE CUT OR PUNCHED
WITHOUT PRE-PUNCHED KNOCKOUTS. PENETRATIONS
BOXES TO MATCH WALL FINISH. COORDINATE FINISH
WITH ARCH. PLANS.
A - NEMA 12
NONE - NEMA 1
B - NEMA 3R
NOTE 1
SUFFIX:
J16
J17
J15
J13
J14
J12
C - NEMA 4
D - NEMA 4X
30 36
30 24
24 24
30 30
24 20
24 20
J8
J11
J10
J9
J6
J7
J5
J1
J4
J3
J2
SYMBOL
20 20
20 20
16 18
12 20
20 16
16 12
18 12
(INCHES)
6 12
12 8
H
6 12
12 8
W
JUNCTION BOX SCHEDULE
(INCHES)
J18 36 36
4 4
4 6
8 6
8 6
8 6
8 6
8 8
8 8
8 8
, DIA.
SHEET NUMBER
WALL SECTION KEY
SHEET NUMBER
DRAWING NUMBER
ELEVATION KEY
DRAWING NUMBER
SHEET NUMBER
DRAWING NUMBER
DETAIL SYMBOL
SHEET NUMBER
REVISION NUMBER
REVISION SYMBOL
BUILDING LABEL
COLUMN GRID
GRID LINES
DRAWING MATCH LINE
SHEET NUMBER
DRAWING NUMBER
ROOM NAME
ROOM NUMBER
ROOM KEY
BLDG. SECTION KEY
DRAWING NUMBER
GENERAL SYMBOLS
O.F.O.I OWNER FURNISHED, OWNER INSTALLED
ACJ
TKN
1 1
1 1
1 1
1 1
1 A1
1 XXXX
XXXX
1 1
1 1
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TY001
ESS - GENERAL
NOTES, LEGEND,
SYMBOLS, ABBR
AND JBOX
SCHEDULE
Project Number
SYMBOL DEVICE FUNCTION OR
SERVICE LOCATION WORK OF ROUGH-IN RACEWAY ELEVATION
CABLE FILL &
HOMERUN
DESTINATION,
U.O.N.
FINISH
WEIGHT,
LB
DETAIL
SHEET(S)
WALL SLEEVE PATHWAY INDICATED 28 05 28 N/A R11
CCTV CAMERA, FIXED FOCUS, TCP/IP. VISUAL SURVEILLANCE INDICATED 28 05 28
28 23 00
WO3
FLUSH 5S BOX, 1 G. RING. AT CMU WALLS,
PROVIDE 3-1/2” DEEP 2 GANG MASONRY BOX
WITH 1 GANG RING. LRI17.
R5 INDICATED PER FUNCTIONAL
SUBMIT FOR
SELECTION BY CITY'S
REP.
TY903
CCTV CAMERA, FIXED FOCUS, TCP/IP,
EXTERIOR. VISUAL SURVEILLANCE INDICATED
28 05 28
28 23 00
WO3
FLUSH CAST 5S BOX. 1 G. RING AT CMU
WALLS, PROVIDE 3-1/2” DEEP 2 GANG
MASONRY BOX WITH 1 GANG RING. LRI17
R5 INDICATED PER FUNCTIONAL
SUBMIT FOR
SELECTION BY CITY'S
REP.
TY903
CCTV CAMERA, 180 DEGREE
HORIZONTAL, 90 DEGREE VERTICAL
CAPABLE MULTI-IMAGER FIXED FOCUS,
TCP/IP, INDOOR/OUTDOOR.
VISUAL SURVEILLANCE INDICATED
28 05 28
28 23 00
WO3
AT INTERIOR, 5S BOX, 1 G. RING. AT CMU
WALLS, PROVIDE 3-1/2” DEEP 2 GANG
MASONRY BOX WITH 1 GANG RING. AT
EXTERIOR, FLUSH CAST 5S BOX. 1 G. RING
LRI17
R5 INDICATED PER FUNCTIONAL
SUBMIT FOR
SELECTION BY CITY'S
REP.
TY903
CCTV CAMERA, 180 DEGREE
HORIZONTAL, 90 DEGREE VERTICAL
CAPABLE MULTI-IMAGER FIXED FOCUS,
WITH HIGH RESOLUTION TCP/IP,
INDOOR/OUTDOOR.
VISUAL SURVEILLANCE INDICATED
28 05 28
28 23 00
WO3
AT INTERIOR, 5S BOX, 1 G. RING. AT CMU
WALLS, PROVIDE 3-1/2” DEEP 2 GANG
MASONRY BOX WITH 1 GANG RING. AT
EXTERIOR, FLUSH CAST 5S BOX. 1 G. RING
LRI17
R5 INDICATED PER FUNCTIONAL
SUBMIT FOR
SELECTION BY CITY'S
REP.
TY903
CCTV CAMERA, 180-270 DEGREE
CAPABLE MULTI-IMAGER FIXED FOCUS,
TCP/IP, INDOOR/OUTDOOR. .
VISUAL SURVEILLANCE INDICATED
28 05 28
28 23 00
WO3
AT INTERIOR, 5S BOX, 1 G. RING. AT CMU
WALLS, PROVIDE 3-1/2” DEEP 2 GANG
MASONRY BOX WITH 1 GANG RING. AT
EXTERIOR, FLUSH CAST 5S BOX. 1 G. RING
LRI17
R5 INDICATED PER FUNCTIONAL
SUBMIT FOR
SELECTION BY CITY'S
REP.
TY903
CCTV CAMERA, 360 DEGREE CAPABLE
MULTI-IMAGER FIXED FOCUS, TCP/IP,
INDOOR/OUTDOOR.
VISUAL SURVEILLANCE INDICATED
28 05 28
28 23 00
WO3
AT INTERIOR, 5S BOX, 1 G. RING. AT CMU
WALLS, PROVIDE 3-1/2” DEEP 2 GANG
MASONRY BOX WITH 1 GANG RING. AT
EXTERIOR, FLUSH CAST 5S BOX. 1 G. RING
LRI17
R5 INDICATED PER FUNCTIONAL
SUBMIT FOR
SELECTION BY CITY'S
REP.
TY903
CARD READER, MULTI-PROTOCOL
PROX/SMART WITH INTEGRAL KEYPAD. ACCESS CONTROL/IDS INDICATED 28 05 28 28 13 00
FLUSH 4-11/16" S BOX, 2-1/8" DEEP MIN., 1 G.
RING. AT CMU WALLS, PROVIDE 3-1/2” DEEP 2
GANG MASONRY BOX WITH 1 GANG RING. AT
EXTERIOR, FLUSH CAST 4S BOX. 1 G. RING
R4 C.L. AT +45" A.F.F
SUBMIT FOR
SELECTION BY CITY'S
REP.
3/TY901
ROUGH-IN FOR CARD READER, FUTURE. PATHWAY INDICATED 28 05 28 FLUSH 4-11/16" S BOX, 2-1/8" DEEP MIN., 1 G.
RING. AT CMU WALLS, PROVIDE 3-1/2” DEEP 2
GANG MASONRY BOX WITH 1 GANG RING. AT
EXTERIOR, FLUSH CAST 4S BOX. 1 G. RING
LRI4. C.L. AT +45" A.F.F
BLANK COVER PLATE
MATCHES
SURROUNDING
ELECTRICAL
CARD READER, MULTI-PROTOCOL
PROX/SMART NARROW DOOR MULLION
MOUNT TYPE
ACCESS CONTROL/IDS INDICATED 28 05 28
28 13 00
MOUNTS TO DOOR MULLION CUTOUT. R4 C.L. AT +45" A.F.F
SUBMIT FOR
SELECTION BY CITY'S
REP.
2/TY901
CARD READER, MULTI-PROTOCOL
PROX/SMART ACCESS CONTROL/IDS INDICATED 28 05 28
28 13 00
FLUSH 4-11/16" S BOX, 2-1/8" DEEP MIN., 1 G.
RING. AT CMU WALLS, PROVIDE 3-1/2” DEEP 2
GANG MASONRY BOX WITH 1 GANG RING. AT
EXTERIOR, FLUSH CAST 4S BOX. 1 G. RING
R4 C.L. AT +45" A.F.F
SUBMIT FOR
SELECTION BY CITY'S
REP.
1/TY901
CARD READER, MULTI-PROTOCOL
PROX/SMART. CRS SHUNTS ALARM OF
DOOR OPERATION IN DIRECTION OF FREE
TRAVEL.
ACCESS CONTROL/IDS INDICATED 28 05 28
28 13 00
FLUSH 4-11/16" S BOX, 2-1/8" DEEP MIN., 1 G.
RING. AT CMU WALLS, PROVIDE 3-1/2” DEEP 2
GANG MASONRY BOX WITH 1 GANG RING. AT
EXTERIOR, FLUSH CAST 4S BOX. 1 G. RING
R4 C.L. AT +45" A.F.F
SUBMIT FOR
SELECTION BY CITY'S
REP.
1/TY901
2/TY901
DURESS ALARM, CASEWORK MTD. ACCESS CONTROL/IDS LRI16 28 05 28 LRI16 LRI16 N/A
DURESS ALARM TRANSITION ELECTRONIC SECURITY
SYSTEMS PATHWAY
INDICATED –
COORDINATE
WITH FURN. PLAN
28 05 28
4S BOX, 2-1/8" DEEP MIN., W 1 GANG RING.
BLANK COVER PLATE WITH GROMMETED
OPENING.
R3, R8 +18 INCHES AFF N/A
BLANK COVER PLATE
MATCHES
SURROUNDING
ELECTRICAL
DOOR POSITION SWITCH ACCESS CONTROL/IDS LRI2 28 05 28
28 13 00
LRI2 R4 AS DETAILED
TY901
TY902
DURESS ALARM, WALL MTD. ACCESS CONTROL/IDS INDICATED 28 05 28 4S BOX, 2-1/8" DEEP MIN., W/ 1 GANG RING,
U.O.N.
R4 +47" A.F.F TO TOP OF JBOX
ELECTRIC LOCK. AT ER, LOCK
INCORPORATES INTEGRAL
MICRO-SWITCH REX.
ACCESS CONTROL/IDS INDICATED WO1 MUD BOX AT SOLID GROUTED DOOR FRAMES R4
WIRE TO MIDDLE HINGE OF
DOOR OPPOSITE LOCK
TY901
TY902
CKP
DC
DS
CRS
DW
DT
4 CN
CR
EL ER
CF
3 2
2 H
FE I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TY002
ESS - SYMBOL
SCHEDULE
Project Number
PHA
GLASS BREAK DETECTOR. ACCESS CONTROL/IDS INDICATED 28 05 28 28 13 00 LRI3 R1
AT SUSPENDED CLG.
CONDITIONS, 12" MIN. BELOW
CLG. ELSEWHERE, +15' AFF ON
WALLS, U.O.N.
GLASS BREAK DETECTOR, CEILING ACCESS CONTROL/IDS INDICATED 28 05 28 28 13 00 LRI5 R1 AT UNDERSIDE OF CEILING
GATE POSITION SWITCH INTRUSION DETECTION INDICATED 28 05 28 28 13 00 LRI12 R4
PER FUNCTIONAL
DOOR HARDWARE INCORPORATES
INTEGRAL MICRO-SWITCH REX. ACCESS CONTROL/IDS INDICATED M MUD BOX AT SOLID GROUTED DOOR FRAMES R4
WIRE TO MIDDLE HINGE OF
DOOR.
TY901
TY902
ROOF HATCH SWITCH INTRUSION DETECTION INDICATED, ON
LATCH SIDE
28 05 28
28 13 00 LRI13 R1
ON FRAMING ADJACENT TO
HATCH
J-BOX WITH BLANK FACE PLATE ELECTRONIC SECURITY
SYSTEMS PATHWAY INDICATED 28 05 28 4S BOX, 2-1/8" DEEP MIN., U.O.N. R4 INDICATED
BLANK COVER PLATE
MATCHES
SURROUNDING
ELECTRICAL
2 INTRUSION DETECTION SYSTEM KEYPAD ACCESS CONTROL/IDS INDICATED 28 05 28 28 13 00
FLUSH 4-11/16" S BOX, 2-1/8" DEEP MIN., 1 G.
RING. AT CMU WALLS, PROVIDE 3-1/2” DEEP 2
GANG MASONRY BOX WITH 1 GANG RING. AT
EXTERIOR, FLUSH CAST 4S BOX. 1 G. RING
R4 C.L. AT +45" A.F.F
SUBMIT FOR
SELECTION BY CITY'S
REP.
LOCAL ALARM, WALL MOUNT WITH
PROJECT STANDARD KEY CYLINDER FOR
LOCAL OVERRIDE
ACCESS CONTROL/IDS INDICATED 28 05 28
28 13 00 FLUSH 3 GANG BOX, 2-1/8" DEEP MIN., 1 G. RING R4 C.L. AT +45" A.F.F PER FUNCTIONAL
BLANK COVER PLATE
MATCHES
SURROUNDING
ELECTRICAL
11/TY901
MOTION DETECTOR ACCESS CONTROL/IDS INDICATED 28 05 28
28 13 00 LRI3 R1
AT SUSPENDED CLG.
CONDITIONS, 12" MIN. BELOW
CLG. ELSEWHERE, +15' AFF ON
WALLS, U.O.N.
MOTION DETECTOR, CEILING. ACCESS CONTROL/IDS INDICATED 28 05 28 28 13 00 LRI5 R1 AT UNDERSIDE OF CEILING
PANIC HARDWARE WITH INTEGRAL
REQUEST TO EXIT MICROSWITCH AND
LOCAL ALARM FUNCTIONALITY
ACCESS CONTROL/IDS MOUNTED TO
DOOR. WO1 MUD BOX AT SOLID GROUTED DOOR FRAMES R4
WIRE TO MIDDLE HINGE OF
DOOR OPPOSITE LOCK
PER FUNCTIONAL
TY901
TY902
POWERED OPERATOR, MOTOR ASSISTED
DOOR ACCESS CONTROL/IDS
WHERE
INDICATED ON
THE ELECTRICAL
PLANS OR ARCH
PLANS.
WO2 N/A - STUB TO MOTOR CONTROLLER AT LV
TERMINAL SIDE.
R2
WHERE INDICATED ON THE
ELECTRICAL PLANS OR ARCH
PLANS.
AS REQUIRED -
COORDINATE
INTERFACE TYPE
WITH WORK OF
DIV.S 8 AND 26.
N/A
TY901
TY902
RELEASE BUTTON ACCESS CONTROL/IDS INDICATED 28 05 28
28 13 00
4S BOX, 2-1/8" DEEP MIN., W/ 1 GANG RING,
U.O.N.
R4 +47" A.F.F TO TOP OF JBOX
REQUEST TO EXIT DETECTOR ACCESS CONTROL/IDS INDICATED 28 05 28 28 13 00
4S BOX, 2-1/8" DEEP MIN., W/ 1 GANG RING,
U.O.N., OR ON FRAME
R4 DOOR HEAD FRAME
MATCH TO DOOR
FRAME FINISH
TY901
TY902
LRI12
TOP OF DOOR AND IN DOOR FRAME, NOT MORE THAN 6” FROM JAMB SIDE. INSTALLATION SHALL NOT COMPROMISE FIRE RATING OF DOOR.
LRI13
4S BOX W/ BLANK COVER PLATE W/ GROMMET OPENING MTD WITHIN 6" OF LATCH AT UNDERSIDE OF ROOF.
EXTEND HS TO HATCH FRAME AND INSTALL IN ACCORDANCE WITH MANUFACTURER INSTRUCTIONS.
LRI14 NOT USED
LRI15 AS DETAILED AND/OR SCHEDULED ON THE ARCHITECTURAL DRAWINGS.
LRI16
LOCATE AS DIRECTED BY THE CITY'S REPRESENTATIVE. FASTEN SECURELY TO THE CASEWORK OR WALL STRUCTURE WITH MECHANICAL FASTENERS. CONCEAL CABLING UNDER FURNITURE WITH SURFACE RACEWAY.
AT WALL, PROVIDE 1 GANG BOX WITH 1 GANG BLANK COVER PLATE WITH GROMMETTED OPENING. STUB 3/4” C.
FROM BOX UP TO ACCESSIBLE CEILING.
LRI17
COORDINATE ROUGH-IN WITH DEVICE AND MEANS OF SUPPORT AT EACH LOCATION, INCLUDING PENDANT MOUNT, CORNER MOUNT AND SIMILAR.
RACEWAY NOTES
R1 1/2" C. H.R. TO NEAREST IDS TERMINAL CABINET
R2 3/4" C. H.R. TO NEAREST IDS TERMINAL CABINET
R3 1" C. H.R. TO NEAREST IDS TERMINAL CABINET
R4 AS DETAILED AND/OR SCHEDULED
R5 3/4" C. H.R. TO ACCESSIBLE CEILING OR FLOOR, OR TO SERVING BDF, IDF OR EQUIPMENT ROOM, U.O.N.
R6 1" C. H.R. TO ACCESSIBLE CEILING OR FLOOR, OR TO SERVING BDF, IDF OR EQUIPMENT ROOM, U.O.N.
R7 1-1/4" C. H.R. TO ACCESSIBLE CEILING OR FLOOR, OR TO SERVING BDF, IDF OR EQUIPMENT ROOM, U.O.N.
R8 NOT USED
R9 NOT USED
R10 NOT USED
R11
UNLESS OTHERWISE SHOWN, PROVIDE 1.5" EMT SLEEVE, WITH INSULATED THROAT BUSHING AT EACH END, STUBBED OUT 4 INCHES FROM FACE OF WALL, AT ELEVATION APPROXIMATELY 6 INCHES ABOVE ACCESSIBLE CEILING. INSTALL SLEEVE IN AN ACCESSIBLE LOCATION AS DEFINED IN CALIFORNIA ELECTRICAL CODE, ARTICLE 100 DEFINITIONS. PROVIDE FIRESTOPPING UNDER WORK OF SECTION 28 05 28. BOND TO GROUND. COMPLY WITH DIVISION 26 AND SECTION 28 05 26.
ACCESSIBLE CEILING IS A T-BAR OR SIMILAR GRID BASED, PANELIZED REMOVEABLE CEILING MEETING THE DEFINITION FOR ACCESSIBLE WIRING METHODS IN ARTICLE 100 OF THE CALIFORNIA ELECTRICAL CODE.
NOTE NO. DEVICE NOTES
DN1 NOT USED
WORK OF NOTES
WO1 ELECTRIC LOCK, ELECTRIC STRIKE, DOOR HARDWARE BASED MICROSWITCH REX, TRANSFER HINGE AND/OR PANIC DOOR ALARM INTEGRATED IN PANIC HARDWARE BY DIV. 8, LV FIELD WIRING AND POWER SUPPLIES BY DIVISION 28.
WO2 MOTOR ASSISTED POWER DOOR OPERATOR BY DIVISION 8 AND 26. DOOR ENTRY FROM UNSECURE SIDE UNDER CONTROL OF ACCESS CONTROL SYSTEM.
WO3
CABLING FOR INTERIOR IP CAMERAS AND EXTERIOR CAMERAS MOUNTED TO FACE OF BUILDING PROVIDED OR WITHIN 295 CABLE FEET OF THE MDF PATCH PANELS ARE UNDER THE WORK OF DIVISION 27. SITE CAMERAS BEYOND 295 CABLE FEET FROM THE MDF TO BE CABLED UNDER THE WORK OF 28 23 00.
LOCATION & ROUGH-IN NOTES
LRI1 FLUSH 4S BOX IN WALL ADJ. TO INDICATED LOCATION. FISH CABLE THROUGH FURNITURE TO CITY SELECTED MOUNTING LOCATION.
LRI2 TOP OF DOOR AND IN DOOR FRAME, NOT MORE THAN 6” FROM JAMB SIDE. INSTALLATION SHALL NOT COMPROMISE FIRE RATING OF DOOR.
LRI3 4S BOX W/ 1 GANG RING BLANK COVER PLATE
LRI4 ROUGH-IN & PATHWAY AS DETAILED FOR CR STUBS TO ACCESSIBLE CLG.
LRI5 AT SUSPENDED CLG CONDITIONS, SM 4S BOX, BLANK COVER & FLEX C TO DEVICE. ELSEWHERE MOUNTED IN CEILING ADJ TO DEVICE OR MNT DEVICE TO COVER PLATE.
LRI6
SURFACE MTD 4S BOX WITH BLANK COVER PLATE INSTALLED ADJACENT TO TRACK AND WITHIN 6" OF FLOOR.
PROVIDE ONE DEVICE AT OPPOSITE SIDE OF EACH OPENING. INSTALL DEVICE TO TRACK PER MANUFACTURER'S INSTRUCTION.
LRI7 NOT USED
LRI8 4S BOX W/ BLANK COVER PLATE W/ GROMMET OPENING MTD WITHIN 6" OF LATCH AT UNDERSIDE OF ROOF.
EXTEND HS TO HATCH FRAME AND INSTALL IN ACCORDANCE WITH MANUFACTURER INSTRUCTIONS.
LRI9 4S BOX, 2-1/8" DEEP MIN., W/ 1 GANG RING WITH LOCKING HINGED COVER PLATE (FSR WB-MR2G OR EQUAL).
LRI10 OUTLETS SHALL BE PLACED SO THEY WILL NOT BE COVERED BY AN UNDER-COUNTER CABINET.
LRI11 PROVIDE BACKING AND SUPPORT FOR 5 POUND DEVICE.
GB
GB
GS
HR
HS
PO
MD
MD
LA
KP
RB
REX
J
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TY003
ESS - SYMBOL
SCHEDULE
Project Number
UP
UP
3 3
3 3
3 1
1 3
1 24TH STREET
24TH STREET BYPASS
2101
0643
2102
270
270
270
270
270
TKN2004
(E)
(E)
(E)
TKN2004
270
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
R C
NDE N VA
,N I N G
CRAE
I T E C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
N
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TY100
ESS - SITE PLAN
Project Number
1/16" = 1'-0" 1
ESS - SITE PLAN
KEYNOTES
TKN2004 (E) EXTERIOR IP EXTERIOR CAMERA.
CONTRACTOR TO REMOVE DURING
CONSTRUCTION, THEN FOLLOWING COMPLETION
OF THE WORK, RE-INSTALL TO NEW STRUCTURED
CABLING PROVIDED UNDER THE WORK OF THE
PROJECT, AND PROGRAM TO OPERATE WITH THE
NEW NVR PROVIDED UNDER THE WORK OF THE
PROJECT. CLEAN LENS AND HOUSING, RE-AIM AND
FOCUS AS DIRECTED BY THE CITY/SPL'S
REPRESENTATIVE FOLLOWING RE-INSTALLATION.
UP
UP
JLD
JLD
JLD
JLD
JLD
JLD
JLD
JLD
JLD
YLD
YLD
ALD
ALD
A
ANEW
NEW
A
ANEW
NEW
A
ADVD
DVD
AA
AAUDIO
UDIO
A
ADVD
DVD
J
JDVD
DVD
JAUDIO
ALD
ALD
DVOICE
DVOICE
CR
CR
CR
CN
CR
CN
CR
CR
DS CR
CN
LA
LA
DS
DS
DC
DC
DC
DC
KP
LA
DS
DS
DS
ER
ER
DSER
DSER
DSER
ER
CN
DSER
DS
DS
ER
ER
CR
DSER
ERDSDSER
DS
ER
DS
EL
REX
DC
DT
DT
DW
DS
DS
ER
ER
DT
1 1
A A
2 2
B B
C C
E E
5 F F
3 3
D D
OPEN TO
BELOW
STORAGE
104
HALL
106
ALL GENDER
RESTROOM
105
FOL
112
PATIO
10 CHILDREN
112
STUDY
113
STUDY
114
GROUP
STUDY
117
TEEN
115
MARKETPLACE
116
ADULT
118
STAFF
WORKROOM
125
OFFICE
119
STAFF
BREAKROOM
121
STAFF RR
123
IT
124
AMH/SORTING
122
ENTRY
101
119
STAFF
WORKROOM
125
PATIO
46 121
101B
007
113
114
117
005
004
101
COMMUNITY
MEETING
102
THE STUDIO
110
WELLNESS
108
FAMILY
RESTROOM
109
JANITOR
107
109
108
107
4 4
002
105
104
102B
102
102A
006
LINE OF SOFFIT ABOVE
LINE OF SOFFIT ABOVE
LINE OF SOFFIT ABOVE
106
120
124
123
116B
116A
103
KITCHENETTE
103
101A
003
WHISPER
ROOM (E)
1043
1043
009
008
TKN2002
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
R C
NDE N VA
,N I N G
CRAE
I T E C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
N
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TY201
ESS - FIRST FLOOR
PLAN
Project Number
1/8" = 1'-0" 1
ESS - FIRST FLOOR PLAN
KEYNOTES
TKN2002 CARD READER TO PROVIDE GROUP LOCK/UNLOCK
OF RESTROOM DOORS.
MD
MD
MD
MD
MD MD
MD
2 2
MD
MD
MD
3 3
MD MD
MD
MD
3 3
3 2
3 2
2 2
3 3
3 3
1 1
1 MD MDMD MD MD
MD MD
1 1
A
2 2
B
C
E
5 5
F
3 3
D
OPEN TO ABOVE
9' - 0"
8' - 8 1/8"
8' - 8 1/8"
8' - 8 1/8"
9' - 0"
8' - 11 7/8"
8' - 6 3/4"
8' - 11 7/8"
8' - 11 7/8"
COMMUNITY
MEETING
CHILDREN
THE STUDIO
STUDY
STUDY
GROUP
STUDY
STORAGE
WELLNESS
FAMILY
RESTROOM
ALL GENDER
RESTROOM HALL
FOL
MARKETPLACE
TEEN
ADULT
STAFF
BREAKROOM
STAFF RR
IT
AMH/SORTING
STAFF
WORKROOM
STAFF
WORKROOM
OFFICE
ENTRY
JANITOR
KITCHENETTE
4 4
0939
9' - 1 3/8"
7' - 6"
9' - 1 3/8"
9' - 1 3/8"
9' - 0"
9' - 1"
0123
ACT-1
ACT-1
ACT-1
T-1
T-1
T-1
G-1
G-1
G-1
W-1
W-1
W-1
W-1
T-1
G-1
G-1
ACT-1
ACT-1
ACT-1
ACT-1
ACC-2
?
?
ACC-2
?
?
8' - 0"
8' - 0"
7' - 6" 8' - 0"
7' - 6"
G-1
G-1
G-1
G-1
G-1
ACT-1
9' - 0 3/8"
9' - 1 3/8"
9' - 1 3/8"
G-1
2602
2602
2602 2602
2602
2602
2602
2602
2602
1058 2602
2602
2602
2602
2602
2602
2602
2602
2602
2602
2304
2602
2304
2304
2602
2304
2304
2304
2602
2602
ACC-2
G-1
8' - 8 1/8"
8' - 6 3/4"
8' - 6 3/4"
8' - 6 3/4"
0560
8' - 0" 8' - 0" 8' - 0" 7' - 0" 7' - 10 1/2" 7' - 8 5/8" 8' - 0" 8' - 0" 6' - 10" 8' - 0" 8' - 0" 8' - 0" 6' - 10"
8' - 0" 7' - 0"
8' - 0" 8' - 0" 8' - 0" 8' - 0"
8' - 0" 8' - 0"
5' - 8 1/2" 8' - 0" 8' - 0" 8' - 0" 8' - 0" 6' - 7 1/2" 10' - 0" 8' - 0" 8' - 0"
8' - 0"
8' - 0" 8' - 0" 8' - 0" 8' - 0" 8' - 0" 7' - 0"
6' - 6" 8' - 0"
ALT. D-03: ACT-1 @ MARKETPLACE,
TEEN, AND ADULT SOFFT
W-1
W-1
W-1
G-1
8' - 0"
0560
0560
0560
0560
0560
0560
0560
0560
C
NEW ENLARGED
DRAWING DRAWING
C
NEW ENLARGED
DRAWING DRAWING
7' - 6"
2602
180
H
180
270
270
270
270
270
H
180
270
180
180 180
TKN2003 (E)
TKN2004
(E)
(E)
(E)
TKN2004
I
U
E
I
H
U
9 AS.O
A
FRANCN
4 0 8 0
H
I
N
S
L11
AL
E
R C
NDE N VA
,N I N G
CRAE
I T E C T
SC
S
N
N
G R O U P
7 S
5 06
C
07 18
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
N
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TY601
ESS - FIRST FLOOR
RCP
Project Number
1/8" = 1'-0" 1
ESS - FIRST FLOOR RCP
KEYNOTES
TKN2003 (E) IP INTERIOR CAMERA. CONTRACTOR TO
REMOVE DURING CONSTRUCTION, THEN
FOLLOWING COMPLETION OF THE WORK,
RE-INSTALL TO NEW STRUCTURED CABLING
PROVIDED UNDER THE WORK OF THE PROJECT,
AND PROGRAM TO OPERATE WITH THE NEW NVR
PROVIDED UNDER THE WORK OF THE PROJECT.
CLEAN LENS AND HOUSING, RE-AIM AND FOCUS AS
DIRECTED BY THE CITY/SPL'S REPRESENTATIVE
FOLLOWING RE-INSTALLATION.
TKN2004 (E) EXTERIOR IP EXTERIOR CAMERA.
CONTRACTOR TO REMOVE DURING
CONSTRUCTION, THEN FOLLOWING COMPLETION
OF THE WORK, RE-INSTALL TO NEW STRUCTURED
CABLING PROVIDED UNDER THE WORK OF THE
PROJECT, AND PROGRAM TO OPERATE WITH THE
NEW NVR PROVIDED UNDER THE WORK OF THE
PROJECT. CLEAN LENS AND HOUSING, RE-AIM AND
FOCUS AS DIRECTED BY THE CITY/SPL'S
REPRESENTATIVE FOLLOWING RE-INSTALLATION.
A
ARCHITECTURAL: COMPLY WITH DIVISIONS 3 THROUGH
14 - SEE ARCHITECTURAL DRAWINGS.
A1
DOOR POWER OPERATOR, WHERE OCCURS - REFER TO
PLANS.
E
ELECTRICAL: COMPLY WITH DIVISION 26 - SEE
ELECTRICAL DRAWINGS
E1
CONNECT ELECTRICAL SERVICE TO THIS AREA TO THE
EMERGENCY POWER BACKUP SYSTEM WHERE SAME
PROVIDED FOR IN ELECTRICAL PLANS AND
SPECIFICATIONS.
E2
PROVIDE INTERFACE TO FIRE ALARM SYSTEM TO
ENSURE THAT EXIT DOOR LOCKS IN THE PATH OF
TRAVEL DEFINED FOR EMERGENCY EGRESS ARE
RELEASED IN ACCORDANCE WITH THE CBC UPON
OPERATION OF FIRE ALARM.
TKN
ELECTRONIC SECURITY SYSTEMS: COMPLY WITH
DIVISIONS 28.
TKN1
LOW VOLTAGE POWER SUPPLIES REQUIRED VARY WITH
SUPPLIED DEVICE MANUFACTURER(S). MATCH
MANUFACTURER RECOMMENDATIONS WITH AT LEAST
50% RESERVE CAPACITY.
TKN2 DEVICE QUANTITY AS INDICATED ON THE PLANS.
TKN3 NOT USED.
TKN4 CAT6 PATCH CORDS. PROVIDE QTY. AS REQUIRED.
TKN5
PROVIDE WIRE GAGE, SHIELDING, PAIR COUNT AND
CONSTRUCTION AS REQUIRED TO SUIT DEVICE IN
ACCORDANCE WITH THE MANUFACTURER'S
INSTALLATION INSTRUCTIONS. BRING ALL CONTACT
POINTS BACK TO THE SECURITY ELECTRONICS
TERMINAL CABINETS AT THE COMMUNICATIONS ROOMS
- DO NOT LOOP OR DAISY CHAIN ANY FIELD DEVICES
UNLESS THEY ARE SPECIFIED AS DIGITALLY
ADDRESSABLE TYPE. PROVIDE JACKET TYPE IN
CONFORMANCE WITH THE INSTALLATION CONDITIONS
AND THE CALIFORNIA ELECTRIC CODE.
TKN6
STRUCTURED CABLING IS WORK OF DIVISION 27 – REFER
TO TN SHEETS. CATEGORY CABLING TO BE RATED FOR
OUTDOOR SERVICE WHERE INSTALLED UNDERGROUND.
TKN7
DUPLEX FIBER OPTIC PATCH CORDS. PROVIDE QTY. AS
REQUIRED.
TKN8 NOT USED.
TKN9 PROVIDE QTY AS REQUIRED.
TKN10
PROVIDE UNINTERRUPTIBLE POWER BACKUP FOR
ENTIRE SYSTEM FOR UP TO 20 MINUTES OPERATION
FOLLOWING LOSS OF POWER.
TKN11 NOT USED.
TKN12 NOT USED.
TKN13 NOT USED.
TKN14
SACRAMENTO PUBLIC LIBRARY FURNISHED POE
ETHERNET SWITCH.
TKN15
PLACE ALL SECURITY ELECTRONICS WIRING ENTERING
COMMUNICATIONS ROOMS ARE IN METALLIC RACEWAY
FROM THE POINT OF ENTRY TO ROOM. WITHIN
COMMUNICATIONS ROOM, PROTECT IN SURFACE
MOUNTED GUTTER AT BACKBOARDS.
TKN16 UTP6-4OP.
TKN17
WHERE INTRUSION DETECTION FUNCTIONALITY IS
INDICATED ON THE PLANS, PROVIDE SEPARATE
INTRUSION DETECTION PANEL AS SPECIFIED IN SECTION
28 13 00, PROGRAMMED AND INTEGRATED TO FUNCTION
WITH ACCESS CONTROL SYSTEM TO PROVIDE
INTEGRATE MONITORING.
TKN18
INCORPORATE INTEGRATED INTRUSION DETECTION
SYSTEM/ACCESS CONTROL SYSTEM ALARM AND
CONTROL RESPONSE WITHIN PROGRAMMING OF
SACRAMENTO PUBLIC LIBRARY STANDARD ACCESS
CONTROL SYSTEM.
TKN19
WHERE INSTALLED ELECTRIC LOCKING HARDWARE
PROVIDES LATCH RETRACTION MONITORING, PROVIDE
CONDUCTORS AND DGP MONITORING POINTS AND DGP
PROGRAMMING AS REQUIRED TO MONITOR LATCH
STATUS.
TKN20
PROGRAM THE INDICATED CKP’S AND WIRE THE DGP TO
THE IDS PANEL TO BE ABLE TO ARM AND DISARM THE
INTRUSION DETECTION PANEL IN LIEU OF RELYING ON
USE OF A SEPARATE INTRUSION DETECTION KEYPAD.
1. SINGLE DIAGRAM IS DIAGRAMMATIC. CONTRACTOR TO
SUBMIT SHOP DRAWINGS INDICATING EXACT QTY AND
LOCATION OF ACCESS CONTROL PANELS AND RELATED
HARDWARE REQUIRED TO MEET THE FUNCTIONAL
REQUIREMENTS OF THE PROJECT.
2. PROVIDE BATTERY BACKUP (UPS AND/OR PANEL
MOUNTED BATTERY) TO SUPPORT OPERATIONS OF THE
BACKBOARD MOUNTED PORTIONS OF THE ELECTRONIC
SECURITY SYSTEMS FOR AT LEAST 20 MIN. FOLLOWING
LOSS OF POWER, INCLUDING CARD READERS, ACCESS
CONTROL (DGP) AND IDS PANELS, ELECTRIC LOCKS AND
FIELD MONITORING DEVICES.
3. PROVIDE HIGH LEVEL COMMUNICATIONS INTERFACE
USING TCP/IP COMMUNICATIONS AND NATIVE SDK/API
INTERFACES TO INTERFACE ACCESS CONTROL AND
INTRUSION DETECTION EVENTS WITH CAMERA CALL UP
IN THE ASSOCIATED AREA, AND FOR RECEIPT OF
MOTION DETECTION ALERTS FROM THE CCTV SYSTEM.
(E) COUNTY
C-CURE ACCESS
SYSTEM
SACRAMENTO
PUBLIC LIBRARY
WAN
MD
MDE
1 ACCESS CONTROL AND SINGLE LINE DIAGRAM
NTS
48 C6PP
POE ESW
IT ROOM 116
BACKBOARD MTD
MMP6
R28
FIELD DEVICE
QUANTITY AS SHOWN
ON PLANS
HINGE
CARD READER
INPUTS
CLOSURE
INPUTS
RELAY
OUTPUTS
ACCESS CONTROL PANEL
TRANSFER EL
DS
PHR
CN
CKP
ETHERNET
INTERFACE
CLOSURE
OUTPUTS
DGP
POWER SUPPLY
DOOR LOCK
CLOSURE
&POPIT
ADDRESSABLE
INPUTS
KEY
PAD
INPUTS
KP
TCP/IP OUTPUT
DIALER OUTPUT
INTRUSION DETECTION PANEL CLOSURE OUTPUTS
MD
CNS
CR
CRS
VR
GB
DC
SERIAL I/OSERIAL I/O
DU
RB
TO FACP
PO
ER
HR
REX
HINGE
TRANSFER
LA
PS
(E) COUNTY DATACENTER
TO 110TB100
AS SHOWN ON
TN7.0-1
WS
KEYNOTES (CONT.) SHEET NOTES
KEYNOTES
TKN5
E1
TKN10
E1
E2
TKN18
A1
TKN15
TKN4
E1
TKN4
TKN17
E1
TKN19
E2
TKN20
TKN20
TKN4
TKN9
TKN10
TKN1
TKN10
TKN10
TKN14
TKN4
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TY701
ACCESS CONTROL
AND SINGLE LINE
DIAGRAM
Project Number
1. SINGLE DIAGRAM IS DIAGRAMMATIC. CONTRACTOR TO
SUBMIT SHOP DRAWINGS INDICATING EXACT QTY AND
LOCATION OF POWER SUPPLIES AND MEDIA
TRANSCEIVERS AND RELATED HARDWARE REQUIRED TO
MEET THE FUNCTIONAL REQUIREMENTS OF THE
PROJECT.
2. PROVIDE BATTERY BACKUP (UPS AND/OR PANEL
MOUNTED BATTERY) TO SUPPORT OPERATIONS OF THE
BACKBOARD MOUNTED PORTIONS OF THE ELECTRONIC
SECURITY SYSTEMS FOR AT LEAST 20 MIN. FOLLOWING
LOSS OF POWER, INCLUDING CARD READERS, ACCESS
CONTROL (DGP) AND IDS PANELS, ELECTRIC LOCKS AND
FIELD MONITORING DEVICES.
3. PROVIDE HIGH LEVEL COMMUNICATIONS INTERFACE
USING TCP/IP COMMUNICATIONS AND NATIVE SDK/API
INTERFACES TO INTERFACE ACCESS CONTROL AND
INTRUSION DETECTION EVENTS WITH CAMERA CALL UP
IN THE ASSOCIATED AREA, AND FOR RECEIPT OF
MOTION DETECTION ALERTS FROM THE CCTV SYSTEM.
E
ELECTRICAL: COMPLY WITH DIVISION 26 - SEE
ELECTRICAL DRAWINGS
E1
CONNECT ELECTRICAL SERVICE TO THIS AREA TO THE
EMERGENCY POWER BACKUP SYSTEM WHERE SAME
PROVIDED FOR IN ELECTRICAL PLANS AND
SPECIFICATIONS.
TKN
ELECTRONIC SECURITY SYSTEMS: COMPLY WITH
DIVISIONS 28.
TKN1
LOW VOLTAGE POWER SUPPLIES REQUIRED VARY WITH
SUPPLIED DEVICE MANUFACTURER(S). MATCH
MANUFACTURER RECOMMENDATIONS WITH AT LEAST
50% RESERVE CAPACITY.
TKN2 DEVICE QUANTITY AS INDICATED ON THE PLANS.
TKN3
PROTECT PATCH INTERFACE AND TRANSCEIVERS IN
POLE MTD NEMA 4 ENCLOSURE. PROVIDE WATERTIGHT
PATCH CORDS EQUIPMENT WITH GLAND FITTINGS TO
MATCH THOSE ON THE SUPPLIED CAMERA.
TKN4 CAT6 PATCH CORDS. PROVIDE QTY. AS REQUIRED.
TKN5 NOT USED.
TKN6
STRUCTURED CABLING IS WORK OF DIVISION 27 – REFER
TO TN SHEETS. CATEGORY CABLING TO BE RATED FOR
OUTDOOR SERVICE WHERE INSTALLED UNDERGROUND.
TKN7
DUPLEX FIBER OPTIC PATCH CORDS. PROVIDE QTY. AS
REQUIRED.
TKN8
MMP6 MOUNTED TO SURFACE MTD BACKBOX OR
EQUIVALENT USING SPECIFIED JACKS MTD IN 'BISCUIT
BOX' MECHANICALLY FASTENED TO INTERIOR OF
ENCLOSURE. WHERE CIRCUIT REQUIRES FIBER
CONNECTIVITY, PROVIDE LC CONNECTOR, OTHERWISE
PROVIDE CAT6 RJ45. PROVIDED UNDER THE WORK OF
DIVISION 27.
TKN9 PROVIDE QTY AS REQUIRED.
TKN10
PROVIDE UNINTERRUPTIBLE POWER BACKUP FOR
ENTIRE SYSTEM FOR UP TO 20 MINUTES OPERATION
FOLLOWING LOSS OF POWER.
TKN11
PROVIDE AUXILIARY CAMERA POWER AS REQUIRED
WHERE CAMERA IS NOT DESIGNED TO OPERATE ON POE
POWER ALONE INCLUDING ALL EXTERIOR CAMERAS,
WHICH SHALL BE PROVIDED WITH INTEGRAL HEATERS.
TKN12
WHERE PATHWAY IS UNDERGROUND, PROVIDE THWN
OR EQUIVALENT UNDERGROUND RATED CABLING AS
SPECIFIED IN DIVISION 26 FOR SIM APPLICATIONS.
SELECT GAUGE TO SUIT RUN LENGTHS.
TKN13 NOT USED.
TKN14
SACRAMENTO PUBLIC LIBRARY FURNISHED POE
ETHERNET SWITCH.
TKN15 NOT USED.
TKN16 UTP6-4OP.
1 VISUAL SURVEILLANCE SINGLE LINE DIAGRAM.
NTS
BUILDING AND SITE CAMERAS
(N) NVR
ETH
INTERIOR ETH
CAMERAS
PS
CAM
UTP6-4OP
UTP6-4
QTY. AS
SHOWN
ON PLANS
48 C6PP
POE ESW
R28
IT ROOM 116
OTHER
EXTERIOR
CAMERAS
SHEET NOTES
KEYNOTES
TKN4
TKN4
TKN12
TKN8
TKN8
TKN14
TKN4
TKN6
TKN6
TKN3
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TY702
VISUAL
SURVEILLANCE
SINGLE LINE
DIAGRAM
Project Number
1.55 [39.48]
4.96 [125.93]
.73 [18.46]
2.67 [67.79]
3.88 [98.66]
.77 [19.48]
84.84 mm
3.34 in.
122.05 mm
4.81 in.
122.05 m
1.07 in.
ES4200-K4-T1
BLUEWHITERED
N/CN/OCOMMON
/O ALARM
20 SHUNT CONTACT MODE (ON=N/O)INTRUSION DETECT ENABLESHUNT RECYCLE ENABLE 0 SEC
DOOR PROP
(ON=NORMALLY ENERGIZED)
3 12
DRY
CONTACT
SHUNT
VOLTAGE SENSE +
LED GREEN OUT
VOLTAGE SENSE -
54 6 87
LED RED OUT
CONTACT
N/C DOOR
STATUS
RESERVEDSHUNT DELAY 0SHUNT DELAY 1
DOOR
RELAY
SUPERVISION ENABLE
ES4200
DOOR 23
/O
VOLTAGE SENSE MODE
/C
24 OM
/C
2221
BYPASS/KEY
STATUS RELAY
INTRUSION &
EXTENDED TIME
HORN VOLUME
(ON = HIGH)
20 SEC
SHUNT DELAY TIME
5 SEC
10 SEC POWER SUPPLY
12 - 24 VAC/VDC
RESET/BYPASS
9 1011
N/O REMOTE
TAMPER
12 RELAY
ALARM
RELAY
SILENT
TIME
SELECT (800) 272-3555
DESIGNED SECURITY, INC.
ALARM
DELAY
SELECT
AUTO
RESET
SELECT
17 OM
/C
1819
/O
OM
/C
1615
/O
OM
1413
SWITCH, DS.
DOOR
CEILING
3/4" C. EACH
FLOOR
SWITCH, DS.
DOOR
CEILING
3/4" C. EACH
FLOOR
J1
CEILING
FLOOR
SWITCH, DS.
DOOR
CEILING
FLOOR
3/4"C.
SWITCH, DS.
DOOR
CEILING
FLOOR
3/4"C.
SWITCH, DS.
DOOR
3/4"C.
AT VERTICAL
INSTALL LINE
CENTER OF GATE
BRACKETS
SHEET NOTES
J1
KEYNOTES
A
ARCHITECTURAL: COMPLY WITH DIVISIONS 3
THROUGH 14 - SEE ARCHITECTURAL DRAWINGS.
A1 TRANSFER HINGE WITH 1 PR CONDUCTORS MIN.
A2 TRANSFER HINGE WITH 2 PR CONDUCTORS MIN.
A3
HR - DOOR HANDLE OR PANIC HARDWARE WITH
MECHANICAL LOCK AND INTEGRAL ALARM
SUPPRESSION MICROSWITCH TO DETECT
OPERATION OF DOOR FROM SECURE SIDE.
A4 EL - ELECTRIC DOOR LOCK OR ELECTRIC STRIKE.
TKN
ELECTRONIC SECURITY SYSTEMS: COMPLY WITH
DIVISION 27 AND 28.
TKN1
EXTEND 1" MIN C. TO ACCESSIBLE CEILING AND/OR
TELECOMMUNICATIONS ROOM SERVING THIS
DOOR. REFER ADDITIONALLY TO THE
REQUIREMENTS OF THE SHEET NOTES.
TKN2
EXTEND 1.25" MIN C. TO ACCESSIBLE CEILING
AND/OR TELECOMMUNICATIONS ROOM SERVING
THIS DOOR. REFER ADDITIONALLY TO THE
REQUIREMENTS OF THE SHEET NOTES.
TKN3
REX - EXIT ALARM SUPPRESSION SENSOR, IR
BASED, MOUNTED ABOVE DOOR.
TKN4
LOCATE ABOVE DOOR AT ACCESSIBLE CEILING
CONDTIONS. AT GYP CEILING CONDITIONS,
LOCATE REMOTELY AT NEAREST UTILITY SPACE.
TKN5 MATCH PROJECT SWITCH HEIGHT.
TKN6
PROVIDE MUD BOX INSIDE DOOR FRAME AT
GROUTED DOOR ASSEMBLIES.
TKN7
STUB CONDUIT INSIDE DOOR FRAME TO ABOVE
THE MIDDLE HINGE OPPOSITE DOOR
HANDLE/EL/ER/ES/PANIC HW. MEASURE DOOR ON
SITE. COORDINATE SIDE OF DOOR SCHEDULED TO
RECEIVE ACTIVE DOOR HARDWARE, INCLUDING EL
OR ES WITH WORK OF DIVISION 8.
TKN8
DOOR HARDWARE (DOOR HANDLE, ES, EL, HR,
AND/OR PHR AS APPLIES) AND TRANSFER HINGE
FURNISHED AND INSTALLED UNDER THE WORK OF
DIVISION 8. WORK OF DIVISION 28 WIRES LOCKING
HARDWARE VIA TRANSFER HINGE AND PROVIDES
WIRING AND PATHWAY BACK TO DGP.
TKN9
CR - WALL MOUNTED CARD READER WITH 4S BOX
AND 1 GANG RING INSTALLED FACING UN-SECURE
SIDE OF DOOR.
TKN10
CN - MULLION MOUNTED CARD READER MOUNTED
TO FACE OF DOOR FRAME FACING UN-SECURE
SIDE OF DOOR.
TKN11 STUB CONDUIT INSIDE DOOR FRAME TO ABOVE
CUTOUT FOR MULLION MOUNT CARD READER.
GS- GATE SWITCH.
CORROSION RESISTANT JUNCTION BOX SUITABLE
FOR EXTERIOR USE FASTENED TO STRUCTURE AT
THE SECURE SIDE OF THE GATE. PROTECT BOX
WITH BLANK COVER FASTENED WITH TAMPER
PROOF FASTENERS.
1" C., TYP.
PROVIDE PROJECT STANDARD DOOR LOCK
CYLINDER, AS SPECIFIED IN DIVISION 8.
TKN12
TKN13
TKN14
1. NOT EVERY DOOR CONDITION IS DEPICTED.
REFER TO THE FLOOR PLANS FOR THE DEVICES
REQUIRED AT EACH OPENING AND PROVIDE
ROUGH-IN AS REQUIRED BASED ON SIMILAR
ASSEMBLIES DETAILED ON THE TY SHEETS,
2. NOT USED.
3. WHERE ESS SIGNAL CABLING IS CONSOLIDATED
WITH A NETWORK OF CONDUITS AND PULL BOXES,
MAINTAIN 40% MAXIMUM FILL.
4 HORIZONTAL ARRANGEMENT OF DEVICES MAY
VARY - REFER TO THE FLOOR PLANS FOR THE
REQUIRED ARRANGEMENTS. CARD READERS
SHOULD GENERALLY BE PLACED ADJACENT TO
THE DOOR HANDLE OF THE ACCESS CONTROLLED
DOOR. REFER TO THE DIVISION 8 HW SCHEDULES
AND THE APPROVED DIVISON 8 SUBMITTALS TO
DETERMINE WHETHER EL OR ES ARE USED AT
EACH OPENING.
TKN15
5 TYPICAL MONITORED SINGLE DOOR ELEVATION,
IR REX EXIT ALARM SUPPRESSION
VIEW FROM SECURE SIDE, CEILING ACCESS NTS 6
TYPICAL MONITORED SINGLE DOOR ELEVATION,
DOOR HARDWARE EXIT ALARM SUPPRESSION
VIEW FROM SECURE SIDE, CEILING ACCESS NTS 7
TYPICAL ACCESS CONTROLLED SINGLE DOOR
IR REX EXIT ALARM SUPPRESSION ELEVATION
VIEW FROM SECURE SIDE, CEILING ACCESS NTS
8 TYPICAL ACCESS CONTROLLED SINGLE DOOR
IR REX EXIT ALARM SUPPRESSION ELEVATION
VIEW FROM SECURE SIDE, CEILING ACCESS NTS
9 TYPICAL ACCESS CONTROLLED SINGLE DOOR
IDOOR HARDWARE EXIT ALARM SUPPRESSION ELEVATION
VIEW FROM SECURE SIDE, CEILING ACCESS NTS
1 WALL MOUNT
MULTI-PROTOCOL CARD READER - TYPE CR
NTS 2
MULLION MOUNT
MULTI-PROTOCOL CARD READER - TYPE CN
NTS 3
WALL MOUNT MULTI-PROTOCOL CARD READER
W/ INTEGRATED KEYPAD - TYPE CKP
NTS 4
GS - TYPE GATE SWITCH
NTS
10 LA - LOCAL ALARM
NTS
6.40 4.60
2.30 TKN1 TKN4
TKN3
TKN1 TKN4
TKN7
TKN6
A1
TKN8
A3
TKN2 TKN4
TKN7
TKN6
TKN8
A4
TKN5
TKN9
TKN3
TKN2 TKN4
TKN7
TKN6
TKN8 A4
TKN5
TKN10
TKN3
TKN11
TKN2 TKN4
TKN7
TKN6
A2
TKN8 A5
TKN5
TKN9 A2
A2
TKN14
TKN13
TKN15
TKN12
J1
J1 J1
ES4200-K4-T1
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TY901
DETAILS - SINGLE
DOOR ACCESS
CONTROL
Project Number
3/4" C. EACH
DS.
DOOR SWITCH,
CEILING
FLOOR
REX
3/4" C. EACH
DS.
DOOR SWITCH,
CEILING
FLOOR
ACTIVE
LEAF
PASSIVE
LEAF
3/4" C. EACH
DS.
DOOR SWITCH,
CEILING
FLOOR
ACTIVE
LEAF
PASSIVE
LEAF
3/4" C. EACH
DS.
DOOR SWITCH,
CEILING
FLOOR
ACTIVE
LEAF
PASSIVE
LEAF
REX
3/4" C. EACH
DS.
DOOR SWITCH,
CEILING
FLOOR
ACTIVE
LEAF
PASSIVE
LEAF
REX
3/4" C. EACH
DS.
DOOR SWITCH,
CEILING
FLOOR
ACTIVE
LEAF
PASSIVE
LEAF
REX
3/4" C. EACH
DS.
DOOR SWITCH,
CEILING
FLOOR
ACTIVE
LEAF
PASSIVE
LEAF
3/4" C. EACH
DS.
DOOR SWITCH,
CEILING
FLOOR
ACTIVE
LEAF
PASSIVE
LEAF
REX
SHEET NOTES
KEYNOTES
1. NOT EVERY DOOR CONDITION IS DEPICTED. REFER
TO THE FLOOR PLANS FOR THE DEVICES REQUIRED
AT EACH OPENING AND PROVIDE ROUGH-IN AS
REQUIRED BASED ON SIMILAR ASSEMBLIES
DETAILED ON THE TY SHEETS,
NOT USED.
WHERE ESS SIGNAL CABLING IS CONSOLIDATED
WITH A NETWORK OF CONDUITS AND PULL BOXES,
MAINTAIN 40% MAXIMUM FILL.
HORIZONTAL ARRANGEMENT OF DEVICES MAY
VARY - REFER TO THE FLOOR PLANS FOR THE
REQUIRED ARRANGEMENTS. CARD READERS
SHOULD GENERALLY BE PLACED ADJACENT TO THE
DOOR HANDLE OF THE ACCESS CONTROLLED
DOOR. REFER TO THE DIVISION 8 HW SCHEDULES
AND THE APPROVED DIVISON 8 SUBMITTALS TO
DETERMINE WHETHER EL OR ES ARE USED AT EACH
OPENING.
2. 3.
4. A
A1
A2
A3
A4
A5
A6
A7
A8
A9
E
E1
TKN
TKN1
TKN2
TKN3
TKN4
TKN5
TKN6
TKN7
TKN8
TKN9
TKN10
TKN11
TKN12
TKN13
ARCHITECTURAL. WORK OF DIVISIONS 3-14.
TRANSFER HINGE WITH 1 PR CONDUCTORS MIN.
TRANSFER HINGE WITH 2 PR CONDUCTORS MIN.
HR - DOOR HANDLE OR PANIC HARDWARE WITH
MECHANICAL LOCK AND INTEGRAL ALARM
SUPPRESSION MICROSWITCH TO DETECT OPERATION
OF DOOR FROM SECURE SIDE.
EL - ELECTRIC DOOR LOCK OR ELECTRIC STRIKE,
REFER TO DIVISION 8.
ER - DOOR HANDLE OR PANIC HARDWARE WITH
ELECTRIC LOCK AND INTEGRAL ALARM SUPPRESSION
MICROSWITCH TO DETECT OPERATION OF DOOR
FROM SECURE SIDE.
ES - ELECTRIC STRIKE.
ARCHITECTURAL PEDESTAL - WHERE OCCURS, SEE
PLANS
DO - POWERED DOOR OPERATOR SWITCH MOUNTED
TO PEDESTAL OR WALL ON BOTH SECURE AND
UN-SECURE SIDES OF OPENING. WIRED TO DGP BY
DIVISION 28.
PO - POWERED DOOR OPERATOR
ELECTRICAL. COMPLY WITH DIVISION 26
PROVIDES POWER TO POWERED DOOR OPERATOR.
ELECTRONIC SECURITY SYSTEMS: COMPLY WITH
DIVISION 28.
EXTEND 1" MIN C. TO ACCESSIBLE CEILING AND/OR
TELECOMMUNICATIONS ROOM SERVING THIS DOOR.
REFER ADDITIONALLY TO THE REQUIREMENTS OF
THE SHEET NOTES.
EXTEND 1.25" MIN C. TO ACCESSIBLE CEILING AND/OR
TELECOMMUNICATIONS ROOM SERVING THIS DOOR.
REFER ADDITIONALLY TO THE REQUIREMENTS OF
THE SHEET NOTES.
REX - EXIT ALARM SUPPRESSION SENSOR, IR BASED,
MOUNTED ABOVE DOOR.
LOCATE ABOVE DOOR AT ACCESSIBLE CEILING
CONDTIONS. AT GYP CEILING CONDITIONS, LOCATE
REMOTELY AT NEAREST UTILITY SPACE.
MATCH PROJECT SWITCH HEIGHT.
PROVIDE MUD BOX INSIDE DOOR FRAME AT GROUTED
DOOR ASSEMBLIES.
STUB CONDUIT INSIDE DOOR FRAME TO ABOVE THE
MIDDLE HINGE OPPOSITE DOOR
HANDLE/EL/ER/ES/PANIC HW. MEASURE DOOR ON
SITE. COORDINATE SIDE OF DOOR SCHEDULED TO
RECEIVE ACTIVE DOOR HARDWARE, INCLUDING EL
OR ES WITH WORK OF DIVISION 8.
DOOR HARDWARE (DOOR HANDLE, ES, EL, HR,
AND/OR PHR AS APPLIES) AND TRANSFER HINGE
FURNISHED AND INSTALLED UNDER THE WORK OF
DIVISION 8. WORK OF DIVISION 28 WIRES LOCKING
HARDWARE VIA TRANSFER HINGE AND PROVIDES
WIRING AND PATHWAY BACK TO DGP.
CR - WALL MOUNTED CARD READER WITH 4S BOX
AND 1 GANG RING INSTALLED FACING UN-SECURE
SIDE OF DOOR.
CN - MULLION MOUNTED CARD READER MOUNTED TO
FACE OF DOOR FRAME FACING UN-SECURE SIDE OF
DOOR.
STUB CONDUIT INSIDE DOOR FRAME TO ABOVE
CUTOUT FOR MULLION MOUNT CARD READER.
CARD READER MOUNTED TO WALL OR PEDESTAL AT
POWER DOOR OPERATOR ENABLED ENTRIES ON
UN-SECURE SIDE.
1" C. FROM BASE OF PEDESTAL OR WALL MOUNT
LOCATION OF DO AND RELATED CT, TO J2. OCCURS
ON BOTH SECURE AND UN-SECURE SIDES OF
OPENING.
2 TYPICAL MONITORED DOUBLE DOOR OPENING,
DOOR HARDWARE EXIT ALARM SUPPRESSION 1 VIEW FROM SECURE SIDE, CEILING ACCESS NTS
TYPICAL MONITORED DOUBLE DOOR OPENING,
IR REX EXIT ALARM SUPPRESSION
VIEW FROM SECURE SIDE, CEILING ACCESS NTS
4 DOOR OPENING, AUTO LOCK/UNLOCK,
IR REX EXIT ALARM SUPPRESSION
VIEW FROM SECURE SIDE, CEILING ACCESS NTS
3 DOOR OPENING, ACTIF LEAF PANIC
HARDWARE EXIT ALARM SUPPRESSION
VIEW FROM SECURE SIDE, CEILING ACCESS NTS
5 OPENING, WALL MOUNT CARD READER,
IR REX EXIT ALARM SUPPRESSION
VIEW FROM SECURE SIDE, CEILING ACCESS NTS
7 OPENING, WALL MOUNT CARD READER,
DOOR HARDWARE EXIT ALARM SUPPRESSION
VIEW FROM SECURE SIDE, CEILING ACCESS NTS
6 OPENING, MULLION MOUNT CARD READER,
IR REX EXIT ALARM SUPPRESSION
VIEW FROM SECURE SIDE, CEILING ACCESS NTS
8 & DOOR OPERATOR, POWERED OPERATOR
& IR REX EXIT ALARM SUPPRESSION
VIEW FROM SECURE SIDE, CEILING ACCESS NTS
TYPICAL ACCESS CONTROLLED DOUBLE DOOR
TYPICAL ACCESS CONTROLLED DOUBLE DOOR
OPENING, PEDESTAL MOUNTED CARD READER
TYPICAL ACCESS CONTROLLED DOUBLE DOOR
TYPICAL ACCESS CONTROLLED DOUBLE
TYPICAL MONITORED DOUBLE
TYPICAL ACCESS CONTROLLED DOUBLE DOOR
TKN1
TKN3
TKN1 TKN4
TKN7
A1 TKN8
TKN6
A3
TKN1 TKN4
TKN7
A1 TKN8
TKN6
A3
TKN7
A1 TKN8
TKN6 A4
TKN3
TKN9
TKN5
TKN2 TKN4
TKN7
A1
TKN8
TKN6 A4
TKN3
TKN10
TKN5
A2 TKN5
TKN6
TKN9
TKN8 A5
TKN7
TKN2 TKN4
TKN6
A1
TKN6
A7
TKN8
A1
TKN7
TKN4 TKN2
TKN7
A4
A6
A8
TKN12
A9
E1
TKN13
TKN1 TKN4 TKN1 TKN4
TKN7
A1
TKN6
A4
TKN3
TKN8
J1 J1 J1
J1 J1 J1
J1 J2
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TY902
DETAILS - DOUBLE
DOOR ACCESS
CONTROL
Project Number
TKN7
TKN1
TKN1
TKN5
TKN5
TKN4
TKN2
TKN3
TKN3
TKN2
TKN4
TKN6
TKN9
TKN8
TKN7
A1
TKN2
TKN2
TKN2
TKN2
TKN2
TKN2
TKN2
KEYNOTES
CEILING ASSEMBLY, TYP.
A
ARCHITECTURAL. WORK OF DIVISIONS 3-14.
PAINT AS DESCRIBED/REQUIRED IN DIVISION 9
TKN
ELECTRONIC SECURITY SYSTEMS: COMPLY WITH
DIVISION 28.
CATEGORY 6 STATION CABLING BY DIVISION 27.
CATEGORY 6 PATCH CORD PROVIDE LENGTH AS
REQUIRED. WHERE CAMERA IS MOUNTED TO BACKBOX,
COIL INSIDE BACKBOX.
PROVIDE EQUAL TO CHIEF MANUFACTURING CMA110, 8"
X 8" STEEL PLATE CEILING PLATE FITTING WITH 1" NPT
PIPE THREAD ADAPTER.
1" NPT PIPE THREADED FOR PENDENT MOUNTING FROM
STRUCTURE ABOVE.
5S TYPE ELECTRICAL BACKBOX EQUAL TO RANDL
INDUSTRIES T-55017 WHERE SURFACE MOUNT OF IP
CAMERA TO FLUSH MOUNT BACKBOX WITH INTEGRAL
STRUCTURED CABLING BISCUIT BOX REQUIRED.
PROVIDE EXTERIOR GRADE BOX AT EXTERIOR
CONDITIONS AS REQUIRED BY SECTION 28 05 28 -
PATHWAYS FOR ELECTRONIC SAFETY AND SECURITY
SMALL FORM FACTOR MULTIMEDIA ENCLOSURE
SUITABLE FOR SURFACE MOUNTING WITH INTEGRAL
CATEGORY 6 JACK FOR TERMINATION OF STATION
CABLING.
SURFACE MOUNT IP CAMERA SUPPORTED FROM FLUSH
MOUNTED BACKBOX.
IP SECURITY CAMERA.
CAMERA MANUFACTURER'S PENDANT MOUNT ADAPTER.
ELECTRICAL
BACKBOX-5S OR
AS REQUIRED TO
FLUSH MOUNT
CAMERA. PROVIDE
EXTERIOR GRADE
BOX AT EXPOSED
CONDITIONS.
SECURE WITH 5/16" FASTENERS
SUITED FOR ENVIRONMENT
CATEGORY MEDIA STATION CABLING TO IP CAMERAS TO TERMINATE AT
PERMANENT ENCLOSURE/JACK ASSEMBLY, AND A PATCH CORD SHALL BE
USED TO MAKE THE CONNECTION FROM THE PERMANENTLY INSTALLED JACK TO THE CAMERA.
A1
TKN1
TKN2
TKN3
TKN4
TKN5
TKN6
TKN7
TKN8
TKN9
NOTES:
1) CAMERAS AND CONDUIT SHALL BE INDEPENDENTLY SUPPORTED AND SHALL NOT RELY ON CEILING SYSTEM CABLE SUPPORTS, FRAME OR TILES FOR SUPPORT. 2) WHERE CEILING-MOUNTED CAMERAS ARE TO BE INSTALLED ON CEILING TILES, THEY SHALL BE CENTERED ON THE TILE IN BOTH DIRECTIONS.
4" SQUARE BACKBOX
AND BLANK FACEPLATE
CAMERA BACKBOX (PLENUM-RATED)
DROP CEILING TILE
6" TO 12"
ABOVE CEILING
CAMERA
3/4" FLEXIBLE
CONDUIT
THREADED ROD
ANCHORED TO
STRUCTURAL
CEILING
MOUNTING
BRACKET
INCLUDED WITH
CAMERA
CONDUIT FOR
NETWORK CABLING
(WHERE REQUIRED
TO TRANSITION TO
OPEN RUN CABLING)
FLUSH-MOUNTED 4"
SQUARE BACKBOX
CEILING
SECURELY
MOUNT TO
JUNCTION BOX
PER
SPECIFICATION
AND
MANUFACTURER'S
INSTRUCTIONS.
CAMERA
INTERIOR WALL
CONDUIT FOR
NETWORK CABLING
(WHERE REQUIRED
TO TRANSITION TO
OPEN RUN CABLING)
WALL MOUNT
BRACKET AND
FLANGED TRIM AS
REQUIRED PER
CAMERA
MANUFACTURER.
FIELD VERIFIED
FOR MOUNTING
HEIGHT.
MOUNTING BRACKET
INCLUDED WITH CAMERA
NOTE:
1) CAMERA SHALL BE INDEPENDENTLY FASTENED TO THE WALL VIA BACKBOX USING MANUFACTURER RECOMMENDED MOUNTING HARDWARE.
FLUSH-MOUNTED 4"
SQUARE BACKBOX
CAMERA
CONDUIT FOR
NETWORK CABLING
(WHERE REQUIRED
TO TRANSITION TO
OPEN RUN CABLING) FLUSH-MOUNTED 4"
SQUARE BACKBOX
CEILING
SECURELY MOUNT TO
JUNCTION BOX PER
SPECIFICATION AND
MANUFACTURER'S
INSTRUCTIONS.
CAMERA
CEILING BRACKET
NOTE:
1) FOR EXTERIOR CAMERA USE INCLUDED WEATHERPROOF HOUSING.
CONDUIT FOR
NETWORK CABLING
(WHERE REQUIRED
TO TRANSITION TO
OPEN RUN CABLING)
WALL MOUNT ARM WITH ROOM
FOR CONNECTIVITY DEVICES,
MIDSPANS AND SERVICE LOOP
INTERIOR WALL
FLUSH-MOUNTED 4"
SQUARE BACKBOX
CAMERA
NOTE:
1) FOR EXTERIOR CAMERA USE INCLUDED WEATHERPROOF HOUSING.
CEILING
FLUSH-MOUNTED 4"
SQUARE BACKBOX
CONDUIT FOR
NETWORK CABLING
(WHERE REQUIRED
TO TRANSITION TO
OPEN RUN CABLING)
INTERIOR WALL
SECURELY MOUNT TO
JUNCTION BOX PER
SPECIFICATION AND
MANUFACTURER'S
INSTRUCTIONS.
WALL MOUNT ARM
WITH 1.5" NPS
THREAD
PENDANT KIT
CAMERA
CAMERA
ACI CONDUIT ADAPTER 3/4"
U-SHAPE
(EXPOSED CONDUIT APPLIES
AT PARKING GARAGE ONLY)
PAINT EXPOSED CONDUIT
TO MATCH SURFACE FINISH
MOUNTING BRACKET
INCLUDED WITH
CAMERA
CONDUIT FOR NETWORK
CABLING (WHERE
REQUIRED TO TRANSITION
TO OPEN RUN CABLING)
FLUSH-MOUNTED 4"
SQUARE BACKBOX
3A
SIDE VIEW
NTS 3B
TOP VIEW
NTS
3 IP CAMERA WIRING DETAIL
NTS
5 IP CAMERA PENDANT MOUNT 4 INTERIOR CEILING/STRUCTURE MOUNTED. NTS
WALL-MOUNTED PENDANT
CAMERA WITH EXTENSION
NTS
WALL ASSEMBLY, TYP.
FLUSH MOUNT CAMERA ASSEMBLY
WALL ASSEMBLY, TYP.
1" C. MIN. TO THE NEAREST ACCESSIBLE CEILING CONDITION
CEILING. REFER TO PLANS
1" C. MIN. TO THE NEAREST
ACCESSIBLE CEILING.
ROOF OVERHANG AND
REFER TO PLANS
FLUSH
MOUNT
CAMERA
ASSEMBLY
FINISH
WALL
1 FMW-FLUSH MOUNT WALL
NTS 2
USC-UNDERSIDE OF CEILING
NTS
6 DOME CAMERA DROP CEILING MOUNT TYP.
NTS 8
DOME CAMERA
CEILING MOUNT TYP.
7 NTS
DOME CAMERA WALL MOUNT TYP.
NTS
11 180° CAMERA CEILING MOUNT TYP.
10 NTS
180° CAMERA WALL MOUNT ARM TYP.
NTS 12
360° CAMERA WALL MOUNT ARM TYP.
9 NTS
360° CAMERA CEILING MOUNT TYP.
NTS
I
U
E
I
H
U
9 AS.O
A
N FRANC
4080
H
I
N
S
L11
AL
E
RC
NDEN VA
NING,
CRAE
IT E C T
SC
S
N
N
G R O U P
7 S
5 06
C
8 71 0
2 P
R
A
O
90 A
EU
C
+
ER
4 SHEET TITLE AND NO.
ISSUE DATE
PROJECT:
CA REG.
Project Arch. --
----
7340 24TH STEET
BYPASS, SACRAMENTO,
CA 95822
MARTIN LUTHER
KING JR. LIBRARY
REMODEL
SD SUBMITTAL 03/12/2024
DD SUBMITTAL 05/31/2024
90% CD - PLAN CHECK 08/29/2024
- MO/DA/YEAR
TY903
DETAILS - ELEC
SECURITY CAMERA
DETAILS
Project Number
Martin Luther King, Jr. Library Remodel
7340 24TH STEET BYPASS,
SACRAMENTO, CA 95822
Back Check 2
December 09, 2024
Architectís Project Number: 23604-01
Group 4 Architecture Research + Planning, Inc.
211 Linden Avenue
South San Francisco, CA
(650) 871-0709
Group 4 Architecture Research + Planning CITY OF SACRAMENTO - Martin Luther King, Jr. Library Remodel
PART 1 - Group4 Project No. 23604-01 Back Check Submission ñ November 01, 2024 PRELIMINARY TABLE OF CONTENTS 00 0010-1
DOCUMENT 00 0010 - TABLE OF CONTENTS
PROCUREMENT AND CONTRACTING REQUIREMENTS GROUP:
DIVISION 00 PROCUREMENT AND CONTRACTING REQUIREMENTS
00 0010 Project Title Page
SPECIFICATIONS GROUP:
GENERAL REQUIREMENTS SUBGROUP:
DIVISION 01 ñ GENERAL REQUIREMENTS
01 1100 Summary of Work
01 2300 Alternates
01 2500 Substitution Procedures
01 2600 Contract Modification Procedures
01 2900 Payment Procedures
01 3100 Project Management and Coordination
01 3200 Construction Progress Documentation
01 3300 Submittal Procedures
01 4000 Quality Requirements
01 4200 References
01 6000 Product Requirements
01 7300 Execution
01 7419 Construction Waste Management and Disposal
01 7700 Closeout Procedures
01 7700 Warranty and guarantee form
01 7710 Cert. of Comp
01 7823 Operation and Maintenance Data
01 7839 Project Record Documents
FACILITY CONSTRUCTION SUBGROUP:
DIVISION 02 ñ EXISTING CONDITIONS
02 4119 Selective Structure Demolition
DIVISION 03 ñ CONCRETE
03 1000 Concrete Forming and Accessories
03 2000 Concrete Reinforcing
03 3000 Cast-in-place Concrete
03 9300 Concrete Epoxy-Injection Crack Repair
Group 4 Architecture Research + Planning CITY OF SACRAMENTO - Martin Luther King, Jr. Library Remodel
PART 1 - Group4 Project No. 23604-01 Back Check Submission ñ November 01, 2024 PRELIMINARY TABLE OF CONTENTS 00 0010-2
DIVISION 04 ñ MASONRY
Not Included
DIVISION 05 ñ METALS
05 1200 Structural Steel Framing
05 3000 Metal Decking
05 4000 Cold-Formed Metal Framing
05 5000 Metal Fabrications
DIVISION 06 ñ WOOD, PLASTICS, AND COMPOSITES
06 1000 Rough Carpentry
06 1053 Miscellaneous Rough Carpentry
06 1800 Glued Laminated Construction
06 2000 Finish Carpentry
06 4100 Architectural Woodwork
06 6413 Fiberglass-Reinforced Plastic Panels
DIVISION 07 ñ THERMAL AND MOISTURE PROTECTION
07 1326 Self-Adhering Sheet Waterproofing
07 2100 Building Insulation
07 2616 Below-Grade Vapor Retarders
07 2729 Underlayment
07 6000 Flashing and Sheet Metal
07 9200 Joint Sealants
DIVISION 08 ñ OPENINGS
08 1113 Hollow Metal Doors and Frames
08 1116 Interior Aluminum Door and Window Frames
08 1416 Flush Wood Doors
08 3113 Access Doors
08 3300 Coiling Doors and Grilles
08 4113 Aluminum-Framed Entrances and Storefronts
08 4230 Sliding Automatic Entrances
08 5113 Window Glazing Retrofit
08 6213 Domed Unit Skylights
08 7100 Door Hardware
08 8100 Glass Glazing
DIVISION 09 ñ FINISHES
09 0512 Concrete Floor Moisture Content and pH Testing
09 2216 Non-Structural Metal Framing
09 2400 Portland Cement Plastering
09 2900 Gypsum Board
Group 4 Architecture Research + Planning CITY OF SACRAMENTO - Martin Luther King, Jr. Library Remodel
PART 1 - Group4 Project No. 23604-01 Back Check Submission ñ November 01, 2024 PRELIMINARY TABLE OF CONTENTS 00 0010-3
09 3000 Tiling
09 5123 Acoustical Tile Ceilings
09 6423 Vapor Emission Treatment System
09 6500 Resilient Flooring
09 6813 Tile Carpeting
09 8400 Acoustic Room Components
09 8414 Acoustical Wall Panels
09 9100 Painting
09 9300 Staining and Transparent Finishing
09 9623 Graffiti-Resistant Coatings
DIVISION 10 ñ SPECIALTIES
10 1100 Visual Display Surfaces
10 1400 Signage
10 2113 Solid Surface Toilet Compartments
10 2623 Impact-Resistant Wall Protection
10 2813 Commercial Toilet Accessories
10 4400 Fire Protection Specialties
10 5113 Metal Lockers
10 5613 Metal Storage Shelving
DIVISION 11 ñ EQUIPMENT
11 5123 Library Stack Systems
DIVISION 12 ñ FURNISHINGS
12 2413 Roller Window Shades
12 3640 Countertops
FACILITY SERVICES SUBGROUP:
DIVISION 21 ñ FIRE SUPPRESSION
21 0500 Basic Fire Suppression Requirements
21 0503 Through Penetration Firestopping
21 0529 Fire Suppression Supports and Anchors
21 0550 Seismic Requirements for Equipment And Supports 21 0553 Fire Suppression Identification
21 1301 Fire Protection Full Design
DIVISION 22 ñ PLUMBING
22 0500 Basic Plumbing Requirements
22 0505 Plumbing Demolition for Remodeling
22 0513 Motors
22 0529 Plumbing Supports and Anchors
22 0550 Seismic Requirements for Equipment And Supports Group 4 Architecture Research + Planning CITY OF SACRAMENTO - Martin Luther King, Jr. Library Remodel
PART 1 - Group4 Project No. 23604-01 Back Check Submission ñ November 01, 2024 PRELIMINARY TABLE OF CONTENTS 00 0010-4
22 0553 Plumbing Identification
22 0593 Plumbing Testing, Adjusting, And Balancing
22 0716 Plumbing Equipment Insulation
22 0719 Plumbing Piping Insulation
22 0800 Commissioning Of Plumbing
22 1000 Plumbing Piping
22 1030 Plumbing Specialties
22 1200 Tanks - Plumbing
22 1329 Sanitary Sewerage Pumps
22 1429 Sump Pumps
22 3000 Plumbing Equipment
22 4000 Plumbing Fixtures
DIVISION 23 ñ HEATING VENTILATING AND AIR CONDITIONING
23 0500 Basic HVAC Requirements
23 0503 Through Penetration Firestopping
23 0505 HVAC Demolition For Remodeling
23 0513 Motors
23 0529 HVAC Supports And Anchors
23 0548 HVAC Vibration Isolation
23 0553 HVAC Identification
23 0593 Testing, Adjusting, and Balancing
23 0713 Ductwork Insulation
23 0719 HVAC Piping Insulation
23 0800 Commissioning Of HVAC
23 0900 Controls
23 2100 Hydronic Piping
23 2300 Refrigeration Piping and Specialties
23 3100 Ductwork
23 3300 Ductwork Accessories
23 3423 Power Ventilators
23 3600 Air Terminal Units
23 3700 Air Inlets and Outlets
23 4000 Air Cleaning
23 6213 Air Cooled Condensing Units
23 6313 Air Cooled Refrigerant Condensers
23 8126 Split System Air Conditioning Units
23 8145 Variable Refrigerant Flow Heat Pumps
23 8200 Terminal Heat Transfer Units
DIVISION 26 ñ ELECTRICAL
26 0500 Basic Electrical Requirements
26 0503 Through Penetration Firestopping
26 0505 Electrical Demolition for Remodeling
26 0513 Wire and Cable
26 0526 Grounding and Bonding
26 0527 Supporting Devices
Group 4 Architecture Research + Planning CITY OF SACRAMENTO - Martin Luther King, Jr. Library Remodel
PART 1 - Group4 Project No. 23604-01 Back Check Submission ñ November 01, 2024 PRELIMINARY TABLE OF CONTENTS 00 0010-5
26 0533 Conduit and Boxes
26 0553 Electrical Identification
26 0573 Power System Study
26 0800 Commissioning of Electrical
26 0933 Lighting Control Systems
26 2000 Service Entrance
26 2416 Panelboards
26 2726 Wiring Devices
26 2813 Fuses
26 2816 Disconnect Switches
26 5119 LED Lighting
DIVISION 27 ñ COMMUNICATIONS
27 0500 Common Work Results for Communications
27 0526 Grounding Bonding for Communications Systems
27 0529 Hangers And Supports for Communications Systems 27 0533 Conduits and Backboxes for Communications Systems 27 0536 Cable Trays for Communications Systems
27 0543 Underground Ducts and Raceways for Communications Systems 27 0548 Noise And Vibration for Communications Systems
27 0553 Identification for Communications Systems
27 1000 Structured Cabling, Basic Materials & Methods
27 1116 Communications Cabinets, Racks, Frames and Enclosures 27 1119 Communications Termination Blocks and Patch Panels 27 1123 Communications Cable Management
27 1300 Communications Indoor Backbone Cabling
27 1500 Communications Horizontal Cabling
27 4116 Integrated Audio-Video Systems and Equipment
27 5116 Public Address and Mass Notification Systems
DIVISION 28 ñ ELECTRONIC SAFETY AND SECURITY
28 0500 Common Work Results for Electronic Safety and Security 28 0513 Conductors and Cables for Electronic Safety and Security 28 0526 Grounding and Bonding for Electronic Safety and Security 28 0528 Pathways for Electronic Safety and Security
28 1300 Access Control and Alarms Systems
28 2300 Visual Surveillance
28 3100 Fire Alarm and Detection Systems
SITE AND INFRASTRUCTURE SUBGROUP:
DIVISION 31 ñ EARTHWORK
31 1000 Site Clearing
31 2000 Earth Moving
31 2100 Utility Trenching and Backfill
Group 4 Architecture Research + Planning CITY OF SACRAMENTO - Martin Luther King, Jr. Library Remodel
PART 1 - Group4 Project No. 23604-01 Back Check Submission ñ November 01, 2024 PRELIMINARY TABLE OF CONTENTS 00 0010-6
DIVISION 32 ñ EXTERIOR IMPROVEMENTS
32 31 19 Decorative Metal Security Fences and Gates
DIVISION 33 ñ UTILITIES
33 1000 Water System
PROCESS EQUIPMENT SUBGROUP: NOT USED
APPENDIX A:
Structural Calculations
APPENDIX B:
Fire Protection Hydraulic Calculations
APPENDIX C:
Fire Protection Cut Sheets
APPENDIX D:
Fire Alarm Cut Sheets
END OF DOCUMENT
Group 4 Architecture Research + Planning CITY OF SACRAMENTO - Martin Luther King, Jr. Library Remodel
PART 1 - Group4 Project No. 23604-01 Back Check Submission ñ November 01, 2024 PRELIMINARY TABLE OF CONTENTS 00 0010-7
This Page Intentionally Left Blank
Group 4 Architecture Research + Planning CITY OF SACRAMENTO ñ Martin Luther King, Jr. Library Remodel Group 4 Project No. 23604-01 Back Check Submission ñ November 01, 2024 SUMMARY OF WORK 01 1100-1
SECTION 01 1100 - SUMMARY OF WORK
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections, apply to this Section.
1.2 SCOPE OF WORK
A. Abbreviated Written Summary: Briefly and without force and effect upon the Contract Documents, the Work of the Contract can be summarized as follows
1.3 The MLK, Jr. Library Remodel project will transform the interior of the existing ~15,300 library. Full interior renovation including demolition of existing interior, new configuration of spaces, interior finishes, and lighting. Minimal exterior building improvements and sitework related to the fire service connection for the fire sprinkler system will also be included as part of the project.
1.4 DEFINITIONS
A. Order of Precedence: Where a conflict is found between the Drawings and Specifications, the more restrictive requirement takes precedence.
1.5 CONTRACTOR USE OF PREMISES
A. Limit use of the premises to construction activities in areas indicated; allow for Owner occupancy and use by the public.
B. Coordinate use of premises and access to site with the Owner and Architect.
C. Confine operations to areas within Contract limits indicated. Portions of the site beyond areas in which construction operations are indicated are not to be disturbed.
D. Keep driveways and entrances clear at all times. Do not use these areas for parking or storage of materials. Schedule deliveries to minimize requirements for storage of materials.
E. Assume full responsibility for the protection and safekeeping of products under this Contract, stored on the site.
F. Limit use of site for work and storage to areas within the site boundaries unless specific areas are allowed in writing by the Owner.
G. Move any stored products, under Contractor's control, which interfere with operations of the Landlord, or separate contractor.
H. If necessary, obtain and pay for the use of additional storage or work areas needed for operations. Unless otherwise agreed upon, on-site storage shall be limited to areas of new construction.
Group 4 Architecture Research + Planning CITY OF SACRAMENTO ñ Martin Luther King, Jr. Library Remodel Group 4 Project No. 23604-01 Back Check Submission ñ November 01, 2024 SUMMARY OF WORK 01 1100-2
I. Do not unreasonably encumber space with materials.
J. Work area must be kept clean and safe at all times.
K. No propane or similar flammable gas or liquid used in construction is permitted to be stored on the premises. It is to be removed from the premises when not in use during the off hours and weekends.
L. Repair damage caused by construction operations. Take precautions necessary to protect the building and occupants during the construction period.
M. Contractors shall submit both home and office numbers to the Ownerís Project Managerís office for a minimum of 2 employees in the event they must be contacted during off hours or weekends.
1.6 COORDINATION
A. Coordinate work to assure efficient and orderly sequence of installation of construction elements.
B. Verify that characteristics of interrelated operation equipment are compatible; coordinate work having interdependent responsibilities for installing, connection to, and placing such equipment in service. Coordinate space requirements and installation of mechanical and electrical work; make runs parallel with lines of building.
C. Conceal pipes, ducts, and wiring in finished areas unless otherwise indicated. Coordinate locations of fixtures and outlets with finish elements.
D. Coordinate construction schedule and operations with Owner and Architect.
1.7 FIELD ENGINEERING
A. Provide project engineering service; establish lines and levels by use of recognized engineering survey practices.
B. Locate and protect control and reference points.
1.8 REGULATORY REQUIREMENTS AND REFERENCE STANDARDS
A. Regulatory Requirements:
1. Architect has contacted governing authorities and reviewed design requirements of local, state and federal agencies for applicability to Project.
2. Contractor shall be responsible for contacting governing authorities directly for necessary information and decisions bearing upon performance of Work.
B. Reference Standards:
1. For Products specified by association or trade standards, comply with requirements of referenced standard, except when more rigid requirements are specified or are required by applicable codes.
2. Applicable date of each standard is that in effect as of Contract date, except when a specific date is specified.
Group 4 Architecture Research + Planning CITY OF SACRAMENTO ñ Martin Luther King, Jr. Library Remodel Group 4 Project No. 23604-01 Back Check Submission ñ November 01, 2024 SUMMARY OF WORK 01 1100-3
1.9 ORDERING OF MATERIALS
A. Certain materials are considered custom or long-lead items and must be expedited through submittals and ordering. Contractor shall verify delivery for all materials and schedule submittals and orders accordingly.
B. Contractor shall provide written verification that each custom or long-lead item has been ordered in sufficient time to meet proposed construction schedule.
C. When Specifications or Drawings call for materials or construction of a higher quality or larger size than required by governing codes, laws, rules and regulations, the provisions of the Specifications or Drawings shall take precedence.
1.10 CERTIFICATE OF SUBSTANTIAL COMPLETION
A. Certificate of Substantial Completion will be executed for the Work occupied.
B. Prior to Owner occupancy, mechanical and electrical systems shall be fully operational.
Required inspections and tests shall have been successfully completed.
PART 2 - PRODUCTS ñ NOT USED
PART 3 - EXECUTION ñ NOT USED
END OF SECTION 01 1100
Group 4 Architecture Research + Planning CITY OF SACRAMENTO ñ Martin Luther King, Jr. Library Remodel Group 4 Project No. 23604-01 Back Check Submission ñ November 01, 2024 SUMMARY OF WORK 01 1100-4
This Page Intentionally Left Blank
Group 4 Architecture Research + Planning CITY OF SACRAMENTO ñ Martin Luther King, Jr. Library Remodel Group 4 Project No. 23604-01 Back Check Submission ñ November 01, 2024 ALTERNATES 01 2300-1
SECTION 01 2300 ñ ALTERNATES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections, apply to this Section.
1.2 SECTION INCLUDES
A. Submission procedures.
B. Documentation of changes to Contract Sum/Price and Contract Time.
1.3 RELATED SECTIONS
A. Section 01 2513 - Product Substitution Procedures.
B. Section 01 3300 ñ Submittal Procedures: Work schedule affected by Alternates.
1.4 DESCRIPTION
A. The items of work indicated below propose modifications to, substitutions for, additions to and/or deletions from the various parts of the Work specified in other Sections of the Specifications. The acceptance or rejection of any of the alternates is strictly at the option of the City subject to Cityís acceptance of Contractor's stated prices contained in this Proposal.
1.5 REQUIREMENTS
A. Submit Alternates with full description of the proposed Alternate and the effect on adjacent or related components.
B. Alternates quoted on Bid Forms will be reviewed and accepted or rejected at Owner's option.
Accepted Alternates will be identified in the Owner-Contractor Agreement.
C. Coordinate related work and modify surrounding work to integrate the Work of each Alternate.
1.6 SELECTION AND AWARD OF ALTERNATES
A. Indicate variation of Bid Price for Alternates described below and list in Bid Form Document or any supplement to it, which requests a 'difference' in Bid Price by adding to or deducting from the base bid price.
B. Bid will be evaluated on base bid price. After determination of preferred bidder, consideration will be given to Alternates and Bid Price adjustments.
CITY OF FOSTER CITY Group 4 Architecture Research + Planning, Inc.
Foster City Recreation Center Rebuild Project Group 4 Project No. 12421-04 Permit Conform Set ñ 08/14/2024
ALTERNATES 01 2300-2
1.7 SCHEDULE OF ALTERNATES
A. Add Alternate A-01: Fence to enclose north patio area. See A1.2-2 B. Add Alternate A-02: Automated material handling system, OFCI. Opening in (E) wall for dedicated book return for the AMHSs. See a2.5-3
C. Add Alternate A-03: Low roof fascia, repair where damaged and cover full fascia with flashing. See A8.0-1
D. Add Alternate A-04: Replace existing board + batten siding with fiber cement board + batten siding. See A8.0-1
E. Add Alternate A-05: Meeting room "Brown Act" AV technology F. Deduct Alternate D-01: Exterior glazing retrofit. Existing exterior glazing to remain. Add glazing retrofit insulated glazing units to the interior surface of exterior storefront system.
See 08 51 13 ñ window glazing retrofit and 7/A8.0-1
G. Deduct Alternate D-02: 4x4 act ceiling assembly at meeting room instead of wood acoustic ceiling. See A6.0-1
H. Deduct Alternate D-03: 2x4 act ceiling assembly at marketplace, teen, and adult soffit instead of wood acoustical ceiling. See A6.0-1
I. Deduct Alternate D-04: 2X4 act at high roof instead of 4x4 act. See A6.0-2.
J. Deduct Alternate D-05: Eliminate large study room, display and technology to remain on east wall. See A2.5-4
K. Deduct Alternate D-06: Eliminate small study rooms, one display and it's associated with technology to be moved to furred out exterior wall. See A2.5-2 PART 2 - PRODUCTS ñ NOT USED
PART 3 - EXECUTION ñ NOT USED
END OF SECTION 01 2300
Group 4 Architecture Research + Planning CITY OF SACRAMENTO ñ Martin Luther King, Jr. Library Remodel Group 4 Project No. 23604-01 Back Check Submission ñ November 01, 2024 ALTERNATES 01 2300-3
This Page Intentionally Left Blank
Group 4 Architecture Research + Planning CITY OF SACRAMENTO ñ Martin Luther King, Jr. Library Remodel Group 4 Project No. 23604-01 90% CD Plan Check Submission ñ August 29, 2024 SUBSTITUTION PROCEDURES - 012500 - 1
SECTION 012500 - SUBSTITUTION PROCEDURES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes administrative and procedural requirements for substitutions and Value Engineering.
B. Related Requirements:
1. Section 016000 "Product Requirements" for requirements for submitting comparable product submittals for products by listed manufacturers.
1.3 DEFINITIONS
A. Substitutions: Changes in products, materials, equipment, and methods of construction from those required by the Contract Documents and proposed by Contractor.
1. Substitutions for Cause: Changes proposed by Contractor that are required due to changed Project conditions, such as unavailability of product, regulatory changes, or unavailability of required warranty terms.
2. Substitutions for Convenience / Equal: Changes proposed by Contractor or Owner that are not required in order to meet other Project requirements but may offer advantage to Contractor or Owner.
1.4 ACTION SUBMITTALS
A. Substitution Requests: Submit three copies of each request for consideration. Identify product or fabrication or installation method to be replaced. Include Specification Section number and title and Drawing numbers and titles.
1. Substitution Request Form: Use electronic (PDF) copy of form provided in Project Manual.
2. Documentation: Show compliance with requirements for substitutions and the following, as applicable:
a. Statement indicating why specified product or fabrication, or installation method cannot be provided, if applicable.
Group 4 Architecture Research + Planning CITY OF SACRAMENTO ñ Martin Luther King, Jr. Library Remodel Group 4 Project No. 23604-01 90% CD Plan Check Submission ñ August 29, 2024 SUBSTITUTION PROCEDURES - 012500 - 2
b. Coordination of information, including a list of changes or revisions needed to other parts of the Work and to construction performed by Owner and separate contractors that will be necessary to accommodate proposed substitution.
c. Detailed comparison of significant qualities of proposed substitutions with those of the Work specified. Include annotated copy of applicable Specification Section. Significant qualities may include attributes, such as performance, weight, size, durability, visual effect, sustainable design characteristics, warranties, and specific features and requirements indicated. Indicate deviations, if any, from the Work specified. d. Product Data, including drawings and descriptions of products and fabrication and installation procedures.
e. Samples, where applicable or requested.
f. Certificates and qualification data, where applicable or requested. g. List of similar installations for completed projects, with project names and addresses as well as names and addresses of architects and owners. h. Material test reports from a qualified testing agency, indicating and interpreting test results for compliance with requirements indicated. i. Detailed comparison of Contractor's construction schedule using proposed substitutions with products specified for the Work, including effect on the overall Contract Time. If specified product or method of construction cannot be provided within the Contract Time, include letter from manufacturer, on manufacturer's letterhead, stating date of receipt of purchase order, lack of availability, or delays in delivery.
j. Cost information, including a proposal of change, if any, in the Contract Sum.
k. Contractor's certification that proposed substitution complies with requirements in the Contract Documents, except as indicated in substitution request, is compatible with related materials and is appropriate for applications indicated.
l. Contractor's waiver of rights to additional payment or time that may subsequently become necessary because of failure of proposed substitution to produce indicated results.
3. Architect's Action: If necessary, Architect will request additional information or documentation for evaluation within seven (7) days of receipt of a request for substitution. Architect will notify Contractor through Construction Manager of acceptance or rejection of proposed substitution within 15 days of receipt of request, or seven (7) days of receipt of additional information or documentation, whichever is later.
a. Forms of Acceptance: Change Order, Construction Change Directive, or Architect's Supplemental Instructions for minor changes in the Work. b. Use product specified if Architect does not issue a decision on use of a proposed substitution within time allocated.
Group 4 Architecture Research + Planning CITY OF SACRAMENTO ñ Martin Luther King, Jr. Library Remodel Group 4 Project No. 23604-01 90% CD Plan Check Submission ñ August 29, 2024 SUBSTITUTION PROCEDURES - 012500 - 3
1.5 QUALITY ASSURANCE
A. Compatibility of Substitutions: Investigate and document compatibility of proposed substitution with related products and materials. Engage a qualified testing agency to perform compatibility tests recommended by manufacturers.
1.6 PROCEDURES
A. Coordination: Revise or adjust affected work as necessary to integrate work of the approved substitutions.
1.7 SUBSTITUTIONS
A. Substitutions for Cause: Submit requests for substitution immediately on discovery of need for change, but not later than 10 days prior to time required for preparation and review of related submittals.
1. Conditions: Architect will consider Contractor's request for substitution when the following conditions are satisfied. If the following conditions are not satisfied, Architect will return requests without action, except to record noncompliance with these requirements:
a. Requested substitution is consistent with the Contract Documents and will produce indicated results.
b. Substitution request is fully documented and properly submitted. c. Requested substitution will not adversely affect Contractor's construction schedule.
d. Requested substitution has received necessary approvals of authorities having jurisdiction.
e. Requested substitution is compatible with other portions of the Work. f. Requested substitution has been coordinated with other portions of the Work.
g. Requested substitution provides specified warranty.
h. If requested substitution involves more than one contractor, requested substitution has been coordinated with other portions of the Work, is uniform and consistent, is compatible with other products, and is acceptable to all contractors involved.
B. Substitutions for Convenience / Equal:
1. Architect will consider requests for substitution if received no later than 10 days prior to Bid Date.
2. All Substitutions for Convenience / Equal must be pre-approved prior to Bid Date.
3. All requests for pre-approval of Substitutions for Convenience / Equal must be in writing.
Group 4 Architecture Research + Planning CITY OF SACRAMENTO ñ Martin Luther King, Jr. Library Remodel Group 4 Project No. 23604-01 90% CD Plan Check Submission ñ August 29, 2024 SUBSTITUTION PROCEDURES - 012500 - 4
4. All items, materials or processes that are to be considered for pre-approval must be submitted in the manner described in the individual Specification Sections in which they appear, and must include all required and necessary support information, certificates, and product information needed for evaluation.
Responsibility for assembling and providing adequate review material is solely that of the pre-approval application. Adequacy of the material submitted will be determined solely by the Architect, whose decision shall be final.
5. Inadequate applications will not be reviewed. Neither the Architect nor the Owner has an obligation to notify applicants of inadequate applications prior to the established cut-off dates for review.
6. Neither the Architect nor the Owner has an obligation to review proposed equals prior to Bidding unless pre-approval of a particular material, method or item of equipment is expressly required in the Specifications.
7. Conditions: Architect will consider Contractor's request for substitution when the following conditions are satisfied. If the following conditions are not satisfied, Architect will return requests without action, except to record noncompliance with these requirements:
a. Requested substitution offers Owner a substantial advantage in cost, time, energy conservation, or other considerations, after deducting additional responsibilities Owner must assume. Owner's additional responsibilities may include compensation to Architect for redesign and evaluation services, increased cost of other construction by Owner, and similar considerations. b. Requested substitution does not require extensive revisions to the Contract Documents.
c. Requested substitution is consistent with the Contract Documents and will produce indicated results.
d. Substitution request is fully documented and properly submitted. e. Requested substitution will not adversely affect Contractor's construction schedule.
f. Requested substitution has received necessary approvals of authorities having jurisdiction.
g. Requested substitution is compatible with other portions of the Work. h. Requested substitution has been coordinated with other portions of the Work.
i. Requested substitution provides specified warranty.
j. If requested substitution involves more than one contractor, requested substitution has been coordinated with other portions of the Work, is uniform and consistent, is compatible with other products, and is acceptable to all contractors involved.
END OF SECTION 0125000
(SUBSTITUTION FORM TO FOLLOW)
Group 4 Architecture Research + Planning CITY OF SACRAMENTO ñ Martin Luther King, Jr. Library Remodel Group 4 Project No. 23604-01 90% CD Plan Check Submission ñ August 29, 2024 SUBSTITUTION PROCEDURES - 012500 - 5
FORM FOR USE WITH SUBSTITUTION REQUESTS / EQUALS
TO:
PROJECT:
SPECIFIED ITEM:
SECTION: PAGE: PARAGRAPH: DESCRIPTION:
The undersigned requests consideration of the following:
PROPOSED SUBSTITUTION:
Attached data includes product description, specifications, drawings, photographs, performance and test data adequate for evaluation of the requests; applicable portions of the data are clearly identified. Attached data also includes description of changes to Contract Documents that proposed substitution will require for its proper installation.
The undersigned states that the following paragraphs, unless modified on attachments, are correct:
1. The proposed substitution does not affect dimensions shown on Drawings.
2. The undersigned will pay for changes to the building design, including engineering, design, detailing and construction costs caused by the requested substitution.
3. The proposed substitution will have no adverse effect on other trades, the construction schedule or specified warranty requirements.
4. Maintenance and service parts will be locally available for the proposed substitution.
The undersigned further states that the function, appearance and quality of the proposed substitution are equivalent or superior to the specified item.
Submitted by: Title:
Signature: Date:
Firm: Phone:
Address:
Attachments:
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * Accepted: City Architect Rejected: City Architect
By: Date: (City)
By: Date: (Architect)
END FORM FOR USE WITH SUBSTITUTION REQUESTS / EQUALS
Group 4 Architecture Research + Planning CITY OF SACRAMENTO ñ Martin Luther King, Jr. Library Remodel Group 4 Project No. 23604-01 90% CD Plan Check Submission ñ August 29, 2024 SUBSTITUTION PROCEDURES - 012500 - 6
(This page intentionally left blank)