d. Or approved equal.
e. Substitutions: See Section 01 60 00 - Product Requirements.
2. Listed and labeled as complying with UL 267.
3. Suitable for use with conductors/cables and associated insulation/jackets to be installed.
4. Suitable for use at installation temperature.
E. Cable Ties: Material and tensile strength rating suitable for application.
1. Manufacturers:
a. Burndy LLC: www.burndy.com/#sle.
b. Scotchflex.
c. Thomas & Betts.
d. Or approved equal.
e. Substitutions: See Section 01 60 00 - Product Requirements.
F. Sealing Systems for Roof Penetrations: Premanufactured components and accessories as required to preserve integrity of roofing system and maintain roof warranty; suitable for cables and roofing system to be installed; designed to accommodate existing penetrations where applicable.
1. Products:
a. Menzies Metal Products; Electrical Roof Stack and
Cap: www.menzies-metal.com/#sle.
b. Menzies Metal Products; Electrical Retro Box: www.menzies- metal.com/#sle.
c. Substitutions: See Section 01 60 00 - Product Requirements.
G. Firestop Sleeves: Listed; provide as required to preserve fire resistance rating of building elements.
1. Products:
a. HoldRite, a brand of Reliance Worldwide Corporation; HydroFlame Pro Series/HydroFlame Custom Built: www.holdrite.com/#sle. b. Substitutions: See Section 01 60 00 - Product Requirements.
Lionakis No. 019124.02 26 05 19
January 26, 2024 Low-Voltage Electrical Power Conductors and Cables
PART 3 EXECUTION
3.1 EXAMINATION
A. Verify that interior of building has been protected from weather.
B. Verify that work likely to damage wire and cable has been completed.
C. Verify that raceways, boxes, and equipment enclosures are installed and are properly sized to accommodate conductors and cables in accordance with NFPA 70.
D. Verify that raceway installation is complete and supported.
E. Verify that field measurements are as indicated.
F. Verify that conditions are satisfactory for installation prior to starting work.
3.2 PREPARATION
A. Clean raceways thoroughly to remove foreign materials before installing conductors and cables.
3.3 INSTALLATION
A. Circuiting Requirements:
1. Unless dimensioned, circuit routing indicated is diagrammatic.
2. When circuit destination is indicated without specific routing, determine exact routing required.
3. Arrange circuiting to minimize splices.
4. Include circuit lengths required to install connected devices within 10 ft of location indicated.
5. Maintain separation of Class 1, Class 2, and Class 3 remote-control, signaling, and power-limited circuits in accordance with NFPA 70.
6. Maintain separation of wiring for emergency systems in accordance with NFPA 70.
7. Circuiting Adjustments: Unless otherwise indicated, when branch circuits are indicated as separate, combining them together in a single raceway is permitted, under the following conditions:
26 05 19 Lionakis No. 019124.02
Low-Voltage Electrical Power Conductors
and Cables
January 26, 2024
a. Provide no more than six current-carrying conductors in a single raceway. Dedicated neutral conductors are considered current- carrying conductors.
b. Increase size of conductors as required to account for ampacity derating.
c. Size raceways, boxes, etc. to accommodate conductors. d. Record any circuit changes on record drawings.
8. Common Neutrals: Sharing of neutral/grounded conductors among branch circuits is not permitted.
9. Provide oversized neutral/grounded conductors where indicated and as specified below.
a. Provide 200 percent rated neutral for feeders fed from K-rated transformers.
b. Provide 200 percent rated neutral for feeders serving panelboards with 200 percent rated neutral bus.
B. Install products in accordance with manufacturer's instructions.
C. Perform work in accordance with NECA 1 (general workmanship).
D. Install metal-clad cable (Type MC) in accordance with NECA 120.
E. Installation in Raceway:
1. Tape ends of conductors and cables to prevent infiltration of moisture and other contaminants.
2. Pull all conductors and cables together into raceway at same time.
3. Do not damage conductors and cables or exceed manufacturer's recommended maximum pulling tension and sidewall pressure.
4. Use suitable wire pulling lubricant where necessary, except when lubricant is not recommended by the manufacturer.
F. Paralleled Conductors: Install conductors of the same length and terminate in the same manner.
Lionakis No. 019124.02 26 05 19
January 26, 2024 Low-Voltage Electrical Power Conductors and Cables
G. Secure and support conductors and cables in accordance with NFPA 70 using suitable supports and methods approved by the authority having jurisdiction. Provide independent support from building structure. Do not provide support from raceways, piping, ductwork, or other systems.
1. Installation Above Suspended Ceilings: Do not provide support from ceiling support system. Do not provide support from ceiling grid or allow conductors and cables to lay on ceiling tiles.
2. Installation in Vertical Raceways: Provide supports where vertical rise exceeds permissible limits.
H. Terminate cables using suitable fittings.
1. Metal-Clad Cable (Type MC):
a. Use listed fittings.
b. Cut cable armor only using specialized tools to prevent damaging conductors or insulation. Do not use hacksaw or wire cutters to cut armor.
c. Do not use direct-bearing set-screw type fittings for cables with aluminum armor.
I. Install conductors with a minimum of 12 inches of slack at each outlet.
J. Where conductors are installed in enclosures for future termination by others, provide a minimum of 5 feet of slack.
K. Neatly train and bundle conductors inside boxes, wireways, panelboards and other equipment enclosures.
L. Group or otherwise identify neutral/grounded conductors with associated ungrounded conductors inside enclosures in accordance with NFPA 70.
M. Make wiring connections using specified wiring connectors.
1. Make splices and taps only in accessible boxes. Do not pull splices into raceways or make splices in conduit bodies or wiring gutters.
2. Remove appropriate amount of conductor insulation for making connections without cutting, nicking or damaging conductors.
3. Do not remove conductor strands to facilitate insertion into connector. 26 05 19 Lionakis No. 019124.02
Low-Voltage Electrical Power Conductors
and Cables
January 26, 2024
4. Clean contact surfaces on conductors and connectors to suitable remove corrosion, oxides, and other contaminates. Do not use wire brush on plated connector surfaces.
5. Connections for Aluminum Conductors: Fill connectors with oxide inhibiting compound where not pre-filled by manufacturer.
6. Mechanical Connectors: Secure connections according to manufacturer's recommended torque settings.
7. Compression Connectors: Secure connections using manufacturer's recommended tools and dies.
N. Insulate splices and taps that are made with uninsulated connectors using methods suitable for the application, with insulation and mechanical strength at least equivalent to unspliced conductors.
1. Dry Locations: Use insulating covers specifically designed for the connectors, electrical tape, or heat shrink tubing.
a. For taped connections, first apply adequate amount of rubber splicing electrical tape or electrical filler tape, followed by outer covering of vinyl insulating electrical tape.
b. For taped connections likely to require re-entering, including motor leads, first apply varnished cambric electrical tape, followed by adequate amount of rubber splicing electrical tape, followed by outer covering of vinyl insulating electrical tape.
2. Damp Locations: Use insulating covers specifically designed for the connectors, electrical tape, or heat shrink tubing.
a. For connections with insulating covers, apply outer covering of moisture sealing electrical tape.
b. For taped connections, follow same procedure as for dry locations but apply outer covering of moisture sealing electrical tape.
3. Wet Locations: Use heat shrink tubing.
O. Insulate ends of spare conductors using vinyl insulating electrical tape.
P. Field-Applied Color Coding: Where vinyl color coding electrical tape is used in lieu of integrally colored insulation as permitted in Part 2 under "Color Coding", apply half overlapping turns of tape at each termination and at each location conductors are accessible.
Lionakis No. 019124.02 26 05 19
January 26, 2024 Low-Voltage Electrical Power Conductors and Cables
Q. Identify conductors and cables in accordance with Section 26 05 53.
R. Color Code Legend: Provide identification label identifying color code for ungrounded conductors at each piece of feeder or branch-circuit distribution equipment when premises has feeders or branch circuits served by more than one nominal voltage system.
S. Install firestopping to preserve fire resistance rating of partitions and other elements, using materials and methods specified in Section 07 84 00.
T. Unless specifically indicated to be excluded, provide final connections to all equipment and devices, including those furnished by others, as required for a complete operating system.
U. Install wire and cable securely, in a neat and workmanlike manner, as specified in NECA 1.
V. Route wire and cable as required to meet project conditions.
1. Wire and cable routing indicated is approximate unless dimensioned.
2. Where wire and cable destination is indicated and routing is not shown, determine exact routing and lengths required.
3. Include wire and cable of lengths required to install connected devices within 10 ft of location shown.
W. Use wiring methods indicated.
X. Pull all conductors into raceway at same time.
Y. Use suitable wire pulling lubricant for building wire 4 AWG and larger.
Z. Protect exposed cable from damage.
AA. Support cables above accessible ceiling, using spring metal clips or metal cable ties to support cables from structure or ceiling suspension system. Do not rest cable on ceiling panels.
BB. Use suitable cable fittings and connectors.
CC. Neatly train and lace wiring inside boxes, equipment, and panelboards.
DD. Clean conductor surfaces before installing lugs and connectors.
EE. Make splices, taps, and terminations to carry full ampacity of conductors with no perceptible temperature rise.
26 05 19 Lionakis No. 019124.02
Low-Voltage Electrical Power Conductors
and Cables
January 26, 2024
FF. Use split bolt connectors for copper conductor splices and taps, 6 AWG and larger. Tape uninsulated conductors and connector with electrical tape to 150 percent of insulation rating of conductor.
GG. Use solderless pressure connectors with insulating covers for copper conductor splices and taps, 8 AWG and smaller.
HH. Use insulated spring wire connectors with plastic caps for copper conductor splices and taps, 10 AWG and smaller.
II. Trench and backfill for direct burial cable installation as specified in Sections 31 2316 and 31 2323. Install warning tape along entire length of direct burial cable, within 3 inches of grade, as specified in Section 26 0553.
JJ. Identify and color code wire and cable under provisions of Section 26 0553. Identify each conductor with its circuit number or other designation indicated.
3.4 FIELD QUALITY CONTROL
A. See Section 01 40 00 - Quality Requirements, for additional requirements.
B. Inspect wire for physical damage and proper connections.
C. Measure tightness of bolted connections and compare torque measurements with manufacturer’s values.
D. Perform field inspection and testing in accordance with Section 01 4000.
E. Inspect and test in accordance with NETA ATS, except Section 4.
F. Perform inspections and tests listed in NETA ATS, Section 7.3.2. The insulation resistance test is required for all conductors. The resistance test for parallel conductors listed as optional is not required.
1. Disconnect surge protective devices (SPDs) prior to performing any high potential testing. Replace SPDs damaged by performing high potential testing with SPDs connected.
G. Correct deficiencies and replace damaged or defective conductors and cables.
H. Perform field inspection
I. Megger test and record all feeder conductors.
1. Replace conductors failing test.
Lionakis No. 019124.02 26 05 19
January 26, 2024 Low-Voltage Electrical Power Conductors and Cables
2. Test replaced conductors in same manner.
END OF SECTION 26 05 19
Lionakis No. 019124.02 26 05 26
January 26, 2024 Grounding and Bonding for Electrical
Systems
SECTION 26 05 26 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 GENERAL
1.1 SUMMARY
A. Scope: provide a complete grounding and bonding system as shown on the electrical drawings and as described in the specifications such that the entire raceway system including all equipment enclosures, data racks, telephone backboards and cabinets, fixtures, and outlets, etc. are effectively connected to ground.
B. Grounding and bonding requirements.
C. Section includes:
1. Materials and methods for grounding systems and equipment.
2. Grounding electrodes and conductors.
3. Equipment ground conductors.
4. Bonding
5. Grounding well.
6. Ground bars.
7. Chemically enhanced ground electrodes.
8. Ground plate electrodes.
D. Connectors for grounding and bonding.
E. Ground bars.
F. Ground rod electrodes.
G. Chemically-enhanced ground electrodes.
H. Ground plate electrodes.
I. Ground enhancement material.
J. Ground access wells.
K. Pre-fabricated signal reference grids.
L. Provide all components necessary to complete the grounding system(s) consisting of:
26 05 26 Lionakis No. 019124.02
Grounding and Bonding for Electrical
Systems
January 26, 2024
1. Metal underground water pipe.
2. Metal frame of the building.
3. Concrete-encased electrode.
4. Existing metal underground gas piping system.
5. Metal underground gas piping system.
1.2 RELATED REQUIREMENTS
A. Section 26 05 00-Common Work Results for Electrical.
B. Section 26 05 19 - Low-Voltage Electrical Power Conductors and Cables: Additional requirements for conductors for grounding and bonding, including conductor color coding.
1. Includes oxide inhibiting compound.
C. Section 26 05 36 - Cable Trays for Electrical Systems: Additional grounding and bonding requirements for cable tray systems.
D. Section 26 05 53 - Identification for Electrical Systems: Identification products and requirements.
E. Section 26 31 00 - Photovoltaic Collectors: Additional grounding and bonding requirements for photovoltaic systems.
F. Section 26 56 00 - Exterior Lighting: Additional grounding and bonding requirements for pole-mounted luminaires.
1.3 REFERENCE STANDARDS
A. IEEE 81 - IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Grounding System; 2012.
B. NECA 1 - Standard for Good Workmanship in Electrical Construction; 2015.
C. NEMA GR 1 - Grounding Rod Electrodes and Grounding Rod Electrode Couplings; 2022.
D. NETA ATS - Standard For Acceptance Testing Specifications For Electrical Power Equipment And Systems; 2021.
E. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.
Lionakis No. 019124.02 26 05 26
January 26, 2024 Grounding and Bonding for Electrical
Systems
F. NFPA 99 - Health Care Facilities Code; 2024.
G. NFPA 780 - Standard for the Installation of Lightning Protection Systems; 2023.
H. UL 467 - Grounding and Bonding Equipment; Current Edition, Including All Revisions.
1.4 ADMINISTRATIVE REQUIREMENTS
A. Coordination:
1. Verify exact locations of underground metal water service pipe entrances to building.
2. Coordinate the work with other trades to provide steel reinforcement complying with specified requirements for concrete-encased electrode.
3. Notify Electrical Engineer of Record of any conflicts with or deviations from Contract Documents. Obtain direction before proceeding with work.
B. Sequencing:
1. Do not install ground rod electrodes until final backfill and compaction is complete.
1.5 PERFORMANCE REQUIREMENTS
A. Grounding System Resistance:
1. Building grounding electrode: 10 ohms.
2. Separately Derived Sources Grounding Electrode: 10 ohms
3. Non-current carrying metal parts: 25 ohms
4. Grounds not covered above: 25 ohms
1.6 SUBMITTALS
A. See Section 01 30 00 - Administrative Requirements for submittals procedures.
B. Product Data: Provide manufacturer's standard catalog pages and data sheets for grounding and bonding system components.
C. Shop Drawings:
26 05 26 Lionakis No. 019124.02
Grounding and Bonding for Electrical
Systems
January 26, 2024
1. Indicate proposed arrangement for signal reference grids. Include locations of items to be bonded and methods of connection.
D. Product Data: Provide for grounding electrodes and connections.
E. Test Reports: Indicate overall resistance to ground and resistance of each electrode.
F. Manufacturer's Instructions: Indicate application conditions and limitations of use stipulated by product testing agency. Include instructions for storage, handling, protection, examination, preparation, and installation of product.
G. Field quality control test reports.
H. Project Record Documents: Record actual locations of grounding electrode system components and connections.
I. Project Record Documents: Record actual locations of components and grounding electrodes.
J. Certificate of Compliance: Indicate approval of installation by authority having jurisdiction.
1.7 QUALITY ASSURANCE
A. Comply with requirements of NFPA 70.
B. Maintain at the project site a copy of each referenced document that prescribes execution requirements.
C. Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum three years documented experience.
D. Installer Qualifications for Signal Reference Grids: Company with minimum five years documented experience with high frequency grounding systems.
E. Product Listing Organization Qualifications: An organization recognized by OSHA as a Nationally Recognized Testing Laboratory (NRTL) and acceptable to authorities having jurisdiction.
1.8 DELIVERY, STORAGE, AND HANDLING
A. Receive, inspect, handle, and store products in accordance with manufacturer's instructions.
Lionakis No. 019124.02 26 05 26
January 26, 2024 Grounding and Bonding for Electrical
Systems
PART 2 PRODUCTS
2.1 GROUNDING AND BONDING REQUIREMENTS
A. Existing Work: Where existing grounding and bonding system components are indicated to be reused, they may be reused only where they are free from corrosion, integrity and continuity are verified, and where acceptable to the authority having jurisdiction.
B. Do not use products for applications other than as permitted by NFPA 70 and product listing.
C. Unless specifically indicated to be excluded, provide all required components, conductors, connectors, conduit, boxes, fittings, supports, accessories, etc. as necessary for a complete grounding and bonding system.
D. Where conductor size is not indicated, size to comply with NFPA 70 but not less than applicable minimum size requirements specified.
E. Grounding System Resistance:
1. Achieve specified grounding system resistance under normally dry conditions unless otherwise approved by Electrical Engineer of Record.
Precipitation within the previous 48 hours does not constitute normally dry conditions.
2. Grounding Electrode System: Not greater than 5 ohms to ground, when tested according to IEEE 81 using "fall-of-potential" method.
3. Between Grounding Electrode System and Major Electrical Equipment Frames, System Neutral, and Derived Neutral Points: Not greater than
0.5 ohms, when tested using "point-to-point" methods.
F. Grounding Electrode System:
1. Provide connection to required and supplemental grounding electrodes indicated to form grounding electrode system.
a. Provide continuous grounding electrode conductors without splice or joint.
b. Install grounding electrode conductors in raceway where exposed to physical damage. Bond grounding electrode conductor to metallic raceways at each end with bonding jumper.
2. Metal Underground Water Pipe(s):
26 05 26 Lionakis No. 019124.02
Grounding and Bonding for Electrical
Systems
January 26, 2024
a. Provide connection to underground metal domestic and fire protection (where present) water service pipe(s) that are in direct contact with earth for at least 10 feet at an accessible location not more than 5 feet from the point of entrance to the building.
b. Provide bonding jumper(s) around insulating joints/pipes as required to make pipe electrically continuous.
c. Provide bonding jumper around water meter of sufficient length to permit removal of meter without disconnecting jumper.
3. Metal In-Ground Support Structure:
a. Provide connection to metal in-ground support structure that is in direct contact with earth in accordance with NFPA 70.
4. Concrete-Encased Electrode:
a. Provide connection to concrete-encased electrode consisting of not less than 20 feet of bare copper conductor not smaller than 4 AWG embedded within concrete foundation or footing that is in direct contact with earth in accordance with NFPA 70.
5. Ground Ring:
a. Where indicated on drawings, provide a ground ring encircling the building or structure consisting of bare copper conductor not less than 2 AWG in direct contact with earth, installed at a depth of not less than 30 inches.
b. Where location is not indicated, locate ground ring conductor at least 24 inches outside building perimeter foundation.
c. Provide ground enhancement material around conductor where indicated.
d. Provide connection from ground ring conductor to:
1) Perimeter columns of metal building frame.
2) Ground rod electrodes located as indicated.
3) Building structural steel.
6. Ground Rod Electrode(s):
a. Provide three electrodes in an equilateral triangle configuration unless otherwise indicated or required.
Lionakis No. 019124.02 26 05 26
January 26, 2024 Grounding and Bonding for Electrical
Systems
b. Space electrodes not less than 10 feet from each other and any other ground electrode.
c. Where location is not indicated, locate electrode(s) at least 5 feet outside building perimeter foundation as near as possible to electrical service entrance; where possible, locate in softscape (uncovered) area.
d. Provide ground enhancement material around electrode where indicated.
e. Provide ground access well for each electrode.
7. Provide additional ground electrode(s) as required to achieve specified grounding electrode system resistance.
8. Ground Bar: Provide ground bar, separate from service equipment enclosure, for common connection point of grounding electrode system bonding jumpers as permitted in NFPA 70. Connect grounding electrode conductor provided for service-supplied system grounding to this ground bar.
a. Ground Bar Size: 1/4 by 4 by 12 inches unless otherwise indicated or required.
b. Where ground bar location is not indicated, locate in accessible location as near as possible to service disconnect enclosure. c. Ground Bar Mounting Height: 18 inches above finished floor unless otherwise indicated.
9. Ground Riser: Provide common grounding electrode conductor not less than 3/0 AWG for tap connections to multiple separately derived systems as permitted in NFPA 70.
G. Service-Supplied System Grounding:
1. For each service disconnect, provide grounding electrode conductor to connect neutral (grounded) service conductor to grounding electrode system. Unless otherwise indicated, make connection at neutral (grounded) bus in service disconnect enclosure.
2. For each service disconnect, provide main bonding jumper to connect neutral (grounded) bus to equipment ground bus where not factory- installed. Do not make any other connections between neutral (grounded) conductors and ground on load side of service disconnect. 26 05 26 Lionakis No. 019124.02
Grounding and Bonding for Electrical
Systems
January 26, 2024
H. Grounding for Separate Building or Structure Supplied by Feeder(s) or Branch Circuits:
1. Provide grounding electrode system for each separate building or structure.
2. Provide equipment grounding conductor routed with supply conductors.
3. For each disconnecting means, provide grounding electrode conductor to connect equipment ground bus to grounding electrode system.
4. Do not make any connections and remove any factory-installed jumpers between neutral (grounded) conductors and ground.
I. Separately Derived System Grounding:
1. Separately derived systems include, but are not limited to:
a. Transformers (except autotransformers such as buck-boost transformers).
b. Uninterruptible power supplies (UPS), when configured as separately derived systems.
c. Generators, when neutral is switched in the transfer switch.
2. Provide grounding electrode conductor to connect derived system grounded conductor to common grounding electrode conductor ground riser. Unless otherwise indicated, make connection at neutral (grounded) bus in source enclosure.
3. Provide bonding jumper to connect derived system grounded conductor to nearest metal building frame and nearest metal water piping in the area served by the derived system, where not already used as a grounding electrode for the derived system. Make connection at same location as grounding electrode conductor connection.
4. Where common grounding electrode conductor ground riser is used for tap connections to multiple separately derived systems, provide bonding jumper to connect the metal building frame and metal water piping in the area served by the derived system to the common grounding electrode conductor.
5. Outdoor Source: Where the source of the separately derived system is located outside the building or structure supplied, provide connection to grounding electrode at source in accordance with NFPA 70.
Lionakis No. 019124.02 26 05 26
January 26, 2024 Grounding and Bonding for Electrical
Systems
6. Provide system bonding jumper to connect system grounded conductor to equipment ground bus. Make connection at same location as grounding electrode conductor connection. Do not make any other connections between neutral (grounded) conductors and ground on load side of separately derived system disconnect.
7. Where the source and first disconnecting means are in separate enclosures, provide supply-side bonding jumper between source and first disconnecting means.
J. Bonding and Equipment Grounding:
1. Provide bonding for equipment grounding conductors, equipment ground busses, metallic equipment enclosures, metallic raceways and boxes, device grounding terminals, and other normally non-current-carrying conductive materials enclosing electrical conductors/equipment or likely to become energized as indicated and in accordance with NFPA 70.
2. Provide insulated equipment grounding conductor in each feeder and branch circuit raceway. Do not use raceways as sole equipment grounding conductor.
3. Where circuit conductor sizes are increased for voltage drop, increase size of equipment grounding conductor proportionally in accordance with NFPA 70.
4. Unless otherwise indicated, connect wiring device grounding terminal to branch circuit equipment grounding conductor and to outlet box with bonding jumper.
5. Terminate branch circuit equipment grounding conductors on solidly bonded equipment ground bus only. Do not terminate on neutral (grounded) or isolated/insulated ground bus.
6. Provide bonding jumper across expansion or expansion/deflection fittings provided to accommodate conduit movement.
7. Provide bonding for interior metal piping systems in accordance with NFPA 70. This includes, but is not limited to:
a. Metal water piping where not already effectively bonded to metal underground water pipe used as grounding electrode.
b. Metal gas piping.
c. Metal process piping.
26 05 26 Lionakis No. 019124.02
Grounding and Bonding for Electrical
Systems
January 26, 2024
8. Provide bonding for interior metal air ducts.
9. Provide bonding for metal building frame.
10. Provide bonding for metal siding not effectively bonded through attachment to metal building frame.
11. Provide bonding and equipment grounding for pools and fountains and associated equipment in accordance with NFPA 70.
12. Provide redundant grounding and bonding for patient care areas of health care facilities in accordance with NFPA 70 and NFPA 99.
K. Communications Systems Grounding and Bonding:
1. Provide intersystem bonding termination at service equipment or metering equipment enclosure and at disconnecting means for any additional buildings or structures in accordance with NFPA 70.
2. Provide bonding jumper in raceway from intersystem bonding termination to each communications room or backboard and provide ground bar for termination.
a. Bonding Jumper Size: 6 AWG, unless otherwise indicated or required.
b. Raceway Size: 3/4 inch trade size unless otherwise indicated or required.
c. Ground Bar Size: 1/4 by 2 by 12 inches unless otherwise indicated or required.
d. Ground Bar Mounting Height: 18 inches above finished floor unless otherwise indicated.
L. Cable Tray Systems: Also comply with Section 26 05 36.
M. Photovoltaic Systems: Also comply with Section 26 31 00.
N. Pole-Mounted Luminaires: Also comply with Section 26 56 00.
2.2 GROUNDING AND BONDING COMPONENTS
A. General Requirements:
1. Provide products listed, classified, and labeled as suitable for the purpose intended.
Lionakis No. 019124.02 26 05 26
January 26, 2024 Grounding and Bonding for Electrical
Systems
2. Provide products listed and labeled as complying with UL 467 where applicable.
B. Conductors for Grounding and Bonding, in Addition to Requirements of Section 26 05 26:
1. Use insulated copper conductors unless otherwise indicated. a. Exceptions:
1) Use bare copper conductors where installed underground in direct contact with earth.
2) Use bare copper conductors where directly encased in concrete (not in raceway).
2. Factory Pre-fabricated Bonding Jumpers: Furnished with factory-installed ferrules; size braided cables to provide equivalent gauge of specified conductors.
C. Connectors for Grounding and Bonding:
1. Description: Connectors appropriate for the application and suitable for the conductors and items to be connected; listed and labeled as complying with UL 467.
2. Unless otherwise indicated, use exothermic welded connections for underground, concealed and other inaccessible connections. a. Exceptions:
1) Use mechanical connectors for connections to electrodes at ground access wells.
3. Unless otherwise indicated, use mechanical connectors for accessible connections.
a. Exceptions:
1) Use exothermic welded connections for connections to metal building frame.
4. Manufacturers - Mechanical and Compression Connectors:
a. Advanced Lightning Technology (ALT): www.altfab.com/#sle. b. Burndy LLC: www.burndy.com/#sle.
26 05 26 Lionakis No. 019124.02
Grounding and Bonding for Electrical
Systems
January 26, 2024
c. Harger Lightning & Grounding: www.harger.com/#sle.
d. Thomas & Betts Corporation: www.tnb.com/#sle.
e. Or approved equal.
f. Substitutions: See Section 01 60 00 - Product Requirements.
5. Manufacturers - Exothermic Welded Connections:
a. Burndy LLC: www.burndy.com/#sle.
b. ThermOweld, subsidiary of Continental Industries; division of Burndy LLC: www.thermoweld.com/#sle.
c. Or approved equal.
d. Substitutions: See Section 01 60 00 - Product Requirements.
D. Ground Bars:
1. Description: Copper rectangular ground bars with mounting brackets and insulators.
2. Size: As indicated.
3. Holes for Connections: As indicated or as required for connections to be made.
4. Manufacturers:
a. Advanced Lightning Technology (ALT): www.altfab.com/#sle. b. Harger Lightning & Grounding: www.harger.com/#sle.
c. ThermOweld, subsidiary of Continental Industries; division of Burndy LLC: www.thermoweld.com/#sle.
d. Or approved equal.
e. Substitutions: See Section 01 60 00 - Product Requirements.
E. Ground Rod Electrodes:
1. Comply with NEMA GR 1.
2. Material: Copper-bonded (copper-clad) steel.
3. Size: 3/4 inch diameter by 10 feet length, unless otherwise indicated.
Lionakis No. 019124.02 26 05 26
January 26, 2024 Grounding and Bonding for Electrical
Systems
4. Where rod lengths of greater than 10 feet are indicated or otherwise required, sectionalized ground rods may be used.
5. Manufacturers:
a. Advanced Lightning Technology (ALT): www.altfab.com/#sle. b. Galvan Industries, Inc: www.galvanelectrical.com/#sle. c. Harger Lightning & Grounding: www.harger.com/#sle.
d. Or approved equal.
e. Substitutions: See Section 01 60 00 - Product Requirements.
F. Chemically-Enhanced Ground Electrodes:
1. Description: Copper tube factory-filled with electrolytic salts designed to provide a low-impedance ground in locations with high soil resistivity; straight (for vertical installations) or L-shaped (for horizontal installations) as indicated or as required.
2. Length: 10 feet.
3. Integral Pigtail: Factory-attached, sized not less than grounding electrode conductor to be attached.
4. Backfill Material: Grounding enhancement material recommended by electrode manufacturer.
5. Manufacturers:
a. Advanced Lightning Technology (ALT): www.altfab.com/#sle. b. Harger Lightning & Grounding: www.harger.com/#sle.
c. ThermOweld, subsidiary of Continental Industries; division of Burndy LLC: www.thermoweld.com/#sle.
d. Or approved equal.
e. Substitutions: See Section 01 60 00 - Product Requirements.
G. Ground Plate Electrodes:
1. Material: Copper.
2. Size: 24 by 24 by 1/4 inches, unless otherwise indicated. 26 05 26 Lionakis No. 019124.02
Grounding and Bonding for Electrical
Systems
January 26, 2024
3. Manufacturers:
a. Advanced Lightning Technology (ALT): www.altfab.com/#sle. b. Harger Lightning & Grounding: www.harger.com/#sle.
c. ThermOweld, subsidiary of Continental Industries; division of Burndy LLC: www.thermoweld.com/#sle.
d. Or approved equal.
e. Substitutions: See Section 01 60 00 - Product Requirements.
H. Ground Enhancement Material:
1. Description: Factory-mixed conductive material designed for permanent and maintenance-free improvement of grounding effectiveness by lowering resistivity.
2. Resistivity: Not more than 20 ohm-cm in final installed form.
3. Manufacturers:
a. Harger Lightning & Grounding: www.harger.com/#sle.
b. ThermOweld, subsidiary of Continental Industries; division of Burndy LLC: www.thermoweld.com/#sle.
c. Or approved equal.
d. Substitutions: See Section 01 60 00 - Product Requirements.
I. Ground Access Wells:
1. Description: Open bottom round or rectangular well with access cover for testing and inspection; suitable for the expected load at the installed location.
a. Areas Exposed to Vehicular Traffic: Rated for not less than 2000 pounds vertical design load.
2. Size: As required to provide adequate access for testing and inspection, but not less than minimum size requirements specified.
a. Round Wells: Not less than 8 inches in diameter.
b. Rectangular Wells: Not less than 12 by 12 inches.
Lionakis No. 019124.02 26 05 26
January 26, 2024 Grounding and Bonding for Electrical
Systems
3. Depth: As required to extend below frost line to prevent frost upheaval, but not less than 10 inches.
4. Cover: Factory-identified by permanent means with word "GROUND".
5. Manufacturers:
a. Advanced Lightning Technology (ALT): www.altfab.com/#sle. b. Harger Lightning & Grounding: www.harger.com/#sle.
c. ThermOweld, subsidiary of Continental Industries; division of Burndy LLC: www.thermoweld.com/#sle.
d. Or approved equal.
e. Substitutions: See Section 01 60 00 - Product Requirements.
J. Oxide Inhibiting Compound: Comply with Section 26 05 19.
2.3 MANUFACTURERS
A. Cooper Power Systems: www.cooperpower.com.
B. Framatome Connectors International: www.fciconnect.com.
C. Or approved equal.
D. Substitutions: See Section 01 6000 - Product Requirements.
2.4 ELECTRODES
A. Manufacturers:
1. Cooper Power Systems: www.cooperpower.com.
2. Framatome Connectors International: www.fciconnect.com.
3. Or approved equal.
4. Substitutions: See Section 01 6000 - Product Requirements.
B. Rod Electrodes: Copper.
1. Diameter: 3/4 inch.
2. Length: 10 feet.
C. Foundation Electrodes: 3/0 AWG. unless noted on plan. 26 05 26 Lionakis No. 019124.02
Grounding and Bonding for Electrical
Systems
January 26, 2024
2.5 CONNECTORS AND ACCESSORIES
A. Mechanical Connectors: Bronze.
B. Exothermic Connections: Weld
C. Wire: Stranded copper.
D. Grounding Electrode Conductor: Size to meet NFPA 70 requirements.
E. Grounding Well:
1. Well Pipe: 8 inch by 24 inch long clay tile pipe with belled end.
2. Well Cover: Cast iron with legend "GROUND" embossed on cover.
PART 3 EXECUTION
3.1 EXAMINATION
A. Verify that work likely to damage grounding and bonding system components has been completed.
B. Verify that field measurements are as indicated.
C. Verify that conditions are satisfactory for installation prior to starting work.
D. Verify existing conditions prior to beginning work.
E. Verify that final backfill and compaction has been completed before driving rod electrodes.
3.2 INSTALLATION
A. Install products in accordance with manufacturer's instructions.
B. Perform work in accordance with NECA 1 (general workmanship).
C. Ground Electrodes: Provide a grounding electrode system in the main electrical room/space of each building as follows:
1. Provide a 2-inch x 1/4-inch copper ground bar. Length shall be a minimum of 12 inches but longer as required for the number of connections made to the bar. This bar shall serve as the connection point for all grounding electrodes in the building. Install the copper ground bar in a NEMA 1 screw cover cabinet, minimum size 18 inches x 12 inches x 6 inches.
Lionakis No. 019124.02 26 05 26
January 26, 2024 Grounding and Bonding for Electrical
Systems
2. Connect the copper ground bar to the underground metal pipe (other than gas).
a. Connect to metal pipe with approved pipe clamp near the pressure reducing valve.
b. Connect to ground bar with exothermic weld.
c. Connect to metal pipe with copper clamp where copper water pipe occurs and with a malleable iron clamp where cast iron pipe occurs. d. Install grounding conductor, sized as indicated on plans, in a 3/4-inch metal conduit from the ground cabinet to the water pipe. Provide grounding bushings at each end of the conduit.
3. Connect the copper ground bar to the metal frame of the building. a. At all steel framed buildings, provide a connection to the closest column.
b. Connect to column with exothermic weld.
c. Connect to the ground bar with exothermic weld or bolted-type connector.
d. Install grounding conductor, sized as indicated on the plans, in a 3/4- inch metal conduit from the ground cabinet to the column. Provide grounding bushing at each end of the conduit.
4. Connect the copper ground bar to a concrete-encased electrode/Ufer. a. Install a minimum of 20 feet of #3/0 AWG conductor (minimum unless noted otherwise) encased in a minimum of 3 inches of concrete.
Provide a non-metallic protective sleeve, minimum 6 inches long (3 inches in the concrete and 3 inches out of the concrete), located where the conductor exits the concrete.
b. Install a #3/0 conductor from the ground bar to the concrete-encased electrode in a 3/4-inch metal conduit with grounding bushings. Make connections to the concrete-encased electrode with a bolted-type connector and transition from the metal conduit and non-metallic sleeve.
c. Connect to the ground bar with exothermic weld or bolted-type connector.
26 05 26 Lionakis No. 019124.02
Grounding and Bonding for Electrical
Systems
January 26, 2024
5. Provide additional ground rod or concrete-encased electrodes as required to meet the performance requirements listed in these specifications at the ground bar.
a. Install additional ground rods a minimum of 5 feet from any other rod. b. Notify the Owner’s Representative if performance requirements have not been met after installing 2 additional ground rods or concrete- encased electrodes.
6. Install other grounding electrodes as indicated on the single line diagram and other Contract Documents.
D. Grounding Electrode Conductor
1. Install grounding electrode conductor from the main normal and emergency power panels and each separately derived system in the building to the ground bar (grounding electrode system). Install grounding electrode conductor in steel conduit and bond grounding conductor to conduit at entrance and exit. Connect to the ground bar (grounding electrode system) with exothermic weld.
a. Unless otherwise indicated, install main ground unspliced. b. Make connections easily accessible for inspection in ground bar cabinet.
2. Grounding electrode conductor shall be of the same type and quality as other conductors in the building.
3. The main neutral to ground bonding jumper will be located at the site utilities switchboard. Locate additional neutral to ground bonding jumper at separately derived systems only, or at the main service panel when the building is served from a dedicated transformer. Neutral bar with all interior secondary neutrals shall be isolated from the common equipment grounding bus at all other locations.
E. Bonding
1. Provide bonding to meet requirements of CEC.
2. Bond together metal siding not attached to grounded structure, bond to ground.
3. Bond prefabricated metal building to grounding electrode system at a minimum of one location.
Lionakis No. 019124.02 26 05 26
January 26, 2024 Grounding and Bonding for Electrical
Systems
4. Bond together all metallic conduit, boxes, cabinets, and enclosures.
F. Grounding Conductors
1. Provide grounding conductor for each branch circuit indicated.
2. Equipment Grounding Conductor: Provide separate, insulated conductor within each feeder circuit raceway and within each motor feeder raceway.
Terminate each end on suitable lug, bus, or bushing.
3. Provide separate, isolated grounding conductor for each circuit which is installed (all or in part) in non-metallic conduit.
4. Provide separate grounding conductor for circuits installed in flexible steel conduit. Terminate each end on a suitable lug, bus or bushing.
5. Ground all conduit systems, cabinets, equipment, motor frames, etc., in accordance with CEC and applicable codes.
G. Grounding Connections
1. Ground shields of shielded power cable and signal cable at each splice or termination in accordance with recommendations of the splice or termination manufacturer.
2. Ground metal sheathing and exposed metal vertical structural elements of buildings. Ground metal fences enclosing electrical equipment. Bond any metal equipment platforms which support electrical equipment to that equipment. Provide good electrical contact between metal frames and railings supporting pushbutton stations, receptacles, instrument cabinets, etc., and raceways carrying circuits to these devices.
3. Ground all fencing as shown on the grounding details on the Drawings.
4. Bond neutrals of transformers within buildings to the system ground network, and to additional indicated grounding electrodes.
5. Unless shown otherwise, make connections of grounding conductors to ground rods at the upper end of the rod with the end of the rod and the connection point below finished grade.
6. Make connections of sections of outdoor ground mats (counterpoise) for substations or other equipment underground. Make connections of other grounding conductors generally accessible.
26 05 26 Lionakis No. 019124.02
Grounding and Bonding for Electrical
Systems
January 26, 2024
7. In manhole pull boxes, install ground rods with ends 4 to 6 inches above the floor with connections of grounding conductors fully visible and accessible.
8. When making thermite welds, wire brush or file the point of contact to a bare metal surface. Use thermite welding cartridges and molds in accordance with the manufacturer’s recommendations. After welds have been made and cooled, brush slag from the weld area and thoroughly clean the joint. Re-galvanize area if required. For compression connectors, use homogeneous copper, anti-corrosion, surface treatment compound at connectors in accordance with connector manufacturer’s recommendations. Use connectors of proper size for conductors and ground rods specified. Use connector manufacturer’s compression tool.
Notify the Owner’s Representative prior to backfilling any ground connections.
9. Grounding pad plates shall be cast into the slab with the surface flush with the finished floor.
H. Ground Rod Electrodes: Unless otherwise indicated, install ground rod electrodes vertically. Where encountered rock prohibits vertical installation, install at 45 degree angle or bury horizontally in trench at least 30 inches (750 mm) deep in accordance with NFPA 70 or provide ground plates.
1. Outdoor Installations: Unless otherwise indicated, install with top of rod 6 inches below finished grade.
2. Indoor Installations: Unless otherwise indicated, install with 4 inches of top of rod exposed.
3. Provide ground well for future access to rod electrodes.
I. Ground Plate Electrodes: Unless otherwise indicated, install ground plate electrodes at a depth of not less than 30 inches.
J. Make grounding and bonding connections using specified connectors.
1. Remove appropriate amount of conductor insulation for making connections without cutting, nicking or damaging conductors. Do not remove conductor strands to facilitate insertion into connector.
2. Remove nonconductive paint, enamel, or similar coating at threads, contact points, and contact surfaces.
Lionakis No. 019124.02 26 05 26
January 26, 2024 Grounding and Bonding for Electrical
Systems
3. Exothermic Welds: Make connections using molds and weld material suitable for the items to be connected in accordance with manufacturer's recommendations.
4. Mechanical Connectors: Secure connections according to manufacturer's recommended torque settings.
5. Compression Connectors: Secure connections using manufacturer's recommended tools and dies.
K. Identify grounding and bonding system components in accordance with Section 26 05 53.
L. Install ground electrodes at locations indicated. Install additional rod electrodes as required to achieve specified resistance to ground.
M. Provide grounding well pipe with cover at each rod location. Install well pipe top flush with finished grade.
N. Provide grounding electrode conductor and connect to reinforcing steel in foundation footing . Bond steel together.
O. Provide bonding to meet requirements described in Quality Assurance.
P. Provide isolated grounding conductor for circuits supplying electronic cash registers and other similar electronic equipment loads. .
Q. Equipment Grounding Conductor: Provide separate, insulated conductor within each feeder and branch circuit raceway. Terminate each end on suitable lug, bus, or bushing.
3.3 FIELD QUALITY CONTROL
A. See Section 01 40 00 - Quality Requirements, for additional requirements.
B. Inspect and test in accordance with NETA ATS except Section 4.
C. Perform inspections and tests listed in NETA ATS, Section 7.13.
D. Site Tests:
1. Test under provisions of Section 26 08 13.
2. Notify the Owner’s Representative five days before inspection and testing.
26 05 26 Lionakis No. 019124.02
Grounding and Bonding for Electrical
Systems
January 26, 2024
3. Use suitable test instruments to measure resistance to ground of systems. Perform testing in accordance with test instrument manufacturer’s recommendations using the fall-of-potential method.
4. Remove main bonding jumper at main service switchboard and at each separately derived system and test for infinite resistance between neutral and ground systems. Reconnect bonding jumper(s) after completion of testing.
5. Record test results in accordance with Section 26 05 00 and submit.
E. Perform ground electrode resistance tests under normally dry conditions.
Precipitation within the previous 48 hours does not constitute normally dry conditions.
F. Investigate and correct deficiencies where measured ground resistances do not comply with specified requirements.
G. Submit detailed reports indicating inspection and testing results and corrective actions taken.
END OF SECTION 26 05 26
Lionakis No. 019124.02 26 05 29
January 26, 2024 Hangers and Supports for Electrical
Systems
SECTION 26 05 29 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 GENERAL
1.1 SECTION INCLUDES
A. Support and attachment requirements and components for equipment, conduit, cable, boxes, and other electrical work.
1.2 RELATED REQUIREMENTS
A. Section 03 30 00 - Cast-in-Place Concrete: Concrete equipment pads.
B. Section 05 50 00 - Metal Fabrications: Materials and requirements for fabricated metal supports.
C. Section 26 05 00 – Common Work Results for Electrical.
D. Section 26 05 33.13 - Conduit for Electrical Systems: Additional support and attachment requirements for conduits.
E. Section 26 05 33.16 - Boxes for Electrical Systems: Additional support and attachment requirements for boxes.
F. Section 26 05 48 - Vibration and Seismic Controls for Electrical Systems.
G. Section 26 51 00 - Interior Lighting: Additional support and attachment requirements for interior luminaires.
H. Section 26 56 00 - Exterior Lighting: Additional support and attachment requirements for exterior luminaires.
1.3 REFERENCE STANDARDS
A. ASTM A123/A123M - Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products; 2017.
B. ASTM A153/A153M - Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware; 2023.
C. ASTM B633 - Standard Specification for Electrodeposited Coatings of Zinc on Iron and Steel; 2023.
D. ASTM D635 - Standard Test Method for Rate of Burning and/or Extent and Time of Burning of Plastics in a Horizontal Position; 2022.
E. ASTM E84 - Standard Test Method for Surface Burning Characteristics of Building Materials; 2023c.
26 05 29 Lionakis No. 019124.02
Hangers and Supports for Electrical
Systems
January 26, 2024
F. MFMA-4 - Metal Framing Standards Publication; 2004.
G. ICC-ES AC01 - Acceptance Criteria for Expansion Anchors in Masonry Elements; 2009.
H. ICC-ES AC106 - Acceptance Criteria for Predrilled Fasteners (Screw Anchors) in Masonry Elements; 2006
I. ICC-ES AC193 - Acceptance Criteria for Mechanical Anchors in Concrete Elements; 2010
J. ICC-ES AC308 - Acceptance Criteria for Post-Installed Adhesive Anchors in Concrete Elements; 2009.
K. NECA 1 - Standard for Good Workmanship in Electrical Construction; 2015.
L. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.
M. NFPA 101 - Life Safety Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.
N. UL 5B - Strut-Type Channel Raceways and Fittings; Current Edition, Including All Revisions.
1.4 ADMINISTRATIVE REQUIREMENTS
A. Coordination:
1. Coordinate sizes and arrangement of supports and bases with actual equipment and components to be installed.
2. Coordinate work to provide additional framing and materials required for installation.
3. Coordinate compatibility of support and attachment components with mounting surfaces at installed locations.
4. Coordinate arrangement of supports with ductwork, piping, equipment and other potential conflicts.
5. Notify LP Consulting Engineers, Inc. of any conflicts with or deviations from Contract Documents. Obtain direction before proceeding with work.
B. Sequencing:
Lionakis No. 019124.02 26 05 29
January 26, 2024 Hangers and Supports for Electrical
Systems
1. Do not install products on or provide attachment to concrete surfaces until concrete has cured; see Section 03 30 00.
1.5 SUBMITTALS
A. See Section 01 30 00 - Administrative Requirements for submittal procedures.
B. Product Data: Provide manufacturer's standard catalog pages and data sheets for channel/strut framing systems, nonpenetrating rooftop supports, and post-installed concrete/masonry anchors.
1. Fiberglass Channel/Strut Framing Systems: Include requirements for strength derating according to ambient temperature.
C. Shop Drawings: Include details for fabricated hangers and supports where materials or methods other than those indicated are proposed for substitution.
D. Design Data
1. Indicate hanger and support framing and attachment methods.
2. Submit seismic and structural calculations for proposed methods of support and attachment.
E. Derating Calculations for Fiberglass Channel/Strut Framing Systems: Indicate load ratings adjusted for applicable service conditions.
F. Evaluation Reports: For products specified as requiring evaluation and recognition by ICC Evaluation Service, LLC (ICC-ES), provide current ICC- ES evaluation reports upon request.
G. Installer's qualification statement.
H. Product Data: Provide manufacturer’s catalog data for fastening systems.
I. Manufacturer's Instructions: Indicate application conditions and limitations of use stipulated by product testing agency. Include instructions for storage, handling, protection, examination, preparation, and installation of product.
1.6 QUALITY ASSURANCE
A. Conform to requirements of NFPA 70.
B. Maintain at project site one copy of each referenced document that prescribes execution requirements.
C. Installer Qualifications for Field Welding: See Section 05 50 00. 26 05 29 Lionakis No. 019124.02
Hangers and Supports for Electrical
Systems
January 26, 2024
D. Product Listing Organization Qualifications: Organization recognized by OSHA as Nationally Recognized Testing Laboratory (NRTL) and acceptable to authorities having jurisdiction.
1.7 DELIVERY, STORAGE, AND HANDLING
A. Receive, inspect, handle, and store products in accordance with manufacturer's instructions.
PART 2 PRODUCTS
2.1 SUPPORT AND ATTACHMENT COMPONENTS
A. General Requirements:
1. Comply with the following. Where requirements differ, comply with most stringent.
a. NFPA 70.
b. Applicable building code.
c. Requirements of authorities having jurisdiction.
2. Provide required hangers, supports, anchors, fasteners, fittings, accessories, and hardware as necessary for complete installation of electrical work.
3. Provide products listed, classified, and labeled as suitable for purpose intended, where applicable.
4. Where support and attachment component types and sizes are not indicated, select in accordance with manufacturer's application criteria as required for the load to be supported with a minimum safety factor of 25% . Include consideration for vibration, equipment operation, and shock loads where applicable.
5. Do not use products for applications other than as permitted by NFPA 70 and product listing.
6. Do not use wire, chain, perforated pipe strap, or wood for permanent supports unless specifically indicated or permitted.
7. Steel Components: Use corrosion-resistant materials suitable for environment where installed.
a. Indoor Dry Locations: Use zinc-plated steel or approved equivalent unless otherwise indicated.
Lionakis No. 019124.02 26 05 29
January 26, 2024 Hangers and Supports for Electrical
Systems
b. Outdoor and Damp or Wet Indoor Locations: Use galvanized steel, stainless steel, or approved equivalent unless otherwise indicated. c. Zinc-Plated Steel: Electroplated in accordance with ASTM B633. d. Galvanized Steel: Hot-dip galvanized after fabrication in accordance with ASTM A123/A123M or ASTM A153/A153M.
B. Components for Vibration Isolation and/or Seismic Controls: See Section 26 05 48.
C. Materials for Metal Fabricated Supports: See Section 05 50 00.
D. Conduit and Cable Supports: Straps and clamps suitable for conduit or cable to be supported.
1. Manufacturers:
a. ABB: www.electrification.us.abb.com/#sle.
b. Eaton Corporation: www.eaton.com/#sle.
c. Emerson Electric Co; O-Z/Gedney: www.emerson.com/#sle. d. HoldRite, a brand of Reliance Worldwide
Corporation: www.holdrite.com/#sle.
e. nVent; Caddy: www.nvent.com/#sle.
f. Substitutions: See Section 01 60 00 - Product Requirements.
2. Conduit Straps: One-hole or two-hole type; steel or malleable iron.
3. Conduit Clamps: Bolted type unless otherwise indicated.
E. Outlet Box Supports: Hangers and brackets suitable for boxes to be supported.
F. Metal Channel/Strut Framing Systems:
1. Description: Factory-fabricated, continuous-slot, metal channel/strut and associated fittings, accessories, and hardware required for field assembly of supports.
2. Comply with MFMA-4.
3. Channel/Strut Used as Raceway, Where Indicated: Listed and labeled as complying with UL 5B.
26 05 29 Lionakis No. 019124.02
Hangers and Supports for Electrical
Systems
January 26, 2024
4. Channel Material:
a. Indoor Dry Locations: Use painted steel, zinc-plated steel, or galvanized steel.
b. Outdoor and Damp or Wet Indoor Locations: Use galvanized steel.
5. Minimum Channel Thickness: Steel sheet, 12 gauge, 0.1046 inch.
6. Minimum Channel Dimensions: 1-5/8 inch width by 1-5/8 inch height.
G. Fiberglass Channel/Strut Framing Systems:
1. Description: Factory-fabricated, continuous-slot, fiberglass channel/strut and associated fittings, accessories, and hardware required for field assembly of supports.
2. Channel Material: Use polyester resin or vinyl ester resin.
3. Minimum Channel Dimensions: 1-5/8 inch wide by 1 inch high.
4. Flammability: Fire retardant with NFPA 101, Class A flame spread index, maximum of 25, when tested in accordance with ASTM E84; self extinguishing in accordance with ASTM D635.
H. Hanger Rods: Threaded, zinc-plated steel unless otherwise indicated.
1. Minimum Size, Unless Otherwise Indicated or Required:
a. Equipment Supports: 1/2-inch diameter.
b. Busway Supports: 1/2-inch diameter.
c. Single Conduit up to 1-inch (27 mm) Trade Size: 1/4-inch diameter. d. Single Conduit Larger than 1-inch (27 mm) Trade Size: 3/8-inch diameter.
e. Trapeze Support for Multiple Conduits: 3/8-inch diameter. f. Outlet Boxes: 1/4-inch diameter.
g. Luminaires: 1/4-inch diameter.
I. Nonpenetrating Rooftop Supports for Low-Slope Roofs:
1. Description: Steel pedestals with thermoplastic or rubber bases that rest on top of roofing membrane, not requiring attachment to roof structure and not penetrating roofing assembly, with support fixtures as specified.
Lionakis No. 019124.02 26 05 29
January 26, 2024 Hangers and Supports for Electrical
Systems
2. Base Sizes: As required to distribute load sufficiently to prevent indentation of roofing assembly.
3. Attachment/Support Fixtures: As recommended by manufacturer, same type as indicated for equivalent indoor hangers and supports.
4. Mounting Height: Provide minimum clearance of 6 inches under supported component to top of roofing.
J. Anchors and Fasteners:
1. Unless otherwise indicated and where not otherwise restricted, use anchor and fastener types indicated for specified applications.
2. Concrete: Use preset concrete inserts, expansion anchors, or screw anchors.
3. Solid or Grout-Filled Masonry: Use expansion anchors or screw anchors.
4. Hollow Masonry: Use toggle bolts.
5. Hollow Stud Walls: Use toggle bolts.
6. Steel: Use beam clamps, machine bolts, or welded threaded studs.
7. Sheet Metal: Use sheet metal screws.
8. Wood: Use wood screws.
9. Hammer-driven anchors and fasteners are not permitted. a. Nails are permitted for attachment of nonmetallic boxes to wood frame construction.
b. Staples are permitted for attachment of nonmetallic-sheathed cable to wood frame construction.
10. Preset Concrete Inserts: Continuous metal channel/strut and spot inserts specifically designed to be cast in concrete ceilings, walls, and floors. a. Manufacturer: Same as manufacturer of metal channel/strut framing system.
b. Comply with MFMA-4.
c. Channel Material: Use galvanized steel.
d. Minimum Channel Thickness: Steel sheet, 12 gauge, 0.1046 inch minimum base metal thickness.
26 05 29 Lionakis No. 019124.02
Hangers and Supports for Electrical
Systems
January 26, 2024
11. Post-Installed Concrete and Masonry Anchors: Evaluated and recognized by ICC Evaluation Service, LLC (ICC-ES) for compliance with applicable building code.
2.2 MANUFACTURERS (LISTED IN ALPHABETICALLY ORDER ONLY AND NOT
NECESSARY BY PREFERENCE)
A. Thomas & Betts Corporation: www.tnb.com.
B. Threaded Rod Company: www.threadedrod.com.
C. Or Approved Equal.
D. Substitutions: See Section 01 6000 - Product Requirements.
2.3 SUPPORTS
A. Pipe hangers for individual conduits shall be factory made, consisting of a pipe ring and threaded suspension rod. The pipe ring shall be malleable iron, split and hinged, or shall be springable wrought steel. Rings shall be bolted to or interlocked with the suspension rod socket.
B. Pipe racks for groups of parallel conduits shall be constructed of galvanized structural steel preformed channels of length as required, suspended on threaded rods and secured thereto with nuts above and below the cross bar.
C. Factory made pipe straps shall be one hole malleable iron or two hole galvanized clamps.
D. Supporting rods shall be at least 3/8" diameter and channel shall be at least 3/4" deep. Supporting hardware shall be galvanized steel.
2.4 MATERIALS
A. Hangers, Supports, Anchors, and Fasteners - General: Corrosion-resistant materials of size and type adequate to carry the loads of equipment and conduit, including weight of wire in conduit.
B. Supports: Fabricated of structural steel or formed steel members; galvanized.
C. Anchors and Fasteners:
1. Sheet Metal Screws: Steel
2. Machine Screws Bolts, Nuts and Washers: Steel
3. Precast Inserts: Suitable for the purpose.
Lionakis No. 019124.02 26 05 29
January 26, 2024 Hangers and Supports for Electrical
Systems
4. Anchor Bolts, expansion type (stainless steel).
a. Phillips Red-Head
b. Hilti Kwik-Bolt.
c. WEJ-IT.
5. Cast-in-Place Anchors: Suitable for the purpose (hot-dip galvanized except cadmium plated in dry locations)
6. Beam Clamps: Steel.
7. Detention Fasteners: In accordance with Section 11 19 23.
D. Concrete Structural Elements: Use precast inserts, expansion anchors, or preset inserts.
E. Steel Structural Elements: Use beam clamps or welded fasteners.
F. Concrete Surfaces: Use self-drilling anchors or expansion anchors.
G. Hollow Masonry, Plaster, and Gypsum Board Partitions: Use toggle bolts or hollow wall fasteners.
H. Solid Masonry Walls: Use expansion anchors or preset inserts.
I. Sheet Metal: Use sheet metal screws.
J. Wood Elements: Use wood screws.
K. Fastener Types:
1. Concrete Wedge Expansion Anchors: Complying with ICC-ES AC193.
2. Masonry Wedge Expansion Anchors: Complying with ICC-ES AC01.
3. Concrete Screw Type Anchors: Complying with ICC-ES AC193.
4. Masonry Screw Type Anchors: Complying with ICC-ES AC106.
5. Other Types: As required.
6. Manufacturers:
a. Powers Fasteners, Inc: www.powers.com.
b. Or approved equal.
L. Formed Steel Channel as indicated on drawings.
26 05 29 Lionakis No. 019124.02
Hangers and Supports for Electrical
Systems
January 26, 2024
M. Steel Spring Clips: As indicated on drawings
PART 3 EXECUTION
3.1 EXAMINATION
A. Verify that field measurements are as indicated.
B. Verify that mounting surfaces are ready to receive support and attachment components.
C. Verify that conditions are satisfactory for installation prior to starting work.
3.2 INSTALLATION
A. General
1. Install products in accordance with manufacturer's instructions.
2. Provide independent support from building structure. Do not provide support from piping, ductwork, or other systems.
3. Do not penetrate or otherwise notch or cut structural members without approval of Structural Engineer.
4. In Correctional Facilities, provide and install detention metal fasteners in inmate accessible areas in accordance with Section 11 19 23.
B. Install hangers and supports in accordance with NECA 1.
C. Install anchors and fasteners in accordance with ICC Evaluation Services, LLC (ICC-ES) evaluation report conditions of use where applicable.
1. Concrete – Precast inserts, cast-place anchors, or expansion type anchor bolts.
a. When installing drilled-in anchors in non-prestresses reinforced concrete, avoid the reinforcing bars.
b. When installing drilled-in anchors into prestressed concrete (Pre- or Post-tensioned) locate tendons by using a non-destructive method prior to installation. Maintain a minimum clearance of one-inch between the reinforcement and the drilled-in anchor.
2. Sheet Metal – Sheet metal screws or machine bolts, nuts, and washers.
3. Structural Steel Members – Beam clamps, machine screws, bolts, nuts, and washers.
Lionakis No. 019124.02 26 05 29
January 26, 2024 Hangers and Supports for Electrical
Systems
D. Provide independent support from building structure. Do not provide support from piping, ductwork, or other systems.
E. Unless specifically indicated or approved by LP Consulting Engineers, Inc., do not provide support from suspended ceiling support system or ceiling grid.
F. Unless specifically indicated or approved by LP Consulting Engineers, Inc., do not provide support from roof deck.
G. Do not penetrate or otherwise notch or cut structural members without approval of Structural Engineer.
H. Provide required vibration isolation and/or seismic controls; see Section 26 05 48.
I. Field Welding, Where Approved by LP Consulting Engineers, Inc.: See Section 05 50 00.
J. Equipment Support and Attachment:
1. Use metal, fabricated supports or supports assembled from metal channel/strut to support equipment as required.
2. Use metal channel/strut secured to studs to support equipment surface mounted on hollow stud walls when wall strength is not sufficient to resist pull-out.
3. Use metal channel/strut to support surface-mounted equipment in wet or damp locations to provide space between equipment and mounting surface.
4. Unless otherwise indicated, mount floor-mounted equipment on properly sized concrete pad 3 inches in height; see Section 03 30 00.
5. Securely fasten floor-mounted equipment. Do not install equipment such that it relies on its own weight for support.
6. Install surface mounted cabinets and panelboards with minimum of four anchors.
7. In wet and damp locations, use steel channel supports to stand cabinets and panelboards 13/16-inch minimum off wall.
8. Use sheet metal channels to bridge studs above and below cabinets and panelboards recessed in hollow partitions.
9. Support equipment in accordance with manufacturer’s instructions. 26 05 29 Lionakis No. 019124.02
Hangers and Supports for Electrical
Systems
January 26, 2024
10. Verify that equipment will fit support layouts indicated. a. Where suitable equipment is used, revise indicated supports to fit at no additional cost.
11. Arrange for necessary openings to allow entry of equipment. a. Where equipment cannot be installed as structure is being erected, provide and arrange for building-in of boxes, sleeves, or other devices to allow for later installation.
K. Conduit Support and Attachment
1. In damp or wet locations, space conduit support directly from concrete or metal structure out at least ¼ inch using straps with spacers or, if three (3) or more conduits are located in a parallel run, they shall be spaced out from the wall approximately 5/8 inch to 1 inch by means of a channel.
2. Runs of individual conduit suspended from the floor or ceiling shall be supported with pipe hangers. Where three (3) or more conduits are suspended from the floor or ceiling, suitable racks shall be constructed from channel material with suitable fittings.
3. Space supporting points no greater than required by CEC.
L. Sleeves
1. Set sleeves in position in formwork. Provide reinforcing around sleeves.
2. Extend sleeves through floors 1 inch above finished floor levels. Caulk sleeves full depth and provide floor plate.
3. Where raceway penetrated floor, ceiling, or wall. Close off space between pipe or duct and adjacent work with fire stopping insulation and caulk seal.
M. Conduit Support and Attachment: See Section 26 05 33.13 for additional requirements.
N. Box Support and Attachment: See Section 26 05 33.16 for additional requirements.
O. Busway Support and Attachment: See Section 26 25 13 for additional requirements.
Lionakis No. 019124.02 26 05 29
January 26, 2024 Hangers and Supports for Electrical
Systems
P. Interior Luminaire Support and Attachment: See Section 26 51 00 for additional requirements.
Q. Exterior Luminaire Support and Attachment: See Section 26 56 00 for additional requirements.
R. Preset Concrete Inserts: Use manufacturer provided closure strips to inhibit concrete seepage during concrete pour.
S. Secure fasteners in accordance with manufacturer's recommended torque settings.
T. Remove temporary supports.
U. Identify independent electrical component support wires above accessible ceilings, where permitted, with color distinguishable from ceiling support wires in accordance with NFPA 70.
3.3 FIELD QUALITY CONTROL
A. See Section 01 40 00 - Quality Requirements for additional requirements.
B. Inspect support and attachment components for damage and defects.
C. Repair cuts and abrasions in galvanized finishes using zinc-rich paint recommended by manufacturer. Replace components that exhibit signs of corrosion.
D. Correct deficiencies and replace damaged or defective support and attachment components.
1. Obtain permission from the Architect and the Structural Engineer before drilling or cutting structural members.
E. All expansion anchors shall have 50 percent of the bolts (alternate bolts in any group arrangement) proof tested in tension and certified by a recognized testing agency at the values indicated in the following table, except where shown otherwise in the Contract Documents. If there are any failures, the immediately adjacent bolts must then also be tested. Anchor capacities shall not exceed 80 percent of the values in the published ICBO report. 26 05 29 Lionakis No. 019124.02
Hangers and Supports for Electrical
Systems
January 26, 2024
END OF SECTION 26 05 29
Lionakis No. 019124.02 26 05 33.13
January 26, 2024 Conduit for Electrical Systems
SECTION 26 05 33.13 - CONDUIT FOR ELECTRICAL SYSTEMS
PART 1 GENERAL
1.1 SUMMARY
A. Scope: Provide rigid metallic conduit, rigid non-metallic conduit, intermediate metal conduit, flexible metal conduit, electrical metallic tubing, surface metal and/or non-metallic raceways, cable tray and wireways as shown on the drawings and as described in the specifications.
1.2 SECTION INCLUDES
A. Galvanized steel rigid metal conduit (RMC).
B. Galvanized steel intermediate metal conduit (IMC).
C. PVC-coated galvanized steel rigid metal conduit (RMC).
D. Flexible metal conduit (FMC).
E. Liquidtight flexible metal conduit (LFMC).
F. Galvanized steel electrical metallic tubing (EMT).
G. Rigid polyvinyl chloride (PVC) conduit.
H. Reinforced thermosetting resin conduit (RTRC).
I. Conduit, fittings and conduit bodies.
1.3 RELATED REQUIREMENTS
A. Section 03 30 00 - Cast-in-Place Concrete: Concrete encasement of conduits.
B. Section 07 84 00 - Firestopping.
C. Section 26 05 00 – Common Work Results for Electrical.
D. Section 26 05 19 - Low-Voltage Electrical Power Conductors and Cables: Cable assemblies consisting of conductors protected by integral metal armor.
E. Section 26 05 26 - Grounding and Bonding for Electrical Systems.
1. Includes additional requirements for fittings for grounding and bonding.
F. Section 26 05 29 - Hangers and Supports for Electrical Systems. 26 05 33.13 Lionakis No. 019124.02
Conduit for Electrical Systems January 26, 2024
G. Section 26 05 33.16 - Boxes for Electrical Systems.
H. Section 26 05 33.23 - Surface Raceways for Electrical Systems.
I. Section 26 05 39 - Underfloor Raceways for Electrical Systems.
J. Section 26 05 48 - Vibration and Seismic Controls for Electrical Systems.
K. Section 26 05 53 - Identification for Electrical Systems: Identification products and requirements.
L. Section 26 21 00 - Low-Voltage Electrical Service Entrance: Additional requirements for electrical service conduits.
M. Section 26 27 23 - Indoor Service Poles.
N. Section 27 05 33.13 - Conduit for Communications Systems.
O. Section 31 23 16 - Excavation.
P. Section 31 23 16.13 - Trenching: Excavating, bedding, and backfilling.
Q. Section 31 23 23 - Fill: Bedding and backfilling.
R. Section 33 71 19 - Electrical Underground Ducts, Ductbanks, and Manholes.
S. The requirements of the kitchen equipment consultan plans and specifications.
1.4 REFERENCE STANDARDS
A. ANSI C80.1 - American National Standard for Electrical Rigid Steel Conduit (ERSC); 2020.
B. ANSI C80.3 - American National Standard for Electrical Metallic Tubing -- Steel (EMT-S); 2020.
C. ANSI C80.5 - American National Standard for Electrical Rigid Metal Conduit - - Aluminum (ERMC-A); 2020.
D. ANSI C80.6 - American National Standard for Electrical Intermediate Metal Conduit; 2018.
E. NECA 1 - Standard for Good Workmanship in Electrical Construction; 2015.
F. NECA 101 - Standard for Installing Steel Conduits (Rigid, IMC, EMT); 2020.
G. NECA 102 - Standard for Installing Aluminum Rigid Metal Conduit; 2004.
Lionakis No. 019124.02 26 05 33.13
January 26, 2024 Conduit for Electrical Systems
H. NECA 111 - Standard for Installing Nonmetallic Raceways (RNC, ENT, LFNC); 2017.
I. NEMA FB 1 - Fittings, Cast Metal Boxes, and Conduit Bodies for Conduit, Electrical Metallic Tubing, and Cable; 2014.
J. NEMA RN 1 - Polyvinyl-Chloride (PVC) Externally Coated Galvanized Rigid Steel Metal Conduit and Intermediate Metal Conduit; 2018.
K. NEMA TC 2 - Electrical Polyvinyl Chloride (PVC) Conduit; 2020.
L. NEMA TC 3 - Polyvinyl Chloride (PVC) Fittings for Use with Rigid PVC Conduit and Tubing; 2021.
M. NEMA TC 14 (SERIES) - Reinforced Thermosetting Resin Conduit and Fittings Series; 2015.
N. NEMA TC 14.AG - Aboveground Reinforced Thermosetting Resin Conduit (RTRC) and Fittings; 2015 (Reaffirmed 2021).
O. NEMA TC 14.BG - Belowground Reinforced Thermosetting Resin Conduit (RTRC) and Fittings; 2015 (Reaffirmed 2020).
P. NEMA TC 14.XW - Extra Heavy Wall Aboveground Reinforced Thermosetting Resin Conduit (RTRC) and Fittings; 2015 (Reaffirmed 2021).
Q. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.
R. UL 1 - Flexible Metal Conduit; Current Edition, Including All Revisions.
S. UL 6 - Electrical Rigid Metal Conduit-Steel; Current Edition, Including All Revisions.
T. UL 6A - Electrical Rigid Metal Conduit-Aluminum, Red Brass, and Stainless Steel; Current Edition, Including All Revisions.
U. UL 360 - Liquid-Tight Flexible Metal Conduit; Current Edition, Including All Revisions.
V. UL 514B - Conduit, Tubing, and Cable Fittings; Current Edition, Including All Revisions.
W. UL 651 - Schedule 40, 80, Type EB and A Rigid PVC Conduit and Fittings; Current Edition, Including All Revisions.
26 05 33.13 Lionakis No. 019124.02
Conduit for Electrical Systems January 26, 2024
X. UL 797 - Electrical Metallic Tubing-Steel; Current Edition, Including All Revisions.
Y. UL 1203 - Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use in Hazardous (Classified) Locations; Current Edition, Including All Revisions.
Z. UL 1242 - Electrical Intermediate Metal Conduit-Steel; Current Edition, Including All Revisions.
AA. UL 1660 - Liquid-Tight Flexible Nonmetallic Conduit; Current Edition, Including All Revisions.
BB. UL 2419 - Outline of Investigation for Electrically Conductive Corrosion Resistant Compounds; Current Edition, Including All Revisions.
CC. UL 2420 - Belowground Reinforced Thermosetting Resin Conduit (RTRC) and Fittings; Current Edition, Including All Revisions.
DD. UL 2515 - Aboveground Reinforced Thermosetting Resin Conduit (RTRC) and Fittings; Current Edition, Including All Revisions.
EE. UL 2515A - Standard for Supplemental Requirements for Extra Heavy Wall Reinforced Thermosetting Resin Conduit (RTRC) and Fittings; Current Edition, Including All Revisions.
1.5 ADMINISTRATIVE REQUIREMENTS
A. Coordination:
1. Coordinate minimum sizes of conduits with actual type and quantity of conductors to be installed, including adjustments for conductor sizes increased for voltage drop.
2. Coordinate arrangement of conduits with structural members, ductwork, piping, equipment, and other potential conflicts.
3. Verify exact conduit termination locations required for boxes, enclosures, and equipment.
4. Coordinate work to provide roof penetrations that preserve integrity of roofing system and do not void roof warranty.
5. Notify Electrical Engineer of Record of any conflicts with or deviations from Contract Documents. Obtain direction before proceeding with work.
B. Sequencing:
Lionakis No. 019124.02 26 05 33.13
January 26, 2024 Conduit for Electrical Systems
1. Do not begin installation of conductors and cables until installation of conduit between termination points is complete.
1.6 SUBMITTALS
A. See Section 01 30 00 - Administrative Requirements for submittals procedures.
B. Product Data: Provide manufacturer's standard catalog pages and data sheets for conduits and fittings.
C. Shop Drawings:
1. Indicate proposed arrangement for conduits to be installed within structural concrete slabs, where permitted.
2. Include proposed locations of roof penetrations and proposed methods for sealing.
D. Project Record Documents: Record actual routing for conduits installed underground, conduits embedded within concrete slabs, and conduits 2-inch (53 mm) trade size and larger.
E. Product Data: Provide for metallic conduit, flexible metal conduit, liquidtight flexible metal conduit, metallic tubing, nonmetallic conduit, fittings, and conduit bodies.
F. Project Record Documents: Accurately record actual routing of conduits larger than 1 1/4 inches.
1.7 QUALITY ASSURANCE
A. Documents at Project Site: Maintain at project site one copy of manufacturer's instructions and shop drawings.
B. Product Listing Organization Qualifications: Organization recognized by OSHA as Nationally Recognized Testing Laboratory (NRTL) and acceptable to authorities having jurisdiction.
C. Products: Listed and classified by Underwriters Laboratories Inc. as suitable for purpose specified and shown.
1.8 DELIVERY, STORAGE, AND HANDLING
A. Receive, inspect, handle, and store conduit and fittings in accordance with manufacturer's instructions.
B. Accept conduit on site. Inspect for damage.
26 05 33.13 Lionakis No. 019124.02
Conduit for Electrical Systems January 26, 2024
C. Protect conduit from corrosion and entrance of debris by storing above grade. Provide appropriate covering.
D. Protect PVC conduit from sunlight.
1.9 PROJECT CONDITIONS
A. Verify that field measurements are as shown on drawings.
B. Verify conduit routing and termination locations of conduits prior to rough in.
C. Conduit routing is shown on drawings in approximate locations unless dimensioned. Route as required to complete wiring systems.
1.10 RATED WALLS AND CEILINGS
A. Inspect architectural plans for locations and fire ratings for all walls, ceilings, and floors. Install materials as required to maintain the fire integrity of the rated assemblies.
PART 2 PRODUCTS
2.1 CONDUIT APPLICATIONS
A. Do not use conduit and associated fittings for applications other than as permitted by NFPA 70, manufacturer's instructions, and product listing.
B. Unless otherwise indicated and where not otherwise restricted, use conduit types indicated for specified applications. Where more than one listed application applies, comply with most restrictive requirements. Where conduit type for particular application is not specified, use galvanized steel rigid metal conduit.
C. Underground:
1. Under Slab on Grade: Use galvanized steel rigid metal conduit, intermediate metal conduit (IMC), PVC-coated galvanized steel rigid metal conduit, or rigid PVC conduit.
2. Exterior, Direct-Buried: Use galvanized steel rigid metal conduit, intermediate metallic conduit (IMC), PVC-coated galvanized steel rigid metal conduit, or rigid PVC conduit.
3. Exterior, Embedded Within Concrete: Use galvanized steel rigid metal conduit, intermediate metallic conduit (IMC), PVC-coated galvanized steel rigid metal conduit, or rigid PVC conduit.
Lionakis No. 019124.02 26 05 33.13
January 26, 2024 Conduit for Electrical Systems
4. Where rigid polyvinyl (PVC) conduit is provided, transition to galvanized steel rigid metal conduit or PVC-coated galvanized steel rigid metal conduit where emerging from underground.
5. Where rigid polyvinyl (PVC) conduit larger than 2 inch (53 mm) trade size is provided, use galvanized steel rigid metal conduit elbows or PVC- coated galvanized steel rigid metal conduit elbows for bends.
6. Where galvanized rigid metal conduit (RMC), galvanized steel intermediate metal conduit (IMC), or galvanized steel electrical metallic tubing (EMT) emerges from concrete into soil, use corrosion protection tape, factory-applied corrosion protection coating, or field-applied corrosion protection compound acceptable to authorities having jurisdiction to provide supplementary corrosion protection for minimum of 4 inches on either side of where conduit emerges.
D. Embedded Within Concrete:
1. Within Slab on Grade: Use galvanized steel rigid metal conduit (RMC), stainless steel rigid metal conduit (RMC), galvanized steel intermediate metal conduit (IMC), stainless steel intermediate metal conduit (IMC), PVC-coated galvanized steel rigid metal conduit (RMC), galvanized steel electrical metallic tubing (EMT), rigid PVC conduit, or reinforced thermosetting resin conduit (RTRC). Embed within structural slabs only where approved by Structural Engineer.
2. Within Slab Above Ground: Use galvanized steel rigid metal conduit (RMC), stainless steel rigid metal conduit (RMC), galvanized steel intermediate metal conduit (IMC), stainless steel intermediate metal conduit (IMC), PVC-coated galvanized steel rigid metal conduit (RMC), galvanized steel electrical metallic tubing (EMT), rigid PVC conduit, or reinforced thermosetting resin conduit (RTRC). Embed within structural slabs only where approved by Structural Engineer.
3. Within Concrete Walls Above Ground: Use galvanized steel rigid metal conduit, intermediate metal conduit (IMC), PVC-coated galvanized steel rigid metal conduit, or rigid PVC conduit.
4. Where rigid polyvinyl (PVC) conduit is provided, transition to galvanized steel rigid metal conduit or PVC-coated galvanized steel rigid metal conduit where emerging from concrete.
26 05 33.13 Lionakis No. 019124.02
Conduit for Electrical Systems January 26, 2024
5. Where galvanized steel electrical metallic tubing (EMT) emerges from concrete into salt air, use corrosion protection tape, factory-applied corrosion protection coating, or field-applied corrosion protection compound acceptable to authorities having jurisdiction to provide supplementary corrosion protection for minimum of 4 inches on either side of where conduit emerges.
E. Concealed Within Masonry Walls: Use galvanized steel rigid metal conduit (RMC), stainless steel rigid metal conduit (RMC), galvanized steel intermediate metal conduit (IMC), stainless steel intermediate metal conduit (IMC), galvanized steel electrical metallic tubing (EMT), or stainless steel electrical metallic tubing (EMT).
F. Concealed Within Hollow Stud Walls: Use galvanized steel rigid metal conduit (RMC), stainless steel rigid metal conduit (RMC), galvanized steel intermediate metal conduit (IMC), stainless steel intermediate metal conduit (IMC), galvanized steel electrical metallic tubing (EMT), or stainless steel electrical metallic tubing (EMT).
G. Concealed Above Accessible Ceilings: Use galvanized steel rigid metal conduit (RMC), stainless steel rigid metal conduit (RMC), galvanized steel intermediate metal conduit (IMC), stainless steel intermediate metal conduit (IMC), galvanized steel electrical metallic tubing (EMT), or stainless steel electrical metallic tubing (EMT).
H. Interior, Damp or Wet Locations: Use galvanized steel rigid metal conduit (RMC), stainless steel rigid metal conduit (RMC), galvanized steel intermediate metal conduit (IMC), stainless steel intermediate metal conduit (IMC), galvanized steel electrical metallic tubing (EMT), or stainless steel electrical metallic tubing (EMT).
I. Exposed, Interior, Not Subject to Physical Damage: Use galvanized steel rigid metal conduit (RMC), stainless steel rigid metal conduit (RMC), galvanized steel intermediate metal conduit (IMC), stainless steel intermediate metal conduit (IMC), galvanized steel electrical metallic tubing (EMT), or stainless steel electrical metallic tubing (EMT).
J. Exposed, Interior, Subject to Physical Damage: Use galvanized steel rigid metal conduit (RMC), stainless steel rigid metal conduit (RMC), galvanized steel intermediate metal conduit (IMC), stainless steel intermediate metal conduit (IMC), galvanized steel electrical metallic tubing (EMT), or stainless steel electrical metallic tubing (EMT).
1. Locations subject to physical damage include, but are not limited to:
Lionakis No. 019124.02 26 05 33.13
January 26, 2024 Conduit for Electrical Systems
a. Where exposed below 8 feet, except within electrical and communication rooms or closets.
b. Where exposed below 20 feet in warehouse areas.
c. In Correctional Facilities, Galvanized rigid steel only for inmate accessible areas. Locations shall be verified with the architect.
K. Exposed, Exterior, Not Subject to Severe Physical Damage: Use galvanized steel rigid metal conduit (RMC), stainless steel rigid metal conduit (RMC), galvanized steel intermediate metal conduit (IMC), stainless steel intermediate metal conduit (IMC), galvanized steel electrical metallic tubing (EMT), or stainless steel electrical metallic tubing (EMT).
L. Concealed, Exterior, Not Embedded in Concrete or in Contact With Earth: Use galvanized steel rigid metal conduit (RMC), stainless steel rigid metal conduit (RMC), galvanized steel intermediate metal conduit (IMC), stainless steel intermediate metal conduit (IMC), galvanized steel electrical metallic tubing (EMT), or stainless steel electrical metallic tubing (EMT).
M. Corrosive Locations Above Ground: Use PVC-coated galvanized steel rigid metal conduit.
N. Hazardous/Classified Locations: Use galvanized steel rigid metal conduit (RMC), stainless steel rigid metal conduit (RMC), galvanized steel intermediate metal conduit (IMC), stainless steel intermediate metal conduit (IMC), or PVC-coated galvanized steel rigid metal conduit (RMC).
O. Flexible Connections to Luminaires Above Accessible Ceilings: Use flexible metal conduit (FMC).
1. Maximum Length: 6 feet.
P. Flexible Connections to Vibrating Equipment:
1. Dry Locations: Use flexible metal conduit (FMC).
2. Damp, Wet, or Corrosive Locations: Use liquidtight flexible metal conduit (LFMC).
3. Maximum Length: 6 feet unless otherwise indicated.
4. Vibrating equipment includes, but is not limited to:
a. Transformers.
b. Motors.
26 05 33.13 Lionakis No. 019124.02
Conduit for Electrical Systems January 26, 2024
c. Engine generators.
Q. Fished in Existing Walls, Where Necessary: Use flexible metal conduit.
R. Freezer and Refrigeration Rooms
1. Galvanized rigid steel conduit.
2. Use sealing fittings on refrigeration and freezer room conduit runs in accordance with CEC 300-7(a).
2.2 CONDUIT - GENERAL REQUIREMENTS
A. Comply with NFPA 70.
B. Existing Work: Where existing conduits are indicated to be reused, they may be reused only where they comply with specified requirements, are free from corrosion, and integrity is verified by pulling mandrel through them.
C. Electrical Service Conduits: See Section 26 21 00 for additional requirements.
D. Fittings for Grounding and Bonding: See Section 26 05 26 for additional requirements.
E. Provide conduit, fittings, supports, and accessories required for complete raceway system.
F. Provide products listed, classified, and labeled as suitable for purpose intended.
G. Minimum Conduit Size, Unless Otherwise Indicated:
1. Branch Circuits: 1/2-inch trade size.
2. Branch Circuit Homeruns: 3/4-inch trade size.
3. Control Circuits: 1/2-inch trade size.
4. Flexible Connections to Luminaires: 1/2 inch (16 mm) trade size.
5. Underground, Interior: 1 inch (27 mm) trade size.
6. Underground, Exterior: 1-inch trade size.
H. Where conduit size is not indicated, size to comply with NFPA 70 but not less than applicable minimum size requirements specified.
Lionakis No. 019124.02 26 05 33.13
January 26, 2024 Conduit for Electrical Systems
2.3 GALVANIZED STEEL RIGID METAL CONDUIT (RMC)
A. Manufacturers:
1. Allied Tube & Conduit, a division of Atkore International : www.alliedeg.com/#sle.
2. Nucor Tubular Products: www.nucortubular.com/#sle.
3. Rymco USA: www.rymcousa.com/#sle.
4. Western Tube, a division of Zekelman
Industries: www.westerntube.com/#sle.
5. Wheatland Tube, a division of Zekelman
Industries: www.wheatland.com/#sle.
6. Or approved equal.
7. Substitutions: See Section 01 60 00 - Product Requirements.
B. Description: NFPA 70, Type RMC galvanized steel rigid metal conduit complying with ANSI C80.1 and listed and labeled as complying with UL 6.
C. Fittings:
1. Manufacturers:
a. Bridgeport Fittings Inc: www.bptfittings.com/#sle.
b. Appleton.
c. Crouse-Hinds.
d. Emerson Electric Co; O-Z/Gedney: www.emerson.com/#sle. e. Or approved equal.
f. Substitutions: See Section 01 60 00 - Product Requirements.
2. Nonhazardous Locations: Use fittings complying with NEMA FB 1 and listed and labeled as complying with UL 514B or UL 6.
3. Hazardous/Classified Locations: Use fittings listed and labeled as complying with UL 1203 for classification of installed location.
4. Material: Use steel or malleable iron.
a. Do not use die cast zinc fittings.
26 05 33.13 Lionakis No. 019124.02
Conduit for Electrical Systems January 26, 2024
5. Connectors and Couplings: Where an expansion type fitting is not required, use a coupling or “Erickson” type coupling as appropriate.
Threadless set screw and compression (gland) type fittings are not permitted.
6. At building expansion joints, use expansion type fittings.
7. Make connections to NEMA 12 boxes with a threaded hub.
D. Locknuts
1. Hardened Steel or malleable iron construction, electro zinc plated, capable of insuring positive bond to enclosure.
a. Non-bonding: T & B Series 142 or approved equal.
b. Bonding: T & B Series 107 or approved equal.
E. Bushings
1. Insulted: T & B Series 223 or approved equal.
2. Insulated Metallic Bushing: T & B Series 1223 or approved equal.
3. Insulated Grounding and Bonding Bushing: T & B Series 3871 or approved equal.
F. Couplings
1. Non-metallic Conduit Coupling: By non-metallic conduit manufacturer for the application.
2. Threaded Rigid Metal Conduit Couplings: By conduit manufacturer for the application.
3. Threadless Coupling: “Erickson” Type Y & B Series 676 or approved equal.
4. Expansion Type: Permit ¾ inch movement any direction. a. Exposed: Weatherproof with external bonding jumper.
b. Embedded: Watertight with internal bonding jumper.
G. Connectors
1. Non-Metallic Conduit Connector: By conduit manufacturer for the application.
Lionakis No. 019124.02 26 05 33.13
January 26, 2024 Conduit for Electrical Systems
2. Threaded Hubs: Electro zinc coated with nylon insulated throat and ail/moisture resistant recessed sealing ring, raintight. a. Non-bonding: T & B Series 371 or approved equal.
b. Bonding: T & B Series 371 with 107 series bonding locknut or approved equals.
H. Nipple: “Chase” Type, insulated: T & B Series 5263 or approved equal.
I. Sealing Gaskets: Oil and moisture resistant rubber bonded to metallic retainer.
1. With rigid conduit – T & B Series 5303 or approved equal.
2. Fittings not specifically listed but required shall be of similar style and quality.
2.4 GALVANIZED STEEL INTERMEDIATE METAL CONDUIT (IMC)
A. Manufacturers:
1. Allied Tube & Conduit, a division of Atkore
International: www.alliedeg.com/#sle.
2. Nucor Tubular Products: www.nucortubular.com/#sle.
3. Western Tube, a division of Zekelman
Industries: www.westerntube.com/#sle.
4. Wheatland Tube, a division of Zekelman
Industries: www.wheatland.com/#sle.
5. Or approved equal.
6. Substitutions: See Section 01 60 00 - Product Requirements.
B. Description: NFPA 70, Type IMC galvanized steel intermediate metal conduit complying with ANSI C80.6 and listed and labeled as complying with UL 1242.
C. Fittings:
1. Manufacturers:
a. Bridgeport Fittings, LLC: www.bptfittings.com/#sle. b. Emerson Electric Co; O-Z/Gedney: www.emerson.com/#sle. 26 05 33.13 Lionakis No. 019124.02
Conduit for Electrical Systems January 26, 2024
c. Or approved equal.
d. Substitutions: See Section 01 60 00 - Product Requirements.
2. Nonhazardous Locations: Use fittings complying with NEMA FB 1 and listed and labeled as complying with UL 514B or UL 1242.
3. Hazardous/Classified Locations: Use fittings listed and labeled as complying with UL 1203 for classification of installed location.
4. Material: Use steel or malleable iron.
a. Do not use die cast zinc fittings.
5. Connectors and Couplings: Use threaded type fittings only. Threadless fittings, including set screw and compression/gland types, are not permitted.
D. Conduit Size: Comply with NFPA 70.
1. Exposed: Use rigid steel conduit or intermediate metal conduit for installation up to 8 feet.
2.5 FLEXIBLE METAL CONDUIT (FMC)
A. Manufacturers:
1. AFC Cable Systems, Inc: www.afcweb.com/#sle.
2. Electri-Flex Company: www.electriflex.com/#sle.
3. International Metal Hose: www.metalhose.com/#sle.
4. Or approved equal.
5. Substitutions: See Section 01 60 00 - Product Requirements.
B. Description: NFPA 70, Type FMC standard-wall steel flexible metal conduit listed and labeled as complying with UL 1, and listed for use in classified firestop systems.
C. Fittings:
1. Manufacturers:
a. ABB; T&B: www.electrification.us.abb.com/#sle.
b. Bridgeport Fittings, LLC: www.bptfittings.com/#sle.
Lionakis No. 019124.02 26 05 33.13
January 26, 2024 Conduit for Electrical Systems
c. Emerson Electric Co; O-Z/Gedney: www.emerson.com/#sle. d. Or approved equal.
e. Substitutions: See Section 01 60 00 - Product Requirements.
2. Description: Fittings complying with NEMA FB 1 and listed and labeled as complying with UL 514B.
3. Material: Use steel or malleable iron.
a. Do not use die cast zinc fittings.
D. Description: Interlocked steel construction.
E. Connectors and Fittings: NEMA FB 1.
1. Flexible metal conduit connector – Insulated throat, suitable as grounding means: T & B Serries 3115.
2.6 LIQUIDTIGHT FLEXIBLE METAL CONDUIT (LFMC)
A. Manufacturers:
1. AFC Cable Systems, Inc: www.afcweb.com/#sle.
2. Electri-Flex Company: www.electriflex.com/#sle.
3. International Metal Hose: www.metalhose.com/#sle.
4. Or approved equal.
5. Substitutions: See Section 01 60 00 - Product Requirements.
B. Description: NFPA 70, Type LFMC polyvinyl chloride (PVC) jacketed steel flexible metal conduit listed and labeled as complying with UL 360.
C. Fittings:
1. Manufacturers:
a. ABB; T&B: www.electrification.us.abb.com/#sle.
b. Bridgeport Fittings, LLC: www.bptfittings.com/#sle. c. Emerson Electric Co; O-Z/Gedney: www.emerson.com/#sle. d. Or approved equal.
e. Substitutions: See Section 01 60 00 - Product Requirements. 26 05 33.13 Lionakis No. 019124.02
Conduit for Electrical Systems January 26, 2024
2. Description: Fittings complying with NEMA FB 1 and listed and labeled as complying with UL 514B.
3. Material: Use steel or malleable iron.
a. Do not use die cast zinc fittings.
D. Description: Interlocked steel construction with PVC jacket.
E. Fittings: NEMA FB 1.
2.7 GALVANIZED STEEL ELECTRICAL METALLIC TUBING (EMT)
A. Manufacturers:
1. Allied Tube & Conduit: www.alliedeg.com/#sle.
2. Nucor Tubular Products: www.nucortubular/#sle.
3. Rymco USA: www.rymcousa.com/#sle.
4. Western Tube, a division of Zekelman
Industries: www.westerntube.com/#sle.
5. Beck Manufacturing, Inc: www.beckmfg.com.
6. Wheatland Tube Company: www.wheatland.com/#sle.
7. Or Equal.
8. Substitutions: See Section 01 60 00 - Product Requirements.
B. Description: NFPA 70, Type EMT galvanized steel electrical metallic tubing complying with ANSI C80.3 and listed and labeled as complying with UL 797.
C. Fittings:
1. Manufacturers:
a. Bridgeport Fittings, LLC: www.bptfittings.com/#sle. b. Emerson Electric Co; O-Z/Gedney: www.emerson.com/#sle. c. Or approved equal.
d. Substitutions: See Section 01 60 00 - Product Requirements.
2. Description: Fittings complying with NEMA FB 1 and listed and labeled as complying with UL 514B.
Lionakis No. 019124.02 26 05 33.13
January 26, 2024 Conduit for Electrical Systems
3. Material: Use steel or malleable iron.
a. Do not use die cast zinc fittings.
4. Connectors and Couplings: Use compression/gland type. a. Do not use indenter type connectors and couplings.
b. Do not use set-screw type connectors and couplings.
c. EMT Coupling: Raintight T & B Series 5220 or approved equal. d. EMT to Rigid Metal Conduit Connector, Raintight: T & B Series 531 or approved equal.
5. Damp or Wet Locations, Where Permitted: Use fittings listed for use in wet locations.
6. Embedded Within Concrete, Where Permitted: Use fittings listed as concrete-tight. Fittings that require taping to be concrete-tight are acceptable.
D. Description: ANSI C80.3; galvanized tubing.
E. Fittings and Conduit Bodies: NEMA FB 1; steel or malleable iron compression type.
2.8 RIGID POLYVINYL CHLORIDE (PVC) CONDUIT
A. Manufacturers:
1. Cantex Inc: www.cantexinc.com/#sle.
2. JM Eagle: www.jmeagle.com/#sle.
3. Or approved equal.
4. Substitutions: See Section 01 60 00 - Product Requirements.
B. Description: NFPA 70, Type PVC rigid polyvinyl chloride conduit complying with NEMA TC 2 and listed and labeled as complying with UL 651; Schedule 40 unless otherwise indicated, Schedule 80 where subject to physical damage; rated for use with conductors rated 90 degrees C.
C. Fittings:
1. Manufacturer: Same as manufacturer of conduit to be connected. 26 05 33.13 Lionakis No. 019124.02
Conduit for Electrical Systems January 26, 2024
2. Description: Fittings complying with NEMA TC 3 and listed and labeled as complying with UL 651; material to match conduit.
2.9 REINFORCED THERMOSETTING RESIN CONDUIT (RTRC)
A. Manufacturers:
1. Champion Fiberglass, Inc: www.championfiberglass.com/#sle.
2. FRE Composites: www.frecompositesinc.com/#sle.
3. United Fiberglass of America, Inc: www.unitedfiberglass.com/#sle.
4. Or approved equal.
5. Substitutions: See Section 01 60 00 - Product Requirements.
B. Applications:
1. Above Ground, Not Subject to Physical Damage: Use aboveground (AG), SW (Standard Wall), HW (Heavy Wall), or XW (Extra Heavy Wall) RTRC.
2. Above Ground, Subject to Physical Damage: Use aboveground (AG), XW (Extra Heavy Wall) RTRC.
3. Underground, Direct-Buried: Use belowground (BG), DB (direct-burial) RTRC or aboveground (AG) RTRC.
4. Underground, Embedded in Concrete: Use belowground (BG), EB (encased-burial) RTRC, belowground (BG), DB (direct-burial) RTRC, or aboveground (AG) RTRC.
5. Do not use RTRC in hazardous/classified locations.
C. Description: NFPA 70, Type RTRC reinforced thermosetting resin conduit complying with NEMA TC 14 (SERIES).
1. Aboveground (AG) RTRC: Comply with NEMA TC 14.AG and list and label as complying with UL 2515.
2. Aboveground (AG), XW (Extra Heavy Wall) RTRC: Comply with NEMA TC 14.XW and list and label as complying with UL 2515A.
3. Belowground (BG) RTRC: Comply with NEMA TC 14.BG and list and label as complying with UL 2420.
D. Supports: As recommended by manufacturer.
Lionakis No. 019124.02 26 05 33.13
January 26, 2024 Conduit for Electrical Systems
E. Fittings: Same type and manufacturer as conduit to be connected.
1. Cement-Tight Joints: Use bonded coupling or bell and spigot.
2. Cement-Tight and Watertight Joints: Use adhesive and manufacturer's standard gaskets.
2.10 ACCESSORIES
A. Corrosion Protection Tape: PVC-based, minimum thickness of 20 mil, 0.020 inch.
B. Conduit Joint Compound: Corrosion-resistant, electrically conductive compound listed as complying with UL 2419; suitable for use with conduit to be installed.
C. Solvent Cement for PVC Conduit and Fittings: As recommended by manufacturer of conduit and fittings to be installed.
D. Epoxy Adhesive for RTRC Conduit and Fittings: As recommended by manufacturer of conduit and fittings to be installed.
E. Pull Strings: Use nylon or polyester tape with average breaking strength of not less than 1,250 lbf.
F. Sealing Compound for Sealing Fittings: Listed for use with the particular fittings to be installed.
1. Internal to fittings
a. Approved by manufacturer for application.
2. Manufacturer
a. Crouse-Hinds Chico A-P and Chico X fiber.
b. O.Z. Gedney.
c. Or approved equal.
G. Sealing Systems for Concrete Penetrations:
1. Sleeves: Provide water stop ring or cement coating that bonds to concrete to prevent water infiltration.
2. Rate for minimum of 40 psig; suitable for sealing around conduits to be installed.
26 05 33.13 Lionakis No. 019124.02
Conduit for Electrical Systems January 26, 2024
H. Sealing Systems for Roof Penetrations: Premanufactured components and accessories as required to preserve integrity of roofing system and maintain roof warranty; suitable for conduits and roofing system to be installed; designed to accommodate existing penetrations where applicable.
1. Products:
a. Menzies Metal Products; Electrical Roof Stack and
Cap: www.menzies-metal.com/#sle.
b. Menzies Metal Products; Electrical Retro Box: www.menzies- metal.com/#sle.
c. Or approved equal.
d. Substitutions: See Section 01 60 00 - Product Requirements.
I. Flashing Panels for Exterior Wall Penetrations: Premanufactured components and accessories as required to preserve integrity of building envelope; suitable for conduits and facade materials to be installed.
1. Products:
a. Quickflash Weatherproofing Products,
Inc: www.quickflashproducts.com/#sle.
b. Or approved equal.
c. Substitutions: See Section 01 60 00 - Product Requirements.
J. Firestop Sleeves: Listed; provide as required to preserve fire resistance rating of building elements.
1. Products:
a. HoldRite, a brand of Reliance Worldwide Corporation; HydroFlame Pro Series/HydroFlame Custom Built: www.holdrite.com/#sle. b. Or approved equal.
c. Substitutions: See Section 01 60 00 - Product Requirements.
K. Duct Bank Spacers: Nonmetallic; designed for maintaining conduit/duct spacing for concrete encasement in open trench installation; suitable for conduit/duct arrangement to be installed.
1. Products:
Lionakis No. 019124.02 26 05 33.13
January 26, 2024 Conduit for Electrical Systems
a. Advance Products & Systems, LLC; Duct Bank
Spacers: www.apsonline.com/#sle.
b. Or approved equal.
c. Substitutions: See Section 01 60 00 - Product Requirements.
L. Bore Spacers: Nonmetallic; designed for maintaining conduit/duct spacing for installation within casing; furnished with roller wheels to facilitate installation, openings to facilitate grout flow, and holes for stabilization cable; suitable for casing and conduit/duct arrangement to be installed.
1. Products:
a. Advance Products & Systems, LLC; Bore
Spacers: www.apsonline.com/#sle.
b. Or approved equal.
c. Substitutions: See Section 01 60 00 - Product Requirements.
PART 3 EXECUTION
3.1 EXAMINATION
A. Verify that field measurements are as indicated.
B. Verify that mounting surfaces are ready to receive conduits.
C. Verify that conditions are satisfactory for installation prior to starting work.
D. Verify routing and termination locations of conduit prior to rough-in.
E. Conduit routing is shown on drawings in approximate locations unless dimensioned. Route as required to complete wiring system.
3.2 INSTALLATION
A. Install products in accordance with manufacturer's instructions.
B. Install conduit in accordance with NECA 1.
C. Install galvanized steel rigid metal conduit (RMC) in accordance with NECA 101.
D. Install aluminum rigid metal conduit (RMC) in accordance with NECA 102.
E. Install intermediate metal conduit (IMC) in accordance with NECA 101. 26 05 33.13 Lionakis No. 019124.02
Conduit for Electrical Systems January 26, 2024
F. Install PVC-coated galvanized steel rigid metal conduit (RMC) using only tools approved by manufacturer.
G. Install rigid polyvinyl chloride (PVC) conduit in accordance with NECA 111.
H. Install liquidtight flexible nonmetallic conduit (LFNC) in accordance with NECA 111.
I. Conduit Routing:
1. Unless dimensioned, conduit routing indicated is diagrammatic.
2. When conduit destination is indicated without specific routing, determine exact routing required.
3. Conceal conduits unless specifically indicated to be exposed.
4. Conduits in the following areas may be exposed, unless otherwise indicated:
a. Electrical rooms.
b. Mechanical equipment rooms.
c. Within joists in areas with no ceiling.
5. Unless otherwise approved, do not route exposed conduits:
a. Across floors.
b. Across roofs.
c. Across top of parapet walls.
d. Across building exterior surfaces.
6. Conduits installed underground or embedded in concrete may be routed in shortest possible manner unless otherwise indicated. Route other conduits parallel or perpendicular to building structure and surfaces, following surface contours where practical.
7. Arrange conduit to maintain adequate headroom, clearances, and access.
8. Arrange conduit to provide no more than equivalent of four 90-degree bends between pull points.
9. Arrange conduit to provide no more than 150 feet between pull points.
Lionakis No. 019124.02 26 05 33.13
January 26, 2024 Conduit for Electrical Systems
10. Route conduits above water and drain piping where possible.
11. Arrange conduit to prevent moisture traps. Provide drain fittings at low points and at sealing fittings where moisture may collect.
12. Maintain minimum clearance of 6 inches between conduits and piping for other systems.
13. Maintain minimum clearance of 12 inches between conduits and hot surfaces. This includes, but is not limited to:
a. Heaters.
b. Hot water piping.
c. Flues.
14. Group parallel conduits in same area on common rack.
J. Conduit Support:
1. Secure and support conduits in accordance with NFPA 70 using suitable supports and methods approved by authorities having jurisdiction; see Section 26 05 29.
2. Provide required vibration isolation and/or seismic controls; see Section 26 05 48.
3. Provide independent support from building structure. Do not provide support from piping, ductwork, or other systems.
4. Installation Above Suspended Ceilings: Do not provide support from ceiling support system. Do not provide support from ceiling grid or allow conduits to lay on ceiling tiles.
5. Use conduit strap to support single surface-mounted conduit. a. Use clamp back spacer with conduit strap for damp and wet locations to provide space between conduit and mounting surface.
6. Use metal channel/strut with accessory conduit clamps to support multiple parallel surface-mounted conduits.
7. Use conduit clamp to support single conduit from beam clamp or threaded rod.
26 05 33.13 Lionakis No. 019124.02
Conduit for Electrical Systems January 26, 2024
8. Use trapeze hangers assembled from threaded rods and metal channel/strut with accessory conduit clamps to support multiple parallel suspended conduits.
9. Use nonpenetrating rooftop supports to support conduits routed across rooftops, where approved.
10. Use of spring steel conduit clips for support of conduits is not permitted. a. Support of electrical metallic tubing (EMT) up to 1-inch (27 mm) trade size concealed above accessible ceilings and within hollow stud walls.
11. Use of wire for support of conduits is not permitted. a. For securing conduits to studs in hollow stud walls. b. For suspending conduits supported by spring steel conduit clips, where specifically indicated or permitted.
12. Where conduit support intervals specified in NFPA 70 and NECA standards differ, comply with most stringent requirements.
K. Connections and Terminations:
1. Use approved zinc-rich paint or conduit joint compound on field-cut threads of galvanized steel conduits prior to making connections.
2. Where two threaded conduits must be joined and neither can be rotated, use three-piece couplings or split couplings. Do not use running threads.
3. Use suitable adapters where required to transition from one type of conduit to another.
4. Provide drip loops for liquidtight flexible conduit connections to prevent drainage of liquid into connectors.
5. Terminate threaded conduits in boxes and enclosures using threaded hubs or double lock nuts for dry locations and raintight hubs for wet locations.
6. Where spare conduits stub up through concrete floors and are not terminated in box or enclosure, provide threaded couplings equipped with threaded plugs set flush with finished floor.
7. Provide insulating bushings, insulated throats, or listed metal fittings with smooth, rounded edges at conduit terminations to protect conductors.
Lionakis No. 019124.02 26 05 33.13
January 26, 2024 Conduit for Electrical Systems
8. Secure joints and connections to provide mechanical strength and electrical continuity.
L. Penetrations:
1. Do not penetrate or otherwise notch or cut structural members, including footings and grade beams, without approval of Structural Engineer.
2. Make penetrations perpendicular to surfaces unless otherwise indicated.
3. Provide sleeves for penetrations as indicated or as required to facilitate installation. Set sleeves flush with exposed surfaces unless otherwise indicated or required.
4. Conceal bends for conduit risers emerging above ground.
5. Provide suitable sealing system where conduits penetrate exterior wall below grade.
6. Where conduits penetrate waterproof membrane, seal as required to maintain integrity of membrane.
7. Make penetrations for roof-mounted equipment within associated equipment openings and curbs where possible to minimize roofing system penetrations. Where penetrations are necessary, seal as indicated or as required to preserve integrity of roofing system and maintain roof warranty.
8. Provide metal escutcheon plates for conduit penetrations exposed to public view.
9. Install firestopping to preserve fire resistance rating of partitions and other elements; see Section 07 84 00.
M. Underground Installation:
1. Provide trenching and backfilling; see Section 31 23 16 and Section 31 23
23. 2. Minimum Cover, Unless Otherwise Indicated or Required:
a. Underground, Exterior: 18 inches.
b. Under Slab on Grade: 12 inches to bottom of slab.
3. Provide underground warning tape along entire conduit length for service entrance where not concrete-encased; see Section 26 05 53. 26 05 33.13 Lionakis No. 019124.02
Conduit for Electrical Systems January 26, 2024
N. Embedment Within Structural Concrete Slabs (only where approved by Structural Engineer):
1. Maximum Conduit Size: 1-inch trade size unless otherwise approved.
2. Minimum Conduit Spacing: As indicated on drawings.
3. Install conduits within middle one third of slab thickness.
4. Secure conduits to prevent floating or movement during pouring of concrete.
O. Concrete Encasement: Where conduits not otherwise embedded within concrete are indicated to be concrete-encased, provide minimum concrete cover of 3 inches on all sides unless otherwise indicated; see Section 03 30
00. P. Conduit Movement Provisions: Where conduits are subject to movement, provide expansion and expansion/deflection fittings to prevent damage to enclosed conductors or connected equipment. This includes, but is not limited to:
1. Where conduits cross structural joints intended for expansion, contraction, or deflection.
2. Where calculated in accordance with NFPA 70 for rigid polyvinyl chloride (PVC) conduit installed above ground to compensate for thermal expansion and contraction.
3. Where calculated in accordance with NFPA 70 for reinforced thermosetting resin conduit (RTRC) conduit installed above ground to compensate for thermal expansion and contraction.
4. Where conduits are subject to earth movement by settlement or frost.
Q. Conduit Sealing:
1. Use foam conduit sealant to prevent entry of moisture and gases. This includes, but is not limited to:
a. Where conduits enter building from outside.
b. Where service conduits enter building from underground distribution system.
c. Where conduits enter building from underground.
d. Where conduits may transport moisture to contact live parts.
Lionakis No. 019124.02 26 05 33.13
January 26, 2024 Conduit for Electrical Systems
2. Where conduits cross barriers between areas of potential substantial temperature differential, use foam conduit sealant at accessible point near penetration to prevent condensation. This includes, but is not limited to:
a. Where conduits pass from outdoors into conditioned interior spaces. b. Where conduits pass from unconditioned interior spaces into conditioned interior spaces.
R. Provide pull string in each empty conduit and in conduits where conductors and cables are to be installed by others. Leave minimum slack of 12 inches at each end.
S. Provide grounding and bonding; see Section 26 05 26.
T. Identify conduits; see Section 26 05 53.
3.3 FIELD QUALITY CONTROL
A. See Section 01 40 00 - Quality Requirements for additional requirements.
B. Repair cuts and abrasions in galvanized finishes using zinc-rich paint recommended by manufacturer. Replace components that exhibit signs of corrosion.
C. Where coating of PVC-coated galvanized steel rigid metal conduit (RMC) contains cuts or abrasions, repair in accordance with manufacturer's instructions.
D. Correct deficiencies and replace damaged or defective conduits.
3.4 EMPTY CONDUITS
A. Certain conduits will have no conductors pulled in as a part of this contract.
Identify with tags at each end of the origin and destination of each such empty conduits. Provide a permanent cap over each end of each empty conduit. Provide a nylon pull wire in each empty conduit, tie off at both ends.
3.5 TESTING AND INSPECTION
A. So not cover up conduit work until inspected. Notify the Owner’s Representative at least 3 days before desired inspection date.
3.6 CLEANING
A. Clean interior of conduits to remove moisture and foreign matter. 26 05 33.13 Lionakis No. 019124.02
Conduit for Electrical Systems January 26, 2024
3.7 PROTECTION
A. Immediately after installation of conduit, use suitable manufactured plugs to provide protection from entry of moisture and foreign material and do not remove until ready for installation of conductors.
B. All conduits shall be run concealed in walls and/or ceiling. Where conduits can not be run concealed in wall and/or ceiling space, the Contractor shall coordinate with the architectural and structural plans and the Architect for installing and routing of exposed conduits.
3.8 INTERFACE WITH OTHER PRODUCTS
A. Install conduit to preserve fire resistance rating of partitions and other elements, using materials and methods specified in Section 07 8400.
END OF SECTION 26 05 33.13
Lionakis No. 019124.02 26 05 33.16
January 26, 2024 Boxes for Electrical Systems
SECTION 26 05 33.16 - BOXES FOR ELECTRICAL SYSTEMS
PART 1 GENERAL
1.1 SUMMARY
A. Scope: Provide boxes, pull boxes, racks, and enclosures as shown on drawings or as required by code(s).
B. Section Includes:
1. Boxes and enclosures for integrated power, data, and audio/video.
2. Boxes for hazardous (classified) locations.
3. Floor boxes.
4. Underground boxes/enclosures.
5. Accessories.
6. Wall and ceiling outlet boxes.
7. Floor boxes.
8. Pull and junction boxes.
1.2 RELATED REQUIREMENTS
A. Section 03 30 00 - Cast-in-Place Concrete.
B. Section 07 84 00 - Firestopping.
C. Section 08 31 00 - Access Doors and Panels: Panels for maintaining access to concealed boxes.
D. Section 26 05 26 - Grounding and Bonding for Electrical Systems.
E. Section 26 05 29 - Hangers and Supports for Electrical Systems.
F. Section 26 05 33.13 - Conduit for Electrical Systems:
1. Conduit bodies and other fittings.
2. Additional requirements for locating boxes to limit conduit length and/or number of bends between pulling points.
G. Section 26 05 33.23 - Surface Raceways for Electrical Systems:
26 05 33.16 Lionakis No. 019124.02
Boxes for Electrical Systems January 26, 2024
1. Accessory boxes designed specifically for surface raceway systems.
2. Lay-in wireways and wiring troughs with removable covers.
H. Section 26 05 48 - Vibration and Seismic Controls for Electrical Systems.
I. Section 26 05 53 - Identification for Electrical Systems: Identification products and requirements.
J. Section 26 27 26 - Wiring Devices:
1. Wall plates.
2. Floor box service fittings.
3. Poke-through assemblies.
4. Access floor boxes.
5. Additional requirements for locating boxes for wiring devices.
K. Section 26 28 13 - Fuses: Spare fuse cabinets.
L. Section 27 10 00 - Structured Cabling: Additional requirements for communications systems outlet boxes.
M. Section 33 71 19 - Electrical Underground Ducts, Ductbanks, and Manholes: Concrete manholes for electrical systems.
N. The requirements of the kitchen equipment consultan plans and specifications.
1.3 REFERENCE STANDARDS
A. NECA 1 - Standard for Good Workmanship in Electrical Construction; 2015.
B. NECA 130 - Standard for Installing and Maintaining Wiring Devices; 2016.
C. NEMA 250 - Enclosures for Electrical Equipment (1000 Volts Maximum); 2020.
D. NEMA FB 1 - Fittings, Cast Metal Boxes, and Conduit Bodies for Conduit, Electrical Metallic Tubing, and Cable; 2014.
E. NEMA OS 1 - Sheet-Steel Outlet Boxes, Device Boxes, Covers, and Box Supports; 2013 (Reaffirmed 2020).
Lionakis No. 019124.02 26 05 33.16
January 26, 2024 Boxes for Electrical Systems
F. NEMA OS 2 - Nonmetallic Outlet Boxes, Device Boxes, Covers and Box Supports; 2013 (Reaffirmed 2020).
G. NEMA 250 - Enclosures for Electrical Equipment (1000 Volts Maximum); 2020.
H. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.
I. SCTE 77 - Specifications for Underground Enclosure Integrity; 2023.
J. UL 50 - Enclosures for Electrical Equipment, Non-Environmental Considerations; Current Edition, Including All Revisions.
K. UL 50E - Enclosures for Electrical Equipment, Environmental Considerations; Current Edition, Including All Revisions.
L. UL 508A - Industrial Control Panels; Current Edition, Including All Revisions.
M. UL 514A - Metallic Outlet Boxes; Current Edition, Including All Revisions.
N. UL 514C - Nonmetallic Outlet Boxes, Flush-Device Boxes, and Covers; Current Edition, Including All Revisions.
O. UL 1203 - Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use in Hazardous (Classified) Locations; Current Edition, Including All Revisions.
1.4 ADMINISTRATIVE REQUIREMENTS
A. Coordination:
1. Coordinate the work with other trades to avoid placement of ductwork, piping, equipment, or other potential obstructions within the dedicated equipment spaces and working clearances for electrical equipment required by NFPA 70.
2. Coordinate arrangement of electrical equipment with the dimensions and clearance requirements of the actual equipment to be installed.
3. Coordinate minimum sizes of boxes with the actual installed arrangement of conductors, clamps, support fittings, and devices, calculated according to NFPA 70.
4. Coordinate minimum sizes of pull boxes with the actual installed arrangement of connected conduits, calculated according to NFPA 70. 26 05 33.16 Lionakis No. 019124.02
Boxes for Electrical Systems January 26, 2024
5. Coordinate the placement of boxes with millwork, furniture, devices, equipment, etc. installed under other sections or by others.
6. Coordinate the work with other trades to preserve insulation integrity.
7. Coordinate the work with other trades to provide walls suitable for installation of flush-mounted boxes where indicated.
8. Notify LP Consulting Engineers, Inc. of any conflicts with or deviations from Contract Documents. Obtain direction before proceeding with work.
1.5 SUBMITTALS
A. See Section 01 30 00 - Administrative Requirements, for submittal procedures.
B. Product Data: Provide manufacturer's standard catalog pages and data sheets for cabinets and enclosures, boxes for hazardous (classified) locations, floor boxes, and underground boxes/enclosures.
1. Underground Boxes/Enclosures: Include reports for load testing in accordance with SCTE 77 certified by a professional engineer or an independent testing agency upon request.
C. Samples:
1. Floor Boxes: Provide one sample(s) of each floor box proposed for substitution upon request.
D. Manufacturer's Installation Instructions: Indicate application conditions and limitations of use stipulated by product testing agency. Include instructions for storage, handling, protection, examination, preparation, and installation of product.
E. Project Record Documents: Record actual locations for outlet and device boxes, pull boxes, cabinets and enclosures, floor boxes, and underground boxes/enclosures.
F. Maintenance Materials: Furnish the following for Owner's use in maintenance of project.
1. See Section 01 60 00 - Product Requirements, for additional provisions.
2. Keys for Lockable Enclosures: Two of each different key.
Lionakis No. 019124.02 26 05 33.16
January 26, 2024 Boxes for Electrical Systems
1.6 QUALITY ASSURANCE
A. Comply with requirements of NFPA 70.
B. Maintain at the project site a copy of each referenced document that prescribes execution requirements.
C. Product Listing Organization Qualifications: An organization recognized by OSHA as a Nationally Recognized Testing Laboratory (NRTL) and acceptable to authorities having jurisdiction.
1.7 DELIVERY, STORAGE, AND HANDLING
A. Receive, inspect, handle, and store products in accordance with manufacturer's instructions.
PART 2 PRODUCTS
2.1 BOXES
A. General Requirements:
1. Do not use boxes and associated accessories for applications other than as permitted by NFPA 70 and product listing.
2. Provide all boxes, fittings, supports, and accessories required for a complete raceway system and to accommodate devices and equipment to be installed.
3. Provide products listed, classified, and labeled as suitable for the purpose intended.
4. Where box size is not indicated, size to comply with NFPA 70 but not less than applicable minimum size requirements specified.
5. Provide grounding terminals within boxes where equipment grounding conductors terminate.
B. Outlet and Device Boxes Up to 100 cubic inches, Including Those Used as Junction and Pull Boxes:
1. Use sheet-steel boxes for dry locations unless otherwise indicated or required.
2. Use cast iron boxes or cast aluminum boxes for damp or wet locations unless otherwise indicated or required; furnish with compatible weatherproof gasketed covers.
26 05 33.16 Lionakis No. 019124.02
Boxes for Electrical Systems January 26, 2024
3. Use cast iron boxes or cast aluminum boxes where exposed galvanized steel rigid metal conduit or exposed intermediate metal conduit (IMC) is used.
4. Use cast aluminum boxes where aluminum rigid metal conduit is used.
5. Use nonmetallic boxes where exposed rigid PVC conduit is used.
6. Use suitable concrete type boxes where flush-mounted in concrete.
7. Use suitable masonry type boxes where flush-mounted in masonry walls.
8. Use raised covers suitable for the type of wall construction and device configuration where required.
9. Use shallow boxes where required by the type of wall construction.
10. Do not use "through-wall" boxes designed for access from both sides of wall.
11. Sheet-Steel Boxes: Comply with NEMA OS 1, and list and label as complying with UL 514A.
12. Cast Metal Boxes: Comply with NEMA FB 1, and list and label as complying with UL 514A; furnish with threaded hubs.
13. Nonmetallic Boxes: Comply with NEMA OS 2, and list and label as complying with UL 514C.
14. Boxes for Supporting Luminaires and Ceiling Fans: Listed as suitable for the type and weight of load to be supported; furnished with fixture stud to accommodate mounting of luminaire where required.
15. Boxes for Ganged Devices: Use multigang boxes of single-piece construction. Do not use field-connected gangable boxes unless specifically indicated or permitted.
16. Minimum Box Size, Unless Otherwise Indicated:
a. Wiring Devices (Other Than Communications Systems Outlets): 4 inch square by 1-1/2 inch deep (100 by 38 mm) trade size. b. Communications Systems Outlets: 4 inch square by 2-1/8 inch (100 by 54 mm) trade size.
c. Ceiling Outlets: 4 inch octagonal or square by 1-1/2 inch deep (100 by 38 mm) trade size.
Lionakis No. 019124.02 26 05 33.16
January 26, 2024 Boxes for Electrical Systems
17. Wall Plates: Comply with Section 26 27 26.
18. Manufacturers:
a. Cooper Crouse-Hinds, a division of Eaton
Corporation: www.cooperindustries.com/#sle.
b. Hubbell Incorporated; Bell Products: www.hubbell-rtb.com/#sle. c. Hubbell Incorporated; RACO Products: www.hubbell-rtb.com/#sle. d. O-Z/Gedney, a brand of Emerson Electric Co
: www.emerson.com/#sle.
e. Thomas & Betts Corporation: www.tnb.com/#sle.
f. Or equal.
g. Substitutions: See Section 01 60 00 - Product Requirements.
C. Cabinets and Enclosures, Including Junction and Pull Boxes Larger Than 100 cubic inches:
1. Comply with NEMA 250, and list and label as complying with UL 50 and UL 50E, or UL 508A.
2. NEMA 250 Environment Type, Unless Otherwise Indicated:
a. Indoor Clean, Dry Locations: Type 1, painted steel. b. Outdoor Locations: Type 3R, painted steel.
c. Kitchens and food prep. Locations: Type 4X, stainless steel, unpainted.
3. Junction and Pull Boxes Larger Than 100 cubic inches:
a. Provide screw-cover or hinged-cover enclosures unless otherwise indicated.
b. Boxes 6 square feet and Larger: Provide sectionalized screw-cover or hinged-cover enclosures.
4. Cabinets and Hinged-Cover Enclosures, Other Than Junction and Pull Boxes:
a. Provide lockable hinged covers, all locks keyed alike unless otherwise indicated.
26 05 33.16 Lionakis No. 019124.02
Boxes for Electrical Systems January 26, 2024
b. Back Panels: Painted steel, removable.
c. Terminal Blocks: Provide voltage/current ratings and terminal quantity suitable for purpose indicated, with 25 percent spare terminal capacity.
5. Finish for Painted Steel Enclosures: Manufacturer's standard grey unless otherwise indicated.
6. Manufacturers:
a. Cooper B-Line, a division of Eaton
Corporation: www.cooperindustries.com/#sle.
b. Hoffman, a brand of Pentair Technical
Products: www.hoffmanonline.com/#sle.
c. Hubbell Incorporated; Wiegmann Products: www.hubbell- wiegmann.com/#sle.
d. Or equal.
e. Substitutions: See Section 01 60 00 - Product Requirements.
D. Boxes and Enclosures for Integrated Power, Data, and Audio/Video: Size and configuration as indicated or as required with partitions to separate services; field-connected gangable boxes may be used.
1. Manufacturers:
a. Hubbell Incorporated: www.hubbell.com/#sle.
b. Or approved equal.
c. Substitutions: See Section 01 60 00 - Product Requirements.
E. Boxes for Hazardous (Classified) Locations: Listed and labeled as complying with UL 1203 for the classification of the installed location.
1. Manufacturers:
a. Appleton, a brand of Emerson Electric Co: www.emerson.com/#sle. b. Cooper Crouse-Hinds, a division of Eaton
Corporation: www.cooperindustries.com/#sle.
c. Hubbell Incorporated; Killark Products: www.hubbell-killark.com/#sle.
Lionakis No. 019124.02 26 05 33.16
January 26, 2024 Boxes for Electrical Systems
d. Or approved equal.
e. Substitutions: See Section 01 60 00 - Product Requirements.
F. Floor Boxes:
1. Description: Floor boxes compatible with floor box service fittings provided in accordance with Section 26 27 26; with partitions to separate multiple services; furnished with all components, adapters, and trims required for complete installation.
2. Use cast iron floor boxes within slab on grade.
3. Use sheet-steel or cast iron floor boxes within slab above grade.
4. Metallic Floor Boxes: Fully adjustable (with integral means for leveling adjustment prior to and after concrete pour).
5. Manufacturer: Same as manufacturer of floor box service fittings.
G. Underground Boxes/Enclosures:
1. Description: In-ground, open bottom boxes furnished with flush, non-skid covers with legend indicating type of service and stainless steel tamper resistant cover bolts.
2. Size: As indicated on drawings.
3. Depth: As required to extend below frost line to prevent frost upheaval, but not less than 12 inches.
4. Provide logo on cover to indicate type of service.
5. Applications:
a. Sidewalks and Landscaped Areas Subject Only to Occasional Nondeliberate Vehicular Traffic: Use polymer concrete enclosures, with minimum SCTE 77 Tier 8 load rating.
b. Parking Lots, in Areas Subject Only To Occasional Nondeliberate Vehicular Traffic: Use polymer concrete enclosures, with minimum SCTE 77 Tier 15 load rating.
c. Do not use polymer concrete enclosures in areas subject to deliberate vehicular traffic.
26 05 33.16 Lionakis No. 019124.02
Boxes for Electrical Systems January 26, 2024
6. Polymer Concrete Underground Boxes/Enclosures: Comply with SCTE
77. a. Manufacturers:
1) Hubbell Incorporated; Quazite
Products: www.hubbellpowersystems.com/#sle.
2) MacLean Highline: www.macleanhighline.com/#sle.
3) Oldcastle Precast, Inc: www.oldcastleprecast.com/#sle. 4) Or equal.
5) Substitutions: See Section 01 60 00 - Product Requirements. b. Combination fiberglass/polymer concrete boxes/enclosures are acceptable.
c. Product(s):
1) MacLean Highline PHA Series: Straight wall, all-polymer concrete splice box/pull box; available Tier 8, Tier 15, and Tier 22 load ratings.
a) 11 by 18 by 12 inches nominal; Model PHA111812
(stackable).
2) MacLean Highline CHA Series: Fiberglass/polymer concrete splice box/pull box; available Tier 8 and Tier 15 load ratings. a) 11 by 18 by 12 inches nominal; Model CHA111812.
3) MacLean Highline CVA Series: Fiberglass/polymer concrete splice vault; available Tier 8, Tier 15, and Tier 22 load ratings. a) 30 by 48 by 18 inches nominal; Model CVA304818.
4) Or approved equal.
2.2 ACCESSORIES
A. Flashing Panels for Exterior Wall Penetrations: Premanufactured components and accessories as required to preserve integrity of building envelope; suitable for boxes and facade materials to be installed.
1. Manufacturers:
Lionakis No. 019124.02 26 05 33.16
January 26, 2024 Boxes for Electrical Systems
a. Quickflash Weatherproofing Products,
Inc: www.quickflashproducts.com/#sle.
b. Or approved equal.
c. Substitutions: See Section 01 60 00 - Product Requirements.
2.3 MANUFACTURERS
A. Appleton Electric: www.appletonelec.com.
B. Arc-Co./Division of Arcade Technology: www.arc-co.com.
C. Unity Manufacturing: www.unitymfg.com.
D. Or approved equal.
E. Substitutions: See Section 01 6000 - Product Requirements.
2.4 OUTLET BOXES
A. Sheet Metal Outlet Boxes: NEMA OS 1, galvanized steel.
1. Luminaire and Equipment Supporting Boxes: Rated for weight of equipment supported; include 1/2 inch male fixture studs where required.
2. Concrete Ceiling Boxes: Concrete type.
B. Cast Boxes: NEMA FB 1, Type FD, aluminum. Provide gasketed cover by box manufacturer. Provide threaded hubs.
C. Wall Plates for Finished Areas: As specified in Section 26 2726.
2.5 FLOOR BOXES
A. Floor Boxes: NEMA OS 1, fully adjustable, 1-1/2 inches deep.
B. Material: Cast metal.
C. Shape: Round.
D. Service Fittings: As specified in Section 26 2726.
2.6 PULL AND JUNCTION BOXES
A. Sheet Metal Boxes: NEMA OS 1, galvanized steel.
B. Hinged Enclosures: As specified in Section 26 2716. 26 05 33.16 Lionakis No. 019124.02
Boxes for Electrical Systems January 26, 2024
C. Surface Mounted Cast Metal Box: NEMA 250, Type 4; flat-flanged, surface mounted junction box:
1. Material: Galvanized cast iron.
2. Cover: Furnish with ground flange, neoprene gasket, and stainless steel cover screws.
D. In-Ground Cast Metal Box: NEMA 250, Type 6, outside flanged, recessed cover box for flush mounting:
1. Material: Galvanized cast iron.
2. Cover: Smooth cover with neoprene gasket and stainless steel cover screws.
3. Cover Legend: "ELECTRIC".
PART 3 EXECUTION
3.1 EXAMINATION
A. Verify that field measurements are as indicated.
B. Boxes are indicated in approximate locations only on the drawings unless specifically dimensioned. Verify all box locations prior to rough-in.
C. Verify that mounting surfaces are ready to receive boxes.
D. Verify that conditions are satisfactory for installation prior to starting work.
E. Verify locations of floor boxes and outlets prior to rough-in.
F. Verify locations of all boxes required for kitchen equipment with kithcen consultant plans and specifications.
3.2 INSTALLATION
A. Install products in accordance with manufacturer's instructions.
B. Install boxes in accordance with NECA 1 (general workmanship) and, where applicable, NECA 130, including mounting heights specified in those standards where mounting heights are not indicated.
C. Arrange equipment to provide minimum clearances in accordance with manufacturer's instructions and NFPA 70.
D. Provide separate boxes for emergency power and normal power systems.
Lionakis No. 019124.02 26 05 33.16
January 26, 2024 Boxes for Electrical Systems
E. Unless otherwise indicated, provide separate boxes for line voltage and low voltage systems.
F. Flush-mount boxes in finished areas unless specifically indicated to be surface-mounted.
G. Unless otherwise indicated, boxes may be surface-mounted where exposed conduits are indicated or permitted.
H. Box Locations:
1. Locate boxes to be accessible. Provide access panels in accordance with Section 08 31 00 as required where approved by the Architect.
2. Unless dimensioned, box locations indicated are approximate.
3. Locate boxes as required for devices installed under other sections or by others.
a. Switches, Receptacles, and Other Wiring Devices: Comply with Section 26 27 26.
b. Communications Systems Outlets: Comply with Section 27 10 00.
4. Locate boxes so that wall plates do not span different building finishes.
5. Locate boxes so that wall plates do not cross masonry joints.
6. Unless otherwise indicated, where multiple outlet boxes are installed at the same location at different mounting heights, install along a common vertical center line.
7. Do not install flush-mounted boxes on opposite sides of walls back-to- back. Provide minimum 6 inches horizontal separation unless otherwise indicated.
8. Acoustic-Rated Walls: Do not install flush-mounted boxes on opposite sides of walls back-to-back; provide minimum 24 inches horizontal separation.
9. Fire Resistance Rated Walls: Install flush-mounted boxes such that the required fire resistance will not be reduced.
a. Do not install flush-mounted boxes on opposite sides of walls back-to- back; provide minimum 24 inches separation where wall is constructed with individual noncommunicating stud cavities or protect both boxes with listed putty pads.
26 05 33.16 Lionakis No. 019124.02
Boxes for Electrical Systems January 26, 2024
b. Do not install flush-mounted boxes with area larger than 16 square inches or such that the total aggregate area of openings exceeds 100 square inches for any 100 square feet of wall area.
10. Locate junction and pull boxes as indicated, as required to facilitate installation of conductors, and to limit conduit length and/or number of bends between pulling points in accordance with Section 26 05 33.13.
11. Locate junction and pull boxes in the following areas, unless otherwise indicated or approved by the Architect:
a. Concealed above accessible suspended ceilings.
b. Within joists in areas with no ceiling.
c. Electrical rooms.
d. Mechanical equipment rooms.
I. Box Supports:
1. Secure and support boxes in accordance with NFPA 70 and Section 26 05 29 using suitable supports and methods approved by the authority having jurisdiction.
2. Provide required seismic controls in accordance with Section 26 05 48.
3. Provide independent support from building structure except for cast metal boxes (other than boxes used for fixture support) supported by threaded conduit connections in accordance with NFPA 70. Do not provide support from piping, ductwork, or other systems.
4. Installation Above Suspended Ceilings: Do not provide support from ceiling grid or ceiling support system.
5. Use far-side support to secure flush-mounted boxes supported from single stud in hollow stud walls. Repair or replace supports for boxes that permit excessive movement.
J. Install boxes plumb and level.
K. Flush-Mounted Boxes:
1. Install boxes in noncombustible materials such as concrete, tile, gypsum, plaster, etc. so that front edge of box or associated raised cover is not set back from finished surface more than 1/4 inch or does not project beyond finished surface.
Lionakis No. 019124.02 26 05 33.16
January 26, 2024 Boxes for Electrical Systems
2. Install boxes in combustible materials such as wood so that front edge of box or associated raised cover is flush with finished surface.
3. Repair rough openings around boxes in noncombustible materials such as concrete, tile, gypsum, plaster, etc. so that there are no gaps or open spaces greater than 1/8 inch at the edge of the box.
L. Floor-Mounted Cabinets: Mount on properly sized 3 inch high concrete pad constructed in accordance with Section 03 30 00.
M. Install boxes as required to preserve insulation integrity.
N. Metallic Floor Boxes: Install box level at the proper elevation to be flush with finished floor.
O. Nonmetallic Floor Boxes: Cut box flush with finished floor after concrete pour.
P. Underground Boxes/Enclosures:
1. Install enclosure on gravel base, minimum 6 inches deep.
2. Flush-mount enclosures located in concrete or paved areas.
3. Mount enclosures located in landscaped areas with top at 1 inch above finished grade.
4. Provide cast-in-place concrete collar constructed in accordance with Section 03 30 00, minimum 10 inches wide by 12 inches deep, around enclosures that are not located in concrete areas.
5. Install additional bracing inside enclosures in accordance with manufacturer's instructions to minimize box sidewall deflections during backfilling. Backfill with cover bolted in place.
Q. Install permanent barrier between ganged wiring devices when voltage between adjacent devices exceeds 300 V.
R. Install firestopping to preserve fire resistance rating of partitions and other elements, using materials and methods specified in Section 07 84 00.
S. Close unused box openings.
T. Install blank wall plates on junction boxes and on outlet boxes with no devices or equipment installed or designated for future use.
U. Provide grounding and bonding in accordance with Section 26 05 26. 26 05 33.16 Lionakis No. 019124.02
Boxes for Electrical Systems January 26, 2024
V. Identify boxes in accordance with Section 26 05 53.
W. Install boxes securely, in a neat and workmanlike manner, as specified in NECA 1.
X. Install in locations as shown on Drawings, and as required for splices, taps, wire pulling, equipment connections, and as required by NFPA 72.
Y. Coordinate installation of outlet boxes for equipment connected under Section 26 2717.
Z. Set wall mounted boxes at elevations to accommodate mounting heights indicated.
AA. Electrical boxes are shown on Drawings in approximate locations unless dimensioned.
1. Adjust box locations up to 10 feet if required to accommodate intended purpose.
BB. Orient boxes to accommodate wiring devices oriented as specified in Section 26 2726.
CC. Maintain headroom and present neat mechanical appearance.
DD. Install pull boxes and junction boxes above accessible ceilings and in unfinished areas only.
EE. Inaccessible Ceiling Areas: Install outlet and junction boxes no more than 6 inches from ceiling access panel or from removable recessed luminaire.
FF. Install boxes to preserve fire resistance rating of partitions and other elements, using materials and methods specified in Section 07 8400.
GG. Coordinate mounting heights and locations of outlets mounted above counters, benches, and backsplashes.
HH. Locate outlet boxes to allow luminaires positioned as shown on reflected ceiling plan.
II. Align adjacent wall mounted outlet boxes for switches, thermostats, and similar devices.
JJ. Use flush mounting outlet box in finished areas.
KK. Locate flush mounting box in masonry wall to require cutting of masonry unit corner only. Coordinate masonry cutting to achieve neat opening.
Lionakis No. 019124.02 26 05 33.16
January 26, 2024 Boxes for Electrical Systems
LL. Do not install flush mounting box back-to-back in walls; provide minimum 6 inches separation. Provide minimum 24 inches separation in fire-rated and acoustic rated walls.
MM. Secure flush mounting box to interior wall and partition studs. Accurately position to allow for surface finish thickness.
NN. Use stamped steel bridges to fasten flush mounting outlet box between studs.
OO. Install flush mounting box without damaging wall insulation or reducing its effectiveness.
PP. Use adjustable steel channel fasteners for hung ceiling outlet box.
QQ. Do not fasten boxes to ceiling support wires.
RR. Support boxes independently of conduit, except cast box that is connected to two rigid metal conduits both supported within 12 inches of box.
SS. Use gang box where more than one device is mounted together. Do not use sectional box.
TT. Use gang box with plaster ring for single device outlets.
UU. Use cast outlet box in exterior locations exposed to the weather and wet locations.
VV. Use cast floor boxes for installations in slab on grade; formed steel boxes are acceptable for other installations.
WW. Set floor boxes level.
XX. Large Pull Boxes: Use hinged enclosure in interior dry locations, surface- mounted cast metal box in other locations.
3.3 ADJUSTING
A. Adjust floor boxes flush with finish flooring material.
B. Adjust flush-mounting outlets to make front flush with finished wall material.
C. Install knockout closures in unused box openings.
26 05 33.16 Lionakis No. 019124.02
Boxes for Electrical Systems January 26, 2024
3.4 CLEANING
A. Clean interior of boxes to remove dirt, debris, plaster and other foreign material.
3.5 PROTECTION
A. Immediately after installation, protect boxes from entry of moisture and foreign material until ready for installation of conductors.
END OF SECTION 26 05 33.16
Lionakis No. 019124.02 26 05 53
January 26, 2024 Identification for Electrical Systems
SECTION 26 05 53 - IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 GENERAL
1.1 SECTION INCLUDES
A. Electrical identification requirements.
B. Identification nameplates and labels.
C. Wire and cable markers.
D. Voltage markers.
E. Underground warning tape.
F. Floor marking tape.
G. Warning signs and labels.
H. Field-painted identification of conduit.
1.2 RELATED REQUIREMENTS
A. Section 09 91 13 - Exterior Painting.
B. Section 09 91 23 - Interior Painting.
C. Section 26 05 00 – Common Work Results for Electrical.
D. Section 26 05 19 - Low-Voltage Electrical Power Conductors and Cables: Color coding for power conductors and cables 600 V and less; vinyl color coding electrical tape.
E. Section 26 05 73 - Power System Studies: Arc flash hazard warning labels.
F. Section 26 27 26 - Wiring Devices: Device and wallplate finishes; factory pre-marked wallplates.
G. Section 27 10 00 - Structured Cabling: Identification for communications cabling and devices.
1.3 REFERENCE STANDARDS
A. ANSI Z535.2 - American National Standard for Environmental and Facility Safety Signs; 2011 (Reaffirmed 2017).
B. ANSI Z535.4 - American National Standard for Product Safety Signs and Labels; 2011 (Reaffirmed 2017).
26 05 53 Lionakis No. 019124.02
Identification for Electrical Systems January 26, 2024
C. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.
D. NFPA 70E - Standard for Electrical Safety in the Workplace; 2024.
E. UL 969 - Marking and Labeling Systems; Current Edition, Including All Revisions.
1.4 ADMINISTRATIVE REQUIREMENTS
A. Coordination:
1. Verify final designations for equipment, systems, and components to be identified prior to fabrication of identification products.
B. Sequencing:
1. Do not conceal items to be identified, in locations such as above suspended ceilings, until identification products have been installed.
2. Do not install identification products until final surface finishes and painting are complete.
1.5 SUBMITTALS
A. See Section 01 30 00 - Administrative Requirements for submittals procedures.
B. Product Data: Provide manufacturer's standard catalog pages and data sheets for each product.
C. Shop Drawings: Provide schedule of items to be identified indicating proposed designations, materials, legends, and formats.
D. Samples:
1. Identification Nameplates: One of each type and color specified.
2. Warning Signs and Labels: One of each type and legend specified.
E. Manufacturer's Instructions: Indicate application conditions and limitations of use stipulated by product testing agency. Include instructions for storage, handling, protection, examination, preparation and installation of product.
1.6 QUALITY ASSURANCE
A. Conform to requirements of CEC.
Lionakis No. 019124.02 26 05 53
January 26, 2024 Identification for Electrical Systems
B. Conform to requirements of NFPA 70.
C. Furnish products listed and classified by UL as suitable for the purpose specified and shown.
1.7 FIELD CONDITIONS
A. Do not install adhesive products when ambient temperature is lower than recommended by manufacturer.
PART 2 PRODUCTS
2.1 IDENTIFICATION REQUIREMENTS
A. Existing Work: Unless specifically excluded, identify existing elements to remain that are not already identified in accordance with specified requirements.
B. Identification for Equipment:
1. Use identification nameplate to identify each piece of electrical distribution and control equipment and associated sections, compartments, and components.
a. Switchboards:
1) Identify ampere rating.
2) Identify voltage and phase.
3) Identify power source and circuit number. Include location when not within sight of equipment.
4) Use identification nameplate to identify main overcurrent protective device.
5) Use identification nameplate to identify load(s) served for each branch device. Do not identify spares and spaces.
b. Panelboards:
1) Identify ampere rating.
2) Identify voltage and phase.
3) Identify power source and circuit number. Include location when not within sight of equipment.
26 05 53 Lionakis No. 019124.02
Identification for Electrical Systems January 26, 2024
4) Identify main overcurrent protective device. Use identification label for panelboards with a door. For power distribution panelboards without a door, use identification nameplate.
5) Use typewritten circuit directory to identify load(s) served for panelboards with a door. Identify spares and spaces using pencil. 6) For power panelboards without a door, use identification nameplate to identify load(s) served for each branch device. Do not identify spares and spaces.
c. Transformers:
1) Identify kVA rating.
2) Identify voltage and phase for primary and secondary. 3) Identify power source and circuit number. Include location when not within sight of equipment.
4) Identify load(s) served. Include location when not within sight of equipment.
d. Enclosed switches, circuit breakers, and motor controllers:
1) Identify voltage and phase.
2) Identify power source and circuit number. Include location when not within sight of equipment.
3) Identify load(s) served. Include location when not within sight of equipment.
e. Time Switches:
1) Identify load(s) served and associated circuits controlled. Include location.
f. Enclosed Contactors:
1) Identify ampere rating.
2) Identify voltage and phase.
3) Identify configuration, e.g., E.O.E.H. (electrically operated, electrically held) or E.O.M.H. (electrically operated, mechanically held).
Lionakis No. 019124.02 26 05 53
January 26, 2024 Identification for Electrical Systems
4) Identify coil voltage.
5) Identify load(s) and associated circuits controlled. Include location. g. Centralized Emergency Lighting Inverters:
1) Identify input and output voltage and phase.
2) Identify power source and circuit number for normal power source.
Include location when not within sight of equipment.
3) Identify load(s) served. Include location.
h. Transfer Switches:
1) Identify voltage and phase.
2) Identify power source and circuit number for both normal power source and standby power source. Include location when not within sight of equipment.
3) Identify load(s) served. Include location when not within sight of equipment.
4) Identify short circuit current rating based on the specific overcurrent protective device type and settings protecting the transfer switch.
i. Electricity Meters:
1) Identify load(s) metered.
2. Service Equipment:
a. Use identification nameplate to identify each service disconnecting means.
b. For buildings or structures supplied by more than one service, or any combination of branch circuits, feeders, and services, use identification nameplate or means of identification acceptable to authority having jurisdiction at each service disconnecting means to identify all other services, feeders, and branch circuits supplying that building or structure. Verify format and descriptions with authority having jurisdiction.
3. Emergency System Equipment:
26 05 53 Lionakis No. 019124.02
Identification for Electrical Systems January 26, 2024
a. Use identification nameplate or voltage marker to identify emergency system equipment in accordance with NFPA 70.
b. Use identification nameplate at each piece of service equipment to identify type and location of on-site emergency power sources. c. Use identification nameplate to identify emergency operating instructions for emergency system equipment.
4. Use voltage marker to identify highest voltage present for each piece of electrical equipment.
5. Use identification nameplate to identify equipment utilizing series ratings, where permitted, in accordance with NFPA 70.
6. Use identification nameplate to identify switchboards and panelboards utilizing a high leg delta system in accordance with NFPA 70.
7. Use identification nameplate to identify disconnect location for equipment with remote disconnecting means.
8. Use identification label or handwritten text using indelible marker on inside of door at each fused switch to identify required NEMA fuse class and size.
9. Use identification label or handwritten text using indelible marker on inside of door at each motor controller to identify nameplate horsepower, full load amperes, code letter, service factor, voltage, and phase of motor(s) controlled.
10. Use identification label to identify overcurrent protective devices for branch circuits serving fire alarm circuits. Identify with text "FIRE ALARM CIRCUIT".
11. Use field-painted floor markings, floor marking tape, or warning labels to identify required equipment working clearances where indicated or where required by the authority having jurisdiction.
a. Field-Painted Floor Markings: Alternating black and white stripes, 3 inches wide, painted in accordance with Section 09 91 23 and 09 91
13. 12. Available Fault Current Documentation: Comply with Section 26 05 73.
Use identification label to identify the available fault current and date calculations were performed at locations requiring documentation by NFPA 70 including but not limited to the following.
Lionakis No. 019124.02 26 05 53
January 26, 2024 Identification for Electrical Systems
a. Service equipment.
b. Industrial control panels.
c. Motor control centers.
d. Elevator control panels.
e. Industrial machinery.
13. Arc Flash Hazard Warning Labels: Comply with Section 26 05 73.
14. Use warning signs to identify electrical hazards for entrances to all rooms and other guarded locations that contain exposed live parts operating at 600 V nominal or less with the word message "DANGER; Electrical hazard; Authorized personnel only" or approved equivalent.
15. Use warning signs to identify electrical hazards for entrances to all buildings, vaults, rooms, or enclosures containing exposed live parts or exposed conductors operating at over 600 V nominal with the word message "DANGER; HIGH VOLTAGE; KEEP OUT".
16. Use warning labels to identify electrical hazards for equipment, compartments, and enclosures containing exposed live parts or exposed conductors operating at over 600 V nominal with the word message "DANGER; HIGH VOLTAGE; KEEP OUT".
17. Use warning labels, identification nameplates, or identification labels to identify electrical hazards for equipment where multiple power sources are present with the word message "DANGER; Hazardous voltage; Multiple power sources may be present; Disconnect all electric power including remote disconnects before servicing" or approved equivalent.
C. Identification for Conductors and Cables:
1. Color Coding for Power Conductors 600 V and Less: Comply with Section 26 05 19.
2. Identification for Communications Conductors and Cables: Comply with Section 27 10 00.
3. Use identification nameplate or identification label to identify color code for ungrounded and grounded power conductors inside door or enclosure at each piece of feeder or branch-circuit distribution equipment when premises has feeders or branch circuits served by more than one nominal voltage system.
26 05 53 Lionakis No. 019124.02
Identification for Electrical Systems January 26, 2024
4. Use wire and cable markers to identify circuit number or other designation indicated for power, control, and instrumentation conductors and cables at the following locations:
a. At each source and load connection.
b. Within boxes when more than one circuit is present.
c. Within equipment enclosures when conductors and cables enter or leave the enclosure.
5. Use wire and cable markers to identify connected grounding electrode system components for grounding electrode conductors.
6. Use underground warning tape to identify direct buried cables.
D. Identification for Raceways:
1. Use voltage markers to identify highest voltage present for accessible conduits at maximum intervals of 20 feet.
2. Use voltage markers, color-coded bands, or factory-painted conduits to identify systems other than normal power system for accessible conduits. a. Maximum Intervals: 20 feet.
b. Color-Coded Bands: Use field-painting or vinyl color coding electrical tape to mark bands 3 inches wide.
1) Field-Painting: Comply with Section 09 91 23 and 09 91 13. 2) Vinyl Color Coding Electrical Tape: Comply with Section 26 05 19. 3) Other Owner required color coding systems.
3. Use identification labels, handwritten text using indelible marker, or plastic marker tags to identify circuits enclosed for accessible conduits at wall penetrations, at floor penetrations, at roof penetrations, and at equipment terminations when source is not within sight.
4. Use identification labels, handwritten text using indelible marker, or plastic marker tags to identify spare conduits at each end. Identify purpose and termination location.
5. Use underground warning tape to identify underground raceways.
6. Use voltage markers to identify highest voltage present for wireways at maximum intervals of 20 feet.
Lionakis No. 019124.02 26 05 53
January 26, 2024 Identification for Electrical Systems
E. Identification for Boxes:
1. Use voltage markers to identify highest voltage present.
2. Use voltage markers or color coded boxes to identify systems other than normal power system.
3. Use identification labels or handwritten text using indelible marker to identify circuits enclosed.. Install on back side of box cover. a. For exposed boxes in public areas, use only identification labels.
4. Use warning labels to identify electrical hazards for boxes containing exposed live parts or exposed conductors operating at over 600 V nominal with the word message "DANGER; HIGH VOLTAGE; KEEP OUT".
F. Identification for Devices:
1. Wiring Device and Wallplate Finishes: Comply with Section 26 27 26.
2. Factory Pre-Marked Wallplates: Comply with Section 26 27 26.
3. Use identification label to identify fire alarm system devices. a. For devices concealed above suspended ceilings, provide additional identification on ceiling tile below device location.
4. Use identification label or engraved wallplate to identify serving branch circuit for all receptacles.
a. For receptacles in public areas or in areas as directed by Architect, provide identification on inside surface of wallplate.
5. Use identification label or engraved wallplate to identify load controlled for wall-mounted control devices controlling loads that are not visible from the control location and for multiple wall-mounted control devices installed at one location.
6. Use identification label to identify receptacles protected by upstream GFI protection, where permitted.
G. Identification for Luminaires:
1. Use permanent red dot on luminaire frame to identify luminaires connected to emergency power system.
H. Buried Electrical Lines: Underground warning tapes.
26 05 53 Lionakis No. 019124.02
Identification for Electrical Systems January 26, 2024
I. Communication Cabinets: Nameplates.
J. Conduit: Conduit markers.
K. Control Device Station: Labels.
L. Electrical Distribution and Control Equipment Enclosures: Nameplates.
2.2 MANUFACTURERS
A. Brady Corporation: www.bradycorp.com.
B. Seton Identification Products: www.seton.com/aec.
C. HellermannTyton: www.hellermanntyton.com.
D. E-Z Code by T&B.
E. Pan-Code by Panduit.
F. Or approved equal.
G. Substitutions: See Section 01 6000 - Product Requirements.
2.3 IDENTIFICATION NAMEPLATES AND LABELS
A. Identification Nameplates:
1. Manufacturers:
a. Brimar Industries, Inc: www.brimar.com/#sle.
b. Kolbi Pipe Marker Co: www.kolbipipemarkers.com/#sle. c. Seton Identification Products: www.seton.com/#sle.
d. Or approved equal.
e. Substitutions: See Section 01 60 00 - Product Requirements.
2. Materials:
a. Indoor Clean, Dry Locations: Use plastic nameplates. b. Outdoor Locations: Use plastic, stainless steel, or aluminum nameplates suitable for exterior use.
3. Plastic Nameplates: Two-layer or three-layer laminated acrylic or electrically non-conductive phenolic with beveled edges; minimum thickness of 1/16 inch; engraved text.
Lionakis No. 019124.02 26 05 53
January 26, 2024 Identification for Electrical Systems
a. Exception: Provide minimum thickness of 1/8 inch when any dimension is greater than 4 inches.
4. Stainless Steel Nameplates: Minimum thickness of 1/32 inch; engraved or laser-etched text.
5. Aluminum Nameplates: Anodized; minimum thickness of 1/32 inch; engraved or laser-etched text.
6. Mounting Holes for Mechanical Fasteners: Two, centered on sides for sizes up to 1 inch high; Four, located at corners for larger sizes.
B. Identification Labels:
1. Manufacturers:
a. Brady Corporation: www.bradyid.com/#sle.
b. Brother International Corporation: www.brother-usa.com/#sle. c. Panduit Corp: www.panduit.com/#sle.
d. Or approved equal.
e. Substitutions: See Section 01 60 00 - Product Requirements.
2. Materials: Use self-adhesive laminated plastic labels; UV, chemical, water, heat, and abrasion resistant.
a. Use only for indoor locations.
3. Text: Use factory pre-printed or machine-printed text. Do not use handwritten text unless otherwise indicated.
C. Format for Equipment Identification:
1. Minimum Size: 1 inch by 2.5 inches.
2. Legend:
a. System designation where applicable:
1) Emergency Power System: Identify with text "EMERGENCY". b. Equipment designation or other approved description. c. Other information as indicated.
3. Text: All capitalized unless otherwise indicated.
26 05 53 Lionakis No. 019124.02
Identification for Electrical Systems January 26, 2024
4. Minimum Text Height:
a. System Designation: 1/2 inch.
b. Equipment Designation: 1/4 inch.
c. Other Information: 1/8 inch.
d. Exception: Provide minimum text height of 1 inch for equipment located more than 10 feet above floor or working platform.
5. Color:
a. Normal Power System: White text on black background. 1) 480Y/277 V, 3 Phase Equipment: White text on orange
background.
2) 208Y/120 V, 3 Phase Equipment: White text on black background. b. Emergency Power System: White text on red background.
D. Format for General Information and Operating Instructions:
1. Minimum Size: 1 inch by 2.5 inches.
2. Legend: Include information or instructions indicated or as required for proper and safe operation and maintenance.
3. Text: All capitalized unless otherwise indicated.
4. Minimum Text Height: 1/4 inch.
5. Color: Black text on white background unless otherwise indicated. a. Exceptions:
1) Provide white text on red background for general information or operational instructions for emergency systems.
2) Provide white text on red background for general information or operational instructions for fire alarm systems.
3) Provide white text on black background for all other systems, unless noted otherwise.
E. Format for Caution and Warning Messages:
1. Minimum Size: 2 inches by 4 inches.
Lionakis No. 019124.02 26 05 53
January 26, 2024 Identification for Electrical Systems
2. Legend: Include information or instructions indicated or as required for proper and safe operation and maintenance.
3. Text: All capitalized unless otherwise indicated.
4. Minimum Text Height: 1/2 inch.
5. Color: Black text on yellow background unless otherwise indicated.
F. Format for Receptacle Identification:
1. Minimum Size: 3/8 inch by 1.5 inches.
2. Legend: Power source and circuit number or other designation indicated. a. Include voltage and phase for other than 120 V, single phase circuits.
3. Text: All capitalized unless otherwise indicated.
4. Minimum Text Height: 3/16 inch.
5. Color: Black text on clear background.
G. Format for Control Device Identification:
1. Minimum Size: 3/8 inch by 1.5 inches.
2. Legend: Load controlled or other designation indicated.
3. Text: All capitalized unless otherwise indicated.
4. Minimum Text Height: 3/16 inch.
5. Color: Black text on clear background.
H. Manufacturers:
1. Kolbi Pipe Marker Co.; Model: www.kolbipipemarkers.com.
2. Seton Identification Product; Model:: www.seton.com.
3. Or approved equal.
I. Nameplates: Engraved three-layer laminated plastic, white letters on black background, unless noted otherwiseon drawings or specifications.
J. Locations:
1. Each electrical distribution and control equipment enclosure. 26 05 53 Lionakis No. 019124.02
Identification for Electrical Systems January 26, 2024
2. Communication cabinets.
K. Letter Size:
1. Use 1/8 inch letters for identifying individual equipment and loads.
2. Use 1/4 inch letters for identifying grouped equipment and loads.
L. Labels: Embossed adhesive tape, with 3/16 inch white letters on black background. Use only for identification of individual wall switches and receptacles, control device stations.
2.4 WIRE AND CABLE MARKERS
A. Manufacturers:
1. Brady Corporation: www.bradyid.com/#sle.
2. Seton Identification Products: www.seton.com.
3. HellermannTyton: www.hellermanntyton.com/#sle.
4. Panduit Corp: www.panduit.com/#sle.
5. Or approved equal.
6. Substitutions: See Section 01 60 00 - Product Requirements.
B. Markers for Conductors and Cables: Use wrap-around self-adhesive vinyl cloth, wrap-around self-adhesive vinyl self-laminating, heat-shrink sleeve, or plastic sleeve type markers suitable for the conductor or cable to be identified.
C. Markers for Conductor and Cable Bundles: Use plastic marker tags secured by nylon cable ties.
D. Legend: Power source and circuit number or other designation indicated.
E. Text: Use factory pre-printed or machine-printed text, all capitalized unless otherwise indicated.
1. Do not use handwritten text.
F. Minimum Text Height: 1/8 inch.
G. Color: Black text on white background unless otherwise indicated.
H. Description: Vinyl cloth type self-adhesive wire markers.
Lionakis No. 019124.02 26 05 53
January 26, 2024 Identification for Electrical Systems
I. Description: Cloth type wire markers.
J. Locations: Each conductor at panelboard gutters, pull boxes, outlet boxes, and junction boxes each load connection.
K. Legend:
1. Power and Lighting Circuits: Branch circuit or feeder number indicated on drawings.
2. Control Circuits: Control wire number indicated on schematic and interconnection diagrams on drawings.
2.5 VOLTAGE MARKERS
A. Manufacturers:
1. Brady Corporation: www.bradyid.com/#sle.
2. Brimar Industries, Inc: www.brimar.com/#sle.
3. Seton Identification Products: www.seton.com/#sle.
4. HellermannTyton: www.hellermanntyton.com.
5. Or approved equal.
6. Substitutions: See Section 01 60 00 - Product Requirements.
B. Markers for Conduits: Use factory pre-printed self-adhesive vinyl, self- adhesive vinyl cloth, or vinyl snap-around type markers.
C. Markers for Boxes and Equipment Enclosures: Use factory pre-printed self- adhesive vinyl or self-adhesive vinyl cloth type markers.
D. Minimum Size:
1. Markers for Equipment: 1 1/8 by 4 1/2 inches.
2. Markers for Conduits: As recommended by manufacturer for conduit size to be identified.
3. Markers for Pull Boxes: 1 1/8 by 4 1/2 inches.
4. Markers for Junction Boxes: 1/2 by 2 1/4 inches.
E. Legend:
1. Markers for Voltage Identification: Highest voltage present. 26 05 53 Lionakis No. 019124.02
Identification for Electrical Systems January 26, 2024
2. Markers for System Identification:
a. Emergency Power System: Text "EMERGENCY".
b. Other Systems: Type of service.
F. Color: Black text on orange background unless otherwise indicated.
G. Location: Furnish markers for each conduit longer than 6 feet.
H. Spacing: 20 feet on center.
I. Color:
1. Fire Alarm System: Red.
2.6 UNDERGROUND WARNING TAPE
A. Manufacturers:
1. Brady Corporation: www.bradyid.com/#sle.
2. Brimar Industries, Inc: www.brimar.com/#sle.
3. Seton Identification Products: www.seton.com/#sle.
4. HellermannTyton: www.hellermanntyton.com.
5. Or approve equal.
6. Substitutions: See Section 01 60 00 - Product Requirements.
B. Materials: Use foil-backed detectable type polyethylene tape suitable for direct burial, unless otherwise indicated.
C. Non-detectable Type Tape: 6 inches wide, with minimum thickness of 4 mil.
D. Foil-backed Detectable Type Tape: 3 inches wide, with minimum thickness of 5 mil, unless otherwise required for proper detection.
E. Legend: Type of service, continuously repeated over full length of tape.
F. Color:
1. Tape for Buried Power Lines: Black text on red background.
2. Tape for Buried Communication, Alarm, and Signal Lines: Black text on orange background.
Lionakis No. 019124.02 26 05 53
January 26, 2024 Identification for Electrical Systems
2.7 FLOOR MARKING TAPE
A. Manufacturers:
1. Brady Corporation: www.bradyid.com/#sle.
2. Brimar Industries, Inc: www.brimar.com/#sle.
3. Insite Solutions, LLC: www.stop-painting.com/#sle.
4. Seton Identification Products: www.seton.com/#sle.
5. Or approved equal..
6. Substitutions: See Section 01 60 00 - Product Requirements.
B. Floor Marking Tape for Equipment Working Clearance Identification: Self- adhesive vinyl or polyester tape with overlaminate, 3 inches wide, with alternating black and white stripes.
2.8 WARNING SIGNS AND LABELS
A. Manufacturers:
1. Brimar Industries, Inc: www.brimar.com/#sle.
2. Clarion Safety Systems, LLC: www.clarionsafety.com/#sle.
3. Insite Solutions, LLC: www.stop-painting.com/#sle.
4. Seton Identification Products: www.seton.com/#sle.
5. Or approved equal.
6. Substitutions: See Section 01 60 00 - Product Requirements.
B. Comply with ANSI Z535.2 or ANSI Z535.4 as applicable.
C. Warning Signs:
1. Materials:
a. Indoor Dry, Clean Locations: Use factory pre-printed rigid plastic or self-adhesive vinyl signs.
b. Outdoor Locations: Use factory pre-printed rigid aluminum signs.
2. Rigid Signs: Provide four mounting holes at corners for mechanical fasteners.
26 05 53 Lionakis No. 019124.02
Identification for Electrical Systems January 26, 2024
3. Minimum Size: 7 by 10 inches unless otherwise indicated.
D. Warning Labels:
1. Materials: Use factory pre-printed or machine-printed self-adhesive polyester or self-adhesive vinyl labels; UV, chemical, water, heat, and abrasion resistant; produced using materials recognized to UL 969. a. Do not use labels designed to be completed using handwritten text.
2. Machine-Printed Labels: Use thermal transfer process printing machines and accessories recommended by label manufacturer.
3. Minimum Size: 2 by 4 inches unless otherwise indicated.
E. Floor Signs:
1. Materials: Use factory preprinted, self-adhesive vinyl, polyester, or rubber labels with protective overlaminate; removable.
2. Minimum Size: 17-inch diameter unless otherwise indicated.
F. Description: 3 inch wide polyethylene tape, detectable type colored red with suitable warning legend describing buried electrical lines.
G. Description: 4 inch wide plastic tape, detectable type colored red with suitable warning legend describing buried electrical lines.
PART 3 EXECUTION
3.1 PREPARATION
A. Clean surfaces to receive adhesive products according to manufacturer's instructions.
B. Degrease and clean surfaces to receive nameplates and labels.
3.2 INSTALLATION
A. Install products in accordance with manufacturer's instructions.
B. Install identification products to be plainly visible for examination, adjustment, servicing, and maintenance. Unless otherwise indicated, locate products as follows:
1. Surface-Mounted Equipment: Enclosure front.
2. Flush-Mounted Equipment: Enclosure front.
Lionakis No. 019124.02 26 05 53
January 26, 2024 Identification for Electrical Systems
3. Free-Standing Equipment: Enclosure front; also enclosure rear for equipment with rear access.
4. Elevated Equipment: Legible from the floor or working platform.
5. Branch Devices: Adjacent to device.
6. Interior Components: Legible from the point of access.
7. Conduits: Legible from the floor.
8. Boxes: Outside face of cover.
9. Conductors and Cables: Legible from the point of access.
10. Devices: Outside face of cover.
C. Install identification products centered, level, and parallel with lines of item being identified.
D. Secure nameplates to exterior surfaces of enclosures using stainless steel screws and to interior surfaces using self-adhesive backing or epoxy cement.
1. Do not use adhesives on exterior surfaces except where substrate cannot be penetrated.
E. Install self-adhesive labels and markers to achieve maximum adhesion, with no bubbles or wrinkles and edges properly sealed.
F. Install underground warning tape above buried lines with one tape per trench at 3 inches below finished grade.
G. Secure rigid signs using stainless steel screws.
H. Mark all handwritten text, where permitted, to be neat and legible.
3.3 FIELD QUALITY CONTROL
A. See Section 01 40 00 - Quality Requirements, for additional requirements.
B. Replace self-adhesive labels and markers that exhibit bubbles, wrinkles, curling or other signs of improper adhesion.
END OF SECTION 26 05 53
Lionakis No. 019124.02 26 05 83
January 26, 2024 Wiring Connections
SECTION 26 05 83 - WIRING CONNECTIONS
PART 1 GENERAL
1.1 SECTION INCLUDES
A. Electrical connections to equipment.
1.2 RELATED REQUIREMENTS
A. Section 26 05 00 – Common Work Results for Electrical.
B. Section 26 05 19 - Low-Voltage Electrical Power Conductors and Cables.
C. Section 26 05 33.13 - Conduit for Electrical Systems.
D. Section 26 05 33.16 - Boxes for Electrical Systems.
E. Section 26 27 26 - Wiring Devices.
F. Section 26 28 16.16 - Enclosed Switches.
G. Section 26 29 13 - Enclosed Controllers.
1.3 REFERENCE STANDARDS
A. NEMA WD 1 - General Color Requirements for Wiring Devices; 1999 (Reaffirmed 2020).
B. NEMA WD 6 - Wiring Devices - Dimensional Specifications; 2021.
C. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.
1.4 ADMINISTRATIVE REQUIREMENTS
A. Coordination:
1. Obtain and review shop drawings, product data, manufacturer's wiring diagrams, and manufacturer's instructions for equipment furnished under other sections.
2. Determine connection locations and requirements.
B. Sequencing:
1. Install rough-in of electrical connections before installation of equipment is required.
26 05 83 Lionakis No. 019124.02
Wiring Connections January 26, 2024
2. Make electrical connections before required start-up of equipment.
1.5 SUBMITTALS
A. See Section 01 30 00 - Administrative Requirements, for submittal procedures.
B. Product Data: Provide wiring device manufacturer’s catalog information showing dimensions, configurations, and construction.
C. Manufacturer's Instructions: Indicate application conditions and limitations of use stipulated by product testing agency. Include instructions for storage, handling, protection, examination, preparation, and installation of product.
1.6 QUALITY ASSURANCE
A. Conform to requirements of NFPA 70.
B. Products: Listed, classified, and labeled as suitable for the purpose intended.
C. Product Listing Organization Qualifications: An organization recognized by OSHA as a Nationally Recognized Testing Laboratory (NRTL) and acceptable to authorities having jurisdiction.
PART 2 PRODUCTS
2.1 MATERIALS
A. Cords and Caps: NEMA WD 6; match receptacle configuration at outlet provided for equipment.
1. Colors: Comply with NEMA WD 1.
2. Cord Construction: NFPA 70, Type SO, multiconductor flexible cord with identified equipment grounding conductor, suitable for use in damp locations.
3. Size: Suitable for connected load of equipment, length of cord, and rating of branch circuit overcurrent protection.
4. Product: As noted on drawings or as required for the application.
5. Substitutions: See Section 01 60 00 - Product Requirements.
B. Disconnect Switches: As described and in individual equipment sections.
C. Wiring Devices: As specified in Section 26 27 26.
D. Flexible Conduit: As specified in Section 26 05 33.13.
Lionakis No. 019124.02 26 05 83
January 26, 2024 Wiring Connections
E. Wire and Cable: As specified in Section 26 05 19.
F. Boxes: As specified in Section 26 05 33.16.
2.2 EQUIPMENT CONNECTIONS
A. Connection Types and Ratings::
1. Electrical Connection: Flexible conduit, metallic or liquid tight flexible conduit as required by the application.
2. Electrical Connection: Cord and plug (Verify NEMA configuration and rating with equipment installer at jobsite).
3. Provide field-installed disconnect switch.
4. Voltage: Verify with equipment nameplate.
5. Load rating: Verify with equipment nameplate.
6. FLA: Verify with equipment nameplate.
7. WSA: Verify with equipment nameplate.
8. Branch Circuit: Verify with equipment nameplate.
9. Location: As indicated on drawings. Verify with equipment installer at jobsite.
PART 3 EXECUTION
3.1 EXAMINATION
A. Verify that equipment is ready for electrical connection, wiring, and energization.
3.2 ELECTRICAL CONNECTIONS
A. Make electrical connections in accordance with equipment manufacturer's instructions.
B. Make conduit connections to equipment using flexible conduit. Use liquidtight flexible conduit with watertight connectors in damp or wet locations.
C. Connect heat producing equipment using wire and cable with insulation suitable for temperatures encountered.
D. Provide receptacle outlet to accommodate connection with attachment plug. 26 05 83 Lionakis No. 019124.02
Wiring Connections January 26, 2024
E. Provide cord and cap where field-supplied attachment plug is required.
F. Install suitable strain-relief clamps and fittings for cord connections at outlet boxes and equipment connection boxes.
G. Install disconnect switches, controllers, control stations, and control devices to complete equipment wiring requirements.
H. Install terminal block jumpers to complete equipment wiring requirements.
I. Install interconnecting conduit and wiring between devices and equipment to complete equipment wiring requirements.
J. Coolers and Freezers: Cut and seal conduit openings in freezer and cooler walls, floor, and ceilings.
END OF SECTION 26 05 83
Lionakis No. 019124.02 26 08 00
January 26, 2024 Electrical Commissioning Requirements
SECTION 26 08 00 - ELECTRICAL COMMISSIONING REQUIREMENTS PART 1 - GENERAL
1.1 DESCRIPTION
A. The purpose of this section is to specify the Contractor's responsibilities and participation in the commissioning process relative to division 26.
B. The commissioning process is primarily the responsibility of the Commissioning Authority, with support for start-up, testing, and commissioning the responsibility of the Contractors. The commissioning process does not relieve the Contractor from participation in the process, or diminish the role and obligations to complete all portions of work in a satisfactory and fully operational manner.
C. Work of Division 26 includes:
1. Testing and start-up of the electrical equipment.
2. Providing qualified personnel to assist in commissioning tests to verify equipment/ system performance.
3. Completion and endorsement of pre-functional test checklists provided by the Commissioning Authority to assure that Division 26 equipment and systems are fully operational and ready for functional testing.
4. Providing equipment, materials, and labor necessary to correct deficiencies found during the commissioning process which fulfill contract and warranty requirements.
5. Providing training for the systems specified in Division 26 with coordination of owner by the Commissioning Authority.
1.2 RELATED WORK
A. All testing and start-up procedures and documentation requirements specified within Division 26.
B. Section 01 9100 - General Commissioning Requirements C. Commissioning functional test procedures that require participation of the Contractors.
D. Cooperate with the Commissioning Authority in the following manner:
1. Allow sufficient time before final completion dates so that testing can be accomplished.
26 08 00 Lionakis No. 019124.02
Electrical Commissioning Requirements January 26, 2024
2. Provide labor and material to make corrections when required without undue delay.
3. Coordinate all required support of that equipment which is provided to or installed with involvement of Division 23 contractors.
PART 2 - PRODUCTS
2.1 TEST EQUIPMENT
A. Standard certified test equipment for commissioning shall be provided by the Division 26 Contractor.
B. Proprietary test equipment required by the manufacturer, whether specified or not, shall be provided by the manufacturer of the equipment. Manufacturer shall provide the test equipment, demonstrate its use, and assist the Commissioning Authority in the commissioning process.
PART 3 - EXECUTION
3.1 WORK PRIOR TO COMMISSIONING
A. Complete all phases of work so the system can be started, tested, balanced, and otherwise commissioned. Division 26 has temporary power and start-up responsibilities with obligations to complete systems, including all sub- systems so they are functional. This includes the complete installation of all equipment and materials per the contract documents and related directives, clarifications, change orders, etc.
B. The Commissioning Authority will develop a Commissioning Plan. Upon request of the Commissioning Authority, the Contractor shall provide assistance and consultation. The Commissioning Plan will be developed prior to completion of the installation. The Contractor is obligated to assist the Commissioning Authority in preparing the Commissioning Plan by providing all necessary information pertaining to the actual equipment and installation.
C. Specific pre-commissioning responsibilities of Division 26 are as follows:
1. Normal start-up services required to bring each system into a fully operational state. The Commissioning Authority will not begin the commissioning process until each system is complete and documented, including normal contractor start-up.
Lionakis No. 019124.02 26 08 00
January 26, 2024 Electrical Commissioning Requirements
2. The Contractor shall perform pre-functional tests on the equipment and systems as noted in section 01 9100 General Commissioning Requirements.
3. Contractor start-up forms may be substituted for the pre-functional test forms with prior approval by the Commissioning Authority.
4. Pre-functional test forms will be kept in the Contractors job trailer in a Commissioning Field Notebook provided by the Commissioning Authority.
5. Factory start-up services will be provided for key equipment and systems specified in Division 26. The Contractor shall coordinate this work with the manufacturer and the Commissioning Authority.
D. Commissioning is intended to begin upon completion of a system. Commissioning may proceed prior to the completion of systems and/or sub-systems, if expediting this work is in the best interests of the Owner. Commissioning activities and schedule will be coordinated with the Contractor. Start of commissioning before system completion will not relieve the Contractor from completing those systems as per the schedule.
E. The Field Commissioning Notebook will be used to identify and track all pertinent commissioning documentation required during the Installation phase. This Notebook will be assembled by the Commissioning Authority and maintained by the Contractor. The Notebook provides a central location for the Commissioning Authority to identify, copy and organize all pertinent information and will include the following format:
1. Summary describing Notebook contents and use.
2. Copy of Commissioning Plan for contractor field reference.
3. Listing of all specification documentation requirements listed by specification section, with sign off spots for appropriate contractors.
4. Tabs for each specification section with copies of pre-functional test check sheets provided by coordination of subcontractors and Commissioning Authority for contractor completion and space for related contractor-supplied documents.
5. Prior to functional testing the Commissioning Authority will use this book to verify that all appropriate contractors have completed their work and signed off that they have done so. Once the Commissioning Authority is satisfied that all components of a system are complete functional testing will begin.
26 08 00 Lionakis No. 019124.02
Electrical Commissioning Requirements January 26, 2024
3.2 PARTICIPATION IN COMMISSIONING
A. Provide skilled technicians to start up and debug all systems within the division of work. These same technicians shall be made available to assist the Commissioning Authority in completing the commissioning program as it relates to each system and their technical specialty. Work schedules, time required for testing, etc., will be requested by the Commissioning Authority and coordinated by the Contractor. Contractor will ensure the qualified technician(s) are available and present during the agreed-upon schedules and of sufficient duration to complete the necessary tests, adjustments, and/or problem resolutions.
B. The Commissioning Authority reserves the right to judge the appropriateness and qualifications of the technicians relative to each item of equipment, system, and/or sub-system. Qualifications of technicians include expert knowledge relative to the specific equipment involved, adequate documentation and tools to service/commission the equipment, and an attitude/willingness to work with the Commissioning Authority to get the job done. A liaison or intermediary between the Commissioning Authority and qualified factory representatives does not constitute the availability of a qualified technician for purposes of this work.
3.3 WORK TO RESOLVE DEFICIENCIES
A. Maladjustments, misapplied equipment, and/or deficient performance under varying loads will result in a system that does not meet the original design intent. Correction of work will be completed under the direction of the Architect, with input from the Contractor, equipment supplier, and Commissioning Authority. Whereas all members will have input and the opportunity to discuss, debate, and work out problems, the Architect/Engineer of Record will have final jurisdiction on the necessary work to be done to achieve performance and or design intent.
3.4 ADDITIONAL COMMISSIONING
A. Additional commissioning activities may be required after system adjustments, replacements, etc., are completed. The Contractor, suppliers, and Commissioning Authority shall include a reasonable reserve to complete this work as part of their standard contractual obligations.
Lionakis No. 019124.02 26 08 00
January 26, 2024 Electrical Commissioning Requirements
3.5 SEASONAL COMMISSIONING AND OCCUPANCY VARIATIONS
A. Seasonal commissioning pertains to testing under full-load conditions during peak heating and peak cooling seasons, as well as part-load conditions in the spring and fall. Initial commissioning will be done as soon as contract work is completed regardless of season. Subsequent commissioning may be undertaken at any time thereafter to ascertain adequate performance during the different seasons.
B. All equipment and systems will be tested and commissioned in a peak season to observe full-load performance. The Contractor will be responsible to participate in the initial and the alternate peak season test of the systems required to demonstrate performance.
C. Subsequent commissioning may be required under conditions of minimum and/or maximum occupancy or use. All equipment and systems affected by occupancy variations will be tested and commissioned at the minimum and peak loads to observe system performance. The Contractor will be responsible to participate in the occupancy sensitive testing of systems to provide verification of adequate performance.
3.6 TRAINING
A. The Contractor will be required to participate in the training of the Owner's engineering and maintenance staff for each mechanical system and the related components. Training may be conducted in a classroom setting, with system and component documentation, and suitable classroom training aids, or in the field with the specific equipment. The type of training will be per the Owner's option.
B. Training will be conducted jointly with the Commissioning Authority, the design engineers, the equipment vendors, and the Contractor. The Contractor will be responsible for the generic training, as well as instructing the Owner's staff on the system peculiarities specific to this project.
3.7 SYSTEMS DOCUMENTATION
A. Contract Documents to incorporate field changes and revisions to system designs to account for actual constructed configurations will be addressed as required in Division 1. All drawings should be red-lined on two sets. Division 26 as-built drawings should include updated architectural floor plans, and the individual electrical systems in relation to actual building layout.
B. Maintain as-built red-lines on the job site as required in Division 1. 26 08 00 Lionakis No. 019124.02
Electrical Commissioning Requirements January 26, 2024
C. In addition to the stated requirements for operation and maintenance data, provide one copy of equipment technical literature, operation and maintenance literature, and shop drawings to the Commissioning Authority as soon as they are available. This requirement is for review of these documents prior to distribution of multiple copies for the Owner's final use.
END OF SECTION 26 08 00
Lionakis No. 019124.02 26 09 23
January 26, 2024 Lighting Control Devices
SECTION 26 09 23 - LIGHTING CONTROL DEVICES
PART 1 GENERAL
1.1 SECTION INCLUDES
A. Occupancy sensors.
B. Outdoor motion sensors.
C. Time switches.
D. In-wall time switches.
E. In-wall interval timers.
F. Outdoor photo controls.
G. Daylighting controls.
H. Lighting contactors.
I. Accessories.
1.2 RELATED REQUIREMENTS
A. Section 26 05 26 - Grounding and Bonding for Electrical Systems.
B. Section 26 05 29 - Hangers and Supports for Electrical Systems C. Section 26 05 33.16 - Boxes for Electrical Systems.
D. Section 26 05 53 - Identification for Electrical Systems: Identification products and requirements.
E. Section 26 05 73 - Power System Studies.
F. Section 26 09 18 - Remote Control Switching Devices: Remotely controlled devices for lighting control, including networked lighting controls, programmable relay panels, and remote control switching relays.
G. Section 26 2716 - Electrical Cabinets and Enclosures.
H. Section 26 27 26 - Wiring Devices: Devices for manual control of lighting, including wall switches, wall dimmers, and fan speed controllers.
1. Includes finish requirements for wall controls specified in this section.
2. Includes accessory receptacles, switches, dimmers and wall plates, to match lighting controls specified in this section.
26 09 23 Lionakis No. 019124.02
Lighting Control Devices January 26, 2024
I. Section 26 28 13 - Fuses.
J. Section 26 51 00 - Interior Lighting.
K. Section 26 56 00 - Exterior Lighting.
1.3 REFERENCE STANDARDS
A. 47 CFR 15 - Radio Frequency Devices; current edition.
B. ANSI C136.10 - American National Standard for Roadway and Area Lighting Equipment - Locking-Type Photocontrol Devices and Mating Receptacles - Physical and Electrical Interchangeability and Testing; 2023.
C. ANSI C136.24 - American National Standard for Roadway and Area Lighting Equipment - Nonlocking (Button) Type Photocontrols; 2020.
D. NECA 1 - Standard for Good Workmanship in Electrical Construction; 2015.
E. NECA 130 - Standard for Installing and Maintaining Wiring Devices; 2016.
F. NEMA 250 - Enclosures for Electrical Equipment (1000 Volts Maximum); 2020.
G. NEMA 410 - Performance Testing for Lighting Controls and Switching Devices with Electronic Drivers and Discharge Ballasts; 2023.
H. NEMA ICS 2 - Industrial Control and Systems Controllers, Contactors and Overload Relays Rated 600 Volts; 2008 (Reaffirmed 2020).
I. NEMA ICS 5 - Industrial Control and Systems: Control Circuit and Pilot Devices; 2017.
J. NEMA ICS 6 - Industrial Control and Systems: Enclosures; 1993 (Reaffirmed 2016).
K. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.
L. UL 773 - Plug-in, Locking Type Photocontrols for Use with Area Lighting; Current Edition, Including All Revisions.
M. UL 773A - Nonindustrial Photoelectric Switches for Lighting Control; Current Edition, Including All Revisions.
N. UL 916 - Energy Management Equipment; Current Edition, Including All Revisions.
Lionakis No. 019124.02 26 09 23
January 26, 2024 Lighting Control Devices
O. UL 917 - Clock-Operated Switches; Current Edition, Including All Revisions.
P. UL 1472 - Solid-State Dimming Controls; Current Edition, Including All Revisions.
Q. UL 60947-1 - Low-Voltage Switchgear and Controlgear - Part 1: General Rules; Current Edition, Including All Revisions.
R. UL 60947-4-1 - Low-Voltage Switchgear and Controlgear - Part 4-1:
Contactors and Motor-starters - Electromechanical Contactors and Motor- starters; Current Edition, Including All Revisions.
1.4 ADMINISTRATIVE REQUIREMENTS
A. Coordination:
1. Coordinate the placement of lighting control devices with millwork, furniture, equipment, etc. installed under other sections or by others.
2. Coordinate the placement of wall switch occupancy sensors with actual installed door swings.
3. Coordinate the placement of occupancy sensors with millwork, furniture, equipment or other potential obstructions to motion detection coverage installed under other sections or by others.
4. Coordinate the placement of photo sensors for daylighting controls with windows, skylights, and luminaires to achieve optimum
operation. Coordinate placement with ductwork, piping, equipment, or other potential obstructions to light level measurement installed under other sections or by others.
5. Notify the Architect and/or the Electrical Engineer of Record of any conflicts or deviations from the contract documents to obtain direction prior to proceeding with work.
B. Sequencing:
1. Do not install lighting control devices until final surface finishes and painting are complete.
1.5 SUBMITTALS
A. See Section 01 30 00 - Administrative Requirements, for submittal procedures.
26 09 23 Lionakis No. 019124.02
Lighting Control Devices January 26, 2024
B. Product Data: Include ratings, configurations, standard wiring diagrams, dimensions, colors, service condition requirements, and installed features.
1. Occupancy Sensors: Include detailed motion detection coverage range diagrams.
C. Shop Drawings:
1. Occupancy Sensors: Provide lighting plan indicating location, model number, and orientation of each occupancy sensor and associated system component.
2. Daylighting Controls: Provide lighting plan indicating location, model number, and orientation of each photo sensor and associated system component.
D. Samples:
1. Occupancy Sensors: One for each type and color specified.
2. In-Wall Time Switches: One for each type and color specified.
3. In-Wall Interval Timers: One for each type and color specified.
4. Daylighting Control Photo Sensors: One for each type and color specified.
E. Field Quality Control Reports.
F. Manufacturer's Installation Instructions: Include application conditions and limitations of use stipulated by product testing agency. Include instructions for storage, handling, protection, examination, preparation, and installation of product.
G. Operation and Maintenance Data: Include detailed information on device programming and setup.
H. Maintenance Materials: Furnish the following for Owner's use in maintenance of project.
1. See Section 01 60 00 - Product Requirements, for additional provisions.
2. Extra Locking Receptacle-Mounted Outdoor Photo Controls: Five percent of total quantity installed for each type, but not less than two of each type.
3. Electronic Trip Circuit Breakers: Provide one portable test set.
4. Indicating Lights: Two of each different type.
Lionakis No. 019124.02 26 09 23
January 26, 2024 Lighting Control Devices
I. Project Record Documents: Record actual installed locations and settings for lighting control devices.
1.6 QUALITY ASSURANCE
A. Conform to requirements of CEC.
B. Maintain at the project site a copy of each referenced document that prescribes execution requirements.
C. Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum three years documented experience.
D. Product Listing Organization Qualifications: An organization recognized by OSHA as a Nationally Recognized Testing Laboratory (NRTL) and acceptable to authorities having jurisdiction.
1.7 DELIVERY, STORAGE, AND PROTECTION
A. Store products in a clean, dry space in original manufacturer's packaging in accordance with manufacturer's written instructions until ready for installation.
1.8 FIELD CONDITIONS
A. Maintain field conditions within manufacturer's required service conditions during and after installation.
1.9 WARRANTY
A. See Section 01 78 00 - Closeout Submittals, for additional warranty requirements.
B. Provide five year manufacturer warranty for all occupancy sensors.
C. Provide five year manufacturer warranty for utility grade locking receptacle- mounted outdoor photo controls.
D. Provide two year manufacturer warranty for all daylighting controls.
PART 2 PRODUCTS
2.1 LIGHTING CONTROL DEVICES - GENERAL REQUIREMENTS
A. General Requirements
1. Provide products listed, classified, and labeled as suitable for the purpose intended.
26 09 23 Lionakis No. 019124.02
Lighting Control Devices January 26, 2024
2. Unless specifically indicated to be excluded, provide all required conduit, wiring, connectors, hardware, components, accessories, etc. as required for a complete operating system.
3. Products for Switching of Electronic Ballasts/Drivers: Tested and rated to be suitable for peak inrush currents specified in NEMA 410.
2.2 OCCUPANCY SENSORS
A. Manufacturers:
1. Acuity Brands, Inc: www.acuitybrands.com/#sle.
2. Hubbell Incorporated: www.hubbell.com/#sle.
3. Intermatic, Inc: www.intermatic.com/#sle.
4. Legrand North America, Inc: www.legrand.us/#sle.
5. Lutron Electronics Company, Inc: www.lutron.com/#sle.
6. RAB Lighting, Inc: www.rablighting.com/#sle.
7. Or approved equal..
8. Substitutions: See Section 01 60 00 - Product Requirements.
9. Source Limitations: Furnish products produced by a single manufacturer and obtained from a single supplier.
B. All Occupancy Sensors:
1. Description: Factory-assembled commercial specification grade devices for indoor use capable of sensing both major motion, such as walking, and minor motion, such as small desktop level movements, according to published coverage areas, for automatic control of load indicated.
2. Sensor Technology:
a. Passive Infrared (PIR) Occupancy Sensors: Designed to detect occupancy by sensing movement of thermal energy between zones. b. Ultrasonic Occupancy Sensors: Designed to detect occupancy by sensing frequency shifts in emitted and reflected inaudible sound waves.
Lionakis No. 019124.02 26 09 23
January 26, 2024 Lighting Control Devices
c. Passive Infrared/Ultrasonic Dual Technology Occupancy Sensors: Designed to detect occupancy using a combination of both passive infrared and ultrasonic technologies.
d. Passive Infrared/Acoustic Dual Technology Occupancy
Sensors: Designed to detect occupancy using a combination of both passive infrared and audible sound sensing technologies.
3. Provide LED to visually indicate motion detection with separate color LEDs for each sensor type in dual technology units.
4. Operation: Unless otherwise indicated, occupancy sensor to turn load on when occupant presence is detected and to turn load off when no occupant presence is detected during an adjustable turn-off delay time interval.
5. Dual Technology Occupancy Sensors: Field configurable turn-on and hold-on activation with settings for activation by either or both sensing technologies.
6. Passive Infrared Lens Field of View: Field customizable by addition of factory masking material, adjustment of integral blinders, or similar means to block motion detection in selected areas.
7. Turn-Off Delay: Field adjustable, with time delay settings up to 30 minutes.
8. Sensitivity: Field adjustable.
9. Adaptive Technology: Field selectable; capable of self-adjusting sensitivity and time delay according to conditions.
10. Integral Photocell: For field selectable and adjustable inhibition of automatic turn-on of load when ambient lighting is above the selected level.
11. Compatibility (Non-Dimming Sensors): Suitable for controlling incandescent lighting, low-voltage lighting with electronic and magnetic transformers, fluorescent lighting with electronic and magnetic ballasts, and fractional motor loads, with no minimum load requirements.
12. Load Rating for Line Voltage Occupancy Sensors: As required to control the load indicated on drawings.
13. Isolated Relay for Low Voltage Occupancy Sensors: SPDT dry contacts, ratings as required for interface with system indicated. 26 09 23 Lionakis No. 019124.02
Lighting Control Devices January 26, 2024
14. Where wired sensors are indicated, wireless sensors are acceptable provided that all components and wiring modifications necessary for proper operation are included.
15. Wireless Sensors:
a. RF Range: 30 feet through typical construction materials. b. Electromagnetic Interference/Radio Frequency Interference (EMI/RFI) Limits: Comply with FCC requirements of 47 CFR 15, for Class B application.
c. Power: Battery-operated with minimum ten-year battery life.
C. Wall Switch Occupancy Sensors:
1. All Wall Switch Occupancy Sensors:
a. Description: Occupancy sensors designed for installation in standard wall box at standard wall switch mounting height with a field of view of 180 degrees, integrated manual control capability, and no leakage current to load in off mode.
b. Unless otherwise indicated or required to control the load indicated on drawings, provide line voltage units with self-contained relay. c. Where indicated, provide two-circuit units for control of two separate lighting loads, with separate manual controls and separately programmable operation for each load.
d. Operation: Field selectable to operate either as occupancy sensor (automatic on/off) or as vacancy sensor (manual-on/automatic off). e. Manual-Off Override Control: When used to turn off load while in automatic-on mode, unit to revert back to automatic mode after no occupant presence is detected during the delayed-off time interval. f. Provide selectable audible alert to notify occupant of impending load turn-off.
g. Finish: Match finishes specified for wiring devices in Section 26 27 26, unless otherwise indicated.
h. Provide vandal resistant lenses for passive infrared (PIR) and dual technology wall switch occupancy sensors where indicated.
Lionakis No. 019124.02 26 09 23
January 26, 2024 Lighting Control Devices
2. Passive Infrared (PIR) Wall Switch Occupancy Sensors: Capable of detecting motion within an area of 900 square feet.
3. Ultrasonic Wall Switch Occupancy Sensors: Capable of detecting motion within an area of 400 square feet.
4. Passive Infrared/Ultrasonic Dual Technology Wall Switch Occupancy Sensors: Capable of detecting motion within an area of 900 square feet.
D. Wall Dimmer Occupancy Sensors:
1. General Requirements:
a. Description: Occupancy sensors designed for installation in standard wall box at standard wall switch mounting height with a field of view of 180 degrees, integrated dimming control capability , and no leakage current to load in off mode.
b. Operation: Field selectable to operate either as occupancy sensor (automatic on/off) or as vacancy sensor (manual-on/automatic off). c. Manual-Off Override Control Capability: When used to turn off load while in automatic-on mode, unit to revert back to automatic mode after no occupant presence is detected during the delayed-off time interval.
d. Dimmer: Solid-state with continuous full-range even control following square law dimming curve, integral radio frequency interference filtering, power failure preset memory, air gap switch accessible without removing wall plate, and listed as complying with UL 1472; type and rating suitable for load controlled.
e. Provide field adjustable dimming preset for occupied state. f. Provide fade-to-off operation to notify occupant of impending load turn-off.
g. Finish: Match finishes specified for wiring devices in Section 26 27 26, unless otherwise indicated.
2. Passive Infrared (PIR) Wall Dimmer Occupancy Sensors: Capable of detecting motion within an area of 900 square feet.
E. Ceiling Mounted Occupancy Sensors:
1. All Ceiling Mounted Occupancy Sensors:
26 09 23 Lionakis No. 019124.02
Lighting Control Devices January 26, 2024
a. Description: Low profile occupancy sensors designed for ceiling installation.
b. Unless otherwise indicated or required to control the load indicated on drawings, provide low voltage units, for use with separate compatible accessory power packs.
c. Provide field selectable setting for disabling LED motion detector visual indicator.
d. Occupancy sensor to be field selectable as either manual- on/automatic-off or automatic on/off.
e. Finish: White unless otherwise indicated.
2. Passive Infrared (PIR) Ceiling Mounted Occupancy Sensors:
a. Standard Range Sensors: Capable of detecting motion within an area of 450 square feet at a mounting height of 9 feet, with a field of view of 360 degrees.
b. Extended Range Sensors: Capable of detecting motion within an area of 1,200 square feet at a mounting height of 9 feet, with a field of view of 360 degrees.
3. Ultrasonic Ceiling Mounted Occupancy Sensors:
a. Standard Range Sensors: Capable of detecting motion within an area of 500 square feet at a mounting height of 9 feet, with a field of view of 360 degrees.
b. Medium Range Sensors: Capable of detecting motion within an area of 1,000 square feet at a mounting height of 9 feet, with a field of view of 360 degrees.
c. Extended Range Sensors: Capable of detecting motion within an area of 2,000 square feet at a mounting height of 9 feet.
4. Passive Infrared/Ultrasonic Dual Technology Ceiling Mounted Occupancy Sensors:
a. Standard Range Sensors: Capable of detecting motion within an area of 450 square feet at a mounting height of 9 feet, with a field of view of 360 degrees.
Lionakis No. 019124.02 26 09 23
January 26, 2024 Lighting Control Devices
b. Extended Range Sensors: Capable of detecting motion within an area of 1,200 square feet at a mounting height of 9 feet, with a field of view of 360 degrees.
5. Passive Infrared/Acoustic Dual Technology Ceiling Mounted Occupancy Sensors:
a. Standard Range Sensors: Capable of detecting motion within an area of 450 square feet at a mounting height of 9 feet, with a field of view of 360 degrees.
b. Extended Range Sensors: Capable of detecting motion within an area of 1,200 square feet at a mounting height of 9 feet.
F. Directional Occupancy Sensors:
1. All Directional Occupancy Sensors: Designed for wall or ceiling mounting, with integral swivel for field adjustment of motion detection coverage.
a. Unless otherwise indicated or required to control the load indicated on drawings, provide low voltage units, for use with separate compatible accessory power packs.
b. Provide field selectable setting for disabling LED motion detector visual indicator.
c. Finish: White unless otherwise indicated.
2. Passive Infrared (PIR) Directional Occupancy Sensors:
a. Standard Range Sensors: Capable of detecting motion within a distance of 40 feet at a mounting height of 10 feet.
b. Long Range Sensors: Capable of detecting motion within a distance of 80 feet at a mounting height of 10 feet.
c. High Bay Sensors: Capable of detecting motion within a distance of 50 feet at a mounting height of 30 feet.
3. Passive Infrared/Ultrasonic Dual Technology Directional Occupancy Sensors: Capable of detecting motion within a distance of 40 feet at a mounting height of 10 feet.
G. Luminaire Mounted Occupancy Sensors: Designed for direct luminaire installation and control, suitable for use with specified luminaires. 26 09 23 Lionakis No. 019124.02
Lighting Control Devices January 26, 2024
1. Fluorescent High Bay Luminaire Mounted Occupancy Sensors: Passive infrared (PIR) type with a field of view of 360 degrees unless otherwise indicated.
a. Unless otherwise indicated or required to control the load indicated on drawings, provide line voltage units with self-contained relay. b. Finish: White unless otherwise indicated.
c. Circular Coverage Sensors: Capable of detecting motion within a distance of 40 feet at a mounting height of 20 feet.
d. Linear Aisle Coverage Sensors: Capable of detecting motion within an area of 20 feet wide by 60 feet long at a mounting height of 40 feet. e. Accessories:
1) Provide mounting bracket for lowering occupancy sensor such that luminaire does not block sensor field of view where required.
H. Power Packs for Low Voltage Occupancy Sensors:
1. Description: Plenum rated, self-contained low voltage class 2 transformer and relay compatible with specified low voltage occupancy sensors for switching of line voltage loads.
2. Provide quantity and configuration of power and slave packs with all associated wiring and accessories as required to control the load indicated on drawings.
3. Input Supply Voltage: Dual rated for 120/277 V ac.
4. Load Rating: As required to control the load indicated on drawings.
I. Power Packs for Wireless Occupancy Sensors:
1. Description: Plenum rated, self-contained relay compatible with specified wireless occupancy sensors for switching of line voltage loads.
2. Input Supply Voltage: Dual rated for 120/277 V ac.
3. Load Rating: As required to control the load indicated on drawings.
4. Provide auxiliary contact closure output where indicated.
5. Rated Life of Relay: One million cycles.
J. Accessories:
Lionakis No. 019124.02 26 09 23
January 26, 2024 Lighting Control Devices
1. Provide heavy duty coated steel wire protective guards compatible with specified occupancy sensors where indicated on plans.
K. OUTDOOR MOTION SENSORS
1. Manufacturers:
a. Acuity Brands, Inc: www.acuitybrands.com/#sle.
b. Hubbell Lighting, Inc: www.hubbelllighting.com/#sle. c. Legrand North America, Inc: www.legrand.us/#sle.
d. RAB Lighting, Inc: www.rablighting.com/#sle.
e. Or approved equal.
f. Substitutions: See Section 01 60 00 - Product Requirements. g. Source Limitations: Furnish products produced by a single manufacturer and obtained from a single supplier.
2. Description: Factory-assembled wet location listed device suitable for wall or ceiling/eave mounting, with integral swivel for field adjustment of coverage, capable of detecting motion for automatic control of load indicated.
3. Sensor Technology: Passive Infrared (PIR) designed to detect occupancy by sensing movement of thermal energy between zones.
4. Operation: Unless otherwise indicated, motion sensor to turn load on when motion is detected and to turn load off when no motion is detected during an adjustable turn-off delay time interval.
5. Turn-Off Delay: Field adjustable, with time delay settings available up to 15 minutes.
6. Integral Photocell: For dusk to dawn operation.
7. Manual Override: Activated by switching power off to unit and then back on.
8. Load Rating: 1,000 W incandescent and fluorescent load at 120 V ac.
9. Coverage: Capable of detecting motion within a distance of 50 feet at a mounting height of 8 feet, with a field of view of 270 degrees.
10. Finish: Color to be selected by architect.
26 09 23 Lionakis No. 019124.02
Lighting Control Devices January 26, 2024
11. Provide integral lamp holders suitable for two 150 watt PAR 38 lamps.
L. TIME SWITCHES
1. Manufacturers:
a. Intermatic, Inc: www.intermatic.com/#sle.
b. Tork, a division of NSI Industries LLC: www.tork.com/#sle. c. Or approved equal.
d. Substitutions: See Section 01 60 00 - Product Requirements. e. Source Limitations: Furnish products produced by a single manufacturer and obtained from a single supplier.
2. Digital Electronic Time Switches:
a. Description: Factory-assembled solid state programmable controller with LCD display, listed and labeled as complying with UL 916 or UL 917.
b. Program Capability:
1) 24-Hour Time Switches: Single channel, with same schedule for each day of the week and skip-a-day feature to omit selected days.
2) 7-Day Time Switches: Single channel, capable of different schedule for each day of the week with additional holiday schedule available to override normal schedule for selected days. 3) Astronomic Time Switches: Single channel, capable of different schedule for each day of the week with additional holiday schedule available to override normal schedule for selected days and field-configurable astronomic feature to automatically adjust for seasonal changes in sunrise and sunset times.
c. Schedule Capacity: Not less than 16 programmable on/off operations.
d. Provide automatic daylight savings time and leap year compensation. e. Provide power outage backup to retain programming and maintain clock.
Lionakis No. 019124.02 26 09 23
January 26, 2024 Lighting Control Devices
f. Manual override: Capable of overriding current schedule both permanently and temporarily until next scheduled event. g. Provide remote photocell input with light level adjustment. h. Input Supply Voltage: As indicated on the drawings. i. Output Switch Configuration: As required to control the load indicated on drawings.
j. Output Switch Contact Ratings: As required to control the load indicated on drawings.
k. Provide lockable enclosure; environmental type per NEMA 250 as specified for the following installation locations:
1) Indoor clean, dry locations: Type 1.
2) Outdoor locations: Type 3R.
l. Provide flush-mounted unit where indicated, where mounted in public areas, or where mounted adjacent to flush-mounted equipment.
3. Electromechanical Time Switches:
a. Description: Factory-assembled controller with motor-operated timing dial mechanism and adjustable trippers for setting on/off operations, listed and labeled as complying with UL 917.
b. Program Capability:
1) 24-Hour Time Switches: With same schedule for each day of the week and skip-a-day feature to omit selected days.
2) 7-Day Time Switches: Capable of different schedule for each day of the week.
3) Astronomic Time Switches: With same schedule for each day of the week and skip-a-day feature to omit selected days with automatic adjustment for seasonal changes in sunrise and sunset times.
c. Schedule Capacity:
1) 24-Hour Time Switches: Accommodating not less than 12 pairs of selected on/off operations per day.
26 09 23 Lionakis No. 019124.02
Lighting Control Devices January 26, 2024
2) 7-Day Time Switches: Accommodating not less than two pairs of selected on/off operations per day.
3) Astronomic Time Switches: Capable of turning load on at sunset and off at either sunrise or selected fixed time.
d. Provide spring reserve backup to maintain clock during power outage. e. Manual override: Capable of overriding current schedule both permanently and temporarily until next scheduled event. f. Input Supply Voltage: As indicated on the drawings. g. Output Switch Configuration: As required to control the load indicated on drawings.
h. Output Switch Contact Ratings: As required to control the load indicated on drawings.
i. Provide lockable enclosure; environmental type per NEMA 250 as specified for the following installation locations:
1) Indoor clean, dry locations: Type 1.
2) Outdoor locations: Type 3R.
j. Provide flush-mounted unit where indicated, where mounted in public areas, or where mounted adjacent to flush-mounted equipment.
M. IN-WALL TIME SWITCHES
1. Manufacturers:
a. Intermatic, Inc: www.intermatic.com/#sle.
b. Tork, a division of NSI Industries LLC: www.tork.com/#sle. c. Or approved equal.
d. Substitutions: See Section 01 60 00 - Product Requirements. e. Source Limitations: Furnish products produced by a single manufacturer and obtained from a single supplier.
2. Digital Electronic In-Wall Time Switches:
a. Description: Factory-assembled solid state programmable controller with LCD display, suitable for mounting in standard wall box, and listed and labeled as complying with UL 916 or UL 917.
Lionakis No. 019124.02 26 09 23
January 26, 2024 Lighting Control Devices
b. Program Capability:
1) 7-Day Time Switches: Capable of different schedule for each day of the week.
2) Astronomic Time Switches: Capable of different schedule for each day of the week and field-configurable astronomic feature to automatically adjust for seasonal changes in sunrise and sunset times.
c. Schedule Capacity: Not less than 40 programmable on/off operations.
d. Provide automatic daylight savings time compensation. e. Provide power outage backup to retain programming and maintain clock.
f. Manual override: Capable of overriding current schedule both permanently and temporarily until next scheduled event. g. Switch Configuration: Suitable for use in either SPST or 3-way application.
h. Contact Ratings: As required to control the load indicated on drawings.
3. Electromechanical In-Wall Time Switches:
a. Description: Factory-assembled controller with motor-operated timing dial mechanism and adjustable trippers for setting on/off operations, suitable for mounting in standard wall box, and listed and labeled as complying with UL 917.
b. Program Capability: 24-hour time switch with same schedule for each day of the week.
c. Schedule Capacity: Accommodating not less than 24 selected on/off operations per day.
d. Manual override: Capable of permanently overriding current schedule.
e. Switch Configuration: SPST.
f. Contact Ratings: As required to control the load indicated on drawings.
26 09 23 Lionakis No. 019124.02
Lighting Control Devices January 26, 2024
N. IN-WALL INTERVAL TIMERS
1. Manufacturers:
a. Intermatic, Inc: www.intermatic.com/#sle.
b. Tork, a division of NSI Industries LLC: www.tork.com/#sle. c. Or approved equal.
d. Substitutions: See Section 01 60 00 - Product Requirements. e. Source Limitations: Furnish products produced by a single manufacturer and obtained from a single supplier.
2. Digital Electronic In-Wall Interval Timers:
a. Description: Factory-assembled solid state programmable controller with LCD display, suitable for mounting in standard wall box, and listed and labeled as complying with UL 916 or UL 917.
b. Program Capability: Designed to turn load off at end of preset time interval.
c. Time Interval: Field selectable range of presets available up to 12 hours.
d. Provide field selectable audible and visual indication to warn that end of interval operation is about to turn off load.
e. Provide power outage backup to retain programming and maintain clock.
f. Manual override: Capable of both turning load off and resetting timer to original preset time interval.
g. Switch Configuration: Suitable for use in either SPST or 3-way application.
h. Contact Ratings: As required to control the load indicated on drawings.
3. Spring Wound In-Wall Interval Timers:
Lionakis No. 019124.02 26 09 23
January 26, 2024 Lighting Control Devices
a. Description: Factory-assembled controller with mechanical spring wound timing mechanism requiring no electricity to operate; suitable for mounting in standard wall box; rotary control operator with matching wall plate factory marked with time interval units; listed and labeled as complying with UL 916 or UL 917.
b. Program Capability: Designed to turn load off at end of preset time interval.
c. Time Interval: User selectable from zero up to 15 minutes. d. Manual override: Provide hold feature to disable timer for constant on operation.
e. Switch Configuration: SPST.
f. Contact Ratings: As required to control the load indicated on drawings.
O. OUTDOOR PHOTO CONTROLS
1. Manufacturers:
a. Intermatic, Inc: www.intermatic.com/#sle.
b. Tork, a division of NSI Industries LLC: www.tork.com/#sle. c. Substitutions: See Section 01 60 00 - Product Requirements. d. Source Limitations: Furnish products produced by a single manufacturer and obtained from a single supplier.
2. Stem-Mounted Outdoor Photo Controls:
a. Description: Direct-wired photo control unit with threaded conduit mounting stem and field-adjustable swivel base, listed and labeled as complying with UL 773A.
b. Housing: Weatherproof, impact resistant polycarbonate. c. Photo Sensor: Cadmium sulfide.
d. Provide external sliding shield for field adjustment of light level activation.
e. Light Level Activation: 1 to 5 footcandles turn-on and 3 to 1 turn-off to turn-on ratio with delayed turn-off.
26 09 23 Lionakis No. 019124.02
Lighting Control Devices January 26, 2024
f. Voltage: As required to control the load indicated on the drawings. g. Failure Mode: Fails to the on position.
h. Load Rating: As required to control the load indicated on the drawings.
i. Provide accessory wall-mounting bracket where indicated or as required to complete installation.
3. Locking Receptacle-Mounted Outdoor Photo Controls
a. Description: Plug-in locking type photo control unit complying with ANSI C136.10 for mounting on a compatible receptacle, listed and labeled as complying with UL 773.
b. Housing: Weatherproof, impact resistant UV stabilized polypropylene, color to be selected.
c. Photo Sensor: Cadmium sulfide.
d. Light Level Activation: 1 to 3 footcandles turn-on and 1.5 to 1 turn-off to turn-on ratio with instant turn-on and delayed turn-off. e. Voltage: As required to control the load indicated on the drawings. f. Failure Mode: Fails to the on position.
g. Load Rating: As required to control the load indicated on the drawings.
h. Surge Protection: 160 joule metal oxide varistor.
i. Provide the following accessories where indicated or as required to complete installation:
1) Receptacle: Complying with ANSI C136.10.
2) Mounting Bracket.
3) Shorting Cap: Suitable for replacing locking photo control to complete circuit.
4. Button Type Outdoor Photo Controls
a. Description: Direct-wired photo control unit complying with ANSI C136.24 with weatherproof gasketed wall plate where required or indicated, listed and labeled as complying with UL 773A.
Lionakis No. 019124.02 26 09 23
January 26, 2024 Lighting Control Devices
b. Housing: Weather resistant polycarbonate.
c. Photo Sensor: Cadmium sulfide.
d. Light Level Activation: 1 to 3 footcandles turn-on and 3 to 1 turn-off to turn-on ratio with delayed turn-off.
e. Voltage: As required to control the load indicated on the drawings. f. Failure Mode: Fails to the on position.
g. Load Rating: As required to control the load indicated on the drawings.
P. DAYLIGHTING CONTROLS
1. Manufacturers:
a. Hubbell Control
Solutions: www.hubbell.com/hubbellcontrolsolutions/en/#sle. b. Lutron Electronics Company, Inc: www.lutron.com/#sle. c. Sensor Switch Inc: www.sensorswitch.com/#sle.
d. WattStopper: www.wattstopper.com/#sle.
e. Or approved equal.
f. Substitutions: See Section 01 60 00 - Product Requirements. g. Source Limitations: Furnish products produced by a single manufacturer and obtained from a single supplier.
2. System Description: Control system consisting of photo sensors and compatible control modules and power packs, contactors, or relays as required for automatic control of load indicated according to available natural light; capable of integrating with occupancy sensors and manual override controls.
3. Daylighting Control Photo Sensors: Low voltage class 2 photo sensor units with output signal proportional to the measured light level and provision for zero or offset based signal.
a. Sensor Type: Filtered silicon photo diode.
b. Sensor Range:
1) Indoor Photo Sensors: 5 to 100 footcandles.
26 09 23 Lionakis No. 019124.02
Lighting Control Devices January 26, 2024
2) Outdoor Photo Sensors: 5 to 250 footcandles.
3) Atrium Photo Sensors: 200 to 2,500 footcandles.
4) Skylight Photo Sensors: 1,000 to 6,000 footcandles. 5) Open Loop Photo Sensors: 3 to 6,000 footcandles.
c. Finish: White unless otherwise indicated.
4. Where wired sensors are indicated, wireless sensors are acceptable provided that all components and wiring modifications necessary for proper operation are included.
5. Wireless Daylighting Control Photo Sensors:
a. RF Range: 30 feet through typical construction materials. b. Electromagnetic Interference/Radio Frequency Interference (EMI/RFI) Limits: Comply with FCC requirements of 47 CFR 15, for Class B application.
c. Power: Battery-operated with minimum ten-year battery life.
6. Dimming Photo Sensors: Photo sensor units with integral controller compatible with specified dimming ballasts, for direct continuous dimming of up to 50 ballasts.
7. Daylighting Control Switching Modules for Low Voltage Sensors: Low voltage class 2 control unit compatible with specified photo sensors, for switching of compatible power packs, contactors, or relays in response to changes in measured light levels according to selected settings. a. Operation: Unless otherwise indicated, load to be turned on when light level is below selected low set point and load to be turned off when light level is above selected high set point, with a no switching dead band between set points to prevent unwanted cycling. b. Input Delay: To prevent unwanted cycling due to intermittent light level fluctuations.
c. Control Capability:
1) Single Zone Switching Modules: Capable of controlling one programmable channel.
2) Multi-Zone Switching Modules: Capable of controlling up to three separately programmable channels.
Lionakis No. 019124.02 26 09 23
January 26, 2024 Lighting Control Devices
Q. Daylighting Control Switching Modules for Wireless Sensors:
1. Description: Plenum rated, self-contained relay compatible with specified wireless photo sensors for switching of line voltage loads in response to changes in measured light levels according to selected settings.
2. Operation: Unless otherwise indicated, load to be turned on when light level is below selected low set point and load to be turned off when light level is above selected high set point, with a no switching dead band between set points to prevent unwanted cycling.
3. Input Delay: To prevent unwanted cycling due to intermittent light level fluctuations.
4. Control Capability: Capable of controlling one programmable channel.
5. Input Supply Voltage: Dual rated for 120/277 V ac.
6. Load Rating: As required to control the load indicated on drawings.
7. Provide auxiliary contact closure output where indicated.
8. Rated Life of Relay: One million cycles.
9. Daylighting Control Dimming Modules for Low Voltage Sensors: Low voltage class 2 control unit compatible with specified photo sensors and with specified dimming ballasts, for both continuous dimming of compatible dimming ballasts and switching of compatible power packs, contactors, or relays in response to changes in measured light levels according to selected settings.
a. Operation: Unless otherwise indicated, specified load to be continuously brightened as not enough daylight becomes available and continuously dimmed as enough daylight becomes available. b. Load to be turned off when available daylight is sufficient to fully dim the load, after the selected time delay.
c. Control Capability: Capable of controlling up to three separately programmable channels, with up to 50 ballasts per channel. d. Dimming and Fade Rates: Adjustable from 5 to 60 seconds. e. Cut-Off Delay: Selectable and adjustable from 0 to 20 minutes. f. Output Voltage: Compatible with specified dimming ballasts.
R. Daylighting Control Dimming Modules for Wireless Sensors:
26 09 23 Lionakis No. 019124.02
Lighting Control Devices January 26, 2024
1. Description: Plenum rated control unit compatible with specified wireless photo sensors and with specified dimming ballasts, for continuous dimming of compatible dimming ballasts in response to changes in measured light levels according to selected settings.
2. Operation: Unless otherwise indicated, specified load to be continuously brightened as not enough daylight becomes available and continuously dimmed as enough daylight becomes available.
3. Load to be turned off when available daylight is sufficient to fully dim the load, after the selected time delay.
4. Control Capability: Capable of controlling up to 32 ballasts with up to two separately programmable daylighting zones.
5. Power Packs for Low Voltage Daylighting Control Modules:
a. Description: Plenum rated, self-contained low voltage class 2 transformer and relay compatible with specified low voltage daylighting control modules for switching of line voltage loads. Provide quantity and configuration of power and slave packs with all associated wiring and accessories as required to control the load indicated on drawings.
b. Input Supply Voltage: Dual rated for 120/277 V ac.
6. Load Ratings: As required to control the load indicated on drawings.
7. Accessories:
a. Where indicated, provide compatible accessory wall switches for manual override control.
8. Where indicated, provide compatible accessory wireless controls for manual override control.
S. LIGHTING CONTACTORS
1. Manufacturers:
a. ABB/GE: www.geindustrial.com/#sle.
b. Eaton Corporation: www.eaton.com/#sle.
c. Rockwell Automation Inc; Allen-Bradley
Products: ab.rockwellautomation.com/#sle.
Lionakis No. 019124.02 26 09 23
January 26, 2024 Lighting Control Devices
d. Schneider Electric; Square D Products: www.schneider- electric.us/#sle.
e. Siemens Industry, Inc: www.usa.siemens.com/#sle.
f. Or approved equal.
g. Substitutions: See Section 01 60 00 - Product Requirements.
2. Description: Magnetic lighting contactors complying with NEMA ICS 2, and listed and labeled as complying with UL 60947-1 and UL 60947-4-1; noncombination type unless otherwise indicated; ratings, configurations and features as indicated on the drawings.
3. Combination Contactors: NEMA ICS 2, Class A combination controllers with magnetic contactor(s) and externally operable disconnect. a. Disconnects: Circuit breaker type.
1) Disconnect Switches: Fusible type unless otherwise indicated. 2) Provide externally operable handle with means for locking in the OFF position. Provide safety interlock to prevent opening the cover with the disconnect in the ON position with capability of overriding interlock for testing purposes.
3) Provide auxiliary interlock for disconnection of external control power sources where applicable.
4. Short Circuit Current Rating:
a. Provide contactors with listed short circuit current rating not less than the available fault current at the installed location as determined by short circuit study performed in accordance with Section 26 05 73.
5. Enclosures:
a. Comply with NEMA ICS 6.
b. Environment Type per NEMA 250: Unless otherwise indicated, as specified for the following installation locations:
1) Indoor Clean, Dry Locations: Type 1 or Type 12.
2) Outdoor Locations: Type 3R or Type 4.
c. Finish: Manufacturer's standard unless otherwise indicated. 26 09 23 Lionakis No. 019124.02
Lighting Control Devices January 26, 2024
T. ACCESSORIES
1. Auxiliary Contacts:
a. Comply with NEMA ICS 5.
b. Provide number and type of contacts indicated or required to perform necessary functions, including holding (seal-in) circuit and interlocking, plus one normally open (NO) and one normally closed (NC) spare contact for each lighting contactor, minimum.
2. Pilot Devices:
a. Comply with NEMA ICS 5; heavy-duty type.
b. Nominal Size: 30 mm.
c. Pushbuttons: Unless otherwise indicated, provide momentary, non- illuminated type with flush button operator; normally open or normally closed as indicated or as required.
d. Selector Switches: Unless otherwise indicated, provide maintained, non-illuminated type with knob operator; number of switch positions as indicated or as required.
e. Indicating Lights: Push-to-test type unless otherwise indicated. f. Provide LED lamp source for indicating lights and illuminated devices.
3. Control and Timing Relays:
a. Comply with NEMA ICS 5.
b. Provide number and type of relays indicated or required to perform necessary functions.
c. Timing Relays: Electronic or pneumatic as indicated. 1) Adjustable Timing Range: As indicated on drawings.
4. Fire-Rated Device Enclosures:
a. Manufacturers:
1) Fire Rated Product Specialties Corp: www.frpsonline.com/#sle. 2) Or approved equal.
3) Substitutions: See Section 01 60 00 - Product Requirements.
Lionakis No. 019124.02 26 09 23
January 26, 2024 Lighting Control Devices
b. Provide as required to preserve fire resistance rating of building elements.
PART 3 EXECUTION
3.1 EXAMINATION
A. Verify that field measurements are as indicated.
B. Verify that outlet boxes are installed in proper locations and at proper mounting heights and are properly sized to accommodate devices and conductors in accordance with CEC 2007.
C. Verify that openings for outlet boxes are neatly cut and will be completely covered by devices or wall plates.
D. Verify that final surface finishes are complete, including painting.
E. Verify that branch circuit wiring installation is completed, tested, and ready for connection to lighting control devices.
F. Verify that the service voltage and ratings of lighting control devices are appropriate for the service voltage and load requirements at the location to be installed.
G. Verify that conditions are satisfactory for installation prior to starting work.
3.2 PREPARATION
A. Provide extension rings to bring outlet boxes flush with finished surface.
B. Clean dirt, debris, plaster, and other foreign materials from outlet boxes.
3.3 INSTALLATION
A. Install lighting control devices in accordance with NECA 1 (general workmanship) and, where applicable, NECA 130, including mounting heights specified in those standards unless otherwise indicated.
B. Perform work in a neat and workmanlike manner in accordance with NECA 1, including mounting heights specified in that standard unless otherwise indicated
C. Coordinate locations of outlet boxes provided under Section 26 05 33.16 as required for installation of lighting control devices provided under this section.
1. Orient outlet boxes for vertical installation of lighting control devices unless otherwise indicated.
26 09 23 Lionakis No. 019124.02
Lighting Control Devices January 26, 2024
2. Locate wall switch occupancy sensors on strike side of door with edge of wall plate 3 inches from edge of door frame. Where locations are indicated otherwise, notify Architect and/or Owner's Representative to obtain direction prior to proceeding with work.
D. Install lighting control devices in accordance with manufacturer's instructions.
E. Unless otherwise indicated, connect lighting control device grounding terminal or conductor to branch circuit equipment grounding conductor and to outlet box with bonding jumper.
F. Install lighting control devices plumb and level, and held securely in place.
G. Where required and not furnished with lighting control device, provide wall plate in accordance with Section 26 27 26.
H. Provide required supports in accordance with Section 26 05 29.
I. Where applicable, install lighting control devices and associated wall plates to fit completely flush to mounting surface with no gaps and rough opening completely covered without strain on wall plate. Repair or reinstall improperly installed outlet boxes or improperly sized rough openings. Do not use oversized wall plates in lieu of meeting this requirement.
J. Identify lighting control devices in accordance with Section 26 05 53.
K. Occupancy Sensor Locations:
1. Location Adjustments: Locations indicated are diagrammatic and only intended to indicate which rooms or areas require devices. Provide quantity and locations as required for complete coverage of respective room or area based on manufacturer's recommendations for installed devices.
2. Locate ultrasonic and dual technology passive infrared/ultrasonic occupancy sensors a minimum of 4 feet from air supply ducts or other sources of heavy air flow and as per manufacturer's recommendations, in order to minimize false triggers.
L. Outdoor Photo Control Locations:
1. Where possible, locate outdoor photo controls with photo sensor facing north. If north facing photo sensor is not possible, install with photo sensor facing east, west, or down.
2. Locate outdoor photo controls so that photo sensors do not face artificial light sources, including light sources controlled by the photo control itself.
Lionakis No. 019124.02 26 09 23
January 26, 2024 Lighting Control Devices
M. Install outdoor photo controls so that connections are weatherproof. Do not install photo controls with conduit stem facing up in order to prevent infiltration of water into the photo control.
N. Daylighting Control Photo Sensor Locations:
1. Location Adjustments: Locations indicated are diagrammatic and only intended to indicate which rooms or areas require devices. Provide quantity and locations as required for proper control of respective room or area based on manufacturer's recommendations for installed devices.
2. Unless otherwise indicated, locate photo sensors for closed loop systems to accurately measure the light level controlled at the designated task location, while minimizing the measured amount of direct light from natural or artificial sources such as windows or pendant luminaires.
3. Unless otherwise indicated, locate photo sensors for open loop systems to accurately measure the level of daylight coming into the space, while minimizing the measured amount of lighting from artificial sources.
O. Combination Enclosed Lighting Contactors:
1. Except where indicated to be mounted adjacent to the equipment they supply, mount lighting contactors such that the highest position of the operating handle does not exceed 79 inches above the floor or working platform.
2. Provide fuses complying with Section 26 28 13 for fusible switches as indicated.
P. Lamp Burn-In: Operate lamps at full output for minimum of 100 hours or prescribed period per manufacturer's recommendations prior to use with any dimming controls. Replace lamps that fail prematurely due to improper lamp burn-in.
Q. Unless otherwise indicated, install power packs for lighting control devices above accessible ceiling or above access panel in inaccessible ceiling near the sensor location.
R. Where indicated, install separate compatible wall switches for manual control interface with lighting control devices or associated power packs.
S. Unless otherwise indicated, install switches on load side of power packs so that switch does not turn off power pack.
26 09 23 Lionakis No. 019124.02
Lighting Control Devices January 26, 2024
T. Where indicated or required, provide cabinet or enclosure in accordance with Section 26 05 33.16 for mounting of lighting control device system components.
U. Where indicated or required, provide cabinet or enclosure in accordance with Section 26 2716 for mounting of lighting control device system components.
3.4 FIELD QUALITY CONTROL
A. See Section 01 40 00 - Quality Requirements, for additional requirements.
B. Inspect each lighting control device for damage and defects.
C. Test occupancy sensors to verify proper operation, including time delays and ambient light thresholds where applicable. Verify optimal coverage for entire room or area. Record test results in written report to be included with submittals.
D. Test time switches to verify proper operation.
E. Test outdoor photo controls to verify proper operation, including time delays where applicable.
F. Test daylighting controls to verify proper operation, including light level measurements and time delays where applicable. Record test results in written report to be included with submittals.
G. Correct wiring deficiencies and replace damaged or defective lighting control devices.
3.5 ADJUSTING
A. Adjust devices and wall plates to be flush and level.
B. Adjust occupancy sensor settings to minimize undesired activations while optimizing energy savings, and to achieve desired function as indicated or as directed by manufacturer.
C. Adjust position of directional occupancy sensors and outdoor motion sensors to achieve optimal coverage as required.
D. Where indicated or as directed by Architect, install factory masking material or adjust integral blinders on passive infrared (PIR) and dual technology occupancy sensor lenses to block undesired motion detection.
Lionakis No. 019124.02 26 09 23
January 26, 2024 Lighting Control Devices
E. Adjust time switch settings to achieve desired operation schedule as indicated or as directed by Owner's Representative.. Record settings in written report to be included with submittals.
F. Adjust external sliding shields on outdoor photo controls under optimum lighting conditions to achieve desired turn-on and turn-off activation as indicated or as directed by LP Consulting Engineers, Inc..
G. Adjust daylighting controls under optimum lighting conditions after all room finishes, furniture, and window treatments have been installed to achieve desired operation as indicated or as directed by Architect. Record settings in written report to be included with submittals. Readjust controls calibrated prior to installation of final room finishes, furniture, and window treatments that do not function properly as determined by Ownere's Representative.
3.6 CLEANING
A. Clean exposed surfaces to remove dirt, paint, or other foreign material and restore to match original factory finish.
3.7 COMMISSIONING
A. See Section 01 91 13 - General Commissioning Requirements for commissioning requirements.
3.8 CLOSEOUT ACTIVITIES
A. See Section 01 78 00 - Closeout Submittals, for closeout submittals.
B. See Section 01 79 00 - Demonstration and Training, for additional requirements.
C. Demonstration: Demonstrate proper operation of lighting control devices to District Representative, and correct deficiencies or make adjustments as directed.
D. Training: Train Owner's (Owner's) personnel on operation, adjustment, programming, and maintenance of lighting control devices.
1. Use operation and maintenance manual as training reference, supplemented with additional training materials as required.
2. Provide minimum of two hours of training.
3. Instructor: Qualified contractor familiar with the project and with sufficient knowledge of the installed lighting control devices.
26 09 23 Lionakis No. 019124.02
Lighting Control Devices January 26, 2024
4. Location: At project site.
END OF SECTION 26 09 23
Lionakis No. 019124.02 26 24 16
January 26, 2024 Panelboards
SECTION 26 24 16 - PANELBOARDS
PART 1 GENERAL
1.1 SECTION INCLUDES
A. Power distribution panelboards.
B. Lighting and appliance panelboards.
C. Load centers.
D. Overcurrent protective devices for panelboards.
1.2 RELATED REQUIREMENTS
A. Section 26 05 00 – Common Work Results for Electrical.
B. Section 26 05 26 - Grounding and Bonding for Electrical Systems.
C. Section 26 05 29 - Hangers and Supports for Electrical Systems.
D. Section 26 05 48 - Vibration and Seismic Controls for Electrical Systems.
1. Includes requirements for the seismic qualification of equipment specified in this section.
E. Section 26 05 53 - Identification for Electrical Systems: Identification products and requirements.
F. Section 26 05 73 - Power System Studies: Additional criteria for the selection and adjustment of equipment and associated protective devices specified in this section.
G. Section 26 22 00 - Low-Voltage Transformers: Small power centers with integral primary breaker, transformer, and panelboard.
H. Section 26 27 13 - Electricity Metering: For interface with equipment specified in this section.
I. Section 26 43 00 - Surge Protective Devices.
1.3 REFERENCE STANDARDS
A. FS W-C-375 - Circuit Breakers, Molded Case; Branch Circuit and Service; 2013e, with Amendments (2022).
B. NECA 1 - Standard for Good Workmanship in Electrical Construction; 2015. 26 24 16 Lionakis No. 019124.02
Panelboards January 26, 2024
C. NECA 407 - Standard for Installing and Maintaining Panelboards; 2015.
D. NEMA 250 - Enclosures for Electrical Equipment (1000 Volts Maximum); 2020.
E. NEMA ICS 2 - Industrial Control and Systems Controllers, Contactors and Overload Relays Rated 600 Volts; 2008 (Reaffirmed 2020).
F. NEMA KS 1 - Heavy Duty Enclosed and Dead-Front Switches (600 Volts Maximum); 2013.
G. NEMA PB 1 - Panelboards; 2011.
H. NEMA PB 1.1 - General Instructions for Proper Installation, Operation and Maintenance of Panelboards Rated 1000 Volts or Less; 2023.
I. NETA ATS - Standard For Acceptance Testing Specifications For Electrical Power Equipment And Systems; 2021.
J. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.
K. UL 50 - Enclosures for Electrical Equipment, Non-Environmental Considerations; Current Edition, Including All Revisions.
L. UL 50E - Enclosures for Electrical Equipment, Environmental Considerations; Current Edition, Including All Revisions.
M. UL 67 - Panelboards; Current Edition, Including All Revisions.
N. UL 98 - Enclosed and Dead-Front Switches; Current Edition, Including All Revisions.
O. UL 489 - Molded-Case Circuit Breakers, Molded-Case Switches and Circuit Breaker Enclosures; Current Edition, Including All Revisions.
P. UL 869A - Reference Standard for Service Equipment; Current Edition, Including All Revisions.
Q. UL 943 - Ground-Fault Circuit-Interrupters; Current Edition, Including All Revisions.
R. UL 1053 - Ground-Fault Sensing and Relaying Equipment; Current Edition, Including All Revisions.
S. UL 1699 - Arc-Fault Circuit-Interrupters; Current Edition, Including All Revisions.
Lionakis No. 019124.02 26 24 16
January 26, 2024 Panelboards
1.4 ADMINISTRATIVE REQUIREMENTS
A. Coordination:
1. Coordinate the work with other trades to avoid placement of ductwork, piping, equipment, or other potential obstructions within the dedicated equipment spaces and working clearances for electrical equipment required by NFPA 70.
2. Coordinate arrangement of electrical equipment with the dimensions and clearance requirements of the actual equipment to be installed.
3. Coordinate the work with other trades to provide walls suitable for installation of flush-mounted panelboards where indicated.
4. Verify with manufacturer that conductor terminations are suitable for use with the conductors to be installed.
5. Notify LP Consulting Engineers, Inc. of any conflicts with or deviations from Contract Documents. Obtain direction before proceeding with work.
1.5 SUBMITTALS
A. See Section 01 30 00 - Administrative Requirements, for submittal procedures.
B. Product Data: Provide manufacturer's standard catalog pages and data sheets for panelboards, enclosures, overcurrent protective devices, and other installed components and accessories.
1. Include characteristic trip curves for each type and rating of overcurrent protective device upon request.
C. Shop Drawings: Indicate outline and support point dimensions, voltage, main bus ampacity, overcurrent protective device arrangement and sizes, short circuit current ratings, conduit entry locations, conductor terminal information, and installed features and accessories.
1. Include dimensioned plan and elevation views of panelboards and adjacent equipment with all required clearances indicated.
2. Include wiring diagrams showing all factory and field connections.
3. Clearly indicate whether proposed short circuit current ratings are fully rated or, where acceptable, series rated systems.
4. Include documentation of listed series ratings upon request. 26 24 16 Lionakis No. 019124.02
Panelboards January 26, 2024
5. Identify mounting conditions required for equipment seismic qualification.
D. Manufacturer's equipment seismic qualification certification.
E. Source Quality Control Test Reports: Include reports for tests designated in NEMA PB 1 as routine tests.
F. Field Quality Control Test Reports.
G. Manufacturer's Installation Instructions: Indicate application conditions and limitations of use stipulated by product testing agency. Include instructions for storage, handling, protection, examination, preparation, and installation of product.
H. Project Record Documents: Record actual installed locations of panelboards and actual installed circuiting arrangements.
I. Maintenance Data: Include information on replacement parts and recommended maintenance procedures and intervals.
J. Maintenance Materials: Furnish the following for Owner's (Owner's) use in maintenance of project.
1. See Section 01 60 00 - Product Requirements, for additional provisions.
2. Panelboard Keys: Two of each different key.
1.6 QUALITY ASSURANCE
A. Conform to requirements of CEC.
B. Conform to requirements of NFPA 70.
C. Maintain at the project site a copy of each referenced document that prescribes execution requirements.
D. Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum five years documented experience.
E. Product Listing Organization Qualifications: An organization recognized by OSHA as a Nationally Recognized Testing Laboratory (NRTL) and acceptable to authorities having jurisdiction.
1.7 DELIVERY, STORAGE, AND HANDLING
A. Receive, inspect, handle, and store panelboards in accordance with manufacturer's instructions and NECA 407.
Lionakis No. 019124.02 26 24 16
January 26, 2024 Panelboards
B. Store in a clean, dry space. Maintain factory wrapping or provide an additional heavy canvas or heavy plastic cover to protect units from dirt, water, construction debris, and traffic.
C. Handle carefully in accordance with manufacturer's written instructions to avoid damage to panelboard internal components, enclosure, and finish.
1.8 FIELD CONDITIONS
A. Maintain ambient temperature within the following limits during and after installation of panelboards:
1. Panelboards Containing Circuit Breakers: Between 23 degrees F and 104 degrees F.
PART 2 PRODUCTS
2.1 MANUFACTURERS
A. ABB: www.electrification.us.abb.com/#sle.
B. Eaton Corporation: www.eaton.com/#sle.
C. Schneider Electric; Square D Products
D. Siemens Industry, Inc: www.usa.siemens.com/#sle.
E. Or approved equivalent subject to substitution process F. Substitutions: See Section 01 60 00 - Product Requirements.
G. Source Limitations: Furnish panelboards and associated components produced by the same manufacturer as the other electrical distribution equipment used for this project and obtained from a single supplier.
2.2 PANELBOARDS - GENERAL REQUIREMENTS
A. Provide products listed, classified, and labeled as suitable for the purpose intended.
B. Seismic Qualification: Provide panelboards and associated components suitable for application under the seismic design criteria specified in Section 26 05 48 where required. Include certification of compliance with submittals.
C. Unless otherwise indicated, provide products suitable for continuous operation under the following service conditions:
1. Altitude: Less than 6,600 feet.
26 24 16 Lionakis No. 019124.02
Panelboards January 26, 2024
2. Ambient Temperature:
a. Panelboards Containing Circuit Breakers: Between 23 degrees F and 104 degrees F.
D. Short Circuit Current Rating:
1. Provide panelboards with listed short circuit current rating not less than the available fault current at the installed location as determined by short circuit study performed in accordance with Section 26 05 73.
2. Listed series ratings are not acceptable, except where pre-appoved by the Owner and LP Consulting Engineers, Inc.
3. Label equipment utilizing series ratings as required by NFPA 70 where permitted.
E. Panelboards Used for Service Entrance: Listed and labeled as suitable for use as service equipment according to UL 869A.
F. Mains: Configure for top or bottom incoming feed as indicated or as required for the installation.
G. Branch Overcurrent Protective Devices: Replaceable without disturbing adjacent devices.
H. Bussing: Sized in accordance with UL 67 temperature rise requirements.
1. Provide fully rated neutral bus unless otherwise indicated, with a suitable lug for each feeder or branch circuit requiring a neutral connection.
2. Provide 200 percent rated neutral bus and lugs where indicated, where oversized neutral conductors are provided, or where panelboards are fed from K-rated transformers.
3. Provide solidly bonded equipment ground bus in each panelboard, with a suitable lug for each feeder and branch circuit equipment grounding conductor.
4. Provide separate isolated/insulated ground bus where indicated or where isolated grounding conductors are provided.
I. Conductor Terminations: Suitable for use with the conductors to be installed.
J. Enclosures: Comply with NEMA 250, and list and label as complying with UL 50 and UL 50E.
Lionakis No. 019124.02 26 24 16
January 26, 2024 Panelboards
1. Environment Type per NEMA 250: Unless otherwise indicated, as specified for the following installation locations:
a. Indoor Clean, Dry Locations: Type 1.
b. Outdoor Locations: Type 3R.
2. Boxes: Galvanized steel unless otherwise indicated. a. Provide wiring gutters sized to accommodate the conductors to be installed.
b. Increase gutter space as required where sub-feed lugs, feed-through lugs, gutter taps, or oversized lugs are provided.
c. Provide removable end walls for NEMA Type 1 enclosures. d. Provide painted steel boxes for surface-mounted panelboards where indicated, finish to match fronts.
3. Fronts:
a. Fronts for Surface-Mounted Enclosures: Same dimensions as boxes. b. Fronts for Flush-Mounted Enclosures: Overlap boxes on all sides to conceal rough opening.
c. Finish for Painted Steel Fronts: Manufacturer's standard grey unless otherwise indicated.
4. Lockable Doors: All locks keyed alike unless otherwise indicated. Provide door-in-door construction.
K. Future Provisions: Prepare all unused spaces for future installation of devices including bussing, connectors, mounting hardware and all other required provisions.
L. Surge Protective Devices: Where factory-installed, internally mounted surge protective devices are provided in accordance with Section 26 43 00, list and label panelboards as a complete assembly including surge protective device.
M. Panelboard Contactors: Where panelboard contactors are indicated, provide electrically operated, mechanically held magnetic contactor complying with NEMA ICS 2.
1. Ampere Rating: Not less than ampere rating of panelboard bus. 26 24 16 Lionakis No. 019124.02
Panelboards January 26, 2024
2. Short Circuit Current Rating: Not less than the panelboard short circuit current rating.
3. Coil Voltage: As required for connection to control system indicated.
N. Ground Fault Protection: Where ground-fault protection is indicated, provide system listed and labeled as complying with UL 1053.
1. Where electronic circuit breakers equipped with integral ground fault protection are used, provide separate neutral current sensor where applicable.
2. Where accessory ground fault sensing and relaying equipment is used, equip companion overcurrent protective devices with ground-fault shunt trips.
a. Use zero sequence ground fault detection method unless otherwise indicated.
b. Provide test panel and field-adjustable ground fault pick-up and delay settings.
c. Provide zone selective interlocking capability where indicated, capable of communicating with other electronic trip circuit breakers and external ground fault sensing systems to control ground fault delay functions for system coordination purposes.
O. Selectivity: Where the requirement for selectivity is indicated, furnish products as required to achieve selective coordination.
P. Multi-Section Panelboards: Provide enclosures of the same height, with feed-through lugs or sub-feed lugs and feeders as indicated or as required to interconnect sections.
Q. Provide the following features and accessories where indicated or where required to complete installation:
1. Feed-through lugs.
2. Sub-feed lugs.
2.3 POWER DISTRIBUTION PANELBOARDS
A. Description: Panelboards complying with NEMA PB 1, power and feeder distribution type, circuit breaker type, and listed and labeled as complying with UL 67; ratings, configurations and features as indicated on the drawings.
Lionakis No. 019124.02 26 24 16
January 26, 2024 Panelboards
B. Conductor Terminations:
1. Main and Neutral Lug Material: Suitable for terminating aluminum or copper conductors.
2. Main and Neutral Lug Type: Mechanical.
a. Provide an individual terminal or lug for each neutral wire.
C. Bussing:
1. Phase and Neutral Bus Material: Copper.
2. Ground Bus Material: Copper.
D. Circuit Breakers:
1. Provide bolt-on type.
2. Provide thermal magnetic circuit breakers unless otherwise indicated.
3. Provide electronic trip circuit breakers where indicated.
E. Enclosures:
1. Provide surface-mounted or flush-mounted enclosures unless otherwise indicated.
2. Fronts: Provide trims to cover access to load terminals, wiring gutters, and other live parts, with exposed access to overcurrent protective device handles.
3. Fronts: Provide lockable hinged door with concealed hinges for access to overcurrent protective device handles without exposing live parts.
4. Fronts: Provide door-in-door trim with hinged cover for access to load terminals and wiring gutters, and separate lockable hinged door with concealed hinges for access to overcurrent protective device handles without exposing live parts.
5. Provide clear plastic circuit directory holder mounted on inside of door.
6. Painted gray over rust inhibiting primer.
F. Description: NEMA PB 1, circuit breaker type.
G. Panelboard Bus: Copper, ratings as indicated. Provide copper ground bus in each panelboard.
26 24 16 Lionakis No. 019124.02
Panelboards January 26, 2024
H. Minimum integrated short circuit rating: As indicated or as required by the short circuit study.
1. 240 Volt Panelboards: amperes rms symmetrical per plan.
2. 480 Volt Panelboards: amperes rms symmetrical per plan.
I. Molded Case Circuit Breakers: With integral thermal and instantaneous magnetic trip in each pole; UL listed. For air conditioning equipment branch circuits provide circuit breakers UL listed as Type HACR.
J. Controllers: NEMA ICS 2, AC general-purpose Class A magnetic controller for induction motors rated in horsepower, with bimetal overload relay.
1. Coil operating voltage: 120 volts, 60 Hz.
2. Size as shown on Drawings.
K. Circuit Breaker Accessories: Trip units and auxiliary switches as indicated.
L. Enclosure: NEMA PB 1, Type 1, 6 inches deep, 20 inches wide, cabinet box.
M. Cabinet Front: Surface type, fastened with screws, hinged door with flush lock, metal directory frame, finished in manufacturer's standard gray enamel.
N. Nameplate: Provide factory nameplate to include the following:
1. Manufacturer.
2. Order number.
3. Panelboard Type.
4. System Voltage.
5. Bus ampacity.
6. Short circuit bracing rating.
7. UL label.
8. Service entrance label. (if applicable)
2.4 LIGHTING AND APPLIANCE PANELBOARDS
A. Description: Panelboards complying with NEMA PB 1, lighting and appliance branch circuit type, circuit breaker type, and listed and labeled as complying with UL 67; ratings, configurations and features as indicated on the drawings.
Lionakis No. 019124.02 26 24 16
January 26, 2024 Panelboards
B. Conductor Terminations:
1. Main and Neutral Lug Material: Suitable for terminating aluminum or copper conductors. .
2. Main and Neutral Lug Type: Mechanical.
a. Provide an individual terminal or lug for each neutral wire.
C. Bussing:
1. Phase Bus Connections: Arranged for sequential phasing of overcurrent protective devices.
2. Phase and Neutral Bus Material: Copper.
3. Ground Bus Material: Copper.
D. Circuit Breakers: Thermal magnetic bolt-on type unless otherwise indicated.
E. Enclosures:
1. Provide surface-mounted or flush-mounted enclosures as indicated.
2. Fronts: Provide lockable hinged door with concealed hinges for access to overcurrent protective device handles without exposing live parts.
3. Fronts: Provide door-in-door trim with hinged cover for access to load terminals and wiring gutters, and separate lockable hinged door with concealed hinges for access to overcurrent protective device handles without exposing live parts.
4. Provide clear plastic circuit directory holder mounted on inside of door.
F. Provide column-width panelboards with accessory column-width cable trough and pullbox where indicated.
G. Description: NEMA PB1, circuit breaker type, lighting and appliance branch circuit panelboard.
H. Panelboard Bus: Copper, ratings as indicated. Provide copper ground bus in each panelboard ; provide insulated ground bus where scheduled.
I. Minimum Integrated Short Circuit Rating: As indicated or as required by the short circuit study.
1. 240 Volt Panelboards: 10,000 amperes rms symmetrical.
2. 480 Volt Panelboards: 14,000 amperes rms symmetrical. 26 24 16 Lionakis No. 019124.02
Panelboards January 26, 2024
J. Molded Case Circuit Breakers: Thermal magnetic trip circuit breakers, bolt- on type, with common trip handle for all poles; UL listed.
1. Type SWD for lighting circuits.
2. Type HACR for air conditioning equipment circuits.
3. Class A ground fault interrupter circuit breakers where scheduled.
4. Do not use tandem circuit breakers.
K. Enclosure: NEMA PB 1, Type 1.
L. Cabinet Box: 6 inches deep, 20 inches wide for 240 volt and less panelboards, 20 inches wide for 480 volt panelboards.
M. Cabinet Front: Flush cabinet front with concealed trim clamps, concealed hinge, metal directory frame, and flush lock all keyed alike. Finish in manufacturer's standard gray enamel.
N. Special Features:
1. Provide blocking clips or lock-off devices on circuit breakers as indicated on the drawings.
2. Provide barriered space for mounting contactors and control devices with a hinged door and lock, where shown or required.
3. Provide neutral bars with terminal for all active, spare, and inactive circuits.
4. Provide feed-thru lugs or sub-feed lugs for 2 and 3 section panels.
5. Equip bus bars for panelboard with main lugs, main fused switch, or main circuit breaker, capacity as required or as indicated.
6. Provide special features such as split bus, lighting contactors, extra-wide gutters as required or as indicated.
7. Provide panels with individual branch circuit power metering where noted on plans for connections to Facility Energy Management System. Provide Square D type NFMVP, NQMVP or approved equal.
2.5 LOAD CENTERS
A. Description: Circuit breaker type load centers listed and labeled as complying with UL 67; ratings, configurations, and features as indicated on the drawings.
Lionakis No. 019124.02 26 24 16
January 26, 2024 Panelboards
1. Load centers are permitted only where called for specifically on the drawings
B. Manufacturers:
1. Square D.
2. Siemens.
3. Cutler-Hammer.
4. Or approved equal.
5. Substitutions: See Section 01 60 00 - Product Requirements.
C. Bussing:
1. Phase Bus Connections: Arranged for sequential phasing of overcurrent protective devices.
2. Bus Material: Copper.
D. Circuit Breakers: Thermal magnetic plug-in type, quantity and ratings as indicated on drawings..
E. Enclosures:
1. Provide flush-mounted enclosures unless otherwise indicated.
2. Fronts: Provide cover without door to cover access to load terminals, wiring gutters, and other live parts, with exposed access to overcurrent protective device handles.
3. Fronts: Provide hinged door with concealed hinges for access to overcurrent protective device handles without exposing live parts.
4. Provide circuit directory label on inside of door or individual circuit labels adjacent to circuit breakers.
5. Provide NEMA 3R enclosure where installed outdoors.
2.6 SOURCE QUALITY CONTROL
A. See Section 01 40 00 - Quality Requirements, for additional requirements.
B. Factory test panelboards according to NEMA PB 1.
26 24 16 Lionakis No. 019124.02
Panelboards January 26, 2024
PART 3 EXECUTION
3.1 EXAMINATION
A. Verify that field measurements are as indicated.
B. Verify that the ratings and configurations of the panelboards and associated components are consistent with the indicated requirements.
C. Verify that mounting surfaces are ready to receive panelboards.
D. Verify that conditions are satisfactory for installation prior to starting work.
3.2 INSTALLATION
A. Perform work in accordance with NECA 1 (general workmanship).
B. Install products in accordance with manufacturer's instructions.
C. Install panelboards in accordance with NECA 407 and NEMA PB 1.1.
D. Arrange equipment to provide minimum clearances in accordance with manufacturer's instructions and NFPA 70.
E. Provide required support and attachment in accordance with Section 26 05
29. F. Provide required seismic controls in accordance with Section 26 05 48.
G. Install panelboards plumb and when recessed, flush with wall finishes.
Provide all backing for equipment support. Fasten all free-standing equipment to concrete slab. Mounting bolts on floor mounted panels shall extend into pads only and shall not be in direct contact with building structural members.
H. Install flush-mounted panelboards so that trims fit completely flush to wall with no gaps and rough opening completely covered.
I. Mount panelboards such that the highest position of any operating handle for circuit breakers or switches does not exceed 79 inches above the floor or working platform.
J. Mount floor-mounted power distribution panelboards on properly sized 3 inch high concrete pad constructed in accordance with Section 03 30 00.
K. Provide minimum of six spare 1 inch trade size conduits out of each flush- mounted panelboard stubbed into accessible space above ceiling and below floor.
Lionakis No. 019124.02 26 24 16
January 26, 2024 Panelboards
L. Provide grounding and bonding in accordance with Section 26 05 26.
1. Terminate branch circuit equipment grounding conductors on solidly bonded equipment ground bus only. Do not terminate on
isolated/insulated ground bus.
2. Terminate branch circuit isolated grounding conductors on isolated/insulated ground bus only. Do not terminate on solidly bonded equipment ground bus.
M. Install all field-installed branch devices, components, and accessories.
N. Where accessories are not self-powered, provide control power source as indicated or as required to complete installation.
O. Multi-Wire Branch Circuits: Group grounded and ungrounded conductors together in the panelboard as required by NFPA 70.
P. Set field-adjustable circuit breaker tripping function settings as indicated.
Q. Set field-adjustable circuit breaker tripping function settings as determined by overcurrent protective device coordination study performed according to Section 26 05 73.
R. Set field-adjustable ground fault protection pickup and time delay settings as indicated.
S. Install panelboards in accordance with NEMA PB 1.1 and NECA 1.
T. Install panelboards plumb. Install recessed panelboards flush with wall finishes.
U. Height: 6 feet to top of panelboard; install panelboards taller than 6 feet with bottom no more than 4 inches above floor.
V. Provide filler plates to cover unused spaces in panelboards.
W. Provide circuit breaker lock-on devices to prevent unauthorized personnel from de-energizing essential loads where indicated. Also provide for the following:
1. Emergency and night lighting circuits.
2. Fire detection and alarm circuits.
3. Communications equipment circuits.
4. Intrusion detection and access control system circuits. 26 24 16 Lionakis No. 019124.02
Panelboards January 26, 2024
5. Video surveillance system circuits.
X. Identify panelboards in accordance with Section 26 05 53.
Y. Provide computer-generated circuit directory card for each lighting and appliance panelboard and each power distribution panelboard provided with a door, clearly and specifically indicating the loads served. Identify spares and spaces.
Z. Provide typed circuit directory for each branch circuit panelboard. Revise directory to reflect circuiting changes required to balance phase loads.
AA. Provide engraved plastic nameplates under the provisions of Section 26 05
53. BB. Provide arc flash warning labels in accordance with NFPA 70.
CC. Provide spare conduits out of each recessed panelboard to an accessible location above ceiling. Identify each as SPARE.
1. Minimum spare conduits: 6 empty 1 inch.
DD. Ground and bond panelboard enclosure according to Section 26 05 26.
3.3 FIELD QUALITY CONTROL
A. See Section 01 40 00 - Quality Requirements, for additional requirements.
B. Perform field inspection and testing in accordance with Section 01 40 00.
C. Inspect and test in accordance with NETA ATS, except Section 4.
D. Molded Case Circuit Breakers: Perform inspections and tests listed in NETA ATS, Section 7.6.1.1 for all main circuit breakers and circuit breakes larger than 100 amperes.. Tests listed as optional are not required.
E. Ground Fault Protection Systems: Test in accordance with manufacturer's instructions as required by NFPA 70.
1. Perform inspections and tests listed in NETA ATS, Section 7.14. The insulation-resistance test on control wiring listed as optional is not required.
F. Test GFCI circuit breakers to verify proper operation.
G. Test AFCI circuit breakers to verify proper operation.
H. Test shunt trips to verify proper operation.
Lionakis No. 019124.02 26 24 16
January 26, 2024 Panelboards
I. Procure services of a qualified manufacturer's representative to observe installation and assist in inspection, testing, and adjusting. Include manufacturer's reports with field quality control submittals.
J. Correct deficiencies and replace damaged or defective panelboards or associated components.
K. Perform inspections and tests listed in NETA STD ATS, Section 7.5 for switches, Section 7.6 for circuit breakers.
3.4 ADJUSTING
A. Adjust tightness of mechanical and electrical connections to manufacturer's recommended torque settings.
B. Adjust alignment of panelboard fronts.
C. Load Balancing: For each panelboard, rearrange circuits such that the difference between each measured steady state phase load does not exceed 20 percent and adjust circuit directories accordingly. Maintain proper phasing for multi-wire branch circuits.
3.5 CLEANING
A. Clean dirt and debris from panelboard enclosures and components according to manufacturer's instructions.
B. Repair scratched or marred exterior surfaces to match original factory finish.
END OF SECTION 26 24 16
Lionakis No. 019124.02 26 27 26
January 26, 2024 Wiring Devices
SECTION 26 27 26 - WIRING DEVICES
PART 1 GENERAL
1.1 SECTION INCLUDES
A. Wall switches.
B. Wall dimmers.
C. Fan speed controllers.
D. Receptacles.
E. Wall plates and covers.
F. Floor box service fittings.
G. Poke-through assemblies.
H. Access floor boxes.
I. Occupancy sensors
1.2 RELATED REQUIREMENTS
A. Section 09 69 00 - Access Flooring.
B. Section 26 05 00 – Common Work Results for Electrical.
C. Section 26 05 19 - Low-Voltage Electrical Power Conductors and Cables: Manufactured wiring systems for use with access floor boxes with compatible pre-wired connectors.
D. Section 26 05 26 - Grounding and Bonding for Electrical Systems.
E. Section 26 05 33.16 - Boxes for Electrical Systems.
F. Section 26 05 39 - Underfloor Raceways for Electrical Systems.
G. Section 26 05 53 - Identification for Electrical Systems: Identification products and requirements.
H. Section 26 05 83 - Wiring Connections: Cords and plugs for equipment.
I. Section 26 09 23 - Lighting Control Devices: Devices for automatic control of lighting, including occupancy sensors, in-wall time switches, and in-wall interval timers.
26 27 26 Lionakis No. 019124.02
Wiring Devices January 26, 2024
1.3 REFERENCE STANDARDS
A. FS W-C-596 - Connector, Electrical, Power, General Specification for; 2014h, with Amendments (2017).
B. FS W-S-896 - Switches, Toggle (Toggle and Lock), Flush Mounted (General Specification); 2014g, with Amendment (2017).
C. NECA 1 - Standard for Good Workmanship in Electrical Construction; 2015.
D. NECA 130 - Standard for Installing and Maintaining Wiring Devices; 2016.
E. NEMA WD 1 - General Color Requirements for Wiring Devices; 1999 (Reaffirmed 2020).
F. NEMA WD 6 - Wiring Devices - Dimensional Specifications; 2021.
G. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.
H. UL 20 - General-Use Snap Switches; Current Edition, Including All Revisions.
I. UL 498 - Attachment Plugs and Receptacles; Current Edition, Including All Revisions.
J. UL 514D - Cover Plates for Flush-Mounted Wiring Devices; Current Edition, Including All Revisions.
K. UL 943 - Ground-Fault Circuit-Interrupters; Current Edition, Including All Revisions.
L. UL 1310 - Class 2 Power Units; Current Edition, Including All Revisions.
M. UL 1449 - Standard for Surge Protective Devices; Current Edition, Including All Revisions.
N. UL 1472 - Solid-State Dimming Controls; Current Edition, Including All Revisions.
O. UL 1917 - Solid-State Fan Speed Controls; Current Edition, Including All Revisions.
1.4 ADMINISTRATIVE REQUIREMENTS
A. Coordination:
Lionakis No. 019124.02 26 27 26
January 26, 2024 Wiring Devices
1. Coordinate the placement of outlet boxes with millwork, furniture, equipment, etc. installed under other sections or by others.
2. Coordinate wiring device ratings and configurations with the electrical requirements of actual equipment to be installed.
3. Coordinate the placement of outlet boxes for wall switches with actual installed door swings.
4. Coordinate the installation and preparation of uneven surfaces, such as split face block, to provide suitable surface for installation of wiring devices.
5. Coordinate the core drilling of holes for poke-through assemblies with the work covered under other sections.
6. Notify the Architect of any conflicts or deviations from the contract documents to obtain direction prior to proceeding with work.
B. Sequencing:
1. Do not install wiring devices until final surface finishes and painting are complete.
1.5 SUBMITTALS
A. See Section 01 30 00 - Administrative Requirements, for submittal procedures.
B. Product Data: Provide manufacturer's catalog information showing dimensions, colors, and configurations.
1. Wall Dimmers: Include derating information for ganged multiple devices.
2. Surge Protection Receptacles: Include surge current rating, voltage protection rating (VPR) for each protection mode, and diagnostics information.
C. Samples: One for each type and color of device and wall plate specified.
D. Certificates for Surge Protection Receptacles: Manufacturer's documentation of listing for compliance with UL 1449.
E. Field Quality Control Test Reports.
26 27 26 Lionakis No. 019124.02
Wiring Devices January 26, 2024
F. Manufacturer's Installation Instructions: Indicate application conditions and limitations of use stipulated by product testing agency. Include instructions for storage, handling, protection, examination, preparation, and installation of product.
G. Operation and Maintenance Data:
1. Wall Dimmers: Include information on operation and setting of presets.
2. GFCI Receptacles: Include information on status indicators.
3. Surge Protection Receptacles: Include information on status indicators.
H. Project Record Documents: Record actual installed locations of wiring devices.
I. Maintenance Materials: Furnish the following for Owner's use in maintenance of project.
1. See Section 01 60 00 - Product Requirements, for additional provisions.
2. Screwdrivers for Tamper-Resistant Screws: Two for each type of screw.
3. Extra Keys for Locking Switches: Two of each type.
4. Extra Surge Protection Receptacles: Two of each type.
5. Extra Wall Plates: One of each style, size, and finish.
6. Extra Flush Floor Service Fittings: Two of each type.
7. Extra Poke-Through Core Hole Closure Plugs: Two for each core size.
1.6 QUALITY ASSURANCE
A. Comply with requirements of NFPA 70.
B. Maintain at the project site a copy of each referenced document that prescribes execution requirements.
C. Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum five years documented experience.
D. Products: Listed, classified, and labeled as suitable for the purpose intended.
E. Product Listing Organization Qualifications: An organization recognized by OSHA as a Nationally Recognized Testing Laboratory (NRTL) and acceptable to authorities having jurisdiction.
Lionakis No. 019124.02 26 27 26
January 26, 2024 Wiring Devices