City of San Jacinto
Bath Well Improvements
For
Mathew Osborn
Water Utilities Superintendent
City of San Jacinto
270 Bissell Place, San Jacinto, CA 92582
P: 951.487.7330 x755 C: 951.537.7721
[email protected]
Prepared by
Mike Perez Adam Kelly
Proposal Number Project Engineer West Coast Manager
P24SAJ01A 919.387.1200 ext. 86356 330.842.7732
November 7, 2024 [email protected] [email protected] P24SAJ01A November 7, 2024
Bath Well Improvements Page 2 of 27
Table of Contents
1 RoviSys Background ................................................................................................ 4
1.1 Our Mission ................................................................................................................................ 4
1.2 Background ................................................................................................................................ 4
1.3 Summary .................................................................................................................................... 4 2 Project Proposal....................................................................................................... 5
2.1 Project Overview.......................................................................................................................... 5
2.2 Basis for Proposal ....................................................................................................................... 7
2.3 Services Scope and Deliverables .................................................................................................. 8
2.4 RoviSys Assumptions ................................................................................................................ 25 3 Pricing ................................................................................................................... 26
3.1 Pricing Summary....................................................................................................................... 26
3.2 Fixed Services Breakout ............................................................................................................ 26
3.3 Outside Hardware and Services Total ........................................................................................ 27
3.4 Engineering Rates for Bath Well ................................................................................................ 27 4 Terms and Conditions............................................................................................ 27 P24SAJ01A November 7, 2024
Bath Well Improvements Page 3 of 27
Proposal Revision History
Rev Date Description
A October 17, 2024 Initial Revision
B November 7, 2024 District Review and Civiltec Notification of Functional Narrative Change
NOTICE
This document contains RoviSys proprietary information and has been provided for the sole purpose of evaluation. Acceptance of the document constitutes agreement that the recipient shall not disclose RoviSys proprietary information to any third party in whole or in part or transmit any documents or copies thereof in whole or in part to any third party without the expressed written consent of The RoviSys Company.
All copyrights and trademarks remain the property of their respective owners.
P24SAJ01A November 7, 2024
Bath Well Improvements Page 4 of 27
1 RoviSys Background
1.1 Our Mission
The RoviSys mission is: Provide our clients with automation and information integration solutions using the best technologies and platforms, regardless of who makes them, giving our clients choices. We provide uncompromising focus on customer satisfaction providing the best engineered process control solutions to meet your needs.
1.2 Background
RoviSys was formed in April 1989 to provide timely, cost effective, reliable, and modern solutions to a wide range of systems applications using the best technology. This primary philosophy and our focus on customer satisfaction enables and drives our continuous growth to over 1,200 engineers at multiple locations in North America, Asia, and Europe.
RoviSys is an independent integrator offering broad range expertise in current and legacy technologies applied across a wide variety of markets. We are focused on providing solutions that are a best fit for our customers giving them the freedom to choose solutions with flexibility to integrate the best in class technologies for each of their system applications.
The most valuable asset at RoviSys is our staff. One of our greatest strengths is a diverse employee knowledge base that spans technologies and industries. Each of our employees has developed application experience in many industries we serve. Considerable effort is committed to hiring, developing, and retaining personnel. Our personnel retention is among the best in the industry benefiting our customers by maintaining project team continuity.
RoviSys draws across all functions and employee skill sets to properly execute complex projects. In addition to our diverse technical skill sets, we employ Registered Professional Engineers (PE) as well as Project Management Professionals (PMP).
1.3 Summary
As an independent automation organization and an approved system integrator for a wide range of control systems and MES platforms, RoviSys is well suited to meet the diverse needs of City of San Jacinto. Our independence combined with our experience on multi-faceted projects results in efficiency and quality in execution.
When clients are asked why they return to RoviSys project after project, they indicate that it is RoviSys' ability to manage, deliver, and complete projects. Additionally, the integrity with which we execute their projects and the ongoing focus on customer satisfaction convinces them to look no further for their system integration and support needs whatever the industry.
P24SAJ01A November 7, 2024
Bath Well Improvements Page 5 of 27
2 Project Proposal
2.1 Project Overview
City of San Jacinto has requested that RoviSys provide a proposal in response to the City of Jacinto Bath Well Site Portable Water Improvements project (designed by CIVILTEC Engineering Inc). Bath Well Improvements effort will run in parallel with ongoing Potable Water SCADA Migration. Bath Well Improvements calls for City’s Preferred Integrator (RoviSys) to:
• Design Radio Communications
o 5 GHz radio and flat panel antenna to be provided by the City’s preferred integrator.
• Design/build RTU-100 control panel
o NEMA 12 enclosure with subpanel
o Fuses, breakers, terminal blocks, relays
o Dual power supplies and UPS
o Labelled wires and color coding per specs
o Field IO and ethernet network wiring terminating at existing Bath SCADAPack PLC Panel to be extended to new RTU-100 PLC Panel. Field install/wiring to be done by others.
• RTU-100 OIT (Operator Interface Terminal) Configuration ▪ RTU-100 OIT will be part of VTScada plant wide SCADA instance. ▪ If radio fails, thin client can still run RTU-100 locally. ▪ RTU-100 SCADA programming shall verify that a “TREATMENT SYSTEM READY SIGNAL” is present from FCP-100 prior to sending a “WELL PUMP START COMMAND (YC-100)” to the Well Pump. The Treatment System Ready Signal will verify correct valve lineup and that no Backwash Operations are present.
▪ Ensure that Filter System Control Panel (FCP-100) I/O and alarm information, is communicated (mapped) to new RTU-100 Control Panel and communications established via Ethernet.
▪ Ensure that PLC panel I/O and alarm information at existing booster pump station is communicated to new RTU-100 Control Panel, and communications are established via Ethernet.
• RTU-100 PLC (Programmable Logic Controller) Configuration ▪ Booster Pump Motor Control Center PLC will be connected to RTU-100 via Ethernet connection in next phase of work.
▪ Treatment System Ready Signal from FCP-100 via Soft IO, prior to sending a Well Pump Start Command YC-100 to the Well Pump. ▪ PLC will be programmed to provide a well pump hardwired run permissive in the event of Reservoir NO.1 or NO.2 high level condition.
P24SAJ01A November 7, 2024
Bath Well Improvements Page 6 of 27
▪ In the event that Reservoir Level drops to the Well Pump “START” setpoint, the following signals shall be transmitted between RTU-100 and FCP-100 prior to Bath Well or Artesia Well starting in AUTO and sending flows through the treatment system:
1. Well Pump “PERMISSION TO START” from RTU-100 to FCP-100.
2. FCP-100 “CALL FOR WATER” signal is received from FCP-100. ▪ Well Pumps shall not start until a “CALL FOR WATER” signal is received from FCP-100.
▪ PLC to be programmed to provide a digital output in the event that a Sodium HypoChlorite Tank Leak Alarm (LS-661) is actuated at the Filter Control Panel (FCP-100). The digital output signal will cause the Chlorine Alarm Panel (CAP-660) Local Beacon and Buzzer to annunciate. ▪ RTU-100 PLC to include programming that provides a “WELL PUMP DISCHARGE FLOW” analog output. Analog output to be wired to a local loop-powered indicator display. Display provided by others.
P24SAJ01A November 7, 2024
Bath Well Improvements Page 7 of 27
2.2 Basis for Proposal
The information in the following sections reflects the estimated quantities used as the basis for this proposal. These quantities are derived from the data provided and are utilized for estimation purposes only. Final field quantities will be determined during the design portion of this control system project. This proposal is based on bid documents received September 20th, 2024, sent by Hao Liu from CIVILTEC Engineering Inc. on behalf of City of San Jacinto, and subsequent communications.
This Request for Proposal includes the following documents:
2.2.1 I/O Quantities per P&ID Drawings
IO Type – Hardwired to
RTU-100 Qty
Analog Inputs 3
Analog Outputs 1
Digital Inputs 12
Digital Outputs 3
Total Hardwired I/O 19
IO Type – Soft IO from OEM Qty
Analog Inputs 50
Analog Outputs 57
Digital Inputs 11
Digital Outputs 7
Total Hardwired I/O 125
2.2.2 Graphics Quantities
An estimated total of 10 overview displays to be incorporated into RTU-100’s field OIT.
Graphic Type Qty
Custom Faceplates 0
Overview Displays 10
Simple Displays 0
Simple Displays (Copies) 0
Medium Displays 0
Medium Displays (Copies) 0
Complex Displays 0
Complex Displays (Copies) 0
Trends 0
P24SAJ01A November 7, 2024
Bath Well Improvements Page 8 of 27
2.3 Services Scope and Deliverables
RoviSys will provide the following scope items to meet the project requirements for RTU-100 as defined in the specifications and drawings. All RoviSys scope is limited to called out sections located within Division 40 PROCESS of the bid specification, plus supporting sections called out: Division 01 GENERAL and Division 26 ELECTRICAL. These sections are identified below along with a summary of the scope that RoviSys will provide, as well as any exceptions/clarifications associated with that scope.
Section Title Notes
40 05 13 Common Work Results for Process Piping Excluded 40 05 13.09 Flushing and Disinfection Excluded
40 05 13.10 Flushing and Testing Excluded
40 05 13.11 Leak Testing of Piping Excluded
40 05 13.12 Tracer Wire & Marking Tape for Buried Piping Excluded 40 05 13.13 Steel Process Piping Excluded
40 05 13.53 Ductile, Malleable, & Cast Iron Alloys Process Piping Excluded
40 05 13.73 Plastic Process Piping Excluded
40 05 23 Common Work Results for Process Valves Excluded 40 05 29 Hangers & Supports for Process Piping Systems Excluded 40 90 00 Instrumentation & Controls for Process
Systems
Included, see below
section for additional
details
40 91 23.55 Limit and Position Switches Excluded
40 96 36 Process Control Descriptions
Included, see below
section for additional
details
01 00 00 General Requirements Excluded
01 04 50 Existing Facilities Excluded
01 11 00 Summary of Work Excluded
01 14 13 Access to Site Excluded
01 14 16 Coordination with the Owner Excluded
01 14 19 Use of Site Excluded
01 20 00 Price & Payment Procedures Excluded
01 31 19 Project Meetings Excluded
P24SAJ01A November 7, 2024
Bath Well Improvements Page 9 of 27
Section Title Notes
01 32 16 Construction Progress Schedule
01 32 19 Submittals Schedule
Included, see below
section for additional
details
01 33 00 Submittal Procedures Excluded
01 33 23 Shop Drawings, Product Data & Samples
Included, see below
section for additional
details
01 40 00 Quality Requirements Excluded
01 42 13 Abbreviations Excluded
01 42 19 Reference Standards Excluded
01 45 16 Field Quality Control Procedures Excluded
01 45 16.13 Contractor Quality Control Excluded
01 51 00 Temporary Utilities Excluded
01 52 19 Sanitary Facilities Excluded
01 55 26 Traffic Control Excluded
01 56 26 Temporary Fencing Excluded
01 57 19 Temporary Environmental Controls Excluded
01 60 00 Product Requirements Excluded
01 65 00 Equipment Testing, Training, and Startup
Included, see below
section for additional
details
01 66 00 Product Storage & Handling Requirements Excluded 01 71 13 Mobilization Excluded
01 71 18 Site Access and Storage Excluded
01 71 23.16 Construction Surveying Excluded
01 71 31 Protection of Existing Facilities Excluded
01 73 50 Testing, Disinfection of Water Facilities Excluded 01 77 00 Closeout Procedures
Included, see below
section for additional
details
01 78 23 Operation & Maintenance Data
Included, see below
section for additional
details
P24SAJ01A November 7, 2024
Bath Well Improvements Page 10 of 27
Section Title Notes
01 78 39 Project Record Documents
Included, see below
section for additional
details
01 79 00 Final Acceptance Testing
Included, see below
section for additional
details
26 00 00 General Electrical Requirements
Included, see below
section for additional
details
26 00 01 Packaged System and Control Panels
Included, see below
section for additional
details
26 01 27 Electrical Acceptance Testing Excluded
26 05 19 Low Voltage Electrical Power Conductors and
Cables
Included, see below
section for additional
details
26 05 26 Grounding and Bonding for Electrical Systems Excluded 26 05 33 Pullboxes for Electrical Systems Excluded
26 05 35 Conduit for Electrical Systems Excluded
26 05 53 Identification for Electrical Systems Excluded 26 05 73 Power System Study Excluded
26 05 83 Wiring Connections
Included, see below
section for additional
details
26 05 90 Enclosures, General
Included, see below
section for additional
details
26 09 13 Power Metering and Monitoring Excluded
26 21 00 Low Voltage Electrical Service Entrance Excluded 26 22 13 Low-Voltage Distribution Transformers Excluded 26 22 20 Mini Power Centers Excluded
26 24 16 Panelboards Excluded
26 24 19 Motor Control Center Excluded
26 27 26 Wiring Devices Excluded
26 28 17 Enclosed Switches Excluded
P24SAJ01A November 7, 2024
Bath Well Improvements Page 11 of 27
Section Title Notes
26 29 13 Motor Starters Excluded
26 32 26 Engine Driven Generator Set Excluded
26 36 23 Automatic Transfer Switch Excluded
26 43 00 Surge Protective Devices Excluded
26 50 00 Lighting Excluded
01 32 19 Submittals Schedule
RoviSys accepts all the “City’s Preferred Integrator” responsibilities identified in this section, with inclusions/exclusions noted below.
Inclusions:
1. All submittals shall be submitted for review within 30 days of the Notice to Proceed (provided by CONTRACTOR).
2. RoviSys to expect 10-15 calendar days after receipt by the Owner for review of each submittal, including re-submittals.
3. RoviSys submittal cover sheets to include name, address, telephone number, submittal number, date, contract title / number, subcontractor information if applicable.
4. Each RoviSys submittal includes applicable drawings and specification references.
Exclusions:
1. CONTRACTOR responsible for all other requirements in this specification.
P24SAJ01A November 7, 2024
Bath Well Improvements Page 12 of 27
01 33 23 Shop Drawings, Product Data & Samples
RoviSys accepts all the “City’s Preferred Integrator” responsibilities identified in this section, with inclusions/exclusions noted below.
Inclusions:
1. Panel drawings shall be produced using Autocad.
2. All drawings shall be tabloid sized 11” x 17”.
3. Panel drawings shall include external panel details, internal panel details, power distribution, PLC schematics, loop/interconnect drawings, and network architecture details. A symbol distribution legend shall be provided as required.
4. Custom title block shall be produced with
a. Drawing number, date, title, revision, number, and sheet number b. Name of CONTRACTOR
c. Contract number.
d. Subcontractor/manufacturer name (if applicable)
e. Name of installation location
5. Product data shall be provided. Applicable submittals shall have a technical literature section to illustrate/describe each BOM item.
6. Model number and serial numbers shall be provided in the O&M manual. Hardware Factory Acceptance Testing shall provide steps to record all serial numbers.
Exclusions:
1. Elevation view drawings with conduit details not included.
2. No samples to be provided by RoviSys.
3. Certificate of compliance to be produced by others.
4. Contract sheet number, contract page number will be provided in respective specification check sections in submittals, not title blocks.
5. Seismic studies to be provided by others.
P24SAJ01A November 7, 2024
Bath Well Improvements Page 13 of 27
01 65 00 Equipment Testing, Training, and Startup
RoviSys accepts all the “City’s Preferred Integrator” responsibilities identified in this section, with inclusions/exclusions noted below.
Inclusions:
1. The purpose of RoviSys’ panel testing ensures that the panels have been fabricated per District approved design drawing packages. RoviSys panel testing is conducted by the project engineers during fabrication and upon final completion of the panels.
Panel testing will be documented in the Hardware Factory Acceptance Testing report with pictures.
2. RoviSys shall provide proposed dates for training, site acceptance testing, and operations/maintenance training that relate to RTU-100.
3. Training shall not commence until O&M manuals have been accepted.
Exclusions:
1. Video recordings shall be coordinated and provided by others for training. 01 77 00 - Closeout Procedures
RoviSys accepts all the “City’s Preferred Integrator” responsibilities identified in this section, with inclusions/exclusions noted below.
Inclusions:
1. CONTRACTOR to submit all approved submittals to District prior to formal closeout in a transmittal format. RoviSys shall provide all as built material to CONTRACTOR prior to close out.
Exclusions:
1. Construction cleanup to be done by others.
P24SAJ01A November 7, 2024
Bath Well Improvements Page 14 of 27
01 78 23 – Operation and Maintenance Data
RoviSys accepts all the “City’s Preferred Integrator” responsibilities identified in this section, with inclusions/exclusions noted below.
Inclusions:
1. RoviSys shall produce an Operation and Maintenance (O&M) Manual submittal for review/approval in an electronic format.
2. Any printing or backups via USB/CD shall be pro
Exclusions:
1. Hard copy prints with binders shall be provided by others.
2. Soft copy backups via USB/CD shall be provided by others.
SECTION 01 78 39 – PROJECT RECORD DOCUMENTS
RoviSys accepts all the “City’s Preferred Integrator” responsibilities identified in this section, with inclusions/exclusions noted below.
Inclusions:
1. Installation, testing and startup reports shall be included in the final O&M submittal.
2. As built drawings shall be included in the final O&M submittal. Both pdf and dwg formats shall be provided.
3. Final payment shall be granted once final O&M submittal is approved.
Exclusions:
1. Certificates of inspection and acceptance by local governing agencies to be provided by others.
2. Others to submit Record Drawings to Safeway Vons DC on behalf of RoviSys.
P24SAJ01A November 7, 2024
Bath Well Improvements Page 15 of 27
SECTION 01 79 00 – FINAL ACCEPTANCE TESTING
RoviSys accepts all the “City’s Preferred Integrator” responsibilities identified in this section, with inclusions/exclusions noted below.
Inclusions:
1. Approval of hardware SAT report submittal and software SAT report submittal indicate that all system availability requirements and final system acceptance have been met.
2. As built drawings shall be included in the final O&M submittal. Both pdf and dwg formats shall be provided.
3. Final payment shall be granted once final O&M submittal is approved.
Exclusions:
1. Certificates of inspection and acceptance by local governing agencies to be provided by others.
2. Others to submit Record Drawings to Safeway Vons DC on behalf of RoviSys.
P24SAJ01A November 7, 2024
Bath Well Improvements Page 16 of 27
SECTION 26 00 00 – GENERAL ELECTRICAL REQUIREMENTS
RoviSys accepts all the “City’s Preferred Integrator” responsibilities identified in this section, with inclusions/exclusions noted below.
Inclusions:
1. Panel shall be fabricated at a UL listed panel shop.
2. Panel drawings shall include external panel details, internal panel details, power distribution, PLC schematics, loop/interconnect drawings, and network architecture details. A symbol distribution legend shall be provided as required.
3. Wire labels and numbers to be provided in panel drawings.
4. Contractor to provide all applicable vendor submittals related to field wiring for RTU-100 to RoviSys.
5. Final payment shall be granted once final O&M submittal is approved.
6. Power up, power down procedures to be provided in O&M submittals.
7. Loop/interconnect drawings for RTU-100 will only show power/controls/networking interconnects to hardwired field devices. Circuit numbers, conduit sizes, number of conductors, and major junction boxes (if any) shall be shown.
8. Nameplates, labels, and legend plates to be provided.
9. Control wire markers to be provided by panel manufacturer.
10. Heating/cooling calculations shall consider the site conditions provided in spec.
11. Multiple sources of power hazard sign and general electrical danger signs to be provided.
Exclusions:
1. Anchoring devices and supports to be provided by others.
2. Utility coordination to be executed by others.
3. Concrete pad or foundations to be provided and installed by others.
4. Seismic studies to be provided by others.
5. Conduits and any accessories to be installed/provided by others.
6. Arc flash studies to be provided by others.
P24SAJ01A November 7, 2024
Bath Well Improvements Page 17 of 27
26 00 01 – Packaged System and Control Panels
RoviSys accepts all the “City’s Preferred Integrator” responsibilities identified in this section, with inclusions/exclusions noted below.
Inclusions:
1. Panel drawings to show power & controls interconnects to hard IO connected to RTU-100.
2. Follow hardware requirements called out.
Exclusions:
1. No control/power interconnects drawings to be provided outside of P&ID drawing Sheet 1.
26 05 19 Low Voltage Electrical Power Conductors and Cables RoviSys accepts all the “City’s Preferred Integrator” responsibilities identified in this section, with inclusions/exclusions noted below.
Inclusions:
1. Panel drawings shall follow 20 05 19 for internal controls, power, and networking cabling.
2. Follow hardware requirements called out.
Exclusions:
1. Field wiring and conduits provided by others.
2. Wire pulling provided by others.
3. Cable pulling calculations by others.
26 05 83 – Wiring Connections
RoviSys accepts all the “City’s Preferred Integrator” responsibilities identified in this section, with inclusions/exclusions noted below.
Inclusions:
1. Follow hardware requirements called out for power/controls terminal blocks, fuse holders, terminal strips, grounding blocks, and ancillary terminal strip details.
Exclusions:
1. n/a
P24SAJ01A November 7, 2024
Bath Well Improvements Page 18 of 27
26 05 90 – Enclosures, General
RoviSys accepts all the “City’s Preferred Integrator” responsibilities identified in this section, with inclusions/exclusions noted below.
Inclusions:
1. RTU-100 to be fabricated at a UL rated panel shop.
2. Nameplates to follow 26 05 90.
3. Fabrication standards shall be followed for NEMA 12 cabinet.
4. A heat load study shall be conducted to size any cooling solutions appropriately.
5. Each interior temperature alarm shall be displayed on the HMI. A device aside from thermostat shall trigger a PLC input once preset high temperature is reached.
6. Intrusion switches shall be incorporated, and wired into PLC.
7. Terminal blocks shall be labelled on both sides, and jumpered as needed.
8. Minimum wire sizes shall be followed.
9. Grounding busses shall be provided (copper) .
10. Duplex receptacle to be provided.
11. Multiple sources of Power shall be provided in red background white font lamacoid, see spec for font and dimension sizing.
Exclusions:
1. n/a
P24SAJ01A November 7, 2024
Bath Well Improvements Page 19 of 27
40 90 00 – Instrumentation & Controls for Process Systems RoviSys accepts all the “City’s Preferred Integrator” responsibilities identified in this section, with inclusion/exclusions noted below.
Inclusions:
1. RTU-100 hardware and software submittals.
2. RTU-100 hardware FATs and SATs.
3. Provide FAT procedure for factory inspection,
4. Programming methodology, control strategies, and ancillary application software to be provided in software submittal. Applicable for OIT and PLC configurations.
5. Equipment shall received 120VAC to power enclosure.
6. Calculate temperature based on indoor and outdoor provided data.
7. Power supplies shall be 24VDC, 10A minimum.
8. Signal isolators shall be provided for analog 4-20mA signals.
9. Interposing relays shall be provided for all discrete signals (input/outputs).
10. Dual power supplies and UPS shall be provided and shall be monitored by PLC.
11. 5 GHz radio and flat panel antenna to be provided by the City’s preferred integrator.
12. System validation shall be provided for RTU-100 at panel shop and in the field.
Exclusions:
1. Printing of O&M manuals by others.
2. Programming/design of FCP-100 control panel, HMI, and PLC.
3. RoviSys will NOT perform any of the following services as part of this contract:
• Installation of control panels or instrumentation.
• Installation of electrical conduit.
• Pulling of wiring or cables.
• Field device or control panel wire terminations.
P24SAJ01A November 7, 2024
Bath Well Improvements Page 20 of 27
40 96 36 – Process Control Descriptions
RoviSys accepts all the “City’s Preferred Integrator” responsibilities identified in this section, with inclusion/exclusions noted below.
Inclusions:
1. RTU-100 HMI and OIT shall be configured per process narratives mentioned in 40 96 36.
Exclusions:
1. Programming/design of FCP-100 control panel, HMI, and PLC.
2. Per Civiltec, narratives with mention of Well 34 PLC panel and GAC are not applicable.
P24SAJ01A November 7, 2024
Bath Well Improvements Page 21 of 27
See estimated deliverables below
Items in blue are already in scope with city’s SCADA project, no cost to this project.
Items in green are already in scope with city’s SCADA project, but may require additional modifications.
Submittal
Number
Submittal Name Descriptions
1 RTU-100 Control Panel
Design Submittal
• Bill of Materials
▪ Enclosure hardware
▪ Subpanel hardware
▪ Schneider PLC
• Technical Literature
• Power Load Study
• Heat Load Study
• loop & interconnect drawings relative to
RTU-100
• Hard IO list
• Procure and build once submittal is
approved.
2 Bath Well Radio Design
Submittal
• Design/procure 5GHz radio and flat panel
antenna.
• Procure radio and flat panel once submittal
is approved.
• Updates to Cybervision instance from
server, updates to Cisco 3300 switch.
3 RTU-100 Hardware FAT
Protocol
• Panel Shop Energized/Non-Energized
steps, including:
• IP Pings
• Simulated discrete/analog values
using Fluke
4 RTU-100 Hardware FAT
Report
• Pictures
• Signatures (remotely or in person)
• Redlined drawings
• As Built drawings
5 RTU-100 Software Design
Submittal
• PLC & OIT Functional Specification
(modifications to ongoing Bath Well FS
docs)
• Soft IO List: Data sharing spreadsheet
(RTU-100 to Filter FCP-100 panel)
• Soft IO List: Data sharing spreadsheet
(RTU-100 to Existing Booster Pump
Station panel)
• OIT Configuration and Screen Graphics –
RTU 100
P24SAJ01A November 7, 2024
Bath Well Improvements Page 22 of 27
• PLC configuration – RTU 100 (add-on
configurations)
• PLC configuration – Booster Station (add
on configurations)
• IP addresses
6 RTU-100 Software FAT
Protocol
Using simulated values in remote environment or panel
shop:
• Test Operational Logic
• Test Failure responses
• Test Adjustable Setpoints
• Test Interlocks
• Test Calculated Variables
• Test Alarms
• Test Graphic Displays
7 RTU-100 Software FAT
Report
Pictures and signed forms by all parties (remotely or in person)
8 RTU-100 Hardware SAT
Protocol
Once all field wiring has been terminated and energized:
• IP Pings
• De-Energized and Energized checks
• Loop checks of hardwired discrete/analog
values
• Soft IO loop check
9 RTU-100 Hardware SAT
Report
Pictures and signed forms by all parties (remotely or in person)
10 RTU-100 Software SAT
Protocol
Using real values:
• Test Operational Logic
• Test Failure responses
• Test Adjustable Setpoints
• Test Interlocks
• Test Calculated Variables
• Test Alarms
• Test Graphic Displays
11 RTU-100 Software SAT
Report
Pictures and signed forms by all parties (remotely or in person)
12 RTU-100 Final O&M Includes final as built RTU-100 drawing P24SAJ01A November 7, 2024
Bath Well Improvements Page 23 of 27
2.3.1 Project Meetings
The following table is a summary of the quantity of meetings proposed for this project. Below the table describes the purpose of each meeting type.
Meeting Description Qty Duration
RoviSys
Resources
Location
Weekly Client Project Status Meetings
(Civeltec/SAJ) 6 1-Hr 1 Remote
Weekly Internal Status Meetings 3 30-Min 3
RoviSys
Internal
Design Review Meetings 3 1.5-Hr 1
Remote or
In Person
RoviSys will conduct regularly scheduled project status review meetings with City of San Jacinto project personnel to review progress and address issues.
Items that will be reviewed during these meetings include:
• Review of previous meeting minutes and project action item log • Review of project schedule and/or planning documents
• Review & status of scheduled deliverables
• Review of technical and design topics
The agenda of these meetings will be flexible throughout the course of project to address current and upcoming tasks. For example, when the project is close to the on-site phase, the project status meeting will focus on planning and coordination of the on-site activities.
2.3.1.1 Design Review Meetings
Design Reviews are performed by the project teams to ensure that project implementation is meeting project objectives and user requirements. The RoviSys lead engineer will conduct these meetings either on-site at City of San Jacinto or via web conference. Three Design review meetings are allocated for the following:
• Workshop soft IO details with Filter PLC OEM (Pureflow). • Workshop software design specifications with district and/or CivilTec. • Workshop updated telemetry design with the district and/or CivilTec.
P24SAJ01A November 7, 2024
Bath Well Improvements Page 24 of 27
2.3.2 Schedule
The RoviSys project manager will develop and maintain a detailed project schedule. The schedule will be reviewed and agreed to with City of San Jacinto. The project schedule will be developed based on the following milestone dates that have been provided by City of San Jacinto.
Date Milestone
September 20, 2024 RFP Received
October 18, 2024 Proposed Response Date
xx/xx/20xx Project Award
xx/xx/20xx Kickoff Meeting
xx/xx/20xx Milestone 1 (Approval of RTU-100 Panel Design) xx/xx/20xx Milestone 2 (Approval of RTU-100 Software Design) xx/xx/20xx Milestone 3 (Approval of Bath Wells Radio Design) xx/xx/20xx Software FAT (Virtual or In Person)
xx/xx/20xx Hardware FAT (Panel Shop)
xx/xx/20xx Equipment Delivery
xx/xx/20xx Commissioning Begins
xx/xx/20xx Commissioning Complete
xx/xx/20xx Training
xx/xx/20xx Project Complete
The following high-level project development and delivery schedule assumed first half 2025 total duration for planning, design, and implementation along with remaining latter half 2025 total duration for field installations, startup, and commissioning.
2.3.3 Project Closeout
RoviSys will assemble a turn-over package for City of San Jacinto once the project has been successfully delivered. The project turnover package will include electronic copies of the last transmitted version of every document supplied by RoviSys. The project turnover package will also include the as-installed software configuration files.
The Project Closeout Activities will include a lessons-learned meeting attended by the appropriate RoviSys and City of San Jacinto project and management personnel.
P24SAJ01A November 7, 2024
Bath Well Improvements Page 25 of 27
2.4 RoviSys Assumptions
This proposal is based upon the following assumptions:
1. This proposal is based on quantities detailed in the Basis for Proposal section.
2. RoviSys has assumed that equipment and systems will be available when required to support the scheduled field activities without causing any delays. Delays of system availability may impact project schedules or resource availability, as well as price.
3. Field devices including instrumentation, transmitters, sensors, switches or other networking interfaces, network cables, all field wiring, VFDs, motor starters and drives will be procured and installed by others.
4. The programming of field instruments or the verification of field instrument wiring and calibration will be provided by others.
5. Physical installation of control system hardware, wiring, instrumentation, field panels, and HMIs will be performed by others.
6. PLC-1 former SCADAPack PLC cabinet at some point will have a running Schneider PLC (replacing legacy Schneider SCADAPack PLC). The RTU-100 control panel shall be temporarily installed adjacent to existing PLC-1 cabinet. 2 conduits to be installed in between panels. Once PLC-1 cabinet is ready to be decommissioned, relocate RTU-100 (and Unistrut if possible) to the new building. Installation and wiring to be done by others.
7. Booster Pump MCC PLC-2 section at some point will have a running remote Schneider PLC (replacing legacy Rockwell SLC500).
P24SAJ01A November 7, 2024
Bath Well Improvements Page 26 of 27
3 Pricing
RoviSys has estimated, in good faith, the effort and cost of this project. The cost estimate is based on the information provided by City of San Jacinto and on our experience in defining and implementing projects of similar scope and complexity.
3.1 Pricing Summary
Pricing Summary Table
Scope Item Price Hours
Engineering Services - Fixed $70,376 416
Outside Purchased Equipment, Software & Services $40,418 - Travel and Living Expenses (estimated) $2,423 -
Tax on OPE (estimated) $30 -
Bond Pricing $1,699
Proposal Total $114,946 416
3.2 Fixed Services Breakout
Engineering Services Pricing Table
Services Scope - Fixed Price Price Hours
Project Management $10,700 50
Meetings $2,825 15
Design Documents $4,974 30
Electrical Design $6,084 40
Infrastructure Configuration $828 4
Graphics Configuration $6,280 40
Control Configuration $9,420 60
Test Documents $2,776 16
In-House Testing $3,140 20
Site Support - Install & Loop Checks $9,308 52
Site Support - Commissioning $4,833 27
Training $3,580 20
As Built Documentation $1,253 7
Travel Hours $4,375 35
Fixed Price Services Subtotal $70,376 416
P24SAJ01A November 7, 2024
Bath Well Improvements Page 27 of 27
3.3 Outside Hardware and Services Total
Outside Purchased Services Pricing Table
Outside Purchased Services Price Tax
Subcontracted Services – Panel Shop Labor and
Hardware $35,225 $0
Outside Purchased Services Subtotal $35,225 $0
Outside Purchased Equipment & Software Pricing
Table
Outside Purchased Equipment & Software Price Tax
Network Hardware – Flat Antenna $345 $30
Software and Licenses – VTScada Remote Terminal $4,848 $0 Outside Purchased Equipment Subtotal $5,193 $30
3.4 Engineering Rates for Bath Well
Preferred rates have been applied.
2024 Rate Table $/Hr
Project Manager $214
Senior (Engineer/Developer) $207
Lead (Engineer/Developer) $179
Engineer/Developer/Analyst $157
CAD Technician $121
Engineer Travel $125
4 Terms and Conditions
This proposal is valid for 90 days.
Please refer to P24SAJ01RevE – SCADA Upgrade Pricing document for agreement details.
Preferred rates have been applied for this project.
If RoviSys is selected for this work please send the purchase order to [email protected]