ATTACHMENT D.10
NOISE ANALYSIS
Noise Analysis for the
Santa Fe Flores Townhomes Project
San Marcos, California
Project Nos. GPA25-0001, R25-0001, MFSDP25-0001, and
TSM25-0001
Prepared for
Santa Fe Flores, LP
P.O. Box 903
Rancho Santa Fe, CA 92067
Contact: Paul Mayer
Prepared by
RECON Environmental, Inc.
3111 Camino del Rio North, Suite 600
San Diego, CA 92108
P 619.308.9333
RECON Number 10587
January 28, 2026
Jessica Fleming
Senior Air Quality/Noise/GHG Specialist
Noise Analysis
Santa Fe Flores Townhomes Project
i
TABLE OF CONTENTS
Acronyms and Abbreviations ................................ ................................ ................................ ................... iii Executive Summary ................................ ................................ ................................ ................................ ...... 1
1.0 Introduction ................................ ................................ ................................ ................................ ..... 3
1.1 Project Description ............................................................................................................................ 3
1.2 Fundamentals of Noise .................................................................................................................... 7
2.0 Applicable Noise Standards ................................ ................................ ................................ ........ 8
2.1 General Plan ......................................................................................................................................... 8
2.2 Municipal Code ................................................................................................................................... 9
2.3 California Green Building Standards Code – Environmental Comfort ........................... 10
3.0 Existing Conditions ................................ ................................ ................................ ...................... 10
4.0 Analysis Methodology ................................ ................................ ................................ ................ 13
4.1 Construction Noise Analysis ......................................................................................................... 13
4.2 Traffic Noise Analysis ...................................................................................................................... 14
4.3 On-site Generated Noise Analysis .............................................................................................. 16
5.0 Future Acoustical Environment and Impacts ................................ ................................ ......... 17
5.1 Construction Noise .......................................................................................................................... 17
5.2 Traffic Noise ....................................................................................................................................... 18
5.3 On-site Generated Noise ............................................................................................................... 23
6.0 Conclusions ................................ ................................ ................................ ................................ .... 25
6.1 Construction Noise .......................................................................................................................... 25
6.2 Traffic Noise ....................................................................................................................................... 26
6.3 On-site Generated Noise ............................................................................................................... 26
7.0 References Cited ................................ ................................ ................................ .......................... 27
FIGURES
1: Regional Location ............................................................................................................................................. 4 2: Project Location on Aerial Photograph ..................................................................................................... 5 3: Site Plan ................................................................................................................................................................ 6 4: Noise Measurement Locations ................................................................................................................... 12 5: Construction Noise Contours ...................................................................................................................... 19 6: Future Vehicle and Rail Traffic Noise Contours ..................................................................................... 19 7: HVAC Noise Contours .................................................................................................................................. 24 Noise Analysis
Santa Fe Flores Townhomes Project
ii
TABLE OF CONTENTS (cont.)
TABLES
1: Interior and Exterior Noise Guidelines ....................................................................................................... 9 2: Municipal Code Property Line Noise Standards ................................................................................... 10 3: Noise Measurements ...................................................................................................................................... 11 4: 15-minute Traffic Counts ............................................................................................................................... 11 5: Typical Construction Equipment Noise Levels ...................................................................................... 13 6: Modeled Vehicle Traffic Parameters ......................................................................................................... 15 7: Modeled Sprinter Trains ............................................................................................................................... 15 8: Future Vehicle Traffic Parameters .............................................................................................................. 16 9: Construction Noise Levels ............................................................................................................................ 17 10: Future Vehicle and Rail Traffic Noise Levels ........................................................................................... 21 11: Traffic Noise Level with and without Project and Ambient Noise Increases .............................. 23 12: HVAC Noise Levels at Adjacent Properties ........................................................................................... 25
ATTACHMENTS
1: Noise Measurement Data
2: HVAC Specifications
3: SoundPLAN Data – Construction Noise
4: SoundPLAN Data – On-site Traffic and Rail Noise
5: Fresnel Barrier Reduction Calculations
6: FHWA RD-77-108 – Off-site Traffic Noise
7: SoundPLAN Data – On-site Generated Noise
Noise Analysis
Santa Fe Flores Townhomes Project
iii
Acronyms and Abbreviations
APN assessor parcel number
Caltrans California Department of Transportation
CCR California Code of Regulations
City City of San Marcos
CNEL community noise equivalent level
dB decibel
dB(A) A-weighted decibel
FHWA Federal Highway Administration
GPA General Plan Amendment
HVAC heating, ventilating, and air conditioning
L90 noise level exceeded 90 percent of the time
Leq one-hour equivalent noise level
LLG Linscott, Law & Greenspan, Engineers, Inc.
Lmax maximum noise level
Lpw sound power level
MND Mitigated Negative Declaration
project Santa Fe Flores Townhomes Project
STC sound transmission class
Noise Analysis
Santa Fe Flores Townhomes Project
Executive Summary
The Santa Fe Flores Townhomes Project (project) is located in the city of San Marcos at 2966, 2972, and 2982 South Santa Fe Avenue, adjacent to North Las Flores Drive. The 2.6-acre (net) project site is comprised of assessor parcel numbers (APNs) 217-161-18, 217-161-19, and 0.37 acres of APN 217- 161-17. The project would require a General Plan A mendment (GPA) and Rezone to allow the development of 46 multi-family residential townhome units. The project also proposes approximately 0.12 acres of off -site improvements, including the construction of a new shared driveway extending into the southern portion of APN 217 -161-17, upgrades to the existing liquor store parking lot, and landscaping within the 8-foot-wide irrevocable offer of dedication area along the project frontage. The liquor store, Gourmet Liquor, located on the southern portion of APN 217- 161-17 is not part of the project and would remain.
This report discusses potential noise impacts from the construction and operation of the project. As part of this assessment, noise levels due to vehicle traffic were calculated and evaluated against City of San Marcos (City) noise and land use compatibility guidelines. In addition to compatibility, the potential for noise to impact adjacent uses from future on-site sources and construction activity was assessed. A summary of the findings is provided below.
Construction Noise
Construction activity is regulated by the City Municipal Code, which limits noise by restricting construction activities to hours unlikely to impact the community. Noise associated with the grading, building, and paving for the project would potentially result in short -term impacts to surrounding residential properties. Construction noise levels would range from 56 to 73 A-weighted decibels equivalent noise level (dB(A) L
eq) at the adjacent properties. Construction activities would generally occur over the period between 7:00 a.m. and 6:00 p.m. on weekdays. Although the existing adjacent uses would be exposed to construction noise levels that may be heard above ambient conditions, the exposure would be temporary and would not exceed 75 dB(A) L eq. As construction activities associated with the project would comply with Section 10.24.020 (b)(9) of the City Municipal Code, temporary increases in noise levels from construction activities would be less than significant.
Traffic Noise
The additional vehicle trips associated with the project would increase noise levels on nearby roadways. A noise increase of 3 dB or more would be considered significant because 3 dB is the level at which an increase in noise is perceptible to a person. Ho wever, the project would not generate enough trips to result in a direct or cumulative noise increase of more than 3 dB. Therefore, the project would result in less than significant direct and cumulative impacts related to traffic noise.
The main source of noise at the project site is vehicle traffic on South Santa Fe Avenue and North Las Flores Drive as well as Sprinters on the adjacent rail line. Exterior noise levels were modeled at the project site to determine compatibility with City standards. The applicable standards for multi-family uses are an exterior noise level of 65 community noise equivalent level (CNEL) and an Noise Analysis
Santa Fe Flores Townhomes Project
interior noise level of 45 CNEL. The project’s exterior useable spaces include second- and third-floor balconies, roof decks, and the five amenity areas located on the south side of Building 1, on the north side of Building 2 , on the east side of Building 4, on the north side of Building 5, and between Buildings 6 and 7. These amenity areas consist of active play areas and passive gathering space. As calculated in this analysis, without consideration of any noise barriers, exterior noise levels are projected to range from 42 to 70 CNEL at the building façades and amenity areas. Noise levels would be compatible with the City’s exterior multi-family noise level standard of 65 CNEL at all locations except the amenity area on the south side of Building 1 ( Amenity Area A, Receiver 1) and the south and east sides of Building 1 facing the roadways (Receivers 8 and 9). In order to reduce noise levels at these locations, the project would include a 6-foot barrier adjacent to the amenity area south of Building 1, and a solid 3.5 -foot barrier on the balconies located on the south and east sides of Building 1 and on the south and east sides of the Building 1 roof deck. With construction of these barriers, exterior noise levels would be reduced to less than 65 CNEL and exterior nois e impacts would be less than significant.
The interior noise level standard is 45 CNEL. Interior noise levels can be reduced through standard construction techniques. When windows are closed, standard construction techniques provide various exterior-to-interior noise level reductions depending on the type of structure and window.
Standard light-frame construction would reduce exterior to interior noise levels by at least 20 dB (Federal Highway Administration 2011). With the installation of windows with a sound transmission class (STC) rating of 25 or higher, interior noise levels within the units in Building 1 would be reduced to 45 CNEL and interior noise levels would be less than significant. Interior noise levels at all other buildings would be 45 CNEL with standard light frame construction and without consideration of specific building components.
On-site Generated Noise
The project site is surrounded by single-family residential uses to the northeast and southeast, multi-family residential uses to the east, a mobile home park to the south, a commercial use to the southwest, and industrial uses to the west and north. The applicable daytime (7:00 a.m. to 10:00 p.m.) and nighttime (10:00 p.m. to 7:00 a.m.) Noise Ordinance limits are 60 dB(A) L eq and 50 dB(A) Leq at the single-family residential uses, 65 dB(A) Leq and 55 dB(A) L eq at the multi -family residential and mobile home park uses, 65 dB(A) Leq and 55 dB(A) Leq at the commercial uses, and 65 dB(A) Leq and 60 dB(A) L eq at the industrial uses. The noise sources on the project site after completion of construction are anticipated to be those that would be typical of any residential use, such as vehicles arriving and leaving, children at play, and landscape maintenance machinery. None of these noise sources are anticipated to violate the Municipal Code. Rooftop heating, ventilating, and air conditioning noise levels were modeled at the property line adjacent properties. As calculated in this analysis, HVAC noise levels would range from 33 to 42 dB(A) Leq at the adjacent properties. Noise levels would not exceed the applicable Noise Ordinance limits at the property lines.
Noise Analysis
Santa Fe Flores Townhomes Project
1.0 Introduction
1.1 Project Description
The project is located in the city of San Marcos at 2966, 2972, and 2982 South Santa Fe Avenue adjacent to North Las Flores Drive on assessor parcel numbers (APNs) 217 -161-18, 217-161-19, and
0.37 acres of APN 217-161-17 . The 2.6-acre (net) project site is comprised of APNs 217 -161-18, 217- 161-19, and 0.37 acres of APN 217-161-17. The project also proposes approximately 0.12 acres of off- site improvements, including the construction of a new shared driveway extending into the southern portion of APN 217-161-17, upgrades to the existing liquor store parking lot, and landscaping within the 8-foot-wide irrevocable offer of dedication area along the project frontage. Figure 1 shows the regional location. Figure 2 shows an aerial photograph of the project site and vicinity.
On February 28, 2023, the City of San Marcos City Council adopted a Mitigated Negative Declaration (MND; ND22-008; SCH No. 2022090486), approved a GPA (GPA21-0008), approved a Rezone (21 - 0004), and approved a Multi-Family Site Development Plan (MFSDP21-0002) for the Santa Fe Flores, LP Project (approved project). The requested Rezone (R21-0004) required a second reading prior to approval on March 14, 2023. The approved project evaluated the impacts associated with a GPA to change the land use from Commercial (C) and Light Industrial (L-I) to Medium Density Residential 2 (MDR2) and a zone change from Commercial (C) and Light Industrial (L-I) to Multi-Family Residential (R-3-10) to allow for the construction of 50 multi-family residential townhome units, in conjunction with a Density Bonus, on a 2.23-acre site consisting of two parcels, APNs 217-161-18 and 217-161-19.
Subsequent to MND approval, the applicant modified the site plan and added 0.37 acres of APN 217-161-17 through a lot line adjustment to be proces sed. The project would require a GPA from Medium Density Residential 2 (MDR2) to Medium High Density Residential (MHDR) for APNs 217 - 161-18 and 217-161-19, and a GPA from Commercial (C) to Medium High Density Residential (MHDR) for 0.37 acres of the northern portion of APN 217-161-17. Additionally, the project would rezone APNs 217-161-18 and 217-161-19 from Multi-Family Residential 3 (R-3-10) to Multi-Family Residential (R-3- 6) and 0.37 acres of the northern portion of APN 217-161-17 from Commercial (C) to Mu lti-Family Residential (R-3-6). The project would develop 46 multi-family residential townhome units in seven buildings that would be three stories in height. Vehicle parking would include 92 spaces within attached garages and 15 guest spaces. The liquor store would not be part of the project and would remain. Project grading would include 23,300 cubic yards of cut and 3,200 cubic yards of fill resulting in the export of 20,100 cubic yards of soil. Figure 3 shows the proposed site plan.
!
!
!
!
!
!
!
!
!
!
!
Los
Penasquitos Canyon Presv
Daley Ranch
Lake Wohlford
Batiquitos Lagoon
Lake Hodges
San Vicente
Reservoir
Usmc Air
Station
Miramar
Camp Pendleton
Marine Co Base
Cleveland National
Forest
Temecula
San Diego
Encinitas
Oceanside
Poway
San Marcos
Vista
Carlsbad
Santee
Escondido
Solana
Beach
Del
Mar
Pauma and
Yuima
Reservation
Pala
Reservation
San
Pasqual
Reservation
Rincon
Reservation
Pechanga
Tribal Lands
Bonsall
Camp Pendleton
North
Camp Pendleton South
Eucalyptus
Hills
Fairbanks
Ranch
Fallbrook
Hidden
Meadows
Lake
San Marcos
Rainbow
Rancho
Santa Fe
Valley Center
R I V E R S I D E
C O U N T Y
S A N D I E G O
C O U N T Y
78 56
67 805
5 15
M:\JOBS6\10587\common_gis\PRO\standard_figures\standardfigures.aprx 10/29/2024 fmm Regional Location
FIGURE 1
0 5Miles [
Project Locationkj
kj
FIGURE 2
Project Location on Aerial Photograph
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
% % % %
% % % % %
%
%
% % % % %
%
%%
%
% % % % %
%
%
% % % % %
% % % %
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
% % % % %
%
%
% % % % %
% % % %
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
VIA LA
VENTA
VIA S
ANT
ALINA
LAS FLOR
ES DR
VIA HACIENDA
N L
ASFLORES DR
HOLLENCRE
STRD
BOS
STICKBLVD
POLLEY DR
HYDRACT
NORMAN STRASSE R
D
S SANTA FE AVE
DE LE
ONE
RD
UV78
SPRINTER
0 300Feet
M:\JOBS6\10587\common_gis\PRO\standard_figures\standardfigures.aprx 07/21/2025 bma [
Project Boundary
Off-site Improvements
Image Source: Nearmap (flown May 2025)
Noise Analysis
Santa Fe Flores Townhomes Project
1.2 Fundamentals of Noise
Sound levels are described in units called the decibel (dB). Decibels are measured on a logarithmic scale that quantifies sound intensity in a manner similar to the Richter scale used for earthquake magnitudes. Thus, a doubling of the energy of a noise sou rce, such as doubling of traffic volume, would increase the noise level by 3 dB; a halving of the energy would result in a 3 dB decrease.
However, human perception of noise has no simple correlation with acoustical energy. A change in noise levels is generally perceived as follows: 3 A -weighted dB (dB(A)) barely perceptible, 5 dB(A) readily perceptible, and 10 dB(A) perceived as a doubling or halving of noise (California Department of Transportation [Caltrans] 2013).
In technical terms, sound levels are described as either a “sound power level” or a “sound pressure level,” which while commonly confused, are two distinct characteristics of sound. Both share the same unit of measure, the dB. However, sound power, expressed as L pw, is the energy converted into sound
by the source. As sound energy travels through the air, it creates a sound wave that exerts pressure on receivers such as an eardrum or microphone, the sound pressure level. Sound measurement instruments only measure sound pressure, and limits used in standards are generally sound pressure levels.
The human ear is not equally sensitive to all frequencies within the sound spectrum. To accommodate this phenomenon, the A -scale, which approximates the frequency response of the average young ear when listening to most ordinary everyday sounds, was devise d. When people make relative judgments of the loudness or annoyance of a sound, their judgments correlate well with the A-scale sound levels of those sounds. Therefore, the “A -weighted” noise scale is used for measurements and standards involving the human perception of noise. Noise levels using A-weighted measurements are designated with the notation dB(A).
1.2.1 Descriptors
The impact of noise is not a function of loudness alone. The time of day when noise occurs and the duration of the noise are also important. In addition, most noise that lasts for more than a few seconds is variable in its intensity. Consequently, a variety of noise descriptors has been developed.
The noise descriptors used for this study are the equivalent noise level (L eq) and the community noise
equivalent level (CNEL). The Leq is the equivalent steady-state noise level in a stated period of time that is calculated by averaging the acoustic energy over a time period; when no period is specified, a 1-hour period is assumed.
The CNEL is a 24 -hour equivalent sound level. The CNEL calculation applies an additional 5 dB(A) penalty to noise occurring during evening hours, between 7:00 p.m. and 10:00 p.m., and a 10 dB(A) penalty is added to noise occurring during the night, between 10:00 p.m. and 7:00 a.m. These increases for certain times are intended to account for the added sensitivity of humans to noise during the evening and night.
Noise Analysis
Santa Fe Flores Townhomes Project
1.2.2 Propagation
Sound from a localized source (approximating a “point” source) radiates uniformly outward as it travels away from the source in a spherical pattern, known as geometric spreading. The sound level decreases or drops off at a rate of 6 dB(A) for each doubling of the distance (e.g., a noise level of 60 dB(A) at 50 feet from a point source would attenuate to 54 dB(A) at 100 feet).
Traffic noise is not a single, stationary point source of sound. The movement of vehicles makes the source of the sound appear to emanate from a line (line source) rather than a point when viewed over some time interval. The drop-off rate for a line source is 3 dB(A) for each doubling of distance (e.g., a noise level of 60 dB(A) at 50 feet from a line source would attenuate to 57 dB(A) at 100 feet).
The propagation of noise is also affected by the intervening ground, known as ground absorption.
A hard site (such as parking lots or smooth bodies of water) receives no additional ground attenuation, and the changes in noise levels with distance (drop-off rate) are simply the geometric spreading of the source. A soft site (such as soft dirt, grass, or scattered bushes and trees) provides an additional ground attenuation value of 1.5 dB(A) per doubling of distance. For example, under soft site conditions, a noise level of 60 dB(A) at 50 feet from a point source would attenuate to 52.5 dB(A) at 100 feet, and a noise level of 60 dB(A) at 50 feet from a line source would attenuate to 55.5 dB(A) at 100 feet.
2.0 Applicable Noise Standards
2.1 General Plan
The Noise Element of the City General Plan provides land use compatibility guidelines to ensure that new developments are sited, designed, and constructed in such a manner that ambient noise levels would not create an unacceptable noise environment for the occupants and patrons of the new development. Table 1 provides the interior and exterior noise guidelines for various types of uses and developments.
The project proposes multi-family residential uses. As shown in Table 1, the applicable standards for multi-family uses are an exterior noise level of 65 CNEL and an interior noise level of 45 CNEL. The exterior noise level standard is applicable at the proposed exterior use areas. For the proposed project, this includes second- and third-floor balconies, rooftop decks, and the five proposed amenity areas consisting of active play areas and passive gathering areas.
Noise Analysis
Santa Fe Flores Townhomes Project
Table 1
Interior and Exterior Noise Guidelines
Land Use
Maximum Noise Level
(CNEL)
Interior1 Exterior2,3
Residential – single-family, mobile homes, or age-restricted housing 45 60 Residential – multi-family residences or mixed use 45 65 Lodging – hotels, motels 45 65
Schools, churches, hospitals, residential care facility, childcare facilities 50 65 Passive recreational parks, nature preserves, contemplative spaces, cemeteries -- 65 Active parks, golf courses, athletic fields, outdoor spectator sports, water recreation -- 65 Office/professional, government, medical/dental, commercial, retail, laboratories 50 65 Industrial, manufacturing, utilities, agriculture, mining, stables, ranching, warehouse, maintenance/repair -- 65
CNEL = community noise equivalent level
SOURCE: City of San Marcos General Plan Update, Noise Element 2012. 1Applies only to interior habitable rooms.
2Exterior noise standard does not apply for land uses where no exterior use area is proposed or necessary, such as a library.
3For single-family detached dwelling units, “exterior noise level” is defined as the noise level measured at an outdoor living area that adjoins and is on the same lot as the dwelling.
2.2 Municipal Code
2.2.1 Title 10, Chapter 10.24 – Construction
Section 10.24.020 (b)(9) of the City Municipal Code identifies permissible hours for general construction activities. Excluding City holidays, construction may occur weekdays from 7:00 a.m. to 6:00 p.m. or Saturdays from 8:00 a.m. to 5:00 p.m. Grading is often the loudest phase of construction.
Section 17.32.180 restricts grading and earthworks activities to between the hours of 7:00 a.m. and 4:30 p.m., Monday through Friday.
2.2.2 Title 20 – Zoning Ordinance
City Municipal Code Title 20 – Zoning Ordinance contains General Development Standards.
Performance standards in Section 20.300.070 (f) set restrictions on noise levels by zoning. No person shall create or allow the creation of exterior noise that causes the noise level to exceed the noise standards shown in Table 2.
Noise Analysis
Santa Fe Flores Townhomes Project
Table 2
Municipal Code Property Line Noise Standards
Zone Time
Allowable Property
Line Noise Level
[dB(A) Leq]
Single-Family Residential (A, R-1, R-2) 7:00 a.m. to 10:00 p.m. 10:00 p.m. to 7:00 a.m.
60 50
Multi-Family Residential (R-3) 7:00 a.m. to 10:00 p.m.
10:00 p.m. to 7:00 a.m.
65 55
Commercial (C, O-P, SR) 7:00 a.m. to 10:00 p.m.
10:00 p.m. to 7:00 a.m.
65 55
Industrial 7:00 a.m. to 10:00 p.m.
10:00 p.m. to 7:00 a.m.
65 60
dB(A) Leq = A-weighted decibels equivalent noise level
SOURCE: Section 20.300.070(f) Table 20.300-4, San Marcos Municipal Code Title 20 – Zoning Code.
The project site is surrounded by si ngle-family residential uses to the northeast and southeast, multi-family residential uses to the east, a mobile home park to the south, a commercial use to the southwest, and industrial uses to the west and north.
2.3 California Green Building Standards Code –
Environmental Comfort
Interior noise levels for habitable rooms are regulated also by Title 24 of the California Code of Regulations (CCR) California Noise Insulation Standards. Title 24, Chapter 12, Section 1206.4, of the 2019 California Building Code requires that interior noise levels attributable to exterior sources not exceed 45 CNEL in any habitable room. A habitable room is a room used for living, sleeping, eating, or cooking. Bathrooms, closets, hallways, utility spaces, and similar areas are not considered habitable rooms for this regulation (24 CCR, Chapter 12, Section 1206.4).
3.0 Existing Conditions
Existing noise levels in the vicinity of the project site were measured on March 22, 2022 , using one Larson-Davis Model LxT, Type 1 Integrating Sound Level Meter, serial number 3895. The following parameters were used:
Filter: A-weighted
Response: Slow
Interval Period 1 minute
Time History Period: 5 seconds
The meter was calibrated before and after each measurement. The meter was set 5 feet above the ground level for each measurement.
Noise measurements were taken to obtain typical ambient noise levels at the project site and in the vicinity. The weather was sunny and warm. Two 15-minute measurements were taken, as described Noise Analysis
Santa Fe Flores Townhomes Project
below. The measurement locations are shown on Figure 4, and detailed data is contained in Attachment 1.
Measurement 1 was located near the southern project boundary, 50 feet north of S outh Santa Fe Avenue. Noise levels were measured for 15 minutes. The main noise source at this location was vehicle traffic on South Santa Fe Avenue . Vehicle traffic on South Santa Fe Avenue was counted during the measurement period. The average measured noise level was 63.2 dB(A) Leq.
Measurement 2 was located near the eastern project boundary, approximately 50 feet west of North Las Flores Drive. Noise levels were measured for 15 minutes. The main noise source at this location was vehicle traffic on North Las Flores Drive. Secondary sources of noise included vehicle traffic on South Santa Fe Avenue . Vehicle traffic on North Las Flores Drive was counted during the measurement period. The average measured noise level was 57.5dB(A) L eq.
Noise measurements are summarized in Table 3. Traffic counts conducted during Measurements 1 and 2 are summarized in Table 4.
Table 3
Noise Measurements
Measurement Location Time Main Noise Source Leq
1 50 Feet North of
South Santa Fe Avenue 1:34 p.m. – 1:49 p.m. Vehicle Traffic on South Santa Fe Avenue 63.2
2 50 feet west of
North Las Flores Drive 1:55 p.m. – 2:10 p.m. Vehicle traffic on North Las Flores Drive 57.5
L90 = Noise level exceeded 90 percent of the time.
NOTE: Noise measurement data is contained in Attachment 1.
Table 4
15-minute Traffic Counts
Measurement Roadway Direction Autos
Medium
Trucks
Heavy
Trucks Buses Motorcycles
1 South Santa Fe
Avenue
Eastbound 78 8 0 5 0
Westbound 71 4 1 2 0
2 North Las
Flores Drive
Northbound 13 0 0 0 0
Southbound 11 0 0 0 0
FIGURE 4
Noise Measurement Locations
%
%
%
%
%
%
%
%
%
%
%
%
%
%
% % % % % %
%
%
%
%
%
%
%
% % % %
%%
% % % %
%
%
%
%
%
%
%
% % % % % %
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
% % % %
%
%
%
%
%
%
%
% % % % % %
%
%
%
%
%
%
%
%
%
%
%
%
%
%
SPRINTER
1 2
0 200Feet
M:\JOBS6\10587\common_gis\PRO\standard_figures\standardfigures.aprx 07/21/2025 bma [
Project Boundary
Off-site Improvements
Noise Measurement Location
Image Source: Nearmap (flown May 2025)
Noise Analysis
Santa Fe Flores Townhomes Project
4.0 Analysis Methodology
Noise level predictions and contour mapping were developed using noise modeling software, SoundPlan Essential, version 4.1 (Navcon Engineering 2018). SoundPLAN calculates noise propagation based on the International Organization for Standardization method (ISO 9613 -2 – Acoustics, Attenuation of Sound during Propagation Outdoors). The model calculates noise levels at selected receiver locations using input parameter estimates such as total noise generated by each noise source; distances between sources, barriers, and receivers; and shielding provided by intervening terrain, barriers, and structures. The model outputs can be developed as noise level contour maps or noise levels at specific receivers. In all cases, receivers were modeled at 5 feet above ground elevation, which represents the average height of the human ear.
4.1 Construction Noise Analysis
Project construction noise would be generated by diesel engine-driven construction equipment used for site preparation and grading, building construction, loading, unloading, and placing materials and paving. Diesel engine-driven trucks also would bring materials to the site and remove the soils from excavation.
Construction equipment with a diesel engine typically generates maximum noise levels from 70 to 95 dB(A) Leq at a distance of 50 feet (Federal Highway Administration [FHWA] 2006 and 2008, Federal Transit Authority 2018). D uring construction, equipment moves to different locations and goes through varying load cycles, and there are breaks for the operators and for nonequipment tasks, such as measurement. Table 5 summarizes typical construction equipment noise levels and duty cycles.
Table 5
Typical Construction Equipment Noise Levels
Equipment
Noise Level at 50 Feet
(dB(A) Leq) Typical Duty Cycle
Auger Drill Rig 85 20%
Backhoe 80 40%
Blasting 94 1%
Chain Saw 85 20%
Clam Shovel 93 20%
Compactor (ground) 80 20%
Compressor (air) 80 40%
Concrete Mixer Truck 85 40%
Concrete Pump 82 20%
Concrete Saw 90 20%
Crane (mobile or stationary) 85 20%
Dozer 85 40%
Dump Truck 84 40%
Excavator 85 40%
Front End Loader 80 40%
Generator (25 kilovolt amps or less) 70 50%
Generator (more than 25 kilovolt amps) 82 50%
Noise Analysis
Santa Fe Flores Townhomes Project
Table 5
Typical Construction Equipment Noise Levels
Equipment
Noise Level at 50 Feet
(dB(A) Leq) Typical Duty Cycle
Grader 85 40%
Hydra Break Ram 90 10%
Impact Pile Driver (diesel or drop) 95 20%
In situ Soil Sampling Rig 84 20%
Jackhammer 85 20%
Mounted Impact Hammer (hoe ram) 90 20%
Paver 85 50%
Pneumatic Tools 85 50%
Pumps 77 50%
Rock Drill 85 20%
Roller 74 40%
Scraper 85 40%
Tractor 84 40%
Vacuum Excavator (vac-truck) 85 40%
Vibratory Concrete Mixer 80 20%
Vibratory Pile Driver 95 20%
dB(A) Leq = A-weighted decibels average noise level
SOURCE: Federal Highway Administration 2006 and 2008; Federal Transit Authority 2018.
Construction equipment would generate maximum noise levels between 70 and 95 dB(A) maximum noise level ( Lmax) at 50 feet from the source when in operation. During excavation, grading, and paving operations, equipment moves to different locations and goes through varying load cycles, and there are breaks for the operators and for nonequipment tasks, such as measurement. Average construction noise levels were calculated for the simultaneous operation of three common pieces of construction equipment: dozer, e xcavator, and loader . FTA guidance recommends analyzing the two noisiest pieces of construction equipment (FTA 2018), therefore this is a conservative assessment.
The usage factors were applied to the maximum noise level at 50 feet for each piece of equipment, and then noise levels were added logarithmically. Hourly average noise levels would be approximately 85 dB(A) L
eq at 50 feet from the center of construction activity when assessing three pieces of common construction equipment working simultaneously.
4.2 Traffic Noise Analysis
4.2.1 On-site Traffic and Rail Noise
The SoundPLAN program uses the FHWA Traffic Noise Model algorithms and reference levels to calculate noise levels at selected receiver locations. The model uses various input parameters, such as projected hourly average traffic rates; vehicle mix, distribution, and speed; roadway lengths and gradients; distances between sources, barriers, and receivers; and shielding provided by intervening terrain, barriers, and structures. Receivers, roadways, and barriers were input into the model using three-dimensional coordinates. The locations of future buildings were obtained from project plans and drawings.
Noise Analysis
Santa Fe Flores Townhomes Project
The main source of traffic noise at the project site is vehicle traffic on South Santa Fe Avenue and North Las Flores Drive as well as Sprinters on the adjacent rail line. Future year 205 0 with project traffic volumes for South Santa Fe Avenue were obtained from the Traffic Impact Analysis prepared for the project (Linscott, Law & Greenspan , Engineers [LLG] 2026). Future year 2050 traffic volumes for North Las Flores Drive were obtained from San Diego Association of Governments (SANDAG) traffic projections (SANDAG 2025). A vehicle classification mix of 93.0 percent automobiles, 3.0 percent medium trucks, 2.0 percent heavy trucks, 1.0 percent buses, and 1.0 percent motorcycles were modeled. Based on the field traffic counts, this classification mix is conservative.
Table 6 summarizes the traffic volumes and vehicle classification mixes for the modeled roadways.
Table 6
Modeled Vehicle Traffic Parameters
Roadway Segment
Year 2050
Average
Daily Traffic Speed
Vehicle Mix (percent)
Autos
Medium
Trucks
Heavy
Trucks Buses Motorcycles
South
Santa Fe
Avenue
Community Drive to
North Las Flores Drive 22,570 45 93 3 2 1 1
North Las Flores Drive
to North Rancho Santa
Fe Road
21,480 45 93 3 2 1 1
Las Flores
Drive
South of South Santa
Fe Avenue 3,400 25 93 3 2 1 1
North Las
Flores Drive
North of South Santa
Fe Avenue 1,600 25 93 3 2 1 1
The project site is also located approximately 150 feet southwest of the Sprinter rail line. The Sprinter is a light rail commuter train operated by the North County Transit District. The east -west Sprinter rail spans 22 miles from Oceanside to Escondido. The Palomar College Station is the closest Sprinter station to the project site. Fridays experience the largest number of daily Sprinter trains. The number of Friday daytime, evening, and nighttime Sprinter trains was obtained from published schedules and is summarized in Table 7.
Table 7
Modeled Sprinter Trains
Direction
Daytime
7:00 a.m. – 7:00 p.m.
Evening
7:00 p.m. – 10:00 p.m.
Nighttime
10:00 p.m. – 7:00 a.m.
Eastbound 24 6 10
Westbound 24 6 8
TOTAL 48 12 18
4.2.2 Off-site Traffic Noise
Off-site traffic noise was modeled using the FHWA Traffic Noise Prediction Model algorithms and reference levels. Traffic noise levels were calculated at 50 feet from the centerline of the affected roadways to determine the noise level increase associated with the project. The model uses various input parameters, such as traffic volumes, vehicle mix, distribution, and speed.
Noise Analysis
Santa Fe Flores Townhomes Project
The roadways included in the traffic impact analysis are South Santa Fe Avenue, Hollencrest Road, and North Rancho Santa Fe Road . Traffic noise levels were calculated based on the total average daily traffic volumes on each roadway segment. For modeling purposes, “hard” ground conditions were used for the analysis of future conditions, since a majority of the project area is paved and the hard site provides the most conservative impact assessment.
Existing (year 2022), near term (year 2027 ), and future (year 2050) traffic volumes with and without the project were obtained from the project traffic impact analysis ( LLG 2026). Table 8 summarizes the future traffic volumes for the area roadway segments. Modeled noise levels do not account for shielding provided by intervening barriers and structures.
Table 8
Future Vehicle Traffic Parameters
Roadway Segment
Average Daily Traffic
Speed
(mph) Existing
Existing
+
Project
Year
2027
Year
2027 +
Project
Year
2050
Year
2050 +
Project
South Santa Fe Avenue
Similax Road to Bosstick Boulevard 14,850 14,960 16,110 16,220 22,200 22,310 45 Bosstick Boulevard to Community Drive 16,660 16,770 18,080 18,190 22,200 22,310 45 Community Drive to North Las Flores Drive 16,660 17,030 18,080 18,450 22,200 22,570 45 North Las Flores Drive to North Rancho
Santa Fe Road 14,600 14,780 15,840 16,020 21,300 21,480 45 North Rancho Santa Fe Road to North
Pacific Street 13,500 13,570 14,650 14,720 24,400 24,470 40 Hollencrest Road
De Leone Road to Hollenbeck Road 560 600 610 650 830 870 25 North Rancho Santa Fe Avenue
South Santa Fe Avenue to Capalina Road 11,730 11,840 12,730 12,840 16,800 16,910 40 mph = miles per hour
SOURCE: Linscott, Law & Greenspan, Engineers, Inc. 2026.
4.3 On-site Generated Noise Analysis
On-site noise sources on the project site after completion of construction are anticipated to be those that would be typical of any multi-family use, such as vehicles arriving and leaving, children at play, and landscape maintenance machinery. None of these noise sources are anticipated to violate the City Municipal Code or result in a substantial permanent increase in existing noise levels. However, the project would include rooftop heating, ventilation, and air conditioning (HVAC) equipment. Noise levels due to HVAC equipment were modeled and compared to City limits (see Table 2).
The HVAC equipment would be located on the roof with screened walls. It is not known at this time which manufacturer, brand, or model of unit or units will be selected for use in the project. For the purposes of this analysis, to determine what general noise levels the HVAC units would generate, it was assumed that the rooftop units would be similar to a Carrier unit with a sound power level of 75 dB(A). Noise specifications are contained in Attachment 2. All units were modeled at full capacity during the daytime and nighttime hours.
Noise Analysis
Santa Fe Flores Townhomes Project
Noise levels due to on -site sources were modeled using SoundPLAN. The SoundPLAN program models noise propagation following the International Organization for Standardization method ISO 9613-2 – Acoustics, Attenuation of Sound during Propagation Outdoors . The model calculates noise levels at selected receiver locations using input parameter estimates such as total noise generated by each noise source; distances between sources, barriers, and receivers; and shielding provided by intervening structures.
5.0 Future Acoustical Environment and Impacts
5.1 Construction Noise
Noise associated with the grading, building, and paving for the project would potentially result in short-term impacts to surrounding residential properties. There are residential uses located northeast, east, southeast, and south of the project site. A variety of noise-generating equipment would be used during the construction phase of the project, such as excavators, backhoes, front-end loaders, and concrete saws, along with others. The exact number and pieces of construction equipment required are not known at this time. As discussed, average construction noise levels were calculated. Based on this analysis, hourly average noise levels would be approximately 85 dB(A) L eq
at 50 feet from the center of construction activity when assessing three pieces of common construction equipment working simultaneously. Construction noise is considered a point source and would attenuate at approximately 6 dB(A) for every doubling of distance. To reflect the nature of grading and construction activities, equipment was modeled as an area source distributed over the project footprint. Noise levels were modeled at a series of 18 receivers located at the adjacent uses. The results are summarized in Table 9. Modeled receiver locations and construction noise contours are shown in Figure 5. SoundPLAN data is contained in Attachment 3.
Table 9
Construction Noise Levels
Receiver Land Use
Noise Level
[dB(A) Leq]
1 Single-Family Residential 58
2 Single-Family Residential 60
3 Single-Family Residential 61
4 Single-Family Residential 60
5 Single-Family Residential 59
6 Multi-Family Residential 56
7 Multi-Family Residential 58
8 Multi-Family Residential 68
9 Multi-Family Residential 70
10 Single-Family Residential 63
11 Mobile Home Park 66
12 Mobile Home Park 65
13 Mobile Home Park 61
14 Mobile Home Park 59
15 Industrial 68
16 Industrial 66
17 Industrial 73
18 Commercial 73
dB(A) Leq = A-weighted decibels equivalent noise level
Noise Analysis
Santa Fe Flores Townhomes Project
As shown, construction noise levels would range from 56 to 73 dB(A) Leq at the adjacent uses. The City’s Municipal Code does not place noise limit restrictions on construction activities; however, other jurisdictions commonly apply a noise level limit of 75 dB(A) Leq at residential uses. Construction noise levels would not exceed 75 dB(A) L eq. Construction activities would generally occur over the period between 7:00 a.m. and 6:00 p.m. on weekdays. Although the existing adjacent uses would be exposed to construction noise levels that may be heard above ambient conditions, the exposure would be temporary and would not exceed 75 dB(A) Leq. As construction activities associated with the project would comply with the time limits established in Section 10.24.020 (b)(9) of the City Municipal Code, temporary increases in noise levels from construction activities would be less than significant.
5.2 Traffic Noise
5.2.1 On-site Traffic and Rail Noise
On-site traffic and rail noise contours were developed using the SoundPLAN program. Noise level contours were modeled at the first-floor level. These contours take into account shielding provided by the proposed buildings and grading. Future vehicle and rail traffic noise-level contours are shown in Figure 6. SoundPLAN data are contained in Attachment 4.
As discussed in Section 2.1, the exterior noise level standard for multi-family uses is 65 CNEL. This standard is applicable at exterior use areas which include second- and third-floor balconies, rooftop decks, and the five proposed amenity areas consisting of active play areas and passive gathering areas The interior noise level standard is 45 CNEL. To refine the noise analysis and determine noise levels at exterior use areas and the building façade, exterior noise levels were calculated at a series of fir st- through third-floor specific receiver locations at the outdoor use areas and around the proposed building. Modeled receiver locations are shown in Figure 6. Table 10 summarizes the projected future noise levels at the 26 modeled receivers. Modeled noise levels shown in Table 10 do not include noise reduction provided by any noise barriers.
FIGURE 5
Construction Noise Contours
%
%
%
%
%
%
%
%
%
%
%
%
%
%
% % % % % %
%
%
%
%
%
%
%
% % % %
%%
% % % %
%
%
%
%
%
%
%
% % % % % %
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
% % % %
%
%
%
%
%
%
%
% % % % % %
%
%
%
%
%
%
%
%
%
%
%
%
%
%
LA
S
FLORES
DR
VIA LA
VENTA
NLAS FLOR
ES DR
NORMANSTRASSE
RD
S SANTA FE AVE
DELEONE RD
SPRINTER
1 2
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18
0 200Feet
M:\JOBS6\10587\common_gis\PRO\standard_figures\standardfigures.aprx 12/17/2025 bma [
Project Boundary
Off-site Improvements
Receivers
Construction Noise
60 dB(A) Leq
65 dB(A) Leq
70 dB(A) Leq
75 dB(A) Leq
Image Source: Nearmap (flown May 2025)
FIGURE 6
Future Vehicle and Rail Noise Contours
%
%
%
%
%
%
%
%
% % % % % % % %
% % % % % % % %
% % % % % % % %
% % % % % % % %
%
%
%
%
%
%
%
%
% % % % % % %
% % % % % % % % %
%
%
%
%
%
%
%
SPRINTER
1 2
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
25 26
27 28
29 30
31 0 150Feet
M:\JOBS6\10587\common_gis\PRO\standard_figures\standardfigures.aprx 12/02/2025 bma [
Project Boundary
Off-site Improvements
Receivers
Site Plan
Amenity Area A 6-foot Barrier
Buildings
Vehicle and Rail Noise
50 CNEL
55 CNEL
60 CNEL
65 CNEL
Image Source: Nearmap (flown May 2025)
Noise Analysis
Santa Fe Flores Townhomes Project
Table 10
Future Vehicle and Rail Traffic Noise Levels
Receiver Location
Exterior Noise Level (CNEL)
First-Floor Second-Floor Third-Floor
1 Amenity Area A 68 -- --
2 Amenity Area B 46 -- --
3 Amenity Area C 50 -- --
4 Amenity Area D 46 -- --
5 Amenity Area E 54 -- --
6 Amenity Area E 42 -- --
7 Building 1 61 63 65
8 Building 1 67 69 70
9 Building 1 63 65 66
10 Building 1 and 2 49 53 55
11 Building 2 57 61 61
12 Building 2 46 50 52
13 Building 2 54 58 60
14 Building 3 54 55 56
15 Building 3 58 60 61
16 Building 3 57 60 60
17 Building 3 and 4 45 49 51
18 Building 4 51 55 59
19 Building 4 48 51 52
20 Building 4 46 51 52
21 Building 5 46 50 51
22 Building 5 45 49 50
23 Building 5 48 54 56
24 Building 5 and 6 43 49 50
25 Building 6 51 56 57
26 Building 6 55 58 59
27 Building 6 49 53 55
28 Building 7 43 45 49
29 Building 7 47 56 60
30 Building 7 59 63 65
31 Building 7 54 56 58
CNEL = community noise equivalent level
Bold = Exceeds 65 CNEL
As shown, exterior noise levels are projected to range from 42 to 70 CNEL at the building façade s and amenity areas. Noise levels would be compatible with the City’s exterior multi-family noise level standard of 65 CNEL at all locations except the amenity area on the south side of Building 1 (Amenity Area A, Receiver 1) and the south and east sides of Building 1 facing the roadways (Receivers 8 and 9). There are second-floor balconies on the south side of Building 1 and third-floor balconies on the east side of Building 1 and a rooftop deck. These balconies and rooftop deck could be exposed to noise levels that exceed 65 CNEL. Based upon these findings, noise control recommendations are necessary at the amenity area south of Building 1, at the balconies on the south and east sides of Building 1, and on the south and east sides of the Building 1 roof deck in order to comply with the City’s noise standard of 65 CNEL. A 6-foot barrier adjacent to the amenity area as shown in Figure 6 was modeled using SoundPLAN and would be necessary to reduce noise levels to 65 CNEL or less Noise Analysis
Santa Fe Flores Townhomes Project
at this active play area. Modeling data is provided in Attachment 4. To determine the required barrier heights at the Building 1 balconies and roof deck, the Fresnel barrier noise reductions were modeled.
The balcony and roof deck barriers were modeled using this equation -based method rather than SoundPLAN because of the geometry of these barriers when elevated on balconies and the roof deck. These reductions are based on distance, source height, receiver elevation, and barrier height.
The Fresnel barrier reduction calculations are provided as Attachment 5. It was calculated that a
3.5-foot balcony barrier would provide a 7.4 dB reduction at the balconies on the south side of Building 1 (Receiver 2), a 5.9 dB reduction at the balconies on the east side of Building 1 (Receiver 3), and a 7.0 dB reduction on the roof deck. In order to reduce noise levels at these locations, the project would include a 3.5-foot balcony railing as a solid barrier. With construction of these barriers, exterior noise levels would be reduced to less than 65 CNEL.
The interior noise level standard is 45 CNEL. Interior noise levels can be reduced through standard construction techniques. When windows are closed, standard construction techniques provide various exterior-to-interior noise level reductions depending on the type of structure and window.
Standard light-frame construction would reduce exterior to interior noise levels by at least 20 dB (FHWA 2011).
As shown in Table 10, noise levels would be as high as 70 CNEL at the south side of Building 1 and 66 CNEL at the east side of Building 1. While the proposed 3.5 -foot balcony barriers would reduce noise levels to 65 CNEL at a seated receiver, the entire building façade would not get the same noise attenuation, and the evaluation of specific building components is required. The sound transmission class (STC) rating of windows, walls, and roofs is an integer value that rates how well a building component attenuates noise. The STC rating generally reflects the decibel reduction that a building component can achieve. Standard walls and roofs typically have STC ratings greater than 40, while window components have lower ratings; thus, this analysis focuses on the minimum required window STC ratings. Because a noise reduction of up to 25 dB(A) is required to achieve interior noise levels of 45 CNEL or less, window components with an STC rating of 25 or higher are required for units located on the south and east side of Building 1. With the installation of windows with an STC rating of 25 or higher, interior noise levels within the units in Building 1 would be reduced to 45 CNEL and interior noise levels would be less than significant. Interior noise levels at all other buildings would be 45 CNEL with standard light frame construction and without consideration of specific building components.
5.2.2 Off-site Traffic Noise
The project would increase traffic volumes on local roadways. However, t he project would not substantially alter the vehicle classifications mix on local or regional roadways, nor would the project alter the speed on an existing roadway or create a new roadway. Thus, the primary factor affecting off-site noise levels would be increased traffic volumes. While changes in noise levels would occur along any roadway where project -related traffic occurs, for noise assessment purposes, noise level increases are assumed to be greatest nearest the project site, as this location would represent the greatest concentration of project -related traffic. Traffic noise increases attributable to the project were assessed against a significance threshold of 3 dB, which is the level at which an increase in noise is considered to be barely perceptible (Caltrans 2013).
Noise Analysis
Santa Fe Flores Townhomes Project
Table 11 presents a conservative assessment of traffic noise levels based on the existing, near term (year 2027), and future (year 2050) noise levels without and with the project. Table 11 also summarizes the direct and cumulative traffic noise level increases due to the project. Noise level calculations are contained in Attachment 6.
Table 11
Traffic Noise Level with and without Project and Ambient Noise Increases (CNEL)
Roadway Segment
Existing Near-Term (Year 2027) Future (Year 2050) Cumulative Increase
Over
Existing
No
Project Project Increase
No
Project Project Increase
No
Project Project Increase
South Santa Fe Avenue
Similax Road to Bosstick
Boulevard 71.3 71.3 0.0 71.6 71.7 0.1 73.0 73.1 0.1 1.8 Bosstick Boulevard to
Community Drive 71.8 71.8 0.0 72.1 72.2 0.1 73.0 73.1 0.1 1.3 Community Drive to
North Las Flores Drive 71.8 71.9 0.1 72.1 72.2 0.1 73.0 73.1 0.1 1.3 North Las Flores Drive
to North Rancho Santa
Fe Road 71.2 71.3 0.1 71.6 71.6 0.0 72.9 72.9 0.0 1.7
North Rancho Santa Fe
Road to North Pacific
Street 69.8 69.8 0.0 70.1 70.1 0.0 72.3 72.3 0.0 2.5
Hollencrest Road
De Leone Road to
Hollenbeck Road 52.7 53.0 0.3 53.1 53.4 0.3 54.4 54.6 0.2 1.9 North Rancho Santa Fe Avenue
South Santa Fe Avenue
to Capalina Road 69.1 69.2 0.1 69.5 69.5 0.0 70.7 70.7 0.0 1.6 NOTE: Increase calculations may vary due to independent rounding.
As shown, the project would not result in a direct or cumulative noise increase of more than 3 dB.
Therefore, the project would result in less than significant direct and cumulative impacts related to traffic noise.
5.3 On-site Generated Noise
The primary noise sources on-site would be HVAC equipment. Rooftop HVAC equipment that would have the potential to produce noise in excess of City limits (see Table 2). Using the on -site noise source parameters discussed in Section 4.3, noise levels were modeled at a series of 17 receivers located at the adjacent properties. Noise generated by HVAC equipment would occur on an intermittent basis, primarily during the day and evening hours and less frequently during the nighttime hours. For a worst -case analysis, it was assumed that the HVAC units would operate at maximum capacity during the daytime and nighttime hours.
Modeled receivers and the locations of the HVAC units are shown in Figure 7. Modeled data is included in Attachment 7. Future projected noise levels are summarized in Table 12.
FIGURE 7
HVAC Noise Contours
%
%
%
%
%
%
%
%
%
%
%
%
%
%
% % % % % %
%
%
%
%
%
%
%
% % % %
% % % %
%
%
%
%
%
%
%
% % % % % %
%
%
%
%
%
%
%
%
%
%
%
%
%
%
% % % %
%
%
%
%
%
%
%
% % % % % %
%
%
%
%
%
%
%
%
%
%
%
%
%
%
SPRINTER
1 2
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18
0 200Feet
M:\JOBS6\10587\common_gis\PRO\standard_figures\standardfigures.aprx 12/17/2025 bma [
Project Boundary
Off-site Improvements
Receivers
HVAC
Site Plan
Buildings
HVAC Noise
30 dB(A) Leq
35 dB(A) Leq
40 dB(A) Leq
45 dB(A) Leq
Image Source: Nearmap (flown May 2025)
Noise Analysis
Santa Fe Flores Townhomes Project
As shown, HVAC noise levels would range from 33 to 42 dB(A) Leq. Noise levels would not exceed the applicable Noise Ordinance limits at the property lines and impacts related to on-site generated noise would be less than significant.
Table 12
HVAC Noise Levels at Adjacent Properties
Receiver Land Use
Noise Level
[dB(A) Leq]
Noise Ordinance Limit
Daytime/Nighttime
[dB(A) Leq]
1 Single Family Residential 33 60/50
2 Single Family Residential 35 60/50
3 Single Family Residential 36 60/50
4 Single-Family Residential 35 60/50
5 Single-Family Residential 34 60/50
6 Multi-Family Residential 34 65/55
7 Multi-Family Residential 35 65/55
8 Multi-Family Residential 42 65/55
9 Multi-Family Residential 41 65/55
10 Single-Family Residential 35 60/50
11 Mobile Home Park 36 65/55
12 Mobile Home Park 36 65/55
13 Mobile Home Park 35 65/55
14 Mobile Home Park 34 65/55
15 Industrial 39 65/60
16 Industrial 38 65/60
17 Industrial 40 65/60
18 Commercial 39 65/55
dB(A) Leq = A-weighted decibels equivalent noise level
6.0 Conclusions
6.1 Construction Noise
As shown in Table 9, construction noise levels would range from 56 to 73 dB(A) Leq at the adjacent property lines. The City’s Municipal Code does not place noise limit restrictions on construction activities, however, other jurisdictions commonly apply a noise level limit of 75 dB(A) L eq at residential
uses. Construction activities would generally occur over the period between 7:00 a.m. and 6:00 p.m. on weekdays. Although the existing adjacent uses would be exposed to construction noise levels that may be heard above ambient conditions, the exposure would be temporary and would not exceed 75 dB(A) L
eq. As construction activities associated with the project would comply with the time limits established in Section 10.24.020 (b)(9) of the City Municipal Code, temporary increases in noise levels from construction activities would be less than significant.
Noise Analysis
Santa Fe Flores Townhomes Project
6.2 Traffic Noise
6.2.1 On-site Traffic and Rail Noise
The main source of noise at the project site is vehicle traffic on South Santa Fe Avenue and North Las Flores Drive as well as Sprinters on the adjacent rail line . The exterior noise level standard for multi-family uses is 65 CNEL. This standard is applicable at exterior use areas which include second- and third-floor balconies, rooftop decks, and the five proposed amenity areas consisting of active play areas and passive gathering areas . As shown in Table 10 , without consideration of any noise barriers, exterior noise levels are projected to range from 42 to 70 CNEL at the building façades and amenity area. Noise levels would be compatible with the City’s exterior multi-family noise level standard of 65 CNEL at all locations except the amenity area on the south side of Building 1 (Amenity Area A, Receiver 1) and the south and east sides of Building 1 facing the roadways (Receivers 8 and 9). In order to reduce noise levels at these locations, the project would include a 6-foot barrier adjacent to the amenity area south of Building 1, and a solid 3.5-foot barrier on the balconies located on the south and east sides of Building 1 and on the south and east sides of the Building 1 roof deck.
With construction of these barriers, exterior noise levels would be reduced to less than 65 CNEL and exterior noise impacts would be less than significant.
The interior noise level standard is 45 CNEL. Interior noise levels can be reduced through standard construction techniques. When windows are closed, standard construction techniques provide various exterior-to-interior noise level reductions depending on the type of structure and window.
Standard light-frame construction would reduce exterior to interior noise levels by at least 20 dB (FHWA 2011). With the installation of windows with an STC rating of 25 or higher, interior noise levels within the units in Building 1 would be reduced to 45 CNEL and interior noise levels would be less than significant. Interior noise levels at all other buildings would be 45 CNEL with standard light frame construction and without consideration of specific building components.
6.2.2 Off-site Traffic Noise
The additional vehicle trips associated with the project would increase noise levels on nearby roadways. A noise increase of 3 dB or more would be considered significant because 3 dB is the level at which an increase in noise is perceptible to a person. As shown in Table 11, the project would not result in a direct or cumulative noise increase of more than 3 dB. Therefore, the project would result in less than significant direct and cumulative impact related to traffic noise.
6.3 On-site Generated Noise
The noise sources on the project site after completion of construction are anticipated to be those that would be typical of any residential use, such as vehicles arriving and leaving, children at play, and landscape maintenance machinery. None of these noise sources are anticipated to violate the City Municipal Code. Rooftop HVAC noise levels were modeled at the adjacent properties. As shown in Table 12, HVAC noise levels would range from 33 to 42 dB(A) Leq. Noise levels would not exceed the applicable Noise Ordinance limits at the property lines.
Noise Analysis
Santa Fe Flores Townhomes Project
7.0 References Cited
California Department of Transportation (Caltrans)
2013 Technical Noise Supplement. November.
Federal Highway Administration (FHWA)
2006 Roadway Construction Noise Model. FHWA-HEP-05-054, SOT-VNTSC-FHWA-05-01. Final Report. January.
2008 Roadway Construction Noise Mode, V1.1. Washington, D.C.
2011 Highway Traffic Noise: Analysis and Abatement Guidance. FHWA-HEP-10-025. December.
Federal Transit Administration (FTA)
2018 Transit Noise and Vibration Impact Assessment. FTA Report No. 0123. Prepared by John A.
Volpe National Transportation Systems Center. September.
Linscott, Law, & Greenspan, Engineers, Inc. (LLG)
2026 Local Transportation Analysis for the Santa Fe Flores Project. LLG Ref. 3-24-3940. January.
Navcon Engineering, Inc.
2018 SoundPLAN Essential version 4.1.
San Diego Association of Governments (SANDAG)
2025 Transportation Forecast Information Center. Year 2050 ABM2+/2021 RP Traffic Volumes.
Accessed January 20, 2025. https://tfic.sandag.org/.
San Marcos, City of
2012 City of San Marcos General Plan Update, Noise Element.
Noise Analysis
Santa Fe Flores Townhomes Project
ATTACHMENTS
Noise Analysis
Santa Fe Flores Townhomes Project
ATTACHMENT 1
Noise Measurement Data
10587 Santa Fe Flores Townhomes
Noise Measurement Data
Summary
Start 2022/03/22 13:34:51
Stop 2022/03/22 13:49:56
Duration 0:15:04.7
Run Time 0:15:02.6
Pause 0:00:02.1
Pre Calibration 2022/03/22 13:33:32
Post Calibration None
Calibration Deviation ---
Overall Settings
RMS Weight A Weighting
Peak Weight A Weighting
Detector Slow
Preamp PRMLxT1
Microphone Correction Off
Integration Method Linear
Overload 144.6 dB
A C Z
Under Range Peak 100.6 97.6 102.6 dB
Under Range Limit 37.8 37.4 44.5 dB
Noise Floor 28.6 28.3 35.3 dB
Results
LAeq 63.2 dB
LAE 92.8 dB
EA 210.368 µPa²h
EA8 6.712 mPa²h
EA40 33.562 mPa²h
LApeak (max) 2022/03/22 13:37:15 101.8 dB
LASmax 2022/03/22 13:39:26 74.7 dB
LASmin 2022/03/22 13:46:59 51.6 dB
SEA -99.9 dB
LAS > 60.0 dB (Exceedence Counts / Duration) 31 563.6 s LAS > 70.0 dB (Exceedence Counts / Duration) 6 27.3 s
LApeak > 135.0 dB (Exceedence Counts / Duration) 0 0.0 s LApeak > 137.0 dB (Exceedence Counts / Duration) 0 0.0 s LApeak > 140.0 dB (Exceedence Counts / Duration) 0 0.0 s LCeq 75.2 dB
LAeq 63.2 dB
LCeq - LAeq 12.0 dB
LAIeq 65.0 dB
LAeq 63.2 dB
LAIeq - LAeq 1.8 dB
# Overloads 0
Overload Duration 0.0 s
Dose Settings
Dose Name OSHA-1 OSHA-2
Exch. Rate 5 5 dB
Threshold 90 80 dB
Criterion Level 90 90 dB
Criterion Duration 8 8 h
Results
Dose -99.9 -99.9 %
Projected Dose -99.9 -99.9 %
TWA (Projected) -99.9 -99.9 dB
TWA (t) -99.9 -99.9 dB
Lep (t) 48.2 48.2 dB
Statistics
LAS5.00 68.6 dB
LAS10.00 66.6 dB
LAS33.30 62.9 dB
LAS50.00 60.5 dB
LAS66.60 58.4 dB
LAS90.00 55.0 dB
Measurement 1
10587 Santa Fe Flores Townhomes
Noise Measurement Data
Summary
Start 2022/03/22 13:55:50
Stop 2022/03/22 14:10:51
Duration 0:15:00.5
Run Time 0:15:00.5
Pause 0:00:00.0
Pre Calibration 2022/03/22 13:33:30
Post Calibration None
Calibration Deviation ---
Overall Settings
RMS Weight A Weighting
Peak Weight A Weighting
Detector Slow
Preamp PRMLxT1
Microphone Correction Off
Integration Method Linear
Overload 144.6 dB
A C Z
Under Range Peak 100.6 97.6 102.6 dB
Under Range Limit 37.8 37.4 44.5 dB
Noise Floor 28.6 28.3 35.3 dB
Results
LAeq 57.5 dB
LAE 87.0 dB
EA 55.989 µPa²h
EA8 1.791 mPa²h
EA40 8.953 mPa²h
LApeak (max) 2022/03/22 14:03:57 102.3 dB
LASmax 2022/03/22 14:09:26 66.5 dB
LASmin 2022/03/22 14:03:45 49.9 dB
SEA -99.9 dB
LAS > 60.0 dB (Exceedence Counts / Duration) 19 185.3 s LAS > 70.0 dB (Exceedence Counts / Duration) 0 0.0 s
LApeak > 135.0 dB (Exceedence Counts / Duration) 0 0.0 s LApeak > 137.0 dB (Exceedence Counts / Duration) 0 0.0 s LApeak > 140.0 dB (Exceedence Counts / Duration) 0 0.0 s LCeq 66.1 dB
LAeq 57.5 dB
LCeq - LAeq 8.6 dB
LAIeq 59.3 dB
LAeq 57.5 dB
LAIeq - LAeq 1.8 dB
# Overloads 0
Overload Duration 0.0 s
Dose Settings
Dose Name OSHA-1 OSHA-2
Exch. Rate 5 5 dB
Threshold 90 80 dB
Criterion Level 90 90 dB
Criterion Duration 8 8 h
Results
Dose -99.9 -99.9 %
Projected Dose -99.9 -99.9 %
TWA (Projected) -99.9 -99.9 dB
TWA (t) -99.9 -99.9 dB
Lep (t) 42.4 42.4 dB
Statistics
LAS5.00 61.7 dB
LAS10.00 60.6 dB
LAS33.30 57.6 dB
LAS50.00 56.1 dB
LAS66.60 54.4 dB
LAS90.00 52.7 dB
Measurement 2
Noise Analysis
Santa Fe Flores Townhomes Project
ATTACHMENT 2
HVAC Specifications
1 50VG - - -A
Performancet 16 SEER 2 - - -Stage Packaged
Air Conditioner System with Puron R (R - - -410A)
Refrigerant
Single and Three Phase
2t o5N o m i n a lT o n s( S i z e s2 4 - - - 6 0 )
Product Data
A09033
Fig. 1 - - Unit 50VG- -A
Single- -Packaged Products with Energy- -Saving Features and PuronR refrigerant.
S 15.0- -16.0 SEER / 12.0- -12.5 EER
S Factory- -Installed TXV
S Multi- -speed ECM Blower Motor - - Standard
S Sound levels as low as 72dBA
S Two Stages of Cooling
S Dehumidification Feature
FEATURES/BENEFITS
One- -piece cooling unit with optional electric heater, low sound levels, easy installation, low maintenance, and dependable performance.
Puron Environmentally Sound Refrigerant is Carrier’s unique refrigerant designed to help protect the environment. Puron is an HFC refrigerant which does not contain chlorine that can harm the ozone layer. Puron refrigerant is in service in millions of systems proving highly reliable, environmentally sound performance.
Easy Installation
Factory- -assembled package is a compact, fully self- -contained, electric cooling unit that is prewired, pre- -piped, and pre- -charged for minimum installation expense. These units are available in a variety of standard cooling sizes with voltage options to meet residential and light commercial requirements. Units are lightweight and install easily on a rooftop or at ground level. The high tech composite base eliminates rust problems associated with ground level applications.
Innovative Unit Base Design
On the inside a high- -tech composite material will not rust and incorporates a sloped drain pan which improves drainage and helps inhibit mold, algae and bacterial growth. On the outside metal base rails provide added stability as well as easier handling and rigging.
Convertible duct configuration
Unit is designed for use in either downflow or horizontal applications. Each unit is converted from horizontal to downflow and includes horizontal duct covers. Downflow operation is provided in the field to allow vertical ductwork connections. The basepan seals on the bottom openings to ensure a positive seal in the vertical airflow mode.
Efficient operation High- -efficiency design offers SEER (Seasonal Energy Efficiency Ratios) of up to 16.0. (See page 4.) Durable, dependable components
Scroll Compressors have 2 stages of cooling and are designed for high efficiency. Each compressor is hermetically sealed against contamination to help promote longer life and dependable operation. Each compressor also has vibration isolation to provide quieter operation. All compressors have internal high pressure and overcurrent protection.
Multi- -speed ECM Blower Motor is standard on all 50VG- -A.
Direct- -drive PSC (Permanent Split Capacitor) condenser- -fan motors are designed to help reduce energy consumption and provide for cooing operation down to 40 _F( 4 . 4_C) outdoor temperature. Motormaster r II low ambient kit is available as a field- -installed accessory.
Thermostatic Expansion Valve - - A hard shutoff, balance port TXV maintains a constant superheat at the evaporator exit (cooling cycle) resulting in higher overall system efficiency.
Refrigerant system is designed to provide dependability. Liquid filter driers are used to promote clean, unrestricted operation. Each unit leaves the factory with a full refrigerant charge. Refrigerant service connections make checking operating pressures easier.
High and Low Pressure Switches provide added reliability for the compressor.
Indoor and Outdoor coils are computer- -designed for optimum heat transfer and efficiency. The indoor coil is fabricated from copper tube and aluminum fins and is located inside the unit for protection against damage. The outdoor coil is internally mounted on the top tier of the unit.
Low sound ratings ensure a quiet indoor and outdoor
environment with sound ratings as low as 72dBA. (See Page 4.) Easy to service cabinets provide easy 3 panel accessibility to serviceable com ponents during maintenance and installation. The basepan with integrated drain pan provides easy ground level installation with a mounting pad. A nesting feature ensures a positive basepan to roof curb seal when the unit is roof m ounted. A convenient 3/4- -in. (19.05 mm) wide perimeter flange makes frame mounting on a rooftop easy.
4 AHRI* CAPACITIES
Cooling Capacities and Efficiencies
Unit Model
50VG-A
Nominal
To n s
Standard CFM
(High / Low Stage)
Net Cooling
Capacities - Btuh
(High Stage)
EER @A** SEER†
24 2 800 / 600 23000 12.0 15.0
30 2-1/2 1000 / 750 29000 12.0 15.0
36 3 1200 / 900 35400 12.5 16.0
42 3-1/2 1400 / 1050 42000 12.5 16.0
48 4 1600 / 1200 47500 12.3 16.0
60 5 1750 / 1200 57000 12.3 16.0
LEGEND
d B ---Sound Levels (decibels)
db—Dry Bulb
SEER—Seasonal Energy Efficiency Ratio
wb—Wet Bulb
COP - - -Coefficient of Performance
* Air Conditioning, Heating & Refrigeration Institute.
**At “A ” conditions - - -80_F (26.7_C) indoor db/67 _F (19.4_C) indoor wb & 95_F( 3 5_C) outdoor db.
{ Rated in accordance with U.S. Government DOE Department of Energy) test procedures and/or AHRI Standards 210/240.
Notes:
1. Ratings are net values, reflecting the effects of circulating fan heat.
Ratings are based on:
Cooling Standard: 80F (26.7_C) db, 67 F wb (19.4 _C ) i n d o o r e n t e r i n g --- a i r temperature and 95 Fd b( 3 5_C) outdoor entering - - -air temperature.
2. Before purchasing this appliance, read important energy cost and effi- ciency information available from AHRIdirectory.org.
A- -WEIGHTED SOUND POWER LEVEL (dBA)
Model 50VG-A Sound Ratings
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment) 125 250 500 1000 2000 4000 8000
24 73 60.0 62.5 68.5 68.5 64.0 60.0 53.0
30 77 57.5 67.0 73.5 72.0 67.0 61.0 52.5
36 73 62.5 65.5 67.5 68.0 65.5 60.0 52.5
42 73 60.5 63.5 68.0 68.0 66.0 60.5 53.0
48 72 60.0 63.5 66.0 67.0 63.5 58.5 49.5
60 75 69.0 67.0 69.0 68.0 65.0 61.5 54.0
NOTE: Tested in accordance with AHRI Standard 270 (not listed in AHRI). 50VG -- A
Noise Analysis
Santa Fe Flores Townhomes Project
ATTACHMENT 3
SoundPLAN Data – Construction Noise
10587 Santa Fe Flores Townhomes
SoundPLAN Data - Construction
Noise
Source name Reference Level Cwall CI CT
dB(A) dB(A) dB(A) dB(A)
Construction Lw/unit 116.3 - - -
Corrections
Construction
10587 Santa Fe Flores Townhomes
SoundPLAN Data - Construction
Noise
No. X Y Height Level
(meters) dB(A)
1 481468.23 3668972.47 182.38 58.4
2 481477.03 3668933.16 185.26 60.2
3 481491.51 3668901.09 186.46 60.8
4 481513.24 3668863.85 186.82 59.9
5 481534.96 3668832.30 186.16 58.7
6 481452.72 3668803.33 161.69 56.1
7 481417.03 3668787.30 160.02 57.7
8 481389.61 3668758.33 159.09 67.6
9 481373.58 3668720.06 157.61 69.9
10 481348.75 3668660.57 154.54 63.1
11 481317.72 3668679.71 153.92 66.0
12 481280.47 3668693.16 153.14 64.7
13 481232.89 3668717.47 152.07 61.4
14 481185.82 3668741.78 151.46 58.9
15 481288.85 3668803.43 156.64 67.9
16 481306.71 3668845.77 157.91 66.3
17 481370.21 3668885.46 167.46 73.2
18 481303.57 3668756.45 153.75 72.6
Coordinates
(meters)
Receivers
Noise Analysis
Santa Fe Flores Townhomes Project
ATTACHMENT 4
SoundPLAN Data – On-site Traffic and Rail Noise
10587 Santa Fe Flores Townhomes
SoundPLAN Data - Vehicle and Rail Traffic
Traffic values Control Constr. Affect. Gradient
Station ADT Vehicles type Vehicle nameday evening night Speed device Speed veh. Road surface Min / Max km Veh/24h Veh/h Veh/h Veh/h km/h km/h % %
S Santa Fe Avenue Traffic direction: In entry direction 0+000 21474 Total - 1378 716 310 - none - - Average (of DGAC and PCC) 2.481481481 0+000 21474 Automobiles - 1282 666 288 72 none - - Average (of DGAC and PCC) 2.481481481 0+000 21474 Medium trucks - 41 21 9 72 none - - Average (of DGAC and PCC) 2.481481481 0+000 21474 Heavy trucks - 28 14 6 72 none - - Average (of DGAC and PCC) 2.481481481 0+000 21474 Buses - 14 7 3 72 none - - Average (of DGAC and PCC) 2.481481481 0+000 21474 Motorcycles - 14 7 3 72 none - - Average (of DGAC and PCC) 2.481481481 0+000 21474 Auxiliary vehicle - - - - - none - - Average (of DGAC and PCC) 2.481481481 0+426 22566 Total - 1448 752 326 - none - - Average (of DGAC and PCC) -2.923076923 0+426 22566 Automobiles - 1347 699 303 72 none - - Average (of DGAC and PCC) -2.923076923 0+426 22566 Medium trucks - 43 23 10 72 none - - Average (of DGAC and PCC) -2.923076923 0+426 22566 Heavy trucks - 29 15 7 72 none - - Average (of DGAC and PCC) -2.923076923 0+426 22566 Buses - 14 8 3 72 none - - Average (of DGAC and PCC) -2.923076923 0+426 22566 Motorcycles - 14 8 3 72 none - - Average (of DGAC and PCC) -2.923076923 0+426 22566 Auxiliary vehicle - - - - - none - - Average (of DGAC and PCC) -2.923076923 0+985 - - - - - -
N Las Flores Drive Traffic direction: In entry direction 0+000 3396 Total - 218 113 49 - none - - Average (of DGAC and PCC) 42 0+000 3396 Automobiles - 203 105 46 40 none - - Average (of DGAC and PCC) 42 0+000 3396 Medium trucks - 7 3 1 40 none - - Average (of DGAC and PCC) 42 0+000 3396 Heavy trucks - 4 2 1 40 none - - Average (of DGAC and PCC) 42 0+000 3396 Buses - 2 1 0 40 none - - Average (of DGAC and PCC) 42 0+000 3396 Motorcycles - 2 1 0 40 none - - Average (of DGAC and PCC) 42 0+000 3396 Auxiliary vehicle - - - - - none - - Average (of DGAC and PCC) 42 0+258 1602 Total - 103 53 23 - none - - Average (of DGAC and PCC) 0.0 / 19.3 0+258 1602 Automobiles - 96 49 21 40 none - - Average (of DGAC and PCC) 0.0 / 19.3 0+258 1602 Medium trucks - 3 2 1 40 none - - Average (of DGAC and PCC) 0.0 / 19.3 0+258 1602 Heavy trucks - 2 1 0 40 none - - Average (of DGAC and PCC) 0.0 / 19.3 0+258 1602 Buses - 1 1 0 40 none - - Average (of DGAC and PCC) 0.0 / 19.3 0+258 1602 Motorcycles - 1 1 0 40 none - - Average (of DGAC and PCC) 0.0 / 19.3 0+258 1602 Auxiliary vehicle - - - - - none - - Average (of DGAC and PCC) 0.0 / 19.3 0+628 - - - - - -
Road
10587 Santa Fe Flores Townhomes
SoundPLAN Data - Vehicle and Rail Traffic
Track Coordinates of track axis Track Curve Multiple Corrected Station X Y Z type radius reflectionsEmission level
km [dB] [dB] [dB] day Evening night
Sprinter Rail track: Direction: Section: 1 Km: 0+000 Train type Number of trains Speed Length per Emission level day Evening night train Max day Evening night
km/h m dB(A) dB(A) dB(A)
0 48 12 18 80 80 yes 57.3 57.3 54.3
0+000 481709.9 3668428 173.36 - - - - 57.3 57.3
0+951 481421.7 3669304 162.19 - - - - 57.3 57.3
Rail
10587 Santa Fe Flores Townhomes
SoundPLAN Data - Vehicle and Rail Traffic
No. X Y Floor Height Day Evening Night CNEL Day Evening Night CNEL Day Evening Night CNEL (meters) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) 1 481335.65 3668716.01 1.Fl 153.62 66.2 63.3 59.7 68.1 61.8 59.0 55.3 63.7 -4.4 -4.3 -4.3 -4.3 1 481335.65 3668716.01 2.Fl 156.72 67.8 64.9 61.3 69.7 67.6 64.8 61.1 69.5 -0.2 -0.2 -0.2 -0.2 1 481335.65 3668716.01 3.Fl 159.82 67.8 65.0 61.4 69.7 67.8 65.0 61.3 69.7 0.0 0.0 0.0 0.0 2 481355.89 3668781.10 1.Fl 153.90 44.1 41.5 38.0 46.3 44.1 41.5 38.0 46.3 0.0 0.0 0.0 0.0 2 481355.89 3668781.10 2.Fl 157.00 47.4 44.8 41.2 49.5 47.4 44.8 41.2 49.5 0.0 0.0 0.0 0.0 2 481355.89 3668781.10 3.Fl 160.10 50.8 48.3 44.8 53.0 50.8 48.3 44.8 53.0 0.0 0.0 0.0 0.0 3 481402.17 3668834.91 1.Fl 164.87 47.2 45.0 41.6 49.7 47.2 45.0 41.6 49.7 0.0 0.0 0.0 0.0 3 481402.17 3668834.91 2.Fl 167.97 51.6 49.2 45.8 53.9 51.5 49.2 45.7 53.8 -0.1 -0.1 -0.1 -0.1 3 481402.17 3668834.91 3.Fl 171.07 56.1 53.6 50.1 58.3 56.1 53.6 50.0 58.3 0.0 0.0 0.0 0.0 4 481347.96 3668870.55 1.Fl 163.63 42.9 41.4 38.2 46.0 42.9 41.4 38.2 46.0 0.0 0.0 0.0 0.0 4 481347.96 3668870.55 2.Fl 166.73 48.6 46.6 43.3 51.3 48.6 46.6 43.3 51.3 0.0 0.0 0.0 0.0 4 481347.96 3668870.55 3.Fl 169.83 49.9 48.0 44.6 52.6 49.9 48.0 44.6 52.6 0.0 0.0 0.0 0.0 5 481330.02 3668811.50 1.Fl 160.91 51.8 49.1 45.5 53.8 51.8 49.1 45.5 53.8 0.0 0.0 0.0 0.0 5 481330.02 3668811.50 2.Fl 164.01 55.0 52.3 48.7 57.0 55.0 52.3 48.6 57.0 0.0 0.0 0.0 0.0 5 481330.02 3668811.50 3.Fl 167.11 56.9 54.1 50.5 58.9 56.9 54.1 50.5 58.9 0.0 0.0 0.0 0.0 6 481326.76 3668793.80 1.Fl 154.66 39.5 37.5 34.2 42.2 39.5 37.5 34.2 42.2 0.0 0.0 0.0 0.0 6 481326.76 3668793.80 2.Fl 157.76 42.1 40.5 37.2 45.1 42.1 40.5 37.2 45.1 0.0 0.0 0.0 0.0 6 481326.76 3668793.80 3.Fl 160.86 46.1 44.0 40.5 48.6 46.1 44.0 40.5 48.6 0.0 0.0 0.0 0.0 7 481331.07 3668741.36 1.Fl 153.90 59.0 56.2 52.5 60.9 59.0 56.2 52.5 60.9 0.0 0.0 0.0 0.0 7 481331.07 3668741.36 2.Fl 157.00 61.4 58.6 54.9 63.3 61.4 58.6 54.9 63.3 0.0 0.0 0.0 0.0 7 481331.07 3668741.36 3.Fl 160.10 63.0 60.1 56.5 64.9 63.0 60.1 56.5 64.9 0.0 0.0 0.0 0.0 8 481336.40 3668724.08 1.Fl 153.90 65.3 62.5 58.8 67.2 63.1 60.3 56.6 65.0 -2.2 -2.2 -2.2 -2.2 8 481336.40 3668724.08 2.Fl 157.00 67.4 64.6 60.9 69.3 67.3 64.4 60.8 69.2 -0.1 -0.1 -0.1 -0.1 8 481336.40 3668724.08 3.Fl 160.10 67.9 65.0 61.4 69.8 67.9 65.0 61.4 69.8 0.0 0.0 0.0 0.0 9 481351.47 3668732.17 1.Fl 153.96 61.0 58.2 54.6 62.9 60.8 58.0 54.4 62.7 -0.2 -0.2 -0.2 -0.2 9 481351.47 3668732.17 2.Fl 157.06 62.6 59.7 56.1 64.5 62.5 59.7 56.0 64.4 -0.1 -0.1 -0.1 -0.1 9 481351.47 3668732.17 3.Fl 160.16 63.6 60.8 57.2 65.5 63.6 60.8 57.2 65.5 0.0 0.0 0.0 0.0 10 481344.49 3668750.54 1.Fl 153.90 46.6 44.1 40.6 48.8 46.6 44.1 40.6 48.8 0.0 0.0 0.0 0.0 10 481344.49 3668750.54 2.Fl 157.00 51.3 48.7 45.1 53.4 51.4 48.7 45.1 53.4 0.0 0.0 0.0 0.0 10 481344.49 3668750.54 3.Fl 160.10 53.2 50.6 47.0 55.3 53.2 50.6 47.0 55.3 0.0 0.0 0.0 0.0 11 481359.92 3668758.08 1.Fl 153.90 54.7 51.9 48.2 56.6 54.7 51.9 48.3 56.7 0.0 0.0 0.0 0.0 11 481359.92 3668758.08 2.Fl 157.00 58.5 55.8 52.1 60.5 58.5 55.8 52.1 60.5 0.0 0.0 0.0 0.0 11 481359.92 3668758.08 3.Fl 160.10 59.5 56.7 53.1 61.4 59.5 56.7 53.1 61.4 0.0 0.0 0.0 0.0 12 481355.15 3668776.09 1.Fl 153.90 43.9 41.4 37.9 46.1 43.9 41.4 37.9 46.1 0.0 0.0 0.0 0.0 12 481355.15 3668776.09 2.Fl 157.00 47.8 45.2 41.7 50.0 47.8 45.2 41.7 50.0 0.0 0.0 0.0 0.0 12 481355.15 3668776.09 3.Fl 160.10 49.9 47.5 44.1 52.2 49.9 47.5 44.1 52.2 0.0 0.0 0.0 0.0 13 481339.34 3668768.00 1.Fl 153.90 52.2 49.4 45.8 54.2 52.2 49.4 45.8 54.2 0.0 0.0 0.0 0.0 13 481339.34 3668768.00 2.Fl 157.00 56.0 53.2 49.6 57.9 56.0 53.2 49.6 57.9 0.0 0.0 0.0 0.0 13 481339.34 3668768.00 3.Fl 160.10 57.8 55.0 51.4 59.8 57.8 55.0 51.4 59.8 0.0 0.0 0.0 0.0 14 481360.11 3668813.57 1.Fl 164.57 51.9 49.3 45.7 54.0 51.9 49.3 45.7 54.0 0.0 0.0 0.0 0.0 14 481360.11 3668813.57 2.Fl 167.67 52.7 50.0 46.4 54.7 52.7 50.0 46.4 54.7 0.0 0.0 0.0 0.0 14 481360.11 3668813.57 3.Fl 170.77 53.4 50.8 47.2 55.5 53.4 50.8 47.2 55.5 0.0 0.0 0.0 0.0 15 481366.91 3668795.75 1.Fl 164.34 56.2 53.5 49.9 58.2 56.2 53.5 49.9 58.2 0.0 0.0 0.0 0.0 15 481366.91 3668795.75 2.Fl 167.44 58.1 55.4 51.7 60.1 58.1 55.4 51.7 60.1 0.0 0.0 0.0 0.0 15 481366.91 3668795.75 3.Fl 170.54 59.2 56.4 52.8 61.1 59.2 56.4 52.8 61.1 0.0 0.0 0.0 0.0 16 481386.75 3668803.65 1.Fl 164.57 55.1 52.3 48.7 57.0 55.1 52.3 48.7 57.0 0.0 0.0 0.0 0.0 16 481386.75 3668803.65 2.Fl 167.67 58.1 55.4 51.9 60.2 58.1 55.4 51.9 60.2 0.0 0.0 0.0 0.0 16 481386.75 3668803.65 3.Fl 170.77 58.4 55.7 52.1 60.4 58.4 55.7 52.1 60.4 0.0 0.0 0.0 0.0 17 481379.40 3668822.58 1.Fl 164.87 42.6 40.7 37.4 45.3 42.6 40.7 37.4 45.3 0.0 0.0 0.0 0.0 17 481379.40 3668822.58 2.Fl 167.97 46.5 44.8 41.5 49.4 46.5 44.8 41.5 49.4 0.0 0.0 0.0 0.0 17 481379.40 3668822.58 3.Fl 171.07 47.6 45.9 42.6 50.5 47.6 45.9 42.6 50.5 0.0 0.0 0.0 0.0 18 481397.04 3668829.19 1.Fl 164.87 48.6 46.4 42.9 51.0 48.6 46.4 42.9 51.0 0.0 0.0 0.0 0.0 18 481397.04 3668829.19 2.Fl 167.97 52.7 50.2 46.7 54.9 52.8 50.2 46.7 54.9 0.0 0.0 0.0 0.0 18 481397.04 3668829.19 3.Fl 171.07 56.6 54.0 50.5 58.7 56.6 54.0 50.5 58.7 0.0 0.0 0.0 0.0 19 481390.79 3668848.85 1.Fl 164.87 44.6 43.8 40.6 48.3 44.6 43.8 40.6 48.3 0.0 0.0 0.0 0.0 19 481390.79 3668848.85 2.Fl 167.97 46.8 46.0 42.8 50.5 46.8 46.0 42.8 50.5 0.0 0.0 0.0 0.0 19 481390.79 3668848.85 3.Fl 171.07 48.1 47.2 44.0 51.7 48.1 47.2 44.0 51.7 0.0 0.0 0.0 0.0 20 481372.23 3668840.95 1.Fl 164.87 43.2 41.5 38.2 46.1 43.2 41.5 38.2 46.1 0.0 0.0 0.0 0.0 20 481372.23 3668840.95 2.Fl 167.97 48.8 46.5 43.0 51.2 48.8 46.5 43.0 51.2 0.0 0.0 0.0 0.0 20 481372.23 3668840.95 3.Fl 171.07 49.5 47.2 43.7 51.9 49.5 47.2 43.7 51.9 0.0 0.0 0.0 0.0 21 481358.45 3668847.75 1.Fl 163.35 42.9 41.6 38.4 46.2 42.9 41.6 38.4 46.2 0.0 0.0 0.0 0.0 21 481358.45 3668847.75 2.Fl 166.45 47.2 45.3 41.9 49.9 47.2 45.3 41.9 49.9 0.0 0.0 0.0 0.0 21 481358.45 3668847.75 3.Fl 169.55 48.2 46.3 43.0 51.0 48.2 46.3 43.0 51.0 0.0 0.0 0.0 0.0 22 481354.78 3668864.47 1.Fl 163.35 41.6 40.4 37.2 45.0 41.6 40.4 37.2 45.0 0.0 0.0 0.0 0.0 22 481354.78 3668864.47 2.Fl 166.45 45.8 44.6 41.5 49.2 45.8 44.6 41.5 49.2 0.0 0.0 0.0 0.0 22 481354.78 3668864.47 3.Fl 169.55 46.9 45.7 42.5 50.2 46.9 45.7 42.5 50.2 0.0 0.0 0.0 0.0 23 481338.24 3668856.75 1.Fl 163.36 46.2 43.5 39.9 48.2 46.2 43.5 39.9 48.2 0.0 0.0 0.0 0.0 23 481338.24 3668856.75 2.Fl 166.46 52.4 49.7 46.1 54.4 52.4 49.7 46.1 54.4 0.0 0.0 0.0 0.0 23 481338.24 3668856.75 3.Fl 169.56 53.8 51.1 47.5 55.8 53.8 51.1 47.5 55.8 0.0 0.0 0.0 0.0 24 481341.92 3668839.85 1.Fl 162.53 40.3 38.5 35.1 43.1 40.3 38.5 35.1 43.1 0.0 0.0 0.0 0.0 24 481341.92 3668839.85 2.Fl 165.63 46.1 44.0 40.5 48.6 46.1 44.0 40.5 48.6 0.0 0.0 0.0 0.0 24 481341.92 3668839.85 3.Fl 168.73 48.0 45.7 42.2 50.3 48.0 45.7 42.2 50.3 0.0 0.0 0.0 0.0 25 481326.48 3668829.93 1.Fl 161.82 49.1 46.4 42.8 51.1 49.1 46.4 42.8 51.1 0.0 0.0 0.0 0.0 25 481326.48 3668829.93 2.Fl 164.92 53.7 50.9 47.3 55.7 53.7 50.9 47.3 55.7 0.0 0.0 0.0 0.0 25 481326.48 3668829.93 3.Fl 168.02 55.2 52.4 48.8 57.1 55.2 52.4 48.8 57.1 0.0 0.0 0.0 0.0 26 481330.89 3668813.57 1.Fl 161.73 52.9 50.1 46.5 54.9 52.9 50.1 46.5 54.9 0.0 0.0 0.0 0.0 26 481330.89 3668813.57 2.Fl 164.83 55.6 52.8 49.2 57.5 55.6 52.8 49.2 57.5 0.0 0.0 0.0 0.0 26 481330.89 3668813.57 3.Fl 167.93 57.4 54.7 51.0 59.4 57.4 54.7 51.0 59.4 0.0 0.0 0.0 0.0 27 481346.51 3668821.84 1.Fl 161.82 46.9 44.3 40.8 49.0 46.9 44.3 40.8 49.0 0.0 0.0 0.0 0.0 27 481346.51 3668821.84 2.Fl 164.92 51.2 48.6 45.0 53.3 51.2 48.6 45.0 53.3 0.0 0.0 0.0 0.0 27 481346.51 3668821.84 3.Fl 168.02 52.6 50.0 46.4 54.7 52.6 50.0 46.4 54.7 0.0 0.0 0.0 0.0 28 481322.44 3668793.91 1.Fl 154.66 39.8 38.0 34.6 42.6 39.8 38.0 34.6 42.6 0.0 0.0 0.0 0.0 28 481322.44 3668793.91 2.Fl 157.76 42.3 40.8 37.5 45.3 42.3 40.8 37.5 45.3 0.0 0.0 0.0 0.0 28 481322.44 3668793.91 3.Fl 160.86 46.0 43.9 40.5 48.6 46.0 43.9 40.5 48.6 0.0 0.0 0.0 0.0 29 481307.92 3668785.09 1.Fl 154.66 45.4 42.7 39.1 47.4 45.4 42.7 39.1 47.4 0.0 0.0 0.0 0.0 29 481307.92 3668785.09 2.Fl 157.76 53.6 50.8 47.2 55.5 53.6 50.8 47.2 55.5 0.0 0.0 0.0 0.0 29 481307.92 3668785.09 3.Fl 160.86 58.3 55.4 51.8 60.2 58.3 55.4 51.8 60.2 0.0 0.0 0.0 0.0 30 481311.78 3668768.92 1.Fl 154.66 57.5 54.7 51.0 59.4 57.4 54.5 50.9 59.3 -0.1 -0.1 -0.1 -0.1 30 481311.78 3668768.92 2.Fl 157.76 61.0 58.2 54.6 62.9 61.0 58.1 54.5 62.9 -0.1 -0.1 -0.1 -0.1 30 481311.78 3668768.92 3.Fl 160.86 62.9 60.1 56.4 64.8 62.9 60.1 56.4 64.8 0.0 0.0 0.0 0.0 31 481326.85 3668775.72 1.Fl 154.70 51.7 48.9 45.3 53.6 51.6 48.8 45.2 53.5 -0.1 -0.1 -0.1 -0.1 31 481326.85 3668775.72 2.Fl 157.80 54.1 51.3 47.7 56.1 54.0 51.3 47.7 56.0 -0.1 -0.1 -0.1 -0.1 31 481326.85 3668775.72 3.Fl 160.90 55.8 53.1 49.5 57.8 55.6 53.0 49.4 57.7 -0.1 -0.1 -0.1 -0.1 Coordinates
(meters)
Noise Level without Amenity Area A Barrier Noise Level with Amenity Area A Barrier Difference Receivers
10587 Santa Fe Flores Townhomes
SoundPLAN Data - Vehicle and Rail Traffic
Source name Day Evening Night CNEL Day Evening Night CNEL dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A)
1 1.Fl 66.2 63.3 59.7 68.1 61.8 59.0 55.3 63.7 N Las Flores Drive 51.4 48.5 44.9 53.3 47.0 44.1 40.5 48.9 S Santa Fe Avenue 66.0 63.2 59.5 67.9 61.6 58.8 55.2 63.5 Sprinter 37.8 37.8 34.8 42.2 37.7 37.7 34.7 42.2
1 2.Fl 67.8 64.9 61.3 69.7 67.6 64.8 61.1 69.5 N Las Flores Drive 52.9 50.0 46.4 54.8 52.7 49.8 46.2 54.6 S Santa Fe Avenue 67.6 64.8 61.2 69.5 67.5 64.6 61.0 69.4 Sprinter 38.3 38.3 35.3 42.8 38.3 38.3 35.3 42.7
1 3.Fl 67.8 65.0 61.4 69.7 67.8 65.0 61.3 69.7 N Las Flores Drive 53.0 50.1 46.5 54.9 53.0 50.1 46.5 54.9 S Santa Fe Avenue 67.7 64.8 61.2 69.6 67.7 64.8 61.2 69.6 Sprinter 39.7 39.7 36.7 44.1 39.6 39.6 36.6 44.1
2 1.Fl 44.1 41.5 38.0 46.3 44.1 41.5 38.0 46.3 N Las Flores Drive 42.7 39.8 36.2 44.5 42.7 39.8 36.2 44.5 S Santa Fe Avenue 37.6 34.7 31.1 39.5 37.6 34.7 31.1 39.5 Sprinter 32.5 32.5 29.5 36.9 32.5 32.5 29.5 36.9
2 2.Fl 47.4 44.8 41.2 49.5 47.4 44.8 41.2 49.5 N Las Flores Drive 46.2 43.4 39.7 48.1 46.2 43.4 39.7 48.1 S Santa Fe Avenue 39.8 36.9 33.3 41.7 39.8 36.9 33.3 41.7 Sprinter 35.3 35.3 32.2 39.7 35.3 35.3 32.2 39.7
2 3.Fl 50.8 48.3 44.8 53.0 50.8 48.3 44.8 53.0 N Las Flores Drive 48.4 45.5 41.9 50.3 48.4 45.5 41.9 50.3 S Santa Fe Avenue 46.1 43.3 39.6 48.0 46.1 43.3 39.6 48.0 Sprinter 40.2 40.2 37.2 44.7 40.2 40.2 37.2 44.7
3 1.Fl 47.2 45.0 41.6 49.7 47.2 45.0 41.6 49.7 N Las Flores Drive 45.2 42.4 38.7 47.1 45.2 42.3 38.7 47.1 S Santa Fe Avenue 39.9 37.1 33.5 41.8 39.8 36.9 33.3 41.7 Sprinter 39.8 39.8 36.8 44.2 39.8 39.8 36.8 44.2
3 2.Fl 51.6 49.2 45.8 53.9 51.5 49.2 45.7 53.8 N Las Flores Drive 48.3 45.5 41.8 50.2 48.3 45.5 41.8 50.2 S Santa Fe Avenue 47.7 44.8 41.2 49.6 47.4 44.6 40.9 49.3 Sprinter 42.7 42.7 39.7 47.1 42.7 42.7 39.7 47.1
3 3.Fl 56.1 53.6 50.1 58.3 56.1 53.6 50.0 58.3 N Las Flores Drive 52.0 49.1 45.5 53.9 52.0 49.1 45.5 53.9 S Santa Fe Avenue 53.4 50.5 46.9 55.3 53.3 50.5 46.8 55.2 Sprinter 45.3 45.3 42.3 49.7 45.3 45.3 42.3 49.7
4 1.Fl 42.9 41.4 38.2 46.0 42.9 41.4 38.2 46.0 N Las Flores Drive 36.7 33.8 30.2 38.6 36.7 33.8 30.2 38.6 S Santa Fe Avenue 38.5 35.7 32.0 40.4 38.5 35.7 32.0 40.4 Sprinter 39.0 39.0 35.9 43.4 39.0 39.0 35.9 43.4
4 2.Fl 48.6 46.6 43.3 51.3 48.6 46.6 43.3 51.3 N Las Flores Drive 37.2 34.3 30.7 39.1 37.2 34.3 30.7 39.1 S Santa Fe Avenue 46.8 44.0 40.4 48.7 46.8 44.0 40.4 48.7 Sprinter 42.6 42.6 39.6 47.1 42.6 42.6 39.6 47.1
4 3.Fl 49.9 48.0 44.6 52.6 49.9 48.0 44.6 52.6 N Las Flores Drive 37.7 34.8 31.2 39.6 37.7 34.8 31.2 39.6 S Santa Fe Avenue 48.4 45.5 41.9 50.3 48.4 45.5 41.9 50.3 Sprinter 43.7 43.7 40.7 48.2 43.7 43.7 40.7 48.2
5 1.Fl 51.8 49.1 45.5 53.8 51.8 49.1 45.5 53.8 N Las Flores Drive 38.8 35.9 32.3 40.7 38.8 35.9 32.3 40.7 S Santa Fe Avenue 51.5 48.7 45.0 53.4 51.5 48.7 45.0 53.4 Sprinter 36.0 36.0 33.0 40.4 36.0 36.0 33.0 40.4
5 2.Fl 55.0 52.3 48.7 57.0 55.0 52.3 48.6 57.0 N Las Flores Drive 40.6 37.7 34.1 42.5 40.6 37.7 34.1 42.5 S Santa Fe Avenue 54.8 51.9 48.3 56.7 54.8 51.9 48.3 56.7 Sprinter 37.7 37.7 34.7 42.1 37.7 37.7 34.7 42.1
5 3.Fl 56.9 54.1 50.5 58.9 56.9 54.1 50.5 58.9 N Las Flores Drive 41.8 39.0 35.3 43.7 41.8 39.0 35.3 43.7 S Santa Fe Avenue 56.7 53.9 50.3 58.6 56.7 53.9 50.2 58.6 Sprinter 38.6 38.6 35.6 43.1 38.6 38.6 35.6 43.1
6 1.Fl 39.5 37.5 34.2 42.2 39.5 37.5 34.2 42.2 N Las Flores Drive 36.4 33.6 29.9 38.3 36.4 33.6 29.9 38.3 S Santa Fe Avenue 33.5 30.7 27.0 35.4 33.5 30.7 27.0 35.4 Sprinter 33.5 33.5 30.5 37.9 33.5 33.5 30.5 37.9
6 2.Fl 42.1 40.5 37.2 45.1 42.1 40.5 37.2 45.1 N Las Flores Drive 38.5 35.6 32.0 40.4 38.5 35.6 32.0 40.4 S Santa Fe Avenue 35.8 32.9 29.3 37.7 35.8 32.9 29.3 37.7 Sprinter 37.5 37.5 34.4 41.9 37.5 37.5 34.4 41.9
6 3.Fl 46.1 44.0 40.5 48.6 46.1 44.0 40.5 48.6 N Las Flores Drive 40.0 37.2 33.5 41.9 40.0 37.2 33.5 41.9 S Santa Fe Avenue 43.6 40.7 37.1 45.5 43.6 40.7 37.1 45.5 Sprinter 39.0 39.0 36.0 43.4 39.0 39.0 36.0 43.4
7 1.Fl 59.0 56.2 52.5 60.9 59.0 56.2 52.5 60.9 N Las Flores Drive 25.6 22.7 19.1 27.5 25.6 22.7 19.1 27.5 S Santa Fe Avenue 59.0 56.1 52.5 60.9 59.0 56.1 52.5 60.9 Sprinter 33.3 33.3 30.3 37.7 33.3 33.3 30.3 37.7
7 2.Fl 61.4 58.6 54.9 63.3 61.4 58.6 54.9 63.3 N Las Flores Drive 27.6 24.7 21.1 29.5 27.6 24.7 21.1 29.5 S Santa Fe Avenue 61.4 58.5 54.9 63.3 61.4 58.5 54.9 63.3 Sprinter 33.7 33.7 30.7 38.1 33.7 33.7 30.7 38.1
7 3.Fl 63.0 60.1 56.5 64.9 63.0 60.1 56.5 64.9 N Las Flores Drive 31.0 28.1 24.5 32.9 31.0 28.1 24.5 32.9 S Santa Fe Avenue 63.0 60.1 56.5 64.9 63.0 60.1 56.5 64.9 Sprinter 34.1 34.1 31.1 38.5 34.1 34.1 31.1 38.5
Noise Level without Amenity Area A Barrier Noise Level with Amenity Area A Barrier Contributions
10587 Santa Fe Flores Townhomes
SoundPLAN Data - Vehicle and Rail Traffic
Source name Day Evening Night CNEL Day Evening Night CNEL dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A)
Noise Level without Amenity Area A Barrier Noise Level with Amenity Area A Barrier 8 1.Fl 65.3 62.5 58.8 67.2 63.1 60.3 56.6 65.0 N Las Flores Drive 50.3 47.4 43.8 52.2 46.4 43.5 39.9 48.3 S Santa Fe Avenue 65.2 62.3 58.7 67.1 63.0 60.2 56.5 64.9 Sprinter 36.2 36.2 33.2 40.6 36.1 36.1 33.1 40.5
8 2.Fl 67.4 64.6 60.9 69.3 67.3 64.4 60.8 69.2 N Las Flores Drive 51.9 49.0 45.4 53.8 51.5 48.6 45.0 53.4 S Santa Fe Avenue 67.3 64.4 60.8 69.2 67.2 64.3 60.7 69.1 Sprinter 36.2 36.2 33.2 40.6 36.2 36.2 33.2 40.6
8 3.Fl 67.9 65.0 61.4 69.8 67.9 65.0 61.4 69.8 N Las Flores Drive 52.1 49.2 45.6 54.0 52.1 49.2 45.6 54.0 S Santa Fe Avenue 67.8 64.9 61.3 69.7 67.8 64.9 61.3 69.7 Sprinter 37.2 37.2 34.2 41.6 37.2 37.2 34.1 41.6
9 1.Fl 61.0 58.2 54.6 62.9 60.8 58.0 54.4 62.7 N Las Flores Drive 55.1 52.2 48.6 56.9 55.0 52.1 48.5 56.9 S Santa Fe Avenue 59.7 56.8 53.2 61.6 59.4 56.6 52.9 61.3 Sprinter 40.1 40.1 37.1 44.6 40.1 40.1 37.1 44.6
9 2.Fl 62.6 59.7 56.1 64.5 62.5 59.7 56.0 64.4 N Las Flores Drive 56.2 53.3 49.7 58.1 56.2 53.3 49.7 58.1 S Santa Fe Avenue 61.4 58.5 54.9 63.3 61.3 58.4 54.8 63.2 Sprinter 41.3 41.3 38.3 45.8 41.3 41.3 38.3 45.8
9 3.Fl 63.6 60.8 57.2 65.5 63.6 60.8 57.2 65.5 N Las Flores Drive 56.0 53.1 49.5 57.8 56.0 53.1 49.5 57.9 S Santa Fe Avenue 62.8 59.9 56.3 64.7 62.7 59.9 56.3 64.6 Sprinter 42.4 42.4 39.4 46.8 42.4 42.4 39.4 46.8
10 1.Fl 46.6 44.1 40.6 48.8 46.6 44.1 40.6 48.8 N Las Flores Drive 41.3 38.4 34.8 43.2 41.3 38.4 34.8 43.2 S Santa Fe Avenue 44.2 41.4 37.8 46.1 44.2 41.4 37.8 46.1 Sprinter 37.2 37.2 34.2 41.6 37.2 37.2 34.2 41.6
10 2.Fl 51.3 48.7 45.1 53.4 51.4 48.7 45.1 53.4 N Las Flores Drive 45.1 42.2 38.6 47.0 45.1 42.2 38.6 47.0 S Santa Fe Avenue 49.9 47.0 43.4 51.8 49.9 47.0 43.4 51.8 Sprinter 38.4 38.4 35.4 42.8 38.4 38.4 35.4 42.8
10 3.Fl 53.2 50.6 47.0 55.3 53.2 50.6 47.0 55.3 N Las Flores Drive 45.1 42.2 38.6 47.0 45.1 42.2 38.6 47.0 S Santa Fe Avenue 52.3 49.4 45.8 54.2 52.3 49.4 45.8 54.2 Sprinter 40.2 40.2 37.2 44.7 40.2 40.2 37.2 44.7
11 1.Fl 54.7 51.9 48.2 56.6 54.7 51.9 48.3 56.7 N Las Flores Drive 50.1 47.2 43.6 52.0 50.1 47.2 43.6 52.0 S Santa Fe Avenue 52.8 50.0 46.3 54.7 52.9 50.0 46.4 54.8 Sprinter 31.6 31.6 28.6 36.0 31.6 31.6 28.6 36.0
11 2.Fl 58.5 55.8 52.1 60.5 58.5 55.8 52.1 60.5 N Las Flores Drive 54.7 51.8 48.2 56.6 54.7 51.8 48.2 56.6 S Santa Fe Avenue 56.1 53.2 49.6 58.0 56.1 53.3 49.6 58.0 Sprinter 40.9 40.9 37.9 45.3 40.9 40.9 37.9 45.3
11 3.Fl 59.5 56.7 53.1 61.4 59.5 56.7 53.1 61.4 N Las Flores Drive 54.8 51.9 48.3 56.7 54.8 51.9 48.3 56.7 S Santa Fe Avenue 57.5 54.7 51.1 59.4 57.5 54.7 51.1 59.4 Sprinter 42.2 42.2 39.2 46.6 42.2 42.2 39.2 46.6
12 1.Fl 43.9 41.4 37.9 46.1 43.9 41.4 37.9 46.1 N Las Flores Drive 43.1 40.2 36.5 44.9 43.1 40.2 36.5 44.9 S Santa Fe Avenue 32.4 29.6 26.0 34.3 32.4 29.6 26.0 34.3 Sprinter 33.8 33.8 30.8 38.3 33.8 33.8 30.8 38.3
12 2.Fl 47.8 45.2 41.7 50.0 47.8 45.2 41.7 50.0 N Las Flores Drive 47.2 44.4 40.7 49.1 47.2 44.4 40.7 49.1 S Santa Fe Avenue 33.3 30.4 26.8 35.2 33.3 30.4 26.8 35.2 Sprinter 37.0 37.0 34.0 41.5 37.0 37.0 34.0 41.5
12 3.Fl 49.9 47.5 44.1 52.2 49.9 47.5 44.1 52.2 N Las Flores Drive 49.0 46.1 42.5 50.8 49.0 46.1 42.5 50.8 S Santa Fe Avenue 37.5 34.7 31.0 39.4 37.5 34.7 31.0 39.4 Sprinter 41.3 41.3 38.3 45.7 41.3 41.3 38.3 45.7
13 1.Fl 52.2 49.4 45.8 54.2 52.2 49.4 45.8 54.2 N Las Flores Drive 31.0 28.1 24.5 32.9 31.0 28.1 24.5 32.9 S Santa Fe Avenue 52.1 49.3 45.7 54.0 52.1 49.3 45.7 54.0 Sprinter 33.1 33.1 30.0 37.5 33.1 33.1 30.0 37.5
13 2.Fl 56.0 53.2 49.6 57.9 56.0 53.2 49.6 57.9 N Las Flores Drive 32.5 29.6 26.0 34.4 32.5 29.6 26.0 34.4 S Santa Fe Avenue 55.9 53.1 49.4 57.8 55.9 53.1 49.4 57.8 Sprinter 36.6 36.6 33.6 41.1 36.6 36.6 33.6 41.1
13 3.Fl 57.8 55.0 51.4 59.8 57.8 55.0 51.4 59.8 N Las Flores Drive 34.5 31.7 28.0 36.4 34.5 31.7 28.0 36.4 S Santa Fe Avenue 57.7 54.9 51.3 59.6 57.7 54.9 51.3 59.6 Sprinter 38.6 38.6 35.6 43.0 38.6 38.6 35.6 43.0
14 1.Fl 51.9 49.3 45.7 54.0 51.9 49.3 45.7 54.0 N Las Flores Drive 34.9 32.1 28.4 36.8 35.0 32.1 28.5 36.8 S Santa Fe Avenue 51.6 48.8 45.2 53.5 51.6 48.8 45.2 53.5 Sprinter 38.6 38.6 35.6 43.0 38.6 38.6 35.6 43.0
14 2.Fl 52.7 50.0 46.4 54.7 52.7 50.0 46.4 54.7 N Las Flores Drive 35.5 32.6 29.0 37.4 35.5 32.7 29.0 37.4 S Santa Fe Avenue 52.4 49.5 45.9 54.3 52.4 49.5 45.9 54.3 Sprinter 39.0 39.0 36.0 43.4 39.0 39.0 36.0 43.4
14 3.Fl 53.4 50.8 47.2 55.5 53.4 50.8 47.2 55.5 N Las Flores Drive 35.8 32.9 29.3 37.7 35.8 33.0 29.3 37.7 S Santa Fe Avenue 53.2 50.3 46.7 55.1 53.2 50.3 46.7 55.1 Sprinter 39.5 39.5 36.5 43.9 39.5 39.5 36.5 43.9
Contributions
10587 Santa Fe Flores Townhomes
SoundPLAN Data - Vehicle and Rail Traffic
Source name Day Evening Night CNEL Day Evening Night CNEL dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A)
Noise Level without Amenity Area A Barrier Noise Level with Amenity Area A Barrier 15 1.Fl 56.2 53.5 49.9 58.2 56.2 53.5 49.9 58.2 N Las Flores Drive 48.9 46.0 42.4 50.8 48.9 46.0 42.4 50.8 S Santa Fe Avenue 55.2 52.4 48.8 57.1 55.2 52.4 48.8 57.1 Sprinter 39.5 39.5 36.5 44.0 39.5 39.5 36.5 44.0
15 2.Fl 58.1 55.4 51.7 60.1 58.1 55.4 51.7 60.1 N Las Flores Drive 50.1 47.2 43.6 52.0 50.1 47.2 43.6 52.0 S Santa Fe Avenue 57.3 54.5 50.8 59.2 57.3 54.5 50.8 59.2 Sprinter 40.6 40.6 37.6 45.0 40.6 40.6 37.6 45.0
15 3.Fl 59.2 56.4 52.8 61.1 59.2 56.4 52.8 61.1 N Las Flores Drive 50.2 47.3 43.7 52.0 50.2 47.3 43.7 52.0 S Santa Fe Avenue 58.5 55.6 52.0 60.4 58.5 55.6 52.0 60.4 Sprinter 41.4 41.4 38.4 45.8 41.4 41.4 38.4 45.8
16 1.Fl 55.1 52.3 48.7 57.0 55.1 52.3 48.7 57.0 N Las Flores Drive 51.8 48.9 45.3 53.7 51.8 48.9 45.3 53.7 S Santa Fe Avenue 52.1 49.2 45.6 54.0 52.1 49.3 45.6 54.0 Sprinter 38.5 38.5 35.5 42.9 38.5 38.5 35.5 42.9
16 2.Fl 58.1 55.4 51.9 60.2 58.1 55.4 51.9 60.2 N Las Flores Drive 55.2 52.3 48.7 57.1 55.2 52.3 48.7 57.1 S Santa Fe Avenue 54.6 51.7 48.1 56.5 54.6 51.8 48.1 56.5 Sprinter 44.5 44.5 41.5 48.9 44.5 44.5 41.5 48.9
16 3.Fl 58.4 55.7 52.1 60.4 58.4 55.7 52.1 60.4 N Las Flores Drive 55.0 52.1 48.5 56.9 55.0 52.1 48.5 56.9 S Santa Fe Avenue 55.2 52.3 48.7 57.1 55.2 52.3 48.7 57.1 Sprinter 45.7 45.7 42.7 50.1 45.7 45.7 42.7 50.1
17 1.Fl 42.6 40.7 37.4 45.3 42.6 40.7 37.4 45.3 N Las Flores Drive 40.4 37.6 33.9 42.3 40.4 37.6 33.9 42.3 S Santa Fe Avenue 33.4 30.6 27.0 35.3 33.4 30.6 27.0 35.3 Sprinter 36.9 36.9 33.9 41.4 36.9 36.9 33.9 41.4
17 2.Fl 46.5 44.8 41.5 49.4 46.5 44.8 41.5 49.4 N Las Flores Drive 43.7 40.8 37.1 45.5 43.7 40.8 37.1 45.5 S Santa Fe Avenue 38.3 35.4 31.8 40.2 38.3 35.4 31.8 40.2 Sprinter 41.7 41.7 38.7 46.1 41.7 41.7 38.7 46.1
17 3.Fl 47.6 45.9 42.6 50.5 47.6 45.9 42.6 50.5 N Las Flores Drive 44.1 41.2 37.6 45.9 44.1 41.2 37.6 45.9 S Santa Fe Avenue 41.5 38.6 35.0 43.4 41.5 38.6 35.0 43.4 Sprinter 42.6 42.6 39.6 47.1 42.6 42.6 39.6 47.1
18 1.Fl 48.6 46.4 42.9 51.0 48.6 46.4 42.9 51.0 N Las Flores Drive 46.2 43.3 39.6 48.0 46.2 43.3 39.6 48.0 S Santa Fe Avenue 42.9 40.1 36.4 44.8 42.9 40.1 36.5 44.8 Sprinter 40.7 40.7 37.7 45.2 40.7 40.7 37.7 45.2
18 2.Fl 52.7 50.2 46.7 54.9 52.8 50.2 46.7 54.9 N Las Flores Drive 49.4 46.5 42.9 51.3 49.4 46.5 42.9 51.3 S Santa Fe Avenue 49.3 46.5 42.8 51.2 49.3 46.5 42.9 51.2 Sprinter 42.2 42.2 39.2 46.6 42.2 42.2 39.2 46.6
18 3.Fl 56.6 54.0 50.5 58.7 56.6 54.0 50.5 58.7 N Las Flores Drive 52.7 49.9 46.2 54.6 52.7 49.9 46.2 54.6 S Santa Fe Avenue 53.6 50.8 47.1 55.5 53.6 50.8 47.2 55.5 Sprinter 45.5 45.5 42.5 49.9 45.5 45.5 42.5 49.9
19 1.Fl 44.6 43.8 40.6 48.3 44.6 43.8 40.6 48.3 N Las Flores Drive 39.9 37.0 33.4 41.7 39.9 37.0 33.4 41.7 S Santa Fe Avenue 30.7 27.9 24.2 32.6 30.7 27.9 24.2 32.6 Sprinter 42.6 42.6 39.6 47.0 42.6 42.6 39.6 47.0
19 2.Fl 46.8 46.0 42.8 50.5 46.8 46.0 42.8 50.5 N Las Flores Drive 40.8 37.9 34.3 42.7 40.8 37.9 34.3 42.7 S Santa Fe Avenue 37.7 34.9 31.3 39.6 37.7 34.9 31.2 39.6 Sprinter 44.8 44.8 41.8 49.2 44.8 44.8 41.8 49.2
19 3.Fl 48.1 47.2 44.0 51.7 48.1 47.2 44.0 51.7 N Las Flores Drive 42.5 39.6 36.0 44.4 42.5 39.6 36.0 44.4 S Santa Fe Avenue 39.6 36.7 33.1 41.5 39.6 36.7 33.1 41.5 Sprinter 45.8 45.8 42.8 50.3 45.8 45.8 42.8 50.3
20 1.Fl 43.2 41.5 38.2 46.1 43.2 41.5 38.2 46.1 N Las Flores Drive 32.1 29.2 25.6 34.0 32.1 29.2 25.6 34.0 S Santa Fe Avenue 41.0 38.1 34.5 42.9 41.0 38.1 34.5 42.9 Sprinter 38.3 38.3 35.3 42.7 38.3 38.3 35.3 42.7
20 2.Fl 48.8 46.5 43.0 51.2 48.8 46.5 43.0 51.2 N Las Flores Drive 33.0 30.2 26.5 34.9 33.0 30.2 26.5 34.9 S Santa Fe Avenue 48.1 45.2 41.6 50.0 48.1 45.2 41.6 50.0 Sprinter 40.1 40.1 37.1 44.5 40.1 40.1 37.1 44.5
20 3.Fl 49.5 47.2 43.7 51.9 49.5 47.2 43.7 51.9 N Las Flores Drive 31.7 28.8 25.2 33.6 31.7 28.8 25.2 33.6 S Santa Fe Avenue 48.8 45.9 42.3 50.7 48.8 45.9 42.3 50.7 Sprinter 40.9 40.9 37.9 45.4 40.9 40.9 37.9 45.4
21 1.Fl 42.9 41.6 38.4 46.2 42.9 41.6 38.4 46.2 N Las Flores Drive 33.8 31.0 27.3 35.7 33.8 31.0 27.4 35.7 S Santa Fe Avenue 39.0 36.2 32.6 40.9 39.0 36.2 32.6 40.9 Sprinter 39.6 39.6 36.6 44.1 39.6 39.6 36.6 44.1
21 2.Fl 47.2 45.3 41.9 49.9 47.2 45.3 41.9 49.9 N Las Flores Drive 35.8 33.0 29.3 37.7 35.8 33.0 29.3 37.7 S Santa Fe Avenue 45.4 42.5 38.9 47.3 45.4 42.5 38.9 47.3 Sprinter 41.5 41.5 38.5 45.9 41.5 41.5 38.5 45.9
21 3.Fl 48.2 46.3 43.0 51.0 48.2 46.3 43.0 51.0 N Las Flores Drive 37.8 34.9 31.3 39.7 37.8 35.0 31.3 39.7 S Santa Fe Avenue 46.2 43.4 39.8 48.1 46.2 43.4 39.8 48.1 Sprinter 42.6 42.6 39.6 47.0 42.6 42.6 39.6 47.0
Contributions
10587 Santa Fe Flores Townhomes
SoundPLAN Data - Vehicle and Rail Traffic
Source name Day Evening Night CNEL Day Evening Night CNEL dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A)
Noise Level without Amenity Area A Barrier Noise Level with Amenity Area A Barrier 22 1.Fl 41.6 40.4 37.2 45.0 41.6 40.4 37.2 45.0 N Las Flores Drive 37.2 34.3 30.7 39.1 37.2 34.3 30.7 39.1 S Santa Fe Avenue 32.3 29.4 25.8 34.2 32.3 29.4 25.8 34.2 Sprinter 38.7 38.7 35.7 43.2 38.7 38.7 35.7 43.2
22 2.Fl 45.8 44.6 41.5 49.2 45.8 44.6 41.5 49.2 N Las Flores Drive 38.2 35.3 31.7 40.1 38.2 35.3 31.7 40.1 S Santa Fe Avenue 40.4 37.6 34.0 42.3 40.4 37.6 34.0 42.3 Sprinter 43.0 43.0 40.0 47.4 43.0 43.0 40.0 47.4
22 3.Fl 46.9 45.7 42.5 50.2 46.9 45.7 42.5 50.2 N Las Flores Drive 38.7 35.8 32.2 40.6 38.7 35.8 32.2 40.6 S Santa Fe Avenue 42.0 39.2 35.6 43.9 42.0 39.2 35.6 43.9 Sprinter 44.0 44.0 41.0 48.4 44.0 44.0 41.0 48.4
23 1.Fl 46.2 43.5 39.9 48.2 46.2 43.5 39.9 48.2 N Las Flores Drive 17.7 14.8 11.2 19.6 17.7 14.8 11.2 19.6 S Santa Fe Avenue 46.0 43.1 39.5 47.9 46.0 43.1 39.5 47.9 Sprinter 32.7 32.7 29.6 37.1 32.7 32.7 29.6 37.1
23 2.Fl 52.4 49.7 46.1 54.4 52.4 49.7 46.1 54.4 N Las Flores Drive 18.6 15.8 12.1 20.5 18.6 15.8 12.1 20.5 S Santa Fe Avenue 52.3 49.5 45.8 54.2 52.3 49.5 45.8 54.2 Sprinter 37.1 37.1 34.1 41.6 37.1 37.1 34.1 41.6
23 3.Fl 53.8 51.1 47.5 55.8 53.8 51.1 47.5 55.8 N Las Flores Drive 23.3 20.5 16.8 25.2 23.3 20.5 16.8 25.2 S Santa Fe Avenue 53.7 50.9 47.2 55.6 53.7 50.9 47.2 55.6 Sprinter 38.1 38.1 35.1 42.5 38.1 38.1 35.1 42.5
24 1.Fl 40.3 38.5 35.1 43.1 40.3 38.5 35.1 43.1 N Las Flores Drive 30.6 27.8 24.1 32.5 30.6 27.8 24.1 32.5 S Santa Fe Avenue 38.0 35.2 31.6 39.9 38.0 35.2 31.6 39.9 Sprinter 35.0 35.0 31.9 39.4 35.0 35.0 31.9 39.4
24 2.Fl 46.1 44.0 40.5 48.6 46.1 44.0 40.5 48.6 N Las Flores Drive 30.2 27.4 23.7 32.1 30.2 27.4 23.7 32.1 S Santa Fe Avenue 45.1 42.2 38.6 47.0 45.1 42.2 38.6 47.0 Sprinter 38.9 38.9 35.8 43.3 38.9 38.9 35.8 43.3
24 3.Fl 48.0 45.7 42.2 50.3 48.0 45.7 42.2 50.3 N Las Flores Drive 32.8 29.9 26.3 34.7 32.8 29.9 26.3 34.7 S Santa Fe Avenue 47.2 44.3 40.7 49.1 47.2 44.3 40.7 49.1 Sprinter 39.4 39.4 36.3 43.8 39.4 39.4 36.3 43.8
25 1.Fl 49.1 46.4 42.8 51.1 49.1 46.4 42.8 51.1 N Las Flores Drive 17.8 14.9 11.3 19.7 17.8 14.9 11.3 19.7 S Santa Fe Avenue 49.0 46.2 42.6 50.9 49.0 46.2 42.6 50.9 Sprinter 32.6 32.6 29.6 37.0 32.6 32.6 29.6 37.0
25 2.Fl 53.7 50.9 47.3 55.7 53.7 50.9 47.3 55.7 N Las Flores Drive 19.4 16.5 12.9 21.3 19.4 16.5 12.9 21.3 S Santa Fe Avenue 53.6 50.8 47.1 55.5 53.6 50.8 47.1 55.5 Sprinter 36.5 36.5 33.5 40.9 36.5 36.5 33.5 40.9
25 3.Fl 55.2 52.4 48.8 57.1 55.2 52.4 48.8 57.1 N Las Flores Drive 23.5 20.6 17.0 25.4 23.5 20.6 17.0 25.4 S Santa Fe Avenue 55.1 52.3 48.7 57.0 55.1 52.3 48.7 57.0 Sprinter 36.8 36.8 33.8 41.3 36.8 36.8 33.8 41.3
26 1.Fl 52.9 50.1 46.5 54.9 52.9 50.1 46.5 54.9 N Las Flores Drive 39.0 36.1 32.5 40.9 39.0 36.1 32.5 40.8 S Santa Fe Avenue 52.6 49.7 46.1 54.5 52.6 49.7 46.1 54.5 Sprinter 36.8 36.8 33.8 41.2 36.8 36.8 33.8 41.2
26 2.Fl 55.6 52.8 49.2 57.5 55.6 52.8 49.2 57.5 N Las Flores Drive 41.0 38.2 34.5 42.9 41.0 38.1 34.5 42.9 S Santa Fe Avenue 55.3 52.5 48.8 57.2 55.3 52.5 48.8 57.2 Sprinter 38.6 38.6 35.6 43.0 38.6 38.6 35.6 43.0
26 3.Fl 57.4 54.7 51.0 59.4 57.4 54.7 51.0 59.4 N Las Flores Drive 42.3 39.4 35.8 44.2 42.3 39.4 35.8 44.2 S Santa Fe Avenue 57.2 54.4 50.8 59.1 57.2 54.4 50.8 59.1 Sprinter 39.3 39.3 36.3 43.7 39.3 39.3 36.3 43.7
27 1.Fl 46.9 44.3 40.8 49.0 46.9 44.3 40.8 49.0 N Las Flores Drive 33.7 30.8 27.2 35.6 33.7 30.8 27.2 35.6 S Santa Fe Avenue 46.3 43.5 39.8 48.2 46.3 43.5 39.8 48.2 Sprinter 35.6 35.6 32.6 40.0 35.6 35.6 32.6 40.0
27 2.Fl 51.2 48.6 45.0 53.3 51.2 48.6 45.0 53.3 N Las Flores Drive 37.7 34.8 31.2 39.6 37.7 34.8 31.2 39.6 S Santa Fe Avenue 50.8 47.9 44.3 52.7 50.8 47.9 44.3 52.7 Sprinter 38.8 38.8 35.8 43.2 38.8 38.8 35.8 43.2
27 3.Fl 52.6 50.0 46.4 54.7 52.6 50.0 46.4 54.7 N Las Flores Drive 39.4 36.5 32.9 41.3 39.4 36.5 32.9 41.3 S Santa Fe Avenue 52.2 49.3 45.7 54.1 52.2 49.3 45.7 54.1 Sprinter 39.9 39.9 36.9 44.3 39.9 39.9 36.9 44.3
28 1.Fl 39.8 38.0 34.6 42.6 39.8 38.0 34.6 42.6 N Las Flores Drive 37.0 34.1 30.5 38.9 37.0 34.1 30.5 38.9 S Santa Fe Avenue 32.8 29.9 26.3 34.7 32.8 29.9 26.3 34.7 Sprinter 34.3 34.3 31.3 38.7 34.3 34.3 31.3 38.7
28 2.Fl 42.3 40.8 37.5 45.3 42.3 40.8 37.5 45.3 N Las Flores Drive 38.7 35.9 32.2 40.6 38.7 35.9 32.2 40.6 S Santa Fe Avenue 34.8 31.9 28.3 36.7 34.8 31.9 28.3 36.7 Sprinter 38.1 38.1 35.1 42.5 38.1 38.1 35.1 42.5
28 3.Fl 46.0 43.9 40.5 48.6 46.0 43.9 40.5 48.6 N Las Flores Drive 40.1 37.2 33.6 42.0 40.1 37.2 33.6 42.0 S Santa Fe Avenue 43.4 40.5 36.9 45.3 43.4 40.5 36.9 45.3 Sprinter 39.1 39.1 36.1 43.5 39.1 39.1 36.1 43.5
Contributions
10587 Santa Fe Flores Townhomes
SoundPLAN Data - Vehicle and Rail Traffic
Source name Day Evening Night CNEL Day Evening Night CNEL dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A) dB(A)
Noise Level without Amenity Area A Barrier Noise Level with Amenity Area A Barrier 29 1.Fl 45.4 42.7 39.1 47.4 45.4 42.7 39.1 47.4 N Las Flores Drive 18.6 15.7 12.1 20.4 18.5 15.7 12.1 20.4 S Santa Fe Avenue 45.2 42.3 38.7 47.1 45.2 42.3 38.7 47.1 Sprinter 31.7 31.7 28.7 36.2 31.7 31.7 28.7 36.2
29 2.Fl 53.6 50.8 47.2 55.5 53.6 50.8 47.2 55.5 N Las Flores Drive 20.0 17.2 13.6 21.9 20.0 17.2 13.5 21.9 S Santa Fe Avenue 53.6 50.7 47.1 55.5 53.6 50.7 47.1 55.5 Sprinter 31.9 31.9 28.9 36.4 31.9 31.9 28.9 36.4
29 3.Fl 58.3 55.4 51.8 60.2 58.3 55.4 51.8 60.2 N Las Flores Drive 24.1 21.2 17.6 26.0 24.1 21.2 17.6 26.0 S Santa Fe Avenue 58.2 55.4 51.8 60.1 58.2 55.4 51.8 60.1 Sprinter 33.2 33.2 30.2 37.7 33.2 33.2 30.2 37.7
30 1.Fl 57.5 54.7 51.0 59.4 57.4 54.5 50.9 59.3 N Las Flores Drive 40.7 37.9 34.2 42.6 40.6 37.7 34.1 42.5 S Santa Fe Avenue 57.4 54.5 50.9 59.3 57.2 54.4 50.8 59.1 Sprinter 34.2 34.2 31.2 38.6 34.2 34.2 31.2 38.6
30 2.Fl 61.0 58.2 54.6 62.9 61.0 58.1 54.5 62.9 N Las Flores Drive 41.8 38.9 35.3 43.7 41.4 38.6 34.9 43.3 S Santa Fe Avenue 61.0 58.1 54.5 62.9 60.9 58.1 54.4 62.8 Sprinter 35.3 35.3 32.2 39.7 35.3 35.3 32.2 39.7
30 3.Fl 62.9 60.1 56.4 64.8 62.9 60.1 56.4 64.8 N Las Flores Drive 42.7 39.8 36.2 44.6 42.6 39.8 36.1 44.5 S Santa Fe Avenue 62.8 60.0 56.4 64.7 62.8 60.0 56.4 64.8 Sprinter 37.4 37.4 34.4 41.8 37.4 37.4 34.4 41.8
31 1.Fl 51.7 48.9 45.3 53.6 51.6 48.8 45.2 53.5 N Las Flores Drive 38.5 35.6 32.0 40.4 38.3 35.4 31.8 40.2 S Santa Fe Avenue 51.4 48.5 44.9 53.3 51.3 48.4 44.8 53.2 Sprinter 34.6 34.6 31.6 39.0 34.6 34.6 31.6 39.0
31 2.Fl 54.1 51.3 47.7 56.1 54.0 51.3 47.7 56.0 N Las Flores Drive 39.9 37.0 33.4 41.8 39.9 37.0 33.4 41.8 S Santa Fe Avenue 53.9 51.0 47.4 55.8 53.8 50.9 47.3 55.7 Sprinter 36.7 36.7 33.7 41.2 36.7 36.7 33.7 41.2
31 3.Fl 55.8 53.1 49.5 57.8 55.6 53.0 49.4 57.7 N Las Flores Drive 41.2 38.4 34.7 43.1 41.2 38.3 34.7 43.1 S Santa Fe Avenue 55.4 52.6 49.0 57.3 55.3 52.5 48.8 57.2 Sprinter 41.6 41.6 38.6 46.0 41.6 41.6 38.6 46.0
Contributions
Noise Analysis
Santa Fe Flores Townhomes Project
ATTACHMENT 5
Fresnel Barrier Reduction Calculations
10587 Santa Fe Flores Townhomes
Fresnel Barrier Reduction Calculations
Fresnel Barrier Reduction Calculations
Receiver 8, Level 2, Santa Fe Avenue
Reference Noise Level 69.2 GF = 500
Reference Distance 104 2nd Floor = 510
Site Conditions Hard Balcony Wall = 3.5
Distance from Barrier to
Source
Distance
from Barrier
to Receiver
Distance
from Source
to Receiver
Height of
Source
Height of
Wall
Height of
Receiver
Noise Level
Reduction
Unabated
Noise Level
Resultant
Noise Level
108 3 111 498 513.5 513 6.97 69 61.66
Receiver 8, Level 2, Las Flores Drive
Reference Noise Level 53.8 GF = 500
Reference Distance 72 2nd Floor = 510
Site Conditions Hard Balcony Wall = 3.5
Distance from Barrier to
Source
Distance
from Barrier
to Receiver
Distance
from Source
to Receiver
Height of
Source
Height of
Wall
Height of
Receiver
Noise Level
Reduction
Unabated
Noise Level
Resultant
Noise Level
46 3 49 504 513.5 513 7.58 57 49.56
Receiver 8, Level 2, Combined Santa Fe Avenue and Las Flores Drive No Barrier 69.3
With Barrier 61.9
Barrier Reduction 7.4
Receiver 9, Level 3, Santa Fe Avenue
Reference Noise Level 64.7 GF = 500
Reference Distance 151 3rd Floor = 520
Site Conditions Hard Balcony Wall = 3.5
Distance from Barrier to
Source
Distance
from Barrier
to Receiver
Distance
from Source
to Receiver
Height of
Source
Height of
Wall
Height of
Receiver
Noise Level
Reduction
Unabated
Noise Level
Resultant
Noise Level
108 3 111 498 523.5 523 7.98 67 59.39
Receiver 9, Level 3, Las Flores Drive
Reference Noise Level 57.8 GF = 500
Reference Distance 39 3rd Floor = 510
Site Conditions Hard Balcony Wall = 3.5
Distance from Barrier to
Source
Distance
from Barrier
to Receiver
Distance
from Source
to Receiver
Height of
Source
Height of
Wall
Height of
Receiver
Noise Level
Reduction
Unabated
Noise Level
Resultant
Noise Level
46 3 49 504 523.5 523 9.84 56 45.98
Receiver 9, Level 3, Combined Santa Fe Avenue and Las Flores Drive No Barrier 65.5
With Barrier 59.6
Barrier Reduction 5.9
10587 Santa Fe Flores Townhomes
Fresnel Barrier Reduction Calculations
Receiver 8, Roof Deck, Santa Fe Avenue
Reference Noise Level 69.2 GF = 500
Reference Distance 104 Roof = 530
Site Conditions Hard Balcony Wall = 3.5
Distance from Barrier to
Source
Distance
from Barrier
to Receiver
Distance
from Source
to Receiver
Height of
Source
Height of
Wall
Height of
Receiver
Noise Level
Reduction
Unabated
Noise Level
Resultant
Noise Level
108 3 111 498 533.5 533 8.98 69 59.65
Receiver 8, Roof Deck Las Flores Drive
Reference Noise Level 53.8 GF = 500
Reference Distance 72 Roof = 530
Site Conditions Hard Balcony Wall = 3.5
Distance from Barrier to
Source
Distance
from Barrier
to Receiver
Distance
from Source
to Receiver
Height of
Source
Height of
Wall
Height of
Receiver
Noise Level
Reduction
Unabated
Noise Level
Resultant
Noise Level
46 3 49 504 533.5 533 11.64 57 45.50
Receiver 8, Roof Deck, Combined Santa Fe Avenue and Las Flores Drive No Barrier 69.3
With Barrier 59.8
Barrier Reduction 9.5
Receiver 9, Roof Deck, Santa Fe Avenue
Reference Noise Level 64.7 GF = 500
Reference Distance 151 Roof = 530
Site Conditions Hard Balcony Wall = 3.5
Distance from Barrier to
Source
Distance
from Barrier
to Receiver
Distance
from Source
to Receiver
Height of
Source
Height of
Wall
Height of
Receiver
Noise Level
Reduction
Unabated
Noise Level
Resultant
Noise Level
108 3 111 498 533.5 533 8.98 67 58.39
Receiver 9, Roof Deck, Las Flores Drive
Reference Noise Level 57.8 GF = 500
Reference Distance 39 Roof = 530
Site Conditions Hard Balcony Wall = 3.5
Distance from Barrier to
Source
Distance
from Barrier
to Receiver
Distance
from Source
to Receiver
Height of
Source
Height of
Wall
Height of
Receiver
Noise Level
Reduction
Unabated
Noise Level
Resultant
Noise Level
46 3 49 504 533.5 533 11.64 56 44.18
Receiver 9, Roof Deck, Combined Santa Fe Avenue and Las Flores Drive No Barrier 65.5
With Barrier 58.6
Barrier Reduction 7.0
Noise Analysis
Santa Fe Flores Townhomes Project
ATTACHMENT 6
FHWA RD-77-108 – Off-site Traffic Noise
Data Input Sheet
Project Name : Santa Fe Flores Townhomes
Project Number : 10587 Surface Refelction: CNEL
Modeled Condition : Existing Assessment Metric: Hard
Peak ratio to ADT: 10.0
Traffic Desc. (Peak or ADT) : ADT
Segment Roadway Segment Traffic Vol. % Autos %MT % HT Day % Eve % Night %
WITHOUT PROJECT
1 S. Santa Fe Avenue Smilax Road to Bosstick Boulevard 14,850 45 50 95.00 3.00 2.00 77.00 10.00 13.00 2 S. Santa Fe Avenue Bosstick Boulevard to Community Drive 16,660 45 50 95.00 3.00 2.00 77.00 10.00 13.00 3 S. Santa Fe Avenue Community Drive to Las Flores Drive 16,660 45 50 95.00 3.00 2.00 77.00 10.00 13.00 4 S. Santa Fe Avenue Las Flores Drive to N. Rancho Santa Fe Road 14,600 45 50 95.00 3.00 2.00 77.00 10.00 13.00 5 S. Santa Fe Avenue N. Rancho Santa Fe Road and N. Pacific Street 13,500 40 50 95.00 3.00 2.00 77.00 10.00 13.00 6 Hollencrest Road De Leone Road to Hollenbeck Road 560 25 50 95.00 3.00 2.00 77.00 10.00 13.00 7 N. Rancho Santa Fe Road S. Santa Fe Avenue to Capalina Road 11,730 40 50 95.00 3.00 2.00 77.00 10.00 13.00
WITH PROJECT
1 S. Santa Fe Avenue Smilax Road to Bosstick Boulevard 14,960 45 50 95.00 3.00 2.00 77.00 10.00 13.00 2 S. Santa Fe Avenue Bosstick Boulevard to Community Drive 16,770 45 50 95.00 3.00 2.00 77.00 10.00 13.00 3 S. Santa Fe Avenue Community Drive to Las Flores Drive 17,030 45 50 95.00 3.00 2.00 77.00 10.00 13.00 4 S. Santa Fe Avenue Las Flores Drive to N. Rancho Santa Fe Road 14,780 45 50 95.00 3.00 2.00 77.00 10.00 13.00 5 S. Santa Fe Avenue N. Rancho Santa Fe Road and N. Pacific Street 13,570 40 50 95.00 3.00 2.00 77.00 10.00 13.00 6 Hollencrest Road De Leone Road to Hollenbeck Road 600 25 50 95.00 3.00 2.00 77.00 10.00 13.00 7 N. Rancho Santa Fe Road S. Santa Fe Avenue to Capalina Road 11,840 40 50 95.00 3.00 2.00 77.00 10.00 13.00 Predicted Noise Levels
Project Name : Santa Fe Flores Townhomes
Project Number : 10587
Modeled Condition : Existing
Assessment Metric: Hard
Segment Roadway Segment Auto MT HT Total 75 dB 70 dB 65 dB 60 dB 55 dB 50 dB
WITHOUT PROJECT
1 S. Santa Fe Avenue Smilax Road to Bosstick Boulevard 69.2 62.5 65.2 71.3 21 67 213 674 2,133 6,745 2 S. Santa Fe Avenue Bosstick Boulevard to Community Drive 69.7 63.0 65.7 71.8 24 76 239 757 2,393 7,568 3 S. Santa Fe Avenue Community Drive to Las Flores Drive 69.7 63.0 65.7 71.8 24 76 239 757 2,393 7,568 4 S. Santa Fe Avenue Las Flores Drive to N. Rancho Santa Fe Road 69.2 62.4 65.1 71.2 21 66 208 659 2,084 6,591 5 S. Santa Fe Avenue N. Rancho Santa Fe Road and N. Pacific Street 67.3 61.3 64.3 69.8 15 48 151 477 1,510 4,775 6 Hollencrest Road De Leone Road to Hollenbeck Road 47.6 44.3 50.1 52.7 0 1 3 9 29 93 7 N. Rancho Santa Fe Road S. Santa Fe Avenue to Capalina Road 66.7 60.6 63.7 69.1 13 41 129 406 1,285 4,064
WITH PROJECT
1 S. Santa Fe Avenue Smilax Road to Bosstick Boulevard 69.3 62.5 65.2 71.3 21 67 213 674 2,133 6,745 2 S. Santa Fe Avenue Bosstick Boulevard to Community Drive 69.8 63.0 65.7 71.8 24 76 239 757 2,393 7,568 3 S. Santa Fe Avenue Community Drive to Las Flores Drive 69.8 63.1 65.8 71.9 24 77 245 774 2,449 7,744 4 S. Santa Fe Avenue Las Flores Drive to N. Rancho Santa Fe Road 69.2 62.4 65.2 71.3 21 67 213 674 2,133 6,745 5 S. Santa Fe Avenue N. Rancho Santa Fe Road and N. Pacific Street 67.4 61.3 64.3 69.8 15 48 151 477 1,510 4,775 6 Hollencrest Road De Leone Road to Hollenbeck Road 47.9 44.6 50.4 53.0 0 1 3 10 32 100 7 N. Rancho Santa Fe Road S. Santa Fe Avenue to Capalina Road 66.8 60.7 63.8 69.2 13 42 132 416 1,315 4,159 Noise Levels, dBA Hard Distance to Traffic Noise Level Contours, Feet FHWA RD-77-108
Traffic Noise Prediction Model
Speed
(Mph)
Distance
to CL K-Factor
FHWA RD-77-108
Traffic Noise Prediction Model
Data Input Sheet
Project Name : Santa Fe Flores Townhomes
Project Number : 10587 Surface Refelction: CNEL
Modeled Condition : Near-Term (2027) Assessment Metric: Hard Peak ratio to ADT: 10.0
Traffic Desc. (Peak or ADT) : ADT
Segment Roadway Segment Traffic Vol. % Autos %MT % HT Day % Eve % Night %
WITHOUT PROJECT
1 S. Santa Fe Avenue Smilax Road to Bosstick Boulevard 16,110 45 50 95.00 3.00 2.00 77.00 10.00 13.00 2 S. Santa Fe Avenue Bosstick Boulevard to Community Drive 18,080 45 50 95.00 3.00 2.00 77.00 10.00 13.00 3 S. Santa Fe Avenue Community Drive to Las Flores Drive 18,080 45 50 95.00 3.00 2.00 77.00 10.00 13.00 4 S. Santa Fe Avenue Las Flores Drive to N. Rancho Santa Fe Road 15,840 45 50 95.00 3.00 2.00 77.00 10.00 13.00 5 S. Santa Fe Avenue N. Rancho Santa Fe Road and N. Pacific Street 14,650 40 50 95.00 3.00 2.00 77.00 10.00 13.00 6 Hollencrest Road De Leone Road to Hollenbeck Road 610 25 50 95.00 3.00 2.00 77.00 10.00 13.00 7 N. Rancho Santa Fe Road S. Santa Fe Avenue to Capalina Road 12,730 40 50 95.00 3.00 2.00 77.00 10.00 13.00
WITH PROJECT
1 S. Santa Fe Avenue Smilax Road to Bosstick Boulevard 16,220 45 50 95.00 3.00 2.00 77.00 10.00 13.00 2 S. Santa Fe Avenue Bosstick Boulevard to Community Drive 18,190 45 50 95.00 3.00 2.00 77.00 10.00 13.00 3 S. Santa Fe Avenue Community Drive to Las Flores Drive 18,450 45 50 95.00 3.00 2.00 77.00 10.00 13.00 4 S. Santa Fe Avenue Las Flores Drive to N. Rancho Santa Fe Road 16,020 45 50 95.00 3.00 2.00 77.00 10.00 13.00 5 S. Santa Fe Avenue N. Rancho Santa Fe Road and N. Pacific Street 14,720 40 50 95.00 3.00 2.00 77.00 10.00 13.00 6 Hollencrest Road De Leone Road to Hollenbeck Road 650 25 50 95.00 3.00 2.00 77.00 10.00 13.00 7 N. Rancho Santa Fe Road S. Santa Fe Avenue to Capalina Road 12,840 40 50 95.00 3.00 2.00 77.00 10.00 13.00 Predicted Noise Levels
Project Name : Santa Fe Flores Townhomes
Project Number : 10587
Modeled Condition : Near-Term (2027)
Assessment Metric: Hard
Segment Roadway Segment Auto MT HT Total 75 dB 70 dB 65 dB 60 dB 55 dB 50 dB
WITHOUT PROJECT
1 S. Santa Fe Avenue Smilax Road to Bosstick Boulevard 69.6 62.8 65.6 71.6 23 72 229 723 2,285 7,227 2 S. Santa Fe Avenue Bosstick Boulevard to Community Drive 70.1 63.3 66.1 72.1 26 81 256 811 2,564 8,109 3 S. Santa Fe Avenue Community Drive to Las Flores Drive 70.1 63.3 66.1 72.1 26 81 256 811 2,564 8,109 4 S. Santa Fe Avenue Las Flores Drive to N. Rancho Santa Fe Road 69.5 62.7 65.5 71.6 23 72 229 723 2,285 7,227 5 S. Santa Fe Avenue N. Rancho Santa Fe Road and N. Pacific Street 67.7 61.6 64.7 70.1 16 51 162 512 1,618 5,116 6 Hollencrest Road De Leone Road to Hollenbeck Road 48.0 44.6 50.5 53.1 0 1 3 10 32 102 7 N. Rancho Santa Fe Road S. Santa Fe Avenue to Capalina Road 67.1 61.0 64.1 69.5 14 45 141 446 1,409 4,456
WITH PROJECT
1 S. Santa Fe Avenue Smilax Road to Bosstick Boulevard 69.6 62.9 65.6 71.7 23 74 234 740 2,339 7,396 2 S. Santa Fe Avenue Bosstick Boulevard to Community Drive 70.1 63.4 66.1 72.2 26 83 262 830 2,624 8,298 3 S. Santa Fe Avenue Community Drive to Las Flores Drive 70.2 63.4 66.1 72.2 26 83 262 830 2,624 8,298 4 S. Santa Fe Avenue Las Flores Drive to N. Rancho Santa Fe Road 69.6 62.8 65.5 71.6 23 72 229 723 2,285 7,227 5 S. Santa Fe Avenue N. Rancho Santa Fe Road and N. Pacific Street 67.7 61.6 64.7 70.1 16 51 162 512 1,618 5,116 6 Hollencrest Road De Leone Road to Hollenbeck Road 48.3 44.9 50.8 53.4 0 1 3 11 35 109 7 N. Rancho Santa Fe Road S. Santa Fe Avenue to Capalina Road 67.1 61.0 64.1 69.5 14 45 141 446 1,409 4,456 FHWA RD-77-108
Traffic Noise Prediction Model
Speed
(Mph)
Distance
to CL K-Factor
FHWA RD-77-108
Traffic Noise Prediction Model
Noise Levels, dBA Hard Distance to Traffic Noise Level Contours, Feet Data Input Sheet
Project Name : Santa Fe Flores Townhomes
Project Number : 10587 Surface Refelction: CNEL
Modeled Condition : Long-Term (2050) Assessment Metric: Hard Peak ratio to ADT: 10.0
Traffic Desc. (Peak or ADT) : ADT
Segment Roadway Segment Traffic Vol. % Autos %MT % HT Day % Eve % Night %
WITHOUT PROJECT
1 S. Santa Fe Avenue Smilax Road to Bosstick Boulevard 22,200 45 50 95.00 3.00 2.00 77.00 10.00 13.00 2 S. Santa Fe Avenue Bosstick Boulevard to Community Drive 22,200 45 50 95.00 3.00 2.00 77.00 10.00 13.00 3 S. Santa Fe Avenue Community Drive to Las Flores Drive 22,200 45 50 95.00 3.00 2.00 77.00 10.00 13.00 4 S. Santa Fe Avenue Las Flores Drive to N. Rancho Santa Fe Road 21,300 45 50 95.00 3.00 2.00 77.00 10.00 13.00 5 S. Santa Fe Avenue N. Rancho Santa Fe Road and N. Pacific Street 24,400 40 50 95.00 3.00 2.00 77.00 10.00 13.00 6 Hollencrest Road De Leone Road to Hollenbeck Road 830 25 50 95.00 3.00 2.00 77.00 10.00 13.00 7 N. Rancho Santa Fe Road S. Santa Fe Avenue to Capalina Road 16,800 40 50 95.00 3.00 2.00 77.00 10.00 13.00
WITH PROJECT
1 S. Santa Fe Avenue Smilax Road to Bosstick Boulevard 22,310 45 50 95.00 3.00 2.00 77.00 10.00 13.00 2 S. Santa Fe Avenue Bosstick Boulevard to Community Drive 22,310 45 50 95.00 3.00 2.00 77.00 10.00 13.00 3 S. Santa Fe Avenue Community Drive to Las Flores Drive 22,570 45 50 95.00 3.00 2.00 77.00 10.00 13.00 4 S. Santa Fe Avenue Las Flores Drive to N. Rancho Santa Fe Road 21,480 45 50 95.00 3.00 2.00 77.00 10.00 13.00 5 S. Santa Fe Avenue N. Rancho Santa Fe Road and N. Pacific Street 24,470 40 50 95.00 3.00 2.00 77.00 10.00 13.00 6 Hollencrest Road De Leone Road to Hollenbeck Road 870 25 50 95.00 3.00 2.00 77.00 10.00 13.00 7 N. Rancho Santa Fe Road S. Santa Fe Avenue to Capalina Road 16,910 40 50 95.00 3.00 2.00 77.00 10.00 13.00 Predicted Noise Levels
Project Name : Santa Fe Flores Townhomes
Project Number : 10587
Modeled Condition : Long-Term (2050)
Assessment Metric: Hard
Segment Roadway Segment Auto MT HT Total 75 dB 70 dB 65 dB 60 dB 55 dB 50 dB
WITHOUT PROJECT
1 S. Santa Fe Avenue Smilax Road to Bosstick Boulevard 71.0 64.2 67.0 73.0 32 100 315 998 3,155 9,976 2 S. Santa Fe Avenue Bosstick Boulevard to Community Drive 71.0 64.2 67.0 73.0 32 100 315 998 3,155 9,976 3 S. Santa Fe Avenue Community Drive to Las Flores Drive 71.0 64.2 67.0 73.0 32 100 315 998 3,155 9,976 4 S. Santa Fe Avenue Las Flores Drive to N. Rancho Santa Fe Road 70.8 64.0 66.8 72.9 31 97 308 975 3,083 9,749 5 S. Santa Fe Avenue N. Rancho Santa Fe Road and N. Pacific Street 69.9 63.8 66.9 72.3 27 85 269 849 2,685 8,491 6 Hollencrest Road De Leone Road to Hollenbeck Road 49.3 46.0 51.8 54.4 0 1 4 14 44 138 7 N. Rancho Santa Fe Road S. Santa Fe Avenue to Capalina Road 68.3 62.2 65.3 70.7 19 59 186 587 1,858 5,874
WITH PROJECT
1 S. Santa Fe Avenue Smilax Road to Bosstick Boulevard 71.0 64.2 67.0 73.1 32 102 323 1,021 3,228 10,209 2 S. Santa Fe Avenue Bosstick Boulevard to Community Drive 71.0 64.2 67.0 73.1 32 102 323 1,021 3,228 10,209 3 S. Santa Fe Avenue Community Drive to Las Flores Drive 71.0 64.3 67.0 73.1 32 102 323 1,021 3,228 10,209 4 S. Santa Fe Avenue Las Flores Drive to N. Rancho Santa Fe Road 70.8 64.1 66.8 72.9 31 97 308 975 3,083 9,749 5 S. Santa Fe Avenue N. Rancho Santa Fe Road and N. Pacific Street 69.9 63.8 66.9 72.3 27 85 269 849 2,685 8,491 6 Hollencrest Road De Leone Road to Hollenbeck Road 49.6 46.2 52.0 54.6 0 1 5 14 46 144 7 N. Rancho Santa Fe Road S. Santa Fe Avenue to Capalina Road 68.3 62.2 65.3 70.7 19 59 186 587 1,858 5,874 FHWA RD-77-108
Traffic Noise Prediction Model
Speed
(Mph)
Distance
to CL K-Factor
FHWA RD-77-108
Traffic Noise Prediction Model
Noise Levels, dBA Hard Distance to Traffic Noise Level Contours, Feet Noise Analysis
Santa Fe Flores Townhomes Project
ATTACHMENT 7
SoundPLAN Data – On-site Generated Noise
10587 Santa Fe Flores Townhomes
SoundPLAN Data - HVAC
Noise
Source name Reference Level Cwall CI CT
dB(A) dB(A) dB(A) dB(A)
HVAC1 Lw/unit 75 - - -
HVAC2 Lw/unit 75 - - -
HVAC3 Lw/unit 75 - - -
HVAC4 Lw/unit 75 - - -
HVAC5 Lw/unit 75 - - -
HVAC6 Lw/unit 75 - - -
HVAC7 Lw/unit 75 - - -
HVAC8 Lw/unit 75 - - -
HVAC9 Lw/unit 75 - - -
HVAC10 Lw/unit 75 - - -
HVAC11 Lw/unit 75 - - -
HVAC12 Lw/unit 75 - - -
HVAC13 Lw/unit 75 - - -
HVAC14 Lw/unit 75 - - -
HVAC15 Lw/unit 75 - - -
HVAC16 Lw/unit 75 - - -
HVAC17 Lw/unit 75 - - -
HVAC18 Lw/unit 75 - - -
HVAC19 Lw/unit 75 - - -
HVAC20 Lw/unit 75 - - -
HVAC21 Lw/unit 75 - - -
HVAC22 Lw/unit 75 - - -
HVAC23 Lw/unit 75 - - -
HVAC24 Lw/unit 75 - - -
HVAC25 Lw/unit 75 - - -
HVAC26 Lw/unit 75 - - -
HVAC27 Lw/unit 75 - - -
HVAC28 Lw/unit 75 - - -
HVAC29 Lw/unit 75 - - -
HVAC30 Lw/unit 75 - - -
HVAC31 Lw/unit 75 - - -
HVAC32 Lw/unit 75 - - -
HVAC33 Lw/unit 75 - - -
HVAC34 Lw/unit 75 - - -
HVAC35 Lw/unit 75 - - -
HVAC36 Lw/unit 75 - - -
HVAC37 Lw/unit 75 - - -
HVAC38 Lw/unit 75 - - -
HVAC39 Lw/unit 75 - - -
HVAC40 Lw/unit 75 - - -
HVAC41 Lw/unit 75 - - -
HVAC42 Lw/unit 75 - - -
HVAC43 Lw/unit 75 - - -
HVAC44 Lw/unit 75 - - -
HVAC45 Lw/unit 75 - - -
HVAC46 Lw/unit 75 - - -
Corrections
HVAC
10587 Santa Fe Flores Townhomes
SoundPLAN Data - HVAC
Noise
No. X Y Height Level
(meters) dB(A)
1 481468.23 3668972.47 182.38 32.8
2 481477.03 3668933.16 185.26 34.8
3 481491.51 3668901.09 186.46 35.5
4 481513.24 3668863.85 186.82 35.3
5 481534.96 3668832.30 186.16 34.3
6 481452.72 3668803.33 161.69 33.9
7 481417.03 3668787.30 160.02 35.0
8 481389.61 3668758.33 159.84 41.9
9 481373.58 3668720.06 157.61 40.7
10 481348.75 3668660.57 154.54 35.0
11 481317.72 3668679.71 153.92 35.5
12 481280.47 3668693.16 153.14 35.8
13 481232.89 3668717.47 152.07 34.9
14 481185.82 3668741.78 151.46 33.6
15 481288.85 3668803.43 156.64 39.0
16 481306.71 3668845.77 157.91 38.0
17 481370.21 3668885.46 167.45 39.6
18 481303.57 3668756.45 154.67 38.8
Coordinates
(meters)
Receivers
10587 Santa Fe Flores Townhomes
SoundPLAN Data - HVAC
Noise
Source name Level
dB(A)
1 1.Fl 32.8 0.0
HVAC1 10.9
HVAC2 11.3
HVAC3 10.7
HVAC4 12.3
HVAC5 10.8
HVAC6 9.9
HVAC7 8.0
HVAC8 7.6
HVAC9 7.4
HVAC10 5.6
HVAC11 6.3
HVAC12 6.3
HVAC13 14.7
HVAC14 15.0
HVAC15 12.6
HVAC16 10.0
HVAC17 13.2
HVAC18 15.4
HVAC19 16.1
HVAC20 16.3
HVAC21 16.5
HVAC22 15.4
HVAC23 16.3
HVAC24 16.9
HVAC25 17.5
HVAC26 18.9
HVAC27 18.7
HVAC28 17.9
HVAC29 18.3
HVAC30 18.3
HVAC31 18.5
HVAC32 18.7
HVAC33 18.7
HVAC34 18.9
HVAC35 19.2
HVAC36 19.2
HVAC37 19.2
HVAC38 19.2
HVAC39 16.8
HVAC40 16.8
HVAC41 16.9
HVAC42 16.8
HVAC43 16.8
HVAC44 16.9
HVAC45 16.8
HVAC46 16.7
2 1.Fl 34.8 0.0
HVAC1 13.7
HVAC2 15.4
HVAC3 14.9
HVAC4 15.6
HVAC5 15.6
HVAC6 12.6
HVAC7 10.1
HVAC8 10.9
HVAC9 16.3
HVAC10 7.6
HVAC11 9.0
HVAC12 7.9
HVAC13 12.6
HVAC14 14.5
HVAC15 14.9
HVAC16 11.9
HVAC17 14.8
HVAC18 12.9
HVAC19 17.2
HVAC20 18.9
HVAC21 16.9
HVAC22 17.0
HVAC23 17.6
HVAC24 18.2
HVAC25 18.8
HVAC26 20.6
HVAC27 20.1
HVAC28 19.3
HVAC29 20.7
HVAC30 19.6
HVAC31 20.6
HVAC32 21.1
HVAC33 20.8
HVAC34 21.8
HVAC35 21.4
HVAC36 21.0
HVAC37 21.4
HVAC38 21.2
HVAC39 18.3
HVAC40 18.6
HVAC41 18.7
HVAC42 19.7
HVAC43 19.0
HVAC44 18.7
HVAC45 19.6
HVAC46 19.4
Contributions
10587 Santa Fe Flores Townhomes
SoundPLAN Data - HVAC
Noise
Source name Level
dB(A)
3 1.Fl 35.5 0.0
HVAC1 15.8
HVAC2 15.9
HVAC3 15.3
HVAC4 15.9
HVAC5 16.1
HVAC6 16.2
HVAC7 12.8
HVAC8 17.0
HVAC9 16.7
HVAC10 16.8
HVAC11 14.0
HVAC12 9.8
HVAC13 11.9
HVAC14 13.2
HVAC15 14.4
HVAC16 14.8
HVAC17 13.3
HVAC18 10.2
HVAC19 17.2
HVAC20 17.9
HVAC21 18.9
HVAC22 17.5
HVAC23 17.3
HVAC24 17.8
HVAC25 19.0
HVAC26 20.7
HVAC27 20.2
HVAC28 19.7
HVAC29 21.0
HVAC30 19.6
HVAC31 21.6
HVAC32 22.6
HVAC33 21.9
HVAC34 21.7
HVAC35 21.6
HVAC36 21.0
HVAC37 22.4
HVAC38 22.0
HVAC39 19.2
HVAC40 20.0
HVAC41 20.0
HVAC42 20.1
HVAC43 19.5
HVAC44 19.0
HVAC45 20.5
HVAC46 20.2
4 1.Fl 35.3 0.0
HVAC1 16.4
HVAC2 16.8
HVAC3 15.6
HVAC4 16.1
HVAC5 16.9
HVAC6 16.7
HVAC7 17.0
HVAC8 17.4
HVAC9 17.0
HVAC10 17.4
HVAC11 17.6
HVAC12 16.9
HVAC13 14.0
HVAC14 13.0
HVAC15 13.4
HVAC16 12.8
HVAC17 11.7
HVAC18 10.4
HVAC19 18.2
HVAC20 16.6
HVAC21 16.6
HVAC22 18.4
HVAC23 16.8
HVAC24 17.5
HVAC25 18.1
HVAC26 19.7
HVAC27 19.2
HVAC28 19.4
HVAC29 19.8
HVAC30 18.7
HVAC31 21.1
HVAC32 22.6
HVAC33 21.7
HVAC34 21.0
HVAC35 20.8
HVAC36 20.5
HVAC37 21.5
HVAC38 21.2
HVAC39 19.4
HVAC40 20.7
HVAC41 19.9
HVAC42 19.5
HVAC43 19.3
HVAC44 19.0
HVAC45 20.0
HVAC46 19.6
Contributions
10587 Santa Fe Flores Townhomes
SoundPLAN Data - HVAC
Noise
Source name Level
dB(A)
5 1.Fl 34.3 0.0
HVAC1 16.6
HVAC2 17.0
HVAC3 15.4
HVAC4 15.9
HVAC5 17.2
HVAC6 17.0
HVAC7 17.3
HVAC8 17.8
HVAC9 16.5
HVAC10 16.9
HVAC11 17.9
HVAC12 17.4
HVAC13 15.4
HVAC14 15.3
HVAC15 14.9
HVAC16 11.7
HVAC17 13.4
HVAC18 11.5
HVAC19 16.2
HVAC20 15.8
HVAC21 15.5
HVAC22 15.7
HVAC23 16.4
HVAC24 16.3
HVAC25 16.6
HVAC26 16.9
HVAC27 17.2
HVAC28 18.0
HVAC29 18.2
HVAC30 17.2
HVAC31 20.1
HVAC32 20.6
HVAC33 19.8
HVAC34 19.5
HVAC35 19.3
HVAC36 19.2
HVAC37 20.0
HVAC38 19.6
HVAC39 18.3
HVAC40 19.8
HVAC41 18.8
HVAC42 18.7
HVAC43 18.4
HVAC44 18.2
HVAC45 19.5
HVAC46 18.9
6 1.Fl 33.9 0.0
HVAC1 19.1
HVAC2 19.7
HVAC3 20.0
HVAC4 20.6
HVAC5 20.0
HVAC6 19.7
HVAC7 19.7
HVAC8 20.9
HVAC9 21.4
HVAC10 21.6
HVAC11 20.5
HVAC12 18.2
HVAC13 16.6
HVAC14 13.1
HVAC15 12.5
HVAC16 3.4
HVAC17 7.6
HVAC18 12.8
HVAC19 7.2
HVAC20 6.5
HVAC21 6.2
HVAC22 5.5
HVAC23 6.2
HVAC24 6.8
HVAC25 6.4
HVAC26 5.1
HVAC27 4.9
HVAC28 3.7
HVAC29 4.4
HVAC30 4.8
HVAC31 7.7
HVAC32 9.1
HVAC33 10.2
HVAC34 11.5
HVAC35 13.9
HVAC36 15.6
HVAC37 12.7
HVAC38 10.8
HVAC39 12.5
HVAC40 15.4
HVAC41 19.5
HVAC42 21.6
HVAC43 23.9
HVAC44 23.6
HVAC45 20.3
HVAC46 18.1
Contributions
10587 Santa Fe Flores Townhomes
SoundPLAN Data - HVAC
Noise
Source name Level
dB(A)
7 1.Fl 35.0 0.0
HVAC1 20.9
HVAC2 22.7
HVAC3 23.1
HVAC4 24.2
HVAC5 23.1
HVAC6 19.1
HVAC7 20.3
HVAC8 24.5
HVAC9 21.3
HVAC10 22.6
HVAC11 20.7
HVAC12 16.4
HVAC13 14.7
HVAC14 13.8
HVAC15 13.1
HVAC16 12.5
HVAC17 13.7
HVAC18 14.6
HVAC19 10.3
HVAC20 9.9
HVAC21 9.1
HVAC22 5.0
HVAC23 9.5
HVAC24 10.5
HVAC25 7.1
HVAC26 5.8
HVAC27 5.3
HVAC28 5.1
HVAC29 5.4
HVAC30 6.0
HVAC31 9.4
HVAC32 11.3
HVAC33 13.0
HVAC34 14.2
HVAC35 15.6
HVAC36 16.8
HVAC37 15.0
HVAC38 11.7
HVAC39 16.5
HVAC40 15.4
HVAC41 20.6
HVAC42 21.6
HVAC43 22.7
HVAC44 23.2
HVAC45 15.9
HVAC46 12.6
8 1.Fl 41.9 0.0
HVAC1 25.3
HVAC2 27.2
HVAC3 28.2
HVAC4 29.7
HVAC5 27.8
HVAC6 26.5
HVAC7 27.0
HVAC8 30.4
HVAC9 31.8
HVAC10 32.6
HVAC11 30.5
HVAC12 29.0
HVAC13 24.2
HVAC14 23.6
HVAC15 22.9
HVAC16 23.5
HVAC17 24.0
HVAC18 26.7
HVAC19 24.0
HVAC20 20.8
HVAC21 20.6
HVAC22 12.9
HVAC23 12.3
HVAC24 8.7
HVAC25 7.7
HVAC26 6.6
HVAC27 7.0
HVAC28 5.3
HVAC29 5.7
HVAC30 5.6
HVAC31 9.4
HVAC32 12.8
HVAC33 20.5
HVAC34 21.5
HVAC35 21.9
HVAC36 24.3
HVAC37 12.8
HVAC38 10.1
HVAC39 17.4
HVAC40 19.7
HVAC41 24.3
HVAC42 24.1
HVAC43 25.0
HVAC44 27.5
HVAC45 24.6
HVAC46 23.6
Contributions
10587 Santa Fe Flores Townhomes
SoundPLAN Data - HVAC
Noise
Source name Level
dB(A)
9 1.Fl 40.7 0.0
HVAC1 25.3
HVAC2 29.1
HVAC3 32.7
HVAC4 32.4
HVAC5 28.9
HVAC6 25.2
HVAC7 23.8
HVAC8 27.0
HVAC9 29.9
HVAC10 28.6
HVAC11 26.2
HVAC12 24.1
HVAC13 20.3
HVAC14 15.8
HVAC15 15.2
HVAC16 14.6
HVAC17 15.8
HVAC18 17.5
HVAC19 21.4
HVAC20 19.0
HVAC21 20.1
HVAC22 20.8
HVAC23 21.8
HVAC24 20.4
HVAC25 10.5
HVAC26 18.0
HVAC27 16.2
HVAC28 16.2
HVAC29 10.1
HVAC30 6.9
HVAC31 7.8
HVAC32 9.5
HVAC33 17.7
HVAC34 18.4
HVAC35 19.3
HVAC36 17.6
HVAC37 10.4
HVAC38 10.1
HVAC39 17.6
HVAC40 18.1
HVAC41 24.4
HVAC42 20.1
HVAC43 20.7
HVAC44 23.7
HVAC45 22.0
HVAC46 22.1
10 1.Fl 35.0 0.0
HVAC1 23.2
HVAC2 23.0
HVAC3 25.5
HVAC4 24.2
HVAC5 22.0
HVAC6 20.8
HVAC7 18.4
HVAC8 19.8
HVAC9 21.7
HVAC10 21.6
HVAC11 19.3
HVAC12 17.5
HVAC13 14.7
HVAC14 14.2
HVAC15 19.8
HVAC16 14.5
HVAC17 13.5
HVAC18 12.5
HVAC19 15.5
HVAC20 16.4
HVAC21 16.2
HVAC22 14.8
HVAC23 15.7
HVAC24 14.9
HVAC25 15.2
HVAC26 12.9
HVAC27 11.5
HVAC28 11.0
HVAC29 12.0
HVAC30 14.6
HVAC31 8.1
HVAC32 8.3
HVAC33 14.8
HVAC34 15.3
HVAC35 14.1
HVAC36 13.4
HVAC37 9.6
HVAC38 9.6
HVAC39 16.7
HVAC40 16.9
HVAC41 18.7
HVAC42 20.2
HVAC43 17.3
HVAC44 19.0
HVAC45 18.8
HVAC46 18.9
Contributions
10587 Santa Fe Flores Townhomes
SoundPLAN Data - HVAC
Noise
Source name Level
dB(A)
11 1.Fl 35.5 0.0
HVAC1 24.8
HVAC2 23.8
HVAC3 25.0
HVAC4 21.7
HVAC5 22.2
HVAC6 21.5
HVAC7 18.5
HVAC8 18.1
HVAC9 18.5
HVAC10 17.1
HVAC11 17.1
HVAC12 16.9
HVAC13 22.5
HVAC14 23.1
HVAC15 23.3
HVAC16 21.4
HVAC17 22.6
HVAC18 21.3
HVAC19 18.5
HVAC20 19.5
HVAC21 19.7
HVAC22 18.9
HVAC23 19.0
HVAC24 11.4
HVAC25 11.0
HVAC26 12.4
HVAC27 12.9
HVAC28 10.9
HVAC29 11.4
HVAC30 9.2
HVAC31 7.0
HVAC32 7.0
HVAC33 6.8
HVAC34 7.5
HVAC35 8.4
HVAC36 8.9
HVAC37 8.8
HVAC38 8.8
HVAC39 12.4
HVAC40 12.5
HVAC41 12.4
HVAC42 13.1
HVAC43 14.6
HVAC44 17.4
HVAC45 15.9
HVAC46 16.5
12 1.Fl 35.8 0.0
HVAC1 24.6
HVAC2 22.1
HVAC3 22.7
HVAC4 20.0
HVAC5 20.8
HVAC6 23.8
HVAC7 22.4
HVAC8 19.6
HVAC9 18.0
HVAC10 17.7
HVAC11 19.4
HVAC12 21.6
HVAC13 22.9
HVAC14 22.3
HVAC15 22.1
HVAC16 21.0
HVAC17 21.5
HVAC18 21.6
HVAC19 19.8
HVAC20 19.3
HVAC21 19.8
HVAC22 18.8
HVAC23 16.3
HVAC24 18.8
HVAC25 12.9
HVAC26 12.0
HVAC27 12.7
HVAC28 10.6
HVAC29 11.0
HVAC30 10.7
HVAC31 15.5
HVAC32 7.5
HVAC33 7.2
HVAC34 7.9
HVAC35 8.6
HVAC36 8.9
HVAC37 9.0
HVAC38 14.4
HVAC39 18.4
HVAC40 16.4
HVAC41 16.3
HVAC42 16.8
HVAC43 17.7
HVAC44 19.2
HVAC45 18.6
HVAC46 18.5
Contributions
10587 Santa Fe Flores Townhomes
SoundPLAN Data - HVAC
Noise
Source name Level
dB(A)
13 1.Fl 34.9 0.0
HVAC1 22.6
HVAC2 20.1
HVAC3 19.5
HVAC4 18.4
HVAC5 19.4
HVAC6 21.8
HVAC7 21.1
HVAC8 19.1
HVAC9 18.4
HVAC10 17.8
HVAC11 18.6
HVAC12 20.1
HVAC13 20.6
HVAC14 21.2
HVAC15 24.3
HVAC16 21.3
HVAC17 19.1
HVAC18 18.2
HVAC19 19.1
HVAC20 19.5
HVAC21 18.1
HVAC22 17.5
HVAC23 19.1
HVAC24 18.2
HVAC25 11.9
HVAC26 13.9
HVAC27 16.7
HVAC28 16.0
HVAC29 14.9
HVAC30 9.8
HVAC31 10.8
HVAC32 13.7
HVAC33 9.0
HVAC34 8.4
HVAC35 8.0
HVAC36 7.8
HVAC37 10.6
HVAC38 16.5
HVAC39 16.6
HVAC40 16.5
HVAC41 15.5
HVAC42 16.1
HVAC43 16.9
HVAC44 18.2
HVAC45 16.8
HVAC46 17.7
14 1.Fl 33.6 0.0
HVAC1 18.6
HVAC2 17.5
HVAC3 17.1
HVAC4 19.4
HVAC5 17.5
HVAC6 18.4
HVAC7 18.1
HVAC8 19.8
HVAC9 19.5
HVAC10 16.6
HVAC11 20.0
HVAC12 18.8
HVAC13 18.4
HVAC14 18.5
HVAC15 19.9
HVAC16 19.4
HVAC17 18.3
HVAC18 19.5
HVAC19 16.3
HVAC20 15.9
HVAC21 17.4
HVAC22 16.9
HVAC23 15.7
HVAC24 18.1
HVAC25 18.4
HVAC26 18.5
HVAC27 16.2
HVAC28 15.6
HVAC29 14.7
HVAC30 13.7
HVAC31 9.6
HVAC32 10.4
HVAC33 9.7
HVAC34 10.8
HVAC35 9.9
HVAC36 9.0
HVAC37 12.0
HVAC38 13.8
HVAC39 15.6
HVAC40 15.8
HVAC41 15.3
HVAC42 15.6
HVAC43 15.5
HVAC44 15.7
HVAC45 15.4
HVAC46 16.9
Contributions
10587 Santa Fe Flores Townhomes
SoundPLAN Data - HVAC
Noise
Source name Level
dB(A)
15 1.Fl 39.0 0.0
HVAC1 14.4
HVAC2 12.0
HVAC3 11.4
HVAC4 11.2
HVAC5 12.0
HVAC6 13.6
HVAC7 14.2
HVAC8 12.6
HVAC9 12.3
HVAC10 20.2
HVAC11 13.2
HVAC12 14.5
HVAC13 22.9
HVAC14 26.3
HVAC15 31.3
HVAC16 32.6
HVAC17 26.7
HVAC18 23.4
HVAC19 26.5
HVAC20 20.2
HVAC21 26.1
HVAC22 25.0
HVAC23 26.2
HVAC24 25.1
HVAC25 14.4
HVAC26 17.2
HVAC27 23.1
HVAC28 21.7
HVAC29 17.7
HVAC30 12.0
HVAC31 7.6
HVAC32 6.7
HVAC33 6.2
HVAC34 7.2
HVAC35 8.3
HVAC36 9.0
HVAC37 9.8
HVAC38 10.5
HVAC39 12.6
HVAC40 18.2
HVAC41 16.0
HVAC42 16.0
HVAC43 15.8
HVAC44 21.0
HVAC45 18.8
HVAC46 23.9
16 1.Fl 38.0 0.0
HVAC1 14.5
HVAC2 15.2
HVAC3 15.1
HVAC4 15.0
HVAC5 15.9
HVAC6 15.8
HVAC7 19.0
HVAC8 19.2
HVAC9 18.3
HVAC10 7.5
HVAC11 19.4
HVAC12 21.1
HVAC13 22.7
HVAC14 23.7
HVAC15 25.5
HVAC16 27.4
HVAC17 24.9
HVAC18 25.3
HVAC19 19.6
HVAC20 22.7
HVAC21 28.3
HVAC22 29.4
HVAC23 23.5
HVAC24 19.9
HVAC25 20.6
HVAC26 21.7
HVAC27 27.7
HVAC28 26.5
HVAC29 21.9
HVAC30 18.3
HVAC31 8.7
HVAC32 6.8
HVAC33 5.6
HVAC34 7.7
HVAC35 6.8
HVAC36 6.9
HVAC37 8.5
HVAC38 10.9
HVAC39 11.2
HVAC40 8.3
HVAC41 6.8
HVAC42 6.8
HVAC43 6.8
HVAC44 6.7
HVAC45 8.7
HVAC46 10.7
Contributions
10587 Santa Fe Flores Townhomes
SoundPLAN Data - HVAC
Noise
Source name Level
dB(A)
17 1.Fl 39.6 0.0
HVAC1 18.4
HVAC2 18.6
HVAC3 15.2
HVAC4 13.6
HVAC5 18.7
HVAC6 19.0
HVAC7 20.2
HVAC8 20.6
HVAC9 12.5
HVAC10 9.7
HVAC11 17.3
HVAC12 21.0
HVAC13 11.2
HVAC14 7.8
HVAC15 7.3
HVAC16 7.1
HVAC17 7.7
HVAC18 11.5
HVAC19 15.3
HVAC20 15.2
HVAC21 14.9
HVAC22 16.0
HVAC23 15.7
HVAC24 16.4
HVAC25 25.1
HVAC26 26.3
HVAC27 25.1
HVAC28 30.3
HVAC29 28.8
HVAC30 30.9
HVAC31 29.5
HVAC32 26.7
HVAC33 27.0
HVAC34 24.4
HVAC35 22.1
HVAC36 21.2
HVAC37 23.0
HVAC38 26.6
HVAC39 25.9
HVAC40 18.3
HVAC41 15.6
HVAC42 15.6
HVAC43 15.5
HVAC44 15.4
HVAC45 19.5
HVAC46 23.7
18 1.Fl 38.8 0.0
HVAC1 29.2
HVAC2 23.9
HVAC3 22.0
HVAC4 22.1
HVAC5 24.0
HVAC6 29.5
HVAC7 29.2
HVAC8 23.7
HVAC9 22.4
HVAC10 21.3
HVAC11 23.6
HVAC12 28.1
HVAC13 26.8
HVAC14 25.0
HVAC15 27.6
HVAC16 21.7
HVAC17 22.6
HVAC18 28.7
HVAC19 12.2
HVAC20 11.8
HVAC21 12.8
HVAC22 11.4
HVAC23 9.1
HVAC24 11.0
HVAC25 7.1
HVAC26 6.5
HVAC27 7.5
HVAC28 5.7
HVAC29 5.7
HVAC30 5.2
HVAC31 5.4
HVAC32 4.9
HVAC33 4.0
HVAC34 4.5
HVAC35 5.4
HVAC36 6.0
HVAC37 6.5
HVAC38 7.7
HVAC39 11.6
HVAC40 9.5
HVAC41 9.2
HVAC42 9.8
HVAC43 11.0
HVAC44 22.4
HVAC45 12.0
HVAC46 12.2
Contributions