FLORA TERRA DISPENSARY
SANTA ROSA, CALIFORNIA 95404
1226 4TH STREET
T-1
·
·
·
SITE
FLORA TERRA
17 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
Attachment 4
T-2
FLORA TERRA
17 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
T-3
FLORA TERRA
17 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
1 A-0
N
FLORA TERRA
17 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
1 A-1
N
FLORA TERRA
17 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
1 A-1.1
N
FLORA TERRA
17 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
1 A-1.2
N
FLORA TERRA
17 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
1 A-1.3
N
FLORA TERRA
17 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
FLORA TERRA
17 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
1 A-1.4
N
1 A-1.5
N
FLORA TERRA
17 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
FLORA TERRA
17 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
1 A-2
FLORA TERRA
17 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
1 A-2.1
1 2
A-3
FLORA TERRA
17 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
1 A-3.1
FLORA TERRA
17 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
1 2
A-4
FLORA TERRA
17 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
1 2
A-4.1
FLORA TERRA
17 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
FLORA TERRA
17 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
A-5
4 31
2 1
A-6
FLORA TERRA
17 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
1 FLORA TERRA
17 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
M0.1
MECHANICAL
LEGEND & NOTES
MECHANICAL LEGEND
1. INSULATION SHALL MEET THE CALIFORNIA QUALITY STANDARD PER SECTION 110.8 2016 ENERGY EFFICIENCY STANDARDS (E.E.S.).
2. ALL PIPING AND DUCTWORK SHALL BE INSULATED CONSISTENT WITH THE REQUIREMENTS OF SECTIONS 120.3, 120.4 AND 120.7 TITLE 24 ENERGY STANDARDS AND CHAPTER 6 OF CMC.
3. ALL HVAC SYSTEMS SHALL MEET THE CONTROL REQUIREMENTS PER SECTION 110.2 AND 120.2.
4. CERTIFICATE OF ACCEPTANCE AND ALL RELATED ACCEPTANCE DOCUMENTS
SHALL BE SUBMITTED TO THE FIELD INSPECTOR
DURING CONSTRUCTION. CERTIFICATE OF OCCUPANCY WILL NOT BE ISSUED UNTIL THESE FORMS ARE REVIEWED AND APPROVED.
5. DOORS AND WINDOWS SHALL MEET THE MINIMUM INFILTRATION REQUIREMENTS PER SECTION 110.6(a) and 110.6(b).
6. ALL HVAC EQUIPMENT AND APPLIANCES SHALL MEET THE REQUIREMENTS PER SECTION 110.1 - 110.3, 110.5, 120.1 - 120.4 TITLE 24 ENERGY STANDARDS.
TITLE 24 NOTES GENERAL NOTES
1. THESE PLANS ARE DIAGRAMMATIC ONLY, AND ILLUSTRATE GENERAL INTENT OF DUCTWORK / PIPE ROUTING, EQUIPMENT LOCATION, MOUNTING, ETC. CONTRACTOR SHALL MAINTAIN A CURRENT SET OF AS-BUILT DRAWINGS ON SITE AT ALL TIMES DURING CONSTRUCTION.
2. CODES: ALL HEATING, AIR CONDITIONING, AND VENTILATING WORK SHALL CONFIRM TO THE LATEST REQUIREMENTS OF THE CALIFORNIA BUILDING/MECHANICAL/PLUMBING CODES (2016), LATEST TITLE 24 ENERGY COMMISSION NON-RESIDENTIAL STANDARDS, N.F.P.A. AND THE LOCAL MECHANICAL CODE AND ANY OTHER LEGALLY CONSTITUTED BODY HAVING JURISDICTION THEREOF.
3. PERMITS: THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL FEES, PERMITS, AND LICENSES REQUIRED FOR THE INSTALLATION OF THE WORK AND SHALL DELIVER SAME TO THE OWNERS REPRESENTATIVE/ARCHITECT.
4. SHEET METAL DUCTWORK: ALL SUPPLY AND RETURN DUCTWORK MAINS AND BRANCHES SHALL BE A MINIMUM 26 GA. GALVANIZED SHEET METAL IN ACCORDANCE WITH THE LATEST SMACNA DUCT MANUAL, AND LOCAL CODES. SUPPLY AND RETURN DUCTWORK SHALL BE INSULATED PER NON-RESIDENTIAL TITLE 24.
5. FLEXIBLE DUCTWORK: DUCTWORK SHALL BE INSULATED HIGH PRESSURE FLEXIBLE DUCT WITH A FACTORY ASSEMBLY CONSISTING OF A GALVANIZED SPRING STEEL WIRE HELIX, A CONTINUOUS INNER LINER WRAPPED WITH NOMINAL 1 IN. THICK BY 1 LB/CU.
DENSITY GLASS FIBER INSULATION. THE ASSEMBLY SHALL BE ENCLOSED IN A CLASS 1 FIRE RESISTIVE VAPOR BARRIER JACKET, FACTORY SEALED AT BOTH ENDS. THE FLEXIBLE DUCT SHALL BE LISTED BY U.L. AND SHALL CONFORM TO THE 90-A CLASS 1 REQUIREMENTS OF THE N.F.P.A. FLEXIBLE DUCT SHALL BE INSULATED IN FULLY EXTENDED CONDITION FREE OF SAGS AND KINKS AS FAR AS PRACTICAL. MINIMUM THERMAL RESISTANCE SHALL BE PER TITLE 24. FLEXIBLE DUCT SHALL BE GLASS-FLEX, CAL-FLEX, CASCO OR APPROVED EQUAL.
6. EQUIPMENT: SHALL BE MODEL, TYPE AND CAPACITIES AS INDICATED ON THE DRAWINGS AND SHALL MEET OR EXCEED THE MINIMUM EFFICIENCY AS LISTED IN THE T24 BUILDING ENERGY EFFICIENCY STANDARDS.
7. CONTROLS: SHALL BE FURNISHED AND INSTALLED AS INDICATED ON THE DRAWINGS. THERMOSTATS: ALL THERMOSTATS TO BE TITLE-24 APPROVED. THERMOSTATS TO BE PROGRAMMABLE WITH NIGHT SET BACK FEATURES AND AUTOMATIC COOLING/ HEATING MODE CHANGE-OVER.
8. VENTILATION AIR SHALL NOT BE TRANSFERRED FROM ADJACENT DWELLING UNITS, GARAGES, OR CRAWLSPACES.
9. AIR INLETS (NOT EXHAUST) SHALL BE LOCATED AWAY FROM KNOWN CONTAMINANTS.
10. OCCUPIED AREAS OF MECHANICALLY VENTILATED BUILDINGS SHALL BE PROVIDED WITH AIR FILTRATION MEDIA FOR OUTSIDE AND RETURN AIR PRIOR TO OCCUPANCY THAT PROVIDES AT LEAST MERV OF 6.
11. AT THE TIME OF ROUGH INSTALLATION AND DURING STORAGE ON THE CONSTRUCTION SITE UNTIL FINAL START-UP OF HEATING,
COOLING AND VENTILATION EQUIPMENT, ALL DUCT AND OTHER RELATED RELATED AIR DISTRIBUTION COMPONENT OPENINGS
SHALL BE COVERED WITH TAPE, PLASTIC, SHEET METAL OR OTHER METHODS ACCEPTABLE TO THE ENFORCING AGENCY TO REDUCE THE AMOUNT OF DUST, WATER AND DEBRIS WHICH MAY ENTER THE SYSTEM PER SECTION 5.504.3 OF THE CALIFORNIA GREEN BUILDING.
12. EXHAUST DUCTS SHALL BE EQUIPPED WITH BACK-DRAFT DAMPERS PER SEC. 504.0 CMC.
13. IN ADDITION TO TESTING AND ADJUSTING, BEFORE A NEW SPACE CONDITIONING SYSTEM SERVING A BUILDING OR SPACE IS
OPERATED FOR NORMAL USE, BALANCE THE SYSTEM IN ACCORDANCE WITH THE PROCEDURES DEFINED BY THE TESTING, ADJUSTING AND BALANCING BUREAU NATIONAL STANDARDS, NEBB PROCEDURAL STANDARDS, OR AABC NATIONAL STANDARDS.
14. PROVIDE THE BUILDING OWNER OR REPRESENTATIVE WITH DETAILED OPERATING AND MAINTENANCE INSTRUCTIONS AND COPIES OF GUARANTEES/WARRANTIES FOR EACH SYSTEM. O&M INSTRUCTIONS SHALL BE CONSISTENT WITH OSHA REQUIREMENTS IN CCR, TITLE 8, SECTION 5142, AND OTHER REGULATIONS.
15. CALIFORNIA MECHANICAL CODE 2016 (CMC 2016), CALIFORNIA PLUMBING CODE 2016 (CPC 2016) AND 2016 TITLE 24 ENERGY STANDARDS ARE THE CURRENT CODES/STANDARDS THAT ARE APPLICABLE TO THIS PROJECT.
16. PROVIDE SMOKE DETECTORS IN MAIN SUPPLY DUCTS OF AIR MOVING SYSTEMS EXCEEDING 2,000 CFM.
17. ROOF ACCESS LADDER SHALL COMPLY WITH SECTION 304 CMC.
18. ACCESS PANELS: VERIFY & COORDINATE LOCATION WITH OWNER/ARCHITECT PRIOR TO INSTALLATION OF EQUIPMENT.
19. BATHROOM EXHAUST DUCTS SHALL BE GALVANIZED SHEET METAL. SUCH DUCTS MUST BE CONTINUOUS TO THE OUTSIDE OF THE BUILDING AND MUST BE EQUIPPED WITH BACKDRAFT DAMPERS.
20.FOR LIVING UNITS - KITCHEN EXHAUST TO BE TO BE DUCTED TO OUTDOORS. SUCH DUCTS MUST BE CONTINUOUS TO THE OUTSIDE OF THE BUILDING AND MUST BE EQUIPPED WITH A BACKDRAFT DAMPER.
21. CLOTHES DRYER EXHAUST DUCTS MUST BE OF APPROVED METAL CONSTRUCTION AND MUST HAVE SMOOTH INTERIOR SURFACES, HOWEVER, APPROVED FLEXIBLE DUCT CONNECTORS NOT MORE THAN 6'-0" IN LENGTH MAY BE USED WITH DOMESTIC DRYER EXHAUSTS. FLEXIBLE DUCT CONNECTORS SHALL NOT BE CONCEALED WITHIN THE CONSTRUCTION OF THE BUILDING PER SECTION 504.3 OF THE U.M.C. CLOTHES DRYER EXHAUST DUCTS MUST BE SUBSTANTIALLY AIRTIGHT AND MUST COMPLY WITH THE PROVISIONS OF SECTIONS 504.3 AND 908 OF THE U.M.C. CLOTHES DRYER EXHAUST DUCTS MUST BE CONTINUOUS TO THE OUTSIDE OF THE BUILDING AND MUST BE EQUIPPED WITH BACKDRAFT DAMPERS.
22. ALL DUCT SIZES ARE CLEAR INSIDE DIMENSIONS. ALLOW FOR DUCT INSULATION AND ACOUSTICAL LINER WHERE REQUIRED FOR OUTSIDE DIMENSIONS.
23. FACTORY-MADE FLEXIBLE AIR DUCTS AND CONNECTORS SHALL NOT BE MORE THAN 5 FEET IN LENGTH PER SECTION 603.4.1 CMC.
FLORA TERRA
1 7 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
M0.2
MECHANICAL
SCHEDULE
REMARKS MANUFACTURER & MODEL NO.
ELECTRICAL
V./PH./HZ.
FLA S.P. EXT.
W.G.)(IN.
FAN
TYPE UNIT LOCATION UNIT
NO.
EXHAUST FAN SCHEDULE
C.F.M.
VIBRATION
ISOLATION SONES
(HVI)
HP
(WATTS)
WEIGHT
(LBS)
120/1/60 --- 0.375 CEILINGCEILING
MOUNTED2.5FACTORY 12 SEE PLANS100(53) "COOK" GC-148
OR EQUALINTERLOCK WITH LIGHT SWITCH. PROVIDE WITH BACKDRAFT DAMPER AND FILTER BOX WITH CARBON FILTER. 1 EF
SUPPLY DIFFUSER SCHEDULE
UNIT
NO.MANUFACTURER MODELNECK
SIZE
FRAME
TYPE
RANGE
C.F.M.REMARKS
A
#VARIES PCS50-350WHITE.
MAX NC 25
RETURN / EXHAUST REGISTER SCHEDULE
UNIT
NO.MANUFACTURER MODELNECK
SIZE
FRAME
TYPE
RANGE
C.F.M.REMARKS
B
# -TITUS 0-1500 VARIES TITUSPARPERFORATED CEILING
RETURN REGISTER
MARK
PACKAGED ROOFTOP UNIT SCHEDULE - EXISTING TO REMAIN
CFM
PH VOLTSHZ
MCA
BHP
ELECTRICAL DATA
SEER
1 RTU
AREA
SERVED
UNIT
LOCATION
MIN
O.S.A.
CFM
DESIGN
AMBIENT
(DEG. F.)
E.S.P. (IN.
W.G.)
TOTAL
COOLING
MBH
SENSIBLE
COOLING
MBH
HTG. MBH
HSPFDESIGN
AMBIENT
(DEG. F.)
MAX
FUSE
OPER.
WEIGHT
MANUFACTURER &
MODEL NO. COP
REMARKS
ROOF SEE PLANS325 1,950BRYANT
583ANW042
C
#10"Ø TMRA400WHITE.
MAX NC 25 TITUS
SEE
RCP
SEE
RCP
SEE
RCP
PACKAGED ROOFTOP UNITS - GENERAL NOTES:
EXISTING TO REMAIN.
PROVIDE WITH 2" MERV 13 PLEATED FILTER.
PROVIDE WITH TITLE 24 COMPLIANT PROGRAMMABLE THERMOSTAT IF NOT EXISTING.
1 2
3 123 1 60 14.044.0 0.5 99/7060.028 45 - .75 48.6 60.0
8.2 -
208
TONNAGE
3.5 GRILLE/DIFFUSER MOUNTING
SCALE: NONE2
SCALE: NONE3 TYPICAL BRANCH DUCT DETAILS
SCALE: NONE1 TYPICAL DUCT MOUNT DETAIL
JOIST OR BLOCKING
DUCT
TYPICAL EXHAUST
1-1/8" SHEET METAL
STRAP AROUND DUCT
STRAP SWAY BRACE
1-1/8" SHEET METAL
1-1/2"x1-1/2"x1/8" ANGLE CLIP
FASTEN TO JOIST ABOVE
WITH LAG BOLT
12" MAX
RTU
16 1
6"Ø
EF
1 2
3 7
4T5
8 9
9 FLORA TERRA
1 7 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
1 SCALE: 3/8"=1'-0"
MECHANICAL ROOF PLAN 2 SCALE: 3/8"=1'-0"
MECHAINCAL FLOOR PLANM2.1
MECHANICAL
FLOOR PLAN &
ROOF PLAN
FLOOR PLAN SHEET NOTES
ROOF MOUNTED SUPPLY AND RETURN DUCTS. ROUTE 16"Ø SUPPLY AND RETURN DUCTS DOWN FROM ROOF INTO CEILING SPACE.
PROVIDE NEW TOILET EXHAUST FAN. ROUTE EXISTING DUCT UP
THROUGH ROOF. PROVIDE GOOSNECK FITTING WITH INSECT SCREEN AT DISCHARGE.
INSTALL DUCTWORK AS HIGH AS POSSIBLE AND ADJUST DUCTWORK AS REQUIRED TO AVOID STRUCTURAL ELEMENTS. COORDINATE
ROUTING OF DUCTWORK IN FIELD WITH OTHER TRADES PRIOR TO FABRICATING ANY DUCTWORK.
FLEX DUCT 5'-0" MAX LENGTH TYPICAL FOR ALL.
PROPOSED LOCATION OF THERMOSTAT. COORDINATE EXACT
LOCATION WITH OWNER PRIOR TO INSTALLATION.
EXISTING LANDLORD PROVIDED 5 TON ROOFTOP UNIT (RTU-1). VERIFY EXACT LOCATION ON SITE.
VOLUME DAMPER AND SPIN-IN. TYPICAL FOR ALL.
ROUTE 3/4" CONDENSATE DRAIN WASTE LINE FROM EXISTING
CONDENSATE LINE ROUTED DOWN THRU ROOF AND TERMINATE AT
TAILPIECE OF LAVATORY PER LOCAL CODE REQUIREMENTS.
CEILING MOUNTED AIR SCRUBBER FOR ODOR CONTROL. PROVIDE
WITH CEILING MOUNTS AND SUPPORTS. PROVIDE WITH 8" CAN FILTER 75 CARBON FILTER.
MANUFACTURER = CAN FILTERS
MODEL = CAN FAN Q MAX 8"
785 CFM, 35 LB, 120V/1, 1.6 AMPS.
FLORA TERRA
1 7 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
P0.1
PLUMBING
LEGEND & NOTES
POINT OF CONNECTION / POINT OF DISCONNECTION
PLUMBING LEGEND
DWG/DWGSDRAWING/DRAWINGS
PSIPOUNDS PER SQUARE INCHPOUNDS PER SQUARE INCH
EQUIPMENT IDENTIFICATION SYMBOL
W.C.
SOV
VTR
SQ FT
TYP
SPEC
P&TRV
QTY
WATER COLUMN
PRESSURE AND TEMPERATURE RELIEF VALVE
SHUT OFF VALVE
VENT THRU ROOF
SQUARE FEET
TYPICAL
SPECIFICATION
QUANTITY
GALVGALVANIZED
PD
OPER
NTS
MTD
MIN
MS
MECH
MAX
IPS
I.E.
HD
MOP SINK / SERVICE SINK
PRESSURE DROP
NOT TO SCALE
OPERATING
MOUNTED
MINIMUM
MECHANICAL
MAXIMUM
IRON PIPE SIZE
INVERT ELEVATION
HEAD
FT HD
GPM
GA
GPF
FH
FT
FFE
ELECT
°F
ELEV
EA
DN
GALLONS PER MINUTE
GALLONS PER FLUSH
FINISHED FLOOR ELEVATION
FEET OF HEAD
GAUGE
FUME HOOD
FEET
DEGREES FAHRENHEIT
ELECTRICALELEVATION
EACH
DOWN
AFF
B/G
B/S
C.I.
DF
B/C
ARCH
AFG
FS
SOV
GPR
FD
ABOVE FINISHED FLOOR
ARCHITECT OR ARCHITECTURAL
ABOVE FINISHED GRADE
BELOW GRADE
DRINKING FOUNTAIN
CAST IRON
BELOW SLAB
BELOW COUNTER
GAS PRESSURE REGULATOR
PLUG VALVE / GAS COCK
PRESSURE GUAGE
SHUT OFF VALVE
FLOOR SINK
FLOOR DRAIN
FCO/COTG
WCO
WHA
CDCD
DIRECTION OF FLOW
PIPE SLOPE & DIRECTION OF FALL
FLOOR CLEANOUT OR CLEANOUT TO GRADE
WATER HAMMER ARRESTOR
WALL CLEANOUT
PIPE CONTINUATION
PIPE BREAK
THERMOMETER
CONDENSATE DRAIN PIPING
PIPE BRANCH - TOP CONNECTION
PIPE BRANCH - BOTTOM CONNECTION
PIPE BRANCH - SIDE CONNECTION
PIPE CAP
PIPE DOWN
PIPE UP
G
HW
G
HWR
VT
CW
SYMBOL
W
POC/POD
W
ABBREVIATION
DOMESTIC HOT WATER RETURN
DOMESTIC COLD WATER PIPING
NATURAL GAS PIPING - 8" WATER COLUMN
DOMESTIC HOT WATER
SANITARY VENT PIPING
SANITARY OR WASTE PIPING
EQUIPMENT IDENTIFIER
EQUIPMENT TYPE
DESCRIPTION
HB(+18")
GENERAL NOTES
1ALL WORK AND MATERIAL SHALL BE IN COMPLIANCE WITH AND PERFORMED AND
INSTALLED INCOMFORMANCE WITH THE FOLLOWING CODES AS ADOPTED AND AMENDED BY THE INSPECTING AUTHORITY. NOTHING IN THESE DRAWINGS IS TO BE CONSTRUED TO
PERMIT WORK NOT CONFORMING TO THESE CODES OR OTHERS APPLICABLE TO THIS PROJECT:
BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1, TITLE 24 C.C.R. 2019 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 C.C.R. 2019 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R. 2019 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R. 2019 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R. 2019 CALIFORNIA ENERGY CODE, PART 6, TITLE 24 C.C.R. 2019 CALIFORNIA FIRE CODE (CFC), PART 9, TITLE 24 C.C.R., 2019 CALIFORNIA REFERENCED STANDARDS, PART 12, TITLE 24 C.C.R. 2019 TITLE 19, CCR, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS 2013 NFPA 13 -
AUTOMATIC SPRINKLER SYSTEMS
2THE ARCHITECTURAL DESIGN DRAWINGS SHALL INDICATE ALL ACCESSIBLE FIXTURE LOCATIONS AND MOUNTING HEIGHTS. FURNISH ALL EXPOSED HOT WATER AND DRAIN PIPING BELOW ACCESSIBLE LAVATORIES AND SINKS WITH INSULATION. ALL WATER CLOSET FLUSHING LEVERS SHALL BE TO THE WIDE SIDE OF THE STALL. 3TRAPS FOR ALL LAVATORIES AND SINKS SHALL TRAP STRAIGHT BACK TO WALL WITH ALL REQUIRED OFFSETS HAPPENING WITHIN THE WALL.
4ALL PLUMBING WORK SHALL BE INSTALLED TO AVOID INTERFERENCE WITH ELECTRICAL AND MECHANICAL EQUIPMENT AND STRUCTURAL FRAMING.
5ALL CLEANOUTS SHALL BE INSTALLED WHERE EASILY ACCESSIBLE. THE CONTRACTOR
SHALL COORDINATE ALL CLEANOUT LOCATIONS WITH ALL EQUIPMENT, CABINETS AND OTHER OBSTRUCTION PRIOR TO ANY INSTALLATION. CLEANOUTS MUST BE EXTENDED TO FLUSH WITH FINISHED WALL.
6ALL PLUMBING FIXTURE VENTS SHALL TERMINATE A MINIMUM OF 12 INCHES FROM ANY VERTICAL SURFACE AND 10 FEET FROM ANY OUTSIDE AIR INTAKES. 7ALL VALVES, UNIONS, ETC. TO BE SAME SIZE AS PIPE UNLESS OTHERWISE INDICATED ON PLANS.
8UNIONS SHALL BE PROVIDED AND INSTALLED AFTER EACH VALVE AND PRIOR TO ALL EQUIPMENT CONNECTIONS.
9THE ARCHITECTURAL DESIGN DRAWINGS SHALL INDICATE THE EXACT LOCATIONS AND MOUNTING HEIGHTS OF ALL PLUMBING FIXTURES.
10BEFORE FABRICATION OR INSTALLATION THE CONTRACTOR SHALL VERIFY EXACT
LOCATIONS OF ALL MECHANICAL EQUIPMENT AND EQUIPMENT PROVIDED UNDER OTHER SECTIONS OF SPECIFICATIONS. ROUGH-IN LOCATIONS AND REQUIREMENTS SHALL BE COORDINATED IN THE FIELD.
11 ALL SEWER AND VENT PIPING LESS THAN 4" SHALL SLOPE AT 2%. 4" AND LARGER SHALL SLOPE AT 1%.
12ALL VALVES, TRAP PRIMERS, WATER HAMMER ARRESTERS OR OTHER EQUIPMENT
LOCATED IN WALLS OR ABOVE NON-ACCESSIBLE CEILINGS SHALL BE INSTALLED BEHIND AN ACCESS PANEL. ALL PIPING & DEVICES SHALL BE INSTALLED ABOVE CEILING, WITHIN WALLS, BELOW FLOORS, OR OTHERWISE CONCEALED. EXCEPT PIPING AND DEVICES INSTALLED IN MECHANICAL ROOMS AND OTHER UNFINISHED SPACES. 13ALL PLUMBING FIXTURES AND EQUIPMENT SHALL BE CERTIFIED BY THE CALIFORNIA
STATE ENERGY COMMISSION TO COMPLY WITH EFFICIENCY STANDARDS PER SECTION 110 OF THE TITLE-24 REGULATIONS.
14ALL HOT WATER SUPPLY & RETURN PIPING SHALL BE INSULATED. INSULATION SHALL HAVE A FLAME SPREAD OF NOT MORE THAN 25 AND A SMOKE DENSITY NOT EXCEEDING 50 PER CMC SEC. 12.1.2.1.8 SEE SPECIFICATION FOR OTHER REQUIREMENTS. 15PIPING THROUGH FIRE RATED WALLS SHALL BE PROTECTED PER U.L. FIRE RESISTANCE SYSTEM NO. WL1001. THE ARCHITECTURAL DESIGN DRAWINGS SHALL INDICATE ALL RATED WALL LOCATIONS.
16SEISMIC BRACING AND ANCHORAGE REQUIREMENTS ARE AS FOLLOWS:
A. HE SEISMIC ANCHORAGE FOR ALL MECHANICAL AND ELECTRICAL EQUIPMENT SHALL BE DESIGNED TO WITHSTAND A LATERAL FORCE.
1. CALCULATED AS SPECIFIED IN SECTION 1632A AND TABLE 16A-0 OF THE VOL. 2, TITLE 24, 2019 CBC. A LATERAL FORCE:
B. THE ATTACHMENT OF THE FOLLOWING ITEMS SHALL BE DESIGNED TO RESIST THE FORCES PRESCRIBED IN PART 2, TITLE 24, 2019 CBC:
1. EQUIPMENT WEIGHING LESS THAN 400 LBS. SUPPORTED DIRECTLY ON FLOOR OR ROOF.
2. FURNITURE REQUIRED TO BE ATTACHED IN ACCORDANCE WITH PART 2, TITLE 24, C.C.R..
3. TEMPORARY OR MOBILE EQUIPMENT.
4. EQUIPMENT WEIGHING LESS THAN 20 LBS. SUPPORTED BY VIBRATION ISOLATORS.
5. EQUIPMENT WEIGHING LESS THAN 20 LBS. SUSPENDED FROM A ROOF OR HUNG FROM A WALL.
17THE PLUMBING CONTRACTOR SHALL PROVIDE THE WATER & SEWER SYSTEMS TO A POINT OF CONNECTION 5'-0" OUTSIDE OF THE BUILDING. PIPING BEYOND THIS POINT IS
SPECIFIED UNDER ANOTHER SECTION OF THE SPECIFICATIONS AND SHALL BE AS SHOWN ON THE CIVIL DRAWINGS. FINAL CONNECTIONS TO SITE PIPING SHALL BE BY THE PLUMBING CONTRACTOR.
18WATER HAMMER ARRESTERS SHALL BE PROVIDED WHERE REQUIRED AND NECESSARY
FOR AND TO ALL FIXTURES, EQUIPMENT OR APPLIANCES WITH QUICK CLOSING VALVE AND SHALL BE OF TYPE SPECIFIED.
19ALL PIPE SIZES SHALL BE THE SAME AS THE UPSTREAM PIPE SIZES UNLESS OTHERWISE INDICATED ON PLAN.
20CLEAN OUT SHALL BE PROVIDED AS PER CALIFORNIA PLUMBING CODE SECTION 707. 21NO STRUCTURAL MEMBER SHALL BE CUT, NEITHER DRILLED NOR NOTCHED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM THE STRUCTURAL ENGINEER. 22THESE DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ARE NOT INTENDED TO INDICATE ALL DETAILS AND NECESSARY OFFSETS OF PIPING. THE CONTRACTOR SHALL
INSTALL MATERIAL AND EQUIPMENT IN A MANNER AS TO CONFORM TO STRUCTURE,
AVOID OBSTRUCTIONS, PRESERVE HEADROOM, AND KEEP OPENINGS AND PASSAGEWAYS CLEAR. ALL INSTALLATIONS SHALL BE CONSISTENT WITH NORMALLY ACCEPTABLE INDUSTRY STANDARDS. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT
IN WRITING OF ANY DISCREPANCIES OR CONFLICTS THAT WOULD EFFECT THE SYSTEM PERFORMANCE OR INCUR ADDITIONAL COSTS. THIS NOTIFICATION SHALL BE SUBMITTED PRIOR TO INSTALLATION OF THE ITEMS CONCERNED.
23EACH PLUMBING FIXTURES THAT CONNECT TO THE SANITARY SEWER SYSTEM SHALL BE PROPERLY TRAPPED AND VENTED IN ACCORDANCE WITH THE 2019 CALIFORNIA PLUMBING CODE.
24PROVIDE COMPLETE CONDENSATE DRAIN PIPING FOR ALL AC UNITS AND DISCHARGE CONDENSATE TO AN APPROVED RECEPTOR.
25ALL LAYOUTS, PIPE SIZES, FIXTURE & EQUIPMENT SELECTIONS SHOWN ON THESE PLANS ARE FOR REFERENCE ONLY. THE CONTRACTOR SHALL PROVIDE A COMPLETE PLUMBING SYSTEM. THE DESIGN, CALCULATIONS, FIXTURE, TRIM, EQUIPMENT AND MATERIALS
SELECTIONS & DRAWINGS SHALL BE SUBMITTED FOR REVIEW AND APPROVAL AS SPECIFIED.
TABLE 5.303.2.3 FIXTURE FLOW
RATES
FIXTURE TYPEMAXIMUM FLOW RATE AT 20% REDUCTION
SHOWERHEADS2.5 GPM @ 80 PSI
LAVATORY FAUCETS-NON RESIDENTIAL
LAVATORY FAUCETS-RESIDENTIAL
2.5 GPM @ 60 PSI
2.2 GPM @ 60 PSI
KITCHEN FAUCETS RESIDENTIAL
AND NON RESIDENTIAL1.8 GPM @ 80 PSI
WASH FOUNTAIN1.8 [RIM SPACE (IN.)/20 GPM @ 60 PSI]
METERING FAUCETS0.25 GALLONS PER CYCLE
METERING FAUCETS FOR WASH FOUNTAIN1.8 [RIM SPACE (IN.)/20 GPM @ 60 PSI] GRAVITY TANK TYPE WATER CLOSETS1.28 GALLONS PER FLUSH
FLUSHOMETERS TANK WATER CLOSETS1.28 GALLONS PER FLUSH
FLUSHOMETERS VALVE TYPE WATER CLOSETS 1.28 GALLONS PER FLUSH
ELECTROMECHANICAL HYDRAULIC WATER
CLOSETS1.28 GALLONS PER FLUSH
URINALS0.125 GALLONS PER FLUSH
INCLUDES SINGLE AND DUAL FLUSH WATER CLOSETS WITH AN EFFECTIVE FLUSH OF 1.28 GALLONS OR LESS:
SINGLE FLUSH TOILETS - THE EFFECTIVE FLUSH VOLUME SHALL NOT EXCEED 1.28 GALLONS (4.8 LITERS). THE EFFECTIVE FLUSH VOLUME IS THE AVERAGE FLUSH VOLUME WHEN TESTED IN ACCORDANCE WITH ASME A 112.19.233.2.
DUAL FLUSH TOILETS - THE EFFECTIVE FLUSH VOLUME SHALL NOT EXCEED 1.28 GALLONS (4.8 LITERS). THE EFFECTIVE FLUSH VOLUME IS DEFINED AS THE COMPOSITE, AVERAGE FLUSH VOLUME OF TWO REDUCED FLUSHES AND ONE FULL FLUSH. FLUSH VOLUMES WILL BE TESTED IN ACCORDANCE WITH ASME A 112.19.2 AND ASME A 112.19.14. 1 1
1 1
TABLE 5.303.6
STANDARDS FOR PLUMBING FIXTURES AND FIXTURE FITTINGS
WATER CLOSETS (TOILETS) - FLUSHOMETER
VALVE-TYPE SINGLE FLUSH, MAXIMUM FLUSH
VOLUME
ASME A 112.19.2/CSA B45.I - 1.28 GAL (4.8 L)
WATER CLOSETS (TOILETS) - FLUSHOMETER
VALVE-TYPE DUAL FLUSH, MAXIMUM FLUSH
VOLUME
ASME A 112.19.14 AND U.S. EPA
WATERSENSE TANK-TYPE HIGH EFFICIENCY
TOILET SPECIFICATION - 1.28 GAL (4.8 L)
URINALS, MAX FLUSH VOLUMEASME A 112.19.2/CSA B45.1 - 0.125 GAL (1.9 L) PUBLIC LAVATORY FAUCETS:
MAXIMUM FLOW RATE - 0.5 GPM (1.9 L/MIN.)ASME A 112.18.1/CSA B125.1 PUBLIC METERING SELF-CLOSING FAUCETS:
MAXIMUM WATER USE - 0.25 GAL (1.0 L) PER
METERING CYCLE
ASME A 112.18.1/CSA B 125.1
GENERAL NOTES
26INSULATION THICKNESS AND R-VALUES SHALL EXCEED THE REQUIREMENTS OF TITLE 24 BY AT LEAST 20 PERCENT OR NEXT LARGER STANDARD SIZE, WHICH EVER IS GREATER.
PIPE INSULATION SHALL BE NOT LESS THAN 1.0 INCH THICK, NOT INCLUDING THE MOISTURE BARRIER OR EXTERIOR JACKET THICKNESS.
27ALL GAS PRESSURE REGULATOR SHALL BE LOCATED AT GROUND LEVEL OR CLOSE TO
APPLIANCE AND LOCATIONS SHALL BE COORDINATED WITH THE ARCHITECT FOR APPROVAL. SIZE AND INSTALLATION SHALL BE AS PER MANUFACTURER'S RECOMMENDATIONS. NO MEDIUM PRESSURE GAS INSIDE THE BUILDING. 28NO GAS & WATER PIPE SHALL BE INSTALLED UNDER BUILDING SLAB. GAS & WATER PIPES SHALL RISE TIGHT AGAINST EXTERIOR WALL UP TO MIN. 18" AFF AND PENETRATE INTO BUILDING. PROVIDE SHUT-OFF VALVE AND REGULATOR ABOVE GRADE AT INCOMING GAS RISERS.
29CONTRACTOR SHALL CAREFULLY REVIEW THESE PLANS AND SPECIFICATIONS PRIOR TO BID. CONTRACTOR SHALL ALSO REVIEW PLANS AND SPECIFICATIONS OF OTHER
RELATED TRADES (INCLUDING MECHANICAL, CIVIL, STRUCTURAL, AND ELECTRICAL) PRIOR TO BID TO INSURE AN ACCURATE UNDERSTANDING OF EXACT SCOPE OF WORK.
ANY ITEMS REQUIRING DESCRIPTION CLARIFICATION SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT IN SUFFICIENT TIME TO BE INCORPORATED INTO THE BID. 30ALL PLUMBING SYSTEM COMPONENTS SHALL MEET OR EXCEED THE REQUIREMENTS OF C.B.C. (CALIFORNIA EDITION), CMC, CPC, NEC, NFPA, ASTM, ANSI, AND ALL LOCAL AND STATE CODE REQUIREMENTS.
31ALL PLUMBING EQUIPMENT LISTED IN (CCR) SECTION 113 OF THE 2019 CALIFORNIA CODE OF REGULATIONS, TITLE-24, PART 1, ENERGY EFFICIENCY STANDARDS MUST BE
CERTIFIED BY THE MANUFACTURER TO MEET OR EXCEED SPECIFICATIONS OR EFFICIENCIES ADOPTED BY THE CEC.
32ALL PIPING EXPOSED TO WEATHER SHALL BE METALLIC.
33ALL PIPING EXPOSED TO WEATHER SHALL BE METALLIC.
34ALL PIPES, FITTINGS AND FIXTURES USED TO CONVEY POTABLE WATER SHALL BE LEAD FREE IN COMPLIANCE WITH CALIFORNIA AB 1953.
35ALL INSULATING MATERIALS INSTALLED MUST BE CERTIFIED BY CALIFORNIA ENERGY COMMISSION TO MEET C.E.C. ENERGY EFFICIENCY STANDARDS (E.E.S.) SECTION 120.3 AND SECTION 1201.3.2.1.1 OF CMC (CALIFORNIA EDITION).
36ALL INSULATION INSTALLED SHALL MEET THE FLAME SPREAD AND SMOKE DENSITY REQUIREMENTS OF SECTION 719 OF THE 2019 CBC.
37CROSS CONNECTION PROTECTION SHALL BE PROVIDED AT ALL POTABLE WATER
SUPPLIED APPLIANCES AND EQUIPMENT (OTHER THAN THOSE LISTED IN INFORMATION BULLETIN 103).
38ALL HEATERS FOR DOMESTIC HOT WATER MUST BE CERTIFIED BY THE MANUFACTURER TO MEET THE SPECIFICATIONS OR EFFICIENCIES AS ADOPTED BY THE CEC. IN ACCORDANCE WITH SECTION 110.1 OF THE CCR AND ENERGY EFFICIENCY STANDARDS
RESIDENTIAL NON-RESIDENTIAL
39A WATER HEATER PRESSURE AND TEMPERATURE RELIEF DRAIN THAT TERMINATES OUTSIDE THE BUILDING SHALL COMPLY WITH SECTION 608.5 OF CPC. 40WATER HEATER SHALL BE ANCHORED OR STRAPPED TO RESIST HORIZONTAL DISPLACEMENT DUE TO EARTHQUAKE MOTION PER SECTION 508.2 OF CPC. 41WATER HEATER SHALL COMPLY WITH SECTION 608.3 OF CPC, FOR THERMAL EXPANSION REQUIREMENTS.
42KITCHEN FAUCETS AND WASH FOUNTAINS SHALL BE 1.8 GPM MAXIMUM. 43DISHWASHERS AND WASHING MACHINES SHALL MEET US EPA WATER SENSE LABELING REQUIREMENT.
44ROUTING AND TERMINATION OF FLUE AND COMBUSTION AIR INTAKE FOR WATER HEATER SHALL COMPLY WITH CHAPTER 5, CPC 2019 WITH MANUFACTURER'S SPECIFICATIONS. 45A SLOPE OF NOT LESS THAN 1/8 INCH PER FOOT OR 1.0 % IS PROVIDED FOR DRAINAGE PIPING 4 INCHES OR LARGER ONLY WHERE IT IS IMPRACTICAL DUE TO DEPTH OF THE
STREET SEWER, TO THE STRUCTURAL FEATURES, OR TO THE ARRANGEMENT OF A BUILDING OR STRUCTURE TO OBTAIN A SLOPE OF 1/4 INCH PER FOOT OR 2 % AND THAT IS SUBJECT TO THE CITY OF SAN DIEGO PLUMBING FIELD INSPECTORS APPROVAL. 46FLOOR DRAINS OR SIMILAR TRAPS DIRECTLY CONNECTED TO THE DRAINAGE SYSTEM
AND SUBJECT TO INFREQUENT USE SHALL BE PROVIDED WITH AN AUTOMATIC MEANS OF
MAINTAINING THEIR WATER SEALS
47BUILDING DRAIN AND VENT PIPING MATERIALS SHALL COMPLY WITH SECTIONS 701.0 AND 903.0 OF THE CALIFORNIA PLUMBING CODE.
48ALL SANITARY SYSTEM MATERIALS SHALL BE LISTED BY AN APPROVED LISTING AGENCY. 49EACH VENT SHALL RISE VERTICALLY TO A POINT NOT LESS THAN SIX (6) INCHES ABOVE
THE FLOOD LEVEL RIM OF THE FIXTURE SERVED BEFORE OFFSETTING HORIZONTALLY OR BEFORE BEING CONNECTED TO ANY OTHER VENT.
50PLUMBING FIXTURES AND FITTINGS SHALL COMPLY WITH ALL THE REQUIREMENTS IN SECTION 4.303 IN THE CALIFORNIA GREEN BUILDING CODE.
51PIPE INSULATION: INSULATION OF DOMESTIC HOT WATER PIPING SHALL BE IN ACCORDANCE WITH SECTION 609.11.1 AND SECTION 609.2 CPC 2019. 609.11.1 INSULATION REQUIREMENTS. DOMESTIC WATER PIPING SHALL BE INSULATED 609.12.1 PIPE INSULATION WALL THICKNESS. HOT WATER PIPING INSULATION SHALL HAVE
A MINIMUM WALL THICKNESS OF NOT LESS THAN THE DIAMETER OF THE PIPE FOR A PIPE UP TO 2 INCHES IN DIAMETER. INSULATION WALL THICKNESS SHALL BE NOT LESS THAN 2 INCHES FOR A PIPE OF 2 INCHES OR MORE IN DIAMETER
FLORA TERRA
1 7 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
P0.2
PLUMBING
FIXTURES & CAL
REVISIONS:
COLD WATER PIPE SIZINGHOT WATER PIPE SIZING
FIXTURE DATA AND WATER CALCULATION
ITEMDESCRIPTIONNO. OF FIXT WFU 'S DFU 'S CW HW SEWER
WC-1 WATER CLOSET (TANK TYPE)12.5 4.0 2.514.0
LV-1LAVATORY11.0 2.0 1.0 0.8 2.0
SK-1 HAND SINK12.0 2.0 2.0 1.5 2.0
TOTAL WFU'S, DFU'S#05.53.3 8.0
MAIN DOMESTIC WATER SUPPLY SIZING BASE ON LATEST
EDITION CPC 2016 TABLE A 103.1, CHART A 105.1 (1)
COLD WATER FIXTURES UNITS = 36 GPM
HOT WATER FIXTURES UNITS == 11 GPM
EXISTING FRICTION LOSSES
WATER PRESSURE AT THE STREET. FIELD VERIFY PRIOR TO START OF WORK.165PSI LENGTH OF DOMESTIC WATER SYSTEM TO THE FURTHEST RUN.200FT WATER METER8PSI
2" BACKFLOW PREVENTER15PSI
2" PRESSURE REGULATOR15PSI
TOTAL LOSSES38PSI
PRESSURE INSIDE THE BUILDING65PSI
STATIC HEIGHT0FT
RESIDUAL PRESSURE:25PSI
PRESSURE AVAILABLE FOR FRICTION LOSS40.00PSI
ALLOWABLE FRICTION LOSS PER HUNDRED FEET20.0PSI
PIPE MATERIAL SCHEDULE
DOMESTIC WATER PIPING ABOVE GRADE
TYPE "L" COPPER TUBING, HARD DRAWN CONFORMING TO ASTM B 88, WITH WROUGHT COPPER SOLDER SWEAT FITTINGS CONFORMING TO ASTM B 16.22. PROVIDE LABELING AND INSULATION.
DOMESTIC WATER PIPING UNDERGROUND OR BELOW SLAB:
TYPE "K" HARD COPPER TUBING ANNEALED, WITH NO FITTINGS CONFORMING TO ASTM B 88.
WASTE AND VENT PIPING:
ABOVE GRADE - PVC SCHEDULE 40 WITH PVC SCHEDULE 40 FITTINGS.
BELOW GRADE - PVC SCHEDULE 40 WITH PVC SCHEDULE 40 FITTINGS.
PLUMBING FIXTURE SCHEDULE
ITEM WASTE TRAP VENT CW HW MOUNTDESCRIPTION
3"INTEGRAL 2"12" -- FLOOR
WATER CLOSET (FLUSH TANK): 1.0 GPF, ELONGATED
BOWL, 12" ROUGH-IN. PROVIDE WITH MAXIMUM
PERFORMANCE (MaP) THRESHOLD OF NO LESS THAN
500 GRAMS. KOHLER WELLWORTH OR EQUAL. ADA
COMPLIANCE
2" 2" 2"12"12" COUNTER
LAVATORY: COUNTER MOUNTED WITH 4" ON
CENTER. PROVIDE FAUCET WITH .5 GPM. WATER
SENSE APPROVED. ADA COMPLIACE
2" 2" 2"3/4" 3/4"FLOOR
BATH TUB: PER OWNER SPECS. ALL GROUND
LEVEL BATHTUB CONTROLS SHALL BE OFFSET ON
WALL. SEE ARCHITECTURAL FOR EXACT
LOCATION. PROVIDE FITTINGS TO COMPLY WITH
GREEN BUILDING CODE. 2.0 GPM
2" 2" 1 12"12"12" COUNTER
KITCHEN SINK: DOUBLE COMPARTMENT 16 GAUGE
TYPE 304, 18-8 STAINLESS STEEL. SEAMLESS
DIE-DRAWN CONSTRUCTION. SELF RIMMING TOP
MOUNT GRIP-RIM PLUS WITH STAINLESS STEEL
MOUNTING CHANNELS. PROVIDE FAUCET 1.5 GPM.
PROVIDE 1/2HP IN-SINKEARATOR GARBAGE
DISPOSER. ELECTRICAL 120 VOLTS, 60HZ, 1725
RPM, 9.5 AMPS. ADA COMPLIANCE
2" 2" 2" -- -- FLOOR
FLOOR DRAIN: D.C.C.I. BODY WITH BOTTOM
OUTLET, COMBINATION INVERTIBLE MEMBRANE
CLAMP AND ADJUSTABLE COLLAR WITH TYPE "B"
POLISHED NICKLE BRONZE STRAINER. PROVIDE
TRAP PRIMER CONNECTION AND BACKWATER
VALVE TO PREVENT REVERSIBLE SEWER
SPILLAGE.
-- -- --12"12" WALL
SHOWER: S-3501-CYL-B-TRM
SHOWER TRIM WITH INTEGRAL VOLUME
CONTROL, PROVIDE TEMPTROL PRESSURE
BALANCING SHOWER VALVE
-- -- --34" -- WALLHOSE BIBB: "PIER" 400-LF SERIES 34'' INLET WITH VACUUM BREAKER.
WC-1
LV-1
BTH-1
SK-1
FD-1
SHR-1
HB-1
FLORA TERRA
1 7 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
P0.3
PLUMBING
WATER HEATER
SPECIFICATIONS
REVISIONS:
BASE FLASHING BY
GEN'L. CONT'R.
CRIMP EDGE OVER PIPE IN A NEAT
MANNER TO PREVENT REDUCTION OF
EFFECTIVE VENT AREA.
REFER TO ARCH.
DWGS. FOR ROOF
CONSTRUCTION.
REFER TO PLANS FOR SIZE
AND LOCATION
SHEET COPPER OR LEAD
COUNTER FLASHING BY
PLBG. CONT'R. (TO MATCH
MATERIAL OF BASE
FLASHING).
CLEANOUT ACCESS COVER (FCO)
FINISHED FLOOR OR PAVED AREA
PROVIDE 18"X18"X6" CONCRETE PAD
WHEN FINISHING AT EXTERIOR OF
BUILDING.
C.I. CLEANOUT
FERRULE & PLUG
SEWER
9 INCHES
FLOOR LINE
BOTTOM PLATE
WALL
WASTE PIPE.
PLUGGED TEE WITH
CLEANOUT.
MAY EXTEND AS A
WASTE OR A VENT
LINE.
WALL COVER
AND SCREW.
(FIRE RATED
WHERE REQ'D)
BALANCE OF PIPING
SAME AS CLEANOUT
TO GRADE.
1 SCALE: NONE
FLOOR CLEAN OUT DETAIL2 SCALE: NONE
WALL CLEAN OUT DETAIL3 SCALE: NONE
VENT THRU OUT DETAIL
WH
1 FLORA TERRA
1 7 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714.752.4263 | f ax 949.760.3931
1 SCALE: 3/8"=1'-0"
PLUMBING FLOOR PLAN WASTE & VENT2 SCALE: 3/8"=1'-0"
PLUMBING FLOOR PLAN WATER
SK-1A
WC-1ALV-1A
2"WCO
3''WCO
P.O.C. VERIFY
EXACT LOCATION
3"WCO
(E) 3/4" WATER
METER
3/4"
CW
3/4"
CW
1/2"
CW
1/2"CW
1/2"CW
WH1
WH1
P2.1
PLUMBING FLOOR
PLAN WASTE,
VENT & WATER
GENERAL NOTES
“ ”
# #
TYP
#
#
SHT
ELECTRICAL SHEET INDEX
RACEWAYS AND BOXES GENERAL NOTES
” ”
BRANCH CIRCUIT SYMBOLS
RACEWAYS AND BOXES GENERAL NOTES
APPLICABLE CODES
ABBREVIATIONS
E-1.0
ELECTRICAL NOTES,
APPLICABLE CODES,
AND DRAWING
INDEX
FLORA TERRA
1 7 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714 .75 2.42 63 | f ax 9 49.7 60.3 931
ELECTRICAL SYMBOLS
PP
OS
WS
WD
LCP
D4
PS
OR
J
J
S
D
F
DW-100
LINE VOLTAGE 1-ZONE SWITCH
WITH INTEGRATED
OCCUPANCY SENSOR.
DW-200
LINE VOLTAGE 2-ZONES SWITCH WITH
INTEGRATED OCCUPANCY SENSOR.
CONFIRM TYPE AND
QTY PER PLANS
CONFIRM TYPE AND
QTY PER PLANS
COMBINATION OCC/SW WIRING
PL
OS
0-10V DIMMER-SWITCH & POWER-PACK & OCC. SENSOR WIRING
OS
PP
E-1.1
PL
PP ELECTRICAL SYMBOLS
AND LIGHTING
CONTROL DIAGRAMS
WS
WS
FLORA TERRA
1 7 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714 .75 2.42 63 | f ax 9 49.7 60.3 931
LCP
LCP TYPICAL WIRING
FIXTURE SCHEDULE
TYPE
LIGHTING FIXTURE SCHEDULE GENERAL NOTES:
LIGHTING FIXTURE SCHEDULE GENERAL NOTES:
1 2
T22 1
T14 1
XE
XB
2 P8 1
3 2
S6 1
3 THE INFORMATION CONTAINED IN THIS
SET OF CONSTRUCTION DOCUMENTS IS
PROPRIETARY BY NATURE. ANY USE
OR DISCLOSURE OTHER THAN THAT
WHICH RELATES TO MOTIVE AND
ASSOCIATES IS STRICTLY PROHIBITED.
DRAWING DATES
1226 4TH STREET
SANTA ROSA, CALIFORNIA 95404
PROJECT NAME
TENANT
LANDLORD
APPROVALS
SHEET TITLE
CITY SUBMISSION SET02/15/22
FLORA TERRA
1 7 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 7 14.7 52. 4263 | f ax 949. 760. 393 1
E-1.2
LIGHTING FIXTURE
SCHEDULE
P3 1
WP 1
3 101
DISPENSARY
102
STORAGE
103
HALLWAY
105
TOILET
104
BREAK ROOM
WS
OS
DPP
OS
S
PP D
D D
P8
P3
T22T22
T22
S6
T14
1 2
3 33
4 4
4 4
5 S
6 6
6 6WP
6WP
6 LCPOR7
8 8
8 8
D
3 XB6
XB6
XB6
XB6
S S
3 D
LIGHTING PLAN1
GENERAL NOTES:
KEYNOTES NOTES:
1 2
3 4
5 6
7 8
E-2.0
LIGHTING PLAN
FLORA TERRA
1 7 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 7 14.7 52. 4263 | f ax 949. 760. 393 1
J
9 101
DISPENSARY
102
STORAGE
103
HALLWAY
105
TOILET
104
BREAK ROOM
S
PL
JJ
1 2
3 4
55 6 7WH
1 WH
1 SM
SM
EF
1 (E) RTU
1 F
8 8
12 SM
11 T
10 SM
SM
POWER PLAN1
KEYNOTES:
1 2
3 GENERAL NOTES:
4 5
6 7
8 9
10 11
12 E-3.0
POWER PLAN
FLORA TERRA
1 7 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 7 14.7 52. 4263 | f ax 949. 760. 393 1
#
FLORA TERRA
1 7 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 7 14.7 52. 4263 | f ax 949. 760. 393 1
E-4.0
SINGLE LINE
DIAGRAM AND
PANEL SCHEDULES
PANEL SCHEDULE TELECOMMUNICATION GROUNDING SYSTEM
KEYNOTES:
1 2
3 4
1 2
2 2
2 2
2 3
3 2
4 4
4 4
4 4
PANEL SCHEDULE KEYNOTES:
1 1
SINGLE LINE DIAGRAM
GENERAL NOTES:
FLORA TERRA
1 7 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714. 752 .426 3 | f ax 94 9.76 0.3 931
E-5.0
TITLE 24
COMPLIANCE
FORMS - INDOOR
FLORA TERRA
1 7 2 6 0 N e w h o p e S t r e e t
F o u n t a i n V a l l e y , C a l i f o r n i a 9 2 7 0 8 tel 714. 752. 4263 | f ax 949 .760 .393 1