Datacenter SFO1 - Silicon Valley Data Center
Bill To
City of Sunnyvale
Attn. Mark Witt
456 W. Olive Avenue
Sunnyvale, CA 94086 US
Initial Term (Months): 60
Wil Guitarte
Michael MurrayAccount Executive:
Contact Email: [email protected]
Primary Contact:
04/01/2025Billing Start Date:
City of Sunnyvale/Space and Power Renewal/SFO_v4 12-10-24 Summary:
Net ChangeNew
Quantity
Added
Quantity
MonthlyDescription
One Time
Charge
Cost per Unit
SERVICE CHANGES
0 sqft - Data Center Space - Private Cage "All-In" kW
Power Model - SFO1.F1.DC01.C0102 (Asset: 313580)
250 $0.00$0.00
Private Cage on raised floor data center. Cabinets over 1,200lbs may require additional support and spacing and may result in additional NRC.
-8 $385.00 $21,175.00 55 Provisioned A&B PDU kW capacity - All-In Model (Asset:
313581)
$3,299.10
The all-in rate set forth herein is subject to increase if the then-current Utility Rate is at least ten percent (10%) more than the Utility Rate as of the date this Order Form is first signed by both parties ("Initial Utility Rate"). The amount of any such rate increase shall be proportional to the
difference between the Utility Rate for the power provided hereunder and any increase will continue only for so long as DataBank’s power usage rates exceed 110% of the
Initial Utility Rate. "Utility Rate" is the average cost per kilowatt hour payable to DataBank's utility provider at the data center referenced above for the previous twelve (12) month period.
DataBank will provision specified kW amount from data
center PDU / PDU panel / RPP to customer environment.
If Customer purchases dedicated PDU / PDU panel / RPP,
Customer may connect as many circuits as contracted
PDU / PDU panel / RPP size will support. Customer is
responsible for monitoring load across all circuits
connected, and overloading of PDU / PDU panel / RPP
breaker by Customer is not eligible for SLA credit.
Otherwise, DataBank will provide specified amount of kW capacity to be shared by customer circuits on shared PDU / PDU panel / RPP. Connected capacity cannot exceed
130% of commitment.
The total draw of all primary (A-side) connected circuits should not exceed specified kW of draw.
The committed kW for this solution is 55
The "Initial Utility Rate" is $0.1620.
DataBank will bill a burst charge of 100% of the billable kW rate for every kW consumed over the billable kW. The
charge is calculated as: (consumed kW - billable kW) x
(billable kW rate x 100% burst rate)
Original Remarks:
The all-in rate set forth herein is subject to increase if DataBank’s power usage rates payable to its third party power provider are 10% or more greater than DataBank’s
power usage rates as of the date of this Order Form. The amount of any such rate increase shall be proportional to the increases in DataBank’s power rates and the increase will continue only for so long as DataBank’s applicable power usage rates are 10% or more greater than the power usage rates as of the date of this Order Form.
DataBank will provision specified kW amount from data
center PDU / PDU panel / RPP to customer environment.
Attachment 1
Renewal 112976
02/08/2025
2 of 5
12/10/2024
Expires
Page
PrintDate
Datacenter SFO1 - Silicon Valley Data Center
If Customer purchases dedicated PDU / PDU panel / RPP,
Customer may connect as many circuits as contracted
PDU / PDU panel / RPP size will support. Customer is
responsible for monitoring load across all circuits
connected, and overloading of PDU / PDU panel / RPP
breaker by Customer is not eligible for SLA credit.
Otherwise, DataBank will provide specified amount of kW capacity to be shared by customer circuits on shared PDU / PDU panel / RPP. Connected capacity cannot exceed
130% of commitment.
The total draw of all primary (A-side) connected circuits should not exceed specified kW of draw.
The committed kW for this solution is 63 kW.
DataBank will bill a burst charge of 100% of the billable kW rate for every kW consumed over the billable kW rate. The charge is calculated as: (consumed kW - billable kW) x
(billable kW rate x 100% burst rate).
Quantity was decreased from 63.00 to 55.00.
Monthly Total was increased from 17,875.90 to 21,175.00. 0 $0.00 63 linear ft - Cage/Suite Wall (Asset: 313582) $0.00 0 Cabinet position for Private Cage/Suite -
SFO1.F1.DC01.C0102.04.A1 (Asset: 313583)
1 $0.00$0.00
0 $0.00 1 Secure Cabinet Enclosure - 42U (Asset: 313584) $0.00 Secure Cabinet Enclosure - 42U Does not include power or rack PDU, customer may provide rack PDU or order from
DataBank. Appropriate power circuit should be ordered for customer requirements.
0 $0.00 1 Power : AC amp : 30 amp 208V A Side (Asset: 313585) $0.00 208 Volt / 30 Amp AC power for Primary circuit (A side).
Draw from "A" or combined "A & B" circuit will not exceed 80% of breaker.
Plug Type: L6-30 Twist Lock
0 $0.00 1 Power : AC amp : 30 amp 208V B Side (Asset: 313586) $0.00 208 Volt / 30 Amp AC power for Secondary circuit (B side).
Draw from "B" or combined "A & B" circuit will not exceed 80% of breaker.
Plug Type: L6-30 Twist Lock
0 Cabinet position for Private Cage/Suite -
SFO1.F1.DC01.C0102.04.A2 (Asset: 313587)
1 $0.00$0.00
0 $0.00 1 Secure Cabinet Enclosure - 42U (Asset: 313588) $0.00 Secure Cabinet Enclosure - 42U Does not include power or rack PDU, customer may provide rack PDU or order from
DataBank. Appropriate power circuit should be ordered for customer requirements.
0 $0.00 1 Power : AC amp : 30 amp 208V A Side (Asset: 313589) $0.00 208 Volt / 30 Amp AC power for Primary circuit (A side).
Draw from "A" or combined "A & B" circuit will not exceed 80% of breaker.
Plug Type: L6-30 Twist Lock
0 $0.00 1 Power : AC amp : 30 amp 208V B Side (Asset: 313590) $0.00 208 Volt / 30 Amp AC power for Secondary circuit (B side).
Draw from "B" or combined "A & B" circuit will not exceed 80% of breaker.
Plug Type: L6-30 Twist Lock
0 Cabinet position for Private Cage/Suite -
SFO1.F1.DC01.C0102.04.A3 (Asset: 313591)
1 $0.00$0.00
0 $0.00 1 Secure Cabinet Enclosure - 42U (Asset: 313592) $0.00 Secure Cabinet Enclosure - 42U Does not include power or rack PDU, customer may provide rack PDU or order from
DataBank. Appropriate power circuit should be ordered for customer requirements.
0 $0.00 1 Power : AC amp : 30 amp 208V A Side (Asset: 313593) $0.00 208 Volt / 30 Amp AC power for Primary circuit (A side).
Draw from "A" or combined "A & B" circuit will not exceed 80% of breaker.
Plug Type: L6-30 Twist Lock
0 $0.00 1 Power : AC amp : 30 amp 208V B Side (Asset: 313594) $0.00 208 Volt / 30 Amp AC power for Secondary circuit (B side).
Draw from "B" or combined "A & B" circuit will not exceed 80% of breaker.
Attachment 1
Renewal 112976
02/08/2025
3 of 5
12/10/2024
Expires
Page
PrintDate
Datacenter SFO1 - Silicon Valley Data Center
Plug Type: L6-30 Twist Lock
0 Cabinet position for Private Cage/Suite -
SFO1.F1.DC01.C0102.04.A4 (Asset: 313595)
1 $0.00$0.00
0 $0.00 1 Secure Cabinet Enclosure - 42U (Asset: 313596) $0.00 Secure Cabinet Enclosure - 42U Does not include power or rack PDU, customer may provide rack PDU or order from
DataBank. Appropriate power circuit should be ordered for customer requirements.
0 $0.00 1 Power : AC amp : 30 amp 208V A Side (Asset: 313597) $0.00 208 Volt / 30 Amp AC power for Primary circuit (A side).
Draw from "A" or combined "A & B" circuit will not exceed 80% of breaker.
Plug Type: L6-30 Twist Lock
0 $0.00 1 Power : AC amp : 30 amp 208V B Side (Asset: 313598) $0.00 208 Volt / 30 Amp AC power for Secondary circuit (B side).
Draw from "B" or combined "A & B" circuit will not exceed 80% of breaker.
Plug Type: L6-30 Twist Lock
0 Cabinet position for Private Cage/Suite -
SFO1.F1.DC01.C0102.04.A5 (Asset: 313599)
1 $0.00$0.00
0 $0.00 1 Secure Cabinet Enclosure - 42U (Asset: 313600) $0.00 Secure Cabinet Enclosure - 42U Does not include power or rack PDU, customer may provide rack PDU or order from
DataBank. Appropriate power circuit should be ordered for customer requirements.
0 $0.00 1 Power : AC amp : 30 amp 208V A Side (Asset: 313601) $0.00 208 Volt / 30 Amp AC power for Primary circuit (A side).
Draw from "A" or combined "A & B" circuit will not exceed 80% of breaker.
Plug Type: L6-30 Twist Lock
0 $0.00 1 Power : AC amp : 30 amp 208V B Side (Asset: 313602) $0.00 208 Volt / 30 Amp AC power for Secondary circuit (B side).
Draw from "B" or combined "A & B" circuit will not exceed 80% of breaker.
Plug Type: L6-30 Twist Lock
0 Cabinet position for Private Cage/Suite -
SFO1.F1.DC01.C0102.04.B1 (Asset: 313603)
1 $0.00$0.00
0 $0.00 1 Secure Cabinet Enclosure - 42U (Asset: 313604) $0.00 Secure Cabinet Enclosure - 42U Does not include power or rack PDU, customer may provide rack PDU or order from
DataBank. Appropriate power circuit should be ordered for customer requirements.
0 $0.00 1 Power : AC amp : 30 amp 208V A Side (Asset: 313605) $0.00 208 Volt / 30 Amp AC power for Primary circuit (A side).
Draw from "A" or combined "A & B" circuit will not exceed 80% of breaker.
Plug Type: L6-30 Twist Lock
0 $0.00 1 Power : AC amp : 30 amp 208V B Side (Asset: 313606) $0.00 208 Volt / 30 Amp AC power for Secondary circuit (B side).
Draw from "B" or combined "A & B" circuit will not exceed 80% of breaker.
Plug Type: L6-30 Twist Lock
0 $0.00 1 Power : AC amp : 30 amp 208V A Side (Asset: 588918) $0.00 0 $0.00 1 Power : AC amp : 30 amp 208V B Side (Asset: 588919) $0.00 0 Cabinet position for Private Cage/Suite -
SFO1.F1.DC01.C0102.04.B2 (Asset: 313607)
1 $0.00$0.00
0 $0.00 1 Secure Cabinet Enclosure - 42U (Asset: 313608) $0.00 Secure Cabinet Enclosure - 42U Does not include power or rack PDU, customer may provide rack PDU or order from
DataBank. Appropriate power circuit should be ordered for customer requirements.
0 $0.00 1 Power : AC amp : 30 amp 208V A Side (Asset: 313609) $0.00 208 Volt / 30 Amp AC power for Primary circuit (A side).
Draw from "A" or combined "A & B" circuit will not exceed 80% of breaker.
Plug Type: L6-30 Twist Lock
0 $0.00 1 Power : AC amp : 30 amp 208V B Side (Asset: 313610) $0.00 208 Volt / 30 Amp AC power for Secondary circuit (B side).
Draw from "B" or combined "A & B" circuit will not exceed 80% of breaker.
Attachment 1
Renewal 112976
02/08/2025
4 of 5
12/10/2024
Expires
Page
PrintDate
Datacenter SFO1 - Silicon Valley Data Center
Plug Type: L6-30 Twist Lock
0 Cabinet position for Private Cage/Suite -
SFO1.F1.DC01.C0102.04.B3 (Asset: 313611)
1 $0.00$0.00
0 $0.00 1 Secure Cabinet Enclosure - 42U (Asset: 313612) $0.00 Secure Cabinet Enclosure - 42U Does not include power or rack PDU, customer may provide rack PDU or order from
DataBank. Appropriate power circuit should be ordered for customer requirements.
0 $0.00 1 Power : AC amp : 30 amp 208V A Side (Asset: 313613) $0.00 208 Volt / 30 Amp AC power for Primary circuit (A side).
Draw from "A" or combined "A & B" circuit will not exceed 80% of breaker.
Plug Type: L6-30 Twist Lock
0 $0.00 1 Power : AC amp : 30 amp 208V B Side (Asset: 313614) $0.00 208 Volt / 30 Amp AC power for Secondary circuit (B side).
Draw from "B" or combined "A & B" circuit will not exceed 80% of breaker.
Plug Type: L6-30 Twist Lock
0 Cabinet position for Private Cage/Suite -
SFO1.F1.DC01.C0102.04.B4 (Asset: 313615)
1 $0.00$0.00
0 $0.00 1 Secure Cabinet Enclosure - 42U (Asset: 313616) $0.00 Secure Cabinet Enclosure - 42U Does not include power or rack PDU, customer may provide rack PDU or order from
DataBank. Appropriate power circuit should be ordered for customer requirements.
0 $0.00 1 Power : AC amp : 30 amp 208V A Side (Asset: 313617) $0.00 208 Volt / 30 Amp AC power for Primary circuit (A side).
Draw from "A" or combined "A & B" circuit will not exceed 80% of breaker.
Plug Type: L6-30 Twist Lock
0 $0.00 1 Power : AC amp : 30 amp 208V B Side (Asset: 313618) $0.00 208 Volt / 30 Amp AC power for Secondary circuit (B side).
Draw from "B" or combined "A & B" circuit will not exceed 80% of breaker.
Plug Type: L6-30 Twist Lock
0 Cabinet position for Private Cage/Suite -
SFO1.F1.DC01.C0102.04.B5 (Asset: 588920)
1 $0.00$0.00
0 $0.00 1 Power : AC amp : 30 amp 208V A Side (Asset: 588921) $0.00 0 $0.00 1 Power : AC amp : 30 amp 208V B Side (Asset: 588922) $0.00 Subtotal $21,175.00$3,299.10
Service Changes:
Net Changes:
$3,299.10
$3,299.10
Renewal Net Changes:
Monthly Recurring Charges:
Non-Recurring Charges:
$21,175.00
$0.00
Renewal Summary Totals:
Click Here to order online
Attachment 1
Renewal 112976
02/08/2025
5 of 5
12/10/2024
Expires
Page
PrintDate
Datacenter SFO1 - Silicon Valley Data Center
Customer Signature DataBank Holdings Ltd. Signature
TitlePrint NamePrint Name
Title
Date Date
1. The Master Service Agreement (“MSA”) between DataBank Holdings Ltd. or its applicable “Local Entity” (collectively “DataBank”) is hereby incorporated into this Order Form and made a part thereof, and Customer and DataBank agree to be bound as if such MSA were fully set forth herein. DataBank may assign or delegate its performance under this Order Form, including through the assignment or delegation to a “Local Entity”. Such Local Entity will perform the Services in accordance with, and subject to, the terms and conditions of this Order Form and the MSA. DataBank may act as agent for such Local Entity, and in such capacity will invoice Customer for Services rendered, manage Service delivery hereunder and may exercise and enforce other rights on behalf of such Local Entity. “Local Entity” means a partnership, corporation, or other legal entity that now or in the future, directly or indirectly controls, is controlled with or by or is under common control with DataBank and such legal entity is authorized to provide the applicable Services. For purposes of the foregoing, “control” means, with respect to: (a) a corporation, the ownership, directly or indirectly, of fifty percent (50%) or more of the voting power to elect directors thereof and (b) any other entity, fifty percent (50%) or more ownership interest in said entity, of the power to direct the management of such entity.
2. Unless a different annual increase is specified in the MSA, the prices listed in this Order Form will be increased by three percent (3%) per annum during the initial term and any renewal term(s).
3. Unless otherwise stated elsewhere in the MSA or this Order Form, upon the expiration of the initial term of this Order Form, the term of this Order Form will continue automatically for additional terms equal to the initial term (each a “Renewal Term”) unless Customer or DataBank notifies the other party in writing at least ninety (90) days prior to the end of the then-current term, that it has elected to terminate this Order Form, in which case this Order Form shall terminate at the end of such term.
4. Customer acknowledges that DataBank may increase power charges at a rate proportional to utility rate increases during the Initial Term or any Renewal Term.
5. In support of DataBank meeting the target Service Commencement Date provided by DataBank, Customer specifically acknowledges that Customer is responsible for performing its obligations specified in this Order Form and the MSA (“Customer Requirements”). Customer acknowledges that any delay in Customer providing such Customer Requirements may delay DataBank from completing work at any location. In the event that Customer has not provided the Customer Requirements in time to allow DataBank to complete work at any location on or before the target Service Commencement Date, then DataBank may continue with any remaining acceptance procedures within DataBank’s control and deem the Services delivered and accepted upon notice to Customer. The date of such notice to Customer shall be the Service Commencement Date.
Attachment 1