Cities Index.
WRF - Facility Plan Update - Carollo Presentation 2_20_2024

Visalia City Council
February 20, 2024

Document
WRF - Facility Plan Update - Carollo Presentation 2_20_2024
Meeting
February 20, 2024
Body
Visalia City Council
Original file
10.1 MB
Text extracted from the city's file for reading and search. Open the original on visalia.legistar1.com. That file is the official record.

Visalia Water
Reclamation
Facility
Facility Plan Update
Council Presentation
City of Visalia
2/20/2024

Background and Purpose
CAROLLO / 3
updatefooter0323.pptx/3updatefooter0323.pptx/3
WRF Overview

CAROLLO / 4
updatefooter0323.pptx/4updatefooter0323.pptx/4
T reatment Photos

CAROLLO / 5
updatefooter0323.pptx/5updatefooter0323.pptx/5
Project Background and Severity
• The WRF was upgraded in 2017 due to
increased regulations
• Improvements were made for a rated capacity
of 22 mgd, however to save costs some
improvements were not implemented leaving
the total design capacity at 18 mgd.
• In recent years, increased industrial loads along
with water conservation efforts have increased
influent wastewater concentrations and as a
result put increased strains on the facility.
• This study is an effort to update current
treatment process capacities using a biological
process model.

T reatment Process
Performance
CAROLLO / 7
updatefooter0323.pptx/7updatefooter0323.pptx/7
Solids Handling Facilities are Struggling
• Digesters are operating at very low HRTs and
are currently being overloaded during peak
loading periods
• PS and TWAS pumping is limited to 2-3%,
which exacerbates HRT limitation
• Digesters are overloaded with Grit causing
reduced volume (est 20% by volume filled)
• City does not have sufficient redundancy with
dewatering equipment due to no standby
dewatering screw press
CAROLLO / 8
updatefooter0323.pptx/8updatefooter0323.pptx/8
Historical Influent Data

CAROLLO / 9
updatefooter0323.pptx/9updatefooter0323.pptx/9
Biological Oxygen Demand and T otal
Suspended Solids Loadings

CAROLLO / 10
updatefooter0323.pptx/10updatefooter0323.pptx/10
Capacity/Firm Capacity Analysis

CAROLLO / 11
updatefooter0323.pptx/11updatefooter0323.pptx/11
Process Area Capacity

CAROLLO / 12
updatefooter0323.pptx/12updatefooter0323.pptx/12
Sludge Flows & Dewatering Capacity
Rated Screw Press Capacity (x1) – 158,400 gpd
Rated Screw Press Capacity (x2) – 316,800 gpd
CAROLLO / 13
updatefooter0323.pptx/13updatefooter0323.pptx/13
Impact of higher feed concentration (4.5%) on Digester SRT Minimum recommended
HRT of 15 days
Condition Assessment
CAROLLO / 15
updatefooter0323.pptx/15updatefooter0323.pptx/15
Condition Assessment Findings
• In general the equipment at the WRF is in good condition • There were significant upgrades in the last improvement project and all of this equipment is in good condition
• The following areas need some attention:
»Headworks
»Digesters
»Sludge Drying beds
»Misc. piping/pumps/valves
CAROLLO / 16
updatefooter0323.pptx/16updatefooter0323.pptx/16
Site Photos

Environmental Opportunities
CAROLLO / 18
updatefooter0323.pptx/18updatefooter0323.pptx/18
Environmental Opportunities
• Engine Generators
• Microturbines
• Gas Turbines
• Fuel Cells
• RNG to Pipeline Injection
• R-CNG to Vehicle Fuel

Near-T erm Improvements
CAROLLO / 20
updatefooter0323.pptx/20updatefooter0323.pptx/20
Near-term capacity related projects
•Now:
»Replace PS and TWAS pumps to allow
thickening of the sludge more
−Goal: 3% PS and 6% TWAS
»Add one screw press for firm
capacity/redundancy
»Add one digester with same capacity
as Digester No. 8
»Add additional UV Bank to provide
firm capacity/redundancy
Summary and
Recommendations
CAROLLO / 22
updatefooter0323.pptx/22updatefooter0323.pptx/22
Immediate Recommendations for Digesters
• Place Dig No. 4 back in service (waiting on piping)
• Continue tracking digester health parameters and develop response plan for early signs of failure
• Clean/de-grit digesters that have not been cleaned recently (i.e. last 2-4 years)
• PS and TWAS pumping modifications and/or replace discharge piping • Re-purpose Dig #8 as a primary digester (Currently used as 70% storage)
• Additional digester volume likely needed to accommodate future growth to buildout
CAROLLO / 23
updatefooter0323.pptx/23updatefooter0323.pptx/23
Solids Handling Improvements

CAROLLO / 24
updatefooter0323.pptx/24updatefooter0323.pptx/24
TWAS Pumps
•Now:
»Replace PS and TWAS pumps to allow
thickening of the sludge more
−Goal: 3% PS and 6% TWAS
»Add two screw presses
»Add three digesters with same
capacity as Digester No. 8

CAROLLO / 25
updatefooter0323.pptx/25updatefooter0323.pptx/25
TWAS Pump Station Upgrades

CAROLLO / 26
updatefooter0323.pptx/26updatefooter0323.pptx/26
Digester Upgrades

CAROLLO / 27
updatefooter0323.pptx/27updatefooter0323.pptx/27
Digester Upgrades

CAROLLO / 28
updatefooter0323.pptx/28updatefooter0323.pptx/28
Near T erm Dewatering Recommendations
• Additional dewatering unit needed to provide
redundancy/standby
• Provide additional drying beds and sludge storage if
dewatering maintenance or down time is experienced
CAROLLO / 29
updatefooter0323.pptx/29updatefooter0323.pptx/29
Dewatering Unit
• Add photo and potential layout

CAROLLO / 30
updatefooter0323.pptx/30updatefooter0323.pptx/30
Screw Press

CAROLLO / 31
updatefooter0323.pptx/31updatefooter0323.pptx/31
Sludge Drying Beds
SLUDGE
DRYING
BEDS
CAROLLO / 32
updatefooter0323.pptx/32updatefooter0323.pptx/32
Digester Sludge Holding Pond
Digester
Sludge
Holding
Pond
CAROLLO / 33
updatefooter0323.pptx/33updatefooter0323.pptx/33
Digester Sludge Holding Pond

CAROLLO / 34
updatefooter0323.pptx/34updatefooter0323.pptx/34
Near T erm UV Recommendations
• Additional UV bank unit needed to provide
redundancy/standby

← All documents from this meeting