cc/bsd 2025 AR 09/23 raceway basin and buena creek pump station improvements and fog abatement

Vista City Council
September 23, 2025

Document
cc/bsd 2025 AR 09/23 raceway basin and buena creek pump station improvements and fog abatement
Meeting
September 23, 2025
Body
Vista City Council
Pages
856
Original file
2.1 MB
Text extracted from the city's file for reading and search. Open the original on portal.laserfiche.com. That file is the official record.

0. 9
2 .4
0 .6
3 .9
$29,000
Fence

2.1 0.4
1 .2

3.7 $61,000
Assets Near End of Useful
Life
0 2
1 .5
3 .5
$170,000
V&A Recommendations

0.3 1. 6
0 .6
2 .5
$10,000
Exhaust Fan Replacement

2. 4
0 0
2 .4
$11,000
TOTAL
0 $894,000

SZ0Z/£Z/60
n
Cn
Z L I, I, 40 ZLS abed
Cli ent: City of Vista
Pr oject: Pump Station Rehabilitation
Description: Raceway Pump Station
SOCIAL
Potential Project/
Process Area
Replace
Floating Plug at
Interconnect
W et W ell
Sprayer
Fence
Odor Control
Unit
Maintenance
Building and
Site
Improvements
Overflow
Storage Pond
Grind er
Improvements
E xhaust Fan
Replacement
Assets Near
End of Useful
Life
PLC
Replacement
V&A
Recommendation
Replace Floating Plug
at Interconnect
X
o
0 0
0 0
0 0
1 0
Wet Well Sprayer
1 x
1 1
1 1
0 1
1 1
1 Fence
1 0
X
1 1
1 0
0 1
1 1
Odor Contro l Unit
Maintenance
1 0
0 X
0 0
0 0
1 0
1 Building and Site
Improvements
1 0
0 1
X
1 0
0 1
0 1
Overflow Storage Pond
1 0
0 1
o
X
o
0 1
0 1
Grinder Improvements
1 1
1 1
1 1
X
1 1
1 1
Ex haust Fan
Replacement

0 1
1 1
1 0
X
1 1
1 Asse ts Near End of
Useful Life
o
0 0
0 0
0 0
o
x
0 0
PLC Replacement
1 0
o
1 1
1 0
0 1
X
1 V&A Recommendations
0 0
0 0
0 0
0 0
1 0
X
Note:

1. Projects are scored by starting with the project listed in the vertical column It is then compared to each project listed al ong th e horiz ontal top axis . If the pr oject is de em ed more critical than the project listed along the top, it is given a score of 1. If the project listed a long the top is considered more critical for the gi ven r anking category, then the proj ect is giv en a score of 0. The proj ect score is then the sum of 1's and O's running horizontally across the page. The sum is then multiplied by the category weight to determine the pr oject's score in that category

SZ0Z/£Z/60
n
U7
Z L I, I, 40 £LS abed
Cli ent: City of Vista
Pr oject: Pump Station Rehabilitation
Descripti on: Raceway Pump Station

ENVIRONMENTAL
Po ten tia l Project/
Proce ss Are a
Replac e
Floating Plug at
Interconnect
Wet Well
Sprayer
Fence
Odor Control
Unit
Maintenance
Building and
Site
Improvements
Overflow
Storage Pond
Grinder
Impr ovements
Exhaust Fan
Replacement
Assets Near
End of Useful
Life
PLC
Replacement
V&A
Recommendation
Replace Floating Plug
at Interco nnect
X
1 1
1 0
0 0
1 1
1 1
Wet Well Sprayer
0 X
1 1
1 0
0 1
Q
0 0
Fence
0 0
X
0 0
0 0
1 0
0 0
Odor Control Unit
Maintenance
0 0
1 X
1 0
0 1
1 1
1 Building and Site
Impro vements
1 0
1 0
X
o
0 1
tl
0 1
Overflow Storage Pond
1 1
1 1
1 X
0 1
0 0
7 Grinder Improvements
1 1
1 1
1 1
X
1 1
1 1
Exhaust Fan
Replacement
0 0
0 0
0 0
0 X
0 0
0 Assets Near End of
Useful Life
0 1
1 0
1 1
0 1
X
0 0
PLC Replacement
0 1
1 0
1 1
0 1
1 X
1 V&A Recommendations
0 1
1 0
0 0
0 1
1 0
X
Note:

1. Projects are scored by starting with the proje ct listed in the vertical column It is then c ompar ed to each pr oject listed along the horizo ntal top axis. If the project is deem ed more criti cal than the project listed along the top, it is given a score of 1. If the project listed along the to p is considered more critical for the given ranking category, then the proj ect is given a score of 0. The proj ect sc ore is then the sum of 1's and O's running horizontally a cross the page. The sum is then multiplied by the category weight to d etermine the pr oje ct's s core in that category

SZ0Z/£Z/60
n
U7
Z L I, I, 40 17LS abed
Cli ent: City of Vista
Pr oject: Pump Station Rehabilitation
Descripti on: Raceway Pump Station

FINA NCIAL
Po tential Project/
Proc ess Area
Replace
Floating Plug at
Interconnect
Wet Well
Sprayer
Fence
Od or C ontr ol
Unit
Maintenance
Building and
Site
Improvements
Overflow
Storage Pond
Grinder
Improvements
Exhaust Fan
Replacem ent
Assets Near
End of Useful
Life
PLC
Replacement
V&A
Rec ommendation
Replace Floating Plug
at Interconnect
X
1 1
1 1
1 0
1 1
1 1
Wet Well Sprayer
0 X
0 1
0 0
0 1
0 0
0 Fence
0 1
X
1 0
0 0
1 0
0 1
Odor Control Unit
M aintenance
0 0
0'
X
0 0
0 1
0 0
i
Building and Site
Improvements
o
1 1
1 x
1 0
1 1
1 1
Overflow Storage Pond
0 1
1 1
0 X
0 1
1 1
1 Grinder Improvements
1 1
1 1
1 1
X
1 1
1 1
Exhaust Fa n
Replacement
0 0
0 0
0 0
0 x
0 0
0 Assets Near End of
Useful Life
0 1
1 1
0 0
0 1
X
0 1
PLC Replacement
1 1
1 1
1 1
0 1
1 X
1 V&A Recommendations
0 1
0 0
0 0
0 1
0 o
x
Note:

1. Projects are scored by starting with the pro ject listed in the vertical column It is then compared to each proj ect listed along the horiz ontal top axis . If the proj ect is deem ed more critical than th e project listed along the top, it is given a score of 1. If the project listed along the top is considered more critical for the given ranking category, then the project is given a score of 0. The project sc ore is then the sum of 1's and 0's running horizo ntally across the pa ge . The sum is then multiplied by the cat egory w eight to det ermin e th e pr oj ect's sc ore in that category

PUMP STATION REHABILITATION STUDY I CITY OF VISTA
Appendix B
BUENA VISTA PUMP STATION: CONDITION

ASSESSMENT FORMS
FINAL I AUGUST2016
09/23/2025
C5 Page 575 of 1112

09/23/2025
C5 Page 576 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component CHECK VALVE - SEWAGE PUMP #1, 14"
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Mechanical
62 CKV-9901-000
2 Anniston AL (M&H valve co?)
cushioned swing, spring -loaded
1995
15 Component Information Tab
Comments
Pump #1 was not running
Mechanical
Date of Inspection
7/22/2015
Assessed By JL
Photo # 102901-102904
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive Some corrosion?
Excessive Some leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
Yes
Yes
N/A
Yes
Yes
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
N/A
N/A
N/A
N/A
09/23/2025
C5 Page 577 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component CHECK VALVE - SEWAGE PUMP #2, 14"
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:
63 CKV-9902-000
Discipline: Mechanical
2 Anniston AL (M&H valve co?)
cushioned swing, spring -loaded
1995
15 Component Information Tab
Comments
Pump #2 was not running.

Mechanical
Date of Inspection
7/22/2015
Assessed By JL
Photo #
102959
Excessive vibration?
Excessive noise?
At packing---> Excessive corrosion?
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
Yes
Yes
Yes
No
N/A
Yes
Yes
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
Yes
No
Yes
Yes
09/23/2025
C5 Page 578 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component CHECK VALVE - SEWAGE PUMP #4, 14"
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:
64 CKV-9904-000
Discipline: Mechanical
2 Anniston AL (M&H valve co?)
cushioned swing, spring -loaded
1995
15 Component Information Tab
Comments
Pump #4 not running
Mechanical
Date of Inspection
7/22/2015
Assessed By JL
Photo #
103408
Vertically oriented
Excessive vibration?
Excessive noise?
At packing - > Exccssivo Some corrosion?
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
Yes
No
N/A
Yes
Yes
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
Yes
Yes
09/23/2025
C5 Page 579 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component PLUG VALVE - DIP FORCEMAIN W/RESTRAINT, 24"
Item No./Asset ID: 66 V-9795-010
Discipline: Mechanical
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
2 1995
15 Component Information Tab
Comments
Mechanical
Date of Inspection
7/22/2015
Assessed By JL
Photo #
104130
Excessive vibration?
Excessive noise?
Excessive corrosion?
At connections > Excessive Some leaks?
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
No
Yes
N/A
Yes
Yes
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
N/A
N/A
N/A
N/A
09/23/2025
C5 Page 580 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component PLUG VALVE - RESTRAINED MECH, 16"
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:
67 V-9795-011
Discipline: Mechanical
5 1995
15 Component Information Tab
Comments
Mechanical
Date of Inspection
7/22/2015
Assessed By JW
Photo #
104130
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
Yes
Yes
N/A
Yes
Yes
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
Yes
Yes
No
N/A
09/23/2025
C5 Page 581 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: PLUG VALVE - FORCE MAIN, 16"
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Mechanical
68 V-9795-012
5 1995
15 Component Information Tab
Comments
Mechanical
Date of Inspection 7/22/2015
Assessed By JW
Photo # 103108
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
Yes
Yes
N/A
Yes
Yes
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
Yes
Yes
No
N/A
09/23/2025
C5 Page 582 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: PLUG VALVE - FORECEMAIN, 24"
Item No./Asset ID: 69 V-9795-041
Discipline: Mechanical
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
5 1995
15 Component Information Tab
Comments
Mechanical
Date of Inspection 7/22/2015
Assessed By JW
Photo # 103113
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
Yes
Yes
N/A
Yes
Yes
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
Yes N Yes
Yes
No
N/A
09/23/2025
C5 Page 583 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: PLUG VALVE - 20" FORCEMAIN ISOLATION
Item No./Asset ID: 79 V-9961-000
Discipline: Mechanical
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
5 1995
15 Component Information Tab
Comments
Mechanical
Date of Inspection 7/22/2015
Assessed By JW
Photo #
103323
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
Yes
Yes
N/A
Yes
Yes
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
Yes N Yes
Yes
No
N/A
09/23/2025
C5 Page 584 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: PLUG VALVE - 20" FORCEMAIN ISOLATION
Item No./Asset ID: 80 V-9965-000
Discipline: Mechanical
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
5 1995
15 Component Information Tab
Comments
Mechanical
Date of Inspection 7/22/2015
Assessed By JW
Photo #
103710
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
Yes
Yes
N/A
Yes
Yes
No
Yes
Yes
N/A
Excessive corrosion? Yes
Excessive leaks? Yes
Paint in good condition? No
Supports in good condition? N/A
09/23/2025
C5 Page 585 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: PLUG VALVE - 20" FORCEMAIN ISOLATION
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:
81 V-9970-000
Discipline: Mechanical
5 1995
15 Component Information Tab
Comments
Mechanical
Date of Inspection 7/22/2015
Assessed By JW
Photo # 104153
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
Yes
Yes
N/A
Yes
Yes
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
Yes
Yes
No
N/A
09/23/2025
C5 Page 586 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: TANK - HYDROPNEUMATIC TANK
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Mechanical
118
PVL-9770-000
2 1996
15 Component Information Tab
Comments
60 gal, 6 hp air supply anchorage for seismic
Mechanical
Date of Inspection 7/22/2015
Assessed By JL
Photo #
113236
should be checked (per Raj G)
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
Yes
No
No
Yes
Yes
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
Yes
Yes
09/23/2025
C5 Page 587 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Buena Vista Pumping Station
Component: PANEL - SEAL WATER - #1 SEWAGE PUMP
Item No./Asset ID:

Discipline: Mechanical
58 SW P-9901-000

4.5 Date of Inspection 7/22/2015
N/A
N/A
1996
15 Component Information Tab
Comments
Not using external seal water system
Mechanical
Assessed By JL
Photo #
102121
Excessive vibration?
Excessive noise?
Excessive corrosion?
Not in use--> Excessive leaks?
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
N/A
Yes
N/A
No
No
Yes
?
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
Yes
Yes
No
09/23/2025
C5 Page 588 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Buena Vista Pumping Station
Component: PANEL - SEAL WATER - #2 SEWAGE PUMP
Item No./Asset ID:

Discipline: Mechanical
59 SW P-9902-000

4.5 Date of Inspection 7/22/2015
N/A
N/A
1996
15 Component Information Tab
Comments
Mechanical
Assessed By JL
Photo #
102121
Excessive vibration?
Excessive noise?
Excessive corrosion?
Not in use--> Excessive leaks?
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
N/A
Yes
N/A
No
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
Yes
Yes
No
09/23/2025
C5 Page 589 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Buena Vista Pumping Station
Component: PANEL - SEAL WATER - #4 SEWAGE PUMP
Item No./Asset ID: 60 SWP-9904-000
Discipline: Mechanical
5 N/A
N/A
1996
15 Component Information Tab
Comments
Mechanical
Date of Inspection 7/22/2015
Assessed By JL
Photo #
104535
Excessive vibration?
Excessive noise?
Excessive corrosion?
Not in use--> Excessive leaks?
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
N/A
Yes
N/A
No
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
Yes
Yes
No
09/23/2025
C5 Page 590 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Buena Vista Pumping Station
Component: PANEL - SEAL WATER - SEWAGE PUMP #5
Item No./Asset ID:

Discipline: Mechanical
61 SW P-9905-000

4.5 Date of Inspection 7/22/2015
N/A
N/A
1996
15 Component Information Tab
Comments
Mechanical
Assessed By JL
Photo #
104535
Excessive vibration?
Excessive noise?
Excessive corrosion?
Not in use--> Excessive leaks?
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
N/A
Yes
N/A
No
No
Yes
?
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
Yes
Yes
No
09/23/2025
C5 Page 591 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process: Ventilation
Component WET WELL FAN VENTILATION STACK
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Mechanical
2 Component Information Tab
Comments
Mechanical
Date of Inspection
7/22/2015
Assessed By JL
Photo #
112915
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
No
No
N/A
Yes
Yes
No
?
Yes
?
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
N/A
N/A
N/A
N/A
09/23/2025
C5 Page 592 of 1112

Facility: Buena Vista Pumping Station
Process:

Component CHECK VALVE - SEWAGE PUMP #5, 14"
Item No./Asset ID: 65 CKV-9905-000
Discipline: Mechanical
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
3 Anniston AL (M&H valve co?)
Date of Inspection 7/22/2015
cushioned swing, spring -loaded Assessed By JL
1996
Photo #
15 Component Information Tab
Comments
Vertically oriented
Mechanical
103656
Excessive vibration?
At packing--> Excessive noise?
May be pump--> Excessive corrosion?
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
Yes
Yes
Yes
No
N/A
Yes
Yes
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
Yes
Yes
09/23/2025
C5 Page 593 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component PUMP - #2 SEWAGE
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Mechanical
22 P-9902-000
2 Yeoman's Chicago Pump
10522-6
1995
2008
20 Component Information Tab
Comments
Mechanical
Date of Inspection 7/22/2015
Assessed By JL
Photo #
102917
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
No
No
No
Yes
Yes
No
Yes
Yes
check with electrician
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
Yes
Yes
09/23/2025
C5 Page 594 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component DOOR - ROLL -UP (GENERATOR ROOM)
Item No./Asset ID: 163 MME -9750-000
Discipline: Mechanical
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
1 1995
20 Component Information Tab
Comments
Mechanical
Date of Inspection 7/22/2015
Assessed By JL
Photo #
115623
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
No
No
N/A
Yes
Yes
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
Yes
Yes
09/23/2025
C5 Page 595 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component SURGE TANK - FORCEMAIN
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Mechanical
120
PVL-9830-000
1 2001
15 Component Information Tab
Comments
Mechanical
Date of Inspection 7/22/2015
Assessed By JL
Photo #
105831
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
No
No
N/A
Yes
Yes
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
Yes
Yes
09/23/2025
C5 Page 596 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: CRANE - CHAIN HOIST (GENERATOR ROOM)
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Mechanical
148
C-9750-000
1 1996
20 Component Information Tab
Comments
In generator room, experiences only light use
Mechanical
Date of Inspection 7/22/2015
Assessed By JL
Photo #
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
N/A
N/A
N/A
Yes
Yes
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
Yes
Yes
09/23/2025
C5 Page 597 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: GRINDER
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Mechanical
116
GDR -9820-000
3 1996
2008
15 Component Information Tab
Comments
Mechanical
Date of Inspection 7/22/2015
Assessed By JW
Photo #
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
No
No
No
Yes
Yes
No
No
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
Yes
Yes
09/23/2025
C5 Page 598 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process: Raw Sewage
Component: PUMP - #4 SEWAGE
Item No./Asset ID:

Discipline: Mechanical
23 P-9904-000
Main Tab
Condition* 2
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Yeoman/s Chicago Pump
Date of Inspection 7/22/2015
10522-6 Assessed By JL
1995
2006 Photo #
20 Component Information Tab
Comments
Pump #4 not running
Mechanical
GPM= 4016/500 Head= 179/165
Excessive vibration?
Excessive noise?
Intake elbow and pump base--> Excessive corrosion?
Intake elbow connection to pump > Excessive Some leaks? Running hot?
Capable of running when inspected?
Some corrosion, needs to be recoated--> Support equipment functional? Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Pump #4 not running--> Motor amps within rating?
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Piping
N/A
N/A
Yes
Yes
N/A
Yes
Yes
No
Yes
Yes
N/A
Excessive Some corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
***corrosion, needs to be recoated
Yes
No
Yes
Yes
09/23/2025
C5 Page 599 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process: Raw Sewage
Component: PUMP - #5 SEWAGE
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Mechanical
24 P-9905-000
3 Date of Inspection 7/22/2015
***needs more attention than other pumps
Yeoman/s Chicago Pump
10522-6
1995
2007
20 Component Information Tab
Comments
Pump #5 has more noises than other pumps.

Mechanical
Assessed By JL
Photo #
Can Hear popping in volute/impeller
Could be due to hydraulics
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
***need tocheck with electrician
Piping
Yes
Yes
No
No
No
Yes
Yes
No
Yes
Yes
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
Yes
Yes
09/23/2025
C5 Page 600 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Process:

Raw sewage
Component: PUMP - #1 SEWAGE
Item No./Asset ID:

Discipline: Mechanical
21 P-9901-000
2 Yeoman's Chicago Pump
10522-6
1995
2008
20 Component Information Tab
Comments
Pump #1 was not running
Mechanical
Date of Inspection 7/22/2015
Assessed By JL
Photo #
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
No
No
N/A
Yes
Yes
No
Yes
Yes
not running
Excessive corrosion?
**base support
Excessive leaks?
Paint in good condition?
Supports in good condition?
Yes
No
Yes
Yes
09/23/2025
C5 Page 601 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: FENCE
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Structural
91 FENCE
1 2 3 4 5 0 Date of Inspection 7/22/2015
1995
20 Component Information Tab
Comments Structural
Assessed By JW
Photo # 112507
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Spalling concrete? N/A
Visible rebar? N/A
Excessive corrosion to structure? No
Excessive corrosion to members? No
Corrosion coating intact & in place? N/A
Visible structural deformations? No
Foundation settling evident? N/A
Major cracks? N/A
Evidence of tank leakage? N/A
Joint sealant replacement? N/A
Damaged members? No
09/23/2025
C5 Page 602 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: PAVEMENT - ASPHALT
Item No./Asset ID:

Discipline: Structural
92 PAVEMENT
Main Tab
Level of Service* 3
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
1995
20 Component Information Tab
Comments
Significant cracking
Structural
Date of Inspection 7/22/2015
Assessed By JW
Photo # 123059
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Spalling concrete? N/A
Visible rebar? N/A
Excessive corrosion to structure? N/A
Excessive corrosion to members? N/A
Corrosion coating intact & in place? N/A
Visible structural deformations? N/A
Foundation settling evident? N/A
Major cracks? Yes
Evidence of tank leakage? N/A
Joint sealant replacement? N/A
Damaged members? N/A
09/23/2025
C5 Page 603 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: BUILDING - WET WELL
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Structural
94 WETWELL
2 1995
50 Component Information Tab
Comments
Roof of wet well has multiple cracks, possibly
Structural
Date of Inspection 7/22/2015
Assessed By RG
Photo #
causing the leaks inside the room.

This should be fixed to prevent rebar corrosion.
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Spalling concrete?
Visible rebar?
Excessive corrosion to structure?
Excessive corrosion to members?
Corrosion coating intact & in place?
Visible structural deformations?
Foundation settling evident?
Major cracks?
Evidence of tank leakage?
Joint sealant replacement?
Damaged members?
No
No
No
No
N/A
No
No
Yes
N/A
N/A
N/A
09/23/2025
C5 Page 604 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: STRUCTURE - VAULT FOR FLOW METER
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Structural
164
STR-9790-000
3 1995
50 Component Information Tab
Comments Structural
Water leaking in causing rusting at aluminum
Date of Inspection 7/22/2015
Assessed By RG
Photo #
beam and also along the perimeter wall. The
vault ws wet due to rain yesterday. It usually
dries out bu the crew thinks it could be
groundwater infiltration due to the hgih water
table. It should be investigated to prevent
rebar corrosion
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Spalling concrete? No
Visible rebar? No
Excessive corrosion to structure? Yes
Excessive corrosion to members? Rebar: Maybe
Corrosion coating intact & in place? Yes
Visible structural deformations? No
Foundation settling evident? No
Major cracks? No
Evidence of tank leakage? N/A
Joint sealant replacement? N/A
Damaged members? Rebar: Maybe
09/23/2025
C5 Page 605 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: BUILDING - BUENA VISTA PUMP STATION
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Structural
165
BLD-9750-000
1 Roof concrete 2
1995
50 Component Information Tab
Comments

1. 60 gal, 6 hp hydropneumatic tank air supply
Structural
Date of Inspection 7/22/2015
Assessed By RG
Photo #
anchorage for seismic should be checked.

Spalling concrete?
Visible rebar?

2. White residue seen on ceiling of concrete roof after Excessive corrosion to structure? Most likely caused by water leak thru cracks.

3. Minor shrinkage crack in basement wall. Also a
larger size crack lining up w/ C.J. in perp. wall.

Does not seem to be structural issue.

Excessive corrosion to members?
Corrosion coating intact & in place?
Visible structural deformations?
Foundation settling evident?

4. The roof concrete slab leaks per David (maint). The Major cracks? expansion joint between CMU and concrete Structure Evidence of tank leakage? leaks at the floor level. The expansion joint was Joint sealant replacement? probably compromised on roof. Damaged members?
No
No
No
No
N/A
No
No
No
No
N/A
N/A

5. Roof of wet well has multiple cracks, possible causing the leaks inside the room. This should be fixed to

6. Random cracks in plaster on exterior wall - non-structural

7. Expansion joint behind stair stringer on roof is broken. Water is probably leaking through this broken joint and to the floor below between the building expansion joint. * Condition / Level of Service
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
09/23/2025
C5 Page 606 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: ROOF Generator Room
Item No./Asset ID:

Discipline: Structural
Main Tab
Level of Service* 1
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Component Information Tab
Comments Structural
Date of Inspection 7/22/2015
Assessed By RG
Photo #

1. Minor cracks in wood beams in a couple of location1 Spalling concrete? No Sister new joists to strengthen. Visible rebar? N/A

2. Some of wood framing appears to have been expos( Excessive corrosion to structure? No to moisture but wood has not deteriorated. Excessive corrosion to members? No Corrosion coating intact & in place? Yes

3. Fans pull in moisture from the coast and probably Visible structural deformations? Yes causing mold on a few pieces of wood. Foundation settling evident? No Major cracks? No
Evidence of tank leakage? N/A
Joint sealant replacement? N/A
Damaged members? No
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
09/23/2025
C5 Page 607 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: FLOW METER VAULTS, NORTH AND SOUTH
Item No./Asset ID: I _
Discipline: Structural
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

2.5 Date of Inspection 7/22/2015
2013
Component Information Tab
Comments Structural
Assessed By RG
Photo #
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Spalling concrete? No
Visible rebar? No
Excessive corrosion to structure? Yes
Excessive corrosion to members? Yes
Corrosion coating intact & in place? Yes
Visible structural deformations? No
Foundation settling evident? No
Major cracks? No
Evidence of tank leakage? N/A
Joint sealant replacement? N/A
Damaged members? No
09/23/2025
C5 Page 608 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: SWITCH - AUTO TRANSFER SWITCH - #1 GEN
Item No./Asset ID: 125 ATS-9801-000
Discipline: Electrical and Instrumentation
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
2 Asco
s/o: 75276501
1994
Nominal Useful Life (years): 20
Component Information Tab
Comments
Minor scratches and spots
Electrical
Date of Inspection 7/22/2015
Assessed By SM
Photo #
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?Yes
Supports in good condition? Yes
Instrumentation
No
Yes
No N/A
No N/A
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioningYes
Alarms functional? Yes
Equipment or missing parts? Yes
Parts available for maintenance?Yes
No N/A
No N/A
No N/A
No N/A
09/23/2025
C5 Page 609 of 1112

Facility / System Condition Assessment Form
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Buena Vista Pumping Station
Component: PANEL - PUMP CONTROL
Item No./Asset ID:
43 PCP -9800-000
Discipline: Electrical and Instrumentation
1 Allen-Bradley
1995
15 Component Information Tab
Comments
No signs of corrosion or damage
Electrical
Date of Inspection 7/22/2015
Assessed By SM
Photo #
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
Yes
Yes
Yes
No
No
No
No
N/A
N/A
N/A
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
09/23/2025
C5 Page 610 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: MAIN TIE BREAKER, BVPS
Item No./Asset ID: 140
M BT -9900-000
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years): 20
1995
Component Information Tab
Comments
No signs of damage or corrosion
Electrical
Date of Inspection 7/22/2015
Assessed By SM
Photo #
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
09/23/2025
C5 Page 611 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: MOTOR - #1 SEWAGE PUMP
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:
17 M-9901-000
Discipline: Electrical and Instrumentation
1 1996
Date of Inspection 7/22/2015
Assessed By SM
2004 Photo # 2650-2655
10 Component Information Tab
Comments
No signs of corrosion or damage
Electrical
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
Yes
No
Yes
Yes
No N/A
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
09/23/2025
C5 Page 612 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: PANEL - VFD, #1 SEWAGE PUMP MOTOR
Item No./Asset ID: 100 VFD-9901-000
Discipline: Electrical and Instrumentation
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
5 Allen-Bradley
s/o: IWC-KFKY85-V1
1995
Year Refurbished/Replaced 2009
Nominal Useful Life (years): 10
Component Information Tab
Comments
No signs of corrosion or damage
Electrical
Date of Inspection 7/22/2015
Assessed By SM
Photo #
***Obsolete and scheduled for replacement
Excessive corrosion? Yes
Clean, well maintained contacts?Yes
Parts available for maintenance?Yes
Supports in good condition? Yes
Instrumentation
No N/A
No N/A
No N/A
No N/A
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioninPs
Alarms functional? Yes
Equipment or missing parts? Yes
Parts available for maintenanceWes
No N/A
No N/A
No N/A
No N/A
09/23/2025
C5 Page 613 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: CONTROL PANEL FOR SURGE TANK
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:
110
PN L-9830-000
Discipline: Electrical and Instrumentation
1 2001
15 Component Information Tab
Comments
No signs of damage or corrosion
Electrical
Date of Inspection
Assessed By
Photo #
7/22/2015
SM
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
Yes
Yes
Yes
Yes
No N/A
No N/A
No N/A
No N/A
09/23/2025
C5 Page 614 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: PANEL - WET WELL BUBBLWER
Item No./Asset ID: 108
P N L-9800-000
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer
Date of Inspection 7/22/2015
Model Assessed By SM
Year Installed 1995
Year Refurbished/Replaced 2005 Photo # 2662-2673
Nominal Useful Life (years): 15
Component Information Tab
Comments Electrical
No signs of corrosion.

Panel in good condition
Excessive corrosion? Yes No N/A
Clean, well maintained contacts?Yes No N/A
Parts available for maintenance?Yes No N/A
Supports in good condition? Yes No N/A
Instrumentation
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioninPs No N/A
Alarms functional? Yes No N/A
Equipment or missing parts? Yes No N/A
Parts available for maintenanceWes No N/A
09/23/2025
C5 Page 615 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: PANEL - VFD, #2 SEWAGE PUMP MOTOR
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:
101
VFD-9902-000
Discipline: Electrical and Instrumentation
5 Allen-Bradley
s/o: IWC-HOZ093
1995
2009
10 Component Information Tab
Comments
No signs of corrosion or damage
Electrical
Date of Inspection
Assessed By
Photo #
7/22/2015
SM
***Obsolete and scheduled for replacement
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
Yes
Yes
Yes
Yes
No N/A
No N/A
No N/A
No N/A
09/23/2025
C5 Page 616 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: MOTOR CONTROL CENTER - #2
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:
142
MCC -9800-B00
Discipline: Electrical and Instrumentation
2 Allen-Bradley
1995
40 Component Information Tab
Comments
Minor scratches and spots
Electrical
Date of Inspection 7/22/2015
Assessed By SM
Photo #
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
09/23/2025
C5 Page 617 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: SWITCH - AUTOTRANSFER SWITCH - #2 GENERATOR
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:
126
ATS-9802-000
Discipline: Electrical and Instrumentation
2 Asco
1994
2006
20 Component Information Tab
Comments
Minor scratches and spots
Electrical
Date of Inspection 7/22/2015
Assessed By SM
Photo #
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
09/23/2025
C5 Page 618 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: PANEL - GRINDER LEVEL
Item No./Asset ID:
109
PNL-9820-000
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 2
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
1996
15 Component Information Tab
Comments
Minor scratches
Electrical
Date of Inspection 7/22/2015
Assessed By SM
Photo #
Excessive corrosion? No
Clean, well maintained contacts? Yes No N/A
Parts available for maintenance? Yes No N/A
Supports in good condition? Yes No N/A
Instrumentation
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes No N/A
Alarms functional? Yes No N/A
Equipment or missing parts? Yes No N/A
Parts available for maintenance? Yes No N/A
09/23/2025
C5 Page 619 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: PANEL - BARSCREEN CONTROL PANEL
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:
146
PNL-9815-000
Discipline: Electrical and Instrumentation
1 1996
15 Component Information Tab
Comments
No sign of corrosion or damage
Electrical
Date of Inspection 7/22/2015
Assessed By SM
Photo #
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
Yes
Yes
Yes
No
No
No
No
N/A
N/A
N/A
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
09/23/2025
C5 Page 620 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: MOTOR - #5 SEWAGE PUMP
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:
20 M-9905-000
Discipline: Electrical and Instrumentation
1 1996
Date of Inspection 7/22/2015
Assessed By SM
2003 Photo # 2633-2637
10 Component Information Tab
Comments
No signs of damage or corrosion
Electrical
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
Yes
Yes
Yes
No
No
No
No
N/A
N/A
N/A
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
09/23/2025
C5 Page 621 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: AUTOTRANSFER SWITCH
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID: 128
Discipline: Electrical and Instrumentation
ATS-9803-000
2 Asco
1994
20 Component Information Tab
Comments
Minor scratches and spots
Electrical
Date of Inspection 7/22/2015
Assessed By SM
Photo #
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
Yes
Yes
Yes
No
No
No
No
N/A
N/A
N/A
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
09/23/2025
C5 Page 622 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: MAIN BREAKER, MCC -1
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID: 138
Discipline: Electrical and Instrumentation
M BA -9900-000
2 Allen-Bradley
1995
20 Component Information Tab
Comments
Minor scratches and spots.

Electrical
Date of Inspection 7/22/2015
Assessed By SM
Photo #
Also minor signs of corrosion
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
Yes
Yes
Yes
No
No
No
No
N/A
N/A
N/A
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
09/23/2025
C5 Page 623 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: MAIN BREAKER, MCC -2
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID: I 139
Discipline: Electrical and Instrumentation
M BB -9900-000
2 Allen-Bradley
1995
20 Component Information Tab
Comments
Minor scratches
Electrical
Date of Inspection 7/22/2015
Assessed By
Photo #
Excessive corrosion? No
Clean, well maintained contacts? Yes No N/A
Parts available for maintenance? Yes No N/A
Supports in good condition? Yes No N/A
Instrumentation
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes No N/A
Alarms functional? Yes No N/A
Equipment or missing parts? Yes No N/A
Parts available for maintenance? Yes No N/A
09/23/2025
C5 Page 624 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: PANEL - VFD, #4 SEWAGE PUMP MOTOR
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Item No./Asset ID: 102
VFD-9904-000
Discipline: Electrical and Instrumentation
5 Allen-Bradley
s/o: IWC-KFKY85-V2
1995
Year Refurbished/Replaced 2009
Nominal Useful Life (years): 10
Component Information Tab
Comments
No signs of corrosion or damage
Electrical
Date of Inspection 7/22/2015
Assessed By SM
Photo #
***Obsolete and scheduled for replacement
Excessive corrosion? Yes
Clean, well maintained contacts?Yes
Parts available for maintenance?Yes
Supports in good condition? Yes
Instrumentation
No N/A
No N/A
No N/A
No N/A
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioninPs
Alarms functional? Yes
Equipment or missing parts? Yes
Parts available for maintenanceWes
No N/A
No N/A
No N/A
No N/A
09/23/2025
C5 Page 625 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: DETECTOR - GAS/OXYGEN ALARM UNIT, BVPS
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID: 104
Discipline: Electrical and Instrumentation
AE -9772-000
1 1996
Date of Inspection 7/22/2015
Assessed By
2008 Photo # 2762-2764 Wet well
20 Component Information Tab
Comments
No signs of corrosion or damage
Electrical
2765-2768 Dry well
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
Yes
Yes
Yes
Yes
No N/A
No N/A
No N/A
No N/A
09/23/2025
C5 Page 626 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: MOTOR - #2 SEWAGE PUMP
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID: 1$
Discipline: Electrical and Instrumentation
M-9902-000
1 1996
Date of Inspection 7/22/2015
Assessed By SM
2007 Photo # 2656-2661
10 Component Information Tab
Comments
No signs of corrosion or damage
Electrical
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
Yes
Yes
Yes
Yes
No N/A
No N/A
No N/A
No N/A
09/23/2025
C5 Page 627 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: SWITCH - AUTOTRANSFER SWITCH
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID: 127
Discipline: Electrical and Instrumentation
ATS-9803-00A
2 Asco
1994
2006
20 Component Information Tab
Comments
Minor scratches and spots
Electrical
Date of Inspection 7/22/2015
Assessed By SM
Photo #
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
Yes
Yes
Yes
Yes
No N/A
No N/A
No N/A
No N/A
09/23/2025
C5 Page 628 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: PANEL - VFD, #5 SEWAGE PUMP MOTOR
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID: 103
Discipline: Electrical and Instrumentation
VFD-9905-000
5 Allen_Bradley
s/o: IWC-KFKY85-V3
1995
2009
10 Component Information Tab
Comments
No signs of corrosion or damage
Electrical
Date of Inspection
Assessed By
Photo #
7/22/2015
SM
***Obsolete and scheduled for replacement
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
Yes
Yes
Yes
Yes
No N/A
No N/A
No N/A
No N/A
09/23/2025
C5 Page 629 of 1112

Facility / System Condition Assessment Form
Facility: Buena Vista Pumping Station
Process:

Component: MOTOR CONTROL CENTER - #1
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID: 141
Discipline: Electrical and Instrumentation
MCC -9800-A00
2 1995
40 Component Information Tab
Comments
Minor signs of corrosion and scratches
Electrical
Date of Inspection
Assessed By
Photo #
7/22/2015
SM
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
Yes
Yes
Yes
Yes
No N/A
No N/A
No N/A
No N/A
09/23/2025
C5 Page 630 of 1112

PUMP STATION REHABILITATION STUDY I CITY OF VISTA
Appendix C
RACEWAY PUMP STATION: CONDITION

ASSESSMENT FORMS
FINAL I AUGUST2016
09/23/2025
C5 Page 631 of 1112

09/23/2025
C5 Page 632 of 1112

cacility / System Condition Assessment Form
�cility: Raceway Pumping Station
-ocess:
)mponent: STORAGE BASIN
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Mechanical
4 Component Information Tab
Comments
Groundwater infiltration issues
Mechanical
Date of Inspection 7/23/2015
Assessed By JW/RLG
Photo # 0104-0106
esst valve to/from emergency overflow not
sealing, can see flow
Curbing with rail needs to be redone
- concrete cracking at handrail posts
-redo curb with appropriate insertion material
- handrail can be reused
* Condition
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
N/A
N/A
N/A
N/A
09/23/2025
C5 Page 633 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Raceway Pumping Station
Component: CHANNEL GRINDER, RWPS
Item No./Asset ID:

Discipline: Mechanical
14 GDR -12000-000
5 MOYNO
M32C3 CS7R5R
2006
15 Component Information Tab
Comments
Grinder NOT INSTALLED
Mechanical
Date of Inspection 7/23/2015
Assessed By JW/RLG
Photo #
110628
Not functioning
Valves not exercised enough
Valves should be separate assets
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
N/A
N/A
N/A
No
Yes
N/A
No
No
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
N/A
N/A
N/A
N/A
09/23/2025
C5 Page 634 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component: PUMP - #1 SEWAGE PUMP, SUBMERSIBLE, 75 HP, RWPS Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Mechanical
20 P-12001-000
2 FAIRBANKS MORSE PUMP CO
Date of Inspection 7/23/2015
4" D5434MV Assessed By JW/RLG
2007
2008 operators stated more recent Photo #
15 Component Information Tab
Comments
Well -maintained: pull up annually to inspect
Mechanical
100551
Ragging issues
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
No
No
No
Yes
Yes
No
Yes
Yes
Yes
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
**Minor on Flanges
No
N/A
N/A
09/23/2025
C5 Page 635 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Raceway Pumping Station
Component: PUMP - #2 SEWAGE PUMP, SUBMERSIBLE, 75 HP, RWPS Item No./Asset ID:

Discipline: Mechanical
21 P-12002-000
2 FAIRBANKS MORSE PUMP CO
4" D5434MV
2007
15 Component Information Tab
Comments
Well -maintained: pull up annually to inspect
Mechanical
Date of Inspection 7/23/2015
Assessed By JW/RLG
Photo # 100559
Ragging issues
* Condition
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
No
No
No
Yes
Yes
No
Yes
Yes
Yes
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
**Minor on Flanges
No
N/A
N/A
09/23/2025
C5 Page 636 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Raceway Pumping Station
Component: PUMP - #3 SEWAGE PUMP, SUBMERSIBLE, 75 HP, RWPS Item No./Asset ID:

Discipline: Mechanical
22 P-12003-000
2 FAIRBANKS MORSE PUMP CO
4" D5434MV
2007
15 Component Information Tab
Comments
Well -maintained: pull up annually to inspect
Mechanical
Date of Inspection 7/23/2015
Assessed By JW/RLG
Photo #
100541
Ragging issues
* Condition
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
No
No
No
Yes
Yes
No
Yes
Yes
Yes
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
**Minor on Flanges
No
N/A
N/A
09/23/2025
C5 Page 637 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Component:

Raceway Pumping Station

PUMP DISCHARGE VALVES
Item No./Asset ID:

Discipline: Mechanical
2 Component Information Tab
Comments
Exercised weekly
Mechanical
Date of Inspection 7/23/2015
Assessed By JW/RLG
Photo # 110708
No sign of leakage
* Condition
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
No
No
No
Yes
Yes
N/A
N/A
N/A
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
N/A
N/A
09/23/2025
C5 Page 638 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Component:

Raceway Pumping Station

ODOR CONTROL SCRUBBER SYSTEM, LOW -FLOW, RWPS
Item No./Asset ID:

Discipline: Mechanical
19 ORF-12000-000
3 Date of Inspection 7/23/2015
FRP Radial Fume Exhauster Assessed By JW/RLG
2005
20 Component Information Tab
Comments
Pipes brittle
Mechanical
Photo # 101708
Carbon has never been changed
Rust on supports and bolts

0.68 hp motor
* Condition
1 - Very Good
2 - Minor Defects
3- Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
No
No
No
Yes
Yes
N/A
N/A
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
Yes
Yes
09/23/2025
C5 Page 639 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component: SLUICE GATE VALVE- WET WELL GRINDER SIDE, 16", RWP5 Item No./Asset ID: 25 SLG-12009-000
Discipline: Mechanical
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
2 Hydrogate
2007
20 Component Information Tab
Comments
Valves get stuck, hard to move
Mechanical
Date of Inspection 7/23/2015
Assessed By JW/RLG
Photo #
2250
Seals well
Valves are exercised annually
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
N/A
N/A
N/A
N/A
Yes
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
N/A
N/A
N/A
N/A
09/23/2025
C5 Page 640 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Component:

Raceway Pumping Station
SLUICE GATE VALVE- WET WELL BAR RACK SIDE, 16", RWP
Item No./Asset ID:

Discipline: Mechanical
26 SLG-12010-000
2 Hydrogate
2007
20 Component Information Tab
Comments
Valves get stuck, hard to move
Mechanical
Date of Inspection 7/23/2015
Assessed By JW/RLG
Photo #
104
Seals well
Valves are exercised annually
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
N/A
N/A
N/A
N/A
Yes
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
N/A
N/A
N/A
N/A
09/23/2025
C5 Page 641 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component: FENCE & PAVEMENT
Item No./Asset ID:

Discipline: Mechanical
Main Tab
Condition* 3
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Component Information Tab
Comments Mechanical
Date of Inspection 7/23/2015
Assessed By JW/RLG
Photo #
1311
8' chain link fencing in good condition Excessive vibration? Back fence/gate notsecure with just a lock Excessive noise? -needs a chain at least Excessive corrosion?
Roof overhangs building: easy access to site Excessive leaks? -Is fence at property line or can move it back? Running hot? Need additional security on top of fence Capable of running when inspected? -City Ord. 2003-3, Section 18.02.300.F precludes use Support equipment functional? of barbed/razor wire within city limits Equipment or parts missing? -Candy cane style security fencing acceptable Parts for maintenance available? Asphalt and concrete good Adequate for intended purpose? Motor amps within rating?
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Piping
N/A
N/A
No
N/A
N/A
N/A
N/A
N/A
N/A
No
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
N/A
N/A
N/A
N/A
09/23/2025
C5 Page 642 of 1112

Facility / System Condition Assessment Form
Facility:

Process:

Component:

Raceway Pumping Station

WEST FLAP GATE VALVE - WET WELL
Item No./Asset ID:

Discipline: Mechanical
Main Tab
Condition* 2
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Component Information Tab
Comments
No issues
Mechanical
Date of Inspection 7/23/2015
Assessed By JW/RLG
Photo #
104
Exercised weekly
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
No
No
N/A
N/A
N/A
N/A
N/A
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
No
No
09/23/2025
C5 Page 643 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component:

Item No./Asset ID:

EAST FLAP GATE VALVE - WET WELL
Discipline: Mechanical
Main Tab
Condition* 4
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Component Information Tab
Comments
Surficial, moderate corrosion and leaking reported
Is gasket damaged, missing?
Mechanical
Date of Inspection 7/23/2015
Assessed By JW/RLG
Photo #
104
Can see water flowing toward flap gate
If basin is full, will pressure of water seal the gate? * Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?Yes
Motor amps within rating? Yes
Piping
N/A
N/A
Moderate
Moderate
N/A
N/A
N/A
N/A
N/A
No N/A
No N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
N/A
N/A
N/A
N/A
09/23/2025
C5 Page 644 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component: WET WELL
Item No./Asset ID:

Discipline: Mechanical
Main Tab
Condition* 2
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Component Information Tab
Comments
Good condition
Mechanical
Date of Inspection 7/23/2015
Assessed By JW/RLG
Photo # 100534
Liner is good
Operator concerns:
-Mixing system to homogenize grease build up
-Chopper pump?
-spray down system?
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
N/A
No
N/A
N/A
Yes
N/A
N/A
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
N/A
No
N/A
N/A
09/23/2025
C5 Page 645 of 1112

Facility / System Condition Assessment Form
Facility:

Process:

Raceway Pumping Station
Component: AIR AND VACUUM RELIEF VALVE
Item No./Asset ID:

Discipline: Mechanical
Main Tab
Condition* 2
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Component Information Tab
Comments
Cleaned regularly, in good shape
Mechanical
Date of Inspection 7/23/2015
Assessed By JW/RLG
Photo #
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
No
No
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
N/A
N/A
09/23/2025
C5 Page 646 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component: BUILDING
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Mechanical
2 Component Information Tab
Comments
Exhaust fan- minor corrosion, looks good
Mechanical
Date of Inspection 7/23/2015
Assessed By JW/RLG
Photo #
119
NEEDS:
- New solid doors to replac elouvered door that
allow plant material infiltration
- roof intake fans
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
No
No
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
N/A
N/A
09/23/2025
C5 Page 647 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component: FENCE - 8' HIGH CHAIN LINK, RWPS
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Structural
53 FENCE
3 2007
10 Component Information Tab
Comments Structural
Date of Inspection 7/23/2015
Assessed By JW/RLG
Photo #
8' chain link fencing in good condition Spalling concrete? N/A Back fence/gate notsecure with just a lock Visible rebar? N/A - needs a chain at least Excessive corrosion to structure? No Roof overhangs building: easy access to site Excessive corrosion to members? N/A - Is fence at property line or can move it back? Corrosion coating intact & in place? N/A Need additional security on top of fence Visible structural deformations? No - City Ord. 2003-3, Section 18.02.300.F precludes use Foundation settling evident? N/A of barbed/razor wire within city limits Major cracks? N/A - Candy cane style security fencing acceptable Evidence of tank leakage? N/A Joint sealant replacement? N/A
Damaged members? N/A
* Condition / Level of Service
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
09/23/2025
C5 Page 648 of 1112

Facility / System Condition Assessment Form
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Component:

Raceway Pumping Station

PAVEMENT, AC - PUMP STATION SITE, RWPS
Item No./Asset ID:

Discipline: Structural
54 AC PAVING
2 Date of Inspection
2007
20 Component Information Tab
Comments Structural
Assessed By
Photo # 1311
* Condition / Level of Service
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Spalling concrete? Yes No N/A
Visible rebar? Yes No N/A
Excessive corrosion to structure? Yes No N/A
Excessive corrosion to members? Yes No N/A
Corrosion coating intact & in place? Yes No N/A
Visible structural deformations? Yes No N/A
Foundation settling evident? Yes No N/A
Major cracks? Yes No N/A
Evidence of tank leakage? Yes No N/A
Joint sealant replacement? Yes No N/A
Damaged members? Yes No N/A
09/23/2025
C5 Page 649 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component: BUILDING
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Structural
3 BLD-12000-000
1 2007
50 Date of Inspection 7/23/2015
Assessed By RG
Photo # 119
Component Information Tab
Comments Structural

1. Overflow tank gets groundwater seeping Spalling concrete? No though the bottom slab to liner joint Visible rebar? No

2. PVC liner peeling in a few areas at the top of Excessive corrosion to structure? No the vaults Excessive corrosion to members? No

3. Roof wod exposed to outside environment; Corrosion coating intact & in place? Yes these joists were not pressure -treated; plywood Visible structural deformations? No can be seen flaking due to moisture caused Foundation settling evident? No shrinkage Major cracks? No

4. Joists outside the building walls are only Evidence of tank leakage? No painted for protection. Can cause deterioration Joint sealant replacement? No in future. Damaged members? Yes

5. PVC liner looks in good shape in wet well, no tears or damage. * Condition / Level of Service
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
09/23/2025
C5 Page 650 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component: EMERGENCY OVERFLOW STORAGE POND
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Structural
28 STR-12001-000
3 2007
50 Component Information Tab
Comments
groundwater leakage
Structural
Date of Inspection
Assessed By JW
Photo #
104
* Condition / Level of Service
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Spalling concrete?
Visible rebar?
Excessive corrosion to structure?
Excessive corrosion to members?
Corrosion coating intact & in place?
Visible structural deformations?
Foundation settling evident?
Major cracks?
Evidence of tank leakage?
Joint sealant replacement?
Damaged members?
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
09/23/2025
C5 Page 651 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component: WET WELL, RWPS
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Structural
29 STR-12003-000
1 2007
50 Component Information Tab
Comments
PVC liner looks good
Structural
Date of Inspection
Assessed By RG
Photo # 122-130
No tears or damage
* Condition / Level of Service
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Spalling concrete?
Visible rebar?
Excessive corrosion to structure?
Excessive corrosion to members?
Corrosion coating intact & in place?
Visible structural deformations?
Foundation settling evident?
Major cracks?
Evidence of tank leakage?
Joint sealant replacement?
Damaged members?
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
09/23/2025
C5 Page 652 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component: Exterior Lights
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

N/A
Discipline: Electrical and Instrumentation
1 Component Information Tab
Comments
2 pole lights are not on the photo eye.

Electrical
Date of Inspection
7/23/15
Assessed By TH/AM
Photo # 2781-2789
Fixture on top of building needs to be replaced.

All other fixtures are in good condition.

Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
N/A
Yes
Yes
* Condition / Level of Service
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
N/A
N/A
N/A
N/A
09/23/2025
C5 Page 653 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component: AUTOMATIC TRANSFER SWITCH, RWPS
Item No./Asset ID: 1 ATS-12000-000
Discipline: Electrical and Instrumentation
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
1 GE Zenith Controls
2007
15 Component Information Tab
Comments
Electrical
Date of Inspection 7/23/15
Assessed By TH/AM
Photo # 2857-2861
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
* Condition / Level of Service
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
No
Yes
Yes
Yes
Yes
Yes
No
Yes
09/23/2025
C5 Page 654 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component: Discharge Meter Vault
Item No./Asset ID: I N/A
Discipline: Electrical and Instrumentation
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
1 Sparling Tiger Mag EP
Date of Inspection 7/23/15
FM 656 Assessed By TH/AM
Component Information Tab
Comments
In good condition
Electrical
Photo # 2790-2791 &
2849-2851
No reported issues
Vault has ver low risk of flooding
Transmitter located in electrical room
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
No
N/A
Yes
Yes
Yes
Yes
No
Yes
09/23/2025
C5 Page 655 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component: Grinder Control Panel
Item No./Asset ID:

Discipline: Electrical and Instrumentation
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
1 Manyo Annihilator Controller
Component Information Tab
Comments
Electrical
Date of Inspection 7/23/15
Assessed By TH/AM
Photo # 2852-2856
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
No
N/A
Yes
Yes
Yes
Yes
No
Yes
09/23/2025
C5 Page 656 of 1112

Facility / System Condition Assessment Form
Facility:

Process:

Component:

Raceway Pumping Station
VFD - SEWAGE PUMP # 2 RWPS
Item No./Asset ID:
43 VFD-12002-000
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Allen-Bradley
Powerflex
2007
10 Component Information Tab
Comments
Maintenance staff has reported issues of VFD failures
caused by dirty environment in electrical room.

Electrical
Date of Inspection 7/23/15
Assessed By TH/AM
Photo # 2801-2807
Minor UV degredation on FRP cable termination box.

Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
N/A
Yes
N/A
* Condition / Level of Service
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
Yes
Yes
No
Yes
09/23/2025
C5 Page 657 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component: PLC, RWPS
Item No./Asset ID: 24 PLC -12000-000
Discipline: Electrical and Instrumentation
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
1 Allen-Bradley
FlexLogix 5434
2007
15 Component Information Tab
Comments
Inside of the cabinet is very dirty.

Electrical
Date of Inspection 7/23/15
Assessed By TH/AM
Photo # 2818-2844
Ventilation fan I very dirty.

FlexLogix PLC fails every couple months and needs
to be reset.

FlexLogix PLC doesn no allow for redundant
processor.

Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3- Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
09/23/2025
C5 Page 658 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Process:

Component:

Odor Control System
Item No./Asset ID:

Discipline: Electrical and Instrumentation
1 Square D
Component Information Tab
Comments Electrical
Date of Inspection 7/23/15
Assessed By TH/AM
Photo # 2792-2795
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
No
N/A
Yes
Yes
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 659 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component: Building Interior Lights
Item No./Asset ID:

Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Component Information Tab
Comments Electrical
Date of Inspection 7/23/15
Assessed By TH/AM
Photo # 2889-2893
8' - 2 lamp wet location flourecents in good condition Excessive corrosion? Emergency lights are functional Clean, well maintained contacts? Light switch is functional Parts available for maintenance? Supports in good condition?
Instrumentation
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
No
N/A
Yes
Yes
All critical indications functioning? N/A
Alarms functional? N/A
Equipment or missing parts? N/A
Parts available for maintenance? N/A
09/23/2025
C5 Page 660 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component: VFD - DRIVE SEWAGE PUMP#3 RWPS
Item No./Asset ID:
44 VFD-12003-000
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Allen-Bradley
Date of Inspection 7/23/15
Powerflex Assessed By TH/AM
2007
10 Component Information Tab
Comments Electrical
Photo # 2808-2813
Maintenance staff has reported issues of VFD failures Excessive corrosion? No caused by dirty environment in electrical room. Clean, well maintained contacts? N/A Minor UV degredation on FRP cable termination box. Parts available for maintenance? Yes Supports in good condition? N/A
Instrumentation
* Condition / Level of Service
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 661 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component: ENGINE - EMERGENCY STANDBY GENERATOR, RWPS
Item No./Asset ID:
19 Discipline: Electrical and Instrumentation
E-12000-000
Main Tab
Level of Service* 1
Manufacturer Kohler Power Ssytems
Date of Inspection 7/23/15
Model 275REOZV Assessed By TH/AM
Year Installed 2007
Year Refurbished/Replaced Photo # 2769-2780
Nominal Useful Life (years): 20
Component Information Tab
Comments
140 of runtime
Electrical
No observed or reported issues.

Excessive corrosion? No
Clean, well maintained contacts? N/A
Parts available for maintenance? Yes
Supports in good condition? Yes
Instrumentation
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 662 of 1112

Facility / System Condition Assessment Form
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility: Raceway Pumping Station
Process:

Component:

Pump Discharge manifold - Pressure transmitter gauge
Item No./Asset ID:

Discipline: Electrical and Instrumentation
1 Rosemount
Date of Inspection 7/23/15
3051 Assessed By TH/AM
Component Information Tab
Comments
Minor corrosion on manifold valves.

Electrical
Photo # 2814-2817
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
N/A
Yes
Yes
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
Yes
Yes
No
Yes
09/23/2025
C5 Page 663 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component: VFD - SEWAGE PUMP #1 RWPS
Item No./Asset ID:
42 VFD-12001-000
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Allen-Bradley
Date of Inspection 7/23/15
Powerflex Assessed By TH/AM
2007
2008 Photo # 2796-2800
10 Component Information Tab
Comments Electrical
Maintenance staff has reported issues of VFD failures Excessive corrosion? No caused by dirty environment in electrical room. Clean, well maintained contacts? N/A Minor UV degredation on FRP cable termination box. Parts available for maintenance? Yes Supports in good condition? N/A
Instrumentation
* Condition / Level of Service
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 664 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component: MOTOR CONTROL CENTER, RWPS
Item No./Asset ID: 18 MCC -12001-000
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Allen-Bradley
Date of Inspection 7/23/15
CenterLine Assessed By TH/AM
2005
40 Component Information Tab
Comments Electrical
MCC does not have a surge protective device.

Photo # 2862-2888
Excessive corrosion? No
Clean, well maintained contacts? Yes
Parts available for maintenance? Yes
Supports in good condition? Yes
Instrumentation
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 665 of 1112

Facility / System Condition Assessment Form
Facility: Raceway Pumping Station
Process:

Component: Wetwell ultrasonic level transmitter
Item No./Ass N/A
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1 Date of Inspection 7/23/15
Manufacturer Siemens
Model HyroRanger 2000 Assessed By TH/AM
Year Installed
Year Refurbished/Replaced Photo # 2845-2848
Nominal Useful Life (years):

Component Information Tab
Comments Electrical
In good condition, but not functional due to high
levels of foam.

Excessive corrosion? No
Clean, well maintained contacts? N/A
Parts available for maintenance? Yes
Supports in good condition? N/A
Instrumentation
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 666 of 1112

PUMP STATION REHABILITATION STUDY I CITY OF VISTA
Appendix D
BUENA CREEK PUMP STATION: CONDITION

ASSESSMENT FORMS
FINAL i AUGUST2016
09/23/2025
C5 Page 667 of 1112

09/23/2025
C5 Page 668 of 1112

racility / System Condition Assessment Form
3cility: Buena Creek Pump Station
rocess:
omponent: AIR COMPRESSOR (GRINDERS HU'S)
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
em No./Asset ID:
iscipline: Mechanical
2 Ingersoll Rand
Component Information Tab
Comments
Mechanical
Date of Inspection 7/28/2015
Assessed By JW/RLG
Photo #
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
09/23/2025
C5 Page 669 of 1112

Facility / System Condition Assessment Form
Facility:

Process:

Component: SITE WORK
Item No./Asset ID: I _
Discipline: Mechanical
Buena Creek Pump Station
Main Tab
Condition* 5
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Component Information Tab
Comments Mechanical
Date of Inspection 7/28/2015
Assessed By JW/RLG
Photo #

1. Asphalt resurfacing due to large cracks Excessive vibration?

2. Berm or curb installed to direct flow to basin on Excessive noise? west side of site for containment in case of spill Excessive corrosion? coming out manholes. Prevent flow to creek Excessive leaks?

3. Fence is too short Running hot?

4. Stairs needed to access SDG&E meter on east side Capable of running when inspected? of the building; dirt hill with erosion poses a safety Support equipment functional? hazard; erosion control needed Equipment or parts missing?

5. Staging area for bypass pumping Parts for maintenance available? Adequate for intended purpose?
Motor amps within rating?
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Piping
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
Excessive corrosion? Yes No N/A
Excessive leaks? Yes No N/A
Paint in good condition? Yes No N/A
Supports in good conditii Yes No N/A
09/23/2025
C5 Page 670 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Process:

Component: EXHAUST FAN
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Mechanical
2 New York Blower Co
FRP Radial Fume Exhauster
manufactured 2004
Component Information Tab
Comments
Shop# W06393 100
Mechanical
Date of Inspection 7/28/2015
Assessed By JW/RLG
Photo #
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
09/23/2025
C5 Page 671 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Process:

Component: CRANE (A -FRAME HOIST)
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Mechanical
1 Date of Inspection 7/28/2015
Wallace Products
S4T10-S10
Component Information Tab
Comments
Wallace 2 ton crane, 10' span
Mechanical
Assessed By JW/RLG
Photo #
Coffey hoist
M522S4T10-S10
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
09/23/2025
C5 Page 672 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Process:

Component: ELECTRIC VALVES (TO SHADOWRIDGE AND ENCINA)
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

Discipline: Mechanical
5 Component Information Tab
Comments
Crew stated that reaching end of useful life and
Mechanical
Date of Inspection 7/28/2015
Assessed By JW/RLG
Photo #
need replacement
2 valves per pump used to divert flow to Shadow -
ridge and Encina
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
09/23/2025
C5 Page 673 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Process:

Component: DRYWELL SUMP PUMP #1 BCPS
Item No./Asset ID: 37 P-11080-000
Discipline: Mechanical
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
2 Component Information Tab
Comments
No issues
Mechanical
Date of Inspection 7/28/2015
Assessed By JW/RLG
Photo #
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
09/23/2025
C5 Page 674 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Process:

Component: DRYWELL SUMP PUMP #2 BCPS
Item No./Asset ID: 38 P-11090-000
Discipline: Mechanical
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
2 Component Information Tab
Comments
No issues
Mechanical
Date of Inspection 7/28/2015
Assessed By JW/RLG
Photo #
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
No N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
Yes No N/A
Yes No N/A
Yes No N/A
Yes No N/A
09/23/2025
C5 Page 675 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Component:

Raceway Pumping Station

SURGE TANK - ENCINA FORCEMAIN
Item No./Asset ID:

Discipline: Mechanical
25 T-11000-000
2 2002
15 Component Information Tab
Comments
Minor corrosion on valves
Mechanical
Date of Inspection 7/28/2015
Assessed By JW/RLG
Photo #
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
No
No
No
Yes
Yes
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
Yes
Yes
09/23/2025
C5 Page 676 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Component:

Raceway Pumping Station
PLUG VALVE - 24" FORCE MAIN
Item No./Asset ID:

Discipline: Mechanical
48 V -11200-C01
5 Valmatic, Camcentric
2002
15 Component Information Tab
Comments
Operators reported that forcemain valves are leaking
and need replacement
Mechanical
Date of Inspection 7/28/2015
Assessed By JW/RLG
Photo #
* Condition
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
No
Yes
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
N/A
N/A
N/A
N/A
09/23/2025
C5 Page 677 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Raceway Pumping Station
Component: HYDRAULIC UNIT CHANNEL GRINDER #1
Item No./Asset ID:

Discipline: Mechanical
23 HU-11010-000
2 Component Information Tab
Comments
Mechanical
Date of Inspection 7/28/2015
Assessed By JW/RLG
Photo #
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
No
No
No
Yes
Yes
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
N/A
N/A
N/A
N/A
09/23/2025
C5 Page 678 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Raceway Pumping Station
Component: HYDRAULIC UNIT CHANNEL GRINDER #2
Item No./Asset ID: 24 HU-11020-000
Discipline: Mechanical
2 Component Information Tab
Comments
Mechanical
Date of Inspection 7/28/2015
Assessed By JW/RLG
Photo #
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
No
No
No
Yes
Yes
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
N/A
N/A
N/A
N/A
09/23/2025
C5 Page 679 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Component:

Raceway Pumping Station
CHANNEL GRINDER UNIT #2
Item No./Asset ID:

Discipline: Mechanical
72 GDR -11020-000
2 JWC Environmental
Channel Monster
2002
2006
15 Component Information Tab
Comments
No issues noted
Mechanical
Date of Inspection 7/28/2015
Assessed By JW/RLG
Photo #
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
No
No
No
Yes
Yes
No
Yes
Yes
Yes
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
Yes
Yes
09/23/2025
C5 Page 680 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Component:

Raceway Pumping Station
PUMP - #1, SEWAGE
Item No./Asset ID:

Discipline: Mechanical
7 P-11010-000
2 Cornell Pumps
8NNT
2002
20 Component Information Tab
Comments
S/N 124073
Mechanical
Date of Inspection 7/28/2015
Assessed By JW/RLG
Photo #
1736 GPM
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
No
No
No
Yes
Yes
No
Yes
Yes
Yes
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
Yes
Yes
09/23/2025
C5 Page 681 of 1112

Facility / System Condition Assessment Form
Facility:

Process:

Component:

Raceway Pumping Station

ODOR CONTROL UNIT -BIO-FILTER
Item No./Asset ID:

Discipline: Mechanical
82 ORF-11000-000
Main Tab
Condition* 3
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
2002
20 Component Information Tab
Comments
Condition level 3 due to housing
Mechanical
Date of Inspection 7/28/2015
Assessed By JW/RLG
Photo #
Minor corrosion on baseFiberglass with surficial cracks Fiberglass needs to be patched and painted
Fans, solenoids, and piping good
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
N/A
N/A
No
No
No
Yes
Yes
No
Yes
Yes
N/A
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
N/A
N/A
No
Yes
09/23/2025
C5 Page 682 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Component:

Raceway Pumping Station
CHANNEL GRINDER UNIT#1
Item No./Asset ID:

Discipline: Mechanical
71 GDR -11010-000
2 JWC Environmental
Channel Monster
2002
2008
15 Component Information Tab
Comments
No issues noted
Mechanical
Date of Inspection 7/28/2015
Assessed By JW/RLG
Photo #
A spare unit is kept onsite
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
No
No
No
Yes
Yes
No
Yes
Yes
Yes
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
Yes
Yes
09/23/2025
C5 Page 683 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Component:

Raceway Pumping Station
PUMP - #2, SEWAGE
Item No./Asset ID:

Discipline: Mechanical
8 P-11020-000
2 Cornell Pumps
8NNT
2002
2007
20 Component Information Tab
Comments
S/N 124072
Mechanical
Date of Inspection 7/28/2015
Assessed By JW/RLG
Photo #
3600GPM
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
No
No
No
Yes
Yes
No
Yes
Yes
Yes
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
Yes
Yes
09/23/2025
C5 Page 684 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Component:

Raceway Pumping Station
PUMP - #3, SEWAGE
Item No./Asset ID:

Discipline: Mechanical
9 P-11030-000
2 Cornell Pumps
8NNT
2002
2008
20 Component Information Tab
Comments
S/N 124071
Mechanical
Date of Inspection 7/28/2015
Assessed By JW/RLG
Photo #
2037 GPM
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
No
No
No
Yes
Yes
No
Yes
Yes
Yes
Excessive corrosion? Yes N
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
Yes
Yes
09/23/2025
C5 Page 685 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Component:

Raceway Pumping Station
PUMP - #4, SEWAGE
Item No./Asset ID:

Discipline: Mechanical
10 P-11040-000
2 Cornell Pumps
8NNT
2002
2008
20 Component Information Tab
Comments
S/N 124070
Mechanical
Date of Inspection 7/28/2015
Assessed By JW/RLG
Photo #
2037 GPM
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
No
No
No
Yes
Yes
No
Yes
Yes
Yes
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
Yes
Yes
09/23/2025
C5 Page 686 of 1112

Facility / System Condition Assessment Form
Main Tab
Condition*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Component:

Raceway Pumping Station
PUMP - #5, SEWAGE
Item No./Asset ID:

Discipline: Mechanical
11 P-11050-000
2 Cornell Pumps
8NNT
2002
2008
20 Component Information Tab
Comments
S/N 124069
Mechanical
Date of Inspection 7/28/2015
Assessed By JW/RLG
Photo #
2037 GPM
* Condition
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
Excessive vibration?
Excessive noise?
Excessive corrosion?
Excessive leaks?
Running hot?
Capable of running when inspected?
Support equipment functional?
Equipment or parts missing?
Parts for maintenance available?
Adequate for intended purpose?
Motor amps within rating?
Piping
No
No
No
No
No
Yes
Yes
No
Yes
Yes
Yes
Excessive corrosion?
Excessive leaks?
Paint in good condition?
Supports in good condition?
No
No
Yes
Yes
09/23/2025
C5 Page 687 of 1112

Facility / System Condition Assessment Form
Facility:

Process:

Component:

Item No./Asset ID:

Discipline: Structural
Buena Creek Pump Station

BUILDING - BUENA CREEK PUMP STATION
83 BLD-11000-000
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
2 2002
50 Date of Inspection 7/28/2015
Assessed By RG
Photo #
Component Information Tab
Comments

1. Water leaking from west wall penetraion close to
mechanical duct; groundwater can be seen dripping'

2. Evidence of past leak at bottom of wet well (12"
wall at north); evidence of water leak at bottom
of east wall as well
Structural

3. Evidence of past leak and calcium seen on south
wall near stair entrance. Seems like it was patched
before with plaster concrete

4. Evidence of leak at bottom of south wall

5. Crack in overhead slab at south-west corner

6. Small hairline cracks on walls, appear to be minor
non-structural cracks.

7. Patch on south wall was done during first year of
construction due to leak issues. Since then it does
seem like leak occurred at crack in the past.

8. Seal the leak on west wall to stop water infiltration into the room. * Condition / Level of Service
1 -Very Good
2 -Minor Defects
3 -Requires Significant Maintenance
4 -Requires Rehabilitation
5 -Requires Replacement (> 50%)
0 -Non -Existent
Spalling concrete?
Visible rebar?
Excessive corrosion to structure?
Excessive corrosion to members?
Corrosion coating intact & in place?
Visible structural deformations?
Foundation settling evident?
Major cracks?
Evidence of tank leakage?
Joint sealant replacement?
Damaged members?
No
No
No
No
Yes
No
No
No
Yes
Yes
No
09/23/2025
C5 Page 688 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Process:

Component: BUILDING - WET WELL
Item No./Asset ID:

Discipline: Structural
84 WET WELL
Main Tab
Level of Service* 4
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
2002
50 Component Information Tab
Comments Structural
PVC liner known to be failing; will be replaced in
Date of Inspection 7/28/2015
Assessed By JW
Photo #
an upcoming project.

Concrete not visible
Grinders look ok
Stainless gates look ok
* Condition / Level of Service
1 -Very Good
2 -Minor Defects
3 -Requires Significant Maintenance
4 -Requires Rehabilitation
5 -Requires Replacement (> 50%)
0 -Non -Existent
Spalling concrete?
Visible rebar?
Excessive corrosion to structure?
Excessive corrosion to members?
Corrosion coating intact & in place?
Visible structural deformations?
Foundation settling evident?
Major cracks?
Evidence of tank leakage?
Joint sealant replacement?
Damaged members?
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
09/23/2025
C5 Page 689 of 1112

Facility / System Condition Assessment Form
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Component:

Item No./Asset ID:

Discipline: Structural
Buena Creek Pump Station

BASIN - OVERFLOW
54 BASIN
2 2002
50 Component Information Tab
Comments Structural
Abandoned Shadkowridge pump vault used for
emergency storage; 50K gal capacity
Unlined vault
Date of Inspection 7/28/2015
Assessed By JW
Photo #
Small sump for pump back to wet well
No major issues
* Condition / Level of Service
1 -Very Good
2 -Minor Defects
3 -Requires Significant Maintenance
4 -Requires Rehabilitation
5 -Requires Replacement (> 50%)
0 -Non -Existent
Spalling concrete?
Visible rebar?
Excessive corrosion to structure?
Excessive corrosion to members?
Corrosion coating intact & in place?
Visible structural deformations?
Foundation settling evident?
Major cracks?
Evidence of tank leakage?
Joint sealant replacement?
Damaged members?
No
No
No
No
N/A
No
No
No
No
No
No
09/23/2025
C5 Page 690 of 1112

Facility / System Condition Assessment Form
Facility:

Process:

Component:

Item No./Asset ID:

Discipline: Structural
Buena Creek Pump Station
FENCE - 8' HIGH CHAIN LINK
I 53 FENCE
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

RG-1; JW/RLG-4
2002
20 Date of Inspection 7/28/2015
Assessed By RG &JW/RLG
Photo #
Component Information Tab
Comments
JW/RLG: fence too short
Structural
* Condition / Level of Service
1 -Very Good
2 -Minor Defects
3 -Requires Significant Maintenance
4 -Requires Rehabilitation
5 -Requires Replacement (> 50%)
0 -Non -Existent
Spalling concrete?
Visible rebar?
Excessive corrosion to structure?
Excessive corrosion to members?
Corrosion coating intact & in place?
Visible structural deformations?
Foundation settling evident?
Major cracks?
Evidence of tank leakage?
Joint sealant replacement?
Damaged members?
No
N/A
No
No
Yes
No
No
No
N/A
N/A
No
09/23/2025
C5 Page 691 of 1112

Facility / System Condition Assessment Form
Facility:

Process:

Component:

Item No./Asset ID: 52
Buena Creek Pump Station

PAVEMENT - AC
Discipline: Structural
19 Main Tab
Level of Service* RG-2; JW/RLG-5
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
2002
20 Date of Inspection 7/28/2015
Assessed By RG &JW/RLG
Photo #
Component Information Tab
Comments Structural
RG: Pavement has relatively large cracks on surface
JW/RLG: Asphalt needs resurfacing due to extensive
cracking
* Condition / Level of Service
1 -Very Good
2 -Minor Defects
3 -Requires Significant Maintenance
4 -Requires Rehabilitation
5 -Requires Replacement (> 50%)
0 -Non -Existent
Spalling concrete?
Visible rebar?
Excessive corrosion to structure?
Excessive corrosion to members?
Corrosion coating intact & in place?
Visible structural deformations?
Foundation settling evident?
Major cracks?
Evidence of tank leakage?
Joint sealant replacement?
Damaged members?
N/A
N/A
N/A
N/A
N/A
N/A
No
Yes
N/A
N/A
N/A
09/23/2025
C5 Page 692 of 1112

Facility / System Condition Assessment Form
Facility:

Process:

Component:

Buena Creek Pump Station
MOTOR - #1 SEWAGE PUMP
Item No./Asset ID:
2 M-11010-000
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Licoln Motors
2002
10 Component Information Tab
Comments Electrical
Minor corrosion on suction side diaphram seal.

Date of Inspection 7/28/2015
Assessed By TH/AM
Photo # 3003-3022
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
Yes
Yes
Yes
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 693 of 1112

Facility / System Condition Assessment Form
Facility:

Process:

Component:

Buena Creek Pump Station
MOTOR - #2 SEWAGE PUMP
Item No./Asset ID:
3 M-11020-000
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Licoln Motors
2002
10 Component Information Tab
Comments Electrical
Minor corrosion on suction side diaphram seal.

Date of Inspection 7/28/2015
Assessed By TH/AM
Photo # 3023-3045
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
Yes
Yes
Yes
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 694 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Process:

Component:

MOTOR - #3 SEWAGE PUMP
Item No./Asset ID:
4 M-11030-000
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Licoln Motors
2002
10 Component Information Tab
Comments Electrical
Minor corrosion on suction side diaphram seal.

Date of Inspection 7/28/2015
Assessed By TH/AM
Photo # 3046-3067
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
Yes
Yes
Yes
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 695 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Process:

Component:

MOTOR - #4 SEWAGE PUMP
Item No./Asset ID:
5 M-11040-000
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Licoln Motors
2002
10 Component Information Tab
Comments Electrical
Minor corrosion on suction side diaphram seal.

Date of Inspection 7/28/2015
Assessed By TH/AM
Photo # 3068-3089
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
Yes
Yes
Yes
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 696 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Process:

Component:

MOTOR - #5 SEWAGE PUMP
Item No./Asset ID:
6 M-11050-000
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Licoln Motors
2002
10 Component Information Tab
Comments Electrical
Minor corrosion on suction side diaphram seal.

Date of Inspection 7/28/2015
Assessed By TH/AM
Photo # 3090-3109
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
Yes
Yes
Yes
* Condition / Level of Service
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 697 of 1112

Facility / System Condition Assessment Form
Facility:

Process:

Component:

Buena Creek Pump Station
FLOW METER - ENCINA FORCEMAIN 14"
Item No./Asset ID:
16 FE -11020-000
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):
2002
10 Component Information Tab
Comments Electrical
Date of Inspection 7/28/2015
Assessed By TH/AM
Photo # 313-3121
Excessive corrosion? No
Clean, well maintained contacts? N/A
Parts available for maintenance? Yes
Supports in good condition? Yes
Instrumentation
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 698 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Process:

Component:

VFD - #2, SEWAGE PUMP BCPS
Item No./Asset ID:
66 VFD-11020-000
Discipline: Electrical and Instrumentation
5 Allen-Bradley
2002
10 Component Information Tab
Comments Electrical
VFD's are obsolete and will be replaced as part
Date of Inspection 7/28/2015
Assessed By TH/AM
Photo # 2977-2980
of current project.

Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
N/A
Yes
Yes
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 699 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Process:

Component:

VFD - #3, SEWAGE PUMP BCPS
Item No./Asset ID:
67 VFD-11030-000
Discipline: Electrical and Instrumentation
5 Allen-Bradley
2002
10 Component Information Tab
Comments Electrical
VFD's are obsolete and will be replaced as part
Date of Inspection 7/28/2015
Assessed By TH/AM
Photo # 2973-2976
of current project.

Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
N/A
Yes
Yes
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 700 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Process:

Component:

VFD - #4, SEWAGE PUMP BCPS
Item No./Asset ID:
68 VFD-11040-000
Discipline: Electrical and Instrumentation
5 Allen-Bradley
2002
10 Component Information Tab
Comments Electrical
VFD's are obsolete and will be replaced as part
Date of Inspection 7/28/2015
Assessed By TH/AM
Photo # 2970-2972
of current project.

Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
N/A
Yes
Yes
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 701 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Process:

Component:

VFD - #5, SEWAGE PUMP BCPS
Item No./Asset ID:
69 VFD-11050-
000
Discipline: Electrical and Instrumentation
5 Allen-Bradley
2002
10 Component Information Tab
Comments Electrical
VFD's are obsolete and will be replaced as part
Date of Inspection 7/28/2015
Assessed By TH/AM
Photo # 2965-2969
of current project.

Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
N/A
Yes
Yes
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 702 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Process:

Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Component:

Item No./Asset ID:

GAS ANALYZER DRY WELL
14 AE -11010-000
Discipline: Electrical and Instrumentation
1 MSA
2002
Date of Inspection 7/28/2015
Assessed By TH/AM
2006 Photo # 3126-3131
10 Component Information Tab
Comments
This 1 panel used for both dry well and wetwell.

Electrical
Using a manual 3 -way valve to switch between
wetwell and dry well air samples.

Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
N/A
Yes
N/A
* Condition / Level of Service
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
Yes
Yes
No
Yes
09/23/2025
C5 Page 703 of 1112

Facility / System Condition Assessment Form
Facility:

Process:

Component:

Buena Creek Pump Station

CONTROL PANEL - PLC (BCPS)
Item No./Asset ID:
70 PNL-11000-000
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 4 Date of Inspection 7/28/2015
Manufacturer Allen-Bradley
Model 5/40C Assessed By TH/AM
Year Installed 2002
Year Refurbished/Replaced Photo # 3145-3176
Nominal Useful Life (years): 15
Component Information Tab
Comments
PLC to be replaced.

Electrical
Client wants hard -wired data link type connection
between PLC and flow meter.

Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
Yes
Yes
Yes
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 704 of 1112

Facility / System Condition Assessment Form
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Component:

Buena Creek Pump Station
EMERGENCY STANDBY GENERATOR / 500 KW
Item No./Asset ID:
77 G-11000-000
Discipline: Electrical and Instrumentation
1 Kohler Power Systems
2002
20 Component Information Tab
Comments
Minor corrosion on exhaust silencers.

Electrical
Date of Inspection 7/28/15
Assessed By TH/AM
Photo # 2900-2916
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
Yes
Yes
Yes
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
Yes
Yes
No
Yes
09/23/2025
C5 Page 705 of 1112

Facility / System Condition Assessment Form
Facility:

Process:

Component:

Buena Creek Pump Station

MOTOR CONTROL PANEL
Item No./Asset ID:
1 MCC -11000-000
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer Allen-Bradley
Date of Inspection 7/28/15
Model Centerline Assessed By TH/AM
Year Installed 2002
Year Refurbished/Replaced Photo # 2945-3002
Nominal Useful Life (years): 40
Component Information Tab
Comments Electrical
VFD's are obsolete and will be replaced as part
of current project.

Excessive corrosion? No
Clean, well maintained contacts? N/A
Parts available for maintenance? Yes
Supports in good condition? Yes
Instrumentation
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 706 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Process:

Component: Exterior Lighting
Item No./Asset ID:

N/A
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Component Information Tab
Comments Electrical
Date of Inspection 7/28/15
Assessed By TH/AM
Photo # 2927-2933
The lights on the west side of the building will be Excessive corrosion? No replaced by Encina maintenance. Clean, well maintained contacts? N/A Parts available for maintenance? Yes
Supports in good condition? Yes
Instrumentation
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? N/A
Alarms functional? N/A
Equipment or missing parts? N/A
Parts available for maintenance? N/A
09/23/2025
C5 Page 707 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Process:

Component: Force Main Flow Meter (ShadowRidge)
Item No./Asset ID:

N/A
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Component Information Tab
Comments Electrical
Date of Inspection 7/28/15
Assessed By TH/AM
Photo # 3122-3125
Excessive corrosion? No
Clean, well maintained contacts? N/A
Parts available for maintenance? Yes
Supports in good condition? Yes
Instrumentation
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 708 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Process:

Component: Grinders
Item No./Asset ID:

N/A
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Component Information Tab
Comments Electrical
Date of Inspection 7/28/15
Assessed By TH/AM
Photo # 3138-3144
Excessive corrosion? No
Clean, well maintained contacts? N/A
Parts available for maintenance? Yes
Supports in good condition? N/A
Instrumentation
* Condition / Level of Service
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 709 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Process:

Component: Return Pump
Item No./Asset ID:

N/A
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Component Information Tab
Comments
Replace pilot lights.

Electrical
Date of Inspection 7/28/15
Assessed By TH/AM
Photo # 3177-3180
Excessive corrosion? No
Clean, well maintained contacts? N/A
Parts available for maintenance? Yes
Supports in good condition? Yes
Instrumentation
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 710 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Process:

Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Component:

VFD - #1, SEWAGE PUMP BCPS
Item No./Asset ID:
65 VFD-11010-000
Discipline: Electrical and Instrumentation
5 Allen-Bradley
2002
10 Component Information Tab
Comments Electrical
VFD's are obsolete and will be replaced as part
Date of Inspection 7/28/2015
Assessed By TH/AM
Photo # 2981-2984
of current project.

Excessive corrosion? No
Clean, well maintained contacts? N/A
Parts available for maintenance? Yes
Supports in good condition? Yes
Instrumentation
* Condition / Level of Service
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 711 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Process:

Component:

AUTOMATIC TRANSFER SWITCH
Item No./Asset ID:
64 ATS-11000-000
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer Allen-Bradley
Date of Inspection 7/28/2015
Model Mx 200 Assessed By TH/AM
Year Installed 2002
Year Refurbished/Replaced 2007 Photo # 2945-2947
Nominal Useful Life (years): 15
Component Information Tab
Comments Electrical
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
N/A
Yes
Yes
* Condition / Level of Service
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 712 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Process:

Component: Service Entrance
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Item No./Asset ID:

N/A
Discipline: Electrical and Instrumentation
1 GE
Component Information Tab
Comments
Very minor corrosion on exterior of enclosure.

Electrical
Date of Inspection 7/28/2015
Assessed By TH/AM
Photo # 2894-2899
2917-2926
Challenging access, recommend installing
staircase.

Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
N/A
Yes
Yes
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
N/A
N/A
N/A
N/A
09/23/2025
C5 Page 713 of 1112

Facility / System Condition Assessment Form
Main Tab
Level of Service*
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Facility:

Process:

Buena Creek Pump Station
Component: Interior Lighting
Item No./Asset ID:

N/A
Discipline: Electrical and Instrumentation
1 Component Information Tab
Comments
No reported or observed issues.

Electrical
Date of Inspection 7/28/2015
Assessed By TH/AM
Photo # 2934-2944
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
N/A
Yes
Yes
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning?
Alarms functional?
Equipment or missing parts?
Parts available for maintenance?
N/A
N/A
N/A
N/A
09/23/2025
C5 Page 714 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Process:

Component: Blower Motor High Water Floats
Item No./Asset ID:

N/A
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Component Information Tab
Comments Electrical
Date of Inspection 7/28/2015
Assessed By TH/AM
Photo # 3110-3112
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
N/A
Yes
N/A
* Condition / Level of Service
1 - Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 715 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Process:

Component: Air Compressor
Item No./Asset ID:

N/A
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Component Information Tab
Comments Electrical
Date of Inspection 7/28/2015
Assessed By TH/AM
Photo # 3132-3137
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
N/A
Yes
N/A
* Condition / Level of Service
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 716 of 1112

Facility / System Condition Assessment Form
Facility: Buena Creek Pump Station
Process:

Component: Odor Control Blower Control Panel
Item No./Asset ID:

N/A
Discipline: Electrical and Instrumentation
Main Tab
Level of Service* 1
Manufacturer
Model
Year Installed
Year Refurbished/Replaced
Nominal Useful Life (years):

Component Information Tab
Comments Electrical
Replace pilot lights.

Date of Inspection 7/28/2015
Assessed By TH/AM
Photo # 3181-3184
Excessive corrosion?
Clean, well maintained contacts?
Parts available for maintenance?
Supports in good condition?
Instrumentation
No
N/A
Yes
Yes
* Condition / Level of Service
1- Very Good
2 - Minor Defects
3 - Requires Significant Maintenance
4 - Requires Rehabilitation
5 - Requires Replacement (> 50%)
0 - Non -Existent
All critical indications functioning? Yes
Alarms functional? Yes
Equipment or missing parts? No
Parts available for maintenance? Yes
09/23/2025
C5 Page 717 of 1112

09/23/2025
C5 Page 718 of 1112

PUMP STATION REHABILITATION STUDY I CITY OF VISTA
Appendix E

V&A CONSULTING ENGINEERS PUMP STATION

CONDITION ASSESSMENTS DRAFT REPORT
FINAL i AUGUST2016
09/23/2025
C5 Page 719 of 1112

09/23/2025
C5 Page 720 of 1112

CITY OF VISTA, CALIFORNIA

PUMP STATION CONDITION ASSESSMENTS

DRAFT REPORT
Prepared for:

Carollo Engineers, Inc.
5075 Shoreham Place
Suite 120
San Diego, CA 92122
Date: March 2016
Prepared by:
! V&A
V&A Project No. 15-0024
09/23/2025
C5 Page 721 of 1112

09/23/2025
C5 Page 722 of 1112

TABLE OF CONTENTS
ES EXECUTIVE SUMMARY 1
Actions carried out on September 9, 10, and 11, 2015• 1 Actions carried out on January 12, 2016• 1

1.0 INTRODUCTION 6

2.0 ASSESSMENT APPROACH 8

2.1 Access 8

2.2 Visual Assessment 8

2.3 Ultrasonic Thickness Testing 9

2.3.1 Wall Thickness Loss Analysis 9

2.4 Pit Depth Measurements 10

2.5 Vibration Analysis 10

2.6 In -Situ Soil Resistivity 11

2.6.1 Wenner Four -Electrode Method: General Information 11

2.6.2 Soil Resistivity Calculation - to Depth 12

2.6.3 Soil Resistivity Calculation - per Layer (Barnes Method) 13

2.7 Soil Sample Analysis 14

2.7.1 Resistivity 14

2.7.2 Bicarbonate Ions 14

2.7.3 Chloride Ions 15

2.7.4 Sulfate Ions 15

2.7.5 Soil pH 15

2.8 VANDA® Metal Condition Index 16

2.9 VANDA® Concrete Condition Index 17

3.0 BUENA CREEK PUMP STATION AND PIPELINES 18

3.1 Dry Well Visual Assessment 18

3.2 Ultrasonic Thickness Measurements 22

3.3 Vibration Analysis Results 23

3.4 In -situ Soil Resistivity Results 23

3.5 Soil Sample Analysis Results 25

3.6 Conclusions 26

3.7 Recommendations 27

4.0 BUENA VISTA PUMP STATION 28
V&A Project No. 15-0024
09/23/2025
Table of Contents IMBP
C5 Page 723 of 1112

V&A
City of Vista, California
Pump Station Condition Assessments Draft Report

4.1 Dry Well Visual Assessment 28

4.2 Meter Vault Visual Assessments 32

4.3 Ultrasonic Thickness Measurements 35

4.4 Vibration Analysis Results 36

4.5 Conclusions 37

4.6 Recommendations 38

5.0 RACEWAY PUMP STATION 40

5.1 Visual Assessment 40

5.2 Ultrasonic Thickness Measurements 41

5.3 Conclusions 42

5.4 Recommendations 43
APPENDIX A. REED ELECTRIC & FIELD SERVICES VIBRATION ANALYSIS REPORT 1 APPENDIX B. IN -SITU SOIL RESISTIVITY COMPLETE RESULTS 1 APPENDIX C. PROJECT X CORROSION ENGINEERING SOIL ANALYSIS REPORT 1 TABLES
Table ES -1. Buena Creek Pump Station Assessment Summary 2 Table ES -2. Buena Vista Pump Station Assessment Summary 3 Table ES -3. Raceway Pump Station Assessment Summary 5
Table 2-1. Effect of Resistivity on Soil Corrosivity 14 Table 2-2. Effect of Chloride Ions on Soil Corrosivity 15 Table 2-3. Effect of Sulfate Ions on Soil Corrosivity 15 Table 2-4. Effect of pH on Soil Corrosivity 16
Table 2-5. VANDA® Metal Condition Index 16
Table 2-6. VANDA® Concrete Condition Index 17
Table 3-1. Buena Creek Pump Station Ultrasonic Thickness Data Summary 22 Table 3-2. Buena Creek Pump Station Vibration Analysis Results 23 Table 3-3. Summary of In -Situ Soil Resistivity Test Results 24 Table 3-4. Summary of Laboratory Soil Analysis Results 26 Table 4-1. Buena Vista Pump Station Ultrasonic Thickness Data Summary 36 Table 4-2. Buena Vista Pump Station Vibration Analysis Summary 37 Table 5-1. Raceway Pump Station Ultrasonic Thickness Data Summary 42 V&A Project No. 15-0024
09/23/2025
Table of Contents
It
C5 Page 724 of 1112

• V&A
City of Vista, California
Pump Station Condition Assessments Draft Report

FIGURES
Figure 1-1. Aerial Map Showing Locations of the Buena Creek, Buena Vista, and Raceway Pump Stations 6
Figure 2-1. Standard Pit Depth Gage 10
Figure 2-2. Typical Reed Electric Vibration Test Monitoring Sites on Pump Motors 11 Figure 2-3. Wenner 4 -Electrode Method Schematic 12
Figure 3-1. Soil Resistivity Testing Site Plan 24
Figure 3-2 Excavation Location Site Plan 25
V&A Project No. 15-0024
09/23/2025
Table of Contents
C5 Page 725 of 1112

09/23/2025
C5 Page 726 of 1112

ES

EXECUTIVE SUMMARY
V&A Consulting Engineers, Inc. (V&A) was retained by Carollo Engineers, Inc. (Carollo) to conduct a condition assessment of the Buena Vista Pump Station (BVPS), the Buena Creek Pump Station (BCPS), and the Raceway Pump Station (RPS). These stations are owned by the City of Vista and Buena Sanitation District, and operated by the Encina Wastewater Authority. The intent of the assessments are to assist in preparing Preliminary Design Reports for the three pump stations which will outline capital projects and plan budgets for future fiscal years. Concrete surfaces, piping, motors, and pumps were evaluated in each of the three pump stations. The assessment methods used to assess these features are as follows:

Actions carried out on September 9, 10, and 11, 2015:
• Visual evaluation of the concrete surfaces and metal piping and appurtenances in the BCPS and BVPS dry wells using digital photographs to document notable observations. • Visual evaluation of coatings on concrete and metal structures • Pit depth measurement on corroded metallic surfaces in the BCPS and BVPS dry wells and on above grade RPS piping.
• Pipe wall thickness measurements using an ultrasonic testing gage for dry well piping in the BCPS and BVPS dry wells, and on above grade piping at the RPS. • Rating the evaluated concrete and metal surfaces using the VANDA® Concrete and Metal Condition Index
• Motor and pump vibration analysis by Reed Electric at BCPS and BVPS Actions carried out on January 12, 2016:
• In -situ soil resistivity testing along the 16 -inch diameter force main and 14 -inch diameter excess effluent pipeline alignments for the BCPS. Cursory foreign utility investigation along both ductile iron pipelines (DIPs) for potential cathodically protected structures. After potholing over the pipeline, collected three soil samples at pipe depth for corrosivity analysis.

Soil samples were laboratory tested for as -received and saturated (minimum) soil resistivity, pH, and soluble chloride, sulfate, and bicarbonate ion concentrations.

V&A Project No. 15-0024
09/23/2025
C5 Page 727 of 1112

• V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Conclusions and recommendations based on the results of the assessments are presented in Table ES -1 through Table ES -3:

Table ES -1. Buena Creek Pump Station Assessment Summary Conclusion
Recommendation
Implementation
Timeframe (years)
The evaluated concrete surfaces are in
good condition. However, there was
evidence of infiltration at the pipe
penetrations and on the south wall of the
dry well.

Metal surfaces are in good condition with
the majority of the coating (about 90%)
intact. There is some copper piping that is
significantly corroded.

The evidence of groundwater infiltration on
the concrete walls and the corrosive soil
environment the pump station is located in
warrant additional testing in the concrete
pump room.

Repair damaged coating on mechanical
equipment and piping as needed. Clean
the surfaces of the copper piping and
determine if the replacement of copper
piping is warranted.
0 to 2
3 to 5
At most of the testing locations, the
ductile iron pipe is in good condition.

There were a few locations that showed
wall thickness outside the manufacturing
tolerances by what is considered a minor
degree. No significant exterior corrosion
or leaks were observed on the rest of the
piping in the dry well, which was outside
the ultrasonic testing areas.

Routine assessment.
5 to 10
The inverted pendulum arrangement of
the motor and pumps appears to be a
significant issue with respect to seismic
loading.

Evaluate the seismic vulnerability of the
motor and pump arrangement.

O to 2
Vibration levels are high on most motor
and pump test locations, with many
exceeding ISO and Hydraulic Institute
acceptance standards for operating
levels.

Reed Electric recommended additional
testing during the next planned outage.

O to 2
The buried excess effluent and force main
ductile iron pipes are within a moderately
to very highly corrosive soil environment.

Consider cathodic protection for buried
metal piping if it is to remain in service for
the next 20 years. If a new pipeline is to be
installed, alternative materials to metal or
concrete, such as plastic, should be
considered.

As Appropriate
V&A Project No. 15-0024
09/23/2025
Executive Summary
C5 Page 728 of 1112

• V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Table ES -2. Buena Vista Pump Station Assessment Summary Conclusion
Recommendation
In general, the concrete interior surfaces
of the dry well were in good condition.

There were, however, some isolated areas
of groundwater infiltration, some with
staining indicating possible corrosion of
the reinforcing steel. The grout pads
under the pump bases showed
deterioration at the edges in some cases.

Monitor areas of infiltration within the dry
well for increased evidence of infiltration or
corrosion staining. Consider further
evaluation of the concrete and reinforcing
steel in areas where there is corrosion
staining.
mplementation
imeframe (years)
O to 2
The coating on the piping was generally in
good condition at higher elevations, with
numerous chips and other defects in the
coating at lower elevations. Generally,
there was minor surface corrosion where
the coating was damaged. There was also
one spool downstream of Pumps 1 and 2
that exhibited moderate external
corrosion.

Repair damaged coating on mechanical
equipment and piping as needed.

O to 2
At most of the ultrasonic thickness testing
locations, the dry well piping is in good
condition, but there was one location on
the header downstream of Pumps 1 and 2
that exhibited a significant thickness loss
of 37%. This location also exhibited
external corrosion. It is possible, though
considered unlikely, that the pipe at this
location was manufactured thinner than
required by AWWA standards. No
significant exterior corrosion or leaks were
observed on the rest of the piping in the
dry well, which was outside the ultrasonic
testing areas.

Calculate the minimum required thickness
for the piping based on pressure, loading,
etc. Compare the minimum required
thickness against the measured
thicknesses in this report to determine the
amount of further wall loss that can be
tolerated, if any, before the integrity of the
piping is impaired. With the results of this
analysis in mind, consider activities to
address corrosion and integrity of the dry
well piping:
3 to 5
The bathroom drain piping and ventilation Repair the bathroom drain piping and ducting exhibited various moderate -
severity defects. ventilation ducting connections.
0 to 2
The meter vaults show moderate to
extensive groundwater infiltration, with
staining that indicates possible corrosion
of the reinforcing steel. The vaults are
only a few years old. The extent of staining
may indicate that the water leaking into
the vaults is brackish, which would
promote corrosion.

Perform testing to quantify the extent of
degradation of the concrete and
reinforcement in the two meter vaults.

Testing to consider is similar to that
recommended for the dry well. Sample the
water entering the vaults for resistivity and
chloride content.
0 to 2
V&A Project No. 15-0024
09/23/2025
Executive Summary
C5 Page 729 of 1112

V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Conclusion
The piping, pipe supports, sump pump
fittings, and electrical items within the
meter vaults also showed various defects
that appear to be related to the
groundwater infiltration, particularly if it is
brackish.

Recommendation
i

1. Address the electrical connections
within the meter vaults (meter
ground cables and power for
sump pump). Replace corroded
connectors with corrosion -
resistant materials and take
precautions for galvanic corrosion
between dissimilar metals.

2. Replace the cam -lock fittings for
the sump pump in the south
meter vault.

3. Assuming that the groundwater
entering the meter vaults is
brackish, use materials and
coatings suitable for a marine
environment for all items within
the vaults.

4. Consider whether the groundwater
may also be aggressive to the
buried DIP force mains within the
pump station site, review the
construction details for the force
mains to determine whether
adequate corrosion protection
was provided for the buried pipe.

Consider conducting field
evaluations to determine the
corrosivity of the soil and/or the
condition of the buried DIP.
mplementation
imeframe (years)
3 to 5
Reed Electric identified several minor- to
moderate -severity vibration issues and
recommended that these be addressed
during the next planned outage
Reed Electric recommended additional
testing during the next planned outage.
0 to 2
V&A Project No. 15-0024
09/23/2025
Executive Summary
C5 Page 730 of 1112

:� V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Table ES -3. Raceway Pump Station Assessment Summary
Conclusion
Recommendation
Implementation
Timeframe (years)
There is potential infiltration/exfiltration
at cracks in the concrete reservoir. The
concrete surface is in good condition
though. The concrete has spalled at the
base of the guardrail around the concrete
reservoir due to a lack of insulation
between the aluminum and concrete
material.

Seal points of infiltration/exfiltration within
the concrete reservoir Install a grout or
sealant at the base of the aluminum posts
and slope it so that water runoff is allowed
to flow away from the embedded section.
3 to 5
The coating on the electrical box supports
has failed and the concrete is damaged at
the base. There is corrosion staining on
the electrical box and conduits.

Replace corroded conduits. Recoat
electrical equipment as needed.
3 to 5
The surface of the piping is in good
condition, with the majority of the coating
(about 90%) intact. The coating on the
flange near the Pump 3 discharge pipe
has failed though, leading to the exposed
metal surface to have moderate
corrosion.

Recoat piping and associated equipment
as needed.
3 to 5
At most of the testing locations, the pipe
and fittings are in good condition. There
were a few locations that showed wall
thickness outside the manufacturing
tolerances by what is considered a minor
degree. The pipe spools that showed this
increased wall thickness loss were
assumed to have been manufactured
thicker than Class 53 (minimum required
for flanged DIP per AWWA C115). Overall,
while there may have been a minor
thickness loss at a few locations, it does
not appear to have been to a significant
degree.

Recoat or replace the corroded metal
flange near the Pump 3 discharge pipe.
3 to 5
V&A Project No. 15-0024
09/23/2025
Executive Summary
C5 Page 731 of 1112

1.O INTRODUCTION
V&A Consulting Engineers, Inc. (V&A) was retained by Carollo Engineers, Inc. (Carollo) to conduct a condition assessment of three pump stations for the City of Vista (City) and the Buena Sanitation District (District). The pump stations of interest are the Buena Vista Pump Station (BVPS), the Buena Creek Pump Station (BCPS), and the Raceway Pump Station (RPS). The BVPS is located in Carlsbad, California, and the BCPS and the RPS are located in Vista, California. These pump stations are part of four pump stations that convey water to the Encina Wastewater Authority's (EWA) Water Pollution Control Facility. The EWA operates these pump stations for the City and the District. The BVPS and RPS are in the City service area, and the BCPS is in the District service area. Figure 1-1 is an aerial view of the pump station locations.

Figure 1-1. Aerial Map Showing Locations of the
Buena Creek, Buena Vista, and Raceway Pump Stations
V&A Project No. 15-0024
09/23/2025
Introduction 6
C5 Page 732 of 1112

6 A V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
The City and District wish to assess the condition of assets in the wastewater conveyance system for rehabilitation planning and providing the necessary upgrades to improve the safety, reliability, and efficiency of the stations, and meet current applicable treatment codes, standards, and guidelines.

V&A's assessments are intended to provide information to assist Carollo in preparing Preliminary Design Reports for the three pump stations. The assessment consisted of the following actions, which were carried out between September 2015 and January 2016:
• Visual evaluation of the concrete surfaces and metal piping and appurtenances in the BCPS and BVPS dry wells using digital photographs to document notable observations. • Visual evaluation of coatings on concrete and metal structures • Pit depth measurement on corroded metallic surfaces in the BCPS and BVPS dry wells and on above grade RPS piping.
• Pipe wall thickness measurements using an ultrasonic testing gage for dry well piping in the BCPS and BVPS dry wells, and on above grade piping at the RPS. • Rating the evaluated concrete and metal surfaces using the VANDA® Concrete and Metal Condition Index
• Motor and pump vibration analysis by Reed Electric at BCPS and BVPS • In -situ soil resistivity testing along the 18 -inch diameter force main and 14 -inch diameter excess effluent pipeline alignments for the BCPS. Cursory foreign utility investigation along both ductile iron pipelines for potential cathodically protected structures. After potholing over the pipeline, collect three soil samples at pipe depth for corrosivity analysis. Soil samples were laboratory tested for as -received and saturated (minimum) soil resistivity, pH, and soluble chloride, sulfate, and bicarbonate ion concentrations.

The assessment approach is described in more detail in Section 2.0.

V&A Project No. 15-0024 Introduction
09/23/2025
C5 Page 733 of 1112

2.0 ASSESSMENT APPROACH
V&A uses both qualitative and quantitative means to evaluate structures and their components. The condition assessment utilized the methods and techniques described in this section.

2.1 Access
The dry wells accessed during the assessments are not confined spaces, yet V&A personnel wore 4 - gas monitors as a precautionary measure. Piping and concrete surfaces intended for evaluation were accessible while standing on the dry well floors. A ladder was used when needed to reach and evaluate concrete and metal surfaces. Above grade piping and other components were easy to access on foot and did not require ladders or scaffolding. The assessment team members wore the appropriate personal protective equipment while on -site, which included steel -toed shoes, safety glasses, gloves, and hard hats.
7 2 Visual Assessment
The visual assessment focused on the condition of concrete and metal surfaces. Observations such as exposed aggregate, cracks, and evidence of corrosion were recorded when found, supplemented with digital photographs. Pipeline joints were evaluated for offsets, leaks, gaps, and other notable items if found. It should be noted that the assessment of concrete for this project was limited to a visual evaluation. Physical and quantitative testing was not performed for the concrete surfaces.

V&A Project No. 15-0024
09/23/2025
Assessment Approach
C5 Page 734 of 1112

:� V&A
City of Vista, California
Pump Station Condition Assessments Draft Report

2.3 Ultrasonic Thickness Testing
V&A conducted ultrasonic thickness testing on the piping in the dry wells at the BCPS and BVPS, and on the above -
grade header piping at the RPS. Ultrasonic thickness
testing is a non-destructive evaluation technique that
allows for the determination of metal wall thickness. High - frequency sound waves are transmitted through one side
of a metal wall from a transducer. When sound waves
reach the other side of the metal wall, a fraction of the waves will echo back to the transducer. The metal
thickness is determined by recording the time it takes for the sound wave to travel through the metal and return.

V&A used an Olympus ultrasonic thickness gauge to obtain thickness measurements for the metallic piping (Photo
2-1). Prior to taking measurements, the gauge was
calibrated to the velocity of sound in ductile iron or steel, as appropriate. The type of testing that was conducted is known as A -scan, which gives the wall thickness at a single point at each measurement location. It should be noted
that the wall thickness at other locations may vary. Test locations were chosen to provide a representative
condition of the entire pipe surface. Testing was performed on accessible piping (i.e. able to be reached without a ladder/scaffolding/confined space entry).

2.3.1 Wa11 Thickness Loss Analysis
Photo 2-1. Olympus Ultrasonic
Thickness Gauge
The classes and nominal thicknesses of the pipe and fittings used at the pump stations were unknown. The wall thickness loss was calculated based on the nominal thickness and the associated casting tolerance from the ductile iron pipe (DIP) standards that were assumed to be applicable. The nominal thickness defines each class of pipe or fitting and is used in specifying and ordering. The casting tolerance is a "minus" tolerance given by the applicable standard, allowing the pipe or fitting to be thinner than the nominal thickness at manufacture. If the measured thicknesses are within the casting tolerance, variations in thickness at a given location are not necessarily an indicator of corrosion.

Since the pipe spools that were tested had threaded flanges or grooved ends, they are assumed to have been made from Class 53 ductile iron pipe, or thicker, per the requirements of AWWA C115, "Flanged Ductile -Iron Pipe with Threaded Flanges," and AWWA C606, "Grooved and Shouldered Joints." It should be noted that the piping was not evaluated for pressure or other loading considerations. Higher pressures, for example, could have dictated a need for pipe that was thicker than the minimum class allowed by these standards, which are based on manufacturing considerations.

V&A Project No. 15-0024 Assessment Approach
09/23/2025
C5 Page 735 of 1112

• V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
In addition to the ductile iron pipe spools that were tested, steel rectangular suction lines at the BVPS and ductile iron elbows at the RPS were also tested. The nominal thickness for the steel rectangular components was unknown, so they were assumed to have been fabricated from fractional -inch plate. The nominal thickness and casting tolerance for the ductile iron elbows were taken from AWWA C11O, "Ductile -Iron and Gray -Iron Fittings," for Class 250 ductile iron fittings.

2.4 Pit Depth Measurements
Where pitting was observed on the exterior of
the piping, pit depths were measured using a
handheld pit depth gage (Figure 2-1). The
gage is held in a vertical position above the pit
to be measured with the lower edge flush
against the metal surface. The claw is inserted
into the pit. The pit depth is read on the dial at
the right hand side of the gage.

Vibration Analysis

PIPE PIT GAGE
AAu - 0.00dI . 0•
CURUL • VA*.0
IMAM • lull 1 0. 1
P•C4MAE • !
1 - reel. f1A.11
1 • *Au 1.$aace
0•.Rw.na/
A' • AI[.nAIL
L • LEr41M
A AoOtt 41
cis 161111141IL6-
wn
pn.e.ta a 7.4«53750
grow r . 0x
L IP n+�

40. -'_ =_�
v
r —
e — -
—W
JAI
K
Figure 2-1. Standard Pit Depth Gage
Reed Electric & Field Services was retained to perform vibration tests for the motors and pumps at the BCPS and BVPS. The RPS has submersible pumps, so testing was not performed there. The intent of testing is to screen for maintenance and repair activities. The vibration tests were performed for Pumps and Motors 1, 2, 3, 4, and 5 at the BCPS and the BVPS. Motor 3 at the BCPS experienced Variable Frequency Drive (VFD) or other electrical issues, and the testing was aborted.

A four -channel data recorder and analyzer were used with three magnetic -mount accelerometers and a laser speed tachometer to monitor vibration and motor speeds in revolutions per minute (rpm).

Sensors were mounted as shown in Figure 2-2 on the motor upper bearing, motor lower bearing, pump upper bearing, and pump lower bearing in the in -line, perpendicular, and axial directions.

System control limitations allowed data to be collected only at certain pump speeds for several test points. The following data was recorded for each test performed at both pump stations:

Overall velocity and displacement vibration
Velocity spectrum plots
Filtered amplitude/phase measurements where the tachometer was available The test observations and Reed Electric's recommendations for future monitoring and evaluation are presented in the Findings sections for the BCPS and the BVPS assessments.

V&A Project No. 15-0024 Assessment Approach
09/23/2025
C5 Page 736 of 1112

:: V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Motor
Upper
Motor
Lower
Pump
Upper
Pump
Lower
WPM
iimpnimv
3 measurements taken at each
bearing location
1 In -line with piping
2 Perpendicular to piping (Crossline)
3 Axial (parallel to shaft)
Laser Tachometer monitoring speed
through VFD operating range
Figure 2-2. Typical Reed Electric Vibration Test Monitoring Sites on Pump Motors

2.6 In -Situ Soil Resistivity

2.6.1 Wenner Four -Electrode Method: General Information Understanding how easily current will travel through a medium surrounding a metallic object is important in evaluating the corrosivity of the environment. Resistivity is an inverse measure of the ability of a soil to conduct an electric current, with higher resistivity resulting in a lesser degree of current flow. Corrosion rate depends on current flow between a metal and the adjacent medium.

Normally, the corrosion activity on metals in soil increases as soil resistivity decreases.

Soil resistivity measurements were conducted in accordance with ASTM G57, "Standard Test Method for Field Measurement of Soil Resistivity Using the Wenner Four -Electrode Method." The Wenner method involves the use of four metal electrodes (pins) driven into the ground along a straight line, equidistant from each other, as shown in Figure 2-3. At each of the two excavation locations, soil resistance measurements were recorded at pin spacings of 5, 7.5, 10, 15, and 20 feet.

V&A Project No. 15-0024 Assessment Approach
09/23/2025
C5 Page 737 of 1112

V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
An alternating current from the soil resistance meter causes a current to flow through the soil between the outside pins C1 and C2. The soil resistance creates a voltage gradient, which is proportional to the average resistance of the soil mass to a depth equal to the distance between pins. The voltage drop is then measured across pins P1 and P2, and the soil resistance (in ohms) is calculated by the soil resistance meter. Resistivity of the soil (in ohm -cm) is then computed from the instrument reading using the procedure described in Sections 2.6.2 and 2.6.3.

PIN (TYP OF 4)
C1
P1
C2
P2
C1

CURRENT FLOWS

BETWEEN PINS
C1 AND C2
CLIP (TYP OF 4)

POTENTIAL

MEASURED BETWEEN
PINS P1 AND P2
P1
J
P2

HARNESS
C
SOIL

RESISTANCE
METER

SOIL MASS WITH

RESISTANCE R AND
RESISTIVITY p
FINAL
GRADE
Figure 2-3. Wenner Four -Electrode Method Schematic

2.6.2 Soil Resistivity Calculation — to Depth
In the Wenner four -electrode method, the average resistivity of the soil mass below the pins, to a depth equal to the pin spacing, is calculated with the equation p = 2. n' A' R,
where p = average soil resistivity to a depth of A (ohm -cm), A = distance between electrodes (cm),
R = soil resistance to a depth of A, soil resistance meter reading (ohm), and n = 3.14 (approximately).

V&A Project No. 15-0024 Assessment Approach
09/23/2025
C5 Page 738 of 1112

A V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
The resulting resistivity value represents the average resistivity of the soil below the pins to a depth equal to the pin spacing. This average resistivity value includes the effect of soil layers near the surface. The Barnes layer method, described below in Section 2.6.3, allows the resistivity of each soil layer below grade to be calculated without the effect of shallower layers.

2.6.3 Soil Resistivity Calculation — per Layer (Barnes Method) The Wenner four -electrode method, described above in Sections 2.6.1 and 2.6.2, determines the average soil resistivity from grade to a depth equal to the pin spacing. These results can be expanded using the Barnes layer method to remove the effect of shallower soil layers and arrive at the resistivity of each soil layer individually. For example, the average resistivity of the soil layer between 5 feet and 10 feet deep may be calculated using the four -electrode resistance measurements for the 5- and 10 -foot depths.

The results of the Barnes layer calculations are used to evaluate the corrosivity of the soil in lieu of the average resistivity from grade to a given depth. The Barnes layer method isolates the layer of soil that a particular structure will be in contact with, while neglecting the soil in layers that will not be in contact with the structure. The soil layers that are not in contact with the structure will have little to no effect on the corrosion rate of the structure. Soil corrosivity as a function of soil resistivity is discussed in Section 2.7.

In the Barnes layer method, the soil layer resistance (RA -B) is first calculated using the equation RA -B= (RA •RB) / (RA - RB),
where RA -B = soil layer resistance from depth A to depth B (ohms), RA = soil resistance to depth A, soil resistance meter reading (ohms), and RB = soil resistance to depth B, soil resistance meter reading (ohms).

Next, the average soil layer resistivity (pA-B) is calculated using the equation where
PA-B=2•n•(B-A)•RA-B,
PA -B =
A=
B=
FT =
RA -B =
average resistivity of soil layer between depth A and depth B (ohm -cm), depth below grade to the top of the soil layer (cm),
depth below grade to the bottom of the soil layer (cm),

3.14 (approximately), and
soil layer resistance from depth A to depth B (ohms), as determined above.

V&A Project No. 15-0024 Assessment Approach
09/23/2025
C5 Page 739 of 1112

• V&A
City of Vista, California
Pump Station Condition Assessments Draft Report

2.7 Soil Sample Analysis
A wide variety of water-soluble salts is typically found in soils. Two soils having the same resistivity may have significantly different corrosion characteristics, depending on the specific ions available.

The major constituents which accelerate corrosion are bicarbonate ions, chloride ions, sulfate ions, and the pH (acidity) of the soil. Potholing was performed to collect soil samples near the depth of the pipe invert. These soil samples were sent to a Project X Corrosion Engineering laboratory in Murrieta, California to be tested for resistivity and the major corrosive constituents described below.

2.7.1 Resistivity
The in -situ soil resistivity testing per ASTM G57 discussed in Section 2.6 determines the soil resistivity at several different depths at a point in time. The minimum soil resistivity provides information about the soil during wet -weather conditions.

Soil resistivity is primarily dependent on the ion and moisture content of the soil. Higher levels of ions in the soil lower the soil resistivity. Additional moisture decreases the soil resistivity up to the point where the maximum solubility for the dissolved ionic compounds is achieved. Beyond this point, an increase in moisture increases the resistivity as the ions become more and more diluted. The decrease in soil resistivity is attributed to the presence of ions in the "as -received" soil going into solution and providing a less resistive path for current flow.

The following table correlates resistivity values with degree of corrosivity. The interpretation of corrosivity correlation to soil resistivity varies somewhat among corrosion engineers. However, Table 2-1 is a generally accepted guide and is based upon corrosivity rankings presented in "Corrosion Basics - An Introduction," pg. 191 (1984), published by the National Association of Corrosion Engineers (NACE).

Table 2-1. Effect of Resistivity on Soil Corrosivity
Soil Resistivity
(ohm -cm)
10,000

2.7.2 Bicarbonate Ions
Degree of Corrosivity
Very high
High
Moderate
Mild
Negligible
High concentrations of bicarbonates tend to decrease soil resistivities. Bicarbonates are not directly aggressive to buried metal, but the lower -resistivity environments can promote corrosion activity.

V&A Project No. 15-0024 Assessment Approach
09/23/2025
C5 Page 740 of 1112

:� V&A
City of Vista, California
Pump Station Condition Assessments Draft Report

2.7.3 Chloride Ions
Chloride ions found in soils tend to break down otherwise protective surface deposits and can result in corrosion of buried metallic structures and reinforcing steel in concrete structures. Table 2-2 shows the effect of chloride ions on the corrosivity of the soil. These ranges are generally accepted by the corrosion engineering community.

Table 2-2. Effect of Chloride Ions on Soil Corrosivity
Water-soluble Chloride
Concentration (mg/kg)
> 5,000
1,500 - 5,000
500 - 1,500
100 - 500
2,000
1,000 - 2,000
< 1,000

2.7.5 Soil pH
Very high
Moderate
Negligible
Acidity, as indicated by the pH value, is another important factor of soil with respect to corrosivity.

Lower pH (more acidic) will result in a greater degree of corrosivity with respect to buried metallic and concrete structures. When pH increases above 7.0 (the neutral value), the conditions become increasingly more alkaline. In alkaline environments, steel forms a protective layer on its surface.

This is referred to as passivation. V&A developed Table 2-4, which correlates the effect of pH on the rate of corrosion for buried steel or concrete structures.

V&A Project No. 15-0024 Assessment Approach
09/23/2025
C5 Page 741 of 1112

• V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Table 2-4. Effect of pH on Soil Corrosivity
Soil pH
Degree of Corrosivity

7.5 `L Negligible

2.8 VANDA® Metal Condition Index
The VANDA Metal Condition Index was created by V&A to provide consistent reporting of metal corrosion damage based on qualitative, objective criteria. Condition of corrosion can vary from Level 1 to Level 4 based upon visual observations and field measurements, with Level 1 indicating the best condition and Level 4 indicating severe damage.

Table 2-5. VANDA° Metal Condition Index
Condition
Rating
Description
Representative
Photograph
Little or No Corrosion
• Loss of Wall Thickness %: None
• Pitting Depth (as % of Wall Thickness): None to Minimal • Extent (Area) of Corrosion: None
Level 2
Minor Surface Corrosion
• Loss of Wall Thickness %: 75%
• Pitting Depth (as % of Wall Thickness): 75% or More
• Extent (Area) of Corrosion: Affects Most or All of Surface © 2016 V&A Consulting Engineers, Inc. All rights reserved.

V&A Project No. 15-0024
09/23/2025
Assessment Approach
C5 Page 742 of 1112

:� V&A
City of Vista, California
Pump Station Condition Assessments Draft Report

2.9 VANDA® Concrete Condition Index
The VANDA Concrete Condition Index was created by V&A to provide consistent reporting of corrosion damage based on qualitative, objective criteria. Condition of corrosion can vary from Level 1 to Level 4 based upon visual observations and field measurements, with Level 1 indicating the best condition and Level 4 indicating severe damage.

Table 2-6. VANDA° Concrete Condition Index
Condition
Rating
Description
Representative
Photograph
None/Minimal Damage to Concrete
• Hardness: No Loss
• Surface Profile: No Loss
• Cracking: Shrinkage Cracks
• Spalling: None
• Reinforcing Steel (Rebar): Not Exposed or Damaged
Level 2
Damage to Concrete Mortar
• Hardness: Damage to Concrete Mortar
• Surface Profile: Some Loss
• Cracking: Thumbnail Sized Cracks of Minimal Frequency • Spalling: Shallow Spalling of Minimal Frequency,
Related Rebar Damage
• Reinforcing Steel (Rebar): May Be Exposed but Not Damaged Level 3
Loss of Concrete Mortar/Damage to Rebar
• Hardness: Complete Loss
• Surface Profile: Large Diameter Exposed Aggregate
• Cracking: 1/4 -inch to 1h -inch Cracks, Moderate Frequency • Spalling: Deep Spalling of Moderate Frequency,
Related Rebar Damage
• Reinforcing Steel (Rebar): Exposed and Damaged, Can Be Rehabilitated
Level 4
Rebar Severely Corroded/Significant Damage to Structure • Hardness: Complete Loss
• Surface Profile: Large Diameter Exposed Aggregate
• Cracking: 1/2 -inch Cracks or Greater, High Frequency • Spalling: Deep Spalling at High Frequency, Related Rebar Damage • Reinforcing Steel (Rebar): Damaged or Consumed,
Loss of Structural Integrity
© 2016 V&A Consulting Engineers, Inc. All rights reserved.

V&A Project No. 15-0024
09/23/2025
Assessment Approach
C5 Page 743 of 1112

Photo 3-1. Groundwater leachate deposits
along hairline cracks, south wall.

3.O BUENA CREEK PUMP STATION

AND PIPELINES
The BCPS was constructed circa 2002 and has a capacity of 8.8 million gallons per day (mgd). The collection system for the District culminates at this station, and is conveyed to the Buena outfall and the EWA Water Pollution Control Facility. V&A conducted a visual assessment, ultrasonic thickness testing, in -situ soil resistivity surveys, and soil sampling at the BCPS and along the downstream pipeline alignments. The visual assessment and ultrasonic thickness testing were conducted on September 10, 2015. Reed Electric & Field Service conducted the pump and motor vibration tests on September 10, 2015. The corrosivity of the soil environment that the pump station excess effluent and force main pipelines are buried in was also assessed. This was done by performing in - situ resistivity testing on January 12, 2016, which included a foreign utility investigation and soil sample analysis. The results of these studies are presented below.

Dry Well Visual Assessment
The BCPS has five pumps, each rated 4,500 gallons per minute. Pumps 1 and 2 drain the West Wet Well and Pumps 3, 4, and 5 drain the East Wet Well. The concrete walls, floor, and ceiling of the Pump Room are in good condition. No major spalls or cracks were observed. A few isolated hairline cracks with groundwater leak deposits were seen, predominantly on the south wall. The leachate mineral deposits did not show the brownish staining indicative of reinforcing steel corrosion (Photo 3-1 and Photo 3-2).

Photo 3-2. Groundwater seepage deposits on
Pump Room wall at hairline cracks.

V&A Project No. 15-0024
09/23/2025
Buena Creek Pump Station and Pipelines
C5 Page 744 of 1112

V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
The mounting of the pump motors appears to be a significant issue with respect to seismic loading.

The motors and pumps form an inverted -pendulum arrangement that is only supported by the suction and discharge flanges on each pump (Photo 3-3 and Photo 3-4). It should be noted that the condition assessment did not focus on seismic and structural issues, but this particular issue was apparent based on V&A's experience with other pump stations.

Photo 3-3. Typical pump motor supported by Photo 3-4. Typical pump motor supported by pump volute flanges. pump volute flanges.

A variety of minor defects on equipment in the Pump Room was documented. Minor corrosion staining and hairline cracking was seen on the Pump 3 support pedestal (Photo 3-5). Coating failure and corrosion were observed on a discharge piping support at Pump 4 (Photo 3-6). These features indicate minor leaks from above the support pedestals that collect on flat surfaces.

Photo 3-5. Minor cracks and corrosion Photo 3-6. Coating failure and corrosion on a staining on Pump 3 support pedestal.

Pump 4 discharge piping support.

V&A Project No. 15-0024
09/23/2025
Buena Creek Pump Station and Pipelines
C5 Page 745 of 1112

V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Overall the coatings on the metal piping and appurtenances are intact. Minor coating delaminations were seen, but the exposed metal surfaces, if not directly exposed to water, are not corroded (Photo 3-7 and Photo 3-8).

Photo 3-7. Small coating loss on Pump 1 Photo 3-8. Delaminated coating and exposed, electric motor housing.
uncorroded metal substrate.

Leakage appears to have occurred at a flange bolt on Pump 3, which is evident from and corrosion staining (Photo 3-9). Wall penetrations of pump suction piping for Pumps 2, 3, 4, and 5 have leak stains running down the wall. A representative example from Pump 3 is shown in Photo 3-10.

Photo 3-9. Leak along flange at bolt.

Photo 3-10. Wall staining at Pump 5 suction
pipe at wall penetration.

The only active leak in the Pump Room was on the west wall behind ventilation ducting (Photo 3-11 and Photo 3-12). It may be a supply line to an upstairs bathroom in the Pump Station, and is not associated with the discharge piping and pump systems. A 1 -inch diameter copper pipe extending from ceiling to floor on the west wall a few feet south of the active leak is corroded at a tee fitting adjacent to a grounding cable connection (Photo 3-13). The corroded area was high on the wall and could not be accessed, but appeared to be a connection from a slightly larger pipe entering the wall at this point.

V&A Project No. 15-0024 Buena Creek Pump Station and Pipelines 09/23/2025
C5 Page 746 of 1112

V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Photo 3-11. Active leak along west wall of
Pump Room. Not associated with pump
discharge and suction piping.

Photo 3-13. Corroded copper piping on Pump
Room west wall.

Photo 3-12. Active leak along west wall of
Pump Room. Not associated with pump
discharge and suction piping.

Four of the five galvanized pipe support brackets for the pump discharge piping along the Pump Room walls are loose and are providing little support. The fourth support in the effluent direction was rattling during pump operation and the coating is being damaged from the vibration. Overall, no significant corrosion staining or corrosive exfoliation of piping or appurtenances was observed in the Pump Room.

V&A Project No. 15-0024 Buena Creek Pump Station and Pipelines 09/23/2025
C5 Page 747 of 1112

Pump 1 suction, upstream
• V&A
City of Vista, California
Pump Station Condition Assessments Draft Report

3.2 Ultrasonic Thickness Measurements
The ultrasonic thickness data is summarized in Table 3-1. As shown in the table, the wall thickness loss for the ductile iron pipe and fittings, at the locations that were tested, was mostly within manufacturing tolerances. There were four locations that the wall thickness was outside the tolerances, yet by what is considered a minor degree. The maximum wall thickness loss was calculated to be 19%. However, the wall thickness at these locations was outside the manufacturing tolerances by only 0.014 inches.

Table 3-1. Buena Creek Pump Station Ultrasonic Thickness Data Summary Measured Thickness (in.)
Min.

Avg.
55 Assumed Pipe
Specifications
Nom.

Thick-
ness
(in.)
Cast-
ing
Tol.
(in.)
Max.

Wall
Loss
(in.)
Max.

Wall
Loss
Pump 1 suction, downstream
12 0.440 0.453 0A77

0.46 -0.06 0.020
4%
12 0.365 0.388 0.413 53 0.40 -0.06 0.035 9%
Pump 2 suction, upstream
12 0.521 0.527 0.534 56 0.49 -0.06 (a) (a)
Pump 2 suction, downstream
12 0.326 0.337 0.351 53 0.40 -0.06 0.074 19%
Pump 3 suction, upstream
12 0.388 0.398 0.423 53 0.40 -0.06 0.012 3%
Pump 3 suction, downstream
12 0.357 0.374 0.394 53 0.40 -0.06 0.043 11%
Pump 4 suction, upstream
12 0.344 0.375 0.399 53 0.40 -0.06 0.056 14%
Pump 4 suction, downstream
12 0.359 0.384 0.397 53 0.40 -0.06 0.041 10%
Pump 5 suction, upstream
12 0.326 0.364 0.395 53 0.40 -0.06 0.074 19%
Pump 5 suction, downstream
12 0.342 0.371 0.395 53 0.40 -0.06 0.058 15%
Pump 4 discharge
12 0.352 0.360 0.370 53 0.40 -0.06 0.048 12%
Pump 5 discharge
12 0.337 0.349 0.358 53 0.40 -0.06 0.063 16%
Lower header between Pumps 4 and 5
12 0.409 0.424 0.451 54 0.43 -0.06 0.021 5%
Surge tank riser
12 0.343 0.369 0.394 53 0.40 —0.06 0.057 14%
Force main on S. wall, upstream of meter
14 0.403 0.424 0.438 54 0.45 —0.07 0.047 10%
Force main on S. wall, downstream of meter
14 0.367 0.394 0.420 53 0.42 —0.07 0.053 13%
Flow meter bypass along south wall
14 0.353 0.353 0.353 53 0.42 —0.07 0.067 16%
Lower header between Pumps 3 and 4
24 0.506 0.522 0.536 56 0.56 —0.07 0.054 10%
Lower header between Pumps 2 and 3
24 0.560 0.576 0.645 56 0.56 —0.07 0.000 0%
Lower header between Pumps 1 and 2
24 0.464 0.526 0.557 56 0.56 —0.07 0.096 17%
Lower header west of Pump 1
24 0.515 0.531 0.549 56 0.56 —0.07 0.045 8%
Force main along west wall 24 0.502 0.523 0.543 56 0.56 —0.07 0.058 10% Notes
(a) Measured thickness within manufacturing tolerances or greater than nominal; wall loss not reported.

V&A Project No. 15-0024
09/23/2025
Buena Creek Pump Station and Pipelines
C5 Page 748 of 1112

:� V&A
City of Vista, California
Pump Station Condition Assessments Draft Report

3.3 Vibration Analysis Results
Vibration testing was performed on Motors and Pumps 1, 2, 4, and 5. Pump 3 was not operational and was not tested. The pumps were run between 78 to 87% speed during the test. System control limitations and high cavitation vibration at lower loads dictated that data only be collected at those speeds. General observations of the testing indicate that vibration levels are high on most motor and pump test locations, with many exceeding International Standards Organization (ISO) and Hydraulic Institute acceptance standards for operating levels. The high readings were directional, primarily in the in -line direction on both the motors and the pumps. The highest readings on each pump system were typically in the pump lower bearing area. Predominant vibration frequency peaks were at two times the running speed. Reed theorizes that the stiffness of the pipe and pump supports may have a significant bearing on the severity of vibration. There was no indication of high -frequency mechanical or electrical peaks on any of the test points, indicating that there is minimum hydraulic noise and no apparent VFD issues. A summary of the testing results is presented in Table 3-2. The full report from Reed Electric is attached is Appendix A.

Table 3-2. Buena Creek Pump Station Vibration Analysis Results Motor
Observation
Motor/Pump 1
High directional levels in the inline direction from the motor bearings down to the pump bearings. This motor generally had the highest readings at all test points.

Motor/Pump 2
High directional levels in the inline direction from the motor bearings down to the pump bearings, but at lower levels than Pump 1.

Motor/Pump 3 Not tested.

Motor/Pump 4
Pump bearings showed a higher perpendicular relationship than the other pumps. While performing testing, the suction piping support for Pump 4 was found to be loose.

Motor/Pump 5
Generally comparable or lower levels of vibration compared to the other three pumps that were tested.

3.4 In -situ Soil Resistivity Results
Figure 3-1 shows the locations where soil resistivity testing was performed along the excess effluent and force main pipelines. A summary of the in -situ soil resistivity results is presented in Table 3-3.

The complete list of in -situ soil resistivity results is presented in Appendix B. The "resistivity to depth" at a given test site is the resistivity of the soil mass from grade down to the designated depth. Per Section 2.6, resistivities of 10,000 ohm -cm and greater can be considered negligible with regards to corrosion. The resistivities for the layers down to a depth of 7.5 - 10 feet on average are between 2,766 - 2,696 ohm -cm, with locations as low as 287 ohm -cm. This means the majority of the tested soils along the alignment are moderately to highly corrosive, with areas of very highly corrosive conditions. Per the provided record drawings, the depth of cover for the pipelines ranges from about 5 to 7.5 feet below grade.

V&A Project No. 15-0024 Buena Creek Pump Station and Pipelines 09/23/2025
C5 Page 749 of 1112

:41 V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Legend
:s Excess Effluent
• Feature 1
:+ Force Main
A Foreign Pipeline CPTS
Depth
(feet)
5 7.5
10 15
Figure 3-1. Soil Resistivity Testing Site Plan
Table 3-3. Summary of In -Situ Soil Resistivity Test Results Resistivity to Depth (ohm -cm
Average
3,015
Minimum
335
2,766
287
2,696
2,301
20 1,961
All Depths
2,548
287
259
268
259
Maximum
14,995
11,563
10,208
8,905
8,235
14,995
Layer
(feet)
0-5
5 - 7.5

7.5 - 10
10 - 15
15-20
All Layers
Resistivity of Layer (ohm -cm)
Average
3,015
Minimum
335
Maximum
14,995
2,657
187
10,249
3,075
1,969
2,189
2,581
271
15,052
215
7,170
230
11,462
187
15,052
V&A Project No. 15-0024
09/23/2025
Buena Creek Pump Station and Pipelines
24 C5 Page 750 of 1112

V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Foreign utility investigation revealed a 16 -inch concrete mortar lined and tape wrapped pipeline owned by Olivenhain Water District on Faraday Avenue (as noted on the brass tag at the cathodic protection test station). Based on the type of test station and the results of the potential testing, the pipeline is cathodically protected with a galvanic system. Current output from galvanic anode beds is low compared to that of typical impressed current anode beds, so galvanic systems are not considered to be a risk of interference.

Power utilities are primarily underground along the alignment routes evaluated. High voltage power lines cross the pipeline alignments on Melrose Drive between Sycamore Avenue and Mountain Pass Circle. High voltage alternating current can be reason for concern when power lines parallel buried pipelines for long distances. This short crossing is noted, but is not of concern.

3.5 Soil Sample Analysis Results
The locations of the potholing where soil samples were collected are shown in Figure 3-2. Table 3-4 presents a summary of the laboratory analysis results. Based on the guidelines in Section 2.7 the three soil samples were high to moderately corrosive. Site 3 is the most corrosive considering the high chloride concentration.

Figure 3-2 Potholing Location Site Plan
Legend
A Excavation Site
• Excess Effluent
Force Mein
V&A Project No. 15-0024
09/23/2025
Buena Creek Pump Station and Pipelines
C5 Page 751 of 1112

:� V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Table 3-4. Summary of Laboratory Soil Analysis Results
Pothole
Location
Depth
(ft)
Resistivity (ohm -cm)
As -
received
Minimum
Chemical Data /
Rating
pH
Sulfate
(mg/kg)
Chloride
(mg/kg)
Bicarbonate
(mg/kg)
Overall
Corrosivity
Rating
1 4
67,000
670

6.7 234
334
330
High

3.5 201,000 1,005 6.8 108 564
133.2
Moderate
3 3.5 603,000 2,144 7.7 24 2,904 180 High

3.6 Conclusions
Based on the results of the condition assessment, V&A presents the following conclusions:

1. The evaluated concrete surfaces are in good condition, rated VANDA Level 1.

2. Metal surfaces are in good condition with the majority of the coating (about 90%) intact.

There is some copper piping that is significantly corroded (VANDA Level 3).

3. At most of the testing locations, the DIP is in good condition and is rated VANDA Level 1.

There were a few locations that showed wall thickness outside the manufacturing tolerances by what is considered a minor degree. No significant exterior corrosion or leaks were observed on the rest of the piping in the dry well, which was outside the ultrasonic testing areas.

4. The inverted pendulum arrangement of the motor and pumps appears to be a significant issue with respect to seismic loading. However, seismic/structural analysis was not part of the project scope of work.

5. Vibration levels are high on most motor and pump test locations, with many exceeding ISO and Hydraulic Institute acceptance standards for operating levels.

6. The buried excess effluent and force main DIP are within a moderately to very highly corrosive soil environment.

V&A Project No. 15-0024 Buena Creek Pump Station and Pipelines 09/23/2025
C5 Page 752 of 1112

• V&A
City of Vista, California
Pump Station Condition Assessments Draft Report

3.7 Recommendations
Based on the conclusions of the condition assessment, V&A presents the following recommendations:

1. The evidence of groundwater infiltration on the concrete walls and the corrosive soil environment around the pump station warrant additional testing in the concrete pump room.

Testing to be considered includes:
a. Concrete core analysis to identify corrosion stimulants and concrete characteristics b. Determining placement of reinforcing steel
c. Identify corrosion potential on reinforcing steel and visually verify condition

2. Seal points of infiltration at the construction joints. It is recommended this be done after performing additional concrete testing to determine the appropriate repair/rehabilitation approach.

3. Repair damaged coating on mechanical equipment and piping as needed. Prepare surfaces to remain per SSPC SP 2 to 3. Coat with a 100% solids epoxy or polyurethane coating system, such as Carboline Carboguard 890, PPG Amercoat Amerlock 400, or Tnemec Series N69 at 2 to 3 mils dry film thickness.

4. Clean the surfaces of the copper piping and determine if the replacement of copper piping is warranted.

5. Evaluate the seismic vulnerability of the motor and pump arrangement.

6. Reed Electric recommended the following actions for the pumps and motors based on the vibration analysis results:
a. #3 Motor & Pump: This unit had VFD drive or other electrical issues during the test. It will need to be scheduled for a retest when feasible.
b. The evidence of high vibration on all motor and pump structures warrants a full structural mode shape analysis, to allow proper definition of any resonance issues as they relate to structure, and should result in effective recommendations to adjust or change the supports, etc., to reduce the effect.
c. #1 Motor & Pump - The extremely high levels on this unit warrant prioritized scheduling of detailed analysis and correction. In the meantime, the stiffness of the pump supports should be inspected for rigidity (see typical pump supports, Figures 4 & 5).
d. #2 Motor & Pump - The high levels on this unit warrant scheduling of detailed analysis and correction. In the meantime, the stiffness of the pump supports should be inspected for rigidity.
e. #4 Pump - This units' suction piping support was found loose, and should be adjusted.

7. Consider cathodic protection for buried metal piping if it is to remain in service for the next 20 years. If a new pipeline is to be installed, alternative materials to metal or concrete, such as plastic, should be considered.

V&A Project No. 15-0024 Buena Creek Pump Station and Pipelines 09/23/2025
C5 Page 753 of 1112

4.0 BUENA VISTA PUMP STATION
The BVPS is a 23.1-mgd pump station originally constructed circa 1986. The pumps and piping were rebuilt circa 1994. The force main within the pump station site was reconfigured circa 2013, including the addition of two new flow meter vaults and surge tanks. V&A conducted a visual assessment and ultrasonic thickness testing at the pump station on September 9, 2015. Reed Electric & Field Service conducted the pump and motor vibration tests on September 10, 2015. The findings of these studies are presented below.

4.1 Dry Well Visual Assessment
The interior concrete surfaces of the dry well (lower level pump room) generally appeared to be in good condition and exhibited minimal evidence of degradation (Photo 4-1). However, there were some notable observations and minor, isolated defects, such as the following:

L . There were several isolated areas where there was evidence of groundwater seeping in through the exterior walls of the dry well. Some of these areas appeared to have been abandoned penetrations that have been patched. Some locations showed rust -colored staining (Photo 4-2).
%. At a few other locations, such as the discharge manifold penetration from Pumps 4 and 5, there was apparently some type of injection foam or epoxy that had dripped down the wall, probably during construction (Photo 4-3). No evidence of infiltration was observed though.

3. The mortar below the pump baseplates has cracked or spalled in some locations, particularly on Pumps 4 and 5 (Photo 4-4).

V&A Project No. 15-0024
09/23/2025
Buena Vista Pump Station
C5 Page 754 of 1112

V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Photo 4-1. Typical concrete surfaces inside
BVPS dry well.

Photo 4-3. Apparent foam or epoxy injected
around pipe penetration.

Photo 4-2. Evidence of groundwater intrusion
and rust -colored staining under
pipe penetration.

Photo 4-4. Deteriorated mortar below
pump baseplates.

The coatings on the pumps, piping, and valves were generally intact, but again there were some notable observations and defects, such as the following:

There were numerous small chips in the coating in some areas, particularly on the components at lower elevations, such as the pump volutes, pump stands, valves, and pipe supports (Photo 4-5).

V&A Project No. 15-0024 Buena Vista Pump Station
09/23/2025
C5 Page 755 of 1112

V&A
City of Vista, California
Pump Station Condition Assessments Draft Report

5. The coating has failed around the penetration of the check valve lever shafts (Photo 4-6).

This is probably due to leakage through the packing. There was minor surface corrosion of the valve body where the coating has failed.

6. The underside of the rectangular suction lines did not appear to be coated thoroughly at the wall penetrations from the wet well.

Photo 4-5. Typical coating condition on
piping at lower levels. Numerous small chips
in paint.

Photo 4-6. Coating failure and apparent
leakage on check valves.

In general, the exterior of the dry well piping was in good condition, along with the coatings as noted above (Photo 4-7). The pipe supports also appeared to be in good condition. Notable observations and defects included the following:

One pipe spool on the discharge header from Pumps 1 and 2 had a direct -threaded tap at the top of the pipe, with coating failure and moderate external corrosion surrounding the tap (Photo 4-8). It appears that the threaded tap may leak. This spool was also an isolated location of internal wall thickness loss, as noted below in Section 4.3. It may be that the corrosion was caused by installation of the tap having damaged both the coating and lining on this spool.

B. Most of the flanged joints did not exhibit signs of leakage, but there were stains emanating from the suction flange on Pump 4 (Photo 4-9). There was also evidence of minor leakage from some of the check valve covers (Photo 4-10).

V&A Project No. 15-0024 Buena Vista Pump Station
09/23/2025
C5 Page 756 of 1112

V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Photo 4-7. Typical piping at upper elevations
in dry well, coated and in good condition.

Photo 4-8. Evidence of corrosion and
apparent leakage around threaded tap on 20 -
inch header spool for Pumps 1 and 2.

Photo 4-9. Leakage from suction flange on Photo 4-10. Typical evidence of leakage from Pump 4.
check valve covers.

Other observations from the dry well included the site bathroom drain plumbing and the ventilation equipment:

9. The drain plumbing exhibited visible corrosion on the exterior and evidence of leakage. Some of the band clamps for the couplings were broken or missing (Photo 4-11).

19. One of the flanges for the ventilation ducting at the blower was missing most of the nuts and bolts, and it was misaligned by about 1/2 of an inch (Photo 4-12).

V&A Project No. 15-0024 Buena Vista Pump Station
09/23/2025
C5 Page 757 of 1112

V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Photo 4-11. Motor room bathroom drain
piping. Corrosion evident; broken band
clamp visible at right.

Photo 4-12. Missing bolts and misalignment
at ventilation ducting flange.

4.2 Meter Vault Visual Assessments
The two meter vaults showed moderate to extensive groundwater seepage at several locations at various heights on the walls. Most of these locations were characterized by rust -colored staining. The floor of each vault was wet during the evaluation, with a slight amount of puddling in some areas.

Examples of the groundwater infiltration are shown in Photo 4-13 to Photo 4-16. This water may be brackish due to proximity to a nearby creek and lagoon. The chloride content in brackish water would tend to promote corrosion of the reinforcing steel in the walls, as well as items inside the vaults that may be immersed. It should be noted that the meter vaults are only a few years old. virTir 006' Al
Photo 4-13. Groundwater seepage stains
along joint near hatch opening in north
meter vault.

Photo 4-14. Extensive seepage at mid -height
construction joint in south meter vault walls.

V&A Project No. 15-0024
09/23/2025
Buena Vista Pump Station
C5 Page 758 of 1112

V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Photo 4-15. Deposits from seepage above Photo 4-16. Active seep at the bottom of the pipe penetration in south meter vault.
north meter vault.

The coating on the 24 -inch DIP force main in the meter vaults is peeling off the pipe at the concrete wall penetrations. There is surface corrosion on the DIP, particularly in the north meter vault (Photo 4-17). This coating failure and corrosion appears to be related to groundwater intrusion at the pipe penetrations. The wall penetration details shown on the "as built" drawings for the "Buena Vista Lift Station Force Main (VC -4) - Contract No. 55081" differed from the penetrations observed on -site.

The drawings show a sleeve with a waterstop ring embedded in the concrete, with mechanical expanding rubber seals (i.e., Link -Seals) and a sealant sealing the gap between the pipe and the sleeve. Instead the DIP force mains appear to have been directly embedded in the concrete walls and there may not be a waterstop ring. This would tend to explain the evidence of groundwater intrusion at the pipe penetrations.

The flow meter within each vault is equipped with a bare copper ground cable that attaches to a grounding ring at one of the meter flanges. The copper cables show a green copper oxide product on the surface, but generally appear to be intact. There is greater and apparently ongoing oxidation at some of the connectors for the copper cables. Where the cables connect to the meter flanges, the moisture is dripping on the adjacent pipe flange and causing apparent coating failure and surface corrosion (Photo 4-18). In comparison with the corrosion observed at the connectors, the green oxide product on the cable itself does not appear to be a significant concern. The ground cable is also zip - tied to the outside of another conduit and appears to be damaging the coating on the conduit.

Other than the isolated defects noted above, the DIP and flow meter, as well as their coatings, within each vault appear to be in good condition. However, the hold-down rods for the pipe supports in each vault may eventually cause coating failure and corrosion of the pipe at that location. The hold-down rods were applied directly over the coated DIP surface without any form of galvanic or vibration isolation (such as a rubber pad) in between.

V&A Project No. 15-0024 Buena Vista Pump Station
09/23/2025
C5 Page 759 of 1112

V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Photo 4-17. Failed coating and metal
corrosion on DIP force main in north meter
vault (typical of both vaults).

Photo 4-18. Corrosion stains at copper ground
cable connection and jumper wire at flange
on flow meter (typical of both vaults).

The pipe support saddle in each vault has what appears to be a square galvanized steel baseplate bolted to a small concrete mortar pad. Despite the galvanizing, the edges of the baseplate in each vault show evidence of corrosion (Photo 4-19). The corrosion may be due to water standing within the vaults, particularly if it is brackish water.

The plug valve downstream from each flow meter rests on a concrete support. The valve support in the north meter vault exhibits isolated spalling and corrosion of the reinforcing steel, probably due to insufficient depth of concrete cover (Photo 4-20).

Photo 4-19. Corroding baseplate for pipe Photo 4-20. Valve support pedestal in north support (typical of both vaults).
meter vault. Corroding reinforcing steel.

V&A Project No. 15-0024
09/23/2025
Buena Vista Pump Station
C5 Page 760 of 1112

V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
The north meter vault drains to the south meter vault, which has a sump pump. The sump pump is connected to the discharge piping by a short length of rubber hose with cam -lock fittings at either end. The lower fitting is severely corroded or encrusted (Photo 4-21), while the upper fitting shows surface corrosion. The fittings appear to be aluminum, which is not corrosion -resistant in an environment with brackish water or seawater. The pump is plugged into a standard 120 -volt outlet higher on the vault wall. The outlet box has surface corrosion along its lower edge and may not be watertight (Photo 4-22).

Photo 4-21. Severely corroded or encrusted Photo 4-22. Surface corrosion at lower edge of quick -connect fitting for sump pump. sump pump outlet box in south meter vault.

4.3 Ultrasonic Thickness Measurements
The ultrasonic thickness data is summarized in Table 4-1. As shown in the table, the wall thickness loss for the DIP, at the locations that were tested, was within manufacturing tolerances, except at one location on the header downstream of Pumps 1 and 2. At this location, there appears to be a significant thickness loss of 0.167 inches, or 37% of the assumed nominal thickness. This spool also exhibited localized external corrosion, as noted above in Photo 4-8. The maximum wall thickness loss for the fabricated, rectangular steel suction lines was 9%, which is considered negligible considering the tolerances that may have been applicable (steel pipe made to ASTM standards often has a thickness tolerance of -12.5%).

V&A Project No. 15-0024 Buena Vista Pump Station II
09/23/2025 C5 Page 761 of 1112

Pump 1 discharge riser
:� V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Table 4-1. Buena Vista Pump Station Ultrasonic Thickness Data Summary Measured Thickness (in.)
Assumed Pipe
Specifications
Max
51111111
Nom. Cast- Wall
Thick- ing Loss
ness Tol. (in.)
(in.) (in.)
Max.

Wall
Loss
14 0.399 0.415 0.424
53 0.42 —0.07 0.021
5%
Pump 2 discharge riser
14 0.375 0.392 0.408 53 0.42 —0.07 0.045 11%
Pump 4 discharge riser
14 0.404 0.409 0.415 53 0.42 —0.07 0.016 4%
Pump 5 discharge riser
14 0.402 0.412 0.424 53 0.42 —0.07 0.018 4%
Header between Pumps 1 and 2
14 0.390 0.397 0.408 53 0.42 —0.07 0.030 7%
Header downstream of Pumps 1 and 2 20 0.283 0.305 0.343 53 0.45 —0.07 0.167 37% Spool upstream of NW. force main penetration 24 0.757 0.758 0.759 (a) (a) (a) (a) (a) Pump 1 suction wall spool (b) 0.343 0.359 0.368 (b) 0.375 (b) 0.032 9% Pump 2 suction wall spool (b) 0.340 0.354 0.371 (b) 0.375 (b) 0.035 9% Pump 4 suction wall spool (b) 0.350 0.367 0.374 (b) 0.375 (b) 0.025 7%
Pump 5 suction wall spool (b) 0.351 0.373 0.394 (b) 0.375 (b) 0.024 6% Pump 1 suction reducer (b) 0.517 0.521 0.524 (b) 0.500 (b) (c) (c) Pump 2 suction reducer (b) 0.505 0.520 0.523 (b) 0.500 (b) (c) (c) Pump 4 suction reducer (b) 0.516 0.520 0.523 (b) 0.500 (b) (c) (c) Pump 5 suction reducer (b) 0.515 0.520 0.525 (b) 0.500 (b) (c) (c) Notes
(a) This spool measured much thicker than the published thicknesses for centrifugally cast (typical) ductile iron pipe. It may be pit - cast; the applicable class, nominal thickness, etc., are unknown. (b) The pump suction lines are rectangular and are fabricated from steel. As a result, the pipe "class" is not applicable terminology and they were assumed to have been made from fractional -inch -thickness plate. The plate thickness tolerance is also unknown. (c) Measured thickness within manufacturing tolerances or greater than nominal; wall loss not reported.

Vibration Analysis Results
Vibration testing was performed on Motors and Pumps 1, 2, 4 and 5. There is no Motor or Pump 3 at the BVPS. The pumps were run at approximately 65% and near 100% speed. System control limitations only allowed data to be collected at approximately 65% speed on many of the pump test points. General observations of the testing indicate that vibration levels are reasonable on most motor and pump test locations, with the majority meeting ISO and Hydraulic Institute acceptance standards for operating levels. The highest readings were noted in the perpendicular direction on both the motors and the pumps. This appears to be due to a residual resonance issue. There was no indication of high -frequency mechanical or electrical peaks on any of the test points, pointing to minimum hydraulic noise and no apparent VFD issues. Predominant vibration frequency peaks were two, three, and six times running speed, felt primarily to be the area of resonant response on these structures. Reed believes the stiffening beams above the pumps to be related to reducing vibration.

However, it also appears likely that they were installed for seismic considerations. A summary of the testing results is presented in Table 4-2. The full report from Reed Electric is attached in Appendix A.

V&A Project No. 15-0024 Buena Vista Pump Station
09/23/2025
C5 Page 762 of 1112

• V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Table 4-2. Buena Vista Pump Station Vibration Analysis Summary Motor/Pump 1
Generally comparable or lower levels of vibration compared to the other three pumps that were tested.

Motor/Pump 2
Pump upper bearing has a high 4x peak at 65% speed. Generally higher vibration levels than other pumps.

Motor/Pump 3 Does not exist.

Motor/Pump 4
Showed unusual running speed harmonics on the motor upper bearing. Generally had the highest readings at all test points.

Motor/Pump 5
Motor has high 6x peak on motor upper bearings, with some high -frequency peaks indicative of bearing looseness. Pump upper bearing shows some indication of cavitation noise at low load and is the only pump at the station to exhibit this.

Conclusions
Based on the results of the condition assessment, V&A presents the following conclusions:

1. In general, the concrete interior surfaces of the dry well were in good condition (VANDA Level 1). There were, however, some isolated areas of groundwater infiltration, some with staining indicating possible corrosion of the reinforcing steel. The grout pads under the pump bases showed deterioration at the edges in some cases.

2. The coating on the piping was generally in good condition at higher elevations, with numerous chips and other defects in the coating at lower elevations. Generally, there was minor surface corrosion where the coating was damaged. There was also one spool downstream of Pumps 1 and 2 that exhibited moderate external corrosion.

3. At most of the ultrasonic thickness testing locations, the dry well piping is in good condition, but there was one location on the header downstream of Pumps 1 and 2 that exhibited a significant thickness loss of 37%. This location also exhibited external corrosion. It is possible, though considered unlikely, that the pipe at this location was manufactured thinner than required by AWWA standards. No significant exterior corrosion or leaks were observed on the rest of the piping in the dry well, which was outside the ultrasonic testing areas.

4. The bathroom drain piping and ventilation ducting exhibited various moderate -severity defects.

5. The meter vaults show moderate to extensive groundwater infiltration, with staining that indicates possible corrosion of the reinforcing steel. The vaults are only a few years old. The extent of staining may indicate that the water leaking into the vaults is brackish, which would promote corrosion.

6. The piping, pipe supports, sump pump fittings, and electrical items within the meter vaults also showed various defects that appear to be related to the groundwater infiltration, particularly if it is brackish.

7. Reed Electric identified several minor- to moderate -severity vibration issues and recommended that these be addressed during the next planned outage.

V&A Project No. 15-0024 Buena Vista Pump Station
09/23/2025
C5 Page 763 of 1112

6 A V&A
City of Vista, California
Pump Station Condition Assessments Draft Report

4.6 Recommendations
Based on the conclusions of the condition assessment, V&A presents the following recommendations:

1. Monitor areas of infiltration within the dry well for increased evidence of infiltration or corrosion staining. Consider further evaluation of the concrete and reinforcing steel in areas where there is corrosion staining. Testing to be considered includes:
o Concrete core analysis to identify corrosion stimulants and concrete characteristics o Determining placement of reinforcing steel
o Identify corrosion potential on reinforcing steel and visually verify condition

2. Consider repairing the grout pads under the pump bases.

3. Recoat the exterior of the piping, at least at lower elevations, to prevent further corrosion.

The lower elevations are subject to more water splashing and dripping from operations and maintenance activities, which exacerbates any minor coating defects that may be present.

Prepare surfaces to remain per SSPC SP 2 to 3. Coat with a 100% solids epoxy or polyurethane coating system, such as Carboline Carboguard 890, PPG Amercoat Amerlock 400, or Tnemec Series N69 at 2 to 3 mils dry film thickness.

4. Calculate the minimum required thickness for the piping based on pressure, loading, etc.

Compare the minimum required thickness against the measured thicknesses in this report to determine the amount of further wall loss that can be tolerated, if any, before the integrity of the piping is impaired. With the results of this analysis in mind, consider conducting the following activities to address corrosion and integrity of the dry well piping:
o Address the corrosion on the spool downstream of Pumps 1 and 2. Replacing the spool is probably the most cost-effective option. When the piping is shut down and drained for this activity, consider using this opportunity to evaluate the interior of the remaining piping. This could be done using closed-circuit television (CCTV). This would provide further insight on the lining condition and corrosion inside the piping, which is expected to be localized.
o Ensure that there is a contingency plan and materials available in case of a piping leak or failure. The data indicated that there may be isolated areas of corrosion.

Consider the impact of a failure or leak. If the impact to operations is greater, the preparations should be more comprehensive, and further evaluation of the piping should be conducted.

5. Repair the bathroom drain piping and ventilation ducting connections.

6. Perform testing to quantify the extent of degradation of the concrete and reinforcement in the two meter vaults. Testing to consider is similar to that recommended for the dry well.

Sample the water entering the vaults for resistivity and chloride content.

7. Address the electrical connections within the meter vaults (meter ground cables and power for sump pump). Replace corroded connectors with corrosion -resistant materials and take precautions for galvanic corrosion between dissimilar metals.

8. Replace the cam -lock fittings for the sump pump in the south meter vault.

V&A Project No. 15-0024 Buena Vista Pump Station
09/23/2025
C5 Page 764 of 1112

:� V&A
City of Vista, California
Pump Station Condition Assessments Draft Report

9. Assuming that the groundwater entering the meter vaults is brackish (see sampling recommendation above), use materials and coatings suitable for a marine environment for all items within the vaults.

10. Consider whether the groundwater may also be aggressive to the buried DIP force mains within the pump station site, review the construction details for the force mains to determine whether adequate corrosion protection was provided for the buried pipe. Consider conducting field evaluations to determine the corrosivity of the soil and/or the condition of the buried DIP.

11. Reed Electric recommended the following actions for the pumps and motors based on the vibration analysis results:
o The evidence of historical vibration issues based on the need for dampeners on all motor and pump structures necessitates the frequent periodic monitoring of the vibration, to assure that the stiffness of the arms does not change significantly with time or maintenance.
o #4 Motor - If a motor inspection is forecast, this would be the prioritized unit for mechanical disassembly and inspection.
o #5 Motor & Pump - If a unit inspection is forecast, this would be the prioritized unit for motor bearing inspection and pump impeller inspection. o #2 Pump - The pump dampener structures and piping supports should be inspected for rigidity.

V&A Project No. 15-0024 Buena Vista Pump Station
09/23/2025
C5 Page 765 of 1112

5.O RACEWAY PUMP STATION
The RPS was constructed circa 1988 and is a 1.9 mgd pump station. The station was replaced in 2007. V&A conducted a visual assessment and ultrasonic thickness testing at the pump station on September 11, 2015. The findings of these studies are presented below.

5.1 Visual Assessment
The majority of exterior surface of pump piping has no signs of corrosion. The exterior coating is in good condition. There is corrosion staining and cracked coating on conduits near the pump piping.

The concrete reservoir has cracking and staining indicating possible infiltration or exfiltration at some of those areas. The concrete at the guard rail connections is cracked and damaged by spalling.

The embedded guardrail post was not coated with a coal tar and PVC sleeve in order to isolate it from the concrete. There is no horizontal reinforcing steel on the outer wall of the curb which also allowed the corroding railing to crack the concrete. Examples of the defects are shown in Photo 5-1 through Photo 5-6.

Photo 5-1. Cracking and staining in
concrete reservoir.

Photo 5-2. Crack in concrete at base of
guard rail.

V&A Project No. 15-0024
09/23/2025
Raceway Pump Station
C5 Page 766 of 1112

V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Photo 5-3. Defective coating, staining, cracks, Photo 5-4. Defective coating and corrosion on missing concrete at electrical box support. flange near Pump 3 discharge piping.

Photo 5-5. Spalling at base of guard rail. Photo 5-6. Staining on electrical box.

5.2 Ultrasonic Thickness Measurements
The ultrasonic thickness data is summarized in Table 5-1. As shown in the table, the wall thickness loss for the DIP and fittings, at the locations that were tested, was mostly within manufacturing tolerances. At three locations the wall thickness was outside the tolerances by what is considered a minor degree. The maximum wall thickness loss was calculated to be 18% for the DIP and 21% for the fittings. However, at these locations, the wall thickness was outside the manufacturing tolerances by only 0.028 inches or less.

V&A Project No. 15-0024 Raceway Pump Station
09/23/2025
C5 Page 767 of 1112

Pump 1 discharge, ground penetration
:� V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Table 5-1. Raceway Pump Station Ultrasonic Thickness Data Summary Measured Thickness (in.)
Assumed Pipe
Specifications
Max
Nom. Cast- Wall
Class Thick- ing Loss
(in.)
Hess Tol.
(in.) (in.)
18%
6 0.352 0.412 0.435 56 0.43 -0.05 0.078
Pump 2 discharge, ground penetration
6 0.359 0.381 0.397 55 0.40 -0.05 0.041 10%
Pump 3 discharge, ground penetration
6 0.303 0.341 0.361 54 0.37 -0.05 0.067 18%
Pump 1 discharge, horizontal spool
6 0.353 0.361 0.366 54 0.37 -0.05 0.017 5%
Pump 2 discharge, horizontal spool 6 0.378 0.383 0.392 55 0.40 -0.05 0.022 6% Pump 3 discharge, horizontal spool 6 0.363 0.374 0.396 55 0.40 -0.05 0.037 9%
Pump 1 discharge, elbow 6 0.435 0.501 0.547 250 0.55 -0.10 0.115 21% Pump 2 discharge, elbow 6 0.456 0.516 0.639 250 0.55 -0.10 0.094 17% Pump 3 discharge, elbow 6 0.455 0.515 0.592 250 0.55 -0.10 0.095 17% Discharge header, horizontal spool
Discharge header, ground penetration
Discharge header, elbow
Notes
(a) Measured thickness within manufacturing tolerances or greater than nominal; wall loss not reported.

5.3 Conclusions
8 0.357 0.376 0.399 54 0.39 -0.05 0.033 8%
8 0.353 0.366 0.379 54 0.39 -0.05 0.037 9%
8 0.653 0.702 0.759 250 0.60 -0.12 (a) (a)
Based on the results of the condition assessment, V&A presents the following conclusions:

1. There is potential infiltration/exfiltration at cracks in the concrete reservoir. The concrete surface is in good condition though (VANDA Level 1). The concrete has spalled at the base of the guardrail around the concrete reservoir due to a lack of insulation between the aluminum and concrete material.

2. The coating on the electrical box supports has failed and the concrete is damaged at the base. There is corrosion staining on the electrical box and conduits.

3. The surface of the piping is in good condition, with the majority of the coating (about 90%) intact. The coating on the flange near the Pump 3 discharge pipe has failed though, leading to the exposed metal surface to have moderate corrosion (VANDA Level 3).

4. At most of the testing locations, the pipe and fittings are in good condition. There were a few locations that showed wall thickness outside the manufacturing tolerances by what is considered a minor degree. The pipe spools that showed this increased wall thickness loss were assumed to have been manufactured thicker than Class 53 (minimum required for flanged DIP per AWWA 0115). Overall, while there may have been a minor thickness loss at a few locations, it does not appear to have been to a significant degree. The piping and fittings are rated a VANDA Level 1.

V&A Project No. 15-0024 Raceway Pump Station
09/23/2025
C5 Page 768 of 1112

• V&A
City of Vista, California
Pump Station Condition Assessments Draft Report

5.4 Recommendations
Based on the conclusions of the condition assessment, V&A presents the following recommendations:

1. Seal points of infiltration/exfiltration within the concrete reservoir

2. Install a grout or sealant at the base of the aluminum posts and slope it so that water runoff is allowed to flow away from the embedded section.

3. Replace corroded conduits.

4. Recoat or replace the corroded metal flange near the Pump 3 discharge pipe.

5. Recoat piping and electrical equipment as needed. Prepare surfaces to remain per SSPC SP 2 to 3. Coat with a 100% solids epoxy or polyurethane coating system, such as Carboline Carboguard 890, PPG Amercoat Amerlock 400, or Tnemec Series N69 at 2 to 3 mils dry film thickness.

V&A Project No. 15-0024 Raceway Pump Station
09/23/2025
C5 Page 769 of 1112

09/23/2025
C5 Page 770 of 1112

APPENDIX A. REED ELECTRIC & FIELD

SERVICES VIBRATION ANALYSIS REPORT
As mentioned in Section 3.3 and 4.4, attached are the results of the vibration analysis for the BCPS and the BVPS.

V&A Project No. 15-0024 Appendix A. Reed Electric & Field Services Vibration Analysis Report 09/23/2025
C5 Page 771 of 1112

09/23/2025
C5 Page 772 of 1112

yid REED
(S.cr, c & firld Sainte

BUENA CREEK SEWAGE PUMPS VIBRATION ANALYSIS

FOR CONDITION ASSESSMENT
TEST SETUP:

1. Instrumentation: An ADASH 4 -channel data recorder and analyzer was utilized along with three magnetic - mount accelerometers and a laser speed tachometer (see typical Motor monitoring setup, Figure 1).

2. Test Locations: The sensors were mounted on the Motor Upper, Motor Lower, Pump Upper, and Pump Lower bearings, in the Inline, Crossline (Perpendicular), and axial directions for each of the tests (see test layout schematic, Figure 2).

3. Test Conditions: The units were run between 78-87% load under normal operating mode. System control limitations and high cavitation vibration at lower loads dictated that data only be collected at that condition. The following data was recorded for each test:
a. overall velocity and displacement vibration
b. velocity spectrum plots
c. filtered amplitude/phase measurements (where the tach was available) See a table of overall velocity levels for each test point in Figure 6, and charts showing comparative levels on Pages 11 -14.

OBSERVATIONS:

4. General:
a. Vibration levels are high on most motor and pump test locations, with many exceeding ISO and Hydraulic Institute acceptance standards for operating levels. b. In general, the high readings were very directional, primarily in the In -Line (Parallel) direction on both the Motors and Pumps. The highest readings on each pump system were typically in the Pump Lower bearing area. This was felt to be due to a residual system resonance issue, which appears to be sensitive to piping support stiffness (see and typical motor -pump layout, Figure 3). c. In general, there was no indication of high -frequency mechanical or electrical peaks on any of the test points, pointing to minimum hydraulic noise, and no apparent VFD issues. d. Predominant frequencies peaks of vibration was 2X running speed, felt primarily to be the area of resonant response on these structures.

5. Specific Units:
a. #1 Motor -Pump — This unit showed high directional levels in the inline direction from the motor bearings down to the pump bearings. The predominant frequency of vibration was the 2X running speed peak (see all #1 bearing inline spectrums Figure 7). This motor generally had the highest readings at all test points (see level comparison charts, Pages 11— 14). b. #2 Motor -Pump — This unit showed similar high directional levels in the inline direction from the motor bearings down to the pump bearings, though at lower levels, with the same predominant frequency (see all #2 bearing inline spectrums Figure 8, and level comparison charts, Pages 11— 14). c. #4 Pump — the pump bearings showed a higher perpendicular relationship than the other pumps. 09/23/2025
C5 Page 773 of 1112
1 �I REED
Ef�ef��c d Field Serr,ce
RECOMMENDATIONS:

1. #3 Motor & Pump: This unit had VFD drive or other electrical issues during the test. It will need to be scheduled for a retest when feasible.

2. General Monitoring: The evidence of high vibration on all motor and pump structures warrants a full structural mode shape analysis, to allow proper definition of any resonance issues as they relate to structure, and should result in effective recommendations to adjust or change the supports, etc., to reduce the effect.

3. #1 Motor & Pump — The extremely high levels on this unit warrant prioritized scheduling of detailed analysis and correction. In the meantime, the stiffness of the pump supports should be inspected for rigidity (see typical pump supports, Figures 4 & 5).

4. #2 Motor & Pump — The high levels on this unit warrant scheduling of detailed analysis and correction. In the meantime, the stiffness of the pump supports should be inspected for rigidity.

5. #4 Pump — This units' suction piping support was found loose, and should be adjusted.

DATA

1. A summary table of overall velocity levels for each position at each test load is shown in Figure 6.

2. Charts showing comparison levels for each position at the different loads is shown on Pages 11- 14.

3. Spectrum Waterfall plots for each position are available if requested. 09/23/2025
C5 Page 774 of 1112
2 RE
ED
Electric d field Ser•iee
Figure 1 - Typical Buena Creek Motor Bearing Monitoring Points 09/23/2025
C5 Page 775 of 1112
3 REED
f 1919
Electric & Field Serra
MOTOR
1M,M
Pt POP
JIAPtil
Pump
Lower
L
•
3 measurements taken at each
bearing location

1. In -line with piping

2. Perpendicular to piping (Crossline)

3. Axial (parallel to shaft)
I Laser Tachometer monitoring speed
IPS through VFD operating range
i'
Figure 2 - Typical Pump Layout Test Locations
09/23/2025
C5 Page 776 of 1112
4 RE
ED
Electric d field Service
Figure 3— Buena Creek Motor -Pumps
09/23/2025
C5 Page 777 of 1112
5 ..;:j REED
fir flr,4 d frrld $rrrI<.r
Figure 4 - Pump #4 suction piping saddle support
09/23/2025
C5 Page 778 of 1112
6 REED
fr
Figure 5 - Pump #5 discharge piping support
09/23/2025
C5 Page 779 of 1112
7 - REED
Elecl,,c S Field Seivic♦
Plant:

Buena Creek
Plant
Unit:

Pumps 1,2, 3,
4, and 5
Date:
9/10/2015
Instrument:

ADASH
VA4 PRO
Operator:

Costa Yiannakakis
Overall Spectrum IPS, RMS (0-1600 Hz)
Bearing
Probe Dir.
% Load
Speed (RPM)
Pump #1
Pump #2
Pump #3
Pump #4
Pump #5
Motor Upper
Inline
87 1560

1.508
Not Op.

1.140

1.037
Motor Upper
Perpendicular
87 1560

0.215

0.206
Not Op.

0.295

0.096
Motor Upper
Axial
87 1560

0.186

0.090
Not Op.

0.268

0.133
Motor Lower
Inline
87 1560

1.503
Not Op.

1.220

0.753
Motor Lower
Perpendicular
87 1560

0.135

0.116
Not Op.

0.293

0.085
Pump Upper
Inline
87 1560
Not Op.

1.897

1.278
Pump Upper
Perpendicular
87 1560

0.197

0.241
Not Op.

0.437

0.114
Pump Upper
Axial
87 1560

0.304

0.184
Not Op.

0.184

0.069
Pump Lower
Inline
87 1560
Not Op.

1.388

1.516
Pump Lower
Perpendicular
87 1560

0.203

0.351
Not Op.

0.418

0.124
Figure 6 - Buena Creek Pumps - Overall Velocity Levels for all positions for each test point 09/23/2025
C5 Page 780 of 1112
8 REED
flec►rrc & field Serrrce
G ty of Vata Sewage Pumps\Buaaa Creek VFD Motors001 Vertical Mo or Pt, M to M \VEL City of Vlsta Sewage Pumas Buena Creek VFD Matgrs001 Vertloal Motor-Rump\Motor\ MIS Infna_CH t
2,700
CPM Order.

1.5126
Value:

1.5126
iris (RMS)

5.02 4.75
450

4.25 4.05

3.75 3.50

3.25 3:00
2/5
250
225

2.00 1.75
150
125

1.00 0.75
050
025

0.00 nls (RMS) _T2527in1s (RMS)', Speed 1,785CPM (1705RP M) CPM
25,050 55,050 75,000
2,709
CPM Order
1,0126
Value:

1.5126
inls (RMS}

5.03 4.75
450

4.25 4.00
3/5
350
325

3.00 2.75
250

2.25 2.00
1 75

1.50 125

1.00 0.75
050

0.25 0.00
nls (RMS) _ T 3.730inis (RMS)', Speed 1,785CPM (1 785RPM) CPM
25,000 53,000 75000
Cl,, of Vista Sewage Pornps\Burna Creek VFV Motors'O1 Vertical Motor-Pump\Pump \PUB Inline SH City of V sta Sewage Pumps VBuena Creek VFD Motors0#1 Vertical Motor PumpAPurnfPPLB InhItB_C. f.
2,700
GPM Order:

1.5120
Value:

3.4525
Sirs (RMS)

5.00 4.75
4 50
425

4.00 375

3.50 3.25

3.00 215

2.50 2.25
200
1/5

1.50 1.25

1.00 075
050

0.25 0.00
1nls (RMS) -T 3706in/s (RMS)', Speed 1,785CPM (1 785RPM) OP
25,000 75,000
2,700
CPM Order:

1.5120
Value:

3.7154
Ines (ROS)

5.00 I nls (RMS) T 4081inis- (RMS); Speed 1,785CPM (1785RPM)

4.75 450
425

4.03 3 75

3.53 3.25

3.00 2.75

2.50 2.25

2.03 1.75

1.50 1.25

1.00 075

0.50 0.25
GPM

0.00 25,000

50.000 7^.000
Figure 7 - Buena Creek Pump #1 Motor & Pump Bearings Inline Spectrums 09/23/2025
C5 Page 781 of 1112
9 REED
flec►rrc & field Semite
C ty of Vista Sewage Pumps\Bupso Creek VFD MotorsVf2 VeiVoal Motor-Punw\Motor\MU00 Inlln2_CH City 0 Veto Sewage Pumps \Buena Creek VFD Motele42 Vertloal Motor-Rum\Rump\PCB Infine_CH f. 2;940 GPM Order. 1.6471 Value: 1.4344 iris (RMS) I
f. 2,940 CPM Order 1.6471 Value: 0.10948 his (RMS)

4.00 -

3.75 3.50

3.25 3.00

2.75 250 -

2.25 2.00

1.75 1.50 -
lnls (RMS) _T 1- 50 Bi nis (RMS). Speed 1,785CPM (1,78 5RPM) -
-
-

4.00 3.75

3.50 3.25
3-00
275

2.50 2.25

2.00 175

1.50 1.25

1.00 0.75

0.50 0.25
infs (RIB) _T 34{21rifs (RMS). Speed 1 765CPM (1 785RPM)

1.25 1.00-

0..75

5.50 025

0.00 CPM

0.00 CPM
0 25,000 50 000 75.000
0 25,000 50,000 75,000
City of Vista Sewage Purnpa\Buena Creek VFD Motors \Pa Vekboal Mobr-Pum¢\Vump\PIMP Ioline_CH City of Vista Sewage Pums0Buzn2 Creek V'FD MotersP52 VPnccal Moto' Pump\Motor\MLSlit o\VED 7 49 Hz Order: 1:6471 Value, 5.4592 Inls (RMS)
f 49, Hz Order 1.6471 Value: 1.2992 ints (RMS)

4.00 3.75

3.50 -

3.25 3.00

2.75-

2.50-

2.25 2.00 -

1.75 1.50

1.25 1.00

0.75 0 50
I nls (RMS) TOT 32.51inls (RMS)'; Speed 29-75Hz(1785RPM) -
-

4.00 375

3.50 3.25
30❑

2.75 2.50

2.25 2.90

1.75 1.50
roll (RMS) TOT 1.503107s(RMS): Speed 29 75H (1785RPM)

1.25 1.00

0.75 0.50

0.25 Hz

0.25 Hz

0.00 0 250 500 750 1,000 1,250 1,500

0.00 0 255 590 750 1,000 1,250 1500
Figure 8 - Buena Creek Pump #2 Motor & Pump Bearings Inline Spectrums 09/23/2025
10 C5 Page 782 of 1112

a REED
Howse s Fie Irl S•,rie•

4.000

3.500

3.000
a 2.500

2.000
0 1.500

1.000

0.500

0.000
Buena Creek Pumps
Motor Upper Inline - at 85% Load
I 1 1
Pump #1 Pump #2 Pump #3 Pump #4 Pump #5

0.350

0.300

0.250
V)
a
-. 0.200
O 0.150
v

0.100

0.050

0.000
Buena Creek Pumps
Motor Upper Perpendicular - at 85% Load
i
Pump #1 Pump #2 Pump #3 Pump #4 Pump #5

0.300

0.250
a 0.200

0.150
0 v
> 0.100

0.050

0.000
Buena Creek Pumps
Motor Upper Axial - at 85% Load
I
Pump #1 Pump #2 Pump #3 Pump #4 Pump #5
09/23/2025
C5 Page 783 of 1112 11

REED
Est 1929
Howie d Fisle S•,rie•

3.000

2.500
a 2.000

1.500
> 1.000

0.500

0.000
Buena Creek Pumps
Motor Lower Inline - at 85% Load
I
1 Pump #1 Pump #2 Pump #3 Pump #4 Pump #5

0.350

0.300

0.250
a

0.200
0 0.150
v

0.100

0.050

0.000
Buena Creek Pumps
Motor Lower Perpendicular- at 85% Load
1 Pump #1 Pump #2 Pump #3 Pump #4 Pump #5
09/23/2025
C5 Page 784 of 1112 12

a REED
_01—zargai
Howse & field Se,riee

4.000

3.500

3.000
a 2.500
u 2.000
0 • 1.500

1.000

0.500

0.000
Buena Creek Pumps
Pump Upper Inline - at 85% Load
I
Pump #1 Pump #2 Pump #3 Pump #4 Pump #5

0.500

0.450

0.400

0.350
V)
• 0.300
• 0.250
v 0.200
• 0.150

0.100

0.050

0.000
Buena Creek Pumps
Pump Upper Perpendicular- at 85% Load
I
1 Pump #1 Pump #2 Pump #3 Pump #4 Pump #5

0.35 0.3

0.25 T • 0.2

0.1 0.05
0 Buena Creek Pumps
Pump Upper Axial - at 85% Load
i
I
■
Pump #1 Pump #2 Pump #3 Pump #4 Pump #5
09/23/2025
C5 Page 785 of 1112 13

0 REED
Electric & Field Service

4.5 4

3.5 (n 3
a
5: 2.5
0 2
1 0.5
0 0.45

0.4 0.35
cn 0.3
a
5: 0.25

0.05 0
Buena Creek Pumps
Pump Lower Inline - at 85% Load
Pump #1 Pump #2 Pump #3 Pump #4 Pump #5
Buena Creek Pumps
Pump Lower Perpendicular - at 85% Load
I
Pump #1 Pump #2 Pump #3 Pump #4 Pump #5
09/23/2025
C5 Page 786 of 1112 14

eis REED
(S.cr,lc !L f.eld Selrtce

BUENA VISTA & SEWAGE PUMPS VIBRATION ANALYSIS

FOR CONDITION ASSESSMENT
TEST SETUP:

1. Instrumentation: An ADASH 4 -channel data recorder and analyzer was utilized along with three magnetic - mount accelerometers and a laser speed tachometer (see typical Pump monitoring setup, Figure 1).

2. Test Locations: The sensors were mounted on the Motor Upper, Motor Lower, Pump Upper, and Pump Lower bearings, in the Inline, Crossline (Perpendicular), and axial directions for each of the tests (see test layout schematic, Figure 2).

3. Test Conditions: The units were run at "'65% and near 100% load. System control limitations only allowed data to be collected at "'65% load on many of the pump test points. The following data was recorded for each test:
a. overall velocity and displacement vibration
b. velocity spectrum plots
c. filtered amplitude/phase measurements (where the tach was available) See a table of overall velocity levels for each test point in Figure 5, and charts showing comparative levels on Pages 12 —15.

OBSERVATIONS:

4. General:
a. Vibration levels are reasonable on most motor and pump test locations, with the majority meeting ISO and Hydraulic Institute acceptance standards for operating levels. b. In general, the highest readings were noted in the Cross Line (Perpendicular) direction on both the Motors and Pumps. This was felt to be due to a residual system resonance issue, which was likely the reason for the stiffening beams on both the Motor and Pump structures (see and typical motor and pump layouts, 3 & 4).
c. In general, there was no indication of high -frequency mechanical or electrical peaks on any of the test points, pointing to minimum hydraulic noise, and no apparent VFD issues. d. Predominant frequencies peaks of vibration were 2X, 3X, and 6X running speed, felt primarily to be the area of resonant response on these structures.

5. Specific Units:
a. #4 Motor — This motor showed some unusual multiple harmonics of running speed on the Motor Upper bearing (see Motor Upper Perpendicular spectrum Figure 6). This motor generally had the highest readings at all test points (see level comparison charts, Pages 12 — 15). b. #5 Motor & Pump — This motor has a high 6X peak on the Motor Upper bearings, with some high - frequency peaks indicative of bearing looseness (see Motor Upper Perpendicular spectrum Figure 7).

Additionally, the Pump Upper bearing shows some indication of cavitation noise, and is the only pump in the plant to exhibit this, though only at low load (see Pump Upper Perpendicular spectrum, Figure 8). c. #2 Pump — the pump Upper bearing has a high 4X peak at 65% load. Most of this pump's test points are higher than the other pumps (see Pump Perpendicular spectrum, Figure 9). 09/23/2025
C5 Page 787 of 1112
1 vid REED
Ef.cl,,c d Feld Serr,ce
RECOMMENDATIONS:

1. General Monitoring: The evidence of historical vibration issues based on the need for dampeners on all motor and pump structures necessitates the frequent periodic monitoring of the vibration, to assure that the stiffness of the arms does not change significantly with time or maintenance.

2. #4 Motor — If a motor inspection is forecast, this would be the prioritized unit for mechanical disassembly and inspection.

3. #5 Motor & Pump — If a unit inspection is forecast, this would be the prioritized unit for motor bearing inspection and pump impeller inspection.

4. #2 Pump — The pump dampener structures and piping supports should be inspected for rigidity.

DATA

1. A summary table of overall velocity levels for each position at each test load is shown in Figure 5.

2. Charts showing comparison levels for each position at the different loads is shown on Pages 12 - 15.

3. Spectrum Waterfall plots for each position are available if requested.

Figure 1 - Typical Buena Vista Pump Upper Bearing Monitoring Points 09/23/2025
C5 Page 788 of 1112
2 REED
f 1919
Electric & Field Serra
MOTOR
1M,M
Pt POP
JIAPtil
•
3 measurements taken at each
bearing location

1. In -line with piping

2. Perpendicular to piping (Crossline)

3. Axial (parallel to shaft)
I Laser Tachometer monitoring speed
IPS through VFD operating range
i'
Pump
�_■
Lower
Figure 2 - Typical Pump Layout Test Locations
09/23/2025
C5 Page 789 of 1112
3 zj REED
flrrrr,c X f,rld Sr,r ,.r
Figure 3 — Buena Vista Motors
09/23/2025
C5 Page 790 of 1112
4 REED
Electric d field Service
Figure 4 - Buena Vista Pump
09/23/2025
C5 Page 791 of 1112
5 l
REED
fleelr,e & firld Serr.tr
Plant:

Buena Vista
Plant
Unit:

Pumps 1,2,
4, and 5
Date:
9/10/2015
Instrument:

ADASH VA4 PRO
Operator:

Costa Yiannakakis
Overall Spectrum IPS, RMS (0-1600 Hz)
Bearing
Probe Dir.

Unit
Load (%)
Speed
(RPM)
Pump #1
Pump #2
Pump #3
Pump #4
Pump #5
Motor Upper
Inline
65 780

0.015

0.070
N/A

0.033

0.036
95 1185

0.117

0.050
N/A

0.213

0.123
Motor Upper
Perp.
65 780

0.112

0.297
N/A

0.151

0.249
95 1185

0.361

0.483
N/A

0.801

0.731
Motor Upper
Axial
65 780

0.016

0.027
N/A

0.024

0.026
95 1185

0.060

0.039
N/A

0.114

0.048
Motor Lower
Inline
65 780

0.017

0.042
N/A

0.036

0.067
95 1185

0.096
---
N/A

0.078
---
Motor Lower
Perp.
65 780

0.081

0.357
N/A

0.155

0.335
95 1185

0.309
---
N/A

0.558
---
Pump Upper
Inline
65 780

0.058

0.156
N/A

0.075

0.128
95 1185
---
---
N/A
---
---
Pump Upper
Perp.
65 780

0.259

0.872
N/A

0.226

0.676
95 1185
---
---
N/A
Pump Upper
Axial
65 780

0.06 0.082
N/A

0.067

0.094
95 1185
---
---
N/A
Pump Lower
Inline
65 780

0.127

0.115
N/A

0.058

0.123
95 1185
---
---
N/A
---
---
Pump Lower
Perp.
65 780

0.512

0.557
N/A

0.202

0.488
95 1185
---
---
N/A
---
---
Figure 5 - Buena Vista Pumps - Overall Velocity Levels for all positions for each test point 09/23/2025
C5 Page 792 of 1112
6 REED

MEMIEDIREI
Flec►rrt & Field Sere n e
:ity of Vista Sewage Pumps\BuenaVista VFD Motors'44Vertical Motor-PumplMotoriMUB Perpindicular_CH 2WELQCITY SPECTRUM 1600 Hz 9110/201510:22:34.60.c 1,200
CPM Order:
1 Value: 0.11996 ints (RMS) li
1,200
CPM

0.15 — inls (RMS

0.70 —

0.65 —

0.60-

0.55 —

0.50 —

0.45—

0.40 — ,`R

0.35—

0.30 —

0.25 —

0.20 —

0.15 —

0.10 —

0.05 —

0.00 Z3r40' GPMt;
fY_61 i4 i ['VS fRMS.

TOT 0.0007inls (RMS) Speed 1,200CPM (1,200RPM)
•
CPM
0 10,000 20.000 30.000
I I I

40.0011 III, ICI I I I SLI,11111 1
7 70,0100
I I
00,000 90,000
Figure 6 - Buena Vista Pump #4 Motor Upper Perpendicular Spectrum 09/23/2025
C5 Page 793 of 1112
7 4,) REED
Electtoc d Field Se,r,ce
3ity of Vista Sewage PumpsOuena Vista VFD MotorsYt5 Vertical Motor-Pump\rMlotorkMUB Perpindicular_CH 21VELOCITY SPECTRUM 1600 Hz 9/10,2015 8:55:51.656 f
1,140
GPM Order:

0.75 — inls (RMS)

0.70 —

0.65 —

0.60 —

0.55 —

0.50 —

0.45 —

0.40 —

0.35 —

0.30 0.25 —

0.20 —

0.15 —

0.10-

0.05 —

0.00 1
0 10,000
20,000
30,000
40,000
50,000
60,000
70,000
80,000
Value:

0.3014
6,840 CPM;

0.525 inls (RMS)
infs (RMS)
TOT 0.7307inis (RMS); Speed 1,140CPM (1,140RPM)
90,000
Figure 7 - Buena Vista Pump #5 Motor Upper Perpendicular Spectrum CPM
09/23/2025
C5 Page 794 of 1112
8 REED
(Sacrist & Field Semite
:it} of Vista Sewage PumpslBuena Vista VFD Motors##5 Vertical Motor-Pump\PumptPUB Perpindicular_CH 2\VELOCITY SPECTRUM 1600 Hz 9(1012.015 9:18:4©.296 81,180
CPM Order
101.43
Value:

0.0217
inls (RMS)

0.250 — inls (RMS)

0.225 —

0.200 —

0.175 —

0.150 —
i

0.125 —

0.100 —

0.075 —
�j0.050 — f

0.025 —

0.000
TOT 0.5756in1s (RMS); Speed 800.4CPM (800.4RPM)
81,180 CPM;

0.0217 inls (RMS)
CPM
0 10,000 20.000 30.000 40,000 50.000 60.000 70.000 80,000 90,000 Figure 8 - Buena Vista Pump #5 Pump Upper Perpendicular 09/23/2025
C5 Page 795 of 1112
9 REED
fleetest & Field Service
My of Vista Sewage Pumps \BuenaVista VFD Motors4P2Vertical Motor-PumplPumplPUB Perpindicular_CH2WEL0CITYSPECTRUM 1600 Hz 9110/2015 9:08:18.031 f.
3,240
CPM Order.
72614
Value:

0.58836
inls (RMS)

0.75 — inls (RMS)

0.70 —

0.65-

0.60 —

0.55 —

0.50 —

0.45—

0.40 —

0.35 —

0.30 —

0.25 —

0.20 —

0.15 —

0.10 —

0.05-

0.00 TOT 0.872in/s (RMS); Speed 446 2C -PM (4462RPM)
0 10.000
20,000
3U.nnn
41u,uuu
u.uun
3,240 CPM;

0.5884 inls (RMS
CPl.1
Ij l 1:11:1 rl
-, 'II, Il rlll
0u, rlrl rl
Figure 9 - Buena Vista Pump #2 Pump Upper Perpendicular Spectrum 0 LI. rl nn
09/23/2025
10 C5 Page 796 of 1112

REED

AMOMMINIUMIESI
flrcl,sc d Fisli S.tvic•

0.250

0.200
0 0.150

0.100
a

0.050

0.000
Buena Vista Pumps
Motor Upper Inline
1■
Pump #1 Pump #2
■
.1
Pump #4 Pump #5
■ 65% Load ■ 98% Load

0.900

0.800

0.700
+� 0.600
U
0 0.500
> 0.400
a 0.300

0.200

0.100

0.000
Buena Vista Pumps
Motor Upper Perpendicular
1 Pump #1 Pump #2 Pump #4 Pump #5
■ 65% Load ■ 98% Load

0.120

0.100

0.080
U
j 0.060
o- 0.040

0.020

0.000
Buena Vista Pumps
Motor Upper Axial
■
Pump #1 Pump #2
Pump #4 Pump #5
■ 68% Load ■ 98% Load
09/23/2025
C5 Page 797 of 1112 11

a REED
Electric 3 field Service

0.120

0.100
o.oso
U
O

0.060
a 0.040

0.020

0.000
Buena Vista Pumps
Motor Lower Inline
■
i
i
Pump #1 Pump #2 Pump #4 Pump #5
■ 65% Load ■ 98% Load

0.600

0.500
• 0.400
U
a) • 0.300
n- 0.200

0.100

0.000
Buena Vista Pumps
Motor Lower Perpendicular
■
I
i
Pump ##1 Pump #2
1 i
Pump #4 Pump #5
■ 65% Load • 98$ Load
09/23/2025
C5 Page 798 of 1112 12

RE
ED
Electric S Fish' S•rvic•

0.180

0.160

0.140
• 0.120
V
O 0.100
> 0.080
a 0.060

0.040

0.020

0.000
Buena Vista Pumps
Pump Upper Inline
Pump #1 Pump #2
Pump #4 Pump #5
■ 65% Load • 98% Load

1.000

0.800

0.600
a.)
,6,.; 0.400
e�

0.200

0.000
Buena Vista Pumps
Pump Upper Perpendicular
1 t
Pump #1 Pump #2 Pump #4 Pump #5
■ 65% Load • 98% Load

0.1 0.08

0.06 0.04

0.02 0
Buena Vista Pumps
Pump Upper Axial
i
Pump #1
Pump #2
i
Pump #4 Pump #5
■ 65% Load ■ 98% Load
09/23/2025
C5 Page 799 of 1112 13

a REED
fi! f919
fl•clwie d Fislt S•.•ie•
T

0.14 0.12

0.1 O 0.08
v
> 0.06
vi
— - 0.04

0.02 0
Buena Vista Pumps
Pump Lower Inline
Pump #1
Pump #2
Pump #4 Pump #5
■ 65% Load ■ 98% Load

0.6 0.5

0.4 U
O
j 0.3
a 0.2

0.1 0
Buena Vista Pumps
Pump Lower Perpendicular
Pump #1
Pump #2
Pump #4 Pump #5
■ 65% Load ■ 98% Load
09/23/2025
C5 Page 800 of 1112 14

APPENDIX B. IN -SITU SOIL RESISTIVITY

COMPLETE RESULTS
As mentioned in Section 3.4, the results of the in -situ soil resistivity testing using the Wenner Four - Electrode Method are presented in Table A-1.

Table A- 1. In -situ Soil Resistivity Results
Site
Number
1 Resistance
to Depth,
Meter
Reading
(ohm)
5 5.72

7.5 2.62
10 1.24
15 0.66
20 0.39
5 15.66
Resistivity
to Depth
(ohm -cm)
5,477
3,763
2,375
1,896
1,494
Resistance
of Soil
Layer
(ohm)
Resistivity
of Soil
Layer
(ohm -cm)
Degree of
Corrosivity
for Layer
0 - 5 5.7 5,477 W- Mild
5 - 7.5 4.8 2,315 Mild

7.5 - 10 2.4 1,127 Moderate
10 - 15 1.4 1,351 Moderate
15 - 20 1.0 913 High
14,995 { Negligible
7,931 Mild
7,552 Mild
3,964 Mild
2,627 Mild
0 5 9.2 8,762 ' Mild
5 - 7.5 21.4 10,249 [Negligible

7.5 - 10 30.3 14,495 boligible
10 - 15 7.5 7,170 . Mild
15 - 20 7.0 6,718 Mild
4,328 Mild
5,191 Mild
3,444 Mild
3,023 Mild
9,544 Mild
0 - 5 6.3 5,985 Mild
14,995 0 - 5 15.7

7.5 8.05 11,563
2 10 5.33 10,208
15 2.33 6,693
20 1.26 4,826
5 9.15 8,762

7.5 6.41 9,207
10 5.29 10,131
15 3.10 8,905
20 2.15 8,235

4.52 4,328

3.19 2.21

1.30 3,734

1.15 4,405
5 5 6.25 5,985
3 4
5 7.5
10 15
20 4,582
4,232
5-7.5 16.6

7.5 - 10 15.8
10 - 15 4.1
15 - 20 2.7
0-5 4.5
5-7.5 10.8

7.5 - 10 7.2
10 - 15 3.2
15 - 20 10.0
V&A Project No. 15-0024 Appendix B. In -Situ Soil Resistivity Complete Results 09/23/2025
C5 Page 801 of 1112

:1 V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Site
Number
Depth
(feet)
Resistance
to Depth,
Meter
Reading
(ohm)
Resistivity
to Depth
(ohm -cm)
Layer
(feet)
Resistance
of Soil
Layer
(ohm)
Resistivity
of Soil
Layer
(ohm -cm)
Degree of
Corrosivity
for Layer
6 7
8 9
10 11

7.5 10
15 20
5 7.5
10 15
20 5

7.5 10
15 20
5 7.5
10 15
20 5

7.5 10
15 20
5 7.5
10 15
20 5

7.5 10

4.57 3.99

2.45 0.76

2.83 2.06

1.54 1.15

0.89 t67

0.88 0.60

0.44 0.24

2.29 1.08

0.73 0.41

0.24 1.37

0.87 0.61

0.21 0.16

0.78 0.36

0.22 0.16

0.11 3.40

2.27 1.74
6,564 5- 7.5
7,641 7.5 - 10
7,038 10 - 15
2,911 15 - 20
2,710 0 - 5
2,959 5 - 7.5
2,949 7.5 - 10
3,304 10 - 15
3,409 15 - 20
1,599 0 - 5
1,264 5 - 7.5
1,149 T5-10
1,264 10 - 15
919 15 - 20
2,193 0-5
1,551 5 - 7.5
1,398 7.5 - 10
1,178 10 - 15
919 15 - 20
1,312 0 - 5
1,250 5 - 7.5
1,168 7.5 - 10
603 10 - 15
613 15 - 20
747 0-5
517 5 - 7.5
421 7.5 - 10
460 10 - 15
421 15-20
3,256 0 - 5
3,260 5 - 7.5
3,332 7.5 - 10

17.0 31.4

6.3 1.1

2.8 7.6

6.1 4.5

3.9 1.7

1.9 1.9

1.7 0.5

2.3 2.0

2.3 0.9

0.6 1.4

2.4 2.0

0.3 0.7

0.8 0.7

0.6 0.6

0.4 3.4

6.8 7.5
8,140
15,052
6,078
1,055
2,710
3,625
2,921
4,348
3,769
1,599
891
903
1,580
506
2,193
979 High
1,078
896
554
1,312
1,141
977
307
643
747
320
271
562 High
337 /ery High
3,256
3,270
3,568
Moderate
L
r
Mild
Mild
Mild
Mild
Mild
Moderate
L
F
High
High
Moderate
High
p Mild
Moderate
High
High
Moderate
Moderate
High
L High
r High
Very High
Very High
•
Mild
Mild
Mild
V&A Project No. 15-0024 Appendix B. In -Situ Soil Resistivity Complete Results 09/23/2025
B-2
C5 Page 802 of 1112

:1 V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Site
Number
Depth
(feet)
Resistance
to Depth,
Meter
Reading
(ohm)
Resistivity
to Depth
(ohm -cm)
Layer
(feet)
Resistance
of Soil
Layer
(ohm)
Resistivity
of Soil
Layer
(ohm -cm)
Degree of
Corrosivity
for Layer
Moderate
Moderate
12 13
14 15
16 17
15 20
5 7.5
10 15
20 5

7.5 10
15 20
5 7.5
10 15
20 5

7.5 10
15 20
5 7.5
10 15
20 5

7.5 10
15 20

0.93 0.60

0.82 0.48

0.32 0.18

0.14 3.67

2.49 L76
L26

1.14 0.41

0.20 0.15

0.09 0.07

0.60 0.35

0.30 0.18

0.13 0.86

0.63 0.48

0.31 0.24

0.83 0.51

0.41 0.23

0.16 2,672 10 - 15
2,298 15 - 20
785 0-5
689 5 - 7.5
613 7.5 - 10
517 10 - 15
536 15 - 20
3,514 0 - 5
3,576 5 - 7.5
3,371 7.5 - 10
3,620 10 - 15
4,366 15 - 20
393 0 - 5
287 5 - 7.5
287 7.5 - 10
259 10 - 15
268 15 - 20
575 0 - 5
503 5 - 7.5
575 7.5 - 10
517 10 - 15
498 15-20
823 0-5
905 5 - 7.5
919 7.5 - 10
891 10 - 15
919 15 - 20
795 0-5
733 5 - 7.5
785 7.5 - 10
661 10 - 15
613 15 - 20

2.0 1,913

1.7 1,619

0.8 785

1.2 554

1.0 460

0.4 394
High
High
Very High
k Very High

0.6 603 High

3.7 3,514

7.7 3,708

6.0 2,874

4.4 4,247

12.0 11,462 Negligible

0.4 393

0.4 187

0.6 287

0.2 215

0.3 302

0.6 575 High

0.8 402 Very High

2.1 1,005 Moderate

0.5 431

0.5 448

0.9 823 High

2.4 1,128 Moderate

2.0 965

0.9 838

1.1 1,018 Moderate

0.8 795

1.3 633

2.1 1,001 Moderate
•
•
•
Mild
Mild
Mild
Mild
Very High
Very High
Very High
Very High
Very High
Very High
Very High
High
High
High
High

0.5 502

0.5 503
High
dm -
▪ High
V&A Project No. 15-0024 Appendix B. In -Situ Soil Resistivity Complete Results 09/23/2025
B-3
C5 Page 803 of 1112

:1 V&A
City of Vista, California
Pump Station Condition Assessments Draft Report
Site
Number
18 19
20 Depth
(feet)
5 7.5
10 15
20 5

7.5 10
15 20
5 7.5
10 15
20 Resistance
to Depth,
Meter
Reading
(ohm)

0.42 0.29

0.24 0.15

0.11 1.38

1.01 0.85

0.36 0.22

0.35 0.20

0.15 0.12

0.08 Resistivity
to Depth
(ohm -cm)
Layer
(feet)
402 0-5
417 5-7.5
460 7.5 - 10
431 10 - 15
421 15-20
1,321 0 - 5
1,451 5 - 7.5
1,628 7.5 - 10
1,034 10 - 15
843 15 - 20
335 0-5
287 5 - 7.5
287 7.5 - 10
345 10 - 15
306 15 - 20
Resistance
of Soil
Layer
(ohm)
Resistivity
of Soil
Layer
(ohm -cm)

0.4 402

0.9 449

1.4 666

0.4 383

0.4 395

1.4 1,321

3.8 1,804
Degree of
Corrosivity
for Layer
High
Moderate
Moderate

5.4 2,569 Mild
iu

0.6 598 I High

0.6 542 a High

0.4 335 "'try High

0.5 223 Very High

0.6 287 Very High

0.6 575 High

0.2 230 Very High
V&A Project No. 15-0024 Appendix B. In -Situ Soil Resistivity Complete Results 09/23/2025
B-4
C5 Page 804 of 1112

APPENDIX C. PROJECT X CORROSION

ENGINEERING SOIL ANALYSIS REPORT
As mentioned in Section 3.5, attached are the results of the soil sample analysis for the BCPS.

V&A Project No. 15-0024 Appendix C. Project X Corrosion Engineering Soil Analysis Report 09/23/2025
C5 Page 805 of 1112

09/23/2025
C5 Page 806 of 1112

X
Project X
Corrosion Engineers
Soil & Condition Assessment Corrosion Engineering
REPORT S160216A

Page 1 ends

City of Vista Rehab
February 22, 2016
PREPARED FOR:

MICHAEL SHERMAN

V&A ENGINEERING
11011 VIA FRONTERA SUITE C
SAN DIEGO, CA 92127
mshermangvaengineering. corn
Client Job Number: 15-0024
Project X Job Number: S 160216A
09/23/ 2gechnology Dr, Suite 105F, Murrieta, CO62563 Tel: 213-928-7213 F 4 2.8tObf 1112 www.projectxcorrosion.com

Project X
Corrosion Engineers
Soil & Condition Assessment — Corrosion Engineering
REPORT S160216A

Page 2 ends