LIGHT FIXTURE SAFETY WIRE SUPPORT HOLE TYPICAL.

EXPOSED T-BAR CEILING SYSTEM, HEAVY DUTY GRID
TYPICAL.
5/16'' DIA. DRILL-IN EXPANSION ANCHOR (TO CONCRETE)
OR (2) #8 x 1/2'' SELF-TAPPING SCREWS (TO METAL
DECKING).

ANCHOR TO

STRUCTURE
(TYPICAL)

CABLE DESCRIPTION
CIRCUIT'S ACTUAL VOLTAGE RATING.

CIRCUIT'S ACTUAL DESIGNATION.

SUBMIT COMPLETE AND PROPER

SCHEDULE OF THE CIRCUIT
DESIGNATIONS TO BE USED. PROVIDE

DESCRIPTIONS FOR EACH MANHOLE
INVOLVED.

CABLE'S ACTUAL PHASE DESIGNATION.

CABLE'S ACTUAL SIZE DESIGNATION.
1" HIGH POLYETHYLENE "BLANK" INSERT

TILE WITH YELLOW FINISH
1" HIGH POLYETHYLENE INSERT TILE WITH BLACK ON
YELLOW FINISH AND STANDARD BLOCK CHARACTERS.

TYPICAL CABLE IDENTIFICATION SHOWN.

PRIMARY CABLE WITH FIREPROOFING TAPE

POLYETHYLENE TAG HOLDER WITH BLACK FINISH

SELF-LOCKING NYLON TIE STRAP
KV

13.2 C TK Y ∅
B
/4 0

1. 2.

3. 4.
32 4
1 3''
12''
3''
3''3''
3''

BACKFILL COMPACT
TO 95% RELATIVE

DENSITY

SHOWN ON PLANS

CONDUIT(S) AS

WARNING TAPE

OR PAVING
MIN.
24''

FINISHED GRADE
3'' CONCRETE ENCASEMENT AT

PARKING LOT AND DRIVEWAYS
FOR ALL CONDUIT 2'' AND
LARGER. 3'' SAND ENCASEMENT

AT LANDSCAPED AREAS

EXACT DEPTH TO BE

DETERMINED IN FIELD

BY COORDINATION

WITH EXISTING
UTILITIES.

AN
TON

N A T H A NSON
Exp. 03/31/21

LATRICECLE
REE

REGISTERED PROFESSIONAL ENGIN

STATE OF CALIFORNIA
No. E 21090
9150 CHESAPEAKE DR, STE 220
SAN DIEGO, CA 92123
www.ELENconsulting.com
Description: Date:

Project Number:

Drawn By:

Checked By:

Sheet Title:

Approved By:

PROJECT:
6353 DEL CERRO BLVD., SAN DIEGO, CA 92120
619.698.9177 | www.jeffkatzarchitecture.com
005-104

FOR CONSTRUCTION

ELECTRICAL

DETAILS
200102
E4.1
AN
AN
KS

ADMINISTRATION

BUILDING

CITY OF VISTA PUBLIC

WORKS DEPARTMENT
1165 E TAYLOR ST.

VISTA, CA 92084
12" = 1'-0"1 ADA DETAIL
12" = 1'-0"2 GROUNDING DETAIL
12" = 1'-0"3 SIESMIC DETAIL
12" = 1'-0"4 CABLE TAG DETAIL
12" = 1'-0"5 TRENCH DETAIL
FOR

CONSTRUCTION
05/18/21

BLDG DEPT

SUBMITTAL
09/02/20

BLDG DEPT

RESUBMITTAL
11/25/20
BID SET 02/11/21
02/10/2026 C7 303 of 321

M
M DS
M DS
M
M
M DS
M
DS
1 2
2 34
1 2
3 4
5 6

1. REFER TO LIGHTING AND

POWER PLANS FOR QUANTITY

AND APPROXIMATE LOCATION

OF LIGHTING FIXTURES,

RECEPTACLES, DEVICES AND
CONTROLS.

2. WIRING CLASS AND TYPE CAN

VARY PER MANUFACTURER
AND CONTROL SYSTEM.

VERIFY ALL WIRING AND

CONTROLS WITH

MANUFACTURER PRIOR TO
INSTALLATION.

3. AUTOMATIC DAYLIGHTING

CONTROLS SHALL BE

INSTALLED ONLY IF THE TOTAL

COMBINED WATTAGE

INSTALLED IS GREATER THAN
120 WATTS AND IN ROOMS
THAT HAVE MORE THAN 24sq ft
OF GLAZING.

GENERAL NOTES
6 6
6 6

CEC REQUIREMENT NOTES
c
a
b
a
b
4 5
b b
6 6
6 6
c
4 5
a a
6 6
1 2
3 1
2 2
2 3

1. REFER TO LIGHTING AND

POWER PLANS FOR QUANTITY

AND APPROXIMATE LOCATION

OF LIGHTING FIXTURES,

RECEPTACLES, DEVICES AND
CONTROLS.

2. WIRING CLASS AND TYPE CAN

VARY PER MANUFACTURER
AND CONTROL SYSTEM.

VERIFY ALL WIRING AND

CONTROLS WITH

MANUFACTURER PRIOR TO
INSTALLATION.

3. AUTOMATIC DAYLIGHTING

CONTROLS SHALL BE

INSTALLED ONLY IF THE TOTAL

COMBINED WATTAGE

INSTALLED IS GREATER THAN
120 WATTS AND IN ROOMS
THAT HAVE MORE THAN 24sq ft
OF GLAZING.

GENERAL NOTES
6 6
6 6
4 4
5 6

CEC REQUIREMENT NOTES
6 4
5 4 5
6 6
6 6
6 4
6 6

OCCUPANCY SENSOR
*per section 130.1(C)

PLUG LOAD CONTROL
*per section 130.5 (D)

DAYLIGHT

HARVESTING
*per section 130.1(D)

SWITCH WITH ON/OFF

RAISE/LOWER
*per section 130.1(A)

RELAY MODULE WITH ON/OFF

DIMMING
*per section 130.1(B)

AUTOMATIC DEMAND

RESPONSE
*per section 130.1(E)
Dab
N

SECONDARY DAYLIGHTNIG ZONE
277/120VAC DIMMING
GRN
BLUE
W
H
T
■B
L
K
/
O
R
N
BL
U
E
N H

CONTINUE

AS REQ'D

SEE PLANS
N

PRIMARY DAYLIGHTNIG ZONE
277/120VAC DIMMING
GRN
BLUE

CONTINUE

AS REQ'D

SEE PLANS
BLUE
W
H
T
BL
K
BL
U
E
N H

CONTINUE

AS REQ'D

SEE PLANS
W
H
T
*B
L
K
/
O
R
N
BL
U
E
N H

NOTE DESCRIPTION
16 AMP RELAY PACK WITH DIMMING CONTROL
16 AMP RELAY PACK FOR PLUG LOAD CONTROL

ON/OFF SWITCH WITH DIMMING

NOTE DESCRIPTION
STANDARD RANGE 360° SENSOR-CEILING MOUNT

AUTOMATIC DIMMING CONTROL PHOTOCELL- CEILING MOUNT
CONTROL WIRE - CAT5/6, 0-10V, OR LINE VOLTAGE
(PER MANUFACTURER REQUIREMENTS)
■ BLK - 120VAC OR ORN - 277VAC

SCHEMATIC OF TYPICAL CEILING-MOUNTED MOTION & DAYLIGHT - WIRING DIAGRAM PLUG

LIGHTING

LIGHTING
GRN

BILL OF MATERIAL
N
c

CONTINUE AS REQ'D

SEE PLANS

SCHEMATIC OF TYPICAL CEILING-MOUNT WITH MANUAL DIMMING - WIRING DIAGRAM

BILL OF MATERIAL

NOTE DESCRIPTION
16 AMP RELAY PACK WITH DIMMING CONTROL
16 AMP RELAY PACK FOR PLUG LOAD CONTROL

ON/OFF SWITCH WITH DIMMING
Dabc
N

SECONDARY DAYLIGHTNIG ZONE
277/120VAC DIMMING
GRN
BLUE
W
H
T
■B
L
K
/
O
R
N
BL
U
E
N H

CONTINUE AS
REQ'D

SEE PLANS
N

PRIMARY DAYLIGHTNIG ZONE
277/120VAC DIMMING
GRN
BLUE

CONTINUE

AS REQ'D
SEE
PLANS
W
H
T
■B
L
K
/
O
R
N
BL
U
E
N H
BLUE
W
H
T
BL
K
BL
U
E
N H

CONTINUE

AS REQ'D

SEE PLANS

NMANUAL
277/120VAC DIMMING
GRN
BLUE

CONTINUE

AS REQ'D

SEE PLANS
W
H
T
■B
L
K
/
O
R
N
BL
U
E
N H
■ BLK - 120VAC OR ORN - 277VAC

NOTE DESCRIPTION
STANDARD RANGE 360° SENSOR-CEILING MOUNT

AUTOMATIC DIMMING CONTROL PHOTOCELL- CEILING MOUNT
CONTROL WIRE - CAT5/6, 0-10V, OR LINE VOLTAGE
(PER MANUFACTURER RECOMMENDATION)
N
c
b
a

OCCUPANCY SENSOR
*per section 130.1(C)

PLUG LOAD CONTROL
*per section 130.5 (D)

DAYLIGHT

HARVESTING
*per section 130.1(D)

SWITCH WITH ON/OFF

RAISE/LOWER
*per section 130.1(A)

RELAY MODULE WITH ON/OFF

DIMMING
*per section 130.1(B)

AUTOMATIC DEMAND

RESPONSE
*per section 130.1(E)
GRN
c
b
a
PLUG

LIGHTING
a a
b
b
d
c
d
d

LIGHTING

LIGHTING

CONTINUE

AS REQ'D

SEE PLANS
AN
TON

N A T H A NSON
Exp. 03/31/21

LATRICECLE
REE

REGISTERED PROFESSIONAL ENGIN

STATE OF CALIFORNIA
No. E 21090
9150 CHESAPEAKE DR, STE 220
SAN DIEGO, CA 92123
www.ELENconsulting.com
Description: Date:

Project Number:

Drawn By:

Checked By:

Sheet Title:

Approved By:

PROJECT:
6353 DEL CERRO BLVD., SAN DIEGO, CA 92120
619.698.9177 | www.jeffkatzarchitecture.com
005-104

FOR CONSTRUCTION

ELECTRICAL

DETAILS
200102
E4.2
AN
AN
KS

ADMINISTRATION

BUILDING

CITY OF VISTA PUBLIC

WORKS DEPARTMENT
1165 E TAYLOR ST.

VISTA, CA 92084
SCALE:12" = 1'-0"E4.2
1 CONTROL DIAGRAMS
FOR

CONSTRUCTION
05/18/21

BLDG DEPT

SUBMITTAL
09/02/20

BLDG DEPT

RESUBMITTAL
11/25/20
BID SET 02/11/21
02/10/2026 C7 304 of 321

FIRST LEVEL CORR.

MSB-3150A. 3P.

ELECTRICAL SERVICE

ALL LETTERS ARE CAPITAL
LINE 2 - EQUIPMENT BEING SERVED
LINE 1 -DISCONNECT NAME
LINE 3 - SIZE OF FEEDER / FEEDER
NO.

BLACK ON WHITE
LAMINATED PLASTIC 3/32''
THICK MIN. WITH BEVELED
EDGE

CADMIUM OR STAINLESS
STL. ROUNDHEAD SCREWS

DISCONNECT
FIRST LEVEL CORR.

MSB-3150A. 3P.

PANEL A

ALL LETTERS ARE CAPITAL
LINE 2 -LOCATION OF EQUIPMENT
BEING SERVED (SW. BD. NP'S ONLY)
LINE 1 -EQUIPMENT NAME
LINE 3 - SIZE OF FEEDER / FEEDER
NO.

BLACK ON WHITE
LAMINATED PLASTIC 3/32''
THICK MIN. WITH BEVELED
EDGE

CADMIUM OR STAINLESS
STL. ROUNDHEAD SCREWS
PANELS

DISCONNECTING
MEANS _ OF _
3"1" Min.
3"1" Min.

PER PLAN

RATED FIREWALL
APPROVED U.L. LISTED FIRESTOP

MATERIAL, INSTALLED IN

CONFORMANCE WITH

MANUFACTURER'S INSTRUCTIONS
MAX 1-1/2" DIAMETER

STEEL CONDUIT
F RATING = 1 OR 2 HOUR
T RATING = 1 HOUR

PER PLAN

RATED FIREWALL
APPROVED U.L. LISTED FIRESTOP

MATERIAL, INSTALLED IN

CONFORMANCE WITH

MANUFACTURER'S INSTRUCTIONS
MAX 2" DIAMETER

STEEL CONDUIT
F RATING = 1 OR 2 HOUR
T RATING = 1 HOUR
FIRE STOPPING DETAIL FOR 2" CONDUIT
FIRE STOPPING DETAIL FOR 1" AND SMALLER CONDUIT
TO BE CONSISTENT WITH U.L. PENETRATION
FIRESTOP SYSTEM No. W-L-1050 FOR WALL

ASSEMBLY - PER ARCHITECTURAL PLANS
TO BE CONSISTENT WITH U.L. PENETRATION
FIRESTOP SYSTEM No. W-L-1012 FOR WALL

ASSEMBLY - PER ARCHITECTURAL PLANS

BUR MEMBRANE

ROOFING

CONDUIT, SEE DRAWINGS

FOR LOCATION & SIZE

SEALANT
24 G.A. 24 G.I. FLASHING SET
ON MASTIC OVER ROOFING.

STRIP IN WITH BASE

FLASHING
ROOF
4" MIN.
2" 2"
12"

PLYWOOD ROOF
1 THREADED HUB.

GALVANIZED PIPE STRAP, TYP.

RGS CONDUIT.

BUILDINGS WALL.

TRANSITION COUPLING.

FINISH GRADE.

WHERE NECESSARY.

WEATHERPROOF BOX. JUNCTION
BOX SIZED PER NEC.

PAINT CONDUITS AND JUNCTION BOX
TO MATCH EXISTING WALL SURFACE.
9 2
3 4
5 6
7 8
NOTES:
1 8
2 4
3 TYP.
5 76

MOUNT DISCONNECT DIRECTLY

TO UNIT AT POINT OF

CONNECTION PROVIDED

FOR DISCONNECT SIZE REFER
TO ELECTRICAL ROOF PLAN.

CONDUIT TO

POWER SOURCE

ROOFTOP UNIT AS

NOTED ON ROOF
PLANS

HVAC UNIT

SERVICE
PANEL
ROOF
LIGHTING CONTROL DIAGRAM NOTES:

LIGHTING CONTROL PANEL 'LCP' PANEL SCHEDULE

LIGHTING CIRCUIT
''P2''
PANEL
LVHV
P1-16
RM #111
WALL

MOUNTED

PHOTOCELL
ROOF

MOUNTED

NORTH FACING

PHOTOCELL

EXTERIOR LIGHTING CIRCUIT WITH PHOTOCELL ''ON'' TIME CLOCK 12 LIGHTING BRANCH CIRCUIT PANEL ''P2''.

LIGHTING CONTROL PANEL ''LCP''.1
2 1
''OFF' CONTROL.

NO.
-
P-2
NO.

RELAY
2 3
1 CIRCUIT
PANEL
-
-5
4 6
LIGHTING AREA SERVEDNO.

ZONE
2 3
1 5
4 --
NOTES
TYPE &
1 1

CONTROL
1 1
-5 6
----
2 --
PROVIDE PANEL WITH U.L. LISTED AND APPROVED VOLTAGE5
BARRIER.

CONTACT INPUT PHOTOCELL3
EXTERIOR CONTACT INPUT PHOTOCELL4
3 1
1 4
INTERIOR TIME CLOCK ''ON'', TIME CLOCK ''OFF'' CONTROL. 3 EXTERIOR FACADE LIGHTING
---
--
--
J
CR
12"
48"
FLOOR, REF.

LINE OF
AND FRAME, REF.

SINGLE DOOR

AND BLOCK LAYOUT

STRUCTURAL STEEL

WITH THE

COORDINATE
AS REQUIRED4S RECESSED BOX

AND BLANK COVER
WITH 1/2" KNOCK

OUT FOR CARD
READER

MORTISE LOCK

WITH HANDLE
(L-LOCK) DOOR

TO BE DRILLED

BY OTHERS
POWER

TRANSFER
HINGE

SECURITY DOOR

CONTACT DEVICES
(BY OTHERS)
DOOR CONTACT 3" FROM

LATCH SIDE OF DOOR

UNLESS THE DOOR IS
METAL, THEN 6" FROM

LATCH SIDE OF DOOR EDGE
NOTE:

CARD READERS SHALL HAVE

MANUAL OVERRIDE FOR

EXITING IN CASE OF POWER
OUTAGE.

CEILING LINE
4x4 J-BOX, MOUNT ON

SECURE SIDE
3/4" IN EMT
NOTE:

VERIFY ALL REQUIREMENTS WITH
SECURITY SHOP DRAWINGS.
3/4" IN EMT
AN
TON

N A T H A NSON
Exp. 03/31/21

LATRICECLE
REE

REGISTERED PROFESSIONAL ENGIN

STATE OF CALIFORNIA
No. E 21090
9150 CHESAPEAKE DR, STE 220
SAN DIEGO, CA 92123
www.ELENconsulting.com
Description: Date:

Project Number:

Drawn By:

Checked By:

Sheet Title:

Approved By:

PROJECT:
6353 DEL CERRO BLVD., SAN DIEGO, CA 92120
619.698.9177 | www.jeffkatzarchitecture.com
005-104

FOR CONSTRUCTION

ELECTRICAL

DETAILS
200102
E4.3
AN
AN
KS

ADMINISTRATION

BUILDING

CITY OF VISTA PUBLIC

WORKS DEPARTMENT
1165 E TAYLOR ST.

VISTA, CA 92084
12" = 1'-0"1 NAMEPLATE DETAIL
12" = 1'-0"2 PENETRATION DETAILS
12" = 1'-0"3 ROOF PENETRATION DETAIL
12" = 1'-0"4 ROOF RECEPTACLE DETAIL
12" = 1'-0"5 DISCONNECT MOUNTING DETAIL
12" = 1'-0"6 LIGHTING CONTROL PANEL
12" = 1'-0"7 CARD READER DETAIL
FOR

CONSTRUCTION
05/18/21

BLDG DEPT

SUBMITTAL
09/02/20

BLDG DEPT

RESUBMITTAL
11/25/20
BID SET 02/11/21
02/10/2026 C7 305 of 321

AN
TON

N A T H A NSON
Exp. 03/31/21

LATRICECLE
REE

REGISTERED PROFESSIONAL ENGIN

STATE OF CALIFORNIA
No. E 21090
9150 CHESAPEAKE DR, STE 220
SAN DIEGO, CA 92123
www.ELENconsulting.com
Description: Date:

Project Number:

Drawn By:

Checked By:

Sheet Title:

Approved By:

PROJECT:
6353 DEL CERRO BLVD., SAN DIEGO, CA 92120
619.698.9177 | www.jeffkatzarchitecture.com
005-104

FOR CONSTRUCTION
TITLE 24
200102
E5.1
AN
AN
KS

ADMINISTRATION

BUILDING

CITY OF VISTA PUBLIC

WORKS DEPARTMENT
1165 E TAYLOR ST.

VISTA, CA 92084
FOR

CONSTRUCTION
05/18/21

BLDG DEPT

SUBMITTAL
09/02/20

BLDG DEPT

RESUBMITTAL
11/25/20
BID SET 02/11/21
02/10/2026 C7 306 of 321

AN
TON

N A T H A NSON
Exp. 03/31/21

LATRICECLE
REE

REGISTERED PROFESSIONAL ENGIN

STATE OF CALIFORNIA
No. E 21090
9150 CHESAPEAKE DR, STE 220
SAN DIEGO, CA 92123
www.ELENconsulting.com
Description: Date:

Project Number:

Drawn By:

Checked By:

Sheet Title:

Approved By:

PROJECT:
6353 DEL CERRO BLVD., SAN DIEGO, CA 92120
619.698.9177 | www.jeffkatzarchitecture.com
005-104

FOR CONSTRUCTION
TITLE 24
200102
E5.2
AN
AN
KS

ADMINISTRATION

BUILDING

CITY OF VISTA PUBLIC

WORKS DEPARTMENT
1165 E TAYLOR ST.

VISTA, CA 92084
FOR

CONSTRUCTION
05/18/21

BLDG DEPT

SUBMITTAL
09/02/20

BLDG DEPT

RESUBMITTAL
11/25/20
BID SET 02/11/21
02/10/2026 C7 307 of 321

AN
TON

N A T H A NSON
Exp. 03/31/21

LATRICECLE
REE

REGISTERED PROFESSIONAL ENGIN

STATE OF CALIFORNIA
No. E 21090
9150 CHESAPEAKE DR, STE 220
SAN DIEGO, CA 92123
www.ELENconsulting.com
Description: Date:

Project Number:

Drawn By:

Checked By:

Sheet Title:

Approved By:

PROJECT:
6353 DEL CERRO BLVD., SAN DIEGO, CA 92120
619.698.9177 | www.jeffkatzarchitecture.com
005-104

FOR CONSTRUCTION
TITLE 24
200102
E5.3
AN
AN
KS

ADMINISTRATION

BUILDING

CITY OF VISTA PUBLIC

WORKS DEPARTMENT
1165 E TAYLOR ST.

VISTA, CA 92084
FOR

CONSTRUCTION
05/18/21

BLDG DEPT

SUBMITTAL
09/02/20

BLDG DEPT

RESUBMITTAL
11/25/20
BID SET 02/11/21
02/10/2026 C7 308 of 321

CONDUIT STUBOUT

CONDUIT RISING UP

CONDUIT DROP DOWN
#8
CONDUIT CONCEALED IN WALLS OR CEILING.

FLEXIBLE CONDUIT
HOMERUN TO PANEL AND CIRCUITS INDICATED.

CROSSMARKS DENOTE QUANTITY OF NEUTRAL
(LONG), PHASE (SHORT), AND GROUND (DOT)
CONDUCTORS IN BRANCH CIRCUIT CONDUIT. NO

CROSSMARKS DENOTES PHASE, NEUTRAL, AND
GROUND WIRES. NUMBER ADJACENT TO CROSSMARKS
DENOTES WIRE SIZE OTHER THAN #12 FOR ALL
CONDUCTORS UNO.

DETAIL NUMBER DESIGNATION

SHEET ON WHICH DETAIL IS FOUND
E1
3 SHEET NOTE REFERENCE

GENERAL SYMBOLS LEGEND
A-1
1 CONDUIT CONCEALED IN FLOOR, UNDERFLOOR,

OR BELOW GRADE

ELECTRICAL ABBREVIATIONS

PULL BOX
PHASE
POLE

NOT TO SCALE
PH.

P
PB
NTS
ATS
C
AFF
ALT.

A

AUTOMATIC TRANSFER SWITCH

ABOVE FINISHED FLOOR

CONDUIT

AMPERES

ALTERNATE
PANEL

RECEPTACLE

REQUIRED

RIGID GALVANIZED STEEL

POST INDICATOR VALVE

POINT OF CONNECTION

SECURITY

SWITCHGEAR

TYPICAL

TERMINAL CABINET

UNDER COUNTER

TELEPHONE

UNLESS NOTED OTHERWISE
WATTS
VOLTS

TRANSFORMER

NEW LOCATION OF EXISTING ITEM

WEATHERPROOF

WATER HEATER
PNL
PIV
RECEPT
RGS
SEC
UNO
TYP
U.C.

TEL.

TC
CONC.

CB
C.O.

CKT.

DWG.

DIST.

GFI
FA
HORIZ.

JB
LTG.

MCA

GROUND FAULT INTERRUPTER

HORIZONTALLY MOUNTED

LIGHTING

JUNCTION BOX

CONDUIT ONLY

EMERGENCY SERVICE

FIRE ALARM

CONCRETE

DRAWING

DISTRIBUTION

CIRCUIT BREAKER

CIRCUIT

MINIMUM CIRCUIT AMPS W
WP
V
W.H.

XL
MTD.

MCC
MOP
MTG. HT.

NL
NIC

NIGHT LIGHT

NOT IN CONTRACT

MOTOR CONTROL CENTER

MOUNTED

MOUNTING HEIGHT

MAXIMUM OVERCURRENT PROTECTION
XFMR
SWGR.

REQ'D
POC

OWNER FURNISHED, CONTRACTOR INSTALLEDOFCI

CFCI CONTRACTOR FURNISHED, CONTRACTOR INSTALLED

FLA FULL LOAD AMPS
SOLID NEUTRALS.N.

EXISTING TO BE RELOCATEDXR

EXISTING TO REMAINX

EXISTING TO BE DEMOLISHEDXD

CU COPPER

EG EQUIPMENT GROUND

TAMPER RESISTANTTR
EXIST. EXISTING
EM

ON CENTEROC

MEP MECHANICAL, ELECTRICAL, PLUMBING
TENANT IMPROVEMENTT.I.

UNDERWRITERS LABORATORYUL

CFL COMPACT FLUORESCENT LAMP

REFLECTED CEILING PLANRCP

ADA AMERICANS WITH DISABILITIES ACT

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

KVA KILOVOLT-AMPERES

KW KILOWATTS

HP HORSEPOWER

L LOCKABLE

EX EXISTING

NON-FUSIBLE DISCONNECT SWITCH
(RATINGS AS NOTED)

FUSIBLE DISCONNECT SWITCH
(RATINGS AS NOTED)
M
T
J

CIRCUIT BREAKER CALLOUT

FUSE CALLOUT
-POLE
-TRIP SIZE
-FUSE SIZE
-POLE

NON-FUSIBLE DISCONNECT SWITCH (RATINGS AS NOTED)

FUSIBLE DISCONNECT SWITCH (RATINGS AS NOTED)

COMBINATION FUSIBLE DISCONNECT SWITCH AND MOTOR
STARTER, (NEMA SIZE AS NOTED), 3P, 600 VAC MAXIMUM
RATING.

T TOGGLE TYPE FRACTIONAL HP MANUAL MOTOR STARTER

WITH THERMAL OVERLOADS (DELETED IF FOR

DISCONNECT USE ONLY) AND HANDLE GUARD/LOCK-OFF,
2 POLES (VERIFY WITH BRANCH CIRCUIT).

MOTOR
GROUND

CIRCUIT BREAKER

TRANSFORMER DELTA PRIMARY, WYE
SECONDARY WITH kVA RATING
GFP

SPD SURGE PROTECTION DEVICE

GROUND FAULT PROTECTION

ENCLOSED CIRCUIT BREAKER

SINGLE LINE LEGEND

TC TIME CLOCK

KILOWATT-HOUR METER

FUSED SWITCH

MOTOR STARTER (NEMA SIZE AS NOTED)
CB

AUTOMATIC TRANSFER
SWITCH

PANEL BOARD
2 2
3 225
150
3 EPO - EMERGENCY POWER OFF BUTTON

PANEL BOARD (SURFACE)

SWITCHBOARD OR MCC

POWER LEGEND

PANEL BOARD (FLUSH)

TRANSFORMER

JUNCTION BOX
LCP

LOW VOLTAGE PANEL

LIGHTING CONTROL PANEL
TELEPHONE BACKBOARD. 3/4'' PLYWOOD, LENGTH AND
WIDTH AS NOTED.

EQUIPMENT SIZES SHOWN ON PLANS ARE NOT EXACT. CONTRACTOR IS

RESPONSIBLE FOR ENSURING EQUIPMENT CLEARANCES ARE MET BASED ON ACTUAL SIZE OF EQUIPMENT.

PHOTOVOLTAIC LEGEND
G N

INVERTER
G
G

PV MODULE
PV ARRAY: S#.#-#
MPPT

STRING NUMBER

ASSOCIATED INVERTER

TOTAL SYSTEM WATTAGE

MODULE DC NAMEPLATE

INVERTER AC NAMEPLATE

ANNUAL PRODUCTION

88.8 KW
168 KW
133 MWh
AN
TON

N A T H A NSON
Exp. 03/31/21

LATRICECLE
REE

REGISTERED PROFESSIONAL ENGIN

STATE OF CALIFORNIA
No. E 21090
9150 CHESAPEAKE DR, STE 220
SAN DIEGO, CA 92123
www.ELENconsulting.com
Description: Date:

Project Number:

Drawn By:

Checked By:

Sheet Title:

Approved By:

PROJECT:
6353 DEL CERRO BLVD., SAN DIEGO, CA 92120
619.698.9177 | www.jeffkatzarchitecture.com
005-104

FOR CONSTRUCTION

ELECTRICAL PV

SYMBOLS
200102
PV0.1
AN
AN
MG

ADMINISTRATION

BUILDING

CITY OF VISTA PUBLIC

WORKS DEPARTMENT
1165 E TAYLOR ST.

VISTA, CA 92084
FOR

CONSTRUCTION
05/18/21

BLDG DEPT

SUBMITTAL
09/02/20

BLDG DEPT

RESUBMITTAL
11/25/20
BID SET 02/11/21
02/10/2026 C7 309 of 321

ALUMINUM CONDUCTOR INSTALLATION NOTES

1. MINIMUM WIRE SIZE FOR POWER LINES WHEN IMPLEMENTING ALUMINUM AS A CONDUCTOR SHALL BE #4 AWG STRANDED, COMPACT ELECTRICAL GRADE AA-8000 SERIES ALLOY.

2. ALUMINUM POWER CABLE, WIRE CONNECTORS, AND INSULATING AND CODING TAPE MANUFACTURERS SHALL BE APPROVED BY CLIMATEC PRIOR TO USAGE.

3. WHERE BOLTED CONNECTIONS ARE NOT POSSIBLE, MECHANICAL SCREW STYLE

LUGS AND TERMINATIONS ARE APPROVED ONLY WHEN USED IN CONJUNCTION WITH A LISTED COPPER PIGTAIL COMPRESSION ADAPTOR. USE OF A "ONE-SHOT" CRIMPER OR "DIE-LESS CRIMPERS" WILLNOT BE ALLOWED

4. COMPRESSION STYLE LUGS AND TERMINATIONS SHALL BE RATED FOR THE MAXIMUM DC VOLTAGE OF THE SYSTEM.

4.1. MUST BE PRE-FILLED WITH OXIDE INHIBITOR.

4.2. WIRE STRIPPING AND BRUSHING OF CONDUCTOR IN ACCORDANCE WITH VENDOR SPECS IS REQUIRED IMMEDIATELY PRIOR TO LUG INSTALLATION.

4.3. OXIDE INHIBITOR MUST BE APPLIED TO EXPOSED CONDUCTOR IMMEDIATELY

AFTER STRIPPING AND BRUSHING AND IMMEDIATELY PRIOR TO INSTALLATION OF THE LUG.

4.4. USE COMPRESSION TOOL LISTED FOR USE WITH SELECTED COMPRESSION CONNECTOR.

4.5. COLD SHRINK SHALL BE APPLIED TO COVER ANY EXPOSED WIRE SURFACE AT THE JUNCTION WHERE THE WIRE MEETS THE TERMINAL.

4.6. ALL CONNECTORS AND CORRESPONDING CRIMPING TOOLS SHALL BE UL LISTED FOR THEIR SPECIFIC APPLICATION.

5. INSULATING AND COLOR CODING TAPE SHALL BE PREMIUM GRADE PRESSURE SENSITIVE VINYL, HEAT/COLD/MOISTURE/SUNLIGHT/ RESISTANT. INSULATING TAPE SHALL BE BLACK AND COLOR CODING TAPE SHALL BE FADE RESISTANT.

6. FOR ALUMINUM MV CONDUCTORS, WHERE USED, THE GUIDELINES IN THIS

SECTION PLUS GENERAL REQUIREMENTS FOR MV CONDUCTOR INSTALLATION SHALL APPLY.

GROUNDING

SEE ELECTRICAL DIAGRAM AND ELECTRICAL DETAILS FOR MORE GROUNDING INFORMATION.

1. ONLY ONE CONNECTION TO DC CIRCUITS AND ONE CONNECTION TO AC CIRCUITS WILL BE USED FOR SYSTEM GROUNDING (CEC 250-21) (REFERENCED TO THE SAME POINT).

2. EQUIPMENT GROUNDING CONDUCTORS AND SYSTEM GROUNDING

CONDUCTORS WILL HAVE AS SHORT A DISTANCE TO GROUND AS POSSIBLE AND A MINIMUM NUMBER OF TURNS.

3. NON-CURRENT CARRYING METAL PARTS SHALL BE CHECKED FOR PROPER GROUNDING; NOTING THAT TERMINAL LUGS BOLTED ON AN ENCLOSURE'S FINISHED SURFACE MAY BE INSULATED BECAUSE OF PAINT/FINISH.

PAINT/FINISH AT POINT OF CONTACT SHALL BE PROPERLY REMOVED.

4. RACKING COMPONENTS AND STRUCTURAL SUPPORTS MUST BE ELECTRICALLY BONDED TOGETHER BY AN ACCEPTABLE MEANS.

5. MODULES SHALL BE GROUNDED WITH EQUIPMENT GROUNDING CONDUCTORS

BONDED TO A LOCATION APPROVED BY THE MANUFACTURER WITH A MEANS OF BONDING LISTED FOR THIS PURPOSE.

6. THE CONNECTION TO THE MODULE OR PANEL OF THIS PROPOSED SOLAR

ELECTRIC SYSTEM SHALL BE SO ARRANGED THAT REMOVAL OF A MODULE OR

A PANEL FROM THE PHOTOVOLTAIC SOURCE CIRCUIT DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER PHOTOVOLTAIC SOURCE CIRCUIT.

SETS OF MODULES INTERCONNECTED AS SYSTEMS RATED AT 50 VOLTS OR

LESS WITH OR WITHOUT BLOCKING DIODES, AND HAVING A SINGLE OVER CURRENT DEVICE SHALL BE CONSIDERED AS A SINGLE SOURCE CIRCUIT.

7. GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,

INCLUDING BUT NOT LIMITED TO GROUND RODS, GROUNDING LUGS, GROUNDING CLAMPS, ECT.

8. ALL GROUNDING CONNECTIONS SHALL BE RATED FOR DIRECT BURIAL (DB

RATED) , CONTRACTOR IS TO SUPPLY DOCUMENTATION PROVING THIS

DURRING PRODUCT SUBMITTALS
ELECTRICAL NOTES FOR NEW PHOTOVOLTAIC SYSTEM:

1. THIS PROPOSED SOLAR ELECTRIC SYSTEM IS INTENDED TO OPERATE IN PARALLEL WITH POWER RECEIVED FROM THE UTILITY SERVICE PROVIDER.

2. THE INVERTER FOR THE PROPOSED SOLAR ELECTRIC SYSTEM SHALL BE IDENTIFIED FOR USE IN SOLAR PHOTOVOLTAIC SYSTEMS. ALL EQUIPMENT SHALL BE UL APPROVED.

3. THIS SYSTEM IS INTENDED TO CONNECT TO THE EXISTING FACILITY POWER SYSTEM AT ONE POINT, POINT OF COMMON COUPLING (POCC). THIS CONNECTION SHALL BE IN COMPLIANCE WITH THE CEC ARTICLE 705.12 "POINT OF CONNECTION".

4. ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION FOR TESTING AND ISOLATION.

5. ALL DISCONNECTING COMBINERS SHALL BE SECURED FROM
UNAUTHORIZED/UNQUALIFIED PERSONNEL BY LOCK OR LOCATION.

6. ALL DISCONNECTING COMBINERS, PULL/SPLICE BOXES, AND ENCLOSURES SHALL BE LISTED FOR IT'S PURPOSE.

7. EQUIPMENT SHALL BE INSTALLED IN A SECURE AREA. INVERTER PERFORMANCE MAY BE AFFECTED IF INSTALLED IN DIRECT SUNLIGHT.

WIRING AND WIRING METHODS

ALL WIRING METHODS AND INSTALLATION PRACTICES SHALL CONFORM TO THE

NATIONAL ELECTRIC CODE, LOCAL STATE CODES, AND OTHER APPLICABLE LOCAL CODES

1. EXPOSED PV SOLAR PANEL WIRING WILL BE PV WIRE OR APPROVED EQUIVALENT, 90 DEGREE C, WET RATED AND UV RESISTANT. ALL EXPOSED

CABLES, SUCH AS MODULE LEADS SHALL BE SECURED WITH MECHANICAL OR OTHER SUN-LIGHT RESISTANT MEANS.

2. PV STRING HOME RUNS SHALL BE LABELED ON BOTH ENDS, AT ARRAY AND AT COMBINER. COMBINER OUTPUT CONDUCTORS SHALL BE LABELED AT BOTH ENDS, AT COMBINER AND AT DISCONNECT.

3. LIQUID TIGHT FLEXIBLE METAL CONDUIT IS GENERALLY SUITABLE FOR INSTALLATION IN WET AND DRY LOCATIONS. SHOULD IT BE EMPLOYED, SUPPORTS WILL BE NO MORE 12 INCHES FROM BOXES (JUNCTION BOX, CABINETS, OR CONDUIT FITTING) AND NO MORE THAN 36 INCHES APART (CEC 350.30)

4. THE PHOTOVOLTAIC SOURCE CIRCUITS AND PHOTOVOLTAIC OUTPUT CIRCUITS

OF THIS PROPOSED SOLAR SYSTEM SHALL NOT BE CONTAINED IN THE SAME

RACEWAY CABLE TRAY, CABLE, OUTLET BOX, JUNCTION BOX, OR SIMILAR

FITTING AS FEEDERS OR BRANCH CIRCUITS OF OTHER SYSTEMS UNLESS THE

CONDUCTORS OF THE DIFFERENT SYSTEMS ARE SEPARATED BY A PARTITION OR ARE CONNECTED TOGETHER.

5. UNLESS MARKED AS UV RESISTANT, PVC IS NOT APPROVED FOR INSTALLATION IN

LOCATIONS SUBJECTED TO DIRECT SUNLIGHT AND SHALL NOT BE EMPLOYED IN ANY SUCH LOCATION.

6. LONG STRAIGHT EXPOSED CONDUIT RUNS, 100 FEET OR MORE, SHALL HAVE EXPANSION FITTINGS INSTALLED PER CEC 300.7(B). EXPANSION FITTINGS SHALL ALSO BE USED WHEN CONDUIT SPANS AN EXPANSION JOINT.

7. FUSES AND WIRES SUBJECT TO TRANSFORMER INRUSH CURRENT SHALL BE SIZED ACCORDINGLY.

8. ALL D.C. MATERIALS SHALL BE UL LISTED FOR MAXIMUM DC SYSTEM VOLTAGE.

9. WHEN TRANSITIONING UNDERGROUND PVC CONDUIT TO ABOVE GROUND RMC, IMC OR EMT CONDUIT, USE 20 MIL PIPE WRAP TAPE HALF-LAPPED FROM 6” PAST TRANSITION POINT ON PVC TO 6” ABOVE GROUND ON METALLIC CONDUIT. AN EXPANSION JOINT SHALL BE USED IN THE TRANSITION TO ABOVE GROUND CONDUIT WHERE REQUIRED BY CEC 300.5(J).

10. ANY METAL SHAVINGS RESULTING FROM SITE WORK SHALL BE CLEANED FROM

ENCLOSURE INTERIORS, TOP SURFACES OF ENCLOSURE, ROOF SURFACE,

AND ANY ADDITIONAL AREAS WHERE OXIDATION OR CONDUCTIVE METAL

SHAVINGS MAY CAUSE RUST, ELECTRICAL SHORT CIRCUIT OR OTHER DAMAGE.

11. CONDUITS LONGER THAN 200' WITH NEGATIVE SLOPE TOWARD ELECTRICAL

EQUIPMENT SHALL HAVE A PULL BOX OR VAULT ADJACENT TO THE ENTRY POINT INTO THE ELECTRICAL EQUIPMENT.

12. WHEN TRANSITIONING FROM FREE AIR TO CONDUCTORS TO CONDUIT A LISTED FITTING SHALL BE USED TO PREVENT THE ENTRY OF MOISTURE.

13. ALL COPPER TERMINATION AC AND DC SHALL HAVE KOPR-SHIELD APPLIED.

14. ALL AC AND DC WIRING SHALL BE MEGGER TESTED BEFORE TERMINATING AT 1,000 VDC TO DEMONSTRATE A MINIMUM OF 250 MEGAOHMS RESISTANCE TO GROUND. DO NOT MEGGER THE SOLAR MODULES AS THEY WILL LIKLEY DAMAGE THEIR INTERNAL DIODES. MEGGERING IS INTENDED FOR ALL CONDUCTORS INSTALLED BY THE ELECTRICAL CONTRACTOR.

15. BENDS SHALL NOT DAMAGE THE RACEWAY OR SIGNIFICANTLY CHANGE THE INTERNAL DIAMETER OF RACEWAY (NO KINKS).

16. MODULE TO SOURCE CIRCUIT CONNECTORS MUST BE OF THE SAME MAKE AND MODEL AS THE MODULE TO MODULE CONNECTORS. THE CONNECTION TO

SOURCE CIRCUITS MUST BE PER THE MODULE MANUFACTURER AND CONNECTOR MANUFACTURER INSTRUCTIONS. CONTRACTOR TO VERIFY THAT

THE STRING CONDUCTOR DIAMETER IS COMPATIBLE WITH THE STRING CIRCUIT HOME RUN CONNECTORS.

17. SUPPORT CONDUCTORS IN VERTICAL CONDUITS IN ACCORDANCE WITH THE REQUIREMENT OF CEC 300.19.

18. ALL CRIMP TERMINATIONS SHALL BE 90 DEGREE C RATED.

19. CONNECTORS TO BE TORQUED PER DEVICE LISTING, OR MANUFACTURERS

RECOMMENDATIONS

20. SPLIT BOLTS/SPLICES/CONNECTORS SHALL BE INSULATED WITH APPROVED MEANS. UL LISTED ELECTRICAL TAPE ALONE IS NOT SUITABLE AS THE ONLY INSULATION MEANS. FOLLOW MANUFACTURERS INSTRUCTIONS FOR INSTALLATION, AND APPLICATION OF INSULATING PRODUCT.

21. ALL LV AC WIRING SHALL BE TYPE THWN-2 RATED AT 90 DEGREES C. XHHW-2 IS AN APPROVED ALTERNATE. THIS NOTE WILL BE SUPERCEDED BY ANY

INVERTER SPECIFICATIONS REQUIRING LV AC WIRE TO MEET HIGHER VOLTAGE OR INSULATION STANDARDS.

22. USE MEYERS HUB LISTED TO PROVIDE MOISTURE PROTECTION FOR CONDUIT ENTRANCES IN ALL APPLICABLE LOCATIONS AS REQUIRED BY CEC 314.15. ANY

CONDUIT ENTERING THE TOP OF AN ENCLOSURE SHALL HAVE A MYERS HUB CONNECTION.

23. PROTECT WIRE FROM SHARP EDGES WITH UV RATED SPIRAL WRAP, EDGEGUARD, OR SPLIT LOOM.

24. PROVIDE AN EQUIPMENT PAD FOR ALL ELECTRICAL EQUIPMENT. PAD IS TO EXTEND TO AT LEAST 8" OUTSIDE OF EQUIPMENT. WHERE EQUIPMENT IS NOT

INSTALLED ON LEVEL PAVEMENT, EQUIPMENT PAD IS TO BE BUILT SUCH THAT IT ENCOMPASSES THE EQUIPMENT WORKING CLEARANCE AS WELL.

9. ALL EQUIPMENT GROUNDS INSTALLED SHOULD BE COPPER ONLY

10. CEC ARTICLE 250.50 - GROUNDINGS EARTH RESISTANCE SHALL NOT EXCEED 25 OHMS. IF A SINGLE GROUND ROD, PIPE OR PLATE HAS EARTH RESISTANCE IN EXCESS OF 25 OHMS, SUPPLEMENTAL GROUNDING ELECTRODES SHALL BE ADDED AT 6FT MIN. INTERVALS ON ORDER TO ACHIEVE EARTH RESISTANCE OF LESS THAN 25 OHMS.

DAMAGE PROTECTION

1. THE ELECTRICAL CONTRACTOR SHALL CONSIDER THE WEATHERING OF

EQUIPMENT OVER TIME AND ELIMINATE THE POSSIBILITY OF DEGRADATION DUE TO CORROSION, WATER ENTRY AND UV EXPOSURE. AS A RESULT, THE USE OF

UNISTRUT OR SIMILAR MOUNTING SYSTEMS IS REQUIRED TO MOUNT

ENCLOSURES, PULL BOXES, LOAD CENTERS, FUSE BOXES, OR OTHER

EQUIPMENT

2. ALL NEMA 4 BOXES SHALL BE EQUIPPED WITH LISTED DRAIN PLUGS INSTALLED TO ALLOW WATER TO DRAIN. ANY MODIFICATION TO AS-MANUFACTURED

EQUIPMENT SHOULD BE DONE IN SUCH A WAY AS TO MAINTAIN ALL LISTED RATINGS.

3. ALL NEMA 3 BOXES SHALL BE EQUIPPED WITH A WEEP HOLE OR LISTED DRAIN

PLUGS INSTALLED TO ALLOW WATER TO DRAIN

4. ALL ELECTRICAL CONDUIT, EQUIPMENT AND COMPONENTS MUST BE

ADEQUATELY PROTECTED FROM DAMAGE AND VANDALISM BY THE USE OF BOLLARDS, SHIELDS, GUARDS OR OTHER ACCEPTABLE MEANS.

5. ALL CIRCUIT BREAKERS INSTALLED THAT ARE SUBJECT TO REVERSE POWER

FLOW SHALL BE LISTED AND LABELED AS BACKFEED COMPATIBLE

6. SOURCE CIRCUIT WIRING SHALL NOT BE SUPPORTED BY PLASTIC CABLE TIES

GROUND FAULT PROTECTION

1. PHOTOVOLTAIC INVERTERS SHALL BE EQUIPPED WITH D.C. GROUND FAULT PROTECTION TO REDUCE FIRE HAZARDS. INVERTERS ARE ALSO EQUIPPED

WITH ANTI-ISLANDING CIRCUITRY

DISCONNECTING MEANS

1. MEANS SHALL BE PROVIDED TO DISCONNECT ALL CURRENT CARRYING

CONDUCTORS OF THE PHOTOVOLTAIC POWER SOURCE FROM ALL OTHER CONDUCTORS IN THE BUILDING.

2. WHERE A CIRCUIT GROUNDING CONNECTION IS NOT DESIGNED TO BE

AUTOMATICALLY INTERRUPTED AS PART OF THE GROUND-FAULT
PROTECTION SYSTEM REQUIRED BY SECTION 690-5, A SWITCH OR CIRCUIT

BREAKER USED AS A DISCONNECTING MEANS SHALL NOT HAVE A POLE IN THE GROUNDED CONDUCTOR.

3. THE GROUNDED CONDUCTOR MAY HAVE A BOLTED OR TERMINAL

DISCONNECTING MEANS TO ALLOW MAINTENANCE OR TROUBLESHOOTING BY QUALIFIED PERSONNEL.

4. UNLESS DISCONNECT IS SERVICING A LINE-SIDE TAP, THE DISCONNECTING

MEANS SHALL NOT BE REQUIRED TO BE SUITABLE AS SERVICE EQUIPMENT AND SHALL BE RATED IN ACCORDANCE WITH SECTION 690-17.

5. EQUIPMENT SUCH AS PHOTOVOLTAIC SOURCE CIRCUITS, OVER CURRENT

DEVICES, AND BLOCKING DIODES SHALL BE PERMITTED ON THE
PHOTOVOLTAIC SIDE OF THE PHOTOVOLTAIC DISCONNECTING MEANS.

6. MEANS SHALL BE PROVIDED TO DISCONNECT EQUIPMENT SUCH AS

INVERTERS, BATTERIES, CHARGE CONTROLLERS, AND THE LIKE FROM ALL UNGROUNDED CONDUCTORS OF ALL SOURCES. IF THE EQUIPMENT IS

ENERGIZED FROM MORE THAN ONE SOURCE, THE DISCONNECTING MEANS SHALL BE GROUPED AND IDENTIFIED.

7. A SINGLE DISCONNECTING MEANS SHALL BE PERMITTED FOR THE COMBINED A.C. OUTPUT OF ONE OR MORE INVERTERS IN AN INTERACTIVE SYSTEM -

PROVIDED EACH INVERTER ASSOCIATED WITH THE DISCONNECT HAS ITS OWN INTERNAL AC DISCONNECT.

8. DISCONNECTING MEANS SHALL BE PROVIDED TO DISCONNECT A FUSE FROM

ALL SOURCES OF SUPPLY IF THE FUSE IS ENERGIZED FROM BOTH DIRECTIONS AND IS ACCESSIBLE TO OTHER THAN QUALIFIED PERSONS.

SUCH A FUSE IN A PHOTOVOLTAIC SOURCE CIRCUIT SHALL BE CAPABLE OF

BEING DISCONNECTED INDEPENDENTLY OF FUSES IN OTHER
PHOTOVOLTAIC SOURCE CIRCUITS.

9. ALL DISCONNECTS AND COMBINERS SHALL BE SECURED FROM

UNAUTHORIZED AND UNQUALIFIED PERSONNELL BY EITHER LOCK OR LOCATION.

REQUIRED SAFETY SIGNS AND LABELS

REQUIRED SAFETY SIGNS AND LABELS SHALL BE PERMAMENTLY ATTACHED BY ADHESIVE, OR OTHER MECHANICAL MEANS. LABELS SHALL COMPLY WITH ARTICLE 690 OF THE CEC OR OTHER APPLICABLE STATE AND LOCAL CODES.

SEE LABELS AND MARKING PAGE FOR MORE INFORMATION.

WEAR PPE APPROPRIATE FOR THE HAZARD: INSULATED GLOVES WITH

PROTECTORS, INSULATED MATS AND TOOLS

1. ANY SWITCH, FUSES, OR CIRCUIT BREAKERS THAT CAN BE ENERGIZED IN EITHER DIRECTION SHALL BE LABELED AS FOLLOWS:

WARNING:

ELECTRICAL SHOCK HAZARD DO NOT TOUCH TERMINALS.

TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE

ENERGIZED IN THE OPEN POSITION

2. THIS PHOTOVOLTAIC SYSTEM WILL BE EQUIPPED WITH DC DISCONNECTING COMBINERS WHICH WILL BE LABELED AS FOLLOWS:

PHOTOVOLTAIC

DISCONNECTING COMBINERS

3. THIS PHOTOVOLTAIC SYSTEM WILL BE EQUIPPED WITH AN A.C. DISCONNECT WHICH WILL BE LABELED AS FOLLOWS:

PHOTOVOLTAIC

DISCONNECTING MEANS
A.C. DISCONNECT

4. A MARKING SPECIFYING THE PHOTOVOLTAIC POWER SOURCE RATED AS

FOLLOWS SHALL BE PROVIDED AT AN ACCESSIBLE LOCATION AT THE DISCONNECTION MEANS FOR THE POWER SOURCE:

OPERATING CURRENT

OPERATING VOLTAGE

MAXIMUM SYSTEM VOLTAGE

SHORT CIRCUIT CURRENT

COMBINER
MARKINGS:

1. ALL INTERACTIVE SYSTEM POINTS OF INTERCONNECTION WITH OTHER

SOURCES SHALL BE MARKED AT AN ACCESSIBLE LOCATION AT THE DISCONNECTION MEANS.

2. A PERMANENT PLAQUE OR DIRECTORY SHALL BE PROVIDED IDENTIFYING THE

LOCATION OF THE SERVICE DISCONNECTION MEANS AND THE

PHOTOVOLTAIC SYSTEM DISCONNECTION MEANS, IF NOT LOCATED AT THE SAME LOCATION.

3. PHOTOVOLTAIC MODULES SHALL BE MARKED TO IDENTIFY LEAD POLARITY,

DEVICE RATINGS, AND SPECIFICATIONS FOR VOLTAGES, CURRENTS, AND POWER.

4. ALL REQUIRED EQUIPTMENT SHALL BE UL LISTED AND LABELED

ACCORDINGLY

DC WIRE MANAGEMENT

1. MODULE TO MODULE WIRE MANAGEMENT

1.1. CONDUCTORS SHALL BE SECURED TO MODULE FRAMES WITH STAINLESS STEEL WIRE CLIPS, CABLES OR EQUIVALENT. PLASTIC ZIP TIES ARE NOT APPROVED.

1.2. WIRE SHALL BE SECURED AND SUPPORTED AT A MINIMUM OF EVERY 4 FT OR ON EVERY MODULE.

1.3. WIRE SHALL BE SECURED IN A WAY THAT IT MAY NOT COME INTO CONTACT WITH ANY SHARP EDGES.

1.4. MODULE WIRING SHALL NOT BE UNDER STRAIN AT THE JUNCTION BOX, AND SHALL MEET ALL BENDING RADIUS REQUIREMENTS.

1.5. MODULE TO MODULE CONNECTORS, AND MODULE TO SOURCE
CONNECTORS SHALL BE SECURED OUT OF DIRECT SUNLIGHT.

2. ROW TO ROW WIRE MANAGEMENT

2.1. MODULE CIRCUITS AND STRING CIRCUITS SHALL BE PROTECTED FROM UV LIGHT AND PHYSICAL DAMAGE BETWEEN ROWS.

2.2. UNLESS OTHERWISE NOTED, THE FOLLOWING ARE SUITABLE TO PROTECT CONDUCTORS BETWEEN ROWS:

2.2.1. EMT, RMC, AND IMC CONDUIT (METAL RACEWAYS MUST USE

GROUND BUSHING AND PROTECTIVE BUSHINGS)

2.2.2. UV RESISTANT PVC CONDUIT

2.2.3. UV RESISTANT SPLIT CORRUGATED TUBING

2.2.4. UV RESISTANT LIQUID-TITE FLEXIBLE NONMETALLIC CONDUIT

2.3. WIRE SHALL BE BUNDLED SUCH THAT THE NUMBER OF

CONDUCTORS IN THE BUNDLE SHALL NOT EXCEED THE DERATED
AMPACITY OF THE CONDUCTORS.

3. CONDUIT ENTRANCE

3.1. WHERE SOURCE CIRCUITS ENTER CONDUIT THAT IS ROUTED TO

THE COMBINER BOX OR INVERTER, CONDUCTORS MUST PASS

THROUGH A WATER TIGHT STRAIN RELIEF SUCH AS THE HAYCO
MASTHEAD OR EQUIVALENT.

3.2. SOURCE CIRCUITS SHALL HAVE A "DRIP LOOP" IN THE WIRE BEFORE ENTERING THE CONDUIT.

SUPPLY SIDE TAP

1. SUPPLY SIDE TAP TO COMPLY WITH NEC 705.12(A)

2. SUPPLY SIDE TAP TO COMPLY WITH UL 891 AND CERTIFIED TO MAINTAIN THE UL LISTING OF SWITCHBOARD.

2.1 CERTIFICATION TO BE PREFORMED BY UL APPROVED INSPECTOR.

AN
TON

N A T H A NSON
Exp. 03/31/21

LATRICECLE
REE

REGISTERED PROFESSIONAL ENGIN

STATE OF CALIFORNIA
No. E 21090
9150 CHESAPEAKE DR, STE 220
SAN DIEGO, CA 92123
www.ELENconsulting.com
Description: Date:

Project Number:

Drawn By:

Checked By:

Sheet Title:

Approved By:

PROJECT:
6353 DEL CERRO BLVD., SAN DIEGO, CA 92120
619.698.9177 | www.jeffkatzarchitecture.com
005-104

FOR CONSTRUCTION

ELECTRICAL PV
NOTES
200102
PV0.2
AN
AN
MG

ADMINISTRATION

BUILDING

CITY OF VISTA PUBLIC

WORKS DEPARTMENT
1165 E TAYLOR ST.

VISTA, CA 92084
FOR

CONSTRUCTION
05/18/21

BLDG DEPT

SUBMITTAL
09/02/20

BLDG DEPT

RESUBMITTAL
11/25/20
BID SET 02/11/21
02/10/2026 C7 310 of 321

2"
1'-0"
11_
4"
3_
4"
1_
4"
2"
1'-0"
11_
4"
1"
3__
16"
11_
2"
41_
2"
3__
16"
3 7__
16"
2"
43_
4"
3__
16"
1"
43_
4"
3__
16"
41_
2"
1_
4"
3__
16"
5"
3__
16"
3__
16"
3__
16"
5"5"
1_
4"1_
4"
1_
4"1_
4"TO BE PLACED AT ALL 208VAC EQUIPMENT
208 VOLTS AC
CAUTION:

POWER TO THIS SERVICE IS ALSO SUPPLIED FROM

THE FOLLOWING SOURCES WITH DISCONNECTS AS
SHOWN
TO BE PLACED "UDS" AND "ACC-1"
600 VOLTS DC
3"

TO BE PLACED AT INVERTERS
SOLAR

PHOTOVOLTAIC
INVERTER INV-#

1. LABELS AND MARKINGS SHALL BE APPLIED

TO THE APPROPRIATE COMPONENTS IN

ACCORDANCE WITH THE NEC, SUN EDISON
STANDARDS AND CAL FIRE GUIDELINES.

2. SOLAR MODULES ARE SUPPLIED FROM THE

MANUFACTURER WITH MARKINGS

PRE-APPLIED TO MEET THE REQUIREMENTS
OF THE NEC.

3. TEXT LABELS WILL BE ETCHED WITH WHITE
GRAPHICS ONTO 1/16” RED PLASTIC
PLACARDS. THE LABEL WILL BE ATTACHED

TO THE APPROPRIATE COMPONENT

ENCLOSURES IN CONSPICUOUS PLACES
USING RIVITS.

4. ALL EXPOSED RACEWAYS, COVERS FOR

PULLBOX/JUNCTION BOXES AND CONDUIT

BODIES WITH ANY AVAILABLE UNUSED

CONDUIT OPENINGS SHALL BE LABELED WITH
THE WORDING "PHOTOVOLTAIC POWER
SOURCE"

POINT OF COMMON COUPLING
(POCC) PHOTOVOLTAIC LINE SIDE
TAP. FEEDER FROM DISCONNECT
"UDS"

ARC FLASH SHOCK HAZARD

XX INCHES FLASH HAZARD BOUNDARY
X.XX FLASH HAZARD AT 18 INCHES

CATEGORY X CLOTHING REQUIREMENTS
480VAC WHEN COVER IS REMOVED

XX GLOVE CLASS

XX INCHES LIMITED APPROACH

XX INCHES RESTRICTED APPROACH

XX INCHES PROHIBITED APPROACH

APPROPRIATE PPE REQUIRED

PROVIDE INPUT FROM ARC FLASH REPORT
PROVIDE SIGNAGE AT ALL DB1, ACC1, AND UDS

WARNING
ELECTRIC SHOCK HAZARD.

THE DC CONDUCTORS OF THIS

PHOTOVOLTAIC SYSTEM ARE

UNGROUNDED AND MAY BE
ENERGIZED.

TO BE PLACED AT EACH JUNCTION BOX,

COMBINER BOX, DISCONNECT, AND DEVICE

WHERE ENERGIZED, UNGROUNDED CIRCUITS

MAY BE EXPOSED DURING SERVICE

NO ADDITIONAL LOADS MAY BE
ADDED TO THIS SWITCHBOARD.

TO BE PLACED AT ALL 600VDC EQUIPMENT
TO BE PLACED AT DB1 AT POCC
TO BE PLACED AT "ACC-1"
6"
TO BE PLACED AT UTILITY DISCONNECT "UDS"

PHOTOVOLTAIC SYSTEM UTILITY
WARNING:

ELECTRIC SHOCK HAZARD. DO NOT TOUCH
TERMINALS. TERMINALS ON BOTH LINE AND

LOAD SIDE MAY BE ENERGIZED IN THE OPEN

POSITION
AC DISCONNECT RATINGS:

OPERATING CURRENT: 200A
OPERATING VOLTAGE: 208V/3P
MAXIMUM CURRENT: 250A
MAXIMUM VOLTAGE: 600V

SAFETY DISCONNECT SWITCH
6"
TO BE PLACED AT INVERTER INV-1, INV-2, INV-3 AND INV-4
CAUTION:

TERMINALS ON BOTH LINE AND LOAD SIDE

MAY BE ENERGIZED WHEN PHOTOVOLTAIC
MODULES ARE EXPOSED TO SUNLIGHT.

WARNING:

ELECTRIC SHOCK HAZARD IF A GROUND

FAULT IS INDICATED, NORMALLY GROUNDED

CONDUCTORS MAY BY UNGROUNDED AND
ENERGIZED.

MAXIMUM VOLTAGE: 600VDC
MAXIMUM CURRENT: 180ADC
OPERATING VOLTAGE: 450VDC
OPERATING CURRENT: 137.3ADC

PV ARRAYS

MAIN ELECTRICAL
ROOM
AN
TON

N A T H A NSON
Exp. 03/31/21

LATRICECLE
REE

REGISTERED PROFESSIONAL ENGIN

STATE OF CALIFORNIA
No. E 21090
9150 CHESAPEAKE DR, STE 220
SAN DIEGO, CA 92123
www.ELENconsulting.com
Description: Date:

Project Number:

Drawn By:

Checked By:

Sheet Title:

Approved By:

PROJECT:
6353 DEL CERRO BLVD., SAN DIEGO, CA 92120
619.698.9177 | www.jeffkatzarchitecture.com
005-104

FOR CONSTRUCTION

ELECTRICAL PV
LABELS
200102
PV0.3
AN
AN
MG

ADMINISTRATION

BUILDING

CITY OF VISTA PUBLIC

WORKS DEPARTMENT
1165 E TAYLOR ST.

VISTA, CA 92084
FOR

CONSTRUCTION
05/18/21

BLDG DEPT

SUBMITTAL
09/02/20

BLDG DEPT

RESUBMITTAL
11/25/20
BID SET 02/11/21
02/10/2026 C7 311 of 321

S2-3S1-3
S1-4 S2-4 S3-4 S4-4 S5-4 S6-4
S1-1
S2-1S3-1
S4-1
S5-1
S6-1
S1-2
S2-2
S3-2
S4-2
S5-2
S6-2
S7-2
S7-1

INVERTER MPPT STRING MODULE

CONFIGURATION
INV-1
42kW
1 11
2 3
4 5
6 7
8-24 NOT USED
1 2
3 4
5 6
7 8-24
11 11
11 11
11 11

INVERTER MPPT STRING MODULE

CONFIGURATION
INV-2
42kW
1 11
2 3
4 5
6 7
1 2
3 4
5 6
7 11
11 11
11 11
11 INVERTER MPPT STRING MODULE

CONFIGURATION
INV-3
42kW
1 7
2 3-24 NOT USED
1 2
3-24
7 INVERTER MPPT STRING MODULE

CONFIGURATION
INV-4
42kW
1 9
2 3
4 5
6 7-24 NOT USED
1 2
3 4
5 6
7-24
9 9
9 9
9 8-24 NOT USED8-24
ACC-1
INV-1
INV-2
INV-3
INV-4
2 G
E
J
F
H
3 C
A
641
B
5 D
7 8 9 10 AN
TON

N A T H A NSON
Exp. 03/31/21

LATRICECLE
REE

REGISTERED PROFESSIONAL ENGIN

STATE OF CALIFORNIA
No. E 21090
9150 CHESAPEAKE DR, STE 220
SAN DIEGO, CA 92123
www.ELENconsulting.com
Description: Date:

Project Number:

Drawn By:

Checked By:

Sheet Title:

Approved By:

PROJECT:
6353 DEL CERRO BLVD., SAN DIEGO, CA 92120
619.698.9177 | www.jeffkatzarchitecture.com
005-104

FOR CONSTRUCTION

SOLAR LAYOUT
200102
PV1.0
Checker
AN
MG

ADMINISTRATION

BUILDING

CITY OF VISTA PUBLIC

WORKS DEPARTMENT
1165 E TAYLOR ST.

VISTA, CA 92084
FOR

CONSTRUCTION
05/18/21

BLDG DEPT

SUBMITTAL
09/02/20

BLDG DEPT

RESUBMITTAL
11/25/20
BID SET 02/11/21
02/10/2026 C7 312 of 321

FEEDER RACEWAY AND CONDUCTORS
NOTE
VOLTS

FED FROM

MOUNTING
ROOM

CBCIRCUIT DESCRIPTION

LOAD KVA
#

CKT BREAKER

TRIP/POLES A

NEUTRAL

BUS AMPS
AIC

MAIN BKR
LUGS

TOTAL CONNECTED KVA BY PHASE

FEEDER RACEWAY AND CONDUCTORS
NOTE
VOLTS

FED FROM

MOUNTING
ROOM

CBCIRCUIT DESCRIPTION

LOAD KVA
#

CKT BREAKER

TRIP/POLES A

NEUTRAL

BUS AMPS
AIC

MAIN BKR
LUGS

TOTAL CONNECTED KVA BY PHASE
208Y/120V 3P 4W

SURFACE
ACC-2

MSB STANDARD
150
22,000
150
100%
1-1/2"C,3#1,#1N,#8G1.87100/3 1.87 1.87
1-1/2"C,3#1/0,#1/0N,#6G7.2100/3 7.2 7.2
0-/3 0 0
0-/3 0 0

9.079.079.07

27.2 34 34

94.4 A
INV-3
INV-4
SPACE
SPACE
208Y/120V 3P 4W

SURFACE
ACC-1
DB1 STANDARD
250
22,000
250
100%
1-1/2"C,3#1/0,#1/0N,#6G10.3125/3 10.3 10.3
1-1/2"C,3#1/0,#1/0N,#6G10.3125/3 10.3 10.3
0-/3 0 0
0-/3 0 0

20.520.520.5

61.6 77 77
214 A
INV-1
INV-2
SPACE
SPACE
1 2
3 4
CONN
KVA
CALC
KVA
CALC
KVA
CONTINUOUS (125%)TOTAL LOAD
BALANCED 3-PHASE LOAD
1 2
3 4
CONN
KVA
CALC
KVA
CALC
KVA
CONTINUOUS (125%)TOTAL LOAD
BALANCED 3-PHASE LOAD

FAULT CURRENT SCHEDULE

DEVICE FAULT AIC
RATING
L-N
VOLTS

UTILITY

FAULT X R

FED FROM

DEVICE FAULT X R
FEEDER
SIZE X / 1000' R / 1000' LENGTH X R
DB1 42,000 42,000 120V 42,000 0.002802 0.0005603 (2)#350kcmil0.02 0.019 0 0 ACC-1 18,661 22,000 120V 18,661 0.005268 0.003688 DB1 42,000 0.002802 0.0005603 #250kcmil 0.041 0.052 60' 0.0025 0.0031 INV-1 14,450 22,000 120V 14,450 0.006015 0.005726 ACC-1 18,661 0.005268 0.003688 #1/0 0.044 0.12 17' 0.0007 0.002 INV-2 12,645 22,000 120V 12,645 0.006463 0.006949 ACC-1 18,661 0.005268 0.003688 #1/0 0.044 0.12 27' 0.0012 0.0033 MSB 42,000 42,000 120V 42,000 0.002802 0.0005603 (3)#600kcmil0.013 0.0077 0 0 ACC-2 13,185 22,000 120V 13,185 0.005307 0.007393 MSB 42,000 0.002802 0.0005603 #1/0 0.044 0.12 57' 0.0025 0.0068 INV-3 2,766 22,000 120V 2,766 0.01547 0.04053 ACC-2 13,185 0.005307 0.007393 #1 0.046 0.15 221' 0.0102 0.0331 INV-4 2,207 22,000 120V 2,207 0.02099 0.05015 ACC-2 13,185 0.005307 0.007393 #1/0 0.044 0.12 356' 0.0157 0.0428

FEEDER SCHEDULE
FEEDER
AMPS

CONDUIT AND FEEDER FEEDING THESE DEVICES
100 1-1/2"C,3#1,#1N,#8G INV-3
125 1-1/2"C,3#1/0,#1/0N,#6G INV-1, INV-2, INV-4
150 1-1/2"C,3#1/0,#1/0N,#6G ACC-2
250 2-1/2"C,3#250kcmil,#250kcmil N,#4G ACC-1
SIZING METHOD: COPPER AND ALUMINUM, 60°C #12 THROUGH #1, 75°C 1/0 AND ABOVE

VOLTAGE DROP SCHEDULE

DEVICE FEEDER

VOLTAGE DROP WIRE SIZE
DB1 0%(2)#350kcmil
ACC-1 0.7%#250kcmil
INV-1 0.89%#1/0
INV-2 1.01%#1/0
MSB 0%(3)#600kcmil
ACC-2 0.33%#1/0
INV-3 0.81%#1
INV-4 2.93%#1/0
M M
PANEL "ACC-1"

SINGLE LINE DIAGRAM
SCALE: NONE
INV-1INV-1
G
G N
INV-1INV-2
G
G N
G
N
1 AC AND DC DISCONNECTS ARE INTEGRAL TO
INVERTER.
2 2 2
TYPICAL INVERTER CONNECTION. SEE PANEL

SCHEDULES ON THIS SHEET FOR CONDUIT
AND CONDUCTOR SIZES. SEE SHEET PV2.1

FOR TYPICAL INVERTER CONNECTION DETAIL
AND SHEET PV3.0 FOR CUT SHEET
INFORMATION.
3 3 3

SEE PANEL SCHEDULE ON THIS SHEET FOR
PANEL AND MAIN BREAKER CHARACTERISTICS.
1 250A, 208Y/120V, 3PH, 4W
125A
3P
125A
3P
UTILITY DISCONNECT "UDS1"
600V, 250A WITH VISIBLE BLADES
250A
208Y/120V
TO MSB
TO MSB
PANEL "ACC-2"
G
N
1 INV-1INV-3
G
G N
2 3
150A, 208Y/120V, 3PH, 4W
100A
3P
TO DB1
INV-1INV-3
G
G N
2 3
100A
3P
BUILDING B-1 BUILDING B-2 CAR PORT-1 CAR PORT-2
UTILITY DISCONNECT "UDS2"
600V, 150A WITH VISIBLE BLADES
150A
208Y/120V
TO DB1
AN
TON

N A T H A NSON
Exp. 03/31/21

LATRICECLE
REE

REGISTERED PROFESSIONAL ENGIN

STATE OF CALIFORNIA
No. E 21090
9150 CHESAPEAKE DR, STE 220
SAN DIEGO, CA 92123
www.ELENconsulting.com
Description: Date:

Project Number:

Drawn By:

Checked By:

Sheet Title:

Approved By:

PROJECT:
6353 DEL CERRO BLVD., SAN DIEGO, CA 92120
619.698.9177 | www.jeffkatzarchitecture.com
005-104

FOR CONSTRUCTION

PV SINGLE LINE

DIAGRAM
200102
PV2.0
AN
AN
MG

ADMINISTRATION

BUILDING

CITY OF VISTA PUBLIC

WORKS DEPARTMENT
1165 E TAYLOR ST.

VISTA, CA 92084
FOR

CONSTRUCTION
05/18/21

BLDG DEPT

SUBMITTAL
09/02/20

BLDG DEPT

RESUBMITTAL
11/25/20
BID SET 02/11/21
02/10/2026 C7 313 of 321

INVERTER
GROUND
#6CU.
#10CU.

PV STRINGS#6CU.

BOND TO

RACKING

DC SCHEMATIC DESIGN - GROUNDING SCHEMATIC
SCALE: NONE

UL LISTED GROUNDING
HARDWARE. PROVIDE
(2) FOR EVERY
MODULE. (TYPICAL)

DC SCHEMATIC DIAGRAM - STRING CONNECTION DETAIL
SCALE: NONE

STRUCTURE
G
6 +-
7 +-
8 +-
3 +-
4 +-
5 +-
2 +-
1 +-

GROUND LUGS ATTACHED
TO MOUNTING STRUCTURE.

ROUTE CONDUCTORS WITH STRUCTURE. CONCEAL

CONDUCTORS BEHIND STRUCTURE WHERE
POSSIBLE. PROVIDE (2) #10 CU. PER STRING. CABLE
TO BE PV WIRE FOR UNGROUNDED PV SYSTEMS.

PROVIDE (1) #10 BARE CU. E.G. AND BOND TO EACH
STRING. (TYPICAL FOR EACH STRING).

INVERTER

SEE SHEET
PV3.0 FOR

INVERTER CUT
SHEETS

TO AC COMBINER BOARDS

GROUND AT MODULE WITH

LUGS AT GROUNDING
LOCATION ONLY. PER

MODULE INSTALLATION
MANUAL. PROVIDE

CONTINUOUS MODULE

BOND WIRE
ALL DC WIRING SHALL BE 1000VDC PV
WIRE TYPE INSULATION.

RED STRIPE ON POSITIVE WIRES AND
YELLOW STRIPE ON NEGATIVE.

NOTE:

ALL AC CONDUCTORS ARE THWN-2.

ALL DC CONDUCTORS ARE PV WIRE.

PROVIDE POWER

TERMINAL LUGS IN

A WP J-BOX WHEN

CONDUCTORS

EXCEED INVERTER
LUG SIZES.

UL LISTED GROUNDING
HARDWARE. PROVIDE
(2) FOR EVERY
MODULE. (TYPICAL)

TO ADDITIONAL
STRINGS. SEE
SHEET PV1.0.

G+-COMBINER BOX
(REQUIRED FOR 2

STRING INPUTS PER
MPPT)
N
9 +-
10 +-
11 +-
AN
TON

N A T H A NSON
Exp. 03/31/21

LATRICECLE
REE

REGISTERED PROFESSIONAL ENGIN

STATE OF CALIFORNIA
No. E 21090
9150 CHESAPEAKE DR, STE 220
SAN DIEGO, CA 92123
www.ELENconsulting.com
Description: Date:

Project Number:

Drawn By:

Checked By:

Sheet Title:

Approved By:

PROJECT:
6353 DEL CERRO BLVD., SAN DIEGO, CA 92120
619.698.9177 | www.jeffkatzarchitecture.com
005-104

FOR CONSTRUCTION

DC SCHEMATIC

DIAGRAM
200102
PV2.1
AN
AN
MG

ADMINISTRATION

BUILDING

CITY OF VISTA PUBLIC

WORKS DEPARTMENT
1165 E TAYLOR ST.

VISTA, CA 92084
FOR

CONSTRUCTION
05/18/21

BLDG DEPT

SUBMITTAL
09/02/20

BLDG DEPT

RESUBMITTAL
11/25/20
BID SET 02/11/21
02/10/2026 C7 314 of 321

AN
TON

N A T H A NSON
Exp. 03/31/21

LATRICECLE
REE

REGISTERED PROFESSIONAL ENGIN

STATE OF CALIFORNIA
No. E 21090
9150 CHESAPEAKE DR, STE 220
SAN DIEGO, CA 92123
www.ELENconsulting.com
Description: Date:

Project Number:

Drawn By:

Checked By:

Sheet Title:

Approved By:

PROJECT:
6353 DEL CERRO BLVD., SAN DIEGO, CA 92120
619.698.9177 | www.jeffkatzarchitecture.com
005-104

FOR CONSTRUCTION
PV

SPECIFICATIONS
200102
PV3.0
AN
AN
MG

ADMINISTRATION

BUILDING

CITY OF VISTA PUBLIC

WORKS DEPARTMENT
1165 E TAYLOR ST.

VISTA, CA 92084
FOR

CONSTRUCTION
05/18/21

BLDG DEPT

SUBMITTAL
09/02/20

BLDG DEPT

RESUBMITTAL
11/25/20
BID SET 02/11/21
02/10/2026 C7 315 of 321

AN
TON

N A T H A NSON
Exp. 03/31/21

LATRICECLE
REE

REGISTERED PROFESSIONAL ENGIN

STATE OF CALIFORNIA
No. E 21090
9150 CHESAPEAKE DR, STE 220
SAN DIEGO, CA 92123
www.ELENconsulting.com
Description: Date:

Project Number:

Drawn By:

Checked By:

Sheet Title:

Approved By:

PROJECT:
6353 DEL CERRO BLVD., SAN DIEGO, CA 92120
619.698.9177 | www.jeffkatzarchitecture.com
005-104

FOR CONSTRUCTION
PV

CALCULATIONS
200102
PV4.0
AN
AN
MG

ADMINISTRATION

BUILDING

CITY OF VISTA PUBLIC

WORKS DEPARTMENT
1165 E TAYLOR ST.

VISTA, CA 92084
FOR

CONSTRUCTION
05/18/21

BLDG DEPT

SUBMITTAL
09/02/20

BLDG DEPT

RESUBMITTAL
11/25/20
BID SET 02/11/21
02/10/2026 C7 316 of 321

EXHIBIT 4
Project Site
02/10/2026 C7 317 of 321

ProProposed

BUILDING C IMPROVEMENTS

APPENDIX C
02/10/2026 C7 318 of 321

EXHIBIT 5
Agreement to Comply With California Labor Law Requirements 02/10/2026 C7 319 of 321

00052253 1

AGREEMENT TO COMPLY WITH CALIFORNIA LABOR LAW REQUIREMENTS [Labor Code §§ 1720, 1771.1, 1773.8, 1775, 1776, 1777.5, 1813, 1860, 1861, 3700] The undersigned Contractor certifies that it is aware of and hereby agrees to fully comply with the following provisions of California law:

1.No contractor or subcontractor may be listed on a bid proposal for a public works project unless registered with the Department of Industrial Relations pursuant to Labor Code section 1725.5 [with limited exceptions from this requirement for bid purposes only under Labor Code section 1771.1(a)]. No contractor or subcontractor of any tier may be awarded a contract for public work on a public works project without proof of registration with the Department of Industrial Relations pursuant to Labor Code section 1725.5.

This project is subject to compliance monitoring and enforcement by the Department of Industrial Relations.

2.Contractor acknowledges that this contract is subject to the provisions of Division 2, Part 7, Chapter 1 (commencing with Section 1720) of the California Labor Code relating to public works and the awarding public agency (“Agency”) and agrees to be bound by all the provisions thereof as though set forth in full herein.

3.Contractor agrees to comply with the provisions of California Labor Code Section 1773.8 which requires the payment of travel and subsistence payments to each worker needed to execute the work to the extent required by law.

4.Contractor agrees to comply with the provisions of California Labor Code Sections 1774 and 1775 concerning the payment of prevailing rates of wages to workers and the penalties for failure to pay prevailing wages. The Contractor shall, as a penalty to the Agency, forfeit not more than fifty dollars ($50) for each calendar day, or portion thereof, for each worker paid less than the prevailing rates as determined by the Director of Industrial Relations for the work or craft in which the worker is employed for any public work done under the contract by Contractor or by any subcontractor.

5.Contractor agrees to comply with the provisions of California Labor Code Section 1776 which require Contractor and each subcontractor to (1) keep accurate payroll records, (2) certify and make such payroll records available for inspection as provided by Section 1776, and (3) inform the Agency of the location of the records. The Contractor is responsible for compliance with Section 1776 by itself and all of its subcontractors.

6.Contractor agrees to comply with the provisions of California Labor Code Section 1777.5 concerning the employment of apprentices on public works projects, and further agrees that Contractor is responsible for compliance with Section 1777.5 by itself and all of its subcontractors.

7.Contractor agrees to comply with the provisions of California Labor Code Section 1813 concerning penalties for workers who work excess hours. The Contractor shall, as a penalty to the Agency, forfeit twenty-five dollars ($25) for each worker employed in the execution of the contract by the Contractor or by any subcontractor for each calendar day during which such worker is required or permitted to work more than 8 hours in any one calendar day and 40 hours in any one calendar week in violation of the provisions of Division 2, Part 7, Chapter 1, Article 3 of the California Labor Code.

8.Registrations under Section 1725.5 expire annually at the end of June, and Contractor is responsible for verifying the renewal status of each subcontractor, of any tier, working on this Contract, and providing City with an updated list of all subcontractors and their registration status. Subcontractors who do not timely renew their registration must be removed from the job site until they are registered. The removal of a subcontractor for failure to be registered shall not be cause for any extension of time or additional compensation of any nature under the Contract.

9.Contractor shall provide to City, as a condition precedent to the payment of Contractor’s final retention, a complete list of all subcontractors who have worked on the Project, including their registration numbers. This list must be provided at least 30 days prior to the payment of the final retention and shall be submitted under penalty of perjury.
02/10/2026 C7 320 of 321

00052253 1

10.To the fullest extent permitted by law and without limitation by the other provisions of this Contract relating to indemnification and insurance, Contractor shall also indemnify, defend and hold harmless City, and its directors, officers, employees and agents from and against all liability, excluding penalties assessed against City under Labor Code Section 1773.3, but including, without limitation, associated investigation and administrative expenses, defense costs, reasonable attorneys' fees, expert witnes s fees, court costs, and costs of alternative dispute resolution, resulting from Contractor’s failure to comply with the provisions of this section and of Article 2, Chapter 1, Part 7, Division 2 of the California Labor Code with respect to Contractor, all subcontractors of any tier, and their respective employees working under this Contract.

11.California Labor Code Sections 1860 and 3700 provide that every contractor will be required to secure the payment of compensation to its employees. In accordance with the provisions of California Labor Code Section 1861, Contractor hereby certifies as follows:
“I am aware of the provisions of Section 3700 of the Labor Code which require every employer to be insured against liability for worker’s compensation or to undertake self-insurance in accordance with the provisions of that code, and I will comply with such provisions before commencing the performance of the work of this contract.”