2024-09-10; City Council; 08; Monroe Street Pool Renovation and Replacement Project Plans, Specifications and Contract Documents, Appropriation of Construction Funding, and Authorization to Advertise

Carlsbad City Council
September 10, 2024

Document
2024-09-10; City Council; 08; Monroe Street Pool Renovation and Replacement Project Plans, Specifications and Contract Documents, Appropriation of Construction Funding, and Authorization to Advertise
Meeting
September 10, 2024
Body
Carlsbad City Council
Pages
254
Original file
4.9 MB
Text extracted from the city's file for reading and search. Open the original on records.carlsbadca.gov. That file is the official record.

CA Review GH
Meeting Date: Sept. 10, 2024
To: Mayor and City Council
From: Scott Chadwick, City Manager
Staff Contact: Steven Stewart, Municipal Projects Manager [email protected], 442-339-2938
Kyle Lancaster, Parks & Recreation Director
[email protected], 442-339-2941
Subject: Monroe Street Pool Renovation and Replacement Project Plans, Specifications and Contract Documents, Appropriation of Construction Funding, and Authorization to Advertise the Project for Construction Bids District: 1
Recommended Actions
Adopt a resolution approving the Monroe Street Pool Renovation and Replacement Project’s plans, specifications and contract documents, appropriating $18,158,361 in construction funding, and authorizing the City Clerk to advertise the project for construction bids.

Executive Summary
Monroe Street Pool, located next to Carlsbad High School in northern Carlsbad, was built in 1982 and now requires significant repairs and upgrades to remain operational and compliant with health and safety and building codes. City staff developed three options, ranging from the bare minimum to keep the pool operational and compliant to an option that would increase the pool complex’s capacity, use and lifespan. Based on community input, the City Council voted in 2021 to pursue the latter option.

Because certain projects over $1 million require voter approval, the City Council put a measure on the ballot for the Monroe Street Pool Renovation and Replacement Project in November 2022, which was approved. Since that time, staff have completed all the work needed to get the project ready to be put out for construction bids, including obtaining a detailed cost estimate.

To date, the City Council has approved $4.8 million for the project. An additional $18.16 million is needed for construction, which is expected to take about a year and a half once the work gets underway.

Carlsbad Municipal Code Section 3.28.080(E) requires City Council approval of plans, specifications and contract documents of projects when the expected value of work is more than $200,000.

Sept. 10, 2024
Item #8 Page 1 of 15

Explanation & Analysis
Starting in 2015, the City Council has taken several actions to address this need for repairs and upgrades for the pool.

Past City Council actions
June 30, 2015 Approved adding the Monroe Street Pool Renovation/Replacement Project, to the fiscal year 2015-16 Capital Improvement Program as Project No. 4724.

April 9, 2019 Authorized a $674,577 agreement with the design firm LPA Inc. for architectural and engineering design services for the project. (Resolution No. 2019-049) Jan. 26, 2021 Approved a motion selecting design concept three for the project and directing staff to pursue placing an expenditure measure on the June 7, 2022, primary election ballot.

Feb. 22, 2022 Deferred the timing of the ballot measure. (Resolution No. 2022-049) April 26, 2022 Approved a motion directing staff to prioritize maintenance and repairs to keep the pool facility functioning until the project was ready to build.

June 21, 2022 Placed the measure on the Nov. 8, 2022, general election ballot. (Resolution No. 2022-156).

Feb. 14, 2023 Amended the agreement with LPA Inc. to develop the final design and construction plans and specifications for the project. (Resolution No. 2023-055) Public input
Monroe Street Pool users have reported concerns to the city in recent years about the condition of the facility and the need for more pool lanes overall in Carlsbad. Neighbors of the Monroe Street Pool have also contacted the city over the years with concerns related to abating noise.

City staff used this background along with other input gathered from pool users and neighbors, to develop three options for the project. Option one is the bare minimum to keep the pool operational; option two was to modernize the pool but keep it the same size, while option three was to increase the pool’s size and configuration to provide 50% more lanes and include added solar energy opportunities, a new mechanical room and family restrooms, a reconfigured lobby, first aid and administrative offices, meeting space, a larger parking lot and several other features.

Between Aug. 31 and Sept. 30, 2020, staff sought feedback on the options, including the features, timeframe to complete, costs and expected lifespan of the improvements.

In all, 944 community members provided a total of 23,964 responses to an online survey seeking feedback about the options. The city also gathered 591 open-ended comments from the public during this time. Nearly half of the respondents – 47% – were from District 1, followed by 25% from District 2, 15% from District 3 and 14% from District 4. Opinions did not differ significantly among respondents from different districts.

Based on this input, the most important features of a renovated or new Monroe Street Pool facility were:
• A larger pool size
• More availability for lap swimming
• More use of solar
Sept. 10, 2024
Item #8 Page 2 of 15

When asked about the tradeoffs among the three options, most respondents favored making the pool complex as good as it can be now, so the city does not need to come back later to make more upgrades.

In January 2021, staff presented the options and community feedback to the City Council. The City Council voted to proceed with the community’s preferred concept, option three, which had the highest cost but maximized the capacity, use and lifespan of the pool complex.

Project description
The Monroe Street Pool Renovation and Replacement Project includes the following features:
• Larger and reconfigured pool with 50% more lanes
• New 8-foot wall with metal gates along Monroe Street to reduce sound for the surrounding neighborhood
• Larger pool deck with lockers and outdoor showers
• Renovated locker rooms
• More shade
• More bleachers
• Larger parking lot
• Addition of an outdoor entrance for competitions (instead of going through the lobby to get to the pool)
• Family restrooms
• Reconfigured lobby, first aid and administration offices and a room that can be used for meetings and small gatherings like birthday parties
• All new pool tile, plaster, piping, pool deck, drainage, pumps and filters • New building for pool equipment with separate entrance for service vehicles so they don’t take up space in the parking lot
• Replacement of existing solar water heating system and installation of rooftop solar panels to generate electricity

Sept. 10, 2024
Item #8 Page 3 of 15
Monroe Street Pool
33-meter pool,
15 lanes (7' 3")
More parking spaces
Family restrooms
, Sports lighting
Shade
Exterior entrance/exit
Locker rooms, reception,
office space

Voter approval
In Carlsbad, spending over $1 million in general city funds for certain types of construction projects requires voter approval. The City Council put the following measure on the Nov. 8, 2022, ballot:

Measure J
Do the voters of the City of Carlsbad approve spending existing city funds from various sources, including the General Fund, in an amount to exceed $1 million for the Monroe Street Pool Renovation/Replacement Project located at 3401 Monroe Street for an estimated cost range of $22 million up to $24 million, adjusted annually by the percentage increase in the regional construction cost index? The measure was approved. Following voter approval, the City Council directed staff to proceed with a final design, and the construction plans and specifications, and then develop an updated cost estimate. Staff have completed this work.

Regional Construction Cost Index
Measure J authorized the city to spend up to $24 million, adjusted annually based on the regional construction cost index. This index tracks inflation specifically for the construction industry. The regional construction cost index for 2023 was 9.4%.

Approved spending
2022 Voter approved use of city funds $24.00 million
2023 Regional construction cost index 9.4%
2024 Funds authorized in today’s dollars $25.02 million Fiscal Analysis
The total cost of the Monroe Street Pool Renovation and Replacement Project is estimated at $22,969,126, which is within the amount approved by voters.

Available funding sources
Different types of city funds come with different restrictions on how they can be spent. The following funds could be used to pay for the construction of the Monroe Street Pool project:

Northwest Park Development (Park-In-Li
eu) Fund
When residential developers build projects of a certain size in Carlsbad, they pay fees to help fund the infrastructure and amenities new residents will need. The fees for parks and recreation amenities are called park in lieu fees. These funds are collected by region of the city and may only be used for projects in that region.

Public Facilities Fund
Money in this fund is collected by developers to be used for civic facilities, park development, streets, traffic signals and other similar uses.

Infrastructure Rep air and Replacement Fund
The city sets aside a percentage of its annual budget each year to fund future infrastructure needs. This money can pay for maintaining or replacing city facilities and other infrastructure.

Sept. 10, 2024
Item #8 Page 4 of 15

General Capital Construction Fund
The city also sets aside money each year to save up for major construction projects that cannot be paid for through other more restricted funds. For example, money the city collects through the gas tax is restricted to paying only for road projects. Therefore, the city would first use gas tax funds to pay for a road project. The city would only consider other funding sources if there weren’t enough money in the gas tax fund.

General Fund
The city’s General Fund is used to carry out the essential day-to-day services of local government, like police and fire protection, street maintenance and library operations.

The main sources of money for this fund are the city’s portion of sales tax and property tax, as well as the tax visitors pay when they stay in local hotels and short-term vacation rentals. The City Council has the greatest discretion over how money in the General Fund is spent.

Funding to date
The City Council has appropriated the following funding for the Monroe Street Pool Renovation and Replacement Project

Funding appropriated to date
General Capital Construction Fund $236
Infrastructure Replacement Fund $1,748,766
Park Development (Park-In-Lieu) Fund - Northwest $3,061,765 TOTAL $4,810,765*
Design and Permitting Services (completed) -$2,348,791
REMAINING $2,461,974
* Actual amount (individual fund dollar amounts have been rounded)

Construction cost estimate
Completing the project’s final design, plans and specifications has allowed staff and consultants to develop a more detailed construction cost estimate:

Monroe Street Pool Renovation and Replacement Project
Construction contract (estimated)* $16,668,000
Construction contingency (10%) $1,666,800
Construction management and inspection costs, furnishings, neighborhood outreach during construction (estimated) $2,285,535 CONSTRUCTION COST ESTIMATE $20,620,335
FUNDS ALREADY APPROPRIATED -$2,461,974
ADDITIONAL APPROPRIATION NEEDED $18,158,361
* Actual construction costs depend on the bids received.

Sept. 10, 2024
Item #8 Page 5 of 15

Funding considerations
When more than one funding source is available, staff consider the following:
• Which fund is most appropriate based on the nature of the project • What other projects may be drawing from these funds in the next five years • The fund’s balance today and projected balance in five years Approximately one-third of the project’s scope of work is associated with core maintenance, repair and refurbishment needs of the 42-year-old facility. The funding for that one-third of the project, which is estimated to cost over $6 million, would be needed regardless of whether other elements of the project were included. The other approximately two-thirds of the project’s scope of work is associated with expanding, enhancing and modernizing the facility.

After considering other planned projects that may use the available funding sources over the next five years, staff recommend one-third of the construction funding for the Monroe Street Pool Renovation and Replacement Project come from the Infrastructure Repair and Replacement Fund and two-thirds of the construction funding come from the General Capital Construction Fund.

Balance
today
5-year
projection
Recommended
appropriation
Public Facilities Fees Fund $28 M $35 M none
Infrastructure Replacement Fund $63 M $34 M $6,052,787
General Capital Construction Fund $31 M $37 M $12,105,574 General Fund Reserve $131 M $141 M none

Operating Costs
The city’s Finance Department considers not just the construction cost of a new or expanded facility, but the cost to operate and maintain the facility in the future. The operating expenses for the renovated and expanded facility are projected to increase by approximately $370,000 a year due to the facility’s increase in size, capacity, programming and maintenance costs.

Staff expect this increase in annual operating expenses would be fully offset by an increase in revenues resulting from greater use of the facility by community members, and the implementation of fees consistent with that of the Alga Norte Aquatic Center. A recreation planning and operations consulting firm has independently reviewed staff’s calculations and validated the expectation of a net cost neutrality over current budget.

Sept. 10, 2024
Item #8 Page 6 of 15

Next Steps
With the City Council’s approval, the City Clerk will advertise the construction project for bids.

Staff anticipate returning to the City Council in early 2025 to request the award of a contract for the construction and a contract for the construction management and inspection services.

Construction is expected to take about a year and a half, with completion expected in summer 2026.

Environmental Eval uation
On July 19, 1977, the City Council certified the environmental impact report (EIR-380) for the Monroe Street Pool, at the time identified as the “community swimming pool.” The project is within the scope of the prior environmental document and no further environmental documentation is required per California Environmental Quality Act Guidelines Section 15162.

The conditional use permit (CUP-158) and the certified environmental impact report (EIR-380) for the Community Swim Complex allowed for larger pool(s), building(s) and parking lots than what was originally constructed. All applicable mitigation measures contained in the prior environmental document have either been satisfied previously and/or were made conditions of approval of the project’s approved conditional use permit. There have not been substantial changes to the circumstances under which the project is undertaken and there have been no new significant environmental effects that would modify or change any mitigation measures.

The pool operates in conjunction with the existing school facility, and the proposed changes do not result in new significant impacts or a substantial increase in the severity of previously identified impacts because the site and neighborhood context have not changed. Projects constructed by the school district since the pool was constructed have not impacted pool operations. The changes to the pool will have no impact to the adjacent school facilities. The mitigation measures to reduce impacts remain in place and are adequate to maintain the same level of significance studied in the previous environmental impact report, therefore none of the situations in Section 15162(a) exist and no additional environmental review is necessary. The certified environmental impact report and mitigation measures are on file for review at the Planning Division.

The City Planner determined on Feb. 7, 2023, that design concept three was consistent with the approved conditional use permit for the Community Swim Complex (the former name of the Monroe Street Pool facility), as shown in Exhibit 3.

Exhibits

1. City Council resolution

2. Plans, specifications and contract documents (on file in the Office of the City Clerk)

3. City Planner’s consistency determination with conditional use permit, dated Feb. 7, 2023

Sept. 10, 2024
Item #8 Page 7 of 15
Exhibit 1
Sept. 10, 2024
Item #8 Page 8 of 15
RESOLUTION NO. 2024-214

A RESOLUTION OF THE CITY COUNCIL OF THE CITY OF CARLSBAD,

CALIFORNIA, APPROVING THE MONROE STREET POOL RENOVATION AND

REPLACEMENT PROJECT'S PLANS, SPECIFICATIONS AND CONTRACT DOCUMENTS, APPROPRIATING $18,158,361 IN CONSTRUCTION FUNDING,

AND AUTHORIZING THE CITY CLERK TO ADVERTISE THE PROJECT FOR

CONSTRUCTION BIDS
WHEREAS, the City Council of the City of Carlsbad, California has determined it necessary, desirable and in the public interest to construct the Monroe Street Pool Renovation and Replacement Project as designed; and
WHEREAS, on Feb. 14, 2023, the City Council adopted Resolution No. 2023-055, authorizing the execution of Amendment No. 3 to the agreement with LPA Inc. to prepare design and construction plans and specifications for the Monroe Street Pool Renovation and Replacement Project, Capital Improvement Program Project No. 4724, and
WHEREAS, the City Council of the City of Carlsbad, California has determined that the plans, specifications and contract documents for the Monroe Street Pool Renovation and Replacement Project have been completed to the satisfaction of staff; and WHEREAS, the plans, specifications and contract documents for the project are on file at the City Clerk's Office and are incorporated by reference; and WHEREAS, an additional appropriation in the amount of $18,158,361, to be funded with $6,052,787 from the Infrastructure Repair and Replacement Fund, and $12,105,174 from the General Capital Construction Fund, is needed to fund the construction of the project; and WHEREAS, on July 19, 1977, the City Council certified the Environmental Impact Report (EIR- 380) for the Monroe Street Pool, at the time identified as the "community swimming pool"; and WHEREAS, the Monroe Street Pool Renovation and Replacement Project, Concept 3, is within the scope of the prior environmental document and no further environmental documentation is required in accordance with California Environmental Quality Act Guidelines Section 15162; and WHEREAS, the City Planner determined on Feb. 7, 2023, that design concept three was consistent with the approved conditional use permit for the Community Swim Complex, the former name of the Monroe Street Pool facility .

Sept. 10, 2024
Item #8 Page 9 of 15
NOW, THEREFORE, BE IT RESOLVED by the City Council of the City of Carlsbad, California, as follows:

1. That the above recitations are true and correct.

2. That the plans, specifications and contract documents for the Monroe Street Pool Renovation and Replacement Project, Capital Improvement Program Project No. 4724, are approved and on file at the City Clerk's Office.

3. That the City Manager or designee is authorized to appropriate $18,158,361 to Project No. 4724 to be funded as follows: $6,052,787 from the Infrastructure Repair and Replacement Fund and $12,105,574 from the General Capital Construction Fund.

4. That the City Clerk is hereby authorized and directed to publish, in accordance with state law and Carlsbad Municipal Code Section 3.28.080((), a notice to contractors inviting bids for construction of the Monroe Street Pool Renovation and Replacement Project, Project No. 4724, in accordance with the plans, specifications and contract documents referred to herein.

PASSED, APPROVED AND ADOPTED at a Regular Meeting of the City Council of the City of Carlsbad on the 10th day of September, 2024, by the following vote, to wit:

AYES:

NAYS:

ABSTAIN:

ABSENT:

BLACKBURN, BHAT-PATEL, ACOSTA, BURKHOLDER, LUNA.

NONE.

NONE.

NONE.
\
KEITH B CKBURN, Mayor
(JJl
SHERRY FREISINGER, City Clerk
(SEAL)
Exhibit 2
Plans
, specifications and contract documents
(on file in the Office of the City Clerk)
Sept. 10, 2024
Item #8 Page 10 of 15
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

PROJECT NUMBER

NOT FOR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIORS

LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
1902710
3RD PLANCHECK SUBMITTAL
08/09/2024
08/09/2024
Exhibit 2

CAB CABINET

CB CATCH BASIN

CEM CEMENT

CER CERAMIC

CI CAST IRON

CIP CAST IN PLACE

CIV ENG CIVIL ENGINEER

CG CORNER GUARD

CJ CONTROL JOINT

CLG CEILING

CLKG CAULKING

CLO CLOSET

CLR CLEAR

CNTR COUNTER

CO CASED OPENING

COL COLUMN

CONC CONCRETE

CONN CONNECTION

CONSTR CONSTRUCTION

CONT CONTINUOUS

CORR CORRIDOR

CT CERAMIC TILE

CTR CENTER

CTSK COUNTERSUNK

DA DISABLED ACCESS

DBL DOUBLE

DEPT DEPARTMENT

DESC DESCRIPTION

DF DRINKING FOUNTAIN

DET DETAIL

DIA DIAMETER

DIM DIMENSION

DISP DISPENSER

DN DOWN

DO DOOR OPENING

DR DOOR

DWR DRAWER

DS DOWNSPOUT

DSP DRY STANDPIPE

DWG DRAWING
E EAST

EA EACH

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRICAL

ELEV ELEVATOR

EMER EMERGENCY

ENCL ENCLOSURE

EP ELECTRICAL PANELBOARD

EQ EQUAL

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXIST EXISTING

EXPO EXPOSED

EXP EXPANSION

EXT EXTERIOR

FA FIRE ALARM

FB FLAT BAR

FD FLOOR DRAIN

FDN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER

CABINET

FHC FIRE HOSE CABINET

FIN FINISH

FLR FLOOR

FLASH FLASHING

FLUOR FLUORESCENT

FOC FACE OF CONCRETE

FOF FACE OF FINISH

FOM FACE OF MASONRY

FOS FACE OF STUD

FOV FACE OF VENEER (BRICK OR

PRECAST)

FOW FACE OF WALL

FR FIRE RETARDANT

FPRF FIREPROOF

FS FINISH SURFACE

FT FOOT OR FEET

FTG FOOTING

FURR FURRING

FUT FUTURE

ID INSIDE DIAMETER

INSUL INSULATION

INT INTERIOR

JAN JANITOR

JT JOINT

KIT KITCHEN

LAB LABORATORY

LAM LAMINATE

LAND ARCH LANDSCAPE ARCHITECT

LAV LAVATORY

LKR LOCKER

LT LIGHT

MATL MATERIAL

MAX MAXIMUM

MC MEDICINE CABINET

MECH MECHANICAL

MEMB MEMBRANE

MET METAL

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MIR MIRROR

MISC MISCELLANEOUS

MO MASONRY OPENING

MTD MOUNTED

MUL MULLION

N NORTH

NIC NOT IN CONTRACT
NO/# NUMBER

NOM NOMINAL

NTS NOT TO SCALE

OA OVERALL

OA OUTSIDE AIR

OBS OBSCURE

OC ON CENTER

OD OUTSIDE DIAMETER

OFF OFFICE

OPNG OPENING

OPP OPPOSITE

OSA OUTSIDE AIR

PA PLANTING AREA

PRCST PRECAST

PH PANIC HARDWARE

PL PLATE

P LAM PLASTIC LAMINATE

PLAS PLASTER

PLYWD PLYWOOD

POT PATH OF TRAVEL

PR PAIR

PT PAINT

PTD PAPER TOWEL DISPENSER

PTD/R COMBINATION PAPER

TOWEL DISPENSER &

RECEPTACLE

PTN PARTITION

PTR PAPER TOWEL

RECEPTACLE

QT QUARRY TILE

R RISER

RAD RADIUS

RD ROOF DRAIN

REF REFERENCE

REFR REFRIGERATOR

RGTR REGISTER

REINF REINFORCED

REQD REQUIRED

RESIL RESILIENT

RM ROOM

RO ROUGH OPENING

ROW RIGHT OF WAY

RWD REDWOOD

RWL RAIN WATER LEADER

S SOUTH

SC SOLID CORE

SCD SEAT COVER DISPENSER

SCHED SCHEDULE

SD SOAP DISPENSER

SECT SECTION

SF SQUARE FEET

SH SHELF

SHR SHOWER

SHT SHEET

SIM SIMILAR

SND SANITARY NAPKIN

DISPENSER

SNR SANITARY NAPKIN

RECEPTACLE

SPEC SPECIFICATION(S)

SQ SQUARE

SS STAINLESS STEEL

S SK SERVICE SINK

STA STATION

STD STANDARD

STL STEEL

STOR STORAGE

STR STRUCTURAL

SUSP SUSPENDED

SYM SYMMETRICAL
& AND
∠ ANGLE
@ AT
℄ CENTERLINE
∅ DIAMETER OR ROUND
# POUND OR NUMBER
(E) EXISTING
(P) PAINT
(R) REMOVE
+/- DIM TOLERANCE

AC ASPHALTIC CONCRETE

ACC ACCESSIBLE

ACOUS ACOUSTICAL

ACM ALUM COMPOSITE MATERIAL

ACT ACOUS CLG TILE

AD AREA DRAIN

AED AUTO EXT DEFIBRILLATOR

ADJ ADJUSTABLE

AFF ABOVE FINISH FLOOR

AGGR AGGREGATE

AHJ AUTHORITY HAVING

JURISDICTION

ALUM ALUMINUM

APPROX APPROXIMATE

ARCH ARCHITECTURAL

ASF ASSIGNABLE SF

ASPH ASPHALT

BD BOARD

BITUM BITUMINOUS

BLDG BUILDING

BLK BLOCK

BLK'G BLOCKING

BM BEAM

BOC BACK OF CURB

BOT BOTTOM

BO BOTTOM OF

BOC BACK OF CURB

BOW BOTTOM OF WALL

BS BOTTOM OF SLOPE

GA GAUGE

GALV GALVANIZED

GB GRAB BAR

GC GENERAL CONTRACTOR

GI GALVANIZED IRON

GL GLASS

GND GROUND

GR GRADE

GYP GYPSUM

HB HOSE BIB

HC HOLLOW CORE

HDWD HARDWOOD

HDW HARDWARE

HM HOLLOW METAL

HORIZ HORIZONTAL

HR HOUR

HGT/HT HEIGHT

T TREAD

TB TOWEL BAR

TC TOP OF CURB

TEL TELEPHONE

TER TERRAZZO

T&G TONGUE & GROOVE

THK THICK

TOB TOP OF BEAM

TOC TOP OF CONCRETE

TOW TOP OF WALL

TOP TOP OF PARAPET

TPD TOILET PAPER DISPENSER

TS TOP OF SLOPE

TV TELEVISION

TYP TYPICAL

UNF UNFINISHED

UNO UNLESS NOTED

OTHERWISE

UR URINAL

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE
W WEST

W/ WITH

WC WATER CLOSET

WD WOOD

W/O WITHOUT

WP WATERPROOF

WR WATER RESISTANT

WSCT WAINSCOT

WT WEIGHT

WWF WELDED WIRE FABRIC

COLUMN LINES
0 0

SURFACE DRAINAGE

ARROW INDICATES

DIRECTION OF FLOW
N

PROJECT NORTH

BUILDING SECTION
1 A101
TYP

SECTION ID

SHEET NUMBER
1 A101 TYP

WALL SECTION

SECTION ID

SHEET NUMBER

DETAIL CALLOUTS

DETAIL ID

SHEET NUMBER
1 A101
SIM

DETAIL SECTION

DETAIL ID

SHEET NUMBER
1 A101
SIM

DETAIL REFERENCE

DETAIL ID

SHEET NUMBER
1 A101
SIM

INTERIOR ELEVATIONS

DETAIL ID

SHEET NUMBER
A
C
SIM
D BA101

DOOR DESIGNATION

ROOM DESIGNATION

ROOM NUMBER

ROOM AREA
1REVISION CLOUD &

TAG (OPTIONAL
SA2U
1t

SHADED PORTION POINTS

TO SIDE REFERENCED

DATUM POINT

KEYNOTE

WALL TYPE

WINDOW TYPE
TYP.
?

MATCH LINE
SEE SHEET A101
Name
Elevation

LEVEL LINE, CONTROL POINT
EL: 12'-8" = ELEVATION/SECTION

STAIR DIRECTION
DN
UP

CENTER LINES, FLOOR LINES

HIDDEN CONSTRUCTION FEATURE

BREAK LINE
####
FINISH TAG XX -##
EQUIPMENT TAG 1i

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

SHEET INDEX
G0.10
MD
MONROE ST. POOL REPLACEMENT

SHEET INDEX

SHEET INDEX

SHEET NUMBER SHEET NAME

GENERAL INFORMATION
G0.00 COVER SHEET
G0.10 SHEET INDEX
G0.20 GENERAL PROJECT INFORMATION
G0.40 CALGREEN (CA)
G0.41 CALGREEN (CA)
G0.42 CALGREEN (CA)
G2.10 CODE ANALYSIS
G2.11 EGRESS PLAN
G0.31 TYPICAL ACCESSIBILITY NOTES AND DETAILS
G0.32 TYPICAL ACCESSIBILITY NOTES AND DETAILS
CIVIL
C1 TITLE SHEET
C2 CIVIL NOTES
C3 EXISTING CONDITIONS
C4 DEMOLITION PLAN
C5 GRADING PLAN
C6 GRADING ENLARGEMENT
C7 STORM DRAIN PLAN
C8 UTILITY PLAN
C9 HORIZONTAL CONTROL AND PAVING PLAN
C10 DETAILS
C11 DETAILS
C12 SINGLE SHEET BMP SITE PLAN

LANDSCAPE
L0.01 LANDSCAPE NOTES AND SCHEDULE
L0.02 LANDSCAPE NOTES AND SCHEDULE
L1.01 MATERIALS PLAN
L1.02 LAYOUT PLAN
L3.01 ENLARGEMENT PLAN
L4.01 SECTIONS AND ELEVATIONS
L4.02 SECTIONS AND ELEVATIONS
L4.03 SECTIONS AND ELEVATIONS
L4.04 SECTIONS AND ELEVATIONS
L5.01 CONSTRUCTION DETAILS
L5.02 CONSTRUCTION DETAILS
L5.03 CONSTRUCTION DETAILS
L5.04 CONSTRUCTION DETAILS
L5.05 CONSTRUCTION DETAILS
L5.06 CONSTRUCTION DETAILS
L5.07 CONSTRUCTION DETAILS
L5.08 CONSTRUCTION DETAILS
L5.09 CONSTRUCTION DETAILS
L5.10 CONSTRUCTION DETAILS
L5.11 CONSTRUCTION DETAILS
L5.12 CONSTRUCTION DETAILS
L6.01 IRRIGATION PLAN
L6.02 IRRIGATION LEGEND
L6.03 IRRIGATION DETAILS
L6.04 IRRIGATION DETAILS
L6.05 IRRIGATION DETAILS
L6.06 IRRIGATION DETAILS
L7.01 PLANTING PLAN
L7.02 PLANTING DETAILS

ARCHITECTURE
A0.21 SITE PLAN
A0.31 TRASH ENCLOSURE
A1.01 DEMO FLOOR PLAN & RCP BLDG A
A1.02 DEMO ROOF PLAN - BLDG A
A1.03 DEMO ELEVATIONS BLDG A
A2.01 FIRST FLOOR PLAN - BLDG A & B
A2.09 ROOF PLAN - BLDG A & B
A2.11 FIRST FLOOR EDGE OF SLAB PLAN - BLDG A & B
A2.21 FIRST FLOOR FINISHES PLAN - BLDG A & B
A2.31 FIRST FLOOR REFLECTED CEILING PLAN - BLDG A & B
A3.01 EXTERIOR ELEVATIONS - BLDG A
A3.02 EXTERIOR ELEVATIONS - BLDG B
A3.11 BUILDING SECTIONS BLDG A
A3.12 BUILDING SECTIONS BLDG B
A3.20 WALL SECTIONS
A3.21 WALL SECTIONS
A3.22 WALL SECTIONS
A3.23 WALL SECTIONS
A3.24 WALL SECTIONS
A3.26 WALL SECTIONS
A3.27 WALL SECTIONS
A4.01 ENLARGED PLANS & INTERIOR ELEVATIONS
A4.02 ENLARGED PLANS & INTERIOR ELEVATIONS
A4.03 ENLARGED RESTROOM PLANS & ELEVATIONS
A4.04 ENLARGED RESTROOM PLANS & ELEVATIONS
A4.05 ENLARGED RESTROOM PLANS & ELEVATIONS
A4.06 ENLARGED RESTROOM PLANS & ELEVATIONS
A4.07 ENLARGED RESTROOM PLANS & ELEVATIONS
A6.11 DOOR SCHEDULES
A6.21 OPENING TYPES
A6.31 FINISH & EQUIPMENT SCHEDULES
A8.12 EXTERIOR DETAILS
A8.13 EXTERIOR DETAILS
A8.14 OPENING DETAILS
A8.21 ROOF DETAILS
A8.22 ROOF DETAILS
A9.01 PARTITION TYPES
A9.11 INTERIOR DETAILS
A9.12 INTERIOR DETAILS
A9.21 CEILING DETAILS
A9.31 CASEWORK DETAILS
A9.32 CASEWORK DETAILS
A9.41 RESTROOM DETAILS
A9.42 RESTROOM DETAILS
A10.01 SIGNAGE PLAN & SCHEDULE - BLDG A & B
A10.41 SIGNAGE DETAILS

STRUCTURAL

SHEET INDEX

SHEET NUMBER SHEET NAME
AV3.01 AUDIO VISUAL ELEVATIONS
AV4.01 AUDIO VISUAL ONE LINE DIAGRAM
AV5.02 AUDIO VISUAL DETAILS

TECHNOLOGY
T0.01 TECHNOLOGY SYMBOLS AND LEGENDS
T0.02 TECHNOLOGY SITE PLAN
T1.00 TECHNOLOGY OVERALL FLOOR PLAN
T1.01 DEMO FLOOR PLANS - BUILDING A & B
T2.01 TECHNOLOGY FLOOR PLANS - BUILDING A & B
T5.01 TECHNOLOGY DETAILS

AQUATICS
SP-0 SWIMMING POOL AREA PLAN
SP-1 SWIMMING POOL LAYOUT PLAN
SP-2 SWIMMING POOL PIPING PLAN
SP-3 SWIMMING POOL UNDERWATER LIGHTING AND TIMING
PLAN
SP-4 SWIMMING POOL SECTIONS
SP-5 SWIMMING POOL WATER POLO LAYOUT
SP-6 DETAILS
SP-7 DETAILS
SP-8 DETAILS
SP-9 DETAILS
SP-10 DETAILS
SP-11 DETAILS
SP-12 DETAILS
SP-13 DETAILS
SP-14 DETAILS
SP-15 DETAILS
SP-16 DETAILS
SP-17 DETAILS
SP-18 SWIMMING POOL THERMAL SOLAR PLAN
SP-19 DETAILS
SP-20 DETAILS

AQUATICS
MR-1 MECHANICAL ROOM LAYOUT PLAN
MR-2 MECHANICAL ROOM SECTIONS
MR-3 DETAILS
MR-4 DETAILS
MR-5 DETAILS
MR-6 DETAILS
MR-7 DETAILS
MR-8 DETAILS
MR-9 DETAILS
MR-10 DETAILS
MR-11 DETAILS

SPORTS LIGHTING
MT1 NOTES FOUNDATION DETAIL
MS1 POLE DETAILS
MD1 ATTACHMENT DETAILS
MD2 ATTACHMENT DETAILS
MD3 ATTACHMENT DETAILS
SHADE
NC90132-1-1
000

NOTES/ LOM
NC90132-1-2
000

VIEWS AND DETAILS
NC90132-1-3
000

FOOTING DETAILS
NC90132-2-1
000

NOTES/ LOM
NC90132-2-2
000

VIEWS AND DETAILS
NC90132-2-3
000

FOOTING DETAILS
NC90132-3-1
000

NOTES/ LOM
NC90132-3-2
000

VIEWS AND DETAILS
NC90132-3-3
000

FOOTING DETAILS

ABBREVIATIONS SYMBOLS LEGEND SHEET INDEX

SHEET NUMBER SHEET NAME
S0.01 GENERAL NOTES
S0.02 GENERAL NOTES
S0.03 GENERAL NOTES
S1.11 SITE DETAILS
S1.12 SITE DETAILS
S1.13 SITE DETAILS
S1.21 SITE PLAN
S2.01A FOUNDATION PLAN - BLDG A
S2.09A ROOF FRAMING PLAN - BLDG A
S2.09B ROOF FRAMING PLAN - BLDG B
S3.01 ELEVATIONS - BLDG B
S3.02 ELEVATIONS - BLDG A
S3.21 PERF PANEL FRAMING ELEVATIONS AND SECTION
S6.01 TYPICAL FOUNDATION AND SOG DETAILS
S6.02 TYPICAL FOUNDATION AND SOG DETAILS
S6.03 TYPICAL FOUNDATION AND SOG DETAILS
S6.04 TYPICAL FOUNDATION AND SOG DETAILS
S6.05 TYPICAL FOUNDATION AND SOG DETAILS
S6.11 TYPICAL STRUCTURAL STEEL DETAILS
S6.12 TYPICAL STRUCTURAL STEEL DETAILS
S6.13 TYPICAL METAL DECKING DETAILS
S6.14 TYPICAL DECK SUPPORTING DETAILS
S6.61 TYP. CMU WALL ELEVATION AND DETAILS
S6.62 TYP. CMU WALL ELEVATION AND DETAILS
S6.63 TYP CMU WALL DETAILS
S6.81 TYP WOOD FRAMING DETAILS
S6.82 WOOD FRAMING DETAILS
S6.94 TYP EQUIP ANCHORAGE to WOOD
S6.71 TYPICAL LIGHT GAUGE FRAMING SCHEDULES and

ELEVATIONS
S6.72 TYPICAL LIGHT GAUGE METAL FRAMING DETAILS
S6.73 TYPICAL LIGHT GAUGE METAL FRAMING DETAILS 2
S6.74 TYPICAL INTERIOR LIGHT GAUGE FRAMING DETAILS
S6.91 EQUIPMENT ANCHORAGE DETAILS
S6.92 EQUIPMENT ANCHORAGE DETAILS
S6.93 TYP EQUIP ANCHORAGE to WOOD

MECHANICAL
M0.10 MECHANICAL LEGENDS AND GENERAL NOTES
M0.11 MECHANICAL LEGENDS AND GENERAL NOTES
M0.20 MECHANICAL SCHEDULES
M0.30 MECHANICAL TITLE-24 FORMS
M0.31 MECHANICAL TITLE-24 FORMS
M0.32 MECHANICAL TITLE-24 FORMS
M0.33 MECHANICAL TITLE-24 FORMS
M1.01 MECHANICAL DEMO FLOOR PLAN - BLDG A & B
M1.09 MECHANICAL DEMO ROOF PLAN - BLDG A & B
M2.01 MECHANICAL FLOOR PLAN - BLDG A & B
M2.09 MECHANICAL ROOF PLAN - BLDG A & B
M3.01 MECHANICAL PIPING/CONTROLS FLOOR PLAN - BLDG A & B M3.09 MECHANICAL PIPING & CONTROLS ROOF PLAN - BLDG A & B
M6.01 MECHANICAL CONTROL SEQUENCES AND DIAGRAMS
M7.10 MECHANICAL DETAILS AND DIAGRAMS
M7.11 MECHANICAL DETAILS AND DIAGRAMS
M7.12 MECHANICAL DETAILS AND DIAGRAMS

PLUMBING
P0.10 PLUMBING LEGENDS AND GENERAL NOTES
P0.20 PLUMBING FIXTURE AND EQUIPMENT SCHEDULES
P0.21 PLUMBING FIXTURE SCHEDULE & CALCULATIONS
P0.22 PLUMBING T24 BUILDING A
P0.23 PLUMBING T24 BUILDING B
P1.01 PLUMBING DEMO FLOOR PLAN - BLDG A & B
P1.09 PLUMBING DEMO ROOF PLAN - BLDG A & B
P2.01 PLUMBING DRAINAGE FLOOR PLAN - BLDG A & B
P3.01 PLUMBING WATER & GAS FLOOR PLAN - BLDG A & B
P3.09 PLUMBING ROOF PLAN - BLDG A & B
P4.01 PLUMBING ENLARGED PLANS - BLDG A
P4.02 PLUMBING ENLARGED PLANS - BLDG B
P6.10 PLUMBING DETAILS
P6.20 PLUMBING DETAILS

ELECTRICAL
E0.10 ELECTRICAL LEAD SHEET
E0.11 ELECTRICAL LEAD SHEET
E0.20 LIGHTING FIXTURE NOTES AND LCP SCHEDULES
E0.21 LIGHTING FIXTURE SCHEDULE
E1.10 ELECTRICAL SITE PLAN
E1.11 LIGHTING SITE PLAN
E2.01 ELECTRICAL DEMOLITION FLOOR PLAN - BLDG A & B
E2.02 ELECTRICAL FIRST FLOOR PLAN - BLDG A & B
E2.03 MECHANICAL/POWER FIRST FLOOR PLAN - BLDG A & B
E2.04 MECHANICAL/POWER ROOF PLAN - BLDG A & B
E3.01 LIGHTING PLANS
E4.01 ENLARGED ELECTRICAL PLANS
E5.01 SINGLE LINE DIAGRAM AND LOAD FEEDER SCHEDULE
E5.02 PV SYSTEM SINGLE LINE DIAGRAM
E5.03 PANEL SCHEDULES
E5.04 PANEL SCHEDULES
E5.05 PANEL SCHEDULES
E6.01 LIGHTING CONTROL DIAGRAM AND DETAILS
E6.02 LIGHTING CONTROL DIAGRAM AND DETAILS
E6.03 LIGHTING CONTROL DIAGRAMS AND DETAILS
E7.01 ELECTRICAL DETAILS
E7.02 ELECTRICAL DETAILS
E7.03 ELECTRICAL DETAILS
E7.04 PV DETAILS
E7.05 LIGHTING DETAILS
E8.01 ENERGY COMPLIANCE FORMS
E8.02 ENERGY COMPLIANCE FORMS

AUDIO VISUAL
AV0.01 AUDIO VISUAL SYMBOLS AND LEGENDS
AV0.03 AUDIO VISUAL SITE PLAN
AV1.02 AUDIO VISUAL OVERALL FLOOR PLAN
2 203

SHEET INDEX

SHEET NAME

SHEET LABEL
ISSUE DATEG0.00COVER SHEETGENERALG0.10SHEET INDEXG0.20GENERAL PROJECT INFORMATIONG0.32G0.40TYPICAL ACCESSIBILITY NOTES AND DETAILS G2.10G2.11CODE ANALYSIS
A1.01DEMO FLOOR PLAN & RCP BLDG A

ARCHITECTURE
08/09/2024
08/09/2024
08/09/202408/09/2024
08/09/202408/09/202408/09/202408/09/202408/09/2024
A2.01FIRST FLOOR PLAN - BLDG A & B08/09/2024A2.09
MECHANICALM0.10MECHANICAL LEGENDS AND GENERAL NOTES08/09/2024 E0.10ELECTRICAL LEAD SHEETELECTRICAL08/09/2024
E1.10ELECTRICAL SITE PLAN08/09/2024E1.1108/09/2024E2.01LIGHTING SITE PLAN08/09/2024E2.02ELECTRICAL DEMO FLOOR PLAN - BLDG A & B08/09/2024E2.03MECHANICAL/POWER FIRST FLOOR PLAN - BLDG A & B08/09/2024E3.01LIGHTING PLANS08/09/2024 08/09/2024A2.11
08/09/2024A3.01EXTERIOR ELEVATIONS - BLDG A08/09/2024A3.0208/09/2024A3.1208/09/2024A3.20WALL SECTIONS 08/09/202408/09/202408/09/2024ENLARGED RESTROOM PLANS AND ELEVATIONS M0.20MECHANICAL SCHEDULES08/09/2024M0.30MECHANICAL TITLE-24 FORMS08/09/2024M0.3108/09/2024 M2.01MECHANICAL FLOOR PLAN - BLDG A & B08/09/2024M3.01MECHANICAL PIPING/CONTROLS FLOOR PLAN - A & B08/09/2024 M7.1008/09/2024M7.1108/09/2024
MECHANICAL TITLE-24 FORMS

MECHANICAL DETAILS AND DIAGRAMSPLUMBING

SHEET NAME

ISSUE DATE
P0.10PLUMBING LEGENDS AND GENERAL NOTES08/09/2024P0.21PLUMBING FIXTURES AND EQUIPMENT SCHEDULES08/09/2024 P2.01

PLUMBING ENLARGED PLANS - BLDG A
08/09/2024
P4.01

PLUMBING DRAINAGE FLOOR PLAN - BLDG A & B
08/09/2024P6.20

PLUMBING WATER AND GAS FLOOR PLAN - BLDG A & B
08/09/2024
AV0.01AUDIO VISUAL08/09/2024
E0.11ELECTRICAL LEAD SHEET08/09/2024E0.20LIGHTING FIXTURE NOTES AND LCP SCHEDULES08/09/2024E0.21LIGHTING FIXTURE SCHEDULE08/09/2024 E4.01ENLARGED ELECTRICAL PLANS08/09/2024E5.01SINGLE LINE DIAGRAM AND LOAD FEEDER SCHEDULE08/09/2024E5.03PANEL SCHEDULES08/09/2024E5.0408/09/2024E6.01LIGHTING CONTROL DIAGRAMS AND DETAILS08/09/2024 E7.01ELECTRICAL DETAILS08/09/2024E7.02ELECTRICAL DETAILS08/09/2024E7.0308/09/2024 TECHNOLOGYT0.01TECHNOLOGY SYMBOLS & LEGENDS08/09/2024
T2.01TECHNOLOGY FLOOR PLANS - BLDG A & B08/09/2024T1.01TECHNOLOGY DEMO FLOOR PLANS - BLDG A & B08/09/202408/09/2024T5.01TECHNOLOGY DETAILS08/09/202408/09/2024 AUDIO VISUAL SYMBOLS AND LEGENDSAV0.0308/09/2024AUDIO VISUAL SITE PLANAV1.0208/09/2024AUDIO VISUAL OVERALL FLOOR PLANAV4.0108/09/2024AUDIO VISUAL ONE LINE DIAGRAMAV5.0208/09/2024AUDIO VISUAL DETAILS

SWIMMING POOL
08/09/2024SWIMMING POOL LAYOUT PLAN
08/09/2024SWIMMING POOL PIPING PLAN
08/09/2024SWIMMING POOL UNDERWATER LIGHT/TIMING PLAN
08/09/2024

SWIMMING POOL SECTIONS
08/09/2024DETAILS08/09/2024DETAILS08/09/2024DETAILS08/09/2024DETAILS08/09/2024DETAILS08/09/2024DETAILS08/09/2024DETAILS08/09/2024

MECHANICAL ROOM LAYOUT PLAN
08/09/202408/09/202408/09/202408/09/202408/09/2024

DETAILSDETAILSDETAILSDETAILS

DETAILS EGRESS PLAN
A4.01EXTERIOR PLANS & INTERIOR ELEVATIONS
08/09/2024
P6.10PLUMBING DETAILS08/09/2024
08/09/2024A2.2108/09/2024A2.31
08/09/2024A3.11BUILDING SECTIONS - BLDG A
08/09/202408/09/202408/09/202408/09/2024
08/09/202408/09/2024A4.04
MECHANICAL CONTROL SEQUENCES AND DIAGRAMSMECHANICAL DETAILS AND DIAGRAMS08/09/2024M6.0108/09/2024 PLUMBING ROOF PLAN08/09/2024
E8.0108/09/2024E8.02ENERGY COMPLIANCE FORMS08/09/2024ENERGY COMPLIANCE FORMS 08/09/2024
MECHANICAL ROOM SECTIONS G0.41CALGREEN08/09/2024G0.4208/09/2024 08/09/2024
T0.02TECHNOLOGY SITE PLAN08/09/2024T1.00TECHNOLOGY OVERALL FLOOR PLAN08/09/2024 AV3.0108/09/2024AUDIO VISUAL ELEVATIONS
P0.2008/09/2024
GRAND TOTAL SHEETS: 245
08/09/2024

CALGREENCALGREEN
A0.21SITE PLAN08/09/2024
A1.02DEMO FLOOR PLAN BLDG B08/09/2024A1.03DEMO ELEVATIONS BLDG A08/09/2024ROOF PLAN BLDG A & BFIRST FLOOR EDGE OF SLAB PLAN - BLDG A & BFIRST FLOOR FINISHES PLAN - BLDG A & BFIRST FLOOR REFLECTED CEILING PLAN - BLDG A & BEXTERIOR ELEVATIONS - BLDG BBUILDING SECTIONS - BLDG BA3.21WALL SECTIONSA3.22WALL SECTIONSA3.23WALL SECTIONSA3.24WALL SECTIONSA3.26WALL SECTIONSA3.27WALL SECTIONSA4.02EXTERIOR PLANS & INTERIOR ELEVATIONSA4.03ENLARGED RESTROOM PLANS AND ELEVATIONSA4.05ENLARGED RESTROOM PLANS AND ELEVATIONSA4.06ENLARGED RESTROOM PLANS AND ELEVATIONSA4.07ENLARGED RESTROOM PLANS AND ELEVATIONS08/09/2024A6.11DOOR SCHEDULES08/09/2024A6.31FINISH & EQUIPMENT SCHEDULES08/09/2024

TRASH ENCLOSURE
EXTERIOR DETAILSA8.1208/09/2024EXTERIOR DETAILSA8.1308/09/2024OPENING DETAILSA8.1408/09/2024OPENING DETAILSA8.1508/09/2024ROOF DETAILSA8.2108/09/2024ROOF DETAILSA8.2208/09/2024PARTITION TYPESA9.0108/09/2024A9.1108/09/2024INTERIOR TYPESA9.1208/09/2024INTERIOR TYPES

SHEET INDEX

SHEET NAME

SHEET LABEL

ISSUE DATE
A9.41RESTROOM DETAILS08/09/202408/09/202408/09/2024
A10.0108/09/2024A10.4108/09/2024SIGNAGE PLAN & SCHEDULE - BLDG A & BSIGNAGE DETAILS A9.32CASEWORK DETAILSA9.42RESTROOM DETAILS
S0.01GENERAL NOTESSTRUCTURAL08/09/2024
S1.11SITE DETAILS08/09/2024
S2.01AFOUNDATION PLAN - BLDG A
08/09/202408/09/2024
S3.01
08/09/2024
ELEVATIONS - BLDG B08/09/2024
S6.01TYPICAL FOUNDATION AND SOG DETAILSS6.02TYPICAL FOUNDATION AND SOG DETAILS S6.11
08/09/2024
TYPICAL STRUCTURAL STEEL DETAILSS6.13
08/09/2024
TYPICAL METAL DECKING DETAILS08/09/2024
S6.61TYPICAL CMU WALL ELEVATION AND DETAILSS6.63TYPICAL CMU WALL DETAILS S6.94
08/09/2024
08/09/2024S6.93
08/09/2024
TYPICAL EQUIP. ANCHORAGE TO WOOD
08/09/2024
S6.91TYPICAL EQUIPMENT ANCHORAGE DETAILSS6.92
08/09/2024

EQUIPMENT ANCHORAGE DETAILS
S0.02GENERAL NOTESS0.03GENERAL NOTESS1.12SITE DETAILS08/09/2024S1.21SITE PLAN08/09/2024S2.01BFOUNDATION PLAN - BLDG B08/09/2024S2.09AROOF FRAMING PLAN - BLDG A08/09/2024S2.09B08/09/2024ROOF FRAMING PLAN - BLDG BS3.02ELEVATIONS - BLDG B08/09/2024S3.21PERF PANEL FRAMING ELEVATIONS AND SECTION08/09/2024 S6.03TYPICAL FOUNDATION AND SOG DETAILS08/09/2024S6.04TYPICAL FOUNDATION AND SOG DETAILS08/09/2024S6.05TYPICAL FOUNDATION AND SOG DETAILS08/09/2024S6.12TYPICAL STRUCTURAL STEEL DETAILS08/09/2024 S6.62TYPICAL CMU WALL ELEVATION AND DETAILS08/09/2024
S6.81TYPICAL WOOD FRAMING DETAILS08/09/2024S6.82WOOD FRAMING DETAILS08/09/2024 TYPICAL EQUIP. ANCHORAGE TO WOOD08/09/202408/09/202408/09/2024 M0.11MECHANICAL LEGENDS AND GENERAL NOTES08/09/2024
M0.3208/09/2024MECHANICAL TITLE-24 FORMSM1.0108/09/2024MECHANICAL DEMO FLOOR PLAN - BLDG A & BM1.0908/09/2024MECHANICAL DEMO ROOF PLAN - BLDG A & BM2.09MECHANICAL ROOF PLAN - BLDG A & B08/09/2024M3.09MECHANICAL PIPING/CONTROLS ROOF PLAN - A & B M7.1208/09/2024MECHANICAL DETAILS AND DIAGRAMS

PLUMBING CALCULATIONS
P0.3008/09/2024PLUMBING DEMO SITE PLANP0.4008/09/2024PLUMBING SITE PLANP0.4008/09/2024PLUMBING SITE PLANP0.4108/09/2024PLUMBING SITE GAS PLANP1.0108/09/2024PLUMBING DEMO FLOOR PLAN - BLDG A & BP1.0908/09/2024PLUMBING DEMO ROOF PLAN - BLDG A & BP3.0108/09/2024P3.0908/09/2024PLUMBING ENLARGED PLANS - BLDG BP4.02PLUMBING DETAILS ELECTRICAL FIRST FLOOR PLAN - BLDG A & BE2.04MECHANICAL/POWER ROOF FLOOR PLAN - BLDG A & B08/09/2024 E5.02PV SYSTEM SINGLE LINE DIAGRAM08/09/2024
E5.0508/09/2024PANEL SCHEDULESPANEL SCHEDULESE6.02LIGHTING CONTROL DIAGRAMS AND DETAILS08/09/2024E6.03LIGHTING CONTROL DIAGRAMS AND DETAILS08/09/2024 ELECTRICAL DETAILSPV DETAILSE7.0408/09/2024LIGHTING DETAILSE7.0508/09/2024 SWIMMING POOL CONT.

E9.11EM EGRESS PHOTOMETRICS SITE08/09/2024
08/09/2024SP-0SWIMMING POOL AREA PLANSP-1SP-2SP-3SP-4SP-5SWIMMING POOL WATER POLO LAYOUTSP-6SP-7DETAILSDETAILS08/09/2024SP-8SP-9SP-10SP-11SP-12SP-13SP-14SP-15SP-16 SP-17SP-18SP-19SP-20MECHANICAL ROOMMR-108/09/2024MR-2MR-308/09/2024DETAILSMR-408/09/2024DETAILSMR-508/09/2024DETAILSMR-608/09/2024DETAILSMR-808/09/2024DETAILSMR-908/09/2024DETAILSMR-1008/09/2024DETAILSMR-1108/09/2024NOTES, FOUNDATION DETAILSMT108/09/2024

DETAILSDETAILS

SPORTS LIGHTING
DETAILSMR-708/09/2024
POLE DETAILSMS108/09/2024ATTACHMENT DETAILSMD108/09/2024ATTACHMENT DETAILSMD208/09/2024ATTACHMENT DETAILSMD308/09/2024 SHEET NUMBER010203040506070809101112131415161718192021222324252627282930313233343536373839404142434445474648495051525354555657585960616263646566676869717072737475767778798182838486858788899091 9394
A6.21OPENING TYPES08/09/2024
80 A9.21CEILING DETAILSA9.31CASEWORK DETAILS08/09/202408/09/2024

SHEET NUMBER
9596979899100101102103104
S1.13SITE DETAILS08/09/2024
S6.14TYPICAL DECK SUPPORTING DETAILS08/09/2024
S6.7408/09/2024S6.7308/09/2024S6.72TYPICAL LIGHT GAUGE METAL FRAMING DETAILS08/09/2024S6.7108/09/2024 106107108109110111112113114115116117118119120121122123124125126127128129130131132133134135136137138139140141 TYP. LIGHT GAUGE FRAMING SCH. AND ELEVATIONSTYPICAL LIGHT GAUGE METAL FRAMING DETAILSTYPICAL INTERIOR LIGHT GAUGE FRAMING DETAILS 142143144145146147148149150151153
M0.3308/09/2024MECHANICAL TITLE-24 FORMS
152154155156157158159160161162163164165166167
170171
P0.2208/09/2024PLUMBING T24 BUILDING AP0.2308/09/2024PLUMBING T24 BUILDING B 168169
172173174175176177178179180181182183
185186187188189190191192193194 SHEET LABEL

SHEET NUMBER
195196197
E9.12EM EGRESS PHOTOMETRICS BLD. A & B08/09/2024
198199201202200

SHEET INDEX
* A0.3108/09/2024
C3 EXISTING CONDITIONS
CIVIL
C4 DEMOLITION PLANC5C6C7 GRADING PLAN
C8C9 STORM DRAIN PLAN
C10C11C12

UTILITY PLAN
L0.01LANDSCAPE NOTES AND SCHEDULESLANDSCAPEL0.02L1.01MATERIALS PLAN L4.01SECTIONS AND ELEVATIONS
L5.01LANDSCAPE DETAILS
L7.01PLANTING PLANL7.02
08/09/2024
08/09/202408/09/202408/09/202408/09/2024
08/09/202408/09/202408/09/2024
08/09/202408/09/202408/09/202408/09/202408/09/202408/09/202408/09/202408/09/202408/09/202408/09/2024C2 CIVIL NOTES08/09/2024

HORIZONTAL CONTROL AND PAVING PLAN

SINGLE SHEET BMP PLAN
L4.02SECTIONS AND ELEVATIONS
08/09/2024
L4.03SECTIONS AND ELEVATIONS
08/09/2024
L5.02
08/09/2024
L5.03
08/09/2024
L5.04
08/09/2024
L5.05
08/09/2024L6.02
08/09/2024
L6.01IRRIGATION PLAN
08/09/2024L6.03
08/09/2024
IRRIGATION LEGEND AND NOTESL6.04
08/09/2024
IRRIGATION DETAILSL6.05IRRIGATION DETAILS

DETAILS
08/09/2024

DETAILS
08/09/202408/09/2024
L2.01LAYOUT PLAN
08/09/202408/09/2024
L3.01ENLARGEMENT PLAN
08/09/2024
08/09/202408/09/202408/09/2024
08/09/2024
***********
L4.04SECTIONS AND ELEVATIONS
C1 TITLE SHEET08/09/2024*

GRADING ENLARGEMENTS
08/09/2024

LANDSCAPE NOTES AND SCHEDULES
L5.06L5.07L5.08L5.09L5.10L5.11L5.12

LANDSCAPE DETAILSLANDSCAPE DETAILSLANDSCAPE DETAILSLANDSCAPE DETAILSLANDSCAPE DETAILSLANDSCAPE DETAILSLANDSCAPE DETAILSLANDSCAPE DETAILSLANDSCAPE DETAILSLANDSCAPE DETAILS

LANDSCAPE DETAILS

IRRIGATION DETAILS
PLANTING DETAILSL6.06IRRIGATION CALCULATIONS
******************************************************** 105
01020304050607080910111213
0102030405060708091011121314151617181920212223242526272829 TOTAL SHEETS: 203
* PER SEPARATE GRADING PERMIT
** PER SEPARATE LANDSCAPE PERMIT
92 G0.3108/09/2024TYPICAL ACCESSIBILITY NOTES AND DETAILS 184
203
08/09/2024

THESE PLANS AND SPECIFCATIONS DO NOT PROVIDE ANY DIRECTION

OR INSTRUCTIONS TO CONTRACTORS, SUBCONTRACTORS, MATERIAL

SUPPLIERS OR THEIR EMPLOYEES OR AGENTS RELATED TO

CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES OR

PROCEDURES, SAFETY PRECAUTIONS, MANNERS OR METHODS OF

EGRESS OR INGRESS, INCLUDING BUT NOT LIMITED TO JOB SITE

SAFETY, THE PHYSICAL CONDITION OF THE JOB SITE, THE MANNER OR

METHOD IN WHICH THE AREA WHERE WORK IS PERFORMED IS

ACCESSED BY WORKERS, AND SAFETY PROGRAMS OR SAFETY
PROTOCOLS OF ANY KIND IN CONNECTION WITH THE WORK. ALL OF

THE FOREGOING ARE SOLELY AND EXCLUSIVELY THE RESPONSIBILITY

OF THE CONTRACTOR, SUBCONTRACTOR, MATERIAL SUPPLIERS, OR ANY AGENTS OR EMPLOYEES THEREOF.

THE ARCHITECT EXPRESSLY DISCLAIMS ANY CONTROL OVER AND

RESPONSIBILITY FOR CONSTRUCTION MEANS, METHODS,

TECHNIQUES, SEQUENCES OR PROCEDURES, SAFETY PRECAUTIONS,

MANNERS OR METHODS OF EGRESS OR INGRESS, INCLUDING BUT

NOT LIMITED TO JOB SITE SAFETY, THE PHYSICAL CONDITION OF THE

JOB SITE, THE MANNER OR METHOD IN WHICH THE AREA WHERE

WORK IS PERFORMED IS ACCESSED BY WORKERS, AND SAFETY

PROGRAMS OR SAFETY PROTOCOLS OF ANY KIND IN CONNECTION WITH THE WORK.

THE ARCHITECT HAS NOT CONDUCTED AN EVALUATION OR ANALYSIS

OF SAFETY PROCEDURES OR APPLICABLE LAW REGARDING OR

RELATING TO ACCESSING THE JOB SITE OR AREAS OF THE WORK DURING THE COURSE OF CONSTRUCTION.

THE ARCHITECT, THE ARCHITECT ’S DESIGNS, AND ANY OTHER WORK

PERFORMED BY THE ARCHITECT DO NOT ADDRESS, ANALYZE OR

PROVIDE ANY DIRECTION OR ADVICE TO ANY PERSON OR ENTITY ON

WHETHER OR NOT THE USE OF EXISTING LADDERS, DOORS, RAILINGS,

INGRESS AND INGRESS ROUTES OR THE LIKE ARE IN COMPLIANCE OR

NON -COMPLIANCE WITH OSHA, CAL -OSHA(CALIFORNIA ONLY), OR ANY

OTHER APPLICABLE STATUTE, REGULATION, OR STANDARD RELATED

TO JOB SITE SAFETY DURING THE COURSE OF CONSTRUCTION OF THE IMPROVEMENTS.

NOTICE TO PERSONS PERFORMING WORK ON JOB

SITE, INCLUDING CONTRACTORS, SUBCONTRACTORS,

MATERIAL SUPPLIERS AND ANY AGENTS OR

EMPLOYEES THEREOF

RESPONSIBILTY FOR JOB SITE SAFETY

1. ALL CONSTRUCTION & MATERIALS SHALL BE AS SPECIFIED & IN ACCORDANCE

WITH ALL APPLICABLE CODES, ORDINANCES, LAWS, PERMITS & THE CONTRACT DOCUMENTS.

2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE ACCURATE PLACEMENT OF ALL NEW CONSTRUCTION ON THE SITE.

3. THE CONTRACTOR IS RESPONSIBLE FOR ALL EXG SURVEY MONUMENTS WHICH

MAY BE DISTURBED THROUGH CONSTRUCTION ACTIVITIES DEEMED NECESSARY FOR PRESERVATION BY THE CIVIL ENGINEER. IF SUCH

MONUMENTS WERE DISTURBED, THE APPLICANT SHALL HAVE A LICENSED

LAND SURVEYOR QUALIFIED CIVIL ENGINEER REESTABLISH ANY SUCH

MONUMENTATION DAMAGED OR DESTROYED DURING THE CONSTRUCTION OF THE PROJECT & SUBMIT "PRELIMINARY CORNER RECORDS" TO THE CIVIL ENGINEER AFTER REPLACEMENT. AFTER APPROVAL BY THE CIVIL ENGINEER,

THE APPLICANT SHALL FILE THE CORNER RECORDS WITH THE COUNTY SURVEYOR. PRIOR TO THE EXONERATION OF ANY SECURITY, EVIDENCE OF SUCH FILING SHALL BE FURNISHED TO THE CIVIL ENGINEER.

4. THE CONTRACTOR IS RESPONSIBLE TO INSURE THAT TRUCK ROUTES SHALL BE STEERED AWAY FROM RESIDENTIAL AREAS.

5. THE CONTRACTOR SHALL ENSURE THAT TRUCKS HAULING DIRT ON PUBLIC ROADS TO & FROM THE SITE SHALL BE COVERED OR WILL MAINTAIN A 6"

DIFFERENTIAL BETWEEN THE MAX HGT OF ANY HAULED MATERIAL & THE TOP OF THE HAUL TRAILER. HAUL TRUCK DRIVERS SHALL WATER THE LOAD PRIOR TO LEAVING THE SITE TO PREVENT SOIL LOSS DURING TRANSPORT.

6. THE CONTRACTOR SHALL ENSURE THAT GRADED SURFACES USED FOR OFF

ROAD PARKING, MATERIALS LAY -DOWN, OR AWAITING FUTURE CONSTRUCTION SHALL BE STABILIZED FOR DUST CONTROL AS NEEDED. FREQUENTLY

ACCESSED UNPAVED AREAS SHALL BE PAVED AS EARLY AS POSSIBLE TO MINIMIZE DIRT TRACKOUT TO PUBLIC RIGHTS -OF -WAY.

7. THE CONSTRACTOR SHALL COORDINATE ANY LANE CLOSURES OR DETOURS WITH THE CITY/COUNTY. FLAG PERSONS & APPROPRIATE TRAFFIC CONTROL

DEVICES SHALL BE USED AS NEEDED TO MINIMIZE CONSTRUCTION ACTIVITY INTERFERENCE WITH OFF -SITE -TRAFFIC.

8. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS & SITE CONDITIONS BEFORE STARTING WORK. SHOULD A DISCREPANCY APPEAR IN THE CONTRACT

DOCUMENTS OR BETWEEN THE CONTRACT DOCUMENTS & EXISTING

CONDITIONS, NOTIFY THE ARCHITECT AT ONCE FOR INSTRUCTION ON HOW TO PROCEED.

9. SHOULD A CONFLICT OCCUR BETWEEN DWGS & SPECIFICATIONS, THE MORE

COSTLY CONDITION SHALL TAKE PRECEDENCE, UNLESS A WRITTEN DECISION

FROM THE ARCHITECT HAS BEEN OBTAINED WHICH DESCRIBES A
CLARIFICATION OR ALTERNATE METHOD AND/OR MATERIALS.

10. THE CONTRACTOR SHALL CONFINE HIS OPERATION ON THE SITE TO AREAS PERMITTED BY OWNER.

11. THE JOBSITE SHALL BE MAINTAINED IN A CLEAN, ORDERLY CONDITION FREE OF

DEBRIS & LITTER & SHALL NOT BE UNREASONABLY ENCUMBERED WITH ANY MATERIALS OR EQUIPMENT. EACH SUBCONTRACTOR IMMEDIATELY UPON

COMPLETION OF EACH PHASE OF HIS WORK SHALL REMOVE ALL TRASH & DEBRIS AS A RESULT OF HIS OPERATION.

12. ALL MATERIAL STORED ON THE SITE SHALL BE PROPERLY STACKED & PROTECTED TO PREVENT DAMAGE & DETERIORATION. FAILURE TO PROTECT MATERIALS MAY BE CAUSE FOR REJECTION OF WORK.

13. THE CONTRACTOR SHALL DO ALL CUTTING, FITTING, AND/OR PATCHING OF HIS

WORK THAT MAY BE REQ TO MAKE ITS SEVERAL PARTS FIT TOGETHER

PROPERLY & SHALL NOT ENDANGER ANY OTHER WORK BY CUTTING, EXCAVATING, OR OTHERWISE ALTERING THE TOTAL WORK OR ANY PART OF IT.

ALL PATCHING, REPAIRING AND REPLACING OF MATERIALS AND SURFACES,

CUT OR DAMAGED IN EXECUTION OF WORK, SHALL BE DONE WITH APPLICABLE

MATERIALS SO THAT SURFACES REPLACED WILL, UPON COMPLETION, MATCH SURROUNDING SIMILAR SURFACES.

14. STRUCTURAL OBSERVATION WILL BE PERFORMED BY THE STRUCTURAL ENGINEER. WHEN REQ, A STATEMENT IN WRITING SHALL BE GIVEN TO THE

BUILDING OFFICIAL, STATING THAT THE SITE VISITS HAVE BEEN MADE &

WHETHER OR NOT ANY OBSERVED DEFICIENCIES HAVE BEEN CORRECTED TO CONFORM TO THE APPROVED PLANS & SPECIFICATIONS.

15. SUBMITTAL DOCUMENTS FOR DEFERRED SUBMITAL ITEMS SHALL BE

SUBMITTED TO THE ARCHITECT OR ENGINEER OF RECORD, WHO SHALL

REVIEW THEM & RETURN THEM TO THE CONTRACTOR (WITH A NOTIFICATION

INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN

REVIEWED & THAT THEY HAVE BEEN FOUND TO BE IN GENERAL

CONFORMANCE WITH THE DESIGN OF THE BUILDING) FOR PLAN CHECK APPROVAL. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL

THEIR DESIGN & SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE AUTHORITY HAVING JURISDICTION.

16. PROVIDE ALL ACCESS PANELS AS REQ BY GOVERNING CODES TO ALL CONCEALED SPACES, VOIDS, ATTICS, ETC. VERIFY TYPE REQ WITH ARCHITECT PRIOR TO INSTALLATION.

17. NO PORTION OF WORK REQ A SHOP DWG OR SAMPLE SUBMISSION SHALL BE COMMENCED UNTIL THE SUBMISSION HAS BEEN REVIEWED BY THE ARCHITECT.

ALL SUCH PORTIONS OF THE WORK SHALL BE IN ACCORDANCE WITH CORRECTED SHOP DWGS. AND SAMPLES.

18. DIMENSIONS:

A. ALL DIMS SHALL TAKE PRECEDENCE OVER SCALE.

B. ALL DIMS ARE TO FACE OF STUD / CONCRETE / MASONRY UNO C. CLG HGT DIMS ARE FROM FACE OF SLAB TO FACE OF FIN CLG MATERIAL UNO

19. DO NOT SCALE DRAWINGS

20. PROVIDE ALL NECESSARY BLOCKING, BACKING, & FRAMING FOR LIGHT

FIXTURES, ELECTRIC UNITS, AC EQUIP, RECESSED ITEMS, AND ALL OTHER ITEMS AS REQ.

21. WHERE LARGER STUDS OR FURRING ARE REQ TO COVER PIPING AND

CONDUITS, THE LARGER STUD SIZE OR FURRING SHALL EXTEND THE FULL

SURFACE OF THE WALL WIDTH AND LENGTH WHERE THE FURRING OCCURS, UNO.

22. ALL DOORS SHALL BE OPERABLE FROM THE INSIDE W/O THE USE OF A KEY OR SPECIAL KNOWLEDGE OF EFFORT. EXIT SIGNS SHALL BE PROVIDED AT ALL EXITS AS REQ BY THE APPLICABLE CODES. ALL DOOR SWINGS SERVING AN OCCUPANT LOAD OF 50 OR GREATER SHALL SWING IN THE DIRECTION OF TRAVEL.

23. ALL GLASS AND GLAZING SHALL COMPLY WITH THE APPLICABLE CODES.

24. WALL AND CLG MATERIALS SHALL NOT EXCEED THE FLAME SPREAD CLASSIFICATIONS IN THE APPLICABLE CODES.

25. SURVEYORS CERTIFICATE REQ PRIOR TO FINAL COMPLETION.

26. THE CONTRACTOR SHALL COMPLY WITH THE APPLICABLE CODES FOR FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION.

27. A DSA CERTIFIED CLASS 1 PROJECT INSPECTOR EMPLOYED BY THE DISTRICT (OWNER) AND APPROVED BY THE DIVISION OF THE STATE ARCHITECT (DSA) SHALL PROVIDE CONTINUOUS INSPECTION OF THE WORK. THE DUTIES OF THE INSPECTOR ARE DEFINED IN SECTION 4 -342, CALIFORNIA BUILDING STANDARDS ADMINISTRAIVE CODE (PART 1, TITLE 24, CCR)

28. A DSA ACCEPTED TESTING LABORATORY DIRECTLY EMPLOYED BY THE

DISTRICT (OWNER) SHALL CONDUCT ALL THE REQ TESTS AND INSPECTIONS FOR THE PROJECT.

29. CHANGE TO THE APPROVED DWGS AND SPECIFICATIONS SHALL BE MADE BY

ADDENDA OR CONSTRUCTION CHANGE DOCUMENT (CCD) APPROVED BY DSA, AS REQ BY SECTION 4 -338, PART 1, TITLE 24, CCR.

30. THE INTENT OF THESE DWGS AND SPECIFICATIONS IS THAT THE WORK OF THE

ALTERATION, REHABILITATION OR RECONSTRUCTION IS TO BE IN ACCORDANCE WITH TITLE 24, CCR. SHOULD ANY EXG CONDITIONS SUCH AS

DETERIORATION OR NON -COMPLYING CONSTRUCTION BE DISCOVERED

WHICH IS NOT COVERED BY THE CONTRACT DOCUMENTS WHEREIN THE FINISHED WORK WILL NOT COMPLY WITH TITLE 24, CCR, A CONSTRUCTION

CHANGE DOCUMENT (CCD), OR A SEPARATE SET OF PLANS AND

SPECIFICATIONS, DETAILING AND SPECIFYING THE REQ WORK SHALL BE

SUBMITTED TO AND APPROVED BY DSA BEFORE PROCEEDING WITH THE WORK. (SECTION 4 -317(c), PART 1, TITLE 24, CCR)

1. PLANS FOR THE FIRE SPRINKLER SYSTEMS MUST BE APPROVED BY THE AUTHORITY HAVING JURISDICTION (AHJ) PRIOR TO INSTALLATION. SUBMIT

PLANS IN A MANNER WHICH WILL NOT IMPEDE THE PROGRESS OF CONSTRUCTION.

2. FIRE SPRINKLER SYSTEMS & INSTALLATION SHALL CONFORM W/ THE APPLICABLE STANDARDS AND CODES.

3. FIRE SPRINKLER SYSTEMS TO BE TIED INTO THE ALARM SYSTEM PER THE APPLICABLE CODES.

4. AUTOMATIC SPRINKLER SYSTEM(S) SHALL BE SUPERVISED BY AN APPROVED

CENTRAL OR REMOTE STATION SERVICE, AND/OR SHALL BE PROVIDED W/ A LOCAL ALARM WHICH WILL GIVE AN AUDIBLE SIGNAL.

5. FIRE SPRINKLER SYSTEM(S) & ALL CONTROL VALVES SHALL BE SUPERVISED BY A U.L. LISTED CENTRAL ALARM STATION OR PER THE APPLICABLE CODES.

6. FIRE HYDRANT & FIRE SPRINKLER SYSTEM(S) SHALL BE FLUSHED

THOROUGHLY BEFORE CONNECTION IS MADE TO EXISTING SYSTEM STUBOUTS & WITNESSED BY THE PROJECT INSPECTOR.

7. A HYDROSTATIC TEST (200 PSI PRESSURE FOR 2 HRS. OR @ 50 PSI IN EXCESS OF THE MIN. STATIC PRESSURE WHEN IT IS IN EXCESS OF 150 PSI) SHALL BE

WITNESSED BY THE PROJECT INSPECTOR PRIOR TO COVERING PIPING JOINTS.

8. A 3' CLR SPACE SHALL BE MAINTAINED AROUND THE CIRCUMFERENCE OF FIRE

HYDRANTS EXCEPT AS OTHERWISE REQ OR APPROVED PER THE APPLICABLE CODES.

9. THRUST BLOCKS SHALL BE PROVIDED WHEREVER PIPE CHANGES DIRECTION.

10. ALL PIPE SHALL BE UL LISTED FOR FIRE SERVICE SYSTEMS, CLASS 200 MIN.

11. FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED W/I 100' FROM A PUBLIC FIRE HYDRANT PER THE APPLICABLE STANDARDS AND CODES.

12. FIRE SPRINKLER RISER SHALL BE LOCATED WITHIN 5 FT OF THE EXT WALL (OR AS REQ BY THE AHJ) AND TERMINATE 6" ABV FF

13. AN ALL -WEATHER FIRE ACCESS ROAD SHALL BE IN PLACE BEFORE ANY COMBUSTIBLE MATERIALS ARE PLACED ON THE SITE OR AS REQ BY THE AHJ.

14. STORAGE, DISPENSING, OR USE OF ANY FLAMMABLE & COMBUSTIBLE LIQUIDS,

FLAMMABLE & COMPRESSED GASES & OTHER HAZARDOUS MATERIALS SHALL COMPLY W/ THE APPLICABLE CODES.

15. EXIT SIGNS SHALL BE POSTED OVER EXIT DOORS & DIRECTIONAL EXIT SIGNS SHALL BE LOCATED TO DIRECT PERSONS TOWARD EXIT DOORS.

16. EXIT SIGNS SHALL BE SELF -LUMINOUS TYPE OR ELECTRONICALLY

ILLUMINATED & ENERGIZED FROM SEPARATE CIRCUITS, ONE OF WHICH SHALL

BE FROM STORAGE BATTERIES OR AN ON -SITE GENERATOR, FOR A DURATION OF 90 MINUTES PER THE APPLICABLE CODES.

17. EXIT DOORS SHALL BE OPENABLE FROM THE INSIDE WITHOUT THE USE OF A KEY OR ANY SPECIAL KNOWLEDGE OR EFFORT.

18. ACCESS GATE(S) SHALL BE OPENABLE W/ FIRE DEPT MASTER KEY FROM THE EXTERIOR.

19. CURBS ALONG FIRE LANES SHALL BE PAINTED SAFETY RED & MARKED "FIRE LANE NO PARKING" W/ 3" WHITE LETTERS ON THE TOP OF CURBING EVERY 30' AS INDICATED ON THE APPROVED DRAWINGS.

20. APPROVED NUMBERS OR ADDRESSES SHALL BE PROVIDED FOR ALL NEW &

EXG BLDGS IN SUCH A POSITION AS TO BE PLAINLY VISIBLE & LEGIBLE FROM

THE STREET OR ROAD FRONTING THE PROPERTY PER THE APPLICABLE CODES.

21. PROVIDE PERMANENT OR TEMPORARY STANDPIPES WHILE BUILDING IS UNDER CONSTRUCTION PER THE APPLICABLE CODES.

22. PROVIDE FIRE EXTINGUISHERS PER THE REQ THE APPLICABLE STANDARDS AND CODES.
11B-201.4 CONSTRUCTION SUPPORT FACILITIES. These requirements shall apply to temporary or permanent construction support facilities for uses and activities not directly associated with the actual processes of construction, including but not limited to offices, meeting rooms, plan rooms, other administrative or support functions. When provided, toilet and bathing facilities serving construction support facilities shall comply with 11B-213. When toilet and bathing facilities serving construction support facilities are provided by portable units, at least one of each type shall be accessible and connected to the construction support facilities it serves by an accessible route.

EXCEPTION: During construction an accessible route shall not be required between site arrival points or the boundary of the area of construction and the entrance to the construction support facilities if the only means of access between them is a vehicular way not providing pedestrian access.

ACCESSIBLE CONSTRUCTION SUPPORT FACILITIES
TEL: 422.339.2941

DIRECTOR OF FACILITY
NAME: CITY OF CARLSBAD

CLIENT INFORMATION
CITY,STATE, ZIP: CARLSBAD, CA 92008
ADDRESS: 1200 CARLSBAD VILLAGE DRIVE
CONTACT: KYLE LANCASTER E-MAIL: [email protected] TEL: 619/795-2555
NAME: LPA, INC.

ARCHITECT
CONTACT: MICHAEL DAVIS E-MAIL: mdavis@lpadesignstud ios.com TEL: 916.287.2336
NAME: LPA, INC.

LANDSCAPE ARCHITECT
CONTACT: RITA FRINK E-MAIL: rfrink@lpadesignstudios. com TEL: 949.769.6265
NAME: LPA, INC.

CIVIL ENGINEER
CITY,STATE, ZIP: IRVINE, CA 92617
ADDRESS: 5301 CALIFORNIA AVE, SUITE 100
CONTACT: ROBERT RICHARDSON
E-MAIL:
[email protected] TEL: 619.280.4321
NAME: ATLAS TECHNICAL CONSULTANTS LLC

GEOTECHNICAL ENGINEER
CITY,STATE, ZIP: SAN DIEGO, CA 92120
ADDRESS: 6280 RIVERDALE STREET
CONTACT: ERICK ALDRICH E-MAIL: erick.aldrich@oneatl as.com TEL: 619/795-2555
NAME: LPA, INC.

STRUCTURAL ENGINEER
CITY,STATE, ZIP: SAN DIEGO, CA 92106
ADDRESS: 2765 TRUXTUN RD
CONTACT: HARSHDA PRASAD E-MAIL: hprasad@lpadesignst udios.com TEL: 949.701.4228
NAME: LPA, INC.

MECHANICAL ENGINEER
CITY,STATE, ZIP: IRVINE, CA 92617
ADDRESS: 5301 CALIFORNIA AVE, SUITE 100
CONTACT: ERICK PULIDO E-MAIL: epulido@lpadesignstud ios.com TEL: 949.701.4272
NAME: LPA, INC.

ELECTRICAL ENGINEER
CITY,STATE, ZIP: IRVINE, CA 92617
ADDRESS: 5301 CALIFORNIA AVE, SUITE 100
CONTACT: OSCAR CHAVEZ E-MAIL: ochavez@lpadesignstud ios.com TEL: 949.701.4172
NAME: LPA, INC.

PLUMBING ENGINEER
CITY,STATE, ZIP: IRVINE, CA 92617
ADDRESS: 5301 CALIFORNIA AVE, SUITE 100
CONTACT: ERIK RING E-MAIL: [email protected] om TEL: ###-###-####
NAME: TK1SC

FIRE ALARM
CITY,STATE, ZIP: IRVINE, CA 92618
ADDRESS: 15231 LAGUNA CANYON ROAD, SUITE 100
CONTACT: ROBINSON NGUYEN E-MAIL: robinson.nguyen@ws p.com CITY,STATE, ZIP: SAN DIEGO, CA 92106
ADDRESS: 2765 TRUXTUN RD
CITY,STATE, ZIP: SAN DIEGO, CA 92106
ADDRESS: 2765 TRUXTUN RD
TEL: 949-751-5819
NAME: TK1SC

AUDIO VISUAL
CITY,STATE, ZIP: IRVINE, CA 92618
ADDRESS: 15231 LAGUNA CANYON ROAD, SUITE 100
CONTACT: DAVID BROWN E-MAIL: [email protected]
TEL: 949-751-5819
NAME: TK1SC

TECHNOLOGY
CITY,STATE, ZIP: IRVINE, CA 92618
ADDRESS: 15231 LAGUNA CANYON ROAD, SUITE 100
CONTACT: RICHARD BRYSACZ E-MAIL: [email protected] om N

PROJECT NORTH
SITE
ADDRESS:
3401 Monroe St, Carlsbad, CA
92008
N

TRUE NORTH

1. THE SCOPE OF THE PROJECT INCLIDES THE FOLLOWING:
- DEMO OF EXISTING POOL, POOL DECK, POOL PUMP BUILDING AND INTERIOR OF EXISTING

POOL FACILITIES BUILDING ( EXISTING RESTROOMS, CHANGING ROOMS, LOBBY, OFFICE ETC) - NEW POOL WITH ASSOCIATED INFRASTRUCTUE, POOL PUMP BUILDING NEW INTERIOR WALLS

AND FINISHES OF EXISTING BUILDING
- NEW DETACHED ADDITION TO EXISTING BUILDING
- NEW PV SOLAR SYSTEM FOR BUILDING
- NEW SOLAR THERMAL SYSTEM FOR POOL HEATING

LIST OF APPLICABLE CODES
2022 CALIFORNIA ADMINISTRATIVE CODE (CAC), PART 1, TITLE 24 CCR 2022 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 CCR 2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 CCR 2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 CCR 2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 CCR 2022 CALIFORNIA ENERGY CODE, PART 6, TITLE 24 CCR
2022 CALIFORNIA FIRE CODE (CFC), PART 9, TITLE 24 CCR
2022 CALIFORNIA EXISTING BUILDING CODE (CEBC), PART 10, TITLE 2 4 CCR 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN), PART 11, TITLE 24 CCR
2022 CALIFORNIA REFERENCED STANDARDS CODE, PART 12, TITLE 24 CC R TITLE 19 CCR, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS

APPLICABLE STANDARDS

FOR A LIST OF APPLICABLE STANDARDS, INCLUDING CALIFORNIA AMENDME NTS TO THE NFPA STANDARDS, REFER TO CBC CHAPTER 35 AND CFC CHAPTER 8 0.

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

GENERAL PROJECT

INFORMATION
G0.20
MD
MONROE ST. POOL REPLACEMENT

GENERAL PROJECT INFORMATION

CONSTRUCTION NOTES

FIRE AND LIFE SAFETY NOTES

ACCESSIBILITY NOTES PROJECT DIRECTORY

VICINITY MAP

PROJECT SCOPE

LIMIT OF WORK

THE INTENT OF THE LIMIT OF WORK LINE IS TO DESCRIBE IN GENERAL THE AREAS AFFECTED BY PROJECT CONSTRUCTION. IT IS NOT INTENDED TO BE AN EXACT INDICATION OR EDGE OF THE CONSTRUCTION AREA. THE CONTRACTOR SHOULD

VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING CONDITIONS AND THEIR RELATIONSHIP TO THE WORK PROPOSED IN THE CONTRACT DOCUMENTS. ALL

ITEMS NECESSARY FOR THE PROPER EXECUTION AND COMPLETION OF THE WORK SHALL BE INCLUDED. THE CONTRACT DOCUMENTS ARE COMPLEMENTARY

AND WHAT IS REQUIRED BY ONE SHALL BE BINDING AS IF REQUIRED BY ALL TO

THE EXTENT THAT IT IS REASONABLY INFERABLE FROM THEM AS BEING NECESSARY TO PRODUCE THE INTENDED RESULTS.

DEFERRED APPROVALS

ADDITIVE ALTERNATES

APPLICABLE CODES

1. (N) STUCCO FINISH ON ALL EXTERIOR WALLS AT (E) "BUILDING A", PENDING

SELECTIVE DEMO AND REVIEW OF EXISTING CONDITION OF CMU BLOCK BY CLIENT AND ARCHITECT.

1. FIRE ALARM

2. SHADE CANOPY ENGINEERING

3. MECHANICAL ROOF SCREEN ENGINEERS
203
3 08/09/2024

TO REFLECTIVE SURFACE

LAVATORY GRAB BAR MIRROR

FEMININE
NAPKIN

VENDING

MACHINE
SEAT
COVER

DISPENSER URINAL
HAND
DRYER
BABY

CHANGING

STATION
33" MIN
36" MAX
40" MAX ABOVE LAVATORIES
44" MAX
40" MAX
34" MAX

KNEE CLEARANCE
29" MIN

KNEE CLEARANCE
27" MIN
NOTE: ALL KNEE & TOE AREAS ARE TO BE CLEAR

COUNTERTOP / TOP OF LAVATORY

ALL EXPOSED PIPES TO BE

INSULATED TO PROTECT AGAINST
CONTACT. NO SHARP OR ABRASIVE

SURFACES UNDER LAVATORIES
6" MAX
KNEE CLEARANCE AT 9"
25" MAX
8"MIN KNEE CLEARANCE
9" MIN
WASTE
TOWEL
17" MAX
13 1/2" MIN
REFER TO: CBC 11B306.2, CBC 11B306.2.2, CBC 11B306.3, CBC 11B-603.3, CBC 11B603.5, CBC 11B-605.2, CBC 11B-606, & CBC 11B609.4 11" MIN
27" MAX
25" MAX
17" MIN TOE CLEARANCE
1 / 4 "
1 / 4 "
1 / 2 "
1/4" MAX
1 2
REFER TO: 11B-303.3
REFER TO: 11B-303.2
60" MIN
59" FLOOR M
TD W
C
56" M
IN W
ALL M
TD W
C

CLEARANCE
6" MIN
PLAN
NOTES:

1. TOE CLEARANCE AT THE SIDE PARTITION IS NOT REQ I N A COMPARTMENT > 66" WIDE

2. REFER TO: CBC 11B-604.8.1.4 & CBC 11B-604.8.1.1. 3
ELEVATION CHILDREN (K-12) ELEVATION ADULT
12" M
IN
6" MIN
9" M
IN
6" MIN
TOILET

PARTITION
TOILET

PARTITION
17"-18"
42" MIN 12" MAX
56" MIN
48" MIN CLR
60" M
IN CLR
12" M
IN
24" M
IN
30" M
IN CLR
48" MIN CLR
REFER TO: CBC 11B-604.3.1,
CBC 11B-604.5.1, & CBC
11B-606.2
18" M
IN

DOOR PERMITTED

TO SWING OVER

HATCHED

PORTION OF

MANEUVERING
SPACE
REFER TO: CBC 11B-305.7.1
30 x 48
CLR
≤ 24"
30 x 48
CLR
> 24"
36" MIN

TOILET TISSUE

DISPENSER
3" MAX PROJECTION

WATER CLOSET (SIDE) WATER CLOSET (FRONT)

CENTERLINE OF WATER

CLOSET TO FACE OF FINISH

FLUSH VALVE TO

WIDE SIDE OF
SPACE

SANITARY NAPKIN

DISPENSER
3" MAX PROJECTION
54" MIN
42" MIN 12" MAX
33" M
IN 36" M
AX
M
IN
19"
M
IN

1-1/2"
24" MIN
7"-9"
36" MIN
12" MIN

ACCESSIBLE WATER CLOSET
17" - 18" AT WHEELCHAIR
24" MIN

TOP OF GRAB BAR
36" M
AX
REFER TO: CBC 11B-604.1/2/7
17" - 19" TOP OF SEAT
X>27"
4"MAX
X> 80"
REFER TO: 11B-307.2

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

TYPICAL

ACCESSIBILITY

NOTES AND

DETAILS
G0.31
MD
MONROE ST. POOL REPLACEMENT

TYPICAL ACCESSIBILITY NOTES AND DETAILS
1/2" = 1' -0"
G0.31 01 ACCESSIBLE MOUNTING HEIGHTS
6" = 1' -0"
G0.31 10 CHANGES IN LEVEL
3/8" = 1' -0"
G0.31 02 WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT TOE CLEARANCE 1/2" = 1' -0"
G0.31 06 ACCESSIBLE FIXTURES AT
SINGLE OCC. RESTROOM
3/8" = 1' -0"
G0.31 03 ACCESSIBLE URINAL PARTITIONS
1/2" = 1' -0"
G0.31 11 ACCESSIBLE MOUNTING HEIGHTS
3/8" = 1' -0"
G0.31 09 ACCESSIBLE PATH OF TRAVEL

PROTRUDING OBJECT LIMITS
4 203
08/09/2024

38" MIN - 43" MAX
36" MAX
27" MIN
14"
16" MIN 16" 16" MIN
48" MIN
(80" MIN CLR)

SEE RCP

DRINKING

FOUNTAIN

ELEVATION
18" MIN
19" MAX
18" MIN
16" MIN 16" 16" MIN
32" MIN AT SINGLE ACCESSIBLE DF

REFER TO FLOOR PLAN
PLAN
NOTES:

1. DRINKING FOUNTAIN SHALL BE ACCESSIBLE.

2. DRINKING FOUNTAINS SHALL BE LOCATED COMPLETELY W ITHIN ALCOVES OR

OTHERWISE POSITIONED SO AS NOT TO ENCROACH INTO PEDESTRIAN WAYS. THE ALCOVE IN WHICH THE WATER FOUNTAIN IS LOCATED SHALL NOT BE LESS THAN 32" WIDE AND 18" DEEP.

3. DRINKING FOUNTAIN SHALL BE A MIN OF 18" AND A MA X OF 19" DEEP AND

THERE SHALL BE A CLEAR AND UNOBSTRUCTED KNEE SPACE UNDER THE DRINKING FOUNTAIN NOT LESS THAN 27" HIGH, 30" WIDE AND 8" DEEP, THE

DEPTH MEASUREMENT BEING TAKEN FROM THE FRONT EDGE OF THE FOUNTAIN.

4. THERE SHALL BE TOE CLEARANCE OF 9" ABOVE THE FLO OR, AND 17" DEEP FROM THE FRONT EDGE OF THE FOUNTAIN.

5. A CLEAR FLOOR SPACE AT LEAST 30" X 48" SHALL BE PROVIDED IN FRONT OF THE DRINKING FOUNTAIN TO ALLOW FORWARD APPROACH.

6. THE DRINKING FOUNTAIN BUBBLER SHALL BE ACTIVATED BY A MANUALLY

OPERATED SYSTEM THAT IS FRONT MOUNTED OR SIDE MOUNTED AND LOCATED WITHIN 6" OF THE FRONT EDGE OF THE FOUNTAIN OR AN ELECTRONICALLY CONTROLLED DEVICE.

7. THE BUBBLER OUTLET ORIFICE SHALL BE LOCATED WITH IN 5" OF THE FRONT OF THE DRINKING FOUNTAIN AND SHALL BE WITHIN 36" OF THE FLOOR. THE

WATER STREAM FROM THE BUBBLER SHALL BE SUBSTANTIALLY PARALLEL TO THE FRONT EDGE OF THE DRINKING FOUNTAIN.
5" MAX
15" MIN
30"
48"
8" MIN
19" MAX.
1 8 "
16" 16" 16"

PLAN - GUARDRAIL WHERE NOTED
5" MAX
15" MIN
30"
4 8 "
1 2 " 6"
32" MIN AT SINGLE ACCESSIBLE DF

REFER TO FLOOR PLAN

GUARDRAIL, TYP

BARRIER NEEDS

TO PROJECT ST

LEAST AS FAR AS

THE DRINKING

FOUNTAIN
REFER TO: CBC 11B-306.3, CBC 11B-602, & CBC 11B-602.9
6" MAX
6" MAX
5" MAX
18"-19"
18" MIN
27" MIN
36" MAX
32" MIN CLR
48" MIN 48" MIN
48" MIN
(A) (B)
(C)
REFER TO: CBC 11B-404.2.6
NOTES:

1. ALIGN CENTER OF ALL WALL SWITCHES & WALL DEVICES @ CENTERLINES UNO

2. REFER TO: CBC 11B-308

J-BOX FOR CLOCK

WALL SWITCHES,

ELEC DEVICES &

THERMOSTAT
WHERE OCCURS;

PROVIDE BRIDGING

FRAME REQ

ELEC OUTLET

WHERE OCCURS
15" AFF UNO
48" AFF MAX
27" MAX
X < 80"
REFER TO: CBC 11B-307.4

GUARDRAIL OR

OTHER BARRIER
60" MIN SIDE OF EXT DOOR
18" MIN AT INT
24" MIN ON EXT
X > 8 "
(A) PULL SIDE (B) PUSH SIDE
48" MIN
X > 8 "
(C) PUSH SIDE, DOOR

PROVIDED WITH

BOTH CLOSER AND
LATCH
48" MIN
X > 8 "
12" MIN
REFER TO: CBC 11B-404.2.4.3
15" MIN
48" MAX 48" MAX

UNOBSTRUCTED

FORWARD REACH

OBSTRUCTED HIGH

FORWARD REACH

OBSTRUCTED HIGH

FORWARD REACH
20" MAX
44" MAX
>20"-25" MAX
REFER TO: CBC 11B-308.2.1 & CBC 11B-308.2.2
15" MIN
48" MAX
34" MAX
48" MAX

UNOBSTRUCTED SIDE REACH

OBSTRUCTED HIGH SIDE REACH OBSTRUCTED HIGH SIDE REACH
46" MAX
10" MAX
10" MAX >10"-24" MAX
34" MAX
REFER TO: CBC 11B-306.3.1 & CBC 11B-308.3.2
60" MIN 18" MIN
48" MIN
12" MIN
48" MIN
36" MIN
60" MIN 44" MIN 22" MIN
48" MIN
22" MIN
60" MIN 24" MIN
44" MIN 24" MIN
48" MIN 24" MIN
(A)

FRONT APPROACH, PULL SIDE
(C)

FRONT APPROACH, PUSH SIDE, DOOR

PROVIDED WITH BOTH CLOSER AND LATCH
(B)

FRONT APPROACH, PUSH SIDE
(D)

HINGE APPROACH, PULL SIDE
(G)

HINGE APPROACH, PUSH SIDE, DOOR

PROVIDED WITH BOTH CLOSER AND LATCH
(F)

HINGE APPROACH, PUSH SIDE
(H)

LATCH APPROACH, PULL SIDE
(J)

LATCH APPROACH, PUSH SIDE
(K)

LATCH APPROACH, PUSH SIDE, DOOR

PROVIDED WITH CLOSER
ADD 6 INCHES AT

EXT SIDE OF EXT
DOOR
REFER TO: CBC 11B-404.2.4.1

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

TYPICAL

ACCESSIBILITY

NOTES AND

DETAILS
G0.32
MD
MONROE ST. POOL REPLACEMENT

TYPICAL ACCESSIBILITY NOTES AND DETAILS
1/2" = 1' -0"
G0.32 17 DRINKING FOUNTAIN ALCOVE
3/8" = 1' -0"
G0.32 05 DOOR CLEARANCES - DOORS IN SERIES
1/2" = 1' -0"
G0.32 10 TYPICAL DEVICE INSTALLATION
3/8" = 1' -0"
G0.32 08 VERTICAL CLEARANCE
3/8" = 1' -0"
G0.32 03 RECESSED DOOR CLEARANCES
3/8" = 1' -0"
G0.32 02 ACCESSIBLE FORWARD REACH

REQUIREMENTS
3/8" = 1' -0"
G0.32 04 ACCESSIBLE SIDE REACH

REQUIREMENTS
3/8" = 1' -0"
G0.32 11 DOOR CLEARANCES
5 207
203
08/09/2024

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

CALGREEN (CA)
G0.40
MD
MONROE ST. POOL REPLACEMENT

CALGREEN (CA)
X
X
X
X
X
X
X
6 203
2 08/09/2024

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

CALGREEN (CA)
G0.41
MD
MONROE ST. POOL REPLACEMENT

CALGREEN (CA)
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
7 203
08/09/2024

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

CALGREEN (CA)
G0.42
MD
MONROE ST. POOL REPLACEMENT

CALGREEN (CA)
X
X
X
X
X
X
X
X
X
8 203
08/09/2024

COMPACT

COMPACT

COMPACT

COMPACT

COMPACT

COMPACT

COMPACT

COMPACT

COMPACT

COMPACT

COMPACT

COMPACT
N S - 2 4 0 6 2 7 0 2 . 7 0 7 2 9 5 R E V IT CO N T R O L P O IN T E W - 7 4 7 7 8 5 0 1 . 9 9 4 5 0 9 E le v - 0 ' -0 " NO

PARKING
EV

CHARGING
ONLY

NO PARKING
EV

CHARGING
ONLY
EV

CHARGING
ONLY
EV

CHARGING
ONLY
EV

CHARGING
ONLY
EV

CHARGING
ONLY
R
T
MIN. 8" FROM BACK OF

PEDESTAL TO EOP
1M 1M
10 13
18 16
16 12
12 13
11 11
11 11
14 20
20 11
21 21
21 22
21 22
22 22
22 22
23 11
22 22
22 24
24 17
11 22
22 11
11 11
11 11
17 17
25 25
26 24
24 21 21 21 21
22 22
22 27
27 27
11 15
28 19
19 27
27 10
28 27
17 206
208
203
208
207
207
206
208
207
210
205
205
200
200
200
200
205
6"
4"
5"
5"
12"
6"
12"
12"
4"
4"
4"
12"
12"
12"
6"x2
EV

CHARGING
ONLY
EV

CHARGING
ONLY
EV

CHARGING
ONLY
EV

CHARGING
ONLY
EV

CHARGING
ONLY
EV

CHARGING
ONLY
EV

CHARGING
ONLY
R
T
R
T
C
C
C
10 13
18 16
16 12
12 13
11 11
11 11
14 20
20 11
21 21
21 22
21 22
22 22
22 22
23 11
22 22
22 24
24 17
11 22
22 11
11 11
11 11
17 17
25 25
26 24
24 21 21 21 21
22 22
22 27
27 27
11 15
28 19
19 27
27 10
28 27
17 NO

PARKING
DECK: 11169 SF/15 OLF = 745 OCC
POOL: 9227 SF / 50 OLD = 185 OCC
BLEACHERS: (25' X 12)/18" = 200 OCC
BLDG: 55 OCCUPANTS
TOTAL = 1182
344
344
344
344
150
BLDG B
BLDG A
L=140'
L=150'
L=150'
(E) FIRE ACCESS

FROMN PRIVATE DRIVE AISLE
150

REQUIRED
PROVIDED 36"
30"

REQUIRED
PROVIDED 48"
30"

REQUIRED
PROVIDED 72"
69"

REQUIRED
PROVIDED 96"
69"

REQUIRED
PROVIDED 96"
69"
166'-0"
146'-0" 35'-6"
108'-0" EATD
132'-0" EATD
19'-2" EATD
41'-3" EATD
96'-8" EATD 42'-4" EATD
13'-3"
241'-2"

VAN ACCESSIBLE
CONTROL AREAS, PER MR-1, MR-4

NORTH POOL
CANOPY

WEST POOL
CANOPY

WEST BLDG A NEW CANOPY
SOUTH

BLDG A NEW
CANOPY
38'-8"
75'-8"
61'-11"
89'-8"
21'-8"
26'-0"
51'-2"
106'-11"
54'-6"
30'-5"
45'-11" EATD
109'-2" EATD
BUILDINGS "A" & "B"

BUILDING CLASSIFICATION
BUILDING USE: RESTROOMS, SHOWERS/ LOCKERS, ADMIN/ O FFICE POOL SUPPORT SPACES. POOL PUMP ROOM, FAMILY

RESTROOMS SHOWERS/ CHANGING ROOMS
OCCUPANCY: A-5, B
ACCESSORY OCCUPANCIES (508.3.1): S-2
INCIDENTAL USES (508.2): NONE
CONSTRUCTION TYPE: TYPE V - B
FIRE PROTECTION: NON SPRINKLERED
FLOOR AREA ALLOWABLE - CBC (CHAPTER 5)
BASIC ALLOWABLE AREA AND HEIGHT (TABLE 503)
AREA PER STORY: 9,000SF (A t)
NUMBER OF STORIES: 2
HEIGHT: 40 FT

PROPOSED BUILDING HEIGHT/STORY
BUILDING HEIGHT A: 17'-2" (EXISTING)
BUILDING HEIGHT B: 17'-2"
FRONTAGE INCREASE FACTOR l
f (CBC 506.3.3)
If: .38 (83% OF BUILDING PERIMETER HAS 20' TO LESS THA N 25' OPEN SPACE) AREA INCREASE MIXED USE PER STORY A a = [A t + (NS x l f ) (CBC 506.2.2) At: 9,000
NS: 9,000
I
f: .38
TOTAL ALLOWABLE AREA (CBC 506.2.2)
Aa: 12,420SF

PROPOSED BUILDINGS SQUARE FOOTAGE
2,968 SF - EXISTING BUILDING 'A'
+ 242 SF - PROPOSED BUILDING 'A' ADDITION
+ 800 SF - PROPOSED BUILDING 'A SOUTH STORAGE FABRIC CANOPY + 725 SF - PROPOSED BUILDING 'A' WEST CANOPY
+ 2,108 SF - PROPOSED BUILDING 'B'
+ 1,429 SF - PROPOSED NORTH POOL DECK FABRIC CANOPY
+ 1,254 SF - PROPOSED WEST POOL DECK FABRIC CANOPY
+ 187 SF - PROPOSED TRASH ENCLOSURE
TOTAL 9,713 SF < 12,420SF (OK)
FIRE-RESISTANCE RATING REQ FOR BLDG ELEMENTS (CBC 601)
STRUCTURAL FRAME: 0
EXTERIOR BEARING WALLS: 0
INTERIOR BEARING WALLS: 0
EXTERIOR NONBEARING WALLS: 0
INTERIOR NONBEARING WALLS: 0
FLOOR CONSTRUCTION: 0
ROOF CONSTRUCTION: 0
TOTAL OCCUPANCY: 1,182 OCCUPANTS/ 2 = 591 MEN / 591 WOMEN

TOTAL REQUIRED FIXTURES

WATER CLOSET URINALS LAVATORIES SHOWERS
MEN 4 4 4 6
WOMEN 5 4 6
DRINKING FOUNT.
3 PROPOSED POOL
POOL CLASSIFICATION`
OCCUPANCY TYPE: A-5
AREA: 8,812 SF
POOL DECK AREAS: 12,450 SF
REQUIRED PUBLIC FIXTURES PER SECTION 3116B.2
POOL: 15 SF / OCCUPANT
TOTAL OCCUPANTS: 1,182 OCCUPANTS
PARKING SPACES (11B-208)
TOTAL STALLS: 54
REQUIRED TOTAL ACCESSIBLE STALLS: 03
REQUIRED VAN ACCESSIBLE STALLS: 01
ACCESSIBLE STALLS PROVIDED: 03
ACCESSIBLE VAN STALLS PROVIDED: 01
EV PARKING SPACES (11B-228.3.2.1)
REQUIRED EV CAPABLE SPACES 10
REQUIRED EVCS 03
REQUIRED EV VAN STALLS 01
LEGEND

ACCESSIBLE PATH OF TRAVEL

HOSE PULL

PROPERTY LINE

EXIT ACCESS TRAVEL DISTANCE EATD

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. T he
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

CODE ANALYSIS
G2.10
MD
MONROE ST. POOL REPLACEMENT

CODE ANALYSIS
1" = 20' -0"
G2.10 08 SITE EXITING PLAN

CODE ANALYSIS LEGEND
203
9 08/09/2024

1 A
2 BC
3 4
D
232 SF
16 OCC.

MULTI

PURPOSE
ROOM
14 B 1:15
56 SF
1 OCC.

ELEC.
14A
S-2 1:300
25 SF
1 OCC.

STORAGE
04A
S-2 1:300
124 SF
4 OCC.

MEN'S

CHANGING/

LOCKERS
05 B 1:50
MEN'S
SHOWER
06 MEN'S

RESTROOM
04 CORRIDOR
02 221 SF
15 OCC.

STAFF
LOUNGE
03 B 1:15
230 SF
16 OCC.

LOBBY
01 B 1:15
STAFF
SHOWER
03B
STAFF
RR
03A
128 SF
1 OCC.

ADMIN
07 B 1:150
99 SF
1 OCC.

OFFICE
07A
B 1:150

CORRIDOR
08 WOMEN'S
SHOWER
11 126 SF
4 OCC.

WOMEN'S

CHANGING/

LOCKERS
10 B 1:50 WOMEN'S

RESTROOM
09 23 SF
1 OCC.

STORAGE
09A
S-2 1:300
15 REQUIRED
PROVIDED 72"
3"
14 14
17 1
5 1
3 1
21 5
1 REQUIRED
PROVIDED 48"
3"

REQUIRED
PROVIDED 48"
3"

REQUIRED
PROVIDED 48"
3"

REQUIRED
PROVIDED 48"
3"

REQUIRED
PROVIDED 36"
3"

REQUIRED
PROVIDED 64"
3 1/2"
15 386 SF
2 OCC.

EXTERIOR

STORAGE
18 S-2 1:300
2 114 SF
3 OCC.

FIRST AID
16 B 1:50
76 SF
1 OCC.

EQUIPMENT

STORAGE
17 S-2 1:300
18'-9"
5 6
7 F E
903 SF
3 OCC.

POOL PUMP
ROOM
22 S-2 1:300
175 SF
1 OCC.

STORAGE
19 S-2 1:300
120 SF
1 OCC.

ELECTRICAL
21 S-2 1:300
140 SF
3 OCC.

CORRIDOR/

LOCKERS
20 A-3 1:50
FAMILY

RESTROOM/
SHOWER
20C
1 1

REQUIRED
PROVIDED 62"
3"

REQUIRED
PROVIDED 32"
3"

REQUIRED
PROVIDED 48"
3"

REQUIRED
PROVIDED 48"
3"
64 SF

CHEMICAL
ROOM
24 64 SF

CHEMICAL
ROOM
25 3 1 1
3 LEGEND

METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION

CMU WALL CONSTRUCTION

GLAZING SYSTEM

PATH OF TRAVEL

EXISTING WALLS

1. CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS AND REPORT ALL DISCREPANCIES TO ARCHITECT.

2. EXTERIOR WALL DIMENSIONS ARE TO FACE OF STRUCTURAL SHEATHING, U.N.O. INTERIOR WALL DIMENSIONS ARE TO FACE OF STUD, U.N.O. VERIFY ANY DISCREPANCIES IN THE FIELD WITH THE ARCHITECT PRIOR TO BUILDING.

3. ALL GYPSUM BOARD EXPOSED TO VIEW SHALL HAVE LEVEL #4 FINISH, U.N.O.

4. FURRING AT COLUMNS, ROOF DRAINS, PIPES AND SIMILAR ELEMENTS TO BE HELD AS TIGHT TO OBSTRUCTION AS POSSIBLE, U.N.O.

5. AT ALL WET WALL LOCATIONS INCLUDING TOILET ROOMS, PROVIDE MOISTURE

RESISTANT GYPSUM BOARD AT EXPOSED AREAS AND CEMENTITIOUS BACKER BOARD BEHIND TILE.

6. PROVIDE THERMAL BATT INSULATION AT ALL EXTERIOR WALL AND ROOF ASSEMBLIES. R19 MIN. AT WALLS AND R40 MIN. AT ROOF.

7. LOCATE DOOR FRAME 6" MIN. FROM ADJACENT WALL FRAMING, TYP. DOOR FRAMES ARE TO BE LOCATED 6" FROM ADJACENT WALL FRAMING, U.N.O.

8. SLAB PLANS INDICATE WHICH WALLS REQUIRE CURBS. REFER TO WALL TYPES AND DETAILS FOR CURB WIDTHS.

9. WINDOW FRAME AND GLAZING TYPES PER EXTERIOR ELEVATIONS.

10. REFER TO INTERIOR ELEVATIONS FOR QUANTITY, LOCATION, AND DIMENSIONS OF WHITEBOARDS. COORDINATE AND PROVIDE BACKING AS REQUIRED.

11. ALL PLYWOOD AND WOOD BLOCKING SHALL BE FIRE TREATED PER TYPE IIA CONSTRUCTION.

12. CURTAINS SHALL NOT BE USED TO COVER OR BLOCK THE VIEW OF EXITS P ER SECTIONS 806.2 AND 1010.1 CBC.

13. THE MEANS OF EGRESS SHALL BE ILLUMINATED AT ALL TIMES THE BUILDI NG SPACE IS OCCUPIED.

14. THE MEANS OF EGRESS ILLUMINATION LEVEL SHALL NOT BE LESS THAN 1 FOOT -CANDLE AT THE WALKING SURFACE.

15. THE MEANS OF EGRESS ILLUMINATION SHALL BE SUPPLIED BY BACKUP

POWER (CONSISTING OF STORAGE BATTERIES, UNIT EQUIPMENT, OR AN ON - SITE GENERATOR) FOR A DURATION OF NOT LESS THAN 90 MINUTES. CBC 1008.3

GENERAL NOTES
0 0
### SF
Occ-Load OCC.

Room Name
###
# 1:OLF

ROOM NUMBER

SQUARE FOOTAGE

OCCUPANT LOAD

OCCUPANCY LOAD FACTOR

OCCUPANCY GROUP

COMBINED ROOM OCCUPANCY LOAD

INDIVIDUAL ROOM OCCUPANCY LOAD

REQUIRED
PROVIDED 36"
32"

REQUIRED EGREE WIDTH PER CODE

ANALYSIS
- DOORS/THRESHOLDS AT .15"/OCC PER
EXCEPTION #1 1005.3.2 OF CBC 2022;
- STAIRWAYS AT .3"/OCC

PROVIDED WIDTH

NO OCCUPANT LOAD

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

EGRESS PLAN
G2.11
MD
MONROE ST. POOL REPLACEMENT

EGRESS PLAN

KEYNOTE LEGEND
1/8" = 1' -0"
G2.11 04 BLDG A EGRESS
1/8" = 1' -0"
G2.11 11 BLDG B EGRESS
10 203
08/09/2024

COMPACT

COMPACT

COMPACT

COMPACT

COMPACT

COMPACT

COMPACT

COMPACT

COMPACT

COMPACT

COMPACT

COMPACT
N S - 2 4 0 6 2 7 0 2 . 7 0 7 2 9 5
R E V IT CO N T R O L P O IN T E W - 7 4 7 7 8 5 0 1 . 9 9 4 5 0 9 E le v - 0 ' -0 " NO

PARKING
EV

CHARGING
ONLY

NO PARKING
EV

CHARGING
ONLY
EV

CHARGING
ONLY
EV

CHARGING
ONLY
EV

CHARGING
ONLY
EV

CHARGING
ONLY
R
T
MIN. 8" FROM BACK OF

PEDESTAL TO EOP
1M 1M
10 13
18 16
16 12
12 13
11 11
11 11
14 20
20 11
11 21 21
22 21
22 22
22 22
22 23 11
22 22
22 24
24 24
17 11
22 22
11 11
11 11
11 11
17 17
17 25
25 26
24 24
21 21 21 21
22 22
22 11
27 27
27 11
15 28
19 19
27 27
10 28
27 17
206
208
203
208
207
207
206
208
207
210
205
205
200
200
200
200
205
6"
4"
5"
5"
12"
6"
12"
12"
4"
4"
4"
12"
12"
12"
6"x2
EV

CHARGING
ONLY
EV

CHARGING
ONLY
EV

CHARGING
ONLY
EV

CHARGING
ONLY
EV

CHARGING
ONLY
EV

CHARGING
ONLY
EV

CHARGING
ONLY
R
T
R
T
C
C
C
10 13
18 16
16 12
12 13
11 11
11 11
14 20
20 11
11 21 21
22 21
22 22
22 22
22 23 11
22 22
22 24
24 24
17 11
22 22
11 11
11 11
11 11
17 17
17 25
25 26
24 24
21 21 21 21
22 22
22 11
27 27
27 11
15 28
19 19
27 27
10 28
27 17
NO

PARKING
N

PROJECT NORTH
N

TRUE NORTH
A0.31
06 32.01
61'-11"
89'-8"
75'-8"
28'-2"

32.02 106'-11"
LEGEND
ACCESSIBLE PATH OF TRAVEL (P.O.T.)
ACCESSIBLE PATH OF TRAVEL (P.O.T.). BARRIER -FREE

ACCESS ROUTE WITHOUT ANY ABRUPT VERTICAL CHANGES
EXCEEDING 1/2" BEVELED AT 1:2 MAXIMUM SLOPE, EXCEPT
THAT LEVEL CHANGES DO NOT EXCEED 1/4" VERTICAL AND
IS AT LEAST 48" WIDE. SURFACE IS SLIP RESISTANT,
STABLE, FIRM, AND SMOOTH. CROSS -SLOPE DOES NOT
EXCEED 2% AND SLOPE IN THE DIRECTION OF TRAVEL IS
LESS THAN 5% UNLESS OTHERWISE INDICATED. P.O.T.

SHALL MAINTAIN FREE OF OVERHANGING OBSTRUCTIONS
TO 80" MINIMUM (11B -307.4) AND PROTRUDING OBJECTS
GREATER THAN 4" PROJECTION FROM WALL AND ABOVE 27"
AND LESS THAN 80" (11B -204 AND 11B -307). ARCHITECT TO

VERIFY THAT ALL BARRIERS IN THE PATH OF TRAVEL HAVE

BEEN REMOVED OR WILL BE REMOVED UNDER THIS

PROJECT, AND PATH OF TRAVEL COMPLIES WITH CBC
11B -206 PER 11B -201.4.

CONSTRUCTION SUPPORT FACILITIES, RELATED PARKING,

AND TOILETS SHOULD BE INCLUDED IN THE PATH OF
TRAVEL (EXCEPT AS NOTED IN 11B -203.2)

GENERAL NOTES

1. FOR PATH OF TRAVEL, CODE ANALYSIS, AND BUILDING DATA, REFER TO G2.10

2. FOR FIRE ACCESS INFORMATION, REFER TO G2.10

3. ALL AREAS AND SQUARE FOOTAGE DESCRIPTIONS SHOWN ARE FOR AGENCY

USE ONLY AND SHALL NOT BE USED FOR BIDDING OR CONSTRUCTION PURPOSE.

4. GATES IN THE PATH OF EGRESS MUST COMPLY WITH EXIT DOOR REQUIREMENTS. PROVIDE LEVER HARDWARE AND KICKPLATE. REFER TO LANDSCAPE DRAWINGS.

5. SHADE CANOPY ENGINEERING IS A DEFERRED SUBMITTAL.

PROPOSED BUILDING CANOPY/ OVERHANG

INDICATES RESTROOM OUTLINES (M) MEN, (W)

WOMEN, (R) RESTROOM

EASEMENT BOUNDARY, PER CIVIL DRAWINGS

PROPOSED CANOPY, PER LANDSCAPE
DRAWINGS. SHADE CANOPY ENGINEERING IS
A DEFERRED SUBMITTAL.

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

SITE PLAN
A0.21
MD
MONROE ST. POOL REPLACEMENT

SITE PLAN

KEYNOTE LEGEND

32.01 OUTDOOR STORAGE, WITH FABRIC CANOPY, REF SHEET : 3.0-2000.

SHADE CANOPY ENGINEERING IS A DEFERRED SUBMITTAL.

32.02 NEW POOL PER, SP-1
B
A
NEW

BUILDING
NEW

ADDITION

EXISTING

BUILDING
2,108 SF
2,968 SF
242 SF

EASEMENT BOUNDARY, PER CIVIL DRAWINGS

EASEMENT BOUNDARY, PER CIVIL DRAWINGS
11 203
08/09/2024

A0.31
09 A0.31
04 A0.31
08 A0.31
05 18'-8"
10'-8"
8'-8"
1'-0"

32.04 3'-8"
1'-0"
6'-6"
2'-4"
6'-6"
1'-0"
1'-0"
1'-0"
1'-0"
1'-0"
1'-0"
11 A0.31

32.03 32.04
04 L5.12

32.03 10
L5.12

CONCRETE CURB
8" CONCRETE UNIT

MASONRY, SPLIT FACE

TO MATCH EXISTING

CONCRETE BLOCK CAP
FOOTING, REF TO: 02/S1.11
CMU WALL, REF TO: 02/S1.11
CONCRETE SLAB PER CIVIL 0'-6"
1'-0" 6'-4"
2"
6'-6"

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

TRASH ENCLOSURE
A0.31
MD
MONROE ST. POOL REPLACEMENT

TRASH ENCLOSURE

KEYNOTE LEGEND

32.03 CMU SPEC

32.04 6" TALL CONCRETE CURB.
1/4" = 1' -0"
A0.31 06 TRASH ENCLOSURE FLOOR PLAN
3/8" = 1' -0"
A0.31 09 SOUTHWEST ELEVATION
3/8" = 1' -0"
A0.31 04 NORTHWEST ELEVATION
3/8" = 1' -0"
A0.31 08 NORTHEAST ELEVATION
3/8" = 1' -0"
A0.31 05 SOUTHEAST ELEVATION
1" = 1' -0"
A0.31 11 TRASH ENCLOSURE WALL AND
CURB
12 203
08/09/2024

1 A
2 BC
3 4
D
A1.03
15 A1.03 05
A1.03 11
A1.03
04 02.01 02.01

02.02 02.05

02.12 02.11

02.06 02.07

02.04 02.04

02.05 02.02

02.12 02.11

02.08 02.06

02.07 02.16

02.15 02.18

02.18 02.23

02.22 02.13

02.28 02.28

02.36 02.37
1 A
2 BC
3 4
D

02.17 02.20

02.21 02.21

02.20 02.20

02.21 02.20

02.29 02.29

02.29 02.29

02.29 02.29

02.29 02.23

DEMO FLOOR PLAN LEGEND
EXISTING WALL TO REMAIN. PROTECT IN PLACE.

EXISTING WALL TO BE DEMOLISHED

EXISTING DOOR AND FRAME TO BE REMOVED

EXTENTS OF EXISTING SLAB DEMOLITION

DEMO RCP LEGEND

EXISTING HARD LID CEILING TO BE DEMOLISHED
2'X2' ACT CEILING SYSTEM TO BE DEMOLISHED
INCLUDES TILE AND GRID.

DEMO KEYOTE

LIGHT FIXTURE TO BE DEMOLISHED
?

DEMOLITION GENERAL NOTES

1. THE EXISTING CONDITIONS SHOWN ARE FROM AVAILABLE RECORD DRAWINGS AND SHOWN FOR REFERENCE ONLY. CONTRACTOR SHALL VERIFY ACTUAL EXISTING CONDITIONS AT SITE PRIOR TO SUBMITTING BID. ALL DEMOLITION, ALTERATION,

EXTENSION, RELOCATION, REHABILITATION WORK SHALL BE INCLUDED IN CONTRACT. NO ADDITIONAL ALLOWANCE OR CHANGE ORDERS WILL BE ACCEPTED.

2. CONTRACTOR IS RESPONSIBLE TO RELOCATE OR REMOVE FROM WALLS, CEILINGS, FLOOR SPACES, ETC. ANY EXISTING CONDUITS, WIRES, BOXES, FITTINGS,

FIXTURES OR OTHER ELECTRICAL EQUIPMENT WHICH INTERFERES WITH PLANNED REMODEL WORK. PROVIDE CIRCUIT CONTINUATION REQUIRED FOR ALL EXISTING OUTLETS, FIXTURES, EQUIPMENT, ETC. SCHEDULED TO REMAIN.

3. NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY WHEREVER EXISTING EQUIPMENT

IS ENCOUNTERED WHICH MUST BE RELOCATED DUE TO THE NEW CONSTRUCTION, OR NOT INDICATED ON "AS -BUILT" DRAWINGS OR WAS BURIED UNDERGROUND OR EMBEDDED IN STRUCTURE WALLS.

4. CAREFULLY PROTECT ALL WALLS, TRIM, FLOORS, EQUIPMENT, UTILITY LINES AND MATERIALS. WHEN WORKING ON FINISHED SURFACES, LIMIT DAMAGE TO THE

SMALLER AREA IF POSSIBLE AND RESTORE TO THE ORIGINAL CONDITION ALL SURFACES WHICH ARE DAMAGED BECAUSE OF THE INSTALLATION OF THIS WORK.

5. EQUIPMENT, MATERIALS AND SUPPLIES TEMPORARILY REMOVED FOR PROTECTION SHALL BE REPLACED IN ORIGINAL LOCATIONS. ANY MATERIALS DAMAGED SHALL

BE REPLACED WITH NEW MATERIALS OF LIKE KIND AND QUALITY

6. DEMOLITION WORK SHALL BE DONE IN A MANNER WHICH WILL NOT CAUSE

UNNECESSARY INCONVENIENCE OR DANGER TO USERS OF THE PREMISES AND ADJACENT SITE, AND NOT INTERFERE WITH ITS OPERATION. ANY DEMOLITION WORK TO BE PERFORMED MUST BE PLANNED IN ADVANCE.

7. DO ALL DRILLING, CUTTING, ETC. REQUIRED TO DEMOLISH ELECTRICAL WORK AS

INDICATED OR PROVIDE BLANK COVER PLATE ON ALL OUTLETS EXPOSED BY REMOVAL OF FIXTURE OF DEVICES.

8. RESEAL ALL PENETRATIONS OR OPENING THROUGH WALLS, CEILING, FLOORS, ETC., TO MAINTAIN THE RATING OF STRUCTURE.

9. CONTRACTOR SHALL VERIFY EXISTING CONDUIT/CONDUCTOR RUNS ON CIVIL DEMOLITION PLAN, SHEET C1.1. REUSE AS REQUIRED AND REMOVE ALL UNUSED CONDUIT/CONDUCTORS. REMOVE CONDUIT BACK TO SCOPE OF WORK LIMIT LINE.

AT EACH END OF FEEDER, TAG AND LABEL CONDUIT. DOCUMENT DETAILED DIMENSIONS ON AS -BUILTS. REMOVE CONDUCTORS BACK TO SOURCE (VERIFY WITH OWNER). UNUSED CONDUIT IN INACCESSIBLE LOCATIONS (WALLS TO REMAIN) CAN BE ABANDONED IN PLACE.

10. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDUIT/WIRING RUNS, REUSE AS REQUIRE AND REMOVED ALL UNUSED CONDUIT/WIRING. UNUSED CONDUIT IN INACCESSIBLE LOCATIONS (WALLS TO REMAIN) CAN BE ABANDONED IN PLACE.

REMOVE UNUSED WIRING.

11. CONTRACTOR TO VERIFY CIRCUIT NUMBER AND LOADS FOR ALL EXISTING

EQUIPMENT PRIOR TO INSTALLATION OF NEW OR RELOCATED ELECTRICAL EQUIPMENT. REASSIGN CIRCUITS AND LOADS ACCORDINGLY. PROVIDE COMPLETE "AS BUILT" DRAWINGS AND TYPEWRITTEN DIRECTORIES FOR PANELS.

12. WHERE NECESSARY TO SHUT OFF UTILITY SERVICES OR CAUSE INTERRUPTION TO

POWER OR SIGNAL SYSTEMS WHILE A BUILDING IS OCCUPIED OR THAT EFFECT

ADJACENT BUILDINGS, SCHEDULE OUTAGES OR INTERRUPTIONS WITH THE

OWNER, BUILDING OCCUPANTS AND/OR ADJACENT BUILDING OWNER(S) AND OCCUPANTS PRIOR TO CONDUCTING OUTAGE(S) OR INTERRUPTIONS.

13. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ONLY. DO NOT SCALE THE

ELECTRICAL DRAWINGS TO DETERMINE THE LOCATION OF EQUIPMENT OR OUTLETS. SEE ARCHITECTURAL PLANS, WHERE PROVIDED ON PROJECT, FOR EXTENT OF DEMOLITION.

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

DEMO FLOOR PLAN
& RCP BLDG A
A1.01
MD
MONROE ST. POOL REPLACEMENT

DEMO FLOOR PLAN & RCP BLDG A
1/8" = 1' -0"
04 / A1.03 DEMO FLOOR BLDG A 04
1/8" = 1' -0"
04 / A1.03 RCP DEMO BLDG A 11

KEYNOTE LEGEND

02.01 EXISTING CARPET TO BE REMOVED, PREP CONCRETE F OR NEW

FLOORING FINISH

02.02 EXISTING FLOORING FINISH TO BE DEMOLISHED

02.04 EXISTING COUNTERTOP AND FIXTURES TO BE DEMOLIS HED

02.05 EXISTING SHOWERS TO BE DEMOLISHED

02.06 EXISTING TOILETS, URINALS AND TOILET PARTITION TO BE

DEMOLISHED

02.07 EXISTING WALL MOUNTED LAVATORY TO BE DEMOLISHE D

02.08 EXISTING COLUMN TO REMAIN, PROTECT IN PLACE

02.11 EXISTING LOCKERS TO BE DEMOLISHED

02.12 EXISTING SHOWER BENCH TO BE DEMOLISHED

02.13 EXISTING STOREFRONT AND DOOR TO BE DEMOLISHED

02.15 EXISTING CASEWORK TO BE DEMOLISHED

02.16 EXISTING RECEPTION DESK TO BE DEMOLISHED

02.17 EXISTING SUSPENDED CEILING AND GRID TO BE DEMO LISHED

02.18 EXISTING DRINKING FOUNTAIN TO BE DEMOLISHED

02.20 EXISTING LIGHTING TO BE DEMOLISHED

02.21 EXISTING GYP CEILING TO BE DEMOLISHED

02.22 EXISTING WATER HEATER TO BE DEMOLISHED

02.23 EXISTING ROOF ACCESS LADDER AND HATCH TO BE DE MOLISHED

02.28 EXISTING SLAB TO BE DEMO'D FOR NEW PLUMBING

02.29 EXISTING SKYLIGHT TO BE REMOVED. INFILL WITH JOISTS AND PLYWOOD SHEATHING.

02.36 EXISTING AV CABINET - REMOVE AND RETURN TO BUI LDING OWNER.

02.37 EXISTING WALL MOUNTED TV, REMOVE AND RETURN TO OWNER

KEYPLAN
A
B
13 203
08/09/2024

DEMOLITION GENERAL NOTES

1. THE EXISTING CONDITIONS SHOWN ARE FROM AVAILABLE RECORD DRAWINGS AND SHOWN FOR REFERENCE ONLY. CONTRACTOR SHALL VERIFY ACTUAL EXISTING CONDITIONS AT SITE PRIOR TO SUBMITTING BID. ALL DEMOLITION, ALTERATION,

EXTENSION, RELOCATION, REHABILITATION WORK SHALL BE INCLUDED IN CONTRACT. NO ADDITIONAL ALLOWANCE OR CHANGE ORDERS WILL BE ACCEPTED.

2. CONTRACTOR IS RESPONSIBLE TO RELOCATE OR REMOVE FROM WALLS, CEILINGS, FLOOR SPACES, ETC. ANY EXISTING CONDUITS, WIRES, BOXES, FITTINGS,

FIXTURES OR OTHER ELECTRICAL EQUIPMENT WHICH INTERFERES WITH PLANNED REMODEL WORK. PROVIDE CIRCUIT CONTINUATION REQUIRED FOR ALL EXISTING OUTLETS, FIXTURES, EQUIPMENT, ETC. SCHEDULED TO REMAIN.

3. NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY WHEREVER EXISTING EQUIPMENT

IS ENCOUNTERED WHICH MUST BE RELOCATED DUE TO THE NEW CONSTRUCTION, OR NOT INDICATED ON "AS -BUILT" DRAWINGS OR WAS BURIED UNDERGROUND OR EMBEDDED IN STRUCTURE WALLS.

4. CAREFULLY PROTECT ALL WALLS, TRIM, FLOORS, EQUIPMENT, UTILITY LINES AND MATERIALS. WHEN WORKING ON FINISHED SURFACES, LIMIT DAMAGE TO THE

SMALLER AREA IF POSSIBLE AND RESTORE TO THE ORIGINAL CONDITION ALL SURFACES WHICH ARE DAMAGED BECAUSE OF THE INSTALLATION OF THIS WORK.

5. EQUIPMENT, MATERIALS AND SUPPLIES TEMPORARILY REMOVED FOR PROTECTION SHALL BE REPLACED IN ORIGINAL LOCATIONS. ANY MATERIALS DAMAGED SHALL

BE REPLACED WITH NEW MATERIALS OF LIKE KIND AND QUALITY

6. DEMOLITION WORK SHALL BE DONE IN A MANNER WHICH WILL NOT CAUSE

UNNECESSARY INCONVENIENCE OR DANGER TO USERS OF THE PREMISES AND ADJACENT SITE, AND NOT INTERFERE WITH ITS OPERATION. ANY DEMOLITION WORK TO BE PERFORMED MUST BE PLANNED IN ADVANCE.

7. DO ALL DRILLING, CUTTING, ETC. REQUIRED TO DEMOLISH ELECTRICAL WORK AS

INDICATED OR PROVIDE BLANK COVER PLATE ON ALL OUTLETS EXPOSED BY REMOVAL OF FIXTURE OF DEVICES.

8. RESEAL ALL PENETRATIONS OR OPENING THROUGH WALLS, CEILING, FLOORS, ETC., TO MAINTAIN THE RATING OF STRUCTURE.

9. CONTRACTOR SHALL VERIFY EXISTING CONDUIT/CONDUCTOR RUNS ON CIVIL DEMOLITION PLAN, SHEET C1.1. REUSE AS REQUIRED AND REMOVE ALL UNUSED CONDUIT/CONDUCTORS. REMOVE CONDUIT BACK TO SCOPE OF WORK LIMIT LINE.

AT EACH END OF FEEDER, TAG AND LABEL CONDUIT. DOCUMENT DETAILED DIMENSIONS ON AS -BUILTS. REMOVE CONDUCTORS BACK TO SOURCE (VERIFY WITH OWNER). UNUSED CONDUIT IN INACCESSIBLE LOCATIONS (WALLS TO REMAIN) CAN BE ABANDONED IN PLACE.

10. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDUIT/WIRING RUNS, REUSE AS REQUIRE AND REMOVED ALL UNUSED CONDUIT/WIRING. UNUSED CONDUIT IN INACCESSIBLE LOCATIONS (WALLS TO REMAIN) CAN BE ABANDONED IN PLACE.

REMOVE UNUSED WIRING.

11. CONTRACTOR TO VERIFY CIRCUIT NUMBER AND LOADS FOR ALL EXISTING

EQUIPMENT PRIOR TO INSTALLATION OF NEW OR RELOCATED ELECTRICAL EQUIPMENT. REASSIGN CIRCUITS AND LOADS ACCORDINGLY. PROVIDE COMPLETE "AS BUILT" DRAWINGS AND TYPEWRITTEN DIRECTORIES FOR PANELS.

12. WHERE NECESSARY TO SHUT OFF UTILITY SERVICES OR CAUSE INTERRUPTION TO

POWER OR SIGNAL SYSTEMS WHILE A BUILDING IS OCCUPIED OR THAT EFFECT

ADJACENT BUILDINGS, SCHEDULE OUTAGES OR INTERRUPTIONS WITH THE

OWNER, BUILDING OCCUPANTS AND/OR ADJACENT BUILDING OWNER(S) AND OCCUPANTS PRIOR TO CONDUCTING OUTAGE(S) OR INTERRUPTIONS.

13. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ONLY. DO NOT SCALE THE

ELECTRICAL DRAWINGS TO DETERMINE THE LOCATION OF EQUIPMENT OR OUTLETS. SEE ARCHITECTURAL PLANS, WHERE PROVIDED ON PROJECT, FOR EXTENT OF DEMOLITION.
1 A
2 BC
3 4
D

02.29 02.23 02.29

02.29 02.29

02.24 02.41

02.29 02.29

02.29 02.29
LEGEND

EXISTING ROOF DRAIN, TO REMAIN

EXISTING SKYLIGHT TO BE REMOVED AND INFILLED
AND/OR UTILIZED USED BY MECHANICAL; SEE

MECHANICAL

ROOF ASSEMBLY TO BE

DEMOLISHED

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

DEMO ROOF PLAN -
BLDG A
A1.02
MD
MONROE ST. POOL REPLACEMENT

DEMO ROOF PLAN - BLDG A

KEYNOTE LEGEND

02.23 EXISTING ROOF ACCESS LADDER AND HATCH TO BE DE MOLISHED

02.24 EXISTING MANSARD ROOF TO BE DEMOLISHED

02.29 EXISTING SKYLIGHT TO BE REMOVED. INFILL WITH JOISTS AND PLYWOOD SHEATHING.

02.41 EXISTING ROOF SOFFIT FRAMING TO BE DEMOLISHED

KEYPLAN
A
B
1/8" = 1' -0"
A1.02 04 DEMO ROOF PLAN
14 203
08/09/2024

01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
A

TOP OF BLOCK WING

WALLS - BLDG A
17'-2"
B C D

02.25 02.26
01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
1 TOP OF BLOCK WING

WALLS - BLDG A
17'-2"
234

02.26 02.46

02.33 02.33 02.38 02.39 02.39
01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
1 TOP OF BLOCK WING

WALLS - BLDG A
17'-2"
2 3 4

02.24 TYP.

02.25 TYP.

02.25 02.13
TYP.

02.14 02.41
01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
A

TOP OF BLOCK WING

WALLS - BLDG A
17'-2"
BCD

02.13 02.25

02.41 DEMOLITION GENERAL NOTES

1. THE EXISTING CONDITIONS SHOWN ARE FROM AVAILABLE RECORD DRAWINGS AND SHOWN FOR REFERENCE ONLY. CONTRACTOR SHALL VERIFY ACTUAL EXISTING CONDITIONS AT SITE PRIOR TO SUBMITTING BID. ALL DEMOLITION, ALTERATION,

EXTENSION, RELOCATION, REHABILITATION WORK SHALL BE INCLUDED IN CONTRACT. NO ADDITIONAL ALLOWANCE OR CHANGE ORDERS WILL BE ACCEPTED.

2. CONTRACTOR IS RESPONSIBLE TO RELOCATE OR REMOVE FROM WALLS, CEILINGS, FLOOR SPACES, ETC. ANY EXISTING CONDUITS, WIRES, BOXES, FITTINGS,

FIXTURES OR OTHER ELECTRICAL EQUIPMENT WHICH INTERFERES WITH PLANNED REMODEL WORK. PROVIDE CIRCUIT CONTINUATION REQUIRED FOR ALL EXISTING OUTLETS, FIXTURES, EQUIPMENT, ETC. SCHEDULED TO REMAIN.

3. NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY WHEREVER EXISTING EQUIPMENT

IS ENCOUNTERED WHICH MUST BE RELOCATED DUE TO THE NEW CONSTRUCTION, OR NOT INDICATED ON "AS -BUILT" DRAWINGS OR WAS BURIED UNDERGROUND OR EMBEDDED IN STRUCTURE WALLS.

4. CAREFULLY PROTECT ALL WALLS, TRIM, FLOORS, EQUIPMENT, UTILITY LINES AND MATERIALS. WHEN WORKING ON FINISHED SURFACES, LIMIT DAMAGE TO THE

SMALLER AREA IF POSSIBLE AND RESTORE TO THE ORIGINAL CONDITION ALL SURFACES WHICH ARE DAMAGED BECAUSE OF THE INSTALLATION OF THIS WORK.

5. EQUIPMENT, MATERIALS AND SUPPLIES TEMPORARILY REMOVED FOR PROTECTION SHALL BE REPLACED IN ORIGINAL LOCATIONS. ANY MATERIALS DAMAGED SHALL

BE REPLACED WITH NEW MATERIALS OF LIKE KIND AND QUALITY

6. DEMOLITION WORK SHALL BE DONE IN A MANNER WHICH WILL NOT CAUSE

UNNECESSARY INCONVENIENCE OR DANGER TO USERS OF THE PREMISES AND ADJACENT SITE, AND NOT INTERFERE WITH ITS OPERATION. ANY DEMOLITION WORK TO BE PERFORMED MUST BE PLANNED IN ADVANCE.

7. DO ALL DRILLING, CUTTING, ETC. REQUIRED TO DEMOLISH ELECTRICAL WORK AS

INDICATED OR PROVIDE BLANK COVER PLATE ON ALL OUTLETS EXPOSED BY REMOVAL OF FIXTURE OF DEVICES.

8. RESEAL ALL PENETRATIONS OR OPENING THROUGH WALLS, CEILING, FLOORS, ETC., TO MAINTAIN THE RATING OF STRUCTURE.

9. CONTRACTOR SHALL VERIFY EXISTING CONDUIT/CONDUCTOR RUNS ON CIVIL DEMOLITION PLAN, SHEET C1.1. REUSE AS REQUIRED AND REMOVE ALL UNUSED CONDUIT/CONDUCTORS. REMOVE CONDUIT BACK TO SCOPE OF WORK LIMIT LINE.

AT EACH END OF FEEDER, TAG AND LABEL CONDUIT. DOCUMENT DETAILED DIMENSIONS ON AS -BUILTS. REMOVE CONDUCTORS BACK TO SOURCE (VERIFY WITH OWNER). UNUSED CONDUIT IN INACCESSIBLE LOCATIONS (WALLS TO REMAIN) CAN BE ABANDONED IN PLACE.

10. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDUIT/WIRING RUNS, REUSE AS REQUIRE AND REMOVED ALL UNUSED CONDUIT/WIRING. UNUSED CONDUIT IN INACCESSIBLE LOCATIONS (WALLS TO REMAIN) CAN BE ABANDONED IN PLACE.

REMOVE UNUSED WIRING.

11. CONTRACTOR TO VERIFY CIRCUIT NUMBER AND LOADS FOR ALL EXISTING

EQUIPMENT PRIOR TO INSTALLATION OF NEW OR RELOCATED ELECTRICAL EQUIPMENT. REASSIGN CIRCUITS AND LOADS ACCORDINGLY. PROVIDE COMPLETE "AS BUILT" DRAWINGS AND TYPEWRITTEN DIRECTORIES FOR PANELS.

12. WHERE NECESSARY TO SHUT OFF UTILITY SERVICES OR CAUSE INTERRUPTION TO

POWER OR SIGNAL SYSTEMS WHILE A BUILDING IS OCCUPIED OR THAT EFFECT

ADJACENT BUILDINGS, SCHEDULE OUTAGES OR INTERRUPTIONS WITH THE

OWNER, BUILDING OCCUPANTS AND/OR ADJACENT BUILDING OWNER(S) AND OCCUPANTS PRIOR TO CONDUCTING OUTAGE(S) OR INTERRUPTIONS.

13. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ONLY. DO NOT SCALE THE

ELECTRICAL DRAWINGS TO DETERMINE THE LOCATION OF EQUIPMENT OR OUTLETS. SEE ARCHITECTURAL PLANS, WHERE PROVIDED ON PROJECT, FOR EXTENT OF DEMOLITION.

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

DEMO ELEVATIONS
BLDG A
A1.03
MD
MONROE ST. POOL REPLACEMENT

DEMO ELEVATIONS BLDG A
1/8" = 1' -0"
A1.03 15 EXT ELEVATION - NORTH DEMO
1/8" = 1' -0"
A1.03 05 EXT ELEVATION - EAST DEMO
1/8" = 1' -0"
A1.03 11 EXT ELEVATION - WEST DEMO
1/8" = 1' -0"
A1.03 04 EXT ELEVATION - SOUTH DEMO

KEYNOTE LEGEND

02.13 EXISTING STOREFRONT AND DOOR TO BE DEMOLISHED

02.14 EXISTING LOUVERS TO BE DEMOLISHED

02.24 EXISTING MANSARD ROOF TO BE DEMOLISHED

02.25 EXISTING PLASTER ON CMU WALL TO BE REMOVED AND BLOCK

SANDBLASTED

02.26 EXISTING DOOR IN CMU TO BE DEMOLISHED

02.33 EXISTING SCREEN, FRAME TO BE REMOVED, OPENING TO BE INFILLED, REF:

02.38 EXISTING WINDOW AND FRAME TO BE DEMOLISHED AND INFILLED, REF:

02.39 EXISTING WINDOW AND FRAME TO BE DEMOLISHED

02.41 EXISTING ROOF SOFFIT FRAMING TO BE DEMOLISHED

02.46 EXISTING HI-LOW ACCESSIBLE DRINKING FOUNTAIN T O BE REMOVED.

KEYPLAN
A
B

EXISTING SECTION DRAWINGS FOR REFERENCE ONLY (NOT TO SCALE)

02.24 02.24 02.41
15 203
08/09/2024

LEGEND
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.01.

STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.01.

METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION

CMU WALL CONSTRUCTION

GLAZING SYSTEM

LINE OF ELEMENT ABOVE

HATCH INDICATES NEW BUILT -IN CASEWORK

EXISTING STUD WALLS

1. CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS AND REPORT ALL DISCREPANCIES TO ARCHITECT.

2. EXTERIOR WALL DIMENSIONS ARE TO FACE OF STRUCTURAL SHEATHING, U.N.O. INTERIOR WALL DIMENSIONS ARE TO FACE OF STUD, U.N.O. VERIFY ANY DISCREPANCIES IN THE FIELD WITH THE ARCHITECT PRIOR TO BUILDING.

3. ALL GYPSUM BOARD EXPOSED TO VIEW SHALL HAVE LEVEL #4 FINISH, U.N.O.

4. FURRING AT COLUMNS, ROOF DRAINS, PIPES AND SIMILAR ELEMENTS TO BE HELD AS TIGHT TO OBSTRUCTION AS POSSIBLE, U.N.O.

5. AT ALL WET WALL LOCATIONS INCLUDING TOILET ROOMS, PROVIDE MOISTURE

RESISTANT GYPSUM BOARD AT EXPOSED AREAS AND CEMENTITIOUS BACKER BOARD BEHIND TILE.

6. PROVIDE THERMAL BATT INSULATION AT ALL ROOF ASSEMBLIES. R40 MIN. AT ROOF.

7. LOCATE DOOR FRAME 6" MIN. FROM ADJACENT WALL FRAMING, TYP. DOOR FRAMES ARE TO BE LOCATED 6" FROM ADJACENT WALL FRAMING, U.N.O.

8. SLAB PLANS INDICATE WHICH WALLS REQUIRE CURBS. REFER TO WALL TYPES AND DETAILS FOR CURB WIDTHS.

9. REFER TO INTERIOR ELEVATIONS FOR QUANTITY, LOCATION, AND DIMENSIONS OF WHITEBOARDS. COORDINATE AND PROVIDE BACKING AS REQUIRED.

GENERAL NOTES
FINISH SCHEDULE: REFER TO A6.31

FIRE EXTINGUISHER CABINET, WALL
MOUNTED. REF: 12/A9.11
FEC

EXISTING CMU WALLS
1 A
A3.01 13
A3.01
05 A3.01
06 A3.01 12
06 A3.11
13 A3.11
2 BC
3 4
D
LOBBY
01 STAFF
LOUNGE
03 MULTI

PURPOSE
ROOM
14 TELEPHONE
15 STAFF
RR
03A
STAFF
SHOWER
03B
ADMIN
07 OFFICE
07A

WOMEN'S

CHANGING/

LOCKERS
10 WOMEN'S

RESTROOM
09 WOMEN'S
SHOWER
11 CORRIDOR
08 CORRIDOR
02 MEN'S

RESTROOM
04 MEN'S

CHANGING/

LOCKERS
05 MEN'S
SHOWER
06 STORAGE
04A
04 A3.11

STORAGE
09A
11'-0"

08.05 ELEC.
14A

22.01 10.01
05 A3.11
09 A3.11
A4.03
06 A4.04
06 A4.02
06 A4.01
06 A4.02
05 A4.01
13 4A
4A
5D
5D
3A
3A
102 103
104
106
107
109A
109
108
111A
111
108A
110
105
1A
SA6
SA6
MA8
SB6
FIRST
AID
16 EQUIPMENT

STORAGE
17 EXTERIOR

STORAGE
18 A3.01 04
FEC
FEC
101
07 A3.21
10 1/2"
9'-10 1/8"
(E)12'-8"
112
5D
5D
2A
4'-4"
5'-0" CLR.
18" MIN.
18" MIN. 5'-0" CLR.
5'-0" MIN. CLR.
5'-5"
A4.05
06 6'-2" 13'-6" 13'-6" 6'-5"
8'-4"
SA6 SA6
1" 10'-0"
15'-6" 15'-6" 15'-6" 13'-6"
10"
2'-2" 3'-4" 3'-4" 3'-4" 3'-3" 3'-5" 3'-4" 3'-4" 3'-4" 1'-8" 104A
28'-8"

10.05 11'-4" 22'-0"
9'-8" 8'-0" 4'-8" 7'-4"
11"
4'-8" 35'-0"
4"
7'-4" 2'-8"
5'-4" 12'-7"
4'-6"
5 6
7 F E
POOL
PUMP
ROOM
22 A3.02
A3.02
05 A3.02
11 A3.02 04
06 A3.12
05 A3.12
13 A3.12

ELECTRICAL
21 STORAGE
19 FAMILY

RESTROOM/
SHOWER
20C
12 CORRIDOR/

LOCKERS
20 34'-0"
62'-0"
36'-0" 26'-0"

22.05 11
A3.12
04 A3.12
12 A3.12
A4.06
06 119
113
114A
114B
114C
115
116 117 118
SN6

CHEMICAL
ROOM
24 CHEMICAL
ROOM
25 BACKWASH
22A
PUMP
PIT
22B
SE3
114D
114E
TANK

STORAGE
23 130
114
10'-8" 41'-6" 9'-3"
2'-4" 9'-1" 7'-8" 5'-10" 8'-6"
9'-1" 9'-1" 5'-1"
4'-0" 4'-8"
8'-10"
5'-2" 14'-8"
2'-4"
CLR.
2'-10"

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. T he
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

FIRST FLOOR PLAN
- BLDG A & B
A2.01
MD
MONROE ST. POOL REPLACEMENT

FIRST FLOOR PLAN - BLDG A & B

KEYNOTE LEGEND

08.05 NEW STOREFRONT GLAZING WITH FRITTED GLASS AND LOUVERS

AT UPPER SECTION

10.01 CUSTOM DIGITALLY PRINTED GRAPHIC ON VINYL WALL COVERING

10.05 SHADE STRUCTURE: SEE SHADE CONSULTANT SHEETS. SHADE CANOPY ENGINEERING IS A DEFERRED SUBMITTAL.

22.01 NEW WATER HEATER

22.05 NEW HI-LOW ACCESSIBLE DRINKING FOUNTAIN/ BOTTL E FILLING

STATION
1/8" = 1' -0"
A2.01 04 FLOOR PLAN - BLDG A
1/8" = 1' -0"
A2.01 11 FLOOR PLAN - BLDG B

KEYPLAN
A
B
203
16 08/09/2024

WP
WP
F F
M
M M
M
M
M
M
M
M
WP
WP

LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED

LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED

LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED M
M
WP
OS
OS
OS
WP
WP
M
M M
M
J
M
M
J
J
J
M
1 A
2 BC
3 4
D

05.03 08.03

05.01 1/4"/12"
1/4"/12"
1/4"/12"
1/4"/12"
1/4"/12"
3/8"/12"
3/8"/12"
3/8"/12"
3/8"/12"
1/4"/12"
9'-4 1/8"
9'-7 167/256"
07 A3.21
TYP.

23.02 TYP.

23.01 TYP.

23.03 TYP.

23.01 TYP.

23.01 TYP.

23.01 TYP.

02.42 TYP.

02.42 TYP.

02.42 TYP.

02.42 TYP.

23.06 10.04

07.05 10.05
5 6
7 F E

08.03 07.02

10.03 6'-2"
8'-3"
3/8" / 1'-0"
3/8" / 1'-0"
1/4" / 1'-0"
1/4" / 1'-0"
3/8"/12" 3/8"/12" 3/8"/12" 3/8"/12"
31'-0 3/4"
16'-4 3/8"
11'-5 41/64"
11'-0 1/8"
11'-11 25/32" 11'-5 41/64"
13'-0"
11'-5 41/64"
11'-11 25/32"
11'-0 1/8"
11'-5 41/64"
1/4" / 1'-0"
3/8" / 1'-0"
TYP.

23.01 TYP.

23.03 23.02
3'-3"
3'-3"

1. BACKGROUND DRAWINGS ARE BASED ON ORIGINAL CONSTRUCTION DOCUMENTS, NOT AS -BUILT DRAWINGS. PLEASE VERIFY ALL CONDITIONS AND DIMENSIONS PRIOR TO CONSTRUCTION. REPORT AN DISCREPANCIES TO THE ARCHITECT.

2. EXISTING CONDITIONS DAMAGED OR REMOVED AS A RESULT OF ALL WORK

REQUIRED TO BE DONE UNDER THIS CONTRACT SHALL BE REPAIRED OR

REPLACED TO ORIGINAL CONDITION AND FINISHED TO MATCH ADJACENT SURFACES WITHOUT ADDITIONAL COST TO THE OWNER.

3. CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS AND REPORT ALL DISCREPANCIES TO THE DESIGNER.

4. ROOFING MATERIAL TO HAVE A CLASS A FIRE CLASSIFICATION, PER CIT Y OF

CARLSBAD

GENERAL NOTES
LEGEND

ROOF DRAIN AND OVERFLOW DRAIN, REFER TO

PLUMBING DRAWINGS

EV PANEL - SOLAR THERMAL -

WITH HSS STRUCTURAL GRID

SUPPORT, PER
1/2" COVER BOARD OVER TAPERED RIGID
INSULATION CRICKET, SLOPED TO DRAIN, 1/4" MIN.

AT VALLEY; RE: 10/A8.21
XX" / XX" ROOF SLOPE

MECHICANICAL EQUIPMENT PER MECH DRAWINGS

EXISTING ROOF DRAIN

EXISTING WALL

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

ROOF PLAN - BLDG
A & B
A2.09
MD
MONROE ST. POOL REPLACEMENT

ROOF PLAN - BLDG A & B

KEYNOTE LEGEND

02.42 EXISTING ROOF DRAIN

05.01 NEW ROOF ACCESS LADDER, 13/A8.22

05.03 NEW MECHANICAL SCREEN SYSTEM

07.02 ROOF CRICKET / TAPERED INSULATION SLOPED TO DR AIN

07.05 ROOF TO WALL JOINT TRANSITION. FULL LENGTH OF WALL AT NEW ADDITION. CONSTRUCTION SPECIALTIES SC-800 JOINT. SEE
04/A8.21.

08.03 NEW ROOF HATCH

10.03 PV - PHOTOVOLTAIC PANELS, PER ELECTRICAL DRAWI NGS,

STRUCTURAL SUPPORT PER STRUCTURAL DRAWINGS

10.04 FALL PROTECTION TIEBACK ANCHOR, PER S6.12/5

10.05 SHADE STRUCTURE: SEE SHADE CONSULTANT SHEETS. SHADE CANOPY ENGINEERING IS A DEFERRED SUBMITTAL.

23.01 ROOF EXHAUST, PER MECHANICAL DRAWINGS

23.02 MECHANICAL DUCTING, PER MECHANICAL DRAWINGS

23.03 ROOF VENT PER MECHANICAL DRAWINGS

23.06 MECHANICAL PIPING PER MECHANICAL DRAWINGS
1/8" = 1' -0"
A2.09 04 BLDG A - ROOF PLAN
1/8" = 1' -0"
A2.09 11 BLDG B - ROOF PLAN

KEYPLAN
A
B
17 203
08/09/2024

5 6
7 F E
8'-5 1/8" 8'-5 1/8"
14'-11 1/4"
8'-10 1/4"
8'-2 5/8"
14'-0 1/2"
-2'-2 3/8" -2'-2 3/8"
-2'-2 3/8"
-7'-2 3/8"
-2'-2 3/8"
-2'-2 3/8"
-0'-4 5/8"
4'-5 3/4" 9'-6"
25'-4 3/4"
32'-8 3/4"
6'-4"
14'-8"
13'-5"
2'-0" 10'-0" 10'-4"
3'-9" 8'-0" 6'-6" 4'-2"
2'-9" 2'-9"
4'-3"
4'-11"
2'-0" 1'-9" 6'-8" 1'-6" 6'-9"
2'-9" 3'-2"
-1'-10 3/8"
-1'-10 3/8"
-1'-10 3/8"
4'-8"
8'-8"
4'-6"
1 A
2 B
3 4
D

03.01 03.01

02.31 03.01
-0'-4 5/8"

02.43 0'-0"
0'-0"
0'-0"
0'-0"
0'-0"
9'-4 3/4"
21'-4 5/8" 10'-8 5/8"
38'-4 3/8"
5'-6" 7'-5"
7'-0"
7'-4"
11'-6"
5'-6" 8'-11" 6'-2" 6'-10"
7'-4"
11'-6"
7'-9"
5'-6"
3'-11"
6'-2" 13'-6" 13'-6" 6'-5"
1'-0"

10.05 LEGEND

GENERAL NOTES
6" HIGH CONCRETE CURB, U.N.O.
4" HIGH EQUIPMENT PAD, COORDINATE FINAL SIZE

OF PAD WITH EQUIPMENT PER STRUCTURAL

1. SLAB PLANS INDICATE WHICH WALLS REQUIRE CURBS. CURB WIDTH TO MATCH WALL TYPE DETAILS, U.N.U. REFER TO PARTITION LAYOUT ON FLOOR PLANS AND DETAILS.

2. EDGE OF SLAB ALIGNS TO FACE OF CMU WALLS.

3. ALL SPOT ELEVATIONS ARE RELATIVE TO F.F. SEE SHEETS C5 AND C6 GRADING PLANS FOR FINISH FLOOR LEVELS AT SLAB ON GRADE.

4. SEE CIVIL SHEETS C5 AND C6 GRADING PLANS FOR SITE PAVING ELEVATIONS.

5. SEE LANDSCAPE SHEETS FOR PAVING LAYOUT.

6. DIMENSIONS OF FLOOR DRAIN LOCATIONS ARE TAKEN FROM CENTERLINE OF DRAIN U.N.O.

7. MEDIUM SANDBLAST FINISH AT EXTERIOR CURBS AT EXPOSED FACES.

8. CONTRACTOR TO COORDINATE EDGE OF SLAB PLANS WITH STRUCTURAL FOUNDATION AND FRAMING PLANS.

9. CONTRACTOR SHALL COORDINATE BLOCKOUTS IN CONCRETE CURBS FOR PLUMBING FIXTURES.

10. CONTRACTOR SHALL CONFIRM ALL EQUIPMENT PLATFORM / HOUSEKEEPING

PAD DIMENSION REQUIREMENTS AND SHAFT OPENINGS WITH MANUFACTURER

REQUIREMENTS, MECHANICAL DRAWINGS, AND REVIEWED SUBMITTALS AND ADJUST ACCORDINATLY.

CONCRETE SLAB ON GRADE

DEPRESSED CONCRETE SLAB, DEPTH OF

DEPRESSION AS INDICATED ON PLAN

SPOT ELEVATION

SLOPE DIRECTION - SLOPE TO
BE 2% MAX PER CBC 11B -403.3

NEW CMU WALL CONSTRUCTION

EXISTING CMU WALLS

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

FIRST FLOOR EDGE

OF SLAB PLAN -

BLDG A & B
A2.11
MD
MONROE ST. POOL REPLACEMENT

FIRST FLOOR EDGE OF SLAB PLAN - BLDG A & B

KEYNOTE LEGEND

02.31 EXISTING CONCRETE SLAB ON GRADE

02.43 EXISTING CONCRETE SLAB

03.01 NEW CONCRETE SLAB PER STRUCTURAL

10.05 SHADE STRUCTURE: SEE SHADE CONSULTANT SHEETS. SHADE CANOPY ENGINEERING IS A DEFERRED SUBMITTAL.
1/8" = 1' -0"
A2.11 11 FIRST FLOOR EDGE OF SLAB PLAN - BLDG B
1/8" = 1' -0"
A2.11 04 FIRST FLOOR EDGE OF SLAB PLAN - BLDG A

KEYPLAN
A
B
18 203
08/09/2024

1 A
2 BC
3 4
D
LOBBY
01 STAFF
LOUNGE
03 MULTI

PURPOSE
ROOM
14 TELEPHONE
15 ADMIN
07 OFFICE
07A
STAFF
SHOWER
03B
STAFF
RR
03A

WOMEN'S

CHANGING/

LOCKERS
10 MEN'S

RESTROOM
04 STORAGE
09A

WOMEN'S
SHOWER
11 WOMEN'S

RESTROOM
09 MEN'S
SHOWER
06 MEN'S

CHANGING/

LOCKERS
05 CORRIDOR
08 CORRIDOR
02 STORAGE
04A
ELEC.
14A

EXTERIOR

STORAGE
18 FIRST
AID
16 EQUIPMENT

STORAGE
17 CPT 1 CPT 1
T2
T2
B1
P1
B1
P1
P3 P3
P3
B2
P1
P3 B2
P1
P1
P1
P1
A4.01
13 A4.01
06 A4.03
06 A4.02
06 A4.04
06 P1
CONC-1
A4.02
05 CONC -1
CONC -1
5 6
7 F E
POOL
PUMP
ROOM
22 ELECTRICAL
21 STORAGE
19 CORRIDOR/

LOCKERS
20 FAMILY

RESTROOM/
SHOWER
20C
FAMILY

RESTROOM/
SHOWER
20D
FAMILY

RESTROOM/
SHOWER
20A
FAMILY

RESTROOM/
SHOWER
20B

CHEMICAL
ROOM
24 CHEMICAL
ROOM
25 BACKWASH
22A
PUMP
PIT
22B
CONC-1
CONC-1 CONC-1
CONC-1
CONC-1
T2
A4.06
06 LEGEND

GENERAL NOTES

ALIGN FINISHES

WALL ACCENT FINISH TAG

FINISH TAG

NEW BUILT-IN CASEWORK

1. TYPICAL FINISHES TO BE (P -1) AND (B -1) THROUGHOUT U.N.O.

2. FOR TYPICAL WALL BASE DETAILS REF: 07/A9.12

3. ALL EXPOSED CEILINGS, INCLUDING BEAMS, JOISTS, PLYWOOD SHEATHING, MECHANICAL SYSTEMS, SPRINKLERS, ELECTRICAL TO BE PAINTED, U.N.O.

REFER TO REFLECTED CEILING PLANS A2.31 FOR ADDITIONAL INFORMATION.

4. PAINT ALL ACCESS PANELS TO MATCH THE SURFACE THEY OCCUR ON, TYP.

5. TYPICAL FLOOR COVERING TRANSITIONS IS AT THE CENTERLINE OF THE DOOR

OR AT THE CENTERLINE OF THE OPENING WHERE NO DOOR IS PRESENT, U.N.O. PROVIDE FLUSH TRANSITIONS AS MUCH AS POSSIBLE, REF: 01/A9.12

6. "LOW SHEEN" PAINT FINISH TYPICAL THROUGHOUT, "SEMI -GLOSS" FINISH AT ALL RESTROOMS AND OTHER WET LOCATIONS, "FLAT" FINISH AT ALL CEILINGS WHERE CEILING OCCURS.

7. REFER TO INTERIOR ELEVATIONS FOR CABINET FINISHES.

8. REFER TO INTERIOR ELEVATIONS FOR ADDITIONAL WALL FINISHES.

9. FURNITURE NOT IN SCOPE.

10. ALL PLYWOOD AND WOOD BLOCKING SHALL BE FIRE TREATED PER TYPE V -B.

FLOORING TRANSITION, SEE 01/A9.12
XX
XX
*REFERENCE FINISH SCHEDULE ON SHEET A6.31

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

FIRST FLOOR

FINISHES PLAN -

BLDG A & B
A2.21
MD
MONROE ST. POOL REPLACEMENT

FIRST FLOOR FINISHES PLAN - BLDG A & B
1/8" = 1' -0"
A2.21 04 FIRST FLOOR FINISHES PLAN - BLDG A

KEYNOTE LEGEND
1/8" = 1' -0"
A2.21 11 FIRST FLOOR FINISHES PLAN - BLDG B

KEYPLAN
A
B
19 203
08/09/2024

WP
WP
F F
M
M
M

LED LED LED LED LED
OS
OS
OS OS
OS
OS
OS
OS
OS OS
OS
OS
OS
M M
M
M
M
M
M
M
WP
WP
J
J
J J
OS
OS
OS
OS
OS
OS
OS
OS

LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED

LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED

LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED J

LED LED LED

LED LED LED LED LED LED LED LED LED LED LED LED LED

LED LED LED LED LED LED LED LED

LED LED LED LED LED LED LED LED LED LED LED LED LED
M
M

LED LED LED LED LED LED LED LED LED LED LED LED LED LED

RDCL RDCL
WP
OS
OS
OS
OS
WP
WP
M
M M
M
J
M
M
J
J
J
M
1 A
06 A3.11
13 A3.11
2 BC
3 4
D
04 A3.11

09.02 09.02

09.02 09.02
LOBBY
01 MULTI

PURPOSE
ROOM
14 STAFF
RR
03A
STAFF
SHOWER
03B

WOMEN'S

CHANGING/

LOCKERS
10 WOMEN'S

RESTROOM
09 CORRIDOR
08 CORRIDOR
02 STORAGE
04A

STORAGE
09A
ELEC.
14A
05 A3.11
09 A3.11
A4.03
10 A4.04
13 A4.05
10 A4.01
19 8' - 6"
GYP-1
8' - 6"
ACT-1
8' - 6"
ACT-1
8' - 6"
GYP-1
O.T.S
TYP.

26.07 TYP.

26.04 8' - 6"
ACT-1

26.06 TYP.

26.05 TYP.

26.08 MEN'S

CHANGING/

LOCKERS
05 STAFF
LOUNGE
03 8' - 6"
ACT-1
O.T.S.

TYP.

26.03 MEN'S
SHOWER
06 MEN'S

RESTROOM
04 TYP.

26.02 FIRST
AID
16 O.T.S

EQUIPMENT

STORAGE
17 26.06

EXTERIOR

STORAGE
18 10.05
5 6
7 F E
06 A3.12
13 A3.12
TYP.

09.02 11
A3.12
04 A3.12
12 A3.12
A4.06
12 O.T.S.

O.T.S.

O.T.S.
8' - 0"
GYP-1
8' - 0"
GYP-1
8' - 0"
GYP-1
TYP.

26.07 TYP.

26.02 TYP.

26.02 TYP.

26.07 LEGEND

GENERAL NOTES
GYP -1

FRAMED GYPSUM BOARD CEILING
SEE DETAILS ON A9 SERIES
ACT -1
2'X4' ACOUSTIC CEILING TILE
DUNE TEGUALR, 9/16" SILHOUETTE GRID
SEE DETAILS ON A9 SERIES
GYP -3

FRAMED MOISTURE -RESISTANT GYP BD CEILING,
SEE DETAILS ON A9 SERIES

EXIT SIGN

CEILING TYPE

CEIILING ACCESS PANEL

1. ALL GYPSUM BOARD CEILINGS AND SOFFITS TO BE PAIN TED (P-1), U.N.O.

2. ALL EXPOSED CEILINGS, INCLUDING BEAMS, JOISTS, M ECHANICAL SYSTEMS, SPRINKLERS, ELECTRICAL TO BE PAINTED, U.N.O. SEE RECLECTED CEILING PLANS ADDITIONAL INFORMATION.

3. ALL GYPSUM BOARD EXPOSED TO VIEW SHALL HAVE LEVE L #4 FINISH, U.N.O.

4. PROVIDE ACCESS PANELS IN ENCLOSED AREAS ABOVE GY PSUM BOARD CEILINGS. PAINT TO MATCH CEILING FINISH, U.N.O.

5. SINGLE LIGHT FIXTURES TO BE CENTERED IN THE ROOM OR SOFFIT, U.N.O.

6. FOR FIXTURE INFORMATION, REFER TO ELECTRICAL DRA WINGS.

7. ALL LIGHT FIXTURE DIMENSIONS ARE TO CENTERLINE O F FIXTURE, OR GROUP OF FIXTURES, U.N.O.

8. CONTRACTOR TO COORDINATE DUCTS, CONDUIT, FINAL LOCATIONS AND HEIGHTS.

9. ALL PLYWOOD AND WOOD BLOCKING SHALL BE FIRE TREA TED PER TYPE V-B CONSTRUCTION.

10. ALL WALL AND CEILING FINISHES SHALL COMPLY WITH TABLE 803.13 CBC 2022, FOR THE MAXIMUM FLAME SPREAD AND SMOKE DENSITY.

11. CEILINGS SHALL BE INSTALLED TO MEET THE MINIMUM ASCE 7-16 SECTION 13.5.6

INDICATES OPEN TO
STRUCTURE CEILING.

PAINT (P -1) U.N.O.

O.T.S.

OCCUPANCY SENSOR
WiFi ACCESS POINT
X
X' -X" CEILING HEIGHT, SEE PLAN
OS WAP

J JUNCTION BOX,

PER ELECTRICAL

DRAWINGS

MECHANICAL

EXHAUST GRILLES

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

FIRST FLOOR

REFLECTED

CEILING PLAN -

BLDG A & B
A2.31
MD
MONROE ST. POOL REPLACEMENT

FIRST FLOOR REFLECTED CEILING PLAN - BLDG A & B
1/8" = 1' -0"
A2.31 04 REFLECTED CEILING PLAN - BLDG A

KEYNOTE LEGEND

09.02 NEW GYP CEILING WITH NEW LIGHTING

10.05 SHADE STRUCTURE: SEE SHADE CONSULTANT SHEETS. SHADE CANOPY ENGINEERING IS A DEFERRED SUBMITTAL.

26.02 RECESSED SQUARE DOWNLIGHT, PER ELECTRICAL DRAW INGS

26.03 RECESSED LINEAR LIGHT FIXTURE, PER ELECTRICAL DRAWINGS

26.04 2'X2' RECESSED BASKET LIGHT FIXTURE, PER ELEC TRICAL

DRAWINGS

26.05 LED TAPE, PER ELECTRICAL DRAWINGS

26.06 PENDANT LINEAR LIGHT FIXTURE, PER ELECTRICAL D RAWINGS

26.07 PENDANT STRIP LIGHT FIXTURE, PER ELECTRICAL DR AWINGS

26.08 SURFACE MOUNTED LINEAR WALL WASH LIGHT FIXTURE , PER

ELECTRICAL DRAWINGS
1/8" = 1' -0"
A2.31 11 REFLECTED CEILING PLAN - BLDG B

KEYPLAN
A
B
20 203
08/09/2024
203
01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
1 TOP OF BLOCK WING

WALLS - BLDG A
17'-2"
06 A3.11
13 A3.11
2 3 4

05.03 03.03

08.06 EQ EQ EQ EQ
04 A8.12
14 A8.12
14 A8.12
9'-10"
01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
A

TOP OF BLOCK WING

WALLS - BLDG A
17'-2"
BCD 04
A3.11

08.06 05
A3.11
09 A3.11
07 A3.21

04.01 03
A8.12
02 A8.12
05 A8.12
04 A8.12
10 L5.12
01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
A

TOP OF BLOCK WING

WALLS - BLDG A
17'-2"
B C D04
A3.11
05 A3.11
09 A3.11
07 A3.21

04.01 04
A8.12
TYP.
05 A8.12
08 A8.12
10 A8.12
01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
1 TOP OF BLOCK WING

WALLS - BLDG A
17'-2"
06 A3.11
13 A3.11
234

05.03 22.05 08.02
04 A8.12
TYP.
9'-6"
08 A8.12
10 A8.12
09 A8.12 TYP.
05 A9.42
05 A9.42
TYP.
40"
TYP.
78"
TYP.
28"
26" 32"
22"
01 A8.12
04 A8.12
02 A8.12
03 A8.12
08 A8.12
02 A8.12
03 A8.12
04 L5.12
01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
06 A3.11
234
T4
T3

08.08 02.46 08.01 08.01 08.08

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

EXTERIOR

ELEVATIONS - BLDG
A
A3.01
MD
MONROE ST. POOL REPLACEMENT

EXTERIOR ELEVATIONS - BLDG A
1/8" = 1' -0"
A3.01 13 EXT ELEVATION - EAST
1/8" = 1' -0"
A3.01 05 EXT ELEVATION - SOUTH
1/8" = 1' -0"
A3.01 06 EXT ELEVATION - NORTH
1/8" = 1' -0"
A3.01 12 EXT ELEVATION - OVERALL WEST

KEYNOTE LEGEND

02.46 EXISTING HI-LOW ACCESSIBLE DRINKING FOUNTAIN T O BE REMOVED.

03.03 NEW CMU WALLS TO MATCH EXISTING CMU CONSTRUCTI ON

04.01 EXISTING CMU, CLEANED, PATCHED, AND PAINTED

05.03 NEW MECHANICAL SCREEN SYSTEM

08.01 NEW HM WINDOW IN DEMOLISHED DOOR OPENING

08.02 NEW HM WINDOW IN NEW CMU WALL

08.06 NEW STOREFRONT GLAZING

08.08 NEW HM WINDOW IN EXISTING OPENING

22.05 NEW HI-LOW ACCESSIBLE DRINKING FOUNTAIN/ BOTTL E FILLING

STATION
1/8" = 1' -0"
A3.01 04 EXT ELEVATION - UPPER WEST
21 203
08/09/2024
203
FE 05
A3.12

TOP BLDG B
13'-0"
04 A3.12
01 - 206.30 - BLDG B
-2'-2 3/8"
2'-0"
17'-2"
F E05
A3.12

TOP BLDG B
13'-0"
04 A3.12
01 - 207.93
-0'-4 5/8"
2'-0"
567 06
A3.12
13 A3.12

TOP BLDG B
13'-0"

22.05 11
A3.12
12 A3.12
01 - 206.30 - BLDG B
-2'-2 3/8"
01 - 207.93
-0'-4 5/8"
2'-0"
5'-4"
4'-8"
17'-2"
5 6 706
A3.12
13 A3.12

TOP BLDG B
13'-0"
11 A3.12
12 A3.12
01 - 207.93
-0'-4 5/8"
2'-0"

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

EXTERIOR

ELEVATIONS - BLDG
B
A3.02
MD
MONROE ST. POOL REPLACEMENT

EXTERIOR ELEVATIONS - BLDG B

KEYNOTE LEGEND

22.05 NEW HI-LOW ACCESSIBLE DRINKING FOUNTAIN/ BOTTL E FILLING

STATION
1/8" = 1' -0"
A3.02 05 ELEVATION - NORTH
1/8" = 1' -0"
A3.02 11 ELEVATION - SOUTH
1/8" = 1' -0"
A3.02 04 ELEVATION - WEST
1/8" = 1' -0"
A3.02 12 ELEVATION - EAST
22 203
08/09/2024
203
01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
A B C D04
A3.11
A3.20
14 A3.23
11 05
A3.11
07 A3.21
LOBBY
01 CIRCULATION
01A
ADMIN
07 OFFICE
07A

TOP OF BLOCK EAST -
BLDG A
10'-6"
01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
B C D04
A3.11
A3.20
04 A3.20
11 09
A3.11
A3.20
08 WOMEN'S

RESTROOM
09 WOMEN'S

CHANGING/

LOCKERS
10 FIRST
AID
16 TOP OF BLOCK EAST -
BLDG A
10'-6"
01 - FLOOR
0'-0"
1 TOP OF BLOCK WING

WALLS - BLDG A
17'-2"
06 A3.11
13 A3.11
2 3 4
A3.24
2 01 - 207.93
-0'-4 5/8"

WOMEN'S

RESTROOM
09 EXTERIOR

STORAGE
18 CORRIDOR
08 ADMIN
07 STAFF
SHOWER
03B
STAFF
RR
03A
MEN'S

RESTROOM
04 TOP OF BLOCK EAST -
BLDG A
10'-6"
A3.22
11 Sim
01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
06 A3.11
23 A3.21
04 A3.21
11 LOBBY
01 TOP OF BLOCK EAST -
BLDG A
10'-6"
01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
1 13
A3.11
A3.22
04 A3.24
1 FIRST
AID
16 EQUIPMENT

STORAGE
17 EXTERIOR

STORAGE
18 TOP OF BLOCK EAST -
BLDG A
10'-6"

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

BUILDING

SECTIONS BLDG A
A3.11
MD
MONROE ST. POOL REPLACEMENT

BUILDING SECTIONS BLDG A
1/8" = 1' -0"
A3.11 06 EAST-WEST SECTION - BUILDING A
1/8" = 1' -0"
A3.11 13 EAST-WEST SECTION 2 - BUILDING A
1/8" = 1' -0"
A3.11 04 NORTH-SOUTH SECTION - BUILDING A
1/8" = 1' -0"
A3.11 05 NORTH-SOUTH SECTION - BLDG A
LOBBY
1/8" = 1' -0"
A3.11 09 NORTH-SOUTH SECTION - BLDG A

STORAGE
23 203
08/09/2024
203
F E05
A3.12

TOP BLDG B
13'-0"
04 A3.12 A3.26
05 A3.26
14 A3.26
11 01 - 207.93
-0'-4 5/8"

CORRIDOR/

LOCKERS
20 ELECTRICAL
21 5 6 706
A3.12
13 A3.12

TOP BLDG B
13'-0"
12 A3.12
01 - 206.30 - BLDG B
-2'-2 3/8"
01 - 207.93
-0'-4 5/8"
A3.26
04 FAMILY

RESTROOM/
SHOWER
20E

CORRIDOR/

LOCKERS
20 FAMILY

RESTROOM/
SHOWER
20B
POOL
PUMP
ROOM
22 F E05
A3.12

TOP BLDG B
13'-0"
04 A3.12
01 - 207.93
-0'-4 5/8"

ELECTRICAL
21 FAMILY

RESTROOM/
SHOWER
20C
FAMILY

RESTROOM/
SHOWER
20B
FAMILY

RESTROOM/
SHOWER
20A
5 6 706
A3.12
13 A3.12

TOP BLDG B
13'-0"
11 A3.12
12 A3.12
8'-0"
01 - 206.30 - BLDG B
-2'-2 3/8"
01 - 207.93
-0'-4 5/8"
8'-6"
FAMILY

RESTROOM/
SHOWER
20A
FAMILY

RESTROOM/
SHOWER
20D
POOL
PUMP
ROOM
22 F E
05 A3.12

TOP BLDG B
13'-0"
04 A3.12 A3.27
11 A3.27
04 01 - 206.30 - BLDG B
-2'-2 3/8"
POOL
PUMP
ROOM
22 FE 05
A3.12

TOP BLDG B
13'-0"
04 A3.12
01 - 206.30 - BLDG B
-2'-2 3/8"

CHEMICAL
ROOM
25 CHEMICAL
ROOM
24 POOL
PUMP
ROOM
22 ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

BUILDING

SECTIONS BLDG B
A3.12
MD
MONROE ST. POOL REPLACEMENT

BUILDING SECTIONS BLDG B
1/8" = 1' -0"
A3.12 06 WEST-EAST SECTION - BUILDING B
1/8" = 1' -0"
A3.12 05 NORTH-SOUTH SECTION - BUILDING B
1/8" = 1' -0"
A3.12 13 WEST-EAST SECTION 2 - BUILDING B
1/8" = 1' -0"
A3.12 04 NORTH-SOUTH SECTION 2 - BUILDING B
1/8" = 1' -0"
A3.12 12 WEST-EAST SECTION 3 - BUILDING B
1/8" = 1' -0"
A3.12 11 EAST-WEST SECTION - BUILDING B
24 203
08/09/2024
203
01 - FLOOR
0'-0"
D
A8.14
08 A8.14
03 A8.12
08 A8.12
10 03.01

03.03 07.03

05.04 08.02
FIRST
AID
16 TOP OF BLOCK EAST -
BLDG A
10'-6"
A8.22
05 A8.22
06 2'-8" 4'-8" 2" 3'-0"
A8.13
02 GENERAL NOTES

1. REFER TO FLOOR PLANS FOR OPENING DIMENSIONS AND LOCATIONS.

2. FOR VERTICAL CMU CONTROL & EXPANSION JOINT DETAILS, REF: 15/A8.13

3. STOREFRONT, AND DOOR FINISH TYPES AND COLORS PER OPENING TYPE SHEETS AND DOOR SCHEDULE AND.

4. PAINT ALL ELECTRICAL AND TECHNOLOGY DEVICES TO MATCH COLOR OF ADJACENT SURFACES. DO NOT PAINT FIRE ALARM DEVICES AND RECESSED HOSE BIBBS.

5. FOR EXTERIOR WALL PIPE PENETRATIONS AT CMU WALLS, SEE 04/A8.13.

6. SEE A9.0X SERIES FOR WALL TYPES
01 - FLOOR
0'-0"
B

03.01 04.01

07.03 02.45

WOMEN'S

RESTROOM
09 A8.22
14 TOP OF BLOCK EAST -
BLDG A
10'-6"
SIM. OPP.

05.03 (V.I.F.)
+/- 3'-9"
01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
C

03.01 03.01

04.01 03.03

07.03 02.45

07.03 FIRST
AID
16 WOMEN'S

CHANGING/

LOCKERS
10 A8.22
14 TOP OF BLOCK EAST -
BLDG A
10'-6"

05.03 (V.I.F.)
+/- 4'-4 1/4"
A8.22
06 A8.22
05 A8.13
02 SIM. OPP.

07.05 01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
A
8'-6"
A8.12
16 A8.12
15 A8.13
11 A8.22
02 02.31

02.44 08.06

05.09 LOBBY
01 05.04

02.45 4'-0"

EXISTING HEAVY TIMBER BEAM

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

WALL SECTIONS
A3.20
MD
MONROE ST. POOL REPLACEMENT

WALL SECTIONS

KEYNOTE LEGEND

02.31 EXISTING CONCRETE SLAB ON GRADE

02.44 EXISTING CMU

02.45 EXISTING ROOF STRUCTURE

03.01 NEW CONCRETE SLAB PER STRUCTURAL

03.03 NEW CMU WALLS TO MATCH EXISTING CMU CONSTRUCTI ON

04.01 EXISTING CMU, CLEANED, PATCHED, AND PAINTED

05.03 NEW MECHANICAL SCREEN SYSTEM

05.04 PERFORATED METAL SCREEN WITH GRAPHIC INCORPORA TED INTO DESIGN, IMAGE TBD BY ARCHITECT.

05.09 STEEL FRAMED, COMPOSITE ALUMINUM PANEL ENTRY P ORTAL

07.03 SINGLE PLY ROOFING SYSTEM

07.05 ROOF TO WALL JOINT TRANSITION. FULL LENGTH OF WALL AT NEW ADDITION. CONSTRUCTION SPECIALTIES SC-800 JOINT. SEE
04/A8.21.

08.02 NEW HM WINDOW IN NEW CMU WALL

08.06 NEW STOREFRONT GLAZING
1" = 1' -0"
A3.20 04 WALL SECTION THROUGH NEW

ADDITON - BUILDING A
1" = 1' -0"
A3.20 11 WALL SECTION THROUGH

BUILDING A RESTROOM
1" = 1' -0"
A3.20 08 WALL SECTION THROUGH NEW

ADDITION & EXISTING - BUILDING A
1" = 1' -0"
A3.20 14 EAST-WEST SECTION - BUILDING A
25 203
08/09/2024
203

GENERAL NOTES

1. REFER TO FLOOR PLANS FOR OPENING DIMENSIONS AND LOCATIONS.

2. FOR VERTICAL CMU CONTROL & EXPANSION JOINT DETAILS, REF: 15/A8.13

3. STOREFRONT, AND DOOR FINISH TYPES AND COLORS PER OPENING TYPE SHEETS AND DOOR SCHEDULE AND.

4. PAINT ALL ELECTRICAL AND TECHNOLOGY DEVICES TO MATCH COLOR OF ADJACENT SURFACES. DO NOT PAINT FIRE ALARM DEVICES AND RECESSED HOSE BIBBS.

5. FOR EXTERIOR WALL PIPE PENETRATIONS AT CMU WALLS, SEE 04/A8.13.

6. SEE A9.0X SERIES FOR WALL TYPES
01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
2 A8.14
11 A8.12
10 A8.12
09 A8.12
08 A8.22
02 LOBBY
01 02.43

08.06 05.04

EXISTING HEAVY

TIMBER BEAM
BEYOND
A8.22
02 SIM.

SIM.

06.01 07.03 07.03
A8.12
06 01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
3 A8.12
08 A8.12
09 A8.12
10 SIM. OPP.

SIM. OPP.

SIM. OPP.

02.31 05.04
A8.22
02 LOBBY
01 A8.12
10 EXISTING

HEAVY TIMBER

BEAM BEYOND
4'-0" 9" 8'-10" 3"
SIM.

SIM.

A8.22
02 SIM.

02.45 07.03 06.01

07.03 01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
2 A8.12
08 A8.12
09 A8.12
10 05.04

02.45 07.03

04.01 A8.22
03 A8.22
02 ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

WALL SECTIONS
A3.21
MD
MONROE ST. POOL REPLACEMENT

WALL SECTIONS

KEYNOTE LEGEND

02.31 EXISTING CONCRETE SLAB ON GRADE

02.43 EXISTING CONCRETE SLAB

02.45 EXISTING ROOF STRUCTURE

04.01 EXISTING CMU, CLEANED, PATCHED, AND PAINTED

05.04 PERFORATED METAL SCREEN WITH GRAPHIC INCORPORA TED INTO DESIGN, IMAGE TBD BY ARCHITECT.

06.01 WOOD FRAMING; SEE STRUCTURAL DET. 8/S6.81

07.03 SINGLE PLY ROOFING SYSTEM

08.06 NEW STOREFRONT GLAZING
1" = 1' -0"
A3.21 04 WALL SECTION THROUGH LOBBY -

BUILDING A
1" = 1' -0"
A3.21 11 WALL SECTION THROUGH LOBBY 3
- BUILDING A
1" = 1' -0"
A3.21 07 WALL SECTION THROUGH LOBBY 2
- BUILDING A
26 203
08/09/2024
203

GENERAL NOTES

1. REFER TO FLOOR PLANS FOR OPENING DIMENSIONS AND LOCATIONS.

2. FOR VERTICAL CMU CONTROL & EXPANSION JOINT DETAILS, REF: 15/A8.13

3. STOREFRONT, AND DOOR FINISH TYPES AND COLORS PER OPENING TYPE SHEETS AND DOOR SCHEDULE AND.

4. PAINT ALL ELECTRICAL AND TECHNOLOGY DEVICES TO MATCH COLOR OF ADJACENT SURFACES. DO NOT PAINT FIRE ALARM DEVICES AND RECESSED HOSE BIBBS.

5. FOR EXTERIOR WALL PIPE PENETRATIONS AT CMU WALLS, SEE 04/A8.13.

6. SEE A9.0X SERIES FOR WALL TYPES
01 - FLOOR
0'-0"
A8.14
03 A8.14
08 03.01

03.03 07.03 07.03
FIRST
AID
16 TOP OF BLOCK EAST -
BLDG A
10'-6"
3'-2" 4'-8" 2'-8"
A8.22
06 A8.22
05 01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
01 - 207.93
-0'-4 5/8"

02.31 03.01

04.01 MULTI

PURPOSE
ROOM
14 OPP.

A9.11
1 ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

WALL SECTIONS
A3.22
MD
MONROE ST. POOL REPLACEMENT

WALL SECTIONS

KEYNOTE LEGEND

02.31 EXISTING CONCRETE SLAB ON GRADE

03.01 NEW CONCRETE SLAB PER STRUCTURAL

03.03 NEW CMU WALLS TO MATCH EXISTING CMU CONSTRUCTI ON

04.01 EXISTING CMU, CLEANED, PATCHED, AND PAINTED

07.03 SINGLE PLY ROOFING SYSTEM
1" = 1' -0"
A3.22 04 WALL SECTION THROUGH NEW

ADDITION - BUILDING A
1" = 1' -0"
A3.22 11 WALL SECTION THROUGH MPR -

BUILDING A
27 203
08/09/2024
203

GENERAL NOTES

1. REFER TO FLOOR PLANS FOR OPENING DIMENSIONS AND LOCATIONS.

2. FOR VERTICAL CMU CONTROL & EXPANSION JOINT DETAILS, REF: 15/A8.13

3. STOREFRONT, AND DOOR FINISH TYPES AND COLORS PER OPENING TYPE SHEETS AND DOOR SCHEDULE AND.

4. PAINT ALL ELECTRICAL AND TECHNOLOGY DEVICES TO MATCH COLOR OF ADJACENT SURFACES. DO NOT PAINT FIRE ALARM DEVICES AND RECESSED HOSE BIBBS.

5. FOR EXTERIOR WALL PIPE PENETRATIONS AT CMU WALLS, SEE 04/A8.13.

6. SEE A9.0X SERIES FOR WALL TYPES
01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
D
0'-4"
A8.12
08 A8.12
10 05.06

TOP OF BLOCK EAST -
BLDG A
10'-6"
01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
C D
A8.12
08 A8.12
10 05.03

TOP OF BLOCK EAST -
BLDG A
10'-6"
01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
C

03.01 04.01

05.06 05.03

07.03 02.45 TOP OF BLOCK EAST -
BLDG A
10'-6"

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

WALL SECTIONS
A3.23
MD
MONROE ST. POOL REPLACEMENT

WALL SECTIONS

KEYNOTE LEGEND

02.45 EXISTING ROOF STRUCTURE

03.01 NEW CONCRETE SLAB PER STRUCTURAL

04.01 EXISTING CMU, CLEANED, PATCHED, AND PAINTED

05.03 NEW MECHANICAL SCREEN SYSTEM

05.06 STEEL FRAMED OVERHANG/ SUNSHADE

07.03 SINGLE PLY ROOFING SYSTEM
1" = 1' -0"
A3.23 11 EAST-WEST SECTION - BUILDING A
- Callout 2
1" = 1' -0"
A3.23 04 Section 11
1" = 1' -0"
A3.23 14 Section 10
28 203
08/09/2024
203

GENERAL NOTES

1. REFER TO FLOOR PLANS FOR OPENING DIMENSIONS AND LOCATIONS.

2. FOR VERTICAL CMU CONTROL & EXPANSION JOINT DETAILS, REF: 15/A8.13

3. STOREFRONT, AND DOOR FINISH TYPES AND COLORS PER OPENING TYPE SHEETS AND DOOR SCHEDULE AND.

4. PAINT ALL ELECTRICAL AND TECHNOLOGY DEVICES TO MATCH COLOR OF ADJACENT SURFACES. DO NOT PAINT FIRE ALARM DEVICES AND RECESSED HOSE BIBBS.

5. FOR EXTERIOR WALL PIPE PENETRATIONS AT CMU WALLS, SEE 04/A8.13.

6. SEE A9.0X SERIES FOR WALL TYPES
01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
1 EQUIPMENT

STORAGE
17 03.03

03.01 07.03 TOP OF BLOCK EAST -
BLDG A
10'-6"
01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
1 WOMEN'S

RESTROOM
09 EXTERIOR

STORAGE
18 03.01

03.03 04.01

02.45 07.03 TOP OF BLOCK EAST -
BLDG A
10'-6"
9'-10"

10.05 ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

WALL SECTIONS
A3.24
MD
MONROE ST. POOL REPLACEMENT

WALL SECTIONS

KEYNOTE LEGEND

02.45 EXISTING ROOF STRUCTURE

03.01 NEW CONCRETE SLAB PER STRUCTURAL

03.03 NEW CMU WALLS TO MATCH EXISTING CMU CONSTRUCTI ON

04.01 EXISTING CMU, CLEANED, PATCHED, AND PAINTED

07.03 SINGLE PLY ROOFING SYSTEM

10.05 SHADE STRUCTURE: SEE SHADE CONSULTANT SHEETS. SHADE CANOPY ENGINEERING IS A DEFERRED SUBMITTAL.
1/2" = 1' -0"
A3.24 1WALL SECTION THROUGH NEW OPEN AIR STORAGE - BUILDING A 1/2" = 1' -0"
A3.24 2WALL SECTION THROUGH NEW OPEN AIR STORAGE 2 - BUILDING A 29 203
08/09/2024
203

GENERAL NOTES

1. REFER TO FLOOR PLANS FOR OPENING DIMENSIONS AND LOCATIONS.

2. FOR VERTICAL CMU CONTROL & EXPANSION JOINT DETAILS, REF: 15/A8.13

3. STOREFRONT, AND DOOR FINISH TYPES AND COLORS PER OPENING TYPE SHEETS AND DOOR SCHEDULE AND.

4. PAINT ALL ELECTRICAL AND TECHNOLOGY DEVICES TO MATCH COLOR OF ADJACENT SURFACES. DO NOT PAINT FIRE ALARM DEVICES AND RECESSED HOSE BIBBS.

5. FOR EXTERIOR WALL PIPE PENETRATIONS AT CMU WALLS, SEE 04/A8.13.

6. SEE A9.0X SERIES FOR WALL TYPES TOP OF BLOCK - BLDG A 9'-10"
E

TOP BLDG B
13'-0"
01 - 207.93
-0'-4 5/8"

03.01 03.03

05.03 07.03

ELECTRICAL
21 TOP OF BLOCK EAST -
BLDG A
10'-6"
F

TOP BLDG B
13'-0"
01 - 207.93
-0'-4 5/8"
A8.14
06 A8.14
15 CORRIDOR/

LOCKERS
20 03.01

05.03 07.03

TOP OF BLOCK EAST -
BLDG A
10'-6"

TOP OF BLOCK - BLDG A
9'-10"
01 - 207.93
-0'-4 5/8"

03.01 07.03

CORRIDOR/

LOCKERS
20 TOP OF BLOCK EAST -
BLDG A
10'-6"
01 - FLOOR
0'-0"

TOP OF BLOCK - BLDG A
9'-10"
01 - 206.30 - BLDG B
-2'-2 3/8"
01 - 207.93
-0'-4 5/8"
POOL
PUMP
ROOM
22 TOP OF BLOCK EAST -
BLDG A
10'-6"

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

WALL SECTIONS
A3.26
MD
MONROE ST. POOL REPLACEMENT

WALL SECTIONS

KEYNOTE LEGEND

03.01 NEW CONCRETE SLAB PER STRUCTURAL

03.03 NEW CMU WALLS TO MATCH EXISTING CMU CONSTRUCTI ON

05.03 NEW MECHANICAL SCREEN SYSTEM

07.03 SINGLE PLY ROOFING SYSTEM
1" = 1' -0"
A3.26 05 WALL SECTION THROUGH

WEST-EAST - BUILDING B
1" = 1' -0"
A3.26 14 WEST-EAST SECTION - BUILDING B
- Callout 2
1" = 1' -0"
A3.26 11 WALL SECTION THROUGH

LOCKERS - BUILDING B
1" = 1' -0"
A3.26 04 NORTH-SOUTH SECTION -
BUILDING B - Callout 3
30 08/09/2024
203
203

GENERAL NOTES

1. REFER TO FLOOR PLANS FOR OPENING DIMENSIONS AND LOCATIONS.

2. FOR VERTICAL CMU CONTROL & EXPANSION JOINT DETAILS, REF: 15/A8.13

3. STOREFRONT, AND DOOR FINISH TYPES AND COLORS PER OPENING TYPE SHEETS AND DOOR SCHEDULE AND.

4. PAINT ALL ELECTRICAL AND TECHNOLOGY DEVICES TO MATCH COLOR OF ADJACENT SURFACES. DO NOT PAINT FIRE ALARM DEVICES AND RECESSED HOSE BIBBS.

5. FOR EXTERIOR WALL PIPE PENETRATIONS AT CMU WALLS, SEE 04/A8.13.

6. SEE A9.0X SERIES FOR WALL TYPES
F

TOP BLDG B
13'-0"
01 - 206.30 - BLDG B
-2'-2 3/8"
A8.21
15 POOL
PUMP
ROOM
22 TOP OF BLOCK EAST -
BLDG A
10'-6"
01 - 206.30 - BLDG B
-2'-2 3/8"

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

WALL SECTIONS
A3.27
MD
MONROE ST. POOL REPLACEMENT

WALL SECTIONS

KEYNOTE LEGEND
3/4" = 1' -0"
A3.27 11 Section 8 - Callout 1
1" = 1' -0"
A3.27 04 Section 8 - Callout 2
31 203
08/09/2024
203
30" X 48"
CLR. FLR.

SPACE
MAX.
2'-10" 2'-2" 2'-2"
T4
PL-1
B1

12.04 F.E.
(3) EQ.
33 155
36 24
302
28 14
26 33
101
14 24
CLR.
16"
PL-1
33 101
18 24

22.00 QTZ-2
P1
B1

06.01 16
A9.21
13 A9.31
C
3 A4.01
04 08
SA6
SF0
SB6
SB6
STAFF
LOUNGE
03 LVT 1
B1
P1
P2
2'-0"

LOCKERS
A
2 B
3 A4.01 05
14 A4.05
LVT 1
LOBBY
01 B1
P1
A8.12
14 5'-0"
101
4'-0" CLR.
9'-1"
2'-0"
ALIGN
4'-10"
A
2 B
3 9' - 0"
ACT-1
8' - 6"
GYP-1
P1
LOBBY
01 16
A9.21
16 A9.21
8' - 6"
GYP-111
A9.21
P2

OPEN TO
BEYOND
P2
23 A9.32
QTZ-1 24
A9.32
QTZ -1
3'-5"
2'-6"

FINISHED EDGE
QTZ -1

FINISHED EDGE
QTZ -1
QTZ-1
QTZ-1

WALL GRAPHIC
B1 1'-0"
WC -1
LEGEND
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.01.

STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.01. REFER TO S0.91 FOR INTERIOR STUD WALL SCHEDULE

LINE OF ELEMENT ABOVE

HATCH INDICATES NEW BUILT -IN CASEWORK

GENERAL NOTES
301
36 33
24 CABINET DESIGN SERIES NUMBERING SYSTEM PER

ARCHITECTURAL WOODWORK STANDARDS

AWI CASEWORK NUMBER

CABINET WIDTH

CABINET HEIGHT

CABINET DEPTH

ALIGN FINISHES
XX
FINISH TAG REF: A6.31 FINISH SCHEDULE
EQUIPMENT TAG 1i

1. FOR FINISH & RESTROOM ACCESSORY SCHEDULES REF: A6.31

2. FOR TYPICAL WALL BASE DETAILS REF: 07/A9.12

3. ALL PLUMBING FIXTURES TO HAVE SOLID BLOCKING AS REQUIRED BY CODE.

4. FOR FIXTURE AND ACCESSORY MOUNTING HEIGHTS, REF: G0.32

5. PROVIDE 5/8" TYPE "X" WATER RESISTANT GYPSUM BOARD AT ALL RESTROOM WALLS NOT RECEIVING TILE. PAINT PER FINISH PLANS

6. PROVIDE CEMENTITIOUS TILE BACKER BOARD AT ALL TILED WALLS, TYP.

7. PROVIDE LOCALIZED SLAB DEPRESSION AT FLOOR DRAINS, REF: 7/A9.41

8. TYPICAL PAINT AT RESTROOMS TO BE "SEMI -GLOSS" FINISH.

9. REFER TO MANUFACTURER'S TOILET ACCESSORY INSTALLATION AND OTHER

MOUNTING INSTRUCTIONS AND PROVIDE WALL BACKING AND OTHER REQUIRED SUPPORT AS INDICATED.

10. REFER TO DETAIL 04/G0.32 FOR ACCESSIBLE STALL INFORMATION. AT ACCESSIBLE STALLS: TOILET PARTITION DOOR WIDTHS ARE TO BE 36" (34" MIN.

CLEAR REG'D) PARTITION STILE WIDTH SHALL NOT EXCEED 4". FLUSH VALVE TO BE LOCATED AT WIDE SIDE OF STALL SPACE.

11. FOR SIGNAGE DETAILS, SEE SHEET A10.01

12. ANY FURNITURE PROVIDED BY OWNER SHALL SHOW 5% OF SEATING WITH WHEELCHAIR ACCESS COMPLYING WITH CBC 11B -802.1.

GYP -1

FRAMED GYPSUM BOARD CEILING

SEE DETAILS ON SHEET A--
ACT -1
2'X4' ACOUSTIC CEILING TILE
DUNE TEGUALR, 9/16" SILHOUETTE GRID

SEE DETAIL ----
GYP -3 FRAMED MOISTURE -RESISTANT GYP BD CEILING,

SEE DETAILS ON SHEET A----

CEILING TYPE X
X' -X" CEILING HEIGHT, SEE PLAN
FINISHED EDGE F.E.

INDICATED ACCESSIBLE LOCKER

METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION

CMU WALL CONSTRUCTION

EXISTING STUD WALLS

EXISTING CMU WALLS
XX
XX

FLOOR FINISH

BASE FINISH

WALL FINISH
*REFERENCE FINISH SCHEDULE ON SHEET A6.31

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. T he
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

ENLARGED PLANS &

INTERIOR

ELEVATIONS
A4.01
MD
MONROE ST. POOL REPLACEMENT

ENLARGED PLANS & INTERIOR ELEVATIONS

KEYNOTE LEGEND

06.01 WOOD FRAMING; SEE STRUCTURAL DET. 8/S6.81

12.04 UNDER COUNTER REFRIGERATOR, OFOI

22.00 DIVISION 22: PLUMBING

23.04 MECHANICAL EQUIPMENT, PER MECHANICAL DRAWINGS

26.03 RECESSED LINEAR LIGHT FIXTURE, PER ELECTRICAL DRAWINGS 1/4" = 1' -0"
A4.01 04 STAFF LOUNGE KITCHEN
1/4" = 1' -0"
A4.01 08 INT ELEVATION - STAFF LOUNGE

STORAGE
1/4" = 1' -0"
A4.01 06 ENLARGED FLOOR PLAN 1- BLDG A
1/4" = 1' -0"
A4.01 13 ENLARGED FLOOR PLAN 2 - BLDG
A
1/4" = 1' -0"
A4.01 19 ENLARGED RCP 2 - BLDG A
1/4" = 1' -0"
A4.01 14 LOBBY RECEPTION
1/4" = 1' -0"
A4.01 05 LOBBY WALL GRAPHIC
1 2nd PLAN CHECK

SUBMITTAL
04/24/24
203
32 08/09/2024
203
BC
4 A4.02 09
SG2
SN6
SF0
SF0
MULTI

PURPOSE
ROOM
14 LVT 1
B1
P1
ELEC.
14A
CONC-1
P2 11
A3.22
5'-6" 5'-7"
1'-3"
2'-10" 2'-11" 2'-2"
QTZ-2QTZ-2
PL-1
PL-1302
27 14
26 12.04
33 155
30 24
33 101
15 24
33 102
24 24
CD
A4.02 08
FIRST
AID
16 LVT 1
B1
P1
P3
2'-10" 1'-8" 2'-2"
PL-1
QTZ-2QTZ-2 PL-1
P1
33 155
30 24
33 101
15 24
33 101
15 24
302
30 14
26 LEGEND
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.01.

STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.01. REFER TO S0.91 FOR INTERIOR STUD WALL SCHEDULE

LINE OF ELEMENT ABOVE

HATCH INDICATES NEW BUILT -IN CASEWORK

GENERAL NOTES
301
36 33
24 CABINET DESIGN SERIES NUMBERING SYSTEM PER

ARCHITECTURAL WOODWORK STANDARDS

AWI CASEWORK NUMBER

CABINET WIDTH

CABINET HEIGHT

CABINET DEPTH

ALIGN FINISHES
XX
FINISH TAG REF: A6.31 FINISH SCHEDULE
EQUIPMENT TAG 1i

1. FOR FINISH & RESTROOM ACCESSORY SCHEDULES REF: A6.31

2. FOR TYPICAL WALL BASE DETAILS REF: 07/A9.12

3. ALL PLUMBING FIXTURES TO HAVE SOLID BLOCKING AS REQUIRED BY CODE.

4. FOR FIXTURE AND ACCESSORY MOUNTING HEIGHTS, REF: G0.32

5. PROVIDE 5/8" TYPE "X" WATER RESISTANT GYPSUM BOARD AT ALL RESTROOM WALLS NOT RECEIVING TILE. PAINT PER FINISH PLANS

6. PROVIDE CEMENTITIOUS TILE BACKER BOARD AT ALL TILED WALLS, TYP.

7. PROVIDE LOCALIZED SLAB DEPRESSION AT FLOOR DRAINS, REF: 7/A9.41

8. TYPICAL PAINT AT RESTROOMS TO BE "SEMI -GLOSS" FINISH.

9. REFER TO MANUFACTURER'S TOILET ACCESSORY INSTALLATION AND OTHER

MOUNTING INSTRUCTIONS AND PROVIDE WALL BACKING AND OTHER REQUIRED SUPPORT AS INDICATED.

10. REFER TO DETAIL 04/G0.32 FOR ACCESSIBLE STALL INFORMATION. AT ACCESSIBLE STALLS: TOILET PARTITION DOOR WIDTHS ARE TO BE 36" (34" MIN.

CLEAR REG'D) PARTITION STILE WIDTH SHALL NOT EXCEED 4". FLUSH VALVE TO BE LOCATED AT WIDE SIDE OF STALL SPACE.

11. FOR SIGNAGE DETAILS, SEE SHEET A10.01

12. ANY FURNITURE PROVIDED BY OWNER SHALL SHOW 5% OF SEATING WITH WHEELCHAIR ACCESS COMPLYING WITH CBC 11B -802.1.

GYP -1

FRAMED GYPSUM BOARD CEILING

SEE DETAILS ON SHEET A--
ACT -1
2'X4' ACOUSTIC CEILING TILE
DUNE TEGUALR, 9/16" SILHOUETTE GRID

SEE DETAIL ----
GYP -3 FRAMED MOISTURE -RESISTANT GYP BD CEILING,

SEE DETAILS ON SHEET A----

CEILING TYPE X
X' -X" CEILING HEIGHT, SEE PLAN
FINISHED EDGE F.E.

INDICATED ACCESSIBLE LOCKER

METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION

CMU WALL CONSTRUCTION

EXISTING STUD WALLS

EXISTING CMU WALLS
XX
XX

FLOOR FINISH

BASE FINISH

WALL FINISH
*REFERENCE FINISH SCHEDULE ON SHEET A6.31

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. T he
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

ENLARGED PLANS &

INTERIOR

ELEVATIONS
A4.02
MD
MONROE ST. POOL REPLACEMENT

ENLARGED PLANS & INTERIOR ELEVATIONS

KEYNOTE LEGEND

12.04 UNDER COUNTER REFRIGERATOR, OFOI

23.02 MECHANICAL DUCTING, PER MECHANICAL DRAWINGS
1/4" = 1' -0"
A4.02 06 ENLARGED FLOOR PLAN 4 - BLDG A
1/4" = 1' -0"
A4.02 09 INT ELEVATION - MPR KITCHEN
1/4" = 1' -0"
A4.02 05 ENLARGED FLOOR PLAN 3 - BLDG
A
1/4" = 1' -0"
A4.02 08 INT ELEVATION - FIRST AID SINK
203
33 08/09/2024
203
BC
A4.03 05
A4.03
16 15
12 19
A4.03 14 08
11 04
09 SE4
SG4
SB6
SB6
SB6
SA6
SA6
SE4
SB6 MEN'S

RESTROOM
04 MEN'S
SHOWER
06 MEN'S

CHANGING/

LOCKERS
05 CORRIDOR
02 STORAGE
04A T1 T5
3'-0" 3'-0" 3'-0" 5'-1" 1'-11"
4'-10" 10" 7'-8" 9'-2"
1'-0" 3'-5" 3'-5" 5'-3" 13'-3" 1'-8"
7'-10" 3'-5" 3'-5" 7'-6"
13'-4" 3'-6"
4'-3" 2'-6" 2'-5" 5'-11" 5'-0"
4'-2" 1'-11"
3'-1" 3'-0" 3'-2" 2'-11"
BC
8' - 6"
GYP-2
6' - 6"
GYP-2
P1
MEN'S

RESTROOM
04 8' - 6"
GYP-1
P1
MEN'S
SHOWER
06 STORAGE
04A
MEN'S

CHANGING/

LOCKERS
05 8' - 6"
GYP-2
11 A9.21
11 A9.21
T4
T5
13 A9.31
10 A9.41
4"
T5 T3
T4
T4
T4
QTZ-1
QQ
1'-6"
4" 4'-0"
T5
T4
T3
T4
4'-0" 4"

QQ QQ QQ
SH-1 SH-1
T3
RR
T5
T4
T4
T3
4" 4'-0"
T4
QTZ-1
10 A9.41
QQ

OPEN TO
BEYOND
T4
T3
T5
QQ T4
T3
T5
SH-1
QQ QQ
4'-0" 4"

QQ QQ SS
SH-1SH-1
T5 T5
?
T4
LL
17 A9.42
2'-10"
40" MAX.

OPEN TO
BEYOND
LL LL
T4 T3
T5
PP
22"
17"
U-1 U-2 U-2
PP II
AA
11 A9.21
T4
T5
II
AA
CC
T3
T4
T5
SS
4" 4'-0"
T4
T5

OPEN TO
BEYOND
U-2
LEGEND
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.01.

STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.01. REFER TO S0.91 FOR INTERIOR STUD WALL SCHEDULE

LINE OF ELEMENT ABOVE

HATCH INDICATES NEW BUILT -IN CASEWORK

GENERAL NOTES
301
36 33
24 CABINET DESIGN SERIES NUMBERING SYSTEM PER

ARCHITECTURAL WOODWORK STANDARDS

AWI CASEWORK NUMBER

CABINET WIDTH

CABINET HEIGHT

CABINET DEPTH

ALIGN FINISHES
XX
FINISH TAG REF: A6.31 FINISH SCHEDULE
EQUIPMENT TAG 1i

1. FOR FINISH & RESTROOM ACCESSORY SCHEDULES REF: A6.31

2. FOR TYPICAL WALL BASE DETAILS REF: 07/A9.12

3. ALL PLUMBING FIXTURES TO HAVE SOLID BLOCKING AS REQUIRED BY CODE.

4. FOR FIXTURE AND ACCESSORY MOUNTING HEIGHTS, REF: G0.32

5. PROVIDE 5/8" TYPE "X" WATER RESISTANT GYPSUM BOARD AT ALL RESTROOM WALLS NOT RECEIVING TILE. PAINT PER FINISH PLANS

6. PROVIDE CEMENTITIOUS TILE BACKER BOARD AT ALL TILED WALLS, TYP.

7. PROVIDE LOCALIZED SLAB DEPRESSION AT FLOOR DRAINS, REF: 7/A9.41

8. TYPICAL PAINT AT RESTROOMS TO BE "SEMI -GLOSS" FINISH.

9. REFER TO MANUFACTURER'S TOILET ACCESSORY INSTALLATION AND OTHER

MOUNTING INSTRUCTIONS AND PROVIDE WALL BACKING AND OTHER REQUIRED SUPPORT AS INDICATED.

10. REFER TO DETAIL 04/G0.32 FOR ACCESSIBLE STALL INFORMATION. AT ACCESSIBLE STALLS: TOILET PARTITION DOOR WIDTHS ARE TO BE 36" (34" MIN.

CLEAR REG'D) PARTITION STILE WIDTH SHALL NOT EXCEED 4". FLUSH VALVE TO BE LOCATED AT WIDE SIDE OF STALL SPACE.

11. FOR SIGNAGE DETAILS, SEE SHEET A10.01

12. ANY FURNITURE PROVIDED BY OWNER SHALL SHOW 5% OF SEATING WITH WHEELCHAIR ACCESS COMPLYING WITH CBC 11B -802.1.

GYP -1

FRAMED GYPSUM BOARD CEILING

SEE DETAILS ON SHEET A--
ACT -1
2'X4' ACOUSTIC CEILING TILE
DUNE TEGUALR, 9/16" SILHOUETTE GRID

SEE DETAIL ----
GYP -3 FRAMED MOISTURE -RESISTANT GYP BD CEILING,

SEE DETAILS ON SHEET A----

CEILING TYPE X
X' -X" CEILING HEIGHT, SEE PLAN
FINISHED EDGE F.E.

INDICATED ACCESSIBLE LOCKER

METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION

CMU WALL CONSTRUCTION

EXISTING STUD WALLS

EXISTING CMU WALLS
XX
XX

FLOOR FINISH

BASE FINISH

WALL FINISH
*REFERENCE FINISH SCHEDULE ON SHEET A6.31

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. T he
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

ENLARGED

RESTROOM PLANS
& ELEVATIONS
A4.03
MD
MONROE ST. POOL REPLACEMENT

ENLARGED RESTROOM PLANS & ELEVATIONS
1/4" = 1' -0"
A4.03 06 MEN'S RESTROOM ENLARGED

FLOOR PLAN - BLDG A
1/4" = 1' -0"
A4.03 10 MEN'S RESTROOM RCP - BLDG A
1/4" = 1' -0"
A4.03 05 MEN'S LOCKERS
1/4" = 1' -0"
A4.03 16 MEN'S SHOWER NORTH
1/4" = 1' -0"
A4.03 19 MEN'S SHOWER EAST
1/4" = 1' -0"
A4.03 12 MEN'S SHOWER SOUTH
1/4" = 1' -0"
A4.03 15 MEN'S SHOWER WEST
1/4" = 1' -0"
A4.03 14 MEN'S RESTROOM SINK
1/4" = 1' -0"
A4.03 08 MEN'S RESTROOM
1/4" = 1' -0"
A4.03 04 MEN'S ADA STALL
1/4" = 1' -0"
A4.03 09 MEN'S CHANGING AREA
1/4" = 1' -0"
A4.03 11 MEN'S RESTROOM EXIT

KEYNOTE LEGEND

23.02 MECHANICAL DUCTING, PER MECHANICAL DRAWINGS

26.08 SURFACE MOUNTED LINEAR WALL WASH LIGHT FIXTURE , PER

ELECTRICAL DRAWINGS
203
34 08/09/2024
203
1 BC
A4.04 04
A4.04
12 A4.04
08 11
14 17
05 09
SB6
SG4
SE4
SB6
SA6
SA6
SE4
SG4

WOMEN'S

CHANGING/

LOCKERS
10 STORAGE
09A

WOMEN'S
SHOWER
11 WOMEN'S

RESTROOM
09 CORRIDOR
08 T1
T5
SB6
SB6
SG4
SE4
SB4
SB4
SB4
SB6
SB6
A4.03 05 Sim
104 104A
5'-1" 3'-0" 3'-0" 3'-0" 1'-11"
1'-3" 3'-5" 3'-5" 5'-1" 13'-5" 1'-4"
4'-10" 10" 7'-8" 9'-2"
6'-4" 4'-3" 4'-11" 5'-6" 5'-2" 1'-4"
4'-6"
3'-5" 4'-2" 3'-5" 3'-5" 7'-10"
3'-0" 3'-0" 3'-0" 3'-7" 4'-10"
3'-9"
1 BC
8' - 6"
GYP-2
6' - 6"
GYP-2
8' - 6"
GYP-1

WOMEN'S

RESTROOM
09 WOMEN'S

CHANGING/

LOCKERS
10 02.19

26.05 11
A9.21
8' - 6"
GYP-2

STORAGE
09A
T4 T5 QTZ-2 17
A9.42
PL -2
T3
T3
LL
3'-4"
2'-10"
4"
11 A9.21
L-1
LL LL
T4
T4
T4 T5 T5
II
AA
T4
4" 4'-0"
T3
T5
AA
T4
T3 T5 CC
T4
T3 T5
RR
SH-1 SH-1
T4
T5
SH-1 QQ
T3
T4

QQ QQ QQ
SH-1SH-1
T3
T4
T5
T4
T3 T5
QQ
LEGEND
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.01.

STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.01. REFER TO S0.91 FOR INTERIOR STUD WALL SCHEDULE

LINE OF ELEMENT ABOVE

HATCH INDICATES NEW BUILT -IN CASEWORK

GENERAL NOTES
301
36 33
24 CABINET DESIGN SERIES NUMBERING SYSTEM PER

ARCHITECTURAL WOODWORK STANDARDS

AWI CASEWORK NUMBER

CABINET WIDTH

CABINET HEIGHT

CABINET DEPTH

ALIGN FINISHES
XX
FINISH TAG REF: A6.31 FINISH SCHEDULE
EQUIPMENT TAG 1i

1. FOR FINISH & RESTROOM ACCESSORY SCHEDULES REF: A6.31

2. FOR TYPICAL WALL BASE DETAILS REF: 07/A9.12

3. ALL PLUMBING FIXTURES TO HAVE SOLID BLOCKING AS REQUIRED BY CODE.

4. FOR FIXTURE AND ACCESSORY MOUNTING HEIGHTS, REF: G0.32

5. PROVIDE 5/8" TYPE "X" WATER RESISTANT GYPSUM BOARD AT ALL RESTROOM WALLS NOT RECEIVING TILE. PAINT PER FINISH PLANS

6. PROVIDE CEMENTITIOUS TILE BACKER BOARD AT ALL TILED WALLS, TYP.

7. PROVIDE LOCALIZED SLAB DEPRESSION AT FLOOR DRAINS, REF: 7/A9.41

8. TYPICAL PAINT AT RESTROOMS TO BE "SEMI -GLOSS" FINISH.

9. REFER TO MANUFACTURER'S TOILET ACCESSORY INSTALLATION AND OTHER

MOUNTING INSTRUCTIONS AND PROVIDE WALL BACKING AND OTHER REQUIRED SUPPORT AS INDICATED.

10. REFER TO DETAIL 04/G0.32 FOR ACCESSIBLE STALL INFORMATION. AT ACCESSIBLE STALLS: TOILET PARTITION DOOR WIDTHS ARE TO BE 36" (34" MIN.

CLEAR REG'D) PARTITION STILE WIDTH SHALL NOT EXCEED 4". FLUSH VALVE TO BE LOCATED AT WIDE SIDE OF STALL SPACE.

11. FOR SIGNAGE DETAILS, SEE SHEET A10.01

12. ANY FURNITURE PROVIDED BY OWNER SHALL SHOW 5% OF SEATING WITH WHEELCHAIR ACCESS COMPLYING WITH CBC 11B -802.1.

GYP -1

FRAMED GYPSUM BOARD CEILING

SEE DETAILS ON SHEET A--
ACT -1
2'X4' ACOUSTIC CEILING TILE
DUNE TEGUALR, 9/16" SILHOUETTE GRID

SEE DETAIL ----
GYP -3 FRAMED MOISTURE -RESISTANT GYP BD CEILING,

SEE DETAILS ON SHEET A----

CEILING TYPE X
X' -X" CEILING HEIGHT, SEE PLAN
FINISHED EDGE F.E.

INDICATED ACCESSIBLE LOCKER

METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION

CMU WALL CONSTRUCTION

EXISTING STUD WALLS

EXISTING CMU WALLS
XX
XX

FLOOR FINISH

BASE FINISH

WALL FINISH
*REFERENCE FINISH SCHEDULE ON SHEET A6.31

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. T he
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

ENLARGED

RESTROOM PLANS
& ELEVATIONS
A4.04
MD
MONROE ST. POOL REPLACEMENT

ENLARGED RESTROOM PLANS & ELEVATIONS
1/4" = 1' -0"
A4.04 06 ENLARGED FLOOR PLAN - WOMENS RESTROOM - BLDG A 1/4" = 1' -0"
A4.04 13 ENLARGED RCP - WOMEN'S RESTROOM - BLDG A
1/4" = 1' -0"
A4.04 04 WOMEN'S RESTROOM SINKS
1/4" = 1' -0"
A4.04 08 TYPICAL STALL
1/4" = 1' -0"
A4.04 11 WOMEN'S RESTROOM STALLS
1/4" = 1' -0"
A4.04 14 WOMEN'S RESTROOM ADA STALL
1/4" = 1' -0"
A4.04 12 WOMEN'S SHOWER SOUTH
1/4" = 1' -0"
A4.04 17 WOMEN'S SHOWER WEST
1/4" = 1' -0"
A4.04 05 WOMEN'S CHANGING ROOMS
1/4" = 1' -0"
A4.04 09 WOMEN'S CHANGING AREA

KEYNOTE LEGEND

02.19 EXISTING SKYLIGHT TO REMAIN, PROTECT IN PLACE

26.05 LED TAPE, PER ELECTRICAL DRAWINGS

26.08 SURFACE MOUNTED LINEAR WALL WASH LIGHT FIXTURE , PER

ELECTRICAL DRAWINGS
203
35 08/09/2024
203
T5
AA
T5
3'-4"
LL
AA
T4
T5
T4
L-2
A4.05 15
05 09
12 A4.05 14
04 08
11 T1
T1
STAFF
SHOWER
03B
STAFF
RR
03A
QTZ-1
7'-6" 3'-3" 5'-6"
1'-6"
11" 3'-10" 3'-1"
6'-10" 1'-0"
T5
T4 T4
T3
T5 QQ
T4
T5
1'-6"
T4
QTZ-110
A9.41
SH-1
RR
4'-0" 4"
T3
T4
T5
8' - 0"
GYP-2
8' - 0"
GYP-2
P1
P1
16 A9.21
11 A9.21
LEGEND
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.01.

STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.01. REFER TO S0.91 FOR INTERIOR STUD WALL SCHEDULE

LINE OF ELEMENT ABOVE

HATCH INDICATES NEW BUILT -IN CASEWORK

GENERAL NOTES
301
36 33
24 CABINET DESIGN SERIES NUMBERING SYSTEM PER

ARCHITECTURAL WOODWORK STANDARDS

AWI CASEWORK NUMBER

CABINET WIDTH

CABINET HEIGHT

CABINET DEPTH

ALIGN FINISHES
XX
FINISH TAG REF: A6.31 FINISH SCHEDULE
EQUIPMENT TAG 1i

1. FOR FINISH & RESTROOM ACCESSORY SCHEDULES REF: A6.31

2. FOR TYPICAL WALL BASE DETAILS REF: 07/A9.12

3. ALL PLUMBING FIXTURES TO HAVE SOLID BLOCKING AS REQUIRED BY CODE.

4. FOR FIXTURE AND ACCESSORY MOUNTING HEIGHTS, REF: G0.32

5. PROVIDE 5/8" TYPE "X" WATER RESISTANT GYPSUM BOARD AT ALL RESTROOM WALLS NOT RECEIVING TILE. PAINT PER FINISH PLANS

6. PROVIDE CEMENTITIOUS TILE BACKER BOARD AT ALL TILED WALLS, TYP.

7. PROVIDE LOCALIZED SLAB DEPRESSION AT FLOOR DRAINS, REF: 7/A9.41

8. TYPICAL PAINT AT RESTROOMS TO BE "SEMI -GLOSS" FINISH.

9. REFER TO MANUFACTURER'S TOILET ACCESSORY INSTALLATION AND OTHER

MOUNTING INSTRUCTIONS AND PROVIDE WALL BACKING AND OTHER REQUIRED SUPPORT AS INDICATED.

10. REFER TO DETAIL 04/G0.32 FOR ACCESSIBLE STALL INFORMATION. AT ACCESSIBLE STALLS: TOILET PARTITION DOOR WIDTHS ARE TO BE 36" (34" MIN.

CLEAR REG'D) PARTITION STILE WIDTH SHALL NOT EXCEED 4". FLUSH VALVE TO BE LOCATED AT WIDE SIDE OF STALL SPACE.

11. FOR SIGNAGE DETAILS, SEE SHEET A10.01

12. ANY FURNITURE PROVIDED BY OWNER SHALL SHOW 5% OF SEATING WITH WHEELCHAIR ACCESS COMPLYING WITH CBC 11B -802.1.

GYP -1

FRAMED GYPSUM BOARD CEILING

SEE DETAILS ON SHEET A--
ACT -1
2'X4' ACOUSTIC CEILING TILE
DUNE TEGUALR, 9/16" SILHOUETTE GRID

SEE DETAIL ----
GYP -3 FRAMED MOISTURE -RESISTANT GYP BD CEILING,

SEE DETAILS ON SHEET A----

CEILING TYPE X
X' -X" CEILING HEIGHT, SEE PLAN
FINISHED EDGE F.E.

INDICATED ACCESSIBLE LOCKER

METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION

CMU WALL CONSTRUCTION

EXISTING STUD WALLS

EXISTING CMU WALLS
XX
XX

FLOOR FINISH

BASE FINISH

WALL FINISH
*REFERENCE FINISH SCHEDULE ON SHEET A6.31

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. T he
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

ENLARGED

RESTROOM PLANS
& ELEVATIONS
A4.05
MD
MONROE ST. POOL REPLACEMENT

ENLARGED RESTROOM PLANS & ELEVATIONS
1/4" = 1' -0"
A4.05 15 INT ELEVATION - STAFF RR WEST
1/4" = 1' -0"
A4.05 05 INT ELEVATION - STAFF RR NORTH
1/4" = 1' -0"
A4.05 09 INT ELEVATION - STAFF RR EAST
1/4" = 1' -0"
A4.05 12 INT ELEVATION - STAFF RR SOUTH
1/4" = 1' -0"
A4.05 06 ENLARGED FLOOR PLAN - STAFF -
BLDG A
1/4" = 1' -0"
A4.05 14 INT ELEVATION - STAFF SHOWER
WEST
1/4" = 1' -0"
A4.05 04 INT ELEVATION - STAFF SHOWER
NORTH
1/4" = 1' -0"
A4.05 08 INT ELEVATION - STAFF SHOWER
EAST
1/4" = 1' -0"
A4.05 11 INT ELEVATION - STAFF SHOWER
SOUTH
1/4" = 1' -0"
A4.05 10 ENLARGED RCP - STAFF - BLDG A

KEYNOTE LEGEND

26.08 SURFACE MOUNTED LINEAR WALL WASH LIGHT FIXTURE , PER

ELECTRICAL DRAWINGS
203
36 08/09/2024
203
5 6
F
A4.06
05 08
11 A4.06 04
A4.06 16
18 14
17 07
10 13
SA4
SG6
SE4
SE4
SB4
SE4
SN6
SG6
SA4 CORRIDOR/

LOCKERS
20 FAMILY

RESTROOM/
SHOWER
20B
FAMILY

RESTROOM/
SHOWER
20C
FAMILY

RESTROOM/
SHOWER
20D

STORAGE
19 ELECTRICAL
21 FAMILY

RESTROOM/
SHOWER
20A
T1
T1 T1
T1
T1
T1
T2
A4.07
04 13
10 07
SA4
SB4
SB4
SA4
SA4
FAMILY

RESTROOM/
SHOWER
20E
INT ELEV:

OPP. RM 20B
INT ELEV:

OPP. RM 20E
SA4
114E
SA4
SA4 SA4
3'-0"
QTZ-1
6'-1" 3'-3" 6'-10"
6'-1" 3'-3"
1'-3" 3'-1" 5'-5" 6'-3" 5'-1" 3'-5" 1'-7"
4'-3" 3'-3" 3'-3" 3'-5"
4'-3" 3'-3" 3'-3" 3'-5" 7'-0" 3'-10"
1'-3" 2'-1" 3'-5" 3'-0" 4'-9" 1'-6"
1'-10"
5 6
F
8' - 6"
GYP-2
8' - 6"
GYP-2
8' - 6"
GYP-2
8' - 6"
GYP-2
8' - 6"
GYP-2
8' - 6"
GYP-2
P1
P1 P1 P1
P1 P1
6' - 2"
GYP-2
T5

10.06 13
A9.31
T5
2'-6"
1'-6"
3'-0"

10.07 TYP.

10.06 10
A9.41
QTZ-1
4'-6"
T5
AA
T4
CC
2'-6"

10.07 T4
T5
T3
RR
4'-0" 4"
T5
RR
LL
3'-4"
T3
T4
4" 4'-0"
T4
T4
T5 T5
4" 4'-0"
QQ
T3
T4
T4
T5
T4
QQ
4'-0" 4"
T5
3'-4"
QQ
LL
T4
T4
T5
LEGEND
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.01.

STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.01. REFER TO S0.91 FOR INTERIOR STUD WALL SCHEDULE

LINE OF ELEMENT ABOVE

HATCH INDICATES NEW BUILT -IN CASEWORK

GENERAL NOTES
301
36 33
24 CABINET DESIGN SERIES NUMBERING SYSTEM PER

ARCHITECTURAL WOODWORK STANDARDS

AWI CASEWORK NUMBER

CABINET WIDTH

CABINET HEIGHT

CABINET DEPTH

ALIGN FINISHES
XX
FINISH TAG REF: A6.31 FINISH SCHEDULE
EQUIPMENT TAG 1i

1. FOR FINISH & RESTROOM ACCESSORY SCHEDULES REF: A6.31

2. FOR TYPICAL WALL BASE DETAILS REF: 07/A9.12

3. ALL PLUMBING FIXTURES TO HAVE SOLID BLOCKING AS REQUIRED BY CODE.

4. FOR FIXTURE AND ACCESSORY MOUNTING HEIGHTS, REF: G0.32

5. PROVIDE 5/8" TYPE "X" WATER RESISTANT GYPSUM BOARD AT ALL RESTROOM WALLS NOT RECEIVING TILE. PAINT PER FINISH PLANS

6. PROVIDE CEMENTITIOUS TILE BACKER BOARD AT ALL TILED WALLS, TYP.

7. PROVIDE LOCALIZED SLAB DEPRESSION AT FLOOR DRAINS, REF: 7/A9.41

8. TYPICAL PAINT AT RESTROOMS TO BE "SEMI -GLOSS" FINISH.

9. REFER TO MANUFACTURER'S TOILET ACCESSORY INSTALLATION AND OTHER

MOUNTING INSTRUCTIONS AND PROVIDE WALL BACKING AND OTHER REQUIRED SUPPORT AS INDICATED.

10. REFER TO DETAIL 04/G0.32 FOR ACCESSIBLE STALL INFORMATION. AT ACCESSIBLE STALLS: TOILET PARTITION DOOR WIDTHS ARE TO BE 36" (34" MIN.

CLEAR REG'D) PARTITION STILE WIDTH SHALL NOT EXCEED 4". FLUSH VALVE TO BE LOCATED AT WIDE SIDE OF STALL SPACE.

11. FOR SIGNAGE DETAILS, SEE SHEET A10.01

12. ANY FURNITURE PROVIDED BY OWNER SHALL SHOW 5% OF SEATING WITH WHEELCHAIR ACCESS COMPLYING WITH CBC 11B -802.1.

GYP -1

FRAMED GYPSUM BOARD CEILING

SEE DETAILS ON SHEET A--
ACT -1
2'X4' ACOUSTIC CEILING TILE
DUNE TEGUALR, 9/16" SILHOUETTE GRID

SEE DETAIL ----
GYP -3 FRAMED MOISTURE -RESISTANT GYP BD CEILING,

SEE DETAILS ON SHEET A----

CEILING TYPE X
X' -X" CEILING HEIGHT, SEE PLAN
FINISHED EDGE F.E.

INDICATED ACCESSIBLE LOCKER

METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION

CMU WALL CONSTRUCTION

EXISTING STUD WALLS

EXISTING CMU WALLS
XX
XX

FLOOR FINISH

BASE FINISH

WALL FINISH
*REFERENCE FINISH SCHEDULE ON SHEET A6.31

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. T he
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

ENLARGED

RESTROOM PLANS
& ELEVATIONS
A4.06
MD
MONROE ST. POOL REPLACEMENT

ENLARGED RESTROOM PLANS & ELEVATIONS
1/4" = 1' -0"
A4.06 06 ENLARGED FLOOR PLAN - FAMILY RESTOOMS - BLDG B 1/4" = 1' -0"
A4.06 12 ENLARGED RCP - FAMILY RESTOOMS - BLDG B
1/4" = 1' -0"
A4.06 05 FAMILY RESTROOMS NORTH
1/4" = 1' -0"
A4.06 08 EAST LOCKERS
1/4" = 1' -0"
A4.06 11 FAMILY RESTROOMS SOUTH
1/4" = 1' -0"
A4.06 04 FAMILY RR 20C WEST
1/4" = 1' -0"
A4.06 07 FAMILY RR 20C NORTH
1/4" = 1' -0"
A4.06 10 FAMILY RR 20C EAST
1/4" = 1' -0"
A4.06 13 FAMILY RR 20C SOUTH
1/4" = 1' -0"
A4.06 16 FAMILY RR 20B WEST
1/4" = 1' -0"
A4.06 18 FAMILY RR 20B NORTH
1/4" = 1' -0"
A4.06 14 FAMILY RR 20B EAST
1/4" = 1' -0"
A4.06 17 FAMILY RR 20B SOUTH

KEYNOTE LEGEND

10.06 SIGNAGE

10.07 CHANGING TABLE, MOUNTING PER G0.32

26.08 SURFACE MOUNTED LINEAR WALL WASH LIGHT FIXTURE , PER

ELECTRICAL DRAWINGS
203
37 08/09/2024
203
LEGEND
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.01.

STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.01. REFER TO S0.91 FOR INTERIOR STUD WALL SCHEDULE

LINE OF ELEMENT ABOVE

HATCH INDICATES NEW BUILT -IN CASEWORK

GENERAL NOTES
301
36 33
24 CABINET DESIGN SERIES NUMBERING SYSTEM PER

ARCHITECTURAL WOODWORK STANDARDS

AWI CASEWORK NUMBER

CABINET WIDTH

CABINET HEIGHT

CABINET DEPTH

ALIGN FINISHES
XX
FINISH TAG REF: A6.31 FINISH SCHEDULE
EQUIPMENT TAG 1i

1. FOR FINISH & RESTROOM ACCESSORY SCHEDULES REF: A6.31

2. FOR TYPICAL WALL BASE DETAILS REF: 07/A9.12

3. ALL PLUMBING FIXTURES TO HAVE SOLID BLOCKING AS REQUIRED BY CODE.

4. FOR FIXTURE AND ACCESSORY MOUNTING HEIGHTS, REF: G0.32

5. PROVIDE 5/8" TYPE "X" WATER RESISTANT GYPSUM BOARD AT ALL RESTROOM WALLS NOT RECEIVING TILE. PAINT PER FINISH PLANS

6. PROVIDE CEMENTITIOUS TILE BACKER BOARD AT ALL TILED WALLS, TYP.

7. PROVIDE LOCALIZED SLAB DEPRESSION AT FLOOR DRAINS, REF: 7/A9.41

8. TYPICAL PAINT AT RESTROOMS TO BE "SEMI -GLOSS" FINISH.

9. REFER TO MANUFACTURER'S TOILET ACCESSORY INSTALLATION AND OTHER

MOUNTING INSTRUCTIONS AND PROVIDE WALL BACKING AND OTHER REQUIRED SUPPORT AS INDICATED.

10. REFER TO DETAIL 04/G0.32 FOR ACCESSIBLE STALL INFORMATION. AT ACCESSIBLE STALLS: TOILET PARTITION DOOR WIDTHS ARE TO BE 36" (34" MIN.

CLEAR REG'D) PARTITION STILE WIDTH SHALL NOT EXCEED 4". FLUSH VALVE TO BE LOCATED AT WIDE SIDE OF STALL SPACE.

11. FOR SIGNAGE DETAILS, SEE SHEET A10.01
GYP -1

FRAMED GYPSUM BOARD CEILING

SEE DETAILS ON SHEET A--
ACT -1
2'X4' ACOUSTIC CEILING TILE
DUNE TEGUALR, 9/16" SILHOUETTE GRID

SEE DETAIL ----
GYP -3 FRAMED MOISTURE -RESISTANT GYP BD CEILING,

SEE DETAILS ON SHEET A----

CEILING TYPE X
X' -X" CEILING HEIGHT, SEE PLAN
FINISHED EDGE F.E.

INDICATED ACCESSIBLE LOCKER

METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION

CMU WALL CONSTRUCTION

EXISTING STUD WALLS

EXISTING CMU WALLS
XX
XX

FLOOR FINISH

BASE FINISH

WALL FINISH
*REFERENCE FINISH SCHEDULE ON SHEET A6.31
T5
T3
T4
T5
T4
T5
T4
3'-4"

26.08 LL
T5
T4

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

ENLARGED

RESTROOM PLANS
& ELEVATIONS
A4.07
MD
MONROE ST. POOL REPLACEMENT

ENLARGED RESTROOM PLANS & ELEVATIONS

KEYNOTE LEGEND

26.08 SURFACE MOUNTED LINEAR WALL WASH LIGHT FIXTURE , PER

ELECTRICAL DRAWINGS
1/4" = 1' -0"
A4.07 04 INT ELEVATION - FAMILY RR 20E
SOUTH
1/4" = 1' -0"
A4.07 07 INT ELEVATION - FAMILY RR 20E
WEST
1/4" = 1' -0"
A4.07 10 INT ELEVATION - FAMILY RR 20E
NORTH
1/4" = 1' -0"
A4.07 13 INT ELEVATION - FAMILY RR 20E
EAST
38 203
08/09/2024
203

ABBREVIATIONS

DOOR NOTES
CORE
GL = GLASS (T = TEMPERED)
SC = SOLID CORE
HC = HOLLOW CORE
HCI = HOLLOW CORE INSULATED
CLOSER
OH = OVERHEAD
FLR = FLOOR
C-OH = CONCEALED OVERHEAD

DOOR PANEL MATERIAL
AL = ALUMINUM
WD = WOOD
HM = HOLLOW METAL

DOOR FRAME FINISH
PT = PAINT
FF = FACTORY FINISH

DOOR FRAME MATERIAL
AL = ALUMINUM
HM = HOLLOW METAL

DOOR PANEL FINISH
PT = PAINT (SEMI -GLOSS)
FF = FACTORY FINISH
PL = PLASTIC LAMINATE
ST =STAIN

GLASS FINISH
FM = FILM ON DOOR & SIDELIGHT GLAZING

DOOR TYPES

REMARKS
PH = PANIC HARDWARE
HO = HOLD OPEN
CR = CARD READER
BG = BULLET -RESISTANT GLASS

1. DOOR OPENING HARDWARE IS MOUNTED 34 ” TO 44 ” ABOVE THE FINISH FLOOR PER CBC 11B -404.2.7.

2. DOOR HARDWARE ARE OPERABLE WITH ONE HAND AND DO NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING OF THE HAND. CBC 11B -404 .2.7 AND 11B -309.4.

3. DOOR OPENING FORCE IS 5 -POUNDS MAXIMUM FOR INTERIOR AND EXTER IOR DOORS PER CBC 11B -404.2.9.

4. LOWER 10 INCH OF THE DOOR SURFACE IS PROVIDED WITH A SMOOTH

SURFACE FOR THE FULL WIDTH OF THE DOOR,
AT THE PUSH SIDE OF THE DOOR PER CBC 11B -404.2.10

5. DOOR THRESHOLDS TO HAEV MAX 1/4" THRESHOLD TRANSITION, OR 1/2 " MAX

TRANSITION WITH BEVELED EDGE, PER

6. DOORS WITH TWO PANELS, ONE PANEL PROVIDE A CLEAR 32 ” WIDTH PER CBC 11B -404.2.

TYPE A TYPE B
+7'-0"
T.O. DOOR

TYPE C TYPE D TYPE E TYPE F
TT
T
10"
EQ EQ
10"

LOUVER PER SCHEDULE
( WHERE OCCURS)
EQ EQ
10"
EQ EQ
10"
EQ EQ
0'-6"
1'-0"
1'-0"

DOOR LITE
( WHERE OCCURS)
ABOVE F.F. TYP.
34" - 44"
43" MAX
01/ A9.12
TYPE H

LOUVER PER SCHEDULE
( WHERE OCCURS)

DOOR LITE
( WHERE OCCURS)

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
1/4" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

DOOR SCHEDULES
A6.11
MD
MONROE ST. POOL REPLACEMENT

DOOR SCHEDULES

DOOR SCHEDULE

DOOR NUMBER

DOOR TYPE

DETAILS DOOR SIZE DOOR PANEL DOOR FRAME

REMARKS
HEAD
JAMB

THRESHOLD
WIDTH
HEIGHT

THICKNESS

MATERIAL
FINISH

MATERIAL
FINISH

HARDWARE GROUP
<vari
es>
<varies> <varies> <varies> <varies> <varies> <varies> <varies> <va rie s>
<varies> <varies>
101 A 6'-0" 8'-2" GL AL 05 CR, PANIC HDW,
102 B 2'-11
13/16"
6'-8" 0'-1 1/2" GL HM PT 11 3/4" UNDERCUT
103 B 3'-0" 6'-8" 0'-1 1/2" GL HM PT 11 3/4" UNDERCUT
104 E 3'-0" 7'-0" 0'-1 1/2" HM PT HM PT 14 26" x 26" METAL LO UVER, 50% OPEN 104A E 2'-8" 7'-0" 0'-1 1/2" HM PT HM PT 11 3/4" UNDERCUT 105 C 06/A8.14 12/A8.14 15/A8.14 3'-0" 6'-10" 0'-1 3/4" HM P T HM PT 02 26" x 26" METAL LOUVER, 50% OPEN. VIF EXISTI NG OPENING 106 C 06/A8.14 12/A8.14 15/A8.14 3'-0" 7'-2" 0'-1 3/4" HM PT HM PT 01 107 D 06/A8.14 12/A8.14 15/A8.14 5'-8" 7'-2" 0'-1 3/4" HM PT HM PT 04 20" x 10" METAL LOUVER EACH LEAF, 50% OPEN 108 E 3'-0" 7'-0" 0'-1 1/2" HM PT HM PT 14 26" x 26" METAL LO UVER, 50% OPEN 108A E 2'-8" 7'-0" 0'-1 1/2" HM PT HM PT 11 3/4" UNDERCUT 109 C 06/A8.14 12/A8.14 14/A8.14 3'-0" 6'-10" 0'-1 3/4" HM C LR HM PT 12 24" X 24" METAL LOUVER, 50% OPEN. VIF EXIS TING OPENING 109A E 3'-0" 7'-0" 0'-1 1/2" HM CLR HM PT 13 3/4" UNDERCUT 110 C 06/A8.14 12/A8.14 15/A8.14 3'-0" 6'-10" 0'-1 3/4" HM P T HM PT 02 26" x 26" METAL LOUVER, 50% OPEN, VIF EXISTI NG OPENING 111 A 6'-0" 7'-0" 0'-1 3/4" GL AL CLR 06 VIF EXISTING OPENIN G 111A E 2'-8" 7'-0" 0'-1 1/2" WD CLR HM PT 10
112 C 06/A8.14 12/A8.14 15/A8.14 3'-0" 6'-10" 0'-1 3/4" HM P T HM PT 07 26" x 26" METAL LOUVER, 50% OPEN, VIF EXISTI NG OPENING 113 C 06/A8.14 12/A8.14 15/A8.14 3'-8" 7'-4" 0'-1 3/4" HM PT HM PT 03 24" x 24" METAL LOUVER, 50% OPEN 114 G11 06/A8.14 12/A8.14 15/A8.14 3'-2" 7'-4 1/2" 0'-1 3/ 4" PT PT 15 24" X 24" METAL LOUVER EACH LEAF, 50% OPEN . 8" DOOR LITE,

EACH LEAF
114A F 3'-0" 7'-0" 0'-1 1/2" HM PT HM PT 09 20" x 10" METAL L OUVER, 30% OPEN 114B F 3'-0" 7'-0" 0'-1 1/2" HM PT HM PT 09 20" x 10" METAL L OUVER, 30% OPEN 114C F 3'-0" 7'-0" 0'-1 1/2" HM PT HM PT 09 20" x 10" METAL L OUVER, 30% OPEN 114D F 3'-0" 7'-0" 0'-1 1/2" HM PT HM PT 09 20" x 10" METAL L OUVER, 30% OPEN 114E F 3'-0" 7'-0" 0'-1 1/2" HM PT HM PT 09 20" x 10" METAL L OUVER, 30% OPEN 115 C 06/A8.14 12/A8.14 15/A8.14 3'-8" 7'-4" 0'-1 3/4" HM PT HM PT 03 24" X 24" METAL LOUVER, 50% OPEN 116 G8 06/A8.14 12/A8.14 15/A8.14 6'-0" 7'-2" 0'-1 3/4" HM P T HM PT 04 24" X 24" METAL LOUVER EACH LEAF, 50% OPEN 117 D 06/A8.14 12/A8.14 15/A8.14 4'-8" 7'-2" 0'-1 3/4" HM PT HM PT 04 20" x 10" METAL LOUVER EACH LEAF, 50% OPEN 118 D 06/A8.14 12/A8.14 15/A8.14 4'-8" 7'-2" 0'-1 3/4" HM PT HM PT 04 20" x 10" METAL LOUVER EACH LEAF, 50% OPEN 119 C 06/A8.14 12/A8.14 15/A8.14 3'-8" 7'-4" 0'-1 3/4" HM PT HM PT 08 26" x 26" METAL LOUVER, 50% OPEN 130 C 3'-0" 7'-2" 0'-1 3/4" 08 26" x 26" METALLOUVER, 50% OPEN

DOUBLE IN AL

STOREFRONT

SINGLE IN AL

FRAME/ SIDE LITE

SINGLE HM IN CMU DOUBLE HM IN CMU SINGLE AL IN STUD SINGLE HM IN STUD SINGLE HM WITH

LOUVER SIDE PANEL
39 203
08/09/2024
203
01 - FLOOR
0'-0"
1A
TTTT
8'-6"
01 - FLOOR
0'-0"
TTT
2A
8'-7"
(VERIFY)
8'-8"
01 - FLOOR
0'-0"
3A
T

EXISTING
(VERIFY)

EXISTING

SPANDREL

TOP OF BLOCK EAST -
BLDG A
10'-6"
8'-6"

SOLID FRIT
6'-0"
50% FRIT
50% FRIT
01 - FLOOR
0'-0"
4A
T
5'-4"
4'-8" 2'-8"
01 - FLOOR
0'-0"
5A
3'-0" 4'-0"
2'-8"
01 - FLOOR
0'-0"
5D
4'-0" 3'-0"
2'-8"

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
3/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

OPENING TYPES
A6.21
MD
MONROE ST. POOL REPLACEMENT

OPENING TYPES

KEYNOTE LEGEND
40 203
08/09/2024
203

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

FINISH &

EQUIPMENT

SCHEDULES
A6.31
MD
MONROE ST. POOL REPLACEMENT

FINISH & EQUIPMENT SCHEDULES
FAB-1 SOLAR SHADE FABRIC MECHO SHADE 1550 SERIES / ECOVEIL / 1% OPEN 1563 GREY - - - SHADE DETAIL REF: 07 & 08/A 9.31

SPECIALTY ,
QTZ-2 QUARTZ SOLID SURFACE ARIZONA TILE DELLA TERRA QUARTZ CONCRETE GREY STANDARD - " QTZ-1 QUARTZ SOLID SURFACE ARIZONA TILE DELLA TERRA QUARTZ AERIAL STANDARD - PL-2 PLASTIC LAMINATE WILSONART - - "
PL-1 PLASTIC LAMINATE WILSONART LANDMARK WOOD 7981 - -

CASEWORK
T-6 TILE BASE DALTILE COLOR WHEEL / LINEAR ARCTIC WHITE 01 90 SEMI-GLOSS 4"H COVE - ALIGN GROUT JOINTS WHERE POSS IBLE T-5 TILE BASE FRY REGLET DRMB-625-300 TBD - 4"H COVE - PROVIDE AN EXTRA LAYER O F GYP. BD. WHERE FIRE RATED WALLS OCCUR B-1 RUBBER BASE JOHNSONITE WALL BASE UMBER #63 - 4" H - REF: 07/A9.42

WALL BASE
FRP FIBER REINFORCED PANEL MARLITE STANDARD FRP, CLASS A W HITE S100G - FULL HEIGHT - PROVIDE ALUMINUM TRIM AS N EEDED, SEE 20/A9.42 WC-1 WALL COVERING KOROSEAL KOROSEAL DIGITALLY PREINTED VI NYL CUSTOM SEMI-GLOSS CUSTOM ADHERED SEE INTERIOR ELEVAT IONS FOR EXTENTS T-4 WALL TILE DALTILE OUTLANDER MARINE RECTANGLE PALAZZO MA TTE 2'X2' STACKED T-3 WALL TILE DALTILE OUTLANDER MARINE RECTANGLE GRANDE MAT TE 2'X2' STACKED P-4 PAINT, ACCENT BEHR - True Copper EGGSHELL - -
P-3 PAINT, ACCENT SHERWIN WILLIAMS - Billowy Breeze EGGSHELL - - P-2 PAINT, ACCENT SHERWIN WILLIAMS - Silken Peacock EGGSHELL - - P-1 PAINT, GENERAL SHERWIN WILLIAMS - SW 7008 ALABASTER EG GSHELL - - PROVIDE FLAT FINISH AT CEILINGS, EGGSHELL FINISH AT WALLS, SEMI-GLOSS AT DOOR FRAMES TYP.

WALL FINISH
CONC-1 POLISHED CONCRETE WESTCOAT SC-42 WB ACRYLIC SEALER MAT CH EXTERIOR CONCRETE SEMI-POLISHED - - T-2 FLOOR TILE DALTILE VOLUME 1.0 STEREO GREY - 6"X6" STAGGA RD T-1 FLOOR TILE DALTILE VOLUME 1.0 DEGREES SILVER - MOSAIC 2"X2" LVT-1 VINYL TILE MILLIKEN THE MAGIC HOUR HORIZON LIGHT - PLAN K 10"X40" RUNNING BOND CPT-2 WALK OFF CARPET INTERFACE STEP AND REPEAT / SR699 COL ORLINE GRANITE 104931 - 40"X40" RUNNING BOND LOCATED AT SLAB DEPRESSION, SEE FINISH PLANS & FLOORING SECTION CPT-1 CARPET TILE SHAW CONTRACT ALL TOGETHER TILE TOGETHER C OLOR 50210 - PLANK 9"X36"

FLOOR FINISH

TAG DESCRIPTION MANUFACTURER STYLE/COLLECTION COLOR FINI SH SIZE INSTALL COMMENTS

FINISH SCHEDULE
U-2 - - ACCESSIBLE URINAL, REFER TO PLUMBING DRAWINGS
U-1 - - URINAL, REFER TO PLUMING DRAWINGS
L-2 - - ACCESSIBLE LAVATORY, REFER TO PLUMBING DRAWING S L-1 - - LAVATORY, REFER TO PLUMBING DRAWINGS
SH-2 - - SHOWER, REFER TO PLUMBING DRAWINGS
SH-1 - - ACCESSIBLE SHOWER, REFER TO PLUMBING DRAWINGS
TAG # DESCRIPTION

PLUMBING FIXTURE SCHEDULE
SS BOBRICK B-207, TBD CHANGING CURTAIN & ROD - FABRIC (TBD) RR BOBRICK B-5191 ACCESSIBLE SHOWER BENCH
QQ BOBRICK B-207, B-204 SHOWER ROD & SHOWER CURTAIN
PP BRADLEY MATCH II 36" URINAL PRIVACY PARTITION, PHEN OLIC OO BOBRICK B-2974 AUTOMATIC SURFACE MOUNTED ROLL TOWEL DISPENSER WITH LED LIGHT NN BOBRICK B-3588 SURFACE-MOUNTED MULTI-ROLL TOILET TI SSUE DISPENSER LL BOBRICK B-290 OR SIM MIRROR WITH 1/2" STAINLESS TEE L FRAME. VARIOUS SIZES, SEE INTERIOR ELEVATIONS KK BOBRICK KB110-SSWM SURFACE MOUNTED BABY CHANGING ST ATION II BRADLEY SERIES 400 FLOOR MOUNTED TOILET PARTITIONS, PHENOLIC CORE FINISH HH BOBRICK B-3974 RECESSED CONVERTIBLE AUTOMATIC ROLL TOWEL DISPENSER EQUIPPED WITH LED LIGHT AND WASTE RECEPTICLE GG BOBRICK B-270 BOBRICK B-270 CONTURA SERIES SURFACE MOUNTED SANITARY NAPKIN DISPOSAL FF BOBRICK B-4221 CONTURA SERIES SURFACE MOUNTED SEAT COVER DISPENSER EE BOBRICK B-3579 SURFACE-MOUNTED SEAT-COVER DISPENSER , SANITARY NAPKIN DISPOSAL, AND TOILET TISSUE DISPENSER DD BOBRICK B-3571 PARTITION MOUNTED, RECESSED TOILET S EAT COVER, TOILET TISSUE DISPENSER AND SANITARY NAPKIN DISPOSAL - TWO COMPARTMENT UNIT CC BOBRICK B-3479 SURFACE MOUNTED SEAT COVER AND TOILE T TISSUE DISPENSER BB BOBRICK B-3471 PARTITION MOUNTED TOILET SEAT COVER AND TOILET TISSUE DISPENSER - TWO COMPARTMENT UNIT AA BOBRICK B-5806 STAINLESS STEEL GRAB BAR
TAG # MANUFACTURER MODEL # DESCRIPTION

RESTROOM ACCESSORIES SCHEDULE
41 203
08/09/2024
203
A
0'-3" TYP.

C4X5.4, SEE STRUCT.; PAINTED TO

MATCH PERFORATED PANEL
3/8" STAINLESS STEEL BOLT
ASSEMBLY; (2) PER ANGLE

PERFORATED ALUMINUM PANELS
W/ 3" RETURNS ON ALL 4 SIDES

ETHER POLYURETHANE WASHERS,
TYP.

STEEL ANGLE 2" x 3" x 1/4" x 9" LONG;

PAINTED TO MATCH PERFORATED
PANEL; (2) ANGLES PER PANEL 3"

FROM ENDS
3/16"
TYP. CEM. PLASTER WALL
ASSEMBLY, SEE DETAIL13/A8.12
CONT. SEALANT O/

BACKER ROD
SLOPE 1/2" : 12"
1'-4" 0'-7 1/2"
TYP. COPING, SEE DETAIL 9/A8.22

TOP OF BLOCK - BLDG A
9'-10"
A
DIM PT
R.O.

ACOUSTICAL LAY-

IN PANEL

EXISTING

HEAVY TIMBER
BEAM
SEALANT & BACKER ROD;

WEEP HOLES AS REQUIRED

ALUMINUM STOREFRONT SYSTEM

PANEL CLIPS PER MANUFACTURER

COMPOSITE ALUMINUM PANEL
0'-6"

STRUCTURAL STUD FRAMING
STRUCT. STUD

FRAMING
HSS FRAME, SEE STRUCT.

HSS FRAME,
SEE STRUCT.

DIM PT
3" MIN.
1/4" / 1'-0"
1/4"

PLASTER ASSEMBLY WALL,
SEE 13/A8.12
8 1/8"
1/4"
C4X5.4, SEE STRUCT.; PAINTED TO

MATCH PERFORATED PANEL
3/8" STAINLESS STEEL BOLT ASSEMBLY
12" O.C. MAX. (MIN. 3 PER PANEL)

PERFORATED ALUMINUM PANELS W/
3" RETURNS ON ALL 4 SIDES

ETHER POLYURETHANE WASHERS,
TYP.

CONTINUOUS STEEL ANGLE 1 1/2" x 3" x
1/4" WELDED TO VERTICAL HSS

PAINTED TO MATCH PERFORATED
PANEL
3/16"
B.O.

PANEL
2"
A

COMPOSITE ALUMINUM PANEL
SEALANT & BACKER ROD;

WEEP HOLES AS REQUIRED

PANEL CLIPS PER MANUFACTURER
1'-6 3/4" 6"

ALUMINUM STOREFRONT SYSTEM
HSS FRAME, SEE STRUCT.

SEALANT & BACKER
ROD; WEEP HOLES

AS REQUIRED

J-BOX FOR INTERCOM
COORD. LOCATION W/ ARCHITECT. 11
A8.12
12 A8.12
C4x5.4, TITEN HD
ANCHOR @ 24" O.C.,

PAINTED TO MATCH

PERFORATED PANEL
3" TYP.
3/8" STAINLESS STEEL CARRIAGE BOLT
W/CAP NUT 3' O.C. MAX. AND 6" FROM EACH
END (MIN. 3 PER PANEL)

PERFORATED ALUMINUM PANELS
W/ 3" RETURNS ON ALL 4 SIDES
ETHER POLYURETHANE WASHERS, TYP.

EDGE OF
PANEL
CONTINUOUS STEEL ANGLE 2"X3"X1/4"

PAINTED TO MATCH PERFORATED PANEL
3/16"
1/2" CONT. BENT PLATE
W/ 1/4" TITEN HD
ANCHOR @ 24" O.C.
0'-2" 0'-8"
7/8" CEMENT PLASTER

METAL LATH
1 1/2" RIGID INSULATION
18 GA. 1.5" HORIZONTAL

Z-CHANNEL ATTACHMENT

WEATHER -RESISTANT

BARRIER
5/8" TYPE 'X' GYPSUM
BOARD

METAL STUD PER

STRUCTURAL
5/8" GYPSUM BOARD
R-19 MIN. BATT INSUL.

EXT INT
#10 SMS @ 16" O.C., TYP.,

ATTACHED TO Z -CHANNEL PER
G.2 / S0.01
#8 S.M.S. AT 16" O.C.,

ATTACHED TO METAL STUD
PER G.2 / S0.01; BUGLE HEAD

AT INTERIOR
#10 SMS @ 16" O.C., TYP.,

ATTACHED TO METAL STUD
PER G.2 / S0.01

STEEL FRAME, SIZE VARIES,
SEE STRUCT.; PAINTED TO

MATCH PERFORATED PANEL
3/8" STAINLESS STEEL

CARRIAGE BOLT W/
CAP NUT 12" O.C. MAX.
(MIN. 3 PER PANEL)
B.O.

PANEL

PERFORATED ALUMINUM
PANELS W/ 3" RETURNS
ON ALL 4 SIDES

ETHER POLYURETHANE
WASHERS, TYP.

CONTINUOUS STEEL ANGLE
1 1/2" x 3" x 1/4" WELDED TO

HSS PAINTED TO MATCH

PERFORATED PANEL

SECTION - SILL & BASE CONDITION

CONCRETE PAVING

WHERE OCCURS PER

LANDSCAPE AND

CIVIL DRAWINGS
3/16"
W

HERE OCCURS
3"M
IN. ABOVE GRADE

SECTION - VERTICAL JOINT
0'-3" TYP.

WHERE NO CMU
WALL OCCURS:

STEEL FRAME, SIZE

VARIES, SEE
STRUCT.; PAINTED

TO MATCH

PERFORATED
PANEL
3/8" STAINLESS STEEL
BOLT ASSEMBLY; (2)

PER ANGLE
PANEL
JOINT

PERFORATED

ALUMINUM PANELS
W/ 3" RETURNS ON
ALL 4 SIDES

ETHER POLYURETHANE
WASHERS, TYP.

STEEL ANGLE 1 1/2" x 3"
x 1/4" x 9" LONG;

PAINTED TO MATCH
PERFORATED PANEL;
(2) ANGLES PER PANEL
3" FROM ENDS
3/16"

AT MAIN ENTRY

ONLY, WHERE CMU

WALL WHERE
OCCURS;
C4x5.4, TITEN HD
ANCHOR @ 24" O.C.,

PAINTED TO MATCH

PERFORATED
PANEL
0'-3" TYP.
3/8" STAINLESS STEEL

CARRIAGE BOLT W/ CAP
NUT 12" O.C. MAX. (MIN. 3

PER PANEL)
T.O.

PANEL

PERFORATED ALUMINUM
PANELS W/ 3" RETURNS
ON ALL 4 SIDES
ETHER

POLYURETHANE
WASHERS, TYP.

CONTINUOUS STEEL
ANGLE 1 1/2" x 3" x 1/4";

PAINTED TO MATCH

PERFORATED PANEL

SECTION - TOP JOINT
3/16"

STEEL FRAME, SIZE VARIES, SEE
STRUCT.; PAINTED TO MATCH

PERFORATED PANEL

PLAN - HORIZONTAL JOINT
0'-3" TYP.
3/8" STAINLESS

STEEL BOLT
ASSEMBLY 3' O.C.

MAX. AND 6" FROM
EACH END (MIN. 3

PER PANEL)
PANEL
JOINT

PERFORATED

ALUMINUM PANELS
W/ 3" RETURNS ON
ALL 4 SIDES

STAINLESS STEEL

TREADED

STANDOFF W/
ETHER

POLYURETHANE

WASHERS EA SIDE
0'-1"

STEEL FRAME, SIZE
VARIES, SEE STRUCT.;

PAINTED TO MATCH

PERFORATED PANEL
0'-3" TYP.

STEEL FRAME, SIZE
VARIES, SEE STRUCT.;

PAINTED TO MATCH

PERFORATED PANEL
3/8" STAINLESS STEEL

CARRIAGE BOLT W/ CAP
NUT 3' O.C. MAX. AND 6"
FROM EACH END (MIN. 3

PER PANEL)

EDGE OF
PANEL

PERFORATED ALUMINUM
PANELS W/ 3" RETURNS
ON ALL 4 SIDES
ETHER

POLYURETHANE
WASHERS, TYP.

CONTINUOUS STEEL
ANGLE 2" x 3" x 1/4"

PAINTED TO MATCH

PERFORATED PANEL

PLAN - END OF PANEL
0'-2"

EXTERIOR CMU WALL

WHERE OCCURS
3/16"
0'-3"
0'-2"

STAINLESS STEEL

PLATE, ALL AROUND EXPOSED

EXTERIOR BASE

EXISTING CONCRETE PAVING

PANEL CLIPS PER

MANUFACTURER

COMPOSITE ALUMINUM PANEL
1/2" CONT. BENT PLATE
W/1/4" TITEN HD ANCHOR @ 24" O.C.
0'-8"
0'-1"
3/16"
1/4" CONT. BENT PLATE
0'-2"

STAINLESS STEEL

PLATE, ALL AROUND EXPOSED

EXTERIOR BASE

EXISTING CONCRETE PAVING

PANEL CLIPS PER

MANUFACTURER

COMPOSITE ALUMINUM PANEL

MTL STUD FRAMING W/
R-19 MIN INSULATION
EXT

DRIP SCREED

PER RCP PLAN

BO SOFFIT

PLASTER ASSY

SECTION - VERTICAL JOINT
0'-3" TYP.
3/8" STAINLESS STEEL
BOLT ASSEMBLY; (2)

PER ANGLE
PANEL
JOINT

PERFORATED

ALUMINUM PANELS
W/ 3" RETURNS ON
ALL 4 SIDES

ETHER POLYURETHANE
WASHERS, TYP.

STEEL ANGLE 1 1/2" x 3"
x 1/4" x 9" LONG;

PAINTED TO MATCH
PERFORATED PANEL;
(2) ANGLES PER PANEL
3" FROM ENDS
3/16"
C4x5.4, TITEN HD
ANCHOR @ 24" O.C.,

PAINTED TO MATCH

PERFORATED
PANEL
0'-3" TYP.

T.O.

PANEL & CMU

PERFORATED ALUMINUM
PANELS W/ 3" RETURNS
ON ALL 4 SIDES
M
IN.
2"
VERTICAL C4X5.4

BEYOND AT EVERY
VERTICAL JOINT. SEE
01/A8.12. STOP 2" MIN.

BELOW TOP OF PANEL

TO ALLOW FOR CMU
COPING CLEARANCE.

SEE 06/A8.22 FOR CMU
COPING DETAIL.

B.O.

PANEL

PERFORATED ALUMINUM
PANELS W/ 3" RETURNS
ON ALL 4 SIDES
VERTICAL C4X5.4

BEYOND AT EVERY
VERTICAL JOINT. SEE
01/A8.12. STOP 2" MIN.

BELOW TOP OF PANEL

TO ALLOW FOR CMU
COPING CLEARANCE.

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

EXTERIOR DETAILS
A8.12
MD
MONROE ST. POOL REPLACEMENT

EXTERIOR DETAILS
3" = 1' -0"
A8.12 16 PERF PANEL & PLASTER TOP
3" = 1' -0"
A8.12 15 ENTRY PORTAL TOP DETAIL
3" = 1' -0"
A8.12 14 ENTRY PORTAL PLAN DETAIL
3" = 1' -0"
A8.12 13 TYP. CEM. PLASTER WALL

ASSEMBLY
6" = 1' -0"
A8.12 08 PERF METAL BASE DETAIL
6" = 1' -0"
A8.12 04 PERF METAL JOINT VERTICAL
6" = 1' -0"
A8.12 10 PERF METAL TOP
6" = 1' -0"
A8.12 09 PERF METAL JOINT HORIZONTAL
6" = 1' -0"
A8.12 05 PERF METAL EDGE
3" = 1' -0"
A8.12 11 ENTRY PORTAL BASE DETAIL
3" = 1' -0"
A8.12 12 ENTRY PORTAL BASE DETAIL @
CMU
3" = 1' -0"
A8.12 06 PLASTER SOFFIT DRIP SCREED
6" = 1' -0"
A8.12 01 PERF METAL JOINT VERTICAL -

DIRECT ATTACHED TO CMU
6" = 1' -0"
A8.12 03 PERF METAL TOP - DIRECT

ATTACHED TO CMU
6" = 1' -0"
A8.12 02 PERF METAL BASE - DIRECT

ATTACHED TO CMU
42 203
08/09/2024
203
0'-0 1/4"

CONSTRUCTION SPECIALTIES
SC-800 JOINT
1/4" x 2 1/4" SCREW BOLT W/
SEALING WASHER 18" O.C.
(FIN: ZINC) ICC ESR-4042
CMU WALL; REF: STRUCTURAL DRAWINGS
5/8" MIN. OF FILL

MATERIAL APPLIED
WITHIN THE ANNULUS.

FLUSH WITH BOTH
SURFACES OF WALL.
2" MAX. THICK HOLLOW -

CYLINDRICAL HEAVY

GLASS FIBER PIPE
INSULATION COVERING.

NOTE:

1. IN MULTIPLE PIPE PENETRATIONS OCCUR IN PARTITION,

MAINTAIN ADEQUATE SEPARATION TO TREAT EA PIPE SEPARATELY

2. UL SYSTEM NO. W -J-5042

PENETRANT TO BE

RIGIDLY SUPPORTED

ON BOTH SIDES OF
WALL ASSEMBLY.

PER PLAN

WALL TYPE
W-J-5042:

FIN. FLOOR
(WHERE OCCURS)
INT. EXT.

CMU WALL BLOCK SEAL AT

EXTERIOR FLOOR SLAB

FLOOR FINISH & BASE PER

FINISH PLAN

COLD FLUID APPLIED

WATERPROOFING (TOP OF

WP NOT TO BE VISIBLE)
EXTERIOR PAVER.

SIDEWALK, WHERE

OCCURES

PER STRUCTURAL

STRUCTURAL FOOTING PER

STRUCTURAL
U937 FOR 1-HR RATED

CONDITION

ALUMINUM

STOREFRONT SYSTEM

EXTERIOR GLAZING SYSTEM,

SEE WINDOW TYPES
CONT. BEARING
PLATE SET IN CONT.

BED OF SEALANT
ALUM. SUBSILL

FLASHING W/ END DAMS,
SET IN CONT. BED OF
SEALANT. MATCH

WINDOW FINISH
CONT. BACKER

ROD AND

SEALANT, BOTH
SIDES
SHIM AS REQ'D.

CONNECTION TO STRUCTURE

BY MANUFACTURER
0'-1"

ALUMINUM

STOREFRONT DOOR

THRESHOLD SET

IN FULL BED OF

SEALANT

CONCRETE FLOOR
1/4" DIA x 1 -5/8" EMBED

STAINLESS STEEL
TITEN HD @24" O/C (ICC
ESR 2713) (2) MIN PER

THRESHOLD
1/2" EXP

JOINT FILLER

FIN GRADE

CONC PAVING

FACE OF CONC
SLAB
2 1
TOS
1/4" 1/4"

EXTERIOR INTERIOR
10".

M
AX
1/4"
3 1/2" MIN.
0'-0 3/8"CONTROL JOINT

CMU BLOCK WALL

FLANGED NEOPRENE

CONTROL JOINT, CONT
VERT

CONT REBAR PER

STRUCTURAL, DO NOT

BREAK AT JOINT

BACKER ROD AND

SEALANT, CONT EACH SIDE
TYP
0'-0 1/2"
0'-0 3/8"EXP JOINT

CMU BLOCK WALL

FLANGED NEOPRENE

CONTROL JOINT, CONT VERT

REBAR PER STRUCTURAL,

DO NOT CONTINUE

THROUGH JOINT

BACKER ROD AND

SEALANT, CONT EACH SIDE
TYP
0'-0 1/2"

CONTROL JOINT AT CMU WALL

EXPANSION JOINT AT CMU WALL

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

EXTERIOR DETAILS
A8.13
MD
MONROE ST. POOL REPLACEMENT

EXTERIOR DETAILS
3" = 1' -0"
A8.13 03 WALL EXPANSION JOINT
3" = 1' -0"
A8.13 04 INSULATED PIPE PENETRATION @ RATED WALL
1 1/2" = 1' -0"
A8.13 02 EXTERIOR CMU WALL BASE
3" = 1' -0"
A8.13 11 STOREFRONT SILL @ SLAB
6" = 1' -0"
A8.13 14 STOREFRONT DOOR SILL
3" = 1' -0"
A8.13 15 TYPICAL MASONRY CONTROL
JOINT
43 203
08/09/2024
203
MIN.
1 1/2"

SEALANT & BACKER

ROD ON BOTH SIDES

ALUM STOREFRONT

DRIP EDGE

SEALANT & BACKER

ROD ON BOTH SIDES

SEALANT BELOW

FLASHING
0'-2" VARIES 0'-2"
0'-0 1/2" 0'-0 1/2"
0'-0 5/8" 0'-2"
& WALL TYPES

PER FLOOR PLANS

METAL STUD WALL PER FLOOR

PLANS & WALL TYPES

DOOR, SEE DOOR SCHEDULE,

SEE FLOOR PLANS FOR DOOR
SWING

HOLLOW METAL
FRAME
BOX HEADER PER 6/S0.92

FINISH WHERE OCCURS PER

FINISH PLANS & INTERIOR

ELEVATIONS
8 5/8"
2"
8"X8"X16" CMU

HOLLOW METAL

FRAME, GROUT SOLID

AT JAMBS

SEALANT BOTH SIDES

JAMB ANCHORS
WOOD SHIM W/3/8" MIN.

CONT. SEALANT AND

BACKER ROD, BOTH
SIDES
CMU WALL. REFER

TO STRUCTURAL

EXTERIOR

INTERIOR

ALUMINUM

STOREFRONT SYSTEM

REFER TO FLOOR PLAN

FOR WALL TYPE AND

LOCATION

GLAZING UNIT
2" VARIES 2"

FINISH WHERE OCCURS PER

FINISH PLANS & INTERIOR

ELEVATIONS

DOOR, SEE DOOR SCHEDULE, SEE

FLOOR PLANS FOR DOOR SWING

ANCHOR PER
& AS REQ. PER MANUF.

HM FRAME ANCHORED TO HEADER

METAL STUD WALL PER

FLOOR PLANS & WALL TYPES
METAL STUD FRAMING PER 1/S0.91 EXT.

INT.
& WALL TYPES

PER FLOOR PLANS
0'-0 3/4" 0'-2"
6" MIN. TO F.O.STUD
NOTES:

1. LOCATE JAMB 6" FROM
F.O.STUD OF ANY ADJACENT
PERPENDICULAR WALL.

XXX
X

DOOR, SEE DOOR

SCHEDULE

BACKER ROD AND

SEALANT
1/2" EXPANSION JOINT
ZERO 673 ALUMINUM

ADJUSTABLE

THRESHOLD SET IN

FULL BED OF SEALANT,
REF: 08/A8.33

PAVING PER CIVIL OR

CONCRETE DECK PER

STRUCTURAL, SLOPE

AWAY FROM DOOR
EXT. INT.

C

AUTOMATIC DOOR
BOTTOM
ZERO 1545 ALUMINUM

THRESHOLD TRANSITION -
1/4" DIA x 1-5/8" EMBED

STAINLESS STEEL TITEN HD
@24" O/C (ICC ESR 2713) (2)

MIN PER THRESHOLD
ZERO 1675 ALUMINUM HALF-

SADDLE THRESHOLD
TRANSITION, REF:

FOR MITERED RETURN
1/4" DIA x 1-5/8" EMBED

STAINLESS STEEL TITEN
HD @24" O/C (ICC ESR
2713) (2) MIN PER

THRESHOLD
3" MIN.

NOTCH SLAB AS

NECESSARY TO RECIVE

THRESHOLD
3/8" CONT. BACKER ROD

AND SEALANT, BOTH
SIDES
EXT. INT.

GLAZING UNIT

SEE WALL SECTIONS

DIM POINT

ALUMINUM

STOREFRONT SYSTEM
1/4"Ø FLAT HEAD TAPCON

SCREW ANCHOR PER
ESR -1671 @ 16" O/C
STAGGERED 2" MIN
EMBEDMENT. 2" MIN EDGE

DISTANCE
2" MIN.

MASONRY LINTEL BLOCK

PER STRUCTURAL

MOUNTING BRACKET

PER MANUFACTURER

MANUAL ROLLER SHADE PER

CEILING PLAN AND INTERIOR

ELEVATION ( WHERE OCCURS)
NOTE:

1. SHADE CLOTH: ECOVEIL (OR EQUAL), 3% OPENING.
1/4" MASONRY SCREWS
WITH 2 -1/2" EMBED @ 16"
O.C. PER STRUCTURAL
DWG.

ALUM STOREFRONT SYSTEM

GLAZING UNIT
WEEP HOLES, TYP.

SEE WALL SECTIONS

DIM POINT
1/4"Ø FLAT HEAD TAPCON

SCREW ANCHOR PER
ESR -1671 @ 16" O/C
STAGGERED 2" MIN
EMBEDMENT. 2" MIN EDGE

DISTANCE
3/8" MIN. CONT. SEALANT AND

BACKER ROD, BOTH SIDES
MTL. FLASHING WITH END

DAMS, FINISH TO MATCH CMU
2" MIN.

DOOR, REF. DOOR

SCHEDULE
2" VARIES 2"
3/8" CONT. BACKER ROD

AND SEALANT, BOTH
SIDES
EXT. INT.

MASONRY LINTEL BLOCK

PER STRUCTURAL

DOOR FRAME, PAINT
TYP. GROUTED SOLID

DOOR ANCHOR TO

MASONRY WALL,
ANCHOR PER 01/A8.51

SEE DR SCHED

DIM POINT
0'-2"
0'-0 5/8"

OPENING
2" VARIES 2"

DOOR, SEE DOOR

SCHEDULE, SEE FLOOR

PLANS FOR DOOR SWING
EXT.

INT.

CONT. SEALANT AND

BACKER ROD, BOTH
SIDES

DOOR ANCHOR TO

MASONRY WALL, ANCHOR
PER 01/A8.51

REFER TO FLOOR PLAN

FOR WALL TYPE AND

LOCATION
0'-2" OPENING

SEE DR SCHED

DIM POINT
2" VARIES 2"
3/8" CONT. BACKER ROD

AND SEALANT, BOTH
SIDES
EXT. INT.

MASONRY LINTEL BLOCK

PER STRUCTURAL

DOOR FRAME, PAINT
TYP. GROUTED SOLID
3/8" DIA. S.S. HILTI KH -EZ
SCREW MIN. 2 1/2"
EMBED W/ 4" MIN. EDGE
DIST. (ESR -3056)

SEE DR SCHED

DIM POINT
0'-2"
0'-0 5/8"

OPENING

CLIP ANGLE

INSECT SCREEN

HIGH PERFORMANCE

FIXED DRAINABLE LOUVER
SYSTEM; PRE-FINISHED
TO MATCH HM FRAMES.

ANCHOR TO HM FRAME
JAMB PER DETAIL 07/A8.51
"U"-LINTEL BLOCK ONLY AT

ALL OPENING

FILL SMALL SPACES BETWEEN

BLOCK AND ROOF FRAMING WITH
GROUT. PAINT TO MATCH CMU.

MIN. DIM. OF CUT BLOCK SHOULD
NOT BE LESS THAN 4" IN ANY

DIRECTIONS

END WITH FULL/ HALF BLOCKS ON TOP

A TYPICAL ELEVATION

WINDOW AS SCHEDULED

BACKER ROD W/

SEALANT

SHIM AS REQUIRED
5/8" TYPE X GYP. BD.
6" METAL STUDS
FRAMING WITH R -19

BATT INSULATION

METAL STUD HEADER
METAL STUDS @ 16' O.C.

ACOUSTICAL BATT

INSULATION AS REQUIRED

PER WALL TYPE
6" METAL STUDS
FRAMING WITH R -19 BATT

INSULATION

SEE RCP

CONTINUOUS SEALANT,
BOTH SIDES (TYP.)

FIXED ALUMINUM

TRANSACTION WINDOW

AS SCHEDULED
5/8" TYPE "X" GYP. BD. TYP.
5"

CORRIDOR SIDE

ALIGN ON
7 1/4"

DRYWALL CORNER
BEAD, TYP.

BACKER ROD AND

SEALANT, BOTH SIDES

ALUMINUM

STOREFRONT WINDOW

AS SCHEDULED
6" METAL STUDS
FRAMING WITH R -19

BATT INSULATION

DOOR - SEE DOOR

SCHEDULE

SMOKE SEAL AT

RATED DOORS FLOORING, SEE

FINISH PLAN
SCHED.

PER
DOOR

FLOORING MATERIAL

TRANSITION AT

CENTERLINE OF DOOR

WHERE OCCURS, PER

FINISH SCHEDULE
T.O. SLAB

TILE OVER

THIN SET

INTEGRATED

DOOR ASSEMBLY,

SEE DOOR

SCHEDULE
T.O. SLAB

FLOOR FINISH,

PER FINISH

SCHEDULE

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

OPENING DETAILS
A8.14
MD
MONROE ST. POOL REPLACEMENT

OPENING DETAILS
3" = 1' -0"
A8.14 04 ALUM. STOREFRONT SIL
3" = 1' -0"
A8.14 10 INT HM DOOR HEAD @ GYP
3" = 1' -0"
A8.14 02 HEAD/JAMB/SILL - HM @ CMU
3" = 1' -0"
A8.14 05 ALUM. STOREFRONT HEAD Copy 1
3" = 1' -0"
A8.14 09 INT HM DOOR JAMB AT GYP
6" = 1' -0"
A8.14 15 EXTERIOR HM DOOR THRESHOLD
3" = 1' -0"
A8.14 03 ALUM. STOREFRONT HEAD1
3" = 1' -0"
A8.14 08 ALUM. STOREFRONT

SILL/COUNTER
3" = 1' -0"
A8.14 06 EXT. H.M. DOOR HEAD
3" = 1' -0"
A8.14 12 EXT. H.M. DOOR JAMB
3" = 1' -0"
A8.14 13 EXT. H.M. LOUVER HEAD
1/4" = 1' -0"
A8.14 01 TYP. CMU OPENING OR END WALL
3" = 1' -0"
A8.14 11 W11 - WINDOW HEAD MWP
3" = 1' -0"
A8.14 16 WINDOW HEAD - INT STOREFRONT
3" = 1' -0"
A8.14 19 HEAD/JAMB/SILL - INT

STOREFRONT
3" = 1' -0"
A8.14 14 INTERIOR DOOR THRESHOLD
3" = 1' -0"
A8.14 17 INTEGRATED DOOR THRESHOLD
Copy 1
44 203
08/09/2024
203

ROOF MEMBRANE

FLASHING HOT AIR

WELDED TO ROOFING
MEMBRANE. EXTEND
UNDER CLAMPING RING.
5/8" GYP.

COVER BOARD

THERMOPLASTIC

ROOFING

ROOF AND OVERFLOW
DRAIN

EXTEND FLASHING UNDER
CLAMPING RING.

UNDER DRAIN CLAMP

LOOSE BATT INSULATION
WITHIN VAPOR JACKET.

SLOPE
SLOPE
SLOPE
W
L
L:W RATIOS FOR SADDLES AND CRICKETS
NOTE:

1. SADDLES SHOULD BE LOCATED
BETWEEN ROOF DRAINS.

ROOF
SLOPE

SADDLE MATERIAL
SLOPE
L:W
RATIO
1/4" 1/2" 3:1
3/8" 1/2" 3:1
1/2" 1/2" 4:1

07.43 6" MIN
8" MIN.

NOTE:

VENT STACKS AND

OTHER PIPES SHALL
HAVE A MIN OF 12" OF

CLEARANCE ON ALL

SIDES FROM WALLS,

CURBS, AND OTHER
PROJECTIONS.
1" MIN. RIGID INSUL,
WHERE
OCCURS

ROOF PENETRATION (STL

PIPE, TUBE, OR SIMILAR ITEM)

SS STL HOSE CLAMP WITH

SEALANT ALL AROUND

ROOFING MEMBRANE BOOT

FLASHING, HOT AIR WELD TO

BASE FLASHING

ROOFING MEMBRANE BASE

FLASHING, HOT AIR WELD TO

ROOF MEMBRANE

THERMOPLASTIC

MEMBRANE ROOFING

MTL ROOF DECK OR CONC FILLED

MTL ROOF DECK, SEE STRUCTURAL

PLANS FOR TYPE

END CLOSURE PL

PER STRUCTURAL
DETAIL 4 AND 5/S0.22

SEALANT, CONT,

PROVIDE BACKER

ROD AS REQ
5/8" ROOF
BOARD
8" MIN.

NOTES:

1. CURB SHALL HAVE A MIN
OF 12" OF CLEARANCE ON

ALL SIDES FROM WALLS,

CURBS, AND OTHER
PROJECTIONS.

2. PROVIDE PREFABRICATED

CORNER FLASHING AT ALL
CORNER CONDITIONS.

3. PROVIDE MIN 16 GA
FLASHING.

4. ALL EXPOSED FASTENERS

TO BE FULLY COVERED
WITH SEALANT.

TERMINATION BAR,
FASTENERS AT 8" OC

THERMOPLASTIC MEMBRANE

ROOFING

ROOFING MEMBRANE

FLASHING, HOT AIR WELDED

TO ROOF MEMBRANE

GALV FLASHING REGLET
5/8" ROOF BOARD
RIGID

INSULATION,
WHERE
OCCURS

BLOCKING, AS

REQUIRED

MTL ROOF DECK OR CONC

FILLED MTL ROOF DECK, SEE

STRUCTURAL PLANS FOR TYPE

SHEET MTL GASKETED
FASTENER, 12" OC MIN, TYP
WOOD
NAILER
DUCT

SHEET MTL

GASKETED
FASTENER, 12"

OC MIN, TYP

PREFABRICATED

CURB ASSY
WITH

INTEGRATED

CAP FLASHING

PACK WITH

FIBERGLASS

INSULATION

ALL AROUND

CONTINUOUS

SEALANT TOP

AND BOTTOM
GALV

FLASHING
CONT

SEALANT
CONT

SEALANT
SLOPE
SLOPE
SLOPE
SLOP E
SLOPE
SLOPE
2'-0"MIN CLR
W
L
L:W RATIOS FOR SADDLES AND CRICKETS
AND MIN. SADDLE/CRICKET SLOPE
NOTE:

1. SADDLES SHOULD BE LOCATED IN

VALLEY BETWEEN ROOF DRAINS, AND

CRICKETS SHOULD BE LOCATED ON
THE HIGH SIDE OF CURBS.

ROOF
SLOPE
SADDLE

MATERIAL
SLOPE
L:W
RATIO
1/4" 1/2" 3:1
3/8" 1/2" 3:1
1/2" 1/2" 4:1

CURBED PENETRATION

BUILT-UP SADDLE OR

CRICKET, SLOPE A MIN OF
1/2" PER FOOT

ROOF AND OVERFLOW
DRAIN, SEE DETAIL 01/-

BUILT-UP SADDLE OR

CRICKET, SLOPE A MIN OF
1/2" PER FOOT
08 A8.21 TYP.
0'-2"

WHERE OCCURS

BLOCK OUT AT CONC FILLED MTL DECK

THERMOPLASTIC

MEMBRANE ROOFING
MIN 5/8" ROOF BD

ROOFING MEMBRANE

FLASHING, HOT AIR WELDED TO

ROOF MEMBRANE, EXTEND

UNDER DRAIN CLAMP RING

ROOF AND OVERFLOW DRAINS,

PROVIDE UNDER DRAIN CLAMPS, REFER
TO PLUMBING DWGS FOR TYPE.

OVERFLOW DRAIN TO HAVE INSERT
STANDPIPE; 2" ABOVE FIN ROOF.

BARE MTL DECK, CONC FILLED

MTL DECK, WITH RIGID INSUL OR
CONC FILLED MTL DECK.

TAPERED RIGID INSUL

BARE MTL DECK OR

CONC FILLED MTL DECK

THERMAL INSULATION,

WHERE OCCURS

LOOSE BATT INSULATION

WITHIN VAPOR JACKET, TYP

UNDER DRAIN

CLAMP, TYP

HOT AIR WELD, TYP

HIGH DOMED SS

FASTENERS W/ SS BACKED
EPDM WASHER @ 18" OC

MECHANICAL EQUIPMENT,
REFER TO MECH. DWGS.

CONTINUOUS SEALANT
20 GA SHEET METAL

REGLET,

GALVANIZED

HIGH DOMED HOT DIP

FASTENERS W/ GALV

BACKED EPDM WASHER AT
12" OC MAX

STEEL BENT PLATE,

REFER TO STRUCT
DWGS

STEEL PLATE

PER STRUCT

METAL DECK

PER STRUCT

STEEL BEAM PER
STRUCT

ROOF BOARD OVER RIGID

INSULATION, WHERE

OCCURS CONDITION BARE METAL DECK

ROOFING MEMBRANE

FLASHING, HOT AIR

WELDED TO ROOF

MEMBRANE

THERMOPLASTIC

MEMBRANE ROOFING

SECUREMENT BAR AND

FASTENER BY ROOFING

MANUFACTURER
8" MIN

CONTINUOUS SEALANT

ROOFING MEMBRANE

FLASHING, HOT AIR WELDED

TO ROOF MEMBRANE
12" MIN
12" MIN
12" MIN
4" MIN
6" MIN
4" MIN
12" MIN
4" MIN
6" MIN

TPA MECHANICALLY FASTENED ROOF MEMBRANE

METAL DECKING PER STRUCTURAL

STEEL BEAM BEYOND PER STRUCTURAL
R-30 RIGID INSULATION
1/4" COVER BOARD

ADHERED TAPERED INSULATION,

WHERE OCCURS PER PLAN
HOT AIR WELD AT LAP, TYP.

OMG XHD #15 ROOFING FASTENER W/ 2 3/8"
BARBED STRESS PLATES FASTENED 12" O.C.

FOR FIELD SHEETS (6' WIDE) AND 6" O.C. AT
PERIMETER SHEETS (2 SHEETS, 3' WIDE). MIN.
3 THREADS ENGAGEMENT THROUGH METAL
DECK, TYP.

CONSTRUCTION SPECIALTIES
BRJW-800 CF JOINT

CONSTRUCTION SPECIALTIES

BASE CLOSURE

CONSTRUCTION SPECIALTIES
SC-800 JOINT

FIELD APPLIED SPLICE COVER

REGLET AND

COUNTERFLASHING

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

ROOF DETAILS
A8.21
MD
MONROE ST. POOL REPLACEMENT

ROOF DETAILS
12" = 1' -0"
A8.21 18 ROOF DRAIN AT SINGLE PLY

ROOFING SYSTEM
1/4" = 1' -0"
A8.21 03 TYPICAL ROOF CRICKETS AT SCUPPER AND COLLECTOR BOX 12" = 1' -0"
A8.21 14 TYP PIPE / PLUMBING VENT

PENETRATION AT MTL DECK ROOF
12" = 1' -0"
A8.21 12 DUCT PENETRATION THROUGH
ROOF
1/4" = 1' -0"
A8.21 10 TYPICAL ROOF SADDLES AND CRICKETS
1" = 1' -0"
A8.21 08 TYP ROOF AND OVERFLOW DRAIN SECTION
3" = 1' -0"
A8.21 15 FLASHING AT MECH PLATFORM
1" = 1' -0"
A8.21 09 TYP ROOF SPACING
3" = 1' -0"
A8.21 19 TYP. ROOF SECTION - METAL
DECK
1" = 1' -0"
A8.21 04 ROOF TO WALL JOINT TRANSITION
45 203
08/09/2024
203
0'-6" 1'-3" 1'-3" 0'-6"
MIN. MIN.
0'-6" 1'-6" 2'-0" 1'-6" 0'-6"

MEMBRANE

FLASHING, HOT AIR

WELDED TO SINGLE-

SINGLE PLY ROOFING
SYSTEM

OVERFLOW DRAIN
WITH 2" WATER DAM

ROOF DRAIN, SEE

LINE OF TAPERED

INSULATION
NOTES:

1. ROOF AND OVERFLOW DRAIN

LOCATIONS & CONFIGURATION

PER ARCHITECTURAL &
PLUMBING ROOF PLAN.
5'-0"
AT CONC.

MET. DECK
AT MET.

DECK

TPA MEMBRANE

HEAT WELDED LAP

TPA UNREINFORCED

MEMBRANE

TPA BONDING ADHESIVE

STAINLESS STEEL
CLAMP

TREMSEAL SEALANT

ROOF ASSEMBLY
REF:
#15 FASTENER w/2
3/8" BARBED STRESS

PLATES FASTENED

METAL CURB

COUNTERFLASHING

TPA MEMBRANE

TPA FLASHING MEMBRANE

FULLY ADHERED TO

VERTICAL SUBTRATE

HEAT WELDED LAP

TPA BONDING ADHESIVE
#15 FASTENER w/2 3/8"

BARBED STRESS PLATES
FASTENED @ 12" O.C.

ROOF ASSEMBLY
REF:

TPA MEMBRANE TO WRAP

OVER TOP OF CURB

SECURE ROOF CAP TO
ROOF CURB WITH #8 ALUM.

SELF TAPPING SCREWS 12"
O.C. MIN. 2 PER SIDE

STRUCTURAL STEEL, REFER
TO STRUCT. FRAMING PLAN

FASTENER PER
STRUCTURAL DRAWINGS.

REF: 09A/S6.91
CONT. BENT PLATE PER
STRUCTURAL DRAWINGS.

REF: 09A/S6.91
T.O. ROOFING
8" M
IN.

EXHAUST FAN. REF.

MECH. DRAWING
0'-7"
16 GA. METAL STUD BACKING
3/8" x 2" BENT STEEL PLATE
WELD TO VERTICAL @
4' -0" O.C. MAX. (PER OSHA)

INTERIOR FINISH
NOTE:

PROVIDE 16 GA. METAL

STUDS AT ALL WALLS

THAT ROOF ACCESS

LADDER IS ATTACHED
1" DIA. STEEL RUNGS @
12" O.C.
3/8" x 2" STEEL BARS
0'-10" 1'-0"
2 1/2" x 2 1/2" x 3/8"

METAL ANGLE
3/8" DIA. X 2 1/2" EMBED.

HILTI KB TZ2. (ESR 4266)
2'-0" CLR.
0'-7"
1" DIA. STEEL RINGS @ 12" O.C.

WELDED TO 3/8" x 2" STEEL RAIL

STEEL BENT PLATE LADDER
SUPPORT, ANCHORED TO 16 GA.

METAL STUD BACKING, 1/4" DIA.

HILTI KWIK FLEX @ EACH BRACKET

WALL TYPE PER PLAN
(MIN 6X16GA)

PLAN VIEW

SECTION
16GA BLOCKING
CONDENSING UNIT.

REF. MECH DRAWING

NEOPRENE ISOLATOR PADS

MECHANICAL

PLATFORM, REFER TO

STRUCTUAL

ANCHORAGE TABS ,

REFER TO MECHACNIAL

FOR ATTACHMENT
NOTE:

1. SEE STRUCTURAL DETAIL 15/S6.12 FOR PLATFORM DETA ILS.

TPA MEMBRANE

TPA FLASHING MEMBRANE

FULLY ADHERED TO

VERTICAL SUBTRATE

HEAT WELDED LAP

TPA BONDING ADHESIVE
#15 FASTENER w/2 3/8"

BARBED STRESS
PLATES FASTENED @
12" O.C.

ROOF ASSEMBLY
REF:

TPA MEMBRANE TO WRAP

OVER TOP OF CURB

STRUCTURAL STEEL, REFER
TO STRUCT. FRAMING PLAN
8" M
IN.
6" CONCEALED

SPLICE PLATE
AT EA. JOINT
2X SHAPED

PTDF WOOD

BLOCKING
T.O.

PARAPET

EXTERIOR CEMENT

PLASTER SYSTEM
SLOPE 1/2" PER FT.
20 GA. GALV. SHEET

METAL COPING,

PAINTED
CONT. CLEAT

METAL STUD

FRAMING PER

STRUCTURAL

SELF ADHERING

SHEET MEMBRANE

FLASHING
#12 P.H.S.M.S. FASTENER

WITH NEOPRENE
WASHER AT 12" O.C.
0'-3"
0'-4"

BLOCKING TO

PARAPET HEAD W/
#12 FLATHEAD SMS
W/ WASHER AT 16"
O.C. STAGGERED
0'-1" MIN. E.D.
0'-1" MIN. E.D.

T.O. PARAPET

PER ELEVATION

SHAPED HOLDOWN
CLEAT, TYP.
#10 SMS @ 16" O.C., TYP.

TPA MEMBRANE TO WRAP

OVER TOP OF BLOCKING
U937 FOR 1-HR RATED

CONDITION

METAL COPING CAP,
PAINTED P-2
0'-4"
MIN 1/2" : 1' 0" SLOPE

FIRE TREATED BLOCKING

AT WHERE REQUIRED
3/8" DIA. HILTI KB-TZ2
ANCHORS WITH 2" MIN.

EMBED @ 16" O.C. (ESR
4561), REFER TO S0.01,
SECTION G.1

STRUCTURAL STEEL, REFER
TO STRUCT. FRAMING PLAN

FASTENER PER
STRUCTURAL DRAWINGS.

REF:

CONT. BENT PLATE PER
STRUCTURAL DRAWINGS.

REF: 09A/S6.91
T.O. ROOFING
8" M
IN.

TPA MEMBRANE
22 GA. GALV. PAN

HEAT WELDED LAP

TPA UNREINFORCED MEMBRANE
#15 FASTENER w/2 3/8" BARBED
STRESS PLATES FASTENED @ 12" O.C.

ROOF ASSEMBLY
REF:

TPA MANUFACTURER APPROVED

SEALANT
S.S. HOSE CLAMP
3/16" ALUMINUM BRACKET @ 4'-0" O.C MAX.

BY MANUFACTURER
S.S. 3/8" DIA. HILTI KH -EZ BOLTS W/ 3 -1/4" EMBED.

CLR
1'-6" M
IN
(2) 1/4" DIA X 3/4" S.S HEX HEAD MACHINE
BOLT W/ NUT AND LOCK WASHER.
1-1/4" SQUARE ALUM. EXTRUDED

SERRATED RUNG
3" X1" X1/8" EXTRUDED ALUMINUM
CHANNEL RAIL ALLOY6063 -T5.
#12 X 1-1/2" HEX HEAD S.S SELF

TAPPING SCREW

EXTRUDED ALUMINUM
PLATE ALLOY 6063 -T5
CLR.
7" MIN. LINE OF ROOF HATCH
ABOVE
1'-2"
1'-2"
A8.22
14 8" M
IN

ROOF SYSTEM, SEE

ROOF PLANS FOR TYPE
CLR
0'-7"

SHEET MTL
SCREWS #12
AT 12" OC
16 GA BENT PLATE,
CONT ALL (4) SIDES,

TYP GALV, PT TO

MATCH ADJ SURFACE

WHERE EXPOSED TO
VIEW.

ROOF HATCH LADDER

STRUCTURAL STL -

REFER TO

STRUCTURAL DWG CONDITION AT

BARE METAL DECK

ROOF HATCH AND CURB ASSEMBLY WITH INTEGRAL
CAP FLASHING AND 1" RIGID INSULATION AROUND
CURB - SEE 16/A8.00

LADDER UP SAFETY POLE
STL RUNGS, 1" DIA x 24" @ 12" OC
0'-7"
NOTE:

ALL METAL TO BE PTD, COLOR:XXXX.
1'-0"
1'-0"
0'-10"
2'-0"
BENT PL, 3/8" x 2", WELD TO
VERT @ 6'-0" OC MAX
1/2" DIA HILTI KBTZ - 3 1/4"
MIN EMBED. EA SIDE OF

VERT STL BAR
0'-4"
0'-8 1/2"
1/4 TOP & BOTTOM
BENT PL 3/8" x 2", WELD TO
VERT @ 6'-0" OC MAX, TYP
CLR
0'-7"

PLAN VIEW AT SUPPORT
24" CLR

LINE OF WALL FINISH
(2) #12 SHEET MTL SCREWS
BACKING PER XX/XX.XX, TYP
MTL STUD FRAMING, SEE S0.91

LINE OF WALL FINISH
VERTICAL LADDER, 3/8" X
2" STL BARS

LINE OF FINISH FLOOR
8" M
IN

ROOF SYSTEM, SEE

ROOF PLANS FOR TYPE

ROOF HATCH LADDER

STRUCTURAL STL -

REFER TO

STRUCTURAL DWG

ROOF HATCH AND CURB ASSEMBLY WITH INTEGRAL
CAP FLASHING AND 1" RIGID INSULATION AROUND
CURB - SEE 16/A8.00

LADDER UP SAFETY POLE

EXISTING ROOF

COVERBOARD

EXISTING CMU

WALL PER PLAN
EXISTING 3" X 8"

CONNECTION ROOF

STRUCTURE PER

STRUCTURAL

DRAWINGS

EXISTING ROOF

STRUCTURE
T.O.B
BLDG A

NEW WOOD BLOCKING

NEW PLYWOOD CRICKET

FRAMING

NEW METAL COPING TO MATCH

REMOVED EXISTING COPING

EXISTING FASCIA BOARD
M
IN.
8"
ALIGN WITH FACE OF CMU 2"
3'-4"

ROOF SCREEN ANCHOR

FRAMING / FLASHING SYSTEM

BY MANUFACTURER

ROOF SCREEN AND FRAMING

SYSTEM BY MANUFACTURER
(V.I.F.)
+/- 4'-4 1/4"
ROOF

COVERBOARD

RIGID INSULATION

CRICKET

NEW CMU PARAPET

WALL PER PLAN

METAL COPING

CONNECTION TO

CMU PER

SCTRUCTURAL

DRAWINGS
T.O.P
BLDG B

STRESS PLY PLUS FR MATERIAL MODIFIED MEMBRANE
FLASHING PLY 9" MIN. [228mm] ON FIELD
BASE FLASHING PLY 6" MIN. [152mm] ON FIELD

STRESS PLY PLUS FR MATERIAL

MODIFIED MEMBRANE

FELT PLIES

INSULATION WHERE

OCCURS, STAGGER

ALL JOINTS, FASTEN PER

SPECIFICATION

FLASHING, SEE SPECIFICATION

COUNTER FLASHING SET IN JOINT

DENSDECK SHEATHING
ATTACH PER MFG. RECOMMENDATIONS (USE 3

COURSE MASTIC WITH MESH OVER FASTENERS)
8" MIN.

SELF ADHERING FLEXIBLE FLASHING MEMBRANE

UP PARAPET WALL, OVERLAPING COUNTER
FLASHING CLEAT 4" MIN.
4" CANT STRIP

WALL FINISH PER WALL TYPE
8" M
IN

CMU WALL PER PLAN

CONT BEAD OF SEALANT

SS STL GROMMETED
FASTENER AT 12" OC

TERMINATION BAR,
FASTENERS AT 8" OC

COMPRESSIBLE DBL

SIDED WP TAPE

COMPRESSIBLE DBL

SIDED WP TAPE

ROOFING MEMBRANE FLASHING, HOT

AIR WELDED TO ROOF MEMBRANE

THERMOPLASTIC MEMBRANE

ROOFING

SECUREMENT BAR AND FASTENER

BY ROOFING MFR

RIGID INSULATION / CRICKET,

WHERE OCCURS

MASONRY FLASHING

REGLET, GALV

CMU WALL

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

ROOF DETAILS
A8.22
MD
MONROE ST. POOL REPLACEMENT

ROOF DETAILS
1/2" = 1' -0"
A8.22 04 ROOF - OVERFLOW DRAIN
3" = 1' -0"
A8.22 3TYP PIPE PENETRATION
1 1/2" = 1' -0"
A8.22 10 UPBLAST EXHAUST FAN FLASHING
1" = 1' -0"
A8.22 09 ACCESS LADDER
1 1/2" = 1' -0"
A8.22 6CONDENSING UNIT ON

MECHANICAL PLATFORM
3" = 1' -0"
A8.22 03 PARAPET COPING AT STUD WALL
3" = 1' -0"
A8.22 06 PARAPET COPING AT CMU WALL
1 1/2" = 1' -0"
A8.22 13 AIR INTAKE ROOF PENETRATION
1 1/2" = 1' -0"
A8.22 08 INTERIOR PREMANUFACTURED
LADDER PLAN1
1" = 1' -0"
A8.22 12 ROOF HATCH AT METAL DECK
1" = 1' -0"
A8.22 7ROOF ACCESS LADDER
1" = 1' -0"
A8.22 11 ROOF HATCH AT METAL DECK
1" = 1' -0"
A8.22 14 MECHANICAL ROOF SCREEN
1" = 1' -0"
A8.22 15 MECHANICAL ROOF SCREEN @

PARAPET
3" = 1' -0"
A8.22 02 TYP. REGLET & COUNTER

FLASHING AT STUD WALL
3" = 1' -0"
A8.22 05 TYP REGLET & COUNTER

FLASHING AT CMU WALL
46 203
08/09/2024
203

BOTTOM OF STRUCTURE

CEILING SYSTEM, WHERE

OCCURS SEE REFLECTED

CEILING PLAN
(1) LAYER OF 5/8" TYPE "X"

GYP BD BOTH SIDES, UNO,

SEE FINISH PLANS AND

ELEVATIONS

METAL STUD FRAMING PER
NOTES

ACOUSTICAL INSULATION

WHERE OCCURS

LINE OF CONCRETE CURB

WHERE OCCURS

CONTINUOUS SEALANT , BOTH

SIDES, TOP AND BOTTOM

CONTINUOUS TRACK TO

MATCH STUD SIZE

BOTTOM OF STRUCTURE

CONTINUOUS SEALANT , BOTH
SIDES

CONTINUOUS TRACK TO

MATCH STUD SIZE

CEILING SYSTEM, WHERE

OCCURS SEE REFLECTED

CEILING PLAN
(1) LAYER OF 5/8" TYPE "X"

GYP BD BOTH SIDES, UNO,

SEE FINISH PLANS AND

ELEVATIONS

METAL STUD FRAMING PER
NOTES

ACOUSTICAL INSULATION

WHERE OCCURS
UNO
0'-6"TYP

LINE OF CONCRETE CURB

WHERE OCCURS

BOTTOM OF STRUCTURE

CEILING SYSTEM, WHERE

OCCURS SEE REFLECTED

CEILING PLAN
(1) LAYER OF 5/8" TYPE "X"

GYP BD BOTH SIDES, UNO,

SEE FINISH PLANS AND

ELEVATIONS

METAL STUD FRAMING PER
NOTES

ACOUSTICAL INSULATION

WHERE OCCURS

LINE OF CONCRETE CURB

WHERE OCCURS

CONTINUOUS SEALANT

CONTINUOUS TRACK TO

MATCH STUD SIZE

STRAP OR BRIDGING
UNO
0'-6"

DESCRIPTION CATEGORY

STEEL STUDS S

WOOD STUDS W
TYPE

CORE/ STRUCTURE SIZE
SA2

BOTTOM OF STRUCTURE

CEILING SYSTEM, WHERE

OCCURS SEE REFLECTED

CEILING PLAN
(1) LAYER OF 5/8" TYPE "X"

GYP BD , UNO, SEE FINISH

PLANS AND ELEVATIONS
METAL CHANNELS 16" O.C.

VERT

CONTINUOUS SEALANT
UNO
0'-6"

ADJACENT WALL PER PLAN
ANCHOR
0'-0 1/4"

CEILING SYSTEM, WHERE

OCCURS SEE REFLECTED

CEILING PLAN

BOTTOM OF STRUCTURE

CEILING SYSTEM, WHERE

OCCURS SEE REFLECTED

CEILING PLAN
(1) LAYER OF 5/8" TYPE "X"

GYP BD , UNO, SEE FINISH

PLANS AND ELEVATIONS

METAL STUD FRAMING PER
NOTES

ACOUSTICAL INSULATION

WHERE OCCURS

LINE OF CONCRETE CURB

WHERE OCCURS

CONTINUOUS SEALANT

CONTINUOUS TRACK TO

MATCH STUD SIZE
0'-6"

ADJACENT WALL PER PLAN

CEILING SYSTEM, WHERE

OCCURS SEE REFLECTED

CEILING PLAN

BOTTOM OF STRUCTURE

CEILING SYSTEM, WHERE

OCCURS SEE REFLECTED

CEILING PLAN
(1) LAYER OF 5/8" TYPE "X"

GYP BD BOTH SIDES, UNO,

SEE FINISH PLANS AND

ELEVATIONS

METAL STUD FRAMING PER
NOTES

ACOUSTICAL INSULATION

WHERE OCCURS

LINE OF CONCRETE CURB

WHERE OCCURS

CONTINUOUS FIRE CAULKING,

BOTH SIDES, TOP AND
BOTTOM

CONTINUOUS TRACK TO

MATCH STUD SIZE

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

PARTITION TYPES
A9.01
MD
MONROE ST. POOL REPLACEMENT

PARTITION TYPES
SA PARTITION TYPE "SA" SB PARTITION TYPE "SB" SE PARTITION TYPE "SE"

PARTITION TYPE TAG
SA Walls

WALL TYPE STUD SIZE
SA3 3 5/8" STUDS
SA4 4" STUDS
SA6 6" STUDS
SB Walls

WALL TYPE STUD SIZE
SB4 4" STUDS
SB6 6" STUDS
SE Walls

WALL TYPE STUD SIZE
SE3 3 5/8" STUDS
SE4 4" STUDS
3" = 1' -0"
A9.01 SF PARTITION TYPE "SF" (FURRED

PARTITION)
SF Walls

WALL TYPE CHANNEL SIZE
SF0 7/8" CHANNEL
3" = 1' -0"
A9.01 SG PARTITION TYPE "SG"
SG Walls

WALL TYPE STUD SIZE
SG2 2 1/2" STUDS
SG3 3 5/8" STUDS
SG4 4" STUDS
SG6 6" STUDS
3" = 1' -0"
A9.01 SN PARTITION TYPE "SN" (1HR)
SN Walls

WALL TYPE STUD SIZE
SN6 6" STUDS
47 203
08/09/2024
203

SEE WALL TYPE

DOOR OPENING

SEE SCHEDULE

DOOR - SEE
DOOR

SCHEDULE

HOLLOW METAL

FRAME AND

ANCHOR -

SEE DOOR

SCHEDULE
0'-0 1/2" 0'-0 1/2"
CMU
8" CMU, SEE

STRUCTURAL FOR

HORIZONTAL AND

VERTICAL

REINFORCING
1/2" SEALANT AND

BACKER ROD, BOTH
SIDES

DOOR AND FRAME,
AS SCHED.

EQ. 6" EQ.

REF. SCHEDULE FOR FINISH

CMU WALL, PER PLAN

HOLLOW METAL DOOR FRAME,

GROUT PACKED

DOOR ANCHOR TO CMU WALL,

ANCHOR STRAP & ADJUSTABLE HAT

SECTION PER FRAME MANUFACTURER

DOOR PER DOOR SCHEDULE
NOTE:

FOR FRAME ANCHOR, SEE

EXTERIOR INTERIOR
0'-2"

CONTINUOUS SEALANT AND

BACKER ROD BOTH SIDES

PARALLEL ARM, PUSH SIDE

MOUNTED DOOR CLOSER, TYP
7 3/4" MAX.
3/8" 1' - 10"

PORCELAIN
TILE

THIN SET
3/8" RADIUS BRUSHED

STAINLESS STEEL

SCHLUTER -DILEX -HKU
COVE AT BASE.

HKUR10EB
5/8" GYP. BD.

METAL STUD
1/8"
0'-0 1/2"
1' 9 1/2"TILE HEIGHT 0'-0 1/8" GROUT
0'-0 3/16"

WALL TILE, PER FINISH

SCHEDULE

WALL, PARTITION TYPE PER

FLOOR PLAN
0'-6"

COATED GLASS MAT WATER-
RESISTANT GYPSUM BACKER BD.

COVED BASE TRIM PIECE

FLOOR TILE PER FINISH PLAN
NOTE:

PROVIDE WATERPROOFING UNDER
TILE WORK, TYP. SEE

SPECIFICATIONS

WALL TILE PER FINISH PLANS

HOLLOW METAL DOOR FRAME

DOOR PER DOOR SCHEDULE

FRAME ANCHOR - SEE
0'-0 1/2" MAX.

WALL TYPE PER FLOOR PLAN
ALIGN
0'-2"

PACK WITH INSULATION

SEE PLAN FOR PARTITION TYPE

FULL WALL TILE PER FINISH PLAN

AND INTERIOR ELEVATIONS

SCHLUTER EDGE, TYP
STEEL PLATE, REFER TO 13/S6.72

METAL DECK

TOP TRACK PER STRUCTURAL DRAWINGS

MINERAL FIBRE INSULATION
MIN (2) FLUTES

SPECSEAL SMOKE 'N' SOUND SPRAY
GRADE, TYP. BOTH SIDES. PAINT TO
MATCH ADJACENT SURFACE.

TOP TRACK PER STRUCTURAL DRAWINGS

METAL DECK

METAL STUD

DO NOT FASTEN GYP BD TO TRACK (TYP)

SOUND INSULATION AS NOTED

SPECSEAL SMOKE 'N' SOUND SPRAY
GRADE, TYP. BOTH SIDES. PAINT TO
MATCH ADJACENT SURFACE.

WALL PARALLEL TO DECK BETWEEN FLUTES - AT SLIP CONNECTION. WALL PERPENDICULAR TO DECK - AT SLIP CONNECTION .

WALL TYPE PER PLAN
WALL PERPENDICULAR TO DECK - AT RIGID CONNECTION.
12 GA 'Z' CHANNEL FOR RIGID CONNECTION

SOUND BATT INSULATION AS NOTED

METAL DECK

MINERAL FIBRE INSULATION

SPECSEAL SMOKE 'N' SOUND SPRAY
GRADE, TYP. BOTH SIDES. PAINT TO
MATCH ADJACENT SURFACE.

WALL TYPE PER PLAN
WALL PARALLEL TO DECK - AT RIGID CONNECTION.

MINERAL FIBER INSULATION

FASTENER TYPE AND SPACING PER
13/S6.72

FASTENER TYPE AND SPACING PER
13/S6.72

METAL STUD

DO NOT FASTEN GYP BD TO TRACK (TYP)

SOUND INSULATION AS NOTED

WALL TYPE PER PLAN

FASTENER TYPE AND SPACING PER
13/S6.72

METAL DECK

SPECSEAL SMOKE 'N' SOUND SPRAY
GRADE, TYP. BOTH SIDES. PAINT TO
MATCH ADJACENT SURFACE.

MINERAL FIBER INSULATION

DO NOT FASTEN GYP BD TO TRACK (TYP)

SOUND INSULATION AS NOTED

WALL TYPE PER PLAN
FASTENER TYPE AND SPACING PER 13/S6.72

TO DECK
1/4" MAX.

TO DECK
1/4" MAX.
@ FRAMED GYP. CEILING

SEE RCP

CEILING HEIGHT

WALL PER PLAN
1/4 -20 x 1 -1/2" SELF DRILLING SELF

TAPPING SCREW WITH LOCK WASHER
(PROVIDE 1 SCREW AT EACH END
AND @ 48" O.C. INTERMEDIATE. 2
SCREWS MINIMUM EACH FIXTURE.)
MAX WEIGHT 5LBS PER LF.

KICKER AND CONNECTION TO DECK

SEE STRUCTURAL
600S162 -43 METAL STUDS
@ 16" O.C., TYP.

FOR SIZE & SPACING OF

STUDS, SEE SCHEDULE ON
5/8" GYP. BD.
0'-3"
12 S6.72
16 S6.72

BACKING TRACK PER

SEE RCP

CEILING HEIGHT

FOR SIZE & SPACING OF

STUDS, SEE SCHEDULE ON
5/8" GYP. BD.
16 S6.72

SURFACE MOUNTED LIGHT

FIXTURE PER LIGHTING
PLAN E3.00; FASTENED TO
PL WITH (8) 1/4" BOLT WITH

NUT AND WASHER
PL MATCHING STUD GAX32"
WIDE SPANNING MIN (3)
STUDS W/ #10 SCREWS @
12" O/C EA STUD
1".
3/8" X 3" WIDE BENT PLATE -

PAINT TO MATCH SHELVING

HEAVY -DUTY METAL CABINET
3/8" DIA. HILTI KH -EZ MASONRY
SCREWS W/ 3 -1/4" EMBED. (ICC
ESR #3056) (1) @ EA. LEG (4 MIN.

PER SHELVING UNIT)
(2) #10 S.M.S. PER ANGLE CLIP
T.O. CABINET
0'-2" 0'-3" 0'-1"
+6' - 6" A.F.F.
3/8" DIA. S.S. HILTI KH-EZ

MASONRY SCREWS W/
3-1/4" EMBED. (ICC ESR #
3056) @ 6" BELOW T.O. OF
EACH LOCKER. REFER TO
S0.01, SECTION G.1

LOCKER PER

SPECIFICATION

WALL TYPE PER PLAN
FIN. FLOOR
(WHERE OCCURS)
0'-6"
3/8" DIA. S.S. HILTI KH-EZ

MASONRY SCREWS W/
3-1/4" EMBED. (ICC ESR #
3056) @ 6" ABOVE B.O. OF
EACH LOCKER. REFER TO
S0.01, SECTION G.1
RIPPED 2x6 P.T. WOOD
BLOCKING TO 1"
MIN. (2) COUNTERSUNK
3/8" DIA. HILTI KH-EZ

MASONRY SCREWS W/
3-1/4" EMBED. (ICC ESR #
3056) @ 32" O.C. REFER
TO S0.01, SECTION G.1
CONT. 1x6 P.T.

WOOD BLOCKING
MIN. (2) COUNTERSUNK
3/8" DIA. HILTI KH-EZ

MASONRY SCREWS W/
3-1/4" EMBED. (ICC ESR #
3056) @ 32" O.C.
1/8" THICK GALVANIZED
STEEL PLATE. SEE

FOR DETAIL
3" MIN.
0'-2"
0'-2"
0'-8" MAX.
27" A.F.F.
3/8" DIA. HILTI KH-EZ
MASONRY SCREWS W/ 3-1/4"
EMBED. (ICC ESR #3056) (1) @
EA. LEG (4 MIN. PER SHELVING
UNIT)

CABINET PER SPECIFICATION

WALL TYPE PER PLAN
NOTES:

1. MOUNT ALL F.E.C. 18" CLEAR FROM DOR U.O.N. ON FL OOR PLAN

2. FIRE EXTINGUISHER TO BE 4A40B

3. FIRE EXTINGUISHERS NOT TO BE LOCATED IN PATH OF TRAVEL.

4. UL-RATED 3-A:40-B:C AT CHEMICAL STORAGE, PUMP RO OM, LOCKER ROOMS, AND WHERE INDICATED ON DRAWINGS.

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

INTERIOR DETAILS
A9.11
MD
MONROE ST. POOL REPLACEMENT

INTERIOR DETAILS
3" = 1' -0"
A9.11 02 DOOR HEAD AT CMU
3" = 1' -0"
A9.11 04 HEAD DETAIL
3" = 1' -0"
A9.11 05 DOOR HEAD - HOLLOW METAL
DOOR @ CMU WALL
6" = 1' -0"
A9.11 14 TILE COVE BASE
3" = 1' -0"
A9.11 11 TILE AT TOP AND BASE
3" = 1' -0"
A9.11 08 DOOR JAMB - HOLLOW METAL

DOOR AT TILE
6" = 1' -0"
A9.11 09 TILE @ CORNER
3" = 1' -0"
A9.11 03 NON-RATED WALL AT METAL DECK
1 1/2" = 1' -0"
A9.11 1RECESSED LINEAR WALL SLOT
LIGHT
1 1/2" = 1' -0"
A9.11 6RECESSED LINEAR WALL SLOT
LIGHT
3" = 1' -0"
A9.11 7METAL SHELVING ANCHORAGE @
WALL
3" = 1' -0"
A9.11 10 METAL LOCKER ANCHORAGE
3" = 1' -0"
A9.11 12 SURFACE MOUNTED FEC
48 203
08/09/2024
203
F550 INSIDE CORNER ALUMINUM TRIM

MOLDING, BY MARLITE OR EQUAL
F565 DIVISION ALUMINUM TRIM

MOLDING, BY MARLITE OR EQUAL
48"X 96" FIBERGLASS REINFORCED PANEL
BY MARLITE, P-199 BRITE WHITE
F560 STAINLESS STEEL OUTSIDE

CORNER GUARD ALUMINUM TRIM

MOLDING, BY MARLITE OR EQUAL

PER MFR PER MFR

PER MFR PER MFR
TYP. PANEL WIDTH
96"
10'-0" U.N.O. 0'-4"

FIBERGLASS REINFORCED PANEL,
(FRP) SEE FINISH SCHEDULE
F565 DIVISION ALUMINUM

TRIM MOLDING BY

MARLITE OR EQUAL
F570 EDGE ALUMINUM TRIM

MOLDING BY MARLITE OR
EQUAL @ TOP AND BOTTOM

OF PANEL

INTEGRAL EPOXY

COVED BASE, SEE
DETAIL 07/A9.41

WALL, SEE FLOOR

PLANS FOR WALL TYPE
F550 INSIDE CORNER ALUMINUM TRIM

MOLDING BY MARLITE, OR EQUAL
F560 OUTSIDE CORNER GUARD

ALUMINUM TRIM MOLDING BY
MARLITE OR EQUAL 03
A9.12
TYP.

WALL PER PLAN
5/8" GYP. BOARD.
1" ACOUSTIC PANEL. PREP
WALL TO RECEIVE LOW V.O.C.

ADHESIVE. SEE (AP-1) ON

FINISH SCHEDULE

FOR MOUNTING HEIGHT

SEE INTERIOR ELEVATION

FOR MOUNTING HEIGHT

SEE INTERIOR ELEVATION
0'-1"

DOOR, WHERE OCCURS

CARPET TILE

CONCRETE SLAB

CARPET / SEALED OR POLISHED CONCRETE

CONCRETE FLOOR

PER FINISH PLAN
1/4" MAX.

NOTE:

1. UNDERCUT ALL DOORS TO CLEAR FLOOR FINISH BY 1/4" EXCEPT AT RATED DOORS, U.O.N. IN DOOR SCHEDULE.

2. FOR FLOORING FINISHES WITH 1/4" OR LESS HEIGHT VARIANCE, PROVIDE TRANSITION STRIP AS INDICATED.
1 2

DOOR, WHERE OCCURS

RUBBER FLOORING,

REFER TO FINISH PLAN

CONCRETE SLAB

RUBBER FLOORING / SEALED OR POLISHED CONCRETE B
A

SEALED CONCRETE

PER FINISH PLAN

ALUMINUM SCHLUTER
RENO -U 6MM

ALUMINUM SCHLUTER
RENO -U 6MM, 2:1 MAX.

SLOPE
2 1
MAX.
1/2" MAX.

MAX.

FRAME BEYOND

DOOR, SEE DOOR

SCHEDULE

CHANGE FLOOR FINISHES AT

CENTER LINE OF DOORS,

TYPICAL

FINISHED FLOOR

PER PLANS
ARIZONA TILE "QTZ -2"

QUARTZ THRESHOLD

SET IN MASTIC

THIN SET TILE PER

FINISH PLANS
0'-0 1/2"
V.I.F.
0'-0 1/2"

RUBBER FLOORING / SEALED OR POLISHED CONCRETE C
1/4" MAX.
1/2" MAX.
2 1
MAX.

WALL FINISH AND

FRAMING PER PLANS

COVED RUBBER
BASE

WALL FINISH AND

FRAMING PER PLANS

STRAIGHT RUBBER
BASE
A (AT CONCRETE, TYP. @ BACK OF

HOUSE AREAS)
B
(AT CARPET, RUBBER &
WOOD FLOORING - U.N.O.)
4".

WALL FINISH AND

FRAMING PER PLANS

STRAIGHT RUBBER
BASE

C (AT RESILIENT FLOORING)

CMU WALL

NO BASE

D (AT CMU WALL)
4"
4"
WALL TYPE PER FLOOR PLAN;

WALL FINISH PER ELEVATION

GLASS BOARD, SEE INTERIOR

ELEVATIONS FOR LOCATIONS

AND CUSTOM SIZING

Z-BAR PER MANUFACTURER
@ 2' -0" O.C., 6" MAX. FROM
EDGE OF PANEL.

T.O. BOARD

SEE INTERIOR ELEVATION
#10 SMS @ 16"O.C.

TYP. BACKING REF:

MAX.
2'-0" O.C.

MAX.
6 " 1" X 1/2" 14 G.A. ALUMINUM
'L' ANGLE ALIGN BOTTOM
LEG W/ F.O. GLASSBOARD,
ATTACH W/ #10 SMS @16"
O.C. MITER AT CORNERS

PLAN DETAIL
1"
B.O. BOARD
SEE INTERIOR ELEVATION 1/2" 1" X 1/2" X 3" 14 G.A. ALUMINUM 'U'; ALIGN BOTTOM LEG W/ F.O. GLASSBOARD,
ATTACH W/ #10 SMS @16" O.C.

MAX.
6".
'TRU MOUNT' BY

MANUFACTURER ADHERED
TO GLASS IN FACTORY.
1/2" 1/2"
1/2"
1" X 1" X 1" 14 G.A. ALUMINUM 'U'; ALIGN
BOTTOM LEG W/ F.O. GLASSBOARD,
ATTACH W/ #10 SMS @16" O.C.
#10 SMS @ 16"O.C.

PRE TAPPED HOLE WITH
FLATHEAD SCREW @ 16" O.C.
1"
1/2".
1"
/- ---

SEE INTERIOR ELEVATION
1/2" THICK PLYWOOD, TYP.

MIRROR, REFER TO INTERIOR

ELEVATION FOR SIZES
HORIZONTAL FRENCH CLEAT, TYP.

MIRROR EDGE, D514BA BRITE
ANODIZED FINISH, DEEP NOSE 1/4"
ALUM. J-CHANNEL, TYP.

ATTACHMENT TO CMU
AT 16" O/C, TYP. CMU WALL PER PLAN
B. O. MIRROR

SEE INTERIOR ELEVATION
TYP. STAINLESS STEEL STUD
MOUNT W/ 1 -1/2" PROJECTED

SPACER W/ BLACK FINISH
1/4" THICK SHEET METAL

PAINTED W/ BLACK ENAMEL
PAINT. SEE INTERIOR

ELEVATION FOR MAP PATTERN

WALL PER PLAN

POSITIVLY FIX SCREWS TO

BACK OF PANEL, DRILL AND
TAP METHOD OR EQ.

U.N.O.
24" M
AX.
12" = 1' -0"
A9.12 03 FRP PANEL SECTION DETAIL
3/4" = 1' -0"
A9.12 08 FRP PANEL PLAN DETAIL
3" = 1' -0"
A9.12 05 ACOUSTIC PANEL ATTACHMENT
3" = 1' -0"
A9.12 01 TYP. INTERIOR FLOOR

TRANSITIONS
3" = 1' -0"
A9.12 09 RUBBER BASE (B-1)
6" = 1' -0"
A9.12 04 GLASSBOARD WALL SECTION
3" = 1' -0"
A9.12 07 MIRROR WALL - SECTION
3" = 1' -0"
A9.12 06 STUD MOUNTING

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

INTERIOR DETAILS
A9.12
MD
MONROE ST. POOL REPLACEMENT

INTERIOR DETAILS
49 203
08/09/2024
203

EQ EQ EQ EQ

LIGHT FIXTURE, TYP

TYPICAL ELEC DEVICE

SPEAKER MECH DIFFUSER
EQ EQ
NOTES:

1. CENTER DEVICE ON LIGHT FIXTURE OR MECH DIFFUSER WHERE OCCURS.

2. IN ACT CLGS, CENTER DEVICES IN CLG TILE, NO MORE THAN TWO DEVICES PER 2x4 TILE.

3. IN ACT CLGS, IF ONLY ONE DEVICE OCCURS, CENTER DEVICE IN TILE, BOTH DIRECTIONS.

4. WHERE MULTIPLE DEVICES OCCUR, CONSOLIDATE INTO ONE AREA WHERE POSSIBLE.

CONDITION AT ACT CEILING

CONDITION AT GYP CEILING

SEE RCP

FOR SIZE & SPACING OF

JOISTS, SEE SCHEDULE ON

CEILING PER PLAN

WALL AND FINISH PER PLAN

LIGHT FIXTURE PER ELECTRICAL /

LIGHTING PLANS
1/4 -20 x 1 -1/2" SELF DRILLING SELF

TAPPING SCREW WITH LOCK WASHER
(PROVIDE 1 SCREW AT EACH END
AND @ 48" O.C. INTERMEDIATE. 2
SCREWS MINIMUM EACH FIXTURE.)
3".

WALL TILE, WHERE OCCURS

PER PLANS

TYPE A PERIMETER STARTER WALLS,

GRID ATTACHED TO
(2) ADJACENT WALLS
(4) EACH 12 GA. SPLAY
WIRES (SEE NOTE #5)
12 GA. HANGER WIRES AT
4'-0" OC EACH WAY

ALONG MAIN RUNNERS
12 GA. HANGER WIRES AT 8"

FROM ALL WALLS AT ALL MAIN

RUNNERS & CROSS TEES

OPPOSITE FREE WALLS, NO
GRID ATTACHMENT - 1/2"
MIN. CLEAR

FIXTURES, SUPPORT PER NOTES

CROSS TEES
AT 24" OC
MAIN

RUNNERS
AT 48" OC

REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION
NOTES:

1. CLASSIFICATION OF CEILING GRID IS: HEAVY DUTY.

2. THESE PLANS AND SPECIFICATIONS ARE FOR CEILING S YSTEMS WHOSE WEIGH

INCLUDING AIR CONDITIONING GRILLES & LIGHT FIXTURES DOESN'T EXCEED FOUR (4) PSF HEAVIER SYSTEMS AND THOSE SUPPORTING LATERAL LOADS FROM PARTITIONS WILL REQUIRE SPECIAL DESIGN DETAILS.

3. SPLICES WILL NOT BE PERMITTED IN ANY HANGER WIRE S.

4. PROVIDE TRAPEZE OR OTHER SUPPLEMENTARY SUPPORT M EMBERS AT OBSTRUCTIONS TO MAIN HANGER SPACING. PROVIDE ADDITIONAL HANGERS,

STRUTS OR BRACES AS REQUIRED AT ALL CEILING BREAKS, SOFFITS OR DISCONTINUOUS AREAS. HANGER WIRES THAT ARE MORE THAN 1 IN 6 OUT OF PLUMB SHALL HAVE COUNTER-SLOPING WIRES.

5. PROVIDE SETS OF FOUR 12 GA. SPLAYED BRACING WIRE S ORIENTED 90 DEGREES FROM EACH OTHER AT THE FOLLOWING SPACING:

A. FOR SCHOOL BUILDINGS, PLACE SETS OF BRACING WIRE S NOT MORE THAN 12'x12' OC
B. PROVIDE BRACING WIRES AT LOCATIONS NOT MORE THAN 1/2 THE SPACING

GIVEN IN 'A' ABOVE FROM EACH PERIMETER WALL AND AT THE EDGE OF VERTICAL CEILING OFFSETS FOR BOTH SCHOOL AND HOSPITAL BUILDINGS.

6. FASTEN HANGER WIRES WITH NOT LESS THAN (3) TIGHT TURNS. FASTEN BRACING WIRES WITH (4) TIGHT TURNS. MAKE ALL TIGHT TURNS WITHIN A DISTANCE OF 3".

HANGER OR BRACING WIRE ANCHORS TO THE STRUCTURE SHALL BE INSTALLED IN

SUCH A MANNER THAT THE DIRECTION OF THE WIRE ALIGNS AS CLOSELY AS POSSIBLE WITH THE DIRECTIONS OF THE FORCES ACTING ON THE WIRE.

7. SEPARATE ALL CEILING HANGING AND BRACING WIRES A T LEAST 6 INCHES FROM ALL UNBRACED DUCTS, PIPES. CONDUIT, ETC. IT IS ACCEPTABLE TO ATTACH LIGHTWEIGHT ITEMS, SUCH AS SINGLE ELECTRICAL CONDUIT NOT EXCEEDING 3/4" NOMINAL DIAMETER, TO HANGER WIRES.

8. ATTACH ALL LIGHT FIXTURES TO THE CEILING GRID RU NNERS TO RESIST A HORIZONTAL FORCE EQUAL TO THE WEIGHT OF THE FIXTURES. ALL LIGHT FIXTURES SHALL BE ATTACHED SECURELY TO THE GRID WITH (4) SCREWS, ONE AT EACH CORNER OF THE FIXTURE.

9. FLUSH OR RECESSED LIGHT FIXTURES AND AIR TERMINA LS OR SERVICES WEIGHING LESS THAN 56 POUNDS MAY BE SUPPORTED DIRECTLY ON THE RUNNERS OF A HEAVY DUTY GRID SYSTEM BUT, IN ADDITION, THEY MUST HAVE A MINIMUM OF (2) 12 GA. SLACK SAFETY WIRES ATTACHED TO THE FIXTURES AT DIAGONAL CORNERS AND ANCHORED TO THE STRUCTURE ABOVE. ALL 4'x4' LIGHT FIXTURES MUST HAVE SLACK SAFETY WIRES AT EACH CORNER.

10. ALL FLUSH OR RECESSED LIGHT FIXTURES AND AIR TERMINALS OR SERVICES WEIGHING 56 POUNDS OR MORE MUST BE INDEPENDENTLY SUPPORTED BY NOT LESS THAN (4) TAUT 12 GA. WIRES EACH ATTACHED TO THE FIXTURE AND AT THE STRUCTURE ABOVE REGARDLESS OF THE TYPE OF CEILING GRID SYSTEM USED.

THE (4) TAUT 12 GA. WIRES INCLUDING THEIR ATTACHMENT TO THE STRUCTURE ABOVE MUST BE CAPABLE OF SUPPORTING FOUR TIMES THE WEIGHT OF THE UNIT.

11. SUPPORT SURFACE MOUNTED LIGHT FIXTURES BY AT LE AST TWO POSITIVE DEVICES

WHICH SURROUND THE CEILING RUNNER AND WHICH ARE EACH SUPPORTED FROM THE STRUCTURE ABOVE BY A 12 GA. WIRE. SPRING CLIPS OR CLAMPS THAT CONNECT ONLY TO THE RUNNER ARE NOT ACCEPTABLE. PROVIDE ADDITIONAL SUPPORTS WHEN LIGHT FIXTURES ARE 8 FEET OR LONGER.

12. SUPPORT PENDANT MOUNTED LIGHT FIXTURES DIRECTLY FROM THE STRUCTURE

ABOVE WITH HANGER WIRES OR CABLES PASSING THROUGH EACH PENDANT HANGER AND CAPABLE OF SUPPORTING FOUR TIMES THE WEIGHT OF THE FIXTURE.

ATTACH ALL LIGHT FIXTURES TO THE CEILING GRID RUNNERS TO RESIST A HORIZONTAL FORCE EQUAL TO THE WEIGHT OF THE FIXTURES. SPECIAL DETAILS ARE NECESSARY FOR THIS CONDITION AT THE CEILING GRID.

13. PROVIDE ALL REQUIRED COMPONENTS (INCLUDING APPR OVED CEILING GRID SEISMIC CLIPS) FOR "CEILING SEISMIC DESIGN" - CBC SECTION #1614A.1.21 (a) SJCG CLIP
08 A9.21
05 A9.21
10 A9.21

COMPRESSION STRUT

SCHEDULE

MAX LENGTH

OF STRUT
STRUT
8' -0"
3 5/8" x 25 GA
"C" - STUDS
SSMA

DESIGNATION
362S125 -18

STEEL STUD

COMPRESSION
STRUT;

SEE SCHEDULE
REMOVE

FLANGES

TO PROVIDE
TIGHT

FIT ON TOP OF

MAIN RUNNER
(2) #12 SMS
SCREWS

THROUGH MAIN

RUNNER &
STUD
WEB

MAIN RUNNER
10' -0"
2 - 1 5/8" x 25 GA
"C" - STUDS
SEE DET. BELOW
15' -0"
2-2 1/2" x 25 GA.
"C" - STUD
SEE DET. BELOW
20' -0"
2-3 5/8" x 25 GA.
"C" - STUD
SEE DET. BELOW

STEEL C STUDS

PER SCHEDULE
3/8" S -12 (12 GA.)
SCREWS AT 12" O.C.

AND 6" FROM ENDS.
162S125 -18
250S125 -18
362S125 -18
A
A

FOR ATTACHMENT TO
STRUCTURE, RE:

NOTES:

1. COMPRESSION STRUTS SHALL NOT REPLACE HANGAR WIRE.

2. CEILING TILE NOT SHOWN FOR CLARITY.

A9.30
07 MIN OPNG 22"x30"

DOUBLE STUD FRAMING, TYP
HINGE

STEEL FRAME

KEYLOCK & PULL

J MOLDING TYP

PAINTED GYP BD

HEAVY DUTY

CEILING GRID
SYSTEM
CLG. GRID CLIP

BOTH ENDS

CEILING LIGHT

FIXTURE
(2) #12 SLACK WIRES
@ DIAGONAL
LOCATIONS.
(4) #12 WIRES IF
MORE THAN 55 LBS.

LATERAL FORCE BRACING MEMBERS MUST BE SPACED A MINIMUM OF 6" FROM

ALL HORIZONTAL PIPING OR DUCT WORK THAT IS NOT PROVIDED WITH BRACING RESTRAINTS FOR HORIZONTAL FORCES. BRACING WIRES MUST BE ATTACHED

TO THE GRID & TO THE STRUCTURE IN SUCH A MANNER THAT THEY CAN SUPPORT A DESIGN LOAD OF NOT LESS THAN 200 LBS OR THE ACTUAL LOADS, WHICHEVER IS GREATER, WITH A SAFETY FACTOR OF 2.

NOTE: (4) NO. 12 GAUGE WIRES MUST BE SECURED TO
THE MAIN RUNNER WITHIN 2" OF THE CROSS RUNNER
INTERSECTION & SPLAYED 90 DEGREES FROM EACH
OTHER AT AN ANGLE NOT EXCEEDING 45 DEGREES
FROM THE PLANE OF THE CEILING.

CEILING PANEL

MTL STUD BLOCKING

WALL AND FRAMING

PER PLAN
7/8" SHADOW MOLD
OR WITHIN 1/4" OF THE

LENGTH OF THE END

TEE, WHICHEVER IS
LEAST
7/8" 3/4"
8" MAX OR WITHIN 1/4" OF

THE LENGTH OF THE END

TEE, WHICHEVER IS
LEAST.

ARMSTRONG 'BERC 2'
CLIP. ACCEPTABLE TO
IBC PER ESR-1308
MAIN "T" @ 48" OC
CROSS "T" @ 24" OC
12 GA HANGER WIRES AT
4'-0" OC EA WAY W/ 3
TIGHT TURNS IN 3"

SECURE WIRES TO

STRUCTURE

ABOVE, REFER TO
12 GA HANGER WIRES AT
4'-0" OC EA. WAY W/ 3
TIGHT TURNS IN 3"
AT METAL STUD WALL: #10
SMS, AT MASONRY WALL:
1/4" MASONRY SCREWS WITH
2-1/2" EMBED PER F/S0.01,
AT CONCRETE WALL:
1/4" CONCRETE SCREWS
WITH 2-1/2" EMBED PER
F/S1.O1
0'-8 1/256"MAX
A9.30
07 OR WITHIN 1/4" OF THE

LENGTH OF THE END

TEE, WHICHEVER IS
LEAST.
7/8"
12 GA HANGER WIRES AT
4'-0" OC EA WAY WITH 3
TIGHT TURNS IN 3"
MAIN "T" @ 48" OC
CROSS "T" @ 24" OC

CEILING PANEL

METAL STUD BLOCKING

SECURE WIRES TO

STRUCTURE ABOVE,

REFER TO

SHADOW MOLD
12 GA HANGER WIRES AT
4'-0" OC EA WAY W/ 3
TIGHT TURNS IN 3"

ARMSTRONG'S
'BERC 2' CLIP.

ACCEPTABLE TO
IBC PER ESR-1308

SCREW TIGHTENED

THROUGH MAIN RUNNER

WEB RESTRICTING

SEPARATION FROM WALL

MOLDING
AT METAL STUD WALL: #10
SMS, AT MASONRY WALL:
1/4" MASONRY SCREWS
WITH 2-1/2" EMBED PER
F/S0.01, AT CONCRETE
WALL: 1/4" CONCRETE
SCREWS WITH 2-1/2"
EMBED PER F/S1.O1
A9.30
07 8" MAX
8" MAX OR WITHIN 1/4"

OF THE LENGTH OF

THE END TEE,
WHICHEVER IS LEAST.

CEILING JOIST FRAMING
(2) #10x1 3/4" SELF TAPPING
SCREWS

STL STRAP
3" WIDE x 4" LONG x 10 GA MIN
10 GA HANGER WIRE WITH
MIN 3 TIGHT TURNS IN 1 1/2"

AT VERTICAL HANGER WIRE
0'-0 177/256"MAX

WALL, PER PLAN
AT MTL STUD WALL: #10 SMS, AT
MASONRY WALL:
1/4" MASONRY SCREWS WITH
2-1/2" EMBED PER F/S0.01
AT CONCRETE WALL: 1/4"
CONCRETE SCREWS WITH 2-1/2"
EMBED PER F/S0.01
STL STRAP 3" WIDE x 4" LONG x
10 GA MIN
10 GA HANGER WIRE WITH
MIN 3 TIGHT TURNS IN 1 1/2"

AT SPLAYED WIRE
M
AX
0'-0 177/256"

AT VERTICAL HANGER WIRE

MTL STUD WALL FRAMING
AT MTL STUD WALL: #10 SMS,
AT MASONRY WALL: 1/4"

MASONRY SCREWS WITH
2 -1/2" EMBED PER F/S0.01 AT
CONCRETE WALL: 1/4"

CONCRETE SCREWS WITH
2 -1/2" EMBED PER F/S0.01
STL STRAP 3" WIDE x 4"
LONG x 10 GA MIN
10 GA HANGER WIRE WITH
MIN 3 TIGHT TURNS IN 1-1/2"
MAX
0'-0 177/256"
NOTE:

AT MTL STUD WALLS,
PROVIDE BACKING AS REQ.
12 GA VERTICAL HANGER WIRE
AT 4'-0" EA WAY WITH MIN 3
TIGHT TURNS IN 3" BOTH ENDS
OF WIRE, TYPICAL.

COMPRESSION STRUTS REQ

AT EA SET OF BRACING

WIRES, TYP ATTACH

COMPRESSION STRUT TO
MAIN RUNNER WITHIN 2" OF
CROSS RUNNER.
(4)-12 GA SPLAYED WIRES 90

DEGREES APART HORIZ WITH
MIN 4 TIGHT TURNS IN 1-1/2"
BOTH ENDS OF WIRE TYPICAL.

WIRES SHOULD BE TAUT

WITHOUT CAUSING THE

CEILING TO LIFT- NO SPLICES
PERMITTED.
45° MAX

VERT TYP
2" MAX. FROM BRACING

WIRES TO CROSS

RUNNERS

MAIN RUNNER

CROSS RUNNER
COMPRESSION STRUTS: STL
SECTION WITH L/R RATIO OF 200

MAX COMPRESSION STRUT SHALL

NOT REPLACE HANGER WIRE,

REFER TO
NOTES:

1. FOR CONNECTIONS OF BRACING & HANGER WIRES TO THE

STRUCTURE ABOVE, REFER TO
A9.30
08 A9.30
10 #12 GA. VERTICAL WIRE NOTE: 1/8" POP RIVET @

ALL MEMBERS ON WALL
CLR.
0'-8"
CLR.
0'-8"

MAIN RUNNER OR CROSS T

HORIZONTAL STRUT

TYPICAL CONTINUOUS ACOUSTICAL BOARD

WALL ANGLE
PROVIDE 1/2" SPACE

OPPOSING WALL
VERT. STRUT FASTENED TO MAIN

RUNNER-EXTEND AND FASTEN TO

UNDERSIDE OF STRUCTURE ABOVE
12'-0" O.C. IN BOTH DIRECTIONS WITH
THE FIRST POINT WITHIN 6'-0" FROM
EACH WALL PER ASTM #C635 AND
#C636 AND CHAPTER 23 OF THE
CALIFORNIA BUILDING CODE.
# 12 HANGER WIRE A 4'-0"
O.C. IN BOTH DIRECTIONS

ALL HANGER AND SPLAY

WIRES TO HAVE A MINIMUM
OF 3 TURNS IN 1" RUN.
#12 GA. SPLAY WIRE BRACING

IN PLANE OF EACH RUNNER
VERTICAL ANGLE = 45 (12'
O.C. IN BOTH DIRECTIONS /
144 SQ.FT. MAX.) START
WITHIN 4'-0" OF WALL.

MAIN RUNNER

CROSS TEE
NOTE: CONTRACTOR TO FIELD VERIFY EXISTING CONDITION WHERE EXISTING GRID OCCURS AND MAINTAIN FLOATING VS. FIXED AT ADJACENT GRID.

TYP.
45 º
0'-6"

MTL STUD KICKER

PER STRUCTURAL
EXTEND GYP BD 6"

ABV ADJ CLG

SEE RCP

ALIGN FACE OF CLG

PANEL WITH FACE

OF GYP BD

WALL ANGLE

AT TRANSITION

CORNER BEAD (TYP)

CLG OR SOFFIT JOISTS,

SEE STRUCTURAL

DRAWINGS

SEE RCP
1/2" = 1' -0"
A9.21 14 TYPICAL DEVICE LAYOUT

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

CEILING DETAILS
A9.21
MD
MONROE ST. POOL REPLACEMENT

CEILING DETAILS
3" = 1' -0"
A9.21 11 PERIMETER SLOT LIGHT @

RESTROOMS
6" = 1' -0"
A9.21 02 CEILING REQUIREMENTS1
1/2" = 1' -0"
A9.21 04 COMPRESSION STRUT
1 1/2" = 1' -0"
A9.21 06 HORIZONTAL ACCESS PANEL1
12" = 1' -0"
A9.21 09 LIGHT FIXTURE AT ACT
3" = 1' -0"
A9.21 05 OPP WALL OF STARTER WALL

REVEAL EDGE
3" = 1' -0"
A9.21 08 PERIMETER STARTER WALL -
SHADOW
6" = 1' -0"
A9.21 8SEISMIC BRACING CONNECT. TO
CLG
6" = 1' -0"
A9.21 12 SEISMIC BRACING CONNECT. TO
WALL
12" = 1' -0"
A9.21 10 SPLAY BRACING DETAIL1
3/4" = 1' -0"
A9.21 15 SUSPENDED CEILING GRID
3" = 1' -0"
A9.21 16 CEILING TRANSITION
50 203
08/09/2024
203
VARIES

FINISH PLUG TO MATCH

CABINET INTERIOR FINISH

STUD WALL
1x4 WALL CLEAT WITH NO. 10 x 2" SELF

TAPPING SHEET METAL SCREWS INTO
METAL STUDS OR BLOCKING. ATTACH
CABINET TO CLEAT WITH NO 8 x 1 1/4"
WOOD SCREWS @ 16" O.C. (TYP.)

DETAIL E
(METAL ANCHORAGE)

DETAIL D
(BLOCKING)
VARIES

DOOR OR EDGE OF OPENING
BLOCKING 2x
#6 FHWS @ 12" OC W/ 1 -1/2"
EMBED
#10 FHPH 3" COUNTERSUNK,
MIN 4" FROM EA END & 16" OC
2x4 WOOD SUPPORT
3/8" DIA. HILTI KWIK -BOLT TZ
(ICC -ESR 1917) W/ 2"
EMBEDMENT, LOCATE 4" FROM
EA END AND 24" OC
#10 FHPH COUNTERSUNK
SCREWS X 2 -1/2", MIN 2" FROM
EA END & 16"OC PROVIDE

PLASTIC CAP TO MATCH

COLOR OF PLAM
#10 FHPH COUNTERSUNK
SCREWS X 2 -1/2", MIN 2" FROM
EA END & 16"OC PROVIDE

PLASTIC CAP TO MATCH

COLOR OF PLAM
3/8" DIA. HILTI KWIK -BOLT TZ
(ICC -ESR 1917) W/ 2"
EMBEDMENT, LOCATE 4" FROM
EA END AND 24" OC
#10 FHPH 3" COUNTERSUNK,
MIN 4" FROM EA END & 16" OC
BLOCKING 2X4 CONTINUOUS,
PTDF
BLOCKING 2X4 CONTINUOUS,
PTDF
3/4" PLYWOOD CABINET RAIL
TYPE 1 -M-2 CABINET SIDE METAL BACKING CHANNEL
PER
#10 FHPH SELF TAPPING
SCREWS. SHEET METAL

SCREWS INTO BLOCKING OR
METAL STUDS @ 24" OC MIN
(2) SCREWS IN EACH

DIRECTION
GWB
3/4" PLYWOOD CABINET

INTERIOR
0'-6"
W.I. DESIGN SERIES

SEE INTERIOR ELEVATIONS

SEE ELEVATION VARIES
W.I. DESIGN SERIES

SEE INTERIOR ELEVATIONS

SEE ELEVATION

SEE ELEVATION

ADJUSTABLE SHELVES

CABINET W/ LOCK

LINE OF BOTTOM SHELF

LIGHT FIXTURE, WHERE OCCURS

HORIZONTAL MOUNTED PULLS, TYP

MATCH DOOR HARDWARE FINISH

BACKSPLASH, WHERE OCCURS,

SEE ELEVATION

DRAWERS, SEE ELEVATION
COUNTERTOP NOT TO EXCEED 1/2"

AT CABINET EXPOSED ENDS

ADJUSTABLE SHELF

BREAK AT ACCESSIBLE SINK DOORS -

PROVIDE FULL DOOR SWING,

INCLUDING TOE KICK
AT EXPOSED ENDS:

PROVIDE A 2" RECESS

BASE, SEE FINISH PLAN

ELEVATION A

FINISHED FLOOR

FINISHED CEILING
(SEE REFLECTED CEILING PLANS)
0'-2"

DRAWER ON FULL EXTENSION HEAVY

DUTY GLIDES, WHERE OCCURS, SEE

ELEVATION

SECTION B

LOWER CABINET

WITHOUT DRAWER

LOWER CABINET

WITH SINK

COUNTERTOP
ONLY
VARIES
0'-6"
@CMU

AND CONCRETE
GENERAL NOTES:

1. SEE SPECIFICATION SECTIONS 064000 & 064116.

2. CONSTRUCTION SHALL BE PER THE ARCHITECTURAL WOOD WORK INSTITUTE (WI) STANDARDS, LATEST EDITION.

3. FINISH PER PLANS, SCHEDULES, AND LEGEND.

4. WHITE THERMALLY FUSED MELAMINE AT CONCEALED INTE RIOR OF CABINETS, UNO

5. AT SINKS, WHEN DOORS OPEN 90° PROVIDE FOR 32" MI N CLEAR BETWEEN KICKS. SEE CBC SECTION 11B-603.3 FOR KNEE CLEARANCE.

6. NO SHARP OR ABRASIVE SURFACES UNDER SINK.

7. ALL JOINTS TO BE CAULKED WITH CLEAR SILICONE CAU LK.

8. WRAP HOT & COLD WATER SUPPLIES AND DRAIN PIPING W/ PVC INSULATION MATERIAL COMPLIANT WITH ASTM E84-07, 25 FLAME / 450 SMOKE INDEX.

9. INSTALL SECURE BACKING AT ALL THREE SIDES OF COU NTER.

10. 2x4 #1 DOUGLAS FIR LEDGER BACK & SIDE WALLS.

11. LOWER CABINET WITH SINK
A. INSULATE ALL EXPOSED HOT WATER AND DRAIN LINES U NDER SINK.

B. SEE CBC SECTION 11B-603.3 FOR KNEE CLEARANCE.

C. AREA HATCHED BELOW SINK SHALL BE ACCESSIBLE & CL EAR.

D. FAUCET CONTROLS TO BE LEVER OR A TYPE NOT REQUIR ING GRASPING, PINCHING, OR TWISTING OF THE WRIST W/ 5 LBS FORCE MAX TO OPERATE. (LOWER CABINET WITH DRAWER SHOWN)

VARIES, SEE

FINISH PLANS

SECTION C
(TALL CABINET)
54" MAX

SEE ELEVATIONS

VARIES, SEE

FINISH PLANS

CABINET W/ LOCK
0'-6"
E
DETAIL
TYP
F
DETAIL
TYP
D
DETAIL
TYP
E
DETAIL
TYP
F
DETAIL
TYP
F
DETAIL
TYP
E
DETAIL
TYP
E
DETAIL
TYP
F
DETAIL
TYP
D
DETAIL
TYP
XXX
X
A9.31
12 A9.31
12 A9.31
17/21

PLASTIC LAMINATE CABINET
DOOR

PLASTIC LAMINATE

ADJUSTABLE SHELF

PLASTIC LAMINATE FIXED

SHELF TYP

PLASTIC LAMINATE DOOR
STOP

RECESSED HEAVY DUTY

ADJUSTABLE SHELF

SUPPORTS WITH SHELF CLIPS

DOOR PULL , TYP - MATCH

DOOR HARDWARE FINISH,
UNO

DRAWER PULL

LIGHT FIXTURE , WHERE
OCCURS

VERIFY DIMENSION WITH

LIGHT FIXTURE

PLASTIC LAMINATE
ADJUSTABLE SHELF , TWO (2)

PLASTIC LAMINATE CABINET
DOOR
6" MAX

COUNTERTOP, SEE

ELEVATION

BACKSPLASH, WHERE

OCCURS, SEE ELEVATION

PLASTIC LAMINATE DOOR

STOP, TYP

CABINET DOOR PLASTIC

LAMINATE
ONE (1) PLASTIC LAMINATE

ADJUSTABLE SHELF

RECESSED HEAVY DUTY

ADJUSTABLE SHELF

SUPPORTS WITH SHELF CLIPS

DOOR PULL , VERTICAL

ORIENTATION AT TALL

CABINETS , TYP - MATCH

DOOR HARDWARE FINISH,
UNO

WALL FRAMING AND FINISH
PER PLAN SEE WALL TYPES.

FINISH PER SCHEDULE

RECESSED HEAVY DUTY

ADJUSTABLE SHELF

SUPPORTS WITH SHELF CLIPS
4" TAB PULLS, BRUSHED CHROME
MAX.
2'-0"
0'-1 1/2" TYP 0'-0 1/8" TYP

PROVIDE EXTERIOR GRADE
3/4" PLYWOOD MDF AT ALL

WET SINK LOCATIONS
0'-0 1/2" MAX

CABINET DOOR

WHERE OCCURS

DRIP EDGE AT WET SINK
LOCATIONS (1/8" RADIUS)

QUARTZ COUNTERTOP PER
PLAN

WALL PER PLAN
3/4" STONE MATERIAL, MITERED

CORNER, FILL AND SEAL SEAMS

ALL EQUAL

HEIGHT & QTY PER ELEVATION
FIXED
SHEVLES, TYP.

LOCK,

TYPICAL

WALL PER
PLAN

FINISH FLOOR

SEE ELEVATION FOR LOCKER CABINET

DESIGN, SPACING, QTY, AND DIMENSIONS

ACCESSIBLE
LOCKER
A9.31
01 PER RCP

SOFFIT PER RCP &

ELEVATION

TO OPERABLE PART
15" M
IN.

ACCESSIBLE
LOCKER
4"

TO OPERABLE PART
48" M
AX.

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

CASEWORK

DETAILS
A9.31
MD
MONROE ST. POOL REPLACEMENT

CASEWORK DETAILS
3" = 1' -0"
A9.31 01 CABINET ANCHORAGE
1" = 1' -0"
A9.31 02 TYPICAL UPPER/LOWER CABINETS
12" = 1' -0"
A9.31 10 QUARTZ COUNTERTOP
1" = 1' -0"
A9.31 13 LOCKER SECTION @ WALL
1 2nd PLAN CHECK

SUBMITTAL
04/24/24
51 203
08/09/2024
203

CABINET INTERIOR

METAL BACKING
PER
#10 x 2" SELF TAPPING SCREWS.

SHEET METAL SCREWS INTO
BLOCKING OR METAL STUDS @
24" O.C. MIN. (2) SCREWS IN

EACH DIRECTION

FINISH PLUG TO

MATCH CABINET

INTERIOR FINISH

STUD WALL
GYP.

BOARD

BASE PER FINISH

PLANS & ELEVATIONS

FINISH FLOOR
DOUBLE 16 GA. METAL STUDS AT

ANGLE SUPPORT
2" X 2" X 1/4" FLAT STEEL ANGLE AT
48" O.C. MAX. MIN. 2 - ATTACH TO
STUD OR HSS POST WITH #12 SMS
@ 6" O.C. PAINT TO MATCH WALL

FINISH/COLOR

BACKSPLASH WHERE

OCCURS - SEE ELEVATION

COUNTERTOP PER

FINISH PLANS

WALL FINISH PER PLAN

1. CONSTRUCTION SHALL BE W.I.C. 'CUSTOM' STANDARDS. FINISH PER FINISH PLANS AND LEGEND.

NOTES:

2. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES BELOW THE COUNTER.

EASED EDGE
U.N.O. ON PLANS
2'-0"
U.N.O.
1'-6" MIN.
0'-0 3/4"
0'-1 1/2"
(34" MAX. @ ACCESSIBLE STATION)

SEE ELEVATION
27" MIN. CLR.
2'-0" U.N.O.

WALL FINISH PER INTERIOR

ELEVATION AND FINISH
LEGEND

MITER AND BUTT WELD

RECYCLE SYMBOL ON METAL COIN

ROUTE PLASTIC LAMINATE TO

ACCEPT METAL COIN WITH
SYMBOL. SKU#: 1010 -2
TRASH SYMBOL ON METAL COIN.
2" 2"

1. BLOCK & ANCHOR EACH SIDE OF CABINET
3/4" TYPE 1 -M-2

PARTICLE BOARD
(CABINET SIDE)
#10 x 2 1/2" RHWS
@ 6" O.C.
1/2" HARDWOOD CABINET RAIL
2"x4" WOOD BLOCKING

CONTINUOUS
.145 DIA. LOW VELOCITY
FASTENERS (1 1/8" EMBED) ICC #
2269
@ 24" O.C. MIN (2 PER CABINET)
(3) #10 x 3" RHWS @ 6"
O.C.

NOTE:
3"
6"
3"
1'-0" 6" 6"
1' -0"
VARIES

FULL HEIGHT OF DESK

METAL STUD
1" X 1/2" DIAMETER MACHINE BOLT.

CONNECTION (TYPICAL) HEAD &

WASHER ON FRAMING BEYOND
2 1/2" x 2 1/2" x 1/4" ANGLE @ EACH

FREESTANDING END
(2) 1/2" DIA MECHANICAL FASTENER
(PER F/S1.01) - MIN 3 1/2" EMBED

CONTINUOUS

FLOOR RUNNER

COUNTERTOP WITH MITERED
EDGES PER SCHEDULE. SEE

INTERIOR ELEVATION

BASE TO MATCH MILLWORK
FINISH
4"

HAFELE DRAWER SLIDE-OUT
DOUBLE WASTE BIN - (2) X 40
LITER, US CARGO 21, SIDE
MOUNTED, SILVER #502 74 252.
21" MIN. WIDTH AS REQ'D.

DOOR MOUNT BRACKET
RECESSED 2" DIA.

STAINLESS STEEL DISK

WITH ROUTED TRASH
& RECYCLE GRAPHIC
3"
4" TAB PULL HARDWARE PER

SPECIFICATIONS
MIN.
1'-10 1/2" CLR.

A9.32
05 U.O.N.
2'-0" CLR.
1 1/4"

SEE ELEVATION
3"
NOTES:

1. SEE FINISH PLAN FOR FINISHES

2. CONST. SHALL BE 3/4" PART BD. WITH P. LAM. ON EX POSED SURFACES, INT.

SURFACES SHALL BE BLACK MELAMINE, U.O.N.

BACKSPLASH PER SCHEDULE
(WHERE OCCURS) SEE

INTERIOR ELEVATION
NOTES:

1. TRASH & RECYCLE LOGOS ONLY, U.N.O.

2. SEE INTERIOR ELEVATIONS FOR TRASH/RECYCLE CABINE T LOCATIONS

3. 1/18" X 2" DIAMETER BRUSHED ALUMINUM DISKS W/ BE AD BLASTED AND BLACK FILLED. RECESS FLUSH WITH FACE OF CABINET DOOR. MFR: ARCHITECTURAL HARDWARE. WEBSITE WWW.ARCHHARDWARE.NET. SKU#: 1010- 2
EQ EQ
O.C.
5 "
EQ EQ
O.C.
5 "
TRASH,

OR RECYCLE ONLY

COMBINED

TRASH AND

RECYCLE
A9.32
05 EQ EQ

PANTRY/ LONG

CABINET DOOR

UPPER CABINET
DOOR

LOWER CABINET
DOOR
DRAWER
NOTES:

1. LOCATE HARDWARE AS NOTED IN DETAIL, TYPICAL THRO UGHOUT

2. TYP. CABINET DOOR & DRAWER PULLS, SEE INTERIOR E LEVATIONS FOR CABINET TYPES PER N.A.A.W.S.

3. SEE SPEC FOR HARDWARE FINISH, BLACK FINISH U.N.O .

QUARTZ SURFACE
SEE INT. ELEV.

WALL PER PLAN
A9.32
09 QUARTZ COUNTERTOP
PER FINISH PLAN. MITER
CORNER, TYP.

CONCRETE FLOORING

PER FINISH PLAN

CONCEALED IN -WALL

BRACKET
CABINET WHERE OCCURS.

SEE INT. ELEV.

GROMMET AS REQUIRED
(MIN. 2 AT RECP. DESK)

POWER OUTLET

WHERE OCCURS
3"

PER ELEVATION

QUARTZ SURFACE
SEE INT. ELEV.

QTZ TRANSACTION

COUNTER BEYOND

QUARTZ SURFACE
SEE INT. ELEV.

WALL PER PLAN
A9.32
09 QUARTZ COUNTERTOP
PER FINISH PLAN. MITER
CORNER, TYP.

CONCRETE FLOORING

PER FINISH PLAN

CONCEALED IN -WALL

BRACKET

MOBILE STORAGE, OFOI

GROMMET AS REQUIRED
(MIN. OF 2 GROMMETS)

POWER OUTLET

WHERE OCCURS
3"

PER ELEVATION
9"
2X4 WOOD FRAMING, 16" O.C
WOOD FRAMING, 16" O.C
1'-0"

QTZ TRANSACTION COUNTER

RETUNR BEYOND

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

CASEWORK

DETAILS
A9.32
MD
MONROE ST. POOL REPLACEMENT

CASEWORK DETAILS
3" = 1' -0"
A9.32 13 ANCHORAGE AT METAL STUD
1" = 1' -0"
A9.32 18 TYP. COUNTER SUPPORT (AS
REQ'D.)
12" = 1' -0"
A9.32 05 PULL-OUT COIN
3" = 1' -0"
A9.32 09 CABINET ANCHORAGE1
1 1/2" = 1' -0"
A9.32 14 BRACING @ FREE STANDING LOW
WALLS
1" = 1' -0"
A9.32 17 PULL-OUT TRASH
6" = 1' -0"
A9.32 21 TRASH / RECYCLE EMBLEM
6" = 1' -0"
A9.32 22 CABINET HORIZONTAL PULL
1 1/2" = 1' -0"
A9.32 23 RECEPTION DESK - LOW
1 1/2" = 1' -0"
A9.32 24 RECEPTION DESK - TRANSACTION
52 203
08/09/2024
203

TOILET PARTITION

ANODIZED

ALUMINUM ANGLE

WALL PER PLAN

BACKING PER
1/4" SMS EA. SIDE W/
RUBBER WASHER @ 48"
O.C. MAX.

BACKING PER
1 1/2" STD. PIPE GRAB BAR W/

MOUNTING CONCEALED PLATE

ANCHOR MOUNTING

PLATE TO BACKING
PLATE W/ (3) - #12
S.M.S.
5/8" GYPSUM BOARD

STUD WALL

GRAB BAR COLLAR
1 1/2" CLR.
1 1/2" STD. PIPE GRAB BAR W/

MOUNTING CONCEALED PLATE

ANCHOR MOUNTING

PLATE TO BACKING
PLATE W/ (3) - #12
S.M.S.

STUD WALL

GRAB BAR COLLAR
1 1/2" CLR.

PLAN

WALL PER PLAN

START FULL TILE

BEHIND TILE ON

ADJACENT SURFACE

LINE OF TOILET

PARTITION

WHERE OCCURS
ANOD. ALUM. CORNER

TRIM - EXTEND TO TOP

OF TILE - SCHLUTER
'INDEC'
FASTENER LOCATION, TYP.

NOTES:

USE 1/4" x 3" PANHEAD TAPPING SCREWS AT FASTENER LOCATIONS. PRIOR TO FASTENING, DRILL W/ 1/2" MASONRY BIT AND INSTALL FASTENERS W/

TOGGLES PER MANUFACTURER INSTRUCTIONS

FLOOR DRAIN
2' - 0"
2' - 0"
.
.
. .

FLOOR FINISH PER FINISH PLANS
2% SLOPE,
TYP.MAX.

EQ EQ
EQ EQ
+0' - 0" A.F.F. AT 4 SIDES & CORNERS
-0' - 1/4" AT DRAIN
.
..

PLAN @ CONCRETE FLOOR SECTION @ FINISHED CONCRETE FLOOR

FLOOR FINISH PER FINISH PLANS

OPENINGS
1/4" MAX.

SEALANT
S.S. FLOOR DRAIN

CONCRETE SLAB
N.T.S.

FLOOR DRAIN WITH
STRAINER, RE:

PLUMBING
(MAX. 1/4" OPENINGS)

SEALANT

WATERPROOFING MEMBRANE

CONCRETE
(SLOPED TO DRAIN)

CONCRETE

SLAB ON
GRADE

1. FOR ADDITIONAL INFORMATION SEE F101 (TCA HANDBOOK).

NOTE:

SLOPE
2% MAX. TYP.
6"

CONCRETE

SLAB ON
GRADE

FLOOR SINK WITH
STRAINER, RE:

PLUMBING

SEALANT ON

ALL SIDES

SOLID SURFACE -

REFER TO ELEVATION &

FLOOR PLANS
1'-6"
1'-6"

FINISH PER PLAN

PER PLAN
WALL
1/2" PLY WOOD OVER
METAL STUDS, 16" O.C.

BRACING 24" O.C.,
(2) MIN. PER BENCH

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

RESTROOM

DETAILS
A9.41
MD
MONROE ST. POOL REPLACEMENT

RESTROOM DETAILS
3" = 1' -0"
A9.41 1PARTITION DETAIL
3" = 1' -0"
A9.41 2GRAB BAR @ METAL STUD
3" = 1' -0"
A9.41 3GRAB BAR @ CMU WALL
3" = 1' -0"
A9.41 4WRAPPED WALL TILE
1 1/2" = 1' -0"
A9.41 5BABY CHANGING STATION
3" = 1' -0"
A9.41 6FLOOR DRAIN DETAILS
3" = 1' -0"
A9.41 7FLOOR DRAIN AT CONCRETE
FLOOR
3" = 1' -0"
A9.41 8FLOOR DRAIN AT CONCRETE
FLOOR
1 1/2" = 1' -0"
A9.41 10 BENCH @ SHOWERS /LOCKERS
53 203
08/09/2024
203

NON -CERAMIC TRIM AT TOP

CEILING HEIGHT

WALL, PARTITION TYPE PER FLOOR
PLAN

CEMENT BACKER BOARD

STAINLESS STEEL COVE -
DILEX -AHKA (B -3) SERIES BY "SCHLUTER"
TILE
NOTE:

PROVIDE WATERPROOFING UNDER
TILE WORK, TYP. SEE SPECIFICATIONS

FOR TILE HEIGHT REF

INTERIOR ELEVATIONS

PARTITION PER PLAN

WALL TILE WHERE OCCURS
(SEE ELEVATION)

GRAB BAR COLLAR

ANCHOR MOUNTING

PLATE TO BACKING
(RE: 14/A9.10) PLATE
W/ #12 SCREWS. 0'-1 1/4"
0'-1 1/2"

GRAB BAR WITH CONCEALED

MOUNTING SUPPORT

BACKING SUPPORT, SEE

MOP AND BROOM RACK

MOP SINK

WALL FINISH AND FRAMING PER PLANS

FLOORING PER

FINISH PLAN

FOR WALL BACKING DETAILS
SEE

WALL FINISH, WHERE OCCURS PER

WALL TYPE

PARTITION, SEE FLOOR PLAN FOR

WALL TYPE DESIGNATION

CEMENTITIOUS BACKER BOARD PER

WALL TYPE

WALL TILE PER FINISH PLAN

THINSET ADHESIVE
0'-0 1/8"

WALL TILE PER

FINISH PLAN

FLOORING

PER FINISH PLAN

PAINTED

CEMENTITIOUS

BACKER BOARD

PER WALL TYPE

HORIZONTAL &

VERTICAL GROUT

JOINTS TO BE
1/8"
A9.42
05 A9.42
19 TYP.

U.N.O. ON ELEVATIONS
9' - 0"
A9.42
19 TYP.

CUT TILE

TOILET PARTITION

ANODIZED

ALUMINUM ANGLE

WALL PER PLAN

BACKING TRACK
PER 14/A9.10
(2) 1/4" THROUGH BOLT
EA. SIDE W/ RUBBER
WASHER @ 48" O.C. MAX.

ALUMINUM DOUBLE

EAR BRACKET
(2) 1/4" DIAM.

THROUGH BOLTS

EACH LEG OF EACH
ANGLE
PLAN

WALL TILE PER

FINISH PLAN

FLOORING

PER FINISH PLAN

PAINTED

CEMENTITIOUS

BACKER BOARD

PER WALL TYPE

HORIZONTAL &

VERTICAL GROUT

JOINTS TO BE
1/8"
A9.42
05 A9.42
19 TYP.

U.N.O. ON ELEVATIONS
9' - 0"
A9.42
19 TYP.

CUT TILE

AREA NOT HATCHED BELOW SINK

SHALL BE ACCESSIBLE & CLEAR

WRAP HOT & COLD WATER

SUPPLIES AND DRAIN PIPING

WITH PVC INSULATION MATERIAL
COMPLIANT WITH ASTM E84-07,
25 FLAME / 450 SMOKE INDEX

QUARTZ COUNTERTOP
OVER 3/4" PLY WD. FOR
EDGE REF:

CONTINUE ADJ FLR - SEE

FINISH PLAN

TILE TO

CONTINUE

BEHIND SINK
NOTES:

1. FINISH PER FINISH PLANS AND LEGEND.

2. REFER TO BACKING TRACK AND SUPPORT DETAIL.

3. NO SHARP OR ABRASIVE SURFACES UNDER SINK.

4. ALL JOINTS TO BE CAULKED WITH CLEAR SILICONE CAU LK.

INSULATE SINK BOTTOM

IF HOT WATER PROVIDED

FAUCET CONTROLS TO BE LEVER OR A

TYPE NOT REQ GRASPING, PINCHING, OR
TWISTING OF THE WRIST W/ 5 LBS FORCE
MAX TO OPERATE.

MIN
2'-3"
M
IN
0'-8 63/64"
0'-6"
2" X 3" X 1/4" LLV STEEL ANGLE @
24" OC MAX - PAINT TO MATCH

WALL FINISH
1/8" RADIUS EASED

EDGE, TYP
2'-4"
2'-1"(ANGLE LEG)

WALL FINISH PER

INTERIOR ELEVATIONS
40" M

AX TO BO M

IRROR/REFLECTIVE SURFACE
1'-5"MIN.
0'-6"MAX.
0'-6"
MIRROR
/18 A9.42

PLAM APRON
PLATE 1/4 X 3 X 1-6"
LONG @ EACH ROD
1/2" THREADED ROD @ 24" OC
C4 X 5.4, CONTINUOUS

CEILING PER REFLECTED

CEILING PLAN

TOILET-PARTITION ASSEMBLY

PER STRUCTURAL
# 12 SMS @ 12" OC, TYP
1"W X 2"L X 13GA.

MIN METAL CLIP, TYP
4-WAY 12 GA. WIRE
BRACE @ 12" OC (TEST
FOR 200 LBS), TYP;

SECURE WIRE TO

STRUCTURE ABOVE
MAX. DIMENSION PER

MANUFACTURER'S

RECOMMENDATION
.
0'-1 1/2"

GRAB BAR

TILE WALL

ALIGN ALIGN

RECESSED SEAT-COVER

DISPENSER, TOILET TISSUE

DISPENSER AND SANITARY

NAPKIN DISPOSAL (WHERE

OCCURS)
1/4" GROUT JOINT MAX,

TYP ALL SIDES

TILE WALL
2"x2"x5/16"
SINK

QUARTZ COUNTERTOP

PER FINISH PLAN

EXTERIOR GRADE

PLYWOOD
0'-0 15/64"
0'-5 7/64"
2"x2"x5/16"

MITER CORNER
0'-6"

FLOOR DRAIN WITH
STRAINER, RE: PLUMBING
(MAX. 1/4" OPENINGS)

SEALANT

WATERPROOFING MEMBRANE

CONCRETE
(SLOPED TO DRAIN)

CONCRETE

SLAB ON
GRADE
SLOPE
2% MAX.

TYP.

CONCRETE FLOOR

CONCRETE
FLOOR

CONCRETE OVER METAL
DECK @ SECOND FLOOR
LOCATIONS, RE: 01/S6.12
EQ EQ
2% MAX.SLOPE
TYP,
U.N.O.

FLOOR DRAIN,
SEE 11/ -EQ EQ
24" U.N.O.

EQ.

EQ.
24" U.N.O.

DIM. PT.

DIM. PT.

CONCRETE

PER PLAN

SEE PLANS FOR PARTITION TYPE
GROUT, TYP.

WALL TILE PER FINISH

PLAN AND INTERIOR

ELEVATIONS
B

SEE PLANS FOR PARTITION TYPE
GROUT, TYP.

WALL TILE PER FINISH

PLAN AND INTERIOR

ELEVATIONS
A

WALL FINISH PER FINISH

PLAN AND INTERIOR

ELEVATIONS

SEE PLANS FOR

PARTITION TYPE

WALL TILE PER FINISH

PLAN AND INTERIOR

ELEVATIONS
D

SEE PLANS FOR

PARTITION TYPE

WALL TILE PER FINISH

PLAN AND INTERIOR

ELEVATIONS
C
ANOD. ALUM. CORNER

TRIM - EXTEND TO TOP

OF TILE - SCHLUTER
'INDEC'
ALUMN. TRIM (FINISH:

ANOD. ALUM)
PLAN

WALL PER PLAN

START FULL TILE

BEHIND TILE ON

ADJACENT SURFACE

LINE OF TOILET

PARTITION

WHERE OCCURS
ANOD. ALUM. CORNER

TRIM - EXTEND TO TOP

OF TILE - SCHLUTER
'INDEC'
3" = 1' -0"
A9.42 19 TILE AT TOP AND BASE
3" = 1' -0"
A9.42 03 GRAB BAR AND SUPPORT
1" = 1' -0"
A9.42 10 MOP SINK WITH BROOM RACK
3" = 1' -0"
A9.42 09 HORIZONTAL TILE JOINT
1/2" = 1' -0"
A9.42 02 BASE TO WAINSCOT
3" = 1' -0"
A9.42 14 URINAL PARTION ANCHORAGE
1/2" = 1' -0"
A9.42 01 BASE TO WAINSCOT
1" = 1' -0"
A9.42 17 RESTROOM SINK COUNTER
1 1/2" = 1' -0"
A9.42 15 ANCHOR FOR TOILET PARTITIONS
3" = 1' -0"
A9.42 13 RECESSED TOILET ACCESSORY
6" = 1' -0"
A9.42 18 COUNTER EDGE DETAIL
3" = 1' -0"
A9.42 11 FLOOR DRAIN AT FIRST FLOOR1
1 1/2" = 1' -0"
A9.42 07 LOCALIZED DEPRESSION
3" = 1' -0"
A9.42 05 TYPICAL TILE CORNERS
3" = 1' -0"
A9.42 06 WRAPPED WALL TILE

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

RESTROOM

DETAILS
A9.42
MD
MONROE ST. POOL REPLACEMENT

RESTROOM DETAILS
54 203
08/09/2024
203
LOBBY
01 STAFF
LOUNGE
03 MULTI

PURPOSE
ROOM
14 TELEPHONE
15 ADMIN
07 OFFICE
07A
STAFF
SHOWER
03B
STAFF
RR
03A

WOMEN'S

CHANGING/

LOCKERS
10 MEN'S

RESTROOM
04 STORAGE
09A

WOMEN'S
SHOWER
11 WOMEN'S

RESTROOM
09 MEN'S
SHOWER
06 MEN'S

CHANGING/

LOCKERS
05 CORRIDOR
08 CORRIDOR
02 STORAGE
04A
ELEC.
14A

EXTERIOR

STORAGE
18 FIRST
AID
16 EQUIPMENT

STORAGE
17 -D-01 14
-E-01 14
-E-01 15
-E-01 14A
-E-01 05-1
-E-01 04-3
-C-03 04-2
-M-01 01-1
-A-01 01-2
-E-01 03B-1
-E-01 08-2
-E-01 16-1
-E-01 17-1
-E-01 18-1
-E-01 09-1 -C-02 09-2
-E-01 09A-1-E-01 10-1
-E-01 09-3
-E-01 04A-1
-E-01 07-1-E-01 07A-1
-A-01 08-1
-E-01 02-2
-A-01 02-1
-C-01 03A-1
-E-01 03-1 -E-01 04-1
-C-04 03A-2
-D-01 03-2
POOL
PUMP
ROOM
22 ELECTRICAL
21 STORAGE
19 CORRIDOR/

LOCKERS
20 FAMILY

RESTROOM/
SHOWER
20C
FAMILY

RESTROOM/
SHOWER
20D
FAMILY

RESTROOM/
SHOWER
20A
FAMILY

RESTROOM/
SHOWER
20B

CHEMICAL
ROOM
24 CHEMICAL
ROOM
25 BACKWASH
22A
PUMP
PIT
22B
-E-01 22-2 -E-01 23-1 -E-01 24-2
-E-01 22-1
-E-01 20-1
-C-01 20A-2
-C-01 20C-2
-C-01 20D-2
-C-01 20E-2
-E-01 19-1
-E-01 21-1
-A-01 22-3
-C-04 20A-1
-C-04 20D-1 -C-04 20E-01
-C-04 20B-1
FAMILY

RESTROOM/
SHOWER
20E
-C-04 20C-1

1. FOR SIGNAGE DETAILS, REF: A10.11 AND A10.12

2. FOR ACCESSIBILITY SIGNAGE NOTES, REF: A10.11

3. FOR SIGNAGE SCHEDULE, REFER TO A10.03

4. FOR SIGN MATERIAL, COLOR, LETTERING, ADN TYPEFACE, REFER TO SPECIFICATION SECTION 101400.

5. FOR LOCATION OF ELEVATOR LEVEL ID AND STAR OF LIFE SIGN NOT SHOWN ON PLAN; REF: 12/A10.11.

6. WHEN SIGNS OCCUR ON GLASS, PROVIDE VINYL BACKING ON OPPOSITE SIDE OF GLASS.

7. WHERE SIGNS OCCUR BACK TO BACK, ENLARGE SMALLER SIGN TO MATCH DIMENSION OF SIGN ON OPPOSITE SIDE OF GLASS.

8. IF ROOMS ARE PROVIDED WITH ROOM NAMES OR SIGNS THESE SHALL ALSO INCLUDE BRAILLE.

LEGEND

GENERAL NOTES

SIGNAGE TAG

SIGN TYPE

ROOM NUMBER

SIGN NUMBER
### -# - X-##

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

SIGNAGE PLAN &

SCHEDULE - BLDG A
& B
A10.01
MD
MONROE ST. POOL REPLACEMENT

SIGNAGE PLAN & SCHEDULE - BLDG A & B
1/8" = 1' -0"
A10.01 1SIGNAGE PLAN - BLDG A
1/8" = 1' -0"
A10.01 2SIGNAGE PLAN - BLDG B
SIGN

NUMBER TYPE MARK SIGN TYPE DETAIL COMMENTS
C-01 ALL GENDER RESTROOM DOOR 07/A10.11
01-1 M-01 NO SMOKING 05/A10.11
01-2 A-01 EXIT 05/A10.11
02-1 A-01 EXIT 05/A10.11
02-2 E-01 ROOM IDENTIFICATION 17/A10.11
03-1 E-01 ROOM IDENTIFICATION 17/A10.11
03-2 D-01 MAXIMUM OCCUPANCY 06/A10.11
03A-1 C-01 ALL GENDER RESTROOM DOOR 07/A10.11
03A-2 C-04 ALL GENDER RESTROOM WALL 11/A10.11
03B-1 E-01 ROOM IDENTIFICATION 17/A10.11
04-1 E-01 ROOM IDENTIFICATION 17/A10.11
04-2 C-03 MENS RESTROOM DOOR 07/A10.11
04-3 E-01 ROOM IDENTIFICATION 17/A10.11
04A-1 E-01 ROOM IDENTIFICATION 17/A10.11
05-1 E-01 ROOM IDENTIFICATION 17/A10.11
07-1 E-01 ROOM IDENTIFICATION 17/A10.11
07A-1 E-01 ROOM IDENTIFICATION 17/A10.11
08-1 A-01 EXIT 05/A10.11
08-2 E-01 ROOM IDENTIFICATION 17/A10.11
09-1 E-01 ROOM IDENTIFICATION 17/A10.11
09-2 C-02 WOMENS RESTROOM DOOR 07/A10.11
09-3 E-01 ROOM IDENTIFICATION 17/A10.11
09A-1 E-01 ROOM IDENTIFICATION 17/A10.11
10-1 E-01 ROOM IDENTIFICATION 17/A10.11
14 E-01 ROOM IDENTIFICATION 17/A10.11
14 D-01 MAXIMUM OCCUPANCY 06/A10.11
14A E-01 ROOM IDENTIFICATION 17/A10.11
15 E-01 ROOM IDENTIFICATION 17/A10.11
16-1 E-01 ROOM IDENTIFICATION 17/A10.11
17-1 E-01 ROOM IDENTIFICATION 17/A10.11
18-1 E-01 ROOM IDENTIFICATION 17/A10.11
19-1 E-01 ROOM IDENTIFICATION 17/A10.11
20-1 E-01 ROOM IDENTIFICATION 17/A10.11
20A-1 C-04 ALL GENDER RESTROOM WALL 11/A10.11
20A-2 C-01 ALL GENDER RESTROOM DOOR 07/A10.11
20B-1 C-04 ALL GENDER RESTROOM WALL 11/A10.11
20C-1 C-04 ALL GENDER RESTROOM WALL 11/A10.11
20C-2 C-01 ALL GENDER RESTROOM DOOR 07/A10.11
20D-1 C-04 ALL GENDER RESTROOM WALL 11/A10.11
20D-2 C-01 ALL GENDER RESTROOM DOOR 07/A10.11
20E-01 C-04 ALL GENDER RESTROOM WALL 11/A10.11
20E-2 C-01 ALL GENDER RESTROOM DOOR 07/A10.11
21-1 E-01 ROOM IDENTIFICATION 17/A10.11
22-1 E-01 ROOM IDENTIFICATION 17/A10.11
22-2 E-01 ROOM IDENTIFICATION 17/A10.11
22-3 A-01 EXIT 05/A10.11
23-1 E-01 ROOM IDENTIFICATION 17/A10.11
24-2 E-01 ROOM IDENTIFICATION 17/A10.11

KEYPLAN
A
B

KEYNOTE LEGEND
55 203
08/09/2024
203
SIGNS SHALL COMPLY WITH SECTION CBC 11B -703 , WHERE BOTH VISUAL AND TACTILE CHARACTERS ARE REQUIRED.

RAISED CHARACTERS SHALL COMPLY WITH CBC 11B -703.2 AND SHALL BE DUPLICATED IN BRAILLE COMPLYING WITH SECTION CBC 11B -703.3. • CHARACTER DEPTH: CBC 11B -703.2.1
• CHARACTER CASE: CBC 11B -703.2.2
• CHARACTER STYLE: CBC 11B -703.2.3
• CHARACTER PROPORTIONS: CBC 11B -703.2.4
• CHARACTER HEIGHT: CBC 11B -703.2.5
• CHARACTER STROKE THICKNESS: CBC 11B -703.2.6
• CHARACTER SPACING: CBC 11B -703.2.7
• CHARACTER LINE SPACING: CBC 11B -703.2.8
• CHARACTER FORMAT: CBC 11B -703.2.9
BRAILLE CHARACTERS SHALL COMPLY WITH CBC 11B -703.3
• BRAILLE SHALL BE CONTRACTED (GRADE 2) AND SHALL COMPLY WITH SECTIONS CBC11B -703.3 AND CBC 11B -703.4.
• BRAILLE DIMENSIONS AND CAPITALIZATION: CBC TABLE 11B -703.3.1 • BRAILLE POSITION: CBC TABLE 11B -703.3.2
VISUAL CHARACTERS SHALL COMPLY WITH CBC 11B -703.5
• FINISH AND CONTRAST: CBC11B -703.5.1
• HEIGHT: CBC TABLE 11B -703 -5.5
• STROKE THICKNESS: CBC11B -703.5.7
• FORMAT: CBC TABLE 11B -703.5.10

SIGNS AT SINGLE DOORS
GLASS

SIGN ON

BOTH SIDES
NOTES:

1. SIGN MOUNTING LOCATION AND HEIGHT SHALL COMPLY WITH CBC 11B -703.4.1; CBC 11B -703.4.2; CBC 11B -703.7.2.6

2. AT SINGLE DOORS, LOCATE SIGN ON LATCH SIDE OUTSIDE OF DOOR ENTERING ROOM THAT IS IDENTIFIED ON SIGN

3. WHEN SIGNS ARE MOUNTED TO GLASS, PROVIDE VINYL BACKING BETWEEN SIGN AND GLASS

4. WHEN SIGNS ARE MOUNTED ON BOTH SIDES OF GLASS, ALIGN SIGNS CL
(58" M
IN. - 60" M
AX.)
60" A.F.F.

EQ EQ CL

RAISED COPY

LOWEST BRAILLE CELLS
48" MIN. BASELINE OF

HIGHEST RAISED CHARACTERS
60" MAX BASELINE OF
EQ EQ
FLR. SPACE
1'-6"

RESTROOM DOOR SIGNAGE

RESTROOM & TACTILE SIGN

RAISED COPY

LOWEST BRAILLE CELLS
48" MIN. BASELINE OF
EQ EQ
FLR. SPACE
1'-6"

HIGHEST RAISED CHARACTERS
60" MAX BASELINE OF

SIGNS AT DOUBLE DOORS SIGNS MOUNTED TO GLASS

SIGN ON

SINGLE SIDE
GLASS

VINYL, SAME SIZE AND

SHAPE AS SIGN -
COLOR (V1)
NOTES:

1. VERTICES SHALL BE RADIUSED BETWEEN 1/8" MIN. AND 1/4" MAX.

MEN
WOMEN

RESTROOM
1/4" THICK ACRYLIC EQUILATERAL

TRIANGLE SIGN PANEL POINTING
UPWARDS WITH 12" SIDES - COLOR
(P2)
DIRECT PRINT - COLOR (P1)
DIRECT PRINT - COLOR (P1)
1/4" THICK ACRYLIC 12" DIAMETER
CIRCLE SIGN PANEL - COLOR (P2)
1/4" THICK ACRYLIC EQUILATERAL

TRIANGLE SIGN PANEL POINTING

UPWARDS, SUPER IMPOSED ON

AND GEOMETRICALLY INSCRIBED
WITHIN THE CIRCLE. THE VERTICES

OF THE TRIANGLE SHALL BE

LOCATED ON THE EDGE OF THE
CIRCLE - COLOR (P1)
RAISED CHARACTER AND BRAILLE EXIT SIGNS: CBC 1013.4
TACTILE EXIT SIGNS SHALL BE REQUIRED AT THE FOLLOWING LOCATIONS:

1. EACH GRADE -LEVEL EXTERIOR EXIT DOOR THAT IS REQUIRED TO COMPLY WITH SECTION 1013.1, SHALL BE IDENTIFIED BY A TACTILE EXI T SIGN WITH THE WORD, "EXIT".

2. EACH EXIT DOOR THAT IS REQUIRED TO COMPLY WITH SECTION 1013.1,

AND THAT LEADS DIRECTLY TO A GRADE -LEVEL EXTERIOR EXIT BY

MEANS OF A STAIRWAY OR RAMP SHALL BE IDENTIFIED BY A TACTILE EXIT SIGN WITH THE FOLLOWING WORDS AS APPROPRIATE:

2.1 "EXIT STAIR DOWN"

2.2 "EXIT RAMP DOWN"

2.3 "EXIT STAIR UP"

2.4 "EXIT RAMP UP"

3. EACH EXIT DOOR THAT IS REQUIRED TO COMPLY WITH SECTION 1013.1,

AND THAT LEADS DIRECTLY TO A GRADE -LEVEL EXTERIOR EXIT BY

MEANS OF AN EXIT ENCLOSURE OR AN EXIT PASSAGEWAY SHALL BE IDENTIFIED BY A TACTILE EXIT SIGN WITH THE WORDS, "EXIT ROUTE."

4. EACH EXIT ACCESS DOOR FROM AN INTERIOR ROOM OR AREA TO A

CORRIDOR OR HALLWAY THAT IS REQUIRED TO COMPLY WITH
SECTION 1013.1, SHALL BE IDENTIFIED BY A TACTILE EXIT SIGN WITH THE WORDS "EXIT ROUTE."

5. EACH EXIT DOOR THROUGH A HORIZONTAL EXIT THAT IS REQUIRED TO COMPLY WITH SECTION 1013.1, SHALL BE IDENTIFIED BY A SIGN WITH THE WORDS, "TO EXIT."

RAISED CHARACTER AND BRAILLE EXIT SIGNS SHALL COMPLY WITH CHAPTER 11B, SECTIONS 11B - 703.1, 11B -703.2, 11B -703.3 AND 11B -703.5.

NOTES:

1. VINYL APPLIED TO SECOND SURFACE OF GLASS

NO SMOKING OR VAPING
WITHIN 25 FEET OF

BUILDING ENTRANCE
0'-0 1/2"
5/8" TALL COPY, FONT TYPE
(C) - COLOR (V1)
0'-3"
PICTOGRAM - COLOR (V1)
0'-8"
5'-0"
A.F.F.

EXIT STAIR
DOWN

FRONT ELEVATION
(TWO LINE COPY)
1/4" THICK CLEAR ACRYLIC
PANEL - COLOR (P2)

APPLIED TO SECOND

SURFACE
5/8" TALL RAISED LETTERS,
FONT TYPE (A) - COLOR (P1)
0'-0 3/8"
EXIT

BRAILLE, COLOR (CLEAR) FRONT ELEVATION
(SINGLE LINE COPY)
EQ. EQ.

COPY SHALL NOT

ENCROACH ON IMAGINARY
1/2" BORDER AROUND SIGN
PANEL 0'-0 1/2"
0'-0 1/2"
EQ. EQ.
0'-0 3/8"
0'-4"
5'-0"
A.F.F.
5/8" TALL RAISED LETTERS,
FONT TYPE (A) - COLOR (P1)
0'-0 3/8"

EXIT ROUTE

BRAILLE, COLOR (CLEAR) FRONT ELEVATION
(SINGLE LINE COPY)
EQ. EQ.

COPY SHALL NOT

ENCROACH ON IMAGINARY
1/2" BORDER AROUND SIGN
PANEL 0'-0 1/2"
0'-0 1/2" 5'-0"
A.F.F.
0'-8"
0'-8"
0'-0 1/2"
0'-0 1/2"
5/8" TALL RAISED LETTERS,
FONT TYPE (A) - COLOR (P1)
0'-0 3/8"

TO EXIT

BRAILLE, COLOR (CLEAR) FRONT ELEVATION
(SINGLE LINE COPY)
EQ. EQ.

COPY SHALL NOT

ENCROACH ON IMAGINARY
1/2" BORDER AROUND SIGN
PANEL 0'-0 1/2"
0'-0 1/2" 5'-0"
A.F.F.
0'-8"
0'-8"
5'-0"
A.F.F.

EXIT RAMP
DOWN

FRONT ELEVATION
(TWO LINE COPY)
1/4" THICK CLEAR ACRYLIC
PANEL - COLOR (P2)

APPLIED TO SECOND

SURFACE
EQ. EQ.
0'-0 3/8"
0'-4"
0'-0 1/2"
0'-0 1/2"

BRAILLE, COLOR (CLEAR)

BRAILLE, COLOR (CLEAR)

COPY SHALL NOT

ENCROACH ON IMAGINARY
1/2" BORDER AROUND SIGN
PANEL

COPY SHALL NOT

ENCROACH ON IMAGINARY
1/2" BORDER AROUND SIGN
PANEL
5/8" TALL RAISED LETTERS,
FONT TYPE (A) - COLOR (P1)

ELECTRICAL

FRONT ELEVATION
(SINGLE LINE COPY)
EQ. EQ.

COPY SHALL NOT

ENCROACH ON IMAGINARY
1/2" BORDER AROUND SIGN
PANEL
0'-0 1/2" 0'-0 1/2"
0'-4"
NOTE: MACHINERY SPACES ARE NOT REQUIRED TO BE
ACCESSIBLE AND SHOW BRAILLE (11B -203.5).

DIRECT TO SUBSTRATE

DIGITAL PRINT SIGN COPY
AND GRAPHIC - COLOR (P1)
5'-10" MAX
A.F.F.

ASSISTIVE LISTENING

SYSTEMS AVAILABLE

AT RECEPTION DESK
3/32" THICK

ALUMINUM

PANEL -
COLOR
(P2)
0'-6"
1'-2"
5/8" TALL COPY, FONT TYPE (B)
5/16" TALL COPY, FONT

TYPE (B)
0'-0 1/2" 0'-0 1/2"
0'-0 1/2" 0'-0 1/2"

MAXIMUM

OCCUPANCY
###
0'-6"
1'-2"

DIRECT TO SUBSTRATE
DIGITAL PRINT COPY, 1"

TALL, FONT TYPE (A) -
COLOR (P1)
3/32" THICK ALUMINUM

SIGN PANEL PAINTED -
COLOR (P2)
5'-10" MAX.

A.F.F.

NOTES:

1. SEE EXIT / CODE ANALYSIS SCHEDULE FOR OCCUPANCY COUNT 1/4" THICK CLEAR ACRYLIC
PANEL
5/8" TALL RAISED LETTERS,
FONT TYPE (A) - COLOR (P1)

PICTOGRAM APPLIED TO

SECOND SURFACE - COLOR
(P1), FIELD COLOR (P2)
0'-8"
0'-0 3/8"
5'-0"
A.F.F.
0'-8"
MEN
0'-2"
0'-5" 0'-0 1/2"

BRAILLE, COLOR (CLEAR) FRONT ELEVATION
5/8" TALL RAISED LETTERS,
FONT TYPE (A) - COLOR (P1)
0'-8"
0'-0 3/8"
5'-0"
A.F.F.
0'-8"
WOMEN
0'-2"
0'-0 1/2" 0'-5"
1/4" THICK CLEAR ACRYLIC
PANEL

PICTOGRAM APPLIED TO

SECOND SURFACE - COLOR
(P1), FIELD COLOR (P2)

BRAILLE, COLOR (CLEAR) FRONT ELEVATION
1/4" THICK CLEAR ACRYLIC
PANEL
5/8" TALL RAISED LETTERS,
FONT TYPE (A) - COLOR (P1)

PICTOGRAM APPLIED TO

SECOND SURFACE - COLOR
(P1), FIELD COLOR (P2)

BRAILLE, COLOR (CLEAR) FRONT ELEVATION
0'-8"
0'-0 3/8"
5'-0"
A.F.F.
0'-8"

RESTROOM
0'-2"
EQ. 0'-4" EQ.

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024

FOR REGULATORY

APPROVAL & PERMITTING

NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL

DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

SIGNAGE DETAILS
A10.41
MD
MONROE ST. POOL REPLACEMENT

SIGNAGE DETAILS

SIGN RAISED CHARACTER & BRAILLE NOTES
NTS
A10.41 05 SIGN MOUNTING
NTS
A10.41 06 SANITARY FACILITY SIGNAGE
(DOOR)

TACTILE EXIT SIGN NOTES
3" = 1' -0"
A10.41 17 INT ACCESSIBILITY SYMBOL
3" = 1' -0"
A10.41 10 TACTILE EXIT SIGNAGE
3" = 1' -0"
A10.41 19 MACHINERY ROOM SIGNAGE
14 ASSISTIVE LISTENING SYSTEMS
15 MAXIMUM OCCUPANCY
07 SANITARY FACILITY SIGNAGE (WALL)
56 203
08/09/2024
203
A. GENERAL

1. Applicable Code: 2022 California Building Code (CBC). References to industry standards herein shall be latest edition as adopted by Applicable Code.

2. Authority Having Jurisdiction (AHJ): City of Ca rlsbad

3. Field Verification: Field verify existing condi tions and dimensions prior to construction. Promptly notify Architect (Structural Engineer) in case of discrepancies.

4. Design Intent: Contract Documents indicate desi gn intent for structure in its completed state. They do not indicate method of construction. Promptly notify Architect (Structural Engineer), prior to proceeding with Work, if design intent requires further clarification.

5. Deviations, Modifications and Substitutions to A pproved Structural Drawings: Must be accepted in writing by Architect (Structural Engineer) and approved by Governing Code Authority. No deviation, modification or substitution will be accepted via shop drawing review.

6. Procedures of Construction: Contractor is respo nsible for procedures of construction complying with national, state and local safety ordinances. Site visits (including Structural Observation) by Architect (Structural Engineer) do not constitute supervision of methods of construction.

A. Protection of Utilities: Locate existing utilit ies, including those not shown on Contract Documents, and protect them from damage. Contractor bears expense of repair or replacement of utilities in conjunction with execution of Work.

B. Excavations: Protect structure, adjacent struct ures, adjacent properties, streets, and utilities during excavation utilizing lagging, shoring, underpinning and related procedures as may be required. Provide necessary supports for soil at sides of excavations. Contractor and affected trades shall refer to Geotechnical Report for more information.

C. Protection of Structure: Provide necessary meas ures to protect structure and adjacent buildings during execution of Work.

D. Contractor Proposed Revisions: Where a revision of structural design or connection is proposed by Contractor to accommodate construction tolerances, construction sequence and/or dimension modifications, Contractor shall retain a structural engineer licensed in State of California to perform design. Submit stamped and signed design drawings and calculations to the Architect (Structural Engineer) for review and the Governing Code Authority for approval.

E. Erection Plans: Determine phases of Work requir ing erection plans according to applicable safety regulations. Maintain certified copies of erection plans at site during construction.

F. Shoring, Bracing, and Other Temporary Supports: Design and erect shoring, bracing, and other temporary supports where structure has not attained design strength and as required for safe erection.

Ensure floor, roof, and wall members are securely shored and braced during construction. Provide shoring at elevated beams and slabs supporting concrete or masonry walls during and after wall pour until wall attains design strength.

G. Temporary Loading: Ensure construction loads do not exceed indicated design live load values. Notify affected sub-contractor trades of these design load limits.

H. Fabrication, Shipment, and Erection of Structura l Steel: Ensure stresses occurring during fabrication, shipment, and erection of structural steel are temporary and are less than design and allowable stress capacities of individual members. Do not impair full design and load carrying capacity of members due to fabrication, shipment, or erection. Contractor is responsible for controlling erection sequence, erection procedure, temperature differentials and weld shrinkage to minimize residue stresses. Provide additional materials for the erection of structural steel such as temporary bracing and guy cables as may be necessary at no additional cost. Remove these materials unless approved in writing by Owner. Do not tighten bolts in typical beam to column connections for erection purposes.

I. Securing Reinforcing Steel, Dowels, Anchor Bolts and Embeds: Firmly support and accurately place complying with ACI standards prior to casting concrete or grout in masonry walls. Use ties and support bars in addition to reinforcing steel shown where necessary. No welding of reinforcing steel, including tack welding, is permitted unless otherwise accepted in writing by Architect (Structural Engineer). Provide plastic or plastic coated chairs and spacers when resting on exposed surfaces.

J. Coordination Responsibility: Contractor is resp onsible for coordination of Work including that of sub- contractor trades.

K. Core drilling shall of hardened concrete shall o nly be done after specific review by Architect (Structural Engineer) Core drilling shall not cut any reinforcing. Concrete coverage for reinforcement as described in these notes shall be maintained at locations of cores.

Wind Design
a. Speed:
b. Exposure:
c. Enclosure Classification:
d. Components and Cladding Design:
e. Wind Drift Limit:
96 MPH (LRFD)
C
GCPi = +0.18/-0.18
Project Seismic Design Parameters:
a. Site Class:
b. Mapped Spectral Acceleration (Ss, S1):
c. Site Specific Spectral Response Coefficient (SDS, SD1):
d. Site Coefficient (Fa, Fv):
e. Seismic Importance Factor Ie:
f. Risk Category:
g. Seismic Design Catagory:

D

1.225 g, 0.41 g (respectively)

0.825 g, 0.517 g (respectively)

1.01, 1.89 (respectively)
1 II
D
Live Load Design
a. Floor / Roof Live Load: See legends as provided on plan sheets. Live loading in accordance with CBC 1607A.1.

Project Rain / Snow Design Parameters:
a. Rain Intensity i: 1.18 (in/hr)
Building B Seismic Design:
a. Basic Seismic Force Resisting System:
b. Seismic Response Coefficient, Cs:
c. Analysis Procedure:
d. Seismic Base Shear:
e. Response Modification Factor R:
f. Overstrength Factor, Ωo:
g. Deflection Amplification Factor, Cd:
h. Maximum Story Inelastic Drift:
i. Irregularities:
j. Reduncancy Factor, P:
k. Building Mass:
l. Wind Base Shear:
m. Location of Seismic Base

SPECIAL REINFORCED MASONRY SHEAR WALLS

0.165 g

EQUIVALENT LATERAL FORCE PROCEDURE

43.4 kips (Bldg B)

5.0 2.5

3.5 Roof Floor:

0.007 x Story Height
Vertical: N/A
Horizontal: N/A
Rho = 1.3 in (North / South)

1.3 in (East / West)
263.3 kips (Bldg B)
N/A: Seismic Governed
Ground Level

7. Submittals: SubmAVit to Architect (Structural E ngineer) as indicated on structural drawings and specifications.

General Contractor shall review submittal for completeness and compliance with Contract Documents prior to submission.

A. Request for Information (RFI) Submittals: Accom pany RFI's with partial structural foundation or framing plans showing location in question and affected structural members. Copy partial plan from structural drawings and indicate grid line locations and floor level. Also provide properly drawn engineering sketches illustrating issues and Contractor's proposed solutions. Photographs are not acceptable substitutes to engineering sketches.

B. Composite Slab Penetration Submittal: Submit to Architect (Structural Engineer) for each floor indicating size and location of each slab penetration and opening as necessary by all affected trades. Submit penetration plans together with corresponding metal decking or reinforcing steel shop drawings. Submit written statement from Special Inspector that no additional penetrations or openings were added to those shown in penetration submittal.

C. Composite Concrete and Masonry Wall Penetration Submittal: Submit to Architect (Structural Engineer) for each wall indicating size and location of each wall penetration and opening as necessary by all affected trades. Submit penetration elevations together with corresponding reinforcing steel shop drawings. Submit written statement from Special Inspector that no additional penetrations or openings were added to those shown in penetration submittal.

8. Contract Documents Use: Review Contract Documen ts in their entirety before performing structural related Work and before developing shop drawings. Bring discrepancies to immediate attention of Architect (Structural Engineer) before starting Work.

A. Scaling of Drawings: Not permitted.

B. Additional Structural Requirements: See specifi cations.

C. Building Geometry: See architectural drawings f or building geometry including, but not limited to, top of floor and roof elevations; depressions; slopes; curbs; drains; trenches; slab and deck edge locations; wall overall dimensions; and size and locations of openings in floors, roof, and walls.

D. Non-structural Items Requiring Special Provision s: See architectural, mechanical, plumbing, and electrical drawings for non-structural items requiring special provisions during construction. They include, but are not limited to, non-structural walls; size and locations of openings and sleeves penetrating structure; size and location of concrete curbs and pads; and size and location of piping, ductwork, and equipment anchorages mounted or suspended from structure. Verify exact size and location of equipment with equipment manufacturer.

9. Materials: Furnish and install in compliance wi th legally constituted public authorities having jurisdiction including county and local ordinances and safety orders of State Industrial Accident Commission, OHSA. The Architect (Structural Engineer) and Owner accept no responsibility for the contractors failure to comply with these requirements.

10. Penetrations, Embedments, and Openings in Struc tural Members: No penetration, embedment, opening, sleeve, pipe, or conduit shall occur in structural members including footings, slabs, walls, columns, and beams unless specifically shown or indicated on structural drawings.

11. Typical Details: Details on sheets indicated a s typical are applicable throughout Project wherever the described condition occurs and may or may not be specifically referenced on structural drawings. Contractor is responsible for identifying these details and understanding extent of their application prior to performing Work.

Details not shown or noted shall be similar to those shown for similar construction. Contractor shall submit RFI's for details such as this to Architect (Strucutral Engineer) prior to proceeding with work.

12. Evaluation Report:

A. References to Evaluation Reports for proprietary materials herein shall be latest edition as adopted by Authority Having Jurisdiction (AHJ).

B. For proprietary structural elements and products , product to hold Evaluation Report in compliance with applicable code for products intended use.

C. Approved Evaluation Report Agencies:

1. ICC (ICC-ES)

2. IAPMO (IAPMO-ES)

3. OSHPD (OPA / OPM / OSP / OPD)

4. City Of Los Angeles (COLA/RR)

5. Miami-Dade (NOA)
A. GENERAL CONT.
eff. Area
(ft 2)
WIND PRESSURE (psf)
TYP. Wall Edge
50 100
200
+17.9/-19.6
+17.0/-18.7
+16.1/-17.8
+17.9/-22.5
+17.0/-20.7
+16.1/-19.0
Building A Seismic Design:
a. Basic Seismic Force Resisting System:
b. Seismic Response Coefficient, Cs:
c. Analysis Procedure:
d. Seismic Base Shear:
e. Response Modification Factor R:
f. Overstrength Factor, Ωo:
g. Deflection Amplification Factor, Cd:
h. Maximum Story Inelastic Drift:
i. Irregularities:
j. Reduncancy Factor, P:
k. Building Mass:
l. Location of Seismic Base
SPECIAL REINFORCED MASONRY SHEAR WALLS(First Aid Room & Canopy NS) STEEL ORDINARY MOMENT FRAME(Canopy EW)

0.165 g(SRMSW) / 0.236 g(SOMF)

EQUIVALENT LATERAL FORCE PROCEDURE

6.70 kips (First Aid Room)/ 2.86 kips (Canopy)

5.0(SRMSW)/3.5(SOMF)

2.5(SRMSW)/3.0(SOMF)

3.5(SRMSW)/3(SOMF)
Roof Floor:

0.007 x Story Height (SRMSW)

0.025 x Story Height (SOMF)
Vertical: N/A
Horizontal: N/A
Rho = 1.3 (First Aid Room)

1.3 (Canopy)

40.6 kips (First Aid Room)/12.1 kips(Canopy)
Ground Level
H/400 (10 yr wind)
B. DEFERRED SUBMITTAL ITEMS ANCHORED OR SUPPORTED BY STRUCTURE

1. Design Responsibility: Contractor to design and obtain separate Governing Code Authority approval for tdeferred approval items noted on Gx series sheets.

2. Shop Drawings and Structural Calculations: Submi t design plans, details and calculations of deferred submittal items signed and sealed by a registered structural engineer registered in State of California to Architect (Structural Engineer) for acceptance and to Governing Code Authority for approval prior to fabrication.

3. Design: Design components for imposed forces inc luding lateral restraint complying with Applicable Code, Contract Documents, and applicable portions of AISI Specifications. If building Seismic Force Resisting System (SFRS) is used for lateral restraint, indicate load paths to building lateral resisting system in calculations and show connection forces on shop drawings. Where building provides vertical support, indicate loads and load paths to building in calculations and show connection forces on shop drawings. Dead load elements at lowest level of connection uno Design loads are as follows:

A. Dead load: Self weight of deferred system (includ ing supported components of other systems).

B. Live load: Per applicable code.

C. Seismic and wind loads: Per applicable code. See General Notes Section A.1.

D. Design Movement: Lateral Movement: Section A.1 of General Notes Vertical Movement: Live Load Deflection of L/360

4. Defferred Submittal Items: Roof Screen.

C. QUALITY ASSURANCE (STRUCTURAL OBSERVATION, MATERI ALS TESTING, and SPECIAL INSPECTION)

1. Structural Observation:

A. The Architect (Structural Engineer) of record wi ll perform visual observation of the construction as required CAC 4-333 and 4-341 in accordance with the governing code. These visual observations shall not be considered a substitute for special inspections.

B. Coordination Responsibilities of Contractor: Not ify Architect (Structural Engineer) 48 hours in advance of critical stages of construction indicated below so visits may be scheduled by Structural Observer. Failure by Contractor to meet observation schedule may require removal of subsequent Work for observation. Contractor to bear costs of removal and replacement of finished Work or framing damaged by removal process or as required for corrective action and for any associated scheduling delays.

Critical stages of construction requiring structural observation:

1. Prior to pouring first foundation.

2. Prior to pouring elevated concrete deck.

3. Prior to pouring first concrete filled metal deck.

4. After roof deck welded off.

5. After nailing of first plywood diaphragm.

C. Pre-construction Meeting: Owner may coordinate a nd call for meeting between Architect (Structural Engineer) responsible for structural design, Structural Observer, Contractor, affected subcontractors and Special Inspector. structural observer will preside over this meeting. Purpose of meeting is to identify major structural elements and connections that affect vertical and lateral load resisting systems of structure and to review schedule of Structural Observation, Materials Testing, and Special Inspection of Project.

2. Mill Test Reports Certifying Materials: Contract or to submit mill test reports certifying reinforcing steel, and structural steel are of identifiable tested stock to Owner, Special Inspector, Architect (Structural Engineer) and, upon request, to Governing Code Authority.

Ensure materials are properly tagged for identification. If mill test reports cannot be made available or if material cannot be identified, Testing Laboratory will perform tests as directed by Architect (Structural Engineer). Contractor shall pay Testing Laboratory for costs related to tests and inspections of unidentifiable materials or materials furnished without mill test reports, materials found deficient after initial tests and inspections, or materials replacing deficient materials.

A. Ultrasonic Examination of Heavy Rolled Shapes an d Thick Plates at Proposed Welded Moment Connections: Where complete penetration groove welds occur at Groups 4 and 5 structural steel shapes, as defined in ASTM A6, and plates exceeding 2 inches thick, submit mill test reports to Architect (Structural Engineer) and, upon request, to Governing Code Authority. Mill test reports shall certify that Charpy V-notch testing was conducted in compliance with ASTM A6, Supplementary Requirement S5, including impact test complying with ASTM A673 at frequency P with minimum average value of 20 ft.-lbs. absorbed energy at 70 degrees Fahrenheit.

3. Weld Testing and Inspection: Testing Laboratory will submit weld test results to Owner, Contractor, Architect (Structural Engineer) and to Governing Code Authority. See Specifications for testing requirements not indicated on structural drawings.

A. Structural Steel Welding: Apart from visual insp ection and review of fabrication and erection reports of fabricator/erector's own quality control testing and inspection, Owner's Testing Laboratory will perform indicated shop and field inspection and testing.

Testing Laboratory will be AWS Q.C.-1 certified and will provide inspectors for continuous inspection of steel fabrication and erection and structural welding. Shop and field testing of materials and welding will be as follows:
a. Ultrasonic testing (UT) is required for all (100% ) complete penetration welds. Test groove welding on continuity plates by ultrasonic testing after beam flange weld connection. Testing will be performed 24 hours or more after completion of welding. Weld backing removal areas and fillet welds will be subjected to magnetic particle examination.

1. UT testing reduction: Where the initial rate for UT is 100%, the NDT rate for an individual welder or welding operator is permitted to be reduced to 25% provided that the number of welds containing unacceptable defects operator. A sampling of at least 40 completed welds for a job shall be made for such reduction evaluation. See AISC 360-10 N5.5e and AISC 341 J6.2g for additional information.

2. UT Reduction is NOT permitted at demand critical welds.

3. Documentation: All NDT performed shall be documen ted per AISC 360-10 N5.5g b. Base metal thicker than 1-1/2 inches, subjected t o through thickness weld shrinkage, will be ultrasonically tested directly behind such welds after welds have cooled to ambient temperature. c. Welds shall be visually inspected and periodicall y measured (15 percent minimum). d. Check 10 percent of fillet welds by magnetic part icle (ASTM 109 method). Check 25 percent of continuity plate fillet welds and beam fillet welds (100 percent in moment zones) by magnetic particle. e, Ultrasonically test column flanges located at pro posed welded moment connections, continuity plates, doubler plates and base plates where column flange or plate thickness exceeds 1-1/2 inches. Test for evidence of laminations, inclusions or other discontinuities in accordance with ASTM A435, straight beam ultrasonic examination of steel plates, or ASTM A898, straight beam ultrasonic examination of rolled steel structural shapes, as applicable. Test zone to include area 6 inches above and below each beam flange connection. For plates, any discontinuity causing a total loss of back reflection not contained within 3-inch diameter circle, or one-half thickness of plate, whichever is greater, will be rejected. For rolled shapes, ASTM A898, Level I criteria applies. Testing will be performed on material prior to fabrication, after fabrication, and after final welding of beam.
f. k-Area welds shall be MT'd no sooner than 48 hour s after completion of weld. g. Amperage, voltage, polarity and electrode stick o ut will be verified for compliance with electrode manufacturer's recommendations.

4. Special Inspection: 1704.2.3 of CBC. See S0.03
D. EARTHWORK and FOUNDATIONS

1. Geotechnical Report: Perform soils work complyin g with foundation design based on recommendations in report log no. 10573-1; prepared by Atlas; dated Nov.6.2023 and subsequent addenda letters. Maintain at site a copy of report and addenda.

2. Allowable Foundation Design Values per Geotechni cal Report.

A. Bearing Capacity: 2500 psf, for min. 2'-0" wide spread footing and 1'-6" wide continuous footings both with 2'-0" min. below adjacent finished grade. Values may be increased by 1/3 for transient loading.

B. Passive Lateral Bearing Pressure: 300 psf/ft. Va lues may be increased by 1/3 for transient loading.

C. Coefficient of Friction: 0.35.

D. Combined Lateral Resistance : The allowable late ral resistance can be taken as 350psf/ft .

E. Slab on Grade Bearing Capacity: 2000psf

3. Grading, Excavations, Backfill and Compaction of Backfill: Comply with Geotechnical Report and requirements of Governing Code Authority and performed only under Continuous Special Inspection of geotechnical engineer. Building pads shall be over excavated per figure below as recommended in Geotechnical Report. If soft pockets are discovered during over excavation, additional over excavation will be required as directed by the Geotechnical Engineer.

4. Foundation Excavations: Foundations are to bear on approved compacted fill as indicated in Geotechnical Report. Excavations are to be inspected by geotechnical engineer prior to placement of reinforcing steel and formwork. Ensure excavations are clean, dry and free of debris or loose soil. Slope sides of excavation not less than minimum slope indicated in Geotechnical Report. Cast concrete directly against excavated surfaces. Graphic presentation of extent of excavation below is based on Geotechnical Report. In case of discrepancy, information in Geotechnical Report shall take precedence.

5. Backfilling of Retaining Walls: Place after comp letion and inspection of waterproofing. Adequately shore retaining walls during backfill operation. Unless adequately shored, do not place backfill behind building structure retaining walls until concrete at elevated floor levels adjacent to walls are completely poured and have cured for at least 7 days at site walls, concrete shall reach full design strength prior to backfilling unless adequately shored.

6. Retaining Wall Design Values:

A. Active earth pressure: __40_ pcf (triangular) At Level Backfill / __60__ pcf (triangular) at 2H:1V Backfill B. At-rest earth pressure: __60_ pcf (triangular) A t Level Backfill / __80__ pcf (triangular) at 2H:1V Backfill

7. Soil observation shall be performed by the Geote chnical Engineer per Geotechnical Report.

EXTENT OF OVER
EXCAVATION and

RE-COMPACTION
PER

GEOTECHNICAL
REPORT
X
1 X
1 SPREAD FOOTING, CONT.

FOOTING, OR MAT FOUNDATION
X
1 X
1 X
1 SITE FEATURE

EXTENT OF OVER
EXCAVATION and RE-

COMPACTION PER

GEOTECHNICAL REPORT
X
1 E. REINFORCING STEEL

1. Reinforcing Steel: All bars shall be deformed.

A. All bars unless indicated otherwise: ASTM A615, Grade 60 B. Bars to be welded: ASTM A706, Grade 60
C. Additional Requirements for Bars, Excluding Ties , for vertical bars in Shear Walls: No additional requirements if ASTM A706, Grade 60 bars used. ASTM A615, Grade 60 bars are permitted provided actual yield strength based on mill tests does not exceed specified yield strength by more than 18,000 psi (retests shall not exceed this value by more than an additional 3,000 psi) and ratio of actual ultimate tensile stress to actual yield stress is not less than 1.25.

2. Wire and Spiral Reinforcing:

A. Smooth welded wire fabric (W.W.F.): ASTM A1064, Fy =65 ksi, flat sheets only - do not use rolled mesh. Lap 1-1/2 wire spaces (1 foot minimum). Offset laps in adjacent sheets to avoid continuous laps.

B. Deformed wire stirrups (D4 and larger only): AS TM A1064, Fy =65 ksi C. Spiral reinforcing: ASTM A1064, Fy =65 ksi

3. Reinforcing shall be placed in accordance with t he American Concrete Institute Standard 318 (ACI318) and Concrete Reinforcing Steel Institute's (CRSI) "Manual of standard practice". Reinforcing shall be kept clean and free of rust.

4. Provide all accessories needed to support reinfo rcing in the positions shown in the drawings. Chairs and spacers for reinforcing shall be non-ferrous of plastic coated when resting on exposed concrete surfaces.

5. Shop Drawings: ACI 318-19. Show reinforcing st eel placement including sizes, quantities, spacing, clearances, splice locations, lap lengths, and concrete coverage's and submit to Architect (Structural Engineer). Promptly notify Architect (Structural Engineer) prior to developing shop drawings if insufficient clear distances between reinforcing steel and other congestion is encountered. Notify Special Inspector of adjustments made from approved Contract Documents which are indicated on accepted shop drawings that facilitate field placement of reinforcing steel and concrete. All bars shall be marked so that they can easily be identified by the project inspector after installation.

6. Lap Splices: At concrete, Provide Class B splice s per 04/S6.01 UNO. At masonry provide, 72db lap splice length UNO. Splice bars only at locations indicated. If additional splice locations are proposed, promptly notify Architect (Structural Engineer) prior to developing shop drawings.

A. Splices in Walls: Locate splices in horizontal bars at well-staggered locations. Do not splice vertical bars except at horizontal supports such as floor and roof diaphragms.

7. Mechanical and Welded Splice: Mechanical Splice and Welded Splice are to be used only at locations indicated. Notify Architect (Structural Engineer) of all instances prior to developing shop drawings.

A. Mechanical Splice: Mechanical couplers shall have current Evaluation Report and satisfy ACI requirements for type 2 coupler for the applicable bar size / grade designation.

B. Welded Splice: Welded splice shall develop at lea st 125 percent of the yield strength of the spliced bar for the applicable bar size and grade designation

8. Minimum Clearances Between Parallel Reinforcing Steel Including Distance Between Sets of Spliced Bars: 1 inch, 1 bar diameter, or 4/3 times the minimum aggregate size whichever is greater. 1-1/2 inches, 1-1/2 bar diameters, or 4/3 times the minimum aggregate size whichever is greater, at columns, piers, and pilasters only. For bundled bars, minimum clear distances between units of bundled bars shall be same as single bars except bar diameter is derived from equivalent total area of bundle.

9. Minimum Concrete Coverage: Place bars as near t o concrete surface as the following minimum coverages permit, unless noted otherwise:

A. Slabs on Grade - locate at center of slab.

B. Slabs Supporting Earth Above - 1-1/2 inches from top.

C. Formed Concrete Exposed to Earth or Weather - 1-1 /2 inches (#5 and smaller); 2 inches (#6 and larger) D. Concrete Poured Against Earth (Unformed) - 3 inch es E. Walls Above Grade, Exposed to Weather - See C. abo ve F. Walls Above Grade, Not Exposed to Weather 3/4 inc h (#11 and smaller); 1-1/2 inches (#14 and larger) G. Columns (Clear to Face of Ties) - 1-1/2 inches
H. Beams (Clear to Face of Ties) - 1-1/2 inches
I. Structural Slabs, Not Exposed to Weather (Top an d Bottom) - 1 inch (#8 and smaller); 1db (#9 and larger) J. Structural Slabs, Exposed to Weather - See C. abo ve

10. Dowels between footings and vertical wall & col umn bars shall match the size, grade and spacing of the column up wall vertical reinforcing and be lapped with a class B lap splice, UNO.

11. Dowels at Construction Joints: Provide dowels matching size and quantity of reinforcing steel interrupted at construction joints, unless detailed otherwise.

12. Placement of Bars in Walls (unless detailed oth erwise): Place vertical bars closest to wall surfaces at curtains containing vertical and horizontal bars of the same size. In curtains which vertical and horizontal bars are of different sizes or spacing, place layer with most steel area closest to near wall surface.

13. Bars Terminating at Walls, Columns, Beams, and Foundations: Extend bars to within 2 inches (3 inches at concrete poured against earth) of far face of wall, column, beam, or foundation and provide standard hook unless detailed otherwise.

14. Bars Interrupted by Structural Steel: Extend b ars to within 2 inches of steel face and provide standard hook unless detailed otherwise.

15. Welding: AWS D1.4, edition adopted by applicab le code.

A. Acceptable Reinforcing Steel for Welding: ASTM A706. If welding of reinforcing steel other than A706 is desired, submit proposed procedure, indicating conformance to Applicable Code and requirements of Governing Code Authority, to Architect (Structural Engineer) for acceptance and to Governing Code Authority for approval prior to execution.

B. Rebar to rebar weld not allowed except where spe cifically indicated on plans. Provide electrode E80XX (80 ksi) where permitted.

C. Welder Certification: As required by Governing Code Authority.

D. See welding notes in Structural Steel Section of these notes for additional requirements.

16. Bending: Bend cold unless otherwise accepted b y Architect (Structural Engineer). Do not field-bend reinforcing steel bars embedded in concrete unless otherwise accepted in writing by Architect (Structural Engineer).

17. Reinforcing Steel Allowance: In addition to re inforcing steel indicated in Contract Documents, allow for an additional 2 tons of reinforcing steel to be constructed under direction of Architect (Structural Engineer) during construction. Direction will be given during multiple occasions. Reinforcing steel under this allowance will be of any size, shape and grade. Quantity of pieces and location in Project will vary. Include in this allowance fabrication and erection and necessary construction services such as shop drawing preparation, and access for inspection. Submit expenditures in writing for any part of this allowance to Architect (Structural Engineer) prior to fabrication and erection. The unused portion of this allowance shall be credited to the owner at the completion of the project.

18. In-plant fusion welding of holding wires to ties , stirrups and hoops in beams, columns and grade beams to preassemble reinforcing steel cages is permitted under the following conditions per CBC 2022 1903.8:
a. Fusion welding is not allowed to longitudinal re inforcing steel in any beam, column or grade beam. The holding wire area shall not exceed 5% of the beam, column or grade beam cross sectional longitudinal steel area. b. Fusion welding of holding wires to the ends of t he reinforcing steel placed in mats (spread footings, slab reinforcement, etc.) provided the fusion weld occurs within 6 bar diameters of the free end of the bar (e g. not allowed at the end of coupled, t-headed or weld spliced bars).
c. Fusion welding of holding wires shall not occur on a bent portion of a reinforcing bar. After holding wire has been fusion welded to a reinforcing bar, that bar may not be bent where the fusion weld occurs. d. Contractor to submit complete shop drawings indi cating which members will use fusion welding process for preassembly.

Provide complete details indicating the size of stirrups, holding wires and welding requirements. e. Holding wires shall conform to ASTM A1064.
f. All reinforcing steel to be welded shall comply with ASTM A706 Grade 60. g. Contractor to submit complete shop welding progr am outlining the following:

1. Type of specific fusion welding machine (i.e. Sch nell IDEA 12/25 Machine, etc.)

2. Periodic inspection of the in-plant welding.
h. Fusion welded reinforcing steel shall have one t ensile test taken from one specimen sampled at a rate of 2.5 tons or fraction thereof of each size of reinforcing steel fusion welded. No bend test is necessary. The specimen shall have a holding wire attached to it that need not be removed. The elongation requirements shall comply with the ASTM of reinforcing steel specified on the construction documents (e g. if A615 is specified, but A706 is used due to the welding requirement, then A615 elongation requirements shall be satisfied).

L The use of fusion welding shall conform to ACI318 -19 26.6.4. j. If field conditions result in conflicts with oth er structural members (ex. anchor bolts) the rebar must be relocated in the field to avoid said conflicts.

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"

CIVIL ENGINEER DATE
RCE EXP.

REVIEWED BY:

INSPECTOR DATE

SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

GENERAL NOTES
S0.01
Checker
MONROE ST. POOL REPLACEMENT

GENERAL NOTES
09/30/25
256
57 203
08/09/2024
203
F. CAST-IN-PLACE CONCRETE

1. Applicable Standards: ACI 318 and ACI 301 except as amended in California Building Code Chapter 19 and as modified by supplemental requirements herein. Concrete mixing shall comply with ASTM C94.

2. Portland Cement: ASTM C150, type II. Submit mill test with certification of compliance to Architect (Structural Engineer)

3. Aggregates:

A. Normal Weight Concrete Aggregate: ASTM C33 for a ggregates of natural sand and rock. Maximum aggregate size is 1-1/2 inches at foundations and slabs on grade and 1 inch elsewhere.

B. Light Weight Aggregate for Structural Concrete: ASTM C330, expanded shale light weight aggregate.

4. Minimum 28-Day Concrete Compressive Strengths an d Types:

Concrete Unless Otherwise Indicated on
Structural Drawings
Footings and Grade Beams
Concrete Walls
Concrete Slabs on Grade
Equipment Curb/Pad Over Metal Deck
Concrete fill on Metal Deck
4000 psi normal weight (145 pcf)
4000 psi normal weight (145 pcf)
5000 psi normal weight (145 pcf)
4000 psi normal weight (145 pcf)
4000 psi normal weight (145 pcf)
4000 psi light weight (115 pcf)

0.5 0.5

0.5 0.45

0.5 0.45

5. Slump: Per ACI 301, CH. 4 and CBC section 1705.3 .

6. All concrete above grade, including, slab on gra de, deck fill, wall, topping slab, stair landing and tread shall have 1.5 pounds of 1 1/2" long fibrous reinforcing per cubic yard of concrete.

7. Lean Concrete: Where specifically indicated, con taining 2 sacks of cement per cubic yard of concrete. Use only where specifically called for.

8. Non-shrink Grout: ASTM C109, cementitious, non-m etallic attaining a compressive strength of 8000 psi.

9. Concrete Mix Design Submittal: Prior to ordering concrete, submit for each compressive strength and type of concrete required designed, signed, and sealed by a registered Civil or Structural Engineer in State of California to Architect (Structural Engineer), Special Inspector and to Governing Code Authority complying with California Building Code, Chapter 19.

10. Construction Joint: Roughen surface to 1/4-inch amplitude. Clean, remove laitance, thoroughly wet and remove standing water before placing new concrete. Submit to Architect (Structural Engineer) at least 14 days prior to placing concrete indicating locations of construction joints and extent of pours. Place joints at locations to minimize effects of shrinkage as well as being placed at points which least impair strength of structure. Provide dowels as directed.

11. Embedments and Penetrations in Concrete: No pen etration through structural concrete is permitted unless shown in these drawings or specifically accepted in writing by Architect (Structural Engineer). Do not cut any reinforcing.

A. Pipes, Sleeves, Conduits, and Ducts: Not permitt ed embedded or penetrating concrete spread footings, columns, walls or concrete cast over metal decking, except as shown in these drawings.

B. Conduits Embedded in Structural Concrete Slabs: Not permitted unless limited to two layers of 1 inch, and 1/6 slab thickness. outside diameter conduits and smaller spaced at least 3 inches center to center and within middle third of slab thickness. No conduit embedded in concrete cast over metal decking is permitted. No aluminum conduit is permitted.

12. Chamfered Corners: Provide 3/4-inch chamfer at exposed corners of columns, beams and walls except where structural walls are laid flush with column or beam faces, unless detailed otherwise.

13. Curing: Maintain concrete above 50 degrees Fahr enheit and in a moist condition for a minimum of 7 days after placement unless otherwise accepted by Architect (Structural Engineer).

14. Non-Structural Topping slab shall be normal wei ght concrete reinforced with 6x6-W3.5x3.5 W.W.F. at center line of slab. See plans & details for information on concrete fill over metal deck.

Element Compressive Strength and
Type of Concrete
Max. W/C
Ratio

15. No more than one class of concrete shall be on s ite at one time.

16. The maximum size for a single elevated concrete slab pour shall be 25,000 sq. ft. and shall have a maximum length to depth ratio of 2:1.

17. The maximum water-soluble chloride ION (CI) cont ent in concrete by percentage of weight cement is 0.30.

18. Where "Styrofoam" indicated on plans provide Po lystyrene product conforming to ASTM D6817. Foam shall have a minimum density of

0.70 lb/ft3 when tested in accordance with ASTM D1622. Foam shall have a minimum compressive strength of 2.2psi at 1 percent deformation when tested in accordance with ASTM D1621.

G. PROPRIETARY ANCHORAGES and FASTENERS

1. Anchorages:

A. Drill and Epoxy Anchors:
i. At Concrete: Hilti HIT-RE 500 V3 adhesive anchor system complying with ICC-ES Evaluation Report ESR-3814. ii. At Masonry: Hilti HIT-HY 270 adhesive anchor system complying with ICC-ES Evaluation Report ESR-4143. iii. Provide anchor type, size and embedment as indicated in details. iv. Overhead applications must be installed using the Hilti HIT-SZ piston plug system.

B. Mechanical Anchors:
i. At Concrete: Hilti KB-TZ2 carbon steel expansion anchor complying with ICC-ES Evaluation Report ESR-4266. ii. At Masonry: Hilti KB-TZ2 carbon steel expansion anchor complying with ICC-ES Evaluation Report ESR-4561. iii. Where mechanical anchor is exposed to weather, provide stainless steel anchor conforming to the ICC-ES Evaluation Report in lieu of carbon steel.

C. Welded Shear Studs: Nelson S3L flux filled, head ed stud anchors, 65,000 psi minimum ultimate tensile strength conforming to ASTM A29, automatically end welded in field and complying with ICC-ES Evaluation Report ESR-2856.

D. Welded Deformed Anchors: Nelson D2L, cold rolled , deformed steel reinforcing bars conforming to ASTM A1064 and complying with ICC-ES Evaluation Report ESR-2907.

2. Fasteners:

A. Powder Actuated Fasteners: Hilti Low-velocity Po wder Actuated Drive, 0.157" diameter (X-U), complying with ICC-ES Report ESR-2269. Provide appropriate washer between fastener head and light gauge metal or wood surface. Shot pins shall not be used @ PT slab or beams.

B. Self-Drilling Metal Screws (Indicated "Screws" o r "SMS" on Drawings): Hilti Self Drilling Screw complying with current ICC-ES Evaluation Report ESR-2196.

C. Concrete Screws: Hilti KH-EZ carbon steel screw anchor complying with ICC ES Evaluation Report ESR-3027.

D. Masonry Screws: Hilti KH-EZ carbon steel screw anchor complying with ICC ES Evaluation Report ESR-3056.

E. Where Concrete or Masory Screws are exposed to w eather, provide stainless steel anchors conforming to the ICC-ES Evaluation Report in lieu of carbon steel.

3. Installation: See manufacturer's written instruc tions and referenced ICC-ES evaluation report. Contractor shall arrange an anchor manfacturer's representative to provide onsite installation training for all anchor products specified.

A. Prior to drilling holes for post-installed ancho rs, contractor shall locate existing rebar, prestressing tendons, post-tensioning tendons, and embedded utilities using non-hazardous, non-destructive methods with accurate location tolerances (plus or minus 1/4-inch). Do not cut, hit, or otherwise damage existing rebar or tendons during anchor installation.

B. Drilling Holes in Existing Concrete or Masonry f or Anchorages: Use non-pneumatic, rotary hammer tools with ANSI compliant non-rebar cutting drill bits to drill holes of proper tolerances. Locate existing rebar including prestressing and post-tensioning tendons using non-hazardous, non- destructive methods with accurate location tolerances (plus or minus 1/4-inch) prior to drilling holes to avoid cutting or damaging Holes shall be thoroughly cleaned per manufacturer's written recommendations prior to installation of anchorages.

C. Deleterious Materials: Keep anchorages, includin g holes for drill and epoxy anchors and mechanical anchors, free of dust, grease, and other materials that impair bond.

D. Use of diamond core bit with roughening tool for anchor holes requires approval from Engineer of Record prior to drilling. Unless otherwise shown in the drawings, all holes shall be drilled perpendicular to the concrete surface.

E. Embedment Depths:
i. Mechanical Anchors: Embedment depths noted in drawings are the effective minimum embedment UNO. Refer to applicable evaluation report for the corresponding minimum hole depth and nominal embedment. ii. Screw Anchors: Embedment depths noted in dra wings are the nominal minimum embedment UNO. Refer to the applicable evaluation report for the corresponding minimum hole depth.

A. Anchor installer certification is required for a ll installers of drill and epoxy anchors in horizontal or upwardly inclined orientation. Installer qualification must be provided to the inspector prior to installation.

B. Installation Torques for Expansion Anchors shall be as noted:

4. Provide testing of post-install anchors as follows:

A. At expansion anchors and screw anchors: Provide installation using torque as noted above or per most recent ICC-ES Report.

B. At Drill and Epoxy anchors: Provide pull testing to tension values noted on corresponding detail(s) or provided by SEOR. Apply testing to 10% of anchors at each condition. If failure occurs, increase frequency to 100% until 20 consecutive anchors pass pull testing, then resume initial frequency. If subsequent failures occur, notify SEOR for further direction

I. Installation Torques for Screw Anchors shall be as noted:

Nominal
Anchor
Diameter
Expansion Anchor Installation Torque (ft-lb)
Into Concrete Into Masonry
KB-TZ2
Carbon Steel
KB-TZ2
Stainless Steel
KB-TZ2
Stainless Steel
KB-TZ2
Carbon Steel
1/4" 4 6 4 6
3/8" 30 30 15 15
1/2" 50 40 25 25
5/8" 40 60 30 35
3/4" 110 125 50 50
Nominal
Anchor
Diameter
Screw Anchor Installation Torque (ft-lb)
Into Concrete Into Masonry
Hilti
KH-EZ Hex
1/4" 18
3/8"
1/2"
5/8"
3/4"
Note: 1/4" dia. Hilti KH-EZ P, PM & PL in concrete shall have installation torque of 18 ft-lb.

Hilti

KH-EZ C
Hilti

KH-EZ CRC
Hilti

KH-EZ E & KH-EZ I
Hilti KH-EZ
(Hex, P, PM, PL & C)
Hilti

KH-EZ CRC
N/A 18 21 N/A
40 (19 @ h nom <2.5") 40 40 22 20
45 N/A 45 N/A 34 25
85 N/A 85 N/A 38 35
95 N/A 85 N/A 70 45
G. PROPRIETARY ANCHORAGES and FASTENERS (CONT.)
H. METAL DECKING

1. Metal Decking and Accessories: Verco Manufacturi ng Company, type and gauge as indicated on structural drawings, ASTM A653-SS grade 50 minimum conforming to IAPMO report ER-2018, G60 coating, unless heavier galvanized coating is indicated in specifications. Run deck units continuous over three or more spans where possible, deck is designed for unshored construction, uno Provide vented deck where vapor impervious material occurs over concrete fill.

2. Deck Welding: AWS D1.3 using prequalified proced ures.

A. Qualification of Welders: Welders shall be expe rienced in welding light-gauge steel and using prequalified procedures. Erector shall establish welding procedure for arc spot welding of metal decking to structural steel, for each gauge of decking to be used. Prior to deck erection, each welder shall be qualified using this procedure and witnessed by Special Inspector. See California Building Code, Chapter 22 and 17, for additional qualification requirements.

3. Shop Drawings: Submit to Architect (Structural Engineer) for review. Shop drawings shall include layout of deck, type of deck, methods of attachment, and all deck openings larger than 1'-0".

4. Limits to Non-Structural Items Suspended From Co ncrete Filled Metal Decking and Bare Metal Decking:

A. Hangers supported by metal decking with structur al concrete fill may be installed using ICC-ES approved anchorage systems. Limit hangers to supporting duct work 6 square feet in cross sectional area maximum, 3-inch diameter pipe maximum, and acoustical ceilings. Locate hangers two flutes apart when they occur on same deck span. Support larger duct work and piping for structural beams or columns as shown in typical details. Do not support utilities, ductwork, piping conduits, and etc. from metal deck without concrete . See typical details for hanger details.

B. Hangers supported by metal decking without struc tural concrete fill may be used for 12"x16" max ducts, 1-1/2" diameter pipes or ceilings. The hangers may be attached w/ 3/8" round x 12" long bars located above and perpendicular to the deck flutes. Locate hangers two flutes apart when they occur in the same deck span.

5. Pre-punched Holes in Metal Decking and Accessori es: Metal deck welding and installation of welded shear studs are not permitted through single layer sheets greater than 16 gauge (G90 MAX), nor through double layer sheets greater than 20 gauge (G60 MAX), nor through sheets with total galvanized coating thickness greater than 1.25 ounces per square foot. Provide pre-punched holes as necessary. Provide closure angle at all openings per typical details.

6. Excess Structural Concrete: Concrete filled met al decking and steel framing will deflect during placement of concrete. These deflections will require placement of concrete in excess of amount based on nominal dimensions in order to bring slab within tolerances of a horizontal plane. Provide excess concrete at no cost to Owner.

7. Deck shall be layed out such that low flutes lan d on each parallel support wherever possible. Provide filler deck accessory where low flutes do not align with parallel framing. Provide 2" minimum bearing at each support and 2" lap at ends of decking panels.

8. Composite slabs:

A. See "Proprietary Anchorage and Fasteners" notes for welded headed studs.

B. Stud welding, inspection and testing shall confo rm to AWS D1.1, CH. 7.

C. 18 gage or thicker decking shall not be lapped w here welded studs are attached through decking.

J. STRUCTURAL STEEL (CONT.)
k. List of applicable electrical characteristics fo r process employed. Clearly indicate specific values required for each welding pass. These electrical characteristics shall include at a minimum the following:
• Electrode diameter.
• Type of current and acceptable ranges of current measured in amperage. For wire feed processes, indicate manufacturers' recommended melt-off rate, deposition rate, and wire feed speed. • Voltage (for all processes).
• Actual field condition travel speed and manufactu rer's data for travel speed. • Electrode extension (stick out) for wire feed pro cesses. • Amperage, voltage and electrode extension (as app licable) shall be within filler metal manufacturer's recommendations (compare to AWS D1.1, Section 3.6 and 3.7).
• Electrode manufacturer's technical information, w ith identification number listed, and welding parameter recommendations.

F. Welding Electrode (Filler Metal): E70xx (70 ksi) uno, provide filler metal with Charpy V-notch toug hness of 20 ft/lbs at -20 degrees Fahrenheit at complete penetration groove welds.
a. Welding Electrode (Filler Metal): E70xx (70 ksi) u.n.o., provide filler metal with Charpy V-notch toughness of 20 ft/lbs at -20 degrees Fahrenheit at complete penetration groove welds.
b. Welds indicated as part of the "SFRS" shall comp ly with AISC 341 sections A3.4a and I2.3. These welded connections shall be made with a filler metal achieving a minimum Charpy V-notch toughness of 20ft/lbs at a temperature lower than 0°F. c. Welds indicated as "Demand Critical" (DC) shall comply with AISC 341 sections A3.4b and I2.3. These welded connections shall be made with a filler metal achieving a minimum Charpy V-notch toughness of 20ft/lbs at a temperature lower than 0°F, and a filler metal producing welds that have a minimum Charpv V-notch toughness of 40ft/lbs at temperature lower than +70°F.

G. Welding Toughness Requirements: Certify conforma nce to Charpy V-notch toughness requirements with tests by an independent testing laboratory for each AWS classification, manufacturer and trade name. Testing procedures shall be in accordance to Applicable Welding Standard and AWS D1.8
H. Fabricators: Perform shop welds by fabricators a pproved by LA City or AISC. a. Welder Qualification: Welders, regardless if Wor k is performed in shop or in field, shall be qualified for the Work they will be doing and shall have certifications current and acceptable to Governing Code Authority. b. Special inspection shall be required for all wel ding, as required by governing code authority.

I. Welds Exposed to View:
a. Faces of fillet welds exposed to view shall have as-welded surfaces that are reasonably smooth and uniform. No finishing or grinding shall be required, except where clearances or fit of other items may so necessitate. b. Partial and full penetration welds exposed to vi ew shall be ground smooth and flush with finish surface of steel. Remove backup bars and weld tabs. Fill holes with weld metal or body solder and smooth by grinding or filing.

J. Groove Preparation: Clean groove preparation the rmal cuts by grinding.

K. Termination of Welds: Terminate at joint ends in a manner that ensures sound welds. Use extension bars and run-off tabs whenever necessary.

L. Hand-held Calibrated Amp and Volt Meters: To be used by fabricator, erector and inspectors to assure proper amperage and voltage of welding process. Measure amperage and voltage at arc. Verify travel speed and electrode stick-out in compliance with electrode manufacturer's recommendations and with approved WPS.

M. Storage of Electrodes: Adhere to Section 5.3 of AWS D1.1.

N. Weld each flange of moment frame beam to column connections in one continuous process without cooling below pre-heat temperature.

O. Welding of ASTM A913 Materials: Perform accordin g to requirements of latest edition of AWS standard, structural drawings and specifications, whichever is more stringent.

P. Minimum Fillet Weld Size: Where minimum fillet w eld size, as stipulated by AISC Section J2 and Table J2.4, exceeds fillet weld size indicated on structural drawings, use AISC stipulated size.

Q. Minimum Groove or Butt Weld Size: Provide comple te penetration unless indicated otherwise.

R. Weld Length: Length of welds shown are net effec tive lengths. Where length of weld is not indicated, provide weld full length of joint.

6. Shop Drawings: Submit To Architect (Structural E ngineer) for review and, upon request, to Governing Code Authority. Include sequence of erection procedures from approved WPS:

7. Fabrication: Perform in shop certified by AISC o r City of Los Angeles.

A. Moment Connections: Orient flange stiffener plat es and cap plates used in moment connections so that rolling direction of plate is parallel with direction of principal stress.

B. Horizontal Members: Place natural camber up.

C. Filler Plates: Provide at splices of parts havin g more than 1/8-inch difference in thickness. Filler plates to match grade of material spliced.

8. Cleaning: After fabrication, clean steel surfaces free of rust, loose mill scale, and oil.

9. Oversized Holes for Anchor Bolts in Base Plates: Oversized holes in base plate may be provided at contractor's option in accordance with AISC Table 14-2 UNO. Where oversized holes are provided, provide plate washer with standard hole with minimum size per AISC Table 14-2 (3/8" thick min) UNO.

10. Exposure to Soil: Encase structural steel in lea n concrete with 4-inches concrete cover where exposed to soil.

11. Exposure to Weather: All structural steel (inclu ding connection elements) exposed to weather shall be hot dipped galvanized. Coordinate finishes with architect at AESS. At welding on galvanized members, remove and repair galvanization as required.

12. Structural Steel Allowance: In addition to the s teel shown or implied in this document, allow for an additional 2 tons of structural steel to be constructed at the direction of the Structural Engineer during construction. The allowed steel may be of any shape or sizes, including plates, wide flanges, tubes, pipes, channels, angles, and/or any other structural shapes. The number of pieces may vary. The locations of applications may vary. Direction may be given in multiple occasions during construction. The allowance should include all fabrication and construction related services, such as shop drawings, shop preparation, field erection and coordination, bolted connections and field welding. Expenditure of any part of this allowance shall be approved in writing by the Structural Engineer prior to any fabrication and erection.

13. Heavy Sections
a. Heavy sections shall comply with AISC 360-16 S ection A3.1c b. Heavy sections forming part of the "SFRS" shal l also comply with AISC 341-16 Section A3.3 c. Welded Splices including welds to baseplates shall comply with AISC 360-16 Section J1.5

14. See quality assurance note C-3 and C.4 for non-d estructive testing.

15. SFRS denotes items considered part of the "SEIM SIC FORCE RESISTING SYSTEM" (Refer to AISC 341-16 and AWS D1.8).

16. DC denotes welds considered "DEMAND CRITICAL" pe r AISC 341-16 Section A3.4B and I2.3

17. Field weld flag symbols indicate design intent but are not requirements. Whether a weld is to be made in shop or field is means and methods and to be coordinated by contractor.

18. Where bent plates specified cannot be bent due to thickness provide two plate pieces joined with a complete penetration weld.

J. STRUCTURAL STEEL

1. Detailing, Fabrication, and Erection: AISC 360-1 6 "Specification for Structural Steel Buildings" and AISC 341-16 "Seismic Provisions for Structural Steel Buildings" except as amended in Applicable Code Chapter 22 and as modified by supplemental requirements herein.

2. Structural Steel: Provide readily identifiable s tructural steel in compliance with Applicable Code Section 2202.1. Furnish structural steel complying with the following ASTM standard specifications, unless noted otherwise:

A. Structural Steel Unless Indicated Otherwise: AS TM A992, Grade 50 B. Angles and Channels: ASTM A36
C. Plates: ASTM A572, Grade 50
D. Pipes: ASTM A53, Grade B (35 ksi)
E. Rectangular Tubes: ASTM A500, Grade C (50 ksi)
F. Round Tubes: ASTM A500, Grade C (46 ksi) G. Anchor Bolts: ASTM F1554, grade 55 (weldable)

3. Holes for Bolted Connections and Anchor Bolts: A ISC "standard" holes limited to 1/16-inch larger in diameter than nominal bolt diameter, unless noted otherwise. See Note 9, for oversized holes for anchor bolts in base plates.

4. High Strength Bolts, Nuts and Washers: AISC "Spe cification for Structural Joints Using High-Strength Bolts." A. Hardened Washers: ASTM F436, under nuts except w here plate washers are used. Provide beveled washers where joint face slope is greater than 1:20.

B. Tightening: Snug tight for all high strength bol ts except tighten A325-SC and A490-SC bolts to at least the minimum proper tension according to AISC Specification.

C. Provide Class A Faying Surface or better at bolt ed connections indicated with "SC" type bolts.

D. All bolts parts of "SFRS" shall be "SC" type bol ts.

5. Welding:

A. Applicable Welding Standard: Applicable Code and latest adopted edition of AWS D1.1 including, but not limited to, the following:
a. Section 6.4 for qualified welders.
b. Section 4.2 and AISC 360-16 Specification Sectio n M2-2 for jumbo sections for preheat and interpass temperature requirements. c. Section 5 for arc welding.
d. Section 6 for inspection.

B. Pre-qualified and Non Pre-qualified Welds: Welds shall be pre-qualified in compliance with Applicable Welding Standard. Where non pre- qualified welds are to be used, qualify by test and procedure qualification test record complying with Applicable Welding Standard.

C. Work performed by Welders and Inspectors: Adher e to approved Welding Procedure Specification (WPS). Each welder and inspector shall retain a copy of WPS.

D. Pre-construction Meeting: Conduct to include Arc hitect (Structural Engineer), fabricator, erector, Contractor and inspectors to discuss Welding Procedure Specification (WPS).

E. Welding Procedure Specification (WPS): Fabricato r/erector to develop WPS in compliance with Applicable Welding Standard. Submit to Architect (Structural Engineer) for acceptance and Governing Code Authority for approval prior to fabrication. WPS submittal to include the following:
a. Welding manufacturers' specifications.
b. Information required by Applicable Code, Contrac t Documents and any other information necessary to produce welds that are in compliance with Applicable Welding Standard.
c. Detailed sequence of weld sketches addressing ef fects of welding heat for welds at joints and within seismic frame assemblies as a whole. Plan sequence of erection and welding to minimize locked in stresses and distortion considering effects of welding heat.

Procedures submitted shall result in completed connections which comply with design intent of structural drawings. No deviation from structural drawings is permitted unless otherwise accepted by Architect (Structural Engineer) and approved by Governing Code Authority.
d. Welding parameters recommended by electrode manu facturer. e. List of applicable base metal types and thicknes ses. f. Welding joint sketches including joint type, wel d type, joint geometry, and applicable dimensions. Individual weld passes shall be identified in sketches and numbered to identify the sequence of their deposition. Sketches shall identify the maximum layer thicknesses and bead widths. In no case shall layer thickness exceed 1/4-inch, nor shall maximum bead width exceed 5/8-inch. g. Applicable welding process.
h. Position of welding.
i. List of filler metal per Applicable Welding Stan dard and electrode specification and classification. Include details showing shielding material to be used.
j. Minimum preheat requirements, interpass temperat ures and post weld heat treatment. Minimum specified preheat shall meet requirements of AWS D1.1, table 3.2, and AISC 360-16 Section M2-2 requirements for jumbo sections.

K. LIGHT GAUGE METAL FRAMING GENERAL NOTES (CONT.)

8. Securing Studs and Braces: Plumb, align and tigh tly nest in both upper and lower tracks with secure attachment to both flanges of tracks.

Splices in axial loaded studs and braces are not permitted.

9. Self-Drilling Screws: See General Notes.

10. Welding: ANSI/AWS D1.3 and CBC Section 2210A. Wire tying of framing components is not permitted. a. Welder Certification: Governing Code Authority.
b. Electrodes: E60XX at 33 ksi members, E70XX at 50 ksi members. c. Touch-Up: Zinc-rich paint at galvanized members and regular paint at carbon sheet steel.

K. LIGHT GAUGE METAL FRAMING GENERAL NOTES

1. Applicable Standards: CBC Section 2210A and "Spec ifications for the Design of Cold-Formed Steel Structural Members" of AISI, S100-2016 Edition including amendments and referenced standards. Minimum yield strength shall be as follows:
a. 43 mils (18 gauge) and lighter (33 ksi):

1. Carbon Sheet Steel to be Painted: ASTM A1003 , Grade 33.

2. Galvanized: ASTM A653, Grade A.
b. 54 mils (16 gauge) and heavier (50 ksi):

1. Carbon Sheet Steel to be Painted: ASTM A100 3, Grade 50.

2. Galvanized: ASTM A653, Grade D.

2. Manufacturer and Properties: Member of Steel Stu d Manufacturer's Association (SSMA) complying with ICC-ESR 3064P or Cemco compything with ICC-ESR 3016. Provide punched studs as scheduled in these drawings with minimum effective section properties as indicated in referenced evaluation report.

3. Minimum Gauge Thicknesses: Indicated properties are based on the following thicknesses:
12 ga. - 0.1017 inch, 97 mils 14 ga. - 0.0713 inch, 68 mils 16 ga. - 0.0566 inch, 54 mils 18 ga. - 0.0451 inch, 43 mils 20 ga. - .0329 inch, 33 mils

4. Track Material: Provide unpunched track of dimens ions to ensure proper fit of studs with minimum effective section properties as indicated in referenced evaluation report.

5. Lateral Bridging for Studs: Required when rigid wall finish does not continue full height on either or both sides of studs. Install horizontal straps or cold-rolled channels as shown and in accordance with Section D3 of AISI specification. See typical det ails.

6. Lateral Blocking for Joists: Joists shall be bra ced by full depth blocking at all points of support. Joist blocking shall also be provided at the following locations: See typical details.

7. Joist Web Punch-Out Locations: Web punch-outs sh all not be located closer than twice the member depth from edge of bearing support or concentrated loads, 12" minimum. Do not provide punchouts at tracks.

1. Specified Compressive Strength of Masonry (f'm): 2000 psi typical unless noted otherwise.

2. Verifying Specified Compressive Strength of Maso nry (f'm): Use masonry prism testing method unless otherwise acceptable to Architect (Structural Engineer). Full allowable stresses are used in design. Submit masonry prism data for each type and compressive strength of masonry required, with a professional engineer's signature and state of California seal, to Architect (Structural Engineer). Compliance with minimum required compressive strength shall be based on Applicable Code Section 2105.2.

3. Concrete Block: ASTM C90, medium weight, attain ing a minimum compressive strength as required to meet specified compressive strength of masonry (f'm).

4. Face Brick: ASTM C216.

5. Portland Cement for Mortar and Grout: ASTM C150 , type I or II. Use of masonry cement or plastic cement is not permitted.

6. Aggregates for Mortar and Grout:

A. Aggregates for Mortar: ASTM C144.

B. Aggregates for Grout: ASTM C404, coarse type.

7. Mortar: ASTM C270, Type S.

8. Grout: ASTM C476, coarse type, attaining a mini mum compressive strength as required to meet specified compressive strength of masonry (f'm). However, in no case shall grout compressive strength be less than 2000 psi at 28 days.

9. Reinforcing Steel: Reinforcing steel section of general notes unless indicated otherwise.

10. Composite Masonry Wall Penetration Submittal: Submit for each wall indicating size and location of each wall penetration and opening as necessary by affected trades. Submit together with appropriate reinforcing steel shop drawings. Submit written statement from Special Inspector that no additional penetrations or openings were added to those shown in penetration submittal.

11. Reinforcing Steel Splices: Lap reinforcing ste el at splices a minimum of 72 bar diameters, except dowels in footings at base of walls shall splice a minimum of 72 bar diameters, unless noted otherwise. Where minimum clear distance between bars at adjacent splices is 3 inches or less, increase lap length 30 percent unless splices are staggered at least 24 bar diameters.

12. Dowels for Walls, Columns, Pilasters, and Piers : Match size and spacing of vertical reinforcing steel, unless noted otherwise. Set dowels to align with cells containing reinforcing steel.

13. Minimum Reinforcing Steel Clearances:

A. Minimum Clearances Between Reinforcing and Outsi de Face of Masonry: 2 inches except in no case shall clearance be less than 2-1/2 bar diameters.

B. Minimum Clearance Between Reinforcing and Inside Face of Grout Cell: 1/2 inch or 1 bar diameter whichever is greater.

C. Minimum Clearance Distances Between Parallel Rei nforcing: 1 inch or nominal bar diameter, whichever is greater. Increase to 1-1/2 inches or 1-1/2 times nominal bar diameter, whichever is greater, at columns, pilasters, and piers only.

14. Placement: Set courses in running bond pattern unless indicated otherwise. Set cells in vertical alignment. Provide flush mortar joints at surfaces to receive waterproofing or damp-proofing.

15. Grouting: Grout solid all cells. Mechanically vibrate grout in cells.

A. Grout Height Limits: CBC Section 2104.2.4 TMS 6 02, Article 3.5 D B. Horizontal Construction Joints: Hold grout 1 1/ 2 inches below top of masonry unit if work is stopped one hour longer.

C. Grout Cover Around Reinforcing Steel, Anchor Bol ts and Inserts Penetrating Masonry Shell: 1 inch minimum.

16. Horizontal Bars Terminating at Wall Ends and Op ening Jambs: Extend bars to within 2 inches of end of wall and provide standard ACI 90- degree hook unless detailed otherwise.

17. Control joints shall be provided as indicated o n Arch and per detail 01/S6.61. If not indicated on Arch, provide control joints at 25'-0" o/c maximum and coordinate w/ Arch.

L. MASONRY

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"

CIVIL ENGINEER DATE
RCE EXP.

REVIEWED BY:

INSPECTOR DATE

SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
12" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

GENERAL NOTES
S0.02
Checker
MONROE ST. POOL REPLACEMENT

GENERAL NOTES
UPDATE
09/30/25
256
58 203
3RD PLAN CHECK SUBMITTAL 07/21/2024

08/09/2024

203
Q. EXISTING CONDITIONS:

1. Field verify all conditions and dimensions prior to shop drawings production and fabrication of structural elements.

2. Where existing conditions vary significantly fro m those shown on these drawings, the Structural Engineer shall be notified prior to continued construction related to subject conditions.

3. Shore all existing construction as required.

4. All existing (E) connections at elements to be r eplaced shall be replaced or re-attached to match existing conditions u.n.o.

5. Verfity location of existing (E) rebar before fr abrication using non-destructive testing.

6. Verify location of existing (E) sleeve before dr illing holes(s) for bolt(s).

7. See "As-Builts" drawings for existing building d esign for items not shown or noted.

P. ROUGH CARPENTRY

1. Structural Lumber: Grade marked Douglas Fir-Lar ch structural lumber complying with Standard Grading Rules No. 17 (2018) of the West Coast Lumber Inspection Bureau. Provide air-dry lumber with 19 percent maximum moisture content. 4x and larger members may be provided green and air dried to 19 percent maximum moisture content

2. Classifications and Grades:

3. Plywood: U.S. Product Standard PS 1-19 and class ified as Exposure 1. Each sheet of plywood shall be identified with appropriate trademark of the American Plywood Association.

4. Pressure Treat Structural Lumber Bearing on Conc rete or Masonry: See Specifications. Provide hot dipped galvanized or stainless steel fasteners and hardware connectors where in contact with pressure treated structural lumber.

5. Nails: Common nails with dimensional properties complying with ASTM Fl 667. Install nails in compliance with Applicable Code Chapter 23, including Table 2304.10.2 2022 CBC (repeated below).

6. Bolts: ASTM A307 bolts with standard cut washer under bolt head and nut Provide holes for bolts 1/32 to 1/16 inch larger than nominal bolt diameter. Re-lighten bons prior to application of sheathing or finish.

7. Anchor Bolts: ASTM F1554, Grade 55, UNO.

8. Lag Screws: ANSI/ASME Standard B18.2.1 including Appendix I for lag screw dimensions. Pre-drill all holes. Hole at shank portion to match diameter of shank. Holes at threaded portion to be 40-70 percent of shank diameter and equal to length of threaded portion. Use soap and lubricants to facilitate installation. Driving with hammer is not permitted.

9. Wood Screw: ANSI/ASME Standard 818.6.1 for wood screw dimensions. Driving with hammer is not permitted.

10. Plate Washers: Provide under heads or nuts of b olts (including anchor bolts at sill plates) and lag screws per 09/S6.81 when anchoring wood.

11. Wood Hardware Connectors: Manufactured by Simps on Strong-Tie Company. Inc complying with ICC-ES Evaluation Report No's ESR-2105, ESR-2523. ESR-2549, ESR-2553. ESR-2604. ESR-2615, and ESR-3096. Install connectors using fasteners in acoordance with manufacturer's written instructions. Fill all holes to achieve maximum load capacity per manufacturer. For connectors requiring nails. use common nails unless shorter nails (sinkers) are specifically indicated.

12. Notching or Cutting Structural Lumber: Not perm itted unless specifically detailed or indicated.

13. Lateral Support for Beams. Rafters and Joists: Full Depth 2 inches thick continuous solid bloddng shall be proved at 8 feet on center or midspan, whichever is less

14. Provide 4x or 3 1/2" min. thick framing members at fire sprinkler lateral andlor longitudinal bracing attachment location.

Coordinate with fire sprinkler drawings for locations of pipe bracing required.

Member
Rafters and Joists Larger Than 2x4
2x4 Joists and Rafters
4x Beams, Headers and Stringers
Beams, Headers and Stringers Larger Than 4x
4x Posts
Posts Larger Than 4x
Studs, Plates and Blocking in bearing or shear walls
Studs, Plates and Blocking in non-bearing walls
Size Classification
2" to 4" thick, 2" and wider
2" to 4" thick, 2" and wider
2" to 4" thick, 2" and wider
Beams and Stringers
4" thick, 4" and wider
Posts and Timbers
2" to 4" thick, 2" and wider
2" to 4" thick, 2" and wider
Grade
No. 1
No. 1
No. 1
No. 1
No. 1
No. 1
No. 1
No. 2
All nails are common nails unless written acceptance by Architect (Structural Engineer) is attained.

1. Joist to sill or girder, toenail

2. Bridging to joist, toe nail each end

3. 1"x6" subfloor or less to each joist, face nail

4. Wider than 1"x6" subfloor to each joist, face na il

5. 2" subfloor to joist or girder, blind and face n ail

6. Sole plate to joist or blocking, typical face na il

7. Sole plate to joist or blocking, at braced wall panels

8. Top plate to stud, end nail

9. Stud to sole plate

10. Double studs, face nail

11. Doubled top plates, typical face nail

12. Doubled top plates, lap splice

13. Blocking between joists or rafters to top plate , toe nail

14. Rim joist to top plate, toe nail

15. Top plates, laps and intersections, face nail

16. Continuous header, two pieces

17. Ceiling joist to plate, toe nail

18. Continuous header to stud, toe nail

19. Ceiling joists, laps over partitions, face nail

20. Ceiling joists to parallel rafters, face nail

21. Rafter to plate, toe nail

22. 1" brace to each stud and plate, face nail

23. 1"x8" sheathing or less to each bearing, face n ail

24. Wider than 1"x8" sheathing to each bearing, fac e nail

25. 2" planks

26. Built-up corner studs

27. Built-up girder and beams
S. NAILING SCHEDULE (PORTION OF CBC TABLE 2304.10.2)
3-8d
2-8d
2-8d
3-8d
2-16d
16d @ 6" o/c
3-16d per 16"
2-16d
4-8d, toe nail or 2-16d, end nail
16d @ 24" o/c
16d @ 16" o/c
8-16d
3-8d
8d @ 6" o/c
2-16d
16d @ 16" o/c along each edge
3-8d
4-8d
3-16d
3-16d
3-8d
2-8d
3-8d
3-8d
2-16d at each bearing
16d @ 24" o/c
20d @ 32" o/c at top and bottom and staggered 2-20d
at ends and at each splice.

T. STATEMENT OF SPECIAL INSPECTION
Special Inspections shall be performed in accordance with Chapter 17 of the California Building Code and any local ordinance. (FILLED BOXES INDICATES REQUIRED ITEMS)
Section 1705 Special Inspections

1. Steel, section 1705.2 . All onsite structural steel fabrication and erection including welding, and high strength bolting is subject to special inspection per CBC Table 1705.2.3 Offsite fabrication may only be performed by an approved fabricator.

2. Concrete, section 1705.3 . All Structural Concrete is subject to special inspection per Table 1705.3 and local ordinance.

3. Masonry section 1705.4. Structural masonry elements, except for masonry fireplaces, are subject to special inspection.

4. High Load Diaphragms, section 1705.5 . The following describes high load diaphragms (diaphragms designed in accordance to Table 2306.2) subject special inspection requirements as described in section 1705.5.1, (plan sheet or detail reference is acceptable).

5. Soil, section 1705.6 . Footing excavations are subject to verification that proper depth and bearing material have been reached prior to placement of concrete per Table 1705.6 (Note: work performed under a grading permit is subject to separate special inspection requirements.)

6. Pile Foundation, section 1705.7 . Piles are subject to special inspection per Table 1705.7.

7. Pier Foundation, section 1705.8 . Piers are subject to special inspection per Table 1705.8.

8. Sprayed Fire-Resistant Material. Sprayed Fire-Re sistant applied to structural elements and decks are subject to special inspection per section 1705.15

9. Mastic and Intumescent Fire-resistant Coatings. Mastic and Intumescent Fire-resistant Coatings applied to structural elements and decks are subject to special inspection per section 1705.16.

10. Exterior Insulation and Finish Systems (EIFS). Exterior Insulation and Finish Systems (EIFS) are subject to special inspection per section 1705.17.

11. Other, section 1705.1.1. The following describe s additional systems or elements subject to special inspection as required by the Chief building Official, Engineer of Record, manufacturer's instructions or Evaluation Report: All those required by referenced Evaluation Reports, including Epoxy anchors per ICC ER-2322 and expansion anchors per ICC ER-1917.

12. Smoke Control, section 1705.19.

Section 1705.13 Special Inspections for Seismic Resistance The following are applicable to specified seismic force-resisting systems, designated seismic systems, and architectural, mechanical, and electrical components.

Seismic-Force Resisting Systems . The following describes the seismic-force resisting system(s) subject to special inspection per applicable section 1705.13 as indicated below:

13. Structural Steel, section 1705.13.1 Continuous inspection is required for structural steel welding in accordance with AISC 341.

14. Structural Wood Systems, section 1705.13.2 The following describes the nailing, bolting, anchoring and other fastening components subject to periodic special inspection

15. Cold-Formed Steel framing, section1705.13.3 The following describes the welding, screw attachment, bolting, anchoring and other fastening components such as struts, braces and hold-downs subject to periodic inspection.

16. Storage racks and access floors, section 1705.13.7 Periodic special inspection is required during the anchorage of storage racks 8 feet or greater in height.

17. Architectural components, section 1705.13.5. Periodic special inspection is required during the erection and fastening of suspended ceiling system, exterior cladding, interior and exterior nonbearing walls, and interior and exterior veneer.

18. Mechanical and Electrical Components, section 1705.13.6 . Periodic special inspection is required during the installation and anchorage of:

A. Electrical equipment for emergency or standby po wer system, B. Other electrical equipment,
C. The following piping system(s) and associated me chanical units intended to carry flammable, combustible or highly toxic contents:

D. The following HVAC ducts intended to carry hazar dous materials:

E. The following vibration isolation system:

19. Designated Seismic System Verifications, section 1705.13 . The special inspector shall verify the certificated of compliance per section 1705.13.4, and that labeling, anchorage and mounting conforms to the certificate for the following mechanical and electrical equipment:

20. Seismic Isolation System, section 1705.14.4 Periodic special inspection is required during the fabrication and installation for isolator units and energy dissipation devices.

Section 1705.14 Structural Testing for Seismic Resistance Note: Documentation referred to below shall be referenced and made part of the special inspector's daily and final report.

21. Masonry, section 1705.4 and TMS 402/602-16
A. The special inspector shall verify certificates of compliance prior to construction.

B. The special inspector shall verify tests and sub mittal per TMS 602 Tables 3 and 4 (Level 2 QA) C. The special inspector shall verify tests and sub mittal per TMS 602 Tables 3 and 4 (Level 3 QA)

22. Reinforcing and Prestressing Steel, section 1705.3
A. The special inspector shall verify certified mil l test reports for each delivery of reinforcing steel for steel used to resist flexural, shear and axial forces in intermediate or special moment frames, and boundary elements of special reinforced concrete or masonry shear wall.

B. ASTM A 615 reinforcing steel grade 40 or 60 used to resist flexural or axial forces in special moment frames and boundary elements in shear walls. The special inspector shall verify testing demonstrates requirements of ACI 318-19 section 20.2.2.5 are met
a. actual yield strength shall not exceed fy by more than 18,000 psi b. the ratio of actual tensile strength to actual y ield strength is not less than 1.25. (i) Actual yield strength based on mill tests does not exceed/j. by more than 18,000 psi (ii) Ratio of the actual tensile strength to the act ual yield strength is at least 1.25 (iii) Minimum fracture elongation in 8 in. shall be at least 14 percent for bar sizes No. 3 through No. 6, at least 12 percent for bar sizes No. 7 through No. 11, and at least 10 percent for bar sizes No. 14 and No. 18. (iv) Minimum uniform elongation shall be at least 9 percent for bar sizes No. 3 through No. 10, and at least 6 percent for bar sizes No. 11, No. 14, and No. 18.

C. ASTM A 615 reinforcing steel specified to be weld ed. The special inspector shall verify chemical testing report demonstrates weldability per ACI 318-19 section 26.6.4 and ANSI/AWS D1.4. Above documentation shall be referenced a nd made part of the special inspector's daily and final report.

23. Structural Steel, section 1705.14.1. The following describes required testing of welds, base metal, weld tab removal sites, and thermally cut surfaces of beam copes or access holes per CBC section 1705.13 and AISC 341. MT = Magnetic Particle Testing per AWS D1.8, UT = Ultrasonic Testing AWS D1.8. Testing procedures and acceptance criteria shall conform to AISC 341 and AWS D1.8. Testing shall be performed at a construction materials testing laboratory certified by the Authority Having Jurisdiction.

A. K-area welding- web area shall be MT'd for cracks in the k-area base metal within 3 inches minimum of the weld.

B. Complete joint penetration groove welds - All sha ll be UT'd for materials 5/16 inches or thicker.

C. Complete joint penetration groove welds - 25% of all beam to column connections shall be MT'd.

D. Base metal for lamellar tearing - UT testing for discontinuities behind and adjacent to weld fusion line for all complete joint penetration groove welded connections for tension loading in the through thickness direction of base metal greater than 1 1/2 inch thickness to connected piece greater than 3/4 inch.

E. Flange and web thicknesses exceeding 1 1/2 inche s.

F. Ends of welds from which a weld tab has been rem oved shall be MT'd. (Note: n/a for continuity plate weld tabs) G. MT percentage reduction protocol is as follows ( note- may not exceed that allowed by AISC 341):

H. High-strength bolting per AISC 341-16 J7.

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"

CIVIL ENGINEER DATE
RCE EXP.

REVIEWED BY:

INSPECTOR DATE

SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
12" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

GENERAL NOTES
S0.03
Checker
MONROE ST. POOL REPLACEMENT

GENERAL NOTES
09/30/25
256
59 203
3RD PLAN CHECK SUBMITTAL 07/21/2024

08/09/2024

203
A

CAISSON DETAIL

SECTION A -A
(3) TIES WITHIN 5" OF

CAISSON TOP
STD 90° HOOKS

STEEL POST PER LANDSCAPE/ARCH

TOP OF LOWEST EXT

OR BUILDING CONC

SLAB ON GRADE OR FINISH

GRADE ELEVATION

CONC CAISSON

PER SCHEDULE

STL POST PER PLAN W/
3/4"Øx4" LONG WELDED HEADED
ANCHORS EA SIDE @ 12" O/C (1st
SET OF ANCHORS 3" FROM BOTTOM

OF HSS) - WHERE OCCURS PER

SCHEDULE
TERMINATE TIE @

SEPARATE VERT
BARS W/ 135° HOOK,
TYP

WHERE ADJ TO SOIL
3" MIN CONC COVER

SEE SCHED
A
3" CLR.
1 1/2"
3"
3" CLR.
3" CLR.

PER SCHEDULE

CAISSON DIA
CAISSON DEPTH SCHEDULE 1'-0"

C A I S S O N S C H E D U L E
DIA

DESCRIPTION

CAISSON

DEPTH VERTICAL
BARS "Bv"
TIES

DESIGNATION REFERENCE
1A
1B
18" 4'-6" STEEL FENCE
1D
(6) #5 #3 @ 6"
1C
1E
1F
1G
1H
HEADED

STUDS REQ

POST MAX
HEIGHT
"H"

PEDESTRIAN GATE

VEHICULAR GATE
TRASH

ENCLOSURE GATE
---
---
---
---

SEE SEC A-A
8'-0" 04/L5.08

REINFORCEMENT PER

SCHEDULE
6" MIN LAP

STL POST PER

LANDSCAPE/ARCH
"H" TO TOP

OF POST
18" 5'-0" (6) #5 #3 @ 6" SEE SEC A-A 9'-0" 08/L5.08 & 02/L5.10 18" 5'-0" (6) #5 #3 @ 6" SEE SEC A-A 8'-0" 04/L4.04
18" 4'-6" (6) #5 #3 @ 6" SEE SEC A-A 6'-0" ----
NOTE: SEE LIGHT POLE MFR FOR

LIGHT POLE, BASE PLATE, &

ANCHORAGE INFO
3/4" CHAMFER UNLESS

INDICATED OTHERWISE

ON ARCH
(3) #4 TIES WITHIN TOP 5"
OF FTG - 1st TIE 1 1/2" FROM

TOP OF CONC

PREPARE COMPACTED FILL OR

UNDISTURBED SOIL
(6)#5 VERT BARS W/ #4
TIES @ 9" OC

FINISH GRADE OR

PAVING SURFACE
NOTE:

1. CONCRETE F'c = 3500 AT 28 DAYS

PVC CONDUIT

FIXTURE PER ELEC DWG

HEIGHT CAISSON
DEPTH
20'-0" MAX 5'-6"
DIA
24"

TOP OF CAISSON WHERE

OCCURS PER LANDSCAPE

HEIGHT CAISSON DEPTH
5"
4" CLR
TYP
3" CLR

DIA PER SCHED

CAISSON
NOTE:

CAST CAISSON FTG INTEGRAL WITH

CONT FTG

EXT GRADE OR PAVING PER

ARCH / CIVIL

CAISSON FTG CONT FTG
PER SCHED 06/-

WHERE CONT FTG

LONGITUDINAL BARS ARE OBSTRUCTED,

DRAPE BARS TO PASS OR ADD BAR OF SAME

SIZE FOR EA INTERRUPTED BAR AS SHOWN

CONT FTG TRANSVERSE BAR OR TIE
A

PLAN VIEW A -A

SECTION
A
CLASS "B"
SPLICE
CLASS "B"
SPLICE
2" TYP

REINF PER SCHED

CMU WALL THICKNESS
HEIGHT "H" WIDTH "W" CMU WALL

THICKNESS VERTICAL REINF

S C H E D U L E
#4 @ 16" ALT FACE
#5 @ 16" AT ALT FACE
#5 @ 16" EA FACE
#6 @ 16" EA FACE
#6 @ 16" EA FACE
6'-0" 3'-0"
8'-0" 4'-0"
5'-0" 10'-0"
13'-0"
15'-0" 7'-6"
6'-6"
8"
8"
8"
8"
10"
#5x 30" @ 16" OC WHERE CONC

SLAB OCCURS

DOWELS TO MATCH VERT REINF W/
STD 90° HOOKS AT BOTTOM OF FTG

VERT REINF PER

SCHEDULE

CONC BLOCK GROUTED

SOLID PER SCHEDULE
12"
#4 HORIZ @ 16" OC - PLACE AT ℄

OF WALL
EQ.

ADD BAR AT SLAB
DOWELS

EXT PAVING BY
OTHERS
2x4 CONT KEY - FILL W/

MASONRY GROUT OR
MORTAR
FTG REINF #6 @ 12" OC
EA WAY
2'-0"
HEIGHT "H"
2"
W
72db
MIN
1'-0"
TYP
3" CLR

CMU WALL THICKNESS

EXTERIOR FINISH

PER LANDSCAPE
CLR
3"
18"
MIN

PER LANDSCAPE
MIN.
1'-6"
(E) WALL AND FOOTING
AS OCCURS (V.I.F.) -

CONTRACTOR SHALL

NOTIFY SHALL

ARCHITECT IF (E)
CONDITION DIFFERS.
#5 @ 6" O/C W/ 90° HOOKED ENDS
(4) #5 LONGITUDINAL BARS
3'-0" LONG AT 4"x4" POST
4'-0" LONG AT 6"x6" POST
1" MIN. - 2" MAX.

NON-SHRINK GROUT
4" MIN. CONC.

COVER, TYP.

B B A A

EXTERIOR GRADE OR

SLAB PER

CIVIL/LANDSCAPE

BUILDING WALL WHERE
OCCURS
A A

POST PER LANDSCAPE
4" MAX.

PER LANDSCAPE
4" MIN. CONC.

COVER, TYP.

FENCE AND GATE ADJACENT TO (E) BUILDING___ FENCE AND GATE ADJACENT TO NEW BUILDING OR NEW WALL___ MIN.
4"
3" MIN.

WHERE ADJACENT WALL

DOES NOT OCCUR, PROVIDE

BASE PLATE PER PLAN VIEW
B-B
AB
MIN.
6 "
WALL and FOOTING ARE
CONT. WERE OCCURS
MIN.
1 2 "
PAPER JOINT.

POST PER LANDSCAPE
EQ. EQ.

PLAN VIEW A-A
AT 4"x4" POST
5/16

PLAN VIEW A-A
AT 6"x6" POST
BASE PL. 5/8x10x0'-10" W/
(4) 1/2"Ø THREADED
RODS SET IN DRILL and

EPOXY ANCHORS PER
GEN'L NOTES - 8" MIN.

EMBED.

BASE PL. 5/8x12x1'-0" W/
(4) 1/2"Ø THREADED
RODS SET IN DRILL and

EPOXY ANCHORS PER
GEN'L NOTES - 8" MIN.

EMBED.

EQ. EQ.
5/16
TYP.
1 1/2"

WALL PARALLEL TO FENCE/GATE

WHERE OCCURS, EXTEND
FOOTING 30" MIN. PAST END OF
WALL FOR POST CONN.

FOOTING PER PLAN
EQ. EQ.

PLAN VIEW B-B
AT 4"x4" POST
5/16

PLAN VIEW B-B
AT 6"x6" POST
BASE PL. 5/8x10x0'-10" W/
(4) 1/2"Ø THREADED
RODS SET IN DRILL and

EPOXY ANCHORS PER
GEN'L NOTES - 8" MIN.

EMBED.

BASE PL. 5/8x12x1'-0" W/
(4) 1/2"Ø THREADED
RODS SET IN DRILL and

EPOXY ANCHORS PER
GEN'L NOTES - 8" MIN.

EMBED.

EQ. EQ.
5/16
TYP.
1 1/2"
EQ. EQ. EQ. EQ.
(CENTERED CONDITION) (CENTERED CONDITION)

PROVIDE PAPER
JOINT.

MIN.
10" 24" MAX.

VERIFY W/ MECH'L/ELECT.
4" MIN.
#5@9" EA. WAY TOP &
BOTT. W/ STD. BEND EA.

END TYP., U.N.O.

ON GRADE
EXT. SLAB ON GRADE

OR FINISH GRADE PER

CIVIL/LANDSCAPE
NOTES:

SEE MECHANICAL and ELECTRICAL DRAWINGS FOR THE FOLLOWING:

1. LOCATION and DIMENSIONS OF BASES.

2. LOCATION, NUMBER, SIZE and TYPE OF BOLTS.

3. EMBEDMENT DEPTH OF EXPANSION ANCHORS WHERE OCCURS.
3" CLR. 2" CLR.

TYP.
3" CLR.

VERIFY W/ MECH and ELEC.

TYP.
12" MIN.

TYP.
6" MIN.

ANCHOR PER MECH AND

ELEC DRAWING

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"

CIVIL ENGINEER DATE
RCE EXP.

REVIEWED BY:

INSPECTOR DATE

SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

SITE DETAILS
S1.11
Checker
MONROE ST. POOL REPLACEMENT

SITE DETAILS
N.T.S.
01 TYP CAISSON SCHED. and DETAIL
N.T.S.
04 TYP SITE LIGHT POLE DETAIL
N.T.S.
03 TYPICAL CMU WALL ADJACENT

TO LIGHT POLE FOOTING
N.T.S.
02 TYP MASONRY FREE STANDING WALL
N.T.S.
05 TYP. FENCE POST NEXT TO (E) BLDG OR CMU WALL
06 TYPICAL CONCRETE BASE FOR EQUIPMENT
09/30/25
8'-0"
256
60 203
3RD PLAN CHECK SUBMITTAL 07/21/2024

08/09/2024

203

EXT GRADE OR PAVING

PER ARCH / CIVIL

CONT FTG

PER SCHED

REINF PER SCHED

CMU WALL THICKNESS

GATE POST WHERE
OCCURS
NOTE:

ADJACENT SCOREBOARD FOOTING SHALL

HAVE NO INFLUENCE OR SURCHARGE ON
FREESTANDING WALL FOOTING.
02 S1.11
1'-6"
3'-0"

ADJACENT SCOREBOARD

FOOTING PER OTHERS
12" MIN

TOP OF LOWEST EXT

OR BUILDING CONC

SLAB ON GRADE OR FINISH

GRADE ELEVATION
1"
6" TYP
9"

SOLAR PANEL &

ATTACHMENT PER

MEP/MANUFACTURER

CENENTITIOUS GROUT
1" MIN. NON-SHRINK

ROUND CONCRETE

PEDESTAL PER PLAN
1/2"Ø F1554 GR36 ANCHOR

AT EACH PEDESTAL
2"
6"
A

SECTION A-A
A

CHANNEL BEAM PER PLAN
6" MAX

CHANNEL BEAM PER PLAN

PLAN VIEW

CASSION AND REINF'G
PER 01/-
CASSION PER 01/-
LANDSCAPE AND ARCHITEC.

PER

SECTION

POST PER PLAN

CASSION AND REINF'G
PER 01/-
CASSION PER 01/-

FINISH GRADE OR

EXTERIOR PAVING
A A

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"

CIVIL ENGINEER DATE
RCE EXP.

REVIEWED BY:

INSPECTOR DATE

SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

SITE DETAILS
S1.12
Checker
MONROE ST. POOL REPLACEMENT

SITE DETAILS
N.T.S.
02 FREESTANDING CMU WALL ADJACENT TO

SCOREBOARD FOOTING
N.T.S.
7SOLAR PANEL DETAIL
N.T.S.
01 TYP. COMBINED CAISSON FOOTING
09/30/25
256
61 203
3RD PLAN CHECK SUBMITTAL 07/21/2024

08/09/2024

203
C6X10.5
C6X10.5
1'-0"Øx2'-0" DEEP

PEDESTAL, TYP
C6X10.5
C6X10.5
C6X10.5
C6X10.5
C6X10.5
C6X10.5
C6X10.5
C6X10.5
C6X10.5
C6X10.5
C6X10.5
C6X10.5
7 S1.12

SOLAR PANEL

CONN DETAIL
TYP
EQ.
21'-0" MAX
EQ.

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"

CIVIL ENGINEER DATE
RCE EXP.

REVIEWED BY:

INSPECTOR DATE

SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

SITE PLAN
S1.21
Checker
MONROE ST. POOL REPLACEMENT

SITE PLAN
1/8" = 1' -0"
1SOLAR PANEL FOUNDATION PLAN
N

PROJECT NORTH
N

TRUE NORTH
09/30/25
256
62 203
3RD PLAN CHECK SUBMITTAL 07/21/2024

08/09/2024

11 S6.61
11 S6.61
8 S6.03
1 A
2 BC
3 4
D
11'-0" 28'-8" 12'-8"
33'-4" 17'-4" 45'-4"
96'-0"
52'-4"
S2.01A
13 SEISM
IC GAP
1 1/2"
1 S3.02
3 S3.02
2 S3.02
4 S3.02
5 S3.02
CF1
CF1
CF1
HSS4
X4X3/8
TYP
4" 9'-10"
1'-10" 15'-5 3/4" 15'-5 3/4" 15'-5 3/4" 13'-5 3/4"
TYP
TYP
6"
GB1
GB1
GB1
GB1
GB1
2 S3.21
1 S3.21
(E) HSS3 1/2 SQ, TYP
(E) HSS3 1/2 SQ, TYP
(N) 4x6
(N) 4x6 (E)DBL 2X4
STUDS
(E) 1'-4"WX1'-0"

CONT FOOTING
TYP
(E) 4'-3"SQX1'-0"

DEEP FOOTING (VIF)
(E) 4'-3"SQX1'-0"

DEEP FOOTING (VIF)
(E) 1'-4"WX1'-0"

CONT FOOTING
(VIF)
(E) 2'-0"SQX1'-0"

DEEP FTG
(E) 2'-0"SQX1'-0"

DEEP FTG
4 S6.82
TYP
10 S3.21
(N) SLAB-ON-GRADE

PER FOUNDATION
PLAN NOTE 3
03 S6.04
(N) SLAB-ON-GRADE

PER FOUNDATION
PLAN NOTE 3
1'-0"
6"

PLAN NOTES

1. FOR GENERAL NOTES SEE S0 SERIES SHEETS. FOR TYPI CAL DETAILS SEE S6 SERIES SHEETS.

2. SEE ARCHITECTURAL, MECHANICAL, ELECTRICAL, and P LUMBING DRAWINGS FOR TOP OF

CONCRETE SLAB ON GRADE ELEVATIONS, DEPRESSIONS, SLOPES, OPENINGS, DRAINS, TRENCHES, PADS, and CURBS; SLAB EDGE LOCATIONS; WALL OVERALL DIMENSIONS; and LOCATIONS OF OPENINGS NOT INDICATED ON STRUCTURAL D RAWINGS.

3. BUILDING SLAB-ON-GRADE: 5" THICK W/ #4 @ 12 O/C EACH WAY at CENTER OF SLAB OVER 15 MIL VISQUEEN (LAP 6" AT JOINTS and TAPE SEAL - OMIT VISQUEEN AT EXTERIOR AREAS) OVER PROPERLY COMPACTED FILL AS DESCRIBED IN GEOTECHNICAL REPORT. PROVIDE

CONSTRUCTION JOINTS OR WEAKENED PLANE JOINTS IN SLAB-ON-GRADE EACH DIRECTION PER DETAIL 06/S6.01 - AT AREAS TO RECEIVE TILE, COORDINATE LOCATION OF JOINTS IN SLAB TO ALIGN WITH TILE EXPANSION JOINTS PER ARCH.

4. CENTER COLUMNS ON NUMBERED GRID LINES UNLESS NOT ED OTHERWISE. CENTER SPREAD FOOTINGS and CONTINUOUS FOOTINGS ON COLUMNS UNLESS NOTED OTHERWISE.

5. IN NO CASE SHALL PIPES, CONDUITS, OR SLEEVES BE EMBEDDED IN SPREAD OR

CONTINUOUS FOOTINGS OR WITHIN TOP OR BOTTOM THIRD OF GRADE BEAMS UNLESS SPECIFICALLY DETAILED ON STRUCTURAL DRAWINGS. PIPES, CONDUITS OR SLEEVES MAY

ONLY BE EMBEDDED WITHIN THE MIDDLE THIRD OF GRADE BEAMS WHERE NOTED ON STRUCTURAL PLANS AND DETAILED IN THE STRUCTURAL DRAWINGS.

6. WHERE CONTINUOUS FOOTINGS and SPREAD FOOTINGS IN TERSECT, EXCAVATE TO BOTTOM OF DEEPER FOOTING and CONTINUE ALL BARS THRU INTERSECTION. PLACE BARS AT CONTINUOUS FOOTING CORNERS and INTERSECTIONS PER 05/S6.01. WHERE CONTINUOUS

FOOTINGS TERMINATE AT SIDES OF GRADE BEAMS OR SPREA D FOOTINGS, EXTEND LONGITUDINAL BARS TO FAR SIDE OF GRADE BEAM OR SPRE AD FOOTING and TERMINATE W/ STANDARD 90° HOOK.

7. LOCATE TOP OF SPREAD FOOTINGS, GRADE BEAMS and C ONTINUOUS FOOTINGS -2'-0" BELOW LOWEST ADJACENT SLAB OR GRADE ELEVATION UNLESS NOTED OTHERWISE.

8. GEOTECHNICAL OBSERVATION / COMPACTION REPORT SHA LL BE SUBMITTED TO THE BUILDING INSPECTOR PRIOR TO FOOTING INSPECTION.

9. COORDINATE EXTENT OF CONCRETE PADS SUPPORTING EQ UIPMENT WITH MANUFACTURER

AND WITH EDGE DISTANCE REQUIREMENTS PER EQUIPMENT A NCHORAGE DETAILS IN S6.9X SERIES.

10. CONTRACTOR SHALL BE RESPONSIBLE FOR NECESSARY S HORING OF ADJACENT EXISTING FOOTING.

11. SEE CIVIL DRAWINGS FOR APPROXIMATE LOCATION OF EXISTING UNDERGROUND UTILITIES.

PROTECT OR RELOCATE EXISTING UTILITIES AS REQUIRED DURING FOOTING EXCAVATION OR CONSTRUCTION. DO NOT SURCHARGE EXISTING UTILITIE S, SEE 01/S6.01 FOR ADDITIONAL CLARIFICATION.
1 CD
2 S3.02
4 S3.02
5 S3.02
CF1
CF1
CF1
CF1
11 S6.61 TYP TYP
(N) SLAB-ON-GRADE

PER FOUNDATION
PLAN NOTE 3
LEGEND
HSSXx
XX
INDICATES COLUMN ABOVE GB - SEE 04/S6.05 UNO
FX
XX.XX'
CFX

INDICATES CHANGE IN ELEVATION AT SLAB ON GRADE - SEE DETAIL 12/S6.02 UNLESS DETAILED OTHERWISE

INDICATES CONCRETE CURB OR HOUSEKEEPING
PAD - CONSTRUCT PER 06D/S6.01 UNO
OR
+X'-X"

S - - - - - - - S
INDICATES CONT. FOOTING - SEE SCHEDULE ON S2.01

INDICATES SPREAD FOOTING MARK - SEE SCHEDULE THIS SHEET and 13/S6.01

INDICATES TOP OF SPREAD FOOTING ELEVATION - IF NO ELEVATION INDICATED, LOCATE TOP OF SPREAD FOOTING PER NOTE 7

INDICATES ELEVATION OF TOP OF STRUCTURAL CONCRETE S LAB (TOC) -

SEE ARCHITECTURAL FOR TOC IF NO ELEVATION INDICATE D

INDICATES TOP OF FOOTING ELEVATION

DENOTES LIGHT GAUGE METAL STUD FRAMING - SEE SCHEDULE ON 01/S6.71A AND 01/S6.71B
INDICATES STEP IN CONTINUOUS FOOTING OR GRADE BEAM - SEE 06/S6.01 TOF
DENOTES 8" THICK CONCRETE BLOCK SHEAR WALL SOLID GROUTED - FOR REINFORCING and OTHER INFORMATION SEE CMU WALL
ELEVATIONS and S6.61

DENOTES EXISTING CMU WALLS
GB INDICATES GRADE BEAM - SEE SCHEDULE ON 01/S6.04

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"

CIVIL ENGINEER DATE
RCE EXP.

REVIEWED BY:

INSPECTOR DATE

SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

FOUNDATION PLAN
- BLDG A
S2.01A
Checker
MONROE ST. POOL REPLACEMENT

FOUNDATION PLAN - BLDG A

KEYPLAN
A
B
1/8" = 1' -0"
07 FOUNDATION PLAN - BLDG A
1/4" = 1' -0"
13 ENLARGED FOUNDATION PLAN - BLDG A

C O N T I N U O U S F O O T I N G S C H E D U L E
Mark

FOOTING SIZE
(WIDTH x DEPTH)

REINFORCING

CONTINUOUS

LONGITUDINAL BARS TRANSVERSE BARS
CF1 48"x18" (3) #6 TOP & BOTTOM #6 @ 12"O/C TOP & BOTT OM N

PROJECT NORTH
N

TRUE NORTH
N

PROJECT NORTH
N

TRUE NORTH
09/30/25
256
63 3RD PLAN CHECK SUBMITTAL 07/21/2024

08/09/2024

203

PLAN NOTES

1. FOR GENERAL NOTES SEE S0 SERIES SHEETS. FOR TYPI CAL DETAILS SEE S6 SERIES SHEETS.

2. SEE ARCHITECTURAL, MECHANICAL, ELECTRICAL, and P LUMBING DRAWINGS FOR TOP OF

CONCRETE SLAB ON GRADE ELEVATIONS, DEPRESSIONS, SLOPES, OPENINGS, DRAINS, TRENCHES, PADS, and CURBS; SLAB EDGE LOCATIONS; WALL OVERALL DIMENSIONS; and LOCATIONS OF OPENINGS NOT INDICATED ON STRUCTURAL D RAWINGS.

3. BUILDING SLAB-ON-GRADE: 5" THICK W/ #4 @ 12 O/C EACH WAY at CENTER OF SLAB OVER 15 MIL VISQUEEN (LAP 6" AT JOINTS and TAPE SEAL - OMIT VISQUEEN AT EXTERIOR AREAS) OVER PROPERLY COMPACTED FILL AS DESCRIBED IN GEOTECHNICAL REPORT. PROVIDE

CONSTRUCTION JOINTS OR WEAKENED PLANE JOINTS IN SLAB-ON-GRADE EACH DIRECTION PER DETAIL 06/S6.01 - AT AREAS TO RECEIVE TILE, COOR DINATE LOCATION OF JOINTS IN SLAB TO ALIGN WITH TILE EXPANSION JOINTS PER ARCH.

4. CENTER COLUMNS ON NUMBERED GRID LINES UNLESS NOT ED OTHERWISE. CENTER SPREAD FOOTINGS and CONTINUOUS FOOTINGS ON COLUMNS UNLESS NOTED OTHERWISE.

5. IN NO CASE SHALL PIPES, CONDUITS, OR SLEEVES BE EMBEDDED IN SPREAD OR

CONTINUOUS FOOTINGS OR WITHIN TOP OR BOTTOM THIRD OF GRADE BEAMS UNLESS SPECIFICALLY DETAILED ON STRUCTURAL DRAWINGS. PIPES, CONDUITS OR SLEEVES MAY

ONLY BE EMBEDDED WITHIN THE MIDDLE THIRD OF GRADE BEAMS WHERE NOTED ON STRUCTURAL PLANS AND DETAILED IN THE STRUCTURAL DRAWINGS.

6. WHERE CONTINUOUS FOOTINGS and SPREAD FOOTINGS IN TERSECT, EXCAVATE TO BOTTOM OF DEEPER FOOTING and CONTINUE ALL BARS THRU INTERSECTION. PLACE BARS AT CONTINUOUS FOOTING CORNERS and INTERSECTIONS PER 05/S6.01. WHERE CONTINUOUS

FOOTINGS TERMINATE AT SIDES OF GRADE BEAMS OR SPREA D FOOTINGS, EXTEND LONGITUDINAL BARS TO FAR SIDE OF GRADE BEAM OR SPRE AD FOOTING and TERMINATE W/ STANDARD 90° HOOK.

7. LOCATE TOP OF SPREAD FOOTINGS, GRADE BEAMS and C ONTINUOUS FOOTINGS -2'-0" BELOW LOWEST ADJACENT SLAB OR GRADE ELEVATION UNLESS NOTED OTHERWISE.

8. GEOTECHNICAL OBSERVATION / COMPACTION REPORT SHA LL BE SUBMITTED TO THE BUILDING INSPECTOR PRIOR TO FOOTING INSPECTION.

9. COORDINATE EXTENT OF CONCRETE PADS SUPPORTING EQ UIPMENT WITH MANUFACTURER

AND WITH EDGE DISTANCE REQUIREMENTS PER EQUIPMENT A NCHORAGE DETAILS IN S6.9X SERIES.

10. CONTRACTOR SHALL BE RESPONSIBLE FOR NECESSARY S HORING OF ADJACENT EXISTING FOOTING.

11. SEE CIVIL DRAWINGS FOR APPROXIMATE LOCATION OF EXISTING UNDERGROUND UTILITIES.

PROTECT OR RELOCATE EXISTING UTILITIES AS REQUIRED DURING FOOTING EXCAVATION OR CONSTRUCTION. DO NOT SURCHARGE EXISTING UTILITIE S, SEE 01/S6.01 FOR ADDITIONAL CLARIFICATION.
5 6
7 F E
2 S3.01
1 S3.01
4 S3.01
3 S3.01
10 S6.61
10 S6.61
11 S6.61
12 S6.61
TYP.
11 S6.61
12 S6.61 TYP.

S - - - - S

PUMP PIT

SLAB-ON-GRADE

PER FOUNDATION
PLAN NOTE 3

SLAB-ON-GRADE

PER FOUNDATION
PLAN NOTE 3
CF1
CF1
CF1
CF1
CF1
CF1
34'-0"
26'-3 13/16" 35'-8 3/16"
62'-0"
5 S3.01

S - - - - S

S - - - - S

S - - - - S

S - - - - S

S - - - - S

S - - - - S

S - - - - S
CF1
CF1
CF1
CF1
CF1
TOF = -2'-0"
TOF = -7'-0"
TOF = -7'-0"

S - - - - S
TOF = -2'-0"
8 S6.63

TYP AT NON-

BEARING CMU
WALLS

S - - - - S
TOF = -4'-0"

PUMP ROOM PITS,
EQT. PAD REFER TO

POOL DESIGN

DRAWINGS, TYP
04 S6.03

SLAB-ON-GRADE
TOF = -4'-0"
5'-0" 8'-0"
6'-0"
LEGEND
HSSXx
XX
INDICATES COLUMN ABOVE GB - SEE 04/S6.05 UNO
FX
XX.XX'
CFX

INDICATES CHANGE IN ELEVATION AT SLAB ON GRADE - SEE DETAIL 12/S6.02 UNLESS DETAILED OTHERWISE

INDICATES CONCRETE CURB OR HOUSEKEEPING
PAD - CONSTRUCT PER 06D/S6.01 UNO
OR
+X'-X"

S - - - - - - - S
INDICATES CONT. FOOTING - SEE SCHEDULE ON S2.01

INDICATES SPREAD FOOTING MARK - SEE SCHEDULE THIS SH EET and 13/S6.01

INDICATES TOP OF SPREAD FOOTING ELEVATION - IF NO EL EVATION INDICATED, LOCATE TOP OF SPREAD FOOTING PER NOTE 7

INDICATES ELEVATION OF TOP OF STRUCTURAL CONCRETE S LAB (TOC) -

SEE ARCHITECTURAL FOR TOC IF NO ELEVATION INDICATE D

INDICATES TOP OF FOOTING ELEVATION

DENOTES LIGHT GAUGE METAL STUD FRAMING - SEE SCHEDULE ON 01/S6.71A AND 01/S6.71B
INDICATES STEP IN CONTINUOUS FOOTING OR GRADE BEAM - SEE 06/S6.01 TOF
DENOTES 8" THICK CONCRETE BLOCK SHEAR WALL SOLID GROUTED - FOR REINFORCING and OTHER INFORMATION SEE CMU WALL
ELEVATIONS and S6.61

DENOTES EXISTING CMU WALLS
GB INDICATES GRADE BEAM - SEE SCHEDULE ON 01/S6.04

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"

CIVIL ENGINEER DATE
RCE EXP.

REVIEWED BY:

INSPECTOR DATE

SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

FOUNDATION PLAN
- BLDG B
S2.01B
Checker
MONROE ST. POOL REPLACEMENT

FOUNDATION PLAN - BLDG B

KEYPLAN
A
B
1/4" = 1' -0"
101 - FLOOR - ENLARGED - BLDG B

C O N T I N U O U S F O O T I N G S C H E D U L E
Mark

FOOTING SIZE
(WIDTH x DEPTH)

REINFORCING

CONTINUOUS

LONGITUDINAL BARS TRANSVERSE BARS
CF1 48"x18" (3) #6 TOP & BOTTOM #6 @ 12"O/C TOP & BOTT OM N

PROJECT NORTH
N

TRUE NORTH
09/30/25
256
64 203
3RD PLAN CHECK SUBMITTAL 07/21/2024

08/09/2024

1 A
2 BC
3 4
D
S2.09A
13 HSS8X4X1/4
HSS12X4X3/8
HSS12X4X3/8
HSS12X4X3/8
HSS12X4X3/8
HSS8X4X1/4 HSS8X4X1/4 HSS8X4X1/4 HSS8X4X1/4 HSS8X4X1/4
HSS8X4X1/4 HSS8X4X1/4 HSS8X4X1/4 HSS8X4X1/4 HSS8X4X1/4
HSS12X4X3/8
RD1
4B
S6.12
TYP

O P E N
2 S3.21
1 S3.21
(E) 2X10 @ 24" O/C (E) 2X10 @ 24" O/C
(E) 4x12 (E) 4x12 (E) 4x12 (N) 4x14 (E) 6x10 (E) 4x12 (E) 4x12 (E) 4x12 (N) 4x14 (E) 2X10 @ 24" O/C (E) 2X10 @ 24" O/C
(E) 2X10 @ 24" O/C (E) 2X10 @ 24" O/C
(E) 2X8 @ 16" O/C
(E) 6x14
(E) 6x14
(E) 4x10
8 S6.81
8 S6.81
1 S6.81
BM TO
POST
CONN
3 S6.81
(E) BM TO (N)

BM/POST CONN
6 S6.81

NEW ROOF OPENINGS
SEE PLAN NOTE 14
10 S3.21

FRAMING AROUND

OPENING PER PLAN
NOTE 5, TYP
5 S6.63
EF
5A
75#
EF
6 60#
SF
4 70#
EF
5B
50#
SF
3 125#
EF
4 45#
EF
1B
50#
EF
1A
75#
SF
1 105#
(N) HSS TO (E) CMU

CONN PER
HSS 4x4x1/4
6 S6.63 TYP
HSS 4X4X1/4
@ 4'-0" O/C
4A
S6.12
TYP

1. 1.FOR GENERAL NOTES SEE S0 SERIES SHEETS. FOR TY PICAL DETAILS SEE S6 SERIES SHEETS.

2. SEE ARCHITECTURAL, MECHANICAL, ELECTRICAL, and P LUMBING DRAWINGS FOR TOP OF

STRUCTURAL CONCRETE SLAB OR METAL DECK ELEVATIONS, DEPRESSIONS, SLOPES, CURBS, DRAINS, PADS, DECK EDGE LOCATIONS; WALL OVERALL DIMENSIONS; and LOCATIONS OF OPENINGS IN WALLS and SLABS NOT INDICATED ON STRUCTURAL DRAWINGS.

3. CENTER COLUMNS AT GRID INTERSECTIONS UNLESS NOTE D OTHERWISE.

4. BEAMS ARE SPACED EQUALLY BETWEEN COLUMNS AND GIR DERS UNLESS NOTED OTHERWISE.

5. FOR OPENINGS IN FLOOR UP TO 2'-0" SQUARE SEE 5/S 6.13 and FOR OPENINGS UP TO 4'-0" MAXIMUM (PERPENDICULAR TO DECK SPAN) SEE 3/S6.13. AT EXHAUST FANS, ROOF ACCESS HATCHES, AND OTHER SIMILAR ROOFTOP EQUIPMENT PROVID E DETAILING PER 3/S6.91 REGARDLESS OF OPENING SIZE UNO.

6. ADD ANGLES AT COLUMNS FOR SUPPORT OF METAL DECKI NG PER 15/S6.12.

7. SET BACK STEEL BEAMS ADJACENT TO INTERIOR OPENIN GS OR EXTERIOR EDGES 10 INCHES (CENTERLINE OF BEAM TO DECK EDGE) UNLESS NOTED OTHERWISE - SEE DETAIL 01/S6.13 OR 03/S6.13 FOR TYPICAL DECK EDGE.

8. NO PENETRATION IN STRUCTURAL STEEL IS PERMITTED UNLESS SPECIFICALLY SHOWN ON STRUCTURAL DRAWINGS.

9. SEE S6.9X SERIES FOR EQUIPMENT ANCHORAGE UNLESS NOTED OTHERWISE. WHERE

EQUIPMENT IS ANCHORED DIRECTLY TO BEAM, LOCATE BEAM S CENTERED UNDER EQUIPMENT CURB. WHERE EQUIPMENT IS ANCHORED ON A CONCRETE PAD, LOCATE BEAM CENTERLINE 6" INWARD FROM EDGE OF PAD. WHERE EQUIPMENT IS ANCHORED TO A BUILT-UP CONCRETE PAD, CENTER BEAM ON CONCRETE WALL OF BUILT-UP CONCRETE PAD. COORDINATE EXTENT

OF CONCRETE PADS SUPPORTING EQUIPMENT WITH MANUFACT URER AND WITH EDGE DISTANCE REQUIREMENTS PER EQUIPMENT ANCHORAGE DETAILS.

10. COORDINATE DETAILING AND SECONDARY MEMBERS FOR DEFERRED SUBMITTAL ITEMS PER GENERAL NOTE SECTION B.

11. PROVIDE CONNECTIONS AND SUPPORT FRAMING FOR ROO FTOP DUCTING PER 13/M7.12.

12. SEE ARCH/MEP PLANS FOR EXACT EXTENT OF ROOF PV. EXTENT HAS BEEN DESIGNED FOR AN ADDITTIONAL 7 PSF. UNIFORM DEAD LOAD.

13. VERIFY IN FIELD (V.I.F) ALL (E) FRAMING, DIMENS IONS, CONDITIONS, ETC.

14. CONTRACTOR SHALL VERIFY EXISTING ROOF RAFTER LO CATIONS AND ENSURE NO EXISTING ROOF RAFTER CUT DUE TO ROOF OPENINGS UNLESS APPROVE D BY SEOR. ROOF OPENING DETAIL PER 4/S6.81

15. ROOF SCREEN PER OTHERS, REFER TO ARCH DRAWINGS AND DEFFERED SUBMITTAL ITEMS

PLAN NOTES
1 CD
RD1
W12X26
W12X19
EF
2 45#
SF
2 70#
LEGEND

INDICATES COLUMN BELOW - SEE FOUNDATION PLAN FOR COLUMN SIZE

DENOTES ELEVATION OF TOP OF STRUCTURAL CONCRETE SLA B (TOC) - SEE ARCHITECTURAL FOR TOC IF NO ELEVATION INDICATED +X'-X"
CB

INDICATES CMU WALL BELOW
XxXX <X"> INDICATES WOOD BEAM

INDICATES UPWARD CAMBER (IN INCHES) AT MIDSPAN OF BEAM (IF BEAM

CANTILEVERS, HOLD CANTILEVERED PORTION LEVEL) - IF NO CAMBER INDICATED, NO

CAMBER REQUIRED

DENOTES SEISMIC FORCE RESISTING SYSTEM (SFRS) - SEE GENERAL NOTE SECTION H NOTE 4.C - WHEN (SFRS) IS INDICATED, ALL MEMBERS IN THAT FRAMING LINE ARE (SFRS) MEMBERS
SFRS
INDICATES FACE PLATE BEAM CONNECTION - SEE 07/S6.62

INDICATES LIGHT GAUGE METAL STUD FRAMING BELOW
XX#
INDICATES MEP EQUIPMENT TAG. SEE 01/S6.91 FOR CONCR ETE PAD and/or

ANCHORAGE INFORMATION UNO
INDICATES MAX. EQUIPMENT WEIGHT INCLUDING ALL ACCESSORIES DENOTES ROOF CONSTRUCTION MARK - SEE SCHEDULE THIS SHEET and DETAIL 01/S6.12 - PROVIDE CONSTRUCTION JOINTS IN CONCRETE-FILLED DECK PER 01A/S6.12 - PROVIDE CLOSURES OVER BEAMS AT DECKING CHANGE IN SPAN DIRECTION PER 01B/S6.12 - PROVIDE BENT PLATE OVER BEAMS AT PITCHED ROOFS PER 20/S6.13
RDX
INDICATES BEAM CONTINOUS - SEE X/S6.62

DENOTES EXISTING STURCUTRE MEMBERS

DENOTES NEW STRUCTURE MEMBERS
(N)
(E)
DENOTES BEAM SPLICE - SEE 01D/S6.11 UNO
INDICATES BOTTOM FLANGE BRACING - SEE DETAIL 2/S6.12

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"

CIVIL ENGINEER DATE
RCE EXP.

REVIEWED BY:

INSPECTOR DATE

SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

ROOF FRAMING

PLAN - BLDG A
S2.09A
Checker
MONROE ST. POOL REPLACEMENT

ROOF FRAMING PLAN - BLDG A

KEYPLAN
A
B
1/8" = 1' -0"
07 ROOF FRAMING PLAN - BLDG A
1/4" = 1' -0"
13 ENLARGED ROOF FRAMING PLAN - BLDG A
N

PROJECT NORTH
N

TRUE NORTH
N

PROJECT NORTH
N

TRUE NORTH
09/30/25
256
65 203
3RD PLAN CHECK SUBMITTAL 07/21/2024

08/09/2024

5 6
7 F E
RD1
1 S6.63
TYP
8 S6.62
1 S6.63
TYP
8 S6.62
7B
S6.62 TYP
SLOPE

PER ARCH
4 S6.63
4 S6.63
TYP
TYP
W12X26
W12X45
W12X19
W12X19
W12X45
W12X26
C6X8.2
C6X8.2

ROOF DRAINS,

PROVIDE FRAMING
PER PLAN NOTE 5

TYP UNO

FRAMING AROUND

OPENING PER PLAN
NOTE 5, TYP
W12X19
W12X26 W12X26
W12X26 W12X26
HSS4
X0.12
5 POST ABV, TYP
5 S3.01
08 -

PV FRAMING
PLAN

INVERTER RACK PER
MECH DWGS.

W12X19
W12X19
W12X19
W12X19
W12X26
W12X26
W12X19 W12X19
EF
10 55#
EF
11 60#
EF
12 75#
EF
7 80#

PIPE HANGING PER
DETAIL
2 S6.92
TYP

HANGING PIPE BELOW

PER MEP DRAWINGS
W12X26
W12X19
W12X19

1. 1.FOR GENERAL NOTES SEE S0 SERIES SHEETS. FOR TY PICAL DETAILS SEE S6 SERIES SHEETS.

2. SEE ARCHITECTURAL, MECHANICAL, ELECTRICAL, and P LUMBING DRAWINGS FOR TOP OF

STRUCTURAL CONCRETE SLAB OR METAL DECK ELEVATIONS, DEPRESSIONS, SLOPES, CURBS, DRAINS, PADS, DECK EDGE LOCATIONS; WALL OVERALL DIMENSIONS; and LOCATIONS OF OPENINGS IN WALLS and SLABS NOT INDICATED ON STRUCTURAL DRAWINGS.

3. CENTER COLUMNS AT GRID INTERSECTIONS UNLESS NOTE D OTHERWISE.

4. BEAMS ARE SPACED EQUALLY BETWEEN COLUMNS AND GIR DERS UNLESS NOTED OTHERWISE.

5. FOR OPENINGS IN FLOOR UP TO 2'-0" SQUARE SEE 5/S 6.13 and FOR OPENINGS UP TO 4'-0" MAXIMUM (PERPENDICULAR TO DECK SPAN) SEE 3/S6.13. AT EXHAUST FANS, ROOF ACCESS HATCHES, AND OTHER SIMILAR ROOFTOP EQUIPMENT PROVID E DETAILING PER 3/S6.91 REGARDLESS OF OPENING SIZE UNO.

6. ADD ANGLES AT COLUMNS FOR SUPPORT OF METAL DECKI NG PER 15/S6.12.

7. SET BACK STEEL BEAMS ADJACENT TO INTERIOR OPENIN GS OR EXTERIOR EDGES 10 INCHES (CENTERLINE OF BEAM TO DECK EDGE) UNLESS NOTED OTHERWISE - SEE DETAIL 01/S6.13 OR 03/S6.13 FOR TYPICAL DECK EDGE.

8. NO PENETRATION IN STRUCTURAL STEEL IS PERMITTED UNLESS SPECIFICALLY SHOWN ON STRUCTURAL DRAWINGS.

9. SEE S6.9X SERIES FOR EQUIPMENT ANCHORAGE UNLESS NOTED OTHERWISE. WHERE

EQUIPMENT IS ANCHORED DIRECTLY TO BEAM, LOCATE BEAM S CENTERED UNDER EQUIPMENT CURB. WHERE EQUIPMENT IS ANCHORED ON A CONCRETE PAD, LOCATE BEAM CENTERLINE 6" INWARD FROM EDGE OF PAD. WHERE EQUIPMENT IS ANCHORED TO A BUILT-UP CONCRETE PAD, CENTER BEAM ON CONCRETE WALL OF BUILT-UP CONCRETE PAD. COORDINATE EXTENT

OF CONCRETE PADS SUPPORTING EQUIPMENT WITH MANUFACT URER AND WITH EDGE DISTANCE REQUIREMENTS PER EQUIPMENT ANCHORAGE DETAILS.

10. COORDINATE DETAILING AND SECONDARY MEMBERS FOR DEFERRED SUBMITTAL ITEMS PER GENERAL NOTE SECTION B.

11. PROVIDE CONNECTIONS AND SUPPORT FRAMING FOR ROO FTOP DUCTING PER 13/M7.12.

12. SEE ARCH/MEP PLANS FOR EXACT EXTENT OF ROOF PV. EXTENT HAS BEEN DESIGNED FOR AN ADDITTIONAL 7 PSF. UNIFORM DEAD LOAD.

13. VERIFY IN FIELD (V.I.F) ALL (E) FRAMING, DIMENS IONS, CONDITIONS, ETC.

14. CONTRACTOR SHALL VERIFY EXISTING ROOF RAFTER LO CATIONS AND ENSURE NO EXISTING ROOF RAFTER CUT DUE TO ROOF OPENINGS UNLESS APPROVE D BY SEOR. ROOF OPENING DETAIL PER 4/S6.81

15. ROOF SCREEN PER OTHERS, REFER TO ARCH DRAWINGS AND DEFFERED SUBMITTAL ITEMS

PLAN NOTES LEGEND

INDICATES COLUMN BELOW - SEE FOUNDATION PLAN FOR COLUMN SIZE

DENOTES ELEVATION OF TOP OF STRUCTURAL CONCRETE SLA B (TOC) - SEE ARCHITECTURAL FOR TOC IF NO ELEVATION INDICATED +X'-X"
CB

INDICATES CMU WALL BELOW
XxXX <X"> INDICATES WOOD BEAM

INDICATES UPWARD CAMBER (IN INCHES) AT MIDSPAN OF BEAM (IF BEAM

CANTILEVERS, HOLD CANTILEVERED PORTION LEVEL) - IF NO CAMBER INDICATED, NO

CAMBER REQUIRED

DENOTES SEISMIC FORCE RESISTING SYSTEM (SFRS) - SEE GENERAL NOTE SECTION H NOTE 4.C - WHEN (SFRS) IS INDICATED, ALL MEMBERS IN THAT FRAMING LINE ARE (SFRS) MEMBERS
SFRS
INDICATES FACE PLATE BEAM CONNECTION - SEE 07/S6.62

INDICATES LIGHT GAUGE METAL STUD FRAMING BELOW
XX#
INDICATES MEP EQUIPMENT TAG. SEE 01/S6.91 FOR CONCR ETE PAD and/or

ANCHORAGE INFORMATION UNO
INDICATES MAX. EQUIPMENT WEIGHT INCLUDING ALL ACCESSORIES DENOTES ROOF CONSTRUCTION MARK - SEE SCHEDULE THIS SHEET and DETAIL 01/S6.12 - PROVIDE CONSTRUCTION JOINTS IN CONCRETE-FILLED DECK PER 01A/S6.12 - PROVIDE CLOSURES OVER BEAMS AT DECKING CHANGE IN SPAN DIRECTION PER 01B/S6.12 - PROVIDE BENT PLATE OVER BEAMS AT PITCHED ROOFS PER 20/S6.13
RDX
INDICATES BEAM CONTINOUS - SEE X/S6.62

DENOTES EXISTING STURCUTRE MEMBERS

DENOTES NEW STRUCTURE MEMBERS
(N)
(E)
DENOTES BEAM SPLICE - SEE 01D/S6.11 UNO
INDICATES BOTTOM FLANGE BRACING - SEE DETAIL 2/S6.12
6 W6X12
W6X12
W6X9
W6X9
W6X9
TYP
5 S3.01
6 S6.92

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"

CIVIL ENGINEER DATE
RCE EXP.

REVIEWED BY:

INSPECTOR DATE

SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

ROOF FRAMING

PLAN - BLDG B
S2.09B
Checker
MONROE ST. POOL REPLACEMENT

ROOF FRAMING PLAN - BLDG B

KEYPLAN
A
B
1/4" = 1' -0"
07 ROOF FRAMING PLAN - BLDG B
1/4" = 1' -0"
08 PV FRAMING PLAN BLDG B
N

PROJECT NORTH
N

TRUE NORTH
N

PROJECT NORTH
N

TRUE NORTH
09/30/25
256
66 203
3RD PLAN CHECK SUBMITTAL 07/21/2024

08/09/2024

01 - FLOOR
0"
5 6 7
(2) #5 CHORD REINF
OPEN
OPEN
(2) #5
(2) #5
(2) #5
(2) #5
(2) #5
(2) #5
TYP HORIZ REINF. PER 1/S6.61
TYP VERT REINF.

PER 1/S6.61
(2) #5
(2) #5

TOP OF BLOCK

EAST - BLDG A
10' -6"
01 - FLOOR
0"
567
(2) #5 CHORD REINF
OPEN
TYP HORIZ REINF. PER 1/S6.61
(2) #5
(2) #5
(2) #5
(2) #5
(2) #5
TYP VERT REINF.

PER 1/S6.61

TOP OF BLOCK

EAST - BLDG A
10' -6"
01 - FLOOR
0"
FE
(2) #5 CHORD REINF
OPEN
(2) #5
(2) #5
(2) #5
TYP HORIZ REINF. PER 1/S6.61
TYP VERT REINF.

PER 1/S6.61
(2) #5
(2) #5

TOP OF BLOCK

EAST - BLDG A
10' -6"
01 - FLOOR
0"
F E
(2) #5 CHORD REINF

OPEN OPEN OPEN
(2) #5
(2) #5
(2) #5
(2) #5
(2) #5
(2) #5
TYP HORIZ REINF. PER 1/S6.61

TYP VERT
REINF. PER
1/S6.61 (2) #5
(2) #5
(2) #5
OPEN

TOP OF BLOCK

EAST - BLDG A
10' -6"

CONCRETE BLOCK SHEAR WALL ELEVATION NOTES

1. FOR GENERAL NOTES SEE S0 SERIES SHEETS. FOR TYPICAL DETAILS SEE S6 SERIES SHEETS.

2. SEE ARCHITECTURAL DRAWINGS FOR WALL DIMENSIONS and LOCATIONS OF OPENINGS NOT INDICATED ON STRUCTURAL DRAWINGS.

3. COORDINATE LOCATIONS OF PIPE, DUCT, and CONDUIT PENE TRATIONS OF SHEAR WALLS WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, and PLUMBING DRAWINGS. REINFORCE DUCT PENETRATIONS PER 01/S6.61 UNO and REINFORCE PIPE and CONDUIT PENETRATIONS PER 04/S6.63 UNO. NO OPENINGS LARGER THAN 8" SQ. (MADE WITHOUT INTERRUPTING WALL REINFORCING) IS PERMITTED UNLESS THE LOCATIONS and SIZES ARE SHOWN ON SHEAR WALL ELEVATIONS. SEE DETAIL 04/S6.63 FOR

LIMITATIONS OF OPENINGS MADE WITHOUT INTERRUPTING WALL
REINFORCING.

4. SEE REINFORCING STEEL SECTION OF THE GENERAL NOTES FOR

ADDITIONAL REBAR REQUIREMENTS FOR VERTICAL REBAR IN SHEAR WALLS.

5. CONSTRUCT MASONRY WALL INCLUDING OPENINGS AND WALL ENDS PER DETAIL 01/S6.61 UNO. SOLID GROUT ALL CELLS IN MASONRY WALLS. SEE 03/S6.61 FOR CONDITION AT CORNERS AND INTERSECTIONS UNO.

6. PROVIDE CHORD REINFORCING WITHIN 24" OF T.O.S. OR T.O .W. ELEVATION.

ENSURE 72db STAGGERED LAP SPLICE. PROVIDE 3 LAYERS OF 2 WALL HORIZONTAL REINFORCING MINIMUM.

7. ENSURE FIRST HORIZONTAL CMU BLOCK JOINT ALIGNS W/ F INISH FLOOR.

CUT FIRST CMU BLOCK ABOVE FOOTING IF NECESSARRY.

8. PROVIDE VERTICAL CONTROL JOINTS IN MASONRY WALLS (R EBAR TO BE CONTINUOUS) PER ARCH (25'-0" O/C MAX) AND 01/S6.61. JOINTS SHALL OCCUR IN FULL HEIGHT WALLS. NO JOINTS SHALL OCCUR IN COLUMNS, BEAMS, OR PILASTERS. CLEARLY INDICATE JOINT LOCATIONS IN CMU WALL SHOP DRAWINGS FOR REVIEW BY ARCHITECT (STRUCTURAL ENGINEER).

9. EMBED CONDUIT VERTICALLY IN WALL ONLY WHERE SPEC IFICALLY SHOWN ON STRUCTURAL ELEVATIONS. CONSTRUCT PER DETAIL 16/S6.61. NO

OTHER UTILITIES MAY BE EMBEDDED IN WALL UNLESS INDICATED OTHERWISE.

10. COORDINATE HORIZONTAL COLLECTOR AND CHORD BARS WITH ANCHOR BOLTS AND EMBED PLATES OVER LENGTH OF WALL. NOTE LEDGER

ANGLES, ANCHOR BOLTS, FACE PLATES AND EMBED PLATES NOT SHOWN FOR CLARITY.

LEGEND
DENOTES 8" THICK CONCRETE BLOCK SHEAR WALL SOLID GROUTED - FOR REINFORCING and OTHER INFORMATION SEE S6.61
01 - FLOOR
0"
F E
(2) #5

TOP OF BLOCK

EAST - BLDG A
10' -6"

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"

CIVIL ENGINEER DATE
RCE EXP.

REVIEWED BY:

INSPECTOR DATE

SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

ELEVATIONS - BLDG
B
S3.01
Checker
MONROE ST. POOL REPLACEMENT

ELEVATIONS - BLDG B
3/16" = 1' -0"
1BUILDING B - POOL MECHANICAL ROOM - WEST
3/16" = 1' -0"
2BUILDING B - POOL MECHANICAL ROOM - EAST
3/16" = 1' -0"
3BUILDING B - POOL MECHANICAL ROOM - SOUTH
3/16" = 1' -0"
4BUILDING B - POOL MECHANICAL ROOM - NORTH
3/16" = 1' -0"
5BUILDING B - POOL MECHANICAL ROOFM
09/30/25
256
67 203
3RD PLAN CHECK SUBMITTAL 07/21/2024

08/09/2024

CONCRETE BLOCK SHEAR WALL ELEVATION NOTES

1. FOR GENERAL NOTES SEE S0 SERIES SHEETS. FOR TYPICAL DETAILS SEE S6 SERIES SHEETS.

2. SEE ARCHITECTURAL DRAWINGS FOR WALL DIMENSIONS and LOCATIONS OF OPENINGS NOT INDICATED ON STRUCTURAL DRAWINGS.

3. COORDINATE LOCATIONS OF PIPE, DUCT, and CONDUIT PENE TRATIONS OF SHEAR WALLS WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, and PLUMBING DRAWINGS. REINFORCE DUCT PENETRATIONS PER 01/S6.61 UNO and REINFORCE PIPE and CONDUIT PENETRATIONS PER 04/S6.63 UNO. NO OPENINGS LARGER THAN 8" SQ. (MADE WITHOUT INTERRUPTING WALL REINFORCING) IS PERMITTED UNLESS THE LOCATIONS and SIZES ARE SHOWN ON SHEAR WALL ELEVATIONS. SEE DETAIL 04/S6.63 FOR

LIMITATIONS OF OPENINGS MADE WITHOUT INTERRUPTING WALL
REINFORCING.

4. SEE REINFORCING STEEL SECTION OF THE GENERAL NOTES FOR

ADDITIONAL REBAR REQUIREMENTS FOR VERTICAL REBAR IN SHEAR WALLS.

5. CONSTRUCT MASONRY WALL INCLUDING OPENINGS AND WALL ENDS PER DETAIL 01/S6.61 UNO. SOLID GROUT ALL CELLS IN MASONRY WALLS. SEE 03/S6.61 FOR CONDITION AT CORNERS AND INTERSECTIONS UNO.

6. PROVIDE CHORD REINFORCING WITHIN 24" OF T.O.S. OR T.O .W. ELEVATION.

ENSURE 72db STAGGERED LAP SPLICE. PROVIDE 3 LAYERS OF 2 WALL HORIZONTAL REINFORCING MINIMUM.

7. ENSURE FIRST HORIZONTAL CMU BLOCK JOINT ALIGNS W/ F INISH FLOOR.

CUT FIRST CMU BLOCK ABOVE FOOTING IF NECESSARRY.

8. PROVIDE VERTICAL CONTROL JOINTS IN MASONRY WALLS (R EBAR TO BE CONTINUOUS) PER ARCH (25'-0" O/C MAX) AND 01/S6.61. JOINTS SHALL OCCUR IN FULL HEIGHT WALLS. NO JOINTS SHALL OCCUR IN COLUMNS, BEAMS, OR PILASTERS. CLEARLY INDICATE JOINT LOCATIONS IN CMU WALL SHOP DRAWINGS FOR REVIEW BY ARCHITECT (STRUCTURAL ENGINEER).

9. EMBED CONDUIT VERTICALLY IN WALL ONLY WHERE SPEC IFICALLY SHOWN ON STRUCTURAL ELEVATIONS. CONSTRUCT PER DETAIL 16/S6.61. NO

OTHER UTILITIES MAY BE EMBEDDED IN WALL UNLESS INDICATED OTHERWISE.

10. COORDINATE HORIZONTAL COLLECTOR AND CHORD BARS WITH ANCHOR BOLTS AND EMBED PLATES OVER LENGTH OF WALL. NOTE LEDGER

ANGLES, ANCHOR BOLTS, FACE PLATES AND EMBED PLATES NOT SHOWN FOR CLARITY.

LEGEND
DENOTES 8" THICK CONCRETE BLOCK SHEAR WALL SOLID GROUTED - FOR REINFORCING and OTHER INFORMATION SEE S6.61
01 - FLOOR
0"
B C D
OPEN
(2) #5
(2) #5
(2) #5 (2) #5 CHORD REINF
TYP. HORIZ REINFORCEMENT PER 1/S6.61
TYP. VERT REINF
PER 1/S6.61

TOP OF BLOCK

EAST - BLDG A
10' -6"
01 - FLOOR
0"
1 (2) #5
(2) #5

PER PLAN
GAP
TYP. HORIZ REINF
PER 1/S6.61
TYP. VERT REINF
PER 1/S6.61

TOP OF BLOCK

EAST - BLDG A
10' -6"
01 - FLOOR
0"
1 OPEN
(2) #5
(2) #5
OPEN

OPEN OPEN
(2) #5
(2) #5
(2) #5
(2) #5
(2) #5
(2) #5
(2) #5
(2) #5
(2) #5
TYP. VERT REINF PER 1/S6.61
TYP. HORIZ REINF PER 1/S6.61
(2) #5

TOP OF BLOCK

EAST - BLDG A
10' -6"
01 - FLOOR
0"
CD
OPEN
(2) #5
(2) #5
(2) #5
(2) #5
TYP. HORIZ REINF
PER 1/S6.61 TYP. VERT REINF
PER 1/S6.61

TOP OF BLOCK

EAST - BLDG A
10' -6"
01 - FLOOR
0"
C D
(2) #5
(2) #5
TYP. HORIZ REINF
PER 1/S6.61
TYP. VERT REINF
PER 1/S6.61

TOP OF BLOCK

EAST - BLDG A
10' -6"

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"

CIVIL ENGINEER DATE
RCE EXP.

REVIEWED BY:

INSPECTOR DATE

SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

ELEVATIONS - BLDG
A
S3.02
Checker
MONROE ST. POOL REPLACEMENT

ELEVATIONS - BLDG A
3/16" = 1' -0"
1BUILDING A - POOL MECHANICAL ROOM - SOUTH
3/16" = 1' -0"
3BUILDING A - POOL MECHANICAL ROOM - EAST
3/16" = 1' -0"
2BUILDING A - POOL MECHANICAL ROOM - WEST
3/16" = 1' -0"
4BUILDING A - POOL MECHANICAL ROOM - NORTH
3/16" = 1' -0"
5BUILDING A - POOL MECHANICAL ROOM - SOUTH
09/30/25
256
68 203
3RD PLAN CHECK SUBMITTAL 07/21/2024

08/09/2024

01 - FLOOR
0"
CD
4C
S6.12
S6.05
4 SLAB ON GRADE

PER LANDSCAPE

HSS BEAM

PER PLAN

GRADE BEAM PER PLAN

HSS COL PER

PLAN - TYP
(E) CMU WALL
(E) FOOTING
NOTES:

CONTRACTOR SHALL BE

RESPONSIBLE FOR

NECESSARY SHORING OF

ADJACENT (E) FOOTING

TOP OF BLOCK

EAST - BLDG A
10' -6"
01 - FLOOR
0"
234
HSS4X4X1/4 HSS4X4X1/4
HSS4X4X1/4 HSS4X4X1/4 HSS4X4X1/4
HSS8X4X1/4 HSS8X4X1/4 HSS8X4X1/4 HSS8X4X1/4 HSS8X4X1/4
HSS3x3x3/16
HSS4X4X3/8
HSS4X4X3/8
HSS4X4X3/8
HSS4X4X3/8

TYP, UNO
HSS3x3x3/16
4B
S6.12
TYP
4B
S6.12
TYP
3 -
HSS3x3x3/16

GRADE BEAM

PER PLAN -
TYP

TOP OF BLOCK

EAST - BLDG A
10' -6"
01 - FLOOR
0"
T.O. BLOCK
9' -10"
AB

TOB BLDG B
13' -0"
HSS3X3X1/4
HSS3X3X1/4 HSS3x3x3/16
HSS3x3x3/16
3 S6.63
(N) BM TO (E)

CMU WALL

CONN SEE

TOP OF BLOCK

EAST - BLDG A
10' -6"

PANEL W/ ANGLES

PER ARCH

HSS BEAM PER PLAN

VERTICAL HSS PER PLAN/SEC
3/16 (3) SIDES
3/16

SCREWS TO VERTICAL

HSS PER OTHERS

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"

CIVIL ENGINEER DATE
RCE EXP.

REVIEWED BY:

INSPECTOR DATE

SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

PERF PANEL

FRAMING

ELEVATIONS AND

SECTION
S3.21
Checker
MONROE ST. POOL REPLACEMENT

PERF PANEL FRAMING ELEVATIONS AND SECTION
1/4" = 1' -0"
2FRAME SECTION
1/4" = 1' -0"
1PERF PANEL FRAMING ELEVATION
1/4" = 1' -0"
10 PERF PANEL FRAMING ELEVATION
1" = 1' -0"
3VERTICAL HSS TO HSS AT PERF PANEL
09/30/25
256
69 203
3RD PLAN CHECK SUBMITTAL 07/21/2024

08/09/2024

PIPES THRU OR BELOW FOUNDATION

TRENCH ADJACENT TO FOUNDATION
A
A

ELEVATION A-A
1 1
PROVIDE PIPE SLEEVE (I.D. 2" LARGER THAN
PIPE O.D. - AT FIRE SPRINKLER PROVIDE I.D.
4" LARGER THAN PIPE O.D.) WHERE

ADJACENT TO CONCRETE - TYPICAL

PLACE THIS CONCRETE BEFORE FOOTING ABOVE -
LEAN CONCRETE PER GENERAL NOTE F.7
PIPE

LOCATE TRENCH SO

THAT FOOTINGS ARE

NOT UNDERMINED
CONT. FOOTING

OR GRADE BEAM
PIPE

LIMIT DISTANCE BETWEEN

SLEEVES TO NO LESS THAN

LARGER SLEEVE OUTSIDE
DIAMETER OR 6"
CONT. FOOTING

OR GRADE BEAM

SPREAD FTG,

CONT FTG, OR

GRADE BEAM
NOTES:

1. DO NOT PLACE SLEEVES OR

CONDUIT IN ISOLATED SPREAD

FOOTINGS - RUN AROUND OR
BELOW THESE FOOTINGS.

2. SLEEVES ARE NOT TO PASS

THROUGH CONTINUOUS

FOOTINGS OR GRADE BEAMS

UNLESS SHOWN OTHERWISE -

WHERE SLEEVES ARE

PERMITTED, LOCATE WITHIN

MIDDLE THIRD OF FOOTING OR
GRADE BEAM DEPTH.

PIPE

SLAB ON GRADE

BACKFILL TRENCH PER

GEOTECHNICAL REPORT

NO EXCAVATION

ALLOWED BELOW

THIS LINE
9" MIN
3 1/2" MIN.
9" MIN

NO SLEEVES
HERE
3" TYP

CONT FTG
OR GRADE BEAM "D"
4" MIN
3'-0" MAX 6" MIN
"D"/3 MAX
1"
1'-6" MIN

STANDARD HOOKS OTHER THAN STIRRUPS AND TIES
#6

B A R D I A M E T E R D I S T A N C E S

STANDARD HOOKS FOR STIRRUPS AND TIES
#3 #4 #5 #10 #9 #7 #8 #11

MAXIMUM OFFSET AT SPLICES
2 1/4"
4 1/2"
-
9"
3"
* INDICATES MINIMUM DIMENSIONS MAY GOVERN
NOTE:

HOOKS OF TWO SUCCESSIVE STIRRUPS OR TIES ENGAGING

SAME LONGITUDINAL BAR SHALL BE ALTERNATED END FOR END
6db FOR #3 THRU #5
12db FOR #6 THRU #8
12db 4 1/2" 6" 7 1/2"
3db

BAR DIAMETERS
8db
6db
4db
1 1/8" 1 1/2" 1 7/8"
2 1/4"* 3"
- -
1 1/2"* 2"*
-
3 3/4"
2 1/2"
#9 THRU #11
#3 THRU #8
15" 13 1/2" 12" 10 1/2" 16 1/2"
135°
10"
3" - -2 5/8"

BAR SIZE
6"
9" -
- -
4 1/2" 4" 5"
5 1/4"
-
3 1/2"
-
11"
-
5 1/2"
90°
1:6 MAXIMUM SHOP

OFFSET BEND
db
6db
#3 - #8
8db
#9 - #11
10db
#14 & #18
2 1/2" MIN.
4db
12db 3db
4db

AS INDICATED

SPLICE LENGTH
db
4db FOR #3 thru #5
6db FOR #6 thru #8
6db FOR #3 THRU #8
3" M
IN.
3" MIN

BAR SPACING DIAGRAM

DIAGRAM AT

STAGGERED SPLICES
I II

S C H E D U L E

F O R D E T E R M I N I N G C A T E G O R Y

SPLICE OR

LAPPING BAR
1:6 MAXIMUM SHOP

OFFSET BEND
LEGEND
A. CLEAR EDGE DISTANCE
B. CENTER TO CENTER SPACING OF SPLICED
OR LAPPED BARS (SEE GENERAL NOTE 'E.8'

FOR MINIMUM CLEAR SPACING)
db - BAR DIAMETER
NOTES:

1. ALL SPLICES SHALL BE CLASS B SPLICES UNLESS INDI CATED OTHERWISE. DEVELOPMENT Ld TO BE USED WHERE SPECIFICALLY INDICATED.

2. SCHEDULE APPLIES TO UNCOATED GRADE 60 BARS IN NO RMAL WEIGHT CONCRETE.

3. TOP BARS (INDICATED "T" IN SCHEDULE) ARE HORIZON TAL BARS WITH MORE THAN 12" OF CONCRETE CAST BELOW THE BARS.

4. BOTTOM BARS (INDICATED "B" IN SCHEDULE) ARE ALL VERTICAL BARS AND HORIZONTAL BARS WITH LESS THAN 12" OF CONCRETE CAST BELOW HORIZONTAL BARS.

5. FOR LIGHTWEIGHT CONCRETE MULTIPLY LENGTHS IN SCH EDULE BY 1.33.

6. AT SPLICE BETWEEN BARS OF VARYING SIZE, PROVIDE LAP SPLICE CORRESPONDING TO LARGER OF 'Ls' OF SMALLER BAR and 'Ld' OF LARGER BAR.

1. A>db and
B>2db and
TIES THRUOUT Ld

2. A>db and
B>3db

OTHER CASES
LENGTH
SPLICE
LENGTH
SPLICE
db

B LENGTH
SPLICE
B A
A B A
db
B

DIAGRAM AT NON -

STAGGERED SPLICES
#6 #4 #3 #5 #10 #8 #7 #9 #11
I

0.750
T T
28 T
4000
3000
B

0.375
T B B

0.625 0.500 1.270
T

1.000

T T B B

0.875
T B B

1.128
T B B

1.410
24 22
19 37
32 29
25 47
40 36
31 56
48 43
37 81
70 63
54 93
80 72
62 105
91 81
70 118
102
91 79
131
113
101
87 SPLICE LENGTH (INCHES)
NORMAL
WEIGHT

CONCRETE
f'c PSI

CATEGORY
TENSION LAP SPLICE "Ls" SCHEDULE
5000 22 17 29 22 36 28 43 33 63 49 72 55 81 63 91 70 101 78 II
42 4000
3000
36 32
28 56
48 43
37 70
60 54
47 84
72 64
56 122
106
94 81
139
121
107
93 157
136
121
105
177
153
136
118
196
170
151
131
5000 33 25 43 33 54 42 65 50 94 73 108 83 122 94 137 105 152 117 #6 #4 #3 #5 #10 #8 #7 #9 #11
I

0.750
T T
22 T
4000
3000
B

0.375
T B B

0.625 0.500 1.270
T

1.000

T T B B

0.875
T B B

1.128
T B B

1.410
19 17
15 29
25 22
19 36
31 28
24 43
37 33
29 63
54 48
42 72
62 55
48 81
70 62
54 91
79 70
61 101
87 78
67 DEVELOPMENT LENGTH (INCHES)
NORMAL
WEIGHT

CONCRETE
f'c PSI

CATEGORY
DEVELOPMENT "Ld" SCHEDULE
5000 17 13 22 17 28 22 33 26 49 37 55 43 63 48 70 54 78 60 II
32 4000
3000
28 25
22 43
37 33
29 54
47 41
36 64
56 50
43 94
81 72
63 107
93 82
71 121
105
93 81
136
118
105
91 151
131
116
101
5000 25 19 33 26 42 32 50 38 73 56 83 64 94 72 105 81 117 90

SLAB ON GRADE JOINT DIAGRAM (PLAN VIEW) TYPICAL SECTION AT SLAB ON GRADE BTYP.

CTYP.

ATYP.

A
TYP.

CONSTRUCTION JOINT

LOCATION TO BE DETERMINED
BY CONTRACTOR PER NOTE 1
ADD (2) #5x4'-0" @ 4" O/C

DIAGONALS (CENTERED IN

SLAB) TYPICAL AT RE-ENTRANT

CORNERS WHERE JOINTS DO

NOT OCCUR

BLOCKOUTS AT

COLUMNS PER
NOTES

1. AREA OF CONCRETE POURS TO BE DETERMINED BY CONTR ACTOR. SUBMIT JOINT LAYOUT PRIOR TO POURING SLABS P ER GENERAL NOTES. PROVIDE CONSTRUCTION JOINTS SURROUNDING AREA OF EACH POUR UNLESS DETAILED OTHERWISE.

ALLOW 24 HOURS MINIMUM BEFORE CASTING SLABS AT ADJACENT AREAS.

2. SAWCUT WEAKENED PLANE JOINT AS SOON AS CONCRETE CAN SUPPORT WEIGHT OF PERSONNEL AND SAW WITHOUT AFFECTING FINAL FINISH BUT NO LATER THAN 12 HOURS AFTER POUR. LOCATE WEAKENED PLANE JOINTS NO GREATER THAN 36 TIMES SLAB THICKNESS "T" (20'-0" MAXIMUM) IN BOTH DIRECTIONS, UNLESS NOTED OTHERWISE.

WEAKENED PLANE
JOINTS PER NOTE 2
SEE NOTE 3 ON

FOUNDATION PLAN

FOR SLAB ON GRADE

THICKNESS AND

REINFORCING SEE PLAN

CLASS B

SLAB THICKNESS
"T"
0"
POUR PER NOTE 1

SHADED AREAS INDICATE
EXTENT OF CONCRETE POUR PER NOTE 1

SHADED AREAS INDICATE

EXTENT OF CONCRETE
13 S6.01
D
#3 DOWELS @ 18" O/C (#4 @
18" O/C WHERE "H">8") SET IN
DRILL and EPOXY ANCHORS

PER GENERAL NOTES
#4 CONTINUOUS
DRILL and EPOXY ANCHOR OPTION

SEE ARCH

DRAWINGS
#4 @ 16" O/C EA. WAY
#3 DOWELS @ 18" O/C (#4 @ 18" O/C
WHERE "H">8") W/ STD. 90° HOOKS

IN SLAB ON GRADE
PREPARE "CONSTRUCTION
JOINT" SURFACE PER
GENERAL NOTES - TYP.
(2) #4 CONTINUOUS
NOTE: DOWELS AT

HOUSEKEEPING PADS ARE REQUIRED AT
PERIMETER OF PADS and AT
INTERMEDIATE ROWS SPACED @ 6'-0"

EACH DIRECTION
NOTE: SEE ARCHITECTURAL

FOR SIZE AND LOCATION OF
CURBS and PADS

TYPICAL CONDITION

CONDITION AT CURB OR HOUSEKEEPING PAD
MAX
6"
1'-6'' MAX
"H"
1'-6"
NOTE: SEE TYPICAL

CONDITION BELOW FOR

REMAINDER OF INFO
1'-6'' MAX
"H"
MAX
6"

PLASTIC

SHEATHING
0"

CONSTRUCTION JOINT A

BARS MAY BE

CONTINUOUS

GALVANIZED TYPE
"KEYED KOLD JOINT"
.

CLASS B

SLAB THICKNESS
"T" T/2
1' - 6" 1' - 6"
2' - 0"

WEAKENED PLANE JOINT B
PLASTIC SHEATHING 1/8" WIDE WET SAWCUT -

FILL W/ SEALANT IF REQ'D

PER ARCHITECTURAL
1' - 0" 1' - 0"
"T"/4

TURNED -DOWN SLAB EDGE C

FINISH GRADE OR

EXTERIOR SURFACE
HOOK BARS 90° AS SHOWN OR

ADD DOWELS MATCHING SLAB
REINFORCING SIZE and SPACING
(#4 @ 24" O/C MIN.) x 2'-0"

CURB WHERE OCCURS -
SEE
#4 CONT. @ 12" O/C -
(2) #4 MIN.
1'-0'' MIN

AS REQ'D AS EXTERIOR
1'-6" MIN INCREASE

8" 6"
06D
-

PLAN VIEW AT INTERSECTIONS PLAN VIEW AT CORNERS

TIE WHERE OCCUR - EXTEND TIES IN

ONE FOOTING THRU INTERSECTIONS

AND CORNERS AS SHOWN

ADD BARS AT CORNERS MATCHING

SIZE AND QUANTITY OF TOP AND

BOTTOM BARS ON OUTSIDE FACE

EXTEND TOP AND BOTTOM

FOOTING BARS TO FAR SIDE

OF INTERSECTING FOOTING
AND PROVIDE STANDARD 90°

HOOKS, TYPICAL

EXTEND TOP AND

BOTTOM FOOTING BARS

TO FAR SIDE OF

INTERSECTING FOOTING

AND PROVIDE STDANDARD
90° HOOKS, TYPICAL

CLASS B SPLICE

CLASS B SPLICE
2" MAX
2" MAX

TYPICAL STEP

MULTIPLE STEPS

ADD BARS MATCHING FOOTING TOP BARS -
IF NO FOOTING TOP BARS, ADD 2 BARS

MATCHING FOOTING BOTTOM BARS
("Rd" = "D"-6")

ADD BARS MATCHING

FOOTING BOTTOM BARS
PROVIDE STD. 90° HOOKS

AT TOP BARS
PROVIDE STD. 90º HOOKS AT

BOTTOM BARS

MAINTAIN TIE SPACING
(WHERE TIES OCCUR)

AT STEPS
"Rd"
DEPTH
"Rd"
DEPTH
.

TYP.

CLASS B
"Rd" DEPTH
MATCH
NOTE: DEPTH "Rd"

INDICATES DISTANCE

BETWEEN TOP AND

BOTTOM FOOTING

LONGITUDINAL BARS
DEPTH "D"
FTG
1' - 6" MAX.
"H"
1' - 6" MAX.
"H"
1' - 6'' MAX
''H''
1' - 6'' MAX
''H''
"D"
MATCH

DEPTH ''D''
FTG
2 (''H'')
1' - 6'' MAX
''H''

DEPTH ''D''
FTG
2(''H'') + ''D''
3'' CLR.
3" CLR.
2("H")

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"

CIVIL ENGINEER DATE
RCE EXP.

REVIEWED BY:

INSPECTOR DATE

SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

TYPICAL

FOUNDATION AND

SOG DETAILS
S6.01
Checker
MONROE ST. POOL REPLACEMENT

TYPICAL FOUNDATION AND SOG DETAILS
N.T.S.
1TYPICAL PIPES THRU OR TRENCHES

ADJACENT TO FOUNDATIONS
N.T.S.
2TYPICAL REINFORCING STEEL
HOOKS, BENDS and OFFSETS AT SPLICES
N.T.S.
3TYPICAL REBAR TENSION SPLICE and BAR DEVELOPMENT SCHEDULE (IN CONCRETE) N.T.S.
4TYPICAL SLAB ON GRADE DETAILS
N.T.S.
5TYPICAL FOOTING REINFORCING AT CORNERS

AND INTERSECTIONS
N.T.S.
6TYP. STEPPED FOOTING/GRADE BEAM DETAIL
09/30/25
256
70 203
3RD PLAN CHECK SUBMITTAL 07/21/2024

08/09/2024

0"
GRADE
(2) #5 x 5'-0"
- TYPICAL

CONSTRUCTION JOINT

AROUND LOCKOUTS -

TYPICAL (NO BARS TO

PASS THRU JOINT)
6x6-W1.4xW1.4 WELDED

WIRE MESH (WRAP
AROUND COLUMN) PROVIDE 90°

BENDS AT ALL

EDGES OF SPREAD

FTG AS SHOWN

BASE PLATE PER PLAN

ADDED DOWELS AT BLOCKOUT

EDGE PER PLANS ABOVE
STL. COL. PER PLAN
SEE PLAN NOTE 8 ON

FOUNDATION PLANS
DOUBLE
NUT
PLAN VIEW at SLAB BLOCKOUTS

INTERIOR CONDITION

PERIMETER CONDITION

SLAB ON GRADE

CONSTRUCTION JOINT OR

WEAKENED PLANE PER
PLAN
FILL BLOCKOUT WITH CONC.

AFTER COMPLETION OF ROOF

CONSTRUCTION ABOVE

INTERIOR PERIMETER
4" CONCRETE COVER OVER

COLUMN ANCHOR BOLTS AND

BASE PLATE
NOTE:

FOR REMINDER OF INFO SEE

INTERIOR CONDITION BELOW
#4 DOWELS @ 12" O/C W/
STD. 90° HOOKS TOP AND
BOTTOM

FOOTING PER PLAN

FOOTING SIZE AND REINFORCING PER PLAN
4" MIN.
3" CLR
3" CLR.
4" MIN
6" MIN
2" TYP. 2" TYP.
.
4 1/2"
.

DOUBLE NUT
2"
2"
NOTES:

1. ADD #4 x 12" DOWELS @ 12" O/C WHERE S IDE WALLS OCCUR AT STAIRS OR RAMP U.N.O.

2. SEE ARCHITECTURAL OR LANDSCAPE FOR TREAD and RIS ER

GEOMETRY AND FINISHING
36"
(2) #4 CONTINUOUS
#4 @ 12" O/C

EACH WAY
#3 NOSING BAR AT

STEPS ON GRADE ONLY

TYPICAL

RAMP LINE
#3 @ 15" O/C AT EACH

NOSING BAR
6"
6"
AT TOP AT BOTTOM TYP.
6"
24"
6"
6"
(2) #4 CONT.

SLAB ON GRADE - (SEE

LANDSCAPE DWGS AT

EXTERIOR CONDITIONS)
#4 BENT BARS @ 12" O/C

SLAB ON GRADE - (SEE
LANDSCAPE DWGS. AT

EXTERIOR CONDITIONS)
2'-0" TYP. 1' - 6" 1' - 6"
2'-0" TYP.
1'-0" 1' - 6"
CLR.
3"
6" MIN.
06A
-
SIM.
06A
-
SIM.

H O O K E D B A R D E V E L O P M E N T
L E N G T H ( L d h ) S C H E D U L E
#3 9"
BAR SIZE Fc' = 3000psi
8"
11" 10"
14" 12"
17" 15"
#5
#6
NOTES:

1. FOR TYPICAL BAR HOOKS & BENDS, SEE DETAIL

2. BAR DEVELOPMENT LENGTHS SHOWN IN SCHEDULE ABOVE APPLY TO NORMAL WEIGHT CONCRETE - MULTIPLY THE SPECIFIED DEVELOPMENT LENGTH BY 1.33 FOR LIGHTWEIGHT CONCRETE.

3. LENGTHS SHOWN IN SCHEDULE ABOVE APPLY TO UNCOATE D GRADE 60 BARS - MULTIPLY THE SPECIFIED LENGTH BY 1.25 FOR GRADE 75 BARS. MULTIPLY THE SPECIFIED LENGTH BY

1.33 FOR GRADE 80 BARS

4. LENGTHS SHOWN IN SCHEDULE ABOVE APPLY TO UNCONFI NED BARS - WHERE CONFINEMENT CAN BE PROVIDED BY ENCLOSED TIES OR STI RRUPS SPACED @ 3db EITHER 1) PERPENDICULAR TO Ldh ALONG THE LENGTH OF Ldh OR 2) PERPENDICULAR TO Lext ALONG THE LENGTH OF Lext, MULTIPLY THE SPECIFIED DE VELOPMENT LENGTH BY 0.8.

5. HOOKED BARS MAY BE SUBSTITUTED WITH HEADED BARS PER 'Ldt' SCHEDULE AT LEFT. #4
#7
20" 17"
#8
Fc' = 4000psi
7"
9"
11"
13"
15"
Fc' = 5000psi
22" 19" 17"
#9 25" 22" 19"
#10 28" 25" 22"
#11 31" 27" 24"
MIN
Ldh
6"
8"
10"
12"
14"
16"
18"
20"
22"

H O O K E D B A R D E V E L O P M E N T
L E N G T H ( L d t ) S C H E D U L E
#3
9"
BAR SIZE Fc' = 3000psi
8"
11" 10"
16"
12"
18" 15"
#5
#6
NOTES:

1. THESE BAR DEVELOPMENT LENGTHS APPLY TO NORMAL WE IGHT CONCRETE ONLY.

2. PROVIDE LENTON HEADED REINFORCING BARS PER IAPMO-UES ER-0188. #4
#7
20" 17"
#8
Fc' = 4000psi
7"
9"
10"
14"
16"
Fc' = 5000psi
23" 20" 18"
#9
25" 22" 19"
#10
#11
MIN
Ldt
6"
8"
10"
13"
14"
16"
18"
13"
7" 6" 6" 6"
Fc' = 6000psi Fc' = 6000psi
12" 14" 11"
Ldt Ldh
Lext
03 -
1/16"
"L" WELD
(MIN)
SIZE
WELD "S"
2"
3"
4"
BAR
SIZE
#3
#4
#5
4"
5"
6"
#6
#7
#8
6"
7"
#9
#10
REBAR

WELDMENT
STEEL

PLATE OR
ANGLE

REBAR START OF

BEND WHERE

APPLICABLE
"D" 3/16"
1/4"
5/16"
3/8"
7/16"
1/2"
9/16"
5/8"
''S''= ''D''/2
"L"
MIN.
5 "D"
"D"
''S''
NOTES

1. ALL REINFORCING WELDING SHALL BE IN ACCORDANCE W ITH A.W.S. CODE D1.4-05 CURRENT EDITION.

2. WELDED REINFORCING SHALL CONFORM TO ASTM A706.

3. ASTM A615 REINFORCING STEEL MAY BE WELDED PROVID ED A CHEMICAL ANALYSIS IS PERFORMED TO DETERMINE CARBON EQUIVALENCY, TO ESTABLISH MINIM UM PREHEATING REQUIREMENTS. HEAT STICKS SHALL BE USED 6" FROM WELD TO VERIFY PREHEAT TEMPERATURES. CHEMICAL ANALYSIS REPORTS SHALL BE PROVIDED TO ARCHITECT (STRUCTURAL ENGINEER) PRIOR TO WELDING. "S" L
"S"

PRIOR TO WELDING

OTHER SIDE, CHIP OR

GRIND ROOT TO

SOUND METAL
NOTES:

1. AS AN ALTERNATE TO LAP SPLICE, BUTT WELD MAY BE USED AS INDICATED ABOVE, PROVIDED THEY ARE STAGGERED @ 24" MINIMUM.

2. AN APPROVED TESTING LABORATORY SHALL PROVIDE A P REQUALIFICATION TENSION TEST FOR SAMPLES ON EVERY SIZE OF BAR BEING WELDED.

3. MATERIALS, CONDITIONS AND WELDING PROCEDURES UTI LIZED SHALL COMPLY WITH THE

CURRENT APPLICABLE BUILDING CODE AND THE REQUIREMENTS OF THE GOVERNING INSPECTION AGENCY.

4. GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL COSTS INCURRED IN OBTAINING APPROVAL.

HORIZONTAL BAR VERTICAL BAR

60.00°
1/8''
1/8''
1/8'' 1/8"

45.00°

FORMOWORK PER

SPECIFICATIONS

STARTER WALL DETAIL

TYPICAL SECTION
A
2" PLANKING

TYPICAL

AFTER SETTING OF

CONCRETE, CLEAN TO
REMOVE LAITANCE and

SCUM - FORMWORK NOT

PERMITTED BELOW GRADE

UNLESS FULLY FORMED
CURB

CONTINUOUS

MINIMUM CLEAN OUT
3x LUMBER

TYPICAL
NOTE:

STAKES NOT PERMITTED WITHIN

FOOTING SECTION

FOOTING

CONCRETE OR

MASONRY WALL
2x4 CONT. SHAPED

KEY UNLESS

DETAILED

OTHERWISE

DRAWINGS+2"
WIDTH

SHOWN ON
6"

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.

Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"

CIVIL ENGINEER DATE
RCE EXP.

REVIEWED BY:

INSPECTOR DATE

SHEETS SHEET

ENGINEERING DEPARTMENT

CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:

APPROVED:

ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:

CHKD BY:

RVWD BY:

DATE INITIAL DATE INITIAL DATE INITIAL

ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4

JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008

CITY OF CARLSBAD
1902710

TYPICAL

FOUNDATION AND

SOG DETAILS
S6.02
Checker
MONROE ST. POOL REPLACEMENT

TYPICAL FOUNDATION AND SOG DETAILS
N.T.S.
1TYPICAL SPREAD FOOTING AT STEEL COLUMN
N.T.S.
2TYPICAL SECTION

AT CONCRETE STEPS OR RAMP ON GRADE
N.T.S.
3HOOKED (Ldh) AND HEADED (Ldt) BAR DEVELOPMENT LENGTH SCHEDULES N.T.S.
4TYPICAL REBAR WELDING
N.T.S.
5TYPICAL REINFORCING BUTT WELDS DETAIL
(ALTERNATE TO SPLICES)
N.T.S.
6TYPICAL MANDATORY FOUNDATION FORWORK
(UNLESS FULLY FORMED)
09/30/25
256
71 203
3RD PLAN CHECK SUBMITTAL 07/21/2024

08/09/2024

INTERSECTION (SINGLE CURTAIN)

CORNER (SINGLE CURTAIN)
#7 OR WALL VERTICALS

WHICHEVER IS GREATER
(4 TOTAL)

ALTERNATE BENDS
#7 OR WALL VERTICALS -

WHICHEVER IS GREATER
(3 TOTAL)
8"
8"
CLASS "B" SPLICE
8"
CLASS "B" SPLICE
8"
NOTE: "db" INDICATES

DIAMETER OF BAR
8" THK CONCRETE WALL
W/ #5 @ 12" O/C EACH WAY
DOWELS TO MATCH SIZE and

SPACING OF VERTICAL BARS -
PROVIDE STD. 90° HOOKS AT

← All documents from this meeting