CA Review GH
Meeting Date: Sept. 10, 2024
To: Mayor and City Council
From: Scott Chadwick, City Manager
Staff Contact: Steven Stewart, Municipal Projects Manager [email protected], 442-339-2938
Kyle Lancaster, Parks & Recreation Director
[email protected], 442-339-2941
Subject: Monroe Street Pool Renovation and Replacement Project Plans, Specifications and Contract Documents, Appropriation of Construction Funding, and Authorization to Advertise the Project for Construction Bids District: 1
Recommended Actions
Adopt a resolution approving the Monroe Street Pool Renovation and Replacement Project’s plans, specifications and contract documents, appropriating $18,158,361 in construction funding, and authorizing the City Clerk to advertise the project for construction bids.
Executive Summary
Monroe Street Pool, located next to Carlsbad High School in northern Carlsbad, was built in 1982 and now requires significant repairs and upgrades to remain operational and compliant with health and safety and building codes. City staff developed three options, ranging from the bare minimum to keep the pool operational and compliant to an option that would increase the pool complex’s capacity, use and lifespan. Based on community input, the City Council voted in 2021 to pursue the latter option.
Because certain projects over $1 million require voter approval, the City Council put a measure on the ballot for the Monroe Street Pool Renovation and Replacement Project in November 2022, which was approved. Since that time, staff have completed all the work needed to get the project ready to be put out for construction bids, including obtaining a detailed cost estimate.
To date, the City Council has approved $4.8 million for the project. An additional $18.16 million is needed for construction, which is expected to take about a year and a half once the work gets underway.
Carlsbad Municipal Code Section 3.28.080(E) requires City Council approval of plans, specifications and contract documents of projects when the expected value of work is more than $200,000.
Sept. 10, 2024
Item #8 Page 1 of 15
Explanation & Analysis
Starting in 2015, the City Council has taken several actions to address this need for repairs and upgrades for the pool.
Past City Council actions
June 30, 2015 Approved adding the Monroe Street Pool Renovation/Replacement Project, to the fiscal year 2015-16 Capital Improvement Program as Project No. 4724.
April 9, 2019 Authorized a $674,577 agreement with the design firm LPA Inc. for architectural and engineering design services for the project. (Resolution No. 2019-049) Jan. 26, 2021 Approved a motion selecting design concept three for the project and directing staff to pursue placing an expenditure measure on the June 7, 2022, primary election ballot.
Feb. 22, 2022 Deferred the timing of the ballot measure. (Resolution No. 2022-049) April 26, 2022 Approved a motion directing staff to prioritize maintenance and repairs to keep the pool facility functioning until the project was ready to build.
June 21, 2022 Placed the measure on the Nov. 8, 2022, general election ballot. (Resolution No. 2022-156).
Feb. 14, 2023 Amended the agreement with LPA Inc. to develop the final design and construction plans and specifications for the project. (Resolution No. 2023-055) Public input
Monroe Street Pool users have reported concerns to the city in recent years about the condition of the facility and the need for more pool lanes overall in Carlsbad. Neighbors of the Monroe Street Pool have also contacted the city over the years with concerns related to abating noise.
City staff used this background along with other input gathered from pool users and neighbors, to develop three options for the project. Option one is the bare minimum to keep the pool operational; option two was to modernize the pool but keep it the same size, while option three was to increase the pool’s size and configuration to provide 50% more lanes and include added solar energy opportunities, a new mechanical room and family restrooms, a reconfigured lobby, first aid and administrative offices, meeting space, a larger parking lot and several other features.
Between Aug. 31 and Sept. 30, 2020, staff sought feedback on the options, including the features, timeframe to complete, costs and expected lifespan of the improvements.
In all, 944 community members provided a total of 23,964 responses to an online survey seeking feedback about the options. The city also gathered 591 open-ended comments from the public during this time. Nearly half of the respondents – 47% – were from District 1, followed by 25% from District 2, 15% from District 3 and 14% from District 4. Opinions did not differ significantly among respondents from different districts.
Based on this input, the most important features of a renovated or new Monroe Street Pool facility were:
• A larger pool size
• More availability for lap swimming
• More use of solar
Sept. 10, 2024
Item #8 Page 2 of 15
When asked about the tradeoffs among the three options, most respondents favored making the pool complex as good as it can be now, so the city does not need to come back later to make more upgrades.
In January 2021, staff presented the options and community feedback to the City Council. The City Council voted to proceed with the community’s preferred concept, option three, which had the highest cost but maximized the capacity, use and lifespan of the pool complex.
Project description
The Monroe Street Pool Renovation and Replacement Project includes the following features:
• Larger and reconfigured pool with 50% more lanes
• New 8-foot wall with metal gates along Monroe Street to reduce sound for the surrounding neighborhood
• Larger pool deck with lockers and outdoor showers
• Renovated locker rooms
• More shade
• More bleachers
• Larger parking lot
• Addition of an outdoor entrance for competitions (instead of going through the lobby to get to the pool)
• Family restrooms
• Reconfigured lobby, first aid and administration offices and a room that can be used for meetings and small gatherings like birthday parties
• All new pool tile, plaster, piping, pool deck, drainage, pumps and filters • New building for pool equipment with separate entrance for service vehicles so they don’t take up space in the parking lot
• Replacement of existing solar water heating system and installation of rooftop solar panels to generate electricity
Sept. 10, 2024
Item #8 Page 3 of 15
Monroe Street Pool
33-meter pool,
15 lanes (7' 3")
More parking spaces
Family restrooms
, Sports lighting
Shade
Exterior entrance/exit
Locker rooms, reception,
office space
Voter approval
In Carlsbad, spending over $1 million in general city funds for certain types of construction projects requires voter approval. The City Council put the following measure on the Nov. 8, 2022, ballot:
Measure J
Do the voters of the City of Carlsbad approve spending existing city funds from various sources, including the General Fund, in an amount to exceed $1 million for the Monroe Street Pool Renovation/Replacement Project located at 3401 Monroe Street for an estimated cost range of $22 million up to $24 million, adjusted annually by the percentage increase in the regional construction cost index? The measure was approved. Following voter approval, the City Council directed staff to proceed with a final design, and the construction plans and specifications, and then develop an updated cost estimate. Staff have completed this work.
Regional Construction Cost Index
Measure J authorized the city to spend up to $24 million, adjusted annually based on the regional construction cost index. This index tracks inflation specifically for the construction industry. The regional construction cost index for 2023 was 9.4%.
Approved spending
2022 Voter approved use of city funds $24.00 million
2023 Regional construction cost index 9.4%
2024 Funds authorized in today’s dollars $25.02 million Fiscal Analysis
The total cost of the Monroe Street Pool Renovation and Replacement Project is estimated at $22,969,126, which is within the amount approved by voters.
Available funding sources
Different types of city funds come with different restrictions on how they can be spent. The following funds could be used to pay for the construction of the Monroe Street Pool project:
Northwest Park Development (Park-In-Li
eu) Fund
When residential developers build projects of a certain size in Carlsbad, they pay fees to help fund the infrastructure and amenities new residents will need. The fees for parks and recreation amenities are called park in lieu fees. These funds are collected by region of the city and may only be used for projects in that region.
Public Facilities Fund
Money in this fund is collected by developers to be used for civic facilities, park development, streets, traffic signals and other similar uses.
Infrastructure Rep air and Replacement Fund
The city sets aside a percentage of its annual budget each year to fund future infrastructure needs. This money can pay for maintaining or replacing city facilities and other infrastructure.
Sept. 10, 2024
Item #8 Page 4 of 15
General Capital Construction Fund
The city also sets aside money each year to save up for major construction projects that cannot be paid for through other more restricted funds. For example, money the city collects through the gas tax is restricted to paying only for road projects. Therefore, the city would first use gas tax funds to pay for a road project. The city would only consider other funding sources if there weren’t enough money in the gas tax fund.
General Fund
The city’s General Fund is used to carry out the essential day-to-day services of local government, like police and fire protection, street maintenance and library operations.
The main sources of money for this fund are the city’s portion of sales tax and property tax, as well as the tax visitors pay when they stay in local hotels and short-term vacation rentals. The City Council has the greatest discretion over how money in the General Fund is spent.
Funding to date
The City Council has appropriated the following funding for the Monroe Street Pool Renovation and Replacement Project
Funding appropriated to date
General Capital Construction Fund $236
Infrastructure Replacement Fund $1,748,766
Park Development (Park-In-Lieu) Fund - Northwest $3,061,765 TOTAL $4,810,765*
Design and Permitting Services (completed) -$2,348,791
REMAINING $2,461,974
* Actual amount (individual fund dollar amounts have been rounded)
Construction cost estimate
Completing the project’s final design, plans and specifications has allowed staff and consultants to develop a more detailed construction cost estimate:
Monroe Street Pool Renovation and Replacement Project
Construction contract (estimated)* $16,668,000
Construction contingency (10%) $1,666,800
Construction management and inspection costs, furnishings, neighborhood outreach during construction (estimated) $2,285,535 CONSTRUCTION COST ESTIMATE $20,620,335
FUNDS ALREADY APPROPRIATED -$2,461,974
ADDITIONAL APPROPRIATION NEEDED $18,158,361
* Actual construction costs depend on the bids received.
Sept. 10, 2024
Item #8 Page 5 of 15
Funding considerations
When more than one funding source is available, staff consider the following:
• Which fund is most appropriate based on the nature of the project • What other projects may be drawing from these funds in the next five years • The fund’s balance today and projected balance in five years Approximately one-third of the project’s scope of work is associated with core maintenance, repair and refurbishment needs of the 42-year-old facility. The funding for that one-third of the project, which is estimated to cost over $6 million, would be needed regardless of whether other elements of the project were included. The other approximately two-thirds of the project’s scope of work is associated with expanding, enhancing and modernizing the facility.
After considering other planned projects that may use the available funding sources over the next five years, staff recommend one-third of the construction funding for the Monroe Street Pool Renovation and Replacement Project come from the Infrastructure Repair and Replacement Fund and two-thirds of the construction funding come from the General Capital Construction Fund.
Balance
today
5-year
projection
Recommended
appropriation
Public Facilities Fees Fund $28 M $35 M none
Infrastructure Replacement Fund $63 M $34 M $6,052,787
General Capital Construction Fund $31 M $37 M $12,105,574 General Fund Reserve $131 M $141 M none
Operating Costs
The city’s Finance Department considers not just the construction cost of a new or expanded facility, but the cost to operate and maintain the facility in the future. The operating expenses for the renovated and expanded facility are projected to increase by approximately $370,000 a year due to the facility’s increase in size, capacity, programming and maintenance costs.
Staff expect this increase in annual operating expenses would be fully offset by an increase in revenues resulting from greater use of the facility by community members, and the implementation of fees consistent with that of the Alga Norte Aquatic Center. A recreation planning and operations consulting firm has independently reviewed staff’s calculations and validated the expectation of a net cost neutrality over current budget.
Sept. 10, 2024
Item #8 Page 6 of 15
Next Steps
With the City Council’s approval, the City Clerk will advertise the construction project for bids.
Staff anticipate returning to the City Council in early 2025 to request the award of a contract for the construction and a contract for the construction management and inspection services.
Construction is expected to take about a year and a half, with completion expected in summer 2026.
Environmental Eval uation
On July 19, 1977, the City Council certified the environmental impact report (EIR-380) for the Monroe Street Pool, at the time identified as the “community swimming pool.” The project is within the scope of the prior environmental document and no further environmental documentation is required per California Environmental Quality Act Guidelines Section 15162.
The conditional use permit (CUP-158) and the certified environmental impact report (EIR-380) for the Community Swim Complex allowed for larger pool(s), building(s) and parking lots than what was originally constructed. All applicable mitigation measures contained in the prior environmental document have either been satisfied previously and/or were made conditions of approval of the project’s approved conditional use permit. There have not been substantial changes to the circumstances under which the project is undertaken and there have been no new significant environmental effects that would modify or change any mitigation measures.
The pool operates in conjunction with the existing school facility, and the proposed changes do not result in new significant impacts or a substantial increase in the severity of previously identified impacts because the site and neighborhood context have not changed. Projects constructed by the school district since the pool was constructed have not impacted pool operations. The changes to the pool will have no impact to the adjacent school facilities. The mitigation measures to reduce impacts remain in place and are adequate to maintain the same level of significance studied in the previous environmental impact report, therefore none of the situations in Section 15162(a) exist and no additional environmental review is necessary. The certified environmental impact report and mitigation measures are on file for review at the Planning Division.
The City Planner determined on Feb. 7, 2023, that design concept three was consistent with the approved conditional use permit for the Community Swim Complex (the former name of the Monroe Street Pool facility), as shown in Exhibit 3.
Exhibits
1. City Council resolution
2. Plans, specifications and contract documents (on file in the Office of the City Clerk)
3. City Planner’s consistency determination with conditional use permit, dated Feb. 7, 2023
Sept. 10, 2024
Item #8 Page 7 of 15
Exhibit 1
Sept. 10, 2024
Item #8 Page 8 of 15
RESOLUTION NO. 2024-214
A RESOLUTION OF THE CITY COUNCIL OF THE CITY OF CARLSBAD,
CALIFORNIA, APPROVING THE MONROE STREET POOL RENOVATION AND
REPLACEMENT PROJECT'S PLANS, SPECIFICATIONS AND CONTRACT DOCUMENTS, APPROPRIATING $18,158,361 IN CONSTRUCTION FUNDING,
AND AUTHORIZING THE CITY CLERK TO ADVERTISE THE PROJECT FOR
CONSTRUCTION BIDS
WHEREAS, the City Council of the City of Carlsbad, California has determined it necessary, desirable and in the public interest to construct the Monroe Street Pool Renovation and Replacement Project as designed; and
WHEREAS, on Feb. 14, 2023, the City Council adopted Resolution No. 2023-055, authorizing the execution of Amendment No. 3 to the agreement with LPA Inc. to prepare design and construction plans and specifications for the Monroe Street Pool Renovation and Replacement Project, Capital Improvement Program Project No. 4724, and
WHEREAS, the City Council of the City of Carlsbad, California has determined that the plans, specifications and contract documents for the Monroe Street Pool Renovation and Replacement Project have been completed to the satisfaction of staff; and WHEREAS, the plans, specifications and contract documents for the project are on file at the City Clerk's Office and are incorporated by reference; and WHEREAS, an additional appropriation in the amount of $18,158,361, to be funded with $6,052,787 from the Infrastructure Repair and Replacement Fund, and $12,105,174 from the General Capital Construction Fund, is needed to fund the construction of the project; and WHEREAS, on July 19, 1977, the City Council certified the Environmental Impact Report (EIR- 380) for the Monroe Street Pool, at the time identified as the "community swimming pool"; and WHEREAS, the Monroe Street Pool Renovation and Replacement Project, Concept 3, is within the scope of the prior environmental document and no further environmental documentation is required in accordance with California Environmental Quality Act Guidelines Section 15162; and WHEREAS, the City Planner determined on Feb. 7, 2023, that design concept three was consistent with the approved conditional use permit for the Community Swim Complex, the former name of the Monroe Street Pool facility .
Sept. 10, 2024
Item #8 Page 9 of 15
NOW, THEREFORE, BE IT RESOLVED by the City Council of the City of Carlsbad, California, as follows:
1. That the above recitations are true and correct.
2. That the plans, specifications and contract documents for the Monroe Street Pool Renovation and Replacement Project, Capital Improvement Program Project No. 4724, are approved and on file at the City Clerk's Office.
3. That the City Manager or designee is authorized to appropriate $18,158,361 to Project No. 4724 to be funded as follows: $6,052,787 from the Infrastructure Repair and Replacement Fund and $12,105,574 from the General Capital Construction Fund.
4. That the City Clerk is hereby authorized and directed to publish, in accordance with state law and Carlsbad Municipal Code Section 3.28.080((), a notice to contractors inviting bids for construction of the Monroe Street Pool Renovation and Replacement Project, Project No. 4724, in accordance with the plans, specifications and contract documents referred to herein.
PASSED, APPROVED AND ADOPTED at a Regular Meeting of the City Council of the City of Carlsbad on the 10th day of September, 2024, by the following vote, to wit:
AYES:
NAYS:
ABSTAIN:
ABSENT:
BLACKBURN, BHAT-PATEL, ACOSTA, BURKHOLDER, LUNA.
NONE.
NONE.
NONE.
\
KEITH B CKBURN, Mayor
(JJl
SHERRY FREISINGER, City Clerk
(SEAL)
Exhibit 2
Plans
, specifications and contract documents
(on file in the Office of the City Clerk)
Sept. 10, 2024
Item #8 Page 10 of 15
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
PROJECT NUMBER
NOT FOR CONSTRUCTION
ARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
1902710
3RD PLANCHECK SUBMITTAL
08/09/2024
08/09/2024
Exhibit 2
CAB CABINET
CB CATCH BASIN
CEM CEMENT
CER CERAMIC
CI CAST IRON
CIP CAST IN PLACE
CIV ENG CIVIL ENGINEER
CG CORNER GUARD
CJ CONTROL JOINT
CLG CEILING
CLKG CAULKING
CLO CLOSET
CLR CLEAR
CNTR COUNTER
CO CASED OPENING
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONSTR CONSTRUCTION
CONT CONTINUOUS
CORR CORRIDOR
CT CERAMIC TILE
CTR CENTER
CTSK COUNTERSUNK
DA DISABLED ACCESS
DBL DOUBLE
DEPT DEPARTMENT
DESC DESCRIPTION
DF DRINKING FOUNTAIN
DET DETAIL
DIA DIAMETER
DIM DIMENSION
DISP DISPENSER
DN DOWN
DO DOOR OPENING
DR DOOR
DWR DRAWER
DS DOWNSPOUT
DSP DRY STANDPIPE
DWG DRAWING
E EAST
EA EACH
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
ENCL ENCLOSURE
EP ELECTRICAL PANELBOARD
EQ EQUAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXPO EXPOSED
EXP EXPANSION
EXT EXTERIOR
FA FIRE ALARM
FB FLAT BAR
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER
CABINET
FHC FIRE HOSE CABINET
FIN FINISH
FLR FLOOR
FLASH FLASHING
FLUOR FLUORESCENT
FOC FACE OF CONCRETE
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUD
FOV FACE OF VENEER (BRICK OR
PRECAST)
FOW FACE OF WALL
FR FIRE RETARDANT
FPRF FIREPROOF
FS FINISH SURFACE
FT FOOT OR FEET
FTG FOOTING
FURR FURRING
FUT FUTURE
ID INSIDE DIAMETER
INSUL INSULATION
INT INTERIOR
JAN JANITOR
JT JOINT
KIT KITCHEN
LAB LABORATORY
LAM LAMINATE
LAND ARCH LANDSCAPE ARCHITECT
LAV LAVATORY
LKR LOCKER
LT LIGHT
MATL MATERIAL
MAX MAXIMUM
MC MEDICINE CABINET
MECH MECHANICAL
MEMB MEMBRANE
MET METAL
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
MO MASONRY OPENING
MTD MOUNTED
MUL MULLION
N NORTH
NIC NOT IN CONTRACT
NO/# NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OVERALL
OA OUTSIDE AIR
OBS OBSCURE
OC ON CENTER
OD OUTSIDE DIAMETER
OFF OFFICE
OPNG OPENING
OPP OPPOSITE
OSA OUTSIDE AIR
PA PLANTING AREA
PRCST PRECAST
PH PANIC HARDWARE
PL PLATE
P LAM PLASTIC LAMINATE
PLAS PLASTER
PLYWD PLYWOOD
POT PATH OF TRAVEL
PR PAIR
PT PAINT
PTD PAPER TOWEL DISPENSER
PTD/R COMBINATION PAPER
TOWEL DISPENSER &
RECEPTACLE
PTN PARTITION
PTR PAPER TOWEL
RECEPTACLE
QT QUARRY TILE
R RISER
RAD RADIUS
RD ROOF DRAIN
REF REFERENCE
REFR REFRIGERATOR
RGTR REGISTER
REINF REINFORCED
REQD REQUIRED
RESIL RESILIENT
RM ROOM
RO ROUGH OPENING
ROW RIGHT OF WAY
RWD REDWOOD
RWL RAIN WATER LEADER
S SOUTH
SC SOLID CORE
SCD SEAT COVER DISPENSER
SCHED SCHEDULE
SD SOAP DISPENSER
SECT SECTION
SF SQUARE FEET
SH SHELF
SHR SHOWER
SHT SHEET
SIM SIMILAR
SND SANITARY NAPKIN
DISPENSER
SNR SANITARY NAPKIN
RECEPTACLE
SPEC SPECIFICATION(S)
SQ SQUARE
SS STAINLESS STEEL
S SK SERVICE SINK
STA STATION
STD STANDARD
STL STEEL
STOR STORAGE
STR STRUCTURAL
SUSP SUSPENDED
SYM SYMMETRICAL
& AND
∠ ANGLE
@ AT
℄ CENTERLINE
∅ DIAMETER OR ROUND
# POUND OR NUMBER
(E) EXISTING
(P) PAINT
(R) REMOVE
+/- DIM TOLERANCE
AC ASPHALTIC CONCRETE
ACC ACCESSIBLE
ACOUS ACOUSTICAL
ACM ALUM COMPOSITE MATERIAL
ACT ACOUS CLG TILE
AD AREA DRAIN
AED AUTO EXT DEFIBRILLATOR
ADJ ADJUSTABLE
AFF ABOVE FINISH FLOOR
AGGR AGGREGATE
AHJ AUTHORITY HAVING
JURISDICTION
ALUM ALUMINUM
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ASF ASSIGNABLE SF
ASPH ASPHALT
BD BOARD
BITUM BITUMINOUS
BLDG BUILDING
BLK BLOCK
BLK'G BLOCKING
BM BEAM
BOC BACK OF CURB
BOT BOTTOM
BO BOTTOM OF
BOC BACK OF CURB
BOW BOTTOM OF WALL
BS BOTTOM OF SLOPE
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GI GALVANIZED IRON
GL GLASS
GND GROUND
GR GRADE
GYP GYPSUM
HB HOSE BIB
HC HOLLOW CORE
HDWD HARDWOOD
HDW HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HOUR
HGT/HT HEIGHT
T TREAD
TB TOWEL BAR
TC TOP OF CURB
TEL TELEPHONE
TER TERRAZZO
T&G TONGUE & GROOVE
THK THICK
TOB TOP OF BEAM
TOC TOP OF CONCRETE
TOW TOP OF WALL
TOP TOP OF PARAPET
TPD TOILET PAPER DISPENSER
TS TOP OF SLOPE
TV TELEVISION
TYP TYPICAL
UNF UNFINISHED
UNO UNLESS NOTED
OTHERWISE
UR URINAL
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
W WEST
W/ WITH
WC WATER CLOSET
WD WOOD
W/O WITHOUT
WP WATERPROOF
WR WATER RESISTANT
WSCT WAINSCOT
WT WEIGHT
WWF WELDED WIRE FABRIC
COLUMN LINES
0 0
SURFACE DRAINAGE
ARROW INDICATES
DIRECTION OF FLOW
N
PROJECT NORTH
BUILDING SECTION
1 A101
TYP
SECTION ID
SHEET NUMBER
1 A101 TYP
WALL SECTION
SECTION ID
SHEET NUMBER
DETAIL CALLOUTS
DETAIL ID
SHEET NUMBER
1 A101
SIM
DETAIL SECTION
DETAIL ID
SHEET NUMBER
1 A101
SIM
DETAIL REFERENCE
DETAIL ID
SHEET NUMBER
1 A101
SIM
INTERIOR ELEVATIONS
DETAIL ID
SHEET NUMBER
A
C
SIM
D BA101
DOOR DESIGNATION
ROOM DESIGNATION
ROOM NUMBER
ROOM AREA
1REVISION CLOUD &
TAG (OPTIONAL
SA2U
1t
SHADED PORTION POINTS
TO SIDE REFERENCED
DATUM POINT
KEYNOTE
WALL TYPE
WINDOW TYPE
TYP.
?
MATCH LINE
SEE SHEET A101
Name
Elevation
LEVEL LINE, CONTROL POINT
EL: 12'-8" = ELEVATION/SECTION
STAIR DIRECTION
DN
UP
CENTER LINES, FLOOR LINES
HIDDEN CONSTRUCTION FEATURE
BREAK LINE
####
FINISH TAG XX -##
EQUIPMENT TAG 1i
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
SHEET INDEX
G0.10
MD
MONROE ST. POOL REPLACEMENT
SHEET INDEX
SHEET INDEX
SHEET NUMBER SHEET NAME
GENERAL INFORMATION
G0.00 COVER SHEET
G0.10 SHEET INDEX
G0.20 GENERAL PROJECT INFORMATION
G0.40 CALGREEN (CA)
G0.41 CALGREEN (CA)
G0.42 CALGREEN (CA)
G2.10 CODE ANALYSIS
G2.11 EGRESS PLAN
G0.31 TYPICAL ACCESSIBILITY NOTES AND DETAILS
G0.32 TYPICAL ACCESSIBILITY NOTES AND DETAILS
CIVIL
C1 TITLE SHEET
C2 CIVIL NOTES
C3 EXISTING CONDITIONS
C4 DEMOLITION PLAN
C5 GRADING PLAN
C6 GRADING ENLARGEMENT
C7 STORM DRAIN PLAN
C8 UTILITY PLAN
C9 HORIZONTAL CONTROL AND PAVING PLAN
C10 DETAILS
C11 DETAILS
C12 SINGLE SHEET BMP SITE PLAN
LANDSCAPE
L0.01 LANDSCAPE NOTES AND SCHEDULE
L0.02 LANDSCAPE NOTES AND SCHEDULE
L1.01 MATERIALS PLAN
L1.02 LAYOUT PLAN
L3.01 ENLARGEMENT PLAN
L4.01 SECTIONS AND ELEVATIONS
L4.02 SECTIONS AND ELEVATIONS
L4.03 SECTIONS AND ELEVATIONS
L4.04 SECTIONS AND ELEVATIONS
L5.01 CONSTRUCTION DETAILS
L5.02 CONSTRUCTION DETAILS
L5.03 CONSTRUCTION DETAILS
L5.04 CONSTRUCTION DETAILS
L5.05 CONSTRUCTION DETAILS
L5.06 CONSTRUCTION DETAILS
L5.07 CONSTRUCTION DETAILS
L5.08 CONSTRUCTION DETAILS
L5.09 CONSTRUCTION DETAILS
L5.10 CONSTRUCTION DETAILS
L5.11 CONSTRUCTION DETAILS
L5.12 CONSTRUCTION DETAILS
L6.01 IRRIGATION PLAN
L6.02 IRRIGATION LEGEND
L6.03 IRRIGATION DETAILS
L6.04 IRRIGATION DETAILS
L6.05 IRRIGATION DETAILS
L6.06 IRRIGATION DETAILS
L7.01 PLANTING PLAN
L7.02 PLANTING DETAILS
ARCHITECTURE
A0.21 SITE PLAN
A0.31 TRASH ENCLOSURE
A1.01 DEMO FLOOR PLAN & RCP BLDG A
A1.02 DEMO ROOF PLAN - BLDG A
A1.03 DEMO ELEVATIONS BLDG A
A2.01 FIRST FLOOR PLAN - BLDG A & B
A2.09 ROOF PLAN - BLDG A & B
A2.11 FIRST FLOOR EDGE OF SLAB PLAN - BLDG A & B
A2.21 FIRST FLOOR FINISHES PLAN - BLDG A & B
A2.31 FIRST FLOOR REFLECTED CEILING PLAN - BLDG A & B
A3.01 EXTERIOR ELEVATIONS - BLDG A
A3.02 EXTERIOR ELEVATIONS - BLDG B
A3.11 BUILDING SECTIONS BLDG A
A3.12 BUILDING SECTIONS BLDG B
A3.20 WALL SECTIONS
A3.21 WALL SECTIONS
A3.22 WALL SECTIONS
A3.23 WALL SECTIONS
A3.24 WALL SECTIONS
A3.26 WALL SECTIONS
A3.27 WALL SECTIONS
A4.01 ENLARGED PLANS & INTERIOR ELEVATIONS
A4.02 ENLARGED PLANS & INTERIOR ELEVATIONS
A4.03 ENLARGED RESTROOM PLANS & ELEVATIONS
A4.04 ENLARGED RESTROOM PLANS & ELEVATIONS
A4.05 ENLARGED RESTROOM PLANS & ELEVATIONS
A4.06 ENLARGED RESTROOM PLANS & ELEVATIONS
A4.07 ENLARGED RESTROOM PLANS & ELEVATIONS
A6.11 DOOR SCHEDULES
A6.21 OPENING TYPES
A6.31 FINISH & EQUIPMENT SCHEDULES
A8.12 EXTERIOR DETAILS
A8.13 EXTERIOR DETAILS
A8.14 OPENING DETAILS
A8.21 ROOF DETAILS
A8.22 ROOF DETAILS
A9.01 PARTITION TYPES
A9.11 INTERIOR DETAILS
A9.12 INTERIOR DETAILS
A9.21 CEILING DETAILS
A9.31 CASEWORK DETAILS
A9.32 CASEWORK DETAILS
A9.41 RESTROOM DETAILS
A9.42 RESTROOM DETAILS
A10.01 SIGNAGE PLAN & SCHEDULE - BLDG A & B
A10.41 SIGNAGE DETAILS
STRUCTURAL
SHEET INDEX
SHEET NUMBER SHEET NAME
AV3.01 AUDIO VISUAL ELEVATIONS
AV4.01 AUDIO VISUAL ONE LINE DIAGRAM
AV5.02 AUDIO VISUAL DETAILS
TECHNOLOGY
T0.01 TECHNOLOGY SYMBOLS AND LEGENDS
T0.02 TECHNOLOGY SITE PLAN
T1.00 TECHNOLOGY OVERALL FLOOR PLAN
T1.01 DEMO FLOOR PLANS - BUILDING A & B
T2.01 TECHNOLOGY FLOOR PLANS - BUILDING A & B
T5.01 TECHNOLOGY DETAILS
AQUATICS
SP-0 SWIMMING POOL AREA PLAN
SP-1 SWIMMING POOL LAYOUT PLAN
SP-2 SWIMMING POOL PIPING PLAN
SP-3 SWIMMING POOL UNDERWATER LIGHTING AND TIMING
PLAN
SP-4 SWIMMING POOL SECTIONS
SP-5 SWIMMING POOL WATER POLO LAYOUT
SP-6 DETAILS
SP-7 DETAILS
SP-8 DETAILS
SP-9 DETAILS
SP-10 DETAILS
SP-11 DETAILS
SP-12 DETAILS
SP-13 DETAILS
SP-14 DETAILS
SP-15 DETAILS
SP-16 DETAILS
SP-17 DETAILS
SP-18 SWIMMING POOL THERMAL SOLAR PLAN
SP-19 DETAILS
SP-20 DETAILS
AQUATICS
MR-1 MECHANICAL ROOM LAYOUT PLAN
MR-2 MECHANICAL ROOM SECTIONS
MR-3 DETAILS
MR-4 DETAILS
MR-5 DETAILS
MR-6 DETAILS
MR-7 DETAILS
MR-8 DETAILS
MR-9 DETAILS
MR-10 DETAILS
MR-11 DETAILS
SPORTS LIGHTING
MT1 NOTES FOUNDATION DETAIL
MS1 POLE DETAILS
MD1 ATTACHMENT DETAILS
MD2 ATTACHMENT DETAILS
MD3 ATTACHMENT DETAILS
SHADE
NC90132-1-1
000
NOTES/ LOM
NC90132-1-2
000
VIEWS AND DETAILS
NC90132-1-3
000
FOOTING DETAILS
NC90132-2-1
000
NOTES/ LOM
NC90132-2-2
000
VIEWS AND DETAILS
NC90132-2-3
000
FOOTING DETAILS
NC90132-3-1
000
NOTES/ LOM
NC90132-3-2
000
VIEWS AND DETAILS
NC90132-3-3
000
FOOTING DETAILS
ABBREVIATIONS SYMBOLS LEGEND SHEET INDEX
SHEET NUMBER SHEET NAME
S0.01 GENERAL NOTES
S0.02 GENERAL NOTES
S0.03 GENERAL NOTES
S1.11 SITE DETAILS
S1.12 SITE DETAILS
S1.13 SITE DETAILS
S1.21 SITE PLAN
S2.01A FOUNDATION PLAN - BLDG A
S2.09A ROOF FRAMING PLAN - BLDG A
S2.09B ROOF FRAMING PLAN - BLDG B
S3.01 ELEVATIONS - BLDG B
S3.02 ELEVATIONS - BLDG A
S3.21 PERF PANEL FRAMING ELEVATIONS AND SECTION
S6.01 TYPICAL FOUNDATION AND SOG DETAILS
S6.02 TYPICAL FOUNDATION AND SOG DETAILS
S6.03 TYPICAL FOUNDATION AND SOG DETAILS
S6.04 TYPICAL FOUNDATION AND SOG DETAILS
S6.05 TYPICAL FOUNDATION AND SOG DETAILS
S6.11 TYPICAL STRUCTURAL STEEL DETAILS
S6.12 TYPICAL STRUCTURAL STEEL DETAILS
S6.13 TYPICAL METAL DECKING DETAILS
S6.14 TYPICAL DECK SUPPORTING DETAILS
S6.61 TYP. CMU WALL ELEVATION AND DETAILS
S6.62 TYP. CMU WALL ELEVATION AND DETAILS
S6.63 TYP CMU WALL DETAILS
S6.81 TYP WOOD FRAMING DETAILS
S6.82 WOOD FRAMING DETAILS
S6.94 TYP EQUIP ANCHORAGE to WOOD
S6.71 TYPICAL LIGHT GAUGE FRAMING SCHEDULES and
ELEVATIONS
S6.72 TYPICAL LIGHT GAUGE METAL FRAMING DETAILS
S6.73 TYPICAL LIGHT GAUGE METAL FRAMING DETAILS 2
S6.74 TYPICAL INTERIOR LIGHT GAUGE FRAMING DETAILS
S6.91 EQUIPMENT ANCHORAGE DETAILS
S6.92 EQUIPMENT ANCHORAGE DETAILS
S6.93 TYP EQUIP ANCHORAGE to WOOD
MECHANICAL
M0.10 MECHANICAL LEGENDS AND GENERAL NOTES
M0.11 MECHANICAL LEGENDS AND GENERAL NOTES
M0.20 MECHANICAL SCHEDULES
M0.30 MECHANICAL TITLE-24 FORMS
M0.31 MECHANICAL TITLE-24 FORMS
M0.32 MECHANICAL TITLE-24 FORMS
M0.33 MECHANICAL TITLE-24 FORMS
M1.01 MECHANICAL DEMO FLOOR PLAN - BLDG A & B
M1.09 MECHANICAL DEMO ROOF PLAN - BLDG A & B
M2.01 MECHANICAL FLOOR PLAN - BLDG A & B
M2.09 MECHANICAL ROOF PLAN - BLDG A & B
M3.01 MECHANICAL PIPING/CONTROLS FLOOR PLAN - BLDG A & B M3.09 MECHANICAL PIPING & CONTROLS ROOF PLAN - BLDG A & B
M6.01 MECHANICAL CONTROL SEQUENCES AND DIAGRAMS
M7.10 MECHANICAL DETAILS AND DIAGRAMS
M7.11 MECHANICAL DETAILS AND DIAGRAMS
M7.12 MECHANICAL DETAILS AND DIAGRAMS
PLUMBING
P0.10 PLUMBING LEGENDS AND GENERAL NOTES
P0.20 PLUMBING FIXTURE AND EQUIPMENT SCHEDULES
P0.21 PLUMBING FIXTURE SCHEDULE & CALCULATIONS
P0.22 PLUMBING T24 BUILDING A
P0.23 PLUMBING T24 BUILDING B
P1.01 PLUMBING DEMO FLOOR PLAN - BLDG A & B
P1.09 PLUMBING DEMO ROOF PLAN - BLDG A & B
P2.01 PLUMBING DRAINAGE FLOOR PLAN - BLDG A & B
P3.01 PLUMBING WATER & GAS FLOOR PLAN - BLDG A & B
P3.09 PLUMBING ROOF PLAN - BLDG A & B
P4.01 PLUMBING ENLARGED PLANS - BLDG A
P4.02 PLUMBING ENLARGED PLANS - BLDG B
P6.10 PLUMBING DETAILS
P6.20 PLUMBING DETAILS
ELECTRICAL
E0.10 ELECTRICAL LEAD SHEET
E0.11 ELECTRICAL LEAD SHEET
E0.20 LIGHTING FIXTURE NOTES AND LCP SCHEDULES
E0.21 LIGHTING FIXTURE SCHEDULE
E1.10 ELECTRICAL SITE PLAN
E1.11 LIGHTING SITE PLAN
E2.01 ELECTRICAL DEMOLITION FLOOR PLAN - BLDG A & B
E2.02 ELECTRICAL FIRST FLOOR PLAN - BLDG A & B
E2.03 MECHANICAL/POWER FIRST FLOOR PLAN - BLDG A & B
E2.04 MECHANICAL/POWER ROOF PLAN - BLDG A & B
E3.01 LIGHTING PLANS
E4.01 ENLARGED ELECTRICAL PLANS
E5.01 SINGLE LINE DIAGRAM AND LOAD FEEDER SCHEDULE
E5.02 PV SYSTEM SINGLE LINE DIAGRAM
E5.03 PANEL SCHEDULES
E5.04 PANEL SCHEDULES
E5.05 PANEL SCHEDULES
E6.01 LIGHTING CONTROL DIAGRAM AND DETAILS
E6.02 LIGHTING CONTROL DIAGRAM AND DETAILS
E6.03 LIGHTING CONTROL DIAGRAMS AND DETAILS
E7.01 ELECTRICAL DETAILS
E7.02 ELECTRICAL DETAILS
E7.03 ELECTRICAL DETAILS
E7.04 PV DETAILS
E7.05 LIGHTING DETAILS
E8.01 ENERGY COMPLIANCE FORMS
E8.02 ENERGY COMPLIANCE FORMS
AUDIO VISUAL
AV0.01 AUDIO VISUAL SYMBOLS AND LEGENDS
AV0.03 AUDIO VISUAL SITE PLAN
AV1.02 AUDIO VISUAL OVERALL FLOOR PLAN
2 203
SHEET INDEX
SHEET NAME
SHEET LABEL
ISSUE DATEG0.00COVER SHEETGENERALG0.10SHEET INDEXG0.20GENERAL PROJECT INFORMATIONG0.32G0.40TYPICAL ACCESSIBILITY NOTES AND DETAILS G2.10G2.11CODE ANALYSIS
A1.01DEMO FLOOR PLAN & RCP BLDG A
ARCHITECTURE
08/09/2024
08/09/2024
08/09/202408/09/2024
08/09/202408/09/202408/09/202408/09/202408/09/2024
A2.01FIRST FLOOR PLAN - BLDG A & B08/09/2024A2.09
MECHANICALM0.10MECHANICAL LEGENDS AND GENERAL NOTES08/09/2024 E0.10ELECTRICAL LEAD SHEETELECTRICAL08/09/2024
E1.10ELECTRICAL SITE PLAN08/09/2024E1.1108/09/2024E2.01LIGHTING SITE PLAN08/09/2024E2.02ELECTRICAL DEMO FLOOR PLAN - BLDG A & B08/09/2024E2.03MECHANICAL/POWER FIRST FLOOR PLAN - BLDG A & B08/09/2024E3.01LIGHTING PLANS08/09/2024 08/09/2024A2.11
08/09/2024A3.01EXTERIOR ELEVATIONS - BLDG A08/09/2024A3.0208/09/2024A3.1208/09/2024A3.20WALL SECTIONS 08/09/202408/09/202408/09/2024ENLARGED RESTROOM PLANS AND ELEVATIONS M0.20MECHANICAL SCHEDULES08/09/2024M0.30MECHANICAL TITLE-24 FORMS08/09/2024M0.3108/09/2024 M2.01MECHANICAL FLOOR PLAN - BLDG A & B08/09/2024M3.01MECHANICAL PIPING/CONTROLS FLOOR PLAN - A & B08/09/2024 M7.1008/09/2024M7.1108/09/2024
MECHANICAL TITLE-24 FORMS
MECHANICAL DETAILS AND DIAGRAMSPLUMBING
SHEET NAME
ISSUE DATE
P0.10PLUMBING LEGENDS AND GENERAL NOTES08/09/2024P0.21PLUMBING FIXTURES AND EQUIPMENT SCHEDULES08/09/2024 P2.01
PLUMBING ENLARGED PLANS - BLDG A
08/09/2024
P4.01
PLUMBING DRAINAGE FLOOR PLAN - BLDG A & B
08/09/2024P6.20
PLUMBING WATER AND GAS FLOOR PLAN - BLDG A & B
08/09/2024
AV0.01AUDIO VISUAL08/09/2024
E0.11ELECTRICAL LEAD SHEET08/09/2024E0.20LIGHTING FIXTURE NOTES AND LCP SCHEDULES08/09/2024E0.21LIGHTING FIXTURE SCHEDULE08/09/2024 E4.01ENLARGED ELECTRICAL PLANS08/09/2024E5.01SINGLE LINE DIAGRAM AND LOAD FEEDER SCHEDULE08/09/2024E5.03PANEL SCHEDULES08/09/2024E5.0408/09/2024E6.01LIGHTING CONTROL DIAGRAMS AND DETAILS08/09/2024 E7.01ELECTRICAL DETAILS08/09/2024E7.02ELECTRICAL DETAILS08/09/2024E7.0308/09/2024 TECHNOLOGYT0.01TECHNOLOGY SYMBOLS & LEGENDS08/09/2024
T2.01TECHNOLOGY FLOOR PLANS - BLDG A & B08/09/2024T1.01TECHNOLOGY DEMO FLOOR PLANS - BLDG A & B08/09/202408/09/2024T5.01TECHNOLOGY DETAILS08/09/202408/09/2024 AUDIO VISUAL SYMBOLS AND LEGENDSAV0.0308/09/2024AUDIO VISUAL SITE PLANAV1.0208/09/2024AUDIO VISUAL OVERALL FLOOR PLANAV4.0108/09/2024AUDIO VISUAL ONE LINE DIAGRAMAV5.0208/09/2024AUDIO VISUAL DETAILS
SWIMMING POOL
08/09/2024SWIMMING POOL LAYOUT PLAN
08/09/2024SWIMMING POOL PIPING PLAN
08/09/2024SWIMMING POOL UNDERWATER LIGHT/TIMING PLAN
08/09/2024
SWIMMING POOL SECTIONS
08/09/2024DETAILS08/09/2024DETAILS08/09/2024DETAILS08/09/2024DETAILS08/09/2024DETAILS08/09/2024DETAILS08/09/2024DETAILS08/09/2024
MECHANICAL ROOM LAYOUT PLAN
08/09/202408/09/202408/09/202408/09/202408/09/2024
DETAILSDETAILSDETAILSDETAILS
DETAILS EGRESS PLAN
A4.01EXTERIOR PLANS & INTERIOR ELEVATIONS
08/09/2024
P6.10PLUMBING DETAILS08/09/2024
08/09/2024A2.2108/09/2024A2.31
08/09/2024A3.11BUILDING SECTIONS - BLDG A
08/09/202408/09/202408/09/202408/09/2024
08/09/202408/09/2024A4.04
MECHANICAL CONTROL SEQUENCES AND DIAGRAMSMECHANICAL DETAILS AND DIAGRAMS08/09/2024M6.0108/09/2024 PLUMBING ROOF PLAN08/09/2024
E8.0108/09/2024E8.02ENERGY COMPLIANCE FORMS08/09/2024ENERGY COMPLIANCE FORMS 08/09/2024
MECHANICAL ROOM SECTIONS G0.41CALGREEN08/09/2024G0.4208/09/2024 08/09/2024
T0.02TECHNOLOGY SITE PLAN08/09/2024T1.00TECHNOLOGY OVERALL FLOOR PLAN08/09/2024 AV3.0108/09/2024AUDIO VISUAL ELEVATIONS
P0.2008/09/2024
GRAND TOTAL SHEETS: 245
08/09/2024
CALGREENCALGREEN
A0.21SITE PLAN08/09/2024
A1.02DEMO FLOOR PLAN BLDG B08/09/2024A1.03DEMO ELEVATIONS BLDG A08/09/2024ROOF PLAN BLDG A & BFIRST FLOOR EDGE OF SLAB PLAN - BLDG A & BFIRST FLOOR FINISHES PLAN - BLDG A & BFIRST FLOOR REFLECTED CEILING PLAN - BLDG A & BEXTERIOR ELEVATIONS - BLDG BBUILDING SECTIONS - BLDG BA3.21WALL SECTIONSA3.22WALL SECTIONSA3.23WALL SECTIONSA3.24WALL SECTIONSA3.26WALL SECTIONSA3.27WALL SECTIONSA4.02EXTERIOR PLANS & INTERIOR ELEVATIONSA4.03ENLARGED RESTROOM PLANS AND ELEVATIONSA4.05ENLARGED RESTROOM PLANS AND ELEVATIONSA4.06ENLARGED RESTROOM PLANS AND ELEVATIONSA4.07ENLARGED RESTROOM PLANS AND ELEVATIONS08/09/2024A6.11DOOR SCHEDULES08/09/2024A6.31FINISH & EQUIPMENT SCHEDULES08/09/2024
TRASH ENCLOSURE
EXTERIOR DETAILSA8.1208/09/2024EXTERIOR DETAILSA8.1308/09/2024OPENING DETAILSA8.1408/09/2024OPENING DETAILSA8.1508/09/2024ROOF DETAILSA8.2108/09/2024ROOF DETAILSA8.2208/09/2024PARTITION TYPESA9.0108/09/2024A9.1108/09/2024INTERIOR TYPESA9.1208/09/2024INTERIOR TYPES
SHEET INDEX
SHEET NAME
SHEET LABEL
ISSUE DATE
A9.41RESTROOM DETAILS08/09/202408/09/202408/09/2024
A10.0108/09/2024A10.4108/09/2024SIGNAGE PLAN & SCHEDULE - BLDG A & BSIGNAGE DETAILS A9.32CASEWORK DETAILSA9.42RESTROOM DETAILS
S0.01GENERAL NOTESSTRUCTURAL08/09/2024
S1.11SITE DETAILS08/09/2024
S2.01AFOUNDATION PLAN - BLDG A
08/09/202408/09/2024
S3.01
08/09/2024
ELEVATIONS - BLDG B08/09/2024
S6.01TYPICAL FOUNDATION AND SOG DETAILSS6.02TYPICAL FOUNDATION AND SOG DETAILS S6.11
08/09/2024
TYPICAL STRUCTURAL STEEL DETAILSS6.13
08/09/2024
TYPICAL METAL DECKING DETAILS08/09/2024
S6.61TYPICAL CMU WALL ELEVATION AND DETAILSS6.63TYPICAL CMU WALL DETAILS S6.94
08/09/2024
08/09/2024S6.93
08/09/2024
TYPICAL EQUIP. ANCHORAGE TO WOOD
08/09/2024
S6.91TYPICAL EQUIPMENT ANCHORAGE DETAILSS6.92
08/09/2024
EQUIPMENT ANCHORAGE DETAILS
S0.02GENERAL NOTESS0.03GENERAL NOTESS1.12SITE DETAILS08/09/2024S1.21SITE PLAN08/09/2024S2.01BFOUNDATION PLAN - BLDG B08/09/2024S2.09AROOF FRAMING PLAN - BLDG A08/09/2024S2.09B08/09/2024ROOF FRAMING PLAN - BLDG BS3.02ELEVATIONS - BLDG B08/09/2024S3.21PERF PANEL FRAMING ELEVATIONS AND SECTION08/09/2024 S6.03TYPICAL FOUNDATION AND SOG DETAILS08/09/2024S6.04TYPICAL FOUNDATION AND SOG DETAILS08/09/2024S6.05TYPICAL FOUNDATION AND SOG DETAILS08/09/2024S6.12TYPICAL STRUCTURAL STEEL DETAILS08/09/2024 S6.62TYPICAL CMU WALL ELEVATION AND DETAILS08/09/2024
S6.81TYPICAL WOOD FRAMING DETAILS08/09/2024S6.82WOOD FRAMING DETAILS08/09/2024 TYPICAL EQUIP. ANCHORAGE TO WOOD08/09/202408/09/202408/09/2024 M0.11MECHANICAL LEGENDS AND GENERAL NOTES08/09/2024
M0.3208/09/2024MECHANICAL TITLE-24 FORMSM1.0108/09/2024MECHANICAL DEMO FLOOR PLAN - BLDG A & BM1.0908/09/2024MECHANICAL DEMO ROOF PLAN - BLDG A & BM2.09MECHANICAL ROOF PLAN - BLDG A & B08/09/2024M3.09MECHANICAL PIPING/CONTROLS ROOF PLAN - A & B M7.1208/09/2024MECHANICAL DETAILS AND DIAGRAMS
PLUMBING CALCULATIONS
P0.3008/09/2024PLUMBING DEMO SITE PLANP0.4008/09/2024PLUMBING SITE PLANP0.4008/09/2024PLUMBING SITE PLANP0.4108/09/2024PLUMBING SITE GAS PLANP1.0108/09/2024PLUMBING DEMO FLOOR PLAN - BLDG A & BP1.0908/09/2024PLUMBING DEMO ROOF PLAN - BLDG A & BP3.0108/09/2024P3.0908/09/2024PLUMBING ENLARGED PLANS - BLDG BP4.02PLUMBING DETAILS ELECTRICAL FIRST FLOOR PLAN - BLDG A & BE2.04MECHANICAL/POWER ROOF FLOOR PLAN - BLDG A & B08/09/2024 E5.02PV SYSTEM SINGLE LINE DIAGRAM08/09/2024
E5.0508/09/2024PANEL SCHEDULESPANEL SCHEDULESE6.02LIGHTING CONTROL DIAGRAMS AND DETAILS08/09/2024E6.03LIGHTING CONTROL DIAGRAMS AND DETAILS08/09/2024 ELECTRICAL DETAILSPV DETAILSE7.0408/09/2024LIGHTING DETAILSE7.0508/09/2024 SWIMMING POOL CONT.
E9.11EM EGRESS PHOTOMETRICS SITE08/09/2024
08/09/2024SP-0SWIMMING POOL AREA PLANSP-1SP-2SP-3SP-4SP-5SWIMMING POOL WATER POLO LAYOUTSP-6SP-7DETAILSDETAILS08/09/2024SP-8SP-9SP-10SP-11SP-12SP-13SP-14SP-15SP-16 SP-17SP-18SP-19SP-20MECHANICAL ROOMMR-108/09/2024MR-2MR-308/09/2024DETAILSMR-408/09/2024DETAILSMR-508/09/2024DETAILSMR-608/09/2024DETAILSMR-808/09/2024DETAILSMR-908/09/2024DETAILSMR-1008/09/2024DETAILSMR-1108/09/2024NOTES, FOUNDATION DETAILSMT108/09/2024
DETAILSDETAILS
SPORTS LIGHTING
DETAILSMR-708/09/2024
POLE DETAILSMS108/09/2024ATTACHMENT DETAILSMD108/09/2024ATTACHMENT DETAILSMD208/09/2024ATTACHMENT DETAILSMD308/09/2024 SHEET NUMBER010203040506070809101112131415161718192021222324252627282930313233343536373839404142434445474648495051525354555657585960616263646566676869717072737475767778798182838486858788899091 9394
A6.21OPENING TYPES08/09/2024
80 A9.21CEILING DETAILSA9.31CASEWORK DETAILS08/09/202408/09/2024
SHEET NUMBER
9596979899100101102103104
S1.13SITE DETAILS08/09/2024
S6.14TYPICAL DECK SUPPORTING DETAILS08/09/2024
S6.7408/09/2024S6.7308/09/2024S6.72TYPICAL LIGHT GAUGE METAL FRAMING DETAILS08/09/2024S6.7108/09/2024 106107108109110111112113114115116117118119120121122123124125126127128129130131132133134135136137138139140141 TYP. LIGHT GAUGE FRAMING SCH. AND ELEVATIONSTYPICAL LIGHT GAUGE METAL FRAMING DETAILSTYPICAL INTERIOR LIGHT GAUGE FRAMING DETAILS 142143144145146147148149150151153
M0.3308/09/2024MECHANICAL TITLE-24 FORMS
152154155156157158159160161162163164165166167
170171
P0.2208/09/2024PLUMBING T24 BUILDING AP0.2308/09/2024PLUMBING T24 BUILDING B 168169
172173174175176177178179180181182183
185186187188189190191192193194 SHEET LABEL
SHEET NUMBER
195196197
E9.12EM EGRESS PHOTOMETRICS BLD. A & B08/09/2024
198199201202200
SHEET INDEX
* A0.3108/09/2024
C3 EXISTING CONDITIONS
CIVIL
C4 DEMOLITION PLANC5C6C7 GRADING PLAN
C8C9 STORM DRAIN PLAN
C10C11C12
UTILITY PLAN
L0.01LANDSCAPE NOTES AND SCHEDULESLANDSCAPEL0.02L1.01MATERIALS PLAN L4.01SECTIONS AND ELEVATIONS
L5.01LANDSCAPE DETAILS
L7.01PLANTING PLANL7.02
08/09/2024
08/09/202408/09/202408/09/202408/09/2024
08/09/202408/09/202408/09/2024
08/09/202408/09/202408/09/202408/09/202408/09/202408/09/202408/09/202408/09/202408/09/202408/09/2024C2 CIVIL NOTES08/09/2024
HORIZONTAL CONTROL AND PAVING PLAN
SINGLE SHEET BMP PLAN
L4.02SECTIONS AND ELEVATIONS
08/09/2024
L4.03SECTIONS AND ELEVATIONS
08/09/2024
L5.02
08/09/2024
L5.03
08/09/2024
L5.04
08/09/2024
L5.05
08/09/2024L6.02
08/09/2024
L6.01IRRIGATION PLAN
08/09/2024L6.03
08/09/2024
IRRIGATION LEGEND AND NOTESL6.04
08/09/2024
IRRIGATION DETAILSL6.05IRRIGATION DETAILS
DETAILS
08/09/2024
DETAILS
08/09/202408/09/2024
L2.01LAYOUT PLAN
08/09/202408/09/2024
L3.01ENLARGEMENT PLAN
08/09/2024
08/09/202408/09/202408/09/2024
08/09/2024
***********
L4.04SECTIONS AND ELEVATIONS
C1 TITLE SHEET08/09/2024*
GRADING ENLARGEMENTS
08/09/2024
LANDSCAPE NOTES AND SCHEDULES
L5.06L5.07L5.08L5.09L5.10L5.11L5.12
LANDSCAPE DETAILSLANDSCAPE DETAILSLANDSCAPE DETAILSLANDSCAPE DETAILSLANDSCAPE DETAILSLANDSCAPE DETAILSLANDSCAPE DETAILSLANDSCAPE DETAILSLANDSCAPE DETAILSLANDSCAPE DETAILS
LANDSCAPE DETAILS
IRRIGATION DETAILS
PLANTING DETAILSL6.06IRRIGATION CALCULATIONS
******************************************************** 105
01020304050607080910111213
0102030405060708091011121314151617181920212223242526272829 TOTAL SHEETS: 203
* PER SEPARATE GRADING PERMIT
** PER SEPARATE LANDSCAPE PERMIT
92 G0.3108/09/2024TYPICAL ACCESSIBILITY NOTES AND DETAILS 184
203
08/09/2024
THESE PLANS AND SPECIFCATIONS DO NOT PROVIDE ANY DIRECTION
OR INSTRUCTIONS TO CONTRACTORS, SUBCONTRACTORS, MATERIAL
SUPPLIERS OR THEIR EMPLOYEES OR AGENTS RELATED TO
CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES OR
PROCEDURES, SAFETY PRECAUTIONS, MANNERS OR METHODS OF
EGRESS OR INGRESS, INCLUDING BUT NOT LIMITED TO JOB SITE
SAFETY, THE PHYSICAL CONDITION OF THE JOB SITE, THE MANNER OR
METHOD IN WHICH THE AREA WHERE WORK IS PERFORMED IS
ACCESSED BY WORKERS, AND SAFETY PROGRAMS OR SAFETY
PROTOCOLS OF ANY KIND IN CONNECTION WITH THE WORK. ALL OF
THE FOREGOING ARE SOLELY AND EXCLUSIVELY THE RESPONSIBILITY
OF THE CONTRACTOR, SUBCONTRACTOR, MATERIAL SUPPLIERS, OR ANY AGENTS OR EMPLOYEES THEREOF.
THE ARCHITECT EXPRESSLY DISCLAIMS ANY CONTROL OVER AND
RESPONSIBILITY FOR CONSTRUCTION MEANS, METHODS,
TECHNIQUES, SEQUENCES OR PROCEDURES, SAFETY PRECAUTIONS,
MANNERS OR METHODS OF EGRESS OR INGRESS, INCLUDING BUT
NOT LIMITED TO JOB SITE SAFETY, THE PHYSICAL CONDITION OF THE
JOB SITE, THE MANNER OR METHOD IN WHICH THE AREA WHERE
WORK IS PERFORMED IS ACCESSED BY WORKERS, AND SAFETY
PROGRAMS OR SAFETY PROTOCOLS OF ANY KIND IN CONNECTION WITH THE WORK.
THE ARCHITECT HAS NOT CONDUCTED AN EVALUATION OR ANALYSIS
OF SAFETY PROCEDURES OR APPLICABLE LAW REGARDING OR
RELATING TO ACCESSING THE JOB SITE OR AREAS OF THE WORK DURING THE COURSE OF CONSTRUCTION.
THE ARCHITECT, THE ARCHITECT ’S DESIGNS, AND ANY OTHER WORK
PERFORMED BY THE ARCHITECT DO NOT ADDRESS, ANALYZE OR
PROVIDE ANY DIRECTION OR ADVICE TO ANY PERSON OR ENTITY ON
WHETHER OR NOT THE USE OF EXISTING LADDERS, DOORS, RAILINGS,
INGRESS AND INGRESS ROUTES OR THE LIKE ARE IN COMPLIANCE OR
NON -COMPLIANCE WITH OSHA, CAL -OSHA(CALIFORNIA ONLY), OR ANY
OTHER APPLICABLE STATUTE, REGULATION, OR STANDARD RELATED
TO JOB SITE SAFETY DURING THE COURSE OF CONSTRUCTION OF THE IMPROVEMENTS.
NOTICE TO PERSONS PERFORMING WORK ON JOB
SITE, INCLUDING CONTRACTORS, SUBCONTRACTORS,
MATERIAL SUPPLIERS AND ANY AGENTS OR
EMPLOYEES THEREOF
RESPONSIBILTY FOR JOB SITE SAFETY
1. ALL CONSTRUCTION & MATERIALS SHALL BE AS SPECIFIED & IN ACCORDANCE
WITH ALL APPLICABLE CODES, ORDINANCES, LAWS, PERMITS & THE CONTRACT DOCUMENTS.
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE ACCURATE PLACEMENT OF ALL NEW CONSTRUCTION ON THE SITE.
3. THE CONTRACTOR IS RESPONSIBLE FOR ALL EXG SURVEY MONUMENTS WHICH
MAY BE DISTURBED THROUGH CONSTRUCTION ACTIVITIES DEEMED NECESSARY FOR PRESERVATION BY THE CIVIL ENGINEER. IF SUCH
MONUMENTS WERE DISTURBED, THE APPLICANT SHALL HAVE A LICENSED
LAND SURVEYOR QUALIFIED CIVIL ENGINEER REESTABLISH ANY SUCH
MONUMENTATION DAMAGED OR DESTROYED DURING THE CONSTRUCTION OF THE PROJECT & SUBMIT "PRELIMINARY CORNER RECORDS" TO THE CIVIL ENGINEER AFTER REPLACEMENT. AFTER APPROVAL BY THE CIVIL ENGINEER,
THE APPLICANT SHALL FILE THE CORNER RECORDS WITH THE COUNTY SURVEYOR. PRIOR TO THE EXONERATION OF ANY SECURITY, EVIDENCE OF SUCH FILING SHALL BE FURNISHED TO THE CIVIL ENGINEER.
4. THE CONTRACTOR IS RESPONSIBLE TO INSURE THAT TRUCK ROUTES SHALL BE STEERED AWAY FROM RESIDENTIAL AREAS.
5. THE CONTRACTOR SHALL ENSURE THAT TRUCKS HAULING DIRT ON PUBLIC ROADS TO & FROM THE SITE SHALL BE COVERED OR WILL MAINTAIN A 6"
DIFFERENTIAL BETWEEN THE MAX HGT OF ANY HAULED MATERIAL & THE TOP OF THE HAUL TRAILER. HAUL TRUCK DRIVERS SHALL WATER THE LOAD PRIOR TO LEAVING THE SITE TO PREVENT SOIL LOSS DURING TRANSPORT.
6. THE CONTRACTOR SHALL ENSURE THAT GRADED SURFACES USED FOR OFF
ROAD PARKING, MATERIALS LAY -DOWN, OR AWAITING FUTURE CONSTRUCTION SHALL BE STABILIZED FOR DUST CONTROL AS NEEDED. FREQUENTLY
ACCESSED UNPAVED AREAS SHALL BE PAVED AS EARLY AS POSSIBLE TO MINIMIZE DIRT TRACKOUT TO PUBLIC RIGHTS -OF -WAY.
7. THE CONSTRACTOR SHALL COORDINATE ANY LANE CLOSURES OR DETOURS WITH THE CITY/COUNTY. FLAG PERSONS & APPROPRIATE TRAFFIC CONTROL
DEVICES SHALL BE USED AS NEEDED TO MINIMIZE CONSTRUCTION ACTIVITY INTERFERENCE WITH OFF -SITE -TRAFFIC.
8. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS & SITE CONDITIONS BEFORE STARTING WORK. SHOULD A DISCREPANCY APPEAR IN THE CONTRACT
DOCUMENTS OR BETWEEN THE CONTRACT DOCUMENTS & EXISTING
CONDITIONS, NOTIFY THE ARCHITECT AT ONCE FOR INSTRUCTION ON HOW TO PROCEED.
9. SHOULD A CONFLICT OCCUR BETWEEN DWGS & SPECIFICATIONS, THE MORE
COSTLY CONDITION SHALL TAKE PRECEDENCE, UNLESS A WRITTEN DECISION
FROM THE ARCHITECT HAS BEEN OBTAINED WHICH DESCRIBES A
CLARIFICATION OR ALTERNATE METHOD AND/OR MATERIALS.
10. THE CONTRACTOR SHALL CONFINE HIS OPERATION ON THE SITE TO AREAS PERMITTED BY OWNER.
11. THE JOBSITE SHALL BE MAINTAINED IN A CLEAN, ORDERLY CONDITION FREE OF
DEBRIS & LITTER & SHALL NOT BE UNREASONABLY ENCUMBERED WITH ANY MATERIALS OR EQUIPMENT. EACH SUBCONTRACTOR IMMEDIATELY UPON
COMPLETION OF EACH PHASE OF HIS WORK SHALL REMOVE ALL TRASH & DEBRIS AS A RESULT OF HIS OPERATION.
12. ALL MATERIAL STORED ON THE SITE SHALL BE PROPERLY STACKED & PROTECTED TO PREVENT DAMAGE & DETERIORATION. FAILURE TO PROTECT MATERIALS MAY BE CAUSE FOR REJECTION OF WORK.
13. THE CONTRACTOR SHALL DO ALL CUTTING, FITTING, AND/OR PATCHING OF HIS
WORK THAT MAY BE REQ TO MAKE ITS SEVERAL PARTS FIT TOGETHER
PROPERLY & SHALL NOT ENDANGER ANY OTHER WORK BY CUTTING, EXCAVATING, OR OTHERWISE ALTERING THE TOTAL WORK OR ANY PART OF IT.
ALL PATCHING, REPAIRING AND REPLACING OF MATERIALS AND SURFACES,
CUT OR DAMAGED IN EXECUTION OF WORK, SHALL BE DONE WITH APPLICABLE
MATERIALS SO THAT SURFACES REPLACED WILL, UPON COMPLETION, MATCH SURROUNDING SIMILAR SURFACES.
14. STRUCTURAL OBSERVATION WILL BE PERFORMED BY THE STRUCTURAL ENGINEER. WHEN REQ, A STATEMENT IN WRITING SHALL BE GIVEN TO THE
BUILDING OFFICIAL, STATING THAT THE SITE VISITS HAVE BEEN MADE &
WHETHER OR NOT ANY OBSERVED DEFICIENCIES HAVE BEEN CORRECTED TO CONFORM TO THE APPROVED PLANS & SPECIFICATIONS.
15. SUBMITTAL DOCUMENTS FOR DEFERRED SUBMITAL ITEMS SHALL BE
SUBMITTED TO THE ARCHITECT OR ENGINEER OF RECORD, WHO SHALL
REVIEW THEM & RETURN THEM TO THE CONTRACTOR (WITH A NOTIFICATION
INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
REVIEWED & THAT THEY HAVE BEEN FOUND TO BE IN GENERAL
CONFORMANCE WITH THE DESIGN OF THE BUILDING) FOR PLAN CHECK APPROVAL. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL
THEIR DESIGN & SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE AUTHORITY HAVING JURISDICTION.
16. PROVIDE ALL ACCESS PANELS AS REQ BY GOVERNING CODES TO ALL CONCEALED SPACES, VOIDS, ATTICS, ETC. VERIFY TYPE REQ WITH ARCHITECT PRIOR TO INSTALLATION.
17. NO PORTION OF WORK REQ A SHOP DWG OR SAMPLE SUBMISSION SHALL BE COMMENCED UNTIL THE SUBMISSION HAS BEEN REVIEWED BY THE ARCHITECT.
ALL SUCH PORTIONS OF THE WORK SHALL BE IN ACCORDANCE WITH CORRECTED SHOP DWGS. AND SAMPLES.
18. DIMENSIONS:
A. ALL DIMS SHALL TAKE PRECEDENCE OVER SCALE.
B. ALL DIMS ARE TO FACE OF STUD / CONCRETE / MASONRY UNO C. CLG HGT DIMS ARE FROM FACE OF SLAB TO FACE OF FIN CLG MATERIAL UNO
19. DO NOT SCALE DRAWINGS
20. PROVIDE ALL NECESSARY BLOCKING, BACKING, & FRAMING FOR LIGHT
FIXTURES, ELECTRIC UNITS, AC EQUIP, RECESSED ITEMS, AND ALL OTHER ITEMS AS REQ.
21. WHERE LARGER STUDS OR FURRING ARE REQ TO COVER PIPING AND
CONDUITS, THE LARGER STUD SIZE OR FURRING SHALL EXTEND THE FULL
SURFACE OF THE WALL WIDTH AND LENGTH WHERE THE FURRING OCCURS, UNO.
22. ALL DOORS SHALL BE OPERABLE FROM THE INSIDE W/O THE USE OF A KEY OR SPECIAL KNOWLEDGE OF EFFORT. EXIT SIGNS SHALL BE PROVIDED AT ALL EXITS AS REQ BY THE APPLICABLE CODES. ALL DOOR SWINGS SERVING AN OCCUPANT LOAD OF 50 OR GREATER SHALL SWING IN THE DIRECTION OF TRAVEL.
23. ALL GLASS AND GLAZING SHALL COMPLY WITH THE APPLICABLE CODES.
24. WALL AND CLG MATERIALS SHALL NOT EXCEED THE FLAME SPREAD CLASSIFICATIONS IN THE APPLICABLE CODES.
25. SURVEYORS CERTIFICATE REQ PRIOR TO FINAL COMPLETION.
26. THE CONTRACTOR SHALL COMPLY WITH THE APPLICABLE CODES FOR FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION.
27. A DSA CERTIFIED CLASS 1 PROJECT INSPECTOR EMPLOYED BY THE DISTRICT (OWNER) AND APPROVED BY THE DIVISION OF THE STATE ARCHITECT (DSA) SHALL PROVIDE CONTINUOUS INSPECTION OF THE WORK. THE DUTIES OF THE INSPECTOR ARE DEFINED IN SECTION 4 -342, CALIFORNIA BUILDING STANDARDS ADMINISTRAIVE CODE (PART 1, TITLE 24, CCR)
28. A DSA ACCEPTED TESTING LABORATORY DIRECTLY EMPLOYED BY THE
DISTRICT (OWNER) SHALL CONDUCT ALL THE REQ TESTS AND INSPECTIONS FOR THE PROJECT.
29. CHANGE TO THE APPROVED DWGS AND SPECIFICATIONS SHALL BE MADE BY
ADDENDA OR CONSTRUCTION CHANGE DOCUMENT (CCD) APPROVED BY DSA, AS REQ BY SECTION 4 -338, PART 1, TITLE 24, CCR.
30. THE INTENT OF THESE DWGS AND SPECIFICATIONS IS THAT THE WORK OF THE
ALTERATION, REHABILITATION OR RECONSTRUCTION IS TO BE IN ACCORDANCE WITH TITLE 24, CCR. SHOULD ANY EXG CONDITIONS SUCH AS
DETERIORATION OR NON -COMPLYING CONSTRUCTION BE DISCOVERED
WHICH IS NOT COVERED BY THE CONTRACT DOCUMENTS WHEREIN THE FINISHED WORK WILL NOT COMPLY WITH TITLE 24, CCR, A CONSTRUCTION
CHANGE DOCUMENT (CCD), OR A SEPARATE SET OF PLANS AND
SPECIFICATIONS, DETAILING AND SPECIFYING THE REQ WORK SHALL BE
SUBMITTED TO AND APPROVED BY DSA BEFORE PROCEEDING WITH THE WORK. (SECTION 4 -317(c), PART 1, TITLE 24, CCR)
1. PLANS FOR THE FIRE SPRINKLER SYSTEMS MUST BE APPROVED BY THE AUTHORITY HAVING JURISDICTION (AHJ) PRIOR TO INSTALLATION. SUBMIT
PLANS IN A MANNER WHICH WILL NOT IMPEDE THE PROGRESS OF CONSTRUCTION.
2. FIRE SPRINKLER SYSTEMS & INSTALLATION SHALL CONFORM W/ THE APPLICABLE STANDARDS AND CODES.
3. FIRE SPRINKLER SYSTEMS TO BE TIED INTO THE ALARM SYSTEM PER THE APPLICABLE CODES.
4. AUTOMATIC SPRINKLER SYSTEM(S) SHALL BE SUPERVISED BY AN APPROVED
CENTRAL OR REMOTE STATION SERVICE, AND/OR SHALL BE PROVIDED W/ A LOCAL ALARM WHICH WILL GIVE AN AUDIBLE SIGNAL.
5. FIRE SPRINKLER SYSTEM(S) & ALL CONTROL VALVES SHALL BE SUPERVISED BY A U.L. LISTED CENTRAL ALARM STATION OR PER THE APPLICABLE CODES.
6. FIRE HYDRANT & FIRE SPRINKLER SYSTEM(S) SHALL BE FLUSHED
THOROUGHLY BEFORE CONNECTION IS MADE TO EXISTING SYSTEM STUBOUTS & WITNESSED BY THE PROJECT INSPECTOR.
7. A HYDROSTATIC TEST (200 PSI PRESSURE FOR 2 HRS. OR @ 50 PSI IN EXCESS OF THE MIN. STATIC PRESSURE WHEN IT IS IN EXCESS OF 150 PSI) SHALL BE
WITNESSED BY THE PROJECT INSPECTOR PRIOR TO COVERING PIPING JOINTS.
8. A 3' CLR SPACE SHALL BE MAINTAINED AROUND THE CIRCUMFERENCE OF FIRE
HYDRANTS EXCEPT AS OTHERWISE REQ OR APPROVED PER THE APPLICABLE CODES.
9. THRUST BLOCKS SHALL BE PROVIDED WHEREVER PIPE CHANGES DIRECTION.
10. ALL PIPE SHALL BE UL LISTED FOR FIRE SERVICE SYSTEMS, CLASS 200 MIN.
11. FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED W/I 100' FROM A PUBLIC FIRE HYDRANT PER THE APPLICABLE STANDARDS AND CODES.
12. FIRE SPRINKLER RISER SHALL BE LOCATED WITHIN 5 FT OF THE EXT WALL (OR AS REQ BY THE AHJ) AND TERMINATE 6" ABV FF
13. AN ALL -WEATHER FIRE ACCESS ROAD SHALL BE IN PLACE BEFORE ANY COMBUSTIBLE MATERIALS ARE PLACED ON THE SITE OR AS REQ BY THE AHJ.
14. STORAGE, DISPENSING, OR USE OF ANY FLAMMABLE & COMBUSTIBLE LIQUIDS,
FLAMMABLE & COMPRESSED GASES & OTHER HAZARDOUS MATERIALS SHALL COMPLY W/ THE APPLICABLE CODES.
15. EXIT SIGNS SHALL BE POSTED OVER EXIT DOORS & DIRECTIONAL EXIT SIGNS SHALL BE LOCATED TO DIRECT PERSONS TOWARD EXIT DOORS.
16. EXIT SIGNS SHALL BE SELF -LUMINOUS TYPE OR ELECTRONICALLY
ILLUMINATED & ENERGIZED FROM SEPARATE CIRCUITS, ONE OF WHICH SHALL
BE FROM STORAGE BATTERIES OR AN ON -SITE GENERATOR, FOR A DURATION OF 90 MINUTES PER THE APPLICABLE CODES.
17. EXIT DOORS SHALL BE OPENABLE FROM THE INSIDE WITHOUT THE USE OF A KEY OR ANY SPECIAL KNOWLEDGE OR EFFORT.
18. ACCESS GATE(S) SHALL BE OPENABLE W/ FIRE DEPT MASTER KEY FROM THE EXTERIOR.
19. CURBS ALONG FIRE LANES SHALL BE PAINTED SAFETY RED & MARKED "FIRE LANE NO PARKING" W/ 3" WHITE LETTERS ON THE TOP OF CURBING EVERY 30' AS INDICATED ON THE APPROVED DRAWINGS.
20. APPROVED NUMBERS OR ADDRESSES SHALL BE PROVIDED FOR ALL NEW &
EXG BLDGS IN SUCH A POSITION AS TO BE PLAINLY VISIBLE & LEGIBLE FROM
THE STREET OR ROAD FRONTING THE PROPERTY PER THE APPLICABLE CODES.
21. PROVIDE PERMANENT OR TEMPORARY STANDPIPES WHILE BUILDING IS UNDER CONSTRUCTION PER THE APPLICABLE CODES.
22. PROVIDE FIRE EXTINGUISHERS PER THE REQ THE APPLICABLE STANDARDS AND CODES.
11B-201.4 CONSTRUCTION SUPPORT FACILITIES. These requirements shall apply to temporary or permanent construction support facilities for uses and activities not directly associated with the actual processes of construction, including but not limited to offices, meeting rooms, plan rooms, other administrative or support functions. When provided, toilet and bathing facilities serving construction support facilities shall comply with 11B-213. When toilet and bathing facilities serving construction support facilities are provided by portable units, at least one of each type shall be accessible and connected to the construction support facilities it serves by an accessible route.
EXCEPTION: During construction an accessible route shall not be required between site arrival points or the boundary of the area of construction and the entrance to the construction support facilities if the only means of access between them is a vehicular way not providing pedestrian access.
ACCESSIBLE CONSTRUCTION SUPPORT FACILITIES
TEL: 422.339.2941
DIRECTOR OF FACILITY
NAME: CITY OF CARLSBAD
CLIENT INFORMATION
CITY,STATE, ZIP: CARLSBAD, CA 92008
ADDRESS: 1200 CARLSBAD VILLAGE DRIVE
CONTACT: KYLE LANCASTER E-MAIL: [email protected] TEL: 619/795-2555
NAME: LPA, INC.
ARCHITECT
CONTACT: MICHAEL DAVIS E-MAIL: mdavis@lpadesignstud ios.com TEL: 916.287.2336
NAME: LPA, INC.
LANDSCAPE ARCHITECT
CONTACT: RITA FRINK E-MAIL: rfrink@lpadesignstudios. com TEL: 949.769.6265
NAME: LPA, INC.
CIVIL ENGINEER
CITY,STATE, ZIP: IRVINE, CA 92617
ADDRESS: 5301 CALIFORNIA AVE, SUITE 100
CONTACT: ROBERT RICHARDSON
E-MAIL:
[email protected] TEL: 619.280.4321
NAME: ATLAS TECHNICAL CONSULTANTS LLC
GEOTECHNICAL ENGINEER
CITY,STATE, ZIP: SAN DIEGO, CA 92120
ADDRESS: 6280 RIVERDALE STREET
CONTACT: ERICK ALDRICH E-MAIL: erick.aldrich@oneatl as.com TEL: 619/795-2555
NAME: LPA, INC.
STRUCTURAL ENGINEER
CITY,STATE, ZIP: SAN DIEGO, CA 92106
ADDRESS: 2765 TRUXTUN RD
CONTACT: HARSHDA PRASAD E-MAIL: hprasad@lpadesignst udios.com TEL: 949.701.4228
NAME: LPA, INC.
MECHANICAL ENGINEER
CITY,STATE, ZIP: IRVINE, CA 92617
ADDRESS: 5301 CALIFORNIA AVE, SUITE 100
CONTACT: ERICK PULIDO E-MAIL: epulido@lpadesignstud ios.com TEL: 949.701.4272
NAME: LPA, INC.
ELECTRICAL ENGINEER
CITY,STATE, ZIP: IRVINE, CA 92617
ADDRESS: 5301 CALIFORNIA AVE, SUITE 100
CONTACT: OSCAR CHAVEZ E-MAIL: ochavez@lpadesignstud ios.com TEL: 949.701.4172
NAME: LPA, INC.
PLUMBING ENGINEER
CITY,STATE, ZIP: IRVINE, CA 92617
ADDRESS: 5301 CALIFORNIA AVE, SUITE 100
CONTACT: ERIK RING E-MAIL: [email protected] om TEL: ###-###-####
NAME: TK1SC
FIRE ALARM
CITY,STATE, ZIP: IRVINE, CA 92618
ADDRESS: 15231 LAGUNA CANYON ROAD, SUITE 100
CONTACT: ROBINSON NGUYEN E-MAIL: robinson.nguyen@ws p.com CITY,STATE, ZIP: SAN DIEGO, CA 92106
ADDRESS: 2765 TRUXTUN RD
CITY,STATE, ZIP: SAN DIEGO, CA 92106
ADDRESS: 2765 TRUXTUN RD
TEL: 949-751-5819
NAME: TK1SC
AUDIO VISUAL
CITY,STATE, ZIP: IRVINE, CA 92618
ADDRESS: 15231 LAGUNA CANYON ROAD, SUITE 100
CONTACT: DAVID BROWN E-MAIL: [email protected]
TEL: 949-751-5819
NAME: TK1SC
TECHNOLOGY
CITY,STATE, ZIP: IRVINE, CA 92618
ADDRESS: 15231 LAGUNA CANYON ROAD, SUITE 100
CONTACT: RICHARD BRYSACZ E-MAIL: [email protected] om N
PROJECT NORTH
SITE
ADDRESS:
3401 Monroe St, Carlsbad, CA
92008
N
TRUE NORTH
1. THE SCOPE OF THE PROJECT INCLIDES THE FOLLOWING:
- DEMO OF EXISTING POOL, POOL DECK, POOL PUMP BUILDING AND INTERIOR OF EXISTING
POOL FACILITIES BUILDING ( EXISTING RESTROOMS, CHANGING ROOMS, LOBBY, OFFICE ETC) - NEW POOL WITH ASSOCIATED INFRASTRUCTUE, POOL PUMP BUILDING NEW INTERIOR WALLS
AND FINISHES OF EXISTING BUILDING
- NEW DETACHED ADDITION TO EXISTING BUILDING
- NEW PV SOLAR SYSTEM FOR BUILDING
- NEW SOLAR THERMAL SYSTEM FOR POOL HEATING
LIST OF APPLICABLE CODES
2022 CALIFORNIA ADMINISTRATIVE CODE (CAC), PART 1, TITLE 24 CCR 2022 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 CCR 2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 CCR 2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 CCR 2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 CCR 2022 CALIFORNIA ENERGY CODE, PART 6, TITLE 24 CCR
2022 CALIFORNIA FIRE CODE (CFC), PART 9, TITLE 24 CCR
2022 CALIFORNIA EXISTING BUILDING CODE (CEBC), PART 10, TITLE 2 4 CCR 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN), PART 11, TITLE 24 CCR
2022 CALIFORNIA REFERENCED STANDARDS CODE, PART 12, TITLE 24 CC R TITLE 19 CCR, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS
APPLICABLE STANDARDS
FOR A LIST OF APPLICABLE STANDARDS, INCLUDING CALIFORNIA AMENDME NTS TO THE NFPA STANDARDS, REFER TO CBC CHAPTER 35 AND CFC CHAPTER 8 0.
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
GENERAL PROJECT
INFORMATION
G0.20
MD
MONROE ST. POOL REPLACEMENT
GENERAL PROJECT INFORMATION
CONSTRUCTION NOTES
FIRE AND LIFE SAFETY NOTES
ACCESSIBILITY NOTES PROJECT DIRECTORY
VICINITY MAP
PROJECT SCOPE
LIMIT OF WORK
THE INTENT OF THE LIMIT OF WORK LINE IS TO DESCRIBE IN GENERAL THE AREAS AFFECTED BY PROJECT CONSTRUCTION. IT IS NOT INTENDED TO BE AN EXACT INDICATION OR EDGE OF THE CONSTRUCTION AREA. THE CONTRACTOR SHOULD
VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING CONDITIONS AND THEIR RELATIONSHIP TO THE WORK PROPOSED IN THE CONTRACT DOCUMENTS. ALL
ITEMS NECESSARY FOR THE PROPER EXECUTION AND COMPLETION OF THE WORK SHALL BE INCLUDED. THE CONTRACT DOCUMENTS ARE COMPLEMENTARY
AND WHAT IS REQUIRED BY ONE SHALL BE BINDING AS IF REQUIRED BY ALL TO
THE EXTENT THAT IT IS REASONABLY INFERABLE FROM THEM AS BEING NECESSARY TO PRODUCE THE INTENDED RESULTS.
DEFERRED APPROVALS
ADDITIVE ALTERNATES
APPLICABLE CODES
1. (N) STUCCO FINISH ON ALL EXTERIOR WALLS AT (E) "BUILDING A", PENDING
SELECTIVE DEMO AND REVIEW OF EXISTING CONDITION OF CMU BLOCK BY CLIENT AND ARCHITECT.
1. FIRE ALARM
2. SHADE CANOPY ENGINEERING
3. MECHANICAL ROOF SCREEN ENGINEERS
203
3 08/09/2024
TO REFLECTIVE SURFACE
LAVATORY GRAB BAR MIRROR
FEMININE
NAPKIN
VENDING
MACHINE
SEAT
COVER
DISPENSER URINAL
HAND
DRYER
BABY
CHANGING
STATION
33" MIN
36" MAX
40" MAX ABOVE LAVATORIES
44" MAX
40" MAX
34" MAX
KNEE CLEARANCE
29" MIN
KNEE CLEARANCE
27" MIN
NOTE: ALL KNEE & TOE AREAS ARE TO BE CLEAR
COUNTERTOP / TOP OF LAVATORY
ALL EXPOSED PIPES TO BE
INSULATED TO PROTECT AGAINST
CONTACT. NO SHARP OR ABRASIVE
SURFACES UNDER LAVATORIES
6" MAX
KNEE CLEARANCE AT 9"
25" MAX
8"MIN KNEE CLEARANCE
9" MIN
WASTE
TOWEL
17" MAX
13 1/2" MIN
REFER TO: CBC 11B306.2, CBC 11B306.2.2, CBC 11B306.3, CBC 11B-603.3, CBC 11B603.5, CBC 11B-605.2, CBC 11B-606, & CBC 11B609.4 11" MIN
27" MAX
25" MAX
17" MIN TOE CLEARANCE
1 / 4 "
1 / 4 "
1 / 2 "
1/4" MAX
1 2
REFER TO: 11B-303.3
REFER TO: 11B-303.2
60" MIN
59" FLOOR M
TD W
C
56" M
IN W
ALL M
TD W
C
CLEARANCE
6" MIN
PLAN
NOTES:
1. TOE CLEARANCE AT THE SIDE PARTITION IS NOT REQ I N A COMPARTMENT > 66" WIDE
2. REFER TO: CBC 11B-604.8.1.4 & CBC 11B-604.8.1.1. 3
ELEVATION CHILDREN (K-12) ELEVATION ADULT
12" M
IN
6" MIN
9" M
IN
6" MIN
TOILET
PARTITION
TOILET
PARTITION
17"-18"
42" MIN 12" MAX
56" MIN
48" MIN CLR
60" M
IN CLR
12" M
IN
24" M
IN
30" M
IN CLR
48" MIN CLR
REFER TO: CBC 11B-604.3.1,
CBC 11B-604.5.1, & CBC
11B-606.2
18" M
IN
DOOR PERMITTED
TO SWING OVER
HATCHED
PORTION OF
MANEUVERING
SPACE
REFER TO: CBC 11B-305.7.1
30 x 48
CLR
≤ 24"
30 x 48
CLR
> 24"
36" MIN
TOILET TISSUE
DISPENSER
3" MAX PROJECTION
WATER CLOSET (SIDE) WATER CLOSET (FRONT)
CENTERLINE OF WATER
CLOSET TO FACE OF FINISH
FLUSH VALVE TO
WIDE SIDE OF
SPACE
SANITARY NAPKIN
DISPENSER
3" MAX PROJECTION
54" MIN
42" MIN 12" MAX
33" M
IN 36" M
AX
M
IN
19"
M
IN
1-1/2"
24" MIN
7"-9"
36" MIN
12" MIN
ACCESSIBLE WATER CLOSET
17" - 18" AT WHEELCHAIR
24" MIN
TOP OF GRAB BAR
36" M
AX
REFER TO: CBC 11B-604.1/2/7
17" - 19" TOP OF SEAT
X>27"
4"MAX
X> 80"
REFER TO: 11B-307.2
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
TYPICAL
ACCESSIBILITY
NOTES AND
DETAILS
G0.31
MD
MONROE ST. POOL REPLACEMENT
TYPICAL ACCESSIBILITY NOTES AND DETAILS
1/2" = 1' -0"
G0.31 01 ACCESSIBLE MOUNTING HEIGHTS
6" = 1' -0"
G0.31 10 CHANGES IN LEVEL
3/8" = 1' -0"
G0.31 02 WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT TOE CLEARANCE 1/2" = 1' -0"
G0.31 06 ACCESSIBLE FIXTURES AT
SINGLE OCC. RESTROOM
3/8" = 1' -0"
G0.31 03 ACCESSIBLE URINAL PARTITIONS
1/2" = 1' -0"
G0.31 11 ACCESSIBLE MOUNTING HEIGHTS
3/8" = 1' -0"
G0.31 09 ACCESSIBLE PATH OF TRAVEL
PROTRUDING OBJECT LIMITS
4 203
08/09/2024
38" MIN - 43" MAX
36" MAX
27" MIN
14"
16" MIN 16" 16" MIN
48" MIN
(80" MIN CLR)
SEE RCP
DRINKING
FOUNTAIN
ELEVATION
18" MIN
19" MAX
18" MIN
16" MIN 16" 16" MIN
32" MIN AT SINGLE ACCESSIBLE DF
REFER TO FLOOR PLAN
PLAN
NOTES:
1. DRINKING FOUNTAIN SHALL BE ACCESSIBLE.
2. DRINKING FOUNTAINS SHALL BE LOCATED COMPLETELY W ITHIN ALCOVES OR
OTHERWISE POSITIONED SO AS NOT TO ENCROACH INTO PEDESTRIAN WAYS. THE ALCOVE IN WHICH THE WATER FOUNTAIN IS LOCATED SHALL NOT BE LESS THAN 32" WIDE AND 18" DEEP.
3. DRINKING FOUNTAIN SHALL BE A MIN OF 18" AND A MA X OF 19" DEEP AND
THERE SHALL BE A CLEAR AND UNOBSTRUCTED KNEE SPACE UNDER THE DRINKING FOUNTAIN NOT LESS THAN 27" HIGH, 30" WIDE AND 8" DEEP, THE
DEPTH MEASUREMENT BEING TAKEN FROM THE FRONT EDGE OF THE FOUNTAIN.
4. THERE SHALL BE TOE CLEARANCE OF 9" ABOVE THE FLO OR, AND 17" DEEP FROM THE FRONT EDGE OF THE FOUNTAIN.
5. A CLEAR FLOOR SPACE AT LEAST 30" X 48" SHALL BE PROVIDED IN FRONT OF THE DRINKING FOUNTAIN TO ALLOW FORWARD APPROACH.
6. THE DRINKING FOUNTAIN BUBBLER SHALL BE ACTIVATED BY A MANUALLY
OPERATED SYSTEM THAT IS FRONT MOUNTED OR SIDE MOUNTED AND LOCATED WITHIN 6" OF THE FRONT EDGE OF THE FOUNTAIN OR AN ELECTRONICALLY CONTROLLED DEVICE.
7. THE BUBBLER OUTLET ORIFICE SHALL BE LOCATED WITH IN 5" OF THE FRONT OF THE DRINKING FOUNTAIN AND SHALL BE WITHIN 36" OF THE FLOOR. THE
WATER STREAM FROM THE BUBBLER SHALL BE SUBSTANTIALLY PARALLEL TO THE FRONT EDGE OF THE DRINKING FOUNTAIN.
5" MAX
15" MIN
30"
48"
8" MIN
19" MAX.
1 8 "
16" 16" 16"
PLAN - GUARDRAIL WHERE NOTED
5" MAX
15" MIN
30"
4 8 "
1 2 " 6"
32" MIN AT SINGLE ACCESSIBLE DF
REFER TO FLOOR PLAN
GUARDRAIL, TYP
BARRIER NEEDS
TO PROJECT ST
LEAST AS FAR AS
THE DRINKING
FOUNTAIN
REFER TO: CBC 11B-306.3, CBC 11B-602, & CBC 11B-602.9
6" MAX
6" MAX
5" MAX
18"-19"
18" MIN
27" MIN
36" MAX
32" MIN CLR
48" MIN 48" MIN
48" MIN
(A) (B)
(C)
REFER TO: CBC 11B-404.2.6
NOTES:
1. ALIGN CENTER OF ALL WALL SWITCHES & WALL DEVICES @ CENTERLINES UNO
2. REFER TO: CBC 11B-308
J-BOX FOR CLOCK
WALL SWITCHES,
ELEC DEVICES &
THERMOSTAT
WHERE OCCURS;
PROVIDE BRIDGING
FRAME REQ
ELEC OUTLET
WHERE OCCURS
15" AFF UNO
48" AFF MAX
27" MAX
X < 80"
REFER TO: CBC 11B-307.4
GUARDRAIL OR
OTHER BARRIER
60" MIN SIDE OF EXT DOOR
18" MIN AT INT
24" MIN ON EXT
X > 8 "
(A) PULL SIDE (B) PUSH SIDE
48" MIN
X > 8 "
(C) PUSH SIDE, DOOR
PROVIDED WITH
BOTH CLOSER AND
LATCH
48" MIN
X > 8 "
12" MIN
REFER TO: CBC 11B-404.2.4.3
15" MIN
48" MAX 48" MAX
UNOBSTRUCTED
FORWARD REACH
OBSTRUCTED HIGH
FORWARD REACH
OBSTRUCTED HIGH
FORWARD REACH
20" MAX
44" MAX
>20"-25" MAX
REFER TO: CBC 11B-308.2.1 & CBC 11B-308.2.2
15" MIN
48" MAX
34" MAX
48" MAX
UNOBSTRUCTED SIDE REACH
OBSTRUCTED HIGH SIDE REACH OBSTRUCTED HIGH SIDE REACH
46" MAX
10" MAX
10" MAX >10"-24" MAX
34" MAX
REFER TO: CBC 11B-306.3.1 & CBC 11B-308.3.2
60" MIN 18" MIN
48" MIN
12" MIN
48" MIN
36" MIN
60" MIN 44" MIN 22" MIN
48" MIN
22" MIN
60" MIN 24" MIN
44" MIN 24" MIN
48" MIN 24" MIN
(A)
FRONT APPROACH, PULL SIDE
(C)
FRONT APPROACH, PUSH SIDE, DOOR
PROVIDED WITH BOTH CLOSER AND LATCH
(B)
FRONT APPROACH, PUSH SIDE
(D)
HINGE APPROACH, PULL SIDE
(G)
HINGE APPROACH, PUSH SIDE, DOOR
PROVIDED WITH BOTH CLOSER AND LATCH
(F)
HINGE APPROACH, PUSH SIDE
(H)
LATCH APPROACH, PULL SIDE
(J)
LATCH APPROACH, PUSH SIDE
(K)
LATCH APPROACH, PUSH SIDE, DOOR
PROVIDED WITH CLOSER
ADD 6 INCHES AT
EXT SIDE OF EXT
DOOR
REFER TO: CBC 11B-404.2.4.1
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
TYPICAL
ACCESSIBILITY
NOTES AND
DETAILS
G0.32
MD
MONROE ST. POOL REPLACEMENT
TYPICAL ACCESSIBILITY NOTES AND DETAILS
1/2" = 1' -0"
G0.32 17 DRINKING FOUNTAIN ALCOVE
3/8" = 1' -0"
G0.32 05 DOOR CLEARANCES - DOORS IN SERIES
1/2" = 1' -0"
G0.32 10 TYPICAL DEVICE INSTALLATION
3/8" = 1' -0"
G0.32 08 VERTICAL CLEARANCE
3/8" = 1' -0"
G0.32 03 RECESSED DOOR CLEARANCES
3/8" = 1' -0"
G0.32 02 ACCESSIBLE FORWARD REACH
REQUIREMENTS
3/8" = 1' -0"
G0.32 04 ACCESSIBLE SIDE REACH
REQUIREMENTS
3/8" = 1' -0"
G0.32 11 DOOR CLEARANCES
5 207
203
08/09/2024
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
CALGREEN (CA)
G0.40
MD
MONROE ST. POOL REPLACEMENT
CALGREEN (CA)
X
X
X
X
X
X
X
6 203
2 08/09/2024
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
CALGREEN (CA)
G0.41
MD
MONROE ST. POOL REPLACEMENT
CALGREEN (CA)
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
7 203
08/09/2024
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
CALGREEN (CA)
G0.42
MD
MONROE ST. POOL REPLACEMENT
CALGREEN (CA)
X
X
X
X
X
X
X
X
X
8 203
08/09/2024
COMPACT
COMPACT
COMPACT
COMPACT
COMPACT
COMPACT
COMPACT
COMPACT
COMPACT
COMPACT
COMPACT
COMPACT
N S - 2 4 0 6 2 7 0 2 . 7 0 7 2 9 5 R E V IT CO N T R O L P O IN T E W - 7 4 7 7 8 5 0 1 . 9 9 4 5 0 9 E le v - 0 ' -0 " NO
PARKING
EV
CHARGING
ONLY
NO PARKING
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
R
T
MIN. 8" FROM BACK OF
PEDESTAL TO EOP
1M 1M
10 13
18 16
16 12
12 13
11 11
11 11
14 20
20 11
21 21
21 22
21 22
22 22
22 22
23 11
22 22
22 24
24 17
11 22
22 11
11 11
11 11
17 17
25 25
26 24
24 21 21 21 21
22 22
22 27
27 27
11 15
28 19
19 27
27 10
28 27
17 206
208
203
208
207
207
206
208
207
210
205
205
200
200
200
200
205
6"
4"
5"
5"
12"
6"
12"
12"
4"
4"
4"
12"
12"
12"
6"x2
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
R
T
R
T
C
C
C
10 13
18 16
16 12
12 13
11 11
11 11
14 20
20 11
21 21
21 22
21 22
22 22
22 22
23 11
22 22
22 24
24 17
11 22
22 11
11 11
11 11
17 17
25 25
26 24
24 21 21 21 21
22 22
22 27
27 27
11 15
28 19
19 27
27 10
28 27
17 NO
PARKING
DECK: 11169 SF/15 OLF = 745 OCC
POOL: 9227 SF / 50 OLD = 185 OCC
BLEACHERS: (25' X 12)/18" = 200 OCC
BLDG: 55 OCCUPANTS
TOTAL = 1182
344
344
344
344
150
BLDG B
BLDG A
L=140'
L=150'
L=150'
(E) FIRE ACCESS
FROMN PRIVATE DRIVE AISLE
150
REQUIRED
PROVIDED 36"
30"
REQUIRED
PROVIDED 48"
30"
REQUIRED
PROVIDED 72"
69"
REQUIRED
PROVIDED 96"
69"
REQUIRED
PROVIDED 96"
69"
166'-0"
146'-0" 35'-6"
108'-0" EATD
132'-0" EATD
19'-2" EATD
41'-3" EATD
96'-8" EATD 42'-4" EATD
13'-3"
241'-2"
VAN ACCESSIBLE
CONTROL AREAS, PER MR-1, MR-4
NORTH POOL
CANOPY
WEST POOL
CANOPY
WEST BLDG A NEW CANOPY
SOUTH
BLDG A NEW
CANOPY
38'-8"
75'-8"
61'-11"
89'-8"
21'-8"
26'-0"
51'-2"
106'-11"
54'-6"
30'-5"
45'-11" EATD
109'-2" EATD
BUILDINGS "A" & "B"
BUILDING CLASSIFICATION
BUILDING USE: RESTROOMS, SHOWERS/ LOCKERS, ADMIN/ O FFICE POOL SUPPORT SPACES. POOL PUMP ROOM, FAMILY
RESTROOMS SHOWERS/ CHANGING ROOMS
OCCUPANCY: A-5, B
ACCESSORY OCCUPANCIES (508.3.1): S-2
INCIDENTAL USES (508.2): NONE
CONSTRUCTION TYPE: TYPE V - B
FIRE PROTECTION: NON SPRINKLERED
FLOOR AREA ALLOWABLE - CBC (CHAPTER 5)
BASIC ALLOWABLE AREA AND HEIGHT (TABLE 503)
AREA PER STORY: 9,000SF (A t)
NUMBER OF STORIES: 2
HEIGHT: 40 FT
PROPOSED BUILDING HEIGHT/STORY
BUILDING HEIGHT A: 17'-2" (EXISTING)
BUILDING HEIGHT B: 17'-2"
FRONTAGE INCREASE FACTOR l
f (CBC 506.3.3)
If: .38 (83% OF BUILDING PERIMETER HAS 20' TO LESS THA N 25' OPEN SPACE) AREA INCREASE MIXED USE PER STORY A a = [A t + (NS x l f ) (CBC 506.2.2) At: 9,000
NS: 9,000
I
f: .38
TOTAL ALLOWABLE AREA (CBC 506.2.2)
Aa: 12,420SF
PROPOSED BUILDINGS SQUARE FOOTAGE
2,968 SF - EXISTING BUILDING 'A'
+ 242 SF - PROPOSED BUILDING 'A' ADDITION
+ 800 SF - PROPOSED BUILDING 'A SOUTH STORAGE FABRIC CANOPY + 725 SF - PROPOSED BUILDING 'A' WEST CANOPY
+ 2,108 SF - PROPOSED BUILDING 'B'
+ 1,429 SF - PROPOSED NORTH POOL DECK FABRIC CANOPY
+ 1,254 SF - PROPOSED WEST POOL DECK FABRIC CANOPY
+ 187 SF - PROPOSED TRASH ENCLOSURE
TOTAL 9,713 SF < 12,420SF (OK)
FIRE-RESISTANCE RATING REQ FOR BLDG ELEMENTS (CBC 601)
STRUCTURAL FRAME: 0
EXTERIOR BEARING WALLS: 0
INTERIOR BEARING WALLS: 0
EXTERIOR NONBEARING WALLS: 0
INTERIOR NONBEARING WALLS: 0
FLOOR CONSTRUCTION: 0
ROOF CONSTRUCTION: 0
TOTAL OCCUPANCY: 1,182 OCCUPANTS/ 2 = 591 MEN / 591 WOMEN
TOTAL REQUIRED FIXTURES
WATER CLOSET URINALS LAVATORIES SHOWERS
MEN 4 4 4 6
WOMEN 5 4 6
DRINKING FOUNT.
3 PROPOSED POOL
POOL CLASSIFICATION`
OCCUPANCY TYPE: A-5
AREA: 8,812 SF
POOL DECK AREAS: 12,450 SF
REQUIRED PUBLIC FIXTURES PER SECTION 3116B.2
POOL: 15 SF / OCCUPANT
TOTAL OCCUPANTS: 1,182 OCCUPANTS
PARKING SPACES (11B-208)
TOTAL STALLS: 54
REQUIRED TOTAL ACCESSIBLE STALLS: 03
REQUIRED VAN ACCESSIBLE STALLS: 01
ACCESSIBLE STALLS PROVIDED: 03
ACCESSIBLE VAN STALLS PROVIDED: 01
EV PARKING SPACES (11B-228.3.2.1)
REQUIRED EV CAPABLE SPACES 10
REQUIRED EVCS 03
REQUIRED EV VAN STALLS 01
LEGEND
ACCESSIBLE PATH OF TRAVEL
HOSE PULL
PROPERTY LINE
EXIT ACCESS TRAVEL DISTANCE EATD
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. T he
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
CODE ANALYSIS
G2.10
MD
MONROE ST. POOL REPLACEMENT
CODE ANALYSIS
1" = 20' -0"
G2.10 08 SITE EXITING PLAN
CODE ANALYSIS LEGEND
203
9 08/09/2024
1 A
2 BC
3 4
D
232 SF
16 OCC.
MULTI
PURPOSE
ROOM
14 B 1:15
56 SF
1 OCC.
ELEC.
14A
S-2 1:300
25 SF
1 OCC.
STORAGE
04A
S-2 1:300
124 SF
4 OCC.
MEN'S
CHANGING/
LOCKERS
05 B 1:50
MEN'S
SHOWER
06 MEN'S
RESTROOM
04 CORRIDOR
02 221 SF
15 OCC.
STAFF
LOUNGE
03 B 1:15
230 SF
16 OCC.
LOBBY
01 B 1:15
STAFF
SHOWER
03B
STAFF
RR
03A
128 SF
1 OCC.
ADMIN
07 B 1:150
99 SF
1 OCC.
OFFICE
07A
B 1:150
CORRIDOR
08 WOMEN'S
SHOWER
11 126 SF
4 OCC.
WOMEN'S
CHANGING/
LOCKERS
10 B 1:50 WOMEN'S
RESTROOM
09 23 SF
1 OCC.
STORAGE
09A
S-2 1:300
15 REQUIRED
PROVIDED 72"
3"
14 14
17 1
5 1
3 1
21 5
1 REQUIRED
PROVIDED 48"
3"
REQUIRED
PROVIDED 48"
3"
REQUIRED
PROVIDED 48"
3"
REQUIRED
PROVIDED 48"
3"
REQUIRED
PROVIDED 36"
3"
REQUIRED
PROVIDED 64"
3 1/2"
15 386 SF
2 OCC.
EXTERIOR
STORAGE
18 S-2 1:300
2 114 SF
3 OCC.
FIRST AID
16 B 1:50
76 SF
1 OCC.
EQUIPMENT
STORAGE
17 S-2 1:300
18'-9"
5 6
7 F E
903 SF
3 OCC.
POOL PUMP
ROOM
22 S-2 1:300
175 SF
1 OCC.
STORAGE
19 S-2 1:300
120 SF
1 OCC.
ELECTRICAL
21 S-2 1:300
140 SF
3 OCC.
CORRIDOR/
LOCKERS
20 A-3 1:50
FAMILY
RESTROOM/
SHOWER
20C
1 1
REQUIRED
PROVIDED 62"
3"
REQUIRED
PROVIDED 32"
3"
REQUIRED
PROVIDED 48"
3"
REQUIRED
PROVIDED 48"
3"
64 SF
CHEMICAL
ROOM
24 64 SF
CHEMICAL
ROOM
25 3 1 1
3 LEGEND
METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION
CMU WALL CONSTRUCTION
GLAZING SYSTEM
PATH OF TRAVEL
EXISTING WALLS
1. CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS AND REPORT ALL DISCREPANCIES TO ARCHITECT.
2. EXTERIOR WALL DIMENSIONS ARE TO FACE OF STRUCTURAL SHEATHING, U.N.O. INTERIOR WALL DIMENSIONS ARE TO FACE OF STUD, U.N.O. VERIFY ANY DISCREPANCIES IN THE FIELD WITH THE ARCHITECT PRIOR TO BUILDING.
3. ALL GYPSUM BOARD EXPOSED TO VIEW SHALL HAVE LEVEL #4 FINISH, U.N.O.
4. FURRING AT COLUMNS, ROOF DRAINS, PIPES AND SIMILAR ELEMENTS TO BE HELD AS TIGHT TO OBSTRUCTION AS POSSIBLE, U.N.O.
5. AT ALL WET WALL LOCATIONS INCLUDING TOILET ROOMS, PROVIDE MOISTURE
RESISTANT GYPSUM BOARD AT EXPOSED AREAS AND CEMENTITIOUS BACKER BOARD BEHIND TILE.
6. PROVIDE THERMAL BATT INSULATION AT ALL EXTERIOR WALL AND ROOF ASSEMBLIES. R19 MIN. AT WALLS AND R40 MIN. AT ROOF.
7. LOCATE DOOR FRAME 6" MIN. FROM ADJACENT WALL FRAMING, TYP. DOOR FRAMES ARE TO BE LOCATED 6" FROM ADJACENT WALL FRAMING, U.N.O.
8. SLAB PLANS INDICATE WHICH WALLS REQUIRE CURBS. REFER TO WALL TYPES AND DETAILS FOR CURB WIDTHS.
9. WINDOW FRAME AND GLAZING TYPES PER EXTERIOR ELEVATIONS.
10. REFER TO INTERIOR ELEVATIONS FOR QUANTITY, LOCATION, AND DIMENSIONS OF WHITEBOARDS. COORDINATE AND PROVIDE BACKING AS REQUIRED.
11. ALL PLYWOOD AND WOOD BLOCKING SHALL BE FIRE TREATED PER TYPE IIA CONSTRUCTION.
12. CURTAINS SHALL NOT BE USED TO COVER OR BLOCK THE VIEW OF EXITS P ER SECTIONS 806.2 AND 1010.1 CBC.
13. THE MEANS OF EGRESS SHALL BE ILLUMINATED AT ALL TIMES THE BUILDI NG SPACE IS OCCUPIED.
14. THE MEANS OF EGRESS ILLUMINATION LEVEL SHALL NOT BE LESS THAN 1 FOOT -CANDLE AT THE WALKING SURFACE.
15. THE MEANS OF EGRESS ILLUMINATION SHALL BE SUPPLIED BY BACKUP
POWER (CONSISTING OF STORAGE BATTERIES, UNIT EQUIPMENT, OR AN ON - SITE GENERATOR) FOR A DURATION OF NOT LESS THAN 90 MINUTES. CBC 1008.3
GENERAL NOTES
0 0
### SF
Occ-Load OCC.
Room Name
###
# 1:OLF
ROOM NUMBER
SQUARE FOOTAGE
OCCUPANT LOAD
OCCUPANCY LOAD FACTOR
OCCUPANCY GROUP
COMBINED ROOM OCCUPANCY LOAD
INDIVIDUAL ROOM OCCUPANCY LOAD
REQUIRED
PROVIDED 36"
32"
REQUIRED EGREE WIDTH PER CODE
ANALYSIS
- DOORS/THRESHOLDS AT .15"/OCC PER
EXCEPTION #1 1005.3.2 OF CBC 2022;
- STAIRWAYS AT .3"/OCC
PROVIDED WIDTH
NO OCCUPANT LOAD
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
EGRESS PLAN
G2.11
MD
MONROE ST. POOL REPLACEMENT
EGRESS PLAN
KEYNOTE LEGEND
1/8" = 1' -0"
G2.11 04 BLDG A EGRESS
1/8" = 1' -0"
G2.11 11 BLDG B EGRESS
10 203
08/09/2024
COMPACT
COMPACT
COMPACT
COMPACT
COMPACT
COMPACT
COMPACT
COMPACT
COMPACT
COMPACT
COMPACT
COMPACT
N S - 2 4 0 6 2 7 0 2 . 7 0 7 2 9 5
R E V IT CO N T R O L P O IN T E W - 7 4 7 7 8 5 0 1 . 9 9 4 5 0 9 E le v - 0 ' -0 " NO
PARKING
EV
CHARGING
ONLY
NO PARKING
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
R
T
MIN. 8" FROM BACK OF
PEDESTAL TO EOP
1M 1M
10 13
18 16
16 12
12 13
11 11
11 11
14 20
20 11
11 21 21
22 21
22 22
22 22
22 23 11
22 22
22 24
24 24
17 11
22 22
11 11
11 11
11 11
17 17
17 25
25 26
24 24
21 21 21 21
22 22
22 11
27 27
27 11
15 28
19 19
27 27
10 28
27 17
206
208
203
208
207
207
206
208
207
210
205
205
200
200
200
200
205
6"
4"
5"
5"
12"
6"
12"
12"
4"
4"
4"
12"
12"
12"
6"x2
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
EV
CHARGING
ONLY
R
T
R
T
C
C
C
10 13
18 16
16 12
12 13
11 11
11 11
14 20
20 11
11 21 21
22 21
22 22
22 22
22 23 11
22 22
22 24
24 24
17 11
22 22
11 11
11 11
11 11
17 17
17 25
25 26
24 24
21 21 21 21
22 22
22 11
27 27
27 11
15 28
19 19
27 27
10 28
27 17
NO
PARKING
N
PROJECT NORTH
N
TRUE NORTH
A0.31
06 32.01
61'-11"
89'-8"
75'-8"
28'-2"
32.02 106'-11"
LEGEND
ACCESSIBLE PATH OF TRAVEL (P.O.T.)
ACCESSIBLE PATH OF TRAVEL (P.O.T.). BARRIER -FREE
ACCESS ROUTE WITHOUT ANY ABRUPT VERTICAL CHANGES
EXCEEDING 1/2" BEVELED AT 1:2 MAXIMUM SLOPE, EXCEPT
THAT LEVEL CHANGES DO NOT EXCEED 1/4" VERTICAL AND
IS AT LEAST 48" WIDE. SURFACE IS SLIP RESISTANT,
STABLE, FIRM, AND SMOOTH. CROSS -SLOPE DOES NOT
EXCEED 2% AND SLOPE IN THE DIRECTION OF TRAVEL IS
LESS THAN 5% UNLESS OTHERWISE INDICATED. P.O.T.
SHALL MAINTAIN FREE OF OVERHANGING OBSTRUCTIONS
TO 80" MINIMUM (11B -307.4) AND PROTRUDING OBJECTS
GREATER THAN 4" PROJECTION FROM WALL AND ABOVE 27"
AND LESS THAN 80" (11B -204 AND 11B -307). ARCHITECT TO
VERIFY THAT ALL BARRIERS IN THE PATH OF TRAVEL HAVE
BEEN REMOVED OR WILL BE REMOVED UNDER THIS
PROJECT, AND PATH OF TRAVEL COMPLIES WITH CBC
11B -206 PER 11B -201.4.
CONSTRUCTION SUPPORT FACILITIES, RELATED PARKING,
AND TOILETS SHOULD BE INCLUDED IN THE PATH OF
TRAVEL (EXCEPT AS NOTED IN 11B -203.2)
GENERAL NOTES
1. FOR PATH OF TRAVEL, CODE ANALYSIS, AND BUILDING DATA, REFER TO G2.10
2. FOR FIRE ACCESS INFORMATION, REFER TO G2.10
3. ALL AREAS AND SQUARE FOOTAGE DESCRIPTIONS SHOWN ARE FOR AGENCY
USE ONLY AND SHALL NOT BE USED FOR BIDDING OR CONSTRUCTION PURPOSE.
4. GATES IN THE PATH OF EGRESS MUST COMPLY WITH EXIT DOOR REQUIREMENTS. PROVIDE LEVER HARDWARE AND KICKPLATE. REFER TO LANDSCAPE DRAWINGS.
5. SHADE CANOPY ENGINEERING IS A DEFERRED SUBMITTAL.
PROPOSED BUILDING CANOPY/ OVERHANG
INDICATES RESTROOM OUTLINES (M) MEN, (W)
WOMEN, (R) RESTROOM
EASEMENT BOUNDARY, PER CIVIL DRAWINGS
PROPOSED CANOPY, PER LANDSCAPE
DRAWINGS. SHADE CANOPY ENGINEERING IS
A DEFERRED SUBMITTAL.
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
SITE PLAN
A0.21
MD
MONROE ST. POOL REPLACEMENT
SITE PLAN
KEYNOTE LEGEND
32.01 OUTDOOR STORAGE, WITH FABRIC CANOPY, REF SHEET : 3.0-2000.
SHADE CANOPY ENGINEERING IS A DEFERRED SUBMITTAL.
32.02 NEW POOL PER, SP-1
B
A
NEW
BUILDING
NEW
ADDITION
EXISTING
BUILDING
2,108 SF
2,968 SF
242 SF
EASEMENT BOUNDARY, PER CIVIL DRAWINGS
EASEMENT BOUNDARY, PER CIVIL DRAWINGS
11 203
08/09/2024
A0.31
09 A0.31
04 A0.31
08 A0.31
05 18'-8"
10'-8"
8'-8"
1'-0"
32.04 3'-8"
1'-0"
6'-6"
2'-4"
6'-6"
1'-0"
1'-0"
1'-0"
1'-0"
1'-0"
1'-0"
11 A0.31
32.03 32.04
04 L5.12
32.03 10
L5.12
CONCRETE CURB
8" CONCRETE UNIT
MASONRY, SPLIT FACE
TO MATCH EXISTING
CONCRETE BLOCK CAP
FOOTING, REF TO: 02/S1.11
CMU WALL, REF TO: 02/S1.11
CONCRETE SLAB PER CIVIL 0'-6"
1'-0" 6'-4"
2"
6'-6"
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
TRASH ENCLOSURE
A0.31
MD
MONROE ST. POOL REPLACEMENT
TRASH ENCLOSURE
KEYNOTE LEGEND
32.03 CMU SPEC
32.04 6" TALL CONCRETE CURB.
1/4" = 1' -0"
A0.31 06 TRASH ENCLOSURE FLOOR PLAN
3/8" = 1' -0"
A0.31 09 SOUTHWEST ELEVATION
3/8" = 1' -0"
A0.31 04 NORTHWEST ELEVATION
3/8" = 1' -0"
A0.31 08 NORTHEAST ELEVATION
3/8" = 1' -0"
A0.31 05 SOUTHEAST ELEVATION
1" = 1' -0"
A0.31 11 TRASH ENCLOSURE WALL AND
CURB
12 203
08/09/2024
1 A
2 BC
3 4
D
A1.03
15 A1.03 05
A1.03 11
A1.03
04 02.01 02.01
02.02 02.05
02.12 02.11
02.06 02.07
02.04 02.04
02.05 02.02
02.12 02.11
02.08 02.06
02.07 02.16
02.15 02.18
02.18 02.23
02.22 02.13
02.28 02.28
02.36 02.37
1 A
2 BC
3 4
D
02.17 02.20
02.21 02.21
02.20 02.20
02.21 02.20
02.29 02.29
02.29 02.29
02.29 02.29
02.29 02.23
DEMO FLOOR PLAN LEGEND
EXISTING WALL TO REMAIN. PROTECT IN PLACE.
EXISTING WALL TO BE DEMOLISHED
EXISTING DOOR AND FRAME TO BE REMOVED
EXTENTS OF EXISTING SLAB DEMOLITION
DEMO RCP LEGEND
EXISTING HARD LID CEILING TO BE DEMOLISHED
2'X2' ACT CEILING SYSTEM TO BE DEMOLISHED
INCLUDES TILE AND GRID.
DEMO KEYOTE
LIGHT FIXTURE TO BE DEMOLISHED
?
DEMOLITION GENERAL NOTES
1. THE EXISTING CONDITIONS SHOWN ARE FROM AVAILABLE RECORD DRAWINGS AND SHOWN FOR REFERENCE ONLY. CONTRACTOR SHALL VERIFY ACTUAL EXISTING CONDITIONS AT SITE PRIOR TO SUBMITTING BID. ALL DEMOLITION, ALTERATION,
EXTENSION, RELOCATION, REHABILITATION WORK SHALL BE INCLUDED IN CONTRACT. NO ADDITIONAL ALLOWANCE OR CHANGE ORDERS WILL BE ACCEPTED.
2. CONTRACTOR IS RESPONSIBLE TO RELOCATE OR REMOVE FROM WALLS, CEILINGS, FLOOR SPACES, ETC. ANY EXISTING CONDUITS, WIRES, BOXES, FITTINGS,
FIXTURES OR OTHER ELECTRICAL EQUIPMENT WHICH INTERFERES WITH PLANNED REMODEL WORK. PROVIDE CIRCUIT CONTINUATION REQUIRED FOR ALL EXISTING OUTLETS, FIXTURES, EQUIPMENT, ETC. SCHEDULED TO REMAIN.
3. NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY WHEREVER EXISTING EQUIPMENT
IS ENCOUNTERED WHICH MUST BE RELOCATED DUE TO THE NEW CONSTRUCTION, OR NOT INDICATED ON "AS -BUILT" DRAWINGS OR WAS BURIED UNDERGROUND OR EMBEDDED IN STRUCTURE WALLS.
4. CAREFULLY PROTECT ALL WALLS, TRIM, FLOORS, EQUIPMENT, UTILITY LINES AND MATERIALS. WHEN WORKING ON FINISHED SURFACES, LIMIT DAMAGE TO THE
SMALLER AREA IF POSSIBLE AND RESTORE TO THE ORIGINAL CONDITION ALL SURFACES WHICH ARE DAMAGED BECAUSE OF THE INSTALLATION OF THIS WORK.
5. EQUIPMENT, MATERIALS AND SUPPLIES TEMPORARILY REMOVED FOR PROTECTION SHALL BE REPLACED IN ORIGINAL LOCATIONS. ANY MATERIALS DAMAGED SHALL
BE REPLACED WITH NEW MATERIALS OF LIKE KIND AND QUALITY
6. DEMOLITION WORK SHALL BE DONE IN A MANNER WHICH WILL NOT CAUSE
UNNECESSARY INCONVENIENCE OR DANGER TO USERS OF THE PREMISES AND ADJACENT SITE, AND NOT INTERFERE WITH ITS OPERATION. ANY DEMOLITION WORK TO BE PERFORMED MUST BE PLANNED IN ADVANCE.
7. DO ALL DRILLING, CUTTING, ETC. REQUIRED TO DEMOLISH ELECTRICAL WORK AS
INDICATED OR PROVIDE BLANK COVER PLATE ON ALL OUTLETS EXPOSED BY REMOVAL OF FIXTURE OF DEVICES.
8. RESEAL ALL PENETRATIONS OR OPENING THROUGH WALLS, CEILING, FLOORS, ETC., TO MAINTAIN THE RATING OF STRUCTURE.
9. CONTRACTOR SHALL VERIFY EXISTING CONDUIT/CONDUCTOR RUNS ON CIVIL DEMOLITION PLAN, SHEET C1.1. REUSE AS REQUIRED AND REMOVE ALL UNUSED CONDUIT/CONDUCTORS. REMOVE CONDUIT BACK TO SCOPE OF WORK LIMIT LINE.
AT EACH END OF FEEDER, TAG AND LABEL CONDUIT. DOCUMENT DETAILED DIMENSIONS ON AS -BUILTS. REMOVE CONDUCTORS BACK TO SOURCE (VERIFY WITH OWNER). UNUSED CONDUIT IN INACCESSIBLE LOCATIONS (WALLS TO REMAIN) CAN BE ABANDONED IN PLACE.
10. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDUIT/WIRING RUNS, REUSE AS REQUIRE AND REMOVED ALL UNUSED CONDUIT/WIRING. UNUSED CONDUIT IN INACCESSIBLE LOCATIONS (WALLS TO REMAIN) CAN BE ABANDONED IN PLACE.
REMOVE UNUSED WIRING.
11. CONTRACTOR TO VERIFY CIRCUIT NUMBER AND LOADS FOR ALL EXISTING
EQUIPMENT PRIOR TO INSTALLATION OF NEW OR RELOCATED ELECTRICAL EQUIPMENT. REASSIGN CIRCUITS AND LOADS ACCORDINGLY. PROVIDE COMPLETE "AS BUILT" DRAWINGS AND TYPEWRITTEN DIRECTORIES FOR PANELS.
12. WHERE NECESSARY TO SHUT OFF UTILITY SERVICES OR CAUSE INTERRUPTION TO
POWER OR SIGNAL SYSTEMS WHILE A BUILDING IS OCCUPIED OR THAT EFFECT
ADJACENT BUILDINGS, SCHEDULE OUTAGES OR INTERRUPTIONS WITH THE
OWNER, BUILDING OCCUPANTS AND/OR ADJACENT BUILDING OWNER(S) AND OCCUPANTS PRIOR TO CONDUCTING OUTAGE(S) OR INTERRUPTIONS.
13. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ONLY. DO NOT SCALE THE
ELECTRICAL DRAWINGS TO DETERMINE THE LOCATION OF EQUIPMENT OR OUTLETS. SEE ARCHITECTURAL PLANS, WHERE PROVIDED ON PROJECT, FOR EXTENT OF DEMOLITION.
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
DEMO FLOOR PLAN
& RCP BLDG A
A1.01
MD
MONROE ST. POOL REPLACEMENT
DEMO FLOOR PLAN & RCP BLDG A
1/8" = 1' -0"
04 / A1.03 DEMO FLOOR BLDG A 04
1/8" = 1' -0"
04 / A1.03 RCP DEMO BLDG A 11
KEYNOTE LEGEND
02.01 EXISTING CARPET TO BE REMOVED, PREP CONCRETE F OR NEW
FLOORING FINISH
02.02 EXISTING FLOORING FINISH TO BE DEMOLISHED
02.04 EXISTING COUNTERTOP AND FIXTURES TO BE DEMOLIS HED
02.05 EXISTING SHOWERS TO BE DEMOLISHED
02.06 EXISTING TOILETS, URINALS AND TOILET PARTITION TO BE
DEMOLISHED
02.07 EXISTING WALL MOUNTED LAVATORY TO BE DEMOLISHE D
02.08 EXISTING COLUMN TO REMAIN, PROTECT IN PLACE
02.11 EXISTING LOCKERS TO BE DEMOLISHED
02.12 EXISTING SHOWER BENCH TO BE DEMOLISHED
02.13 EXISTING STOREFRONT AND DOOR TO BE DEMOLISHED
02.15 EXISTING CASEWORK TO BE DEMOLISHED
02.16 EXISTING RECEPTION DESK TO BE DEMOLISHED
02.17 EXISTING SUSPENDED CEILING AND GRID TO BE DEMO LISHED
02.18 EXISTING DRINKING FOUNTAIN TO BE DEMOLISHED
02.20 EXISTING LIGHTING TO BE DEMOLISHED
02.21 EXISTING GYP CEILING TO BE DEMOLISHED
02.22 EXISTING WATER HEATER TO BE DEMOLISHED
02.23 EXISTING ROOF ACCESS LADDER AND HATCH TO BE DE MOLISHED
02.28 EXISTING SLAB TO BE DEMO'D FOR NEW PLUMBING
02.29 EXISTING SKYLIGHT TO BE REMOVED. INFILL WITH JOISTS AND PLYWOOD SHEATHING.
02.36 EXISTING AV CABINET - REMOVE AND RETURN TO BUI LDING OWNER.
02.37 EXISTING WALL MOUNTED TV, REMOVE AND RETURN TO OWNER
KEYPLAN
A
B
13 203
08/09/2024
DEMOLITION GENERAL NOTES
1. THE EXISTING CONDITIONS SHOWN ARE FROM AVAILABLE RECORD DRAWINGS AND SHOWN FOR REFERENCE ONLY. CONTRACTOR SHALL VERIFY ACTUAL EXISTING CONDITIONS AT SITE PRIOR TO SUBMITTING BID. ALL DEMOLITION, ALTERATION,
EXTENSION, RELOCATION, REHABILITATION WORK SHALL BE INCLUDED IN CONTRACT. NO ADDITIONAL ALLOWANCE OR CHANGE ORDERS WILL BE ACCEPTED.
2. CONTRACTOR IS RESPONSIBLE TO RELOCATE OR REMOVE FROM WALLS, CEILINGS, FLOOR SPACES, ETC. ANY EXISTING CONDUITS, WIRES, BOXES, FITTINGS,
FIXTURES OR OTHER ELECTRICAL EQUIPMENT WHICH INTERFERES WITH PLANNED REMODEL WORK. PROVIDE CIRCUIT CONTINUATION REQUIRED FOR ALL EXISTING OUTLETS, FIXTURES, EQUIPMENT, ETC. SCHEDULED TO REMAIN.
3. NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY WHEREVER EXISTING EQUIPMENT
IS ENCOUNTERED WHICH MUST BE RELOCATED DUE TO THE NEW CONSTRUCTION, OR NOT INDICATED ON "AS -BUILT" DRAWINGS OR WAS BURIED UNDERGROUND OR EMBEDDED IN STRUCTURE WALLS.
4. CAREFULLY PROTECT ALL WALLS, TRIM, FLOORS, EQUIPMENT, UTILITY LINES AND MATERIALS. WHEN WORKING ON FINISHED SURFACES, LIMIT DAMAGE TO THE
SMALLER AREA IF POSSIBLE AND RESTORE TO THE ORIGINAL CONDITION ALL SURFACES WHICH ARE DAMAGED BECAUSE OF THE INSTALLATION OF THIS WORK.
5. EQUIPMENT, MATERIALS AND SUPPLIES TEMPORARILY REMOVED FOR PROTECTION SHALL BE REPLACED IN ORIGINAL LOCATIONS. ANY MATERIALS DAMAGED SHALL
BE REPLACED WITH NEW MATERIALS OF LIKE KIND AND QUALITY
6. DEMOLITION WORK SHALL BE DONE IN A MANNER WHICH WILL NOT CAUSE
UNNECESSARY INCONVENIENCE OR DANGER TO USERS OF THE PREMISES AND ADJACENT SITE, AND NOT INTERFERE WITH ITS OPERATION. ANY DEMOLITION WORK TO BE PERFORMED MUST BE PLANNED IN ADVANCE.
7. DO ALL DRILLING, CUTTING, ETC. REQUIRED TO DEMOLISH ELECTRICAL WORK AS
INDICATED OR PROVIDE BLANK COVER PLATE ON ALL OUTLETS EXPOSED BY REMOVAL OF FIXTURE OF DEVICES.
8. RESEAL ALL PENETRATIONS OR OPENING THROUGH WALLS, CEILING, FLOORS, ETC., TO MAINTAIN THE RATING OF STRUCTURE.
9. CONTRACTOR SHALL VERIFY EXISTING CONDUIT/CONDUCTOR RUNS ON CIVIL DEMOLITION PLAN, SHEET C1.1. REUSE AS REQUIRED AND REMOVE ALL UNUSED CONDUIT/CONDUCTORS. REMOVE CONDUIT BACK TO SCOPE OF WORK LIMIT LINE.
AT EACH END OF FEEDER, TAG AND LABEL CONDUIT. DOCUMENT DETAILED DIMENSIONS ON AS -BUILTS. REMOVE CONDUCTORS BACK TO SOURCE (VERIFY WITH OWNER). UNUSED CONDUIT IN INACCESSIBLE LOCATIONS (WALLS TO REMAIN) CAN BE ABANDONED IN PLACE.
10. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDUIT/WIRING RUNS, REUSE AS REQUIRE AND REMOVED ALL UNUSED CONDUIT/WIRING. UNUSED CONDUIT IN INACCESSIBLE LOCATIONS (WALLS TO REMAIN) CAN BE ABANDONED IN PLACE.
REMOVE UNUSED WIRING.
11. CONTRACTOR TO VERIFY CIRCUIT NUMBER AND LOADS FOR ALL EXISTING
EQUIPMENT PRIOR TO INSTALLATION OF NEW OR RELOCATED ELECTRICAL EQUIPMENT. REASSIGN CIRCUITS AND LOADS ACCORDINGLY. PROVIDE COMPLETE "AS BUILT" DRAWINGS AND TYPEWRITTEN DIRECTORIES FOR PANELS.
12. WHERE NECESSARY TO SHUT OFF UTILITY SERVICES OR CAUSE INTERRUPTION TO
POWER OR SIGNAL SYSTEMS WHILE A BUILDING IS OCCUPIED OR THAT EFFECT
ADJACENT BUILDINGS, SCHEDULE OUTAGES OR INTERRUPTIONS WITH THE
OWNER, BUILDING OCCUPANTS AND/OR ADJACENT BUILDING OWNER(S) AND OCCUPANTS PRIOR TO CONDUCTING OUTAGE(S) OR INTERRUPTIONS.
13. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ONLY. DO NOT SCALE THE
ELECTRICAL DRAWINGS TO DETERMINE THE LOCATION OF EQUIPMENT OR OUTLETS. SEE ARCHITECTURAL PLANS, WHERE PROVIDED ON PROJECT, FOR EXTENT OF DEMOLITION.
1 A
2 BC
3 4
D
02.29 02.23 02.29
02.29 02.29
02.24 02.41
02.29 02.29
02.29 02.29
LEGEND
EXISTING ROOF DRAIN, TO REMAIN
EXISTING SKYLIGHT TO BE REMOVED AND INFILLED
AND/OR UTILIZED USED BY MECHANICAL; SEE
MECHANICAL
ROOF ASSEMBLY TO BE
DEMOLISHED
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
DEMO ROOF PLAN -
BLDG A
A1.02
MD
MONROE ST. POOL REPLACEMENT
DEMO ROOF PLAN - BLDG A
KEYNOTE LEGEND
02.23 EXISTING ROOF ACCESS LADDER AND HATCH TO BE DE MOLISHED
02.24 EXISTING MANSARD ROOF TO BE DEMOLISHED
02.29 EXISTING SKYLIGHT TO BE REMOVED. INFILL WITH JOISTS AND PLYWOOD SHEATHING.
02.41 EXISTING ROOF SOFFIT FRAMING TO BE DEMOLISHED
KEYPLAN
A
B
1/8" = 1' -0"
A1.02 04 DEMO ROOF PLAN
14 203
08/09/2024
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
A
TOP OF BLOCK WING
WALLS - BLDG A
17'-2"
B C D
02.25 02.26
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
1 TOP OF BLOCK WING
WALLS - BLDG A
17'-2"
234
02.26 02.46
02.33 02.33 02.38 02.39 02.39
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
1 TOP OF BLOCK WING
WALLS - BLDG A
17'-2"
2 3 4
02.24 TYP.
02.25 TYP.
02.25 02.13
TYP.
02.14 02.41
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
A
TOP OF BLOCK WING
WALLS - BLDG A
17'-2"
BCD
02.13 02.25
02.41 DEMOLITION GENERAL NOTES
1. THE EXISTING CONDITIONS SHOWN ARE FROM AVAILABLE RECORD DRAWINGS AND SHOWN FOR REFERENCE ONLY. CONTRACTOR SHALL VERIFY ACTUAL EXISTING CONDITIONS AT SITE PRIOR TO SUBMITTING BID. ALL DEMOLITION, ALTERATION,
EXTENSION, RELOCATION, REHABILITATION WORK SHALL BE INCLUDED IN CONTRACT. NO ADDITIONAL ALLOWANCE OR CHANGE ORDERS WILL BE ACCEPTED.
2. CONTRACTOR IS RESPONSIBLE TO RELOCATE OR REMOVE FROM WALLS, CEILINGS, FLOOR SPACES, ETC. ANY EXISTING CONDUITS, WIRES, BOXES, FITTINGS,
FIXTURES OR OTHER ELECTRICAL EQUIPMENT WHICH INTERFERES WITH PLANNED REMODEL WORK. PROVIDE CIRCUIT CONTINUATION REQUIRED FOR ALL EXISTING OUTLETS, FIXTURES, EQUIPMENT, ETC. SCHEDULED TO REMAIN.
3. NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY WHEREVER EXISTING EQUIPMENT
IS ENCOUNTERED WHICH MUST BE RELOCATED DUE TO THE NEW CONSTRUCTION, OR NOT INDICATED ON "AS -BUILT" DRAWINGS OR WAS BURIED UNDERGROUND OR EMBEDDED IN STRUCTURE WALLS.
4. CAREFULLY PROTECT ALL WALLS, TRIM, FLOORS, EQUIPMENT, UTILITY LINES AND MATERIALS. WHEN WORKING ON FINISHED SURFACES, LIMIT DAMAGE TO THE
SMALLER AREA IF POSSIBLE AND RESTORE TO THE ORIGINAL CONDITION ALL SURFACES WHICH ARE DAMAGED BECAUSE OF THE INSTALLATION OF THIS WORK.
5. EQUIPMENT, MATERIALS AND SUPPLIES TEMPORARILY REMOVED FOR PROTECTION SHALL BE REPLACED IN ORIGINAL LOCATIONS. ANY MATERIALS DAMAGED SHALL
BE REPLACED WITH NEW MATERIALS OF LIKE KIND AND QUALITY
6. DEMOLITION WORK SHALL BE DONE IN A MANNER WHICH WILL NOT CAUSE
UNNECESSARY INCONVENIENCE OR DANGER TO USERS OF THE PREMISES AND ADJACENT SITE, AND NOT INTERFERE WITH ITS OPERATION. ANY DEMOLITION WORK TO BE PERFORMED MUST BE PLANNED IN ADVANCE.
7. DO ALL DRILLING, CUTTING, ETC. REQUIRED TO DEMOLISH ELECTRICAL WORK AS
INDICATED OR PROVIDE BLANK COVER PLATE ON ALL OUTLETS EXPOSED BY REMOVAL OF FIXTURE OF DEVICES.
8. RESEAL ALL PENETRATIONS OR OPENING THROUGH WALLS, CEILING, FLOORS, ETC., TO MAINTAIN THE RATING OF STRUCTURE.
9. CONTRACTOR SHALL VERIFY EXISTING CONDUIT/CONDUCTOR RUNS ON CIVIL DEMOLITION PLAN, SHEET C1.1. REUSE AS REQUIRED AND REMOVE ALL UNUSED CONDUIT/CONDUCTORS. REMOVE CONDUIT BACK TO SCOPE OF WORK LIMIT LINE.
AT EACH END OF FEEDER, TAG AND LABEL CONDUIT. DOCUMENT DETAILED DIMENSIONS ON AS -BUILTS. REMOVE CONDUCTORS BACK TO SOURCE (VERIFY WITH OWNER). UNUSED CONDUIT IN INACCESSIBLE LOCATIONS (WALLS TO REMAIN) CAN BE ABANDONED IN PLACE.
10. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDUIT/WIRING RUNS, REUSE AS REQUIRE AND REMOVED ALL UNUSED CONDUIT/WIRING. UNUSED CONDUIT IN INACCESSIBLE LOCATIONS (WALLS TO REMAIN) CAN BE ABANDONED IN PLACE.
REMOVE UNUSED WIRING.
11. CONTRACTOR TO VERIFY CIRCUIT NUMBER AND LOADS FOR ALL EXISTING
EQUIPMENT PRIOR TO INSTALLATION OF NEW OR RELOCATED ELECTRICAL EQUIPMENT. REASSIGN CIRCUITS AND LOADS ACCORDINGLY. PROVIDE COMPLETE "AS BUILT" DRAWINGS AND TYPEWRITTEN DIRECTORIES FOR PANELS.
12. WHERE NECESSARY TO SHUT OFF UTILITY SERVICES OR CAUSE INTERRUPTION TO
POWER OR SIGNAL SYSTEMS WHILE A BUILDING IS OCCUPIED OR THAT EFFECT
ADJACENT BUILDINGS, SCHEDULE OUTAGES OR INTERRUPTIONS WITH THE
OWNER, BUILDING OCCUPANTS AND/OR ADJACENT BUILDING OWNER(S) AND OCCUPANTS PRIOR TO CONDUCTING OUTAGE(S) OR INTERRUPTIONS.
13. THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ONLY. DO NOT SCALE THE
ELECTRICAL DRAWINGS TO DETERMINE THE LOCATION OF EQUIPMENT OR OUTLETS. SEE ARCHITECTURAL PLANS, WHERE PROVIDED ON PROJECT, FOR EXTENT OF DEMOLITION.
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
DEMO ELEVATIONS
BLDG A
A1.03
MD
MONROE ST. POOL REPLACEMENT
DEMO ELEVATIONS BLDG A
1/8" = 1' -0"
A1.03 15 EXT ELEVATION - NORTH DEMO
1/8" = 1' -0"
A1.03 05 EXT ELEVATION - EAST DEMO
1/8" = 1' -0"
A1.03 11 EXT ELEVATION - WEST DEMO
1/8" = 1' -0"
A1.03 04 EXT ELEVATION - SOUTH DEMO
KEYNOTE LEGEND
02.13 EXISTING STOREFRONT AND DOOR TO BE DEMOLISHED
02.14 EXISTING LOUVERS TO BE DEMOLISHED
02.24 EXISTING MANSARD ROOF TO BE DEMOLISHED
02.25 EXISTING PLASTER ON CMU WALL TO BE REMOVED AND BLOCK
SANDBLASTED
02.26 EXISTING DOOR IN CMU TO BE DEMOLISHED
02.33 EXISTING SCREEN, FRAME TO BE REMOVED, OPENING TO BE INFILLED, REF:
02.38 EXISTING WINDOW AND FRAME TO BE DEMOLISHED AND INFILLED, REF:
02.39 EXISTING WINDOW AND FRAME TO BE DEMOLISHED
02.41 EXISTING ROOF SOFFIT FRAMING TO BE DEMOLISHED
02.46 EXISTING HI-LOW ACCESSIBLE DRINKING FOUNTAIN T O BE REMOVED.
KEYPLAN
A
B
EXISTING SECTION DRAWINGS FOR REFERENCE ONLY (NOT TO SCALE)
02.24 02.24 02.41
15 203
08/09/2024
LEGEND
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.01.
STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.01.
METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION
CMU WALL CONSTRUCTION
GLAZING SYSTEM
LINE OF ELEMENT ABOVE
HATCH INDICATES NEW BUILT -IN CASEWORK
EXISTING STUD WALLS
1. CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS AND REPORT ALL DISCREPANCIES TO ARCHITECT.
2. EXTERIOR WALL DIMENSIONS ARE TO FACE OF STRUCTURAL SHEATHING, U.N.O. INTERIOR WALL DIMENSIONS ARE TO FACE OF STUD, U.N.O. VERIFY ANY DISCREPANCIES IN THE FIELD WITH THE ARCHITECT PRIOR TO BUILDING.
3. ALL GYPSUM BOARD EXPOSED TO VIEW SHALL HAVE LEVEL #4 FINISH, U.N.O.
4. FURRING AT COLUMNS, ROOF DRAINS, PIPES AND SIMILAR ELEMENTS TO BE HELD AS TIGHT TO OBSTRUCTION AS POSSIBLE, U.N.O.
5. AT ALL WET WALL LOCATIONS INCLUDING TOILET ROOMS, PROVIDE MOISTURE
RESISTANT GYPSUM BOARD AT EXPOSED AREAS AND CEMENTITIOUS BACKER BOARD BEHIND TILE.
6. PROVIDE THERMAL BATT INSULATION AT ALL ROOF ASSEMBLIES. R40 MIN. AT ROOF.
7. LOCATE DOOR FRAME 6" MIN. FROM ADJACENT WALL FRAMING, TYP. DOOR FRAMES ARE TO BE LOCATED 6" FROM ADJACENT WALL FRAMING, U.N.O.
8. SLAB PLANS INDICATE WHICH WALLS REQUIRE CURBS. REFER TO WALL TYPES AND DETAILS FOR CURB WIDTHS.
9. REFER TO INTERIOR ELEVATIONS FOR QUANTITY, LOCATION, AND DIMENSIONS OF WHITEBOARDS. COORDINATE AND PROVIDE BACKING AS REQUIRED.
GENERAL NOTES
FINISH SCHEDULE: REFER TO A6.31
FIRE EXTINGUISHER CABINET, WALL
MOUNTED. REF: 12/A9.11
FEC
EXISTING CMU WALLS
1 A
A3.01 13
A3.01
05 A3.01
06 A3.01 12
06 A3.11
13 A3.11
2 BC
3 4
D
LOBBY
01 STAFF
LOUNGE
03 MULTI
PURPOSE
ROOM
14 TELEPHONE
15 STAFF
RR
03A
STAFF
SHOWER
03B
ADMIN
07 OFFICE
07A
WOMEN'S
CHANGING/
LOCKERS
10 WOMEN'S
RESTROOM
09 WOMEN'S
SHOWER
11 CORRIDOR
08 CORRIDOR
02 MEN'S
RESTROOM
04 MEN'S
CHANGING/
LOCKERS
05 MEN'S
SHOWER
06 STORAGE
04A
04 A3.11
STORAGE
09A
11'-0"
08.05 ELEC.
14A
22.01 10.01
05 A3.11
09 A3.11
A4.03
06 A4.04
06 A4.02
06 A4.01
06 A4.02
05 A4.01
13 4A
4A
5D
5D
3A
3A
102 103
104
106
107
109A
109
108
111A
111
108A
110
105
1A
SA6
SA6
MA8
SB6
FIRST
AID
16 EQUIPMENT
STORAGE
17 EXTERIOR
STORAGE
18 A3.01 04
FEC
FEC
101
07 A3.21
10 1/2"
9'-10 1/8"
(E)12'-8"
112
5D
5D
2A
4'-4"
5'-0" CLR.
18" MIN.
18" MIN. 5'-0" CLR.
5'-0" MIN. CLR.
5'-5"
A4.05
06 6'-2" 13'-6" 13'-6" 6'-5"
8'-4"
SA6 SA6
1" 10'-0"
15'-6" 15'-6" 15'-6" 13'-6"
10"
2'-2" 3'-4" 3'-4" 3'-4" 3'-3" 3'-5" 3'-4" 3'-4" 3'-4" 1'-8" 104A
28'-8"
10.05 11'-4" 22'-0"
9'-8" 8'-0" 4'-8" 7'-4"
11"
4'-8" 35'-0"
4"
7'-4" 2'-8"
5'-4" 12'-7"
4'-6"
5 6
7 F E
POOL
PUMP
ROOM
22 A3.02
A3.02
05 A3.02
11 A3.02 04
06 A3.12
05 A3.12
13 A3.12
ELECTRICAL
21 STORAGE
19 FAMILY
RESTROOM/
SHOWER
20C
12 CORRIDOR/
LOCKERS
20 34'-0"
62'-0"
36'-0" 26'-0"
22.05 11
A3.12
04 A3.12
12 A3.12
A4.06
06 119
113
114A
114B
114C
115
116 117 118
SN6
CHEMICAL
ROOM
24 CHEMICAL
ROOM
25 BACKWASH
22A
PUMP
PIT
22B
SE3
114D
114E
TANK
STORAGE
23 130
114
10'-8" 41'-6" 9'-3"
2'-4" 9'-1" 7'-8" 5'-10" 8'-6"
9'-1" 9'-1" 5'-1"
4'-0" 4'-8"
8'-10"
5'-2" 14'-8"
2'-4"
CLR.
2'-10"
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. T he
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
FIRST FLOOR PLAN
- BLDG A & B
A2.01
MD
MONROE ST. POOL REPLACEMENT
FIRST FLOOR PLAN - BLDG A & B
KEYNOTE LEGEND
08.05 NEW STOREFRONT GLAZING WITH FRITTED GLASS AND LOUVERS
AT UPPER SECTION
10.01 CUSTOM DIGITALLY PRINTED GRAPHIC ON VINYL WALL COVERING
10.05 SHADE STRUCTURE: SEE SHADE CONSULTANT SHEETS. SHADE CANOPY ENGINEERING IS A DEFERRED SUBMITTAL.
22.01 NEW WATER HEATER
22.05 NEW HI-LOW ACCESSIBLE DRINKING FOUNTAIN/ BOTTL E FILLING
STATION
1/8" = 1' -0"
A2.01 04 FLOOR PLAN - BLDG A
1/8" = 1' -0"
A2.01 11 FLOOR PLAN - BLDG B
KEYPLAN
A
B
203
16 08/09/2024
WP
WP
F F
M
M M
M
M
M
M
M
M
WP
WP
LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED
LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED
LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED M
M
WP
OS
OS
OS
WP
WP
M
M M
M
J
M
M
J
J
J
M
1 A
2 BC
3 4
D
05.03 08.03
05.01 1/4"/12"
1/4"/12"
1/4"/12"
1/4"/12"
1/4"/12"
3/8"/12"
3/8"/12"
3/8"/12"
3/8"/12"
1/4"/12"
9'-4 1/8"
9'-7 167/256"
07 A3.21
TYP.
23.02 TYP.
23.01 TYP.
23.03 TYP.
23.01 TYP.
23.01 TYP.
23.01 TYP.
02.42 TYP.
02.42 TYP.
02.42 TYP.
02.42 TYP.
23.06 10.04
07.05 10.05
5 6
7 F E
08.03 07.02
10.03 6'-2"
8'-3"
3/8" / 1'-0"
3/8" / 1'-0"
1/4" / 1'-0"
1/4" / 1'-0"
3/8"/12" 3/8"/12" 3/8"/12" 3/8"/12"
31'-0 3/4"
16'-4 3/8"
11'-5 41/64"
11'-0 1/8"
11'-11 25/32" 11'-5 41/64"
13'-0"
11'-5 41/64"
11'-11 25/32"
11'-0 1/8"
11'-5 41/64"
1/4" / 1'-0"
3/8" / 1'-0"
TYP.
23.01 TYP.
23.03 23.02
3'-3"
3'-3"
1. BACKGROUND DRAWINGS ARE BASED ON ORIGINAL CONSTRUCTION DOCUMENTS, NOT AS -BUILT DRAWINGS. PLEASE VERIFY ALL CONDITIONS AND DIMENSIONS PRIOR TO CONSTRUCTION. REPORT AN DISCREPANCIES TO THE ARCHITECT.
2. EXISTING CONDITIONS DAMAGED OR REMOVED AS A RESULT OF ALL WORK
REQUIRED TO BE DONE UNDER THIS CONTRACT SHALL BE REPAIRED OR
REPLACED TO ORIGINAL CONDITION AND FINISHED TO MATCH ADJACENT SURFACES WITHOUT ADDITIONAL COST TO THE OWNER.
3. CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS AND REPORT ALL DISCREPANCIES TO THE DESIGNER.
4. ROOFING MATERIAL TO HAVE A CLASS A FIRE CLASSIFICATION, PER CIT Y OF
CARLSBAD
GENERAL NOTES
LEGEND
ROOF DRAIN AND OVERFLOW DRAIN, REFER TO
PLUMBING DRAWINGS
EV PANEL - SOLAR THERMAL -
WITH HSS STRUCTURAL GRID
SUPPORT, PER
1/2" COVER BOARD OVER TAPERED RIGID
INSULATION CRICKET, SLOPED TO DRAIN, 1/4" MIN.
AT VALLEY; RE: 10/A8.21
XX" / XX" ROOF SLOPE
MECHICANICAL EQUIPMENT PER MECH DRAWINGS
EXISTING ROOF DRAIN
EXISTING WALL
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
ROOF PLAN - BLDG
A & B
A2.09
MD
MONROE ST. POOL REPLACEMENT
ROOF PLAN - BLDG A & B
KEYNOTE LEGEND
02.42 EXISTING ROOF DRAIN
05.01 NEW ROOF ACCESS LADDER, 13/A8.22
05.03 NEW MECHANICAL SCREEN SYSTEM
07.02 ROOF CRICKET / TAPERED INSULATION SLOPED TO DR AIN
07.05 ROOF TO WALL JOINT TRANSITION. FULL LENGTH OF WALL AT NEW ADDITION. CONSTRUCTION SPECIALTIES SC-800 JOINT. SEE
04/A8.21.
08.03 NEW ROOF HATCH
10.03 PV - PHOTOVOLTAIC PANELS, PER ELECTRICAL DRAWI NGS,
STRUCTURAL SUPPORT PER STRUCTURAL DRAWINGS
10.04 FALL PROTECTION TIEBACK ANCHOR, PER S6.12/5
10.05 SHADE STRUCTURE: SEE SHADE CONSULTANT SHEETS. SHADE CANOPY ENGINEERING IS A DEFERRED SUBMITTAL.
23.01 ROOF EXHAUST, PER MECHANICAL DRAWINGS
23.02 MECHANICAL DUCTING, PER MECHANICAL DRAWINGS
23.03 ROOF VENT PER MECHANICAL DRAWINGS
23.06 MECHANICAL PIPING PER MECHANICAL DRAWINGS
1/8" = 1' -0"
A2.09 04 BLDG A - ROOF PLAN
1/8" = 1' -0"
A2.09 11 BLDG B - ROOF PLAN
KEYPLAN
A
B
17 203
08/09/2024
5 6
7 F E
8'-5 1/8" 8'-5 1/8"
14'-11 1/4"
8'-10 1/4"
8'-2 5/8"
14'-0 1/2"
-2'-2 3/8" -2'-2 3/8"
-2'-2 3/8"
-7'-2 3/8"
-2'-2 3/8"
-2'-2 3/8"
-0'-4 5/8"
4'-5 3/4" 9'-6"
25'-4 3/4"
32'-8 3/4"
6'-4"
14'-8"
13'-5"
2'-0" 10'-0" 10'-4"
3'-9" 8'-0" 6'-6" 4'-2"
2'-9" 2'-9"
4'-3"
4'-11"
2'-0" 1'-9" 6'-8" 1'-6" 6'-9"
2'-9" 3'-2"
-1'-10 3/8"
-1'-10 3/8"
-1'-10 3/8"
4'-8"
8'-8"
4'-6"
1 A
2 B
3 4
D
03.01 03.01
02.31 03.01
-0'-4 5/8"
02.43 0'-0"
0'-0"
0'-0"
0'-0"
0'-0"
9'-4 3/4"
21'-4 5/8" 10'-8 5/8"
38'-4 3/8"
5'-6" 7'-5"
7'-0"
7'-4"
11'-6"
5'-6" 8'-11" 6'-2" 6'-10"
7'-4"
11'-6"
7'-9"
5'-6"
3'-11"
6'-2" 13'-6" 13'-6" 6'-5"
1'-0"
10.05 LEGEND
GENERAL NOTES
6" HIGH CONCRETE CURB, U.N.O.
4" HIGH EQUIPMENT PAD, COORDINATE FINAL SIZE
OF PAD WITH EQUIPMENT PER STRUCTURAL
1. SLAB PLANS INDICATE WHICH WALLS REQUIRE CURBS. CURB WIDTH TO MATCH WALL TYPE DETAILS, U.N.U. REFER TO PARTITION LAYOUT ON FLOOR PLANS AND DETAILS.
2. EDGE OF SLAB ALIGNS TO FACE OF CMU WALLS.
3. ALL SPOT ELEVATIONS ARE RELATIVE TO F.F. SEE SHEETS C5 AND C6 GRADING PLANS FOR FINISH FLOOR LEVELS AT SLAB ON GRADE.
4. SEE CIVIL SHEETS C5 AND C6 GRADING PLANS FOR SITE PAVING ELEVATIONS.
5. SEE LANDSCAPE SHEETS FOR PAVING LAYOUT.
6. DIMENSIONS OF FLOOR DRAIN LOCATIONS ARE TAKEN FROM CENTERLINE OF DRAIN U.N.O.
7. MEDIUM SANDBLAST FINISH AT EXTERIOR CURBS AT EXPOSED FACES.
8. CONTRACTOR TO COORDINATE EDGE OF SLAB PLANS WITH STRUCTURAL FOUNDATION AND FRAMING PLANS.
9. CONTRACTOR SHALL COORDINATE BLOCKOUTS IN CONCRETE CURBS FOR PLUMBING FIXTURES.
10. CONTRACTOR SHALL CONFIRM ALL EQUIPMENT PLATFORM / HOUSEKEEPING
PAD DIMENSION REQUIREMENTS AND SHAFT OPENINGS WITH MANUFACTURER
REQUIREMENTS, MECHANICAL DRAWINGS, AND REVIEWED SUBMITTALS AND ADJUST ACCORDINATLY.
CONCRETE SLAB ON GRADE
DEPRESSED CONCRETE SLAB, DEPTH OF
DEPRESSION AS INDICATED ON PLAN
SPOT ELEVATION
SLOPE DIRECTION - SLOPE TO
BE 2% MAX PER CBC 11B -403.3
NEW CMU WALL CONSTRUCTION
EXISTING CMU WALLS
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
FIRST FLOOR EDGE
OF SLAB PLAN -
BLDG A & B
A2.11
MD
MONROE ST. POOL REPLACEMENT
FIRST FLOOR EDGE OF SLAB PLAN - BLDG A & B
KEYNOTE LEGEND
02.31 EXISTING CONCRETE SLAB ON GRADE
02.43 EXISTING CONCRETE SLAB
03.01 NEW CONCRETE SLAB PER STRUCTURAL
10.05 SHADE STRUCTURE: SEE SHADE CONSULTANT SHEETS. SHADE CANOPY ENGINEERING IS A DEFERRED SUBMITTAL.
1/8" = 1' -0"
A2.11 11 FIRST FLOOR EDGE OF SLAB PLAN - BLDG B
1/8" = 1' -0"
A2.11 04 FIRST FLOOR EDGE OF SLAB PLAN - BLDG A
KEYPLAN
A
B
18 203
08/09/2024
1 A
2 BC
3 4
D
LOBBY
01 STAFF
LOUNGE
03 MULTI
PURPOSE
ROOM
14 TELEPHONE
15 ADMIN
07 OFFICE
07A
STAFF
SHOWER
03B
STAFF
RR
03A
WOMEN'S
CHANGING/
LOCKERS
10 MEN'S
RESTROOM
04 STORAGE
09A
WOMEN'S
SHOWER
11 WOMEN'S
RESTROOM
09 MEN'S
SHOWER
06 MEN'S
CHANGING/
LOCKERS
05 CORRIDOR
08 CORRIDOR
02 STORAGE
04A
ELEC.
14A
EXTERIOR
STORAGE
18 FIRST
AID
16 EQUIPMENT
STORAGE
17 CPT 1 CPT 1
T2
T2
B1
P1
B1
P1
P3 P3
P3
B2
P1
P3 B2
P1
P1
P1
P1
A4.01
13 A4.01
06 A4.03
06 A4.02
06 A4.04
06 P1
CONC-1
A4.02
05 CONC -1
CONC -1
5 6
7 F E
POOL
PUMP
ROOM
22 ELECTRICAL
21 STORAGE
19 CORRIDOR/
LOCKERS
20 FAMILY
RESTROOM/
SHOWER
20C
FAMILY
RESTROOM/
SHOWER
20D
FAMILY
RESTROOM/
SHOWER
20A
FAMILY
RESTROOM/
SHOWER
20B
CHEMICAL
ROOM
24 CHEMICAL
ROOM
25 BACKWASH
22A
PUMP
PIT
22B
CONC-1
CONC-1 CONC-1
CONC-1
CONC-1
T2
A4.06
06 LEGEND
GENERAL NOTES
ALIGN FINISHES
WALL ACCENT FINISH TAG
FINISH TAG
NEW BUILT-IN CASEWORK
1. TYPICAL FINISHES TO BE (P -1) AND (B -1) THROUGHOUT U.N.O.
2. FOR TYPICAL WALL BASE DETAILS REF: 07/A9.12
3. ALL EXPOSED CEILINGS, INCLUDING BEAMS, JOISTS, PLYWOOD SHEATHING, MECHANICAL SYSTEMS, SPRINKLERS, ELECTRICAL TO BE PAINTED, U.N.O.
REFER TO REFLECTED CEILING PLANS A2.31 FOR ADDITIONAL INFORMATION.
4. PAINT ALL ACCESS PANELS TO MATCH THE SURFACE THEY OCCUR ON, TYP.
5. TYPICAL FLOOR COVERING TRANSITIONS IS AT THE CENTERLINE OF THE DOOR
OR AT THE CENTERLINE OF THE OPENING WHERE NO DOOR IS PRESENT, U.N.O. PROVIDE FLUSH TRANSITIONS AS MUCH AS POSSIBLE, REF: 01/A9.12
6. "LOW SHEEN" PAINT FINISH TYPICAL THROUGHOUT, "SEMI -GLOSS" FINISH AT ALL RESTROOMS AND OTHER WET LOCATIONS, "FLAT" FINISH AT ALL CEILINGS WHERE CEILING OCCURS.
7. REFER TO INTERIOR ELEVATIONS FOR CABINET FINISHES.
8. REFER TO INTERIOR ELEVATIONS FOR ADDITIONAL WALL FINISHES.
9. FURNITURE NOT IN SCOPE.
10. ALL PLYWOOD AND WOOD BLOCKING SHALL BE FIRE TREATED PER TYPE V -B.
FLOORING TRANSITION, SEE 01/A9.12
XX
XX
*REFERENCE FINISH SCHEDULE ON SHEET A6.31
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
FIRST FLOOR
FINISHES PLAN -
BLDG A & B
A2.21
MD
MONROE ST. POOL REPLACEMENT
FIRST FLOOR FINISHES PLAN - BLDG A & B
1/8" = 1' -0"
A2.21 04 FIRST FLOOR FINISHES PLAN - BLDG A
KEYNOTE LEGEND
1/8" = 1' -0"
A2.21 11 FIRST FLOOR FINISHES PLAN - BLDG B
KEYPLAN
A
B
19 203
08/09/2024
WP
WP
F F
M
M
M
LED LED LED LED LED
OS
OS
OS OS
OS
OS
OS
OS
OS OS
OS
OS
OS
M M
M
M
M
M
M
M
WP
WP
J
J
J J
OS
OS
OS
OS
OS
OS
OS
OS
LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED
LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED
LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED J
LED LED LED
LED LED LED LED LED LED LED LED LED LED LED LED LED
LED LED LED LED LED LED LED LED
LED LED LED LED LED LED LED LED LED LED LED LED LED
M
M
LED LED LED LED LED LED LED LED LED LED LED LED LED LED
RDCL RDCL
WP
OS
OS
OS
OS
WP
WP
M
M M
M
J
M
M
J
J
J
M
1 A
06 A3.11
13 A3.11
2 BC
3 4
D
04 A3.11
09.02 09.02
09.02 09.02
LOBBY
01 MULTI
PURPOSE
ROOM
14 STAFF
RR
03A
STAFF
SHOWER
03B
WOMEN'S
CHANGING/
LOCKERS
10 WOMEN'S
RESTROOM
09 CORRIDOR
08 CORRIDOR
02 STORAGE
04A
STORAGE
09A
ELEC.
14A
05 A3.11
09 A3.11
A4.03
10 A4.04
13 A4.05
10 A4.01
19 8' - 6"
GYP-1
8' - 6"
ACT-1
8' - 6"
ACT-1
8' - 6"
GYP-1
O.T.S
TYP.
26.07 TYP.
26.04 8' - 6"
ACT-1
26.06 TYP.
26.05 TYP.
26.08 MEN'S
CHANGING/
LOCKERS
05 STAFF
LOUNGE
03 8' - 6"
ACT-1
O.T.S.
TYP.
26.03 MEN'S
SHOWER
06 MEN'S
RESTROOM
04 TYP.
26.02 FIRST
AID
16 O.T.S
EQUIPMENT
STORAGE
17 26.06
EXTERIOR
STORAGE
18 10.05
5 6
7 F E
06 A3.12
13 A3.12
TYP.
09.02 11
A3.12
04 A3.12
12 A3.12
A4.06
12 O.T.S.
O.T.S.
O.T.S.
8' - 0"
GYP-1
8' - 0"
GYP-1
8' - 0"
GYP-1
TYP.
26.07 TYP.
26.02 TYP.
26.02 TYP.
26.07 LEGEND
GENERAL NOTES
GYP -1
FRAMED GYPSUM BOARD CEILING
SEE DETAILS ON A9 SERIES
ACT -1
2'X4' ACOUSTIC CEILING TILE
DUNE TEGUALR, 9/16" SILHOUETTE GRID
SEE DETAILS ON A9 SERIES
GYP -3
FRAMED MOISTURE -RESISTANT GYP BD CEILING,
SEE DETAILS ON A9 SERIES
EXIT SIGN
CEILING TYPE
CEIILING ACCESS PANEL
1. ALL GYPSUM BOARD CEILINGS AND SOFFITS TO BE PAIN TED (P-1), U.N.O.
2. ALL EXPOSED CEILINGS, INCLUDING BEAMS, JOISTS, M ECHANICAL SYSTEMS, SPRINKLERS, ELECTRICAL TO BE PAINTED, U.N.O. SEE RECLECTED CEILING PLANS ADDITIONAL INFORMATION.
3. ALL GYPSUM BOARD EXPOSED TO VIEW SHALL HAVE LEVE L #4 FINISH, U.N.O.
4. PROVIDE ACCESS PANELS IN ENCLOSED AREAS ABOVE GY PSUM BOARD CEILINGS. PAINT TO MATCH CEILING FINISH, U.N.O.
5. SINGLE LIGHT FIXTURES TO BE CENTERED IN THE ROOM OR SOFFIT, U.N.O.
6. FOR FIXTURE INFORMATION, REFER TO ELECTRICAL DRA WINGS.
7. ALL LIGHT FIXTURE DIMENSIONS ARE TO CENTERLINE O F FIXTURE, OR GROUP OF FIXTURES, U.N.O.
8. CONTRACTOR TO COORDINATE DUCTS, CONDUIT, FINAL LOCATIONS AND HEIGHTS.
9. ALL PLYWOOD AND WOOD BLOCKING SHALL BE FIRE TREA TED PER TYPE V-B CONSTRUCTION.
10. ALL WALL AND CEILING FINISHES SHALL COMPLY WITH TABLE 803.13 CBC 2022, FOR THE MAXIMUM FLAME SPREAD AND SMOKE DENSITY.
11. CEILINGS SHALL BE INSTALLED TO MEET THE MINIMUM ASCE 7-16 SECTION 13.5.6
INDICATES OPEN TO
STRUCTURE CEILING.
PAINT (P -1) U.N.O.
O.T.S.
OCCUPANCY SENSOR
WiFi ACCESS POINT
X
X' -X" CEILING HEIGHT, SEE PLAN
OS WAP
J JUNCTION BOX,
PER ELECTRICAL
DRAWINGS
MECHANICAL
EXHAUST GRILLES
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
FIRST FLOOR
REFLECTED
CEILING PLAN -
BLDG A & B
A2.31
MD
MONROE ST. POOL REPLACEMENT
FIRST FLOOR REFLECTED CEILING PLAN - BLDG A & B
1/8" = 1' -0"
A2.31 04 REFLECTED CEILING PLAN - BLDG A
KEYNOTE LEGEND
09.02 NEW GYP CEILING WITH NEW LIGHTING
10.05 SHADE STRUCTURE: SEE SHADE CONSULTANT SHEETS. SHADE CANOPY ENGINEERING IS A DEFERRED SUBMITTAL.
26.02 RECESSED SQUARE DOWNLIGHT, PER ELECTRICAL DRAW INGS
26.03 RECESSED LINEAR LIGHT FIXTURE, PER ELECTRICAL DRAWINGS
26.04 2'X2' RECESSED BASKET LIGHT FIXTURE, PER ELEC TRICAL
DRAWINGS
26.05 LED TAPE, PER ELECTRICAL DRAWINGS
26.06 PENDANT LINEAR LIGHT FIXTURE, PER ELECTRICAL D RAWINGS
26.07 PENDANT STRIP LIGHT FIXTURE, PER ELECTRICAL DR AWINGS
26.08 SURFACE MOUNTED LINEAR WALL WASH LIGHT FIXTURE , PER
ELECTRICAL DRAWINGS
1/8" = 1' -0"
A2.31 11 REFLECTED CEILING PLAN - BLDG B
KEYPLAN
A
B
20 203
08/09/2024
203
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
1 TOP OF BLOCK WING
WALLS - BLDG A
17'-2"
06 A3.11
13 A3.11
2 3 4
05.03 03.03
08.06 EQ EQ EQ EQ
04 A8.12
14 A8.12
14 A8.12
9'-10"
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
A
TOP OF BLOCK WING
WALLS - BLDG A
17'-2"
BCD 04
A3.11
08.06 05
A3.11
09 A3.11
07 A3.21
04.01 03
A8.12
02 A8.12
05 A8.12
04 A8.12
10 L5.12
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
A
TOP OF BLOCK WING
WALLS - BLDG A
17'-2"
B C D04
A3.11
05 A3.11
09 A3.11
07 A3.21
04.01 04
A8.12
TYP.
05 A8.12
08 A8.12
10 A8.12
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
1 TOP OF BLOCK WING
WALLS - BLDG A
17'-2"
06 A3.11
13 A3.11
234
05.03 22.05 08.02
04 A8.12
TYP.
9'-6"
08 A8.12
10 A8.12
09 A8.12 TYP.
05 A9.42
05 A9.42
TYP.
40"
TYP.
78"
TYP.
28"
26" 32"
22"
01 A8.12
04 A8.12
02 A8.12
03 A8.12
08 A8.12
02 A8.12
03 A8.12
04 L5.12
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
06 A3.11
234
T4
T3
08.08 02.46 08.01 08.01 08.08
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
EXTERIOR
ELEVATIONS - BLDG
A
A3.01
MD
MONROE ST. POOL REPLACEMENT
EXTERIOR ELEVATIONS - BLDG A
1/8" = 1' -0"
A3.01 13 EXT ELEVATION - EAST
1/8" = 1' -0"
A3.01 05 EXT ELEVATION - SOUTH
1/8" = 1' -0"
A3.01 06 EXT ELEVATION - NORTH
1/8" = 1' -0"
A3.01 12 EXT ELEVATION - OVERALL WEST
KEYNOTE LEGEND
02.46 EXISTING HI-LOW ACCESSIBLE DRINKING FOUNTAIN T O BE REMOVED.
03.03 NEW CMU WALLS TO MATCH EXISTING CMU CONSTRUCTI ON
04.01 EXISTING CMU, CLEANED, PATCHED, AND PAINTED
05.03 NEW MECHANICAL SCREEN SYSTEM
08.01 NEW HM WINDOW IN DEMOLISHED DOOR OPENING
08.02 NEW HM WINDOW IN NEW CMU WALL
08.06 NEW STOREFRONT GLAZING
08.08 NEW HM WINDOW IN EXISTING OPENING
22.05 NEW HI-LOW ACCESSIBLE DRINKING FOUNTAIN/ BOTTL E FILLING
STATION
1/8" = 1' -0"
A3.01 04 EXT ELEVATION - UPPER WEST
21 203
08/09/2024
203
FE 05
A3.12
TOP BLDG B
13'-0"
04 A3.12
01 - 206.30 - BLDG B
-2'-2 3/8"
2'-0"
17'-2"
F E05
A3.12
TOP BLDG B
13'-0"
04 A3.12
01 - 207.93
-0'-4 5/8"
2'-0"
567 06
A3.12
13 A3.12
TOP BLDG B
13'-0"
22.05 11
A3.12
12 A3.12
01 - 206.30 - BLDG B
-2'-2 3/8"
01 - 207.93
-0'-4 5/8"
2'-0"
5'-4"
4'-8"
17'-2"
5 6 706
A3.12
13 A3.12
TOP BLDG B
13'-0"
11 A3.12
12 A3.12
01 - 207.93
-0'-4 5/8"
2'-0"
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
EXTERIOR
ELEVATIONS - BLDG
B
A3.02
MD
MONROE ST. POOL REPLACEMENT
EXTERIOR ELEVATIONS - BLDG B
KEYNOTE LEGEND
22.05 NEW HI-LOW ACCESSIBLE DRINKING FOUNTAIN/ BOTTL E FILLING
STATION
1/8" = 1' -0"
A3.02 05 ELEVATION - NORTH
1/8" = 1' -0"
A3.02 11 ELEVATION - SOUTH
1/8" = 1' -0"
A3.02 04 ELEVATION - WEST
1/8" = 1' -0"
A3.02 12 ELEVATION - EAST
22 203
08/09/2024
203
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
A B C D04
A3.11
A3.20
14 A3.23
11 05
A3.11
07 A3.21
LOBBY
01 CIRCULATION
01A
ADMIN
07 OFFICE
07A
TOP OF BLOCK EAST -
BLDG A
10'-6"
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
B C D04
A3.11
A3.20
04 A3.20
11 09
A3.11
A3.20
08 WOMEN'S
RESTROOM
09 WOMEN'S
CHANGING/
LOCKERS
10 FIRST
AID
16 TOP OF BLOCK EAST -
BLDG A
10'-6"
01 - FLOOR
0'-0"
1 TOP OF BLOCK WING
WALLS - BLDG A
17'-2"
06 A3.11
13 A3.11
2 3 4
A3.24
2 01 - 207.93
-0'-4 5/8"
WOMEN'S
RESTROOM
09 EXTERIOR
STORAGE
18 CORRIDOR
08 ADMIN
07 STAFF
SHOWER
03B
STAFF
RR
03A
MEN'S
RESTROOM
04 TOP OF BLOCK EAST -
BLDG A
10'-6"
A3.22
11 Sim
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
06 A3.11
23 A3.21
04 A3.21
11 LOBBY
01 TOP OF BLOCK EAST -
BLDG A
10'-6"
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
1 13
A3.11
A3.22
04 A3.24
1 FIRST
AID
16 EQUIPMENT
STORAGE
17 EXTERIOR
STORAGE
18 TOP OF BLOCK EAST -
BLDG A
10'-6"
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
BUILDING
SECTIONS BLDG A
A3.11
MD
MONROE ST. POOL REPLACEMENT
BUILDING SECTIONS BLDG A
1/8" = 1' -0"
A3.11 06 EAST-WEST SECTION - BUILDING A
1/8" = 1' -0"
A3.11 13 EAST-WEST SECTION 2 - BUILDING A
1/8" = 1' -0"
A3.11 04 NORTH-SOUTH SECTION - BUILDING A
1/8" = 1' -0"
A3.11 05 NORTH-SOUTH SECTION - BLDG A
LOBBY
1/8" = 1' -0"
A3.11 09 NORTH-SOUTH SECTION - BLDG A
STORAGE
23 203
08/09/2024
203
F E05
A3.12
TOP BLDG B
13'-0"
04 A3.12 A3.26
05 A3.26
14 A3.26
11 01 - 207.93
-0'-4 5/8"
CORRIDOR/
LOCKERS
20 ELECTRICAL
21 5 6 706
A3.12
13 A3.12
TOP BLDG B
13'-0"
12 A3.12
01 - 206.30 - BLDG B
-2'-2 3/8"
01 - 207.93
-0'-4 5/8"
A3.26
04 FAMILY
RESTROOM/
SHOWER
20E
CORRIDOR/
LOCKERS
20 FAMILY
RESTROOM/
SHOWER
20B
POOL
PUMP
ROOM
22 F E05
A3.12
TOP BLDG B
13'-0"
04 A3.12
01 - 207.93
-0'-4 5/8"
ELECTRICAL
21 FAMILY
RESTROOM/
SHOWER
20C
FAMILY
RESTROOM/
SHOWER
20B
FAMILY
RESTROOM/
SHOWER
20A
5 6 706
A3.12
13 A3.12
TOP BLDG B
13'-0"
11 A3.12
12 A3.12
8'-0"
01 - 206.30 - BLDG B
-2'-2 3/8"
01 - 207.93
-0'-4 5/8"
8'-6"
FAMILY
RESTROOM/
SHOWER
20A
FAMILY
RESTROOM/
SHOWER
20D
POOL
PUMP
ROOM
22 F E
05 A3.12
TOP BLDG B
13'-0"
04 A3.12 A3.27
11 A3.27
04 01 - 206.30 - BLDG B
-2'-2 3/8"
POOL
PUMP
ROOM
22 FE 05
A3.12
TOP BLDG B
13'-0"
04 A3.12
01 - 206.30 - BLDG B
-2'-2 3/8"
CHEMICAL
ROOM
25 CHEMICAL
ROOM
24 POOL
PUMP
ROOM
22 ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
BUILDING
SECTIONS BLDG B
A3.12
MD
MONROE ST. POOL REPLACEMENT
BUILDING SECTIONS BLDG B
1/8" = 1' -0"
A3.12 06 WEST-EAST SECTION - BUILDING B
1/8" = 1' -0"
A3.12 05 NORTH-SOUTH SECTION - BUILDING B
1/8" = 1' -0"
A3.12 13 WEST-EAST SECTION 2 - BUILDING B
1/8" = 1' -0"
A3.12 04 NORTH-SOUTH SECTION 2 - BUILDING B
1/8" = 1' -0"
A3.12 12 WEST-EAST SECTION 3 - BUILDING B
1/8" = 1' -0"
A3.12 11 EAST-WEST SECTION - BUILDING B
24 203
08/09/2024
203
01 - FLOOR
0'-0"
D
A8.14
08 A8.14
03 A8.12
08 A8.12
10 03.01
03.03 07.03
05.04 08.02
FIRST
AID
16 TOP OF BLOCK EAST -
BLDG A
10'-6"
A8.22
05 A8.22
06 2'-8" 4'-8" 2" 3'-0"
A8.13
02 GENERAL NOTES
1. REFER TO FLOOR PLANS FOR OPENING DIMENSIONS AND LOCATIONS.
2. FOR VERTICAL CMU CONTROL & EXPANSION JOINT DETAILS, REF: 15/A8.13
3. STOREFRONT, AND DOOR FINISH TYPES AND COLORS PER OPENING TYPE SHEETS AND DOOR SCHEDULE AND.
4. PAINT ALL ELECTRICAL AND TECHNOLOGY DEVICES TO MATCH COLOR OF ADJACENT SURFACES. DO NOT PAINT FIRE ALARM DEVICES AND RECESSED HOSE BIBBS.
5. FOR EXTERIOR WALL PIPE PENETRATIONS AT CMU WALLS, SEE 04/A8.13.
6. SEE A9.0X SERIES FOR WALL TYPES
01 - FLOOR
0'-0"
B
03.01 04.01
07.03 02.45
WOMEN'S
RESTROOM
09 A8.22
14 TOP OF BLOCK EAST -
BLDG A
10'-6"
SIM. OPP.
05.03 (V.I.F.)
+/- 3'-9"
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
C
03.01 03.01
04.01 03.03
07.03 02.45
07.03 FIRST
AID
16 WOMEN'S
CHANGING/
LOCKERS
10 A8.22
14 TOP OF BLOCK EAST -
BLDG A
10'-6"
05.03 (V.I.F.)
+/- 4'-4 1/4"
A8.22
06 A8.22
05 A8.13
02 SIM. OPP.
07.05 01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
A
8'-6"
A8.12
16 A8.12
15 A8.13
11 A8.22
02 02.31
02.44 08.06
05.09 LOBBY
01 05.04
02.45 4'-0"
EXISTING HEAVY TIMBER BEAM
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
WALL SECTIONS
A3.20
MD
MONROE ST. POOL REPLACEMENT
WALL SECTIONS
KEYNOTE LEGEND
02.31 EXISTING CONCRETE SLAB ON GRADE
02.44 EXISTING CMU
02.45 EXISTING ROOF STRUCTURE
03.01 NEW CONCRETE SLAB PER STRUCTURAL
03.03 NEW CMU WALLS TO MATCH EXISTING CMU CONSTRUCTI ON
04.01 EXISTING CMU, CLEANED, PATCHED, AND PAINTED
05.03 NEW MECHANICAL SCREEN SYSTEM
05.04 PERFORATED METAL SCREEN WITH GRAPHIC INCORPORA TED INTO DESIGN, IMAGE TBD BY ARCHITECT.
05.09 STEEL FRAMED, COMPOSITE ALUMINUM PANEL ENTRY P ORTAL
07.03 SINGLE PLY ROOFING SYSTEM
07.05 ROOF TO WALL JOINT TRANSITION. FULL LENGTH OF WALL AT NEW ADDITION. CONSTRUCTION SPECIALTIES SC-800 JOINT. SEE
04/A8.21.
08.02 NEW HM WINDOW IN NEW CMU WALL
08.06 NEW STOREFRONT GLAZING
1" = 1' -0"
A3.20 04 WALL SECTION THROUGH NEW
ADDITON - BUILDING A
1" = 1' -0"
A3.20 11 WALL SECTION THROUGH
BUILDING A RESTROOM
1" = 1' -0"
A3.20 08 WALL SECTION THROUGH NEW
ADDITION & EXISTING - BUILDING A
1" = 1' -0"
A3.20 14 EAST-WEST SECTION - BUILDING A
25 203
08/09/2024
203
GENERAL NOTES
1. REFER TO FLOOR PLANS FOR OPENING DIMENSIONS AND LOCATIONS.
2. FOR VERTICAL CMU CONTROL & EXPANSION JOINT DETAILS, REF: 15/A8.13
3. STOREFRONT, AND DOOR FINISH TYPES AND COLORS PER OPENING TYPE SHEETS AND DOOR SCHEDULE AND.
4. PAINT ALL ELECTRICAL AND TECHNOLOGY DEVICES TO MATCH COLOR OF ADJACENT SURFACES. DO NOT PAINT FIRE ALARM DEVICES AND RECESSED HOSE BIBBS.
5. FOR EXTERIOR WALL PIPE PENETRATIONS AT CMU WALLS, SEE 04/A8.13.
6. SEE A9.0X SERIES FOR WALL TYPES
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
2 A8.14
11 A8.12
10 A8.12
09 A8.12
08 A8.22
02 LOBBY
01 02.43
08.06 05.04
EXISTING HEAVY
TIMBER BEAM
BEYOND
A8.22
02 SIM.
SIM.
06.01 07.03 07.03
A8.12
06 01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
3 A8.12
08 A8.12
09 A8.12
10 SIM. OPP.
SIM. OPP.
SIM. OPP.
02.31 05.04
A8.22
02 LOBBY
01 A8.12
10 EXISTING
HEAVY TIMBER
BEAM BEYOND
4'-0" 9" 8'-10" 3"
SIM.
SIM.
A8.22
02 SIM.
02.45 07.03 06.01
07.03 01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
2 A8.12
08 A8.12
09 A8.12
10 05.04
02.45 07.03
04.01 A8.22
03 A8.22
02 ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
WALL SECTIONS
A3.21
MD
MONROE ST. POOL REPLACEMENT
WALL SECTIONS
KEYNOTE LEGEND
02.31 EXISTING CONCRETE SLAB ON GRADE
02.43 EXISTING CONCRETE SLAB
02.45 EXISTING ROOF STRUCTURE
04.01 EXISTING CMU, CLEANED, PATCHED, AND PAINTED
05.04 PERFORATED METAL SCREEN WITH GRAPHIC INCORPORA TED INTO DESIGN, IMAGE TBD BY ARCHITECT.
06.01 WOOD FRAMING; SEE STRUCTURAL DET. 8/S6.81
07.03 SINGLE PLY ROOFING SYSTEM
08.06 NEW STOREFRONT GLAZING
1" = 1' -0"
A3.21 04 WALL SECTION THROUGH LOBBY -
BUILDING A
1" = 1' -0"
A3.21 11 WALL SECTION THROUGH LOBBY 3
- BUILDING A
1" = 1' -0"
A3.21 07 WALL SECTION THROUGH LOBBY 2
- BUILDING A
26 203
08/09/2024
203
GENERAL NOTES
1. REFER TO FLOOR PLANS FOR OPENING DIMENSIONS AND LOCATIONS.
2. FOR VERTICAL CMU CONTROL & EXPANSION JOINT DETAILS, REF: 15/A8.13
3. STOREFRONT, AND DOOR FINISH TYPES AND COLORS PER OPENING TYPE SHEETS AND DOOR SCHEDULE AND.
4. PAINT ALL ELECTRICAL AND TECHNOLOGY DEVICES TO MATCH COLOR OF ADJACENT SURFACES. DO NOT PAINT FIRE ALARM DEVICES AND RECESSED HOSE BIBBS.
5. FOR EXTERIOR WALL PIPE PENETRATIONS AT CMU WALLS, SEE 04/A8.13.
6. SEE A9.0X SERIES FOR WALL TYPES
01 - FLOOR
0'-0"
A8.14
03 A8.14
08 03.01
03.03 07.03 07.03
FIRST
AID
16 TOP OF BLOCK EAST -
BLDG A
10'-6"
3'-2" 4'-8" 2'-8"
A8.22
06 A8.22
05 01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
01 - 207.93
-0'-4 5/8"
02.31 03.01
04.01 MULTI
PURPOSE
ROOM
14 OPP.
A9.11
1 ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
WALL SECTIONS
A3.22
MD
MONROE ST. POOL REPLACEMENT
WALL SECTIONS
KEYNOTE LEGEND
02.31 EXISTING CONCRETE SLAB ON GRADE
03.01 NEW CONCRETE SLAB PER STRUCTURAL
03.03 NEW CMU WALLS TO MATCH EXISTING CMU CONSTRUCTI ON
04.01 EXISTING CMU, CLEANED, PATCHED, AND PAINTED
07.03 SINGLE PLY ROOFING SYSTEM
1" = 1' -0"
A3.22 04 WALL SECTION THROUGH NEW
ADDITION - BUILDING A
1" = 1' -0"
A3.22 11 WALL SECTION THROUGH MPR -
BUILDING A
27 203
08/09/2024
203
GENERAL NOTES
1. REFER TO FLOOR PLANS FOR OPENING DIMENSIONS AND LOCATIONS.
2. FOR VERTICAL CMU CONTROL & EXPANSION JOINT DETAILS, REF: 15/A8.13
3. STOREFRONT, AND DOOR FINISH TYPES AND COLORS PER OPENING TYPE SHEETS AND DOOR SCHEDULE AND.
4. PAINT ALL ELECTRICAL AND TECHNOLOGY DEVICES TO MATCH COLOR OF ADJACENT SURFACES. DO NOT PAINT FIRE ALARM DEVICES AND RECESSED HOSE BIBBS.
5. FOR EXTERIOR WALL PIPE PENETRATIONS AT CMU WALLS, SEE 04/A8.13.
6. SEE A9.0X SERIES FOR WALL TYPES
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
D
0'-4"
A8.12
08 A8.12
10 05.06
TOP OF BLOCK EAST -
BLDG A
10'-6"
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
C D
A8.12
08 A8.12
10 05.03
TOP OF BLOCK EAST -
BLDG A
10'-6"
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
C
03.01 04.01
05.06 05.03
07.03 02.45 TOP OF BLOCK EAST -
BLDG A
10'-6"
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
WALL SECTIONS
A3.23
MD
MONROE ST. POOL REPLACEMENT
WALL SECTIONS
KEYNOTE LEGEND
02.45 EXISTING ROOF STRUCTURE
03.01 NEW CONCRETE SLAB PER STRUCTURAL
04.01 EXISTING CMU, CLEANED, PATCHED, AND PAINTED
05.03 NEW MECHANICAL SCREEN SYSTEM
05.06 STEEL FRAMED OVERHANG/ SUNSHADE
07.03 SINGLE PLY ROOFING SYSTEM
1" = 1' -0"
A3.23 11 EAST-WEST SECTION - BUILDING A
- Callout 2
1" = 1' -0"
A3.23 04 Section 11
1" = 1' -0"
A3.23 14 Section 10
28 203
08/09/2024
203
GENERAL NOTES
1. REFER TO FLOOR PLANS FOR OPENING DIMENSIONS AND LOCATIONS.
2. FOR VERTICAL CMU CONTROL & EXPANSION JOINT DETAILS, REF: 15/A8.13
3. STOREFRONT, AND DOOR FINISH TYPES AND COLORS PER OPENING TYPE SHEETS AND DOOR SCHEDULE AND.
4. PAINT ALL ELECTRICAL AND TECHNOLOGY DEVICES TO MATCH COLOR OF ADJACENT SURFACES. DO NOT PAINT FIRE ALARM DEVICES AND RECESSED HOSE BIBBS.
5. FOR EXTERIOR WALL PIPE PENETRATIONS AT CMU WALLS, SEE 04/A8.13.
6. SEE A9.0X SERIES FOR WALL TYPES
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
1 EQUIPMENT
STORAGE
17 03.03
03.01 07.03 TOP OF BLOCK EAST -
BLDG A
10'-6"
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
1 WOMEN'S
RESTROOM
09 EXTERIOR
STORAGE
18 03.01
03.03 04.01
02.45 07.03 TOP OF BLOCK EAST -
BLDG A
10'-6"
9'-10"
10.05 ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
WALL SECTIONS
A3.24
MD
MONROE ST. POOL REPLACEMENT
WALL SECTIONS
KEYNOTE LEGEND
02.45 EXISTING ROOF STRUCTURE
03.01 NEW CONCRETE SLAB PER STRUCTURAL
03.03 NEW CMU WALLS TO MATCH EXISTING CMU CONSTRUCTI ON
04.01 EXISTING CMU, CLEANED, PATCHED, AND PAINTED
07.03 SINGLE PLY ROOFING SYSTEM
10.05 SHADE STRUCTURE: SEE SHADE CONSULTANT SHEETS. SHADE CANOPY ENGINEERING IS A DEFERRED SUBMITTAL.
1/2" = 1' -0"
A3.24 1WALL SECTION THROUGH NEW OPEN AIR STORAGE - BUILDING A 1/2" = 1' -0"
A3.24 2WALL SECTION THROUGH NEW OPEN AIR STORAGE 2 - BUILDING A 29 203
08/09/2024
203
GENERAL NOTES
1. REFER TO FLOOR PLANS FOR OPENING DIMENSIONS AND LOCATIONS.
2. FOR VERTICAL CMU CONTROL & EXPANSION JOINT DETAILS, REF: 15/A8.13
3. STOREFRONT, AND DOOR FINISH TYPES AND COLORS PER OPENING TYPE SHEETS AND DOOR SCHEDULE AND.
4. PAINT ALL ELECTRICAL AND TECHNOLOGY DEVICES TO MATCH COLOR OF ADJACENT SURFACES. DO NOT PAINT FIRE ALARM DEVICES AND RECESSED HOSE BIBBS.
5. FOR EXTERIOR WALL PIPE PENETRATIONS AT CMU WALLS, SEE 04/A8.13.
6. SEE A9.0X SERIES FOR WALL TYPES TOP OF BLOCK - BLDG A 9'-10"
E
TOP BLDG B
13'-0"
01 - 207.93
-0'-4 5/8"
03.01 03.03
05.03 07.03
ELECTRICAL
21 TOP OF BLOCK EAST -
BLDG A
10'-6"
F
TOP BLDG B
13'-0"
01 - 207.93
-0'-4 5/8"
A8.14
06 A8.14
15 CORRIDOR/
LOCKERS
20 03.01
05.03 07.03
TOP OF BLOCK EAST -
BLDG A
10'-6"
TOP OF BLOCK - BLDG A
9'-10"
01 - 207.93
-0'-4 5/8"
03.01 07.03
CORRIDOR/
LOCKERS
20 TOP OF BLOCK EAST -
BLDG A
10'-6"
01 - FLOOR
0'-0"
TOP OF BLOCK - BLDG A
9'-10"
01 - 206.30 - BLDG B
-2'-2 3/8"
01 - 207.93
-0'-4 5/8"
POOL
PUMP
ROOM
22 TOP OF BLOCK EAST -
BLDG A
10'-6"
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
WALL SECTIONS
A3.26
MD
MONROE ST. POOL REPLACEMENT
WALL SECTIONS
KEYNOTE LEGEND
03.01 NEW CONCRETE SLAB PER STRUCTURAL
03.03 NEW CMU WALLS TO MATCH EXISTING CMU CONSTRUCTI ON
05.03 NEW MECHANICAL SCREEN SYSTEM
07.03 SINGLE PLY ROOFING SYSTEM
1" = 1' -0"
A3.26 05 WALL SECTION THROUGH
WEST-EAST - BUILDING B
1" = 1' -0"
A3.26 14 WEST-EAST SECTION - BUILDING B
- Callout 2
1" = 1' -0"
A3.26 11 WALL SECTION THROUGH
LOCKERS - BUILDING B
1" = 1' -0"
A3.26 04 NORTH-SOUTH SECTION -
BUILDING B - Callout 3
30 08/09/2024
203
203
GENERAL NOTES
1. REFER TO FLOOR PLANS FOR OPENING DIMENSIONS AND LOCATIONS.
2. FOR VERTICAL CMU CONTROL & EXPANSION JOINT DETAILS, REF: 15/A8.13
3. STOREFRONT, AND DOOR FINISH TYPES AND COLORS PER OPENING TYPE SHEETS AND DOOR SCHEDULE AND.
4. PAINT ALL ELECTRICAL AND TECHNOLOGY DEVICES TO MATCH COLOR OF ADJACENT SURFACES. DO NOT PAINT FIRE ALARM DEVICES AND RECESSED HOSE BIBBS.
5. FOR EXTERIOR WALL PIPE PENETRATIONS AT CMU WALLS, SEE 04/A8.13.
6. SEE A9.0X SERIES FOR WALL TYPES
F
TOP BLDG B
13'-0"
01 - 206.30 - BLDG B
-2'-2 3/8"
A8.21
15 POOL
PUMP
ROOM
22 TOP OF BLOCK EAST -
BLDG A
10'-6"
01 - 206.30 - BLDG B
-2'-2 3/8"
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
WALL SECTIONS
A3.27
MD
MONROE ST. POOL REPLACEMENT
WALL SECTIONS
KEYNOTE LEGEND
3/4" = 1' -0"
A3.27 11 Section 8 - Callout 1
1" = 1' -0"
A3.27 04 Section 8 - Callout 2
31 203
08/09/2024
203
30" X 48"
CLR. FLR.
SPACE
MAX.
2'-10" 2'-2" 2'-2"
T4
PL-1
B1
12.04 F.E.
(3) EQ.
33 155
36 24
302
28 14
26 33
101
14 24
CLR.
16"
PL-1
33 101
18 24
22.00 QTZ-2
P1
B1
06.01 16
A9.21
13 A9.31
C
3 A4.01
04 08
SA6
SF0
SB6
SB6
STAFF
LOUNGE
03 LVT 1
B1
P1
P2
2'-0"
LOCKERS
A
2 B
3 A4.01 05
14 A4.05
LVT 1
LOBBY
01 B1
P1
A8.12
14 5'-0"
101
4'-0" CLR.
9'-1"
2'-0"
ALIGN
4'-10"
A
2 B
3 9' - 0"
ACT-1
8' - 6"
GYP-1
P1
LOBBY
01 16
A9.21
16 A9.21
8' - 6"
GYP-111
A9.21
P2
OPEN TO
BEYOND
P2
23 A9.32
QTZ-1 24
A9.32
QTZ -1
3'-5"
2'-6"
FINISHED EDGE
QTZ -1
FINISHED EDGE
QTZ -1
QTZ-1
QTZ-1
WALL GRAPHIC
B1 1'-0"
WC -1
LEGEND
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.01.
STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.01. REFER TO S0.91 FOR INTERIOR STUD WALL SCHEDULE
LINE OF ELEMENT ABOVE
HATCH INDICATES NEW BUILT -IN CASEWORK
GENERAL NOTES
301
36 33
24 CABINET DESIGN SERIES NUMBERING SYSTEM PER
ARCHITECTURAL WOODWORK STANDARDS
AWI CASEWORK NUMBER
CABINET WIDTH
CABINET HEIGHT
CABINET DEPTH
ALIGN FINISHES
XX
FINISH TAG REF: A6.31 FINISH SCHEDULE
EQUIPMENT TAG 1i
1. FOR FINISH & RESTROOM ACCESSORY SCHEDULES REF: A6.31
2. FOR TYPICAL WALL BASE DETAILS REF: 07/A9.12
3. ALL PLUMBING FIXTURES TO HAVE SOLID BLOCKING AS REQUIRED BY CODE.
4. FOR FIXTURE AND ACCESSORY MOUNTING HEIGHTS, REF: G0.32
5. PROVIDE 5/8" TYPE "X" WATER RESISTANT GYPSUM BOARD AT ALL RESTROOM WALLS NOT RECEIVING TILE. PAINT PER FINISH PLANS
6. PROVIDE CEMENTITIOUS TILE BACKER BOARD AT ALL TILED WALLS, TYP.
7. PROVIDE LOCALIZED SLAB DEPRESSION AT FLOOR DRAINS, REF: 7/A9.41
8. TYPICAL PAINT AT RESTROOMS TO BE "SEMI -GLOSS" FINISH.
9. REFER TO MANUFACTURER'S TOILET ACCESSORY INSTALLATION AND OTHER
MOUNTING INSTRUCTIONS AND PROVIDE WALL BACKING AND OTHER REQUIRED SUPPORT AS INDICATED.
10. REFER TO DETAIL 04/G0.32 FOR ACCESSIBLE STALL INFORMATION. AT ACCESSIBLE STALLS: TOILET PARTITION DOOR WIDTHS ARE TO BE 36" (34" MIN.
CLEAR REG'D) PARTITION STILE WIDTH SHALL NOT EXCEED 4". FLUSH VALVE TO BE LOCATED AT WIDE SIDE OF STALL SPACE.
11. FOR SIGNAGE DETAILS, SEE SHEET A10.01
12. ANY FURNITURE PROVIDED BY OWNER SHALL SHOW 5% OF SEATING WITH WHEELCHAIR ACCESS COMPLYING WITH CBC 11B -802.1.
GYP -1
FRAMED GYPSUM BOARD CEILING
SEE DETAILS ON SHEET A--
ACT -1
2'X4' ACOUSTIC CEILING TILE
DUNE TEGUALR, 9/16" SILHOUETTE GRID
SEE DETAIL ----
GYP -3 FRAMED MOISTURE -RESISTANT GYP BD CEILING,
SEE DETAILS ON SHEET A----
CEILING TYPE X
X' -X" CEILING HEIGHT, SEE PLAN
FINISHED EDGE F.E.
INDICATED ACCESSIBLE LOCKER
METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION
CMU WALL CONSTRUCTION
EXISTING STUD WALLS
EXISTING CMU WALLS
XX
XX
FLOOR FINISH
BASE FINISH
WALL FINISH
*REFERENCE FINISH SCHEDULE ON SHEET A6.31
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. T he
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
ENLARGED PLANS &
INTERIOR
ELEVATIONS
A4.01
MD
MONROE ST. POOL REPLACEMENT
ENLARGED PLANS & INTERIOR ELEVATIONS
KEYNOTE LEGEND
06.01 WOOD FRAMING; SEE STRUCTURAL DET. 8/S6.81
12.04 UNDER COUNTER REFRIGERATOR, OFOI
22.00 DIVISION 22: PLUMBING
23.04 MECHANICAL EQUIPMENT, PER MECHANICAL DRAWINGS
26.03 RECESSED LINEAR LIGHT FIXTURE, PER ELECTRICAL DRAWINGS 1/4" = 1' -0"
A4.01 04 STAFF LOUNGE KITCHEN
1/4" = 1' -0"
A4.01 08 INT ELEVATION - STAFF LOUNGE
STORAGE
1/4" = 1' -0"
A4.01 06 ENLARGED FLOOR PLAN 1- BLDG A
1/4" = 1' -0"
A4.01 13 ENLARGED FLOOR PLAN 2 - BLDG
A
1/4" = 1' -0"
A4.01 19 ENLARGED RCP 2 - BLDG A
1/4" = 1' -0"
A4.01 14 LOBBY RECEPTION
1/4" = 1' -0"
A4.01 05 LOBBY WALL GRAPHIC
1 2nd PLAN CHECK
SUBMITTAL
04/24/24
203
32 08/09/2024
203
BC
4 A4.02 09
SG2
SN6
SF0
SF0
MULTI
PURPOSE
ROOM
14 LVT 1
B1
P1
ELEC.
14A
CONC-1
P2 11
A3.22
5'-6" 5'-7"
1'-3"
2'-10" 2'-11" 2'-2"
QTZ-2QTZ-2
PL-1
PL-1302
27 14
26 12.04
33 155
30 24
33 101
15 24
33 102
24 24
CD
A4.02 08
FIRST
AID
16 LVT 1
B1
P1
P3
2'-10" 1'-8" 2'-2"
PL-1
QTZ-2QTZ-2 PL-1
P1
33 155
30 24
33 101
15 24
33 101
15 24
302
30 14
26 LEGEND
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.01.
STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.01. REFER TO S0.91 FOR INTERIOR STUD WALL SCHEDULE
LINE OF ELEMENT ABOVE
HATCH INDICATES NEW BUILT -IN CASEWORK
GENERAL NOTES
301
36 33
24 CABINET DESIGN SERIES NUMBERING SYSTEM PER
ARCHITECTURAL WOODWORK STANDARDS
AWI CASEWORK NUMBER
CABINET WIDTH
CABINET HEIGHT
CABINET DEPTH
ALIGN FINISHES
XX
FINISH TAG REF: A6.31 FINISH SCHEDULE
EQUIPMENT TAG 1i
1. FOR FINISH & RESTROOM ACCESSORY SCHEDULES REF: A6.31
2. FOR TYPICAL WALL BASE DETAILS REF: 07/A9.12
3. ALL PLUMBING FIXTURES TO HAVE SOLID BLOCKING AS REQUIRED BY CODE.
4. FOR FIXTURE AND ACCESSORY MOUNTING HEIGHTS, REF: G0.32
5. PROVIDE 5/8" TYPE "X" WATER RESISTANT GYPSUM BOARD AT ALL RESTROOM WALLS NOT RECEIVING TILE. PAINT PER FINISH PLANS
6. PROVIDE CEMENTITIOUS TILE BACKER BOARD AT ALL TILED WALLS, TYP.
7. PROVIDE LOCALIZED SLAB DEPRESSION AT FLOOR DRAINS, REF: 7/A9.41
8. TYPICAL PAINT AT RESTROOMS TO BE "SEMI -GLOSS" FINISH.
9. REFER TO MANUFACTURER'S TOILET ACCESSORY INSTALLATION AND OTHER
MOUNTING INSTRUCTIONS AND PROVIDE WALL BACKING AND OTHER REQUIRED SUPPORT AS INDICATED.
10. REFER TO DETAIL 04/G0.32 FOR ACCESSIBLE STALL INFORMATION. AT ACCESSIBLE STALLS: TOILET PARTITION DOOR WIDTHS ARE TO BE 36" (34" MIN.
CLEAR REG'D) PARTITION STILE WIDTH SHALL NOT EXCEED 4". FLUSH VALVE TO BE LOCATED AT WIDE SIDE OF STALL SPACE.
11. FOR SIGNAGE DETAILS, SEE SHEET A10.01
12. ANY FURNITURE PROVIDED BY OWNER SHALL SHOW 5% OF SEATING WITH WHEELCHAIR ACCESS COMPLYING WITH CBC 11B -802.1.
GYP -1
FRAMED GYPSUM BOARD CEILING
SEE DETAILS ON SHEET A--
ACT -1
2'X4' ACOUSTIC CEILING TILE
DUNE TEGUALR, 9/16" SILHOUETTE GRID
SEE DETAIL ----
GYP -3 FRAMED MOISTURE -RESISTANT GYP BD CEILING,
SEE DETAILS ON SHEET A----
CEILING TYPE X
X' -X" CEILING HEIGHT, SEE PLAN
FINISHED EDGE F.E.
INDICATED ACCESSIBLE LOCKER
METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION
CMU WALL CONSTRUCTION
EXISTING STUD WALLS
EXISTING CMU WALLS
XX
XX
FLOOR FINISH
BASE FINISH
WALL FINISH
*REFERENCE FINISH SCHEDULE ON SHEET A6.31
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. T he
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
ENLARGED PLANS &
INTERIOR
ELEVATIONS
A4.02
MD
MONROE ST. POOL REPLACEMENT
ENLARGED PLANS & INTERIOR ELEVATIONS
KEYNOTE LEGEND
12.04 UNDER COUNTER REFRIGERATOR, OFOI
23.02 MECHANICAL DUCTING, PER MECHANICAL DRAWINGS
1/4" = 1' -0"
A4.02 06 ENLARGED FLOOR PLAN 4 - BLDG A
1/4" = 1' -0"
A4.02 09 INT ELEVATION - MPR KITCHEN
1/4" = 1' -0"
A4.02 05 ENLARGED FLOOR PLAN 3 - BLDG
A
1/4" = 1' -0"
A4.02 08 INT ELEVATION - FIRST AID SINK
203
33 08/09/2024
203
BC
A4.03 05
A4.03
16 15
12 19
A4.03 14 08
11 04
09 SE4
SG4
SB6
SB6
SB6
SA6
SA6
SE4
SB6 MEN'S
RESTROOM
04 MEN'S
SHOWER
06 MEN'S
CHANGING/
LOCKERS
05 CORRIDOR
02 STORAGE
04A T1 T5
3'-0" 3'-0" 3'-0" 5'-1" 1'-11"
4'-10" 10" 7'-8" 9'-2"
1'-0" 3'-5" 3'-5" 5'-3" 13'-3" 1'-8"
7'-10" 3'-5" 3'-5" 7'-6"
13'-4" 3'-6"
4'-3" 2'-6" 2'-5" 5'-11" 5'-0"
4'-2" 1'-11"
3'-1" 3'-0" 3'-2" 2'-11"
BC
8' - 6"
GYP-2
6' - 6"
GYP-2
P1
MEN'S
RESTROOM
04 8' - 6"
GYP-1
P1
MEN'S
SHOWER
06 STORAGE
04A
MEN'S
CHANGING/
LOCKERS
05 8' - 6"
GYP-2
11 A9.21
11 A9.21
T4
T5
13 A9.31
10 A9.41
4"
T5 T3
T4
T4
T4
QTZ-1
QQ
1'-6"
4" 4'-0"
T5
T4
T3
T4
4'-0" 4"
QQ QQ QQ
SH-1 SH-1
T3
RR
T5
T4
T4
T3
4" 4'-0"
T4
QTZ-1
10 A9.41
QQ
OPEN TO
BEYOND
T4
T3
T5
QQ T4
T3
T5
SH-1
QQ QQ
4'-0" 4"
QQ QQ SS
SH-1SH-1
T5 T5
?
T4
LL
17 A9.42
2'-10"
40" MAX.
OPEN TO
BEYOND
LL LL
T4 T3
T5
PP
22"
17"
U-1 U-2 U-2
PP II
AA
11 A9.21
T4
T5
II
AA
CC
T3
T4
T5
SS
4" 4'-0"
T4
T5
OPEN TO
BEYOND
U-2
LEGEND
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.01.
STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.01. REFER TO S0.91 FOR INTERIOR STUD WALL SCHEDULE
LINE OF ELEMENT ABOVE
HATCH INDICATES NEW BUILT -IN CASEWORK
GENERAL NOTES
301
36 33
24 CABINET DESIGN SERIES NUMBERING SYSTEM PER
ARCHITECTURAL WOODWORK STANDARDS
AWI CASEWORK NUMBER
CABINET WIDTH
CABINET HEIGHT
CABINET DEPTH
ALIGN FINISHES
XX
FINISH TAG REF: A6.31 FINISH SCHEDULE
EQUIPMENT TAG 1i
1. FOR FINISH & RESTROOM ACCESSORY SCHEDULES REF: A6.31
2. FOR TYPICAL WALL BASE DETAILS REF: 07/A9.12
3. ALL PLUMBING FIXTURES TO HAVE SOLID BLOCKING AS REQUIRED BY CODE.
4. FOR FIXTURE AND ACCESSORY MOUNTING HEIGHTS, REF: G0.32
5. PROVIDE 5/8" TYPE "X" WATER RESISTANT GYPSUM BOARD AT ALL RESTROOM WALLS NOT RECEIVING TILE. PAINT PER FINISH PLANS
6. PROVIDE CEMENTITIOUS TILE BACKER BOARD AT ALL TILED WALLS, TYP.
7. PROVIDE LOCALIZED SLAB DEPRESSION AT FLOOR DRAINS, REF: 7/A9.41
8. TYPICAL PAINT AT RESTROOMS TO BE "SEMI -GLOSS" FINISH.
9. REFER TO MANUFACTURER'S TOILET ACCESSORY INSTALLATION AND OTHER
MOUNTING INSTRUCTIONS AND PROVIDE WALL BACKING AND OTHER REQUIRED SUPPORT AS INDICATED.
10. REFER TO DETAIL 04/G0.32 FOR ACCESSIBLE STALL INFORMATION. AT ACCESSIBLE STALLS: TOILET PARTITION DOOR WIDTHS ARE TO BE 36" (34" MIN.
CLEAR REG'D) PARTITION STILE WIDTH SHALL NOT EXCEED 4". FLUSH VALVE TO BE LOCATED AT WIDE SIDE OF STALL SPACE.
11. FOR SIGNAGE DETAILS, SEE SHEET A10.01
12. ANY FURNITURE PROVIDED BY OWNER SHALL SHOW 5% OF SEATING WITH WHEELCHAIR ACCESS COMPLYING WITH CBC 11B -802.1.
GYP -1
FRAMED GYPSUM BOARD CEILING
SEE DETAILS ON SHEET A--
ACT -1
2'X4' ACOUSTIC CEILING TILE
DUNE TEGUALR, 9/16" SILHOUETTE GRID
SEE DETAIL ----
GYP -3 FRAMED MOISTURE -RESISTANT GYP BD CEILING,
SEE DETAILS ON SHEET A----
CEILING TYPE X
X' -X" CEILING HEIGHT, SEE PLAN
FINISHED EDGE F.E.
INDICATED ACCESSIBLE LOCKER
METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION
CMU WALL CONSTRUCTION
EXISTING STUD WALLS
EXISTING CMU WALLS
XX
XX
FLOOR FINISH
BASE FINISH
WALL FINISH
*REFERENCE FINISH SCHEDULE ON SHEET A6.31
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. T he
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
ENLARGED
RESTROOM PLANS
& ELEVATIONS
A4.03
MD
MONROE ST. POOL REPLACEMENT
ENLARGED RESTROOM PLANS & ELEVATIONS
1/4" = 1' -0"
A4.03 06 MEN'S RESTROOM ENLARGED
FLOOR PLAN - BLDG A
1/4" = 1' -0"
A4.03 10 MEN'S RESTROOM RCP - BLDG A
1/4" = 1' -0"
A4.03 05 MEN'S LOCKERS
1/4" = 1' -0"
A4.03 16 MEN'S SHOWER NORTH
1/4" = 1' -0"
A4.03 19 MEN'S SHOWER EAST
1/4" = 1' -0"
A4.03 12 MEN'S SHOWER SOUTH
1/4" = 1' -0"
A4.03 15 MEN'S SHOWER WEST
1/4" = 1' -0"
A4.03 14 MEN'S RESTROOM SINK
1/4" = 1' -0"
A4.03 08 MEN'S RESTROOM
1/4" = 1' -0"
A4.03 04 MEN'S ADA STALL
1/4" = 1' -0"
A4.03 09 MEN'S CHANGING AREA
1/4" = 1' -0"
A4.03 11 MEN'S RESTROOM EXIT
KEYNOTE LEGEND
23.02 MECHANICAL DUCTING, PER MECHANICAL DRAWINGS
26.08 SURFACE MOUNTED LINEAR WALL WASH LIGHT FIXTURE , PER
ELECTRICAL DRAWINGS
203
34 08/09/2024
203
1 BC
A4.04 04
A4.04
12 A4.04
08 11
14 17
05 09
SB6
SG4
SE4
SB6
SA6
SA6
SE4
SG4
WOMEN'S
CHANGING/
LOCKERS
10 STORAGE
09A
WOMEN'S
SHOWER
11 WOMEN'S
RESTROOM
09 CORRIDOR
08 T1
T5
SB6
SB6
SG4
SE4
SB4
SB4
SB4
SB6
SB6
A4.03 05 Sim
104 104A
5'-1" 3'-0" 3'-0" 3'-0" 1'-11"
1'-3" 3'-5" 3'-5" 5'-1" 13'-5" 1'-4"
4'-10" 10" 7'-8" 9'-2"
6'-4" 4'-3" 4'-11" 5'-6" 5'-2" 1'-4"
4'-6"
3'-5" 4'-2" 3'-5" 3'-5" 7'-10"
3'-0" 3'-0" 3'-0" 3'-7" 4'-10"
3'-9"
1 BC
8' - 6"
GYP-2
6' - 6"
GYP-2
8' - 6"
GYP-1
WOMEN'S
RESTROOM
09 WOMEN'S
CHANGING/
LOCKERS
10 02.19
26.05 11
A9.21
8' - 6"
GYP-2
STORAGE
09A
T4 T5 QTZ-2 17
A9.42
PL -2
T3
T3
LL
3'-4"
2'-10"
4"
11 A9.21
L-1
LL LL
T4
T4
T4 T5 T5
II
AA
T4
4" 4'-0"
T3
T5
AA
T4
T3 T5 CC
T4
T3 T5
RR
SH-1 SH-1
T4
T5
SH-1 QQ
T3
T4
QQ QQ QQ
SH-1SH-1
T3
T4
T5
T4
T3 T5
QQ
LEGEND
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.01.
STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.01. REFER TO S0.91 FOR INTERIOR STUD WALL SCHEDULE
LINE OF ELEMENT ABOVE
HATCH INDICATES NEW BUILT -IN CASEWORK
GENERAL NOTES
301
36 33
24 CABINET DESIGN SERIES NUMBERING SYSTEM PER
ARCHITECTURAL WOODWORK STANDARDS
AWI CASEWORK NUMBER
CABINET WIDTH
CABINET HEIGHT
CABINET DEPTH
ALIGN FINISHES
XX
FINISH TAG REF: A6.31 FINISH SCHEDULE
EQUIPMENT TAG 1i
1. FOR FINISH & RESTROOM ACCESSORY SCHEDULES REF: A6.31
2. FOR TYPICAL WALL BASE DETAILS REF: 07/A9.12
3. ALL PLUMBING FIXTURES TO HAVE SOLID BLOCKING AS REQUIRED BY CODE.
4. FOR FIXTURE AND ACCESSORY MOUNTING HEIGHTS, REF: G0.32
5. PROVIDE 5/8" TYPE "X" WATER RESISTANT GYPSUM BOARD AT ALL RESTROOM WALLS NOT RECEIVING TILE. PAINT PER FINISH PLANS
6. PROVIDE CEMENTITIOUS TILE BACKER BOARD AT ALL TILED WALLS, TYP.
7. PROVIDE LOCALIZED SLAB DEPRESSION AT FLOOR DRAINS, REF: 7/A9.41
8. TYPICAL PAINT AT RESTROOMS TO BE "SEMI -GLOSS" FINISH.
9. REFER TO MANUFACTURER'S TOILET ACCESSORY INSTALLATION AND OTHER
MOUNTING INSTRUCTIONS AND PROVIDE WALL BACKING AND OTHER REQUIRED SUPPORT AS INDICATED.
10. REFER TO DETAIL 04/G0.32 FOR ACCESSIBLE STALL INFORMATION. AT ACCESSIBLE STALLS: TOILET PARTITION DOOR WIDTHS ARE TO BE 36" (34" MIN.
CLEAR REG'D) PARTITION STILE WIDTH SHALL NOT EXCEED 4". FLUSH VALVE TO BE LOCATED AT WIDE SIDE OF STALL SPACE.
11. FOR SIGNAGE DETAILS, SEE SHEET A10.01
12. ANY FURNITURE PROVIDED BY OWNER SHALL SHOW 5% OF SEATING WITH WHEELCHAIR ACCESS COMPLYING WITH CBC 11B -802.1.
GYP -1
FRAMED GYPSUM BOARD CEILING
SEE DETAILS ON SHEET A--
ACT -1
2'X4' ACOUSTIC CEILING TILE
DUNE TEGUALR, 9/16" SILHOUETTE GRID
SEE DETAIL ----
GYP -3 FRAMED MOISTURE -RESISTANT GYP BD CEILING,
SEE DETAILS ON SHEET A----
CEILING TYPE X
X' -X" CEILING HEIGHT, SEE PLAN
FINISHED EDGE F.E.
INDICATED ACCESSIBLE LOCKER
METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION
CMU WALL CONSTRUCTION
EXISTING STUD WALLS
EXISTING CMU WALLS
XX
XX
FLOOR FINISH
BASE FINISH
WALL FINISH
*REFERENCE FINISH SCHEDULE ON SHEET A6.31
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. T he
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
ENLARGED
RESTROOM PLANS
& ELEVATIONS
A4.04
MD
MONROE ST. POOL REPLACEMENT
ENLARGED RESTROOM PLANS & ELEVATIONS
1/4" = 1' -0"
A4.04 06 ENLARGED FLOOR PLAN - WOMENS RESTROOM - BLDG A 1/4" = 1' -0"
A4.04 13 ENLARGED RCP - WOMEN'S RESTROOM - BLDG A
1/4" = 1' -0"
A4.04 04 WOMEN'S RESTROOM SINKS
1/4" = 1' -0"
A4.04 08 TYPICAL STALL
1/4" = 1' -0"
A4.04 11 WOMEN'S RESTROOM STALLS
1/4" = 1' -0"
A4.04 14 WOMEN'S RESTROOM ADA STALL
1/4" = 1' -0"
A4.04 12 WOMEN'S SHOWER SOUTH
1/4" = 1' -0"
A4.04 17 WOMEN'S SHOWER WEST
1/4" = 1' -0"
A4.04 05 WOMEN'S CHANGING ROOMS
1/4" = 1' -0"
A4.04 09 WOMEN'S CHANGING AREA
KEYNOTE LEGEND
02.19 EXISTING SKYLIGHT TO REMAIN, PROTECT IN PLACE
26.05 LED TAPE, PER ELECTRICAL DRAWINGS
26.08 SURFACE MOUNTED LINEAR WALL WASH LIGHT FIXTURE , PER
ELECTRICAL DRAWINGS
203
35 08/09/2024
203
T5
AA
T5
3'-4"
LL
AA
T4
T5
T4
L-2
A4.05 15
05 09
12 A4.05 14
04 08
11 T1
T1
STAFF
SHOWER
03B
STAFF
RR
03A
QTZ-1
7'-6" 3'-3" 5'-6"
1'-6"
11" 3'-10" 3'-1"
6'-10" 1'-0"
T5
T4 T4
T3
T5 QQ
T4
T5
1'-6"
T4
QTZ-110
A9.41
SH-1
RR
4'-0" 4"
T3
T4
T5
8' - 0"
GYP-2
8' - 0"
GYP-2
P1
P1
16 A9.21
11 A9.21
LEGEND
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.01.
STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.01. REFER TO S0.91 FOR INTERIOR STUD WALL SCHEDULE
LINE OF ELEMENT ABOVE
HATCH INDICATES NEW BUILT -IN CASEWORK
GENERAL NOTES
301
36 33
24 CABINET DESIGN SERIES NUMBERING SYSTEM PER
ARCHITECTURAL WOODWORK STANDARDS
AWI CASEWORK NUMBER
CABINET WIDTH
CABINET HEIGHT
CABINET DEPTH
ALIGN FINISHES
XX
FINISH TAG REF: A6.31 FINISH SCHEDULE
EQUIPMENT TAG 1i
1. FOR FINISH & RESTROOM ACCESSORY SCHEDULES REF: A6.31
2. FOR TYPICAL WALL BASE DETAILS REF: 07/A9.12
3. ALL PLUMBING FIXTURES TO HAVE SOLID BLOCKING AS REQUIRED BY CODE.
4. FOR FIXTURE AND ACCESSORY MOUNTING HEIGHTS, REF: G0.32
5. PROVIDE 5/8" TYPE "X" WATER RESISTANT GYPSUM BOARD AT ALL RESTROOM WALLS NOT RECEIVING TILE. PAINT PER FINISH PLANS
6. PROVIDE CEMENTITIOUS TILE BACKER BOARD AT ALL TILED WALLS, TYP.
7. PROVIDE LOCALIZED SLAB DEPRESSION AT FLOOR DRAINS, REF: 7/A9.41
8. TYPICAL PAINT AT RESTROOMS TO BE "SEMI -GLOSS" FINISH.
9. REFER TO MANUFACTURER'S TOILET ACCESSORY INSTALLATION AND OTHER
MOUNTING INSTRUCTIONS AND PROVIDE WALL BACKING AND OTHER REQUIRED SUPPORT AS INDICATED.
10. REFER TO DETAIL 04/G0.32 FOR ACCESSIBLE STALL INFORMATION. AT ACCESSIBLE STALLS: TOILET PARTITION DOOR WIDTHS ARE TO BE 36" (34" MIN.
CLEAR REG'D) PARTITION STILE WIDTH SHALL NOT EXCEED 4". FLUSH VALVE TO BE LOCATED AT WIDE SIDE OF STALL SPACE.
11. FOR SIGNAGE DETAILS, SEE SHEET A10.01
12. ANY FURNITURE PROVIDED BY OWNER SHALL SHOW 5% OF SEATING WITH WHEELCHAIR ACCESS COMPLYING WITH CBC 11B -802.1.
GYP -1
FRAMED GYPSUM BOARD CEILING
SEE DETAILS ON SHEET A--
ACT -1
2'X4' ACOUSTIC CEILING TILE
DUNE TEGUALR, 9/16" SILHOUETTE GRID
SEE DETAIL ----
GYP -3 FRAMED MOISTURE -RESISTANT GYP BD CEILING,
SEE DETAILS ON SHEET A----
CEILING TYPE X
X' -X" CEILING HEIGHT, SEE PLAN
FINISHED EDGE F.E.
INDICATED ACCESSIBLE LOCKER
METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION
CMU WALL CONSTRUCTION
EXISTING STUD WALLS
EXISTING CMU WALLS
XX
XX
FLOOR FINISH
BASE FINISH
WALL FINISH
*REFERENCE FINISH SCHEDULE ON SHEET A6.31
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. T he
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
ENLARGED
RESTROOM PLANS
& ELEVATIONS
A4.05
MD
MONROE ST. POOL REPLACEMENT
ENLARGED RESTROOM PLANS & ELEVATIONS
1/4" = 1' -0"
A4.05 15 INT ELEVATION - STAFF RR WEST
1/4" = 1' -0"
A4.05 05 INT ELEVATION - STAFF RR NORTH
1/4" = 1' -0"
A4.05 09 INT ELEVATION - STAFF RR EAST
1/4" = 1' -0"
A4.05 12 INT ELEVATION - STAFF RR SOUTH
1/4" = 1' -0"
A4.05 06 ENLARGED FLOOR PLAN - STAFF -
BLDG A
1/4" = 1' -0"
A4.05 14 INT ELEVATION - STAFF SHOWER
WEST
1/4" = 1' -0"
A4.05 04 INT ELEVATION - STAFF SHOWER
NORTH
1/4" = 1' -0"
A4.05 08 INT ELEVATION - STAFF SHOWER
EAST
1/4" = 1' -0"
A4.05 11 INT ELEVATION - STAFF SHOWER
SOUTH
1/4" = 1' -0"
A4.05 10 ENLARGED RCP - STAFF - BLDG A
KEYNOTE LEGEND
26.08 SURFACE MOUNTED LINEAR WALL WASH LIGHT FIXTURE , PER
ELECTRICAL DRAWINGS
203
36 08/09/2024
203
5 6
F
A4.06
05 08
11 A4.06 04
A4.06 16
18 14
17 07
10 13
SA4
SG6
SE4
SE4
SB4
SE4
SN6
SG6
SA4 CORRIDOR/
LOCKERS
20 FAMILY
RESTROOM/
SHOWER
20B
FAMILY
RESTROOM/
SHOWER
20C
FAMILY
RESTROOM/
SHOWER
20D
STORAGE
19 ELECTRICAL
21 FAMILY
RESTROOM/
SHOWER
20A
T1
T1 T1
T1
T1
T1
T2
A4.07
04 13
10 07
SA4
SB4
SB4
SA4
SA4
FAMILY
RESTROOM/
SHOWER
20E
INT ELEV:
OPP. RM 20B
INT ELEV:
OPP. RM 20E
SA4
114E
SA4
SA4 SA4
3'-0"
QTZ-1
6'-1" 3'-3" 6'-10"
6'-1" 3'-3"
1'-3" 3'-1" 5'-5" 6'-3" 5'-1" 3'-5" 1'-7"
4'-3" 3'-3" 3'-3" 3'-5"
4'-3" 3'-3" 3'-3" 3'-5" 7'-0" 3'-10"
1'-3" 2'-1" 3'-5" 3'-0" 4'-9" 1'-6"
1'-10"
5 6
F
8' - 6"
GYP-2
8' - 6"
GYP-2
8' - 6"
GYP-2
8' - 6"
GYP-2
8' - 6"
GYP-2
8' - 6"
GYP-2
P1
P1 P1 P1
P1 P1
6' - 2"
GYP-2
T5
10.06 13
A9.31
T5
2'-6"
1'-6"
3'-0"
10.07 TYP.
10.06 10
A9.41
QTZ-1
4'-6"
T5
AA
T4
CC
2'-6"
10.07 T4
T5
T3
RR
4'-0" 4"
T5
RR
LL
3'-4"
T3
T4
4" 4'-0"
T4
T4
T5 T5
4" 4'-0"
QQ
T3
T4
T4
T5
T4
QQ
4'-0" 4"
T5
3'-4"
QQ
LL
T4
T4
T5
LEGEND
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.01.
STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.01. REFER TO S0.91 FOR INTERIOR STUD WALL SCHEDULE
LINE OF ELEMENT ABOVE
HATCH INDICATES NEW BUILT -IN CASEWORK
GENERAL NOTES
301
36 33
24 CABINET DESIGN SERIES NUMBERING SYSTEM PER
ARCHITECTURAL WOODWORK STANDARDS
AWI CASEWORK NUMBER
CABINET WIDTH
CABINET HEIGHT
CABINET DEPTH
ALIGN FINISHES
XX
FINISH TAG REF: A6.31 FINISH SCHEDULE
EQUIPMENT TAG 1i
1. FOR FINISH & RESTROOM ACCESSORY SCHEDULES REF: A6.31
2. FOR TYPICAL WALL BASE DETAILS REF: 07/A9.12
3. ALL PLUMBING FIXTURES TO HAVE SOLID BLOCKING AS REQUIRED BY CODE.
4. FOR FIXTURE AND ACCESSORY MOUNTING HEIGHTS, REF: G0.32
5. PROVIDE 5/8" TYPE "X" WATER RESISTANT GYPSUM BOARD AT ALL RESTROOM WALLS NOT RECEIVING TILE. PAINT PER FINISH PLANS
6. PROVIDE CEMENTITIOUS TILE BACKER BOARD AT ALL TILED WALLS, TYP.
7. PROVIDE LOCALIZED SLAB DEPRESSION AT FLOOR DRAINS, REF: 7/A9.41
8. TYPICAL PAINT AT RESTROOMS TO BE "SEMI -GLOSS" FINISH.
9. REFER TO MANUFACTURER'S TOILET ACCESSORY INSTALLATION AND OTHER
MOUNTING INSTRUCTIONS AND PROVIDE WALL BACKING AND OTHER REQUIRED SUPPORT AS INDICATED.
10. REFER TO DETAIL 04/G0.32 FOR ACCESSIBLE STALL INFORMATION. AT ACCESSIBLE STALLS: TOILET PARTITION DOOR WIDTHS ARE TO BE 36" (34" MIN.
CLEAR REG'D) PARTITION STILE WIDTH SHALL NOT EXCEED 4". FLUSH VALVE TO BE LOCATED AT WIDE SIDE OF STALL SPACE.
11. FOR SIGNAGE DETAILS, SEE SHEET A10.01
12. ANY FURNITURE PROVIDED BY OWNER SHALL SHOW 5% OF SEATING WITH WHEELCHAIR ACCESS COMPLYING WITH CBC 11B -802.1.
GYP -1
FRAMED GYPSUM BOARD CEILING
SEE DETAILS ON SHEET A--
ACT -1
2'X4' ACOUSTIC CEILING TILE
DUNE TEGUALR, 9/16" SILHOUETTE GRID
SEE DETAIL ----
GYP -3 FRAMED MOISTURE -RESISTANT GYP BD CEILING,
SEE DETAILS ON SHEET A----
CEILING TYPE X
X' -X" CEILING HEIGHT, SEE PLAN
FINISHED EDGE F.E.
INDICATED ACCESSIBLE LOCKER
METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION
CMU WALL CONSTRUCTION
EXISTING STUD WALLS
EXISTING CMU WALLS
XX
XX
FLOOR FINISH
BASE FINISH
WALL FINISH
*REFERENCE FINISH SCHEDULE ON SHEET A6.31
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. T he
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
ENLARGED
RESTROOM PLANS
& ELEVATIONS
A4.06
MD
MONROE ST. POOL REPLACEMENT
ENLARGED RESTROOM PLANS & ELEVATIONS
1/4" = 1' -0"
A4.06 06 ENLARGED FLOOR PLAN - FAMILY RESTOOMS - BLDG B 1/4" = 1' -0"
A4.06 12 ENLARGED RCP - FAMILY RESTOOMS - BLDG B
1/4" = 1' -0"
A4.06 05 FAMILY RESTROOMS NORTH
1/4" = 1' -0"
A4.06 08 EAST LOCKERS
1/4" = 1' -0"
A4.06 11 FAMILY RESTROOMS SOUTH
1/4" = 1' -0"
A4.06 04 FAMILY RR 20C WEST
1/4" = 1' -0"
A4.06 07 FAMILY RR 20C NORTH
1/4" = 1' -0"
A4.06 10 FAMILY RR 20C EAST
1/4" = 1' -0"
A4.06 13 FAMILY RR 20C SOUTH
1/4" = 1' -0"
A4.06 16 FAMILY RR 20B WEST
1/4" = 1' -0"
A4.06 18 FAMILY RR 20B NORTH
1/4" = 1' -0"
A4.06 14 FAMILY RR 20B EAST
1/4" = 1' -0"
A4.06 17 FAMILY RR 20B SOUTH
KEYNOTE LEGEND
10.06 SIGNAGE
10.07 CHANGING TABLE, MOUNTING PER G0.32
26.08 SURFACE MOUNTED LINEAR WALL WASH LIGHT FIXTURE , PER
ELECTRICAL DRAWINGS
203
37 08/09/2024
203
LEGEND
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.01.
STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.01. REFER TO S0.91 FOR INTERIOR STUD WALL SCHEDULE
LINE OF ELEMENT ABOVE
HATCH INDICATES NEW BUILT -IN CASEWORK
GENERAL NOTES
301
36 33
24 CABINET DESIGN SERIES NUMBERING SYSTEM PER
ARCHITECTURAL WOODWORK STANDARDS
AWI CASEWORK NUMBER
CABINET WIDTH
CABINET HEIGHT
CABINET DEPTH
ALIGN FINISHES
XX
FINISH TAG REF: A6.31 FINISH SCHEDULE
EQUIPMENT TAG 1i
1. FOR FINISH & RESTROOM ACCESSORY SCHEDULES REF: A6.31
2. FOR TYPICAL WALL BASE DETAILS REF: 07/A9.12
3. ALL PLUMBING FIXTURES TO HAVE SOLID BLOCKING AS REQUIRED BY CODE.
4. FOR FIXTURE AND ACCESSORY MOUNTING HEIGHTS, REF: G0.32
5. PROVIDE 5/8" TYPE "X" WATER RESISTANT GYPSUM BOARD AT ALL RESTROOM WALLS NOT RECEIVING TILE. PAINT PER FINISH PLANS
6. PROVIDE CEMENTITIOUS TILE BACKER BOARD AT ALL TILED WALLS, TYP.
7. PROVIDE LOCALIZED SLAB DEPRESSION AT FLOOR DRAINS, REF: 7/A9.41
8. TYPICAL PAINT AT RESTROOMS TO BE "SEMI -GLOSS" FINISH.
9. REFER TO MANUFACTURER'S TOILET ACCESSORY INSTALLATION AND OTHER
MOUNTING INSTRUCTIONS AND PROVIDE WALL BACKING AND OTHER REQUIRED SUPPORT AS INDICATED.
10. REFER TO DETAIL 04/G0.32 FOR ACCESSIBLE STALL INFORMATION. AT ACCESSIBLE STALLS: TOILET PARTITION DOOR WIDTHS ARE TO BE 36" (34" MIN.
CLEAR REG'D) PARTITION STILE WIDTH SHALL NOT EXCEED 4". FLUSH VALVE TO BE LOCATED AT WIDE SIDE OF STALL SPACE.
11. FOR SIGNAGE DETAILS, SEE SHEET A10.01
GYP -1
FRAMED GYPSUM BOARD CEILING
SEE DETAILS ON SHEET A--
ACT -1
2'X4' ACOUSTIC CEILING TILE
DUNE TEGUALR, 9/16" SILHOUETTE GRID
SEE DETAIL ----
GYP -3 FRAMED MOISTURE -RESISTANT GYP BD CEILING,
SEE DETAILS ON SHEET A----
CEILING TYPE X
X' -X" CEILING HEIGHT, SEE PLAN
FINISHED EDGE F.E.
INDICATED ACCESSIBLE LOCKER
METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION
CMU WALL CONSTRUCTION
EXISTING STUD WALLS
EXISTING CMU WALLS
XX
XX
FLOOR FINISH
BASE FINISH
WALL FINISH
*REFERENCE FINISH SCHEDULE ON SHEET A6.31
T5
T3
T4
T5
T4
T5
T4
3'-4"
26.08 LL
T5
T4
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
ENLARGED
RESTROOM PLANS
& ELEVATIONS
A4.07
MD
MONROE ST. POOL REPLACEMENT
ENLARGED RESTROOM PLANS & ELEVATIONS
KEYNOTE LEGEND
26.08 SURFACE MOUNTED LINEAR WALL WASH LIGHT FIXTURE , PER
ELECTRICAL DRAWINGS
1/4" = 1' -0"
A4.07 04 INT ELEVATION - FAMILY RR 20E
SOUTH
1/4" = 1' -0"
A4.07 07 INT ELEVATION - FAMILY RR 20E
WEST
1/4" = 1' -0"
A4.07 10 INT ELEVATION - FAMILY RR 20E
NORTH
1/4" = 1' -0"
A4.07 13 INT ELEVATION - FAMILY RR 20E
EAST
38 203
08/09/2024
203
ABBREVIATIONS
DOOR NOTES
CORE
GL = GLASS (T = TEMPERED)
SC = SOLID CORE
HC = HOLLOW CORE
HCI = HOLLOW CORE INSULATED
CLOSER
OH = OVERHEAD
FLR = FLOOR
C-OH = CONCEALED OVERHEAD
DOOR PANEL MATERIAL
AL = ALUMINUM
WD = WOOD
HM = HOLLOW METAL
DOOR FRAME FINISH
PT = PAINT
FF = FACTORY FINISH
DOOR FRAME MATERIAL
AL = ALUMINUM
HM = HOLLOW METAL
DOOR PANEL FINISH
PT = PAINT (SEMI -GLOSS)
FF = FACTORY FINISH
PL = PLASTIC LAMINATE
ST =STAIN
GLASS FINISH
FM = FILM ON DOOR & SIDELIGHT GLAZING
DOOR TYPES
REMARKS
PH = PANIC HARDWARE
HO = HOLD OPEN
CR = CARD READER
BG = BULLET -RESISTANT GLASS
1. DOOR OPENING HARDWARE IS MOUNTED 34 ” TO 44 ” ABOVE THE FINISH FLOOR PER CBC 11B -404.2.7.
2. DOOR HARDWARE ARE OPERABLE WITH ONE HAND AND DO NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING OF THE HAND. CBC 11B -404 .2.7 AND 11B -309.4.
3. DOOR OPENING FORCE IS 5 -POUNDS MAXIMUM FOR INTERIOR AND EXTER IOR DOORS PER CBC 11B -404.2.9.
4. LOWER 10 INCH OF THE DOOR SURFACE IS PROVIDED WITH A SMOOTH
SURFACE FOR THE FULL WIDTH OF THE DOOR,
AT THE PUSH SIDE OF THE DOOR PER CBC 11B -404.2.10
5. DOOR THRESHOLDS TO HAEV MAX 1/4" THRESHOLD TRANSITION, OR 1/2 " MAX
TRANSITION WITH BEVELED EDGE, PER
6. DOORS WITH TWO PANELS, ONE PANEL PROVIDE A CLEAR 32 ” WIDTH PER CBC 11B -404.2.
TYPE A TYPE B
+7'-0"
T.O. DOOR
TYPE C TYPE D TYPE E TYPE F
TT
T
10"
EQ EQ
10"
LOUVER PER SCHEDULE
( WHERE OCCURS)
EQ EQ
10"
EQ EQ
10"
EQ EQ
0'-6"
1'-0"
1'-0"
DOOR LITE
( WHERE OCCURS)
ABOVE F.F. TYP.
34" - 44"
43" MAX
01/ A9.12
TYPE H
LOUVER PER SCHEDULE
( WHERE OCCURS)
DOOR LITE
( WHERE OCCURS)
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
1/4" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
DOOR SCHEDULES
A6.11
MD
MONROE ST. POOL REPLACEMENT
DOOR SCHEDULES
DOOR SCHEDULE
DOOR NUMBER
DOOR TYPE
DETAILS DOOR SIZE DOOR PANEL DOOR FRAME
REMARKS
HEAD
JAMB
THRESHOLD
WIDTH
HEIGHT
THICKNESS
MATERIAL
FINISH
MATERIAL
FINISH
HARDWARE GROUP
<vari
es>
<varies> <varies> <varies> <varies> <varies> <varies> <varies> <va rie s>
<varies> <varies>
101 A 6'-0" 8'-2" GL AL 05 CR, PANIC HDW,
102 B 2'-11
13/16"
6'-8" 0'-1 1/2" GL HM PT 11 3/4" UNDERCUT
103 B 3'-0" 6'-8" 0'-1 1/2" GL HM PT 11 3/4" UNDERCUT
104 E 3'-0" 7'-0" 0'-1 1/2" HM PT HM PT 14 26" x 26" METAL LO UVER, 50% OPEN 104A E 2'-8" 7'-0" 0'-1 1/2" HM PT HM PT 11 3/4" UNDERCUT 105 C 06/A8.14 12/A8.14 15/A8.14 3'-0" 6'-10" 0'-1 3/4" HM P T HM PT 02 26" x 26" METAL LOUVER, 50% OPEN. VIF EXISTI NG OPENING 106 C 06/A8.14 12/A8.14 15/A8.14 3'-0" 7'-2" 0'-1 3/4" HM PT HM PT 01 107 D 06/A8.14 12/A8.14 15/A8.14 5'-8" 7'-2" 0'-1 3/4" HM PT HM PT 04 20" x 10" METAL LOUVER EACH LEAF, 50% OPEN 108 E 3'-0" 7'-0" 0'-1 1/2" HM PT HM PT 14 26" x 26" METAL LO UVER, 50% OPEN 108A E 2'-8" 7'-0" 0'-1 1/2" HM PT HM PT 11 3/4" UNDERCUT 109 C 06/A8.14 12/A8.14 14/A8.14 3'-0" 6'-10" 0'-1 3/4" HM C LR HM PT 12 24" X 24" METAL LOUVER, 50% OPEN. VIF EXIS TING OPENING 109A E 3'-0" 7'-0" 0'-1 1/2" HM CLR HM PT 13 3/4" UNDERCUT 110 C 06/A8.14 12/A8.14 15/A8.14 3'-0" 6'-10" 0'-1 3/4" HM P T HM PT 02 26" x 26" METAL LOUVER, 50% OPEN, VIF EXISTI NG OPENING 111 A 6'-0" 7'-0" 0'-1 3/4" GL AL CLR 06 VIF EXISTING OPENIN G 111A E 2'-8" 7'-0" 0'-1 1/2" WD CLR HM PT 10
112 C 06/A8.14 12/A8.14 15/A8.14 3'-0" 6'-10" 0'-1 3/4" HM P T HM PT 07 26" x 26" METAL LOUVER, 50% OPEN, VIF EXISTI NG OPENING 113 C 06/A8.14 12/A8.14 15/A8.14 3'-8" 7'-4" 0'-1 3/4" HM PT HM PT 03 24" x 24" METAL LOUVER, 50% OPEN 114 G11 06/A8.14 12/A8.14 15/A8.14 3'-2" 7'-4 1/2" 0'-1 3/ 4" PT PT 15 24" X 24" METAL LOUVER EACH LEAF, 50% OPEN . 8" DOOR LITE,
EACH LEAF
114A F 3'-0" 7'-0" 0'-1 1/2" HM PT HM PT 09 20" x 10" METAL L OUVER, 30% OPEN 114B F 3'-0" 7'-0" 0'-1 1/2" HM PT HM PT 09 20" x 10" METAL L OUVER, 30% OPEN 114C F 3'-0" 7'-0" 0'-1 1/2" HM PT HM PT 09 20" x 10" METAL L OUVER, 30% OPEN 114D F 3'-0" 7'-0" 0'-1 1/2" HM PT HM PT 09 20" x 10" METAL L OUVER, 30% OPEN 114E F 3'-0" 7'-0" 0'-1 1/2" HM PT HM PT 09 20" x 10" METAL L OUVER, 30% OPEN 115 C 06/A8.14 12/A8.14 15/A8.14 3'-8" 7'-4" 0'-1 3/4" HM PT HM PT 03 24" X 24" METAL LOUVER, 50% OPEN 116 G8 06/A8.14 12/A8.14 15/A8.14 6'-0" 7'-2" 0'-1 3/4" HM P T HM PT 04 24" X 24" METAL LOUVER EACH LEAF, 50% OPEN 117 D 06/A8.14 12/A8.14 15/A8.14 4'-8" 7'-2" 0'-1 3/4" HM PT HM PT 04 20" x 10" METAL LOUVER EACH LEAF, 50% OPEN 118 D 06/A8.14 12/A8.14 15/A8.14 4'-8" 7'-2" 0'-1 3/4" HM PT HM PT 04 20" x 10" METAL LOUVER EACH LEAF, 50% OPEN 119 C 06/A8.14 12/A8.14 15/A8.14 3'-8" 7'-4" 0'-1 3/4" HM PT HM PT 08 26" x 26" METAL LOUVER, 50% OPEN 130 C 3'-0" 7'-2" 0'-1 3/4" 08 26" x 26" METALLOUVER, 50% OPEN
DOUBLE IN AL
STOREFRONT
SINGLE IN AL
FRAME/ SIDE LITE
SINGLE HM IN CMU DOUBLE HM IN CMU SINGLE AL IN STUD SINGLE HM IN STUD SINGLE HM WITH
LOUVER SIDE PANEL
39 203
08/09/2024
203
01 - FLOOR
0'-0"
1A
TTTT
8'-6"
01 - FLOOR
0'-0"
TTT
2A
8'-7"
(VERIFY)
8'-8"
01 - FLOOR
0'-0"
3A
T
EXISTING
(VERIFY)
EXISTING
SPANDREL
TOP OF BLOCK EAST -
BLDG A
10'-6"
8'-6"
SOLID FRIT
6'-0"
50% FRIT
50% FRIT
01 - FLOOR
0'-0"
4A
T
5'-4"
4'-8" 2'-8"
01 - FLOOR
0'-0"
5A
3'-0" 4'-0"
2'-8"
01 - FLOOR
0'-0"
5D
4'-0" 3'-0"
2'-8"
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
3/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
OPENING TYPES
A6.21
MD
MONROE ST. POOL REPLACEMENT
OPENING TYPES
KEYNOTE LEGEND
40 203
08/09/2024
203
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
FINISH &
EQUIPMENT
SCHEDULES
A6.31
MD
MONROE ST. POOL REPLACEMENT
FINISH & EQUIPMENT SCHEDULES
FAB-1 SOLAR SHADE FABRIC MECHO SHADE 1550 SERIES / ECOVEIL / 1% OPEN 1563 GREY - - - SHADE DETAIL REF: 07 & 08/A 9.31
SPECIALTY ,
QTZ-2 QUARTZ SOLID SURFACE ARIZONA TILE DELLA TERRA QUARTZ CONCRETE GREY STANDARD - " QTZ-1 QUARTZ SOLID SURFACE ARIZONA TILE DELLA TERRA QUARTZ AERIAL STANDARD - PL-2 PLASTIC LAMINATE WILSONART - - "
PL-1 PLASTIC LAMINATE WILSONART LANDMARK WOOD 7981 - -
CASEWORK
T-6 TILE BASE DALTILE COLOR WHEEL / LINEAR ARCTIC WHITE 01 90 SEMI-GLOSS 4"H COVE - ALIGN GROUT JOINTS WHERE POSS IBLE T-5 TILE BASE FRY REGLET DRMB-625-300 TBD - 4"H COVE - PROVIDE AN EXTRA LAYER O F GYP. BD. WHERE FIRE RATED WALLS OCCUR B-1 RUBBER BASE JOHNSONITE WALL BASE UMBER #63 - 4" H - REF: 07/A9.42
WALL BASE
FRP FIBER REINFORCED PANEL MARLITE STANDARD FRP, CLASS A W HITE S100G - FULL HEIGHT - PROVIDE ALUMINUM TRIM AS N EEDED, SEE 20/A9.42 WC-1 WALL COVERING KOROSEAL KOROSEAL DIGITALLY PREINTED VI NYL CUSTOM SEMI-GLOSS CUSTOM ADHERED SEE INTERIOR ELEVAT IONS FOR EXTENTS T-4 WALL TILE DALTILE OUTLANDER MARINE RECTANGLE PALAZZO MA TTE 2'X2' STACKED T-3 WALL TILE DALTILE OUTLANDER MARINE RECTANGLE GRANDE MAT TE 2'X2' STACKED P-4 PAINT, ACCENT BEHR - True Copper EGGSHELL - -
P-3 PAINT, ACCENT SHERWIN WILLIAMS - Billowy Breeze EGGSHELL - - P-2 PAINT, ACCENT SHERWIN WILLIAMS - Silken Peacock EGGSHELL - - P-1 PAINT, GENERAL SHERWIN WILLIAMS - SW 7008 ALABASTER EG GSHELL - - PROVIDE FLAT FINISH AT CEILINGS, EGGSHELL FINISH AT WALLS, SEMI-GLOSS AT DOOR FRAMES TYP.
WALL FINISH
CONC-1 POLISHED CONCRETE WESTCOAT SC-42 WB ACRYLIC SEALER MAT CH EXTERIOR CONCRETE SEMI-POLISHED - - T-2 FLOOR TILE DALTILE VOLUME 1.0 STEREO GREY - 6"X6" STAGGA RD T-1 FLOOR TILE DALTILE VOLUME 1.0 DEGREES SILVER - MOSAIC 2"X2" LVT-1 VINYL TILE MILLIKEN THE MAGIC HOUR HORIZON LIGHT - PLAN K 10"X40" RUNNING BOND CPT-2 WALK OFF CARPET INTERFACE STEP AND REPEAT / SR699 COL ORLINE GRANITE 104931 - 40"X40" RUNNING BOND LOCATED AT SLAB DEPRESSION, SEE FINISH PLANS & FLOORING SECTION CPT-1 CARPET TILE SHAW CONTRACT ALL TOGETHER TILE TOGETHER C OLOR 50210 - PLANK 9"X36"
FLOOR FINISH
TAG DESCRIPTION MANUFACTURER STYLE/COLLECTION COLOR FINI SH SIZE INSTALL COMMENTS
FINISH SCHEDULE
U-2 - - ACCESSIBLE URINAL, REFER TO PLUMBING DRAWINGS
U-1 - - URINAL, REFER TO PLUMING DRAWINGS
L-2 - - ACCESSIBLE LAVATORY, REFER TO PLUMBING DRAWING S L-1 - - LAVATORY, REFER TO PLUMBING DRAWINGS
SH-2 - - SHOWER, REFER TO PLUMBING DRAWINGS
SH-1 - - ACCESSIBLE SHOWER, REFER TO PLUMBING DRAWINGS
TAG # DESCRIPTION
PLUMBING FIXTURE SCHEDULE
SS BOBRICK B-207, TBD CHANGING CURTAIN & ROD - FABRIC (TBD) RR BOBRICK B-5191 ACCESSIBLE SHOWER BENCH
QQ BOBRICK B-207, B-204 SHOWER ROD & SHOWER CURTAIN
PP BRADLEY MATCH II 36" URINAL PRIVACY PARTITION, PHEN OLIC OO BOBRICK B-2974 AUTOMATIC SURFACE MOUNTED ROLL TOWEL DISPENSER WITH LED LIGHT NN BOBRICK B-3588 SURFACE-MOUNTED MULTI-ROLL TOILET TI SSUE DISPENSER LL BOBRICK B-290 OR SIM MIRROR WITH 1/2" STAINLESS TEE L FRAME. VARIOUS SIZES, SEE INTERIOR ELEVATIONS KK BOBRICK KB110-SSWM SURFACE MOUNTED BABY CHANGING ST ATION II BRADLEY SERIES 400 FLOOR MOUNTED TOILET PARTITIONS, PHENOLIC CORE FINISH HH BOBRICK B-3974 RECESSED CONVERTIBLE AUTOMATIC ROLL TOWEL DISPENSER EQUIPPED WITH LED LIGHT AND WASTE RECEPTICLE GG BOBRICK B-270 BOBRICK B-270 CONTURA SERIES SURFACE MOUNTED SANITARY NAPKIN DISPOSAL FF BOBRICK B-4221 CONTURA SERIES SURFACE MOUNTED SEAT COVER DISPENSER EE BOBRICK B-3579 SURFACE-MOUNTED SEAT-COVER DISPENSER , SANITARY NAPKIN DISPOSAL, AND TOILET TISSUE DISPENSER DD BOBRICK B-3571 PARTITION MOUNTED, RECESSED TOILET S EAT COVER, TOILET TISSUE DISPENSER AND SANITARY NAPKIN DISPOSAL - TWO COMPARTMENT UNIT CC BOBRICK B-3479 SURFACE MOUNTED SEAT COVER AND TOILE T TISSUE DISPENSER BB BOBRICK B-3471 PARTITION MOUNTED TOILET SEAT COVER AND TOILET TISSUE DISPENSER - TWO COMPARTMENT UNIT AA BOBRICK B-5806 STAINLESS STEEL GRAB BAR
TAG # MANUFACTURER MODEL # DESCRIPTION
RESTROOM ACCESSORIES SCHEDULE
41 203
08/09/2024
203
A
0'-3" TYP.
C4X5.4, SEE STRUCT.; PAINTED TO
MATCH PERFORATED PANEL
3/8" STAINLESS STEEL BOLT
ASSEMBLY; (2) PER ANGLE
PERFORATED ALUMINUM PANELS
W/ 3" RETURNS ON ALL 4 SIDES
ETHER POLYURETHANE WASHERS,
TYP.
STEEL ANGLE 2" x 3" x 1/4" x 9" LONG;
PAINTED TO MATCH PERFORATED
PANEL; (2) ANGLES PER PANEL 3"
FROM ENDS
3/16"
TYP. CEM. PLASTER WALL
ASSEMBLY, SEE DETAIL13/A8.12
CONT. SEALANT O/
BACKER ROD
SLOPE 1/2" : 12"
1'-4" 0'-7 1/2"
TYP. COPING, SEE DETAIL 9/A8.22
TOP OF BLOCK - BLDG A
9'-10"
A
DIM PT
R.O.
ACOUSTICAL LAY-
IN PANEL
EXISTING
HEAVY TIMBER
BEAM
SEALANT & BACKER ROD;
WEEP HOLES AS REQUIRED
ALUMINUM STOREFRONT SYSTEM
PANEL CLIPS PER MANUFACTURER
COMPOSITE ALUMINUM PANEL
0'-6"
STRUCTURAL STUD FRAMING
STRUCT. STUD
FRAMING
HSS FRAME, SEE STRUCT.
HSS FRAME,
SEE STRUCT.
DIM PT
3" MIN.
1/4" / 1'-0"
1/4"
PLASTER ASSEMBLY WALL,
SEE 13/A8.12
8 1/8"
1/4"
C4X5.4, SEE STRUCT.; PAINTED TO
MATCH PERFORATED PANEL
3/8" STAINLESS STEEL BOLT ASSEMBLY
12" O.C. MAX. (MIN. 3 PER PANEL)
PERFORATED ALUMINUM PANELS W/
3" RETURNS ON ALL 4 SIDES
ETHER POLYURETHANE WASHERS,
TYP.
CONTINUOUS STEEL ANGLE 1 1/2" x 3" x
1/4" WELDED TO VERTICAL HSS
PAINTED TO MATCH PERFORATED
PANEL
3/16"
B.O.
PANEL
2"
A
COMPOSITE ALUMINUM PANEL
SEALANT & BACKER ROD;
WEEP HOLES AS REQUIRED
PANEL CLIPS PER MANUFACTURER
1'-6 3/4" 6"
ALUMINUM STOREFRONT SYSTEM
HSS FRAME, SEE STRUCT.
SEALANT & BACKER
ROD; WEEP HOLES
AS REQUIRED
J-BOX FOR INTERCOM
COORD. LOCATION W/ ARCHITECT. 11
A8.12
12 A8.12
C4x5.4, TITEN HD
ANCHOR @ 24" O.C.,
PAINTED TO MATCH
PERFORATED PANEL
3" TYP.
3/8" STAINLESS STEEL CARRIAGE BOLT
W/CAP NUT 3' O.C. MAX. AND 6" FROM EACH
END (MIN. 3 PER PANEL)
PERFORATED ALUMINUM PANELS
W/ 3" RETURNS ON ALL 4 SIDES
ETHER POLYURETHANE WASHERS, TYP.
EDGE OF
PANEL
CONTINUOUS STEEL ANGLE 2"X3"X1/4"
PAINTED TO MATCH PERFORATED PANEL
3/16"
1/2" CONT. BENT PLATE
W/ 1/4" TITEN HD
ANCHOR @ 24" O.C.
0'-2" 0'-8"
7/8" CEMENT PLASTER
METAL LATH
1 1/2" RIGID INSULATION
18 GA. 1.5" HORIZONTAL
Z-CHANNEL ATTACHMENT
WEATHER -RESISTANT
BARRIER
5/8" TYPE 'X' GYPSUM
BOARD
METAL STUD PER
STRUCTURAL
5/8" GYPSUM BOARD
R-19 MIN. BATT INSUL.
EXT INT
#10 SMS @ 16" O.C., TYP.,
ATTACHED TO Z -CHANNEL PER
G.2 / S0.01
#8 S.M.S. AT 16" O.C.,
ATTACHED TO METAL STUD
PER G.2 / S0.01; BUGLE HEAD
AT INTERIOR
#10 SMS @ 16" O.C., TYP.,
ATTACHED TO METAL STUD
PER G.2 / S0.01
STEEL FRAME, SIZE VARIES,
SEE STRUCT.; PAINTED TO
MATCH PERFORATED PANEL
3/8" STAINLESS STEEL
CARRIAGE BOLT W/
CAP NUT 12" O.C. MAX.
(MIN. 3 PER PANEL)
B.O.
PANEL
PERFORATED ALUMINUM
PANELS W/ 3" RETURNS
ON ALL 4 SIDES
ETHER POLYURETHANE
WASHERS, TYP.
CONTINUOUS STEEL ANGLE
1 1/2" x 3" x 1/4" WELDED TO
HSS PAINTED TO MATCH
PERFORATED PANEL
SECTION - SILL & BASE CONDITION
CONCRETE PAVING
WHERE OCCURS PER
LANDSCAPE AND
CIVIL DRAWINGS
3/16"
W
HERE OCCURS
3"M
IN. ABOVE GRADE
SECTION - VERTICAL JOINT
0'-3" TYP.
WHERE NO CMU
WALL OCCURS:
STEEL FRAME, SIZE
VARIES, SEE
STRUCT.; PAINTED
TO MATCH
PERFORATED
PANEL
3/8" STAINLESS STEEL
BOLT ASSEMBLY; (2)
PER ANGLE
PANEL
JOINT
PERFORATED
ALUMINUM PANELS
W/ 3" RETURNS ON
ALL 4 SIDES
ETHER POLYURETHANE
WASHERS, TYP.
STEEL ANGLE 1 1/2" x 3"
x 1/4" x 9" LONG;
PAINTED TO MATCH
PERFORATED PANEL;
(2) ANGLES PER PANEL
3" FROM ENDS
3/16"
AT MAIN ENTRY
ONLY, WHERE CMU
WALL WHERE
OCCURS;
C4x5.4, TITEN HD
ANCHOR @ 24" O.C.,
PAINTED TO MATCH
PERFORATED
PANEL
0'-3" TYP.
3/8" STAINLESS STEEL
CARRIAGE BOLT W/ CAP
NUT 12" O.C. MAX. (MIN. 3
PER PANEL)
T.O.
PANEL
PERFORATED ALUMINUM
PANELS W/ 3" RETURNS
ON ALL 4 SIDES
ETHER
POLYURETHANE
WASHERS, TYP.
CONTINUOUS STEEL
ANGLE 1 1/2" x 3" x 1/4";
PAINTED TO MATCH
PERFORATED PANEL
SECTION - TOP JOINT
3/16"
STEEL FRAME, SIZE VARIES, SEE
STRUCT.; PAINTED TO MATCH
PERFORATED PANEL
PLAN - HORIZONTAL JOINT
0'-3" TYP.
3/8" STAINLESS
STEEL BOLT
ASSEMBLY 3' O.C.
MAX. AND 6" FROM
EACH END (MIN. 3
PER PANEL)
PANEL
JOINT
PERFORATED
ALUMINUM PANELS
W/ 3" RETURNS ON
ALL 4 SIDES
STAINLESS STEEL
TREADED
STANDOFF W/
ETHER
POLYURETHANE
WASHERS EA SIDE
0'-1"
STEEL FRAME, SIZE
VARIES, SEE STRUCT.;
PAINTED TO MATCH
PERFORATED PANEL
0'-3" TYP.
STEEL FRAME, SIZE
VARIES, SEE STRUCT.;
PAINTED TO MATCH
PERFORATED PANEL
3/8" STAINLESS STEEL
CARRIAGE BOLT W/ CAP
NUT 3' O.C. MAX. AND 6"
FROM EACH END (MIN. 3
PER PANEL)
EDGE OF
PANEL
PERFORATED ALUMINUM
PANELS W/ 3" RETURNS
ON ALL 4 SIDES
ETHER
POLYURETHANE
WASHERS, TYP.
CONTINUOUS STEEL
ANGLE 2" x 3" x 1/4"
PAINTED TO MATCH
PERFORATED PANEL
PLAN - END OF PANEL
0'-2"
EXTERIOR CMU WALL
WHERE OCCURS
3/16"
0'-3"
0'-2"
STAINLESS STEEL
PLATE, ALL AROUND EXPOSED
EXTERIOR BASE
EXISTING CONCRETE PAVING
PANEL CLIPS PER
MANUFACTURER
COMPOSITE ALUMINUM PANEL
1/2" CONT. BENT PLATE
W/1/4" TITEN HD ANCHOR @ 24" O.C.
0'-8"
0'-1"
3/16"
1/4" CONT. BENT PLATE
0'-2"
STAINLESS STEEL
PLATE, ALL AROUND EXPOSED
EXTERIOR BASE
EXISTING CONCRETE PAVING
PANEL CLIPS PER
MANUFACTURER
COMPOSITE ALUMINUM PANEL
MTL STUD FRAMING W/
R-19 MIN INSULATION
EXT
DRIP SCREED
PER RCP PLAN
BO SOFFIT
PLASTER ASSY
SECTION - VERTICAL JOINT
0'-3" TYP.
3/8" STAINLESS STEEL
BOLT ASSEMBLY; (2)
PER ANGLE
PANEL
JOINT
PERFORATED
ALUMINUM PANELS
W/ 3" RETURNS ON
ALL 4 SIDES
ETHER POLYURETHANE
WASHERS, TYP.
STEEL ANGLE 1 1/2" x 3"
x 1/4" x 9" LONG;
PAINTED TO MATCH
PERFORATED PANEL;
(2) ANGLES PER PANEL
3" FROM ENDS
3/16"
C4x5.4, TITEN HD
ANCHOR @ 24" O.C.,
PAINTED TO MATCH
PERFORATED
PANEL
0'-3" TYP.
T.O.
PANEL & CMU
PERFORATED ALUMINUM
PANELS W/ 3" RETURNS
ON ALL 4 SIDES
M
IN.
2"
VERTICAL C4X5.4
BEYOND AT EVERY
VERTICAL JOINT. SEE
01/A8.12. STOP 2" MIN.
BELOW TOP OF PANEL
TO ALLOW FOR CMU
COPING CLEARANCE.
SEE 06/A8.22 FOR CMU
COPING DETAIL.
B.O.
PANEL
PERFORATED ALUMINUM
PANELS W/ 3" RETURNS
ON ALL 4 SIDES
VERTICAL C4X5.4
BEYOND AT EVERY
VERTICAL JOINT. SEE
01/A8.12. STOP 2" MIN.
BELOW TOP OF PANEL
TO ALLOW FOR CMU
COPING CLEARANCE.
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
EXTERIOR DETAILS
A8.12
MD
MONROE ST. POOL REPLACEMENT
EXTERIOR DETAILS
3" = 1' -0"
A8.12 16 PERF PANEL & PLASTER TOP
3" = 1' -0"
A8.12 15 ENTRY PORTAL TOP DETAIL
3" = 1' -0"
A8.12 14 ENTRY PORTAL PLAN DETAIL
3" = 1' -0"
A8.12 13 TYP. CEM. PLASTER WALL
ASSEMBLY
6" = 1' -0"
A8.12 08 PERF METAL BASE DETAIL
6" = 1' -0"
A8.12 04 PERF METAL JOINT VERTICAL
6" = 1' -0"
A8.12 10 PERF METAL TOP
6" = 1' -0"
A8.12 09 PERF METAL JOINT HORIZONTAL
6" = 1' -0"
A8.12 05 PERF METAL EDGE
3" = 1' -0"
A8.12 11 ENTRY PORTAL BASE DETAIL
3" = 1' -0"
A8.12 12 ENTRY PORTAL BASE DETAIL @
CMU
3" = 1' -0"
A8.12 06 PLASTER SOFFIT DRIP SCREED
6" = 1' -0"
A8.12 01 PERF METAL JOINT VERTICAL -
DIRECT ATTACHED TO CMU
6" = 1' -0"
A8.12 03 PERF METAL TOP - DIRECT
ATTACHED TO CMU
6" = 1' -0"
A8.12 02 PERF METAL BASE - DIRECT
ATTACHED TO CMU
42 203
08/09/2024
203
0'-0 1/4"
CONSTRUCTION SPECIALTIES
SC-800 JOINT
1/4" x 2 1/4" SCREW BOLT W/
SEALING WASHER 18" O.C.
(FIN: ZINC) ICC ESR-4042
CMU WALL; REF: STRUCTURAL DRAWINGS
5/8" MIN. OF FILL
MATERIAL APPLIED
WITHIN THE ANNULUS.
FLUSH WITH BOTH
SURFACES OF WALL.
2" MAX. THICK HOLLOW -
CYLINDRICAL HEAVY
GLASS FIBER PIPE
INSULATION COVERING.
NOTE:
1. IN MULTIPLE PIPE PENETRATIONS OCCUR IN PARTITION,
MAINTAIN ADEQUATE SEPARATION TO TREAT EA PIPE SEPARATELY
2. UL SYSTEM NO. W -J-5042
PENETRANT TO BE
RIGIDLY SUPPORTED
ON BOTH SIDES OF
WALL ASSEMBLY.
PER PLAN
WALL TYPE
W-J-5042:
FIN. FLOOR
(WHERE OCCURS)
INT. EXT.
CMU WALL BLOCK SEAL AT
EXTERIOR FLOOR SLAB
FLOOR FINISH & BASE PER
FINISH PLAN
COLD FLUID APPLIED
WATERPROOFING (TOP OF
WP NOT TO BE VISIBLE)
EXTERIOR PAVER.
SIDEWALK, WHERE
OCCURES
PER STRUCTURAL
STRUCTURAL FOOTING PER
STRUCTURAL
U937 FOR 1-HR RATED
CONDITION
ALUMINUM
STOREFRONT SYSTEM
EXTERIOR GLAZING SYSTEM,
SEE WINDOW TYPES
CONT. BEARING
PLATE SET IN CONT.
BED OF SEALANT
ALUM. SUBSILL
FLASHING W/ END DAMS,
SET IN CONT. BED OF
SEALANT. MATCH
WINDOW FINISH
CONT. BACKER
ROD AND
SEALANT, BOTH
SIDES
SHIM AS REQ'D.
CONNECTION TO STRUCTURE
BY MANUFACTURER
0'-1"
ALUMINUM
STOREFRONT DOOR
THRESHOLD SET
IN FULL BED OF
SEALANT
CONCRETE FLOOR
1/4" DIA x 1 -5/8" EMBED
STAINLESS STEEL
TITEN HD @24" O/C (ICC
ESR 2713) (2) MIN PER
THRESHOLD
1/2" EXP
JOINT FILLER
FIN GRADE
CONC PAVING
FACE OF CONC
SLAB
2 1
TOS
1/4" 1/4"
EXTERIOR INTERIOR
10".
M
AX
1/4"
3 1/2" MIN.
0'-0 3/8"CONTROL JOINT
CMU BLOCK WALL
FLANGED NEOPRENE
CONTROL JOINT, CONT
VERT
CONT REBAR PER
STRUCTURAL, DO NOT
BREAK AT JOINT
BACKER ROD AND
SEALANT, CONT EACH SIDE
TYP
0'-0 1/2"
0'-0 3/8"EXP JOINT
CMU BLOCK WALL
FLANGED NEOPRENE
CONTROL JOINT, CONT VERT
REBAR PER STRUCTURAL,
DO NOT CONTINUE
THROUGH JOINT
BACKER ROD AND
SEALANT, CONT EACH SIDE
TYP
0'-0 1/2"
CONTROL JOINT AT CMU WALL
EXPANSION JOINT AT CMU WALL
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
EXTERIOR DETAILS
A8.13
MD
MONROE ST. POOL REPLACEMENT
EXTERIOR DETAILS
3" = 1' -0"
A8.13 03 WALL EXPANSION JOINT
3" = 1' -0"
A8.13 04 INSULATED PIPE PENETRATION @ RATED WALL
1 1/2" = 1' -0"
A8.13 02 EXTERIOR CMU WALL BASE
3" = 1' -0"
A8.13 11 STOREFRONT SILL @ SLAB
6" = 1' -0"
A8.13 14 STOREFRONT DOOR SILL
3" = 1' -0"
A8.13 15 TYPICAL MASONRY CONTROL
JOINT
43 203
08/09/2024
203
MIN.
1 1/2"
SEALANT & BACKER
ROD ON BOTH SIDES
ALUM STOREFRONT
DRIP EDGE
SEALANT & BACKER
ROD ON BOTH SIDES
SEALANT BELOW
FLASHING
0'-2" VARIES 0'-2"
0'-0 1/2" 0'-0 1/2"
0'-0 5/8" 0'-2"
& WALL TYPES
PER FLOOR PLANS
METAL STUD WALL PER FLOOR
PLANS & WALL TYPES
DOOR, SEE DOOR SCHEDULE,
SEE FLOOR PLANS FOR DOOR
SWING
HOLLOW METAL
FRAME
BOX HEADER PER 6/S0.92
FINISH WHERE OCCURS PER
FINISH PLANS & INTERIOR
ELEVATIONS
8 5/8"
2"
8"X8"X16" CMU
HOLLOW METAL
FRAME, GROUT SOLID
AT JAMBS
SEALANT BOTH SIDES
JAMB ANCHORS
WOOD SHIM W/3/8" MIN.
CONT. SEALANT AND
BACKER ROD, BOTH
SIDES
CMU WALL. REFER
TO STRUCTURAL
EXTERIOR
INTERIOR
ALUMINUM
STOREFRONT SYSTEM
REFER TO FLOOR PLAN
FOR WALL TYPE AND
LOCATION
GLAZING UNIT
2" VARIES 2"
FINISH WHERE OCCURS PER
FINISH PLANS & INTERIOR
ELEVATIONS
DOOR, SEE DOOR SCHEDULE, SEE
FLOOR PLANS FOR DOOR SWING
ANCHOR PER
& AS REQ. PER MANUF.
HM FRAME ANCHORED TO HEADER
METAL STUD WALL PER
FLOOR PLANS & WALL TYPES
METAL STUD FRAMING PER 1/S0.91 EXT.
INT.
& WALL TYPES
PER FLOOR PLANS
0'-0 3/4" 0'-2"
6" MIN. TO F.O.STUD
NOTES:
1. LOCATE JAMB 6" FROM
F.O.STUD OF ANY ADJACENT
PERPENDICULAR WALL.
XXX
X
DOOR, SEE DOOR
SCHEDULE
BACKER ROD AND
SEALANT
1/2" EXPANSION JOINT
ZERO 673 ALUMINUM
ADJUSTABLE
THRESHOLD SET IN
FULL BED OF SEALANT,
REF: 08/A8.33
PAVING PER CIVIL OR
CONCRETE DECK PER
STRUCTURAL, SLOPE
AWAY FROM DOOR
EXT. INT.
C
AUTOMATIC DOOR
BOTTOM
ZERO 1545 ALUMINUM
THRESHOLD TRANSITION -
1/4" DIA x 1-5/8" EMBED
STAINLESS STEEL TITEN HD
@24" O/C (ICC ESR 2713) (2)
MIN PER THRESHOLD
ZERO 1675 ALUMINUM HALF-
SADDLE THRESHOLD
TRANSITION, REF:
FOR MITERED RETURN
1/4" DIA x 1-5/8" EMBED
STAINLESS STEEL TITEN
HD @24" O/C (ICC ESR
2713) (2) MIN PER
THRESHOLD
3" MIN.
NOTCH SLAB AS
NECESSARY TO RECIVE
THRESHOLD
3/8" CONT. BACKER ROD
AND SEALANT, BOTH
SIDES
EXT. INT.
GLAZING UNIT
SEE WALL SECTIONS
DIM POINT
ALUMINUM
STOREFRONT SYSTEM
1/4"Ø FLAT HEAD TAPCON
SCREW ANCHOR PER
ESR -1671 @ 16" O/C
STAGGERED 2" MIN
EMBEDMENT. 2" MIN EDGE
DISTANCE
2" MIN.
MASONRY LINTEL BLOCK
PER STRUCTURAL
MOUNTING BRACKET
PER MANUFACTURER
MANUAL ROLLER SHADE PER
CEILING PLAN AND INTERIOR
ELEVATION ( WHERE OCCURS)
NOTE:
1. SHADE CLOTH: ECOVEIL (OR EQUAL), 3% OPENING.
1/4" MASONRY SCREWS
WITH 2 -1/2" EMBED @ 16"
O.C. PER STRUCTURAL
DWG.
ALUM STOREFRONT SYSTEM
GLAZING UNIT
WEEP HOLES, TYP.
SEE WALL SECTIONS
DIM POINT
1/4"Ø FLAT HEAD TAPCON
SCREW ANCHOR PER
ESR -1671 @ 16" O/C
STAGGERED 2" MIN
EMBEDMENT. 2" MIN EDGE
DISTANCE
3/8" MIN. CONT. SEALANT AND
BACKER ROD, BOTH SIDES
MTL. FLASHING WITH END
DAMS, FINISH TO MATCH CMU
2" MIN.
DOOR, REF. DOOR
SCHEDULE
2" VARIES 2"
3/8" CONT. BACKER ROD
AND SEALANT, BOTH
SIDES
EXT. INT.
MASONRY LINTEL BLOCK
PER STRUCTURAL
DOOR FRAME, PAINT
TYP. GROUTED SOLID
DOOR ANCHOR TO
MASONRY WALL,
ANCHOR PER 01/A8.51
SEE DR SCHED
DIM POINT
0'-2"
0'-0 5/8"
OPENING
2" VARIES 2"
DOOR, SEE DOOR
SCHEDULE, SEE FLOOR
PLANS FOR DOOR SWING
EXT.
INT.
CONT. SEALANT AND
BACKER ROD, BOTH
SIDES
DOOR ANCHOR TO
MASONRY WALL, ANCHOR
PER 01/A8.51
REFER TO FLOOR PLAN
FOR WALL TYPE AND
LOCATION
0'-2" OPENING
SEE DR SCHED
DIM POINT
2" VARIES 2"
3/8" CONT. BACKER ROD
AND SEALANT, BOTH
SIDES
EXT. INT.
MASONRY LINTEL BLOCK
PER STRUCTURAL
DOOR FRAME, PAINT
TYP. GROUTED SOLID
3/8" DIA. S.S. HILTI KH -EZ
SCREW MIN. 2 1/2"
EMBED W/ 4" MIN. EDGE
DIST. (ESR -3056)
SEE DR SCHED
DIM POINT
0'-2"
0'-0 5/8"
OPENING
CLIP ANGLE
INSECT SCREEN
HIGH PERFORMANCE
FIXED DRAINABLE LOUVER
SYSTEM; PRE-FINISHED
TO MATCH HM FRAMES.
ANCHOR TO HM FRAME
JAMB PER DETAIL 07/A8.51
"U"-LINTEL BLOCK ONLY AT
ALL OPENING
FILL SMALL SPACES BETWEEN
BLOCK AND ROOF FRAMING WITH
GROUT. PAINT TO MATCH CMU.
MIN. DIM. OF CUT BLOCK SHOULD
NOT BE LESS THAN 4" IN ANY
DIRECTIONS
END WITH FULL/ HALF BLOCKS ON TOP
A TYPICAL ELEVATION
WINDOW AS SCHEDULED
BACKER ROD W/
SEALANT
SHIM AS REQUIRED
5/8" TYPE X GYP. BD.
6" METAL STUDS
FRAMING WITH R -19
BATT INSULATION
METAL STUD HEADER
METAL STUDS @ 16' O.C.
ACOUSTICAL BATT
INSULATION AS REQUIRED
PER WALL TYPE
6" METAL STUDS
FRAMING WITH R -19 BATT
INSULATION
SEE RCP
CONTINUOUS SEALANT,
BOTH SIDES (TYP.)
FIXED ALUMINUM
TRANSACTION WINDOW
AS SCHEDULED
5/8" TYPE "X" GYP. BD. TYP.
5"
CORRIDOR SIDE
ALIGN ON
7 1/4"
DRYWALL CORNER
BEAD, TYP.
BACKER ROD AND
SEALANT, BOTH SIDES
ALUMINUM
STOREFRONT WINDOW
AS SCHEDULED
6" METAL STUDS
FRAMING WITH R -19
BATT INSULATION
DOOR - SEE DOOR
SCHEDULE
SMOKE SEAL AT
RATED DOORS FLOORING, SEE
FINISH PLAN
SCHED.
PER
DOOR
FLOORING MATERIAL
TRANSITION AT
CENTERLINE OF DOOR
WHERE OCCURS, PER
FINISH SCHEDULE
T.O. SLAB
TILE OVER
THIN SET
INTEGRATED
DOOR ASSEMBLY,
SEE DOOR
SCHEDULE
T.O. SLAB
FLOOR FINISH,
PER FINISH
SCHEDULE
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
OPENING DETAILS
A8.14
MD
MONROE ST. POOL REPLACEMENT
OPENING DETAILS
3" = 1' -0"
A8.14 04 ALUM. STOREFRONT SIL
3" = 1' -0"
A8.14 10 INT HM DOOR HEAD @ GYP
3" = 1' -0"
A8.14 02 HEAD/JAMB/SILL - HM @ CMU
3" = 1' -0"
A8.14 05 ALUM. STOREFRONT HEAD Copy 1
3" = 1' -0"
A8.14 09 INT HM DOOR JAMB AT GYP
6" = 1' -0"
A8.14 15 EXTERIOR HM DOOR THRESHOLD
3" = 1' -0"
A8.14 03 ALUM. STOREFRONT HEAD1
3" = 1' -0"
A8.14 08 ALUM. STOREFRONT
SILL/COUNTER
3" = 1' -0"
A8.14 06 EXT. H.M. DOOR HEAD
3" = 1' -0"
A8.14 12 EXT. H.M. DOOR JAMB
3" = 1' -0"
A8.14 13 EXT. H.M. LOUVER HEAD
1/4" = 1' -0"
A8.14 01 TYP. CMU OPENING OR END WALL
3" = 1' -0"
A8.14 11 W11 - WINDOW HEAD MWP
3" = 1' -0"
A8.14 16 WINDOW HEAD - INT STOREFRONT
3" = 1' -0"
A8.14 19 HEAD/JAMB/SILL - INT
STOREFRONT
3" = 1' -0"
A8.14 14 INTERIOR DOOR THRESHOLD
3" = 1' -0"
A8.14 17 INTEGRATED DOOR THRESHOLD
Copy 1
44 203
08/09/2024
203
ROOF MEMBRANE
FLASHING HOT AIR
WELDED TO ROOFING
MEMBRANE. EXTEND
UNDER CLAMPING RING.
5/8" GYP.
COVER BOARD
THERMOPLASTIC
ROOFING
ROOF AND OVERFLOW
DRAIN
EXTEND FLASHING UNDER
CLAMPING RING.
UNDER DRAIN CLAMP
LOOSE BATT INSULATION
WITHIN VAPOR JACKET.
SLOPE
SLOPE
SLOPE
W
L
L:W RATIOS FOR SADDLES AND CRICKETS
NOTE:
1. SADDLES SHOULD BE LOCATED
BETWEEN ROOF DRAINS.
ROOF
SLOPE
SADDLE MATERIAL
SLOPE
L:W
RATIO
1/4" 1/2" 3:1
3/8" 1/2" 3:1
1/2" 1/2" 4:1
07.43 6" MIN
8" MIN.
NOTE:
VENT STACKS AND
OTHER PIPES SHALL
HAVE A MIN OF 12" OF
CLEARANCE ON ALL
SIDES FROM WALLS,
CURBS, AND OTHER
PROJECTIONS.
1" MIN. RIGID INSUL,
WHERE
OCCURS
ROOF PENETRATION (STL
PIPE, TUBE, OR SIMILAR ITEM)
SS STL HOSE CLAMP WITH
SEALANT ALL AROUND
ROOFING MEMBRANE BOOT
FLASHING, HOT AIR WELD TO
BASE FLASHING
ROOFING MEMBRANE BASE
FLASHING, HOT AIR WELD TO
ROOF MEMBRANE
THERMOPLASTIC
MEMBRANE ROOFING
MTL ROOF DECK OR CONC FILLED
MTL ROOF DECK, SEE STRUCTURAL
PLANS FOR TYPE
END CLOSURE PL
PER STRUCTURAL
DETAIL 4 AND 5/S0.22
SEALANT, CONT,
PROVIDE BACKER
ROD AS REQ
5/8" ROOF
BOARD
8" MIN.
NOTES:
1. CURB SHALL HAVE A MIN
OF 12" OF CLEARANCE ON
ALL SIDES FROM WALLS,
CURBS, AND OTHER
PROJECTIONS.
2. PROVIDE PREFABRICATED
CORNER FLASHING AT ALL
CORNER CONDITIONS.
3. PROVIDE MIN 16 GA
FLASHING.
4. ALL EXPOSED FASTENERS
TO BE FULLY COVERED
WITH SEALANT.
TERMINATION BAR,
FASTENERS AT 8" OC
THERMOPLASTIC MEMBRANE
ROOFING
ROOFING MEMBRANE
FLASHING, HOT AIR WELDED
TO ROOF MEMBRANE
GALV FLASHING REGLET
5/8" ROOF BOARD
RIGID
INSULATION,
WHERE
OCCURS
BLOCKING, AS
REQUIRED
MTL ROOF DECK OR CONC
FILLED MTL ROOF DECK, SEE
STRUCTURAL PLANS FOR TYPE
SHEET MTL GASKETED
FASTENER, 12" OC MIN, TYP
WOOD
NAILER
DUCT
SHEET MTL
GASKETED
FASTENER, 12"
OC MIN, TYP
PREFABRICATED
CURB ASSY
WITH
INTEGRATED
CAP FLASHING
PACK WITH
FIBERGLASS
INSULATION
ALL AROUND
CONTINUOUS
SEALANT TOP
AND BOTTOM
GALV
FLASHING
CONT
SEALANT
CONT
SEALANT
SLOPE
SLOPE
SLOPE
SLOP E
SLOPE
SLOPE
2'-0"MIN CLR
W
L
L:W RATIOS FOR SADDLES AND CRICKETS
AND MIN. SADDLE/CRICKET SLOPE
NOTE:
1. SADDLES SHOULD BE LOCATED IN
VALLEY BETWEEN ROOF DRAINS, AND
CRICKETS SHOULD BE LOCATED ON
THE HIGH SIDE OF CURBS.
ROOF
SLOPE
SADDLE
MATERIAL
SLOPE
L:W
RATIO
1/4" 1/2" 3:1
3/8" 1/2" 3:1
1/2" 1/2" 4:1
CURBED PENETRATION
BUILT-UP SADDLE OR
CRICKET, SLOPE A MIN OF
1/2" PER FOOT
ROOF AND OVERFLOW
DRAIN, SEE DETAIL 01/-
BUILT-UP SADDLE OR
CRICKET, SLOPE A MIN OF
1/2" PER FOOT
08 A8.21 TYP.
0'-2"
WHERE OCCURS
BLOCK OUT AT CONC FILLED MTL DECK
THERMOPLASTIC
MEMBRANE ROOFING
MIN 5/8" ROOF BD
ROOFING MEMBRANE
FLASHING, HOT AIR WELDED TO
ROOF MEMBRANE, EXTEND
UNDER DRAIN CLAMP RING
ROOF AND OVERFLOW DRAINS,
PROVIDE UNDER DRAIN CLAMPS, REFER
TO PLUMBING DWGS FOR TYPE.
OVERFLOW DRAIN TO HAVE INSERT
STANDPIPE; 2" ABOVE FIN ROOF.
BARE MTL DECK, CONC FILLED
MTL DECK, WITH RIGID INSUL OR
CONC FILLED MTL DECK.
TAPERED RIGID INSUL
BARE MTL DECK OR
CONC FILLED MTL DECK
THERMAL INSULATION,
WHERE OCCURS
LOOSE BATT INSULATION
WITHIN VAPOR JACKET, TYP
UNDER DRAIN
CLAMP, TYP
HOT AIR WELD, TYP
HIGH DOMED SS
FASTENERS W/ SS BACKED
EPDM WASHER @ 18" OC
MECHANICAL EQUIPMENT,
REFER TO MECH. DWGS.
CONTINUOUS SEALANT
20 GA SHEET METAL
REGLET,
GALVANIZED
HIGH DOMED HOT DIP
FASTENERS W/ GALV
BACKED EPDM WASHER AT
12" OC MAX
STEEL BENT PLATE,
REFER TO STRUCT
DWGS
STEEL PLATE
PER STRUCT
METAL DECK
PER STRUCT
STEEL BEAM PER
STRUCT
ROOF BOARD OVER RIGID
INSULATION, WHERE
OCCURS CONDITION BARE METAL DECK
ROOFING MEMBRANE
FLASHING, HOT AIR
WELDED TO ROOF
MEMBRANE
THERMOPLASTIC
MEMBRANE ROOFING
SECUREMENT BAR AND
FASTENER BY ROOFING
MANUFACTURER
8" MIN
CONTINUOUS SEALANT
ROOFING MEMBRANE
FLASHING, HOT AIR WELDED
TO ROOF MEMBRANE
12" MIN
12" MIN
12" MIN
4" MIN
6" MIN
4" MIN
12" MIN
4" MIN
6" MIN
TPA MECHANICALLY FASTENED ROOF MEMBRANE
METAL DECKING PER STRUCTURAL
STEEL BEAM BEYOND PER STRUCTURAL
R-30 RIGID INSULATION
1/4" COVER BOARD
ADHERED TAPERED INSULATION,
WHERE OCCURS PER PLAN
HOT AIR WELD AT LAP, TYP.
OMG XHD #15 ROOFING FASTENER W/ 2 3/8"
BARBED STRESS PLATES FASTENED 12" O.C.
FOR FIELD SHEETS (6' WIDE) AND 6" O.C. AT
PERIMETER SHEETS (2 SHEETS, 3' WIDE). MIN.
3 THREADS ENGAGEMENT THROUGH METAL
DECK, TYP.
CONSTRUCTION SPECIALTIES
BRJW-800 CF JOINT
CONSTRUCTION SPECIALTIES
BASE CLOSURE
CONSTRUCTION SPECIALTIES
SC-800 JOINT
FIELD APPLIED SPLICE COVER
REGLET AND
COUNTERFLASHING
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
ROOF DETAILS
A8.21
MD
MONROE ST. POOL REPLACEMENT
ROOF DETAILS
12" = 1' -0"
A8.21 18 ROOF DRAIN AT SINGLE PLY
ROOFING SYSTEM
1/4" = 1' -0"
A8.21 03 TYPICAL ROOF CRICKETS AT SCUPPER AND COLLECTOR BOX 12" = 1' -0"
A8.21 14 TYP PIPE / PLUMBING VENT
PENETRATION AT MTL DECK ROOF
12" = 1' -0"
A8.21 12 DUCT PENETRATION THROUGH
ROOF
1/4" = 1' -0"
A8.21 10 TYPICAL ROOF SADDLES AND CRICKETS
1" = 1' -0"
A8.21 08 TYP ROOF AND OVERFLOW DRAIN SECTION
3" = 1' -0"
A8.21 15 FLASHING AT MECH PLATFORM
1" = 1' -0"
A8.21 09 TYP ROOF SPACING
3" = 1' -0"
A8.21 19 TYP. ROOF SECTION - METAL
DECK
1" = 1' -0"
A8.21 04 ROOF TO WALL JOINT TRANSITION
45 203
08/09/2024
203
0'-6" 1'-3" 1'-3" 0'-6"
MIN. MIN.
0'-6" 1'-6" 2'-0" 1'-6" 0'-6"
MEMBRANE
FLASHING, HOT AIR
WELDED TO SINGLE-
SINGLE PLY ROOFING
SYSTEM
OVERFLOW DRAIN
WITH 2" WATER DAM
ROOF DRAIN, SEE
LINE OF TAPERED
INSULATION
NOTES:
1. ROOF AND OVERFLOW DRAIN
LOCATIONS & CONFIGURATION
PER ARCHITECTURAL &
PLUMBING ROOF PLAN.
5'-0"
AT CONC.
MET. DECK
AT MET.
DECK
TPA MEMBRANE
HEAT WELDED LAP
TPA UNREINFORCED
MEMBRANE
TPA BONDING ADHESIVE
STAINLESS STEEL
CLAMP
TREMSEAL SEALANT
ROOF ASSEMBLY
REF:
#15 FASTENER w/2
3/8" BARBED STRESS
PLATES FASTENED
METAL CURB
COUNTERFLASHING
TPA MEMBRANE
TPA FLASHING MEMBRANE
FULLY ADHERED TO
VERTICAL SUBTRATE
HEAT WELDED LAP
TPA BONDING ADHESIVE
#15 FASTENER w/2 3/8"
BARBED STRESS PLATES
FASTENED @ 12" O.C.
ROOF ASSEMBLY
REF:
TPA MEMBRANE TO WRAP
OVER TOP OF CURB
SECURE ROOF CAP TO
ROOF CURB WITH #8 ALUM.
SELF TAPPING SCREWS 12"
O.C. MIN. 2 PER SIDE
STRUCTURAL STEEL, REFER
TO STRUCT. FRAMING PLAN
FASTENER PER
STRUCTURAL DRAWINGS.
REF: 09A/S6.91
CONT. BENT PLATE PER
STRUCTURAL DRAWINGS.
REF: 09A/S6.91
T.O. ROOFING
8" M
IN.
EXHAUST FAN. REF.
MECH. DRAWING
0'-7"
16 GA. METAL STUD BACKING
3/8" x 2" BENT STEEL PLATE
WELD TO VERTICAL @
4' -0" O.C. MAX. (PER OSHA)
INTERIOR FINISH
NOTE:
PROVIDE 16 GA. METAL
STUDS AT ALL WALLS
THAT ROOF ACCESS
LADDER IS ATTACHED
1" DIA. STEEL RUNGS @
12" O.C.
3/8" x 2" STEEL BARS
0'-10" 1'-0"
2 1/2" x 2 1/2" x 3/8"
METAL ANGLE
3/8" DIA. X 2 1/2" EMBED.
HILTI KB TZ2. (ESR 4266)
2'-0" CLR.
0'-7"
1" DIA. STEEL RINGS @ 12" O.C.
WELDED TO 3/8" x 2" STEEL RAIL
STEEL BENT PLATE LADDER
SUPPORT, ANCHORED TO 16 GA.
METAL STUD BACKING, 1/4" DIA.
HILTI KWIK FLEX @ EACH BRACKET
WALL TYPE PER PLAN
(MIN 6X16GA)
PLAN VIEW
SECTION
16GA BLOCKING
CONDENSING UNIT.
REF. MECH DRAWING
NEOPRENE ISOLATOR PADS
MECHANICAL
PLATFORM, REFER TO
STRUCTUAL
ANCHORAGE TABS ,
REFER TO MECHACNIAL
FOR ATTACHMENT
NOTE:
1. SEE STRUCTURAL DETAIL 15/S6.12 FOR PLATFORM DETA ILS.
TPA MEMBRANE
TPA FLASHING MEMBRANE
FULLY ADHERED TO
VERTICAL SUBTRATE
HEAT WELDED LAP
TPA BONDING ADHESIVE
#15 FASTENER w/2 3/8"
BARBED STRESS
PLATES FASTENED @
12" O.C.
ROOF ASSEMBLY
REF:
TPA MEMBRANE TO WRAP
OVER TOP OF CURB
STRUCTURAL STEEL, REFER
TO STRUCT. FRAMING PLAN
8" M
IN.
6" CONCEALED
SPLICE PLATE
AT EA. JOINT
2X SHAPED
PTDF WOOD
BLOCKING
T.O.
PARAPET
EXTERIOR CEMENT
PLASTER SYSTEM
SLOPE 1/2" PER FT.
20 GA. GALV. SHEET
METAL COPING,
PAINTED
CONT. CLEAT
METAL STUD
FRAMING PER
STRUCTURAL
SELF ADHERING
SHEET MEMBRANE
FLASHING
#12 P.H.S.M.S. FASTENER
WITH NEOPRENE
WASHER AT 12" O.C.
0'-3"
0'-4"
BLOCKING TO
PARAPET HEAD W/
#12 FLATHEAD SMS
W/ WASHER AT 16"
O.C. STAGGERED
0'-1" MIN. E.D.
0'-1" MIN. E.D.
T.O. PARAPET
PER ELEVATION
SHAPED HOLDOWN
CLEAT, TYP.
#10 SMS @ 16" O.C., TYP.
TPA MEMBRANE TO WRAP
OVER TOP OF BLOCKING
U937 FOR 1-HR RATED
CONDITION
METAL COPING CAP,
PAINTED P-2
0'-4"
MIN 1/2" : 1' 0" SLOPE
FIRE TREATED BLOCKING
AT WHERE REQUIRED
3/8" DIA. HILTI KB-TZ2
ANCHORS WITH 2" MIN.
EMBED @ 16" O.C. (ESR
4561), REFER TO S0.01,
SECTION G.1
STRUCTURAL STEEL, REFER
TO STRUCT. FRAMING PLAN
FASTENER PER
STRUCTURAL DRAWINGS.
REF:
CONT. BENT PLATE PER
STRUCTURAL DRAWINGS.
REF: 09A/S6.91
T.O. ROOFING
8" M
IN.
TPA MEMBRANE
22 GA. GALV. PAN
HEAT WELDED LAP
TPA UNREINFORCED MEMBRANE
#15 FASTENER w/2 3/8" BARBED
STRESS PLATES FASTENED @ 12" O.C.
ROOF ASSEMBLY
REF:
TPA MANUFACTURER APPROVED
SEALANT
S.S. HOSE CLAMP
3/16" ALUMINUM BRACKET @ 4'-0" O.C MAX.
BY MANUFACTURER
S.S. 3/8" DIA. HILTI KH -EZ BOLTS W/ 3 -1/4" EMBED.
CLR
1'-6" M
IN
(2) 1/4" DIA X 3/4" S.S HEX HEAD MACHINE
BOLT W/ NUT AND LOCK WASHER.
1-1/4" SQUARE ALUM. EXTRUDED
SERRATED RUNG
3" X1" X1/8" EXTRUDED ALUMINUM
CHANNEL RAIL ALLOY6063 -T5.
#12 X 1-1/2" HEX HEAD S.S SELF
TAPPING SCREW
EXTRUDED ALUMINUM
PLATE ALLOY 6063 -T5
CLR.
7" MIN. LINE OF ROOF HATCH
ABOVE
1'-2"
1'-2"
A8.22
14 8" M
IN
ROOF SYSTEM, SEE
ROOF PLANS FOR TYPE
CLR
0'-7"
SHEET MTL
SCREWS #12
AT 12" OC
16 GA BENT PLATE,
CONT ALL (4) SIDES,
TYP GALV, PT TO
MATCH ADJ SURFACE
WHERE EXPOSED TO
VIEW.
ROOF HATCH LADDER
STRUCTURAL STL -
REFER TO
STRUCTURAL DWG CONDITION AT
BARE METAL DECK
ROOF HATCH AND CURB ASSEMBLY WITH INTEGRAL
CAP FLASHING AND 1" RIGID INSULATION AROUND
CURB - SEE 16/A8.00
LADDER UP SAFETY POLE
STL RUNGS, 1" DIA x 24" @ 12" OC
0'-7"
NOTE:
ALL METAL TO BE PTD, COLOR:XXXX.
1'-0"
1'-0"
0'-10"
2'-0"
BENT PL, 3/8" x 2", WELD TO
VERT @ 6'-0" OC MAX
1/2" DIA HILTI KBTZ - 3 1/4"
MIN EMBED. EA SIDE OF
VERT STL BAR
0'-4"
0'-8 1/2"
1/4 TOP & BOTTOM
BENT PL 3/8" x 2", WELD TO
VERT @ 6'-0" OC MAX, TYP
CLR
0'-7"
PLAN VIEW AT SUPPORT
24" CLR
LINE OF WALL FINISH
(2) #12 SHEET MTL SCREWS
BACKING PER XX/XX.XX, TYP
MTL STUD FRAMING, SEE S0.91
LINE OF WALL FINISH
VERTICAL LADDER, 3/8" X
2" STL BARS
LINE OF FINISH FLOOR
8" M
IN
ROOF SYSTEM, SEE
ROOF PLANS FOR TYPE
ROOF HATCH LADDER
STRUCTURAL STL -
REFER TO
STRUCTURAL DWG
ROOF HATCH AND CURB ASSEMBLY WITH INTEGRAL
CAP FLASHING AND 1" RIGID INSULATION AROUND
CURB - SEE 16/A8.00
LADDER UP SAFETY POLE
EXISTING ROOF
COVERBOARD
EXISTING CMU
WALL PER PLAN
EXISTING 3" X 8"
CONNECTION ROOF
STRUCTURE PER
STRUCTURAL
DRAWINGS
EXISTING ROOF
STRUCTURE
T.O.B
BLDG A
NEW WOOD BLOCKING
NEW PLYWOOD CRICKET
FRAMING
NEW METAL COPING TO MATCH
REMOVED EXISTING COPING
EXISTING FASCIA BOARD
M
IN.
8"
ALIGN WITH FACE OF CMU 2"
3'-4"
ROOF SCREEN ANCHOR
FRAMING / FLASHING SYSTEM
BY MANUFACTURER
ROOF SCREEN AND FRAMING
SYSTEM BY MANUFACTURER
(V.I.F.)
+/- 4'-4 1/4"
ROOF
COVERBOARD
RIGID INSULATION
CRICKET
NEW CMU PARAPET
WALL PER PLAN
METAL COPING
CONNECTION TO
CMU PER
SCTRUCTURAL
DRAWINGS
T.O.P
BLDG B
STRESS PLY PLUS FR MATERIAL MODIFIED MEMBRANE
FLASHING PLY 9" MIN. [228mm] ON FIELD
BASE FLASHING PLY 6" MIN. [152mm] ON FIELD
STRESS PLY PLUS FR MATERIAL
MODIFIED MEMBRANE
FELT PLIES
INSULATION WHERE
OCCURS, STAGGER
ALL JOINTS, FASTEN PER
SPECIFICATION
FLASHING, SEE SPECIFICATION
COUNTER FLASHING SET IN JOINT
DENSDECK SHEATHING
ATTACH PER MFG. RECOMMENDATIONS (USE 3
COURSE MASTIC WITH MESH OVER FASTENERS)
8" MIN.
SELF ADHERING FLEXIBLE FLASHING MEMBRANE
UP PARAPET WALL, OVERLAPING COUNTER
FLASHING CLEAT 4" MIN.
4" CANT STRIP
WALL FINISH PER WALL TYPE
8" M
IN
CMU WALL PER PLAN
CONT BEAD OF SEALANT
SS STL GROMMETED
FASTENER AT 12" OC
TERMINATION BAR,
FASTENERS AT 8" OC
COMPRESSIBLE DBL
SIDED WP TAPE
COMPRESSIBLE DBL
SIDED WP TAPE
ROOFING MEMBRANE FLASHING, HOT
AIR WELDED TO ROOF MEMBRANE
THERMOPLASTIC MEMBRANE
ROOFING
SECUREMENT BAR AND FASTENER
BY ROOFING MFR
RIGID INSULATION / CRICKET,
WHERE OCCURS
MASONRY FLASHING
REGLET, GALV
CMU WALL
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
ROOF DETAILS
A8.22
MD
MONROE ST. POOL REPLACEMENT
ROOF DETAILS
1/2" = 1' -0"
A8.22 04 ROOF - OVERFLOW DRAIN
3" = 1' -0"
A8.22 3TYP PIPE PENETRATION
1 1/2" = 1' -0"
A8.22 10 UPBLAST EXHAUST FAN FLASHING
1" = 1' -0"
A8.22 09 ACCESS LADDER
1 1/2" = 1' -0"
A8.22 6CONDENSING UNIT ON
MECHANICAL PLATFORM
3" = 1' -0"
A8.22 03 PARAPET COPING AT STUD WALL
3" = 1' -0"
A8.22 06 PARAPET COPING AT CMU WALL
1 1/2" = 1' -0"
A8.22 13 AIR INTAKE ROOF PENETRATION
1 1/2" = 1' -0"
A8.22 08 INTERIOR PREMANUFACTURED
LADDER PLAN1
1" = 1' -0"
A8.22 12 ROOF HATCH AT METAL DECK
1" = 1' -0"
A8.22 7ROOF ACCESS LADDER
1" = 1' -0"
A8.22 11 ROOF HATCH AT METAL DECK
1" = 1' -0"
A8.22 14 MECHANICAL ROOF SCREEN
1" = 1' -0"
A8.22 15 MECHANICAL ROOF SCREEN @
PARAPET
3" = 1' -0"
A8.22 02 TYP. REGLET & COUNTER
FLASHING AT STUD WALL
3" = 1' -0"
A8.22 05 TYP REGLET & COUNTER
FLASHING AT CMU WALL
46 203
08/09/2024
203
BOTTOM OF STRUCTURE
CEILING SYSTEM, WHERE
OCCURS SEE REFLECTED
CEILING PLAN
(1) LAYER OF 5/8" TYPE "X"
GYP BD BOTH SIDES, UNO,
SEE FINISH PLANS AND
ELEVATIONS
METAL STUD FRAMING PER
NOTES
ACOUSTICAL INSULATION
WHERE OCCURS
LINE OF CONCRETE CURB
WHERE OCCURS
CONTINUOUS SEALANT , BOTH
SIDES, TOP AND BOTTOM
CONTINUOUS TRACK TO
MATCH STUD SIZE
BOTTOM OF STRUCTURE
CONTINUOUS SEALANT , BOTH
SIDES
CONTINUOUS TRACK TO
MATCH STUD SIZE
CEILING SYSTEM, WHERE
OCCURS SEE REFLECTED
CEILING PLAN
(1) LAYER OF 5/8" TYPE "X"
GYP BD BOTH SIDES, UNO,
SEE FINISH PLANS AND
ELEVATIONS
METAL STUD FRAMING PER
NOTES
ACOUSTICAL INSULATION
WHERE OCCURS
UNO
0'-6"TYP
LINE OF CONCRETE CURB
WHERE OCCURS
BOTTOM OF STRUCTURE
CEILING SYSTEM, WHERE
OCCURS SEE REFLECTED
CEILING PLAN
(1) LAYER OF 5/8" TYPE "X"
GYP BD BOTH SIDES, UNO,
SEE FINISH PLANS AND
ELEVATIONS
METAL STUD FRAMING PER
NOTES
ACOUSTICAL INSULATION
WHERE OCCURS
LINE OF CONCRETE CURB
WHERE OCCURS
CONTINUOUS SEALANT
CONTINUOUS TRACK TO
MATCH STUD SIZE
STRAP OR BRIDGING
UNO
0'-6"
DESCRIPTION CATEGORY
STEEL STUDS S
WOOD STUDS W
TYPE
CORE/ STRUCTURE SIZE
SA2
BOTTOM OF STRUCTURE
CEILING SYSTEM, WHERE
OCCURS SEE REFLECTED
CEILING PLAN
(1) LAYER OF 5/8" TYPE "X"
GYP BD , UNO, SEE FINISH
PLANS AND ELEVATIONS
METAL CHANNELS 16" O.C.
VERT
CONTINUOUS SEALANT
UNO
0'-6"
ADJACENT WALL PER PLAN
ANCHOR
0'-0 1/4"
CEILING SYSTEM, WHERE
OCCURS SEE REFLECTED
CEILING PLAN
BOTTOM OF STRUCTURE
CEILING SYSTEM, WHERE
OCCURS SEE REFLECTED
CEILING PLAN
(1) LAYER OF 5/8" TYPE "X"
GYP BD , UNO, SEE FINISH
PLANS AND ELEVATIONS
METAL STUD FRAMING PER
NOTES
ACOUSTICAL INSULATION
WHERE OCCURS
LINE OF CONCRETE CURB
WHERE OCCURS
CONTINUOUS SEALANT
CONTINUOUS TRACK TO
MATCH STUD SIZE
0'-6"
ADJACENT WALL PER PLAN
CEILING SYSTEM, WHERE
OCCURS SEE REFLECTED
CEILING PLAN
BOTTOM OF STRUCTURE
CEILING SYSTEM, WHERE
OCCURS SEE REFLECTED
CEILING PLAN
(1) LAYER OF 5/8" TYPE "X"
GYP BD BOTH SIDES, UNO,
SEE FINISH PLANS AND
ELEVATIONS
METAL STUD FRAMING PER
NOTES
ACOUSTICAL INSULATION
WHERE OCCURS
LINE OF CONCRETE CURB
WHERE OCCURS
CONTINUOUS FIRE CAULKING,
BOTH SIDES, TOP AND
BOTTOM
CONTINUOUS TRACK TO
MATCH STUD SIZE
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
PARTITION TYPES
A9.01
MD
MONROE ST. POOL REPLACEMENT
PARTITION TYPES
SA PARTITION TYPE "SA" SB PARTITION TYPE "SB" SE PARTITION TYPE "SE"
PARTITION TYPE TAG
SA Walls
WALL TYPE STUD SIZE
SA3 3 5/8" STUDS
SA4 4" STUDS
SA6 6" STUDS
SB Walls
WALL TYPE STUD SIZE
SB4 4" STUDS
SB6 6" STUDS
SE Walls
WALL TYPE STUD SIZE
SE3 3 5/8" STUDS
SE4 4" STUDS
3" = 1' -0"
A9.01 SF PARTITION TYPE "SF" (FURRED
PARTITION)
SF Walls
WALL TYPE CHANNEL SIZE
SF0 7/8" CHANNEL
3" = 1' -0"
A9.01 SG PARTITION TYPE "SG"
SG Walls
WALL TYPE STUD SIZE
SG2 2 1/2" STUDS
SG3 3 5/8" STUDS
SG4 4" STUDS
SG6 6" STUDS
3" = 1' -0"
A9.01 SN PARTITION TYPE "SN" (1HR)
SN Walls
WALL TYPE STUD SIZE
SN6 6" STUDS
47 203
08/09/2024
203
SEE WALL TYPE
DOOR OPENING
SEE SCHEDULE
DOOR - SEE
DOOR
SCHEDULE
HOLLOW METAL
FRAME AND
ANCHOR -
SEE DOOR
SCHEDULE
0'-0 1/2" 0'-0 1/2"
CMU
8" CMU, SEE
STRUCTURAL FOR
HORIZONTAL AND
VERTICAL
REINFORCING
1/2" SEALANT AND
BACKER ROD, BOTH
SIDES
DOOR AND FRAME,
AS SCHED.
EQ. 6" EQ.
REF. SCHEDULE FOR FINISH
CMU WALL, PER PLAN
HOLLOW METAL DOOR FRAME,
GROUT PACKED
DOOR ANCHOR TO CMU WALL,
ANCHOR STRAP & ADJUSTABLE HAT
SECTION PER FRAME MANUFACTURER
DOOR PER DOOR SCHEDULE
NOTE:
FOR FRAME ANCHOR, SEE
EXTERIOR INTERIOR
0'-2"
CONTINUOUS SEALANT AND
BACKER ROD BOTH SIDES
PARALLEL ARM, PUSH SIDE
MOUNTED DOOR CLOSER, TYP
7 3/4" MAX.
3/8" 1' - 10"
PORCELAIN
TILE
THIN SET
3/8" RADIUS BRUSHED
STAINLESS STEEL
SCHLUTER -DILEX -HKU
COVE AT BASE.
HKUR10EB
5/8" GYP. BD.
METAL STUD
1/8"
0'-0 1/2"
1' 9 1/2"TILE HEIGHT 0'-0 1/8" GROUT
0'-0 3/16"
WALL TILE, PER FINISH
SCHEDULE
WALL, PARTITION TYPE PER
FLOOR PLAN
0'-6"
COATED GLASS MAT WATER-
RESISTANT GYPSUM BACKER BD.
COVED BASE TRIM PIECE
FLOOR TILE PER FINISH PLAN
NOTE:
PROVIDE WATERPROOFING UNDER
TILE WORK, TYP. SEE
SPECIFICATIONS
WALL TILE PER FINISH PLANS
HOLLOW METAL DOOR FRAME
DOOR PER DOOR SCHEDULE
FRAME ANCHOR - SEE
0'-0 1/2" MAX.
WALL TYPE PER FLOOR PLAN
ALIGN
0'-2"
PACK WITH INSULATION
SEE PLAN FOR PARTITION TYPE
FULL WALL TILE PER FINISH PLAN
AND INTERIOR ELEVATIONS
SCHLUTER EDGE, TYP
STEEL PLATE, REFER TO 13/S6.72
METAL DECK
TOP TRACK PER STRUCTURAL DRAWINGS
MINERAL FIBRE INSULATION
MIN (2) FLUTES
SPECSEAL SMOKE 'N' SOUND SPRAY
GRADE, TYP. BOTH SIDES. PAINT TO
MATCH ADJACENT SURFACE.
TOP TRACK PER STRUCTURAL DRAWINGS
METAL DECK
METAL STUD
DO NOT FASTEN GYP BD TO TRACK (TYP)
SOUND INSULATION AS NOTED
SPECSEAL SMOKE 'N' SOUND SPRAY
GRADE, TYP. BOTH SIDES. PAINT TO
MATCH ADJACENT SURFACE.
WALL PARALLEL TO DECK BETWEEN FLUTES - AT SLIP CONNECTION. WALL PERPENDICULAR TO DECK - AT SLIP CONNECTION .
WALL TYPE PER PLAN
WALL PERPENDICULAR TO DECK - AT RIGID CONNECTION.
12 GA 'Z' CHANNEL FOR RIGID CONNECTION
SOUND BATT INSULATION AS NOTED
METAL DECK
MINERAL FIBRE INSULATION
SPECSEAL SMOKE 'N' SOUND SPRAY
GRADE, TYP. BOTH SIDES. PAINT TO
MATCH ADJACENT SURFACE.
WALL TYPE PER PLAN
WALL PARALLEL TO DECK - AT RIGID CONNECTION.
MINERAL FIBER INSULATION
FASTENER TYPE AND SPACING PER
13/S6.72
FASTENER TYPE AND SPACING PER
13/S6.72
METAL STUD
DO NOT FASTEN GYP BD TO TRACK (TYP)
SOUND INSULATION AS NOTED
WALL TYPE PER PLAN
FASTENER TYPE AND SPACING PER
13/S6.72
METAL DECK
SPECSEAL SMOKE 'N' SOUND SPRAY
GRADE, TYP. BOTH SIDES. PAINT TO
MATCH ADJACENT SURFACE.
MINERAL FIBER INSULATION
DO NOT FASTEN GYP BD TO TRACK (TYP)
SOUND INSULATION AS NOTED
WALL TYPE PER PLAN
FASTENER TYPE AND SPACING PER 13/S6.72
TO DECK
1/4" MAX.
TO DECK
1/4" MAX.
@ FRAMED GYP. CEILING
SEE RCP
CEILING HEIGHT
WALL PER PLAN
1/4 -20 x 1 -1/2" SELF DRILLING SELF
TAPPING SCREW WITH LOCK WASHER
(PROVIDE 1 SCREW AT EACH END
AND @ 48" O.C. INTERMEDIATE. 2
SCREWS MINIMUM EACH FIXTURE.)
MAX WEIGHT 5LBS PER LF.
KICKER AND CONNECTION TO DECK
SEE STRUCTURAL
600S162 -43 METAL STUDS
@ 16" O.C., TYP.
FOR SIZE & SPACING OF
STUDS, SEE SCHEDULE ON
5/8" GYP. BD.
0'-3"
12 S6.72
16 S6.72
BACKING TRACK PER
SEE RCP
CEILING HEIGHT
FOR SIZE & SPACING OF
STUDS, SEE SCHEDULE ON
5/8" GYP. BD.
16 S6.72
SURFACE MOUNTED LIGHT
FIXTURE PER LIGHTING
PLAN E3.00; FASTENED TO
PL WITH (8) 1/4" BOLT WITH
NUT AND WASHER
PL MATCHING STUD GAX32"
WIDE SPANNING MIN (3)
STUDS W/ #10 SCREWS @
12" O/C EA STUD
1".
3/8" X 3" WIDE BENT PLATE -
PAINT TO MATCH SHELVING
HEAVY -DUTY METAL CABINET
3/8" DIA. HILTI KH -EZ MASONRY
SCREWS W/ 3 -1/4" EMBED. (ICC
ESR #3056) (1) @ EA. LEG (4 MIN.
PER SHELVING UNIT)
(2) #10 S.M.S. PER ANGLE CLIP
T.O. CABINET
0'-2" 0'-3" 0'-1"
+6' - 6" A.F.F.
3/8" DIA. S.S. HILTI KH-EZ
MASONRY SCREWS W/
3-1/4" EMBED. (ICC ESR #
3056) @ 6" BELOW T.O. OF
EACH LOCKER. REFER TO
S0.01, SECTION G.1
LOCKER PER
SPECIFICATION
WALL TYPE PER PLAN
FIN. FLOOR
(WHERE OCCURS)
0'-6"
3/8" DIA. S.S. HILTI KH-EZ
MASONRY SCREWS W/
3-1/4" EMBED. (ICC ESR #
3056) @ 6" ABOVE B.O. OF
EACH LOCKER. REFER TO
S0.01, SECTION G.1
RIPPED 2x6 P.T. WOOD
BLOCKING TO 1"
MIN. (2) COUNTERSUNK
3/8" DIA. HILTI KH-EZ
MASONRY SCREWS W/
3-1/4" EMBED. (ICC ESR #
3056) @ 32" O.C. REFER
TO S0.01, SECTION G.1
CONT. 1x6 P.T.
WOOD BLOCKING
MIN. (2) COUNTERSUNK
3/8" DIA. HILTI KH-EZ
MASONRY SCREWS W/
3-1/4" EMBED. (ICC ESR #
3056) @ 32" O.C.
1/8" THICK GALVANIZED
STEEL PLATE. SEE
FOR DETAIL
3" MIN.
0'-2"
0'-2"
0'-8" MAX.
27" A.F.F.
3/8" DIA. HILTI KH-EZ
MASONRY SCREWS W/ 3-1/4"
EMBED. (ICC ESR #3056) (1) @
EA. LEG (4 MIN. PER SHELVING
UNIT)
CABINET PER SPECIFICATION
WALL TYPE PER PLAN
NOTES:
1. MOUNT ALL F.E.C. 18" CLEAR FROM DOR U.O.N. ON FL OOR PLAN
2. FIRE EXTINGUISHER TO BE 4A40B
3. FIRE EXTINGUISHERS NOT TO BE LOCATED IN PATH OF TRAVEL.
4. UL-RATED 3-A:40-B:C AT CHEMICAL STORAGE, PUMP RO OM, LOCKER ROOMS, AND WHERE INDICATED ON DRAWINGS.
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
INTERIOR DETAILS
A9.11
MD
MONROE ST. POOL REPLACEMENT
INTERIOR DETAILS
3" = 1' -0"
A9.11 02 DOOR HEAD AT CMU
3" = 1' -0"
A9.11 04 HEAD DETAIL
3" = 1' -0"
A9.11 05 DOOR HEAD - HOLLOW METAL
DOOR @ CMU WALL
6" = 1' -0"
A9.11 14 TILE COVE BASE
3" = 1' -0"
A9.11 11 TILE AT TOP AND BASE
3" = 1' -0"
A9.11 08 DOOR JAMB - HOLLOW METAL
DOOR AT TILE
6" = 1' -0"
A9.11 09 TILE @ CORNER
3" = 1' -0"
A9.11 03 NON-RATED WALL AT METAL DECK
1 1/2" = 1' -0"
A9.11 1RECESSED LINEAR WALL SLOT
LIGHT
1 1/2" = 1' -0"
A9.11 6RECESSED LINEAR WALL SLOT
LIGHT
3" = 1' -0"
A9.11 7METAL SHELVING ANCHORAGE @
WALL
3" = 1' -0"
A9.11 10 METAL LOCKER ANCHORAGE
3" = 1' -0"
A9.11 12 SURFACE MOUNTED FEC
48 203
08/09/2024
203
F550 INSIDE CORNER ALUMINUM TRIM
MOLDING, BY MARLITE OR EQUAL
F565 DIVISION ALUMINUM TRIM
MOLDING, BY MARLITE OR EQUAL
48"X 96" FIBERGLASS REINFORCED PANEL
BY MARLITE, P-199 BRITE WHITE
F560 STAINLESS STEEL OUTSIDE
CORNER GUARD ALUMINUM TRIM
MOLDING, BY MARLITE OR EQUAL
PER MFR PER MFR
PER MFR PER MFR
TYP. PANEL WIDTH
96"
10'-0" U.N.O. 0'-4"
FIBERGLASS REINFORCED PANEL,
(FRP) SEE FINISH SCHEDULE
F565 DIVISION ALUMINUM
TRIM MOLDING BY
MARLITE OR EQUAL
F570 EDGE ALUMINUM TRIM
MOLDING BY MARLITE OR
EQUAL @ TOP AND BOTTOM
OF PANEL
INTEGRAL EPOXY
COVED BASE, SEE
DETAIL 07/A9.41
WALL, SEE FLOOR
PLANS FOR WALL TYPE
F550 INSIDE CORNER ALUMINUM TRIM
MOLDING BY MARLITE, OR EQUAL
F560 OUTSIDE CORNER GUARD
ALUMINUM TRIM MOLDING BY
MARLITE OR EQUAL 03
A9.12
TYP.
WALL PER PLAN
5/8" GYP. BOARD.
1" ACOUSTIC PANEL. PREP
WALL TO RECEIVE LOW V.O.C.
ADHESIVE. SEE (AP-1) ON
FINISH SCHEDULE
FOR MOUNTING HEIGHT
SEE INTERIOR ELEVATION
FOR MOUNTING HEIGHT
SEE INTERIOR ELEVATION
0'-1"
DOOR, WHERE OCCURS
CARPET TILE
CONCRETE SLAB
CARPET / SEALED OR POLISHED CONCRETE
CONCRETE FLOOR
PER FINISH PLAN
1/4" MAX.
NOTE:
1. UNDERCUT ALL DOORS TO CLEAR FLOOR FINISH BY 1/4" EXCEPT AT RATED DOORS, U.O.N. IN DOOR SCHEDULE.
2. FOR FLOORING FINISHES WITH 1/4" OR LESS HEIGHT VARIANCE, PROVIDE TRANSITION STRIP AS INDICATED.
1 2
DOOR, WHERE OCCURS
RUBBER FLOORING,
REFER TO FINISH PLAN
CONCRETE SLAB
RUBBER FLOORING / SEALED OR POLISHED CONCRETE B
A
SEALED CONCRETE
PER FINISH PLAN
ALUMINUM SCHLUTER
RENO -U 6MM
ALUMINUM SCHLUTER
RENO -U 6MM, 2:1 MAX.
SLOPE
2 1
MAX.
1/2" MAX.
MAX.
FRAME BEYOND
DOOR, SEE DOOR
SCHEDULE
CHANGE FLOOR FINISHES AT
CENTER LINE OF DOORS,
TYPICAL
FINISHED FLOOR
PER PLANS
ARIZONA TILE "QTZ -2"
QUARTZ THRESHOLD
SET IN MASTIC
THIN SET TILE PER
FINISH PLANS
0'-0 1/2"
V.I.F.
0'-0 1/2"
RUBBER FLOORING / SEALED OR POLISHED CONCRETE C
1/4" MAX.
1/2" MAX.
2 1
MAX.
WALL FINISH AND
FRAMING PER PLANS
COVED RUBBER
BASE
WALL FINISH AND
FRAMING PER PLANS
STRAIGHT RUBBER
BASE
A (AT CONCRETE, TYP. @ BACK OF
HOUSE AREAS)
B
(AT CARPET, RUBBER &
WOOD FLOORING - U.N.O.)
4".
WALL FINISH AND
FRAMING PER PLANS
STRAIGHT RUBBER
BASE
C (AT RESILIENT FLOORING)
CMU WALL
NO BASE
D (AT CMU WALL)
4"
4"
WALL TYPE PER FLOOR PLAN;
WALL FINISH PER ELEVATION
GLASS BOARD, SEE INTERIOR
ELEVATIONS FOR LOCATIONS
AND CUSTOM SIZING
Z-BAR PER MANUFACTURER
@ 2' -0" O.C., 6" MAX. FROM
EDGE OF PANEL.
T.O. BOARD
SEE INTERIOR ELEVATION
#10 SMS @ 16"O.C.
TYP. BACKING REF:
MAX.
2'-0" O.C.
MAX.
6 " 1" X 1/2" 14 G.A. ALUMINUM
'L' ANGLE ALIGN BOTTOM
LEG W/ F.O. GLASSBOARD,
ATTACH W/ #10 SMS @16"
O.C. MITER AT CORNERS
PLAN DETAIL
1"
B.O. BOARD
SEE INTERIOR ELEVATION 1/2" 1" X 1/2" X 3" 14 G.A. ALUMINUM 'U'; ALIGN BOTTOM LEG W/ F.O. GLASSBOARD,
ATTACH W/ #10 SMS @16" O.C.
MAX.
6".
'TRU MOUNT' BY
MANUFACTURER ADHERED
TO GLASS IN FACTORY.
1/2" 1/2"
1/2"
1" X 1" X 1" 14 G.A. ALUMINUM 'U'; ALIGN
BOTTOM LEG W/ F.O. GLASSBOARD,
ATTACH W/ #10 SMS @16" O.C.
#10 SMS @ 16"O.C.
PRE TAPPED HOLE WITH
FLATHEAD SCREW @ 16" O.C.
1"
1/2".
1"
/- ---
SEE INTERIOR ELEVATION
1/2" THICK PLYWOOD, TYP.
MIRROR, REFER TO INTERIOR
ELEVATION FOR SIZES
HORIZONTAL FRENCH CLEAT, TYP.
MIRROR EDGE, D514BA BRITE
ANODIZED FINISH, DEEP NOSE 1/4"
ALUM. J-CHANNEL, TYP.
ATTACHMENT TO CMU
AT 16" O/C, TYP. CMU WALL PER PLAN
B. O. MIRROR
SEE INTERIOR ELEVATION
TYP. STAINLESS STEEL STUD
MOUNT W/ 1 -1/2" PROJECTED
SPACER W/ BLACK FINISH
1/4" THICK SHEET METAL
PAINTED W/ BLACK ENAMEL
PAINT. SEE INTERIOR
ELEVATION FOR MAP PATTERN
WALL PER PLAN
POSITIVLY FIX SCREWS TO
BACK OF PANEL, DRILL AND
TAP METHOD OR EQ.
U.N.O.
24" M
AX.
12" = 1' -0"
A9.12 03 FRP PANEL SECTION DETAIL
3/4" = 1' -0"
A9.12 08 FRP PANEL PLAN DETAIL
3" = 1' -0"
A9.12 05 ACOUSTIC PANEL ATTACHMENT
3" = 1' -0"
A9.12 01 TYP. INTERIOR FLOOR
TRANSITIONS
3" = 1' -0"
A9.12 09 RUBBER BASE (B-1)
6" = 1' -0"
A9.12 04 GLASSBOARD WALL SECTION
3" = 1' -0"
A9.12 07 MIRROR WALL - SECTION
3" = 1' -0"
A9.12 06 STUD MOUNTING
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
INTERIOR DETAILS
A9.12
MD
MONROE ST. POOL REPLACEMENT
INTERIOR DETAILS
49 203
08/09/2024
203
EQ EQ EQ EQ
LIGHT FIXTURE, TYP
TYPICAL ELEC DEVICE
SPEAKER MECH DIFFUSER
EQ EQ
NOTES:
1. CENTER DEVICE ON LIGHT FIXTURE OR MECH DIFFUSER WHERE OCCURS.
2. IN ACT CLGS, CENTER DEVICES IN CLG TILE, NO MORE THAN TWO DEVICES PER 2x4 TILE.
3. IN ACT CLGS, IF ONLY ONE DEVICE OCCURS, CENTER DEVICE IN TILE, BOTH DIRECTIONS.
4. WHERE MULTIPLE DEVICES OCCUR, CONSOLIDATE INTO ONE AREA WHERE POSSIBLE.
CONDITION AT ACT CEILING
CONDITION AT GYP CEILING
SEE RCP
FOR SIZE & SPACING OF
JOISTS, SEE SCHEDULE ON
CEILING PER PLAN
WALL AND FINISH PER PLAN
LIGHT FIXTURE PER ELECTRICAL /
LIGHTING PLANS
1/4 -20 x 1 -1/2" SELF DRILLING SELF
TAPPING SCREW WITH LOCK WASHER
(PROVIDE 1 SCREW AT EACH END
AND @ 48" O.C. INTERMEDIATE. 2
SCREWS MINIMUM EACH FIXTURE.)
3".
WALL TILE, WHERE OCCURS
PER PLANS
TYPE A PERIMETER STARTER WALLS,
GRID ATTACHED TO
(2) ADJACENT WALLS
(4) EACH 12 GA. SPLAY
WIRES (SEE NOTE #5)
12 GA. HANGER WIRES AT
4'-0" OC EACH WAY
ALONG MAIN RUNNERS
12 GA. HANGER WIRES AT 8"
FROM ALL WALLS AT ALL MAIN
RUNNERS & CROSS TEES
OPPOSITE FREE WALLS, NO
GRID ATTACHMENT - 1/2"
MIN. CLEAR
FIXTURES, SUPPORT PER NOTES
CROSS TEES
AT 24" OC
MAIN
RUNNERS
AT 48" OC
REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION
NOTES:
1. CLASSIFICATION OF CEILING GRID IS: HEAVY DUTY.
2. THESE PLANS AND SPECIFICATIONS ARE FOR CEILING S YSTEMS WHOSE WEIGH
INCLUDING AIR CONDITIONING GRILLES & LIGHT FIXTURES DOESN'T EXCEED FOUR (4) PSF HEAVIER SYSTEMS AND THOSE SUPPORTING LATERAL LOADS FROM PARTITIONS WILL REQUIRE SPECIAL DESIGN DETAILS.
3. SPLICES WILL NOT BE PERMITTED IN ANY HANGER WIRE S.
4. PROVIDE TRAPEZE OR OTHER SUPPLEMENTARY SUPPORT M EMBERS AT OBSTRUCTIONS TO MAIN HANGER SPACING. PROVIDE ADDITIONAL HANGERS,
STRUTS OR BRACES AS REQUIRED AT ALL CEILING BREAKS, SOFFITS OR DISCONTINUOUS AREAS. HANGER WIRES THAT ARE MORE THAN 1 IN 6 OUT OF PLUMB SHALL HAVE COUNTER-SLOPING WIRES.
5. PROVIDE SETS OF FOUR 12 GA. SPLAYED BRACING WIRE S ORIENTED 90 DEGREES FROM EACH OTHER AT THE FOLLOWING SPACING:
A. FOR SCHOOL BUILDINGS, PLACE SETS OF BRACING WIRE S NOT MORE THAN 12'x12' OC
B. PROVIDE BRACING WIRES AT LOCATIONS NOT MORE THAN 1/2 THE SPACING
GIVEN IN 'A' ABOVE FROM EACH PERIMETER WALL AND AT THE EDGE OF VERTICAL CEILING OFFSETS FOR BOTH SCHOOL AND HOSPITAL BUILDINGS.
6. FASTEN HANGER WIRES WITH NOT LESS THAN (3) TIGHT TURNS. FASTEN BRACING WIRES WITH (4) TIGHT TURNS. MAKE ALL TIGHT TURNS WITHIN A DISTANCE OF 3".
HANGER OR BRACING WIRE ANCHORS TO THE STRUCTURE SHALL BE INSTALLED IN
SUCH A MANNER THAT THE DIRECTION OF THE WIRE ALIGNS AS CLOSELY AS POSSIBLE WITH THE DIRECTIONS OF THE FORCES ACTING ON THE WIRE.
7. SEPARATE ALL CEILING HANGING AND BRACING WIRES A T LEAST 6 INCHES FROM ALL UNBRACED DUCTS, PIPES. CONDUIT, ETC. IT IS ACCEPTABLE TO ATTACH LIGHTWEIGHT ITEMS, SUCH AS SINGLE ELECTRICAL CONDUIT NOT EXCEEDING 3/4" NOMINAL DIAMETER, TO HANGER WIRES.
8. ATTACH ALL LIGHT FIXTURES TO THE CEILING GRID RU NNERS TO RESIST A HORIZONTAL FORCE EQUAL TO THE WEIGHT OF THE FIXTURES. ALL LIGHT FIXTURES SHALL BE ATTACHED SECURELY TO THE GRID WITH (4) SCREWS, ONE AT EACH CORNER OF THE FIXTURE.
9. FLUSH OR RECESSED LIGHT FIXTURES AND AIR TERMINA LS OR SERVICES WEIGHING LESS THAN 56 POUNDS MAY BE SUPPORTED DIRECTLY ON THE RUNNERS OF A HEAVY DUTY GRID SYSTEM BUT, IN ADDITION, THEY MUST HAVE A MINIMUM OF (2) 12 GA. SLACK SAFETY WIRES ATTACHED TO THE FIXTURES AT DIAGONAL CORNERS AND ANCHORED TO THE STRUCTURE ABOVE. ALL 4'x4' LIGHT FIXTURES MUST HAVE SLACK SAFETY WIRES AT EACH CORNER.
10. ALL FLUSH OR RECESSED LIGHT FIXTURES AND AIR TERMINALS OR SERVICES WEIGHING 56 POUNDS OR MORE MUST BE INDEPENDENTLY SUPPORTED BY NOT LESS THAN (4) TAUT 12 GA. WIRES EACH ATTACHED TO THE FIXTURE AND AT THE STRUCTURE ABOVE REGARDLESS OF THE TYPE OF CEILING GRID SYSTEM USED.
THE (4) TAUT 12 GA. WIRES INCLUDING THEIR ATTACHMENT TO THE STRUCTURE ABOVE MUST BE CAPABLE OF SUPPORTING FOUR TIMES THE WEIGHT OF THE UNIT.
11. SUPPORT SURFACE MOUNTED LIGHT FIXTURES BY AT LE AST TWO POSITIVE DEVICES
WHICH SURROUND THE CEILING RUNNER AND WHICH ARE EACH SUPPORTED FROM THE STRUCTURE ABOVE BY A 12 GA. WIRE. SPRING CLIPS OR CLAMPS THAT CONNECT ONLY TO THE RUNNER ARE NOT ACCEPTABLE. PROVIDE ADDITIONAL SUPPORTS WHEN LIGHT FIXTURES ARE 8 FEET OR LONGER.
12. SUPPORT PENDANT MOUNTED LIGHT FIXTURES DIRECTLY FROM THE STRUCTURE
ABOVE WITH HANGER WIRES OR CABLES PASSING THROUGH EACH PENDANT HANGER AND CAPABLE OF SUPPORTING FOUR TIMES THE WEIGHT OF THE FIXTURE.
ATTACH ALL LIGHT FIXTURES TO THE CEILING GRID RUNNERS TO RESIST A HORIZONTAL FORCE EQUAL TO THE WEIGHT OF THE FIXTURES. SPECIAL DETAILS ARE NECESSARY FOR THIS CONDITION AT THE CEILING GRID.
13. PROVIDE ALL REQUIRED COMPONENTS (INCLUDING APPR OVED CEILING GRID SEISMIC CLIPS) FOR "CEILING SEISMIC DESIGN" - CBC SECTION #1614A.1.21 (a) SJCG CLIP
08 A9.21
05 A9.21
10 A9.21
COMPRESSION STRUT
SCHEDULE
MAX LENGTH
OF STRUT
STRUT
8' -0"
3 5/8" x 25 GA
"C" - STUDS
SSMA
DESIGNATION
362S125 -18
STEEL STUD
COMPRESSION
STRUT;
SEE SCHEDULE
REMOVE
FLANGES
TO PROVIDE
TIGHT
FIT ON TOP OF
MAIN RUNNER
(2) #12 SMS
SCREWS
THROUGH MAIN
RUNNER &
STUD
WEB
MAIN RUNNER
10' -0"
2 - 1 5/8" x 25 GA
"C" - STUDS
SEE DET. BELOW
15' -0"
2-2 1/2" x 25 GA.
"C" - STUD
SEE DET. BELOW
20' -0"
2-3 5/8" x 25 GA.
"C" - STUD
SEE DET. BELOW
STEEL C STUDS
PER SCHEDULE
3/8" S -12 (12 GA.)
SCREWS AT 12" O.C.
AND 6" FROM ENDS.
162S125 -18
250S125 -18
362S125 -18
A
A
FOR ATTACHMENT TO
STRUCTURE, RE:
NOTES:
1. COMPRESSION STRUTS SHALL NOT REPLACE HANGAR WIRE.
2. CEILING TILE NOT SHOWN FOR CLARITY.
A9.30
07 MIN OPNG 22"x30"
DOUBLE STUD FRAMING, TYP
HINGE
STEEL FRAME
KEYLOCK & PULL
J MOLDING TYP
PAINTED GYP BD
HEAVY DUTY
CEILING GRID
SYSTEM
CLG. GRID CLIP
BOTH ENDS
CEILING LIGHT
FIXTURE
(2) #12 SLACK WIRES
@ DIAGONAL
LOCATIONS.
(4) #12 WIRES IF
MORE THAN 55 LBS.
LATERAL FORCE BRACING MEMBERS MUST BE SPACED A MINIMUM OF 6" FROM
ALL HORIZONTAL PIPING OR DUCT WORK THAT IS NOT PROVIDED WITH BRACING RESTRAINTS FOR HORIZONTAL FORCES. BRACING WIRES MUST BE ATTACHED
TO THE GRID & TO THE STRUCTURE IN SUCH A MANNER THAT THEY CAN SUPPORT A DESIGN LOAD OF NOT LESS THAN 200 LBS OR THE ACTUAL LOADS, WHICHEVER IS GREATER, WITH A SAFETY FACTOR OF 2.
NOTE: (4) NO. 12 GAUGE WIRES MUST BE SECURED TO
THE MAIN RUNNER WITHIN 2" OF THE CROSS RUNNER
INTERSECTION & SPLAYED 90 DEGREES FROM EACH
OTHER AT AN ANGLE NOT EXCEEDING 45 DEGREES
FROM THE PLANE OF THE CEILING.
CEILING PANEL
MTL STUD BLOCKING
WALL AND FRAMING
PER PLAN
7/8" SHADOW MOLD
OR WITHIN 1/4" OF THE
LENGTH OF THE END
TEE, WHICHEVER IS
LEAST
7/8" 3/4"
8" MAX OR WITHIN 1/4" OF
THE LENGTH OF THE END
TEE, WHICHEVER IS
LEAST.
ARMSTRONG 'BERC 2'
CLIP. ACCEPTABLE TO
IBC PER ESR-1308
MAIN "T" @ 48" OC
CROSS "T" @ 24" OC
12 GA HANGER WIRES AT
4'-0" OC EA WAY W/ 3
TIGHT TURNS IN 3"
SECURE WIRES TO
STRUCTURE
ABOVE, REFER TO
12 GA HANGER WIRES AT
4'-0" OC EA. WAY W/ 3
TIGHT TURNS IN 3"
AT METAL STUD WALL: #10
SMS, AT MASONRY WALL:
1/4" MASONRY SCREWS WITH
2-1/2" EMBED PER F/S0.01,
AT CONCRETE WALL:
1/4" CONCRETE SCREWS
WITH 2-1/2" EMBED PER
F/S1.O1
0'-8 1/256"MAX
A9.30
07 OR WITHIN 1/4" OF THE
LENGTH OF THE END
TEE, WHICHEVER IS
LEAST.
7/8"
12 GA HANGER WIRES AT
4'-0" OC EA WAY WITH 3
TIGHT TURNS IN 3"
MAIN "T" @ 48" OC
CROSS "T" @ 24" OC
CEILING PANEL
METAL STUD BLOCKING
SECURE WIRES TO
STRUCTURE ABOVE,
REFER TO
SHADOW MOLD
12 GA HANGER WIRES AT
4'-0" OC EA WAY W/ 3
TIGHT TURNS IN 3"
ARMSTRONG'S
'BERC 2' CLIP.
ACCEPTABLE TO
IBC PER ESR-1308
SCREW TIGHTENED
THROUGH MAIN RUNNER
WEB RESTRICTING
SEPARATION FROM WALL
MOLDING
AT METAL STUD WALL: #10
SMS, AT MASONRY WALL:
1/4" MASONRY SCREWS
WITH 2-1/2" EMBED PER
F/S0.01, AT CONCRETE
WALL: 1/4" CONCRETE
SCREWS WITH 2-1/2"
EMBED PER F/S1.O1
A9.30
07 8" MAX
8" MAX OR WITHIN 1/4"
OF THE LENGTH OF
THE END TEE,
WHICHEVER IS LEAST.
CEILING JOIST FRAMING
(2) #10x1 3/4" SELF TAPPING
SCREWS
STL STRAP
3" WIDE x 4" LONG x 10 GA MIN
10 GA HANGER WIRE WITH
MIN 3 TIGHT TURNS IN 1 1/2"
AT VERTICAL HANGER WIRE
0'-0 177/256"MAX
WALL, PER PLAN
AT MTL STUD WALL: #10 SMS, AT
MASONRY WALL:
1/4" MASONRY SCREWS WITH
2-1/2" EMBED PER F/S0.01
AT CONCRETE WALL: 1/4"
CONCRETE SCREWS WITH 2-1/2"
EMBED PER F/S0.01
STL STRAP 3" WIDE x 4" LONG x
10 GA MIN
10 GA HANGER WIRE WITH
MIN 3 TIGHT TURNS IN 1 1/2"
AT SPLAYED WIRE
M
AX
0'-0 177/256"
AT VERTICAL HANGER WIRE
MTL STUD WALL FRAMING
AT MTL STUD WALL: #10 SMS,
AT MASONRY WALL: 1/4"
MASONRY SCREWS WITH
2 -1/2" EMBED PER F/S0.01 AT
CONCRETE WALL: 1/4"
CONCRETE SCREWS WITH
2 -1/2" EMBED PER F/S0.01
STL STRAP 3" WIDE x 4"
LONG x 10 GA MIN
10 GA HANGER WIRE WITH
MIN 3 TIGHT TURNS IN 1-1/2"
MAX
0'-0 177/256"
NOTE:
AT MTL STUD WALLS,
PROVIDE BACKING AS REQ.
12 GA VERTICAL HANGER WIRE
AT 4'-0" EA WAY WITH MIN 3
TIGHT TURNS IN 3" BOTH ENDS
OF WIRE, TYPICAL.
COMPRESSION STRUTS REQ
AT EA SET OF BRACING
WIRES, TYP ATTACH
COMPRESSION STRUT TO
MAIN RUNNER WITHIN 2" OF
CROSS RUNNER.
(4)-12 GA SPLAYED WIRES 90
DEGREES APART HORIZ WITH
MIN 4 TIGHT TURNS IN 1-1/2"
BOTH ENDS OF WIRE TYPICAL.
WIRES SHOULD BE TAUT
WITHOUT CAUSING THE
CEILING TO LIFT- NO SPLICES
PERMITTED.
45° MAX
VERT TYP
2" MAX. FROM BRACING
WIRES TO CROSS
RUNNERS
MAIN RUNNER
CROSS RUNNER
COMPRESSION STRUTS: STL
SECTION WITH L/R RATIO OF 200
MAX COMPRESSION STRUT SHALL
NOT REPLACE HANGER WIRE,
REFER TO
NOTES:
1. FOR CONNECTIONS OF BRACING & HANGER WIRES TO THE
STRUCTURE ABOVE, REFER TO
A9.30
08 A9.30
10 #12 GA. VERTICAL WIRE NOTE: 1/8" POP RIVET @
ALL MEMBERS ON WALL
CLR.
0'-8"
CLR.
0'-8"
MAIN RUNNER OR CROSS T
HORIZONTAL STRUT
TYPICAL CONTINUOUS ACOUSTICAL BOARD
WALL ANGLE
PROVIDE 1/2" SPACE
OPPOSING WALL
VERT. STRUT FASTENED TO MAIN
RUNNER-EXTEND AND FASTEN TO
UNDERSIDE OF STRUCTURE ABOVE
12'-0" O.C. IN BOTH DIRECTIONS WITH
THE FIRST POINT WITHIN 6'-0" FROM
EACH WALL PER ASTM #C635 AND
#C636 AND CHAPTER 23 OF THE
CALIFORNIA BUILDING CODE.
# 12 HANGER WIRE A 4'-0"
O.C. IN BOTH DIRECTIONS
ALL HANGER AND SPLAY
WIRES TO HAVE A MINIMUM
OF 3 TURNS IN 1" RUN.
#12 GA. SPLAY WIRE BRACING
IN PLANE OF EACH RUNNER
VERTICAL ANGLE = 45 (12'
O.C. IN BOTH DIRECTIONS /
144 SQ.FT. MAX.) START
WITHIN 4'-0" OF WALL.
MAIN RUNNER
CROSS TEE
NOTE: CONTRACTOR TO FIELD VERIFY EXISTING CONDITION WHERE EXISTING GRID OCCURS AND MAINTAIN FLOATING VS. FIXED AT ADJACENT GRID.
TYP.
45 º
0'-6"
MTL STUD KICKER
PER STRUCTURAL
EXTEND GYP BD 6"
ABV ADJ CLG
SEE RCP
ALIGN FACE OF CLG
PANEL WITH FACE
OF GYP BD
WALL ANGLE
AT TRANSITION
CORNER BEAD (TYP)
CLG OR SOFFIT JOISTS,
SEE STRUCTURAL
DRAWINGS
SEE RCP
1/2" = 1' -0"
A9.21 14 TYPICAL DEVICE LAYOUT
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
CEILING DETAILS
A9.21
MD
MONROE ST. POOL REPLACEMENT
CEILING DETAILS
3" = 1' -0"
A9.21 11 PERIMETER SLOT LIGHT @
RESTROOMS
6" = 1' -0"
A9.21 02 CEILING REQUIREMENTS1
1/2" = 1' -0"
A9.21 04 COMPRESSION STRUT
1 1/2" = 1' -0"
A9.21 06 HORIZONTAL ACCESS PANEL1
12" = 1' -0"
A9.21 09 LIGHT FIXTURE AT ACT
3" = 1' -0"
A9.21 05 OPP WALL OF STARTER WALL
REVEAL EDGE
3" = 1' -0"
A9.21 08 PERIMETER STARTER WALL -
SHADOW
6" = 1' -0"
A9.21 8SEISMIC BRACING CONNECT. TO
CLG
6" = 1' -0"
A9.21 12 SEISMIC BRACING CONNECT. TO
WALL
12" = 1' -0"
A9.21 10 SPLAY BRACING DETAIL1
3/4" = 1' -0"
A9.21 15 SUSPENDED CEILING GRID
3" = 1' -0"
A9.21 16 CEILING TRANSITION
50 203
08/09/2024
203
VARIES
FINISH PLUG TO MATCH
CABINET INTERIOR FINISH
STUD WALL
1x4 WALL CLEAT WITH NO. 10 x 2" SELF
TAPPING SHEET METAL SCREWS INTO
METAL STUDS OR BLOCKING. ATTACH
CABINET TO CLEAT WITH NO 8 x 1 1/4"
WOOD SCREWS @ 16" O.C. (TYP.)
DETAIL E
(METAL ANCHORAGE)
DETAIL D
(BLOCKING)
VARIES
DOOR OR EDGE OF OPENING
BLOCKING 2x
#6 FHWS @ 12" OC W/ 1 -1/2"
EMBED
#10 FHPH 3" COUNTERSUNK,
MIN 4" FROM EA END & 16" OC
2x4 WOOD SUPPORT
3/8" DIA. HILTI KWIK -BOLT TZ
(ICC -ESR 1917) W/ 2"
EMBEDMENT, LOCATE 4" FROM
EA END AND 24" OC
#10 FHPH COUNTERSUNK
SCREWS X 2 -1/2", MIN 2" FROM
EA END & 16"OC PROVIDE
PLASTIC CAP TO MATCH
COLOR OF PLAM
#10 FHPH COUNTERSUNK
SCREWS X 2 -1/2", MIN 2" FROM
EA END & 16"OC PROVIDE
PLASTIC CAP TO MATCH
COLOR OF PLAM
3/8" DIA. HILTI KWIK -BOLT TZ
(ICC -ESR 1917) W/ 2"
EMBEDMENT, LOCATE 4" FROM
EA END AND 24" OC
#10 FHPH 3" COUNTERSUNK,
MIN 4" FROM EA END & 16" OC
BLOCKING 2X4 CONTINUOUS,
PTDF
BLOCKING 2X4 CONTINUOUS,
PTDF
3/4" PLYWOOD CABINET RAIL
TYPE 1 -M-2 CABINET SIDE METAL BACKING CHANNEL
PER
#10 FHPH SELF TAPPING
SCREWS. SHEET METAL
SCREWS INTO BLOCKING OR
METAL STUDS @ 24" OC MIN
(2) SCREWS IN EACH
DIRECTION
GWB
3/4" PLYWOOD CABINET
INTERIOR
0'-6"
W.I. DESIGN SERIES
SEE INTERIOR ELEVATIONS
SEE ELEVATION VARIES
W.I. DESIGN SERIES
SEE INTERIOR ELEVATIONS
SEE ELEVATION
SEE ELEVATION
ADJUSTABLE SHELVES
CABINET W/ LOCK
LINE OF BOTTOM SHELF
LIGHT FIXTURE, WHERE OCCURS
HORIZONTAL MOUNTED PULLS, TYP
MATCH DOOR HARDWARE FINISH
BACKSPLASH, WHERE OCCURS,
SEE ELEVATION
DRAWERS, SEE ELEVATION
COUNTERTOP NOT TO EXCEED 1/2"
AT CABINET EXPOSED ENDS
ADJUSTABLE SHELF
BREAK AT ACCESSIBLE SINK DOORS -
PROVIDE FULL DOOR SWING,
INCLUDING TOE KICK
AT EXPOSED ENDS:
PROVIDE A 2" RECESS
BASE, SEE FINISH PLAN
ELEVATION A
FINISHED FLOOR
FINISHED CEILING
(SEE REFLECTED CEILING PLANS)
0'-2"
DRAWER ON FULL EXTENSION HEAVY
DUTY GLIDES, WHERE OCCURS, SEE
ELEVATION
SECTION B
LOWER CABINET
WITHOUT DRAWER
LOWER CABINET
WITH SINK
COUNTERTOP
ONLY
VARIES
0'-6"
@CMU
AND CONCRETE
GENERAL NOTES:
1. SEE SPECIFICATION SECTIONS 064000 & 064116.
2. CONSTRUCTION SHALL BE PER THE ARCHITECTURAL WOOD WORK INSTITUTE (WI) STANDARDS, LATEST EDITION.
3. FINISH PER PLANS, SCHEDULES, AND LEGEND.
4. WHITE THERMALLY FUSED MELAMINE AT CONCEALED INTE RIOR OF CABINETS, UNO
5. AT SINKS, WHEN DOORS OPEN 90° PROVIDE FOR 32" MI N CLEAR BETWEEN KICKS. SEE CBC SECTION 11B-603.3 FOR KNEE CLEARANCE.
6. NO SHARP OR ABRASIVE SURFACES UNDER SINK.
7. ALL JOINTS TO BE CAULKED WITH CLEAR SILICONE CAU LK.
8. WRAP HOT & COLD WATER SUPPLIES AND DRAIN PIPING W/ PVC INSULATION MATERIAL COMPLIANT WITH ASTM E84-07, 25 FLAME / 450 SMOKE INDEX.
9. INSTALL SECURE BACKING AT ALL THREE SIDES OF COU NTER.
10. 2x4 #1 DOUGLAS FIR LEDGER BACK & SIDE WALLS.
11. LOWER CABINET WITH SINK
A. INSULATE ALL EXPOSED HOT WATER AND DRAIN LINES U NDER SINK.
B. SEE CBC SECTION 11B-603.3 FOR KNEE CLEARANCE.
C. AREA HATCHED BELOW SINK SHALL BE ACCESSIBLE & CL EAR.
D. FAUCET CONTROLS TO BE LEVER OR A TYPE NOT REQUIR ING GRASPING, PINCHING, OR TWISTING OF THE WRIST W/ 5 LBS FORCE MAX TO OPERATE. (LOWER CABINET WITH DRAWER SHOWN)
VARIES, SEE
FINISH PLANS
SECTION C
(TALL CABINET)
54" MAX
SEE ELEVATIONS
VARIES, SEE
FINISH PLANS
CABINET W/ LOCK
0'-6"
E
DETAIL
TYP
F
DETAIL
TYP
D
DETAIL
TYP
E
DETAIL
TYP
F
DETAIL
TYP
F
DETAIL
TYP
E
DETAIL
TYP
E
DETAIL
TYP
F
DETAIL
TYP
D
DETAIL
TYP
XXX
X
A9.31
12 A9.31
12 A9.31
17/21
PLASTIC LAMINATE CABINET
DOOR
PLASTIC LAMINATE
ADJUSTABLE SHELF
PLASTIC LAMINATE FIXED
SHELF TYP
PLASTIC LAMINATE DOOR
STOP
RECESSED HEAVY DUTY
ADJUSTABLE SHELF
SUPPORTS WITH SHELF CLIPS
DOOR PULL , TYP - MATCH
DOOR HARDWARE FINISH,
UNO
DRAWER PULL
LIGHT FIXTURE , WHERE
OCCURS
VERIFY DIMENSION WITH
LIGHT FIXTURE
PLASTIC LAMINATE
ADJUSTABLE SHELF , TWO (2)
PLASTIC LAMINATE CABINET
DOOR
6" MAX
COUNTERTOP, SEE
ELEVATION
BACKSPLASH, WHERE
OCCURS, SEE ELEVATION
PLASTIC LAMINATE DOOR
STOP, TYP
CABINET DOOR PLASTIC
LAMINATE
ONE (1) PLASTIC LAMINATE
ADJUSTABLE SHELF
RECESSED HEAVY DUTY
ADJUSTABLE SHELF
SUPPORTS WITH SHELF CLIPS
DOOR PULL , VERTICAL
ORIENTATION AT TALL
CABINETS , TYP - MATCH
DOOR HARDWARE FINISH,
UNO
WALL FRAMING AND FINISH
PER PLAN SEE WALL TYPES.
FINISH PER SCHEDULE
RECESSED HEAVY DUTY
ADJUSTABLE SHELF
SUPPORTS WITH SHELF CLIPS
4" TAB PULLS, BRUSHED CHROME
MAX.
2'-0"
0'-1 1/2" TYP 0'-0 1/8" TYP
PROVIDE EXTERIOR GRADE
3/4" PLYWOOD MDF AT ALL
WET SINK LOCATIONS
0'-0 1/2" MAX
CABINET DOOR
WHERE OCCURS
DRIP EDGE AT WET SINK
LOCATIONS (1/8" RADIUS)
QUARTZ COUNTERTOP PER
PLAN
WALL PER PLAN
3/4" STONE MATERIAL, MITERED
CORNER, FILL AND SEAL SEAMS
ALL EQUAL
HEIGHT & QTY PER ELEVATION
FIXED
SHEVLES, TYP.
LOCK,
TYPICAL
WALL PER
PLAN
FINISH FLOOR
SEE ELEVATION FOR LOCKER CABINET
DESIGN, SPACING, QTY, AND DIMENSIONS
ACCESSIBLE
LOCKER
A9.31
01 PER RCP
SOFFIT PER RCP &
ELEVATION
TO OPERABLE PART
15" M
IN.
ACCESSIBLE
LOCKER
4"
TO OPERABLE PART
48" M
AX.
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
CASEWORK
DETAILS
A9.31
MD
MONROE ST. POOL REPLACEMENT
CASEWORK DETAILS
3" = 1' -0"
A9.31 01 CABINET ANCHORAGE
1" = 1' -0"
A9.31 02 TYPICAL UPPER/LOWER CABINETS
12" = 1' -0"
A9.31 10 QUARTZ COUNTERTOP
1" = 1' -0"
A9.31 13 LOCKER SECTION @ WALL
1 2nd PLAN CHECK
SUBMITTAL
04/24/24
51 203
08/09/2024
203
CABINET INTERIOR
METAL BACKING
PER
#10 x 2" SELF TAPPING SCREWS.
SHEET METAL SCREWS INTO
BLOCKING OR METAL STUDS @
24" O.C. MIN. (2) SCREWS IN
EACH DIRECTION
FINISH PLUG TO
MATCH CABINET
INTERIOR FINISH
STUD WALL
GYP.
BOARD
BASE PER FINISH
PLANS & ELEVATIONS
FINISH FLOOR
DOUBLE 16 GA. METAL STUDS AT
ANGLE SUPPORT
2" X 2" X 1/4" FLAT STEEL ANGLE AT
48" O.C. MAX. MIN. 2 - ATTACH TO
STUD OR HSS POST WITH #12 SMS
@ 6" O.C. PAINT TO MATCH WALL
FINISH/COLOR
BACKSPLASH WHERE
OCCURS - SEE ELEVATION
COUNTERTOP PER
FINISH PLANS
WALL FINISH PER PLAN
1. CONSTRUCTION SHALL BE W.I.C. 'CUSTOM' STANDARDS. FINISH PER FINISH PLANS AND LEGEND.
NOTES:
2. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES BELOW THE COUNTER.
EASED EDGE
U.N.O. ON PLANS
2'-0"
U.N.O.
1'-6" MIN.
0'-0 3/4"
0'-1 1/2"
(34" MAX. @ ACCESSIBLE STATION)
SEE ELEVATION
27" MIN. CLR.
2'-0" U.N.O.
WALL FINISH PER INTERIOR
ELEVATION AND FINISH
LEGEND
MITER AND BUTT WELD
RECYCLE SYMBOL ON METAL COIN
ROUTE PLASTIC LAMINATE TO
ACCEPT METAL COIN WITH
SYMBOL. SKU#: 1010 -2
TRASH SYMBOL ON METAL COIN.
2" 2"
1. BLOCK & ANCHOR EACH SIDE OF CABINET
3/4" TYPE 1 -M-2
PARTICLE BOARD
(CABINET SIDE)
#10 x 2 1/2" RHWS
@ 6" O.C.
1/2" HARDWOOD CABINET RAIL
2"x4" WOOD BLOCKING
CONTINUOUS
.145 DIA. LOW VELOCITY
FASTENERS (1 1/8" EMBED) ICC #
2269
@ 24" O.C. MIN (2 PER CABINET)
(3) #10 x 3" RHWS @ 6"
O.C.
NOTE:
3"
6"
3"
1'-0" 6" 6"
1' -0"
VARIES
FULL HEIGHT OF DESK
METAL STUD
1" X 1/2" DIAMETER MACHINE BOLT.
CONNECTION (TYPICAL) HEAD &
WASHER ON FRAMING BEYOND
2 1/2" x 2 1/2" x 1/4" ANGLE @ EACH
FREESTANDING END
(2) 1/2" DIA MECHANICAL FASTENER
(PER F/S1.01) - MIN 3 1/2" EMBED
CONTINUOUS
FLOOR RUNNER
COUNTERTOP WITH MITERED
EDGES PER SCHEDULE. SEE
INTERIOR ELEVATION
BASE TO MATCH MILLWORK
FINISH
4"
HAFELE DRAWER SLIDE-OUT
DOUBLE WASTE BIN - (2) X 40
LITER, US CARGO 21, SIDE
MOUNTED, SILVER #502 74 252.
21" MIN. WIDTH AS REQ'D.
DOOR MOUNT BRACKET
RECESSED 2" DIA.
STAINLESS STEEL DISK
WITH ROUTED TRASH
& RECYCLE GRAPHIC
3"
4" TAB PULL HARDWARE PER
SPECIFICATIONS
MIN.
1'-10 1/2" CLR.
A9.32
05 U.O.N.
2'-0" CLR.
1 1/4"
SEE ELEVATION
3"
NOTES:
1. SEE FINISH PLAN FOR FINISHES
2. CONST. SHALL BE 3/4" PART BD. WITH P. LAM. ON EX POSED SURFACES, INT.
SURFACES SHALL BE BLACK MELAMINE, U.O.N.
BACKSPLASH PER SCHEDULE
(WHERE OCCURS) SEE
INTERIOR ELEVATION
NOTES:
1. TRASH & RECYCLE LOGOS ONLY, U.N.O.
2. SEE INTERIOR ELEVATIONS FOR TRASH/RECYCLE CABINE T LOCATIONS
3. 1/18" X 2" DIAMETER BRUSHED ALUMINUM DISKS W/ BE AD BLASTED AND BLACK FILLED. RECESS FLUSH WITH FACE OF CABINET DOOR. MFR: ARCHITECTURAL HARDWARE. WEBSITE WWW.ARCHHARDWARE.NET. SKU#: 1010- 2
EQ EQ
O.C.
5 "
EQ EQ
O.C.
5 "
TRASH,
OR RECYCLE ONLY
COMBINED
TRASH AND
RECYCLE
A9.32
05 EQ EQ
PANTRY/ LONG
CABINET DOOR
UPPER CABINET
DOOR
LOWER CABINET
DOOR
DRAWER
NOTES:
1. LOCATE HARDWARE AS NOTED IN DETAIL, TYPICAL THRO UGHOUT
2. TYP. CABINET DOOR & DRAWER PULLS, SEE INTERIOR E LEVATIONS FOR CABINET TYPES PER N.A.A.W.S.
3. SEE SPEC FOR HARDWARE FINISH, BLACK FINISH U.N.O .
QUARTZ SURFACE
SEE INT. ELEV.
WALL PER PLAN
A9.32
09 QUARTZ COUNTERTOP
PER FINISH PLAN. MITER
CORNER, TYP.
CONCRETE FLOORING
PER FINISH PLAN
CONCEALED IN -WALL
BRACKET
CABINET WHERE OCCURS.
SEE INT. ELEV.
GROMMET AS REQUIRED
(MIN. 2 AT RECP. DESK)
POWER OUTLET
WHERE OCCURS
3"
PER ELEVATION
QUARTZ SURFACE
SEE INT. ELEV.
QTZ TRANSACTION
COUNTER BEYOND
QUARTZ SURFACE
SEE INT. ELEV.
WALL PER PLAN
A9.32
09 QUARTZ COUNTERTOP
PER FINISH PLAN. MITER
CORNER, TYP.
CONCRETE FLOORING
PER FINISH PLAN
CONCEALED IN -WALL
BRACKET
MOBILE STORAGE, OFOI
GROMMET AS REQUIRED
(MIN. OF 2 GROMMETS)
POWER OUTLET
WHERE OCCURS
3"
PER ELEVATION
9"
2X4 WOOD FRAMING, 16" O.C
WOOD FRAMING, 16" O.C
1'-0"
QTZ TRANSACTION COUNTER
RETUNR BEYOND
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
CASEWORK
DETAILS
A9.32
MD
MONROE ST. POOL REPLACEMENT
CASEWORK DETAILS
3" = 1' -0"
A9.32 13 ANCHORAGE AT METAL STUD
1" = 1' -0"
A9.32 18 TYP. COUNTER SUPPORT (AS
REQ'D.)
12" = 1' -0"
A9.32 05 PULL-OUT COIN
3" = 1' -0"
A9.32 09 CABINET ANCHORAGE1
1 1/2" = 1' -0"
A9.32 14 BRACING @ FREE STANDING LOW
WALLS
1" = 1' -0"
A9.32 17 PULL-OUT TRASH
6" = 1' -0"
A9.32 21 TRASH / RECYCLE EMBLEM
6" = 1' -0"
A9.32 22 CABINET HORIZONTAL PULL
1 1/2" = 1' -0"
A9.32 23 RECEPTION DESK - LOW
1 1/2" = 1' -0"
A9.32 24 RECEPTION DESK - TRANSACTION
52 203
08/09/2024
203
TOILET PARTITION
ANODIZED
ALUMINUM ANGLE
WALL PER PLAN
BACKING PER
1/4" SMS EA. SIDE W/
RUBBER WASHER @ 48"
O.C. MAX.
BACKING PER
1 1/2" STD. PIPE GRAB BAR W/
MOUNTING CONCEALED PLATE
ANCHOR MOUNTING
PLATE TO BACKING
PLATE W/ (3) - #12
S.M.S.
5/8" GYPSUM BOARD
STUD WALL
GRAB BAR COLLAR
1 1/2" CLR.
1 1/2" STD. PIPE GRAB BAR W/
MOUNTING CONCEALED PLATE
ANCHOR MOUNTING
PLATE TO BACKING
PLATE W/ (3) - #12
S.M.S.
STUD WALL
GRAB BAR COLLAR
1 1/2" CLR.
PLAN
WALL PER PLAN
START FULL TILE
BEHIND TILE ON
ADJACENT SURFACE
LINE OF TOILET
PARTITION
WHERE OCCURS
ANOD. ALUM. CORNER
TRIM - EXTEND TO TOP
OF TILE - SCHLUTER
'INDEC'
FASTENER LOCATION, TYP.
NOTES:
USE 1/4" x 3" PANHEAD TAPPING SCREWS AT FASTENER LOCATIONS. PRIOR TO FASTENING, DRILL W/ 1/2" MASONRY BIT AND INSTALL FASTENERS W/
TOGGLES PER MANUFACTURER INSTRUCTIONS
FLOOR DRAIN
2' - 0"
2' - 0"
.
.
. .
FLOOR FINISH PER FINISH PLANS
2% SLOPE,
TYP.MAX.
EQ EQ
EQ EQ
+0' - 0" A.F.F. AT 4 SIDES & CORNERS
-0' - 1/4" AT DRAIN
.
..
PLAN @ CONCRETE FLOOR SECTION @ FINISHED CONCRETE FLOOR
FLOOR FINISH PER FINISH PLANS
OPENINGS
1/4" MAX.
SEALANT
S.S. FLOOR DRAIN
CONCRETE SLAB
N.T.S.
FLOOR DRAIN WITH
STRAINER, RE:
PLUMBING
(MAX. 1/4" OPENINGS)
SEALANT
WATERPROOFING MEMBRANE
CONCRETE
(SLOPED TO DRAIN)
CONCRETE
SLAB ON
GRADE
1. FOR ADDITIONAL INFORMATION SEE F101 (TCA HANDBOOK).
NOTE:
SLOPE
2% MAX. TYP.
6"
CONCRETE
SLAB ON
GRADE
FLOOR SINK WITH
STRAINER, RE:
PLUMBING
SEALANT ON
ALL SIDES
SOLID SURFACE -
REFER TO ELEVATION &
FLOOR PLANS
1'-6"
1'-6"
FINISH PER PLAN
PER PLAN
WALL
1/2" PLY WOOD OVER
METAL STUDS, 16" O.C.
BRACING 24" O.C.,
(2) MIN. PER BENCH
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
RESTROOM
DETAILS
A9.41
MD
MONROE ST. POOL REPLACEMENT
RESTROOM DETAILS
3" = 1' -0"
A9.41 1PARTITION DETAIL
3" = 1' -0"
A9.41 2GRAB BAR @ METAL STUD
3" = 1' -0"
A9.41 3GRAB BAR @ CMU WALL
3" = 1' -0"
A9.41 4WRAPPED WALL TILE
1 1/2" = 1' -0"
A9.41 5BABY CHANGING STATION
3" = 1' -0"
A9.41 6FLOOR DRAIN DETAILS
3" = 1' -0"
A9.41 7FLOOR DRAIN AT CONCRETE
FLOOR
3" = 1' -0"
A9.41 8FLOOR DRAIN AT CONCRETE
FLOOR
1 1/2" = 1' -0"
A9.41 10 BENCH @ SHOWERS /LOCKERS
53 203
08/09/2024
203
NON -CERAMIC TRIM AT TOP
CEILING HEIGHT
WALL, PARTITION TYPE PER FLOOR
PLAN
CEMENT BACKER BOARD
STAINLESS STEEL COVE -
DILEX -AHKA (B -3) SERIES BY "SCHLUTER"
TILE
NOTE:
PROVIDE WATERPROOFING UNDER
TILE WORK, TYP. SEE SPECIFICATIONS
FOR TILE HEIGHT REF
INTERIOR ELEVATIONS
PARTITION PER PLAN
WALL TILE WHERE OCCURS
(SEE ELEVATION)
GRAB BAR COLLAR
ANCHOR MOUNTING
PLATE TO BACKING
(RE: 14/A9.10) PLATE
W/ #12 SCREWS. 0'-1 1/4"
0'-1 1/2"
GRAB BAR WITH CONCEALED
MOUNTING SUPPORT
BACKING SUPPORT, SEE
MOP AND BROOM RACK
MOP SINK
WALL FINISH AND FRAMING PER PLANS
FLOORING PER
FINISH PLAN
FOR WALL BACKING DETAILS
SEE
WALL FINISH, WHERE OCCURS PER
WALL TYPE
PARTITION, SEE FLOOR PLAN FOR
WALL TYPE DESIGNATION
CEMENTITIOUS BACKER BOARD PER
WALL TYPE
WALL TILE PER FINISH PLAN
THINSET ADHESIVE
0'-0 1/8"
WALL TILE PER
FINISH PLAN
FLOORING
PER FINISH PLAN
PAINTED
CEMENTITIOUS
BACKER BOARD
PER WALL TYPE
HORIZONTAL &
VERTICAL GROUT
JOINTS TO BE
1/8"
A9.42
05 A9.42
19 TYP.
U.N.O. ON ELEVATIONS
9' - 0"
A9.42
19 TYP.
CUT TILE
TOILET PARTITION
ANODIZED
ALUMINUM ANGLE
WALL PER PLAN
BACKING TRACK
PER 14/A9.10
(2) 1/4" THROUGH BOLT
EA. SIDE W/ RUBBER
WASHER @ 48" O.C. MAX.
ALUMINUM DOUBLE
EAR BRACKET
(2) 1/4" DIAM.
THROUGH BOLTS
EACH LEG OF EACH
ANGLE
PLAN
WALL TILE PER
FINISH PLAN
FLOORING
PER FINISH PLAN
PAINTED
CEMENTITIOUS
BACKER BOARD
PER WALL TYPE
HORIZONTAL &
VERTICAL GROUT
JOINTS TO BE
1/8"
A9.42
05 A9.42
19 TYP.
U.N.O. ON ELEVATIONS
9' - 0"
A9.42
19 TYP.
CUT TILE
AREA NOT HATCHED BELOW SINK
SHALL BE ACCESSIBLE & CLEAR
WRAP HOT & COLD WATER
SUPPLIES AND DRAIN PIPING
WITH PVC INSULATION MATERIAL
COMPLIANT WITH ASTM E84-07,
25 FLAME / 450 SMOKE INDEX
QUARTZ COUNTERTOP
OVER 3/4" PLY WD. FOR
EDGE REF:
CONTINUE ADJ FLR - SEE
FINISH PLAN
TILE TO
CONTINUE
BEHIND SINK
NOTES:
1. FINISH PER FINISH PLANS AND LEGEND.
2. REFER TO BACKING TRACK AND SUPPORT DETAIL.
3. NO SHARP OR ABRASIVE SURFACES UNDER SINK.
4. ALL JOINTS TO BE CAULKED WITH CLEAR SILICONE CAU LK.
INSULATE SINK BOTTOM
IF HOT WATER PROVIDED
FAUCET CONTROLS TO BE LEVER OR A
TYPE NOT REQ GRASPING, PINCHING, OR
TWISTING OF THE WRIST W/ 5 LBS FORCE
MAX TO OPERATE.
MIN
2'-3"
M
IN
0'-8 63/64"
0'-6"
2" X 3" X 1/4" LLV STEEL ANGLE @
24" OC MAX - PAINT TO MATCH
WALL FINISH
1/8" RADIUS EASED
EDGE, TYP
2'-4"
2'-1"(ANGLE LEG)
WALL FINISH PER
INTERIOR ELEVATIONS
40" M
AX TO BO M
IRROR/REFLECTIVE SURFACE
1'-5"MIN.
0'-6"MAX.
0'-6"
MIRROR
/18 A9.42
PLAM APRON
PLATE 1/4 X 3 X 1-6"
LONG @ EACH ROD
1/2" THREADED ROD @ 24" OC
C4 X 5.4, CONTINUOUS
CEILING PER REFLECTED
CEILING PLAN
TOILET-PARTITION ASSEMBLY
PER STRUCTURAL
# 12 SMS @ 12" OC, TYP
1"W X 2"L X 13GA.
MIN METAL CLIP, TYP
4-WAY 12 GA. WIRE
BRACE @ 12" OC (TEST
FOR 200 LBS), TYP;
SECURE WIRE TO
STRUCTURE ABOVE
MAX. DIMENSION PER
MANUFACTURER'S
RECOMMENDATION
.
0'-1 1/2"
GRAB BAR
TILE WALL
ALIGN ALIGN
RECESSED SEAT-COVER
DISPENSER, TOILET TISSUE
DISPENSER AND SANITARY
NAPKIN DISPOSAL (WHERE
OCCURS)
1/4" GROUT JOINT MAX,
TYP ALL SIDES
TILE WALL
2"x2"x5/16"
SINK
QUARTZ COUNTERTOP
PER FINISH PLAN
EXTERIOR GRADE
PLYWOOD
0'-0 15/64"
0'-5 7/64"
2"x2"x5/16"
MITER CORNER
0'-6"
FLOOR DRAIN WITH
STRAINER, RE: PLUMBING
(MAX. 1/4" OPENINGS)
SEALANT
WATERPROOFING MEMBRANE
CONCRETE
(SLOPED TO DRAIN)
CONCRETE
SLAB ON
GRADE
SLOPE
2% MAX.
TYP.
CONCRETE FLOOR
CONCRETE
FLOOR
CONCRETE OVER METAL
DECK @ SECOND FLOOR
LOCATIONS, RE: 01/S6.12
EQ EQ
2% MAX.SLOPE
TYP,
U.N.O.
FLOOR DRAIN,
SEE 11/ -EQ EQ
24" U.N.O.
EQ.
EQ.
24" U.N.O.
DIM. PT.
DIM. PT.
CONCRETE
PER PLAN
SEE PLANS FOR PARTITION TYPE
GROUT, TYP.
WALL TILE PER FINISH
PLAN AND INTERIOR
ELEVATIONS
B
SEE PLANS FOR PARTITION TYPE
GROUT, TYP.
WALL TILE PER FINISH
PLAN AND INTERIOR
ELEVATIONS
A
WALL FINISH PER FINISH
PLAN AND INTERIOR
ELEVATIONS
SEE PLANS FOR
PARTITION TYPE
WALL TILE PER FINISH
PLAN AND INTERIOR
ELEVATIONS
D
SEE PLANS FOR
PARTITION TYPE
WALL TILE PER FINISH
PLAN AND INTERIOR
ELEVATIONS
C
ANOD. ALUM. CORNER
TRIM - EXTEND TO TOP
OF TILE - SCHLUTER
'INDEC'
ALUMN. TRIM (FINISH:
ANOD. ALUM)
PLAN
WALL PER PLAN
START FULL TILE
BEHIND TILE ON
ADJACENT SURFACE
LINE OF TOILET
PARTITION
WHERE OCCURS
ANOD. ALUM. CORNER
TRIM - EXTEND TO TOP
OF TILE - SCHLUTER
'INDEC'
3" = 1' -0"
A9.42 19 TILE AT TOP AND BASE
3" = 1' -0"
A9.42 03 GRAB BAR AND SUPPORT
1" = 1' -0"
A9.42 10 MOP SINK WITH BROOM RACK
3" = 1' -0"
A9.42 09 HORIZONTAL TILE JOINT
1/2" = 1' -0"
A9.42 02 BASE TO WAINSCOT
3" = 1' -0"
A9.42 14 URINAL PARTION ANCHORAGE
1/2" = 1' -0"
A9.42 01 BASE TO WAINSCOT
1" = 1' -0"
A9.42 17 RESTROOM SINK COUNTER
1 1/2" = 1' -0"
A9.42 15 ANCHOR FOR TOILET PARTITIONS
3" = 1' -0"
A9.42 13 RECESSED TOILET ACCESSORY
6" = 1' -0"
A9.42 18 COUNTER EDGE DETAIL
3" = 1' -0"
A9.42 11 FLOOR DRAIN AT FIRST FLOOR1
1 1/2" = 1' -0"
A9.42 07 LOCALIZED DEPRESSION
3" = 1' -0"
A9.42 05 TYPICAL TILE CORNERS
3" = 1' -0"
A9.42 06 WRAPPED WALL TILE
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
RESTROOM
DETAILS
A9.42
MD
MONROE ST. POOL REPLACEMENT
RESTROOM DETAILS
54 203
08/09/2024
203
LOBBY
01 STAFF
LOUNGE
03 MULTI
PURPOSE
ROOM
14 TELEPHONE
15 ADMIN
07 OFFICE
07A
STAFF
SHOWER
03B
STAFF
RR
03A
WOMEN'S
CHANGING/
LOCKERS
10 MEN'S
RESTROOM
04 STORAGE
09A
WOMEN'S
SHOWER
11 WOMEN'S
RESTROOM
09 MEN'S
SHOWER
06 MEN'S
CHANGING/
LOCKERS
05 CORRIDOR
08 CORRIDOR
02 STORAGE
04A
ELEC.
14A
EXTERIOR
STORAGE
18 FIRST
AID
16 EQUIPMENT
STORAGE
17 -D-01 14
-E-01 14
-E-01 15
-E-01 14A
-E-01 05-1
-E-01 04-3
-C-03 04-2
-M-01 01-1
-A-01 01-2
-E-01 03B-1
-E-01 08-2
-E-01 16-1
-E-01 17-1
-E-01 18-1
-E-01 09-1 -C-02 09-2
-E-01 09A-1-E-01 10-1
-E-01 09-3
-E-01 04A-1
-E-01 07-1-E-01 07A-1
-A-01 08-1
-E-01 02-2
-A-01 02-1
-C-01 03A-1
-E-01 03-1 -E-01 04-1
-C-04 03A-2
-D-01 03-2
POOL
PUMP
ROOM
22 ELECTRICAL
21 STORAGE
19 CORRIDOR/
LOCKERS
20 FAMILY
RESTROOM/
SHOWER
20C
FAMILY
RESTROOM/
SHOWER
20D
FAMILY
RESTROOM/
SHOWER
20A
FAMILY
RESTROOM/
SHOWER
20B
CHEMICAL
ROOM
24 CHEMICAL
ROOM
25 BACKWASH
22A
PUMP
PIT
22B
-E-01 22-2 -E-01 23-1 -E-01 24-2
-E-01 22-1
-E-01 20-1
-C-01 20A-2
-C-01 20C-2
-C-01 20D-2
-C-01 20E-2
-E-01 19-1
-E-01 21-1
-A-01 22-3
-C-04 20A-1
-C-04 20D-1 -C-04 20E-01
-C-04 20B-1
FAMILY
RESTROOM/
SHOWER
20E
-C-04 20C-1
1. FOR SIGNAGE DETAILS, REF: A10.11 AND A10.12
2. FOR ACCESSIBILITY SIGNAGE NOTES, REF: A10.11
3. FOR SIGNAGE SCHEDULE, REFER TO A10.03
4. FOR SIGN MATERIAL, COLOR, LETTERING, ADN TYPEFACE, REFER TO SPECIFICATION SECTION 101400.
5. FOR LOCATION OF ELEVATOR LEVEL ID AND STAR OF LIFE SIGN NOT SHOWN ON PLAN; REF: 12/A10.11.
6. WHEN SIGNS OCCUR ON GLASS, PROVIDE VINYL BACKING ON OPPOSITE SIDE OF GLASS.
7. WHERE SIGNS OCCUR BACK TO BACK, ENLARGE SMALLER SIGN TO MATCH DIMENSION OF SIGN ON OPPOSITE SIDE OF GLASS.
8. IF ROOMS ARE PROVIDED WITH ROOM NAMES OR SIGNS THESE SHALL ALSO INCLUDE BRAILLE.
LEGEND
GENERAL NOTES
SIGNAGE TAG
SIGN TYPE
ROOM NUMBER
SIGN NUMBER
### -# - X-##
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
SIGNAGE PLAN &
SCHEDULE - BLDG A
& B
A10.01
MD
MONROE ST. POOL REPLACEMENT
SIGNAGE PLAN & SCHEDULE - BLDG A & B
1/8" = 1' -0"
A10.01 1SIGNAGE PLAN - BLDG A
1/8" = 1' -0"
A10.01 2SIGNAGE PLAN - BLDG B
SIGN
NUMBER TYPE MARK SIGN TYPE DETAIL COMMENTS
C-01 ALL GENDER RESTROOM DOOR 07/A10.11
01-1 M-01 NO SMOKING 05/A10.11
01-2 A-01 EXIT 05/A10.11
02-1 A-01 EXIT 05/A10.11
02-2 E-01 ROOM IDENTIFICATION 17/A10.11
03-1 E-01 ROOM IDENTIFICATION 17/A10.11
03-2 D-01 MAXIMUM OCCUPANCY 06/A10.11
03A-1 C-01 ALL GENDER RESTROOM DOOR 07/A10.11
03A-2 C-04 ALL GENDER RESTROOM WALL 11/A10.11
03B-1 E-01 ROOM IDENTIFICATION 17/A10.11
04-1 E-01 ROOM IDENTIFICATION 17/A10.11
04-2 C-03 MENS RESTROOM DOOR 07/A10.11
04-3 E-01 ROOM IDENTIFICATION 17/A10.11
04A-1 E-01 ROOM IDENTIFICATION 17/A10.11
05-1 E-01 ROOM IDENTIFICATION 17/A10.11
07-1 E-01 ROOM IDENTIFICATION 17/A10.11
07A-1 E-01 ROOM IDENTIFICATION 17/A10.11
08-1 A-01 EXIT 05/A10.11
08-2 E-01 ROOM IDENTIFICATION 17/A10.11
09-1 E-01 ROOM IDENTIFICATION 17/A10.11
09-2 C-02 WOMENS RESTROOM DOOR 07/A10.11
09-3 E-01 ROOM IDENTIFICATION 17/A10.11
09A-1 E-01 ROOM IDENTIFICATION 17/A10.11
10-1 E-01 ROOM IDENTIFICATION 17/A10.11
14 E-01 ROOM IDENTIFICATION 17/A10.11
14 D-01 MAXIMUM OCCUPANCY 06/A10.11
14A E-01 ROOM IDENTIFICATION 17/A10.11
15 E-01 ROOM IDENTIFICATION 17/A10.11
16-1 E-01 ROOM IDENTIFICATION 17/A10.11
17-1 E-01 ROOM IDENTIFICATION 17/A10.11
18-1 E-01 ROOM IDENTIFICATION 17/A10.11
19-1 E-01 ROOM IDENTIFICATION 17/A10.11
20-1 E-01 ROOM IDENTIFICATION 17/A10.11
20A-1 C-04 ALL GENDER RESTROOM WALL 11/A10.11
20A-2 C-01 ALL GENDER RESTROOM DOOR 07/A10.11
20B-1 C-04 ALL GENDER RESTROOM WALL 11/A10.11
20C-1 C-04 ALL GENDER RESTROOM WALL 11/A10.11
20C-2 C-01 ALL GENDER RESTROOM DOOR 07/A10.11
20D-1 C-04 ALL GENDER RESTROOM WALL 11/A10.11
20D-2 C-01 ALL GENDER RESTROOM DOOR 07/A10.11
20E-01 C-04 ALL GENDER RESTROOM WALL 11/A10.11
20E-2 C-01 ALL GENDER RESTROOM DOOR 07/A10.11
21-1 E-01 ROOM IDENTIFICATION 17/A10.11
22-1 E-01 ROOM IDENTIFICATION 17/A10.11
22-2 E-01 ROOM IDENTIFICATION 17/A10.11
22-3 A-01 EXIT 05/A10.11
23-1 E-01 ROOM IDENTIFICATION 17/A10.11
24-2 E-01 ROOM IDENTIFICATION 17/A10.11
KEYPLAN
A
B
KEYNOTE LEGEND
55 203
08/09/2024
203
SIGNS SHALL COMPLY WITH SECTION CBC 11B -703 , WHERE BOTH VISUAL AND TACTILE CHARACTERS ARE REQUIRED.
RAISED CHARACTERS SHALL COMPLY WITH CBC 11B -703.2 AND SHALL BE DUPLICATED IN BRAILLE COMPLYING WITH SECTION CBC 11B -703.3. • CHARACTER DEPTH: CBC 11B -703.2.1
• CHARACTER CASE: CBC 11B -703.2.2
• CHARACTER STYLE: CBC 11B -703.2.3
• CHARACTER PROPORTIONS: CBC 11B -703.2.4
• CHARACTER HEIGHT: CBC 11B -703.2.5
• CHARACTER STROKE THICKNESS: CBC 11B -703.2.6
• CHARACTER SPACING: CBC 11B -703.2.7
• CHARACTER LINE SPACING: CBC 11B -703.2.8
• CHARACTER FORMAT: CBC 11B -703.2.9
BRAILLE CHARACTERS SHALL COMPLY WITH CBC 11B -703.3
• BRAILLE SHALL BE CONTRACTED (GRADE 2) AND SHALL COMPLY WITH SECTIONS CBC11B -703.3 AND CBC 11B -703.4.
• BRAILLE DIMENSIONS AND CAPITALIZATION: CBC TABLE 11B -703.3.1 • BRAILLE POSITION: CBC TABLE 11B -703.3.2
VISUAL CHARACTERS SHALL COMPLY WITH CBC 11B -703.5
• FINISH AND CONTRAST: CBC11B -703.5.1
• HEIGHT: CBC TABLE 11B -703 -5.5
• STROKE THICKNESS: CBC11B -703.5.7
• FORMAT: CBC TABLE 11B -703.5.10
SIGNS AT SINGLE DOORS
GLASS
SIGN ON
BOTH SIDES
NOTES:
1. SIGN MOUNTING LOCATION AND HEIGHT SHALL COMPLY WITH CBC 11B -703.4.1; CBC 11B -703.4.2; CBC 11B -703.7.2.6
2. AT SINGLE DOORS, LOCATE SIGN ON LATCH SIDE OUTSIDE OF DOOR ENTERING ROOM THAT IS IDENTIFIED ON SIGN
3. WHEN SIGNS ARE MOUNTED TO GLASS, PROVIDE VINYL BACKING BETWEEN SIGN AND GLASS
4. WHEN SIGNS ARE MOUNTED ON BOTH SIDES OF GLASS, ALIGN SIGNS CL
(58" M
IN. - 60" M
AX.)
60" A.F.F.
EQ EQ CL
RAISED COPY
LOWEST BRAILLE CELLS
48" MIN. BASELINE OF
HIGHEST RAISED CHARACTERS
60" MAX BASELINE OF
EQ EQ
FLR. SPACE
1'-6"
RESTROOM DOOR SIGNAGE
RESTROOM & TACTILE SIGN
RAISED COPY
LOWEST BRAILLE CELLS
48" MIN. BASELINE OF
EQ EQ
FLR. SPACE
1'-6"
HIGHEST RAISED CHARACTERS
60" MAX BASELINE OF
SIGNS AT DOUBLE DOORS SIGNS MOUNTED TO GLASS
SIGN ON
SINGLE SIDE
GLASS
VINYL, SAME SIZE AND
SHAPE AS SIGN -
COLOR (V1)
NOTES:
1. VERTICES SHALL BE RADIUSED BETWEEN 1/8" MIN. AND 1/4" MAX.
MEN
WOMEN
RESTROOM
1/4" THICK ACRYLIC EQUILATERAL
TRIANGLE SIGN PANEL POINTING
UPWARDS WITH 12" SIDES - COLOR
(P2)
DIRECT PRINT - COLOR (P1)
DIRECT PRINT - COLOR (P1)
1/4" THICK ACRYLIC 12" DIAMETER
CIRCLE SIGN PANEL - COLOR (P2)
1/4" THICK ACRYLIC EQUILATERAL
TRIANGLE SIGN PANEL POINTING
UPWARDS, SUPER IMPOSED ON
AND GEOMETRICALLY INSCRIBED
WITHIN THE CIRCLE. THE VERTICES
OF THE TRIANGLE SHALL BE
LOCATED ON THE EDGE OF THE
CIRCLE - COLOR (P1)
RAISED CHARACTER AND BRAILLE EXIT SIGNS: CBC 1013.4
TACTILE EXIT SIGNS SHALL BE REQUIRED AT THE FOLLOWING LOCATIONS:
1. EACH GRADE -LEVEL EXTERIOR EXIT DOOR THAT IS REQUIRED TO COMPLY WITH SECTION 1013.1, SHALL BE IDENTIFIED BY A TACTILE EXI T SIGN WITH THE WORD, "EXIT".
2. EACH EXIT DOOR THAT IS REQUIRED TO COMPLY WITH SECTION 1013.1,
AND THAT LEADS DIRECTLY TO A GRADE -LEVEL EXTERIOR EXIT BY
MEANS OF A STAIRWAY OR RAMP SHALL BE IDENTIFIED BY A TACTILE EXIT SIGN WITH THE FOLLOWING WORDS AS APPROPRIATE:
2.1 "EXIT STAIR DOWN"
2.2 "EXIT RAMP DOWN"
2.3 "EXIT STAIR UP"
2.4 "EXIT RAMP UP"
3. EACH EXIT DOOR THAT IS REQUIRED TO COMPLY WITH SECTION 1013.1,
AND THAT LEADS DIRECTLY TO A GRADE -LEVEL EXTERIOR EXIT BY
MEANS OF AN EXIT ENCLOSURE OR AN EXIT PASSAGEWAY SHALL BE IDENTIFIED BY A TACTILE EXIT SIGN WITH THE WORDS, "EXIT ROUTE."
4. EACH EXIT ACCESS DOOR FROM AN INTERIOR ROOM OR AREA TO A
CORRIDOR OR HALLWAY THAT IS REQUIRED TO COMPLY WITH
SECTION 1013.1, SHALL BE IDENTIFIED BY A TACTILE EXIT SIGN WITH THE WORDS "EXIT ROUTE."
5. EACH EXIT DOOR THROUGH A HORIZONTAL EXIT THAT IS REQUIRED TO COMPLY WITH SECTION 1013.1, SHALL BE IDENTIFIED BY A SIGN WITH THE WORDS, "TO EXIT."
RAISED CHARACTER AND BRAILLE EXIT SIGNS SHALL COMPLY WITH CHAPTER 11B, SECTIONS 11B - 703.1, 11B -703.2, 11B -703.3 AND 11B -703.5.
NOTES:
1. VINYL APPLIED TO SECOND SURFACE OF GLASS
NO SMOKING OR VAPING
WITHIN 25 FEET OF
BUILDING ENTRANCE
0'-0 1/2"
5/8" TALL COPY, FONT TYPE
(C) - COLOR (V1)
0'-3"
PICTOGRAM - COLOR (V1)
0'-8"
5'-0"
A.F.F.
EXIT STAIR
DOWN
FRONT ELEVATION
(TWO LINE COPY)
1/4" THICK CLEAR ACRYLIC
PANEL - COLOR (P2)
APPLIED TO SECOND
SURFACE
5/8" TALL RAISED LETTERS,
FONT TYPE (A) - COLOR (P1)
0'-0 3/8"
EXIT
BRAILLE, COLOR (CLEAR) FRONT ELEVATION
(SINGLE LINE COPY)
EQ. EQ.
COPY SHALL NOT
ENCROACH ON IMAGINARY
1/2" BORDER AROUND SIGN
PANEL 0'-0 1/2"
0'-0 1/2"
EQ. EQ.
0'-0 3/8"
0'-4"
5'-0"
A.F.F.
5/8" TALL RAISED LETTERS,
FONT TYPE (A) - COLOR (P1)
0'-0 3/8"
EXIT ROUTE
BRAILLE, COLOR (CLEAR) FRONT ELEVATION
(SINGLE LINE COPY)
EQ. EQ.
COPY SHALL NOT
ENCROACH ON IMAGINARY
1/2" BORDER AROUND SIGN
PANEL 0'-0 1/2"
0'-0 1/2" 5'-0"
A.F.F.
0'-8"
0'-8"
0'-0 1/2"
0'-0 1/2"
5/8" TALL RAISED LETTERS,
FONT TYPE (A) - COLOR (P1)
0'-0 3/8"
TO EXIT
BRAILLE, COLOR (CLEAR) FRONT ELEVATION
(SINGLE LINE COPY)
EQ. EQ.
COPY SHALL NOT
ENCROACH ON IMAGINARY
1/2" BORDER AROUND SIGN
PANEL 0'-0 1/2"
0'-0 1/2" 5'-0"
A.F.F.
0'-8"
0'-8"
5'-0"
A.F.F.
EXIT RAMP
DOWN
FRONT ELEVATION
(TWO LINE COPY)
1/4" THICK CLEAR ACRYLIC
PANEL - COLOR (P2)
APPLIED TO SECOND
SURFACE
EQ. EQ.
0'-0 3/8"
0'-4"
0'-0 1/2"
0'-0 1/2"
BRAILLE, COLOR (CLEAR)
BRAILLE, COLOR (CLEAR)
COPY SHALL NOT
ENCROACH ON IMAGINARY
1/2" BORDER AROUND SIGN
PANEL
COPY SHALL NOT
ENCROACH ON IMAGINARY
1/2" BORDER AROUND SIGN
PANEL
5/8" TALL RAISED LETTERS,
FONT TYPE (A) - COLOR (P1)
ELECTRICAL
FRONT ELEVATION
(SINGLE LINE COPY)
EQ. EQ.
COPY SHALL NOT
ENCROACH ON IMAGINARY
1/2" BORDER AROUND SIGN
PANEL
0'-0 1/2" 0'-0 1/2"
0'-4"
NOTE: MACHINERY SPACES ARE NOT REQUIRED TO BE
ACCESSIBLE AND SHOW BRAILLE (11B -203.5).
DIRECT TO SUBSTRATE
DIGITAL PRINT SIGN COPY
AND GRAPHIC - COLOR (P1)
5'-10" MAX
A.F.F.
ASSISTIVE LISTENING
SYSTEMS AVAILABLE
AT RECEPTION DESK
3/32" THICK
ALUMINUM
PANEL -
COLOR
(P2)
0'-6"
1'-2"
5/8" TALL COPY, FONT TYPE (B)
5/16" TALL COPY, FONT
TYPE (B)
0'-0 1/2" 0'-0 1/2"
0'-0 1/2" 0'-0 1/2"
MAXIMUM
OCCUPANCY
###
0'-6"
1'-2"
DIRECT TO SUBSTRATE
DIGITAL PRINT COPY, 1"
TALL, FONT TYPE (A) -
COLOR (P1)
3/32" THICK ALUMINUM
SIGN PANEL PAINTED -
COLOR (P2)
5'-10" MAX.
A.F.F.
NOTES:
1. SEE EXIT / CODE ANALYSIS SCHEDULE FOR OCCUPANCY COUNT 1/4" THICK CLEAR ACRYLIC
PANEL
5/8" TALL RAISED LETTERS,
FONT TYPE (A) - COLOR (P1)
PICTOGRAM APPLIED TO
SECOND SURFACE - COLOR
(P1), FIELD COLOR (P2)
0'-8"
0'-0 3/8"
5'-0"
A.F.F.
0'-8"
MEN
0'-2"
0'-5" 0'-0 1/2"
BRAILLE, COLOR (CLEAR) FRONT ELEVATION
5/8" TALL RAISED LETTERS,
FONT TYPE (A) - COLOR (P1)
0'-8"
0'-0 3/8"
5'-0"
A.F.F.
0'-8"
WOMEN
0'-2"
0'-0 1/2" 0'-5"
1/4" THICK CLEAR ACRYLIC
PANEL
PICTOGRAM APPLIED TO
SECOND SURFACE - COLOR
(P1), FIELD COLOR (P2)
BRAILLE, COLOR (CLEAR) FRONT ELEVATION
1/4" THICK CLEAR ACRYLIC
PANEL
5/8" TALL RAISED LETTERS,
FONT TYPE (A) - COLOR (P1)
PICTOGRAM APPLIED TO
SECOND SURFACE - COLOR
(P1), FIELD COLOR (P2)
BRAILLE, COLOR (CLEAR) FRONT ELEVATION
0'-8"
0'-0 3/8"
5'-0"
A.F.F.
0'-8"
RESTROOM
0'-2"
EQ. 0'-4" EQ.
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
619-795-2555 Office
2765 Truxtun Rd,
San Diego, California 92106
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contr actual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1ST PLAN CHECK SUBMITTAL 01/29/2024
2ND PLAN CHECK SUBMITTAL 05/01/2024
3RD PLAN CHECK SUBMITTAL 07/21/2024
4TH PLAN CHECK SUBMITTAL 08/09/2024
FOR REGULATORY
APPROVAL & PERMITTING
NOT FOR CONSTRUCTION
Revision Date SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
DEPUTY CITY ENGINEER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL
DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
SIGNAGE DETAILS
A10.41
MD
MONROE ST. POOL REPLACEMENT
SIGNAGE DETAILS
SIGN RAISED CHARACTER & BRAILLE NOTES
NTS
A10.41 05 SIGN MOUNTING
NTS
A10.41 06 SANITARY FACILITY SIGNAGE
(DOOR)
TACTILE EXIT SIGN NOTES
3" = 1' -0"
A10.41 17 INT ACCESSIBILITY SYMBOL
3" = 1' -0"
A10.41 10 TACTILE EXIT SIGNAGE
3" = 1' -0"
A10.41 19 MACHINERY ROOM SIGNAGE
14 ASSISTIVE LISTENING SYSTEMS
15 MAXIMUM OCCUPANCY
07 SANITARY FACILITY SIGNAGE (WALL)
56 203
08/09/2024
203
A. GENERAL
1. Applicable Code: 2022 California Building Code (CBC). References to industry standards herein shall be latest edition as adopted by Applicable Code.
2. Authority Having Jurisdiction (AHJ): City of Ca rlsbad
3. Field Verification: Field verify existing condi tions and dimensions prior to construction. Promptly notify Architect (Structural Engineer) in case of discrepancies.
4. Design Intent: Contract Documents indicate desi gn intent for structure in its completed state. They do not indicate method of construction. Promptly notify Architect (Structural Engineer), prior to proceeding with Work, if design intent requires further clarification.
5. Deviations, Modifications and Substitutions to A pproved Structural Drawings: Must be accepted in writing by Architect (Structural Engineer) and approved by Governing Code Authority. No deviation, modification or substitution will be accepted via shop drawing review.
6. Procedures of Construction: Contractor is respo nsible for procedures of construction complying with national, state and local safety ordinances. Site visits (including Structural Observation) by Architect (Structural Engineer) do not constitute supervision of methods of construction.
A. Protection of Utilities: Locate existing utilit ies, including those not shown on Contract Documents, and protect them from damage. Contractor bears expense of repair or replacement of utilities in conjunction with execution of Work.
B. Excavations: Protect structure, adjacent struct ures, adjacent properties, streets, and utilities during excavation utilizing lagging, shoring, underpinning and related procedures as may be required. Provide necessary supports for soil at sides of excavations. Contractor and affected trades shall refer to Geotechnical Report for more information.
C. Protection of Structure: Provide necessary meas ures to protect structure and adjacent buildings during execution of Work.
D. Contractor Proposed Revisions: Where a revision of structural design or connection is proposed by Contractor to accommodate construction tolerances, construction sequence and/or dimension modifications, Contractor shall retain a structural engineer licensed in State of California to perform design. Submit stamped and signed design drawings and calculations to the Architect (Structural Engineer) for review and the Governing Code Authority for approval.
E. Erection Plans: Determine phases of Work requir ing erection plans according to applicable safety regulations. Maintain certified copies of erection plans at site during construction.
F. Shoring, Bracing, and Other Temporary Supports: Design and erect shoring, bracing, and other temporary supports where structure has not attained design strength and as required for safe erection.
Ensure floor, roof, and wall members are securely shored and braced during construction. Provide shoring at elevated beams and slabs supporting concrete or masonry walls during and after wall pour until wall attains design strength.
G. Temporary Loading: Ensure construction loads do not exceed indicated design live load values. Notify affected sub-contractor trades of these design load limits.
H. Fabrication, Shipment, and Erection of Structura l Steel: Ensure stresses occurring during fabrication, shipment, and erection of structural steel are temporary and are less than design and allowable stress capacities of individual members. Do not impair full design and load carrying capacity of members due to fabrication, shipment, or erection. Contractor is responsible for controlling erection sequence, erection procedure, temperature differentials and weld shrinkage to minimize residue stresses. Provide additional materials for the erection of structural steel such as temporary bracing and guy cables as may be necessary at no additional cost. Remove these materials unless approved in writing by Owner. Do not tighten bolts in typical beam to column connections for erection purposes.
I. Securing Reinforcing Steel, Dowels, Anchor Bolts and Embeds: Firmly support and accurately place complying with ACI standards prior to casting concrete or grout in masonry walls. Use ties and support bars in addition to reinforcing steel shown where necessary. No welding of reinforcing steel, including tack welding, is permitted unless otherwise accepted in writing by Architect (Structural Engineer). Provide plastic or plastic coated chairs and spacers when resting on exposed surfaces.
J. Coordination Responsibility: Contractor is resp onsible for coordination of Work including that of sub- contractor trades.
K. Core drilling shall of hardened concrete shall o nly be done after specific review by Architect (Structural Engineer) Core drilling shall not cut any reinforcing. Concrete coverage for reinforcement as described in these notes shall be maintained at locations of cores.
Wind Design
a. Speed:
b. Exposure:
c. Enclosure Classification:
d. Components and Cladding Design:
e. Wind Drift Limit:
96 MPH (LRFD)
C
GCPi = +0.18/-0.18
Project Seismic Design Parameters:
a. Site Class:
b. Mapped Spectral Acceleration (Ss, S1):
c. Site Specific Spectral Response Coefficient (SDS, SD1):
d. Site Coefficient (Fa, Fv):
e. Seismic Importance Factor Ie:
f. Risk Category:
g. Seismic Design Catagory:
D
1.225 g, 0.41 g (respectively)
0.825 g, 0.517 g (respectively)
1.01, 1.89 (respectively)
1 II
D
Live Load Design
a. Floor / Roof Live Load: See legends as provided on plan sheets. Live loading in accordance with CBC 1607A.1.
Project Rain / Snow Design Parameters:
a. Rain Intensity i: 1.18 (in/hr)
Building B Seismic Design:
a. Basic Seismic Force Resisting System:
b. Seismic Response Coefficient, Cs:
c. Analysis Procedure:
d. Seismic Base Shear:
e. Response Modification Factor R:
f. Overstrength Factor, Ωo:
g. Deflection Amplification Factor, Cd:
h. Maximum Story Inelastic Drift:
i. Irregularities:
j. Reduncancy Factor, P:
k. Building Mass:
l. Wind Base Shear:
m. Location of Seismic Base
SPECIAL REINFORCED MASONRY SHEAR WALLS
0.165 g
EQUIVALENT LATERAL FORCE PROCEDURE
43.4 kips (Bldg B)
5.0 2.5
3.5 Roof Floor:
0.007 x Story Height
Vertical: N/A
Horizontal: N/A
Rho = 1.3 in (North / South)
1.3 in (East / West)
263.3 kips (Bldg B)
N/A: Seismic Governed
Ground Level
7. Submittals: SubmAVit to Architect (Structural E ngineer) as indicated on structural drawings and specifications.
General Contractor shall review submittal for completeness and compliance with Contract Documents prior to submission.
A. Request for Information (RFI) Submittals: Accom pany RFI's with partial structural foundation or framing plans showing location in question and affected structural members. Copy partial plan from structural drawings and indicate grid line locations and floor level. Also provide properly drawn engineering sketches illustrating issues and Contractor's proposed solutions. Photographs are not acceptable substitutes to engineering sketches.
B. Composite Slab Penetration Submittal: Submit to Architect (Structural Engineer) for each floor indicating size and location of each slab penetration and opening as necessary by all affected trades. Submit penetration plans together with corresponding metal decking or reinforcing steel shop drawings. Submit written statement from Special Inspector that no additional penetrations or openings were added to those shown in penetration submittal.
C. Composite Concrete and Masonry Wall Penetration Submittal: Submit to Architect (Structural Engineer) for each wall indicating size and location of each wall penetration and opening as necessary by all affected trades. Submit penetration elevations together with corresponding reinforcing steel shop drawings. Submit written statement from Special Inspector that no additional penetrations or openings were added to those shown in penetration submittal.
8. Contract Documents Use: Review Contract Documen ts in their entirety before performing structural related Work and before developing shop drawings. Bring discrepancies to immediate attention of Architect (Structural Engineer) before starting Work.
A. Scaling of Drawings: Not permitted.
B. Additional Structural Requirements: See specifi cations.
C. Building Geometry: See architectural drawings f or building geometry including, but not limited to, top of floor and roof elevations; depressions; slopes; curbs; drains; trenches; slab and deck edge locations; wall overall dimensions; and size and locations of openings in floors, roof, and walls.
D. Non-structural Items Requiring Special Provision s: See architectural, mechanical, plumbing, and electrical drawings for non-structural items requiring special provisions during construction. They include, but are not limited to, non-structural walls; size and locations of openings and sleeves penetrating structure; size and location of concrete curbs and pads; and size and location of piping, ductwork, and equipment anchorages mounted or suspended from structure. Verify exact size and location of equipment with equipment manufacturer.
9. Materials: Furnish and install in compliance wi th legally constituted public authorities having jurisdiction including county and local ordinances and safety orders of State Industrial Accident Commission, OHSA. The Architect (Structural Engineer) and Owner accept no responsibility for the contractors failure to comply with these requirements.
10. Penetrations, Embedments, and Openings in Struc tural Members: No penetration, embedment, opening, sleeve, pipe, or conduit shall occur in structural members including footings, slabs, walls, columns, and beams unless specifically shown or indicated on structural drawings.
11. Typical Details: Details on sheets indicated a s typical are applicable throughout Project wherever the described condition occurs and may or may not be specifically referenced on structural drawings. Contractor is responsible for identifying these details and understanding extent of their application prior to performing Work.
Details not shown or noted shall be similar to those shown for similar construction. Contractor shall submit RFI's for details such as this to Architect (Strucutral Engineer) prior to proceeding with work.
12. Evaluation Report:
A. References to Evaluation Reports for proprietary materials herein shall be latest edition as adopted by Authority Having Jurisdiction (AHJ).
B. For proprietary structural elements and products , product to hold Evaluation Report in compliance with applicable code for products intended use.
C. Approved Evaluation Report Agencies:
1. ICC (ICC-ES)
2. IAPMO (IAPMO-ES)
3. OSHPD (OPA / OPM / OSP / OPD)
4. City Of Los Angeles (COLA/RR)
5. Miami-Dade (NOA)
A. GENERAL CONT.
eff. Area
(ft 2)
WIND PRESSURE (psf)
TYP. Wall Edge
50 100
200
+17.9/-19.6
+17.0/-18.7
+16.1/-17.8
+17.9/-22.5
+17.0/-20.7
+16.1/-19.0
Building A Seismic Design:
a. Basic Seismic Force Resisting System:
b. Seismic Response Coefficient, Cs:
c. Analysis Procedure:
d. Seismic Base Shear:
e. Response Modification Factor R:
f. Overstrength Factor, Ωo:
g. Deflection Amplification Factor, Cd:
h. Maximum Story Inelastic Drift:
i. Irregularities:
j. Reduncancy Factor, P:
k. Building Mass:
l. Location of Seismic Base
SPECIAL REINFORCED MASONRY SHEAR WALLS(First Aid Room & Canopy NS) STEEL ORDINARY MOMENT FRAME(Canopy EW)
0.165 g(SRMSW) / 0.236 g(SOMF)
EQUIVALENT LATERAL FORCE PROCEDURE
6.70 kips (First Aid Room)/ 2.86 kips (Canopy)
5.0(SRMSW)/3.5(SOMF)
2.5(SRMSW)/3.0(SOMF)
3.5(SRMSW)/3(SOMF)
Roof Floor:
0.007 x Story Height (SRMSW)
0.025 x Story Height (SOMF)
Vertical: N/A
Horizontal: N/A
Rho = 1.3 (First Aid Room)
1.3 (Canopy)
40.6 kips (First Aid Room)/12.1 kips(Canopy)
Ground Level
H/400 (10 yr wind)
B. DEFERRED SUBMITTAL ITEMS ANCHORED OR SUPPORTED BY STRUCTURE
1. Design Responsibility: Contractor to design and obtain separate Governing Code Authority approval for tdeferred approval items noted on Gx series sheets.
2. Shop Drawings and Structural Calculations: Submi t design plans, details and calculations of deferred submittal items signed and sealed by a registered structural engineer registered in State of California to Architect (Structural Engineer) for acceptance and to Governing Code Authority for approval prior to fabrication.
3. Design: Design components for imposed forces inc luding lateral restraint complying with Applicable Code, Contract Documents, and applicable portions of AISI Specifications. If building Seismic Force Resisting System (SFRS) is used for lateral restraint, indicate load paths to building lateral resisting system in calculations and show connection forces on shop drawings. Where building provides vertical support, indicate loads and load paths to building in calculations and show connection forces on shop drawings. Dead load elements at lowest level of connection uno Design loads are as follows:
A. Dead load: Self weight of deferred system (includ ing supported components of other systems).
B. Live load: Per applicable code.
C. Seismic and wind loads: Per applicable code. See General Notes Section A.1.
D. Design Movement: Lateral Movement: Section A.1 of General Notes Vertical Movement: Live Load Deflection of L/360
4. Defferred Submittal Items: Roof Screen.
C. QUALITY ASSURANCE (STRUCTURAL OBSERVATION, MATERI ALS TESTING, and SPECIAL INSPECTION)
1. Structural Observation:
A. The Architect (Structural Engineer) of record wi ll perform visual observation of the construction as required CAC 4-333 and 4-341 in accordance with the governing code. These visual observations shall not be considered a substitute for special inspections.
B. Coordination Responsibilities of Contractor: Not ify Architect (Structural Engineer) 48 hours in advance of critical stages of construction indicated below so visits may be scheduled by Structural Observer. Failure by Contractor to meet observation schedule may require removal of subsequent Work for observation. Contractor to bear costs of removal and replacement of finished Work or framing damaged by removal process or as required for corrective action and for any associated scheduling delays.
Critical stages of construction requiring structural observation:
1. Prior to pouring first foundation.
2. Prior to pouring elevated concrete deck.
3. Prior to pouring first concrete filled metal deck.
4. After roof deck welded off.
5. After nailing of first plywood diaphragm.
C. Pre-construction Meeting: Owner may coordinate a nd call for meeting between Architect (Structural Engineer) responsible for structural design, Structural Observer, Contractor, affected subcontractors and Special Inspector. structural observer will preside over this meeting. Purpose of meeting is to identify major structural elements and connections that affect vertical and lateral load resisting systems of structure and to review schedule of Structural Observation, Materials Testing, and Special Inspection of Project.
2. Mill Test Reports Certifying Materials: Contract or to submit mill test reports certifying reinforcing steel, and structural steel are of identifiable tested stock to Owner, Special Inspector, Architect (Structural Engineer) and, upon request, to Governing Code Authority.
Ensure materials are properly tagged for identification. If mill test reports cannot be made available or if material cannot be identified, Testing Laboratory will perform tests as directed by Architect (Structural Engineer). Contractor shall pay Testing Laboratory for costs related to tests and inspections of unidentifiable materials or materials furnished without mill test reports, materials found deficient after initial tests and inspections, or materials replacing deficient materials.
A. Ultrasonic Examination of Heavy Rolled Shapes an d Thick Plates at Proposed Welded Moment Connections: Where complete penetration groove welds occur at Groups 4 and 5 structural steel shapes, as defined in ASTM A6, and plates exceeding 2 inches thick, submit mill test reports to Architect (Structural Engineer) and, upon request, to Governing Code Authority. Mill test reports shall certify that Charpy V-notch testing was conducted in compliance with ASTM A6, Supplementary Requirement S5, including impact test complying with ASTM A673 at frequency P with minimum average value of 20 ft.-lbs. absorbed energy at 70 degrees Fahrenheit.
3. Weld Testing and Inspection: Testing Laboratory will submit weld test results to Owner, Contractor, Architect (Structural Engineer) and to Governing Code Authority. See Specifications for testing requirements not indicated on structural drawings.
A. Structural Steel Welding: Apart from visual insp ection and review of fabrication and erection reports of fabricator/erector's own quality control testing and inspection, Owner's Testing Laboratory will perform indicated shop and field inspection and testing.
Testing Laboratory will be AWS Q.C.-1 certified and will provide inspectors for continuous inspection of steel fabrication and erection and structural welding. Shop and field testing of materials and welding will be as follows:
a. Ultrasonic testing (UT) is required for all (100% ) complete penetration welds. Test groove welding on continuity plates by ultrasonic testing after beam flange weld connection. Testing will be performed 24 hours or more after completion of welding. Weld backing removal areas and fillet welds will be subjected to magnetic particle examination.
1. UT testing reduction: Where the initial rate for UT is 100%, the NDT rate for an individual welder or welding operator is permitted to be reduced to 25% provided that the number of welds containing unacceptable defects operator. A sampling of at least 40 completed welds for a job shall be made for such reduction evaluation. See AISC 360-10 N5.5e and AISC 341 J6.2g for additional information.
2. UT Reduction is NOT permitted at demand critical welds.
3. Documentation: All NDT performed shall be documen ted per AISC 360-10 N5.5g b. Base metal thicker than 1-1/2 inches, subjected t o through thickness weld shrinkage, will be ultrasonically tested directly behind such welds after welds have cooled to ambient temperature. c. Welds shall be visually inspected and periodicall y measured (15 percent minimum). d. Check 10 percent of fillet welds by magnetic part icle (ASTM 109 method). Check 25 percent of continuity plate fillet welds and beam fillet welds (100 percent in moment zones) by magnetic particle. e, Ultrasonically test column flanges located at pro posed welded moment connections, continuity plates, doubler plates and base plates where column flange or plate thickness exceeds 1-1/2 inches. Test for evidence of laminations, inclusions or other discontinuities in accordance with ASTM A435, straight beam ultrasonic examination of steel plates, or ASTM A898, straight beam ultrasonic examination of rolled steel structural shapes, as applicable. Test zone to include area 6 inches above and below each beam flange connection. For plates, any discontinuity causing a total loss of back reflection not contained within 3-inch diameter circle, or one-half thickness of plate, whichever is greater, will be rejected. For rolled shapes, ASTM A898, Level I criteria applies. Testing will be performed on material prior to fabrication, after fabrication, and after final welding of beam.
f. k-Area welds shall be MT'd no sooner than 48 hour s after completion of weld. g. Amperage, voltage, polarity and electrode stick o ut will be verified for compliance with electrode manufacturer's recommendations.
4. Special Inspection: 1704.2.3 of CBC. See S0.03
D. EARTHWORK and FOUNDATIONS
1. Geotechnical Report: Perform soils work complyin g with foundation design based on recommendations in report log no. 10573-1; prepared by Atlas; dated Nov.6.2023 and subsequent addenda letters. Maintain at site a copy of report and addenda.
2. Allowable Foundation Design Values per Geotechni cal Report.
A. Bearing Capacity: 2500 psf, for min. 2'-0" wide spread footing and 1'-6" wide continuous footings both with 2'-0" min. below adjacent finished grade. Values may be increased by 1/3 for transient loading.
B. Passive Lateral Bearing Pressure: 300 psf/ft. Va lues may be increased by 1/3 for transient loading.
C. Coefficient of Friction: 0.35.
D. Combined Lateral Resistance : The allowable late ral resistance can be taken as 350psf/ft .
E. Slab on Grade Bearing Capacity: 2000psf
3. Grading, Excavations, Backfill and Compaction of Backfill: Comply with Geotechnical Report and requirements of Governing Code Authority and performed only under Continuous Special Inspection of geotechnical engineer. Building pads shall be over excavated per figure below as recommended in Geotechnical Report. If soft pockets are discovered during over excavation, additional over excavation will be required as directed by the Geotechnical Engineer.
4. Foundation Excavations: Foundations are to bear on approved compacted fill as indicated in Geotechnical Report. Excavations are to be inspected by geotechnical engineer prior to placement of reinforcing steel and formwork. Ensure excavations are clean, dry and free of debris or loose soil. Slope sides of excavation not less than minimum slope indicated in Geotechnical Report. Cast concrete directly against excavated surfaces. Graphic presentation of extent of excavation below is based on Geotechnical Report. In case of discrepancy, information in Geotechnical Report shall take precedence.
5. Backfilling of Retaining Walls: Place after comp letion and inspection of waterproofing. Adequately shore retaining walls during backfill operation. Unless adequately shored, do not place backfill behind building structure retaining walls until concrete at elevated floor levels adjacent to walls are completely poured and have cured for at least 7 days at site walls, concrete shall reach full design strength prior to backfilling unless adequately shored.
6. Retaining Wall Design Values:
A. Active earth pressure: __40_ pcf (triangular) At Level Backfill / __60__ pcf (triangular) at 2H:1V Backfill B. At-rest earth pressure: __60_ pcf (triangular) A t Level Backfill / __80__ pcf (triangular) at 2H:1V Backfill
7. Soil observation shall be performed by the Geote chnical Engineer per Geotechnical Report.
EXTENT OF OVER
EXCAVATION and
RE-COMPACTION
PER
GEOTECHNICAL
REPORT
X
1 X
1 SPREAD FOOTING, CONT.
FOOTING, OR MAT FOUNDATION
X
1 X
1 X
1 SITE FEATURE
EXTENT OF OVER
EXCAVATION and RE-
COMPACTION PER
GEOTECHNICAL REPORT
X
1 E. REINFORCING STEEL
1. Reinforcing Steel: All bars shall be deformed.
A. All bars unless indicated otherwise: ASTM A615, Grade 60 B. Bars to be welded: ASTM A706, Grade 60
C. Additional Requirements for Bars, Excluding Ties , for vertical bars in Shear Walls: No additional requirements if ASTM A706, Grade 60 bars used. ASTM A615, Grade 60 bars are permitted provided actual yield strength based on mill tests does not exceed specified yield strength by more than 18,000 psi (retests shall not exceed this value by more than an additional 3,000 psi) and ratio of actual ultimate tensile stress to actual yield stress is not less than 1.25.
2. Wire and Spiral Reinforcing:
A. Smooth welded wire fabric (W.W.F.): ASTM A1064, Fy =65 ksi, flat sheets only - do not use rolled mesh. Lap 1-1/2 wire spaces (1 foot minimum). Offset laps in adjacent sheets to avoid continuous laps.
B. Deformed wire stirrups (D4 and larger only): AS TM A1064, Fy =65 ksi C. Spiral reinforcing: ASTM A1064, Fy =65 ksi
3. Reinforcing shall be placed in accordance with t he American Concrete Institute Standard 318 (ACI318) and Concrete Reinforcing Steel Institute's (CRSI) "Manual of standard practice". Reinforcing shall be kept clean and free of rust.
4. Provide all accessories needed to support reinfo rcing in the positions shown in the drawings. Chairs and spacers for reinforcing shall be non-ferrous of plastic coated when resting on exposed concrete surfaces.
5. Shop Drawings: ACI 318-19. Show reinforcing st eel placement including sizes, quantities, spacing, clearances, splice locations, lap lengths, and concrete coverage's and submit to Architect (Structural Engineer). Promptly notify Architect (Structural Engineer) prior to developing shop drawings if insufficient clear distances between reinforcing steel and other congestion is encountered. Notify Special Inspector of adjustments made from approved Contract Documents which are indicated on accepted shop drawings that facilitate field placement of reinforcing steel and concrete. All bars shall be marked so that they can easily be identified by the project inspector after installation.
6. Lap Splices: At concrete, Provide Class B splice s per 04/S6.01 UNO. At masonry provide, 72db lap splice length UNO. Splice bars only at locations indicated. If additional splice locations are proposed, promptly notify Architect (Structural Engineer) prior to developing shop drawings.
A. Splices in Walls: Locate splices in horizontal bars at well-staggered locations. Do not splice vertical bars except at horizontal supports such as floor and roof diaphragms.
7. Mechanical and Welded Splice: Mechanical Splice and Welded Splice are to be used only at locations indicated. Notify Architect (Structural Engineer) of all instances prior to developing shop drawings.
A. Mechanical Splice: Mechanical couplers shall have current Evaluation Report and satisfy ACI requirements for type 2 coupler for the applicable bar size / grade designation.
B. Welded Splice: Welded splice shall develop at lea st 125 percent of the yield strength of the spliced bar for the applicable bar size and grade designation
8. Minimum Clearances Between Parallel Reinforcing Steel Including Distance Between Sets of Spliced Bars: 1 inch, 1 bar diameter, or 4/3 times the minimum aggregate size whichever is greater. 1-1/2 inches, 1-1/2 bar diameters, or 4/3 times the minimum aggregate size whichever is greater, at columns, piers, and pilasters only. For bundled bars, minimum clear distances between units of bundled bars shall be same as single bars except bar diameter is derived from equivalent total area of bundle.
9. Minimum Concrete Coverage: Place bars as near t o concrete surface as the following minimum coverages permit, unless noted otherwise:
A. Slabs on Grade - locate at center of slab.
B. Slabs Supporting Earth Above - 1-1/2 inches from top.
C. Formed Concrete Exposed to Earth or Weather - 1-1 /2 inches (#5 and smaller); 2 inches (#6 and larger) D. Concrete Poured Against Earth (Unformed) - 3 inch es E. Walls Above Grade, Exposed to Weather - See C. abo ve F. Walls Above Grade, Not Exposed to Weather 3/4 inc h (#11 and smaller); 1-1/2 inches (#14 and larger) G. Columns (Clear to Face of Ties) - 1-1/2 inches
H. Beams (Clear to Face of Ties) - 1-1/2 inches
I. Structural Slabs, Not Exposed to Weather (Top an d Bottom) - 1 inch (#8 and smaller); 1db (#9 and larger) J. Structural Slabs, Exposed to Weather - See C. abo ve
10. Dowels between footings and vertical wall & col umn bars shall match the size, grade and spacing of the column up wall vertical reinforcing and be lapped with a class B lap splice, UNO.
11. Dowels at Construction Joints: Provide dowels matching size and quantity of reinforcing steel interrupted at construction joints, unless detailed otherwise.
12. Placement of Bars in Walls (unless detailed oth erwise): Place vertical bars closest to wall surfaces at curtains containing vertical and horizontal bars of the same size. In curtains which vertical and horizontal bars are of different sizes or spacing, place layer with most steel area closest to near wall surface.
13. Bars Terminating at Walls, Columns, Beams, and Foundations: Extend bars to within 2 inches (3 inches at concrete poured against earth) of far face of wall, column, beam, or foundation and provide standard hook unless detailed otherwise.
14. Bars Interrupted by Structural Steel: Extend b ars to within 2 inches of steel face and provide standard hook unless detailed otherwise.
15. Welding: AWS D1.4, edition adopted by applicab le code.
A. Acceptable Reinforcing Steel for Welding: ASTM A706. If welding of reinforcing steel other than A706 is desired, submit proposed procedure, indicating conformance to Applicable Code and requirements of Governing Code Authority, to Architect (Structural Engineer) for acceptance and to Governing Code Authority for approval prior to execution.
B. Rebar to rebar weld not allowed except where spe cifically indicated on plans. Provide electrode E80XX (80 ksi) where permitted.
C. Welder Certification: As required by Governing Code Authority.
D. See welding notes in Structural Steel Section of these notes for additional requirements.
16. Bending: Bend cold unless otherwise accepted b y Architect (Structural Engineer). Do not field-bend reinforcing steel bars embedded in concrete unless otherwise accepted in writing by Architect (Structural Engineer).
17. Reinforcing Steel Allowance: In addition to re inforcing steel indicated in Contract Documents, allow for an additional 2 tons of reinforcing steel to be constructed under direction of Architect (Structural Engineer) during construction. Direction will be given during multiple occasions. Reinforcing steel under this allowance will be of any size, shape and grade. Quantity of pieces and location in Project will vary. Include in this allowance fabrication and erection and necessary construction services such as shop drawing preparation, and access for inspection. Submit expenditures in writing for any part of this allowance to Architect (Structural Engineer) prior to fabrication and erection. The unused portion of this allowance shall be credited to the owner at the completion of the project.
18. In-plant fusion welding of holding wires to ties , stirrups and hoops in beams, columns and grade beams to preassemble reinforcing steel cages is permitted under the following conditions per CBC 2022 1903.8:
a. Fusion welding is not allowed to longitudinal re inforcing steel in any beam, column or grade beam. The holding wire area shall not exceed 5% of the beam, column or grade beam cross sectional longitudinal steel area. b. Fusion welding of holding wires to the ends of t he reinforcing steel placed in mats (spread footings, slab reinforcement, etc.) provided the fusion weld occurs within 6 bar diameters of the free end of the bar (e g. not allowed at the end of coupled, t-headed or weld spliced bars).
c. Fusion welding of holding wires shall not occur on a bent portion of a reinforcing bar. After holding wire has been fusion welded to a reinforcing bar, that bar may not be bent where the fusion weld occurs. d. Contractor to submit complete shop drawings indi cating which members will use fusion welding process for preassembly.
Provide complete details indicating the size of stirrups, holding wires and welding requirements. e. Holding wires shall conform to ASTM A1064.
f. All reinforcing steel to be welded shall comply with ASTM A706 Grade 60. g. Contractor to submit complete shop welding progr am outlining the following:
1. Type of specific fusion welding machine (i.e. Sch nell IDEA 12/25 Machine, etc.)
2. Periodic inspection of the in-plant welding.
h. Fusion welded reinforcing steel shall have one t ensile test taken from one specimen sampled at a rate of 2.5 tons or fraction thereof of each size of reinforcing steel fusion welded. No bend test is necessary. The specimen shall have a holding wire attached to it that need not be removed. The elongation requirements shall comply with the ASTM of reinforcing steel specified on the construction documents (e g. if A615 is specified, but A706 is used due to the welding requirement, then A615 elongation requirements shall be satisfied).
L The use of fusion welding shall conform to ACI318 -19 26.6.4. j. If field conditions result in conflicts with oth er structural members (ex. anchor bolts) the rebar must be relocated in the field to avoid said conflicts.
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"
CIVIL ENGINEER DATE
RCE EXP.
REVIEWED BY:
INSPECTOR DATE
SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
GENERAL NOTES
S0.01
Checker
MONROE ST. POOL REPLACEMENT
GENERAL NOTES
09/30/25
256
57 203
08/09/2024
203
F. CAST-IN-PLACE CONCRETE
1. Applicable Standards: ACI 318 and ACI 301 except as amended in California Building Code Chapter 19 and as modified by supplemental requirements herein. Concrete mixing shall comply with ASTM C94.
2. Portland Cement: ASTM C150, type II. Submit mill test with certification of compliance to Architect (Structural Engineer)
3. Aggregates:
A. Normal Weight Concrete Aggregate: ASTM C33 for a ggregates of natural sand and rock. Maximum aggregate size is 1-1/2 inches at foundations and slabs on grade and 1 inch elsewhere.
B. Light Weight Aggregate for Structural Concrete: ASTM C330, expanded shale light weight aggregate.
4. Minimum 28-Day Concrete Compressive Strengths an d Types:
Concrete Unless Otherwise Indicated on
Structural Drawings
Footings and Grade Beams
Concrete Walls
Concrete Slabs on Grade
Equipment Curb/Pad Over Metal Deck
Concrete fill on Metal Deck
4000 psi normal weight (145 pcf)
4000 psi normal weight (145 pcf)
5000 psi normal weight (145 pcf)
4000 psi normal weight (145 pcf)
4000 psi normal weight (145 pcf)
4000 psi light weight (115 pcf)
0.5 0.5
0.5 0.45
0.5 0.45
5. Slump: Per ACI 301, CH. 4 and CBC section 1705.3 .
6. All concrete above grade, including, slab on gra de, deck fill, wall, topping slab, stair landing and tread shall have 1.5 pounds of 1 1/2" long fibrous reinforcing per cubic yard of concrete.
7. Lean Concrete: Where specifically indicated, con taining 2 sacks of cement per cubic yard of concrete. Use only where specifically called for.
8. Non-shrink Grout: ASTM C109, cementitious, non-m etallic attaining a compressive strength of 8000 psi.
9. Concrete Mix Design Submittal: Prior to ordering concrete, submit for each compressive strength and type of concrete required designed, signed, and sealed by a registered Civil or Structural Engineer in State of California to Architect (Structural Engineer), Special Inspector and to Governing Code Authority complying with California Building Code, Chapter 19.
10. Construction Joint: Roughen surface to 1/4-inch amplitude. Clean, remove laitance, thoroughly wet and remove standing water before placing new concrete. Submit to Architect (Structural Engineer) at least 14 days prior to placing concrete indicating locations of construction joints and extent of pours. Place joints at locations to minimize effects of shrinkage as well as being placed at points which least impair strength of structure. Provide dowels as directed.
11. Embedments and Penetrations in Concrete: No pen etration through structural concrete is permitted unless shown in these drawings or specifically accepted in writing by Architect (Structural Engineer). Do not cut any reinforcing.
A. Pipes, Sleeves, Conduits, and Ducts: Not permitt ed embedded or penetrating concrete spread footings, columns, walls or concrete cast over metal decking, except as shown in these drawings.
B. Conduits Embedded in Structural Concrete Slabs: Not permitted unless limited to two layers of 1 inch, and 1/6 slab thickness. outside diameter conduits and smaller spaced at least 3 inches center to center and within middle third of slab thickness. No conduit embedded in concrete cast over metal decking is permitted. No aluminum conduit is permitted.
12. Chamfered Corners: Provide 3/4-inch chamfer at exposed corners of columns, beams and walls except where structural walls are laid flush with column or beam faces, unless detailed otherwise.
13. Curing: Maintain concrete above 50 degrees Fahr enheit and in a moist condition for a minimum of 7 days after placement unless otherwise accepted by Architect (Structural Engineer).
14. Non-Structural Topping slab shall be normal wei ght concrete reinforced with 6x6-W3.5x3.5 W.W.F. at center line of slab. See plans & details for information on concrete fill over metal deck.
Element Compressive Strength and
Type of Concrete
Max. W/C
Ratio
15. No more than one class of concrete shall be on s ite at one time.
16. The maximum size for a single elevated concrete slab pour shall be 25,000 sq. ft. and shall have a maximum length to depth ratio of 2:1.
17. The maximum water-soluble chloride ION (CI) cont ent in concrete by percentage of weight cement is 0.30.
18. Where "Styrofoam" indicated on plans provide Po lystyrene product conforming to ASTM D6817. Foam shall have a minimum density of
0.70 lb/ft3 when tested in accordance with ASTM D1622. Foam shall have a minimum compressive strength of 2.2psi at 1 percent deformation when tested in accordance with ASTM D1621.
G. PROPRIETARY ANCHORAGES and FASTENERS
1. Anchorages:
A. Drill and Epoxy Anchors:
i. At Concrete: Hilti HIT-RE 500 V3 adhesive anchor system complying with ICC-ES Evaluation Report ESR-3814. ii. At Masonry: Hilti HIT-HY 270 adhesive anchor system complying with ICC-ES Evaluation Report ESR-4143. iii. Provide anchor type, size and embedment as indicated in details. iv. Overhead applications must be installed using the Hilti HIT-SZ piston plug system.
B. Mechanical Anchors:
i. At Concrete: Hilti KB-TZ2 carbon steel expansion anchor complying with ICC-ES Evaluation Report ESR-4266. ii. At Masonry: Hilti KB-TZ2 carbon steel expansion anchor complying with ICC-ES Evaluation Report ESR-4561. iii. Where mechanical anchor is exposed to weather, provide stainless steel anchor conforming to the ICC-ES Evaluation Report in lieu of carbon steel.
C. Welded Shear Studs: Nelson S3L flux filled, head ed stud anchors, 65,000 psi minimum ultimate tensile strength conforming to ASTM A29, automatically end welded in field and complying with ICC-ES Evaluation Report ESR-2856.
D. Welded Deformed Anchors: Nelson D2L, cold rolled , deformed steel reinforcing bars conforming to ASTM A1064 and complying with ICC-ES Evaluation Report ESR-2907.
2. Fasteners:
A. Powder Actuated Fasteners: Hilti Low-velocity Po wder Actuated Drive, 0.157" diameter (X-U), complying with ICC-ES Report ESR-2269. Provide appropriate washer between fastener head and light gauge metal or wood surface. Shot pins shall not be used @ PT slab or beams.
B. Self-Drilling Metal Screws (Indicated "Screws" o r "SMS" on Drawings): Hilti Self Drilling Screw complying with current ICC-ES Evaluation Report ESR-2196.
C. Concrete Screws: Hilti KH-EZ carbon steel screw anchor complying with ICC ES Evaluation Report ESR-3027.
D. Masonry Screws: Hilti KH-EZ carbon steel screw anchor complying with ICC ES Evaluation Report ESR-3056.
E. Where Concrete or Masory Screws are exposed to w eather, provide stainless steel anchors conforming to the ICC-ES Evaluation Report in lieu of carbon steel.
3. Installation: See manufacturer's written instruc tions and referenced ICC-ES evaluation report. Contractor shall arrange an anchor manfacturer's representative to provide onsite installation training for all anchor products specified.
A. Prior to drilling holes for post-installed ancho rs, contractor shall locate existing rebar, prestressing tendons, post-tensioning tendons, and embedded utilities using non-hazardous, non-destructive methods with accurate location tolerances (plus or minus 1/4-inch). Do not cut, hit, or otherwise damage existing rebar or tendons during anchor installation.
B. Drilling Holes in Existing Concrete or Masonry f or Anchorages: Use non-pneumatic, rotary hammer tools with ANSI compliant non-rebar cutting drill bits to drill holes of proper tolerances. Locate existing rebar including prestressing and post-tensioning tendons using non-hazardous, non- destructive methods with accurate location tolerances (plus or minus 1/4-inch) prior to drilling holes to avoid cutting or damaging Holes shall be thoroughly cleaned per manufacturer's written recommendations prior to installation of anchorages.
C. Deleterious Materials: Keep anchorages, includin g holes for drill and epoxy anchors and mechanical anchors, free of dust, grease, and other materials that impair bond.
D. Use of diamond core bit with roughening tool for anchor holes requires approval from Engineer of Record prior to drilling. Unless otherwise shown in the drawings, all holes shall be drilled perpendicular to the concrete surface.
E. Embedment Depths:
i. Mechanical Anchors: Embedment depths noted in drawings are the effective minimum embedment UNO. Refer to applicable evaluation report for the corresponding minimum hole depth and nominal embedment. ii. Screw Anchors: Embedment depths noted in dra wings are the nominal minimum embedment UNO. Refer to the applicable evaluation report for the corresponding minimum hole depth.
A. Anchor installer certification is required for a ll installers of drill and epoxy anchors in horizontal or upwardly inclined orientation. Installer qualification must be provided to the inspector prior to installation.
B. Installation Torques for Expansion Anchors shall be as noted:
4. Provide testing of post-install anchors as follows:
A. At expansion anchors and screw anchors: Provide installation using torque as noted above or per most recent ICC-ES Report.
B. At Drill and Epoxy anchors: Provide pull testing to tension values noted on corresponding detail(s) or provided by SEOR. Apply testing to 10% of anchors at each condition. If failure occurs, increase frequency to 100% until 20 consecutive anchors pass pull testing, then resume initial frequency. If subsequent failures occur, notify SEOR for further direction
I. Installation Torques for Screw Anchors shall be as noted:
Nominal
Anchor
Diameter
Expansion Anchor Installation Torque (ft-lb)
Into Concrete Into Masonry
KB-TZ2
Carbon Steel
KB-TZ2
Stainless Steel
KB-TZ2
Stainless Steel
KB-TZ2
Carbon Steel
1/4" 4 6 4 6
3/8" 30 30 15 15
1/2" 50 40 25 25
5/8" 40 60 30 35
3/4" 110 125 50 50
Nominal
Anchor
Diameter
Screw Anchor Installation Torque (ft-lb)
Into Concrete Into Masonry
Hilti
KH-EZ Hex
1/4" 18
3/8"
1/2"
5/8"
3/4"
Note: 1/4" dia. Hilti KH-EZ P, PM & PL in concrete shall have installation torque of 18 ft-lb.
Hilti
KH-EZ C
Hilti
KH-EZ CRC
Hilti
KH-EZ E & KH-EZ I
Hilti KH-EZ
(Hex, P, PM, PL & C)
Hilti
KH-EZ CRC
N/A 18 21 N/A
40 (19 @ h nom <2.5") 40 40 22 20
45 N/A 45 N/A 34 25
85 N/A 85 N/A 38 35
95 N/A 85 N/A 70 45
G. PROPRIETARY ANCHORAGES and FASTENERS (CONT.)
H. METAL DECKING
1. Metal Decking and Accessories: Verco Manufacturi ng Company, type and gauge as indicated on structural drawings, ASTM A653-SS grade 50 minimum conforming to IAPMO report ER-2018, G60 coating, unless heavier galvanized coating is indicated in specifications. Run deck units continuous over three or more spans where possible, deck is designed for unshored construction, uno Provide vented deck where vapor impervious material occurs over concrete fill.
2. Deck Welding: AWS D1.3 using prequalified proced ures.
A. Qualification of Welders: Welders shall be expe rienced in welding light-gauge steel and using prequalified procedures. Erector shall establish welding procedure for arc spot welding of metal decking to structural steel, for each gauge of decking to be used. Prior to deck erection, each welder shall be qualified using this procedure and witnessed by Special Inspector. See California Building Code, Chapter 22 and 17, for additional qualification requirements.
3. Shop Drawings: Submit to Architect (Structural Engineer) for review. Shop drawings shall include layout of deck, type of deck, methods of attachment, and all deck openings larger than 1'-0".
4. Limits to Non-Structural Items Suspended From Co ncrete Filled Metal Decking and Bare Metal Decking:
A. Hangers supported by metal decking with structur al concrete fill may be installed using ICC-ES approved anchorage systems. Limit hangers to supporting duct work 6 square feet in cross sectional area maximum, 3-inch diameter pipe maximum, and acoustical ceilings. Locate hangers two flutes apart when they occur on same deck span. Support larger duct work and piping for structural beams or columns as shown in typical details. Do not support utilities, ductwork, piping conduits, and etc. from metal deck without concrete . See typical details for hanger details.
B. Hangers supported by metal decking without struc tural concrete fill may be used for 12"x16" max ducts, 1-1/2" diameter pipes or ceilings. The hangers may be attached w/ 3/8" round x 12" long bars located above and perpendicular to the deck flutes. Locate hangers two flutes apart when they occur in the same deck span.
5. Pre-punched Holes in Metal Decking and Accessori es: Metal deck welding and installation of welded shear studs are not permitted through single layer sheets greater than 16 gauge (G90 MAX), nor through double layer sheets greater than 20 gauge (G60 MAX), nor through sheets with total galvanized coating thickness greater than 1.25 ounces per square foot. Provide pre-punched holes as necessary. Provide closure angle at all openings per typical details.
6. Excess Structural Concrete: Concrete filled met al decking and steel framing will deflect during placement of concrete. These deflections will require placement of concrete in excess of amount based on nominal dimensions in order to bring slab within tolerances of a horizontal plane. Provide excess concrete at no cost to Owner.
7. Deck shall be layed out such that low flutes lan d on each parallel support wherever possible. Provide filler deck accessory where low flutes do not align with parallel framing. Provide 2" minimum bearing at each support and 2" lap at ends of decking panels.
8. Composite slabs:
A. See "Proprietary Anchorage and Fasteners" notes for welded headed studs.
B. Stud welding, inspection and testing shall confo rm to AWS D1.1, CH. 7.
C. 18 gage or thicker decking shall not be lapped w here welded studs are attached through decking.
J. STRUCTURAL STEEL (CONT.)
k. List of applicable electrical characteristics fo r process employed. Clearly indicate specific values required for each welding pass. These electrical characteristics shall include at a minimum the following:
• Electrode diameter.
• Type of current and acceptable ranges of current measured in amperage. For wire feed processes, indicate manufacturers' recommended melt-off rate, deposition rate, and wire feed speed. • Voltage (for all processes).
• Actual field condition travel speed and manufactu rer's data for travel speed. • Electrode extension (stick out) for wire feed pro cesses. • Amperage, voltage and electrode extension (as app licable) shall be within filler metal manufacturer's recommendations (compare to AWS D1.1, Section 3.6 and 3.7).
• Electrode manufacturer's technical information, w ith identification number listed, and welding parameter recommendations.
F. Welding Electrode (Filler Metal): E70xx (70 ksi) uno, provide filler metal with Charpy V-notch toug hness of 20 ft/lbs at -20 degrees Fahrenheit at complete penetration groove welds.
a. Welding Electrode (Filler Metal): E70xx (70 ksi) u.n.o., provide filler metal with Charpy V-notch toughness of 20 ft/lbs at -20 degrees Fahrenheit at complete penetration groove welds.
b. Welds indicated as part of the "SFRS" shall comp ly with AISC 341 sections A3.4a and I2.3. These welded connections shall be made with a filler metal achieving a minimum Charpy V-notch toughness of 20ft/lbs at a temperature lower than 0°F. c. Welds indicated as "Demand Critical" (DC) shall comply with AISC 341 sections A3.4b and I2.3. These welded connections shall be made with a filler metal achieving a minimum Charpy V-notch toughness of 20ft/lbs at a temperature lower than 0°F, and a filler metal producing welds that have a minimum Charpv V-notch toughness of 40ft/lbs at temperature lower than +70°F.
G. Welding Toughness Requirements: Certify conforma nce to Charpy V-notch toughness requirements with tests by an independent testing laboratory for each AWS classification, manufacturer and trade name. Testing procedures shall be in accordance to Applicable Welding Standard and AWS D1.8
H. Fabricators: Perform shop welds by fabricators a pproved by LA City or AISC. a. Welder Qualification: Welders, regardless if Wor k is performed in shop or in field, shall be qualified for the Work they will be doing and shall have certifications current and acceptable to Governing Code Authority. b. Special inspection shall be required for all wel ding, as required by governing code authority.
I. Welds Exposed to View:
a. Faces of fillet welds exposed to view shall have as-welded surfaces that are reasonably smooth and uniform. No finishing or grinding shall be required, except where clearances or fit of other items may so necessitate. b. Partial and full penetration welds exposed to vi ew shall be ground smooth and flush with finish surface of steel. Remove backup bars and weld tabs. Fill holes with weld metal or body solder and smooth by grinding or filing.
J. Groove Preparation: Clean groove preparation the rmal cuts by grinding.
K. Termination of Welds: Terminate at joint ends in a manner that ensures sound welds. Use extension bars and run-off tabs whenever necessary.
L. Hand-held Calibrated Amp and Volt Meters: To be used by fabricator, erector and inspectors to assure proper amperage and voltage of welding process. Measure amperage and voltage at arc. Verify travel speed and electrode stick-out in compliance with electrode manufacturer's recommendations and with approved WPS.
M. Storage of Electrodes: Adhere to Section 5.3 of AWS D1.1.
N. Weld each flange of moment frame beam to column connections in one continuous process without cooling below pre-heat temperature.
O. Welding of ASTM A913 Materials: Perform accordin g to requirements of latest edition of AWS standard, structural drawings and specifications, whichever is more stringent.
P. Minimum Fillet Weld Size: Where minimum fillet w eld size, as stipulated by AISC Section J2 and Table J2.4, exceeds fillet weld size indicated on structural drawings, use AISC stipulated size.
Q. Minimum Groove or Butt Weld Size: Provide comple te penetration unless indicated otherwise.
R. Weld Length: Length of welds shown are net effec tive lengths. Where length of weld is not indicated, provide weld full length of joint.
6. Shop Drawings: Submit To Architect (Structural E ngineer) for review and, upon request, to Governing Code Authority. Include sequence of erection procedures from approved WPS:
7. Fabrication: Perform in shop certified by AISC o r City of Los Angeles.
A. Moment Connections: Orient flange stiffener plat es and cap plates used in moment connections so that rolling direction of plate is parallel with direction of principal stress.
B. Horizontal Members: Place natural camber up.
C. Filler Plates: Provide at splices of parts havin g more than 1/8-inch difference in thickness. Filler plates to match grade of material spliced.
8. Cleaning: After fabrication, clean steel surfaces free of rust, loose mill scale, and oil.
9. Oversized Holes for Anchor Bolts in Base Plates: Oversized holes in base plate may be provided at contractor's option in accordance with AISC Table 14-2 UNO. Where oversized holes are provided, provide plate washer with standard hole with minimum size per AISC Table 14-2 (3/8" thick min) UNO.
10. Exposure to Soil: Encase structural steel in lea n concrete with 4-inches concrete cover where exposed to soil.
11. Exposure to Weather: All structural steel (inclu ding connection elements) exposed to weather shall be hot dipped galvanized. Coordinate finishes with architect at AESS. At welding on galvanized members, remove and repair galvanization as required.
12. Structural Steel Allowance: In addition to the s teel shown or implied in this document, allow for an additional 2 tons of structural steel to be constructed at the direction of the Structural Engineer during construction. The allowed steel may be of any shape or sizes, including plates, wide flanges, tubes, pipes, channels, angles, and/or any other structural shapes. The number of pieces may vary. The locations of applications may vary. Direction may be given in multiple occasions during construction. The allowance should include all fabrication and construction related services, such as shop drawings, shop preparation, field erection and coordination, bolted connections and field welding. Expenditure of any part of this allowance shall be approved in writing by the Structural Engineer prior to any fabrication and erection.
13. Heavy Sections
a. Heavy sections shall comply with AISC 360-16 S ection A3.1c b. Heavy sections forming part of the "SFRS" shal l also comply with AISC 341-16 Section A3.3 c. Welded Splices including welds to baseplates shall comply with AISC 360-16 Section J1.5
14. See quality assurance note C-3 and C.4 for non-d estructive testing.
15. SFRS denotes items considered part of the "SEIM SIC FORCE RESISTING SYSTEM" (Refer to AISC 341-16 and AWS D1.8).
16. DC denotes welds considered "DEMAND CRITICAL" pe r AISC 341-16 Section A3.4B and I2.3
17. Field weld flag symbols indicate design intent but are not requirements. Whether a weld is to be made in shop or field is means and methods and to be coordinated by contractor.
18. Where bent plates specified cannot be bent due to thickness provide two plate pieces joined with a complete penetration weld.
J. STRUCTURAL STEEL
1. Detailing, Fabrication, and Erection: AISC 360-1 6 "Specification for Structural Steel Buildings" and AISC 341-16 "Seismic Provisions for Structural Steel Buildings" except as amended in Applicable Code Chapter 22 and as modified by supplemental requirements herein.
2. Structural Steel: Provide readily identifiable s tructural steel in compliance with Applicable Code Section 2202.1. Furnish structural steel complying with the following ASTM standard specifications, unless noted otherwise:
A. Structural Steel Unless Indicated Otherwise: AS TM A992, Grade 50 B. Angles and Channels: ASTM A36
C. Plates: ASTM A572, Grade 50
D. Pipes: ASTM A53, Grade B (35 ksi)
E. Rectangular Tubes: ASTM A500, Grade C (50 ksi)
F. Round Tubes: ASTM A500, Grade C (46 ksi) G. Anchor Bolts: ASTM F1554, grade 55 (weldable)
3. Holes for Bolted Connections and Anchor Bolts: A ISC "standard" holes limited to 1/16-inch larger in diameter than nominal bolt diameter, unless noted otherwise. See Note 9, for oversized holes for anchor bolts in base plates.
4. High Strength Bolts, Nuts and Washers: AISC "Spe cification for Structural Joints Using High-Strength Bolts." A. Hardened Washers: ASTM F436, under nuts except w here plate washers are used. Provide beveled washers where joint face slope is greater than 1:20.
B. Tightening: Snug tight for all high strength bol ts except tighten A325-SC and A490-SC bolts to at least the minimum proper tension according to AISC Specification.
C. Provide Class A Faying Surface or better at bolt ed connections indicated with "SC" type bolts.
D. All bolts parts of "SFRS" shall be "SC" type bol ts.
5. Welding:
A. Applicable Welding Standard: Applicable Code and latest adopted edition of AWS D1.1 including, but not limited to, the following:
a. Section 6.4 for qualified welders.
b. Section 4.2 and AISC 360-16 Specification Sectio n M2-2 for jumbo sections for preheat and interpass temperature requirements. c. Section 5 for arc welding.
d. Section 6 for inspection.
B. Pre-qualified and Non Pre-qualified Welds: Welds shall be pre-qualified in compliance with Applicable Welding Standard. Where non pre- qualified welds are to be used, qualify by test and procedure qualification test record complying with Applicable Welding Standard.
C. Work performed by Welders and Inspectors: Adher e to approved Welding Procedure Specification (WPS). Each welder and inspector shall retain a copy of WPS.
D. Pre-construction Meeting: Conduct to include Arc hitect (Structural Engineer), fabricator, erector, Contractor and inspectors to discuss Welding Procedure Specification (WPS).
E. Welding Procedure Specification (WPS): Fabricato r/erector to develop WPS in compliance with Applicable Welding Standard. Submit to Architect (Structural Engineer) for acceptance and Governing Code Authority for approval prior to fabrication. WPS submittal to include the following:
a. Welding manufacturers' specifications.
b. Information required by Applicable Code, Contrac t Documents and any other information necessary to produce welds that are in compliance with Applicable Welding Standard.
c. Detailed sequence of weld sketches addressing ef fects of welding heat for welds at joints and within seismic frame assemblies as a whole. Plan sequence of erection and welding to minimize locked in stresses and distortion considering effects of welding heat.
Procedures submitted shall result in completed connections which comply with design intent of structural drawings. No deviation from structural drawings is permitted unless otherwise accepted by Architect (Structural Engineer) and approved by Governing Code Authority.
d. Welding parameters recommended by electrode manu facturer. e. List of applicable base metal types and thicknes ses. f. Welding joint sketches including joint type, wel d type, joint geometry, and applicable dimensions. Individual weld passes shall be identified in sketches and numbered to identify the sequence of their deposition. Sketches shall identify the maximum layer thicknesses and bead widths. In no case shall layer thickness exceed 1/4-inch, nor shall maximum bead width exceed 5/8-inch. g. Applicable welding process.
h. Position of welding.
i. List of filler metal per Applicable Welding Stan dard and electrode specification and classification. Include details showing shielding material to be used.
j. Minimum preheat requirements, interpass temperat ures and post weld heat treatment. Minimum specified preheat shall meet requirements of AWS D1.1, table 3.2, and AISC 360-16 Section M2-2 requirements for jumbo sections.
K. LIGHT GAUGE METAL FRAMING GENERAL NOTES (CONT.)
8. Securing Studs and Braces: Plumb, align and tigh tly nest in both upper and lower tracks with secure attachment to both flanges of tracks.
Splices in axial loaded studs and braces are not permitted.
9. Self-Drilling Screws: See General Notes.
10. Welding: ANSI/AWS D1.3 and CBC Section 2210A. Wire tying of framing components is not permitted. a. Welder Certification: Governing Code Authority.
b. Electrodes: E60XX at 33 ksi members, E70XX at 50 ksi members. c. Touch-Up: Zinc-rich paint at galvanized members and regular paint at carbon sheet steel.
K. LIGHT GAUGE METAL FRAMING GENERAL NOTES
1. Applicable Standards: CBC Section 2210A and "Spec ifications for the Design of Cold-Formed Steel Structural Members" of AISI, S100-2016 Edition including amendments and referenced standards. Minimum yield strength shall be as follows:
a. 43 mils (18 gauge) and lighter (33 ksi):
1. Carbon Sheet Steel to be Painted: ASTM A1003 , Grade 33.
2. Galvanized: ASTM A653, Grade A.
b. 54 mils (16 gauge) and heavier (50 ksi):
1. Carbon Sheet Steel to be Painted: ASTM A100 3, Grade 50.
2. Galvanized: ASTM A653, Grade D.
2. Manufacturer and Properties: Member of Steel Stu d Manufacturer's Association (SSMA) complying with ICC-ESR 3064P or Cemco compything with ICC-ESR 3016. Provide punched studs as scheduled in these drawings with minimum effective section properties as indicated in referenced evaluation report.
3. Minimum Gauge Thicknesses: Indicated properties are based on the following thicknesses:
12 ga. - 0.1017 inch, 97 mils 14 ga. - 0.0713 inch, 68 mils 16 ga. - 0.0566 inch, 54 mils 18 ga. - 0.0451 inch, 43 mils 20 ga. - .0329 inch, 33 mils
4. Track Material: Provide unpunched track of dimens ions to ensure proper fit of studs with minimum effective section properties as indicated in referenced evaluation report.
5. Lateral Bridging for Studs: Required when rigid wall finish does not continue full height on either or both sides of studs. Install horizontal straps or cold-rolled channels as shown and in accordance with Section D3 of AISI specification. See typical det ails.
6. Lateral Blocking for Joists: Joists shall be bra ced by full depth blocking at all points of support. Joist blocking shall also be provided at the following locations: See typical details.
7. Joist Web Punch-Out Locations: Web punch-outs sh all not be located closer than twice the member depth from edge of bearing support or concentrated loads, 12" minimum. Do not provide punchouts at tracks.
1. Specified Compressive Strength of Masonry (f'm): 2000 psi typical unless noted otherwise.
2. Verifying Specified Compressive Strength of Maso nry (f'm): Use masonry prism testing method unless otherwise acceptable to Architect (Structural Engineer). Full allowable stresses are used in design. Submit masonry prism data for each type and compressive strength of masonry required, with a professional engineer's signature and state of California seal, to Architect (Structural Engineer). Compliance with minimum required compressive strength shall be based on Applicable Code Section 2105.2.
3. Concrete Block: ASTM C90, medium weight, attain ing a minimum compressive strength as required to meet specified compressive strength of masonry (f'm).
4. Face Brick: ASTM C216.
5. Portland Cement for Mortar and Grout: ASTM C150 , type I or II. Use of masonry cement or plastic cement is not permitted.
6. Aggregates for Mortar and Grout:
A. Aggregates for Mortar: ASTM C144.
B. Aggregates for Grout: ASTM C404, coarse type.
7. Mortar: ASTM C270, Type S.
8. Grout: ASTM C476, coarse type, attaining a mini mum compressive strength as required to meet specified compressive strength of masonry (f'm). However, in no case shall grout compressive strength be less than 2000 psi at 28 days.
9. Reinforcing Steel: Reinforcing steel section of general notes unless indicated otherwise.
10. Composite Masonry Wall Penetration Submittal: Submit for each wall indicating size and location of each wall penetration and opening as necessary by affected trades. Submit together with appropriate reinforcing steel shop drawings. Submit written statement from Special Inspector that no additional penetrations or openings were added to those shown in penetration submittal.
11. Reinforcing Steel Splices: Lap reinforcing ste el at splices a minimum of 72 bar diameters, except dowels in footings at base of walls shall splice a minimum of 72 bar diameters, unless noted otherwise. Where minimum clear distance between bars at adjacent splices is 3 inches or less, increase lap length 30 percent unless splices are staggered at least 24 bar diameters.
12. Dowels for Walls, Columns, Pilasters, and Piers : Match size and spacing of vertical reinforcing steel, unless noted otherwise. Set dowels to align with cells containing reinforcing steel.
13. Minimum Reinforcing Steel Clearances:
A. Minimum Clearances Between Reinforcing and Outsi de Face of Masonry: 2 inches except in no case shall clearance be less than 2-1/2 bar diameters.
B. Minimum Clearance Between Reinforcing and Inside Face of Grout Cell: 1/2 inch or 1 bar diameter whichever is greater.
C. Minimum Clearance Distances Between Parallel Rei nforcing: 1 inch or nominal bar diameter, whichever is greater. Increase to 1-1/2 inches or 1-1/2 times nominal bar diameter, whichever is greater, at columns, pilasters, and piers only.
14. Placement: Set courses in running bond pattern unless indicated otherwise. Set cells in vertical alignment. Provide flush mortar joints at surfaces to receive waterproofing or damp-proofing.
15. Grouting: Grout solid all cells. Mechanically vibrate grout in cells.
A. Grout Height Limits: CBC Section 2104.2.4 TMS 6 02, Article 3.5 D B. Horizontal Construction Joints: Hold grout 1 1/ 2 inches below top of masonry unit if work is stopped one hour longer.
C. Grout Cover Around Reinforcing Steel, Anchor Bol ts and Inserts Penetrating Masonry Shell: 1 inch minimum.
16. Horizontal Bars Terminating at Wall Ends and Op ening Jambs: Extend bars to within 2 inches of end of wall and provide standard ACI 90- degree hook unless detailed otherwise.
17. Control joints shall be provided as indicated o n Arch and per detail 01/S6.61. If not indicated on Arch, provide control joints at 25'-0" o/c maximum and coordinate w/ Arch.
L. MASONRY
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"
CIVIL ENGINEER DATE
RCE EXP.
REVIEWED BY:
INSPECTOR DATE
SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
12" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
GENERAL NOTES
S0.02
Checker
MONROE ST. POOL REPLACEMENT
GENERAL NOTES
UPDATE
09/30/25
256
58 203
3RD PLAN CHECK SUBMITTAL 07/21/2024
08/09/2024
203
Q. EXISTING CONDITIONS:
1. Field verify all conditions and dimensions prior to shop drawings production and fabrication of structural elements.
2. Where existing conditions vary significantly fro m those shown on these drawings, the Structural Engineer shall be notified prior to continued construction related to subject conditions.
3. Shore all existing construction as required.
4. All existing (E) connections at elements to be r eplaced shall be replaced or re-attached to match existing conditions u.n.o.
5. Verfity location of existing (E) rebar before fr abrication using non-destructive testing.
6. Verify location of existing (E) sleeve before dr illing holes(s) for bolt(s).
7. See "As-Builts" drawings for existing building d esign for items not shown or noted.
P. ROUGH CARPENTRY
1. Structural Lumber: Grade marked Douglas Fir-Lar ch structural lumber complying with Standard Grading Rules No. 17 (2018) of the West Coast Lumber Inspection Bureau. Provide air-dry lumber with 19 percent maximum moisture content. 4x and larger members may be provided green and air dried to 19 percent maximum moisture content
2. Classifications and Grades:
3. Plywood: U.S. Product Standard PS 1-19 and class ified as Exposure 1. Each sheet of plywood shall be identified with appropriate trademark of the American Plywood Association.
4. Pressure Treat Structural Lumber Bearing on Conc rete or Masonry: See Specifications. Provide hot dipped galvanized or stainless steel fasteners and hardware connectors where in contact with pressure treated structural lumber.
5. Nails: Common nails with dimensional properties complying with ASTM Fl 667. Install nails in compliance with Applicable Code Chapter 23, including Table 2304.10.2 2022 CBC (repeated below).
6. Bolts: ASTM A307 bolts with standard cut washer under bolt head and nut Provide holes for bolts 1/32 to 1/16 inch larger than nominal bolt diameter. Re-lighten bons prior to application of sheathing or finish.
7. Anchor Bolts: ASTM F1554, Grade 55, UNO.
8. Lag Screws: ANSI/ASME Standard B18.2.1 including Appendix I for lag screw dimensions. Pre-drill all holes. Hole at shank portion to match diameter of shank. Holes at threaded portion to be 40-70 percent of shank diameter and equal to length of threaded portion. Use soap and lubricants to facilitate installation. Driving with hammer is not permitted.
9. Wood Screw: ANSI/ASME Standard 818.6.1 for wood screw dimensions. Driving with hammer is not permitted.
10. Plate Washers: Provide under heads or nuts of b olts (including anchor bolts at sill plates) and lag screws per 09/S6.81 when anchoring wood.
11. Wood Hardware Connectors: Manufactured by Simps on Strong-Tie Company. Inc complying with ICC-ES Evaluation Report No's ESR-2105, ESR-2523. ESR-2549, ESR-2553. ESR-2604. ESR-2615, and ESR-3096. Install connectors using fasteners in acoordance with manufacturer's written instructions. Fill all holes to achieve maximum load capacity per manufacturer. For connectors requiring nails. use common nails unless shorter nails (sinkers) are specifically indicated.
12. Notching or Cutting Structural Lumber: Not perm itted unless specifically detailed or indicated.
13. Lateral Support for Beams. Rafters and Joists: Full Depth 2 inches thick continuous solid bloddng shall be proved at 8 feet on center or midspan, whichever is less
14. Provide 4x or 3 1/2" min. thick framing members at fire sprinkler lateral andlor longitudinal bracing attachment location.
Coordinate with fire sprinkler drawings for locations of pipe bracing required.
Member
Rafters and Joists Larger Than 2x4
2x4 Joists and Rafters
4x Beams, Headers and Stringers
Beams, Headers and Stringers Larger Than 4x
4x Posts
Posts Larger Than 4x
Studs, Plates and Blocking in bearing or shear walls
Studs, Plates and Blocking in non-bearing walls
Size Classification
2" to 4" thick, 2" and wider
2" to 4" thick, 2" and wider
2" to 4" thick, 2" and wider
Beams and Stringers
4" thick, 4" and wider
Posts and Timbers
2" to 4" thick, 2" and wider
2" to 4" thick, 2" and wider
Grade
No. 1
No. 1
No. 1
No. 1
No. 1
No. 1
No. 1
No. 2
All nails are common nails unless written acceptance by Architect (Structural Engineer) is attained.
1. Joist to sill or girder, toenail
2. Bridging to joist, toe nail each end
3. 1"x6" subfloor or less to each joist, face nail
4. Wider than 1"x6" subfloor to each joist, face na il
5. 2" subfloor to joist or girder, blind and face n ail
6. Sole plate to joist or blocking, typical face na il
7. Sole plate to joist or blocking, at braced wall panels
8. Top plate to stud, end nail
9. Stud to sole plate
10. Double studs, face nail
11. Doubled top plates, typical face nail
12. Doubled top plates, lap splice
13. Blocking between joists or rafters to top plate , toe nail
14. Rim joist to top plate, toe nail
15. Top plates, laps and intersections, face nail
16. Continuous header, two pieces
17. Ceiling joist to plate, toe nail
18. Continuous header to stud, toe nail
19. Ceiling joists, laps over partitions, face nail
20. Ceiling joists to parallel rafters, face nail
21. Rafter to plate, toe nail
22. 1" brace to each stud and plate, face nail
23. 1"x8" sheathing or less to each bearing, face n ail
24. Wider than 1"x8" sheathing to each bearing, fac e nail
25. 2" planks
26. Built-up corner studs
27. Built-up girder and beams
S. NAILING SCHEDULE (PORTION OF CBC TABLE 2304.10.2)
3-8d
2-8d
2-8d
3-8d
2-16d
16d @ 6" o/c
3-16d per 16"
2-16d
4-8d, toe nail or 2-16d, end nail
16d @ 24" o/c
16d @ 16" o/c
8-16d
3-8d
8d @ 6" o/c
2-16d
16d @ 16" o/c along each edge
3-8d
4-8d
3-16d
3-16d
3-8d
2-8d
3-8d
3-8d
2-16d at each bearing
16d @ 24" o/c
20d @ 32" o/c at top and bottom and staggered 2-20d
at ends and at each splice.
T. STATEMENT OF SPECIAL INSPECTION
Special Inspections shall be performed in accordance with Chapter 17 of the California Building Code and any local ordinance. (FILLED BOXES INDICATES REQUIRED ITEMS)
Section 1705 Special Inspections
1. Steel, section 1705.2 . All onsite structural steel fabrication and erection including welding, and high strength bolting is subject to special inspection per CBC Table 1705.2.3 Offsite fabrication may only be performed by an approved fabricator.
2. Concrete, section 1705.3 . All Structural Concrete is subject to special inspection per Table 1705.3 and local ordinance.
3. Masonry section 1705.4. Structural masonry elements, except for masonry fireplaces, are subject to special inspection.
4. High Load Diaphragms, section 1705.5 . The following describes high load diaphragms (diaphragms designed in accordance to Table 2306.2) subject special inspection requirements as described in section 1705.5.1, (plan sheet or detail reference is acceptable).
5. Soil, section 1705.6 . Footing excavations are subject to verification that proper depth and bearing material have been reached prior to placement of concrete per Table 1705.6 (Note: work performed under a grading permit is subject to separate special inspection requirements.)
6. Pile Foundation, section 1705.7 . Piles are subject to special inspection per Table 1705.7.
7. Pier Foundation, section 1705.8 . Piers are subject to special inspection per Table 1705.8.
8. Sprayed Fire-Resistant Material. Sprayed Fire-Re sistant applied to structural elements and decks are subject to special inspection per section 1705.15
9. Mastic and Intumescent Fire-resistant Coatings. Mastic and Intumescent Fire-resistant Coatings applied to structural elements and decks are subject to special inspection per section 1705.16.
10. Exterior Insulation and Finish Systems (EIFS). Exterior Insulation and Finish Systems (EIFS) are subject to special inspection per section 1705.17.
11. Other, section 1705.1.1. The following describe s additional systems or elements subject to special inspection as required by the Chief building Official, Engineer of Record, manufacturer's instructions or Evaluation Report: All those required by referenced Evaluation Reports, including Epoxy anchors per ICC ER-2322 and expansion anchors per ICC ER-1917.
12. Smoke Control, section 1705.19.
Section 1705.13 Special Inspections for Seismic Resistance The following are applicable to specified seismic force-resisting systems, designated seismic systems, and architectural, mechanical, and electrical components.
Seismic-Force Resisting Systems . The following describes the seismic-force resisting system(s) subject to special inspection per applicable section 1705.13 as indicated below:
13. Structural Steel, section 1705.13.1 Continuous inspection is required for structural steel welding in accordance with AISC 341.
14. Structural Wood Systems, section 1705.13.2 The following describes the nailing, bolting, anchoring and other fastening components subject to periodic special inspection
15. Cold-Formed Steel framing, section1705.13.3 The following describes the welding, screw attachment, bolting, anchoring and other fastening components such as struts, braces and hold-downs subject to periodic inspection.
16. Storage racks and access floors, section 1705.13.7 Periodic special inspection is required during the anchorage of storage racks 8 feet or greater in height.
17. Architectural components, section 1705.13.5. Periodic special inspection is required during the erection and fastening of suspended ceiling system, exterior cladding, interior and exterior nonbearing walls, and interior and exterior veneer.
18. Mechanical and Electrical Components, section 1705.13.6 . Periodic special inspection is required during the installation and anchorage of:
A. Electrical equipment for emergency or standby po wer system, B. Other electrical equipment,
C. The following piping system(s) and associated me chanical units intended to carry flammable, combustible or highly toxic contents:
D. The following HVAC ducts intended to carry hazar dous materials:
E. The following vibration isolation system:
19. Designated Seismic System Verifications, section 1705.13 . The special inspector shall verify the certificated of compliance per section 1705.13.4, and that labeling, anchorage and mounting conforms to the certificate for the following mechanical and electrical equipment:
20. Seismic Isolation System, section 1705.14.4 Periodic special inspection is required during the fabrication and installation for isolator units and energy dissipation devices.
Section 1705.14 Structural Testing for Seismic Resistance Note: Documentation referred to below shall be referenced and made part of the special inspector's daily and final report.
21. Masonry, section 1705.4 and TMS 402/602-16
A. The special inspector shall verify certificates of compliance prior to construction.
B. The special inspector shall verify tests and sub mittal per TMS 602 Tables 3 and 4 (Level 2 QA) C. The special inspector shall verify tests and sub mittal per TMS 602 Tables 3 and 4 (Level 3 QA)
22. Reinforcing and Prestressing Steel, section 1705.3
A. The special inspector shall verify certified mil l test reports for each delivery of reinforcing steel for steel used to resist flexural, shear and axial forces in intermediate or special moment frames, and boundary elements of special reinforced concrete or masonry shear wall.
B. ASTM A 615 reinforcing steel grade 40 or 60 used to resist flexural or axial forces in special moment frames and boundary elements in shear walls. The special inspector shall verify testing demonstrates requirements of ACI 318-19 section 20.2.2.5 are met
a. actual yield strength shall not exceed fy by more than 18,000 psi b. the ratio of actual tensile strength to actual y ield strength is not less than 1.25. (i) Actual yield strength based on mill tests does not exceed/j. by more than 18,000 psi (ii) Ratio of the actual tensile strength to the act ual yield strength is at least 1.25 (iii) Minimum fracture elongation in 8 in. shall be at least 14 percent for bar sizes No. 3 through No. 6, at least 12 percent for bar sizes No. 7 through No. 11, and at least 10 percent for bar sizes No. 14 and No. 18. (iv) Minimum uniform elongation shall be at least 9 percent for bar sizes No. 3 through No. 10, and at least 6 percent for bar sizes No. 11, No. 14, and No. 18.
C. ASTM A 615 reinforcing steel specified to be weld ed. The special inspector shall verify chemical testing report demonstrates weldability per ACI 318-19 section 26.6.4 and ANSI/AWS D1.4. Above documentation shall be referenced a nd made part of the special inspector's daily and final report.
23. Structural Steel, section 1705.14.1. The following describes required testing of welds, base metal, weld tab removal sites, and thermally cut surfaces of beam copes or access holes per CBC section 1705.13 and AISC 341. MT = Magnetic Particle Testing per AWS D1.8, UT = Ultrasonic Testing AWS D1.8. Testing procedures and acceptance criteria shall conform to AISC 341 and AWS D1.8. Testing shall be performed at a construction materials testing laboratory certified by the Authority Having Jurisdiction.
A. K-area welding- web area shall be MT'd for cracks in the k-area base metal within 3 inches minimum of the weld.
B. Complete joint penetration groove welds - All sha ll be UT'd for materials 5/16 inches or thicker.
C. Complete joint penetration groove welds - 25% of all beam to column connections shall be MT'd.
D. Base metal for lamellar tearing - UT testing for discontinuities behind and adjacent to weld fusion line for all complete joint penetration groove welded connections for tension loading in the through thickness direction of base metal greater than 1 1/2 inch thickness to connected piece greater than 3/4 inch.
E. Flange and web thicknesses exceeding 1 1/2 inche s.
F. Ends of welds from which a weld tab has been rem oved shall be MT'd. (Note: n/a for continuity plate weld tabs) G. MT percentage reduction protocol is as follows ( note- may not exceed that allowed by AISC 341):
H. High-strength bolting per AISC 341-16 J7.
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"
CIVIL ENGINEER DATE
RCE EXP.
REVIEWED BY:
INSPECTOR DATE
SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
12" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
GENERAL NOTES
S0.03
Checker
MONROE ST. POOL REPLACEMENT
GENERAL NOTES
09/30/25
256
59 203
3RD PLAN CHECK SUBMITTAL 07/21/2024
08/09/2024
203
A
CAISSON DETAIL
SECTION A -A
(3) TIES WITHIN 5" OF
CAISSON TOP
STD 90° HOOKS
STEEL POST PER LANDSCAPE/ARCH
TOP OF LOWEST EXT
OR BUILDING CONC
SLAB ON GRADE OR FINISH
GRADE ELEVATION
CONC CAISSON
PER SCHEDULE
STL POST PER PLAN W/
3/4"Øx4" LONG WELDED HEADED
ANCHORS EA SIDE @ 12" O/C (1st
SET OF ANCHORS 3" FROM BOTTOM
OF HSS) - WHERE OCCURS PER
SCHEDULE
TERMINATE TIE @
SEPARATE VERT
BARS W/ 135° HOOK,
TYP
WHERE ADJ TO SOIL
3" MIN CONC COVER
SEE SCHED
A
3" CLR.
1 1/2"
3"
3" CLR.
3" CLR.
PER SCHEDULE
CAISSON DIA
CAISSON DEPTH SCHEDULE 1'-0"
C A I S S O N S C H E D U L E
DIA
DESCRIPTION
CAISSON
DEPTH VERTICAL
BARS "Bv"
TIES
DESIGNATION REFERENCE
1A
1B
18" 4'-6" STEEL FENCE
1D
(6) #5 #3 @ 6"
1C
1E
1F
1G
1H
HEADED
STUDS REQ
POST MAX
HEIGHT
"H"
PEDESTRIAN GATE
VEHICULAR GATE
TRASH
ENCLOSURE GATE
---
---
---
---
SEE SEC A-A
8'-0" 04/L5.08
REINFORCEMENT PER
SCHEDULE
6" MIN LAP
STL POST PER
LANDSCAPE/ARCH
"H" TO TOP
OF POST
18" 5'-0" (6) #5 #3 @ 6" SEE SEC A-A 9'-0" 08/L5.08 & 02/L5.10 18" 5'-0" (6) #5 #3 @ 6" SEE SEC A-A 8'-0" 04/L4.04
18" 4'-6" (6) #5 #3 @ 6" SEE SEC A-A 6'-0" ----
NOTE: SEE LIGHT POLE MFR FOR
LIGHT POLE, BASE PLATE, &
ANCHORAGE INFO
3/4" CHAMFER UNLESS
INDICATED OTHERWISE
ON ARCH
(3) #4 TIES WITHIN TOP 5"
OF FTG - 1st TIE 1 1/2" FROM
TOP OF CONC
PREPARE COMPACTED FILL OR
UNDISTURBED SOIL
(6)#5 VERT BARS W/ #4
TIES @ 9" OC
FINISH GRADE OR
PAVING SURFACE
NOTE:
1. CONCRETE F'c = 3500 AT 28 DAYS
PVC CONDUIT
FIXTURE PER ELEC DWG
HEIGHT CAISSON
DEPTH
20'-0" MAX 5'-6"
DIA
24"
TOP OF CAISSON WHERE
OCCURS PER LANDSCAPE
HEIGHT CAISSON DEPTH
5"
4" CLR
TYP
3" CLR
DIA PER SCHED
CAISSON
NOTE:
CAST CAISSON FTG INTEGRAL WITH
CONT FTG
EXT GRADE OR PAVING PER
ARCH / CIVIL
CAISSON FTG CONT FTG
PER SCHED 06/-
WHERE CONT FTG
LONGITUDINAL BARS ARE OBSTRUCTED,
DRAPE BARS TO PASS OR ADD BAR OF SAME
SIZE FOR EA INTERRUPTED BAR AS SHOWN
CONT FTG TRANSVERSE BAR OR TIE
A
PLAN VIEW A -A
SECTION
A
CLASS "B"
SPLICE
CLASS "B"
SPLICE
2" TYP
REINF PER SCHED
CMU WALL THICKNESS
HEIGHT "H" WIDTH "W" CMU WALL
THICKNESS VERTICAL REINF
S C H E D U L E
#4 @ 16" ALT FACE
#5 @ 16" AT ALT FACE
#5 @ 16" EA FACE
#6 @ 16" EA FACE
#6 @ 16" EA FACE
6'-0" 3'-0"
8'-0" 4'-0"
5'-0" 10'-0"
13'-0"
15'-0" 7'-6"
6'-6"
8"
8"
8"
8"
10"
#5x 30" @ 16" OC WHERE CONC
SLAB OCCURS
DOWELS TO MATCH VERT REINF W/
STD 90° HOOKS AT BOTTOM OF FTG
VERT REINF PER
SCHEDULE
CONC BLOCK GROUTED
SOLID PER SCHEDULE
12"
#4 HORIZ @ 16" OC - PLACE AT ℄
OF WALL
EQ.
ADD BAR AT SLAB
DOWELS
EXT PAVING BY
OTHERS
2x4 CONT KEY - FILL W/
MASONRY GROUT OR
MORTAR
FTG REINF #6 @ 12" OC
EA WAY
2'-0"
HEIGHT "H"
2"
W
72db
MIN
1'-0"
TYP
3" CLR
CMU WALL THICKNESS
EXTERIOR FINISH
PER LANDSCAPE
CLR
3"
18"
MIN
PER LANDSCAPE
MIN.
1'-6"
(E) WALL AND FOOTING
AS OCCURS (V.I.F.) -
CONTRACTOR SHALL
NOTIFY SHALL
ARCHITECT IF (E)
CONDITION DIFFERS.
#5 @ 6" O/C W/ 90° HOOKED ENDS
(4) #5 LONGITUDINAL BARS
3'-0" LONG AT 4"x4" POST
4'-0" LONG AT 6"x6" POST
1" MIN. - 2" MAX.
NON-SHRINK GROUT
4" MIN. CONC.
COVER, TYP.
B B A A
EXTERIOR GRADE OR
SLAB PER
CIVIL/LANDSCAPE
BUILDING WALL WHERE
OCCURS
A A
POST PER LANDSCAPE
4" MAX.
PER LANDSCAPE
4" MIN. CONC.
COVER, TYP.
FENCE AND GATE ADJACENT TO (E) BUILDING___ FENCE AND GATE ADJACENT TO NEW BUILDING OR NEW WALL___ MIN.
4"
3" MIN.
WHERE ADJACENT WALL
DOES NOT OCCUR, PROVIDE
BASE PLATE PER PLAN VIEW
B-B
AB
MIN.
6 "
WALL and FOOTING ARE
CONT. WERE OCCURS
MIN.
1 2 "
PAPER JOINT.
POST PER LANDSCAPE
EQ. EQ.
PLAN VIEW A-A
AT 4"x4" POST
5/16
PLAN VIEW A-A
AT 6"x6" POST
BASE PL. 5/8x10x0'-10" W/
(4) 1/2"Ø THREADED
RODS SET IN DRILL and
EPOXY ANCHORS PER
GEN'L NOTES - 8" MIN.
EMBED.
BASE PL. 5/8x12x1'-0" W/
(4) 1/2"Ø THREADED
RODS SET IN DRILL and
EPOXY ANCHORS PER
GEN'L NOTES - 8" MIN.
EMBED.
EQ. EQ.
5/16
TYP.
1 1/2"
WALL PARALLEL TO FENCE/GATE
WHERE OCCURS, EXTEND
FOOTING 30" MIN. PAST END OF
WALL FOR POST CONN.
FOOTING PER PLAN
EQ. EQ.
PLAN VIEW B-B
AT 4"x4" POST
5/16
PLAN VIEW B-B
AT 6"x6" POST
BASE PL. 5/8x10x0'-10" W/
(4) 1/2"Ø THREADED
RODS SET IN DRILL and
EPOXY ANCHORS PER
GEN'L NOTES - 8" MIN.
EMBED.
BASE PL. 5/8x12x1'-0" W/
(4) 1/2"Ø THREADED
RODS SET IN DRILL and
EPOXY ANCHORS PER
GEN'L NOTES - 8" MIN.
EMBED.
EQ. EQ.
5/16
TYP.
1 1/2"
EQ. EQ. EQ. EQ.
(CENTERED CONDITION) (CENTERED CONDITION)
PROVIDE PAPER
JOINT.
MIN.
10" 24" MAX.
VERIFY W/ MECH'L/ELECT.
4" MIN.
#5@9" EA. WAY TOP &
BOTT. W/ STD. BEND EA.
END TYP., U.N.O.
ON GRADE
EXT. SLAB ON GRADE
OR FINISH GRADE PER
CIVIL/LANDSCAPE
NOTES:
SEE MECHANICAL and ELECTRICAL DRAWINGS FOR THE FOLLOWING:
1. LOCATION and DIMENSIONS OF BASES.
2. LOCATION, NUMBER, SIZE and TYPE OF BOLTS.
3. EMBEDMENT DEPTH OF EXPANSION ANCHORS WHERE OCCURS.
3" CLR. 2" CLR.
TYP.
3" CLR.
VERIFY W/ MECH and ELEC.
TYP.
12" MIN.
TYP.
6" MIN.
ANCHOR PER MECH AND
ELEC DRAWING
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"
CIVIL ENGINEER DATE
RCE EXP.
REVIEWED BY:
INSPECTOR DATE
SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
SITE DETAILS
S1.11
Checker
MONROE ST. POOL REPLACEMENT
SITE DETAILS
N.T.S.
01 TYP CAISSON SCHED. and DETAIL
N.T.S.
04 TYP SITE LIGHT POLE DETAIL
N.T.S.
03 TYPICAL CMU WALL ADJACENT
TO LIGHT POLE FOOTING
N.T.S.
02 TYP MASONRY FREE STANDING WALL
N.T.S.
05 TYP. FENCE POST NEXT TO (E) BLDG OR CMU WALL
06 TYPICAL CONCRETE BASE FOR EQUIPMENT
09/30/25
8'-0"
256
60 203
3RD PLAN CHECK SUBMITTAL 07/21/2024
08/09/2024
203
EXT GRADE OR PAVING
PER ARCH / CIVIL
CONT FTG
PER SCHED
REINF PER SCHED
CMU WALL THICKNESS
GATE POST WHERE
OCCURS
NOTE:
ADJACENT SCOREBOARD FOOTING SHALL
HAVE NO INFLUENCE OR SURCHARGE ON
FREESTANDING WALL FOOTING.
02 S1.11
1'-6"
3'-0"
ADJACENT SCOREBOARD
FOOTING PER OTHERS
12" MIN
TOP OF LOWEST EXT
OR BUILDING CONC
SLAB ON GRADE OR FINISH
GRADE ELEVATION
1"
6" TYP
9"
SOLAR PANEL &
ATTACHMENT PER
MEP/MANUFACTURER
CENENTITIOUS GROUT
1" MIN. NON-SHRINK
ROUND CONCRETE
PEDESTAL PER PLAN
1/2"Ø F1554 GR36 ANCHOR
AT EACH PEDESTAL
2"
6"
A
SECTION A-A
A
CHANNEL BEAM PER PLAN
6" MAX
CHANNEL BEAM PER PLAN
PLAN VIEW
CASSION AND REINF'G
PER 01/-
CASSION PER 01/-
LANDSCAPE AND ARCHITEC.
PER
SECTION
POST PER PLAN
CASSION AND REINF'G
PER 01/-
CASSION PER 01/-
FINISH GRADE OR
EXTERIOR PAVING
A A
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"
CIVIL ENGINEER DATE
RCE EXP.
REVIEWED BY:
INSPECTOR DATE
SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
SITE DETAILS
S1.12
Checker
MONROE ST. POOL REPLACEMENT
SITE DETAILS
N.T.S.
02 FREESTANDING CMU WALL ADJACENT TO
SCOREBOARD FOOTING
N.T.S.
7SOLAR PANEL DETAIL
N.T.S.
01 TYP. COMBINED CAISSON FOOTING
09/30/25
256
61 203
3RD PLAN CHECK SUBMITTAL 07/21/2024
08/09/2024
203
C6X10.5
C6X10.5
1'-0"Øx2'-0" DEEP
PEDESTAL, TYP
C6X10.5
C6X10.5
C6X10.5
C6X10.5
C6X10.5
C6X10.5
C6X10.5
C6X10.5
C6X10.5
C6X10.5
C6X10.5
C6X10.5
7 S1.12
SOLAR PANEL
CONN DETAIL
TYP
EQ.
21'-0" MAX
EQ.
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"
CIVIL ENGINEER DATE
RCE EXP.
REVIEWED BY:
INSPECTOR DATE
SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
1/8" = 1'-0"
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
SITE PLAN
S1.21
Checker
MONROE ST. POOL REPLACEMENT
SITE PLAN
1/8" = 1' -0"
1SOLAR PANEL FOUNDATION PLAN
N
PROJECT NORTH
N
TRUE NORTH
09/30/25
256
62 203
3RD PLAN CHECK SUBMITTAL 07/21/2024
08/09/2024
11 S6.61
11 S6.61
8 S6.03
1 A
2 BC
3 4
D
11'-0" 28'-8" 12'-8"
33'-4" 17'-4" 45'-4"
96'-0"
52'-4"
S2.01A
13 SEISM
IC GAP
1 1/2"
1 S3.02
3 S3.02
2 S3.02
4 S3.02
5 S3.02
CF1
CF1
CF1
HSS4
X4X3/8
TYP
4" 9'-10"
1'-10" 15'-5 3/4" 15'-5 3/4" 15'-5 3/4" 13'-5 3/4"
TYP
TYP
6"
GB1
GB1
GB1
GB1
GB1
2 S3.21
1 S3.21
(E) HSS3 1/2 SQ, TYP
(E) HSS3 1/2 SQ, TYP
(N) 4x6
(N) 4x6 (E)DBL 2X4
STUDS
(E) 1'-4"WX1'-0"
CONT FOOTING
TYP
(E) 4'-3"SQX1'-0"
DEEP FOOTING (VIF)
(E) 4'-3"SQX1'-0"
DEEP FOOTING (VIF)
(E) 1'-4"WX1'-0"
CONT FOOTING
(VIF)
(E) 2'-0"SQX1'-0"
DEEP FTG
(E) 2'-0"SQX1'-0"
DEEP FTG
4 S6.82
TYP
10 S3.21
(N) SLAB-ON-GRADE
PER FOUNDATION
PLAN NOTE 3
03 S6.04
(N) SLAB-ON-GRADE
PER FOUNDATION
PLAN NOTE 3
1'-0"
6"
PLAN NOTES
1. FOR GENERAL NOTES SEE S0 SERIES SHEETS. FOR TYPI CAL DETAILS SEE S6 SERIES SHEETS.
2. SEE ARCHITECTURAL, MECHANICAL, ELECTRICAL, and P LUMBING DRAWINGS FOR TOP OF
CONCRETE SLAB ON GRADE ELEVATIONS, DEPRESSIONS, SLOPES, OPENINGS, DRAINS, TRENCHES, PADS, and CURBS; SLAB EDGE LOCATIONS; WALL OVERALL DIMENSIONS; and LOCATIONS OF OPENINGS NOT INDICATED ON STRUCTURAL D RAWINGS.
3. BUILDING SLAB-ON-GRADE: 5" THICK W/ #4 @ 12 O/C EACH WAY at CENTER OF SLAB OVER 15 MIL VISQUEEN (LAP 6" AT JOINTS and TAPE SEAL - OMIT VISQUEEN AT EXTERIOR AREAS) OVER PROPERLY COMPACTED FILL AS DESCRIBED IN GEOTECHNICAL REPORT. PROVIDE
CONSTRUCTION JOINTS OR WEAKENED PLANE JOINTS IN SLAB-ON-GRADE EACH DIRECTION PER DETAIL 06/S6.01 - AT AREAS TO RECEIVE TILE, COORDINATE LOCATION OF JOINTS IN SLAB TO ALIGN WITH TILE EXPANSION JOINTS PER ARCH.
4. CENTER COLUMNS ON NUMBERED GRID LINES UNLESS NOT ED OTHERWISE. CENTER SPREAD FOOTINGS and CONTINUOUS FOOTINGS ON COLUMNS UNLESS NOTED OTHERWISE.
5. IN NO CASE SHALL PIPES, CONDUITS, OR SLEEVES BE EMBEDDED IN SPREAD OR
CONTINUOUS FOOTINGS OR WITHIN TOP OR BOTTOM THIRD OF GRADE BEAMS UNLESS SPECIFICALLY DETAILED ON STRUCTURAL DRAWINGS. PIPES, CONDUITS OR SLEEVES MAY
ONLY BE EMBEDDED WITHIN THE MIDDLE THIRD OF GRADE BEAMS WHERE NOTED ON STRUCTURAL PLANS AND DETAILED IN THE STRUCTURAL DRAWINGS.
6. WHERE CONTINUOUS FOOTINGS and SPREAD FOOTINGS IN TERSECT, EXCAVATE TO BOTTOM OF DEEPER FOOTING and CONTINUE ALL BARS THRU INTERSECTION. PLACE BARS AT CONTINUOUS FOOTING CORNERS and INTERSECTIONS PER 05/S6.01. WHERE CONTINUOUS
FOOTINGS TERMINATE AT SIDES OF GRADE BEAMS OR SPREA D FOOTINGS, EXTEND LONGITUDINAL BARS TO FAR SIDE OF GRADE BEAM OR SPRE AD FOOTING and TERMINATE W/ STANDARD 90° HOOK.
7. LOCATE TOP OF SPREAD FOOTINGS, GRADE BEAMS and C ONTINUOUS FOOTINGS -2'-0" BELOW LOWEST ADJACENT SLAB OR GRADE ELEVATION UNLESS NOTED OTHERWISE.
8. GEOTECHNICAL OBSERVATION / COMPACTION REPORT SHA LL BE SUBMITTED TO THE BUILDING INSPECTOR PRIOR TO FOOTING INSPECTION.
9. COORDINATE EXTENT OF CONCRETE PADS SUPPORTING EQ UIPMENT WITH MANUFACTURER
AND WITH EDGE DISTANCE REQUIREMENTS PER EQUIPMENT A NCHORAGE DETAILS IN S6.9X SERIES.
10. CONTRACTOR SHALL BE RESPONSIBLE FOR NECESSARY S HORING OF ADJACENT EXISTING FOOTING.
11. SEE CIVIL DRAWINGS FOR APPROXIMATE LOCATION OF EXISTING UNDERGROUND UTILITIES.
PROTECT OR RELOCATE EXISTING UTILITIES AS REQUIRED DURING FOOTING EXCAVATION OR CONSTRUCTION. DO NOT SURCHARGE EXISTING UTILITIE S, SEE 01/S6.01 FOR ADDITIONAL CLARIFICATION.
1 CD
2 S3.02
4 S3.02
5 S3.02
CF1
CF1
CF1
CF1
11 S6.61 TYP TYP
(N) SLAB-ON-GRADE
PER FOUNDATION
PLAN NOTE 3
LEGEND
HSSXx
XX
INDICATES COLUMN ABOVE GB - SEE 04/S6.05 UNO
FX
XX.XX'
CFX
INDICATES CHANGE IN ELEVATION AT SLAB ON GRADE - SEE DETAIL 12/S6.02 UNLESS DETAILED OTHERWISE
INDICATES CONCRETE CURB OR HOUSEKEEPING
PAD - CONSTRUCT PER 06D/S6.01 UNO
OR
+X'-X"
S - - - - - - - S
INDICATES CONT. FOOTING - SEE SCHEDULE ON S2.01
INDICATES SPREAD FOOTING MARK - SEE SCHEDULE THIS SHEET and 13/S6.01
INDICATES TOP OF SPREAD FOOTING ELEVATION - IF NO ELEVATION INDICATED, LOCATE TOP OF SPREAD FOOTING PER NOTE 7
INDICATES ELEVATION OF TOP OF STRUCTURAL CONCRETE S LAB (TOC) -
SEE ARCHITECTURAL FOR TOC IF NO ELEVATION INDICATE D
INDICATES TOP OF FOOTING ELEVATION
DENOTES LIGHT GAUGE METAL STUD FRAMING - SEE SCHEDULE ON 01/S6.71A AND 01/S6.71B
INDICATES STEP IN CONTINUOUS FOOTING OR GRADE BEAM - SEE 06/S6.01 TOF
DENOTES 8" THICK CONCRETE BLOCK SHEAR WALL SOLID GROUTED - FOR REINFORCING and OTHER INFORMATION SEE CMU WALL
ELEVATIONS and S6.61
DENOTES EXISTING CMU WALLS
GB INDICATES GRADE BEAM - SEE SCHEDULE ON 01/S6.04
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"
CIVIL ENGINEER DATE
RCE EXP.
REVIEWED BY:
INSPECTOR DATE
SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
FOUNDATION PLAN
- BLDG A
S2.01A
Checker
MONROE ST. POOL REPLACEMENT
FOUNDATION PLAN - BLDG A
KEYPLAN
A
B
1/8" = 1' -0"
07 FOUNDATION PLAN - BLDG A
1/4" = 1' -0"
13 ENLARGED FOUNDATION PLAN - BLDG A
C O N T I N U O U S F O O T I N G S C H E D U L E
Mark
FOOTING SIZE
(WIDTH x DEPTH)
REINFORCING
CONTINUOUS
LONGITUDINAL BARS TRANSVERSE BARS
CF1 48"x18" (3) #6 TOP & BOTTOM #6 @ 12"O/C TOP & BOTT OM N
PROJECT NORTH
N
TRUE NORTH
N
PROJECT NORTH
N
TRUE NORTH
09/30/25
256
63 3RD PLAN CHECK SUBMITTAL 07/21/2024
08/09/2024
203
PLAN NOTES
1. FOR GENERAL NOTES SEE S0 SERIES SHEETS. FOR TYPI CAL DETAILS SEE S6 SERIES SHEETS.
2. SEE ARCHITECTURAL, MECHANICAL, ELECTRICAL, and P LUMBING DRAWINGS FOR TOP OF
CONCRETE SLAB ON GRADE ELEVATIONS, DEPRESSIONS, SLOPES, OPENINGS, DRAINS, TRENCHES, PADS, and CURBS; SLAB EDGE LOCATIONS; WALL OVERALL DIMENSIONS; and LOCATIONS OF OPENINGS NOT INDICATED ON STRUCTURAL D RAWINGS.
3. BUILDING SLAB-ON-GRADE: 5" THICK W/ #4 @ 12 O/C EACH WAY at CENTER OF SLAB OVER 15 MIL VISQUEEN (LAP 6" AT JOINTS and TAPE SEAL - OMIT VISQUEEN AT EXTERIOR AREAS) OVER PROPERLY COMPACTED FILL AS DESCRIBED IN GEOTECHNICAL REPORT. PROVIDE
CONSTRUCTION JOINTS OR WEAKENED PLANE JOINTS IN SLAB-ON-GRADE EACH DIRECTION PER DETAIL 06/S6.01 - AT AREAS TO RECEIVE TILE, COOR DINATE LOCATION OF JOINTS IN SLAB TO ALIGN WITH TILE EXPANSION JOINTS PER ARCH.
4. CENTER COLUMNS ON NUMBERED GRID LINES UNLESS NOT ED OTHERWISE. CENTER SPREAD FOOTINGS and CONTINUOUS FOOTINGS ON COLUMNS UNLESS NOTED OTHERWISE.
5. IN NO CASE SHALL PIPES, CONDUITS, OR SLEEVES BE EMBEDDED IN SPREAD OR
CONTINUOUS FOOTINGS OR WITHIN TOP OR BOTTOM THIRD OF GRADE BEAMS UNLESS SPECIFICALLY DETAILED ON STRUCTURAL DRAWINGS. PIPES, CONDUITS OR SLEEVES MAY
ONLY BE EMBEDDED WITHIN THE MIDDLE THIRD OF GRADE BEAMS WHERE NOTED ON STRUCTURAL PLANS AND DETAILED IN THE STRUCTURAL DRAWINGS.
6. WHERE CONTINUOUS FOOTINGS and SPREAD FOOTINGS IN TERSECT, EXCAVATE TO BOTTOM OF DEEPER FOOTING and CONTINUE ALL BARS THRU INTERSECTION. PLACE BARS AT CONTINUOUS FOOTING CORNERS and INTERSECTIONS PER 05/S6.01. WHERE CONTINUOUS
FOOTINGS TERMINATE AT SIDES OF GRADE BEAMS OR SPREA D FOOTINGS, EXTEND LONGITUDINAL BARS TO FAR SIDE OF GRADE BEAM OR SPRE AD FOOTING and TERMINATE W/ STANDARD 90° HOOK.
7. LOCATE TOP OF SPREAD FOOTINGS, GRADE BEAMS and C ONTINUOUS FOOTINGS -2'-0" BELOW LOWEST ADJACENT SLAB OR GRADE ELEVATION UNLESS NOTED OTHERWISE.
8. GEOTECHNICAL OBSERVATION / COMPACTION REPORT SHA LL BE SUBMITTED TO THE BUILDING INSPECTOR PRIOR TO FOOTING INSPECTION.
9. COORDINATE EXTENT OF CONCRETE PADS SUPPORTING EQ UIPMENT WITH MANUFACTURER
AND WITH EDGE DISTANCE REQUIREMENTS PER EQUIPMENT A NCHORAGE DETAILS IN S6.9X SERIES.
10. CONTRACTOR SHALL BE RESPONSIBLE FOR NECESSARY S HORING OF ADJACENT EXISTING FOOTING.
11. SEE CIVIL DRAWINGS FOR APPROXIMATE LOCATION OF EXISTING UNDERGROUND UTILITIES.
PROTECT OR RELOCATE EXISTING UTILITIES AS REQUIRED DURING FOOTING EXCAVATION OR CONSTRUCTION. DO NOT SURCHARGE EXISTING UTILITIE S, SEE 01/S6.01 FOR ADDITIONAL CLARIFICATION.
5 6
7 F E
2 S3.01
1 S3.01
4 S3.01
3 S3.01
10 S6.61
10 S6.61
11 S6.61
12 S6.61
TYP.
11 S6.61
12 S6.61 TYP.
S - - - - S
PUMP PIT
SLAB-ON-GRADE
PER FOUNDATION
PLAN NOTE 3
SLAB-ON-GRADE
PER FOUNDATION
PLAN NOTE 3
CF1
CF1
CF1
CF1
CF1
CF1
34'-0"
26'-3 13/16" 35'-8 3/16"
62'-0"
5 S3.01
S - - - - S
S - - - - S
S - - - - S
S - - - - S
S - - - - S
S - - - - S
S - - - - S
CF1
CF1
CF1
CF1
CF1
TOF = -2'-0"
TOF = -7'-0"
TOF = -7'-0"
S - - - - S
TOF = -2'-0"
8 S6.63
TYP AT NON-
BEARING CMU
WALLS
S - - - - S
TOF = -4'-0"
PUMP ROOM PITS,
EQT. PAD REFER TO
POOL DESIGN
DRAWINGS, TYP
04 S6.03
SLAB-ON-GRADE
TOF = -4'-0"
5'-0" 8'-0"
6'-0"
LEGEND
HSSXx
XX
INDICATES COLUMN ABOVE GB - SEE 04/S6.05 UNO
FX
XX.XX'
CFX
INDICATES CHANGE IN ELEVATION AT SLAB ON GRADE - SEE DETAIL 12/S6.02 UNLESS DETAILED OTHERWISE
INDICATES CONCRETE CURB OR HOUSEKEEPING
PAD - CONSTRUCT PER 06D/S6.01 UNO
OR
+X'-X"
S - - - - - - - S
INDICATES CONT. FOOTING - SEE SCHEDULE ON S2.01
INDICATES SPREAD FOOTING MARK - SEE SCHEDULE THIS SH EET and 13/S6.01
INDICATES TOP OF SPREAD FOOTING ELEVATION - IF NO EL EVATION INDICATED, LOCATE TOP OF SPREAD FOOTING PER NOTE 7
INDICATES ELEVATION OF TOP OF STRUCTURAL CONCRETE S LAB (TOC) -
SEE ARCHITECTURAL FOR TOC IF NO ELEVATION INDICATE D
INDICATES TOP OF FOOTING ELEVATION
DENOTES LIGHT GAUGE METAL STUD FRAMING - SEE SCHEDULE ON 01/S6.71A AND 01/S6.71B
INDICATES STEP IN CONTINUOUS FOOTING OR GRADE BEAM - SEE 06/S6.01 TOF
DENOTES 8" THICK CONCRETE BLOCK SHEAR WALL SOLID GROUTED - FOR REINFORCING and OTHER INFORMATION SEE CMU WALL
ELEVATIONS and S6.61
DENOTES EXISTING CMU WALLS
GB INDICATES GRADE BEAM - SEE SCHEDULE ON 01/S6.04
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"
CIVIL ENGINEER DATE
RCE EXP.
REVIEWED BY:
INSPECTOR DATE
SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
FOUNDATION PLAN
- BLDG B
S2.01B
Checker
MONROE ST. POOL REPLACEMENT
FOUNDATION PLAN - BLDG B
KEYPLAN
A
B
1/4" = 1' -0"
101 - FLOOR - ENLARGED - BLDG B
C O N T I N U O U S F O O T I N G S C H E D U L E
Mark
FOOTING SIZE
(WIDTH x DEPTH)
REINFORCING
CONTINUOUS
LONGITUDINAL BARS TRANSVERSE BARS
CF1 48"x18" (3) #6 TOP & BOTTOM #6 @ 12"O/C TOP & BOTT OM N
PROJECT NORTH
N
TRUE NORTH
09/30/25
256
64 203
3RD PLAN CHECK SUBMITTAL 07/21/2024
08/09/2024
1 A
2 BC
3 4
D
S2.09A
13 HSS8X4X1/4
HSS12X4X3/8
HSS12X4X3/8
HSS12X4X3/8
HSS12X4X3/8
HSS8X4X1/4 HSS8X4X1/4 HSS8X4X1/4 HSS8X4X1/4 HSS8X4X1/4
HSS8X4X1/4 HSS8X4X1/4 HSS8X4X1/4 HSS8X4X1/4 HSS8X4X1/4
HSS12X4X3/8
RD1
4B
S6.12
TYP
O P E N
2 S3.21
1 S3.21
(E) 2X10 @ 24" O/C (E) 2X10 @ 24" O/C
(E) 4x12 (E) 4x12 (E) 4x12 (N) 4x14 (E) 6x10 (E) 4x12 (E) 4x12 (E) 4x12 (N) 4x14 (E) 2X10 @ 24" O/C (E) 2X10 @ 24" O/C
(E) 2X10 @ 24" O/C (E) 2X10 @ 24" O/C
(E) 2X8 @ 16" O/C
(E) 6x14
(E) 6x14
(E) 4x10
8 S6.81
8 S6.81
1 S6.81
BM TO
POST
CONN
3 S6.81
(E) BM TO (N)
BM/POST CONN
6 S6.81
NEW ROOF OPENINGS
SEE PLAN NOTE 14
10 S3.21
FRAMING AROUND
OPENING PER PLAN
NOTE 5, TYP
5 S6.63
EF
5A
75#
EF
6 60#
SF
4 70#
EF
5B
50#
SF
3 125#
EF
4 45#
EF
1B
50#
EF
1A
75#
SF
1 105#
(N) HSS TO (E) CMU
CONN PER
HSS 4x4x1/4
6 S6.63 TYP
HSS 4X4X1/4
@ 4'-0" O/C
4A
S6.12
TYP
1. 1.FOR GENERAL NOTES SEE S0 SERIES SHEETS. FOR TY PICAL DETAILS SEE S6 SERIES SHEETS.
2. SEE ARCHITECTURAL, MECHANICAL, ELECTRICAL, and P LUMBING DRAWINGS FOR TOP OF
STRUCTURAL CONCRETE SLAB OR METAL DECK ELEVATIONS, DEPRESSIONS, SLOPES, CURBS, DRAINS, PADS, DECK EDGE LOCATIONS; WALL OVERALL DIMENSIONS; and LOCATIONS OF OPENINGS IN WALLS and SLABS NOT INDICATED ON STRUCTURAL DRAWINGS.
3. CENTER COLUMNS AT GRID INTERSECTIONS UNLESS NOTE D OTHERWISE.
4. BEAMS ARE SPACED EQUALLY BETWEEN COLUMNS AND GIR DERS UNLESS NOTED OTHERWISE.
5. FOR OPENINGS IN FLOOR UP TO 2'-0" SQUARE SEE 5/S 6.13 and FOR OPENINGS UP TO 4'-0" MAXIMUM (PERPENDICULAR TO DECK SPAN) SEE 3/S6.13. AT EXHAUST FANS, ROOF ACCESS HATCHES, AND OTHER SIMILAR ROOFTOP EQUIPMENT PROVID E DETAILING PER 3/S6.91 REGARDLESS OF OPENING SIZE UNO.
6. ADD ANGLES AT COLUMNS FOR SUPPORT OF METAL DECKI NG PER 15/S6.12.
7. SET BACK STEEL BEAMS ADJACENT TO INTERIOR OPENIN GS OR EXTERIOR EDGES 10 INCHES (CENTERLINE OF BEAM TO DECK EDGE) UNLESS NOTED OTHERWISE - SEE DETAIL 01/S6.13 OR 03/S6.13 FOR TYPICAL DECK EDGE.
8. NO PENETRATION IN STRUCTURAL STEEL IS PERMITTED UNLESS SPECIFICALLY SHOWN ON STRUCTURAL DRAWINGS.
9. SEE S6.9X SERIES FOR EQUIPMENT ANCHORAGE UNLESS NOTED OTHERWISE. WHERE
EQUIPMENT IS ANCHORED DIRECTLY TO BEAM, LOCATE BEAM S CENTERED UNDER EQUIPMENT CURB. WHERE EQUIPMENT IS ANCHORED ON A CONCRETE PAD, LOCATE BEAM CENTERLINE 6" INWARD FROM EDGE OF PAD. WHERE EQUIPMENT IS ANCHORED TO A BUILT-UP CONCRETE PAD, CENTER BEAM ON CONCRETE WALL OF BUILT-UP CONCRETE PAD. COORDINATE EXTENT
OF CONCRETE PADS SUPPORTING EQUIPMENT WITH MANUFACT URER AND WITH EDGE DISTANCE REQUIREMENTS PER EQUIPMENT ANCHORAGE DETAILS.
10. COORDINATE DETAILING AND SECONDARY MEMBERS FOR DEFERRED SUBMITTAL ITEMS PER GENERAL NOTE SECTION B.
11. PROVIDE CONNECTIONS AND SUPPORT FRAMING FOR ROO FTOP DUCTING PER 13/M7.12.
12. SEE ARCH/MEP PLANS FOR EXACT EXTENT OF ROOF PV. EXTENT HAS BEEN DESIGNED FOR AN ADDITTIONAL 7 PSF. UNIFORM DEAD LOAD.
13. VERIFY IN FIELD (V.I.F) ALL (E) FRAMING, DIMENS IONS, CONDITIONS, ETC.
14. CONTRACTOR SHALL VERIFY EXISTING ROOF RAFTER LO CATIONS AND ENSURE NO EXISTING ROOF RAFTER CUT DUE TO ROOF OPENINGS UNLESS APPROVE D BY SEOR. ROOF OPENING DETAIL PER 4/S6.81
15. ROOF SCREEN PER OTHERS, REFER TO ARCH DRAWINGS AND DEFFERED SUBMITTAL ITEMS
PLAN NOTES
1 CD
RD1
W12X26
W12X19
EF
2 45#
SF
2 70#
LEGEND
INDICATES COLUMN BELOW - SEE FOUNDATION PLAN FOR COLUMN SIZE
DENOTES ELEVATION OF TOP OF STRUCTURAL CONCRETE SLA B (TOC) - SEE ARCHITECTURAL FOR TOC IF NO ELEVATION INDICATED +X'-X"
CB
INDICATES CMU WALL BELOW
XxXX <X"> INDICATES WOOD BEAM
INDICATES UPWARD CAMBER (IN INCHES) AT MIDSPAN OF BEAM (IF BEAM
CANTILEVERS, HOLD CANTILEVERED PORTION LEVEL) - IF NO CAMBER INDICATED, NO
CAMBER REQUIRED
DENOTES SEISMIC FORCE RESISTING SYSTEM (SFRS) - SEE GENERAL NOTE SECTION H NOTE 4.C - WHEN (SFRS) IS INDICATED, ALL MEMBERS IN THAT FRAMING LINE ARE (SFRS) MEMBERS
SFRS
INDICATES FACE PLATE BEAM CONNECTION - SEE 07/S6.62
INDICATES LIGHT GAUGE METAL STUD FRAMING BELOW
XX#
INDICATES MEP EQUIPMENT TAG. SEE 01/S6.91 FOR CONCR ETE PAD and/or
ANCHORAGE INFORMATION UNO
INDICATES MAX. EQUIPMENT WEIGHT INCLUDING ALL ACCESSORIES DENOTES ROOF CONSTRUCTION MARK - SEE SCHEDULE THIS SHEET and DETAIL 01/S6.12 - PROVIDE CONSTRUCTION JOINTS IN CONCRETE-FILLED DECK PER 01A/S6.12 - PROVIDE CLOSURES OVER BEAMS AT DECKING CHANGE IN SPAN DIRECTION PER 01B/S6.12 - PROVIDE BENT PLATE OVER BEAMS AT PITCHED ROOFS PER 20/S6.13
RDX
INDICATES BEAM CONTINOUS - SEE X/S6.62
DENOTES EXISTING STURCUTRE MEMBERS
DENOTES NEW STRUCTURE MEMBERS
(N)
(E)
DENOTES BEAM SPLICE - SEE 01D/S6.11 UNO
INDICATES BOTTOM FLANGE BRACING - SEE DETAIL 2/S6.12
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"
CIVIL ENGINEER DATE
RCE EXP.
REVIEWED BY:
INSPECTOR DATE
SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
ROOF FRAMING
PLAN - BLDG A
S2.09A
Checker
MONROE ST. POOL REPLACEMENT
ROOF FRAMING PLAN - BLDG A
KEYPLAN
A
B
1/8" = 1' -0"
07 ROOF FRAMING PLAN - BLDG A
1/4" = 1' -0"
13 ENLARGED ROOF FRAMING PLAN - BLDG A
N
PROJECT NORTH
N
TRUE NORTH
N
PROJECT NORTH
N
TRUE NORTH
09/30/25
256
65 203
3RD PLAN CHECK SUBMITTAL 07/21/2024
08/09/2024
5 6
7 F E
RD1
1 S6.63
TYP
8 S6.62
1 S6.63
TYP
8 S6.62
7B
S6.62 TYP
SLOPE
PER ARCH
4 S6.63
4 S6.63
TYP
TYP
W12X26
W12X45
W12X19
W12X19
W12X45
W12X26
C6X8.2
C6X8.2
ROOF DRAINS,
PROVIDE FRAMING
PER PLAN NOTE 5
TYP UNO
FRAMING AROUND
OPENING PER PLAN
NOTE 5, TYP
W12X19
W12X26 W12X26
W12X26 W12X26
HSS4
X0.12
5 POST ABV, TYP
5 S3.01
08 -
PV FRAMING
PLAN
INVERTER RACK PER
MECH DWGS.
W12X19
W12X19
W12X19
W12X19
W12X26
W12X26
W12X19 W12X19
EF
10 55#
EF
11 60#
EF
12 75#
EF
7 80#
PIPE HANGING PER
DETAIL
2 S6.92
TYP
HANGING PIPE BELOW
PER MEP DRAWINGS
W12X26
W12X19
W12X19
1. 1.FOR GENERAL NOTES SEE S0 SERIES SHEETS. FOR TY PICAL DETAILS SEE S6 SERIES SHEETS.
2. SEE ARCHITECTURAL, MECHANICAL, ELECTRICAL, and P LUMBING DRAWINGS FOR TOP OF
STRUCTURAL CONCRETE SLAB OR METAL DECK ELEVATIONS, DEPRESSIONS, SLOPES, CURBS, DRAINS, PADS, DECK EDGE LOCATIONS; WALL OVERALL DIMENSIONS; and LOCATIONS OF OPENINGS IN WALLS and SLABS NOT INDICATED ON STRUCTURAL DRAWINGS.
3. CENTER COLUMNS AT GRID INTERSECTIONS UNLESS NOTE D OTHERWISE.
4. BEAMS ARE SPACED EQUALLY BETWEEN COLUMNS AND GIR DERS UNLESS NOTED OTHERWISE.
5. FOR OPENINGS IN FLOOR UP TO 2'-0" SQUARE SEE 5/S 6.13 and FOR OPENINGS UP TO 4'-0" MAXIMUM (PERPENDICULAR TO DECK SPAN) SEE 3/S6.13. AT EXHAUST FANS, ROOF ACCESS HATCHES, AND OTHER SIMILAR ROOFTOP EQUIPMENT PROVID E DETAILING PER 3/S6.91 REGARDLESS OF OPENING SIZE UNO.
6. ADD ANGLES AT COLUMNS FOR SUPPORT OF METAL DECKI NG PER 15/S6.12.
7. SET BACK STEEL BEAMS ADJACENT TO INTERIOR OPENIN GS OR EXTERIOR EDGES 10 INCHES (CENTERLINE OF BEAM TO DECK EDGE) UNLESS NOTED OTHERWISE - SEE DETAIL 01/S6.13 OR 03/S6.13 FOR TYPICAL DECK EDGE.
8. NO PENETRATION IN STRUCTURAL STEEL IS PERMITTED UNLESS SPECIFICALLY SHOWN ON STRUCTURAL DRAWINGS.
9. SEE S6.9X SERIES FOR EQUIPMENT ANCHORAGE UNLESS NOTED OTHERWISE. WHERE
EQUIPMENT IS ANCHORED DIRECTLY TO BEAM, LOCATE BEAM S CENTERED UNDER EQUIPMENT CURB. WHERE EQUIPMENT IS ANCHORED ON A CONCRETE PAD, LOCATE BEAM CENTERLINE 6" INWARD FROM EDGE OF PAD. WHERE EQUIPMENT IS ANCHORED TO A BUILT-UP CONCRETE PAD, CENTER BEAM ON CONCRETE WALL OF BUILT-UP CONCRETE PAD. COORDINATE EXTENT
OF CONCRETE PADS SUPPORTING EQUIPMENT WITH MANUFACT URER AND WITH EDGE DISTANCE REQUIREMENTS PER EQUIPMENT ANCHORAGE DETAILS.
10. COORDINATE DETAILING AND SECONDARY MEMBERS FOR DEFERRED SUBMITTAL ITEMS PER GENERAL NOTE SECTION B.
11. PROVIDE CONNECTIONS AND SUPPORT FRAMING FOR ROO FTOP DUCTING PER 13/M7.12.
12. SEE ARCH/MEP PLANS FOR EXACT EXTENT OF ROOF PV. EXTENT HAS BEEN DESIGNED FOR AN ADDITTIONAL 7 PSF. UNIFORM DEAD LOAD.
13. VERIFY IN FIELD (V.I.F) ALL (E) FRAMING, DIMENS IONS, CONDITIONS, ETC.
14. CONTRACTOR SHALL VERIFY EXISTING ROOF RAFTER LO CATIONS AND ENSURE NO EXISTING ROOF RAFTER CUT DUE TO ROOF OPENINGS UNLESS APPROVE D BY SEOR. ROOF OPENING DETAIL PER 4/S6.81
15. ROOF SCREEN PER OTHERS, REFER TO ARCH DRAWINGS AND DEFFERED SUBMITTAL ITEMS
PLAN NOTES LEGEND
INDICATES COLUMN BELOW - SEE FOUNDATION PLAN FOR COLUMN SIZE
DENOTES ELEVATION OF TOP OF STRUCTURAL CONCRETE SLA B (TOC) - SEE ARCHITECTURAL FOR TOC IF NO ELEVATION INDICATED +X'-X"
CB
INDICATES CMU WALL BELOW
XxXX <X"> INDICATES WOOD BEAM
INDICATES UPWARD CAMBER (IN INCHES) AT MIDSPAN OF BEAM (IF BEAM
CANTILEVERS, HOLD CANTILEVERED PORTION LEVEL) - IF NO CAMBER INDICATED, NO
CAMBER REQUIRED
DENOTES SEISMIC FORCE RESISTING SYSTEM (SFRS) - SEE GENERAL NOTE SECTION H NOTE 4.C - WHEN (SFRS) IS INDICATED, ALL MEMBERS IN THAT FRAMING LINE ARE (SFRS) MEMBERS
SFRS
INDICATES FACE PLATE BEAM CONNECTION - SEE 07/S6.62
INDICATES LIGHT GAUGE METAL STUD FRAMING BELOW
XX#
INDICATES MEP EQUIPMENT TAG. SEE 01/S6.91 FOR CONCR ETE PAD and/or
ANCHORAGE INFORMATION UNO
INDICATES MAX. EQUIPMENT WEIGHT INCLUDING ALL ACCESSORIES DENOTES ROOF CONSTRUCTION MARK - SEE SCHEDULE THIS SHEET and DETAIL 01/S6.12 - PROVIDE CONSTRUCTION JOINTS IN CONCRETE-FILLED DECK PER 01A/S6.12 - PROVIDE CLOSURES OVER BEAMS AT DECKING CHANGE IN SPAN DIRECTION PER 01B/S6.12 - PROVIDE BENT PLATE OVER BEAMS AT PITCHED ROOFS PER 20/S6.13
RDX
INDICATES BEAM CONTINOUS - SEE X/S6.62
DENOTES EXISTING STURCUTRE MEMBERS
DENOTES NEW STRUCTURE MEMBERS
(N)
(E)
DENOTES BEAM SPLICE - SEE 01D/S6.11 UNO
INDICATES BOTTOM FLANGE BRACING - SEE DETAIL 2/S6.12
6 W6X12
W6X12
W6X9
W6X9
W6X9
TYP
5 S3.01
6 S6.92
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"
CIVIL ENGINEER DATE
RCE EXP.
REVIEWED BY:
INSPECTOR DATE
SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
ROOF FRAMING
PLAN - BLDG B
S2.09B
Checker
MONROE ST. POOL REPLACEMENT
ROOF FRAMING PLAN - BLDG B
KEYPLAN
A
B
1/4" = 1' -0"
07 ROOF FRAMING PLAN - BLDG B
1/4" = 1' -0"
08 PV FRAMING PLAN BLDG B
N
PROJECT NORTH
N
TRUE NORTH
N
PROJECT NORTH
N
TRUE NORTH
09/30/25
256
66 203
3RD PLAN CHECK SUBMITTAL 07/21/2024
08/09/2024
01 - FLOOR
0"
5 6 7
(2) #5 CHORD REINF
OPEN
OPEN
(2) #5
(2) #5
(2) #5
(2) #5
(2) #5
(2) #5
TYP HORIZ REINF. PER 1/S6.61
TYP VERT REINF.
PER 1/S6.61
(2) #5
(2) #5
TOP OF BLOCK
EAST - BLDG A
10' -6"
01 - FLOOR
0"
567
(2) #5 CHORD REINF
OPEN
TYP HORIZ REINF. PER 1/S6.61
(2) #5
(2) #5
(2) #5
(2) #5
(2) #5
TYP VERT REINF.
PER 1/S6.61
TOP OF BLOCK
EAST - BLDG A
10' -6"
01 - FLOOR
0"
FE
(2) #5 CHORD REINF
OPEN
(2) #5
(2) #5
(2) #5
TYP HORIZ REINF. PER 1/S6.61
TYP VERT REINF.
PER 1/S6.61
(2) #5
(2) #5
TOP OF BLOCK
EAST - BLDG A
10' -6"
01 - FLOOR
0"
F E
(2) #5 CHORD REINF
OPEN OPEN OPEN
(2) #5
(2) #5
(2) #5
(2) #5
(2) #5
(2) #5
TYP HORIZ REINF. PER 1/S6.61
TYP VERT
REINF. PER
1/S6.61 (2) #5
(2) #5
(2) #5
OPEN
TOP OF BLOCK
EAST - BLDG A
10' -6"
CONCRETE BLOCK SHEAR WALL ELEVATION NOTES
1. FOR GENERAL NOTES SEE S0 SERIES SHEETS. FOR TYPICAL DETAILS SEE S6 SERIES SHEETS.
2. SEE ARCHITECTURAL DRAWINGS FOR WALL DIMENSIONS and LOCATIONS OF OPENINGS NOT INDICATED ON STRUCTURAL DRAWINGS.
3. COORDINATE LOCATIONS OF PIPE, DUCT, and CONDUIT PENE TRATIONS OF SHEAR WALLS WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, and PLUMBING DRAWINGS. REINFORCE DUCT PENETRATIONS PER 01/S6.61 UNO and REINFORCE PIPE and CONDUIT PENETRATIONS PER 04/S6.63 UNO. NO OPENINGS LARGER THAN 8" SQ. (MADE WITHOUT INTERRUPTING WALL REINFORCING) IS PERMITTED UNLESS THE LOCATIONS and SIZES ARE SHOWN ON SHEAR WALL ELEVATIONS. SEE DETAIL 04/S6.63 FOR
LIMITATIONS OF OPENINGS MADE WITHOUT INTERRUPTING WALL
REINFORCING.
4. SEE REINFORCING STEEL SECTION OF THE GENERAL NOTES FOR
ADDITIONAL REBAR REQUIREMENTS FOR VERTICAL REBAR IN SHEAR WALLS.
5. CONSTRUCT MASONRY WALL INCLUDING OPENINGS AND WALL ENDS PER DETAIL 01/S6.61 UNO. SOLID GROUT ALL CELLS IN MASONRY WALLS. SEE 03/S6.61 FOR CONDITION AT CORNERS AND INTERSECTIONS UNO.
6. PROVIDE CHORD REINFORCING WITHIN 24" OF T.O.S. OR T.O .W. ELEVATION.
ENSURE 72db STAGGERED LAP SPLICE. PROVIDE 3 LAYERS OF 2 WALL HORIZONTAL REINFORCING MINIMUM.
7. ENSURE FIRST HORIZONTAL CMU BLOCK JOINT ALIGNS W/ F INISH FLOOR.
CUT FIRST CMU BLOCK ABOVE FOOTING IF NECESSARRY.
8. PROVIDE VERTICAL CONTROL JOINTS IN MASONRY WALLS (R EBAR TO BE CONTINUOUS) PER ARCH (25'-0" O/C MAX) AND 01/S6.61. JOINTS SHALL OCCUR IN FULL HEIGHT WALLS. NO JOINTS SHALL OCCUR IN COLUMNS, BEAMS, OR PILASTERS. CLEARLY INDICATE JOINT LOCATIONS IN CMU WALL SHOP DRAWINGS FOR REVIEW BY ARCHITECT (STRUCTURAL ENGINEER).
9. EMBED CONDUIT VERTICALLY IN WALL ONLY WHERE SPEC IFICALLY SHOWN ON STRUCTURAL ELEVATIONS. CONSTRUCT PER DETAIL 16/S6.61. NO
OTHER UTILITIES MAY BE EMBEDDED IN WALL UNLESS INDICATED OTHERWISE.
10. COORDINATE HORIZONTAL COLLECTOR AND CHORD BARS WITH ANCHOR BOLTS AND EMBED PLATES OVER LENGTH OF WALL. NOTE LEDGER
ANGLES, ANCHOR BOLTS, FACE PLATES AND EMBED PLATES NOT SHOWN FOR CLARITY.
LEGEND
DENOTES 8" THICK CONCRETE BLOCK SHEAR WALL SOLID GROUTED - FOR REINFORCING and OTHER INFORMATION SEE S6.61
01 - FLOOR
0"
F E
(2) #5
TOP OF BLOCK
EAST - BLDG A
10' -6"
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"
CIVIL ENGINEER DATE
RCE EXP.
REVIEWED BY:
INSPECTOR DATE
SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
ELEVATIONS - BLDG
B
S3.01
Checker
MONROE ST. POOL REPLACEMENT
ELEVATIONS - BLDG B
3/16" = 1' -0"
1BUILDING B - POOL MECHANICAL ROOM - WEST
3/16" = 1' -0"
2BUILDING B - POOL MECHANICAL ROOM - EAST
3/16" = 1' -0"
3BUILDING B - POOL MECHANICAL ROOM - SOUTH
3/16" = 1' -0"
4BUILDING B - POOL MECHANICAL ROOM - NORTH
3/16" = 1' -0"
5BUILDING B - POOL MECHANICAL ROOFM
09/30/25
256
67 203
3RD PLAN CHECK SUBMITTAL 07/21/2024
08/09/2024
CONCRETE BLOCK SHEAR WALL ELEVATION NOTES
1. FOR GENERAL NOTES SEE S0 SERIES SHEETS. FOR TYPICAL DETAILS SEE S6 SERIES SHEETS.
2. SEE ARCHITECTURAL DRAWINGS FOR WALL DIMENSIONS and LOCATIONS OF OPENINGS NOT INDICATED ON STRUCTURAL DRAWINGS.
3. COORDINATE LOCATIONS OF PIPE, DUCT, and CONDUIT PENE TRATIONS OF SHEAR WALLS WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, and PLUMBING DRAWINGS. REINFORCE DUCT PENETRATIONS PER 01/S6.61 UNO and REINFORCE PIPE and CONDUIT PENETRATIONS PER 04/S6.63 UNO. NO OPENINGS LARGER THAN 8" SQ. (MADE WITHOUT INTERRUPTING WALL REINFORCING) IS PERMITTED UNLESS THE LOCATIONS and SIZES ARE SHOWN ON SHEAR WALL ELEVATIONS. SEE DETAIL 04/S6.63 FOR
LIMITATIONS OF OPENINGS MADE WITHOUT INTERRUPTING WALL
REINFORCING.
4. SEE REINFORCING STEEL SECTION OF THE GENERAL NOTES FOR
ADDITIONAL REBAR REQUIREMENTS FOR VERTICAL REBAR IN SHEAR WALLS.
5. CONSTRUCT MASONRY WALL INCLUDING OPENINGS AND WALL ENDS PER DETAIL 01/S6.61 UNO. SOLID GROUT ALL CELLS IN MASONRY WALLS. SEE 03/S6.61 FOR CONDITION AT CORNERS AND INTERSECTIONS UNO.
6. PROVIDE CHORD REINFORCING WITHIN 24" OF T.O.S. OR T.O .W. ELEVATION.
ENSURE 72db STAGGERED LAP SPLICE. PROVIDE 3 LAYERS OF 2 WALL HORIZONTAL REINFORCING MINIMUM.
7. ENSURE FIRST HORIZONTAL CMU BLOCK JOINT ALIGNS W/ F INISH FLOOR.
CUT FIRST CMU BLOCK ABOVE FOOTING IF NECESSARRY.
8. PROVIDE VERTICAL CONTROL JOINTS IN MASONRY WALLS (R EBAR TO BE CONTINUOUS) PER ARCH (25'-0" O/C MAX) AND 01/S6.61. JOINTS SHALL OCCUR IN FULL HEIGHT WALLS. NO JOINTS SHALL OCCUR IN COLUMNS, BEAMS, OR PILASTERS. CLEARLY INDICATE JOINT LOCATIONS IN CMU WALL SHOP DRAWINGS FOR REVIEW BY ARCHITECT (STRUCTURAL ENGINEER).
9. EMBED CONDUIT VERTICALLY IN WALL ONLY WHERE SPEC IFICALLY SHOWN ON STRUCTURAL ELEVATIONS. CONSTRUCT PER DETAIL 16/S6.61. NO
OTHER UTILITIES MAY BE EMBEDDED IN WALL UNLESS INDICATED OTHERWISE.
10. COORDINATE HORIZONTAL COLLECTOR AND CHORD BARS WITH ANCHOR BOLTS AND EMBED PLATES OVER LENGTH OF WALL. NOTE LEDGER
ANGLES, ANCHOR BOLTS, FACE PLATES AND EMBED PLATES NOT SHOWN FOR CLARITY.
LEGEND
DENOTES 8" THICK CONCRETE BLOCK SHEAR WALL SOLID GROUTED - FOR REINFORCING and OTHER INFORMATION SEE S6.61
01 - FLOOR
0"
B C D
OPEN
(2) #5
(2) #5
(2) #5 (2) #5 CHORD REINF
TYP. HORIZ REINFORCEMENT PER 1/S6.61
TYP. VERT REINF
PER 1/S6.61
TOP OF BLOCK
EAST - BLDG A
10' -6"
01 - FLOOR
0"
1 (2) #5
(2) #5
PER PLAN
GAP
TYP. HORIZ REINF
PER 1/S6.61
TYP. VERT REINF
PER 1/S6.61
TOP OF BLOCK
EAST - BLDG A
10' -6"
01 - FLOOR
0"
1 OPEN
(2) #5
(2) #5
OPEN
OPEN OPEN
(2) #5
(2) #5
(2) #5
(2) #5
(2) #5
(2) #5
(2) #5
(2) #5
(2) #5
TYP. VERT REINF PER 1/S6.61
TYP. HORIZ REINF PER 1/S6.61
(2) #5
TOP OF BLOCK
EAST - BLDG A
10' -6"
01 - FLOOR
0"
CD
OPEN
(2) #5
(2) #5
(2) #5
(2) #5
TYP. HORIZ REINF
PER 1/S6.61 TYP. VERT REINF
PER 1/S6.61
TOP OF BLOCK
EAST - BLDG A
10' -6"
01 - FLOOR
0"
C D
(2) #5
(2) #5
TYP. HORIZ REINF
PER 1/S6.61
TYP. VERT REINF
PER 1/S6.61
TOP OF BLOCK
EAST - BLDG A
10' -6"
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"
CIVIL ENGINEER DATE
RCE EXP.
REVIEWED BY:
INSPECTOR DATE
SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
ELEVATIONS - BLDG
A
S3.02
Checker
MONROE ST. POOL REPLACEMENT
ELEVATIONS - BLDG A
3/16" = 1' -0"
1BUILDING A - POOL MECHANICAL ROOM - SOUTH
3/16" = 1' -0"
3BUILDING A - POOL MECHANICAL ROOM - EAST
3/16" = 1' -0"
2BUILDING A - POOL MECHANICAL ROOM - WEST
3/16" = 1' -0"
4BUILDING A - POOL MECHANICAL ROOM - NORTH
3/16" = 1' -0"
5BUILDING A - POOL MECHANICAL ROOM - SOUTH
09/30/25
256
68 203
3RD PLAN CHECK SUBMITTAL 07/21/2024
08/09/2024
01 - FLOOR
0"
CD
4C
S6.12
S6.05
4 SLAB ON GRADE
PER LANDSCAPE
HSS BEAM
PER PLAN
GRADE BEAM PER PLAN
HSS COL PER
PLAN - TYP
(E) CMU WALL
(E) FOOTING
NOTES:
CONTRACTOR SHALL BE
RESPONSIBLE FOR
NECESSARY SHORING OF
ADJACENT (E) FOOTING
TOP OF BLOCK
EAST - BLDG A
10' -6"
01 - FLOOR
0"
234
HSS4X4X1/4 HSS4X4X1/4
HSS4X4X1/4 HSS4X4X1/4 HSS4X4X1/4
HSS8X4X1/4 HSS8X4X1/4 HSS8X4X1/4 HSS8X4X1/4 HSS8X4X1/4
HSS3x3x3/16
HSS4X4X3/8
HSS4X4X3/8
HSS4X4X3/8
HSS4X4X3/8
TYP, UNO
HSS3x3x3/16
4B
S6.12
TYP
4B
S6.12
TYP
3 -
HSS3x3x3/16
GRADE BEAM
PER PLAN -
TYP
TOP OF BLOCK
EAST - BLDG A
10' -6"
01 - FLOOR
0"
T.O. BLOCK
9' -10"
AB
TOB BLDG B
13' -0"
HSS3X3X1/4
HSS3X3X1/4 HSS3x3x3/16
HSS3x3x3/16
3 S6.63
(N) BM TO (E)
CMU WALL
CONN SEE
TOP OF BLOCK
EAST - BLDG A
10' -6"
PANEL W/ ANGLES
PER ARCH
HSS BEAM PER PLAN
VERTICAL HSS PER PLAN/SEC
3/16 (3) SIDES
3/16
SCREWS TO VERTICAL
HSS PER OTHERS
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"
CIVIL ENGINEER DATE
RCE EXP.
REVIEWED BY:
INSPECTOR DATE
SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
PERF PANEL
FRAMING
ELEVATIONS AND
SECTION
S3.21
Checker
MONROE ST. POOL REPLACEMENT
PERF PANEL FRAMING ELEVATIONS AND SECTION
1/4" = 1' -0"
2FRAME SECTION
1/4" = 1' -0"
1PERF PANEL FRAMING ELEVATION
1/4" = 1' -0"
10 PERF PANEL FRAMING ELEVATION
1" = 1' -0"
3VERTICAL HSS TO HSS AT PERF PANEL
09/30/25
256
69 203
3RD PLAN CHECK SUBMITTAL 07/21/2024
08/09/2024
PIPES THRU OR BELOW FOUNDATION
TRENCH ADJACENT TO FOUNDATION
A
A
ELEVATION A-A
1 1
PROVIDE PIPE SLEEVE (I.D. 2" LARGER THAN
PIPE O.D. - AT FIRE SPRINKLER PROVIDE I.D.
4" LARGER THAN PIPE O.D.) WHERE
ADJACENT TO CONCRETE - TYPICAL
PLACE THIS CONCRETE BEFORE FOOTING ABOVE -
LEAN CONCRETE PER GENERAL NOTE F.7
PIPE
LOCATE TRENCH SO
THAT FOOTINGS ARE
NOT UNDERMINED
CONT. FOOTING
OR GRADE BEAM
PIPE
LIMIT DISTANCE BETWEEN
SLEEVES TO NO LESS THAN
LARGER SLEEVE OUTSIDE
DIAMETER OR 6"
CONT. FOOTING
OR GRADE BEAM
SPREAD FTG,
CONT FTG, OR
GRADE BEAM
NOTES:
1. DO NOT PLACE SLEEVES OR
CONDUIT IN ISOLATED SPREAD
FOOTINGS - RUN AROUND OR
BELOW THESE FOOTINGS.
2. SLEEVES ARE NOT TO PASS
THROUGH CONTINUOUS
FOOTINGS OR GRADE BEAMS
UNLESS SHOWN OTHERWISE -
WHERE SLEEVES ARE
PERMITTED, LOCATE WITHIN
MIDDLE THIRD OF FOOTING OR
GRADE BEAM DEPTH.
PIPE
SLAB ON GRADE
BACKFILL TRENCH PER
GEOTECHNICAL REPORT
NO EXCAVATION
ALLOWED BELOW
THIS LINE
9" MIN
3 1/2" MIN.
9" MIN
NO SLEEVES
HERE
3" TYP
CONT FTG
OR GRADE BEAM "D"
4" MIN
3'-0" MAX 6" MIN
"D"/3 MAX
1"
1'-6" MIN
STANDARD HOOKS OTHER THAN STIRRUPS AND TIES
#6
B A R D I A M E T E R D I S T A N C E S
STANDARD HOOKS FOR STIRRUPS AND TIES
#3 #4 #5 #10 #9 #7 #8 #11
MAXIMUM OFFSET AT SPLICES
2 1/4"
4 1/2"
-
9"
3"
* INDICATES MINIMUM DIMENSIONS MAY GOVERN
NOTE:
HOOKS OF TWO SUCCESSIVE STIRRUPS OR TIES ENGAGING
SAME LONGITUDINAL BAR SHALL BE ALTERNATED END FOR END
6db FOR #3 THRU #5
12db FOR #6 THRU #8
12db 4 1/2" 6" 7 1/2"
3db
BAR DIAMETERS
8db
6db
4db
1 1/8" 1 1/2" 1 7/8"
2 1/4"* 3"
- -
1 1/2"* 2"*
-
3 3/4"
2 1/2"
#9 THRU #11
#3 THRU #8
15" 13 1/2" 12" 10 1/2" 16 1/2"
135°
10"
3" - -2 5/8"
BAR SIZE
6"
9" -
- -
4 1/2" 4" 5"
5 1/4"
-
3 1/2"
-
11"
-
5 1/2"
90°
1:6 MAXIMUM SHOP
OFFSET BEND
db
6db
#3 - #8
8db
#9 - #11
10db
#14 & #18
2 1/2" MIN.
4db
12db 3db
4db
AS INDICATED
SPLICE LENGTH
db
4db FOR #3 thru #5
6db FOR #6 thru #8
6db FOR #3 THRU #8
3" M
IN.
3" MIN
BAR SPACING DIAGRAM
DIAGRAM AT
STAGGERED SPLICES
I II
S C H E D U L E
F O R D E T E R M I N I N G C A T E G O R Y
SPLICE OR
LAPPING BAR
1:6 MAXIMUM SHOP
OFFSET BEND
LEGEND
A. CLEAR EDGE DISTANCE
B. CENTER TO CENTER SPACING OF SPLICED
OR LAPPED BARS (SEE GENERAL NOTE 'E.8'
FOR MINIMUM CLEAR SPACING)
db - BAR DIAMETER
NOTES:
1. ALL SPLICES SHALL BE CLASS B SPLICES UNLESS INDI CATED OTHERWISE. DEVELOPMENT Ld TO BE USED WHERE SPECIFICALLY INDICATED.
2. SCHEDULE APPLIES TO UNCOATED GRADE 60 BARS IN NO RMAL WEIGHT CONCRETE.
3. TOP BARS (INDICATED "T" IN SCHEDULE) ARE HORIZON TAL BARS WITH MORE THAN 12" OF CONCRETE CAST BELOW THE BARS.
4. BOTTOM BARS (INDICATED "B" IN SCHEDULE) ARE ALL VERTICAL BARS AND HORIZONTAL BARS WITH LESS THAN 12" OF CONCRETE CAST BELOW HORIZONTAL BARS.
5. FOR LIGHTWEIGHT CONCRETE MULTIPLY LENGTHS IN SCH EDULE BY 1.33.
6. AT SPLICE BETWEEN BARS OF VARYING SIZE, PROVIDE LAP SPLICE CORRESPONDING TO LARGER OF 'Ls' OF SMALLER BAR and 'Ld' OF LARGER BAR.
1. A>db and
B>2db and
TIES THRUOUT Ld
2. A>db and
B>3db
OTHER CASES
LENGTH
SPLICE
LENGTH
SPLICE
db
B LENGTH
SPLICE
B A
A B A
db
B
DIAGRAM AT NON -
STAGGERED SPLICES
#6 #4 #3 #5 #10 #8 #7 #9 #11
I
0.750
T T
28 T
4000
3000
B
0.375
T B B
0.625 0.500 1.270
T
1.000
T T B B
0.875
T B B
1.128
T B B
1.410
24 22
19 37
32 29
25 47
40 36
31 56
48 43
37 81
70 63
54 93
80 72
62 105
91 81
70 118
102
91 79
131
113
101
87 SPLICE LENGTH (INCHES)
NORMAL
WEIGHT
CONCRETE
f'c PSI
CATEGORY
TENSION LAP SPLICE "Ls" SCHEDULE
5000 22 17 29 22 36 28 43 33 63 49 72 55 81 63 91 70 101 78 II
42 4000
3000
36 32
28 56
48 43
37 70
60 54
47 84
72 64
56 122
106
94 81
139
121
107
93 157
136
121
105
177
153
136
118
196
170
151
131
5000 33 25 43 33 54 42 65 50 94 73 108 83 122 94 137 105 152 117 #6 #4 #3 #5 #10 #8 #7 #9 #11
I
0.750
T T
22 T
4000
3000
B
0.375
T B B
0.625 0.500 1.270
T
1.000
T T B B
0.875
T B B
1.128
T B B
1.410
19 17
15 29
25 22
19 36
31 28
24 43
37 33
29 63
54 48
42 72
62 55
48 81
70 62
54 91
79 70
61 101
87 78
67 DEVELOPMENT LENGTH (INCHES)
NORMAL
WEIGHT
CONCRETE
f'c PSI
CATEGORY
DEVELOPMENT "Ld" SCHEDULE
5000 17 13 22 17 28 22 33 26 49 37 55 43 63 48 70 54 78 60 II
32 4000
3000
28 25
22 43
37 33
29 54
47 41
36 64
56 50
43 94
81 72
63 107
93 82
71 121
105
93 81
136
118
105
91 151
131
116
101
5000 25 19 33 26 42 32 50 38 73 56 83 64 94 72 105 81 117 90
SLAB ON GRADE JOINT DIAGRAM (PLAN VIEW) TYPICAL SECTION AT SLAB ON GRADE BTYP.
CTYP.
ATYP.
A
TYP.
CONSTRUCTION JOINT
LOCATION TO BE DETERMINED
BY CONTRACTOR PER NOTE 1
ADD (2) #5x4'-0" @ 4" O/C
DIAGONALS (CENTERED IN
SLAB) TYPICAL AT RE-ENTRANT
CORNERS WHERE JOINTS DO
NOT OCCUR
BLOCKOUTS AT
COLUMNS PER
NOTES
1. AREA OF CONCRETE POURS TO BE DETERMINED BY CONTR ACTOR. SUBMIT JOINT LAYOUT PRIOR TO POURING SLABS P ER GENERAL NOTES. PROVIDE CONSTRUCTION JOINTS SURROUNDING AREA OF EACH POUR UNLESS DETAILED OTHERWISE.
ALLOW 24 HOURS MINIMUM BEFORE CASTING SLABS AT ADJACENT AREAS.
2. SAWCUT WEAKENED PLANE JOINT AS SOON AS CONCRETE CAN SUPPORT WEIGHT OF PERSONNEL AND SAW WITHOUT AFFECTING FINAL FINISH BUT NO LATER THAN 12 HOURS AFTER POUR. LOCATE WEAKENED PLANE JOINTS NO GREATER THAN 36 TIMES SLAB THICKNESS "T" (20'-0" MAXIMUM) IN BOTH DIRECTIONS, UNLESS NOTED OTHERWISE.
WEAKENED PLANE
JOINTS PER NOTE 2
SEE NOTE 3 ON
FOUNDATION PLAN
FOR SLAB ON GRADE
THICKNESS AND
REINFORCING SEE PLAN
CLASS B
SLAB THICKNESS
"T"
0"
POUR PER NOTE 1
SHADED AREAS INDICATE
EXTENT OF CONCRETE POUR PER NOTE 1
SHADED AREAS INDICATE
EXTENT OF CONCRETE
13 S6.01
D
#3 DOWELS @ 18" O/C (#4 @
18" O/C WHERE "H">8") SET IN
DRILL and EPOXY ANCHORS
PER GENERAL NOTES
#4 CONTINUOUS
DRILL and EPOXY ANCHOR OPTION
SEE ARCH
DRAWINGS
#4 @ 16" O/C EA. WAY
#3 DOWELS @ 18" O/C (#4 @ 18" O/C
WHERE "H">8") W/ STD. 90° HOOKS
IN SLAB ON GRADE
PREPARE "CONSTRUCTION
JOINT" SURFACE PER
GENERAL NOTES - TYP.
(2) #4 CONTINUOUS
NOTE: DOWELS AT
HOUSEKEEPING PADS ARE REQUIRED AT
PERIMETER OF PADS and AT
INTERMEDIATE ROWS SPACED @ 6'-0"
EACH DIRECTION
NOTE: SEE ARCHITECTURAL
FOR SIZE AND LOCATION OF
CURBS and PADS
TYPICAL CONDITION
CONDITION AT CURB OR HOUSEKEEPING PAD
MAX
6"
1'-6'' MAX
"H"
1'-6"
NOTE: SEE TYPICAL
CONDITION BELOW FOR
REMAINDER OF INFO
1'-6'' MAX
"H"
MAX
6"
PLASTIC
SHEATHING
0"
CONSTRUCTION JOINT A
BARS MAY BE
CONTINUOUS
GALVANIZED TYPE
"KEYED KOLD JOINT"
.
CLASS B
SLAB THICKNESS
"T" T/2
1' - 6" 1' - 6"
2' - 0"
WEAKENED PLANE JOINT B
PLASTIC SHEATHING 1/8" WIDE WET SAWCUT -
FILL W/ SEALANT IF REQ'D
PER ARCHITECTURAL
1' - 0" 1' - 0"
"T"/4
TURNED -DOWN SLAB EDGE C
FINISH GRADE OR
EXTERIOR SURFACE
HOOK BARS 90° AS SHOWN OR
ADD DOWELS MATCHING SLAB
REINFORCING SIZE and SPACING
(#4 @ 24" O/C MIN.) x 2'-0"
CURB WHERE OCCURS -
SEE
#4 CONT. @ 12" O/C -
(2) #4 MIN.
1'-0'' MIN
AS REQ'D AS EXTERIOR
1'-6" MIN INCREASE
8" 6"
06D
-
PLAN VIEW AT INTERSECTIONS PLAN VIEW AT CORNERS
TIE WHERE OCCUR - EXTEND TIES IN
ONE FOOTING THRU INTERSECTIONS
AND CORNERS AS SHOWN
ADD BARS AT CORNERS MATCHING
SIZE AND QUANTITY OF TOP AND
BOTTOM BARS ON OUTSIDE FACE
EXTEND TOP AND BOTTOM
FOOTING BARS TO FAR SIDE
OF INTERSECTING FOOTING
AND PROVIDE STANDARD 90°
HOOKS, TYPICAL
EXTEND TOP AND
BOTTOM FOOTING BARS
TO FAR SIDE OF
INTERSECTING FOOTING
AND PROVIDE STDANDARD
90° HOOKS, TYPICAL
CLASS B SPLICE
CLASS B SPLICE
2" MAX
2" MAX
TYPICAL STEP
MULTIPLE STEPS
ADD BARS MATCHING FOOTING TOP BARS -
IF NO FOOTING TOP BARS, ADD 2 BARS
MATCHING FOOTING BOTTOM BARS
("Rd" = "D"-6")
ADD BARS MATCHING
FOOTING BOTTOM BARS
PROVIDE STD. 90° HOOKS
AT TOP BARS
PROVIDE STD. 90º HOOKS AT
BOTTOM BARS
MAINTAIN TIE SPACING
(WHERE TIES OCCUR)
AT STEPS
"Rd"
DEPTH
"Rd"
DEPTH
.
TYP.
CLASS B
"Rd" DEPTH
MATCH
NOTE: DEPTH "Rd"
INDICATES DISTANCE
BETWEEN TOP AND
BOTTOM FOOTING
LONGITUDINAL BARS
DEPTH "D"
FTG
1' - 6" MAX.
"H"
1' - 6" MAX.
"H"
1' - 6'' MAX
''H''
1' - 6'' MAX
''H''
"D"
MATCH
DEPTH ''D''
FTG
2 (''H'')
1' - 6'' MAX
''H''
DEPTH ''D''
FTG
2(''H'') + ''D''
3'' CLR.
3" CLR.
2("H")
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"
CIVIL ENGINEER DATE
RCE EXP.
REVIEWED BY:
INSPECTOR DATE
SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
TYPICAL
FOUNDATION AND
SOG DETAILS
S6.01
Checker
MONROE ST. POOL REPLACEMENT
TYPICAL FOUNDATION AND SOG DETAILS
N.T.S.
1TYPICAL PIPES THRU OR TRENCHES
ADJACENT TO FOUNDATIONS
N.T.S.
2TYPICAL REINFORCING STEEL
HOOKS, BENDS and OFFSETS AT SPLICES
N.T.S.
3TYPICAL REBAR TENSION SPLICE and BAR DEVELOPMENT SCHEDULE (IN CONCRETE) N.T.S.
4TYPICAL SLAB ON GRADE DETAILS
N.T.S.
5TYPICAL FOOTING REINFORCING AT CORNERS
AND INTERSECTIONS
N.T.S.
6TYP. STEPPED FOOTING/GRADE BEAM DETAIL
09/30/25
256
70 203
3RD PLAN CHECK SUBMITTAL 07/21/2024
08/09/2024
0"
GRADE
(2) #5 x 5'-0"
- TYPICAL
CONSTRUCTION JOINT
AROUND LOCKOUTS -
TYPICAL (NO BARS TO
PASS THRU JOINT)
6x6-W1.4xW1.4 WELDED
WIRE MESH (WRAP
AROUND COLUMN) PROVIDE 90°
BENDS AT ALL
EDGES OF SPREAD
FTG AS SHOWN
BASE PLATE PER PLAN
ADDED DOWELS AT BLOCKOUT
EDGE PER PLANS ABOVE
STL. COL. PER PLAN
SEE PLAN NOTE 8 ON
FOUNDATION PLANS
DOUBLE
NUT
PLAN VIEW at SLAB BLOCKOUTS
INTERIOR CONDITION
PERIMETER CONDITION
SLAB ON GRADE
CONSTRUCTION JOINT OR
WEAKENED PLANE PER
PLAN
FILL BLOCKOUT WITH CONC.
AFTER COMPLETION OF ROOF
CONSTRUCTION ABOVE
INTERIOR PERIMETER
4" CONCRETE COVER OVER
COLUMN ANCHOR BOLTS AND
BASE PLATE
NOTE:
FOR REMINDER OF INFO SEE
INTERIOR CONDITION BELOW
#4 DOWELS @ 12" O/C W/
STD. 90° HOOKS TOP AND
BOTTOM
FOOTING PER PLAN
FOOTING SIZE AND REINFORCING PER PLAN
4" MIN.
3" CLR
3" CLR.
4" MIN
6" MIN
2" TYP. 2" TYP.
.
4 1/2"
.
DOUBLE NUT
2"
2"
NOTES:
1. ADD #4 x 12" DOWELS @ 12" O/C WHERE S IDE WALLS OCCUR AT STAIRS OR RAMP U.N.O.
2. SEE ARCHITECTURAL OR LANDSCAPE FOR TREAD and RIS ER
GEOMETRY AND FINISHING
36"
(2) #4 CONTINUOUS
#4 @ 12" O/C
EACH WAY
#3 NOSING BAR AT
STEPS ON GRADE ONLY
TYPICAL
RAMP LINE
#3 @ 15" O/C AT EACH
NOSING BAR
6"
6"
AT TOP AT BOTTOM TYP.
6"
24"
6"
6"
(2) #4 CONT.
SLAB ON GRADE - (SEE
LANDSCAPE DWGS AT
EXTERIOR CONDITIONS)
#4 BENT BARS @ 12" O/C
SLAB ON GRADE - (SEE
LANDSCAPE DWGS. AT
EXTERIOR CONDITIONS)
2'-0" TYP. 1' - 6" 1' - 6"
2'-0" TYP.
1'-0" 1' - 6"
CLR.
3"
6" MIN.
06A
-
SIM.
06A
-
SIM.
H O O K E D B A R D E V E L O P M E N T
L E N G T H ( L d h ) S C H E D U L E
#3 9"
BAR SIZE Fc' = 3000psi
8"
11" 10"
14" 12"
17" 15"
#5
#6
NOTES:
1. FOR TYPICAL BAR HOOKS & BENDS, SEE DETAIL
2. BAR DEVELOPMENT LENGTHS SHOWN IN SCHEDULE ABOVE APPLY TO NORMAL WEIGHT CONCRETE - MULTIPLY THE SPECIFIED DEVELOPMENT LENGTH BY 1.33 FOR LIGHTWEIGHT CONCRETE.
3. LENGTHS SHOWN IN SCHEDULE ABOVE APPLY TO UNCOATE D GRADE 60 BARS - MULTIPLY THE SPECIFIED LENGTH BY 1.25 FOR GRADE 75 BARS. MULTIPLY THE SPECIFIED LENGTH BY
1.33 FOR GRADE 80 BARS
4. LENGTHS SHOWN IN SCHEDULE ABOVE APPLY TO UNCONFI NED BARS - WHERE CONFINEMENT CAN BE PROVIDED BY ENCLOSED TIES OR STI RRUPS SPACED @ 3db EITHER 1) PERPENDICULAR TO Ldh ALONG THE LENGTH OF Ldh OR 2) PERPENDICULAR TO Lext ALONG THE LENGTH OF Lext, MULTIPLY THE SPECIFIED DE VELOPMENT LENGTH BY 0.8.
5. HOOKED BARS MAY BE SUBSTITUTED WITH HEADED BARS PER 'Ldt' SCHEDULE AT LEFT. #4
#7
20" 17"
#8
Fc' = 4000psi
7"
9"
11"
13"
15"
Fc' = 5000psi
22" 19" 17"
#9 25" 22" 19"
#10 28" 25" 22"
#11 31" 27" 24"
MIN
Ldh
6"
8"
10"
12"
14"
16"
18"
20"
22"
H O O K E D B A R D E V E L O P M E N T
L E N G T H ( L d t ) S C H E D U L E
#3
9"
BAR SIZE Fc' = 3000psi
8"
11" 10"
16"
12"
18" 15"
#5
#6
NOTES:
1. THESE BAR DEVELOPMENT LENGTHS APPLY TO NORMAL WE IGHT CONCRETE ONLY.
2. PROVIDE LENTON HEADED REINFORCING BARS PER IAPMO-UES ER-0188. #4
#7
20" 17"
#8
Fc' = 4000psi
7"
9"
10"
14"
16"
Fc' = 5000psi
23" 20" 18"
#9
25" 22" 19"
#10
#11
MIN
Ldt
6"
8"
10"
13"
14"
16"
18"
13"
7" 6" 6" 6"
Fc' = 6000psi Fc' = 6000psi
12" 14" 11"
Ldt Ldh
Lext
03 -
1/16"
"L" WELD
(MIN)
SIZE
WELD "S"
2"
3"
4"
BAR
SIZE
#3
#4
#5
4"
5"
6"
#6
#7
#8
6"
7"
#9
#10
REBAR
WELDMENT
STEEL
PLATE OR
ANGLE
REBAR START OF
BEND WHERE
APPLICABLE
"D" 3/16"
1/4"
5/16"
3/8"
7/16"
1/2"
9/16"
5/8"
''S''= ''D''/2
"L"
MIN.
5 "D"
"D"
''S''
NOTES
1. ALL REINFORCING WELDING SHALL BE IN ACCORDANCE W ITH A.W.S. CODE D1.4-05 CURRENT EDITION.
2. WELDED REINFORCING SHALL CONFORM TO ASTM A706.
3. ASTM A615 REINFORCING STEEL MAY BE WELDED PROVID ED A CHEMICAL ANALYSIS IS PERFORMED TO DETERMINE CARBON EQUIVALENCY, TO ESTABLISH MINIM UM PREHEATING REQUIREMENTS. HEAT STICKS SHALL BE USED 6" FROM WELD TO VERIFY PREHEAT TEMPERATURES. CHEMICAL ANALYSIS REPORTS SHALL BE PROVIDED TO ARCHITECT (STRUCTURAL ENGINEER) PRIOR TO WELDING. "S" L
"S"
PRIOR TO WELDING
OTHER SIDE, CHIP OR
GRIND ROOT TO
SOUND METAL
NOTES:
1. AS AN ALTERNATE TO LAP SPLICE, BUTT WELD MAY BE USED AS INDICATED ABOVE, PROVIDED THEY ARE STAGGERED @ 24" MINIMUM.
2. AN APPROVED TESTING LABORATORY SHALL PROVIDE A P REQUALIFICATION TENSION TEST FOR SAMPLES ON EVERY SIZE OF BAR BEING WELDED.
3. MATERIALS, CONDITIONS AND WELDING PROCEDURES UTI LIZED SHALL COMPLY WITH THE
CURRENT APPLICABLE BUILDING CODE AND THE REQUIREMENTS OF THE GOVERNING INSPECTION AGENCY.
4. GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL COSTS INCURRED IN OBTAINING APPROVAL.
HORIZONTAL BAR VERTICAL BAR
60.00°
1/8''
1/8''
1/8'' 1/8"
45.00°
FORMOWORK PER
SPECIFICATIONS
STARTER WALL DETAIL
TYPICAL SECTION
A
2" PLANKING
TYPICAL
AFTER SETTING OF
CONCRETE, CLEAN TO
REMOVE LAITANCE and
SCUM - FORMWORK NOT
PERMITTED BELOW GRADE
UNLESS FULLY FORMED
CURB
CONTINUOUS
MINIMUM CLEAN OUT
3x LUMBER
TYPICAL
NOTE:
STAKES NOT PERMITTED WITHIN
FOOTING SECTION
FOOTING
CONCRETE OR
MASONRY WALL
2x4 CONT. SHAPED
KEY UNLESS
DETAILED
OTHERWISE
DRAWINGS+2"
WIDTH
SHOWN ON
6"
ARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
Developed for
Job Number
Checked By
Scale
This document and all other project documents, idea s,
aesthetics and designs incorporated therein are
instruments of service. All project documents are
copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (inc luding the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, us e or misappropriation of property rights held by LPA. The
unauthorized use of the project documents will give rise to the recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existin g
conditions. LPA is not responsible for any discrep ancies between the project documents and the existing
conditions.
© LPA, Inc.
Submittal Date
100% SCHEMATIC DESIGN 06/27/2023
100% DESIGN DEVELOPMENT 09/01/2023
50% CONSTRUCTION DOCS 11/13/2023
1st PLAN CHECK SUBMITTAL 01/29/2024
2nd PLAN CHECK SUBMITTAL 05/01/2024
Revision Date
"AS BUILT"
CIVIL ENGINEER DATE
RCE EXP.
REVIEWED BY:
INSPECTOR DATE
SHEETS SHEET
ENGINEERING DEPARTMENT
CITY OF CARLSBAD
IMPROVEMENT PLAN FOR:
APPROVED:
ENGINEERING MANAGER DATE
DRAWING NO. PROJECT NO. DWN BY:
CHKD BY:
RVWD BY:
DATE INITIAL DATE INITIAL DATE INITIAL
ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL REVISION DESCRIPTION EXPIRES PE 63912 9/30/25
PROJECT 4724 199-4
JOHN MAASHOFF
LICENSE # C61909
As indicated
MONROE ST. POOL REPLACEMENT
3401 MONROE ST
CARLSBAD, CA 92008
CITY OF CARLSBAD
1902710
TYPICAL
FOUNDATION AND
SOG DETAILS
S6.02
Checker
MONROE ST. POOL REPLACEMENT
TYPICAL FOUNDATION AND SOG DETAILS
N.T.S.
1TYPICAL SPREAD FOOTING AT STEEL COLUMN
N.T.S.
2TYPICAL SECTION
AT CONCRETE STEPS OR RAMP ON GRADE
N.T.S.
3HOOKED (Ldh) AND HEADED (Ldt) BAR DEVELOPMENT LENGTH SCHEDULES N.T.S.
4TYPICAL REBAR WELDING
N.T.S.
5TYPICAL REINFORCING BUTT WELDS DETAIL
(ALTERNATE TO SPLICES)
N.T.S.
6TYPICAL MANDATORY FOUNDATION FORWORK
(UNLESS FULLY FORMED)
09/30/25
256
71 203
3RD PLAN CHECK SUBMITTAL 07/21/2024
08/09/2024
INTERSECTION (SINGLE CURTAIN)
CORNER (SINGLE CURTAIN)
#7 OR WALL VERTICALS
WHICHEVER IS GREATER
(4 TOTAL)
ALTERNATE BENDS
#7 OR WALL VERTICALS -
WHICHEVER IS GREATER
(3 TOTAL)
8"
8"
CLASS "B" SPLICE
8"
CLASS "B" SPLICE
8"
NOTE: "db" INDICATES
DIAMETER OF BAR
8" THK CONCRETE WALL
W/ #5 @ 12" O/C EACH WAY
DOWELS TO MATCH SIZE and
SPACING OF VERTICAL BARS -
PROVIDE STD. 90° HOOKS AT