THE USE OF THE PLANS AND SPECIFICATIONS ISRESTRICTED TO THE ORIGINAL SITE FOR WHICHTHEY WERE PREPARED, AND PUBLICATIONTHEREOF IS EXPRESSLY LIMITED TO SUCH USE.REUSE, REPRODUCTION OR PUBLICATION BYANY METHOD IN WHOLE OR IN PART ISPROHIBITED. TITLE TO THE PLANS ANDSPECIFICATIONS REMAINS WITH THE ARCHITECT,AND VISUAL CONTACT WITH THEMCONSTITUTES PRIMA FACIE EVIDENCE OF THEACCEPTANCE OF THESE RESTRICTIONS.
PLOT DATE: 6.5.2024
24040
CENTRAL COAST COMMUNITY ENERGY
1026 PALM STREET - SAN LUIS OBISPO TI
CENTRAL COAST COMMUNITY ENERGY (3CE)
1026 PALM STREET
SAN LUIS OBISPO, CA 93401 APN: 002-323-031
400 N. McCarthy Blvd. Ste. 250
Copyright c 2024
[email protected]
fx: (408) 522-5260
ph: (408) 522-5255
Milpitas, CA 95035
ENGINEERING
NOT FOR CONSTRUCTION
E0.2
ELECTRICAL
SPECIFICATIONS
ELECTIRCAL SPECIFICATIONS
PART 3 EXECUTION
3.05 WIRE COLOR CODE:
COLOR CODING SHALL BE CONTINUOUS FOR WIRE #12 THROUGH #10 AWG. PHASECONDUCTORS #8 AND LARGER AND CONDUCTORS OF ANY SIZE IN CABLE ASSEMBLIES MAY HAVE COLORED PHASING TAPE AT TERMINATIONS. COLOR CODE WIRES ASFOLLOWS:
VOLTAGE PHASE A PHASE B PHASE C NEUTRAL GROUND 120/208V BLACK RED BLUE WHITE GREEN
3.06 IDENTIFICATION:
A. PROVIDE NAMEPLATES FOR SWITCHGEARS, PANELBOARDS, AND ALL SIMILAR DEVICES. NAMEPLATES SHALL BE SCREWED (NO ADHESIVES) ENGRAVED BAKELITE ORPHOTO-ETCHED METALLIC NAMEPLATE IDENTIFICATION SHOWING PANEL DESIGNATION, VOLTAGE AND PHASE IN MINIMUM 1/4" HIGH LETTERS. INDICATE PANEL NAMES AND POWER SOURCE WHERE EQUIPMENT IS FED FROM.B. PROVIDE DYMO LABELS ON ALL LIGHTING SWITCHES AND CONVENIENCE AND SPECIALPURPOSE RECEPTACLES TO SHOW PANEL AND CIRCUIT NUMBER TO WHICH THE DEVICE IS CONNECTED.C. EACH PANELBOARD SHALL CONTAIN A METAL-FRAMED CIRCUIT DIRECTORY INSIDECOVER, WITH PLASTIC PROTECTOR.
D. PANELBOARD SCHEDULE: AFTER COMPLETION OF WORK, PROVIDE TYPEWRITTENUPDATED PANELBOARD SCHEDULES FOR ALL PANELBOARDS.E. ALL CONDUITS SHALL BE LABELED ACCORDING TO THEIR USE (IE. 120V, 277V, 480V, TELEPHONE, FIRE ALARM, ETC.)
3.07 GROUNDING:
A. ELECTRICAL SERVICE AND SEPARATELY DERIVED ALTERNATING CURRENT SYSTEM SHALL BE GROUNDED IN ACCORDANCE WITH NEC ARTICLE 250.3 TO 250.26, INCLUSIVE.
B. GROUND NON-CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENTENCLOSURES, FRAMES, CONDUCTOR RACEWAYS OR CABLE TRAYS TO PROVIDE A LOWIMPEDANCE PATH FOR LINE-TO-GROUND FAULT CURRENT AND TO BAND ALL NON-CURRENT CARRYING METAL FOR LINE-TO-GROUND FAULT CURRENT AND TO BAND ALL NON-CURRENTCARRYING METAL PARTS TOGETHER. PROVIDE GROUND CONDUCTOR IN EACH RACEWAYSYSTEM IN ADDITION TO CONDUCTORS SHOWN. EQUIPMENT GROUND CONDUCTOR SHALL BE
ELECTRICALLY AND MECHANICALLY CONTINUOUS FROM THE ELECTRICAL CIRCUIT SOURCE TO THE EQUIPMENT TO BE GROUNDED. SIZE GROUND CONDUCTORS PER NEC ARTICLE250.122 UNLESS LARGER CONDUCTORS ARE SHOWN ON DRAWINGS.C. GROUNDING CONDUCTORS SHALL BE IDENTIFIED WITH GREEN INSULATION. WHEREGREEN INSULATION IS NOT AVAILABLE ON LARGER SIZES, BLACK INSULATION SHALL BE USED
AND SUITABLY IDENTIFIED WITH GREEN TAPE AT EACH JUNCTION BOX OR DEVICE ENCLOSURE.
3.08 REMODELLING WORK: A. EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BERESTORED TO OPERATING CONDITION. WHERE CONSTRUCTION CHANGES REQUIRE, OUTLETS AND CONDUIT RUNS SHALL BE RELOCATED. EXTEND CONDUITS AND PULL IN NEW WIRING OR INSTALL JUNCTION BOXES AND SPLICE IN NEW WIRING.
B. OUTLETS FROM WHICH FIXTURE, SWITCHES, RECEPTACLES, AND/OR OTHER ELECTRICAL
DEVICES ARE MOVED AND WHICH ARE NOT REPLACED OR REUSED SHALL BE REMOVED, WHERE OUTLETS BOXES, ETC., ARE COMPLETELY REMOVED, THE CONTRACTOR SHALL CUT OFF CONDUITS AND REMOVE WIRING.
C. WHERE CONDUITS EXTENDING THROUGH FLOORS ARE TO BE ABANDONED, THE CONTRACTOR SHALL CUT AND CAP OR PLUG CONDUIT, AND THE CONDUIT SHALL NOTPROTRUDE ABOVE THE FLOOR.
D. WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT SHALL BE REMOVED IF IT IS EXPOSED, IN A CRAWL SPACE OR IN ACCESSIBLE CEILING. WHERE IT IS IMPOSSIBLE TO REMOVE THE CONDUIT, IT SHALL BE CUT OFF AND CAPPED OR PLUGGED.
E. REMOVE ALL EXISTING WIRING NOT REUSED OR REQUIRED TO MAINTAIN CONTINUITY TO CIRCUITS TO REMAIN.
F. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRING PATCHING, PLASTERING, PAINTING AND/OR OTHERREPAIRS DUE TO THE INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF THISSPECIFICATION. CLOSE ALL OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED.
G. MAINTAIN CIRCUIT CONTINUITY TO AREAS OUTSIDE OF THIS WORK. PROVIDE NEW CONDUIT AND CONDUCTORS AS REQUIRED TO MAINTAIN CONTINUITY.
END OF SECTION -
PART 1 GENERAL
1.14 CLEAN-UP:
RID THE PREMISES OF SCRAP MATERIALS, TRASH AND DEBRIS BOTH DURING CONSTRUCTION AND AT COMPLETION OF THE PROJECT. LEAVE THE BUILDING AND SURROUNDING AREA IN A CLEAN AND ORDERLY CONDITION.
1.15 GUARANTEE:GUARANTEE THE INSTALLATION FREE FROM DEFECTS OF WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE
YEAR AFTER DATE OF CERTIFICATION OF FINAL PAYMENT AND PROMPTLY REMEDY ANY DEFECTS DEVELOPING DURING THIS PERIOD, WITHOUT CHARGE.
1.16 TEMPORARY SERVICES:
PROVIDE ADEQUATE AND SAFE TEMPORARY ELECTRICAL POWER AND LIGHTING THROUGHOUT THE CONSTRUCTION AND FINISHING OF THE PREMISES. IN ADDITION TO SPECIAL OR UNUSUAL REQUIREMENTS, PROVIDE AT LEAST THESE ITEMS:
A. THREE 20-AMP CIRCUITS FOR CONSTRUCTION POWER TOOLS. PROVIDE GFI TEMPORARY CIRCUITS WITH COVERPLATES TO MEET OSHA REQUIREMENTS.
B. THREE OR MORE LIGHT STRINGS SUSPENDED APPROXIMATELY ONE FOOT BELOW THE HEIGHT OF FINISH CEILING WITH LAMPS PACED NOT MORE THAN TWELVE FEET ON CENTERS. STRINGS SHALL BE RUN THE LENGTH OF THE STORE SPACE PARALLEL TO THE DEMISING WALLS, WITH ONE STRING WITHIN EIGHT FEET OF EACH WALL AND ONE(OR MORE) INTERMEDIATE STRING(S) ARRANGED TO LIMIT THE SPACING BETWEEN ROWS TO SIXTEEN FEET OR LESS.C. FLOOD LIGHTING AND TASK LIGHTING FOR PAINTING AND OTHER FINISH WORK. WHEN PERMANENT ELECTRICALSERVICE IS OPERABLE, DISCONNECT AND REMOVE FROM THE PREMISES THE MATERIALS AND EQUIPMENT USED FORTEMPORARY POWER AND LIGHTING, AND RESTORE MODIFICATIONS AND REPAIR DAMAGE CAUSED BY THE INSTALLATION, USE OR REMOVAL OF TEMPORARY SERVICE PROVISIONS.
PART 2 PRODUCTS
2.01 MATERIAL APPROVAL:
ALL MATERIALS MUST BE NEW AND BEAR UNDERWRITER'S LABORATORIES LABEL. MATERIALS THAT ARE NOT
COVERED BY UL TESTING STANDARDS SHALL BE TESTED AND APPROVED BY AN INDEPENDENT TESTING LABORATORY OR A GOVERNMENTAL AGENCY. MATERIAL NOT IN ACCORDANCE WITH THESE SPECIFICATIONS MAY BEREJECTED EITHER BEFORE OR AFTER INSTALLATION.
2.02 CONDUITS AND OTHER RACEWAYS:
A. RIGID STEEL: HOT-DIPPED GALVANIZED.
B. INTERMEDIATE METAL CONDUIT (IMC): HOT-DIPPED GALVANIZED.
C. ELECTRICAL METALLIC TUBING (EMT): ELECTRO-GALVANIZED.
D. WIREWAY: CODE GAUGE STEEL, WITH KNOCKOUTS AND HINGED COVER, CORROSION RESISTANT GRAY BAKEDENAMEL FINISH.E. PROVIDE FITTINGS AND ACCESSORIES APPROVED FOR THE PURPOSE EQUAL IN ALL RESPECTS TO THE CONDUIT OR RACEWAY. EMT CONNECTORS AND COUPLINGS SHALL BE STEEL SETSCREW TYPE INDOORS AND STEELCOMPRESSION TYPE IN WET LOCATIONS AND OUTDOORS.
2.03 WIRES AND CABLES:A. FOR POWER AND LIGHTING SYSTEM 600V OR LESS: 1. CONDUCTOR: MINIMUM SIZE #12 AWG. A. #12 AND #10 AWG SOLID COPPER. B. #8 AWG AND LARGER SHALL BE STRANDED COPPER. 2. INSULATION TYPE: A. #12 TO #1 AWG: THWN FOR WET OR UNDERGROUND AND THHN FOR DRY LOCATIONS. B. #1/0 THROUGH #4/0 AWG: XHHW (55 MILS). C. #250 MCM AND LARGER: XHHW (65 MILS). D. GROUNDING WIRE: TW.
B. FOR SIGNAL AND COMMUNICATIONS CIRCUIT: SPECIAL CABLES SHALL BE AS SPECIFIED ON DRAWINGS.
C. ACCEPTABLE PRODUCTS: GENERAL ELECTRIC, ANACONDA, OKONITE, PARANITE OR TRIANGLE PRODUCTSCONFORMING OR EXCEEDING APPLICABLE IPCEA STANDARDS.
2.04 OUTLET BOXES, JUNCTION AND PULL BOXES:
A. OUTLET BOXES: 4" SQUARE X 1-1/2" DEEP (OR LARGER) GALVANIZED SHEET STEEL KO-TYPE WITH PLASTER RINGAND COVER FOR GENERAL INTERIOR USE AND CAST METAL TYPE FS OR FD WITH MATCHING SCREW COVERS FOR EXTERIOR AND EXPOSED INTERIOR LOCATIONS (GASKETED IN DAMP OR WET LOCATIONS).B. JUNCTION BOXES SHALL BE SAME AS OUTLET BOXES UP TO 42 CU. IN. AND CODE GAUGE STEEL IN LARGER SIZES
WITH SURFACE OR FLUSH-TYPE SCREW-MOUNTED TRIM COVERS, BOTH BOXES AND COVERS INHIBITOR-PRIMED AND PAINTED INSIDE OUT.
C. PULL BOXES SHALL BE SAME AS JUNCTION BOXES UNLESS INDICATED OTHERWISE ON THE DRAWINGS, WITHCOVERS.
D. TELEPHONE OUTLET BOXES SHALL BE THE TYPE AND SIZE REQUIRED BY THE SERVING TELEPHONE COMPANYBUT NOT SMALLER THAN 4-11/16" SQUARE X 2-1/8" DEEP WITH SINGLE-GANG RING AND SIERRA #S-754N SPLIT PLATEBUSHING.
2.05 WIRING DEVICES AND PLATES:
UNLESS OTHERWISE INDICATED, ALL WIRING DEVICES AND COVER PLATES SHALL BE FURNISHED AND INSTALLED IN COLOR TO MATCH FINISH SURFACE WHERE IT IS LOCATED ON, I.E., DARK BROWN, BEIGE, WHITE OR STAINLESS STEEL.
2.06 CONDUIT HANGERS:
FOR INDIVIDUAL CONDUIT RUNS NOT DIRECTLY FASTENED TO THE STRUCTURE, USE ROD HANGERS MANUFACTURED BY CADDY, UNISTRUT OR POWERSTRUT. FOR MULTIPLE CONDUIT RUNS, USE UNISTRUT OR POWERSTRUT TRAPEZE TYPECONDUIT SUPPORT DESIGNED FOR MAXIMUM DEFLECTION NOT GREATER THAN 1/8". ROD HANGERS SHALL BE 3/8" MINIMUM DIAMETER.
2.07 WIRE CONNECTORS:
FOR WIRE SIZES #8 AWG AND SMALLER: INSULATED PRESSURE TYPE (WITH LIVE SPRING) RATED 105 DEGREES C, 600V,FOR BUILDING WIRING AND 1000V IN SIGNS OR FIXTURES. SCOTCHLOK OR IDEAL. FOR WIRE SIZE #6 AWG AND LARGER: T & B OR EQUIVALENT COMPRESSION TYPE WITH 3M #33+ OR PLYMOUTH "SLIPKNOT GREY" TAPE INSULATION.
2.08 LIGHTING CONTROL PANEL: AUTOMATIC TIMER CONTROL SHALL MEET CALIFORNIA ENERGY COMMISSION TITLE 24 REQUIREMENTS.2.09 PANELBOARDS:
A. CONSTRUCTION: CABINETS SHALL BE OF CODE GAUGE, GALVANIZED STEEL, SURFACE OR FLUSH MOUNTED AS INDICATED. DOORS SHALL BE OF COLD-ROLLED STEEL WITH CONCEALED HINGES AND FLUSH CATCH AND LOCK. ALLPANELS SHALL BE KEYED ALIKE. PANELS LOCATED ADJACENT TO EACH OTHER HALL HAVE IDENTICALLY SIZEDENCLOSURE AND MINIMUM PANEL WIDTH SHALL BE 20". FINISH EXPOSED PART WITH ONE COAT OF PRIMER AND ONE COAT OF LIGHT GREY ENAMEL SUITABLE FOR OVERPAINTING IN FIELD IF DESIRED.
B. BUS BARS: BUS BARS SHALL BE COPPER. PROVIDE GROUND BLOCK WITH FULL COMPLEMENT OF TERMINALS INADDITION TO INSULATED NEUTRAL BUS. FUTURE BREAKER SPACES SHALL HAVE COMPLETE PROVISION INCLUDING BUSSES AND CONNECTING HARDWARE.
C. MANUFACTURERS: PANELBOARDS SHALL BE GENERAL ELECTRIC TYPE "AQ" OR TYPE "AE" OR EQUIVALENT PRODUCTS OF WESTINGHOUSE, SQUARE-D OR SIEMENS-ITE.
D. CIRCUIT BREAKERS: SHALL BE QUICK-MAKE, QUICK-BREAK, MOLDED CASE TYPE: 1. 120/208 VOLT, 3 PHASE, 4 WIRE PANELS: SHALL BE GENERAL ELECTRIC TYPE "Q" LINE, BOLT-ON TYPE, WITH MINIMUM SYMMETRICAL INTERRUPTING CAPACITY AS SHOWN. 2. PROVIDE MULTI-POLE UNITS WITH COMMON TRIP ELEMENT. E. IDENTIFICATION: PROVIDE SCREWED-ON (NO ADHESIVES) BAKELITE OR PHOTO-ETCHED METALLIC NAMEPLATE IDENTIFICATION ON OUTSIDE OF EACH PANEL SHOWING PANEL DESIGNATION, VOLTAGE AND PHASE IN MINIMUM 1/8" HIGH LETTERS. EACH PANEL SHALL CONTAIN A METAL-FRAMED CIRCUIT DIRECTORY INSIDE COVER, WITH PLASTIC PROTECTOR. F. COMPLETE SHOP DRAWINGS ARE REQUIRED. SEE ARTICLE 1.08. G. PROVIDE NARROW 14" WIDE PANELBOARD WHERE REQUIRED ON PLAN.
PART 3 EXECUTION
3.01 GENERAL:
A. ELECTRIC SYSTEM LAYOUTS INDICATED ON THE DRAWINGS ARE GENERALLY D DIAGRAMMATIC AND SHALL BE FOLLOWED AS CLOSELY AS ACTUAL CONSTRUCTION AND WORKOF OTHER TRADES WILL PERMIT. GOVERN EXACT ROUTING OF CABLE AND WIRING AND THELOCATIONS OF OUTLETS BY THE STRUCTURE AND EQUIPMENT SERVED. TAKE ALL DIMENSIONSFROM ARCHITECTURAL DRAWINGS.B. CONSULT ALL OTHER DRAWINGS, VERIFY SCALES AND REPORT ANY DIMENSIONALDISCREPANCIES OR OTHER CONFLICTS WITH OWNER BEFORE SUBMITTING BID.C. ALL HOME RUNS TO PANELBOARDS ARE INDICATED AS STARTING FROM THE OUTLETNEAREST THE PANEL AND CONTINUING IN THE GENERAL DIRECTION OF THAT PANEL.CONTINUE SUCH CIRCUITS TO THE PANEL AS THOUGH THE ROUTES WERE COMPLETELY INDICATED. TERMINATE HOMERUNS OF SIGNAL, ALARM, AND COMMUNICATION SYSTEMS IN A SIMILAR MANNER.D. AVOID CUTTING AND BORING HOLES THROUGH STRUCTURE OR STRUCTURAL MEMBERS WHEREVER POSSIBLE. OBTAIN PRIOR APPROVAL OF SFIA AND CONFORM TO ALL STRUCTURAL REQUIREMENTS WHEN CUTTING OR BORING THE STRUCTURE IS NECESSARY AND PERMITTED.E. FURNISH AND INSTALL ALL NECESSARY HARDWARE, HANGERS, BLOCKING, BRACKETS,BRACING, RUNNERS, ETC. REQUIRED FOR EQUIPMENT SPECIFIED UNDER THIS SECTION.F. PROVIDE NECESSARY BACKING REQUIRED TO INSURE RIGID MOUNTING OF OUTLET BOXES.
3.02 WIRING METHODS:A. ALL WIRING REGARDLESS OF VOLTAGE MUST BE IN METAL CONDUIT OR RACEWAY.
CONDUIT SHALL BE RIGID STEEL, IMC OR EMT AS FOLLOWS:
1. ABOVE GROUND: USE RIGID STEEL, IMC OR EMT. A. WET LOCATIONS: RIGID STEEL OR IMC ONLY. B. LOCATIONS SUBJECT TO MECHANICAL INJURY: RIGID STEEL OR IMC ONLY. C. DRY LOCATIONS AND NOT SUBJECT TO MECHANICAL INJURY: EMT, IMC OR RIGID STEEL CONDUIT. 2. UNDERGROUND/UNDERFLOOR: USE RIGID STEEL. 3. WHERE ALLOWED TO BE EXPOSED. SHALL BE RIGID AT 60" OR LESS A.F.F.
B. USE FLEXIBLE CONDUITS IN THE FOLLOWING APPLICATIONS:
1. FINAL CONNECTIONS TO MOTOR. 2. FINAL CONNECTIONS INTO AND OUT OF THE TRANSFORMER. 3. FINAL CONNECTIONS TO VIBRATING EQUIPMENT.
C. FLEXIBLE METALLIC CONDUIT MUST BE THE SAME SIZE AS THE RIGID CONDUIT TO WHICH IT IS CONNECTED.
D. THE CONNECTION TO OUTDOOR EQUIPMENT MUST BE WEATHERPROOF, I.E. LIQUIDTIGHTOR SEALTIGHT.E. MINIMUM SIZE FOR ALL LOCATIONS SHALL BE 3/4".
3.03 INSTALLATION OF CONDUITS:
A. GENERAL: 1. RUN ALL CONDUIT CONCEALED UNLESS OTHERWISE NOTED OR SHOWN. 2. RUN ALL CONDUIT PARALLEL TO OR AT RIGHT ANGLES TO CENTER LINES OF COLUMNSAND BEAMS. 3. CONDUITS ABOVE CEILINGS SHALL NOT OBSTRUCT REMOVAL OF CEILING TILES, LIGHTING FIXTURES, AIR DIFFUSERS, ETC. 4. CONDUITS SHALL NOT CROSS ANY DUCT SHAFT OR AREA DESIGNATED AS FUTURE DUCT SHAFT HORIZONTALLY. CONDUIT RISERS WHEN ALLOWED IN DUCT SHAFT MUST BE COORDINATED WITH MECHANICAL WORK TO AVOID ANY CONFLICT. 5. X-RAY ALL PROPOSED CONDUIT PENETRATIONS THROUGH CONCRETE SLAB PRIOR TO BEGINNING OF WORK. 6. BENDS IN ANY ONE RUN SHALL NOT EXCEED A TOTAL OF 270°.
B. CONDUIT SUPPORTS:
1. SUPPORT CONDUITS WITH UNDERWRITER'S LABORATORIES LISTED STEEL CONDUIT SUPPORTS AT INTERVALS REQUIRED BY THE NATIONAL ELECTRIC CODE. WIRES OR SHEET METAL STRIPS ARE NOT ACCEPTABLE FOR CONDUIT SUPPORT. USE CONDUIT HANGERS FOR ALL CONDUITS NOT DIRECTLY FASTENED TO STRUCTURE AND FOR ALL MULTIPLE CONDUIT RUNS. DO NOT ATTACH ANY CONDUIT TO MECHANICAL DUCTS OR PIPES. 2. AVOID ATTACHING CONDUIT TO FAN PLENUMS. WHEN IT IS NECESSARY TO SUPPORT CONDUIT FROM FAN PLENUM, PROVIDE A LENGTH OF FLEXIBLE CONDUIT BETWEEN PORTION ATTACHED FAN PLENUM AND PORTION ATTACHED TO THE BUILDING TO MINIMIZE TRANSMISSION OF VIBRATION TO THE BUILDING STRUCTURE.
C. CONDUIT PENETRATION:
1. PENETRATING FIRE RATED FLOOR: SEAL PENETRATION WITH FIRE RETARDANT SEALANT SPECIFIED HEREIN, U.L. NO. CAJ 5048, F RATING-2 HR, T RATING-2 HR. 2. PENETRATING ROOF OR EXTERIOR WALL: AVOID PENETRATING ROOF OR EXTERIOR WALL WHERE POSSIBLE. WHERE PENETRATIONS ARE NECESSARY, BUILDING WEATHERPROOF INTEGRITY MUST BE PRESERVED. 3. PENETRATING SOUND INSULATED OR AIR PLENUM WALL: INSTALL CONDUIT IN CONDUIT SLEEVE AND SEAL PENETRATION AS DETAILED ON THE DRAWINGS. 4. PENETRATING NON-FIRE RATED DRY WALL: CONDUIT SLEEVES ARE NOT REQUIRED. PENETRATIONS MUST BE SEALED WITH PLASTER PRIOR TO PAINTING. PENETRATIONS MADE AFTER WALL FINISH IS APPLIED MUST BE AS SMALL AS POSSIBLE AND PROVIDED WITH ESCUTCHEONS, ONE ON EACH SIDE OF WALL. 5. PENETRATING SUSPENDED CEILING: CUT HOLE AS SMALL AS POSSIBLE TO PERMIT CONDUIT PENETRATION. PROVIDE ESCUTCHEON FOR EACH CONDUIT BELOW CEILING.
3.04 INSTALLATION OF WIRES:
A. INSTALL WIRES AFTER WORK WHICH MIGHT DAMAGE THE WIRE HAS BEEN COMPLETED.
B. INSTALL ALL WIRE CONTINUOUS FROM OUTLET TO OUTLET OR TERMINAL TO TERMINAL. SPLICES IN CABLES WHEN REQUIRED SHALL BE MADE IN HANDHOLES, PULL BOXES OR JUNCTION BOXES.
MAKE BRANCH CIRCUIT SPLICES IN OUTLET BOXES WITH 8" OF CORRECTLY COLOR-CODED TAILSLEFT IN THE BOX.C. SPLICES IN WIRES AND CABLES SHALL BE MADE UTILIZING MATERIALS AND METHODSDESCRIBED HEREIN BEFORE.D. MAKE ALL GROUND, NEUTRAL AND LINE CONNECTIONS TO RECEPTACLE AND WIRING DEVICE TERMINALS AS RECOMMENDED BY MANUFACTURER. PROVIDE GROUND JUMPER FROM OUTLET
BOX TO GROUND TERMINAL OF DEVICES WHEN THE DEVICE IS NOT APPROVED FOR GROUNDING THROUGH THE MOUNTING SCREWS.
E. PROVIDE BRADY WIRE MARKERS WHERE NUMBER OF CONDUCTORS IN A BOX EXCEEDS FOUR.F. MEGGER AND RECORD INSULATION RESISTANCE OF ALL 600 VOLT INSULATED CONDUCTORSSIZE #4/0 AND LARGER USING 500 VOLT MEGGER FOR ONE MINUTE. MAKE TESTS WITH CIRCUITS ISOLATED FROM SOURCE AND LOAD.
PART 1 GENERAL
1.01 SCOPE OF WORK:FURNISH AND INSTALL ALL MATERIALS AND EQUIPMENT AND PROVIDE ALL LABOR, TOOLS,
TRANSPORTATION, SUPERINTENDENCE AND SERVICES REQUIRED AND NECESSARY TO COMPLETE THE WORK SHOWN ON THE DRAWINGS AND/OR SPECIFIED HEREIN. ALSO INCLUDE
ALL OTHER WORK AND MISCELLANEOUS ITEMS, NOT SPECIFICALLY MENTIONED, BUT
REASONABLY INFERRED FOR A COMPLETE INSTALLATION INCLUDING ALL ACCESSORIES AND APPURTENANCES REQUIRED FOR TESTING THE SYSTEM. IT IS THE INTENT OF THE DRAWINGSAND SPECIFICATIONS THAT ALL SYSTEMS BE COMPLETE, AND READY FOR OPERATION.
1.02 REGULATORY REQUIREMENTS:CODE COMPLIANCE IS MANDATORY. NOTHING IN THESE DRAWINGS AND SPECIFICATIONPERMITS WORK NOT CONFORMING TO THESE CODES. WHERE WORK IS SHOWN TO EXCEEDMINIMUM CODE REQUIREMENTS, COMPLY WITH DRAWINGS AND SPECIFICATIONS. ALL WORK
AND MATERIALS SHALL COMPLY WITH THE LATEST RULES, CODES AND REGULATIONS, INCLUDING, BUT NOT LIMITED TO THE FOLLOWING:
A. 2020 NATIONAL ELECTRICAL CODE - NEC
B. TITLE 24 CALIFORNIA CODE OF REGULATIONS - CBC AND THE ADAC. 2022 CALIFORNIA ELECTRICAL CODE.D. ALL LOCAL ORDINANCES HAVING JURISDICTION.
1.03 LICENSE, FEES AND PERMITS:ELECTRICAL CONTRACTOR SHALL PAY FOR ALL LICENSES, PERMITS AND INSPECTION FEESREQUIRED BY THE AUTHORITY HAVING JURISDICTION AND SHALL ARRANGE FOR ALL REQUIRED INSPECTIONS.
1.04 SAFETY AND INDEMNITY:
THE CONTRACTOR SHALL BE SOLELY AND COMPLETELY RESPONSIBLE FOR CONDITIONS OFTHE JOB SITE, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY DURING PERFORMANCE OF WORK. THIS REQUIREMENT WILL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS. NO ACT, SERVICE, DRAWING REVIEW OR CONSTRUCTION REVIEW BY THE
OWNER, THE ENGINEERS OR THEIR CONSULTANTS, IS INTENDED TO INCLUDE REVIEW OF THE
ADEQUACY OF THE CONTRACTOR'S SAFETY MEASURES, IN, ON, OR NEAR THE CONSTRUCTION SITE.
1.05 DRAWINGS AND SPECIFICATIONS:
ALL DRAWINGS AND ALL DIVISIONS OF THESE SPECIFICATIONS SHALL BE CONSIDERED AS AWHOLE AND WORK OF THIS DIVISION SHOWN ANYWHERE THEREIN SHALL BE FURNISHED UNDER THIS DIVISION. DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT OF EQUIPMENT AND WIRING. MOST DIRECT ROUTING OF CONDUITS ANDWIRING IS NOT ASSURED. EXACT REQUIREMENTS SHALL BE GOVERNED BY CONDITIONS OFTHE JOB. CONSULT ALL OTHER DRAWINGS IN PREPARATION OF THE BID. EXTRA LENGTHS OFWIRING OR ADDITION OF PULL OR JUNCTION BOXES, ETC., NECESSITATE BY SUCH CONDITIONS SHALL BE INCLUDED IN THE BID.
1.06 CONDITIONS AT SITE:
VISIT SITE OF THE WORK, COMPARE IT WITH THE DRAWINGS AND SPECIFICATIONS AS TO THE
CONDITIONS UNDER WHICH WORK IS TO BE PERFORMED, ASCERTAIN AND CHECK ALL CONDITIONS AND ELEVATIONS AND TAKE ALL MEASUREMENTS WHICH MAY AFFECT THE WORK. NOALLOWANCE SHALL SUBSEQUENTLY BE MADE FOR ANY EXTRA EXPENSE OR CLAIMS DUE TO FAILURE OR NEGLECT UNDER THIS REQUIREMENT TO MAKE SUCH EXAMINATION, INCLUDINGEXAMINATION OF RESTRICTED WORKING CONDITIONS OR SUCH OTHER DIFFICULTIES VISUALLYOBSERVED DURING SITE VISIT. CONTRACTOR IS RESPONSIBLE FOR BECOMING COMPLETELYFAMILIAR WITH THE ARCHITECTURAL AND STRUCTURAL CONDITIONS AND LIMITATIONS WHICH WILLEXIST IN THE BUILDING AND TO PROVIDE ALL LABOR, TOOLS AND MATERIALS REQUIRED TOPRODUCE A COMPLETELY CONCEALED INSTALLATION AS INDICATED ON THE PLANS,SPECIFICATIONS, AND REQUIRED BY THE CODE.
1.07 WORKMANSHIP AND CONTRACTOR'S QUALIFICATIONS:
ONLY QUALITY WORKMANSHIP WILL BE ACCEPTED. HAPHAZARD OR POOR INSTALLATION WILLBE CAUSE FOR REJECTION OF WORK.
1.08 SHOP DRAWINGS AND MATERIALS LISTS:SUBMIT TO OWNER IN A SINGLE PACKAGE SIX (6) COPIES OF COMPLETE SHOP DRAWINGS ANDMATERIALS LIST, AS NOTED BELOW, FOR REVIEW WITHIN FIFTEEN (15) DAYS AFTER AWARD OFCONTRACT. SUBMITTALS REQUIRED AS FOLLOWS:
A. WIRING DEVICES: SWITCHES, RECEPTACLES, DEVICE PLATES.
B. MAIN FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER.C. DISCONNECT SWITCHES.D. LIGHTING FIXTURES, LAMPS AND LIGHTING CONTROL EQUIPMENT.
1.09 SUBSTITUTIONS:ONE OR MORE MAKES OF MATERIALS OR METHODS MAY HAVE BEEN SPECIFIED TO ESTABLISH
THE STANDARD OF QUALITY, WORKMANSHIP, FINISH AND DESIGN REQUIRED, BUT OTHER MATERIALS OR METHODS EQUAL IN QUALITY, WORKMANSHIP, FINISH, DESIGN, ANDGUARANTEED PERFORMANCE, WILL BE ACCEPTED. HOWEVER, ALL CHANGES ANDSUBSTITUTIONS SHALL BE REQUESTED IN LETTER FORM AND SHALL BE ACCOMPANIED WITH ASTATEMENT OF THE AMOUNT OF MONEY TO BE RETURNED TO THE CONTRACT IF THESUBSTITUTION IS PERMITTED.NO WORK INVOLVING MATERIALS SUBMITTED FOR SUBSTITUTION SHALL PROCEED UNTIL WRITTEN ACCEPTANCE IS RECEIVED FROM THE OWNER. THE OWNER IS THE SOLE JUDGE OFACCEPTABILITY OF PREFERRED SUBSTITUTIONS. IF A SUBSTITUTION ITEM IS PERMITTED, ANDANY RE-DESIGN EFFORT IS THEREBY NECESSITATED, THE REQUIRED REDESIGN SHALL BE ATTHE CONTRACTOR'S EXPENSE.
1.10 COORDINATION:COORDINATE WORK WITH OTHER TRADES TO AVOID CONFLICT AND TO PROVIDE CORRECTROUGH-IN AND CONNECTION FOR EQUIPMENT FURNISHED UNDER OTHER TRADES THATREQUIRE ELECTRICAL CONNECTIONS. INFORM CONTRACTORS OF OTHER TRADES OF THEREQUIRED ACCESS TO AND CLEARANCES AROUND ELECTRICAL EQUIPMENT TO MAINTAINSERVICE ABILITY AND CODE COMPLIANCE. VERIFY EQUIPMENT DIMENSIONS ANDREQUIREMENTS WITH PROVISIONS SPECIFIED UNDER THIS SECTION. CHECK ACTUAL JOBCONDITIONS BEFORE FABRICATING WORK. REPORT NECESSARY CHANGES IN TIME TOPREVENT NEEDLESS WORK. CHANGES OR ADDITIONS, SUBJECT TO ADDITIONALCOMPENSATION, WHICH ARE MADE WITHOUT WRITTEN AUTHORIZATION AND AN AGREEDPRICE, SHALL BE AT THE CONTRACTOR'S RISK AND EXPENSE.
1.11 CUTTING AND PATCHING:
ALL CUTTING AND PATCHING REQUIRED FOR WORK OF THIS DIVISION IS INCLUDED HEREIN.
COORDINATION WITH GENERAL CONTRACTOR AND OTHER TRADES IS IMPERATIVE.CONTRACTOR SHALL BEAR THE RESPONSIBILITY FOR AND THE ADDED EXPENSE OF ADJUSTING FOR IMPROPER HOLES, SUPPORTS, ETC.
1.12 ACCEPTANCE DEMONSTRATION:
UPON COMPLETION OF THE WORK, AT A TIME TO BE DESIGNATED BY THE OWNER, THECONTRACTOR SHALL DEMONSTRATE FOR THE OWNER THE OPERATION OF THE ELECTRICAL
INSTALLATION, INCLUDING ANY AND ALL SPECIAL ITEMS INSTALLED BY HIM OR INSTALLED UNDER HIS SUPERVISION. PROPERLY SET AUTOMATIC TIME SWITCHES TO PERFORMSWITCHING OPERATIONS IN ACCORDANCE WITH SCHEDULES PROVIDED BY THE OWNER'SREPRESENTATIVE, AND DEMONSTRATE (USING THE MANUFACTURER'S OPERATING INSTRUCTIONS) HOW TO OVERRIDE AND/OR TEST TIME SWITCHES PROGRAMMING.
1.13 RECORD DRAWINGS, EQUIPMENT DATA:MAINTAIN ONE SET OF CLEAN WORKING DRAWINGS AT THE JOB SITE AND ENTER DAILY SUCH"AS-BUILT" INFORMATION AS FEEDER AND SERVICE ROUTES, PULL BOX LOCATIONS ANDCHANGES IN LAYOUT OR ARRANGEMENT WHICH OCCUR DURING CONSTRUCTION. DELIVERCOMPLETED DRAWINGS TO THE OWNER. DELIVER TO THE OWNER'S REPRESENTATIVE THREECOPIES OF DATA SHEETS OR OTHER CURRENT MANUFACTURERS' PUBLICATIONS FOR EACH
ITEM OF ELECTRICAL EQUIPMENT FURNISHED FOR THE PROJECT INCLUDING AT LEAST THESE DATA:
A. TECHNICAL DESCRIPTION AND REPLACEABLE PARTS LIST.
B. PHYSICAL DESCRIPTION AND INSTALLATION INSTRUCTIONS.C. USER'S MANUAL AND OPERATING INSTRUCTIONS.D. MANUFACTURER'S WARRANTY.
PRINT DATE:
DRAWN BY:
JOB NO.2340 GARDEN ROAD, SUITE 100
MONTEREY, CALIFORNIA 93940PHONE: 831.649.4642
FAX: 831.649.3530
WWW.WRDARCH.COM
SHEET NAME:
SHEET NO.:FILE NAME.:
SET ISSUED:CHECKED BY:
THE USE OF THE PLANS AND SPECIFICATIONS ISRESTRICTED TO THE ORIGINAL SITE FOR WHICHTHEY WERE PREPARED, AND PUBLICATIONTHEREOF IS EXPRESSLY LIMITED TO SUCH USE.REUSE, REPRODUCTION OR PUBLICATION BYANY METHOD IN WHOLE OR IN PART ISPROHIBITED. TITLE TO THE PLANS ANDSPECIFICATIONS REMAINS WITH THE ARCHITECT,AND VISUAL CONTACT WITH THEMCONSTITUTES PRIMA FACIE EVIDENCE OF THEACCEPTANCE OF THESE RESTRICTIONS.
PLOT DATE: 6.5.2024
24040
CENTRAL COAST COMMUNITY ENERGY
1026 PALM STREET - SAN LUIS OBISPO TI
CENTRAL COAST COMMUNITY ENERGY (3CE)
1026 PALM STREET
SAN LUIS OBISPO, CA 93401 APN: 002-323-031
400 N. McCarthy Blvd. Ste. 250
Copyright c 2024
[email protected]
fx: (408) 522-5260
ph: (408) 522-5255
Milpitas, CA 95035
ENGINEERING
NOT FOR
CONSTRUCTION
E0.3
SINGLE LINE DIAGRAM
& PANEL SCHEDULES
SINGLE LINE DIAGRAM - EXISTING
PANEL SCHEDULES
FEEDER SCHEDULE
FEEDER CONDUITS (COPPER) CONDUITS (ALUMINUM) CONDUCTORS PER SET (Cu) CONDUCTORS PER SET (Al)
TAG MET SETS RNC MET SETS RNC PHASE/ NEUTRAL GND PHASE/ NEUTRAL GROUND
2.50" 2 2.50" 3.00" 2 3.00" (4) #3/0 #3 (4) 250KCMIL #12.00" 2 2.00" 2.50" 2 2.50" (3) #3/0 #3 (3) 250KCMIL #13.50" 1 3.50" 2.50" 2 2.50" (4) 500KCMIL #3 (4) 4/0 #23.50" 1 3.00" 2.50" 2 2.00" (3) 500KCMIL #3 (3) 4/0 #23.50" 1 3.50" 3.50" 1 3.50" (4) 350KCMIL #4 (4) 500KCMIL #23.00" 1 3.00" 3.50" 1 3.00" (3) 350KCMIL #4 (3) 500KCMIL #22.50" 1 2.50" 3.50" 1 3.50" (4) #4/0 #4 (4) 350KCMIL #22.50" 1 2.00" 3.00" 1 3.00" (3) #4/0 #4 (3) 350KCMIL #22.50" 1 2.50" 3.00" 1 3.00" (4) #4/0 #4 (4) 300KCMIL #22.50" 1 2.00" 3.00" 1 2.50" (3) #4/0 #4 (3) 300KCMIL #22.50" 1 2.50" 3.00" 1 3.00" (4) #3/0 #6 (4) 250KCMIL #42.00" 1 2.00" 2.50" 1 2.50" (3) #3/0 #6 (3) 250KCMIL #42.50" 1 2.50" 3.00" 1 2.50" (4) #3/0 #6 (4) #4/0 #42.00" 1 2.00" 2.50" 1 2.00" (3) #3/0 #6 (3) #4/0 #42.50" 1 2.00" 2.50" 1 2.50" (4) #1/0 #6 (4) #3/0 #42.00" 1 1.50" 2.00" 1 2.00" (3) #1/0 #6 (3) #3/0 #42.00" 1 1.50" 2.00" 1 2.50" (4) #1 #6 (4) #2/0 #4
1.50" 1 1.50" 2.00" 1 2.00" (3) #1 #6 (3) #2/0 #41.50" 1 1.25" 2.00" 1 1.50" (4) #2 #8 (4) #1 #61.25" 1 1.25" 1.50" 1 1.50" (3) #2 #8 (3) #1 #61.50" 1 1.25" 1.50" 1 1.25" (4) #2 #8 (4) #2 #61.25" 1 1.25" 1.25" 1 1.25" (3) #2 #8 (3) #2 #61.25" 1 1.25" 1.25" 1 1.25" (4) #4 #8 (4) #2 #61.25" 1 1.00" 1.25" 1 1.25" (3) #4 #8 (3) #2 #61.25" 1 1.25" 1.25" 1 1.25" (4) #4 #8 (4) #3 #61.25" 1 1.00" 1.25" 1 1.00" (3) #4 #8 (3) #3 #61.00" 1 1.00" 1.25" 1 1.25" (4) #6 #10 (4) #4 #81.00" 1 1.00" 1.25" 1 1.00" (3) #6 #10 (3) #4 #81.00" 1 1.00" 1.00" 1 1.00" (4) #6 #10 (4) #6 #10
0.75" 1 1.00" 0.75" 1 1.00" (3) #6 #10 (3) #6 #100.75" 1 1.00" 0.75" 1 1.00" (4) #8 #10 (4) #8 #100.75" 1 0.75" 0.75" 1 0.75" (3) #8 #10 (3) #8 #100.75" 1 0.75" 0.75" 1 0.75" (4) #10 #10 (4) #10 #100.75" 1 0.75" 0.75" 1 0.75" (3) #10 #10 (3) #10 #100.75" 1 0.75" 0.75" 1 0.75" (4) #12 #12 (4) #12 #120.75" 1 1.00" 0.75" 1 1.00" (3) #12 #12 (3) #12 #12 NOTES:
1. CONDUCTORS AND CONDUITS SHOWN IN THIS SCHEDULE ARE BASED ON COPPER & ALUMINUM CONDUCTORS WITH THHN/THWN INSULATION.
2. THIS SCHEDULE SHALL BE USED ON ALL FEEDERS SERVING LOADS WHERE THE CIRCUIT BREAKER SIZE MATCHES THE AMPACITY OF ITS FEEDER.3. PROVIDE GROUND WIRE NOTED ABOVE IN ALL FEEDERS AND BRANCH CIRCUITS. WHERE MULTIPLE CONDUITS ARE INDICATED PROVIDE NOTED GROUND WIRE IN EACH CONDUIT.4. NOT ALL FEEDERS ARE NECESSARILY USED ON THIS PROJECT.5. NOMINAL AMPACITIES GREATER THAN 100 AMPS ARE FOR 75 DEG..C TERMINALS. 400.4400.3350.4350.3300.4300.3250.4250.3225.4225.3200.4200.3175.4175.3150.4150.3125.4125.3100.4100.3
90.490.380.480.370.470.360.460.350.450.340.440.330.430.320.420.3
GENERAL NOTES
# DESCRIPTION
1 ALL EQUIPMENT IS EXISTING UNLESS SHOWN AS NEW (N). FIELD VERIFY ALL EXISTING CONDITIONS.2 ALL WIRE IS COPPER. REFER TO SPECIFICATION FOR CONDUCTION INSULATION TYPE.3 ONLY U.L. LISTED EQUIPMENT SHALL BE USED.4
RATING OF ALL OVERCURRENT PROTECTION DEVICES, SWITCHES AND MAGNETIC STARTERS
TO BE VERIFIED WITH NAMEPLATE RATING OF ASSOCIATED UNIT AND TO BE REVISED AS REQUIRED.
5 CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS BEFORE ANY WORK OR BID.CONTRACTOR SHALL CONFIRM ACCURACY OF THESE DRAWINGS BEFORE START OF THE PROJECT AND CONTACT ENGINEER AND ARCHITECT IN CASE OF ANY DISCREPANCY.PERFORM ANY NECESSARY REPAIRS AND REPLACEMENTS RELATED TO EXISTING PANELSUNDER THIS SCOPE OF WORK.
6 ALL ELECTRICAL EQUIPMENT SHALL BE FIELD MARKED WARNING QUALIFIED PERSONAL OF THE POTENTIAL ARC FLASH HAZARDS AND THE APPROPRIATE PPE REQUIRED, PER 02 NEC ART. 110-16 AND NFPA-70E-200.
SINGLE LINE DIAGRAM GENERAL NOTE
# NOTES
1 ALL ELEC. EQUIPMENT AND WIRING ARE EXISTING UNLESS OTHERWISE INDICATED AS NEW (N).2 VERIFY EXISTING MAIN DISTRIBUTION PANELS TO BE SUITABLE REGARDING CONDITION AND DESIGN FOR ADDITIONAL NEW CONNECTED LOADS TO BE ADDED TO THE EXISTING POWER DISTRIBUTION SYSTEM INCLUDING PANEL BOARDS, BREAKERS SET POINTS, EQUIPMENT BONDING, GROUNDING ELECTRODE CONDUCTOR, NEUTRAL, EQUIPMENT GROUNDING CONDUCTORS PROTECTION, SAFETY, AND/OR EQUIPMENT MAINTENANCE ACCESS.
SHEET NOTES
# DESCRIPTION
EXISTING MAIN SERVICE SWITCH. RATING AS SHOWN.
EXISTING UTILITY METER TO REMAIN.
POINT OF INTERCEPTION TO BE VERIFIED IN FIELD. PROVIDE CODE SIZED PULLBOX ASREQUIRED. INTERCEPT AND EXTEND NEW FEEDER TO NEW PANEL LOCATION . SEE PLAN INE3.1.EXISTING ELECTRICAL PANEL TO BE REMOVED AND RELOCATED TO NEW LOCATION. 12345
1 2
3 5
M
EXISTING TO REMAINNEW WORK
(E)
LEGEND
NEW FEEDER TO BE INSTALLED. RATING AS SHOWN.
678
EXISTING MAIN CIRCUIT BREAKER TO REMAIN. RATING AS SHOWN.NEW BREAKER TO BE INSTALLED. RATING AS SHOWN.PROVIDE ARC WARNING ON NEW PANELBOARDS. LABEL SHALL BE FIELD MARKED TO WARN OFF POTENTIAL ARC-FLASG HAZARDS, PER CFC 604.1 AND NATIONAL ELECTRICALCODE (NFPA 70-110.16). (N)
# DESCRIPTION
1 ALL NEW CIRCUIT BREAKERS INSTALLED IN EXISTING PANEL "A" AND NEW PANEL "B" SHALL MATCH THE HIGHEST EXISTING AIC RATED CIRCUIT BREAKER WITHIN THAT BOARD.
GENERAL NOTES
2 3
M
2 3
M
T
(E) TRANSFORMER
75KVA, 240-208Y/120V,
3Ø, 60HZ
4 225.4
7 (RELOCATED)
1 2 (E) PNL 3
PRINT DATE:DRAWN BY:
JOB NO.2340 GARDEN ROAD, SUITE 100
MONTEREY, CALIFORNIA 93940PHONE: 831.649.4642
FAX: 831.649.3530
WWW.WRDARCH.COM
SHEET NAME:
SHEET NO.:FILE NAME.:
SET ISSUED:CHECKED BY:
THE USE OF THE PLANS AND SPECIFICATIONS ISRESTRICTED TO THE ORIGINAL SITE FOR WHICHTHEY WERE PREPARED, AND PUBLICATIONTHEREOF IS EXPRESSLY LIMITED TO SUCH USE.REUSE, REPRODUCTION OR PUBLICATION BYANY METHOD IN WHOLE OR IN PART ISPROHIBITED. TITLE TO THE PLANS ANDSPECIFICATIONS REMAINS WITH THE ARCHITECT,AND VISUAL CONTACT WITH THEMCONSTITUTES PRIMA FACIE EVIDENCE OF THEACCEPTANCE OF THESE RESTRICTIONS.
PLOT DATE: 6.5.2024
24040
CENTRAL COAST COMMUNITY ENERGY
1026 PALM STREET - SAN LUIS OBISPO TI
CENTRAL COAST COMMUNITY ENERGY (3CE)
1026 PALM STREET
SAN LUIS OBISPO, CA 93401 APN: 002-323-031
400 N. McCarthy Blvd. Ste. 250
Copyright c 2024
[email protected]
fx: (408) 522-5260
ph: (408) 522-5255
Milpitas, CA 95035
ENGINEERING
NOT FOR
CONSTRUCTION
E1.1
ELECTRICAL
EXISTING/DEMO PLAN
GENERAL NOTES
CODE NOTES
A
UNLESS OTHERWISE INDICATED EXISTING DEVICES AND WIRINGS SHOWN OR NOT SHOWN ON PLAN SHALL REMAIN.EXTEND/REROUTE TO MAINTAIN CONTINUITY OF ANY EXISTINGCIRCUIT THAT ARE TO REMAIN BUT AFFECTED BY THE BUILDING MODIFICATION WORK.
B
CONTRACTOR SHALL INVESTIGATE EXISTING CONDITIONS IMMEDIATELY ADJACENT TO
AND ABOVE PROJECT AREA TO VERIFY EXISTING SYSTEMS AFFECTED BY NEW CONSTRUCTION.
C
TEMPORARILY MOVE ANY (E) SYSTEMS (M, P & E) THAT OBSTRUCT NEW CONSTRUCTION WORK. CONTRACTOR SHALL ENSURE THAT EACH EXISTING UTILITY AND/OR SYSTEM WILL
REMAIN OPERATIONAL AT ALL TIMES SO AS NOT TO AFFECT THE OPERATIONOF ADJOINING AREAS DURING THE COURSE OF CONSTRUCTION ACTIVITIES.
D
FOLLOWING COMPLETION OF THE WORK CONTRACTOR SHALL REINSTALL ALL (E) SYSTEMS TO ORIGINAL LOCATION, CONDITION, AND OPERATION. PATCH AND REPAIRCEILINGS AND WALLSTO MATCH EXISTING CONDITIONS AND SURFACE FINISHES.
E
EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BERESTORED TO OPERATING CONDITION. WHERE CONSTRUCTION CHANGES REQUIRE,OUTLETS AND CONDUIT RUNS SHALL BE RELOCATED. EXTEND CONDUITS AND PULL INNEW WIRING OR INSTALL JUNCTION BOXES AND SPLICE IN NEW WIRING.
F
OUTLETS FROM WHICH FIXTURES, SWITCHES, RECEPTACLES, AND/OR OTHER
ELECTRICAL DEVICES ARE MOVED AND WHICH ARE NOT REPLACED OR REUSED SHALL BE REMOVED. WHERE OUTLETS BOXES, ETC., ARE COMPLETELY REMOVED, THECONTRACTOR SHALL CUT OFF CONDUITS AND REMOVE WIRING.
G
WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT SHALL BE REMOVED IF IT IS EXPOSED, IN A CRAWL SPACE OR IN ACCESSIBLE CEILING . WHERE IT ISIMPOSSIBLE TO REMOVE THE CONDUIT, IT SHALL BE CUT OFF AND CAPPED OR PLUGGED.
SHEET NOTES
# NOTES
REMOVE ALL LIGHT FIXTURES, LIGHT SWITCHES AND LV DEVICES & ASSOCIATED WIRING AFFECTED ON WALLS THAT ARE TO BE REMOVED. SAVE THE CIRCUIT WIRING FOR REUSE.
PROVIDE BOX WITH BLANK COVER AND PAINT TO MATCH WALL FOR CIRCUIT CONTINUITY.IF NEEDED, EXTEND/REROUTE TO MAINTAIN CONTINUITY OF ANY EXISTING CIRCUIT THAT ARE TO REMAIN BUT AFFECTED BY THE BUILDING MODIFICATION WORK.
REMOVE ALL RECEPTACLES AND LV DEVICES & ASSOCIATED WIRING AFFECTED ON WALLS THAT ARE TO BE REMOVED. SAVE THE CIRCUIT WIRING FOR REUSE. PROVIDE BOX WITH BLANK COVER AND PAINT TO MATCH WALL FOR CIRCUIT CONTINUITY. IF NEEDED,EXTEND/REROUTE TO MAINTAIN CONTINUITY OF ANY EXISTING CIRCUIT THAT ARE TOREMAIN BUT AFFECTED BY THE BUILDING MODIFICATION WORK.(E) ELECTRICAL PANEL TO BE REMOVED . INTERCEPT AND EXTEND FEEDER TO NEWPANELBOARD LOCATION , SEE 1/E3.1. 123
1 ELECTRICAL EXISTING/DEMO PLAN SCALE: 1/4"=1'-0"
(E) NOT INSCOPE
(E) NOT INSCOPE
(E) NOT INSCOPE
(N)
PNL 3
D
a
OS
a
OS
D
OS
D
D
OS
D
b
D
D
OS
OSOS
D
OS
b
L1 L1L1 L1 L1 L1
L1
L2
L3
L4
L4
L4
L4
L4
L4
L4
L4
L4L4
L4
L4 L4
L3L3L3L3
B-1a B-1aB-1a B-1a B-1a B-1a
B-1
B-1
B-1B-1 B-1
B-1
B-27b
B-27b
B-27b B-27b
B-27b
B-27b
B-27B-27
B-16B-16B-16B-16B-16
L5
B-8
B-8
PRINT DATE:DRAWN BY:
JOB NO.2340 GARDEN ROAD, SUITE 100
MONTEREY, CALIFORNIA 93940PHONE: 831.649.4642
FAX: 831.649.3530
WWW.WRDARCH.COM
SHEET NAME:
SHEET NO.:FILE NAME.:
SET ISSUED:CHECKED BY:
THE USE OF THE PLANS AND SPECIFICATIONS ISRESTRICTED TO THE ORIGINAL SITE FOR WHICHTHEY WERE PREPARED, AND PUBLICATIONTHEREOF IS EXPRESSLY LIMITED TO SUCH USE.REUSE, REPRODUCTION OR PUBLICATION BYANY METHOD IN WHOLE OR IN PART ISPROHIBITED. TITLE TO THE PLANS ANDSPECIFICATIONS REMAINS WITH THE ARCHITECT,AND VISUAL CONTACT WITH THEMCONSTITUTES PRIMA FACIE EVIDENCE OF THEACCEPTANCE OF THESE RESTRICTIONS.
PLOT DATE: 6.5.2024
24040
CENTRAL COAST COMMUNITY ENERGY
1026 PALM STREET - SAN LUIS OBISPO TI
CENTRAL COAST COMMUNITY ENERGY (3CE)
1026 PALM STREET
SAN LUIS OBISPO, CA 93401 APN: 002-323-031
400 N. McCarthy Blvd. Ste. 250
Copyright c 2024
[email protected]
fx: (408) 522-5260
ph: (408) 522-5255
Milpitas, CA 95035
ENGINEERING
NOT FOR
CONSTRUCTION
E2.1
ELECTRICAL LIGHTING
PLAN
1 ELECTRICAL LIGHTING PLAN SCALE: 1/4"=1'-0"
LIGHTING GENERAL NOTES
CODE NOTES
A SEE GENERAL NOTES ON SHEET E0.1 AND E0.2 FOR INFORMATION AND REQUIREMENTS.B
GENERAL CONTRACTOR SHALL NOTIFY ARCHITECT IMMEDIATELY IF CONFLICTS OCCUR BETWEEN LIGHTING AND ANY OTHER TRADE. DO NOT PROCEED WITH INSTALLATION IN THAT AREA UNTIL CONFLICT HAS BEEN RESOLVED TO THE SATISFACTION OF THE ARCHITECT AND ENGINEER.
C
REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS AND MOUNTING INSTRUCTIONS FOR ALLLIGHT FIXTURES. ELECTRICAL CONTRACTOR'S BID SHALL INCLUDE THE INSTALLATION OF ALL LIGHTFIXTURES AND ASSOCIATED LAMPS. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO ENSURE THE
ADJUSTABILITY OF ALL DOWN LIGHTS AFTER INSTALLATION AND AIM THEM AS DIRECTED BY OWNER'S REPRESENTATIVE.
D ALL WIRES SHALL BE #12 AWG UNLESS NOTED OTHERWISE. PROVIDE SEPARATE NEUTRAL WIRE FOR ALL LIGHTING CIRCUITS BACK TO LIGHTING CONTROL PANEL.
E WHERE WIRE SIZES ARE NOTED ON DRAWINGS, THAT SIZE SHALL BE THROUGH THE ENTIRE RUN UNLESS NOTED OTHERWISE.F
ALL EXIT AND EMERGENCY LIGHT FIXTURES SHALL BE SERVED FROM PRIMARY NORMAL POWER AND BUILT-IN BATTERY BACKUP FOR NOT LESS THAN 90 MINUTES IN THE EVENT OF LOSS OF THE PRIMARYPOWER SUPPLY. E.C. SHALL PROVIDE ADDITIONAL EMERGENCY EGRESS LIGHTING AND EXIT SIGNAGE PERFIRE INSPECTOR REQUIREMENTS. ALL EMERGENCY FIXTURES AND EXIT SIGNS SHALL BE CONNECTED TOUNSWITCHED HOT LEG OF THE LOCAL LIGHTING CIRCUIT.
G
ELECTRICAL CONTRACTOR TO FIELD VERIFY ALL CONDITIONS PRIOR TO BID. ELECTRICAL CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS AS REQUIRED FOR A FULLY COMPLETE AND OPERABLE SYSTEM.COORDINATE ALL LIGHTING WORK WITH MECHANICAL AND FIRE SPRINKLER WORK.
H
THE CONTRACTOR SHALL COORDINATE THE EXACT MOUNTING LOCATION OF ALL LIGHT
FIXTURES, LIGHT SWITCHES, RECEPTACLES, TELEPHONE/DATA OUTLETS, AND ANY OTHERDEVICE LOCATIONS SHOWN ON THIS PLAN WITH THE ARCHITECTURAL FLOOR PLAN, ARCHITECTURAL REFLECTED CEILING PLAN, AND ARCHITECTURAL INTERIOR ELEVATIONS.
DEVICES NOT LOCATED ON THE ARCHITECTURAL DRAWINGS SHALL BE COORDINATED WITH THE ARCHITECT IN THE FORM OF RFI (REQUEST FOR INFORMATION). CONTRACTOR SHALL ASSUMETHAT DEVICES ARE TO BE MOUNTED CENTERED ON THE WALLS, SECTION OF WALLS, WINDOWS, ETC. AND THAT ADDITIONAL MOUNTING BRACKETS AND ACCESSORIES SHALL BE A PART OF THEBID PROPOSAL.
I
INSTALLATION OF CONDUITS AND WIRES SHALL BE CONCEALED ABOVE THE CEILING AND BEHIND WALLS.
WHERE NOT POSSIBLE, CONTRACTOR SHALL OBTAIN APPROVAL FOR EXPOSED LOCATIONS PRIOR TO ROUGH-IN. USE WIREMOLD IN EXPOSED AREAS.
J REFER TO BUILDING GUIDANCE STANDARDS FOR MATERIAL SELECTION CRITERIA, FINISHES AND GENERAL WORK RULES.
K EGRESS LIGHTING, REQUIRED BY CEC 1008.2.1, IS DIFFERENT FROM EMERGENCY LIGHTING, WHICH IS REQUIRED BY CEC 1008.3.
L ALL EXIT, EMERGENCY, AND NIGHT LIGHTS TO BE CONNECTED AHEAD OF ALL LIGHT SWITCHES AND CONTROLS.
M ALL LIGHTING IS NEW UNLESS OTHERWISE NOTED.
N
S.A.D. FOR TYPICAL INSTALLATION OF LIGHT SWITCHES & T-STATS THROUGHOUT, U.O.N. PROVIDE LOCATIONS OF T-STATS AND LIGHT SWITCHES FOR ARCHITECTS APPROVAL PRIOR TO INSTALLATION.PROVIDE ACRYLIC SECURITY BOX WITH LOCK FOR T-STATS.
O FINAL EMERGENCY AND EXIT LIGHTING FIXTURES REQUIREMENTS PER FIRE INSPECTOR. CONTRACTOR SHALL PROVIDE ADDITIONAL EMERGENCY AND EXIT LIGHTING AS REQUIRED.
SHEET NOTES
# NOTES
LIGHTING CONTROLLER SHALL BE TITLE 24 COMPLIANT AND CALIFORNIA ENERGY COMMISSION (CEC) CERTIFIED. CONTROLLER SHALL HAVE INTEGRATED TIME SWITCH FOR INTERIOR LIGHTING SHUT-OFF.SHUT-OFF BY-PASS AS REQUIRED PER TITLE 24.
EXIT/EMERGENCY LIGHT FIXTURE WITH BATTERY PACK. EMERGENCY BATTERY PACK SHALL BE CONNECTED TO LOCAL LIGHTING CIRCUIT AHEAD OF ALL SWITCHES. PROVIDE UNSWITCHED CIRCUIT IN ADDITION TO THE SWITCH CONTROLLED CIRCUIT.
PROVIDE MANUAL DIMMERS (WITH ON-OFF) FOR INDICATED CIRCUITS. DIMMER RATING TO MATCH SERVING LOAD TYPE AND RATING. IF DIMMERS ARE GANGED TOGETHER DO NOT BREAK FINS. IF FINS ARE BROKEN, APPLY DERATING FACTOR. FIELD COORDINATE FINAL LOCATION FOR ALL DIMMERS, PRIOR TO ROUGH-IN.SWITCH WITH INTEGRATED OCCUPANCY SENSOR.
EXHAUST FAN IN BATHROOM TO BE CONTROLLED BY OCCUPANCY SENSOR. COORDINATE WITHMECHANICAL DESIGN FOR EXISTING EXHAUST FAN LOCATION AND ELECTRICAL CONNECTIONS.
PRIMARY DAYLIGHTING ZONE CONTROLLED BY DAYLIGHT SENSOR. SECONDARY DAYLIGHTING ZONE CONTROLLED BY DAYLIGHT SENSOR.
NOT USED
1 23456789
(E) NOT INSCOPE
(E) NOT INSCOPE
(E) NOT INSCOPE
NOT USED
2 2
2 2
2 2
2 2
2 2
2 2
TV
GFCI GFCI
GFCI
(RL)
PNL 'A'
3 B-3
B-15
B-13
B-9
B-7 B-3 B-3
B-15 B-19
B-21 B-21 B-21
B-13
B-9
B-3
B-15
B-19B-19
B-13
B-9B-9
B-9B-9
B-21 B-13
B-21
B-15
B-19
B-3
B-10
B-9
FC
1 FC
2 EF
1 EF
2 HP
2 HP
1 PRINT DATE:DRAWN BY:
JOB NO.2340 GARDEN ROAD, SUITE 100
MONTEREY, CALIFORNIA 93940PHONE: 831.649.4642
FAX: 831.649.3530
WWW.WRDARCH.COM
SHEET NAME:
SHEET NO.:FILE NAME.:
SET ISSUED:CHECKED BY:
THE USE OF THE PLANS AND SPECIFICATIONS ISRESTRICTED TO THE ORIGINAL SITE FOR WHICHTHEY WERE PREPARED, AND PUBLICATIONTHEREOF IS EXPRESSLY LIMITED TO SUCH USE.REUSE, REPRODUCTION OR PUBLICATION BYANY METHOD IN WHOLE OR IN PART ISPROHIBITED. TITLE TO THE PLANS ANDSPECIFICATIONS REMAINS WITH THE ARCHITECT,AND VISUAL CONTACT WITH THEMCONSTITUTES PRIMA FACIE EVIDENCE OF THEACCEPTANCE OF THESE RESTRICTIONS.
PLOT DATE: 6.5.2024
24040
CENTRAL COAST COMMUNITY ENERGY
1026 PALM STREET - SAN LUIS OBISPO TI
CENTRAL COAST COMMUNITY ENERGY (3CE)
1026 PALM STREET
SAN LUIS OBISPO, CA 93401 APN: 002-323-031
400 N. McCarthy Blvd. Ste. 250
Copyright c 2024
[email protected]
fx: (408) 522-5260
ph: (408) 522-5255
Milpitas, CA 95035
ENGINEERING
NOT FOR
CONSTRUCTION
E3.1
ELECTRICAL POWER
PLAN
1 ELECTRICAL POWER PLAN SCALE: 1/4"=1'-0"
SHEET NOTES
# NOTES
NEW ELECTRICAL PANEL. MAINTAIN 42" CLEARANCE IN FRONT OF 480V EQUIPMENT AND 36" CLEARANCE IN FRONT OF 208V EQUIPMENT, 30" MIN. CLEAR WIDTH. SEE SINGLE LINE DIAGRAM FOR FEEDER SIZE.DATA / TELEPHONE OUTLET WITH 1"C UP TO CEILING SPACE. FIELD COORDINATELOCATION AND REQUIREMENT.
SPECIAL RECEPTACLE. FIELD COORDINATE LOCATION AND REQUIREMENT.
DATA / POWER POLE. FIELD COORDINATE LOCATION AND REQUIREMENT. DATA / POWERPOLE MANUF. BY WIREMOLD OR EQUAL.DATA OUTLET WITH 1"C UP TO CEILING SPACE. FIELD COORDINATE LOCATION ANDREQUIREMENT.
TV OUTLET WITH 1"C UP TO CEILING SPACE. FIELD COORDINATE LOCATION AND REQUIREMENT.
DUCT SMOKE DETECTOR. IF REQUIRED PER MECHL PROVIDE SIGNAL AND ALARM CONNECTION TO FACP.
1 2345678
GENERAL NOTES
CODE NOTES
A
PROVIDE GFCI PROTECTION FOR ALL 120V RECEPTACLES IN KITCHEN AND DISH PREP AREAS. ALL GFCI RECEPTACLES SHALL BE READILY ACCESSIBLE AS PER NEC 422.5. FORALL EQUIPMENT WITHOUT READY ACCESS UTILIZE GFI BREAKER AT PANELBOARD (WITH DEDICATED NEUTRAL).
B
KITCHEN EQUIPMENT POWER/ELECTRICAL INFORMATION ARE BASED ON INFORMATION AVAILABLE FROM KITCHEN DRAWINGS. ELECTRICAL CONTRACTOR SHALL VERIFY RECEPTACLE CONFIGURATIONS AND LOADS WITH KITCHEN VENDOR PRIOR TO ROUGH-IN.REPORT TO ENGINEER OF RECORD AS TO DISCREPANCIES.
C ALL WIRES SHALL BE #12 AWG UNLESS NOTED OTHERWISE. PROVIDE SEPARATE NEUTRAL WIRE FOR ALL LIGHTING CIRCUITS BACK TO LIGHTING CONTROL PANEL.
D ALL 120V RUNS LONGER THAN 100' SHALL BE #10 WIRE SIZE UNLESS NOTED OTHERWISE ON PLANS.
E WHERE WIRE SIZES ARE NOTED ON DRAWINGS, THAT SIZE SHALL BE THROUGH THE ENTIRE RUN UNLESS NOTED OTHERWISE.F ELECTRICAL CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS AS REQUIRED FOR A FULLY COMPLETE AND OPERABLE SYSTEM.
G ELECTRICAL CONTRACTOR TO FIELD VERIFY ALL CONDITIONS PRIOR TO BID.
H
THE CONTRACTOR SHALL COORDINATE THE EXACT MOUNTING LOCATION OF ALL LIGHT
FIXTURES, LIGHT SWITCHES, RECEPTACLES, TELEPHONE/DATA OUTLETS, AND ANY OTHERDEVICE LOCATIONS SHOWN ON THIS PLAN WITH THE ARCHITECTURAL FLOOR PLAN, ARCHITECTURAL REFLECTED CEILING PLAN, AND ARCHITECTURAL INTERIOR ELEVATIONS.
DEVICES NOT LOCATED ON THE ARCHITECTURAL DRAWINGS SHALL BE COORDINATED WITH THE ARCHITECT IN THE FORM OF RFI (REQUEST FOR INFORMATION). CONTRACTOR SHALLASSUME THAT DEVICES ARE TO BE MOUNTED CENTERED ON THE WALLS, SECTION OFWALLS, WINDOWS, ETC. AND THAT ADDITIONAL MOUNTING BRACKETS AND ACCESSORIES SHALL BE A PART OF THE BID PROPOSAL.
I
REFER TO MECHANICAL CONTROLS DIAGRAM FOR ADDITIONAL SCOPE OF WORK, SUCH ASPOWER FOR THERMOSTATS, AND OTHER WORK REQUIRED BY ELECTRICAL CONTRACTOR AND NOT SPECIFICALLY MENTIONED IN ELECTRICAL DRAWINGS.
J REFER TO ARCHITECTURAL DETAILS FOR INSTALLATION OF OUTLETS IN FIRE RATED WALLS.
K EACH BRANCH CIRCUIT OF A MULTIWIRE BRANCH CIRCUIT WILL BE SIMULTANEOUSLY DISCONNECTED AT THE POINT WHERE THE BRANCH CIRCUIT ORIGINATES.
L ALL EQUIPMENT UNDER HOODS INCLUDING HOOD LIGHTS TO BE WIRED THRU SHUNT-TRIP BREAKERS.
M
ALL PERMANENTLY CONNECTED (HARD-WIRED) APPLIANCES SHALL BE SERVED WITH
DISCONNECTING MEAN WITHIN SIGHT OF THE UNIT, OR THE SERVING CIRCUIT BREAKER IN
THE PANEL SHALL BE CAPABLE OF BEING LOCKED IN OPEN POSITION AS REQUIRED PER NEC 422.31.
2 ELECTRICAL ROOF POWER PLAN SCALE: 1/4"=1'-0"
(E) MAIN SWBD
(E) PANEL'H' (E) TTB/MPOE MEETING ROOM 103 OFFICE 102 OPEN OFFICE AREA 101 OFFICE 108 OFFICE 107 CLOSET STAIRWAY 104 RESTROOM 105 BREAK AREA 106 B-9 (E) (E) 16 SD SD
7 7 (E) (E)
(E) NOT IN SCOPE