OPERATING DATA
265
Item5.

SG1000 | 49.0L | 1,000 kW

INDUSTRIAL SPARK-IGNITED GENERATOR SET
EPA Certified Stationary Emergency and Non-Emergency

SPEC SHEET
6 of 6

DEMAND RESPONSE READY

YOUR FACTORY RECOGNIZED GENERAC INDUSTRIAL DEALER
Specification characteristics may change without notice. Please contact a Generac Power Systems Industrial Dealer for detailed installation drawings. * All measurements are approximate and for estimation purposes only.

Part No. A0000863976
Rev. B 07/06/2022
Generac Power Systems, Inc. | P.O. Box 8 | Waukesha, WI 53189 P: (262) 544-4811 ©2022 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.

DIMENSIONS AND WEIGHTS*

OPEN SET
L x W x H - in (mm) 220.3 (5,597) x 102.0 (2,590) x 108.1 (2,745) Weight - lbs (kg) 22,798 - 24,495 (10,334 - 11,114)
LEVEL 0 SOUND ATTENUATED ENCLOSURE
L x W x H - in (mm) 329.3 (8,356) x 105.8 (2,688) x 136.9 (3,477) Weight - lbs (kg) Steel - 26,558 - 28,256 (12,050 - 12,820) Aluminum - 24,092 - 25,789 (10,931 - 11,701)
LEVEL 1 SOUND ATTENUATED ENCLOSURE
L x W x H - in (mm) 329.3 (8,356) x 105.8 (2,688) x 136.9 (3,477) Weight - lbs (kg) Steel - 27,801 - 29,499 (12,614 - 13,384) Aluminum - 25,337 - 27,034 (11,496 - 12,266)
LEVEL 2 SOUND ATTENUATED ENCLOSURE
L x W x H - in (mm) 329.3 (8,356) x 105.8 (2,688) x 136.9 (3,477) Weight - lbs (kg) Steel - 29,697 - 31,394 (13,474 - 14,244) Aluminum - 26,279 - 27,976 (11,923 - 12,693)
W
W
W
W
H
H
H
H
L
L
L
L
L x W x H ---> 28' x 9' x 12' 28' 9' 12'
266
Item5.
© 2024 Carrier Form 19MV-CLT-6PD
19MV 50/60 Hz
High-Efficiency Semi-Hermetic Centrifugal Liquid Chillers with Greenspeed® Intelligence, PIC6 Controls, and Ultra Low GWP PUREtec™ R-1234ze(E) or Low GWP R-513A or R-515B Refrigerant
Product Data
AquaEdge® High-Efficiency
Semi-Hermetic Centrifugal
Liquid Chillers
150 to 700 Nominal Tons
(527 to 2,461 kW)
267
Item5.
2 The 19MV AquaEdge® chillers offer:
• Ultra low GWP PUREtec™
R-1234ze(E) or Low GWP R-513A
or R-515B Refrigerant
• Two-stage back-to-back EquiDrive™
semi-hermetic compressor 150 to
700 tons (527 to 2,461 kW)
• Dual EXV (19MV3 only), variable
orifice metering device
• Air cooled variable speed drive
• Positive pressure design with compact footprint
• Modular construction
• Carrier offers a five-year refrigerant
warranty (Domestic and Canada
only)
• Magnetic and roller element bearing
options (Roller element bearing
available on 19MV3 only)
The AquaEdge chiller’s high efficiencies are obtained in real-world operating conditions. Therefore, the effects of potential or indirect global warming
are greatly diminished.

High efficiency
Today’s owners of chilled water plants
demand high efficiency from their
chillers. As a result, the AquaEdge cen- trifugal chiller is offered as a variablespeed machine with a unit-mounted variable speed drive and permanent
magnet motor to maximize part load
efficiency.

Environmental leadership
Carrier has long been committed to the
environment and its sustainability.

AquaEdge chillers provide our customers with a high-efficiency, chlorine-free solution. Carrier’s decision to utilize
ultra low GWP PUREtec™ R-1234ze(E)
or low GWP R-513A or R-515B refrigerant provides our customers with a safer and more environmentally
balanced choice without compromising
efficiency.

Reliability
The AquaEdge chiller’s two-stage posi- tive pressure EquiDrive back-to-back compressor, coupled with ASME (American Society of Mechanical Engineers) constructed heat exchangers, ensures
high reliability and sustainability.

Carrier’s semi-hermetic motors operate
in a clean, refrigerant cooled environment. The semi-hermetic design eliminates the potential shaft seal leaks and refrigerant loss. These are just some of
the reasons why the AquaEdge family of
chillers has one of the industry’s lowest
leak rates.

The AquaEdge chiller’s two-stage positive pressure EquiDrive back-to-back compressor, coupled with ASME constructed heat exchangers, ensures high reliability.

Operating range
The 19MV chiller’s EquiDrive twostage back-to-back compressor provides MORe (More Operating Range) and high efficiency at design conditions, providing the flexibility to operate outside of design conditions to keep your building cool under pressure
including operation down to 10% load
without hot gas bypass (select models).

In addition the 19MV chiller’s frequent
start feature and dual EXVs sized to
enable low lift operation at full load make
the 19MV an ideal fit for chilled water
systems with an integrated water side
economizer.

Semi-hermetic compressor
features
Magnetic bearings are integrated into
the direct drive motor assembly. Motor
is semi-hermetically sealed from the
machine room; cooling is
accomplished by spraying liquid refrigerant on the motor windings.

This highly efficient motor cooling
method results in the use of smaller,
cooler-running motors than could be
realized with air-cooled designs of the
same type.

In addition, Carrier’s semi-hermetic
design eliminates:
• Compressor shaft seals that require
maintenance and increase the likeli- hood of refrigerant leaks • Shaft alignment problems that occur
with open-drive designs during startup and operation, when equipment temperature variations cause thermal expansion
• High noise levels that are common
with air-cooled motors, which radiate noise to the mechanical room and adjacent areas
• Mechanical room cooling requirements associated with air-cooled motors, which dissipate heat to the
mechanical room
Optional shipment with
factory charge for
The AquaEdge 19MV chiller can be
shipped fully charged, minimizing startup and maintenance time. Purge units are not required. The tight construction
of the AquaEdge 19MV centrifugal
chiller ensures that contaminants stay
out and efficiency is maintained
throughout the life of the chiller. The
oil free design enables the AquaEdge
19MV chillers to be shipped with a full
refrigerant charge without the need for
isolation valves.

NOTE: Factory charge is only available
for R-513A and R-515B. R-1234ze(E)
refrigerant requires field charge.

Table of contents
Page
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Chiller Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Features/Benefits
268
Item5.
3 Positive pressure design
The AquaEdge chiller’s positive pressure design reduces the chiller size by up to 35% compared to low-pressure
designs. The smaller size minimizes the
need for valuable mechanical room
floor space. In addition, positive pressure designs eliminate the need for costly low-pressure containment
devices, reducing the initial cost of the
system.

Modular construction
The AquaEdge 19MV chiller is
designed to fit through a 72 in. by
80 in. opening completely assembled
(heat exchanger frame sizes 3 and 4,
standard tier VFD). For smaller spaces,
the evaporator, condenser, and compressor assemblies are completely bolted together, making the AquaEdge
chillers ideally suited for replacement
projects where ease of disassembly and
reassembly at the jobsite are essential.

Marine container shipment
(19MV, heat exchanger
frame sizes 3 and 4 only,
standard tier VFD)
The compact design allows for opentop container shipment to export destinations, ensuring product quality while reducing shipping cost.

Compressors are 100% run-tested to
ensure proper operation of all compressor systems, including vibration, electrical, and compression.

Air-cooled VFD (variable frequency drive)
is designed to be cooled without cooling
water or refrigerant. Enclosure reduces
the risk of exposure of electrical components to dirt, dust, moisture and splashing water. Using air instead of water also eliminates costly maintenance associ- ated with the water cooling pump, heat exchanger, and rubber tubing used with
water-cooled VFDs.

High-efficiency permanent magnet
motor provides high efficiency at full
and part loads.

Heat exchanger features
The American Society of Mechanical
Engineers (ASME) standard requires
the use of an independent agency to
certify the design, manufacture, and
testing of all heat exchangers, ensuring the ultimate in heat exchanger safety, reliability, and long life.

Optional 1 in. tubes provide optimized
cost and less pressure drop than the
standard 3/4 in. tubes. Tube expansion at center support sheets prevents unwanted tube movement and
vibration, thereby reducing the possibility of premature tube failure. Doublegrooved tube sheet holes reduce the possibility of leaks between the water
and refrigerant system, increasing
product reliability. Condenser baffle
prevents direct impingement of high
velocity compressor gas onto the condenser tubes. The baffle eliminates related vibration and wear of the tubes
and distributes the refrigerant flow
evenly over the length of the vessel for
improved efficiency. Closely spaced
intermediate support sheets prevent
tube sagging and vibration, thereby
increasing heat exchanger life.

Refrigerant filter drier isolation valves
allow filter replacement without pumping down the chiller, which means less service time and less expense.

The Sensible Subcooler located in the
bottom of the condenser increases the
refrigeration effect by cooling con- densed liquid refrigerant to a lower temperature, resulting in reduced compressor power consumption.

Dual Expansion Valves (EXV) (19MV3
only) provide precise refrigerant metering over a wide variety of operating conditions. As a result, optimal refrig- erant levels can be maintained in the condenser and evaporator to achieve
the greatest efficiency without uninten- tional hot gas bypass or flooding. The dual EXVs provide full capacity (up to
700 tons) at low lift conditions.

Microprocessor control
features
The 10.4 in. native BACnet®1 touchscreen direct digital Product Integrated Control (PIC6) provides unmatched
flexibility, functionality, and seamless
integration with the Carrier i-Vu®
Building Automation and Control Sys- tem supporting BACnet and Carrier Comfort Network® (CCN) communication protocols. The PIC6 control can be configured to display units in English
or metric, and offers an “all-in-one”
view of key chiller operational data,
simplifying the interaction between the
chiller and user.

Features include:
• Display of over 125 operating, status, and diagnostic messages for improved user experience
• Monitoring of over 100 functions
and parameters to protect the chiller
from abnormal conditions
• Modular pull-out/plug-in design,
reducing wiring requirements and
providing easy installation
• Low-voltage (24-v) design, providing
the ultimate assurance of personal
safety and control integrity
• Display mode uses English and
Chinese.

Automatic capacity override function
unloads the compressor whenever key
safety limits are approached, increas- ing unit life.

Chilled water reset can be accomplished
manually or automatically from the build- ing management system. Reset saves energy when warmer chilled water can
be used. Demand limiting feature limits
the power draw of the chiller during peak
loading conditions. When incorporated
into the Carrier Comfort Network build- ing automation system, a red line command holds chillers at their present capacity and prevents any other chillers
from starting. If a load shed signal is
received, the compressors are unloaded
to avoid high demand charges whenever
possible.

Ramp loading ensures a smooth pulldown of water loop temperature and prevents a rapid increase in compressor power consumption during the pulldown period.

Automated controls test can be exe- cuted prior to start-up to verify that the entire control system is functioning
properly.

The 365-day real time clock feature
allows the operator to program a
yearly schedule for each week, week- ends, and holidays.

Occupancy schedules can be programmed into the controller to ensure that the chiller only operates when
cooling is required.

Extensive service menu features include
password protection to prevent unauthorized access to the service menu. Built-in diagnostic capabilities assist in troubleshooting and recommend proper corrective action for pre-set alarms, resulting in greater operating time.

Alarm file maintains the last 25 time and
date-stamped alarm and alert messages
in memory; this function reduces troubleshooting time and cost. Configuration data backup in nonvolatile memory provides protection during power failures and eliminates time-consuming control
reconfiguration.

1. Third-party trademarks and logos are
property of their respective owners.

Features/Benefits (cont)
269
Item5.
4 Refrigeration Cycle
19MV Refrigeration Cycle (Economized)
19MV Refrigeration Cycle (Non-Economized)
Features/Benefits (cont)
270
Item5.
5 19MV Two-Stage Compressor
19 MV – 4 1 N 4 1 N 6 9 E7 3 5
Description
19 — High Efficiency Semi-Hermetic
Centrifugal Liquid Chiller
MV — Model Designation
– — Magnetic Bearing
R — Roller Element Bearing
1 — Frame 1
2 — Frame 2
3 — Frame 3
4 — Frame 4
5 — Frame 5
Evaporator Frame Size
Evaporator Length
1 — 11 ft (3.4 m) Length
3 — 13 ft (4 m) Length
Evaporator Pass Arrangement and Tube Count
1 — Frame 1
2 — Frame 2
3 — Frame 3
4 — Frame 4
5 — Frame 5
Condenser Frame Size
Special Code
– — Standard
S — Special
Code Volts-Phase-Hertz
3 — 380-3-60
4 — 416-3-60
5 — 460-3-60
9 — 400-3-50

3 — Smallest HP
5 — Medium HP
7 — Large HP
E — Economizer Included
N — No Economizer
Compressor Impeller Diameter Code
9 Compressor Shroud Code
3 4
5 6
7 (Frame 3 Only)
8 (Frame 3 Only)
2 — 150-350 Nominal Tons (527-1,230 kW)
3 — 300-700 Nominal Tons (1,055-2,462 kW)
Compressor Frame Size
Condenser Pass Arrangement and Tube Count
C — 3 pass, 3/4" tube, Lowest Tube Count
D — 3 pass, 3/4" tube, 2nd Lowest Tube Count
F — 3 pass, 3/4" tube, 2nd Highest Tube Count
G — 3 pass, 3/4" tube, Highest Tube Count
K — 1 or 2 pass, 3/4" tube, Lowest Tube Count
L — 1 or 2 pass, 3/4" tube, 2nd Lowest Tube Count
M — 1 or 2 pass, 3/4" tube, 2nd Highest Tube Count
N — 1 or 2 pass, 3/4" tube, Highest Tube Count
P — 1 or 2 pass, 3/4" tube, Highest Tube Count
(Condenser Frame 2 only) Condenser Length
1 — 11 ft (3.4 m) Length
3 — 13 ft (4 m) Length
–
Bearing Option
Voltage Code
E — 3 pass, 3/4" tube, Lowest Tube Count
F — 3 pass, 3/4" tube, Medium Tube Count
G — 3 pass, 3/4" tube, Highest Tube Count
L — 1 or 2 pass, 3/4" tube, Lowest Tube Count
M — 1 or 2 pass, 3/4" tube, Medium Tube Count
N — 1 or 2 pass, 3/4" tube, Highest Tube Count
R — 3 pass, 1" tube, Lower-Medium Tube Count
S — 3 pass, 1" tube, Medium Tube Count
T — 3 pass, 1" tube, Medium-Higher Tube Count
X — 1 or 2 pass, 1" tube, Lowest Tube Count
Y — 1 or 2 pass, 1" tube, Medium Tube Count
Z — 1 or 2 pass, 1" tube, Highest Tube Count
Motor Code
Economizer Option
AHRI (Air-Conditioning, Heating,
and Refrigeration Institute)
Performance Certified
Quality Assurance
ISO 9001:2015-certified processes
A1 Refrigerant
only applies to
R-513A and
R-515B units
Model number nomenclature
271
Item5.
6 Compressor Components
1 2 3
4 5
6 7
8 9
LEGEND
1 — First Stage Volute
2 — Permanent Magnet Motor Rotor
3 — Motor Stator
4 — Second Stage Volute
5 — Second Stage Inlet Guide Vane
6 — Second Stage Impeller
7 — Magnetic Bearing System
8 — First Stage Impeller
9 — First Stage Inlet Guide Vane
Chiller components
272
Item5.
7 Compressor Components (cont)
3 1
2 5
7 6
9 8
4 LEGEND
1 — First Stage Volute
2 — Permanent Magnet Motor Rotor
3 — Motor Stator
4 — Second Stage Volute
5 — Second Stage Inlet Guide Vane
6 — Second Stage Impeller
7 — Oil Bearing System
8 — First Stage Impeller
9 — First Stage Inlet Guide Vane
Chiller components (cont)
273
Item5.
8 Chiller Components — 19MV Standard Tier Option
1 2
4 5
8 7 6
9 10
11 13
14 3
15 12
LEGEND
1 — Suction Elbow First Stage
2 — Refrigerant Economizer
3 — Integrated Power and Control Panel
4 — Condenser Waterbox Return End
5 — Bolt Together Plate
6 — Evaporator Waterbox Return End
7 — HMI Adjustment Arm
8 — 10.4 in. Color Touchscreen Display
9 — Refrigerant Charging Valve
10 — EquiDrive* Two-Stage Back-to-Back
Centrifugal Compressor
11 — Permanent Magnet Motor (hidden)
12 — Evaporator
13 — Magnetic Bearing System
14 — Interstage Compressor Piping
15 — VFD (Variable Frequency Drive)
* Third-party trademarks and logos are
property of their respective owners.
1 2 3
4 6
7 8
9 10
11 12 13
17 16 14
5 LEGEND
1 — Dual Inlet Guide Vane Actuators
2 — Condenser Dual Relief Valves
3 — Evaporator Dual Relief Valves
4 — Evaporator Waterbox
5 — Leaving Evaporator Nozzle
6 — Entering Evaporator Nozzle
7 — ASME Nameplates
8 — Entering Condenser Nozzle
9 — Condenser Waterbox
10 — Leaving Condenser Nozzle
11 — Dual Electronic Expansion Valves
12 — VFD (Variable Frequency Drive)
13 — Condenser Sight Glasses
14 — Strainer
15 — E-stop
16 — Integrated Power and Control Panel
17 — Condenser
18 — Main Circuit Breaker
15 18
Chiller components (cont)
274
Item5.
9 Chiller Components — 19MVR Standard Tier Option (19MV3 Only) 15 14
13 12
11 10 9
8 7
6 5
4 3
2 1
16 15
14 13
12 11
10 9
8 7
6 5
4 3
2 1
LEGEND
1 — Suction Elbow First Stage
2 — Refrigerant Economizer
3 — Integrated Power and Control Panel
4 — Condenser Waterbox Return End
5 — Bolt Together Plate
6 — Evaporator Waterbox Return End
7 — HMI Adjustment Arm
8 — 10.4 in. Color Touchscreen Display
9 — Refrigerant Charging Valve
10 — EquiDrive* Two-Stage Back-to-Back
Centrifugal Compressor
11 — Permanent Magnet Motor (hidden)
12 — Evaporator
13 — Oil Bearing System
14 — Interstage Compressor Piping
15 — VFD (Variable Frequency Drive)
* Third-party trademarks and logos are
property of their respective owners.

LEGEND
1 — Dual Inlet Guide Vane Actuators
2 — Condenser Dual Relief Valves
3 — Evaporator Relief Valve
4 — Evaporator Waterbox
5 — Leaving Evaporator Nozzle
6 — Entering Evaporator Nozzle
7 — ASME Nameplates
8 — Entering Condenser Nozzle
9 — Condenser Waterbox
10 — Leaving Condenser Nozzle
11 — VFD (Variable Frequency Drive)
12 — Condenser Sight Glasses
13 — Strainer
14 — E-stop
15 — Integrated Power and Control Panel
16 — Condenser
Chiller components (cont)
275
Item5.
10 Chiller Components — 19MV2 Standard Tier Option
LEGEND
1 — Suction Elbow First Stage
2 — Integrated Power and Control Panel
3 — Condenser Waterbox Return End
4 — Evaporator Waterbox Return End
5 — HMI Adjustment Arm
6 — 10.4 in. Color Touchscreen Display
7 — Refrigerant Charging Valve
8 — EquiDrive Two-stage Back-to-Back
Centrifugal Compressor
9 — Permanent Magnet Motor (hidden)
10 — Condenser
11 — Magnetic Bearing System
12 — Interstage Compressor Piping
13 — Evaporator Dual Relief Valves
14 — Condenser Dual Relief Valves
15 — ASME Nameplate
LEGEND
1 — Dual Inlet Guide Vane Actuators
2 — Evaporator Waterbox
3 — Leaving Evaporator Nozzle
4 — Entering Evaporator Nozzle
5 — Leaving Condenser Nozzle
6 — Entering Condenser Nozzle
7 — Condenser Waterbox
8 — Strainer
9 — E-stop
10 — Integrated Power and Control Panel
11 — Condenser
12 — Main Circuit Breaker
13 — Refrigerant Economizer
14 — VFD (Variable Frequency Drive)
16 — Evaporator
5 1
11 2
4 3
6 7
8 9
10 12
13 14
15 1
2 3
4 7
5 6 8
9 10
12 11
13 14
16 15
15 — Evaporator
Chiller components (cont)
276
Item5.
11 Chiller Components — High Tier Option (19MV-3 Only)
LEGEND
1 2
3 4
5 6
7 8
15 14
13 12 11 10
1 — Suction Elbow First Stage
2 — Refrigerant Economizer
3 — Integrated Power and Control Panel
4 — Condenser Waterbox Return End
5 — Bolt Together Plate
6 — Evaporator Waterbox Return End
7 — HMI Adjustment Arm
8 — 10.4 in. Color Touchscreen Display
9 — Refrigerant Charging Valve
10 — EquiDrive* Two-Stage Back-to-Back
Centrifugal Compressor
11 — Permanent Magnet Motor (hidden)
12 — Evaporator
13 — Magnetic Bearing System
14 — Interstage Compressor Piping
15 — VFD (Variable Frequency Drive)
* Third-party trademarks and logos are
property of their respective owners.
9 LEGEND
1 — Dual Inlet Guide Vane Actuators
2 — Condenser Dual Relief Valves
3 — Evaporator Dual Relief Valves
4 — Evaporator Waterbox
5 — Leaving Evaporator Nozzle
6 — Entering Evaporator Nozzle
7 — ASME Nameplates
8 — Entering Condenser Nozzle
9 — Condenser Waterbox
10 — Leaving Condenser Nozzle
11 — Main Circuit Breaker
12 — Dual Electronic Expansion Valves
13 — VFD (Variable Frequency Drive)
14 — Condenser Sight Glasses
15 — Strainer
16 — E-stop
17 — Integrated Power and Control Panel
18 — Condenser
1 18
17 16 15 14 13 12 11 10
9 8
7 6
5 4
3 2
Chiller components (cont)
277
Item5.
12 19MV chiller weight
The weight of a 19MV chiller is best obtained by running the chiller selection software. The 19MV has an extensive number of possible combinations of evaporators (including tubing type and length), condensers (including tubing type and length), waterbox types (taking into account heat
exchanger passes), compressors, motors, and system
accessories. The 19MV selection software will determine the rigging weight, operating weight, corner weight, and spring deflection (if applicable) of any configured unit. Due to rigging and installation considerations, there are times when it becomes necessary to determine the contribution of individual components that comprise the chiller. For these situations, a detailed component breakdown is provided in the 19MV Installation Instructions.

Physical data
278
Item5.
13 ITEM OPTION
(FACTORY-INSTALLED)

ACCESSORY
(FIELD-INSTALLED)
2 Pass Evaporator Water-Side Construction X
2 Pass Condenser Water-Side Construction X
Thermal Insulation (except Waterbox Covers) X
Marine Waterboxes 150 psig (1034 kPa)a
NOTE(S):
a. Optional marine waterboxes are available for 19MV, 2 pass only. Standard waterboxes for 19MV are nozzle-in-head type, 150 psig (1034 kPa).

X
Flanged Evaporator and/or Condenser Waterbox Nozzlesb
b. Standard waterbox nozzles are Victaulic type. Flanged nozzles are available as an option with either nozzle-in-head type waterboxes or marine waterboxes.

X
Economizer Assembly (refrigerant circuit) X

0.025, 0.028, 0.035 in. (0.635, 0.711 or 0.889 mm) Internally, Externally Enhanced Copper Tubing – Evaporator X

0.025, 0.028, 0.035 in. (0.635, 0.711 or 0.889 mm) Internally, Externally Enhanced Copper Tubing – Condenser X
Roller Element Bearing (19MV3 Only) X
High Tier VFD (for Harmonic Mitigation) (19MV3 Only) X
Customer Factory Performance Testing X
Extended Warranty (North America only) X
BluEdge Service Agreement X
BluEdge Digital X
Soleplate Package X
Spring Isolator X
Multiple Chiller System Remote Temperature Sensor X
Freestanding Harmonic Filter X
Unit-Mounted VFD Features and Optionsa
NOTE(S):
a. Low voltage: phase to phase and phase to ground.

ITEM STANDARD (S) / OPTIONAL (O)
Microprocessor Based Overload Trip Protection S
Main Power Fuse S: 100kA
Phase Loss/Reversal Imbalance Protection S
Three-Phase Ground Fault Protection S
Three-Phase Over/Under Voltage Protection S
Lightning Surge Arrestor (MOV) O
Harmonic Mitigation O
Options and accessories
279
Item5.
14 19MV3 Recommended Clearances — Standard Tier Option
Extended Overhead Service Clearance for Compressor Service and Rigging. The Service Clearance can be located at either end of the Unit, but must coincide with the tube pull service area end. 4' (1220 mm)
Overhead access area
for compressor rigging
(see note 3b)
Heat
exchanger
width
Tube pull area
(across width of
heat exchangers.)
Service clearance
can be located at
either end of Unit.
11'-3" (3429 mm) or
13'-3" (4039 mm)
A
B
3' to 4' (914 mm - 1220 mm)
As per latest NEC or Local Code Requirements
(for 2017 NEC refer to Article 110.26)
3' (914 mm) or
4' (1220 mm)
(see note 3a)
C
Recommended Overhead Service
Rigging Clearance 5' (1524 mm)

SERVICE AREA
LEGEND
A — Length
B — Width
C — Height
NOTE(S):

1. Dished head (NIH) waterbox shown.

2. Service areas are minimum space required.

3. For compressor service either:
a. Allow 4' (1220 mm) on the evaporator side of the chiller. b. Provide free space above the tube pull area equal to the height of chiller plus 5' (1524 mm). The overhead rigging space will allow the tube pull area to be utilized for service and must therefore coincide with the tube pull service area end.

4. For actual unit dimensions, contact your Carrier sales professional for certified drawings.

5. Pressure relief device sizing is based on the assumption that there are no combustible materials within 20 ft (7.7 m) of the pressure vessels.

6. If the service clearances are not met, extraordinary actions to perform equipment repairs will not be covered by warranty.

Dimensions
280
Item5.
15 SERVICE AREA
A
163.02
[4140.7]

63.00 [ 1600.0 ]

RECOMMENDED

OVERHEAD SERVICE

RIGGING CLEARANCE

52.48 [1333.0]

36.02 - 48.00

AS PER LATEST NEC OR LOCAL CODE REQUIREMENTS
(FOR 2017 NEC REFER TO ARTICAL 110.26)

36.03 - 47.99
[915.0 - 1219.0]
(SEE NOTE 3)

THE EXTENDED OVERHEAD SERVICE CLEARANCE IS FOR
COMPRESSOR SERVICE AND RIGGING. THE SERVICE

CLEARANCE CAN BE LOCATED AT EITHER END OF THE

UNIT, BUT MUST COINCIDE WITH THE TUBE PULL
SERVICE AREA END.

TUBE PULL SERVICE AREA (ACROSS WIDTH OF
HEAT EXCHANGERS). SERVICE CLEARANCE CAN

BE LOCATED AT EITHER END OF THE UNIT
100.03
[ 2540.7 ]
[915.0 - 1219.0]
LEGEND
A — Length
NOTE(S):

1. Dished head (NIH) waterbox shown.

2. Service areas are minimum space required.

3. Allow 48" [1219 mm] on either side of the chiller.

4. Provide free space above the tube pull area equal to the height of the chiller plus 63" [1600 mm]. The overhead rigging space will allow the tube pull area to be utilized for service area.

5. For actual unit dimensions, contact your Carrier sales professional for certified drawings.

6. If the service clearances are not met, extraordinary actions to perform equipment repairs will not be covered by warranty. 19MV2 Recommended Clearances — Standard Tier Option
Dimensions (cont)
281
Item5.
16 Nozzle Size
FRAME SIZE TYPE DESIGN PRESSURE PASSES NOMINAL PIPE SIZE (in.) ACTUAL PIPE ID (in.)

EVAPORATOR CONDENSER EVAPORATOR CONDENSER
2 NIH 150 2 8 8 7.981 7.981
MARINE 150 2 6 6 6.065 6.065
3 NIH 150 2 8 8 7.981 7.981
MARINE 150 2 8 8 7.981 7.981
4 NIH 150 2 8 8 7.981 7.981
MARINE 150 2 8 8 7.981 7.981
5 NIH 150 2 10 10 10.02 10.02
MARINE 150 2 10 10 10.02 10.02
19MV3 Recommended Clearances — High Tier Option
A
Tube pull area
(across width of
heat exchangers).

Service clearance
can be located at
either end of unit.
11'-3'' (3429 mm) or
13'-3'' (4039 mm)
Heat exchanger width
Overhead access area
for compressor rigging
(see note 3b)
3' to 4' (914 mm-1220 mm)
As per latest NEC or Local Code Requirements
(for 2017 NEC refer to Article 110.26)
B
3' (914 mm) or
4' (1220 mm)
(note 3a)

SERVICE AREA
C
Recommended Overhead Service
Rigging Clearance 5'-3" (1600.0 mm)
4' (1220 mm)
Extended Overhead Service Clearance for Compressor Service and Rigging. The Service Clearance can be located at either end of the Unit, but must coincide with the tube pull service area end.

LEGEND
A —Length
B —Width
C —Height
NOTES:

1. For reference, unit shown is HighTier VFD.

2. Dished head (NIH) waterbox shown.

3. Service areas are minimum space required.

4. For compressor service either:
a. Allow 4' (1220 mm) on the evaporator side of the chiller. b. Provide free space above the tube pull area equal to the height of chiller plus 5' (1524 mm). The overhead rigging space will allow the tube pull area to be utilized for service and must therefore coincide with the tube pull service area end.

5. For actual unit dimensions, contact your Carrier sales professional for certified drawings.

Dimensions (cont)
282
Item5.
17 The 19MV chiller can be tailored to the specific requirements of a given application. Please contact your local Carrier representative for a selection. The NG eCAT selection software analyzes many factors, including specific temperature, fluid type, and flow requirements to automatically configure the chiller’s heat exchanger size, compressor aerodynamic model, and electrical sizing to deliver a chiller optimized to the job requirements.

Heat exchangers
Flow rate
If the evaporator flow is variable, the rate of change of flow should not exceed 30% per minute.

Water quality
Please consult your local Carrier representative and/or a local water quality expert.

Selection procedure
283
Item5.
18 Microprocessor controls
The microprocessor control system matches the capacity
of the chiller to the cooling load while providing state-ofthe-art chiller protection. The microprocessor-based control center protects the chiller by monitoring the digital and analog inputs and executing capacity overrides or safety shutdowns as necessary.

The system controls cooling load within the set point (plus or minus the dead band) by sensing the water or brine tem- perature and regulating the inlet guide vanes and regulating VFD speed.

Features
Control system
The control system on each 19MV centrifugal chiller is
native BACnet, factory mounted, wired, and tested to
ensure machine protection and efficient capacity control.

In addition, the program logic ensures proper starting, stopping, and recycling of the chiller and seamlessly integrates with Carrier's i-Vu Building Automation Control System, supporting BACnet and Carrier Comfort Network (CCN) communication protocols. The PIC6 control system
consists of one main control board and up to four IOBs
(input/output board modules). All boards communicate via an internal LEN bus. The main control board is supplied from a 24 vac supply reference to earth ground. In the
event of a power supply interrupt, the unit can restart automatically without the need for an external command. However, any faults active when the supply is interrupted are saved, and may in certain cases prevent a circuit or unit from restarting. IOBs are supplied from a 24 vac supply reference to earth ground. Always separate communication cables from other cables and always run wiring as directly as possible.

Sensors
Pressure transducers
Pressure transducers measure and control the pressures in the unit. These electronic sensors deliver 0 to 5 vdc. The transducers can be calibrated through the controller. The pressure transducers are connected to the IOBs. See the Pressure Transducers table.

Temperature sensors
The system uses electronic sensors to measure and control the temperatures in the unit. There are three types of temperature sensors: 5K thermistor, 10K thermistor, and RTD (resistance temperature detector), 100 ohm, 3-wire based on IOB channel configurations. The temperature sensor
range is –40°F (–40°C) to 245°F (118°C). See the Temperature Sensors table.

Pressure Transducers

PRESSURE TRANSDUCER PURPOSE
Evaporator Measure Evaporator Pressure
Condenser Measure Condenser Pressure
Economizer Measure Economizer Pressure
Temperature Sensors

TEMPERATURE SENSOR PURPOSE
Entering Chilled Water Measure Entering Evaporator Water Temperature Leaving Chilled Water Measure Leaving Evaporator Water Temperature Entering Condenser Water Measure Entering Condenser Water Temperature Leaving Condenser Water Measure Leaving Condenser Water Temperature Evaporator Refrigerant Liquid Measure Evaporator Refrigerant Liquid Temperature Compressor Discharge Measure Compressor Discharge Temperature Radial Bearing Temp Sensor Measure Radial Bearing Temperature Inboard Thrust Bearing Temp Sensor Measure Inboard Thrust Bearing Temperature Outboard Thrust Bearing Temp Sensor Measure Outboard Thrust Bearing Temperature Bearing Controller Temp Sensor Measure Bearing Controller Temperature Motor Winding Temperature Sensors Measure Temperature Of Compressor Motor Windings Oil Sump Temp Sensora Measure Oil Sump Temperature
Bearing oil supply temperaturea Measure Oil Sump Discharge Temperature NOTE(S):
a. 19MVR option only.

Controls
284
Item5.
19 Controls outputs
Evaporator/condenser water pump
The controller can stop and start an evaporator/condenser water pump.

Inlet guide vanes
The inlet guide vanes adjust the refrigerant vapor flow into the compressor to adapt to change in the operating condi- tions of the machine. To adjust the refrigerant flow, the guide vanes open or close to vary the cross-section of the refrigerant path. The high degree of accuracy with which the guide vanes are positioned ensures that the flow of refrigerant is precisely controlled.

Expansion control system valve
The expansion control system valve is set in conjunction with dual EXVs to ensure smooth, proper operation as the chiller unloads across its operating profile.

VFD
The VFD modifies motor voltage input and frequency to
allow the chiller to react to changing lift conditions. Additionally, it allows compressor start-up and, along with inlet guide vanes, provides capacity control.

Safety cutouts
• Guide vane calibration not completed
• Guide vane fault
• High bearing temperature
• High motor temperature
• High discharge temperature
• Low refrigerant temperature
• High evaporator pressure
• Under voltage
• Over voltage
• Intermittent power loss
• VFD configuration conflict
• High pressure switch
• Low liquid level
• Compressor starter faults
• Compressor surge protection
• Evaporator freeze protection
• Ground fault
User interface and web connection
The PIC6 Human Machine Interface (HMI) is a color

10.4 in. touch screen. Navigation is either direct from the touch screen interface or by connecting to a web interface at the Ethernet IP port of the controller. The navigation menus are the same for both connection methods. To
access the PIC6 user interface, enter the IP address of the unit in the address bar of your web browser. The IP address can be viewed or changed from the PIC6 interface.

Controls (cont)
285
Item5.
20 1
1 1
2 3
4 1

TO CHILLER WATER PUMP

TO CONDENSOR WATER PUMP

TO COOLING TOWER FAN

MAIN CHILLER POWER

TO COOLING TOWER FROM

COOLING

TOWER FROM LOAD

TO LOAD
10 9
8 8
11 11
DRAIN
7 5
6 NOTES:

1. Wiring and piping shown are for general point-of-connection only and are not intended to show details for a specific installation. Certified field wiring and dimensional diagrams are available on request.

2. All wiring must comply with applicable codes.

3. Wiring not shown for optional devices such as:
• Remote Start/Stop
• Remote Alarms
• Optional Safety Device
• 4 to 20 mA Resets
• Optional Remote Sensors

4. IMPORTANT: Carrier suggests that a structural engineer be consulted if transmission of vibrations from mechanical equipment is of concern.

5. Isolation valves are recommended on the evaporator and condenser water piping to each chiller for service.

6. Operating environment — Chiller should be installed in an indoor environment where the ambient temperature is 40 to 104°F (4 to 40°C) with a relative humidity (non-condensing) of 95% or less. To ensure that electrical components operate properly, do not locate the chiller in an area exposed to dust, dirt, corrosive fumes, or excessive heat and humidity.

7. Disconnection must be incorporated in the fixed wiring in accordance with the local countryspecific requirements or NFPA (National Fire Protection Association).

8. Tophat is shipped loose and field assembled.

9. Strainers are typically located on the suction side of the water pumps. It is acceptable to install strainers on either side of the pump.
1 — Disconnect
2 — Chilled Water Pump Starter
3 — Condenser Water Pump Starter
4 — Cooling Tower Fan Starter (Low Fan, High Fan)
5 — HMI
6 — Unit-Mounted VFD
7— Power Panel
8 — Strainers
9 — Chilled Water Pump
10 — Condenser Water Pump
11 — Pressure Gages
12 — Local Disconnect (hidden - in power panel)
Piping
Control Wiring
Power Wiring
19MV3 Chiller with Unit-Mounted VFD Diagram — Standard Tier Option Application data
286
Item5.
21 NOTES:

1. Wiring and piping shown are for general point-of-connection only and are not intended to show details for a specific installation. Certified field wiring and dimensional diagrams are available on request.

2. All wiring must comply with applicable codes.

3. Wiring not shown for optional devices such as:
a. Remote Start/Stop
b. Remote Alarms
c. Optional Safety Device
d. 4 to 20 mA Resets
e. Optional Remote Sensors

4. IMPORTANT: Carrier suggests that a structural engineer be consulted if transmission of vibrations from mechanical equipment is of concern.

5. Isolation valves are recommended on the evaporator and condenser water piping to each chiller for service.

6. Operating environment — Chiller should be installed in an indoor environment where the ambient temperature is 40 to 104°F (4 to 40°C) with a relative humidity (non-condensing) of 95% or less. To ensure that electrical components operate properly, do not locate the chiller in an area exposed to dust, dirt, corrosive fumes, or excessive heat and humidity.

7. Disconnection must be incorporated in the fixed wiring in accordance with the local country- specific requirements or NFPA (National Fire Protection Association).

8. Tophat is shipped loose and field assembled.

9. Strainers are typically located on the suction side of the water pumps. It is acceptable to install strainers on either side of the pump.

LEGEND
1 — Disconnect
2 — Chilled Water Pump Starter
3 — Condenser Water Pump Starter
4 — Cooling Tower Fan Starter
(Low Fan, High Fan)
5 — HMI
6 — Power Panel
7 — Strainers
8 — Chilled Water Pump
9 — Condenser Water Pump
10 — Pressure Gages
11 — Local Disconnect
(hidden - in power panel)
Piping
Control Wiring
Power Wiring
From Load
9 7
10 To Load 10
From
Cooling 8 Tower
7 10
To
Cooling
Tower
1 1
1 4
2 3
To Chiller Water Pump
To Condenser Water Pump
To Cooling Tower Fan
5 6
19MV2 Chiller with Unit-Mounted VFD Diagram — Standard Tier Option Application data (cont)
287
Item5.
22 19MV3 Chiller with Unit-Mounted VFD Diagram — High Tier Option 1 1
1 2
3 4
1 TO CHILLER WATER PUMP

TO CONDENSOR WATER PUMP

TO COOLING TOWER FAN

TO COOLING TOWER FROM

COOLING

TOWER FROM LOAD

TO LOAD
10 9
8 8
11 11
DRAIN
7 5
6 NOTES:

1. Wiring and piping shown are for general point-of-connection only and are not intended to show details for a specific installation. Certified field wiring and dimensional diagrams are available on request.

2. All wiring must comply with applicable codes.

3. Wiring not shown for optional devices such as:
• Remote Start/Stop
• Remote Alarms
• Optional Safety Device
• 4 to 20 mA Resets
Optional Remote Sensors

4. IMPORTANT: Carrier suggests that a structural engineer be consulted if transmission of vibrations from mechanical equipment is of concern.

5. Isolation valves are recommended on the evaporator and condenser water piping to each chiller for service.

6. Operating environment — Chiller should be installed in an indoor environment where the ambient temperature is 40 to 104°F (4 to 40°C) with a relative humidity (non-condensing) of 95% or less. To ensure that electrical components operate properly, do not locate the chiller in an area exposed to dust, dirt, corrosive fumes, or excessive heat and humidity.

7. Disconnection must be incorporated in the fixed wiring in accordance with the local countryspecific requirements or NFPA (National Fire Protection Association).

8. Tophat is shipped loose and field assembled.

9. Strainers are typically located on the suction side of the water pumps. It is acceptable to install strainers on either side of the pump.
1 — Disconnect
2 — Chilled Water Pump Starter
3 — Condenser Water Pump Starter
4 — Cooling Tower Fan Starter (Low Fan, High Fan)
5 — HMI
6 — Unit-Mounted VFD
7— Power Panel
8 — Strainers
9 — Chilled Water Pump
10 — Condenser Water Pump
11 — Pressure Gages
12 — Local Disconnect (hidden - in power panel)
Piping
Control Wiring
Power Wiring
•

MAIN CHILLER POWER
Application data (cont)
288
Item5.
23 19MV Two-Stage Compressor Machine Footprint

WIDTH OF FOOT PLATE
19MV HEAT EXCHANGER SIZE
ft-in.
1 11' - 2"
3 4
5 FRAME

DIMENSION C DIMENSION D DIMENSION E DIMENSION F DIMENSION G mm ft-in. mm ft-in. mm ft-in. mm ft-in. mm
11' - 9-1/4" 3588 3404 0 0 1' - 6-3/4" 475 3' - 1-3/8" 950 13' - 9-1/4" 4198 13' - 2" 4013 00 1' - 6-3/4" 475 3' - 1-3/8" 950 11' - 9-1/4" 3588 11' - 2" 3404 2' - 11" 889 1' - 5-1/8" 435 5' - 10" 1778 13' - 9-1/4" 4198 13' - 2" 4013 889 1' - 5-1/8" 435 5' - 10" 1778 11' - 9-1/4" 3588 11' - 2" 3404 889 1' - 4-3/4" 425 5' - 10" 1778 13' - 9-1/4" 4198 13' - 2" 4013 889 1' - 4-3/4" 425 5' - 10" 1778 11' - 9-1/4" 3588 11' - 2" 3404 3' - 3-1/4" 997 1' - 8" 997 7' - 6-1/2" 1994 13' - 9-1/4" 4198 13' - 2" 4013 3' - 3-1/4" 997 1' - 8" 997 7' - 6-1/2" 1994 2' - 11"
2' - 11"
2' - 11"
NOTE(S):

1. View A-A refers to accessory soleplate.

2. View B-B refers to standard support plate.

3. C dimension is measured from actual edge of footplate.

4. D dimension is measured from outside edge to outside edge of tubesheets.

5. E dimension is measured from center line to center line.

6. F dimension is measured from edge of tubesheets (extends past footplate). See certified drawings for actual maximum width.

7. G dimensions are from outermost edge of tubesheets (tubesheet extends slightly past footplate). 2 11' - 9-1/4" 3588 11' - 2" 3404 00 1' - 6-3/4" 475 3' - 1-3/8" 950 13' - 9-1/4" 4198 13' - 2" 4013 0 0 1' - 6-3/4" 475 3' - 1-3/8" 950 Application data (cont)
289
Item5.
24 19MV Isolation with Accessory Soleplate Package

TYPICAL ISOLATION STANDARD ISOLATION

VIEW A-A
NOTES:

1. Optional soleplate package includes 4 soleplates, 16 jacking screws, and 16 leveling pads. Isolation package is also required.

2. Jacking screws to be removed after grout has set.

3. Thickness of grout will vary, depending on the amount necessary to level chiller. Use Ceilcote®1 748 OR MasterFlow™1 885, 1-1/2 in. (38.1 mm) to 2-1/4 in. (57 mm) thick. Both grouts have minimum shrinkage. MasterFLow is premixed.

4. For R-1234ze(E) guidelines please refer to service and installation manuals.

1. Third-party trademarks and logos are property of their respective owners.

VIEW B-B

ISOLATION WITH STANDARD PACKAGE ONLY
NOTE: Isolation package includes
4 Shear-Flex isolation pads.

Support Plate
Tubesheet or End Plate
Shear-Flex Pad
(3/6" [10 mm] Thk.)
Level Base Line
0' - 0 3/8"
[10 mm]
Tubesheet or End Plate
Support Plate
Level Base Line
0'-1 3/8"
[35 mm]
See Note 3
Floor Line
Jacking Screw
(See Note 2)
See Note 1
Soleplate
1" [25 mm] Thk. HRS
Leveling Pad
Support
Plate
Elastomeric
Pad
Jacking
Screw(s)
Leveling
Pad(s)
Soleplate
Standard
Isolation
Accessory
Soleplate
Package
Application data (cont)
290
Item5.
25 19MV3 Nozzle Arrangements Nozzle-in-Head Waterboxes

NOZZLE ARRANGEMENT CODES FOR NOZZLE-IN-HEAD WATERBOXES
EVAPORATOR WATERBOXESa
NOTE(S):
a. Vents and drains are 3/4 in., FPT, located on waterbox head.

CONDENSER WATERBOXESa
PASS In Out Arrangement Codeb
b. Refer to certified drawings.

PASS In Out Arrangement Codeb
2 79 C 2 10 12 R
46 D 13 S

CONDENSER

EVAPORATOR

CONDENSER

EVAPORATOR
2ND STAGE END 1ST STAGE END
19MV2 Nozzle Arrangements Nozzle-in-Head Waterboxes

NOZZLE ARRANGEMENT CODES FOR NOZZLE-IN-HEAD WATERBOXES

EVAPORATOR WATERBOXES CONDENSER WATERBOXES
PASS In Out Arrangement Code PASS In Out Arrangement Code 1 85 A 1 11 2 P
58 B 2 11 Q
2 79 C 2 10 12 R
46 D 13 S
3 76 E
49 F
2nd Stage End 1st Stage End
Application data (cont)
291
Item5.
26 19MV3 Nozzle Arrangements Marine Waterboxes

NOZZLE ARRANGEMENT CODES FOR MARINE WATERBOXES
EVAPORATOR WATERBOXESa
NOTE(S):
a. Vents and drains are 3/4 in., FPT, located on waterbox head.

CONDENSER WATERBOXESa
PASS In Out Arrangement Codeb
b. Refer to certified drawings.

PASS In Out Arrangement Codeb
2 79 C 2 10 12 R
46 D 13 S

CONDENSER

EVAPORATOR

CONDENSER

EVAPORATOR
2ND STAGE END 1ST STAGE END
19MV2 Nozzle Arrangements Marine Waterboxes

NOZZLE ARRANGEMENT CODES FOR MARINE WATERBOXES
EVAPORATOR WATERBOXESa
NOTE(S):
a. Vents and drains are 3/4 in., FPT, located on waterbox head.

CONDENSER WATERBOXESa
PASS In Out Arrangement Codeb
b. Refer to certified drawings.

PASS In Out Arrangement Codeb
1 96 A 1 12 3 P
6 9 B 3 12 Q
2 79 C 2 10 12 R
46 D 13 S
3 76 E
49 F
2nd Stage End 1st Stage End
Application data (cont)
292
Item5.
27 Relief Valve Locationsa
NOTE(S):
a. All valves relieve at 185 psig (1275 kPa).

LOCATION FRAME SIZE PRESSURE RELIEF DEVICE OUTLET SIZE
EVAPORATOR 2, 3, 4, 5 2 x 1-1/4 in. NPT Female Connector (installed with transfer valve) CONDENSER 2 x 1-1/4 in. NPT Female Connector (installed with transfer valve) Relief Device Arrangements
Application data (cont)
293
Item5.
28 Vent and drain connections
Nozzle-in-head waterboxes have vent and drain connections on covers. Marine waterboxes have vent and drain connections on waterbox shells.

Provide high points of the chiller piping system with vents and the low points with drains. If shutoff valves are pro- vided in the main water pipes near the unit, a minimal amount of system water is lost when the heat exchangers are drained. This reduces the time required for drainage and saves on the cost of re-treating the system water.

It is recommended that pressure gauges be provided at
points of entering and leaving water to measure pressure drop through the heat exchanger. Gauges may be installed as shown in Pressure Gauge Location table. Pressure
gauges installed at the vent and drain connections do not include nozzle pressure losses.

Use a reliable differential pressure gauge to measure pressure differential when determining water flow. Regular gauges of the required pressure range do not have the accuracy to provide accurate measurement of flow conditions.

ASME stamping
All 19MV heat exchangers are constructed in accordance
with ASHRAE (American Society of Heating, Refrigerat- ing, and Air-Conditioning Engineers) 15 Safety Code for Mechanical Refrigeration (latest edition). This code, in turn, requires conformance with ASME (American Society
of Mechanical Engineers) Code for Unfired Pressure Vessels wherever applicable.

Each vessel is constructed and certified in accordance with ASME Section 8, Division 1.

Relief valve discharge pipe sizing
See page 27 for number of relief valves and locations.

Relief valve discharge piping size should be calculated per ASHRAE 15, latest edition, using the tabulated C factors for each vessel shown in the Rupture Disc Discharge Pipe Sizing table.

Carrier further recommends that an oxygen sensor be
installed to protect personnel. Sensor should be able to sense the depletion or displacement of oxygen in the machine room below 19.5% volume oxygen per ASHRAE 15, latest edition.

Pressure Gauge Location

NUMBER OF
PASSES

GAUGE LOCATION
(EVAPORATOR OR CONDENSER)
2 Two gauges in waterbox with nozzles
Relief Valve Discharge Pipe Sizing

HEAT EXCHANGER FRAME SIZE REQUIRED C FACTOR
R-134a [LBM AIR / MIN]

REQUIRED C FACTOR
R-513A R-515B
R1234ZE(E)
[LBM AIR / MIN]

RATED C FACTOR
[LBM AIR / MIN]
FIELD

CONNECTION
SIZE in.
[FPT]

EVAPORATOR
21E to 21N 39.6 36.1 70.8 1-1/4
23E to 23N 46.7 42.6 70.8 1-1/4
31B to 31N 39.5 36.0 70.8 1-1/4
33B to 33N 46.5 42.4 70.8 1-1/4
41B to 41N 45.8 41.8 70.8 1-1/4
43B to 43N 54.0 49.3 70.8 1-1/4
51B to 51N 48.8 44.5 70.8 1-1/4
53B to 53N 57.5 52.5 70.8 1-1/4
31O to 31Z 39.5 36.0 70.8 1-1/4
33O to 33Z 46.5 42.4 70.8 1-1/4
41O to 41Z 45.8 41.8 70.8 1-1/4
43O to 43Z 54.0 49.3 70.8 1-1/4
51O to 51Z 48.8 44.5 70.8 1-1/4
53O to 53Z 57.5 52.5 70.8 1-1/4

CONDENSER
21K to 21P 37.8 34.5 70.8 1-1/4
23K to 23P 44.6 40.7 70.8 1-1/4
31B to 31N 37.6 34.3 70.8 1-1/4
33B to 33N 44.3 40.4 70.8 1-1/4
41B to 41N 42.8 39.1 70.8 1-1/4
43B to 43N 50.5 46.1 70.8 1-1/4
51B to 51N 46.5 42.4 70.8 1-1/4
53B to 53N 54.9 50.1 70.8 1-1/4
Application data (cont)
294
Item5.
29 Design pressures
Design and test pressures for heat exchangers are listed below.

Insulation
Factory insulation (optional)
The factory insulation option for the 19MV chillers include the following areas: evaporator (not including waterbox); suction line up to the compressor suction housing; compressor motor and motor cooling return lines; motor MBC cover; the liquid line, economizer, and economizer piping.

Insulation applied at the factory is 3/4 in. (19 mm) thick and has a thermal conductivity K value of 0.28 (Btu in.)/hr ft2 °F [(0.0404 • W)/(m • °C)]. Insulation conforms with Underwriters Laboratories (UL) Standard 94, Classification 94HBF.

Insulation at jobsite
As indicated in the Condensation vs. Relative Humidity
table, the factory insulation provides excellent protection against condensation under most operating conditions. If temperatures in the equipment area exceed the maximum
design conditions, extra insulation is recommended. If the machine is to be field insulated, obtain the approximate areas from the Minimum Field-Installed Insulation Requirements table.

Insulation of waterbox is made only in the field and this area is not included in Minimum Field-Installed Insulation Requirements table. When insulating the covers, allow for service access and removal of covers. To estimate waterbox cover areas refer to certified drawings.

High humidity jobsite locations may require field supplied and installed insulation on the suction housing and lower half of the condenser.

Unit location
The chiller should be installed in an indoor environment where the ambient temperature is 40 to 104°F (4 to 40°C) with a relative humidity (non-condensing) of 95% or less.

To ensure that electrical components operate properly, do not locate the chiller in an area exposed to dust, dirt, corrosive fumes, or excessive heat and humidity.

Design and Test Pressures for Heat Exchangers

VESSEL PRESSURES

SHELL SIDE
(REFRIGERANT)

STANDARD TUBE SIDE
(WATER)

OPTIONAL TUBE SIDE
(WATER)
psig kPa psig kPa psig kPa

EVAPORATOR
Design 185 1276 150 1034 300 2068
Leak Test (min) 185 1276 150 1034 300 2068
Hydrostatic Test — — 195 1344 390 2690
Proof Test (min Pneumatic) 204 1407 — — — —

CONDENSER
Design 185 1276 150 1034 300 2068
Leak Test (min) 185 1276 150 1034 300 2068
Hydrostatic Test — — 195 1344 390 2690
Proof Test (min Pneumatic) 204 1407 — — — —

ECONOMIZER
Design 185 1276 — — — —
Leak Test (min) 185 1276 — — — —
Hydrostatic Test — — — — — —
Proof Test (min Pneumatic) 204 1407 — — — —
Heat Exchanger Material Specifications

ITEM MATERIAL SPECIFICATION
SHELL HR Steel ASME SA516 GR .70
TUBE SHEET HR Steel ASME SA516 GR .70
FLAT COVERS HR Steel ASME/ASTM A516 GR.70
PIPE Steel ASME SA106 GRB/SA53 E/B
FLANGES Steel ASME B16.5
TUBES Per Job
Requirement ASME SB359
DISHED COVER HR Steel ASTM A516 GR.70/GB713 Q345R

MARINE WATER
BOX SHELL HR Steel ASME/ASTM A516 GR.70
Minimum Field-Installed Insulation Requirementsa,b
NOTE(S):
a. Factory installed as shown on page 30.
b. Insulation amount includes only the amount of insulation required to insulate the sections of the chiller that would be included in the factory-installed insulation option.

FRAME
SIZE LENGTH (in.) INSULATION AREA (sq ft)
Frame 2 134 125
158 135
Frame 3 134 125
158 135
Frame 4 134 155
158 170
Frame 5 134 170
158 185
Condensation vs. Relative Humiditya
NOTE(S):
a. These approximate figures are based on 35°F (1.7°C) saturated suction temperature. A 2°F (1.1°C) change in saturated suction temperature changes the relative humidity values by 1% in the same direction.

AMOUNT OF

CONDENSATIO
N

ROOM DRY-BULB TEMP
80°F (27°C) 90°F (32°C) 100°F (38°C)
% RELATIVE HUMIDITY
NONE 80 76 70
SLIGHT 87 84 77
EXTENSIVE 94 91 84
Application data (cont)
295
Item5.
30 Top View
Front View 2nd Stage End 1st Stage End
2nd Stage End 1st Stage End
19MV3 Standard Insulation Area
NOTE: Economized configuration optional, and shown here as reference.

Application data (cont)
296
Item5.
31 19MV2 Standard Insulation Area
NOTE: Economized configuration optional, and shown here as reference.

Application data (cont)
297
Item5.
32 Note about this specification:

This specification is in the “Masterformat” as published by the Construction Specification Institute. Please feel free to copy this specification directly into your building spec.

Packaged Semi-Hermetic Centrifugal
Liquid Chiller
HVAC Guide Specifications — 19MV
Size Range: 19MV to 150 to 700 Nominal Tons
(527 to 2,461 kW)
Carrier Model Number: 19MV
Part 1 — General

1.01 SYSTEM DESCRIPTION
A. Microprocessor-controlled liquid chiller shall use a semi-hermetic centrifugal compressor using Ultra low
GWP PUREtec™ R-1234ze(E) or Low GWP R-513A
or R-515B refrigerant.

B. If a manufacturer proposes a liquid chiller using
R-123 or R-514A refrigerant, then the manufacturer shall include in the chiller price:

1. A vapor activated alarm system capable of
responding to R-123 or R-514A levels of
10 ppm Allowable Exposure Limit (AEL).

2. External refrigerant storage tank and pumpout
unit.

3. Zero emission purge unit capable of operating
even when the chiller is not operating.

4. Back-up relief valve to rupture disk.

5. Chiller pressurizing system to prevent leakage
of noncondensables into chiller during shutdown periods.

6. Plant room ventilation.

1.02 QUALITY ASSURANCE
A. Chiller performance shall be rated in accordance
with AHRI (Air-Conditioning, Heating and Refrigeration Institute) Standard 550/590, latest edition.

The chiller manufacturer, model number and refrigerant shall be listed on the AHRI.org website (www.ahridirectory.org).

B. Equipment and installation shall be in compliance
with ANSI/ASHRAE (American National Standards
Institute/American Society of Heating, Refrigerating
and Air-Conditioning Engineers) 15 (latest edition).

C. Evaporator and condenser refrigerant side shall
include ASME “U” stamp and nameplate certifying
compliance with ASME Section VIII, Division 1 code
for unfired pressure vessels.

D. Chiller shall be designed and constructed to meet
UL (Underwriters Laboratories) and UL, Canada
requirements and have labels appropriately affixed.

E. Centrifugal compressor impellers shall be dynamically balanced and over-speed tested by the manufacturer at a minimum of 120% design operating speed. Each compressor assembly shall undergo a
mechanical run-in test to verify vibration levels are
within acceptable limits.

F. Each compressor assembly shall be proof tested at a
minimum 204 psig (1406 kPa) and leak tested at
185 psig (1276 kPa) with a tracer gas mixture.

G. Entire chiller assembly shall be proof tested at
204 psig (1406 kPa) and leak tested at 185 psig
(1276 kPa) with a tracer gas mixture on the refrigerant side. The water side of each heat exchanger shall be hydrostatically tested at 1.3 times rated
working pressure.

H. Prior to shipment, the chiller automated controls
test shall be executed to check for proper wiring and
ensure correct controls operation.

I. The unit-mounted VFD (variable frequency drive)
shall be factory wired and tested to verify proper
operation prior to shipment.

J. The management system governing the manufacture of this chiller shall be ISO 9001:2015 certified.

1.03 DELIVERY, STORAGE AND HANDLING
A. Unit shall be stored and handled in accordance with
manufacturer's instructions.

B. Unit shall be shipped with all refrigerant piping and control wiring factory installed.

C. Unit shall be shipped charged with full charge of
refrigerant R-515B or R-513A or a nitrogen holding
charge as specified on the equipment schedule.

R-1234ze(E) is field charge only.

D. Unit shall be shipped with firmly attached labels that indicate name of manufacturer, chiller model number, chiller serial number, and refrigerant used.

E. If the chiller is to be exported, the unit shall be sufficiently protected from the factory against sea water corrosion to be suitable for shipment in a standard
open top, ocean shipping container (19MV heat
exchanger frame sizes 3 and 4 only, standard tier
VFD).

1.04 WARRANTY
Warranty shall include parts and labor for one year
after start-up or 18 months from shipment, whichever occurs first.

Part 2 — Products

2.01 EQUIPMENT
A. General:

Factory assembled, single piece, liquid chiller shall
consist of compressor, motor, variable frequency
drive, lubrication system, evaporator, condenser, initial oil and refrigerant operating charges, microprocessor control system, and documentation required prior to start-up.

B. Compressor:

1. One high performance centrifugal compressor.

2. Compressor, motor, and transmission shall be
semi-hermetically sealed into a common assembly and arranged for easy field servicing.

3. Connections to the compressor casing shall use
gaskets to reduce the occurrence of refrigerant
Guide specifications
298
Item5.
33 leakage. Connections to the compressor shall
be flanged or bolted for easy disassembly.

4. All pressure transducers shall have quick disconnects to allow replacement of the sensor without replacement of the entire sensor wire. Pressure
transducers shall be capable of field calibration to
ensure accurate readings and to avoid unnecessary transducer replacement. Pressure transducers and temperature sensors shall be serviceable without the need for refrigerant charge removal or isolation. The high pressure switch requires pulling of the refrigerant charge before changing.

5. The 19MV– unit has magnetic bearings and
backup angular contact roller element bearings.

The 19MVR unit has angular contact ball bearings which control the radial and axial movement of the shaft.

6. Centrifugal compressors shall use variable inlet
guide vanes to provide capacity modulation
while also providing pre-whirl of the refrigerant
vapor entering the impeller for more efficient
compression at all loads.

7. In the 19MVR unit, centrifugal compressors
shall be provided with a factory-installed lubrication system to deliver oil under pressure to bearings and transmission. Included in the system shall be:
a. Hermetic driven oil pump with factory-installed
motor contactor with overload protection.
b. Oil pressure regulator (19MVR rolling element bearing units). c. Oil filter with isolation valves to allow filter
change without removal of refrigerant
charge (19MVR rolling element bearing
units).
d. Oil sump heater controlled from unit microprocessor (19MVR rolling element bearing units).
e. Oil reservoir temperature sensor with main
control center digital readout (19MVR rolling
element bearing units).
f. When factory-mounted compressor motor
starter or VFD is provided, all wiring to oil
pump, oil heater, and controls shall be prewired in the factory. g. Compressor shall be fully field serviceable.

Compressors which must be removed and
returned to the factory for service shall be
unacceptable.

C. Motor:

1. Compressor motor shall be of the semihermetic, liquid refrigerant cooled, permanent magnet type suitable for voltage shown on the
equipment schedule.
a. On 19MVR rolling element bearing units, an
oil reservoir shall collect oil and refrigerant
that leaks past the seal.
b. A float device shall be provided to open when
the reservoir is full, directing the refrigerant/oil
mixture back into the compressor housing.
c. A refrigerant sensor shall be located next to
the open drive seal to detect leaks.

2. Motors shall be suitable for operation in a refrigerant atmosphere and shall be cooled by atomized refrigerant in contact with the motor windings.

3. Motor stator shall be arranged for service or
removal with only minor compressor disassembly and without removing main refrigerant piping connections.

4. Full load operation of the motor shall not
exceed nameplate rating.

5. At least one motor winding temperature sensor
(and one spare) shall be provided.

6. Should the mechanical contractor choose to provide a chiller with an open motor instead of the specified semi-hermetic motor, the contractor
shall install additional cooling equipment to dissipate the motor heat as per the following formula:

Btuh = (FLkW motor) (0.05) (3413)
Btuh = (FLkW motor) (171)
and, alternately,
Tons = Btuh / 12,000
The additional piping, valves, air-handling
equipment, insulation, wiring, switchgear
changes, ductwork, and coordination with other
trades shall be the responsibility of the mechanical contractor. Shop drawings reflecting any changes to the design shall be included in the
submittal, and incorporated into the final as
built drawings for the project.

7. Also, if an open motor is provided, a mechanical room thermostat shall be provided and set at 104°F (40°C). If this temperature is
exceeded, the chillers shall shut down and an
alarm signal shall be generated to the Central
Energy Management System (EMS) display
module prompting the service personnel to
diagnose and repair the cause of the overtemperature condition. The mechanical contractor shall be responsible for all changes to the design, including coordination with temperature control, electrical and other trades. In addition, the electrical power consumption of
any auxiliary ventilation and/or mechanical
cooling required to maintain mechanical room
conditions stated above shall be considered in
the determination of conformance to the scheduled chiller energy efficiency requirement.

D. Evaporator and Condenser:

1. Evaporator shall be of shell and tube type construction, each in separate shells. Units shall be fabricated with high-performance tubing, minimum 1/4 in. (6 mm) steel shell and tube sheets with fabricated steel waterboxes.

Guide specifications (cont)
299
Item5.
34 a. Waterbox shall be nozzle-in-head waterbox
(150 psig [1034 kPa]).
b. Waterbox shall have standard Victaulic
grooves. Victaulic AGS grooves shall be provided for nominal 14 in. pipe and larger.

2. Condenser shall be of shell and tube type construction, each in separate shells. Units shall be fabricated with high-performance tubing, minimum 1/4 in. (6 mm) steel shell and tube sheets with fabricated steel waterboxes.
a. Waterbox shall be nozzle-in-head (150 psig
[1034 kPa]).
b. Waterbox shall have standard Victaulic
grooves. Victaulic AGS grooves shall be provided for nominal 14 in. pipe and larger.

3. Waterboxes shall have vents, drains, and covers
to permit tube cleaning within the space shown
on the drawings. A thermistor-type temperature
sensor with quick connects shall be factory
installed in each water nozzle.

4. Tubes shall be individually replaceable from
either end of the heat exchanger without affecting the strength and durability of the tube sheet and without causing leakage in adjacent tubes.

5. Tubing shall be copper, high-efficiency type,
with integral internal and external enhancement unless otherwise noted. Tubes shall be nominal 3/4 in. or 1 in. OD with nominal wall
thickness of 0.025 in. measured at the root of
the fin at the enhanced areas and nominal wall
thickness of 0.049 in. where the tubes are in
contact with the end tube sheets unless otherwise noted. Tubes shall be rolled into tube sheets and shall be individually replaceable.

Tube sheet holes shall be double grooved for
joint structural integrity.

6. Evaporator shall be designed to prevent liquid
refrigerant from entering the compressor.

7. The condenser shell shall cool the condensed
liquid refrigerant to a reduced temperature,
thereby increasing the refrigeration cycle
efficiency.

8. A reseating-type pressure relief valve shall be
installed on each heat exchanger. If a nonreseating type is used, a backup reseating type shall be installed in series.

E. Refrigerant Flow Control:

1. 19MV3 Only —To maintain optimal part load
efficiency at high or low lift, the chiller shall utilize (2) Electronic Expansion Valves (EXVs) in the liquid line between the condenser and the evaporator. When equipped, the economizer shall use a variable metering valve. To ensure good operating
performance, the valve design will prevent refrigerant gas from the condenser from passing to the evaporator or economizer at full or part load.

2. By maintaining a liquid seal at the flow valve,
bypassed hot gas from the condenser to the
evaporator is eliminated. The float valve chamber shall have a bolted access cover to allow field inspection and the float valve shall be field
serviceable.

F. Controls, Safeties, and Diagnostics:

1. Controls:
a. The chiller shall be provided with a factoryinstalled and wired microprocessor control center. The microprocessor can be configured for either English or SI units. b. All chiller and starter monitoring shall be displayed at the chiller control panel. c. The controls shall make use of non-volatile
memory.
d. The chiller control system shall have the ability to interface and communicate directly to the building control system.
e. The default standard display screen shall
simultaneously indicate the following minimum information:
1) Date and time of day
2) 24-character primary system status
message
3) 24-character secondary status message
4) Chiller operating hours
5) Entering chilled water temperature
6) Leaving chilled water temperature
7) Evaporator refrigerant temperature
8) Entering condenser water temperature
9) Leaving condenser water temperature
10) Condenser refrigerant temperature
11) Percent motor rated load amps (RLA).
f. In addition to the default screen, status
screens shall be accessible to view the status
of every point monitored by the control center including:
1) Evaporator pressure
2) Condenser pressure
3) Oil supply pressure (19MVR rolling element bearing units) 4) Oil sump temperature (19MVR rolling
element bearing units)
5) Bearing oil supply temperature (19MVR
rolling element bearing units)
6) Compressor discharge temperature
7) Motor winding temperature
8) Number of compressor starts
9) Control point settings
10) Discrete output status of various devices
11) Compressor motor starter status
12) Optional spare input channels
Guide specifications (cont)
300
Item5.
35 13) Current and voltage for each phase
14) Frequency.
g. Schedule Function:

The chiller controls shall be configurable for
manual or automatic start-up and shutdown.

In automatic operation mode, the controls
shall be capable of automatically starting and
stopping the chiller according to a stored
user programmable occupancy schedule.

The controls shall include built-in provisions
for accepting:
1) A minimum of two 365-day occupancy
schedules.
2) A minimum of 8 separate occupied/
unoccupied periods per day.
3) Daylight savings start/end.
4) A minimum of 18 user-defined holidays.
5) A means of configuring an occupancy
timed override.
6) Chiller start-up and shutdown via remote
contact closure.
h. Service Function:

The controls shall provide a passwordprotected service function which allows authorized individuals to view an alarm history file which shall contain the last 25 alarm/alert
messages with time and date stamp. These
messages shall be displayed in text form, not
codes.
i. Network Window Function:

Each chiller control panel shall be capable of
viewing multiple point values and statuses
from other like controllers connected on a
common network, including controller maintenance data. The operator shall be able to alter the remote controller’s set points or
time schedule and to force point values or
statuses for those points that are operator
forcible. The control panel shall also have
access to the alarm history file of all like controllers connected on the network. j. Pump Control:

Upon request to start the compressor, the
control system shall start the chilled water
pump and condenser water pumps, and verify that flows have been established. k. Ramp Loading:

A user-configurable ramp loading rate, effective during the chilled water temperature pulldown period, shall control the rate of
guide vane opening to prevent a rapid
increase in compressor power consumption.

The controls shall allow configuration of the
ramp loading rate in either degrees/minute
of chilled water temperature pulldown or
percent motor amps/minute. During the
ramp loading period, a message shall be
displayed informing the operator that the
chiller is operating in ramp loading mode.
l. Chilled Water Reset:

The control center shall allow reset of the
chilled water temperature set point based on
any one of the following criteria:
1) Chilled water reset based on an external
4 to 20 mA signal.
2) Chilled water reset based on a remote
temperature sensor (such as outdoor air).
3) Chilled water reset based on water temperature rise across the evaporator. m. Demand Limit:

The control center shall limit amp draw of
the compressor to the rated load amps or to
a lower value based on one of the following
criteria:
1) Demand limit based on a user input
ranging from 40% to 100% of compressor rated load amps. 2) Demand limit based on external 4 to
20 mA signal.
n. Controlled Compressor Shutdown:

The controls shall be capable of being configured to soft stop the compressor. When the stop button is pressed or remote contacts open
with this feature active, the guide vanes shall
close to a configured amperage level and the
machine shall then shut down. The display
shall indicate “shutdown in progress.”

2. Safeties:
a. Unit shall automatically shut down when any
of the following conditions occur. Each of
these protective limits shall require manual
reset and cause an alarm message to be displayed on the control panel screen, informing the operator of the shutdown cause.
1) Motor overcurrent
2) Over voltage1
3) Under voltage1
4) Single cycle dropout1
5) Bearing oil high temperature (19MVR
rolling element bearing units)
6) Low evaporator refrigerant temperature
7) High condenser pressure
8) High motor temperature
9) High compressor discharge temperature
10) Prolonged surge
11) Loss of evaporator water flow
12) Loss of condenser water flow
13) Starter fault.

1. Shall not require manual reset or cause an alarm if auto-restart after power failure is enabled.

Guide specifications (cont)
301
Item5.
36 b. The control system shall detect conditions that
approach protective limits and take self
corrective action prior to an alarm occurring.

The system shall automatically reduce chiller
capacity when any of the following parameters
are outside their normal operating range:
1) High condenser pressure
2) High motor temperature
3) Low evaporator refrigerant temperature
4) Surge prevention control
5) High motor amps.
c. During the capacity override period, a prealarm (alert) message shall be displayed informing the operator which condition is
causing the capacity override. Once the condition is again within acceptable limits, the override condition shall be terminated and
the chiller shall revert to normal chilled
water control. If during either condition the
protective limit is reached, the chiller shall
shut down and a message shall be displayed
informing the operator which condition
caused the shutdown and alarm.
d. Internal built-in safeties shall protect the
chiller from loss of water flow. Differential
pressure switches shall not be allowed to be
the only form of freeze protection.

3. Diagnostics and Service:
a. A self-diagnostic controls test shall be an integral part of the control system to allow quick identification of malfunctioning components.
b. Once the controls test has been initiated, all
pressure and temperature sensors shall be
checked to ensure they are within normal
operating range. A pump test shall automatically energize the chilled water pump, condenser water pump, and oil pump. The control system shall confirm that water flow
and oil pressure have been established and
require operator confirmation before proceeding to the next test. A guide vane actuator test shall open and close the guide vanes to check for proper operation. The operator
manually acknowledges proper guide vane
operation prior to proceeding to the next
test.
c. In addition to the automated controls test,
the controls shall provide a manual test
which permits selection and testing of individual control components and inputs. A thermistor test and transducer test shall display and an actual reading shall be performed for each transducer and each thermistor installed on the chiller. All out-ofrange sensors shall be identified.

4. Multiple Chiller Control:

The chiller controls shall be supplied as standard
with a two-chiller lead/lag and a third chiller
standby system. The control system shall automatically start and stop a lag or second chiller on a two-chiller system. If one of the two chillers on
line goes into a fault mode, the third standby
chiller shall be automatically started.

The two-chiller lead/lag system shall allow manual rotation of the lead chiller, include load balancing if configured, and allow a staggered
restart of the chillers after a power failure.

G. Electrical Requirements:

1. Electrical contractor shall supply and install
main electrical power line, disconnect switches,
circuit breakers, and electrical protection
devices per local code requirements and as indicated necessary by the chiller manufacturer.

2. Electrical contractor shall wire the chilled water
pump, condenser water pump, and tower fan
control circuit to the chiller control circuit.

3. Electrical contractor shall supply and install
electrical wiring and devices required to interface the chiller controls with the building control system if applicable.

4. Electrical power shall be supplied to the unit at
the voltage, phase, and frequency listed in the
equipment schedule.

H. Piping Requirements — Instrumentation and Safeties:
a. Mechanical contractor shall supply and
install pressure gauges in readily accessible
locations in piping adjacent to the chiller
such that they can be easily read from a
standing position on the floor. Scale range
shall be such that design values shall be indicated at approximately midscale. b. Gauges shall be installed in the entering and
leaving water lines of the evaporator and
condenser.

I. Isolator Pads:

Chiller manufacturer shall furnish neoprene isolator
pads for mounting equipment on a level concrete
surface.

J. Start-up:

1. The chiller manufacturer shall provide a factorytrained representative, employed by the chiller manufacturer, to perform the start-up procedures as outlined in the Start-up, Operation, and Maintenance manual provided by the
chiller manufacturer.

2. Manufacturer shall supply the following literature:
a. Start-up, operation, and maintenance
instructions.
b. Installation instructions.
c. Field wiring diagrams.
d. One complete set of certified drawings.

Guide specifications (cont)
302
Item5.
37 K. Special Features:

1. Soleplate Package Accessory:

Unit manufacturer shall furnish a soleplate
package consisting of soleplates, jacking
screws, leveling pads, and neoprene pads.

2. Spring Isolators Accessory:

Field furnished and selected for the desired
degree of isolation.

3. Spare Sensors with Leads Accessory:

Unit manufacturer shall furnish additional temperature sensors and leads.

4. Stand-Alone Pumpout Unit Accessory (R-513A
units only):

A free-standing pumpout shall be provided. The
pumpout unit shall use a scroll compressor with
water-cooled condenser. Condenser water piping and 3-phase motor power shall be installed at the jobsite by the installing contractor.

5. Separate Storage Tank and Pumpout Unit
Accessory (R-513A units only):

A free-standing refrigerant storage tank and
pumpout unit shall be provided. The storage vessels shall be designed per ASME Section VIII Division 1 code with 185 psig (1276 kPa) design pressure. Double relief valves per ANSI/ASHRAE
15, latest edition, shall be provided. The tank shall
include a liquid level gauge and pressure gauge.

The pumpout unit shall use a scroll compressor
with water cooled condenser. Condenser water
piping and 3-phase motor power shall be installed
at the jobsite by the installing contractor.

6. Refrigerant Charge:

The chiller shall ship from the factory fully
charged with R-515B or R-513A refrigerant.

R-1234ze(E) is field charge only.

7. Thermal Insulation:

Unit manufacturer shall insulate the evaporator
shell, economizer, low side compressor suction
elbow, motor shell, and motor cooling lines. Insulation shall be 3/4 in. (19 mm) thick with a thermal conductivity not exceeding 0.28 (Btu in.)/hr ft2 F [(0.0404 • W)/(m • °C)] and shall conform to
UL standard 94, classification 94 HBF.

8. Evaporator and Condenser Tubes:

Contact local Carrier representative for other
tube offerings.

9. Evaporator and Condenser Passes:

Unit manufacturer shall provide the evaporator
with 2 pass configuration on the water side.

10. Marine Waterboxes, 150 psig (1034 kPa):

Unit manufacturer shall furnish marine style
waterboxes on evaporator and/or condenser
rated at 150 psig (1034 kPa).

11. Flanged Waterbox Nozzles:

Unit manufacturer shall furnish standard
flanged piping connections on the evaporator
and/or condenser.

12. Hinges:

Unit manufacturer shall furnish hinges on
waterboxes to facilitate tube cleaning.

13. Unit-Mounted Variable Frequency Drive
(VFD) without Built-In Harmonic Filter (available
for low voltage only, 19MV3 only):
a. Design:
1) VFD shall be air cooled, microprocessor
based, pulse width modulated (PWM)
design. Water cooled designs are not
acceptable.
2) Output power devices shall be insulated
gate bipolar transistors (IGBTs).
3) Converter section with full-wave fixed
diode bridge rectifier shall convert
incoming fixed voltage/frequency to
fixed DC voltage.
4) DC link shall filter and smooth the converted DC voltage. 5) Transistorized inverter and control regulator shall convert fixed DC voltage to a sinusoidal PWM waveform.
6) Integrated controls shall coordinate
motor speed and guide vane position to
optimize chiller performance over a
wide variety of operating conditions.
7) Surge prevention and surge protection
algorithms shall take action to prevent
surge and move chiller operation away
from surge.
b. Enclosure:
1) Pre-painted, unit-mounted cabinet protected against limited ingress of dust and water splashing shall include hinged
doors and removable lifting lugs.
2) Electrical system shall have a short circuit interrupt and withstand rating of at least 100,000 amps.
3) Provisions to padlock main disconnect
handle in the “Off” position shall be provided. Mechanical interlock to prevent opening cabinet door with disconnect in
the “On” position or moving disconnect
to the “ON” position while the door is
open shall be provided.
4) Provisions shall be made for top entry of
incoming line power cables.

14. Heat Sink:

The heat sink shall be air cooled.
a. VFD Rating:
1) Drive shall be suitable for nameplate
voltage ±10%.

Guide specifications (cont)
303
Item5.
38 2) Drive shall be suitable for continuous
operation at 100% of nameplate amps
and 150% of nameplate amps for
3 seconds.
3) Drive shall comply with applicable UL,
CE, and NEMA standards.
4) Drive shall be suitable for operation in
ambient temperatures between 40 and
104°F (4.4 and 40°C), 95% humidity
(non-condensing) for altitudes up to
8250 ft (2500 m) above sea level; altitude derating applies after 1000 m.

Specific drive performance at jobsite
ambient temperature and elevation shall
be provided by manufacturer in the bid.
b. User Interface:

Displays shall provide interface for programming and display of VFD and chiller parameters. Viewable parameters include:
1) Operating, configuration, and fault
messages.
2) Frequency in hertz.
c. VFD Performance:
1) VFD full load efficiency shall meet or
exceed 97% at 100% VFD Rated
ampacity.
2) Displacement Input Power Factor shall
meet or exceed 94% soft start, linear
acceleration, coast to stop.
3) Base motor frequency shall be up to
480 Hz; adjustable frequency range
from 0 to 480 Hz.
d. Chiller Electrical Service (single point
power):
1) Chiller shall have input circuit breaker
with minimum 100,000 amp interrupt
capacity.
2) Chiller shall have standard 15 amp
branch oil pump circuit breaker to provide power for chiller oil pump. 3) Chiller shall have standard 3 kva control
power transformer with circuit breaker
to provide power for oil heater, VFD
controls and chiller controls.
4) The branch oil pump circuit breaker and
control power transformer shall be factory wired.
5) Input power shall be 380/480 vac,
±10 percent, 3 phase, 50/60 Hz,
±3 Hz.
e. Discrete Outputs:
115-v discrete contact outputs shall be provided for:
1) Circuit breaker shunt trip
2) Chilled water pump
3) Condenser water pump
4) Alarm status.
f. Analog Output:

An analog (4 to 20 mA) output for head
pressure reference shall be provided. This
signal shall be suitable to control a 2-way or
3-way water regulating valve in the condenser piping.
g. Protection — the following shall be supplied:
1) Under-voltage
2) Over voltage
3) Phase loss
4) Phase reversal
5) Ground fault
6) Phase unbalance protection
7) Single cycle voltage loss protection
8) Programmable auto restart after loss of
power
9) Motor overload protection (NEMA
Class 10)
10) Motor overtemperature protection.
h. VFD Testing:

VFD shall be factory mounted, wired and
tested on the chiller prior to shipment.

15. Unit-Mounted Variable Frequency Drive (VFD),
Active Front-End, Low Harmonic VFD (PowerFlex 755TL)
a. Design:
1) VFD is air-cooled, microprocessorbased, pulse width modulated (PWM) design.
2) Input and output power devices shall be
insulated gate bipolar transistors
(IGBTs).
3) Active rectifier shall convert incoming
voltage / frequency to DC voltage. Input
current and voltage shall be regulated.
4) Transistorized inverter and control regulator shall convert DC voltage to a sinusoidal PWM waveform. 5) Integrated chiller controls shall coordinate motor speed and guide vane position to optimize chiller performance over all chiller operating conditions.
6) Surge prevention and surge protection
algorithms shall take action to prevent
surge and move chiller operation away
from surge.
b. Enclosure:
1) Pre-painted unit mounted, NEMA 1
(IP20) or NEMA 12 (IP54) cabinet shall
include hinged, lockable doors and
removable lifting lugs.
2) VFD power modules shall have a short
circuit interrupt and withstand rating of
Guide specifications (cont)
304
Item5.
39 100,000 amps (35,000 amps for 575-v
units).
3) Provisions to padlock main disconnect
handle in the “Off” positions shall be
provided. Mechanical interlock to prevent opening cabinet door with disconnect in the “On” position or moving disconnect to the “On” position while
the door is open shall be provided.
4) Provisions shall be made for top entry of
incoming line power cables.
c. Heat Sink:

The heat sink shall be air cooled.
d. VFD Rating:
1) Drive shall be suitable for continuous
operation at nameplate voltage ±10%.
2) Drive shall be suitable for continuous
operation at 100% of nameplate amps
and 150% of nameplate amps for 3 sec.
3) Drive shall comply with applicable
ANSI, NEMA, UL, CE Standards.
4) Drive shall be suitable for operation in
ambient temperatures between 40 and
104°F (4.4 and 40°C), 95% humidity
(non-condensing) for altitudes up to
6000 ft (1829 m) above sea level. Derating required above 3300 ft (1000 m).

Specific drive performance at jobsite
ambient temperature and elevation shall
be provided by manufacturer in the bid.
e. User Interface:

A single display shall provide interface for
programming and display of VFD and chiller
parameters. Viewable parameters include:
1) Operating, configuration, and fault
messages
2) Frequency in Hz
3) Load and line side voltage and current
(at the VFD)
4) kW (line and load side)
5) IGBT temperatures
f. VFD Performance:
1) VFD voltage total harmonic distortion
(THD) and harmonic current total
demand distortion (TDD) shall not
exceed IEEE-519 requirements using
the VFD circuit breaker input terminals
as the point of common coupling (PCC).

Product will meet IEEE-519 requirements at input CB terminals. 2) VFD full load efficiency shall meet or
exceed 96% at 100% VFD rated
ampacity.
a) Active rectifier shall regulate unity displacement power factor to 0.99 or higher at full load.
b) Soft start, linear acceleration, coast to
stop.
c) Base motor frequency shall be up to
480 Hz. Adjustable frequency range
from 0 to 480 Hz.
g. VFD Electrical Service (single point power):
1) VFD shall have input circuit breaker with
minimum 65,000 amp interrupt capacity, 100,000 amp interrupt available. 2) VFD shall have standard 15 amp branch
circuit breaker to provide power for
chiller oil pump.
3) VFD shall have standard control power
transformer with circuit breaker to provide power for oil heater, VFD controls and chiller controls.
4) The branch oil pump circuit breaker and
control power transformer shall be factory wired.
5) Nameplate voltage shall range between
380 and 460 ±10%, 3 phase, 50/60
Hz ±2% Hz.
h. Discrete Outputs:
115-v discrete contact outputs shall be provided for field wired:
1) Chilled water pump
2) Condenser water pump
3) Alarm status
4) Tower fan low
5) Tower fan high
i. Analog Output:

An analog (4 to 20 mA) output for head
pressure reference shall be provided. This
signal shall be suitable to control a 2-way or
3-way water regulating valve in the condenser piping.
j. Protection (the following shall be supplied):
1) Under-voltage
2) Over voltage
3) Phase loss
4) Phase reversal
5) Ground fault
6) Phase unbalance protection
7) Single cycle voltage loss protection
8) Programmable auto restart after loss of
power
9) Motor overload protection
k. VFD Testing:

VFD shall be factory mounted, wired and
tested on the chiller prior to shipment.
l. VFD Certifications and Standards:
1) CE Standard including:
a) Low Voltage Directive
Guide specifications (cont)
305
Item5.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Pg 40 Catalog No. 04-52190040-01 Printed in U.S.A. Form 19MV-CLT-6PD Replaces: 19MV-CLT-5PD
Carrier Corporation • Syracuse, New York 13221 7-24
b) EMC Directive
c) Machinery Directive
d) Standards applied; EN 61800-3/
EN 61800-5-1
e) EMC Directive (2014/30/EU)
f) Low Voltage Directive (2014/35/EU)
g) RoHS Directive (2011/65/EU)
2) UL 61800-5-1 and 61800-5-2
3) cUL
4) UKCA (EMC, LVD, MD, RHoS).
5) TÜV and Rheinland Standards (with
Safe I/O) applied:
a) IEC 61508 PARTS 1…7
b) EN 61800-3 EN 61800-5-1
c) IEC 61800-5-2 EN
d) ISO 13849-1
e) IEC 62061
f) ISO 60204-1
g) Machinery Directive (2006/42/EC)
Guide specifications (cont)
306
Item5.

Part No: 241879 Rev. 4 Effective: 09-30-22 Replaces: 241879 Rev. 3 Page 1 of 4 Product Submittal for Hi Delta®- Type H
Heating Boiler
Models 992C-2342C
Location:

Contractor:

Gas Type: Natural Gas Propane
100% Factory fire-tested
Thermal efficiency: 84%
Versa IC® Controller with LCD display
Maximum setpoint: 220°F (104°C)
Maximum outlet temperature: 240°F (116°C)
Minimum non-condensing inlet temperature: 105°F (41°C)
Thermal shock proof heat exchanger
Limited 20-year thermal shock warranty
Limited 10-year heat exchanger warranty (closed-loop)
Full safety diagnostics with fault history
Polytuf powder-coated cabinet
No combustible floor shield required
Fan-assisted
Patented burner security blanket
Cascade up to 8 heaters – no external sequencer needed
Cascade in parallel or sequential modulation modes
SCAQMD Rule 1146.2 certified, Low NOx < 20 ppm
(992C-2002C)
Proudly assembled in the USA
Date:

Equipment Tags:

Model:

Prepared by:

Job:

Engineer:

Notes:

Indoor Outdoor
4/11/2025
H9-2002C
307
Item5.

Part No: 241879 Rev. 4 Effective: 09-30-22 Page 2 of 4
Product Submittal for Hi Delta®- Type H
Job:

Features and Options
Heat Exchanger
Q Headers
Glass-lined cast iron (standard)
A-1 Bronze (optional)
Q ASME H-Stamped; 160 PSIG MAWP
Q National Board registered
Q Fin tubing
Copper (standard)
A-3 Cupronickel
Q ASME steel tube sheet
Q Silicone high temp. O-rings
Q ASME Pressure relief valve
60 PSIG (standard)
____PSIG (optional)
Q T&P Gauge
Q Water connections
Left-hand (standard)
A-6 Right-hand
Power
Q 120V, 60Hz, 1Ø, Power supply
Q 120/24V, 60Hz, Transformer
Control
Q Versa IC® Integrated control
Q 100% Shutoff/lockout
Q Hot Surface Ignition (HSI)
Q Cascade up to 8 heaters
Q Parallel and sequential modulation cascade
modes
Q Water temperature sensors 10kΩ
(2 mtd, 3 loose, 1 well)
Q Ignition Module
3-Try (standard)
C-6 Single-try
Q Remote flame sensor
Q High limit, manual-reset, fixed 240°F (104°C)
Q On/off power switch
Q Flow switch
Q Blocked vent pressure switch
Q Low gas pressure switch, manual-reset
Q Combustion air proving switch
Q Programmable pump time delays
Q Pump outputs
• Boiler
• System–pilot duty
• DHW indirect–pilot duty
Q Enable/disable
Q LCD Display; status, fault and diagnostics
Q Modbus RTU BMS Port (Up to 115K baud rate, see
Manual 241515)
B-85 – BMS Gateway – BACnet MS/TP, BACnet
IP, N2 Metasys or Modbus TCP
B-86 – BMS Gateway – LonWorks
Q Cold water protection function
CWR Variable-speed pump
CWS Proportional valve
Gas Train
Q Manual gas shutoff valve(s)
Q Combo valve(s)
Q Firing mode
H8 3-Stage (model 992C only)
H9 4-Stage (models 1262C-2342C)
Q Fuel
Natural gas
Propane gas (minimum grade HD-5, excludes
model 2002C)
G-20 4" W.C. NAT supply pressure
Q Design Certified - ANSI Z21.13/CSA 4.9
Construction
Q Indoor/outdoor construction
Q Front controls enclosed
Q PolyTuf powder-coat finish CSA low-lead certified
(≤ .25% Lead)
Venting
Q Vent location
Top (standard)
D-14 Rear flue exhaust tee
Q Vent termination cap
D-11 Vent termination, outdoor
D-15 Vent termination, sidewall (Cat III)
Indoor, vertical (by others)
Q Combustion air
D-12 Barometric damper w/o thermoswitch
D-16 Air intake elbow
D-17 In-line filter kit (TruSeal only)
D-18 Boiler vent adapter (Cat III & IV)
D-19 Vent termination cap adapter (Cat III & IV)
D-20 Vent termination vertical (Cat I)
D-21* Truseal direct vent air intake
(factory-installed)
D-22* Truseal direct vent air intake
(field-installed) (*must be used with D-17 inline
filter kit)
D-23 Outdoor vent supports
D-37 Motorized combustion air damper
(field-installed)
Options
A-20 30 PSIG MAWP
B-32 Outdoor air sensor
B-65 Indirect tank aquastat control
E-5 Alarm with 4” bell
F-10 Low water cut-off, remote probe
I-1 Adj. high limit, auto-reset 240°F (115.6°C)
max
I-2 Adj. high limit, manual-reset, 240°F (115.6°C)
max
I-5 Adj. high limit, manual-reset, 200°F (93.3°C)
max
I-13 Adj. high limit, auto-reset, 200°F (93.3°C) max
M-1 Safety valve, motorized
M-10 Safety valve, solenoid
M-15 Gas vent valve (requires either M-1 or M-10)
P__ Pump:______HP, 120V, 1Ø, 60Hz
Bronze Cast Iron
Mounted Loose
Front Rear
S-2 High gas pressure switch, manual-reset
X-1 SureRack® Kit
X-2 SureRack Add-on
X-3 SureRack restraint brackets
Z-4 T&P relief valve
Z-9 Thermometer
_________________________
Additional Options or Accessories
________________________________
Multi-Boiler Temperature Controllers
TempTracker Mod+ Hybrid
B-36, 2-4 Heaters
B-37, 5-10 Heaters
B-38, 11-16 Heaters
B-39* EMS 4-20 mA remote setpoint interface
module
B-62* BACnet MS/TP Interface
(*requires B-36 to B-38)

1.5 X G-12 CAL CODE/S-1 LOW GAS SAFETY
X B-31WELLASSEMBLY/P-29CWASVALVE
308
Item5.

Part No: 241879 Rev. 4 Effective: 09-30-22 Page 3 of 4
Product Submittal for Hi Delta®- Type H
Job:

SPECIFICATIONS
Model
MBTUH (kW) Dimensions - Inches (mm)
Input Output Firing
Stages A Width Flue CollarK W Amp. Draw*
Approx. Shipping
Wt. Lbs. (Kg)
992C
990
(290)
832
(244) 3 57-1/8 (1451)
10 (254)
16-13/16
(427) <12 900 (408)
1262C
1260
(369)
1058
(310) 4 68-1/2 (1740)
12 (305)
20-9/16
(522) <12 1010 (458)
1532C
1530
(448)
1285
(377) 4 79-7/8 (2029)
12 (305)
24-3/8
(619) <12 1225 (556)
1802C
1800
(528)
1512
(443) 4 91-1/8 (2315)
14 (356)
28-1/8
(714) <12 1350 (612)
2002C
1999
(586)
1679
(492) 4 102-1/2 (2604)
14 (356)
31-15/16
(811) <12 1450 (658)
2072C
2070
(607)
1739
(510) 4 102-1/2 (2604)
14 (356)
31-15/16
(811) <12 1450 (658)
2342C
2340
(686)
1966
(576) 4 113-7/8 (2892)
16 (406)
35-11/16
(902) <12 1520 (689)
*Without pump
NOTES:

1.Rates shown are for natural or propane gas, and elevations up to 4,500 feet (1372 m). De-rate above 4,500 ft.

2.Required natural gas pressure is 5.6" – 10.5” (178 - 267) WC. Required propane gas pressure is 11 - 13” (279 - 330) WC. 309
Item5.

Part No: 241879 Rev. 4 Effective: 09-30-22 Page 4 of 4
Product Submittal for Hi Delta®- Type H
Job:

RATES OF FLOW AND PRESSURE DROPS
Model
20°F ΔT 30°F ΔT Minimum Flow Maximum Flow*
GPM
(L/min) ΔP (FT.) GPM
(L/min) ΔP (FT.) GPM(L/min) ΔP (FT.) ΔT
ºF (ºC)
GPM
(L/min) ΔP (FT.) ΔT
ºF (ºC)
992C
84 (318) 5.6 56 (212) 2.5 43 (163) 1.5 39 (21.6)
132
(500) 14 13 (7.2)
1262C
107
(406) 10 71(269) 4.5 54 (205) 2.6 39 (21.6)
132
(500) 15.5 16 (8.8)
1532C
130
(493) 16 86 (326) 7.1 66 (250) 4.1 39 (21.6)
132
(500) 16.5 20 (11.1)
1802C
102
(387) 10.8 78 (296) 6 39 (21.6)
132
(500) 18 23 (12.7)
2002C
113
(428) 14 86 (326) 8.1 39 (21.6)
132
(500) 19.5 26 (14.4)
2072C
117
(443) 15 89 (337) 8.7 39 (21.6)
132
(500) 19.5 27 (14.9)
2342C
132
(500) 21 101 (383) 12 39 (21.6)
132
(500) 21 30 (16.6)
*Basis is 40°F ΔT for minimum flow, 132 GPM for maximum flow.

Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 www.raypak.com ■
310
Item5.

Outdoor Unit Heat Pump Ductless System
Outdoor Model: 37MARAQ24AA3
Job Data: Location:

Tag #: Carrier#:

Date:

NOTE: Images for illustration purposes only. Actual models may be slightly different.

Outdoor - Heat Pump
37MARAQ24AA3
24000
Voltage, Phase, Cycle V/Ph/Hz 208-230/1/60
MCA A. 24
MOPA A. 25
SCCR kA 5
Cooling Outdoor DB Min - Max °F(°C) -13~122(-25~50)
Heating Outdoor DB Min - Max °F(°C) -13~75(-25~24)
Min. Piping Length ft (m) 9.8 (3)
Standard Piping Length ft. (m) 24.6 (7.5)
Total Piping Length ft (m) 164.04(50)
Piping Lift*
ft (m) 82.02(25)
Pipe Connection Size - Liquid in (mm) 3/8in(9.52mm)
Pipe Connection Size - Suction in (mm) 5/8in(15.9mm)
R454B
Charge lbs (kg) 4.41(2.0)
Add'l Refrigerant (between Std & Max
Piping Lengths)
Oz/ft
(g/m) 0.32(30)
Capacity Unit W D H L1 L2 Face Area Sq. Ft. 8.18
mm 765 303 555 452.4 313.82 2.6
inch 30.12 11.93 21.85 17.81 12.36 20
mm 890 342 673 663 379.59 6
inch 35.04 13.46 26.5 26.1 14.94 ROTARY
mm 946 410 810 672.96 454.8 KTM240D46UKT2
inch 37.24 16.14 31.89 26.49 17.19 ESTER OIL
Oil Charge Fl. Oz. 20.97
Rated Current RLA 1.05
Airflow CFM 2237.9
Sound Pressure dB(A) 58
Height in (mm) 31.89(810)
Width in (mm) 37.24(946)
Depth in (mm) 16.14(410)
Net Weight lbs (kg) 122.14(55.4)
Shipping Height in (mm) 34.84(885)
Shipping Width in (mm) 42.91(1090)
Shipping Depth in (mm) 19.68(500)
Shipping Net Weight lbs (kg) 132.28(60)
* Condensing unit above or below indoor unit
9K/12K
18K
24K ~ 36K
Outdoor Size
Outdoor Model #
Refrigerant
System
Electrical
Operating Range
Refrigerant Type

OUTDOOR STANDARD FEATURES
• Variable Speed (Inverter)
• Factory installed Base Pan Heater
• Factory installed Crankcase Heater
• Low Voltage Controls
• Auto-Restart function
• Condenser High Temp Protection
• Quiet operation
• Anti-corrosive fin coating
RESIDENTIAL APPLICATION LIMITED WARRANTY*
• Ten (10) years if properly registered within ninety (90) days after original installation, parts are warranted to the original purchaser for a period of ten (10) years. Otherwise, parts warranty is five (5) years.

Piping

OUTDOOR UNIT DIMENSIONS
Dimensions
No. Rows
Fins per inch
Circuits
Type
Model
Outdoor Coil
Compressor
Airflow & Sound
Oil Type
Carrier Corporation Copyright 2024 • Atlanta, GA, 30339

SUBJECT TO CHANGE WITHOUT NOTICE
311
Item5.

High Wall Heat Pump Ductless System
Indoor Model:

Job Data: Location:

Tag #: Carrier#:

Date:

NOTE: Images for illustration purposes only. Actual models may be slightly different. 45MAHAQ24XA3
45MAHAQ24XA3
24000
Voltage, Phase, Cycle V/Ph/Hz 208/230-1-60
Power Supply
MCA A. 3
Cooling Indoor DB Min - Max °F(°C) 60~90(16~32)
Heating Indoor DB Min - Max °F(°C) 32~86(0~30)
Face Area Sq. Ft. 3.6
3 20
7 1000/850/630
Airflow (highest to lowest) CFM 812.3 / 618.0 / 412.0 / 317.8 / / Sound Pressure (highest to lowest) dB(A) 54.5/43.5/38.5/27/16 Moisture Removal L/h 2.7
Air Throw Data ft(m) 30.1(9.18)
Height in (mm) 14.57(370)
Capacity Unit W D H Width in (mm) 44.88(1140)
mm 795 225 295 Depth in (mm) 10.83(275)
inch 31.3 8.86 11.61 Net Weight lbs (kg) 43.65(19.8)
mm 965 239 319 Shipping Height in (mm) 13.98(355)
inch 37.99 9.41 12.56 Shipping Width in (mm) 48.43(1230) mm 1140 275 370 Shipping Depth in (mm) 17.91(455)
inch 44.88 10.83 14.57 Shipping Net Weight lbs (kg) 55.56(25.2)

CONTROLS
Standard
KSACN1401AAA
KSACN1201AAA
KSAIF0701AAA
KSAIC0601230
Wired Remote Control with Timer Function
Wi-Fi™ Kit High Wall
Dimensions
24V Mini Interface
Optional
Wired Remote Control 7 Day Programmable
Wireless Remote Controller (°F/°C Convertible)
45MAHAQ24XA3
Operating Range
Indoor Coil
Indoor Unit
Circuits
Fins per inch

INDOOR STANDARD FEATURES
• Modes: Cool, Heat, Dry, Fan, Auto
• Four fan speeds
• Sleep Mode
• Turbo Mode
• Follow Me (senses temperature at handheld remote)
• Auto-Restart function
• Quiet indoor operation
• Anti-corrosive fin coating
RESIDENTIAL APPLICATION LIMITED WARRANTY*
• Ten (10) years if properly registered within ninety (90) days after original installation, parts are warranted to the original purchaser for a period of ten (10) years. Otherwise, parts warranty is five (5) years.

Indoor Model #
System
Indoor Size
6K/9K/12K
Number of Fan Speeds
Indoor unit powered by outdoor unit
18K
24K ~ 36K

INDOOR UNIT DIMENSIONS
Electrical
No. Rows
Carrier Corporation Copyright 2024 • Atlanta, GA, 30339

SUBJECT TO CHANGE WITHOUT NOTICE
312
Item5.

SUBMITTAL
Project
Climatec - City of Esc - City Hall
Date
Saturday, April 12, 2025
Shawn Harlan
Sigler - Brea
205 Puente Street
Brea CA
313
Item5.

Table Of Contents
Project: Climatec - City of Esc - City Hall 04/13/2025
Prepared By: Shawn Harlan 09:04AM
ID 3,16 3
Unit Report 4
Certified Drawing 5
Performance Summary 8
ID 14 11
Unit Report 12
Performance Summary 13
System Parameters 13
Electrical Data 13
Acoustic Summary 14
Certified Drawing 15
Packaged Rooftop Builder 1.79i Page 2 of 17314
Item5.

ID 3,16
Project: Climatec - City of Esc - City Hall 04/13/2025
Prepared By: Shawn Harlan 09:04AM
ID 3,16
ID 3,16
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 3 of 17 315
Item5.

Unit Report For ID 3,16
Project: Climatec - City of Esc - City Hall 04/13/2025
Prepared By: Shawn Harlan 09:04AM
Unit Report
Unit Parameters
Unit Model: 50FEQM12A2M6-0A0A0
Unit Size: 12 (10 Tons)
Volts-Phase-Hertz: 460-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two-Stage Cooling, Single Circuit
Duct Cfg: Horizontal Supply / Horizontal Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 7' 4.125''
Unit Width: 4' 11.5''
Unit Height: 4' 1.375''
Total Operating Weight: 972 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 4
Return Air Filter Size: 20 x 20 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
1-Year parts (STD.)
5-Year Compressor (std.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50FEQM12A2M6-0A0A0 Rooftop Unit 1
Field Installed Accessories
CRWINSTR001A00 Winter Start Package 1
Packaged Rooftop Builder 1.79i Page 4 of 17 316
Item5.

Certified Drawing for ID 3,16
Project: Climatec - City of Esc - City Hall 04/13/2025
Prepared By: Shawn Harlan 09:04AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 5 of 17 317
Item5.

Certified Drawing for ID 3,16
Project: Climatec - City of Esc - City Hall 04/13/2025
Prepared By: Shawn Harlan 09:04AM
Packaged Rooftop Builder 1.79i Page 6 of 17 318
Item5.

Certified Drawing for ID 3,16
Project: Climatec - City of Esc - City Hall 04/13/2025
Prepared By: Shawn Harlan 09:04AM
Packaged Rooftop Builder 1.79i Page 7 of 17 319
Item5.

Performance Summary For ID 3,16
Project: Climatec - City of Esc - City Hall 04/13/2025
Prepared By: Shawn Harlan 09:04AM
Performance Summary
Part Number:50FEQM12A2M6-0A0A0
Refrigerant: R-454B
ARI EER: 11.00
Application EER (Rooftop Unit only): 11.07
IEER: 15.0
Base Unit Dimensions
Unit Length: 88.1 in
Unit Width: 59.5 in
Unit Height: 49.4 in
Operating Weight
Base Unit Weight: 955 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 16 lb
Accessories
Winter Start Package: 1 lb
Total Operating Weight: 972 lb
Unit
Unit Voltage-Phase-Hertz: 460-3-60
Air Discharge: Horizontal
Fan Drive Type: Vane Axial
Actual Airflow: 4000 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 57.6 F
Evaporator Leaving Air WB: 56.9 F
Evaporator Leaving Air Enthalpy: 24.35 BTU/lb
Unit Discharge Air DB: 58.8 F
Unit Discharge Air WB: 57.4 F
Unit Discharge Air Enthalpy: 24.62 BTU/lb
Gross Cooling Capacity: 127.67 MBH
Net Cooling Capacity: 122.65 MBH
Gross Sensible Capacity: 96.60 MBH
Net Sensible Capacity: 91.58 MBH
Compressor Power Input: 9.01 kW
Coil Bypass Factor: 0.041
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 96.4 F
Total Heating Capacity: 113.90 MBH
Integrated Heating Capacity: 113.90 MBH
Heating Power Input: 9.40 kW
High Temperature COP: 3.40
Low Temperature COP: 2.25
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 1716
Fan Power: 1.72 BHP
NOTE: Selected IFM RPM Range: 1100 - 2000
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Packaged Rooftop Builder 1.79i Page 8 of 17320
Item5.

Performance Summary For ID 3,16
Project: Climatec - City of Esc - City Hall 04/13/2025
Prepared By: Shawn Harlan 09:04AM
Electrical Data
Voltage Range: 414 - 506
Compressor #1 RLA: 8.3
Compressor #1 LRA: 58
Compressor #2 RLA: 8.3
Compressor #2 LRA: 58
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 3
Power Supply MCA: 30
Power Supply MOCP (Fuse or HACR): 35
Disconnect Size FLA: 31
Disconnect Size LRA: 127
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 7.4
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 91.6 53.3 88.1
125 Hz 86.7 81.0 90.0
250 Hz 82.0 75.5 85.9
500 Hz 79.7 72.0 83.0
1000 Hz 80.8 71.1 81.6
2000 Hz 77.4 65.8 78.5
4000 Hz 71.7 56.3 76.4
8000 Hz 63.6 49.1 75.5
A-Weighted 84.7 75.3 87.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Packaged Rooftop Builder 1.79i Page 9 of 17321
Item5.

Performance Summary For ID 3,16
Project: Climatec - City of Esc - City Hall 04/13/2025
Prepared By: Shawn Harlan 09:04AM
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 88.1 90.0 85.9 83.0 81.6 78.5 76.4 75.5 94.0 Lw
B 61.9 73.9 77.3 79.8 81.6 79.7 77.4 74.4 87.0 LwA
C 55.7 57.6 53.5 50.6 49.2 46.1 44.0 43.1 61.6 Lp
D 29.5 41.5 44.9 47.4 49.2 47.3 45.0 42.0 54.6 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 600 RPM
800 RPM
1000 RPM
1200 RPM
1400 RPM
1600 RPM 1800 RPM 2000 RPM
2200 RPM

0.75 BHP

1.00 BHP

1.50 BHP

2.00 BHP

3.00 BHP

5.00 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 1716 BHP = 1.72 Maximum RPM = 2200 Maximum BHP = 5.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0

0.0 0.5

1.0 1.5

2.0 Packaged Rooftop Builder 1.79i Page 10 of 17322
Item5.

ID 14
Project: Climatec - City of Esc - City Hall 04/13/2025
Prepared By: Shawn Harlan
ID 14
ID 14
Submittal Cover Sheet
Unit Report
Performance Summary Report
Acoustic Summary
Certified Drawings
Residential Carrier Products Bldr 1.39j Page 11 of 17323 Item5.

Unit Report For ID 14
Project: Climatec - City of Esc - City Hall 04/13/2025
Prepared By: Shawn Harlan
Unit Report
Outdoor Unit Parameters
Unit Model: 27SCA
Unit Size: 2 Tons (Size 24)
Voltage: 208/230-1-60 V-Ph-Hz
Indoor Coil Parameters
Unit Model: FT5A
Unit Size: 24,000 Btuh
Cabinet Insulation: Singular, TXV
Voltage: 208-1-60 V-Ph-Hz
Refrigerant Type: Puron Advance
Heating Size: No Heat
Outdoor Unit Dimensions and Weight
Unit Length: 31.1875 in
Unit Width: 31.1875 in
Unit Height: 35.5 in
Unit Shipping Weight: 196. lb
Indoor Coil Dimensions and Weight
Unit Length: 22.06 in
Unit Width: 17.6 in
Unit Height: 42.69 in
Unit Shipping Weight: 124. lb

RESIDENTIAL APPLICATIONS
This warranty is to the original purchasing owner and subsequent owners only to the extent and as stated in the Warranty Conditions and below.

The limited warranty period in years, depending on the part and the claimant, is as shown in the table below.

Limited Warranty (Years)
Item Original Owner Subsequent Owner
Parts 10* (or 5) 5
Compressor 10* (or 5) 5
*If properly registered within 90 days of original installation, otherwise 5 years (except in California and Quebec and other jurisdictions that prohibit warranty benefits conditioned on registration). See Warranty Conditions below.

OTHER APPLICATIONS
The warranty period is five (5) years on the compressor, and one (1) year on all other parts. The warranty is the original owner only and is not available for subsequent owners.

Ordering Information
Part Number Description Quantity
Outdoor Unit
27SCA524A003 27SCA Comfort Single Stage Heat Pump with Puron Refrigerant Advanced 2 Tons Cooling
1 15 SEER @ ARI Conditions
Indoor Coil
FT5ANXB24L00 Performance Series Fan Coil with Puron Advance 208/230-1-60 1 Singular, TXV
Aluminum
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 12 of 17
324
Item5.

Performance Summary For ID 14
Project: Climatec - City of Esc - City Hall 04/13/2025
Prepared By: Shawn Harlan
Performance Summary
System Performance
System: 27SCA/FT5A
System Quantity: 1
Altitude: 0.0 ft
Linear Pipe Length: 0.0 ft
COP @ 47 F: 3.88
COP @ 17 F: 2.62
SEER @ ARI Conditions: 15.5
EER @ ARI Conditions: 12.0
HSPF @ ARI Conditions: 7.8
Actual Clg Airflow: 800.0 CFM
Standard Clg Airflow: 800.0 CFM
Total Net Clg Capacity: 22.81 MBH
Net Sensible Clg Capacity: 17.23 MBH
Htg HP Capacity: 24.06 MBH
Htg HP Integrated Capacity: 24.06 MBH
Heating HP Compressor Power: 1.73 kW
Total System Power: 2.41 kW
System Parameters
System Parameters
Outdoor Unit Parameters
Unit Model: 27SCA524A003
Unit Size (Nominal): 2 Tons (Size 24)
Voltage: 208/230-1-60 V-Ph-Hz
Clg Ent Air DB Ambient: 95.0 °F
Htg Ent Air DB Ambient: 47.0 °F
Indoor Coil Parameters
Unit Model: FT5ANXB24L00
Unit Size (Nominal): 24,000 Btuh
Voltage: 208-1-60 V-Ph-Hz
Ent Air DB: 80.00 °F
Ent Air WB: 67.00 °F
Ent Enthalpy: 31.44 BTU/lb
Lvg Air DB: 60.05 °F
Lvg Air WB: 58.11 °F
Lvg Enthalpy: 25.10 BTU/lb
Htg Ent Air DB: 70.0 °F
Htg Lvg Air DB: 97.8 °F
Heating Size (Nominal): No Heat
Total External Static Pressure: 0.50 in wg
Electrical Data
Electrical Data
Outdoor Electrical Data
Unit Voltage: 208/230-1-60 V-Ph-Hz
Fan Motor FLA: 0.60 Amps
MCA: 13.5 Amps
Max Fuse: 20 Amps
Operating Range Min: 197 V
Operating Range Max: 253 V
Compressor RLA: 10.3 Amps
Compressor LRA: 64.4 Amps
Indoor Electrical Data:
(For units with no factory installed electric heaters)
Unit Voltage: 208-1-60 V-Ph-Hz
Unit FLA: 4.0 Amps
Unit MCA: 5.0 Amps
Unit MOCP: 15.0 Amps
Unit Min Wire Size: 14.0
Unit Fuse/Ckt Bkr Amps: 15.0 Amps
Motor HP: 1/2 HP
Notice: Indoor Elect. data is for 208-1-60 voltage
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 13 of 17325 Item5.

Acoustic Summary For ID 14
Project: Climatec - City of Esc - City Hall 04/13/2025
Prepared By: Shawn Harlan
Acoustic Summary
Outdoor Unit Parameters:

Unit Model: 27SCA
Unit Size: 2 Tons (Size 24)
Variations: Standard
Octave Band Center Frequency, Hz 125 250 500 1k 2k 4k 8k dBA Sound Power,dB 66.3 64.7 64.2 64.4 59.2 55.6 54.7
A-Weighted Sound Power, dBA 71.0
Indoor Coil Parameters:

Unit Model: FT5A
Unit Size: 24,000 Btuh
Cabinet Insulation: Singular, TXV
Octave Band Center Frequency, Hz 63 125 250 500 1k 2k 4k Sound Power,dB 72.0 68.0 64.0 61.0 59.0 57.0 53.0
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 14 of 17326 Item5.

Certified Drawing For ID 14
Project: Climatec - City of Esc - City Hall 04/13/2025
Prepared By: Shawn Harlan
Certified Drawing
Outdoor Model
Unit Model: 27SCA
Unit Size: 2 Tons (Size 24)
Voltage: 208/230-1-60 V-Ph-Hz
SEER: 15
PartNumber: 27SCA524A003
Shipping Dimensions and Weights Outdoor Unit
Height 39.81 in
Width 34.25 in
Length 34.25 in
Operating Weight 176. lb
Shipping Weight 196. lb
Dimensions

A B C D E F G H I J K

31.19 in 35.50 in 0.63 in 6.56 in 24.69 in 9.13 in 1.13 in 3.81 in 13.00 in 15.13 in 16.50 in The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 15 of 17327 Item5.

Certified Drawing For ID 14
Project: Climatec - City of Esc - City Hall 04/13/2025
Prepared By: Shawn Harlan
Indoor Coil
Unit Model: FT5A
Unit Size: 24,000 Btuh
Voltage: 208-1-60 V-Ph-Hz
Cabinet Insulation: Singular, TXV
PartNumber: FT5ANXB24L00
Dimensions and Weights Indoor Coil
Height 42.69 in
Width 17.63 in
Length 22.06 in
Shipping Weight 124. lb
Dimensions

A B C D E F G H J

42.69 in 17.63 in 15.75 in 15.63 in 10.75 in 18.56 in 18.25 in -- -- The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 16 of 17328 Item5.

Certified Drawing For ID 14
Project: Climatec - City of Esc - City Hall 04/13/2025
Prepared By: Shawn Harlan
Indoor Coil
Unit Model: FT5A
Unit Size: 24,000 Btuh
Voltage: 208-1-60 V-Ph-Hz
PartNumber: FT5ANXB24L00
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 17 of 17329 Item5.

SUBMITTAL
Project
Climatec - City of Esc - City Hall
Date
Saturday, April 12, 2025
Shawn Harlan
Sigler - Brea
205 Puente Street
Brea CA
330
Item5.

Table Of Contents
Project: Climatec - City of Esc - City Hall 04/12/2025
Prepared By: Shawn Harlan 04:29PM
ID 3,16 3
Unit Report 4
Certified Drawing 5
Performance Summary 8
Packaged Rooftop Builder 1.79i Page 2 of 10331
Item5.

ID 3,16
Project: Climatec - City of Esc - City Hall 04/12/2025
Prepared By: Shawn Harlan 04:29PM
ID 3,16
ID 3,16
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 3 of 10 332
Item5.

Unit Report For ID 3,16
Project: Climatec - City of Esc - City Hall 04/12/2025
Prepared By: Shawn Harlan 04:29PM
Unit Report
Unit Parameters
Unit Model: 50FEQM12A2M6-0A0A0
Unit Size: 12 (10 Tons)
Volts-Phase-Hertz: 460-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two-Stage Cooling, Single Circuit
Duct Cfg: Horizontal Supply / Horizontal Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 7' 4.125''
Unit Width: 4' 11.5''
Unit Height: 4' 1.375''
Total Operating Weight: 972 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 4
Return Air Filter Size: 20 x 20 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
1-Year parts (STD.)
5-Year Compressor (std.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50FEQM12A2M6-0A0A0 Rooftop Unit 1
Field Installed Accessories
CRWINSTR001A00 Winter Start Package 1
Packaged Rooftop Builder 1.79i Page 4 of 10 333
Item5.

Certified Drawing for ID 3,16
Project: Climatec - City of Esc - City Hall 04/12/2025
Prepared By: Shawn Harlan 04:29PM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 5 of 10 334
Item5.

Certified Drawing for ID 3,16
Project: Climatec - City of Esc - City Hall 04/12/2025
Prepared By: Shawn Harlan 04:29PM
Packaged Rooftop Builder 1.79i Page 6 of 10 335
Item5.

Certified Drawing for ID 3,16
Project: Climatec - City of Esc - City Hall 04/12/2025
Prepared By: Shawn Harlan 04:29PM
Packaged Rooftop Builder 1.79i Page 7 of 10 336
Item5.

Performance Summary For ID 3,16
Project: Climatec - City of Esc - City Hall 04/12/2025
Prepared By: Shawn Harlan 04:29PM
Performance Summary
Part Number:50FEQM12A2M6-0A0A0
Refrigerant: R-454B
ARI EER: 11.00
Application EER (Rooftop Unit only): 11.07
IEER: 15.0
Base Unit Dimensions
Unit Length: 88.1 in
Unit Width: 59.5 in
Unit Height: 49.4 in
Operating Weight
Base Unit Weight: 955 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 16 lb
Accessories
Winter Start Package: 1 lb
Total Operating Weight: 972 lb
Unit
Unit Voltage-Phase-Hertz: 460-3-60
Air Discharge: Horizontal
Fan Drive Type: Vane Axial
Actual Airflow: 4000 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 57.6 F
Evaporator Leaving Air WB: 56.9 F
Evaporator Leaving Air Enthalpy: 24.35 BTU/lb
Unit Discharge Air DB: 58.8 F
Unit Discharge Air WB: 57.4 F
Unit Discharge Air Enthalpy: 24.62 BTU/lb
Gross Cooling Capacity: 127.67 MBH
Net Cooling Capacity: 122.65 MBH
Gross Sensible Capacity: 96.60 MBH
Net Sensible Capacity: 91.58 MBH
Compressor Power Input: 9.01 kW
Coil Bypass Factor: 0.041
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 96.4 F
Total Heating Capacity: 113.90 MBH
Integrated Heating Capacity: 113.90 MBH
Heating Power Input: 9.40 kW
High Temperature COP: 3.40
Low Temperature COP: 2.25
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 1716
Fan Power: 1.72 BHP
NOTE: Selected IFM RPM Range: 1100 - 2000
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Packaged Rooftop Builder 1.79i Page 8 of 10 337
Item5.

Performance Summary For ID 3,16
Project: Climatec - City of Esc - City Hall 04/12/2025
Prepared By: Shawn Harlan 04:29PM
Electrical Data
Voltage Range: 414 - 506
Compressor #1 RLA: 8.3
Compressor #1 LRA: 58
Compressor #2 RLA: 8.3
Compressor #2 LRA: 58
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 3
Power Supply MCA: 30
Power Supply MOCP (Fuse or HACR): 35
Disconnect Size FLA: 31
Disconnect Size LRA: 127
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 7.4
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 91.6 53.3 88.1
125 Hz 86.7 81.0 90.0
250 Hz 82.0 75.5 85.9
500 Hz 79.7 72.0 83.0
1000 Hz 80.8 71.1 81.6
2000 Hz 77.4 65.8 78.5
4000 Hz 71.7 56.3 76.4
8000 Hz 63.6 49.1 75.5
A-Weighted 84.7 75.3 87.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Packaged Rooftop Builder 1.79i Page 9 of 10 338
Item5.

Performance Summary For ID 3,16
Project: Climatec - City of Esc - City Hall 04/12/2025
Prepared By: Shawn Harlan 04:29PM
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 88.1 90.0 85.9 83.0 81.6 78.5 76.4 75.5 94.0 Lw
B 61.9 73.9 77.3 79.8 81.6 79.7 77.4 74.4 87.0 LwA
C 55.7 57.6 53.5 50.6 49.2 46.1 44.0 43.1 61.6 Lp
D 29.5 41.5 44.9 47.4 49.2 47.3 45.0 42.0 54.6 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 600 RPM
800 RPM
1000 RPM
1200 RPM
1400 RPM
1600 RPM 1800 RPM 2000 RPM
2200 RPM

0.75 BHP

1.00 BHP

1.50 BHP

2.00 BHP

3.00 BHP

5.00 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 1716 BHP = 1.72 Maximum RPM = 2200 Maximum BHP = 5.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0

0.0 0.5

1.0 1.5

2.0 Packaged Rooftop Builder 1.79i Page 10 of 10 339
Item5.

Submitted by: Shawn Harlan
Cover Sheet
Project Name: Climatec - City of Escondido City Hall Air Cooled Chiller Tag Name: ID 10
Date: 4/12/2025

Page 1340 ends

Item5.

Submitted by: Shawn Harlan
Unit Report
Project Name:

Climatec - City of Escondido City Hall Air Cooled Chiller Tag Name:

ID 10
Tag Name: ID 10
30RC Air Cooled Scroll Chiller
Unit Information
Model Number 30RC-04066-4---23
Unit Quantity 1
Condenser Type Air Cooled
Compressor Type Digital Scroll (Includes Sound Blankets) Communication CCN, BACnet IP & BACnet MS/TP
Manufacturing Source Charlotte, USA
ASHRAE 90.1 2007, 2010, 2013/2016, 2019
Refrigerant Type R-32
Independent Refrigerant Circuits 2
Rigging Weight lb 2304
Operating Weight lb 2384
Refrigerant Weight lb 41
Unit Dimensions (L x W x H) in 95 x 88 x 66
Baserail Dimensions (L x W) in 95 x 88
Chiller Warranty Information (Note: for US and Canada only) Warranty
First year - Parts only (standard)
Complete Unit Year 2 Parts & Labor
Unit Startups
Startup
Start-up & Complete Unit 1st Year Labor, 1st Unit
Extended Leadtime Options
No R-Quotes Specied
Ordering Information
Part Number Description Quantity
Base Unit 1

4.3" Control Panel Colored Display
BACnet IP & BACnet MS/TP
Energy Management Module
Evaporator Heater (Freeze Protection)
10 kA SCCR
Suction Line Insulation
Digital Scroll Compressor (Includes Sound Blankets)
Al/Cu Condenser Coil
Greenspeed Intelligence: High-Eciency Variable Condenser Fans Terminal Block
Brazed Plate Heat Exchanger (BPHE)
Single Point Power
Full Hail Guards
Low Sound - Includes Aero-Acoustic Fans
30RC-04066-4---23 30RC Air Cooled Scroll Chiller
Created on 4/12/2025 4:40:15 PM
Package Chillers NAO v1.7.0.0

Page 2341 ends

Item5.

Submitted by: Shawn Harlan
Performance Report
Project Name:

Climatec - City of Escondido City Hall Air Cooled Chiller Tag Name:

ID 10
Tag Name: ID 10
30RC Air Cooled Scroll Chiller
Non Contractual Picture
Unit Information
Model Number 30RC-04066-4---23
Unit Quantity 1
Condenser Type Air Cooled
Compressor Type Digital Scroll (Includes Sound
Blankets)
Communication CCN, BACnet IP & BACnet MS/TP
Manufacturing Source Charlotte, USA
ASHRAE 90.1 2007, 2010, 2013/2016, 2019
Refrigerant Type R-32
Independent Refrigerant Circuits 2
Rigging Weight lb 2304
Operating Weight lb 2384
Refrigerant Weight lb 41
Unit Dimensions (L x W x H) in 95 x 88 x 66
Baserail Dimensions (L x W) in 95 x 88
Unit Features

4.3" Control Panel Colored Display
BACnet IP & BACnet MS/TP
Energy Management Module
Evaporator Heater (Freeze Protection)
10 kA SCCR
Suction Line Insulation
Digital Scroll Compressor (Includes Sound Blankets)
Al/Cu Condenser Coil
Greenspeed Intelligence: High-Eciency Variable Condenser Fans Terminal Block
Brazed Plate Heat Exchanger (BPHE)
Single Point Power
Full Hail Guards
Low Sound - Includes Aero-Acoustic Fans
Operating Conditions
Evaporator Brazed Plate Heat Exchanger (BPHE)
Fluid Type Fresh Water
Fluid Concentration % 0
Fluid Volume gal 7.20
Fouling Factor (hr-sqft-F)/BTU 0.000100
Leaving Fluid Temperature °F 44.00
Entering Fluid Temperature °F 54.00
Fluid Flow gpm 92.30
Min. Fluid Flow gpm 49.93
Min. Part Load Fluid Flow gpm 35.95
Pressure Drop ft wg 3.34
Condenser Al/Cu Condenser Coil
Entering Air Temperature °F 95.0
Min. Outdoor Operating Temp °F -20.0
Number of Fans 3
Total Condenser Fan Airow CFM 33221
Altitude ft 0
Performance Information
Cooling Capacity Tons 38.58
Chiller Pressure Drop ft wg 10
Total Compressor Power kW 42.95
Total Fan Motor Power kW 3.937
Total Unit Power (without pump) kW 46.89
Minimum Capacity % 9
Capacity Control Steps 44
Cooling Eciency (EER) BTU/(W-hr) 9.874
IPLV.IP BTU/(W-hr) 16.14
Electrical Information
Unit Voltage 460-3-60
Electrical Connection Single Point Power
SCCR 10 kA SCCR
Minimum Voltage V 414
Maximum Voltage V 506
Nominal Voltage V 460
MCA A 90.11
MOCP A 110.0
ICF A 209.7
RecFuse Size A 100.0
Created on 4/12/2025 4:40:15 PM
Package Chillers NAO v1.7.0.0

Page 3342 ends

Item5.

Submitted by: Shawn Harlan
Performance Report
Project Name:

Climatec - City of Escondido City Hall Air Cooled Chiller Tag Name:

ID 10
Integrated Part Load Value (AHRI)
IPLV.IP BTU/(W-hr) 16.14
Unit Performance
Percent Full Load Capacity % 100.0 75.0 50.0 25.0
Percent Full Load Power % 100.0 53.1 28.5 12.3
Cooling Capacity Tons 38.58 28.94 19.29 9.646
Unit Power Input kW 46.89 24.91 13.38 5.789
Cooling Eciency
(EER)
BTU/(W-hr) 9.874 13.94 17.30 19.99
Evaporator Data
Fluid Entering Temperature °F 54.00 51.50 49.00 46.50
Fluid Leaving Temperature °F 44.00 44.00 44.00 44.00
Fluid Flow Rate gpm 92.30 92.30 92.30 92.30
Fouling Factor (hr-sqft-F)/BTU 0.000100 0.000100 0.000100 0.000100 Pressure Drop ft wg 10 9.2 8.46 7.81
Condenser Data
Entering Air Temperature °F 95.0 80.0 65.0 55.0
Values given are interpolated and are not directly measurable under laboratory conditions Created on 4/12/2025 4:40:15 PM
Package Chillers NAO v1.7.0.0 Page 4343
Item5.

Submitted by: Shawn Harlan
Acoustic Report
Project Name:

Climatec - City of Escondido City Hall Air Cooled Chiller Tag Name:

ID 10
A-weighted Sound Power Levels
Octave Band Center Frequency Hz 63 125 250 500 1000 2000 4000 8000 Total Full Load dBA 73.0 70.5 76.5 82.0 85.0 81.0 75.0 72.5 88.5 75% Load dBA 71.5 65.5 71.5 76.0 77.5 76.0 74.0 67.0 83.0 50% Load dBA 73.5 70.0 75.0 80.0 82.5 79.5 74.5 70.5 87.0 25% Load dBA 75.5 62.0 67.5 77.0 77.5 77.0 73.5 67.0 83.5 A-weighted Sound Pressure Levels
Octave Band Center Frequency Hz 63 125 250 500 1000 2000 4000 8000 Total Full Load dBA 45.0 42.5 48.5 54.0 57.0 53.0 47.0 44.5 60.5 75% Load dBA 43.5 37.5 43.5 48.0 49.5 48.0 46.0 39.0 55.0 50% Load dBA 45.5 42.0 47.0 52.0 54.5 51.5 46.5 42.5 58.5 25% Load dBA 47.5 34.0 39.5 49.0 49.5 49.0 45.5 39.0 55.5 Acoustic Notes
1 - Height Above Ground: Chiller = 0.0 ft
2 - Horizontal Distance to Receiver: Chiller = 30.0 ft
3 - Vertical Height of Receiver: Chiller = 3.0 ft
Estimated Sound Power levels - dB re: 1 picowatt
Estimated Sound Pressure levels - dB re: 20 micropascal Estimated sound levels given above are assumed to originate at the acoustic center of the unit.

Estimated average sound pressure Lp at a given distance on a reective surface in a free eld environment.

Created on 4/12/2025 4:40:15 PM
Package Chillers NAO v1.7.0.0

Page 5344 ends

Item5.

Submitted by: Shawn Harlan
Certied Drawings
Project Name:

Climatec - City of Escondido City Hall Air Cooled Chiller Tag Name:

ID 10
Created on 4/12/2025 4:40:15 PM
Package Chillers NAO v1.7.0.0

Page 6345 ends

Item5.

Submitted by: Shawn Harlan
Certied Drawings
Project Name:

Climatec - City of Escondido City Hall Air Cooled Chiller Tag Name:

ID 10
Created on 4/12/2025 4:40:15 PM
Package Chillers NAO v1.7.0.0 Page 7346
Item5.

SUBMITTAL
Project
Climatec - City of Esc - Don E Anderson
Date
Saturday, April 12, 2025
Shawn Harlan
Sigler - Brea
205 Puente Street
Brea CA
347
Item5.

Table Of Contents
Project: Climatec - City of Esc - Don E Anderson 04/12/2025 Prepared By: Shawn Harlan 05:47PM
ID 1,2 3
Unit Report 4
Certified Drawing 5
Performance Summary 6
Packaged Rooftop Builder 1.79i Page 2 of 8348
Item5.

ID 1,2
Project: Climatec - City of Esc - Don E Anderson 04/12/2025 Prepared By: Shawn Harlan 05:47PM
ID 1,2
ID 1,2
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 3 of 8349
Item5.

Unit Report For ID 1,2
Project: Climatec - City of Esc - Don E Anderson 04/12/2025 Prepared By: Shawn Harlan 05:47PM
Unit Report
Unit Parameters
Unit Model: 50NT-B48---3
Unit Size: 48 (4 Tons)
Volts-Phase-Hertz: 208-1-60
Heating Type: Heat Pump
Refrigerant: R-454B
Duct Cfg: Horizontal/Horizontal
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 4' 0.25''
Unit Width: 3' 8.1875''
Unit Height: 3' 8.75''
*** Weights and Dimensions are approximate. Weight does not include roof curbs, unit packaging, field installed accessories or factory installed options. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions and weights, refer to appropriate product data catalog.

Base Unit Weight (Does not include any accessories):
412 lb
Warranty Information
1 year warranty on parts
5 yearwarranty on compressor
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50NT-B48---3 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 4 of 8350
Item5.

Certified Drawing for ID 1,2
Project: Climatec - City of Esc - Don E Anderson 04/12/2025 Prepared By: Shawn Harlan 05:47PM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 5 of 8351
Item5.

Performance Summary For ID 1,2
Project: Climatec - City of Esc - Don E Anderson 04/12/2025 Prepared By: Shawn Harlan 05:47PM
Performance Summary
Part Number:50NT-B48---3
Refrigerant: R-454B
ARI SEER2: 13.40
Application EER (Rooftop Unit only): 0.00
Base Unit Dimensions
Unit Length: 48.3 in
Unit Width: 44.2 in
Unit Height: 44.8 in
Base Unit Weight (Does not include any accessories): 412 lb Unit
Unit Voltage-Phase-Hertz: 208-1-60
Air Discharge: Horizontal
Fan Drive Type: Direct
Actual Airflow: 1590 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 59.0 F
Evaporator Leaving Air WB: 57.5 F
Evaporator Leaving Air Enthalpy: 24.73 BTU/lb
Unit Discharge Air DB: 0.0 F
Unit Discharge Air WB: 0.0 F
Unit Discharge Air Enthalpy: 0.00 BTU/lb
Net Cooling Capacity: 47.98 MBH
Net Sensible Capacity: 36.13 MBH
Total Unit Power Input: 4.10 kW
Coil Bypass Factor: 0.000
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 94.9 F
Total Heating Capacity: 42.84 MBH
Integrated Heating Capacity: 42.84 MBH
Heating Power Input: 3.51 kW
High Temperature COP: 3.70
Low Temperature COP: 2.26
HSPF2: 6.7
Supply Fan
External Static Pressure: 0.50 in wg
Options / Accessories Static Pressure
Wet Coil: 0.11 in wg
Application External Static (ESP + Unit Opts/Acc.): 0.61 in wg Fan Power: 0.57 BHP
Fan Motor Size, hp: 1
NOTE: Medium Motor Speed, Horz
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Minimum Voltage: 197
Maximum Voltage: 253
Packaged Rooftop Builder 1.79i Page 6 of 8352
Item5.

Performance Summary For ID 1,2
Project: Climatec - City of Esc - Don E Anderson 04/12/2025 Prepared By: Shawn Harlan 05:47PM
Compressor RLA: 19.4
Compressor LRA: 102
Outdoor Fan FLA (ea): 1.2
Indoor Fan Motor FLA (Total): 6.9
Power Supply MCA: 32.4
Power Supply MOCP (Fuse or HACR): 50
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Rating: 74.0 db
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz NA NA NA
125 Hz NA NA 56.9
250 Hz NA NA 59.3
500 Hz NA NA 63.9
1000 Hz NA NA 64.5
2000 Hz NA NA 61.7
4000 Hz NA NA 55.4
8000 Hz NA NA 47.4
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 0.0 56.9 59.3 63.9 64.5 61.7 55.4 47.4 69.3 Lw
B -

26.2 40.8 50.7 60.7 64.5 62.9 56.4 46.3 68.2 LwA
C 0.0 24.5 26.9 31.5 32.1 29.3 23.0 15.0 36.9 Lp
D -

26.2 8.4 18.3 28.3 32.1 30.5 24.0 13.9 35.8 LpA
Legend
Packaged Rooftop Builder 1.79i Page 7 of 8353
Item5.

Performance Summary For ID 1,2
Project: Climatec - City of Esc - Don E Anderson 04/12/2025 Prepared By: Shawn Harlan 05:47PM
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted.

Packaged Rooftop Builder 1.79i Page 8 of 8354
Item5.

SUBMITTAL
Project
Climatec - City of Esc - EVCC
Date
Saturday, April 12, 2025
Shawn Harlan
Sigler - Brea
205 Puente Street
Brea CA
355
Item5.

Table Of Contents
Project: Climatec - City of Esc - EVCC 04/12/2025
Prepared By: Shawn Harlan 05:52PM
ID 6,7,11-13,20 3
Unit Report 4
Certified Drawing 5
Performance Summary 8
Packaged Rooftop Builder 1.79i Page 2 of 10356
Item5.

ID 6,7,11-13,20
Project: Climatec - City of Esc - EVCC 04/12/2025
Prepared By: Shawn Harlan 05:52PM
ID 6,7,11-13,20
ID 6,7,11-13,20
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 3 of 10 357
Item5.

Unit Report For ID 6,7,11-13,20
Project: Climatec - City of Esc - EVCC 04/12/2025
Prepared By: Shawn Harlan 05:52PM
Unit Report
Unit Parameters
Unit Model: 50GEQM06A2M5-0A0A0
Unit Size: 06 (5 Tons)
Volts-Phase-Hertz: 208-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two Stage Cooling, Single Circuit
Duct Cfg: Vertical Supply / Vertical Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 6' 2.375''
Unit Width: 3' 10.625''
Unit Height: 3' 5.375''
Total Operating Weight: 613 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 4
Return Air Filter Size: 16 x 16 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
5-Year compressor parts (STD.)
1-Year parts (STD.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50GEQM06A2M5-0A0A0 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 4 of 10 358
Item5.

Certified Drawing for ID 6,7,11-13,20
Project: Climatec - City of Esc - EVCC 04/12/2025
Prepared By: Shawn Harlan 05:52PM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 5 of 10 359
Item5.

Certified Drawing for ID 6,7,11-13,20
Project: Climatec - City of Esc - EVCC 04/12/2025
Prepared By: Shawn Harlan 05:52PM
Packaged Rooftop Builder 1.79i Page 6 of 10 360
Item5.

Certified Drawing for ID 6,7,11-13,20
Project: Climatec - City of Esc - EVCC 04/12/2025
Prepared By: Shawn Harlan 05:52PM
Packaged Rooftop Builder 1.79i Page 7 of 10 361
Item5.

Performance Summary For ID 6,7,11-13,20
Project: Climatec - City of Esc - EVCC 04/12/2025
Prepared By: Shawn Harlan 05:52PM
Performance Summary
Part Number:50GEQM06A2M5-0A0A0
Refrigerant: R-454B
ARI SEER: 17.00
ARI SEER2: 16.00
Application EER (Rooftop Unit only): 11.77
Base Unit Dimensions
Unit Length: 74.4 in
Unit Width: 46.6 in
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 596 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 17 lb
Total Operating Weight: 613 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Vertical
Fan Drive Type: Direct Drive
Actual Airflow: 2000 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 57.3 F
Evaporator Leaving Air WB: 57.1 F
Evaporator Leaving Air Enthalpy: 24.49 BTU/lb
Unit Discharge Air DB: 58.5 F
Unit Discharge Air WB: 57.6 F
Unit Discharge Air Enthalpy: 24.78 BTU/lb
Gross Cooling Capacity: 62.53 MBH
Net Cooling Capacity: 59.91 MBH
Gross Sensible Capacity: 49.01 MBH
Net Sensible Capacity: 46.39 MBH
Compressor Power Input: 4.02 kW
Coil Bypass Factor: 0.014
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 95.2 F
Total Heating Capacity: 54.50 MBH
Integrated Heating Capacity: 54.50 MBH
Heating Power Input: 4.20 kW
High Temperature COP: 3.80
Low Temperature COP: 2.50
HSPF: 7.2
High Temperature COP2: 3.80
Low Temperature COP2: 2.50
HSPF2: 7.2
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 2036
Fan Power: 0.90 BHP
Packaged Rooftop Builder 1.79i Page 8 of 10 362
Item5.

Performance Summary For ID 6,7,11-13,20
Project: Climatec - City of Esc - EVCC 04/12/2025
Prepared By: Shawn Harlan 05:52PM
NOTE: Selected IFM RPM Range: 1228 - 2390
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 15.4
Compressor #1 LRA: 150
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 9.2
Power Supply MCA: 30
Power Supply MOCP (Fuse or HACR): 45
Disconnect Size FLA: 30
Disconnect Size LRA: 166
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 1.3
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 92.3 90.8 85.6
125 Hz 83.5 79.7 84.7
250 Hz 77.6 72.4 80.5
500 Hz 73.9 66.4 76.0
1000 Hz 70.7 68.5 72.4
2000 Hz 67.7 59.3 68.0
4000 Hz 64.3 53.1 62.8
8000 Hz 60.4 46.8 59.3
A-Weighted 77.2 72.6 79.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Packaged Rooftop Builder 1.79i Page 9 of 10 363
Item5.

Performance Summary For ID 6,7,11-13,20
Project: Climatec - City of Esc - EVCC 04/12/2025
Prepared By: Shawn Harlan 05:52PM
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 900 RPM
1100 RPM
1300 RPM
1500 RPM
1700 RPM
1900 RPM
2100 RPM
2300 RPM 2500 RPM 2700 RPM
2900 RPM

0.50 BHP 0.75 BHP

1.00 BHP

1.50 BHP

2.00 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 2036 BHP = 0.90 Maximum RPM = 2836 Maximum BHP = 3.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0

0.0 0.2

0.4 0.6

0.8 1.0

1.2 1.4

1.6 1.8

2.0 Packaged Rooftop Builder 1.79i Page 10 of 10 364
Item5.

SUBMITTAL
Project
Climatec - City of Esc - Fire Station 1
Date
Saturday, April 12, 2025
Shawn Harlan
Sigler - Brea
205 Puente Street
Brea CA
365
Item5.

Table Of Contents
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
ID 1 3
Unit Report 4
Certified Drawing 5
Performance Summary 8
ID 2 11
Unit Report 12
Certified Drawing 13
Performance Summary 16
ID 3 19
Unit Report 20
Certified Drawing 21
Performance Summary 24
ID 4 27
Unit Report 28
Certified Drawing 29
Performance Summary 30
ID 5 34
Unit Report 35
Certified Drawing 36
Performance Summary 39
ID 6 42
Unit Report 43
Certified Drawing 44
Performance Summary 47
ID 8 50
Unit Report 51
Certified Drawing 52
Performance Summary 55
ID 9 59
Unit Report 60
Certified Drawing 61
Performance Summary 64
Packaged Rooftop Builder 1.79i Page 2 of 66366
Item5.

ID 1
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
ID 1
ID 1
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 3 of 66 367
Item5.

Unit Report For ID 1
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Unit Report
Unit Parameters
Unit Model: 50GEQM04A2M5-0A0A0
Unit Size: 04 (3 Tons)
Volts-Phase-Hertz: 208-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two Stage Cooling, Single Circuit
Duct Cfg: Horizontal Supply / Horizontal Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 6' 2.375''
Unit Width: 3' 10.625''
Unit Height: 3' 5.375''
Total Operating Weight: 580 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 2
Return Air Filter Size: 16 x 25 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
5-Year compressor parts (STD.)
1-Year parts (STD.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50GEQM04A2M5-0A0A0 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 4 of 66 368
Item5.

Certified Drawing for ID 1
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 5 of 66 369
Item5.

Certified Drawing for ID 1
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Packaged Rooftop Builder 1.79i Page 6 of 66 370
Item5.

Certified Drawing for ID 1
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Packaged Rooftop Builder 1.79i Page 7 of 66 371
Item5.

Performance Summary For ID 1
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Performance Summary
Part Number:50GEQM04A2M5-0A0A0
Refrigerant: R-454B
ARI SEER: 17.00
ARI SEER2: 16.00
Application EER (Rooftop Unit only): 12.00
Base Unit Dimensions
Unit Length: 74.4 in
Unit Width: 46.6 in
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 567 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 13 lb
Total Operating Weight: 580 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Horizontal
Fan Drive Type: Direct Drive
Actual Airflow: 1200 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 58.5 F
Evaporator Leaving Air WB: 57.2 F
Evaporator Leaving Air Enthalpy: 24.52 BTU/lb
Unit Discharge Air DB: 59.6 F
Unit Discharge Air WB: 57.6 F
Unit Discharge Air Enthalpy: 24.80 BTU/lb
Gross Cooling Capacity: 37.36 MBH
Net Cooling Capacity: 35.86 MBH
Gross Sensible Capacity: 27.90 MBH
Net Sensible Capacity: 26.40 MBH
Compressor Power Input: 2.37 kW
Coil Bypass Factor: 0.027
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 96.1 F
Total Heating Capacity: 33.80 MBH
Integrated Heating Capacity: 33.80 MBH
Heating Power Input: 2.60 kW
High Temperature COP: 3.90
Low Temperature COP: 2.40
HSPF: 8.0
High Temperature COP2: 3.90
Low Temperature COP2: 2.40
HSPF2: 6.7
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 1916
Fan Power: 0.51 BHP
Packaged Rooftop Builder 1.79i Page 8 of 66372
Item5.

Performance Summary For ID 1
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
NOTE: Selected IFM RPM Range: 1037 - 2190
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 11.2
Compressor #1 LRA: 82
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 5.1
Power Supply MCA: 22
Power Supply MOCP (Fuse or HACR): 30
Disconnect Size FLA: 22
Disconnect Size LRA: 93
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 2.6
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 92.0 85.8 85.6
125 Hz 83.3 78.7 84.7
250 Hz 76.1 69.6 80.5
500 Hz 68.7 62.3 76.0
1000 Hz 66.1 63.7 72.4
2000 Hz 63.0 55.4 68.0
4000 Hz 59.0 49.6 62.8
8000 Hz 56.9 43.0 59.3
A-Weighted 74.2 68.9 79.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Packaged Rooftop Builder 1.79i Page 9 of 66373
Item5.

Performance Summary For ID 1
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 500 RPM
700 RPM
900 RPM
1100 RPM
1300 RPM
1500 RPM
1700 RPM
1900 RPM 2100 RPM 2300 RPM 2500 RPM

0.50 BHP

0.75 BHP

1.00 BHP

1.50 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 1916 BHP = 0.51 Maximum RPM = 2490 Maximum BHP = 3.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.3 0.6 0.9 1.2 1.5 1.8

0.0 0.2

0.4 0.6

0.8 1.0

1.2 1.4

1.6 1.8

2.0 Packaged Rooftop Builder 1.79i Page 10 of 66374
Item5.

ID 2
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
ID 2
ID 2
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 11 of 66375
Item5.

Unit Report For ID 2
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Unit Report
Unit Parameters
Unit Model: 50FEQM07A2M5-0A0A0
Unit Size: 07 (6 Tons)
Volts-Phase-Hertz: 208-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control:Two Stage Cooling, Single Circuit (07)
Duct Cfg: Horizontal Supply / Horizontal Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 6' 2.375''
Unit Width: 3' 10.625''
Unit Height: 3' 5.375''
Total Operating Weight: 636 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 4
Return Air Filter Size: 16 x 16 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard Packaging
Warranty Information
5-Year compressor parts (STD.)
1-Year parts (STD.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50FEQM07A2M5-0A0A0 Rooftop Unit 1
Field Installed Accessories
CRPWREXH028A01 Horizontal Power Exhaust 1
Packaged Rooftop Builder 1.79i Page 12 of 66376
Item5.

Certified Drawing for ID 2
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 13 of 66377
Item5.

Certified Drawing for ID 2
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Packaged Rooftop Builder 1.79i Page 14 of 66378
Item5.

Certified Drawing for ID 2
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Packaged Rooftop Builder 1.79i Page 15 of 66379
Item5.

Performance Summary For ID 2
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Performance Summary
Part Number:50FEQM07A2M5-0A0A0
Refrigerant: R-454B
ARI EER: 11.20
Application EER (Rooftop Unit only): 10.99
IEER: 15.0
Base Unit Dimensions
Unit Length: 74.4 in
Unit Width: 46.6 in
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 589 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 17 lb
Accessories
Horizontal Power Exhaust: 30 lb
Total Operating Weight: 636 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Horizontal
Fan Drive Type: Vane Axial
Actual Airflow: 2400 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 57.9 F
Evaporator Leaving Air WB: 57.4 F
Evaporator Leaving Air Enthalpy: 24.67 BTU/lb
Unit Discharge Air DB: 59.1 F
Unit Discharge Air WB: 57.9 F
Unit Discharge Air Enthalpy: 24.96 BTU/lb
Gross Cooling Capacity: 73.11 MBH
Net Cooling Capacity: 70.01 MBH
Gross Sensible Capacity: 57.24 MBH
Net Sensible Capacity: 54.14 MBH
Compressor Power Input: 5.16 kW
Coil Bypass Factor: 0.018
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 96.9 F
Total Heating Capacity: 69.80 MBH
Integrated Heating Capacity: 69.80 MBH
Heating Power Input: 5.10 kW
High Temperature COP: 3.40
Low Temperature COP: 2.25
Supply Fan
External Static Pressure: 1.00 in wg
Options / Accessories Static Pressure
Power Exhaust: (Fan Data Includes Drop)
Application External Static (ESP + Unit Opts/Acc.): 1.00 in wg Fan RPM: 2163
Packaged Rooftop Builder 1.79i Page 16 of 66380
Item5.

Performance Summary For ID 2
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Fan Power: 1.07 BHP
NOTE: Selected IFM RPM Range: 1378 - 2530
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Power Exhaust
Return Duct Static: 0.40 in wg
Max. Air To Exhaust: 1300 CFM
Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 21
Compressor #1 LRA: 162
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 5.5
Power Supply MCA: 36
Power Supply MOCP (Fuse or HACR): 50
Disconnect Size FLA: 34
Disconnect Size LRA: 176
Electrical Convenience Outlet: None
Power Exhaust [Kit Qty / FLA(ea kit)]: 1 / 1.9
Outdoor Fan [Qty / FLA (ea)]: 1 / 1.5
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 92.0 90.7 85.6
125 Hz 83.4 80.5 84.7
250 Hz 77.7 72.7 80.5
500 Hz 75.4 67.7 76.0
1000 Hz 72.2 69.7 72.4
2000 Hz 69.8 60.7 68.0
4000 Hz 65.6 54.1 62.8
8000 Hz 61.2 48.0 59.3
A-Weighted 78.4 73.5 79.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft Packaged Rooftop Builder 1.79i Page 17 of 66381
Item5.

Performance Summary For ID 2
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 900 RPM
1100 RPM
1300 RPM
1500 RPM
1700 RPM
1900 RPM
2100 RPM
2300 RPM
2500 RPM
2700 RPM
2900 RPM

0.50 BHP

0.75 BHP

1.00 BHP

1.50 BHP

2.00 BHP

3.00 BHP

5.00 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 2163 BHP = 1.07 Maximum RPM = 2836 Maximum BHP = 3.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0

0.0 0.2

0.4 0.6

0.8 1.0

1.2 1.4

1.6 1.8

2.0 Packaged Rooftop Builder 1.79i Page 18 of 66382
Item5.

ID 3
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
ID 3
ID 3
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 19 of 66383
Item5.

Unit Report For ID 3
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Unit Report
Unit Parameters
Unit Model: 50GEQM06A2M5-0A0A0
Unit Size: 06 (5 Tons)
Volts-Phase-Hertz: 208-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two Stage Cooling, Single Circuit
Duct Cfg: Horizontal Supply / Horizontal Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 6' 2.375''
Unit Width: 3' 10.625''
Unit Height: 3' 5.375''
Total Operating Weight: 613 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 4
Return Air Filter Size: 16 x 16 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
5-Year compressor parts (STD.)
1-Year parts (STD.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50GEQM06A2M5-0A0A0 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 20 of 66384
Item5.

Certified Drawing for ID 3
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 21 of 66385
Item5.

Certified Drawing for ID 3
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Packaged Rooftop Builder 1.79i Page 22 of 66386
Item5.

Certified Drawing for ID 3
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Packaged Rooftop Builder 1.79i Page 23 of 66387
Item5.

Performance Summary For ID 3
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Performance Summary
Part Number:50GEQM06A2M5-0A0A0
Refrigerant: R-454B
ARI SEER: 17.00
ARI SEER2: 16.00
Application EER (Rooftop Unit only): 11.92
Base Unit Dimensions
Unit Length: 74.4 in
Unit Width: 46.6 in
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 596 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 17 lb
Total Operating Weight: 613 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Horizontal
Fan Drive Type: Direct Drive
Actual Airflow: 2000 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 57.3 F
Evaporator Leaving Air WB: 57.1 F
Evaporator Leaving Air Enthalpy: 24.49 BTU/lb
Unit Discharge Air DB: 58.4 F
Unit Discharge Air WB: 57.6 F
Unit Discharge Air Enthalpy: 24.76 BTU/lb
Gross Cooling Capacity: 62.53 MBH
Net Cooling Capacity: 60.07 MBH
Gross Sensible Capacity: 49.01 MBH
Net Sensible Capacity: 46.55 MBH
Compressor Power Input: 4.02 kW
Coil Bypass Factor: 0.014
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 95.2 F
Total Heating Capacity: 54.50 MBH
Integrated Heating Capacity: 54.50 MBH
Heating Power Input: 4.20 kW
High Temperature COP: 3.80
Low Temperature COP: 2.50
HSPF: 7.2
High Temperature COP2: 3.80
Low Temperature COP2: 2.50
HSPF2: 7.2
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 1995
Fan Power: 0.85 BHP
Packaged Rooftop Builder 1.79i Page 24 of 66388
Item5.

Performance Summary For ID 3
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
NOTE: Selected IFM RPM Range: 1197 - 2390
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 15.4
Compressor #1 LRA: 150
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 9.2
Power Supply MCA: 30
Power Supply MOCP (Fuse or HACR): 45
Disconnect Size FLA: 30
Disconnect Size LRA: 166
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 1.3
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 91.7 90.2 85.6
125 Hz 82.8 79.0 84.7
250 Hz 76.9 72.0 80.5
500 Hz 73.4 65.7 76.0
1000 Hz 70.0 67.9 72.4
2000 Hz 67.1 58.7 68.0
4000 Hz 63.8 52.5 62.8
8000 Hz 60.1 46.3 59.3
A-Weighted 76.6 72.0 79.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Packaged Rooftop Builder 1.79i Page 25 of 66389
Item5.

Performance Summary For ID 3
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 900 RPM
1100 RPM
1300 RPM
1500 RPM
1700 RPM
1900 RPM
2100 RPM
2300 RPM
2500 RPM
2700 RPM
2900 RPM

0.50 BHP

0.75 BHP

1.00 BHP

1.50 BHP

2.00 BHP

3.00 BHP

5.00 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 1995 BHP = 0.85 Maximum RPM = 2836 Maximum BHP = 3.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0

0.0 0.2

0.4 0.6

0.8 1.0

1.2 1.4

1.6 1.8

2.0 Packaged Rooftop Builder 1.79i Page 26 of 66390
Item5.

ID 4
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
ID 4
ID 4
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 27 of 66391
Item5.

Unit Report For ID 4
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Unit Report
Unit Parameters
Unit Model: 50FEQM07A2M5-0A0A0
Unit Size: 07 (6 Tons)
Volts-Phase-Hertz: 208-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control:Two Stage Cooling, Single Circuit (07)
Duct Cfg: Horizontal Supply / Horizontal Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 6' 2.375''
Unit Width: 3' 10.625''
Unit Height: 3' 5.375''
Total Operating Weight: 606 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 4
Return Air Filter Size: 16 x 16 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard Packaging
Warranty Information
5-Year compressor parts (STD.)
1-Year parts (STD.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50FEQM07A2M5-0A0A0 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 28 of 66392
Item5.

Certified Drawing for ID 4
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 29 of 66393
Item5.

Performance Summary For ID 4
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Performance Summary
Part Number:50FEQM07A2M5-0A0A0
Refrigerant: R-454B
ARI EER: 11.20
Application EER (Rooftop Unit only): 10.99
IEER: 15.0
Base Unit Dimensions
Unit Length: 74.4 in
Unit Width: 46.6 in
Packaged Rooftop Builder 1.79i Page 30 of 66394
Item5.

Performance Summary For ID 4
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 589 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 17 lb
Total Operating Weight: 606 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Horizontal
Fan Drive Type: Vane Axial
Actual Airflow: 2400 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 57.9 F
Evaporator Leaving Air WB: 57.4 F
Evaporator Leaving Air Enthalpy: 24.67 BTU/lb
Unit Discharge Air DB: 59.1 F
Unit Discharge Air WB: 57.9 F
Unit Discharge Air Enthalpy: 24.96 BTU/lb
Gross Cooling Capacity: 73.11 MBH
Net Cooling Capacity: 70.01 MBH
Gross Sensible Capacity: 57.24 MBH
Net Sensible Capacity: 54.14 MBH
Compressor Power Input: 5.16 kW
Coil Bypass Factor: 0.018
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 96.9 F
Total Heating Capacity: 69.80 MBH
Integrated Heating Capacity: 69.80 MBH
Heating Power Input: 5.10 kW
High Temperature COP: 3.40
Low Temperature COP: 2.25
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 2163
Fan Power: 1.07 BHP
NOTE: Selected IFM RPM Range: 1378 - 2530
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 21
Compressor #1 LRA: 162
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 5.5
Power Supply MCA: 34
Power Supply MOCP (Fuse or HACR): 50
Disconnect Size FLA: 32
Disconnect Size LRA: 174
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 1.5
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Packaged Rooftop Builder 1.79i Page 31 of 66395
Item5.

Performance Summary For ID 4
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 92.0 90.7 85.6
125 Hz 83.4 80.5 84.7
250 Hz 77.7 72.7 80.5
500 Hz 75.4 67.7 76.0
1000 Hz 72.2 69.7 72.4
2000 Hz 69.8 60.7 68.0
4000 Hz 65.6 54.1 62.8
8000 Hz 61.2 48.0 59.3
A-Weighted 78.4 73.5 79.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical Packaged Rooftop Builder 1.79i Page 32 of 66396
Item5.

Performance Summary For ID 4
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 900 RPM
1100 RPM
1300 RPM
1500 RPM
1700 RPM
1900 RPM
2100 RPM
2300 RPM
2500 RPM
2700 RPM
2900 RPM

0.50 BHP

0.75 BHP

1.00 BHP

1.50 BHP

2.00 BHP

3.00 BHP

5.00 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 2163 BHP = 1.07 Maximum RPM = 2836 Maximum BHP = 3.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0

0.0 0.2

0.4 0.6

0.8 1.0

1.2 1.4

1.6 1.8

2.0 Packaged Rooftop Builder 1.79i Page 33 of 66397
Item5.

ID 5
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
ID 5
ID 5
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 34 of 66398
Item5.

Unit Report For ID 5
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Unit Report
Unit Parameters
Unit Model: 50GEQM05A2M5-0A0A0
Unit Size: 05 (4 Tons)
Volts-Phase-Hertz: 208-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two Stage Cooling, Single Circuit
Duct Cfg: Horizontal Supply / Horizontal Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 6' 2.375''
Unit Width: 3' 10.625''
Unit Height: 3' 5.375''
Total Operating Weight: 607 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 4
Return Air Filter Size: 16 x 16 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
5-Year compressor parts (STD.)
1-Year parts (STD.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50GEQM05A2M5-0A0A0 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 35 of 66399
Item5.

Certified Drawing for ID 5
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 36 of 66400
Item5.

Certified Drawing for ID 5
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Packaged Rooftop Builder 1.79i Page 37 of 66401
Item5.

Certified Drawing for ID 5
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Packaged Rooftop Builder 1.79i Page 38 of 66402
Item5.

Performance Summary For ID 5
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Performance Summary
Part Number:50GEQM05A2M5-0A0A0
Refrigerant: R-454B
ARI SEER: 17.00
ARI SEER2: 16.00
Application EER (Rooftop Unit only): 12.19
Base Unit Dimensions
Unit Length: 74.4 in
Unit Width: 46.6 in
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 594 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 13 lb
Total Operating Weight: 607 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Horizontal
Fan Drive Type: Direct Drive
Actual Airflow: 1600 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 58.4 F
Evaporator Leaving Air WB: 57.1 F
Evaporator Leaving Air Enthalpy: 24.48 BTU/lb
Unit Discharge Air DB: 59.5 F
Unit Discharge Air WB: 57.6 F
Unit Discharge Air Enthalpy: 24.76 BTU/lb
Gross Cooling Capacity: 50.11 MBH
Net Cooling Capacity: 48.11 MBH
Gross Sensible Capacity: 37.34 MBH
Net Sensible Capacity: 35.34 MBH
Compressor Power Input: 3.18 kW
Coil Bypass Factor: 0.000
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 95.9 F
Total Heating Capacity: 44.80 MBH
Integrated Heating Capacity: 44.80 MBH
Heating Power Input: 3.60 kW
High Temperature COP: 3.80
Low Temperature COP: 2.50
HSPF: 7.2
High Temperature COP2: 3.80
Low Temperature COP2: 2.50
HSPF2: 7.2
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 1856
Fan Power: 0.69 BHP
Packaged Rooftop Builder 1.79i Page 39 of 66403
Item5.

Performance Summary For ID 5
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
NOTE: Selected IFM RPM Range: 1022 - 2170
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 15.6
Compressor #1 LRA: 112
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 7.1
Power Supply MCA: 28
Power Supply MOCP (Fuse or HACR): 40
Disconnect Size FLA: 28
Disconnect Size LRA: 125
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 1.3
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 92.1 89.8 85.6
125 Hz 82.9 78.0 84.7
250 Hz 76.6 71.8 80.5
500 Hz 71.7 64.1 76.0
1000 Hz 68.1 66.3 72.4
2000 Hz 64.9 57.2 68.0
4000 Hz 62.2 51.3 62.8
8000 Hz 59.2 44.9 59.3
A-Weighted 75.5 70.9 79.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Packaged Rooftop Builder 1.79i Page 40 of 66404
Item5.

Performance Summary For ID 5
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 700 RPM
900 RPM
1100 RPM
1300 RPM
1500 RPM
1700 RPM
1900 RPM
2100 RPM
2300 RPM
2500 RPM
2700 RPM

0.50 BHP

0.75 BHP

1.00 BHP

1.50 BHP

2.00 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 1856 BHP = 0.69 Maximum RPM = 2660 Maximum BHP = 3.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0

0.0 0.2

0.4 0.6

0.8 1.0

1.2 1.4

1.6 1.8

2.0 Packaged Rooftop Builder 1.79i Page 41 of 66405
Item5.

ID 6
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
ID 6
ID 6
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 42 of 66406
Item5.

Unit Report For ID 6
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Unit Report
Unit Parameters
Unit Model: 50GEQM06A2M5-0A0A0
Unit Size: 06 (5 Tons)
Volts-Phase-Hertz: 208-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two Stage Cooling, Single Circuit
Duct Cfg: Horizontal Supply / Horizontal Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 6' 2.375''
Unit Width: 3' 10.625''
Unit Height: 3' 5.375''
Total Operating Weight: 613 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 4
Return Air Filter Size: 16 x 16 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
5-Year compressor parts (STD.)
1-Year parts (STD.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50GEQM06A2M5-0A0A0 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 43 of 66407
Item5.

Certified Drawing for ID 6
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 44 of 66408
Item5.

Certified Drawing for ID 6
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Packaged Rooftop Builder 1.79i Page 45 of 66409
Item5.

Certified Drawing for ID 6
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Packaged Rooftop Builder 1.79i Page 46 of 66410
Item5.

Performance Summary For ID 6
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Performance Summary
Part Number:50GEQM06A2M5-0A0A0
Refrigerant: R-454B
ARI SEER: 17.00
ARI SEER2: 16.00
Application EER (Rooftop Unit only): 11.92
Base Unit Dimensions
Unit Length: 74.4 in
Unit Width: 46.6 in
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 596 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 17 lb
Total Operating Weight: 613 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Horizontal
Fan Drive Type: Direct Drive
Actual Airflow: 2000 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 57.3 F
Evaporator Leaving Air WB: 57.1 F
Evaporator Leaving Air Enthalpy: 24.49 BTU/lb
Unit Discharge Air DB: 58.4 F
Unit Discharge Air WB: 57.6 F
Unit Discharge Air Enthalpy: 24.76 BTU/lb
Gross Cooling Capacity: 62.53 MBH
Net Cooling Capacity: 60.07 MBH
Gross Sensible Capacity: 49.01 MBH
Net Sensible Capacity: 46.55 MBH
Compressor Power Input: 4.02 kW
Coil Bypass Factor: 0.014
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 95.2 F
Total Heating Capacity: 54.50 MBH
Integrated Heating Capacity: 54.50 MBH
Heating Power Input: 4.20 kW
High Temperature COP: 3.80
Low Temperature COP: 2.50
HSPF: 7.2
High Temperature COP2: 3.80
Low Temperature COP2: 2.50
HSPF2: 7.2
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 1995
Fan Power: 0.85 BHP
Packaged Rooftop Builder 1.79i Page 47 of 66411
Item5.

Performance Summary For ID 6
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
NOTE: Selected IFM RPM Range: 1197 - 2390
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 15.4
Compressor #1 LRA: 150
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 9.2
Power Supply MCA: 30
Power Supply MOCP (Fuse or HACR): 45
Disconnect Size FLA: 30
Disconnect Size LRA: 166
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 1.3
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 91.7 90.2 85.6
125 Hz 82.8 79.0 84.7
250 Hz 76.9 72.0 80.5
500 Hz 73.4 65.7 76.0
1000 Hz 70.0 67.9 72.4
2000 Hz 67.1 58.7 68.0
4000 Hz 63.8 52.5 62.8
8000 Hz 60.1 46.3 59.3
A-Weighted 76.6 72.0 79.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Packaged Rooftop Builder 1.79i Page 48 of 66412
Item5.

Performance Summary For ID 6
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 900 RPM
1100 RPM
1300 RPM
1500 RPM
1700 RPM
1900 RPM
2100 RPM
2300 RPM
2500 RPM
2700 RPM
2900 RPM

0.50 BHP

0.75 BHP

1.00 BHP

1.50 BHP

2.00 BHP

3.00 BHP

5.00 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 1995 BHP = 0.85 Maximum RPM = 2836 Maximum BHP = 3.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0

0.0 0.2

0.4 0.6

0.8 1.0

1.2 1.4

1.6 1.8

2.0 Packaged Rooftop Builder 1.79i Page 49 of 66413
Item5.

ID 8
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
ID 8
ID 8
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 50 of 66414
Item5.

Unit Report For ID 8
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Unit Report
Unit Parameters
Unit Model: 50FEQM12A2M5-0A0A0
Unit Size: 12 (10 Tons)
Volts-Phase-Hertz: 208-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two-Stage Cooling, Single Circuit
Duct Cfg: Horizontal Supply / Horizontal Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 7' 4.125''
Unit Width: 4' 11.5''
Unit Height: 4' 1.375''
Total Operating Weight: 1001 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 4
Return Air Filter Size: 20 x 20 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
1-Year parts (STD.)
5-Year Compressor (std.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50FEQM12A2M5-0A0A0 Rooftop Unit 1
Field Installed Accessories
CRPWREXH028A01 Horizontal Power Exhaust 1
Packaged Rooftop Builder 1.79i Page 51 of 66415
Item5.

Certified Drawing for ID 8
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 52 of 66416
Item5.

Certified Drawing for ID 8
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Packaged Rooftop Builder 1.79i Page 53 of 66417
Item5.

Certified Drawing for ID 8
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Packaged Rooftop Builder 1.79i Page 54 of 66418
Item5.

Performance Summary For ID 8
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Performance Summary
Part Number:50FEQM12A2M5-0A0A0
Refrigerant: R-454B
ARI EER: 11.00
Application EER (Rooftop Unit only): 11.07
IEER: 15.0
Base Unit Dimensions
Unit Length: 88.1 in
Unit Width: 59.5 in
Unit Height: 49.4 in
Operating Weight
Base Unit Weight: 955 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 16 lb
Accessories
Horizontal Power Exhaust: 30 lb
Total Operating Weight: 1001 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Horizontal
Fan Drive Type: Vane Axial
Actual Airflow: 4000 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 57.6 F
Evaporator Leaving Air WB: 56.9 F
Evaporator Leaving Air Enthalpy: 24.35 BTU/lb
Unit Discharge Air DB: 58.8 F
Unit Discharge Air WB: 57.4 F
Unit Discharge Air Enthalpy: 24.62 BTU/lb
Gross Cooling Capacity: 127.67 MBH
Net Cooling Capacity: 122.65 MBH
Gross Sensible Capacity: 96.60 MBH
Net Sensible Capacity: 91.58 MBH
Compressor Power Input: 9.01 kW
Coil Bypass Factor: 0.041
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 96.4 F
Total Heating Capacity: 113.90 MBH
Integrated Heating Capacity: 113.90 MBH
Heating Power Input: 9.40 kW
High Temperature COP: 3.40
Low Temperature COP: 2.25
Supply Fan
External Static Pressure: 1.00 in wg
Options / Accessories Static Pressure
Power Exhaust: (Fan Data Includes Drop)
Application External Static (ESP + Unit Opts/Acc.): 1.00 in wg Fan RPM: 1716
Packaged Rooftop Builder 1.79i Page 55 of 66419
Item5.

Performance Summary For ID 8
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Fan Power: 1.72 BHP
NOTE: Selected IFM RPM Range: 1100 - 2000
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Power Exhaust
Return Duct Static: 0.40 in wg
Max. Air To Exhaust: 2850 CFM
Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 18.6
Compressor #1 LRA: 155
Compressor #2 RLA: 18.6
Compressor #2 LRA: 155
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 6.4
Power Supply MCA: 60
Power Supply MOCP (Fuse or HACR): 70
Disconnect Size FLA: 63
Disconnect Size LRA: 330
Electrical Convenience Outlet: None
Power Exhaust [Kit Qty / FLA(ea kit)]: 1 / 3.8
Outdoor Fan [Qty / FLA (ea)]: 1 / 7.4
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 91.6 53.3 88.1
125 Hz 86.7 81.0 90.0
250 Hz 82.0 75.5 85.9
500 Hz 79.7 72.0 83.0
1000 Hz 80.8 71.1 81.6
2000 Hz 77.4 65.8 78.5
4000 Hz 71.7 56.3 76.4
8000 Hz 63.6 49.1 75.5
A-Weighted 84.7 75.3 87.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft
Packaged Rooftop Builder 1.79i Page 56 of 66420
Item5.

Performance Summary For ID 8
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 88.1 90.0 85.9 83.0 81.6 78.5 76.4 75.5 94.0 Lw
B 61.9 73.9 77.3 79.8 81.6 79.7 77.4 74.4 87.0 LwA
C 55.7 57.6 53.5 50.6 49.2 46.1 44.0 43.1 61.6 Lp
D 29.5 41.5 44.9 47.4 49.2 47.3 45.0 42.0 54.6 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted.

Packaged Rooftop Builder 1.79i Page 57 of 66421
Item5.

Performance Summary For ID 8
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
600 RPM
800 RPM
1000 RPM
1200 RPM
1400 RPM
1600 RPM 1800 RPM 2000 RPM
2200 RPM

0.75 BHP

1.00 BHP

1.50 BHP

2.00 BHP

3.00 BHP

5.00 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 1716 BHP = 1.72 Maximum RPM = 2200 Maximum BHP = 5.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0

0.0 0.5

1.0 1.5

2.0 Packaged Rooftop Builder 1.79i Page 58 of 66422
Item5.

ID 9
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
ID 9
ID 9
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 59 of 66423
Item5.

Unit Report For ID 9
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Unit Report
Unit Parameters
Unit Model: 50GEQM06A2M5-0A0A0
Unit Size: 06 (5 Tons)
Volts-Phase-Hertz: 208-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two Stage Cooling, Single Circuit
Duct Cfg: Horizontal Supply / Horizontal Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 6' 2.375''
Unit Width: 3' 10.625''
Unit Height: 3' 5.375''
Total Operating Weight: 613 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 4
Return Air Filter Size: 16 x 16 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
5-Year compressor parts (STD.)
1-Year parts (STD.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50GEQM06A2M5-0A0A0 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 60 of 66424
Item5.

Certified Drawing for ID 9
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 61 of 66425
Item5.

Certified Drawing for ID 9
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Packaged Rooftop Builder 1.79i Page 62 of 66426
Item5.

Certified Drawing for ID 9
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Packaged Rooftop Builder 1.79i Page 63 of 66427
Item5.

Performance Summary For ID 9
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Performance Summary
Part Number:50GEQM06A2M5-0A0A0
Refrigerant: R-454B
ARI SEER: 17.00
ARI SEER2: 16.00
Application EER (Rooftop Unit only): 11.92
Base Unit Dimensions
Unit Length: 74.4 in
Unit Width: 46.6 in
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 596 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 17 lb
Total Operating Weight: 613 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Horizontal
Fan Drive Type: Direct Drive
Actual Airflow: 2000 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 57.3 F
Evaporator Leaving Air WB: 57.1 F
Evaporator Leaving Air Enthalpy: 24.49 BTU/lb
Unit Discharge Air DB: 58.4 F
Unit Discharge Air WB: 57.6 F
Unit Discharge Air Enthalpy: 24.76 BTU/lb
Gross Cooling Capacity: 62.53 MBH
Net Cooling Capacity: 60.07 MBH
Gross Sensible Capacity: 49.01 MBH
Net Sensible Capacity: 46.55 MBH
Compressor Power Input: 4.02 kW
Coil Bypass Factor: 0.014
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 95.2 F
Total Heating Capacity: 54.50 MBH
Integrated Heating Capacity: 54.50 MBH
Heating Power Input: 4.20 kW
High Temperature COP: 3.80
Low Temperature COP: 2.50
HSPF: 7.2
High Temperature COP2: 3.80
Low Temperature COP2: 2.50
HSPF2: 7.2
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 1995
Fan Power: 0.85 BHP
Packaged Rooftop Builder 1.79i Page 64 of 66428
Item5.

Performance Summary For ID 9
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
NOTE: Selected IFM RPM Range: 1197 - 2390
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 15.4
Compressor #1 LRA: 150
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 9.2
Power Supply MCA: 30
Power Supply MOCP (Fuse or HACR): 45
Disconnect Size FLA: 30
Disconnect Size LRA: 166
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 1.3
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 91.7 90.2 85.6
125 Hz 82.8 79.0 84.7
250 Hz 76.9 72.0 80.5
500 Hz 73.4 65.7 76.0
1000 Hz 70.0 67.9 72.4
2000 Hz 67.1 58.7 68.0
4000 Hz 63.8 52.5 62.8
8000 Hz 60.1 46.3 59.3
A-Weighted 76.6 72.0 79.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Packaged Rooftop Builder 1.79i Page 65 of 66429
Item5.

Performance Summary For ID 9
Project: Climatec - City of Esc - Fire Station 1 04/12/2025 Prepared By: Shawn Harlan 07:47AM
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 900 RPM
1100 RPM
1300 RPM
1500 RPM
1700 RPM
1900 RPM
2100 RPM
2300 RPM
2500 RPM
2700 RPM
2900 RPM

0.50 BHP

0.75 BHP

1.00 BHP

1.50 BHP

2.00 BHP

3.00 BHP

5.00 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 1995 BHP = 0.85 Maximum RPM = 2836 Maximum BHP = 3.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0

0.0 0.2

0.4 0.6

0.8 1.0

1.2 1.4

1.6 1.8

2.0 Packaged Rooftop Builder 1.79i Page 66 of 66430
Item5.

Outdoor Unit Heat Pump Ductless System
Outdoor Model: 37MARAQ24AA3
Job Data: Location:

Tag #: Carrier#:

Date:

NOTE: Images for illustration purposes only. Actual models may be slightly different.

Outdoor - Heat Pump
37MARAQ24AA3
24000
Voltage, Phase, Cycle V/Ph/Hz 208-230/1/60
MCA A. 24
MOPA A. 25
SCCR kA 5
Cooling Outdoor DB Min - Max °F(°C) -13~122(-25~50)
Heating Outdoor DB Min - Max °F(°C) -13~75(-25~24)
Min. Piping Length ft (m) 9.8 (3)
Standard Piping Length ft. (m) 24.6 (7.5)
Total Piping Length ft (m) 164.04(50)
Piping Lift*
ft (m) 82.02(25)
Pipe Connection Size - Liquid in (mm) 3/8in(9.52mm)
Pipe Connection Size - Suction in (mm) 5/8in(15.9mm)
R454B
Charge lbs (kg) 4.41(2.0)
Add'l Refrigerant (between Std & Max
Piping Lengths)
Oz/ft
(g/m) 0.32(30)
Capacity Unit W D H L1 L2 Face Area Sq. Ft. 8.18
mm 765 303 555 452.4 313.82 2.6
inch 30.12 11.93 21.85 17.81 12.36 20
mm 890 342 673 663 379.59 6
inch 35.04 13.46 26.5 26.1 14.94 ROTARY
mm 946 410 810 672.96 454.8 KTM240D46UKT2
inch 37.24 16.14 31.89 26.49 17.19 ESTER OIL
Oil Charge Fl. Oz. 20.97
Rated Current RLA 1.05
Airflow CFM 2237.9
Sound Pressure dB(A) 58
Height in (mm) 31.89(810)
Width in (mm) 37.24(946)
Depth in (mm) 16.14(410)
Net Weight lbs (kg) 122.14(55.4)
Shipping Height in (mm) 34.84(885)
Shipping Width in (mm) 42.91(1090)
Shipping Depth in (mm) 19.68(500)
Shipping Net Weight lbs (kg) 132.28(60)
* Condensing unit above or below indoor unit
9K/12K
18K
24K ~ 36K
Outdoor Size
Outdoor Model #
Refrigerant
System
Electrical
Operating Range
Refrigerant Type

OUTDOOR STANDARD FEATURES
• Variable Speed (Inverter)
• Factory installed Base Pan Heater
• Factory installed Crankcase Heater
• Low Voltage Controls
• Auto-Restart function
• Condenser High Temp Protection
• Quiet operation
• Anti-corrosive fin coating
RESIDENTIAL APPLICATION LIMITED WARRANTY*
• Ten (10) years if properly registered within ninety (90) days after original installation, parts are warranted to the original purchaser for a period of ten (10) years. Otherwise, parts warranty is five (5) years.

Piping

OUTDOOR UNIT DIMENSIONS
Dimensions
No. Rows
Fins per inch
Circuits
Type
Model
Outdoor Coil
Compressor
Airflow & Sound
Oil Type
Carrier Corporation Copyright 2024 • Atlanta, GA, 30339

SUBJECT TO CHANGE WITHOUT NOTICE
431
Item5.

Outdoor Unit Heat Pump Ductless System
Outdoor Model: 37MARAQ30AA3
Job Data: Location:

Tag #: Carrier#:

Date:

NOTE: Images for illustration purposes only. Actual models may be slightly different.

Outdoor - Heat Pump
37MARAQ30AA3
30000
Voltage, Phase, Cycle V/Ph/Hz 208-230/1/60
MCA A. 28
MOPA A. 30
SCCR kA 5
Cooling Outdoor DB Min - Max °F(°C) 5~122(-15~50)
Heating Outdoor DB Min - Max °F(°C) 5~75(-15~24)
Min. Piping Length ft (m) 9.8 (3)
Standard Piping Length ft. (m) 24.6 (7.5)
Total Piping Length ft (m) 164.04(50)
Piping Lift*
ft (m) 82.02(25)
Pipe Connection Size - Liquid in (mm) 3/8in(9.52mm)
Pipe Connection Size - Suction in (mm) 5/8in(15.9mm)
R454B
Charge lbs (kg) 5.29(2.4)
Add'l Refrigerant (between Std & Max
Piping Lengths)
Oz/ft
(g/m) 0.32(30)
Capacity Unit W D H L1 L2 Face Area Sq. Ft. 8.14
mm 765 303 555 452.4 313.82 3
inch 30.12 11.93 21.85 17.81 12.36 19
mm 890 342 673 663 379.59 6
inch 35.04 13.46 26.5 26.1 14.94 ROTARY
mm 946 410 810 672.96 454.8 KTF250D22UMT
inch 37.24 16.14 31.89 26.49 17.19 ESTER OIL
Oil Charge Fl. Oz. 22.66
Rated Current RLA 1.21
Airflow CFM 2237.9
Sound Pressure dB(A) 61
Height in (mm) 31.89(810)
Width in (mm) 37.24(946)
Depth in (mm) 16.14(410)
Net Weight lbs (kg) 142.86(64.8)
Shipping Height in (mm) 34.84(885)
Shipping Width in (mm) 42.91(1090)
Shipping Depth in (mm) 19.68(500)
Shipping Net Weight lbs (kg) 154.54(70.1)
* Condensing unit above or below indoor unit
9K/12K
18K
24K ~ 36K
Outdoor Size
Outdoor Model #
Refrigerant
System
Electrical
Operating Range
Refrigerant Type

OUTDOOR STANDARD FEATURES
• Variable Speed (Inverter)
• Factory installed Base Pan Heater
• Factory installed Crankcase Heater
• Low Voltage Controls
• Auto-Restart function
• Condenser High Temp Protection
• Quiet operation
• Anti-corrosive fin coating
RESIDENTIAL APPLICATION LIMITED WARRANTY*
• Ten (10) years if properly registered within ninety (90) days after original installation, parts are warranted to the original purchaser for a period of ten (10) years. Otherwise, parts warranty is five (5) years.

Piping

OUTDOOR UNIT DIMENSIONS
Dimensions
No. Rows
Fins per inch
Circuits
Type
Model
Outdoor Coil
Compressor
Airflow & Sound
Oil Type
Carrier Corporation Copyright 2024 • Atlanta, GA, 30339

SUBJECT TO CHANGE WITHOUT NOTICE
432
Item5.

Outdoor Unit Heat Pump Ductless System
Outdoor Model: 37MARAQ36AA3
Job Data: Location:

Tag #: Carrier#:

Date:

NOTE: Images for illustration purposes only. Actual models may be slightly different.

Outdoor - Heat Pump
37MARAQ36AA3
36000
Voltage, Phase, Cycle V/Ph/Hz 208-230/1/60
MCA A. 33
MOPA A. 35
SCCR kA 5
Cooling Outdoor DB Min - Max °F(°C) 5~122(-15~50)
Heating Outdoor DB Min - Max °F(°C) 5~75(-15~24)
Min. Piping Length ft (m) 9.8 (3)
Standard Piping Length ft. (m) 24.6 (7.5)
Total Piping Length ft (m) 213.25(65)
Piping Lift*
ft (m) 98.43(30)
Pipe Connection Size - Liquid in (mm) 3/8in(9.52mm)
Pipe Connection Size - Suction in (mm) 5/8in(15.9mm)
R454B
Charge lbs (kg) 7.05(3.2)
Add'l Refrigerant (between Std & Max
Piping Lengths)
Oz/ft
(g/m) 0.32(30)
Capacity Unit W D H L1 L2 Face Area Sq. Ft. 8.14
mm 765 303 555 452.4 313.82 3
inch 30.12 11.93 21.85 17.81 12.36 19
mm 890 342 673 663 379.59 6
inch 35.04 13.46 26.5 26.1 14.94 ROTARY
mm 946 410 810 672.96 454.8 KTF250D22UMT
inch 37.24 16.14 31.89 26.49 17.19 ESTER OIL
Oil Charge Fl. Oz. 22.66
Rated Current RLA 1.21
Airflow CFM 2237.9
Sound Pressure dB(A) 63
Height in (mm) 31.89(810)
Width in (mm) 37.24(946)
Depth in (mm) 16.14(410)
Net Weight lbs (kg) 150.36(68.2)
Shipping Height in (mm) 34.84(885)
Shipping Width in (mm) 42.91(1090)
Shipping Depth in (mm) 19.68(500)
Shipping Net Weight lbs (kg) 160.28(72.7)
* Condensing unit above or below indoor unit
9K/12K
18K
24K ~ 36K
Outdoor Size
Outdoor Model #
Refrigerant
System
Electrical
Operating Range
Refrigerant Type

OUTDOOR STANDARD FEATURES
• Variable Speed (Inverter)
• Factory installed Base Pan Heater
• Factory installed Crankcase Heater
• Low Voltage Controls
• Auto-Restart function
• Condenser High Temp Protection
• Quiet operation
• Anti-corrosive fin coating
RESIDENTIAL APPLICATION LIMITED WARRANTY*
• Ten (10) years if properly registered within ninety (90) days after original installation, parts are warranted to the original purchaser for a period of ten (10) years. Otherwise, parts warranty is five (5) years.

Piping

OUTDOOR UNIT DIMENSIONS
Dimensions
No. Rows
Fins per inch
Circuits
Type
Model
Outdoor Coil
Compressor
Airflow & Sound
Oil Type
Carrier Corporation Copyright 2024 • Atlanta, GA, 30339

SUBJECT TO CHANGE WITHOUT NOTICE
433
Item5.

Air Handler Heat Pump Ductless System
Indoor Model: 45MBAAQ24XB3
Job Data: Location:

Tag #: Carrier#:

Date:

NOTE: Images for illustration purposes only. Actual models may be slightly different. 45MBAAQ24XB3
24000
Voltage, Phase, Cycle V/Ph/Hz 208-230/1/60
Power Supply
MCA A. 4
Cooling Indoor DB Min - Max °F(°C) 60~90 (16~32)
Heating Indoor DB Min - Max °F(°C) 32~86 (0~30)
Face Area Sq. Ft. 3
3 20
6 550/510/450
Airflow (highest to lowest) CFM 824.0 / 759.3 / 694.5 / 629.8 / - Sound Pressure (highest to lowest) dB(A) N\A/43.5/40/25.5/N\A Height in (mm) 45.00(1143)
Width in (mm) 17.52(445)
Depth in (mm) 21.02(534)
Net Weight lbs (kg) 104.28(47.3)
Shipping Height in (mm) 21.20(640)
Shipping Width in (mm) 48.23(1225)
Shipping Depth in (mm) 21.06(535)
Shipping Net Weight lbs (kg) 125.88(57.1)

CONTROLS
Standard
KSACN1401AAA
KSAIC0601230
Inch mm Inch mm
A Model Height 45 1143 49 1245
B Model Width 17.5 445 21 534
C S.A. Opening Width 15.6 397 19.1 486
D R.A. Opening Width 15.1 384 18.6 473
E Model Depth 21 534 21 534
F S.A. Opening Depth 10.3 260 10.3 260
G R.A. Opening Depth 18.8 476 18.8 476
H S.A. Opening Clearance 0.9 24 0.9 24
I R.A. Opening Side Clearance 1.3 32 1.3 32
J R.A. Opening Front Clearance 1.5 38 1.6 41
K R.A. Opening Back Clearance 0.6 16 0.6 16
Wireless Remote Controller (°F/°C Convertible)
Dimensions
Number of Fan Speeds
Fins per inch
Indoor Size
No. Rows
System
Electrical Indoor unit powered by outdoor unit
Operating Range
Indoor Coil
Indoor Model #
Circuits
Indoor Unit

INDOOR UNIT DIMENSIONS
Dimensions
18K/24K 36K
45MBAAQ24XB3

INDOOR STANDARD FEATURES
• Modes: Cool, Heat, Dry, Fan, Auto
• 4-way installation (Up flow, Down flow, Right, Left)
• Auto-Restart function
• Quiet indoor operation
• Aluminum hydrophilic pre-coated fins
RESIDENTIAL APPLICATION LIMITED WARRANTY*
• Ten (10) years if properly registered within ninety (90) days after original installation, parts are warranted to the original purchaser for a period of ten (10) years. Otherwise, parts warranty is five (5) years.

Wired Remote Control 7 Day Programmable
24V Mini Interface
Optional
Carrier Corporation Copyright 2024 • Atlanta, GA, 30339

SUBJECT TO CHANGE WITHOUT NOTICE
434
Item5.

Air Handler Heat Pump Ductless System
Indoor Model: 45MBAAQ30XB3
Job Data: Location:

Tag #: Carrier#:

Date:

NOTE: Images for illustration purposes only. Actual models may be slightly different. 45MBAAQ30XB3
30000
Voltage, Phase, Cycle V/Ph/Hz 208-230/1/60
Power Supply
MCA A. 6
Cooling Indoor DB Min - Max °F(°C) 60~90 (16~32)
Heating Indoor DB Min - Max °F(°C) 32~86 (0~30)
Face Area Sq. Ft. 4.13
4 20
10 685/620/560
Airflow (highest to lowest) CFM 988.8 / 894.7 / 806.4 / 712.2 / N\A Sound Pressure (highest to lowest) dB(A) N\A/44/41/26/N\A Height in (mm) 49.02(1245)
Width in (mm) 21.02(534)
Depth in (mm) 21.02(534)
Net Weight lbs (kg) 127.43(57.8)
Shipping Height in (mm) 21.20(640)
Shipping Width in (mm) 52.17(1325)
Shipping Depth in (mm) 24.61(625)
Shipping Net Weight lbs (kg) 151.68(68.8)

CONTROLS
Standard
KSACN1401AAA
KSAIC0601230
Inch mm Inch mm
A Model Height 45 1143 49 1245
B Model Width 17.5 445 21 534
C S.A. Opening Width 15.6 397 19.1 486
D R.A. Opening Width 15.1 384 18.6 473
E Model Depth 21 534 21 534
F S.A. Opening Depth 10.3 260 10.3 260
G R.A. Opening Depth 18.8 476 18.8 476
H S.A. Opening Clearance 0.9 24 0.9 24
I R.A. Opening Side Clearance 1.3 32 1.3 32
J R.A. Opening Front Clearance 1.5 38 1.6 41
K R.A. Opening Back Clearance 0.6 16 0.6 16
Wireless Remote Controller (°F/°C Convertible)
Dimensions
Number of Fan Speeds
Fins per inch
Indoor Size
No. Rows
System
Electrical Indoor unit powered by outdoor unit
Operating Range
Indoor Coil
Indoor Model #
Circuits
Indoor Unit

INDOOR UNIT DIMENSIONS
Dimensions
18K/24K 36K
45MBAAQ30XB3

INDOOR STANDARD FEATURES
• Modes: Cool, Heat, Dry, Fan, Auto
• 4-way installation (Up flow, Down flow, Right, Left)
• Auto-Restart function
• Quiet indoor operation
• Aluminum hydrophilic pre-coated fins
RESIDENTIAL APPLICATION LIMITED WARRANTY*
• Ten (10) years if properly registered within ninety (90) days after original installation, parts are warranted to the original purchaser for a period of ten (10) years. Otherwise, parts warranty is five (5) years.

Wired Remote Control 7 Day Programmable
24V Mini Interface
Optional
Carrier Corporation Copyright 2024 • Atlanta, GA, 30339

SUBJECT TO CHANGE WITHOUT NOTICE
435
Item5.

Air Handler Heat Pump Ductless System
Indoor Model: 45MBAAQ36XB3
Job Data: Location:

Tag #: Carrier#:

Date:

NOTE: Images for illustration purposes only. Actual models may be slightly different. 45MBAAQ36XB3
36000
Voltage, Phase, Cycle V/Ph/Hz 208-230/1/60
Power Supply
MCA A. 6
Cooling Indoor DB Min - Max °F(°C) 60~90 (16~32)
Heating Indoor DB Min - Max °F(°C) 32~86 (0~30)
Face Area Sq. Ft. 4.13
4 20
10 685/620/560
Airflow (highest to lowest) CFM 1189.0 / 1083.0 / 971.2 / 865.2 / N\A Sound Pressure (highest to lowest) dB(A) N\A/48/44/35/N\A Height in (mm) 49.02(1245)
Width in (mm) 21.02(534)
Depth in (mm) 21.02(534)
Net Weight lbs (kg) 127.87(58)
Shipping Height in (mm) 21.20(640)
Shipping Width in (mm) 52.17(1325)
Shipping Depth in (mm) 24.61(625)
Shipping Net Weight lbs (kg) 154.10(69.9)

CONTROLS
Standard
KSACN1401AAA
KSAIC0601230
Inch mm Inch mm
A Model Height 45 1143 49 1245
B Model Width 17.5 445 21 534
C S.A. Opening Width 15.6 397 19.1 486
D R.A. Opening Width 15.1 384 18.6 473
E Model Depth 21 534 21 534
F S.A. Opening Depth 10.3 260 10.3 260
G R.A. Opening Depth 18.8 476 18.8 476
H S.A. Opening Clearance 0.9 24 0.9 24
I R.A. Opening Side Clearance 1.3 32 1.3 32
J R.A. Opening Front Clearance 1.5 38 1.6 41
K R.A. Opening Back Clearance 0.6 16 0.6 16
Wireless Remote Controller (°F/°C Convertible)
Dimensions
Number of Fan Speeds
Fins per inch
Indoor Size
No. Rows
System
Electrical Indoor unit powered by outdoor unit
Operating Range
Indoor Coil
Indoor Model #
Circuits
Indoor Unit

INDOOR UNIT DIMENSIONS
Dimensions
18K/24K 36K
45MBAAQ36XB3

INDOOR STANDARD FEATURES
• Modes: Cool, Heat, Dry, Fan, Auto
• 4-way installation (Up flow, Down flow, Right, Left)
• Auto-Restart function
• Quiet indoor operation
• Aluminum hydrophilic pre-coated fins
RESIDENTIAL APPLICATION LIMITED WARRANTY*
• Ten (10) years if properly registered within ninety (90) days after original installation, parts are warranted to the original purchaser for a period of ten (10) years. Otherwise, parts warranty is five (5) years.

Wired Remote Control 7 Day Programmable
24V Mini Interface
Optional
Carrier Corporation Copyright 2024 • Atlanta, GA, 30339

SUBJECT TO CHANGE WITHOUT NOTICE
436
Item5.

SUBMITTAL
Project
Climatec - City of Esc - Fire Station 2
Date
Saturday, April 12, 2025
Shawn Harlan
Sigler - Brea
205 Puente Street
Brea CA
437
Item5.

Table Of Contents
Project: Climatec - City of Esc - Fire Station 2 04/12/2025 Prepared By: Shawn Harlan
ID 5 3
Unit Report 4
Performance Summary 6
System Parameters 6
Electrical Data 6
Acoustic Summary 7
Certified Drawing 8
Residential Carrier Products Bldr 1.39j Page 2 of 10438 Item5.

ID 5
Project: Climatec - City of Esc - Fire Station 2 04/12/2025 Prepared By: Shawn Harlan
ID 5
ID 5
Submittal Cover Sheet
Unit Report
Performance Summary Report
Acoustic Summary
Certified Drawings
Residential Carrier Products Bldr 1.39j Page 3 of 10 439 Item5.

Unit Report For ID 5
Project: Climatec - City of Esc - Fire Station 2 04/12/2025 Prepared By: Shawn Harlan
Unit Report
Outdoor Unit Parameters
Unit Model: 27SCA
Unit Size: 3 Tons (Size 36)
Voltage: 208/230-3-60 V-Ph-Hz
Indoor Coil Parameters
Unit Model: F55A
Unit Size: Size (36) 36,000 Btuh
Cabinet Insulation: Singular, TXV
Voltage: 115-1-60 V-Ph-Hz
Refrigerant Type: Puron Advance
Heating Size: No Heat
Outdoor Unit Dimensions and Weight
Unit Length: 31.1875 in
Unit Width: 31.1875 in
Unit Height: 32.0625 in
Unit Shipping Weight: 193. lb
Indoor Coil Dimensions and Weight
Unit Length: 22.0625 in
Unit Width: 17.625 in
Unit Height: 49.625 in
Unit Shipping Weight: 148. lb

RESIDENTIAL APPLICATIONS
This warranty is to the original purchasing owner and subsequent owners only to the extent and as stated in the Warranty Conditions and below.

The limited warranty period in years, depending on the part and the claimant, is as shown in the table below.

Limited Warranty (Years)
Item Original Owner Subsequent Owner
Parts 10* (or 5) 5
Compressor 10* (or 5) 5
*If properly registered within 90 days of original installation, otherwise 5 years (except in California and Quebec and other jurisdictions that prohibit warranty benefits conditioned on registration). See Warranty Conditions below.

OTHER APPLICATIONS
The warranty period is five (5) years on the compressor, and one (1) year on all other parts. The warranty is the original owner only and is not available for subsequent owners.

Ordering Information
Part Number Description Quantity
Outdoor Unit
27SCA536A005 27SCA Comfort Single Stage Heat Pump with Puron Refrigerant Advanced 3 Tons Cooling
1 15 SEER @ ARI Conditions
Indoor Coil
F55AAXB36L00 F55A 115V Base Series Fan Coil for Puron Advance 3 Tons Cooling 115-1-60
1 Singular, TXV
Aluminum
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 4 of 10 440 Item5.

Unit Report For ID 5
Project: Climatec - City of Esc - Fire Station 2 04/12/2025 Prepared By: Shawn Harlan
Residential Carrier Products Bldr 1.39j Page 5 of 10 441 Item5.

Performance Summary For ID 5
Project: Climatec - City of Esc - Fire Station 2 04/12/2025 Prepared By: Shawn Harlan
Performance Summary
System Performance
System: 27SCA/F55A
System Quantity: 1
Altitude: 0.0 ft
Linear Pipe Length: 0.0 ft
COP @ 47 F: 3.72
COP @ 17 F: 2.52
SEER @ ARI Conditions: 14.5
EER @ ARI Conditions: 12.0
HSPF @ ARI Conditions: 7.5
Actual Clg Airflow: 1200.0 CFM
Standard Clg Airflow: 1200.0 CFM
Total Net Clg Capacity: 34.73 MBH
Net Sensible Clg Capacity: 26.33 MBH
Htg HP Capacity: 34.47 MBH
Htg HP Integrated Capacity: 34.47 MBH
Heating HP Compressor Power: 2.68 kW
Total System Power: 2.89 kW
System Parameters
System Parameters
Outdoor Unit Parameters
Unit Model: 27SCA536A005
Unit Size (Nominal): 3 Tons (Size 36)
Voltage: 208/230-3-60 V-Ph-Hz
Clg Ent Air DB Ambient: 95.0 °F
Htg Ent Air DB Ambient: 47.0 °F
Indoor Coil Parameters
Unit Model: F55AAXB36L00
Unit Size (Nominal): Size (36) 36,000 Btuh
Voltage: 115-1-60 V-Ph-Hz
Ent Air DB: 80.00 °F
Ent Air WB: 67.00 °F
Ent Enthalpy: 31.44 BTU/lb
Lvg Air DB: 59.68 °F
Lvg Air WB: 57.96 °F
Lvg Enthalpy: 25.01 BTU/lb
Htg Ent Air DB: 70.0 °F
Htg Lvg Air DB: 96.6 °F
Heating Size (Nominal): No Heat
Total External Static Pressure: 0.75 in wg
Electrical Data
Electrical Data
Outdoor Electrical Data
Unit Voltage: 208/230-3-60 V-Ph-Hz
Fan Motor FLA: 1.20 Amps
MCA: 12.5 Amps
Max Fuse: 20 Amps
Operating Range Min: 187 V
Operating Range Max: 253 V
Compressor RLA: 9.0 Amps
Compressor LRA: 70.0 Amps
Indoor Electrical Data:
(For units with no factory installed electric heaters)
Unit Voltage: 115-1-60 V-Ph-Hz
Unit FLA: 6.5 Amps
Unit MCA: 8.2 Amps
Unit MOCP: 15.0 Amps
Unit Min Wire Size: 14.0
Unit Fuse/Ckt Bkr Amps: 15.0 Amps
Motor HP: 1/2 HP
Notice: Indoor Elect. data is for 115-1-60 voltage
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 6 of 10 442 Item5.

Acoustic Summary For ID 5
Project: Climatec - City of Esc - Fire Station 2 04/12/2025 Prepared By: Shawn Harlan
Acoustic Summary
Outdoor Unit Parameters:

Unit Model: 27SCA
Unit Size: 3 Tons (Size 36)
Variations: Standard
Octave Band Center Frequency, Hz 125 250 500 1k 2k 4k 8k dBA Sound Power,dB 70.6 69.9 68.5 66.0 63.1 59.0 53.2
A-Weighted Sound Power, dBA 76.0
Indoor Coil Parameters:

Unit Model: F55A
Unit Size: Size (36) 36,000 Btuh
Cabinet Insulation: Singular, TXV
Octave Band Center Frequency, Hz 63 125 250 500 1k 2k 4k Sound Power,dB 73.8 69.8 65.8 62.8 60.8 58.8 54.8
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 7 of 10 443 Item5.

Certified Drawing For ID 5
Project: Climatec - City of Esc - Fire Station 2 04/12/2025 Prepared By: Shawn Harlan
Certified Drawing
Outdoor Model
Unit Model: 27SCA
Unit Size: 3 Tons (Size 36)
Voltage: 208/230-3-60 V-Ph-Hz
SEER: 15
PartNumber: 27SCA536A005
Shipping Dimensions and Weights Outdoor Unit
Height 36.44 in
Width 34.25 in
Length 34.25 in
Operating Weight 173. lb
Shipping Weight 193. lb
Dimensions

A B C D E F G H I J K

31.19 in 32.06 in 0.75 in 6.56 in 24.69 in 9.13 in 1.13 in 3.81 in 12.00 in 14.13 in 16.25 in The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 8 of 10 444 Item5.

Certified Drawing For ID 5
Project: Climatec - City of Esc - Fire Station 2 04/12/2025 Prepared By: Shawn Harlan
Indoor Coil
Unit Model: F55A
Unit Size: Size (36) 36,000 Btuh
Voltage: 115-1-60 V-Ph-Hz
Cabinet Insulation: Singular, TXV
PartNumber: F55AAXB36L00
Dimensions and Weights Indoor Coil
Height 49.63 in
Width 17.63 in
Length 22.06 in
Shipping Weight 148. lb
Dimensions

A B C D E F G H J

49.63 in 17.63 in 15.75 in 15.63 in 15.88 in 23.13 in 23.50 in -- -- The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 9 of 10 445 Item5.

Certified Drawing For ID 5
Project: Climatec - City of Esc - Fire Station 2 04/12/2025 Prepared By: Shawn Harlan
Indoor Coil
Unit Model: F55A
Unit Size: Size (36) 36,000 Btuh
Voltage: 115-1-60 V-Ph-Hz
PartNumber: F55AAXB36L00
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 10 of 10 446 Item5.

SUBMITTAL
Project
Climatec - City of Esc - Fire Station 3
Date
Saturday, April 12, 2025
Shawn Harlan
Sigler - Brea
205 Puente Street
Brea CA
447
Item5.

Table Of Contents
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
ID 2 3
Unit Report 4
Certified Drawing 5
Performance Summary 8
ID 3,4,7 11
Unit Report 12
Certified Drawing 13
Performance Summary 16
ID 6 19
Unit Report 20
Certified Drawing 21
Performance Summary 24
Packaged Rooftop Builder 1.79i Page 2 of 26448
Item5.

ID 2
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
ID 2
ID 2
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 3 of 26 449
Item5.

Unit Report For ID 2
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
Unit Report
Unit Parameters
Unit Model: 50GEQM06A2M5-0A0A0
Unit Size: 06 (5 Tons)
Volts-Phase-Hertz: 208-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two Stage Cooling, Single Circuit
Duct Cfg: Vertical Supply / Vertical Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 6' 2.375''
Unit Width: 3' 10.625''
Unit Height: 3' 5.375''
Total Operating Weight: 613 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 4
Return Air Filter Size: 16 x 16 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
5-Year compressor parts (STD.)
1-Year parts (STD.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50GEQM06A2M5-0A0A0 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 4 of 26 450
Item5.

Certified Drawing for ID 2
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 5 of 26 451
Item5.

Certified Drawing for ID 2
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
Packaged Rooftop Builder 1.79i Page 6 of 26 452
Item5.

Certified Drawing for ID 2
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
Packaged Rooftop Builder 1.79i Page 7 of 26 453
Item5.

Performance Summary For ID 2
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
Performance Summary
Part Number:50GEQM06A2M5-0A0A0
Refrigerant: R-454B
ARI SEER: 17.00
ARI SEER2: 16.00
Application EER (Rooftop Unit only): 11.77
Base Unit Dimensions
Unit Length: 74.4 in
Unit Width: 46.6 in
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 596 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 17 lb
Total Operating Weight: 613 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Vertical
Fan Drive Type: Direct Drive
Actual Airflow: 2000 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 57.3 F
Evaporator Leaving Air WB: 57.1 F
Evaporator Leaving Air Enthalpy: 24.49 BTU/lb
Unit Discharge Air DB: 58.5 F
Unit Discharge Air WB: 57.6 F
Unit Discharge Air Enthalpy: 24.78 BTU/lb
Gross Cooling Capacity: 62.53 MBH
Net Cooling Capacity: 59.91 MBH
Gross Sensible Capacity: 49.01 MBH
Net Sensible Capacity: 46.39 MBH
Compressor Power Input: 4.02 kW
Coil Bypass Factor: 0.014
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 95.2 F
Total Heating Capacity: 54.50 MBH
Integrated Heating Capacity: 54.50 MBH
Heating Power Input: 4.20 kW
High Temperature COP: 3.80
Low Temperature COP: 2.50
HSPF: 7.2
High Temperature COP2: 3.80
Low Temperature COP2: 2.50
HSPF2: 7.2
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 2036
Fan Power: 0.90 BHP
Packaged Rooftop Builder 1.79i Page 8 of 26454
Item5.

Performance Summary For ID 2
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
NOTE: Selected IFM RPM Range: 1228 - 2390
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 15.4
Compressor #1 LRA: 150
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 9.2
Power Supply MCA: 30
Power Supply MOCP (Fuse or HACR): 45
Disconnect Size FLA: 30
Disconnect Size LRA: 166
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 1.3
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 92.3 90.8 85.6
125 Hz 83.5 79.7 84.7
250 Hz 77.6 72.4 80.5
500 Hz 73.9 66.4 76.0
1000 Hz 70.7 68.5 72.4
2000 Hz 67.7 59.3 68.0
4000 Hz 64.3 53.1 62.8
8000 Hz 60.4 46.8 59.3
A-Weighted 77.2 72.6 79.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Packaged Rooftop Builder 1.79i Page 9 of 26455
Item5.

Performance Summary For ID 2
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 900 RPM
1100 RPM
1300 RPM
1500 RPM
1700 RPM
1900 RPM
2100 RPM
2300 RPM 2500 RPM 2700 RPM
2900 RPM

0.50 BHP 0.75 BHP

1.00 BHP

1.50 BHP

2.00 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 2036 BHP = 0.90 Maximum RPM = 2836 Maximum BHP = 3.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0

0.0 0.2

0.4 0.6

0.8 1.0

1.2 1.4

1.6 1.8

2.0 Packaged Rooftop Builder 1.79i Page 10 of 26456
Item5.

ID 3,4,7
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
ID 3,4,7
ID 3,4,7
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 11 of 26457
Item5.

Unit Report For ID 3,4,7
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
Unit Report
Unit Parameters
Unit Model: 50GEQM05A2M5-0A0A0
Unit Size: 05 (4 Tons)
Volts-Phase-Hertz: 208-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two Stage Cooling, Single Circuit
Duct Cfg: Vertical Supply / Vertical Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 6' 2.375''
Unit Width: 3' 10.625''
Unit Height: 3' 5.375''
Total Operating Weight: 607 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 4
Return Air Filter Size: 16 x 16 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
5-Year compressor parts (STD.)
1-Year parts (STD.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50GEQM05A2M5-0A0A0 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 12 of 26458
Item5.

Certified Drawing for ID 3,4,7
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 13 of 26459
Item5.

Certified Drawing for ID 3,4,7
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
Packaged Rooftop Builder 1.79i Page 14 of 26460
Item5.

Certified Drawing for ID 3,4,7
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
Packaged Rooftop Builder 1.79i Page 15 of 26461
Item5.

Performance Summary For ID 3,4,7
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
Performance Summary
Part Number:50GEQM05A2M5-0A0A0
Refrigerant: R-454B
ARI SEER: 17.00
ARI SEER2: 16.00
Application EER (Rooftop Unit only): 12.12
Base Unit Dimensions
Unit Length: 74.4 in
Unit Width: 46.6 in
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 594 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 13 lb
Total Operating Weight: 607 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Vertical
Fan Drive Type: Direct Drive
Actual Airflow: 1600 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 58.4 F
Evaporator Leaving Air WB: 57.1 F
Evaporator Leaving Air Enthalpy: 24.48 BTU/lb
Unit Discharge Air DB: 59.6 F
Unit Discharge Air WB: 57.6 F
Unit Discharge Air Enthalpy: 24.76 BTU/lb
Gross Cooling Capacity: 50.11 MBH
Net Cooling Capacity: 48.05 MBH
Gross Sensible Capacity: 37.34 MBH
Net Sensible Capacity: 35.28 MBH
Compressor Power Input: 3.18 kW
Coil Bypass Factor: 0.000
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 95.9 F
Total Heating Capacity: 44.80 MBH
Integrated Heating Capacity: 44.80 MBH
Heating Power Input: 3.60 kW
High Temperature COP: 3.80
Low Temperature COP: 2.50
HSPF: 7.2
High Temperature COP2: 3.80
Low Temperature COP2: 2.50
HSPF2: 7.2
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 1875
Fan Power: 0.71 BHP
Packaged Rooftop Builder 1.79i Page 16 of 26462
Item5.

Performance Summary For ID 3,4,7
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
NOTE: Selected IFM RPM Range: 1047 - 2170
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 15.6
Compressor #1 LRA: 112
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 7.1
Power Supply MCA: 28
Power Supply MOCP (Fuse or HACR): 40
Disconnect Size FLA: 28
Disconnect Size LRA: 125
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 1.3
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 92.4 90.1 85.6
125 Hz 83.3 78.3 84.7
250 Hz 77.0 72.0 80.5
500 Hz 71.9 64.5 76.0
1000 Hz 68.4 66.6 72.4
2000 Hz 65.2 57.5 68.0
4000 Hz 62.5 51.6 62.8
8000 Hz 59.4 45.1 59.3
A-Weighted 75.8 71.2 79.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Packaged Rooftop Builder 1.79i Page 17 of 26463
Item5.

Performance Summary For ID 3,4,7
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 700 RPM
900 RPM
1100 RPM
1300 RPM
1500 RPM1700 RPM
1900 RPM
2100 RPM 2300 RPM 2500 RPM

0.50 BHP

0.75 BHP

1.00 BHP

1.50 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 1875 BHP = 0.71 Maximum RPM = 2660 Maximum BHP = 3.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0

0.0 0.2

0.4 0.6

0.8 1.0

1.2 1.4

1.6 1.8

2.0 Packaged Rooftop Builder 1.79i Page 18 of 26464
Item5.

ID 6
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
ID 6
ID 6
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 19 of 26465
Item5.

Unit Report For ID 6
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
Unit Report
Unit Parameters
Unit Model: 50GEQM04A2M5-0A0A0
Unit Size: 04 (3 Tons)
Volts-Phase-Hertz: 208-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two Stage Cooling, Single Circuit
Duct Cfg: Vertical Supply / Vertical Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 6' 2.375''
Unit Width: 3' 10.625''
Unit Height: 3' 5.375''
Total Operating Weight: 580 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 2
Return Air Filter Size: 16 x 25 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
5-Year compressor parts (STD.)
1-Year parts (STD.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50GEQM04A2M5-0A0A0 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 20 of 26466
Item5.

Certified Drawing for ID 6
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 21 of 26467
Item5.

Certified Drawing for ID 6
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
Packaged Rooftop Builder 1.79i Page 22 of 26468
Item5.

Certified Drawing for ID 6
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
Packaged Rooftop Builder 1.79i Page 23 of 26469
Item5.

Performance Summary For ID 6
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
Performance Summary
Part Number:50GEQM04A2M5-0A0A0
Refrigerant: R-454B
ARI SEER: 17.00
ARI SEER2: 16.00
Application EER (Rooftop Unit only): 11.89
Base Unit Dimensions
Unit Length: 74.4 in
Unit Width: 46.6 in
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 567 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 13 lb
Total Operating Weight: 580 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Vertical
Fan Drive Type: Direct Drive
Actual Airflow: 1200 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 58.5 F
Evaporator Leaving Air WB: 57.2 F
Evaporator Leaving Air Enthalpy: 24.52 BTU/lb
Unit Discharge Air DB: 59.7 F
Unit Discharge Air WB: 57.7 F
Unit Discharge Air Enthalpy: 24.81 BTU/lb
Gross Cooling Capacity: 37.36 MBH
Net Cooling Capacity: 35.79 MBH
Gross Sensible Capacity: 27.90 MBH
Net Sensible Capacity: 26.33 MBH
Compressor Power Input: 2.37 kW
Coil Bypass Factor: 0.027
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 96.1 F
Total Heating Capacity: 33.80 MBH
Integrated Heating Capacity: 33.80 MBH
Heating Power Input: 2.60 kW
High Temperature COP: 3.90
Low Temperature COP: 2.40
HSPF: 8.0
High Temperature COP2: 3.90
Low Temperature COP2: 2.40
HSPF2: 6.7
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 1946
Fan Power: 0.54 BHP
Packaged Rooftop Builder 1.79i Page 24 of 26470
Item5.

Performance Summary For ID 6
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
NOTE: Selected IFM RPM Range: 1058 - 2190
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 11.2
Compressor #1 LRA: 82
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 5.1
Power Supply MCA: 22
Power Supply MOCP (Fuse or HACR): 30
Disconnect Size FLA: 22
Disconnect Size LRA: 93
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 2.6
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 92.4 86.1 85.6
125 Hz 83.6 79.2 84.7
250 Hz 76.5 70.0 80.5
500 Hz 69.1 62.8 76.0
1000 Hz 66.5 64.1 72.4
2000 Hz 63.5 55.8 68.0
4000 Hz 59.4 50.0 62.8
8000 Hz 57.1 43.3 59.3
A-Weighted 74.6 69.3 79.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Packaged Rooftop Builder 1.79i Page 25 of 26471
Item5.

Performance Summary For ID 6
Project: Climatec - City of Esc - Fire Station 3 04/12/2025 Prepared By: Shawn Harlan 08:11AM
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 500 RPM
700 RPM
900 RPM
1100 RPM
1300 RPM
1500 RPM
1700 RPM
1900 RPM
2100 RPM
2300 RPM
2500 RPM

0.50 BHP

0.75 BHP

1.00 BHP

1.50 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 1946 BHP = 0.54 Maximum RPM = 2490 Maximum BHP = 3.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.3 0.6 0.9 1.2 1.5 1.8

0.0 0.2

0.4 0.6

0.8 1.0

1.2 1.4

1.6 1.8

2.0 Packaged Rooftop Builder 1.79i Page 26 of 26472
Item5.

Outdoor Unit Heat Pump Ductless System
Outdoor Model: 37MARAQ24AA3
Job Data: Location:

Tag #: Carrier#:

Date:

NOTE: Images for illustration purposes only. Actual models may be slightly different.

Outdoor - Heat Pump
37MARAQ24AA3
24000
Voltage, Phase, Cycle V/Ph/Hz 208-230/1/60
MCA A. 24
MOPA A. 25
SCCR kA 5
Cooling Outdoor DB Min - Max °F(°C) -13~122(-25~50)
Heating Outdoor DB Min - Max °F(°C) -13~75(-25~24)
Min. Piping Length ft (m) 9.8 (3)
Standard Piping Length ft. (m) 24.6 (7.5)
Total Piping Length ft (m) 164.04(50)
Piping Lift*
ft (m) 82.02(25)
Pipe Connection Size - Liquid in (mm) 3/8in(9.52mm)
Pipe Connection Size - Suction in (mm) 5/8in(15.9mm)
R454B
Charge lbs (kg) 4.41(2.0)
Add'l Refrigerant (between Std & Max
Piping Lengths)
Oz/ft
(g/m) 0.32(30)
Capacity Unit W D H L1 L2 Face Area Sq. Ft. 8.18
mm 765 303 555 452.4 313.82 2.6
inch 30.12 11.93 21.85 17.81 12.36 20
mm 890 342 673 663 379.59 6
inch 35.04 13.46 26.5 26.1 14.94 ROTARY
mm 946 410 810 672.96 454.8 KTM240D46UKT2
inch 37.24 16.14 31.89 26.49 17.19 ESTER OIL
Oil Charge Fl. Oz. 20.97
Rated Current RLA 1.05
Airflow CFM 2237.9
Sound Pressure dB(A) 58
Height in (mm) 31.89(810)
Width in (mm) 37.24(946)
Depth in (mm) 16.14(410)
Net Weight lbs (kg) 122.14(55.4)
Shipping Height in (mm) 34.84(885)
Shipping Width in (mm) 42.91(1090)
Shipping Depth in (mm) 19.68(500)
Shipping Net Weight lbs (kg) 132.28(60)
* Condensing unit above or below indoor unit
9K/12K
18K
24K ~ 36K
Outdoor Size
Outdoor Model #
Refrigerant
System
Electrical
Operating Range
Refrigerant Type

OUTDOOR STANDARD FEATURES
• Variable Speed (Inverter)
• Factory installed Base Pan Heater
• Factory installed Crankcase Heater
• Low Voltage Controls
• Auto-Restart function
• Condenser High Temp Protection
• Quiet operation
• Anti-corrosive fin coating
RESIDENTIAL APPLICATION LIMITED WARRANTY*
• Ten (10) years if properly registered within ninety (90) days after original installation, parts are warranted to the original purchaser for a period of ten (10) years. Otherwise, parts warranty is five (5) years.

Piping

OUTDOOR UNIT DIMENSIONS
Dimensions
No. Rows
Fins per inch
Circuits
Type
Model
Outdoor Coil
Compressor
Airflow & Sound
Oil Type
Carrier Corporation Copyright 2024 • Atlanta, GA, 30339

SUBJECT TO CHANGE WITHOUT NOTICE
473
Item5.

Outdoor Unit Heat Pump Ductless System
Outdoor Model: 37MARAQ36AA3
Job Data: Location:

Tag #: Carrier#:

Date:

NOTE: Images for illustration purposes only. Actual models may be slightly different.

Outdoor - Heat Pump
37MARAQ36AA3
36000
Voltage, Phase, Cycle V/Ph/Hz 208-230/1/60
MCA A. 33
MOPA A. 35
SCCR kA 5
Cooling Outdoor DB Min - Max °F(°C) 5~122(-15~50)
Heating Outdoor DB Min - Max °F(°C) 5~75(-15~24)
Min. Piping Length ft (m) 9.8 (3)
Standard Piping Length ft. (m) 24.6 (7.5)
Total Piping Length ft (m) 213.25(65)
Piping Lift*
ft (m) 98.43(30)
Pipe Connection Size - Liquid in (mm) 3/8in(9.52mm)
Pipe Connection Size - Suction in (mm) 5/8in(15.9mm)
R454B
Charge lbs (kg) 7.05(3.2)
Add'l Refrigerant (between Std & Max
Piping Lengths)
Oz/ft
(g/m) 0.32(30)
Capacity Unit W D H L1 L2 Face Area Sq. Ft. 8.14
mm 765 303 555 452.4 313.82 3
inch 30.12 11.93 21.85 17.81 12.36 19
mm 890 342 673 663 379.59 6
inch 35.04 13.46 26.5 26.1 14.94 ROTARY
mm 946 410 810 672.96 454.8 KTF250D22UMT
inch 37.24 16.14 31.89 26.49 17.19 ESTER OIL
Oil Charge Fl. Oz. 22.66
Rated Current RLA 1.21
Airflow CFM 2237.9
Sound Pressure dB(A) 63
Height in (mm) 31.89(810)
Width in (mm) 37.24(946)
Depth in (mm) 16.14(410)
Net Weight lbs (kg) 150.36(68.2)
Shipping Height in (mm) 34.84(885)
Shipping Width in (mm) 42.91(1090)
Shipping Depth in (mm) 19.68(500)
Shipping Net Weight lbs (kg) 160.28(72.7)
* Condensing unit above or below indoor unit
9K/12K
18K
24K ~ 36K
Outdoor Size
Outdoor Model #
Refrigerant
System
Electrical
Operating Range
Refrigerant Type

OUTDOOR STANDARD FEATURES
• Variable Speed (Inverter)
• Factory installed Base Pan Heater
• Factory installed Crankcase Heater
• Low Voltage Controls
• Auto-Restart function
• Condenser High Temp Protection
• Quiet operation
• Anti-corrosive fin coating
RESIDENTIAL APPLICATION LIMITED WARRANTY*
• Ten (10) years if properly registered within ninety (90) days after original installation, parts are warranted to the original purchaser for a period of ten (10) years. Otherwise, parts warranty is five (5) years.

Piping

OUTDOOR UNIT DIMENSIONS
Dimensions
No. Rows
Fins per inch
Circuits
Type
Model
Outdoor Coil
Compressor
Airflow & Sound
Oil Type
Carrier Corporation Copyright 2024 • Atlanta, GA, 30339

SUBJECT TO CHANGE WITHOUT NOTICE
474
Item5.

Outdoor Heat Pump Ductless System
Outdoor Model:

Job Data: Location:

Tag #: Carrier#:

Date:

NOTE: Images for illustration purposes only. Actual models may be slightly different.

Outdoor - Heat Pump
37MBRAQ48AA3
48000
Voltage, Phase, Cycle V/Ph/Hz 208-230/1/60
MCA A. 39
MOPA A. 40
SCCR kA 5
Cooling Outdoor DB Min - Max °F(°C) -13~122(-25~50)
Heating Outdoor DB Min - Max °F(°C) -13~75(-25~24)
Min. Piping Length ft (m) 9.8 (3)
Standard Piping Length ft. (m) 24.6 (7.5)
Total Piping Length ft (m) 246(75)
Piping Lift*
ft (m) 98.4(30)
Pipe Connection Size - Liquid in (mm) 3/8"(9.52)
Pipe Connection Size - Suction in (mm) 3/4"(19)
R454B
Charge lbs (kg) 7.94(3.6)
Add'l Refrigerant (between Std & Max
Piping Lengths)
Oz/ft
(g/m) 0.32(30)
Face Area Sq. Ft. 6.61
2 22
10 TWIN-ROTARY
EKPQ420D1UMUA

ESTER OIL
Oil Charge Fl. Oz. 47.35
Rated Current RLA 7
Airflow CFM 4240.3
Sound Pressure dB(A) 62.5
Height in (mm) 52.48(1333)
Width in (mm) 37.48(952)
Depth in (mm) 16.34(415)
Net Weight lbs (kg) 208.78(94.7)
Shipping Height in (mm) 57.48(1460)
Shipping Width in (mm) 43.11(1095)
Shipping Depth in (mm) 19.49(495)
Shipping Net Weight lbs (kg) 237.44(107.7)
* Condensing unit above or below indoor unit
37MBRAQ48AA3

OUTDOOR STANDARD FEATURES
• Variable Speed (Inverter)
• Factory installed Base Pan Heater
• Factory installed Crankcase Heater
• Low Voltage Controls
• Auto-Restart function
• Condenser High Temp Protection
• Quiet operation
• Anti-corrosive fin coating
RESIDENTIAL APPLICATION LIMITED WARRANTY*
• Ten (10) years if properly registered within ninety (90) days after original installation, parts are warranted to the original purchaser for a period of ten (10) years. Otherwise, parts warranty is five (5) years.

System
Electrical
Operating Range
Refrigerant Type
Outdoor Size
Outdoor Model #
Piping
Refrigerant
Dimensions
No. Rows
Fins per inch
Circuits
Type
Model
Outdoor Coil
Compressor
Airflow & Sound
Oil Type
Carrier Corporation Copyright 2024 • Atlanta, GA, 30339

SUBJECT TO CHANGE WITHOUT NOTICE
475
Item5.

Air Handler Heat Pump Ductless System
Indoor Model: 45MBAAQ24XB3
Job Data: Location:

Tag #: Carrier#:

Date:

NOTE: Images for illustration purposes only. Actual models may be slightly different. 45MBAAQ24XB3
24000
Voltage, Phase, Cycle V/Ph/Hz 208-230/1/60
Power Supply
MCA A. 4
Cooling Indoor DB Min - Max °F(°C) 60~90 (16~32)
Heating Indoor DB Min - Max °F(°C) 32~86 (0~30)
Face Area Sq. Ft. 3
3 20
6 550/510/450
Airflow (highest to lowest) CFM 824.0 / 759.3 / 694.5 / 629.8 / - Sound Pressure (highest to lowest) dB(A) N\A/43.5/40/25.5/N\A Height in (mm) 45.00(1143)
Width in (mm) 17.52(445)
Depth in (mm) 21.02(534)
Net Weight lbs (kg) 104.28(47.3)
Shipping Height in (mm) 21.20(640)
Shipping Width in (mm) 48.23(1225)
Shipping Depth in (mm) 21.06(535)
Shipping Net Weight lbs (kg) 125.88(57.1)

CONTROLS
Standard
KSACN1401AAA
KSAIC0601230
Inch mm Inch mm
A Model Height 45 1143 49 1245
B Model Width 17.5 445 21 534
C S.A. Opening Width 15.6 397 19.1 486
D R.A. Opening Width 15.1 384 18.6 473
E Model Depth 21 534 21 534
F S.A. Opening Depth 10.3 260 10.3 260
G R.A. Opening Depth 18.8 476 18.8 476
H S.A. Opening Clearance 0.9 24 0.9 24
I R.A. Opening Side Clearance 1.3 32 1.3 32
J R.A. Opening Front Clearance 1.5 38 1.6 41
K R.A. Opening Back Clearance 0.6 16 0.6 16
Wireless Remote Controller (°F/°C Convertible)
Dimensions
Number of Fan Speeds
Fins per inch
Indoor Size
No. Rows
System
Electrical Indoor unit powered by outdoor unit
Operating Range
Indoor Coil
Indoor Model #
Circuits
Indoor Unit

INDOOR UNIT DIMENSIONS
Dimensions
18K/24K 36K
45MBAAQ24XB3

INDOOR STANDARD FEATURES
• Modes: Cool, Heat, Dry, Fan, Auto
• 4-way installation (Up flow, Down flow, Right, Left)
• Auto-Restart function
• Quiet indoor operation
• Aluminum hydrophilic pre-coated fins
RESIDENTIAL APPLICATION LIMITED WARRANTY*
• Ten (10) years if properly registered within ninety (90) days after original installation, parts are warranted to the original purchaser for a period of ten (10) years. Otherwise, parts warranty is five (5) years.

Wired Remote Control 7 Day Programmable
24V Mini Interface
Optional
Carrier Corporation Copyright 2024 • Atlanta, GA, 30339

SUBJECT TO CHANGE WITHOUT NOTICE
476
Item5.

Air Handler Heat Pump Ductless System
Indoor Model: 45MBAAQ36XB3
Job Data: Location:

Tag #: Carrier#:

Date:

NOTE: Images for illustration purposes only. Actual models may be slightly different. 45MBAAQ36XB3
36000
Voltage, Phase, Cycle V/Ph/Hz 208-230/1/60
Power Supply
MCA A. 6
Cooling Indoor DB Min - Max °F(°C) 60~90 (16~32)
Heating Indoor DB Min - Max °F(°C) 32~86 (0~30)
Face Area Sq. Ft. 4.13
4 20
10 685/620/560
Airflow (highest to lowest) CFM 1189.0 / 1083.0 / 971.2 / 865.2 / N\A Sound Pressure (highest to lowest) dB(A) N\A/48/44/35/N\A Height in (mm) 49.02(1245)
Width in (mm) 21.02(534)
Depth in (mm) 21.02(534)
Net Weight lbs (kg) 127.87(58)
Shipping Height in (mm) 21.20(640)
Shipping Width in (mm) 52.17(1325)
Shipping Depth in (mm) 24.61(625)
Shipping Net Weight lbs (kg) 154.10(69.9)

CONTROLS
Standard
KSACN1401AAA
KSAIC0601230
Inch mm Inch mm
A Model Height 45 1143 49 1245
B Model Width 17.5 445 21 534
C S.A. Opening Width 15.6 397 19.1 486
D R.A. Opening Width 15.1 384 18.6 473
E Model Depth 21 534 21 534
F S.A. Opening Depth 10.3 260 10.3 260
G R.A. Opening Depth 18.8 476 18.8 476
H S.A. Opening Clearance 0.9 24 0.9 24
I R.A. Opening Side Clearance 1.3 32 1.3 32
J R.A. Opening Front Clearance 1.5 38 1.6 41
K R.A. Opening Back Clearance 0.6 16 0.6 16
Wireless Remote Controller (°F/°C Convertible)
Dimensions
Number of Fan Speeds
Fins per inch
Indoor Size
No. Rows
System
Electrical Indoor unit powered by outdoor unit
Operating Range
Indoor Coil
Indoor Model #
Circuits
Indoor Unit

INDOOR UNIT DIMENSIONS
Dimensions
18K/24K 36K
45MBAAQ36XB3

INDOOR STANDARD FEATURES
• Modes: Cool, Heat, Dry, Fan, Auto
• 4-way installation (Up flow, Down flow, Right, Left)
• Auto-Restart function
• Quiet indoor operation
• Aluminum hydrophilic pre-coated fins
RESIDENTIAL APPLICATION LIMITED WARRANTY*
• Ten (10) years if properly registered within ninety (90) days after original installation, parts are warranted to the original purchaser for a period of ten (10) years. Otherwise, parts warranty is five (5) years.

Wired Remote Control 7 Day Programmable
24V Mini Interface
Optional
Carrier Corporation Copyright 2024 • Atlanta, GA, 30339

SUBJECT TO CHANGE WITHOUT NOTICE
477
Item5.

Air Handler Heat Pump Ductless System
Indoor Model: 45MBAAQ48XA3
Job Data: Location:

Tag #: Carrier#:

Date:

NOTE: Images for illustration purposes only. Actual models may be slightly different. 45MBAAQ48XA3
48000
Voltage, Phase, Cycle V/Ph/Hz 208-230/1/60
Power Supply
MCA A. 9.75
Cooling Indoor DB Min - Max °F(°C) 60~90(16~32)
Heating Indoor DB Min - Max °F(°C) 32~86(0~30)
5 20
14 820/720/615
Airflow (highest to lowest) CFM 1601.0 / 1471.5 / 1283.1 / 1094.8 / / Sound Pressure (highest to lowest) dB(A) 54.5/51/48
Height in (mm) 52.99(1346)
Width in (mm) 24.49(622)
Depth in (mm) 21.02(534)
Net Weight lbs (kg) 161.82(73.4)
Shipping Height in (mm) 21.20(640)
Shipping Width in (mm) 56.30(1430)
Shipping Depth in (mm) 28.15(715)
Shipping Net Weight lbs (kg) 191.58(86.9)

CONTROLS
Standard
KSACN1401AAA
KSAIC0601230
Inch mm Inch mm
A Model Height 49 1245 53 1346
B Model Width 21 534 24.5 622
C S.A. Opening Width 19.1 486 22.6 575
D R.A. Opening Width 18.6 473 22.1 562
E Model Depth 21 534 21 534
F S.A. Opening Depth 10.3 260 10.3 260
G R.A. Opening Depth 18.8 476 18.8 476
H S.A. Opening Clearance 0.9 24 0.9 24
I R.A. Opening Side Clearance 1.3 32 1.1 28
J R.A. Opening Front Clearance 1.6 41 1.6 41
K R.A. Opening Back Clearance 0.6 16 0.8 19
Wireless Remote Controller (°F/°C Convertible)
Dimensions
Number of Fan Speeds
Fins per inch
Indoor Size
No. Rows
System
Electrical Indoor unit powered by outdoor unit
Operating Range
Indoor Model #
Circuits
Indoor Unit

INDOOR UNIT DIMENSIONS
Dimensions
36K 48K/60K
45MBAAQ48XA3

INDOOR STANDARD FEATURES
• Modes: Cool, Heat, Dry, Fan, Auto
• 4-way installation (Up flow, Down flow, Right, Left)
• Auto-Restart function
• Quiet indoor operation
• Aluminum hydrophilic pre-coated fins
RESIDENTIAL APPLICATION LIMITED WARRANTY*
• Ten (10) years if properly registered within ninety (90) days after original installation, parts are warranted to the original purchaser for a period of ten (10) years. Otherwise, parts warranty is five (5) years.

Wired Remote Control 7 Day Programmable
24V Mini Interface
Optional
Indoor Coil
Carrier Corporation Copyright 2024 • Atlanta, GA, 30339

SUBJECT TO CHANGE WITHOUT NOTICE
478
Item5.

SUBMITTAL
Project
Climatec - City of Esc - Fire Station 5
Date
Saturday, April 12, 2025
Shawn Harlan
Sigler - Brea
205 Puente Street
Brea CA
479
Item5.

Table Of Contents
Project: Climatec - City of Esc - Fire Station 5 04/12/2025 Prepared By: Shawn Harlan
FS 5 ID1 3
Unit Report 4
Performance Summary 5
System Parameters 5
Electrical Data 5
Acoustic Summary 6
Certified Drawing 7
Residential Carrier Products Bldr 1.39j Page 2 of 9480
Item5.

FS 5 ID1
Project: Climatec - City of Esc - Fire Station 5 04/12/2025 Prepared By: Shawn Harlan
FS 5 ID1
FS 5 ID1
Submittal Cover Sheet
Unit Report
Performance Summary Report
Acoustic Summary
Certified Drawings
Residential Carrier Products Bldr 1.39j Page 3 of 9481
Item5.

Unit Report For FS 5 ID1
Project: Climatec - City of Esc - Fire Station 5 04/12/2025 Prepared By: Shawn Harlan
Unit Report
Outdoor Unit Parameters
Unit Model: 27SCA
Unit Size: 2 Tons (Size 24)
Voltage: 208/230-1-60 V-Ph-Hz
Indoor Coil Parameters
Unit Model: FT5A
Unit Size: 24,000 Btuh
Cabinet Insulation: Singular, TXV
Voltage: 208-1-60 V-Ph-Hz
Refrigerant Type: Puron Advance
Heating Size: No Heat
Outdoor Unit Dimensions and Weight
Unit Length: 31.1875 in
Unit Width: 31.1875 in
Unit Height: 35.5 in
Unit Shipping Weight: 196. lb
Indoor Coil Dimensions and Weight
Unit Length: 22.06 in
Unit Width: 17.6 in
Unit Height: 42.69 in
Unit Shipping Weight: 124. lb

RESIDENTIAL APPLICATIONS
This warranty is to the original purchasing owner and subsequent owners only to the extent and as stated in the Warranty Conditions and below.

The limited warranty period in years, depending on the part and the claimant, is as shown in the table below.

Limited Warranty (Years)
Item Original Owner Subsequent Owner
Parts 10* (or 5) 5
Compressor 10* (or 5) 5
*If properly registered within 90 days of original installation, otherwise 5 years (except in California and Quebec and other jurisdictions that prohibit warranty benefits conditioned on registration). See Warranty Conditions below.

OTHER APPLICATIONS
The warranty period is five (5) years on the compressor, and one (1) year on all other parts. The warranty is the original owner only and is not available for subsequent owners.

Ordering Information
Part Number Description Quantity
Outdoor Unit
27SCA524A003 27SCA Comfort Single Stage Heat Pump with Puron Refrigerant Advanced 2 Tons Cooling
1 15 SEER @ ARI Conditions
Indoor Coil
FT5ANXB24L00 Performance Series Fan Coil with Puron Advance 208/230-1-60 1 Singular, TXV
Aluminum
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 4 of 9
482
Item5.

Performance Summary For FS 5 ID1
Project: Climatec - City of Esc - Fire Station 5 04/12/2025 Prepared By: Shawn Harlan
Performance Summary
System Performance
System: 27SCA/FT5A
System Quantity: 1
Altitude: 0.0 ft
Linear Pipe Length: 0.0 ft
COP @ 47 F: 3.88
COP @ 17 F: 2.62
SEER @ ARI Conditions: 15.5
EER @ ARI Conditions: 12.0
HSPF @ ARI Conditions: 7.8
Actual Clg Airflow: 800.0 CFM
Standard Clg Airflow: 800.0 CFM
Total Net Clg Capacity: 22.81 MBH
Net Sensible Clg Capacity: 17.23 MBH
Htg HP Capacity: 24.06 MBH
Htg HP Integrated Capacity: 24.06 MBH
Heating HP Compressor Power: 1.73 kW
Total System Power: 2.41 kW
System Parameters
System Parameters
Outdoor Unit Parameters
Unit Model: 27SCA524A003
Unit Size (Nominal): 2 Tons (Size 24)
Voltage: 208/230-1-60 V-Ph-Hz
Clg Ent Air DB Ambient: 95.0 °F
Htg Ent Air DB Ambient: 47.0 °F
Indoor Coil Parameters
Unit Model: FT5ANXB24L00
Unit Size (Nominal): 24,000 Btuh
Voltage: 208-1-60 V-Ph-Hz
Ent Air DB: 80.00 °F
Ent Air WB: 67.00 °F
Ent Enthalpy: 31.44 BTU/lb
Lvg Air DB: 60.05 °F
Lvg Air WB: 58.11 °F
Lvg Enthalpy: 25.10 BTU/lb
Htg Ent Air DB: 70.0 °F
Htg Lvg Air DB: 97.8 °F
Heating Size (Nominal): No Heat
Total External Static Pressure: 0.50 in wg
Electrical Data
Electrical Data
Outdoor Electrical Data
Unit Voltage: 208/230-1-60 V-Ph-Hz
Fan Motor FLA: 0.60 Amps
MCA: 13.5 Amps
Max Fuse: 20 Amps
Operating Range Min: 197 V
Operating Range Max: 253 V
Compressor RLA: 10.3 Amps
Compressor LRA: 64.4 Amps
Indoor Electrical Data:
(For units with no factory installed electric heaters)
Unit Voltage: 208-1-60 V-Ph-Hz
Unit FLA: 4.0 Amps
Unit MCA: 5.0 Amps
Unit MOCP: 15.0 Amps
Unit Min Wire Size: 14.0
Unit Fuse/Ckt Bkr Amps: 15.0 Amps
Motor HP: 1/2 HP
Notice: Indoor Elect. data is for 208-1-60 voltage
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 5 of 9483
Item5.

Acoustic Summary For FS 5 ID1
Project: Climatec - City of Esc - Fire Station 5 04/12/2025 Prepared By: Shawn Harlan
Acoustic Summary
Outdoor Unit Parameters:
27SCA Unit Model:
2 Tons (Size 24) Unit Size:

Standard Variations:

Octave Band Center Frequency, Hz 125 250 500 1k 2k 4k 8k dBA Sound Power,dB 66.3 64.7 64.2 64.4 59.2 55.6 54.7
A-Weighted Sound Power, dBA 71.0
Indoor Coil Parameters:

FT5A Unit Model:
24,000 Btuh Unit Size:

Singular, TXV Cabinet Insulation:

Octave Band Center Frequency, Hz 63 125 250 500 1k 2k 4k Sound Power,dB 72.0 68.0 64.0 61.0 59.0 57.0 53.0
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 6 of 9484
Item5.

Certified Drawing For FS 5 ID1
Project: Climatec - City of Esc - Fire Station 5 04/12/2025 Prepared By: Shawn Harlan
Certified Drawing
Outdoor Model
Unit Model: 27SCA
Unit Size: 2 Tons (Size 24)
Voltage: 208/230-1-60 V-Ph-Hz
SEER: 15
PartNumber: 27SCA524A003
Shipping Dimensions and Weights Outdoor Unit
Height 39.81 in
Width 34.25 in
Length 34.25 in
Operating Weight 176. lb
Shipping Weight 196. lb
Dimensions

A B C D E F G H I J K

31.19 in 35.50 in 0.63 in 6.56 in 24.69 in 9.13 in 1.13 in 3.81 in 13.00 in 15.13 in 16.50 in The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 7 of 9485
Item5.

Certified Drawing For FS 5 ID1
Project: Climatec - City of Esc - Fire Station 5 04/12/2025 Prepared By: Shawn Harlan
Indoor Coil
Unit Model: FT5A
Unit Size: 24,000 Btuh
Voltage: 208-1-60 V-Ph-Hz
Cabinet Insulation: Singular, TXV
PartNumber: FT5ANXB24L00
Dimensions and Weights Indoor Coil
Height 42.69 in
Width 17.63 in
Length 22.06 in
Shipping Weight 124. lb
Dimensions

A B C D E F G H J

42.69 in 17.63 in 15.75 in 15.63 in 10.75 in 18.56 in 18.25 in -- -- The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 8 of 9486
Item5.

Certified Drawing For FS 5 ID1
Project: Climatec - City of Esc - Fire Station 5 04/12/2025 Prepared By: Shawn Harlan
Indoor Coil
Unit Model: FT5A
Unit Size: 24,000 Btuh
Voltage: 208-1-60 V-Ph-Hz
PartNumber: FT5ANXB24L00
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 9 of 9487
Item5.

SUBMITTAL
Project
Climatec - City of Esc - Fire Station 6
Date
Saturday, April 12, 2025
Shawn Harlan
Sigler - Brea
205 Puente Street
Brea CA
488
Item5.

Table Of Contents
Project: Climatec - City of Esc - Fire Station 6 04/12/2025 Prepared By: Shawn Harlan 08:29AM
ID 1,2 3
Unit Report 4
Certified Drawing 5
Performance Summary 8
ID 3,5 11
Unit Report 12
Certified Drawing 13
Performance Summary 16
Packaged Rooftop Builder 1.79i Page 2 of 18489
Item5.

ID 1,2
Project: Climatec - City of Esc - Fire Station 6 04/12/2025 Prepared By: Shawn Harlan 08:29AM
ID 1,2
ID 1,2
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 3 of 18 490
Item5.

Unit Report For ID 1,2
Project: Climatec - City of Esc - Fire Station 6 04/12/2025 Prepared By: Shawn Harlan 08:29AM
Unit Report
Unit Parameters
Unit Model: 50GEQM05A2M5-0A0A0
Unit Size: 05 (4 Tons)
Volts-Phase-Hertz: 208-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two Stage Cooling, Single Circuit
Duct Cfg: Vertical Supply / Vertical Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 6' 2.375''
Unit Width: 3' 10.625''
Unit Height: 3' 5.375''
Total Operating Weight: 607 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 4
Return Air Filter Size: 16 x 16 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
5-Year compressor parts (STD.)
1-Year parts (STD.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50GEQM05A2M5-0A0A0 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 4 of 18 491
Item5.

Certified Drawing for ID 1,2
Project: Climatec - City of Esc - Fire Station 6 04/12/2025 Prepared By: Shawn Harlan 08:29AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 5 of 18 492
Item5.

Certified Drawing for ID 1,2
Project: Climatec - City of Esc - Fire Station 6 04/12/2025 Prepared By: Shawn Harlan 08:29AM
Packaged Rooftop Builder 1.79i Page 6 of 18 493
Item5.

Certified Drawing for ID 1,2
Project: Climatec - City of Esc - Fire Station 6 04/12/2025 Prepared By: Shawn Harlan 08:29AM
Packaged Rooftop Builder 1.79i Page 7 of 18 494
Item5.

Performance Summary For ID 1,2
Project: Climatec - City of Esc - Fire Station 6 04/12/2025 Prepared By: Shawn Harlan 08:29AM
Performance Summary
Part Number:50GEQM05A2M5-0A0A0
Refrigerant: R-454B
ARI SEER: 17.00
ARI SEER2: 16.00
Application EER (Rooftop Unit only): 12.12
Base Unit Dimensions
Unit Length: 74.4 in
Unit Width: 46.6 in
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 594 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 13 lb
Total Operating Weight: 607 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Vertical
Fan Drive Type: Direct Drive
Actual Airflow: 1600 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 58.4 F
Evaporator Leaving Air WB: 57.1 F
Evaporator Leaving Air Enthalpy: 24.48 BTU/lb
Unit Discharge Air DB: 59.6 F
Unit Discharge Air WB: 57.6 F
Unit Discharge Air Enthalpy: 24.76 BTU/lb
Gross Cooling Capacity: 50.11 MBH
Net Cooling Capacity: 48.05 MBH
Gross Sensible Capacity: 37.34 MBH
Net Sensible Capacity: 35.28 MBH
Compressor Power Input: 3.18 kW
Coil Bypass Factor: 0.000
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 95.9 F
Total Heating Capacity: 44.80 MBH
Integrated Heating Capacity: 44.80 MBH
Heating Power Input: 3.60 kW
High Temperature COP: 3.80
Low Temperature COP: 2.50
HSPF: 7.2
High Temperature COP2: 3.80
Low Temperature COP2: 2.50
HSPF2: 7.2
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 1875
Fan Power: 0.71 BHP
Packaged Rooftop Builder 1.79i Page 8 of 18495
Item5.

Performance Summary For ID 1,2
Project: Climatec - City of Esc - Fire Station 6 04/12/2025 Prepared By: Shawn Harlan 08:29AM
NOTE: Selected IFM RPM Range: 1047 - 2170
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 15.6
Compressor #1 LRA: 112
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 7.1
Power Supply MCA: 28
Power Supply MOCP (Fuse or HACR): 40
Disconnect Size FLA: 28
Disconnect Size LRA: 125
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 1.3
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 92.4 90.1 85.6
125 Hz 83.3 78.3 84.7
250 Hz 77.0 72.0 80.5
500 Hz 71.9 64.5 76.0
1000 Hz 68.4 66.6 72.4
2000 Hz 65.2 57.5 68.0
4000 Hz 62.5 51.6 62.8
8000 Hz 59.4 45.1 59.3
A-Weighted 75.8 71.2 79.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Packaged Rooftop Builder 1.79i Page 9 of 18496
Item5.

Performance Summary For ID 1,2
Project: Climatec - City of Esc - Fire Station 6 04/12/2025 Prepared By: Shawn Harlan 08:29AM
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 700 RPM
900 RPM
1100 RPM
1300 RPM
1500 RPM1700 RPM
1900 RPM
2100 RPM 2300 RPM 2500 RPM

0.50 BHP

0.75 BHP

1.00 BHP

1.50 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 1875 BHP = 0.71 Maximum RPM = 2660 Maximum BHP = 3.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0

0.0 0.2

0.4 0.6

0.8 1.0

1.2 1.4

1.6 1.8

2.0 Packaged Rooftop Builder 1.79i Page 10 of 18497
Item5.

ID 3,5
Project: Climatec - City of Esc - Fire Station 6 04/12/2025 Prepared By: Shawn Harlan 08:29AM
ID 3,5
ID 3,5
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 11 of 18498
Item5.

Unit Report For ID 3,5
Project: Climatec - City of Esc - Fire Station 6 04/12/2025 Prepared By: Shawn Harlan 08:29AM
Unit Report
Unit Parameters
Unit Model: 50GEQM04A2M5-0A0A0
Unit Size: 04 (3 Tons)
Volts-Phase-Hertz: 208-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two Stage Cooling, Single Circuit
Duct Cfg: Vertical Supply / Vertical Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 6' 2.375''
Unit Width: 3' 10.625''
Unit Height: 3' 5.375''
Total Operating Weight: 580 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 2
Return Air Filter Size: 16 x 25 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
5-Year compressor parts (STD.)
1-Year parts (STD.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50GEQM04A2M5-0A0A0 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 12 of 18499
Item5.

Certified Drawing for ID 3,5
Project: Climatec - City of Esc - Fire Station 6 04/12/2025 Prepared By: Shawn Harlan 08:29AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 13 of 18500
Item5.

Certified Drawing for ID 3,5
Project: Climatec - City of Esc - Fire Station 6 04/12/2025 Prepared By: Shawn Harlan 08:29AM
Packaged Rooftop Builder 1.79i Page 14 of 18501
Item5.

Certified Drawing for ID 3,5
Project: Climatec - City of Esc - Fire Station 6 04/12/2025 Prepared By: Shawn Harlan 08:29AM
Packaged Rooftop Builder 1.79i Page 15 of 18502
Item5.

Performance Summary For ID 3,5
Project: Climatec - City of Esc - Fire Station 6 04/12/2025 Prepared By: Shawn Harlan 08:29AM
Performance Summary
Part Number:50GEQM04A2M5-0A0A0
Refrigerant: R-454B
ARI SEER: 17.00
ARI SEER2: 16.00
Application EER (Rooftop Unit only): 11.89
Base Unit Dimensions
Unit Length: 74.4 in
Unit Width: 46.6 in
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 567 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 13 lb
Total Operating Weight: 580 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Vertical
Fan Drive Type: Direct Drive
Actual Airflow: 1200 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 58.5 F
Evaporator Leaving Air WB: 57.2 F
Evaporator Leaving Air Enthalpy: 24.52 BTU/lb
Unit Discharge Air DB: 59.7 F
Unit Discharge Air WB: 57.7 F
Unit Discharge Air Enthalpy: 24.81 BTU/lb
Gross Cooling Capacity: 37.36 MBH
Net Cooling Capacity: 35.79 MBH
Gross Sensible Capacity: 27.90 MBH
Net Sensible Capacity: 26.33 MBH
Compressor Power Input: 2.37 kW
Coil Bypass Factor: 0.027
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 96.1 F
Total Heating Capacity: 33.80 MBH
Integrated Heating Capacity: 33.80 MBH
Heating Power Input: 2.60 kW
High Temperature COP: 3.90
Low Temperature COP: 2.40
HSPF: 8.0
High Temperature COP2: 3.90
Low Temperature COP2: 2.40
HSPF2: 6.7
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 1946
Fan Power: 0.54 BHP
Packaged Rooftop Builder 1.79i Page 16 of 18503
Item5.

Performance Summary For ID 3,5
Project: Climatec - City of Esc - Fire Station 6 04/12/2025 Prepared By: Shawn Harlan 08:29AM
NOTE: Selected IFM RPM Range: 1058 - 2190
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 11.2
Compressor #1 LRA: 82
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 5.1
Power Supply MCA: 22
Power Supply MOCP (Fuse or HACR): 30
Disconnect Size FLA: 22
Disconnect Size LRA: 93
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 2.6
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 92.4 86.1 85.6
125 Hz 83.6 79.2 84.7
250 Hz 76.5 70.0 80.5
500 Hz 69.1 62.8 76.0
1000 Hz 66.5 64.1 72.4
2000 Hz 63.5 55.8 68.0
4000 Hz 59.4 50.0 62.8
8000 Hz 57.1 43.3 59.3
A-Weighted 74.6 69.3 79.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Packaged Rooftop Builder 1.79i Page 17 of 18504
Item5.

Performance Summary For ID 3,5
Project: Climatec - City of Esc - Fire Station 6 04/12/2025 Prepared By: Shawn Harlan 08:29AM
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 500 RPM
700 RPM
900 RPM
1100 RPM
1300 RPM
1500 RPM
1700 RPM
1900 RPM
2100 RPM
2300 RPM
2500 RPM

0.50 BHP

0.75 BHP

1.00 BHP

1.50 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 1946 BHP = 0.54 Maximum RPM = 2490 Maximum BHP = 3.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.3 0.6 0.9 1.2 1.5 1.8

0.0 0.2

0.4 0.6

0.8 1.0

1.2 1.4

1.6 1.8

2.0 Packaged Rooftop Builder 1.79i Page 18 of 18505
Item5.

SUBMITTAL
Project
Climatec - City of Esc - Fire Station 7
Date
Saturday, April 12, 2025
Shawn Harlan
Sigler - Brea
205 Puente Street
Brea CA
506
Item5.

Table Of Contents
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
ID 1,5 3
Unit Report 4
Certified Drawing 5
Performance Summary 8
ID 2,4 11
Unit Report 12
Certified Drawing 13
Performance Summary 16
ID 7 19
Unit Report 20
Certified Drawing 21
Performance Summary 24
Packaged Rooftop Builder 1.79i Page 2 of 26507
Item5.

ID 1,5
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
ID 1,5
ID 1,5
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 3 of 26 508
Item5.

Unit Report For ID 1,5
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
Unit Report
Unit Parameters
Unit Model: 50GEQM05A2M5-0A0A0
Unit Size: 05 (4 Tons)
Volts-Phase-Hertz: 208-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two Stage Cooling, Single Circuit
Duct Cfg: Vertical Supply / Vertical Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 6' 2.375''
Unit Width: 3' 10.625''
Unit Height: 3' 5.375''
Total Operating Weight: 607 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 4
Return Air Filter Size: 16 x 16 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
5-Year compressor parts (STD.)
1-Year parts (STD.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50GEQM05A2M5-0A0A0 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 4 of 26 509
Item5.

Certified Drawing for ID 1,5
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 5 of 26 510
Item5.

Certified Drawing for ID 1,5
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
Packaged Rooftop Builder 1.79i Page 6 of 26 511
Item5.

Certified Drawing for ID 1,5
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
Packaged Rooftop Builder 1.79i Page 7 of 26 512
Item5.

Performance Summary For ID 1,5
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
Performance Summary
Part Number:50GEQM05A2M5-0A0A0
Refrigerant: R-454B
ARI SEER: 17.00
ARI SEER2: 16.00
Application EER (Rooftop Unit only): 12.12
Base Unit Dimensions
Unit Length: 74.4 in
Unit Width: 46.6 in
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 594 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 13 lb
Total Operating Weight: 607 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Vertical
Fan Drive Type: Direct Drive
Actual Airflow: 1600 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 58.4 F
Evaporator Leaving Air WB: 57.1 F
Evaporator Leaving Air Enthalpy: 24.48 BTU/lb
Unit Discharge Air DB: 59.6 F
Unit Discharge Air WB: 57.6 F
Unit Discharge Air Enthalpy: 24.76 BTU/lb
Gross Cooling Capacity: 50.11 MBH
Net Cooling Capacity: 48.05 MBH
Gross Sensible Capacity: 37.34 MBH
Net Sensible Capacity: 35.28 MBH
Compressor Power Input: 3.18 kW
Coil Bypass Factor: 0.000
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 95.9 F
Total Heating Capacity: 44.80 MBH
Integrated Heating Capacity: 44.80 MBH
Heating Power Input: 3.60 kW
High Temperature COP: 3.80
Low Temperature COP: 2.50
HSPF: 7.2
High Temperature COP2: 3.80
Low Temperature COP2: 2.50
HSPF2: 7.2
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 1875
Fan Power: 0.71 BHP
Packaged Rooftop Builder 1.79i Page 8 of 26513
Item5.

Performance Summary For ID 1,5
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
NOTE: Selected IFM RPM Range: 1047 - 2170
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 15.6
Compressor #1 LRA: 112
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 7.1
Power Supply MCA: 28
Power Supply MOCP (Fuse or HACR): 40
Disconnect Size FLA: 28
Disconnect Size LRA: 125
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 1.3
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 92.4 90.1 85.6
125 Hz 83.3 78.3 84.7
250 Hz 77.0 72.0 80.5
500 Hz 71.9 64.5 76.0
1000 Hz 68.4 66.6 72.4
2000 Hz 65.2 57.5 68.0
4000 Hz 62.5 51.6 62.8
8000 Hz 59.4 45.1 59.3
A-Weighted 75.8 71.2 79.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Packaged Rooftop Builder 1.79i Page 9 of 26514
Item5.

Performance Summary For ID 1,5
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 700 RPM
900 RPM
1100 RPM
1300 RPM
1500 RPM1700 RPM
1900 RPM
2100 RPM 2300 RPM 2500 RPM

0.50 BHP

0.75 BHP

1.00 BHP

1.50 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 1875 BHP = 0.71 Maximum RPM = 2660 Maximum BHP = 3.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0

0.0 0.2

0.4 0.6

0.8 1.0

1.2 1.4

1.6 1.8

2.0 Packaged Rooftop Builder 1.79i Page 10 of 26515
Item5.

ID 2,4
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
ID 2,4
ID 2,4
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 11 of 26516
Item5.

Unit Report For ID 2,4
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
Unit Report
Unit Parameters
Unit Model: 50GEQM04A2M5-0A0A0
Unit Size: 04 (3 Tons)
Volts-Phase-Hertz: 208-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two Stage Cooling, Single Circuit
Duct Cfg: Vertical Supply / Vertical Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 6' 2.375''
Unit Width: 3' 10.625''
Unit Height: 3' 5.375''
Total Operating Weight: 580 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 2
Return Air Filter Size: 16 x 25 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
5-Year compressor parts (STD.)
1-Year parts (STD.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50GEQM04A2M5-0A0A0 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 12 of 26517
Item5.

Certified Drawing for ID 2,4
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 13 of 26518
Item5.

Certified Drawing for ID 2,4
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
Packaged Rooftop Builder 1.79i Page 14 of 26519
Item5.

Certified Drawing for ID 2,4
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
Packaged Rooftop Builder 1.79i Page 15 of 26520
Item5.

Performance Summary For ID 2,4
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
Performance Summary
Part Number:50GEQM04A2M5-0A0A0
Refrigerant: R-454B
ARI SEER: 17.00
ARI SEER2: 16.00
Application EER (Rooftop Unit only): 11.89
Base Unit Dimensions
Unit Length: 74.4 in
Unit Width: 46.6 in
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 567 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 13 lb
Total Operating Weight: 580 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Vertical
Fan Drive Type: Direct Drive
Actual Airflow: 1200 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 58.5 F
Evaporator Leaving Air WB: 57.2 F
Evaporator Leaving Air Enthalpy: 24.52 BTU/lb
Unit Discharge Air DB: 59.7 F
Unit Discharge Air WB: 57.7 F
Unit Discharge Air Enthalpy: 24.81 BTU/lb
Gross Cooling Capacity: 37.36 MBH
Net Cooling Capacity: 35.79 MBH
Gross Sensible Capacity: 27.90 MBH
Net Sensible Capacity: 26.33 MBH
Compressor Power Input: 2.37 kW
Coil Bypass Factor: 0.027
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 96.1 F
Total Heating Capacity: 33.80 MBH
Integrated Heating Capacity: 33.80 MBH
Heating Power Input: 2.60 kW
High Temperature COP: 3.90
Low Temperature COP: 2.40
HSPF: 8.0
High Temperature COP2: 3.90
Low Temperature COP2: 2.40
HSPF2: 6.7
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 1946
Fan Power: 0.54 BHP
Packaged Rooftop Builder 1.79i Page 16 of 26521
Item5.

Performance Summary For ID 2,4
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
NOTE: Selected IFM RPM Range: 1058 - 2190
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 11.2
Compressor #1 LRA: 82
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 5.1
Power Supply MCA: 22
Power Supply MOCP (Fuse or HACR): 30
Disconnect Size FLA: 22
Disconnect Size LRA: 93
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 2.6
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 92.4 86.1 85.6
125 Hz 83.6 79.2 84.7
250 Hz 76.5 70.0 80.5
500 Hz 69.1 62.8 76.0
1000 Hz 66.5 64.1 72.4
2000 Hz 63.5 55.8 68.0
4000 Hz 59.4 50.0 62.8
8000 Hz 57.1 43.3 59.3
A-Weighted 74.6 69.3 79.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Packaged Rooftop Builder 1.79i Page 17 of 26522
Item5.

Performance Summary For ID 2,4
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 500 RPM
700 RPM
900 RPM
1100 RPM
1300 RPM
1500 RPM
1700 RPM
1900 RPM
2100 RPM
2300 RPM
2500 RPM

0.50 BHP

0.75 BHP

1.00 BHP

1.50 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 1946 BHP = 0.54 Maximum RPM = 2490 Maximum BHP = 3.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.3 0.6 0.9 1.2 1.5 1.8

0.0 0.2

0.4 0.6

0.8 1.0

1.2 1.4

1.6 1.8

2.0 Packaged Rooftop Builder 1.79i Page 18 of 26523
Item5.

ID 7
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
ID 7
ID 7
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 19 of 26524
Item5.

Unit Report For ID 7
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
Unit Report
Unit Parameters
Unit Model: 50GEQM06A2M5-0A0A0
Unit Size: 06 (5 Tons)
Volts-Phase-Hertz: 208-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two Stage Cooling, Single Circuit
Duct Cfg: Vertical Supply / Vertical Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 6' 2.375''
Unit Width: 3' 10.625''
Unit Height: 3' 5.375''
Total Operating Weight: 613 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 4
Return Air Filter Size: 16 x 16 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
5-Year compressor parts (STD.)
1-Year parts (STD.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50GEQM06A2M5-0A0A0 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 20 of 26525
Item5.

Certified Drawing for ID 7
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 21 of 26526
Item5.

Certified Drawing for ID 7
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
Packaged Rooftop Builder 1.79i Page 22 of 26527
Item5.

Certified Drawing for ID 7
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
Packaged Rooftop Builder 1.79i Page 23 of 26528
Item5.

Performance Summary For ID 7
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
Performance Summary
Part Number:50GEQM06A2M5-0A0A0
Refrigerant: R-454B
ARI SEER: 17.00
ARI SEER2: 16.00
Application EER (Rooftop Unit only): 11.77
Base Unit Dimensions
Unit Length: 74.4 in
Unit Width: 46.6 in
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 596 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 17 lb
Total Operating Weight: 613 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Vertical
Fan Drive Type: Direct Drive
Actual Airflow: 2000 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 57.3 F
Evaporator Leaving Air WB: 57.1 F
Evaporator Leaving Air Enthalpy: 24.49 BTU/lb
Unit Discharge Air DB: 58.5 F
Unit Discharge Air WB: 57.6 F
Unit Discharge Air Enthalpy: 24.78 BTU/lb
Gross Cooling Capacity: 62.53 MBH
Net Cooling Capacity: 59.91 MBH
Gross Sensible Capacity: 49.01 MBH
Net Sensible Capacity: 46.39 MBH
Compressor Power Input: 4.02 kW
Coil Bypass Factor: 0.014
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 95.2 F
Total Heating Capacity: 54.50 MBH
Integrated Heating Capacity: 54.50 MBH
Heating Power Input: 4.20 kW
High Temperature COP: 3.80
Low Temperature COP: 2.50
HSPF: 7.2
High Temperature COP2: 3.80
Low Temperature COP2: 2.50
HSPF2: 7.2
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 2036
Fan Power: 0.90 BHP
Packaged Rooftop Builder 1.79i Page 24 of 26529
Item5.

Performance Summary For ID 7
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
NOTE: Selected IFM RPM Range: 1228 - 2390
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 15.4
Compressor #1 LRA: 150
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 9.2
Power Supply MCA: 30
Power Supply MOCP (Fuse or HACR): 45
Disconnect Size FLA: 30
Disconnect Size LRA: 166
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 1.3
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 92.3 90.8 85.6
125 Hz 83.5 79.7 84.7
250 Hz 77.6 72.4 80.5
500 Hz 73.9 66.4 76.0
1000 Hz 70.7 68.5 72.4
2000 Hz 67.7 59.3 68.0
4000 Hz 64.3 53.1 62.8
8000 Hz 60.4 46.8 59.3
A-Weighted 77.2 72.6 79.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Packaged Rooftop Builder 1.79i Page 25 of 26530
Item5.

Performance Summary For ID 7
Project: Climatec - City of Esc - Fire Station 7 04/12/2025 Prepared By: Shawn Harlan 08:35AM
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 900 RPM
1100 RPM
1300 RPM
1500 RPM
1700 RPM
1900 RPM
2100 RPM
2300 RPM 2500 RPM 2700 RPM
2900 RPM

0.50 BHP 0.75 BHP

1.00 BHP

1.50 BHP

2.00 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 2036 BHP = 0.90 Maximum RPM = 2836 Maximum BHP = 3.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0

0.0 0.2

0.4 0.6

0.8 1.0

1.2 1.4

1.6 1.8

2.0 Packaged Rooftop Builder 1.79i Page 26 of 26531
Item5.

Outdoor Heat Pump Ductless System
Outdoor Model:

Job Data: Location:

Tag #: Carrier#:

Date:

NOTE: Images for illustration purposes only. Actual models may be slightly different.

Outdoor - Heat Pump
37MBRAQ48AA3
48000
Voltage, Phase, Cycle V/Ph/Hz 208-230/1/60
MCA A. 39
MOPA A. 40
SCCR kA 5
Cooling Outdoor DB Min - Max °F(°C) -13~122(-25~50)
Heating Outdoor DB Min - Max °F(°C) -13~75(-25~24)
Min. Piping Length ft (m) 9.8 (3)
Standard Piping Length ft. (m) 24.6 (7.5)
Total Piping Length ft (m) 246(75)
Piping Lift*
ft (m) 98.4(30)
Pipe Connection Size - Liquid in (mm) 3/8"(9.52)
Pipe Connection Size - Suction in (mm) 3/4"(19)
R454B
Charge lbs (kg) 7.94(3.6)
Add'l Refrigerant (between Std & Max
Piping Lengths)
Oz/ft
(g/m) 0.32(30)
Face Area Sq. Ft. 6.61
2 22
10 TWIN-ROTARY
EKPQ420D1UMUA

ESTER OIL
Oil Charge Fl. Oz. 47.35
Rated Current RLA 7
Airflow CFM 4240.3
Sound Pressure dB(A) 62.5
Height in (mm) 52.48(1333)
Width in (mm) 37.48(952)
Depth in (mm) 16.34(415)
Net Weight lbs (kg) 208.78(94.7)
Shipping Height in (mm) 57.48(1460)
Shipping Width in (mm) 43.11(1095)
Shipping Depth in (mm) 19.49(495)
Shipping Net Weight lbs (kg) 237.44(107.7)
* Condensing unit above or below indoor unit
37MBRAQ48AA3

OUTDOOR STANDARD FEATURES
• Variable Speed (Inverter)
• Factory installed Base Pan Heater
• Factory installed Crankcase Heater
• Low Voltage Controls
• Auto-Restart function
• Condenser High Temp Protection
• Quiet operation
• Anti-corrosive fin coating
RESIDENTIAL APPLICATION LIMITED WARRANTY*
• Ten (10) years if properly registered within ninety (90) days after original installation, parts are warranted to the original purchaser for a period of ten (10) years. Otherwise, parts warranty is five (5) years.

System
Electrical
Operating Range
Refrigerant Type
Outdoor Size
Outdoor Model #
Piping
Refrigerant
Dimensions
No. Rows
Fins per inch
Circuits
Type
Model
Outdoor Coil
Compressor
Airflow & Sound
Oil Type
Carrier Corporation Copyright 2024 • Atlanta, GA, 30339

SUBJECT TO CHANGE WITHOUT NOTICE
532
Item5.

Air Handler Heat Pump Ductless System
Indoor Model: 45MBAAQ48XA3
Job Data: Location:

Tag #: Carrier#:

Date:

NOTE: Images for illustration purposes only. Actual models may be slightly different. 45MBAAQ48XA3
48000
Voltage, Phase, Cycle V/Ph/Hz 208-230/1/60
Power Supply
MCA A. 9.75
Cooling Indoor DB Min - Max °F(°C) 60~90(16~32)
Heating Indoor DB Min - Max °F(°C) 32~86(0~30)
5 20
14 820/720/615
Airflow (highest to lowest) CFM 1601.0 / 1471.5 / 1283.1 / 1094.8 / / Sound Pressure (highest to lowest) dB(A) 54.5/51/48
Height in (mm) 52.99(1346)
Width in (mm) 24.49(622)
Depth in (mm) 21.02(534)
Net Weight lbs (kg) 161.82(73.4)
Shipping Height in (mm) 21.20(640)
Shipping Width in (mm) 56.30(1430)
Shipping Depth in (mm) 28.15(715)
Shipping Net Weight lbs (kg) 191.58(86.9)

CONTROLS
Standard
KSACN1401AAA
KSAIC0601230
Inch mm Inch mm
A Model Height 49 1245 53 1346
B Model Width 21 534 24.5 622
C S.A. Opening Width 19.1 486 22.6 575
D R.A. Opening Width 18.6 473 22.1 562
E Model Depth 21 534 21 534
F S.A. Opening Depth 10.3 260 10.3 260
G R.A. Opening Depth 18.8 476 18.8 476
H S.A. Opening Clearance 0.9 24 0.9 24
I R.A. Opening Side Clearance 1.3 32 1.1 28
J R.A. Opening Front Clearance 1.6 41 1.6 41
K R.A. Opening Back Clearance 0.6 16 0.8 19
Wireless Remote Controller (°F/°C Convertible)
Dimensions
Number of Fan Speeds
Fins per inch
Indoor Size
No. Rows
System
Electrical Indoor unit powered by outdoor unit
Operating Range
Indoor Model #
Circuits
Indoor Unit

INDOOR UNIT DIMENSIONS
Dimensions
36K 48K/60K
45MBAAQ48XA3

INDOOR STANDARD FEATURES
• Modes: Cool, Heat, Dry, Fan, Auto
• 4-way installation (Up flow, Down flow, Right, Left)
• Auto-Restart function
• Quiet indoor operation
• Aluminum hydrophilic pre-coated fins
RESIDENTIAL APPLICATION LIMITED WARRANTY*
• Ten (10) years if properly registered within ninety (90) days after original installation, parts are warranted to the original purchaser for a period of ten (10) years. Otherwise, parts warranty is five (5) years.

Wired Remote Control 7 Day Programmable
24V Mini Interface
Optional
Indoor Coil
Carrier Corporation Copyright 2024 • Atlanta, GA, 30339

SUBJECT TO CHANGE WITHOUT NOTICE
533
Item5.

SUBMITTAL
Project
Climatec - City of Esc - HARFF
Date
Saturday, April 12, 2025
Shawn Harlan
Sigler - Brea
205 Puente Street
Brea CA
534
Item5.

Table Of Contents
Project: Climatec - City of Esc - HARFF 04/12/2025
Prepared By: Shawn Harlan 09:23AM
ID 16 3
Unit Report 4
Certified Drawing 5
Performance Summary 7
ID 20 10
Unit Report 11
Certified Drawing 12
Performance Summary 15
Packaged Rooftop Builder 1.79i Page 2 of 17535
Item5.

ID 16
Project: Climatec - City of Esc - HARFF 04/12/2025
Prepared By: Shawn Harlan 09:23AM
ID 16
ID 16
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 3 of 17 536
Item5.

Unit Report For ID 16
Project: Climatec - City of Esc - HARFF 04/12/2025
Prepared By: Shawn Harlan 09:23AM
Unit Report
Unit Parameters
Unit Model: 50FEQM14A2M6-0A0A0
Unit Size: 14 (12.5 Tons)
Volts-Phase-Hertz: 460-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two-Stage Cooling, Single Circuit
Duct Cfg: Vertical Supply / Vertical Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 9' 7.875''
Unit Width: 5' 3.375''
Unit Height: 4' 9.375''
Total Operating Weight: 1284 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 6
Return Air Filter Size: 18 x 24 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
1-Year parts (STD.)
5-Year Compressor (std.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50FEQM14A2M6-0A0A0 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 4 of 17 537
Item5.

Certified Drawing for ID 16
Project: Climatec - City of Esc - HARFF 04/12/2025
Prepared By: Shawn Harlan 09:23AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 5 of 17 538
Item5.

Certified Drawing for ID 16
Project: Climatec - City of Esc - HARFF 04/12/2025
Prepared By: Shawn Harlan 09:23AM
Packaged Rooftop Builder 1.79i Page 6 of 17 539
Item5.

Performance Summary For ID 16
Project: Climatec - City of Esc - HARFF 04/12/2025
Prepared By: Shawn Harlan 09:23AM
Performance Summary
Part Number:50FEQM14A2M6-0A0A0
Refrigerant: R-454B
ARI EER: 10.60
Application EER (Rooftop Unit only): 11.00
IEER: 15.0
Base Unit Dimensions
Unit Length: 115.9 in
Unit Width: 63.4 in
Unit Height: 57.4 in
Operating Weight
Base Unit Weight: 1250 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 34 lb
Total Operating Weight: 1284 lb
Unit
Unit Voltage-Phase-Hertz: 460-3-60
Air Discharge: Vertical
Fan Drive Type: Vane Axial
Actual Airflow: 5000 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 58.7 F
Evaporator Leaving Air WB: 57.3 F
Evaporator Leaving Air Enthalpy: 24.58 BTU/lb
Unit Discharge Air DB: 59.7 F
Unit Discharge Air WB: 57.7 F
Unit Discharge Air Enthalpy: 24.82 BTU/lb
Gross Cooling Capacity: 154.23 MBH
Net Cooling Capacity: 148.81 MBH
Gross Sensible Capacity: 115.02 MBH
Net Sensible Capacity: 109.60 MBH
Compressor Power Input: 11.34 kW
Coil Bypass Factor: 0.059
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 95.3 F
Total Heating Capacity: 136.50 MBH
Integrated Heating Capacity: 136.50 MBH
Heating Power Input: 11.06 kW
High Temperature COP: 3.30
Low Temperature COP: 2.05
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 1546
Fan Power: 1.86 BHP
NOTE: Selected IFM RPM Range: 947 - 2200
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Packaged Rooftop Builder 1.79i Page 7 of 17540
Item5.

Performance Summary For ID 16
Project: Climatec - City of Esc - HARFF 04/12/2025
Prepared By: Shawn Harlan 09:23AM
Voltage Range: 414 - 506
Compressor #1 RLA: 8.8
Compressor #1 LRA: 75
Compressor #2 RLA: 8.8
Compressor #2 LRA: 75
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 3.5
Power Supply MCA: 26
Power Supply MOCP (Fuse or HACR): 30
Disconnect Size FLA: 27
Disconnect Size LRA: 163
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 3 / 0.8
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 87.5 82.2 89.3
125 Hz 81.9 76.2 85.2
250 Hz 78.4 71.9 80.3
500 Hz 75.6 68.2 78.0
1000 Hz 76.7 67.9 77.0
2000 Hz 72.2 61.2 74.4
4000 Hz 66.4 52.3 73.7
8000 Hz 58.3 46.7 68.9
A-Weighted 80.3 71.7 83.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 89.3 85.2 80.3 78.0 77.0 74.4 73.7 68.9 91.6 Lw
Packaged Rooftop Builder 1.79i Page 8 of 17541
Item5.

Performance Summary For ID 16
Project: Climatec - City of Esc - HARFF 04/12/2025
Prepared By: Shawn Harlan 09:23AM
B 63.1 69.1 71.7 74.8 77.0 75.6 74.7 67.8 82.5 LwA
C 56.9 52.8 47.9 45.6 44.6 42.0 41.3 36.5 59.2 Lp
D 30.7 36.7 39.3 42.4 44.6 43.2 42.3 35.4 50.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 200 RPM
400 RPM
600 RPM
800 RPM
1000 RPM
1200 RPM 1400 RPM
1600 RPM 1800 RPM
2000 RPM

1.50 BHP

2.00 BHP

3.00 BHP

5.00 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 1546 BHP = 1.86 Maximum RPM = 2200 Maximum BHP = 5.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0

0.0 0.5

1.0 1.5

2.0 Packaged Rooftop Builder 1.79i Page 9 of 17542
Item5.

ID 20
Project: Climatec - City of Esc - HARFF 04/12/2025
Prepared By: Shawn Harlan 09:23AM
ID 20
ID 20
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 10 of 17543
Item5.

Unit Report For ID 20
Project: Climatec - City of Esc - HARFF 04/12/2025
Prepared By: Shawn Harlan 09:23AM
Unit Report
Unit Parameters
Unit Model: 50FEQM08A2M6-0A0A0
Unit Size: 08 (7.5 Tons)
Volts-Phase-Hertz: 460-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two-Stage Cooling, Single Circuit
Duct Cfg: Vertical Supply / Vertical Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 7' 4.125''
Unit Width: 4' 11.5''
Unit Height: 3' 0.375''
Total Operating Weight: 821 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 4
Return Air Filter Size: 20 x 20 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
1-Year parts (STD.)
5-Year Compressor (std.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50FEQM08A2M6-0A0A0 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 11 of 17544
Item5.

Certified Drawing for ID 20
Project: Climatec - City of Esc - HARFF 04/12/2025
Prepared By: Shawn Harlan 09:23AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 12 of 17545
Item5.

Certified Drawing for ID 20
Project: Climatec - City of Esc - HARFF 04/12/2025
Prepared By: Shawn Harlan 09:23AM
Packaged Rooftop Builder 1.79i Page 13 of 17546
Item5.

Certified Drawing for ID 20
Project: Climatec - City of Esc - HARFF 04/12/2025
Prepared By: Shawn Harlan 09:23AM
Packaged Rooftop Builder 1.79i Page 14 of 17547
Item5.

Performance Summary For ID 20
Project: Climatec - City of Esc - HARFF 04/12/2025
Prepared By: Shawn Harlan 09:23AM
Performance Summary
Part Number:50FEQM08A2M6-0A0A0
Refrigerant: R-454B
ARI EER: 11.20
Application EER (Rooftop Unit only): 11.32
IEER: 15.0
Base Unit Dimensions
Unit Length: 88.1 in
Unit Width: 59.5 in
Unit Height: 36.4 in
Operating Weight
Base Unit Weight: 805 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 16 lb
Total Operating Weight: 821 lb
Unit
Unit Voltage-Phase-Hertz: 460-3-60
Air Discharge: Vertical
Fan Drive Type: Vane Axial
Actual Airflow: 3000 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 57.8 F
Evaporator Leaving Air WB: 57.1 F
Evaporator Leaving Air Enthalpy: 24.47 BTU/lb
Unit Discharge Air DB: 59.0 F
Unit Discharge Air WB: 57.6 F
Unit Discharge Air Enthalpy: 24.75 BTU/lb
Gross Cooling Capacity: 94.00 MBH
Net Cooling Capacity: 90.28 MBH
Gross Sensible Capacity: 71.86 MBH
Net Sensible Capacity: 68.14 MBH
Compressor Power Input: 6.29 kW
Coil Bypass Factor: 0.061
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 96.1 F
Total Heating Capacity: 84.60 MBH
Integrated Heating Capacity: 84.60 MBH
Heating Power Input: 7.40 kW
High Temperature COP: 3.40
Low Temperature COP: 2.25
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 1528
Fan Power: 1.28 BHP
NOTE: Selected IFM RPM Range: 920 - 2000
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Packaged Rooftop Builder 1.79i Page 15 of 17548
Item5.

Performance Summary For ID 20
Project: Climatec - City of Esc - HARFF 04/12/2025
Prepared By: Shawn Harlan 09:23AM
Voltage Range: 414 - 506
Compressor #1 RLA: 6.4
Compressor #1 LRA: 49
Compressor #2 RLA: 6.4
Compressor #2 LRA: 49
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 3
Power Supply MCA: 19
Power Supply MOCP (Fuse or HACR): 25
Disconnect Size FLA: 20
Disconnect Size LRA: 106
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 2 / 0.8
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 87.2 83.1 89.7
125 Hz 82.9 76.8 81.5
250 Hz 75.6 70.5 80.5
500 Hz 72.7 65.1 79.2
1000 Hz 73.7 65.3 77.1
2000 Hz 69.4 59.0 73.2
4000 Hz 64.8 52.2 70.2
8000 Hz 55.8 47.0 67.4
A-Weighted 77.7 69.7 82.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 89.7 81.5 80.5 79.2 77.1 73.2 70.2 67.4 91.3 Lw
Packaged Rooftop Builder 1.79i Page 16 of 17549
Item5.

Performance Summary For ID 20
Project: Climatec - City of Esc - HARFF 04/12/2025
Prepared By: Shawn Harlan 09:23AM
B 63.5 65.4 71.9 76.0 77.1 74.4 71.2 66.3 82.0 LwA
C 57.3 49.1 48.1 46.8 44.7 40.8 37.8 35.0 58.9 Lp
D 31.1 33.0 39.5 43.6 44.7 42.0 38.8 33.9 49.6 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 200 RPM
400 RPM
600 RPM
800 RPM
1000 RPM
1200 RPM
1400 RPM
1600 RPM 1800 RPM
2000 RPM 2200 RPM

1.50 BHP

2.00 BHP

3.00 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 1528 BHP = 1.28 Maximum RPM = 2200 Maximum BHP = 3.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0

0.0 0.5

1.0 1.5

2.0 Packaged Rooftop Builder 1.79i Page 17 of 17550
Item5.

SUBMITTAL
Project
Climatec - City of Esc - Kit Carson Park
Date
Saturday, April 12, 2025
Shawn Harlan
Sigler - Brea
205 Puente Street
Brea CA
551
Item5.

Table Of Contents
Project: Climatec - City of Esc - Kit Carson Park 04/12/2025 Prepared By: Shawn Harlan
ID 2 3
Unit Report 4
Performance Summary 5
System Parameters 5
Electrical Data 5
Acoustic Summary 6
Certified Drawing 7
Residential Carrier Products Bldr 1.39j Page 2 of 9552
Item5.

ID 2
Project: Climatec - City of Esc - Kit Carson Park 04/12/2025 Prepared By: Shawn Harlan
ID 2
ID 2
Submittal Cover Sheet
Unit Report
Performance Summary Report
Acoustic Summary
Certified Drawings
Residential Carrier Products Bldr 1.39j Page 3 of 9553
Item5.

Unit Report For ID 2
Project: Climatec - City of Esc - Kit Carson Park 04/12/2025 Prepared By: Shawn Harlan
Unit Report
Outdoor Unit Parameters
Unit Model: 27SCA
Unit Size: 3.5 Tons (Size 42)
Voltage: 208/230-1-60 V-Ph-Hz
Indoor Coil Parameters
Unit Model: FT5A
Unit Size: 48,000 Btuh
Cabinet Insulation: Singular, TXV
Voltage: 208-1-60 V-Ph-Hz
Refrigerant Type: Puron Advance
Heating Size: No Heat
Outdoor Unit Dimensions and Weight
Unit Length: 31.1875 in
Unit Width: 31.1875 in
Unit Height: 32.0625 in
Unit Shipping Weight: 224. lb
Indoor Coil Dimensions and Weight
Unit Length: 22.06 in
Unit Width: 21.1 in
Unit Height: 53.44 in
Unit Shipping Weight: 168. lb

RESIDENTIAL APPLICATIONS
This warranty is to the original purchasing owner and subsequent owners only to the extent and as stated in the Warranty Conditions and below.

The limited warranty period in years, depending on the part and the claimant, is as shown in the table below.

Limited Warranty (Years)
Item Original Owner Subsequent Owner
Parts 10* (or 5) 5
Compressor 10* (or 5) 5
*If properly registered within 90 days of original installation, otherwise 5 years (except in California and Quebec and other jurisdictions that prohibit warranty benefits conditioned on registration). See Warranty Conditions below.

OTHER APPLICATIONS
The warranty period is five (5) years on the compressor, and one (1) year on all other parts. The warranty is the original owner only and is not available for subsequent owners.

Ordering Information
Part Number Description Quantity
Outdoor Unit
27SCA542A003 27SCA Comfort Single Stage Heat Pump with Puron Refrigerant Advanced 3.5 Tons Cooling
1 15 SEER @ ARI Conditions
Indoor Coil
FT5ANXC48L00 Performance Series Fan Coil with Puron Advance 208/230-1-60 1 Singular, TXV
Aluminum
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 4 of 9
554
Item5.

Performance Summary For ID 2
Project: Climatec - City of Esc - Kit Carson Park 04/12/2025 Prepared By: Shawn Harlan
Performance Summary
System Performance
System: 27SCA/FT5A
System Quantity: 1
Altitude: 1.0 ft
Linear Pipe Length: 0.0 ft
COP @ 47 F: 3.92
COP @ 17 F: 2.70
SEER @ ARI Conditions: 15.0
EER @ ARI Conditions: 12.0
HSPF @ ARI Conditions: 7.5
Actual Clg Airflow: 1400.1 CFM
Standard Clg Airflow: 1400.0 CFM
Total Net Clg Capacity: 41.14 MBH
Net Sensible Clg Capacity: 31.68 MBH
Htg HP Capacity: 42.66 MBH
Htg HP Integrated Capacity: 42.66 MBH
Heating HP Compressor Power: 3.13 kW
Total System Power: 4.14 kW
System Parameters
System Parameters
Outdoor Unit Parameters
Unit Model: 27SCA542A003
Unit Size (Nominal): 3.5 Tons (Size 42)
Voltage: 208/230-1-60 V-Ph-Hz
Clg Ent Air DB Ambient: 95.0 °F
Htg Ent Air DB Ambient: 47.0 °F
Indoor Coil Parameters
Unit Model: FT5ANXC48L00
Unit Size (Nominal): 48,000 Btuh
Voltage: 208-1-60 V-Ph-Hz
Ent Air DB: 80.00 °F
Ent Air WB: 67.00 °F
Ent Enthalpy: 31.44 BTU/lb
Lvg Air DB: 59.05 °F
Lvg Air WB: 57.81 °F
Lvg Enthalpy: 24.91 BTU/lb
Htg Ent Air DB: 70.0 °F
Htg Lvg Air DB: 98.2 °F
Heating Size (Nominal): No Heat
Total External Static Pressure: 0.50 in wg
Electrical Data
Electrical Data
Outdoor Electrical Data
Unit Voltage: 208/230-1-60 V-Ph-Hz
Fan Motor FLA: 1.05 Amps
MCA: 24.9 Amps
Max Fuse: 40 Amps
Operating Range Min: 197 V
Operating Range Max: 253 V
Compressor RLA: 19.0 Amps
Compressor LRA: 123.0 Amps
Indoor Electrical Data:
(For units with no factory installed electric heaters)
Unit Voltage: 208-1-60 V-Ph-Hz
Unit FLA: 5.7 Amps
Unit MCA: 7.1 Amps
Unit MOCP: 15.0 Amps
Unit Min Wire Size: 14.0
Unit Fuse/Ckt Bkr Amps: 15.0 Amps
Motor HP: 3/4 HP
Notice: Indoor Elect. data is for 208-1-60 voltage
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 5 of 9555
Item5.

Acoustic Summary For ID 2
Project: Climatec - City of Esc - Kit Carson Park 04/12/2025 Prepared By: Shawn Harlan
Acoustic Summary
Outdoor Unit Parameters:

Unit Model: 27SCA
Unit Size: 3.5 Tons (Size 42)
Variations: Standard
Octave Band Center Frequency, Hz 125 250 500 1k 2k 4k 8k dBA Sound Power,dB 70.2 71.3 71.2 72.1 64.9 62.7 59.5
A-Weighted Sound Power, dBA 76.0
Indoor Coil Parameters:

Unit Model: FT5A
Unit Size: 48,000 Btuh
Cabinet Insulation: Singular, TXV
Octave Band Center Frequency, Hz 63 125 250 500 1k 2k 4k Sound Power,dB 69.0 65.0 61.0 58.0 56.0 54.0 50.0
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 6 of 9556
Item5.

Certified Drawing For ID 2
Project: Climatec - City of Esc - Kit Carson Park 04/12/2025 Prepared By: Shawn Harlan
Certified Drawing
Outdoor Model
Unit Model: 27SCA
Unit Size: 3.5 Tons (Size 42)
Voltage: 208/230-1-60 V-Ph-Hz
SEER: 15
PartNumber: 27SCA542A003
Shipping Dimensions and Weights Outdoor Unit
Height 36.44 in
Width 34.25 in
Length 34.25 in
Operating Weight 204. lb
Shipping Weight 224. lb
Dimensions

A B C D E F G H I J K

31.19 in 32.06 in 0.88 in 6.56 in 24.69 in 9.13 in 1.13 in 3.81 in 13.50 in 14.25 in 15.00 in The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 7 of 9557
Item5.

Certified Drawing For ID 2
Project: Climatec - City of Esc - Kit Carson Park 04/12/2025 Prepared By: Shawn Harlan
Indoor Coil
Unit Model: FT5A
Unit Size: 48,000 Btuh
Voltage: 208-1-60 V-Ph-Hz
Cabinet Insulation: Singular, TXV
PartNumber: FT5ANXC48L00
Dimensions and Weights Indoor Coil
Height 53.44 in
Width 21.13 in
Length 22.06 in
Shipping Weight 168. lb
Dimensions

A B C D E F G H J

53.44 in 21.13 in 19.25 in 19.13 in 19.50 in 27.25 in 26.94 in -- -- The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 8 of 9558
Item5.

Certified Drawing For ID 2
Project: Climatec - City of Esc - Kit Carson Park 04/12/2025 Prepared By: Shawn Harlan
Indoor Coil
Unit Model: FT5A
Unit Size: 48,000 Btuh
Voltage: 208-1-60 V-Ph-Hz
PartNumber: FT5ANXC48L00
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 9 of 9559
Item5.

SUBMITTAL
Project
Climatec - City of Esc - Mathes CC
Date
Saturday, April 12, 2025
Shawn Harlan
Sigler - Brea
205 Puente Street
Brea CA
560
Item5.

Table Of Contents
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
ID 2 3
Unit Report 4
Certified Drawing 5
Performance Summary 6
ID 3,5 9
Unit Report 10
Certified Drawing 11
Performance Summary 14
ID 4, 6-9 17
Unit Report 18
Certified Drawing 19
Performance Summary 22
Packaged Rooftop Builder 1.79i Page 2 of 24561
Item5.

ID 2
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
ID 2
ID 2
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 3 of 24 562
Item5.

Unit Report For ID 2
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
Unit Report
Unit Parameters
Unit Model: 50NT-B24---3
Unit Size: 24 (2 Tons)
Volts-Phase-Hertz: 208-1-60
Heating Type: Heat Pump
Refrigerant: R-454B
Duct Cfg: Vertical/Vertical
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 4' 0.1875''
Unit Width: 2' 8.625''
Unit Height: 4' 3.75''
*** Weights and Dimensions are approximate. Weight does not include roof curbs, unit packaging, field installed accessories or factory installed options. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions and weights, refer to appropriate product data catalog.

Base Unit Weight (Does not include any accessories):
338 lb
Warranty Information
1 year warranty on parts
5 yearwarranty on compressor
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50NT-B24---3 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 4 of 24 563
Item5.

Certified Drawing for ID 2
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 5 of 24 564
Item5.

Performance Summary For ID 2
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
Performance Summary
Part Number:50NT-B24---3
Refrigerant: R-454B
ARI SEER2: 13.40
Application EER (Rooftop Unit only): 0.00
Base Unit Dimensions
Unit Length: 48.2 in
Unit Width: 32.6 in
Unit Height: 51.8 in
Base Unit Weight (Does not include any accessories): 338 lb Unit
Unit Voltage-Phase-Hertz: 208-1-60
Air Discharge: Vertical
Fan Drive Type: Direct
Actual Airflow: 828 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 59.8 F
Evaporator Leaving Air WB: 58.3 F
Evaporator Leaving Air Enthalpy: 25.21 BTU/lb
Unit Discharge Air DB: 0.0 F
Unit Discharge Air WB: 0.0 F
Unit Discharge Air Enthalpy: 0.00 BTU/lb
Net Cooling Capacity: 23.20 MBH
Net Sensible Capacity: 18.05 MBH
Total Unit Power Input: 1.95 kW
Coil Bypass Factor: 0.000
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 96.3 F
Total Heating Capacity: 23.50 MBH
Integrated Heating Capacity: 23.50 MBH
Heating Power Input: 1.88 kW
High Temperature COP: 3.80
Low Temperature COP: 2.20
HSPF2: 6.7
Supply Fan
External Static Pressure: 0.50 in wg
Options / Accessories Static Pressure
Wet Coil: 0.04 in wg
Application External Static (ESP + Unit Opts/Acc.): 0.54 in wg Fan Power: 0.22 BHP
Fan Motor Size, hp: 1/2
NOTE: Medium Motor Speed, Vert
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Minimum Voltage: 197
Maximum Voltage: 253
Packaged Rooftop Builder 1.79i Page 6 of 24 565
Item5.

Performance Summary For ID 2
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
Compressor RLA: 11.8
Compressor LRA: 63
Outdoor Fan FLA (ea): 0.71
Indoor Fan Motor FLA (Total): 3.9
Power Supply MCA: 18.9
Power Supply MOCP (Fuse or HACR): 30
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Rating: 69.9 db
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz NA NA NA
125 Hz NA NA 59.0
250 Hz NA NA 56.6
500 Hz NA NA 57.9
1000 Hz NA NA 60.9
2000 Hz NA NA 55.3
4000 Hz NA NA 51.7
8000 Hz NA NA 44.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 0.0 59.0 56.6 57.9 60.9 55.3 51.7 44.0 65.6 Lw
B -

26.2 42.9 48.0 54.7 60.9 56.5 52.7 42.9 63.5 LwA
C 0.0 26.6 24.2 25.5 28.5 22.9 19.3 11.6 33.2 Lp
D -

26.2 10.5 15.6 22.3 28.5 24.1 20.3 10.5 31.1 LpA
Legend
Packaged Rooftop Builder 1.79i Page 7 of 24 566
Item5.

Performance Summary For ID 2
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted.

Packaged Rooftop Builder 1.79i Page 8 of 24 567
Item5.

ID 3,5
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
ID 3,5
ID 3,5
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 9 of 24568
Item5.

Unit Report For ID 3,5
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
Unit Report
Unit Parameters
Unit Model: 50GEQM04A2M5-0A0A0
Unit Size: 04 (3 Tons)
Volts-Phase-Hertz: 208-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two Stage Cooling, Single Circuit
Duct Cfg: Vertical Supply / Vertical Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 6' 2.375''
Unit Width: 3' 10.625''
Unit Height: 3' 5.375''
Total Operating Weight: 580 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 2
Return Air Filter Size: 16 x 25 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
5-Year compressor parts (STD.)
1-Year parts (STD.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50GEQM04A2M5-0A0A0 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 10 of 24569
Item5.

Certified Drawing for ID 3,5
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 11 of 24570
Item5.

Certified Drawing for ID 3,5
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
Packaged Rooftop Builder 1.79i Page 12 of 24571
Item5.

Certified Drawing for ID 3,5
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
Packaged Rooftop Builder 1.79i Page 13 of 24572
Item5.

Performance Summary For ID 3,5
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
Performance Summary
Part Number:50GEQM04A2M5-0A0A0
Refrigerant: R-454B
ARI SEER: 17.00
ARI SEER2: 16.00
Application EER (Rooftop Unit only): 11.89
Base Unit Dimensions
Unit Length: 74.4 in
Unit Width: 46.6 in
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 567 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 13 lb
Total Operating Weight: 580 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Vertical
Fan Drive Type: Direct Drive
Actual Airflow: 1200 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 58.5 F
Evaporator Leaving Air WB: 57.2 F
Evaporator Leaving Air Enthalpy: 24.52 BTU/lb
Unit Discharge Air DB: 59.7 F
Unit Discharge Air WB: 57.7 F
Unit Discharge Air Enthalpy: 24.81 BTU/lb
Gross Cooling Capacity: 37.36 MBH
Net Cooling Capacity: 35.79 MBH
Gross Sensible Capacity: 27.90 MBH
Net Sensible Capacity: 26.33 MBH
Compressor Power Input: 2.37 kW
Coil Bypass Factor: 0.027
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 96.1 F
Total Heating Capacity: 33.80 MBH
Integrated Heating Capacity: 33.80 MBH
Heating Power Input: 2.60 kW
High Temperature COP: 3.90
Low Temperature COP: 2.40
HSPF: 8.0
High Temperature COP2: 3.90
Low Temperature COP2: 2.40
HSPF2: 6.7
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 1946
Fan Power: 0.54 BHP
Packaged Rooftop Builder 1.79i Page 14 of 24573
Item5.

Performance Summary For ID 3,5
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
NOTE: Selected IFM RPM Range: 1058 - 2190
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 11.2
Compressor #1 LRA: 82
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 5.1
Power Supply MCA: 22
Power Supply MOCP (Fuse or HACR): 30
Disconnect Size FLA: 22
Disconnect Size LRA: 93
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 2.6
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 92.4 86.1 85.6
125 Hz 83.6 79.2 84.7
250 Hz 76.5 70.0 80.5
500 Hz 69.1 62.8 76.0
1000 Hz 66.5 64.1 72.4
2000 Hz 63.5 55.8 68.0
4000 Hz 59.4 50.0 62.8
8000 Hz 57.1 43.3 59.3
A-Weighted 74.6 69.3 79.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Packaged Rooftop Builder 1.79i Page 15 of 24574
Item5.

Performance Summary For ID 3,5
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 500 RPM
700 RPM
900 RPM
1100 RPM
1300 RPM
1500 RPM
1700 RPM
1900 RPM
2100 RPM
2300 RPM
2500 RPM

0.50 BHP

0.75 BHP

1.00 BHP

1.50 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 1946 BHP = 0.54 Maximum RPM = 2490 Maximum BHP = 3.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.3 0.6 0.9 1.2 1.5 1.8

0.0 0.2

0.4 0.6

0.8 1.0

1.2 1.4

1.6 1.8

2.0 Packaged Rooftop Builder 1.79i Page 16 of 24575
Item5.

ID 4, 6-9
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
ID 4, 6-9
ID 4, 6-9
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 17 of 24576
Item5.

Unit Report For ID 4, 6-9
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
Unit Report
Unit Parameters
Unit Model: 50GEQM06A2M5-0A0A0
Unit Size: 06 (5 Tons)
Volts-Phase-Hertz: 208-3-60
Heating Type: Heat Pump
Refrigerant: R-454B
Heat Control: Two Stage Cooling, Single Circuit
Duct Cfg: Vertical Supply / Vertical Return
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 6' 2.375''
Unit Width: 3' 10.625''
Unit Height: 3' 5.375''
Total Operating Weight: 613 lb
*** Weights and Dimensions are approximate. Weight does not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.

Lines and Filters
Return Air Filter Type: Throwaway
Return Air Filter Quantity: 4
Return Air Filter Size: 16 x 16 x 2
Selection includes construction throwaway filter into the base fan curve.

Unit Configuration
Standard/Medium Static - EcoBlue Vane Axial Fan
Al/Cu - Al/Cu - Louvered Hail Guards
Standard Electromechanical Controls (can be used with field installed economizers and dampers) Standard
Warranty Information
5-Year compressor parts (STD.)
1-Year parts (STD.)
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50GEQM06A2M5-0A0A0 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 18 of 24577
Item5.

Certified Drawing for ID 4, 6-9
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 19 of 24578
Item5.

Certified Drawing for ID 4, 6-9
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
Packaged Rooftop Builder 1.79i Page 20 of 24579
Item5.

Certified Drawing for ID 4, 6-9
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
Packaged Rooftop Builder 1.79i Page 21 of 24580
Item5.

Performance Summary For ID 4, 6-9
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
Performance Summary
Part Number:50GEQM06A2M5-0A0A0
Refrigerant: R-454B
ARI SEER: 17.00
ARI SEER2: 16.00
Application EER (Rooftop Unit only): 11.77
Base Unit Dimensions
Unit Length: 74.4 in
Unit Width: 46.6 in
Unit Height: 41.4 in
Operating Weight
Base Unit Weight: 596 lb
Al/Cu - Al/Cu - Louvered Hail Guards: 17 lb
Total Operating Weight: 613 lb
Unit
Unit Voltage-Phase-Hertz: 208-3-60
Air Discharge: Vertical
Fan Drive Type: Direct Drive
Actual Airflow: 2000 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 57.3 F
Evaporator Leaving Air WB: 57.1 F
Evaporator Leaving Air Enthalpy: 24.49 BTU/lb
Unit Discharge Air DB: 58.5 F
Unit Discharge Air WB: 57.6 F
Unit Discharge Air Enthalpy: 24.78 BTU/lb
Gross Cooling Capacity: 62.53 MBH
Net Cooling Capacity: 59.91 MBH
Gross Sensible Capacity: 49.01 MBH
Net Sensible Capacity: 46.39 MBH
Compressor Power Input: 4.02 kW
Coil Bypass Factor: 0.014
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 95.2 F
Total Heating Capacity: 54.50 MBH
Integrated Heating Capacity: 54.50 MBH
Heating Power Input: 4.20 kW
High Temperature COP: 3.80
Low Temperature COP: 2.50
HSPF: 7.2
High Temperature COP2: 3.80
Low Temperature COP2: 2.50
HSPF2: 7.2
Supply Fan
External Static Pressure: 1.00 in wg
Fan RPM: 2036
Fan Power: 0.90 BHP
Packaged Rooftop Builder 1.79i Page 22 of 24581
Item5.

Performance Summary For ID 4, 6-9
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
NOTE: Selected IFM RPM Range: 1228 - 2390
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Voltage Range: 187 - 253
Compressor #1 RLA: 15.4
Compressor #1 LRA: 150
Indoor Fan Motor Type: MED
Indoor Fan Motor FLA (Total): 9.2
Power Supply MCA: 30
Power Supply MOCP (Fuse or HACR): 45
Disconnect Size FLA: 30
Disconnect Size LRA: 166
Electrical Convenience Outlet: None
Outdoor Fan [Qty / FLA (ea)]: 1 / 1.3
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 92.3 90.8 85.6
125 Hz 83.5 79.7 84.7
250 Hz 77.6 72.4 80.5
500 Hz 73.9 66.4 76.0
1000 Hz 70.7 68.5 72.4
2000 Hz 67.7 59.3 68.0
4000 Hz 64.3 53.1 62.8
8000 Hz 60.4 46.8 59.3
A-Weighted 77.2 72.6 79.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Packaged Rooftop Builder 1.79i Page 23 of 24582
Item5.

Performance Summary For ID 4, 6-9
Project: Climatec - City of Esc - Mathes CC 04/12/2025
Prepared By: Shawn Harlan 08:55AM
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 85.6 84.7 80.5 76.0 72.4 68.0 62.8 59.3 89.2 Lw
B 59.4 68.6 71.9 72.8 72.4 69.2 63.8 58.2 78.5 LwA
C 53.2 52.3 48.1 43.6 40.0 35.6 30.4 26.9 56.8 Lp
D 27.0 36.2 39.5 40.4 40.0 36.8 31.4 25.8 46.1 LpA
Legend
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted. 900 RPM
1100 RPM
1300 RPM
1500 RPM
1700 RPM
1900 RPM
2100 RPM
2300 RPM 2500 RPM 2700 RPM
2900 RPM

0.50 BHP 0.75 BHP

1.00 BHP

1.50 BHP

2.00 BHP
SC
RP
Fan Curve
SC - System Curve RP - Rated Point
RPM = 2036 BHP = 0.90 Maximum RPM = 2836 Maximum BHP = 3.00 Static Pressure (in. wg.)
Airflow (CFM - thousands)

0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8 3.0

0.0 0.2

0.4 0.6

0.8 1.0

1.2 1.4

1.6 1.8

2.0 Packaged Rooftop Builder 1.79i Page 24 of 24583
Item5.

Outdoor Unit Heat Pump Ductless System
Outdoor Model: 37MARAQ09AA3
Job Data: Location:

Tag #: Carrier#:

Date:

NOTE: Images for illustration purposes only. Actual models may be slightly different.

Outdoor - Heat Pump
37MARAQ09AA3
9000
Voltage, Phase, Cycle V/Ph/Hz 208-230/1/60
MCA A. 12
MOPA A. 15
SCCR kA 5
Cooling Outdoor DB Min - Max °F(°C) -13~122(-25~50)
Heating Outdoor DB Min - Max °F(°C) -13~75(-25~24)
Min. Piping Length ft (m) 9.8 (3)
Standard Piping Length ft. (m) 24.6 (7.5)
Total Piping Length ft (m) 82.02(25)
Piping Lift*
ft (m) 49.21(15)
Pipe Connection Size - Liquid in (mm) 1/4in(6.35mm)
Pipe Connection Size - Suction in (mm) 3/8in(9.52mm)
R454B
Charge lbs (kg) 2.03(0.92)
Add'l Refrigerant (between Std & Max
Piping Lengths)
Oz/ft
(g/m) 0.16(15)
Capacity Unit W D H L1 L2 Face Area Sq. Ft. 4.04
mm 765 303 555 452.4 313.82 2
inch 30.12 11.93 21.85 17.81 12.36 20
mm 890 342 673 663 379.59 4
inch 35.04 13.46 26.5 26.1 14.94 ROTARY
mm 946 410 810 672.96 454.8 KSK103D33UEZ3
inch 37.24 16.14 31.89 26.49 17.19 ESTER OIL
Oil Charge Fl. Oz. 10.48
Rated Current RLA 0.62
Airflow CFM 1236.7
Sound Pressure dB(A) 52.5
Height in (mm) 21.85(555)
Width in (mm) 30.12(765)
Depth in (mm) 11.93(303)
Net Weight lbs (kg) 62.17(28.2)
Shipping Height in (mm) 24.02(610)
Shipping Width in (mm) 34.92(887)
Shipping Depth in (mm) 13.27(337)
Shipping Net Weight lbs (kg) 67.68(30.7)
* Condensing unit above or below indoor unit
9K/12K
18K
24K ~ 36K
Outdoor Size
Outdoor Model #
Refrigerant
System
Electrical
Operating Range
Refrigerant Type

OUTDOOR STANDARD FEATURES
• Variable Speed (Inverter)
• Factory installed Base Pan Heater
• Factory installed Crankcase Heater
• Low Voltage Controls
• Auto-Restart function
• Condenser High Temp Protection
• Quiet operation
• Anti-corrosive fin coating
RESIDENTIAL APPLICATION LIMITED WARRANTY*
• Ten (10) years if properly registered within ninety (90) days after original installation, parts are warranted to the original purchaser for a period of ten (10) years. Otherwise, parts warranty is five (5) years.

Piping

OUTDOOR UNIT DIMENSIONS
Dimensions
No. Rows
Fins per inch
Circuits
Type
Model
Outdoor Coil
Compressor
Airflow & Sound
Oil Type
Carrier Corporation Copyright 2024 • Atlanta, GA, 30339

SUBJECT TO CHANGE WITHOUT NOTICE
584
Item5.

Outdoor Heat Pump Ductless System
Outdoor Model:

Job Data: Location:

Tag #: Carrier#:

Date:

NOTE: Images for illustration purposes only. Actual models may be slightly different.

Outdoor - Heat Pump
37MBHAQ58AA3
60000
Voltage, Phase, Cycle V/Ph/Hz 208-230/1/60
MCA A. 3
MOPA A. 15
SCCR kA 5
Cooling Outdoor DB Min - Max °F(°C) -22~122(-30~50)
Heating Outdoor DB Min - Max °F(°C) -22~75(-30~24)
Min. Piping Length ft (m) 9.8 (3)
Standard Piping Length ft. (m) 24.6 (7.5)
Total Piping Length ft (m) 246(75)
Piping Lift*
ft (m) 98.4(30)
Pipe Connection Size - Liquid in (mm) 3/8"(9.52)
Pipe Connection Size - Suction in (mm) 3/4"(19)
R454B
Charge lbs (kg) 9.48(4.3)
Add'l Refrigerant (between Std & Max
Piping Lengths)
Oz/ft
(g/m) 0.32(30)
Face Area Sq. Ft. 6.65

2.6 20
5 TWIN-ROTARY
EKPQ440D1UMUB

ESTER OIL
Oil Charge Fl. Oz. 43.96
Rated Current RLA 7
Airflow CFM 4235.3
Sound Pressure dB(A) 64.5
Height in (mm) 52.48(1333)
Width in (mm) 37.48(952)
Depth in (mm) 16.34(415)
Net Weight lbs (kg) 230.38(104.5)
Shipping Height in (mm) 57.48(1460)
Shipping Width in (mm) 43.11(1095)
Shipping Depth in (mm) 19.49(495)
Shipping Net Weight lbs (kg) 261.69(118.7)
* Condensing unit above or below indoor unit
37MBHAQ58AA3

OUTDOOR STANDARD FEATURES
• Variable Speed (Inverter)
• Factory installed Base Pan Heater
• Factory installed Crankcase Heater
• Low Voltage Controls
• Auto-Restart function
• Condenser High Temp Protection
• Quiet operation
• Anti-corrosive fin coating
RESIDENTIAL APPLICATION LIMITED WARRANTY*
• Ten (10) years if properly registered within ninety (90) days after original installation, parts are warranted to the original purchaser for a period of ten (10) years. Otherwise, parts warranty is five (5) years.

System
Electrical
Operating Range
Refrigerant Type
Outdoor Size
Outdoor Model #
Piping
Refrigerant
Dimensions
No. Rows
Fins per inch
Circuits
Type
Model
Outdoor Coil
Compressor
Airflow & Sound
Oil Type
Carrier Corporation Copyright 2024 • Atlanta, GA, 30339

SUBJECT TO CHANGE WITHOUT NOTICE
585
Item5.

High Wall Heat Pump Ductless System
Indoor Model:

Job Data: Location:

Tag #: Carrier#:

Date:

NOTE: Images for illustration purposes only. Actual models may be slightly different. 45MAHAQ09XA3
45MAHAQ09XA3
9000
Voltage, Phase, Cycle V/Ph/Hz 208/230-1-60
Power Supply
MCA A. 3
Cooling Indoor DB Min - Max °F(°C) 60~90(16~32)
Heating Indoor DB Min - Max °F(°C) 32~86(0~30)
Face Area Sq. Ft. 2.15
2 20
3 1100/850/700
Airflow (highest to lowest) CFM 441.4 / 323.7 / 229.6 / 176.6 / 147.2 Sound Pressure (highest to lowest) dB(A) N\A/38/33/20.5/19.5 Moisture Removal L/h 0.3
Air Throw Data ft(m) 23.62(7.2)
Height in (mm) 11.61(295)
Capacity Unit W D H Width in (mm) 31.30(795)
mm 795 225 295 Depth in (mm) 8.86(225)
inch 31.3 8.86 11.61 Net Weight lbs (kg) 23.37(10.6)
mm 965 239 319 Shipping Height in (mm) 12.01(305)
inch 37.99 9.41 12.56 Shipping Width in (mm) 34.25(870) mm 1140 275 370 Shipping Depth in (mm) 14.57(370)
inch 44.88 10.83 14.57 Shipping Net Weight lbs (kg) 29.98(13.6)

CONTROLS
Standard
KSACN1401AAA
KSACN1201AAA
KSAIF0701AAA
KSAIC0601230
Wired Remote Control with Timer Function
Wi-Fi™ Kit High Wall
Dimensions
24V Mini Interface
Optional
Wired Remote Control 7 Day Programmable
Wireless Remote Controller (°F/°C Convertible)
45MAHAQ09XA3
Operating Range
Indoor Coil
Indoor Unit
Circuits
Fins per inch

INDOOR STANDARD FEATURES
• Modes: Cool, Heat, Dry, Fan, Auto
• Four fan speeds
• Sleep Mode
• Turbo Mode
• Follow Me (senses temperature at handheld remote)
• Auto-Restart function
• Quiet indoor operation
• Anti-corrosive fin coating
RESIDENTIAL APPLICATION LIMITED WARRANTY*
• Ten (10) years if properly registered within ninety (90) days after original installation, parts are warranted to the original purchaser for a period of ten (10) years. Otherwise, parts warranty is five (5) years.

Indoor Model #
System
Indoor Size
6K/9K/12K
Number of Fan Speeds
Indoor unit powered by outdoor unit
18K
24K ~ 36K

INDOOR UNIT DIMENSIONS
Electrical
No. Rows
Carrier Corporation Copyright 2024 • Atlanta, GA, 30339

SUBJECT TO CHANGE WITHOUT NOTICE
586
Item5.

Air Handler Heat Pump Ductless System
Indoor Model: 45MBAAQ60XA3
Job Data: Location:

Tag #: Carrier#:

Date:

NOTE: Images for illustration purposes only. Actual models may be slightly different. 45MBAAQ60XA3
60000
Voltage, Phase, Cycle V/Ph/Hz 208-230/1/60
Power Supply
MCA A. 11
Cooling Indoor DB Min - Max °F(°C) 60~90(16~32)
Heating Indoor DB Min - Max °F(°C) 32~86(0~30)
5 20
14 820/720/615
Airflow (highest to lowest) CFM 1807.0 / 1553.9 / 1353.8 / 724.0 / N\A Sound Pressure (highest to lowest) dB(A) 53.0/48.0/33.5 Height in (mm) 52.99(1346)
Width in (mm) 24.49(622)
Depth in (mm) 21.02(534)
Net Weight lbs (kg) 164.02(74.4)
Shipping Height in (mm) 21.20(640)
Shipping Width in (mm) 56.30(1430)
Shipping Depth in (mm) 28.15(715)
Shipping Net Weight lbs (kg) 189.82(86.1)

CONTROLS
Standard
KSACN1401AAA
KSAIC0601230
Inch mm Inch mm
A Model Height 49 1245 53 1346
B Model Width 21 534 24.5 622
C S.A. Opening Width 19.1 486 22.6 575
D R.A. Opening Width 18.6 473 22.1 562
E Model Depth 21 534 21 534
F S.A. Opening Depth 10.3 260 10.3 260
G R.A. Opening Depth 18.8 476 18.8 476
H S.A. Opening Clearance 0.9 24 0.9 24
I R.A. Opening Side Clearance 1.3 32 1.1 28
J R.A. Opening Front Clearance 1.6 41 1.6 41
K R.A. Opening Back Clearance 0.6 16 0.8 19
Wireless Remote Controller (°F/°C Convertible)
Dimensions
Number of Fan Speeds
Fins per inch
Indoor Size
No. Rows
System
Electrical Indoor unit powered by outdoor unit
Operating Range
Indoor Model #
Circuits
Indoor Unit

INDOOR UNIT DIMENSIONS
Dimensions
36K 48K/60K
45MBAAQ60XA3

INDOOR STANDARD FEATURES
• Modes: Cool, Heat, Dry, Fan, Auto
• 4-way installation (Up flow, Down flow, Right, Left)
• Auto-Restart function
• Quiet indoor operation
• Aluminum hydrophilic pre-coated fins
RESIDENTIAL APPLICATION LIMITED WARRANTY*
• Ten (10) years if properly registered within ninety (90) days after original installation, parts are warranted to the original purchaser for a period of ten (10) years. Otherwise, parts warranty is five (5) years.

Wired Remote Control 7 Day Programmable
24V Mini Interface
Optional
Indoor Coil
Carrier Corporation Copyright 2024 • Atlanta, GA, 30339

SUBJECT TO CHANGE WITHOUT NOTICE
587
Item5.

SUBMITTAL
Project
Climatec - City of Esc - Oak Hill Activity Center
Date
Saturday, April 12, 2025
Shawn Harlan
Sigler - Brea
205 Puente Street
Brea CA
588
Item5.

Table Of Contents
Project: Climatec - City of Esc - Oak Hill Activity Center 04/12/2025 Prepared By: Shawn Harlan
ID 2 3
Unit Report 4
Performance Summary 6
System Parameters 6
Electrical Data 6
Acoustic Summary 7
Certified Drawing 8
Residential Carrier Products Bldr 1.39j Page 2 of 10589 Item5.

ID 2
Project: Climatec - City of Esc - Oak Hill Activity Center 04/12/2025 Prepared By: Shawn Harlan
ID 2
ID 2
Submittal Cover Sheet
Unit Report
Performance Summary Report
Acoustic Summary
Certified Drawings
Residential Carrier Products Bldr 1.39j Page 3 of 10 590 Item5.

Unit Report For ID 2
Project: Climatec - City of Esc - Oak Hill Activity Center 04/12/2025 Prepared By: Shawn Harlan
Unit Report
Outdoor Unit Parameters
Unit Model: 27SCA
Unit Size: 5 Tons (Size 60)
Voltage: 208/230-1-60 V-Ph-Hz
Indoor Coil Parameters
Unit Model: F55A
Unit Size: Size (60) 60,000 Btuh
Cabinet Insulation: Modular, TXV
Voltage: 115-1-60 V-Ph-Hz
Refrigerant Type: Puron Advance
Heating Size: No Heat
Outdoor Unit Dimensions and Weight
Unit Length: 35 in
Unit Width: 35 in
Unit Height: 35.5 in
Unit Shipping Weight: 255. lb
Indoor Coil Dimensions and Weight
Unit Length: 22.0625 in
Unit Width: 24.4375 in
Unit Height: 59.1875 in
Unit Shipping Weight: 210.5 lb

RESIDENTIAL APPLICATIONS
This warranty is to the original purchasing owner and subsequent owners only to the extent and as stated in the Warranty Conditions and below.

The limited warranty period in years, depending on the part and the claimant, is as shown in the table below.

Limited Warranty (Years)
Item Original Owner Subsequent Owner
Parts 10* (or 5) 5
Compressor 10* (or 5) 5
*If properly registered within 90 days of original installation, otherwise 5 years (except in California and Quebec and other jurisdictions that prohibit warranty benefits conditioned on registration). See Warranty Conditions below.

OTHER APPLICATIONS
The warranty period is five (5) years on the compressor, and one (1) year on all other parts. The warranty is the original owner only and is not available for subsequent owners.

Ordering Information
Part Number Description Quantity
Outdoor Unit
27SCA560A003 27SCA Comfort Single Stage Heat Pump with Puron Refrigerant Advanced 5 Tons Cooling
1 15 SEER @ ARI Conditions
Indoor Coil
F55AABD60L00 F55A 115V Base Series Fan Coil for Puron Advance 5 Tons Cooling 115-1-60
1 Modular, TXV
Aluminum
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 4 of 10 591 Item5.

Unit Report For ID 2
Project: Climatec - City of Esc - Oak Hill Activity Center 04/12/2025 Prepared By: Shawn Harlan
Residential Carrier Products Bldr 1.39j Page 5 of 10 592 Item5.

Performance Summary For ID 2
Project: Climatec - City of Esc - Oak Hill Activity Center 04/12/2025 Prepared By: Shawn Harlan
Performance Summary
System Performance
System: 27SCA/F55A
System Quantity: 1
Altitude: 0.0 ft
Linear Pipe Length: 0.0 ft
COP @ 47 F: 3.74
COP @ 17 F: 2.60
SEER @ ARI Conditions: 14.5
EER @ ARI Conditions: 12.0
HSPF @ ARI Conditions: 7.5
Actual Clg Airflow: 1950.0 CFM
Standard Clg Airflow: 1950.0 CFM
Total Net Clg Capacity: 57.76 MBH
Net Sensible Clg Capacity: 44.09 MBH
Htg HP Capacity: 57.60 MBH
Htg HP Integrated Capacity: 57.60 MBH
Heating HP Compressor Power: 4.27 kW
Total System Power: 5.83 kW
System Parameters
System Parameters
Outdoor Unit Parameters
Unit Model: 27SCA560A003
Unit Size (Nominal): 5 Tons (Size 60)
Voltage: 208/230-1-60 V-Ph-Hz
Clg Ent Air DB Ambient: 95.0 °F
Htg Ent Air DB Ambient: 47.0 °F
Indoor Coil Parameters
Unit Model: F55AABD60L00
Unit Size (Nominal): Size (60) 60,000 Btuh
Voltage: 115-1-60 V-Ph-Hz
Ent Air DB: 80.00 °F
Ent Air WB: 67.00 °F
Ent Enthalpy: 31.44 BTU/lb
Lvg Air DB: 59.07 °F
Lvg Air WB: 57.72 °F
Lvg Enthalpy: 24.86 BTU/lb
Htg Ent Air DB: 70.0 °F
Htg Lvg Air DB: 97.4 °F
Heating Size (Nominal): No Heat
Total External Static Pressure: 0.50 in wg
Electrical Data
Electrical Data
Outdoor Electrical Data
Unit Voltage: 208/230-1-60 V-Ph-Hz
Fan Motor FLA: 1.50 Amps
MCA: 31.1 Amps
Max Fuse: 50 Amps
Operating Range Min: 197 V
Operating Range Max: 253 V
Compressor RLA: 23.7 Amps
Compressor LRA: 157.0 Amps
Indoor Electrical Data:
(For units with no factory installed electric heaters)
Unit Voltage: 115-1-60 V-Ph-Hz
Unit FLA: 8.5 Amps
Unit MCA: 10.7 Amps
Unit MOCP: 15.0 Amps
Unit Min Wire Size: 14.0
Unit Fuse/Ckt Bkr Amps: 15.0 Amps
Motor HP: 3/4 HP
Notice: Indoor Elect. data is for 115-1-60 voltage
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 6 of 10 593 Item5.

Acoustic Summary For ID 2
Project: Climatec - City of Esc - Oak Hill Activity Center 04/12/2025 Prepared By: Shawn Harlan
Acoustic Summary
Outdoor Unit Parameters:

Unit Model: 27SCA
Unit Size: 5 Tons (Size 60)
Variations: Standard
Octave Band Center Frequency, Hz 125 250 500 1k 2k 4k 8k dBA Sound Power,dB 66.6 68.6 69.2 70.8 62.9 60.8 62.7
A-Weighted Sound Power, dBA 74.0
Indoor Coil Parameters:

Unit Model: F55A
Unit Size: Size (60) 60,000 Btuh
Cabinet Insulation: Modular, TXV
Octave Band Center Frequency, Hz 63 125 250 500 1k 2k 4k Sound Power,dB 76.0 72.0 68.0 65.0 63.0 61.0 57.0
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 7 of 10 594 Item5.

Certified Drawing For ID 2
Project: Climatec - City of Esc - Oak Hill Activity Center 04/12/2025 Prepared By: Shawn Harlan
Certified Drawing
Outdoor Model
Unit Model: 27SCA
Unit Size: 5 Tons (Size 60)
Voltage: 208/230-1-60 V-Ph-Hz
SEER: 15
PartNumber: 27SCA560A003
Shipping Dimensions and Weights Outdoor Unit
Height 39.81 in
Width 34.25 in
Length 34.25 in
Operating Weight 234. lb
Shipping Weight 255. lb
Dimensions

A B C D E F G H I J K

35.00 in 35.50 in 0.88 in 6.56 in 28.44 in 9.13 in 1.13 in 3.81 in 13.00 in 15.50 in 16.75 in The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 8 of 10 595 Item5.

Certified Drawing For ID 2
Project: Climatec - City of Esc - Oak Hill Activity Center 04/12/2025 Prepared By: Shawn Harlan
Indoor Coil
Unit Model: F55A
Unit Size: Size (60) 60,000 Btuh
Voltage: 115-1-60 V-Ph-Hz
Cabinet Insulation: Modular, TXV
PartNumber: F55AABD60L00
Dimensions and Weights Indoor Coil
Height 59.19 in
Width 24.44 in
Length 22.06 in
Shipping Weight 210.5 lb
Dimensions

A B C D E F G H J

59.19 in 24.69 in 22.75 in 22.69 in 25.25 in 32.94 in 32.63 in 34.06 in -- The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 9 of 10 596 Item5.

Certified Drawing For ID 2
Project: Climatec - City of Esc - Oak Hill Activity Center 04/12/2025 Prepared By: Shawn Harlan
Indoor Coil
Unit Model: F55A
Unit Size: Size (60) 60,000 Btuh
Voltage: 115-1-60 V-Ph-Hz
PartNumber: F55AABD60L00
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 10 of 10 597 Item5.

Marvair MAH Wall Mount Heat Pumps PDS 09/2024 New 8
Room Size Limitations
MAH1020H MAH1024H MAH1030H MAH1036H MAH1042H MAH1048H MAH1060H Refrigerant Charge (oz.) 110 110 112 120 140 160 184
Minimum Room Size (ft²) 108.0 108.0 109.8 117.8 137.5 157.1 180.6 Minimum Supply Height (ft) 6.9 6.9 6.9 6.9 6.9 6.9 6.9
MAH2024H MAH2030H MAH2036H MAH2042H MAH2048H MAH2060H
Refrigerant Charge (oz.) 120 120 150 140 160 184
Minimum Room Size (ft²) 117.8 117.8 147.5 137.5 157.1 180.6 Minimum Supply Height (ft) 6.9 6.9 6.9 6.9 6.9 6.9
Marvair Heat Pump Model Identification
Example M A H 1 0 3 6 H A 0 5 0 C + + R + 1 E A + A 3 1 + + + + + + Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 1 Unit Designation/Family M = Marvair Wall Mount
S = Stock Unit
2 Energy Efficiency Ratio
(EER) A = 11
3 Refrigerant Type H = R-454B
4 Compressor Type/Quantity 1 = Single Stage Compressor
2 = 2-Stage Compressor
5 Unit Capacity/Nominal
Cooling (BTUH)
020 = 20,000 042 = 42,000
024 = 24,000 048 = 48,000
030 = 30,000 060 = 60,000
036 = 36,000
6 7
8 System Type H = Heat Pump
9 Power Supply
(Volts-Hz-Phase)
A = 208/230-60-1 D = 460-60-3
C = 208/230-60-3
10 Heat Designation
@ Rated Voltage
000 = No Heat 090= 9KW
040 = 4KW 100= 10KW
050 = 5KW 120= 12KW
060 = 6KW 150= 15KW
080 = 8KW
11 12
13 Ventilation
Configuration
C = Economizer
D = Motorized Damper w/Pressure Relief
E = Motorized Damper w/Pressure Relief &
Independent Motorized Damper Control
H = GreenWheel® ERV
N = Barometric Damper w/15% OSA
T = Title 24 Compliant Economizer & Controls
+ = None
$ = Special
14 Dehumidification
G = Hot Gas Reheat
R = Electric Reheat
T = Electric Reheat w/Humidity Control
+ = None
$ = Special
15 Controls
A = Power Fail Alarm w/Additional Lockouts
C = 24V EMS Relay Kit
+ = None
$ = Special
16 Operating Condition
A = Evaporator Freeze Sensor (EFS)
C = EFS w/Hot Gas Bypass
D = Desert Duty
E = Extreme Duty
F = Desert Duty w/Hard Start
G = Desert Duty w/EFS
H = Desert Duty w/Hard Start & EFS
J = Extreme Duty w/Hard Start
K = Extreme Duty w/EFS
M = Extreme Duty w/Hard Start & EFS
N = Hard Start
P = Hard Start w/Low Ambient & CCH
Q = Hard Start w/Low Ambient &
Fan Cycle Control (FCC)
R = Crank Case Heater (CCH)
T = Hard Start w/EFS
U = Hard Start w/Hot Gas Bypass
V = Hard Start w/Low Ambient & CCH & EFS
W = Low Ambient w/CCH
X = Hot Gas Bypass
Y = Low Ambient w/CCH & FCC
Z = Low Ambient w/CCH & EFS
1 = Low Ambient w/FCC
2 = Low Ambient w/FCC & EFS
3 = CCH w/Hot Gas Bypass
+ = None
$ = Special
17 Indoor Air Quality Features
A = UV Light
D = Dry Bulb Sensor
E = Dry Bulb Sensor w/Dirty Filter
G = Dirty Filter Sensor
K = Bi-Polar Ionization
M = Dry Bulb Sensor & CO2 Sensor
(Only w/Economizer)
+ = None
$ = Special
18 Air Flow 1 = Top Supply/Center Return (STD)
$ = Special
19 Compressor Location D = Left Hand - All 31
/2 to 5 ton units
E = Right Hand - All 11
/2 to 3 ton units
20 Filter Option
A = 2” Pleated (MERV 8, AC/HP-C)
C = 2” Charcoal
D = MERV 11 High Filtration Package
E = MERV 13 High Filtration Package
F = Filter Access Through Return Air Grille
W = Aluminum Washable
+ = None
$ = Special
21 Corrosion Protection
A = Condenser Coil Only
C = Evaporator Coil Only
D = Both Coils Condenser & Evaporator
E = All Coils Cond/Evap/Reheat
F = Coat All
G = Coastal Package & Evaporator Coil
K = Coastal Package
+ = None
$ = Special
22 Engineering Revision Level A3
23 D3
24 Cabinet Color
1 = Marvair Beige (STD)
2 = Gray (STD)
3 = Carlsbad Canyon (STD)
4 = White (STD)
5 = Stainless Steel Exterior
9 = Pebble Gray
A = Stainless Steel - Unit
$ = Custom Color (Powder Coat)
25 Sound Attenuation 2 = Compressor Blanket
+ = None
26 Security Option
A = Lockable Access Plate/Tamper Proof
C = Tamper Proof Screws
D = Lockable Access Plate w/Tamper Proof
+ = None
$ = Special
27 Fastener/Drain Pan Option
A = Stainless Steel Fasteners
C = Stainless Steel Drain Pan
D = Stainless Steel Fasteners & Drain Pan
+ = None
$ = Special
28 Miscellaneous
C = Copeland Compressor
+ = None
$ = Special
29 Unused + = None
$ = Special
30 Special Variation
+ = None
$ = Special Configuration Not Covered by
Model Nomenclature
Note: Not all options are available with all configurations. Contact your Marvair sales representative for configuration details and feature compatibility. 598
Item5.
9 Marvair MAH Wall Mount Heat Pumps PDS 09/2024 New
Marvair MAH Single Stage Heat Pump Certified Ratings & Performance Efficiency and Capacity Ratings at ANSI/AHRI Standard 390 - MAH Heat Pumps Model Number
MAH1020H MAH1024H MAH1030H MAH1036H MAH1042H MAH1048H MAH1060H

A A C D A C D A C D A C D A C D A C D
Cooling BTUH¹ 20,000 24,000 29,000 35,000 42,000 46,000 57,000 EER² 11 11 11 11 11 11 11
High Temperature Heating³ 20,000 24,000 27,000 30,000 34,000 42,000 51,000 High Temperature COP4 3.3 3.3 3.3 3.3 3.3 3.3 3.3
Rated Air Flow (CFM5
) 760 820 1,150 1,200 1,350 1,700 1,800
1 Cooling is rated at 95°F (35°C) outdoor and 80°F DB/67°F WB (26.5°C DB/19.5°C WB) return air. 2 EER = Energy Efficiency Ratio
3 High Temperature Heating & COP are rated at 47°F DB/43°WB (8.3°C DB/6.1°C WB) outdoor and 70°F (21.1°C) return air. 4 COP = Coefficient of Performance
5 CFM = Cubic Feet per Minute
Ratings are with no outside air. Performance will be affected by altitude. Ratings are at 230 volts for 208/230 volt units (“A” & “C” models) and 460 volts for “D” models.

Operation of units at a different voltage from that of the rating point will affect performance and air flow.

Sensible Total Heat Ratio @ 95ºF (35ºC) Outside Air DB - MAH Heat Pumps Model Number
MAH1020H MAH1024H MAH1030H MAH1036H MAH1042H MAH1048H MAH1060H

A A C D A C D A C D A C D A C D A C D
Total Capacity 20,000 24,000 29,000 35,000 42,000 46,000 57,000 Sensible Heat Ratio 0.80 0.80 0.70 0.70 0.70 0.70 0.60
Sensible Capacity 15,000 18,600 21,500 24,500 27,400 31,000 36,900 Rated Air Flow (CFM¹) 760 820 1,150 1,200 1,350 1,700 1,800 1 CFM=Cubic Feet per Minute
Sensible Heat Ratios based upon ANSI/AHRI std. 390 outdoor conditions of 95°F (35°C) outdoor and 80°F DB/67°F WB (26.5°C DB/19.5°C WB) return air.

Cooling Performance (BTUH) at Various Outdoor Temperatures - MAH Heat Pumps Model
Number
Outdoor Temperature
75ºF/24ºC 80ºF/26.5ºC 85ºF/29ºC 90ºF/32ºC 95ºF/35ºC 100ºF/38ºC 105ºF/40.5ºC 110ºF/43.3ºC 115ºF/46ºC 120ºF/49ºC 125ºF/52ºC 130ºF/54ºC MAH1020H 23,200 22,400 21,600 20,800 20,000 19,200 18,400 17,600 17,200 16,840 16,480 16,120 MAH1024H 27,840 26,880 25,920 24,960 24,000 23,040 22,080 21,120 20,640 20,208 19,776 19,344 MAH1030H 33,640 32,480 31,320 30,160 29,000 27,840 26,680 25,520 24,940 24,418 23,896 23,374 MAH1036H 40,600 39,200 37,800 36,400 35,000 33,600 32,200 30,800 30,100 29,470 28,840 28,210 MAH1042H 48,720 47,040 45,360 43,680 42,000 40,320 38,640 36,960 36,120 35,364 34,608 33,852 MAH1048H 53,360 51,520 49,680 47,840 46,000 44,160 42,320 40,480 39,560 38,732 37,904 37,076 MAH1060H 66,120 63,840 61,560 59,280 57,000 54,720 52,440 50,160 49,020 47,994 46,968 45,942 Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67°F WB (26.5°C DB/19.5°C WB). Return air at rated air flow.

Heating Performance (BTUH) at Various Outdoor Temperatures - MAH Heat Pumps Model Number Outdoor Temperature
10ºF/-12.2ºC 17ºF/-8.3ºC 20ºF/-6.7ºC 30ºF/-1.1ºC 40ºF/4.4ºC 47ºF/8.3ºC 50ºF/10ºC 60ºF/15.6ºC 70ºF/21.1ºC MAH1020H 10,766 11,333 12,200 15,233 17,833 20,000 20,600 21,500 22,500 MAH1024H 11,560 13,600 14,640 18,280 21,400 24,000 24,720 25,800 27,000 MAH1030H 15,130 17,800 18,720 21,940 24,700 27,000 27,810 29,025 30,375 MAH1036H 15,810 18,600 19,740 23,730 27,150 30,000 30,900 32,250 33,750 MAH1042H 18,700 22,000 23,340 28,030 32,050 35,400 36,462 38,055 39,825 MAH1048H 20,400 24,000 25,800 32,100 37,500 42,000 43,260 45,150 47,250 MAH1060H 22,900 27,000 29,300 37,500 44,600 51,000 51,900 54,300 61,100 Based upon ANSI/AHRI std. 390 return air conditions of 70°F DB (21.1°C DB). Return air at rated air flow. 599
Item5.

Marvair MAH Wall Mount Heat Pumps PDS 09/2024 New 10
Electrical Characteristics - Compressor, Fan, Ventilation & Blower Motors MAH Heat Pumps with Single Stage Compressor
Basic
Model
Compressor Outdoor Fan Motor Indoor Blower Motor
Ventilation
GreenWheel
AMPS
Type Volts-Hz-Ph RLA¹ LRA² Volts-Hz-PH RPM³ FLA4 HP5 Volts-Hz-PH RPM³ FLA4 HP5 OAM6 EXM7 WD8 MAH1020HA
Scroll
208/230-60-1 10.3 60.2 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 2.8 1/3 MAH1024HA 208/230-60-1 11.9 67.8 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 2.8 1/3 1.0 1.0 0.2 MAH1030HA 208/230-60-1 13.5 82.5 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 4.1 1/2 1.0 1.0 0.2 MAH1036HA 208/230-60-1 14.7 109.0 208/230-60-1 1200 3.5 1/3 208/230-60-1 1050 4.1 1/2 1.0 1.0 0.2 MAH1042HA 208/230-60-1 18.6 123.0 208/230-60-1 1200 5.3 1/2 208/230-60-1 1050 4.1 1/2 1.0 1.0 0.2 MAH1048HA 208/230-60-1 22.4 126.0 208/230-60-1 1200 5.3 1/2 208/230-60-1 1050 4.1 1/2 1.0 1.0 0.2 MAH1060HA 208/230-60-1 25.6 155.0 208/230-60-1 1200 6.3 3/4 208/230-60-1 1050 6.0 3/4 1.0 1.0 0.2 MAH1024HC
Scroll
208/230-60-3 8.3 67.7 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 2.8 1/3 MAH1030HC 208/230-60-3 12.8 97.5 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 4.1 1/2 1.0 1.0 0.2 MAH1036HC 208/230-60-3 12.2 102.8 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 4.1 1/2 1.0 1.0 0.2 MAH1042HC 208/230-60-3 12.8 102.8 208/230-60-1 1200 5.3 1/2 208/230-60-1 1050 4.1 1/2 1.0 1.0 0.2 MAH1048HC 208/230-60-3 12.8 120.4 208/230-60-1 1200 5.3 1/2 208/230-60-1 1050 4.1 1/2 1.0 1.0 0.2 MAH1060HC 208/230-60-3 18.6 155.0 208/230-60-1 1200 6.3 3/4 208/230-60-1 1050 6.0 3/4 1.0 1.0 0.2 MAH1024HD
Scroll
460-60-3 5.1 38.1 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 2.8 1/3 MAH1030HD 460-60-3 5.1 44.3 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 4.1 1/2 1.0 1.0 0.2 MAH1036HD 460-60-3 5.8 50.0 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 4.1 1/2 1.0 1.0 0.2 MAH1042HD 460-60-3 5.8 50.0 208/230-60-1 1200 5.3 1/2 208/230-60-1 1050 4.1 1/2 1.0 1.0 0.2 MAH1048HD 460-60-3 6.0 49.4 208/230-60-1 1200 5.3 1/2 208/230-60-1 1050 4.1 1/2 1.0 1.0 0.2 MAH1060HD 460-60-3 8.3 58.1 208/230-60-1 1200 6.3 3/4 208/230-60-1 1050 6.0 3/4 1.0 1.0 0.2 MAH1024HZ
Scroll
575-60-3 3.8 27.7 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 2.8 1/3 MAH1030HZ 575-60-3 4.5 27.1 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 4.1 1/2 1.0 1.0 0.2 MAH1036HZ 575-60-3 4.5 41.0 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 4.1 1/2 1.0 1.0 0.2 MAH1042HZ 575-60-3 5.1 41.0 208/230-60-1 1200 5.3 1/2 208/230-60-1 1050 4.1 1/2 1.0 1.0 0.2 MAH1048HZ 575-60-3 5.8 41.0 208/230-60-1 1200 5.3 1/2 208/230-60-1 1050 4.1 1/2 1.0 1.0 0.2 MAH1060HZ 575-60-3 7.7 47.8 208/230-60-1 1200 6.3 3/4 208/230-60-1 1050 6.0 3/4 1.0 1.0 0.2 1 RLA = Rated Load Amps 2LRA = Locked Rotor Amps 3RPM = Revolutions per Minute 4FLA = Full Load Amps 5 HP = Horsepower 6OAM = Outside Air Mover 7EXM = Exhaust Air Mover 8WD = Wheel Drive Motor The 460 volt units have a step down transformer for the 230 volt motors. 600
Item5.
11 Marvair MAH Wall Mount Heat Pumps PDS 09/2024 New
MAH Heat Pumps Summary Electrical Ratings (Wire and HACR Circuit Breaker Sizing) - Ventilation Configuration:

C: Economizer, Outside Air with Pressure Relief
D: Motorized 2-Position Damper, up to 450 cfm of Outside Air w/Pressure Relief E: Motorized Damper w/Pressure Relief & Independent Motorized Damper Control N: Barometric Damper, up to 15% Outside Air
T: Title 24 Compliant Economizer & Controls
Electric Heat 000 = None 040 = 4 kw 050 = 5 kw 060 = 6 kw 080 = 8 kw 090 = 9 kw 100 = 10 kw 120 = 12 kw 150 = 15 kw Basic
Model Volts-Hz-Ph SPPE³ SPPE³ SPPE³ SPPE³ SPPE³ SPPE³ SPPE³ SPPE³ SPPE³ MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MCA1 MFS2 MAH1020HA 208/230-60-1 19.2 25 40.0 45 45.2 50 50.4 60 60.8 70 71.3 80 MAH1024HA 208/230-60-1 21.2 30 42.0 45 47.2 50 52.4 60 62.8 70 73.3 80 MAH1030HA 208/230-60-1 24.5 35 45.3 50 50.5 60 55.7 60 66.1 70 76.6 80 87.0 90 102.6 110 MAH1036HA 208/230-60-1 26.0 40 46.8 50 52.0 60 57.2 60 67.6 70 78.1 80 88.5 90 104.1 110 MAH1042HA 208/230-60-1 32.7 50 53.5 60 58.7 70 84.7 90 95.2 100 110.8 125 MAH1048HA 208/230-60-1 37.4 50 58.2 70 63.4 80 89.5 100 99.9 100 115.5 125 MAH1060HA 208/230-60-1 44.3 60 65.1 80 70.3 90 96.4 110 106.8 110 122.4 125 MAH1024HC 208/230-60-3 16.7 20 34.7 35 43.7 45 52.8 60 61.8 70 MAH1030HC 208/230-60-3 23.6 35 41.6 50 50.7 60 59.7 60 68.7 70 MAH1036HC 208/230-60-3 22.9 35 40.9 45 49.9 50 58.9 60 68.0 70 MAH1042HC 208/230-60-3 25.4 35 43.4 50 52.5 60 61.5 70 70.5 80 MAH1048HC 208/230-60-3 25.4 35 43.4 50 52.5 60 61.5 70 70.5 80 MAH1060HC 208/230-60-3 35.6 50 53.6 60 62.6 70 71.6 80 80.7 90 MAH1024HD 460-60-3 9.5 15 18.5 20 23.1 25 27.6 30 32.1 35 MAH1030HD 460-60-3 10.2 15 19.2 20 23.7 25 28.2 30 32.7 35 MAH1036HD 460-60-3 11.1 15 20.1 25 24.6 25 29.1 30 33.6 35 MAH1042HD 460-60-3 12.0 15 21.0 25 25.5 30 30.0 30 34.5 35 MAH1048HD 460-60-3 12.2 15 21.2 25 25.7 30 30.2 35 34.8 35 MAH1060HD 460-60-3 16.5 20 25.5 30 30.1 35 34.6 35 39.1 40 MAH1024HZ 575-60-3 7.3 15 14.8 15 18.6 20 22.3 25 26.1 30 MAH1030HZ 575-60-3 8.7 15 16.2 20 20.0 20 23.7 25 27.5 30 MAH1036HZ 575-60-3 8.7 15 16.2 20 20.0 20 23.7 25 27.5 30 MAH1042HZ 575-60-3 10.1 15 17.7 20 21.4 25 25.2 30 29.0 30 MAH1048HZ 575-60-3 11.0 15 18.5 20 22.3 25 26.1 30 29.8 30 MAH1060HZ 575-60-3 14.5 20 22.1 25 25.8 30 29.6 30 33.4 35 S-Circuit - The user can move a pin on the board to control whether the electric heat will operate simultaneously with the compressor ( S Circuit – NO) or will not run simultaneously with the compressor (S Circuit – Yes). 1 MCA = Minimum Circuit Ampacity (Wiring Size Amps) 2MFS = Maximum Fuse or HACR Breaker Size 3SPPE = Single Point Power Entry MCA & MFS are calculated at 230 volts on the 208-230v. (HPA & HPC) models. The 460 volt HPD models are calculated at 460 volts. This chart should only be used as a guideline for estimating conductor size and overcurrent protection. For the requirements of specific units, always refer to the data label on the unit. 601
Item5.

Marvair MAH Wall Mount Heat Pumps PDS 09/2024 New 16
Dimensional Data: MAH1020H/1024H & MAH2024H
Engineering Revision “A”
4 4

LH SIDE VIEW

TOP VIEW
4 FRONT VIEW
2 4
4 4
4 4

BACK SIDE VIEW
4 2 4
4 RH SIDE VIEW
Installation Weight
MAH1020H/1024H & MAH2024H Base w/Economizer w/3 Phase w/Economizer & 3 Phase Pounds 337 357 356 376
Kilograms 153 162 161 171
Filter Size
MAH1020H/1024H & MAH2024H INCHES MILLIMETERS PART NUMBER FILTERS PER UNIT MERV RATING RETURN AIR FILTER 16 x 25 x 2 406 x 635 x 51 80137 1 8 (STD) Note: All overall outside dimensions are given with +/- .250” (6mm) tolerance. 602 Item5.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53400094-01 Printed in U.S.A. Form No. 40RL-7-12-02SI Pg 1 3-25 Replaces: 40RL-7-12-01SI Installation, Start-up and
Service Instructions

CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1 Detection of Flammable Refrigerants . . . . . . . . . . . . 2 Ignition Source Mitigation . . . . . . . . . . . . . . . . . . . . . 2 Ventilation Requirements . . . . . . . . . . . . . . . . . . . . . . 3 Evacuation, Removal, and Recovery . . . . . . . . . . . . 3 Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 PRE-INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Moving and Storage . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Checks to Refrigerating Equipment . . . . . . . . . . . . . 3 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Uncrating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Rated Indoor Airflow (cfm) . . . . . . . . . . . . . . . . . . . . 10 Unit Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Unit Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 • REQUIREMENTS OF A2L REFRIGERANT PIPING
Refrigerant and Chilled Water Piping Access . . . . 11
Chilled Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . 13 Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Fan Motors and Drives . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Power Supply and Wiring . . . . . . . . . . . . . . . . . . . . . . . 14 • THREE STAGE OPERATION
Leak Dissipation System . . . . . . . . . . . . . . . . . . . . . 20 • SEQUENCE OF OPERATION
• LEAK DISSIPATION SYSTEM SELF-TEST
• TROUBLESHOOTING
Connecting Ductwork . . . . . . . . . . . . . . . . . . . . . . . . 23 • DISCHARGE CONNECTION
• RETURN CONNECTIONS
• OUTDOOR-AIR INLET CONNECTIONS
Return-Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 40RLA and 40RLQ ONLY . . . . . . . . . . . . . . . . . . . . . 24 Adjusting TXV for Superheat
(40RLA and 40RLQ only) . . . . . . . . . . . . . . . . . . . 24 Fan Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Quarterly Inspection
(and 30 days after initial start) . . . . . . . . . . . . . . . 24 • INDOOR SECTION
Seasonal Maintenance . . . . . . . . . . . . . . . . . . . . . . . 25 • AIR CONDITIONING
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25 Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25 SUPPLY FAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26 Supply Fan (Direct-Drive) . . . . . . . . . . . . . . . . . . . . .26 • EVALUATING MOTOR SPEED
• SELECTING FAN SPEED
• FAN FAULT DETECTION
• FREEZE PROTECTION
• TROUBLESHOOTING THE ECM MOTOR
Service Access for Supply Fan and Motor . . . . . . .30 • HORIZONTAL APPLICATIONS
• VERTICAL APPLICATIONS
Condensate Drains . . . . . . . . . . . . . . . . . . . . . . . . . .33 Return-Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . .33 Chilled Water Coil Freeze Protection . . . . . . . . . . . .33 Coil Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33 Cleaning Cooling Coil . . . . . . . . . . . . . . . . . . . . . . . .33 Cleaning Insulation . . . . . . . . . . . . . . . . . . . . . . . . . .34 Replacing Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . .34 FAN PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . .34 General Fan Performance Notes . . . . . . . . . . . . . . .34 DECOMMISSIONING . . . . . . . . . . . . . . . . . . . . . . . . .53 START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . .CL-1

SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.

Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloths for brazing operations and have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions attached to the unit. Consult local building codes and appropriate national electrical codes (in U.S.A., ANSI/NFPA70, National Electrical Code (NEC); in Canada, CSA C22.1) for special requirements.

It is important to recognize safety information. This is the safetyalert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.

Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.

DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal 40RLA/S/Q 07-12
Packaged Air-Handling Units
with Puron Advance™ (R-454B) Refrigerant
60 Hz
603
Item5.
2 injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.

Detection of Flammable Refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector utilizing a naked flame) shall not be used.

The following leak detection methods are deemed acceptable for all refrigerant systems.

Electronic leak detectors may be used to detect refrigerant leaks, but in the case of flammable refrigerants the sensitivity may not be adequate, or may need recalibration. Detection equipment shall be calibrated in a refrigerant-free area. Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed, and the appropriate percentage of gas (25% max.) is confirmed.

Leak detection fluids are also suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work.

Examples of leak detection fluids:
• Bubble method.
• Fluorescent method agents.

If a leak is suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Removal of refrigerant shall be according to the following section.

Ignition Source Mitigation
No person carrying out work on an appliance containing A2L refrigerants which involves exposing any pipe work shall use any sources of ignition in such a way that can lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, must be kept sufficiently far away from the site of work. This includes, but is not limited to, installation, repair, removal, and disposal of equipment.

Work shall be performed under a controlled procedure so as to minimize the risk of flammable gas or vapors being present while work is performed.

DANGER

ELECTRICAL SHOCK HAZARD
Failure to follow this warning will result in personal injury or death.

Before performing service or maintenance operations on unit, turn off main power switch to unit and install lock(s) and lockout tag(s). Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate. Unit may have more than one power switch.

WARNING

UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury, death and/or equipment damage.

R-454B is an A2L refrigerant. All service equipment or
components must be A2L refrigerant rated. Do not use nonA2L rated equipment or components on R-454B refrigerant equipment.

WARNING

UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal injury, death and/or equipment damage.

These air handling units are dedicated voltages. Unlike older air handler units the voltage of these units cannot be changed in the field.

WARNING

PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could cause personal injury or death.

Relieve pressure and recover all refrigerant before system repair or final unit disposal.

Wear safety glasses and gloves when handling refrigerants.

Keep torches and other ignition sources away from
refrigerants and oils.

CAUTION

CUT HAZARD
Failure to follow this caution may result in personal injury.

Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses, and gloves when handling parts and servicing units.

CAUTION

UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment damage.

Ensure voltage listed on unit data plate agrees with electrical supply provided for the unit.

WARNING
RISK OF FIRE — FLAMMABLE REFRIGERANT
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.

Do not pierce or burn.

Be aware that refrigerants may not contain an odor.

Unit Label Safety Symbols

WARNING
This symbol shows that the appliance
used a flammable refrigerant. If the
refrigerant is leaked and exposed to an
ignition source, there is a risk of fire.

CAUTION This symbol shows that the operation
manual should be read carefully.

CAUTION
This symbol shows that the service
personnel should be handling the
equipment with reference to the
installation manual.

CAUTION
This symbol shows that the information
is available such as the operating
manual or installation manual.
604
Item5.
3 Ventilation Requirements
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree ventilation shall continue during the period that work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it external atmosphere. Should an auxiliary ventilation system be present, check that it is operating correctly and no outlets are obstructed.

Evacuation, Removal, and Recovery
When breaking into the refrigerant circuit to make repairs - or for any other purpose - conventional procedures shall be used. However, for flammable refrigerants it is important that best practice be followed, since flammability is a consideration.

The following procedure shall be adhered to:

1. Safely remove refrigerant following local and national regulations.

2. Evacuate.

3. Purge the circuit with inert gas (optional for A2L
refrigerants).

4. Evacuate (optional for A2L refrigerants).

5. Continuously flush or purge with inert gas when using flame to open circuit.

6. Open the circuit.

For appliances containing flammable refrigerants, purging shall be achieved by breaking the vacuum in the system with oxygen-free nitrogen and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process may need to be repeated several times until the system is free from refrigerant. When the final oxygen-free nitrogen charge is used, the system shall be vented down to atmospheric pressure to enable work to take place.

The refrigerant charge shall be recovered into the correct recovery cylinders if venting is not allowed by local and national codes. Ensure that the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant. Cylinders shall be complete with pressure-relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible cooled before recovery occurs.

The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of the flammable refrigerant. If in doubt, the manufacturer should be consulted. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect coupling and in good condition.

The recovered refrigerant shall be processed according to local legislation in the correct recovery cylinder, and the relevant waste transfer not arranged. Do not mix refrigerants in recovery units, and especially not in cylinders.

If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant.

The compressor body shall not be heated by an open flame or other ignition sources to accelerate this process. When oil is drained from a system, it shall be carried out safely.

At no point during this process should the outlet for the vacuum pump be close to any potential ignition sources, and ventilation shall be available.

Charging
In addition to conventional charging procedures, the following requirements shall be followed.
• Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them. • Cylinders shall be kept in an appropriate position according to the instructions. • Ensure that the refrigerating system is earthed prior to charging the system with refrigerant.
• Label the system when charging is complete (if not already). • Extreme care shall be taken not to overfill the refrigerating system.

Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. The system shall be leak tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.

PRE-INSTALLATION

1. The power supply (v, Ph, and Hz) must correspond to that specified on unit rating plate.

2. The electrical supply provided by the utility must be sufficient to handle load imposed by this unit.

3. Refer to Installation, General section (page 3) and Fig. 2 for locations of electrical inlets, condensate drain, duct connections, and required clearances before setting unit in place.

4. This installation must conform with local building codes and with the NEC (National Electrical Code) or ANSI
(American National Standards Institute)/NFPA (National
Fire Protection Association) latest revision. Refer to provincial and local plumbing or wastewater codes and other applicable local codes.

Moving and Storage
To transfer unit from truck to storage site, use a fork truck. Do not stack units more than 2 high during storage. If unit is to be stored for more than 2 weeks before installation, choose a level, dry storage site free from vibration. Do not remove plastic wrap or skid from unit until final installation.

Rigging
All 40RL Series units can be rigged by using the shipping skid.

Units are shipped fully assembled. Do not remove shipping skids or protective covering until unit is ready for final placement; damage to bottom panels can result. Use slings and spreader bars as applicable to lift unit.

Checks to Refrigerating Equipment
The following checks shall be made to installations using A2L refrigerants:
• The actual charge is in accordance with the room size within which the refrigerant containing parts are installed. • Supplementary ventilation machinery and outlets are operating adequately and are not obstructed. • For appliances utilizing indirect refrigeration, the secondary circuit shall be checked for the presence of refrigerant. • Warning markings on the equipment is visible and legible, with those that are not being either replaced or corrected. • Refrigerant piping or components are installed in a position where they are unlikely to be exposed to any substance which may corrode them, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against said corrosion.

INSTALLATION
General
Allow the following clearances for service access and airflow:
605
Item5.
4 • Rear: 2-1/2 ft (762 mm)
NOTE: Units equipped with accessory electric heat may
require additional rear clearance to allow service access. • Front: 2-1/2 ft (762 mm)
• Right Side: 2-1/2 ft (762 mm)
• Left Side: 2-1/2 ft (762 mm)
For units equipped with an economizer, refer to the accessory installation instructions for additional clearance requirements. Be sure floor, wall, or ceiling can support unit weight (Tables 1-3).

See Fig. 2 for dimensions.

Uncrating
Move unit as near as possible to final location before removing shipping skid.

Remove metal banding, top skid, and plastic wrap. Examine unit for shipping damage. If shipping damage is evident, file claim with transportation agency. Remove base skid just prior to actual installation.

Check nameplate information against available power supply and model number description in Fig. 1.

NOTE: Be sure to remove the foam shipping pad from the thermostatic expansion valve (TXV). Verify that it has been removed.

See Fig. 3 for determining foam pad location.

Accessories
Refer to instructions shipped with each accessory for specific information.

Fig. 1 — Model Number Nomenclature
Model Type
40RL = Vane Axial Fan Packaged Air-Handling
Puron Advance™ R-454B Refrigerant
Coil Options
A = Standard Aluminum Fin/Copper Tube
Type of Coil
A = Standard 4 Row DX
S = Chilled Water Coil
Q = Heat Pump Coil
Refrigeration Options
A = None
Fan Motor Speed Controller
A = Two Speed Direct Drive - EcoBlue™ Vane Axial Fan
Indoor Fan Motor Options — ECM Motor
2 = Medium Static
3 = High Static
Nominal Tonage
07 = 6.0 Tona
08 = 7.5 Ton
10 = 8.5 Tonb
12 = 10.0 Ton
Voltage
1 = 575-3-60
5 = 208/230-3-60
6 = 460-3-60
Design Revision
– = Factory Design Revision
Control Box
U = Electromechanical Unit Control Board
Future Use
A = Standard
Cabinet Paint
0 = None
1 = Painted
Packaging Compliance
0 = Standard
Future Use
A = Standard
Example:

Position:
4 0RL AA 1 2A2 A 6– U A0A0
123456789 10 11 12 13 14 15 16 17 18
NOTE(S):
a
40RLA and 40RLQ units only.
b
40RLS units only.
606
Item5.
5 Fig. 2 — 40RL 07-12 Base Unit Dimensions
607
Item5.
6 Fig. 2 — 40RL 07-12 Base Unit Dimensions (cont)
608
Item5.
7 Table 1 — 40RLA 6-10 Ton Direct Expansion with Puron Advance™ Refrigerant Units UNIT 40RLAA07 40RLAA08 40RLAA12
NOMINAL CAPACITY (Tons) 67.5 10
OPERATING WEIGHT (lb)
Base Unit with TXV (4 Row) 399 404 425
Plenum 175 175 175
Economizer 185 185 185
Hot Water Coila
NOTE(S):
a. Field-installed accessory only.
195 195 195
Steam Coila 215 215 215
FANS
Qty...Diam. (in.) 1…23 1…23 1…23
Nominal Airflow (cfm) 2400 3000 4000
Airflow Range (cfm) 1800-3000 2250-3750 3000-5000
Nominal Motor HP (Standard Motor)b
b. 40RL units are medium static option.
208/230-3-60 and 460-3-60 2.4 2.4 2.4
575-3-60 2.4 2.4 2.4
Motor Speed (rpm)
208/230-3-60 and 460-3-60 2000 2000 2000
575-3-60 2000 2000 2000
REFRIGERANTc
c. Units are shipped without refrigerant charge.

Puron Advance™ (R-454B) Puron Advance™ (R-454B) Puron Advance™ (R-454B) Shipping Charge (lb) Nitrogen Purge Nitrogen Purge Nitrogen Purge Metering Device TXV TXV TXV
Operating Charge (lb) (approx per circuit) 3.0 3.0 1.5/1.5 DIRECT-EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins Max Working Pressure (psig) 650 650 650
Material (Tube / Fin) Al / Cu Al / Cu Al / Cu
Coil Type RTPF RTPF RTPF
Face Area (sq ft) 6.67 8.33 10.01
No. of Splits 112
Split Type...Percentage — — Face...50/50
No. of Circuits per Split 12 15 9
Rows...Fins/in. 4...15 4...15 4...15
STEAM COILa
Max Working Press. (psig at 260°F) 20 20 20
Total Face Area (sq ft) 6.67 6.67 6.67
Rows...Fins/in. 1...9 1...9 1...9
HOT WATER COILa
Max Working Pressure (psig) 150 150 150
Total Face Area (sq ft) 6.67 6.67 6.67
Rows...Fins/in. 2...8.5 2...8.5 2...8.5
Water Volume
(gal) 8.3 8.3 8.3
(ft3) 1.1 1.1 1.1

PIPING CONNECTIONS
Quantity...Size (in.)
DX Coil — Suction (ODF) 1...1-1/8 1...1-1/8 2...1-1/8
DX Coil — Liquid Refrig, (ODF) 1...5/8 1...5/8 2...5/8
Steam Coil, In (MPT) 1...2-1/2 1...2-1/2 1...2-1/2
Steam Coil, Out (MPT) 1...1-1/2 1...1-1/2 1...1-1/2
Hot Water Coil, In (MPT) 1...1-1/2 1...1-1/2 1...1-1/2
Hot Water Coil, Out (MPT) 1...1-1/2 1...1-1/2 1...1-1/2 Condensate (PVC) 1...5/8 ODM / 1-1/4 IDF
FILTERS Throwaway — Factory-Supplied
Quantity...Size (in.) 4...16 x 24 x 2
Access Location Right or Left Side
LEGEND
DX — Direct Expansion
IDF — Inside Diameter, Female
ODF — Outside Diameter, Female
ODM — Outside Diameter, Male
TXV — Thermostatic Expansion Valve
609
Item5.
8 LEGEND
Table 2 — 40RLQ 6-10 Ton Heat Pump Units
UNIT 40RLQA07 40RLQA08 40RLQA12
NOMINAL CAPACITY (Tons) 67.5 10
OPERATING WEIGHT (lb)
Base Unit with TXV 381 385 427
Plenum 175 175 175
FANS
Qty...Diam. (in.) 1…23 1…23 1…23
Nominal Airflow (cfm) 2400 2625 3000
Airflow Range (cfm) 1800-3000 2250-3750 3000-5000
Nominal Motor HP (Standard Motor)
208/230-3-60 and 460-3-60 2.4 2.4 2.4
575-3-60 2.4 2.4 2.4
Motor Speed (rpm)
208/230-3-60 and 460-3-60 2000 2000 2000
575-3-60 2000 2000 2000
REFRIGERANT R-454B R-454B R-454B
Operating Charge (lb) (approx per circuit)a
NOTE(S):
a. Units are shipped without refrigerant charge.

3.0 3.0 2.0/2.0

DIRECT-EXPANSION COIL
Max Working Pressure (psig) 650 650 650
Face Area (sq ft) 8.33 8.33 10.0
No. of Splits 112
No. of Circuits per Split 12 12 9
Split Type...Percentage Face...100 Face...100 Face...50/50 Rows...Fins/in. 4...15 4...15 4...15

PIPING CONNECTIONS
Quantity...Size (in.)
DX Coil — Suction (ODF) 1...1-1/8 1...1-1/8 2...1-1/8
DX Coil — Liquid Refrigerant (ODF) 1...5/8 1...5/8 2...5/8 Steam Coil, In (MPT) 1...2-1/2 1...2-1/2 1...2-1/2
Steam Coil, Out (MPT) 1...1-1/2 1...1-1/2 1...1-1/2
Hot Water Coil, In (MPT) 1...1-1/2 1...1-1/2 1...1-1/2
Hot Water Coil, Out (MPT) 1...1-1/2 1...1-1/2 1...1-1/2 Condensate (PVC) 1...5/8 ODM / 1-1/4 IDF

FILTERS
Quantity...Size (in.) 4...16 x 24 x 2 4...16 x 24 x 2 4...16 x 24 x 2 Access Location Either Side Either Side Either Side
STEAM COILb
b. Field installed accessory only.

Max Working Pressure (psig at 260°F) 20 20 20
Total Face Area (sq ft) 6.67 6.67 6.67
Rows...Fins/in. 1...9 1...9 1...9
HOT WATER COILb
Max Working Pressure (psig) 150 150 150
Total Face Area (sq ft) 6.67 6.67 6.67
Rows...Fins/in. 2...8.5 2...8.5 2...8.5
Water Volume
(gal) 8.3 8.3 8.3
(ft3) 1.1 1.1 1.1
DX — Direct Expansion
IDF — Inside Diameter, Female
ODF — Outside Diameter, Female
ODM — Outside Diameter, Male
TXV — Thermostatic Expansion Valve
610
Item5.
9 LEGEND
Table 3 — 40RLS Physical Data — Chilled Water Units
UNIT 40RLSA08 40RLSA10 40RLSA12
NOMINAL CAPACITY (Tons) 7.5 8.5 10
OPERATING WEIGHT (lb)
Base Unit with TXV (4 Row) 390 391 391
Plenum 175 175 175
Economizer 185 185 185
Hot Water Coila
NOTE(S):
a. Field installed accessory only.
195 195 195
Steam Coila 215 215 215
FANS
Qty...Diam. (in.) 1…23 1…23 1…23
Nominal Airflow (cfm) 3000 3400 4000
Airflow Range (cfm) 2250-3750 2250-4250 3000-5000
Nominal Motor HP (Standard Motor)b
b. 40RL units are medium static option.
208/230-3-60 and 460-3-60 2.4 2.4 2.4
575-3-60 2.4 2.4 2.4
Motor Speed (rpm)
208/230-3-60 and 460-3-60 2000 2000 2000
575-3-60 2000 2000 2000
CHILLED WATER COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins Max Working Pressure (psig) 435 435 435
Face Area (sq ft) — Upper 8.3 9.0 9.8
Face Area (sq ft) — Lower ———
Rows...Fins/in. 3...15 3...15 3...15
Water Volume
(gal) 3.0 3.3 3.5
(ft3) 0.40 0.47 0.46
STEAM COILa
Max Working Pressure
(psig at 260°F) 20 20 20
Total Face Area (sq ft) 6.67 6.67 6.67
Rows...Fins/in. 1...9 1...9 1...9
HOT WATER COILa
Max Working Press. (in. wg) 150 150 150
Total Face Area (sq ft) 6.67 6.67 6.67
Rows...Fins/in. 2...8.5 2...8.5 2...8.5
Water Volume
(gal) 8.3 8.3 8.3
(ft3) 1.1 1.1 1.1

PIPING CONNECTIONS
Quantity...Size (in.)
Chilled Water — In 1...1-3/8 ODF 1...1-3/8 ODF 1...1-3/8 ODF Chilled Water—Out 1...1-3/8 ODF 1...1-3/8 ODF 1...1-3/8 ODF Steam Coil, In (MPT) 1...2-1/2 1...2-1/2 1...2-1/2
Steam Coil, Out (MPT) 1...1-1/2 1...1-1/2 1...1-1/2
Hot Water Coil, In (MPT) 1...1-1/2 1...1-1/2 1...1-1/2
Hot Water Coil, Out (MPT) 1...1-1/2 1...1-1/2 1...1-1/2 Condensate (PVC) 1...5/8 ODM / 1-1/4 IDF
FILTERS Throwaway — Factory-Supplied
Quantity...Size (in.) 4...16 x 24 x 2
Access Location Right or Left Side
IDF — Inside Diameter, Female
ODF — Outside Diameter, Female
ODM — Outside Diameter, Male
611
Item5.
10 Fig. 3 — Foam Block Location
Rated Indoor Airflow (cfm)
Tables 4-6 list the rated indoor airflow used for the AHRI (AirConditioning, Heating, and Refrigeration Institute) efficiency rating for the units covered in this document.

Unit Positioning
The unit can be mounted on the floor for vertical application with return air entering the face of the unit and supply air discharging vertically through the top of the unit. The unit can also be applied in a horizontal arrangement with return air entering horizontally and the supply air discharging horizontally.

When applying the unit in a horizontal arrangement, ensure the condensate drain pan is located at the bottom center of the unit for adequate condensate disposal. See Fig. 4 for condensate connections for each unit position.

Fig. 4 — Typical Unit Positioning
Typical positioning and alternate return air locations are shown in Fig. 4. Alternate return air locations can be used by moving the unit panel from the alternate return air location to the standard return air location. Refer to overhead suspension accessory drawing (see Fig. 5) for preferred suspension technique. The unit needs support underneath to prevent sagging.

Unit Isolation
Where extremely quiet operation is essential, install isolators between floor and base of unit, or between ceiling and top section of unit.

Be sure that unit is level and adequately supported. Use channels at front and sides of unit for reference points when leveling.

Fig. 5 — Preferred Suspension Technique
Table 4 — 38AXZ with 40RLA

MODEL NUMBER FULL LOAD AIRFLOW (CFM)
38AXZM/N07 — 40RLA*07 2400
38AXZM/N08 — 40RLA*08 3000
38AXZM/N12 — 40RLA*12 4000
Table 5 — 38AXD with 40RLA

MODEL NUMBER FULL LOAD AIRFLOW (CFM)
38AXDT/U12 — 40RLA*12 4000
Table 6 — 38AXQ with 40RLQ

MODEL NUMBER FULL LOAD COOLING

AIRFLOW (CFM)

FULL LOAD HEATING

AIRFLOW (CFM)
38AXQM/N07 — 40RLQ*07 2400 2400
38AXQM/N08 — 40RLQ*08 3000 3000
38AXQM/N12 — 40RLQ*12a
NOTE(S):
a. The 38AXQM/N12 — 40RLQ*12 has different rated airflows for heating and cooling. Set airflow while unit is in cooling mode, when unit switches to heating, the controls will automatically adjust airflow.
3500 3000
Coil TXV
Remove Foam Block
LEGEND
TXV — Thermostatic Expansion Valve
IMPORTANT: Do NOT attempt to install unit with return air entering top panel of unit. Condensate will not drain from unit.

IMPORTANT: Do not bury refrigerant piping underground.

LEGEND
Accessory Line
Alternate Air Intake and Discharge
Air Intake and Discharge
Plug
Plug Condensate Drain
NOTE: Dimensions in [ ] are millimeters.

OVERHEAD SUSPENSION ACCESSORY
UNIT SIZE 6-10 TONS
612
Item5.
11 Refrigerant Piping
See Tables 1-3 for refrigerant pipe connection sizes. For ease in brazing, it is recommended that all internal solder joints be made before unit is placed in final position.

The 40RL direct-expansion units have internal factory-installed thermostatic expansion valves (TXVs), distributors, and nozzles for use with R-454B. See Table 7 for part numbers. Knockouts are provided in the unit corner posts for 40RL refrigerant piping. See Fig. 6, which also lists recommended knockouts and access holes to use for each 40RL unit size. Recommended fittings are listed in Table 8.

The sensor bulb capillary tubes must be routed from the TXVs inside the unit through one of the piping access holes. Clamp the TXV sensor bulb on a vertical portion of the suction line, outside the unit. (See Fig. 7.)
Requirements of A2L Refrigerant Piping
The following must be adhered to for refrigerant piping:
• Installation of pipe-work must be kept to a minimum, with minimum piping lengths whenever possible.
• Connecting joints shall only be made in easily accessible locations for service purposes.
• There shall be no bends in pipe-work lines with a centerline bend radius less than 2.5 times the external diameter. • Pipework must be protected from potential damage during normal operation, service or maintenance.

Refrigerant and Chilled Water Piping Access
The 40RL Series units come with standard knockouts for refrigerant and chilled water piping. These knockouts are located on both sides of the unit for installation flexibility. The standard knockouts provide sufficient access to the unit’s coils for all 40RLA*07, 08, and 12 and 40RLQ*07, 08, and 12 units. 40RLS*08 and units require additional holes that must be field-fabricated to accommodate the piping. See Fig. 6 for the positions and dimensions of the additional access holes required for 40RLS units. Recommended access hole use is also listed for all units. Note that Fig. 6 shows the access holes on the controlbox side of the unit; this is the side of the unit with the coil headers, so it is used most often for piping access.

NOTE: Be sure to remove the foam shipping pad from the TXV.

Verify that it has been removed. (See Fig. 3.)
The 40RL Series evaporator coils have a face-split design. Ensure that lower circuit of coil is first on/last off when connected to the condensing unit and/or system controls. (See Fig. 8.)
External TXV equalizer connections are provided and factorybrazed into the coil suction manifolds.

If suction line must be horizontal, clamp bulb to suction line at least 45 degrees above bottom, at approximately the 4 o’clock or 8 o’clock position. (See Fig. 9.)
Fig. 6 — Refrigerant and Chilled Water Piping Access Holes IMPORTANT: Never attach the sensor to the suction manifold. Do NOT mount the sensor on a trapped portion of the suction line.

Table 7 — Factory-Installed Nozzle and Distributor Data

UNIT COIL TYPE STD TXV
QTY...PART NO.

DISTRIBUTOR
QTY... PART NO.

FEEDER TUBES PER
DISTRIBUTORa
QTY...SIZE (in.)
NOTE(S):
a. Feeder tube size is 1/4 in. (6.35 mm).

NOZZLE
QTY...PART NO.
40RLA*07 4 Row 1...BBIZE— 4— GA 1...1135 12...1/4 1...G4 40RLQ*07 4 Row 1...BBIZE—4— GA 1...1136 15...1/4 1...G5 40RLA*08 4 Row 1...BBIZE— 6— GA 1...1136 15...1/4 1...G5 40RLQ*08 4 Row 1...BBIZE— 8— GA 1...1113 12...3/16 1...G5 40RLA*12 4 Row 2...HXAE-5-KX 2...1135 9...1/4 2...G3
40RLQ*12 4 Row 2...BBIZE— 5— GA 2...1113 9...3/16 2...G3 4 3
2 1
5 A
Field-Fabricated Access Holes

UNIT USE HOLE
NUMBERSa
NOTE(S):
a. Access hole knockouts 1-4 are factory-supplied.

FIELD-FABRICATED HOLE

DIAMETERS
in. (mm)

FIELD-FABRICATED HOLE

POSITION
DIMENSIONS, in. (mm)
NO. 5 NO. 6 NO.7 A B C
40RLA*07, 08
40RLQ*07,08 1, 3 — — — — — —
40RLA*12
40RLQ*12 1, 2, 3, 4 — — — — — —
40RLS*08, 10, 12 4, 5 1-3/4
(44.5) —— 6.25
(158.8) ——
613
Item5.
12 Fig. 7 — Face-Split Coil and Liquid Line Piping (Typical) Table 8 — Fitting Requirements
UNIT ACCESS HOLE NO.a
NOTE(S):
a. See Fig. 6 for access hole location by number.

CONNECTION TYPE CIRCUIT FITTING REQUIREDb (in.)
b. Fittings are listed in order from header or tee stub connection out to access hole in corner support post. 40RLA*07
40RLQ*07
1 Suction —
1-1/8 Street Elbow
1-1/8 Nipple, 10-5/8 L
1-1/8 Long Radius Elbow
3 Liquid —
5/8 Street Elbow
5/8 Nipple, 8-5/8 L
5/8 Long Radius Elbow
40RLA*08
40RLQ*08
1 Suction —
1-1/8 Street Elbow
1-1/8 Nipple, 8-5/8 L
1-1/8 Long Radius Elbow
3 Liquid —
5/8 Street Elbow
5/8 Nipple, 8-5/8 L
5/8 Long Radius Elbow
40RLS*08
40RLS*10
40RLS*12
4 Return —
1-3/8 Nipple, 4-3/8 L
1-3/8 Long Radius Elbow
1-3/8 Nipple, 7-3/8 L
1-3/8 Long Radius Elbow
5 Supply — 1-3/8 Nipple, 6-5/8 L
1-3/8 Long Radius Elbow
40RLA*12
1 Suction Lower (2) 1-1/8 Street Elbow
2 Liquid Lower
5/8 Street Elbow
5/8 Nipple, 8-1/2 L
5/8 Long Radius Elbow
3 Liquid Upper
5/8 Street Elbow
5/8 Nipple, 13-1/2 L
5/8 Long Radius Elbow
4 Suction Upper
1-1/8 Nipple, 5-3/4 L
1-1/8 Long Radius Elbow
1-1/8 Nipple, 12 L
1-1/8 Long Radius Elbow
40RLQ*12
1 Suction Lower (2) 1-1/8 Street Elbow
2 Liquid Lower
5/8 Street Elbow
5/8 Nipple, 5-1/2 L
5/8 Long Radius Elbow
3 Liquid Upper
5/8 Street Elbow
5/8 Nipple, 10-1/2 L
5/8 Long Radius Elbow
4 Suction Upper
1-1/8 Nipple, 5-5/8 L
1-1/8 Long Radius Elbow
1-1/8 Nipple, 12 L
1-1/8 Long Radius Elbow
LEGEND
TXV — Thermostatic Expansion Valve
NOTE: Component location arrangement shown for field installation of sight glasses, solenoid valves, filter driers, and TXV sensing bulbs.

The TXVs and equalizer lines are factory-installed.

UPPER
SPLIT

AIRFLOW
LOWER
SPLIT

AIRFLOW
15 DIAMS
MIN 10
DIAMS
8 DIAMS
MIN
TXV

SENSING
BULB

EQUALIZER LINE
SIGHT

TXV GLASS

SOLENOID
VALVE
FILTER

DRIER TXV

SENSING
BULB
TXV
8 DIAMS
MIN
15 DIAMS
MIN 10
DIAMS
INDOOR
COIL

EQUALIZER
LINE
Single Circuit Coil Piping Configuration - 6-7.5 ton units For single compressor condensing units.

Dual Circuit Coil Piping Configuration - 10 ton units
For single compressor condensing units
UPPER
SPLIT
AIRFLOW 15 DIAMS
MIN 10
DIAMS
8 DIAMS
MIN
TXV

SENSING
BULB

EQUALIZER LINE
SIGHT
GLASS
TXV

SOLENOID
VALVE
FILTER
DRIER
614
Item5.
13 Fig. 8 — Typical Evaporator Coil Connections (40RL)
Fig. 9 — TXV Sensing Bulb Location
Chilled Water Piping
See Table 3 for chilled water connection sizes. For ease in brazing, it is recommended that all internal solder joints be made before unit is placed in final position.

Knockouts are provided in the unit corner posts for 40RLS refrigerant piping. Additional field-fabricated access holes are required for 40RLS chilled water piping. See Fig. 6, which lists recommended knockouts and access holes to use for each 40RLS unit size.

To size, design, and install chilled water piping, consult the Carrier System Design manual. See Fig. 10 for an example of a typical installation. Recommended fittings are listed in Table 8.

To access 40RLS coil vents and drains, remove the unit side panel over the coil header. Vent and drain plugs are on the top and bottom of header, respectively. See the Service section for information on preventing coil freeze-up during winter.

Fig. 10 — Typical 40RLS Chilled Water Piping
First On/Last Off = B
Vertical Installation
First On/Last Off = A
Horizontal Installation
A
B
Liquid Line
Connection
Suction-Vapor
Connection
Condensate
Drain
Connection
A
B
Condensate Drain Connection
LEGEND
TXV — Thermostatic Expansion Valve
NOTE: The 8 o’clock position is shown above.

Vapor Line
45°
Strap
TVX Bulb
Return
Air
Subbase Subbase
Gauge
Cocks
Condensate
Trap
Disconnect
Union
Control
Valve
Caps for
Blowout
Return Return
Dirt
Leg
Cap
Pump
Supply Line
615
Item5.
14 Condensate Drain
Install a trapped condensate drain line to unit connection as shown in Fig. 11. The unit drain connection is a PVC stub. (See Fig. 12.) Some areas may require an adapter to connect to either galvanized steel or copper pipe. For these applications, install a field-supplied threaded PVC adapter.

NOTE: A trap must be installed in the condensate drain line to ensure that the static pressure of fans is balanced with the water column in the drain line and that condensate can drain completely from pan. Without a trap, air can be drawn up drain line until water level in condensate pan becomes equal to static pressure created by fans, preventing complete drainage. Conditions will worsen as filters become dirty.

Install clean-out plugs in trap. Pitch drain line downward to an open floor drain or sump. Provide service clearance around drain line to permit removal of unit panels. Observe all local sanitary codes.

As shipped, the unit’s condensate drain pan is NOT sloped towards the drain connection. The pan slope must be changed to pitch towards the side of the unit with the drain connection. (See Fig. 12.) Loosen the 2 screws next to the drain outlet at both ends of the unit, push drain pan down in the slots near the drain connection, and up in the slots on the opposite end. Re-tighten screws.

The pan should have a pitch of at least 1/4 in. over its length toward the drain connection.

Fig. 11 — Condensate Drain
Fan Motors and Drives
Motor and drive packages are factory installed in all units. The motor and drive packages consist of the following items:
1 — ECM fan motor
1 — EcoBlue™ direct drive vane axial fan system
For instructions on setting the fan speed see Supply Fan (Direct Drive) on page 26.

Fig. 12 — Drain Pan Slope Adjustment
Power Supply and Wiring
Check the unit data plate to ensure that available power supply matches electrical characteristics of the unit. Provide a disconnect switch with an integrated lock-out feature of size required to provide adequate fan motor starting current. See Table 9 for unit electrical data. See Table 10 for recommended torque of the ground lug screw when using approved electrical wire for the electrical ground. Route the field power wiring in through the opening designated in Fig. 14.

Fig. 13 — Disconnect Switch and Unit
3” MIN.
[76]
NOTE: Dimensions in [ ] are in millimeters
Plug
3" Min.
[76]
From
Condensate
Pan
Existing Floor
Drain, Sink, or
Hopper Unit
Condensate
Conn
Trap
Not Less Than 18" [457]
Long and Two Sizes
Larger Than Waste Pipe
To Sewer
1" Min. 1" Min.

Plug
Plug
3" Min.
[76]
3" Min.
[76]
Trap
[25] [25]
Plug

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.

Do not use gas piping as an electrical ground. Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code); ANSI/NFPA 70, latest edition (in Canada, Canadian Electrical Code CSA [Canadian Standards Association] C22.1), and local electrical codes.

WARNING

FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.

Do not connect aluminum wire between disconnect switch
and fan coil unit. Use only copper wire. (See Fig. 13.) Adjustment Slots
(both ends of unit)
PVC Stub Unit
Drain Connection
Electric
Disconnect
Switch
Aluminum
Wire
Copper
Wire Only
616
Item5.
15 LEGEND
NOTES:

1. Minimum circuit amps (MCA) and maximum overcurrent protection (MOCP) values are calculated in accordance with The NEC.

Article 440.

2. Motor FLA values are established in accordance with Underwriters Laboratories (UL) Standard 60335-2-40.

3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the formula in the example (see column to the right) to determine the percentage of voltage imbalance.

4. Installation with Accessory Electric Heaters
Size the Field Power Wiring between the heater TB1 and the 40RL indoor fan motor per NEC Article 430-28 (1) or (2) (depends on length of conduit between heater enclosure and 40RL power entry location). Install wires in field-installed conduit.

Example: Supply voltage is 230-3-60
Determine maximum deviation from average voltage.
(AB) 227-224 = 3 v
(BC) 231-227 = 4 v
(AC) 227-226 = 1 v
Maximum deviation is 4 v.

Determine percent of voltage imbalance.

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

Table 9 — Electrical Data, Standard Motors — Two Speed

UNIT NOMINAL
V-PH-Hz
IFM
TYPE

UNIT VOLTAGE

RANGE FAN MOTOR POWER SUPPLY
Min. Max. Hp kW FLA
Minimum
Circuit Amps
(MCA)
Maximum
Overcurrent
Protection
(MOCP)
40RLA*07
40RLQ*07
208/230-3-60 MED 187 253 2.4 1.76 6.4/5.8 8/8 15/15
HIGH 187 253 3.0 2.24 7.5/6.7 10/9 15/15
460-3-60 MED 414 506 2.4 1.76 3.0 4 15
HIGH 414 506 3.0 2.24 3.5 5 15
575-3-60 MED 518 632 2.4 1.76 2.5 4 15
HIGH 518 632 3.0 2.24 3.0 4 15
40RLA*08
40RLS*08
40RLQ*08
208/230-3-60 MED 187 253 2.4 1.76 6.4/5.8 8/8 15/15
HIGH 187 253 3.0 2.24 7.5/6.7 10/9 15/15
460-3-60 MED 414 506 2.4 1.76 3.0 4 15
HIGH 414 506 3.0 2.24 3.5 5 15
575-3-60 MED 518 632 2.4 1.76 2.5 4 15
HIGH 518 632 3.0 2.24 3.0 4 15
40RLS*10
208/230-3-60 MED 187 253 2.4 1.76 6.4/5.8 8/8 15/15
HIGH 187 253 3.0 2.24 7.5/6.7 10/9 15/15
460-3-60 MED 414 506 2.4 1.76 3.0 4 15
HIGH 414 506 3.0 2.24 3.5 5 15
575-3-60 MED 518 632 2.4 1.76 2.5 4 15
HIGH 518 632 3.0 2.24 3.0 4 15
40RLA*12
40RLS*12
40RLQ*12
208/230-3-60 MED 187 253 2.4 1.76 6.4/5.8 8/8 15/15
HIGH 187 253 3.0 2.24 7.5/6.7 10/9 15/15
460-3-60 MED 414 506 2.4 1.76 3.0 4 15
HIGH 414 506 3.0 2.24 3.5 5 15
575-3-60 MED 518 632 2.4 1.76 2.5 4 15
HIGH 518 632 3.0 2.24 3.0 4 15
FLA — Full Load Amps
HACR — Heating, Air Conditioning, and Refrigeration
% Voltage
Imbalance = 100 x max voltage deviation from average voltage average voltage
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage = (224 + 231 + 226) = 681 = 227 33
% Voltage Imbalance = 100x 4 = 1.78% 227
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

A B C
MOTOR
617
Item5.
16 Install disconnect switch and power wiring in accordance with all applicable local codes. See Fig. 13-15 and the unit wiring diagram label (Fig. 18). For units with motor sizes less than 5 Hp (3.7 kW), connect power wiring to unit with no. 10 ring terminal. For units with motor sizes of 5 Hp (3.7 kW) or more, connect power wiring with 1/4 in. ring terminal.

Fig. 14 — Wiring and Service Access
(Side Panel Removed)
Fan motors are factory-installed on all units.

The control box contains a Unit Control Board (UCB) that receives thermostat commands from the thermostat (through the Thermostat Connection Board) and, outputs these commands to the condensing unit (through the Indoor Connection Board) as well as a high voltage terminal block.

Complete 24-v control circuit wiring. Wire the thermostat to the Thermostat Connection Board terminal strip (TSTAT CB), according to Fig. 15 and the unit wiring diagram label (see Fig. 18). If the air handler is part of a split system, complete the wiring from the condensing unit to the Indoor Connection Board terminal strip (IDCB). Refer to Fig. 15 and the unit wiring diagram label. Route the field control wiring in through the opening designated in Fig. 14.

NOTE: The control box may have some additional components; see Fig. 16 and 17.

Fig. 15 — Unit Control Box
Table 10 — Recommended Torque of
Ground Lug Field Connection
AWG TORQUE (in.-lb)
16 35±4
14 35±4
12 35±4
10 35±4
8 40±5
6 45±5.5
4 45±5.5
2 50±6
0 50±6
00 50±6
Refrigerant
Piping Access
Field Control
Wiring Entrance
Field Power
Wiring Entrance
Filter
Retainer
Clip
Dissipation
Board
Control Box
(Cover On)
Condensate
Drain
Connection
(Horizontal)
A2L
Sensor 1 Coil
Filter
Elements
Fan Assembly
Condensate
Drain
Connection
(Vertical)
A2L Sensor 2
TXV Bulb
Access
Control Box
(Cover Off)
Indoor
Connection
Board (IDCB)
Thermostat
Connection Board
(TSTAT CB)
High Voltage
Terminal Block
Unit
Control
Board
Ground
Lug
Exit for Power Wiring Exit for Low Voltage Wiring
618
Item5.
17 Fig. 16 — Unit Control Box
with Freeze Protection Relay
Fig. 17 — Unit Control Box
with Heat Speed Reduction Relay (DIN Rail Mounted)
Freeze
Protection
Relay Heat Speed
Reduction Relay
(DIN Rail-Mounted)
619
Item5.
18 Fig. 18 — Unit Wiring Diagram 620
Item5.
19 THREE STAGE OPERATION
All units are factory shipped for 2-stage cooling operation. To convert a unit to 3-stage operation, see Fig. 19 and adjust the following wires between the control board and two terminal strips on the side of the control box:

1. Remove gray wire at Thermostat CB terminal X and insulate.

2. Move orange wire from Thermostat CB terminal Y2 to
terminal X.

3. Make connections of blue wire included in factory harness.

Connect one end to Thermostat CB terminal Y2 and the other to Indoor Connection Board terminal Y2.

4. Move orange wire from Indoor Connection Board terminal Y2 to terminal X.

The 3-stage system will run the fan at low speed with a G, Y1, and Y1+Y2 call, and at high speed with a call for Y1, Y2, and Y3.

A thermostat with 3 cooling stage capability is required for this system configuration.

Fig. 19 — Three Stage Wiring
DDC
TSTAT
Y1
Y2
X
Y1
Y2
X
UCB
COMP
BLU
BLU
BLU
BLU
ORN
BLU
ORN
ORN

TSTAT CB
IDCB
This wire is included
in factory harness
GRA
Disconnect this wire from
TSTAT CB-X and insulate.
621
Item5.
20 Leak Dissipation System
40RL units use R-454B refrigerant. These units are equipped with a factory installed R-454B leak dissipation system to ensure safe operation in the event of a refrigerant leak. This systems consists of two A2L sensors and the dissipation control board (Fig. 20) which are located in the return (indoor entering) section of the unit. The A2L sensors are located between the indoor coil and the air filters. See Fig. 22 for a more detailed view of the dissipation control box.

Fig. 20 — Location of A2L Sensors and Dissipation
Control Board (Shown with Cover Removed)
The A2L detection sensors communicate via wiring harnesses to the dissipation boards. Each sensor harness is routed directly from the sensor to the dissipation control board through the wire access hole in the sheet metal box. Extra length of harness should be neatly bundled and wire tied.

The drain wire must be properly connected to the ground lug on the dissipation board via the quick connect and ground harness.

Failure of proper sensor harness grounding can lead to false dissipation events.

NOTE: Chilled water units do not come with the leak dissipation system.

SEQUENCE OF OPERATION
The control functions as an R-454B refrigerant dissipation system.

If either of the refrigerant detection sensors sends a signal indicating a refrigerant leak, the control board will prevent heating and cooling operation and begin dissipating the sensed refrigerant with a blower request. The refrigerant dissipation board will display a flash code from the yellow status LED (see Fig. 21) indicating the sensor that detected the refrigerant. See Fig. 24 — on page 22 for the full text on the Dissipation Control box cover label.

When the sensor signal indicates the refrigerant has dissipated, the dissipation board yellow status LED will display a flash code 3 and return to its normal state and allow unit operations after a 5 minute delay.

LEAK DISSIPATION SYSTEM SELF-TEST
Power on the unit and verify proper functioning of equipment.

The yellow Status LED on the dissipation board should be steady (see Fig. 21). If flash codes are present, see Troubleshooting on page 22.

NOTE: Operation of the Test Mode is only possible if no faults exist on the dissipation board.

Remove the cover from the Dissipation control box to access the Test button (see Fig. 23). The Test button is located above the COMM LED.

Fig. 21 — Yellow STATUS LED
Fig. 22 — Dissipation Control Box
A2L Sensor 1
A2L Sensor 2
Dissipation Board
Status
LED
622
Item5.
21 Fig. 23 — Dissipation Control Board — Shown without Dust Cover Press the Test button on the dissipation system control board to ensure proper dissipation system operation under each test condition listed below. After pressing the Test button, system will enter Dissipation Mode for 60 seconds to help verify correct operation.

Ensure that the unit is able to meet the minimum required dissipation mode airflows. These required minimum airflow rates during Dissipation Mode are listed in Table 12. Table 12 also shows the minimum required total conditioned room area. Both minimum required airflow and room area are based on the maximum possible charge in the system, calculated from the longest line set for each system listed in the condensing unit installation instructions.

See
Detail A
See
Detail B
Detail A — Test Button Detail B — Status LED
IMPORTANT: Press the Test button for roughly ONE SECOND to enter Test Mode. Pressing the Test button for a longer periods enables different functions (see Table 11).

Table 11 — Dissipation Board Test Button Functions

HOLD BUTTON TIME (SEC) FUNCTION
1-4 Dissipation Mode for 60 seconds
5-29 Display flash code history
30+ Flash code 6
3 Rapid Presses Clear flash code history
Table 12 — Minimum Dissipation Airflow and Minimum Required Area of Total Conditioned Space Based on Max System Charge
UNIT MAX ALLOWABLE CHARGE (lb) AIRFLOW (cfm) ROOM AREA (ft2) 38AXZM/N07-40RLA*07 33.5 910 505
38AXZM/N08-40RLA*08 43.2 1170 650
38AXZM/N12-40RLA*12 78.8 2130 1180
38AXDT/U12-40RLA*12 82.5 2230 1240
38AXQM/N07-40RLQ*07 23.0 490 345
38AXQM/N08-40RLA*08 32.2 660 485
38AXQM/N12-40RLA*12 34.7 730 520
623
Item5.
22 Table 13 details the required operational checks to ensure proper dissipation system function.

Fig. 24 shows the flash codes displayed on the Dissipation control board.

TROUBLESHOOTING
For all flash codes, first try power cycling the system to remove the code.

No Power
Verify the wiring to/from pins 1 and 8 on the power harness plug.

Check the 24V system wiring the IDCB terminal in the main control box.

See Table 14 for details on the operating status and troubleshooting of the Dissipation system for the various flash codes.

Fig. 24 — Dissipation Control Cover Label
Table 13 — Dissipation System Required Operational
Checks

NORMAL OPERATION
TEST NO. UNIT

DEMAND COMPRESSOR INDOOR FAN

ELECTRIC
HEAT
1 None Off Off Off
2 Cool On On Off
3 Heat On for 40RLQ On On

DISSIPATION ACTIVATED
4 None Off On Off
5 Cool Off On Off
6 Heat Off On Off
Table 14 — Status LED Troubleshooting Table

STATUS LED REASON CONTROL VERBIAGE MODE
1 Flash Sensor 1 ≥ 20% LFL REFRIG DISSIPATION ACTIVE Dissipation in Process 2 Flash Sensor 1 Open REFRIG SENSOR OPEN Dissipation in Process 3 Flash
5 Minute Blower Operating, Sensor < 20%
LFL and sensors are not opened (done after
fault 1, 2, 9 and 10)
DISSIPATION OFF DELAY ACTIVE Dissipation in Process
4 Flash 0 VAC sensed on G output. BLOWER OUTPUT NOT OPERATING Dissipation in Process 5 Flash Fault with the A2L digital sensor REFRIG SENSOR FAULT Dissipation in Process 6 Flash If KY1 is stuck pressed for more than 30
seconds. TEST BUTTON STUCK
To prevent a shorted KY1 to keep
the dissipation running
continuously.
7 Flash Y out switched with Y in or W out switched
with W in Y (K4) OR W (K1) WIRING INVERTED Normal mode
8 Flash Y or W shorted (relay detects both sides are
high)
Y (K4) OR W (K1) OUTPUT SHORTED
TO Y (K4) OR W (K1) INPUT Normal mode
9 Flash Sensor 2 ≥ 20% LFL SENSOR 2 DISSIPATION ACTIVE Dissipation in Process 10 Flash Sensor 2 Open SENSOR 2 OPEN Dissipation in Process 11 Flash Fault with the second A2L digital sensor SENSOR 2 FAULT Dissipation in Process 12 Flash High temperature sensor attached on
commercial

OVERCURRENT INCORRECT
SENSOR Normal mode
13 Flash G input signal is lost. Indicates another unit safety will override dissipation. EXT SAFETY OVERRIDE Normal mode LEGEND
LFL — Lower Flammable Limit
624
Item5.
23 Connecting Ductwork
Refer to the Carrier System Design Manual for the recommended design and layout of ductwork.

DISCHARGE CONNECTION
Duct flanges are factory-supplied; they are shipped inside the unit attached to the hairpin end of the coil tube sheet for field installation. Using the existing screws, install the duct flange on the unit’s fan deck. The fan discharge requires 2 flanges; each flange must be bent in the middle to conform to the discharge opening. (See Fig. 25.) After flanges are installed, connect them to the supply duct using a canvas connection to prevent vibration. It is important that this connection be properly fabricated to prevent high air friction losses and air noise.

RETURN CONNECTIONS
When using return-air ductwork, route return-air duct to the unit’s return air inlet near the filter rack, using a canvas connection to prevent transmission of unit vibration. If the duct blocks off the unit’s access panel, provide a slip joint in the ductwork to permit removal for servicing.

OUTDOOR-AIR INLET CONNECTIONS
Connect outdoor-air inlet to field-installed accessory economizer.

Refer to Economizer Installation Instructions.

Return-Air Filters
Type and size of filters are shown in Tables 1-3 and are factorysupplied and factory-installed. In all units with 2 fans, a filter replacement tool (hook) is shipped inside the unit for field use when replacing filters. See the Service section for instructions on filter element replacement.

Fig. 25 — Duct Flange Installation

CAUTION

UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment damage.

Do not operate unit without ductwork or discharge plenum unless fan speed has been adjusted for external static pressure of zero in. wg. Failure to do so may result in motor overload.

Duct Flange
625
Item5.
24 START-UP
Before starting unit, check the following and correct as necessary:
• Is unit solidly supported?
• Are there any loose parts that will rattle or vibrate? • Is condensate drain pan pitched for correct drainage? • Are coil baffle plates tight against coil to prevent air bypass?
• Are all panels securely fastened?
• Are all electrical connections correct and tight?
• Are there any loose or disconnected wires in the control box, or wires in contact with sharp edges or moving parts? • Have all safety, caution, and warning labels been read? 40RLA and 40RLQ ONLY
• Is TXV bulb located on suction tube per Fig. 26?
• Is the capillary tube to the bulb free of kinks and not subject to pinching?
• Is the bulb well secured to the suction tube with strap? Also refer to condensing unit or outdoor heat pump section instructions before starting a split system. A split system start-up checklist is provided at the end of these instructions.

Fig. 26 — TXV Bulb Location Label
Adjusting TXV for Superheat
(40RLA and 40RLQ only)
The unit-mounted thermostatic expansion valve(s) is/are factory set to provided superheat at the bulb location in 10°F to 15°F (5.5°C to 8.3°C) range. Actual system load conditions may require adjustment of the factory setting. (See Fig. 27.)
To adjust the TXV superheat setting:

1. Remove the seal cap from the bottom of the TXV body.

2. To increase superheat, turn the stem clockwise. To decrease the superheat, turn the stem counterclockwise. Do not turn the stem more than one full turn.

3. Wait until suction pressure and superheat stabilize. This may take more than 30 minutes.

4. Continue adjustment until superheat reaches 10°F to 15°F (5.5°C to 8.3°C).

5. Replace the seal cap; tighten.

Fig. 27 — TXV Adjustment Label
Fan Performance
See Tables 19-45 for fan performance data, starting on page 35.

1. Interpolation is permissible. Do not extrapolate.

2. External static pressure is the static pressure difference between the return duct and the supply duct plus the static pressure caused by any FIOPs or accessories.

3. Tabular data accounts for pressure loss due to clean filters, unit casing and wet coils.

4. Factory options and accessories may effect static pressure losses. Selection software is available, through your salesperson, to help you select the best motor/drive combination for your application.

5. The fan performance tables (see Tables 19-45) offer motor/ drive recommendations. In cases when two motor/drive combinations would work, Carrier recommends the lower horsepower option.

6. The EPACT (Energy Policy Act of 1992) regulates energy requirements for specific types of indoor fan motors.

Motors regulated by EPACT include any general purpose,
T-frame (three-digit, 143 and larger), single-speed, foot mounted, polyphase, squirrel cage induction motors of
NEMA (National Electrical Manufacturers Association)
design A and B, manufactured for use in the United States.

Ranging from 1 to 200 Hp, these continuous-duty motors
operate on 230 and 460 volt, 60 Hz power. If a motor does not fit into these specifications, the motor does not have to be replaced by an EPACT compliant energy-efficient motor.

Variable-speed motors are exempt from EPACT compliance
requirements.

MAINTENANCE
These items should be part of a routine maintenance program, to be checked every month or two, until a specific schedule for each can be identified for this installation:

Quarterly Inspection
(and 30 days after initial start)

INDOOR SECTION
• Condenser coil cleanliness checked.
• Return air filter replacement
• Outdoor hood inlet filters cleaned
• Fan shaft bearing locking collar tightness checked
• Condensate drain checked
Heating
• Power wire connections
• Fuses ready
• Manual-reset limit switch is closed

IMPORTANT! / IMPORTANT40RU500072 2.0
The sensor bulb capillary tubes must be routed from the TXVs inside the unit through one of the piping access holes. Clamp the TXV sensor bulb on a vertical portion of the suction line, outside the unit.

Super heat must be adjusted in field.

Les tubes capillaires du capteur doivent être acheminé à partir du détendeur thermostatique situé à l'intérieur de l'appareil au travers de l'un des trous d'accès de conduites. Attacher le capteur sur une portion verticale de la conduite de succion, à l'extérieur de l'appareil. La surchauffe doit être ajustée sur place.

AIR FLOW

CIRCULATION
D'AIR

UPPER SPLIT
BLOC SUPÉRIEUR
LOWER
SPLIT
BLOC
INFÉRIEUR

AIR FLOW

CIRCULATION
D'AIR 15 DIAMS MIN
15 x DIA. MIN
10 DIAMS
10 x DIA. MIN

TXV SENSING
BULB

CAPTEUR TXV
15 DIAMS MIN
15 x DIA. MIN
10 DIAMS
10 x DIA. MIN
TXV

SENSING
BULB

CAPTEUR TXV

EQUALIZER LINE
CONDUITE D'ÉQUILIBRAGE

SIGHT GLASS
HUBLOT
8 DIAMS MIN
8 x DIA. MIN
TXV

SOLENOID
VALVE
VANNE
SOLÉNOÏDE
FILTER
DRIER
FILTRE

DESSICCATEUR
TXV

EQUALIZER LINE
CONDUITE D'ÉQUILIBRAGE
8 DIAMS MIN
8 x DIA. MIN INDOOR COIL
ÉCHANGEUR INTÉRIEUR

INSTALLER / INSTALLATEUR
TXV superheat must be checked at initial
unit start-up and adjusted if necessary.

Superheat must be 10 - 15 deg F.

La surchauffe TXV doit être vérifiée au
moment de la mise en route initiale et
ajustée si nécessaire. La surchauffe doit
être comprise entre 10 et 15 degrés F. 40RU500073 2.0
626
Item5.
25 See Tables 15 and 16 for unit specific maintenance checklists.

Seasonal Maintenance
These items should be checked at the beginning of each season (or more often if local conditions and usage patterns dictate):

AIR CONDITIONING
• Condenser fan motor mounting bolts tightness
• Compressor mounting bolts
• Condenser fan blade positioning
• Control box cleanliness and wiring condition
• Wire terminal tightness
• Refrigerant charge level
• Evaporator coil cleaning
• Evaporator blower motor amperage

SERVICE
Inspection and maintenance should be performed at regular intervals and should include the following:
• Complete cleaning of cabinet, fan wheel, cooling coil, condensate pan and drain, heating coils, and return-air grille (if present).
• Inspection of panels and sealing of unit against air leakage. • Cleaning or replacement of filters.
• Testing for cooling/heating system leaks.
• Checking of all electrical connections.

Most unit service can be performed by removing one or both of the unit’s side panels. Coil cleaning, removal or insulation cleaning may require removal of a rear, top, or bottom panel, depending on the unit’s orientation. When service is completed, replace unit panels.

Panels
Panels are fastened to unit frame with sheet metal screws. Fan and coil compartment must be sealed tightly after service to prevent air from bypassing the cooling coil.

Table 15 — Outdoor Unit Maintenance Checklist
MAINTENANCE CHECKLISTa
NOTE(S):
a. The above list may not include all maintenance items. Inspection intervals may vary depending on climate and opening hours. Consult your Carrier dealer about a service contact for seasonal inspections.

RECOMMENDED
INTERVALb
b. Monthly maintenance items and outdoor unit rinsing may be performed by the customer. All other maintenance items and all service work must be performed by a qualified service technician. Read all warning labels.

Outdoor unit specific: Monthly Annual
Clear away debris and vegetation near unit. X
Inspect cabinet for damage. Replace
components that are damaged or severely
rusted.

X
Inspect electrical disconnect for proper
function. Repair or replace as necessary. X
Inspect electrical wiring and connections.

Tighten loose connections. Inspect and
perform functional test of equipment as
needed to ensure proper function. Repair or
replace damaged or overheated components
and wiring.

X
Check refrigerant system subcooling and
superheat. X
Inspect inside of unit. Clean if debris is
present. X
Inspect condenser coil. Clean if dust, dirt, or
debris is present. Rinse unit with fresh
water.c
c. Do not use harsh chemicals or high pressure water on coils. More frequent rinsing is required near a sea coast.

Xd
d. Monthly rinsing of the condenser coil is recommended if the unit is located in a corrosive climate.

Inspect motor and fan for damage. Make
sure fans spin freely. X
Table 16 — Indoor Unit Maintenance Checklist
MAINTENANCE CHECKLISTa
NOTE(S):
a. The above list may not include all maintenance items. Inspection intervals may vary depending on climate and opening hours. Consult your Carrier dealer about a service contact for seasonal inspections.

RECOMMENDED
INTERVALb
b. Monthly maintenance items and outdoor unit rinsing may be performed by the customer. All other maintenance items and all service work must be performed by a qualified service technician. Read all warning labels.

Indoor unit specific: (for accessories
refer to unit specific literature) Monthly Annual
Inspect, clean, or replace air filter if dirty. X
Inspect and clean blower assembly (includes
blower housing, wheel, and motor). X
Inspect internal and external cabinet. Clean
as needed. X
Inspect electrical disconnect for proper
function. Repair or replace as necessary. X
Inspect electrical components, wiring, and
connections. Tighten loose connections.

Repair or replace damaged components and
wiring.

X
Inspect evaporator coil. Clean if dust, dirt, or
debris is present.c
c. Do not use harsh chemicals or high pressure water on coils. More frequent rinsing is required near a sea coast.

X
Clean condensate pan, trap, and drain lines
(more frequent maintenance may be
required in humid climates - consult your
local HVAC dealer).

X
Inspect motor and fan for damage. Inspect
airflow system (ductwork). Check for leaks
and repair as needed.

X

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.

Before performing service or maintenance operations on unit, always turn off main power switch to unit and install lockout tag. Unit may have more than one power switch.
627
Item5.
26 SUPPLY FAN
Supply Fan (Direct-Drive)
All 40RL units have the EcoBlue™ direct drive vane axial fan system. The fan is driven by an ECM motor with speed that is user set through the Unit Control Board (UCB). Speeds are fully configurable from 40% to 100% of motor’s maximum speed. See Fig. 28 and 29.

EVALUATING MOTOR SPEED
The direct drive ECM blower motor uses a constant speed design.

Motor speed is controlled by a 0-10 vdc signal, where 10 vdc is equal to motor’s maximum rpm.

Fig. 28 — Direct-Drive Supply Fan Assembly

SELECTING FAN SPEED
All units come factory-set 8.9 vdc or approximately 89% of the motor's maximum speed. Fan speed should be set per job specification cfm (cubic feet per minute) and ESP (external static pressure) required and per Fan Speed Set Up label mounted on the control box. In some cases, the Fan Speed Set Up label may already include the field setting if unit was previously installed.

Check the box on the lower half of the label to see if the field voltage setting was filled in and if so, set fan speed to that voltage.

Otherwise see detailed instructions below.

NOTE: Fan Speed Set Up is for full load airflow. If the unit has multiple stages of cooling, low cool and ventilation may operate at lower fan rpms. This offset is factory set and controlled by the UCB. If fan speed verification is being done with a strobe, fan speed should be verified in all unit operation modes.

Units with Electromechanical controls
The Fan Speed Set Up controls are located on the lower section of the Unit Control Board (UCB). See Fig. 30 for location.

1. Check the job specifications for the cfm (cubic feet per minute) and ESP (external static pressure) required.

2. Using the chart on the Fan Speed Set Up labels (see
Fig. 31), calculate the vdc from the cfm and ESP for the base unit.

3. If installing any accessories listed at the bottom of the Fan Speed Set Up Label, add accessory vdc to base unit vdc in upper portion of label. For electric heaters use only one adder (ex. 2 stage heater uses only 2 stage adder, not 1 stage plus 2 stage).

NOTE: The Fan Speed Set Up labels are located on the Control Box.

4. Connect a multimeter to the vdc terminals on the UCB.

5. Set the Range Switch to either A, B, or C per the Switch Range table.

6. Using a straight blade screwdriver turn the vdc control dial to fine tune the vdc reading.

7. Record the reading in the Field Setting field.

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.

Before performing service or maintenance operations on
unit, LOCKOUT/TAG-OUT the main power switch to unit.

Electrical shock and rotating equipment could cause severe injury.

CAUTION

UNIT OPERATION HAZARD
Failure to follow this caution could cause equipment damage.

Increasing fan speed produces a greater load on motor.

Do not exceed rated capacity of motor.

Direct Drive
Fan Assembly
628
Item5.
27 Fig. 29 — ECM Motor Plug Connectors
Low Speed Fan Adjustment
2-Pin DIP Switch
The Low Speed 2-Pin DIP switch is located near the center of the UCB. See Fig. 30.

When replacing UCB, the board will be shipped as default without a low speed selected. For all units, set both dip switches to “OFF” (0) for Test and Balance. Set both dip switches to “ON” (1) for normal operation. See Table 17. The dip switch positions can also be found on the unit’s control label diagram.

FAN FAULT DETECTION
The supply fan assembly is equipped with a relay internal to the motor and a manual limit switch installed on the stator. These components work in tandem to prevent the supply fan from running if the there are electrical issues or high temperatures in the supply air section. If the 40RL is connected to the condensing unit correctly (refer to Power Supply and Wiring), the Unit Control Board will also prevent the thermostat signals from being sent to the condensing unit, preventing compressor(s) from energizing if there is a problem with the supply fan.

FREEZE PROTECTION
On select models (40RLAA07 and 40RLAA12), there is a
factory-installed and wired temperature switch (P/N
HH18HB016) to protect the compressor(s) in the condensing unit when frost buildup is present on the indoor coil. The temperature switch is used to prevent the compressor(s) from turning on while the indoor coil is frosted. See Fig. 18 — Unit Wiring Diagram for the wiring of this switch. Fig. 30 — UCB Fan Speed Controls 1 4
7 2
5 8
3 6
9 10 11 12
WHITE CTL Signal Common
BLACK
YELLOW
Power L1
Power L2
BLUE
ORANGE
GRAY Power L3
10vdc Source
0-10vdc Signal
YEL/GRN Earth Ground
RED
VIOLET
Safety Relay
PWM Signal
PINK
RED
Serial (R/T)
Safety Relay
Table 17 — Low Speed 2-Pin DIP Switch Settings
LOW SPEED % OF USER SET
FAN SPEED MODE DIP1 DIP2
0 0 100% Test and Balance
1 1 66% Normal Operation
Fan Speed Set Up Controls
629
Item5.
28 NOTE: Values in the Field Accessories section are VDC adders.

Fig. 31 — Example of Fan Speed Set Up Labels for Electromechanical Controls Factory Setting:

9.0 VDC
Field Setting:

V
Switch Range:

A
B
C
B A C
Field Accessories:

VDC Calculator ESP in. wg CFM

0.2 5.4

5.8 6.1

6.5 6.8

7.2 7.6

7.9 8.3
1500
1625
1750
1875
2000
2125
2250
2375
2500

0.1 0.4

6.2 6.5

6.8 7.1

7.4 7.7

8.0 8.4

8.7 0.1

0.6 6.9

7.1 7.4

7.7 7.9

8.2 8.5

8.8 0.1

0.8 7.5

7.7 8.0

8.2 8.5

8.7 9.0

0.1 1.0

8.1 8.3

8.5 8.7

9.0 0.1

1.2 8.6

8.8 9.0

9.2 0.1

1.4 9.1

9.3 9.5

0.1 1.6 1.8 2.0

9.6 Economizer 0.1
1 Stage E Heat
2 Stage E Heat

UNIT MODEL NUMBER

4.1 - 7.5

6.9 - 8.7

7.7 - 10.0

0.2 0.3

0.2 0.3

0.2 0.3

0.2 0.3

0.2 0.3

0.2 0.3

0.2 0.3

0.2 0.3

9.8 9.9

9.7 9.5 9.9

9.7 10.0

9.2 9.5

9.3 9.8

9.69.2 Record field setting here
*
* Overlap in A, B, C switch range
designed for maximum field
adjustment potential. For example

7.2 can be set at either A or B.
630
Item5.
29 TROUBLESHOOTING THE ECM MOTOR
EcoBlue™ motors are designed with several built-in protections included in the motor software. If the motor detects a fault it will safely shut down. See Table 18 for a complete list.

Troubleshooting the motor requires a voltmeter.

1. Disconnect main power to the unit.

2. Disconnect motor plug in supply section of the unit.

3. Restore main unit power.

4. Check for proper line voltage at motor power leads Black (PL1-1), Yellow (PL1-2), and Blue (PL1-3). See the following table.

5. Disconnect main power.

6. Reconnect motor plug in supply section of unit.

7. Restore main power.

8. Check for proper motor control voltage signal of 9.7 vdc to 10.3 vdc at IFM-1 and IFM-3 on Unit Control Board
(UCB). See Fig. 32.

9. Using a jumper wire from TSTAT CB terminals R to G,
engage motor operation.

10. Verify control signal from user speed selection switch by placing voltmeter taps in provided terminals marked vdc.

Signal should be between 3.8 vdc and 10.3 vdc.

11. If the motor does not start and run, remove the fan assembly and replace the motor with one having the same part number. Do not substitute with an alternate design motor as the voltage/speed programming will not be the same as that on an original factory motor.

Fig. 32 — Supply Fan Control Wiring Diagram
Table 18 — Supply Fan Motor Logic
and Safety Relays

DESCRIPTION START DELAY
No Error —
NTC OverTemperature
Protection
Automatic Reset – Motor starts 12 seconds after the
temperature falls below reset limit.

Phase Fault Automatic Reset – Motor to start after 3 phases present.

Over Current
Protection
Automatic Reset – If motor over-current protection
trips, motor restarts after 20 seconds off time.

If over-current is detected 3 times consecutively, the
motor is off for 3 minutes and restarts. Cycle starts
again after 20 seconds.

Locked Rotor
Protection, Start-up
Automatic Reset – If motor detects locked rotor, it
attempts to restart after 5 seconds.

If motor detects 3 consecutive faults, the motor waits
3 minutes and restarts.

Cycle starts again after 20 seconds.

Locked Rotor
Protection, Running
Over/Under Voltage Automatic Reset – Motor restarts as soon as input voltage is back within ±10%.

Current Sampling
Error
Manual Reset – Power off and wait 2 minutes and
restart motor.

Microelectronic (MCU)
Fault
Automatic Reset – Motor restarts 3 minutes after fault
clears.

Manual Reset – Power off and wait 2 minutes and
restart motor.
40RL UNIT

VOLTAGE MOTOR VOLTAGE MIN-MAX VOLTS
208/230 230 187-253
460 460 360-506
575 575 517-633
631
Item5.
30 Service Access for Supply Fan and Motor

HORIZONTAL APPLICATIONS
Removing the Motor and Fan Assembly
NOTE: Due to press fit design of composite Rotor on Motor, it is highly recommended that any time a motor is replaced the fan rotor is replaced as well. The rest of the assembly may be reused.

1. Unplug motor harness from control box harness. See Fig. 33.

2. Unplug connectors from stator temperature limit switch. See Fig. 33.

3. Remove three screws from each of the quarter round stator retention brackets. See Fig. 34.

4. Slide fan assembly out of the panel opening that is being used. Side panel access will require the assembly to be angled to clear the opening. See Fig. 35.

Fig. 33 — Locations of Motor Harness and Stator
Temperature Limit Switch
Fig. 34 — Quarter Round Stator Retention Brackets
Fig. 35 — Fan Assembly, Side Panel Access
(Side Panel Removed)
Disassembling Motor and Fan Assembly
See Fig. 36 for 2.4 Hp motor units; see Fig. 37 for 3.0 Hp motor units.

1. Remove the four bolts that hold the orifice ring to the stator.

2. Remove the orifice ring from the stator

3. Remove three screws from the top of the fan rotor.

4. Remove the rotor from the motor.

5. Remove the four screws connecting the motor to stator flange.

6. Remove stator from motor.

7. If required, remove stator limit switch on the stator.

Motor Harness
Control Box
Harness
Stator Temperature
Limit Switch
Quarter Round Stator
Retention Brackets
632
Item5.
31 Fig. 36 — Fan Assembly for Units with 2.4 Hp Motor
Fig. 37 — Fan Assembly for Units with 3.0 Hp Motor
1 2
3 4
5 6
7 1
2 3
4 5
6 7
633
Item5.
32 Reassembly of Motor and Fan Assembly

1. See Fig. 36 for 2.4 Hp motor units; see Fig. 37 for 3.0 Hp motor units. Place motor on flat surface.

2. If required, install stator limit switch on the stator with two plastic push rivets (P/N: HH18HA597).

3. Fit motor wire harness into keyhole feature on the side of the stator and pull wire harness out prior to fixing the motor to the stator. See Fig. 38.

Fig. 38 — Stator Keyhole Location

4. The 2.4 Hp motors attach to the stator from the bottom by setting the stator assembly on the motor. The 3.0 Hp motors attach to the stator from the top and are gently lowered into the recess for the motor.

5. For the 2.4 Hp motor, install four 1/4-20 x 1-in. hex head machine screws (P/N: AC67AP170) to connect stator to
motor. Tighten to 50 in.-lb (5.65 Nm).

6. For the 3.0 Hp motor, install six 1/4-20 x 1-in. hex head machine screws (P/N: AC67AP170) to connect stator to
motor. Tighten to 30 in.-lb (3.39 Nm).

7. Install rotor on motor by lining up the rotor holes to the motor holes. The rotor has self-aligning features that engage into the motor holes. Press fan rotor down until it is flush with the motor flange.

8. Install three 1/4-20 x 1-in. hex head machine screws (P/N: AC67AP170) through the holes in the rotor. Tighten to 50 in.-lb (5.65 Nm)

9. Align holes of composite fan inlet casing with screw holes on the top flange of the fan stator. Using a socket extension and either a 1/4-in. or 3/8-in. drive socket, install four #10-16 hex head machine screws (P/N: AP13ADAD128) and tighten to
14 in.-lb (1.58 Nm).

10. Final assembly should have a small clearance between top of plastic rotor and underside of casing lip. Spin rotor by hand to ensure no contact or rubbing between these two parts.

Reinstalling Motor and Fan Assembly

1. Re-install the two lower quarter round retainers

2. Align motor harness/grommet aligned with the control box

3. Drop fan assembly down into fan deck opening and slide it so that the lip is in the fan deck recess and is retained by the quarter round brackets.

4. Install the remaining quarter round brackets.

5. Adjust the orientation of the stator so that it aligns with the embossed recess in the fan deck.

6. Reconnect wires for stator temperature limit switch.

7. Pull motor harness tight through grommet and plug it in to the control box harness and secure in the corner with snap-in wire tie.

VERTICAL APPLICATIONS
Removing the Motor and Fan Assembly
NOTE: Due to press fit design of composite Rotor on Motor, it is highly recommended that any time a motor is replaced the fan rotor is replaced as well. The rest of the assembly may be reused.

See Fig. 36 for 2.4 Hp motor units; see Fig. 37 for 3.0 Hp motor units.

1. Unplug motor harness from control box harness. See Fig. 33.

2. Unplug connectors from stator temperature limit switch. See Fig. 33.

3. Remove six screws from the fan deck. See Fig. 39.

4. Allow the fan deck to drop into the slider tracks (careful not to pinch body parts when the fan drops) See Fig. 40.

5. Slide fan deck assembly out of the panel opening that is being used. Side panel access will not be allowed. See Fig. 41.

6. Remove the quarter round plates to free the fan assembly.

Fig. 39 — Remove Screws from Fan Deck Assembly
Fig. 40 — Lower Fan Deck Assembly to Slider Tracks
Stator Keyhole
Remove Screws
6-Places
Slider Tracks
634
Item5.
33 Fig. 41 — Slide Out Fan Deck Assembly
Disassembling Motor and Fan Assembly
See Fig. 36 for 2.4 Hp motor units; see Fig. 37 for 3.0 Hp motor units.

1. Remove the four bolts that hold the orifice ring to the stator.

2. Remove the orifice ring from the stator.

3. Remove three screws from the top of the fan rotor.

4. Remove rotor from motor.

5. Remove four screws connecting motor to stator flange.

6. Remove stator from motor.

7. If required, remove stator limit switch on the stator.

Reassembly of Motor and Fan Assembly
See Fig. 36 for 2.4 Hp motor units; see Fig. 37 for 3.0 Hp motor units.

1. Place motor on flat surface.

2. If required, install stator limit switch on the stator with two plastic push rivets (P/N: HH18HA597).

3. Fit motor wire harness into keyhole feature on the side of the stator and pull wire harness out prior to fixing the motor to the stator.

4. The 2.4 Hp motors attach to the stator from the bottom by setting the stator assembly on the motor. The 3.0 Hp motors attach to the stator from the top and are gently lowered into the recess for the motor.

5. For the 2.4 Hp motor, install four 1/4-20 x 1-in. hex head machine screws (P/N: AC67AP170) to connect stator to
motor. Tighten to 50 in.-lb (5.65 Nm).

6. For the 3.0 Hp motor, install six 1/4-20 x 1-in. hex head machine screws (P/N: AC67AP170) to connect stator to
motor. Tighten to 30 in.-lb (3.39 Nm).

7. Install rotor on motor by lining up the rotor holes to the motor holes. The rotor has self-aligning features that engage into the motor holes. Press fan rotor down until it is flush with the motor flange.

8. Install three 1/4-20 x 1-in. hex head machine screws (P/N: AC67AP170) through the holes in the rotor. Tighten to 50 in.-lb (5.65 Nm)

9. Align holes of composite fan inlet casing with screw wells on the top flange of the fan stator.

10. Final assembly should have a small clearance between top of plastic rotor and underside of casing lip. Spin rotor by hand to ensure no contact or rubbing between these two
parts. Insert four screws (P/N: AP13AD128) and tighten to 14 in.-lb (1.58 Nm).

Reinstalling Motor and Fan Assembly

1. Reassemble the motor assembly to the fan deck.

2. Reinstall the quarter round plates and tighten the screws.

3. Align motor harness/grommet aligned with the control box.

4. Slide the fan deck back into the unit assembly.

5. Re-install the six retainer screws.

6. Reconnect wires for stator temperature limit switch.

7. Pull motor harness tight through grommet and plug it in to the control box harness and secure in the corner with snap-in wire tie.

Condensate Drains
Keep condensate drains free of dirt and foreign matter.

Return-Air Filters
Refer to Replacing Filters section on page 34 for filter accessibility and removal. Replace with clean filters of the sizes listed in Tables 1-3.

Chilled Water Coil Freeze Protection
Shut off water supply to unit. Remove side panel of unit and remove vent and drain plugs in top and bottom of coil header.

Drain coil and blow out remaining water. Reinstall plugs and side panel. Alternative freeze protection methods follow:
• Circulate hot water within the water coil’s supply main or supplementary space heating.
• Close off supply lines to unit and open a union or fieldsupplied drain valve in the return line. • After draining as much water as possible from coils, add sufficient antifreeze to prevent residual water in the coil from freezing.
• Add a sufficient quantity of non-corrosive antifreeze to the entire system to prevent all water within the system from freezing.

Coil Removal
Remove unit panels and corner posts as required. Disconnect coil connections and remove fastening screws. Remove coil through end or side sections of unit.

Cleaning Cooling Coil
Remove return-air filters. Remove any heavy dirt that may have accumulated on underside of coil. Coil can be cleaned more easily with a stiff brush, vacuum cleaner, or compressed air when coil is dry. If coil is wet or if water is to be used for cleaning, guard against splashing water on electrical components or damaging surrounding area. Clean coil baffles as applicable and check for tight fit to be sure air does not bypass coil.

IMPORTANT: Draining from return line will not completely drain water from coils.
635
Item5.
34 Cleaning Insulation
The insulation contains an immobilized antimicrobial agent that helps inhibit the growth of bacteria and fungi. Clean the inner surface of the insulation according to the separate maintenance instructions shipped with the unit.

Replacing Filters
Filters can be removed and installed from either side of the unit.

Install new filters in units that have one fan as follows:

1. Remove the side access panel (retain screws).

2. Remove the filter retainer clip (see Fig. 42).

3. Remove old filters by lifting and tilting them out of the filter track. (See Fig. 14 and 43.)

4. Reverse the procedure to install new filters.

To install new filters in larger units that have 2 fans, follow the preceding steps, but use the factory-supplied filter hook to slide filters within reach for removal. The filter hook is shipped inside the unit in the filter track.

Fig. 42 — Remove Filter Retainer Clip
Fig. 43 — Filter Removal/Replacement

FAN PERFORMANCE
General Fan Performance Notes
See Tables 19-45 for fan performance data.

1. Interpolation is permissible. Do not extrapolate.

2. External static pressure is the static pressure difference between the return duct and the supply duct plus the static pressure caused by any FIOPs or accessories.

3. Tabular data accounts for pressure loss due to clean filters, unit casing and wet coils.

4. Factory options and accessories may effect static pressure losses. Selection software is available, through your salesperson, to help you select the best motor/drive combination for your application.

5. The fan performance tables (see Tables 19-45) offer motor/ drive recommendations. In cases when two motor/drive combinations would work, Carrier recommends the lower horsepower option.

6. The EPACT (Energy Policy Act of 1992) regulates energy requirements for specific types of indoor fan motors.

Motors regulated by EPACT include any general purpose,
T-frame (three-digit, 143 and larger), single-speed, foot mounted, polyphase, squirrel cage induction motors of
NEMA (National Electrical Manufacturers Association)
design A and B, manufactured for use in the United States.

Ranging from 1 to 200 Hp, these continuous-duty motors
operate on 230 and 460 volt, 60 Hz power. If a motor does not fit into these specifications, the motor does not have to be replaced by an EPACT compliant energy-efficient motor.

Variable-speed motors are exempt from EPACT compliance
requirements.

CAUTION

EQUIPMENT DAMAGE HAZARD
Failure to follow this CAUTION can result in premature wear and damage to equipment.

DO NOT OPERATE THE UNIT WITHOUT THE RETURN
AIR FILTERS IN PLACE.

Dirt and debris can collect on heat exchangers and coils possibly resulting in a small fire. Dirt buildup on components can cause excessive current used resulting in motor failure.

Slide
Filter
Retainer
Clip
636
Item5.
35 Table 19 — 40RLAA07 Fan Data (rpm - bhp)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
1800 788 0.18 942 0.31 1081 0.48 1202 0.67 1308 0.88
1950 828 0.20 973 0.34 1107 0.52 1227 0.71 1333 0.92
2100 870 0.23 1005 0.37 1134 0.55 1252 0.75 1358 0.97
2250 914 0.26 1040 0.41 1163 0.59 1278 0.80 1383 1.02
2400 958 0.30 1077 0.45 1194 0.63 1305 0.84 1409 1.07
2550 1004 0.34 1115 0.50 1226 0.68 1334 0.89 1435 1.13
2700 1050 0.39 1155 0.55 1261 0.74 1364 0.95 1462 1.18
2850 1097 0.44 1197 0.60 1297 0.79 1395 1.01 1491 1.25
3000 1144 0.50 1239 0.66 1334 0.86 1429 1.08 1521 1.32
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
1800 1403 1.09 1491 1.32 1571 1.55 1647 1.79 1718 2.04
1950 1429 1.14 1517 1.38 1598 1.62 1674 1.87 1745 2.13
2100 1454 1.20 1542 1.44 1624 1.69 1700 1.95 1772 2.21
2250 1479 1.25 1568 1.50 1650 1.76 1726 2.02 1799 2.30
2400 1504 1.31 1593 1.57 1675 1.83 1752 2.11 1825 2.39
2550 1529 1.37 1618 1.64 1700 1.91 1777 2.19 1850 2.48
2700 1555 1.44 1643 1.70 1725 1.98 1802 2.27 1875 2.57
2850 1582 1.50 1668 1.78 1750 2.06 1827 2.36 1900 2.66
3000 1610 1.58 1695 1.86 1775 2.14 1852 2.45 1925 2.76
Medium Static 788-1695 rpm, 1.86 Max bhp
High Static 788-1925 rpm, 2.76 Max bhp
Table 20 — 40RLAA07 Medium Static Fan Data (rpm - vdc)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
1800 788 3.8 942 4.6 1081 5.3 1202 5.9 1308 6.4
1950 828 4.0 973 4.7 1107 5.4 1227 6.0 1333 6.6
2100 870 4.2 1005 4.9 1134 5.5 1252 6.2 1358 6.7
2250 914 4.4 1040 5.1 1163 5.7 1278 6.3 1383 6.8
2400 958 4.6 1077 5.3 1194 5.9 1305 6.4 1409 7.0
2550 1004 4.9 1115 5.4 1226 6.0 1334 6.6 1435 7.1
2700 1050 5.1 1155 5.7 1261 6.2 1364 6.7 1462 7.2
2850 1097 5.4 1197 5.9 1297 6.4 1395 6.9 1491 7.4
3000 1144 5.6 1239 6.1 1334 6.6 1429 7.1 1521 7.5
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
1800 1403 6.9 1491 7.4— — — — — —
1950 1429 7.1 1517 7.5— — — — — —
2100 1454 7.2 1542 7.6— — — — — —
2250 1479 7.3 1568 7.8— — — — — —
2400 1504 7.4 1593 7.9— — — — — —
2550 1529 7.6 1618 8.0— — — — — —
2700 1555 7.7 1643 8.2— — — — — —
2850 1582 7.9 1668 8.3— — — — — —
3000 1610 8.0 1695 8.4— — — — — —
Medium Static 788-1695 rpm
637
Item5.
36 Table 21 — 40RLAA07 High Static Fan Data (rpm - vdc) CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
1800 788 3.5 942 4.2 1081 4.8 1202 5.4 1308 5.9
1950 828 3.7 973 4.3 1107 5.0 1227 5.5 1333 6.0
2100 870 3.9 1005 4.5 1134 5.1 1252 5.6 1358 6.1
2250 914 4.1 1040 4.6 1163 5.2 1278 5.7 1383 6.2
2400 958 4.3 1077 4.8 1194 5.4 1305 5.9 1409 6.3
2550 1004 4.5 1115 5.0 1226 5.5 1334 6.0 1435 6.5
2700 1050 4.7 1155 5.2 1261 5.7 1364 6.1 1462 6.6
2850 1097 4.9 1197 5.4 1297 5.8 1395 6.3 1491 6.7
3000 1144 5.1 1239 5.6 1334 6.0 1429 6.4 1521 6.9
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
1800 1403 6.3 1491 6.7 1571 7.1 1647 7.4 1718 7.8
1950 1429 6.4 1517 6.8 1598 7.2 1674 7.6 1745 7.9
2100 1454 6.6 1542 7.0 1624 7.3 1700 7.7 1772 8.0
2250 1479 6.7 1568 7.1 1650 7.5 1726 7.8 1799 8.1
2400 1504 6.8 1593 7.2 1675 7.6 1752 7.9 1825 8.3
2550 1529 6.9 1618 7.3 1700 7.7 1777 8.0 1850 8.4
2700 1555 7.0 1643 7.4 1725 7.8 1802 8.2 1875 8.5
2850 1582 7.1 1668 7.5 1750 7.9 1827 8.3 1900 8.6
3000 1610 7.3 1695 7.7 1775 8.0 1852 8.4 1925 8.7
High Static 788-1925 rpm
638
Item5.
37 Table 22 — 40RLAA08 Fan Data (rpm - bhp)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
2250 884 0.23 1009 0.37 1131 0.54 1247 0.74 1354 0.95
2440 937 0.27 1053 0.42 1168 0.59 1279 0.79 1383 1.01
2625 991 0.32 1099 0.47 1206 0.64 1311 0.84 1412 1.07
2815 1048 0.37 1149 0.53 1249 0.70 1348 0.90 1445 1.13
3000 1103 0.43 1199 0.59 1293 0.77 1386 0.97 1478 1.20
3190 1161 0.50 1252 0.66 1340 0.85 1428 1.05 1516 1.28
3375 1218 0.57 1304 0.74 1388 0.93 1471 1.14 1554 1.37
3565 1277 0.66 1359 0.83 1438 1.02 1517 1.24 1596 1.47
3750 1335 0.75 1413 0.93 1489 1.13 1564 1.34 1639 1.58
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
2250 1452 1.18 1542 1.43 1625 1.68 1703 1.94 1776 2.21
2440 1480 1.25 1570 1.50 1653 1.76 1731 2.03 1805 2.31
2625 1507 1.31 1597 1.57 1680 1.83 1759 2.11 1833 2.40
2815 1537 1.38 1625 1.64 1708 1.91 1787 2.20 1861 2.50
3000 1568 1.45 1654 1.72 1736 2.00 1814 2.29 1888 2.60
3190 1602 1.54 1685 1.80 1765 2.09 1842 2.39 1916 2.70
3375 1636 1.62 1717 1.90 1795 2.18 1871 2.49 1944 2.81
3565 1675 1.73 1752 2.00 1828 2.29 1902 2.60 1973 2.92
3750 1714 1.83 1788 2.11 1862 2.41 1933 2.71 2003 3.04
Medium Static 884-1788 rpm, 1.84 Max bhp High Static 884-2003 rpm, 2.70 Max bhp Table 23 — 40RLAA08 Medium Static Fan Data (rpm - vdc)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
2250 884 4.3 1009 4.9 1131 5.5 1247 6.1 1354 6.7
2440 937 4.5 1053 5.1 1168 5.7 1279 6.3 1383 6.8
2625 991 4.8 1099 5.4 1206 5.9 1311 6.5 1412 7.0
2815 1048 5.1 1149 5.6 1249 6.1 1348 6.6 1445 7.1
3000 1103 5.4 1199 5.9 1293 6.4 1386 6.8 1478 7.3
3190 1161 5.7 1252 6.2 1340 6.6 1428 7.1 1516 7.5
3375 1218 6.0 1304 6.4 1388 6.9 1471 7.3 1554 7.7
3565 1277 6.3 1359 6.7 1438 7.1 1517 7.5 1596 7.9
3750 1335 6.6 1413 7.0 1489 7.4 1564 7.8 1639 8.1
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
2250 1452 7.2 1542 7.6— — — — — —
2440 1480 7.3 1570 7.8— — — — — —
2625 1507 7.5 1597 7.9— — — — — —
2815 1537 7.6 1625 8.1— — — — — —
3000 1568 7.8 1654 8.2— — — — — —
3190 1602 8.0 1685 8.4— — — — — —
3375 1636 8.1 1717 8.5— — — — — —
3565 1675 8.3 1752 8.7— — — — — —
3750 1714 8.5 1788 8.9— — — — — —
Medium Static 884-1788 rpm
639
Item5.
38 Table 24 — 40RLAA08 High Static Fan Data (rpm - vdc) CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
2250 884 3.9 1009 4.5 1131 5.1 1247 5.6 1354 6.1
2440 937 4.2 1053 4.7 1168 5.2 1279 5.7 1383 6.2
2625 991 4.4 1099 4.9 1206 5.4 1311 5.9 1412 6.4
2815 1048 4.7 1149 5.1 1249 5.6 1348 6.1 1445 6.5
3000 1103 4.9 1199 5.4 1293 5.8 1386 6.2 1478 6.7
3190 1161 5.2 1252 5.6 1340 6.0 1428 6.4 1516 6.8
3375 1218 5.5 1304 5.9 1388 6.3 1471 6.6 1554 7.0
3565 1277 5.7 1359 6.1 1438 6.5 1517 6.8 1596 7.2
3750 1335 6.0 1413 6.4 1489 6.7 1564 7.1 1639 7.4
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
2250 1452 6.5 1542 7.0 1625 7.3 1703 7.7 1776 8.0
2440 1480 6.7 1570 7.1 1653 7.5 1731 7.8 1805 8.2
2625 1507 6.8 1597 7.2 1680 7.6 1759 8.0 1833 8.3
2815 1537 6.9 1625 7.3 1708 7.7 1787 8.1 1861 8.4
3000 1568 7.1 1654 7.5 1736 7.9 1814 8.2 1888 8.6
3190 1602 7.2 1685 7.6 1765 8.0 1842 8.3 1916 8.7
3375 1636 7.4 1717 7.8 1795 8.1 1871 8.5 1944 8.8
3565 1675 7.6 1752 7.9 1828 8.3 1902 8.6 1973 9.0
3750 1714 7.8 1788 8.1 1862 8.4 1933 8.8 2003 9.1
High Static 884-2003 rpm
640
Item5.
39 Table 25 — 40RLAA12 Fan Data (rpm - bhp)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3000 1080 0.40 1175 0.55 1268 0.72 1361 0.92 1453 1.14
3250 1154 0.48 1243 0.64 1329 0.81 1415 1.01 1501 1.24
3500 1229 0.57 1312 0.74 1393 0.92 1473 1.13 1553 1.35
3750 1305 0.68 1384 0.86 1459 1.04 1534 1.25 1609 1.48
4000 1381 0.80 1456 0.99 1527 1.18 1598 1.40 1668 1.63
4250 1458 0.94 1529 1.13 1597 1.34 1664 1.56 1730 1.79
4500 1535 1.09 1603 1.29 1668 1.50 1731 1.73 1794 1.97
4750 1613 1.26 1678 1.47 1740 1.69 1800 1.92 1860 2.17
5000 1691 1.45 1753 1.67 1813 1.90 1870 2.14 1927 2.39
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3000 1543 1.38 1629 1.64 1712 1.91 1791 2.20 1866 2.50
3250 1586 1.48 1668 1.74 1748 2.02 1825 2.31 1899 2.62
3500 1632 1.59 1711 1.86 1787 2.14 1862 2.44 1935 2.75
3750 1683 1.73 1757 1.99 1830 2.28 1902 2.58 1972 2.89
4000 1738 1.88 1807 2.14 1877 2.43 1945 2.73 2013 3.05
4250 1795 2.04 1861 2.31 1927 2.60 1992 2.90 ——
4500 1856 2.23 1918 2.50 1980 2.79 2042 3.09 ——
4750 1919 2.43 1977 2.71 2036 3.00 ————
5000 1983 2.66 2039 2.94 ——————
Medium Static 1080-1918 rpm, 2.50 Max bhp
High Static 1080-2013 rpm, 3.09 Max bhp
Table 26 — 40RLAA12 Medium Static Fan Data (rpm - vdc)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
3000 1080 5.3 1175 5.8 1268 6.2 1361 6.7 1453 7.2
3250 1154 5.6 1243 6.1 1329 6.5 1415 7.0 1501 7.4
3500 1229 6.0 1312 6.5 1393 6.9 1473 7.3 1553 7.7
3750 1305 6.4 1384 6.8 1459 7.2 1534 7.6 1609 8.0
4000 1381 6.8 1456 7.2 1527 7.6 1598 7.9 1668 8.3
4250 1458 7.2 1529 7.6 1597 7.9 1664 8.3 1730 8.6
4500 1535 7.6 1603 8.0 1668 8.3 1731 8.6 1794 8.9
4750 1613 8.0 1678 8.3 1740 8.7 1800 9.0 1860 9.3
5000 1691 8.4 1753 8.7 1813 9.0 1870 9.3 1927 9.6
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
3000 1543 7.6 1629 8.1— — — — — —
3250 1586 7.9 1668 8.3— — — — — —
3500 1632 8.1 1711 8.5— — — — — —
3750 1683 8.4 1757 8.8— — — — — —
4000 1738 8.7 1807 9.0— — — — — —
4250 1795 8.9 1861 9.3— — — — — —
4500 1856 9.3 1918 9.6— — — — — —
4750 1919 9.6— — — — — — — —
5000 ——————————
Medium Static 1080-1918 rpm
641
Item5.
40 Table 27 — 40RLAA12 High Static Fan Data (rpm - vdc) CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
3000 1080 4.8 1175 5.3 1268 5.7 1361 6.1 1453 6.6
3250 1154 5.2 1243 5.6 1329 6.0 1415 6.4 1501 6.8
3500 1229 5.5 1312 5.9 1393 6.3 1473 6.6 1553 7.0
3750 1305 5.9 1384 6.2 1459 6.6 1534 6.9 1609 7.3
4000 1381 6.2 1456 6.6 1527 6.9 1598 7.2 1668 7.5
4250 1458 6.6 1529 6.9 1597 7.2 1664 7.5 1730 7.8
4500 1535 6.9 1603 7.2 1668 7.5 1731 7.8 1794 8.1
4750 1613 7.3 1678 7.6 1740 7.9 1800 8.2 1860 8.4
5000 1691 7.7 1753 7.9 1813 8.2 1870 8.5 1927 8.7
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
3000 1543 7.0 1629 7.4 1712 7.7 1791 8.1 1866 8.5
3250 1586 7.2 1668 7.5 1748 7.9 1825 8.3 1899 8.6
3500 1632 7.4 1711 7.7 1787 8.1 1862 8.4 1935 8.8
3750 1683 7.6 1757 8.0 1830 8.3 1902 8.6 1972 8.9
4000 1738 7.9 1807 8.2 1877 8.5 1945 8.8 2013 9.1
4250 1795 8.1 1861 8.4 1927 8.7 1992 9.0 ——
4500 1856 8.4 1918 8.7 1980 9.0 2042 9.3 ——
4750 1919 8.7 1977 9.0 2036 9.2 ————
5000 1983 9.0 2039 9.3 ——————
High Static 1080-2013 rpm
642
Item5.
41 Table 28 — 40RLQA07 Fan Data (rpm - bhp)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
1800 788 0.18 942 0.31 1081 0.48 1202 0.67 1308 0.88
1950 828 0.20 973 0.34 1107 0.52 1227 0.71 1333 0.92
2100 870 0.23 1005 0.37 1134 0.55 1252 0.75 1358 0.97
2250 914 0.26 1040 0.41 1163 0.59 1278 0.80 1383 1.02
2400 958 0.30 1077 0.45 1194 0.63 1305 0.84 1409 1.07
2550 1004 0.34 1115 0.50 1226 0.68 1334 0.89 1435 1.13
2700 1050 0.39 1155 0.55 1261 0.74 1364 0.95 1462 1.18
2850 1097 0.44 1197 0.60 1297 0.79 1395 1.01 1491 1.25
3000 1144 0.50 1239 0.66 1334 0.86 1429 1.08 1521 1.32
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
1800 1403 1.09 1491 1.32 1571 1.55 1647 1.79 1718 2.04
1950 1429 1.14 1517 1.38 1598 1.62 1674 1.87 1745 2.13
2100 1454 1.20 1542 1.44 1624 1.69 1700 1.95 1772 2.21
2250 1479 1.25 1568 1.50 1650 1.76 1726 2.02 1799 2.30
2400 1504 1.31 1593 1.57 1675 1.83 1752 2.11 1825 2.39
2550 1529 1.37 1618 1.64 1700 1.91 1777 2.19 1850 2.48
2700 1555 1.44 1643 1.70 1725 1.98 1802 2.27 1875 2.57
2850 1582 1.50 1668 1.78 1750 2.06 1827 2.36 1900 2.66
3000 1610 1.58 1695 1.86 1775 2.14 1852 2.45 1925 2.76
Medium Static 788-1695 rpm, 1.86 Max bhp High Static 788-1925 rpm, 2.76 Max bhp Table 29 — 40RLQA07 Medium Static Fan Data (rpm - vdc)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
1800 788 3.8 942 4.6 1081 5.3 1202 5.9 1308 6.4
1950 828 4.0 973 4.7 1107 5.4 1227 6.0 1333 6.6
2100 870 4.2 1005 4.9 1134 5.5 1252 6.2 1358 6.7
2250 914 4.4 1040 5.1 1163 5.7 1278 6.3 1383 6.8
2400 958 4.6 1077 5.3 1194 5.9 1305 6.4 1409 7.0
2550 1004 4.9 1115 5.4 1226 6.0 1334 6.6 1435 7.1
2700 1050 5.1 1155 5.7 1261 6.2 1364 6.7 1462 7.2
2850 1097 5.4 1197 5.9 1297 6.4 1395 6.9 1491 7.4
3000 1144 5.6 1239 6.1 1334 6.6 1429 7.1 1521 7.5
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
1800 1403 6.9 1491 7.4— — — — — —
1950 1429 7.1 1517 7.5— — — — — —
2100 1454 7.2 1542 7.6— — — — — —
2250 1479 7.3 1568 7.8— — — — — —
2400 1504 7.4 1593 7.9— — — — — —
2550 1529 7.6 1618 8.0— — — — — —
2700 1555 7.7 1643 8.2— — — — — —
2850 1582 7.9 1668 8.3— — — — — —
3000 1610 8.0 1695 8.4— — — — — —
Medium Static 788-1695 rpm
643
Item5.
42 Table 30 — 40RLQA07 High Static Fan Data (rpm - vdc) CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
1800 788 3.5 942 4.2 1081 4.8 1202 5.4 1308 5.9
1950 828 3.7 973 4.3 1107 5.0 1227 5.5 1333 6.0
2100 870 3.9 1005 4.5 1134 5.1 1252 5.6 1358 6.1
2250 914 4.1 1040 4.6 1163 5.2 1278 5.7 1383 6.2
2400 958 4.3 1077 4.8 1194 5.4 1305 5.9 1409 6.3
2550 1004 4.5 1115 5.0 1226 5.5 1334 6.0 1435 6.5
2700 1050 4.7 1155 5.2 1261 5.7 1364 6.1 1462 6.6
2850 1097 4.9 1197 5.4 1297 5.8 1395 6.3 1491 6.7
3000 1144 5.1 1239 5.6 1334 6.0 1429 6.4 1521 6.9
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
1800 1403 6.3 1491 6.7 1571 7.1 1647 7.4 1718 7.8
1950 1429 6.4 1517 6.8 1598 7.2 1674 7.6 1745 7.9
2100 1454 6.6 1542 7.0 1624 7.3 1700 7.7 1772 8.0
2250 1479 6.7 1568 7.1 1650 7.5 1726 7.8 1799 8.1
2400 1504 6.8 1593 7.2 1675 7.6 1752 7.9 1825 8.3
2550 1529 6.9 1618 7.3 1700 7.7 1777 8.0 1850 8.4
2700 1555 7.0 1643 7.4 1725 7.8 1802 8.2 1875 8.5
2850 1582 7.1 1668 7.5 1750 7.9 1827 8.3 1900 8.6
3000 1610 7.3 1695 7.7 1775 8.0 1852 8.4 1925 8.7
High Static 788-1925 rpm
644
Item5.
43 Table 31 — 40RLQA08 Fan Data (rpm - bhp)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
2250 884 0.23 1009 0.37 1131 0.54 1247 0.74 1354 0.95
2440 937 0.27 1053 0.42 1168 0.59 1279 0.79 1383 1.01
2625 991 0.32 1099 0.47 1206 0.64 1311 0.84 1412 1.07
2815 1048 0.37 1149 0.53 1249 0.70 1348 0.90 1445 1.13
3000 1103 0.43 1199 0.59 1293 0.77 1386 0.97 1478 1.20
3190 1161 0.50 1252 0.66 1340 0.85 1428 1.05 1516 1.28
3375 1218 0.57 1304 0.74 1388 0.93 1471 1.14 1554 1.37
3565 1277 0.66 1359 0.83 1438 1.02 1517 1.24 1596 1.47
3750 1335 0.75 1413 0.93 1489 1.13 1564 1.34 1639 1.58
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
2250 1452 1.18 1542 1.43 1625 1.68 1703 1.94 1776 2.21
2440 1480 1.25 1570 1.50 1653 1.76 1731 2.03 1805 2.31
2625 1507 1.31 1597 1.57 1680 1.83 1759 2.11 1833 2.40
2815 1537 1.38 1625 1.64 1708 1.91 1787 2.20 1861 2.50
3000 1568 1.45 1654 1.72 1736 2.00 1814 2.29 1888 2.60
3190 1602 1.54 1685 1.80 1765 2.09 1842 2.39 1916 2.70
3375 1636 1.62 1717 1.90 1795 2.18 1871 2.49 1944 2.81
3565 1675 1.73 1752 2.00 1828 2.29 1902 2.60 1973 2.92
3750 1714 1.83 1788 2.11 1862 2.41 1933 2.71 2003 3.04
Medium Static 884-1788 rpm, 2.11 Max bhp
High Static 884-2003 rpm, 3.04 Max bhp
Table 32 — 40RLQA08 Medium Static Fan Data (rpm - vdc)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
2250 884 4.3 1009 4.9 1131 5.5 1247 6.1 1354 6.7
2440 937 4.5 1053 5.1 1168 5.7 1279 6.3 1383 6.8
2625 991 4.8 1099 5.4 1206 5.9 1311 6.5 1412 7.0
2815 1048 5.1 1149 5.6 1249 6.1 1348 6.6 1445 7.1
3000 1103 5.4 1199 5.9 1293 6.4 1386 6.8 1478 7.3
3190 1161 5.7 1252 6.2 1340 6.6 1428 7.1 1516 7.5
3375 1218 6.0 1304 6.4 1388 6.9 1471 7.3 1554 7.7
3565 1277 6.3 1359 6.7 1438 7.1 1517 7.5 1596 7.9
3750 1335 6.6 1413 7.0 1489 7.4 1564 7.8 1639 8.1
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
2250 1452 7.2 1542 7.6— — — — — —
2440 1480 7.3 1570 7.8— — — — — —
2625 1507 7.5 1597 7.9— — — — — —
2815 1537 7.6 1625 8.1— — — — — —
3000 1568 7.8 1654 8.2— — — — — —
3190 1602 8.0 1685 8.4— — — — — —
3375 1636 8.1 1717 8.5— — — — — —
3565 1675 8.3 1752 8.7— — — — — —
3750 1714 8.5 1788 8.9— — — — — —
Medium Static 884-1788 rpm
645
Item5.
44 Table 33 — 40RLQA08 High Static Fan Data (rpm - vdc) CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
2250 884 3.9 1009 4.5 1131 5.1 1247 5.6 1354 6.1
2440 937 4.2 1053 4.7 1168 5.2 1279 5.7 1383 6.2
2625 991 4.4 1099 4.9 1206 5.4 1311 5.9 1412 6.4
2815 1048 4.7 1149 5.1 1249 5.6 1348 6.1 1445 6.5
3000 1103 4.9 1199 5.4 1293 5.8 1386 6.2 1478 6.7
3190 1161 5.2 1252 5.6 1340 6.0 1428 6.4 1516 6.8
3375 1218 5.5 1304 5.9 1388 6.3 1471 6.6 1554 7.0
3565 1277 5.7 1359 6.1 1438 6.5 1517 6.8 1596 7.2
3750 1335 6.0 1413 6.4 1489 6.7 1564 7.1 1639 7.4
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
2250 1452 6.5 1542 7.0 1625 7.3 1703 7.7 1776 8.0
2440 1480 6.7 1570 7.1 1653 7.5 1731 7.8 1805 8.2
2625 1507 6.8 1597 7.2 1680 7.6 1759 8.0 1833 8.3
2815 1537 6.9 1625 7.3 1708 7.7 1787 8.1 1861 8.4
3000 1568 7.1 1654 7.5 1736 7.9 1814 8.2 1888 8.6
3190 1602 7.2 1685 7.6 1765 8.0 1842 8.3 1916 8.7
3375 1636 7.4 1717 7.8 1795 8.1 1871 8.5 1944 8.8
3565 1675 7.6 1752 7.9 1828 8.3 1902 8.6 1973 9.0
3750 1714 7.8 1788 8.1 1862 8.4 1933 8.8 2003 9.1
High Static 884-2003 rpm
646
Item5.
45 Table 34 — 40RLQA12 Fan Data (rpm - bhp)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3000 1080 0.40 1175 0.55 1268 0.72 1361 0.92 1453 1.14
3250 1154 0.48 1243 0.64 1329 0.81 1415 1.01 1501 1.24
3500 1229 0.57 1312 0.74 1393 0.92 1473 1.13 1553 1.35
3750 1305 0.68 1384 0.86 1459 1.04 1534 1.25 1609 1.48
4000 1381 0.80 1456 0.99 1527 1.18 1598 1.40 1668 1.63
4250 1458 0.94 1529 1.13 1597 1.34 1664 1.56 1730 1.79
4500 1535 1.09 1603 1.29 1668 1.50 1731 1.73 1794 1.97
4750 1613 1.26 1678 1.47 1740 1.69 1800 1.92 1860 2.17
5000 1691 1.45 1753 1.67 1813 1.90 1870 2.14 1927 2.39
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3000 1543 1.38 1629 1.64 1712 1.91 1791 2.20 1866 2.50
3250 1586 1.48 1668 1.74 1748 2.02 1825 2.31 1899 2.62
3500 1632 1.59 1711 1.86 1787 2.14 1862 2.44 1935 2.75
3750 1683 1.73 1757 1.99 1830 2.28 1902 2.58 1972 2.89
4000 1738 1.88 1807 2.14 1877 2.43 1945 2.73 2013 3.05
4250 1795 2.04 1861 2.31 1927 2.60 1992 2.90 ——
4500 1856 2.23 1918 2.50 1980 2.79 2042 3.09 ——
4750 1919 2.43 1977 2.71 2036 3.00 ————
5000 1983 2.66 2039 2.94 ——————
Medium Static 1080-1918 rpm, 2.50 Max bhp High Static 1080-2013 rpm, 3.05 Max bhp Table 35 — 40RLQA12 Medium Static Fan Data (rpm - vdc)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
3000 1080 5.3 1175 5.8 1268 6.2 1361 6.7 1453 7.2
3250 1154 5.6 1243 6.1 1329 6.5 1415 7.0 1501 7.4
3500 1229 6.0 1312 6.5 1393 6.9 1473 7.3 1553 7.7
3750 1305 6.4 1384 6.8 1459 7.2 1534 7.6 1609 8.0
4000 1381 6.8 1456 7.2 1527 7.6 1598 7.9 1668 8.3
4250 1458 7.2 1529 7.6 1597 7.9 1664 8.3 1730 8.6
4500 1535 7.6 1603 8.0 1668 8.3 1731 8.6 1794 8.9
4750 1613 8.0 1678 8.3 1740 8.7 1800 9.0 1860 9.3
5000 1691 8.4 1753 8.7 1813 9.0 1870 9.3 1927 9.6
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
3000 1543 7.6 1629 8.1— — — — — —
3250 1586 7.9 1668 8.3— — — — — —
3500 1632 8.1 1711 8.5— — — — — —
3750 1683 8.4 1757 8.8— — — — — —
4000 1738 8.7 1807 9.0— — — — — —
4250 1795 8.9 1861 9.3— — — — — —
4500 1856 9.3 1918 9.6— — — — — —
4750 1919 9.6— — — — — — — —
5000 ——————————
Medium Static 1080-1918 rpm
647
Item5.
46 Table 36 — 40RLQA12 High Static Fan Data (rpm - vdc) CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
3000 1080 4.8 1175 5.3 1268 5.7 1361 6.1 1453 6.6
3250 1154 5.2 1243 5.6 1329 6.0 1415 6.4 1501 6.8
3500 1229 5.5 1312 5.9 1393 6.3 1473 6.6 1553 7.0
3750 1305 5.9 1384 6.2 1459 6.6 1534 6.9 1609 7.3
4000 1381 6.2 1456 6.6 1527 6.9 1598 7.2 1668 7.5
4250 1458 6.6 1529 6.9 1597 7.2 1664 7.5 1730 7.8
4500 1535 6.9 1603 7.2 1668 7.5 1731 7.8 1794 8.1
4750 1613 7.3 1678 7.6 1740 7.9 1800 8.2 1860 8.4
5000 1691 7.7 1753 7.9 1813 8.2 1870 8.5 1927 8.7
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
3000 1543 7.0 1629 7.4 1712 7.7 1791 8.1 1866 8.5
3250 1586 7.2 1668 7.5 1748 7.9 1825 8.3 1899 8.6
3500 1632 7.4 1711 7.7 1787 8.1 1862 8.4 1935 8.8
3750 1683 7.6 1757 8.0 1830 8.3 1902 8.6 1972 8.9
4000 1738 7.9 1807 8.2 1877 8.5 1945 8.8 2013 9.1
4250 1795 8.1 1861 8.4 1927 8.7 1992 9.0 ——
4500 1856 8.4 1918 8.7 1980 9.0 2042 9.3 ——
4750 1919 8.7 1977 9.0 2036 9.2 ————
5000 1983 9.0 2039 9.3 ——————
High Static 1080-2013 rpm
648
Item5.
47 Table 37 — 40RLSA08 Fan Data (rpm - bhp)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
2250 850 0.20 975 0.33 1096 0.49 1210 0.67 1315 0.87
2440 900 0.24 1017 0.37 1130 0.53 1239 0.71 1342 0.92
2625 951 0.27 1060 0.41 1167 0.57 1270 0.76 1369 0.97
2815 1004 0.32 1107 0.46 1207 0.62 1305 0.81 1400 1.02
3000 1056 0.37 1154 0.51 1248 0.68 1341 0.87 1432 1.08
3190 1111 0.42 1203 0.57 1292 0.74 1380 0.94 1467 1.15
3375 1165 0.48 1253 0.64 1337 0.81 1421 1.01 1503 1.23
3565 1221 0.55 1304 0.71 1385 0.89 1464 1.09 1543 1.31
3750 1275 0.62 1355 0.79 1432 0.97 1508 1.18 1583 1.40
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
2250 1412 1.09 1503 1.32 1587 1.56 1666 1.81 1740 2.08
2440 1437 1.14 1527 1.37 1611 1.62 1690 1.88 1765 2.15
2625 1463 1.19 1551 1.43 1634 1.68 1713 1.95 1788 2.22
2815 1490 1.25 1577 1.49 1659 1.75 1738 2.02 1812 2.30
3000 1519 1.31 1604 1.56 1685 1.82 1762 2.09 1836 2.38
3190 1551 1.38 1633 1.63 1712 1.90 1788 2.18 1861 2.47
3375 1584 1.46 1663 1.71 1740 1.98 1815 2.26 1886 2.55
3565 1621 1.55 1697 1.80 1771 2.07 1843 2.35 1914 2.65
3750 1658 1.64 1731 1.90 1803 2.17 1873 2.45 1942 2.75
Medium Static 850-1731 rpm, 1.90 Max bhp
High Static 850-1942 rpm, 2.75 Max bhp
Table 38 — 40RLSA08 Medium Static Fan Data (rpm - vdc)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
2250 850 4.1 975 4.7 1096 5.4 1210 5.9 1315 6.5
2440 900 4.3 1017 4.9 1130 5.5 1239 6.1 1342 6.6
2625 951 4.6 1060 5.2 1167 5.7 1270 6.2 1369 6.8
2815 1004 4.9 1107 5.4 1207 5.9 1305 6.4 1400 6.9
3000 1056 5.1 1154 5.6 1248 6.1 1341 6.6 1432 7.1
3190 1111 5.4 1203 5.9 1292 6.4 1380 6.8 1467 7.3
3375 1165 5.7 1253 6.2 1337 6.6 1421 7.0 1503 7.4
3565 1221 6.0 1304 6.4 1385 6.8 1464 7.2 1543 7.6
3750 1275 6.3 1355 6.7 1432 7.1 1508 7.5 1583 7.9
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
2250 1412 7.0 1503 7.4— — — — — —
2440 1437 7.1 1527 7.6— — — — — —
2625 1463 7.2 1551 7.7— — — — — —
2815 1490 7.4 1577 7.8— — — — — —
3000 1519 7.5 1604 8.0— — — — — —
3190 1551 7.7 1633 8.1— — — — — —
3375 1584 7.9 1663 8.3— — — — — —
3565 1621 8.1 1697 8.4— — — — — —
3750 1658 8.2 1731 8.6— — — — — —
Medium Static 850-1731 rpm
649
Item5.
48 Table 39 — 40RLSA08 High Static Fan Data (rpm - vdc) CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
2250 850 3.8 975 4.3 1096 4.9 1210 5.4 1315 5.9
2440 900 4.0 1017 4.5 1130 5.1 1239 5.6 1342 6.0
2625 951 4.2 1060 4.7 1167 5.2 1270 5.7 1369 6.2
2815 1004 4.5 1107 5.0 1207 5.4 1305 5.9 1400 6.3
3000 1056 4.7 1154 5.2 1248 5.6 1341 6.0 1432 6.5
3190 1111 5.0 1203 5.4 1292 5.8 1380 6.2 1467 6.6
3375 1165 5.2 1253 5.6 1337 6.0 1421 6.4 1503 6.8
3565 1221 5.5 1304 5.9 1385 6.2 1464 6.6 1543 7.0
3750 1275 5.7 1355 6.1 1432 6.5 1508 6.8 1583 7.2
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
2250 1412 6.4 1503 6.8 1587 7.2 1666 7.5 1740 7.9
2440 1437 6.5 1527 6.9 1611 7.3 1690 7.6 1765 8.0
2625 1463 6.6 1551 7.0 1634 7.4 1713 7.8 1788 8.1
2815 1490 6.7 1577 7.1 1659 7.5 1738 7.9 1812 8.2
3000 1519 6.9 1604 7.2 1685 7.6 1762 8.0 1836 8.3
3190 1551 7.0 1633 7.4 1712 7.7 1788 8.1 1861 8.4
3375 1584 7.2 1663 7.5 1740 7.9 1815 8.2 1886 8.6
3565 1621 7.3 1697 7.7 1771 8.0 1843 8.4 1914 8.7
3750 1658 7.5 1731 7.8 1803 8.2 1873 8.5 1942 8.8
High Static 850-1942 rpm
650
Item5.
49 Table 40 — 40RLSA10 Fan Data (rpm - bhp)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
2550 929 0.26 1041 0.39 1151 0.55 1256 0.74 1357 0.94
2765 989 0.30 1093 0.44 1195 0.61 1294 0.80 1390 1.00
2975 1048 0.36 1146 0.50 1241 0.67 1335 0.86 1426 1.07
3190 1110 0.42 1202 0.57 1291 0.74 1379 0.94 1465 1.15
3400 1171 0.49 1257 0.64 1342 0.82 1425 1.02 1507 1.23
3615 1234 0.57 1316 0.73 1396 0.91 1474 1.11 1552 1.33
3825 1296 0.65 1374 0.82 1450 1.01 1525 1.21 1598 1.43
4040 1360 0.75 1435 0.92 1507 1.12 1578 1.32 1648 1.55
4250 1423 0.86 1494 1.03 1563 1.23 1631 1.44 1698 1.67
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
2550 1451 1.17 1540 1.40 1624 1.65 1703 1.92 1777 2.19
2765 1482 1.23 1569 1.47 1651 1.73 1730 2.00 1804 2.27
2975 1514 1.30 1599 1.55 1680 1.81 1757 2.08 1831 2.36
3190 1550 1.38 1632 1.63 1711 1.89 1786 2.17 1859 2.46
3400 1587 1.47 1666 1.72 1743 1.99 1817 2.27 1888 2.56
3615 1629 1.57 1704 1.82 1778 2.09 1850 2.37 1920 2.67
3825 1672 1.67 1744 1.93 1815 2.20 1884 2.49 1952 2.79
4040 1718 1.79 1786 2.05 1855 2.33 1922 2.62 1987 2.92
4250 1765 1.92 1831 2.19 1896 2.46 1960 2.75 2024 3.06
Medium Static 929-1831 rpm, 2.19 Max bhp High Static 929-2024 rpm, 3.06 Max bhp Table 41 — 40RLSA10 Medium Static Fan Data (rpm - vdc)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
2550 929 4.5 1041 5.1 1151 5.6 1256 6.2 1357 6.7
2765 989 4.8 1093 5.3 1195 5.9 1294 6.4 1390 6.9
2975 1048 5.1 1146 5.6 1241 6.1 1335 6.6 1426 7.0
3190 1110 5.4 1202 5.9 1291 6.4 1379 6.8 1465 7.2
3400 1171 5.7 1257 6.2 1342 6.6 1425 7.0 1507 7.5
3615 1234 6.1 1316 6.5 1396 6.9 1474 7.3 1552 7.7
3825 1296 6.4 1374 6.8 1450 7.2 1525 7.6 1598 7.9
4040 1360 6.7 1435 7.1 1507 7.5 1578 7.8 1648 8.2
4250 1423 7.0 1494 7.4 1563 7.8 1631 8.1 1698 8.4
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
2550 1451 7.2 1540 7.6— — — — — —
2765 1482 7.3 1569 7.8— — — — — —
2975 1514 7.5 1599 7.9— — — — — —
3190 1550 7.7 1632 8.1— — — — — —
3400 1587 7.9 1666 8.3— — — — — —
3615 1629 8.1 1704 8.5— — — — — —
3825 1672 8.3 1744 8.7— — — — — —
4040 1718 8.5 1786 8.9— — — — — —
4250 1765 8.8 1831 9.1— — — — — —
Medium Static 929-1831 rpm
651
Item5.
50 Table 42 — 40RLSA10 High Static Fan Data (rpm - vdc) CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
2550 929 4.1 1041 4.7 1151 5.2 1256 5.6 1357 6.1
2765 989 4.4 1093 4.9 1195 5.4 1294 5.8 1390 6.3
2975 1048 4.7 1146 5.1 1241 5.6 1335 6.0 1426 6.4
3190 1110 5.0 1202 5.4 1291 5.8 1379 6.2 1465 6.6
3400 1171 5.3 1257 5.6 1342 6.0 1425 6.4 1507 6.8
3615 1234 5.5 1316 5.9 1396 6.3 1474 6.6 1552 7.0
3825 1296 5.8 1374 6.2 1450 6.5 1525 6.9 1598 7.2
4040 1360 6.1 1435 6.5 1507 6.8 1578 7.1 1648 7.5
4250 1423 6.4 1494 6.7 1563 7.1 1631 7.4 1698 7.7
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
2550 1451 6.5 1540 7.0 1624 7.3 1703 7.7 1777 8.0
2765 1482 6.7 1569 7.1 1651 7.5 1730 7.8 1804 8.2
2975 1514 6.8 1599 7.2 1680 7.6 1757 8.0 1831 8.3
3190 1550 7.0 1632 7.4 1711 7.7 1786 8.1 1859 8.4
3400 1587 7.2 1666 7.5 1743 7.9 1817 8.2 1888 8.6
3615 1629 7.4 1704 7.7 1778 8.1 1850 8.4 1920 8.7
3825 1672 7.6 1744 7.9 1815 8.2 1884 8.5 1952 8.9
4040 1718 7.8 1786 8.1 1855 8.4 1922 8.7 1987 9.0
4250 1765 8.0 1831 8.3 1896 8.6 1960 8.9 2024 9.2
High Static 929-2024 rpm
652
Item5.
51 Table 43 — 40RLSA12 Fan Data (rpm - bhp)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3000 1049 0.36 1146 0.50 1240 0.67 1333 0.85 1424 1.06
3250 1120 0.43 1211 0.58 1299 0.75 1385 0.94 1470 1.15
3500 1193 0.51 1278 0.67 1360 0.85 1440 1.04 1520 1.25
3750 1266 0.61 1346 0.77 1423 0.95 1499 1.15 1574 1.37
4000 1340 0.71 1415 0.88 1488 1.07 1560 1.28 1630 1.50
4250 1414 0.84 1486 1.01 1555 1.21 1623 1.42 1689 1.64
4500 1489 0.97 1557 1.15 1623 1.36 1687 1.57 1751 1.81
4750 1564 1.12 1629 1.31 1692 1.52 1753 1.74 1814 1.98
5000 1639 1.28 1702 1.49 1762 1.70 1820 1.93 1878 2.17
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3000 1512 1.29 1596 1.54 1677 1.79 1754 2.06 1828 2.35
3250 1553 1.38 1634 1.63 1712 1.89 1788 2.17 1861 2.46
3500 1599 1.49 1676 1.74 1751 2.00 1824 2.28 1895 2.58
3750 1648 1.61 1721 1.86 1793 2.13 1863 2.41 1932 2.71
4000 1700 1.74 1770 2.00 1838 2.27 1906 2.55 1972 2.85
4250 1756 1.89 1822 2.15 1887 2.42 1951 2.71 2015 3.01
4500 1814 2.05 1876 2.31 1938 2.59 2000 2.89 2060 3.19
4750 1874 2.23 1933 2.50 1992 2.78 2051 3.08 ——
5000 1935 2.43 1992 2.70 2048 2.98 ————
Medium Static 1049-1933 rpm, 2.50 Max bhp
High Static 1049-2060 rpm, 3.19 Max bhp
Table 44 — 40RLSA12 Medium Static Fan Data (rpm - vdc)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
3000 1049 5.1 1146 5.6 1240 6.1 1333 6.6 1424 7.0
3250 1120 5.5 1211 5.9 1299 6.4 1385 6.8 1470 7.3
3500 1193 5.8 1278 6.3 1360 6.7 1440 7.1 1520 7.5
3750 1266 6.2 1346 6.6 1423 7.0 1499 7.4 1574 7.8
4000 1340 6.6 1415 7.0 1488 7.4 1560 7.7 1630 8.1
4250 1414 7.0 1486 7.4 1555 7.7 1623 8.1 1689 8.4
4500 1489 7.4 1557 7.7 1623 8.1 1687 8.4 1751 8.7
4750 1564 7.8 1629 8.1 1692 8.4 1753 8.7 1814 9.0
5000 1639 8.1 1702 8.5 1762 8.8 1820 9.1 1878 9.4
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
3000 1512 7.5 1596 7.9— — — — — —
3250 1553 7.7 1634 8.1— — — — — —
3500 1599 7.9 1676 8.3— — — — — —
3750 1648 8.2 1721 8.6— — — — — —
4000 1700 8.5 1770 8.8— — — — — —
4250 1756 8.7 1822 9.1— — — — — —
4500 1814 9.0 1876 9.4— — — — — —
4750 1874 9.4 1933 9.7— — — — — —
5000 1935 9.7— — — — — — — —
Medium Static 1049-1933 rpm
653
Item5.
52 Table 45 — 40RLSA12 High Static Fan Data (rpm - vdc) CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2 0.4 0.6 0.8 1.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
3000 1049 4.7 1146 5.1 1240 5.6 1333 6.0 1424 6.4
3250 1120 5.0 1211 5.4 1299 5.8 1385 6.2 1470 6.6
3500 1193 5.4 1278 5.7 1360 6.1 1440 6.5 1520 6.9
3750 1266 5.7 1346 6.1 1423 6.4 1499 6.8 1574 7.1
4000 1340 6.0 1415 6.4 1488 6.7 1560 7.0 1630 7.4
4250 1414 6.4 1486 6.7 1555 7.0 1623 7.3 1689 7.6
4500 1489 6.7 1557 7.0 1623 7.3 1687 7.6 1751 7.9
4750 1564 7.1 1629 7.4 1692 7.7 1753 7.9 1814 8.2
5000 1639 7.4 1702 7.7 1762 8.0 1820 8.2 1878 8.5
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2 1.4 1.6 1.8 2.0
rpm vdc rpm vdc rpm vdc rpm vdc rpm vdc
3000 1512 6.8 1596 7.2 1677 7.6 1754 7.9 1828 8.3
3250 1553 7.0 1634 7.4 1712 7.7 1788 8.1 1861 8.4
3500 1599 7.2 1676 7.6 1751 7.9 1824 8.3 1895 8.6
3750 1648 7.5 1721 7.8 1793 8.1 1863 8.4 1932 8.8
4000 1700 7.7 1770 8.0 1838 8.3 1906 8.6 1972 8.9
4250 1756 8.0 1822 8.3 1887 8.6 1951 8.9 2015 9.1
4500 1814 8.2 1876 8.5 1938 8.8 2000 9.1 2060 9.4
4750 1874 8.5 1933 8.8 1992 9.0 2051 9.3 ——
5000 1935 8.8 1992 9.0 2048 9.3 ————
High Static 1049-2060 rpm
654
Item5.
53 DECOMMISSIONING
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of recovered refrigerant. It is essential that electrical power is available before the task is commenced.

1. Become familiar with the equipment and its operation.

2. Isolate the system electrically.

3. Before attempting the procedure, ensure that:
a. Mechanical handling equipment is available, if required for handling refrigerant cylinders.
b. All personal protective equipment is available and being used correctly.
c. The recovery process is supervised at all times by a competent person. d. Recovery equipment and cylinders conform to the
appropriate standards.

4. Pump down refrigerant system, if possible.

5. If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.

6. Make sure that the cylinder is situated on the scales before recovery takes place.

7. Start the recovery machine and operate in accordance with instructions.

8. Do not overfill cylinders (no more than 80% of volume liquid charge).

9. Do not exceed the maximum working pressure of the cylinder, even temporarily.

10. When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from the site promptly and all isolation valves on the equipment are closed off.

11. Recovered refrigerant shall not be charged into another refrigerating system unless it has been cleaned and checked.

Equipment shall be labeled that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. For appliances containing flammable refrigerants, ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.
655
Item5.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53400094-01 Printed in U.S.A. Form No. 40RL-7-12-02SI Pg 54 3-25 Replaces: 40RL-7-12-01SI © 2025 Carrier
656
Item5.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53400094-01 Printed in U.S.A. Form No. 40RL-7-12-02SI Pg CL-1 3-25 Replaces: 40RL-7-12-01SI

START-UP CHECKLIST
(SPLIT SYSTEMS WITH 40RL UNITS)
I. PRELIMINARY INFORMATION
OUTDOOR:

MODEL NO. ____________________ _________________________ SERIAL NO. ____________________ _________________________ INDOOR:

MODEL NO. ____________________ _________________________ SERIAL NO. ____________________ _________________________ ADDITIONAL ACCESSORIES _______________________________________________________________________________ __________________________________________________________________________________________________________ II. PRE-START-UP

OUTDOOR UNIT
Is there any shipping damage?
If so, where:_________________________________________________________________________________________________ __________________________________________________________________________________________________________ Will this damage prevent unit start-up? (Y/N) ______
Check power supply. Does it agree with unit? (Y/N) ______ Has the ground wire been connected? (Y/N) ______
Has ground integrity been verified with a continuity test? (Y/N) ______ Has the circuit protection been sized and installed properly? (Y/N) ______ Are the power wires to the unit sized and installed properly? (Y/N) ______ Have compressor holddown bolts been loosened? (Y/N) ______

CONTROLS
Are thermostat(s) & indoor fan control wiring connections made & checked? (Y/N) ______ Are all wiring terminals (including main power supply) tight? (Y/N) ______ Have outdoor unit crankcase heaters been energized for 24 hours? (Y/N) ______

INDOOR UNIT
Has water been placed in drain pan to confirm proper drainage? (Y/N) ______ Are proper air filters in place? (Y/N) ______
PIPING
40RLA, 40RLQ
Has foam shipping block been removed from the TXV (Thermostatic Expansion Valve)? (Y/N) ______ Are Liquid Line Solenoid Valves located at the indoor unit or outdoor unit coils as required? (Y/N) ______ Have leak checks been made at compressors, condensers, indoor coils, TXVs (Thermostatic Expansion Valves) solenoid valves, filter driers, and fusible plugs with a leak detector? (Y/N) ______ Locate, repair, and report any leaks. ___________
Have all compressor service valves been fully opened (backseated) (Y/N) ______ Are the compressor oil sight glasses showing correct levels? (Y/N) ______ 40RLS
Has air been bled from system? (Y/N) ______
Have leak checks been made at compressors, chillers, valves, & indoor coils? (Y/N) ______ Locate, repair, and report any leaks. ___________
NOTE: To avoid injury to personnel and damage to equipment or property when completing the procedures listed in this start-up checklist, use good judgment, follow safe practices, and adhere to the safety considerations/information as outlined in preceding sections of this Installation, Start-Up, and Service document.
657
Item5.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Catalog No. 04-53400094-01 Printed in U.S.A. Form No. 40RL-7-12-02SI Pg CL-2 3-25 Replaces: 40RL-7-12-01SI © 2025 Carrier
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -

CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE

CHECK VOLTAGE IMBALANCE
LINE-TO-LINEV OLTS: AB_____________ V AC______________ V BC_____________ V (AB + AC + BC) / 3 = Average Voltage = __________V
Maximum deviation from average voltage = __________V
Voltage imbalance = 100 x (Max Deviation) / (Average Voltage) = __________ IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM! CALL LOCAL POWER COMPANY FOR ASSISTANCE.

III. START-UP
Check indoor fan motor speed and record.

After at least 10 minutes running time, record the following measurements:

COMP A1 COMP B1
Oil pressure ______________ ____________
Suction pressure ______________ ____________
Suction line temp ______________ ____________
Discharge pressure ______________ ____________
Discharge line temp ______________ ____________
Entering outdoor unit air temp ______________ ____________ Leaving outdoor unit air temp ______________ ____________ Indoor unit entering air DB temp ______________ ____________ Indoor unit entering air WB temp ______________ ____________ Indoor unit leaving air DB temp ______________ ____________ Indoor unit leaving air WB temp ______________ ____________ Outdoor unit entering water temp (40RLS only) ______________ ____________ Outdoor unit leaving water temp (40RLS only) ______________ ____________ Indoor unit entering water temp (40RLS only) ______________ ____________ Indoor unit leaving water temp (40RLS only) ______________ ____________ Compressor amps (L1/L2/L3) ____/____/____ ____/____/____ Check the compressor oil level sight glasses: are the sight glasses showing oil level at 1/8 to 1/3 full? (Y/N) ______ NOTES:
__________________________________________________________________________________________________________ __________________________________________________________________________________________________________ __________________________________________________________________________________________________________ __________________________________________________________________________________________________________ __________________________________________________________________________________________________________ __________________________________________________________________________________________________________ 658
Item5.

SUBMITTAL
Project
Climatec - City of Esc - Public Works Yard
Date
Saturday, April 12, 2025
Shawn Harlan
Sigler - Brea
205 Puente Street
Brea CA
659
Item5.

Table Of Contents
Project: Climatec - City of Esc - Public Works Yard 04/12/2025 Prepared By: Shawn Harlan
ID 6 3
Unit Report 4
Performance Summary 5
System Parameters 5
Electrical Data 5
Acoustic Summary 6
Certified Drawing 7
Residential Carrier Products Bldr 1.39j Page 2 of 9660
Item5.

ID 6
Project: Climatec - City of Esc - Public Works Yard 04/12/2025 Prepared By: Shawn Harlan
ID 6
ID 6
Submittal Cover Sheet
Unit Report
Performance Summary Report
Acoustic Summary
Certified Drawings
Residential Carrier Products Bldr 1.39j Page 3 of 9661
Item5.

Unit Report For ID 6
Project: Climatec - City of Esc - Public Works Yard 04/12/2025 Prepared By: Shawn Harlan
Unit Report
Outdoor Unit Parameters
Unit Model: 27SCA
Unit Size: 1.5 Tons (Size 18)
Voltage: 208/230-1-60 V-Ph-Hz
Indoor Coil Parameters
Unit Model: FT5A
Unit Size: 24,000 Btuh
Cabinet Insulation: Singular, TXV
Voltage: 208-1-60 V-Ph-Hz
Refrigerant Type: Puron Advance
Heating Size: No Heat
Outdoor Unit Dimensions and Weight
Unit Length: 31.1875 in
Unit Width: 31.1875 in
Unit Height: 32.0625 in
Unit Shipping Weight: 169. lb
Indoor Coil Dimensions and Weight
Unit Length: 22.06 in
Unit Width: 17.6 in
Unit Height: 42.69 in
Unit Shipping Weight: 124. lb

RESIDENTIAL APPLICATIONS
This warranty is to the original purchasing owner and subsequent owners only to the extent and as stated in the Warranty Conditions and below.

The limited warranty period in years, depending on the part and the claimant, is as shown in the table below.

Limited Warranty (Years)
Item Original Owner Subsequent Owner
Parts 10* (or 5) 5
Compressor 10* (or 5) 5
*If properly registered within 90 days of original installation, otherwise 5 years (except in California and Quebec and other jurisdictions that prohibit warranty benefits conditioned on registration). See Warranty Conditions below.

OTHER APPLICATIONS
The warranty period is five (5) years on the compressor, and one (1) year on all other parts. The warranty is the original owner only and is not available for subsequent owners.

Ordering Information
Part Number Description Quantity
Outdoor Unit
27SCA518A003 27SCA Comfort Single Stage Heat Pump with Puron Refrigerant Advanced 1.5 Tons Cooling
1 15 SEER @ ARI Conditions
Indoor Coil
FT5ANXB24L00 Performance Series Fan Coil with Puron Advance 208/230-1-60 1 Singular, TXV
Aluminum
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 4 of 9
662
Item5.

Performance Summary For ID 6
Project: Climatec - City of Esc - Public Works Yard 04/12/2025 Prepared By: Shawn Harlan
Performance Summary
System Performance
System: 27SCA/FT5A
System Quantity: 1
Altitude: 0.0 ft
Linear Pipe Length: 0.0 ft
COP @ 47 F: 3.76
COP @ 17 F: 2.50
SEER @ ARI Conditions: 14.5
EER @ ARI Conditions: 11.7
HSPF @ ARI Conditions: 7.5
Actual Clg Airflow: 600.0 CFM
Standard Clg Airflow: 600.0 CFM
Total Net Clg Capacity: 17.00 MBH
Net Sensible Clg Capacity: 12.95 MBH
Htg HP Capacity: 17.30 MBH
Htg HP Integrated Capacity: 17.30 MBH
Heating HP Compressor Power: 1.39 kW
Total System Power: 1.84 kW
System Parameters
System Parameters
Outdoor Unit Parameters
Unit Model: 27SCA518A003
Unit Size (Nominal): 1.5 Tons (Size 18)
Voltage: 208/230-1-60 V-Ph-Hz
Clg Ent Air DB Ambient: 95.0 °F
Htg Ent Air DB Ambient: 47.0 °F
Indoor Coil Parameters
Unit Model: FT5ANXB24L00
Unit Size (Nominal): 24,000 Btuh
Voltage: 208-1-60 V-Ph-Hz
Ent Air DB: 80.00 °F
Ent Air WB: 67.00 °F
Ent Enthalpy: 31.44 BTU/lb
Lvg Air DB: 60.02 °F
Lvg Air WB: 58.17 °F
Lvg Enthalpy: 25.14 BTU/lb
Htg Ent Air DB: 70.0 °F
Htg Lvg Air DB: 96.7 °F
Heating Size (Nominal): No Heat
Total External Static Pressure: 0.50 in wg
Electrical Data
Electrical Data
Outdoor Electrical Data
Unit Voltage: 208/230-1-60 V-Ph-Hz
Fan Motor FLA: 0.50 Amps
MCA: 10.9 Amps
Max Fuse: 15 Amps
Operating Range Min: 197 V
Operating Range Max: 253 V
Compressor RLA: 8.3 Amps
Compressor LRA: 45.1 Amps
Indoor Electrical Data:
(For units with no factory installed electric heaters)
Unit Voltage: 208-1-60 V-Ph-Hz
Unit FLA: 4.0 Amps
Unit MCA: 5.0 Amps
Unit MOCP: 15.0 Amps
Unit Min Wire Size: 14.0
Unit Fuse/Ckt Bkr Amps: 15.0 Amps
Motor HP: 1/2 HP
Notice: Indoor Elect. data is for 208-1-60 voltage
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 5 of 9663
Item5.

Acoustic Summary For ID 6
Project: Climatec - City of Esc - Public Works Yard 04/12/2025 Prepared By: Shawn Harlan
Acoustic Summary
Outdoor Unit Parameters:

Unit Model: 27SCA
Unit Size: 1.5 Tons (Size 18)
Variations: Standard
Octave Band Center Frequency, Hz 125 250 500 1k 2k 4k 8k dBA Sound Power,dB 63.9 65.8 66.6 68.3 63.3 59.7 54.6
A-Weighted Sound Power, dBA 72.0
Indoor Coil Parameters:

Unit Model: FT5A
Unit Size: 24,000 Btuh
Cabinet Insulation: Singular, TXV
Octave Band Center Frequency, Hz 63 125 250 500 1k 2k 4k Sound Power,dB 72.0 68.0 64.0 61.0 59.0 57.0 53.0
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 6 of 9664
Item5.

Certified Drawing For ID 6
04/12/2025 Project: Climatec - City of Esc - Public Works Yard Prepared By: Shawn Harlan
Certified Drawing
Outdoor Model
Unit Model: 27SCA
Unit Size: 1.5 Tons (Size 18)
Voltage: 208/230-1-60 V-Ph-Hz
SEER: 15
PartNumber: 27SCA518A003
Shipping Dimensions and Weights Outdoor Unit
Height 36.44 in
Width 34.25 in
Length 34.25 in
Operating Weight 149. lb
Shipping Weight 169. lb
Dimensions

A B C D E F G H I J K

31.19 in 32.06 in 0.63 in 6.56 in 24.69 in 9.13 in 1.13 in 3.81 in 12.50 in 11.00 in 11.75 in The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 7 of 9665
Item5.

Certified Drawing For ID 6
04/12/2025 Project: Climatec - City of Esc - Public Works Yard Prepared By: Shawn Harlan
Indoor Coil
Unit Model: FT5A
Unit Size: 24,000 Btuh
Voltage: 208-1-60 V-Ph-Hz
Cabinet Insulation: Singular, TXV
PartNumber: FT5ANXB24L00
Dimensions and Weights Indoor Coil
Height 42.69 in
Width 17.63 in
Length 22.06 in
Shipping Weight 124. lb
Dimensions

A B C D E F G H J

42.69 in 17.63 in 15.75 in 15.63 in 10.75 in 18.56 in 18.25 in -- -- The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 8 of 9666
Item5.

Certified Drawing For ID 6
04/12/2025 Project: Climatec - City of Esc - Public Works Yard Prepared By: Shawn Harlan
Indoor Coil
Unit Model: FT5A
Unit Size: 24,000 Btuh
Voltage: 208-1-60 V-Ph-Hz
PartNumber: FT5ANXB24L00
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 9 of 9667
Item5.

SUBMITTAL
Project
Climatec - City of Esc - Real Property
Date
Saturday, April 12, 2025
Shawn Harlan
Sigler - Brea
205 Puente Street
Brea CA
668
Item5.

Table Of Contents
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan 10:53AM
ID 5 3
Unit Report 4
Certified Drawing 5
Performance Summary 6
ID 7 9
Unit Report 10
Certified Drawing 11
Performance Summary 12
ID 3 15
Unit Report 16
Certified Drawing 17
Performance Summary 18
ID 6 21
Unit Report 22
Performance Summary 23
System Parameters 23
Electrical Data 23
Acoustic Summary 24
Certified Drawing 25
Packaged Rooftop Builder 1.79i Page 2 of 27669
Item5.

ID 5
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan 10:53AM
ID 5
ID 5
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 3 of 27 670
Item5.

Unit Report For ID 5
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan 10:53AM
Unit Report
Unit Parameters
Unit Model: 50NT-B48---3
Unit Size: 48 (4 Tons)
Volts-Phase-Hertz: 208-1-60
Heating Type: Heat Pump
Refrigerant: R-454B
Duct Cfg: Horizontal/Horizontal
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 4' 0.25''
Unit Width: 3' 8.1875''
Unit Height: 3' 8.75''
*** Weights and Dimensions are approximate. Weight does not include roof curbs, unit packaging, field installed accessories or factory installed options. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions and weights, refer to appropriate product data catalog.

Base Unit Weight (Does not include any accessories):
412 lb
Warranty Information
1 year warranty on parts
5 yearwarranty on compressor
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50NT-B48---3 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 4 of 27 671
Item5.

Certified Drawing for ID 5
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan 10:53AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 5 of 27 672
Item5.

Performance Summary For ID 5
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan 10:53AM
Performance Summary
Part Number:50NT-B48---3
Refrigerant: R-454B
ARI SEER2: 13.40
Application EER (Rooftop Unit only): 0.00
Base Unit Dimensions
Unit Length: 48.3 in
Unit Width: 44.2 in
Unit Height: 44.8 in
Base Unit Weight (Does not include any accessories): 412 lb Unit
Unit Voltage-Phase-Hertz: 208-1-60
Air Discharge: Horizontal
Fan Drive Type: Direct
Actual Airflow: 1591 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 59.0 F
Evaporator Leaving Air WB: 57.5 F
Evaporator Leaving Air Enthalpy: 24.73 BTU/lb
Unit Discharge Air DB: 0.0 F
Unit Discharge Air WB: 0.0 F
Unit Discharge Air Enthalpy: 0.00 BTU/lb
Net Cooling Capacity: 47.98 MBH
Net Sensible Capacity: 36.13 MBH
Total Unit Power Input: 4.10 kW
Coil Bypass Factor: 0.000
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 94.9 F
Total Heating Capacity: 42.84 MBH
Integrated Heating Capacity: 42.84 MBH
Heating Power Input: 3.51 kW
High Temperature COP: 3.70
Low Temperature COP: 2.26
HSPF2: 6.7
Supply Fan
External Static Pressure: 0.50 in wg
Options / Accessories Static Pressure
Wet Coil: 0.10 in wg
Application External Static (ESP + Unit Opts/Acc.): 0.60 in wg Fan Power: 0.57 BHP
Fan Motor Size, hp: 1
NOTE: Medium Motor Speed, Horz
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Minimum Voltage: 197
Maximum Voltage: 253
Packaged Rooftop Builder 1.79i Page 6 of 27 673
Item5.

Performance Summary For ID 5
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan 10:53AM
Compressor RLA: 19.4
Compressor LRA: 102
Outdoor Fan FLA (ea): 1.2
Indoor Fan Motor FLA (Total): 6.9
Power Supply MCA: 32.4
Power Supply MOCP (Fuse or HACR): 50
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Rating: 74.0 db
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz NA NA NA
125 Hz NA NA 56.9
250 Hz NA NA 59.3
500 Hz NA NA 63.9
1000 Hz NA NA 64.5
2000 Hz NA NA 61.7
4000 Hz NA NA 55.4
8000 Hz NA NA 47.4
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 0.0 56.9 59.3 63.9 64.5 61.7 55.4 47.4 69.3 Lw
B -

26.2 40.8 50.7 60.7 64.5 62.9 56.4 46.3 68.2 LwA
C 0.0 24.5 26.9 31.5 32.1 29.3 23.0 15.0 36.9 Lp
D -

26.2 8.4 18.3 28.3 32.1 30.5 24.0 13.9 35.8 LpA
Legend
Packaged Rooftop Builder 1.79i Page 7 of 27 674
Item5.

Performance Summary For ID 5
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan 10:53AM
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted.

Packaged Rooftop Builder 1.79i Page 8 of 27 675
Item5.

ID 7
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan 10:53AM
ID 7
ID 7
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 9 of 27676
Item5.

Unit Report For ID 7
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan 10:53AM
Unit Report
Unit Parameters
Unit Model: 50NT-B30---3
Unit Size: 30 (2-1/2 Tons)
Volts-Phase-Hertz: 208-1-60
Heating Type: Heat Pump
Refrigerant: R-454B
Duct Cfg: Horizontal/Horizontal
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 4' 0.1875''
Unit Width: 2' 8.625''
Unit Height: 4' 3.75''
*** Weights and Dimensions are approximate. Weight does not include roof curbs, unit packaging, field installed accessories or factory installed options. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions and weights, refer to appropriate product data catalog.

Base Unit Weight (Does not include any accessories):
373 lb
Warranty Information
1 year warranty on parts
5 yearwarranty on compressor
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50NT-B30---3 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 10 of 27677
Item5.

Certified Drawing for ID 7
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan 10:53AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 11 of 27678
Item5.

Performance Summary For ID 7
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan 10:53AM
Performance Summary
Part Number:50NT-B30---3
Refrigerant: R-454B
ARI SEER2: 13.40
Application EER (Rooftop Unit only): 0.00
Base Unit Dimensions
Unit Length: 48.2 in
Unit Width: 32.6 in
Unit Height: 51.8 in
Base Unit Weight (Does not include any accessories): 373 lb Unit
Unit Voltage-Phase-Hertz: 208-1-60
Air Discharge: Horizontal
Fan Drive Type: Direct
Actual Airflow: 959 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 59.4 F
Evaporator Leaving Air WB: 57.6 F
Evaporator Leaving Air Enthalpy: 24.78 BTU/lb
Unit Discharge Air DB: 0.0 F
Unit Discharge Air WB: 0.0 F
Unit Discharge Air Enthalpy: 0.00 BTU/lb
Net Cooling Capacity: 28.73 MBH
Net Sensible Capacity: 21.33 MBH
Total Unit Power Input: 2.30 kW
Coil Bypass Factor: 0.000
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 96.3 F
Total Heating Capacity: 27.26 MBH
Integrated Heating Capacity: 27.26 MBH
Heating Power Input: 2.54 kW
High Temperature COP: 3.00
Low Temperature COP: 2.10
HSPF2: 6.7
Supply Fan
External Static Pressure: 0.50 in wg
Options / Accessories Static Pressure
Wet Coil: 0.05 in wg
Application External Static (ESP + Unit Opts/Acc.): 0.55 in wg Fan Power: 0.38 BHP
Fan Motor Size, hp: 1/2
NOTE: Med-High Motor Speed, Horz
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Minimum Voltage: 197
Maximum Voltage: 253
Packaged Rooftop Builder 1.79i Page 12 of 27679
Item5.

Performance Summary For ID 7
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan 10:53AM
Compressor RLA: 13.9
Compressor LRA: 67
Outdoor Fan FLA (ea): 1.05
Indoor Fan Motor FLA (Total): 3.9
Power Supply MCA: 22.4
Power Supply MOCP (Fuse or HACR): 35
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Rating: 73.1 db
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz NA NA NA
125 Hz NA NA 55.9
250 Hz NA NA 57.0
500 Hz NA NA 63.1
1000 Hz NA NA 63.7
2000 Hz NA NA 59.7
4000 Hz NA NA 54.2
8000 Hz NA NA 48.8
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 0.0 55.9 57.0 63.1 63.7 59.7 54.2 48.8 68.2 Lw
B -

26.2 39.8 48.4 59.9 63.7 60.9 55.2 47.7 67.0 LwA
C 0.0 23.5 24.6 30.7 31.3 27.3 21.8 16.4 35.8 Lp
D -

26.2 7.4 16.0 27.5 31.3 28.5 22.8 15.3 34.6 LpA
Legend
Packaged Rooftop Builder 1.79i Page 13 of 27680
Item5.

Performance Summary For ID 7
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan 10:53AM
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted.

Packaged Rooftop Builder 1.79i Page 14 of 27681
Item5.

ID 3
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan 10:53AM
ID 3
ID 3
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Packaged Rooftop Builder 1.79i Page 15 of 27682
Item5.

Unit Report For ID 3
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan 10:53AM
Unit Report
Unit Parameters
Unit Model: 50NT-B24---3
Unit Size: 24 (2 Tons)
Volts-Phase-Hertz: 208-1-60
Heating Type: Heat Pump
Refrigerant: R-454B
Duct Cfg: Vertical/Vertical
Dimensions (ft. in.) & Weight (lb.) ***
Unit Length: 4' 0.1875''
Unit Width: 2' 8.625''
Unit Height: 4' 3.75''
*** Weights and Dimensions are approximate. Weight does not include roof curbs, unit packaging, field installed accessories or factory installed options. Approximate dimensions are provided primarily for shipping purposes. For exact dimensions and weights, refer to appropriate product data catalog.

Base Unit Weight (Does not include any accessories):
338 lb
Warranty Information
1 year warranty on parts
5 yearwarranty on compressor
No optional warranties were selected.

NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.

Ordering Information
Part Number Description Quantity
50NT-B24---3 Rooftop Unit 1
Packaged Rooftop Builder 1.79i Page 16 of 27683
Item5.

Certified Drawing for ID 3
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan 10:53AM
Certified Drawing
Packaged Rooftop Builder 1.79i Page 17 of 27684
Item5.

Performance Summary For ID 3
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan 10:53AM
Performance Summary
Part Number:50NT-B24---3
Refrigerant: R-454B
ARI SEER2: 13.40
Application EER (Rooftop Unit only): 0.00
Base Unit Dimensions
Unit Length: 48.2 in
Unit Width: 32.6 in
Unit Height: 51.8 in
Base Unit Weight (Does not include any accessories): 338 lb Unit
Unit Voltage-Phase-Hertz: 208-1-60
Air Discharge: Vertical
Fan Drive Type: Direct
Actual Airflow: 828 CFM
Site Altitude: 0 ft
Cooling Performance
Condenser Entering Air DB: 95.0 F
Evaporator Entering Air DB: 80.0 F
Evaporator Entering Air WB: 67.0 F
Entering Air Enthalpy: 31.44 BTU/lb
Evaporator Leaving Air DB: 59.8 F
Evaporator Leaving Air WB: 58.3 F
Evaporator Leaving Air Enthalpy: 25.21 BTU/lb
Unit Discharge Air DB: 0.0 F
Unit Discharge Air WB: 0.0 F
Unit Discharge Air Enthalpy: 0.00 BTU/lb
Net Cooling Capacity: 23.20 MBH
Net Sensible Capacity: 18.05 MBH
Total Unit Power Input: 1.95 kW
Coil Bypass Factor: 0.000
Heating Performance
Outdoor Ambient Temperature: 47.0 F
Entering Air Indoor Coil DB: 70.0 F
Leaving Air Indoor Coil DB: 96.3 F
Total Heating Capacity: 23.50 MBH
Integrated Heating Capacity: 23.50 MBH
Heating Power Input: 1.88 kW
High Temperature COP: 3.80
Low Temperature COP: 2.20
HSPF2: 6.7
Supply Fan
External Static Pressure: 0.50 in wg
Options / Accessories Static Pressure
Wet Coil: 0.04 in wg
Application External Static (ESP + Unit Opts/Acc.): 0.54 in wg Fan Power: 0.22 BHP
Fan Motor Size, hp: 1/2
NOTE: Medium Motor Speed, Vert
Selection includes construction throwaway filter into the base fan curve. This filter is not MERV Rated.

Electrical Data
Minimum Voltage: 197
Maximum Voltage: 253
Packaged Rooftop Builder 1.79i Page 18 of 27685
Item5.

Performance Summary For ID 3
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan 10:53AM
Compressor RLA: 11.8
Compressor LRA: 63
Outdoor Fan FLA (ea): 0.71
Indoor Fan Motor FLA (Total): 3.9
Power Supply MCA: 18.9
Power Supply MOCP (Fuse or HACR): 30
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage Acoustics
Sound Rating: 69.9 db
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz NA NA NA
125 Hz NA NA 59.0
250 Hz NA NA 56.6
500 Hz NA NA 57.9
1000 Hz NA NA 60.9
2000 Hz NA NA 55.3
4000 Hz NA NA 51.7
8000 Hz NA NA 44.0
Advanced Acoustics
Advanced Accoustics Parameters

1. Unit height above ground: 30.0 ft

2. Horizontal distance from unit to receiver: 50.0 ft

3. Receiver height above ground: 5.7 ft

4. Height of obstruction: 0.0 ft

5. Horizontal distance from obstruction to receiver: 0.0 ft

6. Horizontal distance from unit to obstruction: 0.0 ft Detailed Acoustics Information
Octave Band Center Freq. Hz 63 125 250 500 1k 2k 4k 8k Overall A 0.0 59.0 56.6 57.9 60.9 55.3 51.7 44.0 65.6 Lw
B -

26.2 42.9 48.0 54.7 60.9 56.5 52.7 42.9 63.5 LwA
C 0.0 26.6 24.2 25.5 28.5 22.9 19.3 11.6 33.2 Lp
D -

26.2 10.5 15.6 22.3 28.5 24.1 20.3 10.5 31.1 LpA
Legend
Packaged Rooftop Builder 1.79i Page 19 of 27686
Item5.

Performance Summary For ID 3
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan 10:53AM
A Sound Power Levels at Unit's Acoustic Center, Lw
B A-Weighted Sound Power Levels at Unit's Acoustic Center, LwA C Sound Pressure Levels at Specific Distance from Unit, Lp D A-Weighted Sound Pressure Levels at Specific Distance from Unit, LpA Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an Acoustical Engineer or a person with sound prediction expertise should be consulted.

Packaged Rooftop Builder 1.79i Page 20 of 27687
Item5.

ID 6
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan
ID 6
ID 6
Submittal Cover Sheet
Unit Report
Performance Summary Report
Acoustic Summary
Certified Drawings
Residential Carrier Products Bldr 1.39j Page 21 of 27688 Item5.

Unit Report For ID 6
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan
Unit Report
Outdoor Unit Parameters
Unit Model: 27SCA
Unit Size: 3 Tons (Size 36)
Voltage: 208/230-1-60 V-Ph-Hz
Indoor Coil Parameters
Unit Model: FT5A
Unit Size: 36,000 Btuh
Cabinet Insulation: Singular, TXV
Voltage: 208-1-60 V-Ph-Hz
Refrigerant Type: Puron Advance
Heating Size: No Heat
Outdoor Unit Dimensions and Weight
Unit Length: 31.1875 in
Unit Width: 31.1875 in
Unit Height: 32.0625 in
Unit Shipping Weight: 193. lb
Indoor Coil Dimensions and Weight
Unit Length: 22.06 in
Unit Width: 21.1 in
Unit Height: 53.44 in
Unit Shipping Weight: 146. lb

RESIDENTIAL APPLICATIONS
This warranty is to the original purchasing owner and subsequent owners only to the extent and as stated in the Warranty Conditions and below.

The limited warranty period in years, depending on the part and the claimant, is as shown in the table below.

Limited Warranty (Years)
Item Original Owner Subsequent Owner
Parts 10* (or 5) 5
Compressor 10* (or 5) 5
*If properly registered within 90 days of original installation, otherwise 5 years (except in California and Quebec and other jurisdictions that prohibit warranty benefits conditioned on registration). See Warranty Conditions below.

OTHER APPLICATIONS
The warranty period is five (5) years on the compressor, and one (1) year on all other parts. The warranty is the original owner only and is not available for subsequent owners.

Ordering Information
Part Number Description Quantity
Outdoor Unit
27SCA536A003 27SCA Comfort Single Stage Heat Pump with Puron Refrigerant Advanced 3 Tons Cooling
1 15 SEER @ ARI Conditions
Indoor Coil
FT5ANXC36L00 Performance Series Fan Coil with Puron Advance 208/230-1-60 1 Singular, TXV
Aluminum
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 22 of 27
689
Item5.

Performance Summary For ID 6
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan
Performance Summary
System Performance
System: 27SCA/FT5A
System Quantity: 1
Altitude: 0.0 ft
Linear Pipe Length: 0.0 ft
COP @ 47 F: 3.72
COP @ 17 F: 2.52
SEER @ ARI Conditions: 15.2
EER @ ARI Conditions: 12.5
HSPF @ ARI Conditions: 7.5
Actual Clg Airflow: 1200.0 CFM
Standard Clg Airflow: 1200.0 CFM
Total Net Clg Capacity: 34.71 MBH
Net Sensible Clg Capacity: 26.31 MBH
Htg HP Capacity: 34.08 MBH
Htg HP Integrated Capacity: 34.08 MBH
Heating HP Compressor Power: 2.68 kW
Total System Power: 3.35 kW
System Parameters
System Parameters
Outdoor Unit Parameters
Unit Model: 27SCA536A003
Unit Size (Nominal): 3 Tons (Size 36)
Voltage: 208/230-1-60 V-Ph-Hz
Clg Ent Air DB Ambient: 95.0 °F
Htg Ent Air DB Ambient: 47.0 °F
Indoor Coil Parameters
Unit Model: FT5ANXC36L00
Unit Size (Nominal): 36,000 Btuh
Voltage: 208-1-60 V-Ph-Hz
Ent Air DB: 80.00 °F
Ent Air WB: 67.00 °F
Ent Enthalpy: 31.44 BTU/lb
Lvg Air DB: 59.70 °F
Lvg Air WB: 57.97 °F
Lvg Enthalpy: 25.01 BTU/lb
Htg Ent Air DB: 70.0 °F
Htg Lvg Air DB: 96.3 °F
Heating Size (Nominal): No Heat
Total External Static Pressure: 0.75 in wg
Electrical Data
Electrical Data
Outdoor Electrical Data
Unit Voltage: 208/230-1-60 V-Ph-Hz
Fan Motor FLA: 1.20 Amps
MCA: 19.2 Amps
Max Fuse: 30 Amps
Operating Range Min: 197 V
Operating Range Max: 253 V
Compressor RLA: 14.4 Amps
Compressor LRA: 86.0 Amps
Indoor Electrical Data:
(For units with no factory installed electric heaters)
Unit Voltage: 208-1-60 V-Ph-Hz
Unit FLA: 4.0 Amps
Unit MCA: 5.0 Amps
Unit MOCP: 15.0 Amps
Unit Min Wire Size: 14.0
Unit Fuse/Ckt Bkr Amps: 15.0 Amps
Motor HP: 1/2 HP
Notice: Indoor Elect. data is for 208-1-60 voltage
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 23 of 27690 Item5.

Acoustic Summary For ID 6
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan
Acoustic Summary
Outdoor Unit Parameters:

Unit Model: 27SCA
Unit Size: 3 Tons (Size 36)
Variations: Standard
Octave Band Center Frequency, Hz 125 250 500 1k 2k 4k 8k dBA Sound Power,dB 70.6 69.9 68.5 66.0 63.1 59.0 53.2
A-Weighted Sound Power, dBA 76.0
Indoor Coil Parameters:

Unit Model: FT5A
Unit Size: 36,000 Btuh
Cabinet Insulation: Singular, TXV
Octave Band Center Frequency, Hz 63 125 250 500 1k 2k 4k Sound Power,dB 69.0 65.0 61.0 58.0 56.0 54.0 50.0
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 24 of 27691 Item5.

Certified Drawing For ID 6
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan
Certified Drawing
Outdoor Model
Unit Model: 27SCA
Unit Size: 3 Tons (Size 36)
Voltage: 208/230-1-60 V-Ph-Hz
SEER: 15
PartNumber: 27SCA536A003
Shipping Dimensions and Weights Outdoor Unit
Height 36.44 in
Width 34.25 in
Length 34.25 in
Operating Weight 173. lb
Shipping Weight 193. lb
Dimensions

A B C D E F G H I J K

31.19 in 32.06 in 0.75 in 6.56 in 24.69 in 9.13 in 1.13 in 3.81 in 12.00 in 14.13 in 16.25 in The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 25 of 27692 Item5.

Certified Drawing For ID 6
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan
Indoor Coil
Unit Model: FT5A
Unit Size: 36,000 Btuh
Voltage: 208-1-60 V-Ph-Hz
Cabinet Insulation: Singular, TXV
PartNumber: FT5ANXC36L00
Dimensions and Weights Indoor Coil
Height 53.44 in
Width 21.13 in
Length 22.06 in
Shipping Weight 146. lb
Dimensions

A B C D E F G H J

53.44 in 21.13 in 19.25 in 19.13 in 19.19 in 26.94 in 27.50 in -- 19.00 in The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 26 of 27693 Item5.

Certified Drawing For ID 6
Project: Climatec - City of Esc - Real Property 04/12/2025 Prepared By: Shawn Harlan
Indoor Coil
Unit Model: FT5A
Unit Size: 36,000 Btuh
Voltage: 208-1-60 V-Ph-Hz
PartNumber: FT5ANXC36L00
The Product and Ratings Data in this program is subject to change at any time and without notice. Please refer to the latest product literature and the AHRI directory at www.ahridirectory.org for the most up-to-date information.

Residential Carrier Products Bldr 1.39j Page 27 of 27694 Item5.

Marvair MAH Wall Mount Heat Pumps PDS 09/2024 New 8
Room Size Limitations
MAH1020H MAH1024H MAH1030H MAH1036H MAH1042H MAH1048H MAH1060H Refrigerant Charge (oz.) 110 110 112 120 140 160 184
Minimum Room Size (ft²) 108.0 108.0 109.8 117.8 137.5 157.1 180.6 Minimum Supply Height (ft) 6.9 6.9 6.9 6.9 6.9 6.9 6.9
MAH2024H MAH2030H MAH2036H MAH2042H MAH2048H MAH2060H
Refrigerant Charge (oz.) 120 120 150 140 160 184
Minimum Room Size (ft²) 117.8 117.8 147.5 137.5 157.1 180.6 Minimum Supply Height (ft) 6.9 6.9 6.9 6.9 6.9 6.9
Marvair Heat Pump Model Identification
Example M A H 1 0 3 6 H A 0 5 0 C + + R + 1 E A + A 3 1 + + + + + + Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 1 Unit Designation/Family M = Marvair Wall Mount
S = Stock Unit
2 Energy Efficiency Ratio
(EER) A = 11
3 Refrigerant Type H = R-454B
4 Compressor Type/Quantity 1 = Single Stage Compressor
2 = 2-Stage Compressor
5 Unit Capacity/Nominal
Cooling (BTUH)
020 = 20,000 042 = 42,000
024 = 24,000 048 = 48,000
030 = 30,000 060 = 60,000
036 = 36,000
6 7
8 System Type H = Heat Pump
9 Power Supply
(Volts-Hz-Phase)
A = 208/230-60-1 D = 460-60-3
C = 208/230-60-3
10 Heat Designation
@ Rated Voltage
000 = No Heat 090= 9KW
040 = 4KW 100= 10KW
050 = 5KW 120= 12KW
060 = 6KW 150= 15KW
080 = 8KW
11 12
13 Ventilation
Configuration
C = Economizer
D = Motorized Damper w/Pressure Relief
E = Motorized Damper w/Pressure Relief &
Independent Motorized Damper Control
H = GreenWheel® ERV
N = Barometric Damper w/15% OSA
T = Title 24 Compliant Economizer & Controls
+ = None
$ = Special
14 Dehumidification
G = Hot Gas Reheat
R = Electric Reheat
T = Electric Reheat w/Humidity Control
+ = None
$ = Special
15 Controls
A = Power Fail Alarm w/Additional Lockouts
C = 24V EMS Relay Kit
+ = None
$ = Special
16 Operating Condition
A = Evaporator Freeze Sensor (EFS)
C = EFS w/Hot Gas Bypass
D = Desert Duty
E = Extreme Duty
F = Desert Duty w/Hard Start
G = Desert Duty w/EFS
H = Desert Duty w/Hard Start & EFS
J = Extreme Duty w/Hard Start
K = Extreme Duty w/EFS
M = Extreme Duty w/Hard Start & EFS
N = Hard Start
P = Hard Start w/Low Ambient & CCH
Q = Hard Start w/Low Ambient &
Fan Cycle Control (FCC)
R = Crank Case Heater (CCH)
T = Hard Start w/EFS
U = Hard Start w/Hot Gas Bypass
V = Hard Start w/Low Ambient & CCH & EFS
W = Low Ambient w/CCH
X = Hot Gas Bypass
Y = Low Ambient w/CCH & FCC
Z = Low Ambient w/CCH & EFS
1 = Low Ambient w/FCC
2 = Low Ambient w/FCC & EFS
3 = CCH w/Hot Gas Bypass
+ = None
$ = Special
17 Indoor Air Quality Features
A = UV Light
D = Dry Bulb Sensor
E = Dry Bulb Sensor w/Dirty Filter
G = Dirty Filter Sensor
K = Bi-Polar Ionization
M = Dry Bulb Sensor & CO2 Sensor
(Only w/Economizer)
+ = None
$ = Special
18 Air Flow 1 = Top Supply/Center Return (STD)
$ = Special
19 Compressor Location D = Left Hand - All 31
/2 to 5 ton units
E = Right Hand - All 11
/2 to 3 ton units
20 Filter Option
A = 2” Pleated (MERV 8, AC/HP-C)
C = 2” Charcoal
D = MERV 11 High Filtration Package
E = MERV 13 High Filtration Package
F = Filter Access Through Return Air Grille
W = Aluminum Washable
+ = None
$ = Special
21 Corrosion Protection
A = Condenser Coil Only
C = Evaporator Coil Only
D = Both Coils Condenser & Evaporator
E = All Coils Cond/Evap/Reheat
F = Coat All
G = Coastal Package & Evaporator Coil
K = Coastal Package
+ = None
$ = Special
22 Engineering Revision Level A3
23 D3
24 Cabinet Color
1 = Marvair Beige (STD)
2 = Gray (STD)
3 = Carlsbad Canyon (STD)
4 = White (STD)
5 = Stainless Steel Exterior
9 = Pebble Gray
A = Stainless Steel - Unit
$ = Custom Color (Powder Coat)
25 Sound Attenuation 2 = Compressor Blanket
+ = None
26 Security Option
A = Lockable Access Plate/Tamper Proof
C = Tamper Proof Screws
D = Lockable Access Plate w/Tamper Proof
+ = None
$ = Special
27 Fastener/Drain Pan Option
A = Stainless Steel Fasteners
C = Stainless Steel Drain Pan
D = Stainless Steel Fasteners & Drain Pan
+ = None
$ = Special
28 Miscellaneous
C = Copeland Compressor
+ = None
$ = Special
29 Unused + = None
$ = Special
30 Special Variation
+ = None
$ = Special Configuration Not Covered by
Model Nomenclature
Note: Not all options are available with all configurations. Contact your Marvair sales representative for configuration details and feature compatibility. 695
Item5.
9 Marvair MAH Wall Mount Heat Pumps PDS 09/2024 New
Marvair MAH Single Stage Heat Pump Certified Ratings & Performance Efficiency and Capacity Ratings at ANSI/AHRI Standard 390 - MAH Heat Pumps Model Number
MAH1020H MAH1024H MAH1030H MAH1036H MAH1042H MAH1048H MAH1060H

A A C D A C D A C D A C D A C D A C D
Cooling BTUH¹ 20,000 24,000 29,000 35,000 42,000 46,000 57,000 EER² 11 11 11 11 11 11 11
High Temperature Heating³ 20,000 24,000 27,000 30,000 34,000 42,000 51,000 High Temperature COP4 3.3 3.3 3.3 3.3 3.3 3.3 3.3
Rated Air Flow (CFM5
) 760 820 1,150 1,200 1,350 1,700 1,800
1 Cooling is rated at 95°F (35°C) outdoor and 80°F DB/67°F WB (26.5°C DB/19.5°C WB) return air. 2 EER = Energy Efficiency Ratio
3 High Temperature Heating & COP are rated at 47°F DB/43°WB (8.3°C DB/6.1°C WB) outdoor and 70°F (21.1°C) return air. 4 COP = Coefficient of Performance
5 CFM = Cubic Feet per Minute
Ratings are with no outside air. Performance will be affected by altitude. Ratings are at 230 volts for 208/230 volt units (“A” & “C” models) and 460 volts for “D” models.

Operation of units at a different voltage from that of the rating point will affect performance and air flow.

Sensible Total Heat Ratio @ 95ºF (35ºC) Outside Air DB - MAH Heat Pumps Model Number
MAH1020H MAH1024H MAH1030H MAH1036H MAH1042H MAH1048H MAH1060H

A A C D A C D A C D A C D A C D A C D
Total Capacity 20,000 24,000 29,000 35,000 42,000 46,000 57,000 Sensible Heat Ratio 0.80 0.80 0.70 0.70 0.70 0.70 0.60
Sensible Capacity 15,000 18,600 21,500 24,500 27,400 31,000 36,900 Rated Air Flow (CFM¹) 760 820 1,150 1,200 1,350 1,700 1,800 1 CFM=Cubic Feet per Minute
Sensible Heat Ratios based upon ANSI/AHRI std. 390 outdoor conditions of 95°F (35°C) outdoor and 80°F DB/67°F WB (26.5°C DB/19.5°C WB) return air.

Cooling Performance (BTUH) at Various Outdoor Temperatures - MAH Heat Pumps Model
Number
Outdoor Temperature
75ºF/24ºC 80ºF/26.5ºC 85ºF/29ºC 90ºF/32ºC 95ºF/35ºC 100ºF/38ºC 105ºF/40.5ºC 110ºF/43.3ºC 115ºF/46ºC 120ºF/49ºC 125ºF/52ºC 130ºF/54ºC MAH1020H 23,200 22,400 21,600 20,800 20,000 19,200 18,400 17,600 17,200 16,840 16,480 16,120 MAH1024H 27,840 26,880 25,920 24,960 24,000 23,040 22,080 21,120 20,640 20,208 19,776 19,344 MAH1030H 33,640 32,480 31,320 30,160 29,000 27,840 26,680 25,520 24,940 24,418 23,896 23,374 MAH1036H 40,600 39,200 37,800 36,400 35,000 33,600 32,200 30,800 30,100 29,470 28,840 28,210 MAH1042H 48,720 47,040 45,360 43,680 42,000 40,320 38,640 36,960 36,120 35,364 34,608 33,852 MAH1048H 53,360 51,520 49,680 47,840 46,000 44,160 42,320 40,480 39,560 38,732 37,904 37,076 MAH1060H 66,120 63,840 61,560 59,280 57,000 54,720 52,440 50,160 49,020 47,994 46,968 45,942 Based upon ANSI/AHRI std. 390 return air conditions of 80°F DB/67°F WB (26.5°C DB/19.5°C WB). Return air at rated air flow.

Heating Performance (BTUH) at Various Outdoor Temperatures - MAH Heat Pumps Model Number Outdoor Temperature
10ºF/-12.2ºC 17ºF/-8.3ºC 20ºF/-6.7ºC 30ºF/-1.1ºC 40ºF/4.4ºC 47ºF/8.3ºC 50ºF/10ºC 60ºF/15.6ºC 70ºF/21.1ºC MAH1020H 10,766 11,333 12,200 15,233 17,833 20,000 20,600 21,500 22,500 MAH1024H 11,560 13,600 14,640 18,280 21,400 24,000 24,720 25,800 27,000 MAH1030H 15,130 17,800 18,720 21,940 24,700 27,000 27,810 29,025 30,375 MAH1036H 15,810 18,600 19,740 23,730 27,150 30,000 30,900 32,250 33,750 MAH1042H 18,700 22,000 23,340 28,030 32,050 35,400 36,462 38,055 39,825 MAH1048H 20,400 24,000 25,800 32,100 37,500 42,000 43,260 45,150 47,250 MAH1060H 22,900 27,000 29,300 37,500 44,600 51,000 51,900 54,300 61,100 Based upon ANSI/AHRI std. 390 return air conditions of 70°F DB (21.1°C DB). Return air at rated air flow. 696
Item5.

Marvair MAH Wall Mount Heat Pumps PDS 09/2024 New 10
Electrical Characteristics - Compressor, Fan, Ventilation & Blower Motors MAH Heat Pumps with Single Stage Compressor
Basic
Model
Compressor Outdoor Fan Motor Indoor Blower Motor
Ventilation
GreenWheel
AMPS
Type Volts-Hz-Ph RLA¹ LRA² Volts-Hz-PH RPM³ FLA4 HP5 Volts-Hz-PH RPM³ FLA4 HP5 OAM6 EXM7 WD8 MAH1020HA
Scroll
208/230-60-1 10.3 60.2 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 2.8 1/3 MAH1024HA 208/230-60-1 11.9 67.8 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 2.8 1/3 1.0 1.0 0.2 MAH1030HA 208/230-60-1 13.5 82.5 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 4.1 1/2 1.0 1.0 0.2 MAH1036HA 208/230-60-1 14.7 109.0 208/230-60-1 1200 3.5 1/3 208/230-60-1 1050 4.1 1/2 1.0 1.0 0.2 MAH1042HA 208/230-60-1 18.6 123.0 208/230-60-1 1200 5.3 1/2 208/230-60-1 1050 4.1 1/2 1.0 1.0 0.2 MAH1048HA 208/230-60-1 22.4 126.0 208/230-60-1 1200 5.3 1/2 208/230-60-1 1050 4.1 1/2 1.0 1.0 0.2 MAH1060HA 208/230-60-1 25.6 155.0 208/230-60-1 1200 6.3 3/4 208/230-60-1 1050 6.0 3/4 1.0 1.0 0.2 MAH1024HC
Scroll
208/230-60-3 8.3 67.7 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 2.8 1/3 MAH1030HC 208/230-60-3 12.8 97.5 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 4.1 1/2 1.0 1.0 0.2 MAH1036HC 208/230-60-3 12.2 102.8 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 4.1 1/2 1.0 1.0 0.2 MAH1042HC 208/230-60-3 12.8 102.8 208/230-60-1 1200 5.3 1/2 208/230-60-1 1050 4.1 1/2 1.0 1.0 0.2 MAH1048HC 208/230-60-3 12.8 120.4 208/230-60-1 1200 5.3 1/2 208/230-60-1 1050 4.1 1/2 1.0 1.0 0.2 MAH1060HC 208/230-60-3 18.6 155.0 208/230-60-1 1200 6.3 3/4 208/230-60-1 1050 6.0 3/4 1.0 1.0 0.2 MAH1024HD
Scroll
460-60-3 5.1 38.1 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 2.8 1/3 MAH1030HD 460-60-3 5.1 44.3 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 4.1 1/2 1.0 1.0 0.2 MAH1036HD 460-60-3 5.8 50.0 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 4.1 1/2 1.0 1.0 0.2 MAH1042HD 460-60-3 5.8 50.0 208/230-60-1 1200 5.3 1/2 208/230-60-1 1050 4.1 1/2 1.0 1.0 0.2 MAH1048HD 460-60-3 6.0 49.4 208/230-60-1 1200 5.3 1/2 208/230-60-1 1050 4.1 1/2 1.0 1.0 0.2 MAH1060HD 460-60-3 8.3 58.1 208/230-60-1 1200 6.3 3/4 208/230-60-1 1050 6.0 3/4 1.0 1.0 0.2 MAH1024HZ
Scroll
575-60-3 3.8 27.7 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 2.8 1/3 MAH1030HZ 575-60-3 4.5 27.1 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 4.1 1/2 1.0 1.0 0.2 MAH1036HZ 575-60-3 4.5 41.0 208/230-60-1 1200 3.5 1/3 208/230-60-1 1200 4.1 1/2 1.0 1.0 0.2 MAH1042HZ 575-60-3 5.1 41.0 208/230-60-1 1200 5.3 1/2 208/230-60-1 1050 4.1 1/2 1.0 1.0 0.2 MAH1048HZ 575-60-3 5.8 41.0 208/230-60-1 1200 5.3 1/2 208/230-60-1 1050 4.1 1/2 1.0 1.0 0.2 MAH1060HZ 575-60-3 7.7 47.8 208/230-60-1 1200 6.3 3/4 208/230-60-1 1050 6.0 3/4 1.0 1.0 0.2 1 RLA = Rated Load Amps 2LRA = Locked Rotor Amps 3RPM = Revolutions per Minute 4FLA = Full Load Amps 5 HP = Horsepower 6OAM = Outside Air Mover 7EXM = Exhaust Air Mover 8WD = Wheel Drive Motor The 460 volt units have a step down transformer for the 230 volt motors. 697
Item5.
11 Marvair MAH Wall Mount Heat Pumps PDS 09/2024 New
MAH Heat Pumps Summary Electrical Ratings (Wire and HACR Circuit Breaker Sizing) - Ventilation Configuration: