EXHIBIT A
Chapter 13.28 CROSS-CONNECTIONS
Sections:

13.28.010 Definition.

A. “Backflow” is the undesirable reverse flow of water from a private property into the public potable water system that can introduce contaminants into the potable water supply.

B. “Backflow Prevention Assembly” (BPA) is an approved device that prevents contaminated or non-potable water from flowing backward into the potable water supply.

C. "Cross-connection" is any physical connection or arrangement between two otherwise separate piping systems, one of which contains potable water and the other water or substances of unknown or questionable safety, whereby water may flow from one system to the other, the direction of flow depending on the pressure differential between the two systems.

D. “California Cross-Connection Control Policy Handbook” (CCCPH) is a comprehensive guide, adopted by the California State Water Resources Control Board on July 1, 2024, and replacing the previous Title 17 regulations, that provides regulations and guidance to public water systems to protect against crossconnections and backflow contamination.

E. “Cross-Connection Control Plan” is the plan implemented by Hillsborough, in accordance with the CCCPH, to protect its potable water system from contamination resulting from unprotected cross-connections and backflow.

F. “Cross-Connection Control Coordinator” is authorized by the Town’s Director of Public Works Director to perform the daily duties required to implement the Town’s Cross-Connection Control Plan.

G. “Cross-Connection Control Specialist” is certified by an organization recognized in California to prevent contamination of drinking water supplies by identifying and eliminating potential cross-connections and to comply with the California cross-connection control policy handbook requirements (CCCPH, §3.4.1(a), (c); and §3.4.1(a), (c)).

H. “Hazard Assessment” is required for all Hillsborough water customers, in accordance with the CCCPH, and at the time of an Initiating Event, to identify the degree of cross-connection contamination hazard as high, low or no hazard by a certified Cross-Connection Control Specialist.

I. “San Mateo County’s Cross-Connection Control Program” is a program in which the County’s Environmental Health Services contracts with water purveyors to implement a cross-connection program, to protect the public drinking water supply in San Mateo County, as mandated by the State Resources Control Board, Drinking Water Division.
(Ord. 337 § 1 (part), 1976: prior code § 91.10.4)

13.28.020 Maintenance—Prohibited.

It is unlawful for any person to have, keep, maintain, install, or allow the existence of a cross-connection. -190-

Page 2 of 3 ends

(Ord. 337 § 1 (part), 1976: prior code § 91.10.8)

13.28.030 Elimination—Procedure to meet plumbing code, health officer requirements.

A Backflow Prevention Device installed for the purpose of eliminating a cross-connection shall be approved by and installed in accordance with the requirements of law, including, without limitation, any requirements of the CCCPH, the San Mateo County’s Cross-Connection Control Program, Hillsborough’s Cross-Connection Control Plan, and the health officer as defined in Chapter 2.08.

This shall not exempt any person from compliance with applicable requirements of the local plumbing code. (Ord. 608 § 13, 2000; Ord. 337 § 1 (part), 1976: prior code § 91.10.10)

13.28.040 Backflow prevention device—Pollution restriction.

No person shall advertise, sell or offer for use or sale, any water-treating chemical or substance, water-using or water-operated equipment, mechanism or contrivance, which may cause contamination or pollution of the domestic water supply. Such devices may be permitted only when equipped with approved backflow protection devices.
(Ord. 608 § 14, 2000; Ord. 337 § 1 (part), 1976: prior code § 91.10.16)

13.28.050 Backflow prevention device—Testing.

Backflow prevention devices (double check valves, reduced pressure principal devices and pressure vacuum breakers) which have been installed to meet the requirements of the CCCPH and this code shall be tested when installed and at least once each calendar year by a person authorized by the San Mateo County’s Cross-Connection Control Program.
(Ord. 337 § 1 (part), 1976: prior code § 91.10.20(a))

13.28.060 Backflow prevention device—Tester qualifications.

No person shall test and make reports on backflow prevention devices unless authorized to do so by the San Mateo County’s Cross-Connection Control Program. A list of authorized backflow prevention assembly testers is maintained and made available by the San Mateo County’s Environmental Health Services. It is unlawful for any person to maintain a backflow prevention device unless it is tested at least annually by a County authorized tester. (Ord. 337 § 1 (part), 1976: prior code § 91.10.20(b))

13.28.070 Backflow prevention device—Maintenance required.

It is unlawful to use any backflow prevention device installed to meet the requirements of the CCCPH and this code unless it is in good repair. Devices which are defective shall be repaired and tested immediately upon being put into use, and a report of such shall be filed with the San Mateo County’s Environmental Health Services within thirty days after such test.
(Ord. 337 § 1 (part), 1976: prior code § 91.10.206)

13.28.080 Cross-Connection Hazard Assessments
-191-

Page 3 of 3 ends

In accordance with the CCCPH, the following events require a Cross-Connection Control Specialist complete a hazard assessment and submit to the Hillsborough’s Cross-Connection Control Coordinator for approval:
a) if a user premises changes account holder, excluding single-family residences; b) if a user premises is newly or re-connected to the Town’s potable water system; c) if evidence exists of changes in the activities or materials on a user’s premises; d) if backflow from a user’s premises occurs;
e) periodically, as identified in the Hillsborough’s Cross-Connection Control Plan required pursuant to CCCPH section 3.1.4
f) if the State Water Board requests a hazard assessment of a user’s premises; and g) if the Town concludes an existing hazard assessment may no longer accurately represent the degree of hazard.

Hillsborough’s cross-connection control specialist must review or conduct each initial and follow-up hazard assessment pursuant to this section and make a written finding that, in the specialist’s judgment based on crossconnection control principles, the hazard assessment properly identified all hazards at the time of the assessment, the appropriate degree of hazards, and the corresponding backflow protection.

13.28.090 Interpretation of this Chapter.

In interpreting the intent or requirements associated with this Chapter, the Town of Hillsborough’s Cross Control Prevention Plan shall be used to provide guidance, as reasonably determined by the Town. In the event of any inconsistency between this Chapter and the Town’s Cross Control Prevention Plan, the Plan shall control. -192-

Page 1 of 3 ends

EXHIBIT A
Chapter 13.28 CROSS-CONNECTIONS
Sections:

13.28.010 Definition.

A. “Backflow” is the undesirable reverse flow of water from a private property into the public potable water system that can introduce contaminants into the potable water supply.

B. “Backflow Prevention Assembly” (BPA) is an approved device that prevents contaminated or non-potable water from flowing backward into the potable water supply.

C. "Cross-connection" is any physical connection or arrangement between two otherwise separate piping systems, one of which contains potable water and the other water or substances of unknown or questionable safety, whereby water may flow from one system to the other, the direction of flow depending on the pressure differential between the two systems.

D. “California Cross-Connection Control Policy Handbook” (CCCPH) is a comprehensive guide, adopted by the California State Water Resources Control Board on July 1, 2024, and replacing the previous Title 17 regulations, that provides regulations and guidance to public water systems to protect against crossconnections and backflow contamination.

E. “Cross-Connection Control Plan” is the plan implemented by Hillsborough, in accordance with the CCCPH, to protect its potable water system from contamination resulting from unprotected cross-connections and backflow.

F. “Cross-Connection Control Coordinator” is authorized by the Town’s Director of Public Works Director to perform the daily duties required to implement the Town’s Cross-Connection Control Plan.

G. “Cross-Connection Control Specialist” is certified by an organization recognized in California to prevent contamination of drinking water supplies by identifying and eliminating potential cross-connections and to comply with the California cross-connection control policy handbook requirements (CCCPH, §3.4.1(a), (c); and §3.4.1(a), (c)).

H. “Hazard Assessment” is required for all Hillsborough water customers, in accordance with the CCCPH, and at the time of an Initiating Event, to identify the degree of cross-connection contamination hazard as high, low or no hazard by a certified Cross-Connection Control Specialist.

I. “San Mateo County’s Cross-Connection Control Program” is a program in which the County’s Environmental Health Services contracts with water purveyors to implement a cross-connection program, to protect the public drinking water supply in San Mateo County, as mandated by the State Resources Control Board, Drinking Water Division.
(Ord. 337 § 1 (part), 1976: prior code § 91.10.4)

13.28.020 Maintenance—Prohibited.

It is unlawful for any person to have, keep, maintain, install, or allow the existence of a cross-connection. (Ord. 337 § 1 (part), 1976: prior code § 91.10.8)
-193-

Page 2 of 3 ends

13.28.030 Elimination—Procedure to meet plumbing code, health officer requirements.

A Backflow Prevention Device installed for the purpose of eliminating a cross-connection shall be approved by and installed in accordance with the requirements of law, including, without limitation, any requirements of the CCCPH, the San Mateo County’s Cross-Connection Control Program, Hillsborough’s Cross-Connection Control Plan, and the health officer as defined in Chapter 2.08.

This shall not exempt any person from compliance with applicable requirements of the local plumbing code. (Ord. 608 § 13, 2000; Ord. 337 § 1 (part), 1976: prior code § 91.10.10)

13.28.040 Backflow prevention device—Pollution restriction.

No person shall advertise, sell or offer for use or sale, any water-treating chemical or substance, water-using or water-operated equipment, mechanism or contrivance, which may cause contamination or pollution of the domestic water supply. Such devices may be permitted only when equipped with approved backflow protection devices.
(Ord. 608 § 14, 2000; Ord. 337 § 1 (part), 1976: prior code § 91.10.16)

13.28.050 Backflow prevention device—Testing.

Backflow prevention devices (double check valves, reduced pressure principal devices and pressure vacuum breakers) which have been installed to meet the requirements of the CCCPH and this code shall be tested when installed and at least once each calendar year by a person authorized by the San Mateo County’s Cross-Connection Control Program.
(Ord. 337 § 1 (part), 1976: prior code § 91.10.20(a))

13.28.060 Backflow prevention device—Tester qualifications.

No person shall test and make reports on backflow prevention devices unless authorized to do so by the San Mateo County’s Cross-Connection Control Program. A list of authorized backflow prevention assembly testers is maintained and made available by the San Mateo County’s Environmental Health Services. It is unlawful for any person to maintain a backflow prevention device unless it is tested at least annually by a County authorized tester. (Ord. 337 § 1 (part), 1976: prior code § 91.10.20(b))

13.28.070 Backflow prevention device—Maintenance required.

It is unlawful to use any backflow prevention device installed to meet the requirements of the CCCPH and this code unless it is in good repair. Devices which are defective shall be repaired and tested immediately upon being put into use, and a report of such shall be filed with the San Mateo County’s Environmental Health Services within thirty days after such test.
(Ord. 337 § 1 (part), 1976: prior code § 91.10.206)

13.28.080 Cross-Connection Hazard Assessments
In accordance with the CCCPH, the following events require a Cross-Connection Control Specialist complete a hazard assessment and submit to the Hillsborough’s Cross-Connection Control Coordinator for approval:
a) if a user premises changes account holder, excluding single-family residences; -194-

Page 3 of 3 ends

b) if a user premises is newly or re-connected to the Town’s potable water system; c) if evidence exists of changes in the activities or materials on a user’s premises; d) if backflow from a user’s premises occurs;
e) periodically, as identified in the Hillsborough’s Cross-Connection Control Plan required pursuant to CCCPH section 3.1.4
f) if the State Water Board requests a hazard assessment of a user’s premises; and g) if the Town concludes an existing hazard assessment may no longer accurately represent the degree of hazard.

Hillsborough’s cross-connection control specialist must review or conduct each initial and follow-up hazard assessment pursuant to this section and make a written finding that, in the specialist’s judgment based on crossconnection control principles, the hazard assessment properly identified all hazards at the time of the assessment, the appropriate degree of hazards, and the corresponding backflow protection.

13.28.090 Interpretation of this Chapter.

In interpreting the intent or requirements associated with this Chapter, the Town of Hillsborough’s Cross Control Prevention Plan shall be used to provide guidance, as reasonably determined by the Town. In the event of any inconsistency between this Chapter and the Town’s Cross Control Prevention Plan, the Plan shall control. -195-

Page 1 of 3 ends

EXHIBIT A - REDLINE
Chapter 13.28 CROSS-CONNECTIONS
Sections:

13.28.010 Definition.

A. A.“Backflow” is the undesirable reverse flow of water from a private property into the public potable water system that can introduce contaminants into the potable water supply.

B. “Backflow Prevention Assembly” (BPA) is an approved device that prevents contaminated or non-potable water from flowing backward into the potable water supply.

C. "Cross connection" is any physical connection or arrangement between two otherwise separate piping systems, one of which contains potable water and the other water or substances of unknown or questionable safety, whereby water may flow from one system to the other, the direction of flow depending on the pressure differential between the two systems.

D. “California Cross-Connection Control Policy Handbook” (CCCPH) is a comprehensive guide, adopted by the California State Water Resources Control Board on July 1, 2024, and replacing the previous Title 17 regulations, that provides regulations and guidance to public water systems to protect against crossconnections and backflow contamination.

E. “Cross-Connection Control Plan” is the plan implemented by Hillsborough, in accordance with the CCCPH, to protect its potable water system from contamination resulting from unprotected cross-connections and backflow.

F. “Cross-Connection Control Coordinator” is authorized by the Town’s Director of Public Works Director to perform the daily duties required to implement the Town’s Cross-Connection Control Plan.

G. “Cross-Connection Control Specialist” is certified by an organization recognized in California to prevent contamination of drinking water supplies by identifying and eliminating potential cross-connections and to comply with the California cross-connection control policy handbook requirements (CCCPH, §3.4.1(a), (c); and §3.4.1(a), (c)).

H. “Hazard Assessment” is required for all Hillsborough water customers, in accordance with the CCCPH, and at the time of an Initiating Event, to identify the degree of cross-connection contamination hazard as high, low or no hazard by a certified Cross Connection Control Specialist.

I. “San Mateo County’s Cross-Connection Control Program” is a program in which the County’s Environmental Health Services contracts with water purveyors to implement a cross-connection program, to protect the public drinking water supply in San Mateo County, as mandated by the State Resources Control Board, Drinking Water Division.
(Ord. 337 § 1 (part), 1976: prior code § 91.10.4)

13.28.020 Maintenance—Prohibited.

It is unlawful for any person to have, keep, maintain, install, or allow the existence of a cross- connection. (Ord. 337 § 1 (part), 1976: prior code § 91.10.8)
-196-
ATTACHMENT 2
(Supp. No. 29)

Page 2 of 3 ends

13.28.030 Elimination—Procedure to meet plumbing code, health officer requirements.

Any A Backflow Prevention Ddevice installed for the purpose of eliminating a cross- connection shall be approved by and installed in accordance with the requirements of law, including, without limitation, any requirements of the CCCPH, the San Mateo County’s Cross-Connection Control Program, Hillsborough’s CrossConnection Control Plan, and the health officer as defined in Chapter 2.08.

This shall not exempt any person from compliance with applicable requirements of the local plumbing code. (Ord. 608 § 13, 2000; Ord. 337 § 1 (part), 1976: prior code § 91.10.10)

13.28.040 Backflow prevention device—Pollution restriction.

No person shall advertise, sell or offer for use or sale, any water-treating chemical or substance, water-using or water-operated equipment, mechanism or contrivance, which may cause contamination or pollution of the domestic water supply. Such devices may be permitted only when equipped with approved backflow protection devices.
(Ord. 608 § 14, 2000; Ord. 337 § 1 (part), 1976: prior code § 91.10.16)

13.28.050 Backflow prevention device—Testing.

Backflow prevention devices (double check valves, reduced pressure principal devices and pressure vacuum breakers) which have been installed to meet the requirements of the CCCPH Title 17 of the California Administrative Code and this code shall be tested when installed and at least once each calendar year by a person having received a certificate of competence fromauthorized by the health officerSan Mateo County’s CrossConnection Control Program. Records of such tests shall be filed with the health officer within thirty days after such tests, upon forms provided by the health officer.
(Ord. 337 § 1 (part), 1976: prior code § 91.10.20(a))

13.28.060 Backflow prevention device—Tester qualifications.

No person shall test and make reports on backflow prevention devices as required in Title 17 of the California Administrative Code unless he has a certificate of competence issued by the health officerauthorized to do so by the San Mateo County’s Cross- Connection Control Program. The health officer may conduct examinations to determine the competency of any person desiring to test and make reports on backflow prevention devices for the purpose of complying with the requirements of Title 17 of the California Administrative Code. Those persons who have been determined by the health officer to be competent shall receive from the health officer a certificate of competenceA list of authorized backflow prevention assembly testers is maintained and made available by the San Mateo County’s Environmental Health Services. It is unlawful for any person to maintain a backflow prevention device unless it is tested at least annually by a County authorized tester. (Ord. 337 § 1 (part), 1976: prior code § 91.10.20(b))

13.28.070 Backflow prevention device—Maintenance required.

It is unlawful to use any backflow prevention device installed to meet the requirements of Title 17 of the California Administrative Codethe CCCPH and this code unless it is in good repair. Devices which are defective shall -197-

Page 3 of 3 ends

be repaired and tested immediately upon being put into use, and a report of such shall be filed with the San Mateo County’s Environmental Health Services health officer within thirty days after such test. (Ord. 337 § 1 (part), 1976: prior code § 91.10.206)

13.28.080 Cross- Connection Hazard Assessments
In accordance with the CCCPH, the following events require a Cross-Connection Control Specialist complete a hazard assessment and submit to the Hillsborough’s Cross-Connection Control Coordinator for approval:
a) if a user premises changes account holder, excluding single-family residences; b) if a user premises is newly or re-connected to the Town’s potable water system; c) if evidence exists of changes in the activities or materials on a user’s premises; d) if backflow from a user’s premises occurs;
e) periodically, as identified in the Hillsborough’s Cross-Connection Control Plan required pursuant to CCCPH section 3.1.4
f) if the State Water Board requests a hazard assessment of a user’s premises; and g) if the Town concludes an existing hazard assessment may no longer accurately represent the degree of hazard.

Hillsborough’s cross-connection control specialist must review or conduct each initial and follow-up hazard assessment pursuant to this section and make a written finding that, in the specialist’s judgment based on crossconnection control principles, the hazard assessment properly identified all hazards at the time of the assessment, the appropriate degree of hazards, and the corresponding backflow protection.

13.28.090 Interpretation of this Chapter.

In interpreting the intent or requirements associated with this Chapter, the Town of Hillsborough’s Cross Control Prevention Plan shall be used to provide guidance, as reasonably determined by the Town. In the event of any inconsistency between this Chapter and the Town’s Cross Control Prevention Plan, the Plan shall control. -198-