319
Figure 1 Plywood Shearwall Identification
320
Figure 2 Seismic Key Plan with Identifying Gridlines
321
1.1 Codes and References
The As-Built documents provided indicate the Building was designed under the 1979 Building code.
The ASCE 41-17, Seismic Evaluation and Retrofit of Existing Buildings is utilized as the reference document for the Evaluation. Due to the Essential Facility status, Occupancy Category IV, the Benchmark date for the building is set from Table 3.2, which stipulates a benchmark date of 1998.
Benchmark dates are the code threshold to where a building is deemed to comply. The Benchmark date is after the Code date use of the original design. ASCE 41 is therefore applicable. See Attachment 2 for ASCE 41 Tier 1 checklist
The evaluation methodology utilized is Basic Performance Objective Equivalent to New Building Standards. (BPON), Category IV, Immediate Occupancy.
2.0 Design Results and Identified Deficiencies
In general, the documents indicate a structure which is regular, has a logical load path, and designed in apparent conformance with the 1797 Uniform Building Code. The verification to current code standards produce a few areas where retrofit would be recommended. The building appears to be is good to excellent condition.
The ASCE 41-17 BPON seismic base shear values yield Allowable Strength Design Base Shear Levels as indicated below : (See calculations Attachment 1)
See the Shearwall Key Plan in Figure 1
V=.20 ASD Plywood Shearwall R = 6.5
The shearwalls were analyzed to current code level, and all wall shears are within permissible limits.
Overturning on grids 1 and 4 have Simpson HD 7N anchors, which have a capacity less than the calculated value. This was anticipated, the large apparatus bay doors limit the permissible length of shearwall, resulting in increased overturning. The foundation under the highly loaded piers on either side of the app bay doors is also of inadequate size.
The As-Built drawings provide information as to the anchorage of the 6” slump stone veneer located on parts of wall on all elevations. This veneer is of considerable weight and adds measurable seismic mass to the building. Of potential concern is the current longevity of the veneer anchorage system.
The anchorage is noted as (Sheet S1 Veneer Notes):
Minimum 22 Ga corrosion resistant sheet metal (1”) or is of wire shall be of min #9 wire. Anchors shall be spaced so as to not support more than 2 square feet on center horizontally. Anchor Ties shall be provided to horizontal joint reinforcement wire of #9 Ga or equivalent. Notes call for mortar to be slushed into the 1” space between the veneer and the sheathing on studs.
Heavy veneer performance in seismic events is in question. The lateral displacement of a veneer panel without control joints is generally not compatible with the ductile displacement of the plywood shear walls, with the veneer being considerably more rigid.
Current code criteria recognized the potential long term performance issues of veneer anchorage, and seismic performance, and has revised the requirements. CBC 1404.6.2 indicates masonry veneer shall be anchored per 12.2.2.11 of TMS 402 (The Masonry Society). The anchorage requirements of this
322
section is 18: o.c. max each way, maximum anchorage area 2.67 sq ft x .7 = 1.87 sq ft. n a building of this type, that would yield anchors at 16” on center horizontally and 18” o.c. vertically. The existing anchorage does not meet current code recommendations.
Figure 3 Exterior Elevations Indicating Extent of Exterior Veneer Summary of identified building lateral deficiencies:
• Grid 1 and 4, Uplift Anchors and Foundation inadequate. o The repair would be strengthening the shear components on either side of the App Bay doors, providing new foundation and retrofitted uplift mechanism Rough Order of Magnitude Retrofit Costs (ROM): $100,000
323
• Grid 1, and 4 from B to C Chord Splice inadequate for chord force. o The repair would utilize the addition of a Simpson CS strap applied to the top of the plywood sheathing, full length of the grid, with blocking below.
ROM $25,000
• Existing Masonry Veneer Anchorage
o Current code criteria has more stringent anchorage requirements. If architectural considerations permit, the building structure mass reduction and masonry anchorage inadequacies would benefit from the removal of the 6” slump stone Veneer o ROM Architect to Determine
• Diaphragms so not indicate blocking at plywood sheathing edges. Retrofit at high roof recommended.
o Add 3 x blocking and nailing at unblocked edges over App Bay. o ROM $15,000
• Miscellaneous Seismic Anchorage and Contingency
o ROM $10.00 psf @ 14,000 SF $140,000
The ROM costs are estimates of probable cost and do not include the impact to, or replacement of services and finishes required to be removed and replaced during the retrofit. We are not cost estimators, and costs shall be verified by a cost analysis professional.
In addition to the base building review, the non-structural components were visually verified. The nonstructural components include mechanical systems, architectural attachments, cabinets, piping, ceiling systems, etc. Services in the attic space were unable to be viewed due to the hard lid ceilings and limited access.
As an essential facility, there are rigid requirements for bracing of these components.
Observed items include:
• HWH is braced, no retrofit requirement (see photo 17) • Diesel Fuel Tank is bolted to the Foundation, no retrofit required. (photo 10) • Generator is bolted to foundation, no retrofit requirement (photo 7) • Roof top mechanical units are not fastened to platform, retrofit required. (photo 14,15, 16) • Air Compressor is bolted to foundation, no retrofit requirement (photo 8) • Cabinets over 6 feet in height not bolted to wall, attachment required (photo 20)) • Extractor is anchored to foundation, No retrofit required (photo 11) It appears that there is potential for a remodel of the existing facility, and the preliminary plans indicate that the South end (Area A2 in Figure 2) could receive an expansion to the east and west in alignment with existing shearwalls.
Recommendations: Minimize the impact to Grid 1 and Grid 4 existing shearwalls.
324
Architectural Schematic
Remodel Plan Page 24
325
Sincerely,
Miyamoto International, Inc.
Rick Byrd S.E.
Principal
[email protected]
326
Enclosure 1
Structural Calculations
327
CA-111 & El Paseo, Palm Desert, CA 92260, USA
Latitude, Longitude: 33.7213654, -116.3708848
Date 7/21/2023, 3:41:33 PM
Design Code Reference Document ASCE7-16
Risk Category IV
Site Class D - Default (See Section 11.4.3)
Type Value Description
SS 1.5 MCER ground motion. (for 0.2 second period)
S1 0.6 MCER ground motion. (for 1.0s period)
SMS 1.8 Site-modified spectral acceleration value
SM1 null -See Section 11.4.8 Site-modified spectral acceleration value SDS 1.2 Numeric seismic design value at 0.2 second SA
SD1 null -See Section 11.4.8 Numeric seismic design value at 1.0 second SA Type Value Description
SDC null -See Section 11.4.8 Seismic design category
Fa 1.2 Site amplification factor at 0.2 second
Fv null -See Section 11.4.8 Site amplification factor at 1.0 second PGA 0.586 MCEG peak ground acceleration
FPGA 1.2 Site amplification factor at PGA
PGAM 0.703 Site modified peak ground acceleration
TL 8 Long-period transition period in seconds
SsRT 1.701 Probabilistic risk-targeted ground motion. (0.2 second) SsUH 1.854 Factored uniform-hazard (2% probability of exceedance in 50 years) spectral acceleration SsD 1.5 Factored deterministic acceleration value. (0.2 second) S1RT 0.649 Probabilistic risk-targeted ground motion. (1.0 second) S1UH 0.723 Factored uniform-hazard (2% probability of exceedance in 50 years) spectral acceleration.
S1D 0.6 Factored deterministic acceleration value. (1.0 second) PGAd 0.586 Factored deterministic acceleration value. (Peak Ground Acceleration) PGAUH 0.732 Uniform-hazard (2% probability of exceedance in 50 years) Peak Ground Acceleration CRS 0.918 Mapped value of the risk coefficient at short periods CR1 0.897 Mapped value of the risk coefficient at a period of 1 s CV 1.4 Vertical coefficient
328
Palm Desert FS 33
Seismic Assessment
329
330
331
332
Enclosure 2 ASCE 41
Checklist
333
334
335
336
337
338
339
340
Sacramento • San Francisco
www.miyamotointernational.com
• San Jose • Pleasanton • Los Angeles • Ontario • Orange County • San Diego • Reno • Las Vegas • Phoenix • Washington, D.C.
Puerto Rico • Mexico • Costa Rica • Colombia • Haiti • Italy • Ukraine • Turkey • Uzbekistan • Afghanistan • India • Nepal • Thailand • Indonesia • Japan • New Zealand
KEY PLAN
Enclosure 3
Photos and Photo Key Plan 341
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
PHOTOS / ATTACHMENTS
Photo #1
Photo #2
342
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
Photo #3
Photo #4
343
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
Photo #5
Photo #6
344
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
Photo #7
Photo #8
345
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
Photo #9
Photo #10
346
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
Photo #11
Photo #12
347
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
Photo #13
Photo #14
348
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
Photo #15
Photo #16
349
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
Photo #17
Photo #18
350
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
Photo #19
Photo #20
351
Consulting Engineers
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Mechanical and Plumbing Systems Assessment
Palm Desert Fire Station 33
at
44400 Town Center Way
Palm Desert, CA 92260
May 17, 2023
Prepared By:
Pocock Design Solutions, Inc.
Andrew Gossman, PE, HFDP, LEED AP BD+C
14451 Chambers, Rd. Ste. 210
Tustin, CA 92780
Palm Desert Fire Station 33 & 71 Assessments Page 15 Page 51 352
Palm Desert Fire Station 33 May 17, 2023
HVAC and Plumbing Assessment Page 2
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Introduction
Pocock Design Solutions, Inc. has been contracted by PBK Architects to perform an assessment of the existing mechanical and plumbing systems at the Palm Desert Fire Station 33 located at 44400 Town Center Dr, in Palm Desert, CA. The primary purpose of this assessment is to review and document the condition of existing mechanical and plumbing systems, identify apparent non-code-compliant systems, and provide recommendations for future tenant improvements. A site investigation was performed on March 21, 2023.
The facility was reviewed with the following codes:
CBC 2022………………………………………... California Building Code
CMC 2022……………………………………….. California Mechanical Code
CPC 2022……………………………………….. California Plumbing Code
CEC 2022………………………………………. . California Energy Code
CAL Green 2022………………………………… California Green Building Code Existing HVAC Conditions
The fire station is primary conditioned by five (5) rooftop packaged gas/electric a/c units located on the roof. The units are not original and have been replaced at various times throughout the past eight years. All of the units are in good condition but do not currently have outside air intakes or economizers for building ventilation.
Manufacturer Model Capacity (Tons) Date Manu.
Age
(years)
Carrier 48VL 5 2017 6
Carrier 48VL 5 2015 8
Carrier 48VL 5 2022 1
Carrier 48VL 5 2018 5
Carrier 48VL 4 2015 8
All of the packaged a/c units are horizontal discharge with the supply and return ductwork routed above the roof. The rooftop ductwork appears to be original and is in fair to poor condition. The units are all sitting on roof pads with sheet metal caps. It does not appear the units are currently anchored and are just resting on the roof pads. The unit located in the mechanical well does not fit on the existing roof pad and overhangs by a couple inches.
Each AC unit is controlled by a wall mounted electronic thermostat. The thermostats vary in age and functionality with some that are very basic with limited programmability and some that are more advanced with a touch screen interface.
The restrooms are typically exhausted by ceiling mounted exhaust fans with ductwork up to roof caps. The roof caps are basic bent sheet metal hoods. The ceiling exhaust fans are in fair to good condition. There is a utility set exhaust fan on the roof which serves the existing kitchen hood. It is anchored to wood blocks with a horizontal discharge. This fan is aged and in need of replacement. The workshop has a roof mounted centrifugal exhaust fan located on a curb on the low roof. There is no permanent access to this roof and the fan is located within 10’ of the roof edge with no parapet or fall protection. The fan appears to be in good to fair condition.
Palm Desert Fire Station 33 & 71 Assessments Page 52
353
Palm Desert Fire Station 33 May 17, 2023
HVAC and Plumbing Assessment Page 3
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 The apparatus bay is semi-conditioned by four (4) evaporative cooling units located in a mechanical well on the north side. The units were manufactured in 2020 and are in good condition. The evaporative media within the units is worn to the expected condition for the age of the units and will need replacement in the next year or two. The mechanical well is very congested with the units stacked on built up metal framing. Ductwork is routed in the well to sidewall supply registers on the north side of the apparatus bay. Barometric relief louvers on the south side of the apparatus bay relieve the air when the evaporative coolers are in operation. The louvers appear to be functional although the system was not running at the time of survey. The as built documents indicate the app bay once had suspended gas-fired unit heaters but it appears these have been removed.
The apparatus bay has a Plymovent vehicle exhaust system with piped intakes routed to a utility set fan on the roof. The exhaust fan looks aged and in need of replacement.
There is a generator room adjacent to the app bay that is naturally ventilated with high and low louvers at the exterior wall. The generator exhaust pipe is routed out through the wall to the north.
A clothes dryer located in the workshop is vented through the exterior wall with flexible aluminum duct. Another dryer located in the central mechanical room is vented up through an existing ceiling register and then through the roof.
Recommendations
Single zone packaged a/c units controlled by a single thermostat have gone out of favor for this building application due to limited controllability of temperature from room to room. However, the existing packaged a/c units are in good condition with likely 10+ years of useful life remaining. If the layout of the interior of the building is to remain relatively unchanged, then the existing systems can remain as is. The existing ductwork on the roof is aged but can remain with minor clean and repair as required. It is recommended the existing a/c units be retrofitted with new economizers for improved indoor air quality and energy savings. Economizers are required per current energy code requirements. Recommend cleaning and resealing existing to remain ductwork within the building and replacing duct insulation. It is recommended all units to remain be anchored to the roof at the existing roof pads. If the building is to be re-roofed, it is recommended to remove the existing a/c units and reinstall them on new built-up roof curbs for improved weatherproofing.
If the interior of the building is to receive an extensive remodel with a modified floor layout or if the department is currently unhappy with the temperature control of the existing systems, then brand-new AC systems can be provided. All existing ductwork and systems would be removed and a completely new system would be provided. VRF systems with heat recovery are recommended which would include fan coil units throughout the building for complete independent temperature control from room to room.
The VRF system would include roof mounted condensing units and a central controller.
The existing evaporative coolers are in good condition and have significant useful life expectancy remaining. The interior media will need replacement in the next year or so which is typical for these units.
The existing ceiling exhaust fans are in good condition and can be cleaned and remain. If the building is to be re-roofed, it is recommended the existing roof caps be removed and replaced with new curb mounted caps for improved weatherproofing and durability.
Palm Desert Fire Station 33 & 71 Assessments Page 53
354
Palm Desert Fire Station 33 May 17, 2023
HVAC and Plumbing Assessment Page 4
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Recommend replacement of the existing Plymovent exhaust fan based on apparent condition. Existing vehicle exhaust ductwork can remain and be reused.
To improve energy efficiency and controllability of the various mechanical systems, it is recommended all new electronic programmable thermostats be provided with wifi connection for remote access and control.
Photos:
Photo 1: Typical rooftop gas/electric packaged a/c units with roof ductwork.
Palm Desert Fire Station 33 & 71 Assessments Page 54
355
Palm Desert Fire Station 33 May 17, 2023
HVAC and Plumbing Assessment Page 5
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Photo 2: Mechanical well with App Bay evaporative coolers and rooftop packaged a/c unit.
Photo 3: Evaporative cooler block support and pan rust.
Palm Desert Fire Station 33 & 71 Assessments Page 55
356
Palm Desert Fire Station 33 May 17, 2023
HVAC and Plumbing Assessment Page 6
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Photo 4: Apparatus Bay Plymovent exhaust system on roof.
Photo 5: Return grille in hallway ceiling.
Palm Desert Fire Station 33 & 71 Assessments Page 56
357
Palm Desert Fire Station 33 May 17, 2023
HVAC and Plumbing Assessment Page 7
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Photo 6: Typical wall mounted electronic thermostat.
Photo 7: Typical restroom ceiling mounted exhaust fan.
Palm Desert Fire Station 33 & 71 Assessments Page 57
358
Palm Desert Fire Station 33 May 17, 2023
HVAC and Plumbing Assessment Page 8
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Photo 9: Typical restroom exhaust roof caps.
Photo 9: Evaporative cooler supply grilles in apparatus bay.
Palm Desert Fire Station 33 & 71 Assessments Page 58
359
Palm Desert Fire Station 33 May 17, 2023
HVAC and Plumbing Assessment Page 9
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Existing Plumbing Conditions
The plumbing infrastructure appears to be original to the building and is approximately 42 years old. Domestic water piping within the building was observed to be copper and waste/vent piping observed to be cast iron. Per the as-built drawings, the existing domestic water service is 1-1/2” and the existing sewer lateral is 4”.
Plumbing fixtures within the building include tank type water closets, flush valve urinals, and lavatories with manual faucets. Fixtures appear to be in good condition.
The existing domestic hot water system consists of a central gas-fired instantaneous high-efficiency water heater and 99-gallon storage tank. The water heater was manufactured around 2015 and is in good condition. The system includes a circulating pump with timeclock and expansion tank. The expansion tank is currently supported by the piping it is connected to on the bottom. The water heater flue thru the roof terminates at a location that is within 10’ of an existing a/c unit. Although there is no current outside air intake at this unit, if one is to be added, the existing flue termination will need to be relocated.
The building is provided natural gas from the meter located on the north side of the building. Gas piping is black iron and mainly routed below the roof then stubbed up to the a/c units.
The apparatus bay includes area drains which are routed through an existing grease trap located below grade adjacent to the building.
Makeup water is provided to the evaporative cooling units located in the mechanical well through individual copper lines with angle stops and a central gate valve. A backflow prevention device was not observed on the water line feeding these units.
A hose bib could not be located on the roof near the mechanical units.
A generator and air compressor are located in a room adjacent to the apparatus bay. The air compressor is piped to outlets in the workshop. The compressed air piping was observed to be copper.
The kitchen includes a commercial gas range and hood which appear to be in good condition. It does not appear the building has a control station with gas shutoff valves connected to the emergency call system.
Plumbing Recommendations
The existing 1-1/2” cold water line is likely adequate for any tenant improvement scope but will continue to require the use of flush tank water closets in lieu of flash valve type.
The existing 4” sewer line is likely adequate for any tenant improvement scope. It is recommended the existing underground waste piping be inspected with a camera system to confirm there are no obstructions or broken pipes.
Any tenant improvement scope that requires removal of existing plumbing fixtures, will also require installation of new plumbing fixtures which are low-flow and compliant with current Cal Green requirements.
The existing domestic water heater and storage tank are in good condition with useful life expectancy remaining. This system can remain and be reused for any future tenant improvement scope. Recommend reinstalling the existing expansion tank with proper support and attachment per code requirements.
It is recommended new hose bibb with vacuum breakers be provided on the roof for cleaning purposes.
Palm Desert Fire Station 33 & 71 Assessments Page 59
360
Palm Desert Fire Station 33 May 17, 2023
HVAC and Plumbing Assessment Page 10
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Recommend painting any existing black steel gas piping that is exposed on the roof to prevent rust and deterioration.
Recommend providing new backflow preventer in existing domestic cold-water line that is feeding the evaporative cooling units in the mechanical well per code requirements.
Recommend installing new gas control station with automatic shutoff solenoid valve to kitchen with connection to the emergency call system.
The existing water heater flue termination will need to be relocated further than 10’ away from the new recommended outside air intake on the existing a/c unit on the roof.
Photos:
Photo 1: Domestic hot water heater and storage tank located in mechanical room.
Palm Desert Fire Station 33 & 71 Assessments Page 60
361
Palm Desert Fire Station 33 May 17, 2023
HVAC and Plumbing Assessment Page 11
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Photo 2: Typical flush tank water closet.
Photo 3: Typical area drain in Apparatus Bay.
Palm Desert Fire Station 33 & 71 Assessments Page 61
362
Palm Desert Fire Station 33 May 17, 2023
HVAC and Plumbing Assessment Page 12
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Photo 4: Commercial washer/extractor and dryer located in Workshop.
Photo 5: Gas meter and regulator on the north side of the building.
Palm Desert Fire Station 33 & 71 Assessments Page 62
363
Palm Desert Fire Station 33 May 17, 2023
HVAC and Plumbing Assessment Page 13
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Photo 6: Typical gas and condensate piping to a/c unit on roof.
Photo 7: Makeup water connections for evaporative cooling units in mechanical well.
Palm Desert Fire Station 33 & 71 Assessments 364
Palm Desert Fire Station 33 May 17, 2023
HVAC and Plumbing Assessment Page 14
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Photo 8: Generator and workshop air compressor.
Palm Desert Fire Station 33 & 71 Assessments 365
A & F ENGINEERING GROUP, INC.
CONSULTING ELECTRICAL ENGINEERS
9320 BASELINE RD. SUITE C, RANCHO CUCAMONGA, CA 91701, Tel (909) 941-3008, Fax (909) 941-8211 May 22, 2023
Mr. Kelley Needham
PBK Architects
8163 Rochester Avenue, Suite 100
Rancho Cucamonga, CA 91730
Re: Electrical Systems Assessment
Riverside County Fire, Fire Station #33
73995 Country Club Dr. Palm Desert, CA
Mr Needham,
The following is our evaluation of the electrical systems at the aforementioned fire station:
Existing Conditions:
Lighting
Building interior lighting consists primarily of fluorescent 2x4 and 1x4 light fixtures, incandescent downlight fixtures, wall mounted reading lights in the dorms, and H.I.D. fixtures in the Hose Tower. The fixtures appear to be in fair condition.
The 2x4, 1x4 and H.I.D. light fixtures do not have dimming capabilities and cannot meet current dimming requirements of the 2022 Energy Efficiency Standards (Title 24) Light fixtures using incandescent lamps with screw-in bases do not comply with the high efficiency requirements of Title and must be replaced.
The Kitchen downlights and the lights in the newly remodeled restroom are controlled by occupant sensor. All other lighting controls consist of standard toggle switches that provide bi-level switching. The bi-level switching consists of two switches, configured in the traditional “a/b” configuration, that allows the occupant to turn “on” or “off” half the fixtures in the room. In addition to bi-level switching, the Corridor, Open Office, and Dayroom have 3-way switching.
The lighting controls do not meet the dimming and automatic shut-off control requirements of Title 24.
Switches connected to emergency circuits are not “red” in color, do not have “red” wall plates and are not identified as being connected to emergency circuits.
Lighting circuits are protected by standard thermal magnetic type circuit breakers. The circuit breakers cannot provide the arc fault circuit interrupter functions required by current codes.
Building exterior lighting consists of downlights recessed in the overhangs and soffits, wall mounted residential style dual head incandescent security flood light fixtures at the patio/BBQ area, wall pack fixtures at the return drive, and wall mounted floodlights at the response drive. The fixtures appear to be in fair to good condition. Wall pack and floodlight type fixtures are not shielded , therefore, not T24 compliant.
Palm Desert Fire Station 33 & 71 Assessments Page 65
366
A&F ENGINEERING GROUP, INC.
9320 BASELINE RD. SUITE C, RANCHO CUCAMONGA, CA 91701, Tel (909) 941-3008, Fax (909) 941-8211
Electrical Systems Assessment
Riverside Co. Fire, Station #33
Palm Desert, CA
The building exterior light fixtures are controlled by time clocks located above panel A in the corridor leading to the App Bay from the Dayroom. The time clocks are not astronomical time clocks with daylight savings functions, therefore, do not meet current Title 24 requirements.
Site/Parking lot lighting consists of pole mounted fixtures, with H.I.D. lamps, mounted at approximately 10’-0” above grade. H.I.D. lamps do not meet current dimming and automatic control requirements. The site lighting fixtures are controlled by a time clock located above panel C in the Storage room adjacent to the generator room. The time clock is not an astronomical time clock with daylight savings functions, therefore, do not meet current Title 24 requirements.
Power
The utility service is 600 amps and operates at 120/208V, 3 phase, 4 wire. The rating of the service is capable of serving the 200 Amps building demand load with 65% spare capacity for expansion.
The main service switchboard was manufactured by Square-D and uses Square-D “QMB” style fused switches as overcurrent devices. The switchboard is 30 plus years old, in fair condition, and replacement switches are available. One switch in the “off” position is labeled “Bad” and must be replaced. The switchboard does not have space to install additional 100A or larger switches and there is no space in the room to expand the gear, thus, restricting the addition of switches required to support the installation of panels for EV chargers and a PV power plant.
The main switchboard is located in the main Electrical room. The electrical room is compliant with the utility company requirements.
Branch circuit panels consist of commercial grade branch circuit panels and one residential grade load center. Panels A, B and C are commercial grade, in good condition, and replacement circuit breakers are readily available. The unmarked/not labeled residential grade load center is sub-fed from panel C and is part of the emergency power distribution system, it is in good condition and replacement circuit breakers are readily available. Emergency panel C is a 225A. panel and cannot carry the full load of the 100kW (300 Amps) generator.
Emergency panel C and the unmarked load center are not labeled or identified as emergency panels.
There are no arc fault circuit interrupter (AFCI) circuit breakers in the panels, AFCI circuit breakers are required to protect circuits serving the residential areas of the building.
The main switchboard and panels do not have Arc flash labels.
Receptacles are standard duplex grounding type and receptacles near the kitchen and bathroom sinks are GFI type.
Palm Desert Fire Station 33 & 71 Assessments Page 66
367
A&F ENGINEERING GROUP, INC.
9320 BASELINE RD. SUITE C, RANCHO CUCAMONGA, CA 91701, Tel (909) 941-3008, Fax (909) 941-8211
Electrical Systems Assessment
Riverside Co. Fire, Station #33
Palm Desert, CA
However, the receptacles do not comply with current codes. Receptacles in residential (R Occupancy) areas must be tamper proof and either AFCI type or protected by an AFCI circuit breaker at the panel. Administrative (B Occupancy) areas, such as offices, conference rooms, lobbies, breakrooms, must have controlled receptacles within six feet of a standard receptacle, the controlled receptacles must be clearly identified and controlled by the room’s occupant sensor. All kitchen 120V. 15 or 20 amp receptacles must be GFI and protected by an AFCI circuit breaker. The Laundry room and App Bay receptacles must be GFI type.
Receptacles do not comply with current ADA mounting height requirements. ADA requires receptacles to be mounted at +48” maximum to the top of the box and +15” minimum to the bottom of the box, and +46” maximum to the top of box when located above counter tops.
Receptacles connected to emergency circuits are not “red” in color, do not have “red” wall plates and are not identified as being connected to emergency circuits.
Outdoor receptacles are GFI type. However, the covers are not U.L. listed for use in wet locations when “in-use”, therefore, do not meet code.
The 100kW (300 Amps) Caterpillar emergency generator, located in the Hose Tower room, is 40 plus years old and provides emergency power to the station upon loss of utility power. The station’s emergency power distribution system is designed to provide emergency power for life safety equipment and selected building loads, the system does not provide emergency power to the entire station.
The Zenith automatic transfer switch (ATS) appears to be the same vintage as the generator, is located in the main electrical room and remote from the generator. The ATS is obsolete, and in fair to good condition.
The Hose Tower room was not designed to house a generator. The room’s construction must be reviewed by a Structural Engineer to confirm the 2 hours fire rating requirement. The ventilation system and engine exhaust system must be reviewed by a Mechanical Engineer for compliance with current codes. The compressor located in the Hose Tower room must be relocated, only equipment related to the generator can reside in the generator room.
Fuel to the generator is supplied from a remote aboveground fuel tank.
Communications
The alerting system/base radio is operational and in good working condition. The system includes a Kenwood base radio with power supply, a Comtronix station control interface that manages the signaling and audio systems, a printer, a microphone, an amplifier, a stereo tuner, a media selector, and speakers throughout the station. The system is outdated and the Comtronix controller is obsolete. The equipment is located in the corridor leading to the App Bay from the Dayroom.
The telephone service enters the building underground and terminates on a backboard located in the main electrical room (north side of the App Bay). City/FD owned telephone cable is routed between the telephone company main point of entry (MPOE) in the electrical room Palm Desert Fire Station 33 & 71 Assessments Page 67
368
A&F ENGINEERING GROUP, INC.
9320 BASELINE RD. SUITE C, RANCHO CUCAMONGA, CA 91701, Tel (909) 941-3008, Fax (909) 941-8211
Electrical Systems Assessment
Riverside Co. Fire, Station #33
Palm Desert, CA
and the telephone switch in the Storage room located in the main building (south of the App Bay). Due to the nature of the Storage room, access to the terminals and telephone equipment may be obstructed by stored materials. The equipment should be relocated to a secure location accessible to only to authorized personnel.
There is no 911 phone at the front of the station.
The cable TV (CATV) service enters the building aboveground. From an underground utility box, located in the turf area near the west wall of the old hose drying area, the service cable transitions to aboveground and runs exposed along the wall of the building and enters the electrical room through a plastic sleeve in the wall and terminates in a terminal cabinet in the electrical room. CATV lines are distributed to the TV monitor in the Conference room and Dayroom. No other CATV line or drop was found during the site visit.
The entry doors to the station are equipped with entry keypads and a door bell push button that alerts FD personnel of visitors at the entry doors.
The data/computer network system consists of a router located in the Storage room. The system provides service to wall mounted station outlets and two wireless access points. Due to the nature of the Storage room, access to the network equipment may be obstructed by stored materials. The equipment should be relocated to a secure location accessible to only to authorized personnel.
Areas of the station, accessible to the public, did not have fire alarm coverage. The corridor leading to the dorms was equipped with a smoke detector. The dorms did not have smoke detectors, and there were no CO detectors.
Recommendations:
Lighting:
Replace all interior light fixtures with new high efficiency LED fixtures with dimming drivers.
Provide dimers in each room to control the new LED fixtures. Mount dimmers at ADA compliant mounting heights. Dimmers connected to emergency circuits are to be provided with “red” wall plates. The serving panel and circuit number should be engraved on the wall plate.
Provide ceiling mounted or wall switch type occupant sensors for perform the T24 required automatic building shut-off functions. Sensors in the non-residential areas of the station are to operate in “automatic” mode. Sensors in the residential areas of the station are to operate in “vacancy” mode. The vacancy setting ensures that lights do not automatically turn on when motion is detected, lights must be physically turned on and will shut off automatically.
Replace all building exterior light fixtures with new high efficiency LED fixtures with dimming drivers. Wall mounted fixtures are to be shielded to prevent light spill.
Palm Desert Fire Station 33 & 71 Assessments Page 68
369
A&F ENGINEERING GROUP, INC.
9320 BASELINE RD. SUITE C, RANCHO CUCAMONGA, CA 91701, Tel (909) 941-3008, Fax (909) 941-8211
Electrical Systems Assessment
Riverside Co. Fire, Station #33
Palm Desert, CA
Replace the H.I.D. area/parking lot fixtures with new high efficiency LED fixtures. For compliance with current Title 24 requirements the fixtures are to be provided with a dimming driver and integral motion sensor that will allow the illumination levels to automatically dim to 50% when the surrounding area is unoccupied. Additional fixtures may be required to comply with the IES recommended foot-candle levels for security and safety purposes.
Replace the time clock with a new astronomical time clock and compatible photocell.
Provide AFCI circuit breakers for all lighting circuits serving the residential areas of the station.
Power:
Replace the main service switchboard, with a new switchboard that utilizes circuit breakers, to increase circuit capacity and facilitate the connection of the new generator for whole building back-up power, provide power to existing panels, HVAC equipment, the compressor and have space for circuit breakers to provide power for EV charging stations and a 40kW PV power plant. Replacement of the main service switchboard will require SCE to confirm the existing utility infrastructure is adequate to support the new service.
Remove the ATS from the electrical room and designate the vacated space for the installation of a solar AC disconnect switch and SCE meter.
Replace the panels with new commercial grade branch circuit panels and provide the panel with AFCI circuit breakers for circuits serving the residential areas. Trace all existing circuits and update the panel directories If existing panels are re-used, replace existing circuit breakers serving circuits in the residential areas of the station with AFCI circuit breakers.
Provide a new panel for EV charging stations.
Perform a short circuit and arc fault study to ensure panels are rated to withstand the available fault currents and to identify the arc flash boundaries. Provide arch flash labels for all panels Replace the receptacles in the residential areas with tamper proof receptacles. If AFCI circuit breakers are not provided, the new receptacles must be tamper proof AFCI type.
Provide controlled receptacles in offices, conference rooms, lobbies and breakrooms. The installation of controlled receptacles must be coordinated with the installation of occupant sensors.
Replace all kitchen receptacles with GFI receptacles. If AFCI circuit breakers are not provided, the new receptacles must be combination GFI/AFCI type.
Relocate receptacles as required to meet the ADA mounting height requirements.
Identify a new location for the compressor and reconnect to the serving panel.
Palm Desert Fire Station 33 & 71 Assessments Page 69
370
A&F ENGINEERING GROUP, INC.
9320 BASELINE RD. SUITE C, RANCHO CUCAMONGA, CA 91701, Tel (909) 941-3008, Fax (909) 941-8211
Electrical Systems Assessment
Riverside Co. Fire, Station #33
Palm Desert, CA
Provide a new 180kW generator to provide stand-by power to the entire station. The 180kW generator would be capable of sustaining the existing 57.5 kW load (46kW demand + 25% per CEC Article 220.87) and have sufficient capacity for future EV chargers.
Assuming the Hose Tower room construction meets code, locate the new generator in the Hose Tower room in place of the removed generator and connect the new generator to the existing fuel lines. The fuel lines must be verified as being capable of providing the required fuel to the generator. Upgrade the ventilation system as required to meet the requirements of the new generator.
Locate the new ATS in the generator room and provide required interconnection between the ATS and the new switchboard, and the ATS and the generator.
Should the City decide not to provide stand-by power for the entire station and opt to maintain the current partial station stand-by power model, the minimum size of the new generator should be no less than 100kW, to match existing, and consideration should be given to increasing the size of the emergency power panel from 225A. to 400A. to ensure the station can accesses the full 347 Amps output of the new generator and accommodate the installation of future truck/apparatus electric vehicle chargers.
Where the current emergency power configuration is maintained, receptacles connected to emergency circuits must be replaced with “red” devices and wall plates. The serving panel and circuit number should be engraved on the wall plate.
Communications:
Construct a communications room or convert the Storage room, currently housing the various communications and alarm systems, into a communications room to house the base radio, alerting system head-end equipment, telephone equipment, CATV equipment and data/network equipment. Converting the Storage room into a communications room would minimize or eliminate the need to rewire the station outlets to terminate the systems cables at the new communications room.
Provide a new alerting system to work in conjunction with the base radio.
Relocate wall mounted telephone outlets as required to meet the ADA mounting height requirements.
Provide a 911 phone at the front of the station.
Rework the CATV service cabling to provide physical protection for the aboveground cable run. Contact the CATV company to discuss available options.
Provide additional ceiling mounted wireless access points (WAP) to ensure complete station coverage.
Palm Desert Fire Station 33 & 71 Assessments Page 70
371
A&F ENGINEERING GROUP, INC.
9320 BASELINE RD. SUITE C, RANCHO CUCAMONGA, CA 91701, Tel (909) 941-3008, Fax (909) 941-8211
Electrical Systems Assessment
Riverside Co. Fire, Station #33
Palm Desert, CA
Provide single station smoke detectors in the dorm rooms. Provide combination CO/smoke detectors in the corridors leading to the dorms. The detectors must be interconnected to ensure the audible device in all smoke and combination CO/smoke detectors activate whenever one detector in the system goes into alarm.
For areas accessible to the public, add a manual pull station at the exit door, a combination horn/strobe in the lobby, a strobe in the restroom, and a control panel to supervise the devices.
Please call if you have questions or require additional information.
Sincerely,
Luis E. Flores
Principal
Palm Desert_FS#33_Assessment.doc
Palm Desert Fire Station 33 & 71 Assessments Page 71
372
Palm Desert Fire Station 33 & 71 Assessments
4.0 Existing Building Evaluations
The following pages provide the existing building evaluations completed by the structural, mechanical/plumbing and electrical engineers.
ADA ASSESSMENT REPORT
FIRE STATION NO.33 Palm Desert Fire Station 33 & 71 Assessments Page 36 Page 72 373
Accessibility Report
Prepared By
Fire Station # 33
44-400 Town Center Way
Palm Desert, CA 92260
Date of Inspection
8/22/2018
Disability Access Consultants, LLC
City of Palm Desert
Palm Desert Fire Station 33 & 71 Assessments Page 73
374
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 429466
The access aisle does not contain the wording
"No Parking" painted in white letters within the
access aisle.
Paint the words "NO PARKING" a compliant
height within the access aisle.
CA 11B- 502.3
Parking Lot
Accessible Space
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Parking : Access Aisle - "No Parking"
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 2 of 61 Palm Desert Fire Station 33 & 71 Assessments 375
Finding
On-Site Finding Not Found
Recommendation
Code Reference
Record Number 429465
There is no minimum fine sign at the parking
space.
Provide a minimum fine sign at the parking
space below the International Symbol of
Accessibility.
CA 11B- 502.6
Parking Lot
Accessible Space
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Parking : Parking Lot Warnings
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 3 of 61 Palm Desert Fire Station 33 & 71 Assessments 376
Finding
On-Site Finding Faded or Damaged
Recommendation
Code Reference
Record Number 510081
The accessible parking space outline is faded,
damaged, missing or otherwise not viewable.
Re-stripe the existing parking space marked as
accessible to define the width of the space.
ADA 502, 502.2, CA 11B-502.2
Parking Lot
Accessible Space
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Parking : Outline is Faded, Damaged or Missing
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 4 of 61 Palm Desert Fire Station 33 & 71 Assessments 377
Finding
On-Site Finding Not Found
Recommendation
Code Reference
Record Number 429498
The curb ramp does not provide a detectable
warning surface which includes truncated
domes.
Provide compliant detectable warnings to
surface.
CA 11B- 406.5
Curb Ramp at the Access Aisle
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Curb Ramps : Detectable Warnings
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 5 of 61 Palm Desert Fire Station 33 & 71 Assessments 378
Finding
On-Site Finding 22.40 percent
Recommendation
Recommendation Up to 10.00 percent
Code Reference
Record Number 429499
The slope of the curb ramp left side flare is
greater than allowed.
Provide curb ramp side flares with a compliant
slope.
ADA 406.3, CA 11B-406.2
Curb Ramp at the Access Aisle
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Curb Ramps : Left Side Flare Slope
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 6 of 61 Palm Desert Fire Station 33 & 71 Assessments 379
Finding
On-Site Finding Not Beveled
Recommendation
Code Reference
Record Number 429500
The transition from the bottom of the curb
ramp to the walk, gutter, or street is abrupt.
Patch the transition area at the bottom of the
curb ramp so that the transition is flush and
free of abrupt changes.
ADA 406.2, CA 11B-406.5
Curb Ramp at the Access Aisle
Bottom Landing
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Curb Ramps : Bottom Landing Change in Level - Curb Ramps Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 7 of 61 Palm Desert Fire Station 33 & 71 Assessments 380
Finding
On-Site Finding 0.50 inches
Recommendation
Recommendation Up to 0.25 inches
Code Reference
Record Number 429529
There is a change in elevation greater than
recommended value.
Ensure that the change in elevation is within
the recommended value.
ADA 303, 403.4, CA 11B-303,403.4
Walkway from the Accessible Spaces
Change in Level
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Path of Travel : Change in Level
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 8 of 61 Palm Desert Fire Station 33 & 71 Assessments 381
Finding
On-Site Finding 30.00 inches
Recommendation
Recommendation Up to 4.00 inches
Code Reference
Record Number 429530
The leading edge of the item protrudes into the
circulation route greater than permitted.
Install side extensions, modify, relocate, or
lower the item so that it is not a protruding
object into the circulation route.
ADA 307, 307.2, CA 11B-307.2
Walkway from the Accessible Spaces
Vegetation
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Path of Travel : Protruding Objects - Protrusion Limit
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 9 of 61 Palm Desert Fire Station 33 & 71 Assessments 382
Finding
On-Site Finding 2.70 percent for 14.00 feet
Recommendation
Recommendation Up to 2.08 percent
Code Reference
Record Number 429527
There are cross slopes greater than allowed on
the primary path of travel.
Provide a compliant path of travel.
ADA 402, 403.3, CA 11B-403.3
Walkway from the Accessible Spaces
Exterior Walkway
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Path of Travel : Walking Surface Cross Slope
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 10 of 61 Palm Desert Fire Station 33 & 71 Assessments 383
Finding
On-Site Finding 47.00 inches
Recommendation
Recommendation At least 48.00 inches
Code Reference
Record Number 429528
The width of the path of travel is insufficient.
Widen the primary path of travel to provide the
correct width.
ADA 403.5, CA 11B-403.5
Walkway from the Accessible Spaces
Exterior Walkway
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Path of Travel : Sidewalk Width
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 11 of 61 Palm Desert Fire Station 33 & 71 Assessments 384
Finding
On-Site Finding 5.50 inches
Recommendation
Recommendation Up to 0.50 inches
Code Reference
Record Number 429494
The height of the threshold at the entrance
door is greater than allowed.
Modify or replace the threshold to provide the
recommended height.
ADA 404, 404.2, CA 11B-404.2
Apparatus Bay
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Door Threshold
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 12 of 61 Palm Desert Fire Station 33 & 71 Assessments 385
Finding
On-Site Finding 5.75 inches
Recommendation
Recommendation At least 18.00 inches
Code Reference
Record Number 429496
There is less than the required latch side
clearance on the pull side of the door.
Provide required latch side clearance on the
pull side of the door.
ADA 404, 404.2, CA 11B-404.2
Apparatus Bay
Pull Side
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Front Approach Latch Side Clearance
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 13 of 61 Palm Desert Fire Station 33 & 71 Assessments 386
Finding
On-Site Finding Not Compliant
Recommendation
Code Reference
Record Number 429497
An unstable floor mat is provided at the door
landing.
Provide a compliant floor mat for the door.
ADA 403.2, 302.1, CA 11B-302.1,403.2
Apparatus Bay
Pull Side
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Floor Mat
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 14 of 61 Palm Desert Fire Station 33 & 71 Assessments 387
Finding
On-Site Finding 6.25 inches
Recommendation
Recommendation At least 12.00 inches
Code Reference
Record Number 429495
There is less than the required latch side
clearance on the push side of the door.
Provide the recommended latch side clearance
on the push side of the door.
ADA 404, 404.2, 404.2, CA 11B-404.2
Apparatus Bay
Push Side
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Front Approach Latch Side Clearance
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 15 of 61 Palm Desert Fire Station 33 & 71 Assessments 388
Finding
On-Site Finding Found
Recommendation
Code Reference
Record Number 429511
Has a door stop.
Remove the door stop.
ADA 404, 404.2, CA 11B-404.2
Kitchen Entrance
None
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Door Hardware
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 16 of 61 Palm Desert Fire Station 33 & 71 Assessments 389
Finding
On-Site Finding 0.37 inches
Recommendation
Code Reference
Record Number 429512
The height of the threshold at the entrance
door is greater than allowed for a vertical rise.
Modify or replace the threshold to provide the
recommended height.
ADA 404, 404.2, CA 11B-404.2
Kitchen Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Door Threshold
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 17 of 61 Palm Desert Fire Station 33 & 71 Assessments 390
Finding
On-Site Finding Not Found
Recommendation
Code Reference
Record Number 510084
Door hardware is broken or missing.
Provide compliant accessible door hardware.
ADA 404.2, CA 11B-404.2
Kitchen Entrance
None
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Hardware
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 18 of 61 Palm Desert Fire Station 33 & 71 Assessments 391
Finding
On-Site Finding 14.00 pounds
Recommendation
Recommendation Up to 5.00 pounds
Code Reference
Record Number 429507
The door opening force for this door is greater
than allowed.
Adjust the closer on the door to meet the door
opening force requirements.
ADA 404.2, CA 11B-404.2
Main Entrance
Lever
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Door Opening Pressure
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 19 of 61 Palm Desert Fire Station 33 & 71 Assessments 392
Finding
On-Site Finding 0.87 inches
Recommendation
Recommendation Up to 0.50 inches
Code Reference
Record Number 429508
The height of the threshold at the entrance
door is greater than allowed.
Modify or replace the threshold to provide the
recommended height.
ADA 404, 404.2, CA 11B-404.2
Main Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Door Threshold
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 20 of 61 Palm Desert Fire Station 33 & 71 Assessments 393
Finding
On-Site Finding Not Compliant
Recommendation
Code Reference
Record Number 429509
An unstable floor mat is provided at the door
landing.
Provide a compliant floor mat for the door.
ADA 403.2, 302.1, CA 11B-302.1,403.2
Main Entrance
Push Side
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Floor Mat
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 21 of 61 Palm Desert Fire Station 33 & 71 Assessments 394
Finding
On-Site Finding Not Accessible
Recommendation
Code Reference
Record Number 429463
The door lock requires tight grasping, pinching,
or twisting of the wrist to operate.
Provide a compliant door lock for the door that
does not require tight grasping, pinching, or
twisting of the wrist to operate.
ADA 404.2, 309.4
Office Next to Captains
Lever
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Door Lock
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 22 of 61 Palm Desert Fire Station 33 & 71 Assessments 395
Finding
On-Site Finding 15.00 pounds
Recommendation
Recommendation Up to 5.00 pounds
Code Reference
Record Number 429489
The door opening force for this door is greater
than allowed.
Adjust the closer on the door to meet the door
opening force requirements.
ADA 404.2, CA 11B-404.2
Patio Door
Lever
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Door Opening Pressure
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 23 of 61 Palm Desert Fire Station 33 & 71 Assessments 396
Finding
On-Site Finding 1.00 inches
Recommendation
Recommendation Up to 0.50 inches
Code Reference
Record Number 429490
The height of the threshold at the entrance
door is greater than allowed.
Modify or replace the threshold to provide the
recommended height.
ADA 404, 404.2, CA 11B-404.2
Patio Door
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Door Threshold
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 24 of 61 Palm Desert Fire Station 33 & 71 Assessments 397
Finding
On-Site Finding 6.00 inches
Recommendation
Recommendation At least 12.00 inches
Code Reference
Record Number 429491
There is less than the required latch side
clearance on the push side of the door.
Provide the recommended latch side clearance
on the push side of the door.
ADA 404, 404.2, CA 11B-404.2
Patio Door
Push Side
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Front Approach Latch Side Clearance
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 25 of 61 Palm Desert Fire Station 33 & 71 Assessments 398
Finding
On-Site Finding Not Compliant
Recommendation
Code Reference
Record Number 429492
An unstable floor mat is provided at the door
landing.
Provide a compliant floor mat for the door.
ADA 403.2, 302.1, CA 11B-302.1,403.2
Patio Door
Push Side
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Floor Mat
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 26 of 61 Palm Desert Fire Station 33 & 71 Assessments 399
Finding
On-Site Finding 0.50 inches
Recommendation
Recommendation At least 18.00 inches
Code Reference
Record Number 510083
There is less than the required latch side
clearance on the pull side of the door.
Provide required latch side clearance on the
pull side of the door.
ADA 404, 404.2, CA 11B-404.2
Reception
Pull Side
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Front Approach Latch Side Clearance
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 27 of 61 Palm Desert Fire Station 33 & 71 Assessments 400
Finding
On-Site Finding 42.00 inches
Recommendation
Recommendation 28.00 - 34.00 inches
Code Reference
Record Number 429696
The height of the counter or desk does not
comply with height requirements.
Provide a portion of counter at the compliant
height.
ADA 902, 904, CA 11B-904.4
Reception Counter
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Counters - Interior : Counter Height
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 28 of 61 Palm Desert Fire Station 33 & 71 Assessments 401
Finding
On-Site Finding 40.37 inches
Recommendation
Recommendation 28.00 - 34.00 inches
Code Reference
Record Number 429493
The height of the counter or desk does not
comply with height requirements.
Provide a portion of counter at the compliant
height.
ADA 902, 904, CA 11B-904.4
Window Counter
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Counters - Interior : Counter Height
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 29 of 61 Palm Desert Fire Station 33 & 71 Assessments 402
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 429484
There is no compliant room identification
signage provided.
Install compliant room identification signage.
ADA 703, 216, 216.2, CA 11B-216.2
Apparatus Bay
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Signage - Interior : Room Identification
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 30 of 61 Palm Desert Fire Station 33 & 71 Assessments 403
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 429477
There is no compliant room identification
signage provided.
Install compliant room identification signage.
ADA 703, 216, 216.2, CA 11B-216.2
Captains Office
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Signage - Interior : Room Identification
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 31 of 61 Palm Desert Fire Station 33 & 71 Assessments 404
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 429515
There is no compliant room identification
signage provided.
Install compliant room identification signage.
ADA 703, 216, 216.2, CA 11B-216.2
Conference Room
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Signage - Interior : Room Identification
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 32 of 61 Palm Desert Fire Station 33 & 71 Assessments 405
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 429486
There is no directional signage.
Install directional signage to each accessible
element or room.
ADA 703, 216, 216.3, CA 11B-216.3, 703.5,703.5
Directional Signage From The Public Right Of Way
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Signage : Directional or Information Signage
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 33 of 61 Palm Desert Fire Station 33 & 71 Assessments 406
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 429514
There is no compliant room identification
signage provided.
Install compliant room identification signage.
ADA 703, 216, 216.2, CA 11B-216.2
Kitchen Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Signage - Interior : Room Identification
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 34 of 61 Palm Desert Fire Station 33 & 71 Assessments 407
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 429480
There is no room signage.
Install accessible room signage.
ADA 216.2, 216.6, CA 11B-216.2,216.6
Main Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Signage - Interior : Accessible Element/Entrance Signage Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 35 of 61 Palm Desert Fire Station 33 & 71 Assessments 408
Finding
On-Site Finding Not Found
Recommendation
Code Reference
Record Number 510085
There is no informational signage.
Install informational signage to each accessible
element or room or location.
ADA 216.3, CA 11B-216.3, 703.5,703.5
Main Entrance Doorbell
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Signage - Interior : Information Signage
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 36 of 61 Palm Desert Fire Station 33 & 71 Assessments 409
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 429485
There is no compliant room identification
signage provided.
Install compliant room identification signage.
ADA 703, 216, 216.2, CA 11B-216.2
Office Next to Captain
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Signage - Interior : Room Identification
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 37 of 61 Palm Desert Fire Station 33 & 71 Assessments 410
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 429517
There is no room signage.
Install accessible room signage.
ADA 216.2, 216.6, CA 11B-216.2,216.6
Patio Door
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Signage - Interior : Accessible Element/Entrance Signage Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 38 of 61 Palm Desert Fire Station 33 & 71 Assessments 411
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 429483
There is no compliant room identification
signage provided.
Install compliant room identification signage.
ADA 703, 216, 216.2, CA 11B-216.2
Reception Office
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Signage - Interior : Room Identification
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 39 of 61 Palm Desert Fire Station 33 & 71 Assessments 412
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 429481
There is no compliant room identification
signage provided.
Install compliant room identification signage.
ADA 703, 216, 216.2, CA 11B-216.2
TV Room
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Signage - Interior : Room Identification
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 40 of 61 Palm Desert Fire Station 33 & 71 Assessments 413
Finding
On-Site Finding 17.50 inches on center
Recommendation
At least 18.00 inches on
center
Recommendation
Code Reference
Record Number 429473
The lavatory center line does not meet the
minimum required distance when located
adjacent to a side wall, partition or fixture.
Replace or remount lavatory to meet the
minimum required distance to the center line
of the fixture, when located adjacent to a side
wall or partition.
Notes : Supply Lines Not Completely Wrapped.
CA 11B- 606.6
Unisex Restroom
Lavatory
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Lavatory Distance From Wall/Fixture Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 41 of 61 Palm Desert Fire Station 33 & 71 Assessments 414
Finding
On-Site Finding Not Wrapped
Recommendation
Code Reference
Record Number 429474
The supply lines under the lavatory do not
provide protection against contact.
Insulate or otherwise configure pipes under
the lavatory to protect against contact. Make
certain there are no sharp or abrasive surfaces
under the lavatory.
Notes : Supply Lines Not Completely Wrapped.
ADA 213, 606, 606.5, CA 11B-606.5
Unisex Restroom
Lavatory
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Lavatory - Supply Lines Wrapping Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 42 of 61 Palm Desert Fire Station 33 & 71 Assessments 415
Finding
On-Site Finding 49.50 inches
Recommendation
Recommendation Up to 40.00 inches
Code Reference
Record Number 429471
The height of the controls and operating
mechanisms for the dispenser is not at the
correct height.
Relocate the dispenser to the correct height.
ADA 309, 205, 308, 606, 308.1, CA 11B-603.5
Unisex Restroom
Paper Towel
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Dispenser Height
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 43 of 61 Palm Desert Fire Station 33 & 71 Assessments 416
Finding
On-Site Finding 41.00 inches
Recommendation
Recommendation Up to 40.00 inches
Code Reference
Record Number 429472
The height of the controls and operating
mechanisms for the dispenser is not at the
correct height.
Relocate the dispenser to the correct height.
ADA 309, 205, 308, 606, 308.1, CA 11B-603.5
Unisex Restroom
Soap
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Dispenser Height
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 44 of 61 Palm Desert Fire Station 33 & 71 Assessments 417
Finding
On-Site Finding 49.50 inches
Recommendation
Recommendation Up to 40.00 inches
Code Reference
Record Number 429475
The bottom edge of the reflective surface of
the mirror is not at the correct height.
Lower the mirror so the bottom edge of the
reflective surface is no higher than
recommended above the finished floor.
ADA 603, 213, 603.3, CA 11B-603.3
Unisex Restroom
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Mirror Bottom Edge Height
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 45 of 61 Palm Desert Fire Station 33 & 71 Assessments 418
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 429476
There is no compliant signage indicating
accessibility on the latch side of the entry door
of the restroom.
Provide compliant signage on latch side of
door.
ADA 703, 216, 216.8, CA 11B-216.8
Unisex Restroom
Wall Sign
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Wall Signage
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 46 of 61 Palm Desert Fire Station 33 & 71 Assessments 419
Finding
On-Site Finding Wrong Side of Toilet
Recommendation
Code Reference
Record Number 429503
The flush control on the toilet is not on the
wide (approach) side of the toilet.
Relocate the flush control so it is on the wide
(approach) side of the toilet area. Flush
controls shall be hand-operated or automatic
mechanisms.
ADA 603, 604.6, CA 11B-604.6
Unisex Restroom
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Toilet Flush Control - Wide Side Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 47 of 61 Palm Desert Fire Station 33 & 71 Assessments 420
Finding
On-Site Finding 47.62 inches
Recommendation
Recommendation At least 48.00 inches
Code Reference
Record Number 429504
There is less than the required minimum space
in front of the toilet.
Create the required minimum clear space in
front of the toilet.
ADA 603, CA 11B-604.8
Unisex Restroom
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Toilet Clear Floor Space
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 48 of 61 Palm Desert Fire Station 33 & 71 Assessments 421
Finding
On-Site Finding 10.00 inches
Recommendation
Recommendation 7.00 - 9.00 inches
Code Reference
Record Number 429505
The location of the toilet paper dispenser is not
within the required distance from the front
edge of the toilet seat.
Remount the toilet paper dispenser at a
compliant height and location.
ADA 603, 604.7, CA 11B-604.7,309.4
Unisex Restroom
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Toilet Paper Dispenser Distance From Seat Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 49 of 61 Palm Desert Fire Station 33 & 71 Assessments 422
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 429469
The restroom door does not provide a
compliant privacy lock with occupancy
indicator.
Install a compliant privacy lock with occupancy
indicator to the door.
ADA 213, 213.2, CA 11B-213.2
Unisex Restroom
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Door Privacy Lock and Occupied Indicator Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 50 of 61 Palm Desert Fire Station 33 & 71 Assessments 423
Finding
On-Site Finding 50.50 inches
Recommendation
Recommendation At least 60.00 inches
Code Reference
Record Number 429470
There is not sufficient clear floor space in the
restroom to accommodate an individual in a
wheelchair.
Modify the restroom to provide sufficient clear
floor space for a turning radius in the restroom
to accommodate an individual in a wheelchair.
ADA 603, 304, 304.3, 603.2, 304.3, 603.2, CA 11B-304.3
Unisex Restroom
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Circular Turning Space Diameter
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 51 of 61 Palm Desert Fire Station 33 & 71 Assessments 424
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 429501
There are no grab bars.
Install the required grab bars in the toilet
compartment.
ADA 603, 609, 604.5, CA 11B-604.5
Unisex Restroom
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Grab Bars
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 52 of 61 Palm Desert Fire Station 33 & 71 Assessments 425
Finding
On-Site Finding 16.00 inches
Recommendation
Recommendation At least 19.00 inches
Code Reference
Record Number 510082
The table knee depth does not meet required
standards.
Provide compliant tables.
ADA 306, 902, CA 11B-306,902
Conference Room
Table
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Break/Conference Room - Interior : Tables - Knee Depth
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 53 of 61 Palm Desert Fire Station 33 & 71 Assessments 426
Finding
On-Site Finding 3.20 percent
Recommendation
Recommendation Up to 2.08 percent
Code Reference
Record Number 429479
The slope of the clear floor space at the table is
not compliant.
Provide compliant clear floor space at the
table.
ADA 305.3, 902.2, CA 11B-305.2
Picnic Table
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Picnic Areas : Clear Floor Space Slope
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 54 of 61 Palm Desert Fire Station 33 & 71 Assessments 427
Finding
On-Site Finding 61.00 inches
Recommendation
Recommendation 15.00 - 48.00 inches
Code Reference
Record Number 429482
The highest point of operation for the element
is not compliant.
Make sure that the highest point of operation
is within the recommended value.
ADA 309, 308, CA 11B-308,309
Main Entrance
Doorbell - Other
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Reach Ranges - Interior : Element Highest Point of Operation Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 55 of 61 Palm Desert Fire Station 33 & 71 Assessments 428
Finding
On-Site Finding 37.37 inches
Recommendation
Recommendation Up to 34.00 inches
Code Reference
Record Number 429522
Sink counter height does not meet the
standards.
Provide compliant sink.
ADA 904, CA 11B-606.3
Kitchen
Sink - Lever
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Kitchens - Interior : Counter Height
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 56 of 61 Palm Desert Fire Station 33 & 71 Assessments 429
Finding
On-Site Finding Not Wrapped
Recommendation
Code Reference
Record Number 429523
The pipes are not wrapped for the sink.
Insulate or otherwise configure the water
supply and drain pipes under the sink to
protect against contact. Make certain there are
no sharp or abrasive surfaces under the sink.
ADA 606.5, CA 11B-606.5
Kitchen
Sink - Lever
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Kitchens - Interior : Pipes Wrapping
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 57 of 61 Palm Desert Fire Station 33 & 71 Assessments 430
Finding
On-Site Finding Not Removed
Recommendation
Code Reference
Record Number 429524
The toe kick for the sink in kitchen is not
removed.
Remove the toe kick for the sink.
ADA 305, 606.2, CA 11B-606.2,305,306
Kitchen
Sink - Lever
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Kitchens - Interior : Toe Kick - Removed
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 58 of 61 Palm Desert Fire Station 33 & 71 Assessments 431
Finding
On-Site Finding Not Wrapped
Recommendation
Code Reference
Record Number 429525
Supply lines are not wrapped for the kitchen
sink.
Make sure that the supply lines are fully
wrapped and insulated for the sink.
ADA 606.5, CA 11B-606.5
Kitchen
Sink - Lever
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Kitchens - Interior : Supply Lines
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 59 of 61 Palm Desert Fire Station 33 & 71 Assessments 432
Finding
On-Site Finding 25.75 inches
Recommendation
Recommendation At least 27.00 inches
Code Reference
Record Number 429526
The table knee clearance does not meet
required standards.
Provide compliant table.
CA 11B- 902.2,306
Kitchen
Table
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Kitchens - Interior : Table - Knee Clearance
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 60 of 61 Palm Desert Fire Station 33 & 71 Assessments 433
Palm Desert Fire Station 33 & 71 Assessments
4.0 Existing Building Evaluations
The following pages provide the existing building evaluations completed by the structural, mechanical/plumbing and electrical engineers.
ADA ASSESSMENT REPORT
FIRE STATION NO.33 Palm Desert Fire Station 33 & 71 Assessments Page 133 434
Prepared By Prepared Using
Fire Station # 33
44-400 Town Center Way
Palm Desert, CA 92260
Date of Inspection
8/22/2018
Disability Access Consultants, LLC
Fire Station # 33
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 61 of 61 Palm Desert Fire Station 33 & 71 Assessments 435
Palm Desert Fire Station 33 & 71 Assessments
4.0 Existing Building Evaluations
The following pages provide the existing building evaluations completed by the structural, mechanical/plumbing and electrical engineers.
STRUCTURAL/MECHANICAL/PLUMBING AND ELECTRICAL
FIRE STATION NO.71 Palm Desert Fire Station 33 & 71 Assessments Page 132 Page 135 436
1047 W. 6th Street, Ontario, CA 91762 • P 626.664.0092
Sacramento • San Francisco • San Jose • Pleasanton • Los Angeles • Ontario • Orange County • San Diego • Reno • Las Vegas • Phoenix • Washington, D.C. Puerto Rico • Mexico • Costa Rica • Colombia • Haiti • Italy • Turkey • Uzbekistan • India • Nepal • Thailand • Indonesia • Japan • New Zealand July 3, 2023
Mr. Kelley Needham,
PBK Architects
8163 Rochester Ave, Suite 100
Subject: Palm Desert Fire Station 71 Seismic Assessment Country Club Drive and Portola Ave
Palm Desert, CA
MI2228116
Dear Mr. Needham,
Per the request of PBK, our firm has performed a seismic assessment for the existing Palm Desert Fire Station 71. The assessment included a review of available as-built documents, a preliminary ASCE 41 evaluation and a field visitation, performed March 3, 2023. The filed visitation was provided to visually verify accessible structural components.
The as-built documents provided, where limited in completeness as it pertains to the original Structural design. The documents included:
1985 Original Building Plans - Sheets A1, A3, and M1.
John Outcault Architect, Palm Desert
2018 Plans, Enlargement of App Bay Doors – Sheets S1, S1.1, S1.2, S2- S5 Structural Calculations pertaining to the added Moment Frame BG Structural Engineering, Brian Gottlieb, Civil Engineer, Palm Desert
1.0 Project Description
The facility is a single-story building of approximately 5500 square feet, with a conventional wood frame system. The building utilizes a plywood horizontal diaphragm and plywood shearwall lateral system. The system is reasonably regular, possesses an apparent logical lateral load path. The original 1985 plywood shearwall layout is as identified Figure 1. The shearwall designations are indicated on the plan, but referenced to Sheet A6, which was not made available.
The 2018 Moment Frame added at the Apparatus Bay Door, is shown in Figure 2.
Roof framing at the low roof over Eastern side of the facility were visually verified as 2 x rafters at 24” o.c.
Visual verification was possible above the suspended ceiling for this portion, with the plywood shearwalls evident on the exterior walls and the East and North corridor walls as highlighted in Figure 1.
The roof over the Apparatus Bay is apparently framed with open web wood chord trusses, as indicated on the 2018 framing plan for the Apparatus Bay widening project (Figure 2) This was not able to be independently verified due to the hard lid ceilings, and the absence of a roof framing plan in the As-Built Documents.
The foundation system is concrete slab on grade with an assumed conventional used of concrete cast in place continuous and pad footings.
437
Figure 1 Plywood Shearwall Identification
438
Figure 2 Moment Frame at Enlarged Apparatus Bay Door
439
Figure 3 Seismic Key Plan with Identifying Gridlines
440
1.1 Codes and References
The Document preparation date of 1985 for the original construction, would suggest the potential use of the 1982 Uniform Building Code, but adoption of that edition of the UBC was irregular between Jurisdictions, and it is likely that the facility was designed under the 1979 Uniform Building Code. There was no identification of the utilized code identified on the few available as-built documents during our review.
The Apparatus Bay door enlargement project, prepared by BG Structural Engineering, was designed under the guidelines of the 2016 California Building Code, and includes current and applicable code criteria.
The ASCE 41-17, Seismic Evaluation and Retrofit of Existing Buildings is utilized as the reference document for the Evaluation. Due to the Essential Facility status, Occupancy Category IV, the Benchmark date for the building is set from Table 3.2, which stipulates a benchmark date of 1998.
Benchmark dates are the code threshold to where a building is deemed to comply. The Benchmark date is after the Code date of either 1979, 0r 1982.
The evaluation methodology utilized is Basic Performance Objective Equivalent to New Building Standards. (BPON), Category IV, Immediate Occupancy. The ASCE 41 Tier 1 (Seismic Review) checklist may be found in enclosure 2.
2.0 Design Results and Identified Deficiencies
The ASCE 41-17 BPON seismic base shear values yields values noted below: (Ref calculations Attachment 1)
See the Shearwall Key Plan in Figure 3
V=.20 ASD Plywood Shearwall R = 6.5
V= .37 ASD Moment Frame Direction R = 3.5
R= Response modification factor, a value used in the base shear derivation with consideration to the expected performance of the chosen system. R 3.5 (Ordinary Moment Frame) results in a base shear 87% higher than the plywood shearwall base shear.
The 2018 Moment Frame addition created a non-compliant issue with the introduction of the Ordinary Moment Frame on the South Apparatus Bay door. The code requires (ASCE 12.2.3.3) the lower R value to be used for the systems in that “same direction”. The North end of the building is subject to the increased base shear due to this requirement. The code exception which permits the treatment of individual lines in the same direction is limited to flexible diaphragms, which is applicable in this case, but also only permitted in Category I and II buildings. A Fire Station is a Category IV Building.
The preliminary analysis performed for our evaluation used the higher R = 6.5 for plywood shearwall as a basis for design. This is comparable to the seismic level of the original construction, and does not initially consider the increase shear generated by the ASCE 12.2.3.3 requirement. These nonconservative results indicate the shearwalls on Gridline 4 and 3, are overstressed. Factoring the shear values generated from the higher base shear associated with R= 3.5, yields a grossly overstressed condition. In this example, the existing condition is over stressed without the additional R value penalty.
In addition, there is no drag component for gridline 4 and 5 from the Apparatus Bay roof to east portion roof, to assure deformation compatibility.
441
2.1 Summary of identified building lateral deficiencies:
• Grid 3, shearwall inadequate, retrofit required
o The repair would include adding additional interior East West shear elements to reduce the demand on grid 3. Potential to add drag tie and transfer load to existing frame.
Rough Order of Magnitude Retrofit Costs (ROM): $50,000
• Grid 4, Shearwall inadequate, retrofit required
o The repair would require the introduction of a New Ordinary Moment Frame on grid 4, similar to the Frame that was added to Grid 5 in 2018
ROM $200,000
• Drag ties required at grids 4 and 5
o ROM $15,000
• Verification of existing conditions and potential retrofit of anchorage, overturning issues, foundations, etc.
o ROM 5500 sf x $60.00 psf $330,000
If possible, providing the missing sheets in the As-built set would be beneficial to the project, and add clarity to square foot seismic upgrade costs. Confirmation of the shearwall overstress levels can be confirmed with additional information.
The ROM costs are estimates of probable cost and do not include the impact to, or replacement of services and finishes required to be removed and replaced during the retrofit. We are not cost estimators, and costs shall be verified by a cost analysis professional.
In addition to the base building review, the non-structural components were visually verified. The nonstructural components include mechanical systems, architectural attachments, cabinets, piping, ceiling systems, etc.
As an essential facility, there are rigid requirements for bracing of these components.
Observed items include:
• HWH is braced, no retrofit requirement (see photo 12) • Suspended ceiling lateral bracing non-conformant, no compression struts. Retrofit (photo 19) • Bracing requirements for Sprinkler piping not met, bracing required. (photo 7) • Generator is bolted to foundation, no retrofit requirement (photo 13) • Roof top mechanical units are not fastened to platform, retrofit required. (photo 14, 16) • Air Compressor is bolted to foundation, no retrofit requirement (photo 15) • Cabinets over 6 feet in height not bolted to wall, attachment required (photo 17, 20, 21,22) • Turnout lockers in App Bay are fastened to wall, no retrofit requirement (photo 18, 19) Photos may be found in Enclosure 3
442
2.2 Commentary on Proposed Remodel Plans
It appears that there is a proposed or potential remodel of the existing facility, and the preliminary Architectural plans indicate the wall on grid 1 and 2, are proposed to receive new openings for the individual dorm facilities. The walls are primary plywood shearwalls, and would require retrofit if openings are created.
The plan reconfiguration required in the remodel will require a seismic upgrade to the existing structure.
All identified seismic upgrade potential retrofit items may be combined into the remodel efforts.
Sincerely,
Miyamoto International, Inc.
Rick Byrd S.E.
Principal
[email protected]
443
CALCULATIONS
ENCLOSURE 1 Page 143
444
Country Club Dr & Portola Ave, Palm Desert, CA 92260, USA Latitude, Longitude: 33.7579166, -116.3737299
Date 7/20/2023, 4:53:50 PM
Design Code Reference Document ASCE7-16
Risk Category IV
Site Class D - Default (See Section 11.4.3)
Type Value Description
SS 1.557 MCER ground motion. (for 0.2 second period)
S1 0.64 MCER ground motion. (for 1.0s period)
SMS 1.868 Site-modified spectral acceleration value
SM1 null -See Section 11.4.8 Site-modified spectral acceleration value SDS 1.245 Numeric seismic design value at 0.2 second SA SD1 null -See Section 11.4.8 Numeric seismic design value at 1.0 second SA Type Value Description
SDC null -See Section 11.4.8 Seismic design category
Fa 1.2 Site amplification factor at 0.2 second
Fv null -See Section 11.4.8 Site amplification factor at 1.0 second PGA 0.682 MCEG peak ground acceleration
FPGA 1.2 Site amplification factor at PGA
PGAM 0.818 Site modified peak ground acceleration
TL 8 Long-period transition period in seconds
SsRT 1.896 Probabilistic risk-targeted ground motion. (0.2 second) SsUH 2.085 Factored uniform-hazard (2% probability of exceedance in 50 years) spectral acceleration SsD 1.557 Factored deterministic acceleration value. (0.2 second) S1RT 0.733 Probabilistic risk-targeted ground motion. (1.0 second) S1UH 0.822 Factored uniform-hazard (2% probability of exceedance in 50 years) spectral acceleration.
S1D 0.64 Factored deterministic acceleration value. (1.0 second) PGAd 0.682 Factored deterministic acceleration value. (Peak Ground Acceleration) PGAUH 0.825 Uniform-hazard (2% probability of exceedance in 50 years) Peak Ground Acceleration CRS 0.909 Mapped value of the risk coefficient at short periods CR1 0.892 Mapped value of the risk coefficient at a period of 1 s CV 1.411 Vertical coefficient
445
Figure 3 Seismic Key Plan Page 145
446
447
448
449
450
Legend: C = Compliant, NC = Noncompliant, N/A = Not Applicable, U = Unknown © 2014 American Society of Civil Engineers 1 Rev. 41-31.1 Project Name
Project Number
ASCE 41-13 Tier 1 Checklists
FIRM:
PROJECT NAME:
SEISMICITY LEVEL:
PROJECT NUMBER:
COMPLETED BY:
DATE COMPLETED:
REVIEWED BY:
REVIEW DATE:
ENCLOSURE 2
Palm Desert FS #71 MI2822116 Miyamoto International Palm Desert FS #71 BPON MI2822116 Byrd 7-3-2023 451
Legend: C = Compliant, NC = Noncompliant, N/A = Not Applicable, U = Unknown © 2014 American Society of Civil Engineers 2 Rev. 41-31.1 Project Name
Project Number
16.2IO Immediate Occupancy Structural Checklist for Building Types W1: Wood Light Frames and W1A: Multi-Story, Multi-Unit Residential Wood Frame Very Low Seismicity
Seismic-Force-Resisting System
RATING DESCRIPTION COMMENTS
C NC N/A U REDUNDANCY: The number of lines of shear walls in each principal direction is greater than or equal
to 2. (Commentary: Sec. A.3.2.1.1. Tier 2: Sec.
5.5.1.1)
C NC N/A U SHEAR STRESS CHECK: The shear stress in the
shear walls, calculated using the Quick Check
procedure of Section 4.5.3.3, is less than the
following values (Commentary: Sec. A.3.2.7.1. Tier
2: Sec. 5.5.3.1.1):
Structural panel sheathing 1,000 lb/ft
Diagonal sheathing 700 lb/ft
Straight sheathing 100 lb/ft
All other conditions 100 lb/ft
C NC N/A U STUCCO (EXTERIOR PLASTER) SHEAR WALLS:
Multi-story buildings do not rely on exterior
stucco walls as the primary seismic-force-resisting
system. (Commentary: Sec. A.3.2.7.2. Tier 2: Sec.
5.5.3.6.1)
C NC N/A U GYPSUM WALLBOARD OR PLASTER SHEAR
WALLS: Interior plaster or gypsum wallboard are
not used as shear walls on buildings more than
one story high with the exception of the
uppermost level of a multi-story building.
(Commentary: Sec. A.3.2.7.3. Tier 2: Sec. 5.5.3.6.1)
Palm Desert FS #71 MI2822116
See calculations.
BPON calculations indicate over stress on
grids 3 and 4
R = 3.5 for EW direction per 12.2.3.3 ASCE 7
further exacerbates the over stress levels
Plans not all exterior walls to receive 3/8
plywood. Shearwall schedule not included in
as-built documents provided (sheet S6
needed)
Visible plywood shearwalls confirmed,
remainder covered, plan indicate all ext walls
receive 3/8 plywood. Shearwalls indicated on
Architectural plan, but no shearwall schedule
included. Need sheet S6
452
Legend: C = Compliant, NC = Noncompliant, N/A = Not Applicable, U = Unknown © 2014 American Society of Civil Engineers 3 Rev. 41-31.1 Project Name
Project Number
C NC N/A U NARROW WOOD SHEAR WALLS: Narrow wood
shear walls with an aspect ratio greater than 2-
to-1 are not used to resist seismic forces.
(Commentary: Sec. A.3.2.7.4. Tier 2: Sec. 5.5.3.6.1)
C NC N/A U WALLS CONNECTED THROUGH FLOORS: Shear
walls have an interconnection between stories to
transfer overturning and shear forces through the
floor. (Commentary: Sec. A.3.2.7.5. Tier 2:
Sec.5.5.3.6.2)
C NC N/A U HILLSIDE SITE: For structures that are taller on at least one side by more than one-half story
because of a sloping site, all shear walls on the
downhill slope have an aspect ratio less than 1 to
2. (Commentary: Sec. A.3.2.7.6. Tier 2: Sec.5.5.3.6.3)
C NC N/A U CRIPPLE WALLS: Cripple walls below first-floorlevel shear walls are braced to the foundation with wood structural panels. (Commentary: Sec.
A.3.2.7.7. Tier 2: Sec. 5.5.3.6.4)
Palm Desert FS #71 MI2822116
Grid 4, NE corner inadequate aspect ratio
453
Legend: C = Compliant, NC = Noncompliant, N/A = Not Applicable, U = Unknown © 2014 American Society of Civil Engineers 4 Rev. 41-31.1 Project Name
Project Number
C NC N/A U OPENINGS: Walls with openings greater than 80% of the length are braced with wood structural
panel shear walls with aspect ratios of not more
than 1.5-to-1 or are supported by adjacent
construction through positive ties capable of
transferring the seismic forces. (Commentary: Sec.
A.3.2.7.8. Tier 2: Sec. 5.5.3.6.5)
Connections
RATING DESCRIPTION COMMENTS
C NC N/A U WOOD POSTS: There is a positive connection of wood posts to the foundation. (Commentary: Sec.
A.5.3.3. Tier 2: Sec. 5.7.3.3)
C NC N/A U WOOD SILLS: All wood sills are bolted to the foundation. (Commentary: Sec. A.5.3.4. Tier 2: Sec.
5.7.3.3)
C NC N/A U GIRDER-COLUMN CONNECTION: There is a
positive connection using plates, connection
hardware, or straps between the girder and the
column support. (Commentary: Sec. A.5.4.1. Tier 2:
Sec. 5.7.4.1)
Palm Desert FS #71 MI2822116
unable to field verify unable to field verify items visible indicate positive connection, not all conditions accessible.
454
Legend: C = Compliant, NC = Noncompliant, N/A = Not Applicable, U = Unknown © 2014 American Society of Civil Engineers 5 Rev. 41-31.1 Project Name
Project Number
Foundation System
RATING DESCRIPTION COMMENTS
C NC N/A U DEEP FOUNDATIONS: Piles and piers are capable of transferring the lateral forces between the
structure and the soil. (Commentary: Sec. A.6.2.3.)
C NC N/A U SLOPING SITES: The difference in foundation
embedment depth from one side of the building
to another shall not exceed one story high.
(Commentary: Sec. A.6.2.4)
Low, Moderate, and High Seismicity
Seismic-Force-Resisting System
RATING DESCRIPTION COMMENTS
C NC N/A U HOLD-DOWN ANCHORS: All shear walls have
hold-down anchors, constructed per acceptable
construction practices, attached to the end studs.
(Commentary: Sec. A.3.2.7.9. Tier 2: Sec. 5.5.3.6.6)
C NC N/A U NARROW WOOD SHEAR WALLS: Narrow wood
shear walls with an aspect ratio greater than 1.5-
to-1 are not used to resist seismic forces.
(Commentary: Sec. A.3.2.7.4. Tier 2: Sec. 5.5.3.6.1)
Palm Desert FS #71 MI2822116
Foundation plan not included in as-builts
documents, Hold downs unable to be verified.
Few instances applicable, grid 4, partial grid 2
455
Legend: C = Compliant, NC = Noncompliant, N/A = Not Applicable, U = Unknown © 2014 American Society of Civil Engineers 6 Rev. 41-31.1 Project Name
Project Number
Diaphragms
RATING DESCRIPTION COMMENTS
C NC N/A U DIAPHRAGM CONTINUITY: The diaphragms are
not composed of split-level floors and do not
have expansion joints. (Commentary: Sec. A.4.1.1.
Tier 2: Sec. 5.6.1.1)
C NC N/A U ROOF CHORD CONTINUITY: All chord elements
are continuous, regardless of changes in roof
elevation. (Commentary: Sec. A.4.1.3. Tier 2: Sec.
5.6.1.1)
C NC N/A U PLAN IRREGULARITIES: There is tensile capacity to develop the strength of the diaphragm at
reentrant corners or other locations of plan
irregularities. (Commentary: Sec. A.4.1.7. Tier 2:
Sec. 5.6.1.4)
C NC N/A U DIAPHRAGM REINFORCEMENT AT OPENINGS:
There is reinforcing around all diaphragm
openings larger than 50% of the building width in
either major plan dimension. (Commentary: Sec.
A.4.1.8. Tier 2: Sec. 5.6.1.5)
Palm Desert FS #71 MI2822116
Drag not provided st grid 4 and 5 Unable to verify
456
Legend: C = Compliant, NC = Noncompliant, N/A = Not Applicable, U = Unknown © 2014 American Society of Civil Engineers 7 Rev. 41-31.1 Project Name
Project Number
C NC N/A U STRAIGHT SHEATHING: All straight sheathed
diaphragms have aspect ratios less than 1-to-1 in
the direction being considered. (Commentary:
Sec. A.4.2.1. Tier 2: Sec. 5.6.2)
C NC N/A U SPANS: All wood diaphragms with spans greater than 12 ft consist of wood structural panels or
diagonal sheathing. (Commentary: Sec. A.4.2.2.
Tier 2: Sec. 5.6.2)
C NC N/A U DIAGONALLY SHEATHED AND UNBLOCKED
DIAPHRAGMS: All diagonally sheathed or
unblocked wood structural panel diaphragms
have horizontal spans less than 30 ft and aspect
ratios less than or equal to 3-to-1 ft. (Commentary:
Sec. A.4.2.3. Tier 2: Sec. 5.6.2)
C NC N/A U OTHER DIAPHRAGMS: The diaphragm does not
consist of a system other than wood, metal deck,
concrete, or horizontal bracing. (Commentary:
Sec. A.4.7.1. Tier 2: Sec. 5.6.5)
Palm Desert FS #71 MI2822116
Unable to verify
457
Legend: C = Compliant, NC = Noncompliant, N/A = Not Applicable, U = Unknown © 2014 American Society of Civil Engineers 8 Rev. 41-31.1 Project Name
Project Number
Connections
RATING DESCRIPTION COMMENTS
C NC N/A U WOOD SILL BOLTS: Sill bolts are spaced at 4 ft or less, with proper edge and end distance provided
for wood and concrete. (Commentary: Sec.
A.5.3.7. Tier 2: Sec. 5.7.3.3)
Palm Desert FS #71 MI2822116
documents not provided, unable to verify
458
Sacramento • San Francisco
www.miyamotointernational.com
• San Jose • Pleasanton • Los Angeles • Ontario • Orange County • San Diego • Reno • Las Vegas • Phoenix • Washington, D.C.
Puerto Rico • Mexico • Costa Rica • Colombia • Haiti • Italy • Ukraine • Turkey • Uzbekistan • Afghanistan • India • Nepal • Thailand • Indonesia • Japan • New Zealand
KEY PLAN
Enclosure 3 PHOTO KEY PLAN PHOTO KEY PLAN 459
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
PHOTOS / ATTACHMENTS
Photo #1
Photo #2
460
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
Photo #3
Photo #4
461
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
Photo #5
Photo #6
462
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
Photo #7
Photo #8
463
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
Photo #9
Photo #10
464
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
Photo #11
Photo #12
465
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
Photo #13
Photo #14
466
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
Photo #15:
Photo #16
467
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
Photo #17
Photo #18
468
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
Photo #19
Photo #20
469
This observation was limited to structural elements exposed to view and accessible during the period of the site visit. Observations by the structural engineer do not constitute a comprehensive review of the project conditions and are not a substitute for general or special inspection requirements. The contractor remains responsible for compliance with the contract documents.
Photo #21
Photo #22
470
Consulting Engineers
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Mechanical and Plumbing Systems Assessment
Palm Desert Fire Station 71
at
73995 Country Club Dr.
Palm Desert, CA 92260
May 17, 2023
Prepared By:
Pocock Design Solutions, Inc.
Andrew Gossman, PE, HFDP, LEED AP BD+C
14451 Chambers, Rd. Ste. 210
Tustin, CA 92780
Palm Desert Fire Station 33 & 71 Assessments Page 170
471
Palm Desert Fire Station 71 May 17, 2023
HVAC and Plumbing Assessment Page 2
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Introduction
Pocock Design Solutions, Inc. has been contracted by PBK Architects to perform an assessment of the existing mechanical and plumbing systems at the Palm Desert Fire Station 71 located at 73995 Country Club Dr., in Palm Desert, CA. The primary purpose of this assessment is to review and document the condition of existing mechanical and plumbing systems, identify apparent non-code-compliant systems, and provide recommendations for future tenant improvements. A site investigation was performed on March 21, 2023.
The facility was reviewed with the following codes:
CBC 2022………………………………………... California Building Code
CMC 2022……………………………………….. California Mechanical Code
CPC 2022……………………………………….. California Plumbing Code
CEC 2022………………………………………. . California Energy Code
CAL Green 2022………………………………… California Green Building Code Existing HVAC Conditions
The fire station is primary conditioned by two (2) rooftop packaged gas/electric a/c units located on the roof in a mechanical well. The units were manufactured in 2006 and 2017 and are in good condition. The unit manufactured in 2006 is nearing the end of its useful life expectancy but the unit manufactured in 2017 has 10+ years of life expectancy remaining. Both units do not have outside air intakes or economizers for building ventilation.
Manufacturer Model Capacity (Tons) Date Manu.
Age
(years)
Carrier 48DU 5 2006 17
Carrier 48VL 5 2017 6
The packaged a/c units are horizontal discharge with the supply and return ductwork routed through the wall of the mechanical well. The rooftop ductwork appears to be in good condition. The units are sitting on roof pads with sheet metal caps. It does not appear the units are currently anchored and are just resting on the roof pads.
Each AC unit is controlled by a wall mounted electronic thermostat. The thermostats are aged with limited programmability and function.
The restrooms are exhausted by a ceiling mounted exhaust fan with ductwork up to a roof cap. The roof cap is a basic bent sheet metal hood in which the cover is currently disconnected and the exhaust duct is open to the sky. The ceiling exhaust fan is in good condition. The kitchen hood is a small residential type with an integral exhaust fan and ductwork to a vent in bottom of the roof overhang. It appears to be in good condition.
The apparatus bay is semi-conditioned by two (2) evaporative cooling units. There is one installed in each of the two mezzanines on opposite sides of the building. The mezzanines are accessible through a ladder down to the space below. The units were manufactured in 2020 and are in good condition. The evaporative media within the units is worn to the expected condition for the age of the units and will need replacement in the next year or two. Ductwork is routed to sidewall supply registers in two corners of the apparatus bay. There does not appear to be any relief openings in the apparatus bay. If Palm Desert Fire Station 33 & 71 Assessments Page 171
472
Palm Desert Fire Station 71 May 17, 2023
HVAC and Plumbing Assessment Page 3
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 the evaporative coolers are operating with the roll up doors closed, the apparatus bay may become positively pressurized causing fumes/vapors to enter the living area of the building.
The apparatus bay includes a Plymovent vehicle exhaust system with intake pipes routed to an exhaust fan mounted on the exterior of the apparatus bay.
There is a generator room adjacent to the apparatus bay that is naturally ventilated with high and low door louvers. The generator has a ducted air intake to the radiator from an exterior wall louver. The generator exhaust pipe is routed out through the exterior wall.
Recommendations
Single zone packaged a/c units controlled by a single thermostat have gone out of favor for this building application due to limited controllability of temperature from room to room. One of the existing packaged a/c units is in good condition with likely 10+ years of useful life remaining while the other unit is getting to the end of its useful life expectancy.
If the layout of the interior of the building is to remain relatively unchanged, then the existing systems can remain as is with replacement of the one a/c unit as required. The existing ductwork on the roof can remain with minor clean and repair as required. It is recommended the existing a/c units be retrofitted with new economizers for improved indoor air quality and energy savings. Economizers are required per current energy code requirements. Due to the close proximity of the a/c units the mechanical well wall and relatively short lengths of ducts on the roof, it may not be possible to provide new economizers without relocating the existing a/c units.
Recommend cleaning and resealing existing to remain ductwork within the building and replacing duct insulation. It is recommended all units to remain be anchored to the roof at the existing roof pads. If the building is to be re-roofed, it is recommended to remove the existing a/c units and reinstall them on new built-up roof curbs for improved weatherproofing.
If the interior of the building is to receive an extensive remodel with a modified floor layout or if the department is currently unhappy with the temperature control of the existing systems, then brand-new AC systems can be provided. All existing ductwork and systems would be removed and a completely new system would be provided. VRF systems with heat recovery are recommended which would include fan coil units throughout the building for complete independent temperature control from room to room.
The VRF system would include a roof mounted condensing unit and a central controller.
The existing evaporative coolers are in good condition and have significant useful life expectancy remaining. The interior media will need replacement in the next year or so which is typical for these units.
The existing ceiling exhaust fans are in good condition and can be cleaned and remain.
The existing roof cap needs to be repaired to prevent water from entering the exhaust duct at the roof. If the building is to be re-roofed, it is recommended the existing roof cap be removed and replaced with a new curb mounted cap for improved weatherproofing and durability.
Recommend replacement of the existing Plymovent exhaust fan based on apparent condition and to relocate it to an accessible location on the roof. Existing vehicle exhaust ductwork can remain and be reused and extended to the new exhaust fan location.
Palm Desert Fire Station 33 & 71 Assessments Page 172
473
Palm Desert Fire Station 71 May 17, 2023
HVAC and Plumbing Assessment Page 4
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 To improve energy efficiency and controllability of the systems, it is recommended all new electronic programmable thermostats be provided with wifi connection for remote access and control.
Photos:
Photo 1: Typical rooftop gas/electric packaged a/c unit with roof ductwork through exterior wall.
Photo 2: Mechanical mezzanine with evaporative cooling unit serving apparatus bay.
Palm Desert Fire Station 33 & 71 Assessments Page 173
474
Palm Desert Fire Station 71 May 17, 2023
HVAC and Plumbing Assessment Page 5
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Photo 3: Supply register from evaporative cooler serving apparatus bay.
Photo 4: Ceiling exhaust fan located in restroom.
Palm Desert Fire Station 33 & 71 Assessments 475
Palm Desert Fire Station 71 May 17, 2023
HVAC and Plumbing Assessment Page 6
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Photo 5: Exhaust roof termination with disconnected cap.
Photo 6: Plymovent exhaust system mounted on side of apparatus bay.
Palm Desert Fire Station 33 & 71 Assessments 476
Palm Desert Fire Station 71 May 17, 2023
HVAC and Plumbing Assessment Page 7
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Photo 7: Typical a/c unit thermostat.
Palm Desert Fire Station 33 & 71 Assessments 477
Palm Desert Fire Station 71 May 17, 2023
HVAC and Plumbing Assessment Page 8
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Existing Plumbing Conditions
The plumbing infrastructure appears to be original to the building and is approximately 38 years old. Domestic water piping within the building was observed to be copper and waste/vent piping observed to be cast iron. Per the as-built drawings, the existing domestic water service is 1-1/2”. We are not able to determine the existing underground sewer lateral size based on the as builts but it is anticipated to be either 3” or 4”.
Plumbing fixtures within the building include flush valve type water closets, flush valve urinals, and lavatories with manual faucets. Fixtures appear to be in good condition.
The existing domestic hot water system consists of a central gas-fired tank type water heater. The water heater was manufactured around 2019 and is in good condition. The system does not have a recirculating loop or an expansion tank.
The building is provided natural gas from the meter located on the north-west side of the building. Gas piping is black iron and mainly routed below the roof then stubbed up to the a/c units.
Makeup water is provided to the evaporative cooling units located in the mechanical mezzanines through individual copper lines. A backflow prevention device was not observed on the water line feeding either of these units.
A hose bib could not be located on the roof near the mechanical units on the roof.
The air compressor is located in the central mechanical room adjacent to the apparatus bay. The air compressor is piped to outlets in the workshop. The compressed air piping was observed to be plastic.
The kitchen includes a small residential style gas range and hood which appear to be in good condition. It does not appear the building has a control station with gas shutoff valves connected to the emergency call system. There is also a gas barbeque on the exterior patio that is connected to the building natural gas system.
Condensate piping from the a/c units on the roof was observed to be PVC. The piping is missing a code required p-trap and currently discharges to a roof drain.
The building is fully sprinklered with an automatic fire sprinkler system. The riser is 2-1/2” and located in the south-east corner of the apparatus bay. There is FDC, PIV, and vault which is assumed to have a backflow preventer on the north side of the site.
Plumbing Recommendations
The existing 1-1/2” cold water line and existing sewer line are likely adequate for any tenant improvement scope. It is recommended the existing underground waste piping be inspected with a camera system to confirm there are no obstructions or broken pipes.
Any tenant improvement scope that requires removal of existing plumbing fixtures, will also require installation of new plumbing fixtures which are low-flow and compliant with current Cal Green requirements. Generally, a 2” water line is required for flush valve water closets. Any new water closets are recommended to be tank-type to avoid potential issues with lack of water pressure.
The existing domestic water heater is in good condition with useful life expectancy remaining. Recommend installing a new expansion tank per code requirements. If the time to receive hot water is excessively long at the furthest fixtures, recommend installing a return line and recirculating pump with timeclock and aquastat.
It is recommended new hose bibb with vacuum breakers be provided on the roof for cleaning purposes.
Palm Desert Fire Station 33 & 71 Assessments 478
Palm Desert Fire Station 71 May 17, 2023
HVAC and Plumbing Assessment Page 9
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Recommend replacing the existing condensate piping for the roof mounted a/c units with new copper piping including new p-traps. Condensate piping will be rerouted from the non-compliant roof drain termination to a compliant location within the building just as a service sink or sink tailpiece.
Recommend providing new backflow preventer in existing domestic cold-water line that is feeding the evaporative cooling units in the mechanical mezzanines per code requirements.
Recommend installing new gas control station with automatic shutoff solenoid valve to kitchen and outdoor barbeque with connection to the emergency call system.
All future tenant improvement work will require relocation and extension of the existing automatic sprinkler system per NFPA 13 requirements.
Photos:
Photo 1: Existing tank type gas water heater in closet.
Palm Desert Fire Station 33 & 71 Assessments 479
Palm Desert Fire Station 71 May 17, 2023
HVAC and Plumbing Assessment Page 10
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Photo 2: Air compressor in mechanical room.
Photo 3: PVC A/C unit condensate piping currently discharging to roof drain.
Palm Desert Fire Station 33 & 71 Assessments 480
Palm Desert Fire Station 71 May 17, 2023
HVAC and Plumbing Assessment Page 11
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Photo 4: Fire sprinkler riser in south-west corner of apparatus bay.
Photo 5: Natural gas barbeque on exterior patio.
Palm Desert Fire Station 33 & 71 Assessments 481
Palm Desert Fire Station 71 May 17, 2023
HVAC and Plumbing Assessment Page 12
14451 Chambers Road, Suite 210, Tustin, CA 92780 Phone (949) 417-3903 Fax (949) 419-1393 Photo 6: Natural gas meter on north side of building.
Palm Desert Fire Station 33 & 71 Assessments 482
A & F ENGINEERING GROUP, INC.
CONSULTING ELECTRICAL ENGINEERS
9320 BASELINE RD. SUITE C, RANCHO CUCAMONGA, CA 91701, Tel (909) 941-3008, Fax (909) 941-8211 May 22, 2023
Mr. Kelley Needham
PBK Architects
8163 Rochester Avenue, Suite 100
Rancho Cucamonga, CA 91730
Re: Electrical Systems Assessment
Riverside County Fire, Fire Station #71
73995 Country Club Dr. Palm Desert, CA
Mr. Needham,
The following is our evaluation of the electrical systems at the aforementioned fire station:
Existing Conditions:
Lighting
Building interior lighting consists primarily of fluorescent 2x4 and 1x4 light fixtures, incandescent downlight fixtures, decorative pendant fixtures in the kitchen, and wall mounted reading lights in the dorms. The fixtures in the offices and living areas appear to be in fair condition. The fixtures in the showers, utility rooms and the App Bay are in poor to fair condition. The pendant fixtures in the kitchen appear to be in good condition.
The 2x4 and 1x4 light fixtures do not have dimming capabilities and cannot meet current dimming requirements of the 2022 Energy Efficiency Standards (Title 24).
Light fixtures using incandescent lamps with screw-in bases do not comply with the high efficiency requirements of Title 24 and must be replaced.
The Equipment Room lights are controlled by an occupant sensor. All other lighting controls consist of standard toggle switches that provide bi-level switching. The bi-level switching consists of two switches, configured in the traditional “a/b” configuration, that allows the occupant to turn “on” or “off” half the fixtures in the room. In addition to bi-level switching, the Corridor, App Bay, and the Men’s Dorm have 3-way switching.
The lighting controls do not meet the dimming and automatic shut-off control requirements of Title 24.
Switches connected to emergency circuits are not “red” in color, do not have “red” wall plates and are not identified as being connected to emergency circuits.
Lighting circuits are protected by standard thermal magnetic type circuit breakers. The circuit breakers cannot provide the arc fault circuit interrupter functions required by current codes.
Building exterior lighting consists of downlights recessed in the overhangs and soffits, wall pack fixtures at the Hose Rack, one wall pack fixture at the return drive, a residential style dual head incandescent security flood light at the response drive, and a single head flood light Palm Desert Fire Station 33 & 71 Assessments Page 182
483
A&F ENGINEERING GROUP, INC.
9320 BASELINE RD. SUITE C, RANCHO CUCAMONGA, CA 91701, Tel (909) 941-3008, Fax (909) 941-8211
Electrical Systems Assessment
Riverside Co. Fire, Station #71
Palm Desert, CA
at the BBQ. The fixtures appear to be in fair to good condition. Wall pack and floodlight type fixtures are not shielded , therefore, not T24 compliant.
The building exterior light fixtures are controlled by a time clock located in the Equipment room. The time clock is not an astronomical time clock with daylight savings functions, therefore, does not meet current Title 24 requirements.
Site/Parking lot lighting consists of pole mounted LED fixtures mounted at approximately 20’-0” above grade. The fixtures do not have motion sensors, thus, do not meet current dimming and automatic control requirements.
Power
The utility service is 400 amps and operates at 120/208V, 3 phase, 4 wire. The rating of the service is capable of serving the 113 Amps building demand load with 70% spare capacity for expansion.
The main service switchboard was manufactured by Square-D, it is 30 plus years old, in good condition, and replacement circuit breakers are readily available. However, based on the arrangement of the circuit breakers, there does not appear to be space to install additional 100A or larger circuit breakers, thus, restricting the addition of circuit breakers required to support the installation of panels for EV chargers and a PV power plant.
The main service switchboard is located in the Equipment room and alongside telephone equipment and alarm panels. The meter location and its proximity to building alarm panels do not meet current utility company requirements.
Branch circuit panels are commercial grade, in fair to good condition, and replacement circuit breakers are readily available. There are no arc fault circuit interrupter (AFCI) circuit breakers in the panels, AFCI circuit breakers are required to protect circuits serving the residential areas of the building.
The main switchboard and panels do not have Arc flash labels.
Receptacles are standard duplex grounding type and receptacles near the kitchen and bathroom sinks are GFI type.
However, the receptacles do not comply with current codes. Receptacles in residential (R Occupancy) areas must be tamper proof and either AFCI type or protected by and AFCI circuit breaker at the panel. Administrative (B Occupancy) areas, such as offices, conference rooms, lobbies, breakrooms, must have controlled receptacles within six feet of a standard receptacle, the controlled receptacles must be clearly identified and controlled by the room’s occupant sensor. All kitchen 120V. 15 or 20 amp receptacles must be GFI and protected by an AFCI circuit breaker. App Bay receptacles must be GFI type.
Receptacles do not comply with current ADA mounting height requirements. ADA requires receptacles to be mounted at +48” maximum to the top of the box and +15” minimum to the bottom of the box, and +46” maximum to the top of box when located above counter tops.
Palm Desert Fire Station 33 & 71 Assessments Page 183
484
A&F ENGINEERING GROUP, INC.
9320 BASELINE RD. SUITE C, RANCHO CUCAMONGA, CA 91701, Tel (909) 941-3008, Fax (909) 941-8211
Electrical Systems Assessment
Riverside Co. Fire, Station #71
Palm Desert, CA
Receptacles connected to emergency circuits are not “red” in color, do not have “red” wall plates and are not identified as being connected to emergency circuits.
Outdoor receptacles are GFI type. However, the covers are not U.L. listed for use in wet locations when “in-use”, therefore, do not meet code.
The 30kW (104 Amps) Generac emergency generator with subbase fuel tank, located in the generator room, is 30 plus years old, is out of commission and is not capable of providing emergency power to the station. At the time of the site visit a 30kW temporary generator was being used to provide emergency power to the station.
The temporary generator has been connected to the existing ATS and will provide emergency power to the station upon loss of utility power. The station’s emergency power distribution system is designed to provide emergency power for life safety equipment and selected building loads, the system does not provide emergency power to the entire station.
Communications
The alerting system/base radio is operational and in good working condition. The system includes a Kenwood base radio with power supply, a Comtronix station control interface that manages the signaling and audio systems, a printer, a microphone, an amplifier, a stereo tuner, lighted speakers in the dorms and standard speakers in all other locations. The system is outdated and the Comtronix controller is obsolete. The head-end equipment is located in a below counter cabinet and should be relocated to a secure location accessible to only to authorized personnel (i.e. Communications room).
The telephone service enters the building underground and terminates on a backboard located in the Equipment room. Due to the nature of the Equipment room, the telephone terminals and equipment are subject to dust and other contaminants. Most wall mounted telephone outlets, other than those located at workstations/desks, are mounted above +48” and are not ADA compliant.
There is no 911 phone at the front of the station
The cable TV (CATV) service is located outside of the building, on the other side of the Dayroom wall where the TV is mounted. The service cabling is exposed and not housed in a weatherproof box. No other CATV line or drop was found during the site visit.
The entry doors to the station are equipped with entry keypads and a door bell push button that alerts FD personnel of visitors at the entry doors.
The data/computer network system consists of a PC and router located under a desk in the Reception room. There system provides service to wall mounted station outlets and one wireless access point. The equipment and cabling under the desk is in disarray, subject to damage, and should be relocated to a secure location accessible to only to authorized personnel (i.e. Communications room).
Palm Desert Fire Station 33 & 71 Assessments Page 184
485
A&F ENGINEERING GROUP, INC.
9320 BASELINE RD. SUITE C, RANCHO CUCAMONGA, CA 91701, Tel (909) 941-3008, Fax (909) 941-8211
Electrical Systems Assessment
Riverside Co. Fire, Station #71
Palm Desert, CA
Areas of the station, accessible to the public, did not have fire alarm coverage. The dorms and corridors leading to the dorms are equipped with smoke detectors. However, the Men’s Dorm only has one smoke detector and due to the placement of the detector (east side of the room) there is insufficient coverage for the west side of the room. Furthermore, the detectors in the corridors are not combination CO/smoke detectors.
Recommendations:
Lighting:
Replace all interior light fixtures with new high efficiency LED fixtures with dimming drivers.
Provide dimers in each room to control the new LED fixtures. Mount dimmers at ADA compliant mounting heights. Dimmers connected to emergency circuits are to be provided with “red” wall plates. The serving panel and circuit number should be engraved on the wall plate.
Provide ceiling mounted or wall switch type occupant sensors for perform the T24 required automatic building shut-off functions. Sensors in the non-residential areas of the station are to operate in “automatic” mode. Sensors in the residential areas of the station are to operate in “vacancy” mode. The vacancy setting ensures that lights do not automatically turn on when motion is detected, lights must be physically turned on and will shut off automatically.
Replace all building exterior light fixtures with new high efficiency LED fixtures with dimming drivers. Wall mounted fixtures are to be shielded to prevent light spill.
Replace the time clock with a new astronomical time clock and compatible photocell.
For compliance with current Title 24 requirements, replace existing LED area/parking lot fixtures with fixtures containing dimming drivers and motion sensors that will allow the illumination levels to automatically dim to 50% when the surrounding area is unoccupied.
Additional fixtures may be required to comply with the IES recommended foot-candle levels for security and safety purposes.
Provide AFCI circuit breakers for all lighting circuits serving the residential areas of the station.
Power:
Replace the main service switchboard to facilitate the connection of the new generator for whole building back-up power, provide power to existing panels, HVAC equipment, the compressor and have space for circuit breakers to provide power for EV charging stations and a 20kW PV power plant. Locate the new service switchboard outdoors or in a room with exterior access and in compliance with SCE requirements. Replacement of the main service switchboard will require SCE to provide engineering and design services for the new infrastructure required to support the service rework.
Palm Desert Fire Station 33 & 71 Assessments Page 185
486
A&F ENGINEERING GROUP, INC.
9320 BASELINE RD. SUITE C, RANCHO CUCAMONGA, CA 91701, Tel (909) 941-3008, Fax (909) 941-8211
Electrical Systems Assessment
Riverside Co. Fire, Station #71
Palm Desert, CA
Dedicate space near the main switchboard for the addition of a solar AC disconnect switch and SCE meter.
Replace the panels with new commercial grade branch circuit panels and provide the panel with AFCI circuit breakers for circuits serving the residential areas. Trace all existing circuits and update the panel directories If existing panels are re-used, replace existing circuit breakers serving circuits in the residential areas of the station with AFCI circuit breakers.
Provide a new panel for EV charging stations.
Perform a short circuit and arc fault study to ensure panels are rated to withstand the available fault currents and to identify the arc flash boundaries. Provide arch flash labels for all panels.
Replace the receptacles in the residential areas with tamper proof receptacles. If AFCI circuit breakers are not provided, the new receptacles must be tamper proof AFCI type.
Provide controlled receptacles in offices, conference rooms, lobbies and breakrooms. The installation of controlled receptacles must be coordinated with the installation of occupant sensors.
Replace all kitchen receptacles with GFI receptacles. If AFCI circuit breakers are not provided, the new receptacles must be combination GFI/AFCI type.
Relocate receptacles as required to meet the ADA mounting height requirements.
Provide a new 125kW generator with subbase fuel tank to provide stand-by power to the entire station. The 125kW generator would be capable of sustaining the existing 32.5 kW load (26kW demand + 25% per CEC Article 220.87) and have sufficient capacity for future EV chargers.
Locate the new generator outdoors and in near proximity to the generator room. Locate the new ATS in the generator room and provide required interconnection between the ATS and the new switchboard, and the ATS and the generator.
Should the City decide not to provide stand-by power for the entire station and opt to maintain the current partial station stand-by power model, the minimum size of the new generator should be no less than 30kW, to match existing, and consideration should be given to increasing the size to accommodate future truck/apparatus electric vehicle chargers.
Where the current emergency power configuration is maintained, receptacles connected to emergency circuits must be replaced with “red” devices and wall plates. The serving panel and circuit number should be engraved on the wall plate.
Communications:
Construct a communications room to house the base radio, alerting system head-end equipment, telephone equipment, CATV equipment and data/network equipment. Rewire the station outlets as required to terminate the systems cables at the new communications room.
Palm Desert Fire Station 33 & 71 Assessments Page 186
487
A&F ENGINEERING GROUP, INC.
9320 BASELINE RD. SUITE C, RANCHO CUCAMONGA, CA 91701, Tel (909) 941-3008, Fax (909) 941-8211
Electrical Systems Assessment
Riverside Co. Fire, Station #71
Palm Desert, CA
Provide a new alerting system to work in conjunction with the base radio.
Relocate wall mounted telephone outlets as required to meet the ADA mounting height requirements.
Provide a 911 phone at the front of the station.
Move the existing CATV service equipment indoors or provide a secure, weatherproof cover, for the equipment. Contact the CATV company to discuss available options.
Provide additional ceiling mounted wireless access points (WAP) to ensure complete station coverage.
Add a single station smoke detector to the west end of the Men’s Dorm room to provide full room coverage. Provide combination CO/smoke detectors in the corridors leading to the dorms. The detectors must be interconnected to ensure the audible device in all smoke and combination CO/smoke detectors activate whenever one detector in the system goes into alarm.
For areas accessible to the public, add a manual pull station at the exit door, a combination horn/strobe in the lobby, a strobe in the restroom, and a control panel to supervise the devices.
Please call if you have questions or require additional information.
Sincerely,
Luis E. Flores
Principal
Palm Desert_FS#71_Assessment.doc
Palm Desert Fire Station 33 & 71 Assessments Page 187
488
Palm Desert Fire Station 33 & 71 Assessments
4.0 Existing Building Evaluations
The following pages provide the existing building evaluations completed by the structural, mechanical/plumbing and electrical engineers.
ADA ASSESSMENT REPORT
FIRE STATION NO.71 Palm Desert Fire Station 33 & 71 Assessments Page 118 Page 188 489
Accessibility Report
Prepared By
Fire Station #71
73-995 Country Club
Palm Desert, CA 92260
Date of Inspection
8/21/2018
Disability Access Consultants, LLC
City of Palm Desert
Palm Desert Fire Station 33 & 71 Assessments 490
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 428887
There is no additional signage marked "van
accessible" at the van accessible parking space.
Van accessible parking spaces shall provide
additional signage that states "van
accessible" .
ADA 502, 502.6
Parking Lot
Accessible Space Next to Main Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Parking : Van Accessible Signage
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 2 of 63 Palm Desert Fire Station 33 & 71 Assessments 491
Finding
On-Site Finding Faded or Damaged
Recommendation
Code Reference
Record Number 428888
Parking space has signage however sign is
faded, damaged or otherwise not viewable.
Provide compliant parking signage.
ADA 502.6
Parking Lot
Accessible Space Next to Main Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Parking : Accessible Signage is Faded or Damaged
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 3 of 63 Palm Desert Fire Station 33 & 71 Assessments 492
Finding
On-Site Finding 63.00 inches
Recommendation
Recommendation At least 96.00 inches
Code Reference
Record Number 428889
The access aisle does not meet the minimum
required width.
Re-stripe the access aisle.
CA 11B- 502.2
Parking Lot
Accessible Space Next to Main Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Parking : Access Aisle Width
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 4 of 63 Palm Desert Fire Station 33 & 71 Assessments 493
Finding
On-Site Finding 4.20 percent
Recommendation
Recommendation Up to 2.08 percent
Code Reference
Record Number 428891
The slope of the access aisle is not compliant.
Repave the access aisle to provide a compliant
surface slope.
ADA 502, 502.4, CA 11B-502.4
Parking Lot
Accessible Space Next to Main Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Parking : Access Aisle Slope
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 5 of 63 Palm Desert Fire Station 33 & 71 Assessments 494
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 428892
The access aisle does not contain the wording
"No Parking" painted in white letters within the
access aisle.
Paint the words "NO PARKING" a compliant
height within the access aisle.
CA 11B- 502.3
Parking Lot
Accessible Space Next to Main Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Parking : Access Aisle - "No Parking"
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 6 of 63 Palm Desert Fire Station 33 & 71 Assessments 495
Finding
On-Site Finding 2.50 percent
Recommendation
Recommendation Up to 2.08 percent
Code Reference
Record Number 428883
The slope of the accessible parking space is not
compliant.
Repave the access aisle to provide a compliant
surface slope.
ADA 502, 502.4, CA 11B-502.4
Parking Lot
Accessible Space Next to Main Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Parking : Parking Space Slope
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 7 of 63 Palm Desert Fire Station 33 & 71 Assessments 496
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 428884
The accessible parking space does not provide
an International Symbol of Accessibility surface
identification.
Provide compliant surface identification at the
accessible parking space.
ADA 502, CA 11B-502.6
Parking Lot
Accessible Space Next to Main Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Parking : Parking Space ISA Symbol
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 8 of 63 Palm Desert Fire Station 33 & 71 Assessments 497
Finding
On-Site Finding 201.00 inches
Recommendation
Recommendation At least 216.00 inches
Code Reference
Record Number 428885
The accessible parking space does not meet
the minimum requirement for length.
Re-stripe the accessible parking space.
CA 11B- 502.2
Parking Lot
Accessible Space Next to Main Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Parking : Parking Space Length
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 9 of 63 Palm Desert Fire Station 33 & 71 Assessments 498
Finding
On-Site Finding Not Found
Recommendation
Code Reference
Record Number 428886
There is no minimum fine sign at the parking
space.
Provide a minimum fine sign at the parking
space below the International Symbol of
Accessibility.
CA 11B- 502.6
Parking Lot
Accessible Space Next to Main Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Parking : Parking Lot Warnings
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 10 of 63 Palm Desert Fire Station 33 & 71 Assessments 499
Finding
On-Site Finding 52.50 inches
Recommendation
Recommendation At least 60.00 inches
Code Reference
Record Number 428897
The access aisle does not meet the minimum
required width.
Re-stripe the access aisle.
ADA 502, 502.3, CA 11B-502.3
Parking Lot
Accessible Space Next to Rear Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Parking : Access Aisle Width
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 11 of 63 Palm Desert Fire Station 33 & 71 Assessments 500
Finding
On-Site Finding 2.90 percent
Recommendation
Recommendation Up to 2.08 percent
Code Reference
Record Number 428899
The slope of the access aisle is not compliant.
Repave the access aisle to provide a compliant
surface slope.
ADA 502, 502.4, CA 11B-502.4
Parking Lot
Accessible Space Next to Rear Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Parking : Access Aisle Slope
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 12 of 63 Palm Desert Fire Station 33 & 71 Assessments 501
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 428900
The access aisle does not contain the wording
"No Parking" painted in white letters within the
access aisle.
Paint the words "NO PARKING" a compliant
height within the access aisle.
CA 11B- 502.3
Parking Lot
Accessible Space Next to Rear Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Parking : Access Aisle - "No Parking"
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 13 of 63 Palm Desert Fire Station 33 & 71 Assessments 502
Finding
On-Site Finding 4.10 percent
Recommendation
Recommendation Up to 2.08 percent
Code Reference
Record Number 428893
The slope of the accessible parking space is not
compliant.
Repave the access aisle to provide a compliant
surface slope.
ADA 502, 502.4, CA 11B-502.4
Parking Lot
Accessible Space Next to Rear Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Parking : Parking Space Slope
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 14 of 63 Palm Desert Fire Station 33 & 71 Assessments 503
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 428894
The accessible parking space does not provide
an International Symbol of Accessibility surface
identification.
Provide compliant surface identification at the
accessible parking space.
ADA 502, CA 11B-502.6
Parking Lot
Accessible Space Next to Rear Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Parking : Parking Space ISA Symbol
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 15 of 63 Palm Desert Fire Station 33 & 71 Assessments 504
Finding
On-Site Finding 206.00 inches
Recommendation
Recommendation At least 216.00 inches
Code Reference
Record Number 428895
The accessible parking space does not meet
the minimum requirement for length.
Re-stripe the accessible parking space.
CA 11B- 502.2
Parking Lot
Accessible Space Next to Rear Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Parking : Parking Space Length
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 16 of 63 Palm Desert Fire Station 33 & 71 Assessments 505
Finding
On-Site Finding Not Found
Recommendation
Code Reference
Record Number 428896
There is no minimum fine sign at the parking
space.
Provide a minimum fine sign at the parking
space below the International Symbol of
Accessibility.
CA 11B- 502.6
Parking Lot
Accessible Space Next to Rear Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Parking : Parking Lot Warnings
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 17 of 63 Palm Desert Fire Station 33 & 71 Assessments 506
Finding
On-Site Finding Not Found
Recommendation
Code Reference
Record Number 428901
There is no warning signage posted regarding
unauthorized use of accessible parking spaces
in the parking lot.
Provide compliant signage regarding
unauthorized use of accessible parking spaces.
CA 11B- 502.8
Parking Lot
Warning Sign
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Parking : Parking Lot Warning Sign
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 18 of 63 Palm Desert Fire Station 33 & 71 Assessments 507
Finding
On-Site Finding 4.50 percent for 70.00 feet
Recommendation
Recommendation Up to 2.08 percent
Code Reference
Record Number 428851
There are cross slopes greater than allowed on
the primary path of travel.
Provide a compliant path of travel.
ADA 402, 403.3, CA 11B-403.3
Path of Travel from the Accessible Space to the Rear Entrance Exterior Walkway
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Path of Travel : Walking Surface Cross Slope
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 19 of 63 Palm Desert Fire Station 33 & 71 Assessments 508
Finding
On-Site Finding Not Compliant
Recommendation
Code Reference
Record Number 428833
An unstable floor mat is provided at the door
landing.
Provide a compliant floor mat for the door.
ADA 403.2, 302.1, CA 11B-302.1,403.2
Apparatus Bay
Push Side
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Floor Mat
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 20 of 63 Palm Desert Fire Station 33 & 71 Assessments 509
Finding
On-Site Finding 2.40 percent
Recommendation
Recommendation Up to 2.08 percent
Code Reference
Record Number 428903
There is no level landing at this door.
Provide a level landing.
ADA 302, 404, 305, 404.2, CA 11B-404.2
Main Entrance
Pull Side
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Floor Surface Slope
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 21 of 63 Palm Desert Fire Station 33 & 71 Assessments 510
Finding
On-Site Finding 11.00 pounds
Recommendation
Recommendation Up to 5.00 pounds
Code Reference
Record Number 428902
The door opening force for this door is greater
than allowed.
Adjust the closer on the door to meet the door
opening force requirements.
ADA 404.2, CA 11B-404.2
Main Entrance
Push / Pull
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Door Opening Pressure
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 22 of 63 Palm Desert Fire Station 33 & 71 Assessments 511
Finding
On-Site Finding 0.75 inches
Recommendation
Recommendation Up to 0.50 inches
Code Reference
Record Number 428848
The height of the threshold at the entrance
door is greater than allowed.
Modify or replace the threshold to provide the
recommended height.
ADA 404, 404.2, CA 11B-404.2
Rear Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Door Threshold
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 23 of 63 Palm Desert Fire Station 33 & 71 Assessments 512
Finding
On-Site Finding 3.40 percent
Recommendation
Recommendation Up to 2.08 percent
Code Reference
Record Number 428850
There is no level landing at this door.
Provide a level landing.
ADA 302, 404, 305, 404.2, CA 11B-404.2
Rear Entrance
Pull Side
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Floor Surface Slope
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 24 of 63 Palm Desert Fire Station 33 & 71 Assessments 513
Finding
On-Site Finding Found
Recommendation
Code Reference
Record Number 428847
Has a door stop.
Remove the door stop.
ADA 404, 404.2, CA 11B-404.2
Rear Entrance
Push Bar / Lever
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Door Hardware
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 25 of 63 Palm Desert Fire Station 33 & 71 Assessments 514
Finding
On-Site Finding 2.00 inches
Recommendation
Recommendation At least 12.00 inches
Code Reference
Record Number 428849
There is less than the required latch side
clearance on the push side of the door.
Provide the recommended latch side clearance
on the push side of the door.
ADA 404, 404.2, CA 11B-404.2
Rear Entrance
Push Side
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Front Approach Latch Side Clearance
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 26 of 63 Palm Desert Fire Station 33 & 71 Assessments 515
Finding
On-Site Finding 10.00 pounds
Recommendation
Recommendation Up to 5.00 pounds
Code Reference
Record Number 428863
The door opening force for this door is greater
than allowed.
Adjust the closer on the door to meet the door
opening force requirements.
ADA 404.2, CA 11B-404.2
Unisex Restroom
Push / Pull
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Door Opening Pressure
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 27 of 63 Palm Desert Fire Station 33 & 71 Assessments 516
Finding
On-Site Finding Found
Recommendation
Code Reference
Record Number 428864
Has a door stop.
Remove the door stop.
ADA 404, 404.2, CA 11B-404.2
Unisex Restroom
Push / Pull
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Door Hardware
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 28 of 63 Palm Desert Fire Station 33 & 71 Assessments 517
Finding
On-Site Finding 10.00 pounds
Recommendation
Recommendation Up to 5.00 pounds
Code Reference
Record Number 428859
The door opening force for this door is greater
than allowed.
Adjust the closer on the door to meet the door
opening force requirements.
ADA 404.2, CA 11B-404.2
Unisex Restroom Next to Kitchen
Lever
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Door Opening Pressure
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 29 of 63 Palm Desert Fire Station 33 & 71 Assessments 518
Finding
On-Site Finding Found
Recommendation
Code Reference
Record Number 428860
Has a door stop.
Remove the door stop.
ADA 404, 404.2, CA 11B-404.2
Unisex Restroom Next to Kitchen
Lever
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Doors - Interior : Door Hardware
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 30 of 63 Palm Desert Fire Station 33 & 71 Assessments 519
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 428865
There is no compliant room identification
signage provided.
Install compliant room identification signage.
ADA 703, 216, 216.2, CA 11B-216.2
Apparatus Bay, Reception Office, Captains Office
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Signage - Interior : Room Identification
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 31 of 63 Palm Desert Fire Station 33 & 71 Assessments 520
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 428866
There is no directional signage.
Install directional signage to each accessible
element or room.
ADA 703, 216, 216.3, CA 11B-216.3, 703.5,703.5
Directional Signage from the Public Right of Way
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Signage : Directional or Information Signage
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 32 of 63 Palm Desert Fire Station 33 & 71 Assessments 521
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 510040
There is no room signage.
Install accessible room signage.
Notes : ISA is Present.
ADA 216.2, 216.6, CA 11B-216.2,216.6
Main Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Signage - Interior : Accessible Element/Entrance Signage Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 33 of 63 Palm Desert Fire Station 33 & 71 Assessments 522
Finding
On-Site Finding Not Found
Recommendation
Code Reference
Record Number 510042
There is no informational signage.
Install informational signage to each accessible
element or room or location.
ADA 216.3, CA 11B-216.3, 703.5,703.5
Main Entrance Doorbell
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Signage : Information Signage
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 34 of 63 Palm Desert Fire Station 33 & 71 Assessments 523
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 510041
There is no room signage.
Install accessible room signage.
ADA 216.2, 216.6, CA 11B-216.2,216.6
Rear Entrance
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Signage - Interior : Accessible Element/Entrance Signage Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 35 of 63 Palm Desert Fire Station 33 & 71 Assessments 524
Finding
On-Site Finding Not Found
Recommendation
Code Reference
Record Number 510043
There is no informational signage.
Install informational signage to each accessible
element or room or location.
ADA 216.3, CA 11B-216.3, 703.5,703.5
Rear Entrance Doorbell
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Signage : Information Signage
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 36 of 63 Palm Desert Fire Station 33 & 71 Assessments 525
Finding
On-Site Finding 44.50 inches
Recommendation
Recommendation Up to 44.00 inches
Code Reference
Record Number 428840
The height of the urinal flush control in the
restroom is greater than the required
maximum height.
Lower the flush control valve on the urinal to a
height not greater than the required maximum
height.
ADA 605, 309.3, 605.4, 308.2, CA 11B-605.4
Unisex Restroom
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Urinal Flush Control Height
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 37 of 63 Palm Desert Fire Station 33 & 71 Assessments 526
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 428841
There is no gender use signage on the entrance
door.
Post gender use signage on the center of the
door at the required height.
CA 11B- 216.8,703.7
Unisex Restroom
Door Sign - All Gender
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Door Signage
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 38 of 63 Palm Desert Fire Station 33 & 71 Assessments 527
Finding
On-Site Finding Not Wrapped
Recommendation
Code Reference
Record Number 428839
The supply lines under the lavatory do not
provide protection against contact.
Insulate or otherwise configure pipes under
the lavatory to protect against contact. Make
certain there are no sharp or abrasive surfaces
under the lavatory.
ADA 213, 606, 606.5, CA 11B-606.5
Unisex Restroom
Lavatory
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Lavatory - Supply Lines Wrapping Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 39 of 63 Palm Desert Fire Station 33 & 71 Assessments 528
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 428842
There is no compliant signage indicating
accessibility on the latch side of the entry door
of the restroom.
Provide compliant signage on latch side of
door.
ADA 703, 216, 216.8, CA 11B-216.8
Unisex Restroom
Wall Sign
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Wall Signage
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 40 of 63 Palm Desert Fire Station 33 & 71 Assessments 529
Finding
On-Site Finding 20.50 inches on center
Recommendation
Recommendation 17.00 - 18.00 inches
Code Reference
Record Number 428868
The distance from the center of the toilet to the
nearest side wall does not meet the required
distance.
Relocate the toilet so the distance from the
center line of the toilet to the nearest side wall
meets the required distance.
ADA 603, 604.2, CA 11B-604.2
Unisex Restroom
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Toilet Distance From Wall
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 41 of 63 Palm Desert Fire Station 33 & 71 Assessments 530
Finding
On-Site Finding 39.50 inches
Recommendation
Recommendation At least 42.00 inches
Code Reference
Record Number 428870
The toilet does not provide the required
distance from the center line to a fixture or
wall on the wide side.
Provide a compliant amount of clearance from
the center line of the toilet to the nearest
fixture or wall on the wide side.
ADA 603, 604, CA 11B-604
Unisex Restroom
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Toilet Minimum Distance From Any fixture Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 42 of 63 Palm Desert Fire Station 33 & 71 Assessments 531
Finding
On-Site Finding Swings In
Recommendation
Code Reference
Record Number 428871
The door to the compartment swings inward
into the minimum required compartment area.
Modify the swing of the door so that it does
not swing into the minimum required
compartment area.
ADA 603, 604.8, 304.4, CA 11B-604.8
Unisex Restroom
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Compartment Door Swings In
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 43 of 63 Palm Desert Fire Station 33 & 71 Assessments 532
Finding
On-Site Finding 5.00 inches
Recommendation
Recommendation 7.00 - 9.00 inches
Code Reference
Record Number 428872
The location of the toilet paper dispenser is not
within the required distance from the front
edge of the toilet seat.
Remount the toilet paper dispenser at a
compliant height and location.
ADA 603, 604.7, CA 11B-604.7,309.4
Unisex Restroom
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Toilet Paper Dispenser Distance From Seat Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 44 of 63 Palm Desert Fire Station 33 & 71 Assessments 533
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 432003
The restroom door does not provide a
compliant privacy lock with occupancy
indicator.
Install a compliant privacy lock with occupancy
indicator to the door.
ADA 213, 213.2, CA 11B-213.2
Unisex Restroom
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Door Privacy Lock and Occupied Indicator Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 45 of 63 Palm Desert Fire Station 33 & 71 Assessments 534
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 428867
There are no grab bars.
Install the required grab bars in the toilet
compartment.
ADA 603, 609, 604.5, CA 11B-604.5
Unisex Restroom
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Grab Bars
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 46 of 63 Palm Desert Fire Station 33 & 71 Assessments 535
Finding
On-Site Finding 18.50 inches on center
Recommendation
Recommendation 17.00 - 18.00 inches
Code Reference
Record Number 428843
The distance from the center of the toilet to the
nearest side wall does not meet the required
distance.
Relocate the toilet so the distance from the
center line of the toilet to the nearest side wall
meets the required distance.
ADA 603, 604.2, CA 11B-604.2
Unisex Restroom Next to Kitchen
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Toilet Distance From Wall
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 47 of 63 Palm Desert Fire Station 33 & 71 Assessments 536
Finding
On-Site Finding 35.62 inches
Recommendation
Recommendation At least 42.00 inches
Code Reference
Record Number 428845
The toilet does not provide the required
distance from the center line to a fixture or
wall on the wide side.
Provide a compliant amount of clearance from
the center line of the toilet to the nearest
fixture or wall on the wide side.
ADA 603, 604, CA 11B-604
Unisex Restroom Next to Kitchen
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Toilet Minimum Distance From Any fixture Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 48 of 63 Palm Desert Fire Station 33 & 71 Assessments 537
Finding
On-Site Finding 6.00 inches
Recommendation
Recommendation 7.00 - 9.00 inches
Code Reference
Record Number 428846
The location of the toilet paper dispenser is not
within the required distance from the front
edge of the toilet seat.
Remount the toilet paper dispenser at a
compliant height and location.
ADA 603, 604.7, CA 11B-604.7,309.4
Unisex Restroom Next to Kitchen
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Toilet Paper Dispenser Distance From Seat Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 49 of 63 Palm Desert Fire Station 33 & 71 Assessments 538
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 428879
There is no gender use signage on the entrance
door.
Post gender use signage on the center of the
door at the required height.
CA 11B- 216.8,703.7
Unisex Restroom Next to Kitchen
Door Sign - All Gender
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Door Signage
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 50 of 63 Palm Desert Fire Station 33 & 71 Assessments 539
Finding
On-Site Finding 17.00 inches on center
Recommendation
At least 18.00 inches on
center
Recommendation
Code Reference
Record Number 428877
The lavatory center line does not meet the
minimum required distance when located
adjacent to a side wall, partition or fixture.
Replace or remount lavatory to meet the
minimum required distance to the center line
of the fixture, when located adjacent to a side
wall or partition.
CA 11B- 606.6
Unisex Restroom Next to Kitchen
Lavatory
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Lavatory Distance From Wall/Fixture Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 51 of 63 Palm Desert Fire Station 33 & 71 Assessments 540
Finding
On-Site Finding Not Wrapped
Recommendation
Code Reference
Record Number 428878
The supply lines under the lavatory do not
provide protection against contact.
Insulate or otherwise configure pipes under
the lavatory to protect against contact. Make
certain there are no sharp or abrasive surfaces
under the lavatory.
ADA 213, 606, 606.5, CA 11B-606.5
Unisex Restroom Next to Kitchen
Lavatory
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Lavatory - Supply Lines Wrapping Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 52 of 63 Palm Desert Fire Station 33 & 71 Assessments 541
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 428880
There is no compliant signage indicating
accessibility on the latch side of the entry door
of the restroom.
Provide compliant signage on latch side of
door.
ADA 703, 216, 216.8, CA 11B-216.8
Unisex Restroom Next to Kitchen
Wall Sign
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Wall Signage
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 53 of 63 Palm Desert Fire Station 33 & 71 Assessments 542
Finding
On-Site Finding None Found
Recommendation
Code Reference
Record Number 428873
The restroom door does not provide a
compliant privacy lock with occupancy
indicator.
Install a compliant privacy lock with occupancy
indicator to the door.
ADA 213, 213.2, CA 11B-213.2
Unisex Restroom Next to Kitchen
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Door Privacy Lock and Occupied Indicator Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 54 of 63 Palm Desert Fire Station 33 & 71 Assessments 543
Finding
On-Site Finding 32.00 inches
Recommendation
Recommendation At least 48.00 inches
Code Reference
Record Number 428876
The entrance door swings into the turning
space within the restroom.
Reverse the door swing, or modify the
restroom to provide sufficient clear floor space
for a turning radius in the restroom to
accommodate an individual in a wheelchair.
ADA 304, 603.2, 305.3, 603.2, CA 11B-603.2
Unisex Restroom Next to Kitchen
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Restrooms - Interior : Distance from Door Edge to Nearest Fixture Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 55 of 63 Palm Desert Fire Station 33 & 71 Assessments 544
Finding
On-Site Finding 38.00 inches
Recommendation
Recommendation 39.00 - 41.00 inches
Code Reference
Record Number 428835
The water control valve is not mounted at a
compliant height.
Remount the water control valve.
ADA 213, 608, 608.5, CA 11B-608.5
Unisex Restroom Next to Kitchen
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Accessible Showers - Interior : Water Valve Height
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 56 of 63 Palm Desert Fire Station 33 & 71 Assessments 545
Finding
On-Site Finding 4.00 percent
Recommendation
Recommendation Up to 2.08 percent
Code Reference
Record Number 428881
The clear floor space slope is not compliant.
Provide compliant clear floor space.
ADA 304, CA 11B-305.2
Rear Entrance
Exterior Doorbell - Other
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Reach Ranges : Clear Floor Space Slope
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 57 of 63 Palm Desert Fire Station 33 & 71 Assessments 546
Finding
On-Site Finding 61.50 inches
Recommendation
Recommendation 15.00 - 48.00 inches
Code Reference
Record Number 428858
Kitchen appliance control height is not
compliant.
Provide compliant appliance with
recommended control height.
ADA 308, CA 11B-308
Kitchen
Appliance - Oven
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Kitchens - Interior : Control Height
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 58 of 63 Palm Desert Fire Station 33 & 71 Assessments 547
Finding
On-Site Finding 74.50 inches
Recommendation
Recommendation 15.00 - 48.00 inches
Code Reference
Record Number 428857
Exhaust fan controls height is not at a
compliant height.
Adjust the exhaust fan controls to the
recommended value.
ADA 308, CA 11B-308
Kitchen
Appliance - Range/Cooktop
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Kitchens - Interior : Exhaust Controls Height
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 59 of 63 Palm Desert Fire Station 33 & 71 Assessments 548
Finding
On-Site Finding 60.00 inches
Recommendation
Recommendation Up to 48.00 inches
Code Reference
Record Number 428855
The height of the controls and operating
mechanisms for the dispenser is not at the
correct height.
Relocate the dispenser to the correct height.
ADA 309, CA 11B-603.5
Kitchen
Paper Towel
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Kitchens - Interior : Height
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 60 of 63 Palm Desert Fire Station 33 & 71 Assessments 549
Finding
On-Site Finding Not Wrapped
Recommendation
Code Reference
Record Number 428853
The pipes are not wrapped for the sink.
Insulate or otherwise configure the water
supply and drain pipes under the sink to
protect against contact. Make certain there are
no sharp or abrasive surfaces under the sink.
ADA 606.5, CA 11B-606.5
Kitchen
Sink - Lever
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Kitchens - Interior : Pipes Wrapping
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 61 of 63 Palm Desert Fire Station 33 & 71 Assessments 550
Finding
On-Site Finding Not Wrapped
Recommendation
Code Reference
Record Number 428854
Supply lines are not wrapped for the kitchen
sink.
Make sure that the supply lines are fully
wrapped and insulated for the sink.
ADA 606.5, CA 11B-606.5
Kitchen
Sink - Lever
Progress
Progress Not_Set
Actual Date Projected Date
Actual Cost
Priority Not_Set
Comments No Comments
$0.00
Kitchens - Interior : Supply Lines
Resolution Not_Set
Contractor
Assignment Not.Set New Value 0
Designated Staff
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 62 of 63 Palm Desert Fire Station 33 & 71 Assessments 551
Prepared By Prepared Using
Fire Station #71
73-995 Country Club
Palm Desert, CA 92260
Date of Inspection
8/21/2018
Disability Access Consultants, LLC
Fire Station #71
Disability Access Consultants LLC (DAC) 1-800-743-7067 Page 63 of 63 Palm Desert Fire Station 33 & 71 Assessments 552
Contract No. ___________
1 Revised 01-2024
BBK 72500.00001\32374915.1
CITY OF PALM DESERT
PROFESSIONAL SERVICES AGREEMENT
1. Parties and Date. This Agreement is made and entered into this 27th day of June, 2024, by and between the City of Palm Desert, a municipal corporation organized under the laws of the State of California with its principal place of business at 73-510 Fred Waring Drive, Palm Desert, California 92260-2578 (“City”) and PBK Architects, a Corporation, with its principal place of business at 8163 Rochester Avenue, Rancho Cucamonga, CA 91730 ("Vendor"). The City and Vendor are sometimes individually referred to herein as "Party" and collectively as "Parties."
2. Recitals.
2.1 Project.
The City is a public agency of the State of California and is in need of professional services for the following project:
Architectural Design Services for FS 33 and FS 71 Project CFA00017/CFA00019 (hereinafter referred to as “the Project”).
2.2 Consultant.
Consultant desires to perform and assume responsibility for the provision of certain professional services required by the City on the terms and conditions set forth in this Agreement.
Consultant is duly licensed and has the necessary qualifications to provide such services.
3. Terms.
3.1 Scope of Services and Term.
3.1.1 General Scope of Services. Consultant promises and agrees to furnish to the City all labor, materials, tools, equipment, services, and incidental and customary work necessary to fully and adequately supply the services necessary for the Project ("Services"). The Services are more particularly described in Exhibit "A" attached hereto and incorporated herein by reference. All Services shall be subject to, and performed in accordance with, this Agreement, the exhibits attached hereto and incorporated herein by reference, and all applicable local, state and federal laws, rules and regulations.
3.1.2 Term. The term of this Agreement shall be from June 27, 2024, to June 30, 2027, unless earlier terminated as provided herein. Contractor shall complete the Services within the term of this Agreement and shall meet any other established schedules and deadlines.
3.2 Responsibilities of Consultant.
3.2.1 Independent Contractor; Control and Payment of Subordinates. The Services shall be performed by Consultant or under its supervision. Consultant will determine the means, methods, and details of performing the Services subject to the requirements of this Agreement. City retains Consultant on an independent contractor basis and not as an employee.
Any personnel performing the Services shall not be employees of City and shall at all times be under Consultant's exclusive direction and control. Neither City, or any of its officials, officers, directors, employees, or agents shall have control over the conduct of Consultant or any of Consultants officers, employees or agents, except as set forth in this Agreement. Consultant shall pay all wages, salaries, and other amounts due such personnel in connection with their performance of Services under this Agreement and as required by law. Consultant shall be responsible for all reports and obligations respecting such additional personnel, including, but not 553
Contract No. ___________
2 Revised 01-2024
BBK 72500.00001\32374915.1
limited to: social security taxes, income tax withholding, unemployment insurance, disability insurance, and workers' compensation insurance.
3.2.2 Schedule of Services. Consultant shall perform the Services in a prompt and timely manner in accordance with the Schedule of Services set forth in Exhibit "B" attached hereto and incorporated herein by reference. Consultant represents that it has the professional and technical personnel required to perform the Services expeditiously. Upon request of City, Consultant shall provide a more detailed schedule of anticipated performance to meet the Schedule of Services.
3.2.3 Conformance to Applicable Requirements. All work prepared by Consultant shall be subject to the approval of City.
3.2.4 Substitution of Key Personnel. Consultant has represented to City that certain key personnel will perform and coordinate the Services. Should one or more of such personnel become unavailable, Consultant may substitute other personnel of at least equal competence upon written approval of City. In the event that City and Consultant cannot agree as to the substitution of key personnel, City shall be entitled to terminate this Agreement for cause.
The key personnel for performance of this Agreement are as follows: Lisa Cox, Principal Architect.
3.2.5 City's Representative. The City hereby designates Lucero Leyva, Senior Project Manager, or his/her designee, to act as its representative in all matters pertaining to the administration and performance of this Agreement ("City's Representative"). City's Representative shall have the power to act on behalf of the City for review and approval of all products submitted by Consultant but not the authority to enlarge the scope of Services or change the total compensation due to Consultant under this Agreement. The City Manager shall be authorized to act on City's behalf and to execute all necessary documents which enlarge the scope of services or change the Consultant's total compensation subject to the provisions contained in Section 3.3 of this Agreement. Consultant shall not accept direction or orders from any person other than the City Manager, City's Representative or his/her designee.
3.2.6 Consultant's Representative. Consultant hereby designates Lisa Cox, Principal Architect, or his/her designee, to act as its representative for the performance of this Agreement ("Consultant's Representative"). Consultant's Representative shall have full authority to represent and act on behalf of the Consultant for all purposes under this Agreement. The Consultant's Representative shall supervise and direct the Services, using his/her best skill and attention, and shall be responsible for all means, methods, techniques, sequences, and procedures and for the satisfactory coordination of all portions of the Services under this Agreement.
3.2.7 Coordination of Services. Consultant agrees to work closely with City staff in the performance of Services and shall be available to City's staff, consultants, and other staff at all reasonable times.
3.2.8 Standard of Care; Performance of Employees. Consultant shall perform all Services under this Agreement in a skillful and competent manner, consistent with the standards generally recognized as being employed by professionals in the same discipline in the State of California. Consultant represents and maintains that it is skilled in the professional calling necessary to perform the Services. Consultant warrants that all employees and subconsultants shall have sufficient skill and experience to perform the Services assigned to them. Consultant represents that it, its employees and subconsultants have all licenses, permits, qualifications and 554
Contract No. ___________
3 Revised 01-2024
BBK 72500.00001\32374915.1
approvals of whatever nature that are legally required to perform the Services, and that such licenses and approvals shall be maintained throughout the term of this Agreement. Consultant shall perform, at its own cost and expense and without reimbursement from the City, any services necessary to correct errors or omissions which are caused by the Consultant's failure to comply with the standard of care provided herein. Any employee of the Consultant or its sub-consultants who is determined by the City to be uncooperative, incompetent, a threat to the adequate or timely completion of the Project, a threat to the safety of persons or property, or any employee who fails or refuses to perform the Services in a manner acceptable to the City, shall be promptly removed from the Project by the Consultant and shall not be re-employed to perform any of the Services or to work on the Project.
3.2.9 Period of Performance. Consultant shall perform and complete all Services under this Agreement within the term set forth in Section 3.1.2 above (“Performance Time”).
Consultant shall also perform the Services in strict accordance with any completion schedule or Project milestones described in Exhibits “A” or “B” attached hereto, or which may be separately agreed upon in writing by the City and Consultant (“Performance Milestones”). Consultant agrees that if the Services are not completed within the aforementioned Performance Time and/or pursuant to any such Performance Milestones developed pursuant to provisions of this Agreement, it is understood, acknowledged and agreed that the City will suffer damage.
Neither City nor Consultant shall be considered in default of this Agreement for delays in performance caused by circumstances beyond the reasonable control of the non-performing Party. For purposes of this Agreement, such circumstances include a Force Majeure Event. A Force Majeure Event shall mean an event that materially affects a Party’s performance and is one or more of the following: (1) Acts of God or other natural disasters; (2) terrorism or other acts of a public enemy; (3) orders of governmental authorities (including, without limitation, unreasonable and unforeseeable delay in the issuance of permits or approvals by governmental authorities that are required for the services); (4) strikes and other organized labor action occurring at the site and the effects thereof on the services, only to the extent such strikes and other organized labor action are beyond the control of Consultant and its subcontractors, and to the extent the effects thereof cannot be avoided by use of replacement workers; and (5) pandemics, epidemics or quarantine restrictions. For purposes of this section, “orders of governmental authorities,” includes ordinances, emergency proclamations and orders, rules to protect the public health, welfare and safety, and other actions of a public agency applicable to the services and Agreement.
Should a Force Majeure Event occur, the non-performing Party shall, within a reasonable time of being prevented from performing, give written notice to the other Party describing the circumstances preventing continued performance and the efforts being made to resume performance of this Agreement. Force Majeure Events and/or delays, regardless of the Party responsible for the delay, shall not entitle Consultant to any additional compensation.
Notwithstanding the foregoing in this section, the City may still terminate this Agreement in accordance with the termination provisions of this Agreement.
3.2.10 Laws and Regulations; Employee/Labor Certification. Consultant shall keep itself fully informed of and in compliance with all local, state and federal laws, rules and regulations in any manner affecting the performance of the Project or the Services and shall give all notices required by law. Consultant shall be liable for all violations of such laws and regulations in connection with the Services and this Agreement. All violations of such laws and regulations shall be grounds for the City to terminate the Agreement for cause.
3.2.10.1 Employment Eligibility; Consultant. Consultant certifies that it fully complies with all requirements and restrictions of state and federal law respecting the 555
Contract No. ___________
4 Revised 01-2024
BBK 72500.00001\32374915.1
employment of undocumented aliens, including, but not limited to, the Immigration Reform and Control Act of 1986, as may be amended from time to time and shall require all subconsultants and sub-subconsultants to comply with the same. Consultant certifies that it has not committed a violation of any such law within the five (5) years immediately preceding the date of execution of this Agreement and shall not violate any such law at any time during the term of the Agreement.
3.2.10.2 Equal Opportunity Employment. Consultant represents that it is an equal opportunity employer, and it shall not discriminate against any subconsultant, employee or applicant for employment because of race, religion, color, national origin, physical disability, ancestry, sex, age, marital status, gender, gender identity, gender expression, sexual orientation, reproductive health decision making, veteran or military status, or any other consideration made unlawful by federal, state, or local laws. Such non-discrimination shall include, but not be limited to, all activities related to initial employment, upgrading, demotion, transfer, recruitment or recruitment advertising, layoff or termination. Consultant shall also comply with all relevant provisions of City's Minority Business Enterprise program, Affirmative Action Plan or other related programs or guidelines currently in effect or hereinafter enacted.
3.2.10.3 Safety. Consultant shall execute and maintain its work so as to avoid injury or damage to any person or property. In carrying out its Services, the Consultant shall at all times be in compliance with all applicable local, state and federal laws, rules and regulations, and shall exercise all necessary precautions for the safety of employees appropriate to the nature of the work and the conditions under which the work is to be performed.
3.2.11 Insurance.
3.2.11.1 Minimum Requirements. Without limiting Consultant’s indemnification of City, and prior to commencement of the Services, Consultant shall obtain, provide, and maintain at its own expense during the term of this Agreement, policies of insurance of the type and amounts described below and in a form that is satisfactory to City. (A) General Liability Insurance. Consultant shall maintain commercial general liability insurance with coverage at least as broad as Insurance Services Office form CG 00 01, in an amount not less than $2,000,000 per occurrence, $4,000,000 general aggregate, for bodily injury, personal injury, and property damage. The policy must include contractual liability that has not been amended. Any endorsement restricting standard ISO “insured contract” language will not be accepted.
(B) Automobile Liability Insurance. Consultant shall maintain automobile insurance at least as broad as Insurance Services Office form CA 00 01 covering bodily injury and property damage for all activities of the Consultant arising out of or in connection with Work to be performed under this Agreement, including coverage for any owned, hired, nonowned or rented vehicles, in an amount not less than $1,000,000 combined single limit for each accident. The City’s Risk Manger may modify this requirement if it is determined that Consultant will not be utilizing a vehicle in the performance of his/her duties under this Agreement. (C) Professional Liability (Errors & Omissions) Insurance.
Consultant shall maintain professional liability insurance that covers the Services to be performed in connection with this Agreement, in the minimum amount of $1,000,000 per claim and in the aggregate. Any policy inception date, continuity date, or retroactive date must be before the effective date of this Agreement and Consultant agrees to maintain continuous coverage through a period no less than three years after completion of the Services required by this Agreement. 556
Contract No. ___________
5 Revised 01-2024
BBK 72500.00001\32374915.1
(D) Workers’ Compensation Insurance. Consultant shall
maintain Workers’ Compensation Insurance (Statutory Limits) and Employer’s Liability Insurance (with limits of at least $1,000,000). Consultant shall submit to City, along with the certificate of insurance, a Waiver of Subrogation endorsement in favor of the City, its officers, agents, employees, volunteers, and representatives.
(E) Umbrella or Excess Liability Insurance. Consultant may opt to utilize umbrella or excess liability insurance in meeting insurance requirements. In such circumstances, Consultant shall obtain and maintain an umbrella or excess liability insurance policy with limits that will provide bodily injury, personal injury and property damage liability coverage at least as broad as the primary coverages set forth above, including commercial general liability and employer’s liability. Such policy or policies shall include the following terms and conditions:
(1) A drop-down feature requiring the policy to respond if any primary insurance that would otherwise have
applied proves to be uncollectible in whole or in part for any reason;
(2) Pay on behalf of wording as opposed to reimbursement; (3) Concurrency of effective dates with primary policies; and (4) Policies shall “follow form” to the underlying primary policies.
(5) Insureds under primary policies shall also be insureds under the umbrella or excess policies.
(F) Fidelity Coverage. Reserved.
(G) Cyber Liability Insurance. Reserved.
If coverage is maintained on a claims-made basis, Consultant shall maintain such coverage for an additional period of three (3) years following termination of the Agreement.
3.2.11.2 Other Provisions or Requirements.
(A) Proof of Insurance. Consultant shall provide certificates of insurance to City as evidence of the insurance coverage required herein, along with a waiver of subrogation endorsement for workers’ compensation. Insurance certificates and endorsements must be approved by City’s Risk Manager prior to commencement of performance. Current certification of insurance shall be kept on file with City at all times during the term of this Agreement. City reserves the right to require complete, certified copies of all required insurance policies, at any time.
(B) Duration of Coverage. Consultant shall procure and
maintain for the duration of the Agreement insurance against claims for injuries to persons or damages to property, which may arise from or in connection with the performance of the Services hereunder by Consultant, his/her agents, representatives, employees or subconsultants. (C) Primary/Non-Contributing. Coverage provided by
Consultant shall be primary and any insurance or self-insurance procured or maintained by City 557
Contract No. ___________
6 Revised 01-2024
BBK 72500.00001\32374915.1
shall not be required to contribute with it. The limits of insurance required herein may be satisfied by a combination of primary and umbrella or excess insurance. Any umbrella or excess insurance shall contain or be endorsed to contain a provision that such coverage shall also apply on a primary and non-contributory basis for the benefit of City before the City’s own insurance or selfinsurance shall be called upon to protect it as a named insured. (D) City’s Rights of Enforcement. In the event any policy of insurance required under this Agreement does not comply with these specifications, or is canceled and not replaced, City has the right, but not the duty, to obtain the insurance it deems necessary, and any premium paid by City will be promptly reimbursed by Consultant, or City will withhold amounts sufficient to pay premium from Consultant payments. In the alternative, City may terminate this Agreement.
(E) Acceptable Insurers. All insurance policies shall be issued by an insurance company currently authorized by the Insurance Commissioner to transact business of insurance or is on the List of Approved Surplus Line Insurers in the State of California, with an assigned policyholders’ Rating of A- (or higher) and Financial Size Category Class VII (or larger) in accordance with the latest edition of Best’s Key Rating Guide, unless otherwise approved by the City’s Risk Manager.
(F) Waiver of Subrogation. All insurance coverage maintained or procured pursuant to this agreement shall be endorsed to waive subrogation against the City, its elected or appointed officers, agents, officials, employees, volunteers, and representatives or shall specifically allow Consultant or others providing insurance evidence in compliance with these specifications to waive their right of recovery prior to a loss. Consultant hereby waives its own right of recovery against the City, its elected or appointed officers, agents, officials, employees, volunteers and representatives and shall require similar written express waivers and insurance clauses from each of its subconsultants.
(G) Enforcement of Contract Provisions (non estoppel).
Consultant acknowledges and agrees that any actual or alleged failure on the part of the City to inform Consultant of non-compliance with any requirement imposes no additional obligations on the City nor does it waive any rights hereunder.
(H) Requirements Not Limiting. Requirements of specific coverage features or limits contained in this Section are not intended as a limitation on coverage, limits or other requirements, or a waiver of any coverage normally provided by any insurance.
Specific reference to a given coverage feature is for purposes of clarification only as it pertains to a given issue and is not intended by any party or insured to be all inclusive, or to the exclusion of other coverage, or a waiver of any type. If the Consultant maintains higher limits than the minimums shown above, the City requires and shall be entitled to coverage for the higher limits maintained by the Consultant. Any available insurance proceeds in excess of the specified minimum limits of insurance and coverage shall be available to the City. (I) Notice of Cancellation. Consultant agrees to oblige its insurance agent or broker and insurers to provide City with a thirty (30) day notice of cancellation (except for nonpayment for which a ten (10) day notice is required) or nonrenewal of coverage for each required coverage.
(J) Additional Insured Status. General liability, automobile liability, and if applicable, pollution liability and cyber liability, policies shall provide or be endorsed to provide that the City and its officers, officials, employees, agents, volunteers and 558
Contract No. ___________
7 Revised 01-2024
BBK 72500.00001\32374915.1
representatives shall be additional insureds with regard to liability and defense of suits or claims arising out of the performance of the Agreement, under such policies. This provision shall also apply to any excess/umbrella liability policies.
(K) Prohibition of Undisclosed Coverage Limitations. None of the coverages required herein will be in compliance with these requirements if they include any limiting endorsement of any kind that has not been first submitted to City and approved of in writing.
(L) Separation of Insureds. A severability of interests provision must apply for all additional insureds ensuring that Consultant’s insurance shall apply separately to each insured against whom claim is made or suit is brought, except with respect to the insurer’s limits of liability. The policy(ies) shall not contain any cross-liability exclusions. (M) Pass Through Clause. Consultant agrees to ensure that its subconsultants, subcontractors, and any other party involved with the Project who is brought onto or involved in the Project by Consultant, provide the same minimum insurance coverage and endorsements required of Consultant. Consultant agrees to monitor and review all such coverage and assumes all responsibility for ensuring that such coverage is provided in conformity with the requirements of this section. Consultant agrees that upon request, all agreements with subconsultants, subcontractors, and others engaged in the Project will be submitted to City for review.
(N) City’s Right to Revise Specifications. The City and the City’s Risk Manager reserve the right at any time during the term of the Agreement to change the amounts and types of insurance required by giving the Consultant ninety (90) days advance written notice of such change. If such change results in additional cost to the Consultant, the City and Consultant may renegotiate Consultant’s compensation. If the City reduces the insurance requirements, the change shall go into effect immediately and require no advanced written notice. (O) Self-Insured Retentions. Any self-insured retentions must be declared to and approved by City. City reserves the right to require that self-insured retentions be eliminated, lowered, or replaced by a deductible. Self-insurance will not be considered to comply with these specifications unless approved by City. (P) Timely Notice of Claims. Consultant shall give City prompt and timely notice of claims made or suits instituted that arise out of or result from Consultant’s performance under this Agreement, and that involve or may involve coverage under any of the required liability policies.
(Q) Additional Insurance. Consultant shall also procure and maintain, at its own cost and expense, any additional kinds of insurance, which in its own judgment may be necessary for its proper protection and prosecution of the Services.
3.2.12 Water Quality Management and Compliance. Consultant shall keep itself and all subcontractors, staff, and employees fully informed of and in compliance with all local, state and federal laws, rules and regulations that may impact, or be implicated by the performance of the Services including, without limitation, all applicable provisions of the City’s ordinances regulating water quality and storm water; the Federal Water Pollution Control Act (33 U.S.C. § 1251, et seq.); the California Porter-Cologne Water Quality Control Act (Water Code § 13000 et seq.); and any and all regulations, policies, or permits issued pursuant to any such authority.
Consultant must comply with the lawful requirements of the City, and any other municipality, 559
Contract No. ___________
8 Revised 01-2024
BBK 72500.00001\32374915.1
drainage district, or other local agency with jurisdiction over the location where the Services are to be conducted, regulating water quality and storm water discharges. Failure to comply with laws, regulations, and ordinances listed in this Section is a violation of federal and state law. Consultant warrants that all employees and subcontractors shall have sufficient skill and experience to perform the work assigned to them without impacting water quality in violation of the laws, regulations, and policies of this Section.
3.3 Fees and Payments.
3.3.1 Compensation. Contractor shall receive compensation, including authorized reimbursements, for all Services rendered under this Agreement at the rates set forth in Exhibit “C” attached hereto and incorporated herein by reference. The total compensation shall not exceed ONE MILLION THREE HUNDRED NINETY-SEVEN THOUSAND DOLLARS ($1,397,000.00) without written approval of the City Council or City Manager, as applicable.
3.3.2 Payment of Compensation. Consultant shall submit to City monthly invoices which provide a detailed description of the Services and hours rendered by Consultant.
City shall, within 30 days of receiving such invoice, review the invoice and pay all non-disputed and approved charges. If the City disputes any of Consultant's fees, the City shall give written notice to Consultant within thirty (30) days of receipt of an invoice of any disputed fees set forth therein. Consultant shall submit its final invoice to City within thirty (30) days from the last date of provided Services or termination of this Agreement and failure by the Consultant to submit a timely invoice may constitute a waiver of its right to final payment. Payment shall not constitute acceptance of any Services completed by Consultant. The making of final payment shall not constitute a waiver of any claims by the City for any reason whatsoever.
3.3.3 Reimbursement for Expenses. Consultant shall not be reimbursed for any expenses unless authorized in writing by City or included in Exhibit "C" of this Agreement.
3.3.4 Extra Work. At any time during the term of this Agreement, City may request that Consultant perform Extra Work. As used herein, "Extra Work" means any work which is determined by City to be necessary for the proper completion of the Project, but which the Parties did not reasonably anticipate would be necessary at the execution of this Agreement.
Consultant shall not perform, nor be compensated for, Extra Work without written authorization from the City.
3.4 Labor Code Requirements.
3.4.1 Prevailing Wages. Consultant is aware of the requirements of California Labor Code Section 1720, et seq., and 1770, et seq., as well as California Code of Regulations, Title 8, Section 16000, et seq., ("Prevailing Wage Laws"), which require the payment of prevailing wage rates and the performance of other requirements on "public works" and "maintenance" projects. If the Services are being performed as part of an applicable "public works" or "maintenance" project, as defined by the Prevailing Wage Laws, Consultant agrees to fully comply with such Prevailing Wage Laws. City shall provide Consultant with a copy of the prevailing rates of per diem wages in effect at the commencement of this Agreement. Consultant shall make copies of the prevailing rates of per diem wages for each craft, classification or type of worker needed to execute the Services available to interested parties upon request and shall post copies at the Consultant's principal place of business and at the project site. It is the intent of the parties to effectuate the requirements of sections 1771, 1774, 1775, 1776, 1777.5, 1813, and 1815 of the Labor Code within this Agreement, and Consultant shall therefore comply with such Labor Code sections to the fullest extent required by law. Consultant shall defend, indemnify, and hold the 560
Contract No. ___________
9 Revised 01-2024
BBK 72500.00001\32374915.1
City, its officials, officers, employees, agents, volunteers and representatives, free and harmless from any claim or liability arising out of any failure or alleged failure to comply with the Prevailing Wage Laws.
3.4.2 Registration/DIR Compliance. If the Services are being performed on a public works project of over $25,000 when the project is for construction, alteration, demolition, installation, or repair work, or a public works project of over $15,000 when the project is for maintenance work, in addition to the foregoing, then pursuant to Labor Code sections 1725.5 and 1771.1, the Consultant and all subconsultants must be registered with the Department of Industrial Relations (“DIR”). Consultant shall maintain registration for the duration of the Project and require the same of any subconsultants. This Project may also be subject to compliance monitoring and enforcement by the DIR. It shall be Consultant’s sole responsibility to comply with all applicable registration and labor compliance requirements, including the submission of payroll records directly to the DIR. Any stop orders issued by the DIR against Consultant or any subconsultant that affect Consultant’s performance of Services, including any delay, shall be Consultant’s sole responsibility. Any delay arising out of or resulting from such stop orders shall be considered Consultant caused delay and shall not be compensable by the City. Consultant shall defend, indemnify, and hold the City, its officials, officers, employees, agents, volunteers and representatives free and harmless from any claim or liability arising out of stop orders issued by the DIR against Consultant or any subconsultant.
3.4.3 Labor Certification. By its signature hereunder, Consultant certifies that it is aware of the provisions of Section 3700 of the California Labor Code which require every employer to be insured against liability for Worker's Compensation or to undertake self-insurance in accordance with the provisions of that Code and agrees to comply with such provisions before commencing the performance of the Services.
3.5 Accounting Records.
3.5.1 Maintenance and Inspection. Consultant shall maintain complete and accurate records with respect to all costs and expenses incurred under this Agreement. All such records shall be clearly identifiable. Consultant shall allow a representative of City during normal business hours to examine, audit, and make transcripts or copies of such records and any other documents created pursuant to this Agreement. Consultant shall allow inspection of all work, data, documents, proceedings, and activities related to the Agreement for a period of three (3) years from the date of final payment under this Agreement.
3.6 General Provisions.
3.6.1 Termination of Agreement.
3.6.1.1 Grounds for Termination. City may, by written notice to Consultant, terminate the whole or any part of this Agreement at any time and without cause by giving written notice to Consultant of such termination, and specifying the effective date thereof, at least seven (7) days before the effective date of such termination. Upon termination, Consultant shall be compensated only for those Services which have been adequately rendered to City, and Consultant shall be entitled to no further compensation. Consultant may not terminate this Agreement except for cause. The rights and remedies of the City provided in this section shall not be exclusive and are in addition to any other rights and remedies provided by law, equity or under this Agreement.
561
Contract No. ___________
10 Revised 01-2024
BBK 72500.00001\32374915.1
3.6.1.2 Effect of Termination. If this Agreement is terminated as provided herein, City may require Consultant to provide all finished or unfinished Documents and Data and other information of any kind prepared by Consultant in connection with the performance of Services under this Agreement. Consultant shall be required to provide such document and other information within fifteen (15) days of the request.
3.6.1.3 Early Termination. Notwithstanding any provision herein to the contrary, if for any fiscal year of this Agreement the City Council fails to appropriate or allocate funds for future payment under the Agreement after exercising reasonable efforts to do so, the City may upon seven (7) days’ written notice, order work on the Project to cease. Upon termination, Consultant shall be compensated only for those Services which have been adequately rendered to City, and Consultant shall be entitled to no further compensation.
3.6.1.4 Additional Services. In the event this Agreement is terminated in whole or in part as provided herein, City may procure, upon such terms and in such manner as it may determine appropriate, services similar to those terminated.
3.6.2 Delivery of Notices. All notices permitted or required under this Agreement shall be given to the respective parties at the following address, or at such other address as the respective parties may provide in writing for this purpose:
Consultant: PBK Architects
8163 Rochester Avenue
Rancho Cucamonga, CA 91730
ATTN: Lisa Cox, Principal Architect
City: City of Palm Desert
73-510 Fred Waring Drive
Palm Desert, CA 92260-2578
ATTN: Lucero Leyva, Capital Projects Department
Such notice shall be deemed made when personally delivered or when mailed, forty-eight (48) hours after deposit in the U.S. Mail, first class postage prepaid and addressed to the party at its applicable address. Actual notice shall be deemed adequate notice on the date actual notice occurred, regardless of the method of service.
3.6.3 Ownership of Materials and Confidentiality.
3.6.3.1 Documents & Data; Licensing of Intellectual Property. This Agreement creates a non-exclusive and perpetual license for City to copy, use, modify, reuse, or sublicense any and all copyrights, designs, and other intellectual property embodied in plans, specifications, studies, drawings, estimates, and other documents or works of authorship fixed in any tangible medium of expression, including but not limited to, physical drawings or data magnetically or otherwise recorded on computer diskettes, which are prepared or caused to be prepared by Consultant under this Agreement ("Documents & Data"). All Documents & Data shall be and remain the property of City and shall not be used in whole or in substantial part by Consultant on other projects without the City’s express written permission. Within thirty (30) days following the completion, suspension, abandonment or termination of this Agreement, Consultant shall provide to City reproducible copies of all Documents & Data, in a form and amount required by City. City reserves the right to select the method of document reproduction and to establish where the reproduction will be accomplished. The reproduction expense shall be borne by City at 562
Contract No. ___________
11 Revised 01-2024
BBK 72500.00001\32374915.1
the actual cost of duplication. In the event of a dispute regarding the amount of compensation to which the Consultant is entitled under the termination provisions of this Agreement, Consultant shall provide all Documents & Data to City upon payment of the undisputed amount. Consultant shall have no right to retain or fail to provide to City any such documents pending resolution of the dispute. In addition, Consultant shall retain copies of all Documents & Data on file for a minimum of fifteen (15) years following completion of the Project and shall make copies available to City upon the payment of actual reasonable duplication costs. Before destroying the Documents & Data following this retention period, Consultant shall make a reasonable effort to notify City and provide City with the opportunity to obtain the documents.
3.6.3.2 Subconsultants. Consultant shall require all subconsultants to agree in writing that City is granted a non-exclusive and perpetual license for any Documents & Data the subconsultant prepares under this Agreement. Consultant represents and warrants that Consultant has the legal right to license any and all Documents & Data. Consultant makes no such representation and warranty in regard to Documents & Data which were prepared by professionals other than Consultant or its subconsultants, or those provided to Consultant by the City.
3.6.3.3 Right to Use. City shall not be limited in any way in its use or reuse of the Documents and Data or any part of them at any time for purposes of this Project or another project, provided that any such use not within the purposes intended by this Agreement or on a project other than this Project without employing the services of Consultant shall be at City’s sole risk. If City uses or reuses the Documents & Data on any project other than this Project, it shall remove the Consultant’s seal from the Documents & Data and indemnify and hold harmless Consultant and its officers, directors, agents, and employees from claims arising out of the negligent use or re-use of the Documents & Data on such other project. Consultant shall be responsible and liable for its Documents & Data, pursuant to the terms of this Agreement, only with respect to the condition of the Documents & Data at the time they are provided to the City upon completion, suspension, abandonment, or termination. Consultant shall not be responsible or liable for any revisions to the Documents & Data made by any party other than Consultant, a party for whom the Consultant is legally responsible or liable, or anyone approved by the Consultant.
3.6.3.4 Indemnification – Documents and Data. Consultant shall defend, indemnify and hold the City, its directors, officials, officers, employees, volunteers, agents and representatives free and harmless, pursuant to the indemnification provisions of this Agreement, for any alleged infringement of any patent, copyright, trade secret, trade name, trademark, or any other proprietary right of any person or entity in consequence of the use on the Project by City of the Documents & Data, including any method, process, product, or concept specified or depicted.
3.6.3.5 Confidentiality. All ideas, memoranda, specifications, plans, procedures, drawings, descriptions, computer program data, input record data, written information, and other Documents & Data either created by or provided to Consultant in connection with the performance of this Agreement shall be held confidential by Consultant. Such materials shall not, without the prior written consent of City, be used by Consultant for any purposes other than the performance of the Services. Nor shall such materials be disclosed to any person or entity not connected with the performance of the Services or the Project. Nothing furnished to Consultant which is otherwise known to Consultant or is generally known, or has become known, to the related industry shall be deemed confidential. Consultant shall not use City's name or insignia, photographs of the Project, or any publicity pertaining to the Services or 563
Contract No. ___________
12 Revised 01-2024
BBK 72500.00001\32374915.1
the Project in any magazine, trade paper, newspaper, television or radio production or other similar medium without the prior written consent of City.
3.6.3.6 Confidential Information. The City shall refrain from releasing Consultant’s proprietary information ("Proprietary Information") unless the City's legal counsel determines that the release of the Proprietary Information is required by the California Public Records Act or other applicable state or federal law, or order of a court of competent jurisdiction, in which case the City shall notify Consultant of its intention to release Proprietary Information. Consultant shall have five (5) working days after receipt of the release notice to give City written notice of Consultant's objection to the City's release of Proprietary Information.
Consultant shall indemnify, defend, and hold harmless the City, and its officers, directors, employees, agents, volunteers and representatives from and against all liability, loss, cost or expense (including attorney’s fees) arising out of a legal action brought to compel the release of Proprietary Information. City shall not release the Proprietary Information after receipt of an objection notice unless either: (1) Consultant fails to fully indemnify, defend (with City's choice of legal counsel), and hold City harmless from any legal action brought to compel such release; and/or (2) a final and non-appealable order by a court of competent jurisdiction requires that City release such information.
3.6.4 Cooperation; Further Acts. The Parties shall fully cooperate with one another and shall take any additional acts or sign any additional documents as may be necessary, appropriate, or convenient to attain the purposes of this Agreement.
3.6.5 [Reserved]
3.6.6 Indemnification.
3.6.6.1 To the fullest extent permitted by law, Consultant shall defend (with counsel of City’s choosing), indemnify and hold the City, its officials, officers, employees, volunteers, agents, and representatives free and harmless from any and all claims, demands, causes of action, costs, expenses, liability, loss, damage or injury of any kind, in law or equity, to property or persons, including wrongful death, in any manner arising out of, pertaining to, or incident to any acts, errors or omissions, or willful misconduct of Consultant, its officials, officers, employees, subconsultants or agents in connection with the performance of the Consultant’s Services, the Project or this Agreement, including without limitation the payment of all expert witness fees, attorney’s fees and other related costs and expenses except such loss or damage caused by the sole negligence or willful misconduct of the City. Consultant's obligation to indemnify shall survive expiration or termination of this Agreement and shall not be restricted to insurance proceeds, if any, received by Consultant, the City, its officials, officers, employees, agents, volunteers, or representatives.
3.6.6.2 If Consultant’s obligation to defend, indemnify, and/or hold harmless arises out of Consultant’s performance as a “design professional” (as that term is defined under Civil Code section 2782.8), then, and only to the extent required by Civil Code section 2782.8, which is fully incorporated herein, Consultant’s indemnification obligation shall be limited to claims that arise out of, pertain to, or relate to the negligence, recklessness, or willful misconduct of the Consultant, and, upon Consultant obtaining a final adjudication by a court of competent jurisdiction, Consultant’s liability for such claim, including the cost to defend, shall not exceed the Consultant’s proportionate percentage of fault.
3.6.7 Entire Agreement. This Agreement contains the entire agreement of the Parties with respect to the subject matter hereof, and supersedes all prior negotiations, 564
Contract No. ___________
13 Revised 01-2024
BBK 72500.00001\32374915.1
understandings, or agreements.
3.6.8 Governing Law. This Agreement shall be governed by the laws of the State of California. Venue shall be in Riverside County.
3.6.9 Time of Essence. Time is of the essence for each and every provision of this Agreement.
3.6.10 City's Right to Employ Other Consultants. City reserves right to employ other consultants in connection with this Project.
3.6.11 Successors and Assigns. This Agreement shall be binding on the successors and assigns of the Parties.
3.6.12 Assignment; Subcontracting. Consultant shall not assign, sublet, or transfer this Agreement or any rights under or interest in this Agreement without the written consent of the City, which may be withheld for any reason. Any attempt to so assign or so transfer without such consent shall be void and without legal effect and shall constitute grounds for termination. Consultant shall not subcontract any portion of the Services required by this Agreement, except as expressly stated herein, without prior written approval of City.
Subcontracts, if any, shall contain a provision making them subject to all provisions stipulated in this Agreement.
3.6.13 Construction; References; Captions. Since the Parties or their agents have participated fully in the preparation of this Agreement, the language of this Agreement shall be construed simply, according to its fair meaning, and not strictly for or against any Party. Any term referencing time, days or period for performance shall be deemed calendar days and not workdays. All references to Consultant include all personnel, employees, agents, and subconsultants of Consultant, except as otherwise specified in this Agreement. All references to City include its elected officials, officers, employees, agents, volunteers, and representatives except as otherwise specified in this Agreement. The captions of the various articles and paragraphs are for convenience and ease of reference only, and do not define, limit, augment, or describe the scope, content, or intent of this Agreement.
3.6.14 Amendment; Modification. No supplement, modification, or amendment of this Agreement shall be binding unless executed in writing and signed by both Parties.
3.6.15 Waiver. No waiver of any default shall constitute a waiver of any other default or breach, whether of the same or other covenant or condition. No waiver, benefit, privilege, or service voluntarily given or performed by a Party shall give the other Party any contractual rights by custom, estoppel, or otherwise.
3.6.16 No Third-Party Beneficiaries. There are no intended third-party beneficiaries of any right or obligation assumed by the Parties.
3.6.17 Invalidity; Severability. If any portion of this Agreement is declared invalid, illegal, or otherwise unenforceable by a court of competent jurisdiction, the remaining provisions shall continue in full force and effect.
3.6.18 Prohibited Interests. Consultant maintains and warrants that it has not employed nor retained any company or person, other than a bona fide employee working solely for Consultant, to solicit or secure this Agreement. Further, Consultant warrants that it has not 565
Contract No. ___________
14 Revised 01-2024
BBK 72500.00001\32374915.1
paid, nor has it agreed to pay any company or person, other than a bona fide employee working solely for Consultant, any fee, commission, percentage, brokerage fee, gift or other consideration contingent upon or resulting from the award or making of this Agreement. For breach or violation of this warranty, City shall have the right to rescind this Agreement without liability. For the term of this Agreement, no member, officer, or employee of City, during the term of his or her service with City, shall have any direct interest in this Agreement, or obtain any present or anticipated material benefit arising therefrom.
3.6.19 Authority to Enter Agreement. Consultant has all requisite power and authority to conduct its business and to execute, deliver, and perform the Agreement. Each Party warrants that the individuals who have signed this Agreement have the legal power, right, and authority to make this Agreement and bind each respective Party.
3.6.20 Counterparts. This Agreement may be signed in counterparts, each of which shall constitute an original.
3.6.21 Survival. All rights and obligations hereunder that by their nature are to continue after any expiration or termination of this Agreement, including, but not limited to, the indemnification obligations, shall survive any such expiration or termination. [SIGNATURES ON NEXT PAGE]
566
Contract No. ___________
15 Revised 01-2024
BBK 72500.00001\32374915.1
SIGNATURE PAGE TO PROFESSIONAL SERVICES AGREEMENT
BY AND BETWEEN THE CITY OF PALM DESERT
AND PBK ARCHITECTS
IN WITNESS WHEREOF, each of the Parties has caused this Agreement to be executed on the day and year first above written.
CITY OF PALM DESERT
By:
L. Todd Hileman
City Manager
Attest:
By:
Anthony J. Mejia
City Clerk
Approved as to form:
By:
Isra Shah
Best Best & Krieger LLP
City Attorney
PBK ARCHITECTS, A CORPORATION
By:
Chris Cunico
President
By:
Kelley Needham
Secretary
QC: _____
Insurance:
_____
Initial Review
_____
Final Approval
567
Contract No. ___________
Exhibit “A” Revised 01-2024
BBK 72500.00001\32374915.1
EXHIBIT “A”
SCOPE OF SERVICES/SCHEDULE OF SERVICES
568
Contract No. ___________
Exhibit “B” Revised 01-2024
BBK 72500.00001\32374915.1
EXHIBIT "B"
COMPENSATION
THE AMOUNT IS NOT TO EXCEED ONE MILLION TWO HUNDRED FORTY THOUSAND DOLLARS ($1,240,000)
569
570
June 6, 2024
Ms. Melanie Perry
Senior Management Analyst
City of Palm Desert
73-510 Fred Waring Drive
Palm Desert, CA 92260
Re: Preliminary Fee Proposal
Fire Stations 33 and 71
City of Palm Desert
Dear Ms. Perry:
Attached please find our Preliminary Fee Proposal for the above referenced project. With our unique type of experience and our local presence, your new project is of special interest to our firm.
In that architecture is a professional service as opposed to a commodity, we believe that the selection of an architect is not only about fee, but about the relationship between the design team and the City. This proposal is intended as a starting point to begin more in depth discussions regarding program and project scope. It is not our intention to create a fee that is more or less than our professional colleagues, but to work with you to create the best possible project for the funds available.
The fees attached are not intended to be a “take it or leave it” offer and should be understood to be the beginning of a negotiation to determine the best value for your needs and budget.
Ms. Perry, thank you again for this opportunity. If you should have any questions or require any additional information, please do not hesitate to contact me at any time.
Very truly yours,
LISA COX, AIA
Principal, Architect
KN:LC:hb\24020-mkt
Attachment: Preliminary Fee Proposal
571
Preliminary Fee Proposal
Your contract with PBK will mark a purposeful investment in your facilities. We are here to make sure that you consider that investment to be a good one, with significant returns. PBK is extremely flexible when it comes to the fee structure that best suits each new commission. We want the City and Fire Department to feel that you are getting both a quality architectural product and excellent professional services at a fair market price.
In an effort to better define our fee proposal, we have broken it down into the following components:
A. Basic Architectural Fee - Fire Station 33
B. Project Specific Fees - Fire Station 33
C. Basic Architectural Fee - Fire Station 71
D. Project Specific Feel - Fire Station 71
E. Total Fee
F. Reimbursables
G. Items Excluded
H. Hourly Rate Schedule
A description of each component is as follows:
A. BASIC ARCHITECTURAL FEE - FIRE STATION 33
Our fee for basic architectural services will be a fixed lump sum and includes the following disciplines:
• Civil Engineering
• Architectural Design
• Structural Engineering
• Mechanical Engineering
• Electrical Engineering
• Landscape Architecture
Our fee includes all on-site improvements, circulation areas, parking areas, and landscaping. For the purposes of establishing a fee, we have assumed a preliminary construction budget of $6,000,000.00. The fee will be adjusted to correspond to any increases in project scope. A breakdown of our proposed fee is as follows:
PHASE OF SERVICE FEE
Schematic Design $ 93,000.00
Design Development 62,000.00
Construction Documents 310,000.00
Bidding 31,000.00
Construction Administration 124,000.00
TOTAL BASIC ARCHITECTURAL FEE $ 620,000.00
Fire Stations 33 and 71 Assessment Page 1
572
B. PROJECT SPECIFIC FEES - FIRE STATION 33
The following items are unique to each project and not typically found in the basic scope of architectural services. Based on our experience and interpretation of the information available, we believe the following services will also be required:
TASK
Topographical Survey $ 14,000.00
Geotechnical Investigation 20,000.00
Hazardous Material Survey 3,000.00
Environmental Planning (CEQA) 27,000.00 *
SWPPP 3,000.00
TOTAL PROJECT SPECIFIC FEE $67,000.00
* The Environmental Planning is based on preparation of an Initial Study and an assumed Categorical Exemption. Technical Studies for air quality, noise and cultural resources have been included.
C. BASIC ARCHITECTURAL FEE - FIRE STATION 71
Our fee for basic architectural services will be a fixed lump sum and includes the following disciplines:
• Civil Engineering
• Architectural Design
• Structural Engineering
• Mechanical Engineering
• Electrical Engineering
• Landscape Architecture
Our fee includes all on-site improvements, circulation areas, parking areas, landscaping and off-site street improvements. For the purposes of establishing a fee. A preliminary construction budget of $6,500,000.00. The fee will be adjusted to correspond to any increases in project scope. A breakdown of our proposed fee is as follows:
PHASE OF SERVICE FEE
Schematic Design $ 93,000.00
Design Development 62,000.00
Construction Documents 310,000.00
Bidding 31,000.00
Construction Administration 124,000.00
TOTAL BASIC ARCHITECTURAL FEE $ 620,000.00
Fire Stations 33 and 71 Assessment Page 2
573
D. PROJECT SPECIFIC FEES - FIRE STATION 71
The following items are unique to each project and not typically found in the basic scope of architectural services. Based on our experience and interpretation of the information available, we believe the following services will also be required:
TASK
Topographical Survey $ 14,000.00
Geotechnical Investigation 20,000.00
Hazardous Material Surveys 3,000.00
Environmental Planning (CEQA) 30,000.00 *
SWPPP 3,000.00
TOTAL PROJECT SPECIFIC FEE $ 70,000.00
* The Environmental Planning is based on preparation of an Initial Study and an assumed Categorical Exemption. Technical Studies for air quality, noise and cultural resources have been included.
E. TOTAL FEE
The following is the total of all fees along with an allowance for reimbursables:
SERVICE
Basic Architectural Fees (Both Stations) $ 1,240,000.00 Project Specific Fees (Both Stations) 137,000.00
Reimbursable Allowance 20,000.00
TOTAL FEE $ 1,397,000.00
F. REIMBURSABLES
Items required or requested by the City, Fire Department, or approving agency will be invoiced as reimbursable without markup on monthly intervals. Reimbursables generally include the following:
1. Bulk paper copy.
2. Printing/Mylars.
3. Express or overnight mail/courier service.
The City will not incur any cost for travel, travel time, phone calls, faxes, or incidental printing or copying.
Fire Stations 33 and 71 Assessment Page 3
574
G. ITEMS EXCLUDED
The following is a list of items which are excluded from our scope of services or are not anticipated to be required. However, these services can be included, if requested, or once additional information is known:
1. Plan Check/Permit Fees.
2. Professionally Constructed Building Models.
3. Shoring Design.
4. Arborist/Biologist Reports.
5. Construction Surveying/Staking.
6. Cone Penetration Testing.
7. QSP services during construction.
8. QSD services during construction.
9. Radius maps, mailing lists and public hearing signage.
10. Traffic control plans.
11. County, State, Title Company and Utility Purveyor Fees.
12. Soil Management or Agronomy Reports.
13. Services related to an Underground Parking Structure.
14. Preparation of a Record of Survey map or corner record as required by the City or County.
15. Services related to the undergrounding of overhead utility lines, or the relocation/replacement of poles, along the street or alley frontages.
16. Foundation System: Our fee assumes typical spread footings in average soil conditions. Any other type of foundation system required as a result of poor soil conditions would not be considered within our scope of work.
17. Multiple bid packages.
18. Commissioning.
Fire Stations 33 and 71 Assessment Page 4
575
F. HOURLY RATE SCHEDULE
For additional services, the following hourly rates are proposed for the basis of negotiating scope modifications which may be necessary for the project. Hourly rates include mark-up that will be applied to all fees. Reimbursable costs for reprographic services, computer plotting, and printing will be negotiated at the time additional services are requested.
ARCHITECT
Principals of Firm $260.00
Design Director $220.00
Senior Project Manager $210.00
Senior Project Architect $210.00
Project Manager $190.00
Project Architect $185.00
Project Leader / Technical Leader $155.00
Project Coordinator $140.00
Architectural Intern / Designer $130.00
Intern $100.00
Senior Project Designer $200.00
Project Designer $185.00
Design Leader $140.00
Designer II $135.00
Designer $110.00
Senior Ed Facilities Planner $230.00
Facilities Planner $185.00
Senior Construction Administrator $210.00
Construction Administrator $175.00
Sustainable Designer $160.00
Specification Writer $185.00
Agency Compliance $110.00
Cost Estimator $210.00
Clerical / Office $110.00
CIVIL ENGINEER
Principal $185.00
Project Manager $150.00
Project Surveyor $120.00
Design Engineer $100.00
Draftsperson $ 75.00
Project Assistant $ 60.00
STRUCTURAL ENGINEER
Principal Engineer $175.00
Project Engineer $150.00
Chief Draftsman $110.00
Draftsman $ 90.00
Technical Support $ 75.00
ELECTRICAL ENGINEER
Principal $175.00
Project Manager $135.00
Project Engineer $125.00
Designer $ 95.00
Designer/CADD Technician $ 90.00
Jr. Designer/CADD Technician $ 80.00
CADD Technician/Drafter $ 70.00
Technical Support $ 50.00
MECHANICAL ENGINEER
Principal $225.00
Associate Principal $205.00
Senior Project Manager $195.00
Project Manager $185.00
Senior Project Engineer $170.00
Project Engineer $150.00
Senior Design Engineer $135.00
Design Engineer $125.00
Senior Designer $115.00
Designer $105.00
CADD Designer $100.00
CADD Technician $ 80.00
Administrative $ 75.00
Technical Support $ 65.00
LANDSCAPE ARCHITECT
Principal Architect $165.00
Associate Architect $140.00
Architect/Project Manager $125.00
Job Captain/Designer $110.00
CADD Technician $ 95.00
Draftsperson $ 80.00
Technical Support $ 65.00
ENVIRONMENTAL ENGINEER
Senior Director $225.00
Program Manager $200.00
Senior Project Manager $165.00
Project Manager $140.00
Project Assistant $ 82.00
Technical Support $ 62.00
Fire Stations 33 and 71 Assessment Page 5
576
CITY OF PALM DESERT
CITY MANAGER’S OFFICE
INTEROFFICE MEMORANDUM
Date: July 11, 2024
To: Honorable Mayor and Councilmembers
From: Anthony J. Mejia, City Clerk
Subject: City Council Meeting of July 11, 2024
Below you will find questions received from the Mayor or Councilmembers and answers provided by City staff regarding tonight’s City Council meeting:
ITEM 2a: STUDY SESSION: IMPERIAL IRRIGATION DISTRICT’S ENERGY INFRASTRUCTURE
PARTNERSHIP
Q1: Regarding the IID substation, is it correct that we will not be liable for the $5 million in bonds, as we will either be reimbursed by other property owners or indirectly through increased sales tax revenue over several years
A1: The City would front the initial cash outlay to get the substation underway and then require payback agreements prior to the landowners developing their properties. The City may be out $1- $3 million over the next decade or two depending on the speed of development. Without the substation, the property owners are frozen out.
ITEM 13a: APPROVAL OF CITY COUNCIL, SUCCESSOR AGENCY, AND HOUSING AUTHORITY
MINUTES
After further review, the City Clerk recommends the approval of the June 27, 2024, City Council Meeting minutes with the following revision:
15a. APPEAL OF THE BUILDING BOARD OF APPEALS DETERMINATION OF THE CHIEF BUILDING OFFICIAL’S APPLICATION OF THE 2022 CALIFORNIA RESIDENTIAL CODE, SECTION R310.1 (EMERGENCY ESCAPE AND RESCUE)
Dylan Guzel, provided closing remarks on behalf of the City, asserted that there are regulations that businesses are required to follow that homeowners do not in order to protect the public; asserted that this action is not considered a regulatory taking as the City stated the room was never intended to be a bedroom, the City did not sell or advertise the unit, and the City upheld the Code at the time of construction.
Dylan Guzel, Deputy City Attorney, provided closing remarks on behalf of the City; pointed out that a vacation rental is a commercial endeavor which is subject to regulations similar to other businesses; noted these regulations are in place for the public health and safety during emergencies; asserted that the County Assessor’s Office statements regarding the number of bedrooms are based on a visual floorplan inspection without comparison to the California Building Codes and pointed out these representatives are not official building inspectors, architects, engineers, or professionals in that capacity; opined that the City’s actions are not a regulatory taking as the City has consistently applied the building code standard that dens cannot be used as a sleeping room and had no role in the advertising or marketing of the property. 577
06/27/2024 Question & Answer Memo
Carrie Kropfl, Appellant, provided closing remarks; stated she represents the innocent victims; urged the City prepare a disclosure form for short-term rental operators and renters, and send a cease and desist letter to Monterey Country Club property management.
Carrie Kropfl, Appellant, provided closing remarks; voiced support for allowing potential renters to sign a disclosure form regarding the use of a den as a sleeping room; asserted that other communities have advertised dens attached to an atrium as bedrooms and that Coachella Valley cities need to address false advertising, including the City of Palm Desert issuing a cease and desist letter to the Monterey County Club management; opined that the City’s interpretation will impact not only vacation rental owners but also all properties with a similar floorplan, leading to a reduction of a bedroom and decreased property values.
ITEM 13b: APPROVAL OF WARRANT REGISTERS
Q1: Where is the $13 million coming from to buy the parcels? (Page 43) A1:The sale of the property at Desert Willow (DW) is $4.6 million. That’s the only amount coming from the City. There are a few transactions happening in this one register:
1. The City is buying the property (DW Parking Lot) from the SARDA at Fair Market Value ($4.6M) from our Golf Amenity Fees - Capital Funds (441) with the first wire - #57353787.
2. The 2nd and 3rd wires are a result of staff reaching out to the County due to a stale dated check.
The County of Riverside lost the SARDA check ($4.4M) related to the sale of land from SARDA to Vitalia/Pacific West for affordable housing, so we canceled payment and reissued wire #71465195. The additional $16k, was a separate part of that transaction as well - #71465387.
3. The SARDA then sent the $4.6M proceeds (DW Parking Lot) to the County of Riverside for distribution to the various taxing entities - #72032577.
Ultimately, the City (as a taxing entity) will receive a small apportionment from each of these transactions. Those proceeds are then deposited into the Economic Development Fund upon receipt.
ITEM 13g: ADOPT RESOLUTION OPTING INTO SETTLEMENT AGREEMENT WITH
DISTRIBUTORS OF OPIOIDS, GROCERY CHAIN KROGER, AND FUTURE PROPOSED
OPIOD SETTLEMENTS
Q1: What is the estimated amount that the City is expected to receive from this settlement? A1: Based on the amount awarded to the State of California and our other settlement allocations, an estimate could be around $40,000 disbursed over 11 years. 578
06/27/2024 Question & Answer Memo
ITEM 13j: AWARD CONTRACT TO PBK ARCHITECTS, INC., FOR ARCHITECTURAL DESIGN SERVICES OF FIRE STATION 33 AND 71 (CFA00017 & CFA00019) Q1: This item includes the recommendation to demolish and rebuild Station 71. Is this item intended to approve that recommendation? If so, could you provide more information on the following aspects:
a. What is the justification for this recommendation given that a rebuild costs $1,272,905 more than renovation?
b. What is the plan for timing and provision of services during the demolition and rebuild process?
c. How will service disruptions be managed, considering that renovations can be done in stages to minimize disruptions, whereas demolition and rebuild inherently include delays? A1: Staff estimates that the construction will take approximately 12-14 months. The current plan involves setting up temporary housing for both Fire Stations during this period to minimize impacts on response times. We considered moving staff to other Fire Stations and having FS 102 assist with calls from FS 67. However, current trends indicate that assistance from FS 102 to FS 71 will be limited. CalFire Chiefs support the recommendation for temporary housing.
FS 33 has ample space to accommodate a temporary site. However, FS 71 is located on a small parcel, making it impossible to host temporary housing and construction activities simultaneously.
Therefore, staff is exploring nearby city-owned lots for temporary housing, bays, and equipment during construction. The goal is to minimize impacts on response times as much as possible. Staff will continue to adjust this plan as the design progresses.
The renovations will involve the demolition and structural reconfiguration of the building's interior, making it unsafe for Cal Fire staff to work in the building during construction.
ITEM 13k: AWARD ON-CALL CONTRACTS TO MULTIPLE VENDORS FOR PARK AND
FACILITIES REPAIRS AND IMPROVEMENT PROJECTS
Q1: What has been the budgeted dollar amount for these CIP projects in previous years? This year's budget is $5.3 million.
A1: Although the on-call facilities maintenance and repair agreements can be utilized to complete task orders for capital projects, staff primarily utilize the agreements to accomplish updates on deferred maintenance or minor repair projects as needed. The budget for these agreements includes both capital and operations funding.
Previous fiscal years’ Park and Facilities CIP project budgets are below:
• Fiscal Year 24/25 $5.3 Million
• Fiscal Year 23/24 $4.0 Million, increased to $5.7
• Fiscal Year 22/23 $3.5 Million
• Fiscal Year 21/22 $2.0 Million
579
06/27/2024 Question & Answer Memo
ITEM 13l: AWARD CONTRACT NO. C47680 TO JACOBSSON ENGINEERING CONSTRUCTION, INC., FOR THE EL PASEO CURB RAMP MODIFICATION PROJECT (PROJECT CST00025)
Q1: Can you provide the additional cost of undertaking this project as a standalone effort compared to incorporating it into the overall repaving scheduled for 2025? A1: Staff did not anticipate additional costs would be incurred by the City from splitting the project into two phases. The concrete work that will be constructed in Phase I of the project is typically performed by a subcontractor and the prime contractor marks up the subcontractors bid 10-15% to cover administration expenses related to the subcontract. By bidding the concrete work and the asphalt work separately staff expects the markup will be eliminated.
Q2: This item refers to curb and gutter work intended to be completed "in the summer of 2024." As it is now July 10th, could you please provide an updated timetable for this work? Given the current date, is it still feasible to complete the project within the summer timeframe? A2: The project will begin construction by August 1, 2024, and will be completed by September 15, 2024.The intent is to complete the project before the beginning of the busy season.
ITEM 13n: REJECT ALL PROPOSALS SUBMITTED FOR COURTESY PATROL SERVICES AT THE
HOUSING AUTHORITY PROPERTIES
Q1: Why did Courtesy Patrol Services decline to renew their contract? A1: The current service provider indicated that they are facing difficulties in securing the necessary insurance coverage, which has been an ongoing issue.
ITEM 13o: REJECT ALL BIDS, APPROPRIATE FUNDS, AUTHORIZE THE CITY MANAGER TO
AWARD A CONTRACT FOR THE CIVIC CENTER PARKING LOT REHABILITATION PROJECT IN AN AMOUNT NOT TO EXCEED $600,000
Q1: is this project for repaving or resealing/slurry?
A1: The entry/exit drive at Fred Waring is a re-pave, while the rest of the parking lot will be repaired as needed and slurry sealed. There is also a crosswalk near the Desert Recreation building that will be replaced with concrete. Please reference the “Area of Work Aerial” for further clarification.
ITEM 13s: APPROVE CONTRACT WITH FEHR & PEERS FOR THE PREPARATION OF A
GENERAL PLAN AMENDMENT TO THE MOBILITY ELEMENT IN AN AMOUNT NOT TO EXCEED $139,076 AND APPROPRIATE FUNDS
Q1: Can the language of the deliverables in Task 6 be revised to align with the broader scope described in the staff report, ensuring it includes collaboration with SunLine Transit Agency for a variety of public transit solutions, not just the evaluation of existing and proposed bus lines?
A1: This action will be included in Task 6 of the Scope of Work found in Exhibit A of the Professional Services Agreement. The formatting and text of the agreement for Task 6 has been revised to add a new bullet point for "Collaboration with SunLine Transit Agency ("STA") for a variety of public transit solutions". This will be in addition to the deliverable item for evaluation of existing and proposed bus lines. Staff has also revised task 3.1 to require collaboration with STA. 580
06/27/2024 Question & Answer Memo
ITEM 14d: CONSIDERATION FOR APPROVAL OF A PORTION OF PUBLIC RIGHT-OF-WAY (EXPLORER DRIVE) IS “EXEMPT SURPLUS LAND” PURSUANT TO GOVERNMENT CODE SECTION 54221
Q1: Is this decision consistent with our previous surplus land/right-of-way decision that we voted on in South Palm Desert a few months ago?
A1: There is a small sliver of property that was missed in the original land sale to Refuge that needs to be addressed. Therefore, this portion of the city right-of-way was not in the City’s Central Inventory. The process will be consistent with the Surplus Land Act (SLA) requirements. Once the SLA process is cleared, the same per square foot charge will be applied to this property as was used in the initial sale.
ITEM 14e: ADOPT RESOLUTION APPROVING FINAL TRACT MAP NO. 38434-1 AND
AGREEMENTS
Q1: Could you provide the zoning rules that applied to the vacant land at the time when the property was developed and homes were sold on the south border of this development? Specifically, what was the maximum allowable height? Additionally, if there have been any changes to these zoning rules, when did they occur?
A1: In October 1995, during the original approval of residential Tract 28258, the vacant land ("Refuge Site") was designated PR-5 (Planned Residential 5 dwelling units/acre). The PR zoning designation allowed buildings up to two-stories with a maximum height of 24', with a minimum setback of 100' from the project perimeter for all two-story, detached, single-family structures.
In June 2012, as a requirement of State Housing Element law, the City approved a change of zone for a 38-acre portion of the Refuge Site from PR-5 to Planned Residential 20 dwelling units per acre (PR-20). The development standards for the PR zoning district did not substantially change until 2017.
In August 2017, as a part of a general plan consistency update, the City approved a change of zone for the entire vacant Refuge Site to PR-20 and amended the PR zoning district to allow threestory buildings with a maximum height to 40'-0", with a minimum setback of 100' from the project perimeter for all two-story, detached, single-family structures. 581
1 Revised 07-2023
BBK 72500.00001\32374915.1
CITY OF PALM DESERT
PROFESSIONAL SERVICES AGREEMENT
1. Parties and Date. This Agreement is made and entered into this 11th day of July, 2024, by and between the City of Palm Desert, a municipal corporation organized under the laws of the State of California with its principal place of business at 73-510 Fred Waring Drive, Palm Desert, California 92260-2578 (“City”) and FEHR & PEERS an S Corporation, with its principal place of business at 100 PRINGLE AVENUE, SUITE 600, WALNUT CREEK, CA 94596("Consultant").
The City and Consultant are sometimes individually referred to herein as "Party" and collectively as "Parties."
2. Recitals.
2.1 Project.
The City is a public agency of the State of California and is in need of professional services for the following project:
Amendment of the Palm Desert Mobility (Circulation) Element of the General Plan (hereinafter referred to as “the Project”).
2.2 Consultant.
Consultant desires to perform and assume responsibility for the provision of certain professional services required by the City on the terms and conditions set forth in this Agreement.
Consultant is duly licensed and has the necessary qualifications to provide such services.
3. Terms.
3.1 Scope of Services and Term.
3.1.1 General Scope of Services. Consultant promises and agrees to furnish to the City all labor, materials, tools, equipment, services, and incidental and customary work necessary to supply the services for the Project ("Services") as more particularly described in Exhibit "A" attached hereto and incorporated herein by reference. All Services shall be subject to, and performed in accordance with, this Agreement, the exhibits attached hereto and incorporated herein by reference, and all applicable local, state and federal laws, rules and regulations.
3.1.2 Term. The term of this Agreement shall be from July 1, 2024, to June 30, 2025, unless earlier terminated as provided herein. The City shall have the unilateral option, at its sole discretion, to renew this Agreement automatically for no more than TWO additional one-year terms. Contractor shall complete the Services within the term of this Agreement and shall meet any other established schedules and deadlines.
3.2 Responsibilities of Consultant.
3.2.1 Independent Contractor; Control and Payment of Subordinates.
The Services shall be performed by Consultant or under its supervision. Consultant will determine the means, methods, and details of performing the Services subject to the requirements of this Agreement. City retains Consultant on an independent contractor basis and not as an employee.
Any personnel performing the Services shall not be employees of City and shall at all times be under Consultant's exclusive direction and control. Neither City, or any of its officials, officers, directors, employees, or agents shall have control over the conduct of Consultant or any of Consultants officers, employees or agents, except as set forth in this Agreement. Consultant shall pay all wages, salaries, and other amounts due such personnel in connection with their performance of Services under this Agreement and as required by law. Consultant shall be 07/11/2024
Item 13s
Revised Agreement
582
Contract No. C48060
2 Revised 07-2023
BBK 72500.00001\32374915.1
responsible for all reports and obligations respecting such additional personnel, including, but not limited to: social security taxes, income tax withholding, unemployment insurance, disability insurance, and workers' compensation insurance.
3.2.2 Schedule of Services. Consultant shall perform the Services in accordance with the Schedule of Services set forth in Exhibit "B" attached hereto and incorporated herein by reference. Consultant represents that it has the professional and technical personnel required to perform the Services as expeditiously as is required by the Schedule of Services and the standard of care applicable to Consultant’s Services. Upon reasonable request of City, Consultant shall provide a more detailed schedule of anticipated performance to meet the Schedule of Services.
3.2.3 Conformance to Applicable Requirements. All work prepared by Consultant shall be in accordance with this Agreement .
3.2.4 Substitution of Key Personnel. Consultant has represented to City that certain key personnel will perform and coordinate the Services. Should one or more of such personnel become unavailable, Consultant may substitute other personnel of at least equal competence upon written approval of City. In the event that City and Consultant cannot agree as to the substitution of key personnel, City shall be entitled to terminate this Agreement for cause.
The key personnel for performance of this Agreement are as follows: JASON D. PACK.
3.2.5 City's Representative. The City hereby designates Nick Melloni, Principal Planner, or his/her designee, to act as its representative in all matters pertaining to the administration and performance of this Agreement ("City's Representative"). City's Representative shall have the power to act on behalf of the City for review and approval of all products submitted by Consultant but not the authority to enlarge the scope of Services or change the total compensation due to Consultant under this Agreement. The City Manager shall be authorized to act on City's behalf and to execute all necessary documents which enlarge the scope of services or change the Consultant's total compensation subject to the provisions contained in Section 3.3 of this Agreement. Consultant shall not accept direction or orders from any person other than the City Manager, City's Representative or his/her designee.
3.2.6 Consultant's Representative. Consultant hereby designates JASON D. PACK, or his/her designee, to act as its representative for the performance of this Agreement ("Consultant's Representative"). Consultant's Representative shall have full authority to represent and act on behalf of the Consultant for all purposes under this Agreement. The Consultant's Representative shall supervise and direct the Services, using his/her best skill and attention, and shall be responsible for all means, methods, techniques, sequences, and procedures and for the satisfactory coordination of all portions of the Services under this Agreement.
3.2.7 Coordination of Services. Consultant agrees to work closely with City staff in the performance of Services and shall be available to City's staff, consultants, and other staff at all reasonable times.
3.2.8 Standard of Care; Performance of Employees. Consultant shall perform all Services exercising that degree of care, skill, and diligence ordinarily exercised by professionals performing similar services in the same or similar locale and under similar circumstances that of Consultant under this Agreement . Consultant represents and maintains that it is skilled in the professional calling necessary to perform the Services. Consultant warrants that all employees and subconsultants shall have sufficient skill and experience to perform the 583
Contract No. C48060
3 Revised 07-2023
BBK 72500.00001\32374915.1
Services assigned to them. Consultant represents that it, its employees and subconsultants have all licenses, permits, qualifications and approvals of whatever nature that are legally required to perform the Services, and that such licenses and approvals shall be maintained throughout the term of this Agreement. Consultant shall perform, at its own cost and expense and without reimbursement from the City, any services necessary to correct errors or omissions which are caused by the Consultant's failure to comply with the standard of care provided herein. Any employee of the Consultant or its sub-consultants who is determined by the City to be uncooperative, incompetent, a threat to the adequate or timely completion of the Project, a threat to the safety of persons or property, or any employee who fails or refuses to perform the Services in a manner acceptable to the City, shall be promptly removed from the Project by the Consultant and shall not be re-employed to perform any of the Services or to work on the Project.
3.2.9 Period of Performance. Consultant shall perform and complete all Services under this Agreement within the term set forth in Section 3.1.2 above (“Performance Time”). Consultant shall also perform the Services in accordance with any completion schedule or Project milestones described in Exhibits “A” or “B” attached hereto, or which may be separately agreed upon in writing by the City and Consultant (“Performance Milestones”). Consultant agrees that if the Services are not completed within the aforementioned Performance Time and/or pursuant to any such Performance Milestones developed pursuant to provisions of this Agreement, it is understood, acknowledged and agreed that the City will suffer damage.
Neither City nor Consultant shall be considered in default of this Agreement for delays in performance caused by circumstances beyond the reasonable control of the non-performing Party. For purposes of this Agreement, such circumstances include a Force Majeure Event. A Force Majeure Event shall mean an event that materially affects a Party’s performance and is one or more of the following: (1) Acts of God or other natural disasters; (2) terrorism or other acts of a public enemy; (3) orders of governmental authorities (including, without limitation, unreasonable and unforeseeable delay in the issuance of permits or approvals by governmental authorities that are required for the services); (4) strikes and other organized labor action occurring at the site and the effects thereof on the services, only to the extent such strikes and other organized labor action are beyond the control of Consultant and its subcontractors, and to the extent the effects thereof cannot be avoided by use of replacement workers; (5) pandemics, epidemics or quarantine restrictions; or (6) any other causes beyond the reasonable control of the defaulting or delayed Party. For purposes of this section, “orders of governmental authorities,” includes ordinances, emergency proclamations and orders, rules to protect the public health, welfare and safety, and other actions of a public agency applicable to the services and Agreement.
Should a Force Majeure Event occur, the non-performing Party shall, within a reasonable time of being prevented from performing, give written notice to the other Party describing the circumstances preventing continued performance and the efforts being made to resume performance of this Agreement. Force Majeure Events and/or delays, regardless of the Party responsible for the delay, shall not entitle Consultant to any additional compensation.
Notwithstanding the foregoing in this section, the City may still terminate this Agreement in accordance with the termination provisions of this Agreement.
3.2.10 Laws and Regulations; Employee/Labor Certification. Consultant shall keep itself fully informed of and in compliance with all local, state and federal laws, rules and regulations in any manner affecting the performance of the Project or the Services and shall give all notices required by law. Consultant shall be liable for all violations of such laws and regulations in connection with the Services and this Agreement. All violations of such laws and regulations shall be grounds for the City to terminate the Agreement for cause. 584
Contract No. C48060
4 Revised 07-2023
BBK 72500.00001\32374915.1
3.2.10.1 Employment Eligibility; Consultant. Consultant certifies that it fully complies with all requirements and restrictions of state and federal law respecting the employment of undocumented aliens, including, but not limited to, the Immigration Reform and Control Act of 1986, as may be amended from time to time and shall require all subconsultants and sub-subconsultants to comply with the same. Consultant certifies that it has not committed a violation of any such law within the five (5) years immediately preceding the date of execution of this Agreement and shall not violate any such law at any time during the term of the Agreement.
3.2.10.2 Equal Opportunity Employment. Consultant represents that it is an equal opportunity employer, and it shall not discriminate against any subconsultant, employee or applicant for employment because of race, religion, color, national origin, physical disability, ancestry, sex, age, marital status, gender, gender identity, gender expression, sexual orientation, reproductive health decision making, veteran or military status, or any other consideration made unlawful by federal, state, or local laws. Such non-discrimination shall include, but not be limited to, all activities related to initial employment, upgrading, demotion, transfer, recruitment or recruitment advertising, layoff or termination. Consultant shall also comply with all relevant provisions of City's Minority Business Enterprise program, Affirmative Action Plan or other related programs or guidelines currently in effect or hereinafter enacted.
3.2.10.3 Safety. Consultant shall execute and maintain its work so as to avoid injury or damage to any person or property. In carrying out its Services, the Consultant shall at all times be in compliance with all applicable local, state and federal laws, rules and regulations, and shall exercise all necessary precautions for the safety of employees appropriate to the nature of the work and the conditions under which the work is to be performed.
3.2.11 Insurance.
3.2.11.1 Minimum Requirements. Without limiting Consultant’s indemnification of City, and prior to commencement of the Services, Consultant shall obtain, provide, and maintain at its own expense during the term of this Agreement, policies of insurance of the type and amounts described below and in a form that is satisfactory to City. (A) General Liability Insurance. Consultant shall maintain commercial general liability insurance with coverage at least as broad as Insurance Services Office form CG 00 01, in an amount not less than $1,000,000 per occurrence, $2,000,000 general aggregate, for bodily injury, personal injury, and property damage. The policy must include contractual liability that has not been amended. Any endorsement restricting standard ISO “insured contract” language will not be accepted.
(B) Automobile Liability Insurance. Consultant shall maintain automobile insurance at least as broad as Insurance Services Office form CA 00 01 covering bodily injury and property damage for all activities of the Consultant arising out of or in connection with Work to be performed under this Agreement, including coverage for any owned, hired, nonowned or rented vehicles, in an amount not less than $1,000,000 combined single limit for each accident. The City’s Risk Manger may modify this requirement if it is determined that Consultant will not be utilizing a vehicle in the performance of his/her duties under this Agreement. (C) Professional Liability (Errors & Omissions) Insurance.
Consultant shall maintain professional liability insurance that covers the Services to be performed in connection with this Agreement, in the minimum amount of $1,000,000 per claim and in the aggregate. Any policy inception date, continuity date, or retroactive date must be before the 585
Contract No. C48060
5 Revised 07-2023
BBK 72500.00001\32374915.1
effective date of this Agreement and Consultant agrees to maintain continuous coverage through a period no less than three years after completion of the Services required by this Agreement. (D) Workers’ Compensation Insurance. Consultant shall
maintain Workers’ Compensation Insurance (Statutory Limits) and Employer’s Liability Insurance (with limits of at least $1,000,000). Consultant shall submit to City, along with the certificate of insurance, a Waiver of Subrogation endorsement in favor of the City, its officers, agents, employees, volunteers, and representatives.
(E) Umbrella or Excess Liability Insurance. Consultant may opt to utilize umbrella or excess liability insurance in meeting insurance requirements. In such circumstances, Consultant shall obtain and maintain an umbrella or excess liability insurance policy with limits that will provide bodily injury, personal injury and property damage liability coverage at least as broad as the primary coverages set forth above, including commercial general liability and employer’s liability. Such policy or policies shall include the following terms and conditions:
(1) A drop-down feature requiring the policy to respond if any primary insurance that would otherwise have
applied proves to be uncollectible in whole or in part for any reason;
(2) Pay on behalf of wording as opposed to reimbursement; (3) Concurrency of effective dates with primary policies; and (4) Policies shall “follow form” to the underlying primary policies.
(5) Insureds under primary policies shall also be insureds under the umbrella or excess policies.
If coverage is maintained on a claims-made basis, Consultant shall maintain such coverage for an additional period of three (3) years following termination of the Agreement.
3.2.11.2 Other Provisions or Requirements.
(A) Proof of Insurance. Consultant shall provide certificates of insurance to City as evidence of the insurance coverage required herein, along with a waiver of subrogation endorsement for workers’ compensation. Insurance certificates and endorsements must be approved by City’s Risk Manager prior to commencement of performance. Current certification of insurance shall be kept on file with City at all times during the term of this Agreement. City reserves the right to require complete, certified copies of all required insurance policies, at any time.
(B) Duration of Coverage. Consultant shall procure and
maintain for the duration of the Agreement insurance against claims for injuries to persons or damages to property, which may arise from or in connection with the performance of the Services hereunder by Consultant, his/her agents, representatives, employees or subconsultants. (C) Primary/Non-Contributing. Coverage provided by
Consultant shall be primary and any insurance or self-insurance procured or maintained by City shall not be required to contribute with it. The limits of insurance required herein may be satisfied 586
Contract No. C48060
6 Revised 07-2023
BBK 72500.00001\32374915.1
by a combination of primary and umbrella or excess insurance. Any umbrella or excess insurance shall contain or be endorsed to contain a provision that such coverage shall also apply on a primary and non-contributory basis for the benefit of City before the City’s own insurance or selfinsurance shall be called upon to protect it as a named insured. (D) City’s Rights of Enforcement. In the event any policy of insurance required under this Agreement does not comply with these specifications, or is canceled and not replaced, City has the right, but not the duty, to obtain the insurance it deems necessary, and any premium paid by City will be promptly reimbursed by Consultant, or City will withhold amounts sufficient to pay premium from Consultant payments. In the alternative, City may terminate this Agreement.
(E) Acceptable Insurers. All insurance policies shall be issued by an insurance company currently authorized by the Insurance Commissioner to transact business of insurance or is on the List of Approved Surplus Line Insurers in the State of California, with an assigned policyholders’ Rating of A- (or higher) and Financial Size Category Class VII (or larger) in accordance with the latest edition of Best’s Key Rating Guide, unless otherwise approved by the City’s Risk Manager.
(F) Waiver of Subrogation. All insurance coverage maintained or procured pursuant to this agreement shall be endorsed to waive subrogation against the City, its elected or appointed officers, agents, officials, employees, volunteers, and representatives or shall specifically allow Consultant or others providing insurance evidence in compliance with these specifications to waive their right of recovery prior to a loss. Consultant hereby waives its own right of recovery against the City, its elected or appointed officers, agents, officials, employees, volunteers and representatives and shall require similar written express waivers and insurance clauses from each of its subconsultants.
(G) Enforcement of Contract Provisions (non estoppel).
Consultant acknowledges and agrees that any actual or alleged failure on the part of the City to inform Consultant of non-compliance with any requirement imposes no additional obligations on the City nor does it waive any rights hereunder.
(H) Requirements Not Limiting. Requirements of specific coverage features or limits contained in this Section are not intended as a limitation on coverage, limits or other requirements, or a waiver of any coverage normally provided by any insurance.
Specific reference to a given coverage feature is for purposes of clarification only as it pertains to a given issue and is not intended by any party or insured to be all inclusive, or to the exclusion of other coverage, or a waiver of any type. If the Consultant maintains higher limits than the minimums shown above, the City requires and shall be entitled to coverage for the higher limits maintained by the Consultant. Any available insurance proceeds in excess of the specified minimum limits of insurance and coverage shall be available to the City. (I) Notice of Cancellation. Consultant agrees to oblige its insurance agent or broker and insurers to provide City with a thirty (30) day notice of cancellation (except for nonpayment for which a ten (10) day notice is required) or nonrenewal of coverage for each required coverage.
(J) Additional Insured Status. General liability, automobile liability, and if applicable, pollution liability and cyber liability, policies shall provide or be endorsed to provide that the City and its officers, officials, employees, agents, volunteers and representatives shall be additional insureds with regard to liability and defense of suits or claims 587
Contract No. C48060
7 Revised 07-2023
BBK 72500.00001\32374915.1
arising out of the performance of the Agreement, under such policies. This provision shall also apply to any excess/umbrella liability policies.
(K) Prohibition of Undisclosed Coverage Limitations. None of the coverages required herein will be in compliance with these requirements if they include any limiting endorsement of any kind that has not been first submitted to City and approved of in writing.
(L) Separation of Insureds. A severability of interests provision must apply for all additional insureds ensuring that Consultant’s insurance shall apply separately to each insured against whom claim is made or suit is brought, except with respect to the insurer’s limits of liability. The policy(ies) shall not contain any cross-liability exclusions. (M) Pass Through Clause. Consultant agrees to ensure that its subconsultants, subcontractors, and any other party involved with the Project who is brought onto or involved in the Project by Consultant, provide the same minimum insurance coverage and endorsements required of Consultant. Consultant agrees to monitor and review all such coverage and assumes all responsibility for ensuring that such coverage is provided in conformity with the requirements of this section. Consultant agrees that upon request, all agreements with subconsultants, subcontractors, and others engaged in the Project will be submitted to City for review.
(N) City’s Right to Revise Specifications. The City and the City’s Risk Manager reserve the right at any time during the term of the Agreement to change the amounts and types of insurance required by giving the Consultant ninety (90) days advance written notice of such change. If such change results in additional cost to the Consultant, the City and Consultant may renegotiate Consultant’s compensation. If the City reduces the insurance requirements, the change shall go into effect immediately and require no advanced written notice. (O) Self-Insured Retentions. Any self-insured retentions must be declared to and approved by City. City reserves the right to require that self-insured retentions be eliminated, lowered, or replaced by a deductible. Self-insurance will not be considered to comply with these specifications unless approved by City. (P) Timely Notice of Claims. Consultant shall give City prompt and timely notice of claims made or suits instituted that arise out of or result from Consultant’s performance under this Agreement, and that involve or may involve coverage under any of the required liability policies.
(Q) Additional Insurance. Consultant shall also procure and maintain, at its own cost and expense, any additional kinds of insurance, which in its own judgment may be necessary for its proper protection and prosecution of the Services.
3.2.12 Water Quality Management and Compliance. Consultant shall keep itself and all subcontractors, staff, and employees fully informed of and in compliance with all local, state and federal laws, rules and regulations that may impact, or be implicated by the performance of the Services including, without limitation, all applicable provisions of the City’s ordinances regulating water quality and storm water; the Federal Water Pollution Control Act (33 U.S.C. § 1251, et seq.); the California Porter-Cologne Water Quality Control Act (Water Code § 13000 et seq.); and any and all regulations, policies, or permits issued pursuant to any such authority.
Consultant must comply with the lawful requirements of the City, and any other municipality, drainage district, or other local agency with jurisdiction over the location where the Services are 588
Contract No. C48060
8 Revised 07-2023
BBK 72500.00001\32374915.1
to be conducted, regulating water quality and storm water discharges. Failure to comply with laws, regulations, and ordinances listed in this Section is a violation of federal and state law. Consultant warrants that all employees and subcontractors shall have sufficient skill and experience to perform the work assigned to them without impacting water quality in violation of the laws, regulations, and policies of this Section.
3.3 Fees and Payments.
3.3.1 Compensation. Contractor shall receive compensation, including authorized reimbursements, for all Services rendered under this Agreement at the rates set forth in Exhibit “C” attached hereto and incorporated herein by reference. The total compensation shall not exceed ONE HUNDRED, AND THIRTY-NINE THOUSAND AND SEVENTY-SIX DOLLARS ($139,076) without written approval of the City Council or City Manager, as applicable.
3.3.2 Payment of Compensation. Consultant shall submit to City monthly invoices which provide a detailed description of the Services and hours rendered by Consultant.
City shall, within 30 days of receiving such invoice, review the invoice and pay all non-disputed and approved charges. If the City disputes any of Consultant's fees, the City shall give written notice to Consultant within thirty (30) days of receipt of an invoice of any disputed fees set forth therein. Payment shall not constitute acceptance of any Services completed by Consultant. The making of final payment shall not constitute a waiver of any claims by the City for any reason whatsoever.
3.3.3 Reimbursement for Expenses. Consultant shall not be reimbursed for any expenses unless authorized in writing by City or included in Exhibit "C" of this Agreement.
3.3.4 Extra Work. At any time during the term of this Agreement, City may request that Consultant perform Extra Work. As used herein, "Extra Work" means any work which is determined by City to be necessary for the proper completion of the Project, but which the Parties did not reasonably anticipate would be necessary at the execution of this Agreement.
Consultant shall not perform, nor be compensated for, Extra Work without written authorization from the City.
3.4 Labor Code Requirements.
3.4.1 Prevailing Wages. Consultant is aware of the requirements of California Labor Code Section 1720, et seq., and 1770, et seq., as well as California Code of Regulations, Title 8, Section 16000, et seq., ("Prevailing Wage Laws"), which require the payment of prevailing wage rates and the performance of other requirements on "public works" and "maintenance" projects. If the Services are being performed as part of an applicable "public works" or "maintenance" project, as defined by the Prevailing Wage Laws, Consultant agrees to fully comply with such Prevailing Wage Laws. City shall provide Consultant with a copy of the prevailing rates of per diem wages in effect at the commencement of this Agreement. Consultant shall make copies of the prevailing rates of per diem wages for each craft, classification or type of worker needed to execute the Services available to interested parties upon request and shall post copies at the Consultant's principal place of business and at the project site. It is the intent of the parties to effectuate the requirements of sections 1771, 1774, 1775, 1776, 1777.5, 1813, and 1815 of the Labor Code within this Agreement, and Consultant shall therefore comply with such Labor Code sections to the fullest extent required by law. Consultant shall defend, indemnify, and hold the City, its officials, officers, employees, agents, volunteers and representatives, free and harmless from any claim or liability arising out of any failure or alleged failure to comply with the Prevailing Wage Laws.
589
Contract No. C48060
9 Revised 07-2023
BBK 72500.00001\32374915.1
3.4.2 Registration/DIR Compliance. If the Services are being performed on a public works project of over $25,000 when the project is for construction, alteration, demolition, installation, or repair work, or a public works project of over $15,000 when the project is for maintenance work, in addition to the foregoing, then pursuant to Labor Code sections 1725.5 and 1771.1, the Consultant and all subconsultants must be registered with the Department of Industrial Relations (“DIR”). Consultant shall maintain registration for the duration of the Project and require the same of any subconsultants. This Project may also be subject to compliance monitoring and enforcement by the DIR. It shall be Consultant’s sole responsibility to comply with all applicable registration and labor compliance requirements, including the submission of payroll records directly to the DIR. Any stop orders issued by the DIR against Consultant or any subconsultant that affect Consultant’s performance of Services, including any delay, shall be Consultant’s sole responsibility. Any delay arising out of or resulting from such stop orders shall be considered Consultant caused delay and shall not be compensable by the City. Consultant shall defend, indemnify, and hold the City, its officials, officers, employees, agents, volunteers and representatives free and harmless from any claim or liability arising out of stop orders issued by the DIR against Consultant or any subconsultant.
3.4.3 Labor Certification. By its signature hereunder, Consultant certifies that it is aware of the provisions of Section 3700 of the California Labor Code which require every employer to be insured against liability for Worker's Compensation or to undertake self-insurance in accordance with the provisions of that Code and agrees to comply with such provisions before commencing the performance of the Services.
3.5 Accounting Records.
3.5.1 Maintenance and Inspection. Consultant shall maintain complete and accurate records with respect to all costs and expenses incurred under this Agreement. All such records shall be clearly identifiable. Consultant shall allow a representative of City during normal business hours to examine, audit, and make transcripts or copies of such records and any other documents created pursuant to this Agreement. Consultant shall allow inspection of all work, data, documents, proceedings, and activities related to the Agreement for a period of three (3) years from the date of final payment under this Agreement.
3.6 General Provisions.
3.6.1 Termination of Agreement.
3.6.1.1 Grounds for Termination. City may, by written notice to Consultant, terminate the whole or any part of this Agreement at any time and without cause by giving written notice to Consultant of such termination, and specifying the effective date thereof, at least seven (7) days before the effective date of such termination. Upon termination, Consultant shall be compensated only for those Services which have been performed in accordance with this Agreement to the date of termination, and Consultant shall be entitled to no further compensation.
Consultant may not terminate this Agreement except for cause. The rights and remedies of the City provided in this section shall not be exclusive and are in addition to any other rights and remedies provided by law, equity or under this Agreement.
3.6.1.2 Effect of Termination. If this Agreement is terminated as provided herein, City may require Consultant to provide all finished or unfinished Documents and Data and other information of any kind prepared by Consultant in connection with the performance of Services under this Agreement. Consultant shall be required to provide such document and 590
Contract No. C48060
10 Revised 07-2023
BBK 72500.00001\32374915.1
other information within fifteen (15) days of the request, provided, however, City pays Consultant for its Services performed in accordance with this Agreement.
3.6.1.3 Early Termination. Notwithstanding any provision herein to the contrary, if for any fiscal year of this Agreement the City Council fails to appropriate or allocate funds for future payment under the Agreement after exercising reasonable efforts to do so, the City may upon seven (7) days’ written notice, order work on the Project to cease. Upon termination, Consultant shall be compensated only for those Services which have been performed in accordance with this Agreement y, and Consultant shall be entitled to no further compensation.
3.6.1.4 Additional Services. In the event this Agreement is terminated in whole or in part as provided herein, City may procure, upon such terms and in such manner as it may determine appropriate, services similar to those terminated.
3.6.2 Delivery of Notices. All notices permitted or required under this Agreement shall be given to the respective parties at the following address, or at such other address as the respective parties may provide in writing for this purpose:
Consultant: FEHR & PEERS
3750 UNIVERSITY AVENUE, SUITE 225
RIVERSIDE, CA 92501
ATTN: JASON D. PACK, PRINCIPAL
City: City of Palm Desert
73-510 Fred Waring Drive
Palm Desert, CA 92260-2578
ATTN: Nick Melloni, Development Services Department
Such notice shall be deemed made when personally delivered or when mailed, forty-eight (48) hours after deposit in the U.S. Mail, first class postage prepaid and addressed to the party at its applicable address. Actual notice shall be deemed adequate notice on the date actual notice occurred, regardless of the method of service.
3.6.3 Ownership of Materials and Confidentiality.
3.6.3.1 Documents & Data; Licensing of Intellectual Property. This Agreement creates a non-exclusive and perpetual license for City to copy, use, modify, reuse, or sublicense any and all copyrights, designs, and other intellectual property embodied in plans, specifications, studies, drawings, estimates, and other documents or works of authorship fixed in any tangible medium of expression, including but not limited to, physical drawings or data magnetically or otherwise recorded on computer diskettes, which are prepared or caused to be prepared by Consultant under this Agreement ("Documents & Data"). All Documents & Data shall be and remain the property of City and shall not be used in whole or in substantial part by Consultant on other projects without the City’s express written permission. Within thirty (30) days following the completion, suspension, abandonment or termination of this Agreement, Consultant shall provide to City reproducible copies of all Documents & Data, in a form and amount required by City. City reserves the right to select the method of document reproduction and to establish where the reproduction will be accomplished. The reproduction expense shall be borne by City at the actual cost of duplication. In the event of a dispute regarding the amount of compensation to which the Consultant is entitled under the termination provisions of this Agreement, Consultant shall provide all Documents & Data to City upon payment of the undisputed amount. Consultant 591
Contract No. C48060
11 Revised 07-2023
BBK 72500.00001\32374915.1
shall have no right to retain or fail to provide to City any such documents pending resolution of the dispute. In addition, Consultant shall retain copies of all Documents & Data on file for a minimum of fifteen (15) years following completion of the Project and shall make copies available to City upon the payment of actual reasonable duplication costs. Before destroying the Documents & Data following this retention period, Consultant shall make a reasonable effort to notify City and provide City with the opportunity to obtain the documents.
3.6.3.2 Subconsultants. Consultant shall require all subconsultants to agree in writing that City is granted a non-exclusive and perpetual license for any Documents & Data the subconsultant prepares under this Agreement. Consultant represents and warrants that Consultant has the legal right to license any and all Documents & Data. Consultant makes no such representation and warranty in regard to Documents & Data which were prepared by professionals other than Consultant or its subconsultants, or those provided to Consultant by the City.
3.6.3.3 Right to Use. City shall not be limited in any way in its use or reuse of the Documents and Data or any part of them at any time for purposes of this Project or another project, provided that any such use not within the purposes intended by this Agreement or on a project other than this Project without employing the services of Consultant shall be at City’s sole risk. If City uses or reuses the Documents & Data on any project other than this Project, it shall remove the Consultant’s seal from the Documents & Data and indemnify and hold harmless Consultant and its officers, directors, agents, and employees from claims arising out of the negligent use or re-use of the Documents & Data on such other project. Consultant shall be responsible and liable for its Documents & Data, pursuant to the terms of this Agreement, only with respect to the condition of the Documents & Data at the time they are provided to the City upon completion, suspension, abandonment, or termination. Consultant shall not be responsible or liable for any revisions to the Documents & Data made by any party other than Consultant, a party for whom the Consultant is legally responsible or liable, or anyone approved by the Consultant.
3.6.3.4 Indemnification – Documents and Data. Consultant shall defend, indemnify and hold the City, its directors, officials, officers, employees, volunteers, agents and representatives free and harmless, pursuant to the indemnification provisions of this Agreement, for any alleged infringement of any patent, copyright, trade secret, trade name, trademark, or any other proprietary right of any person or entity in consequence of the use on the Project by City of the Documents & Data, including any method, process, product, or concept specified or depicted.
3.6.3.5 Confidentiality. All ideas, memoranda, specifications, plans, procedures, drawings, descriptions, computer program data, input record data, written information, and other Documents & Data either created by or provided to Consultant in connection with the performance of this Agreement shall be held confidential by Consultant. Such materials shall not, without the prior written consent of City, be used by Consultant for any purposes other than the performance of the Services. Nor shall such materials be disclosed to any person or entity not connected with the performance of the Services or the Project. Nothing furnished to Consultant which is otherwise known to Consultant or is generally known, or has become known, to the related industry shall be deemed confidential. Consultant shall not use City's name or insignia, photographs of the Project, or any publicity pertaining to the Services or the Project in any magazine, trade paper, newspaper, television or radio production or other similar medium without the prior written consent of City. 592
Contract No. C48060
12 Revised 07-2023
BBK 72500.00001\32374915.1
3.6.3.6 Confidential Information. The City shall refrain from releasing Consultant’s proprietary information ("Proprietary Information") unless the City's legal counsel determines that the release of the Proprietary Information is required by the California Public Records Act or other applicable state or federal law, or order of a court of competent jurisdiction, in which case the City shall notify Consultant of its intention to release Proprietary Information. Consultant shall have five (5) working days after receipt of the release notice to give City written notice of Consultant's objection to the City's release of Proprietary Information.
Consultant shall indemnify, defend, and hold harmless the City, and its officers, directors, employees, agents, volunteers and representatives from and against all liability, loss, cost or expense (including attorney’s fees) arising out of a legal action brought to compel the release of Proprietary Information. City shall not release the Proprietary Information after receipt of an objection notice unless either: (1) Consultant fails to fully indemnify, defend (with City's choice of legal counsel), and hold City harmless from any legal action brought to compel such release; and/or (2) a final and non-appealable order by a court of competent jurisdiction requires that City release such information.
3.6.4 Cooperation; Further Acts. The Parties shall fully cooperate with one another and shall take any additional acts or sign any additional documents as may be necessary, appropriate, or convenient to attain the purposes of this Agreement.
3.6.5 [Reserved]
3.6.6 Indemnification.
3.6.6.1 To the fullest extent permitted by law, Consultant shall defend (with counsel of City’s reasonable choosing), indemnify and hold the City, its officials, officers, employees, volunteers, agents, and representatives free and harmless from any and all claims, demands, causes of action, costs, expenses, liability, loss, damage or injury of any kind, in law or equity, to property or persons, including wrongful death, in any manner arising out of, pertaining to, or incident to any negligent acts, errors or omissions, or willful misconduct of Consultant, its officials, officers, employees, subconsultants or agents in connection with the performance of the Consultant’s Services, the Project or this Agreement, including without limitation the payment of all reasonable expert witness fees, attorney’s fees and other related costs and expenses except such loss or damage caused by the sole negligence or willful misconduct of the City. Consultant's obligation to indemnify shall survive expiration or termination of this Agreement and shall not be restricted to insurance proceeds, if any, received by Consultant, the City, its officials, officers, employees, agents, volunteers, or representatives.
3.6.6.2 If Consultant’s obligation to defend, indemnify, and/or hold harmless arises out of Consultant’s performance as a “design professional” (as that term is defined under Civil Code section 2782.8), then, and only to the extent required by Civil Code section 2782.8, which is fully incorporated herein, Consultant’s indemnification obligation shall be limited to claims to the extent they arise out of, pertain to, or relate to the negligence, recklessness, or willful misconduct of the Consultant. Consultant’s liability for such claim, including the cost to defend, shall not exceed the Consultant’s proportionate percentage of fault.
3.6.7 Entire Agreement. This Agreement contains the entire agreement of the Parties with respect to the subject matter hereof, and supersedes all prior negotiations, understandings, or agreements.
3.6.8 Governing Law. This Agreement shall be governed by the laws of the State of California. Venue shall be in Riverside County.
593
Contract No. C48060
13 Revised 07-2023
BBK 72500.00001\32374915.1
3.6.9 Time of Essence. Time is of the essence for each and every provision of this Agreement.
3.6.10 City's Right to Employ Other Consultants. City reserves right to employ other consultants in connection with this Project.
3.6.11 Successors and Assigns. This Agreement shall be binding on the successors and assigns of the Parties.
3.6.12 Assignment; Subcontracting. Consultant shall not assign, sublet, or transfer this Agreement or any rights under or interest in this Agreement without the written consent of the City, which may be withheld for any reason. Any attempt to so assign or so transfer without such consent shall be void and without legal effect and shall constitute grounds for termination. Consultant shall not subcontract any portion of the Services required by this Agreement, except as expressly stated herein, without prior written approval of City.
Subcontracts, if any, shall contain a provision making them subject to all provisions stipulated in this Agreement.
3.6.13 Construction; References; Captions. Since the Parties or their agents have participated fully in the preparation of this Agreement, the language of this Agreement shall be construed simply, according to its fair meaning, and not strictly for or against any Party. Any term referencing time, days or period for performance shall be deemed calendar days and not workdays. All references to Consultant include all personnel, employees, agents, and subconsultants of Consultant, except as otherwise specified in this Agreement. All references to City include its elected officials, officers, employees, agents, volunteers, and representatives except as otherwise specified in this Agreement. The captions of the various articles and paragraphs are for convenience and ease of reference only, and do not define, limit, augment, or describe the scope, content, or intent of this Agreement.
3.6.14 Amendment; Modification. No supplement, modification, or amendment of this Agreement shall be binding unless executed in writing and signed by both Parties.
3.6.15 Waiver. No waiver of any default shall constitute a waiver of any other default or breach, whether of the same or other covenant or condition. No waiver, benefit, privilege, or service voluntarily given or performed by a Party shall give the other Party any contractual rights by custom, estoppel, or otherwise.
3.6.16 No Third-Party Beneficiaries. There are no intended third-party beneficiaries of any right or obligation assumed by the Parties.
3.6.17 Invalidity; Severability. If any portion of this Agreement is declared invalid, illegal, or otherwise unenforceable by a court of competent jurisdiction, the remaining provisions shall continue in full force and effect.
3.6.18 Prohibited Interests. Consultant maintains and warrants that it has not employed nor retained any company or person, other than a bona fide employee working solely for Consultant, to solicit or secure this Agreement. Further, Consultant warrants that it has not paid, nor has it agreed to pay any company or person, other than a bona fide employee working solely for Consultant, any fee, commission, percentage, brokerage fee, gift or other consideration contingent upon or resulting from the award or making of this Agreement. For breach or violation of this warranty, City shall have the right to rescind this Agreement without liability. For the term of this Agreement, no member, officer, or employee of City, during the term of his or her service 594
Contract No. C48060
14 Revised 07-2023
BBK 72500.00001\32374915.1
with City, shall have any direct interest in this Agreement, or obtain any present or anticipated material benefit arising therefrom.
3.6.19 Authority to Enter Agreement. Consultant has all requisite power and authority to conduct its business and to execute, deliver, and perform the Agreement. Each Party warrants that the individuals who have signed this Agreement have the legal power, right, and authority to make this Agreement and bind each respective Party.
3.6.20 Counterparts. This Agreement may be signed in counterparts, each of which shall constitute an original.
3.6.21 Survival. All rights and obligations hereunder that by their nature are to continue after any expiration or termination of this Agreement, including, but not limited to, the indemnification obligations, shall survive any such expiration or termination. [SIGNATURES ON NEXT PAGE]
595
Contract No. C48060
15 Revised 07-2023
BBK 72500.00001\32374915.1
SIGNATURE PAGE TO PROFESSIONAL SERVICES AGREEMENT
BY AND BETWEEN THE CITY OF PALM DESERT
AND FEHR & PEERS
IN WITNESS WHEREOF, each of the Parties has caused this Agreement to be executed on the day and year first above written.
CITY OF PALM DESERT
By:
L. Todd Hileman
City Manager
Attest:
By:
Anthony J. Mejia
City Clerk
Approved as to form:
By:
Isra Shah
Best Best & Krieger LLP
City Attorney
FEHR &PEERS, an S Corporation
By:
Sarah Brandenberg
Vice President
By:
Lysa Wollard
Chief Financial Officer / Treasurer
QC: MN
Insurance:
_________
Initial Review
_________
Final Approval
596
Contract No. C48060
Exhibit “A”
Revised 07-2023
BBK 72500.00001\32374915.1
EXHIBIT “A”
SCOPE OF SERVICES
The Consultant shall provide full professional services to assist the City of Palm Desert Development Services Staff with an update of the City’s Circulation Element, also known as the Mobility Element of the General Plan.
Task 1: Project Management
Task 1.1: Kick-Off Meeting
The consultant will work with the City’s Project Manager to schedule a project kickoff meeting.
The consultant will prepare a draft agenda to discuss the project schedule and goals, and to confirm the approach to the transportation technical analyses, including travel demand modeling assumptions, roadway network scenarios, and the analysis scenario years. The team will also discuss available data sources and traffic count locations. Additionally, the consultant will discuss contract management and invoicing to ensure timely submittal pf invoices in accordance with City requirements.
Task 1.2: Regular Project Meetings
Recurring monthly meetings will be scheduled between the consultant and City staff to review analyses, deliverables, discuss findings, raise any issues or concerns, and provide an update on next steps.
Task 1.3: Contract Management
The consultant will submit monthly progress reports and invoices. The progress reports will recap work associated with the monthly invoice.
Task 1 Deliverables:
1.Kick-Off Meeting Agenda, including project schedule, data needs, regular status updates/meetings, and invoicing.
2.Monthly check-in calls/meetings (agendas and meeting minutes will be provided).
3.Monthly invoices and progress reports.
Task 2: Existing Conditions
Task 2.1: Data Collection and Review
The consultant’s initial review will include a review of relevant documents including the current General Plan, recent CEQA documents, regional planning documents (such as the Congestion Management Plan (CMP), Regional Transportation Plan (RTP), Area and Specific Plans, documents prepared by CVAG, local transit/active transportation plans, recent traffic impact studies prepared for new development, and any other planning documents that would provide additional information relative to the Circulation Update effort. The purpose of this review is to identify existing data needs and determine which of the previous data collection and mapping efforts can be employed in this analysis.
Task 2.2: Existing Conditions Assessment
Using the data collected in Task 2.1, a background technical report will be prepared documenting existing conditions in the area. This will include a regulatory context summarizing recent legislative requirements the General Plan should consider, existing roadway network classifications, existing and proposed active transportation facilities, transit service, existing truck and rail facilities, and relevant census information such as commute trip information, mode split information, and relative locations of where Palm Desert residents work and vice versa. Key issues and opportunities will be documented in this report. This report will also summarize the Streetlight traffic count data on study roadway segments and will highlight areas where traffic counts have changed significantly since the 2016 assessment was completed. 597
Contract No. C48060
Exhibit “A”
Revised 07-2023
BBK 72500.00001\32374915.1
The consultant will prepare a draft background technical report and submit it to the City for one round of consolidated comments.
Task 2.3: Safety Assessment
The consultant will analyze publicly available collision information to summarize roadway collision trends that will assist in identifying a High Injury Network (HIN) as required by SB 932. This HIN network will be used to supplement and inform policies in this element update. The consultant will also work with the City to better understand and reference the City’s Vision Zero Strategy study.
These findings will be provided in a series of charts that will be included in the existing conditions background technical report.
Task 2.4: Update Travel Demand Model
The consultant will utilize either the latest version of the RIVCOM travel demand model or the previously developed City model for this effort. Next, any proposed changes in land use and the roadway network will be updated in the model. The model will be used to compare the Adopted General Plan Circulation Element and the proposed Circulation Element Update with any associated land use changes.
It is anticipated that this traffic model will be employed for the following purposes:
•Testing roadway network and classification alternatives •Analyzing the level of service at study roadway segments •Forecasting VMT for the City using a couple of different methods. This can be used to better understand how VMT can/should be incorporated into the City’s policy document and to help inform VMT guidelines for the City.
Task 2 Deliverables:
1.List and map of study segments for Streetlight data collection
2.Draft background technical report, including safety assessment
3.Final background technical report, including safety assessment Task 3: Alternatives Development
Task 3.1: Engagement & Coordination
The consultant will meet with City Staff, and other agencies, to review transportation network issues and needs based on existing and expected network operations. This engagement must include collaboration SunLine Transit Agency for a variety of public transit solutions. Additionally, the consultant will hold one council workshop to review current issues and potential opportunities with various stakeholders.
Task 3.2: Roadway Network Alternatives Development
It is anticipated that up to two (2) proposed alternatives will be developed consisting of roadway network, lane, classification, and/or truck routing changes. The updated travel demand model will be used to determine a single preferred roadway network alternative for a future year model. The consultant will discuss with City Staff the appropriate approach to developing forecasts for this effort.
Task 3 Deliverables:
1. Council issues and opportunities workshop materials and attendance
2. Memorandum documenting input from stakeholders, proposed alternatives, and VMT differences for each alternative
Task 4: SB 743 Transportation Impact Assessment Guidelines The consultant shall prepare updated Transportation Study Guidelines that cover both the CEQA requirements under SB 743, as well as the City’s desire to maintain Level of Service (LOS) requirements. The consultant will review the City’s current Transportation Study Guidelines and state requirements provided by the Governor’s Office of Planning and Research. 598
Contract No. C48060
Exhibit “A”
Revised 07-2023
BBK 72500.00001\32374915.1
The consultant will prepare detailed guidelines that explain how to prepare a VMT assessment for screening out projects, as well as how to prepare a VMT analysis for projects that do not screen out. The consultant will also work with City Staff to identify areas of the City where the LOS expectations may need to change. Changes will be incorporated into the Transportation Study Guidelines. Maps will be prepared to identify development locations that screen out of VMT assessment.
Task 4 Deliverables:
1.Draft Transportation Study Guidelines
2.Final Transportation Study Guidelines
Task 5: Roadway Network Recommendations
Task 5.1: Roadway Network Alternatives Modeling
The consultant will model up to two roadway network changes. As part of this exercise, they will calculate the VMT changes associated with the roadway network alternatives.
Task 5.2: Roadway Classifications and Roadway Network Recommendations The consultant will review the results of the alternative roadway network analyses and develop recommendations for altering functional operations and mobility within each roadway classification. These recommendations may consist of changes to roadway classifications or network changes, such as vacating roadway segments, adding or reducing capacity to existing roadways, and/or safety or operational improvements. These changes will consider potential effects on other transportation modes, such as pedestrians, bicyclists, and public transit. The consultant will also review existing truck routes and recommend changes to support industrial development and goods movement. Changes will also include a review of roadway cross-sections to ensure consistency within the General Plan (e.g. consistency with the area plans within the document) and consistency with other planning documents in the City (like the ATP).
Task 5 Deliverables:
1.Draft Technical Memorandum recommending changes to roadway classifications and/or the City roadway network
2.VMT modeling showing change in VMT
3. Present proposed changes (a PowerPoint presentation and present at one (1) meeting)
4.Final Technical Memorandum recommending changes to roadway classifications and/or the City roadway network with input from meeting incorporated per City Staff’s direction Task 6: Circulation Element Update:
Based on recommendations provided in Task 5 and discussions with City Staff, the consultant will develop an initial set of transportation policies related to various items for incorporating into the Circulation Element Update, including but not limited to:
•VMT transportation impacts
•Level of Service (LOS)
•Maximum allowable roadway cross sections
•Consistency with other state laws (e.g. SB 330, SB 35) •Coachella Valley Passenger Rail Service
•Transit System including an evaluation of existing and proposed transit lines •Collaboration with SunLine Transit Agency for a variety of public transit solutions •Transportation Demand Management (TDM)
•Safety and Vision Zero Strategies
•Emergency Evacuation Routes
These policy changes will address changes in state law, specifically AB 1358 (Complete Streets requirement), SB 932 (Safe Systems and Vision Zero Approach requirement), SB 743, and SB 330 (clarifying roadway improvement requirements for new housing developments). 599
Contract No. C48060
Exhibit “A”
Revised 07-2023
BBK 72500.00001\32374915.1
The consultant will develop the initial policies and present these policies to City Staff for review.
The consultant will combine the information developed in the previous tasks into a comprehensive Circulation Element (including text, graphics, and policies). An implementation matrix will also be prepared to align action steps with added and edited policies.
Task 6 Deliverables:
1Draft Circulation Element Update and Implementation Matrix
2.Final Circulation Element Update Implementation Matrix Task 7: CEQA
The focus of the project will be to update the Circulation Element of the General Plan to create better guidance on meeting Vehicle Miles Travelled (VMT) reductions, improve safety by incorporating Vision Zero, and review of the policies to ensure they meet the needs of the City.
The project consultant shall prepare the necessary documentation to ensure compliance with the California Environmental Quality Act (CEQA). The Consultant shall prepare necessary steps for compliance with Senate Bill-18 Tribal Consultation. Completion of the SB 18 process is needed prior to acting on the project.
This scope does not include:
•Public distribution of document
•Attendance at public hearings
•Copies
•Filing fees
•Technical studies (i.e. traffic, AQ, GHG, Noise)
Task 7 Deliverables:
1.Administrative Draft and Public Draft Addendum, SB-18 Tribal Consultation Letters, Notice of Determination, Notice of Completion.
600
Contract No. C48060
Exhibit “B”
Revised 07-2023
BBK 72500.00001\32374915.1
EXHIBIT "B"
SCHEDULE OF SERVICES
(SEE FOLLOWING PAGE)
601
Contract No. C48060
Exhibit “C”
Revised 07-2023
BBK 72500.00001\32374915.1
EXHIBIT "C"
COMPENSATION
In the event that this Agreement is renewed pursuant to Section 3.1.2, the rates set forth above may be increased or reduced each year at the time of renewal, but any increase shall not exceed the Consumer Price Index, All Urban Consumers, Riverside-San Bernardino-Ontario, CA. (SEE FOLLOWING PAGE)
602