J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
SELECTIVE DEMOLITION 024119 - 6
starting flame-cutting operations. Maintain portable fire-suppression devices during flamecutting operations.
5. Maintain fire watch during and for at least 2 hours after flame-cutting operations.
6. Maintain adequate ventilation when using cutting torches.
7. Remove decayed, vermin-infested, or otherwise dangerous or unsuitable materials and promptly dispose of off-site.
8. Remove structural framing members and lower to ground by method suitable to avoid free fall and to prevent ground impact or dust generation.
9. Locate selective demolition equipment and remove debris and materials so as not to impose excessive loads on supporting walls, floors, or framing.
10. Dispose of demolished items and materials promptly. Comply with requirements in Section 017419 "Construction Waste Management and Disposal." B. Site Access and Temporary Controls: Conduct selective demolition and debris-removal operations to ensure minimum interference with roads, streets, walks, walkways, and other adjacent occupied and used facilities.
C. Removed and Salvaged Items:
1. Clean salvaged items.
2. Pack or crate items after cleaning. Identify contents of containers.
3. Store items in a secure area until delivery to Owner.
4. Transport items to Owner's storage area designated by Owner.
5. Protect items from damage during transport and storage.
D. Removed and Reinstalled Items:
1. Clean and repair items to functional condition adequate for intended reuse.
2. Pack or crate items after cleaning and repairing. Identify contents of containers.
3. Protect items from damage during transport and storage.
4. Reinstall items in locations indicated. Comply with installation requirements for new materials and equipment. Provide connections, supports, and miscellaneous materials necessary to make item functional for use indicated.
E. Existing Items to Remain: Protect construction indicated to remain against damage and soiling during selective demolition. When permitted by Architect, items may be removed to a suitable, protected storage location during selective demolition and cleaned and reinstalled in their original locations after selective demolition operations are complete.
3.6 SELECTIVE DEMOLITION PROCEDURES FOR SPECIFIC MATERIALS A. Concrete Slabs-on-Grade: Saw-cut perimeter of area to be demolished, and then break up and remove.
3.7 DISPOSAL OF DEMOLISHED MATERIALS
A. Remove demolition waste materials from Project site and dispose of them in an EPA-approved construction and demolition waste landfill acceptable to authorities having jurisdiction.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
SELECTIVE DEMOLITION 024119 - 7
1. Do not allow demolished materials to accumulate on-site.
2. Remove and transport debris in a manner that will prevent spillage on adjacent surfaces and areas.
3. Remove debris from elevated portions of building by chute, hoist, or other device that will convey debris to grade level in a controlled descent.
4. Comply with requirements specified in Section 017419 "Construction Waste Management and Disposal."
B. Burning: Do not burn demolished materials.
3.8 CLEANING
A. Clean adjacent structures and improvements of dust, dirt, and debris caused by selective demolition operations. Return adjacent areas to condition existing before selective demolition operations began.
END OF SECTION 024119
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 1
SECTION 033000
CAST-IN-PLACE CONCRETE
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Cast-in-place concrete, including concrete materials, mixture design, placement procedures, and finishes.
1.2 DEFINITIONS
A. Cementitious Materials: Portland cement alone or in combination with one or more of the following: blended hydraulic cement, fly ash, slag cement, other pozzolans, and silica fume; materials subject to compliance with requirements.
B. Water/Cement Ratio (w/cm): The ratio by weight of water to cementitious materials.
1.3 ACTION SUBMITTALS
A. Product Data: For each of the following.
1. Portland cement.
2. Fly ash.
3. Slag cement.
4. Blended hydraulic cement.
5. Silica fume.
6. Performance-based hydraulic cement
7. Aggregates.
8. Admixtures:
a. Include limitations of use, including restrictions on cementitious materials, supplementary cementitious materials, air entrainment, aggregates, temperature at time of concrete placement, relative humidity at time of concrete placement, curing conditions, and use of other admixtures.
9. Curing materials.
a. Include documentation from color pigment manufacturer, indicating that proposed methods of curing are recommended by color pigment manufacturer.
10. Joint fillers.
11. Repair materials.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 2
B. Design Mixtures: For each concrete mixture, include the following:
1. Mixture identification.
2. Minimum 28-day compressive strength.
3. Durability exposure class.
4. Maximum w/cm.
5. Calculated equilibrium unit weight, for lightweight concrete.
6. Slump limit.
7. Air content.
8. Nominal maximum aggregate size.
9. Steel-fiber reinforcement content.
10. Synthetic micro-fiber content.
11. Indicate amounts of mixing water to be withheld for later addition at Project site if permitted.
12. Include manufacturer's certification that permeability-reducing admixture is compatible with mix design.
13. Include certification that dosage rate for permeability-reducing admixture matches dosage rate used in performance compliance test.
14. Intended placement method.
15. Submit alternate design mixtures when characteristics of materials, Project conditions, weather, test results, or other circumstances warrant adjustments.
1.4 INFORMATIONAL SUBMITTALS
A. Qualification Data: For the following:
1. Installer: Include copies of applicable ACI certificates.
2. Ready-mixed concrete manufacturer.
3. Testing agency: Include copies of applicable ACI certificates.
B. Material Certificates: For each of the following, signed by manufacturers:
1. Cementitious materials.
2. Admixtures.
3. Fiber reinforcement.
4. Curing compounds.
5. Floor and slab treatments.
6. Bonding agents.
7. Adhesives.
8. Vapor retarders.
9. Semirigid joint filler.
10. Joint-filler strips.
11. Repair materials.
C. Floor surface flatness and levelness measurements report, indicating compliance with specified tolerances.
D. Preconstruction Test Reports: For each mix design.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 3
E. Field quality-control reports.
1.5 QUALITY ASSURANCE
A. Installer Qualifications: A qualified installer who employs Project personnel qualified as an ACI-certified Flatwork Technician and Finisher and a supervisor who is a certified ACI Flatwork Concrete Finisher/Technician or an ACI Concrete Flatwork Technician with experience installing and finishing concrete, incorporating permeability-reducing admixtures.
1. Post-Installed Concrete Anchors Installers: ACI-certified Adhesive Anchor Installer.
B. Ready-Mixed Concrete Manufacturer Qualifications: A firm experienced in manufacturing ready-mixed concrete products and that complies with ASTM C94/C94M requirements for production facilities and equipment.
1. Manufacturer certified in accordance with NRMCA's "Certification of Ready Mixed Concrete Production Facilities."
C. Laboratory Testing Agency Qualifications: A testing agency qualified in accordance with ASTM C1077 and ASTM E329 for testing indicated and employing an ACI-certified Concrete Quality Control Technical Manager.
1. Personnel performing laboratory tests to be an ACI-certified Concrete Strength Testing Technician and Concrete Laboratory Testing Technician, Grade I. Testing agency laboratory supervisor to be an ACI-certified Concrete Laboratory Testing Technician, Grade II.
1.6 DELIVERY, STORAGE, AND HANDLING
A. Comply with ASTM C94/C94M and ACI 301 (ACI 301M).
1.7 FIELD CONDITIONS
A. Cold-Weather Placement: Comply with ACI 301 (ACI 301M) and ACI 306.1 and as follows.
1. Protect concrete work from physical damage or reduced strength that could be caused by frost, freezing actions, or low temperatures.
2. When average high and low temperature is expected to fall below 40 deg F (4.4 deg C) for three successive days, maintain delivered concrete mixture temperature within the temperature range required by ACI 301 (ACI 301M).
3. Do not use frozen materials or materials containing ice or snow.
4. Do not place concrete in contact with surfaces less than 35 deg F (1.7 deg C), other than reinforcing steel.
5. Do not use calcium chloride, salt, or other materials containing antifreeze agents or chemical accelerators unless otherwise specified and approved in mixture designs.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 4
B. Hot-Weather Placement: Comply with ACI 301 (ACI 301M) and ACI 305.1 (ACI 305.1M), and as follows:
1. Maintain concrete temperature at time of discharge to not exceed 95 deg F (35 deg C).
2. Fog-spray forms, steel reinforcement, and subgrade just before placing concrete. Keep subgrade uniformly moist without standing water, soft spots, or dry areas.
1.8 WARRANTY
A. Manufacturer's Warranty: Manufacturer agrees to furnish replacement sheet vapor ret B. arder/termite barrier material and accessories for sheet vapor retarder/ termite barrier and accessories that do not comply with requirements or that fail to resist penetration by termites within specified warranty period.
1. Warranty Period: 10 years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 CONCRETE, GENERAL
A. ACI Publications: Comply with ACI 301 (ACI 301M) unless modified by requirements in the Contract Documents.
2.2 CONCRETE MATERIALS
A. Source Limitations:
1. Obtain all concrete mixtures from a single ready-mixed concrete manufacturer for entire Project.
2. Obtain each type or class of cementitious material of the same brand from the same manufacturer's plant.
3. Obtain aggregate from single source.
4. Obtain each type of admixture from single source from single manufacturer.
B. Cementitious Materials:
1. Portland Cement: ASTM C150/C150M, Type I, gray.
2. Fly Ash: ASTM C618, Class C or F.
3. Slag Cement: ASTM C989/C989M, Grade 100 or 120.
4. Silica Fume: ASTM C1240 amorphous silica.
C. Normal-Weight Aggregates: ASTM C33/C33M, Class 3S, Class 3M, coarse aggregate or better, graded. Provide aggregates from a single source.
1. Alkali-Silica Reaction: Comply with one of the following:
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 5
a. Expansion Result of Aggregate: Not more than 0.04 percent at one-year when tested in accordance with ASTM C1293.
b. Expansion Results of Aggregate and Cementitious Materials in Combination: Not more than 0.10 percent at an age of 16 days when tested in accordance with ASTM C1567.
c. Alkali Content in Concrete: Not more than 4 lb./cu. yd. (2.37 kg/cu. m) for moderately reactive aggregate or 3 lb./cu. yd. (1.78 kg/cu. m) for highly reactive aggregate, when tested in accordance with ASTM C1293 and categorized in accordance with ASTM C1778, based on alkali content being calculated in accordance with ACI 301 (ACI 301M).
2. Maximum Coarse-Aggregate Size: 1-1/2 inches (38 mm) nominal.
3. Fine Aggregate: Free of materials with deleterious reactivity to alkali in cement.
D. Lightweight Aggregate: ASTM C330/C330M, 1-inch (25-mm) nominal maximum aggregate size.
E. Air-Entraining Admixture: ASTM C260/C260M.
F. Chemical Admixtures: Certified by manufacturer to be compatible with other admixtures that do not contribute water-soluble chloride ions exceeding those permitted in hardened concrete.
Do not use calcium chloride or admixtures containing calcium chloride in steel-reinforced concrete.
1. Water-Reducing Admixture: ASTM C494/C494M, Type A.
2. Retarding Admixture: ASTM C494/C494M, Type B.
3. Water-Reducing and -Retarding Admixture: ASTM C494/C494M, Type D.
4. High-Range, Water-Reducing Admixture: ASTM C494/C494M, Type F.
5. High-Range, Water-Reducing and -Retarding Admixture: ASTM C494/C494M, Type G.
6. Plasticizing and Retarding Admixture: ASTM C1017/C1017M, Type II.
7. Set-Accelerating Corrosion-Inhibiting Admixture: Commercially formulated, anodic inhibitor or mixed cathodic and anodic inhibitor; capable of forming a protective barrier and minimizing chloride reactions with steel reinforcement in concrete and complying with ASTM C49
8. 4/C494M, Type C.
9. Non-Set-Accelerating Corrosion-Inhibiting Admixture: Commercially formulated, nonset-accelerating, anodic inhibitor or mixed cathodic and anodic inhibitor; capable of forming a protective barrier and minimizing chloride reactions with steel reinforcement in concrete.
10. Permeability-Reducing Admixture: ASTM C494/C494M, Type S, hydrophilic, permeability-reducing crystalline admixture, capable of reducing water absorption of concrete exposed to hydrostatic pressure (PRAH).
a. Permeability: No leakage when tested in accordance with U.S. Army Corps of Engineers CRD C48 at a hydraulic pressure of 200 psi (1.28 MPa) for 14 days.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 6
G. Water and Water Used to Make Ice: ASTM C94/C94M, potable or complying with ASTM C1602/C1602M, including all limits listed in Table 2 and the requirements of paragraph 5.4
2.3 VAPOR RETARDERS
A. Sheet Vapor Retarder, Class A: ASTM E1745, Class A; not less than 10 mils (0.25 mm) thick.
Include manufacturer's recommended adhesive or pressure-sensitive tape.
B. Sheet Vapor Retarder, Class C: ASTM E1745, Class C; not less than 10 mils (0.25 mm) thick.
Include manufacturer's recommended adhesive or pressure-sensitive joint tape.
C. Sheet Vapor Retarder/Termite Barrier: ASTM E1745, Class A, except with maximum watervapor permeance of 0.03 perms; complying with ICC AC380. Include manufacturer's recommended adhesive or pressure-sensitive tape.
1. Low-Temperature Flexibility: Pass at minus 15 deg F (minus 26 deg C); ASTM D146/D146M.
2. Puncture Resistance: 224 lbf (996 N) minimum; ASTM E154/E154M.
3. Water Absorption: 0.1 percent weight-gain maximum after 48-hour immersion at 70 deg F (21 deg C); ASTM D570.
4. Hydrostatic-Head Resistance: 231 feet (70 m) minimum; ASTM D5385.
D. Bituminous Vapor Retarder: ASTM E1993/E1993M, 110-mil- (2.8-mm-) thick, semiflexible, seven-ply sheet membrane, consisting of reinforced core and carrier sheet with fortified asphalt layers, protective weather coating, and removable plastic release liner. Furnish manufacturer's accessories, including bonding asphalt, pointing mastics, and self-adhering joint tape.
1. Water-Vapor Permeance: 0.0011 grains/h x sq. ft. x inches Hg (0.063 ng/Pa x s x sq. m) when tested in accordance with ASTM E154/E154M.
2. Tensile Strength: 156 lbf/inch (27.35 kN/m) when tested in accordance with ASTM E154/E154M.
3. Puncture Resistance: 140 lbf (662N) when tested in accordance with ASTM E154/E154M.
2.4 CURING MATERIALS
A. Evaporation Retarder: Waterborne, monomolecular film forming, manufactured for application to fresh concrete.
B. Absorptive Cover: AASHTO M 182, Class 2, burlap cloth made from jute or kenaf, weighing approximately 9 oz./sq. yd. (305 g/sq. m) when dry.
C. Moisture-Retaining Cover: ASTM C171, polyethylene film burlap-polyethylene sheet.
1. Color:
a. Ambient Temperature Below 50 deg F (10 deg C): Black.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 7
b. Ambient Temperature between 50 deg F (10 deg C) and 85 deg F (29 deg C): Any color.
c. Ambient Temperature Above 85 deg F (29 deg C): White.
D. Curing Paper: 8-feet- (2438-mm-) wide paper, consisting of two layers of fibered kraft paper laminated with double coating of asphalt.
E. Water: Potable or complying with ASTM C1602/C1602M.
F. Clear, Waterborne, Membrane-Forming, Dissipating Curing Compound: ASTM C309, Type 1, Class B.
G. Clear, Waterborne, Membrane-Forming, Nondissipating Curing Compound: ASTM C309, Type 1, Class B, certified by curing compound manufacturer to not interfere with bonding of floor covering.
H. Clear, Waterborne, Membrane-Forming, Curing Compound: ASTM C309, Type 1, Class B, 18 to 25 percent solids, nondissipating, certified by curing compound manufacturer to not interfere with bonding of floor covering.
I. Clear, Solvent-Borne, Membrane-Forming, Curing and Sealing Compound: ASTM C1315, Type 1, Class A.
J. Clear, Waterborne, Membrane-Forming, Curing and Sealing Compound: ASTM C1315, Type 1, Class A.
2.5 RELATED MATERIALS
A. Expansion- and Isolation-Joint-Filler Strips: ASTM D1751, asphalt-saturated cellulosic fiber or ASTM D1752, cork or self-expanding cork.
B. Semirigid Joint Filler: Two-component, semirigid, 100 percent solids, epoxy resin with a Type A shore durometer hardness of 80 in accordance with ASTM D2240.
C. Bonding Agent: ASTM C1059/C1059M, Type II, nonredispersible, acrylic emulsion or styrene butadiene.
D. Epoxy Bonding Adhesive: ASTM C881, two-component epoxy resin, capable of humid curing and bonding to damp surfaces, of class suitable for application temperature and of grade and class to suit requirements, and as follows:
1. Types I and II, nonload bearing, for bonding hardened or freshly mixed concrete to hardened concrete.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 8
2.6 REPAIR MATERIALS
A. Repair Underlayment: Cement-based, polymer-modified, self-leveling product that can be applied in thicknesses from 1/8 inch (3 mm) and that can be feathered at edges to match adjacent floor elevations.
1. Cement Binder: ASTM C150/C150M portland cement or hydraulic or blended hydraulic cement, as defined in ASTM C219.
2. Primer: Product of underlayment manufacturer recommended for substrate, conditions, and application.
3. Aggregate: Well-graded, washed gravel, 1/8 to 1/4 inch (3 to 6 mm) or coarse sand, as recommended by underlayment manufacturer.
4. Compressive Strength: Not less than 4100 psi (29 MPa) at 28 days when tested in accordance with ASTM C109/C109M.
B. Repair Overlayment: Cement-based, polymer-modified, self-leveling product that can be applied in thicknesses from 1/4 inch (6 mm) and that can be filled in over a scarified surface to match adjacent floor elevations.
1. Cement Binder: ASTM C150/C150M portland cement or hydraulic or blended hydraulic cement, as defined in ASTM C219.
2. Primer: Product of topping manufacturer recommended for substrate, conditions, and application.
3. Aggregate: Well-graded, washed gravel, 1/8 to 1/4 inch (3.2 to 6 mm) or coarse sand as recommended by topping manufacturer.
4. Compressive Strength: Not less than 5000 psi (34.5 MPa) at 28 days when tested in accordance with ASTM C109/C109M.
2.7 CONCRETE MIXTURES, GENERAL
A. Prepare design mixtures for each type and strength of concrete, proportioned on the basis of laboratory trial mixture or field test data, or both, in accordance with ACI 301 (ACI 301M).
1. Use a qualified testing agency for preparing and reporting proposed mixture designs, based on laboratory trial mixtures.
B. Cementitious Materials: Limit percentage, by weight, of cementitious materials other than portland cement in concrete as follows:
1. Fly Ash or Other Pozzolans: 25 percent by mass.
2. Slag Cement: 50 percent by mass.
3. Silica Fume: 10 percent by mass.
4. Total of Fly Ash or Other Pozzolans, Slag Cement, and Silica Fume: 50 percent by mass, with fly ash or pozzolans not exceeding 25 percent by mass and silica fume not exceeding 10 percent by mass.
5. Total of Fly Ash or Other Pozzolans and Silica Fume: 35 percent by mass with fly ash or pozzolans not exceeding 25 percent by mass and silica fume not exceeding 10 percent by mass.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 9
C. Admixtures: Use admixtures in accordance with manufacturer's written instructions.
1. Use water-reducing, high-range water-reducing, or plasticizing admixture in concrete, as required, for placement and workability.
2. Use water-reducing and -retarding admixture when required by high temperatures, low humidity, or other adverse placement conditions.
3. Use water-reducing admixture in pumped concrete, concrete for heavy-use industrial slabs, concrete for parking structure slabs, and concrete with a w/cm below 0.50.
4. Use corrosion-inhibiting admixture in concrete mixtures where indicated.
5. Use permeability-reducing admixture in concrete mixtures where indicated.
D. Color Pigment: Add color pigment to concrete mixture in accordance with manufacturer's written instructions and to result in hardened concrete color consistent with approved mockup.
2.8 CONCRETE MIXTURES
A. Class A Normal-weight concrete used for footings, grade beams, and tie beams.
1. Exposure Class: ACI 318 (ACI 318M) F0.
2. Minimum Compressive Strength: 4000 psi (27.6 MPa) at 28 days.
3. Maximum w/cm: 0.50.
4. Slump Limit: 4 inches (100 mm), plus or minus 1 inch (25 mm).
5. Slump Flow Limit: 22 inches (550 mm), plus or minus 1.5 inches (40 mm).
6. Air Content:
7. Limit water-soluble, chloride-ion content in hardened concrete to 1.00 percent by weight of cement.
2.9 CONCRETE MIXING
A. Ready-Mixed Concrete: Measure, batch, mix, and deliver concrete in accordance with ASTM C94/C94M and ASTM C1116/C1116M, and furnish batch ticket information.
B. Project-Site Mixing: Measure, batch, and mix concrete materials and concrete in accordance with ASTM C94/C94M. Mix concrete materials in appropriate drum-type batch machine mixer.
1. For mixer capacity of 1 cu. yd. (0.76 cu. m) or smaller, continue mixing at least 1-1/2 minutes, but not more than five minutes after ingredients are in mixer, before any part of batch is released.
2. For mixer capacity larger than 1 cu. yd. (0.76 cu. m), increase mixing time by 15 seconds for each additional 1 cu. yd. (0.76 cu. m).
3. Provide batch ticket for each batch discharged and used in the Work, indicating Project identification name and number, date, mixture type, mixture time, quantity, and amount of water added. Record approximate location of final deposit in structure.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 10
PART 3 - EXECUTION
3.1 EXAMINATION
A. Verification of Conditions:
1. Before placing concrete, verify that installation of concrete forms, accessories, and reinforcement, and embedded items is complete and that required inspections have been performed.
2. Do not proceed until unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Provide reasonable auxiliary services to accommodate field testing and inspections, acceptable to testing agency, including the following:
1. Daily access to the Work.
2. Incidental labor and facilities necessary to facilitate tests and inspections.
3. Secure space for storage, initial curing, and field curing of test samples, including source of water and continuous electrical power at Project site during site curing period for test samples.
4. Security and protection for test samples and for testing and inspection equipment at Project site.
3.3 INSTALLATION OF EMBEDDED ITEMS
A. Place and secure anchorage devices and other embedded items required for adjoining Work that is attached to or supported by cast-in-place concrete.
1. Use setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded.
2. Install anchor rods, accurately located, to elevations required and complying with tolerances in Section 7.5 of ANSI/AISC 303.
3. Install reglets to receive waterproofing and to receive through-wall flashings in outer face of concrete frame at exterior walls, where flashing is shown at lintels, shelf angles, and other conditions.
3.4 INSTALLATION OF VAPOR RETARDER
A. Sheet Vapor Retarders: Place, protect, and repair sheet vapor retarder in accordance with ASTM E1643 and manufacturer's written instructions.
1. Install vapor retarder with longest dimension parallel with direction of concrete pour.
2. Face laps away from exposed direction of concrete pour.
3. Lap vapor retarder over footings and grade beams not less than 6 inches (150 mm), sealing vapor retarder to concrete.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 11
4. Lap joints 6 inches (150 mm) and seal with manufacturer's recommended tape.
5. Terminate vapor retarder at the top of floor slabs, grade beams, and pile caps, sealing entire perimeter to floor slabs, grade beams, foundation walls, or pile caps.
6. Seal penetrations in accordance with vapor retarder manufacturer's instructions.
7. Protect vapor retarder during placement of reinforcement and concrete. a. Repair damaged areas by patching with vapor retarder material, overlapping damages area by 6 inches (150 mm) on all sides, and sealing to vapor retarder.
B. Bituminous Vapor Retarders: Place, protect, and repair bituminous vapor retarder in accordance with manufacturer's written instructions.
3.5 CONCRETE PLACEMENT
A. Before placing concrete, verify that installation of formwork, reinforcement, embedded items, and vapor retarder is complete and that required inspections are completed.
1. Immediately prior to concrete placement, inspect vapor retarder for damage and deficient installation, and repair defective areas.
2. Provide continuous inspection of vapor retarder during concrete placement and make necessary repairs to damaged areas as Work progresses.
B. Notify Engineer and testing and inspection agencies 24 hours prior to commencement of concrete placement.
C. Do not add water to concrete during delivery, at Project site, or during placement unless approved by Architect in writing, but not to exceed the amount indicated on the concrete delivery ticket.
1. Do not add water to concrete after adding high-range water-reducing admixtures to mixture.
D. Before test sampling and placing concrete, water may be added at Project site, subject to limitations of ACI 301 (ACI 301M), but not to exceed the amount indicated on the concrete delivery ticket.
1. Do not add water to concrete after adding high-range water-reducing admixtures to mixture.
E. Deposit concrete continuously in one layer or in horizontal layers of such thickness that no new concrete is placed on concrete that has hardened enough to cause seams or planes of weakness.
1. If a section cannot be placed continuously, provide construction joints as indicated.
2. Deposit concrete to avoid segregation.
3. Deposit concrete in horizontal layers of depth not to exceed formwork design pressures and in a manner to avoid inclined construction joints.
4. Consolidate placed concrete with mechanical vibrating equipment in accordance with ACI 301 (ACI 301M).
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 12
a. Do not use vibrators to transport concrete inside forms. b. Insert and withdraw vibrators vertically at uniformly spaced locations to rapidly penetrate placed layer and at least 6 inches (150 mm) into preceding layer. c. Do not insert vibrators into lower layers of concrete that have begun to lose plasticity.
d. At each insertion, limit duration of vibration to time necessary to consolidate concrete, and complete embedment of reinforcement and other embedded items without causing mixture constituents to segregate.
F. Deposit and consolidate concrete for floors and slabs in a continuous operation, within limits of construction joints, until placement of a panel or section is complete.
1. Do not place concrete floors and slabs in a checkerboard sequence.
2. Consolidate concrete during placement operations, so concrete is thoroughly worked around reinforcement and other embedded items and into corners.
3. Maintain reinforcement in position on chairs during concrete placement.
4. Screed slab surfaces with a straightedge and strike off to correct elevations.
5. Level concrete, cut high areas, and fill low areas.
6. Slope surfaces uniformly to drains where required.
7. Begin initial floating using bull floats or darbies to form a uniform and open-textured surface plane, before excess bleedwater appears on the surface.
8. Do not further disturb slab surfaces before starting finishing operations.
3.6 FINISHING FORMED SURFACES
A. As-Cast Surface Finishes:
1. ACI 301 (ACI 301M) Surface Finish SF-1.0: As-cast concrete texture imparted by formfacing material. a. Patch voids larger than 1-1/2 inches (38 mm) wide or 1/2 inch (13 mm) deep. b. Remove projections larger than 1 inch (25 mm).
c. Tie holes do not require patching.
d. Surface Tolerance: ACI 117 (ACI 117M) Class D.
e. Apply to concrete surfaces not exposed to public view.
2. ACI 301 (ACI 301M) Surface Finish SF-2.0: As-cast concrete texture imparted by formfacing material, arranged in an orderly and symmetrical manner with a minimum of seams.
a. Patch voids larger than 3/4 inch (19 mm) wide or 1/2 inch (13 mm) deep. b. Remove projections larger than 1/4 inch (6 mm).
c. Patch tie holes.
d. Surface Tolerance: ACI 117 (ACI 117M) Class B.
e. Locations: Apply to concrete surfaces exposed to public view, to receive a rubbed finish, or to be covered with a coating or covering material applied directly to concrete.
3. ACI 301 (ACI 301M) Surface Finish SF-3.0:
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 13
a. Patch voids larger than 3/4 inch (19 mm) wide or 1/2 inch (13 mm) deep. b. Remove projections larger than 1/8 inch (3 mm).
c. Patch tie holes.
d. Surface Tolerance: ACI 117 (ACI 117M) Class A.
e. Locations: Apply to concrete surfaces exposed to public view, to receive a rubbed finish, or to be covered with a coating or covering material applied directly to concrete.
3.7 INSTALLATION OF MISCELLANEOUS CONCRETE ITEMS
A. Equipment Bases and Foundations:
1. Coordinate sizes and locations of concrete bases with actual equipment provided.
2. Construct concrete bases 4 inches (100 mm) high unless otherwise indicated on Drawings, and extend base not less than 6 inches (150 mm) in each direction beyond the maximum dimensions of supported equipment unless otherwise indicated on Drawings, or unless required for seismic anchor support.
3. Minimum Compressive Strength: 4000 psi (27.6 MPa) at 28 days.
4. For supported equipment, install epoxy-coated anchor bolts that extend through concrete base and anchor into structural concrete substrate.
5. Prior to pouring concrete, place and secure anchorage devices. a. Use setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded.
b. Cast anchor-bolt insert into bases.
c. Install anchor bolts to elevations required for proper attachment to supported equipment.
3.8 CONCRETE CURING
A. Protect freshly placed concrete from premature drying and excessive cold or hot temperatures.
1. Comply with ACI 301 (ACI 301M) and ACI 306.1 for cold weather protection during curing.
2. Comply with ACI 301 (ACI 301M) and ACI 305.1 (ACI 305.1M) for hot-weather protection during curing.
3. Maintain moisture loss no more than 0.2 lb/sq. ft. x h (1 kg/sq. m x h), calculated in accordance with ACI 305.1, before and during finishing operations.
B. Curing Formed Surfaces: Comply with ACI 308.1 (ACI 308.1M) as follows:
1. Cure formed concrete surfaces, including underside of beams, supported slabs, and other similar surfaces.
2. Cure concrete containing color pigments in accordance with color pigment manufacturer's instructions.
3. If forms remain during curing period, moist cure after loosening forms.
4. If removing forms before end of curing period, continue curing for remainder of curing period, as follows:
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 14
a. Continuous Fogging: Maintain standing water on concrete surface until final setting of concrete.
b. Continuous Sprinkling: Maintain concrete surface continuously wet. c. Absorptive Cover: Pre-dampen absorptive material before application; apply additional water to absorptive material to maintain concrete surface continuously wet.
d. Water-Retention Sheeting Materials: Cover exposed concrete surfaces with sheeting material, taping, or lapping seams.
e. Membrane-Forming Curing Compound: Apply uniformly in continuous operation by power spray or roller in accordance with manufacturer's written instructions. 1) Recoat areas subject to heavy rainfall within three hours after initial application.
2) Maintain continuity of coating and repair damage during curing period.
C. Curing Unformed Surfaces: Comply with ACI 308.1 (ACI 308.1M) as follows:
1. Begin curing immediately after finishing concrete.
2. Interior Concrete Floors:
a. Floors to Receive Floor Coverings Specified in Other Sections: Contractor has option of the following:
1) Absorptive Cover: As soon as concrete has sufficient set to permit application without marring concrete surface, install prewetted absorptive cover over entire area of floor.
a) Lap edges and ends of absorptive cover not less than 12 inches (300 mm).
b) Maintain absorptive cover water saturated, and in place, for duration of curing period, but not less than seven days.
2) Moisture-Retaining-Cover Curing: Cover concrete surfaces with moistureretaining cover for curing concrete, placed in widest practicable width, with sides and ends lapped at least 12 inches (300 mm), and sealed by waterproof tape or adhesive.
a) Immediately repair any holes or tears during curing period, using cover material and waterproof tape.
b) Cure for not less than seven days.
3) Ponding or Continuous Sprinkling of Water: Maintain concrete surfaces continuously wet for not less than seven days, utilizing one, or a combination of, the following:
a) Water.
b) Continuous water-fog spray.
b. Floors to Receive Penetrating Liquid Floor Treatments: Contractor has option of the following:
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 15
1) Absorptive Cover: As soon as concrete has sufficient set to permit application without marring concrete surface, install prewetted absorptive cover over entire area of floor.
a) Lap edges and ends of absorptive cover not less than 12 inches (300 mm).
b) Maintain absorptive cover water saturated, and in place, for duration of curing period, but not less than seven days.
2) Moisture-Retaining-Cover Curing: Cover concrete surfaces with moistureretaining cover for curing concrete, placed in widest practicable width, with sides and ends lapped at least 12 inches (300 mm), and sealed by waterproof tape or adhesive.
a) Immediately repair any holes or tears during curing period, using cover material and waterproof tape.
b) Cure for not less than seven days.
3) Ponding or Continuous Sprinkling of Water: Maintain concrete surfaces continuously wet for not less than seven days, utilizing one, or a combination of, the following:
a) Water.
b) Continuous water-fog spray.
c. Floors to Receive Polished Finish: Contractor has option of the following:
1) Absorptive Cover: As soon as concrete has sufficient set to permit application without marring concrete surface, install prewetted absorptive cover over entire area of floor.
a) Lap edges and ends of absorptive cover not less than 12 inches (300 mm).
b) Maintain absorptive cover water saturated, and in place, for duration of curing period, but not less than seven days.
2) Ponding or Continuous Sprinkling of Water: Maintain concrete surfaces continuously wet for not less than seven days, utilizing one, or a combination of, the following:
a) Water.
b) Continuous water-fog spray.
d. Floors to Receive Chemical Stain:
1) As soon as concrete has sufficient set to permit application without marring concrete surface, install curing paper over entire area of floor. 2) Install curing paper square to building lines, without wrinkles, and in a single length without end joints.
3) Butt sides of curing paper tight; do not overlap sides of curing paper.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 16
4) Leave curing paper in place for duration of curing period, but not less than 28 days.
e. Floors to Receive Urethane Flooring:
1) As soon as concrete has sufficient set to permit application without marring concrete surface, install prewetted absorptive cover over entire area of floor. 2) Rewet absorptive cover, and cover immediately with polyethylene moistureretaining cover with edges lapped 6 inches (150 mm) and sealed in place. 3) Secure polyethylene moisture-retaining cover in place to prohibit air from circulating under polyethylene moisture-retaining cover. 4) Leave absorptive cover and polyethylene moisture-retaining cover in place for duration of curing period, but not less than 28 days. f. Floors to Receive Curing Compound:
1) Apply uniformly in continuous operation by power spray or roller in accordance with manufacturer's written instructions.
2) Recoat areas subjected to heavy rainfall within three hours after initial application.
3) Maintain continuity of coating, and repair damage during curing period. 4) Removal: After curing period has elapsed, remove curing compound without damaging concrete surfaces by method recommended by curing compound manufacturer unless manufacturer certifies curing compound does not interfere with bonding of floor covering used on Project. g. Floors to Receive Curing and Sealing Compound:
1) Apply uniformly to floors and slabs indicated in a continuous operation by power spray or roller in accordance with manufacturer's written instructions. 2) Recoat areas subjected to heavy rainfall within three hours after initial application.
3) Repeat process 24 hours later, and apply a second coat. Maintain continuity of coating, and repair damage during curing period.
3.9 TOLERANCES
A. Conform to ACI 117 (ACI 117M).
3.10 JOINT FILLING
A. Prepare, clean, and install joint filler in accordance with manufacturer's written instructions.
1. Defer joint filling until concrete has aged at least one month(s).
2. Do not fill joints until construction traffic has permanently ceased.
B. Remove dirt, debris, saw cuttings, curing compounds, and sealers from joints; leave contact faces of joints clean and dry.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 17
C. Install semirigid joint filler full depth in saw-cut joints and at least 2 inches (50 mm) deep in formed joints.
D. Overfill joint, and trim joint filler flush with top of joint after hardening.
3.11 CONCRETE SURFACE REPAIRS
A. Defective Concrete:
1. Repair and patch defective areas when approved by Architect.
2. Remove and replace concrete that cannot be repaired and patched to Architect's approval.
B. Patching Mortar: Mix dry-pack patching mortar, consisting of 1 part portland cement to 2-1/2 parts fine aggregate passing a No. 16 (1.18-mm) sieve, using only enough water for handling and placing.
C. Repairing Formed Surfaces: Surface defects include color and texture irregularities, cracks, spalls, air bubbles, honeycombs, rock pockets, fins and other projections on the surface, and stains and other discolorations that cannot be removed by cleaning.
1. Immediately after form removal, cut out honeycombs, rock pockets, and voids more than 1/2 inch (13 mm) in any dimension to solid concrete.
a. Limit cut depth to 3/4 inch (19 mm).
b. Make edges of cuts perpendicular to concrete surface. c. Clean, dampen with water, and brush-coat holes and voids with bonding agent. d. Fill and compact with patching mortar before bonding agent has dried. e. Fill form-tie voids with patching mortar or cone plugs secured in place with bonding agent.
2. Repair defects on surfaces exposed to view by blending white portland cement and standard portland cement, so that, when dry, patching mortar matches surrounding color. a. Patch a test area at inconspicuous locations to verify mixture and color match before proceeding with patching.
b. Compact mortar in place and strike off slightly higher than surrounding surface.
3. Repair defects on concealed formed surfaces that will affect concrete's durability and structural performance as determined by Architect.
D. Repairing Unformed Surfaces:
1. Test unformed surfaces, such as floors and slabs, for finish, and verify surface tolerances specified for each surface.
a. Correct low and high areas.
b. Test surfaces sloped to drain for trueness of slope and smoothness; use a sloped template.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 18
2. Repair finished surfaces containing surface defects, including spalls, popouts, honeycombs, rock pockets, crazing, and cracks in excess of 0.01 inch (0.25 mm) wide or that penetrate to reinforcement or completely through unreinforced sections regardless of width, and other objectionable conditions.
3. After concrete has cured at least 14 days, correct high areas by grinding.
4. Correct localized low areas during, or immediately after, completing surface-finishing operations by cutting out low areas and replacing with patching mortar. a. Finish repaired areas to blend into adjacent concrete.
5. Correct other low areas scheduled to receive floor coverings with a repair underlayment. a. Prepare, mix, and apply repair underlayment and primer in accordance with manufacturer's written instructions to produce a smooth, uniform, plane, and level surface.
b. Feather edges to match adjacent floor elevations.
6. Correct other low areas scheduled to remain exposed with repair topping. a. Cut out low areas to ensure a minimum repair topping depth of 1/4 inch (6 mm) to match adjacent floor elevations.
b. Prepare, mix, and apply repair topping and primer in accordance with manufacturer's written instructions to produce a smooth, uniform, plane, and level surface.
7. Repair defective areas, except random cracks and single holes 1 inch (25 mm) or less in diameter, by cutting out and replacing with fresh concrete. a. Remove defective areas with clean, square cuts, and expose steel reinforcement with at least a 3/4-inch (19-mm) clearance all around.
b. Dampen concrete surfaces in contact with patching concrete and apply bonding agent.
c. Mix patching concrete of same materials and mixture as original concrete, except without coarse aggregate.
d. Place, compact, and finish to blend with adjacent finished concrete. e. Cure in same manner as adjacent concrete.
8. Repair random cracks and single holes 1 inch (25 mm) or less in diameter with patching mortar.
a. Groove top of cracks and cut out holes to sound concrete, and clean off dust, dirt, and loose particles.
b. Dampen cleaned concrete surfaces and apply bonding agent. c. Place patching mortar before bonding agent has dried. d. Compact patching mortar and finish to match adjacent concrete. e. Keep patched area continuously moist for at least 72 hours.
E. Perform structural repairs of concrete, subject to Architect's approval, using epoxy adhesive and patching mortar.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 19
F. Repair materials and installation not specified above may be used, subject to Architect's approval.
3.12 FIELD QUALITY CONTROL
A. Special Inspections: Contractor will engage a special inspector to perform field tests and inspections and prepare testing and inspection reports.
B. Testing Agency: Engage a qualified testing and inspecting agency to perform tests and inspections and to submit reports.
1. Testing agency to be responsible for providing curing container for composite samples on Site and verifying that field-cured composite samples are cured in accordance with ASTM C31/C31M.
2. Testing agency to immediately report to Architect, Contractor, and concrete manufacturer any failure of Work to comply with Contract Documents.
3. Testing agency to report results of tests and inspections, in writing, to Owner, Architect, Contractor, and concrete manufacturer within 48 hours of inspections and tests. a. Test reports to include reporting requirements of ASTM C31/C31M, ASTM C39/C39M, and ACI 301, including the following as applicable to each test and inspection:
1) Project name.
2) Name of testing agency.
3) Names and certification numbers of field and laboratory technicians performing inspections and testing.
4) Name of concrete manufacturer.
5) Date and time of inspection, sampling, and field testing. 6) Date and time of concrete placement.
7) Location in Work of concrete represented by samples. 8) Date and time sample was obtained.
9) Truck and batch ticket numbers.
10) Design compressive strength at 28 days.
11) Concrete mixture designation, proportions, and materials. 12) Field test results.
13) Information on storage and curing of samples before testing, including curing method and maximum and minimum temperatures during initial curing period.
14) Type of fracture and compressive break strengths at seven days and 28 days.
C. Batch Tickets: For each load delivered, submit three copies of batch delivery ticket to testing agency, indicating quantity, mix identification, admixtures, design strength, aggregate size, design air content, design slump at time of batching, and amount of water that can be added at Project site.
D. Inspections:
1. Verification of use of required design mixture.
2. Concrete placement, including conveying and depositing.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 20
3. Curing procedures and maintenance of curing temperature.
4. Verification of concrete strength before removal of shores and forms from beams and slabs.
5. Batch Plant Inspections: On a random basis, as determined by Architect.
E. Concrete Tests: Testing of composite samples of fresh concrete obtained in accordance with ASTM C 172/C 172M to be performed in accordance with the following requirements:
1. Testing Frequency: Obtain one composite sample for each day's pour of each concrete mixture exceeding 5 cu. yd. (4 cu. m), but less than 25 cu. yd. (19 cu. m), plus one set for each additional 50 cu. yd. (38 cu. m) or fraction thereof. a. When frequency of testing provides fewer than five compressive-strength tests for each concrete mixture, testing to be conducted from at least five randomly selected batches or from each batch if fewer than five are used.
2. Slump: ASTM C143/C143M:
a. One test at point of placement for each composite sample, but not less than one test for each day's pour of each concrete mixture.
b. Perform additional tests when concrete consistency appears to change.
3. Slump Flow: ASTM C1611/C1611M:
a. One test at point of placement for each composite sample, but not less than one test for each day's pour of each concrete mixture.
b. Perform additional tests when concrete consistency appears to change.
4. Air Content: ASTM C231/C231M pressure method, for normal-weight concrete; ASTM C173/C173M volumetric method, for structural lightweight concrete. a. One test for each composite sample, but not less than one test for each day's pour of each concrete mixture.
5. Concrete Temperature: ASTM C1064/C1064M:
a. One test hourly when air temperature is 40 deg F (4.4 deg C) and below or 80 deg F (27 deg C) and above, and one test for each composite sample.
6. Unit Weight: ASTM C567/C567M fresh unit weight of structural lightweight concrete. a. One test for each composite sample, but not less than one test for each day's pour of each concrete mixture.
7. Compression Test Specimens: ASTM C31/C31M:
a. Cast and laboratory cure two sets of three 6-inch (150 mm) by 12-inch (300 mm) or 4-inch (100 mm) by 8-inch (200 mm) cylinder specimens for each composite sample.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 21
b. Cast, initial cure, and field cure two sets of four standard cylinder specimens for each composite sample.
8. Compressive-Strength Tests: ASTM C39/C39M.
a. Test one set of two laboratory-cured specimens at seven days and one set of two specimens at 28 days.
b. Test one set of two field-cured specimens at seven days and one set of two specimens at 28 days.
c. A compressive-strength test to be the average compressive strength from a set of two specimens obtained from same composite sample and tested at age indicated.
9. When strength of field-cured cylinders is less than 85 percent of companion laboratorycured cylinders, Contractor to evaluate operations and provide corrective procedures for protecting and curing in-place concrete.
10. Strength of each concrete mixture will be satisfactory if every average of any three consecutive compressive-strength tests equals or exceeds specified compressive strength, and no compressive-strength test value falls below specified compressive strength by more than 500 psi (3.4 MPa) if specified compressive strength is 5000 psi (34.5 MPa), or no compressive strength test value is less than 10 percent of specified compressive strength if specified compressive strength is greater than 5000 psi (34.5 MPa).
11. Nondestructive Testing: Impact hammer, sonoscope, or other nondestructive device may be permitted by Architect but will not be used as sole basis for approval or rejection of concrete.
F. Measure floor and slab flatness and levelness in accordance with ASTM E1155 (ASTM E1155M) within 24 hours of completion of floor finishing and promptly report test results to Architect.
3.13 PROTECTION
A. Protect concrete surfaces as follows:
1. Protect from petroleum stains.
2. Diaper hydraulic equipment used over concrete surfaces.
3. Prohibit vehicles from interior concrete slabs.
4. Prohibit use of pipe-cutting machinery over concrete surfaces.
5. Prohibit placement of steel items on concrete surfaces.
6. Prohibit use of acids or acidic detergents over concrete surfaces.
7. Protect liquid floor treatment from damage and wear during the remainder of construction period. Use protective methods and materials, including temporary covering, recommended in writing by liquid floor treatments installer.
8. Protect concrete surfaces scheduled to receive surface hardener or polished concrete finish using Floor Slab Protective Covering.
END OF SECTION 033000
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CAST-IN-PLACE CONCRETE 033000 - 22
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230529 - 1 SECTION 230529
HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Pipe hangers and supports - carbon steel.
2. Pipe hangers and supports - stainless steel.
3. Pipe hangers - metal, trapeze type.
4. Strut support system - metal, rod type.
5. Fastener system - powder-actuated fasteners.
6. Fastener system - mechanical expansion anchors.
7. Equipment supports.
B. Related Requirements:
1. Section 230548 “Vibration and Seismic Controls for HVAC” for vibration isolation devices.
2. Section 233113 “Metal Ducts” for duct hangers and supports.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Shop Drawings: Signed and sealed by a qualified professional engineer. Show fabrication and installation details and include calculations for the following:
1. Trapeze pipe hangers.
2. Metal strut support systems.
3. Pipe stands.
4. Equipment supports.
C. Delegated Design Submittals: For trapeze hangers and strut support systems indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
1. Detail fabrication/assembly and design calculations for trapeze hangers and strut support systems.
2. Detail fabrication/assembly and design calculations for each type of strut support system, by the manufacturer's technical representative.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230529 - 2
1.3 INFORMATIONAL SUBMITTALS
A. Welding certificates.
1.4 QUALITY ASSURANCE
A. Structural-Steel Welding Qualifications: Qualify procedures and personnel in accordance with AWS D1.1/D1.1M, "Structural Welding Code - Steel."
B. Pipe Welding Qualifications: Qualify procedures and operators in accordance with 2021 ASME Boiler and Pressure Vessel Code, Section IX.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Delegated Design: Engage a qualified professional engineer, as defined in Section 014000 "Quality Requirements," to design trapeze hangers, strut support systems, and equipment supports.
B. Structural Performance: Hangers and supports for HVAC piping and equipment are to withstand the effects of gravity loads and stresses within limits and under conditions indicated in accordance with ASCE/SEI 7.
1. Design supports for multiple pipes, including pipe stands, capable of supporting combined weight of supported systems, system contents, and test water.
2. Design equipment supports capable of supporting combined operating weight of supported equipment and connected systems and components.
3. Design seismic-restraint hangers and supports for piping and equipment and obtain approval from authorities having jurisdiction.
2.2 PIPE HANGERS AND SUPPORTS - METAL
A. Pipe Hangers and Supports - Carbon Steel:
1. Description: MSS SP-58, Types 1 through 58, factory-fabricated components.
2. Galvanized Metallic Coatings: Pregalvanized, hot-dip galvanized, or electro-galvanized.
3. Nonmetallic Coatings: Plastic coated, or epoxy powder coated.
4. Padded Hangers: Hanger with fiberglass or other pipe insulation pad or cushion to support bearing surface of piping.
5. Hanger Rods: Continuous-thread rod, nuts, and washers made of stainless steel.
B. Pipe Hangers and Supports - Stainless Steel:
1. Description: MSS SP-58, Types 1 through 58, factory-fabricated components.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230529 - 3
2. Padded Hangers: Hanger with fiberglass or other pipe insulation pad or cushion to support bearing surface of piping.
3. Hanger Rods: Continuous-thread rod, nuts, and washer made of stainless steel.
2.3 PIPE HANGERS - METAL, TRAPEZE TYPE
A. Description: MSS SP-58, Type 59, shop- or field-fabricated pipe-support assembly made from structural carbon-steel shapes with MSS SP-58 carbon-steel hanger rods, nuts, saddles, and Ubolts.
2.4 STRUT SUPPORT SYSTEMS - METAL
A. Strut Support System - Metal, Rod Type:
1. Description: Factory-fabricated pipe-support assembly made of steel channels, vertical metal support rods, accessories, fittings, and other components for supporting multiple parallel pipes.
2. Standard: Comply with MFMA-4 factory-fabricated components for field assembly.
3. Struts: Continuous slotted stainless steel, Type 304.
4. Strut Width: Selected for applicable load criteria.
5. Strut Nuts: Formed or stamped nuts or other devices designed to fit into channel slot and, when tightened, prevent slipping along channel.
6. Hanger Rods: Continuous-thread rod, nuts, and washer made of stainless steel.
7. Metallic Coating: Pregalvanized G90 (Z275).
8. Paint Coating: Green epoxy, acrylic, or urethane.
2.5 FASTENER SYSTEMS
A. Fastener System - Powder-Actuated Fasteners: Threaded-steel stud, for use in hardened portland cement concrete with pull-out, tension, and shear capacities required for supported loads and building materials where used.
B. Fastener System - Mechanical-Expansion Anchors: Insert-wedge-type anchors for use in hardened portland cement concrete; with pull-out, tension, and shear capacities required for supported loads and building materials where used.
1. Indoor Applications: stainless steel.
2. Outdoor Applications: Stainless steel.
2.6 EQUIPMENT SUPPORTS
A. Description: Welded, shop- or field-fabricated equipment support made from structural carbonsteel shapes.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230529 - 4
2.7 MATERIALS
A. Aluminum: ASTM B221 (ASTM B221M).
B. Carbon Steel: ASTM A1011/A1011M.
C. Structural Steel: ASTM A36/A36M, carbon-steel plates, shapes, and bars; galvanized.
D. Stainless Steel: ASTM A240/A240M.
E. Threaded Rods: Continuously threaded. Galvanized steel for indoor applications and stainless steel for outdoor applications. Mating nuts and washers of similar materials as rods.
F. Grout: ASTM C1107/C1107M, factory-mixed and -packaged, dry, hydraulic-cement, nonshrink and nonmetallic grout; suitable for interior and exterior applications.
1. Properties: Nonstaining, noncorrosive, and nongaseous.
2. Design Mix: 5000 psi (34.5 MPa), 28-day compressive strength.
PART 3 - EXECUTION
3.1 APPLICATION
A. Comply with requirements in Section 078413 "Penetration Firestopping" for firestopping materials and installation for penetrations through fire-rated walls, ceilings, and assemblies.
B. Strength of Support Assemblies: Where not indicated, select sizes of components so strength will be adequate to carry static loads within specified loading limits. Minimum static design load used for strength determination is to include weight of supported components plus 200 lb (90 kg).
3.2 INSTALLATION OF HANGERS AND SUPPORTS
A. Install hangers and supports to allow controlled thermal and seismic movement of piping systems, to permit freedom of movement between pipe anchors, and to facilitate action of expansion joints, expansion loops, expansion bends, and similar units.
B. Install lateral bracing with pipe hangers and supports to prevent swaying.
C. Install building attachments within concrete slabs or attach to structural steel. Install additional attachments at concentrated loads, including valves, flanges, and strainers, and at changes in direction of piping. Coordinate location of concrete inserts before concrete is placed.
D. Load Distribution: Install hangers and supports so that piping live and dead loads and stresses from movement will not be transmitted to connected equipment.
E. Pipe Slopes: Install hangers and supports to provide indicated pipe slopes and to not exceed maximum pipe deflections allowed by ASME B31.9 for building services piping.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230529 - 5 F. Insulated Piping:
1. Attach clamps and spacers to piping.
a. Piping Operating above Ambient Air Temperature: Clamp may project through insulation.
b. Piping Operating below Ambient Air Temperature: Use thermal hanger shield insert with clamp sized to match OD of insert.
c. Do not exceed pipe stress limits allowed by ASME B31.9 for building services piping.
2. Install MSS SP-58, Type 39, protection saddles if insulation without vapor barrier is indicated. Fill interior voids with insulation that matches adjoining insulation. a. Thermal hanger shield inserts may be used as an option. Include steel weightdistribution plate for pipe NPS 4 (DN 100) and larger if pipe is installed on rollers.
3. Install MSS SP-58, Type 40, protective shields on cold piping with vapor barrier. Shields are to span an arc of 180 degrees.
a. Thermal hanger shield inserts may be used as an option. Include steel weightdistribution plate for pipe NPS 4 (DN 100) and larger if pipe is installed on rollers.
4. Shield Dimensions for Pipe: Not less than the following:
a. NPS 1/4 to NPS 3-1/2 (DN 8 to DN 90): 12 inches (305 mm) long and 0.048 inch (1.22 mm) thick.
b. NPS 4 (DN 100): 12 inches (305 mm) long and 0.06 inch (1.52 mm) thick. c. NPS 5 and NPS 6 (DN 125 and DN 150): 18 inches (457 mm) long and 0.06 inch (1.52 mm) thick.
d. NPS 8 to NPS 14 (DN 200 to DN 350): 24 inches (610 mm) long and 0.075 inch (1.91 mm) thick.
e. NPS 16 to NPS 24 (DN 400 to DN 600): 24 inches (610 mm) long and 0.105 inch (2.67 mm) thick.
5. Pipes NPS 8 (DN 200) and Larger: Include wood or reinforced calcium-silicateinsulation inserts of length at least as long as protective shield.
G. Metal Pipe-Hanger Installation: Comply with MSS SP-58. Install hangers, supports, clamps, and attachments as required to properly support piping from the building structure.
H. Metal Trapeze Pipe-Hanger Installation: Comply with MSS SP-58. Arrange for grouping of parallel runs of horizontal piping, and support together on field-fabricated trapeze pipe hangers.
1. Pipes of Various Sizes: Support together and space trapezes for smallest pipe size, or install intermediate supports for smaller diameter pipes as specified for individual pipe hangers.
2. Field fabricate in accordance with ASTM A36/A36M, carbon-steel shapes selected for loads being supported. Weld steel in accordance with AWS D1.1/D1.1M.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230529 - 6 I. Strut System Installation: Metal, rod type. Arrange for grouping of parallel runs of piping, and support together on field-assembled strut systems. Install in accordance with manufacturer's written installation instructions.
J. Thermal Hanger Shield Installation: Install in pipe hanger or shield for insulated piping.
K. Fastener System Installation:
1. Install powder-actuated fasteners for use in lightweight concrete or concrete slabs less than 4 inches (100 mm) thick after concrete is placed and cured. Use installers that are trained and certified by power tool manufacturer.
2. Install mechanical-expansion anchors after concrete is placed and completely cured.
3. Install fasteners in accordance with manufacturer's written instructions.
4. Install lag screw wood fasteners in accordance with manufacturer's written instructions.
L. Install hangers and supports complete with necessary attachments, inserts, bolts, rods, nuts, washers, and other accessories.
M. Equipment Support Installation:
1. Fabricate from welded-structural-steel shapes.
2. Fabricate structural-steel stands to suspend equipment from structure overhead or to support equipment above floor.
3. Grouting: Place grout under supports for floor-mounted equipment, and make bearing surface smooth.
4. Provide lateral bracing, to prevent swaying.
3.3 METAL FABRICATIONS
A. Cut, drill, and fit miscellaneous metal fabrications for trapeze pipe hangers and equipment supports.
B. Fit exposed connections together to form hairline joints. Field weld connections that cannot be shop welded.
C. Field Welding: Comply with AWS D1.1/D1.1M procedures for shielded, metal arc welding; appearance and quality of welds; methods used in correcting welding work; and with the following:
1. Use materials and methods that minimize distortion and develop strength and corrosion resistance of base metals.
2. Obtain fusion without undercut or overlap.
3. Remove welding flux immediately.
4. Finish welds at exposed connections so no roughness shows after finishing and so contours of welded surfaces match adjacent contours.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230529 - 7
3.4 ADJUSTING
A. Hanger Adjustments: Adjust hangers to distribute loads equally on attachments and to achieve indicated slope of pipe.
B. Trim excess length of continuous-thread hanger and support rods to 1-1/2 inches (40 mm).
3.5 PAINTING
A. Touchup:
1. Clean field welds and abraded areas of shop paint. Paint exposed areas immediately after erecting hangers and supports. Use same materials as used for shop painting. Comply with SSPC-PA 1 requirements for touching up field-painted surfaces. a. Apply paint by brush or spray to provide a minimum dry film thickness of 2.0 mils (0.05 mm).
2. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply galvanizing-repair paint to comply with ASTM A780/A780M.
3.6 HANGER AND SUPPORT SCHEDULE
A. Specific hanger and support requirements are in Sections specifying piping systems and equipment.
B. Comply with MSS SP-58 for pipe-hanger selections and applications that are not specified in piping system Sections.
C. Use hangers and supports with galvanized metallic coatings for piping and equipment that will not have field-applied finish.
D. Use nonmetallic coatings on attachments for electrolytic protection where attachments are in direct contact with copper tubing.
E. Use stainless steel pipe hangers and stainless steel attachments for hostile environment applications.
F. Use padded hangers for piping that is subject to scratching.
G. Use thermal hanger shield inserts for insulated piping and tubing.
H. Horizontal-Piping Hangers and Supports: Unless otherwise indicated and except as specified in piping system Sections, install the following types:
1. Adjustable, Steel Clevis Hangers (MSS Type 1): For suspension of noninsulated or insulated, stationary pipes NPS 1/2 to NPS 30 (DN 15 to DN 750).
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230529 - 8
2. Yoke-Type Pipe Clamps (MSS Type 2): For suspension of up to 1050 deg F (566 deg C), pipes NPS 4 to NPS 24 (DN 100 to DN 600), requiring up to 4 inches (100 mm) of insulation.
3. Carbon- or Alloy-Steel, Double-Bolt Pipe Clamps (MSS Type 3): For suspension of pipes NPS 3/4 to NPS 36 (DN 20 to DN 900), requiring clamp flexibility and up to 4 inches (100 mm) of insulation.
4. Steel Pipe Clamps (MSS Type 4): For suspension of cold and hot pipes NPS 1/2 to NPS 24 (DN 15 to DN 600) if little or no insulation is required.
5. Pipe Hangers (MSS Type 5): For suspension of pipes NPS 1/2 to NPS 4 (DN 15 to DN 100), to allow off-center closure for hanger installation before pipe erection.
6. Adjustable, Swivel Split- or Solid-Ring Hangers (MSS Type 6): For suspension of noninsulated, stationary pipes NPS 3/4 to NPS 8 (DN 20 to DN 200).
7. Adjustable, Steel Band Hangers (MSS Type 7): For suspension of noninsulated, stationary pipes NPS 1/2 to NPS 8 (DN 15 to DN 200).
8. Adjustable Band Hangers (MSS Type 9): For suspension of noninsulated, stationary pipes NPS 1/2 to NPS 8 (DN 15 to DN 200).
9. Adjustable, Swivel-Ring Band Hangers (MSS Type 10): For suspension of noninsulated, stationary pipes NPS 1/2 to NPS 8 (DN 15 to DN 200).
10. Split Pipe Ring with or without Turnbuckle Hangers (MSS Type 11): For suspension of noninsulated, stationary pipes NPS 3/8 to NPS 8 (DN 10 to DN 200).
11. Extension Hinged or Two-Bolt Split Pipe Clamps (MSS Type 12): For suspension of noninsulated, stationary pipes NPS 3/8 to NPS 3 (DN 10 to DN 80).
12. U-Bolts (MSS Type 24): For support of heavy pipes NPS 1/2 to NPS 30 (DN 15 to DN 750).
13. Clips (MSS Type 26): For support of insulated pipes not subject to expansion or contraction.
14. Pipe Saddle Supports (MSS Type 36): For support of pipes NPS 4 to NPS 36 (DN 100 to DN 900), with steel-pipe base stanchion support and cast-iron floor flange or carbon-steel plate.
15. Pipe Stanchion Saddles (MSS Type 37): For support of pipes NPS 4 to NPS 36 (DN 100 to DN 900), with steel-pipe base stanchion support and cast-iron floor flange or carbonsteel plate, and with U-bolt to retain pipe.
16. Adjustable Pipe Saddle Supports (MSS Type 38): For stanchion-type support for pipes NPS 2-1/2 to NPS 36 (DN 65 to DN 900) if vertical adjustment is required, with steelpipe base stanchion support and cast-iron floor flange.
17. Single-Pipe Rolls (MSS Type 41): For suspension of pipes NPS 1 to NPS 30 (DN 25 to DN 750), from two rods if longitudinal movement caused by expansion and contraction might occur.
18. Adjustable Roller Hangers (MSS Type 43): For suspension of pipes NPS 2-1/2 to NPS 24 (DN 65 to DN 600), from single rod if horizontal movement caused by expansion and contraction might occur.
19. Complete Pipe Rolls (MSS Type 44): For support of pipes NPS 2 to NPS 42 (DN 50 to DN 1050) if longitudinal movement caused by expansion and contraction might occur but vertical adjustment is unnecessary.
20. Pipe Roll and Plate Units (MSS Type 45): For support of pipes NPS 2 to NPS 24 (DN 50 to DN 600) if small horizontal movement caused by expansion and contraction might occur and vertical adjustment is unnecessary.
21. Adjustable Pipe Roll and Base Units (MSS Type 46): For support of pipes NPS 2 to NPS 30 (DN 50 to DN 750) if vertical and lateral adjustment during installation might be required in addition to expansion and contraction.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230529 - 9 I. Vertical-Piping Clamps: Unless otherwise indicated and except as specified in piping system Sections, install the following types:
1. Extension Pipe or Riser Clamps (MSS Type 8): For support of pipe risers NPS 3/4 to NPS 24 (DN 24 to DN 600).
2. Carbon- or Alloy-Steel Riser Clamps (MSS Type 42): For support of pipe risers NPS 3/4 to NPS 24 (DN 20 to DN 600) if longer ends are required for riser clamps.
J. Hanger-Rod Attachments: Unless otherwise indicated and except as specified in piping system Sections, install the following types:
1. Steel Turnbuckles (MSS Type 13): For adjustment up to 6 inches (150 mm) for heavy loads.
2. Steel Clevises (MSS Type 14): For 120 to 450 deg F (49 to 232 deg C) piping installations.
3. Swivel Turnbuckles (MSS Type 15): For use with MSS Type 11, split pipe rings.
4. Malleable-Iron Sockets (MSS Type 16): For attaching hanger rods to various types of building attachments.
5. Steel Weldless Eye Nuts (MSS Type 17): For 120 to 450 deg F (49 to 232 deg C) piping installations.
K. Building Attachments: Unless otherwise indicated and except as specified in piping system Sections, install the following types:
1. Steel or Malleable Concrete Inserts (MSS Type 18): For upper attachment to suspend pipe hangers from concrete ceiling.
2. Top-Beam C-Clamps (MSS Type 19): For use under roof installations with bar-joist construction, to attach to top flange of structural shape.
3. Side-Beam or Channel Clamps (MSS Type 20): For attaching to bottom flange of beams, channels, or angles.
4. Center-Beam Clamps (MSS Type 21): For attaching to center of bottom flange of beams.
5. Welded Beam Attachments (MSS Type 22): For attaching to bottom of beams if loads are considerable and rod sizes are large.
6. C-Clamps (MSS Type 23): For structural shapes.
7. Top-Beam Clamps (MSS Type 25): For top of beams if hanger rod is required tangent to flange edge.
8. Side-Beam Clamps (MSS Type 27): For bottom of steel I-beams.
9. Steel-Beam Clamps with Eye Nuts (MSS Type 28): For attaching to bottom of steel Ibeams for heavy loads.
10. Linked-Steel Clamps with Eye Nuts (MSS Type 29): For attaching to bottom of steel Ibeams for heavy loads, with link extensions.
11. Malleable-Beam Clamps with Extension Pieces (MSS Type 30): For attaching to structural steel.
12. Welded-Steel Brackets: For support of pipes from below or for suspending from above by using clip and rod. Use one of the following for indicated loads:
a. Light (MSS Type 31): 750 lb (340 kg).
b. Medium (MSS Type 32): 1500 lb (680 kg).
c. Heavy (MSS Type 33): 3000 lb (1360 kg).
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT 230529 - 10
13. Side-Beam Brackets (MSS Type 34): For sides of steel or wooden beams.
14. Plate Lugs (MSS Type 57): For attaching to steel beams if flexibility at beam is required.
15. Horizontal Travelers (MSS Type 58): For supporting piping systems subject to linear horizontal movement where headroom is limited.
L. Saddles and Shields: Unless otherwise indicated and except as specified in piping system Sections, install the following types:
1. Steel-Pipe-Covering Protection Saddles (MSS Type 39): To fill interior voids with insulation that matches adjoining insulation.
2. Protection Shields (MSS Type 40): Of length recommended in writing by manufacturer to prevent crushing insulation.
3. Thermal Hanger Shield Inserts: For supporting insulated pipe.
M. Comply with MSS SP-58 for trapeze pipe-hanger selections and applications that are not specified in piping system Sections.
N. Use mechanical-expansion anchors instead of building attachments where required in concrete construction.
END OF SECTION 230529
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
VIBRATION AND SEISMIC CONTROLS FOR HVAC 230548 - 1
SECTION 230548
VIBRATION AND SEISMIC CONTROLS FOR HVAC
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Restraints - rigid type.
2. Restraint accessories.
3. Post-installed concrete anchors.
4. Concrete inserts.
5. Vibration isolation equipment bases.
1.2 DEFINITIONS
A. IBC: International Building Code.
B. OSHPD: Office of Statewide Health Planning and Development (for the State of California owned and regulated medical facilities).
1.3 DELEGATED DESIGN SERVICES
A. Delegated Design Professional: Engage qualified professional structural engineer to design seismic and wind restraints.
1.4 ACTION SUBMITTALS
A. Product Data:
1. For each type of product.
a. Include rated load, rated deflection, and overload capacity for each vibration isolation device.
2. Include load rating for each seismic-restraint device.
3. Illustrate and indicate style, material, strength, fastening provision, and finish for each type and size of vibration isolation device and seismic-restraint component.
4. Annotate types and sizes of seismic restraints and accessories, complete with listing markings or report numbers and load rating in tension and compression as evaluated by ICC-ES product listing.
5. Annotate to indicate application of each product submitted and compliance with requirements.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
VIBRATION AND SEISMIC CONTROLS FOR HVAC 230548 - 2
B. Shop Drawings:
1. Show coordination of seismic-restraints for components with other systems and equipment in the vicinity, including other supports and other seismic restraints.
C. Delegated Design Submittals:
1. All delegated design and submittals for seismic restraints must be signed and sealed by a qualified professional structural engineer responsible for their preparation. Structural engineer is to possess qualifications specified in Section 014000 "Quality Requirements," with expertise in structural engineering, including design of seismic and wind restraints, equipment hangers and supports, and concrete attachments.
2. For each seismic-restraint device, including seismic-restrained mounting, seismic restraint, seismic-restraint accessory, and concrete anchor and insert that is required by this Section or is indicated on Drawings, submit the following:
a. Seismic Restraint, Vibration Isolator, and Vibration Isolation Base Selection:
Select and submit seismic restraints and vibration isolators complying with performance requirements, design criteria, and analysis data. b. Post-Installed Concrete Anchors and Concrete Inserts: Include calculations showing anticipated seismic loads. Include certification that device is approved by an NRTL for reinforcement use.
c. Seismic Design Calculations: Submit all input data and loading calculations.
3. Seismic- and Wind-Restraint Detail Drawing:
a. Design Analysis: To support selection and arrangement of seismic restraints.
Include calculations of combined tensile and shear loads. b. Details: Indicate fabrication and arrangement. Detail attachments of restraints to restrained items and to the structure. Show attachment locations, methods, and spacings. Identify components, list their strengths, and indicate directions and values of forces transmitted to the structure during seismic events. Indicate association with vibration isolation devices.
c. Coordinate seismic-restraint and vibration isolation details with wind-restraint details required for equipment mounted outdoors. Comply also with requirements in other Sections for equipment mounted outdoors.
4. Product Listing, Preapproval, and Evaluation Documentation: By an agency acceptable to authorities having jurisdiction showing maximum ratings of restraint items and basis for approval (tests or calculations).
5. Design Calculations for Vibration Isolation Devices: Calculate static and dynamic loading due to equipment weight and operating forces required to select proper vibration isolators, and to design vibration isolation bases.
6. Riser Supports: Include riser diagrams and calculations showing anticipated expansion and contraction at each support point, initial and final loads on building structure, and spring deflection changes. Include certification that riser system was examined for excessive stress and that none exists.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
VIBRATION AND SEISMIC CONTROLS FOR HVAC 230548 - 3
1.5 INFORMATIONAL SUBMITTALS
A. Coordination Drawings: Show coordination of vibration isolation and seismic-restraint devices for HVAC piping and equipment with other systems and equipment in the vicinity, including other supports and restraints, if any.
B. Qualification Data: For professional engineer.
C. Welding certificates.
D. Field quality-control reports.
1.6 REGULATORY AGENCY APPROVALS
A. Delegated design submittals and Shop Drawings requiring approval by authorities having jurisdiction must be signed by qualified structural professional engineer responsible for their preparation. Submit for action by Architect prior to submitting for approval by authorities having jurisdiction.
1.7 QUALIFICATIONS
A. Professional Structural Engineer: Professional engineer possessing active qualifications specified in Section 014000 "Quality Requirements," with expertise in structural engineering, including design of seismic and wind restraints, equipment hangers and supports, and concrete foundations.
1.8 QUALITY ASSURANCE
A. Testing Agency Qualifications: An independent agency, with the experience and capability to conduct testing indicated, that is an NRTL as defined by OSHA in 29 CFR 1910.7 and that is acceptable to authorities having jurisdiction.
B. Welding Qualifications: Qualify procedures and personnel in accordance with AWS D1.1/D1.1M, "Structural Welding Code - Steel."
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Seismic- and Wind-Restraint-Device Load Ratings: Devices are to be tested and rated in accordance with applicable code requirements and authorities having jurisdiction. Devices are to be listed by a nationally recognized third party that requires periodic follow-up inspections and has a listing directory available to the public. Provide third-party listing by one or more of the following: an agency acceptable to authorities having jurisdiction.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
VIBRATION AND SEISMIC CONTROLS FOR HVAC 230548 - 4
B. Consequential Damage: Provide additional seismic restraints for suspended components or anchorage of floor-, roof-, or wall-mounted components so that failure of a non-essential or essential component will not cause failure of any other essential building component.
C. Fire/Smoke Resistance: Seismic- and wind-restraint devices that are not constructed of ferrous metals are to have a maximum flame-spread index of 25 and maximum smoke-developed index of 50 when tested by qualified testing laboratory in accordance with ASTM E84 or UL 723 and be labeled as such.
D. Component Supports:
1. Load ratings, features, and applications of reinforcement components are to be based on testing standards of qualified testing laboratory.
2.2 RESTRAINTS - RIGID TYPE
A. Source Limitations: Obtain rigid-type restraints from single manufacturer.
B. Description: Shop- or field-fabricated bracing assembly made of AISI S110-07-S1 slotted steel channels, ANSI/ASTM A53/A53M steel pipe as per NFPA 13, or other rigid steel brace member. Includes accessories for attachment to braced component at one end and to building structure at the other end and other matching components and with corrosion-resistant coating; rated in tension, compression, and torsion forces.
2.3 RESTRAINT ACCESSORIES
A. Source Limitations: Obtain restraint accessories from single manufacturer.
B. Hanger-Rod Stiffener: Steel tube or steel slotted-support-system sleeve with internally bolted connections to hanger rod. Non-metallic stiffeners are unacceptable.
C. Hinged and Swivel Brace Attachments: Multifunctional steel connectors for attaching hangers to rigid channel bracings.
D. Bushings for Floor-Mounted Equipment Anchor Bolts: Neoprene bushings designed for rigid equipment mountings and matched to type and size of anchor bolts and studs.
E. Bushing Assemblies for Wall-Mounted Equipment Anchorage: Assemblies of neoprene elements and steel sleeves designed for rigid equipment mountings and matched to type and size of attachment devices used.
F. Resilient Isolation Washers and Bushings: One-piece, molded, oil- and water-resistant neoprene, with a flat washer face.
2.4 POST-INSTALLED CONCRETE ANCHORS
A. Mechanical Anchor Bolts:
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
VIBRATION AND SEISMIC CONTROLS FOR HVAC 230548 - 5
1. Source Limitations: Obtain mechanical anchor bolts from single manufacturer.
2. Drilled-in and stud-wedge or female-wedge type in zinc-coated steel for interior applications and stainless steel for exterior applications. Select anchor bolts with strength for anchor and as tested according to ASTM E488/E488M.
B. Adhesive Anchor Bolts:
1. Source Limitations: Obtain adhesive anchor bolts from single manufacturer.
2. Drilled-in and capsule anchor system containing PVC or urethane methacrylate-based resin and accelerator, or injected polymer or hybrid mortar adhesive. Provide anchor bolts and hardware with zinc-coated steel for interior applications and stainless steel for exterior applications. Select anchor bolts with strength required for anchor and as tested according to ASTM E488/E488M.
C. Provide post-installed concrete anchors that have been prequalified for use in wind-restraint applications. Post-installed concrete anchors must comply with all requirements of ASCE/SEI 7-05, Ch. 13.
1. Prequalify post-installed anchors in concrete in accordance with ACI 355.2 or other approved qualification testing procedures.
2. Prequalify post-installed anchors in masonry in accordance with approved qualification procedures.
D. Expansion-type anchor bolts are not permitted for equipment in excess of 10 hp (7.46 kW) that is not vibration isolated.
1. Undercut expansion anchors are permitted.
2.5 CONCRETE INSERTS
A. Source Limitations: Obtain concrete inserts from single manufacturer.
B. Provide preset concrete inserts that are seismically prequalified in accordance with ICCES AC466 testing.
C. Comply with ANSI/MSS SP-58.
2.6 VIBRATION ISOLATION EQUIPMENT BASES
A. Source Limitations: Obtain vibration isolation equipment bases from single manufacturer.
B. Steel Rails: Factory-fabricated, welded, structural-steel rails.
1. Design Requirements: Lowest possible mounting height with not less than 1-inch (25- mm) clearance above the floor. Include equipment anchor bolts and auxiliary motor slide rails.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
VIBRATION AND SEISMIC CONTROLS FOR HVAC 230548 - 6
2. Structural Steel: Steel shapes, plates, and bars complying with ASTM A36/A36M. Rails to have shape to accommodate supported equipment.
3. Support Brackets: Factory-welded steel brackets on frame for outrigger isolation mountings and to provide for anchor bolts and equipment support.
C. Steel Bases: Factory-fabricated, welded, structural-steel bases and rails.
1. Design Requirements: Lowest possible mounting height with not less than 1-inch (25- mm) clearance above the floor. Include equipment anchor bolts and auxiliary motor slide bases or rails.
2. Structural Steel: Steel shapes, plates, and bars complying with ASTM A36/A36M. Bases to have shape to accommodate supported equipment.
3. Support Brackets: Factory-welded steel brackets on frame for outrigger isolation mountings and to provide for anchor bolts and equipment support.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine areas and equipment to receive vibration isolation and seismic-restraint devices for compliance with requirements for installation tolerances and other conditions affecting performance of the Work.
B. Examine roughing-in of reinforcement and cast-in-place anchors to verify actual locations before installation.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 APPLICATIONS
A. Multiple Pipe Supports: Secure pipes to trapeze member with clamps approved for application by an agency acceptable to authorities having jurisdiction.
B. Hanger-Rod Stiffeners: Install where indicated or scheduled on Drawings to receive them and where required to prevent buckling of hanger rods due to seismic forces.
C. Strength of Support and Assemblies: Where not specifically indicated otherwise, select sizes of components so strength is adequate to carry static and seismic loads within specified loading limits.
3.3 INSTALLATION OF VIBRATION CONTROLS AND SEISMIC RESTRAINTS FOR HVAC
PIPING AND EQUIPMENT
A. Provide seismic-restraint devices and vibration-control devices for systems and equipment where indicated in Equipment Schedules or Vibration-Control Devices Schedules, where
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
VIBRATION AND SEISMIC CONTROLS FOR HVAC 230548 - 7
indicated on Drawings, or where Specifications indicate they are to be installed on specific equipment and systems.
B. Provide seismic-restraint devices for systems and equipment where indicated in Equipment Schedules or Seismic-Restraint Devices Schedules, where indicated on Drawings, where Specifications indicate they are to be installed on specific equipment and systems, and where required by applicable codes.
C. Coordinate location of embedded connection hardware with supported equipment attachment and mounting points and with requirements for concrete reinforcement and formwork specified in Section 033000 "Cast-in-Place Concrete."
D. Installation of vibration isolators must not cause any change of position of equipment, piping, or ductwork resulting in stresses or misalignment.
E. Piping Restraints:
1. Comply with requirements in MSS SP-127.
2. Space lateral supports a maximum of 40 feet (12 m) o.c., and longitudinal supports a maximum of 80 feet (24 m) o.c.
3. Brace a change of direction longer than 12 feet (3.7 m).
F. Ductwork Restraints:
1. Install ducts with hangers and braces designed to support the duct and to restrain against seismic forces required by applicable building codes. Comply with SMACNA's "Seismic Restraint Manual: Guidelines for Mechanical Systems."
2. Space lateral supports a maximum of 40 feet (12 m) o.c., and longitudinal supports a maximum of 80 feet (24 m) o.c.
3. Brace a change of direction longer than 12 feet (3.7 m).
4. Select seismic-restraint devices with capacities adequate to carry static and seismic loads.
5. Install cable restraints on ducts that are suspended with vibration isolators.
G. Install seismic-restraint cables so they do not bend across edges of adjacent equipment or building structure.
H. Install seismic-restraint devices using methods approved by an agency acceptable to authorities having jurisdiction that provides required submittals for component.
I. Install bushing assemblies for anchor bolts for floor-mounted equipment, arranged to provide resilient media between anchor bolt and mounting hole in concrete base.
J. Install bushing assemblies for mounting bolts for wall-mounted equipment, arranged to provide resilient media where equipment or equipment-mounting channels are attached to wall.
K. Attachment to Structure: If specific attachment is not indicated, anchor bracing to structure at flanges of beams, at upper truss chords of bar joists, or at concrete members.
L. Post-Installed Concrete Anchors:
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
VIBRATION AND SEISMIC CONTROLS FOR HVAC 230548 - 8
1. Identify position of reinforcing steel and other embedded items prior to drilling holes for anchors. Do not damage existing reinforcing or embedded items during coring or drilling.
Notify structural engineer if reinforcing steel or other embedded items are encountered during drilling. Locate and avoid prestressed tendons, electrical and telecommunications conduit, and gas lines.
2. Do not drill holes in concrete or masonry until concrete, mortar, or grout has achieved full design strength.
3. Mechanical Anchor Bolts: Protect threads from damage during anchor installation.
Heavy-duty sleeve anchors to be installed with sleeve fully engaged in the structural element to which anchor is to be fastened.
4. Adhesive Anchor Bolts: Clean holes to remove loose material and drilling dust prior to installation of adhesive. Place adhesive in holes proceeding from the bottom of the hole and progressing toward the surface in such a manner as to avoid introduction of air pockets in the adhesive.
5. Set anchors to manufacturer's recommended torque, using a torque wrench.
6. Install zinc-coated steel anchors for interior and stainless steel anchors for exterior applications.
3.4 ACCOMMODATION OF DIFFERENTIAL SEISMIC MOTION
A. Provide flexible connections in piping systems where they cross structural seismic joints and other point where differential movement may occur. Provide adequate flexibility to accommodate differential movement as determined in accordance with ASCE/SEI 7.
3.5 INSTALLATION OF VIBRATION ISOLATION EQUIPMENT BASES A. Coordinate location of embedded connection hardware with supported equipment attachment and mounting points and with requirements for concrete reinforcement and formwork specified in Section 033000 "Cast-in-Place Concrete."
B. Coordinate dimensions of steel equipment rails and bases, concrete inertia bases, and restrained isolation roof-curb rails with requirements of isolated equipment specified in this and other Sections. Where dimensions of these bases are indicated on Drawings, dimensions may require adjustment to accommodate actual isolated equipment.
3.6 ADJUSTING
A. Adjust isolators after system is at operating weight.
B. Adjust limit stops on restrained-spring isolators to mount equipment at normal operating height.
After equipment installation is complete, adjust limit stops so they are out of contact during normal operation.
3.7 FIELD QUALITY CONTROL
A. Testing Agency: Engage a qualified testing agency to perform tests and inspections.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
VIBRATION AND SEISMIC CONTROLS FOR HVAC 230548 - 9
B. Manufacturer's Field Service: Engage a factory-authorized service representative to test and inspect components, assemblies, and equipment installations, including connections.
C. Tests and Inspections:
1. Perform tests and inspections with the assistance of a factory-authorized service representative.
2. Provide evidence of recent calibration of test equipment by a testing agency acceptable to authorities having jurisdiction.
3. Schedule test with Owner, through Architect, before connecting anchorage device to restrained component (unless postconnection testing has been approved), and with at least seven days' advance notice.
4. Obtain Architect's approval before transmitting test loads to structure. Provide temporary load-spreading members.
5. Test no fewer than four of each type and size of installed anchors and fasteners selected by Architect.
6. Test to 90 percent of rated proof load of device.
D. Remove and replace malfunctioning units and retest as specified above.
E. Units will be considered defective if they do not pass tests and inspections.
F. Prepare test and inspection reports.
END OF SECTION 230548
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT 230553 - 1 SECTION 230553
IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Equipment labels.
2. Warning signs and labels.
3. Warning tape.
4. Pipe labels.
5. Duct labels.
6. Valve tags.
7. Warning tags.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Samples: For color, letter style, and graphic representation required for each identification material and device.
C. Equipment-Label Schedule: Include a listing of all equipment to be labeled with the proposed content for each label.
D. Valve-numbering scheme.
E. Valve Schedules: Provide for each piping system. Include in operation and maintenance manuals.
PART 2 - PRODUCTS
2.1 EQUIPMENT LABELS
A. Metal Labels for Equipment:
1. Material and Thickness: anodized aluminum, 0.032-inch (0.8-mm) minimum thickness, with predrilled or stamped holes for attachment hardware.
2. Letter and Background Color: As indicated for specific application under Part 3.
3. Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2 by 3/4 inch (64 by 19 mm).
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT 230553 - 2
4. Minimum Letter Size: 1/4 inch (6.4 mm) for name of units if viewing distance is less than 24 inches (600 mm), 1/2 inch (13 mm) for viewing distances of up to 72 inches (1830 mm), and proportionately larger lettering for greater viewing distances. Include secondary lettering two-thirds to three-fourths the size of principal lettering.
5. Fasteners: Stainless steel rivets or self-tapping screws.
6. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.
B. Label Content: Include equipment's Drawing designation or unique equipment number, Drawing numbers where equipment is indicated (plans, details, and schedules), and the Specification Section number and title where equipment is specified.
2.2 WARNING SIGNS AND LABELS
A. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving, 1/16 inch (1.6 mm) thick, with predrilled holes for attachment hardware.
B. Letter and Background Color: As indicated for specific application under Part 3.
C. Maximum Temperature: Able to withstand temperatures of up to 160 deg F (71 deg C).
D. Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2 by 3/4 inch (64 by 19 mm).
E. Minimum Letter Size: 1/4 inch (6.4 mm) for name of units if viewing distance is less than 24 inches (600 mm), 1/2 inch (13 mm) for viewing distances of up to 72 inches (1830 mm), and proportionately larger lettering for greater viewing distances. Include secondary lettering twothirds to three-fourths the size of principal lettering.
F. Fasteners: Stainless steel rivets or self-taping screws.
G. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.
H. Arc-Flash Warning Signs: Provide arc-flash warning signs in locations and with content in accordance with requirements of OSHA and NFPA70E.
I. Label Content: Include caution and warning information plus emergency notification instructions.
2.3 WARNING TAPE
A. Material: Vinyl.
B. Minimum Thickness: 0.005 inch (0.12 mm).
C. Letter, Pattern, and Background Color: As indicated for specific application under Part 3.
D. Waterproof Adhesive Backing: Suitable for indoor or outdoor use.
E. Maximum Temperature: 160 deg F (70 deg C).
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT 230553 - 3 F. Minimum Width: 2 inches (50 mm).
2.4 PIPE LABELS
A. General Requirements for Manufactured Pipe Labels: Preprinted, color coded, with lettering indicating service and showing flow direction in accordance with ASME A13.1.
B. Letter and Background Color: As indicated for specific application under Part 3.
C. Pretensioned Pipe Labels: Precoiled, semirigid plastic formed to cover full circumference of pipe and to attach to pipe without fasteners or adhesive.
D. Self-Adhesive Pipe Labels: Printed plastic with contact-type, permanent-adhesive backing.
E. Pipe Label Contents: Include identification of piping service using same designations or abbreviations as used on Drawings. Also include:
1. Pipe size.
2. Flow-Direction Arrows: Include flow-direction arrows on main distribution piping.
Arrows may be either integral with label or applied separately.
3. Lettering Size: Size letters in accordance with ASME A13.1 for piping.
2.5 DUCT LABELS
A. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving, 1/16 inch (1.6 mm) thick, and having predrilled holes for attachment hardware.
B. Letter and Background Color: As indicated for specific application under Part 3.
C. Maximum Temperature: Able to withstand temperatures up to 160 deg F (71 deg C).
D. Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2 by 3/4 inch (64 by 19 mm).
E. Minimum Letter Size: 1/4 inch (6.4 mm) for name of units if viewing distance is less than 24 inches (600 mm), 1/2 inch (13 mm) for viewing distances of up to 72 inches (1830 mm), and proportionately larger lettering for greater viewing distances. Include secondary lettering twothirds to three-fourths the size of principal lettering.
F. Fasteners: Stainless steel rivets or self-tapping screws.
G. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.
H. Duct Label Contents: Include identification of duct service using same designations or abbreviations as used on Drawings. Also include the following:
1. Duct size.
2. Flow-Direction Arrows: Include flow-direction arrows on distribution ducts. Arrows may be either integral with label or may be applied separately.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT 230553 - 4
3. Lettering Size: Size letters in accordance with ASME A13.1 for piping.
2.6 VALVE TAGS
A. Description: Stamped or engraved with 1/4-inch (6.4-mm) letters for piping system abbreviation and 1/2-inch (13-mm) numbers.
1. Tag Material: anodized aluminum, 0.031-inch (0.79-mm) minimum thickness, with predrilled or stamped holes for attachment hardware.
2. Fasteners: Brass wire.
B. Letter and Background Color: As indicated for specific application under Part 3.
C. Valve Schedules: For each piping system, on 8-1/2-by-11-inch (A4) bond paper. Tabulate valve number, piping system, system abbreviation (as shown on valve tag), location of valve (room or space), normal-operating position (open, closed, or modulating), and variations for identification. Mark valves for emergency shutoff and similar special uses.
1. Include valve-tag schedule in operation and maintenance data.
2.7 WARNING TAGS
A. Description: Preprinted accident-prevention tags of plasticized card stock with matte finish suitable for writing.
1. Size: 3 by 5-1/4 inches (75 by 133 mm) minimum.
2. Fasteners: Brass grommet and wire.
3. Nomenclature: Large-size primary caption, such as "DANGER," "CAUTION," or "DO NOT OPERATE."
4. Letter and Background Color: As indicated for specific application under Part 3.
PART 3 - EXECUTION
3.1 PREPARATION
A. Clean piping and equipment surfaces of incompatible primers, paints, and encapsulants, as well as dirt, oil, grease, release agents, and other substances that could impair bond of identification devices.
3.2 INSTALLATION, GENERAL REQUIREMENTS
A. Coordinate installation of identifying devices with completion of covering and painting of surfaces where devices are to be applied.
B. Coordinate installation of identifying devices with locations of access panels and doors.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT 230553 - 5 C. Install identifying devices before installing acoustical ceilings and similar concealment.
D. Locate identifying devices so that they are readily visible from the point of normal approach.
3.3 INSTALLATION OF EQUIPMENT LABELS, WARNING SIGNS, AND LABELS A. Permanently fasten labels on each item of mechanical equipment.
B. Sign and Label Colors:
1. White letters on an ANSI Z535.1 safety-blue background.
C. Locate equipment labels where accessible and visible.
D. Arc-Flash Warning Signs: Provide arc-flash warning signs on electrical disconnects and other equipment where arc-flash hazard exists, as indicated on Drawings, and in accordance with requirements of OSHA and NFPA 70E.
3.4 INSTALLATION OF WARNING TAPE
A. Warning Tape Color and Pattern: Yellow background with black diagonal stripes.
B. Install warning tape on pipes and ducts, with cross-designated walkways providing less than 6 ft. (2 m) of clearance.
C. Locate tape so as to be readily visible from the point of normal approach.
3.5 INSTALLATION OF PIPE LABELS
A. Install pipe labels showing service and flow direction with permanent adhesive on pipes.
B. Pipe-Label Locations: Locate pipe labels where piping is exposed or above accessible ceilings in finished spaces; machine rooms; accessible maintenance spaces such as shafts, tunnels, and plenums; and exterior exposed locations as follows:
1. Within 3 ft. (1 m) of each valve and control device.
2. At access doors, manholes, and similar access points that permit view of concealed piping.
3. Within 3 ft. (1 m) of equipment items and other points of origination and termination.
4. Spaced at maximum intervals of 25 ft. (8 m) along each run. Reduce intervals to 10 ft. (3.0 m) in areas of congested piping, ductwork, and equipment.
C. Do not apply plastic pipe labels or plastic tapes directly to bare pipes conveying fluids at temperatures of 125 deg F (52 deg C) or higher. Where these pipes are to remain uninsulated, use a short section of insulation or use stenciled labels.
D. Flow-Direction Arrows: Use arrows to indicate direction of flow in pipes, including pipes where flow is allowed in both directions.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT 230553 - 6 E. Pipe-Label Color Schedule:
1. Toxic and Corrosive Fluids: Black letters on an ANSI Z535.1 safety-orange background.
2. Flammable Fluids: Black letters on an ANSI Z535.1 safety-yellow background.
3. Combustible Fluids: White letters on an ANSI Z535.1 safety-brown background.
4. Compressed Air: White letters on an ANSI Z535.1 safety-blue background.
3.6 INSTALLATION OF DUCT LABELS
A. Install plastic-laminated duct labels showing service and flow direction with permanent adhesive on air ducts.
1. Provide labels in the following color codes:
a. For air supply ducts: White letters on blue background. b. For air return ducts: White letters on blue background. c. For exhaust-, outside-, relief-, return-, and mixed-air ducts: White letters on blue background.
B. Locate label near each point where ducts enter into and exit from concealed spaces and at maximum intervals of 20 ft. (6 m) where exposed or are concealed by removable ceiling system.
3.7 INSTALLATION OF VALVE TAGS
A. Install tags on valves and control devices in piping systems, except check valves, valves within factory-fabricated equipment units, shutoff valves, and HVAC terminal devices and similar roughing-in connections of end-use fixtures and units. List tagged valves in a valve schedule in the operating and maintenance manual.
B. Valve-Tag Application Schedule: Tag valves according to size, shape, and color scheme and with captions similar to those indicated in "Valve-Tag Size and Shape" Subparagraph below.
1. Valve-Tag Size and Shape:
a. Gas: 1-1/2 inches (38 mm) square.
2. Valve-Tag Colors:
a. For each piping system, use the same lettering and background coloring system on valve tags as used for the Pipe Label Schedule text and background.
3.8 INSTALLATION OF WARNING TAGS
A. Warning Tag Color: Black letters on an ANSI Z535.1 safety-yellow background.
B. Attach warning tags, with proper message, to equipment and other items where indicated on Drawings.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT 230553 - 7 END OF SECTION 230553
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 1
SECTION 231123
FACILITY NATURAL-GAS PIPING
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Pipes, tubes, and fittings.
2. Manual gas shutoff valves.
3. Motorized gas valves.
4. Earthquake valves.
5. Pressure regulators.
6. Service meters.
7. Dielectric fittings.
1.2 DEFINITIONS
A. CWP: Cold working pressure.
B. Exposed, Exterior Installations: Exposed to view outdoors or subject to outdoor ambient temperatures and weather conditions. An example includes rooftop locations.
C. Exposed, Interior Installations: Exposed to view indoors. Examples include finished occupied spaces and mechanical equipment rooms.
D. Finished Spaces: Spaces other than mechanical and electrical equipment rooms, furred spaces, pipe and duct shafts, unheated spaces immediately below roof, spaces above ceilings, unexcavated spaces, crawlspaces, and tunnels.
1.3 ACTION SUBMITTALS
A. Product Data:
1. Piping specialties.
2. Corrugated, stainless steel tubing with associated components.
3. Valves. Include pressure rating, capacity, settings, and electrical connection data of selected models.
4. Pressure regulators. Indicate pressure ratings and capacities.
5. Service meters. Indicate pressure ratings and capacities. Include bypass fittings and meter bars.
6. Dielectric fittings.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 2
B. Shop Drawings: For facility natural-gas piping layout. Include plans, piping layout and elevations, sections, and details for fabrication of pipe anchors, hangers, supports for multiple pipes, alignment guides, expansion joints and loops, and attachments of the same to building structure. Detail location of anchors, alignment guides, and expansion joints and loops.
1. Shop Drawing Scale: 1/4 inch per foot (1:50).
2. Detail mounting, supports, and valve arrangements for service-meter assembly and pressure regulator assembly.
1.4 INFORMATIONAL SUBMITTALS
A. Coordination Drawings: Plans and details, drawn to scale, on which natural-gas piping is shown and coordinated with other installations, using input from installers of the items involved.
B. Welding certificates.
C. Site Survey: Plans, drawn to scale, on which natural-gas piping is shown and coordinated with other services and utilities.
D. Field quality-control reports.
E. Qualification Statements: For professional engineer.
1.5 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For pressure regulators and service meters to include in emergency, operation, and maintenance manuals.
1.6 QUALITY ASSURANCE
A. Steel Support Welding Qualifications: Qualify procedures and personnel in accordance with AWS D1.1/D1.1M, "Structural Welding Code - Steel."
B. Pipe Welding Qualifications: Qualify procedures and operators in accordance with the ASME Boiler and Pressure Vessel Code.
1.7 DELIVERY, STORAGE, AND HANDLING
A. Handling Flammable Liquids: Remove and dispose of liquids from existing natural-gas piping in accordance with requirements of authorities having jurisdiction.
B. Deliver pipes and tubes with factory-applied end caps. Maintain end caps through shipping, storage, and handling to prevent pipe end damage and to prevent entrance of dirt, debris, and moisture.
C. Store and handle pipes and tubes having factory-applied protective coatings to avoid damaging coating, and protect from direct sunlight.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 3
D. Protect stored PE pipes and valves from direct sunlight.
1.8 PROJECT CONDITIONS
A. Perform site survey, research public utility records, and verify existing utility locations. Contact utility-locating service for area where Project is located.
B. Interruption of Existing Natural-Gas Service: Do not interrupt natural-gas service to facilities occupied by Owner or others unless permitted under the following conditions, and then only after arranging to provide purging and startup of natural-gas supply in accordance with requirements indicated:
1. Notify Owner no fewer than two days in advance of proposed interruption of natural-gas service.
2. Do not proceed with interruption of natural-gas service without Owner's written permission.
1.9 COORDINATION
A. Coordinate sizes and locations of concrete bases with actual equipment provided.
PART 2 - PRODUCTS
2.1 SOURCE LIMITATIONS
A. Obtain each product type from single source from single manufacturer.
2.2 PERFORMANCE REQUIREMENTS
A. Comply with NFPA 54.
B. Minimum Operating-Pressure Ratings:
1. Piping and Valves: 100 psig (690 kPa) minimum unless otherwise indicated.
2. Service Regulators: 100 psig (690 kPa) minimum unless otherwise indicated.
3. Minimum Operating Pressure of Service Meter: 5 psig (34.5 kPa).
C. Natural-Gas System Pressure within Buildings:
1. Two pressure ranges. Primary pressure is more than 2 psig (13.8 kPa), but not more than 5 psig (34.5 kPa), and is reduced to secondary pressure of more than 0.5 psig (3.45 kPa), but not more than 2 psig (13.8 kPa).
D. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 4
E. Seismic Performance: Natural-gas piping system is to withstand the effects of earthquake motions determined in accordance with ASCE/SEI 7. See Section 230548 "Vibration and Seismic Controls for HVAC Piping and Equipment."
1. The term "withstand" means "the piping system will remain in place without separation of any parts from the device when subjected to the seismic forces specified and the piping system will be fully operational after the seismic event."
2. Component Importance Factor: 1.5.
2.3 PIPES, TUBES, AND FITTINGS
A. Steel Pipe: ASTM A53/A53M, black steel, Schedule 40, Type E or S, Grade B.
1. Malleable-Iron Threaded Fittings: ASME B16.3, Class 150, standard pattern.
2. Wrought-Steel Welding Fittings: ASTM A234/A234M for butt welding and socket welding.
3. Unions: ASME B16.39, Class 150, malleable iron with brass-to-iron seat, ground joint, and threaded ends.
4. Forged-Steel Flanges and Flanged Fittings: ASME B16.5, minimum Class 150, including bolts, nuts, and gaskets of the following material group, end connections, and facings:
a. Material Group: 1.1.
b. End Connections: Threaded or butt welding to match pipe. c. Lapped Face: Not permitted underground.
d. Gasket Materials: ASME B16.20, metallic, flat, asbestos free, aluminum O-rings, and spiral-wound metal gaskets.
e. Bolts and Nuts: ASME B18.2.1, carbon steel aboveground and stainless steel underground.
5. Protective Coating for Underground Piping: Factory-applied, three-layer coating of epoxy, adhesive, and PE.
a. Joint Cover Kits: Epoxy paint, adhesive, and heat-shrink PE sleeves.
6. Mechanical Couplings:
a. Steel flanges and tube with epoxy finish.
b. NBR seals.
c. Stainless steel bolts, washers, and nuts.
d. Coupling is to be capable of joining PE pipe to PE pipe, steel pipe to PE pipe, or steel pipe to steel pipe.
e. Steel body couplings installed underground on plastic pipe are to be factory equipped with anode.
B. Corrugated, Stainless Steel Tubing: Comply with ANSI/IAS LC 1/CSA 6.26.
1. Tubing: ASTM A240/A240M, corrugated, Series 300 stainless steel.
2. Coating: PE with flame retardant.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 5
a. Surface-Burning Characteristics: As determined by testing identical products in accordance with ASTM E84 by qualified testing agency. Identify products with appropriate markings of applicable testing agency.
1) Flame-Spread Index: 25 or less.
2) Smoke-Developed Index: 50 or less.
3. Fittings: Copper-alloy mechanical fittings with ends made to fit and listed for use with corrugated stainless-steel tubing and capable of metal-to-metal seal without gaskets.
Include brazing socket or threaded ends complying with ASME B1.20.1.
4. Striker Plates: Steel, designed to protect tubing from penetrations.
5. Manifolds: Malleable iron or steel with factory-applied protective coating. Threaded connections are to comply with ASME B1.20.1 for pipe inlet and corrugated tubing outlets.
6. Operating-Pressure Rating: 5 psig (34.5 kPa).
C. PE Pipe: ASTM D2513, SDR 11.
1. PE Fittings: ASTM D2683, socket-fusion type or ASTM D3261, butt-fusion type with dimensions matching PE pipe.
2. PE Transition Fittings: Factory-fabricated fittings with PE pipe complying with ASTM D2513, SDR 11; and steel pipe complying with ASTM A53/A53M, black steel, Schedule 40, Type E or S, Grade B.
3. Anodeless Service-Line Risers: Factory fabricated and leak tested. a. Underground Portion: PE pipe complying with ASTM D2513, SDR 11 inlet. b. Casing: Steel pipe complying with ASTM A53/A53M, Schedule 40, black steel, Type E or S, Grade B, with corrosion-protective coating covering. Vent casing aboveground.
c. Aboveground Portion: PE transition fitting.
d. Outlet is threaded or flanged or suitable for welded connection. e. Tracer wire connection.
f. UV shield.
g. Stake supports with factory finish to match steel pipe casing or carrier pipe.
4. Transition Service-Line Risers: Factory fabricated and leak tested. a. Underground Portion: PE pipe complying with ASTM D2513, SDR 11 inlet connected to steel pipe complying with ASTM A53/A53M, Schedule 40, Type E or S, Grade B, with corrosion-protective coating for aboveground outlet. b. Outlet is threaded or flanged or suitable for welded connection. c. Bridging sleeve over mechanical coupling.
d. Factory-connected anode.
e. Tracer wire connection.
f. UV shield.
g. Stake supports with factory finish to match steel pipe casing or carrier pipe.
5. Plastic Mechanical Couplings, NPS 1-1/2 (DN 40) and Smaller: Suitable for joining PE pipe to PE pipe.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 6
a. PE body with molded-in, stainless steel support ring. b. Seals: NBR.
c. Acetal collets.
d. Electro-zinc-plated steel stiffener.
6. Plastic Mechanical Couplings, NPS 2 (DN 50) and Larger: Suitable for joining PE pipe to PE pipe, steel pipe to PE pipe, or steel pipe to steel pipe. a. Fiber-reinforced plastic body.
b. PE body tube.
c. Seals: NBR.
d. Acetal collets.
e. Stainless steel bolts, nuts, and washers.
7. Steel Mechanical Couplings: Suitable for joining plain-end PE pipe to PE pipe, steel pipe to PE pipe, or steel pipe to steel pipe.
a. Stainless steel flanges and tube with epoxy finish.
b. Seals: NBR.
c. Stainless steel bolts, washers, and nuts.
d. Factory-installed anode for steel-body couplings installed underground.
2.4 PIPING SPECIALTIES
A. Appliance Flexible Connectors:
1. Indoor, Fixed-Appliance Flexible Connectors: Comply with ANSI Z21.24.
2. Indoor, Movable-Appliance Flexible Connectors: Comply with ANSI Z21.69.
3. Outdoor, Appliance Flexible Connectors: Comply with ANSI Z21.75.
4. Corrugated, stainless steel tubing with polymer coating.
5. Operating-Pressure Rating: 0.5 psig (3.45 kPa).
6. End Fittings: Zinc-coated steel.
7. Threaded Ends: Comply with ASME B1.20.1.
8. Maximum Length: 72 inches (1830 mm).
B. Quick-Disconnect Devices: Comply with ANSI Z21.41.
1. Copper-alloy convenience outlet and matching plug connector.
2. Seals: Nitrile.
3. Hand operated with automatic shutoff when disconnected.
4. For indoor or outdoor applications.
5. Adjustable, retractable restraining cable.
C. Y-Pattern Strainers:
1. Body: ASTM A126, Class B, cast iron with bolted cover and bottom drain connection.
2. End Connections: Threaded ends for NPS 2 (DN 50) and smaller; flanged ends for NPS 2-1/2 (DN 65) and larger.
3. Strainer Screen: 40-mesh startup strainer, and perforated stainless steel basket with 50 percent free area.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 7
4. CWP Rating: 125 psig (862 kPa).
D. Basket Strainers:
1. Body: ASTM A126, Class B, high-tensile cast iron with bolted cover and bottom drain connection.
2. End Connections: Threaded ends for NPS 2 (DN 50) and smaller; flanged ends for NPS 2-1/2 (DN 65) and larger.
3. Strainer Screen: 40-mesh startup strainer, and perforated stainless steel basket with 50 percent free area.
4. CWP Rating: 125 psig (862 kPa).
E. T-Pattern Strainers:
1. Body: Ductile or malleable iron with removable access coupling and end cap for strainer maintenance.
2. End Connections: Grooved ends.
3. Strainer Screen: 40-mesh startup strainer, and perforated stainless steel basket with 57 percent free area.
4. CWP Rating: 750 psig (5170 kPa).
F. Weatherproof Vent Cap:
1. Cast- or malleable-iron increaser fitting with corrosion-resistant wire screen, with free area at least equal to cross-sectional area of connecting pipe and threaded-end connection.
2.5 JOINING MATERIALS
A. Joint Compound and Tape: Suitable for natural gas.
B. Welding Filler Metals: Comply with AWS D10.12/D10.12M for welding materials appropriate for wall thickness and chemical analysis of steel pipe being welded.
2.6 MANUAL GAS SHUTOFF VALVES
A. General Requirements for Metallic Valves, NPS 2 (DN 50) and Smaller: Comply with ASME B16.33.
1. CWP Rating: 125 psig (862 kPa).
2. Threaded Ends: Comply with ASME B1.20.1.
3. Dryseal Threads on Flare Ends: Comply with ASME B1.20.3.
4. Tamperproof Feature: Locking feature for valves indicated in "Underground, Manual Gas Shutoff Valve Schedule" and "Aboveground, Manual Gas Shutoff Valve Schedule" articles.
5. Listed and labeled by an NRTL acceptable to authorities having jurisdiction for valves 1 inch (25 mm) and smaller.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 8
6. Service Mark: Valves NPS 1-1/4 to NPS 2 (DN 32 to DN 50) having initials "WOG" permanently marked on valve body.
B. General Requirements for Metallic Valves, NPS 2-1/2 (DN 65) and Larger: Comply with ASME B16.38.
1. CWP Rating: 125 psig (862 kPa).
2. Flanged Ends: Comply with ASME B16.5 for steel flanges.
3. Tamperproof Feature: Locking feature for valves indicated in "Underground, Manual Gas Shutoff Valve Schedule" and "Aboveground, Manual Gas Shutoff Valve Schedule" articles.
4. Service Mark: Initials "WOG" permanently marked on valve body.
C. One-Piece, Bronze Ball Valve with Bronze Trim: MSS SP-110.
1. Body: Bronze, complying with ASTM B584.
2. Ball: Chrome-plated brass.
3. Stem: Bronze; blowout proof.
4. Seats: Reinforced TFE; blowout proof.
5. Packing: Separate packnut with adjustable-stem packing threaded ends.
6. Ends: Threaded, flared, or socket as indicated in "Underground, Manual Gas Shutoff Valve Schedule" and "Aboveground, Manual Gas Shutoff Valve Schedule" articles.
7. CWP Rating: 600 psig (4140 kPa).
8. Listing: Valves NPS 1 (DN 25) and smaller are to be listed and labeled by an NRTL acceptable to authorities having jurisdiction.
9. Service: Suitable for natural-gas service with "WOG" indicated on valve body.
D. Two-Piece, Full-Port, Bronze Ball Valves with Bronze Trim: MSS SP-110.
1. Body: Bronze, complying with ASTM B584.
2. Ball: Chrome-plated bronze.
3. Stem: Bronze; blowout proof.
4. Seats: Reinforced TFE; blowout proof.
5. Packing: Threaded-body packnut design with adjustable-stem packing.
6. Ends: Threaded, flared, or socket as indicated in "Underground, Manual Gas Shutoff Valve Schedule" and "Aboveground, Manual Gas Shutoff Valve Schedule" articles.
7. CWP Rating: 600 psig (4140 kPa).
8. Listing: Valves NPS 1 (DN 25) and smaller are to be listed and labeled by an NRTL acceptable to authorities having jurisdiction.
9. Service: Suitable for natural-gas service with "WOG" indicated on valve body.
E. Two-Piece, Regular-Port Bronze Ball Valves with Bronze Trim: MSS SP-110.
1. Body: Bronze, complying with ASTM B584.
2. Ball: Chrome-plated bronze.
3. Stem: Bronze; blowout proof.
4. Seats: Reinforced TFE.
5. Packing: Threaded-body packnut design with adjustable-stem packing.
6. Ends: Threaded, flared, or socket as indicated in "Underground, Manual Gas Shutoff Valve Schedule" and "Aboveground, Manual Gas Shutoff Valve Schedule" articles.
7. CWP Rating: 600 psig (4140 kPa).
8. Listing: Valves NPS 1 (DN 25) and smaller are to be listed and labeled by an NRTL acceptable to authorities having jurisdiction.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 9
9. Service: Suitable for natural-gas service with "WOG" indicated on valve body.
F. Bronze Plug Valves: MSS SP-78.
1. Body: Bronze, complying with ASTM B584.
2. Plug: Bronze.
3. Ends: Threaded, socket, or flanged as indicated in "Underground, Manual Gas Shutoff Valve Schedule" and "Aboveground, Manual Gas Shutoff Valve Schedule" articles.
4. Operator: Square head or lug type with tamperproof feature where indicated.
5. Pressure Class: 125 psig (862 kPa).
6. Listing: Valves NPS 1 (DN 25) and smaller are to be listed and labeled by an NRTL acceptable to authorities having jurisdiction.
7. Service: Suitable for natural-gas service with "WOG" indicated on valve body.
G. Cast-Iron, Nonlubricated Plug Valves: MSS SP-78.
1. Body: Cast iron, complying with ASTM A126, Class B.
2. Plug: Bronze or nickel-plated cast iron.
3. Seat: Coated with thermoplastic.
4. Stem Seal: Compatible with natural gas.
5. Ends: Threaded or flanged as indicated in "Underground, Manual Gas Shutoff Valve Schedule" and "Aboveground, Manual Gas Shutoff Valve Schedule" articles.
6. Operator: Square head or lug type with tamperproof feature where indicated.
7. Pressure Class: 125 psig (862 kPa).
8. Listing: Valves NPS 1 (DN 25) and smaller are to be listed and labeled by an NRTL acceptable to authorities having jurisdiction.
9. Service: Suitable for natural-gas service with "WOG" indicated on valve body.
H. Cast-Iron, Lubricated Plug Valves: MSS SP-78.
1. Body: Cast iron, complying with ASTM A126, Class B.
2. Plug: Bronze or nickel-plated cast iron.
3. Seat: Coated with thermoplastic.
4. Stem Seal: Compatible with natural gas.
5. Ends: Threaded or flanged as indicated in "Underground, Manual Gas Shutoff Valve Schedule" and "Aboveground, Manual Gas Shutoff Valve Schedule" articles.
6. Operator: Square head or lug type with tamperproof feature where indicated.
7. Pressure Class: 125 psig (862 kPa).
8. Listing: Valves NPS 1 (DN 25) and smaller are to be listed and labeled by an NRTL acceptable to authorities having jurisdiction.
9. Service: Suitable for natural-gas service with "WOG" indicated on valve body.
2.7 EARTHQUAKE VALVES
A. Earthquake Valves, Maximum Operating Pressure of 5 psig (34.5 kPa): Comply with ASCE/SEI 25.
1. Listed and labeled by an NRTL acceptable to authorities having jurisdiction.
2. Maximum Operating Pressure: 5 psig (34.5 kPa).
3. Cast-aluminum body with nickel-plated chrome steel internal parts.
4. NBR valve washer.
5. Sight windows for visual indication of valve position.
6. Threaded end connections complying with ASME B1.20.1.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 10
7. Wall-mounting bracket with bubble level indicator.
B. Earthquake Valves, Maximum Operating Pressure of 60 psig (414 kPa): Comply with ASCE/SEI 25.
1. Listed and labeled by an NRTL acceptable to authorities having jurisdiction.
2. Maximum Operating Pressure: 60 psig (414 kPa).
3. Cast-aluminum body with stainless steel internal parts.
4. NBR, reset-stem O-ring seal.
5. Valve position, open or closed, indicator.
6. Composition valve seat with clapper held by spring or magnet locking mechanism.
7. Level indicator.
8. End Connections: Threaded for valves NPS 2 (DN 50) and smaller; flanged for valves NPS 2-1/2 (DN 65) and larger.
2.8 PRESSURE REGULATORS
A. General Requirements:
1. Single stage and suitable for natural gas.
2. Steel jacket and corrosion-resistant components.
3. Elevation compensator.
4. End Connections: Threaded for regulators NPS 2 (DN 50) and smaller; flanged for regulators NPS 2-1/2 (DN 65) and larger.
B. Service Pressure Regulators: Comply with ANSI Z21.80A.
1. Body and Diaphragm Case: Cast iron or die-cast aluminum.
2. Springs: Zinc-plated steel; interchangeable.
3. Diaphragm Plate: Zinc-plated steel.
4. Seat Disc: NBR; resistant to gas impurities, abrasion, and deformation at the valve port.
5. Orifice: Aluminum; interchangeable.
6. Seal Plug: UV-stabilized, mineral-filled nylon.
7. Single-port, self-contained regulator with orifice no larger than required at maximum pressure inlet, and no pressure sensing piping external to regulator.
8. Pressure regulator is to maintain discharge pressure setting downstream and is to not exceed 150 percent of design discharge pressure at shutoff.
9. Overpressure Protection Device: Factory mounted on pressure regulator.
10. Atmospheric Vent: Factory- or field-installed, stainless-steel screen in opening if not connected to vent piping.
11. Maximum Inlet Pressure: 100 psig (690 kPa).
C. Line Pressure Regulators: Comply with ANSI Z21.80A.
1. Body and Diaphragm Case: Cast iron or die-cast aluminum.
2. Springs: Zinc-plated steel; interchangeable.
3. Diaphragm Plate: Zinc-plated steel.
4. Seat Disc: NBR; resistant to gas impurities, abrasion, and deformation at the valve port.
5. Orifice: Aluminum; interchangeable.
6. Seal Plug: UV-stabilized, mineral-filled nylon.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 11
7. Single-port, self-contained regulator with orifice no larger than required at maximum pressure inlet, and no pressure sensing piping external to regulator.
8. Pressure regulator is to maintain discharge pressure setting downstream and is to not exceed 150 percent of design discharge pressure at shutoff.
9. Overpressure Protection Device: Factory mounted on pressure regulator.
10. Atmospheric Vent: Factory- or field-installed, stainless steel screen in opening if not connected to vent piping.
11. Maximum Inlet Pressure: 10 psig (69 kPa).
D. Appliance Pressure Regulators: Comply with ANSI Z21.18.
1. Body and Diaphragm Case: Die-cast aluminum.
2. Springs: Zinc-plated steel; interchangeable.
3. Diaphragm Plate: Zinc-plated steel.
4. Seat Disc: NBR.
5. Seal Plug: UV-stabilized, mineral-filled nylon.
6. Factory-Applied Finish: Minimum three-layer polyester and polyurethane paint finish.
7. Regulator may include vent limiting device, instead of vent connection, if approved by authorities having jurisdiction.
8. Maximum Inlet Pressure: 5 psig (34.5 kPa).
2.9 SERVICE METERS
A. Diaphragm-Type Service Meters: Comply with ANSI B109.1.
1. Case: Die-cast aluminum.
2. Connections: Steel threads.
3. Diaphragm: Synthetic fabric.
4. Diaphragm Support Bearings: Self-lubricating.
5. Compensation: Continuous temperature and pressure.
6. Meter Index: Cubic feet.
7. Meter Case and Index: Tamper resistant.
8. Remote meter reader compatible.
9. Maximum Inlet Pressure: 100 psig (690 kPa).
10. Pressure Loss: Maximum 0.5 inch wg (124 Pa).
11. Accuracy: Maximum plus or minus 1.0 percent.
B. Rotary-Type Service Meters: Comply with ANSI B109.3.
1. Case: Extruded aluminum.
2. Connection: Flange.
3. Impellers: Polished aluminum.
4. Rotor Bearings: Self-lubricating.
5. Compensation: Continuous temperature and pressure.
6. Meter Index: Cubic feet.
7. Tamper resistant.
8. Remote meter reader compatible.
9. Maximum Inlet Pressure: 100 psig (690 kPa).
10. Accuracy: Maximum plus or minus 2.0 percent.
C. Turbine Meters: Comply with ASME MFC-4M.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 12
1. Housing: Cast iron or welded steel.
2. Connection Threads or Flanges: Steel.
3. Turbine: Aluminum or plastic.
4. Turbine Bearings: Self-lubricating.
5. Compensation: Continuous temperature and pressure.
6. Meter Index: Cubic feet.
7. Tamper resistant.
8. Remote meter reader compatible.
9. Maximum Inlet Pressure: 100 psig (690 kPa).
10. Accuracy: Maximum plus or minus 2.0 percent.
D. Service-Meter Bars:
1. Malleable- or cast-iron frame for supporting service meter.
2. Include offset swivel pipes, meter nuts with O-ring seal, and factory- or field-installed dielectric unions.
3. Omit meter offset swivel pipes if service-meter bar dimensions match service-meter connections.
E. Service-Meter Bypass Fittings:
1. Ferrous, tee, pipe fitting with capped side inlet for temporary natural-gas supply.
2. Integral ball-check bypass valve.
2.10 DIELECTRIC FITTINGS
A. General Requirements: Assembly of copper alloy and ferrous materials with separating nonconductive insulating material. Include end connections compatible with pipes to be joined.
B. Dielectric Unions:
1. Description:
a. Standard: ASSE 1079.
b. Pressure Rating: 150 psig (1035 kPa) minimum at 180 deg F (82 deg C). c. End Connections: Solder-joint copper alloy and threaded ferrous.
C. Dielectric Flanges:
1. Description:
a. Standard: ASSE 1079.
b. Factory-fabricated, bolted, companion-flange assembly. c. Pressure Rating: 150 psig (1035 kPa) minimum at 180 deg F (82 deg C). d. End Connections: Solder-joint copper alloy and threaded ferrous; threaded solderjoint copper alloy and threaded ferrous.
D. Dielectric-Flange Insulating Kits:
1. Description:
a. Nonconducting materials for field assembly of companion flanges. b. Pressure Rating: 150 psig (1035 kPa).
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 13
c. Gasket: Neoprene or phenolic.
d. Bolt Sleeves: Phenolic or polyethylene.
e. Washers: Phenolic with steel backing washers.
2.11 LABELING AND IDENTIFYING
A. Detectable Warning Tape: Acid- and alkali-resistant, PE film warning tape manufactured for marking and identifying underground utilities, a minimum of 6 inches (150 mm) wide and 4 mils (0.1 mm) thick, continuously inscribed with a description and rated pressure of utility, with metallic core encased in a protective jacket for corrosion protection, detectable by metal detector when tape is buried up to 30 inches (750 mm) deep; colored yellow.
B. Label and identify gas piping and pressure outside a multitenant building by tenant.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine roughing-in for natural-gas piping system to verify actual locations of piping connections before equipment installation.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Close equipment shutoff valves before turning off natural gas to premises or piping section.
B. Inspect natural-gas piping in accordance with NFPA 54 to determine that natural-gas utilization devices are turned off in piping section affected.
C. Comply with NFPA 54 requirements for preventing accidental ignition.
3.3 INSTALLATION OF OUTDOOR PIPING
A. Comply with NFPA 54 for installation and purging of natural-gas piping.
B. Install underground, natural-gas piping buried at least 36 inches (900 mm) below finished grade. Comply with requirements in Section 312000 "Earth Moving" for excavating, trenching, and backfilling.
1. If natural-gas piping is installed less than 36 inches (900 mm) below finished grade, install it in containment conduit.
C. Install underground, PE, natural-gas piping in accordance with ASTM D2774.
D. Steel Piping with Protective Coating:
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 14
1. Apply joint cover kits to pipe after joining to cover, seal, and protect joints.
2. Repair damage to PE coating on pipe as recommended in writing by protective coating manufacturer.
3. Replace pipe having damaged PE coating with new pipe.
E. Copper Tubing with Protective Coating:
1. Apply joint cover kits over tubing to cover, seal, and protect joints.
2. Repair damage to PE coating on pipe as recommended in writing by protective coating manufacturer.
F. Install fittings for changes in direction and branch connections.
G. Install pressure gauge downstream from each service regulator.
3.4 INSTALLATION OF INDOOR PIPING
A. Comply with NFPA 54 for installation and purging of natural-gas piping.
B. Drawing plans, schematics, and diagrams indicate general location and arrangement of piping systems. Indicated locations and arrangements are used to size pipe and calculate friction loss, expansion, and other design considerations. Install piping as indicated unless deviations to layout are approved on Coordination Drawings.
C. Arrange for pipe spaces, chases, slots, sleeves, and openings in building structure during progress of construction, to allow for mechanical installations.
D. Do not install piping in concealed locations unless sleeved with the sleeve open at both ends.
E. Install piping indicated to be exposed and piping in equipment rooms and service areas at right angles or parallel to building walls. Diagonal runs are prohibited unless specifically indicated otherwise.
F. Where installing piping above accessible ceilings, allow sufficient space for ceiling panel removal.
G. Locate valves for easy access. Do not locate valves within return air plenums.
H. Install natural-gas piping at uniform grade of 2 percent down toward drip and sediment traps.
I. Install piping free of sags and bends.
J. Install fittings for changes in direction and branch connections.
K. Verify final equipment locations for roughing-in.
L. Comply with requirements in Sections specifying gas-fired appliances and equipment for roughing-in requirements.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 15
M. Drips and Sediment Traps: Install drips at points where condensate may collect, including service-meter outlets. Locate where accessible to permit cleaning and emptying. Do not install where condensate is subject to freezing.
1. Construct drips and sediment traps using tee fitting with bottom outlet plugged or capped.
Use nipple a minimum length of 3 pipe diameters, but not less than 3 inches (75 mm) long and same size as connected pipe. Install with space below bottom of drip to remove plug or cap.
2. Install sediment trap on both sides of regulators for gas reduction to 2 psig (13.8 kPa) with valve and cap.
N. Extend relief vent connections for service regulators, line regulators, and overpressure protection devices to outdoors and terminate with weatherproof vent cap.
O. Conceal pipe installations in walls, pipe spaces, utility spaces, above ceilings, below grade or floors, and in floor channels unless indicated to be exposed to view.
P. Concealed Location Installations: Except as specified below, install concealed natural-gas piping and piping installed under the building in containment conduit constructed of steel pipe with welded joints as described in Part 2. Install a vent pipe from containment conduit to outdoors and terminate with weatherproof vent cap.
1. Above Accessible Ceilings: Natural-gas piping, fittings, valves, and regulators may be installed in accessible spaces without containment conduit.
2. In Floors: Install natural-gas piping with welded or brazed joints and protective coating in cast-in-place concrete floors. Cover piping to be cast in concrete slabs with minimum of 1-1/2 inches (38 mm) of concrete. Piping may not be in physical contact with other metallic structures such as reinforcing rods or electrically neutral conductors. Do not embed piping in concrete slabs containing quick-set additives or cinder aggregate.
3. In Floor Channels: Install natural-gas piping in floor channels. Channels must have cover and be open to space above cover for ventilation.
4. In Walls or Partitions: Protect tubing installed inside partitions or hollow walls from physical damage using steel striker barriers at rigid supports. a. Exception: Tubing passing through partitions or walls does not require striker barriers.
5. Prohibited Locations:
a. Do not install natural-gas piping in or through circulating air ducts, clothes or trash chutes, chimneys or gas vents (flues), ventilating ducts, or dumbwaiter or elevator shafts.
b. Do not install natural-gas piping in solid walls or partitions.
Q. Use eccentric reducer fittings to make reductions in pipe sizes. Install fittings with level side down.
R. Connect branch piping from top or side of horizontal piping.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 16
S. Install unions in pipes NPS 2 (DN 50) and smaller, adjacent to each valve, at final connection to each piece of equipment. Unions are not required at flanged connections.
T. Do not use natural-gas piping as grounding electrode.
U. Install strainer on inlet of each line-pressure regulator and automatic or electrically operated valve.
V. Install pressure gauge downstream from each line regulator.
W. Install sleeves for piping penetrations of walls, ceilings, and floors.
X. Install sleeve seals for piping penetrations of concrete walls and slabs.
Y. Install escutcheons for piping penetrations of walls, ceilings, and floors.
3.5 INSTALLATION OF SERVICE-METER ASSEMBLIES
A. Install service-meter assemblies aboveground.
B. Install metal shutoff valves upstream from service regulators. Shutoff valves are not required at second regulators if two regulators are installed in series.
C. Install strainer on inlet of service-pressure regulator and meter set.
D. Install service regulators mounted outside with vent outlet horizontal or facing down. Install screen in vent outlet if not integral with service regulator.
E. Install metal shutoff valves upstream from service meters. Install dielectric fittings downstream from service meters.
F. Install service meters downstream from pressure regulators.
G. Install metal bollards to protect meter assemblies. Comply with requirements in Section 055000 "Metal Fabrications" for pipe bollards.
3.6 INSTALLATION OF VALVES
A. Install manual gas shutoff valve for each gas appliance ahead of corrugated stainless steel tubing, aluminum, or copper connector.
B. Install underground valves with valve boxes.
C. Install regulators and overpressure protection devices with maintenance access space adequate for servicing and testing.
D. Install earthquake valves aboveground outside buildings according to listing.
E. Install anode for metallic valves in underground PE piping.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 17
F. Do not install valves in return-air plenums.
3.7 PIPING JOINT CONSTRUCTION
A. Ream ends of pipes and tubes and remove burrs.
B. Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before assembly.
C. Threaded Joints:
1. Thread pipe with tapered pipe threads complying with ASME B1.20.1.
2. Cut threads full and clean using sharp dies.
3. Ream threaded pipe ends to remove burrs and restore full inside diameter of pipe.
4. Apply appropriate tape or thread compound to external pipe threads unless dryseal threading is specified.
5. Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or damaged. Do not use pipe sections that have cracked or open welds.
D. Welded Joints:
1. Construct joints in accordance with AWS D10.12/D10.12M, using qualified processes and welding operators.
2. Bevel plain ends of steel pipe.
3. Patch factory-applied protective coating as recommended by manufacturer at field welds and where damage to coating occurs during construction.
E. Brazed Joints: Construct joints in accordance with AWS's "Brazing Handbook," "Pipe and Tube" Chapter.
F. Flanged Joints: Install gasket material, size, type, and thickness appropriate for natural-gas service. Install gasket concentrically positioned.
G. Flared Joints: Cut tubing with roll cutting tool. Flare tube end with tool to result in flare dimensions complying with SAE J513. Tighten finger tight, and then use wrench. Do not overtighten.
H. PE Piping Heat-Fusion Joints: Clean and dry joining surfaces by wiping with clean cloth or paper towels. Join in accordance with ASTM D2657.
1. Plain-End Pipe and Fittings: Use butt fusion.
2. Plain-End Pipe and Socket Fittings: Use socket fusion.
3.8 INSTALLATION OF HANGERS AND SUPPORTS
A. Comply with requirements for seismic-restraint devices specified in Section 230548 "Vibration and Seismic Controls for HVAC."
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 18
B. Comply with requirements in Section 230529 "Hangers and Supports for HVAC Piping and Equipment" for hangers, supports, and anchor devices.
C. Install hangers for steel piping, with maximum horizontal spacing and minimum rod diameters, to comply with MSS SP-58, locally enforced codes, and authorities having jurisdiction requirements, whichever are most stringent.
D. Install hangers for corrugated stainless steel tubing, with maximum horizontal spacing and minimum rod diameters, to comply with manufacturer's written instructions, locally enforced codes, and authorities having jurisdiction requirements, whichever are most stringent.
E. Support horizontal piping within 12 inches (300 mm) of each fitting.
F. Support vertical runs of steel piping to comply with MSS SP-58, locally enforced codes, and authorities having jurisdiction requirements, whichever are most stringent.
G. Support vertical runs of corrugated stainless steel tubing to comply with manufacturer's written instructions, locally enforced codes, and authorities having jurisdiction requirements, whichever are most stringent.
3.9 PIPING CONNECTIONS
A. Connect to utility's gas main according to utility's procedures and requirements.
B. Install natural-gas piping electrically continuous, and bonded to gas-appliance equipment grounding conductor of the circuit powering the appliance in accordance with NFPA 70.
C. Where installing piping adjacent to appliances, allow space for service and maintenance of appliances.
D. Connect piping to appliances using manual gas shutoff valves and unions. Install valve within 72 inches (1800 mm) of each gas-fired appliance and equipment. Install union between valve and appliances or equipment.
3.10 LABELING AND IDENTIFICATION
A. Comply with requirements in Section 230553 "Identification for HVAC Piping and Equipment" for piping and valve identification.
B. Install detectable warning tape directly above gas piping, 12 inches (300 mm) below finished grade, except 6 inches (150 mm) below subgrade under pavements and slabs.
3.11 CONCRETE BASES
A. Concrete Bases: Anchor equipment to concrete base in accordance with seismic codes at Project. See Section 230548 "Vibration and Seismic Controls for HVAC."
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 19
1. Construct concrete bases of dimensions indicated, but not less than 4 inches (100 mm) larger in both directions than supported unit.
2. Install dowel rods to connect concrete base to concrete floor. Unless otherwise indicated, install dowel rods on 18-inch (450-mm) centers around the full perimeter of the base.
3. Install epoxy-coated anchor bolts for supported equipment that extend through concrete base, and anchor into structural concrete floor.
4. Place and secure anchorage devices. Use supported equipment manufacturer's setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded.
5. Install anchor bolts to elevations required for proper attachment to supported equipment.
6. Use 3000 psig (20.7 MPa), 28-day, compressive-strength concrete and reinforcement as specified in Section 033000 "Cast-in-Place Concrete."
3.12 FIELD QUALITY CONTROL
A. Tests and Inspections:
1. Test, inspect, and purge natural gas in accordance with NFPA 54 and authorities having jurisdiction.
2. Natural-gas piping will be considered defective if it does not pass tests and inspections.
B. Prepare test and inspection reports.
3.13 DEMONSTRATION
A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain earthquake valves.
3.14 OUTDOOR PIPING SCHEDULE
A. Underground natural-gas piping is to be the following:
1. PE pipe and fittings joined by heat fusion, or mechanical couplings; service-line risers with tracer wire terminated in an accessible location.
B. Aboveground natural-gas piping is to be the following:
1. Steel pipe with malleable-iron fittings and threaded joints.
3.15 INDOOR PIPING SCHEDULE FOR SYSTEM PRESSURES LESS THAN 0.5 PSIG (3.45 kPa)
A. Aboveground, branch piping NPS 1 (DN 25) and smaller is to be one of the following:
1. Corrugated stainless steel tubing with mechanical fittings having socket or threaded ends to match adjacent piping.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 20
2. Steel pipe with malleable-iron fittings and threaded joints.
B. Aboveground, distribution piping is to be the following:
1. Steel pipe with malleable-iron fittings and threaded joints.
3.16 INDOOR PIPING SCHEDULE FOR SYSTEM PRESSURES MORE THAN 0.5 PSIG (3.45 kPa) AND LESS THAN 5 PSIG (34.5 kPa)
A. Aboveground, branch piping NPS 1 (DN 25) and smaller is to be one of the following:
1. Corrugated stainless steel tubing with mechanical fittings having socket or threaded ends to match adjacent piping.
2. Steel pipe with malleable-iron fittings and threaded joints.
B. Aboveground, distribution piping is to be the following:
1. Steel pipe with malleable-iron fittings and threaded joints.
3.17 INDOOR PIPING SCHEDULE FOR SYSTEM PRESSURES MORE THAN 5 PSIG (34.5 kPa)
A. Aboveground Piping: Maximum operating pressure more than 5 psig (34.5 kPa).
B. Aboveground, Branch Piping: Steel pipe with steel welding fittings and welded joints.
C. Aboveground, distribution piping is to be the following:
1. Steel pipe with steel welding fittings and welded joints.
3.18 ABOVEGROUND, MANUAL GAS SHUTOFF VALVE SCHEDULE
A. Valves for pipe sizes NPS 2 (DN 50) and smaller at service meter are to be one of the following:
1. One-piece, bronze ball valve with bronze trim.
2. Two-piece, full-port, bronze ball valves with bronze trim.
3. Bronze plug valve.
B. Valves for pipe sizes NPS 2-1/2 (DN 65) and larger at service meter are to be one of the following:
1. Two-piece, full-port, bronze ball valves with bronze trim.
2. Bronze plug valve.
3. Cast-iron, nonlubricated plug valve.
C. Distribution piping valves for pipe sizes NPS 2 (DN 50) and smaller are to be one of the following:
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY NATURAL-GAS PIPING 231123 - 21
1. One-piece, bronze ball valve with bronze trim.
2. Two-piece, full-port, bronze ball valves with bronze trim.
3. Bronze plug valve.
D. Distribution piping valves for pipe sizes NPS 2-1/2 (DN 65) and larger are to be one of the following:
1. Two-piece, full-port, bronze ball valves with bronze trim.
2. Bronze plug valve.
3. Cast-iron, nonlubricated plug valve.
E. Valves in branch piping for single appliance are to be one of the following:
1. One-piece, bronze ball valve with bronze trim.
2. Two-piece, full-port, bronze ball valves with bronze trim.
3. Bronze plug valve.
END OF SECTION 231123
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY LIQUEFIED-PETROLEUM GAS PIPING 231126 - 1
SECTION 231126
FACILITY LIQUEFIED-PETROLEUM GAS PIPING
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Steel pipe and fittings.
2. CSST and fittings.
3. Mechanical couplings.
4. Piping specialties.
5. Manual gas shutoff valves.
6. Earthquake valves.
7. Pressure regulators.
8. Dielectric fittings.
9. Storage containers.
1.2 DEFINITIONS
A. CSST: Corrugated stainless steel tubing.
B. CWP: Cold working pressure.
C. Exposed, Exterior Installations: Exposed to view outdoors or subject to outdoor ambient temperatures and weather conditions. Examples include rooftop locations.
D. Exposed, Interior Installations: Exposed to view indoors. Examples include finished occupied spaces and mechanical equipment rooms.
E. Finished Spaces: Spaces other than mechanical and electrical equipment rooms, furred spaces, pipe and duct shafts, unheated spaces immediately below roof, spaces above ceilings, unexcavated spaces, crawlspaces, and tunnels.
F. LPG: Liquefied-petroleum gas.
G. PE: Polyethylene.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of the following:
1. Piping specialties.
2. CSST with associated components.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY LIQUEFIED-PETROLEUM GAS PIPING 231126 - 2
3. Valves: Include pressure rating, capacity, settings, and electrical connection data of selected models.
4. Pressure Regulators: Indicate pressure ratings and capacities.
5. Service Meters: Indicate pressure ratings and capacities. Include bypass fittings, meter bars, and supports.
6. Dielectric fittings.
7. Storage containers.
B. Shop Drawings: Provide plans, piping layout and elevations, sections, and details for fabrication of pipe anchors, hangers, supports for multiple pipes, alignment guides, expansion joints and loops, and attachments of the same to building structure. Detail location of anchors, alignment guides, and expansion joints and loops.
1. Shop Drawings Scale: 1/4 inch per foot (1:50).
2. Detail mounting, supports, and valve arrangements for pressure regulator assembly.
C. Delegated Design Submittals: Comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
1. Detail fabrication and assembly of seismic restraints.
2. Design Calculations: Calculate requirements for selecting seismic restraints.
1.4 INFORMATIONAL SUBMITTALS
A. Coordination Drawings: Plans and details, drawn to scale, on which LPG piping is indicated and coordinated with other installations, using input from installers of the items involved.
B. Site Survey: Plans, drawn to scale, on which LPG piping is shown and coordinated with other services and utilities.
C. Seismic Qualification Data: Submit certification that vaporizer, air mixer, storage container supports, accessories, and components will withstand seismic forces defined in Section 230548 "Vibration and Seismic Controls for HVAC." Include the following:
1. Basis for Certification: Indicate whether withstand certification is based on actual test of assembled components or on calculation.
2. Dimensioned Outline Drawings of Equipment Unit: Identify center of gravity and locate and describe mounting and anchorage provisions.
3. Detailed description of equipment anchorage devices on which the certification is based and their installation requirements.
D. Welding certificates.
E. Field quality-control reports.
F. Qualification Statements: For professional engineer.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY LIQUEFIED-PETROLEUM GAS PIPING 231126 - 3
1.5 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For LPG equipment and accessories.
1.6 QUALITY ASSURANCE
A. Steel Support Welding Qualifications: Qualify procedures and personnel in accordance with AWS D1.1/D1.1M, "Structural Welding Code - Steel."
B. Pipe Welding Qualifications: Qualify procedures and operators in accordance with ASME BVPC.
1.7 DELIVERY, STORAGE, AND HANDLING
A. Handling Flammable Liquids: Remove and dispose of liquids from existing LPG piping according to requirements of authorities having jurisdiction.
B. Deliver pipes and tubes with factory-applied end caps. Maintain end caps through shipping, storage, and handling to prevent pipe end damage and to prevent entrance of dirt, debris, and moisture.
C. Store pipes and tubes with protective PE coating to avoid damaging coating and protect from direct sunlight.
D. Protect stored PE pipes, tubing, and valves from direct sunlight.
1.8 PROJECT CONDITIONS
A. Perform site survey, research public utility records, and verify existing utility locations. Contact utility-locating service for area where Project is located.
1.9 COORDINATION
A. Coordinate sizes and locations of concrete bases with actual equipment provided.
PART 2 - PRODUCTS
2.1 SOURCE LIMITATIONS
A. Obtain each product type from single source from single manufacturer.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY LIQUEFIED-PETROLEUM GAS PIPING 231126 - 4
2.2 PERFORMANCE REQUIREMENTS
A. Comply with requirements of NFPA 58 and NFPA 54 for LPG distribution system, including materials, installation, and testing.
B. Comply with requirements of authorities having jurisdiction.
C. Comply with requirements of utility company supplying LPG.
D. Minimum Operating-Pressure Ratings:
1. Minimum Operating Pressure for Piping and Valves: 125 psig (862 kPa) unless otherwise indicated.
E. LPG System Pressure within Buildings:
1. System Pressure within Buildings, Two Pressure Ranges, Not More Than 5 psig (34.5 kPa): Primary pressure is more than 2 psig (13.8 kPa) but not more than 5 psig (34.5 kPa) and is reduced to secondary pressure of more than 0.5 psig (3.45 kPa) but not more than 2 psig (13.8 kPa).
F. Delegated Design: Design restraints and anchors for LPG piping and equipment, including comprehensive engineering analysis by a qualified professional engineer, using performance requirements and design criteria indicated.
G. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.
H. Seismic Performance: Vaporizers and storage container supports are to withstand the effects of earthquake motions determined in accordance with ASCE/SEI 7. See Section 230548 "Vibration and Seismic Controls for HVAC Piping and Equipment."
1. The term "withstand" means "the piping/unit will remain in place without separation of any parts from the device when subjected to the seismic forces specified and the piping system will be fully operational after the seismic event."
2. Component Importance Factor: 1.5.
2.3 PIPE, TUBING, AND FITTINGS
A. Steel Pipe and Fittings:
1. Steel Pipe: ASTM A53/A53M black steel, Schedules 40 and 80, Type E or S, Grade B.
2. Malleable-Iron Threaded Fittings: ASME B16.3, Class 150, standard pattern.
3. Wrought-Steel Welding Fittings: ASTM A234/A234M for butt welding and socket welding.
4. Unions: ASME B16.39, Class 150, malleable iron with brass-to-iron seat, ground joint, and threaded ends.
5. Forged-Steel Flanges and Flanged Fittings: ASME B16.5, minimum Class 150, including bolts, nuts, and gaskets of the following material group, end connections, and facings:
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY LIQUEFIED-PETROLEUM GAS PIPING 231126 - 5
a. Material Group: 1.1.
b. End Connections: Threaded or butt welding to match pipe. c. Lapped Face: Not permitted underground.
d. Gasket Materials: ASME B16.20, metallic, flat, asbestos free, aluminum o-rings, and spiral-wound metal gaskets.
e. Bolts and Nuts: ASME B18.2.1, carbon steel aboveground, and stainless steel underground.
6. Protective Coating for Underground Piping: Factory-applied, three-layer coating of epoxy, adhesive, and PE.
a. Joint Cover Kits: Epoxy paint, adhesive, and heat-shrink PE sleeves.
B. CSST and Fittings:
1. CSST:
a. Standard: ANSI LC 1/CSA 6.26.
b. Tubing: ASTM A240/A240M, corrugated, Series 300 stainless steel. c. Jacket - Electrically Insulative and UV-Resistant Polymer with Flame Retardant:
1) Surface-Burning Characteristics: As determined by testing identical products in accordance with ASTM E84 by a qualified testing agency.
Identify products with appropriate markings of applicable testing agency. a) Flame-Spread Index: 25 or less.
b) Smoke-Developed Index: 50 or less.
d. Jacket - with Fully Vent-Capable PE Sleeve: Include associated fittings suitable for locations requiring vented containment.
2. Fittings: Copper-alloy mechanical fittings with ends made to fit and listed for use with CSST and suitable for metal-to-metal seal without gaskets. Include brazing socket or threaded ends complying with ASME B1.20.1.
3. Striker Plates: Steel, designed to protect tubing from penetrations.
4. Manifolds: Malleable iron or steel with factory-applied protective coating. Threaded connections are to comply with ASME B1.20.1 for pipe inlet and corrugated tubing outlets.
5. Operating-Pressure Rating: 25 psig (172 kPa).
2.4 MECHANICAL COUPLINGS
A. Mechanical Couplings - Steel:
1. Stainless steel flanges and tube with epoxy finish.
2. Buna-nitrile seals.
3. Stainless steel bolts, washers, and nuts.
4. Factory-installed anode for steel-body couplings installed underground.
5. Couplings are to be suitable for joining plain-end PE pipe to PE pipe, steel pipe to PE pipe, or steel pipe to steel pipe.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY LIQUEFIED-PETROLEUM GAS PIPING 231126 - 6
2.5 PIPING SPECIALTIES
A. Flexible Piping Joints:
1. Approved for LPG service.
2. Stainless steel bellows with woven, flexible, bronze, wire-reinforcing protective jacket.
3. Minimum working pressure of 250 psig (1723 kPa) and 250 deg F (121 deg C) operating temperature.
4. Flanged- or threaded-end connections to match equipment connected and to be capable of minimum 3/4-inch (20-mm) misalignment.
5. Maximum 36-inch (914-mm) length for liquid LPG lines.
B. Appliance Flexible Connectors:
1. Indoor, Fixed-Appliance Flexible Connectors: ANSI Z21.24.
2. Indoor, Movable-Appliance Flexible Connectors: ANSI Z21.69.
3. Outdoor, Appliance Flexible Connectors: ANSI Z21.75.
4. CSST with polymer coating.
5. Operating-Pressure Rating: 0.5 psig (3.45 kPa).
6. End Fittings: Zinc-coated steel.
7. Threaded Ends: ASME B1.20.1.
8. Maximum Length: 72 inches (1830 mm).
C. Quick-Disconnect Devices:
1. Standard: ANSI Z21.41/CSA 6.9.
2. Copper-alloy convenience outlet and matching plug connector.
3. Nitrile seals.
4. Hand operated with automatic shutoff when disconnected.
5. For indoor or outdoor applications.
6. Adjustable, retractable restraining cable.
D. Y-Pattern Strainers:
1. Body: ASTM A126, Class B, cast iron with bolted cover and bottom drain connection.
2. End Connections: Threaded ends for NPS 2 (DN 50) and smaller; flanged ends for NPS 2-1/2 (DN 65) and larger.
3. Strainer Screen: 40-mesh startup strainer and perforated stainless steel basket with 50 percent free area.
4. CWP Rating: 125 psig (862 kPa).
E. Weatherproof Vent Cap: Cast- or malleable-iron increaser fitting with corrosion-resistant wire screen, with free area at least equal to cross-sectional area of connecting pipe and threaded-end connection.
2.6 JOINING MATERIALS
A. Joint Compound and Tape: Suitable for LPG.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY LIQUEFIED-PETROLEUM GAS PIPING 231126 - 7
B. Welding Filler Metals: AWS D10.12/D10.12M.
2.7 MANUAL GAS SHUTOFF VALVES
A. Manual Gas Shutoff Valves - Metallic:
1. Description: Metallic ball valve or metallic plug valve of type indicated in schedules under Part 3.
2. Standards:
a. ANSI Z21.15/CSA 9.1.
b. ASME B16.33.
c. ANSI LC 4/CSA 6.32.
3. End Connections:
a. Threaded Ends: ASME B1.20.1.
b. Dryseal Threads on Flare Ends: ASME B1.20.3.
c. Flanged Ends: ASME B16.5 for steel flanges.
4. Tamperproof locking feature.
2.8 EARTHQUAKE VALVES
A. Description: Seismically activated automatic gas shutoff valve.
B. Standard: ASCE/SEI 25.
C. Maximum Operating Pressure: 60 psig (414 kPa).
D. Sight windows for visual indication of valve position.
E. Threaded complying with ASME B1.20.1.
F. Threaded for valves NPS 4 (DN 100) and smaller; or flanged for valves NPS 2 (DN 50) and larger.
2.9 PRESSURE REGULATORS
A. Service Pressure Regulators:
1. Standards:
a. NFPA 58.
b. ANSI Z21.80/CSA 6.22.
2. Single-port, self-contained regulator with orifice no larger than required at maximum pressure inlet and no pressure-sensing piping external to the regulator.
3. Pressure regulator is to maintain discharge pressure-setting downstream and is not to exceed 150 percent of design discharge pressure at shutoff.
4. Maximum Inlet Pressure: 100 psig (690 kPa).
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY LIQUEFIED-PETROLEUM GAS PIPING 231126 - 8
5. Maximum Outlet Pressure: 5 psig (34.5 kPa).
6. End Connections: Threaded for regulators NPS 2 (DN 50) and smaller; flanged for regulators NPS 2-1/2 (DN 65) and larger.
7. Overpressure Protection Device: Factory mounted on pressure regulator.
8. Atmospheric Vent: Factory- or field-installed, stainless steel screen in opening if not connected to vent piping.
B. Line-Pressure Regulators:
1. Standards:
a. NFPA 58.
b. ANSI Z21.80/CSA 6.22.
2. Single-port, self-contained regulator with orifice no larger than required at maximum pressure inlet and no pressure-sensing piping external to the regulator.
3. Pressure regulator is to maintain discharge pressure-setting downstream and is not exceed 150 percent of design discharge pressure at shutoff.
4. Maximum Inlet Pressure: 5 psig (34.5 kPa).
5. Maximum Outlet Pressure: 2 psig (13.8 kPa).
6. End Connections: Threaded for regulators NPS 2 (DN 50) and smaller; flanged for regulators NPS 2-1/2 (DN 65) and larger.
7. Overpressure Protection Device: Factory mounted on pressure regulator.
8. Atmospheric Vent: Factory- or field-installed, stainless steel screen in opening if not connected to vent piping.
C. Appliance Pressure Regulators:
1. Standards:
a. NFPA 58.
b. ANSI Z21.18/CSA 6.3.
2. Regulator may include vent-limiting device, instead of vent connection, if approved by authorities having jurisdiction.
3. Maximum Inlet Pressure: 5 psig (34.5 kPa).
4. Maximum Outlet Pressure: 0.5 psig.
5. End Connections: Threaded for regulators NPS 2 (DN 50) and smaller; flanged for regulators NPS 2-1/2 (DN 65) and larger.
2.10 DIELECTRIC FITTINGS
A. Assembly of copper alloy and ferrous materials with separating nonconductive insulating material. Include end connections compatible with pipes to be joined.
B. Dielectric Unions:
1. Standard: ASSE 1079.
2. Pressure Rating: 150 psig (1035 kPa).
3. End Connections: Solder-joint copper alloy and threaded ferrous.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY LIQUEFIED-PETROLEUM GAS PIPING 231126 - 9
C. Dielectric Flanges:
1. Standard: ASSE 1079.
2. Factory-fabricated, bolted, companion-flange assembly.
3. Pressure Rating: 150 psig (1035 kPa).
4. End Connections: Solder-joint copper alloy and threaded ferrous; threaded copper alloy and threaded ferrous.
D. Dielectric-Flange Insulating Kits:
1. Nonconducting materials for field assembly of companion flanges.
2. Pressure Rating: 150 psig (1035 kPa).
3. Gasket: Neoprene or phenolic.
4. Bolt Sleeves: Phenolic or PE.
5. Washers: Phenolic with steel backing washers.
2.11 STORAGE CONTAINERS
A. Description: Factory-designed, -fabricated, and -tested containers.
B. Standards:
1. NFPA 58.
2. ASME BPVC-VIII-1.
3. UL 125.
4. UL 842.
5. Department of Transportation (DOT) Regulations.
C. Provide all appurtenances as required by NFPA 58, qualified to UL 125:
1. Vapor-shutoff valve.
2. Liquid-shutoff valve.
3. Pressure-relief valve.
4. Fixed maximum liquid level gauge.
5. Filler valve.
6. Overfilling protection device.
7. Actuated liquid withdrawal excess-flow valve.
8. Provide container appurtenances with a minimum service pressure rating of 250 psig (1724 kPa).
D. Provide exposed metal surfaces mechanically cleaned, primed, and painted for resistance to corrosion for outdoor installation.
E. Provide ladders for access to valves more than 72 inches (1830 mm) aboveground.
F. Stainless Steel Nameplate: Attach to aboveground storage container or to adjacent structure for underground storage container.
1. Name and address of supplier or trade name of container.
2. Water capacity in gallons and liters.
3. Design pressure in psig and kPa.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY LIQUEFIED-PETROLEUM GAS PIPING 231126 - 10
a. Outside surface area in square feet and square meters. b. Year of manufacture.
c. Shell thickness in inches and millimeters.
d. Overall length in feet and meters.
e. OD in feet and meters.
f. Manufacturer's serial number.
g. ASME code label.
4. Felt support pads and two concrete or painted-steel saddles per storage container.
Corrosion protection required at container-to-felt contact.
5. Tie straps for each saddle.
6. Straps and anchors for tie-down slab.
7. Asphalt-based coating for corrosion protection.
8. Container connections and valves protected in manway at top of storage container.
9. Manway equipped with ventilation louvers.
2.12 DETECTABLE WARNING TAPE
A. Acid- and alkali-resistant PE film warning tape manufactured for marking and identifying underground utilities, a minimum of 6 inches (150 mm) wide and 4 mils (0.1 mm) thick, continuously inscribed with a description of utility, with metallic core encased in a protective jacket for corrosion protection, detectable by metal detector when tape is buried up to 30 inches (750 mm) deep; colored yellow.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine roughing-in for LPG piping system to verify actual locations of piping connections before equipment installation.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 EARTHWORK
A. Comply with requirements in Section 312000 "Earth Moving" for excavating, trenching, and backfilling.
3.3 PREPARATION
A. Close equipment-shutoff valves before turning off LPG to premises or piping section.
B. Inspect LPG piping in accordance with code(s) and authority having jurisdiction to determine that LPG utilization devices are turned off in piping section affected.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY LIQUEFIED-PETROLEUM GAS PIPING 231126 - 11
C. Comply with requirements of code(s) and authority having jurisdiction for prevention of accidental ignition.
3.4 INSTALLATION OF OUTDOOR PIPING
A. Comply with code and authority having jurisdiction requirements for installation and purging of LPG piping.
B. Install underground, LPG piping buried a minimum of 12 inches (300 mm) below finished grade. Comply with requirements in Section 312000 "Earth Moving" for excavating, trenching, and backfilling.
C. Steel Piping with Protective Coating:
1. Apply joint cover kits to pipe after joining to cover, seal, and protect joints.
2. Replace pipe having damaged PE coating with new pipe.
D. Install fittings for changes in direction and branch connections.
E. Joints for connection to inlets and outlets on vaporizers, regulators, and valves may be flanged or threaded to match the equipment.
F. Install pressure gauge downstream from each service regulator.
3.5 INSTALLATION OF INDOOR PIPING
A. Comply with requirements of the code(s) and authority having jurisdiction for installation and purging of LPG piping.
B. Drawing plans, schematics, and diagrams indicate general location and arrangement of piping systems. Indicated locations and arrangements were used to size pipe and calculate friction loss, expansion, and other design considerations. Install piping as indicated unless deviations to layout are approved on coordination drawings.
C. Arrange for pipe spaces, chases, slots, sleeves, and openings in building structure during progress of construction.
D. Install piping in concealed locations unless otherwise indicated. Piping in equipment rooms and service areas may be installed exposed. Piping is not to be installed in inaccessible locations.
1. Conceal piping in walls, pipe spaces, utility spaces, above ceilings, below grade or floors, and in floor channels unless indicated to be exposed to view.
2. Except as specified below, install concealed piping and piping installed under the building in containment conduit constructed of steel pipe with welded joints, as described in Part 2. Install a vent pipe from containment conduit to outdoors and terminate with weatherproof vent cap.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY LIQUEFIED-PETROLEUM GAS PIPING 231126 - 12
a. Above Accessible Ceilings: Piping, fittings, valves, and regulators may be installed in accessible spaces without containment conduit.
1) Install piping above accessible ceilings to allow sufficient space for ceiling panel removal.
b. In Floors: Install piping with welded or brazed joints and protective coating in cast-in-place concrete floors. Cover piping to be cast in concrete slabs with minimum of 1-1/2 inches (38 mm) of concrete. Piping may not be in physical contact with other metallic structures, such as reinforcing rods or electrically neutral conductors. Do not embed piping in concrete slabs containing quick-set additives or cinder aggregate.
c. In Floor Channels: Channels must have cover and be open to space above cover for ventilation.
d. In Walls or Partitions: Protect piping installed inside partitions or hollow walls from physical damage using steel striker barriers at rigid supports. 1) Exception: Piping passing through partitions or walls does not require striker barriers.
e. Prohibited Locations:
1) Do not install piping in or through circulating air ducts, clothes or trash chutes, chimneys or gas vents (flues), ventilating ducts, or dumbwaiter or elevator shafts.
2) Do not install piping in return-air plenums.
3) Do not install piping in solid walls or partitions.
E. Install piping indicated to be exposed and piping in equipment rooms and service areas at right angles or parallel to building walls. Diagonal runs are prohibited unless specifically indicated otherwise.
F. Locate valves for easy access from a standing position.
G. Install LPG piping at uniform grade of 2 percent down toward drip and sediment traps.
H. Install piping free of sags and bends.
I. Install fittings for changes in direction and branch connections.
J. Comply with requirements in Sections specifying gas-fired appliances and equipment, and verify final appliance and equipment locations for roughing-in.
K. Drips and Sediment Traps: Install drips at points where condensate may collect, including service-meter outlets. Locate where readily accessible to permit cleaning and emptying. Do not install where condensate is subject to freezing.
1. Construct drips and sediment traps using tee fitting with bottom outlet plugged or capped.
Use nipple a minimum length of three pipe diameters, but not less than 3 inches (75 mm)
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY LIQUEFIED-PETROLEUM GAS PIPING 231126 - 13
long and same size as connected pipe. Install with space below bottom of drip to remove plug or cap.
L. Extend relief vent connections for service regulators, line regulators, and overpressure protection devices to outdoors, and terminate with weatherproof vent cap.
M. Use eccentric reducer fittings to make reductions in pipe sizes. Install fittings with level side down.
N. Connect branch piping from top or side of horizontal piping.
O. Install unions in pipes NPS 2 (DN 50) and smaller, adjacent to each valve, at final connection to each piece of equipment. Unions are not required at flanged connections.
P. Do not use LPG piping as grounding electrode.
Q. Install strainer on inlet of each line-pressure regulator and automatic or electrically operated valve.
R. Install pressure gauge downstream from each line regulator.
S. Install sleeves for piping penetrations of walls, ceilings, and floors.
T. Install sleeve seals for piping penetrations of concrete walls and slabs.
U. Install escutcheons for piping penetrations of walls, ceilings, and floors.
3.6 INSTALLATION OF VALVES
A. Install manual gas shutoff valve for each gas appliance ahead of CSST, aluminum, or copper connector.
B. Install underground valves with valve boxes.
C. Install regulators and overpressure protection devices with maintenance access space adequate for servicing and testing.
D. Install earthquake valves aboveground outside buildings according to listing.
E. Install anode for metallic valves in underground PE piping.
F. Do not install valves in return-air plenums.
3.7 PIPING JOINT CONSTRUCTION
A. Ream ends of pipes and tubes and remove burrs.
B. Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before assembly.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY LIQUEFIED-PETROLEUM GAS PIPING 231126 - 14
C. Threaded Joints:
1. Thread pipe with tapered pipe threads complying with ASME B1.20.1.
2. Cut threads full and clean using sharp dies.
3. Ream threaded pipe ends to remove burrs and restore full ID of pipe.
4. Apply appropriate tape or thread compound to external pipe threads unless dryseal threading is specified.
5. Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or damaged. Do not use pipe sections that have cracked or open welds.
D. Welded Joints:
1. Construct joints in accordance with AWS D10.12/D10.12M, using qualified processes and welding operators.
2. Bevel plain ends of steel pipe.
3. Patch factory-applied protective coating as recommended by manufacturer at field welds and where damage to coating occurs during construction.
E. Flanged Joints: Install gasket material, size, type, and thickness appropriate for LPG service.
Install gasket concentrically positioned.
F. PE Piping Heat-Fusion Joints: Clean and dry joining surfaces by wiping with clean cloth or paper towels. Join in accordance with ASTM D2657.
1. Plain-End Pipe and Fittings: Use butt fusion.
2. Plain-End Pipe and Socket Fittings: Use socket fusion.
3.8 PIPING CONNECTIONS
A. Connect to utility's gas main according to utility's procedures and requirements.
B. Install LPG piping electrically continuous and bonded to gas appliance equipment grounding conductor of the circuit powering the appliance in accordance with NFPA 70.
C. Install piping adjacent to appliances to allow service and maintenance of appliances.
D. Connect piping to appliances using manual gas-shutoff valves and unions. Install valve within 72 inches (1830 mm) of each gas-fired appliances and equipment. Install union between valve and appliances or equipment.
3.9 INSTALLATION OF STORAGE CONTAINER
A. Do not install storage containers in a pit.
B. Fill storage container to at least 80 percent capacity with propane.
C. Install piping connections with swing joints or flexible connectors to allow for storage container settlement and for thermal expansion and contraction.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY LIQUEFIED-PETROLEUM GAS PIPING 231126 - 15
D. Ground containers in accordance with NFPA 780. Grounding is specified in Section 264113 "Lightning Protection for Structures."
E. Install tie-downs over storage containers on saddles with proper tension.
F. Set concrete saddles on dowels set in concrete base. Anchor steel saddles to concrete base.
3.10 INSTALLATION OF LABELING AND IDENTIFICATION
A. Comply with requirements in Section 230553 "Identification for HVAC Piping and Equipment" for piping and valve identification.
B. Install detectable warning tape directly above gas piping, 12 inches (305 mm) below finished grade, except 6 inches (150 mm) below subgrade under pavements and slabs.
C. Label and identify gas piping and pressure outside a multitenant building by tenant.
3.11 FIELD QUALITY CONTROL
A. Tests and Inspections:
1. Comply with requirements of the code(s) and authority having jurisdiction for testing, inspection, and purging of LPG installation.
B. LPG installation will be considered defective if it does not pass tests and inspections. Defective products are to be replaced.
C. Prepare test and inspection reports.
3.12 DEMONSTRATION
A. Train Owner's maintenance personnel to adjust, operate, and maintain LPG equipment.
3.13 OUTDOOR PIPING SCHEDULE
A. Underground piping is to be one of the following:
1. PE pipe, tubing, and fittings joined by heat-fusion, or mechanical couplings; service-line risers with tracer wire terminated in an accessible location.
B. Aboveground piping is to be one of the following:
1. Schedule 40, steel pipe with malleable-iron fittings and threaded joints.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
FACILITY LIQUEFIED-PETROLEUM GAS PIPING 231126 - 16
3.14 INDOOR PIPING SCHEDULE FOR SYSTEM PRESSURES LESS THAN 0.5 PSIG (3.45 kPa)
A. Aboveground piping is to be one of the following:
1. CSST and fittings.
2. Schedule 40, steel pipe with malleable-iron fittings and threaded joints.
3.15 INDOOR PIPING SCHEDULE FOR SYSTEM PRESSURES MORE THAN 0.5 PSIG (3.45 kPa) AND LESS THAN 5 PSIG (34.5 kPa)
A. Aboveground piping is to be one of the following:
1. CSST and fittings.
2. Schedule 40, steel pipe with malleable-iron fittings and threaded joints.
3.16 ABOVEGROUND MANUAL GAS SHUTOFF VALVE SCHEDULE
A. Valves for pipe NPS 2 (DN 50) and smaller is to be the following:
1. One-piece, bronze ball valve with bronze trim.
2. Two-piece, full-port, bronze ball valves with bronze trim.
3. Bronze plug valve.
B. Valves for pipe NPS 2-1/2 (DN 65) and larger is to be the following:
1. Two-piece, full-port, bronze ball valves with bronze trim.
2. Bronze plug valve.
3. Cast-iron, nonlubricated plug valve.
END OF SECTION 231126
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 1 SECTION 260519
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Copper building wire.
2. Connectors and splices.
B. Related Requirements:
1. Section 271513 "Communications Copper Horizontal Cabling" for twisted pair cabling used for data circuits.
1.2 ACTION SUBMITTALS
A. Product Data:
1. Copper building wire.
2. Connectors and splices.
B. Product Schedule: CU, THWN, Indoor and Outdoor, underground pull boxes, electrical equipment (lights, receptacles, panels, and switches).
1.3 INFORMATIONAL SUBMITTALS
A. Field quality-control reports.
PART 2 - PRODUCTS
2.1 COPPER BUILDING WIRE
A. Description: Flexible, insulated and uninsulated, drawn copper current-carrying conductor with an overall insulation layer or jacket, or both, rated 600 V or less.
B. Manufacturers:
1. Southwire.
2. International Wire Group, Inc.
3. New England Wire Technologies Corp.
4. Or approved equal.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 2 C. Standards:
1. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use.
2. Conductor and Cable Marking: Comply with wire and cable marking according to UL's "Wire and Cable Marking and Application Guide."
D. Conductors: Copper, complying with ASTM B3 for bare annealed copper and with ASTM B496 for stranded conductors.
E. Conductor Insulation:
1. Type THHN and Type THWN-2. Comply with UL 83.
2.2 CONNECTORS AND SPLICES
A. Description: Factory-fabricated connectors, splices, and lugs of size, ampacity rating, material, type, and class for application and service indicated; listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use.
B. Manufacturers:
1. Dottie.
2. Ideal.
3. 3M.
4. NSI.
5. Or approved equal.
PART 3 - EXECUTION
3.1 CONDUCTOR MATERIAL APPLICATIONS
A. Feeders:
1. Copper; solid for No. 12 AWG and smaller; stranded for No. 10 AWG and larger.
B. Branch Circuits:
1. Copper. Solid for No. 12 AWG and smaller; stranded for No. 10 AWG and larger.
3.2 CONDUCTOR INSULATION AND MULTICONDUCTOR CABLE APPLICATIONS AND
WIRING METHODS
A. Service Entrance: Type THHN/THWN-2, single conductors in raceway.
B. Feeders Concealed in Walls and Partitions: Type THHN/THWN-2.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 3 C. Feeders Concealed in Concrete, below Slabs-on-Grade, and Underground:
Type THHN/THWN-2, single conductors in raceway.
D. Branch Circuits Concealed in Walls, and Partitions: Type THHN/THWN-2, single conductors in raceway.
E. Branch Circuits Concealed in Concrete, below Slabs-on-Grade, and Underground:
Type THHN/THWN-2, single conductors in raceway.
3.3 INSTALLATION, GENERAL
A. Conceal cables in finished walls and floors unless otherwise indicated.
B. Complete raceway installation between conductor and cable termination points in accordance with Section 260533.13 "Conduits for Electrical Systems" prior to pulling conductors and cables.
C. Use manufacturer-approved pulling compound or lubricant where necessary; compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.
D. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will not damage cables or raceway.
E. Support cables according to Section 260529 "Hangers and Supports for Electrical Systems."
3.4 CONNECTIONS
A. Tighten electrical connectors and terminals according to manufacturer's published torquetightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A-486B.
B. Make splices, terminations, and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conductors.
C. Wiring at Outlets: Install conductor at each outlet, with at least 12 inch of slack.
3.5 IDENTIFICATION
A. Identify and color-code conductors and cables according to Section 260553 "Identification for Electrical Systems."
B. Identify each spare conductor at each end with identity number and location of other end of conductor, and identify as spare conductor.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 4
3.6 SLEEVE AND SLEEVE-SEAL INSTALLATION FOR ELECTRICAL PENETRATIONS A. Install sleeves and sleeve seals at penetrations of exterior floor and wall assemblies. Comply with requirements in Section 260544 "Sleeves and Sleeve Seals for Electrical Raceways and Cabling."
3.7 FIELD QUALITY CONTROL
A. Tests and Inspections:
1. After installing conductors and cables and before electrical circuitry has been energized, test service entrance and feeder conductors for compliance with requirements.
2. After installing conductors and cables and before electrical circuitry has been energized, test service entrance and feeder conductors and conductors feeding the following critical equipment and services for compliance with requirements:
3. Perform each of the following visual and electrical tests:
a. Inspect exposed sections of conductor and cable for physical damage and correct connection according to the single-line diagram.
b. Test bolted connections for high resistance using one of the following:
1) Calibrated torque wrench.
c. Inspect for correct identification.
d. Inspect cable jacket and condition.
e. Continuity test on each conductor and cable.
B. Cables will be considered defective if they do not pass tests and inspections.
C. Prepare test and inspection reports to record the following:
1. Procedures used.
2. Results that comply with requirements.
3. Results that do not comply with requirements, and corrective action taken to achieve compliance with requirements.
END OF SECTION 260519
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CONTROL-VOLTAGE ELECTRICAL POWER CABLES 260523 - 1
SECTION 260523
CONTROL-VOLTAGE ELECTRICAL POWER CABLES
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Category 6 balanced twisted pair cable.
2. RS-232 cable.
3. RS-485 cable.
4. Control cable.
5. Control-circuit conductors.
1.2 ACTION SUBMITTALS
A. Product Data:
1. Category 6 balanced twisted pair cable.
2. RS-232 cable.
3. RS-485 cable.
4. Control cable.
5. Control-circuit conductors.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
2.2 CATEGORY 6 BALANCED TWISTED PAIR CABLE
A. Description: Four-pair, balanced-twisted pair cable, with internal spline, certified to meet transmission characteristics of Category 6 cable at frequencies up to 250 MHz.
B. Manufacturers:
1. Ideal
2. DATACOM
3. Nexans
4. Or approved equal.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CONTROL-VOLTAGE ELECTRICAL POWER CABLES 260523 - 2
C. Standard: Comply with NEMA WC 66/ICEA S-116-732 and TIA-568-C.2 for Category 6 cables.
D. Conductors: 100 ohm, No. 23 AWG solid copper.
E. Shielding/Screening: Shielded twisted pairs (FTP.
F. Cable Rating: Riser and Plenum.
G. Jacket: Blue thermoplastic.
2.3 RS-232 CABLE
A. PVC-Jacketed, TIA 232-F:
1. Nine, No. 22 AWG, stranded (7x30) tinned copper conductors.
2. Polypropylene insulation.
3. Aluminum foil-polyester tape shield with 100 percent shield coverage.
4. PVC jacket.
5. Conductors are cabled on common axis with No. 24 AWG, stranded (7x32) tinned copper drain wire.
6. NFPA 70 Type: Type CM.
7. Flame Resistance: Comply with UL 1581.
B. Plenum-Type, TIA 232-F:
1. Nine, No. 22 AWG, stranded (7x30) tinned copper conductors.
2. PE insulation.
3. Aluminum foil-polyester tape shield with 100 percent shield coverage.
4. Fluorinated ethylene propylene jacket.
5. Conductors are cabled on common axis with No. 24 AWG, stranded (7x32) tinned copper drain wire.
6. Flame Resistance: Comply with NFPA 262.
2.4 RS-485 CABLE
A. Standard Cable: NFPA 70, Type CMG.
1. Paired, two pairs, twisted, No. 22 AWG, stranded (7x30) tinned-copper conductors.
2. PVC insulation.
3. Unshielded.
4. PVC jacket.
5. Flame Resistance: Comply with UL 1685.
B. Plenum-Rated Cable: NFPA 70, Type CMP.
1. Paired, two pairs, No. 22 AWG, stranded (7x30) tinned-copper conductors.
2. Fluorinated ethylene propylene insulation.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CONTROL-VOLTAGE ELECTRICAL POWER CABLES 260523 - 3
3. Unshielded.
4. Fluorinated ethylene propylene jacket.
5. Flame Resistance: NFPA 262.
2.5 CONTROL CABLE
A. Paired Cable: NFPA 70, Type CMG.
1. Multi-pair, twisted, No. 16 AWG, stranded (19x29) tinned-copper conductors.
2. PVC insulation.
3. Unshielded.
4. PVC jacket.
5. Flame Resistance: Comply with UL 1685.
B. Plenum-Rated, Paired Cable: NFPA 70, Type CMP.
1. Multi-pair, twisted, No. 16 AWG, stranded (19x29) tinned-copper conductors.
2. PVC insulation.
3. Unshielded.
4. PVC jacket.
5. Flame Resistance: Comply with NFPA 262.
2.6 CONTROL-CIRCUIT CONDUCTORS
A. Manufacturers:
1. Southwire.
2. Lutron
3. Coleman Cable
4. Or approved equal.
B. Class 2 Control Circuits: Stranded copper, Type THHN/THWN-2, complying with UL 83 in raceway.
C. Class 3 Remote-Control and Signal Circuits: Stranded copper, Type THHN/THWN-2, complying with UL 83 in raceway.
2.7 SOURCE QUALITY CONTROL
A. Testing Agency: Owner will engage a qualified testing agency to evaluate cables.
B. Cable will be considered defective if it does not pass tests and inspections.
C. Prepare test and inspection reports.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CONTROL-VOLTAGE ELECTRICAL POWER CABLES 260523 - 4
PART 3 - EXECUTION
3.1 EXAMINATION
A. Test cables on receipt at Project site.
1. Test each pair of twisted pair cable for open and short circuits.
3.2 INSTALLATION OF RACEWAYS AND BOXES
A. Comply with requirements in Section 260533.13 "Conduits for Electrical Systems" for raceway selection and installation requirements for conduits as supplemented or modified in this Section.
B. Comply with requirements in Section 260533.16 "Boxes and Covers for Electrical Systems" for raceway selection and installation requirements for boxes as supplemented or modified in this Section.
1. Outlet boxes must be no smaller than 2 inch wide, 3 inch high, and 2-1/2 inch deep.
2. Outlet boxes for cables must be no smaller than 4 inch square 2-1/8 inch deep with extension ring sized to bring edge of ring to within 1/8 inch of the finished wall surface.
C. Comply with TIA-569-D for pull-box sizing and length of conduit and number of bends between pull points.
D. Install manufactured conduit sweeps and long-radius elbows if possible.
3.3 INSTALLATION OF CONDUCTORS AND CABLES
A. Comply with NECA 1.
B. General Requirements for Cabling:
1. Comply with TIA-568-C Series of standards.
2. Comply with BICSI ITSIMM, Ch. 5, "Copper Structured Cabling Systems."
3. Terminate all conductors; cable must not contain unterminated elements. Make terminations only at indicated outlets, terminals, and cross-connect and patch panels.
4. Cables may not be spliced and must be continuous from terminal to terminal. Do not splice cable between termination, tap, or junction points.
5. Cables serving a common system may be grouped in a common raceway. Install network cabling and control wiring and cable in separate raceway from power wiring. Do not group conductors from different systems or different voltages.
6. Bundle, lace, and train conductors to terminal points without exceeding manufacturer's limitations on bending radii, but not less than radii specified in BICSI ITSIMM, Ch. 5, "Copper Structured Cabling Systems." Install lacing bars and distribution spools.
7. Do not install bruised, kinked, scored, deformed, or abraded cable. Remove and discard cable if damaged during installation and replace it with new cable.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CONTROL-VOLTAGE ELECTRICAL POWER CABLES 260523 - 5
8. Pulling Cable: Comply with BICSI ITSIMM, Ch. 5, "Copper Structured Cabling Systems." Monitor cable pull tensions.
9. Support: Do not allow cables to lie on removable ceiling tiles.
10. Secure: Fasten securely in place with hardware specifically designed and installed so as to not damage cables.
11. Provide strain relief.
12. Keep runs short. Allow extra length for connecting to terminals. Do not bend cables in a radius less than 10 times the cable OD. Use sleeves or grommets to protect cables from vibration at points where they pass around sharp corners and through penetrations.
13. Ground wire must be copper, and grounding methods must comply with IEEE C2.
Demonstrate ground resistance.
C. Installation of Control-Circuit Conductors:
1. Install wiring in raceways.
2. Use insulated spade lugs for wire and cable connection to screw terminals.
3.4 REMOVAL OF CONDUCTORS AND CABLES
A. Remove abandoned conductors and cables. Abandoned conductors and cables are those installed that are not terminated at equipment and are not identified with a tag for future use.
3.5 CONTROL-CIRCUIT CONDUCTORS
A. Minimum Conductor Sizes:
1. Class 2 low-energy, remote-control, and signal circuits; No. 16 AWG.
2. Class 3 low-energy, remote-control, alarm, and signal circuits; No 12 AWG.
3.6 GROUNDING
A. For data communication wiring, comply with TIA-607-B and with BICSI TDMM, "Bonding and Grounding (Earthing)" Chapter.
B. For control-voltage wiring and cabling, comply with requirements in Section 260526 "Grounding and Bonding for Electrical Systems."
3.7 IDENTIFICATION
A. Comply with requirements for identification specified in Section 260553 "Identification for Electrical Systems."
B. Identify data and communications system components, wiring, and cabling according to TIA606-B; label printers must use label stocks, laminating adhesives, and inks complying with UL 969.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CONTROL-VOLTAGE ELECTRICAL POWER CABLES 260523 - 6
C. Identify each wire on each end and at each terminal with a number-coded identification tag.
Each wire must have a unique tag.
3.8 FIELD QUALITY CONTROL
A. Tests and Inspections:
1. Visually inspect cable jacket materials for UL or third-party certification markings.
Inspect cabling terminations to confirm color-coding for pin assignments, and inspect cabling connections to confirm compliance with TIA-568-C.1.
2. Visually inspect cable placement, cable termination, grounding and bonding, equipment and patch cords, and labeling of all components.
3. Test cabling for direct-current loop resistance, shorts, opens, intermittent faults, and polarity between conductors. Test operation of shorting bars in connection blocks. Test cables after termination, but not after cross-connection. a. Test instruments must meet or exceed applicable requirements in TIA-568-C.2.
Perform tests with a tester that complies with performance requirements in its "Test Instruments (Normative)" Annex, complying with measurement accuracy specified in its "Measurement Accuracy (Informative)" Annex. Use only test cords and adapters that are qualified by test equipment manufacturer for channel or link test configuration.
B. End-to-end cabling will be considered defective if it does not pass tests and inspections.
C. Prepare test and inspection reports.
END OF SECTION 260523
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 1 SECTION 260526
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Grounding and bonding conductors.
2. Grounding and bonding bushings.
3. Grounding and bonding busbars.
4. Grounding (earthing) electrodes.
PART 2 - PRODUCTS
2.1 GROUNDING AND BONDING CONDUCTORS
A. Equipment Grounding Conductor:
1. General Characteristics: 600 V, THHN/THWN-2 wire or cable, green color, in accordance with Section 260519 "Low-Voltage Electrical Power Conductors and Cables."
B. ASTM - Bare Copper Grounding and Bonding Conductor:
1. Manufacturers:
a. Southwire.
b. International Wire Group, Inc.
c. New England Wire Technologies Corp.
d. Or approved equal.
2. Referenced Standards: Complying with one or more of the following:
a. Soft Copper Wire: ASTM B3
b. Concentric-Lay Stranded Copper Conductor: ASTM B8.
2.2 GROUNDING AND BONDING BUSHINGS
A. Description: Bonding bushings connect conduit fittings, tubing fittings, threaded metal conduit, and unthreaded metal conduit to metal boxes and equipment enclosures, and have one or more bonding screws intended to provide electrical continuity between bushing and enclosure.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 2 Grounding bushings have provision for connection of bonding or grounding conductor and may or may not also have bonding screws.
B. Performance Criteria:
1. Regulatory Requirements:
a. Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
2. Listing Criteria:
a. Grounding and Bonding Equipment: UL CCN KDER; including UL 467.
C. UL KDER - Bonding Bushing:
1. Manufacturers:
a. Cooper Crouse-Hinds.
b. American Fittings Corp.
c. Bridgeport.
d. Or approved equal.
2. General Characteristics: Threaded bushing with insulated throat.
D. UL KDER - Grounding Bushing:
1. Manufacturers:
a. Cooper Crouse-Hinds.
b. American Fittings Corp.
c. Bridgeport.
d. Or approved equal.
2. General Characteristics: Threaded bushing with insulated throat and mechanical-type wire terminal.
2.3 GROUNDING AND BONDING BUSBARS
A. Description: Miscellaneous grounding and bonding device that serves as common connection for multiple grounding and bonding conductors.
B. Performance Criteria:
1. Regulatory Requirements:
a. Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 3
2. Listing Criteria:
a. Grounding and Bonding Equipment: UL CCN KDER; including UL 467.
C. UL KDER - Equipment Grounding and Bonding Busbar in Metered Switchboard, Metered Pedestal, Panelboards, and Motor Control Center:
1. Manufacturers:
a. Cooper Crouse-Hinds.
b. American Fittings Corp.
c. Bridgeport.
d. Or approved equal.
2. General Characteristics:
a. Bus: Rectangular bar of annealed copper.
b. Mounting Stand-Off Insulators: Lexan or PVC.
1) Comply with UL 891 for use in 600 V switchboards, impulse tested at 5000 V.
2.4 GROUNDING (EARTHING) ELECTRODES
A. Description: Grounding electrodes include rod electrodes, ring electrodes, metal underground water pipes, concrete-encased electrodes, and pipe and plate electrodes.
B. Performance Criteria:
1. Regulatory Requirements:
a. Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
2. Listing Criteria:
a. Grounding and Bonding Equipment: UL CCN KDER; including UL 467.
Copy and re-edit first paragraph below for each configuration indicated on Drawings.
Insert drawing designation. Use these designations on Drawings to identify each product.
C. UL KDER - Rod Electrode :
1. Manufacturers:
a. Burndy.
b. Erico.
c. Thomas & Betts.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 4 d. Or approved equal.
2. General Characteristics: Copper-clad; 3/4 inch by 10 ft.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Inspect test results of grounding system measured at point of electrical service equipment connection.
B. Proceed with connection of electrical service equipment only after unsatisfactory conditions have been corrected.
3.2 SELECTION OF GROUNDING AND BONDING CONDUCTORS
A. Conductors: Install solid conductor for 12 AWG and smaller, and stranded conductors for 10 AWG and larger unless otherwise indicated.
3.3 INSTALLATION
A. Comply with manufacturer's published instructions.
B. Special Techniques:
1. Conductors:
a. Route along shortest and straightest paths possible unless otherwise indicated or required by Code. Avoid obstructing access or placing conductors where they may be subjected to strain, impact, or damage.
2. Connections: Make connections so possibility of galvanic action or electrolysis is minimized. Select connectors, connection hardware, conductors, and connection methods so metals in direct contact are galvanically compatible.
3. Electrodes:
a. Ground Rods: Drive rods until tops are 2 inch (50 mm) below finished floor or final grade unless otherwise indicated.
1) Interconnect ground rods with grounding electrode conductor below grade and as otherwise indicated. Make connections without exposing steel or damaging coating if any.
2) Use exothermic welds for below-grade connections.
b. Concrete-Encased Electrode (Ufer Ground):
1) Fabricate in accordance with NFPA 70; use minimum of 20 ft of bare copper conductor sized as shown on electrical construction documents.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 5 a) If concrete foundation is less than 20 ft (6 m) long, coil excess conductor within base of foundation.
4. Bond grounding conductor to reinforcing steel in at least four locations and to anchor bolts. Grounding at Service:
a. Equipment grounding conductors and grounding electrode conductors must be connected to ground bus. Install main bonding jumper between neutral and ground buses.
5. Grounding Separately Derived Systems:
a. Comply with IEEE C2 grounding requirements.
b. Grounding Manholes and Handholes: Install driven ground rod through manhole or handhole floor, close to wall, and set rod depth so 4 inch (100 mm) will extend above finished floor. If necessary, install ground rod before manhole is placed and provide 1/0 AWG bare, tinned-copper conductor from ground rod into manhole through waterproof sleeve in manhole wall. Protect ground rods passing through concrete floor with double wrapping of pressure-sensitive insulating tape or heatshrunk insulating sleeve from 2 inch (50 mm) above to 6 inch (150 mm) below concrete. Seal floor opening with waterproof, nonshrink grout. c. Grounding Connections to Manhole Components: Bond exposed-metal parts such as inserts, cable racks, pulling irons, ladders, and cable shields within each manhole or handhole, to ground rod or grounding conductor. Make connections with 4 AWG minimum, stranded, hard-drawn copper bonding conductor. Train conductors level or plumb around corners and fasten to manhole walls. Connect to cable armor and cable shields in accordance with manufacturer's published instructions with splicing and termination kits.
d. Pad-Mounted Transformers and Switches: Install two ground rods and ring electrode around pad. Ground pad-mounted equipment and noncurrent-carrying metal items associated with substations by connecting them to underground cable and grounding electrodes. Install tinned-copper conductor not less than 2 AWG for ring electrode and for taps to equipment grounding terminals. Bury ring electrode not less than 6 inch (150 mm) from foundation.
6. Equipment Grounding:
a. Install insulated equipment grounding conductors with feeders and branch circuits. b. Install insulated equipment grounding conductors with the following items, in addition to those required by NFPA 70:
1) Feeders and branch circuits.
2) Lighting circuits.
3) Receptacle circuits.
4) Single-phase motor and appliance branch circuits.
5) Three-phase motor and appliance branch circuits.
6) Flexible raceway runs.
7) Lighting Poles.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260526 - 6 8) Busway Supply Circuits: Install insulated equipment grounding conductor from grounding bus in switchgear, switchboard, or distribution panel to equipment grounding bar terminal on busway.
3.4 FIELD QUALITY CONTROL
A. Field tests and inspections must be witnessed by authorities having jurisdiction.
B. Tests and Inspections:
1. After installing grounding system but before permanent electrical circuits have been energized, test for compliance with requirements.
2. Inspect physical and mechanical condition. Verify tightness of accessible, bolted, electrical connections with calibrated torque wrench in accordance with manufacturer's published instructions.
C. Nonconforming Work:
1. Grounding system will be considered defective if it does not pass tests and inspections.
2. Remove and replace defective components and retest.
D. Collect, assemble, and submit test and inspection reports.
1. Report measured ground resistances that exceed the following values:
a. Power Distribution Units or Panelboards Serving Electronic Equipment: 3 Ω. b. Pad-Mounted Equipment: 5 Ω.
c. Manhole Grounds: 10 Ω.
3.5 PROTECTION
A. After installation, protect grounding and bonding cables and equipment from construction activities. Remove and replace items that are contaminated, defaced, damaged, or otherwise caused to be unfit for use prior to acceptance by Owner.
END OF SECTION 260526
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 1
SECTION 260529
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Support, anchorage, and attachment components.
2. Fabricated metal equipment support assemblies.
1.2 ACTION SUBMITTALS
A. Product Data:
1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for the following:
a. Slotted support systems, hardware, and accessories.
b. Clamps.
c. Hangers.
d. Sockets.
e. Eye nuts.
f. Fasteners.
g. Anchors.
h. Saddles.
i. Brackets.
2. Include rated capacities and furnished specialties and accessories.
B. Shop Drawings: For fabrication and installation details for electrical hangers and support systems.
1. Hangers. Include product data for components.
2. Slotted support systems.
3. Equipment supports.
4. Vibration Isolation Base Details: Detail fabrication including anchorages and attachments to structure and to supported equipment.
PART 2 - PRODUCTSPERFORMANCE REQUIREMENTS
A. Surface-Burning Characteristics: Comply with ASTM E84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 2
1. Flame Rating: Class 1.
2. Self-extinguishing according to ASTM D635.
2.2 SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS
A. Steel Slotted Support Systems: Preformed steel channels and angles with minimum 13/32 inch diameter holes at a maximum of 8 inch on center in at least one surface.
1. Manufacturers:
a. B-Line
b. Erico
c. Unistrut
2. Standard: Comply with MFMA-4 factory-fabricated components for field assembly.
3. Material for Channel, Fittings, and Accessories: Stainless steel, Type 316.
4. Channel Width: Selected for applicable load criteria.
5. Metallic Coatings: Hot-dip galvanized after fabrication and applied according to MFMA4.
B. Conduit and Cable Support Devices: Stainless steel hangers, clamps, and associated fittings, designed for types and sizes of raceway or cable to be supported.
C. Support for Conductors in Vertical Conduit: Factory-fabricated assembly consisting of threaded body and insulating wedging plug or plugs for nonarmored electrical conductors or cables in riser conduits. Plugs must have number, size, and shape of conductor gripping pieces as required to suit individual conductors or cables supported. Body must be made of malleable iron.
D. Structural Steel for Fabricated Supports and Restraints: ASTM A36/A36M steel plates, shapes, and bars; black and galvanized.
E. Mounting, Anchoring, and Attachment Components: Items for fastening electrical items or their supports to building surfaces include the following:
1. Powder-Actuated Fasteners: Threaded-steel stud, for use in hardened portland cement concrete, steel, or wood, with tension, shear, and pullout capacities appropriate for supported loads and building materials where used.
a. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1) Hilti.
2) ITW Ramset/Redhead.
3) MKT Fastening.
2. Mechanical-Expansion Anchors: Insert-wedge-type, stainless steel, for use in hardened portland cement concrete, with tension, shear, and pullout capacities appropriate for supported loads and building materials where used.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 3
a. Manufacturers:
1) Power Fasteners.
2) Metallics.
3) Peco Fastener.
4) Or approved equal.
3. Concrete Inserts: Steel or malleable-iron, slotted support system units are similar to MSS Type 18 units and comply with MFMA-4 or MSS SP-58.
4. Clamps for Attachment to Steel Structural Elements: MSS SP-58 units are suitable for attached structural element.
5. Through Bolts: Structural type, hex head, and high strength. Comply with ASTM F3125/F3125M, Grade A325.
6. Toggle Bolts: Stainless steel springhead type.
7. Hanger Rods: Threaded steel.
2.3 FABRICATED METAL EQUIPMENT SUPPORT ASSEMBLIES
A. Description: Welded or bolted structural-steel shapes, shop or field fabricated to fit dimensions of supported equipment.
PART 3 - EXECUTION
3.1 SELECTION
A. Comply with the following standards for selection and installation of hangers and supports, except where requirements on Drawings or in this Section are stricter:
1. NECA NEIS 101
2. NECA NEIS 102.
3. NECA NEIS 105.
4. NECA NEIS 111.
B. Comply with requirements for raceways specified in Section 260533.13 "Conduits for Electrical Systems."
C. Comply with requirements for boxes specified in Section 260533.16 "Boxes and Covers for Electrical Systems."
D. Provide vibration and seismic controls with hangers and supports.
E. Maximum Support Spacing and Minimum Hanger Rod Size for Raceways: Space supports for EMT and ERMC as required by NFPA 70. Minimum rod size must be 1/4 inch in diameter.
F. Multiple Raceways or Cables: Install trapeze-type supports fabricated with steel slotted support system, sized so capacity can be increased by at least 25percent in future without exceeding specified design load limits.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 4
1. Secure raceways and cables to these supports with two-bolt conduit clamps or single-bolt conduit clamps.
3.2 INSTALLATION OF SUPPORTS
A. Comply with NECA NEIS 101 for installation requirements except as specified in this article.
B. Strength of Support Assemblies: Where not indicated, select sizes of components so strength will be adequate to carry present and future static loads within specified loading limits.
Minimum static design load used for strength determination must be weight of supported components plus 200 lb.
C. Mounting and Anchorage of Surface-Mounted Equipment and Components: Anchor and fasten electrical items and their supports to building structural elements by the following methods unless otherwise indicated by code:
1. To Wood: Fasten with lag screws or through bolts.
2. To New Concrete: Bolt to concrete inserts.
3. To Masonry: Approved toggle-type bolts on hollow masonry units and expansion anchor fasteners on solid masonry units.
4. To Existing Concrete: Expansion anchor fasteners.
5. Manufacturers:
a. Burndy.
b. Erico.
c. Thomas & Betts.
d. Or approved equal.
6. To Steel: Beam clamps (MSS SP-58, Type 19, 21, 23, 25, or 27), complying with MSS SP-69.
7. To Light Steel: Sheet metal screws.
8. Items Mounted on Hollow Walls and Nonstructural Building Surfaces: Mount cabinets, panelboards, disconnect switches, control enclosures, pull and junction boxes, transformers, and other devices on slotted-channel racks attached to substrate by means that comply with seismic-restraint strength and anchorage requirements.
D. Drill holes for expansion anchors in concrete at locations and to depths that avoid the need for reinforcing bars.
3.3 INSTALLATION OF FABRICATED METAL SUPPORTS
A. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and elevation to support and anchor electrical materials and equipment.
B. Field Welding: Comply with AWS D1.1/D1.1M. Submit welding certificates.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 5
3.4 PAINTING
A. Touchup:
1. Clean field welds and abraded areas of shop paint. Paint exposed areas immediately after erecting hangers and supports. Use same materials as used for shop painting. Comply with SSPC-PA 1 requirements for touching up field-painted surfaces. a. Apply paint by brush or spray to provide minimum dry film thickness of 2.0 mils.
B. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply galvanizing-repair paint to comply with ASTM A780.
END OF SECTION 260529
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 260529 - 6
THIS PAGE IS INTENTIONALLY LEFT BLANK
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 1
SECTION 260533.13
CONDUITS FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Type EMT-SS duct raceways and elbows.
2. Type ERMC-SS duct raceways, elbows, couplings, and nipples.
3. Type ERMC-S duct raceways, elbows, couplings, and nipples.
4. Type LFMC duct raceways.
5. Type LFNC duct raceways.
6. Type PVC duct raceways and fittings.
7. Fittings for conduit, tubing, and cable.
8. Electrically conductive corrosion-resistant compounds for threaded conduit.
9. Solvent cements.
B. Products Installed, but Not Furnished, under This Section:
1. See Section 260553 "Identification for Electrical Systems" for electrical equipment labels.
C. Related Requirements:
1. Section 260519 "Low-Voltage for Electrical Power Conductors and Cables" for nonmetallic underground conduit with conductors (Type NUCC).
2. Section 260543 "Underground Ducts and Raceways for Electrical Systems" for exterior duct banks, manholes, and underground utility construction.
1.2 DEFINITIONS
A. Conduit: A structure containing one or more duct raceways.
B. Duct Raceway: A single enclosed raceway for conductors or cable.
C. Duct Bank: An arrangement of conduit providing one or more continuous duct raceways between two points.
1.3 ACTION SUBMITTALS
A. Product Data:
1. Type EMT-SS duct raceways and elbows.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 2
2. Type ERMC-SS duct raceways, elbows, couplings, and nipples.
3. Type ERMC-S duct raceways, elbows, couplings, and nipples.
4. Type LFMC duct raceways.
5. Type LFNC duct raceways.
6. Type PVC duct raceways and fittings.
7. Fittings for conduit, tubing, and cable.
8. Electrically conductive corrosion-resistant compounds for threaded conduit.
9. Solvent cements.
B. Sustainable design submittals.
1. Solvent cements.
PART 2 - PRODUCTS
2.1 TYPE EMT-A AND TYPE EMT-SS DUCT RACEWAYS AND ELBOWS A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
2. Listing Criteria: UL CCN FJMX; including UL 797A.
B. Source Quality Control:
1. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
2. Manufacturer's Published Instructions: Prepare and submit installation, testing, and operating instructions for product.
C. UL FJMX - Stainless Steel Electrical Metal Tubing (EMT-SS) and Elbows:
1. Manufacturers:
a. Allied Conduit.
b. Republic Conduit.
c. Rymco.
d. Or approved equal.
2. Material: Stainless steel.
3. Options:
a. Minimum Trade Size: Metric designator 21 (trade size 3/4). b. Colors: As indicated on Drawings.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 3
2.2 TYPE ERMC-SS DUCT RACEWAYS, ELBOWS, COUPLINGS, AND NIPPLES A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
2. Listing Criteria: UL CCN DYWV; including UL 6A.
B. Source Quality Control:
1. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
2. Manufacturer's Published Instructions: Prepare and submit installation, testing, and operating instructions for product.
C. UL DYWV - Stainless Steel Electrical Rigid Metal Conduit (ERMC-SS), Elbows, Couplings, and Nipples:
1. Manufacturers:
a. Allied Conduit.
b. Republic Conduit.
c. Rymco.
d. Or approved equal.
2. Material: Stainless steel.
3. Options:
a. Minimum Trade Size: Metric designator 21 (trade size 3/4). b. Colors: As indicated on Drawings.
2.3 TYPE ERMC-S DUCT RACEWAYS, ELBOWS, COUPLINGS, AND NIPPLES A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
2. Listing Criteria: UL CCN DYIX; including UL 6.
B. Source Quality Control:
1. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
2. Manufacturer's Published Instructions: Prepare and submit installation, testing, and operating instructions for product.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 4
C. UL DYIX - PVC-Coated-Steel Electrical Rigid Metal Conduit (ERMC-S-PVC), Elbows, Couplings, and Nipples:
1. Manufacturers:
a. Robroy.
b. Calpipe.
c. Or approved equal.
2. Options:
a. Exterior Coating: PVC complying with NEMA RN 1.
b. Interior Coating: Zinc with organic top coating.
c. Minimum Trade Size: Metric designator 21 (trade size 3/4). d. Colors: As indicated on Drawings.
2.4 TYPE LFMC DUCT RACEWAYS
A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
2. Listing Criteria: UL CCN DXHR; including UL 360.
B. Source Quality Control:
1. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
2. Manufacturer's Published Instructions: Prepare and submit installation, testing, and operating instructions for product.
C. UL DXHR - Stainless Steel Liquidtight Flexible Metal Conduit (LFMC-SS):
1. Manufacturers:
a. Atkore.
b. Calbrite.
c. South Wire.
d. Or approved equal.
2. Material: Stainless steel.
3. Options:
a. Minimum Trade Size: Metric designator 21 (trade size 3/4). b. Colors: As indicated on Drawings.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 5
2.5 TYPE LFNC DUCT RACEWAYS
A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
2. Listing Criteria: UL CCN DXOQ; including UL 1660.
B. Source Quality Control:
1. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
2. Manufacturer's Published Instructions: Prepare and submit installation, testing, and operating instructions for product.
C. UL DXOQ - Integral (Type B) Liquidtight Flexible Nonmetallic Conduit (LFNC-B):
1. Manufacturers:
a. Thomas & Betts.
b. AFC.
c. South Wire.
d. Or approved equal.
2. Additional Criteria: Type B conduit with smooth inner surface with integral reinforcement within conduit wall.
3. Options:
a. Minimum Trade Size: Metric designator 21 (trade size 3/4). b. Colors: As indicated on Drawings.
c. Markings: 105 deg C dry and Direct burial.
2.6 TYPE PVC DUCT RACEWAYS AND FITTINGS
A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
2. Listing Criteria: UL CCN DZYR; including UL 651.
B. Source Quality Control:
1. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
2. Manufacturer's Published Instructions: Prepare and submit installation, testing, and operating instructions for product.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 6
C. UL DZYR - Schedule 40 Rigid PVC Conduit (PVC-40) and Fittings:
1. Manufacturers:
a. Allied Conduit.
b. Republic Conduit.
c. Rymco.
d. Or approved equal.
2. Dimensional Specifications: Schedule 40.
3. Options:
a. Minimum Trade Size: Trade size 1).
b. Markings: For use with maximum 90 deg C wire.
D. UL DZYR - Schedule 80 Rigid PVC Conduit (PVC-80) and Fittings:
1. Manufacturers:
a. Allied Conduit.
b. Republic Conduit.
c. Rymco.
d. Or approved equal.
2. Dimensional Specifications: Schedule 80.
3. Options:
a. Minimum Trade Size: Metric designator 27 (trade size 1). b. Markings: For use with maximum 90 deg C wire.
2.7 FITTINGS FOR CONDUIT, TUBING, AND CABLE
A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
B. Source Quality Control:
1. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
2. Manufacturer's Published Instructions: Prepare and submit installation, testing, and operating instructions for product.
C. UL DWTT - Fittings for Type ERMC and Type PVC Duct Raceways:
1. Manufacturers:
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 7
a. Thomas & Betts.
b. Raco.
c. Bridgeport.
d. Or approved equal.
2. Listing Criteria: UL CCN DWTT; including UL 514B.
3. Options:
a. Material: Steel.
b. Coupling Method: Raintight compression coupling with distinctive color gland nut.
c. Expansion and Deflection Fittings: UL 651 with flexible bonding jumper.
D. UL FKAV - Fittings for Type EMT Duct Raceways:
1. Manufacturers:
a. Thomas & Betts.
b. Raco.
c. Bridgeport.
d. Or approved equal.
2. Listing Criteria: UL CCN FKAV; including UL 514B.
3. Options:
a. Material: Steel.
b. Coupling Method: Raintight compression coupling with distinctive color gland nut.
E. UL DXAS - Fittings for Type LFMC and Type LFNC Duct Raceways:
1. Manufacturers:
a. Atkore.
b. Calbrite.
c. South Wire.
d. Thomas & Betts.
e. AFC.
f. Or approved equal.
2. Listing Criteria: UL CCN DXAS; including UL 514B.
2.8 ELECTRICALLY CONDUCTIVE CORROSION-RESISTANT COMPOUNDS FOR
THREADED CONDUIT
A. Performance Criteria:
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 8
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
2. Listing Criteria: UL CCN FOIZ; including UL Subject 2419.
B. Source Quality Control:
1. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
2. Manufacturer's Published Instructions: Prepare and submit installation, testing, and operating instructions for product.
C. UL FOIZ - Electrically Conductive Corrosion-Resistant Compound for Threaded Conduit:
1. Manufacturers:
a. Thomas & Betts.
b. Burndy.
c. 3M.
d. IDEAL.
e. Or approved equal.
2.9 SOLVENT CEMENTS
A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70, by qualified electrical testing laboratory recognized by authorities having jurisdiction, and marked for intended location and application.
2. Listing Criteria: UL CCN DWTT; including UL 514B.
B. Source Quality Control:
1. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
2. Manufacturer's Published Instructions: Prepare and submit installation, testing, and operating instructions for product.
C. UL DWTT - Solvent Cements for Type PVC Duct Raceways and Fittings:
1. Manufacturers:
a. Thomas & Betts.
b. Old Castle.
c. Arrow Fastener.
d. Or approved equal.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 9
PART 3 - EXECUTION
3.1 SELECTION OF CONDUITS FOR ELECTRICAL SYSTEMS
A. Unless more stringent requirements are specified in Contract Documents or manufacturers' published instructions, comply with NFPA 70 for selection of duct raceways. Consult Architect for resolution of conflicting requirements.
B. Outdoors:
1. Exposed and Not Subject to Physical Damage: ERMC and Corrosion-resistant EMT.
2. Concealed Aboveground: ERMC, EMT, PVC-80, and PVC-40.
3. Direct Buried: PVC-80 and PVC-40.
4. Concrete Encased Not in Trench: PVC-80.
3.2 Concrete Encased in Trench: PVC-80INSTALLATION OF CONDUITS FOR ELECTRICAL
SYSTEMS
A. Comply with manufacturer's published instructions.
B. Reference Standards for Installation: Unless more stringent installation requirements are specified in Contract Documents or manufacturers' published instructions, comply with the following:
1. Type EMT-SS: Article 358 of NFPA 70 and NECA NEIS 101.
2. Type ERMC-SS: Article 344 of NFPA 70 and NECA NEIS 101.
3. Type ERMC-S: Article 344 of NFPA 70 and NECA NEIS 101.
4. Type LFMC: Article 350 of NFPA 70 and NECA NEIS 101.
5. Type LFNC: Article 342 of NFPA 70 and NECA NEIS 111.
6. Type PVC: Article 356 of NFPA 70 and NECA NEIS 111.
7. Expansion Fittings: NEMA FB 2.40.
8. Consult Architect for resolution of conflicting requirements.
C. Special Installation Techniques:
1. General Requirements for Installation of Duct Raceways:
a. Complete duct raceway installation before starting conductor installation. b. Provide stub-ups through floors with coupling threaded inside for plugs, set flush with finished floor. Plug coupling until conduit is extended above floor to final destination or a minimum of 2 ft above finished floor.
c. Install no more than equivalent of three 90-degree bends in conduit run except for control wiring conduits, for which no more than equivalent of two 90-degree fewer bends are permitted. Support within 12 inch of changes in direction. d. Make bends in duct raceway using large-radius preformed ells except for parallel bends. Field bending must be in accordance with NFPA 70 minimum radii requirements. Provide only equipment specifically designed for material and size involved.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 10
e. Conceal conduit within finished walls, ceilings, and floors unless otherwise indicated. Install conduits parallel or perpendicular to building lines. f. Support conduit within 12 inch of enclosures to which attached. g. Install duct sealing fittings at accessible locations in accordance with NFPA 70 and fill them with listed sealing compound. For concealed duct raceways, install fitting in flush steel box with blank cover plate having finish similar to that of adjacent plates or surfaces. Install duct sealing fittings in accordance with NFPA 70. h. Install devices to seal duct raceway interiors at accessible locations. Locate seals so no fittings or boxes are between the seal and the following changes of environments. Seal interior of duct raceways at the following points:
1) Where an underground service duct raceway enters a structure. 2) Where otherwise required by NFPA 70.
i. Cut conduit perpendicular to the length. For conduits metric designator 53 (trade size 2) and larger, use roll cutter or a guide to make cut straight and perpendicular to the length. Ream inside of conduit to remove burrs.
j. Install pull wires in empty duct raceways. Provide polypropylene or monofilament plastic line with not less than 200 lb tensile strength. Leave at least 12 inch of slack at both ends of pull wire. Cap underground duct raceways designated as spare above grade alongside duct raceways in use.
k. Install duct raceways square to the enclosure and terminate at enclosures without hubs with locknuts on both sides of enclosure wall. Install locknuts hand tight, plus one-quarter turn more.
1) Termination fittings with shoulders do not require two locknuts. l. Terminate threaded conduits into threaded hubs or with locknuts on inside and outside of boxes or cabinets. Install bushings on conduits up to metric designator 35 (trade size 1-1/4) and insulated throat metal bushings on metric designator 41 (trade size 1-1/2) and larger conduits terminated with locknuts. Install insulated throat metal grounding bushings on service conduits.
2. Types ERMC:
a. Threaded Conduit Joints, Exposed to Wet, Damp, Corrosive, or Outdoor Conditions: Apply listed compound that maintains electrical conductivity to threads of duct raceway and fittings before making up joints. Follow compound manufacturer's published instructions.
3. Type ERMC-S-PVC:
a. Follow manufacturer's installation instructions for clamping, cutting, threading, bending, and assembly.
b. Provide PVC-coated sealing locknut for exposed male threads transitioning into female NPT threads that do not have sealing sleeves, including transitions from PVC couplings/female adapters to Type ERMC-S-PVC elbows in direct-burial applications. PVC-coated sealing locknuts must not be used in place of conduit hub. PVC-coated sealing locknut must cover exposed threads on Type ERMC-SPVC duct raceway.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 11
c. Coat field-cut threads on PVC-coated duct raceway with manufacturer-approved corrosion-preventing conductive compound prior to assembly.
4. Types PVC:
a. Do not install Type PVC conduit where ambient temperature exceeds 122 deg F.
Conductor ratings must be limited to 75 deg C except where installed in a trench outside buildings with concrete encasement, where 90 deg C conductors are permitted.
b. Comply with manufacturer's published instructions for solvent welding and fittings.
5. Duct Raceway Terminations at Locations Subject to Moisture or Vibration:
a. Provide insulating bushings to protect conductors, including conductors smaller than 4 AWG. Install insulated throat metal grounding bushings on service conduits.
6. Duct Fittings: Install fittings in accordance with NEMA FB 2.10 guidelines. a. ERMC-S-PVC: Provide only fittings listed for use with this type of conduit. Patch and seal joints, nicks, and scrapes in PVC coating after installing conduits and fittings. Provide sealant recommended by fitting manufacturer and apply in thickness and number of coats recommended by manufacturer. b. EMT: Provide compression fittings. Comply with NEMA FB 2.10. c. Flexible Conduit: Provide only fittings listed for use with flexible conduit type.
Comply with NEMA FB 2.20.
7. Identification: Provide labels for conduit assemblies, duct raceways, and associated electrical equipment.
a. Provide warning signs.
3.3 PROTECTION
A. Protect coatings, finishes, and cabinets from damage and deterioration.
1. Repair damage to galvanized finishes with zinc-rich paint recommended by manufacturer.
2. Repair damage to PVC coatings or paint finishes with matching touchup coating recommended by manufacturer.
END OF SECTION 260533.13
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
CONDUITS FOR ELECTRICAL SYSTEMS 260533.13 - 12
THIS PAGE IS INTENTIONALLY LEFT BLANK
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS 260543 - 1 SECTION 260543
UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Type ERMC-SS raceways, elbows, couplings, and nipples.
2. Type ERMC-S raceways, elbows, couplings, and nipples.
3. Type PVC raceways and fittings.
4. Fittings for conduit, tubing, and cable.
5. Electrically conductive corrosion-resistant compounds for threaded conduit.
6. Solvent cements.
7. Duct accessories.
8. Handholes and boxes for exterior underground wiring.
9. Duct sealing.
B. Related Requirements:
1. Section 260519 "Low-Voltage for Electrical Power Conductors and Cables" for nonmetallic underground conduit with conductors (Type NUCC).
1.2 DEFINITIONS
A. Duct: A single raceway or multiple raceways, installed singly or as components of a duct bank.
B. Duct Bank: Two or more ducts installed in parallel, direct buried or with additional casing materials such as concrete.
C. Handhole: An underground chamber containing electrical cables, sized such that personnel are not required to enter in order to access the cables.
D. Manhole: An underground chamber containing electrical cables and equipment, sized to provide access with working space clearances.
E. Trafficways: Locations where vehicular or pedestrian traffic is a normal course of events.
1.3 ACTION SUBMITTALS
A. Product Data:
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS 260543 - 2
1. Type ERMC-SS raceways, elbows, couplings, and nipples.
2. Type ERMC-S raceways, elbows, couplings, and nipples.
3. Type PVC raceways and fittings.
4. Fittings for conduit, tubing, and cable.
5. Electrically conductive corrosion-resistant compounds for threaded conduit.
6. Solvent cements.
7. Duct accessories.
8. Handholes and boxes for exterior underground wiring.
9. Duct sealing.
B. Shop Drawings:
1. Factory-Fabricated Handholes and Boxes Other Than Precast Concrete:
a. Include dimensioned plans, sections, and elevations, and fabrication and installation details.
b. Include duct entry provisions, including locations and duct sizes, and methods and materials for waterproofing duct entry locations.
c. Include cover design.
d. Include grounding details.
e. Include dimensioned locations of cable rack inserts, pulling-in and lifting irons, and other accessories.
C. Field quality-control reports.
1.4 INFORMATIONAL SUBMITTALS
A. Certificates: For concrete and steel used in precast concrete handholes, as required by ASTM C858.
B. Manufacturers' published instructions.
PART 2 - PRODUCTS
2.1 TYPE ERMC-SS RACEWAYS, ELBOWS, COUPLINGS, AND NIPPLES A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70 and marked for intended location and use.
2. General Characteristics: UL 6A and UL CCN DYWV.
B. Stainless Steel Electrical Rigid Metal Conduit (ERMC-SS), Elbows, Couplings, and Nipples:
1. Manufacturers:
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS 260543 - 3 a. Crouse-Hinds.
b. Republic Conduit.
c. Thomas & Betts
d. Or approved equal.
2. Material: Stainless steel.
3. Options:
a. Minimum Trade Size: Metric designator 21 (trade size 3/4). b. Colors: As indicated on Drawings.
2.2 TYPE ERMC-S RACEWAYS, ELBOWS, COUPLINGS, AND NIPPLES A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70 and marked for intended location and use.
2. General Characteristics: UL 6 and UL CCN DYIX.
B. Galvanized-Steel Electrical Rigid Metal Conduit (ERMC-S-G), Elbows, Couplings, and Nipples:
1. Manufacturers:
a. Crouse-Hinds.
b. Republic Conduit.
c. Thomas & Betts
d. Or approved equal.
2. Exterior Coating: Zinc.
3. Options:
a. Interior Coating: Zinc.
b. Minimum Trade Size: Metric designator 21 (trade size 3/4).
C. PVC-Coated-Steel Electrical Rigid Metal Conduit (ERMC-S-PVC), Elbows, Couplings, and Nipples:
1. Manufacturers:
a. Calpipe.
b. Robroy.
c. Thomas & Betts
d. Or approved equal.
2. Additional Characteristics:
3. Fittings for PVC-Coated Conduit:
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS 260543 - 4 a. Minimum coating thickness of 0.040 inch, with overlapping sleeves protecting threaded joints.
b. PVC coating on outside of conduit couplings must be protected from tool damage during installation.
c. Female threads on fittings and couplings must be protected by urethane coating. d. Fittings must be from same manufacturer as conduit.
4. Options:
a. Exterior Coating: PVC complying with NEMA RN 1 and marked ETL Verified PVC-001.
b. Interior Coating: Zinc.
c. Minimum Trade Size: Metric designator 21 (trade size 3/4).
2.3 TYPE PVC RACEWAYS AND FITTINGS
A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70 and marked for intended location and use.
2. General Characteristics: UL 651 and UL CCN DZYR.
B. Schedule 40 Rigid PVC Conduit (PVC-40) and Fittings:
1. Manufacturers:
a. Allied Conduit.
b. Republic Conduit.
c. Rymco.
d. Or approved equal.
2. Dimensional Specifications: Schedule 40.
3. Options:
a. Minimum Trade Size: Metric designator 27 (trade size 1). b. Markings: For use with maximum 90 deg C wire.
C. Schedule 80 Rigid PVC Conduit (PVC-80) and Fittings:
1. Manufacturers:
a. Allied Conduit.
b. Republic Conduit.
c. Rymco.
d. Or approved equal.
2. Dimensional Specifications: Schedule 80.
3. Options:
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS 260543 - 5 a. Minimum Trade Size: Metric designator 27 (trade size 1). b. Markings: For use with maximum 90 deg C wire.
2.4 FITTINGS FOR CONDUIT, TUBING, AND CABLE
A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70 and marked for intended location and use.
B. Metallic Fittings for Type ERMC and Type PVC Raceways:
1. Manufacturers:
a. Thomas & Betts.
b. Raco.
c. Bridgeport.
d. Or approved equal.
2. General Characteristics: UL 514B and UL CCN DWTT.
3. Options:
a. Material: Steel.
b. Coupling Method: Raintight compression coupling with distinctive color gland nut.
c. Conduit Fittings for Hazardous (Classified) Locations: UL 1203. d. Expansion and Deflection Fittings: UL 651 with flexible external bonding jumper.
2.5 ELECTRICALLY CONDUCTIVE CORROSION-RESISTANT COMPOUNDS FOR
THREADED CONDUIT
A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70 and marked for intended location and use.
2. General Characteristics: UL Subject 2419 and UL CCN FOIZ.
B. Manufacturers:
1. Thomas & Betts.
2. Burndy.
3. 3M.
4. IDEAL.
5. Or approved equal.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS 260543 - 6
2.6 SOLVENT CEMENTS
A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70 and marked for intended location and use.
2. General Characteristics: As recommended by conduit manufacturer in accordance with UL 514B and UL CCN DWTT.
B. Solvent Cements for Type PVC Raceways and Fittings:
1. Manufacturers:
a. Thomas & Betts.
b. Old Castle.
c. Arrow Fastener.
d. Or approved equal.
2.7 DUCT ACCESSORIES
A. Duct Spacers: Factory-fabricated, rigid, PVC interlocking spacers; sized for type and size of duct with which used, and selected to provide minimum duct spacing indicated while supporting duct during concreting or backfilling.
1. Manufacturers:
a. Thomas & Betts.
b. Old Castle.
c. Quazite.
d. Or approved equal.
B. Underground-Line Warning Tape: In accordance with Section 260553 "Identification for Electrical Systems."
C. Concrete Warning Planks: Nominal 12 by 24 by 3 inch in size, manufactured from concrete.
1. Mark each plank with "ELECTRIC" in 2 inch high, 3/8 inch deep letters.
2.8 HANDHOLES AND BOXES FOR EXTERIOR UNDERGROUND WIRING A. Performance Criteria:
1. Regulatory Requirements: Listed and labeled in accordance with NFPA 70 and marked for intended location and use.
2. General Characteristics:
a. ASTM C858 for design and manufacturing processes.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS 260543 - 7 b. SCTE 77.
B. Precast Concrete Handholes and Boxes:
1. Description: Factory-fabricated, reinforced-concrete, monolithically poured walls and bottom unless open-bottom enclosures are indicated. Frame and cover must form top of enclosure and must have load rating consistent with that of handhole or box.
2. Manufacturers:
a. Thomas & Betts.
b. Old Castle.
c. Quazite.
d. Or approved equal.
3. Configuration: Units must be designed for flush burial and have open bottom unless otherwise indicated.
4. Frame and Cover:
a. Weatherproof steel frame, with steel cover with recessed cover hook eyes and tamper-resistant, captive, cover-securing bolts.
b. Cover Finish: Nonskid finish must have minimum coefficient of friction of 0.50. c. Cover Legend: Molded lettering, as indicated for each service.
5. Joint Sealant: Asphaltic-butyl material with adhesion, cohesion, flexibility, and durability properties necessary to withstand maximum hydrostatic pressures at installation location with ground-water level at grade.
6. Duct Entrances in Handhole Walls: Cast end-bell or duct-terminating fitting in wall for each entering duct.
a. Type and size: Match fittings to duct to be terminated. b. Fittings must align with elevations of approaching duct and be located near interior corners of handholes to facilitate racking of cable.
2.9 DUCT SEALING
A. Manufacturers:
1. Hydra Seal S 60.
2. MD3 FiloSeal.
3. NOFIRNO.
4. Or approved equal.
B. Duct-Sealing Compound: Nonhardening, safe for contact with human skin, not deleterious to cable insulation, and workable at temperatures as low as 35 deg F. Compound must be capable of withstanding temperature of 300 deg F without slump and adhering to clean surfaces of plastic ducts, metallic conduit, conduit and duct coatings, concrete, masonry, lead, cable sheaths, cable jackets, insulation materials, and common metals. Duct sealing compound must be removable without damaging ducts or cables.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS 260543 - 8 C. Inflatable Duct-Sealing System: Wraparound inflatable bladder that seals ducts that are empty or containing conductors against air and water infiltration. System is suitable for use in steel, plastic, or concrete ducts and penetrations.
2.10 SOURCE QUALITY CONTROL
A. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
1. Duct-bank materials, including spacers and miscellaneous components.
2. Ducts, conduits, and their accessories, including elbows, end bells, bends, fittings, and solvent cement.
3. Accessories for handholes and boxes.
4. Underground-line warning tape.
5. Warning planks.
B. Factory Tests for Handholes and Boxes:
1. Factory Tests and Inspections: Perform the following tests and inspections on handholes and boxes, by, or under supervision of, qualified electrical testing laboratory recognized by authorities having jurisdiction, before delivering to site. Affix label with name and date of manufacturer's certification of system compliance. a. Precast Concrete Utility Structures: Test and inspect in accordance with ASTM C1037.
2. Nonconforming Work:
a. Equipment that does not pass tests and inspections will be considered defective.
3. Factory Test Reports: Prepare and submit factory test and inspection reports.
PART 3 - EXECUTION
3.1 PREPARATION
A. Coordinate layout and installation of duct, duct bank, handholes, and boxes with final arrangement of other utilities, site grading, and surface features as determined in field. Notify Architect if there is conflict between areas of excavation and existing structures or archaeological sites to remain.
B. Coordinate elevations of duct and duct-bank entrances into handholes and boxes with final locations and profiles of duct and duct banks, as determined by coordination with other utilities, underground obstructions, and surface features. Revise locations and elevations as required to suit field conditions and to ensure that duct and duct bank will drain to manholes and handholes, and as approved by Architect.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS 260543 - 9 C. Clear and grub vegetation to be removed, and protect vegetation to remain in accordance with drawings and specifications.
3.2 SELECTION OF UNDERGROUND DUCTS
A. Duct for Electrical Feeders 600 V and Less: PVC-80 and PVC-40 unless otherwise indicated.
B. Duct for Electrical Branch Circuits: PVC-40, direct buried unless otherwise indicated.
C. Underground Ducts Crossing Paved Paths and Walks and Driveways: PVC-40.
D. Underground Ducts Crossing Roadways: PVC-80 or PVC-40, encased in reinforced concrete.
E. Stub-ups: Concrete encased, PVC-80 or PVC-40.
3.3 SELECTION OF UNDERGROUND ENCLOSURES
A. Handholes and Boxes:
1. Units in Roadways and Other Deliberate Traffic Paths: Precast concrete, AASHTO HB 17,H-20 structural load rating.
2. Units in Driveway, Parking Lot, and Off-Roadway Locations, Subject to Occasional, Nondeliberate Loading by Heavy Vehicles: Precast concrete, AASHTO HB 17, H20structural load rating.
3. Units in Sidewalk and Similar Applications with Safety Factor for Nondeliberate Loading by Vehicles: Precast concrete, AASHTO HB 17, H-10 structural load rating.
4. Cover design load must not exceed load rating of handhole or box.
3.4 EARTHWORK
A. Excavation and Backfill: Comply with requirements of drawings and specifications, but do not use heavy-duty, hydraulic-operated, compaction equipment.
B. Cut and patch existing pavement in path of underground duct, duct bank, and underground structures in accordance with requirements of drawings and specifications.
3.5 INSTALLATION OF DUCTS AND DUCT BANKS
A. Reference Standards:
1. Unless more stringent requirements are specified in Contract Documents or manufacturers' published instructions, comply with NEMA TCB 2 for installation of underground ducts and duct banks.
2. Consult Architect for resolution of conflicting requirements.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS 260543 - 10 B. Special Techniques:
1. Where indicated on Drawings, install duct, spacers, and accessories into duct-bank configuration shown. Duct installation requirements in this Section also apply to duct bank.
2. Curves and Bends:
a. Use 5-degree angle couplings for small changes in direction. Use manufactured long sweep bends with minimum radius of 48 inch, both horizontally and vertically, at other locations unless otherwise indicated. b. Field bending must be in accordance with NFPA 70 minimum radii requirements, except bends over 45 degrees must be made with minimum radius of 48 inch. Use only equipment specifically designed for material and size involved. Use PVC heating bender for bending PVC conduit.
c. Duct must have maximum of 180 degrees of bends between pull points.
3. Joints: Use solvent-cemented joints in nonmetallic duct and fittings and make watertight in accordance with manufacturer's published instructions. Stagger couplings so those of adjacent duct do not lie in same plane. Couple steel conduits to ducts with adapters designed for this purpose, and encase coupling with minimum 3 inch of concrete for minimum of 12 inch on each side of coupling.
4. Direct-Buried Duct and Duct Bank:
a. Excavate trench bottom to provide firm and uniform support for duct. Comply with requirements in drawings and specifications for preparation of trench bottoms for pipes less than 6 inch in nominal diameter.
b. Width: Excavate trench 12 inch wider than duct on each side. c. Depth: Install top of duct at least 36 inch below finished grade unless otherwise indicated.
d. Set elevation of top of duct bank below frost line.
e. Place minimum 3 inch of sand as bed for duct. Place sand to minimum of 6 inch above top level of duct.
f. Support ducts on duct spacers coordinated with duct size, duct spacing, and outdoor temperature.
g. Spacer Installation: Place spacers close enough to prevent sagging and deforming of duct, with not less than five spacers per 20 ft of duct. Place spacers within 24 inch of duct ends. Stagger spacers approximately 6 inch between tiers. Secure spacers to earth and to ducts to prevent floating during concreting. Tie entire assembly together using fabric straps; do not use tie wires or reinforcing steel that may form conductive or magnetic loops around ducts or duct groups. h. Install manufactured duct elbows for stub-ups, at building entrances, and at changes of direction in duct direction unless otherwise indicated. Encase elbows for stub-up ducts throughout length of elbow.
i. Install manufactured steel elbows for stub-ups, at building entrances, and at changes of direction in duct.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS 260543 - 11 1) Stub-ups to Outdoor Equipment: Extend concrete-encased steel raceway horizontally minimum of 60 inch from edge of base. Install insulated grounding bushings on terminations at equipment.
a) Stub-ups must be minimum 4 inch above finished base and minimum 3 inch from conduit side to edge of base.
2) Stub-ups to Indoor Equipment: Extend concrete-encased steel raceway horizontally on exterior of wall minimum of 60 inch from edge of wall.
Install insulated grounding bushings on terminations at equipment. 3) Stub-ups through interior floors must be minimum 4 inch above finished floor and no less than 3 inch from conduit side to edge of equipment pad or floor slab.
j. After installing first tier of duct, backfill and compact. Start at tie-in point and work toward end of duct run, leaving ducts at end of run free to move with expansion and contraction as temperature changes during this process. Repeat procedure after placing each tier. After placing last tier, hand place backfill to 4 inch over duct and hand tamp. Firmly tamp backfill around ducts to provide maximum supporting strength. Use hand tamper only. After placing controlled backfill over final tier, make final duct connections at end of run and complete backfilling with normal compaction. Comply with requirements in drawings and specifications for installation of backfill materials.
5. Warning Planks: Bury warning planks approximately 12 inch above direct-buried duct, placing them 36 inch o.c. Align planks along width and along centerline of duct or duct bank. Provide additional plank for each 12 inch increment of duct-bank width over nominal 18 inch (450 mm). Space additional planks 12 inch apart, horizontally across width of ducts.
6. Underground-Line Warning Tape: Bury nonconducting underground line specified in Section 260553 "Identification for Electrical Systems" no less than 18 inch above concrete-encased duct and duct banks and approximately 12 inch below grade. Align tape parallel to and within 3 inch of centerline of duct bank. Provide additional warning tape for each 12 inch increment of duct-bank width over nominal 18 inch (. Space additional tapes 12 inch apart, horizontally across width of ducts.
7. Ground ducts and duct banks in accordance with Section 260526 "Grounding and Bonding for Electrical Systems."
3.6 INSTALLATION OF CONCRETE MANHOLES, HANDHOLES, AND BOXES A. Reference Standards:
1. Precast Concrete Handholes: Comply with ASTM C891 unless otherwise indicated.
2. Consult Architect for resolution of conflicting requirements.
B. Special Techniques:
1. Precast Concrete Handholes and Manholes:
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS 260543 - 12 a. Install units level and plumb and with orientation and depth coordinated with connecting duct to minimize bends and deflections required for proper entrances. b. Unless otherwise indicated, support units on level bed of crushed stone or gravel graded from 1 inch (25 mm) sieve to No. 4 (4.75 mm) sieve and compacted to same density as adjacent undisturbed earth.
c. Field-cut openings for conduits in accordance with enclosure manufacturer's published instructions. Cut wall of enclosure with tool designed for material to be cut. Size holes for terminating fittings to be used, and seal around penetrations after fittings are installed.
2. Elevations:
a. Handhole Covers: In paved areas and trafficways, set surface flush with finished grade. Set covers of other handholes 1 inch (25 mm) above finished grade. b. Where indicated, cast handhole cover frame integrally with handhole structure.
3.7 FIELD QUALITY CONTROL
A. Field tests and inspections must be witnessed by Ownerand authorities having jurisdiction.
B. Tests and Inspections:
1. Demonstrate capability and compliance with requirements on completion of installation of underground duct, duct bank, and utility structures.
2. Pull solid aluminum or wood test mandrel through duct to prove joint integrity and adequate bend radii, and test for out-of-round duct. Provide minimum 12 inch long mandrel equal to duct size minus 1/4 inch. If obstructions are indicated, remove obstructions and retest.
3. Test handhole grounding to ensure electrical continuity of grounding and bonding connections. Measure and report ground resistance as specified in Section 260526 "Grounding and Bonding for Electrical Systems."
C. Nonconforming Work:
1. Underground ducts, raceways, and structures will be considered defective if they do not pass tests and inspections.
2. Correct deficiencies and retest as specified above to demonstrate compliance.
D. Field Quality-Control Reports: Collect, assemble, and submit test and inspection reports.
E. Manufacturer Services: Engage factory-authorized service representative to supervise field tests and inspections.
1. Manufacturer's Field Reports for Field Quality-Control Support: Prepare and submit report after each visit by factory-authorized service representative, documenting activities performed at Project site.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS 260543 - 13
3.8 CLEANING
A. Pull leather-washer-type duct cleaner, with graduated washer sizes, through full length of duct until duct cleaner indicates that duct is clear of dirt and debris. Follow with rubber duct swab for final cleaning and to assist in spreading lubricant throughout ducts.
B. Clean internal surfaces of manholes, including sump, and building interiors affected by Work.
1. Sweep floor, removing dirt and debris.
2. Remove foreign material.
END OF SECTION 260543
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS 260543 - 14
THIS PAGE IS INTENTIONALLY LEFT BLANK
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND CABLING 260544 - 1 SECTION 260544
SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND CABLING PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Round sleeves.
2. Foam sealants.
B. Related Requirements:
1. See drawings and specifications for penetration firestopping installed in fire-resistancerated walls, horizontal assemblies, and smoke barriers, with and without penetrating items.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
PART 2 - PRODUCTS
2.1 ROUND SLEEVES
A. PVC Pipe Sleeves:
1. Manufacturers:
a. Allied Conduit.
b. Republic Conduit.
c. Cantex.
d. Or approved equal.
2. PVC-Pipe Sleeves: ASTM D 1785, Schedule 40.
3. Molded-PVC Sleeves: With nailing flange for attaching to wooden forms.
4. Molded-PE or -PP Sleeves: Removable, tapered-cup shaped, and smooth outer surface with nailing flange for attaching to wooden forms.
5. Sleeves for Rectangular Openings:
a. Material: Galvanized sheet steel.
b. Minimum Metal Thickness:
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND CABLING 260544 - 2 c. For sleeve cross-section rectangle perimeter less than 50 inches (1270 mm) and with no side larger than 16 inches (400 mm), thickness shall be 0.052 inch (1.3 mm).
d. For sleeve cross-section rectangle perimeter 50 inches (1270 mm) or more and one or more sides larger than 16 inches (400 mm), thickness shall be 0.138 inch (3.5 mm).
2.2 SLEEVE-SEAL SYSTEMS
A. Description: Modular sealing device, designed for field assembly, to fill annular space between sleeve and raceway or cable.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following or approved equal:
a. Advance Products & Systems
b. CALPICO, Inc
c. Metraflex Company (The)
d. Pipeline Seal and Insulation
e. Proco Products, Inc
2. Sealing Elements: EPDM rubber interlocking links shaped to fit surface of pipe. Include type and number required for pipe material and size of pipe.
3. Pressure Plates: Carbon steel.
4. Connecting Bolts and Nuts: Carbon steel, with corrosion-resistant coating of length required to secure pressure plates to sealing elements.
2.3 SLEEVE-SEAL FITTINGS
A. Description: Manufactured plastic, sleeve-type, waterstop assembly made for embedding in concrete slab or wall. Unit shall have plastic or rubber waterstop collar with center opening to match piping OD.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following or approved equal:
a. HOLDRITE
b. Or approved equal
B. Fittings for conduits in pump wells, in valve boxes or in any other underground box or structure that contains any piping or system other than Electrical systems:
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Cooper
b. Eaton
c. Appleton
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND CABLING 260544 - 3 d. Or approved equal
2. Utilize type EYS (Vertical applications) and type EZS (Horizontal applications). It is acceptable to use one type in lieu of the other only if the manufacturer has listed the box for use in the applicable orientation.
3. In addition, provide Sealing Fittings in the Electrical Enclosure where conduits enter the equipment to avoid allowing gasses to travel into the equipment.
4. Provide and apply sealing compound as recommended by the fitting manufacturer.
2.4 GROUT
A. Description: Nonshrink; recommended for interior and exterior sealing openings in non-firerated walls or floors.
B. Standard: ASTM C 1107/C 1107M, Grade B, post-hardening and volume-adjusting, dry, hydraulic-cement grout.
C. Design Mix: 5000-psi (34.5-MPa), 28-day compressive strength.
D. Packaging: Premixed and factory packaged.
2.5 FOAM SEALANTS
A. Manufacturers:
1. Thomas & Betts.
2. Burndy.
3. 3M.
4. IDEAL.
5. Or approved equal.
B. Performance Criteria:
1. General Characteristics: Multicomponent, liquid elastomers that, when mixed, expand and cure in place to produce a flexible, nonshrinking foam. Foam expansion must not damage cables or crack penetrated structure.
PART 3 - EXECUTION
3.1 INSTALLATION OF SLEEVES FOR NON-FIRE-RATED ELECTRICAL PENETRATIONS A. Comply with NECA 1.
B. Comply with NEMA VE 2 for cable tray and cable penetrations.
C. Sleeves for Conduits Penetrating Above-Grade Non-Fire-Rated Concrete and Masonry-Unit Floors and Walls:
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND CABLING 260544 - 4
1. Interior Penetrations of Non-Fire-Rated Walls and Floors:
a. Seal annular space between sleeve and raceway or cable, using joint sealant appropriate for size, depth, and location of joint. Comply with requirements in Section 079200 "Joint Sealants."
b. Seal space outside of sleeves with mortar or grout. Pack sealing material solidly between sleeve and wall so no voids remain. Tool exposed surfaces smooth; protect material while curing.
2. Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.
3. Size pipe sleeves to provide 1/4-inch (6.4-mm) annular clear space between sleeve and raceway or cable unless sleeve seal is to be installed or unless seismic criteria require different clearance.
4. Install sleeves for wall penetrations unless core-drilled holes or formed openings are used. Install sleeves during erection of walls. Cut sleeves to length for mounting flush with both surfaces of walls. Deburr after cutting.
5. Install sleeves for floor penetrations. Extend sleeves installed in floors 2 inches (50 mm) above finished floor level. Install sleeves during erection of floors.
D. Sleeves for Conduits Penetrating Non-Fire-Rated Wall Assemblies:
1. Use circular metal sleeves unless penetration arrangement requires rectangular sleeved opening.
2. Seal space outside of sleeves with approved joint compound for wall assemblies.
E. Roof-Penetration Sleeves: Seal penetration of individual raceways and cables with flexible boot-type flashing units applied in coordination with roofing work.
F. Aboveground, Exterior-Wall Penetrations: Seal penetrations using steel pipe sleeves and mechanical sleeve-seal systems. Size sleeves to allow for 1 inch annular clear space between pipe and sleeve for installing mechanical sleeve seals.
G. Underground, Exterior-Wall and Floor Penetrations:
1. Install steelpipe sleeves with integral waterstops. Size sleeves to allow for 1 inch annular clear space between raceway or cable and sleeve for installing sleeve-seal system. Install sleeve during construction of floor or wall.
2. Install steel pipe sleeves. Size sleeves to allow for 1 inch annular clear space between raceway or cable and sleeve for installing sleeve-seal system. Grout sleeve into wall or floor opening.
3.2 SLEEVE-SEAL-SYSTEM INSTALLATION
A. Install type and number of sealing elements recommended by manufacturer for raceway or cable material and size. Position raceway or cable in center of sleeve. Assemble mechanical sleeve seals and install in annular space between raceway or cable and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make watertight seal.
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND CABLING 260544 - 5 B. Install EYS and EZY Sealing Fittings for conduits in pump wells, in valve boxes or in any other underground box or structure that contains any piping or system other than Electrical systems.
In addition, provide Sealing Fittings in the Electrical Enclosure where conduits enter the equipment to avoid allowing gasses to travel into the equipment.
3.3 SLEEVE-SEAL-FITTING INSTALLATION
A. Install sleeve-seal fittings in new concrete slabs, structures and boxes as they are constructed.
B. Assemble fitting components of length to be flush with both surfaces of concrete slabs and walls. Position waterstop flange to be centered in concrete slab or wall.
C. Secure nailing flanges to concrete forms.
D. Using grout, seal the space around outside of sleeve-seal fittings.
END OF SECTION 260544
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND CABLING 260544 - 6
THIS PAGE IS INTENTIONALLY LEFT BLANK
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS 260548 - 1 SECTION 260548
VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Post-installed concrete anchors.
B. Related Requirements:
1. Section 260529 "Hangers and Supports for Electrical Systems" for commonly used electrical supports and installation requirements.
1.2 DEFINITIONS
A. OSHPD: Office of Statewide Health Planning and Development (for the State of California owned and regulated medical facilities).
1.3 ACTION SUBMITTALS
A. Product Data:
1. Post-installed concrete anchors.
B. Shop Drawings:
1. Detail fabrication and assembly of equipment bases.
2. Vibration Isolation Base Details: Detail fabrication including anchorages and attachments to structure and to supported equipment. Include adjustable motor bases, rails, and frames for equipment mounting.
3. Show coordination of seismic and wind-load bracing for components with other systems and equipment in the vicinity, including other supports and seismic restraints.
C. Field quality-control reports.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Component Supports:
J.C. Chang & Associates, Inc. City Hall, Community Association Building JCCA No. 24980-1 Emergency Generator Replacement
VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS 260548 - 2
1. Load ratings, features, and applications of reinforcement components must be based on testing standards of qualified testing laboratory.
2.2 POST-INSTALLED CONCRETE ANCHORS
A. Mechanical Anchor Bolts:
1. Manufacturers:
a. Hilti.
b. Dottie.
c. Metallics.
d. Power Fasteners.
e. Or approved equal.
2. Drilled-in and stud-wedge or female-wedge type in stainless steel for exterior applications. Select anchor bolts with strength for anchor and as tested according to ASTM E488/E488M. See detail #1 on sheets E3.4 and E3.5 of electrical drawings.
B. Provide post-installed concrete anchors that have been prequalified for use in seismic and windload applications.
1. Prequalify post-installed anchors in concrete in accordance with ACI 355.2 or other approved qualification testing procedures.
2. Prequalify post-installed anchors in masonry in accordance with approved qualification procedures.
2.3 SOURCE QUALITY CONTROL
A. Product Data: Prepare and submit catalog cuts, brochures, and performance data illustrating size, physical appearance, and other characteristics of product.
1. Annotate types and sizes of seismic restraints and accessories, complete with listing markings or report numbers and load rating in tension and compression as evaluated by UL product listing, FM Approvals, and an agency acceptable to authorities having jurisdiction.
2. Annotate to indicate application of each product submitted and compliance with requirements.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine areas and equipment to receive seismic and wind-load control devices for compliance with requirements for installation tolerances and other conditions affecting performance of the Work.