116
LU SUBMITTAL 05 JULY 05, 2023
ON-SITE LIGHTING SITE PLAN
Attachment 6
117
LU SUBMITTAL 05 JULY 05, 2023
ON-SITE PHOTOMETRIC PLAN
Attachment 6
118
LU SUBMITTAL 05 JULY 05, 2023
EV
EV
EV
AL
56 BIKES
DN
ELEV
OFFICE PARKING
ELEV
BIKE PARKING
UTILITY
MAINTENANCE
ELECTRICAL
TRASH
165' - 0"
85 STALLS
RAMP
RAMP
59'
58'
60'
58'
LOBBY
ELEV
ELECTRICAL TRANSFORMER
RR
OFFICE
BOH
PACKAGE
LOBBY
MAIL
PARLOR
FIRE CONTROL
BOILER
TOOLS
20' - 0"
5' - 6"
18' - 0" 24' - 0" 18' - 0"
1' - 6"
18' - 0" 24' - 0" 18' - 0"
24' - 0"
24' - 0"
57' - 0"
17' - 0" 20' - 0" 20' - 0"
69' - 6" 50' - 6" 69' - 6" 50' - 6" 109' - 6"
349' - 6"
3335 303132 28293637
8385 808182
4644 494847
41 40
777879
525150
747576
555453
26 585756 616059 6362
27 52 11 141312
717273 686970 6667
2425 23
42 10
43 17
18 1 674 9
22 21 20
16 19
39 38
84 45
34 15
64 65
3 TRASH
8 3 BED TOWNHOME 3 BED TOWNHOME 2 BED TOWNHOME 3 BED TOWNHOME 3 BED TOWNHOME 3 BED TOWNHOME2 BED TOWNHOME2 BED TOWNHOME2 BED TOWNHOME 3 BED TOWNHOME
3 BED TOWNHOME
3 BED TOWNHOME
160' - 0" 11' - 0" 77' - 6"
2' - 6"
2' - 6"
5' - 6"
9' -
6"
3' - 6"
UP
LOADING ZONE
OFFICE PARKING
ENTRY
RESIDENTIAL PARKING
ENTRY
10' - 0" SETBACK
10' - 0" SETBACK
22' - 0" SETBACK
10' - 0" SETBACK
15' - 0" SETBACK
120' - 0"
62' - 6"20' - 0"82' - 6"
248' - 0"
78 ' - 6"
GROUND STORY
MARCH 18, 2022 LU37
170 SAN ZENO WAY
SUNNYVALE, CA 94086
1/16" = 1'-0"LU37
1 GROUND STORY
N
DAVIS DOOR VERTICAL LIFT GATE
Combines security and reliability in high-traffic environments. The gate’s aluminum panel can be a visual upgrade to any multi-family or commercial building. Designed for over 1 million cycle usage with a 5 year warranty.
Operator
Standard - Heavy duty gate operator with an opening speed of 12-inch per second.
Upgrade - Direct drive operator with an opening speed of 24-inch per second.
Safety Features
72-inch tall monitored light curtains revese the door when an oibject is detected.
Monitored contact sensing edge on the bottom of the gate.
Laser base curtain securely protects the outside of the door
2.2 ALUMINUM VERTICAL LIFT GATE
A. Aluminum Vertical Lift Gate: Davis Door DDS-WCVLG Units shall have the following characteristics:
1. Door Assembly: Fabricate vertical lift panels consisting of welded aluminum tube frame with overlay of ¾” x .125 expanded aluminum sheeting or .050 solid aluminum sheeting. a. Aluminum tube: ASTM B 221 6063-T52
b. Flattened expanded aluminum sheet, 5005-H34, ¾” x .125 or .050 solid aluminum sheeting c. Welded construction frame, mechanically attached expanded or solid sheet d. Mill finish on aluminum
e. Steel shapes, plates and bars: ASTM A 36
2. Counterbalance system: Counterbalance door by means of roller chains, sprockets, and steel counter- weights traveling in one common galvanized steel counterweight tower.
This system uses heavy duty, 4 bolt
cast flange bearings and solid keyed stress proof shafts.
3. Steel structural towers: 14 gauge hot dipped galvanized ASTM A924
4. Bottom of door: Manufacturers standard design
a. Miller Edge, 2 wire, reversing electric sensing edge, bottom seal combination
5. Finish and Color:
a. Aluminum to be natural mill finished
b. Powder Coating Finish: Color as selected by Architect from manufacturer’s standard colors.
6. Windload Design: Provide to meet the Design/Performance requirements specified.
7. Locking:
a. Panel locks to prevent lifting and bottom arrester/lifting catches.
8. Track: extruded aluminum to minimize contact with continuous UHMW guide strips, eliminating metal to metal contact, reducing noise and vibration. They will allow the door to breakaway in the event of impact with a vehicle.
9. Electric Motor Operation:
a. Industrial duty All-O-Matic SL100DC Motor System
- Opening speed: 12” per second with soft start and stop b. Micanan Titan Series Operator
- Opening speed: 24” per second with soft start and stop VIEW 2
IS SHOWN ABOVE
FASCIA PANEL
GATE PANEL
FLOOR
100"
(8' 4")
OPENING
HEIGHT
30"
(2' 6")
TBD
DAVIS DOOR
2021 Sou
Sea
9 1-800
FAX: 20
EMAIL: info@
280649
JOB #
HYDE SQUAR
JOB NAME
OWNER / PROPER
DAVIS DOOR SER
ARCHITECT
¾” : 1'- 0"
SCALE
JENSEN DAV
ORDERED BY
KEVIN PURDI
DRAWN BY
REVISED 5 / 1
DATE
HYDE SQUAR
GATE REV
COMPUTER FILE
DRAWING # 3
COPYRIGHT 2022 THE INFORMATION PROVIDED ON THIS DOCUMENT IS THE PROPERTY OF DAVIS DOOR SERVICE, INC., ANY REPRODUCTION OR USE OF THIS DESIGN OR CONCEPT WITHOUT WRITTEN PERMISSION IS PROHIBITED.
INSIDE LOOKING
OUT
VERTIC
GA
271 ¼”
(22' 7 ¼”)
OPENING WIDTH
293”
(24' 5”)
TOTAL WIDTH
17 ¾”4"
ALL DIMENSIONS WILL BE FIELD VERIFIED
PRIOR TO CONSTRUCTION
130"
(10' 10")
TOTAL
HEIGHT
130"
(10' 10")
TOTAL
HEIGHT
COLUMN
WALL
CEILING / INSULATION
THE BLUE DOTTED LINES REPRESENT
THE LOCATIONS OF THE #40 NP
LIFTING CHAINS
TYP.
NOTE : THE GREEN DOTTED LINE
REPRESENTS THE LOCATION OF THE GATE
PANELS IN THE OPEN POSITION
TYP.
SENSING
EDGE
NOTE : ¼” X 1" GR8 HEX
FLANGE BOLTS YELLOW
ZINC (FFS324) WILL BE
USED TO ATTACH THE
WEIGHT BOX COVERS TO
THE TOWER
TYP.
ALUMINUM WEIGHT BOX
COVER
(SAME BOTH SIDES)
TYP.
ALUMINUM
FLASHING
TYP.
100"
(8' 4")
OPENING
HEIGHT
DOOR SAFETY LOCK
(HVD470)
6 – ¼” X 1" KINNEAR
SCREWS PER LOCK
(FFS435)
TYP.
17 ¾”4"
WEIGHT
BOX
VIEW 1
IS SHOWN TO
THE RIGHT
271 ¼”
(22' 7 ¼”)
OPENING WIDTH
PANELFASCIA
GATE PANEL
GATE PANEL
GATE PANEL
GATE PANEL
GATE PANEL
DDS ALUMINUM
VERTICAL LIFT
GATE TRACK
TYP.
½” UHMW
GUIDE
TYP.
INSIDE
FACE
1 ½”
TYP.
25 ½”
3" X 4" X ¼”
ALUMINUM ANGLE
BRACKET
TYP.
ALUMINUM
FLASHING / COVER
WALL
COLUMN
EXISTING 6" X 6"
STEEL TUBE
TYP.
ALUMINUM
FLASHING
TYP.
6"
12"
4"
10"
INSIDE
FACE
2”
OVERLAP
TYP.
DOOR SAFETY LOCK
(HVD470)
6 – ¼” X 1" KINNEAR
SCREWS PER LOCK
(FFS435)
TYP.
CEILING / INSULATION
GATE PANEL
GATE PANEL
GATE PANEL
GATE PANEL
WALL
130"
(10' 10")
TOTAL
HEIGHT
EXISTING STEEL TUBE
NOTES:
__ 1 – BEA FALCON XL MOTION SENSOR
(OSE516)
__ 1 – RH NON-MONITORED ME-123
MILLER EDGE WITH A CA3 ALUMINUM
RETAINER AT 22' 6 ¼”
__ 1 – MULTI-CODE REVERSE EDGE
TRANSMITTER (ORC340)
__ 1 – MULTI-CODE RECEIVER 1099-50
(ORC315)
__ 1 – 3 BUTTON STATION 3-PBS
(OPB012)
1 2
FASCIA
PANEL
GATE
PANEL #5
GATE
PANEL #4
GATE
PANEL #3
GATE
PANEL #2
GATE
PANEL #1
NOTES:
* GATE WILL BE MIL
INCLUDE THE FOLLO
__ 1 – MICANAN TITA
OPERATOR (208 VAC
__ 1 – MICANAN TITA
230V / 460V PRIMAR
__ 1 – SET OF MILLE
MONITORED LIGHT
__ 1 – PR. LIGHT CU
BRACKETS (OPH178
__ 1 – BEA LZR-i30 L
(OSE525)
__ 1 – TRC / MEAN W
DIN RAIL POWER SU
MICANAN TITAN
SERIES OPERATOR
(208 VAC 1 PH)
TYP.
MICANAN TITAN
SERIES OPERATOR
(208 VAC 1 PH)
TYP.
*DIMENSIONS FOR REFERENCE ONLY. COORDINATE OPENINGS WITH ACTUAL PROJECT PARAMETERS
GARAGE DOOR DESIGN
Attachment 6
119
LU SUBMITTAL 05 JULY 05, 2023
BICYCLE RACKS
Attachment 6
120
LU SUBMITTAL 05 JULY 05, 2023
Benefits Of Cal Stor-N-Lock Storage Lockers
Security
Cal Stor-N-Lock storage lockers are the ideal solution to securing and organizing your valuable possessions. Wire mesh provides security, while permitting proper lighting and ventilation.
Simplicity
Cal Stor-N-Lock lockers can be erected easily with simple hand tools, along with our installation manual. Modular design makes future relocation or reconfiguration fast and efficient.
Cal Wire
Wire Mesh Products Since 1948
Cal Stor-N-Lock
Welded Wire Storage Lockers
Applications:
Personnel Storage Military Bases
Gym Equipment Retirement Communities
Post Offices Apartment Facilities
Parking Garages Schools
Colocation Areas Any Of Y our Ideas!
Also Available:
Special Finishes Custom Sizes
Ceiling Panels Headerless Gates
Double Doors Custom Colors
Handrail Infill Panels Window Guards
LOCKABLE STORAGE
UNIT TYPE 1 LOCKABLE STORAGE:
3’ x 8’ x 9’ = 216 CUFT - PRODUCT REFERENCED
IN-UNIT TYPE 1 STORAGE IN STUDIO/1BED UNITS
UNIT TYPE 2 LOCKABLE STORAGE:
4’-6” x 8’ x 9’ = 324 CUFT - PRODUCT REFERENCED
IN-UNIT TYPE 2 STORAGE IN 2BED & 3 BED UNITS
COUNT COUNT200 CUFT STORAGE UNITS
STORAGE UNIT SUMMARY
300 CUFT STORAGE UNITS
112
43 59
14 UNIT TYPE 1 & 2 LOCKABLE STORAGEUNIT TYPE 1 LOCKABLE STORAGE UNIT TYPE 2 LOCKABLE STORAGE
UNIT QTY
70 70
73 73
155 155
155
155STUDIOS & 1 BEDROOMS:
2 & 3 BEDROOMS:
200 CUFT PER STUDIO & 1 BEDROOM UNITS
TOTAL 200 CUFT MINIMUM PER STUDIO & 1 BEDROOM UNITS
300 CUFT PER UNIT FOR ALL OTHERS
TOTAL 300 CUFT PER UNIT FOR ALL OTHERS
REQUIRED STORAGE:STORAGE SIZE REQUIREMENTSUNIT TYPES PROVIDED STORAGE:
BEDRO
OM 1
BATH 1
STORAGE
BEDROOM
2 LIVING
DINING
KITCHEN
BALCO
NY
BATH 2
CLOSET
10' - 6" 24' - 4"
35' - 7"
6' - 4"
8' - 0"CLOSET
W/D
IN-UNIT STORAGE MINIMUM DIMENSIONS
3’ - 0”
9FT HEIGHT, TYP.
8’ - 0”
Attachment 6
121
LU SUBMITTAL 05 JULY 05, 2023
1" = 60'-0"LU116
1 GROUND STORY STORAGE UNIT KEY
1" = 60'-0"LU116
2 3RD STORY STORAGE UNIT KEY
1" = 60'-0"LU116
3 4TH STORY STORAGE UNIT KEY
1" = 60'-0"LU116
4 5TH STORY STORAGE UNIT KEY
1" = 60'-0"LU116
5 8TH STORY STORAGE UNIT KEY
1" = 60'-0"LU116
6 6TH & 7TH STORY STORAGE UNIT KEY
1" = 60'-0"LU116
1 GROUND STORY STORAGE UNIT KEY
1" = 60'-0"LU116
2 3RD STORY STORAGE UNIT KEY
1" = 60'-0"LU116
4 5TH STORY STORAGE UNIT KEY
1" = 60'-0"LU116
6 6TH & 7TH STORY STORAGE UNIT KEY
STORAGE IN UNIT PLANS
1" = 60'-0"LU116
1 GROUND STORY STORAGE UNIT KEY
1" = 60'-0"LU116
2 3RD STORY STORAGE UNIT KEY
1" = 60'-0"LU116
3 4TH STORY STORAGE UNIT KEY
1" = 60'-0"LU116
4 5TH STORY STORAGE UNIT KEY
1" = 60'-0"LU116
5 8TH STORY STORAGE UNIT KEY
1" = 60'-0"LU116
6 6TH & 7TH STORY STORAGE UNIT KEY
1" = 60'-0"16
GROUND STORY STORAGE UNIT KEY
1" = 60'-0"16
3RD STORY STORAGE UNIT KEY
1" = 60'-0"16
4TH STORY STORAGE UNIT KEY
1" = 60'-0"LU116
4 5TH STORY STORAGE UNIT KEY
1" = 60'-0"LU116
5 8TH STORY STORAGE UNIT KEY
1" = 60'-0"LU116
6 6TH & 7TH STORY STORAGE UNIT KEY
1" = 60'-0"16
GROUND STORY STORAGE UNIT KEY
1" = 60'-0"16
3RD STORY STORAGE UNIT KEY
1" = 60'-0"LU116
4 5TH STORY STORAGE UNIT KEY
1" = 60'-0"LU116
6 6TH & 7TH STORY STORAGE UNIT KEY
STORAGE IN UNIT PLANS
1" = 60'-0"16
GROUND STORY STORAGE UNIT KEY
1" = 60'-0"16
3RD STORY STORAGE UNIT KEY
1" = 60'-0"16
4TH STORY STORAGE UNIT KEY
1" = 60'-0"LU116
4 5TH STORY STORAGE UNIT KEY
1" = 60'-0"LU116
5 8TH STORY STORAGE UNIT KEY
1" = 60'-0"LU116
6 6TH & 7TH STORY STORAGE UNIT KEY
6TH & 7TH STORY
5TH STORYGROUND STORY
3RD STORY
TOTAL IN UNIT STORAGE COUNT
4TH STORY 8TH STORY
2 BED+ QTY: 11
2 BED+ QTY: 92 BED+ QTY: 5
2 BED+ QTY: 4
2 BED+ QTY: 9 2 BED+ QTY: 10
STUDIO/1 BED QTY: 9
STUDIO/1 BED QTY: 9STUDIO/1 BED QTY: 0
STUDIO/1 BED QTY: 0
STUDIO/1 BED QTY: 9 STUDIO/1 BED QTY: 7
IN-UNIT STORAGE STORY PLANS
IN-UNIT 300CUFT MIN STORAGE IN 2BED & 3 BED UNITS
TOTAL UNITS WITH IN-UNIT STORAGE
59 102
IN-UNIT 200 CUFT MIN STORAGE IN STUDIO/1BED UNITS43
Attachment 6
122
LU SUBMITTAL 05 JULY 05, 2023
DWREF
W/D
W/D
DW
W/D
DW
W/D
W/D
W/D
W/D
W/D
UP W/D
DNSTORAGE
8' - 0"
3' - 11"
STORAGE
6' - 0"
8' - 0"
STORAGE
6' - 5"
8' - 7"
STORAGE
12' - 5"
4' - 0"
STORAGE
4' - 0"
4' - 7"
3' - 0"
5' - 0"
3' - 1"
9' - 3"
5' - 4"
4' - 3"
STORAGE
STORAGE
5' - 8 1/2"8' - 1"
STORAGE
6' - 5"
9' - 8"
STORAGE UNIT KEY
MARCH 02, 2023 LU117
170 SAN ZENO WAY
SUNNYVALE, CA 94086
1/8" = 1'-0"LU117
2 UNIT - 1 BED B 282 CUFT
1/8" = 1'-0"LU117
3 UNIT - 1 BED C 432 CUFT
1/8" = 1'-0"LU117
4 UNIT - 1 BED E 495 CUFT
1/8" = 1'-0"LU117
5 UNIT - 2 BED A 447 CUFT
1/8" = 1'-0"LU117
7 UNIT - 2 BED C 300 CUFT
1/8" = 1'-0"LU117
8 UNIT - 2 BED D 342 CUFT
1/8" = 1'-0"LU117
9 UNIT - 2 BED E 415 CUFT
1/8" = 1'-0"LU117
6 TOWNHOME 3BED TYP KEY
1/8" = 1'-0"LU117
10 TOWNHOME 2BED TYP KEY 2ND STORY 557 CUFT
DWREF
W/D
W/D
DW
W/D
DW
W/D
W/D
W/D
W/D
W/D
UP W/D
DNSTORAGE
8' - 0"
3' - 11"
STORAGE
6' - 0"
8' - 0"
STORAGE
6' - 5"
8' - 7"
STORAGE
12' - 5"
4' - 0"
STORAGE
4' - 0"
4' - 7"
3' - 0"
5' - 0"
3' - 1"
9' - 3"
5' - 4"
4' - 3"
STORAGE
STORAGE
5' - 8 1/2"8' - 1"
STORAGE
6' - 5"
9' - 8"
STORAGE UNIT KEY
MARCH 02, 2023 LU117
170 SAN ZENO WAY
SUNNYVALE, CA 94086
1/8" = 1'-0"LU117
2 UNIT - 1 BED B 282 CUFT
1/8" = 1'-0"LU117
3 UNIT - 1 BED C 432 CUFT
1/8" = 1'-0"LU117
4 UNIT - 1 BED E 495 CUFT
1/8" = 1'-0"LU117
5 UNIT - 2 BED A 447 CUFT
1/8" = 1'-0"LU117
7 UNIT - 2 BED C 300 CUFT
1/8" = 1'-0"LU117
8 UNIT - 2 BED D 342 CUFT
1/8" = 1'-0"LU117
9 UNIT - 2 BED E 415 CUFT
1/8" = 1'-0"LU117
6 TOWNHOME 3BED TYP KEY
1/8" = 1'-0"LU117
10 TOWNHOME 2BED TYP KEY 2ND STORY 557 CUFT
DWREF
W/D
W/D
DW
W/D
DW
W/D
W/D
W/D
W/D
W/D
UP W/D
DNSTORAGE
8' - 0"
3' - 11"
STORAGE
6' - 0"
8' - 0"
STORAGE
6' - 5"
8' - 7"
STORAGE
12' - 5"
4' - 0"
STORAGE
4' - 0"
4' - 7"
3' - 0"
5' - 0"
3' - 1"
9' - 3"
5' - 4"
4' - 3"
STORAGE
STORAGE
5' - 8 1/2"8' - 1"
STORAGE
6' - 5"
9' - 8"
STORAGE UNIT KEY
MARCH 02, 2023 LU117
170 SAN ZENO WAY
SUNNYVALE, CA 94086
1/8" = 1'-0"LU117
2 UNIT - 1 BED B 282 CUFT
1/8" = 1'-0"LU117
3 UNIT - 1 BED C 432 CUFT
1/8" = 1'-0"LU117
4 UNIT - 1 BED E 495 CUFT
1/8" = 1'-0"LU117
5 UNIT - 2 BED A 447 CUFT
1/8" = 1'-0"LU117
7 UNIT - 2 BED C 300 CUFT
1/8" = 1'-0"LU117
8 UNIT - 2 BED D 342 CUFT
1/8" = 1'-0"LU117
9 UNIT - 2 BED E 415 CUFT
1/8" = 1'-0"LU117
6 TOWNHOME 3BED TYP KEY
1/8" = 1'-0"LU117
10 TOWNHOME 2BED TYP KEY 2ND STORY 557 CUFT
DWREF
W/D
W/D
DW
W/D
DW
W/D
W/D
W/D
W/D
W/D
UP W/D
DNSTORAGE
8' - 0"
3' - 11"
STORAGE
6' - 0"
8' - 0"
STORAGE
6' - 5"
8' - 7"
STORAGE
12' - 5"
4' - 0"
STORAGE
4' - 0"
4' - 7"
3' - 0"
5' - 0"
3' - 1"
9' - 3"
5' - 4"
4' - 3"
STORAGE
STORAGE
5' - 8 1/2"8' - 1"
STORAGE
6' - 5"
9' - 8"
STORAGE UNIT KEY
MARCH 02, 2023 LU117
170 SAN ZENO WAY
SUNNYVALE, CA 94086
1/8" = 1'-0"LU117
2 UNIT - 1 BED B 282 CUFT
1/8" = 1'-0"LU117
3 UNIT - 1 BED C 432 CUFT
1/8" = 1'-0"LU117
4 UNIT - 1 BED E 495 CUFT
1/8" = 1'-0"LU117
5 UNIT - 2 BED A 447 CUFT
1/8" = 1'-0"LU117
7 UNIT - 2 BED C 300 CUFT
1/8" = 1'-0"LU117
8 UNIT - 2 BED D 342 CUFT
1/8" = 1'-0"LU117
9 UNIT - 2 BED E 415 CUFT
1/8" = 1'-0"LU117
6 TOWNHOME 3BED TYP KEY
1/8" = 1'-0"LU117
10 TOWNHOME 2BED TYP KEY 2ND STORY 557 CUFT
DWREF
W/D
W/D
DW
W/D
DW
W/D
W/D
W/D
W/D
W/D
UP W/D
DNSTORAGE
8' - 0"
3' - 11"
STORAGE
6' - 0"
8' - 0"
STORAGE
6' - 5"
8' - 7"
STORAGE
12' - 5"
4' - 0"
STORAGE
4' - 0"
4' - 7"
3' - 0"
5' - 0"
3' - 1"
9' - 3"
5' - 4"
4' - 3"
STORAGE
STORAGE
5' - 8 1/2"8' - 1"
STORAGE
6' - 5"
9' - 8"
STORAGE UNIT KEY
MARCH 02, 2023 LU117
170 SAN ZENO WAY
SUNNYVALE, CA 94086
1/8" = 1'-0"LU117
2 UNIT - 1 BED B 282 CUFT
1/8" = 1'-0"LU117
3 UNIT - 1 BED C 432 CUFT
1/8" = 1'-0"LU117
4 UNIT - 1 BED E 495 CUFT
1/8" = 1'-0"LU117
5 UNIT - 2 BED A 447 CUFT
1/8" = 1'-0"LU117
7 UNIT - 2 BED C 300 CUFT
1/8" = 1'-0"LU117
8 UNIT - 2 BED D 342 CUFT
1/8" = 1'-0"LU117
9 UNIT - 2 BED E 415 CUFT
1/8" = 1'-0"LU117
6 TOWNHOME 3BED TYP KEY
1/8" = 1'-0"LU117
10 TOWNHOME 2BED TYP KEY 2ND STORY 557 CUFT
DWREF
W/D
W/D
DW
W/D
DW
W/D
W/D
W/D
W/D
W/D
UP W/D
DNSTORAGE
8' - 0"
3' - 11"
STORAGE
6' - 0"
8' - 0"
STORAGE
6' - 5"
8' - 7"
STORAGE
12' - 5"
4' - 0"
STORAGE
4' - 0"
4' - 7"
3' - 0"
5' - 0"
3' - 1"
9' - 3"
5' - 4"
4' - 3"
STORAGE
STORAGE
5' - 8 1/2"8' - 1"
STORAGE
6' - 5"
9' - 8"
STORAGE UNIT KEY
MARCH 02, 2023 LU117
170 SAN ZENO WAY
SUNNYVALE, CA 94086
1/8" = 1'-0"LU117
2 UNIT - 1 BED B 282 CUFT
1/8" = 1'-0"LU117
3 UNIT - 1 BED C 432 CUFT
1/8" = 1'-0"LU117
4 UNIT - 1 BED E 495 CUFT
1/8" = 1'-0"LU117
5 UNIT - 2 BED A 447 CUFT
1/8" = 1'-0"LU117
7 UNIT - 2 BED C 300 CUFT
1/8" = 1'-0"LU117
8 UNIT - 2 BED D 342 CUFT
1/8" = 1'-0"LU117
9 UNIT - 2 BED E 415 CUFT
1/8" = 1'-0"LU117
6 TOWNHOME 3BED TYP KEY
1/8" = 1'-0"LU117
10 TOWNHOME 2BED TYP KEY 2ND STORY 557 CUFT
IN-UNIT STORAGE TYPICAL FLOOR PLANS
2 BED UNIT
1 BED UNIT
1 BED UNIT
TYPICAL STORY
GROUND STORY
1 BED UNIT
2 BED UNIT
2 BED UNIT
2 BED UNIT
3 BED TOWNHOME UNIT
447 CUFT
495 CUFT
282 CUFT
432 CUFT 342 CUFT
557 CUFT415 CUFT
300 CUFT
STORAGE IN UNIT PLANS
MARCH 02, 2023 LU116
170 SAN ZENO WAY
SUNNYVALE, CA 94086
1" = 60'-0"LU116
1 GROUND STORY STORAGE UNIT KEY
1" = 60'-0"LU116
2 3RD STORY STORAGE UNIT KEY
1" = 60'-0"LU116
3 4TH STORY STORAGE UNIT KEY
1" = 60'-0"LU116
4 5TH STORY STORAGE UNIT KEY
1" = 60'-0"LU116
5 8TH STORY STORAGE UNIT KEY
1" = 60'-0"LU116
6 6TH & 7TH STORY STORAGE UNIT KEY
1" = 60'-0"LU116
1 GROUND STORY STORAGE UNIT KEY
1" = 60'-0"LU116
2 3RD STORY STORAGE UNIT KEY
1" = 60'-0"LU116
3 4TH STORY STORAGE UNIT KEY
6TH & 7TH STORY
3 BED TOWNHOME
NG
N
G
KITCHEN
3' - 3"
BEDRO
OM 1
BATH 1
STORAGE
BEDROOM
2 LIVING
DINING
KITCHEN
BALCO
NY
BATH 2
CLOSET
5' - 0"24' - 11"
30' - 8"
10' - 6" 24' - 4"
35' - 7"
6' - 4"
8' - 0"CLOSET
W/D
IN-UNIT STORAGE MINIMUM DIMENSIONS
3’ - 0”
9FT HEIGHT, TYP.
8’ - 0”
Attachment 6
123
LU SUBMITTAL 05 JULY 05, 2023
2' - 9"
1/4" / 1'-0"1/4" / 1'-0"
2' - 6"
5' - 10"
6' - 0"
9' - 0"
ROOF DIAGRAM
MAY 24, 2023 LU123
170 SAN ZENO WAY
SUNNYVALE, CA 94086
ROOFTOP VISIBLITY
NORTH - SOUTH LINE OF SITE
MECHANICAL EQUIPMENT HEIGHT
EAST - WEST LINE OF SITE
PARAPET
HEAT
PUMP
HEAT
PUMP
CORRIDOR
SUPPLY FAN
MECHANICAL EQUIPMENT ABOVE PARAPET TO BE
PAINTED TO MATCH PARAPET
LAWRENCE EXPY
KIFER RD
SAN ZENO WAY
SOLAR PANELS - 5 KW PV SYSTEM SOLAR PANELS - 5 KW PV SYSTEM
MECHANICAL EQUIPMENT ABOVE PARAPET TO BE
PAINTED TO MATCH PARAPET
MECHANICAL EQUIPMENT ABOVE PARAPET TO BE
PAINTED TO MATCH PARAPET
2 4
3 5
1 Attachment 6
124
LU SUBMITTAL 05 JULY 05, 2023
29 1/2"
8 1/2"5 1/2"8 1/2"
OFFSET
12"
5" 2" 2"
BUILDING CORNICE
CORNICE DETAIL AT WALL SHIFT
CORNICE DETAIL AT PARAPET1
2 2
1 Attachment 6
125
LU SUBMITTAL 05 JULY 05, 2023
0' - 8"
3' - 6"
3' - 6"
RAIL DETAILS
JUNE 30, 2022 LU48
170 SAN ZENO WAY
SUNNYVALE, CA 94086
0' - 8"
3' - 6"
3' - 6"
RAIL DETAILS
JUNE 30, 2022 LU48
170 SAN ZENO WAY
SUNNYVALE, CA 94086
0' - 8"
3' - 6"
RAIL DETAILS
JUNE 30, 2022 LU48
170 SAN ZENO WAY
SUNNYVALE, CA 94086
9"4 1/2"1 1/2"
9"4 1/2"1 1/2"
0' - 8"
3' - 6"
3' - 6"
RAIL DETAILS
JUNE 30, 2022 LU48
170 SAN ZENO WAY
SUNNYVALE, CA 94086
GUARDRAIL DETAILS
GUARD RAIL DETAIL1
CORNICE DETAIL AT WALL SHIFT2
STAINLESS STEEL
INFILL PANEL
STAINLESS STEEL
CHANNEL
STAINLESS STEEL
GUARDRAIL FRAME
CONCRETE PAVER
WITH PEDESTAL SYSTEM
CONCRETE PAVER
WITH PEDESTAL SYSTEM
THIN BRICK CORNICE
GUARDRAIL, RAIL SHOE
HSS BASE FRAME TO MOUNT
GUARDRAIL SYSTEM
GLASS GUARDRAIL
ALUMINUM GUARDRAIL
TOP CAP
KNIFE PLATE WITH
ANCHOR BOLTS
2 1
Attachment 6
126
LU SUBMITTAL 05 JULY 05, 2023
VISUAL VARIATION AT TEXTURED BRICK - BASE BRICK TEXTURE PROFILE
BRICK TEXTURE EXAMPLE
BASE - BRICK TEXTURE
2.89 BASE: FACE BRICK TEXTURE
WILL PROVIDE ADDITIONAL
VISUAL VARIATION CREATED BY
NATURAL LIGHT THROUGHOUT
THE DAY.
SOLDIER COURSE BRICK
CORNICE BETWEEN BASE &
MIDDLE ELEMENTS.
MIDDLE: THIN BRICK
Attachment 6
127
LU SUBMITTAL 05 JULY 05, 2023
1/2"
2 1/2"
MAX ALLOWABLE LENGTH 18'-0"
VARIES
STUCCO
JULY 20, 2022 LU49
170 SAN ZENO WAY
SUNNYVALE, CA 94086
STUCCO OVER METAL LATH
WATERPROOFING SYSTEM
STUCCO CONTROL JOINT
GYPSUM SHEATHING
CONTROL JOINT DETAIL
Attachment 6
128
LU SUBMITTAL 05 JULY 05, 2023
WND R.O.
WRB
THIN BRICK OVER SCR
BROWN COAT OVER M
(1) LAYER OF GLASS M
SHEATHING
NAIL FLANGE WINDOW
SEALANT
WINDOW SILL DETAIL, TYP
GRID
WND R.O.
WRB
22g FLASHING WITH HEMMED EDGE
NAIL FLANGE WINDOW
THIN BRICK OVER SCRATCH AND
BROWN COAT OVER METAL LATH
(1) LAYER OF GLASS MAT
SHEATHING
OPEN JOINT
WINDOW HEAD DETAIL, TYP
3" MIN
WND R.O.
WRB
THIN BRICK OVER SCRATCH AND
BROWN COAT OVER METAL LATH
(1) LAYER OF GLASS MAT
SHEATHING
NAIL FLANGE WINDOW
SEALANT
GRID
WND R.O.
3" MIN
NAIL FLANGE WINDOW
WRB
THIN BRICK OVER SCRATCH AND
BROWN COAT OVER METAL LATH
(1) LAYER OF GLASS MAT SHEATHING
WND R.O.
WRB
THIN BRICK OVER SCRATCH AND
BROWN COAT OVER METAL LATH
(1) LAYER OF GLASS MAT
SHEATHING
NAIL FLANGE WINDOW
SEALANT
GRID
WND R.O.
3" MIN
NAIL FLANGE WINDOW
WRB
THIN BRICK OVER SCRATCH AND
BROWN COAT OVER METAL LATH
(1) LAYER OF GLASS MAT SHEATHING
WINDOW DETAILS - THIN BRICK
Attachment 6
129
LU SUBMITTAL 05 JULY 05, 2023
EXHIBITS
Attachment 6
130
LU SUBMITTAL 05 JULY 05, 2023
SUNNYVALE GATEWAY SIGN - LAWRENCE STATION
9"
A1 - FRONT VIEW
SCALE: 3/8”=1’0”1 A1 - BACK VIEW
SCALE: 3/8”=1’0”2
A1 - TOP VIEW
SCALE: 3/8”=1’0”4
A1- SIDE VIEW
SCALE: 3/8”=1’0”3
Powder coated aluminum sign panel
Color to match to RGB Color (63,68,109)
1” thick push through frosted acrylic logo,
internally illuminated on face and returns
Green color to match Sunnyvale Green
1” thick push through frosted acrylic letters,
internally illuminated on face and returns
1” thick push through frosted acrylic letters,
internally illuminated on face and returns
Font: Avenir Medium
Brushed aluminum sign cabinet
M
//
COMMERCIAL
STREET
MATCHLINE ~SEE ABOVE
KIFER ROAD
KIFER ROAD - STA 24+00 TO STA 29+00
SCALE: 1" = 20'
3"
6"
8"8" 2'-8"
8"2'-5"1'-8"
1'-6"5"
4'-0"
3'-6"
8'-2"1'-8"
3"
14'-6"1'-0"
16'-0"
1'-0"
3"
4'-0"
3'-6"
3"
1'-0"
16'-0"
EXPERIENCE DESIGN
C opyright © 2021 Hellmuth, Obata & Kassabaum, Inc. ORIGINAL DRAWING IS 11 X 17. DO NOT SCALE CONTENTS OF THIS DRAWING.
No.
1 2
3 DESCRIPTION DATEPROJECT INFORMATION
Scope: Signage
Phase: Schematic Design
Issued For: Client review
ISI INTUITIVE SURGICAL HQ
Intuitive Surgical - Sunnyvale
Project Number:
Date: 06/22/2022
SUNNYVALE GATEWAY SIGNSUNNYVALE DIRECTIONAL SIGN TYPE A Attachment 6
131
LU SUBMITTAL 05 JULY 05, 2023
TRASH EXHIBIT - TRASH ENCLOSURE
ROOF PLAN VIEW
EAST / WEST ELEVATIONSOUTH / FRONT ELEVATION
FRONT ELEVATION VIEW STREET VIEW
STEEL GATE WITH THERMORY
WOOD BOARDS
WIRE CABLE
FOR CLIMBING PLANTS
4X4 WOOD BOARDS OVER
STEEL STRUCTURE
CMU WALL W/ STUCCO FINISH COAT
9’- 2”
1’ - 0”
Attachment 6
132
LU SUBMITTAL 05 JULY 05, 2023
EV
EV
EV
SL
AL
EV
EV
EV
SL
AL
Sunnyvale Front Load Truck-32.3
6'-9"
3'-8"
1'
6'-9"
3'-8"
1'
6'-9"
1'
6'-9"
3'-8"
1'
6'-9"
3'-8"
1'
6'-9"
3'-8"
1' 6'-9"
3'-8"
16'
16'-11
2"
NEIGHBORING OFFICE
19'-10"
RESIDENTIAL
6'-9"
4'-6" 1'
6'-9"
4'-6"
6'-9"
4'-6"1'
6'-9"
4'-6"
5'
10'
3'-8"
DN
UP
UP
DN
DN
UP
UP
UP
x1
x7
15 15
2.14567891014
F
G
J
K
12 115'-10"
60'-0"18'-0"
RAMP UP
2'-5 1/4" 12'-0"
29'-11
1/4" 27'-6" 27'-6" 27'-6" 27'-6" 27'-6" 27'-6" 27'-6"
22'-0
3/4" 30'-2" 14'-4" 28'-7" 17'-6"
28'-5"
27'-7"
3 BED TOWNHOME 2 BED TOWNHOME
TRASH
3 BED TOWNHOME 2 BED TOWNHOME 3 BED TOWNHOME
TRASH
3 BED TOWNHOME
3 BED TOWNHOME
3 BED TOWNHOME
THE SHOP
PACKAGE ROOM
BOH
PARLOR
THE POST
OFFICE
TRANSFORMER
1 24'-0"
DRIVE
AISLE
24'-0"
DRIVE AISLE
STAIR 2
STAIR 1
STAIR 3
STAIR 4
ELEV 4 ELEV 3
ELEV 1 & 2
90.00°
ELECTRICALUTILITY
RESIDENTIAL
PARKING
ELECTRICAL
ELECTRICAL
MECHANICAL
ELEC
ELEC
R.R.
13 3 BED TOWNHOME 2 BED TOWNHOME 2 BED TOWNHOME 3 BED TOWNHOME xC
24'-0"
DRIVE
AISLE
211
H
x3
x4
x5
x6
3 x2
5.26.17.28.18.29.110.111.112.112.313.113.2
28'-6"25'-7"4'-11"14'-6"
18'-0"
18'-8
1/2"
25'-0"
25'-0"
17'-4 1/2"
11'-9"
73'-6"
xD
70'-4"
16 16
2'-5 1/4"
16'-4
1/4"
14'-2
1/2" 21'-0" 15'-6" 21'-0" 21'-0" 25'-0"
21'-8
1/2"
13'-10
3/4"
25'-10
3/4" 21'-0"
26'-5
1/4"
245'-5 1/4"
349'-6 1/4"
70'-4"
AMERICAN TRASH MANAGEMENT
1900 POWELL STREET, SUITE 220
EMERYVILLE, CALIFORNIA 94608
P: 415.292.5400
F: 415.292.5410
[email protected]
DRAWING TITLE
1150 - 1170 SAN ZENO WAY
SUNNYVALE, CA
PROJECT NO.
PROJECT
PK
DRAWN
APPROVED
DATE
SCALE
DRAWING NO.
CONSULTANT
OVERALL SITE PLAN
TR0.1
ARCHITECT
OWNER / DEVELOPER
NO. DATE ISSUED BYISSUE / REVISION
BDE - JONES
PROMETHIUS
SS
02/27/23
PROPOSED TRASH
ENCLOSURE (COMMERCIAL)
MAIN RESIDENTIAL
INTERIOR TRASH
COLLECTION ROOM
SECONDARY TRASH COLLECTION ROOM
1 /32" = 1' - 0"PATH OF TRAVEL - TOWN HOUSES TO TRASH COLLECTION ROOMPATH OF TRAVEL - CONTAINERS
EXISTING OFFICE ENCLOSURES TO BE
REMOVED AND RELOCATED TO
PROPOSED CENTRAL ENCLOSURE
AMERICAN TRASH MANAGEMENT
1900 POWELL STREET, SUITE 220
EMERYVILLE, CALIFORNIA 94608
P: 415.292.5400
F: 415.292.5410
[email protected]
CONSULTANT
BDE - JONES
TRASH STAGING AREA MAIN TRASH COLLECTION ROOM SECONDARY TRASH COLLECTION ROOM
PATH OF TRAVEL FROM TOWN HOUSES TO TRASH
COLLECTION ROOM
TRASH EXHIBIT - SITE PLAN
RESIDENTIAL WASTE
STAGING AREA
(3 Parking Spaces -
Sides - visual fence screening)
COLLECTION AREA 1
COLLECTION AREA 2
20'
27'
28'-7 5/8"
STRESS PAD MATERIAL: 5
INCH AGGREGATE BASE
(CLASS II COMPACTED )WITH
A 6 INCH PORTLAND CEMENT
OVERLAY.
Attachment 6
133
LU SUBMITTAL 05 JULY 05, 2023
AMERICAN TRASH MANAGEMENT
1900 POWELL STREET, SUITE 220
EMERYVILLE, CALIFORNIA 94608
P: 415.292.5400
F: 415.292.5410
[email protected]
CONSULTANT
BDE - JONES
TRASH STAGING AREA MAIN TRASH COLLECTION ROOM SECONDARY TRASH COLLECTION ROOM
PATH OF TRAVEL FROM TOWN HOUSES TO TRASH
COLLECTION ROOM
DN
UP
A
B.1
C.1
L
4.1 7.1
7.310.2
10.3 12.2 1
2 BED C
1 BED A
1 BED A
2 BED G
2 BED A
2 BED B
1 BED C
1 BED A 2 BED B 1 BED A
1 BED C+
1 BED B
1 BED B
1 BED D
1 BED B 1 BED B
1 BED B1 BED B
STUDIO A STUDIO A
STRENGTH STUDIO
2 BED A2 BED A
2 BED B
1 BED A
1 BED A
2 BED D
1 BED A
1 BED E
1 BED D
1 BED A1 BED A
STUDIO C
1 BED F
STUDIO D
DEN
STUDIO A
STUDIO A
STUDIO A
POOL
SPA
AMENITY POOL
DECK
AMENITY
COURTYARD
TRASH TRASH
STAIR 2
STAIR 1
STAIR 3
ELEV 3
ELEV 1 & 2
x2.5
11.2 x7.1
ELEC/IDF
5.1 16
16 AMERICAN TRASH MANAGEMENT
1900 POWELL STREET, SUITE 220
EMERYVILLE, CALIFORNIA 94608
P: 415.292.5400
F: 415.292.5410
[email protected]
DRAWING TITLE
1150 - 1170 SAN ZENO WAY
SUNNYVALE, CA
PROJECT NO.
PROJECT
PK
DRAWN
APPROVED
DATE
SCALE
DRAWING NO.
CONSULTANT
OVERALL PLAN - LEVEL 4
TR0.2
ARCHITECT
OWNER / DEVELOPER
NO. DATE ISSUED BYISSUE / REVISION
BDE - JONES
PROMETHIUS
SS
02/27/23
MAIN TRASH COLLECTION ROOM
SECONDARY CHUTE VESTIBULES
1 /32" = 1' - 0"
OVERALL PLAN - LEVEL 4
TRASH EXHIBIT - UPPER STORIES
97’-6”
95’-0”
78’-6”
27’-0”
45’-0”
71’-3” 46’-6”
Attachment 6
134
LU SUBMITTAL 05 JULY 05, 2023
WASTE
FOOD
SCRAPS
35 GAL.
REC PR
U-LINE
COLLAPSIBLE
WIRE
CONTAINER
MODEL H-1731
3412" HEIGHT
REC MC
3 FT
ACCESS
DOOR
96 GAL.
REC PR
WASTE
30"Ø CHUTE
HOPPER
96 GAL.
REC PR
18x18 SH AUTOMATIC OPENING
THRU-WALL INTAKE DOOR
SEE NOTE 17
SECTION B-1 SECTION B-2
HOPPER
18x18 SH AUTOMATIC OPENING
THRU-WALL INTAKE DOOR
SEE NOTE 17
SECTION B-3
24"Ø CHUTE
LEVEL 2
WASTE
MAX) AND FLOOR DRAIN. FLOOR LEVEL UNDER COMPACTOR.
3. WALLS SHALL BE FINISHED WITH WASHABLE WATERPROOF SURFACE SUCH AS FRP OR HIGH-GLOSS ENAMEL PAINT, 8'-0" AFF.
4. INSTALL WALL PROTECTION: 12"Wx5"H CONCRETE CURB AT BASE OF ALL NON-CONCRETE WALLS. DO NOT INSTALL THE CURB AROUND THE COMPACTORS/BISORTER OR POWER PACKS.
5. 10'-0" ROLL UP DOOR AND 3FT EXIT DOOR.
6. ROOM SHALL BE MECHANICALLY VENTILATED WITH (1) CFM/FT PER 2019 CBC.
7. (1) 30"Ø GRAVITY CHUTE FOR LOOSE WASTE & (2) 24"Ø GRAVITY CHUTES FOR PAPER & CONTAINER RECYCLING. CHUTES SHALL TERMINATE AT 5'-9" AFF.
8. MCP: CHUTE MASTER CONTROL PANEL SHALL BE WALL-MOUNTED 60" AFF. MUST ALLOW LOCK DOWN OF CHUTE INTAKES FOR EXCHANGING CONTAINERS AND WASHING CHUTES. REQUIRES 120V 15A DEDICATED SERVICE.
9. AC: 2HP CHUTE AIR COMPRESSOR SHALL BE MOUNTED72" AFF. REQUIRES 110V 15A SERVICE OUTLETS.
10. OC: ODOR CONTROL UNIT SHALL BE WALL-MOUNTED 60" AFF. REQUIRES 120V 15A SERVICE OUTLETS.
11. HB: HOT AND COLD HOSE BIB SHALL BE WALL-MOUNTED 60" AFF.
12. PROVIDE ELECTRIC PALLET TRUCK FOR TRANSFERRING CONTAINERS. 4000lb CAPACITY; TURNING RADIUS: 45.5". REQUIRES 120V 15A SERVICE OUTLETS.
13. CHUTE DISCHARGE DOOR: TYPE-A, HORIZONTALLY INSULATED SLIDING-STEEL DOOR, HELD OPEN BY 165° F FUSIBLE LINK.
14. (1) UNDEDICATED 120V 15A SERVICE OUTLET REQUIRED FOR STAFF MAINTENANCE PURPOSE.
CHUTE INTAKE VESTIBULES:
15. CHUTE INTAKE VESTIBULES SHALL BE 1HR FIRE-RATED WITH 1HR FIRE-RATED DOOR; 5'-0" MIN REQUIRED PER ADA STANDARDS - RESIDENTIAL ACCESS. PROVIDE (3) SELF CLOSING, 15x18 BOTTOM
HINGED, ELECTRICALLY INTERLOCKED, AUTOMATIC OPENING INTAKE DOORS TO DISPOSE TRASH AND RECYCLING PER CBC 713.13.1. POWER TO INTAKE DOORS SUPPLIED BY MCP. SEE DETAIL 1T2.0.
16. CHUTE SHAFT SHALL NOT BE ERECTED UNTIL CHUTE HAS BEEN INSTALLED. FOR SOUND PROOFING PURPOSES, DOUBLE STUD-WALLS ARE REQUIRED ADJACENT TO OCCUPIED SPACES. INTERIOR OF SHAFT SHALL BE TAPED TO PREVENT ODOROUS AIR LEAKING INTO OCCUPIED SPACES (BY OTHERS).
17. PROVIDE 18X18 SIDE HINGED, AUTOMATIC OPENING, ELECTRICALLY INTERLOCKED THRU-WALL INTAKE DOORS THAT DISPOSE INTO CONTAINERS PER CBC 713.13.1. SEE DETAILS 2/T2.0.
18. PROVIDE ROUND FLOOR OPENINGS AT CONCRETE FLOORS AND SQUARED FLOOR OPENINGS AT WOOD-FRAME CONSTRUCTION. INSTALL FLOOR SUPPORT FRAME AT EACH FLOOR PENETRATION TO SECURE CHUTE. SEE DETAIL 9/T2.0 FOR ANCHORING AND MASON BRA-RED SOUND ISOLATION PAD ASSEMBLY. POUR RINGS WILL VARY BASED ON THICKNESS OF FLOOR SLAB AND SHALL BE PROVIDED BY MANUFACTURER.
GENERAL NOTES:
1. ANY DESIGNS OR DESIGN SOLUTIONS PRESENTED IN THIS DRAWING OR SPECIFICATION, WHICH ARE
DIRECT OR IMPLIED, INCLUDING NARRATIVES, DRAWINGS, OR DIAGRAMS, ARE HEREBY CLARIFIED AS
EXAMPLES AND SHALL NOT BE CONSIDERED COMPLETE DESIGNS OR DESIGNS SUITABLE FOR CONSTRUCTION.
2. OMISSIONS FROM DRAWINGS OR SPECIFICATIONS, OR THE INACCURATE DESCRIPTION OF DETAILS OF
WORK, WHICH ARE MANIFESTLY NECESSARY TO CARRY OUT THE INTENT OF THE DRAWINGS AND
SPECIFICATIONS, OR WHICH ARE CUSTOMARILY PERFORMED, SHALL NOT RELIEVE THE CONTRACTOR FROM PERFORMING SUCH OMITTED OR INACCURATELY DESCRIBED DETAILS OF THE WORK. WORK
SHALL BE PERFORMED AS IF FULLY AND CORRECTLY SET FORTH AND DESCRIBED IN THE DRAWINGS AND SPECIFICATIONS.
3. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO START OF CONSTRUCTION. THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY OF ALL EXISTING FIELD CONDITIONS AND ANY DISCREPANCIES OR INCONSISTENCIES.
LEVEL 1.5
LEVEL 1
LEVEL 1.5
LEVEL 1
96 GAL.
REC PR
35 GAL FOOD SCRAP CART
35 GAL.
96 GAL CART
96 GAL.
HOPPER W/
THRU-WALL OPENING
HOPPER
TRASH COLLECTION ROOM- LOOSE
LEVEL3-8
TRASH
96 GAL.
REC MC
U-LINE
COLLAPSIBLE
WIRE
CONTAINER
MODEL H-1731
3412" HEIGHT
3 FT
ACCESS
DOOR
FOOD
SCRAPS
35 GAL.
3 CY
WASTE
CONTAINER
96 GAL.
REC PR
CHUTE
MASTER
CONTROL
SERVICE OUTLETS. (TYP)
AIR COMPRESSORS
3 CY
WASTE
CONTAINER
3 CY
WASTE
CONTAINER
3 CY
WASTE
CONTAINER
ELECTRIC
PALLET JACK
F.D.
B-3
B-2
B-1
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC MC
96 GAL.
REC MC
96 GAL.
REC MC
96 GAL.
REC MC
ODOR CONTROL
WHEEL STOP 12"W x 5"H
WASTE
E
11TRASH COLLECTION ROOM- LOOSE
LEVEL 1
HOT/COLD
HOSE BIB
HOT/COLD
HOSE BIB
AMERICAN TRASH MANAGEM
1900 POWELL STREET, SUITE
EMERYVILLE, CALIFORNIA 94
P: 415.292.5400
F: 415.292.5410
[email protected]
DRAWING TITLE
1150 - 1170 SAN
SUNNYVAL
PROJECT NO.
PROJECT
PK
DRAWN
APPROVED
DATE
SCALE
DRAW
CONSULTANT
MAIN TRASH COLLE
ARCHITECT
OWNER / DEVELOPER
NO. DATE ISSUE /
BDE - JONES
PROMETHIUS
SS
02/27/23
3/16" = 1' - 0"
WASTE
FOOD
SCRAPS
35 GAL.
REC PR
U-LINE
COLLAPSIBLE
WIRE
CONTAINER
MODEL H-1731
3412" HEIGHT
REC MC
3 FT
ACCESS
DOOR
96 GAL.
REC PR
WASTE
30"Ø CHUTE
HOPPER
96 GAL.
REC PR
18x18 SH AUTOMATIC OPENING
THRU-WALL INTAKE DOOR
SEE NOTE 17
SECTION B-1 SECTION B-2
HOPPER
18x18 SH AUTOMATIC OPENING
THRU-WALL INTAKE DOOR
SEE NOTE 17
SECTION B-3
24"Ø CHUTE
LEVEL 2
WASTE
MAX) AND FLOOR DRAIN. FLOOR LEVEL UNDER COMPACTOR.
3. WALLS SHALL BE FINISHED WITH WASHABLE WATERPROOF SURFACE SUCH AS FRP OR HIG ENAMEL PAINT, 8'-0" AFF.
4. INSTALL WALL PROTECTION: 12"Wx5"H CONCRETE CURB AT BASE OF ALL NON-CONCRETE W NOT INSTALL THE CURB AROUND THE COMPACTORS/BISORTER OR POWER PACKS.
5. 10'-0" ROLL UP DOOR AND 3FT EXIT DOOR.
6. ROOM SHALL BE MECHANICALLY VENTILATED WITH (1) CFM/FT PER 2019 CBC.
7. (1) 30"Ø GRAVITY CHUTE FOR LOOSE WASTE & (2) 24"Ø GRAVITY CHUTES FOR PAPER & C RECYCLING. CHUTES SHALL TERMINATE AT 5'-9" AFF.
8. MCP: CHUTE MASTER CONTROL PANEL SHALL BE WALL-MOUNTED 60" AFF. MUST ALLOW LO OF CHUTE INTAKES FOR EXCHANGING CONTAINERS AND WASHING CHUTES. REQUIRES DEDICATED SERVICE.
9. AC: 2HP CHUTE AIR COMPRESSOR SHALL BE MOUNTED72" AFF. REQUIRES 110V 15A SERVICE O
10. OC: ODOR CONTROL UNIT SHALL BE WALL-MOUNTED 60" AFF. REQUIRES 120V 15A SERVICE OU
11. HB: HOT AND COLD HOSE BIB SHALL BE WALL-MOUNTED 60" AFF.
12. PROVIDE ELECTRIC PALLET TRUCK FOR TRANSFERRING CONTAINERS. 4000lb CAPACITY; RADIUS: 45.5". REQUIRES 120V 15A SERVICE OUTLETS.
13. CHUTE DISCHARGE DOOR: TYPE-A, HORIZONTALLY INSULATED SLIDING-STEEL DOOR, HELD 165° F FUSIBLE LINK.
14. (1) UNDEDICATED 120V 15A SERVICE OUTLET REQUIRED FOR STAFF MAINTENANCE PURPOSE.
CHUTE INTAKE VESTIBULES:
15. CHUTE INTAKE VESTIBULES SHALL BE 1HR FIRE-RATED WITH 1HR FIRE-RATED DOOR; REQUIRED PER ADA STANDARDS - RESIDENTIAL ACCESS. PROVIDE (3) SELF CLOSING, 15x18
HINGED, ELECTRICALLY INTERLOCKED, AUTOMATIC OPENING INTAKE DOORS TO DISPOSE TR RECYCLING PER CBC 713.13.1. POWER TO INTAKE DOORS SUPPLIED BY MCP. SEE DETAIL 1T2.
16. CHUTE SHAFT SHALL NOT BE ERECTED UNTIL CHUTE HAS BEEN INSTALLED. FOR SOUND P PURPOSES, DOUBLE STUD-WALLS ARE REQUIRED ADJACENT TO OCCUPIED SPACES. INT
SHAFT SHALL BE TAPED TO PREVENT ODOROUS AIR LEAKING INTO OCCUPIED SPACES (BY OT
17. PROVIDE 18X18 SIDE HINGED, AUTOMATIC OPENING, ELECTRICALLY INTERLOCKED THRU-WA DOORS THAT DISPOSE INTO CONTAINERS PER CBC 713.13.1. SEE DETAILS 2/T2.0.
18. PROVIDE ROUND FLOOR OPENINGS AT CONCRETE FLOORS AND SQUARED FLOOR OPE WOOD-FRAME CONSTRUCTION. INSTALL FLOOR SUPPORT FRAME AT EACH FLOOR PENETR SECURE CHUTE. SEE DETAIL 9/T2.0 FOR ANCHORING AND MASON BRA-RED SOUND ISOLA ASSEMBLY. POUR RINGS WILL VARY BASED ON THICKNESS OF FLOOR SLAB AND SHALL BE P BY MANUFACTURER.
GENERAL NOTES:
1. ANY DESIGNS OR DESIGN SOLUTIONS PRESENTED IN THIS DRAWING OR SPECIFICATION, W
DIRECT OR IMPLIED, INCLUDING NARRATIVES, DRAWINGS, OR DIAGRAMS, ARE HEREBY CLA
EXAMPLES AND SHALL NOT BE CONSIDERED COMPLETE DESIGNS OR DESIGNS SUITA CONSTRUCTION.
2. OMISSIONS FROM DRAWINGS OR SPECIFICATIONS, OR THE INACCURATE DESCRIPTION OF D
WORK, WHICH ARE MANIFESTLY NECESSARY TO CARRY OUT THE INTENT OF THE DRAW
SPECIFICATIONS, OR WHICH ARE CUSTOMARILY PERFORMED, SHALL NOT RELIEVE THE CON
FROM PERFORMING SUCH OMITTED OR INACCURATELY DESCRIBED DETAILS OF THE WOR
SHALL BE PERFORMED AS IF FULLY AND CORRECTLY SET FORTH AND DESCRIBED IN THE D AND SPECIFICATIONS.
3. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO S CONSTRUCTION. THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY OF ALL EXISTIN CONDITIONS AND ANY DISCREPANCIES OR INCONSISTENCIES.
LEVEL 1.5
LEVEL 1
LEVEL 1.5
LEVEL 1
96 GAL.
REC PR
35 GAL FOOD SCRAP CART
35 GAL.
96 GAL CART
96 GAL.
HOPPER W/
THRU-WALL OPENING
HOPPER
TRASH COLLECTION ROOM- LOOSE
LEVEL3-8
TRASH
96 GAL.
REC MC
U-LINE
COLLAPSIBLE
WIRE
CONTAINER
MODEL H-1731
3412" HEIGHT
3 FT
ACCESS
DOOR
FOOD
SCRAPS
35 GAL.
3 CY
WASTE
CONTAINER
96 GAL.
REC PR
CHUTE
MASTER
CONTROL
SERVICE OUTLETS. (TYP)
AIR COMPRESSORS
3 CY
WASTE
CONTAINER
3 CY
WASTE
CONTAINER
3 CY
WASTE
CONTAINER
ELECTRIC
PALLET JACK
F.D.
B-3
B-2
B-1
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC MC
96 GAL.
REC MC
96 GAL.
REC MC
96 GAL.
REC MC
ODOR CONTROL
WHEEL STOP 12"W x 5"H
WASTE
E
11TRASH COLLECTION ROOM- LOOSE
LEVEL 1
HOT/COLD
HOSE BIB
HOT/COLD
HOSE BIB
WASTE
FOOD
SCRAPS
35 GAL.
REC PR
U-LINE
COLLAPSIBLE
WIRE
CONTAINER
MODEL H-1731
3412" HEIGHT
REC MC
3 FT
ACCESS
DOOR
96 GAL.
REC PR
WASTE
30"Ø CHUTE
HOPPER
96 GAL.
REC PR
18x18 SH AUTOMATIC OPENING
THRU-WALL INTAKE DOOR
SEE NOTE 17
SECTION B-1 SECTION B-2
HOPPER
18x18 SH AUTOMATIC OPENING
THRU-WALL INTAKE DOOR
SEE NOTE 17
SECTION B-3
24"Ø CHUTE
LEVEL 2
WASTE
SHEET NOTES:
RESIDENTIAL TRASH TERMINATION ROOM
1. TRASH COLLECTION ROOM IS PART OF 2HR FIRE-RATED TRASH CHUTE SHAFT - RESTRICTED ACCESS.
2. FLOOR SHALL BE FINISHED WITH WATERPROOF DECK COATING. FLOOR TO HAVE MINIMAL SLOPE (1° MAX) AND FLOOR DRAIN. FLOOR LEVEL UNDER COMPACTOR.
3. WALLS SHALL BE FINISHED WITH WASHABLE WATERPROOF SURFACE SUCH AS FRP OR HIGH-GLOSS ENAMEL PAINT, 8'-0" AFF.
4. INSTALL WALL PROTECTION: 12"Wx5"H CONCRETE CURB AT BASE OF ALL NON-CONCRETE WALLS. DO NOT INSTALL THE CURB AROUND THE COMPACTORS/BISORTER OR POWER PACKS.
5. 10'-0" ROLL UP DOOR AND 3FT EXIT DOOR.
6. ROOM SHALL BE MECHANICALLY VENTILATED WITH (1) CFM/FT PER 2019 CBC.
7. (1) 30"Ø GRAVITY CHUTE FOR LOOSE WASTE & (2) 24"Ø GRAVITY CHUTES FOR PAPER & CONTAINER RECYCLING. CHUTES SHALL TERMINATE AT 5'-9" AFF.
8. MCP: CHUTE MASTER CONTROL PANEL SHALL BE WALL-MOUNTED 60" AFF. MUST ALLOW LOCK DOWN OF CHUTE INTAKES FOR EXCHANGING CONTAINERS AND WASHING CHUTES. REQUIRES 120V 15A DEDICATED SERVICE.
9. AC: 2HP CHUTE AIR COMPRESSOR SHALL BE MOUNTED72" AFF. REQUIRES 110V 15A SERVICE OUTLETS.
10. OC: ODOR CONTROL UNIT SHALL BE WALL-MOUNTED 60" AFF. REQUIRES 120V 15A SERVICE OUTLETS.
11. HB: HOT AND COLD HOSE BIB SHALL BE WALL-MOUNTED 60" AFF.
12. PROVIDE ELECTRIC PALLET TRUCK FOR TRANSFERRING CONTAINERS. 4000lb CAPACITY; TURNING RADIUS: 45.5". REQUIRES 120V 15A SERVICE OUTLETS.
13. CHUTE DISCHARGE DOOR: TYPE-A, HORIZONTALLY INSULATED SLIDING-STEEL DOOR, HELD OPEN BY 165° F FUSIBLE LINK.
14. (1) UNDEDICATED 120V 15A SERVICE OUTLET REQUIRED FOR STAFF MAINTENANCE PURPOSE.
CHUTE INTAKE VESTIBULES:
15. CHUTE INTAKE VESTIBULES SHALL BE 1HR FIRE-RATED WITH 1HR FIRE-RATED DOOR; 5'-0" MIN REQUIRED PER ADA STANDARDS - RESIDENTIAL ACCESS. PROVIDE (3) SELF CLOSING, 15x18 BOTTOM
HINGED, ELECTRICALLY INTERLOCKED, AUTOMATIC OPENING INTAKE DOORS TO DISPOSE TRASH AND RECYCLING PER CBC 713.13.1. POWER TO INTAKE DOORS SUPPLIED BY MCP. SEE DETAIL 1T2.0.
16. CHUTE SHAFT SHALL NOT BE ERECTED UNTIL CHUTE HAS BEEN INSTALLED. FOR SOUND PROOFING PURPOSES, DOUBLE STUD-WALLS ARE REQUIRED ADJACENT TO OCCUPIED SPACES. INTERIOR OF SHAFT SHALL BE TAPED TO PREVENT ODOROUS AIR LEAKING INTO OCCUPIED SPACES (BY OTHERS).
17. PROVIDE 18X18 SIDE HINGED, AUTOMATIC OPENING, ELECTRICALLY INTERLOCKED THRU-WALL INTAKE DOORS THAT DISPOSE INTO CONTAINERS PER CBC 713.13.1. SEE DETAILS 2/T2.0.
18. PROVIDE ROUND FLOOR OPENINGS AT CONCRETE FLOORS AND SQUARED FLOOR OPENINGS AT WOOD-FRAME CONSTRUCTION. INSTALL FLOOR SUPPORT FRAME AT EACH FLOOR PENETRATION TO SECURE CHUTE. SEE DETAIL 9/T2.0 FOR ANCHORING AND MASON BRA-RED SOUND ISOLATION PAD ASSEMBLY.
POUR RINGS WILL VARY BASED ON THICKNESS OF FLOOR SLAB AND SHALL BE PROVIDED BY MANUFACTURER.
GENERAL NOTES:
1. ANY DESIGNS OR DESIGN SOLUTIONS PRESENTED IN THIS DRAWING OR SPECIFICATION, WHICH ARE
DIRECT OR IMPLIED, INCLUDING NARRATIVES, DRAWINGS, OR DIAGRAMS, ARE HEREBY CLARIFIED AS
EXAMPLES AND SHALL NOT BE CONSIDERED COMPLETE DESIGNS OR DESIGNS SUITABLE FOR CONSTRUCTION.
2. OMISSIONS FROM DRAWINGS OR SPECIFICATIONS, OR THE INACCURATE DESCRIPTION OF DETAILS OF
WORK, WHICH ARE MANIFESTLY NECESSARY TO CARRY OUT THE INTENT OF THE DRAWINGS AND
SPECIFICATIONS, OR WHICH ARE CUSTOMARILY PERFORMED, SHALL NOT RELIEVE THE CONTRACTOR FROM PERFORMING SUCH OMITTED OR INACCURATELY DESCRIBED DETAILS OF THE WORK. WORK
SHALL BE PERFORMED AS IF FULLY AND CORRECTLY SET FORTH AND DESCRIBED IN THE DRAWINGS AND SPECIFICATIONS.
3. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO START OF CONSTRUCTION. THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY OF ALL EXISTING FIELD CONDITIONS AND ANY DISCREPANCIES OR INCONSISTENCIES.
LEVEL 1.5
LEVEL 1
LEVEL 1.5
LEVEL 1
96 GAL.
REC PR
35 GAL FOOD SCRAP CART
35 GAL.
96 GAL CART
96 GAL.
HOPPER W/
THRU-WALL OPENING
HOPPER
TRASH COLLECTION ROOM- LOOSE
LEVEL3-8
TRASH
96 GAL.
REC MC
U-LINE
COLLAPSIBLE
WIRE
CONTAINER
MODEL H-1731
3412" HEIGHT
3 FT
ACCESS
DOOR
FOOD
SCRAPS
35 GAL.
3 CY
WASTE
CONTAINER
96 GAL.
REC PR
CHUTE
MASTER
CONTROL
SERVICE OUTLETS. (TYP)
AIR COMPRESSORS
3 CY
WASTE
CONTAINER
3 CY
WASTE
CONTAINER
3 CY
WASTE
CONTAINER
ELECTRIC
PALLET JACK
F.D.
B-3
B-2
B-1
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC MC
96 GAL.
REC MC
96 GAL.
REC MC
96 GAL.
REC MC
ODOR CONTROL
WHEEL STOP 12"W x 5"H
WASTE
E
11TRASH COLLECTION ROOM- LOOSE
LEVEL 1
HOT/COLD
HOSE BIB
HOT/COLD
HOSE BIB
AMERIC
1900 PO
EMERYV
P: 415.2
F: 415.2
SBROWN
DRAWING TITLE
11 PROJECT NO.
PROJECT
DRAWN
APPROVED
DATE
SCALE
CONSULTANT
MAIN
ARCHITECT
OWNER / DEVELOP
NO. DA
BDE -
PROME
02 3/16"
WASTE
FOOD
SCRAPS
35 GAL.
REC PR
U-LINE
COLLAPSIBLE
WIRE
CONTAINER
MODEL H-1731
3412" HEIGHT
REC MC
3 FT
ACCESS
DOOR
96 GAL.
REC PR
WASTE
30"Ø CHUTE
HOPPER
96 GAL.
REC PR
18x18 SH AUTOMATIC OPENING
THRU-WALL INTAKE DOOR
SEE NOTE 17
SECTION B-1 SECTION B-2
HOPPER
18x18 SH AUTOMATIC OPENING
THRU-WALL INTAKE DOOR
SEE NOTE 17
SECTION B-3
24"Ø CHUTE
LEVEL 2
WASTE
SHEET NOTES:
RESIDENTIAL TRASH TERMINATION ROOM
1. TRASH COLLECTION ROOM IS PART OF 2HR FIRE-RATED TRASH CHUTE SHAFT - RESTRICTED ACCESS.
2. FLOOR SHALL BE FINISHED WITH WATERPROOF DECK COATING. FLOOR TO HAVE MINIMAL SLOPE (1° MAX) AND FLOOR DRAIN. FLOOR LEVEL UNDER COMPACTOR.
3. WALLS SHALL BE FINISHED WITH WASHABLE WATERPROOF SURFACE SUCH AS FRP OR HIGH-GLOSS ENAMEL PAINT, 8'-0" AFF.
4. INSTALL WALL PROTECTION: 12"Wx5"H CONCRETE CURB AT BASE OF ALL NON-CONCRETE WALLS. DO NOT INSTALL THE CURB AROUND THE COMPACTORS/BISORTER OR POWER PACKS.
5. 10'-0" ROLL UP DOOR AND 3FT EXIT DOOR.
6. ROOM SHALL BE MECHANICALLY VENTILATED WITH (1) CFM/FT PER 2019 CBC.
7. (1) 30"Ø GRAVITY CHUTE FOR LOOSE WASTE & (2) 24"Ø GRAVITY CHUTES FOR PAPER & CONTAINER RECYCLING. CHUTES SHALL TERMINATE AT 5'-9" AFF.
8. MCP: CHUTE MASTER CONTROL PANEL SHALL BE WALL-MOUNTED 60" AFF. MUST ALLOW LOCK DOWN OF CHUTE INTAKES FOR EXCHANGING CONTAINERS AND WASHING CHUTES. REQUIRES 120V 15A DEDICATED SERVICE.
9. AC: 2HP CHUTE AIR COMPRESSOR SHALL BE MOUNTED72" AFF. REQUIRES 110V 15A SERVICE OUTLETS.
10. OC: ODOR CONTROL UNIT SHALL BE WALL-MOUNTED 60" AFF. REQUIRES 120V 15A SERVICE OUTLETS.
11. HB: HOT AND COLD HOSE BIB SHALL BE WALL-MOUNTED 60" AFF.
12. PROVIDE ELECTRIC PALLET TRUCK FOR TRANSFERRING CONTAINERS. 4000lb CAPACITY; TURNING RADIUS: 45.5". REQUIRES 120V 15A SERVICE OUTLETS.
13. CHUTE DISCHARGE DOOR: TYPE-A, HORIZONTALLY INSULATED SLIDING-STEEL DOOR, HELD OPEN BY 165° F FUSIBLE LINK.
14. (1) UNDEDICATED 120V 15A SERVICE OUTLET REQUIRED FOR STAFF MAINTENANCE PURPOSE.
CHUTE INTAKE VESTIBULES:
15. CHUTE INTAKE VESTIBULES SHALL BE 1HR FIRE-RATED WITH 1HR FIRE-RATED DOOR; 5'-0" MIN REQUIRED PER ADA STANDARDS - RESIDENTIAL ACCESS. PROVIDE (3) SELF CLOSING, 15x18 BOTTOM
HINGED, ELECTRICALLY INTERLOCKED, AUTOMATIC OPENING INTAKE DOORS TO DISPOSE TRASH AND RECYCLING PER CBC 713.13.1. POWER TO INTAKE DOORS SUPPLIED BY MCP. SEE DETAIL 1T2.0.
16. CHUTE SHAFT SHALL NOT BE ERECTED UNTIL CHUTE HAS BEEN INSTALLED. FOR SOUND PROOFING PURPOSES, DOUBLE STUD-WALLS ARE REQUIRED ADJACENT TO OCCUPIED SPACES. INTERIOR OF SHAFT SHALL BE TAPED TO PREVENT ODOROUS AIR LEAKING INTO OCCUPIED SPACES (BY OTHERS).
17. PROVIDE 18X18 SIDE HINGED, AUTOMATIC OPENING, ELECTRICALLY INTERLOCKED THRU-WALL INTAKE DOORS THAT DISPOSE INTO CONTAINERS PER CBC 713.13.1. SEE DETAILS 2/T2.0.
18. PROVIDE ROUND FLOOR OPENINGS AT CONCRETE FLOORS AND SQUARED FLOOR OPENINGS AT WOOD-FRAME CONSTRUCTION. INSTALL FLOOR SUPPORT FRAME AT EACH FLOOR PENETRATION TO SECURE CHUTE. SEE DETAIL 9/T2.0 FOR ANCHORING AND MASON BRA-RED SOUND ISOLATION PAD ASSEMBLY. POUR RINGS WILL VARY BASED ON THICKNESS OF FLOOR SLAB AND SHALL BE PROVIDED BY MANUFACTURER.
GENERAL NOTES:
1. ANY DESIGNS OR DESIGN SOLUTIONS PRESENTED IN THIS DRAWING OR SPECIFICATION, WHICH ARE
DIRECT OR IMPLIED, INCLUDING NARRATIVES, DRAWINGS, OR DIAGRAMS, ARE HEREBY CLARIFIED AS
EXAMPLES AND SHALL NOT BE CONSIDERED COMPLETE DESIGNS OR DESIGNS SUITABLE FOR CONSTRUCTION.
2. OMISSIONS FROM DRAWINGS OR SPECIFICATIONS, OR THE INACCURATE DESCRIPTION OF DETAILS OF
WORK, WHICH ARE MANIFESTLY NECESSARY TO CARRY OUT THE INTENT OF THE DRAWINGS AND
SPECIFICATIONS, OR WHICH ARE CUSTOMARILY PERFORMED, SHALL NOT RELIEVE THE CONTRACTOR FROM PERFORMING SUCH OMITTED OR INACCURATELY DESCRIBED DETAILS OF THE WORK. WORK
SHALL BE PERFORMED AS IF FULLY AND CORRECTLY SET FORTH AND DESCRIBED IN THE DRAWINGS AND SPECIFICATIONS.
3. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO START OF CONSTRUCTION. THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY OF ALL EXISTING FIELD CONDITIONS AND ANY DISCREPANCIES OR INCONSISTENCIES.
LEVEL 1.5
LEVEL 1
LEVEL 1.5
LEVEL 1
96 GAL.
REC PR
35 GAL FOOD SCRAP CART
35 GAL.
96 GAL CART
96 GAL.
HOPPER W/
THRU-WALL OPENING
HOPPER
TRASH COLLECTION ROOM- LOOSE
LEVEL3-8
TRASH
96 GAL.
REC MC
U-LINE
COLLAPSIBLE
WIRE
CONTAINER
MODEL H-1731
3412" HEIGHT
3 FT
ACCESS
DOOR
FOOD
SCRAPS
35 GAL.
3 CY
WASTE
CONTAINER
96 GAL.
REC PR
CHUTE
MASTER
CONTROL
SERVICE OUTLETS. (TYP)
AIR COMPRESSORS
3 CY
WASTE
CONTAINER
3 CY
WASTE
CONTAINER
3 CY
WASTE
CONTAINER
ELECTRIC
PALLET JACK
F.D.
B-3
B-2
B-1
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC MC
96 GAL.
REC MC
96 GAL.
REC MC
96 GAL.
REC MC
ODOR CONTROL
WHEEL STOP 12"W x 5"H
WASTE
E
11TRASH COLLECTION ROOM- LOOSE
LEVEL 1
HOT/COLD
HOSE BIB
HOT/COLD
HOSE BIB
AMERICAN TRASH MANAGEMENT
1900 POWELL STREET, SUITE 220
EMERYVILLE, CALIFORNIA 94608
P: 415.292.5400
F: 415.292.5410
[email protected]
DRAWING TITLE
1150 - 1170 SAN ZENO W
SUNNYVALE, CA
PROJECT NO.
PROJECT
PK
DRAWN
APPROVED
DATE
SCALE
DRAWING NO.
CONSULTANT
MAIN TRASH COLLECTION R
TR1
ARCHITECT
OWNER / DEVELOPER
NO. DATE ISSUE / REVISION
BDE - JONES
PROMETHIUS
SS
02/27/23
3/16" = 1' - 0"
AMERICAN TRASH MANAGEMENT
1900 POWELL STREET, SUITE 220
EMERYVILLE, CALIFORNIA 94608
P: 415.292.5400
F: 415.292.5410
[email protected]
CONSULTANT
BDE - JONES
TRASH STAGING AREA MAIN TRASH COLLECTION ROOM SECONDARY TRASH COLLECTION ROOM
PATH OF TRAVEL FROM TOWN HOUSES TO TRASH
COLLECTION ROOM
WASTE
FOOD
SCRAPS
35 GAL.
REC PR
U-LINE
COLLAPSIBLE
WIRE
CONTAINER
MODEL H-1731
3412" HEIGHT
REC MC
3 FT
ACCESS
DOOR
96 GAL.
REC PR
WASTE
30"Ø CHUTE
HOPPER
96 GAL.
REC PR
18x18 SH AUTOMATIC OPENING
THRU-WALL INTAKE DOOR
SEE NOTE 17
SECTION B-1 SECTION B-2
HOPPER
18x18 SH AUTOMATIC OPENING
THRU-WALL INTAKE DOOR
SEE NOTE 17
SECTION B-3
24"Ø CHUTE
LEVEL 2
WASTE
SHEET NOTES:
RESIDENTIAL TRASH TERMINATION ROOM
1. TRASH COLLECTION ROOM IS PART OF 2HR FIRE-RATED TRASH CHUTE SHAFT - RESTRICTED ACCESS.
2. FLOOR SHALL BE FINISHED WITH WATERPROOF DECK COATING. FLOOR TO HAVE MINIMAL SLOPE (1° MAX) AND FLOOR DRAIN. FLOOR LEVEL UNDER COMPACTOR.
3. WALLS SHALL BE FINISHED WITH WASHABLE WATERPROOF SURFACE SUCH AS FRP OR HIGH-GLOSS ENAMEL PAINT, 8'-0" AFF.
4. INSTALL WALL PROTECTION: 12"Wx5"H CONCRETE CURB AT BASE OF ALL NON-CONCRETE WALLS. DO NOT INSTALL THE CURB AROUND THE COMPACTORS/BISORTER OR POWER PACKS.
5. 10'-0" ROLL UP DOOR AND 3FT EXIT DOOR.
6. ROOM SHALL BE MECHANICALLY VENTILATED WITH (1) CFM/FT PER 2019 CBC.
7. (1) 30"Ø GRAVITY CHUTE FOR LOOSE WASTE & (2) 24"Ø GRAVITY CHUTES FOR PAPER & CONTAINER RECYCLING. CHUTES SHALL TERMINATE AT 5'-9" AFF.
8. MCP: CHUTE MASTER CONTROL PANEL SHALL BE WALL-MOUNTED 60" AFF. MUST ALLOW LOCK DOWN OF CHUTE INTAKES FOR EXCHANGING CONTAINERS AND WASHING CHUTES. REQUIRES 120V 15A DEDICATED SERVICE.
9. AC: 2HP CHUTE AIR COMPRESSOR SHALL BE MOUNTED72" AFF. REQUIRES 110V 15A SERVICE OUTLETS.
10. OC: ODOR CONTROL UNIT SHALL BE WALL-MOUNTED 60" AFF. REQUIRES 120V 15A SERVICE OUTLETS.
11. HB: HOT AND COLD HOSE BIB SHALL BE WALL-MOUNTED 60" AFF.
12. PROVIDE ELECTRIC PALLET TRUCK FOR TRANSFERRING CONTAINERS. 4000lb CAPACITY; TURNING RADIUS: 45.5". REQUIRES 120V 15A SERVICE OUTLETS.
13. CHUTE DISCHARGE DOOR: TYPE-A, HORIZONTALLY INSULATED SLIDING-STEEL DOOR, HELD OPEN BY 165° F FUSIBLE LINK.
14. (1) UNDEDICATED 120V 15A SERVICE OUTLET REQUIRED FOR STAFF MAINTENANCE PURPOSE.
CHUTE INTAKE VESTIBULES:
15. CHUTE INTAKE VESTIBULES SHALL BE 1HR FIRE-RATED WITH 1HR FIRE-RATED DOOR; 5'-0" MIN REQUIRED PER ADA STANDARDS - RESIDENTIAL ACCESS. PROVIDE (3) SELF CLOSING, 15x18 BOTTOM
HINGED, ELECTRICALLY INTERLOCKED, AUTOMATIC OPENING INTAKE DOORS TO DISPOSE TRASH AND RECYCLING PER CBC 713.13.1. POWER TO INTAKE DOORS SUPPLIED BY MCP. SEE DETAIL 1T2.0.
16. CHUTE SHAFT SHALL NOT BE ERECTED UNTIL CHUTE HAS BEEN INSTALLED. FOR SOUND PROOFING PURPOSES, DOUBLE STUD-WALLS ARE REQUIRED ADJACENT TO OCCUPIED SPACES. INTERIOR OF SHAFT SHALL BE TAPED TO PREVENT ODOROUS AIR LEAKING INTO OCCUPIED SPACES (BY OTHERS).
17. PROVIDE 18X18 SIDE HINGED, AUTOMATIC OPENING, ELECTRICALLY INTERLOCKED THRU-WALL INTAKE DOORS THAT DISPOSE INTO CONTAINERS PER CBC 713.13.1. SEE DETAILS 2/T2.0.
18. PROVIDE ROUND FLOOR OPENINGS AT CONCRETE FLOORS AND SQUARED FLOOR OPENINGS AT WOOD-FRAME CONSTRUCTION. INSTALL FLOOR SUPPORT FRAME AT EACH FLOOR PENETRATION TO SECURE CHUTE. SEE DETAIL 9/T2.0 FOR ANCHORING AND MASON BRA-RED SOUND ISOLATION PAD ASSEMBLY. POUR RINGS WILL VARY BASED ON THICKNESS OF FLOOR SLAB AND SHALL BE PROVIDED BY MANUFACTURER.
GENERAL NOTES:
1. ANY DESIGNS OR DESIGN SOLUTIONS PRESENTED IN THIS DRAWING OR SPECIFICATION, WHICH ARE
DIRECT OR IMPLIED, INCLUDING NARRATIVES, DRAWINGS, OR DIAGRAMS, ARE HEREBY CLARIFIED AS
EXAMPLES AND SHALL NOT BE CONSIDERED COMPLETE DESIGNS OR DESIGNS SUITABLE FOR CONSTRUCTION.
2. OMISSIONS FROM DRAWINGS OR SPECIFICATIONS, OR THE INACCURATE DESCRIPTION OF DETAILS OF
WORK, WHICH ARE MANIFESTLY NECESSARY TO CARRY OUT THE INTENT OF THE DRAWINGS AND
SPECIFICATIONS, OR WHICH ARE CUSTOMARILY PERFORMED, SHALL NOT RELIEVE THE CONTRACTOR FROM PERFORMING SUCH OMITTED OR INACCURATELY DESCRIBED DETAILS OF THE WORK. WORK
SHALL BE PERFORMED AS IF FULLY AND CORRECTLY SET FORTH AND DESCRIBED IN THE DRAWINGS AND SPECIFICATIONS.
3. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO START OF CONSTRUCTION. THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY OF ALL EXISTING FIELD CONDITIONS AND ANY DISCREPANCIES OR INCONSISTENCIES.
LEVEL 1.5
LEVEL 1
LEVEL 1.5
LEVEL 1
96 GAL.
REC PR
35 GAL FOOD SCRAP CART
35 GAL.
96 GAL CART
96 GAL.
HOPPER W/
THRU-WALL OPENING
HOPPER
TRASH COLLECTION ROOM- LOOSE
LEVEL3-8
TRASH
96 GAL.
REC MC
U-LINE
COLLAPSIBLE
WIRE
CONTAINER
MODEL H-1731
3412" HEIGHT
3 FT
ACCESS
DOOR
FOOD
SCRAPS
35 GAL.
3 CY
WASTE
CONTAINER
96 GAL.
REC PR
CHUTE
MASTER
CONTROL
SERVICE OUTLETS. (TYP)
AIR COMPRESSORS
3 CY
WASTE
CONTAINER
3 CY
WASTE
CONTAINER
3 CY
WASTE
CONTAINER
ELECTRIC
PALLET JACK
F.D.
B-3
B-2
B-1
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC MC
96 GAL.
REC MC
96 GAL.
REC MC
96 GAL.
REC MC
ODOR CONTROL
WHEEL STOP 12"W x 5"H
WASTE
E
11TRASH COLLECTION ROOM- LOOSE
LEVEL 1
HOT/COLD
HOSE BIB
HOT/COLD
HOSE BIB
AMERICAN TRASH MANAGEMENT
1900 POWELL STREET, SUITE 220
EMERYVILLE, CALIFORNIA 94608
P: 415.292.5400
F: 415.292.5410
[email protected]
DRAWING TITLE
1150 - 1170 SAN ZENO W
SUNNYVALE, CA
PROJECT NO.
PROJECT
PK
DRAWN
APPROVED
DATE
SCALE
DRAWING NO.
CONSULTANT
MAIN TRASH COLLECTION R
TR1
ARCHITECT
OWNER / DEVELOPER
NO. DATE ISSUE / REVISION
BDE - JONES
PROMETHIUS
SS
02/27/23
WASTE
FOOD
SCRAPS
35 GAL.
REC PR
U-LINE
COLLAPSIBLE
WIRE
CONTAINER
MODEL H-1731
3412" HEIGHT
REC MC
3 FT
ACCESS
DOOR
96 GAL.
REC PR
WASTE
30"Ø CHUTE
HOPPER
96 GAL.
REC PR
18x18 SH AUTOMATIC OPENING
THRU-WALL INTAKE DOOR
SEE NOTE 17
SECTION B-1 SECTION B-2
HOPPER
18x18 SH AUTOMATIC OPENING
THRU-WALL INTAKE DOOR
SEE NOTE 17
SECTION B-3
24"Ø CHUTE
LEVEL 2
WASTE
SHEET NOTES:
RESIDENTIAL TRASH TERMINATION ROOM
1. TRASH COLLECTION ROOM IS PART OF 2HR FIRE-RATED TRASH CHUTE SHAFT - RESTRICTED ACCESS.
2. FLOOR SHALL BE FINISHED WITH WATERPROOF DECK COATING. FLOOR TO HAVE MINIMAL SLOPE (1° MAX) AND FLOOR DRAIN. FLOOR LEVEL UNDER COMPACTOR.
3. WALLS SHALL BE FINISHED WITH WASHABLE WATERPROOF SURFACE SUCH AS FRP OR HIGH-GLOSS ENAMEL PAINT, 8'-0" AFF.
4. INSTALL WALL PROTECTION: 12"Wx5"H CONCRETE CURB AT BASE OF ALL NON-CONCRETE WALLS. DO NOT INSTALL THE CURB AROUND THE COMPACTORS/BISORTER OR POWER PACKS.
5. 10'-0" ROLL UP DOOR AND 3FT EXIT DOOR.
6. ROOM SHALL BE MECHANICALLY VENTILATED WITH (1) CFM/FT PER 2019 CBC.
7. (1) 30"Ø GRAVITY CHUTE FOR LOOSE WASTE & (2) 24"Ø GRAVITY CHUTES FOR PAPER & CONTAINER RECYCLING. CHUTES SHALL TERMINATE AT 5'-9" AFF.
8. MCP: CHUTE MASTER CONTROL PANEL SHALL BE WALL-MOUNTED 60" AFF. MUST ALLOW LOCK DOWN OF CHUTE INTAKES FOR EXCHANGING CONTAINERS AND WASHING CHUTES. REQUIRES 120V 15A DEDICATED SERVICE.
9. AC: 2HP CHUTE AIR COMPRESSOR SHALL BE MOUNTED72" AFF. REQUIRES 110V 15A SERVICE OUTLETS.
10. OC: ODOR CONTROL UNIT SHALL BE WALL-MOUNTED 60" AFF. REQUIRES 120V 15A SERVICE OUTLETS.
11. HB: HOT AND COLD HOSE BIB SHALL BE WALL-MOUNTED 60" AFF.
12. PROVIDE ELECTRIC PALLET TRUCK FOR TRANSFERRING CONTAINERS. 4000lb CAPACITY; TURNING RADIUS: 45.5". REQUIRES 120V 15A SERVICE OUTLETS.
13. CHUTE DISCHARGE DOOR: TYPE-A, HORIZONTALLY INSULATED SLIDING-STEEL DOOR, HELD OPEN BY 165° F FUSIBLE LINK.
14. (1) UNDEDICATED 120V 15A SERVICE OUTLET REQUIRED FOR STAFF MAINTENANCE PURPOSE.
CHUTE INTAKE VESTIBULES:
15. CHUTE INTAKE VESTIBULES SHALL BE 1HR FIRE-RATED WITH 1HR FIRE-RATED DOOR; 5'-0" MIN REQUIRED PER ADA STANDARDS - RESIDENTIAL ACCESS. PROVIDE (3) SELF CLOSING, 15x18 BOTTOM
HINGED, ELECTRICALLY INTERLOCKED, AUTOMATIC OPENING INTAKE DOORS TO DISPOSE TRASH AND RECYCLING PER CBC 713.13.1. POWER TO INTAKE DOORS SUPPLIED BY MCP. SEE DETAIL 1T2.0.
16. CHUTE SHAFT SHALL NOT BE ERECTED UNTIL CHUTE HAS BEEN INSTALLED. FOR SOUND PROOFING PURPOSES, DOUBLE STUD-WALLS ARE REQUIRED ADJACENT TO OCCUPIED SPACES. INTERIOR OF SHAFT SHALL BE TAPED TO PREVENT ODOROUS AIR LEAKING INTO OCCUPIED SPACES (BY OTHERS).
17. PROVIDE 18X18 SIDE HINGED, AUTOMATIC OPENING, ELECTRICALLY INTERLOCKED THRU-WALL INTAKE DOORS THAT DISPOSE INTO CONTAINERS PER CBC 713.13.1. SEE DETAILS 2/T2.0.
18. PROVIDE ROUND FLOOR OPENINGS AT CONCRETE FLOORS AND SQUARED FLOOR OPENINGS AT WOOD-FRAME CONSTRUCTION. INSTALL FLOOR SUPPORT FRAME AT EACH FLOOR PENETRATION TO SECURE CHUTE. SEE DETAIL 9/T2.0 FOR ANCHORING AND MASON BRA-RED SOUND ISOLATION PAD ASSEMBLY. POUR RINGS WILL VARY BASED ON THICKNESS OF FLOOR SLAB AND SHALL BE PROVIDED BY MANUFACTURER.
GENERAL NOTES:
1. ANY DESIGNS OR DESIGN SOLUTIONS PRESENTED IN THIS DRAWING OR SPECIFICATION, WHICH ARE
DIRECT OR IMPLIED, INCLUDING NARRATIVES, DRAWINGS, OR DIAGRAMS, ARE HEREBY CLARIFIED AS
EXAMPLES AND SHALL NOT BE CONSIDERED COMPLETE DESIGNS OR DESIGNS SUITABLE FOR CONSTRUCTION.
2. OMISSIONS FROM DRAWINGS OR SPECIFICATIONS, OR THE INACCURATE DESCRIPTION OF DETAILS OF
WORK, WHICH ARE MANIFESTLY NECESSARY TO CARRY OUT THE INTENT OF THE DRAWINGS AND
SPECIFICATIONS, OR WHICH ARE CUSTOMARILY PERFORMED, SHALL NOT RELIEVE THE CONTRACTOR FROM PERFORMING SUCH OMITTED OR INACCURATELY DESCRIBED DETAILS OF THE WORK. WORK
SHALL BE PERFORMED AS IF FULLY AND CORRECTLY SET FORTH AND DESCRIBED IN THE DRAWINGS AND SPECIFICATIONS.
3. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO START OF CONSTRUCTION. THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY OF ALL EXISTING FIELD CONDITIONS AND ANY DISCREPANCIES OR INCONSISTENCIES.
LEVEL 1.5
LEVEL 1
LEVEL 1.5
LEVEL 1
96 GAL.
REC PR
35 GAL FOOD SCRAP CART
35 GAL.
96 GAL CART
96 GAL.
HOPPER W/
THRU-WALL OPENING
HOPPER
TRASH COLLECTION ROOM- LOOSE
LEVEL3-8
TRASH
96 GAL.
REC MC
U-LINE
COLLAPSIBLE
WIRE
CONTAINER
MODEL H-1731
3412" HEIGHT
3 FT
ACCESS
DOOR
FOOD
SCRAPS
35 GAL.
3 CY
WASTE
CONTAINER
96 GAL.
REC PR
CHUTE
MASTER
CONTROL
SERVICE OUTLETS. (TYP)
AIR COMPRESSORS
3 CY
WASTE
CONTAINER
3 CY
WASTE
CONTAINER
3 CY
WASTE
CONTAINER
ELECTRIC
PALLET JACK
F.D.
B-3
B-2
B-1
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC MC
96 GAL.
REC MC
96 GAL.
REC MC
96 GAL.
REC MC
ODOR CONTROL
WHEEL STOP 12"W x 5"H
WASTE
E
11TRASH COLLECTION ROOM- LOOSE
LEVEL 1
HOT/COLD
HOSE BIB
HOT/COLD
HOSE BIB
AMERICAN TRASH MANAGEMENT
1900 POWELL STREET, SUITE 220
EMERYVILLE, CALIFORNIA 94608
P: 415.292.5400
F: 415.292.5410
[email protected]
DRAWING TITLE
1150 - 1170 SAN ZENO W
SUNNYVALE, CA
PROJECT NO.
PROJECT
PK
DRAWN
APPROVED
DRAWING NO.
CONSULTANT
MAIN TRASH COLLECTION R
TR1
ARCHITECT
OWNER / DEVELOPER
NO. DATE ISSUE / REVISION
BDE - JONES
PROMETHIUS
SS
15. LIGHTING TO BE MOTION-ACTIVATED.
16. 17.
18. 19.
ODOR CONTROL PROVIDED IN EACH TRASH DISPOSAL ROOM20.
TRASH EXHIBIT
MAIN TRASH COLLECTION ROOM
Attachment 6
135
LU SUBMITTAL 05 JULY 05, 2023
E
TRASH
D
5.2 3 CY
WASTE
CONTAINER
96 GAL.
REC MC
96 GAL.
REC PR
96 GAL.
REC MC
96 GAL.
REC PR
3 CY
WASTE
CONTAINER
3 CY
WASTE
CONTAINER
3 CY
CARDBOARD
CONTAINER
10'-0" ROLL-UP DOOR
96 GAL.
REC MC
96 GAL.
REC PR
3 FT
ACCESS
DOOR
HOT/COLD
HOSE BIB
SECONDARY TRASH COLLECTION ROOM- LOOSE
LEVEL 1
3 FT
ACCESS
DOOR
U-LINE
COLLAPSIBLE WIRE
CONTAINER
MODEL H-1731
FOOD
SCRAPS
35 GAL.
CHUTE MASTER CONTROL
120V 15A
SERVICE OUTLET. (TYP)
ODOR CONTROL
AIR COMPRESSOR
WHEEL STOP
12"W x 5"H
3 FT
ACCESS
DOOR
96 GAL.
REC PR
96 GAL.
REC MC
F.D.
3 FT
ACCESS
DOOR
U-LINE
COLLAPSIBLE WIRE
CONTAINER
MODEL H-1731
3412" HEIGHT
FOOD
SCRAPS
35 GAL.
REC
PR
REC
MC
W
CHUTE VESTIBULE
LEVEL 3-8
DRAWING TITLE
1150 - 1170 SAN ZENO WAY
SUNNYVALE, CA
PROJECT NO.
PROJECT
PK
DRAWN
APPROVED
DATE
SCALE
DRAWING NO.
SECONDARY TRASH COLLECTION ROOM
TR1.1
NO. DATE ISSUED BYISSUE / REVISION
SS
02/27/23
1/4" = 1' - 0"
6. ROOM SHALL BE MECHANICALLY VENTILATED WITH (1) CFM/FT PER 2019 CBC.
7. (1) 30"Ø GRAVITY CHUTE FOR LOOSE WASTE & (2) 24"Ø GRAVITY CHUTES FOR PAPER & CONTAINER RECYCLING. CHUTES SHALL TERMINATE AT 5'-9" AFF.
8. MCP: CHUTE MASTER CONTROL PANEL SHALL BE WALL-MOUNTED 60" AFF. MUST ALLOW LOCK DOWN OF CHUTE INTAKES FOR EXCHANGING CONTAINERS AND WASHING CHUTES. REQUIRES 120V 15A DEDICATED SERVICE.
9. AC: 2HP CHUTE AIR COMPRESSOR SHALL BE MOUNTED72" AFF. REQUIRES 110V 15A SERVICE OUTLETS.
10. OC: ODOR CONTROL UNIT SHALL BE WALL-MOUNTED 60" AFF. REQUIRES 120V 15A SERVICE OUTLETS.
11. HB: HOT AND COLD HOSE BIB SHALL BE WALL-MOUNTED 60" AFF.
12. PROVIDE ELECTRIC PALLET TRUCK FOR TRANSFERRING CONTAINERS. 4000lb CAPACITY; TURNING RADIUS: 45.5". REQUIRES 120V 15A SERVICE OUTLETS.
13. CHUTE DISCHARGE DOOR: TYPE-A, HORIZONTALLY INSULATED SLIDING-STEEL DOOR, HELD OPEN BY 165° F FUSIBLE LINK.
14. (1) UNDEDICATED 120V 15A SERVICE OUTLET REQUIRED FOR STAFF MAINTENANCE PURPOSE.
CHUTE INTAKE VESTIBULES:
15. CHUTE INTAKE VESTIBULES SHALL BE 1HR FIRE-RATED WITH 1HR FIRE-RATED DOOR; 5'-0" MIN REQUIRED PER ADA STANDARDS - RESIDENTIAL ACCESS. PROVIDE (3) SELF CLOSING, 15x18 BOTTOM
HINGED, ELECTRICALLY INTERLOCKED, AUTOMATIC OPENING INTAKE DOORS TO DISPOSE TRASH AND RECYCLING INTO PER CBC 713.13.1. POWER TO INTAKE DOORS SUPPLIED BY MCP. SEE DETAIL 1T2.0.
16. CHUTE SHAFT SHALL NOT BE ERECTED UNTIL CHUTE HAS BEEN INSTALLED. FOR SOUND PROOFING PURPOSES, DOUBLE STUD-WALLS ARE REQUIRED ADJACENT TO OCCUPIED SPACES. INTERIOR OF SHAFT SHALL BE TAPED TO PREVENT ODOROUS AIR LEAKING INTO OCCUPIED SPACES (BY OTHERS).
17. PROVIDE 18X18 SIDE HINGED, AUTOMATIC OPENING, ELECTRICALLY INTERLOCKED THRU-WALL INTAKE DOORS THAT DISPOSE INTO CONTAINERS PER CBC 713.13.1. SEE DETAILS 2/T2.0.
18. PROVIDE ROUND FLOOR OPENINGS AT CONCRETE FLOORS AND SQUARED FLOOR OPENINGS AT WOOD-FRAME CONSTRUCTION. INSTALL FLOOR SUPPORT FRAME AT EACH FLOOR PENETRATION TO SECURE CHUTE. SEE DETAIL 9/T2.0 FOR ANCHORING AND MASON BRA-RED SOUND ISOLATION PAD ASSEMBLY. POUR RINGS WILL VARY BASED ON THICKNESS OF FLOOR SLAB AND SHALL BE PROVIDED BY MANUFACTURER.
GENERAL NOTES:
1. ANY DESIGNS OR DESIGN SOLUTIONS PRESENTED IN THIS DRAWING OR SPECIFICATION, WHICH ARE
DIRECT OR IMPLIED, INCLUDING NARRATIVES, DRAWINGS, OR DIAGRAMS, ARE HEREBY CLARIFIED AS
EXAMPLES AND SHALL NOT BE CONSIDERED COMPLETE DESIGNS OR DESIGNS SUITABLE FOR CONSTRUCTION.
2. OMISSIONS FROM DRAWINGS OR SPECIFICATIONS, OR THE INACCURATE DESCRIPTION OF DETAILS OF
WORK, WHICH ARE MANIFESTLY NECESSARY TO CARRY OUT THE INTENT OF THE DRAWINGS AND
SPECIFICATIONS, OR WHICH ARE CUSTOMARILY PERFORMED, SHALL NOT RELIEVE THE CONTRACTOR FROM PERFORMING SUCH OMITTED OR INACCURATELY DESCRIBED DETAILS OF THE WORK. WORK
SHALL BE PERFORMED AS IF FULLY AND CORRECTLY SET FORTH AND DESCRIBED IN THE DRAWINGS AND SPECIFICATIONS.
3. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO START OF CONSTRUCTION. THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY OF ALL EXISTING FIELD CONDITIONS AND ANY DISCREPANCIES OR INCONSISTENCIES.
E
TRASH
D
3 CY
WASTE
CONTAINER
96 GAL.
REC MC
96 GAL.
REC PR
96 GAL.
REC MC
96 GAL.
REC PR
3 CY
WASTE
CONTAINER
3 CY
WASTE
CONTAINER
3 CY
CARDBOARD
CONTAINER
10'-0" ROLL-UP DOOR
96 GAL.
REC MC
96 GAL.
REC PR
96 GAL.
REC MC
96 GAL.
REC PR
3 CY
WASTE
CONTAINER
SECTION C-1
3 FT
ACCESS
DOOR
HOT/COLD
HOSE BIB
SECONDARY TRASH COLLECTION ROOM- LOOSE
LEVEL 1
3 FT
ACCESS
DOOR
U-LINE
COLLAPSIBLE WIRE
CONTAINER
MODEL H-1731
3412" HEIGHT
FOOD
SCRAPS
35 GAL.
REC
PR
REC
MC
W
120V 15A
SERVICE OUTLET. (TYP)
CONTROL
AIR COMPRESSOR
WHEEL STOP
12"W x 5"H
3 FT
ACCESS
DOOR
CHUTE VESTIBULE
LEVEL 3-8
HOPPER W/
THRU-WALL
OPENING
96 GAL.
REC PR
96 GAL.
REC MC
F.D.
AMERICAN TRASH MANAGEMENT
1900 POWELL STREET, SUITE 220
EMERYVILLE, CALIFORNIA 94608
P: 415.292.5400
F: 415.292.5410
[email protected]
DRAWING TITLE
1150 - 1170 SAN ZENO WAY
SUNNYVALE, CA
PROJECT NO.
PROJECT
PK
DRAWN
APPROVED
DATE
SCALE
DRAWING NO.
CONSULTANT
SECONDARY TRASH COLLECTION ROOM
TR1.1
ARCHITECT
OWNER / DEVELOPER
NO. DATE ISSUED BYISSUE / REVISION
BDE - JONES
PROMETHIUS
SS
02/27/23
1/4" = 1' - 0"
AMERICAN TRASH MANAGEMENT
1900 POWELL STREET, SUITE 220
EMERYVILLE, CALIFORNIA 94608
P: 415.292.5400
F: 415.292.5410
[email protected]
CONSULTANT
BDE - JONES
TRASH STAGING AREA MAIN TRASH COLLECTION ROOM SECONDARY TRASH COLLECTION ROOM
PATH OF TRAVEL FROM TOWN HOUSES TO TRASH
COLLECTION ROOM
WASTE
FOOD
SCRAPS
35 GAL.
REC PR
U-LINE
COLLAPSIBLE
WIRE
CONTAINER
MODEL H-1731
3412" HEIGHT
REC MC
3 FT
ACCESS
DOOR
96 GAL.
REC PR
WASTE
30"Ø CHUTE
HOPPER
96 GAL.
REC PR
18x18 SH AUTOMATIC OPENING
THRU-WALL INTAKE DOOR
SEE NOTE 17
SECTION B-1 SECTION B-2
HOPPER
18x18 SH AUTOMATIC OPENING
THRU-WALL INTAKE DOOR
SEE NOTE 17
SECTION B-3
24"Ø CHUTE
LEVEL 2
WASTE
SHEET NOTES:
RESIDENTIAL TRASH TERMINATION ROOM
1. TRASH COLLECTION ROOM IS PART OF 2HR FIRE-RATED TRASH CHUTE SHAFT - RESTRICTED ACCESS.
2. FLOOR SHALL BE FINISHED WITH WATERPROOF DECK COATING. FLOOR TO HAVE MINIMAL SLOPE (1° MAX) AND FLOOR DRAIN. FLOOR LEVEL UNDER COMPACTOR.
3. WALLS SHALL BE FINISHED WITH WASHABLE WATERPROOF SURFACE SUCH AS FRP OR HIGH-GLOSS ENAMEL PAINT, 8'-0" AFF.
4. INSTALL WALL PROTECTION: 12"Wx5"H CONCRETE CURB AT BASE OF ALL NON-CONCRETE WALLS. DO NOT INSTALL THE CURB AROUND THE COMPACTORS/BISORTER OR POWER PACKS.
5. 10'-0" ROLL UP DOOR AND 3FT EXIT DOOR.
6. ROOM SHALL BE MECHANICALLY VENTILATED WITH (1) CFM/FT PER 2019 CBC.
7. (1) 30"Ø GRAVITY CHUTE FOR LOOSE WASTE & (2) 24"Ø GRAVITY CHUTES FOR PAPER & CONTAINER RECYCLING. CHUTES SHALL TERMINATE AT 5'-9" AFF.
8. MCP: CHUTE MASTER CONTROL PANEL SHALL BE WALL-MOUNTED 60" AFF. MUST ALLOW LOCK DOWN OF CHUTE INTAKES FOR EXCHANGING CONTAINERS AND WASHING CHUTES. REQUIRES 120V 15A DEDICATED SERVICE.
9. AC: 2HP CHUTE AIR COMPRESSOR SHALL BE MOUNTED72" AFF. REQUIRES 110V 15A SERVICE OUTLETS.
10. OC: ODOR CONTROL UNIT SHALL BE WALL-MOUNTED 60" AFF. REQUIRES 120V 15A SERVICE OUTLETS.
11. HB: HOT AND COLD HOSE BIB SHALL BE WALL-MOUNTED 60" AFF.
12. PROVIDE ELECTRIC PALLET TRUCK FOR TRANSFERRING CONTAINERS. 4000lb CAPACITY; TURNING RADIUS: 45.5". REQUIRES 120V 15A SERVICE OUTLETS.
13. CHUTE DISCHARGE DOOR: TYPE-A, HORIZONTALLY INSULATED SLIDING-STEEL DOOR, HELD OPEN BY 165° F FUSIBLE LINK.
14. (1) UNDEDICATED 120V 15A SERVICE OUTLET REQUIRED FOR STAFF MAINTENANCE PURPOSE.
CHUTE INTAKE VESTIBULES:
15. CHUTE INTAKE VESTIBULES SHALL BE 1HR FIRE-RATED WITH 1HR FIRE-RATED DOOR; 5'-0" MIN REQUIRED PER ADA STANDARDS - RESIDENTIAL ACCESS. PROVIDE (3) SELF CLOSING, 15x18 BOTTOM
HINGED, ELECTRICALLY INTERLOCKED, AUTOMATIC OPENING INTAKE DOORS TO DISPOSE TRASH AND RECYCLING PER CBC 713.13.1. POWER TO INTAKE DOORS SUPPLIED BY MCP. SEE DETAIL 1T2.0.
16. CHUTE SHAFT SHALL NOT BE ERECTED UNTIL CHUTE HAS BEEN INSTALLED. FOR SOUND PROOFING PURPOSES, DOUBLE STUD-WALLS ARE REQUIRED ADJACENT TO OCCUPIED SPACES. INTERIOR OF SHAFT SHALL BE TAPED TO PREVENT ODOROUS AIR LEAKING INTO OCCUPIED SPACES (BY OTHERS).
17. PROVIDE 18X18 SIDE HINGED, AUTOMATIC OPENING, ELECTRICALLY INTERLOCKED THRU-WALL INTAKE DOORS THAT DISPOSE INTO CONTAINERS PER CBC 713.13.1. SEE DETAILS 2/T2.0.
18. PROVIDE ROUND FLOOR OPENINGS AT CONCRETE FLOORS AND SQUARED FLOOR OPENINGS AT WOOD-FRAME CONSTRUCTION. INSTALL FLOOR SUPPORT FRAME AT EACH FLOOR PENETRATION TO SECURE CHUTE. SEE DETAIL 9/T2.0 FOR ANCHORING AND MASON BRA-RED SOUND ISOLATION PAD ASSEMBLY.
POUR RINGS WILL VARY BASED ON THICKNESS OF FLOOR SLAB AND SHALL BE PROVIDED BY MANUFACTURER.
GENERAL NOTES:
1. ANY DESIGNS OR DESIGN SOLUTIONS PRESENTED IN THIS DRAWING OR SPECIFICATION, WHICH ARE
DIRECT OR IMPLIED, INCLUDING NARRATIVES, DRAWINGS, OR DIAGRAMS, ARE HEREBY CLARIFIED AS
EXAMPLES AND SHALL NOT BE CONSIDERED COMPLETE DESIGNS OR DESIGNS SUITABLE FOR CONSTRUCTION.
2. OMISSIONS FROM DRAWINGS OR SPECIFICATIONS, OR THE INACCURATE DESCRIPTION OF DETAILS OF
WORK, WHICH ARE MANIFESTLY NECESSARY TO CARRY OUT THE INTENT OF THE DRAWINGS AND
SPECIFICATIONS, OR WHICH ARE CUSTOMARILY PERFORMED, SHALL NOT RELIEVE THE CONTRACTOR FROM PERFORMING SUCH OMITTED OR INACCURATELY DESCRIBED DETAILS OF THE WORK. WORK
SHALL BE PERFORMED AS IF FULLY AND CORRECTLY SET FORTH AND DESCRIBED IN THE DRAWINGS AND SPECIFICATIONS.
3. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO START OF CONSTRUCTION. THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY OF ALL EXISTING FIELD CONDITIONS AND ANY DISCREPANCIES OR INCONSISTENCIES.
LEVEL 1.5
LEVEL 1
LEVEL 1.5
LEVEL 1
96 GAL.
REC PR
35 GAL FOOD SCRAP CART
35 GAL.
96 GAL CART
96 GAL.
HOPPER W/
THRU-WALL OPENING
HOPPER
TRASH COLLECTION ROOM- LOOSE
LEVEL3-8
TRASH
96 GAL.
REC MC
U-LINE
COLLAPSIBLE
WIRE
CONTAINER
MODEL H-1731
3412" HEIGHT
3 FT
ACCESS
DOOR
FOOD
SCRAPS
35 GAL.
3 CY
WASTE
CONTAINER
96 GAL.
REC PR
CHUTE
MASTER
CONTROL
SERVICE OUTLETS. (TYP)
AIR COMPRESSORS
3 CY
WASTE
CONTAINER
3 CY
WASTE
CONTAINER
3 CY
WASTE
CONTAINER
ELECTRIC
PALLET JACK
F.D.
B-3
B-2
B-1
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC PR
96 GAL.
REC MC
96 GAL.
REC MC
96 GAL.
REC MC
96 GAL.
REC MC
ODOR CONTROL
WHEEL STOP 12"W x 5"H
WASTE
E
11TRASH COLLECTION ROOM- LOOSE
LEVEL 1
HOT/COLD
HOSE BIB
HOT/COLD
HOSE BIB
AMERIC
1900 PO
EMERYV
P: 415.2
F: 415.2
SBROWN
DRAWING TITLE
11 PROJECT NO.
PROJECT
DRAWN
APPROVED
DATE
SCALE
CONSULTANT
MAIN
ARCHITECT
OWNER / DEVELOP
NO. DA
BDE -
PROME
02 3/16"
15. LIGHTING TO BE MOTION-ACTIVATED.
ODOR CONTROL PROVIDED IN EACH TRASH DISPOSAL ROOM
16. 17.
18. 19.
20. TRASH EXHIBIT
SECONDARY TRASH COLLECTION ROOM
Attachment 6
SUBMITTAL 05 JULY 05, 2023
3'-8" 3'-8" 3'-8"
6'-9"
3-8
WHEEL STOPS
12"W X 5"H
16'
16'-11
2"
COLLECTION AREA 1
19'-10"
6'-9"
4'-6"
6'-9"
4'-6"
10'
HOLD OPEN DOOR USING
CANE BOLT
NEIGHBORING OFFICE AND
RESIDENTIAL TO BE BILLED
SEPARATELY. DESIGN BASED ON
CURRENT SITUATION
COLLECTION AREAS
SEPARATED BY
ENCLOSURE WALL
ENCLOSURE
USED FOR STAGING ONLY
(REDISTRICTED ACCESS
TO STAFF AND HAULER
ONLY)
CENTRAL TRASH ENCLOSURE | EXISTING OFFICE BUILDINGS
FRONT-LOAD WASTE SERVICE
(7) LOOSE WASTE CONTAINERS STAGED 3X
WEEK, NOT DURING CART SERVICE DAYS
NOTES:
1. STRESS PAD MATERIAL: 5 INCH AGGREGATE BASE (CLASS II COMPACTED )WITH A 6 INCH PORTLAND CEMENT OVERLAY.
6'-9"
3'-8"
WHEEL STOPS
12"W X 5"H
16'
16'-11
2" 19'-10"
6'-9"
4'-6"
6'-9"
4'-6"
10'
HOLD OPEN DOOR USING
CANE BOLT
HOLD OPEN DOOR
USING CANE BOLT
with gates to open to
150 degrees
COLLECTION AREAS
SEPARATED BY
ENCLOSURE WALL
ENCLOSURE
USED FOR STAGING ONLY
(REDISTRICTED ACCESS
TO STAFF AND HAULER
ONLY)
96 GAL.
REC
6"
96 GAL.
REC
6"
96 GAL.
REC
6"
96 GAL.
REC
96 GAL.
REC
6"
96 GAL.
REC
6"
96 GAL.
REC
6"
96 GAL.
REC
6"
96 GAL.
REC
6"
96 GAL.
REC
6"
96 GAL.
REC
6"
96 GAL.
REC
6"
96 GAL.
REC
6"
96 GAL.
REC
96 GAL.
REC
96 GAL.
REC
3CY LOOSE
CARDBOARD
STAGED CONTAINER
(16)
CARTS STAGED 2 x WEEK (RECYCLING 1
DAY, FOODSCRAPS 1 DAY) NOT DURING
WASTE SERVICE DAYS
SPECIFICATIONS, OR WHICH ARE CUSTOMARILY PERFORMED, SHALL NOT RELIEVE THE CONTRACTOR FROM PERFORMING SUCH OMITTED OR INACCURATELY DESCRIBED DETAILS OF THE WORK. WORK
SHALL BE PERFORMED AS IF FULLY AND CORRECTLY SET FORTH AND DESCRIBED IN THE DRAWINGS AND SPECIFICATIONS.
3. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND CONDITIONS PRIOR TO START OF CONSTRUCTION. THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY OF ALL EXISTING FIELD CONDITIONS AND ANY DISCREPANCIES OR INCONSISTENCIES.
AMERICAN TRASH MANAG
1900 POWELL STREET, SU
EMERYVILLE, CALIFORNIA
P: 415.292.5400
F: 415.292.5410
SBROWN@TRASHMANAGE
DRAWING TITLE
1150 - 1170 SA
SUNNYVA
PROJECT NO.
PROJECT
PK
DRAWN
APPROVED
DATE
SCALE
CONSULTANT
TRASH STAGIN
ARCHITECT
OWNER / DEVELOPER
NO. DATE ISSU
BDE - JONES
PROMETHIUS
SS
02/27/23
1/32" = 1' - 0"CENTRAL TRASH ENCLOSURE |RESIDENTIAL BUILDING & EXISTING OFFICE BUILDINGS
AMERICAN TRASH MANAGEMENT
1900 POWELL STREET, SUITE 220
EMERYVILLE, CALIFORNIA 94608
P: 415.292.5400
F: 415.292.5410
[email protected]
CONSULTANT
BDE - JONES
TRASH STAGING AREA MAIN TRASH COLLECTION ROOM SECONDARY TRASH COLLECTION ROOM
PATH OF TRAVEL FROM TOWN HOUSES TO TRASH
COLLECTION ROOM
TRASH EXHIBIT
TRASH STAGING ENCLOSURE
COLLECTION AREA 2
COLLECTION AREA 1 COLLECTION AREA 2
NEIGHBORING OFFICE AND
RESIDENTIAL TO BE BILLED
SEPARATELY. DESIGN BASED ON
CURRENT SITUATION
14-0"
CANE BOLT SLEEVE LOCATION
CANE BOLT SLEEVE LOCATION
3CY LOOSE
WASTE STAGED
CONTAINER
3CY LOOSE
WASTE STAGED
CONTAINER
3CY LOOSE
WASTE STAGED
CONTAINER
3CY LOOSE
WASTE STAGED
CONTAINER
3CY LOOSE
WASTE STAGED
CONTAINER
3CY LOOSE
WASTE STAGED
CONTAINER
3CY LOOSE
WASTE STAGED
CONTAINER
CANE BOLT SLEEVE LOCATION
CANE BOLT SLEEVE LOCATION
Two 4 cyd garbage bins
One 3 cyd garbage bin
Two 3 cyd cardboard bins
Two 35-gallon food scraps carts
Additional Notes (To Be Confirmed by Code and Included In Construction Drawings):
- Bins must have one-foot space between them side-to-side, four-foot space between them front-to-front. - Per each enclosure, given the containers required for each business (Per Notes Above), show the bins/carts installed inside the enclosures respectively. Provide bin dimensions and label them for material type. - Stress pads begin at the end flooring of the enclosure/gates outward. Account for the truck being 10 ft. wide, and the fact that open gates will take up 3 ft. Enlarge width of pad to 14 ft. for operational space. - Include 12" X 5" Wheels Stops
- Install and label cane bolts on gates, cane bolt sleeves installed at closed and open to 150 degrees.
U L 136
Revised 9.22.2023
One 3 cyd cardboard bin
@ 3X/wk
One 4 cyd garbage bin @
2X/wk
One 35-gallon food scraps
cart @ 1-2X/wk
One 3 cyd cardboard bin @
2X/wk
Two 3 cyd garbage bins @
2X/wk with one of the two
@ 3X/wk
One 35-gallon food scraps
cart @ 1-2X/wk.
HOLD OPEN DOOR USING CANE BOLT
with gates to open to
150 degrees
The highest number
of bins to be staged
on any one day would
be three bins given
materials are
collected on separate
days. This diagram is
for informational
staging purposes
only.
SHALL BE PERFORMED AS IF FULLY AND CORRECTLY SET FORTH AND DESC AND SPECIFICATIONS.
3. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND CONDITIONS CONSTRUCTION. THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY O CONDITIONS AND ANY DISCREPANCIES OR INCONSISTENCIES.
137
LU SUBMITTAL 05 JULY 05, 2023
Sunnyvale Front Load Truck-32.3 Sunnyvale Front Load Truck-32.3 6'-9"
3'-8"
1'
6'-9"
3'-8"
1'
6'-9"
1'
6'-9"
3'-8"
1'
6'-9"
3'-8"
1'
6'-9"
3'-8"
1' 6'-9"
3'-8"
16'
16'-11
2"
NEIGHBORING OFFICE
19'-10"
RESIDENTIAL
6'-9"
4'-6" 1'
6'-9"
4'-6"
6'-9"
4'-6"1'
6'-9"
4'-6"
5'
10'
3'-8"
DN
UP
UP
UP
UP
15 28'-7 5/8"3/8"29'-6"
3 BED TOWNHOME 2 BED TOWNHOME
TRASH
3 BED TOWNHOME 2 BED TOWNHOME
STAIR 4
ELEV 4 ELEV 3
MECHANICAL
ELEC
3 BED TOWNHOME 2 BED TOWNHOME 2 BED TOWNHOME 3 BED TOWNHOME
7.28.18.29.110.111.112.112.313.113.216
2'-5 1/4"
16'-4
1/4"
14'-2
1/2" 21'-0" 15'-6" 21'-0" 21'-0" 25'-0"
21'-8
1/2"
13'-10
3/4"
25'-10
3/4" 21'-0"
245'-5 1/4"
SL
AL
SL
AL
Sunnyvale Front Load Truck-32.3
Sunnyvale Front Load Truck-32.3
x1
xA
F
G
J
115'-10"
xB
RAMP UP
28'-5"
27'-7"
3 BED TOWNHOME
3 BED TOWNHOME
PACKAGE ROOM
BOH
PARLOR
THE POST
OFFICE
STAIR 1
ELEV 1 & 2
90.00°
RESIDENTIAL
PARKING
R.R.
xC
H
x3
x4
x2
xA.1
28'-6"25'-7"4'-11"
25'-0"
25'-0"
17'-4 1/2"
11'-9"
56'-0"
73'-6"
xDEV
EV
EV
SL
AL
EV
EV
EV
SL
AL
Sunnyvale Front Load Truck-32.3
Sunnyvale Front Load Truck-32.3 Sunnyvale Front Load Truck-32.3
SOUTH PARCEL
2 ACRES
6'-9"
3'-8"
1'
6'-9"
3'-8"
1'
6'-9"
1'
6'-9"
3'-8"
1'
6'-9"
3'-8"
1'
6'-9"
3'-8"
1' 6'-9"
3'-8"
16'
16'-11
2"
NEIGHBORING OFFICE
19'-10"
RESIDENTIAL
6'-9"
4'-6" 1'
6'-9"
4'-6"
6'-9"
4'-6"1'
6'-9"
4'-6"
5'
10'
3'-8"
Sunnyvale Front Load Truck-32.3
DN
UP
UP
DN
DN
UP
UP
UP
x1
x7
xA
A
L
15 15
2.14567891014
B
E
F F
G G
J J
K K
12 115'-10"
60'-0"18'-0"
xB
RAMP UP
2'-5 1/4" 12'-0"
29'-11
1/4" 27'-6" 27'-6" 27'-6" 27'-6" 27'-6" 27'-6" 27'-6"
22'-0
3/4" 30'-2" 14'-4" 28'-7" 17'-6"
3'-6 1/4"
28'-7 5/8"
23'-4
3/8"29'-6"28'-6"30'-6"14'-6"
6'-4 1/4"
28'-5"
27'-7"
3 BED TOWNHOME 2 BED TOWNHOME
TRASH
3 BED TOWNHOME 2 BED TOWNHOME 3 BED TOWNHOME
TRASH
3 BED TOWNHOME
3 BED TOWNHOME
3 BED TOWNHOME
THE SHOP
PACKAGE ROOM
BOH
PARLOR
THE POST
OFFICE
TRANSFORMER
1 24'-0"
DRIVE
AISLE
24'-0"
DRIVE AISLE
STAIR 2
STAIR 1
STAIR 3
STAIR 4
ELEV 4 ELEV 3
ELEV 1 & 2
164'-10
1/2"
90.00°
ELECTRICALUTILITY
RESIDENTIAL
PARKING
ELECTRICAL
ELECTRICAL
MECHANICAL
ELEC
ELEC
R.R.
C
13 3 BED TOWNHOME 2 BED TOWNHOME 2 BED TOWNHOME 3 BED TOWNHOME xC
24'-0"
DRIVE
AISLE
211
D
H
x3
x4
x5
x6
3 x2
5.26.17.28.18.29.110.111.112.112.313.113.2
xA.1
28'-6"25'-7"4'-11"14'-6"
18'-0"
18'-8
1/2"
25'-0"
25'-0"
17'-4 1/2"
11'-9"
56'-0"
73'-6"
xD
70'-4"
16 16
2'-5 1/4"
16'-4
1/4"
14'-2
1/2" 21'-0" 15'-6" 21'-0" 21'-0" 25'-0"
21'-8
1/2"
13'-10
3/4"
25'-10
3/4" 21'-0"
26'-5
1/4"
245'-5 1/4"
349'-6 1/4"
70'-4"
AMERICAN TRASH MANAGEMEN
1900 POWELL STREET, SUITE 2
EMERYVILLE, CALIFORNIA 9460
P: 415.292.5400
F: 415.292.5410
[email protected]
DRAWING TITLE
1150 - 1170 SAN Z
SUNNYVALE,
PROJECT NO.
PROJECT
PK
DRAWN
APPROVED
DATE
DRAWIN
CONSULTANT
TRASH PICKUP TRUCK
ARCHITECT
OWNER / DEVELOPER
NO. DATE ISSUE / REV
BDE - JONES
PROMETHIUS
SS
02/27/23
TRASH PICKUP TRUCK
ENTERING AND EXITING THE PROPERTY
STAGING LOCATION AND TURN STUDY
TRUCK DIMENSIONS
SCALE: 1/32" = 1' - 0"
SCALE: 1/32" = 1' - 0"
SCALE: 1/16" = 1' - 0"
Sunnyvale Front Load Truck-32.3 Sunnyvale Front Load Truck-32.3 DN
UP
UP
UP
UP
15 28'-7 5/8"3/8"29'-6"
3 BED TOWNHOME 2 BED TOWNHOME
TRASH
3 BED TOWNHOME 2 BED TOWNHOME
STAIR 4
ELEV 4 ELEV 3
MECHANICAL
ELEC
3 BED TOWNHOME 2 BED TOWNHOME 2 BED TOWNHOME 3 BED TOWNHOME
7.28.18.29.110.111.112.112.313.113.216
2'-5 1/4"
16'-4
1/4"
14'-2
1/2" 21'-0" 15'-6" 21'-0" 21'-0" 25'-0"
21'-8
1/2"
13'-10
3/4"
25'-10
3/4" 21'-0"
SL
AL
SL
AL
Sunnyvale Front Load Truck-32.3
Sunnyvale Front Load Truck-32.3
x1
xA
F
G
J
115'-10"
xB
RAMP UP
28'-5"
27'-7"
3 BED TOWNHOME
3 BED TOWNHOME
PACKAGE ROOM
BOH
PARLOR
THE POST
OFFICE
STAIR 1
ELEV 1 & 2
90.00°
RESIDENTIAL
PARKING
R.R.
xC
H
x3
x4
x2
xA.1
28'-6"25'-7"4'-11"
25'-0"
25'-0"
17'-4 1/2"
11'-9"
56'-0"
73'-6"
xDEV
EV
EV
SL
AL
EV
EV
EV
SL
AL
Sunnyvale Front Load Truck-32.3
Sunnyvale Front Load Truck-32.3 Sunnyvale Front Load Truck-32.3
SOUTH PARCEL
2 ACRES
6'-9"
3'-8"
1'
6'-9"
3'-8"
1'
6'-9"
1'
6'-9"
3'-8"
1'
6'-9"
3'-8"
1'
6'-9"
3'-8"
1' 6'-9"
3'-8"
16'
16'-11
2"
NEIGHBORING OFFICE
19'-10"
RESIDENTIAL
6'-9"
4'-6" 1'
6'-9"
4'-6"
6'-9"
4'-6"1'
6'-9"
4'-6"
5'
10'
3'-8"
Sunnyvale Front Load Truck-32.3
DN
UP
UP
DN
DN
UP
UP
UP
x1
x7
xA
A
L
15 15
2.14567891014
B
E
F F
G G
J J
K K
12 115'-10"
60'-0"18'-0"
xB
RAMP UP
2'-5 1/4" 12'-0"
29'-11
1/4" 27'-6" 27'-6" 27'-6" 27'-6" 27'-6" 27'-6" 27'-6"
22'-0
3/4" 30'-2" 14'-4" 28'-7" 17'-6"
3'-6 1/4"
28'-7 5/8"
23'-4
3/8"29'-6"28'-6"30'-6"14'-6"
6'-4 1/4"
28'-5"
27'-7"
3 BED TOWNHOME 2 BED TOWNHOME
TRASH
3 BED TOWNHOME 2 BED TOWNHOME 3 BED TOWNHOME
TRASH
3 BED TOWNHOME
3 BED TOWNHOME
3 BED TOWNHOME
THE SHOP
PACKAGE ROOM
BOH
PARLOR
THE POST
OFFICE
TRANSFORMER
1 24'-0"
DRIVE
AISLE
24'-0"
DRIVE AISLE
STAIR 2
STAIR 1
STAIR 3
STAIR 4
ELEV 4 ELEV 3
ELEV 1 & 2
164'-10
1/2"
90.00°
ELECTRICALUTILITY
RESIDENTIAL
PARKING
ELECTRICAL
ELECTRICAL
MECHANICAL
ELEC
ELEC
R.R.
C
13 3 BED TOWNHOME 2 BED TOWNHOME 2 BED TOWNHOME 3 BED TOWNHOME xC
24'-0"
DRIVE
AISLE
211
D
H
x3
x4
x5
x6
3 x2
5.26.17.28.18.29.110.111.112.112.313.113.2
xA.1
28'-6"25'-7"4'-11"14'-6"
18'-0"
18'-8
1/2"
25'-0"
25'-0"
17'-4 1/2"
11'-9"
56'-0"
73'-6"
xD
70'-4"
16 16
2'-5 1/4"
16'-4
1/4"
14'-2
1/2" 21'-0" 15'-6" 21'-0" 21'-0" 25'-0"
21'-8
1/2"
13'-10
3/4"
25'-10
3/4" 21'-0"
26'-5
1/4"
245'-5 1/4"
349'-6 1/4"
70'-4"
EMERY
P: 415.
F: 415.
SBROW
DRAWING TITLE
1 PROJECT NO.
PROJECT
DRAWN
APPROVED
DATE
SCALE
CONSULTANT
TRA
ARCHITECT
OWNER / DEVEL
NO. D
BDE -
PROM
0 1/32
TRASH PICKUP TRUCK
ENTERING AND EXITING THE PROPERTY
STAGING LOCATION AND TURN STUDY
TRUCK DIMENSIONS
SCALE: 1/32" = 1' - 0"
SCALE: 1/32" = 1' - 0"
SCALE: 1/16" = 1' - 0"
ELEV 3
TRASH
58' 60'
60'
LOBBY
ELEV 4
3 BED TOWNHOME 2 BED TOWNHOME 3 BED TOWNHOME 3 BED TOWNHOME 2 BED TOWNHOME2 BED TOWNHOME
STAIR CIRCULATION
CIRCULATION
1 2 3 4 5 6 7 8 9 10 11
3 BED TOWNHOME 2 BED TOWNHOME
ELEC
ELEV 1 & 2
59'
60'
57.6'
3 BED TOWNHOME
3 BED TOWNHOME
STAIR
CIRCULATION
RR
OFFICE
BOH
PACKAGE
LOBBY
MAIL
PARLOR
59.1'
18 19
20 21
ELEC
9' CLR
SL
AL
SL
AL
AMERICAN TRASH MANAGEMENT
1900 POWELL STREET, SUITE 220
EMERYVILLE, CALIFORNIA 94608
P: 415.292.5400
F: 415.292.5410
[email protected]
DRAWING TITLE
1150 - 1170 SAN ZENO WA
SUNNYVALE, CA
PROJECT NO.
PROJECT
PK
DRAWN
APPROVED
DATE
SCALE
DRAWING NO.
CONSULTANT
TRASH PICKUP TRUCK MANEU
TR2.
ARCHITECT
OWNER / DEVELOPER
NO. DATE ISSUE / REVISION
BDE - JONES
PROMETHIUS
SS
10/13/22
1/32" = 1' - 0"
TRASH PICKUP TRUCK
ENTERING AND EXITING THE PROPERTY
STAGING LOCATION AND TURN STUDY
TRUCK DIMENSIONS
SCALE: 1/32" = 1' - 0"
SCALE: 1/32" = 1' - 0"
SCALE: 1/16" = 1' - 0"
ELEV 3
TRASH
58' 60'
60'
LOBBY
ELEV 4
3 BED TOWNHOME 2 BED TOWNHOME 3 BED TOWNHOME 3 BED TOWNHOME 2 BED TOWNHOME2 BED TOWNHOME
STAIR CIRCULATION
CIRCULATION
1 2 3 4 5 6 7 8 9 10 11
3 BED TOWNHOME 2 BED TOWNHOME
ELEC
ELEV 1 & 2
59'
60'
57.6'
3 BED TOWNHOME
3 BED TOWNHOME
STAIR
CIRCULATION
RR
OFFICE
BOH
PACKAGE
LOBBY
MAIL
PARLOR
59.1'
18 19
20 21
ELEC
9' CLR
SL
AL
SL
AL
TRASH PICKUP TRUCK
STAGING LOCATION AND TURN STUDY
TRUCK DIMENSIONS
SCALE: 1/32" = 1' - 0"
TRASH EXHIBIT
TRASH PICKUP TRUCK MANEUVER
Attachment 6
138
LU SUBMITTAL 05 JULY 05, 2023
GPR CHECKLIST
NEW HOME RATING SYSTEM, VERSION 8.2
94.5 Silver
Option 2: All Electric Compliance
0 %
Points
Targeted
Community
Energy
IAQ/Health
Resources
Water
CALGreen
Yes CALGreen (REQUIRED) 4 1 1 1 1
A. SITE
A2. Job Site Construction Waste Diversion
Yes A2.1 70% C&D Waste Diversion (Including Alternative Daily Cover) 2 2 A6. Stormwater Control: Prescriptive Path
Yes A6.2 Filtration and/or Bio-Retention Features 1 1 C. LANDSCAPE
35.31% Enter the landscape area percentage. Points capped at 3 for less than 15%.
Yes C1. Plants Grouped by Water Needs (Hydrozoning) 1 1 Yes C2. Three Inches of Mulch in Planting Beds 1 1
C3. Resource Efficient Landscapes
Yes C3.1 No Invasive Species According to Cal-IPC 1 1 Yes C3.2 Plants Chosen and Located to Grow to Natural Size 1 1 Yes C3.3 Drought Tolerant, Native, Mediterranean Species, or Other Appropriate Species 33
C4. Minimal Turf in Landscape
Yes C4.1 No Turf on Slopes Exceeding 10% and No Overhead Sprinklers Installed in Areas Less Than Eight Feet Wide 2 2
≤10% C4.2 Turf on a Small Percentage of Landscaped Area 2 2 Yes C7. One Inch of Compost in the Top Six to Twelve Inches of Soil 2 2 Yes C10. Submeter or Dedicated Meter for Landscape Irrigation 2 2 Yes C14. Large Stature Tree(s) 1 1
D3. Engineered Lumber
Yes D3.2 OSB for Subfloor 0.5 0.5
D9. Reduced Pollution Entering the Home from the Garage Yes D9.2 Mitigation Strategies for Attached Garage 1 1 D10. Structural Pest and Rot Controls
Yes D10.1 All Wood Located At Least 12 Inches Above the Soil 1 1 E. EXTERIOR
Yes E4. Durable and Non-Combustible Cladding Materials 1 1 E5. Durable Roofing Materials
N/A E5.2 Roofing Warranty for Shingle Roofing Y R R R R R F. INSULATION
F1. Insulation with 30% Post-Consumer or 60% Post-Industrial Recycled Content Yes F1.1 Walls and Floors 0.5 0.5
Yes F1.2 Ceilings 0.5 0.5
F2. Insulation that Meets the CDPH Standard Method—Residential for Low Emissions Yes F2.1 Walls and Floors 0.5 0.5
Yes F2.2 Ceilings 0.5 0.5
F3. Insulation That Does Not Contain Fire Retardants
Yes F3.1 Cavity Walls and Floors 1 1
Yes F3.2 Ceilings 1 1
G. PLUMBING
G2. Install Water-Efficient Fixtures
Yes G2.1 WaterSense Showerheads ≤ 1.8 gpm with Matching Compensation Valve 2 2
1.28 gpf G2.3 WaterSense Toilets with a Maximum Performance (MaP) Threshold of No Less Than 500 Grams ≤ 1.28 gpf OR ≤ 1.1 gpf 1 2
Yes G6. Submeter Water for Tenants 2 2
H1. Sealed Combustion Units
Yes H1.1 Sealed Combustion Furnace 1 1
Yes H1.2 Sealed Combustion Water Heater 2 2
H4. ENERGY STAR® Bathroom Fans
Yes H4.1 ENERGY STAR® Bathroom Fans Per HVI Standards 1 1 H6. Whole House Mechanical Ventilation Practices to Improve Indoor Air Quality Yes H6.1 Meet ASHRAE Standard 62.2-2016 Ventilation Residential Standards Y R R R R R Yes J4. All Electric or Combustion Appliance Safety Testing 1 1 J5. Building Energy Performance
Option 2: All Electric
Compliance J5.1 Home Outperforms Title 24 25.02 25+ Yes J6. Title 24 Prepared and Signed by a CABEC Certified Energy Analyst 1 1 K. FINISHES
K2. Low-VOC Interior Wall and Ceiling Paints
Yes K2.1 Zero-VOC Interior Wall and Ceiling Paints (< 5 gpl) 2 2 L. FLOORING
Yes L3. Durable Flooring 1 1
Yes M1. ENERGY STAR® Dishwasher 1 1
M2. Efficient Clothes Washing and Drying
Yes M2.2 ENERGY STAR® Dryer 1 1
<25 cubic feet M3. Size-Efficient ENERGY STAR® Refrigerator 1 2 Tier 2 Full Circuit M6. Electric Vehicle Charging Stations and Infrastructure 2 2 Yes M8. Gearless Elevator 1 1
N. COMMUNITY
N1. Smart Development
Yes N1.1 Infill Site 2 1 1
>35 N1.3 Conserve Resources by Increasing Density 4 2 2 N1.5 Home Size Efficiency 1 10
836 Enter the area of the home, in square feet 1 Enter the number of bedrooms
N2. Home(s)/Development Located Near Transit
Yes N2.2. Within 1/2 mile of a Major Transit Stop 2 2
M. APPLIANCES AND LIGHTING
D. STRUCTURAL FRAME AND BUILDING ENVELOPE
Blueprint Scoresh
San Zeno
Possible Points
H. HEATING, VENTILATION, AND AIR CONDITIONING
J. BUILDING PERFORMANCE AND TESTING
Points Targeted:
Certification Level Targeted:
Compliance Pathway Targeted:
T24 Compliance Targeted:
NEW HOME RATING SYSTEM, VERSION 8.2
94.5 Silver
Option 2: All Electric Compliance
0 %
Points
Targeted
Community
Energy
IAQ/Health
Resources
Water
CALGreen
Yes CALGreen (REQUIRED) 4 1 1 1 1
A. SITE
A2. Job Site Construction Waste Diversion
Yes A2.1 70% C&D Waste Diversion (Including Alternative Daily Cover) 2 2 A6. Stormwater Control: Prescriptive Path
Yes A6.2 Filtration and/or Bio-Retention Features 1 1 C. LANDSCAPE
35.31% Enter the landscape area percentage. Points capped at 3 for less than 15%.
Yes C1. Plants Grouped by Water Needs (Hydrozoning) 1 1 Yes C2. Three Inches of Mulch in Planting Beds 1 1
C3. Resource Efficient Landscapes
Yes C3.1 No Invasive Species According to Cal-IPC 1 1 Yes C3.2 Plants Chosen and Located to Grow to Natural Size 1 1 Yes C3.3 Drought Tolerant, Native, Mediterranean Species, or Other Appropriate Species 33
C4. Minimal Turf in Landscape
Yes C4.1 No Turf on Slopes Exceeding 10% and No Overhead Sprinklers Installed in Areas Less Than Eight Feet Wide 2 2
≤10% C4.2 Turf on a Small Percentage of Landscaped Area 2 2 Yes C7. One Inch of Compost in the Top Six to Twelve Inches of Soil 2 2 Yes C10. Submeter or Dedicated Meter for Landscape Irrigation 2 2 Yes C14. Large Stature Tree(s) 1 1
D3. Engineered Lumber
Yes D3.2 OSB for Subfloor 0.5 0.5
D9. Reduced Pollution Entering the Home from the Garage Yes D9.2 Mitigation Strategies for Attached Garage 1 1 D10. Structural Pest and Rot Controls
Yes D10.1 All Wood Located At Least 12 Inches Above the Soil 1 1 E. EXTERIOR
Yes E4. Durable and Non-Combustible Cladding Materials 1 1 E5. Durable Roofing Materials
N/A E5.2 Roofing Warranty for Shingle Roofing Y R R R R R F. INSULATION
F1. Insulation with 30% Post-Consumer or 60% Post-Industrial Recycled Content Yes F1.1 Walls and Floors 0.5 0.5
Yes F1.2 Ceilings 0.5 0.5
F2. Insulation that Meets the CDPH Standard Method—Residential for Low Emissions Yes F2.1 Walls and Floors 0.5 0.5
Yes F2.2 Ceilings 0.5 0.5
F3. Insulation That Does Not Contain Fire Retardants
Yes F3.1 Cavity Walls and Floors 1 1
Yes F3.2 Ceilings 1 1
G. PLUMBING
G2. Install Water-Efficient Fixtures
Yes G2.1 WaterSense Showerheads ≤ 1.8 gpm with Matching Compensation Valve 2 2
1.28 gpf G2.3 WaterSense Toilets with a Maximum Performance (MaP) Threshold of No Less Than 500 Grams ≤ 1.28 gpf OR ≤ 1.1 gpf 1 2
Yes G6. Submeter Water for Tenants 2 2
H1. Sealed Combustion Units
Yes H1.1 Sealed Combustion Furnace 1 1
Yes H1.2 Sealed Combustion Water Heater 2 2
H4. ENERGY STAR® Bathroom Fans
Yes H4.1 ENERGY STAR® Bathroom Fans Per HVI Standards 1 1 H6. Whole House Mechanical Ventilation Practices to Improve Indoor Air Quality Yes H6.1 Meet ASHRAE Standard 62.2-2016 Ventilation Residential Standards Y R R R R R Yes J4. All Electric or Combustion Appliance Safety Testing 1 1 J5. Building Energy Performance
Option 2: All Electric
Compliance J5.1 Home Outperforms Title 24 25.02 25+ Yes J6. Title 24 Prepared and Signed by a CABEC Certified Energy Analyst 1 1 K. FINISHES
K2. Low-VOC Interior Wall and Ceiling Paints
Yes K2.1 Zero-VOC Interior Wall and Ceiling Paints (< 5 gpl) 2 2 L. FLOORING
Yes L3. Durable Flooring 1 1
Yes M1. ENERGY STAR® Dishwasher 1 1
M2. Efficient Clothes Washing and Drying
Yes
M2.2 ENERGY STAR® Dryer 1 1
<25 cubic feet M3. Size-Efficient ENERGY STAR® Refrigerator 1 2 Tier 2 Full Circuit M6. Electric Vehicle Charging Stations and Infrastructure 2 2 Yes M8. Gearless Elevator 1 1
N. COMMUNITY
N1. Smart Development
Yes N1.1 Infill Site 2 1 1
>35 N1.3 Conserve Resources by Increasing Density 4 2 2 N1.5 Home Size Efficiency 1 10
836 Enter the area of the home, in square feet 1 Enter the number of bedrooms
N2. Home(s)/Development Located Near Transit
Yes N2.2. Within 1/2 mile of a Major Transit Stop 2 2
M. APPLIANCES AND LIGHTING
D. STRUCTURAL FRAME AND BUILDING ENVELOPE
Blueprint Scoresh
San Zeno
Possible Points
H. HEATING, VENTILATION, AND AIR CONDITIONING
J. BUILDING PERFORMANCE AND TESTING
Points Targeted:
Certification Level Targeted:
Compliance Pathway Targeted:
T24 Compliance Targeted:
N/A E5.2 Roofing Warranty for Shingle Roofing Y R R R R R F. INSULATION
F1. Insulation with 30% Post-Consumer or 60% Post-Industrial Recycled Content Yes F1.1 Walls and Floors 0.5 0.5
Yes F1.2 Ceilings 0.5 0.5
F2. Insulation that Meets the CDPH Standard Method—Residential for Low Emissions
Yes F2.1 Walls and Floors 0.5 0.5
Yes F2.2 Ceilings 0.5 0.5
F3. Insulation That Does Not Contain Fire Retardants
Yes F3.1 Cavity Walls and Floors 1 1
Yes F3.2 Ceilings 1 1
G. PLUMBING
G2. Install Water-Efficient Fixtures
Yes G2.1 WaterSense Showerheads ≤ 1.8 gpm with Matching Compensation Valve 2 2
1.28 gpf G2.3 WaterSense Toilets with a Maximum Performance (MaP) Threshold of No Less Than 500 Grams ≤ 1.28 gpf OR ≤ 1.1 gpf 1 2
Yes G6. Submeter Water for Tenants 2 2
H1. Sealed Combustion Units
Yes H1.1 Sealed Combustion Furnace 1 1
Yes H1.2 Sealed Combustion Water Heater 2 2
H4. ENERGY STAR® Bathroom Fans
Yes H4.1 ENERGY STAR® Bathroom Fans Per HVI Standards 1 1 H6. Whole House Mechanical Ventilation Practices to Improve Indoor Air Quality Yes H6.1 Meet ASHRAE Standard 62.2-2016 Ventilation Residential Standards Y R R R R R Yes J4. All Electric or Combustion Appliance Safety Testing 1 1 J5. Building Energy Performance
Option 2: All Electric
Compliance J5.1 Home Outperforms Title 24 25.02 25+ Yes J6. Title 24 Prepared and Signed by a CABEC Certified Energy Analyst 1 1 K. FINISHES
K2. Low-VOC Interior Wall and Ceiling Paints
Yes K2.1 Zero-VOC Interior Wall and Ceiling Paints (< 5 gpl) 2 2 L. FLOORING
Yes L3. Durable Flooring 1 1
Yes M1. ENERGY STAR® Dishwasher 1 1
M2. Efficient Clothes Washing and Drying
Yes M2.2 ENERGY STAR® Dryer 1 1
<25 cubic feet M3. Size-Efficient ENERGY STAR® Refrigerator 1 2 Tier 2 Full Circuit M6. Electric Vehicle Charging Stations and Infrastructure 2 2 Yes M8. Gearless Elevator 1 1
N. COMMUNITY
N1. Smart Development
Yes N1.1 Infill Site 2 1 1
>35 N1.3 Conserve Resources by Increasing Density 4 2 2 N1.5 Home Size Efficiency 1 10
836 Enter the area of the home, in square feet 1 Enter the number of bedrooms
N2. Home(s)/Development Located Near Transit
Yes N2.2. Within 1/2 mile of a Major Transit Stop 2 2
N3. Pedestrian and Bicycle Access
N3.1 Pedestrian Access to Services Within 1/2 Mile of Community Services 1 2 4 Enter the number of Tier 1 services
5 Enter the number of Tier 2 services
Yes N3.5 Bicycle Storage for Residents 1 1
1 space per unit N3.7 Reduced Parking Capacity 2 2 N4. Outdoor Gathering Places
Yes N4.1 Public or Semi-Public Outdoor Gathering Places for Residents 1 1 N5. Social Interaction
Yes N5.2 Entrances Visible from Street and/or Other Front Doors 1 1 O. OTHER
Yes O1. GreenPoint Rated Checklist in Blueprints Y R R R R R Yes O2. Pre-Construction Kickoff Meeting with Rater and Subcontractors 2 0.5 1 0.5 Yes O7. Green Appraisal Addendum Y R R R R R
Summary Community Energy IAQ/Health Resources Water
Total Available Points in Specific Categories 404.5 47 135.5 73 91 58 Minimum Points Required in Specific Categories 50 2 25 6 6 6 Total Points Targeted 94.52 11 34.52 12 14.5 22.5
M. APPLIANCES AND LIGHTING
H. HEATING, VENTILATION, AND AIR CONDITIONING
J. BUILDING PERFORMANCE AND TESTING
NEW HOME RATING SYSTEM, VERSION 8.2
94.5 Silver
Option 2: All Electric Compliance
0 %
Points
Targeted
Community
Energy
IAQ/Health
Resources
Water
CALGreen (REQUIRED) 4 1 1 1 1
A2. Job Site Construction Waste Diversion
A2.1 70% C&D Waste Diversion (Including Alternative Daily Cover) 2 2 A6. Stormwater Control: Prescriptive Path
A6.2 Filtration and/or Bio-Retention Features 1 1
E
% Enter the landscape area percentage. Points capped at 3 for les s than 15%.
C1. Plants Grouped by Water Needs (Hydrozoning) 1 1
C2. Three Inches of Mulch in Planting Beds 1 1
C3. Resource Efficient Landscapes
C3.1 No Invasive Species According to Cal-IPC 1 1
C3.2 Plants Chosen and Located to Grow to Natural Size 1 1 C3.3 Drought Tolerant, Native, Mediterranean Species, or Other Appropriate Species 33
C4. Minimal Turf in Landscape
C4.1 No Turf on Slopes Exceeding 10% and No Overhead Sprinklers Installed in Areas Less Than Eight Feet Wide 2 2
% C4.2 Turf on a Small Percentage of Landscaped Area 2 2 C7. One Inch of Compost in the Top Six to Twelve Inches of Soil 2 2 C10. Submeter or Dedicated Meter for Landscape Irrigation 2 2 C14. Large Stature Tree(s) 1 1
D3. Engineered Lumber
D3.2 OSB for Subfloor 0.5 0.5
D9. Reduced Pollution Entering the Home from the Garage D9.2 Mitigation Strategies for Attached Garage 1 1
D10. Structural Pest and Rot Controls
D10.1 All Wood Located At Least 12 Inches Above the Soil 1 1 E4. Durable and Non-Combustible Cladding Materials 1 1
E5. Durable Roofing Materials
E5.2 Roofing Warranty for Shingle Roofing Y R R R R R
F1. Insulation with 30% Post-Consumer or 60% Post-Industrial Recycled Content F1.1 Walls and Floors 0.5 0.5
F1.2 Ceilings 0.5 0.5
F2. Insulation that Meets the CDPH Standard Method—Residential for Low Emissions F2.1 Walls and Floors 0.5 0.5
F2.2 Ceilings 0.5 0.5
F3. Insulation That Does Not Contain Fire Retardants
F3.1 Cavity Walls and Floors 1 1
F3.2 Ceilings 1 1
G2. Install Water-Efficient Fixtures
G2.1 WaterSense Showerheads ≤ 1.8 gpm with Matching Compensation Valve 2 2 pf G2.3 WaterSense Toilets with a Maximum Performance (MaP) Threshold of No Less Than 500 Grams ≤ 1.28 gpf OR ≤ 1.1 gpf 1 2
G6. Submeter Water for Tenants 2 2
H1. Sealed Combustion Units
H1.1 Sealed Combustion Furnace 1 1
H1.2 Sealed Combustion Water Heater 2 2
H4. ENERGY STAR® Bathroom Fans
H4.1 ENERGY STAR® Bathroom Fans Per HVI Standards 1 1
H6. Whole House Mechanical Ventilation Practices to Improve Indoor Air Quality H6.1 Meet ASHRAE Standard 62.2-2016 Ventilation Residential Standards Y R R R R R J4. All Electric or Combustion Appliance Safety Testing 1 1 J5. Building Energy Performance
Electric
nce J5.1 Home Outperforms Title 24 25.02 25+
J6. Title 24 Prepared and Signed by a CABEC Certified Energy Analyst 1 1 K2. Low-VOC Interior Wall and Ceiling Paints
K2.1 Zero-VOC Interior Wall and Ceiling Paints (< 5 gpl) 2 2 L3. Durable Flooring 1 1
M1. ENERGY STAR® Dishwasher 1 1
M2. Efficient Clothes Washing and Drying
M2.2 ENERGY STAR® Dryer 1 1
c feet M3. Size-Efficient ENERGY STAR® Refrigerator 1 2 Circuit M6. Electric Vehicle Charging Stations and Infrastructure 2 2 M8. Gearless Elevator 1 1
Y
N1. Smart Development
N1.1 Infill Site 2 1 1
N1.3 Conserve Resources by Increasing Density 4 2 2
N1.5 Home Size Efficiency 1 10
Enter the area of the home, in square feet
Enter the number of bedrooms
N2. Home(s)/Development Located Near Transit
N2.2. Within 1/2 mile of a Major Transit Stop 2 2
S AND LIGHTING
AL FRAME AND BUILDING ENVELOPE
Blueprint Scoresh
eno
Possible Points
ENTILATION, AND AIR CONDITIONING
ERFORMANCE AND TESTING
Points Targeted:
Certification Level Targeted:
Compliance Pathway Targeted:
T24 Compliance Targeted:
NEW HOME RATING SYSTEM, VERSION 8.2
94.5 Silver
Option 2: All Electric Compliance
0 %
Points
Targeted
Community
Energy
IAQ/Health
Resources
Water
CALGreen
Yes CALGreen (REQUIRED) 4 1 1 1 1
A. SITE
A2. Job Site Construction Waste Diversion
Yes A2.1 70% C&D Waste Diversion (Including Alternative Daily Cover) 2 2 A6. Stormwater Control: Prescriptive Path
Yes A6.2 Filtration and/or Bio-Retention Features 1 1 C. LANDSCAPE
35.31% Enter the landscape area percentage. Points capped at 3 for less than 15%.
Yes C1. Plants Grouped by Water Needs (Hydrozoning) 1 1 Yes C2. Three Inches of Mulch in Planting Beds 1 1
C3. Resource Efficient Landscapes
Yes C3.1 No Invasive Species According to Cal-IPC 1 1 Yes C3.2 Plants Chosen and Located to Grow to Natural Size 1 1 Yes C3.3 Drought Tolerant, Native, Mediterranean Species, or Other Appropriate Species 33
C4. Minimal Turf in Landscape
Yes C4.1 No Turf on Slopes Exceeding 10% and No Overhead Sprinklers Installed in Areas Less Than Eight Feet Wide 2 2
≤10% C4.2 Turf on a Small Percentage of Landscaped Area 2 2 Yes C7. One Inch of Compost in the Top Six to Twelve Inches of Soil 2 2 Yes C10. Submeter or Dedicated Meter for Landscape Irrigation 2 2 Yes C14. Large Stature Tree(s) 1 1
D3. Engineered Lumber
Yes D3.2 OSB for Subfloor 0.5 0.5
D9. Reduced Pollution Entering the Home from the Garage Yes D9.2 Mitigation Strategies for Attached Garage 1 1 D10. Structural Pest and Rot Controls
Yes D10.1 All Wood Located At Least 12 Inches Above the Soil 1 1 E. EXTERIOR
Yes E4. Durable and Non-Combustible Cladding Materials 1 1 E5. Durable Roofing Materials
N/A E5.2 Roofing Warranty for Shingle Roofing Y R R R R R F. INSULATION
F1. Insulation with 30% Post-Consumer or 60% Post-Industrial Recycled Content Yes F1.1 Walls and Floors 0.5 0.5
Yes F1.2 Ceilings 0.5 0.5
F2. Insulation that Meets the CDPH Standard Method—Residential for Low Emissions Yes F2.1 Walls and Floors 0.5 0.5
Yes F2.2 Ceilings 0.5 0.5
F3. Insulation That Does Not Contain Fire Retardants
Yes F3.1 Cavity Walls and Floors 1 1
Yes F3.2 Ceilings 1 1
G. PLUMBING
G2. Install Water-Efficient Fixtures
Yes G2.1 WaterSense Showerheads ≤ 1.8 gpm with Matching Compensation Valve 2 2
1.28 gpf G2.3 WaterSense Toilets with a Maximum Performance (MaP) Threshold of No Less Than 500 Grams ≤ 1.28 gpf OR ≤ 1.1 gpf 1 2
Yes G6. Submeter Water for Tenants 2 2
H1. Sealed Combustion Units
Yes H1.1 Sealed Combustion Furnace 1 1
Yes H1.2 Sealed Combustion Water Heater 2 2
H4. ENERGY STAR® Bathroom Fans
Yes H4.1 ENERGY STAR® Bathroom Fans Per HVI Standards 1 1 H6. Whole House Mechanical Ventilation Practices to Improve Indoor Air Quality Yes H6.1 Meet ASHRAE Standard 62.2-2016 Ventilation Residential Standards Y R R R R R Yes J4. All Electric or Combustion Appliance Safety Testing 1 1 J5. Building Energy Performance
Option 2: All Electric
Compliance J5.1 Home Outperforms Title 24 25.02 25+ Yes J6. Title 24 Prepared and Signed by a CABEC Certified Energy Analyst 1 1 K. FINISHES
K2. Low-VOC Interior Wall and Ceiling Paints
Yes K2.1 Zero-VOC Interior Wall and Ceiling Paints (< 5 gpl) 2 2 L. FLOORING
Yes L3. Durable Flooring 1 1
Yes M1. ENERGY STAR® Dishwasher 1 1
M2. Efficient Clothes Washing and Drying
Yes
M2.2 ENERGY STAR® Dryer 1 1
<25 cubic feet M3. Size-Efficient ENERGY STAR® Refrigerator 1 2 Tier 2 Full Circuit M6. Electric Vehicle Charging Stations and Infrastructure 2 2 Yes M8. Gearless Elevator 1 1
N. COMMUNITY
N1. Smart Development
Yes N1.1 Infill Site 2 1 1
>35 N1.3 Conserve Resources by Increasing Density 4 2 2 N1.5 Home Size Efficiency 1 10
836 Enter the area of the home, in square feet 1 Enter the number of bedrooms
N2. Home(s)/Development Located Near Transit
Yes N2.2. Within 1/2 mile of a Major Transit Stop 2 2
M. APPLIANCES AND LIGHTING
D. STRUCTURAL FRAME AND BUILDING ENVELOPE
Blueprint Scoresh
San Zeno
Possible Points
H. HEATING, VENTILATION, AND AIR CONDITIONING
J. BUILDING PERFORMANCE AND TESTING
Points Targeted:
Certification Level Targeted:
Compliance Pathway Targeted:
T24 Compliance Targeted:
Attachment 6
139
LU SUBMITTAL 05 JULY 05, 2023
BB
BB
BB
BB
BB
BB
SS C O
SSCOSS C O
WM
FH
FDC
FH
WHARF
SAN ZENO WAY
BFP
CB
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
SAI
C1+P1
C1+P1C1+P1
C1+P1
0.73 0.42 0.29 0.25 0.28 0.39 0.60 0.99 1.58 2.17 2.50 2.31 1.79 1.17 0.73 0.48 0.36 0.31 0.36 0.49 0.75 1.22 1.90 2.45 2.59 2.24 1.58 0.98 0.65 0.50 0.50 0.62 0.90 1.32 1.80 2.22 2.24 1.85 1.36
2.29 2.39 1.99 1.44 0.92 0.59 0.41 0.34 0.36 0.46 0.64 0.89 1.14 1.37 1.52 1.44 1.19 0.96 0.71 0.52 0.41 0.37 0.41 0.54 0.76 1.04 1.32 1.61 1.69 1.50 1.24 0.97 0.72 0.58 0.55 0.63 0.78 0.94 1.09 1.24 1.26 1.11 0.95
1.35 1.40 1.24 1.04 0.82 0.60 0.45 0.37 0.35 0.40 0.47 0.55 0.62 0.66 0.70 0.67 0.61 0.55 0.47 0.40 0.35 0.34 0.37 0.43 0.52 0.62 0.70 0.78 0.81 0.78 0.73 0.65 0.57 0.49 0.45 0.45 0.47 0.50 0.51 0.53 0.54 0.51 0.48
0.60 0.62 0.59 0.56 0.49 0.42 0.35 0.30 0.26 0.25 0.24 0.25 0.25 0.24 0.25 0.24 0.23 0.22 0.22 0.21 0.20 0.20 0.21 0.23 0.25 0.27 0.28 0.29 0.30 0.31 0.31 0.31 0.29 0.27 0.25 0.23 0.22 0.19 0.18 0.17 0.17 0.17 0.17
2.63 2.59 2.55 2.62 2.50
2.05 1.38 0.88 0.56 0.37 0.25 0.18
0.17 0.18 0.15 0.14 0.14 0.15 0.18 0.22 0.28 0.37 0.51 0.70 1.00 1.43 1.99 2.46 2.63 2.56 2.56 2.64 2.50 2.08 1.55 1.12 0.82
0.55 0.38 0.30 0.24 0.20 0.18 0.17 0.17 0.18 0.21 0.25 0.31 0.40 0.56
0.84 1.17 1.65 2.18 2.56 2.63 2.55 2.59 2.64 2.40 1.91 1.38 1.00 0.74 0.57 0.47 0.40 0.37 0.37 0.40 0.46 0.55 0.68 0.87 1.12 1.46 1.87 2.21 2.47 2.62 2.65 2.61 2.49
2.22 1.76
1.23 0.81
0.53 0.37
C+P1
C+P1
C+P1
0.05 0.06 0.07
0.08 0.10 0.12
0.12 0.16 0.18
0.18 0.24 0.27
0.37 0.38 0.32
0.59 0.53 0.41
0.96 0.78 0.56
1.56 1.15 0.75
2.14 1.58 0.94
1.76 1.03
1.48 0.94
1.11 0.76 0.49
0.75 0.58 0.42
0.46 0.42 0.35
0.28 0.26
0.18 0.18 0.16
0.12 0.13 0.12
0.08 0.10 0.10
0.09 0.11
0.11 0.14 0.15
0.15 0.19 0.21
0.22 0.29 0.30
0.35 0.43 0.41
0.66 0.58 0.44
1.08 0.87 0.61
1.71 1.28 0.83
2.27 1.73 1.02
1.75 1.08
1.45 0.93 0.56
1.00 0.71 0.49
0.60 0.52 0.40
0.34 0.35 0.31
0.22 0.22
0.13 0.14 0.13
0.08 0.09 0.09
0.06 0.07 0.06
0.05 0.06 0.07 0.05
0.09 0.10 0.09 0.08
0.17 0.16 0.14
0.28 0.24 0.20
0.55 0.43 0.33 0.24
1.20 0.79 0.53 0.37 0.24
1.52 0.94 0.58 0.35
2.28 1.59 0.96 0.54 0.28
1.86 1.32 0.78 0.41
1.36 1.21 0.91 0.53 0.27
0.71 0.82 0.76 0.58 0.34
0.48 0.53 0.49 0.37 0.20
0.03 0.04
0.04 0.05
0.07 0.09
0.11 0.14
0.19 0.25
0.33 0.47
0.65 0.91
1.29 1.77
2.20 2.40
2.42 2.45
2.44 2.33
2.01 1.58
1.18 0.88
0.65 0.48
0.36 0.27
0.21 0.16
0.13 0.11
0.09 0.07
0.06 0.06
0.06 0.06
0.07 0.08
0.10 0.13
0.17 0.22
0.30 0.40
0.55 0.77
1.10 1.53
2.00 2.32
2.39 2.40
2.39 2.36
2.13 1.69
1.23 0.88
0.62 0.44
0.32 0.23
0.17 0.12
0.09 0.07
0.05 0.04
0.03 0.03
0.04 0.05
0.07 0.09
0.13 0.18
0.26 0.36
0.50 0.70
0.99 1.41
1.91 2.30
2.38 2.30
2.33 2.39
2.23 1.80
1.32 0.94
0.68 0.50
0.39 0.32
0.28 0.27
0.30 MATCHLINE MATCHLINE MATCHLINE MATCHLINE MATCHLINE MATCHLINE
AA AAAD
AD AD
SSCO
WM
FH
RPDA
FDC
SAN ZENO WAY
(46' ROW)
BFP
BFP
BFP
LOW
C+P1
0.66 0.39 0.17
0.82 0.34 0.10
0.21 0.09 0.04
0.05 0.03
0.04 0.03
0.03 0.03
0.03 0.04 0.04
0.05 0.06 0.07
0.08 0.10 0.12
0.12 0.16 0.18
0.18 0.24 0.27
0.37 0.38 0.32
0.59 0.53 0.41
0.96 0.78 0.56
1.56 1.15 0.75
2.14 1.58 0.94
1.76 1.03
1.48 0.94
0.54 0.88
1.19 0.94
0.47 0.23
0.15 0.11
0.08 0.06
0.04 0.04
0.03 0.03
0.03 0.04
0.04 0.05
0.07 0.09
0.11 0.14
0.19 0.25
0.33 0.47
0.65 0.91
1.29 1.77
2.20 2.40
2.42 2.45
2.44 MATCHLINE MATCHLINE MATCHLINE MATCHLINE MATCHLINE
BB
BB
AA AA AA AA AA
BB
BB
BB
BB
ADAD AD AD
SS C O
SS C OSS C O
WM
FH
FH
RPDA
FDC
FH
WHARF
SAN ZENO WAY
(46' ROW)
BFP
BFP
BFP
CB
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
SAI
C1+P1
C1+P1C1+P1
C1+P1
0.73 0.42 0.29 0.25 0.28 0.39 0.60 0.99 1.58 2.17 2.50 2.31 1.79 1.17 0.73 0.48 0.36 0.31 0.36 0.49 0.75 1.22 1.90 2.45 2.59 2.24 1.58 0.98 0.65 0.50 0.50 0.62 0.90 1.32 1.80 2.22 2.24 1.85 1.36
2.29 2.39 1.99 1.44 0.92 0.59 0.41 0.34 0.36 0.46 0.64 0.89 1.14 1.37 1.52 1.44 1.19 0.96 0.71 0.52 0.41 0.37 0.41 0.54 0.76 1.04 1.32 1.61 1.69 1.50 1.24 0.97 0.72 0.58 0.55 0.63 0.78 0.94 1.09 1.24 1.26 1.11 0.95
1.35 1.40 1.24 1.04 0.82 0.60 0.45 0.37 0.35 0.40 0.47 0.55 0.62 0.66 0.70 0.67 0.61 0.55 0.47 0.40 0.35 0.34 0.37 0.43 0.52 0.62 0.70 0.78 0.81 0.78 0.73 0.65 0.57 0.49 0.45 0.45 0.47 0.50 0.51 0.53 0.54 0.51 0.48
0.60 0.62 0.59 0.56 0.49 0.42 0.35 0.30 0.26 0.25 0.24 0.25 0.25 0.24 0.25 0.24 0.23 0.22 0.22 0.21 0.20 0.20 0.21 0.23 0.25 0.27 0.28 0.29 0.30 0.31 0.31 0.31 0.29 0.27 0.25 0.23 0.22 0.19 0.18 0.17 0.17 0.17 0.17
2.63 2.59 2.55 2.62 2.50
2.05 1.38 0.88 0.56 0.37 0.25 0.18
0.17 0.18 0.15
0.14 0.14 0.15 0.18 0.22 0.28 0.37 0.51 0.70 1.00 1.43 1.99 2.46 2.63 2.56 2.56 2.64 2.50 2.08 1.55 1.12 0.82
0.55 0.38 0.30 0.24 0.20 0.18 0.17 0.17 0.18 0.21 0.25 0.31 0.40
0.56 0.84 1.17 1.65 2.18 2.56 2.63 2.55 2.59 2.64 2.40 1.91 1.38 1.00 0.74 0.57 0.47 0.40 0.37 0.37 0.40 0.46 0.55 0.68 0.87 1.12 1.46 1.87 2.21 2.47 2.62 2.65 2.61 2.49
2.22 1.76
1.23 0.81
0.53 0.37
C+P1
C+P1
C+P1
0.66 0.39 0.17
0.82 0.34 0.10
0.21 0.09 0.04
0.05 0.03
0.04 0.03
0.03 0.03
0.03 0.04 0.04
0.05 0.06 0.07
0.08 0.10 0.12
0.12 0.16 0.18
0.18 0.24 0.27
0.37 0.38 0.32
0.59 0.53 0.41
0.96 0.78 0.56
1.56 1.15 0.75
2.14 1.58 0.94
1.76 1.03
1.48 0.94
1.11 0.76 0.49
0.75 0.58 0.42
0.46 0.42 0.35
0.28 0.26
0.18 0.18 0.16
0.12 0.13 0.12
0.08 0.10 0.10
0.09 0.11
0.11 0.14 0.15
0.15 0.19 0.21
0.22 0.29 0.30
0.35 0.43 0.41
0.66 0.58 0.44
1.08 0.87 0.61
1.71 1.28 0.83
2.27 1.73 1.02
1.75 1.08
1.45 0.93 0.56
1.00 0.71 0.49
0.60 0.52 0.40
0.34 0.35 0.31
0.22 0.22
0.13 0.14 0.13
0.08 0.09 0.09
0.06 0.07 0.06
0.05 0.06 0.07 0.05
0.09 0.10 0.09 0.08
0.17 0.16 0.14
0.28 0.24 0.20
0.55 0.43 0.33 0.24
1.20 0.79 0.53 0.37 0.24
1.52 0.94 0.58 0.35
2.28 1.59 0.96 0.54 0.28
1.86 1.32 0.78 0.41
1.36 1.21 0.91 0.53 0.27
0.71 0.82 0.76 0.58 0.34
0.48 0.53 0.49 0.37 0.20
0.54 0.88
1.19 0.94
0.47 0.23
0.15 0.11
0.08 0.06
0.04 0.04
0.03 0.03
0.03 0.04
0.04 0.05
0.07 0.09
0.11 0.14
0.19 0.25
0.33 0.47
0.65 0.91
1.29 1.77
2.20 2.40
2.42 2.45
2.44 2.33
2.01 1.58
1.18 0.88
0.65 0.48
0.36 0.27
0.21 0.16
0.13 0.11
0.09 0.07
0.06 0.06
0.06 0.06
0.07 0.08
0.10 0.13
0.17 0.22
0.30 0.40
0.55 0.77
1.10 1.53
2.00 2.32
2.39 2.40
2.39 2.36
2.13 1.69
1.23 0.88
0.62 0.44
0.32 0.23
0.17 0.12
0.09 0.07
0.05 0.04
0.03 0.03
0.04 0.05
0.07 0.09
0.13 0.18
0.26 0.36
0.50 0.70
0.99 1.41
1.91 2.30
2.38 2.30
2.33 2.39
2.23 1.80
1.32 0.94
0.68 0.50
0.39 0.32
0.28 0.27
0.30 Luminaire Schedule - LED
Project: 170 SAN ZENO WAY - SUNNYVALE
Symbol Qty Label Arrangement LLF Luminaire Lumens Luminaire Watts Description 5 AA Single 0.900 2136 18 VISIONAIRE PRE-2-M-T2-16LC-3-3K - 15' POLE 6 BB Single 0.900 4171 35 VISIONAIRE PRE-2-L-T2-32LC-3-3K - 20' POLE Calculation Summary
Project: KIFER ROAD
Description CalcType Units Avg Max Min Avg/Min Max/Min
KIFER ROAD - PROJECT FRONTAGE Illuminance Fc 0.76 2.59 0.17 4.47 15.24 KIFER ROAD SIDEWALKS Illuminance Fc 1.21 2.65 0.14 8.64 18.93 Luminaire Schedule - LED
Project: SAN ZENO WAY
Label Symbol Qty ArrangementLLF Description
C+P1 3 GROUP0.950 LUMEC [MSC-002]-35W32LED4K-G3-LE3F @ 25' LC + 6' ARM + [MSC-C-001]-140L-450-NW-G1-2-UNV @ 14' LC + 2' ARM Luminaire Schedule - LED
Project: KIFER ROAD
Label Symbol Qty LLF Arrangement Description
C1+P1 4 0.950 GROUP LUMEC [MSC-002]-35W32LED4K-G3-LE2F @ 25' LC + 6' ARM + [MSC-C-001]-140L-450-NW-G1-2-UNV @ 14' LC + 2' ARM Calculation Summary
Project: SAN ZENO WAY
Description CalcType Units Avg Max Min Avg/Min Max/Min
SAN ZENO WAY Illuminance Fc 0.51 2.28 0.03 17.00 76.00
SAN ZENO WAY SIDEWALKS Illuminance Fc 0.76 2.45 0.03 25.33 81.67 AGI32 VERSION 20.1
AGI (C) 2021 LIGHTING ANALYSTS, INC.
10268 W. CENTENNIAL ROAD, SUITE 202
LITTLETON, CO 80127
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * SALES REPRESENTATIVE: ALR; KRISTIAN REYES
differences will occur between measured values and calculated values. lighting calculations. If the real environment conditions do not match the input data, dimensions, reflectances, furniture and architectural elements significantly affect the variations. Input data used to generate the attached calculations such as room measurement techniques and field conditions such as voltage and temperature tolerances in calculation methods, testing procedures, component performance, Some differences between measured values and calculated results may occur due to Calculations have been performed according to IES standards and good practice.
BY: APPLICATIONS ENGINEERING; RAMON ZAPATA
REPORT FOR: GIACALONE DESIGN SERVICES
PHONE: (510) 638-0158 - FAX (510) 638-2908
OAKLAND, CA 94621
P.O. BOX 2265
7777 PARDEE LANE
ASSOCIATED LIGHTING REPRESENTATIVES, INC
UES SHOWN ARE MAINTAINED HORIZONTAL FOOTCANDLES AT GRADE AMP, BALLAST, ELECTRICAL, AND SITE CHARACTERISTICS.
AMP, RATINGS, FIELD PERFORMANCE WILL DEPEND ON ACTUAL
S BASED ON ESTABLISHED IES PROCEDURES AND PUBLISHED
PHOTOMETRIC DATA USED AS INPUT FOR THESE CALCULATIONS
DATE REVSHEETSCALE
PROJECT DESCRIPTION
DRAWING NO. / INPUT FILE
170 SAN ZENO WAY
CITY OF SUNNYALE
21366REY-R4.DWG / 21366REY-R4.A32
BB
BB
SS C O
SSCO
WM
FH
FDC
ENO WAY
BFP
CB
LOW
LOW
LOW
LOW
LOW
LOW
LOW
SAI
C+P1
C+P1
C+P1
0.05 0.06 0.07
0.08 0.10 0.12
0.12 0.16 0.18
0.18 0.24 0.27
0.37 0.38 0.32
0.59 0.53 0.41
0.96 0.78 0.56
1.56 1.15 0.75
2.14 1.58 0.94
1.76 1.03
1.48 0.94
1.11 0.76 0.49
0.75 0.58 0.42
0.46 0.42 0.35
0.28 0.26
0.18 0.18 0.16
0.12 0.13 0.12
0.08 0.10 0.10
0.09 0.11
0.11 0.14 0.15
0.15 0.19 0.21
0.22 0.29 0.30
0.35 0.43 0.41
0.66 0.58 0.44
1.08 0.87 0.61
1.71 1.28 0.83
2.27 1.73 1.02
1.75 1.08
1.45 0.93 0.56
1.00 0.71 0.49
0.60 0.52 0.40
0.34 0.35 0.31
0.22 0.22
0.13 0.14 0.13
0.08 0.09 0.09
0.06 0.07 0.06
0.05 0.06 0.07 0.05
0.09 0.10 0.09 0.08
0.17 0.16 0.14
0.28 0.24 0.20
0.55 0.43 0.33 0.24
1.20 0.79 0.53 0.37 0.24
1.52 0.94 0.58 0.35
2.28 1.59 0.96 0.54 0.28
1.86 1.32 0.78 0.41
0.03 0.04
0.04 0.05
0.07 0.09
0.11 0.14
0.19 0.25
0.33 0.47
0.65 0.91
1.29 1.77
2.20 2.40
2.42 2.45
2.44 2.33
2.01 1.58
1.18 0.88
0.65 0.48
0.36 0.27
0.21 0.16
0.13 0.11
0.09 0.07
0.06 0.06
0.06 0.06
0.07 0.08
0.10 0.13
0.17 0.22
0.30 0.40
0.55 0.77
1.10 1.53
2.00 2.32
2.39 2.40
2.39 2.36
2.13 1.69
1.23 0.88
0.62 0.44
0.32 0.23
0.17 0.12
0.09 0.07
0.05 0.04
0.03 0.03
0.04 0.05
0.07 0.09
0.13 0.18
0.26 0.36
0.50 0.70
0.99 1.41
1.91 2.30
2.38 2.30
2.33 2.39
2.23 1.80
MATCHLINE MATCHLINE MATCHLINE MATCHLINE MATCHLINE MATCHLINE
AA AAAD
AD AD
SSCO
WM
FH
RPDA
FDC
SAN ZENO WAY
(46' ROW)
BFP
BFP
BFP
LOW
C+P1
0.66 0.39 0.17
0.82 0.34 0.10
0.21 0.09 0.04
0.05 0.03
0.04 0.03
0.03 0.03
0.03 0.04 0.04
0.05 0.06 0.07
0.08 0.10 0.12
0.12 0.16 0.18
0.18 0.24 0.27
0.37 0.38 0.32
0.59 0.53 0.41
0.96 0.78 0.56
1.56 1.15 0.75
2.14 1.58 0.94
1.76 1.03
1.48 0.94
0.54 0.88
1.19 0.94
0.47 0.23
0.15 0.11
0.08 0.06
0.04 0.04
0.03 0.03
0.03 0.04
0.04 0.05
0.07 0.09
0.11 0.14
0.19 0.25
0.33 0.47
0.65 0.91
1.29 1.77
2.20 2.40
2.42 2.45
2.44 MATCHLINE MATCHLINE MATCHLINE MATCHLINE MATCHLINE
BB
BB
AA AA AA AA AA
BB
BB
BB
BB
ADAD AD AD
SS C O
SS C OSS C O
WM
FH
FH
RPDA
FDC
FH
WHARF
SAN ZENO WAY
(46' ROW)
BFP
BFP
BFP
CB
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
SAI
C1+P1
C1+P1C1+P1
C1+P1
0.73 0.42 0.29 0.25 0.28 0.39 0.60 0.99 1.58 2.17 2.50 2.31 1.79 1.17 0.73 0.48 0.36 0.31 0.36 0.49 0.75 1.22 1.90 2.45 2.59 2.24 1.58 0.98 0.65 0.50 0.50 0.62 0.90 1.32 1.80 2.22 2.24 1.85 1.36
2.29 2.39 1.99 1.44 0.92 0.59 0.41 0.34 0.36 0.46 0.64 0.89 1.14 1.37 1.52 1.44 1.19 0.96 0.71 0.52 0.41 0.37 0.41 0.54 0.76 1.04 1.32 1.61 1.69 1.50 1.24 0.97 0.72 0.58 0.55 0.63 0.78 0.94 1.09 1.24 1.26 1.11 0.95
1.35 1.40 1.24 1.04 0.82 0.60 0.45 0.37 0.35 0.40 0.47 0.55 0.62 0.66 0.70 0.67 0.61 0.55 0.47 0.40 0.35 0.34 0.37 0.43 0.52 0.62 0.70 0.78 0.81 0.78 0.73 0.65 0.57 0.49 0.45 0.45 0.47 0.50 0.51 0.53 0.54 0.51 0.48
0.60 0.62 0.59 0.56 0.49 0.42 0.35 0.30 0.26 0.25 0.24 0.25 0.25 0.24 0.25 0.24 0.23 0.22 0.22 0.21 0.20 0.20 0.21 0.23 0.25 0.27 0.28 0.29 0.30 0.31 0.31 0.31 0.29 0.27 0.25 0.23 0.22 0.19 0.18 0.17 0.17 0.17 0.17
2.63 2.59 2.55 2.62 2.50
2.05 1.38 0.88 0.56 0.37 0.25 0.18
0.17 0.18 0.15
0.14 0.14 0.15 0.18 0.22 0.28 0.37 0.51 0.70 1.00 1.43 1.99 2.46 2.63 2.56 2.56 2.64 2.50 2.08 1.55 1.12 0.82
0.55 0.38 0.30 0.24 0.20 0.18 0.17 0.17 0.18 0.21 0.25 0.31 0.40
0.56 0.84 1.17 1.65 2.18 2.56 2.63 2.55 2.59 2.64 2.40 1.91 1.38 1.00 0.74 0.57 0.47 0.40 0.37 0.37 0.40 0.46 0.55 0.68 0.87 1.12 1.46 1.87 2.21 2.47 2.62 2.65 2.61 2.49
2.22 1.76
1.23 0.81
0.53 0.37
C+P1
C+P1
C+P1
0.66 0.39 0.17
0.82 0.34 0.10
0.21 0.09 0.04
0.05 0.03
0.04 0.03
0.03 0.03
0.03 0.04 0.04
0.05 0.06 0.07
0.08 0.10 0.12
0.12 0.16 0.18
0.18 0.24 0.27
0.37 0.38 0.32
0.59 0.53 0.41
0.96 0.78 0.56
1.56 1.15 0.75
2.14 1.58 0.94
1.76 1.03
1.48 0.94
1.11 0.76 0.49
0.75 0.58 0.42
0.46 0.42 0.35
0.28 0.26
0.18 0.18 0.16
0.12 0.13 0.12
0.08 0.10 0.10
0.09 0.11
0.11 0.14 0.15
0.15 0.19 0.21
0.22 0.29 0.30
0.35 0.43 0.41
0.66 0.58 0.44
1.08 0.87 0.61
1.71 1.28 0.83
2.27 1.73 1.02
1.75 1.08
1.45 0.93 0.56
1.00 0.71 0.49
0.60 0.52 0.40
0.34 0.35 0.31
0.22 0.22
0.13 0.14 0.13
0.08 0.09 0.09
0.06 0.07 0.06
0.05 0.06 0.07 0.05
0.09 0.10 0.09 0.08
0.17 0.16 0.14
0.28 0.24 0.20
0.55 0.43 0.33 0.24
1.20 0.79 0.53 0.37 0.24
1.52 0.94 0.58 0.35
2.28 1.59 0.96 0.54 0.28
1.86 1.32 0.78 0.41
1.36 1.21 0.91 0.53 0.27
0.71 0.82 0.76 0.58 0.34
0.48 0.53 0.49 0.37 0.20
0.54 0.88
1.19 0.94
0.47 0.23
0.15 0.11
0.08 0.06
0.04 0.04
0.03 0.03
0.03 0.04
0.04 0.05
0.07 0.09
0.11 0.14
0.19 0.25
0.33 0.47
0.65 0.91
1.29 1.77
2.20 2.40
2.42 2.45
2.44 2.33
2.01 1.58
1.18 0.88
0.65 0.48
0.36 0.27
0.21 0.16
0.13 0.11
0.09 0.07
0.06 0.06
0.06 0.06
0.07 0.08
0.10 0.13
0.17 0.22
0.30 0.40
0.55 0.77
1.10 1.53
2.00 2.32
2.39 2.40
2.39 2.36
2.13 1.69
1.23 0.88
0.62 0.44
0.32 0.23
0.17 0.12
0.09 0.07
0.05 0.04
0.03 0.03
0.04 0.05
0.07 0.09
0.13 0.18
0.26 0.36
0.50 0.70
0.99 1.41
1.91 2.30
2.38 2.30
2.33 2.39
2.23 1.80
1.32 0.94
0.68 0.50
0.39 0.32
0.28 0.27
0.30 Luminaire Schedule - LED
Project: 170 SAN ZENO WAY - SUNNYVALE
Symbol Qty Label Arrangement LLF Luminaire Lumens Luminaire Watts Description 5 AA Single 0.900 2136 18 VISIONAIRE PRE-2-M-T2-16LC-3-3K - 15' POLE 6 BB Single 0.900 4171 35 VISIONAIRE PRE-2-L-T2-32LC-3-3K - 20' POLE SAN ZENO WAY SIDEWALKS Illuminance Fc 0.76 2.45 0.03 25.33 81.67 REPORT FOR: GIACALONE DESIGN SERVICES
PROJECT DESCRIPTION
170 SAN ZENO WAY
BB
BB
BB
SS C O
SSCOSS C O
WM
FH
BFP
CB
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
SAI
C1+P1
C1+P1C1+P1
0.39 0.60 0.99 1.58 2.17 2.50 2.31 1.79 1.17 0.73 0.48 0.36 0.31 0.36 0.49 0.75 1.22 1.90 2.45 2.59 2.24 1.58 0.98 0.65 0.50 0.50 0.62 0.90 1.32 1.80 2.22 2.24 1.85 1.36
0.46 0.64 0.89 1.14 1.37 1.52 1.44 1.19 0.96 0.71 0.52 0.41 0.37 0.41 0.54 0.76 1.04 1.32 1.61 1.69 1.50 1.24 0.97 0.72 0.58 0.55 0.63 0.78 0.94 1.09 1.24 1.26 1.11 0.95
0.40 0.47 0.55 0.62 0.66 0.70 0.67 0.61 0.55 0.47 0.40 0.35 0.34 0.37 0.43 0.52 0.62 0.70 0.78 0.81 0.78 0.73 0.65 0.57 0.49 0.45 0.45 0.47 0.50 0.51 0.53 0.54 0.51 0.48
0.25 0.24 0.25 0.25 0.24 0.25 0.24 0.23 0.22 0.22 0.21 0.20 0.20 0.21 0.23 0.25 0.27 0.28 0.29 0.30 0.31 0.31 0.31 0.29 0.27 0.25 0.23 0.22 0.19 0.18 0.17 0.17 0.17 0.17 2 0.28 0.37 0.51 0.70 1.00 1.43 1.99 2.46 2.63 2.56 2.56 2.64 2.50 2.08 1.55 1.12 0.82
0.55 0.38 0.30 0.24 0.20 0.18 0.17 0.17 0.18 0.21 0.25 0.31 0.40 0.56
0.84 1.17 1.65 2.18 2.56 2.63 2.55 2.59 2.64 2.40 1.91 1.38 1.00 0.74 0.57 0.47 0.40 0.37 0.37 0.40 0.46 0.55 0.68 0.87 1.12 1.46 1.87 2.21 2.47 2.62 2.65 2.61 2.49
2.22 1.76
1.23 0.81
0.53 0.37
C+P1
C+P1
C+P1
0.12 0.16 0.18
0.18 0.24 0.27
0.37 0.38 0.32
0.59 0.53 0.41
0.96 0.78 0.56
1.56 1.15 0.75
2.14 1.58 0.94
1.76 1.03
1.48 0.94
1.11 0.76 0.49
0.75 0.58 0.42
0.46 0.42 0.35
0.28 0.26
0.18 0.18 0.16
0.12 0.13 0.12
0.08 0.10 0.10
0.09 0.11
0.11 0.14 0.15
0.15 0.19 0.21
0.22 0.29 0.30
0.35 0.43 0.41
0.66 0.58 0.44
1.08 0.87 0.61
1.71 1.28 0.83
2.27 1.73 1.02
1.75 1.08
1.45 0.93 0.56
1.00 0.71 0.49
0.60 0.52 0.40
0.34 0.35 0.31
0.22 0.22
0.13 0.14 0.13
0.08 0.09 0.09
0.06 0.07 0.06
0.05 0.06 0.07 0.05
0.09 0.10 0.09 0.08
0.17 0.16 0.14
0.28 0.24 0.20
0.55 0.43 0.33 0.24
1.20 0.79 0.53 0.37 0.24
1.52 0.94 0.58 0.35
2.28 1.59 0.96 0.54 0.28
1.86 1.32 0.78 0.41
1.36 1.21 0.91 0.53 0.27
0.71 0.82 0.76 0.58 0.34
0.48 0.53 0.49 0.37 0.20
0.09 0.11
0.14 0.19
0.25 0.33
0.47 0.65
0.91 1.29
1.77 2.20
2.40 2.42
2.45 2.44
2.33 2.01
1.58 1.18
0.88 0.65
0.48 0.36
0.27 0.21
0.16 0.13
0.11 0.09
0.07 0.06
0.06 0.06
0.06 0.07
0.08 0.10
0.13 0.17
0.22 0.30
0.40 0.55
0.77 1.10
1.53 2.00
2.32 2.39
2.40 2.39
2.36 2.13
1.69 1.23
0.88 0.62
0.44 0.32
0.23 0.17
0.12 0.09
0.07 0.05
0.04 0.03
0.03 0.04
0.05 0.07
0.09 0.13
0.18 0.26
0.36 0.50
0.70 0.99
1.41 1.91
2.30 2.38
2.30 2.33
2.39 2.23
1.80 1.32
0.94 0.68
0.50 0.39
0.32 0.28
0.27 0.30
MATCHLINE MATCHLINE MATCHLINE MATCHLINE MATCHLINE MATCHLINE
AA AAAD
AD AD
SSCO
WM
FH
RPDA
FDC
SAN ZENO WAY
(46' ROW)
BFP
BFP
BFP
LOW
C+P1
0.66 0.39 0.17
0.82 0.34 0.10
0.21 0.09 0.04
0.05 0.03
0.04 0.03
0.03 0.03
0.03 0.04 0.04
0.05 0.06 0.07
0.08 0.10 0.12
0.12 0.16 0.18
0.18 0.24 0.27
0.37 0.38 0.32
0.59 0.53 0.41
0.96 0.78 0.56
1.56 1.15 0.75
2.14 1.58 0.94
1.76 1.03
1.48 0.94
0.54 0.88
1.19 0.94
0.47 0.23
0.15 0.11
0.08 0.06
0.04 0.04
0.03 0.03
0.03 0.04
0.04 0.05
0.07 0.09
0.11 0.14
0.19 0.25
0.33 0.47
0.65 0.91
1.29 1.77
2.20 2.40
2.42 2.45
2.44 MATCHLINE MATCHLINE MATCHLINE MATCHLINE MATCHLINE
BB
BB
AA AA AA AA AA
BB
BB
BB
BB
ADAD AD AD
SS C O
SS C OSS C O
WM
FH
FH
RPDA
FDC
FH
WHARF
SAN ZENO WAY
(46' ROW)
BFP
BFP
BFP
CB
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
LOW
SAI
C1+P1
C1+P1C1+P1
C1+P1
0.73 0.42 0.29 0.25 0.28 0.39 0.60 0.99 1.58 2.17 2.50 2.31 1.79 1.17 0.73 0.48 0.36 0.31 0.36 0.49 0.75 1.22 1.90 2.45 2.59 2.24 1.58 0.98 0.65 0.50 0.50 0.62 0.90 1.32 1.80 2.22 2.24 1.85 1.36
2.29 2.39 1.99 1.44 0.92 0.59 0.41 0.34 0.36 0.46 0.64 0.89 1.14 1.37 1.52 1.44 1.19 0.96 0.71 0.52 0.41 0.37 0.41 0.54 0.76 1.04 1.32 1.61 1.69 1.50 1.24 0.97 0.72 0.58 0.55 0.63 0.78 0.94 1.09 1.24 1.26 1.11 0.95
1.35 1.40 1.24 1.04 0.82 0.60 0.45 0.37 0.35 0.40 0.47 0.55 0.62 0.66 0.70 0.67 0.61 0.55 0.47 0.40 0.35 0.34 0.37 0.43 0.52 0.62 0.70 0.78 0.81 0.78 0.73 0.65 0.57 0.49 0.45 0.45 0.47 0.50 0.51 0.53 0.54 0.51 0.48
0.60 0.62 0.59 0.56 0.49 0.42 0.35 0.30 0.26 0.25 0.24 0.25 0.25 0.24 0.25 0.24 0.23 0.22 0.22 0.21 0.20 0.20 0.21 0.23 0.25 0.27 0.28 0.29 0.30 0.31 0.31 0.31 0.29 0.27 0.25 0.23 0.22 0.19 0.18 0.17 0.17 0.17 0.17
2.63 2.59 2.55 2.62 2.50
2.05 1.38 0.88 0.56 0.37 0.25 0.18
0.17 0.18 0.15
0.14 0.14 0.15 0.18 0.22 0.28 0.37 0.51 0.70 1.00 1.43 1.99 2.46 2.63 2.56 2.56 2.64 2.50 2.08 1.55 1.12 0.82
0.55 0.38 0.30 0.24 0.20 0.18 0.17 0.17 0.18 0.21 0.25 0.31 0.40
0.56 0.84 1.17 1.65 2.18 2.56 2.63 2.55 2.59 2.64 2.40 1.91 1.38 1.00 0.74 0.57 0.47 0.40 0.37 0.37 0.40 0.46 0.55 0.68 0.87 1.12 1.46 1.87 2.21 2.47 2.62 2.65 2.61 2.49
2.22 1.76
1.23 0.81
0.53 0.37
C+P1
C+P1
C+P1
0.66 0.39 0.17
0.82 0.34 0.10
0.21 0.09 0.04
0.05 0.03
0.04 0.03
0.03 0.03
0.03 0.04 0.04
0.05 0.06 0.07
0.08 0.10 0.12
0.12 0.16 0.18
0.18 0.24 0.27
0.37 0.38 0.32
0.59 0.53 0.41
0.96 0.78 0.56
1.56 1.15 0.75
2.14 1.58 0.94
1.76 1.03
1.48 0.94
1.11 0.76 0.49
0.75 0.58 0.42
0.46 0.42 0.35
0.28 0.26
0.18 0.18 0.16
0.12 0.13 0.12
0.08 0.10 0.10
0.09 0.11
0.11 0.14 0.15
0.15 0.19 0.21
0.22 0.29 0.30
0.35 0.43 0.41
0.66 0.58 0.44
1.08 0.87 0.61
1.71 1.28 0.83
2.27 1.73 1.02
1.75 1.08
1.45 0.93 0.56
1.00 0.71 0.49
0.60 0.52 0.40
0.34 0.35 0.31
0.22 0.22
0.13 0.14 0.13
0.08 0.09 0.09
0.06 0.07 0.06
0.05 0.06 0.07 0.05
0.09 0.10 0.09 0.08
0.17 0.16 0.14
0.28 0.24 0.20
0.55 0.43 0.33 0.24
1.20 0.79 0.53 0.37 0.24
1.52 0.94 0.58 0.35
2.28 1.59 0.96 0.54 0.28
1.86 1.32 0.78 0.41
1.36 1.21 0.91 0.53 0.27
0.71 0.82 0.76 0.58 0.34
0.48 0.53 0.49 0.37 0.20
0.54 0.88
1.19 0.94
0.47 0.23
0.15 0.11
0.08 0.06
0.04 0.04
0.03 0.03
0.03 0.04
0.04 0.05
0.07 0.09
0.11 0.14
0.19 0.25
0.33 0.47
0.65 0.91
1.29 1.77
2.20 2.40
2.42 2.45
2.44 2.33
2.01 1.58
1.18 0.88
0.65 0.48
0.36 0.27
0.21 0.16
0.13 0.11
0.09 0.07
0.06 0.06
0.06 0.06
0.07 0.08
0.10 0.13
0.17 0.22
0.30 0.40
0.55 0.77
1.10 1.53
2.00 2.32
2.39 2.40
2.39 2.36
2.13 1.69
1.23 0.88
0.62 0.44
0.32 0.23
0.17 0.12
0.09 0.07
0.05 0.04
0.03 0.03
0.04 0.05
0.07 0.09
0.13 0.18
0.26 0.36
0.50 0.70
0.99 1.41
1.91 2.30
2.38 2.30
2.33 2.39
2.23 1.80
1.32 0.94
0.68 0.50
0.39 0.32
0.28 0.27
0.30 Luminaire Schedule - LED
Project: 170 SAN ZENO WAY - SUNNYVALE
Symbol Qty Label Arrangement LLF Luminaire LumensLuminaire WattsDescription 5 AA Single 0.900 2136 18 VISIONAIRE PRE-2-M-T2-16LC-3-3K - 15' POLE 6 BB Single 0.900 4171 35 VISIONAIRE PRE-2-L-T2-32LC-3-3K - 20' POLE Calculation Summary
Project: KIFER ROAD
Description CalcType Units Avg Max Min Avg/Min Max/Min
KIFER ROAD - PROJECT FRONTAGE Illuminance Fc 0.76 2.59 0.17 4.47 15.24 KIFER ROAD SIDEWALKS Illuminance Fc 1.21 2.65 0.14 8.64 18.93 Luminaire Schedule - LED
Project: SAN ZENO WAY
Label Symbol Qty ArrangementLLF Description
C+P1 3 GROUP0.950 LUMEC [MSC-002]-35W32LED4K-G3-LE3F @ 25' LC + 6' ARM + [MSC-C-001]-140L-450-NW-G1-2-UNV @ 14' LC + 2' ARM Project: KIFER ROAD
Label Symbol Qty LLF Arrangement Description
C1+P1 4 0.950 GROUP LUMEC [MSC-002]-35W32LED4K-G3-LE2F @ 25' LC + 6' ARM + [MSC-C-001]-140L-450-NW-G1-2-UNV @ 14' LC + 2' ARM Calculation Summary
Project: SAN ZENO WAY
Description CalcType Units Avg Max Min Avg/Min Max/Min
SAN ZENO WAY Illuminance Fc 0.51 2.28 0.03 17.00 76.00
SAN ZENO WAY SIDEWALKS Illuminance Fc 0.76 2.45 0.03 25.33 81.67 R.O.W. PHOTOMETRIC PLAN EXHIBIT
Attachment 6
140 LU SUBMITTAL 05 JULY 05, 2023
!
"#
"$
!
"# "$
%"#"$
&%#
'
"$
#
$
MECHANICAL EQUIPMENT HEIGHT
PARAPET
HEAT
PUMP
HEAT
PUMP
CORRIDOR
SUPPLY FAN
GARARGE
EXHAUST FAN
6FT MECHANICAL EQUIPMENT ABOVE PARAPET TO BE
PAINTED
TO MATCH PARAPET
9FT MECHANICAL EQUIPMENT ABOVE PARAPET TO BE SCREENED AS REQUIRED -
SUPPLEMENTARY STRUCTURAL FRAMING AS NEEDED
SOLAR PANELS - 5 KW PV SYSTEM SOLAR PANELS - 5 KW PV SYSTEM
ROOFTOP PUBLIC VIEW - LAWRENCE EXPY
ROOF PLAN LEGEND
ENLARGED ROOF PLAN - GARAGE EXHAUST F
AN LOCATION
T.O. ROOF
T.O. PARAPET
ROOFTOP MECHANICAL UNIT BEYOND - GARAGE EXHAUST (9FT)
ROOFTOP MECHANICAL UNIT BEYOND - SUPPLY FAN (6FT)
T.O. ROOF
T
.O. PARAPET
SIGHT LINE EXHIBIT - LAWRENCE EXPY
IF NEEDED
IF NEEDED
Attachment 6
141 LU SUBMITTAL 05 JULY 05, 2023
%"#"$
''
#
'
"$%'
ROOFTOP MECHANICAL UNIT BEYOND - SUPPLY FAN (6FT)
ENLARGED ROOF PLAN - SUPPLY FAN
PARAPET
HEAT
PUMP
HEAT
PUMP
CORRIDOR
SUPPLY FAN 6FT MECHANICAL EQUIPMENT ABOVE PARAPET TO BE P
AINTED TO MATCH PARAPET
SOLAR PANELS - 5 KW PV SYSTEM SOLAR PANELS - 5 KW PV SYSTEM
MECHANICAL EQUIPMENT HEIGHT ROOF PLAN LEGEND
ROOFTOP PUBLIC VIEW - SORONA CT
T.O. ROOF
T.O. ROOF
T.O. PARAPET
T.O. PARAPET
SIGHT LINE EXHIBIT - SORONA CT
Attachment 6
142 LU SUBMITTAL 05 JULY 05, 2023
%"#"$
!
"#
"$
!
"#
"$
ROOFTOP MECHANICAL UNIT BEYOND - SUPPLY FAN (6FT)
ENLARGED ROOF PLAN - SUPPLY FAN
T.O. ROOF
T.O. PARAPET
ROOF PLAN LEGEND
ROOFTOP PUBLIC VIEW - KIFER RD
MECHANICAL EQUIPMENT HEIGHT
PARAPET
HEAT
PUMP
HEAT
PUMP
CORRIDOR
SUPPLY FAN 6FT MECHANICAL EQUIPMENT ABOVE PARAPET TO BE P
AINTED TO MATCH PARAPET
SOLAR PANELS - 5 KW PV SYSTEM SOLAR PANELS - 5 KW PV SYSTEM T.O. ROOF
T.O. PARAPET
SIGHT LINE EXHIBIT - KIFER RD
Attachment 6
LU SUBMITTAL 05 JULY 05, 2023