Item No. 3.
TO:HONORABLE MAYOR AND MEMBERS OF THE CITY COUNCIL
FROM:OFFICE OF THE CITY MANAGER
BY:MATTHEW BAUMGARDNER, DIRECTOR OF PUBLIC WORKS/CITY ENGINEER DATE:OCTOBER 28, 2025
SUBJECT:
APPROVAL OF PLANS AND SPECIFICATIONS AND AUTHORIZATION TO SOLICIT
CONSTRUCTION BIDS FOR THE INSPIRATION SHUTTLE EXHIBIT AND EDUCATION BUILDING, CAPITAL IMPROVEMENT PROJECT (CIP) NO. 21-18
EXECUTIVE SUMMARY
The City Council will consider approving plans and specifications, and authorizing the solicitation of construction bids for the Inspiration Shuttle Exhibit and Education Building, Capital Improvement Project (CIP) No. 21-18. The expansion of the existing Columbia Memorial Space Center will create two new buildings, the larger of which will be home to the Space Shuttle Inspiration mock-up and several education exhibits. Full construction is anticipated to begin in February 2026 and be completed by December 2027. The City will be holding a groundbreaking ceremony prior to the start of construction, which will occur on November 17, 2025. Site preparation will occur between November 2025 and February 2026.
RECOMMENDATION
That the City Council:
Approve the plans and specifications, and authorize the solicitation of construction bids, for the Inspiration Shuttle Exhibit and Education Building, Capital Improvement Project (CIP) No. 21-18.
BACKGROUND
The Columbia Memorial Space Center is embarking on a second building expansion project (Project) to create a hub of creative and critical thinking for the youth and families of Southeast Los Angeles. This Project intends to create an integrated campus that includes a new building dedicated to bringing the community together through hands-on, minds-on learning to serve the region. The expansions includes: (1) a 39,725 square-foot building that will house the Space Shuttle “Inspiration” along with several exhibits, (2) a 15,300 square-foot building that will include two youth STEM classrooms, and (3) outdoor gathering spaces.
To date, there has been significant work to get the project ready for construction bid, including:
In January 2022, LPA, Inc, the project Architect, began the design of the Project.
Also in 2022, Rachlin Partners LLC/Huckabee, the Project Management/Construction Management firm, began providing its management services.
In 2023, UltraSystems, Inc, the Environmental Consultant, began the environmental analysis of the Project.
In 2024, Knight Building Systems, the Pre-Engineered Metal Building (PEMB) manufacturer, began its design of the PEMB structure for the building.
Today, the environmental analysis and design of the project are completed, while Knight Building System is currently completing the fabrication of the PEMB structure offsite.
ANALYSIS
Staff has completed the preparation of plans (Attachment A) for the expansion Project. The work consists of the removal of vegetation, demolition, grading, drainage, utilities, walkways, driveway approaches, lighting, landscaping, a 39,725 square-foot exhibit building standing approximately 55 feet in height, and a 15,300 square- foot STEM classroom building standing approximately 17 feet in height.
The plans are currently going through review and permitting. Staff anticipates advertising the project for bid in November 2026. Due to the complexity of the project, staff intends to keep the bidding period open through the middle of January, as there will be many construction trades that will need to review the plans to provide accurate proposals. In order to receive the most competitive bids, staff also needs to provide additional time for bidding during the holiday season.
It is anticipated that staff will return to the City Council for the award of the construction contract by the first meeting in February 2026. Construction is anticipated to begin in February 2026 and be completed by December 2027. A groundbreaking will be held prior to the start of construction on November 17, 2025. Site preparation, including clearing and grubbing, irrigation removals, fencing, and stormwater BMPs, will occur between November 2025 and February 2026.
CITY COUNCIL PRIORITIES
Quality of Life, Safety & Infrastructure
Public Engagement
FISCAL IMPACT
Approval of the recommended action will result in the solicitation of bids being advertised. Estimated expenditures on the project are shown in the table below:
Description Amount
Design and Preliminary Engineering $1,500,000
Construction Contract (Estimated)$24,000,000
Contingencies (10%)$2,400,000
Construction Inspection and Materials Testing $800,000
Construction Engineering and Contract Administration $800,000 Total Estimated Project Cost:$29,500,000
There will be sufficient fund balances for the recommended actions, as shown in the table below:
Account No.Funding Source Amount
26-1-6829 CA State Natural Resources Grant GF1909-0 $5,000,000 26-1-6829 CA State Natural Resources Grant GF2337-0 $2,718,000 26-1-6829 HUD Grant B-23-CP-CA-0201 $1,000,000
40-1-6829 Capital Projects Fund $14,528,125
Future Funding - Fundraising Efforts Underway $6,253,875 Total Available Budget:$29,500,000
Attachments
Attachment A - Space Shuttle Exhibit Construction Documents Set.pdf
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
ARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
PROJECT NUMBER
Submittal Date
SCHEMATIC DESIGN 10/27/2022
50% DESIGN DEVELOPMENT 10/27/2022
100% DESIGN DEVELOPMENT 01/06/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CONSTRUCTION DOCS 08/01/2025
3055401
SPACE SHUTTLE EXHIBIT AND EDUCATION BUILDING
COLUMBIA WAY
DOWNEY, CA 90242
G0.01
TITLE SHEET
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
SHEET INDEX
G0.11
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDINGSHEET INDEX
SHEET NUMBER SHEET NAME
GENERAL INFORMATION
G0.01 TITLE SHEET
G0.11 SHEET INDEX
G0.21 GENERAL INFORMATION
G0.31 ACCESSIBILITY DETAILS
G0.32 ACCESSIBILITY DETAILS
G0.41 CAL GREEN CHECKLIST
G0.42 CAL GREEN CHECKLIST
G1.01 FIRE ACCESS PLAN
G2.01 CODE ANALYSIS
9 CIVIL (CITY OF DOWNEY PUBLIC WORKS - STREET IMPROVEMENT PLANS) 1 OF 3 TITLE SHEET
2 OF 3 STREET PLAN
3 OF 3 DETAILS
3 CIVIL (CITY OF DOWNEY PUBLIC WORKS - OFFSITE WATER UTILITY PLANS) 1 OF 4 TITLE SHEET
2 OF 4 CIVIL NOTES
3 OF 4 WATER UTILITY PLAN
4 OF 4 WATER UTILITY DETAILS
4 CIVIL (CITY OF DOWNEY PUBLIC WORKS - OFFSITE SEWER UTILITY PLANS) 1 OF 3. TITLE SHEET
2 OF 3. SEWER UTILITY PLAN
3 OF 3. SEWER UTILITY DETAILS
3 CIVIL (ONSITE)
C0.01 CIVIL NOTES
C1.01 DEMOLITION PLAN
C2.01 GRADING PLAN
C3.01 STORM DRAIN PLAN
C4.01 UTILITY PLAN
C5.01 HORIZONTAL CONTROL, PAVING, STRIPING AND SIGNAGE PLAN C6.01 EROSION CONTROL PLAN
C7.01 CONSTRUCTION DETAILS
8 LANDSCAPE
L0.01 LANDSCAPE NOTES AND SCHEDULES
L1.01 MATERIALS PLAN
L2.01 LAYOUT PLAN
L4.01 SECTIONS & ELEVATIONS
L5.01 CONSTRUCTION & PLANTING DETAILS
L6.00 IRRIGATION LEGEND & NOTES
L6.01 IRRIGATION PLAN
L6.02 IRRIGATION CALCULATIONS & NOTES
L6.03 IRRIGATION DETAILS
L6.04 IRRIGATION DETAILS
L7.01 PLANTING PLAN
L7.02 PLANTING DETAILS
12 ARCHITECTURE
A0.21 SITE PLAN
A2.01 FIRST FLOOR PLAN
A2.02 SECOND FLOOR PLAN AND STEM ROOF PLAN
A2.03 ROOF PLAN
A2.11 FIRST FLOOR EDGE OF SLAB PLAN
A2.12 EDGE OF DECK SECOND FLOOR
A2.21 FIRST FLOOR FINISH PLAN
A2.22 SECOND FLOOR FINISH PLAN
A2.31 FIRST FLOOR REFLECTED CEILING PLAN
A2.32 SECOND FLOOR REFLECTED CEILING PLAN
A2.41 FIRST FLOOR EQUIPMENT & FURNITURE PLAN
A2.42 SECOND FLOOR EQUIPMENT & FURNITURE PLAN
A3.01 EXTERIOR ELEVATIONS
A3.02 EXTERIOR ELEVATIONS
A3.03 EXTERIOR ELEVATIONS
A3.04 EXTERIOR ELEVATIONS
A3.11 BUILDING SECTIONS
A3.12 BUILDING SECTIONS
A3.21 WALL SECTIONS
A3.22 WALL SECTIONS
A3.23 WALL SECTIONS
A4.01 ENLARGED RESTROOM PLANS
A5.01 INTERIOR RESTROOM ELEVATIONS
A5.02 INTERIOR RESTROOM ELEVATIONS
A5.03 INTERIOR ELEVATIONS
A5.04 INTERIOR ELEVATIONS
A5.05 INTERIOR ELEVATIONS
A5.06 INTERIOR ELEVATIONS
A5.07 INTERIOR ELEVATIONS
A5.08 INTERIOR ELEVATIONS
A5.09 INTERIOR ELEVATIONS
A6.11 DOOR SCHEDULE AND OPENING TYPES
A7.01 ENLARGED STAIR PLANS AND SECTIONS
A7.02 ENLARGED RAMP AND STAIR PLANS AND SECTIONS
A7.11 STAIR DETAILS
A7.21 ENLARGED ELEVATOR PLANS AND SECTIONS
A7.31 ELEVATOR DETAILS
A8.01 FOUNDATION AND UNDERGROUND WATERPROOFING DETAILS
A8.11 BUILDING SYSTEMS
A8.21 ROOF AND CANOPY DETAILS
A8.22 ROOF ACCESS DETAILS
A8.31 INSULATED METAL PANEL DETAILS
A8.32 CURTAIN WALL SYSTEM DETAILS
A8.33 WALL SYSTEMS DETAILS
A8.51 OPENING DETAILS
A8.52 OPENING DETAILS
A8.53 OPENING DETAILS
A9.01 PARTITION TYPES
A9.11 INTERIOR DOOR DETAILS
A9.21 CEILING DETAILS
A9.22 CEILING DETAILS
A9.31 CASEWORK DETAILS
A9.32 CASEWORK DETAILS
A9.41 INTERIOR DETAILS
54 SIGNAGE
SG1.01 SIGNAGE SITE PLAN
SG2.01 FIRST FLOOR SIGNAGE PLAN
SG2.02 SECOND FLOOR SIGNAGE PLAN
SG3.01 SIGNAGE SCHEDULE
SG4.01 SIGNAGE DETAILS
SG4.02 SIGNAGE DETAILS
6 STRUCTURAL
S0.01 GENERAL NOTES
S2.01 FOUNDATION PLAN
S2.02 PEMB SECOND FLOOR AND STEM ROOF FRAMING PLAN
S6.01 TYPICAL FOUNDATION AND SOG DETAILS
S6.02 TYPICAL FOUNDATION AND SOG DETAILS
S6.03 PEMB FOUNDATION DETAILS
S6.11 TYPICAL STRUCTURAL STEEL DETAILS
S6.12 TYPICAL METAL DECKING DETAILS
S6.13 TYPICAL DECK SUPPORTING DETAILS
S6.15 TYPICAL HSS CONNECTION DETAILS
S6.71A TYPICAL LIGHT GAUGE FRAMING SCHEDULES and ELEVATIONS S6.71B TYPICAL LIGHT GAUGE FRAMING SCHEDULES and ELEVATIONS S6.72 TYPICAL LIGHT GAUGE METAL FRAMING DETAILS
S6.73 TYPICAL LIGHT GAUGE METAL FRAMING DETAILS
S6.74 TYPICAL LIGHT GAUGE METAL FRAMING DETAILS
S6.91 TYP. EQUIPMENT ANCHORAGE DETAILS
S6.92 TYP. EQUIPMENT ANCHORAGE DETAILS
S6.93 TYP. EQUIPMENT ANCHORAGE DETAILS
S7.01 STAIR FRAMING PLANS
S7.11 TYPICAL STAIR FRAMING DETAILS
20 SHEET INDEX
SHEET NUMBER SHEET NAME
MECHANICAL
M0.10 MECHANICAL LEGENDS AND GENERAL NOTES
M0.20 MECHANICAL SCHEDULES
M2.01 FIRST FLOOR MECHANICAL PLAN
M2.02 SECOND FLOOR MECHANICAL PLAN
M3.01 FIRST FLOOR PIPING & CONTROL PLAN
M3.02 SECOND FLOOR PIPING & CONTROL PLAN
M5.01 SECTION AND ISOMETRIC VIEWS
M7.00 MECHANICAL DETAILS AND DIAGRAMS
M7.01 MECHANICAL DETAILS AND DIAGRAMS
9 PLUMBING
P0.10 PLUMBING LEGENDS AND GENERAL NOTES
P0.20 PLUMBING FIXTURE SCHEDULES
P0.30 PLUMBING CALCULATION
P0.40 PLUMBING SITE PLAN
P2.00 UNDERGROUND PLUMBING PLAN
P2.01 FIRST FLOOR PLUMBING PLAN
P2.02 SECOND FLOOR PLAN AND STEM ROOF PLAN
P2.03 ROOF PLUMBING PLAN
P4.11 ENLARGED PLUMBING PLANS
P4.12 ENLARGED PLUMBING PLANS
P6.01 PLUMBING DETAILS
P6.02 PLUMBING DETAILS
12 ELECTRICAL
E0.01 ELECTRICAL LEAD SHEET
E0.02 ELECTRICAL LEAD SHEET
E0.20 LIGHTING FIXTURE NOTES, LIGHTING FIXTURE & LCP SCHEDULES E1.01 ELECTRICAL DEMO SITE PLAN
E1.11 ELECTRICAL SITE PLAN
E1.21 LIGHTING SITE PLAN
E2.01 FIRST FLOOR POWER PLAN
E2.01A FIRST FLOOR ELECTRICAL POWER PLAN MAIN BUILDING
E2.02 SECOND FLOOR POWER PLAN
E2.03 ELECTRICAL POWER ROOF PLAN
E3.01 FIRST FLOOR LIGHTING RCP
E3.02 SECOND FLOOR LIGHTING RCP
E4.00 SINGLE LINE DIAGRAM AND LOAD FEEDER SCHEDULE
E4.01 ENLARGED ELECTRICAL/DATA PLAN AND DETAILS
E5.01 SINGLE LINE DIAGRAM AND LOAD FEEDER SCHEDULE
E5.11 PANEL SCHEDULES
E5.12 PANEL SCHEDULES
E5.21 MECHANICAL AND PLUMBING SCHEDULES
E6.01 LIGHTING CONTROL DIAGRAMS AND DETAILS
E7.01 ELECTRICAL DETAILS
E7.02 ELECTRICAL DETAILS
E7.03 LIGHTING DETAILS
E9.01 LIGHTING SITE PHOTOMETRIC
E9.02 LIGHTING SITE EMERGENCY PHOTOMETRIC
E9.03 LIGHTING FIRST FLOOR PHOTOMETRIC
E9.04 LIGHTING FIRST FLOOR EMERGENCY PHOTOMETRIC
E9.05 LIGHTING SECOND FLOOR PHOTOMETRIC
E9.06 LIGHTING SECOND FLOOR EMERGENCY PHOTOMETRIC
28 FIRE ALARM
FA0.01 FIRE ALARM LEAD SHEET
FA2.01 FIRST FLOOR FIRE ALARM RCP
FA2.02 MEZZANINE FIRE ALARM RCP
FA4.00 FIRE ALARM DIAGRAMS AND DETAILS
FA5.00 FIRE ALARM RISER DIAGRAMS
5 TOTAL: 173
SHEET INDEX - REFERENCE PLANS
SHEET NUMBER SHEET NAME
FACADE MAINTENANCE ACCESS
FM0.00 COVER SHEET
FM2.01 FIRST FLOOR PLAN
FM2.03 ROOF PLAN
FM3.01 EXTERIOR ELEVATIONS
FM3.02 EXTERIOR ELEVATIONS
FM3.03 EXTERIOR ELEVATIONS
FM3.04 EXTERIOR ELEVATIONS
FM3.21 WALL SECTIONS
FM5.03 INTERIOR ELEVATIONS
FM5.04 INTERIOR ELEVATIONS
FM9.01 DETAILS
FM9.02 DETAILS
12 TOTAL: 12
(AVAILABLE DRAWINGS FOR BASIS OF DESIGN ITEMS TO BE
SUBMITTED AS DEFERRED APPROVALS BY GC AFTER BUILDING
PERMIT IS ISSUED.)
THESE PLANS AND SPECIFCATIONS DO NOT PROVIDE ANY DIRECTION
OR INSTRUCTIONS TO CONTRACTORS, SUBCONTRACTORS, MATERIAL
SUPPLIERS OR THEIR EMPLOYEES OR AGENTS RELATED TO
CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES OR
PROCEDURES, SAFETY PRECAUTIONS, MANNERS OR METHODS OF
EGRESS OR INGRESS, INCLUDING BUT NOT LIMITED TO JOB SITE
SAFETY, THE PHYSICAL CONDITION OF THE JOB SITE, THE MANNER OR
METHOD IN WHICH THE AREA WHERE WORK IS PERFORMED IS
ACCESSED BY WORKERS, AND SAFETY PROGRAMS OR SAFETY
PROTOCOLS OF ANY KIND IN CONNECTION WITH THE WORK. ALL OF
THE FOREGOING ARE SOLELY AND EXCLUSIVELY THE RESPONSIBILITY
OF THE CONTRACTOR, SUBCONTRACTOR, MATERIAL SUPPLIERS, OR ANY AGENTS OR EMPLOYEES THEREOF.
THE ARCHITECT EXPRESSLY DISCLAIMS ANY CONTROL OVER AND
RESPONSIBILITY FOR CONSTRUCTION MEANS, METHODS,
TECHNIQUES, SEQUENCES OR PROCEDURES, SAFETY PRECAUTIONS,
MANNERS OR METHODS OF EGRESS OR INGRESS, INCLUDING BUT
NOT LIMITED TO JOB SITE SAFETY, THE PHYSICAL CONDITION OF THE
JOB SITE, THE MANNER OR METHOD IN WHICH THE AREA WHERE
WORK IS PERFORMED IS ACCESSED BY WORKERS, AND SAFETY
PROGRAMS OR SAFETY PROTOCOLS OF ANY KIND IN CONNECTION WITH THE WORK.
THE ARCHITECT HAS NOT CONDUCTED AN EVALUATION OR ANALYSIS
OF SAFETY PROCEDURES OR APPLICABLE LAW REGARDING OR
RELATING TO ACCESSING THE JOB SITE OR AREAS OF THE WORK DURING THE COURSE OF CONSTRUCTION.
THE ARCHITECT, THE ARCHITECT’S DESIGNS, AND ANY OTHER WORK
PERFORMED BY THE ARCHITECT DO NOT ADDRESS, ANALYZE OR
PROVIDE ANY DIRECTION OR ADVICE TO ANY PERSON OR ENTITY ON
WHETHER OR NOT THE USE OF EXISTING LADDERS, DOORS, RAILINGS,
INGRESS AND INGRESS ROUTES OR THE LIKE ARE IN COMPLIANCE OR
NON-COMPLIANCE WITH OSHA, CAL-OSHA(CALIFORNIA ONLY), OR ANY
OTHER APPLICABLE STATUTE, REGULATION, OR STANDARD RELATED
TO JOB SITE SAFETY DURING THE COURSE OF CONSTRUCTION OF THE IMPROVEMENTS.
NOTICE TO PERSONS PERFORMING WORK ON JOB
SITE, INCLUDING CONTRACTORS, SUBCONTRACTORS,
MATERIAL SUPPLIERS AND ANY AGENTS OR
EMPLOYEES THEREOF
RESPONSIBILITY FOR JOB SITE SAFETY
CAB CABINET
CB CATCH BASIN
CEM CEMENT
CER CERAMIC
CI CAST IRON
CIP CAST IN PLACE
CIV ENG CIVIL ENGINEER
CG CORNER GUARD
CJ CONTROL JOINT
CLG CEILING
CLKG CAULKING
CLO CLOSET
CLR CLEAR
CNTR COUNTER
CO CASED OPENING
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONSTR CONSTRUCTION
CONT CONTINUOUS
CORR CORRIDOR
CT CERAMIC TILE
CTR CENTER
CTSK COUNTERSUNK
DA DISABLED ACCESS
DBL DOUBLE
DEPT DEPARTMENT
DESC DESCRIPTION
DF DRINKING FOUNTAIN
DET DETAIL
DIA DIAMETER
DIM DIMENSION
DISP DISPENSER
DN DOWN
DO DOOR OPENING
DR DOOR
DWR DRAWER
DS DOWNSPOUT
DSP DRY STANDPIPE
DWG DRAWING
EEAST
EA EACH
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
ENCL ENCLOSURE
EP ELECTRICAL PANELBOARD
EQ EQUAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXPO EXPOSED
EXP EXPANSION
EXT EXTERIOR
FA FIRE ALARM
FB FLAT BAR
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER
CABINET
FHC FIRE HOSE CABINET
FIN FINISH
FLR FLOOR
FLASH FLASHING
FLUOR FLUORESCENT
FOC FACE OF CONCRETE
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUD
FOV FACE OF VENEER (BRICK OR
PRECAST)
FOW FACE OF WALL
FR FIRE RETARDANT
FPRF FIREPROOF
FS FINISH SURFACE
FT FOOT OR FEET
FTG FOOTING
FURR FURRING
FUT FUTURE
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GI GALVANIZED IRON
GL GLASS
GND GROUND
GR GRADE
GYP GYPSUM
HB HOSE BIB
HC HOLLOW CORE
HDWD HARDWOOD
HDW HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HOUR
HGT/HT HEIGHT
IDINSIDE DIAMETER
INSUL INSULATION
INTINTERIOR
JANJANITOR
JTJOINT
KITKITCHEN
LABLABORATORY
LAMLAMINATE
LAND ARCH LANDSCAPE ARCHITECT
LAVLAVATORY
LKRLOCKER
LTLIGHT
MATL MATERIAL
MAXMAXIMUM
MCMEDICINE CABINET
MECH MECHANICAL
MEMB MEMBRANE
METMETAL
MFRMANUFACTURER
MHMANHOLE
MINMINIMUM
MIRMIRROR
MISCMISCELLANEOUS
MOMASONRY OPENING
MTDMOUNTED
MULMULLION
NNORTH
NICNOT IN CONTRACT
NO/#NUMBER
NOMNOMINAL
NTSNOT TO SCALE
OAOVERALL
OAOUTSIDE AIR
OBSOBSCURE
OCON CENTER
ODOUTSIDE DIAMETER
OFFOFFICE
OPNG OPENING
OPPOPPOSITE
OSAOUTSIDE AIR
PAPLANTING AREA
PRCST PRECAST
PHPANIC HARDWARE
PLPLATE
P LAM PLASTIC LAMINATE
PLASPLASTER
PLYWD PLYWOOD
POTPATH OF TRAVEL
PRPAIR
PTPAINT
PTDPAPER TOWEL DISPENSER
PTD/R COMBINATION PAPER
TOWEL DISPENSER &
RECEPTACLE
PTNPARTITION
PTRPAPER TOWEL
RECEPTACLE
QTQUARRY TILE
RRISER
RADRADIUS
RDROOF DRAIN
REFREFERENCE
REFR REFRIGERATOR
RGTR REGISTER
REINF REINFORCED
REQD REQUIRED
RESIL RESILIENT
RMROOM
ROROUGH OPENING
ROWRIGHT OF WAY
RWDREDWOOD
RWLRAIN WATER LEADER
SSOUTH
SCSOLID CORE
SCDSEAT COVER DISPENSER
SCHED SCHEDULE
SDSOAP DISPENSER
SECT SECTION
SFSQUARE FEET
SHSHELF
SHRSHOWER
SHTSHEET
SIMSIMILAR
SNDSANITARY NAPKIN
DISPENSER
SNRSANITARY NAPKIN
RECEPTACLE
SPEC SPECIFICATION(S)
SQSQUARE
SSSTAINLESS STEEL
S SKSERVICE SINK
STASTATION
STDSTANDARD
STLSTEEL
STOR STORAGE
STRSTRUCTURAL
SUSP SUSPENDED
SYMSYMMETRICAL
TTREAD
TBTOWEL BAR
TCTOP OF CURB
TELTELEPHONE
TERTERRAZZO
T>ONGUE & GROOVE
THKTHICK
TOBTOP OF BEAM
TOCTOP OF CONCRETE
TOWTOP OF WALL
TOPTOP OF PARAPET
TPDTOILET PAPER DISPENSER
TSTOP OF SLOPE
TVTELEVISION
TYPTYPICAL
UNFUNFINISHED
UNOUNLESS NOTED
OTHERWISE
URURINAL
VCTVINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
WWEST
W/WITH
WCWATER CLOSET
WDWOOD
W/OWITHOUT
WPWATERPROOF
WRWATER RESISTANT
WSCT WAINSCOT
WTWEIGHT
WWFWELDED WIRE FABRIC
& AND∠ANGLE
@ AT℄CENTERLINE∅DIAMETER OR ROUND
# POUND OR NUMBER
(E) EXISTING
(P) PAINT
(R) REMOVE
+/- DIM TOLERANCE
AC ASPHALTIC CONCRETE
ACC ACCESSIBLE
ACOUS ACOUSTICAL
ACM ALUM COMPOSITE MATERIAL
ACT ACOUS CLG TILE
AD AREA DRAIN
AED AUTO EXT DEFIBRILLATOR
ADJ ADJUSTABLE
AFF ABOVE FINISH FLOOR
AGGR AGGREGATE
AHJ AUTHORITY HAVING
JURISDICTION
ALUM ALUMINUM
APPROX APPROXIMATE
ARCH ARCHITECTURAL
ASF ASSIGNABLE SF
ASPH ASPHALT
BD BOARD
BITUM BITUMINOUS
BLDG BUILDING
BLK BLOCK
BLK'G BLOCKING
BM BEAM
BOC BACK OF CURB
BOT BOTTOM
BO BOTTOM OF
BOC BACK OF CURB
BOW BOTTOM OF WALL
BS BOTTOM OF SLOPE
1. ALL CONSTRUCTION & MATERIALS SHALL BE AS SPECIFIED & IN ACCORDANCE
WITH ALL APPLICABLE CODES, ORDINANCES, LAWS, PERMITS & THE CONTRACT
DOCUMENTS
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE ACCURATE PLACEMENT OF ALL NEW CONSTRUCTION ON THE SITE.
3. THE CONTRACTOR IS RESPONSIBLE FOR ALL EXISTING SURVEY MONUMENTS
WHICH MAY BE DISTURBED THROUGH CONSTRUCTION ACTIVITIES DEEMED NECESSARY FOR PRESERVATION BY THE CIVIL ENGINEER. IF SUCH MONUMENTS
WERE DISTURBED, THE APPLICANT SHALL HAVE A LICENSED LAND SURVEYOR
QUALIFIED CIVIL ENGINEER REESTABLISH ANY SUCH MONUMENTATION DAMAGED
OR DESTROYED DURING THE CONSTRUCTION OF THE PROJECT & SUBMIT "PRELIMINARY CORNER RECORDS" TO THE CIVIL ENGINEER AFTER REPLACEMENT.
AFTER APPROVAL BY THE CIVIL ENGINEER, THE APPLICANT SHALL FILE THE CORNER RECORDS WITH THE COUNTY SURVEYOR. PRIOR TO THE EXONERATION
OF ANY SECURITY, EVIDENCE OF SUCH FILING SHALL BE FURNISHED TO THE CIVIL ENGINEER.
4. THE CONTRACTOR IS RESPONSIBLE TO INSURE THAT TRUCK ROUTES SHALL BE STEERED AWAY FROM RESIDENTIAL AREAS.
5. THE CONTRACTOR SHALL ENSURE THAT TRUCKS HAULING DIRT ON PUBLIC ROADS TO & FROM THE SITE SHALL BE COVERED OR WILL MAINTAIN A 6"
DIFFERENTIAL BETWEEN THE MAX HGT OF ANY HAULED MATERIAL & THE TOP OF THE HAUL TRAILER. HAUL TRUCK DRIVERS SHALL WATER THE LOAD PRIOR TO LEAVING THE SITE TO PREVENT SOIL LOSS DURING TRANSPORT.
6. THE CONTRACTOR SHALL ENSURE THAT GRADED SURFACES USED FOR OFF
ROAD PARKING, MATERIALS LAY-DOWN, OR AWAITING FUTURE CONSTRUCTION SHALL BE STABILIZED FOR DUST CONTROL AS NEEDED. FREQUENTLY ACCESSED
UNPAVED AREAS SHALL BE PAVED AS EARLY AS POSSIBLE TO MINIMIZE DIRT TRACKOUT TO PUBLIC RIGHTS-OF-WAY.
7. THE CONSTRACTOR SHALL COORDINATE ANY LANE CLOSURES OR DETOURS WITH THE CITY/COUNTY. FLAG PERSONS & APPROPRIATE TRAFFIC CONTROL
DEVICES SHALL BE USED AS NEEDED TO MINIMIZE CONSTRUCTION ACTIVITY INTERFERENCE WITH OFF-SITE-TRAFFIC.
8. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS & SITE CONDITIONS BEFORE STARTING WORK. SHOULD A DISCREPANCY APPEAR IN THE CONTRACT
DOCUMENTS OR BETWEEN THE CONTRACT DOCUMENTS & EXISTING CONDITIONS, NOTIFY THE ARCHITECT AT ONCE FOR INSTRUCTION ON HOW TO PROCEED.
9. SHOULD A CONFLICT OCCUR BETWEEN DWGS & SPECIFICATIONS, THE MORE
COSTLY CONDITION SHALL TAKE PRECEDENCE, UNLESS A WRITTEN DECISION
FROM THE ARCHITECT HAS BEEN OBTAINED WHICH DESCRIBES A CLARIFICATION OR ALTERNATE METHOD AND/OR MATERIALS.
10. THE CONTRACTOR SHALL CONFINE HIS OPERATION ON THE SITE TO AREAS PERMITTED BY OWNER.
11. THE JOBSITE SHALL BE MAINTAINED IN A CLEAN, ORDERLY CONDITION FREE
OF DEBRIS & LITTER & SHALL NOT BE UNREASONABLY ENCUMBERED WITH ANY MATERIALS OR EQUIPMENT. EACH SUBCONTRACTOR IMMEDIATELY UPON
COMPLETION OF EACH PHASE OF HIS WORK SHALL REMOVE ALL TRASH & DEBRIS AS A RESULT OF HIS OPERATION.
12. ALL MATERIAL STORED ON THE SITE SHALL BE PROPERLY STACKED & PROTECTED TO PREVENT DAMAGE & DETERIORATION. FAILURE TO PROTECT MATERIALS MAY BE CAUSE FOR REJECTION OF WORK.
13. THE CONTRACTOR SHALL DO ALL CUTTING, FITTING, AND/OR PATCHING OF HIS
WORK THAT MAY BE REQUIRED TO MAKE ITS SEVERAL PARTS FIT TOGETHER
PROPERLY & SHALL NOT ENDANGER ANY OTHER WORK BY CUTTING, EXCAVATING, OR OTHERWISE ALTERING THE TOTAL WORK OR ANY PART OF IT.
ALL PATCHING, REPAIRING AND REPLACING OF MATERIALS AND SURFACES, CUT
OR DAMAGED IN EXECUTION OF WORK, SHALL BE DONE WITH APPLICABLE
MATERIALS SO THAT SURFACES REPLACED WILL, UPON COMPLETION, MATCH SURROUNDING SIMILAR SURFACES.
14. STRUCTURAL OBSERVATION WILL BE PERFORMED BY THE STRUCTURAL ENGINEER. WHEN REQUIRED, A STATEMENT IN WRITING SHALL BE GIVEN TO THE
BUILDING OFFICIAL, STATING THAT THE SITE VISITS HAVE BEEN MADE & WHETHER
OR NOT ANY OBSERVED DEFICIENCIES HAVE BEEN CORRECTED TO CONFORM TO THE APPROVED PLANS & SPECIFICATIONS.
15. SUBMITTAL DOCUMENTS FOR DEFERRED SUBMITAL ITEMS SHALL BE
SUBMITTED TO THE ARCHITECT OR ENGINEER OF RECORD, WHO SHALL REVIEW
THEM & RETURN THEM TO THE CONTRACTOR (WITH A NOTIFICATION INDICATING
THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED & THAT
THEY HAVE BEEN FOUND TO BE IN GENERAL CONFORMANCE WITH THE DESIGN OF THE BUILDING) FOR PLAN CHECK APPROVAL. THE DEFERRED SUBMITTAL
ITEMS SHALL NOT BE INSTALLED UNTIL THEIR DESIGN & SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE AUTHORITY HAVING JURISDICTION.
16. PROVIDE ALL ACCESS PANELS AS REQUIRED BY GOVERNING CODES TO ALL CONCEALED SPACES, VOIDS, ATTICS, ETC. VERIFY TYPE REQUIRED WITH ARCHITECT PRIOR TO INSTALLATION.
17. NO PORTION OF WORK REQUIRING A SHOP DWG. OR SAMPLE SUBMISSION
SHALL BE COMMENCED UNTIL THE SUBMISSION HAS BEEN REVIEWED BY THE ARCHITECT. ALL SUCH PORTIONS OF THE WORK SHALL BE IN ACCORDANCE WITH CORRECTED SHOP DWGS. AND SAMPLES.
18. DIMENSIONS:
ALL DIMS SHALL TAKE PRECEDENCE OVER SCALE.
ALL DIMS ARE TO FACE OF STUD / CONCRETE / MASONRY UNO
CLG HGT DIMS ARE FROM FACE OF SLAB TO FACE OF FIN CLG MATERIAL UNO
19. DO NOT SCALE DRAWINGS
20. PROVIDE ALL NECESSARY BLOCKING, BACKING, & FRAMING FOR LIGHT FIXTURES, ELECTRIC UNITS, A.C. EQUIPMENT, RECESSED ITEMS, AND ALL OTHER ITEMS AS REQUIRED.
21. WHERE LARGER STUDS OR FURRING ARE REQUIRED TO COVER PIPING AND
CONDUITS, THE LARGER STUD SIZE OR FURRING SHALL EXTEND THE FULL SURFACE OF THE WALL WIDTH AND LENGTH WHERE THE FURRING OCCURS, UNO.
22. ALL DOORS SHALL BE OPERABLE FROM THE INSIDE W/O THE USE OF A KEY OR SPECIAL KNOWLEDGE OF EFFORT. EXIT SIGNS SHALL BE PROVIDED AT ALL EXITS AS REQUIRED BY THE APPLICABLE CODES. ALL DOOR SWINGS SERVING AN OCCUPANT LOAD OF 50 OR GREATER SHALL SWING IN THE DIRECTION OF TRAVEL.
23. ALL GLASS AND GLAZING SHALL COMPLY WITH THE APPLICABLE CODES.
24. WALL AND CLG. MATERIALS SHALL NOT EXCEED THE FLAME SPREAD CLASSIFICATIONS IN THE APPLICABLE CODES.
25. SURVEYORS CERTIFICATE REQ. PRIOR TO FINAL COMPLETION.
26. THE CONTRACTOR SHALL COMPLY WITH THE APPLICABLE CODES FOR FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION.
1. PLANS FOR THE FIRE SPRINKLER SYSTEMS MUST BE APPROVED BY THE AUTHORITY HAVING JURISDICTION (AHJ) PRIOR TO INSTALLATION. SUBMIT PLANS IN A MANNER WHICH WILL NOT IMPEDE THE PROGRESS OF CONSTRUCTION.
2. FIRE SPRINKLER SYSTEMS & INSTALLATION SHALL CONFORM W/ THE APPLICABLE STANDARDS AND CODES.
3. FIRE SPRINKLER SYSTEMS TO BE TIED INTO THE ALARM SYSTEM PER THE APPLICABLE CODES.
4. AUTOMATIC SPRINKLER SYSTEM(S) SHALL BE SUPERVISED BY AN APPROVED
CENTRAL OR REMOTE STATION SERVICE, AND/OR SHALL BE PROVIDED W/ A LOCAL ALARM WHICH WILL GIVE AN AUDIBLE SIGNAL.
5. FIRE SPRINKLER SYSTEM(S) & ALL CONTROL VALVES SHALL BE SUPERVISED BY A U.L. LISTED CENTRAL ALARM STATION OR PER THE APPLICABLE CODES.
6. FIRE HYDRANT & FIRE SPRINKLER SYSTEM(S) SHALL BE FLUSHED THOROUGHLY
BEFORE CONNECTION IS MADE TO EXISTING SYSTEM STUBOUTS & WITNESSED BY THE PROJECT INSPECTOR.
7. A HYDROSTATIC TEST (200 PSI PRESSURE FOR 2 HRS. OR @ 50 PSI IN EXCESS OF THE MIN. STATIC PRESSURE WHEN IT IS IN EXCESS OF 150 PSI) SHALL BE WITNESSED BY THE PROJECT INSPECTOR PRIOR TO COVERING PIPING JOINTS.
8. A 3' CLR. SPACE SHALL BE MAINTAINED AROUND THE CIRCUMFERENCE OF FIRE HYDRANTS EXCEPT AS OTHERWISE REQ. OR APPROVED PER THE APPLICABLE CODES.
9. THRUST BLOCKS SHALL BE PROVIDED WHEREVER PIPE CHANGES DIRECTION.
10. ALL PIPE SHALL BE U.L. LISTED FOR FIRE SERVICE SYSTEMS, CLASS 200 MIN.
11. FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED W/I 100' FROM A PUBLIC FIRE HYDRANT PER THE APPLICABLE STANDARDS AND CODES.
12. FIRE SPRINKLER RISER SHALL BE LOCATED WITHIN 5 FEET OF THE EXTERIOR WALL (OR AS REQUIRED BY THE AHJ) AND TERMINATE 6" ABV. F.F.
13. AN ALL-WEATHER FIRE ACCESS ROAD SHALL BE IN PLACE BEFORE ANY
COMBUSTIBLE MATERIALS ARE PLACED ON THE SITE OR AS REQUIRED BY THE AHJ.
14. STORAGE, DISPENSING, OR USE OF ANY FLAMMABLE & COMBUSTIBLE LIQUIDS,
FLAMMABLE & COMPRESSED GASES & OTHER HAZARDOUS MATERIALS SHALL COMPLY W/ THE APPLICABLE CODES.
15. "EXIT" SIGNS SHALL BE POSTED OVER EXIT DOORS & DIRECTIONAL "EXIT" SIGNS SHALL BE LOCATED TO DIRECT PERSONS TOWARD EXIT DOORS.
16. "EXIT" SIGNS SHALL BE SELF-LUMINOUS TYPE OR ELECTRONICALLY
ILLUMINATED & ENERGIZED FROM SEPARATE CIRCUITS, ONE OF WHICH SHALL BE FROM STORAGE BATTERIES OR AN ON-SITE GENERATOR, FOR A DURATION OF 90 MINUTES PER THE APPLICABLE CODES.
17. EXIT DOORS SHALL BE OPENABLE FROM THE INSIDE W/O THE USE OF A KEY OR ANY SPECIAL KNOWLEDGE OR EFFORT.
18. ACCESS GATE(S) SHALL BE OPENABLE W/ FIRE DEPT. MASTER KEY FROM THE EXTERIOR.
19. CURBS ALONG FIRE LANES SHALL BE PAINTED SAFETY RED & MARKED "FIRE LANE NO PARKING" W/ 3" WHITE LETTERS ON THE TOP OF CURBING EVERY 30' AS INDICATED ON THE APPROVED DRAWINGS.
20. APPROVED NUMBERS OR ADDRESSES SHALL BE PROVIDED FOR ALL NEW & EXST. BLDGS. IN SUCH A POSITION AS TO BE PLAINLY VISIBLE & LEGIBLE FROM THE STREET OR ROAD FRONTING THE PROPERTY PER THE APPLICABLE CODES.
21. PROVIDE PERMANENT OR TEMPORARY STANDPIPES WHILE BUILDING IS UNDER CONSTRUCTION PER THE APPLICABLE CODES.
22. PROVIDE FIRE EXTINGUISHERS PER THE REQUIREMENTS THE APPLICABLE STANDARDS AND CODES.
11B-201.4 CONSTRUCTION SUPPORT FACILITIES. These requirements shall apply to temporary or permanent construction support facilities for uses and activities not directly associated with the actual processes of construction, including but not limited to offices, meeting rooms, plan rooms, other administrative or support functions. When provided, toilet and bathing facilities serving construction support facilities shall comply with 11B-213. When toilet and bathing facilities serving construction support facilities are provided by portable units, at least one of each type shall be accessible and connected to the construction support facilities it serves by an accessible route.
EXCEPTION: During construction an accessible route shall not be required between site arrival points or the boundary of the area of construction and the entrance to the construction support facilities if the only means of access between them is a vehicular way not providing pedestrian access.
ACCESSIBLE CONSTRUCTION SUPPORT FACILITIES
TEL: 951-743-5208 FAX: 562-904-7296
DIRECTOR OF PUBLIC WORKS/CITY ENGINEER
NAME: CITY OF DOWNEY
CLIENT INFORMATION
CITY,STATE, ZIP: DOWNEY, CA 90241
ADDRESS: 11111 BROOKSHIRE AVENUE
CONTACT: FABIAN AOUN E-MAIL: [email protected]
TEL: 949-261-1001 FAX: 949-260-1190
NAME: LPA, INC.
ARCHITECT
CITY,STATE, ZIP: IRVINE, CA 92617
ADDRESS: 5301 CALIFORNIA AVE, SUITE 100
CONTACT: JEREMY HART E-MAIL: [email protected] TEL: 619-795-2555 FAX: 619-795-2552
NAME: LPA, INC.
LANDSCAPE ARCHITECT
CITY,STATE, ZIP: SAN DIEGO, CA 92106
ADDRESS: 2765 TRUXTUN ROAD
CONTACT: ROCIO GERTLER E-MAIL: [email protected] TEL: 949-261-1001 FAX: 949-260-1190
NAME: LPA, INC.
CIVIL ENGINEER
CITY,STATE, ZIP: IRVINE, CA 92617
ADDRESS: 5301 CALIFORNIA AVE, SUITE 100
CONTACT: KATHEREEN SHINKAI E-MAIL: [email protected] TEL: 562-426-3355 FAX: 562-426-6424
NAME: TWINING, INC.
GEOTECHNICAL ENGINEER
CITY,STATE, ZIP: LONG BEACH, CA 90806
ADDRESS: 2883 EAST SPRING STREET
CONTACT: ADRIAN MORENO E-MAIL: [email protected] TEL: 949-261-1001 FAX: 949-260-1190
NAME: LPA, INC.
STRUCTURAL ENGINEER
CITY,STATE, ZIP: IRVINE, CA 92617
ADDRESS: 5301 CALIFORNIA AVE, SUITE 100
CONTACT: DANIEL WANG E-MAIL: [email protected] TEL: 949-261-1001 FAX: 949-260-1190
NAME: LPA, INC.
MECHANICAL ENGINEER
CITY,STATE, ZIP: IRVINE, CA 92617
ADDRESS: 5301 CALIFORNIA AVE, SUITE 100
CONTACT: KRISTY NELSON E-MAIL: [email protected] TEL: 949-261-1001 FAX: 949-260-1190
NAME: LPA, INC.
ELECTRICAL ENGINEER
CITY,STATE, ZIP: IRVINE, CA 92617
ADDRESS: 5301 CALIFORNIA AVE, SUITE 100
CONTACT: ALDO BACUZZI E-MAIL: [email protected] TEL: 949-261-1001 FAX: 949-260-1190
NAME: LPA, INC.
PLUMBING ENGINEER
CITY,STATE, ZIP: IRVINE, CA 92617
ADDRESS: 5301 CALIFORNIA AVE, SUITE 100
CONTACT: JARED PLUMMER E-MAIL: [email protected] TEL: 661-287-4211
CITY,STATE, ZIP: STEVENSON RANCH, CA 91381
ADDRESS: 24990 BREENSBRIER DRIVE
CONTACT: ANDREW WILSON E-MAIL:[email protected]
NAME: AWC | WEST
SPECIFICATIONS
TEL: 949-751-5800
NAME: WSP
TECHNOLOGY
CITY,STATE, ZIP: IRVINE, CA 92618
ADDRESS: 15231 LAGUNA CANYON ROAD, SUITE 100
CONTACT: ADRIAN MARSH E-MAIL: [email protected]
TEL: 760-488-3232
CITY,STATE, ZIP: TEHACHAPI, CA 93581
ADDRESS: P.O. BOX 2570
CONTACT: BRENT FILIPPINI E-MAIL: [email protected] NAME: KNIGHT BUILDING SYSTEMS
PEMB STRUCTURAL ENGINEER
TEL:
CITY,STATE, ZIP:
ADDRESS:
CONTACT: E-MAIL:
NAME: NUCOR
COLUMN LINES
0 0
SURFACE DRAINAGE
ARROW INDICATES
DIRECTION OF FLOWN
PROJECT NORTH
BUILDING SECTION
1 A101TYP
SECTION ID
SHEET NUMBER
1 A101TYP
WALL SECTION
SECTION ID
SHEET NUMBER
DETAIL CALLOUTS
DETAIL ID
SHEET NUMBER
1 A101
SIM
DETAIL SECTION
DETAIL ID
SHEET NUMBER
1 A101
SIM
DETAIL REFERENCE
DETAIL ID
SHEET NUMBER
1 A101
SIM
INTERIOR ELEVATIONS
DETAIL ID
SHEET NUMBER
A
C
SIM
DBA101
DOOR DESIGNATION
ROOM DESIGNATION
ROOM NUMBER
ROOM AREA
Room name
101
150 SF
1REVISION CLOUD &
TAG (OPTIONAL
SA2U
1t
SHADED PORTION POINTS
TO SIDE REFERENCED
DATUM POINT
KEYNOTE
WALL TYPE
WINDOW TYPE
TYP.?
MATCH LINE
SEE SHEET A101
Name
ElevationLEVEL LINE, CONTROL POINT
EL: 12'-8" = ELEVATION/SECTION
STAIR DIRECTIONDN
UP
CENTER LINES, FLOOR LINES
HIDDEN CONSTRUCTION FEATURE
BREAK LINE
####
FINISH TAGXX-##
EQUIPMENT TAG1i
PROPOSED SITE
DOWNEY SPACE SHUTTLE MUSEUM
ADDRESS:
COLUMBIA WAY
DOWNEY, CA 90242
I-605
IMPERIAL
HWY
I-105
WOODRUFF
AVE
BELLFLOWER
BLVD
LAKEWOOD
BLVD
FIRESTONE
BLVD
PARAMOUNT
BLVD
DOWNEY
AVE
PROJECT NORTHDOWNEY SPACE SHUTTLE EXHIBIT AND EDUCATION BUILDING IS PROPOSED AS A NEW TWO-STORY 39,725 SF BUILDING TO BE LOCATED AT THE CROSS
SECTION OF COLUMBIA WAY AND STEVE HORN WAY IN DOWNEY,
CALIFORNIA. THE PROPOSED MUSEUM INCLUDES STRUCTURAL,
MECHANICAL, ELECTRICAL, AND PLUMBING SYSTEMS.
LIST OF APPLICABLE CODES
2022 CALIFORNIA ADMINISTRATIVE CODE (CAC), PART 1, TITLE 24 CCR 2022 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 CCR 2022 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 CCR 2022 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 CCR 2022 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 CCR 2022 CALIFORNIA ENERGY CODE, PART 6, TITLE 24 CCR
2022 CALIFORNIA FIRE CODE (CFC), PART 9, TITLE 24 CCR
2022 CALIFORNIA EXISTING BUILDING CODE (CEBC), PART 10, TITLE 24 CCR 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN), PART 11, TITLE 24 CCR
2022 CALIFORNIA REFERENCED STANDARDS CODE, PART 12, TITLE 24 CCR TITLE 19 CCR, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS
APPLICABLE STANDARDS
FOR A LIST OF APPLICABLE STANDARDS, INCLUDING CALIFORNIA AMENDMENTS TO THE NFPA STANDARDS, REFER TO CBC CHAPTER 35 AND CFC CHAPTER 80.
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
GENERAL
INFORMATION
G0.21
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDINGABBREVIATIONSCONSTRUCTION NOTES FIRE AND LIFE SAFETY NOTES
ACCESSIBILITY NOTES
PROJECT DIRECTORYSYMBOLS LEGEND VICINITY MAP
PROJECT SCOPE
LIMIT OF WORK
THE INTENT OF THE LIMIT OF WORK LINE IS TO DESCRIBE IN GENERAL THE AREAS AFFECTED BY PROJECT CONSTRUCTION. IT IS NOT INTENDED TO BE AN EXACT INDICATION OR EDGE OF THE CONSTRUCTION AREA. THE CONTRACTOR SHOULD
VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING CONDITIONS AND THEIR RELATIONSHIP TO THE WORK PROPOSED IN THE CONTRACT DOCUMENTS. ALL
ITEMS NECESSARY FOR THE PROPER EXECUTION AND COMPLETION OF THE WORK SHALL BE INCLUDED. THE CONTRACT DOCUMENTS ARE COMPLEMENTARY
AND WHAT IS REQUIRED BY ONE SHALL BE BINDING AS IF REQUIRED BY ALL TO
THE EXTENT THAT IT IS REASONABLY INFERABLE FROM THEM AS BEING NECESSARY TO PRODUCE THE INTENDED RESULTS.
DEFERRED APPROVALSAPPLICABLE CODES
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
11. THE CONTRACTOR SHALL COORDINATE WITH OTHER TRADES, THE ARCHITECT, AND OTHER CONSULTANTS. DESIGN SHALL INCLUDE THE DESIGN OF THE ELEMENT AND ITS CONNECTION TO THE STRUCTURE.
THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THEIR DESIGN
AND SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING DEPARTMENT (CBC 107.3.4.2).
THIS PROJECT HAS BEEN PERMITTED WITHOUT REVIEW AND/OR APPROVAL OF THE FOLLOWING DEFERRED SUBMITTALS. PLANS APPROVED BY THE CITY SHALL
BE OBTAINED FOR EACH DEFERRED ITEM LISTED BELOW PRIOR TO COMMENCING ANY WORK WITHIN THE SCOPE OF SUCH DEFERRAL. DEFERRALS MUST BE
REVIEWED AND ACCEPTED BY THE ARCHITECT OR ENGINEER OF RECORD PRIOR TO SUBMITTING FOR REVIEW WITH THE CITY.
PRE-ENGINEERED/PRE-FABRICATED BUILDING STRUCTURE INCLUDING SECOND FLOOR ASSEMBLY STRUCTURE.
PRE-ENGINEERED/PRE-FABRICATED BUILDING EXTERIOR INSULATED WALL PANELS AND BUILDING ENVELOPE.
PRE-ENGINEERED/PRE-FABRICATED BUILDING STANDING SEAM METAL ROOF.
ELEVATOR GUIDERAILS AND ASSOCIATED SUPPORTS
FIRE SPRINKLER SYSTEM
FIRE ALARM SYSTEM
CURTAIN WALL GLAZING SYSTEM
TWO-WAY COMMUNICATION SYSTEM AT THE ELEVATOR
FACADE ACCESS
PHOTOVOLTAIC SYSTEM AND SUPPORTING STRUCTURE
SEISMIC AND VIBRATION ANCHORAGE AS REQUIRED FOR MEP EQUIPMENT
STRUCTURAL ENGINEER RESPONSIBILITIES
1. 2.
3. 4.
1. 2.
3. LPA STRUCTURAL:
FOUNDATION DESIGN FOR OVERALL STRUCTURE UP TO PEMB COLUMN
ANCHOR BOLTS
INTERIOR STAIRS & SLOPED WALKWAY AT SOUTH SIDE OF BUILDING AT 2ND FLOOR LEVEL.
STEM BUILDING
MEP SYSTEMS SUPPORTS AND BRACING
NUCOR STRUCTURAL (PEMB):
PEMB COLUMNS, BEAMS, ROD BRACING AND WALL GIRTS
MISC COLUMNS AND BEAMS SUPPORTING BUILDING ELEMENTS INCLUDING CURTAIN WALL, BIFOLDING HANGAR DOOR AND ROLLING SERVICE DOORS.
SECOND FLOOR FRAMING AND METAL DECK.
TO REFLECTIVE SURFACELAVATORY GRAB BARMIRRORFEMININE
NAPKIN
VENDING
MACHINE
SEAT
COVER
DISPENSER
URINAL HAND DRYERBABY CHANGING
STATION 33" MIN36" MAX40" MAX ABOVE LAVATORIES44" MAX40" MAX34" MAXKNEE CLEARANCE29" MINKNEE CLEARANCE27" MINNOTE: ALL KNEE &
TOE AREAS ARE TO
BE CLEAR
COUNTERTOP/
TOP OF LAVATORY
ALL EXPOSED PIPES
TO BE INSULATED TO
PROTECT AGAINST
CONTACT. NO SHARP
OR ABRASIVE
SURFACES UNDER
LAVATORIES
6" MAX
KNEE CLEARANCE AT 9"
25" MAX.
8" MIN KNEE
CLEARANCE9" MIN.WASTE/
TOWEL17" MAX13 1/2" MIN
CBC 11B306.2, CBC 11B306.2.2, CBC 11B306.3, CBC 11B-603.3, CBC 11B603.5, CBC 11B-605.2, CBC 11B-606, & CBC 11B609.4 FF
11" MIN.27" MAX.25" MAX.
17" MIN TOE CLEARANCE 17" - 19"35" - 37"44" MIN WHERE
APPROACH IS TO LATCH SIDE
42"12" MAX
60" MIN
32" MIN18" MIN60" MINWATER CLOSET
56" AT WALL MOUNTED
NOTE: TOILET COMPARTMENT DOORS INCLUDING
HARDWARE, SHALL BE MIN. 32" CLR. AND COMPLY
WITH CBC. TOILET COMPARTMENT DOORS IN THE
SIDE OF THE PARITION SHALL BE MIN. 34" CLR.
WATER CLOSET
59" MIN. AT FLOOR MOUNTED
MANEUVERING SPACE
60" MIN AT SIDE DOOR 60" MINWATER CLOSET
56" AT WALL MOUNTED 36" MIN
WATER CLOSET
59" MIN. AT FLOOR MOUNTED
MANEUVERING SPACE
60" MIN
AT OUT-SWINGING DOOR AT IN-SWINGING DOOR
CLEARANCE
DOOR
PERMITTED TO
SWING OVER
HATCHED
PORTION OF
MANEUVERING
SPACE
AT AMBULATORY STALL
60" MIN56" MIN. AT WALL MOUNTED
WATER CLOSET
59" MIN. AT FLOOR MOUNTED
MANEUVERING SPACE
48"' MIN AT DOOR
60" MINAT WALL MOUNTED
56" MIN 36" MIN
WATER CLOSET
59" MIN. AT FLOOR MOUNTED
MANEUVERING SPACE
48" MIN.
AT OUT-SWINGING DOOR AT IN-SWINGING DOOR
CLEARANCE
DOOR
PERMITTED TO
SWING OVER
HATCHED
PORTION OF
MANEUVERING
SPACE
CLEARANCE
CLEARANCE4" MAX4" MAX.4" MAX
4" MAX.
COMPARTMENT DOOR REQUIREMENTS4" MAXLOCATE DOOR ON
FRONT OR SIDE
PARTITION FARTHEST
FROM THE WATER
CLOSET.
DOOR SHALL NOT
SWING INTO REQUIRED
CLEARANCE FOR ANY
FIXTURE EXCEPT FOR
THE MANEUVERING
SPACE INDICATED BY A
HATCH PATTERN ON
DETAILS.
PROVIDE DOOR
PULL ON BOTH
SIDES OF DOOR
NEAR LATCH.
DOOR SHALL BE
SELF-CLOSING
CBC 11B-604.8.1.1.2 & CBC 11B-604.8.1.2
CBC 11B-604.8.1.1.3 & CBC 11B-604.8.1.2
CBC 11B-604.8.1.2 CBC 11B-604.2,CBC 11B-604.5.1, & CBC 11B-604.8.2
DOOR SHALL BE
SELF-CLOSING.
PROVIDE DOOR PULL
ON BOTH SIDES OF
DOOR NEAR LATCH
MIN. 34" CLR AT ALT LOCATION17"-18"42" MIN12" MAX
56" MIN
48" MIN CLR
60" MIN CLR12" MIN24" MIN30" MIN CLR48" MIN CLR
CBC 11B-604.3.1, CBC 11B-604.5.1, & CBC 11B-606.2 18" MIN.DOOR
PERMITTED TO
SWING OVER
HATCHED
PORTION OF
MANEUVERING
SPACE
CL
TOILET TISSUE
DISPENSER
WATER CLOSET (SIDE)WATER CLOSET (FRONT)
CENTERLINE OF
WATER
CLOSET TO FACE OF
FINISH
FLUSH VALVE TO
WIDE
SIDE OF SPACE
SANITARY
NAPKIN
DISPENSER
54" MIN
42" MIN.12" MAX.33" MIN. 36" MAX.MIN.19"MIN.1 1/2"24" MIN. 7"-9"
36" MIN
12" MIN
ACCESSIBLE WATER CLOSET
17" - 18" AT WHEELCHAIR
24" MIN
T.O. GRAB BAR
36" MAX.CBC 11B-604.1/2/7T.O. SEAT17" - 19"30" MIN60" MIN36" MIN33" MIN - 36" MAX48" MAX27" MAX 19" MIN
17" MIN - 19" MAX6" MAX
6" MAXBACK WALL
SIDE WALLSIDE WALL
BACK WALL
OPERABLE
PARTS OF
CONTROLS
AND FAUCETS
CBC 11B-608.2.2, CBC 11B-608.3.2, CBC 11B-608.5.2, CBC 11B-609.4, & CBC 11B-610.3 6" MAX
CENTERLINE 39"- 41"36"60" MIN
6" MAX
6" MAXBACK WALL
SIDE WALLSIDE WALL
BACK WALL
36" MIN
FRONT
WALL48" MAX19" MIN
27" MAX
SIDE WALL
15" MAX
OPPERABLE
PARTS OF
CONTROLS
AND FAUCETS
CBC 11B-608.2.3, CBC 11B-608.3.3 CBC 11B-608.5.348" MAX6" MAX3" MAX3" MAX15"-16"1 1/2" MAX2 1/2" MAX1 1/2" MAX22"-23"14"-15"RECTANGULARL-SHAPED CBC 11B-610.3, CBC 11B-610.3.1, CBC 11B-610.3.2
15"-16"
60" MIN
59" FLOOR MOUNTED WC56" MIN WALL MOUNTED WCCLEARANCE
6" MIN.
PLAN
CBC 11B-604.8.1.4 & CBC 11B-604.8.1.1.3
NOTE:
TOE CLEARANCE AT THE SIDE PARTITION IS NOT
REQUIRED IN A COMPARTMENT GREATER THAN 66"
WIDE
ELEVATION CHILDREN
(K-12)
ELEVATION ADULT 12" MIN6" MIN
9" MIN6" MIN
TOILET
PARTITION
TOILET
PARTITION
CBC 11B-305.7.1
30 x 48
CLR ≤ 24"30 x 48
CLR > 24"36" MIN
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202230% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
ACCESSIBILITY
DETAILS
G0.31
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/2" = 1'-0"05ACCESSIBLE MOUNTING HEIGHTS 3/8" = 1'-0"06ACCESSIBLE TOILET CLEARANCES
15ACCESSIBLE FIXTURES AT
SINGLE ACCOMMODATION RESTROOM
1/2" = 1'-0"17ACCESSIBLE MOUNTING HEIGHTS
24STANDARD ROLL IN SHOWER20ALTERNATE ROLL IN SHOWER16SHOWER COMPARTMENT SEATS 3/8" = 1'-0"08WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT TOE CLEARANCE 3/8" = 1'-0"14ACCESSIBLE URINAL PARTITIONS
60" MIN18" MIN 48" MIN12" MIN48" MIN36" MIN 60" MIN44" MIN22" MIN 48" MIN22" MIN
60" MIN24" MIN 44" MIN24" MIN
48" MIN24" MIN
(A)
FRONT APPROACH, PULL SIDE
(C)
FRONT APPROACH, PUSH SIDE, DOOR
PROVIDED WITH BOTH CLOSER AND LATCH
(B)
FRONT APPROACH, PUSH SIDE
(D)
HINGE APPROACH, PULL SIDE
(G)
HINGE APPROACH, PUSH SIDE, DOOR
PROVIDED WITH BOTH CLOSER AND LATCH
(F)
HINGE APPROACH, PUSH SIDE
(H)
LATCH APPROACH, PULL SIDE
(J)
LATCH APPROACH, PUSH SIDE
(K)
LATCH APPROACH, PUSH SIDE, DOOR
PROVIDED WITH CLOSER
ADD 6 INCHES AT
EXTERIOR SIDE OF
EXTERIOR DOOR.
CBC 11B-404.2.4.160" MINSIDE OF EXTERIOR DOOR
18" MIN AT INTERIOR
24" MIN ON EXTERIOR
X>8"(A) PULL SIDE(B) PUSH SIDE48" MINX>8"(C) PUSH SIDE, DOOR
PROVIDED WITH
BOTH CLOSER AND
LATCH48" MINX>8"12" MIN
CBC 11B-404.2.4.3
48" MIN 48" MIN
48" MIN
(A)(B)
(C)
CBC 11B-404.2.61/4"1/4"1/2"1/4" MAX12
11B-303.3
11B-303.2 X>27"0'-4" MAX
X> 80"11B-307.2
15" MIN48" MAX34" MAX48" MAXUNOBSTRUCTED SIDE REACH
OBSTRUCTED HIGH SIDE REACHOBSTRUCTED HIGH SIDE REACH46" MAX0'-10" MAX. 0'-10" MAX.>10"-24" MAX34" MAXCBC 11B-306.3.1 & CBC 11B-308.3.2 15" MIN48" MAX48" MAX.UNOBSTRUCTED FORWARD REACH
OBSTRUCTED HIGH FORWARD REACHOBSTRUCTED HIGH FORWARD REACH 20" MAX
44" MAX>20"-25" MAX
CBC 11B-308.2.1 & CBC 11B-308.2.2
NOTE: ALIGN CENTER OF ALL WALL SWITCHES & WALL DEVICES @ CENTERLINES U.N.O.
WALL SWITCHES,
ELECTRICAL DEVICES &
THERMOSTAT WHERE
OCCURS; PROVIDE
BRIDGING FRAME AS
NEEDED
ELECTRICAL OUTLET
WHERE OCCURS1'-3"A.F.F.U.N.O.48" A.F.F. MAX.CBC 11B-30827" MAXX < 80"CBC 11B-307.4
GUARDRAIL OR
OTHER BARRIER
60" MIN.48" MIN.18" MIN
MIN.
12"
(U.N.O.)
4" F.O.F.
24" MINPULL SIDE
PUSH SIDE
FRONT APPROACH
CLEAR AT
EXTERIOR DOORS
ON EXTERIOR SIDE
CLEAR AT
INTERIOR
DOORS
PROVIDE THIS
ADDITIONAL SPACE IF
DOOR IS EQUIPPED
WITH BOTH A LATCH
AND A CLOSER
FRONT APPROACH
CBC 11B-404.2.3 & CBC 11B-404.2.4.1
32" MIN. CLR.(80" MIN CLR.)SEE RCP16" MIN16" MIN 16" MIN 48" MIN38" - 43"36" MAX27" MINDRINKING
FOUNTAIN W/
BOTTLE FILLER
ELEVATION
PLAN @ ALCOVE
PLAN -
GUARDRAIL
WHERE NOTED48" MAX16" MIN16" MIN 16" MIN5" MAX15" MIN18" MIN0'-8"4'-0"2'-6" 16".16" MIN 16".
32" MIN @ SINGLE ACCESSIBLE DF
REFER TO FLOOR PLAN
5" MAX15" MIN4'-0"2'-6"19" MAX18" MIN19" MAX18" MIN32" MIN @ SINGLE ACCESSIBLE DF
REFER TO FLOOR PLAN
GUARDRAIL, TYPMIN1'-6"1.
2. 3.
4. 5.
6. 7.
DRINKING FOUNTAIN SHALL BE ACCESSIBLE.
DRINKING FOUNTAINS SHALL BE LOCATED COMPLETELY WITHIN ALCOVES OR
OTHERWISE POSITIONED SO AS NOT TO ENCROACH INTO PEDESTRIAN WAYS. THE ALCOVE IN WHICH THE WATER FOUNTAIN IS LOCATED SHALL NOT BE LESS THAN 32" IN WIDTH AND 18" IN DEPTH.
DRINKING FOUNTAIN SHALL BE A MINIMUM OF 18" AND A MAXIMUM OF 19" IN
DEPTH AND THERE SHALL BE A CLEAR AND UNOBSTRUCTED KNEE SPACE UNDER THE DRINKING FOUNTAIN NOT LESS THAN 27" IN HEIGHT, 30" IN WIDTH AND 8" IN DEPTH, THE DEPTH MEASUREMENT BEING TAKEN FROM THE FRONT EDGE OF THE FOUNTAIN.
THERE SHALL BE TOE CLEARANCE OF 9" IN HEIGHT ABOVE THE FLOOR, AND 17" IN DEPTH FROM THE FRONT EDGE OF THE FOUNTAIN.
A CLEAR FLOOR SPACE AT LEAST 30" X 48" SHALL BE PROVIDED IN FRONT OF THE DRINKING FOUNTAIN TO ALLOW FORWARD APPROACH.
THE DRINKING FOUNTAIN BUBBLER SHALL BE ACTIVATED BY A MANUALLY
OPERATED SYSTEM THAT IS FRONT MOUNTED OR SIDE MOUNTED AND LOCATED WITHIN 6" OF THE FRONT EDGE OF THE FOUNTAIN OR AN ELECTRONICALLY CONTROLLED DEVICE.
THE BUBBLER OUTLET ORIFICE SHALL BE LOCATED WITHIN 5" OF THE FRONT OF THE DRINKING FOUNTAIN AND SHALL BE WITHIN 36" OF THE FLOOR. THE
WATER STREAM FROM THE BUBBLER SHALL BE SUBSTANTIALLY PARALLEL TO THE FRONT EDGE OF THE DRINKING FOUNTAIN.
CBC 11B-306.3, CBC 11B-602, & CBC 11B-602.96" MAX.6" MAX. 5" MAX.
18"-19"
18" MIN. 27" MIN.36" MAX.32" MIN. CL
R.
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202230% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
ACCESSIBILITY
DETAILS
G0.32
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 3/8" = 1'-0"05DOOR CLEARANCES 3/8" = 1'-0"13RECESSED DOOR CLEARANCES 3/8" = 1'-0"08DOOR CLEARANCES - DOORS IN SERIES24CHANGES IN LEVEL16ACCESSIBLE PATH OF TRAVEL
PROTRUDING OBJECT LIMITS
19ACCESSIBLE SIDE REACH REQUIREMENTS15ACCESSIBLE FORWARD REACH REQUIREMENTS 18TYPICAL DEVICE INSTALLATION
20VERTICAL CLEARANCE
14TYPICAL CLEARANCES AT DOOR
21DRINKING FOUNTAIN ALCOVE W/ BOTTLE FILLER
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.50% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
CAL GREEN
CHECKLIST
G0.41
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDINGExceptions: Walks, hardscape areas covered by solar photovoltaic shade structures, and hardscape areas covered by shade structures with roofing materials that comply with Table A5.106.11.2.2 in Appendix A5, are not included in the total area calculation.
5.106.12.3. Hardscape areas. Shade tree plantings, minimum #10 container size or equal shall be installed to provide shade over 20 percent of the hardscape area within 15 years.N/A
Exceptions: Playfields for organized sport activity are not included in the total area calculation.
5.106.12.2 Landscape areas. Shade tress plantings, minimum #10 container size or equal shall be installed to provide shade of 20% of the landscape area within 15 years.N/A
Exceptions: The surface parking area covered by solar photovoltaic shade structures, or shade structures, with roofing materials that comply with Table A5.106.11.2.2 in Appendix A5, are not included in the total area calculations.
5.106.12.1 Surface parking areas. Shade tree plantings, minimum #10 container size or equal, shall be installed to provide shade over 50 percent of the parking area within 15 years.N/A
5.106.12 SHADE TREES [DSA-SS]. Shade Trees shall be planted to comply with Sections 5.106.12.1, 5.106.12.2, and
5.106.12.3. Percentages shown shall be measured at noon on the summer solstice. Landscape irrigation necessary to...N/APROJECT NOT UNDER DSA-SS Exception: Addtions and alterations not altering the drainage path.
5. Other water measures which keep surface water away from buildings and aid in ground water recharge.
4. Water retention gardens.
3. French drains.
2. Water Collection and disposal systems.
1. Swales
5.106.10 GRADING AND PAVING. Construction plans shall indicate how site grading or a drainage system will manage all surface water flows to keep water from entering buildings. Examples of methods to manage surface water include, but are not limited, to the following:YC2.01, C3.01
4. Custom lighting features as allowed by the local enforcing agency, as permitted by Section 101.8 Alternate materials, designs and methods of construction.
3. Building facade meeting the requirements in Table 140.7-B of the California Energy Code, Part 6.
2. Emergency lighting
1. Luminaires that qualify as exceptions in Sections 130.2(b) and 140.7 of the California Energy Code.
Exceptions: [N]
4. Allowable BUG ratings not exceeding those shown in Table 5.106.8, [N] or Comply with a local ordinance lawfully enacted pursuant to Section 101.7, whichever is more stringent.
3. Uplight and Glare ratings as defined in California Energy Code (shown in Tables 130.2-A and 130.2-B in Chapter 8) and
2. Backlight (B) ratings as defined in IES TM-15-11 (shown in Table A-1 in Chapter 8);
1. The minimum requirements in the California Energy Code for Lighting Zones 0-4 as defined in Chapter 10, Section 10-114 of the California Administrative Code; and
5.106.8 LIGHT POLLUTION REDUCTION. [N].l Outdoor lighting systems shall be designed and installed to comply with the following:XE0.21
5.106.5.3.5 [N] Future charging spaces qualify as designated parking as described in Section 5.106.5.2 Designated parking for clean air vehicles.INFORMATION ONLY
5.106.5.3.4 [N] Identification. The service panel or subpanel(s) circuit directory shall identify the reserved overcurrent protective device space(s) for future EV charging as "EV CAPABLE”. The raceway termination location shall be...N/ANO VEHICLE PARKING PROVIDED.
5.106.5.3.3 EV charging space calculations. [N] Table 5.106.5.3.3 shall be used to determine if single or multiple charging space requirements apply for the future installation of EVSE.INFORMATION ONLY
5.106.5.3 Electric vehicle (EV) charging. [N] Construction shall comply with Section 5.106.5.3.1 or Section 5.106.5.3.2 to facilitate future installation of electric vehicle supply equipment (EVSE). When EVSE(s) is/are installed, it shall be in accordance with the California Building Code, the California Electrical Code and as follows:N/ANO VEHICLE PARKING PROVIDED.
Note: Vehicles bearing Clean Air Vehicle stickers from expired HOV lane programs may be considered eligible for designated parking spaces.
5.106.5.2 DESIGNATED PARKING FOR CLEAN AIR VEHICLES. In new projects or additions or alterations that add 10 or more vehicular parking spaces, provide designated parking for any combination of low-emitting, fuel-efficient and carpool/van pool vehicles as follows:N/ANO VEHICLE PARKING PROVIDED.
5.106.4.1.2 Long-term bicycle parking. For new buildings with tenant spaces that have 10 or more tenant-occupants, provide secure bicycle parking for 5 percent of the tenant-occupant vehicular parking spaces with a minimum of one bicycle parking facility.N/ANO BICYCLE PARKING PROVIDED.
5.106.4.1.1 Short-term bicycle parking. If the new project or an addition or alteration is anticipated to generate visitor traffic, provide permanently anchored bicycle racks within 200 feet of the visitors' entrance, readily visible to passers-by, for 5% of new visitor motorized vehicle parking spaces being added, with a minimum of one two-bike capacity rack.N/ANO BICYCLE PARKING PROVIDED.
5.106.4.1 Bicycle parking. [BSC-CG] Comply with Sections 5.106.4.1.1 and 5.106.4.1.2; or meet the applicable local ordinance, whichever is stricter.INFORMATION ONLY
5.106.4 BICYCLE PARKING. For buildings within the authority of California Building Standards Commission as specified in Section 103, comply with Section 5.106.4.1. For buildings within the authority of the Division of the State Architect pursuant to Section 105, comply with Section 5.106.4.2N/ANO BICYCLE PARKING PROVIDED.
5.106.2 STORMWATER POLLUTION PREVENTION FOR PROJECTS THAT DISTURB ONE OR MORE ACRES OF LAND.
Comply with all lawfully enacted stormwater discharge regulations for projects that (1) disturb one acre or more of land, or (2) disturb less than one acre of land but are part of a larger common plan of development or sale.XC0.01, C3.01, C6.03SEE STORM WATER POLLUTION PREVENTION
PLAN, BMP MAINTENANCE NOTES
5.106.1.2 Best Management Practices (BMPs). Prevent the loss of soil through wind or water erosion by implementing an effective combination of erosion and sediment control and good housekeeping BMPs.XC0.01, C5.01EROSION AND SEDIMENT CONTROL PLAN
AND NOTES
5.106.1.1 Local ordinance. Comply with a lawfully enacted storm water management and/or erosion control ordinance.XC0.01, C5.01
STORM WATER POLLUTION PREVENTION
PLAN AND EROSION CONTROL NOTES AND
PLAN.
5.106.1 STORM WATER POLLUTION PREVENTION FOR PROJECTS THAT DISTURB LESS THAN ONE ACRE OF LAND.
Newly constructed projects and additions which disturb less than one acre of land, and are not part of a larger common plan of development or sale, shall prevent the pollution of storm water runoff from the construction activities through one or more of the following measures:
N/AMORE THAN 1 ACRE SEE 5.106.2
SECTION 5.106 SITE DEVELOPMENT
SECTION 5.101 GENERAL
5.101.1 SCOPE
The provisions of this chapter outline planning, design and development methods that include environmentally responsible site selection, building design, building siting and development to protect, restore and enhance the environmental quality of the site and respect the integrity of adjacent properties.
INFORMATION ONLY
DIVISION 5.1 PLANNING AND DESIGNXPROJECT MEETS ALL REQUIRMENTS OF DIVISION 5.1 THROUGH 5.5
CHAPTER 5
NONRESIDENTIAL MANDATORY MEASURESY N/A
REFERENCE
SHEET(S)COMMENTS
2. For a map of know pest and/or disease quarantine zones, consult with the California Department of Food and Agriculture, ( www.cdfa.ca.gov)
1. If contamination by disease or pest infestation is suspected, contact the County Agricultural Commissioner and follow its direction for recycling or disposal of the material.
Notes:
Exception: Reuse, either on or off-site, of vegetation or soil contaminated by disease or pest infestation.
5.408.3 EXCAVATED SOIL AND LAND CLEARING DEBRIS. 100 percent of trees, stumps, rocks and associated vegetation and soils resulting primarily from land clearing shall be reused or recycled. For a phased project, such material may be stockpiled on site until the storage site is developed.X SPEC SECTION
01 74 19
5.408.2 UNIVERSAL WASTE. [A] Additions and alterations to a building or tenant space that meet the scoping provisions in Section 301.3 for nonresidential additions and alterations, shall require verification that Universal Waste items such as fluorescent lamps and ballast and mercury containing thermostats as well as other California prohibited Universal Waste materials are disposed of properly and are diverted from landfills. A list of prohibited Universal Waste materials shall be included in the construction documents.
X SPEC SECTION
01 74 19
2. Mixed construction and demolition debris processors can be located at the California Department of Resources Recycling and Recovery (CalRecycle).
1. Sample forms found in "A Guide to the California Green Building Standards Code (Nonresidential) ” located at www.bsc.ca.gov/Home/CALGreen.aspx may be used to assist in documenting compliance with the waste management plan.
Notes:
5.408.1.4 Documentation. Documentation shall be provided to the enforcing agency which demonstrates compliance with Sections
5.408.1.1, through 5.408.1.3. The waste management plan shall be updated as necessary and shall be accessible during construction for examination by the enforcing agency.X SPEC SECTION 01 74 19
5.408.1.3 Waste stream reduction alternative. The combined weight of new construction disposal that does not exceed two pounds per square foot of building area may be deemed to meet the 65% minimum requirement as approved by the enforcing agency.X SPEC SECTION 01 74 19
3. Demolition waste meeting local ordinance or calculated in consideration of local recycling facilities and markets.
2. Alternate waste reduction methods developed by working with local agencies if diversion or recycle facilities capable of compliance with this item do not exist.
1. Excavated soil and land-clearing debris.
Exceptions to Sections 5.408.1.1 and 5.408.1.2:
Note: The owner or contractor shall make the determination if the construction and demolition waste material will be diverted by a waste management company.
5.408.1.2 Waste Management Company. Utilize a waste management company that can provide verifiable documentation that the percentage of construction and demolition waste material diverted from the landfill complies with this section.X SPEC SECTION 01 74 19
4. Specifies that the amount of construction and demolition waste materials diverted shall be calculated by weight or volume, but not by both.
3. Identifies diversion facilities where construction and demolition waste material collected will be taken.
2. Determines if construction and demolition waste materials will be sorted on-site (source-separated) or bulk mixed (single stream).
1. Identifies the construction and demolition waste materials to be diverted from disposal by efficient usage, recycling, reuse on the project or salvage for future use or sale.
5.408.1.1 Construction waste management plan. Where a local jurisdiction does not have a construction and demolition waste management ordinance, submit a construction waste management plan that:X SPEC SECTION 01 74 19
5.408.1 CONSTRUCTION WASTE MANAGEMENT. Recycle and/or salvage for reuse a minimum of 65% of the non-hazardous construction and demolition waste in accordance with Section 5.408.1.1,5.408.1.2 or 5.408.1.3; or meet a local construction and demolition waste management ordinance, whichever is more stringent.X SPEC SECTION 01 74 19
SECTION 5.408 CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RECYCLING
5.407.2.2.2 Flashing. Install flashings integrated with a drainage planeX A8.00, A8.10, A8.20, A8.21, A8.31, A8.50 SPEC SECTION 07 22 00
4. Other methods which provide equivalent protection.
3. The door is recessed at least 4 feet.
2. The door is protected by a roof overhang at least 4 feet in depth.X A2.01, A3.11, A3.12
1. An installed awning at least 4 feet in depth.
5.407.2.2.1 Exterior door protection. Primary exterior entries shall be covered to prevent water intrusion by using nonabsorbent floor and wall finishes within at least 2 feet around and perpendicular to such openings plus at least one of the following:X A2.01
5.407.2.2 Entries and openings. Design exterior entries and/or openings subject to foot traffic or wind-driven rain to prevent water intrusion into buildings as follows:X A2.01, A3.11, A3.12
5.407.2.1 Sprinklers. Design and maintain landscape irrigation systems to prevent spray on structures.X L6.01
5.407.2 MOISTURE CONTROL. Employ moisture control measures by the following methods.
5.407.1 WEATHER PROTECTION. Provide a weather-resistant exterior wall and foundation envelope as required by California Building Code Section 1402.2 (Weather Protection), manufacturer's installation instructions or local ordinance, whichever is more stringent.X A8.00, A8.10, A8.20,
A8.21, A8.31, A8.50
SEE ARCHITECTURAL DETAIL SHEETS AND
SPECIFICATIONS
SECTION 5.407 WATER RESISTANCE AND MOISTURE MANAGEMENT
5.401.1 SCOPE. The provisions of this chapter shall outline means of achieving material conservation and resource efficiency through protection of buildings from exterior moisture, construction waste diversion, employment of techniques to reduce pollution through recycling of materials, and building commissioning or testing and adjusting.
SECTION 5.401 GENERAL
DIVISION 5.4 MATERIAL CONSERVATION AND RESOURCE EFFICIENCY
2. MWELO and supporting documents, including a water budget calculator, are available at: https://www.water.ca.gov/ .
1. The Model Water Efficient Landscape Ordinance (MWELO) is located in the California Code of Regulations, Title 23, Chapter
2.7, Division 2.
Notes:
5.304.1 OUTDOOR POTABLE WATER USE IN LANDSCAPE AREAS. Nonresidential developments shall comply with a local water efficient landscape ordinance or the current California Department of Water Resources' Model Water Efficient Landscape Ordinance (MWELO), whichever is more stringent.X L6.00
SECTION 5.304 OUTDOOR WATER USE
5.303.6 STANDARDS FOR PLUMBING FIXTURES AND FITTINGS. Plumbing fixtures and fittings shall be installed in accordance with the California Plumbing Code, and shall meet the applicable standards referenced in Table 1701.1 of the California Plumbing Code and in Chapter 6 of this code.X P0.01
5.303.5 AREAS OF ADDITION OR ALTERATION. For those occupancies within the authority of the California Building Standards Commission as specified in Section 103, the provisions of Section 5.303.3 and 5.303.4 shall apply to new fixtures in additions or areas of alteration to the building.X
5.303.4.1 Food Waste Disposers. Disposers shall either modulate the use of water to no more than 1 gpm when the disposer is not in use (not actively grinding food waste/no-load) or shall automatically shut off after no more than 10 minutes of inactivity. Disposers shall use no more than 8 gpm of water.
Note: This code section does not affect local jurisdiction authority to prohibit or require disposer installation.
N/A
5.303.4 COMMERCIAL KITCHEN EQUIPMENT.
Note: Where complying faucets are unavailable, aerators or other means may be used to achieve reduction.
5.303.3.4.5 Metering faucets for wash fountains. Metering faucets for wash fountains shall have a maximum flow rate of not more than 0.20 gallons per minute/20 [rim space (inches) at 60 psi].X
5.303.3.4.4 Metering faucets. Metering faucets shall not deliver more than 0.20 gallons per cycle.X
5.303.3.4.3 Wash fountains. Wash fountains shall have a maximum flow rate of not more than 1.8 gallons per minute/20 [rim space (inches) at 60 psi].X
5.303.3.4.2 Kitchen faucets. Kitchen faucets shall have a maximum flow rate of not more than 1.8 gallons per minute at 60 psi.
Kitchen faucets may temporarily increase the flow above the maximum rate, but not to exceed 2.2 gallons per minute at 60 psi, and must default to a maximum flow rate of 1.8 gallons per minute at 60 psi.X
5.303.3.4.1 Nonresidential Lavatory faucets. Lavatory faucets shall have a maximum flow rate of not more than 0.5 gallons per minute at 60 psi.X
5.303.3.4 Faucets and fountains.
Note: A hand-held shower shall be considered a showerhead.
5.303.3.3.2 Multiple showerheads serving one shower. When a shower is served by more than one showerhead, the combined flow rate of all the showerheads and/or other shower outlets controlled by a single valve shall not exceed 1.8 gallons per minute at 80 psi, or the shower shall be designed to allow only one shower outlet to be in operation at a time.N/A
5.303.3.3.1 Single showerhead. Showerheads shall have a maximum flow rate of not more than 1.8 gallons per minute at 80 psi.
Showerheads shall be certified to the performance criteria of the U.S. EPA WaterSense Specification for Showerheads.N/A
5.303.3.3 Showerheads. [BSC-CG]N/A
5.303.3.2.2 Floor-mounted Urinals. The effective flush volume of floor-mounted or other urinals shall not exceed 0.5 gallons per flush.X
5.303.3.2.1 Wall-mounted Urinals. The effective flush volume of wall-mounted urinals shall not exceed 0.125 gallons per flush.X ``
5.303.3.2 Urinals.
Note: The effective flush volume of dual flush toilets is defined as the composite, average flush volume of two reduced flushes and one full flush.
5.303.3.1 Water Closets. The effective flush volume of all water closets shall not exceed 1.28 gallons per flush. Tank-type water closets shall be certified to the performance criteria of the U.S. EPA WaterSense Specification for Tank-Type toilets.X
5.303.3 WATER CONSERVING PLUMBING FIXTURES AND FITTINGS. Plumbing fixtures (water closets and urinals) and fittings (faucets and showerheads) shall comply with the following:X 1-P0.02 PROJECT MEETS REQUIREMENTS OF SECTION 5.303.3.1 THROUGH 5.303.3.6
5.303.1.2 Excess consumption. A separate submeter or metering device shall be provided for any tenant within a new building or within an addition that is projected to consume more than 1,000 gal/day. c. Steam and hot water boilers with energy input more than 500,000 Btu/h (147 kW). b. Makeup water for evaporative coolers greater than 6 gpm (0.04 Us). a. Makeup water for cooling towers where flow through is greater than 500 gpm (30 Us).
2. Where separate submeters for individual building tenants are unfeasible, for water supplied to the following subsystems:
(Calculate savings by Water Use Worksheets)
1. For each individual leased, rented or other tenant space within the building projected to consume more than 100 gal/day (380 L/day), including, but not limited to, spaces used for laundry or cleaners, restaurant or food service, medical or dental office, laboratory, or beauty salon or barber shop.
5.303.1.1 Buildings in excess of 50,000 square feet. Separate submeters shall be installed as follows:N/A
5.303.1 METERS. Separate submeters or metering devices shall be installed for the uses described in Sections 503.1.1 and 503.1.2.N/A
SECTION 5.303 INDOOR WATER USE
5.301.1 Scope. The provisions of this chapter shall establish the means of conserving water use indoors, outdoors and in wastewater conveyance.INFORMATION ONLY
SECTION 5.301 GENERAL
DIVISION 5.3 WATER EFFICIENCY AND CONSERVATION
5.201.1 Scope [BSC-CG]. California Energy Code [DSA-SS]. For the purposes of mandatory energy efficiency standards in this code, the California Energy Commission will continue to adopt mandatory building standards.
PROJECT WITHIN CALIFORNIA BUILDING
STANDARDS COMMISSION (BSG-CG)
SECTION 5.201 GENERALX M0.10
DIVISION 5.2 ENERGY EFFICIENCY
CHAPTER 5
NONRESIDENTIAL MANDATORY MEASURESY N/A
REFERENCE
SHEET(S)COMMENTS
5.504.4.3.1 Aerosol Paints and coatings. Aerosol paints and coatings shall meet the PWMIR Limits for ROC in Section 94522(a)(3) and other requirements, including prohibitions on use of certain toxic compounds and ozone depleting substances, in Sections 94522(c)(2) and (d)(2) of California Code of Regulations, Title 17, commencing with Section 94520; and in areas under the jurisdiction of the Bay Area Air Quality Management District additionally comply with the percent VOC by weight of product limits of Regulation 8 Rule 49.
X SPEC SECTION
09 91 00
5.504.4.3 Paints and coatings. Architectural paints and coatings shall comply with VOC limits in Table 1 of the ARB Architectural Coatings Suggested Control Measure, as shown in Table 5.504.4.3, unless more stringent local limits apply. The VOC content limit for coatings that do not meet the definitions for the specialty coatings categories listed in Table 5.504.4.3 shall be determined by classifying the coating as a Flat, Nonflat or Nonflat-High Gloss coating, based on its gloss, as defined in Subsections 4.21,4.36 and
4.37 of the 2007 California Air Resources Board Suggested Control Measure, and the corresponding Flat, Nonflat or Nonflat-High Gloss VOC limit in Table 5.504.4.3 shall apply.
X SPEC SECTION
09 91 00
NOTE: FOR ADDITIONAL INFORMATION REGARDING METHODS TO MEASURE THE VOC CONTENT SPECIFIED IN THESE TABLES, SEE SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT RULE 1168.
2. FOR ADDITIONAL INFORMATION REGARDING METHODS TO MEASURE THE VOC CONTENT SPECIFIED IN THIS TABLE, SEE SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT RULE 1168, www.arb.ca.gov/DRDB/SC/CURHTML/R1168.PDF
1. IF AN ADHESIVE IS USED TO BOND DISSIMILAR SUBSTRATES TOGETHER, THE ADHESIVE WITH THE HIGHEST VOC CONTENT SHALL BE ALLOWED.
2. Aerosol adhesives, and smaller unit sizes of adhesives, and sealant or caulking compounds (in units of product, less packaging, which do not weigh more than one pound and do not consist of more than 16 fluid ounces) shall comply with statewide VOC standards and other requirements, including prohibitions on use of certain toxic compounds, of California Code of Regulations, Title 17, commencing with Section 94507.
1. Adhesives, adhesive bonding primers, adhesive primers, sealants, sealant primers and caulks shall comply with local or regional air pollution control or air quality management district rules where applicable, or SCAQMD Rule 1168 VOC limits, as shown in Tables 5.504.4.1 and 5.504.4.2. Such products also shall comply with the Rule 1168 prohibition on the use of certain toxic compounds (chloroform, ethylene dichloride, methylene chloride, perchloroethylene and trichloroethylene), except for aerosol products as specified in subsection 2, below.
5.504.4.1 Adhesives, sealants and caulks. Adhesives, sealants, and caulks used on the project shall meet the requirements of the following standards:X
SPEC SECTION
07 92 00, DIVISION
09 - FINISHES
5.504.4 FINISH MATERIAL POLLUTANT CONTROL. Finish materials shall comply with Sections 5.504.4.1 through 5.504.4.6.X
5.504.3 Covering of duct openings and protection of mechanical equipment during construction. At the time of rough installation and during storage on the construction site until final startup of the heating, cooling and ventilation equipment, all duct and other related air distribution component openings shall be covered with tape, plastic, sheetmetal or other methods acceptable to the enforcing agency to reduce the amount of dust, water and debris which may enter the system.
X
M0.10,
SPEC SECTION
01 52 00
5.504.1 TEMPORARY VENTILATION. The permanent HVAC system shall only be used during construction if necessary to condition the building or areas of addition or alteration within the required temperature range for material and equipment installation.
If the HVAC system is used during construction, use return air filters with a Minimum Efficiency Reporting Value (MERV) of 8, based on ASHRAE 52.2-1999, or an average efficiency of 30% based on ASHRAE 52.1-1992 Replace all filters immediately prior to occupancy, or, if the building is occupied during alteration, at the conclusion of construction.
X
M0.10,
SPEC SECTION
01 52 00
SECTION 5.504 POLLUTANT CONTROL
5.503.1.1 Woodstoves. Woodstoves and pellet stoves shall comply with U.S. EPA New Source Performance Standards (NSPS) emission limits as applicable, and shall have a permanent label indicating they are certified to meet the emission limits.N/A
5.503.1 FIREPLACES. Install only a direct-vent sealed-combustion gas or sealed wood-burning fireplace, or a sealed woodstove or pellet stove, and refer to residential requirements in the California Energy Code, Title 24, Part 6, Subchapter 7, Section 150.
Woodstoves, pellet stoves and fireplaces shall comply with applicable local ordinances.N/A SECTION 5.503 FIREPLACES N/A
5.501.1 SCOPE. The provisions of this chapter shall outline means of reducing the quantity of air contaminants that are odorous, irritating, and/or harmful to the comfort and well-being of a building's installers, occupants and neighbors.
SECTION 5.501 GENERAL
DIVISION 5.5 ENVIRONMENTAL QUALITY
5.410.2.6 Commissioning report. [N] A report of commissioning process activities undertaken through the design and construction phases of the building project shall be completed and provided to the owner or representative.X SPEC SECTION 01 91 13
4. Review of the record drawings on the system/equipment.
3. Review of the information in the Systems Manual.
2. Review and demonstration of servicing/preventive maintenance.
1. System/equipment overview (what it is, what it does and with what other systems and/or equipment it interfaces).
5.410.2.5.2 Systems operations training. [N] A program for training of the appropriate maintenance staff for each equipment type and/or system shall be developed and documented in the commissioning report and shall include the following:X SPEC SECTION 01 78 13
7. Other resources and documentation, if applicable.
6. A copy of verifications required by the enforcing agency or this code.
5. Site equipment inventory and maintenance notes.
4. Major systems.
3. Basic operations and maintenance, including general site operating procedures, basic troubleshooting, recommended maintenance requirements, site events log.
2. Site contact information.
1. Site information, including facility description, history and current requirements.
5.410.2.5.1 Systems manual. [N] Documentation of the operational aspects of the building shall be completed within the systems manual and delivered to the building owner or representative. The systems manual shall include the following:X SPEC SECTION 01 78 13
5.410.2.5 Documentation and training. [N] A Systems Manual and Systems Operations Training are required, including Occupational Safety and Health Act (OSHA) requirements in California Code of Regulations (OCR), Title 8, Section 5142, and other related regulations.X SPEC SECTION
01 78 13
5.410.2.4 Functional performance testing. [N] Functional performance tests shall demonstrate the correct installation and operation of each component, system and system-to-system interface in accordance with the approved plans and specifications. Functional performance testing reports shall contain information addressing each of the building components tested, the testing methods utilized, and include any readings and adjustments made.
X SPEC SECTION
01 91 13
5. Commissioning process activities, schedules and responsibilities. Plans for the completion of commissioning shall be included.
4. Commissioning team information.
e. Measurable criteria for acceptable performance.
d. Conditions under which the test shall be performed.
c. Functions to be tested.
b. Equipment and systems to be tested, including the extent of tests. a. An explanation of the original design intent.
3. Systems to be commissioned. Plans to test systems and components shall include:
2. Commissioning goals.
1. General project information.
5.410.2.3 Commissioning plan. [N] Prior to permit issuance a commissioning plan shall be completed to document how the project will be commissioned. The commissioning plan shall include the following:X SPEC SECTION 01 91 13
3. Water reuse system.
2. Landscape irrigation systems.
1. Renewable energy systems.
5.410.2.2 Basis of Design (BOD). [N] A written explanation of how the design of the building systems meets the OPR shall be completed at the design phase of the building project. The Basis of Design document shall cover the following systems:X SPEC SECTION 01 91 13
6. Building occupant and operation and maintenance (O&M) personnel expectations.
5. Equipment and systems expectations.
4. Project program, including facility functions and hours of operation, and need for after hours operation.
3. Indoor environmental quality requirements.
2. Building sustainable goals.
1. Environmental and sustainability goals.
5.410.2.1 Owner's or Owner Representative's Project Requirements (OPR). [N] The expectations and requirements of the building appropriate to its phase shall be documented before the design phase of the project begins. This documentation shall include the following:X SPEC SECTION
01 08 23
5.410.2 COMMISSIONING. [N] New buildings 10,000 square feet and over. For new buildings 10,000 square feet and over, building commissioning shall be included in the design and construction processes of the building project to verify that the building systems and components meet the owner’s or owner representative’s project requirements. Commissioning shall be performed in accordance with this section by trained personnel with experience on projects of comparable size and complexity. For l-occupancies that are not regulated by OSHPD or for l-occupancies and L-occupancies that are not regulated y the California Energy Code Section 100.0 Scope, all requirements in Sections 5.410.2 through 5.410.2.6 shall apply.
X SPEC SECTION
01 91 13
5.410.1 RECYCLING BY OCCUPANTS. Provide readily accessible areas that serve the entire building and are identified for the depositing, storage and collection of non-hazardous materials for recycling, including (at a minimum) paper, corrugated cardboard, glass, plastics, organic waste, and metals or meet a lawfully enacted local recycling ordinance, if more restrictive.X EXISTING ON-SITE FACILITIES TO BE UTILIZED.
SECTION 5.410 BUILDING MAINTENANCE AND OPERATIONS
CHAPTER 5
NONRESIDENTIAL MANDATORY MEASURES Y N/A
REFERENCE
SHEET(S)COMMENTS
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.50% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
CAL GREEN
CHECKLIST
G0.42
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING5.508.2.5.2 Leaks. Check the system for leaks, repair any leaks, and retest for pressure using the same gauge.X M0.32
5.508.1.2 Halons. Install HVAC, refrigeration and fire suppression equipment that do not contain Halons.X M0.10
5.508.1.1 Chlorofluorocarbons (CFCs). Install HVAC, refrigeration and fire suppression equipment that do not contain CFCs.X M0.10
5.508.1 Ozone depletion and greenhouse gas reductions. Installations of HVAC, refrigeration and fire suppression equipment shall comply with Sections 5.508.1.1 and 5.508.1.2.X M0.10
SECTION 5.508 OUTDOOR AIR QUALITY
5.507.4.3 Interior sound transmission. Wall and floor-ceiling assemblies separating tenant spaces and tenant spaces and public places shall have an STC of at least 40.X A9.01, A9.02, A9.20, A9.21, A9.22
2. Within the 65 CNEL or Ldn noise contour of a freeway or expressway, railroad, industrial source or fixed-guideway source as determined by the Noise Element of the General Plan.N/A
1. Within the 65 CNEL noise contour of an airport.N/A
5.507.4.1 Exterior noise transmission, prescriptive method. Wall and roof-ceiling assemblies exposed to the noise source making up the building or addition envelope or altered envelope shall meet a composite STC rating of at least 50 or a composite OITC rating of no less than 40, with exterior windows of a minimum STC of 40 or OITC of 30 in the following locations:N/A
5.507.4 ACOUSTICAL CONTROL. Employ building assemblies and components with Sound Transmission Class (STC) values determined in accordance with ASTM E 90 and ASTM E 413, or Outdoor-Indoor Sound Transmission Class (OITC) determined in accordance with ASTM E 1332, using either the prescriptive or performance method in Section 5.507.4.1 or 5.507.4.2.X A2.31, A2.32 SEE SPEC SECTIONS SECTION 5.507 ENVIRONMENTAL COMFORT
5.506.2 CARBON DIOXIDE (CO2) MONITORING. For buildings or additions equipped with demand control ventilation, CO2 sensors and ventilation controls shall be specified and installed in accordance with the requirements of the California Energy Code, Section 120(c)(4).X M0.10
5.506.1 OUTSIDE AIR DELIVERY. For mechanically or naturally ventilated spaces in buildings, meet the minimum requirements of Section 120.1 (Requirements For Ventilation) of the California Energy Code, or the applicable local code, whichever is...
X M0.10
SECTION 5.506 INDOOR AIR QUALITY
5.505.1 INDOOR MOISTURE CONTROL. Buildings shall meet or exceed the provisions of California Building Code, CCR, Title 24, Part 2, Sections 1202 (Ventilation) and Chapter 14 (Exterior Walls). For additional measures, see Section 5.407.2 of this code.
X M0.10
SECTION 5.505 INDOOR MOISTURE CONTROL
5.504.7 ENVIRONMENTAL TOBACCO SMOKE (ETS) CONTROL. Where outdoor areas are provided for smoking, prohibit smoking within 25 feet of building entries, outdoor air intakes and operable windows and within the building as already prohibited by other laws or regulations; or as enforced by ordinances, regulations or policies of any city, county, city and county, California Community College, campus of the California State University, or campus of the University of California, whichever are more stringent. When ordinances, regulations or policies are not in place, post...
X
5.504.5.3.1 Labeling. Installed filters shall be clearly labeled by the manufacturer indicating the MERV rating.X M0.10 Exceptions: Existing mechanical equipment.
5.504.5.3 Filters. In mechanically ventilated buildings, provide regularly occupied areas of the building with air filtration media for outside and return air that provides at least a Minimum Efficiency Reporting Value (MERV) of 13. MERV 13 filters shall be installed prior to occupancy, and recommendations for maintenance with filters of the same value shall be included in the operation and maintenance manual.
X M0.10
5.504.4.8.1 Verification of Compliance
Documentation shall be provided verifying that acoustical finish materials meet the pollutant emission limits.
5.504.4.8 Acoustical Ceilings and Wall Panels.
Comply with the requirements of the California Department of Public Health, "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers," Version 1.2, January 2017 (Emission testing method for California Specification 01350).
See California Department of Public Health's website for certification programs and testing labs. https://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx#material
5.504.4.7.1 Verification of Compliance. Documentation shall be provided verifying that thermal insulation materials meet the pollutant emission limits.
5.504.4.7 Thermal Insulation. Comply with the requirements of the California Department of Public Health, "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers," Version
1.2, January 2017 (Emission testing method for California Specification 01350).See California Department of Public Health's website for certification programs and testing
labs. https://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx#material
5.504.4.6.1 Verification of compliance. Documentation shall be provided verifying that resilient flooring materials meet the pollutant emission limits.X SPEC SECTION 09
65 16
5.504.4.6 Resilient flooring systems. Where resilient flooring is installed, at least 80 percent of floor area receiving resilient flooring shall meet the requirements of the California Department of Public Health, "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers," Version 1.2, January 2017 (Emission testing method for California Specification 01350).See California Department of Public Health's website for certification programs and testing labs. https://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx#material
X SPEC SECTION
09 65 16
2. THIN MEDIUM DENSITY FIBERBOARD HAS A MAXIMUM THICKNESS OF 5/16 INCHES (8 MM).
1. VALUES IN THIS TABLE ARE DERIVED FROM THOSE SPECIFIED BY THE CALIFORNIA AIR RESOURCES BOARD, AIR TOXICS CONTROL MEASURE FOR COMPOSITE WOOD AS TESTED IN ACCORDANCE WITH ASTM E 1333. FOR ADDITIONAL INFORMATION, SEE CALIFORNIA CODE OF REGULATIONS, TITLE 17, SECTIONS 93120 THROUGH 93120.12.
5. Other methods acceptable to the enforcing agency.
4. Exterior grade products marked as meeting the PS-1 or PS-2 standards of the Engineered Wood Association, the Australian AS/NZS 2269 or European 636 3S standards.
3. Product labeled and invoiced as meeting the Composite Wood Products regulation (see CCR, Title 17, Section 93120, et seq.).
2. Chain of custody certifications.
1. Product certifications and specifications.
5.504.4.5.3 Documentation. Verification of compliance with this section shall be provided as requested by the enforcing agency.
Documentation shall include at least one of the following:X SPEC SECTION 06 05 73
5.504.4.5 Composite wood products. Hardwood plywood, particleboard and medium density fiberboard composite wood products used on the interior or exterior of the buildings shall meet the requirements for formaldehyde as specified in ARB's Air Toxics Control Measure (ATCM) for Composite Wood (17 CCR 93120 et seq.). Those materials not exempted under the ATCM must meet the specified emission limits, as shown in Table 5.504.4.5.
X SPEC SECTION
06 05 73
5.504.4.4.2 Carpet adhesive. All carpet adhesive shall meet the requirements of Table 5.504.4.1.X SPEC SECTION 09 68 00
5.504.4.4.1 Carpet cushion. All carpet cushion installed in the building interior shall meet the requirements of the Carpet and Rug Institute Green Label program.
5. Compliant with the Collaborative for High Performance Schools California (2014 CA-CHPS) Criteria listed in the CHPS High Performance Product Database.
4. Scientific Certifications Systems Sustainable Choice; or
3. NSF/ANSI 140 at the Gold level or higher;
2. Compliant with the VOC-emission limits and testing requirements specified in the California Department of Public Health Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers, Version 1.1, February 2010 (also known as CDPH Standard Method V1.1 or Specification 01350).
1. Carpet and Rug Institute's Green Label Plus Program.
5.504.4.4 Carpet Systems. All carpet installed in the building interior shall meet at least one of the testing and product requirements:X SPEC SECTION 09
68 00
2. Field verification of on-site product containers
1. Manufacturer's product specification
5.504.4.3.2 Verification. Verification of compliance with this section shall be provided at the request of the enforcing agency.
Documentation may include, but is not limited to, the following:X SPEC SECTION 09 91 00
3. VALUES IN THIS TABLE ARE DERIVED FROM THOSE SPECIFIED BY THE CALIFORNIA AIR RESOURCES BOARD, ARCHITECTURAL COATINGS SUGGESTED CONTROL MEASURE, FEB. 1, 2008. MORE INFORMATION IS AVAILABLE FROM THE AIR RESOURCES BOARD.
2. THE SPECIFIED LIMITS REMAIN IN EFFECT UNLESS REVISED LIMITS ARE LISTED IN SUBSEQUENT COLUMNS IN THE TABLE.
1. GRAMS OF VOC PER LITER OF COATING, INCLUDING WATER & EXEMPT COMPOUNDS CHAPTER 5
NONRESIDENTIAL MANDATORY MEASURES Y N/A
REFERENCE
SHEET(S)COMMENTS
WVLTCVLTSS
S
S
SN 1792873.09E 6520967.53CGCOLUMBIA WAYPROPERTY LINEPROPOSED 2
STORY BUILDING
PROPOSED 1
STORY
CLASSROOMS
CONGRESSMAN STEVE HORN WAY
PROPERTY LINE LIMIT OF WORKROOF ABOVE
26'-0"17'-0"38
'
-
0 "28'-0"2
8 '
-
0 "
70'-7"61'-11 1/4"25'-11 3/4"20'-0"PROJECT NORTHOCCUPANCY: ASSEMBLY GROUP A-3, B, S-2, NONSEPARATED TOTAL BUILDING AREA: 32,960 SF
NUMBER OF STORIES: 2
BUILDING HEIGHT: 54'-8"
FIRE PROTECTION:
AUTOMATIC SPRINKLER SYSTEM
MONITORED FIRE ALARM SYSTEM
(E)
(E)
(E)
(E)
(E)
EXISTING COLUMBIA SPACE MUSEUM
12400 COLUMBIA WAY
1-STORY
TYPE
A-3 OCCUPANCY
10,770 SF
21.01 21.01
21.02 48'-8 1/4"45'-6"
36'-1 1/2"325'-3 3/4"263'-3 1/4"265'-2 1/2"25'-8"
120'-0 1/2"
16'-7 1/4"68'-3 3/4"18'-0
"5'-0"55'-10"36'-6"30'-0"30'-0"30'-0"122'-6"30'-0"250'-0" 30'-0"
30'-0"30'-0"122'-6"ASSUMED PROPERTY LINE
120'-0 1/2"
37'-6"20'-4"77'-4 1/2"
FIRE FLOW ANALYSIS
LEGEND
FIRE ACCESS LANE:
THE SHADED PORTION REPRESENTS THE PERMANENT FIRE
ACCESS LANE. ANY TEMPORARY FORE ACCESS (LANE) DURING
CONSTRUCTION SHALL BE COORDINATED BETWEEN THE FIRE
DEPARTMENT AND THE GENERAL CONTRACTOR. THE
TEMPORARY FIRE ACCESS (LANE) SHALL BE THE
RESPONSIBILITY OF THE GENERAL CONTRACTOR.
PROPOSED BUILDING WITHIN THE HORIZONTAL PROJECTION OF
ROOF ABOVE
LIMIT OF WORK
KEYNOTES
PROPOSED BUILDING
AREA:
40,142 SF
CONSTRUCTION TYPE: TYPE II-B, FULLY SPRINKLERED
BASIC REQUIRED FLOW
(DURATION) (1):
4,250 GPM (4 HOURS)
ADJUSTED REQUIRED
FLOW (2):
1,062.5 GPM (4 HOURS)
HYDRANT REQUIREMENTS
PER CFC APPENDIX
SECTION B105.2:
1,062.5 GPM (4 HOURS)
NUMBER OF HYDRANTS
MIN.
1 HYDRANT SPACING
(ONSITE / TO ROAD) (3)
500' / 250'
1. 2.
3. PER 2022 CFC APPENDIX B, SECTION B105.1, TABLE B105.1(2).
REDUCTION TO 25% OF REQUIRED FIRE-FLOW PRESCRIBED IN TABLE B105.1(2) OF WITH A MINIMUM FIRE-FLOW RATE OF 1,000 GPM, FOR THE PRESCRIBED DURATION IN TABLE B105.1(2) PER 2022 CFC TABLE B105.2.
NUMBER OF HYDRANTS PROVIDED PER SPACING REQUIREMENTS IN 2022 CFC APPENDIX C, TABLE C102.1.
NOTES:
BUILDING FRONTAGE FROM PUBLIC WAY OR OPEN SPACE
FIRE HOSE PULL PATH (150' MAX.)
RED CURB - FIRE LAND IDENTIFICATION
FIRE LANE ENTRANCE SIGN
FIRE HYDRANT (EXISTING NOTED WITH "(E)")
RECESSED KNOX BOX
DOUBLE DETECTOR CHECK
POST INDICATOR VALVE (PIV)
FIRE DEPARTMENT CONNECTION (FDC)
EXISTING BUILDING
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
FIRE ACCESS PLAN
G1.01
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1" = 20'-0"05FIRE ACCESS PLAN
21.01 FIRE RISER FOR STANDARD SPRINKLER SYSTEM
21.02 FIRE RISER FOR PRE-ACTION SPRINKLER SYSTEM
UP
CGUP
15' - 0"
15' - 0"
BUILDING INFORMATION
CONSTRUCTION TYPE: TYPE II-B, FULLY SPRINKLERED NFPA 13, WITH
EMERGENCY VOICE / ALARM COMMUNICATION
SYSTEM
OCCUPANCY:A-3 ASSEMBLY
B OFFICE
S-2 STORAGE
BASIC ALLOWABLE AREA,
HEIGHT (1):
A-3 At A-3 = 28,500 SF & 2 STORIES, 55'
B At B = 57,000 SF & 4 STORIES, 75'
S-2 At S-2 = 78,000 SF & 4 STORIES, 75'
A-3 AREA & HEIGHT ARE MOST RESTRICTIVE
FRONTAGE INCREASE (2):Aa = At + ( NS X If ) (EQUATION 5-3) NSA-3 = 9,500 SF FOR A-3
NSB = 23,000 SF FOR B
NSS-2 = 78,000 SF FOR S-2
F/P = 823'-1" / 828'-1" = 99.4%
THUS If = 0.75 (PER TABLE 506.3.3)
Aa = At + ( NS SF X 0.75 )
ALLOWABLE AREA:A-3 Aa A-3 = 35,625 SF
B Aa B = 74,250 SF
S-2 Aa S-2 = 97,500 SF
1. 2.
3. 4.
5. TABULAR ALLOWABLE AREA 'S' WITH AREA INCREASE VALUE PER 2022 CBC TABLE 504.3 & 504.4 AND 'SM' VALUE WITHOUT HEIGHT INCREASE, IN ACCORDANCE WITH SECTION 506.2.4, TABLE 506.2 NOTE i AND SECTION 503.1.2.
FRONTAGE INCREASE BASED ON CBC 2022 TABLE 506.3.3 & SECTION 506.2.2 FOR MIXED-OCCUPANCY BUILDINGS.
TOTAL BUILDING AREA BASED ON BUILDING AREA AS DEFINED IN 2022 CBC SECTION 202 (TO INCLUDE ROOF OVERHANGS).
NONSEPARATED OCCUPANCIES PER CBC 2022 SECTION 508.3.2, AS BUILDING
AREA COMPLIES WITH MOST RESTRICTIVE OCCUPANCY ALLOWABLE AREA & HEIGHT. (OCCUPANCIES ARE NON-SEPARATED; THE MOST RESTRICTIVE REQUIREMENTS OF CBC CHAPTER 9 FOR EACH NON-SEPARATED
OCCUPANCY SHALL APPLY THROUGHOUT ALL NON-SEPARATED SPACES) MIXED-OCCUPANCY, MULTISTORY BUILDINGS AS REQUIRED BY 2022 CBC SECTION 506.2.2 SINCE BUILDING CONTAINS "A" OCCUPANCY - THE
AGGREGATE SUM OF THE RATIOS OF THE ACTUAL AREA OF EACH STORY EQUATION 5-3, SHALL NOT EXCEED 2.
NOTES:
FIRE-RESISTANCE RATING REQUIRMENTS
PRIMARY STRUCTURAL FRAME:
EXTERIOR BEARING WALLS:
INTERIOR BEARING WALLS:
EXTERIOR NONBEARING WALLS:
INTERIOR NONBEARING WALLS:
FLOOR CONSTRUCTION:
ROOF CONSTRUCTION:
0 0
0 0
0 0
0 FIRE-RESISTANCE RATING REQ FOR BLDG ELEMENTS (CBC 601) FIRE-RESISTANCE RATING REQ FOR EXTERIOR WALLS (TABLE 705.5) 1-HR PROTECTED: 30'-0"
UNPROTECTED,
SPRINKLERED
TYP.
NO LIMIT
EAST ELEVATION NO LIMIT
SOUTH ELEVATION > 30'-0"NO LIMIT
WEST ELEVATION > 30'-0"NO LIMIT
BASED ON TYPE IIB CONSTRUCTION AND OCCUPANCY GROUP A
> 30'-0"
BUILDING AREA,
STORIES, HEIGHT (3):
A1 = 32,960 SF (FIRST FLOOR)
A2 = 7,182 SF (SECOND FLOOR)
TOTAL = 40,142 SF
2 STORIES & 54'-8" HEIGHT
NONSEPARATED OCC. (4):A1 = 32,960 SF < 35,625 SF & 54'-8" < 55' MIXED-OCCUPANCY ANALYSIS (5):
Aa 1st RATIO 2nd RATIO
A-3 35,625 SF 11,433 SF 0.321 19,828 SF 0.557
B 35,625 SF 2,338 SF 0.066 0 SF 0.000
S-2 35,625 SF 2,783 SF 0.078 82 SF 0.002
SUBTOTAL:16,554 SF 0.465 19,910 SF 0.559
SUM OF THE RATIOS: 0.465 + 0.559 = 1.024 < 2 COMPLIES
COMMON PATH OF EGRESS TRAVEL DISTANCE (TABLE 1006.2.1)
BUILDINGS WITH SPRINKLER SYSTEM
A-3 = 75'
B = 100'
S-2 = 100'
EXIT ACCESS TRAVEL DISTANCE (TABLE 1017.2)
BUILDINGS WITH SPRINKLER SYSTEM
A-3 = 250'
B = 300'
S-2 = 400'
A-3 ASSEMBLY OCCUPANCY
PLUMBING FIXTURE CALCULATIONS
PLUMBING FIXTURE OCCUPANT LOAD (CPC CHAPTER 4)
FUNCTION OF SPACE PER CPC TABLE 4-1
GALLERY, MUSEUM, EXHIBIT
FIRST FLOOR
AREA :
OCCUPANT LOAD FACTOR:
CALCULATED OCCUPANTS:
SECOND FLOOR
AREA :
OCCUPANT LOAD FACTOR:
CALCULATED OCCUPANTS:
STEM CLASSROOMS
AREA :
OCCUPANT LOAD FACTOR:
CALCULATED OCCUPANTS:
STAFF ROOM
AREA :
OCCUPANT LOAD FACTOR:
CALCULATED OCCUPANTS:
STORAGE ROOM
AREA :
OCCUPANT LOAD FACTOR:
CALCULATED OCCUPANTS:
8,950 SF
30 298.33
6,197 SF
30 206.56
1,403 SF
30 46.76
836 SF
30 27.86
1,821 SF
500
3.64 584 (583.15 ROUND UP)
292
292
TOTAL CALCULATED OCCUPANTS:
MALE 50%
FEMALE 50%
MINIMUM PLUMBING FACILITIES (TABLE 422.1)
3: 201-400
WATER
CLOSETS
MEN (295)
6: 201-300WOMEN (295)
3: 201-400
URINALS
-
2: 201-400
LAVATORIES
4: 201-300
3: 501-750
DRINKING
FOUNTAINS
1 SERVICE
SINK
10 TOTAL
(5 F + 3 M +
2 SINGLE
OCC.)
PROVIDED 2 MALE 6 2 DF
+ 1 DISP.
AT SINK
1 8252 SF
275 OCC.
EXHIBIT
SPACE
100
A-3 1:30
1731 SF
7 OCC.
STORAGE
101
S-2 1:300
808 SF
48 OCC.
STAFF ROOM
102
B 1:15
502 SF
MECHANICAL
ROOM
103
207 SF
IDF
ROOM
105
64 SF
FAMILY
RESTROOM
108320 SF
WOMEN'S
RESTROOM
107
302 SF
MEN'S
RESTROOM
106
652 SF
33 OCC.
STEM
CLASSROOM
113
B 1:20
751 SF
38 OCC.
STEM
CLASSROOM
112
B 1:20
255 SF
ELECTRICAL
ROOM
104
61 SF
ELEVATOR
MACHINE
ROOM
110
46 SF
JANITOR'S
ROOM
109
27 SF
FIRE
RISER
115
33 19
OCC LOADWIDTH FACTORCALC. WIDTHOR MIN REQ. WIDTH44.0" MIN
44.0" REQ'D WIDTH
24.0"0.2
60.00" PROVIDED
120
STAIR
OCC LOADWIDTH FACTORCALC. WIDTHOR MIN REQ. WIDTH44.0" MIN
44.0" REQ'D WIDTH
24.0"0.2
78.00" PROVIDED
120
STAIR
48 28
27 216
215
MAX OV
E
R
A
L
L
DI
A
G
O
N
A
L
DI
S
T
A
N
C
E
2 5
2'-
3"
ACCUMULATED OCCUPANTS 646MAX OVERALL DIAGONAL DISTANCE 69'-8"45'-10" (MIN REQUIRED SEPARATION DISTANCE = 69'-8" / 3 = 23'-2")SECOND FLOOR ABOVE 64 SF
STAFF
RESTROOM
114
EXIT ACCESS TRAVEL DISTANCE = 190'-0"
(MAX 250' PER CBC TABLE 1016.2)91'-4" (MIN REQUIRED SEPARATION DISTANCE = 252'-3" / 3 = 84'-1")215 OCC LOADWIDTH FACTORCALC. WIDTHOR MIN REQ. WIDTH32.0" MIN
32.0" REQ'D WIDTH
28.4"0.15
36.00" PROVIDED
189
DOOR
OCC LOADWIDTH FACTORCALC. WIDTHOR MIN REQ. WIDTH32.0" MIN
32.0" REQ'D WIDTH
28.4"0.15
72.00" PROVIDED
189
DOOR
OCC LOADWIDTH FACTORCALC. WIDTHOR MIN REQ. WIDTH32.0" MIN
32.0" REQ'D WIDTH
28.2"0.15
72.00" PROVIDED
188
DOOR
OCC LOADWIDTH FACTORCALC. WIDTHOR MIN REQ. WIDTH 32.0" MIN
32.0" REQ'D WIDTH
4.2"0.15
72.00" PROVIDED
28 DOOR
OCC LOADWIDTH FACTORCALC. WIDTHOR MIN REQ. WIDTH32.0" MIN
32.0" REQ'D WIDTH
2.9"0.15
36.00" PROVIDED
19 DOOR #122A
OCC LOADWIDTH FACTORCALC. WIDTHOR MIN REQ. WIDTH32.0" MIN
32.0" REQ'D WIDTH
3.5"0.15
36.00" PROVIDED
23 DOOR #113
ELEVATOR
OCC LOADWIDTH FACTORCALC. WIDTHOR MIN REQ. WIDTH32.0" MIN
32.0" REQ'D WIDTH
2.9"0.15
36.00" PROVIDED
19 DOOR #122B
19 119
119
146
81 SF
NURSING
ROOM
116
3181 SF
106 OCC.
EXHIBIT
SPACE
100A
A-3 1:30
6190 SF
207 OCC.
OPEN EXHIBIT
SPACE
200
A-3 1:30
OPEN TO BELOW
DN
OCC LOADWIDTH FACTORCALC. WIDTHOR MIN REQ. WIDTH44.0" MIN
44.0" REQ'D WIDTH
24.0"0.2
60.00" PROVIDED
120
STAIR
OCC LOADWIDTH FACTORCALC. WIDTHOR MIN REQ. WIDTH44.0" MIN
44.0" REQ'D WIDTH
24.0"0.2
78.00" PROVIDED
120
STAIR EXIT ACCESS TRAVEL DISTANCE 190'-0"MAX OVERALL DIAGONAL DISTANCE 127' - 8"(MAX 250' PER CBC TABLE 1016.2)ELEVATOR 882 SF
30 OCC.
WALKWAY
VIEWING
GALLERY
202
A-3 1:30
ACCUMULATED OCCUPANTS 237
119
119
82 SF
ACCESS
201
35'-0"17'-7"69'-0"(MIN. REQUIRED SEPARATION DISTANCE = 127'-8" / 3 = 42'-7")40'-8"17'-8"12'-1"47'-8"42'-5" 0 0
### SF
Occ-Load OCC.
Room Name
###
# 1:OLF
ROOM NUMBER
SQUARE FOOTAGE
OCCUPANT LOAD
OCCUPANCY LOAD FACTOR
OCCUPANCY GROUP
COMBINED ROOM OCCUPANCY LOAD
INDIVIDUAL ROOM OCCUPANCY LOAD
EXIT ACCESS TRAVEL DISTANCE
COMMON PATH OF EGRESS DISTANCE
EGRESS PLAN LEGEND
METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD FIRE BARRIER
A-3 ASSEMBLY - EXHIBIT SPACES
B BUSINESS SPACES
S-2 STORAGE SPACES
N/A NON-OCCUPIED SPACES / ACCESSORY SPACE
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
CODE ANALYSIS
G2.01
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 3/32" = 1'-0" G2.01 09FIRST FLOOR EGRESS PLAN
3/32" = 1'-0"
G2.01 11SECOND FLOOR EGRESS PLAN PROJECT NORTHPROJECT NORTH
NTS
VICINITY MAP
NCOLUMBIA WAYARDIS AVEIMPERIAL HWY
CONGRESSMAN
STEVE HORN WAY
CARING WAYAPOLLO WAY
CENTURY FWY
GLENN ANDERSON FWY
FOSTER RD
STEWART AND
GRAY RD
BELLFLOWER BLVDLAKEWOOD BLVDBROOKSHIRE AVEDOWNEY AVEALA M
E
D
A
S
T
IMP
E
R
I
A
L
H
W
Y
105
PROJECT
LOCATION
E E
FW FW
SD SD
W W
DEDICATED PRIVATEFIRE SERVICE
REMOVE EXISTING UTILITY
SANITARY SEWER LINE
DOMESTIC WATER LINE
STORM DRAIN LINE(≤8" DIAMETER)
NATURAL GAS LINE
FLOW LINE
RIGHT OF WAY/PROPERTY LINE
FENCE
AB AGGREGATE BASE
AC ASPHALT CONCRETE PAVEMENT
AE ACCESS EASEMENT
ASPH ASPHALT PAVING
BC BEGIN CURVATURE
BCR BEGIN CURB RETURN
BFP BACK FLOW PREVENTER
BI BOX INLET
BM BENCHMARK
BOP BOTTOM OF PIPE
BOR BOTTOM OF RAMP
BS BOTTOM OF STAIRS
BVC BEGIN VERTICAL CURVATURE
BW BOTTOM OF WALL
C&G CURB AND GUTTER
C/L,CL CENTER LINE
CB CATCH BASIN
CONST CONSTRUCT
CR CURB RETURN
CT COURT
CUL CULVERT
DI DROP INLET
DIP DUCTILE IRON PIPE
DW DOMESTIC WATER
D/W DRIVEWAY
DE DRAINAGE EASEMENT
DR DRIVE
(E) EXISTING
E EAST
EC END CURVATURE
ECR END CURB RETURN
EG EXISTING GRADE
ELEV ELEVATION
EOC EDGE OF CONCRETE
EP EDGE OF PAVEMENT
EQ EQUAL
ESMT EASEMENT
EVC END OF VERTICAL CURVATURE
FF FINISHED FLOOR
FFE FINISHED FLOOR ELEVATION
FG FINISHED GRADE
FH FIRE HYDRANT
FL FLOWLINE
FS FINISHED SURFACE
FW FIRE PROTECTION SERVICE WATER
GB GRADE BREAK
GFL GUTTER FLOWLINE
GSL LIMITS OF GRAVITY SEWER
GR GRATE
GV GAS VALVE
HB HOSE BIB
HP HIGH POINT
ICV IRRIGATION CONTROL VALVE
INTX POINT OF INTERSECTION
INV INVERT
JP JOINT POLE
LE LANDSCAPE EASEMENT
LF LINEAR FEET
LIP LIP OF GUTTER
LP LOW POINT
LT LEFT
MAX MAXIMUM
MH MANHOLE
MIN MINIMUM
MOC MIDDLE OF CURVATURE
N NORTH
NG NATURAL GRADE
NTS NOT TO SCALE
OC ON CENTER
(P) PROPOSED, NEW
PA PLANTING AREA
PBC PULL BOX CABLE
PBE PULL BOX ELECTRIC
PBT PULL BOX TELEPHONE
PBW PULL BOX WATER
PCC POINT OF COMPOUND CURVATURE
PE PEDESTRIAN EASEMENT
PI POINT OF INTERSECTION
PIVC POINT OF INTERSECTION VERTICAL
CURVATURE
PL PROPERTY LINE
POC POINT OF CONNECTION
PP POWER POLE
PRC POINT OF REVERSE CURVATURE
PVC POLYVINYL CHLORIDE
PVMT PAVEMENT
R RADIUS
RCP REINFORCED CONCRETE PIPE
RIM TOP RIM OF STRUCTURE
ROW HIGHWAY EASEMENT
RT RIGHT
RW RECLAIMED WATER
R/W RIGHT OF WAY
S SOUTH OR SLOPE
SBE SETBACK EASEMENT
SCO SANITARY SEWER CLEANOUT
SD STORM DRAIN
SDMH STORM DRAIN MANHOLE
SF SQUARE FEET
SHT SHEET
STA STATION
SMH SANITARY SEWER MANHOLE
SS SANITARY SEWER
SWPPP STORM WATER POLLUTION
PREVENTION PLAN
S/W SIDEWALK
T TANGENT
TB TOP OF BERM
TBC TOP BACK OF CURB
TBW TOP BACK OF WALK
TC TOP OF CURB
TF TOP OF FOOTING
TG TOP OF GRATE
TOE TOE OF SLOPE
TOP TOP OF PIPE
TOR TOP OF RAMP
TOS TOP OF SLOPE
TP TOP OF PLANTER
TS TOP OF STAIRS
TW TOP OF WALL
TYP TYPICAL
TP TELEPHONE POLE
VC VERTICAL CURVATURE
W WEST
WM WATER MAIN
WV WATER VALVE
EXISTING ELECTRICALLINE / CONDUIT
EXISTING DEDICATEDPRIVATE FIRE SERVICE
EXISTING STORM DRAIN LINE
EXISTING WATER LINE
EXISTING SEWER LINE
APPROXIMATE PROJECTLIMITS
GRADE BREAK LINE
PERFORATED STORMDRAIN LINE
G G EXISTING NATURALGAS SERVICE
T T
EXISTINGTELECOMMUNICATIONSLINE / CONDUIT
SS SS
DESCRIPTIONLINE TYPE
STORM DRAIN LINE(>8" DIAMETER)
ABBREVIATIONS
LEGEND
DESCRIPTIONSYMBOL
ROOF DRAIN POC 5' FROM BUILDING
GAS POC 5' FROM BUILDING
FIRE WATER POC 5' FROM BUILDING
DOMESTIC WATER POC 5' FROM BUILDING
SANITARY SEWER POC 5' FROM BUILDING
STORM DRAIN MANHOLE
SANITARY SEWER MANHOLE
DRAIN INLET
AREA DRAIN
TRENCH DRAIN
CLEANOUT
BLOW OFF
FIRE HYDRANT
VALVE
POST INDICATOR VALVE (PIV)/CHECK VALVE(CHK VLV)/FIRE DEPARTMENT CONNECTION (FDC)
CHECK VALVE (CHK VLV)
FIRE DEPARTMENT CONNECTION (FDC)
DOUBLE DETECTOR CHECK (DBL CHK)
REDUCED PRESSURE (BFP)
POST INDICATOR VALVE (PIV)
THRUST BLOCK
BENDS, TEE AND CROSS
WATER METER
AD
XXLF S=X.XXX
XXLF PVC
XXLF S=X.XXX
XXLF S=X.XXX
GB
XXLF PVC
XXLF PVC
co
M
D
S
6"SS
8"FW
6"SD
GAS
6"DW
12"SD
RD
G
F
W
SS
1. THE CONTRACTOR SHALL CONTACT THE RESPECTIVE UTILITY OWNERS FOR LOCATION,
REMOVAL, AND/OR RELOCATION OF ANY UTILITY SERVICES AFFECTED BY CONSTRUCTION. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONARY
MEASURES TO PROTECT UNDERGROUND OR OVERHEAD STRUCTURES WHETHER OR NOT THEY ARE SHOWN ON THESE DRAWINGS.
2. THE CONTRACTOR SHALL NOTIFY THE PROJECT INSPECTOR AND THE RESPECTIVE
UTILITY OWNERS AND OTHER AGENCIES AT LEAST TWO WORKING DAYS PRIOR TO START OF CONSTRUCTION.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR EXPOSING, VERIFYING LOCATIONS (BOTH HORIZONTAL AND VERTICAL), AND MAINTAINING ALL EXISTING UNDERGROUND
UTILITIES, BOTH SHOWN ON THE PLANS AND/OR NOT SHOWN ON THE PLANS DURING CONSTRUCTION. REPAIR DAMAGED UTILITIES TO THE SATISFACTION OF THE ENGINEER.
THE CONTRACTOR SHALL LOCATE EXISTING UNDERGROUND UTILITIES SUFFICIENTLY
AHEAD OF CONSTRUCTION TO PERMIT REVISIONS TO PLANS BECAUSE OF LOCATIONS
OF EXISTING FACILITIES AND SHALL REPORT ALL DISCREPANCIES TO THE ENGINEER PRIOR TO THE COMMENCEMENT OF WORK.
4. THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITIES AND/OR
STRUCTURES SHOWN ON THESE PLANS WERE OBTAINED BY A SEARCH OF THE AVAILABLE RECORDS. APPROVAL OF THESE PLANS DOES NOT CONSTITUTE A
REPRESENTATION AS TO THE ACCURACY OR COMPLETENESS OF THE LOCATION OR
THE EXISTENCE, OR NON-EXISTENCE OF ANY UTILITY AND/OR STRUCTURE WITHIN THE LIMITS OF THIS PROJECT. THE CONTRACTOR IS REQUIRED TO TAKE ALL DUE
PRECAUTIONARY MEASURES TO PROTECT THE UTILITIES OF RECORD AND/OR NOT OF
RECORD SHOWN OR NOT SHOWN AND ANY OTHER LINE(S) OR STRUCTURE(S) NOT SHOWN ON THESE PLANS. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF, AND/OR DAMAGE TO THESE LINE(S) AND/OR STRUCTURE(S).
5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR TEMPORARY SHORING AT PROPOSED
BUILDING FOUNDATIONS, FOOTINGS, AND WALLS TO PROTECT EXISTING UTILITIES IN PLACE.
6. UNAUTHORIZED CHANGES AND USES - CAUTION: THE ENGINEER PREPARING THESE
PLANS WILL NOT BE RESPONSIBLE FOR, OR LIABLE FOR, UNAUTHORIZED CHANGES TO OR USES OF THESE PLANS. ALL CHANGES TO THE PLANS MUST BE IN WRITING AND MUST BE APPROVED BY THE PREPARER OF THESE PLANS.
7. THE CONTRACTOR SHALL MAINTAIN THE EXISTING ACCESSIBLE ROUTE CLEAR OR
PROVIDE AN ALTERNATE ACCESSIBLE ROUTE OF TRAVEL DURING DEMOLITION AND/OR CONSTRUCTION.
8. THE CONTRACTOR SHALL MAINTAIN THE EXISTING FIRE EXITS AND STAIRS CLEAR AND
USABLE OR PROVIDE ALTERNATE FIRE EXITS DURING DEMOLITION AND/OR CONSTRUCTION.
1. ALL ASBESTOS CEMENT PIPE TO BE REMOVED SHALL BE SNAPPED, ENCAPSULATED, AND DISPOSED OF PER LOCAL, STATE, AND FEDERAL REGULATIONS.
2. DOMESTIC WATER SERVICE AND FIRE PROTECTION SHALL BE MAINTAINED DURING CONSTRUCTION. PROVIDE BYPASS LINES DURING CONSTRUCTION INCLUDING TIE-IN.
COORDINATE ALL SHUT DOWNS OF WATER AND POWER WITH OWNER PRIOR TO CONSTRUCTION.
3. PURSUANT TO CALIFORNIA ASSEMBLY BILL 1953 ALL PIPE, FITTINGS, AND FIXTURES
INTENDED TO CONVEY OR DISPENSE WATER FOR HUMAN CONSUMPTION THROUGH DRINKING WATER OR COOKING SHALL BE "LEAD FREE" AS OF JANUARY 1, 2010.
IMPORTANT NOTICE
GENERAL NOTES TO CONTRACTOR
Job Number
Date Published
Checked By
Scale
Revision DateARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
3055401
RR
AS SHOWN
CITY OF DOWNEY PUBLIC WORKS - STREET IMPROVEMENT PLANS
SPACE SHUTTLE EXHIBIT AND EDUCATION BUILDING
COLUMBIA WAY
DOWNEY, CA 90242
CITY OF DOWNEY
Developed for
100% CONSTRUCTION DOCUMENTS 07/25/2025
1. CONTRACTOR SHALL RETAIN THE SERVICES OF AN INDEPENDENT REGISTERED CONSULTING ARBORIST.
2. THE ARBORIST SHALL PROVIDE CONTRACTOR WITH RECOMMENDATIONS AND SPECIFICATIONS AS TO THE REMOVAL OF THE EXISTING TREE.
3. ARBORIST SHALL BE ON-SITE TO OBSERVE THE REMOVAL OF TREE.
4. THE ARBORIST SHALL BE CERTIFIED WITH THE AMERICAN SOCIETY OF CONSULTING ARBORISTS OR INTERNATION SOCIETY OF ARBORICULTURE.
5. CONTRACTOR SHALL FOLLOW ALL ARBORIST RECOMMENDATIONS AND SPECIFICATIONS, UNLESS OTHERWISE DIRECTED BY CLIENT/ARCHITECT.
TREE REMOVAL NOTES
TITLE SHEET
C1.01
7/25/2025
1. THE INTENT OF THE DEMOLITION PLAN IS TO DESCRIBE IN GENERAL THE DEMOLITION AREAS AFFECTED BY THE PROJECT CONSTRUCTION. IT IS NOT INTENDED AS A DETAILED DESCRIPTION OF EXISTING ITEMS OR ELEMENTS TO BE REMOVED. THE
CONTRACTOR SHALL VISIT THE SITE AND REVIEW ANY AVAILABLE RECORD
DOCUMENTS TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS AND SHOULD
INCLUDE THE REMOVAL OF ALL ITEMS NECESSARY FOR THE PROPER EXECUTION AND COMPLETION OF THE WORK. THE CONTRACT DOCUMENTS ARE COMPLEMENTARY, AND
WHAT IS REQUIRED BY ONE SHALL BE BINDING AS IF REQUIRED BY ALL TO THE EXTENT
THAT IT IS REASONABLY INFERABLE FROM THEM AS BEING NECESSARY TO PRODUCE THE INTENDED RESULTS.
2. REMOVE EXISTING BUILDINGS, FOUNDATIONS AND SERVICE UTILITIES AS INDICATED ON PLANS. CAP ALL UTILITIES AT APPROPRIATE POINTS. ALL EXISTING ELECTRICAL /
TELEPHONE / CATV UTILITIES SHALL BE REMOVED AS INDICATED OR BACK TO THE POINT WHERE THE SPECIFIC UTILITY SYSTEM ENTERS THE WORK AREA. COORDINATE DEMOLITION OF ALL UTILITIES WITH THE OWNER. ALL UTILITIES CONNECTED TO
EXISTING BUILDINGS TO REMAIN SHALL CONTINUE TO BE OPERATIONAL DURING THE DEMOLITION PROCESS. DOMESTIC AND FIRE SERVICE WATER AND NATURAL GAS SHALL
BE REMOVED TO A POINT OUTSIDE THE PERIMETER OF PROPOSED NEW CONSTRUCTION TO EXISTING VALVES OR SIMILAR SHUT-OFF DEVICES. IF A SHUT-OFF
DEVICE IS NOT REASONABLY ADJACENT TO THE PERIMETER OF THE PROPOSED NEW CONSTRUCTION, PROVIDE A SHUT-OFF DEVICE IN BELOW-GRADE YARD BOX. CONFIRM LOCATION OF NEW DEVICES WITH OWNER PRIOR TO INSTALLATION. SANITARY SEWER
AND STORM DRAINAGE SHALL BE CAPPED TO A POINT OUTSIDE THE PERIMETER OF THE PROPOSED NEW CONSTRUCTION. OTHER UTILITIES NOT SPECIFICALLY IDENTIFIED
IN THESE DOCUMENTS AND NOT ANTICIPATED FOR REUSE SHALL BE REMOVED IN ENTIRETY.
3. FOR ALL EXISTING MATERIALS THAT CAN BE SALVAGED, OWNER HAS FIRST RIGHT OF
REFUSAL FOR REMOVED ITEMS THAT MAY HAVE RESIDUAL COMMERCIAL OR HISTORIC
VALUE INCLUDING HARDWARE, GLASS, CORNER STONES, TIME CAPSULES, LIGHT
STANDARDS, SIGNS, FENCING, BENCHES, WATER FOUNTAINS, TRASH CONTAINERS, ETC. SHALL REMAIN AS PROPERTY OF THE OWNER. ALL ITEMS TO BE SALVAGED FOR REUSE/REINSTALLATION MUST MEET CURRENT CODE REQUIREMENTS. COORDINATE
ITEMS TO BE RETAINED WITH OWNER AND REMOVE FROM CONSTRUCTION SITE TO A LOCATION APPROVED BY OWNER. REMOVED MATERIALS, NOT INDICATED OR DIRECTED
TO BE SALVAGED FOR THE OWNER'S BENEFIT ARE DEBRIS AND BECOME THE CONTRACTOR'S PROPERTY UPON REMOVAL.
4. THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITY PIPES OR
STRUCTURES SHOWN ON THESE PLANS ARE OBTAINED BY SEARCH OF THE AVAILABLE RECORDS AND FIELD SURVEYS. THE CONTRACTOR SHALL CONTACT UNDERGROUND
SERVICE ALERT, UTILITY COMPANIES, AND/OR FIELD VERIFY AND LOCATE ALL UTILITIES BEFORE PROCEEDING WITH WORK. THE CONTRACTOR IS ALSO REQUIRED TO TAKE DUE
PRECAUTIONARY MEASURES TO PROTECT THE UTILITY LINES SHOWN AND ANY OTHER LINES NOT OF RECORD OR NOT SHOWN ON THESE PLANS. NOTIFY THE ENGINEER IF
ADDITIONAL UTILITIES ARE LOCATED OR IF CONFLICTS ARE FOUND WITH EXISTING CONDITIONS.
5. ALL TREES TO BE REMOVED SHALL BE MARKED BY CONTRACTOR AND APPROVED FOR
REMOVAL BY THE OWNER OR OWNER'S REPRESENTATIVE PRIOR TO REMOVING OR CUTTING TREE(S). EXISTING ROOTS SHALL BE GRINDED TO A DEPTH OF APPROXIMATELY 3-FEET. USE CAUTION WHILE GRINDING WHEN EXISTING UTILITIES ARE IN CLOSE PROXIMITY TO TREES. ALL TREES TO REMAIN WITHIN THE LIMIT OF WORK SHALL BE PROTECTED AND MAINTAINED PER SPECIFICATIONS AND DETAILS.
6. SAWCUT EXISTING CONCRETE AND ASPHALT TO AN EXISTING CONTROL JOINT WHERE POSSIBLE, AT MINIMUM TO A NEAT-STRAIGHT LINE. ALL DEBRIS SHALL BE HAULED OFFSITE TO A LEGAL DUMPING SITE OR SALVAGED FOR REUSE ON PROJECT AS NOTED.
7. WORK WITHIN CITY, COUNTY, OR STATE RIGHT-OF-WAY REQUIRES A SEPARATE
ENCROACHMENT PERMIT WHICH THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING PRIOR TO STARTING WORK WITHIN RIGHT-OF-WAY.
8. CONTRACTOR TO COORDINATE UTILITY DEMOLITION WITH DRAINAGE AND UTILITY WORK SHOWN IN THIS PLAN SET. ALL UTILITY SHUTDOWNS SHALL BE COORDINATED PER PROJECT SPECIFICATIONS.
9. EXISTING DRY UTILITIES SHOWN FOR DEMOLITION ARE SHOWN FOR COORDINATION ONLY. REFER TO OTHER DISCIPLINES FOR LIMITS AND DETAILS OF DEMOLITION.
10. THE CONTRACTOR SHALL RECYCLE CONSTRUCTION DEBRIS, ASPHALT, AND CONCRETE GENERATED FROM REMOVALS REQUIRED TO CONSTRUCT THE PROJECT. THE
CONTRACTOR IS OBLIGATED, UNDER THIS CONTRACT, TO RECYCLE THE WASTE MATERIAL THROUGH AN APPROVED RECYCLING PLANT.
11. A LIST OF FACILITIES THAT ACCEPT CONSTRUCTION & DEMOLITION DEBRIS CAN BE FOUND ON THE CALRECYCLE WEBSITE AT:
HTTPS://WWW.CALRECYCLE.CA.GOV/CONDEMO
12. CONTRACTOR IS RESPONSIBLE FOR PROTECTING EXISTING BUILDING FINISHES DURING DEMOLITION. ANY FINISH THAT IS DAMAGED DURING DEMOLITION SHALL BE REPAIRED OR REPLACED IN-KIND OR BETTER.
DEMOLITION NOTES
FOR SITE PREPARATION, OVEREXCAVATION, FOUNDATION RECOMMENDATIONS, PAVEMENT,
SUBGRADE, AND GRADATION REQUIREMENTS SEE GEOTECHNICAL INVESTIGATION REPORT ENTITLED:
"GEOTECHNICAL ENGINEERING EVALUATION REPORT, SPACE SHUTTLE EXHIBIT AND EDUCATION BUILDING, 12400 COLUMBIA WAY, DOWNEY, CALIFORNIA" PREPARED BY: TWINING, INC.
4811 AIRPORT PLAZA DRIVE
SUITE 220
LONG BEACH, CA 90815
PROJECT NO: 210932.01
DATED: MARCH 11, 2022
DATED:JULY 16, 2025
GEOTECHNICAL INFORMATION
PURSUANT TO THE CALIFORNIA GOVERNMENT CODE
SECTION 4216, NO EXCAVATION PERMIT IS VALID
UNLESS DIG ALERT HAS BEEN CONTACTED AT LEAST
TWO (2) WORKING DAYS PRIOR TO THE
COMMENCEMENT OF EXCAVATION AND AN INQUIRY
IDENTIFICATION NUMBER HAS BEEN ISSUED.
INQUIRY ID#
DIG ALERT NOTICE
LEGAL DESCRIPTION
BASIS OF BEARINGS
BENCHMARK
C1.01 TITLE SHEET
C2.01 SEWER UTILITY PLAN
C3.01 SEWER UTILITY DETAILS
CIVIL SHEET INDEX
ELEVATIONS SHOWN HEREON ARE RELATIVE TO THE NORTH AMERICAN VERTICAL DATUM OF 1988 (NAVD88) COUNTY OF LOS ANGELES PUBLIC WORKS 2005 ADJUSTMENT PER THE FOLLOWING COUNTY BENCHMARK:
LA COUNTY BM EY6105 ELEV.=96.219 FT. NAVD88 YEAR 2005
RDBM TAG IN S CB 5' W/O CBR @ SE COR IMPERIAL HIGHWAY & CLARK AVE
ANY USER OF ELEVATIONS AND/OR COORDINATES SHOWN HEREON FOR THE CONTROL OF CONSTRUCTION, SHALL VERIFY AT LEAST 3 POINTS SHOWN HEREON, FOR MATHEMATICAL CONSISTENCY PRIOR TO SUCH USE.
SUBTRACT 2.208 FEET TO ELEVATIONS HEREON TO ADJUST TO THE NGVD DATUM YEAR 1975 LA COUNTY ADJUSTMENT.
THE BEARING OF N89°51'30"E ALONG THE CENTERLINE OF IMPERIAL HIGHWAY AS SHOWN ON MAP OF RECORD OF SURVEY RS BOOK 229 PG 90 AND IS THE BASIS OF BEARINGS FOR THIS SURVEY.
CURRENT LEGAL DESCRIPTION OF SUBJECT PROPERTY HAS NOT BEEN SUPPLIED TO SURVEYOR. SUBJECT PROPERTY LINES HAVE BEEN DETERMINED BY LA COUNTY ASSESSOR MAP 6256-004; APN OF SUBJECT PROPERTY IS 6256-004-910. PROPERTY LINES ARE SUBJECT TO CHANGE.
CONTRACTOR TO ADJUST TO FINISH GRADE ALL EXISTING UTILITY BOXES, SEWER
CLEANOUT COVERS, PULL BOXES AND VALVE COVERS NOT SPECIFICALLY SHOWN WITHIN THE LIMITS OF WORK.
DEMOLITION LEGEND
DESCRIPTION
REMOVE (E) STRIPING.
REMOVE (E) TREE, SEE DEMOLITION NOTE 5 SHEET C0.01.
SAWCUT (E) PAVEMENT AS NEEDED.
DESCRIPTION
DEMOLITION KEYNOTES
REMOVE (E) TREE.
REMOVE (E) STRIPING.
30 A
LABEL
KEY
NOTE
DEMOLITION NOTES
-SEE DEMOLITION NOTES, SHEET C1.01.
31 9797WWWWWW WWFW FW
WWSDSDSDSSSSSSSSSD
M
REPAIR (E) LANDSCAPE
& IRRIGATION INKINDCLR/W40.00'
(E)12" CML DIP WATER MAIN
PER DWG NO. 3-42-30W
(E)21" VCP TRUNK SEWER
PER DWG NO. 3-38-02
(E)81" RCP STORM DRAIN
PER DWG NO. 364-3103-D2.2
BD
41 41
4142
41 42 42
42 45
44 45
REPAIR (E) LANDSCAPE
& IRRIGATION INKIND
PUBLIC GRADING NOTES
DESCRIPTIONKEY
NOTE
PUBLIC PAVING LEGEND
LABEL DESCRIPTION
GRIND & OVERLAY
GRIND & OVERLAY MINIMUM 2' AND JOIN EXISTING PAVEMENT AND MATCH THE ELEVATION.
JOIN EXISTING PAVEMENT AND MATCH EXISTING GRADE.
JOIN EXISTING CURB AND/OR GUTTER AND MATCH GRADE.
ASPHALT PAVEMENT TRENCH RESTORATION
PAVEMENT SECTION PER CITY OF DOWNEY PER CITY OF DOWNEY
DEPARTMENT OF PUBLIC WORKS ENGINEERING DEPARTMENT
CONSTRUCT ROLLED CURB PER CITY OF DOWNEY DEPARTMENT OF PUBLIC WORKS ENGINEERING DIVISION. SEE DETAILS 01, SHEET C3.01.
PROTECT IN PLACE.
REPLACE PORTIONS OF EXISTING STRIPING DISTURBED DURING CONSTRUCTION.
1. UTILITIES TO CROSS OVER OR UNDER OTHER UTILITIES TO MAINTAIN 12" MINIMUM CLEARANCE AT UTILITY CROSSINGS, UNLESS NOTED OTHERWISE. SANITARY SEWER TO CROSS UNDER POTABLE WATER.
2. CONTRACTOR SHALL VERIFY SIZE AND LOCATION (HORIZONTAL AND VERTICAL) OF
EXISTING CROSSING AND JOINING UTILITIES PRIOR TO CONSTRUCTION AND IMMEDIATELY NOTIFY THE ENGINEER OF ANY CONFLICT.
3. CONTRACTOR SHALL CONSTRUCT GRAVITY UTILITIES (SEWER AND STORM DRAIN) BEFORE OTHER UTILITIES. CONSTRUCTION OF THESE GRAVITY UTILITIES TO START FROM THE DOWNSTREAM ENDS.
4. EXISTING UTILITIES ARE COMPILED BASED ON PREVIOUS BASE FILES, FIELD SURVEY AND FIELD VERIFICATION. POTHOLING IS RECOMMENDED TO VERIFY ANY AND ALL UTILITIES KNOWN OR UNKNOWN WHICH MAY BE IN CONFLICT WITH PROPOSED CONSTRUCTION.
5. PRIOR TO THE REMOVAL OF ANY WET OR DRY UTILITY LINES, THE CONTRACTOR SHALL
CONFIRM WITH OWNER REPRESENTATIVE WHETHER THESE UTILITY LINES ARE STILL ACTIVE OR NOT. IMMEDIATELY NOTIFY THE ENGINEER OF ANY CONFLICT.
6. CONTRACTOR TO ADJUST TO FINISH GRADE ALL EXISTING UTILITY BOXES, SEWER
CLEANOUT COVERS, PULL BOXES AND VALVE COVERS NOT SPECIFICALLY SHOWN WITHIN THE LIMITS OF WORK.
CONSTRUCTION NOTES:
B
CONCRETE PAVEMENT
CONSTRUCT VEHICULAR PAVEMENT SECTION PER CITY OF DOWNEY DEPARTMENT OF PUBLIC WORKS ENGINEERING DEPARTMENT. SEE
DETAIL 02 SHEET C3.01
C
41 42
D
43 44
45 RELOCATE EXISTING STREET LIGHT.469797
SSSSW W W
WWWWWWEEEEEESSSSSSSSSS (E) 15" (ABAND)
CO
SCLR/W40.00'
(E)12" CML DIP WATER MAIN
PER DWG NO. 3-42-30W
(E)21" VCP TRUNK SEWER
PER DWG NO. 3-38-02
(E)81" RCP STORM DRAIN
PER DWG NO. 364-3103-D2.2
BD
41 41
42(96.95)TC
(96.26)FL
42 (96.95)TC
(96.30)FL
43 44
44 44
30 A
32 (96.96)TC
(96.30)FL
97WWWWWEEEEESDSDSD SD
G G G G G G G
SSSSSSSSSSCO
(E)12" CML DIP WATER MAIN
PER DWG NO. 3-42-30W
(E)21" VCP TRUNK SEWER
PER DWG NO. 3-38-02
(E)81" RCP STORM DRAIN
PER DWG NO. 364-3103-D2.2
40.00'CLR/W22'
B
42 (97.07)TC
(96.41)FL
43 44
44 A
46 44
32 42 (97.15)TC
(96.49)FL
xxxx
xxx989797979797979798989898979797969798989797
9696969796989896979898W W W W
GGGGGGGGGGGGSSco coSS
W
WWWWWWWWWWWWW W
SDSDco
EEEEEESDSDSDEEE E E EEEEEEEEEG GSSSSSSSSSSSS
SSSSSSSS (E) 15" (ABAND)
CO
M
CO
CO
CO MS
CO
CO
03 -COLUMBIA WAY80.00'
10.00'EX. EASEMENTCLR/WR/WCONGRESSMAN STEVE HORN WAY
80.00'
10.00'EX. EASEMENT
02 -
40.00'
01 -
40.00'
N
3015 600
1" = 30'PLAN VIEW
N
105 200
1" = 10'01ENLARGEMENT
105 200
1" = 10'03ENLARGEMENT
Job Number
Date Published
Checked By
Scale
Revision DateARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
3055401
RR
AS SHOWN
CITY OF DOWNEY PUBLIC WORKS - STREET IMPROVEMENT PLANS
SPACE SHUTTLE EXHIBIT AND EDUCATION BUILDING
COLUMBIA WAY
DOWNEY, CA 90242
CITY OF DOWNEY
Developed for
100% CONSTRUCTION DOCUMENTS 07/25/2025
N
105 200
1" = 10'02ENLARGEMENT
STREET PLAN
C2.01
7/25/2025
N
Job Number
Date Published
Checked By
Scale
Revision DateARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
3055401
RR
AS SHOWN
CITY OF DOWNEY PUBLIC WORKS - STREET IMPROVEMENT PLANS
SPACE SHUTTLE EXHIBIT AND EDUCATION BUILDING
COLUMBIA WAY
DOWNEY, CA 90242
CITY OF DOWNEY
Developed for
100% CONSTRUCTION DOCUMENTS 07/25/2025
01 C3.01
DETAILS
7/25/2025
NTS02NTS
Job Number
Date Published
Checked By
Scale
Revision DateARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
3055401
RR
AS SHOWN
CITY OF DOWNEY PUBLIC WORKS - OFFSITE WATER UTILITY PLANS
SPACE SHUTTLE EXHIBIT AND EDUCATION BUILDING
COLUMBIA WAY
DOWNEY, CA 90242
CITY OF DOWNEY
Developed for
100% CONSTRUCTION DOCUMENTS 07/25/2025
1.LOCATION OF EXISTING UTILITIES/UNDERGROUND FACILITIES KNOWN TO ENGINEER ARE SHOWN IN THEIR APPROX. LOCATIONS BASED ON BEST AVAILABLE INFORMATION AT TIME OF PREPARING PLANS. ACTUAL LOCATION, SIZE, TYPE, AND NUMBER OF
UTILITIES/UNDERGROUND FACILITIES MAY DIFFER FROM THAT SHOWN AND SUCH UTILITIES/FACILITIES MAY BE PRESENT THAT ARE NOT SHOWN. IT IS THE CONTRACTOR’S RESPONSIBILITY TO HAVE SITE INSPECTED THROUGH USA PRIOR TO
COMMENCING WORK AND TO VERIFY LOCATIONS OF ALL UTILITIES WITH RESPECTIVE OWNERS PRIOR TO STARTING WORK AND THROUGHOUT CONTRACT.
2. POTHOLE/HAND DIG AT UTILITY CROSSINGS/OBSTRUCTIONS, AND AREAS WHERE
LOCATION OF UTILITIES AND UNDERGROUND FACILITIES ARE IN QUESTION PRIOR TO STARTING WORK. ANY CHANGES TO PROPOSED WATER IMPROVEMENTS MUST BE APPROVED BY CITY.
3. COORDINATE WITH OWNER OF ANY UTILITY OR OBSTRUCTION PRIOR TO RELOCATING/ADJUSTING ANY SUCH ITEMS.
4. POTHOLE POCS WITH EXISTING MAINS TO DETERMINE EXISTING ELEVATIONS AND VERIFY MEANS OF CONNECTING PRIOR TO STARTING WORK.
5. WORK LIMITED TO THOSE HOURS AS STATED IN THE ENCROACHMENT AND OTHER CITY PERMITS.
6. CONTACT ROBERT AMAYA AT 562-448-8942 (DOWNEY UTILITIES YARD) INSPECTOR MIN 72-HRS PRIOR TO STARTING WORK TO SCHEDULE INSPECTION
7. MAINTAIN HORIZONTAL (MIN 10-FT) AND VERTICAL SEPARATION (MIN 1-FT ABOVE) FROM RECYCLED WATER AND SEWER LINES.
8. ADD FITTINGS TO MAINTAIN MIN. COVER OF 42-INCH AND TO AVOID EXISTING UTILITIES ENCOUNTERED. IF MINIMUM COVER CANNOT BE MET, PIPELINE SHALL BE ENCASED IN
CONCRETE OR WITH STEEL CASING PIPE (WITH SPACERS AND END CAPS) IF NECESSARY AS DIRECTED BY THE CITY. AT NO TIME SHALL THERE BE LESS THAN 36-INCH COVER FROM TOP OF PIPE TO EXISTING GROUND DURING CONSTRUCTION.
CHANGE IN PROFILE AND/OR NEED FOR ENCASEMENT SHALL BE APPROVED BY CITY OF DOWNEY.
9. CONTRACTOR SHALL RESTORE, AT ITS COST, ANY ITEMS OUTSIDE THE LIMITS OF THE
TRENCH WHICH ARE DAMAGED AS THE RESULT OF CONTRACTOR OPERATIONS, OR
THOSE ITEMS DAMAGED WITHIN THE LIMITS OF THE TRENCH WHICH WERE TO REMAIN IN PLACE. ANY ITEMS REQUIRED TO REMAIN IN PLACE, SHALL BE RESTORED TO THEIR ORIGINAL CONDITION AND LOCATION THAT EXISTED PRIOR TO CONSTRUCTION.
10. LENGTH OF OPEN TRENCH LIMITED TO AMOUNT OF PIPE TO BE INSTALLED IN ONE DAY.
PROTECT TRENCH FROM PEDESTRIAN/VEHICULAR TRAFFIC PER CITY REQUIREMENTS
INCLUDING BARRIERS, BACKFILL, COMPACTION, TEMPORARY PAVEMENT, AND STEEL PLATES. NO OPEN TRENCH AREAS SHALL REMAIN OVERNIGHT.
11. NO STORAGE OF MATERIALS/EQUIPMENT IN PUBLIC RIGHT-OF-WAY. PROVIDE OFFSITE/ONSITE STAGING/STORAGE AREA.
12. TRAFFIC CONTROL PER THE CALIFORNIA MANUAL OF UNIFORM TRAFFIC CONTROL DEVICES (MUTCD), AND AS REQUIRED BY THE TRAFFIC ENGINEER.
13. PIPE BASE, PIPE ZONE, AND TRENCH ZONE BACKFILL - IMPORTED SAND OR NATIVE MATERIAL WITH MIN SE OF 30 OR COEFF. OF PERMEABILITY >1.4 IN/HR @ MIN 90% REL.
COMPACTION. CERT. OF IMPORTED OR NATIVE MATERIAL REQUIRED.
14. PAVEMENT ZONE – FOR AREAS CURRENTLY PAVED, AC/PCC PAVEMENT AND
AGGREGATE BASE SHALL BE REPLACED TO EXISTING THICKNESS PLUS ONE INCH UNLESS OTHERWISE CALLED OUT IN THE PLANS AND SPECS. MIN. 95% REL.
COMPACTION. FOR AREAS THAT ARE NOT CURRENTLY PAVED, SEE STREET IMPROVEMENT PLANS FOR AC PAVEMENT/BASE REQUIREMENTS. MIN. 95% REL.
COMPACTION.
15. OBTAIN AND PAY FOR THE SERVICES OF A CHLORINATION CONTRACTOR. NAME AND
QUALIFICATIONS OF PROPOSED FIRM SHALL BE SUBMITTED FOR APPROVAL BY THE CITY.
16. COMPACTION, PRESSURE, DISINFECTION, AND BACTERIOLOGICAL TESTING PER CITY REQUIREMENTS. COMPACTION TESTS AT RANDOM DEPTHS AND INTERVALS AS DIRECTED BY CITY. PRESSURE TEST AT 200 PSI FOR 4-HR. NO PRESSURE TESTING AGAINST CLOSED VALVES – USE PRESSURE PLATES. COMPLETELY BACKFILL AND COMPACT PRIOR TO CONDUCTING TESTS.
17. PROVIDE TEMP OR PERMANENT MATERIALS/EQUIPMENT NECESSARY TO PERFORM ALL TESTING (I.E. COPPER SERVICES FOR INTRODUCING DISINFECTANT, BLOWOFFS FOR
FLUSHING, AIR RELEASE/VACUUM VALVES FOR REMOVING/ADDING AIR DURING
FILLING/FLUSHING OF PIPELINES, MJXFL ADAPTERS, PRESSURE PLATES, VALVES, PIGS, LAUNCHER, FITTINGS).
18. CONTRACTOR MUST UTILIZE FULL DIAMETER CITY MAIN LINE AND POTABLE WATER FROM DIRECTLY ADJACENT CITY DISTRIBUTION SYSTEM FOR FLUSHING ONLY. USE OF 2” AND 4” OUTLETS AND FIRE HYDRANT HOSES WILL NOT BE ALLOWED FOR FLUSHING PURPOSES.
IF INITIAL FLUSHING AND CHLORINATION FAILS TO PRODUCE REQUIRED RESIDUALS AND
BAC-T TEST RESULTS, CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CITY COSTS
ASSOCIATED WITH RE-FLUSHING, RE-DISINFECTION, AND RE-TESTING OF WATER FACILITIES INCLUDING BUT NOT LIMITED TO: CITY TIME, MATERIALS, EQUIPMENT, WATER, LABORATORY ANALYSIS, ETC.
19. CONTRACTOR SHALL RETURN ALL EXISTING METERS REMOVED IN ORDER FOR CITY
INSPECTOR TO COMPLETE NEW METER FORMS FOR EACH OF THE NEW METERS INSTALLED AND THOSE REMOVED.
20. RPS AND DCDAS SHALL BE CERTIFIED IN THE FIELD BY A LICENSED LA COUNTY DPH CERTIFIED TESTER PRIOR TO PLACING INTO SERVICE. CONTACT DOWNEY UTILITY YARD AT (562) 904-7202 TO SCHEDULE CITY INSPECTION OF TESTING. PROVIDE CERTIFICATION OF TESTING TO DOWNEY UTILITIES YARD REPRESENTATIVE.
21. OWNER MUST ESTABLISH ACCOUNTS WITH THE CITY CASHIER PRIOR TO USING NEW POTABLE WATER METERS AND FIRE SERVICES.
22. SUBMIT CERTIFICATION OF PIPING AND MATERIALS FOR COMPLIANCE WITH CITY STANDARDS. ALL PIPING AND ASSOCIATED MATERIALS MUST BE IN-HAND PRIOR TO START OF CONSTRUCTION.
23. IN NO EVENT SHALL ANY VALVE BE INSTALLED WITHIN A CURB, GUTTER, OR OTHER CONCRETE DRAINAGE DEVICE.
24. CONTRACTOR SHALL FURNISH THE CITY OF DOWNEY WITH RED-LINED CONSTRUCTION
PLANS NOTING ANY AND ALL CHANGES TO THE PLAN AND PROFILE OF THE POTABLE WATER IMPROVEMENTS INSTALLED.
CITY OF DOWNEY: GENERAL NOTES - POTABLE WATER
NTS
VICINITY MAP
NCOLUMBIA WAYARDIS AVEIMPERIAL HWY
CONGRESSMAN
STEVE HORN WAY
CARING WAYAPOLLO WAY
CENTURY FWY
GLENN ANDERSON FWY
FOSTER RD
STEWART AND
GRAY RD
BELLFLOWER BLVDLAKEWOOD BLVDBROOKSHIRE AVEDOWNEY AVEALA M
E
D
A
S
T
IMP
E
R
I
A
L
H
W
Y
105
PROJECT
LOCATION
E E
FW FW
SD SD
W W
DEDICATED PRIVATEFIRE SERVICE
REMOVE EXISTING UTILITY
SANITARY SEWER LINE
DOMESTIC WATER LINE
STORM DRAIN LINE(≤8" DIAMETER)
NATURAL GAS LINE
FLOW LINE
RIGHT OF WAY/PROPERTY LINE
FENCE
AB AGGREGATE BASE
AC ASPHALT CONCRETE PAVEMENT
AE ACCESS EASEMENT
ASPH ASPHALT PAVING
BC BEGIN CURVATURE
BCR BEGIN CURB RETURN
BFP BACK FLOW PREVENTER
BI BOX INLET
BM BENCHMARK
BOP BOTTOM OF PIPE
BOR BOTTOM OF RAMP
BS BOTTOM OF STAIRS
BVC BEGIN VERTICAL CURVATURE
BW BOTTOM OF WALL
C&G CURB AND GUTTER
C/L,CL CENTER LINE
CB CATCH BASIN
CONST CONSTRUCT
CR CURB RETURN
CT COURT
CUL CULVERT
DI DROP INLET
DIP DUCTILE IRON PIPE
DW DOMESTIC WATER
D/W DRIVEWAY
DE DRAINAGE EASEMENT
DR DRIVE
(E) EXISTING
E EAST
EC END CURVATURE
ECR END CURB RETURN
EG EXISTING GRADE
ELEV ELEVATION
EOC EDGE OF CONCRETE
EP EDGE OF PAVEMENT
EQ EQUAL
ESMT EASEMENT
EVC END OF VERTICAL CURVATURE
FF FINISHED FLOOR
FFE FINISHED FLOOR ELEVATION
FG FINISHED GRADE
FH FIRE HYDRANT
FL FLOWLINE
FS FINISHED SURFACE
FW FIRE PROTECTION SERVICE WATER
GB GRADE BREAK
GFL GUTTER FLOWLINE
GSL LIMITS OF GRAVITY SEWER
GR GRATE
GV GAS VALVE
HB HOSE BIB
HP HIGH POINT
ICV IRRIGATION CONTROL VALVE
INTX POINT OF INTERSECTION
INV INVERT
JP JOINT POLE
LE LANDSCAPE EASEMENT
LF LINEAR FEET
LIP LIP OF GUTTER
LP LOW POINT
LT LEFT
MAX MAXIMUM
MH MANHOLE
MIN MINIMUM
MOC MIDDLE OF CURVATURE
N NORTH
NG NATURAL GRADE
NTS NOT TO SCALE
OC ON CENTER
(P) PROPOSED, NEW
PA PLANTING AREA
PBC PULL BOX CABLE
PBE PULL BOX ELECTRIC
PBT PULL BOX TELEPHONE
PBW PULL BOX WATER
PCC POINT OF COMPOUND CURVATURE
PE PEDESTRIAN EASEMENT
PI POINT OF INTERSECTION
PIVC POINT OF INTERSECTION VERTICAL
CURVATURE
PL PROPERTY LINE
POC POINT OF CONNECTION
PP POWER POLE
PRC POINT OF REVERSE CURVATURE
PVC POLYVINYL CHLORIDE
PVMT PAVEMENT
R RADIUS
RCP REINFORCED CONCRETE PIPE
RIM TOP RIM OF STRUCTURE
ROW HIGHWAY EASEMENT
RT RIGHT
RW RECLAIMED WATER
R/W RIGHT OF WAY
S SOUTH OR SLOPE
SBE SETBACK EASEMENT
SCO SANITARY SEWER CLEANOUT
SD STORM DRAIN
SDMH STORM DRAIN MANHOLE
SF SQUARE FEET
SHT SHEET
STA STATION
SMH SANITARY SEWER MANHOLE
SS SANITARY SEWER
SWPPP STORM WATER POLLUTION
PREVENTION PLAN
S/W SIDEWALK
T TANGENT
TB TOP OF BERM
TBC TOP BACK OF CURB
TBW TOP BACK OF WALK
TC TOP OF CURB
TF TOP OF FOOTING
TG TOP OF GRATE
TOE TOE OF SLOPE
TOP TOP OF PIPE
TOR TOP OF RAMP
TOS TOP OF SLOPE
TP TOP OF PLANTER
TS TOP OF STAIRS
TW TOP OF WALL
TYP TYPICAL
TP TELEPHONE POLE
VC VERTICAL CURVATURE
W WEST
WM WATER MAIN
WV WATER VALVE
EXISTING ELECTRICALLINE / CONDUIT
EXISTING DEDICATEDPRIVATE FIRE SERVICE
EXISTING STORM DRAIN LINE
EXISTING WATER LINE
EXISTING SEWER LINE
APPROXIMATE PROJECTLIMITS
GRADE BREAK LINE
PERFORATED STORMDRAIN LINE
G G EXISTING NATURALGAS SERVICE
T T
EXISTINGTELECOMMUNICATIONSLINE / CONDUIT
SS SS
DESCRIPTIONLINE TYPE
STORM DRAIN LINE(>8" DIAMETER)
ABBREVIATIONS
LEGEND
DESCRIPTIONSYMBOL
ROOF DRAIN POC 5' FROM BUILDING
GAS POC 5' FROM BUILDING
FIRE WATER POC 5' FROM BUILDING
DOMESTIC WATER POC 5' FROM BUILDING
SANITARY SEWER POC 5' FROM BUILDING
STORM DRAIN MANHOLE
SANITARY SEWER MANHOLE
DRAIN INLET
AREA DRAIN
TRENCH DRAIN
CLEANOUT
BLOW OFF
FIRE HYDRANT
VALVE
POST INDICATOR VALVE (PIV)/CHECK VALVE(CHK VLV)/FIRE DEPARTMENT CONNECTION (FDC)
CHECK VALVE (CHK VLV)
FIRE DEPARTMENT CONNECTION (FDC)
DOUBLE DETECTOR CHECK (DBL CHK)
REDUCED PRESSURE (BFP)
POST INDICATOR VALVE (PIV)
THRUST BLOCK
BENDS, TEE AND CROSS
WATER METER
AD
XXLF S=X.XXX
XXLF PVC
XXLF S=X.XXX
XXLF S=X.XXX
GB
XXLF PVC
XXLF PVC
co
M
D
S
6"SS
8"FW
6"SD
GAS
6"DW
12"SD
RD
G
F
W
SS
1. THE CONTRACTOR SHALL CONTACT THE RESPECTIVE UTILITY OWNERS FOR LOCATION,
REMOVAL, AND/OR RELOCATION OF ANY UTILITY SERVICES AFFECTED BY CONSTRUCTION. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONARY
MEASURES TO PROTECT UNDERGROUND OR OVERHEAD STRUCTURES WHETHER OR NOT THEY ARE SHOWN ON THESE DRAWINGS.
2. THE CONTRACTOR SHALL NOTIFY THE PROJECT INSPECTOR AND THE RESPECTIVE
UTILITY OWNERS AND OTHER AGENCIES AT LEAST TWO WORKING DAYS PRIOR TO START OF CONSTRUCTION.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR EXPOSING, VERIFYING LOCATIONS (BOTH HORIZONTAL AND VERTICAL), AND MAINTAINING ALL EXISTING UNDERGROUND
UTILITIES, BOTH SHOWN ON THE PLANS AND/OR NOT SHOWN ON THE PLANS DURING CONSTRUCTION. REPAIR DAMAGED UTILITIES TO THE SATISFACTION OF THE ENGINEER.
THE CONTRACTOR SHALL LOCATE EXISTING UNDERGROUND UTILITIES SUFFICIENTLY
AHEAD OF CONSTRUCTION TO PERMIT REVISIONS TO PLANS BECAUSE OF LOCATIONS
OF EXISTING FACILITIES AND SHALL REPORT ALL DISCREPANCIES TO THE ENGINEER PRIOR TO THE COMMENCEMENT OF WORK.
4. THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITIES AND/OR
STRUCTURES SHOWN ON THESE PLANS WERE OBTAINED BY A SEARCH OF THE AVAILABLE RECORDS. APPROVAL OF THESE PLANS DOES NOT CONSTITUTE A
REPRESENTATION AS TO THE ACCURACY OR COMPLETENESS OF THE LOCATION OR
THE EXISTENCE, OR NON-EXISTENCE OF ANY UTILITY AND/OR STRUCTURE WITHIN THE LIMITS OF THIS PROJECT. THE CONTRACTOR IS REQUIRED TO TAKE ALL DUE
PRECAUTIONARY MEASURES TO PROTECT THE UTILITIES OF RECORD AND/OR NOT OF
RECORD SHOWN OR NOT SHOWN AND ANY OTHER LINE(S) OR STRUCTURE(S) NOT SHOWN ON THESE PLANS. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF, AND/OR DAMAGE TO THESE LINE(S) AND/OR STRUCTURE(S).
5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR TEMPORARY SHORING AT PROPOSED
BUILDING FOUNDATIONS, FOOTINGS, AND WALLS TO PROTECT EXISTING UTILITIES IN PLACE.
6. UNAUTHORIZED CHANGES AND USES - CAUTION: THE ENGINEER PREPARING THESE
PLANS WILL NOT BE RESPONSIBLE FOR, OR LIABLE FOR, UNAUTHORIZED CHANGES TO OR USES OF THESE PLANS. ALL CHANGES TO THE PLANS MUST BE IN WRITING AND MUST BE APPROVED BY THE PREPARER OF THESE PLANS.
7. THE CONTRACTOR SHALL MAINTAIN THE EXISTING ACCESSIBLE ROUTE CLEAR OR
PROVIDE AN ALTERNATE ACCESSIBLE ROUTE OF TRAVEL DURING DEMOLITION AND/OR CONSTRUCTION.
8. THE CONTRACTOR SHALL MAINTAIN THE EXISTING FIRE EXITS AND STAIRS CLEAR AND
USABLE OR PROVIDE ALTERNATE FIRE EXITS DURING DEMOLITION AND/OR CONSTRUCTION.
1. ALL ASBESTOS CEMENT PIPE TO BE REMOVED SHALL BE SNAPPED, ENCAPSULATED, AND DISPOSED OF PER LOCAL, STATE, AND FEDERAL REGULATIONS.
2. DOMESTIC WATER SERVICE AND FIRE PROTECTION SHALL BE MAINTAINED DURING CONSTRUCTION. PROVIDE BYPASS LINES DURING CONSTRUCTION INCLUDING TIE-IN.
COORDINATE ALL SHUT DOWNS OF WATER AND POWER WITH OWNER PRIOR TO CONSTRUCTION.
3. PURSUANT TO CALIFORNIA ASSEMBLY BILL 1953 ALL PIPE, FITTINGS, AND FIXTURES
INTENDED TO CONVEY OR DISPENSE WATER FOR HUMAN CONSUMPTION THROUGH DRINKING WATER OR COOKING SHALL BE "LEAD FREE" AS OF JANUARY 1, 2010.
IMPORTANT NOTICE
GENERAL NOTES TO CONTRACTOR
TITLE SHEET
C1.01
7/25/2025
FOR SITE PREPARATION, OVEREXCAVATION, FOUNDATION RECOMMENDATIONS, PAVEMENT,
SUBGRADE, AND GRADATION REQUIREMENTS SEE GEOTECHNICAL INVESTIGATION REPORT ENTITLED:
"GEOTECHNICAL ENGINEERING EVALUATION REPORT, SPACE SHUTTLE EXHIBIT AND EDUCATION BUILDING, 12400 COLUMBIA WAY, DOWNEY, CALIFORNIA" PREPARED BY: TWINING, INC.
4811 AIRPORT PLAZA DRIVE
SUITE 220
LONG BEACH, CA 90815
PROJECT NO: 210932.01
DATED: MARCH 11, 2022
DATED:JULY 16, 2025
GEOTECHNICAL INFORMATION
PURSUANT TO THE CALIFORNIA GOVERNMENT CODE
SECTION 4216, NO EXCAVATION PERMIT IS VALID
UNLESS DIG ALERT HAS BEEN CONTACTED AT LEAST
TWO (2) WORKING DAYS PRIOR TO THE
COMMENCEMENT OF EXCAVATION AND AN INQUIRY
IDENTIFICATION NUMBER HAS BEEN ISSUED.
INQUIRY ID#
DIG ALERT NOTICE
LEGAL DESCRIPTION
BASIS OF BEARINGS
BENCHMARK
C1.01 TITLE SHEET
C1.02 CIVIL NOTES
C2.01 SEWER UTILITY PLAN
C3.01 SEWER UTILITY DETAILS
CIVIL SHEET INDEX
ELEVATIONS SHOWN HEREON ARE RELATIVE TO THE NORTH AMERICAN VERTICAL DATUM OF 1988 (NAVD88) COUNTY OF LOS ANGELES PUBLIC WORKS 2005 ADJUSTMENT PER THE FOLLOWING COUNTY BENCHMARK:
LA COUNTY BM EY6105 ELEV.=96.219 FT. NAVD88 YEAR 2005
RDBM TAG IN S CB 5' W/O CBR @ SE COR IMPERIAL HIGHWAY & CLARK AVE
ANY USER OF ELEVATIONS AND/OR COORDINATES SHOWN HEREON FOR THE CONTROL OF CONSTRUCTION, SHALL VERIFY AT LEAST 3 POINTS SHOWN HEREON, FOR MATHEMATICAL CONSISTENCY PRIOR TO SUCH USE.
SUBTRACT 2.208 FEET TO ELEVATIONS HEREON TO ADJUST TO THE NGVD DATUM YEAR 1975 LA COUNTY ADJUSTMENT.
THE BEARING OF N89°51'30"E ALONG THE CENTERLINE OF IMPERIAL HIGHWAY AS SHOWN ON MAP OF RECORD OF SURVEY RS BOOK 229 PG 90 AND IS THE BASIS OF BEARINGS FOR THIS SURVEY.
CURRENT LEGAL DESCRIPTION OF SUBJECT PROPERTY HAS NOT BEEN SUPPLIED TO SURVEYOR. SUBJECT PROPERTY LINES HAVE BEEN DETERMINED BY LA COUNTY ASSESSOR MAP 6256-004; APN OF SUBJECT PROPERTY IS 6256-004-910. PROPERTY LINES ARE SUBJECT TO CHANGE.
1. PIPE SHALL BE CLASS 52 CEMENT-LINED DIP WITH INTEGRAL BELL AND SPIGOT (PUSH ON) JOINTS WITH ELASTOMERIC RUBBER GASKETS IN ACCORDANCE WITH AWWA C104, C111, AND C151, AND SHALL BE MADE IN THE USA.
2. FITTINGS SHALL BE CLASS 52 CEMENT LINED DUCTILE IRON MJ OR MJXFL (SEE PLANS) IN ACCORDANCE WITH AWWA C104, C110, C111, AND C153, AND SHALL BE MADE IN THE USA.
3. JOINT RESTRAINTS SHALL BE EBBA IRON MEGA LUGS OR PRE-APPROVED EQUAL AND SHALL BE MADE IN THE USA. RESTRAINTS SHALL HAVE POLYESTER-BASED COATING ON THE
GLAND AND TWO COATS OF XYLAN COATING ON THE WEDGE ASSEMBLIES OR OTHER SIMILAR PRE-APPROVED COATING. ALL RESTRAINTS SHALL HAVE IDENTIFICATION NUMBER CONSISTING OF THE YEAR, DAY, PLANT AND SHIFT NUMBER CAST INTO EACH GLAND BODY.
JOINT RESTRAINTS SHALL BE USED FOR ALL FITTINGS AND VALVES UNLESS OTHERWISE SHOWN ON PLANS AND APPROVED IN ADVANCE BY DOWNEY PERSONNEL.
4. THRUST/ANCHOR BLOCKS SHALL BE USED FOR ALL FITTINGS AND VALVES UNLESS OTHERWISE SHOWN ON THE PLANS AND APPROVED IN ADVANCE BY DOWNEY PERSONNEL.
POTABLE WATER - MATERIALS SPECIFICATIONS
5. GATE VALVES SHALL BE RESILIENT SEATED, CONFORMING TO AWWA C509, AND BE DESIGNED FOR 200 PSI WORKING PRESSURE, NON-RISING STEM, MECHANICAL JOINT OR
MECHANICAL JOINT BY FLANGE ENDS, WITH DUCTILE IRON BODY, OPERATING NUT, BONNET, AND SEAL PLATE, DUCTILE IRON GATE AND 316 STAINLESS STEEL BONNET AND SEAL PLATE NUTS AND BOLTS. MUELLER 2360 SERIES, CLOW F-6100 SERIES, OR US PIPE METROSEAL 250.
VALVES INSTALLED AT INTERSECTIONS SHALL BE MJXFL WITH FLANGE ABUTTING THE FITTING UNLESS OTHERWISE INDICATED.
6. TAPPING VALVES SHALL CONFORM TO THE REQUIREMENTS FOR GATE VALVES.
VALVE ENDS SHALL BE FLANGED, AND SHALL FIT STANDARD TAPPING MACHINES. SEAT RINGS SHALL BE OVERSIZED TO PERMIT THE USE OF FULL-SIZE CUTTERS. MUELLER 2360 SERIES, CLOW F-6100 SERIES, OR US PIPE METROSEAL 250.
7. ALL BURIED VALVES SHALL BE PROVIDED WITH RISERS, SLIP-TYPE CAST IRON VALVE BOXES, AND COVERS PER CITY SPECIFICATIONS AND DWG. NO. 5-W. PROVIDE OPERATING EXTENSION STEMS (RISERS) TO BRING OPERATING NUT TO A POINT 18-INCHES TO 30-INCHES BELOW SURFACE OF GROUND AND/OR BOX COVER.
8. BURIED NUTS, BOLTS, AND WASHERS FOR FLANGED FITTINGS SHALL BE TYPE 304 OR 316 STAINLESS STEEL.
9. TAPPING SLEEVES SHALL BE DUCTILE IRON WITH BUNA-N RUBBER WITH A WIDE CROSS-SECTION, MECHANICAL JOINT BY FLANGE (CLOW, MUELLER, OR US PIPE). THE
MECHANICAL JOINT PORTION OF THE TAPPING SLEEVES SHALL BE INSTALLED WITH CORTEN-STEEL T-BOLTS AND NUTS COATED WITH TRIPAC 2000 BLUE COAT SYSTEM.
10. ALL BURIED DUCTILE IRON PIPING, FITTINGS, VALVES, APPURTENANCES, AND COPPER PIPING SHALL BE CORROSION PROTECTED WITH TWO WRAPS OF MIN. 8-MIL POLYETHYLENE
ENCASEMENT (FLAT SHEETS FOR FITTING, VALVES, AND APPURTENANCES AND TUBES FOR PIPING) PER AWWA C105, INSTALLATION METHOD A.
11. 1-INCH AND SMALLER POTABLE WATER METERS SHALL BE LOW LEAD: SENSUS SRII
ENVIROBRASS II POSITIVE DISPLACEMENT WITH AMR/AMI REGISTER AND TOUCHPAD WITH MXU ASSEMBLY REGISTERING IN 1 CUBIC FOOT. TOUCHPAD/MXU ASSEMBLY TO BE MOUNTED TO THE STREET SIDE CORNER OF THE METER BOX LID.
12. 1-1/2-INCH AND 2-INCH POTABLE WATER METERS SHALL BE: SENSUS OMNI T2 TURBINE
WITH STRAINERS AND AMR/AMI REGISTER AND TOUCHPAD WITH MXU ASSEMBLY REGISTERING IN 1 CUBIC FOOT. TOUCHPAD/MXU ASSEMBLY TO BE MOUNTED TO THE STREET SIDE CORNER OF THE METER BOX LID.
13. 3-INCH THROUGH 8-INCH POTABLE WATER NON-IRRIGATION METERS SHALL BE SENSUS OMNI C2 COMPOUND WITH SENSUS AWWA-TYPE STRAINERS WITH DRAIN PLUGS
AND STAINLESS STEEL SCREENS, AND AMR/AMI REGISTER AND TOUCHPAD WITH MXU ASSEMBLY AND 1 CUBIC FOOT REGISTRATION. TOUCHPAD/MXU ASSEMBLY TO BE MOUNTED TO THE MIDDLE CORNER ON ONE SIDE OF THE TWO-PIECE METER BOX LID.
14. 3-INCH THROUGH 6-INCH POTABLE WATER IRRIGATION METERS SHALL BE SENSUS OMNI T2 TURBINE WITH SENSUS AWWA-TYPE STRAINERS WITH DRAIN PLUGS AND STAINLESS STEEL SCREENS, AND AMR/AMI REGISTERS AND TOUCHPAD WITH MXU ASSEMBLY AND 1 CUBIC FOOT REGISTRATION. TOUCHPAD/MXU ASSEMBLY TO BE MOUNTED TO THE MIDDLE CORNER ON ONE SIDE OF THE TWO-PIECE METER BOX LID.
15. 3-INCH AND LARGER METERS SHALL BE INSTALLED WITH A C509 RESILIENT WEDGE
GATE VALVE, INSTALLED IMMEDIATELY DOWNSTREAM OF THE METER, ACCESSIBLE AND REMOVABLE THROUGH THE WATER METER BOX LID.
16. 1-INCH AND SMALLER (12”X20”X12”) POTABLE WATER METER BOXES SHALL BE ARMORCAST ROTOCAST MODEL P6000485 WITH ONE-PIECE POLYMER CONCRETE (RPM) LID (MODEL A6000484-H7) MARKED “WATER”, OR APPROVED EQUAL. USE ARMORCAST TRAFFIC-RATED (20,000 LBS) ONE-PIECE LID (MODEL A6000484T-H7) MARKED “WATER” FOR AREAS WHERE METER BOXES WILL BE SUBJECT TO TRAFFIC LOADS.
17. 1-1/2-INCH AND 2-INCH (17”X30”X12”) POTABLE WATER METER BOXES SHALL BE ARMORCAST ROTOCAST MODEL P6001534X12 WITH TWO-PIECE POLYMER CONCRETE (RPM) LIDS (MODELS A6001643DZ-H7 & A6000482) MARKED “WATER”, OR APPROVED EQUAL. USE ARMORCAST POLYMER CONCRETE (RPM) TRAFFIC-RATED (20,000 LBS) TWO-PIECE LIDS (MODELS A60001947DZ-H7 & A6000482T) MARKED “WATER” FOR AREAS WHERE METER BOXES WILL BE SUBJECT TO TRAFFIC LOADS.
18. 3-INCH (30”WX48”LX48”H MIN.) POTABLE WATER METER BOXES SHALL BE ARMORCAST POLYMER CONCRETE (RPM) MODEL A6001430PCX48 WITH THREE-PIECE LIDS (MODELS A6001470 & A6001470DZ-H7) MARKED “WATER” WITH DROP-IN READ LID (MODEL A6000482).
19. 4-INCH (36”WX60”LX48”H MIN.) AND LARGER POTABLE WATER METER BOXES SHALL BE ARMORCAST POLYMER CONCRETE (RPM) MODEL A6001436APCX48 (4-INCH) WITH THREE-PIECE LIDS (MODELS A6001457 & A6001457DZ-H7) MARKED “WATER” WITH DROP-IN READ LID (MODEL A6000482).
20. SIZE OF BOX FOR LARGER METERS DEPENDENT UPON SIZE OF METER AND APPURTENANCES WITHIN THE BOX PER CITY APPROVAL.
21. WHERE REQUIRED, DOMESTIC WATER SERVICES SHALL BE INSTALLED WITH A
REDUCED PRESSURE PRINCIPLE (RP) DEVICE PLACED JUST DOWNSTREAM OF THE METER OUTSIDE OF PUBLIC RIGHT-OF-WAY PER LA COUNTY DPH REQUIREMENTS. SEE LIST OF LA COUNTY DPH APPROVE BACKFLOW PREVENTION DEVICES.
HTTPS://FCCCHR.USC.EDU/_DOWNLOADS/LIST/LIST.PDF
22. 1-INCH THROUGH 2-INCH REDUCED PRESSURE PRINCIPLE (RP) DEVICES SHALL BE FEBCO MODEL LF825YA.
23. 1-INCH AND 1-1/2-INCH REDUCED PRESSURE PRINCIPLE (RP) DEVICES SHALL BE INSTALLED IN A DARK GREEN, LIFT-OFF “BPDI” GUARDSHACK (MODEL GS-1) (10”WX22”LX24”H) WITH ROUNDED TOP AND CONCRETE PAD AT THE BASE.
24. 2-INCH REDUCED PRESSURE PRINCIPLE (RP) DEVICES SHALL BE INSTALLED IN A DARK GREEN, LIFT-OFF “BPDI” GUARDSHACK (MODEL GS-2) (10”WX30”LX24”H) WITH ROUNDED TOP AND CONCRETE PAD AT THE BASE.
25. 3-INCH AND LARGER REDUCED PRESSURE PRINCIPLE (RP) DEVICES SHALL BE WILKINS MODEL 475.
26. ALL ABOVE GROUND PORTIONS OF THE RP DEVICE (3-INCH AND LARGER) SHALL BE
PAINTED WITH ONE PRIME COAT AND TWO FINISH COATS IN THE FIELD, AFTER THE RP DEVICE HAS BEEN INSTALLED. THE SECOND FINISH COAT SHALL BE APPLIED JUST PRIOR TO THE FINAL INSPECTION. PRIMER SHALL BE STANDARD WHITE (WH-1) AMERON AMERLOCK 2 VOC HIGH-SOLIDS EPOXY COATING. FINISH COATS SHALL BE MEDIUM GREEN (5506) AMERON PSX 700 ENGINEERED SILOXANE COATING.
27. FIRE SERVICES SHALL BE INSTALLED WITH A DOUBLE CHECK DETECTOR ASSEMBLY PLACED ON PRIVATE PROPERTY OUTSIDE OF THE PUBLIC RIGHT-OF-WAY. DOUBLE CHECK
DETECTOR ASSEMBLIES SHALL BE EQUIPPED WITH SENSUS IPERL RADIO-READ BY-PASS METERS REGISTERING IN 1 CUBIC FEET, TOUCHPAD MXU, AND AMR MOUNTING BRACKET.
ASSEMBLIES SHALL BE WILKINS 450DA OR CITY APPROVED EQUAL. SEE LIST OF LA COUNTY DPH APPROVED BACKFLOW PREVENTION DEVICES.
HTTPS://FCCCHR.USC.EDU/_DOWNLOADS/LIST/LIST.PDF
28. ALL ABOVE GROUND PORTIONS OF THE DCDA SHALL BE PAINTED WITH ONE PRIME COAT AND TWO FINISH COATS IN THE FIELD, AFTER THE DCDA HAS BEEN INSTALLED. THE SECOND FINISH COAT SHALL BE APPLIED JUST PRIOR TO THE FINAL INSPECTION. PRIMER SHALL BE STANDARD WHITE (WH-1) AMERON AMERLOCK 2 VOC HIGH-SOLIDS EPOXY COATING. FINISH COATS SHALL BE SAFETY RED (RD-2) AMERON PSX 700 ENGINEERED SILOXANE COATING.
29. FIRE HYDRANTS IN RESIDENTIAL AREAS SHALL BE JONES MODEL J-3700-R WITH FLUTED SPOOL, 3/4-INCH DIAMETER HOLES IN A SIX-HOLE PATTERN WITH A 9-3/8 INCH BOLT CIRCLE.
30. FIRE HYDRANTS IN COMMERCIAL AND INDUSTRIAL AREAS SHALL BE JONES MODEL J-3775-R WITH FLUTED SPOOL, 3/4-INCH DIAMETER HOLES IN A SIX-HOLE PATTERN WITH A 9-3/8 INCH BOLT CIRCLE.
31. FIRE HYDRANTS SHALL BE INSTALLED WITH AN MJXFL TEE WITH THRUST BLOCK (UNLESS OTHERWISE SHOWN ON PLANS AS A HOT TAP), 6-INCH C509 MJXFL RESILIENT WEDGE GATE VALVE AND BOX, MJXFL 90 DEGREE ELBOW, AND FLANGED CLASS 53
CEMENT-LINED DIP SPOOLS (NO HYDRANT BURIES) WITH LENGTH ORDERED PER FIELD CONDITIONS TO MEET 4-INCH REQUIREMENT NOTED BELOW. RISER FLANGES TO MATCH 90-DEGREE ELBOW FLANGE AND FLUTED SPOOL BOLT PATTERN. TYPE 316 STAINLESS STEEL BREAK-AWAY BOLTS AT BASE OF HYDRANT FILLED WITH SILICONE SEALANT.
DISTANCE FROM FINISH GRADE TO BOTTOM OF FLANGE AT BASE OF FIRE HYDRANT SHALL BE 4-INCHES PER STANDARD DRAWING FOR INDUSTRIAL/COMMERCIAL FIRE HYDRANT.
32. ALL ABOVE GROUND PORTIONS OF THE FIRE HYDRANT AND RISER SHALL BE PAINTED
WITH ONE PRIME COAT AND TWO FINISH COATS IN THE FIELD, AFTER THE FIRE HYDRANT HAS BEEN INSTALLED. THE SECOND FINISH COAT SHALL BE APPLIED JUST PRIOR TO THE FINAL INSPECTION. PRIMER SHALL BE STANDARD WHITE (WH-1) AMERON AMERLOCK 2 VOC HIGH-SOLIDS EPOXY COATING. FINISH COATS SHALL BE SAFETY YELLOW (YE-3) AMERON PSX 700 ENGINEERED SILOXANE COATING. ALTERNATIVELY, JAMES JONES MANUFACTURER-APPLIED Z-36 PAINT SCHEDULE CAN BE USED.
33. BLUE REFLECTIVE PAVEMENT MARKERS
ONE (1) TWO-WAY BLUE REFLECTIVE FIRE HYDRANT RAISED PAVEMENT MARKER SHALL BE
INSTALLED ADJACENT TO EACH HYDRANT AND EXISTING BLUE REFLECTIVE PAVEMENT MARKER REMOVED (WHEN PRESENT). REFLECTIVE MARKERS, ADHESIVES, AND METHOD OF INSTALLATION SHALL CONFORM TO THE FOLLOWING CALTRANS STANDARD SPECIFICATION:
SECTION 85-1.02C RETROREFLECTIVE PAVEMENT MARKERS
SECTION 85-1.02D HOT MELT BITUMINOUS ADHESIVE
SECTION 85-1.02E EPOXY ADHESIVE
SECTION 85-1.03B HOT MELT BITUMINOUS ADHESIVE
SECTION 85-1.03C EPOXY ADHESIVE
LOCATION
BLUE REFLECTIVE PAVEMENT MARKERS SHALL BE PLACED ON THE SIDE OF THE STREET NEAREST THE FIRE HYDRANT AS PROVIDED BELOW:
1. TWO-WAY STREETS OR ROADS: PLACE MARKERS 12-INCHES FROM EDGE OF PAINTED CENTERLINE ON THE SIDE NEAREST THE FIRE HYDRANT. IF THE STREET HAS NO CENTERLINE, PLACE THE MARKER 12-INCHES FROM THE
APPROXIMATE CENTER OF THE ROADWAY ON THE SIDE NEAREST THE HYDRANT.
2. STREETS WITH LEFT TURN LANE AT INTERSECTION: PLACE MARKERS 12-INCHES FROM THE EDGE OF PAINTED WHITE CHANNELIZING LINE ON THE SIDE NEAREST THE HYDRANT.
3. STREET WITH CONTINUOUS TWO-WAY LEFT TURN LANE: PLACE MARKERS 12-INCHES FROM THE EDGE OF THE PAINTED YELLOW BARRIER LINE ON THE SIDE NEAREST THE FIRE HYDRANT.
4. STREETS WITH RAISED MEDIANS: PLACE MARKER 12-INCHES FROM EDGE OF GUTTER.
34. TRACEABLE POTABLE WATER IDENTIFICATION TAPE SHALL BE VIRGIN LOW-DENSITY POLYETHYLENE, MIN. THICKNESS OF 5 MILS, OVERALL WIDTH OF 6-IN (6-IN DIAMETER PIPE AND SMALLER). TAPE SHALL BE BLUE WITH MIN. 2-IN HIGH WHITE LETTERING SPECIFYING:
“CAUTION: POTABLE WATER LINE BURIED BELOW”. T. CHRISTY ENTERPRISES, TERRA TAPE (GRIFFOLYN CO. DIVISION OF REEF INDUSTRIES) OR APPROVED EQUAL. NOTE: FOR
CITY-OWNED FIRE SERVICE LATERALS AND PRIVATELY OWNED FIRE WATER MAIN, THE LETTERING SHALL SPECIFY: “CAUTION: FIRE LINE BURIED BELOW”.
35. SERVICE LINES SHALL BE TYPE K SOFT COPPER CONFORMING TO ASTM B88.
36. SERVICE SADDLES SHALL HAVE BRASS BODIES CONFORMING TO NSF 61 AND ASTM B-62 AND/OR ASTM B-584 WITH DOUBLE FLAT BRONZE STRAPS AND BUNA-N GASKETS.
ONE-INCH TAPS WITH CC THREADS, FORD 202B SERIES, MUELLER BR2B SERIES, OR JONES J-979 SERIES. TWO-INCH TAPS WITH FEMALE IRON PIPE THREADS, FORD 202B SERIES, MUELLER BR2B SERIES, OR JONES J-979 SERIES.
37. CORPORATION STOPS SHALL BE BALL VALVE TYPE, BRASS CONFORMING TO AWWA STANDARD C800 (UNS NO. C89833) WHERE IN CONTACT WITH WATER AND AWWA STANDARD C800 (ASTM B-62 AND ASTM B-584, UNS NO. C83600) WHERE NOT IN CONTACT WITH WATER.
ONE-INCH WITH CC THREAD INLET BY COMPRESSION OUTLET, FORD MODEL FB1000-4-Q-NL, MUELLER MODEL H15008N, OR JONES MODEL E1937SG. TWO-INCH WITH MALE IRON PIPE THREAD INLET BY COMPRESSION OUTLET, FORD MODEL FB1100-7-Q-NL, MUELLER MODEL B25028N, OR JONES MODEL E1935SG.
38. CURB STOPS SHALL BE BRASS CONFORMING TO AWWA STANDARD C800 (UNS NO.
C89833) WHERE IN CONTACT WITH WATER AND AWWA STANDARD C800 (ASTM B-62 AND ASTM B-584, UNS NO. C83600) WHERE NOT IN CONTACT WITH WATER. ONE-INCH SHALL BE
FULL-PORT STRAIGHT BALL VALVE WITH FEMALE IRON PIPE THREAD INLET AND FEMALE IRON PIPE OUTLET WITH A LOCKWING TEE HEAD, FORD MODEL B11-444WR-NL, MUELLER MODEL B20200N, OR JONES MODEL E1900W. TWO-INCH SHALL BE FULL PORT ANGLE BALL VALVES
WITH COMPRESSION INLET BY METER FLANGE OUTLET WITH LOCKWING, FORD MODEL BFA43-777WR-Q-NL, MUELLER MODEL B24276N, OR JONES MODEL E1975WSG.
39. COMBINATION AIR RELEASE AND VACUUM VALVES SHALL BE OF THE SINGLE BODY,
DOUBLE ORIFICE TYPE WITH CAST IRON BODY, COVER, AND LEVER FRAME CONFORMING TO ASTM A126 GR. B, STAINLESS STEEL FLOAT CONFORMING TO ASTM A240, BUNA-N NEEDLE AND SEAT, BRONZE PLUG CONFORMING TO ASTM B124, 316 STAINLESS STEEL TRIM, AND DELRIN/CAST IRON LEVER FRAME CONFORMING WITH ASTM D2133/ASTM A126 GR. B.
ONE-INCH THROUGH FOUR-INCH WITH EQUAL SIZE INLET AND OUTLET FEMALE PIPE THREADS, 6-INCH AND 8-INCH WITH 125 LB. FLANGED INLET AND OUTLET.
SIZE
(INCHES) APCO MODEL
NUMBER CRISPIN MODEL SERIES VAL-MATIC MODEL NUMBER
2 145C UL 202C.2
3 147C UL 203C.2
4 149C UL 204C.2
6 150C UL 206C
8 151C UL 208C
40. COMBINATION AIR RELEASE AND VACUUM VALVE COVERS SHALL BE LOW LINEAR
DENSITY POLYETHYLENE WITH UV INHIBITORS, SANDSTONE COLOR, ARMORCAST MODEL P6002001 OR P6002002 SIZED TO FIT VALVE.
41. A MINIMUM OF 8-INCHES OF PEA GRAVEL SHALL BE INSTALLED AT THE BOTTOM OF ALL METER BOXES.
42. NOTE: ALL MATERIALS TO BE USED ON THE PROJECT SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR.
43. IN ADDITION TO THE REQUIRED USE OF POLYETHYLENE ENCASEMENT AS PROVIDED
PREVIOUSLY, THE FOLLOWING CORROSION PROTECTION MEASURES SHALL BE USED AS PROVIDED HEREIN: USE OF DIELECTRIC COUPLINGS/GASKETS WHERE DISSIMILAR METALS
JOIN, USE OF FULL CIRCLE BRASS SERVICE SADDLES TO ELIMINATE DIRECT CONNECTION OF COPPER TO DUCTILE IRON PIPE, AND USE OF STAINLESS STEEL HARDWARE.
Job Number
Date Published
Checked By
Scale
Revision DateARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
3055401
RR
AS SHOWN
CITY OF DOWNEY PUBLIC WORKS - OFFSITE WATER UTILITY PLANS
SPACE SHUTTLE EXHIBIT AND EDUCATION BUILDING
COLUMBIA WAY
DOWNEY, CA 90242
CITY OF DOWNEY
Developed for
100% CONSTRUCTION DOCUMENTS 07/25/2025
CIVIL NOTES
C1.02
7/25/2025
1. THE INTENT OF THE DEMOLITION PLAN IS TO DESCRIBE IN GENERAL THE DEMOLITION AREAS AFFECTED BY THE PROJECT CONSTRUCTION. IT IS NOT INTENDED AS A DETAILED DESCRIPTION OF EXISTING ITEMS OR ELEMENTS TO BE REMOVED. THE
CONTRACTOR SHALL VISIT THE SITE AND REVIEW ANY AVAILABLE RECORD
DOCUMENTS TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS AND SHOULD
INCLUDE THE REMOVAL OF ALL ITEMS NECESSARY FOR THE PROPER EXECUTION AND COMPLETION OF THE WORK. THE CONTRACT DOCUMENTS ARE COMPLEMENTARY, AND
WHAT IS REQUIRED BY ONE SHALL BE BINDING AS IF REQUIRED BY ALL TO THE EXTENT
THAT IT IS REASONABLY INFERABLE FROM THEM AS BEING NECESSARY TO PRODUCE THE INTENDED RESULTS.
2. REMOVE EXISTING BUILDINGS, FOUNDATIONS AND SERVICE UTILITIES AS INDICATED ON PLANS. CAP ALL UTILITIES AT APPROPRIATE POINTS. ALL EXISTING ELECTRICAL /
TELEPHONE / CATV UTILITIES SHALL BE REMOVED AS INDICATED OR BACK TO THE POINT WHERE THE SPECIFIC UTILITY SYSTEM ENTERS THE WORK AREA. COORDINATE DEMOLITION OF ALL UTILITIES WITH THE OWNER. ALL UTILITIES CONNECTED TO
EXISTING BUILDINGS TO REMAIN SHALL CONTINUE TO BE OPERATIONAL DURING THE DEMOLITION PROCESS. DOMESTIC AND FIRE SERVICE WATER AND NATURAL GAS SHALL
BE REMOVED TO A POINT OUTSIDE THE PERIMETER OF PROPOSED NEW CONSTRUCTION TO EXISTING VALVES OR SIMILAR SHUT-OFF DEVICES. IF A SHUT-OFF
DEVICE IS NOT REASONABLY ADJACENT TO THE PERIMETER OF THE PROPOSED NEW CONSTRUCTION, PROVIDE A SHUT-OFF DEVICE IN BELOW-GRADE YARD BOX. CONFIRM LOCATION OF NEW DEVICES WITH OWNER PRIOR TO INSTALLATION. SANITARY SEWER
AND STORM DRAINAGE SHALL BE CAPPED TO A POINT OUTSIDE THE PERIMETER OF THE PROPOSED NEW CONSTRUCTION. OTHER UTILITIES NOT SPECIFICALLY IDENTIFIED
IN THESE DOCUMENTS AND NOT ANTICIPATED FOR REUSE SHALL BE REMOVED IN ENTIRETY.
3. FOR ALL EXISTING MATERIALS THAT CAN BE SALVAGED, OWNER HAS FIRST RIGHT OF
REFUSAL FOR REMOVED ITEMS THAT MAY HAVE RESIDUAL COMMERCIAL OR HISTORIC
VALUE INCLUDING HARDWARE, GLASS, CORNER STONES, TIME CAPSULES, LIGHT
STANDARDS, SIGNS, FENCING, BENCHES, WATER FOUNTAINS, TRASH CONTAINERS, ETC. SHALL REMAIN AS PROPERTY OF THE OWNER. ALL ITEMS TO BE SALVAGED FOR REUSE/REINSTALLATION MUST MEET CURRENT CODE REQUIREMENTS. COORDINATE
ITEMS TO BE RETAINED WITH OWNER AND REMOVE FROM CONSTRUCTION SITE TO A LOCATION APPROVED BY OWNER. REMOVED MATERIALS, NOT INDICATED OR DIRECTED
TO BE SALVAGED FOR THE OWNER'S BENEFIT ARE DEBRIS AND BECOME THE CONTRACTOR'S PROPERTY UPON REMOVAL.
4. THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITY PIPES OR
STRUCTURES SHOWN ON THESE PLANS ARE OBTAINED BY SEARCH OF THE AVAILABLE RECORDS AND FIELD SURVEYS. THE CONTRACTOR SHALL CONTACT UNDERGROUND
SERVICE ALERT, UTILITY COMPANIES, AND/OR FIELD VERIFY AND LOCATE ALL UTILITIES BEFORE PROCEEDING WITH WORK. THE CONTRACTOR IS ALSO REQUIRED TO TAKE DUE
PRECAUTIONARY MEASURES TO PROTECT THE UTILITY LINES SHOWN AND ANY OTHER LINES NOT OF RECORD OR NOT SHOWN ON THESE PLANS. NOTIFY THE ENGINEER IF
ADDITIONAL UTILITIES ARE LOCATED OR IF CONFLICTS ARE FOUND WITH EXISTING CONDITIONS.
5. ALL TREES TO BE REMOVED SHALL BE MARKED BY CONTRACTOR AND APPROVED FOR
REMOVAL BY THE OWNER OR OWNER'S REPRESENTATIVE PRIOR TO REMOVING OR CUTTING TREE(S). EXISTING ROOTS SHALL BE GRINDED TO A DEPTH OF APPROXIMATELY 3-FEET. USE CAUTION WHILE GRINDING WHEN EXISTING UTILITIES ARE IN CLOSE PROXIMITY TO TREES. ALL TREES TO REMAIN WITHIN THE LIMIT OF WORK SHALL BE PROTECTED AND MAINTAINED PER SPECIFICATIONS AND DETAILS.
6. SAWCUT EXISTING CONCRETE AND ASPHALT TO AN EXISTING CONTROL JOINT WHERE POSSIBLE, AT MINIMUM TO A NEAT-STRAIGHT LINE. ALL DEBRIS SHALL BE HAULED OFFSITE TO A LEGAL DUMPING SITE OR SALVAGED FOR REUSE ON PROJECT AS NOTED.
7. WORK WITHIN CITY, COUNTY, OR STATE RIGHT-OF-WAY REQUIRES A SEPARATE
ENCROACHMENT PERMIT WHICH THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING PRIOR TO STARTING WORK WITHIN RIGHT-OF-WAY.
8. CONTRACTOR TO COORDINATE UTILITY DEMOLITION WITH DRAINAGE AND UTILITY WORK SHOWN IN THIS PLAN SET. ALL UTILITY SHUTDOWNS SHALL BE COORDINATED PER PROJECT SPECIFICATIONS.
9. EXISTING DRY UTILITIES SHOWN FOR DEMOLITION ARE SHOWN FOR COORDINATION ONLY. REFER TO OTHER DISCIPLINES FOR LIMITS AND DETAILS OF DEMOLITION.
10. THE CONTRACTOR SHALL RECYCLE CONSTRUCTION DEBRIS, ASPHALT, AND CONCRETE GENERATED FROM REMOVALS REQUIRED TO CONSTRUCT THE PROJECT. THE
CONTRACTOR IS OBLIGATED, UNDER THIS CONTRACT, TO RECYCLE THE WASTE MATERIAL THROUGH AN APPROVED RECYCLING PLANT.
11. A LIST OF FACILITIES THAT ACCEPT CONSTRUCTION & DEMOLITION DEBRIS CAN BE FOUND ON THE CALRECYCLE WEBSITE AT:
HTTPS://WWW.CALRECYCLE.CA.GOV/CONDEMO
12. CONTRACTOR IS RESPONSIBLE FOR PROTECTING EXISTING BUILDING FINISHES DURING DEMOLITION. ANY FINISH THAT IS DAMAGED DURING DEMOLITION SHALL BE REPAIRED OR REPLACED IN-KIND OR BETTER.
DEMOLITION NOTES
x xxxxxxx98979797979797979898989897979797969798989797
9696969796989896979898W W W W
GGGGGGGGGGGG21"SSSSco coSS10"SS12"SS81"SDW
WWWWWWWWWWWW12"DW12"DWW W12"DW
6"FW
SDSDco
SDE
EEEEESDSDSDEEE E E EEEE E
EEEEEE2"GG GSSSSSSSSSSSS
SSSSSSSS (E) 15" (ABAND)
CO
M
3"DWCOLUMBIA WAY1.5"DW
CO
CO
CO MS
97.50 FFE
97.50 FFE
CO
CO
01 -COLUMBIA WAYCONGRESSMAN STEVE HORN WAY
80.00'
10.00'EX. EASEMENTCLR/WR/W9797GGGGGGWWWWWW WWFW FW
WWSDSDSDSDSSSSSSSSSD
M
2CLR/WR/W80.00'
(E)12" CML DIP WATER MAIN
PER DWG NO. 3-42-30W
(E)21" VCP TRUNK SEWER
PER DWG NO. 3-38-02
(E)81" RCP STORM DRAIN
PER DWG NO. 364-3103-D2.2
7B
5 6
1 34
CONSTRUCT 2" PORTABLE WATER SERVICE PER CITY OF DOWNEY DEPARTMENT OF PUBLIC WORKS UTILITIES DIVISION 2-W. SEE DETAIL 01. SHEET C03.01.
PUBLIC WATER CONSTRUCTION NOTES:
1 CONSTRUCT 2" REDUCED PRESSURE PRINCIPLE ASSEMBLY PER DETAIL 02, SHEET C3.012 CONSTRUCT THRUST BLOCK PER CITY OF DOWNEY STD. PLAN 7-W PER DETAIL 03 ON SHEET C3.01.3
4 CONSTRUCT 12" X 8" MJ X FL TAPPING SLEEVE, 8" FL C509 GATE VALVE, AND 8" MJ X FL ADAPTER PER CITY OF DOWNEY STD. PLAN 4-W PER DETAIL 04, SHEET C3.01.
TRENCHING LIMITS PER CITY OF DOWNEY DEPARTMENT OF PUBLIC WORKS UTILITIES DIVISION DWG. NO. 12-W. SEE DETAILS 05 SHEET C3.01.
1. UTILITIES TO CROSS OVER OR UNDER OTHER UTILITIES TO MAINTAIN 12" MINIMUM CLEARANCE AT UTILITY CROSSINGS, UNLESS NOTED OTHERWISE. SANITARY SEWER TO CROSS UNDER POTABLE WATER.
2. CONTRACTOR SHALL VERIFY SIZE AND LOCATION (HORIZONTAL AND VERTICAL) OF
EXISTING CROSSING AND JOINING UTILITIES PRIOR TO CONSTRUCTION AND IMMEDIATELY NOTIFY THE ENGINEER OF ANY CONFLICT.
3. CONTRACTOR SHALL CONSTRUCT GRAVITY UTILITIES (SEWER AND STORM DRAIN) BEFORE OTHER UTILITIES. CONSTRUCTION OF THESE GRAVITY UTILITIES TO START FROM THE DOWNSTREAM ENDS.
4. EXISTING UTILITIES ARE COMPILED BASED ON PREVIOUS BASE FILES, FIELD SURVEY AND FIELD VERIFICATION. POTHOLING IS RECOMMENDED TO VERIFY ANY AND ALL UTILITIES KNOWN OR UNKNOWN WHICH MAY BE IN CONFLICT WITH PROPOSED CONSTRUCTION.
5. PRIOR TO THE REMOVAL OF ANY WET OR DRY UTILITY LINES, THE CONTRACTOR SHALL
CONFIRM WITH OWNER REPRESENTATIVE WHETHER THESE UTILITY LINES ARE STILL ACTIVE OR NOT. IMMEDIATELY NOTIFY THE ENGINEER OF ANY CONFLICT.
6. CONTRACTOR TO ADJUST TO FINISH GRADE ALL EXISTING UTILITY BOXES, SEWER
CLEANOUT COVERS, PULL BOXES AND VALVE COVERS NOT SPECIFICALLY SHOWN WITHIN THE LIMITS OF WORK.
CONSTRUCTION NOTES:
REMOVE (E) AC PAVEMENT, SEE DEMOLITION NOTE 10 SHEET C1.01.B
DEMOLITION NOTES
-SEE DEMOLITION NOTES, SHEET C1.02.
5 CONSTRUCT 8" CLASS 52 CML DUCTILE IRON PIPING INCLUDING DISINFECTION TESTING PER AWWA STANDARDS C651-C699 INCLUDING BACTERIOLOGICAL SAMPLES AND LAB TESTING. PIPE TRENCHING, BEDDING AND PAVING PER CITY STANDARDS 12-W. ALL
SIDEWALK, CURB & GUTTER DAMAGED DURING THE COURSE OF TRENCHING SHALL BE REPLACED JOINT-TO-JOINT TO MATCH EXISTING. SEE DETAILS 05 AND 06, SHEET C3.01. 6 INSTALL 8" WILKINS DOUBLE CHECK DETECTOR ASSEMBLY (DCDA); MODEL 450DA STANDARD ORIENTATION WITH SENSUS SRII BY-PASS METER, SENSUS 520M MXU, AND AMR MOUNTING BRACKET (12" FROM FINISHED GRADE TO BOTTOM OF HANDS WHEELS) PERDETAIL ON SHEET C3.01; SCREEN BACKFLOW DEVICE WITH LANDSCAPING (SEE LANDSCAPE PLANS FOR DETAIL). SEE DETAIL 07, SHEET C3.01. 7 FOR CONTINUATION SEE ON-SITE PLANS.
Job Number
Date Published
Checked By
Scale
Revision DateARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
3055401
RR
AS SHOWN
CITY OF DOWNEY PUBLIC WORKS - OFFSITE WATER UTILITY PLANS
SPACE SHUTTLE EXHIBIT AND EDUCATION BUILDING
COLUMBIA WAY
DOWNEY, CA 90242
CITY OF DOWNEY
Developed for
100% CONSTRUCTION DOCUMENTS 07/25/2025
N
3015 600
1" = 30'PLAN VIEW
N
105 200
1" = 10'01ENLARGEMENT
WATER UTILITY PLAN
C2.01
7/25/2025
Job Number
Date Published
Checked By
Scale
Revision DateARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
3055401
RR
AS SHOWN
CITY OF DOWNEY PUBLIC WORKS - OFFSITE WATER UTILITY PLANS
SPACE SHUTTLE EXHIBIT AND EDUCATION BUILDING
COLUMBIA WAY
DOWNEY, CA 90242
CITY OF DOWNEY
Developed for
100% CONSTRUCTION DOCUMENTS 07/25/2025
CONSTRUCTION ITEMS / MATERIALS LIST
8 1
2 4
5 6 7
1 2
3 4
5 6
7 8
3 C3.01
WATER UTILITY
DETAILS
Z
U
R
N
WI
L
K
I
N
S
DEAD END
TYPICAL SECTION
CROSS
ELEV. (TYP. VERT. BEND)
REDUCER
TEE
90° BEND
HORIZONTAL / VERTICAL ANCHOR AND THRUST BLOCK
CONSTRUCTION ITEMS / MATERIALS LIST
2 3
4 5
6 7
1 8
10 11
9 12
13 SECTION
7 13
11 10
9 PLAN
139
53868
4 3
1 12
2 8
01 7/25/2025
NTS03NTS05NTS07NTS
04NTS06NTS 02
DOUBLE CHECK DETECTOR
NTS4" REDUCED PRESSURE PRINCIPLE ASSEMBLY
Z
U
R
N
WI
L
K
I
N
S
Job Number
Date Published
Checked By
Scale
Revision DateARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
3055401
RR
AS SHOWN
CITY OF DOWNEY PUBLIC WORKS - OFFSITE SEWER UTILITY PLANS
SPACE SHUTTLE EXHIBIT AND EDUCATION BUILDING
COLUMBIA WAY
DOWNEY, CA 90242
CITY OF DOWNEY
Developed for
100% CONSTRUCTION DOCUMENTS 07/25/2025
PURSUANT TO THE CALIFORNIA GOVERNMENT CODE
SECTION 4216, NO EXCAVATION PERMIT IS VALID
UNLESS DIG ALERT HAS BEEN CONTACTED AT LEAST
TWO (2) WORKING DAYS PRIOR TO THE
COMMENCEMENT OF EXCAVATION AND AN INQUIRY
IDENTIFICATION NUMBER HAS BEEN ISSUED.
INQUIRY ID#
DIG ALERT NOTICE
NTS
VICINITY MAP
NCOLUMBIA WAYARDIS AVEIMPERIAL HWY
CONGRESSMAN
STEVE HORN WAY
CARING WAYAPOLLO WAY
CENTURY FWY
GLENN ANDERSON FWY
FOSTER RD
STEWART AND
GRAY RD
BELLFLOWER BLVDLAKEWOOD BLVDBROOKSHIRE AVEDOWNEY AVEALA M
E
D
A
S
T
IMP
E
R
I
A
L
H
W
Y
105
PROJECT
LOCATION
LEGAL DESCRIPTION
BASIS OF BEARINGS
BENCHMARK
E E
FW FW
SD SD
W W
DEDICATED PRIVATEFIRE SERVICE
REMOVE EXISTING UTILITY
SANITARY SEWER LINE
DOMESTIC WATER LINE
STORM DRAIN LINE(≤8" DIAMETER)
NATURAL GAS LINE
FLOW LINE
RIGHT OF WAY/PROPERTY LINE
FENCE
AB AGGREGATE BASE
AC ASPHALT CONCRETE PAVEMENT
AE ACCESS EASEMENT
ASPH ASPHALT PAVING
BC BEGIN CURVATURE
BCR BEGIN CURB RETURN
BFP BACK FLOW PREVENTER
BI BOX INLET
BM BENCHMARK
BOP BOTTOM OF PIPE
BOR BOTTOM OF RAMP
BS BOTTOM OF STAIRS
BVC BEGIN VERTICAL CURVATURE
BW BOTTOM OF WALL
C&G CURB AND GUTTER
C/L,CL CENTER LINE
CB CATCH BASIN
CONST CONSTRUCT
CR CURB RETURN
CT COURT
CUL CULVERT
DI DROP INLET
DIP DUCTILE IRON PIPE
DW DOMESTIC WATER
D/W DRIVEWAY
DE DRAINAGE EASEMENT
DR DRIVE
(E) EXISTING
E EAST
EC END CURVATURE
ECR END CURB RETURN
EG EXISTING GRADE
ELEV ELEVATION
EOC EDGE OF CONCRETE
EP EDGE OF PAVEMENT
EQ EQUAL
ESMT EASEMENT
EVC END OF VERTICAL CURVATURE
FF FINISHED FLOOR
FFE FINISHED FLOOR ELEVATION
FG FINISHED GRADE
FH FIRE HYDRANT
FL FLOWLINE
FS FINISHED SURFACE
FW FIRE PROTECTION SERVICE WATER
GB GRADE BREAK
GFL GUTTER FLOWLINE
GSL LIMITS OF GRAVITY SEWER
GR GRATE
GV GAS VALVE
HB HOSE BIB
HP HIGH POINT
ICV IRRIGATION CONTROL VALVE
INTX POINT OF INTERSECTION
INV INVERT
JP JOINT POLE
LE LANDSCAPE EASEMENT
LF LINEAR FEET
LIP LIP OF GUTTER
LP LOW POINT
LT LEFT
MAX MAXIMUM
MH MANHOLE
MIN MINIMUM
MOC MIDDLE OF CURVATURE
N NORTH
NG NATURAL GRADE
NTS NOT TO SCALE
OC ON CENTER
(P) PROPOSED, NEW
PA PLANTING AREA
PBC PULL BOX CABLE
PBE PULL BOX ELECTRIC
PBT PULL BOX TELEPHONE
PBW PULL BOX WATER
PCC POINT OF COMPOUND CURVATURE
PE PEDESTRIAN EASEMENT
PI POINT OF INTERSECTION
PIVC POINT OF INTERSECTION VERTICAL
CURVATURE
PL PROPERTY LINE
POC POINT OF CONNECTION
PP POWER POLE
PRC POINT OF REVERSE CURVATURE
PVC POLYVINYL CHLORIDE
PVMT PAVEMENT
R RADIUS
RCP REINFORCED CONCRETE PIPE
RIM TOP RIM OF STRUCTURE
ROW HIGHWAY EASEMENT
RT RIGHT
RW RECLAIMED WATER
R/W RIGHT OF WAY
S SOUTH OR SLOPE
SBE SETBACK EASEMENT
SCO SANITARY SEWER CLEANOUT
SD STORM DRAIN
SDMH STORM DRAIN MANHOLE
SF SQUARE FEET
SHT SHEET
STA STATION
SMH SANITARY SEWER MANHOLE
SS SANITARY SEWER
SWPPP STORM WATER POLLUTION
PREVENTION PLAN
S/W SIDEWALK
T TANGENT
TB TOP OF BERM
TBC TOP BACK OF CURB
TBW TOP BACK OF WALK
TC TOP OF CURB
TF TOP OF FOOTING
TG TOP OF GRATE
TOE TOE OF SLOPE
TOP TOP OF PIPE
TOR TOP OF RAMP
TOS TOP OF SLOPE
TP TOP OF PLANTER
TS TOP OF STAIRS
TW TOP OF WALL
TYP TYPICAL
TP TELEPHONE POLE
VC VERTICAL CURVATURE
W WEST
WM WATER MAIN
WV WATER VALVE
EXISTING ELECTRICALLINE / CONDUIT
EXISTING DEDICATEDPRIVATE FIRE SERVICE
EXISTING STORM DRAIN LINE
EXISTING WATER LINE
EXISTING SEWER LINE
APPROXIMATE PROJECTLIMITS
GRADE BREAK LINE
PERFORATED STORMDRAIN LINE
G G EXISTING NATURALGAS SERVICE
T T
EXISTINGTELECOMMUNICATIONSLINE / CONDUIT
SS SS
DESCRIPTIONLINE TYPE
STORM DRAIN LINE(>8" DIAMETER)
ABBREVIATIONS
LEGEND
DESCRIPTIONSYMBOL
ROOF DRAIN POC 5' FROM BUILDING
GAS POC 5' FROM BUILDING
FIRE WATER POC 5' FROM BUILDING
DOMESTIC WATER POC 5' FROM BUILDING
SANITARY SEWER POC 5' FROM BUILDING
STORM DRAIN MANHOLE
SANITARY SEWER MANHOLE
DRAIN INLET
AREA DRAIN
TRENCH DRAIN
CLEANOUT
BLOW OFF
FIRE HYDRANT
VALVE
POST INDICATOR VALVE (PIV)/CHECK VALVE(CHK VLV)/FIRE DEPARTMENT CONNECTION (FDC)
CHECK VALVE (CHK VLV)
FIRE DEPARTMENT CONNECTION (FDC)
DOUBLE DETECTOR CHECK (DBL CHK)
REDUCED PRESSURE (BFP)
POST INDICATOR VALVE (PIV)
THRUST BLOCK
BENDS, TEE AND CROSS
WATER METER
AD
XXLF S=X.XXX
XXLF PVC
XXLF S=X.XXX
XXLF S=X.XXX
GB
XXLF PVC
XXLF PVC
co
M
D
S
6"SS
8"FW
6"SD
GAS
6"DW
12"SD
RD
G
F
W
SS
1. THE CONTRACTOR SHALL CONTACT THE RESPECTIVE UTILITY OWNERS FOR LOCATION,
REMOVAL, AND/OR RELOCATION OF ANY UTILITY SERVICES AFFECTED BY CONSTRUCTION. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONARY
MEASURES TO PROTECT UNDERGROUND OR OVERHEAD STRUCTURES WHETHER OR NOT THEY ARE SHOWN ON THESE DRAWINGS.
2. THE CONTRACTOR SHALL NOTIFY THE PROJECT INSPECTOR AND THE RESPECTIVE
UTILITY OWNERS AND OTHER AGENCIES AT LEAST TWO WORKING DAYS PRIOR TO START OF CONSTRUCTION.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR EXPOSING, VERIFYING LOCATIONS (BOTH HORIZONTAL AND VERTICAL), AND MAINTAINING ALL EXISTING UNDERGROUND
UTILITIES, BOTH SHOWN ON THE PLANS AND/OR NOT SHOWN ON THE PLANS DURING CONSTRUCTION. REPAIR DAMAGED UTILITIES TO THE SATISFACTION OF THE ENGINEER.
THE CONTRACTOR SHALL LOCATE EXISTING UNDERGROUND UTILITIES SUFFICIENTLY
AHEAD OF CONSTRUCTION TO PERMIT REVISIONS TO PLANS BECAUSE OF LOCATIONS
OF EXISTING FACILITIES AND SHALL REPORT ALL DISCREPANCIES TO THE ENGINEER PRIOR TO THE COMMENCEMENT OF WORK.
4. THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITIES AND/OR
STRUCTURES SHOWN ON THESE PLANS WERE OBTAINED BY A SEARCH OF THE AVAILABLE RECORDS. APPROVAL OF THESE PLANS DOES NOT CONSTITUTE A
REPRESENTATION AS TO THE ACCURACY OR COMPLETENESS OF THE LOCATION OR
THE EXISTENCE, OR NON-EXISTENCE OF ANY UTILITY AND/OR STRUCTURE WITHIN THE LIMITS OF THIS PROJECT. THE CONTRACTOR IS REQUIRED TO TAKE ALL DUE
PRECAUTIONARY MEASURES TO PROTECT THE UTILITIES OF RECORD AND/OR NOT OF
RECORD SHOWN OR NOT SHOWN AND ANY OTHER LINE(S) OR STRUCTURE(S) NOT SHOWN ON THESE PLANS. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF, AND/OR DAMAGE TO THESE LINE(S) AND/OR STRUCTURE(S).
5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR TEMPORARY SHORING AT PROPOSED
BUILDING FOUNDATIONS, FOOTINGS, AND WALLS TO PROTECT EXISTING UTILITIES IN PLACE.
6. UNAUTHORIZED CHANGES AND USES - CAUTION: THE ENGINEER PREPARING THESE
PLANS WILL NOT BE RESPONSIBLE FOR, OR LIABLE FOR, UNAUTHORIZED CHANGES TO OR USES OF THESE PLANS. ALL CHANGES TO THE PLANS MUST BE IN WRITING AND MUST BE APPROVED BY THE PREPARER OF THESE PLANS.
7. THE CONTRACTOR SHALL MAINTAIN THE EXISTING ACCESSIBLE ROUTE CLEAR OR
PROVIDE AN ALTERNATE ACCESSIBLE ROUTE OF TRAVEL DURING DEMOLITION AND/OR CONSTRUCTION.
8. THE CONTRACTOR SHALL MAINTAIN THE EXISTING FIRE EXITS AND STAIRS CLEAR AND
USABLE OR PROVIDE ALTERNATE FIRE EXITS DURING DEMOLITION AND/OR CONSTRUCTION.
1. ALL ASBESTOS CEMENT PIPE TO BE REMOVED SHALL BE SNAPPED, ENCAPSULATED, AND DISPOSED OF PER LOCAL, STATE, AND FEDERAL REGULATIONS.
2. DOMESTIC WATER SERVICE AND FIRE PROTECTION SHALL BE MAINTAINED DURING CONSTRUCTION. PROVIDE BYPASS LINES DURING CONSTRUCTION INCLUDING TIE-IN.
COORDINATE ALL SHUT DOWNS OF WATER AND POWER WITH OWNER PRIOR TO CONSTRUCTION.
3. PURSUANT TO CALIFORNIA ASSEMBLY BILL 1953 ALL PIPE, FITTINGS, AND FIXTURES
INTENDED TO CONVEY OR DISPENSE WATER FOR HUMAN CONSUMPTION THROUGH DRINKING WATER OR COOKING SHALL BE "LEAD FREE" AS OF JANUARY 1, 2010.
C1.01 TITLE SHEET
C2.01 SEWER UTILITY PLAN
C3.01 SEWER UTILITY DETAILS
IMPORTANT NOTICE
GENERAL NOTES TO CONTRACTOR
CIVIL SHEET INDEX
TITLE SHEET
C1.01
7/24/2025
1. THE INTENT OF THE DEMOLITION PLAN IS TO DESCRIBE IN GENERAL THE DEMOLITION AREAS AFFECTED BY THE PROJECT CONSTRUCTION. IT IS NOT INTENDED AS A DETAILED DESCRIPTION OF EXISTING ITEMS OR ELEMENTS TO BE REMOVED. THE
CONTRACTOR SHALL VISIT THE SITE AND REVIEW ANY AVAILABLE RECORD
DOCUMENTS TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS AND SHOULD
INCLUDE THE REMOVAL OF ALL ITEMS NECESSARY FOR THE PROPER EXECUTION AND COMPLETION OF THE WORK. THE CONTRACT DOCUMENTS ARE COMPLEMENTARY, AND
WHAT IS REQUIRED BY ONE SHALL BE BINDING AS IF REQUIRED BY ALL TO THE EXTENT
THAT IT IS REASONABLY INFERABLE FROM THEM AS BEING NECESSARY TO PRODUCE THE INTENDED RESULTS.
2. REMOVE EXISTING BUILDINGS, FOUNDATIONS AND SERVICE UTILITIES AS INDICATED ON PLANS. CAP ALL UTILITIES AT APPROPRIATE POINTS. ALL EXISTING ELECTRICAL /
TELEPHONE / CATV UTILITIES SHALL BE REMOVED AS INDICATED OR BACK TO THE POINT WHERE THE SPECIFIC UTILITY SYSTEM ENTERS THE WORK AREA. COORDINATE DEMOLITION OF ALL UTILITIES WITH THE OWNER. ALL UTILITIES CONNECTED TO
EXISTING BUILDINGS TO REMAIN SHALL CONTINUE TO BE OPERATIONAL DURING THE DEMOLITION PROCESS. DOMESTIC AND FIRE SERVICE WATER AND NATURAL GAS SHALL
BE REMOVED TO A POINT OUTSIDE THE PERIMETER OF PROPOSED NEW CONSTRUCTION TO EXISTING VALVES OR SIMILAR SHUT-OFF DEVICES. IF A SHUT-OFF
DEVICE IS NOT REASONABLY ADJACENT TO THE PERIMETER OF THE PROPOSED NEW CONSTRUCTION, PROVIDE A SHUT-OFF DEVICE IN BELOW-GRADE YARD BOX. CONFIRM LOCATION OF NEW DEVICES WITH OWNER PRIOR TO INSTALLATION. SANITARY SEWER
AND STORM DRAINAGE SHALL BE CAPPED TO A POINT OUTSIDE THE PERIMETER OF THE PROPOSED NEW CONSTRUCTION. OTHER UTILITIES NOT SPECIFICALLY IDENTIFIED
IN THESE DOCUMENTS AND NOT ANTICIPATED FOR REUSE SHALL BE REMOVED IN ENTIRETY.
3. FOR ALL EXISTING MATERIALS THAT CAN BE SALVAGED, OWNER HAS FIRST RIGHT OF
REFUSAL FOR REMOVED ITEMS THAT MAY HAVE RESIDUAL COMMERCIAL OR HISTORIC
VALUE INCLUDING HARDWARE, GLASS, CORNER STONES, TIME CAPSULES, LIGHT
STANDARDS, SIGNS, FENCING, BENCHES, WATER FOUNTAINS, TRASH CONTAINERS, ETC. SHALL REMAIN AS PROPERTY OF THE OWNER. ALL ITEMS TO BE SALVAGED FOR REUSE/REINSTALLATION MUST MEET CURRENT CODE REQUIREMENTS. COORDINATE
ITEMS TO BE RETAINED WITH OWNER AND REMOVE FROM CONSTRUCTION SITE TO A LOCATION APPROVED BY OWNER. REMOVED MATERIALS, NOT INDICATED OR DIRECTED
TO BE SALVAGED FOR THE OWNER'S BENEFIT ARE DEBRIS AND BECOME THE CONTRACTOR'S PROPERTY UPON REMOVAL.
4. THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITY PIPES OR
STRUCTURES SHOWN ON THESE PLANS ARE OBTAINED BY SEARCH OF THE AVAILABLE RECORDS AND FIELD SURVEYS. THE CONTRACTOR SHALL CONTACT UNDERGROUND
SERVICE ALERT, UTILITY COMPANIES, AND/OR FIELD VERIFY AND LOCATE ALL UTILITIES BEFORE PROCEEDING WITH WORK. THE CONTRACTOR IS ALSO REQUIRED TO TAKE DUE
PRECAUTIONARY MEASURES TO PROTECT THE UTILITY LINES SHOWN AND ANY OTHER LINES NOT OF RECORD OR NOT SHOWN ON THESE PLANS. NOTIFY THE ENGINEER IF
ADDITIONAL UTILITIES ARE LOCATED OR IF CONFLICTS ARE FOUND WITH EXISTING CONDITIONS.
5. ALL TREES TO BE REMOVED SHALL BE MARKED BY CONTRACTOR AND APPROVED FOR
REMOVAL BY THE OWNER OR OWNER'S REPRESENTATIVE PRIOR TO REMOVING OR CUTTING TREE(S). EXISTING ROOTS SHALL BE GRINDED TO A DEPTH OF APPROXIMATELY 3-FEET. USE CAUTION WHILE GRINDING WHEN EXISTING UTILITIES ARE IN CLOSE PROXIMITY TO TREES. ALL TREES TO REMAIN WITHIN THE LIMIT OF WORK SHALL BE PROTECTED AND MAINTAINED PER SPECIFICATIONS AND DETAILS.
6. SAWCUT EXISTING CONCRETE AND ASPHALT TO AN EXISTING CONTROL JOINT WHERE POSSIBLE, AT MINIMUM TO A NEAT-STRAIGHT LINE. ALL DEBRIS SHALL BE HAULED OFFSITE TO A LEGAL DUMPING SITE OR SALVAGED FOR REUSE ON PROJECT AS NOTED.
7. WORK WITHIN CITY, COUNTY, OR STATE RIGHT-OF-WAY REQUIRES A SEPARATE
ENCROACHMENT PERMIT WHICH THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING PRIOR TO STARTING WORK WITHIN RIGHT-OF-WAY.
8. CONTRACTOR TO COORDINATE UTILITY DEMOLITION WITH DRAINAGE AND UTILITY WORK SHOWN IN THIS PLAN SET. ALL UTILITY SHUTDOWNS SHALL BE COORDINATED PER PROJECT SPECIFICATIONS.
9. EXISTING DRY UTILITIES SHOWN FOR DEMOLITION ARE SHOWN FOR COORDINATION ONLY. REFER TO OTHER DISCIPLINES FOR LIMITS AND DETAILS OF DEMOLITION.
10. THE CONTRACTOR SHALL RECYCLE CONSTRUCTION DEBRIS, ASPHALT, AND CONCRETE GENERATED FROM REMOVALS REQUIRED TO CONSTRUCT THE PROJECT. THE
CONTRACTOR IS OBLIGATED, UNDER THIS CONTRACT, TO RECYCLE THE WASTE MATERIAL THROUGH AN APPROVED RECYCLING PLANT.
11. A LIST OF FACILITIES THAT ACCEPT CONSTRUCTION & DEMOLITION DEBRIS CAN BE FOUND ON THE CALRECYCLE WEBSITE AT:
HTTPS://WWW.CALRECYCLE.CA.GOV/CONDEMO
12. CONTRACTOR IS RESPONSIBLE FOR PROTECTING EXISTING BUILDING FINISHES DURING DEMOLITION. ANY FINISH THAT IS DAMAGED DURING DEMOLITION SHALL BE REPAIRED OR REPLACED IN-KIND OR BETTER.
DEMOLITION NOTES
FOR SITE PREPARATION, OVEREXCAVATION, FOUNDATION RECOMMENDATIONS, PAVEMENT,
SUBGRADE, AND GRADATION REQUIREMENTS SEE GEOTECHNICAL INVESTIGATION REPORT ENTITLED:
"GEOTECHNICAL ENGINEERING EVALUATION REPORT, SPACE SHUTTLE EXHIBIT AND EDUCATION BUILDING, 12400 COLUMBIA WAY, DOWNEY, CALIFORNIA" PREPARED BY: TWINING, INC.
4811 AIRPORT PLAZA DRIVE
SUITE 220
LONG BEACH, CA 90815
PROJECT NO: 210932.01
DATED: MARCH 11, 2022
DATED:JULY 16, 2025
GEOTECHNICAL INFORMATION
ELEVATIONS SHOWN HEREON ARE RELATIVE TO THE NORTH AMERICAN VERTICAL DATUM OF 1988 (NAVD88) COUNTY OF LOS ANGELES PUBLIC WORKS 2005 ADJUSTMENT PER THE FOLLOWING COUNTY BENCHMARK:
LA COUNTY BM EY6105 ELEV.=96.219 FT. NAVD88 YEAR 2005
RDBM TAG IN S CB 5' W/O CBR @ SE COR IMPERIAL HIGHWAY & CLARK AVE
ANY USER OF ELEVATIONS AND/OR COORDINATES SHOWN HEREON FOR THE CONTROL OF CONSTRUCTION, SHALL VERIFY AT LEAST 3 POINTS SHOWN HEREON, FOR MATHEMATICAL CONSISTENCY PRIOR TO SUCH USE.
SUBTRACT 2.208 FEET TO ELEVATIONS HEREON TO ADJUST TO THE NGVD DATUM YEAR 1975 LA COUNTY ADJUSTMENT.
THE BEARING OF N89°51'30"E ALONG THE CENTERLINE OF IMPERIAL HIGHWAY AS SHOWN ON MAP OF RECORD OF SURVEY RS BOOK 229 PG 90 AND IS THE BASIS OF BEARINGS FOR THIS SURVEY.
CURRENT LEGAL DESCRIPTION OF SUBJECT PROPERTY HAS NOT BEEN SUPPLIED TO SURVEYOR. SUBJECT PROPERTY LINES HAVE BEEN DETERMINED BY LA COUNTY ASSESSOR MAP 6256-004; APN OF SUBJECT PROPERTY IS 6256-004-910. PROPERTY LINES ARE SUBJECT TO CHANGE.
W W W W
GGGGGGGGGGGG21"SSSSco coSS10"SS12"SS81"SDW
WWWWWWWWWWWW12"DW12"DWW W12"DW
6"FW
SDSDco
EEEEEESDSDSDEEE E E EEEE
EEEEEE2"GG GSSSSSSSSSSSS
SSSSSSSS (E) 15" (ABAND)
xxxx
xxx98979797979797979898989897979797969798989797
9696969796989896979898CO
M
3"DWCOLUMBIA WAY1.5"DW
CO
CO
CO MS
97.50 FFE
97.50 FFE
CO
CO
01 -COLUMBIA WAYCONGRESSMAN STEVE HORN WAY
80.00'
10.00'EX. EASEMENTCLR/WR/WSSSSGGGGGGW W W
WWWWWWWEEEEEEESSSSSSSSSSSS (E) 15" (ABAND)9797CO
S
1 3
(97.44)RIM
85.00INV 8" IN
(84.99)INV 21" IN
(84.94)INV 21" OUT
2 96.22RIM
86.06INVCLR/WR/W80.00'
4 B
(87.66) INV SD
86.19 TOP OF SWR
(E)12" CML DIP WATER MAIN
PER DWG NO. 3-42-30W
(E)21" VCP TRUNK SEWER
PER DWG NO. 3-38-02
(E)81" RCP STORM DRAIN
PER DWG NO. 364-3103-D2.2
58"SS54 LFS=0.02CONNECT TO (E) SEWER MANHOLE PER SPPWC 208-3.
PUBLIC SEWER CONSTRUCTION NOTES:
1 CONSTRUCT 8" SEWER PER LACSD SPECIFICATION2
CONNECT TO SEWER MANHOLE. SEE ON-SITE PLANS FOR MANHOLE AND SEWER CONTINUATION.3
TRENCHING LIMITS PER DETAIL 03 SHEET C3.01.
REMOVE PORTIONS OF ABANDONED 15" SEWER PIPE NECESSARY TO CONSTRUCT PROPOSED 8" SEWER SERVICE.4
1. UTILITIES TO CROSS OVER OR UNDER OTHER UTILITIES TO MAINTAIN 12" MINIMUM CLEARANCE AT UTILITY CROSSINGS, UNLESS NOTED OTHERWISE. SANITARY SEWER TO CROSS UNDER POTABLE WATER.
2. CONTRACTOR SHALL VERIFY SIZE AND LOCATION (HORIZONTAL AND VERTICAL) OF
EXISTING CROSSING AND JOINING UTILITIES PRIOR TO CONSTRUCTION AND IMMEDIATELY NOTIFY THE ENGINEER OF ANY CONFLICT.
3. CONTRACTOR SHALL CONSTRUCT GRAVITY UTILITIES (SEWER AND STORM DRAIN) BEFORE OTHER UTILITIES. CONSTRUCTION OF THESE GRAVITY UTILITIES TO START FROM THE DOWNSTREAM ENDS.
4. EXISTING UTILITIES ARE COMPILED BASED ON PREVIOUS BASE FILES, FIELD SURVEY AND FIELD VERIFICATION. POTHOLING IS RECOMMENDED TO VERIFY ANY AND ALL UTILITIES KNOWN OR UNKNOWN WHICH MAY BE IN CONFLICT WITH PROPOSED CONSTRUCTION.
5. PRIOR TO THE REMOVAL OF ANY WET OR DRY UTILITY LINES, THE CONTRACTOR SHALL
CONFIRM WITH OWNER REPRESENTATIVE WHETHER THESE UTILITY LINES ARE STILL ACTIVE OR NOT. IMMEDIATELY NOTIFY THE ENGINEER OF ANY CONFLICT.
6. CONTRACTOR TO ADJUST TO FINISH GRADE ALL EXISTING UTILITY BOXES, SEWER
CLEANOUT COVERS, PULL BOXES AND VALVE COVERS NOT SPECIFICALLY SHOWN WITHIN THE LIMITS OF WORK.
CONSTRUCTION NOTES:
REMOVE (E) AC PAVEMENT, SEE DEMOLITION NOTE 10 SHEET C1.01.
DEMOLITION NOTES
-SEE DEMOLITION NOTES, SHEET C1.01.
B
CONSTRUCT BLANKET PROTECTION PER SPPWC 225-03.5
N
3015 600
1" = 30'PLAN VIEW
N
105 200
1" = 10'01ENLARGEMENT
Job Number
Date Published
Checked By
Scale
Revision DateARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
3055401
RR
AS SHOWN
CITY OF DOWNEY PUBLIC WORKS - OFFSITE SEWER UTILITY PLANS
SPACE SHUTTLE EXHIBIT AND EDUCATION BUILDING
COLUMBIA WAY
DOWNEY, CA 90242
CITY OF DOWNEY
Developed for
100% CONSTRUCTION DOCUMENTS 07/25/2025
C2.02
SEWER UTILITY PLAN
7/24/2025
Job Number
Date Published
Checked By
Scale
Revision DateARCHITECTURE ENGINEERING INTERIOR DESIGN
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue, Suite 100
Irvine, California 92617
This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.
Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
3055401
RR
AS SHOWN
CITY OF DOWNEY PUBLIC WORKS - OFFSITE SEWER UTILITY PLANS
SPACE SHUTTLE EXHIBIT AND EDUCATION BUILDING
COLUMBIA WAY
DOWNEY, CA 90242
CITY OF DOWNEY
Developed for
100% CONSTRUCTION DOCUMENTS 07/25/2025
SEWER UTILITY
DETAILS
C3.01
7/24/2025
© LPA, Inc.Developed forJob NumberDate PublishedChecked ByScaleRevision Date ARCHITECTURE ENGINEERING INTERIORSLANDSCAPE ARCHITECTURE PLANNING949-261-1001 Office949-260-1190 FaxLPADesignStudios.comSubmittal Date 5301 California Avenue,Suite 100Irvine, California 92617This document and all other project documents,ideas, aesthetics and designs incorporatedtherein are instruments of service. All projectdocuments are copyright protected, are theproperty of LPA, Inc. (LPA) and cannot be lawfullyused in whole or in part for any project or purposeexcept as set forth in the contractual agreementbetween LPA and its Client. The unauthorizeddisclosure and/or use of the project documents(including the creation of derivative works), maygive rise to liability for copyright infringement,unlawful disclosure, use or misappropriation ofproperty rights held by LPA. The unauthorizeduse of the project documents will give rise to therecovery of monetary losses and damagesincluding attorney fees and costs for which theunauthorized user will be held liable.Project documents describe the design intent ofthe work and are not a representation of as-builtor existing conditions. LPA is not responsible forany discrepancies between the project documentsand the existing conditions.DOWNEY SPACE SHUTTLE MUSEUM
COLUMBIA WAY
DOWNEY, CA 90242
CITY OF DOWNEY3055401R.R.02/10/2023SCHEMATIC DESIGN 10/27/2022 50% DESIGN DEVELOPMENT 12/02/2022
100% DESIGN DEVELOPMENT 01/06/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CONSTRUCTION DOCS 08/01/2025
N/AC0.01CIVIL NOTESC:\ProgramData\LPA\_CAD Library\titleblocks_icon\Digalert_logo.pngEEFWFWSDSDWWC:\ProgramData\LPA\_CAD Library\Titleblocks_Icon\811s_horz.png1. THE INTENT OF THE DEMOLITION PLAN IS TO DESCRIBE IN GENERAL THE DEMOLITIONAREAS AFFECTED BY THE PROJECT CONSTRUCTION. IT IS NOT INTENDED AS ADETAILED DESCRIPTION OF EXISTING ITEMS OR ELEMENTS TO BE REMOVED. THECONTRACTOR SHALL VISIT THE SITE AND REVIEW ANY AVAILABLE RECORDDOCUMENTS TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS AND SHOULDINCLUDE THE REMOVAL OF ALL ITEMS NECESSARY FOR THE PROPER EXECUTION ANDCOMPLETION OF THE WORK. THE CONTRACT DOCUMENTS ARE COMPLEMENTARY, ANDWHAT IS REQUIRED BY ONE SHALL BE BINDING AS IF REQUIRED BY ALL TO THE EXTENTTHAT IT IS REASONABLY INFERABLE FROM THEM AS BEING NECESSARY TO PRODUCETHE INTENDED RESULTS.2. REMOVE EXISTING BUILDINGS, FOUNDATIONS AND SERVICE UTILITIES AS INDICATED ONPLANS. CAP ALL UTILITIES AT APPROPRIATE POINTS. ALL EXISTING ELECTRICAL /TELEPHONE / CATV UTILITIES SHALL BE REMOVED AS INDICATED OR BACK TO THEPOINT WHERE THE SPECIFIC UTILITY SYSTEM ENTERS THE WORK AREA. COORDINATEDEMOLITION OF ALL UTILITIES WITH THE OWNER. ALL UTILITIES CONNECTED TOEXISTING BUILDINGS TO REMAIN SHALL CONTINUE TO BE OPERATIONAL DURING THEDEMOLITION PROCESS. DOMESTIC AND FIRE SERVICE WATER AND NATURAL GAS SHALLBE REMOVED TO A POINT OUTSIDE THE PERIMETER OF PROPOSED NEWCONSTRUCTION TO EXISTING VALVES OR SIMILAR SHUT-OFF DEVICES. IF A SHUT-OFFDEVICE IS NOT REASONABLY ADJACENT TO THE PERIMETER OF THE PROPOSED NEWCONSTRUCTION, PROVIDE A SHUT-OFF DEVICE IN BELOW-GRADE YARD BOX. CONFIRMLOCATION OF NEW DEVICES WITH OWNER PRIOR TO INSTALLATION. SANITARY SEWERAND STORM DRAINAGE SHALL BE CAPPED TO A POINT OUTSIDE THE PERIMETER OFTHE PROPOSED NEW CONSTRUCTION. OTHER UTILITIES NOT SPECIFICALLY IDENTIFIEDIN THESE DOCUMENTS AND NOT ANTICIPATED FOR REUSE SHALL BE REMOVED INENTIRETY.3. FOR ALL EXISTING MATERIALS THAT CAN BE SALVAGED, OWNER HAS FIRST RIGHT OFREFUSAL FOR REMOVED ITEMS THAT MAY HAVE RESIDUAL COMMERCIAL OR HISTORICVALUE INCLUDING HARDWARE, GLASS, CORNER STONES, TIME CAPSULES, LIGHT STANDARDS, SIGNS, FENCING, BENCHES, WATER FOUNTAINS, TRASH CONTAINERS,ETC. SHALL REMAIN AS PROPERTY OF THE OWNER. ALL ITEMS TO BE SALVAGED FORREUSE/REINSTALLATION MUST MEET CURRENT CODE REQUIREMENTS. COORDINATEITEMS TO BE RETAINED WITH OWNER AND REMOVE FROM CONSTRUCTION SITE TO ALOCATION APPROVED BY OWNER. REMOVED MATERIALS, NOT INDICATED OR DIRECTEDTO BE SALVAGED FOR THE OWNER'S BENEFIT ARE DEBRIS AND BECOME THECONTRACTOR'S PROPERTY UPON REMOVAL.4. THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITY PIPES ORSTRUCTURES SHOWN ON THESE PLANS ARE OBTAINED BY SEARCH OF THE AVAILABLERECORDS AND FIELD SURVEYS. THE CONTRACTOR SHALL CONTACT UNDERGROUNDSERVICE ALERT, UTILITY COMPANIES, AND/OR FIELD VERIFY AND LOCATE ALL UTILITIESBEFORE PROCEEDING WITH WORK. THE CONTRACTOR IS ALSO REQUIRED TO TAKE DUEPRECAUTIONARY MEASURES TO PROTECT THE UTILITY LINES SHOWN AND ANY OTHERLINES NOT OF RECORD OR NOT SHOWN ON THESE PLANS. NOTIFY THE ENGINEER IFADDITIONAL UTILITIES ARE LOCATED OR IF CONFLICTS ARE FOUND WITH EXISTINGCONDITIONS.5. ALL TREES TO BE REMOVED SHALL BE MARKED BY CONTRACTOR AND APPROVED FORREMOVAL BY THE OWNER OR OWNER'S REPRESENTATIVE PRIOR TO REMOVING ORCUTTING TREE(S). EXISTING ROOTS SHALL BE GRINDED TO A DEPTH OFAPPROXIMATELY 3-FEET. USE CAUTION WHILE GRINDING WHEN EXISTING UTILITIES AREIN CLOSE PROXIMITY TO TREES. ALL TREES TO REMAIN WITHIN THE LIMIT OF WORKSHALL BE PROTECTED AND MAINTAINED PER SPECIFICATIONS AND DETAILS.6. SAWCUT EXISTING CONCRETE AND ASPHALT TO AN EXISTING CONTROL JOINT WHEREPOSSIBLE, AT MINIMUM TO A NEAT-STRAIGHT LINE. ALL DEBRIS SHALL BE HAULEDOFFSITE TO A LEGAL DUMPING SITE OR SALVAGED FOR REUSE ON PROJECT AS NOTED.7. WORK WITHIN CITY, COUNTY, OR STATE RIGHT-OF-WAY REQUIRES A SEPARATEENCROACHMENT PERMIT WHICH THE CONTRACTOR IS RESPONSIBLE FOR OBTAININGPRIOR TO STARTING WORK WITHIN RIGHT-OF-WAY.8. CONTRACTOR TO COORDINATE UTILITY DEMOLITION WITH DRAINAGE AND UTILITYWORK SHOWN IN THIS PLAN SET. ALL UTILITY SHUTDOWNS SHALL BE COORDINATEDPER PROJECT SPECIFICATIONS.9. EXISTING DRY UTILITIES SHOWN FOR DEMOLITION ARE SHOWN FOR COORDINATIONONLY. REFER TO OTHER DISCIPLINES FOR LIMITS AND DETAILS OF DEMOLITION.10. THE CONTRACTOR SHALL RECYCLE CONSTRUCTION DEBRIS, ASPHALT, AND CONCRETEGENERATED FROM REMOVALS REQUIRED TO CONSTRUCT THE PROJECT. THECONTRACTOR IS OBLIGATED, UNDER THIS CONTRACT, TO RECYCLE THE WASTEMATERIAL THROUGH AN APPROVED RECYCLING PLANT.11. A LIST OF FACILITIES THAT ACCEPT CONSTRUCTION & DEMOLITION DEBRIS CAN BEFOUND ON THE CALRECYCLE WEBSITE AT:HTTPS://WWW.CALRECYCLE.CA.GOV/CONDEMO12. CONTRACTOR IS RESPONSIBLE FOR PROTECTING EXISTING BUILDING FINISHES DURINGDEMOLITION. ANY FINISH THAT IS DAMAGED DURING DEMOLITION SHALL BE REPAIREDOR REPLACED IN-KIND OR BETTER.1. THE CONTRACTOR SHALL CONTACT THE RESPECTIVE UTILITY OWNERS FOR LOCATION,REMOVAL, AND/OR RELOCATION OF ANY UTILITY SERVICES AFFECTED BYCONSTRUCTION. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONARYMEASURES TO PROTECT UNDERGROUND OR OVERHEAD STRUCTURES WHETHER ORNOT THEY ARE SHOWN ON THESE DRAWINGS.2. THE CONTRACTOR SHALL NOTIFY THE PROJECT INSPECTOR AND THE RESPECTIVEUTILITY OWNERS AND OTHER AGENCIES AT LEAST TWO WORKING DAYS PRIOR TOSTART OF CONSTRUCTION.3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR EXPOSING, VERIFYING LOCATIONS(BOTH HORIZONTAL AND VERTICAL), AND MAINTAINING ALL EXISTING UNDERGROUNDUTILITIES, BOTH SHOWN ON THE PLANS AND/OR NOT SHOWN ON THE PLANS DURINGCONSTRUCTION. REPAIR DAMAGED UTILITIES TO THE SATISFACTION OF THE ENGINEER.THE CONTRACTOR SHALL LOCATE EXISTING UNDERGROUND UTILITIES SUFFICIENTLYAHEAD OF CONSTRUCTION TO PERMIT REVISIONS TO PLANS BECAUSE OF LOCATIONSOF EXISTING FACILITIES AND SHALL REPORT ALL DISCREPANCIES TO THE ENGINEERPRIOR TO THE COMMENCEMENT OF WORK.4. THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITIES AND/ORSTRUCTURES SHOWN ON THESE PLANS WERE OBTAINED BY A SEARCH OF THEAVAILABLE RECORDS. APPROVAL OF THESE PLANS DOES NOT CONSTITUTE AREPRESENTATION AS TO THE ACCURACY OR COMPLETENESS OF THE LOCATION ORTHE EXISTENCE, OR NON-EXISTENCE OF ANY UTILITY AND/OR STRUCTURE WITHIN THELIMITS OF THIS PROJECT. THE CONTRACTOR IS REQUIRED TO TAKE ALL DUEPRECAUTIONARY MEASURES TO PROTECT THE UTILITIES OF RECORD AND/OR NOT OFRECORD SHOWN OR NOT SHOWN AND ANY OTHER LINE(S) OR STRUCTURE(S) NOTSHOWN ON THESE PLANS. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTIONOF, AND/OR DAMAGE TO THESE LINE(S) AND/OR STRUCTURE(S).5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR TEMPORARY SHORING AT PROPOSEDBUILDING FOUNDATIONS, FOOTINGS, AND WALLS TO PROTECT EXISTING UTILITIES INPLACE.6. UNAUTHORIZED CHANGES AND USES - CAUTION: THE ENGINEER PREPARING THESEPLANS WILL NOT BE RESPONSIBLE FOR, OR LIABLE FOR, UNAUTHORIZED CHANGES TOOR USES OF THESE PLANS. ALL CHANGES TO THE PLANS MUST BE IN WRITING ANDMUST BE APPROVED BY THE PREPARER OF THESE PLANS.7. THE CONTRACTOR SHALL MAINTAIN THE EXISTING ACCESSIBLE ROUTE CLEAR ORPROVIDE AN ALTERNATE ACCESSIBLE ROUTE OF TRAVEL DURING DEMOLITION AND/ORCONSTRUCTION.8. THE CONTRACTOR SHALL MAINTAIN THE EXISTING FIRE EXITS AND STAIRS CLEAR ANDUSABLE OR PROVIDE ALTERNATE FIRE EXITS DURING DEMOLITION AND/ORCONSTRUCTION.PORTIONS OF DEMOLITION MAY REQUIRE BLOCKING AND/OR OBSTRUCTING THROUGHACCESS TO EMERGENCY / FIRE ACCESS VEHICLES. IT SHALL BE THE SOLE RESPONSIBILITYOF THE CONTRACTOR TO PROVIDE A FIRE WATCH SPECIALIST SERVICE FOR THE DURATIONOF TIME THAT EMERGENCY / FIRE ACCESS VEHICLES ARE BLOCKED AND/OR OBSTRUCTEDDURING CONSTRUCTION UNLESS EQUIVALENT ALTERNATE MEASURES ARE TAKEN TOENSURE CONTINUOUS ACCESS TO EMERGENCY / FIRE ACCESS VEHICLES. CONTRACTOR TOCOORDINATE THROUGH ACCESS TO EMERGENCY / FIRE ACCESS VEHICLES WITH THE LOCALFIRE AUTHORITY HAVING JURISDICTION.FOR SITE PREPARATION, OVEREXCAVATION, FOUNDATION RECOMMENDATIONS, PAVEMENT,SUBGRADE, AND GRADATION REQUIREMENTS SEE GEOTECHNICAL INVESTIGATION REPORTENTITLED:"GEOTECHNICAL ENGINEERING EVALUATION REPORT"PREPARED BY: TWINING, INC.2883 EAST SPRING STREETSUITE 300LONG BEACH, CA 90806PROJECT NO: 210932.1DATED: MARCH 11, 20221. IT IS THE CONTRACTOR'S RESPONSIBILITY TO REVIEW THE GRADING PLANS AND SOILSREPORT THOROUGHLY PRIOR TO SITE MOBILIZATION. IT IS ALSO THE GRADINGCONTRACTOR'S RESPONSIBILITY TO NOTIFY THE CIVIL AND SOILS ENGINEERS IFONSITE DISCREPANCIES ARE OBSERVED THAT WOULD AFFECT THE EARTHWORKQUANTITIES.2. THE EXISTING TOPOGRAPHY AS DELINEATED ON THESE DRAWINGS SHALL BE UTILIZEDAS THE BASIS FOR ALL EARTHWORK COMPUTATIONS. SAID TOPOGRAPHY SHALL BEPRESUMED TO BE ACCEPTABLE TO ALL INTERESTED PARTIES UNLESS A DEVIATION ISFOUND PRIOR TO THE START OF GRADING IN ANY SPECIFIC AREAS. ANY DEVIATION SODETERMINED SHALL BE PROMPTLY TRANSMITTED TO ALL INTERESTED PARTIES.3. THE CONTRACTOR IS REQUIRED TO ESTIMATE THE QUANTITIES OF GRADING WORK TOBE DONE AND INCLUDE ALL COSTS THEREFROM WITH HIS BID, AS NO ADDITIONALALLOWANCE WILL BE MADE WITHOUT PRIOR CONSENT FROM THE OWNER.4. OVER-EXCAVATION AND/OR EXCESS BACKFILLING OR DUPLICATION OF GRADINGACTIVITIES IS NOT A BASIS FOR ADDITIONAL COMPENSATION. THIS ALSO APPLIESWHERE MATERIAL IS TO BE REMOVED AND REPLACED TO REDUCE MOISTURECONTENT.5. OFF-SITE DISPOSAL OF EXCAVATION MATERIAL IS THE RESPONSIBILITY OF THECONTRACTOR AND SHALL BE INCLUDED IN THE BID. THE CONTRACTOR SHALL HOLDTHE OWNER AND ENGINEER HARMLESS AS A RESULT OF ANY CLAIMS ARISING FROMTHE ACTIONS ENROUTE OR AWAY FROM THE SITE.6. EARTH VOLUMES SHOWN HEREON ARE ESTIMATES BASED UPON THE GEOTECHNICALANALYSIS PERFORMED BY THE NAMED SOILS ENGINEER AND TOPOGRAPHIC SURVEYOF THE EXISTING GROUND SURFACE AT THE TIME OF PLAN PREPARATION.EARTHWORK VOLUMES ARE COMPUTED BY METHODS COMMONLY USED IN STANDARDENGINEERING PRACTICE, AND ARE INTENDED FOR USE IN ESTABLISHING GOVERNINGAGENCY FEES. ACTUAL FIELD CONDITIONS MAY VARY FROM OBSERVED OR MEASUREDCONDITIONS AT THE TIME OF PLAN PREPARATION. EARTHWORK QUANTITIES MAY VARYAS A RESULT.7. ANY EXPORT OR IMPORT REQUIRED TO BALANCE THE SITE SHALL BE THE SOLERESPONSIBILITY OF THE CONTRACTOR.8. PAVEMENT AND SUBGRADE RECOMMENDATIONS RELATED TO OVER-EXCAVATION,PAVEMENT SUBGRADE, ETC., PER GEOTECHNICAL REPORT.XXXXXXXXXXXXXXXTHE BOUNDARY LINES SHOWN HEREON ARE BASED UPON ___________________THE COORDINATES RELATING TO THIS DIGITAL FILE ARE DERIVED FROM ____________DEDICATED PRIVATEFIRE SERVICEREMOVE EXISTING UTILITYSANITARY SEWER LINEDOMESTIC WATER LINESTORM DRAIN LINE(≤8" DIAMETER)NATURAL GAS LINEFLOW LINE1. CONTRACTOR SHALL ENSURE THAT THE CONSTRUCTION SITE IS PREPARED PRIOR TOTHE START OF CONSTRUCTION. CONTRACTOR SHALL HAVE ALL EROSION ANDSEDIMENT CONTROL MEASURES IN PLACE AT ALL TIMES DURING CONSTRUCTION.2. ALL EROSION AND SEDIMENT CONTROL MEASURES SHALL BE MAINTAINED UNTILDISTURBED AREAS ARE STABILIZED.3. THIS PLAN MAY NOT COVER ALL THE SITUATIONS THAT ARISE DURING CONSTRUCTIONDUE TO UNANTICIPATED FIELD CONDITIONS.4. ALL EROSION AND SEDIMENT CONTROL MEASURES SHALL BE CHECKED BEFORE ANDAFTER ALL STORMS TO ENSURE MEASURES ARE FUNCTIONING PROPERLY.5. CONTRACTOR SHALL MAINTAIN A LOG AT THE SITE OF ALL INSPECTIONS ORMAINTENANCE OF BMPS, AS WELL AS, ANY CORRECTIVE CHANGES TO THE BMPS OREROSION AND SEDIMENT CONTROL PLAN.6. IN AREAS WHERE SOIL IS EXPOSED, PROMPT REPLANTING WITH NATIVE COMPATIBLE,DROUGHT-RESISTANT VEGETATION SHALL BE PERFORMED. NO AREAS WILL BE LEFTEXPOSED OVER THE WINTER SEASON.7. THE CONTRACTOR SHALL INSTALL THE STABILIZED CONSTRUCTION ENTRANCE PRIORTO COMMENCEMENT OF GRADING. LOCATION OF THE ENTRANCE MAY BE ADJUSTED BYTHE CONTRACTOR TO FACILITATE GRADING OPERATIONS. ALL CONSTRUCTION TRAFFICENTERING THE PAVED ROAD MUST CROSS THE STABILIZED CONSTRUCTION ENTRANCE.8. ALL SEDIMENT DEPOSITED ON PAVED ROADWAYS SHALL BE SWEPT AT THE END OFEACH WORKING DAY OR MORE OFTEN AS NECESSARY.9. CONTRACTOR SHALL PLACE GRAVEL/SAND BAGS AROUND ALL NEW DRAINAGESTRUCTURE OPENINGS IMMEDIATELY AFTER THE STRUCTURE OPENING ISCONSTRUCTED. THESE GRAVEL/SAND BAGS SHALL BE MAINTAINED AND REMAIN INPLACE UNTIL CONSTRUCTION IS COMPLETED.10. CONTRACTOR SHALL IMPLEMENT HOUSEKEEPING PRACTICES AS FOLLOWS:A. SOLID WASTE MANAGEMENT:PROVIDE DESIGNATED WASTE COLLECTION AREAS AND CONTAINERS. ARRANGE FORREGULAR REMOVAL AND DISPOSAL. CLEAR SITE OF TRASH INCLUDING ORGANICDEBRIS, PACKAGING MATERIALS, SCRAP OR SURPLUS BUILDING MATERIALS ANDDOMESTIC WASTE DAILY.B. MATERIAL DELIVERY AND STORAGE:PROVIDE A DESIGNATED MATERIAL STORAGE AREA WITH SECONDARY CONTAINMENTSUCH AS BERMING. STORE MATERIAL ON PALLETS AND PROVIDE COVERING FORSOLUBLE MATERIALS. RELOCATE STORAGE AREA INTO BUILDING SHELL WHENPOSSIBLE. INSPECT AREA WEEKLY.C. CONCRETE WASTE:PROVIDE A DESIGNATED AREA FOR A TEMPORARY PIT TO BE USED FOR CONCRETETRUCK WASH-OUT. CONCRETE WASHOUT CANNOT BE WITHIN 50' MINIMUM OF DRAININLETS. DISPOSE OF HARDENED CONCRETE OFFSITE. AT NO TIME SHALL A CONCRETETRUCK DUMP ITS WASTE AND CLEAN ITS TRUCK INTO THE STORM DRAINS VIA CURBAND GUTTER. INSPECT DAILY TO CONTROL RUNOFF, AND WEEKLY FOR REMOVAL OFHARDENED CONCRETE.D. PAINT AND PAINTING SUPPLIES:PROVIDE INSTRUCTION TO EMPLOYEES AND SUBCONTRACTORS REGARDINGREDUCTION OF POLLUTANTS INCLUDING MATERIAL STORAGE, USE, AND CLEAN UP.INSPECT SITE WEEKLY FOR EVIDENCE OF IMPROPER DISPOSAL.E. VEHICLE FUELING, MAINTENANCE AND CLEANING:PROVIDE A DESIGNATED FUELING AREA WITH SECONDARY CONTAINMENT SUCH ASBERMING. DO NOT ALLOW MOBILE FUELING OF EQUIPMENT. PROVIDE EQUIPMENTWITH DRIP PANS. RESTRICT ONSITE MAINTENANCE AND CLEANING OF EQUIPMENT TOA MINIMUM. INSPECT AREA WEEKLY.F. HAZARDOUS WASTE MANAGEMENT:PREVENT THE DISCHARGE OF POLLUTANTS FROM HAZARDOUS WASTES TO THEDRAINAGE SYSTEM THROUGH PROPER MATERIAL USE, WASTE DISPOSAL ANDTRAINING OF EMPLOYEES. HAZARDOUS WASTE PRODUCTS COMMONLY FOUNDON-SITE INCLUDE BUT ARE NOT LIMITED TO PAINTS & SOLVENTS, PETROLEUMPRODUCTS, FERTILIZERS, HERBICIDES & PESTICIDES, SOIL STABILIZERS,STABILIZATION PRODUCTS, ASPHALT PRODUCTS AND CONCRETE CURING PRODUCTS.11. CONTRACTOR SHALL HYDROSEED ALL GRADED SLOPES. NATIVE SEED MIX SHALL BE20% LANA PUBESCENT WHEAT GRASS, 40% BLANDO BROME, AND 40% ANNUAL RYEGRASS AND SHALL BE APPLIED AT A RATE OF 200 POUNDS PER ACRE. SOIL BINDINGAGENT SHALL BE VERDYOL, SENTINEL, OR EQUAL, APPLIED AT A RATE OF 110 POUNDSPER ACRE. MULCH SHALL BE SILVER-FIBER, CONWED, OR EQUAL, APPLIED AT A RATEOF 1,000 POUNDS PER ACRE. FERTILIZER SHALL BE AGRI-FORM 16-7-12, BEST 16-6-8, OREQUAL, APPLIED AT A RATE OF 500 POUNDS PER ACRE. THE CONTRACTOR SHALLWATER SEEDED AREAS OR RESEED AS NECESSARY TO ENSURE SUFFICIENT PLANTDEVELOPMENT FOR EROSION CONTROL.12. NO GRADING SHALL BE DONE UNTIL SITE- AND SEASON-SPECIFIC SOIL LOSS ANDHOUSEKEEPING STORMWATER BMPs HAVE BEEN APPROVED BY THE INSPECTOR. THECONTRACTOR SHOULD EMPLOY THE DESIGN BMPs AND ANY OTHERS NEEDED ASSITUATIONS ARISE. CONTRACTOR SHOULD CONDUCT SITE INSPECTIONS BEFORE,DURING AND AFTER EACH EXTENDED STORM EVENT TO IDENTIFY CONDITIONS THATMAY CONTRIBUTE TO EROSION AND SEDIMENT PROBLEMS OR ANY OTHER POLLUTANTDISCHARGES. IF ADDITIONAL CONTROL MEASURES ARE NEEDED, CONTRACTORSHOULD IMPLEMENT THEM IMMEDIATELY.RIGHT OF WAY/PROPERTY LINEFENCEAPPROXIMATE CUT: X,XXX CYAPPROXIMATE FILL: X,XXX CYNOTE:EARTHWORK QUANTITIES INDICATED ARE FOR REFERENCE ONLY (NOT FOR BID ORPAYMENT). THE CONTRACTOR IS RESPONSIBLE FOR ACTUAL QUANTITIES.*HAUL ROUTE TO BE DETERMINED AT PRE-GRADE MEETING AND ALL NECESSARY PERMITSSHALL BE OBTAINED BY THE GENERAL CONTRACTOR*AB AGGREGATE BASEAC ASPHALT CONCRETE PAVEMENTAE ACCESS EASEMENTASPH ASPHALT PAVINGBC BEGIN CURVATUREBCR BEGIN CURB RETURNBFP BACK FLOW PREVENTERBI BOX INLETBM BENCHMARKBOP BOTTOM OF PIPEBOR BOTTOM OF RAMPBS BOTTOM OF STAIRSBVC BEGIN VERTICAL CURVATUREBW BOTTOM OF WALLC&G CURB AND GUTTERC/L,CL CENTER LINECB CATCH BASINCONST CONSTRUCTCR CURB RETURNCT COURTCUL CULVERTDI DROP INLETDIP DUCTILE IRON PIPEDW DOMESTIC WATERD/W DRIVEWAYDE DRAINAGE EASEMENTDR DRIVE(E) EXISTINGE EASTEC END CURVATUREECR END CURB RETURNEG EXISTING GRADEELEV ELEVATIONEOC EDGE OF CONCRETEEP EDGE OF PAVEMENTEQ EQUALESMT EASEMENTEVC END OF VERTICAL CURVATUREFF FINISHED FLOORFFE FINISHED FLOOR ELEVATIONFG FINISHED GRADEFH FIRE HYDRANTFL FLOWLINEFS FINISHED SURFACEFW FIRE PROTECTION SERVICE WATERGB GRADE BREAKGFL GUTTER FLOWLINEGSL LIMITS OF GRAVITY SEWERGR GRATEGV GAS VALVEHB HOSE BIBHP HIGH POINTICV IRRIGATION CONTROL VALVEINTX POINT OF INTERSECTIONINV INVERTJP JOINT POLELE LANDSCAPE EASEMENTLF LINEAR FEETLIP LIP OF GUTTERLP LOW POINTLT LEFTMAX MAXIMUMMH MANHOLEMIN MINIMUMMOC MIDDLE OF CURVATUREN NORTHNG NATURAL GRADENTS NOT TO SCALEOC ON CENTER(P) PROPOSED, NEWPA PLANTING AREAPBC PULL BOX CABLEPBE PULL BOX ELECTRICPBT PULL BOX TELEPHONEPBW PULL BOX WATERPCC POINT OF COMPOUND CURVATUREPE PEDESTRIAN EASEMENTPI POINT OF INTERSECTIONPIVC POINT OF INTERSECTION VERTICALCURVATUREPL PROPERTY LINEPOC POINT OF CONNECTIONPP POWER POLEPRC POINT OF REVERSE CURVATUREPVC POLYVINYL CHLORIDEPVMT PAVEMENTR RADIUSRCP REINFORCED CONCRETE PIPERIM TOP RIM OF STRUCTUREROW HIGHWAY EASEMENTRT RIGHTRW RECLAIMED WATERR/W RIGHT OF WAYS SOUTH OR SLOPESBE SETBACK EASEMENTSCO SANITARY SEWER CLEANOUTSD STORM DRAINSDMH STORM DRAIN MANHOLESF SQUARE FEETSHT SHEETSTA STATIONSMH SANITARY SEWER MANHOLESS SANITARY SEWERSWPPP STORM WATER POLLUTIONPREVENTION PLANS/W SIDEWALKT TANGENTTB TOP OF BERMTBC TOP BACK OF CURBTBW TOP BACK OF WALKTC TOP OF CURBTF TOP OF FOOTINGTG TOP OF GRATETOE TOE OF SLOPETOP TOP OF PIPETOR TOP OF RAMPTOS TOP OF SLOPETP TOP OF PLANTERTS TOP OF STAIRSTW TOP OF WALLTYP TYPICALTP TELEPHONE POLEVC VERTICAL CURVATUREW WESTWM WATER MAINWV WATER VALVESTATIC:XXX P.S.I.FLOW: X,XXX G.P.M. @ XX P.S.I.LOCATION: XXXXTEST DATE: XX-XX-XXXXEXISTING ELECTRICALLINE / CONDUITEXISTING DEDICATEDPRIVATE FIRE SERVICEEXISTING STORM DRAIN LINEEXISTING WATER LINEEXISTING SEWER LINEAPPROXIMATE PROJECTLIMITSGRADE BREAK LINETOTAL DISTURBED AREA = XXX± ACRESPURSUANT TO THE CALIFORNIA GOVERNMENT CODESECTION 4216, NO EXCAVATION PERMIT IS VALIDUNLESS DIG ALERT HAS BEEN CONTACTED AT LEASTTWO (2) WORKING DAYS PRIOR TO THECOMMENCEMENT OF EXCAVATION AND AN INQUIRYIDENTIFICATION NUMBER HAS BEEN ISSUED.INQUIRY ID#1. ALL ASBESTOS CEMENT PIPE TO BE REMOVED SHALL BE SNAPPED, ENCAPSULATED,AND DISPOSED OF PER LOCAL, STATE, AND FEDERAL REGULATIONS.2. DOMESTIC WATER SERVICE AND FIRE PROTECTION SHALL BE MAINTAINED DURINGCONSTRUCTION. PROVIDE BYPASS LINES DURING CONSTRUCTION INCLUDING TIE-IN.COORDINATE ALL SHUT DOWNS OF WATER AND POWER WITH OWNER PRIOR TOCONSTRUCTION.3. PURSUANT TO CALIFORNIA ASSEMBLY BILL 1953 ALL PIPE, FITTINGS, AND FIXTURESINTENDED TO CONVEY OR DISPENSE WATER FOR HUMAN CONSUMPTION THROUGHDRINKING WATER OR COOKING SHALL BE "LEAD FREE" AS OF JANUARY 1, 2010.IN ORDER TO MEET THE REQUIREMENTS OF THE NATIONAL POLLUTANT DISCHARGEELIMINATION SYSTEM (NPDES) PROGRAM FOR CONSTRUCTION, CONSTRUCTIONCONTRACTORS SHALL INSTALL AND MAINTAIN APPROPRIATE BEST MANAGEMENTPRACTICES (BMPS), AS SHOWN IN THE EROSION CONTROL PLAN AND IN ACCORDANCE WITHTHE SWPPP (STORM WATER POLLUTION PREVENTION PLAN), ON ALL CONSTRUCTIONPROJECTS. BMPS SHALL BE INSTALLED IN ACCORDANCE WITH INDUSTRY RECOMMENDEDSTANDARDS, AND/OR IN ACCORDANCE WITH ANY GENERAL CONSTRUCTION PERMIT ISSUEDBY THE STATE FOR THE PROJECT TO PREVENT ANY DISCHARGES FROM THE PROJECT SITEOR INTO ANY STORM DRAIN FACILITIES. ALL SEDIMENTS, CONSTRUCTION MATERIALS,DEBRIS AND WASTES, AND OTHER POLLUTANTS MUST BE RETAINED ON SITE AND MAY NOTBE TRANSPORTED FROM THE SITE VIA SHEET FLOW, SWALES, AREA DRAINS, NATURALDRAINAGE COURSES, WIND, OR VEHICLE TRACKING. UNDER DIRECTION OF THE ENGINEEROF RECORD, EROSION AND/OR SEDIMENT CONTROL DEVICES SHALL BE MODIFIED ASNEEDED AS THE PROJECT PROGRESSES TO ENSURE EFFECTIVENESS.C0.01 CIVIL NOTESC1.01 DEMOLITION PLANC2.01 GRADING PLANC3.01 STORM DRAIN PLANC4.01 UTILITY PLANC5.01 HORIZONTAL CONTROL, PAVING, STRIPING AND SIGNAGE PLANC6.01 EROSION CONTROL PLANC7.01 CONSTRUCTION DETAILSPERFORATED STORMDRAIN LINENTSGGEXISTING NATURALGAS SERVICETTEXISTINGTELECOMMUNICATIONSLINE / CONDUIT1. FOLLOWING OWNER ACCEPTANCE OF CONSTRUCTION WORK, POST CONSTRUCTIONBEST MANAGEMENT PRACTICE (BMP) MEASURES SHALL BE MAINTAINED BY THEPROPERTY OWNER, INCLUDING BUT NOT LIMITED TO:1.1. ANNUAL INSPECTION, REPLACEMENT, AND/OR SEDIMENTATION REMOVAL OFVEGETATED SWALES, TREATMENT PONDS, AND OTHER SURFACE STORMWATERTREATMENT MEASURES AS REQUIRED WITH AN INCREASED FREQUENCY BASEDON SITE CONDITIONS.1.2. MAINTENANCE SERVICE AGREEMENT(S) OF STORMWATER TREATMENT VAULTS,INLETS, MANHOLES, AND OTHER DEVICES BASED ON MANUFACTURES'RECOMMENDATIONS AND FREQUENCY.1.3. ANNUAL INSPECTION OF PERMEABLE PAVEMENT AND REMOVAL OF SEDIMENT ASNEEDED.1.4. ANNUAL INSPECTION OF STORMWATER INLETS AND MAINTENANCE AS REQUIREDTO CLEAR GRATES AND INLETS OF DEBRIS.1.5. THE PROJECT STORMWATER POLLUTION PREVENTION PLAN (SWPPP) AND WATERQUALITY MANAGEMENT PLAN (WQMP) MAY CONTAIN ADDITIONAL OR MORESTRINGENT MAINTENANCE REQUIREMENTS.2. BMP DETAILS MAY BE FOUND IN APPENDIX H OF THE PROJECT SWPPP DOCUMENT. BMPDETAILS PER CALIFORNIA STORMWATER QUALITY ASSOCIATION (CASQA) AND AREAVAILABLE AT www.casqa.org.3 . FOR PROJECTS GREATER THAN 1 ACRE: THE CONTRACTOR SHALL VERIFY THE STATUSOF THE SWPPP/NOI/WDID PRIOR TO EARTHMOVING ACTIVITIES. A STORMWATERPOLLUTION PREVENTION PLAN (SWPPP) SHALL BE PREPARED AND A NOTICE OF INTENT(NOI) SHALL BE FILED WITH THE STATE WATER RESOURCES CONTROL BOARD (SWRCB)IN ACCORDANCE WITH THE REQUIREMENTS OF CALIFORNIA GENERAL PERMIT FORSTORMWATER DISCHARGES ASSOCIATED WITH CONSTRUCTION ACTIVITY (PERMIT NO.CAS000002) FOR ALL OPERATIONS ASSOCIATED WITH THESE PLANS. THE CONTRACTORSHALL KEEP A COPY OF THE SWPPP ON SITE AND AVAILABLE FOR REVIEW.1. FIRE WATER PIPE, FITTINGS, AND APPURTENANCES SHALL COMPLY WITH NFPA 24INCLUDING BUT NOT LIMITED TO THE FOLLOWING:1.1. FIRE DEPARTMENT CONNECTIONS (FDC) SHALL BE PER NFPA 24-5.9.1.2. FDC LOCATION AND SIGNAGE SHALL BE PER NFPA 24-5.9.5.1. PRIOR TO INSTALLATION, ALL PLANS AND SPECIFICATIONS SHALL BE APPROVED BYGOVERNING AGENCY.2. INSPECTIONS ARE REQUIRED:1) PRIOR TO POURING THRUST BLOCKS2) FOR HYDROSTATIC TESTING3) FOR FLUSH3. INSTALLATION, INSPECTION, AND TESTING SHALL CONFORM TO 2019 NFPA 13 AND 2019NFPA 24.4. PRIVATE FIRE HYDRANTS SHALL BE APPROVED WET BARREL STYLE WITH A MINIMUM OFONE 2 12" AND ONE 4" OUTLET. THE 4" OUTLET SHALL FACE THE FIRE DEPARTMENTACCESS ROAD. ALL OUTLETS SHALL BE PROVIDED WITH NATIONAL STANDARDTHREADS (NST).5. FIRE HYDRANT SUPPLY PIPING SHALL BE A MINIMUM OF SIX INCHES IN DIAMETER. THELOWEST OPERATING NUT SHALL BE MINIMUM OF 18" ABOVE GRADE AND THE FIREHYDRANT FLANGE SHALL BE A MINIMUM OF 2" ABOVE GRADE.6. FIRE HYDRANTS SHALL BE A MINIMUM OF 40 FEET FROM ALL STRUCTURES. A KEYEDGATE VALVE SHALL BE PROVIDED FOR EACH FIRE HYDRANT IN AN ACCESSIBLELOCATION. VALVES SHALL NOT BE LOCATED IN PARKING STALLS.7. ALL PIPES SHALL BE APPROVED FOR USE IN FIRE SERVICE SYSTEMS (CLASS 900 DR-18MINIMUM). CLASS 900 DR-14 PIPES SHALL BE USED WHERE THE PRESSURES MAYEXCEED 150 PSI.8. ALL FERROUS PIPE AND FITTINGS SHALL BE PROTECTED WITH LOOSE 8-MILPOLYETHYLENE TUBE. THE ENDS OF THE TUBE AND ANY SPLICES MADE FOR T's OROTHER PIPING COMPONENTS SHALL BE SEALED WITH 2" TAPE, APPROVED FORUNDERGROUND USE. ALL BOLT JOINTS SHALL BE CLEANED AND THOROUGHLY COATEDWITH ASPHALT OR OTHER CORROSION RETARDING MATERIAL AFTER ASSEMBLY ANDPRIOR TO POLY-TUBE INSTALLATION.9. A BED OF CLEAN FILL SAND SHALL BE PROVIDED ABOVE AND BELOW THE PIPE, AMINIMUM OF 12" ABOVE AND 6" BELOW.10. ALL BOLTS USED FOR UNDERGROUND CONNECTIONS SHALL BE STAINLESS STEEL.11. A MINIMUM OF 30" OF COVER, FROM FINISHED GRADE TO THE TOP OF THE PIPE SHALLBE PROVIDED. WHEN SURFACE LOADS ARE EXPECTED, A MINIMUM OF 36" COVER SHALLBE PROVIDED.12. THRUST BLOCKS, OR OTHER APPROVED METHOD OF THRUST RESTRAINT, SHALL BEPROVIDED WHEREVER PIPE CHANGES DIRECTION.13. THE TRENCH SHALL BE EXCAVATED FOR THRUST BLOCKS AND INSPECTED PRIOR TOPOUR. ALL CORROSION PROTECTION SHALL BE IN PLACE.14. A HYDROSTATIC TEST (200 PSI FOR TWO HOURS OR 50 PSI OVER MAXIMUM STATICPRESSURE, WHICHEVER IS GREATER) SHALL BE PERFORMED. BACKFILL BETWEEN THEJOINTS TO PREVENT MOVEMENT OF THE PIPE.15. THE SYSTEM SHALL BE THOROUGHLY FLUSHED BEFORE CONNECTION IS MADE TOOVERHEAD PIPING. FLOW SHALL BE THROUGH A MINIMUM 4" HOSE PIPE.16. PRIVATE HYDRANTS, SPRINKLER CONTROL VALVES, DETECTOR CHECK ASSEMBLIES,POST INDICATING VALVES AND FIRE DEPARTMENT CONNECTIONS SHALL BE PAINTEDOSHA RED, UNLESS NOTED OTHERWISE.17. THE CONTROL VALVES SHALL BE LOCKED IN THE OPEN POSITION. VALVES SHALL BEMONITORED IF THEY SERVE 6 OR MORE SPRINKLER HEADS.FIRE PROTECTION SYSTEM NOTESXXXXXXXXXXXXXXXSSSSDESCRIPTIONLINE TYPEDAYLIGHT LINESTORM DRAIN LINE(>8" DIAMETER)ABBREVIATIONSGENERAL EROSION AND SEDIMENT CONTROL NOTESDEMOLITION NOTESEARTHWORK NOTESEARTHWORK QUANTITIESVICINITY MAPLEGENDDESCRIPTIONSYMBOLROOF DRAIN POC 5' FROM BUILDINGGAS POC 5' FROM BUILDINGFIRE WATER POC 5' FROM BUILDINGDOMESTIC WATER POC 5' FROM BUILDINGSANITARY SEWER POC 5' FROM BUILDINGSTORM DRAIN MANHOLESANITARY SEWER MANHOLEDRAIN INLETAREA DRAINTRENCH DRAINCLEANOUTBLOW OFFFIRE HYDRANTVALVEPOST INDICATOR VALVE (PIV)/CHECK VALVE(CHK VLV)/FIRE DEPARTMENT CONNECTION (FDC)CHECK VALVE (CHK VLV)FIRE DEPARTMENT CONNECTION (FDC)DOUBLE DETECTOR CHECK (DBL CHK)REDUCED PRESSURE (BFP)POST INDICATOR VALVE (PIV)THRUST BLOCKBENDS, TEE AND CROSSWATER METERLEGAL DESCRIPTIONBASIS OF BEARINGSDATUM STATEMENTBENCHMARKGEOTECHNICAL INFORMATIONFIRE WATER GENERAL NOTES:IMPORTANT NOTICEDEDICATED FIRE ACCESSDIG ALERT NOTICEGENERAL NOTES TO CONTRACTORPOLLUTION PREVENTION NOTESBMP MAINTENANCE NOTESAREA SUMMARYCIVIL SHEET INDEXSITE FIRE FLOW AVAILABLE WATER PRESSURE ADXXLF S=X.XXXXXLF PVCXXLF S=X.XXXXXLF S=X.XXXGBXXLF PVCXXLF PVCcoMDS6"SS8"FW6"SDGAS6"DW12"SDNRDGFWSSCOLUMBIA WAY
ARDIS AVE
IMPERIAL HWYCONGRESSMANSTEVE HORN WAYCARING WAY
APOLLO WAYCENTURY FWYGLENN ANDERSON FWYFOSTER RDSTEWART ANDGRAY RDBELLFLOWER BLVD LAK
E
W
O
O
D
B
L
V
D
BRO
O
K
S
H
I
R
E
A
V
E
DO
W
N
E
Y
A
V
E
ALAMEDA STIMPERIAL HWY105PROJECTLOCATION
xxxxxxxxxxxxxxx
x
xxxxxxxxxxx9897
97 97
97 97 97
97 98
989898979797979796
97 98989
797
969696959696
97 9
6 96
98 98
96 9795 9898WWWWWW
WSSSSSSSSSSSSSSSSSSG G G G G G G G G G G G G G G G G
SSSSSSSS16"SS21"SS21"SS
16"SSSSSScoScoSSSS10"SS
12"SS
12 81"SD
WW W W W W W W
WW W W W W W W W W
12"DW
12"DW
RWRWRWRWRWRWRWRWRWWWW12"DW8"RWWFW6"FWWW
SDSDSDSDSDcoSS
coSDSDSDS
D
S
D
S
D EEEEEEEEESDSDSDSDSDEEEE E
EEEEEE E E E EEEEEEE
EEEEEEEEEEEEEEEEE2"GG
GGGSSSSSSSSSSSSSSSSSSSSSSSSSSSSSS (E) 15" (ABAND)© LPA, Inc.Developed forJob NumberDate PublishedChecked ByScaleRevision Date ARCHITECTURE ENGINEERING INTERIORSLANDSCAPE ARCHITECTURE PLANNING949-261-1001 Office949-260-1190 FaxLPADesignStudios.comSubmittal Date 5301 California Avenue,Suite 100Irvine, California 92617This document and all other project documents,ideas, aesthetics and designs incorporatedtherein are instruments of service. All projectdocuments are copyright protected, are theproperty of LPA, Inc. (LPA) and cannot be lawfullyused in whole or in part for any project or purposeexcept as set forth in the contractual agreementbetween LPA and its Client. The unauthorizeddisclosure and/or use of the project documents(including the creation of derivative works), maygive rise to liability for copyright infringement,unlawful disclosure, use or misappropriation ofproperty rights held by LPA. The unauthorizeduse of the project documents will give rise to therecovery of monetary losses and damagesincluding attorney fees and costs for which theunauthorized user will be held liable.Project documents describe the design intent ofthe work and are not a representation of as-builtor existing conditions. LPA is not responsible forany discrepancies between the project documentsand the existing conditions.DOWNEY SPACE SHUTTLE MUSEUM
COLUMBIA WAY
DOWNEY, CA 90242
CITY OF DOWNEY3055401R.R.02/10/2023SCHEMATIC DESIGN 10/27/2022 50% DESIGN DEVELOPMENT 12/02/2022
100% DESIGN DEVELOPMENT 01/06/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CONSTRUCTION DOCS 08/01/2025
1' = 20"C1.01DEMOLITION PLANN20104001" = 20'DEMOLITION PLAN
xxxxxxxxxxxxxxxx9897
97 97
97 97 97
97 98
989898979797979796
97 98989
797
96969697
96 98
98 96 979898COLUMBIA WAY
SDCOMCOCOCOMSCOCO
WWWWWW
WSSSSSSSSSSSSSSSSSSG G G G G G G G G G G G G G G G G
SSSSSSSS16"SS21"SS21"SS
16"SSSSSScoScoSSSS10"SS
12"SS
81"SD
WW W W W W W W
WW W W W W W W W W
12"DW
12"DW
RWRWRWRWRWRWRWRWRWWWW12"DWWFW6"FWWW
SDSDSDSDSS
coEEEEEEEEESDSDSDSDSDEEEE E
EEEEEE E E E E
EEEEEEEEEEEE2"GG
GGGSSSSSSSSSSSSSSSSSSSSSSSSSSSSSS (E) 15" (ABAND)97.50 FFECOLUMBIA WAY (98.01±)FSJOIN (E)(98.03±)FSJOIN (E)97.10FS96.99FS96.99FS97.06FS96.15FS97.68FS97.61FS1.5%(95.20±)FS(95.40±)FS(96.76±)FSJOIN (E)(96.71±)FSJOIN (E)1.2%(96.98±)FSJOIN (E)(96.94±)FSJOIN (E)(97.16±)FSJOIN (E)(96.1±)FG96.43FS(95.3)FG(96.0)FG(97.02±)FS1.5%97.48FS97.50FFERIDGERIDGE97.48FS97.48FS97.48FS1.2%1.0%97.48FS0.6%97.48FS1.8%97.48FS97.48FS97.32FS1.5%1.5%97.48FS97.25FS97.01FS96.80FS1.5%96.74FS1.5%1.8%20' (E)
UTILITY
EASEMENT
PROPERTY LINE (P/L)RIGHT-OF-WAY (R/W)97.17FS97.91FS97.86FS97.69FS97.40FS97.31FS96.96FS96.87FS96.52FS96.43FS96.13FS96.39FS96.45FS96.70FS97.00FS95.43FS97.04FS96.83FS96.17FS96.00FS95.72FS(95.26)FSJOIN (E)(95.35)FSJOIN (E)(95.34)FSJOIN (E)(95.48)FSJOIN (E)95.33FS95.24FS95.27FS95.49FS95.87FS96.48FS96.83FS96.35FS95.79FS97.48FS1.5%GB (95.30±)FS96.90FS96.89FS96.79FS96.79FS96.69FS96.65FS96.80FS96.76FS97.38FS97.04FS96.75FS96.43FS96.43FS96.90FS96.90FS97.38FS96.43FS97.32FS96.79FS97.38FS95.06FS97.16FS97.09FS96.83FS96.77FS96.51FS96.47FS96.70FS96.79FS97.12FS97.20FS97.54FS97.62FS97.84FS97.78FS97.90FS97.95FS1.5%
1.4%4.4%4.6%GB
1.5%2.1%2.3%2.4%2.1%1.8%1.7%1.7%1.8%4.7%
1.5%4.6%1.8%
1.8%
1.8%
1.8%
1.8%
1.8%
5.0%
5.0%
5.0%5.0%1.8%1.8%1.2%1.8%1.8%1.8%96.36FS95.75FS95.30FS96.24FL96.49FL96.67FL97.36FS97.35FS97.24FS95.62FS95.70FS97.23FS97.20FS96.43FS96.30FS96.29FS96.29FS96.29FS5.0%96.43FL-HP95.65FL95.20FL96.50FL94.73TG95.48TG95.71FL-HP95.50TG95.50TG95.70FL-HP95.50TG95.16FL-HP95.30TG95.10TG95.30TG96.00TG97.31TG97.10TG97.25FS97.37FS96.28TG96.45TG96.48TG96.62TG96.20TG96.30TG96.30TG96.37TG96.50TG96.31TG96.61TG96.70TG96.50FL-HP96.75FL-HP96.75FL-HP5.0%96.50FL-HP96.50FL-HP96.50FL-HP96.50FL-HP97.48FS97.48FS96.91FS97.06FS1.8%1.5%PLANTING AREASEE LANDSCAPE PLAN DETAILS FOR GRADES ADJACENT TO HARDSCAPELEGENDDESCRIPTIONSYMBOLPAAPPROXIMATE LIMIT OF WORKGRADE BREAKSAWCUT (E) PAVEMENT AS NEEDED. SEE DEMOLITION PLANFLOWLINETOP OF SLOPETOE OF SLOPEGBTOSTOEOVERLAND RELEASE© LPA, Inc.Developed forJob NumberDate PublishedChecked ByScaleRevision Date ARCHITECTURE ENGINEERING INTERIORSLANDSCAPE ARCHITECTURE PLANNING949-261-1001 Office949-260-1190 FaxLPADesignStudios.comSubmittal Date 5301 California Avenue,Suite 100Irvine, California 92617This document and all other project documents,ideas, aesthetics and designs incorporatedtherein are instruments of service. All projectdocuments are copyright protected, are theproperty of LPA, Inc. (LPA) and cannot be lawfullyused in whole or in part for any project or purposeexcept as set forth in the contractual agreementbetween LPA and its Client. The unauthorizeddisclosure and/or use of the project documents(including the creation of derivative works), maygive rise to liability for copyright infringement,unlawful disclosure, use or misappropriation ofproperty rights held by LPA. The unauthorizeduse of the project documents will give rise to therecovery of monetary losses and damagesincluding attorney fees and costs for which theunauthorized user will be held liable.Project documents describe the design intent ofthe work and are not a representation of as-builtor existing conditions. LPA is not responsible forany discrepancies between the project documentsand the existing conditions.DOWNEY SPACE SHUTTLE MUSEUM
COLUMBIA WAY
DOWNEY, CA 90242
CITY OF DOWNEY3055401R.R.02/10/2023SCHEMATIC DESIGN 10/27/2022 50% DESIGN DEVELOPMENT 12/02/2022
100% DESIGN DEVELOPMENT 01/06/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CONSTRUCTION DOCS 08/01/2025
1' = 20"C2.01GRADING PLANN20104001" = 20'GRADING PLAN
xxxxxxxxxxxxxxxx9897
97 97
97 97 97
97 98
989898979797979796
97 98989
797
96969697
96 98
98 96 979898WWWWWW
WSSSSSSSSSSSSSSSSSSG G G G G G G G G G G G G G G G G
SSSSSSSS16"SS21"SS21"SS
16"SSSSSScoScoSSSS10"SS
12"SS
12"SS
81"SD
WW W W W W W
WW W W W W W W W W
12"DW
12"DW
RWRWRWRWRWRWRWRWRWWWW12"DW8"RWWFW6"FWWW
SDSDSDSDSS
coEEEEEEEEESDSDSDSDSDEEEE E
EEEEEE E E E E
EEEEEEEEEEEE2"GG
GGGSSSSSSSSSSSSSSSSSSSSSSSSSSSSSS (E) 15" (ABAND)COMCOCOCOMSCOCOCOLUMBIA WAY 12"SD12"SD
SDRD6" RD POC
96.00 INV
RDRDRDRDRDRD6" RD POC
96.00 INV
6" RD POC
96.00 INV
6" RD POC
96.00 INV
6" RD POC
96.00 INV
6" RD POC
96.00 INV
6" RD POC
96.00 INV
90.00INV2912"SD90.91
INV90.94INV S=0.005 S=0.00592.21INV92.20INV92.02INV91.84INV91.66INV91.48 INV
91.12 INV
18"SD90.00
INV
89.25±
INV 27 S=0.02092.50INV2492.32INV2492.14INV2491.96INV2491.78INV2493.48INV2493.28INV2492.97INV93.19INV93.13 INV24
91.25 INV
91.32 INV
91.62 INV 2423 4"SD
224"SD91.85
INV4"SD
92.65INV2492.02INV2492.50
INV 244"SD4"SD92.60INV2490.83
INV
92.10INV2490.55
INV 92.60INV2490.20
INV 92.42INV2592.90INV2791.99
INV92.02INV4" RD POC96.00 INVRD92.73INV2892.51INV90.00INV92.05 INV 2812"SD92.46INV92.75INV2692.42INV2894.10INV244"SD
12"SD92.10INV2493.10INV2491.32
INV
90.80 INV23 23232291.93INV24STORM DRAIN CONSTRUCTION NOTESSUPPLY AND INSTALL STORM DRAIN CLEAN OUT PER DETAIL 01 SHEET C7.01.SUPPLY AND INSTALL 4" RISER WITH NDS 9"X9" LOW PROFILE HOUSING ADAPTER AND A9"X9" ATRIUM GRATE (BLACK) OR EQUIVALENT. SEE DETAIL __ SHEET ____.SUPPLY AND INSTALL PVC SDR35 STORM DRAIN PIPE. SIZE PER PLAN. PIPE TRENCH PERDETAIL 02 SHEET C7.01.20ROOF DRAIN POINT OF CONNECTION. SUPPLY AND INSTALL ROOF DRAIN LATERALSTUBBED 5 FT. FROM FACE OF BUILDING S=0.020 MIN. PLUG AND MARK END. COORDINATEEXACT LOCATION WITH PLUMBING PLANS.CONNECT TO EXISTING STORM DRAIN. CONTRACTOR TO VERIFY ELEVATION OF EXISTINGPIPE AND NOTIFY ENGINEER OF ANY DISCREPANCIES PRIOR TO CONSTRUCTION.NOTES:1. UTILITIES TO CROSS OVER OR UNDER OTHER UTILITIES TO MAINTAIN 12" MINIMUMCLEARANCE AT UTILITY CROSSINGS, UNLESS NOTED OTHERWISE.2. CONTRACTOR SHALL VERIFY SIZE AND LOCATION (HORIZONTAL AND VERTICAL) OFEXISTING CROSSING AND JOINING UTILITIES PRIOR TO CONSTRUCTION AND IMMEDIATELYNOTIFY THE ENGINEER OF ANY CONFLICT.3. CONTRACTOR SHALL CONSTRUCT GRAVITY UTILITIES (SEWER AND STORM DRAIN) BEFOREOTHER UTILITIES. CONSTRUCTION OF THESE GRAVITY UTILITIES TO START FROM THEDOWNSTREAM ENDS.4. EXISTING UTILITIES ARE COMPILED BASED ON PREVIOUS BASE FILES, FIELD SURVEY ANDFIELD VERIFICATION. POTHOLING IS RECOMMENDED TO VERIFY ANY AND ALL UTILITIESKNOWN OR UNKNOWN WHICH MAY BE IN CONFLICT WITH PROPOSED CONSTRUCTION.5. PRIOR TO THE REMOVAL OF ANY WET OR DRY UTILITY LINES, THE CONTRACTOR SHALLCONFIRM WITH OWNER REPRESENTATIVE WHETHER THESE UTILITY LINES ARE STILLACTIVE OR NOT. IMMEDIATELY NOTIFY THE ENGINEER OF ANY CONFLICT.6. CONTRACTOR TO ADJUST TO FINISHED GRADE ALL EXISTING UTILITY BOXES, STORMDRAIN CLEANOUT COVERS, PULL BOXES AND VALVE COVERS NOT SPECIFICALLY SHOWNWITHIN THE LIMITS OF WORK.7. SEE DETAIL __ SHEET __ FOR STORM DRAIN UTILITY TRENCHING AND BACKFILL.8. SAWCUT, REMOVE AND REPLACE EXISTING CURB AS REQUIRED FOR TRENCHING. MATCHEXISTING CURB.9. ALL PRECAST DRAIN INLETS TO HAVE AN APPROVED "NO DUMPING DRAINS TO ____" 3" X514" ROUNDED CORNERED RECTANGLES STYLE #NDO OR 4" DIAMETER ROUND STYLE #SDOABRASION AND UV RESISTANT DURACAST STYLE MARKER BY DAS MANUFACTURING OREQUIVALENT APPLIED TO THE CONCRETE COLLAR AROUND DRAIN INLET USING RAPID SETURETHANE ADHESIVE OR QUICKSTIK EPOXY PUTTY ADHESIVE PER MANUFACTURER'SRECOMMENDATIONS AND SPECIFICATIONS. http://www.dasmanufacturing.com/product_guide.htmlKEYNOTESUPPLY AND INSTALL 12"x12" PRECAST DRAIN INLET.DESCRIPTIONRD2122232425 SUPPLY AND INSTALL DRAIN INLET PER DETAIL 10 SHEET C7.01.26SUPPLY AND INSTALL HDPE STORM DRAIN PIPE. SIZE PER PLAN. PIPE TRENCH PER DETAIL02 SHEET C7.01.2728SUPPLY AND INSTALL 3.5'X8'X16' OLDCASTLE STORMCAPTURE VAULTS.29CONNECT TO EXISTING PRECAST DRAIN INLET. CONTRACTOR TO VERIFY ELEVATION OFEXISTING DRAIN INLET INVERT AND NOTIFY ENGINEER OF ANY DISCREPANCIES PRIOR TOCONSTRUCTION.SUPPLY AND INSTALL 18"x18" PRECAST DRAIN INLET.© LPA, Inc.Developed forJob NumberDate PublishedChecked ByScaleRevision Date ARCHITECTURE ENGINEERING INTERIORSLANDSCAPE ARCHITECTURE PLANNING949-261-1001 Office949-260-1190 FaxLPADesignStudios.comSubmittal Date 5301 California Avenue,Suite 100Irvine, California 92617This document and all other project documents,ideas, aesthetics and designs incorporatedtherein are instruments of service. All projectdocuments are copyright protected, are theproperty of LPA, Inc. (LPA) and cannot be lawfullyused in whole or in part for any project or purposeexcept as set forth in the contractual agreementbetween LPA and its Client. The unauthorizeddisclosure and/or use of the project documents(including the creation of derivative works), maygive rise to liability for copyright infringement,unlawful disclosure, use or misappropriation ofproperty rights held by LPA. The unauthorizeduse of the project documents will give rise to therecovery of monetary losses and damagesincluding attorney fees and costs for which theunauthorized user will be held liable.Project documents describe the design intent ofthe work and are not a representation of as-builtor existing conditions. LPA is not responsible forany discrepancies between the project documentsand the existing conditions.DOWNEY SPACE SHUTTLE MUSEUM
COLUMBIA WAY
DOWNEY, CA 90242
CITY OF DOWNEY3055401R.R.02/10/2023SCHEMATIC DESIGN 10/27/2022 50% DESIGN DEVELOPMENT 12/02/2022
100% DESIGN DEVELOPMENT 01/06/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CONSTRUCTION DOCS 08/01/2025
1" = 20'C3.01STORM DRAIN PLANN20104001" = 20'STORM DRAIN PLAN
xxxxxxxxxxxxxxxx98979797979797979898
9898979797979796
97 98989
797
96969697
96 98
98 96 979898WWWWWW
WSSSSSSSSSSSSSSSSSSG G G G G G G G G G G G G G G G G SSSSSSSS16"SS21"SS21"SS 16"SSSSSScoScoSSSS10"SS 12"SS
12"SS81"SDWWWWWWWWWWWWWW W W W12"DW 12"DW RWRWRWRWRWRWRWRWRWWWW12"DW8"RWWFW6"FWWW
SDSDSDSDSS
coEEEEEEEEESDSDSDSDSDEEEE E
EEEEEE E E E E
EEEEEEEEEEEE2"GGGGG SSSSSSSSSSSSSSSSSSSSSSSSSSSSSS (E) 15" (ABAND)COLUMBIA WAY SD4"SSCOM4" SS POC
SS2" DW POC
W3"DWCOLUMBIA WAY81 LFS=0.024"SS100 LFS=0.021" DW POCW1.5"DW4" SS POC95.50 INVSSCOCOCO4" S
SXXX.XXRIM87.83 INV 4" IN NORTH87.83 INV X" IN EAST87.73 INV 8" OUT4291.42INV 6"4089.46INV 4"40414"SS M51505041S97.50FFE97.50 FFECOCO92.10INV 4"91.05INV4089.10INV4091.71INV 4088.72INV40SUPPLY AND INSTALL PRECAST CONCRETE SEWER MANHOLE PER SPPWC 200-4.SUPPLY AND INSTALL SEWER CLEANOUT PER DETAIL 01 SHEET C7.01.SEWER SERVICE POINT OF CONNECTION. SUPPLY AND INSTALL SEWER SERVICE LATERALSTUBBED 5 FT. FROM FACE-OF-BUILDING WITH A SLOPE 0.020 MIN. PLUG AND MARK END.COORDINATE EXACT LOCATION WITH PLUMBING PLANS.SEWER CONSTRUCTION NOTES:SUPPLY AND INSTALL PVC SDR 35 (ASTM D 3034). SIZE AS SHOWN. PIPE TRENCH PERDETAIL 03 SHEET C7.01.WATER CONSTRUCTION NOTES:SUPPLY AND INSTALL WATER SERVICE LATERAL TO 5' OUTSIDE FACE-OF-BUILDING. SIZEAS SHOWN. PLUG AND MARK END. VERIFY WATER CONNECTION WITH PLUMBING PLANS.401. UTILITIES TO CROSS OVER OR UNDER OTHER UTILITIES TO MAINTAIN 12" MINIMUMCLEARANCE AT UTILITY CROSSINGS, UNLESS NOTED OTHERWISE. SANITARY SEWER TOCROSS UNDER POTABLE WATER.2. CONTRACTOR SHALL VERIFY SIZE AND LOCATION (HORIZONTAL AND VERTICAL) OFEXISTING CROSSING AND JOINING UTILITIES PRIOR TO CONSTRUCTION AND IMMEDIATELYNOTIFY THE ENGINEER OF ANY CONFLICT.3. CONTRACTOR SHALL CONSTRUCT GRAVITY UTILITIES (SEWER AND STORM DRAIN) BEFOREOTHER UTILITIES. CONSTRUCTION OF THESE GRAVITY UTILITIES TO START FROM THEDOWNSTREAM ENDS.4. EXISTING UTILITIES ARE COMPILED BASED ON PREVIOUS BASE FILES, FIELD SURVEY ANDFIELD VERIFICATION. POTHOLING IS RECOMMENDED TO VERIFY ANY AND ALL UTILITIESKNOWN OR UNKNOWN WHICH MAY BE IN CONFLICT WITH PROPOSED CONSTRUCTION.5. PRIOR TO THE REMOVAL OF ANY WET OR DRY UTILITY LINES, THE CONTRACTOR SHALLCONFIRM WITH OWNER REPRESENTATIVE WHETHER THESE UTILITY LINES ARE STILLACTIVE OR NOT. IMMEDIATELY NOTIFY THE ENGINEER OF ANY CONFLICT.6. CONTRACTOR TO ADJUST TO FINISH GRADE ALL EXISTING UTILITY BOXES, SEWERCLEANOUT COVERS, PULL BOXES AND VALVE COVERS NOT SPECIFICALLY SHOWN WITHINTHE LIMITS OF WORK.7. SEE DETAIL __ SHEET __ FOR ONSITE SEWER UTILITY TRENCHING AND BACKFILL.8. SEE DETAIL __ SHEET __ FOR ONSITE WATER UTILITY TRENCHING AND BACKFILL.9. SAWCUT, REMOVE AND REPLACE EXISTING CURB AS REQUIRED FOR TRENCHING. MATCHEXISTING CURB. CONSTRUCTION NOTES:504142SSWKEYNOTEDESCRIPTIONSUPPLY AND INSTALL PVC SCH 80 WITH 30" MIN. COVER AND 36" MIN COVER WHERESURFACE LOADS ARE EXPECTED. TRENCHING AND BACKFILL PER DETAIL 04 SHEET C7.01.51X52X53X© LPA, Inc.Developed forJob NumberDate PublishedChecked ByScaleRevision Date ARCHITECTURE ENGINEERING INTERIORSLANDSCAPE ARCHITECTURE PLANNING949-261-1001 Office949-260-1190 FaxLPADesignStudios.comSubmittal Date 5301 California Avenue,Suite 100Irvine, California 92617This document and all other project documents,ideas, aesthetics and designs incorporatedtherein are instruments of service. All projectdocuments are copyright protected, are theproperty of LPA, Inc. (LPA) and cannot be lawfullyused in whole or in part for any project or purposeexcept as set forth in the contractual agreementbetween LPA and its Client. The unauthorizeddisclosure and/or use of the project documents(including the creation of derivative works), maygive rise to liability for copyright infringement,unlawful disclosure, use or misappropriation ofproperty rights held by LPA. The unauthorizeduse of the project documents will give rise to therecovery of monetary losses and damagesincluding attorney fees and costs for which theunauthorized user will be held liable.Project documents describe the design intent ofthe work and are not a representation of as-builtor existing conditions. LPA is not responsible forany discrepancies between the project documentsand the existing conditions.DOWNEY SPACE SHUTTLE MUSEUM
COLUMBIA WAY
DOWNEY, CA 90242
CITY OF DOWNEY3055401R.R.02/10/2023SCHEMATIC DESIGN 10/27/2022 50% DESIGN DEVELOPMENT 12/02/2022
100% DESIGN DEVELOPMENT 01/06/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CONSTRUCTION DOCS 08/01/2025
1' = 20"C4.01UTILITY PLANN20104001" = 20'UTILITY PLAN
xxxxxxxxxxxxxxxx9897
97 97
97 97 97
97 98
989898979797979796
97 98989
797
96969697
96 98
98 96 979898COLUMBIA WAY
M97.50FFE97.50 FFE3030303030313031313131COLUMBIA WAY
GRIDLINES A & 9N 1,792,923.2841E 6,521,272.1282GRIDLINES E & 9N 1,793,010.6198E 6,521,278.7097GRIDLINES H & 12N 1,793,103.2419E 6,521,148.6041GRIDLINES F & 12N 1,793,051.3113E 6,521,132.4199PAVING NOTES:SYMBOLPAVING LEGENDDESCRIPTIONVEHICULAR CONCRETE PAVEMENT5.5" PCC OVER 4" CL II AB PER GEOTECHNICAL ENGINEER'SRECOMMENDATION.PLANTING AREASEE LANDSCAPE PLANS.PA1. SEE LANDSCAPE PLANS FOR PAVERS, LOCATION AND TYPE OF CONCRETE WALKSAND HARDSCAPE INCLUDING DETAILS FOR CONCRETE FINISHES, CONTROL JOINTSAND EXPANSION JOINTS.2. VERIFY ALL VEHICULAR AND NON-VEHICULAR LIMITS WITH LANDSCAPE PLANS. CONSTRUCTION NOTES:DESCRIPTIONKEYNOTESTRIPING & SIGNAGE LEGEND4" WIDE WHITE STRIPE AT 45° ANGLE AT 3' SPACING OC.DESCRIPTIONSYMBOLSIGN PER ARCHITECTURAL SIGNAGE PLAN, UNLESS NOTED OTHERWISE.70FIRE ACCESS. PAINT CURB RED PER DETAIL __, SHEET C_.__.STRIPING NOTES1. ALL EXISTING STRIPING AND MARKINGS TO REMAIN UNLESS OTHERWISE NOTED.CONFLICTS BETWEEN EXISTING AND PROPOSED SHALL BE RESOLVED BY THEENGINEER.2. REMOVAL OF EXISTING STRIPING AND PAVEMENT MARKINGS SHALL BEACCOMPLISHED BY WET SANDBLASTING OR OTHER APPROVED GRINDING METHODPRIOR TO INSTALLATION OF NEW STRIPING. ALL CONFLICTING STRIPING, PAVEMENTMARKINGS, AND RAISED PAVEMENT MARKERS SHALL BE REMOVED.3. PAVEMENT THAT IS DAMAGED DUE TO THE REMOVAL OF MARKERS OR STRIPINGSHALL BE REPAIRED TO THE SATISFACTION OF THE OWNER.FAPEDESTRIAN CONCRETE PAVEMENT4" PCC OVER 4" CL II AB PER GEOTECHNICAL ENGINEER'SRECOMMENDATION.-SEE SHEET C0.01 FOR BASIS OF BEARINGS.-SEE SHEET C0.01 FOR BENCHMARK.THIS HORIZONTAL CONTROL PLAN ESTABLISHES THE FOLLOWING TO BE USED AS BASECONTROL FOR CONSTRUCTION STAKING.1. PRIOR TO STAKING ANY BUILDING STRUCTURE, SURVEYOR SHALL VERIFY THAT THEGRIDS SHOWN ON THIS PLAN MATCHES THE ARCHITECTURAL & STRUCTURAL PLANS.2. TWO COORDINATES ARE PROVIDED TO ESTABLISH THE BUILDING GRID. SEEARCHITECTURAL AND STRUCTURAL PLANS FOR FINAL BUILDING DIMENSIONS.3. IF ANY DISCREPANCIES ARE FOUND DURING CONSTRUCTION STAKING NOTIFY CIVILENGINEER IMMEDIATELY.4. SEE LANDSCAPE PLANS FOR DETAILED HARDSCAPE DIMENSIONS.5. SEE LANDSCAPE PLANS FOR LOCATION AND TYPE OF CONCRETE WALKS ANDHARDSCAPE INCLUDING DETAILS FOR CONCRETE FINISHES, CONTROL JOINTS ANDEXPANSION JOINTS.6. SEE PAVING AND STRIPING PLANS FOR LOCATION AND TYPE OF PAVING AND STRIPING.HORIZONTAL CONTROL NOTES:BENCHMARKBASIS OF BEARINGS30311' = 20"C5.01HORIZONTAL CONTROL,PAVING, AND STRIPINGPLANN20104001" = 20'HORIZONTAL CONTROL, PAVING, AND STRIPING PLAN© LPA, Inc.Developed forJob NumberDate PublishedChecked ByScaleRevision Date ARCHITECTURE ENGINEERING INTERIORSLANDSCAPE ARCHITECTURE PLANNING949-261-1001 Office949-260-1190 FaxLPADesignStudios.comSubmittal Date 5301 California Avenue,Suite 100Irvine, California 92617This document and all other project documents,ideas, aesthetics and designs incorporatedtherein are instruments of service. All projectdocuments are copyright protected, are theproperty of LPA, Inc. (LPA) and cannot be lawfullyused in whole or in part for any project or purposeexcept as set forth in the contractual agreementbetween LPA and its Client. The unauthorizeddisclosure and/or use of the project documents(including the creation of derivative works), maygive rise to liability for copyright infringement,unlawful disclosure, use or misappropriation ofproperty rights held by LPA. The unauthorizeduse of the project documents will give rise to therecovery of monetary losses and damagesincluding attorney fees and costs for which theunauthorized user will be held liable.Project documents describe the design intent ofthe work and are not a representation of as-builtor existing conditions. LPA is not responsible forany discrepancies between the project documentsand the existing conditions.DOWNEY SPACE SHUTTLE MUSEUM
COLUMBIA WAY
DOWNEY, CA 90242
CITY OF DOWNEY3055401R.R.02/10/2023SCHEMATIC DESIGN 10/27/2022 50% DESIGN DEVELOPMENT 12/02/2022
100% DESIGN DEVELOPMENT 01/06/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CONSTRUCTION DOCS 08/01/2025
xxxxxxxxxxxxxxxx9897
97 97
97 97 97
97 98
989898979797979796
97 98989
797
96969697
96 98
98 96 979898WWWWWW
WSSSSSSSSSSSSSSSSSSG G G G G G G G G G G G G G G G G
SSSSSSSS16"SS21"SS21"SS
16"SSSSSScoScoSSSS10"SS
12"SS
12"SS
81"SD
WW W W W W W
WW W W W W W W W W
12"DW
12"DW
RWRWRWRWRWRWRWRWRWWWW12"DW8"RWWFW6"FWWW
SDSDSDSDSS
coEEEEEEEEESDSDSDSDSDEEEE E
EEEEEE E E E E
EEEEEEEEEEEE2"GG
GGGSSSSSSSSSSSSSSSSSSSSSSSSSSSSSS (E) 15" (ABAND)COLUMBIA WAY
SDCOLUMBIA WAY
GRAVEL BAGS AND/OR SANDBAGS PER BMP KEYNOTESLEGENDDESCRIPTIONSYMBOLFIBER ROLLEROSION CONTROL NOTES-SEE SHEET C0.01 FOR EROSION AND SEDIMENT CONTROL NOTES.-SEE SHEET C0.01 FOR BMP MAINTENANCE NOTES.-ALL BMPS PER CALIFORNIA STORMWATER QUALITY ASSOCIATION (CASQA)(UNLESS NOTEDOTHERWISE) AND ARE AVAILABLE AT www.casqa.org.-BMPS "NOT" CALLED OUT PER PLAN, ARE SHOWN FOR REFERENCE AS BMP OPTIONS PER QSP(QUALIFIED SWPPP PRACTITIONER) FIELD RECOMMENDATIONS.-AT THE COMPLETION OF PROJECT, CONTRACTOR SHALL REMOVE ALL CONSTRUCTION BMPSFROM SITE AND DISPOSE IN A LEGAL MANNER.WASTE MANAGEMENT AND MATERIALSPOLLUTION CONTROL BMPs:SE-1, SILT FENCEEROSION CONTROL BMPs:EC-1, SCHEDULINGEC-4, HYDROSEEDINGEC-6, STRAW MULCHEC-7, GEOTEXTILES AND MATSSE-5, FIBER ROLLSSE-7, STREET SWEEPING AND VACUUMINGSE-8, SANDBAG BARRIERSE-10, STORM DRAIN INLET PROTECTIONTC-1, STABILIZED CONSTRUCTION ENTRANCE/EXITTC-2, STABILIZED CONSTRUCTION ROADWAYTC-3, ENTRANCE/OUTLET TIRE WASHNS-1, WATER CONSERVATION PRACTICESNS-3, PAVING AND GRINDING OPERATIONSWM-1, MATERIAL DELIVERY AND STORAGEWM-3, STOCKPILE MANAGEMENTWM-5, SOLID WASTE MANAGEMENTWM-7, CONTAMINATED SOIL MANAGEMENTWM-8, CONCRETE WASTE MANAGEMENTWM-9, SANITARY/SEPTIC WASTE MANAGEMENTTRACKING CONTROL BMPs:SEDIMENT CONTROL BMPs:APPROXIMATE LIMIT OF GRADINGFLOW DIRECTIONSILT FENCEE1E4E6E7S1S5S7S8S10T1T2T3N1N3W1W3W5W7W8W9WM-2, MATERIAL USEW2WM-6, HAZARDOUS WASTE MANAGEMENTW6DESCRIPTIONKEYNOTEEC-3, HYDRAULIC MULCHE3EC-5, SOIL BINDERSE5EC-8, WOOD MULCHINGE8EC-15, SOIL PREPARATION/ROUGHENINGE15EC-16, NON-VEGETATIVE STABILIZATIONE16SE-6, GRAVEL BAG BERMS6SE-12, TEMPORARY SILT DIKES12WIND EROSION CONTROL BMPs:WE-1, WIND EROSION CONTROLWEEC-2, PRESERVATION OF EXISTING VEGETATIONE2NS-6, ILLICIT CONNECTION/DISCHARGEN6NS-7, POTABLE WATER/IRRIGATIONNS-8, VEHICLE AND EQUIPMENT CLEANINGNS-9, VEHICLE AND EQUIPMENT FUELINGN7N8N9NS-10, VEHICLE AND EQUIPMENT MAINTENANCENS-12, CONCRETE CURINGN10N12NS-13, CONCRETE FINISHINGN13WM-4, SPILL PREVENTION AND CONTROLW4SC-10, NON-STORMWATER DISCHARGESNON-STORMWATER MANAGEMENT CONTROL BMPs:SC10© LPA, Inc.Developed forJob NumberDate PublishedChecked ByScaleRevision Date ARCHITECTURE ENGINEERING INTERIORSLANDSCAPE ARCHITECTURE PLANNING949-261-1001 Office949-260-1190 FaxLPADesignStudios.comSubmittal Date 5301 California Avenue,Suite 100Irvine, California 92617This document and all other project documents,ideas, aesthetics and designs incorporatedtherein are instruments of service. All projectdocuments are copyright protected, are theproperty of LPA, Inc. (LPA) and cannot be lawfullyused in whole or in part for any project or purposeexcept as set forth in the contractual agreementbetween LPA and its Client. The unauthorizeddisclosure and/or use of the project documents(including the creation of derivative works), maygive rise to liability for copyright infringement,unlawful disclosure, use or misappropriation ofproperty rights held by LPA. The unauthorizeduse of the project documents will give rise to therecovery of monetary losses and damagesincluding attorney fees and costs for which theunauthorized user will be held liable.Project documents describe the design intent ofthe work and are not a representation of as-builtor existing conditions. LPA is not responsible forany discrepancies between the project documentsand the existing conditions.DOWNEY SPACE SHUTTLE MUSEUM
COLUMBIA WAY
DOWNEY, CA 90242
CITY OF DOWNEY3055401R.R.02/10/2023SCHEMATIC DESIGN 10/27/2022 50% DESIGN DEVELOPMENT 12/02/2022
100% DESIGN DEVELOPMENT 01/06/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CONSTRUCTION DOCS 08/01/2025
1' = 20"C6.01EROSION CONTROLPLANN20104001" = 20'EROSION CONTROL PLAN
© LPA, Inc.Developed forJob NumberDate PublishedChecked ByScaleRevision Date ARCHITECTURE ENGINEERING INTERIORSLANDSCAPE ARCHITECTURE PLANNING949-261-1001 Office949-260-1190 FaxLPADesignStudios.comSubmittal Date 5301 California Avenue,Suite 100Irvine, California 92617This document and all other project documents,ideas, aesthetics and designs incorporatedtherein are instruments of service. All projectdocuments are copyright protected, are theproperty of LPA, Inc. (LPA) and cannot be lawfullyused in whole or in part for any project or purposeexcept as set forth in the contractual agreementbetween LPA and its Client. The unauthorizeddisclosure and/or use of the project documents(including the creation of derivative works), maygive rise to liability for copyright infringement,unlawful disclosure, use or misappropriation ofproperty rights held by LPA. The unauthorizeduse of the project documents will give rise to therecovery of monetary losses and damagesincluding attorney fees and costs for which theunauthorized user will be held liable.Project documents describe the design intent ofthe work and are not a representation of as-builtor existing conditions. LPA is not responsible forany discrepancies between the project documentsand the existing conditions.DOWNEY SPACE SHUTTLE MUSEUM
COLUMBIA WAY
DOWNEY, CA 90242
CITY OF DOWNEY3055401R.R.02/10/2023SCHEMATIC DESIGN 10/27/2022 50% DESIGN DEVELOPMENT 12/02/2022
100% DESIGN DEVELOPMENT 01/06/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CONSTRUCTION DOCS 08/01/2025
AS SHOWNC7.01CONSTRUCTIONDETAILSNTS02010806070504LPA9" SQUARE BLACK ATRIUM GRATE. NDSPART NO. 981 OR APPROVED EQUAL01TG ELEVATION PER PLAN0203WYE FITTING05INVERT ELEVATION PER PLAN06079" NDS PART NO. 930 AND 1243 ORAPPROVED EQUAL03PLUG IF AT END OF RUN08044" PVC SDR 35 RISERSTORM DRAIN PER PLAN0109MATERIAL PER LANDSCAPE PLANS10GRATE RIM FLUSH WITH FINISHED GRADEUNLESS NOTED OTHERWISE10099" SQUARE ATRIUM PLANTER DRAINNTSCLEANOUTLPA04TEXT"SEWER" OR "STORM"45° 45°FLOWFLOWZURN ZN-1400-HD-SM OR APPROVED EQUAL01PIPE SIZE PER PLAN05CLEANOUT LID WITH "SEWER" OR "STORM"0203SOLVENT WELD X F.I.P.T. COUPLING WITHM.I.P.T. PLUG WITH MALE SQUARE NUT.WYE FITTING AT LINE CLEANOUT,45° ELBOW AT TERMINAL CLEANOUT06BROOKS 1-RT CLEANOUT OR APPROVEDEQUAL04050506TYPE 11"06NOTES:·CLEANOUT TYPE 1 TO BE INSTALLED IN ALL CONCRETE PAVEMENT AND PEDESTRIANHARDSCAPE AREAS. LID SHALL BE INSTALLED FLUSH WITH FINISHED SURFACE. PROVIDEPCC COLLAR BELOW HARDSCAPE PER MANUFACTURES REQUIREMENTS.·CLEANOUT TYPE 2 TO BE INSTALLED IN ASPHALT PAVEMENT AND PLANTED AREAS.CLEANOUT RIM TO BE INSTALLED FLUSH WITH FINISHED SURFACE OF AC PAVING OR 1"ABOVE FINISHED GRADE IN PLANTER AREAS AS APPLIES.TYPE 2TEXT"SEWER" OR "STORM"FLUSH01020203FLUSHNTSCONCRETE PAVEMENTEQ.EQ.
VARIESNOTES:·REFER TO LANDSCAPE DRAWINGS FOR COLOR, FINISH, PATTERN, TEXTURE, CONTROLJOINTS, EXPANSION JOINTS, AND THICKENED EDGE.·CONCRETE DOWELING PER LANDSCAPE DRAWINGS AND PROJECT GEOTECHNICALREPORT RECOMMENDATIONS.·DO NOT ALLOW CONCRETE OVER-POUR INTO ADJACENT PLANTERS.·MINIMUM CONCRETE STRENGTH PER SPECIFICATION SECTION 321313.LPACONCRETE PAVINGPEDESTRIAN: 4" THICKVEHICULAR: 5.5" THICK0103PEDESTRIAN: #X @ XX" OC EACH WAYVEHICULAR: #X @ XX" OC EACH WAY0202030104SUBGRADE COMPACTED PER PROJECTGEOTECHNICAL REPORT04COMPACTED BASE COURSE PERGEOTECHNICAL REPORT (WHEREOCCURS).NTSFIRE LANE CURB PAINTINGCURB & GUTTERVERTICAL CURBFLUSH CURBCURBS SHALL BE PAINTEDOSHA SAFETY REDLEGENDNO
P
A
R
K
I
NG
-
F
I
R
E
L
A
N
E
NO
P
A
R
K
I
NG
-
F
I
R
E
L
A
N
ENO PARKING - FIRE LANELPAWORDS TO BE STENCILED ON CURB ASSHOWN ABOVE3" HIGH WHITE PAINTED STENCILED(3/4" STROKE) LETTERSSTENCILING AT EVERY 25 FEET ONCENTER OR PORTION THEREOFNTSPIPE TRENCH - SEWERNOTES:1.ALL PIPE SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH ASTM D2321, "STANDARDPRACTICE FOR UNDERGROUND INSTALLATION OF THERMOPLASTIC PIPE FOR SEWERS ANDOTHER GRAVITY FLOW APPLICATIONS", LATEST EDITION.2.IF UNSTABLE FOUNDATION SOIL IS ENCOUNTERED, THE GEOTECHNICAL FIELD INSPECTORSHALL DETERMINE OVEREXCAVATION DEPTH AND FOUNDATION RE-FILL MATERIAL.3.CONTRACTOR SHALL PROVIDE HAND EXCAVATED "BELL HOLE" FOR EACH PIPE JOINT SOTHAT THE WEIGHT OF PIPE DOES NOT BEAR ON THE BELL. CONTRACTOR SHALL RE-FILLAND HAND-TAMP EACH "BELL HOLE" PRIOR TO COMPLETING THE PLACEMENT OF PIPEBEDDING.4.MEASURES SHOULD BE TAKEN TO PREVENT MIGRATION OF NATIVE FINES INTO BACKFILLMATERIAL WHEN REQUIRED BY GEOTECHNICAL REPORT. FILTER FABRIC IF USED SHALLSATISFY THE REQUIREMENTS FOR A TYPE 180N, NONWOVEN GEOTEXTILE PER SSPWC213-2 (LATEST EDITION).6"MIN6"MIN6" MIN
12"
MIN REFER TO PAVING PLANFOR PAVEMENT SECTIONADJACENTPAVINGPIPE SIZEPER PLANSAS REQUIRED (VARIES)FINAL BACKFILL.RELATIVECOMPACTION PERGEOTECHNICALREPORT.PIPE ZONE- 3/4"CRUSHED ROCKBEDDING MATERIALPER SSPWC TABLE200-1.2.1(A).MECHANICALCOMPACTION PERSSPWC 306-12.12" MIN
FOUNDATIONLPA12"TYPDETECTABLEWARNING TAPE PERSPECIFICATIONSNTSPIPE TRENCH - STORM DRAINNOTES:1.ALL PIPE SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH ASTM D2321, "STANDARDPRACTICE FOR UNDERGROUND INSTALLATION OF THERMOPLASTIC PIPE FOR SEWERS ANDOTHER GRAVITY FLOW APPLICATIONS", LATEST EDITION.2.IF UNSTABLE FOUNDATION SOIL IS ENCOUNTERED, THE GEOTECHNICAL FIELD INSPECTORSHALL DETERMINE OVEREXCAVATION DEPTH AND FOUNDATION RE-FILL MATERIAL.3.CONTRACTOR SHALL PROVIDE HAND EXCAVATED "BELL HOLE" FOR EACH PIPE JOINT SOTHAT THE WEIGHT OF PIPE DOES NOT BEAR ON THE BELL. CONTRACTOR SHALL RE-FILLAND HAND-TAMP EACH "BELL HOLE" PRIOR TO COMPLETING THE PLACEMENT OF PIPEBEDDING.4.MEASURES SHOULD BE TAKEN TO PREVENT MIGRATION OF NATIVE FINES INTO BACKFILLMATERIAL WHEN REQUIRED BY GEOTECHNICAL REPORT. FILTER FABRIC IF USED SHALLSATISFY THE REQUIREMENTS FOR A TYPE 180N, NONWOVEN GEOTEXTILE PER SSPWC213-2 (LATEST EDITION).6"MIN6"MIN6" MIN
12"
MIN REFER TO PAVING PLANFOR PAVEMENT SECTIONADJACENTPAVINGPIPE SIZEPER PLANSAS REQUIRED (VARIES)FINAL BACKFILL.RELATIVECOMPACTION PERGEOTECHNICALREPORT.PIPE ZONE- 3/4"CRUSHED ROCKBEDDING MATERIALPER SSPWC TABLE200-1.2.1(A).MECHANICALCOMPACTION PERSSPWC 306-12.12" MIN
FOUNDATIONLPA12"TYPDETECTABLEWARNING TAPE PERSPECIFICATIONSNTSPIPE TRENCH - WATERNOTES:1.ALL PIPE SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH ASTM D2774,"UNDERGROUND INSTALLATION OF THERMOPLASTIC PRESSURE PIPING", LATEST EDITION.2.36" MINIMUM COVER REQUIRED FOR INSTALLATIONS UNDER HARDSCAPE. 30 " MINIMUMCOVER FOR INSTALLATIONS UNDER PLANTED AREAS.3.IF UNSTABLE FOUNDATION SOIL IS ENCOUNTERED, THE GEOTECHNICAL FIELD INSPECTORSHALL DETERMINE OVEREXCAVATION DEPTH AND FOUNDATION RE-FILL MATERIAL.4.CONTRACTOR SHALL PROVIDE HAND EXCAVATED "BELL HOLE" FOR EACH PIPE JOINT SOTHAT THE WEIGHT OF PIPE DOES NOT BEAR ON THE BELL. CONTRACTOR SHALL RE-FILLAND HAND-TAMP EACH "BELL HOLE" PRIOR TO COMPLETING THE PLACEMENT OF PIPEBEDDING.6"MIN(TYP)6" MIN
12"
MIN REFER TO PAVING PLANFOR PAVEMENT SECTIONADJACENTPAVINGTRACER WIRE PERSPECIFICATIONSAS REQUIRED (VARIES)FINAL BACKFILL.RELATIVECOMPACTION PERGEOTECHNICALREPORT.PIPE ZONE.SE-30 MINIMUM SANDBEDDING MATERIAL.MECHANICALCOMPACTION PERSSPWC 306-12.12" MIN
FOUNDATIONDETECTABLEWARNING TAPE PERSPECIFICATIONSLPA12"TYPPIPE SIZEPER PLANSFRENCH DRAIN NTSFLOOR DRAINNTS01020304080706050910SLOPE010403NTSLPAPROMENADE DRAIN INLETZURN ZN-415N-DG02FINISHED SURFACE PCC PAVING PERPLAN4" PVC SDR 35 OUTLET016" MIN03 0204SLOPEFLUSHFLUSHALIGN DRAIN INLET WITH HARDSCAPE SCORE JOINTS PER PLAN6" MIN6" MIN CONCRETE COLLARNOTES:·DRAIN INLET GRATE SHALL BE INSTALLED FLUSH WITH FINISHED SURFACE. PROVIDE PCCCOLLAR BELOW HARDSCAPE PER MANUFACTURES REQUIREMENTS.·DRAIN INLET SHALL HAVE POSITIVE DRAINAGE TOWARD THE GRATE.·DRAIN INLET OPENINGS SHALL BE 12" MAX IN ALL DIRECTIONS.
0LCIISHEET INDEXGENERAL NOTESLAYOUT AND MATERIALS NOTESPLANTING NOTESLANDSCAPE GRADING AND DRAINAGEABBREVIATIONSL0.01 LANDSCAPE NOTES AND SCHEDULESL1.01 MATERIALS PLANL2.01 LAYOUT PLANL4.01 SECTIONS AND ELEVATIONSL5.01 CONSTRUCTION DETAILSL6.00 IRRIGATION LEGEND AND NOTESL6.01 IRRIGATION PLANL6.02 IRRIGATION CALCULATIONS AND NOTEL6.03 IRRIGATION DETAILSL6.04 IRRIGATION DETAILSL7.01 PLANTING PLANL7.02 PLANTING DETAILSTREE REMOVAL NOTES1. CONTRACTOR SHALL RETAIN THE SERVICES OF AN INDEPENDENTREGISTERED CONSULTING ARBORIST.2. THE ARBORIST SHALL PROVIDE CONTRACTOR WITH RECOMMENDATIONS ANDSPECIFICATIONS AS TO THE REMOVAL OF THE EXISTING TREE.3. ARBORIST SHALL BE ON-SITE TO OBSERVE THE REMOVAL OF TREE.4. THE ARBORIST SHALL BE CERTIFIED WITH THE AMERICAN SOCIETY OFCONSULTING ARBORISTS OR INTERNATION SOCIETY OF ARBORICULTURE.5. CONTRACTOR SHALL FOLLOW ALL ARBORIST RECOMMENDATIONS ANDSPECIFICATIONS, UNLESS OTHERWISE DIRECTED BY CLIENT/ARCHITECT.1. REFER TO CIVIL ENGINEER'S DRAWINGS FOR UTILITY LOCATIONS, TREESUBDRAINAGE STUBOUTS, (IF REQUIRED), AND FINAL GRADING. IF ACTUALSITE CONDITIONS VARY FROM WHAT IS SHOWN ON THE LANDSCAPEARCHITECT'S DRAWINGS, THE CONTRACTOR SHALL CONTACT THE OWNER'SAUTHORIZED REPRESENTATIVE AND LANDSCAPE ARCHITECT FOR DIRECTIONAS TO HOW TO PROCEED.2. VERIFY LOCATIONS OF ALL PERTINENT EXISTING AND PROPOSED SITEIMPROVEMENTS. IF ANY PART OF THIS PLAN CANNOT BE FOLLOWED DUE TOSITE CONDITIONS, CONTACT THE LANDSCAPE ARCHITECT FOR INSTRUCTIONPRIOR TO COMMENCING WORK.3. EXACT LOCATIONS OF PLANT MATERIALS SHALL BE REVIEWED BY THELANDSCAPE ARCHITECT IN THE FIELD PRIOR TO INSTALLATION. LANDSCAPEARCHITECT RESERVES THE RIGHT TO ADJUST PLANTS TO EXACT LOCATION INFIELD.4. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL PLANT COUNTSAND SQUARE FOOTAGES. QUANTITIES SHOWN ON PLANS TAKE PRECEDENCEOVER WRITTEN QUANTITIES IN "PLANTING LEGEND."5. PROVIDE MATCHING FORMS AND SIZES FOR ALL PLANT MATERIALS WITHINEACH SPECIES AND SIZE DESIGNATED ON THE DRAWINGS.6. PRUNE NEWLY PLANTED TREES ONLY AS DIRECTED BY LANDSCAPEARCHITECT.7. ALIGNED AND EQUALLY SPACED, IN ALL DIRECTIONS, ALL SHRUBS TO BE ASDESIGNATED PER THESE NOTES AND DRAWINGS.8. ALL TREES IN ROWS TO BE ALIGNED. (UNLESS NOTED OTHERWISE ON PLANS)9. TREES SHALL BEAR SAME RELATION TO FINISH GRADE AS AT PLACE OFGROWTH.10. FINISH GRADES OF ALL TURF AREAS SHALL BE (1") BELOW ADJACENT CURBOR PAVEMENT. FINISH GRADES OF ALL SHRUB AREAS SHALL BE (2-1/2")BELOW ADJACENT CURB, PAVEMENT OR HEADER.11. CONTRACTOR SHALL SUBMIT FOR APPROVAL COLOR PHOTOS OF ALL TREES,SHRUBS, AND GROUNDCOVER. PHOTOS SHOULD INCLUDE A PERSON FORSCALE PURPOSES, PHOTOS SHALL BE OF THE ACTUAL PLANT MATERIAL TOBE USED ON THE PROJECT. ALL PLANT MATERIAL SHALL BE OF A QUALITY ASDETERMINED BY THE LANDSCAPE ARCHITECT. MATERIAL FOUND UNSUITABLEFOR THE DESIGN OR SPECIFICATION INTENT WILL BE REJECTED.12. PROVIDE A (3") LAYER OF MULCH AT PROPOSED TREE, SHRUB, ANDGROUNDCOVER PLANTING AREAS, EXCEPT AREAS WITH JUTE MESHING.13. CONTRACTOR SHALL CONDUCT AGRICULTURAL SUITABILITY AND FERTILITYSOILS TESTING PER SOIL PREPARATION SPECIFICATION. ANALYSIS SHALLINCLUDE RECOMMENDATIONS FOR SOIL PREPARATION AND BACKFILL MIX ASWELL AS RECOMMENDATIONS FOR POST MAINTENANCE FERTILIZATION.SUBMIT SOILS ANALYSES AND SAMPLES OF AMENDMENTS TO LANDSCAPEARCHITECT FOR REVIEW PRIOR TO SOIL PREPARATION.14. QUANTITIES LISTED ON PLANT LEGEND ARE PER SHEET. CONTRACTOR MUSTVERIFY QUANTITIES GIVEN ON THE PLANS WITH ACTUAL QUANTITIES SHOWN.15. PROVIDE ROOT BARRIERS IN ADDITION TO THOSE INDICATED ON THE PLANSFOR ALL TREES WITHIN 5' OF ANY HARDSCAPE.16. PLANT ALL TREES A MIN. OF 5' FROM ANY DRAIN LINES. THE LANDSCAPECONTRACTOR SHALL VERIFY THE LOCATION OF ALL DRAIN LINES PRIOR TOCOMMENCING WORK.17. TREES ARE TO BE A MINIMUM OF 5' AWAY FROM ANY HARDSCAPE SUCH ASCURBS, WALKS, ETC.18. LANDSCAPE MAINTENANCE PERIOD IS 90 DAYS.19. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.1. THE CONTRACTOR SHALL LAYOUT AND FIELD VERIFY ALL DIMENSIONS OFDRIVEWAY, PLANTERS, WALKS, SLOPES AND RELATED WORK PRIOR TOCONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT TO THEATTENTION OF THE OWNER'S AUTHORIZED REPRESENTATIVE.2. VERIFY LOCATIONS OF ALL PERTINENT EXISTING AND PROPOSED SITEIMPROVEMENTS. IF ANY PART OF THIS PLAN CANNOT BE FOLLOWED DUE TOSITE CONDITIONS, CONTACT THE LANDSCAPE ARCHITECT FOR INSTRUCTIONPRIOR TO COMMENCING WORK.3. WRITTEN DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALE.4. THIS DRAWING INCLUDES THE LOCATION OF AREA DRAINS FOR REFERENCE.REFER TO RELATED CIVIL ENGINEER'S DRAWINGS FOR CONSTRUCTIONDETAILS AND UTILITY CONNECTIONS.5. REFER TO ELECTRICAL ENGINEER'S DRAWINGS FOR LIGHT FIXTURESCHEDULE AND CIRCUITRY AS NECESSARY.6. REFER TO SOIL ENGINEER'S GEOTECHNICAL REPORT FOR SUB-BASEMATERIALS AND COMPACTION.7. WHERE DIMENSIONS ARE CALLED AS "EQUAL", ALL REFERENCED ITEMSSHALL BE SPACED EQUALLY, MEASURED TO THEIR CENTERLINES.8. ALL MEASUREMENTS ARE TO FACE OF WALL, CURB OR OTHER FIXED SITEIMPROVEMENT, UNLESS OTHERWISE NOTED. DIMENSIONS TO CENTERLINESAS INDICATED.9. INSTALL ALL INTERSECTING ELEMENTS AT 90 DEGREES TO EACH OTHERUNLESS OTHERWISE NOTED.10. ALL DRAINS/ BASINS SHOULD HAVE BLACK ATRIUM TYPE GRATES WITHINSHRUBS/GROUNDCOVER AREAS AND BLACK FLAT TYPE GRATES IN TURFAREAS.1. BASE INFORMATION INCLUDING THE LOCATION OF PROPERTY LINES,EASEMENTS, BUILDINGS, ROADS AND CURBS HAVE BEEN TAKEN FROM THECIVIL ENGINEER'S DRAWINGS. REFER TO CIVIL ENGINEER'S DRAWINGS FORADDITIONAL INFORMATION.2. REFER TO THE CIVIL ENGINEER'S DRAWINGS FOR PROPOSED UTILITYINFORMATION INCLUDING STORM DRAIN, SEWER, WATER, ELECTRICAL, GAS,TELEPHONE AND CABLE TV.3. REFER TO CITY AND/OR COUNTY STANDARD PLANS AND SPECIFICATIONSWHERE APPLICABLE.4. VERIFY SITE INFORMATION, INCLUDING PROPERTY LINES, EXISTING ABOVEGROUND AND BELOW GROUND UTILITIES AND STRUCTURES, AND OTHERINFORMATION AFFECTING THE SCOPE OF WORK INCLUDED ON THESEDRAWINGS. IF ACTUAL SITE CONDITIONS VARY FROM WHAT IS SHOWN ONTHE LANDSCAPE ARCHITECT'S DRAWINGS, THE CONTRACTOR SHALLCONTACT THE OWNER'S AUTHORIZED REPRESENTATIVE AND THELANDSCAPE ARCHITECT FOR DIRECTION ON HOW TO PROCEED.5. EXCAVATION IN THE VICINITY OF UTILITIES AND EXISTING MATERIALS SHALLBE UNDERTAKEN WITH CARE. THE CONTRACTOR BEARS FULLRESPONSIBILITY FOR THIS WORK. ANY DAMAGE CAUSED BY ANY PERSON,VEHICLE, EQUIPMENT, OR TOOL RELATED TO THE EXECUTION OF THECONTRACT SHALL BE REPAIRED IMMEDIATELY AT NO EXPENSE TO THEOWNER.6. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY COORDINATION REQUIREDTO ACCOMPLISH ALL CONSTRUCTION OPERATIONS. ALL PIPING, CONDUIT,SLEEVES, ETC., SHALL BE SET IN PLACE PRIOR TO INSTALLATION OFCONSTRUCTION ITEMS.7. CONTRACTOR SHALL BE RESPONSIBLE TO CONSULT WITH SITESUPERINTENDENT, APPROPRIATE AGENCIES AND PLANS, FOR THELOCATIONS OF ALL UNDER-GROUND UTILITIES, PIPES AND STRUCTURES.CONTRACTOR SHALL TAKE SOLE RESPONSIBILITY FOR ANY COST INCURREDDUE TO DAMAGE OF SAID UTILITIES.8. CONTRACTOR SHALL NOT WILLFULLY PROCEED WITH CONSTRUCTION ASDESIGNED WHEN IT IS OBVIOUS THAT UNKNOWN OBSTRUCTIONS, AREADISCREPANCIES AND/OR GRADE DIFFERENCES EXIST THAT MAY NOT HAVEBEEN KNOWN DURING DESIGN. SUCH CONDITIONS SHALL BE IMMEDIATELYBROUGHT TO THE ATTENTION OF THE OWNER'S AUTHORIZEDREPRESENTATIVE. THE CONTRACTOR SHALL ASSUME FULL RESPONSIBILITYFOR ALL NECESSARY REVISIONS DUE TO FAILURE TO GIVE SUCHNOTIFICATIONS.9. CONTRACTOR IS RESPONSIBLE FOR REPLACEMENT OF ANY EXISTINGMATERIALS THAT ARE DAMAGED DURING CONSTRUCTION.10. PRIOR TO INSTALLATION OF ANY CONSTRUCTION ITEM, FORMS WITH STEEL INPLACE AND COMPACTED SUBGRADE COMPLETE, SHALL BE OBSERVED ANDREVIEWED BY THE LANDSCAPE ARCHITECT.11. ALL WALLS AND WALKS SHOULD HAVE SMOOTH, CONTINUOUS CURVES ASINDICATED ON PLANS.12. ALL PROPERTY LINES, LOT LINES, AND TOP OF SLOPE LINES SHALL BEVERIFIED PRIOR TO COMMENCING WORK.13. ALL ELECTRICAL JUNCTION BOXES FOR LIGHTS SHALL BE IN PLANTING AREASAND LOCATION REVIEWED BY THE LANDSCAPE ARCHITECT. STAKE LOCATIONPRIOR TO INSTALLATION.14. SEE CIVIL ENGINEER'S DRAWINGS FOR CURBS AND A/C PAVING.15. REFER TO CIVIL ENGINEER'S DRAWINGS FOR ELEVATIONS AND LOCATION OFDRAINAGE STRUCTURES PRIOR TO INSTALLATION OF WALKS, FOOTINGS ANDOTHER STRUCTURES.16. REFER TO GEOTECHNICAL REPORT FOR ADDITIONAL INFORMATION. IF NOTESON THE PLANS DIFFER FROM THE GEOTECHNICAL REPORT, PROVIDE THEMOST STRINGENT REQUIREMENT.17. RAISE ALL VAULTS/UTILITIES BOXES TO GRADE WITHIN LIMITS OF WORK.FIELD VERIFY PRIOR TO BID.1. REFER TO CIVIL ENGINEER'S GRADING PLANS FOR SITE GRADING, DRAINAGE,AND UTILITY LOCATIONS. IF ACTUAL SITE CONDITIONS VARY FROM WHAT ISSHOWN ON THE LANDSCAPE ARCHITECT'S DRAWINGS, THE CONTRACTORSHALL CONTACT THE OWNER'S AUTHORIZED REPRESENTATIVE ANDLANDSCAPE ARCHITECT FOR DIRECTION AS TO HOW TO PROCEED.2. REFER TO CIVIL ENGINEER'S DRAWINGS FOR SUBDRAINAGE POINT OF INCONNECTION TO STORM DRAIN.3. THE CONTRACTOR SHALL REQUEST OBSERVATION AS REQUIRED 48 HOURSADVANCE OF PERFORMING WORK.4. THE CONTRACTOR SHALL NOTIFY UNDERGROUND SERVICE ALERT (USA800/227-2600) OR DIG ALERT (800-422-4133) 48 HOURS PRIOR TO ANYEXCAVATION.5. ALL GRADING OPERATIONS SHALL CONFORM TO LOCAL GUIDELINES.6. FIELD VERIFY EXISTING UNDERGROUND UTILITIES. THE CONTRACTOR SHALLBE RESPONSIBLE FOR VERIFYING THE ACTUAL LOCATION AND ELEVATION INTHE FIELD PRIOR TO BEGINNING CONSTRUCTION. THE CONTRACTOR SHALLPROTECT ALL EXISTING UTILITIES AND SHALL BE RESPONSIBLE FOR ANYDAMAGE TO EXISTING UTILITIES ENCOUNTERED DURING CONSTRUCTION.7. NO CHANGE IN CONTRACT PRICE WILL BE ALLOWED FOR ACTUAL OR CLAIMEDDISCREPANCY BETWEEN EXISTING GRADE AND THOSE SHOWN ON PLANSAFTER CONTRACTOR HAS ACCEPTED EXISTING GRADES AND MOVED ONTOTHE SITE.8. ALL PROPOSED GRADES ARE TO MEET AND BLEND IN WITH EXISTINGGRADING AT PROJECT LIMIT AND EXISTING SIDEWALK. PRECISE ELEVATIONSINDICATED ON PLANS TO BE VERIFIED IN FIELD TO AS-BUILT CONDITION.9. THE DEBRIS CREATED BY LANDSCAPE GRADING OPERATIONS SHALL BECOMETHE PROPERTY OF THE CONTRACTOR AND SHALL BE LEGALLY DISPOSED OFOFF-SITE.10. FINAL LANDSCAPE GRADING SHALL BE REVIEWED BY THE LANDSCAPEARCHITECT IN THE FIELD PRIOR TO INSTALLATION OF PLANTING.GA. GAUGEGALV. GALVANIZEDGND. GROUNDGR. GRADEHDR HEADERHT. HEIGHTLT. LIGHTMAX. MAXIMUMMET. METALMFR. MANUFACTURERMIN. MINIMUMMTD. MOUNTEDMTL. MATERIALN.I.C. NOT IN CONTRACTN.T.S. NOT TO SCALEO.C. ON CENTERO.D. OUTSIDE DIAMETER (DIM.)PA PLANTING AREAPRCST. PRECASTP.I.P. POURED IN PLACEP.O.T. POINT OF TANGENCYP.T.S. POST TENSION SLABQTY QUANTITYR. RISERRAD. RADIUSREINF. REINFORCEDREQ. REQUIREDSCHED. SCHEDULESHT. SHEETSPEC. SPECIFICATIONS.S. STAINLESS STEELSTD. STANDARDSTRL. STRUCTURALT. TREADT.C. TOP OF CURBT.O.S. TOP OF SLOPET.O.W. TOP OF WALLTYP. TYPICALTBD. TO BE DETERMINEDVERT. VERTICALW/ WITHW/O WITHOUT& ANDANGLE@ ATCENTERLINEDIAMETER OR ROUND# POUND OR NUMBERADJ. ADJACENTAGGR. AGGREGATEAL. ALUMINUMAPPROX. APPROXIMATEARCH. ARCHITECTURALAC. ASPHALTACC. ACCESSIBLEB.C.R. BEGINNING OF CURVE RADIUSB.O.C. BACK OF CURBB.O.W. BOTTOM OF WALLB.O.S. BOTTOM OF SLOPEBLDG. BUILDINGBLK. BLOCKC.E. CIVIL ENGINEERC.I.P. CAST IN PLACECLKG. CAULKINGCMU. CONCRETE MASONRY UNITCONC. CONCRETECONSTR. CONSTRUCTIONCONT. CONTINUOUSCTR. CENTERD.A. DISABLED ACCESSDET. DETAILDIA. DIAMETERDIM. DIMENSIONDN. DOWNDWGS. DRAWINGSE.J. EXPANSION JOINTEL. ELEVATIONELEC. ELECTRICALEQ. EQUALEXP. EXPANSIONEXT. EXTERIORF.G. FINISH GRADEF.S. FINISH SURFACEF.O.B. FACE OF BUILDINGF.O.C. FACE OF CURBF.O.W. FACE OF WALLL0.01LANDSCAPE NOTESAND SCHEDULESVICINITY MAPPROJECT TEAM DIRECTORYOWNER:CITY OF DOWNEY/ 11111BROOKSHIRE AVENUE DOWNEY,CA 90241CONTACT: DELFINO CONSUNJI, PE,DIRECTOR OF PUBLIC WORKS/CITY [email protected] ENGINEER:LPA, INC.5301 CALIFORNIA AVE., STE 100IRVINE, CA 92617TEL: 949.261.1001FAX: 949.260.1190ROBERT [email protected] ARCHITECT:LPA, INC.5301 CALIFORNIA AVE., STE 100IRVINE, CA 92617TEL: 949.261.1001FAX: 949.260.1190KENYA [email protected]:LPA, INC.5301 CALIFORNIA AVE., STE 100IRVINE, CA 92617TEL: 949.261.1001FAX: 949.260.1190BRIAN [email protected] SITE:12400 COLUMBIA WAYDOWNEY, CA 90242COLUMBIA WAYARDIS AVE IMPERIAL HWYCONGRESSMANSTEVE HORN WAYCARING WAY APOLLO WAYCENTURY FWYGLENN ANDERSON FWYFOSTER RDSTEWART ANDGRAY RDBELLFLOWER BLVDLAKEWOOD BLVDBROOKSHIRE AVEDOWNEY AVEALAMEDA STIMPERIAL HWYThis document and all other project documents,ideas, aesthetics and designs incorporatedtherein are instruments of service. All projectdocuments are copyright protected, are theproperty of LPA, Inc. (LPA) and cannot be lawfullyused in whole or in part for any project or purposeexcept as set forth in the contractual agreementbetween LPA and its Client. The unauthorizeddisclosure and/or use of the project documents(including the creation of derivative works), maygive rise to liability for copyright infringement,unlawful disclosure, use or misappropriation ofproperty rights held by LPA. The unauthorizeduse of the project documents will give rise to therecovery of monetary losses and damagesincluding attorney fees and costs for which theunauthorized user will be held liable.Project documents describe the design intent ofthe work and are not a representation of as-builtor existing conditions. LPA is not responsible forany discrepancies between the project documentsand the existing conditions.© LPA, Inc.Developed forJob NumberDate PublishedChecked ByScaleRevision Date ARCHITECTURE ENGINEERING INTERIORSLANDSCAPE ARCHITECTURE PLANNING949-261-1001 Office949-260-1190 FaxLPADesignStudios.comSubmittal Date 5301 California Avenue, Suite 100Irvine, California 92617DOWNEY SPACE SHUTTLE EXHIBIT
AND EDUCATION BUILDING
12400 COLUMBIA WAY
DOWNEY. CA 90242
CITY OF DOWNEY3055401KH, RG, JH100% SCHEMATIC DESIGN 10/28/2022 50% DESIGN DEVELOPMENT 12/02/2022
100% DESIGN DEVELOPMENT 01/03/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CONSTRUCTION DOCS 08/01/2025 KEYNOTE DESCRIPTIONCOLOR / FINISH NOTEKEYDESCRIPTIONABCDEF0102030405PASYM. DESC.DET.DESC.SYM.FOC BOC NOTES:A. UTILITIES SHOWN ARE FOR REFERENCE ONLY. SEE CIVIL DWGS FOR DETAILS ANDEXACT LOCATIONS.B. FINAL LOCATIONS TO BE REVIEWED BY LANDSCAPE ARCHITECT.(E) CONCRETE PAVINGPROTECT IN PLACEKEYNOTESREFERENCE KEYNOTESSITE SYMBOLS LEGENDDET/SHTCOMMENTSPROPERTY LINE/ RIGHTOF WAYFIRE HYDRANT (PER CIVIL)DRAIN INLET (PER CIVIL)CLEAN OUT (PER CIVIL)IRRIGATION BACKFLOWPREVENTER (PER CIVIL)PIV/CHECK VALVE/FDC (PER CIVIL)WATER METER (PER CIVIL)LIMIT OF WORKEXPANSION JOINTSSAWCUT JOINTFACE OF CURBBACK OF CURBPLANTING AREAALIGNPROTECT IN PLACE(E) UTILITIES(E) PAVEMENT STRIPINGPROTECT IN PLACEALUMINUM EDGING02/L5.0104/L5.01CONCRETE TIE-IN(E) AC PAVINGPROTECT IN PLACECONCRETE PAVING - TYPE 107/L5.01NATURAL GRAYTOPCAST #0501/L5.01CONCRETE PAVING - TYPE 2TO MATCH EXISTINGNATURAL STONE PAVERS11/L5.011/4" THICK DURAEDGE STEELEDGING, 6" DEEP, COLOR BLACK,FINISH: POWDERCOAT08/L5.01GBUILDING OVERHANGPER ARCHITECTUREH(E) DECOMPOSED GRANITE PAVINGPROTECT IN PLACE(E) CONCRETE CURBPROTECT IN PLACEJKUTILITY EASEMENTLPER CIVIL24"X24" WHITE MIST GRANITEPAVER BY MSI INTERNATIONAL TILE06GRASS FIRELANE PAVINGGRASSPAVE 2INVISIBLE STRUCTURES15/L5.0107DEEPENED CONCRETE HEADERNATURAL GRAYSMOOTH TROWEL10/L5.01PROTECT IN PLACE(E) LIGHT POLE(E) POWER POLE08CONCRETE SEATWALLNATURAL GRAYTOPCAST #0509/L5.01MECHANICAL EQUIPMENTPER MECHANICALMFIRELANEPER CIVILNPROTECT IN PLACE(E) FENCINGPROTECT IN PLACE(E) SHRUB AND GROUNDCOVERP09CONCRETE PAVING - TYPE 3INTEGRAL COLOR DAVISCOBBLESTONE 860,TOPCAST #15STORMWATER DETENTION SYSTEMPER CIVILQMGATE VALVE (PER CIVIL)BACKFLOW PREVENTER (PERCIVIL)FIRE DEPARTMENT CONNECTION(PER CIVIL)BACKFLOW PREVENTER (PERCIVIL)POST INDICATOR VALVE (PERCIVIL)DMANHOLE (PER CIVIL)PER ARCHITECTURERFUTURE BESS PAD LOCATIONSBUILDING COLUMN01/L5.0101/L5.01LIGHTING LEGENDPROTECT IN PLACEROCK COBBLE TYPE 2MIXED BEACH PEBBLE SMALL 12" -1", RCP BLOCK&BRICK10ROCK COBBLE TYPE 1SOUTHWEST BEACH PEBBLEMEDIUM 1"-2", RCP BLOCK&BRICK11DOWNSPOUTPER ARCHITECTURETSTEPPING STONE PAVER18"X18" FRENCH GRAY, LIGHTSANDBLAST, CALARC PAVERS BYSTEPSTONE12TRANSFORMER PADPER ELECTRICALUCRASH RATED BOLLARDPER SOUTHERN CALIFORNIA EDISONV(E) SIGNAGERELOCATE PER LANDSCAPEW(E) DOMESTIC WATER METER & BFPRELOCATE PER CIVILXPEDESTRIAN POLE LIGHTDESC.SYM.COMMENTS22/L5.0122/L5.0112/L5.01(E) BOLLARDPROTECT IN PLACEYDECOMPOSED GRANITE PAVINGTO MATCH EXISTING1316/L5.01SALVAGE EXISTING COBBLE EDGING14SREMOVABLE BOLLARD1520/L5.01R8464-30 STAINLESS STEEL BYRELIANCE FOUNDRY(E) TO REMAINPROTECT IN PLACEZDET/SHT5/E7.0321/L5.01(E)PAEXISTING PLANTING AREA, PATCHAND REPAIR AS NEEDEDBY OTHERSCONCRETE CURBPER CIVILAAPLACE BACK TO THE NEW PATHEDGE TO MATCH EXISTINGSEE ELECTRICALMECHANICAL EQUIPMENT PADPER STRUCTURALBB1. REFER TO ARBORIST REPORT FOR PROTECTION MEASURES OF ALL NOTEDEXISTING TREES.2. EXISTING IRRIGATION SHALL NOT BE INTERRUPTED FOR MORE THAN 48 HOURS.EXISTING TREES TO REMAIN SHALL BE DEEP-WATERED BI-WEEKLY OR ASDIRECTED BY THE ARBORIST. IF NO WATER IS AVAILABLE, POTABLE WATER IS TO BETRUCKED IN.3. CONSTRUCTION DUST SHALL BE WASHED OFF WITH WATER AT WEEKLY INTERVALS.4. ROOTS DAMAGED DURING CONSTRUCTION MUST BE CLEANLY CUT WITH A SAW,NOT RIPPED WITH GRADING EQUIPMENT, UNDER THE DIRECTION OF A CERTIFIEDARBORIST. REFER TO ARBORIST REPORT.5. REFER TO SPECIFICATIONS FOR FURTHER INFORMATION REGARDINGMAINTENANCE OF EXISTING TREES AND FOR INFORMATION REGARDINGINSTALLATION AND MAINTENANCE OF TEMPORARY PROTECTIVE BARRIER. REFERTO ARBORIST REPORT.6. UNDERGROUND UTILITY LINE AND PIPELINE TRENCHING SHALL NOT BE PLACEDWITHIN THE DRIPLINES OF TREES TO BE PRESERVED. IF IT IS NECESSARY PRIORWRITTEN APPROVAL FROM THE LANDSCAPE ARCHITECT IS REQUIRED. IRRIGATIONLINES SHALL BE TRENCHED BY HAND.7. RESTORE PRE-PROJECT SOIL CONDITIONS BY AERATING SOILS WHERECONSTRUCTION-RELATED SOIL COMPACTION HAS OCCURED. REFER TO CERTIFIEDARBORIST REPORT.TREE PROTECTION NOTES7/25/2025
SDxxxxxxxxxxxxxxxxCOMCOCOCOMSCOCOEXISTING BLDGNCOLUMBIA WAY L1.01MATERIALSPLAN1"=20'-0"This document and all other project documents,ideas, aesthetics and designs incorporatedtherein are instruments of service. All projectdocuments are copyright protected, are theproperty of LPA, Inc. (LPA) and cannot be lawfullyused in whole or in part for any project or purposeexcept as set forth in the contractual agreementbetween LPA and its Client. The unauthorizeddisclosure and/or use of the project documents(including the creation of derivative works), maygive rise to liability for copyright infringement,unlawful disclosure, use or misappropriation ofproperty rights held by LPA. The unauthorizeduse of the project documents will give rise to therecovery of monetary losses and damagesincluding attorney fees and costs for which theunauthorized user will be held liable.Project documents describe the design intent ofthe work and are not a representation of as-builtor existing conditions. LPA is not responsible forany discrepancies between the project documentsand the existing conditions.© LPA, Inc.Developed forJob NumberDate PublishedChecked ByScaleRevision Date ARCHITECTURE ENGINEERING INTERIORSLANDSCAPE ARCHITECTURE PLANNING949-261-1001 Office949-260-1190 FaxLPADesignStudios.comSubmittal Date 5301 California Avenue, Suite 100Irvine, California 92617DOWNEY SPACE SHUTTLE EXHIBIT
AND EDUCATION BUILDING
12400 COLUMBIA WAY
DOWNEY. CA 90242
CITY OF DOWNEY3055401KH, RG, JH100% SCHEMATIC DESIGN 10/28/2022 50% DESIGN DEVELOPMENT 12/02/2022
100% DESIGN DEVELOPMENT 01/03/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CONSTRUCTION DOCS 08/01/2025 KEYNOTE DESCRIPTIONCOLOR / FINISH NOTEKEYDESCRIPTIONABCDEF0102030405PASYM. DESC.DET.DESC.SYM.FOC BOC NOTES:A. UTILITIES SHOWN ARE FOR REFERENCE ONLY. SEE CIVIL DWGS FOR DETAILS ANDEXACT LOCATIONS.B. FINAL LOCATIONS TO BE REVIEWED BY LANDSCAPE ARCHITECT.(E) CONCRETE PAVINGPROTECT IN PLACEKEYNOTESREFERENCE KEYNOTESSITE SYMBOLS LEGENDDET/SHTCOMMENTSPROPERTY LINE/ RIGHTOF WAYFIRE HYDRANT (PER CIVIL)DRAIN INLET (PER CIVIL)CLEAN OUT (PER CIVIL)IRRIGATION BACKFLOWPREVENTER (PER CIVIL)PIV/CHECK VALVE/FDC (PER CIVIL)WATER METER (PER CIVIL)LIMIT OF WORKEXPANSION JOINTSSAWCUT JOINTFACE OF CURBBACK OF CURBPLANTING AREAALIGNPROTECT IN PLACE(E) UTILITIES(E) PAVEMENT STRIPINGPROTECT IN PLACEALUMINUM EDGING02/L5.0104/L5.01CONCRETE TIE-IN(E) AC PAVINGPROTECT IN PLACECONCRETE PAVING - TYPE 107/L5.01NATURAL GRAYTOPCAST #0501/L5.01CONCRETE PAVING - TYPE 2TO MATCH EXISTINGNATURAL STONE PAVERS11/L5.011/4" THICK DURAEDGE STEELEDGING, 6" DEEP, COLOR BLACK,FINISH: POWDERCOAT08/L5.01GBUILDING OVERHANGPER ARCHITECTUREH(E) DECOMPOSED GRANITE PAVINGPROTECT IN PLACE(E) CONCRETE CURBPROTECT IN PLACEJKUTILITY EASEMENTLPER CIVIL24"X24" WHITE MIST GRANITEPAVER BY MSI INTERNATIONAL TILE06GRASS FIRELANE PAVINGGRASSPAVE 2INVISIBLE STRUCTURES15/L5.0107DEEPENED CONCRETE HEADERNATURAL GRAYSMOOTH TROWEL10/L5.01PROTECT IN PLACE(E) LIGHT POLE(E) POWER POLE08CONCRETE SEATWALLNATURAL GRAYTOPCAST #0509/L5.01MECHANICAL EQUIPMENTPER MECHANICALMFIRELANEPER CIVILNPROTECT IN PLACE(E) FENCINGPROTECT IN PLACE(E) SHRUB AND GROUNDCOVERP09CONCRETE PAVING - TYPE 3INTEGRAL COLOR DAVISCOBBLESTONE 860,TOPCAST #15STORMWATER DETENTION SYSTEMPER CIVILQMGATE VALVE (PER CIVIL)BACKFLOW PREVENTER (PERCIVIL)FIRE DEPARTMENT CONNECTION(PER CIVIL)BACKFLOW PREVENTER (PERCIVIL)POST INDICATOR VALVE (PERCIVIL)DMANHOLE (PER CIVIL)PER ARCHITECTURERFUTURE BESS PAD LOCATIONSBUILDING COLUMN01/L5.0101/L5.01LIGHTING LEGENDPROTECT IN PLACEROCK COBBLE TYPE 2MIXED BEACH PEBBLE SMALL 12" -1", RCP BLOCK&BRICK10ROCK COBBLE TYPE 1SOUTHWEST BEACH PEBBLEMEDIUM 1"-2", RCP BLOCK&BRICK11DOWNSPOUTPER ARCHITECTURETSTEPPING STONE PAVER18"X18" FRENCH GRAY, LIGHTSANDBLAST, CALARC PAVERS BYSTEPSTONE12TRANSFORMER PADPER ELECTRICALUCRASH RATED BOLLARDPER SOUTHERN CALIFORNIA EDISONV(E) SIGNAGERELOCATE PER LANDSCAPEW(E) DOMESTIC WATER METER & BFPRELOCATE PER CIVILXPEDESTRIAN POLE LIGHTDESC.SYM.COMMENTS22/L5.0122/L5.0112/L5.01(E) BOLLARDPROTECT IN PLACEYDECOMPOSED GRANITE PAVINGTO MATCH EXISTING1316/L5.01SALVAGE EXISTING COBBLE EDGING14SREMOVABLE BOLLARD1520/L5.01R8464-30 STAINLESS STEEL BYRELIANCE FOUNDRY(E) TO REMAINPROTECT IN PLACEZDET/SHT5/E7.0321/L5.01(E)PAEXISTING PLANTING AREA, PATCHAND REPAIR AS NEEDEDBY OTHERSCONCRETE CURBPER CIVILAAPLACE BACK TO THE NEW PATHEDGE TO MATCH EXISTINGSEE ELECTRICALMECHANICAL EQUIPMENT PADPER STRUCTURALBBPAPAPAPAPAPAPAPAPAPAPAPAPAPAPALIMIT OF WORK LIMIT OF WORKPA PAPA040408EDUCATION BLDG.STEMBLDG.0903MATERIALS PLANPROPERTY LINEPROPERTY LINE RQQ0102090909D09VEH.TYP.TYP.TYP.VEH.0606060601 VEH.LLL01Q010909B08CCB0505M05FJQ07PA010101GVEH.03030307030303NPROPERTY LINE LIMIT OF WORKLCONGRESSMAN STEVE HORN WAYTYP.TYP.HF1011111110101011101110111011111011BBR05GQEAKUV01TYP.01PC071207BBM05010501070707TYP.DA07TYP.01X05WYTYP.061313040403TTYP.LIMIT
O
F
W
O
R
K
LIMIT OF WORKPROPERTY LINELIMIT OF WORK
LIMIT OF WORK (E) PA(E) PA(E) PA(E) PA(E) PA(E) PA(E) PA1515ZZ1310S1414AAAAPBB7/25/2025
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxEXISTING BLDGNCOLUMBIA WAY This document and all other project documents,ideas, aesthetics and designs incorporatedtherein are instruments of service. All projectdocuments are copyright protected, are theproperty of LPA, Inc. (LPA) and cannot be lawfullyused in whole or in part for any project or purposeexcept as set forth in the contractual agreementbetween LPA and its Client. The unauthorizeddisclosure and/or use of the project documents(including the creation of derivative works), maygive rise to liability for copyright infringement,unlawful disclosure, use or misappropriation ofproperty rights held by LPA. The unauthorizeduse of the project documents will give rise to therecovery of monetary losses and damagesincluding attorney fees and costs for which theunauthorized user will be held liable.Project documents describe the design intent ofthe work and are not a representation of as-builtor existing conditions. LPA is not responsible forany discrepancies between the project documentsand the existing conditions.© LPA, Inc.Developed forJob NumberDate PublishedChecked ByScaleRevision Date ARCHITECTURE ENGINEERING INTERIORSLANDSCAPE ARCHITECTURE PLANNING949-261-1001 Office949-260-1190 FaxLPADesignStudios.comSubmittal Date 5301 California Avenue, Suite 100Irvine, California 92617DOWNEY SPACE SHUTTLE EXHIBIT
AND EDUCATION BUILDING
12400 COLUMBIA WAY
DOWNEY. CA 90242
CITY OF DOWNEY3055401KH, RG, JH100% SCHEMATIC DESIGN 10/28/2022 50% DESIGN DEVELOPMENT 12/02/2022
100% DESIGN DEVELOPMENT 01/03/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CONSTRUCTION DOCS 08/01/2025 LIMIT OF WORKEDUCATION BLDG.STEMBLDG.LAYOUT PLANPROPERTY LINEPROPERTY LINE LIMIT OF WORKCONGRESSMAN STEVE HORN WAY05L2.01LAYOUTPLAN1"=20'-0"86°90 °
103°112°82°86°86°90°59°17°99°113°
1 1
3 °77°81°9
9 °93°94°90
°
86 °
87 °81°90°94°20'-0"10'-0"TYP4'-0"
TYP 12'-0"2 EQ.48'-7"4 EQ.26'-0"26'-2"
5 E.Q.11'-6"6'-0"4'-0"180'-9"35'-4"4EQ.16'-6"2EQ.R17'-0"18'-0" 2EQ.7'-2"41'-11"
8EQ.
45'-10"
65'-6"
7EQ.20'-0"6'-0"51'-4"5EQ.105'-0"21EQ.48'-7"6'-0"
25'-7"54'-4"4EQ.5'-1"
12'-2"
R2
8 '
-
0 "9'-7"3'-10"3'-4"26'-10"2EQ.31'-10"
8EQ.7'-1"
2EQ.18'-0"
5EQ.4'-1"
TYP 24'-3"
6'-1"24'-3"6EQ. TYP.6'-1"24'-3"
6'-1"24'-3"
6'-1"24'-3"
6'-1"24'-3"
6'-1"24'-3"
6'-1"24'-3"
6'-1"
12'-0"
3EQ.73°1
0 3
°
14'-8"9'-11"211'-9"24'-3"2EQ.21'-4"14'-4"22'-3"10'-5"18'-2"57'-2"10'-2"22'-4"24'-9"35°26°57'-8"14 EQ. 25'-4"
6 EQ.
23'-9"
6 EQ.
CENTER OF LIGHT POLE
CENTERED ON SCORE JOINT
CENTER OF LIGHT POLE
CENTERED ON SCORE JOINT
LIMIT
O
F
W
O
R
K
LIMIT OF WORKPROPERTY LINE LIMIT OF WORK
LIMIT OF WORK
107°68°6'-1"6'-1"
16'-11"
3EQ.6'-0"6'-0"36'-1"4EQ.20'-7"
3EQ.4'-7"16'-2"
4EQ.7'-1 1/2"81°4'-7"
2'-0"
TYP7'-8"94°25'-2"
3EQ.3'-1"CENTER OF LIGHT POLECENTERED ON SCORE JOINT
CENTER OF LIGHT POLECENTERED ON SCORE JOINTCENTER OF LIGHT POLECENTERED ON SCORE JOINT3'-1"4'-2"8'-11"3"32'-10"3EQ.5'-5"27'-3"3EQ.5'-0"52'-3 1/2" TO BOLLARD3"2'-3"25'-1"33'-1"15'-10"98°107°90°7/25/2025
L4.01SECTIONS &ELEVATIONS1/2"=1'-0"This document and all other project documents,ideas, aesthetics and designs incorporatedtherein are instruments of service. All projectdocuments are copyright protected, are theproperty of LPA, Inc. (LPA) and cannot be lawfullyused in whole or in part for any project or purposeexcept as set forth in the contractual agreementbetween LPA and its Client. The unauthorizeddisclosure and/or use of the project documents(including the creation of derivative works), maygive rise to liability for copyright infringement,unlawful disclosure, use or misappropriation ofproperty rights held by LPA. The unauthorizeduse of the project documents will give rise to therecovery of monetary losses and damagesincluding attorney fees and costs for which theunauthorized user will be held liable.Project documents describe the design intent ofthe work and are not a representation of as-builtor existing conditions. LPA is not responsible forany discrepancies between the project documentsand the existing conditions.© LPA, Inc.Developed forJob NumberDate PublishedChecked ByScaleRevision Date ARCHITECTURE ENGINEERING INTERIORSLANDSCAPE ARCHITECTURE PLANNING949-261-1001 Office949-260-1190 FaxLPADesignStudios.comSubmittal Date 5301 California Avenue, Suite 100Irvine, California 92617DOWNEY SPACE SHUTTLE EXHIBIT
AND EDUCATION BUILDING
12400 COLUMBIA WAY
DOWNEY. CA 90242
CITY OF DOWNEY3055401KH, RG, JH100% SCHEMATIC DESIGN 10/28/2022 50% DESIGN DEVELOPMENT 12/02/2022
100% DESIGN DEVELOPMENT 01/03/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CONSTRUCTION DOCS 08/01/2025
CHANGE IN
DIRECTION
ELEVATION AT SEAT WALL BELEVATION AT SEAT WALL A010224'-0"35'-10"PER CIVIL
PER CIVIL
12'-2"CONCRETE SEAT WALLCONCRETE SEAT WALLCHANGE IN
DIRECTION STEM BUILDING(BEYOND)STRUCTURAL COLUMNBEHINDMAIN BUILDING4'-0" O.C. TYPEQ.32'-0"8 REVEALS AT 4'-0" O.C.TYP3'-10"EQ.EQ.7/25/2025
L5.01CONSTRUCTION &PLANTING DETAILSThis document and all other project documents,ideas, aesthetics and designs incorporatedtherein are instruments of service. All projectdocuments are copyright protected, are theproperty of LPA, Inc. (LPA) and cannot be lawfullyused in whole or in part for any project or purposeexcept as set forth in the contractual agreementbetween LPA and its Client. The unauthorizeddisclosure and/or use of the project documents(including the creation of derivative works), maygive rise to liability for copyright infringement,unlawful disclosure, use or misappropriation ofproperty rights held by LPA. The unauthorizeduse of the project documents will give rise to therecovery of monetary losses and damagesincluding attorney fees and costs for which theunauthorized user will be held liable.Project documents describe the design intent ofthe work and are not a representation of as-builtor existing conditions. LPA is not responsible forany discrepancies between the project documentsand the existing conditions.© LPA, Inc.Developed forJob NumberDate PublishedChecked ByScaleRevision Date ARCHITECTURE ENGINEERING INTERIORSLANDSCAPE ARCHITECTURE PLANNING949-261-1001 Office949-260-1190 FaxLPADesignStudios.comSubmittal Date 5301 California Avenue, Suite 100Irvine, California 92617DOWNEY SPACE SHUTTLE EXHIBIT
AND EDUCATION BUILDING
12400 COLUMBIA WAY
DOWNEY. CA 90242
CITY OF DOWNEY3055401KH, RG, JH100% SCHEMATIC DESIGN 10/28/2022 50% DESIGN DEVELOPMENT 12/02/2022
100% DESIGN DEVELOPMENT 01/03/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CONSTRUCTION DOCS 08/01/2025
EQ.EQ.
VARIESREFER TOKEYNOTE 2
CONCRETE PAVING3" = 1'-0"-121202-CONCRETE PAVING; REFER TOMATERIALS PLAN KEYNOTE LEGEND FORFINISH & COLOR.REINFORCEMENT AND PAVINGTHICKNESS PER CIVILNOTES:A. SAWCUT & EXPANSION JOINTS;REFER TO DTL.B. PROVIDE DOWELS WHERE NEWCONCRETE TIES INTO EXISTINGPER DTL.C. PROVIDE THICKENED EDGE ATCOLUMNS, WALLS, AND WHEREPAVING ADJACENT TOPLANTING.D. DO NOT ALLOW CONCRETEOVER-POUR INTO ADJACENTPLANTERS.07-34AGGREGATE BASESUBGRADE COMPACTION AND OVEREXCAVATION PER GEOTECHNICALREPORT3406-08C7.01CONCRETE PAVING; REFER TO DETAIL"SPEED DOWEL"; BY SIKA CORPORATION CONCRETE ACCESSORIES;PRODUCT # PSD12/ #4TXSAWCUT CONTROL JOINT; 1/8-INCH WIDE; CUT TO 1/4 DEPTH OF SLAB;PROVIDE TIGHT 1/8-INCH RADIUS ON EDGE OF PAVING BEFORESAWCUTTING.CONCRETE PAVING REBAR; REFER TO DETAILJOINT ENLARGEMENT; REFER TO DETAILPEDESTRIAN: 5/8" SMOOTH STEEL DOWEL X 24" @ 24" O.C.VEHICULAR: 5/8" SMOOTH STEEL DOWEL X 24" @ 18" O.C.AGGREGATE BASE AND SUBGRADE; REFER TO DETAILB. EXPANSION JOINTA. SAWCUT CONTROL JOINTPOUR "A"POUR "B"01-01-625341704-417CONCRETE PAVING JOINTS3" = 1'-0"-123456701-145CONCRETE PAVING;FIN. GRADE; PER DETAIL1/4" EXPANSION MATERIAL;HOLD 1/2" BELOW FINISHGRADE; REFER TO SPECFOR PRODUCT INFO.DOWEL; PER DETAIL1/8" TOOLED RADIUSJOINT SEALANT WITHSEEDED SILICA SAND; SANDIS TO BE CASCADED OVERJOINT, EXCESS TO BEBRUSHED AWAY; COLOR TOMATCH CONCRETECLOSED CELL BACKER ROD32TYP.TYP.213456602-N.T.S.EXPANSION JOINT ENLARGEMENT-01-8"DEPTH VARIESREFER TOKEYNOTE 53"CLR.TYP.1CONCRETE PAVING; REFER TO DTL.ADJACENT SURFACE/ FINISH GRADE; REFER TO PER MATERIALS PLAN#X REINFORCING; CONTINUOUSEXTEND REINFORCEMENT FROM PAVING INTO THICKENED EDGE & WRAP ENDSTHICKENED EDGE; 8" DEPTH FOR PEDESTRIAN PAVING;12" DEPTH AT FIRELANEBASE MATERIAL & COMPACTED SUBGRADE; REFER TO DTL.EASE ALL EDGES; 1/4"R, TYP.NOTES:A. ADD EXPANSION JOINTS AT ALL THICKENED EDGE CONDITIONS ADJACENTTO OTHER PAVING TYPES PER DETAIL3"CLR.TYP23456 1632776"01-01-02-4CONC. PAVING THICKENED EDGE1-1/2" = 1'-0"-NEW CONCRETE PAVING ANDREINFORCING; REFER TO DTL.EXISTING CONCRETE PAVING1/2" X 24" SMOOTH STEEL DOWEL AT18" O.C.5/8" SLIP SLEEVE DRILLED INTOEXISTING CONCRETE PAVING; DOWELTO HAVE FREE MOVEMENT ON THISSIDEJOINT SEALANT WITH BACKER RODBASE MATERIAL AND COMPACTEDSUBGRADE; REFER TO DTL.1/8" RADIUS; AT NEW CONCRETEPAVINGCONCRETE PAVING TIE-IN3"=1'-0"-1234567NOTES:A. PROVIDE AT ALL LOCATIONS WHERENEW CONCRETE JOINS EXISTINGCONCRETE.B. PROVIDE CLEAN SAWCUT AT EXISTINGPAVING. EXTEND PROPOSED PAVING ASREQUIRED TO CLOSEST ADJACENTJOINT.C. SEE CIVIL PLANS FOR LIMIT OFDEMOLITION.45112"3" CLR.01-01-EQ.EQ.23671/2"NOTES:A. PROVIDE EXPANSION JOINT AT ALL VERTICAL SURFACES.EXPANSION JOINT AT VERTICAL SURFACE3"=1'-0"-31234562"CLR.1/4"CONCRETE PAVING ANDREINFORCEMENT PER DETAILEXPANSION JOINT FILLER;MATCH FULL DEPTH OF CONC.PAVING; REFER TO SPECSFOR MATERIALJOINT SEALANT; COLOR TOMATCH CONCRETE COLORW/SEEDED SILICA SANDBASE MATERIAL ANDSUBGRADE PER CIVIL DETAILFACE OF VERTICAL SURFACE1/8" RADIUS01-1/2"01-2561464351234501-NOTES:A. PROVIDE SAWCUT JOINT EVERY 10'& EXPANSION JOINT EVERY 30' &@ EVERY CHANGE IN DIRECTIONPERB. CORNER @ MOW CURB PER02-14-6"FINISH SURFACE/FINISH GRADE.DEEPENED CONCRETE HEADERPER MATERIALS PLAN. REFER TOKEYNOTE LEGEND FOR COLOR &FINISH.1/4" RADIUS TYP.#4 REBAR CONTINUOUS.BASE MATERIAL & COMPACTEDSUBGRADE PERGRASS FIRELANE PAVING1-1/2" @FG11'-0" -DEEPENED CONCRETE HEADER3"=1'-0"-AT FIRELANE615-2CORNER @ MOW CURB3"=1'-0"-190°1202-SIM.NOTE:A. PROVIDE EXPANSION JOINT AS SHOWN AT ALLCHANGES IN DIRECTION.302-SIM.32CONCRETE MOW CURBEXPANSION JOINT, SEESAWCUT, SEE1/4" 213ROCK COBBLE18" STEEL SPIKE @18" O.C.PLANTING SOIL MIX BELOWNOTE:A. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.B. EDGING SHALL BE FLUSH W/ ADJACENT PAVING.METAL EDGING AT PLANTER1 1/2"=1'-0"-1234"2'-0"1%1%37215341234567CONCRETE FREE-STANDING WALL1" = 1'-0"-NOTES:A. REFER TO PLANS & ELEVATIONS FOR LOCATION OF JOINTS.B. ALL FORM SEAMS ARE TO ALIGN WITH REVEALS SHOWN ON ELEVATIONS & PLANS. PROVIDE CUSTOM FORM BOARDS AS REQUIRED.C. PROVIDE PERMANENT NON-SACRIFICIAL ANTI-GRAFFITI COATING ON ALL EXPOSED WALL SURFACES.(SEE SPECS)D. REVEAL SEE DETAILPER CIVIL 24" MAX.CONCRETE FREE-STANDING WALL PER MATERIALS PLAN. REFER TOKEYNOTE LEGEND FOR COLOR & FINISH1/8" EASED EDGE RADIUS, TYP. ALL EDGES. NO CHAMFERSFINISH SURFACE/FINISH GRADEOVER-EXCAVATION, SUBGRADE SCARIFICATION/COMPACTION SHALL BEPER GEOTECHNICAL REPORTEXPANSION JOINT PER#4 @ 12" O.C.TOP OF WALL PER CIVIL GRADING PLAN(3) #4 CONTINUOUS AT TOP AND BOTTOM#4 @ 12" O.C. EACH WAY AND EACH FACE2'-0"8805-993" CLR.TYP.6EQ.817-EQ.NATURAL STONE PAVERS1 1/2"=1'-0"-12312301-NOTES:A. PROVIDE LAYOUT EXHIBIT FOR APPROVAL PRIOR TOINSTALLATION.24"X24"X1.18" NATURAL STONE PAVER, PER PLANS & SPECSSAND BASE, PER SPECSCOMPACTED SUBGRADE PERCAST IN PLACE CONCRETE SUB-SLAB PER GEOTECH REPORT44DIM PER GEOTECH14 1006020905011107120804GRASS PAVER AT FIRELANE1 1/2"=1'-0"-12301-4123410-55CAST IN PLACE CONCRETE PAVING, PER PLAN L1.01AND DETAILDEEPENED CONCRETE HEADER, PER DETAILGRASSPAVE 2 SYSTEM12" COMPACTED SANDY GRAVEL AGGREGATE ROADBASECOMPACTED SUBGRADE PER GEOTECHNICAL REPORTGRASS, HYDROSEEDED50% SAND AND 50% SOIL MIXHYDROGROW MIX BELOW RING SUPPLIED FREE BYMANUFACTURER6787681 1/2"1"PLAN VIEWSECTION152" CONCRETE WALL REVEALFULL-2" WD. REVEAL @ COLD JOINT2"3/4"NOTE:A. PROVIDE REVEAL @ALL COLD JOINTS.B. REVEAL SHOULD BECONTINUOUS ON SIDES& TOP OF WALL UNLESSOTHERWISE NOTED ONPLAN OR ELEVATION.C. REFER TO PLANS &ELEVATIONS FOR JOINTSIZE & LOCATIONS.D. ALIGN ALL FORMJOINTS W/REVEALS.CUSTOM CUT FORMSAS REQUIRED.11123321/16"TYP.TOP OF CONCRETEWALL PER MATERIALSPLANCOLD JOINT1/4" MACHINE ROUTEDCORNERS AND EDGES1/8" WIDE BY 1 1/2" DEEPSAW CUT JOINT ALONGFACE, TOP, AND BACKOF WALL44FACE OF WALLBACK OF WALL142TYP.1 1/2"12"PLAN VIEWSECTION172/3HEIGHT1/3HEIGHTNOTES:A. COBBLES SHALL BE POWER WASHED PRIOR TO PLACEMENT TO REMOVEDIRT AND DEBRIS.B. PROVIDE FIELD MOCK-UP FOR REVIEW BY THE LANDSCAPE ARCHITECT.C. ROCK COBBLE AT AREA DRAIN.ROCK COBBLE AT PLANTERNTS-1243512345HAND SET COBBLES PER MATERIALS AND LAYOUT PLAN(S). MINIMUM 1/3 OFCOBBLE TO BE BELOW FINISH SURFACE.FINISH GRADE PER CIVIL (PROVIDE POSITIVE DRAINAGE TO CATCH BASIN)NON-WOVEN GEOTEXTILE FABRICBASE MATERIAL AND COMPACTED SUBGRADE PER GEOTECHNICALREPORT1/2" MAXIMUM SPACING BETWEEN COBBLESBUILDING WALL (WHERE OCCURS)661"MIN.21-2122STEPPING STONE PAVERS1 1/2"=1'-0"-12312301-NOTES:A. PROVIDE LAYOUT EXHIBIT FOR APPROVAL PRIOR TOINSTALLATION.18"X18"X2" PRECAST CONCRETE PAVER, PER PLANS & SPECS1" COMPACTED SAND BASE, PER SPECSCOMPACTED SUBGRADE PERROCK COBBLE TYPE 2, PER PLANADJACENT CONCRETE PAVING454FLUSHFLUSH01-06-54" MIN.EQ.TYP3"DECOMPOSED GRANITE PAVING3" = 1'-0"-123123NOTE:A. METAL HEADER PER08-SOUTHWEST BOULDER DECOMPOSED GRANITEPAVING W/ 'STABILIZER'. REFER TO SPECIFICATIONS& MATERIALS PLANSOIL SEPARATOR FABRIC "MIRAFI" 140NSUBGRADE OVER EXCAVATION AND COMPACTIONPER GEOTECHNICAL REPORT.LPA190403201612345NOTES:A. INSTALLATION PER MANUFACTURERB. FOOTING PER GEOTECNICAL REPORTBOLLARDFINISH SURFACECONCRETE FOOTINGCOMPACTED SUBGRADERECEIVERREMOVAVLE BOLLARDN.T.S.-30 18"6 12"4 12"15" MIN.12" MIN.12346 3 4"5PEDESTRIAN LIGHT POLE BASE3/4"=1'-0"POLE LIGHT, PER ELECTRICAL PLANS. SEE LIGHTING LEGEND SHEET L0.01 FOR MOREINFORMATION.FINISHED SURFACE PER MATERIALS PLAN13123NOTE:1. FOR EXPOSED HEIGHT OF LIGHTPOLE, REFER TO ELECTRICAL PLANS.4BASE PLATE PER MANUFACTURER5C.I.P. CONCRETE FOOTING, DIMENSIONS AND REINFORCEMENT PER STRUCTURAL6CONDUIT PER ELECTRICAL6ANCHOR BOLTS PER MANUFACTURER774ADJACENT PAVING PER AND MATERIALS PLAN.8CONCRETE TOPPING PAD 92. FOR CONCRETE PAD DIMENSIONSREFER TO LAYOUT AND MATERIALSPLANS.BASE MATERIAL AND COMPACT SUBGRADE PER GEOTECHNICAL REPORTALIGN289ALIGN7/25/2025
L6.00IRRIGATIONLEGEND & NOTES,This document and all other project documents,ideas, aesthetics and designs incorporatedtherein are instruments of service. All projectdocuments are copyright protected, are theproperty of LPA, Inc. (LPA) and cannot be lawfullyused in whole or in part for any project or purposeexcept as set forth in the contractual agreementbetween LPA and its Client. The unauthorizeddisclosure and/or use of the project documents(including the creation of derivative works), maygive rise to liability for copyright infringement,unlawful disclosure, use or misappropriation ofproperty rights held by LPA. The unauthorizeduse of the project documents will give rise to therecovery of monetary losses and damagesincluding attorney fees and costs for which theunauthorized user will be held liable.Project documents describe the design intent ofthe work and are not a representation of as-builtor existing conditions. LPA is not responsible forany discrepancies between the project documentsand the existing conditions.© LPA, Inc.Developed forJob NumberDate PublishedChecked ByScaleRevision Date ARCHITECTURE ENGINEERING INTERIORSLANDSCAPE ARCHITECTURE PLANNING949-261-1001 Office949-260-1190 FaxLPADesignStudios.comSubmittal Date 5301 California Avenue, Suite 100Irvine, California 92617DOWNEY SPACE SHUTTLE EXHIBIT
AND EDUCATION BUILDING
12400 COLUMBIA WAY
DOWNEY. CA 90242
CITY OF DOWNEY3055401KH, RG, JH100% SCHEMATIC DESIGN 10/28/2022 50% DESIGN DEVELOPMENT 12/02/2022
100% DESIGN DEVELOPMENT 01/03/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CD PRICING SET 08/01/25 EXIST. CALSENSE CS3000 CONTROLLER WILL BE UPGRADED FROM 16 STA. TO 32 STA. VERIFYCOMMUNICATION WITH POINT OF CONNECTION FOR PROPER WATER FLOW. CONTACT JEFFDRONGOWSKI @ CALSENSE (760-580-9428). NO EQUIPMENT ORDERING OR INSTALLATION WILLOCCUR WITHOUT CALSENSE'S COORDINATION AND APPROVAL OF UPGRADE TO THIS SYSTEM.32 STATION N/ALASCO V20101N-SC SLO-CLOSE SCH. 80 PVC TRUE UNION BALL VALVELINE SIZE1"CBPLAN SIZESCH. 40 PVC NON-PRESSURE LATERAL LINE - 12" MIN. COVER (PURPLE PIPE FOR RECYCLEDWATER REQUIRED)PLAN SIZEKKSCH 40 PVC PIPE SLEEVING - EXTEND 12" BEYOND EDGE OF HARDSCAPE - 2" MIN. SIZE / MARKAT EACH END WITH PAINTED SPOT ON THE BACK FACE OF CURB OR OTHER SIMILAR MARKING.PRESSURE MAINLINE - 36" COVER UNDER VEHICULAR PAVING / 30" COVER UNDERNON-VEHICULAR PAVING.NON-PRESSURE LATERALS - 30" COVER UNDER VEHICULAR PAVING / 24" COVER UNDERNON-VEHICULAR PAVING.MARKER TAPE WILL BE INSTALLED PER CITY REQUIREMENTS.SEE CHARTBELOWLSUPERIOR 950DW-PRS-MOD-RW REMOTE VALVE WITH PRESS. REG. AND PURPLE HANDLE*ALL EQUIPMENT WILL BE FOR RECYCLED WATER AND BE INSTALLED IN LABELED PURPLE VALVE BOXES LABELED & INSTALLED PER DISTRICT STDS.DRIP LINE TUBING GRID IN SHRUB AREAS - PROVIDE NETAFIM TLHCVXR-RW7-12 DRIPLINE.TUBING IS PURPLE STRIPED FOR RECYCLED WATER AND WILL HAVE 0.77 GPH EMITTERS AT12" O.C., ROWS OF TUBING TO BE SET AT ABOUT 16" O.C. FOLLOW THE MANUFACTURER'SINSTALLATION RECOMMENDATIONS AND SPECIFICATIONS.0.77 GPH12" O.C.16" O.C.I / JHUNTER 'ECO-ID' OPERATION INDICATOR (INSTALL PER MANUF. SPEC.) - LOCATE WHEREVISIBLE FROM STATION VALVE BOX WHERE POSSIBLE.NETAFIM TLSOV SERIES MANUAL FLUSH VALVE (INSTALL PER MANUF. SPEC.)DHOPMANUFACTURER / MODEL NUMBERSIZE DETAILSYMBOLMANUFACTURER / MODEL NUMBERSIZE DETAILSYMBOLDRIP LINECLASS 315 PVC IRRIGATION PRESSURE MAINLINE (2" AND LARGER) - 18" MIN. COVER (PURPLEPIPE REQUIRED FOR RECYCLED WATER)1"ARAINBIRD XCZ-100-PRB-R DRIP VALVE ASSEMBLY (0.3-20 GPM W/ 200 MESH SCREEN & 40# REG.)TWO WORKING DAYS BEFORE YOU DIGUnderground Service AlertCALL TOLL FREE:CALL B
EFOREYOUDIGSYMBOLMANUFACTURER / MODEL NUMBER NOZZLE RAD PSIFLOW - GPMDETAILQFMP1000(MAROON)14'40 0.2120'0.43 0.7740E / FHHUNTER PROS-06-CV-R6" POP-UP SPRINKLER W/ CHECK VALVE & PURPLE CAP FOR RECYCLED WATERSPRINKLER LEGENDMP2000(BLACK)HUNTER PROS-06-CV-RRECYCLED WATER WARNING SIGNAGEN/AOSUPERIOR 7645 QUICK COUPLER WITH LOCKING PURPLE VINYL COVER AND ACME THREADS1"G2 1/2" SLEEVE3" SLEEVE4" SLEEVE8" SLEEVE6" SLEEVE2" SLEEVE12" SLEEVEN/A55-100 WIRES27-38 WIRES39-54 WIRESN/A100+ WIRES1-26 WIRES1 1/4" PIPE3" PIPE1 1/2" PIPE4" PIPE6" PIPE2" PIPE1" PIPESCH 40 PVC SLEEVING CHARTA201.5"20SHRUB DRIPG.P.M.HYDRO ZONEVALVE SIZEVALVE NUMBERMP3000(BLUE)24'40 0.8614'0.1940HUNTER PROS-06-CV-RMPCORNER(TURCOISE)HUNTER PROS-06-CV-R*ALL EQUIPMENT WILL BE FOR RECYCLED WATER AND BE INSTALLED IN LABELED PURPLE VALVE BOXES LABELED & INSTALLED PER DISTRICT STDS.IRRIGATION NOTES:1. GENERAL - ALL WORK SHALL BE IN ACCORDANCE WITH APPLICABLE CODES AND THESE PLANS. THECONTRACTOR SHALL APPLY FOR ALL PERMITS AND PAY SAME.1.A. THE CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS SHOWN ON THE PLANS ATTHE SITE PRIOR TO COMMENCEMENT OF ANY WORK UNDER THIS CONTRACT.1.B. THE CONTRACTOR SHALL CARRY ALL WORKERS COMPENSATION, PUBLIC LIABILITY ANDPROPERTY DAMAGE INSURANCE, AS REQUIRED BY THE OWNER AND/OR GOVERNING AGENCY.2. SCOPE OF WORK - UNLESS OTHERWISE SPECIFIED, THE CONSTRUCTION OF IRRIGATION SYSTEMSSHALL INCLUDE THE FURNISHING, INSTALLING AND TESTING OF ALL POINTS OF CONNECTION,BACKFLOW DEVICES, AND MAINLINE; AND THE FURNISHING AND INSTALLING OF CONTROLLERS,ELECTRIC CONTROL VALVES, OTHER SPECIFIED VALVES, LATERAL LINES, RISERS AND FITTINGS,SPRINKLER HEADS, AND DRIP LINES; AND EXCAVATION AND BACKFILL AND ALL OTHER WORK INACCORDANCE WITH THESE PLANS, DETAILS, AND NOTES. THE CONTRACTOR SHALL FURNISH ALLLABOR, MATERIAL, EQUIPMENT PROPERTY, TRANSPORTATION, AND PERFORM ALL OPERATIONSREQUIRED FOR A COMPLETE AND OPERABLE IRRIGATION SYSTEM AS INDICATED ON, ORREASONABLY IMPLIED BY THE DRAWINGS, DETAILS, AND NOTES. INCLUDED AS A PART OF THEIRRIGATION WORK, BUT NOT LIMITED BY IT, ARE THE FOLLOWING:2.A. INSTALL COMPLETE OPERABLE INDEPENDENT IRRIGATION SYSTEMS PER THE PLANS, DETAILS,LEGENDS, AND NOTES.2.B. ALL IRRIGATION WORK SHALL BE GUARANTEED BY THE CONTRACTOR AS TO MATERIAL ANDWORKMANSHIP, INCLUDING SETTLING OF BACKFILLED TRENCHES BELOW GRADE FOR A PERIODOF ONE YEAR FOLLOWING THE DATE OF FINAL ACCEPTANCE OF THE WORK.3. CHECK AND VERIFY ALL SITE CONDITIONS AND UTILITY LOCATIONS PRIOR TO ANY SITE WORK. IF IT ISFOUND THAT THE SITE VARIES FROM THE DRAWINGS, NOTIFY THE LANDSCAPE ARCHITECT. THELANDSCAPE ARCHITECT SHALL DECIDE ALL QUESTIONS RELATING TO THE INTERPRETATION OF THEDRAWINGS AND THE ACCEPTABLE FULFILLMENT OF THE CONTRACT.4. COORDINATE ALL IRRIGATION WORK WITH PLANTING AND GRADING OPERATIONS TO AVOID ANYCONFLICT WITH PLANTING PITS, DRAINAGE SWALES, ETC.5. PIPING SHOWN ON THE PLANS IS ESSENTIALLY DIAGRAMMATIC. CONTRACTOR SHALL ROUTE PIPINGTO AVOID CONFLICT WITH STATIONARY ELEMENTS AND IN SUCH A MANNER AS TO CONFORM WITHTHE VARIOUS DETAILS AND DESIGN INTENT OF THESE PLANS. WHERE TREES, LIGHT STANDARDS, OROTHER PHYSICAL OBSTRUCTIONS EXIST, THE PIPING AND SPRINKLER HEAD LOCATIONS SHALL BEADJUSTED AND / OR RELOCATED AS NECESSARY TO OBTAIN FULL COVERAGE WITH MINIMAL OVERSPRAY.6. THE CONTRACTOR SHALL AT ALL TIMES PROTECT HIS WORK FROM DAMAGE AND THEFT ANDREPLACE ALL DAMAGED OR STOLEN PARTS AT HIS EXPENSE UNTIL THE WORK IS ACCEPTED INWRITING BY THE OWNER AND/OR GOVERNING AGENCY.7. EXTREME CARE SHALL BE EXERCISED IN EXCAVATING AND WORKING NEAR EXISTING UTILITIES.CONTRACTOR SHALL VERIFY THE LOCATION AND CONDITION OF ALL UTILITIES AND BE RESPONSIBLEFOR ANY DAMAGE. CONTRACTOR SHALL CONTACT UNDERGROUND SERVICE ALERT A MINIMUM OFTWO WORKING DAYS PRIOR TO DIGGING.8. THE CONTRACTOR SHALL KEEP THE PREMISES CLEAN AND FREE OF EXCESS EQUIPMENT,MATERIALS, AND RUBBISH INCIDENTAL TO HIS WORK.9. THE IRRIGATION DESIGN IS BASED ON THE METER AND/OR POINT OF CONNECTION SIZE AND WATERPRESSURE INDICATED ON THE WATER SOURCE / POINT OF CONNECTION NOTE ON THE PLANS.CONTRACTOR SHALL VERIFY THE PRESSURE PRIOR TO CONSTRUCTION. SHOULD A DISCREPANCYEXIST, NOTIFY THE LANDSCAPE ARCHITECT PRIOR TO BEGINNING CONSTRUCTION. DO NOTPROCEED WITH ANY IRRIGATION INSTALLATION WORK UNTIL ANY AND ALL WATER SUPPLY ANDPRESSURE ISSUES HAVE BEEN RESOLVED.10. CONTRACTOR SHALL MAKE POINT(S) OF CONNECTION (POC) AS NOTED ON THE PLANS. ALL FEESAND LOCAL REQUIREMENTS SHALL BE THE RESPONSIBILITY OF THE LANDSCAPE CONTRACTOR.11. IRRIGATION CONTRACTOR SHALL COORDINATE 120V AC POWER TO FINAL CONTROLLER LOCATIONWITH GENERAL CONTRACTOR AND/OR ELECTRICAL CONTRACTOR AS NECESSARY. IRRIGATIONCONTRACTOR SHALL PAY ALL ASSOCIATED FEES FOR ELECTRICAL SERVICE. IRRIGATIONCONTRACTOR SHALL BE RESPONSIBLE FOR MAKING ALL FINAL CONTROLLER CONNECTIONS PERLOCAL CODES.12. CONTRACTOR SHALL PROVIDE ALL EQUIPMENT REQUIRED TO PERFORM A MAINLINE PRESSURETEST. THE HYDROSTATIC TEST SHALL HOLD A MINIMUM OF 150 PSI FOR 3 HOURS OR MORE.CONTRACTOR SHALL CONTACT THE OWNER'S REPRESENTATIVE A MINIMUM OF 48 HOURS INADVANCE OF THE TEST FOR CERTIFICATION.13. CONTRACTOR SHALL THOROUGHLY FLUSH THE ENTIRE MAINLINE PRIOR TO INSTALLING REMOTECONTROL VALVES. ALL LATERAL LINES SHALL BE COMPLETELY FLUSHED PRIOR TO INSTALLINGHEADS AND NOZZLES. FOR DRIP SYSTEMS, ALL PIPING / TUBING DOWNSTREAM OF THE CONTROLVALVE SHALL BE THOROUGHLY FLUSHED PRIOR TO 'CLOSING' SYSTEM (FOR GRID SYSTEMS), ORBEFORE INSTALLING FLUSH VALVES.14. ALL WIRES SHALL BE SOLID COPPER, PLASTIC INSULATED, U.F. DIRECT BURIAL WIRE. ALL COMMONWIRE SHALL BE AWG #12 WHITE; ALL CONTROL WIRES SHALL BE AWG #14 RED OR BLACK.CONTROLLERS SHALL HAVE SEPARATE COLOR CODED COMMON WIRES AND CONTROL WIRES WHENTWO OR MORE CONTROLLERS ARE ON THE PROJECT.15. ALL CONTROL WIRES AND IRRIGATION PIPING THAT RUNS UNDER HARDSCAPE / PAVING SHALL BEENCASED IN PVC SLEEVES PER THE LEGEND. SLEEVES SHALL BE SIZED ACCORDING TO THESLEEVING CHART ON THE PLANS. SLEEVES SHALL BE STRAIGHT RUNS OF PVC PIPE WITH NOFITTINGS INSTALLED UNDER HARDSCAPED AREAS. IF WIDTH OF HARDSCAPE EXCEEDS A FULLLENGTH OF PIPE, USE BELLED END CONNECTION OR COUPLER WITHIN SLEEVE, ENSURING SLEEVE ISLARGE ENOUGH FOR THE ADDED DIAMETER OF THE CONNECTION.16. THE FINAL LOCATION FOR CONTROL VALVES AND QUICK COUPLERS SHALL BE APPROVED IN THEFIELD BY THE LANDSCAPE ARCHITECT OR THE OWNER'S AUTHORIZED REPRESENTATIVE. ALLVALVES AND QUICK COUPLERS SHALL BE LOCATED IN SHRUB AREAS WHEREVER POSSIBLE.17. THE CONTRACTOR SHALL HEAT BRAND VALVE NUMBERS OR OTHER MARKINGS AS CALLED FOR INTHE IRRIGATION DETAILS ON INSIDE AND OUTSIDE OF ALL VALVE BOX LIDS.18. ALL BRASS OR GALVANIZED CONNECTIONS SHALL BE COATED WITH TEFLON TAPE OR APPROPRIATEPIPE JOINT COMPOUND. ALL PVC TO PVC THREADED CONNECTIONS SHALL BE COATED WITH TEFLONTAPE. NO PIPE DOPE IS ALLOWED AT VALVE OR SPRINKLER HEAD CONNECTIONS. ANY PVC TO METALCONNECTIONS SHALL BE MADE WITH A MALE THREADED PVC FITTING AND A FEMALE THREADEDMETAL FITTING.19. ALL PVC SOLVENT-WELD CONNECTIONS SHALL BE MADE WITH SOLVENT-WELD MATERIALS ASRECOMMENDED BY THE PIPE MANUFACTURER. SOLVENT-WELD PRIMER SHALL BE APPLIED AT ALLCONNECTIONS.20. LOW HEAD DRAINAGE WILL NOT BE ALLOWED. CONTRACTOR TO DETERMINE IN THE FIELD WHICHHEADS DRAIN AFTER THE VALVE IS SHUT OFF. CONTRACTOR SHALL PROVIDE AND INSTALLADDITIONAL IN-LINE CHECK VALVES AS NEEDED AT NO ADDITIONAL COST TO THE OWNER.21. ALL PRESSURE SUPPLY LINES AND CONTROL WIRES TO HAVE 18" MINIMUM COVER. ALL LATERALLINES TO HAVE 12" MINIMUM COVER. FOR RECYCLED WATER SYSTEMS, PIPE DEPTH TO BEDETERMINED BY THE LOCAL GOVERNING AGENCY.22. THE RADIUS OF EACH HEAD IS TO BE ADJUSTED SO THAT HEAD-TO-HEAD COVERAGE IS MAINTAINED,BUT OVER SPRAY ON BUILDINGS, WALKS, WALLS, AND OTHER HARD SURFACES IS MINIMIZED. THISSHALL INCLUDE, BUT NOT BE LIMITED TO USING THE BEST NOZZLE RADIUS AND PATTERN, USINGPRESSURE COMPENSATING DEVICES FOR NOZZLES, USING ADJUSTABLE NOZZLES, OR USING THERADIUS ADJUST SCREW ON INDIVIDUAL NOZZLES.23. FINE TUNE EACH CONTROL VALVE FOR OPTIMUM OPERATION. THIS SHALL BE DONE BY TURNINGDOWN THE FLOW CONTROL OF THE VALVE UNTIL SYSTEM PERFORMANCE STARTS TO SUFFER. ATTHAT POINT, OPEN UP VALVE FLOW CONTROL ABOUT ONE-HALF TURN OR UNTIL THE VALVE IS JUSTOPEN ENOUGH FOR DESIRED OPERATION.24. CONTRACTOR SHALL INSTALL 2 EXTRA WIRES FROM CONTROLLER(S) TO EACH END OF THEMAINLINE. WIRES SHALL COME UP INTO ALL VALVE BOXES ALONG THE MAINLINE PATH WITH 36"EXPANSION COILS IN EACH BOX. SPARE WIRES SHALL BE COLOR-CODED DIFFERENTLY THAN OTHERCONTROL WIRES FOR EACH CONTROLLER.25. UPON COMPLETION OF THE PROJECT, THE CONTRACTOR IS TO TURN OVER TO THE OWNER THEFOLLOWING:25.a. A REPRODUCIBLE SET OF "AS-BUILT" DRAWINGS AND CONTROLLER CHART.25.b. 2 KEYS FOR EACH CONTROLLER / CONTROLLER ENCLOSURE (AS APPLICABLE).25.c. 2 QUICK COUPLER KEYS AND MATCHING HOSE SWIVELS.25.d. 100' OF EACH DRIP LINE TUBING SPECIFIED (AS APPLICABLE).25.e. 10 OF EACH DRIP EMITTER / FLUSH VALVE / DRIP SYSTEM APPARATUS SPECIFIED (ASAPPLICABLE).26. RECORD DRAWINGS - THE CONTRACTOR SHALL PROVIDE AND KEEP UP TO DATE A COMPLETERECORD SET OF PRINTS WHICH SHALL BE CORRECTED DAILY AND SHOW EVERY CHANGE FROM THEORIGINAL DRAWINGS. PRIOR TO FINAL INSPECTION, THE CONTRACTOR SHALL TRANSCRIBE ALLINFORMATION FROM THE RECORD SET TO A BLACK-LINE PRINT PROCURED FROM THE OWNER. ALLWORK SHALL BE NEAT AND LEGIBLE, LOCATING THE FOLLOWING ITEMS FROM PERMANENT POINTSOF REFERENCE: SHUT-OFF VALVES, MAINLINE AND CONTROL WIRE ROUTING, POC, BACKFLOWDEVICE, CONTROL VALVES, CONTROLLER, QUICK COUPLING VALVES, AND OTHER PERTINENTUNDERGROUND ITEMS.27. "CONTROLLER CHART" - UPON APPROVAL OF THE FINAL RECORD DRAWINGS, PROVIDE ONE CHARTFOR EACH CONTROLLER INSTALLED.27.A. THE CHART IS TO BE A REDUCED COPY OF THE APPROVED RECORD DRAWING (A BLACK-LINEPRINT REDUCED TO THE MAXIMUM SIZE THE CONTROLLER DOOR WILL ALLOW, COLORED WITH ADIFFERENT COLOR FOR EACH VALVE STATION'S AREA OF COVERAGE).27.B. WHEN COMPLETED AND APPROVED, THE CHART SHALL BE LAMINATED BETWEEN TWO (2) PIECESOF 20 MIL. CLEAR PLASTIC AND MOUNTED ON THE INSIDE OF THE CONTROLLER DOOR USINGVELCRO TAPE OR EQUAL.28. DRIP LINE IRRIGATION28.A. DRIP LINE TUBING IS SHOWN ON THE PLANS WITH A HATCH AND VALVE-ASSIGNMENT NUMBER INTHE HATCH. CONTRACTOR SHALL ADJUST LAYOUT AS DETERMINED NECESSARY IN THE FIELDTO MATCH THE ACTUAL SITE CONDITIONS, DIMENSIONS, ETC.28.B. ALL DRIP LINE SYSTEMS SHALL BE INSTALLED PER THE MANUFACTURER'S RECOMMENDATIONSAND DIRECTIONS. THIS SHALL INCLUDE, BUT NOT BE LIMITED TO SOIL TYPE CONSIDERATION,PLANT TYPE CONSIDERATION, SLOPES, TYPICAL TUBING LAYOUT, SUPPLY HEADERS, FLUSHHEADERS, FLUSH VALVES, SOIL STAPLES, AND OPERATION INDICATORS, ETC.28.C. EACH DRIP LINE SYSTEM SHALL HAVE A DRIP ZONE VALVE ASSEMBLY THAT INCLUDES APRESSURE REGULATOR AND IN-LINE FILTER PER THE IRRIGATION LEGEND.28.D. EXTEND PVC LATERAL LINE PIPING PER IRRIGATION LEGEND FROM THE DRIP ZONE VALVE INTOTHE PLANTING AREAS. ALL SUPPLY HEADERS AND FLUSH HEADERS SHALL BE PVC PIPING ORDRIP LINE TUBING AS SPECIFIED ON THE DRAWINGS.28.E. CONNECT THE DRIP LINE TUBING INTO THE PVC / POLY TUBING HEADERS PER THEMANUFACTURER'S DIRECTIONS, USING FITTINGS AS SUPPLIED BY THE MANUFACTURER OF THEDRIP LINE TUBING.28.F. DRIP LINE TUBING RUNS SHALL BE SPACED AT APPROXIMATELY 1 6" O.C. OR AS NOTED ON THEPLANS.28.G. TUBING SHALL RUN GENERALLY PARALLEL TO THE LONG AXIS OF THE PLANTING AREAS. THEEXCEPTION TO THIS WOULD BE SLOPED AREAS WHERE THE TUBING SHALL RUN PARALLEL TOTHE SLOPE CONTOURS.28.H. FLUSH VALVES SHALL BE INSTALLED A THE TERMINAL ENDS AND/OR LOW POINTS OF ZONES INALL DIRECTIONS. AIR RELEASE VALVES, WHERE REQUIRED FOR BURIED SYSTEMS, SHALL BEINSTALLED AT THE HIGH POINTS OF EACH ZONE. REFER TO THE MANUFACTURER'S DIRECTIONSFOR THE QUANTITY OF FLUSH VALVES AND AIR-RELEASE VALVES RECOMMENDED FOR EACHZONE.28.I. DRIP LINE TUBING SHALL BE INSTALLED BELOW FINISH GRADE (PER LEGEND), STAPLED DOWN,AND COVERED WITH MULCH/BACKFILL PER THE PLAN.28.J. EACH DRIP LINE ZONE SHALL INCLUDE AN OPERATION INDICATOR. THE OPERATION INDICATORSHALL BE INSTALL AT THE FARTHEST POINT AWAY FROM THE ZONE DRIP VALVE ASSEMBLY.28.K. ALL FITTINGS USED FOR DRIP LINE TUBING CONNECTIONS AND DRIP LINE TUBING TO PVCCONNECTIONS SHALL BE AS PRODUCED, SUPPLIED, AND RECOMMENDED BY THEMANUFACTURER OF THE DRIP LINE TUBING.2" MINIMUMLATERAL LINE CONNECTION TO DRIPLINE AREAS. SCH. 40 PVC NON-PRESSURE LATERAL LINE -12" MIN. COVER (PURPLE PIPE FOR RECYCLED WATER REQUIRED)PLAN SIZE KWIRE PULL BOXPN/ANEW CONTROL WIRE CONNECTION RUN TO UPDATED CONTROLLERQ / P·ADJUST EXISTING SPRINKLER HEAD LAYOUT AND NOZZLES TO PROVIDE IRRIGATION COVERAGE TONEW AREA LIMITS.·PROTECT SYSTEMS IN PLACE IF NOT DISTURBED.·ADJUST HEAD SPACING BY ADDING, REMOVING, OR RELOCATING SPRINKLER HEADS. MATCHPRECIPITATION RATES OF NOZZLES IN EACH VALVE ZONE.·ALL NEW SPRINKLER HEADS WILL HAVE FACTORY PURPLE CAPS FOR RECYCLED WATER·RELOCATE EXISTING VALVES AS NEEDED. CONNECT TO ORIGINAL WATER SOURCE.·DO NOT EXCEED THE RECOMMENDED FLOW RATE OF EXISTING VALVES USED.·NO TURF AREAS WILL BE CONNECTED TO VALVES SERVING SHRUB AREAS.·NO SHRUB AREAS WILL BE CONNECTED TO VALVES SERVING TURF AREAS.·ADJUST FINAL CONDITION TO PREVENT OVERSPRAY OF RECYCLED WATER ONTO WALKS AND SEATINGAREAS.EXISTING TURF / SHRUB AREAS TO BE ADJUSTEDDETAILF / K / R95% CONSTRUCTION DOCS 08/01/2025 7/25/2025
L6.01IRRIGATIONPLAN1"=20'-0",This document and all other project documents,ideas, aesthetics and designs incorporatedtherein are instruments of service. All projectdocuments are copyright protected, are theproperty of LPA, Inc. (LPA) and cannot be lawfullyused in whole or in part for any project or purposeexcept as set forth in the contractual agreementbetween LPA and its Client. The unauthorizeddisclosure and/or use of the project documents(including the creation of derivative works), maygive rise to liability for copyright infringement,unlawful disclosure, use or misappropriation ofproperty rights held by LPA. The unauthorizeduse of the project documents will give rise to therecovery of monetary losses and damagesincluding attorney fees and costs for which theunauthorized user will be held liable.Project documents describe the design intent ofthe work and are not a representation of as-builtor existing conditions. LPA is not responsible forany discrepancies between the project documentsand the existing conditions.© LPA, Inc.Developed forJob NumberDate PublishedChecked ByScaleRevision Date ARCHITECTURE ENGINEERING INTERIORSLANDSCAPE ARCHITECTURE PLANNING949-261-1001 Office949-260-1190 FaxLPADesignStudios.comSubmittal Date 5301 California Avenue, Suite 100Irvine, California 92617DOWNEY SPACE SHUTTLE EXHIBIT
AND EDUCATION BUILDING
12400 COLUMBIA WAY
DOWNEY. CA 90242
CITY OF DOWNEY3055401KH, RG, JH100% SCHEMATIC DESIGN 10/28/2022 50% DESIGN DEVELOPMENT 12/02/2022
100% DESIGN DEVELOPMENT 01/03/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CD PRICING SET 08/01/25IRRIGATION PLANEXISTING BLDGCOLUMBIA WAY LIMI
T
O
F
W
O
R
K
LIMIT OF WORK
LIMIT OF WORKEDUCATION BLDG.STEMBLDG.PROPERTY LINEPROPERTY LINEPROPERTY LINE
LIMIT OF WORKLIMIT OF WORK
CONGRESSMAN STEVE HORN WAYLIMIT OF WORK
05NOTES:A. CONTRACTOR WILL VERIFY EXISTING IRRIGATION SYSTEM IS 100% FUNCTIONAL PRIOR TO BEGINNING OFWORK. ANY EQUIPMENT OR SYSTEMS FOUND TO BE IN NON-FUNCTIONAL CONDITION WILL BE DOCUMENTEDAND REPORTED TO OWNER'S REPRESENTATIVE.B. CONTRACTOR TO PROTECT EXISTING IRRIGATION IN PLACE DURING CONSTRUCTION. ANY DAMAGED /REMOVED IRRIGATION WILL BE REPLACED / REPAIRED IN 100% WORKING ORDER AT CONTRACTOR EXPENSE.C. ALL IRRIGATION CONTROL WIRES CONNECTED TO EXISTING CONTROLLER WILL BE RECONNECTED TOUPGRADED CONTROLLER. CONFIRM PROPER CONTROLLER SPECIFICATION, OPERATION, AND INSTALLATIONWITH OWNER'S REPRESENTATIVE AND CALSENSE REPRESENTATIVE PRIOR TO STARTING WORK AND UPONCOMPLETION OF WORK. CONTACT JON DRONGOWSKI @ CALSENSE (760.580.9428)D. CONTRACTOR WILL BE RESPONSIBLE FOR IRRIGATION OF EXISTING PLANT MATERIAL DURING CONSTRUCTION.WHEN SYSTEM IS SHUT-DOWN FOR IRRIGATION EQUIPMENT INSTALLATION, CONTRACTOR WILL HAND WATERALL AREAS IMPACTED BY THE SHUT-DOWN. CONTRACTOR WILL BE RESPONSIBLE FOR THE HEALTH OFEXISTING PLANT MATERIAL. IF SAID PLANT MATERIAL'S HEALTH DETERIORATES, CONTRACTOR WILL BERESPONSIBLE FOR THE REPLACEMENT AT THE SAME SIZE AS THE EXISTING MATERIAL.E. ALL RECYCLED WATER EQUIPMENT WILL BE LABELED AND TAGGED PER DISTRICT AND HEALTH DEPARTMENTSTANDARD. THIS WILL INCLUDE BUT NOT BE LIMITED TO PURPLE ID TAGS, PURPLE PLASTIC VALVE BOXES, ANDFACTORY PURPLE SPRINKLER HEADS.F. CONTRACTOR WILL CONTACT JEFF DRONGOWSKI @ CALSENSE (760-580-9428) TO CONFIRM CONTROLLERCOMMUNICATION AND FUNCTIONING WITH POINT OF CONNECTION PRIOR TO CONSTRUCTION. NO WORK,INCLUDING EQUIPMENT ORDERING WILL BE DONE WITHOUT CALSENSE'S COORDINATION AND APPROVAL OFTHE UPGRADE TO THIS SYSTEM.G. CONTRACTOR WILL CONTACT ON-SITE MAINTENANCE STAFF AND CONFIRM POINT OF CONNECTION TIE IN.THIS INCLUDES VERIFYING EXISTING MAINLINE LOCATION, WHICH CONTROLLER MANAGES THAT MAINLINEWATER FLOW, AND IF THE SPECIFIED CONTROLLER CAN ACTIVATE THE PUMP START RELAY (IF POINT OFCONNECTION IS ON BOOSTER PUMP SYSTEM).C261"13.6DRIPLINEC221"15.7DRIPLINEC241"17.4ROTARYC251"7.5DRIPLINEC271"16.6ROTARYC281"10.7DRIPLINEC311"9.2DRIPLINEC301"11.6DRIPLINEC291"11.0DRIPLINEC201"8.8DRIPLINEC211"10.4DRIPLINEC191"10.0DRIPLINEC181"9.2DRIPLINEC171"17.4ROTARYC231"12.7DRIPLINE95% CONSTRUCTION DOCS 08/01/2025 7/25/2025
L6.02IRRIGATIONCALCULATIONS & NOTESThis document and all other project documents,ideas, aesthetics and designs incorporatedtherein are instruments of service. All projectdocuments are copyright protected, are theproperty of LPA, Inc. (LPA) and cannot be lawfullyused in whole or in part for any project or purposeexcept as set forth in the contractual agreementbetween LPA and its Client. The unauthorizeddisclosure and/or use of the project documents(including the creation of derivative works), maygive rise to liability for copyright infringement,unlawful disclosure, use or misappropriation ofproperty rights held by LPA. The unauthorizeduse of the project documents will give rise to therecovery of monetary losses and damagesincluding attorney fees and costs for which theunauthorized user will be held liable.Project documents describe the design intent ofthe work and are not a representation of as-builtor existing conditions. LPA is not responsible forany discrepancies between the project documentsand the existing conditions.© LPA, Inc.Developed forJob NumberDate PublishedChecked ByScaleRevision Date ARCHITECTURE ENGINEERING INTERIORSLANDSCAPE ARCHITECTURE PLANNING949-261-1001 Office949-260-1190 FaxLPADesignStudios.comSubmittal Date 5301 California Avenue, Suite 100Irvine, California 92617DOWNEY SPACE SHUTTLE EXHIBIT
AND EDUCATION BUILDING
12400 COLUMBIA WAY
DOWNEY. CA 90242
CITY OF DOWNEY3055401KH, RG, JH100% SCHEMATIC DESIGN 10/28/2022 50% DESIGN DEVELOPMENT 12/02/2022
100% DESIGN DEVELOPMENT 01/03/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CD PRICING SET 08/01/2595% CONSTRUCTION DOCS 08/01/2025 7/25/2025
L6.03IRRIGATIONDETAILSThis document and all other project documents,ideas, aesthetics and designs incorporatedtherein are instruments of service. All projectdocuments are copyright protected, are theproperty of LPA, Inc. (LPA) and cannot be lawfullyused in whole or in part for any project or purposeexcept as set forth in the contractual agreementbetween LPA and its Client. The unauthorizeddisclosure and/or use of the project documents(including the creation of derivative works), maygive rise to liability for copyright infringement,unlawful disclosure, use or misappropriation ofproperty rights held by LPA. The unauthorizeduse of the project documents will give rise to therecovery of monetary losses and damagesincluding attorney fees and costs for which theunauthorized user will be held liable.Project documents describe the design intent ofthe work and are not a representation of as-builtor existing conditions. LPA is not responsible forany discrepancies between the project documentsand the existing conditions.© LPA, Inc.Developed forJob NumberDate PublishedChecked ByScaleRevision Date ARCHITECTURE ENGINEERING INTERIORSLANDSCAPE ARCHITECTURE PLANNING949-261-1001 Office949-260-1190 FaxLPADesignStudios.comSubmittal Date 5301 California Avenue, Suite 100Irvine, California 92617DOWNEY SPACE SHUTTLE EXHIBIT
AND EDUCATION BUILDING
12400 COLUMBIA WAY
DOWNEY. CA 90242
CITY OF DOWNEY3055401KH, RG, JH100% SCHEMATIC DESIGN 10/28/2022 50% DESIGN DEVELOPMENT 12/02/2022
100% DESIGN DEVELOPMENT 01/03/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CD PRICING SET 08/01/25 6"1. FINISH GRADE2. CLEAN BACKFILL WITH ALL ROCKS 1" OR LARGER REMOVED - 90% COMPACTIONREQUIRED - SEE SPECS3. NON-PRESSURE LATERAL LINE PER LEGEND (SNAKE IN TRENCH)4. PRESSURE MAINLINE PER LEGEND (SNAKE IN TRENCH)5. CONTROL WIRES - INSTALL BELOW PRESSURE MAINLINE6. UNDISTURBED NATIVE SOIL**SEE LEGEND FOR MINIMUM BURIAL DEPTHNOTES:BUNDLE AND TAPE WIRES AT 10' O.C. PIGTAIL AND LOOP WIRES AT ALL CHANGES INDIRECTION. SPLICING OF WIRE RUNS IS NOT PERMITTED WITHOUT PRIOR APPROVAL FROMOWNER AND LANDSCAPE ARCHITECT. RUN CONTROL WIRES IN SAME TRENCH AS MAINLINEWHERE POSSIBLE. INSTALL 12"x12"x12" CONCRETE THRUST BLOCKS AT ALL CHANGES INDIRECTION OF PRESSURE MAINLINE (45'S, 90'S, TEES, ETC.) AND AT ALL TERMINAL POINTS.**6"6"**6" MIN6" MIN1. HARDSCAPING AND AGGREGATE (TYPICAL)2. CLEAN SAND BACKFILL - COMPACT TO MATCH DENSITY OF NATIVE SOIL3. LATERAL LINE IN SCH 40 PVC SLEEVE4. PRESSURE MAINLINE IN SCH 40 PVC SLEEVE5. CONTROL WIRES IN SCH 40 PVC SLEEVE6. UNDISTURBED NATIVE SOILNOTES:SIZE ALL SLEEVES PER THE IRRIGATION PLANS. EXTEND SLEEVES 12" MINIMUMBEYOND EDGE OF HARDSCAPE (AT EACH END) INTO THE PLANTING AREAS.* SEE LEGEND FOR MINIMUM PIPE BURIAL DEPTHS.6"6"6"* *1. QUICK COUPLING VALVE PER IRRIGATION LEGEND2. #4x36" REBAR SUPPORT STAKE (2 REQUIRED)3. STAINLESS STEEL CLAMP (2 REQUIRED)4. FINISH GRADE5. 10" ROUND PLASTIC VALVE BOX WITH LOCKING LID (NDS #312BCB)HEAT BRAND "QCV" ON LID IN 2" HIGH BLOCK LETTERS6. 1"x6" SCH 80 PVC NIPPLE7. 1" SCH 40 PVC STREET ELL (3 REQUIRED)8. COMMON BRICK SUPPORTS (3 REQUIRED)9. 1"x12" SCH 80 PVC NIPPLE10. 1" SCH 40 PVC ELL (SxT)11. 1" SCH 40 PVC MAINLINE (12" MINIMUM LENGTH)12. SCH 40 PVC MAINLINE FITTING (TEE OR ELL) WITH 1" SLIP OUTLET13. MAINLINE PIPING PER IRRIGATION LEGEND (PLAN SIZE)14. NATIVE SOIL15. FILL BASE OF BOX WITH PEA GRAVEL* 1/2" IN TURF AREAS, 1" IN SHRUB AREAS / 3" IN SHRUB AREAS WITH MULCH2"*6"36" 18"-24"FVFV1. DRIP ZONE VALVE PER LEGEND2. PVC LATERAL LINE - SIZE PER PLAN3. PVC SUPPLY HEADER - SIZE PER PLAN (LOCATE IN HYDRAULICCENTER OF ZONE)4. SUPPLY HEADER CROSS CONNECTION5. SUPPLY HEADER TEE CONNECTION6. DRIP LINE PER LEGEND7. PVC FLUSH HEADER ELBOW CONNECTION8. PVC FLUSH HEADER TEE CONNECTION9. PVC FLUSH HEADER - 3/4" UNLESS NOTED OTHERWISE10. FLUSH VALVE PLUMBED TO FLUSH HEADER AT LOW POINT11. OPERATION INDICATOR - INSTALL ON TUBING AT FARTHESTPOINT FROM DRIP ZONE VALVE12. AIR RELEASE VALVE AT HIGH POINT (IF SPECIFIED)EQUALEQUALROW SPACING PER PLANROW SPACING PER PLANLAYOUT OUTEMITTERS INTRIANGULARPATTERNARNOTES:THE TOTAL LENGTH OF ALLINTERCONNECTED DRIP LINE SHALL NOTEXCEED THE MAXIMUM RUN LENGTHRECOMMENDED BY THE MANUFACTURER.REFER TO THE MANUFACTURER'SGUIDELINES AND DETAILS FOR THEINSTALLATION OF ALL DRIP LINE SYSTEMS.QUANTITY AND LOCATION OF ALL FLUSHVALVES AND AIR RELEASE VALVES SHALLMEET THE MANUFACTURER'S GUIDELINES.CENTER FEED ALL DRIPLINE SYSTEMSWHEN POSSIBLE.*12"1. FINISH GRADE2. 6" ROUND PLASTIC VALVE BOX WITH SNAP-ON LID (ND #107EBC) HEATBRAND "FIVE" ON LID IN 2" HIGH BLOCK LETTERS3. MANUAL FLUSH VALVE (NETAFIM TLSOV OR APPROVED EQUAL)4. POLY TUBING - DEPTH PER IRRIGATION PLAN5. COMMON BRICK SUPPORTS (2 REQUIRED)6. FILL BASE WITH 1 CUBIC FOOT OF PEA GRAVEL7. NATIVE SOIL8. FILTER FABRIC UNDER / AROUND GRAVEL* 1/2" IN TURF AREAS, 2"-3" IN SHRUB AREAS2" MIN.12"1. REMOTE CONTROL VALVE PERIRRIGATION LEGEND2. SCH 40 PVC MALE ADAPTER(2 REQUIRED) VALVE SIZE3. RECTANGULAR PLASTIC VALVE BOX WITHLOCKING LID (NDS #314BCB) HEATBRAND STATION NUMBER ON LID IN 2"HIGH BLOCK LETTERS4. FINISH GRADE5. PVC LATERAL LINE PER IRRIGATIONLEGEND (VALVE SIZE)6. SCH 40 PVC 45 DEGREE ELL7. SCH 40 PVC 45 DEGREE ELL (BUSH UPTO LATERAL LINE PLAN SIZE)8. RECTANGULAR PLASTIC VALVE BOXEXTENSION (NDS #214-6)9. COMMON BRICK SUPPORTS (4 REQUIRED)4"*18"-24"10. WATERPROOF WIRE CONNECTORS(2 REQUIRED)11. #14 UF WIRES TO CONTROLLER(COLOR CODED)12. I.D. TAG WITH STATION NUMBERPRINTED ON IT (CHRISTY'S #ID-STD-Y1)13. SCH 40 PVC ELL (VALVE SIZE)14. MAINLINE PIPING PER IRRIGATIONLEGEND (VALVE SIZE)15. SCH 40 PVC TEE (OUTLET TO BEVALVE SIZE)16. MAINLINE PIPING PER IRRIGATIONLEGEND (PLAN SIZE)17. FILL BASE OF BOX WITH PEA GRAVEL18. NATIVE SOIL* 1/2" IN TURF AREAS, 1" IN SHRUB AREAS2"4"6"4"4"**18"-24"1. ** REMOTE CONTROL VALVE2. RECTANGULAR JUMBO PLASTIC VALVEBOX WITH LOCKING LID (NDS #318BCB)HEAT BRAND STATION NUMBER AND "DZ" ONLID IN 2" HIGH BLOCK LETTERS3. I.D. TAG WITH STATION NUMBER PRINTEDON IT (CHRISTY'S #ID)4. ** SCH 40 PVC BALL VALVE5. ** SCH 80 PVC CLOSE NIPPLE6. FINISH GRADE7. NATIVE SOIL8. SCH 40 PVC MALE ADAPTER9. PVC PIPING TO SYSTEM (CONNECT ANDADAPT AS NECESSARY)10. RECTANGULAR PLASTIC VALVE BOXUSED AS EXTENSION (NDS #318B)11. ** PRESSURE REGULATOR12. ** Y-FILTER13. FILL BASE OF BOX WITH PEA GRAVEL14. COMMON BRICK SUPPORTS(4 REQUIRED)15. MAINLINE PIPING PER IRRIGATIONLEGEND (PLAN SIZE)16. SCH 40 PVC MAINLINE FITTING WITH 1"OUTLET17. 1" SCH 40 PVC MAINLINE PIPING(LENGTH AS REQUIRED)18. 1" SCH 40 PVC ELL19. #14 UF WIRES TO CONTROLLER(COLOR CODED)20. WATERPROOF WIRE CONNECTOR(2 REQUIRED)** 1/2" IN TURF AREAS, 1" IN SHRUB AREAS /3" IN SHRUB AREAS WITH MULCH** INCLUDED IN DRIPZONE KIT (SEEIRRIGATION LEGEND)4"18"-24"2"4"1. BALL VALVE PER IRRIGATION LEGEND (MAINLINE SIZE)2. RECTANGULAR PLASTIC VALVE BOX WITH LOCKING LID (NDS#314BCB) HEAT BRAND "BV" ON LID IN 2" HIGH BLOCK LETTERS3. FINISH GRADE4. SCH 40 PVC MALE ADAPTER (2 REQUIRED)5. SCH 40 PVC 45 DEGREE ELL (4 REQUIRED)6. NATIVE SOIL7. MAINLINE PIPING PER IRRIGATION LEGEND8. COMMON BRICK SUPPORTS (4 REQUIRED)9. FILL BASE OF BOX WITH PEA GRAVEL** 1/2" IN TURF AREAS, 1" IN SHRUB AREAS / 3" IN SHRUB AREASWITH MULCHNOTES:OFF-SET VALVE BOX AROUND BALL VALVE TO ALLOW SPACE FORFULL MOVEMENT OF THE BALL VALVE HANDLE.**1. FINISH GRADE OF MULCH LAYER2. MULCH TOP DRESSING PER PLANTING PLAN3. POLY TUBING PER IRRIGATION LEGEND4. FINISH GRADE5. STEEL TUBING-SOIL STAPLE (NETAFIM TLS6 OR APPROVED EQUAL)6. NATIVE SOIL7. DEPTH OF MULCH PER PLANTING PLAN OR SPECIFICATIONSNOTES:LOCATE STAPLES ALONG TUBING AT ABOUT 4' O.C. AND AT ALL FITTINGS (TEES, ELLS,ETC.) AND CHANGES IN DIRECTION OF TUBING, AS NEEDED. BURY TUBING PER THEIRRIGATION PLAN / NOTES.3"-4"CEBBALL VALVETRENCHINGSLEEVINGDRIPLINE - TUBINGDDRIPLINE CONTROL VALVE ASSEMBLYFJSPRINKLER IN GRASSPAVE2 ZONEGQUICK COUPLER VALVEHDRIPLINE - MANUAL FLUSH VALVEIECOINDICATORKSPRINKLER - ROTARYLREMOTE CONTROL VALVEADRIPLINE - LAYOUT1.5" MIN.1. PLANT MATERIAL IN GRASSPAVE2 RING2. COMPACTED SANDY GRAVEL ROAD BASE PER MANUF.3. SPRINKLER HEAD4. GRASSPAVE2 UNIT5. EDGING, CONC. BORDER, OR SIDEWALK6. COMPACTED SUBGRADENOTES:NO POP-UP HEADS WILL BE ABOVE FINAL FINISH GRADE OFGRASSPAVE2 UNITS (1.5" MIN. BELOW TOP OF RINGS). ACCOUNTFOR FINAL SETTLING OF UNITS.CUT AND REMOVE GRASSPAVE2 RINGS AND GRID TO ACCOMODATEIRRIGATION HEAD PER MANUF. SPECIFICATIONS1. FINISH GRADE2. NATIVE SOIL / BACKFILL PER SPECS.3. HUNTER ECO INDICATOR (PER LEGEND)4. FLUSH HEADER PIPING PER PLAN.5. 1/2" MARLEX STREET ELL6. FLUSH HEADER FITTING WITH 1/2" FEMALE THREADEDOUTLET - ADAPT AS NECESSARY7. 1/2" SCH 80 PVC THREADED NIPPLE8. 1/2" SCH 40 PVC STREET ELL T X T9. 1/2" MARLEX STREET ELLNOTES:USE TEFLON TAPE ON ALL PVC TOPVC CONNECTIONS; NO PIPE DOPEALLOWED. ADAPT TO DRIP SYSTEMAS REQUIRED (POLY OR PVC).LOCATE FLUSH / INDICATORASSEMBLY IN AREA WITH EASYACCESS FOR MAINTENANCE.12"1"1. FINISH GRADE2. NATIVE SOIL / BACKFILL PER SPECIFICATIONS3. 6" POP-UP ROTARY HEAD & NOZZLE PER LEGEND4. 1/2" MARLEX STREET ELL5. 1/2" SCH 40 PVC STREET ELL TxT6. 1/2" x 12" MIN. SCH 80 PVC THREADED NIPPLE7. 1/2" MARLEX STREET ELL8. SCH 40 PVC LATERAL LINE FITTING WITH1/2" FEMALE THREADED OUTLET9. LATERAL LINE PIPING PER LEGENDNOTES:USE TEFLON TAPE ON ALL PVC TOPVC CONNECTIONS; NO PIPE DOPEALLOWED. SET PERIMETER HEADS4"-6" FROM CURBS AND WALKSAND 6"-12" FROM VERTICALOBJECTS SUCH AS FENCES ANDWALLS, ETC. ONLY USE BOTTOMINLET OF HEAD.12"NOTE:ALL BOXES WILL BE PURPLE PLASTIC LABELEDFOR RECYCLED WATER PER DISTRICT STD.ALL VALVES WILL BE TAGGED WITH PURPLERECYCLED WATER MARKER LABELS PERDISTRICT STD.ALL EQUIPMENT WILL BE INSTALLED WITHPURPLE RECYCLED CAPS/HANDLES ASAPPLICABLE PER DISTRICT STDS.1/2" TURF / 1" SHRUB AREASSEE DETAIL 'E' FOR GRASSPAVE AREA95% CONSTRUCTION DOCS 08/01/2025 7/25/2025
L6.04IRRIGATIONDETAILSThis document and all other project documents,ideas, aesthetics and designs incorporatedtherein are instruments of service. All projectdocuments are copyright protected, are theproperty of LPA, Inc. (LPA) and cannot be lawfullyused in whole or in part for any project or purposeexcept as set forth in the contractual agreementbetween LPA and its Client. The unauthorizeddisclosure and/or use of the project documents(including the creation of derivative works), maygive rise to liability for copyright infringement,unlawful disclosure, use or misappropriation ofproperty rights held by LPA. The unauthorizeduse of the project documents will give rise to therecovery of monetary losses and damagesincluding attorney fees and costs for which theunauthorized user will be held liable.Project documents describe the design intent ofthe work and are not a representation of as-builtor existing conditions. LPA is not responsible forany discrepancies between the project documentsand the existing conditions.© LPA, Inc.Developed forJob NumberDate PublishedChecked ByScaleRevision Date ARCHITECTURE ENGINEERING INTERIORSLANDSCAPE ARCHITECTURE PLANNING949-261-1001 Office949-260-1190 FaxLPADesignStudios.comSubmittal Date 5301 California Avenue, Suite 100Irvine, California 92617DOWNEY SPACE SHUTTLE EXHIBIT
AND EDUCATION BUILDING
12400 COLUMBIA WAY
DOWNEY. CA 90242
CITY OF DOWNEY3055401KH, RG, JH100% SCHEMATIC DESIGN 10/28/2022 50% DESIGN DEVELOPMENT 12/02/2022
100% DESIGN DEVELOPMENT 01/03/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CD PRICING SET 08/01/25 12" MINIMUMSIDEWALK24"METER BOX W/METERPOTABLE SERVICE LINE10' MINIMUM TO POTABLEMAINLINE IN STREETNOTE:CURB & GUTTERRECYCLED WATERIRRIGATION MAINLINEW/SLEEVEVERTICAL CLEARANCE OF 12" MINIMUM IS MANDATORY WHEN CROSSING PATHOF A POTABLE WATER LINE. INSTALLATION OF RECYCLED WATER IRRIGATIONMAINLINE 24" FROM FACE OF SIDEWALK WILL PROVIDE THE NECESSARY10' HORIZONTAL CLEARANCE FROM POTABLE MAINLINE IN THE STREET.FINISH GRADE9"DEPTHLATERAL DEPTH(SEE LEGEND)MAINLINE DEPTH(SEE LEGEND)PURPLE COLORED PRESSURE MAINLINEPIPEPOTABLE MAINLINE(SEE IMPROVEMENT DWGS.)12" MIN. REQUIRED VERICAL SEPARATIONRECYCLED WATER IRRIGATION MAINLINEWHERE POTABLE LINES AND CONSTANT PRESSURE RECYCLED WATER LINES CROSS,THE RECYCLED LINES SHALL BE INSTALLED BELOW THE POTABLE WATER LINE INCLASS 200 PURPLE COLORED PVC SLEEVE. THE SLEEVE SHALL EXTEND 10 FEET ONEITHER SIDE OF THE POTABLE LINE FOR A TOTAL OF 20 FEET.PURPLE COLORED LATERALNON-PRESSURE RECYCLED WATER PIPEFROM SPRINKLER HEAD TO SPRINKLERHEAD. WHENEVER THE LINE CROSSESTHE POTABLE PIPE, NO SLEEVESREQUIRED.TRENCH MARKER TAPE12"PER DISTICT1'-9"1"1"EQEQ18"1"1'-6"3"12"1. STAINLESS STEEL BOLTS WITH LOCKINGWASHERS AND STAINLESS STEEL NUTS2. PAINTED ALUMINUM RECYCLED WATERIDENTIFICATION SIGN - USE CHRISTY'S#ID-SIGN 3.5 OR EQUAL AS APPROVED BY THEWATER DISTRICT AND DHS3. 2 1/2" GALVANIZED CHANNEL4. FINISH GRADE5. CONCRETE FOOTING6. NATIVE SOIL - COMPACT TO MINIMUM 90%FOR WATER CONSERVATIONTHIS PROPERTY IS IRRIGATEDWITH RECYCLED WATERCOMO PARTE DE LOS ESFUERZOS DECONSERVACION DE LA CIUDAD, ESTA AGUA HASIDO TRATADA CON EL PROPOSITO DE SERUTILIZADA UNICAMENTE PARA RIGO.DO NOT DRINKCHRISTY'S #ID-SIGN 3.5ONRECYCLED WATER SIGNAGERECYCLED WATER PIPE AND POTABLE WATER PIPECROSSINGPOTABLE SERVICE LINE CROSSINGMPULL BOXP18"-24"1. FINISH GRADE2. WATER PROOF WIRE CONNECTORS (ONEFOR EACH SPLICE)3. CONTROL WIRES / COMMON WIRES PERIRRIGATION LEGEND4. RECTANGULAR PLASTIC VALVE BOX WITHLOCKING LID (NDS #314BCB) HEAT BRAND"PB" ON LID IN 2" HIGH BLOCK LETTERS5. NATIVE SOIL6. COMMON BRICK SUPPORTS (4 REQUIRED)7. WIRES TO / FROM LANDSCAPED AREAS8. COIL WIRES IN BOX - MINIMUM 24" COIL*9. FILL BASE OF BOX WITH PEA GRAVEL - 2CU. FT. MIN.10. WIRES TO / FROM CONTROLLER(S)* 1/2" IN TURF AREAS, 1" IN SHRUB AREASNOTES:WIRE SPLICES ARE ONLY ALLOWED WITH PREAPPROVAL FROM LANDSCAPE ARCHITECTAND / OR OWNER. ALL CONTROL WIRESPLICES SHALL BE INSTALLED IN PULL BOXES.ALL SPLICES SHALL BE MADE WITHWATERPROOF WIRE CONNECTORS.1. LOW VOLTAGE WIRES - 3 MAXIMUM2. WIRES PASS THROUGH GROOVES INTUBE LID TO ALLOW LID TO CLOSE3. CLOSE TUBE LID AFTER WIRE ISINSERTED INTO TUBE4. POLY TUBE PRE-FILLED WITHWATERPROOF GEL5. LOCK TABS PREVENT WIRE REMOVALONCE CONNECTOR IS INSERTED6. SCOTCHLOK ELECTRICAL SPRINGCONNECTOR - WIRES SHALL BEPRE-STRIPPED OF 1/2" OF THEINSULATION PRIOR TO INSERTION INTOTHE CONNECTOR - TWIST CONNECTORONTO WIRES TO SEAT FIRMLYINSERT SCOTCHLOK CONNECTOR ANDWIRES INTO TUBE UNTIL THE CONNECTORPASSES THE LOCK TABS.NOTES:WIRE CONNECTOR SHALL BE A 3M DBYDIRECT BURY SPLICE KIT.KIT SHALL INCLUDE A SCOTCHLOK SPRINGCONNECTOR, A POLYPROPYLENE TUBE ANDA WATERPROOF SEALING GEL. TUBE SHALLBE SUPPLIED PRE-FILLED WITH GEL.DIRECT BURY SPLICE KIT SHALL BE USED TOELECTRICALLY CONNECT 2-3 #14 OR 2 #12PRE-STRIPPED COPPER WIRES. LARGER ORGREATER QUANTITIES OF WIRES SHALLREQUIRE A LARGER APPROVED WIRECONNECTOR.CONNECTIONS TO HAVE NO EXPOSEDWIRING.WIRE CONNECTIONQ1. FINISH GRADE2. NATIVE SOIL / BACKFILL PER SPECIFICATIONS3. POP-UP ROTOR HEAD & NOZZLE PER LEGEND4. 3/4" MARLEX STREET ELL5. 3/4" SCH 40 PVC STREET ELL TxT6. 3/4" x 12" MIN. SCH 80 PVC THREADED NIPPLE7. 3/4" MARLEX STREET ELL8. SCH 40 PVC LATERAL LINE FITTING WITH3/4" FEMALE THREADED OUTLET9. LATERAL LINE PIPING PER LEGEND12"NOTES:USE TEFLON TAPE ON ALL PVE TOPVC CONNECTIONS; NO PIPE DOPEALLOWED. SET SET PERIMETERHEADS 4"-6" FROM CURBS ANDWALKS AND 6"-12" FROM VERTICALOBJECTS SUCH AS FENCES ANDWALLS, ETC. INSTALL HEADS +/- 1/2"ABOVE FINISH GRADE.1/2"SPRINKLER - ROTOR (EXISTING AREAS)RNOTE:ALL BOXES WILL BE PURPLE PLASTIC LABELEDFOR RECYCLED WATER PER DISTRICT STD.ALL VALVES WILL BE TAGGED WITH PURPLERECYCLED WATER MARKER LABELS PERDISTRICT STD.ALL EQUIPMENT WILL BE INSTALLED WITHPURPLE RECYCLED CAPS/HANDLES ASAPPLICABLE PER DISTRICT STDS.95% CONSTRUCTION DOCS 08/01/2025 7/25/2025
xxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxWFHPHPHPHPHPHPHPHPHPSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAASMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFAAAAAAAAAAAAAAAAAAAAHPHPHPHPCACACACACACACACACACACASMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMHPHPHPHPHPHPHPLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLAAAAAAAAAASMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMWFWFWFWFWFCACACACACACACACACACACACACACACACACACAAAAAAAAAAAAAAAAAAAAAAAAAAASMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMHPHPHPHPHPHPHPHPHPHPHPHPHPHPHPHPHPHPHPHPHPLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAASMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMCACACACACACACACACACACACACACACACACACACACACACACACACACACACAAAAAAAAAAAAAAAAAAAAAAAAAAAAASMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMAAAAAAAAAAAAAAAAAAAAAAAAAAAASMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMAAAAAAAAAAAAAAAAAAAAAAAASMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLCACACACACACACACACACACACAAAAAAAAAAAAAAAAAAAAASMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMHPAAAAAAAAAAHPHPHPHPHPSMSMSMSMSMSMSMSMSMSMSMSMWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFWFAAAAAAAAAAAAAALLLLLLLLLLLLLLLLLLLLLLLLHPHPHPHPHPHPHPHPHPHPHPHPHPHPHPHPHPHPHPLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLHPLLLLLLLLLLLLLLAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAALLSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMCACACACACACACACACACACASMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMPFPFPFPFPFPFPFPFPFPFPFPFPFPFPFPFPFPFPFPFPFPFPFPFPFPFPFPFPFPFPFPFPFAAAAAAAAAAAAAAAAAAAAAAAALLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLLWFWFWFWFWFWFWFWFSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMSMHPHPHPWFWFWFWFAAAAAAAAAAAAAAAAAAAAAAAAAAAAHPHPHPHPHPHPHPHPHPHPHPHPLLSMCACACAHPHPHPHPHPHPHPHPHPHPHPHPHPHPHPHPHPHPCACASMNL7.01PLANTINGPLAN1"=20'-0"This document and all other project documents,ideas, aesthetics and designs incorporatedtherein are instruments of service. All projectdocuments are copyright protected, are theproperty of LPA, Inc. (LPA) and cannot be lawfullyused in whole or in part for any project or purposeexcept as set forth in the contractual agreementbetween LPA and its Client. The unauthorizeddisclosure and/or use of the project documents(including the creation of derivative works), maygive rise to liability for copyright infringement,unlawful disclosure, use or misappropriation ofproperty rights held by LPA. The unauthorizeduse of the project documents will give rise to therecovery of monetary losses and damagesincluding attorney fees and costs for which theunauthorized user will be held liable.Project documents describe the design intent ofthe work and are not a representation of as-builtor existing conditions. LPA is not responsible forany discrepancies between the project documentsand the existing conditions.© LPA, Inc.Developed forJob NumberDate PublishedChecked ByScaleRevision Date ARCHITECTURE ENGINEERING INTERIORSLANDSCAPE ARCHITECTURE PLANNING949-261-1001 Office949-260-1190 FaxLPADesignStudios.comSubmittal Date 5301 California Avenue, Suite 100Irvine, California 92617DOWNEY SPACE SHUTTLE EXHIBIT
AND EDUCATION BUILDING
12400 COLUMBIA WAY
DOWNEY. CA 90242
CITY OF DOWNEY3055401KH, RG, JH100% SCHEMATIC DESIGN 10/28/2022 50% DESIGN DEVELOPMENT 12/02/2022
100% DESIGN DEVELOPMENT 01/03/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CONSTRUCTION DOCS 08/01/2025 NOTES:A. CONTRACTOR IS TO VERIFY ALL PROPERTY LINES/LIMITS OF WORK AND ADJUST ALL PLANTING ANDIRRIGATION ACCORDINGLY. NOTIFY OWNER'S AUTHORIZED REPRESENTATIVE OF ANY DISCREPANCIES PRIORTO COMMENCING WORK.B. CONTRACTOR MUST REPLACE ANY PLANT MATERIAL DAMAGED WITH 'LIKE' KIND, ON ANY ADJACENTPROPERTIES DUE TO GRADING OR CONSTRUCTION TO THE SATISFACTION OF THE LANDSCAPE ARCHITECTAND OWNER'S REPRESENTATIVE AT NO ADDITIONAL COST TO THE OWNER.C. SEE PLANTING NOTES ON SHEET L0.01D. THE CONTRACTOR MUST FAMILIARIZE HIMSELF WITH THE EXISTING IRRIGATION, GRADING, AND PLANTING OFTHIS PROPERTY AND ADJACENT PROPERTIES. ANY DAMAGE OR ADJUSTMENTS REQUIRED INCLUDINGREPLACING OR RELOCATING IRRIGATION LINES, HEADS, VALVES, WIRES OR ANY UTILITY THAT OCCURS ON THEPARCEL DUE TO THE GRADING AND CONSTRUCTION OF THIS PROJECT IS THE SOLE RESPONSIBILITY OF THECONTRACTOR AND SHALL BE PERFORMED AT NO ADDITIONAL COST TO THE OWNER. THE OWNER'S REP. MUSTREVIEW ANY REQUIRED MODIFICATIONS TO THESE AREAS PRIOR TO COMMENCING WORK. THE CONTRACTORMUST NOTIFY THE OWNER'S AUTHORIZED REP. OF THESE CONDITIONS OR ANY DISCREPANCIES PRIOR TOCOMMENCING WORK. TYP. ENTIRE SITE.E. PROTECT ALL (E) TREES ON SITE WITHIN L.O.W. & OUTSIDE L.O.W. CONTRACTOR TO REPLACE ANY (E) TREESAND PLANT MATERIAL DAMAGED DURING CONSTRUCTION.F. WASH ALL TREES WEEKLY AT HORTICULTURALLY APPROPRIATE TIME FOR EACH SPECIES.G. MAINTAIN AND HAND WATER ALL EXISTING PLANT MATERIAL NOT INDICATED IN THE DEMOLITION PLAN ASBEING REMOVED, DURING THE ENTIRE COURSE OF CONSTRUCTION AND MAINTENANCE.H. MULCH TO BE PLACED WITHIN TREE DRIPLINES AT STREETSCAPE PLANTING, TYP.I. MAINTAIN 1' CLEAR AT SIDEWALK EDGE OF NO-MOW, TYP.(*)- UNLESS NOTED ON PLANDET(NCN.)- NO COMMON NAMEQTY.SPACINGCOMMON NAMETREE LISTSIZE/SHRUB AND GROUNDCOVERBOTANICAL NAME/COMMENTS/SYM.WUCOLSTURF AT FIRELANESHOWNAS-PROTECT IN PLACEEXISTING TREEPER PLAN5GAL/LWILD LILACCEANOTHUS G. ANCHOR BAY/REQ'DASPER PLAN5GAL/LJERUSALEM SAGEPHLOMIS FRUTICOSA/REQ'DASPER PLAN5GAL/LSMOKEY COAST ROSEMARYWESTRINGIA FRUTICOSA 'SMOKEY'/REQ'DASPER PLAN1GAL/LKLEINIASENECIO MANDRALISCAE/REQ'DASPER PLAN5GAL/LNYALLA MAT RUSHLOMANDRA LONGIFOLIA 'NYALLA'/REQ'DASPER RING2"POT/LMULLER'S FESCUEFESTUCA MUELLERI/REQ'DAS15/L5.0101/L7.0201/L7.0201/L7.0201/L7.0201/L7.0203/L7.02SIZEMATUREPLANTING LEGENDPER PLAN15GAL/LBLUE FOX TAIL AGAVEAGAVE ATTENUATA 'NOVA'/REQ'DAS01/L7.02PER PLAN5GAL/VLRED YUCCAHESPERALOE PARVIFORA/REQ'DAS01/L7.022'-3'Hx4'-6'W3'-5'Hx4'-6'W4'-6'Hx4'-5'W12"-18"Hx2'-3'W3'-4'Hx3'-4'W3'-4'Hx4'-5'WCAPFWFSMHPAALL3'-4'Hx3'-4'WMISCELLANEOUS SYMBOLSSOIL SAMPLE LOCATION (2 TOTAL)PLANTING PLANEXISTING BLDGCOLUMBIA WAY LIMIT
O
F
W
O
R
K
LIMIT OF WORK
LIMIT OF WORKEDUCATION BLDG.STEMBLDG.PROPERTY LINEPROPERTY LINEPROPERTY LINE
LIMIT OF WORKLIMIT OF WORK
CONGRESSMAN STEVE HORN WAYLIMIT OF WORK
05PATCH AND REPAIR EXISTING GROUNDCOVERIN KIND AT LIMIT OF WORK ADJACENT TOEXISTING PARK IMPROVEMENTS, TYP.PATCH AND REPAIR EXISTINGGROUNDCOVER IN KINDPATCH AND REPAIR EXISTINGGROUNDCOVER IN KINDPATCH AND REPAIR EXISTINGGROUNDCOVER IN KINDPATCH AND REPAIR EXISTINGGROUNDCOVER IN KINDPATCH AND REPAIR EXISTINGGROUNDCOVER IN KINDPATCH AND REPAIR EXISTINGGROUNDCOVER IN KINDPATCH AND REPAIR EXISTINGGROUNDCOVER IN KINDPATCH AND REPAIR EXISTINGGROUNDCOVER IN KINDSOIL SAMPLE LOCATION#1 OF 2SOIL SAMPLE LOCATION#2 OF 27/25/2025
This document and all other project documents,ideas, aesthetics and designs incorporatedtherein are instruments of service. All projectdocuments are copyright protected, are theproperty of LPA, Inc. (LPA) and cannot be lawfullyused in whole or in part for any project or purposeexcept as set forth in the contractual agreementbetween LPA and its Client. The unauthorizeddisclosure and/or use of the project documents(including the creation of derivative works), maygive rise to liability for copyright infringement,unlawful disclosure, use or misappropriation ofproperty rights held by LPA. The unauthorizeduse of the project documents will give rise to therecovery of monetary losses and damagesincluding attorney fees and costs for which theunauthorized user will be held liable.Project documents describe the design intent ofthe work and are not a representation of as-builtor existing conditions. LPA is not responsible forany discrepancies between the project documentsand the existing conditions.© LPA, Inc.Developed forJob NumberDate PublishedChecked ByScaleRevision Date ARCHITECTURE ENGINEERING INTERIORSLANDSCAPE ARCHITECTURE PLANNING949-261-1001 Office949-260-1190 FaxLPADesignStudios.comSubmittal Date 5301 California Avenue, Suite 100Irvine, California 92617DOWNEY SPACE SHUTTLE EXHIBIT
AND EDUCATION BUILDING
12400 COLUMBIA WAY
DOWNEY. CA 90242
CITY OF DOWNEY3055401KH, RG, JH100% SCHEMATIC DESIGN 10/28/2022 50% DESIGN DEVELOPMENT 12/02/2022
100% DESIGN DEVELOPMENT 01/03/2023
30% CONSTRUCTION DOCS 02/10/2023
95% CONSTRUCTION DOCS 08/01/2025 LEGEND6"ROOTBALLROOT BALL
02-12345678910111234567891011SHRUB PLANTING DETAIL3/4" = 1'-0"-2X SIZE OFROOTBALL MIN.NOTE:SEE DETAIL FOR SPACING DIAGRAM1 TO 15 GALLON SHRUB. (SEE PLANTING PLAN)SET CROWN OF ROOTBALL 1" ABOVE FINISH GRADE ANDSLOPE SOIL AWAY FROM ROOTBALL. ADJUST HEIGHT OFPLANTING TO ACCOMODATE SETTLING DUE TO SOILTYPES.WATER BASIN. 4" MIN. FOR 5 GAL. & LARGER. 2" MIN FOR 1GAL.FINISH GRADEAMENDED BACKFILL. SEE SPECS FOR MIX AND PIT SIZE.PLANT TABLET. SEE SPECS.SCARIFY SIDES AND BOTTOM OF PLANTING PIT.EXISTING SOIL.3" MULCH, MAINTAIN CONSTANTLY. SEE SPECS.COMPACTED BACKFILL, SEE SPECS. PUDDLE AND SETTLEPRIOR TO SETTING SHRUB.UNDISTURBED EXISTING SOIL TO FORM PEDESTAL.REPLACE WITH COMPACTED NATURAL SOIL IF HARDPANEXISTS.LEGEND:123123EQUALEQUALEQU A
LTRIANGULAR SPACING1/4" = 1'-0"-LOCATE PLANTS WITH EQUAL SPACING AS INDICATED ON PLAN(TRIANGULAR SPACING).1/2 ON CENTER SPACING.PAVING, BUILDING, OR HEADER SHOWING PLANTING AREALIMIT.L7.02PLANTING DETAILS010203TREE PROTECTION FENCE1/4" = 1'-0"-1 EXISTING TREE, PROTECT IN PLACE.TREE PROTECTION FENCE: HIGH DENSITYPOLYETHYLENE FENCING WITH 3.5" X 1.5"OPENINGS. COLOR: ORANGE. INSTALLSTEEL POSTS AT 8' O.C. USE 11 GAUGEALUMINUM TIES TO SECURE FENCING TOPOSTS.2" DIA. X 6' HT. STEEL POSTS5" THICK LAYER OF MULCHMAINTAIN EXISTING GRADE AT THE BASEOF THE TREE PROTECTION FENCE UNLESSOTHERWISE NOTED ON PLANS.8.5" X 11" PLASTIC LAMINATED SIGNSPACED AT 50' O.C.NOTES:A. NO PRUNING SHALL BE PERFORMEDEXCEPT BY APPROVED ARBORIST.B. NO EQUIPMENT SHALL OPERATEINSIDE THE PROTECTIVE FENCINGINCLUDING DURING FENCEINSTALLATION AND REMOVAL.C. SEE PLANS FOR ADDITIONALINFORMATION.234564'-0"SECTION VIEWKEEP OUT:TREEPROTECTIONAREA123564ROOT PROTECTION ZONE (RPZ) TO MATCH DRIP LINEUNLESS NOTED OTHERWISE7/25/2025
WVLTCVLTSS
S
S
SN 1792873.09E 6520967.53CGCOLUMBIA WAYPROPERTY LINELIMIT OF WORKPROPOSED 2 STORY BUILDING
PROPOSED 1
STORY
CLASSROOMS
CONGRESSMAN STEVE HORN WAY
PROPERTY LINE LIMIT OF WORKROOF PROJECTION ABOVE
23.04 23.04
PROJECT NORTHN.I.C.
N.I.C.
KEYNOTES
LEGEND
GENERAL NOTES
ACCESSIBLE PATH OF TRAVEL
PROPERTY LINE
LIMIT OF WORK
EXISTING FIRE HYDRANT
PROPOSED FIRE HYDRANT
BACKFLOW
THRUST BLOCK
FDC
NOT IN CONTRACT
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
SITE PLAN
A0.21
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1" = 20'-0"05SITE PLAN
23.04 PAD MOUNTED CONDENSING UNIT. SEE MECHANICAL DRAWINGS.
UP
UP
CGKEYNOTESLEGEND
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.0X SERIES.
STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.0X SERIES.
REFER TO S0.91 FOR INTERIOR STUD WALL SCHEDULE
METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION
INSULATED METAL PANEL WALL CONSTRUCTION
CASEWORK/ MILLWORK - REF. FINISH PLANS
DOOR TAG - REF. DOOR SCHEDULE/ DOOR TYPES SHEET, A6.11
WINDOW TAG - SIDELITE ADJACENT TAGGED DOOR.
REF. DOOR SCHEDULE/ DOOR TYPES SHEET. A6.11
###
D#
KEYNOTE?
TYP
FIRE EXTINGUISHER CABINET, SEMI-RECESSED.
INCLUDED FIRE EXTINGUISHER (10LBS, 4A-80B;C)
PER SPECIFICATION SECTIO104400 AND SEE DETAIL
03/ A9.15
STAINLESS STEEL CORNER GUARD. 48" MOUNTED
ABOVE BASE. SEE SPEC SECTIOLN 10 26 00
FEC
CG
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
11. 12.
13. 14.
15. 16.
17. 18.
19. 20.
21. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION
SEE SHEETS G0.31 AND G0.32 FOR ACCESSIBLE DIMENSIONAL REQUIREMENTS.
SEE FINISH PLANS FOR INTERIOR ELEVATION TAGS.
SEE EQUIPMENT PLANS AND LEGEND FOR RESPONSIBILITY.
SEE A9.01 SERIES FOR WALL TYPES
PLAN DIMENSIONS ARE TO CENTERLINE OF JOINT OR GRID AND/OR MODULE, UNLESS NOTED OTHERWISE (U.N.O.).
EDGE OF DOOR FRAME TO BE 4" FROM PERPENDICULAR WALL UNO
DIMENSIONS ARE TO FACE OF STUD UNO
ACCESSIBLE DOORS SHALL COMPLY WITH CBC SECTION 11B-404.
MEZZANINE FRAMING NO LARGER THAN 8"X8" COLUMNS. LARGEST BRACING ANGLES TO HAVE 5" LEGS. REFER TO PEMB DRAWINGS.
PROVIDE CONTINUOUS FIRESTOPPING AT ALL RATED WALL PENETRATIONS AND AT TOP AND BASE OF RATED WALLS. INSTALLATION SHALL CONFORM TO UL ASSEMBLIES.
WALL RATING SHALL CONTINUE AROUND BEAM PENETRATIONS.
MOISTURE RESISTANT GYPSUM BOARD SHALL BE USED AT RESTROOM AND JANITOR WALLS WHERE TILE IS NOT PROVIDED, INCLUDING CEILING.
PROVIDE "J" MOLDING AT ALL EXPOSED EDGE CONDITIONS.
SIGNS TO IDENTIFY PERMANENT ROOMS SHALL COMPLY WITH CBC SECTIONS 11B-703.
THE MEANS OF EGRESS, INCLUDING THE EXIT DISCHARGE, WILL BE ILLUMINATED TO A LEVEL OF NOT LESS THAN
ONE FOOT-CANDLE AT THE WALKING SURFACE AT ALL TIMES THE BUILDING SPACE SERVED BY THE MEANS OF EGRESS IS OCCUPIED.
EXIT SIGNS SHALL BE INTERNALLY OR EXTERNALLY ILLUMINATED AT ALL TIMES. EXTERANLLY ILLUMINATED EXIT
SIGNS SHALL BE CONNECTED TO AN EMERGENCY POWER SYSTEM (BATTERIES, UNIT EQUIPMENT OR AN ON-SITE GENERATOR) THAT WILL AUTOMATICALLY ILLUMINATE THE EXIT SIGNS FOR A DURATION OF NOT LESS THAN 90 MINUTES IN CASE OF PRIMARY POWER LOSS.
DOORS AT EXIT PASSAGEWAYS, EXIT DISCHARGE, AND EXIT STAIRWAYS SHALL BE IDENTIFIED BY TACTILE SIGNS.
SIGNS TO IDENTIFY PERMANENT ROOMS SHALL COMPLY WITH CBC SECTIONS 11B-703.
THE BUILDING SHALL BE EQUIPPED WITH AN EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM IN ACCORDANCE WITH CBC 1009.12 AND NFPA 72. EVIDENCE OF COMPLIANCE SHALL BE PROVIDED TO AHJ OR BUILDING DEPARTMENT, AS APPLICABLE, PRIOR TO OCCUPANCY (CFC 510).
THE BUILDING SHALL BE EQUIPPED WITH A 2-WAY COMMUNICATION SYSTEM COMPLYING WITH CBC 1009.8.1 AND 1009.8.2 AT THE LANDING SERVING EACH ELEVATOR ON EACH ACCESSIBLE FLOOR THAT IS ONE OR MORE STORIES ABOVE OR BELOW THE LEVEL OF EXIT DISCHARGE (CBC 1009.8).
SEE SHEET A2.03 FOR ADDITIONAL ROOF PLAN GENERAL NOTES
GENERAL NOTES
A3.03
04 A3.0204
A3.01
04 1
1 2
2 3
3 45 6
6 7
7 8
8 9
9 A A
F F
F.2
F.2
A3.0302
04 A3.12
04 A3.12
02 A3.11
02 A3.11
03 A3.11
03 A3.11
10 10
12 12
H H
A3.04
10 A3.04
16 A3.04
18 A3.0402
A3.02
02 02
A3.12
02 A3.12
8950 SF
EXHIBIT
SPACE
100
1731 SF
STORAGE
101
808 SF
STAFF
ROOM
102
502 SF
MECHANICAL
ROOM
103
207 SF
IDF
ROOM
105
64 SF
FAMILY
RESTROOM
108
320 SF
WOMEN'S
RESTROOM
107
302 SF
MEN'S
RESTROOM
106
652 SF
STEM
CLASSROOM
113
751 SF
STEM
CLASSROOM
112
255 SF
ELECTRICAL
ROOM
104
61 SF
ELEVATOR
MACHINE
ROOM
110
46 SF
JANITOR'S
ROOM
109
6 8
.
0 0
°
B.5
D
E E
27 SF
FIRE
RISER
115
23.01 17
A3.22
A4.01
03 A7.01
02 A7.21
14 10
A7.02
ROOF ABOVE
ROOF ABOVE
SECOND FLOOR ABOVE
13 A3.2209
A3.22
13 A3.23
SA8
SA8
SN8
SK6
SJ6SJ6
SN4
A3.01
02 64 SF
STAFF
RESTROOM
114
106
105
101A
102A
109
108 114
104
103
101C
101B
100E100D100C100B
100F
112B
112A
113
112C
107
SA8
07.03 1' - 6"
7'-5 1/4"4'-0" 3'-4 3/4" 15'-2"7'-9"3"4'-11 3/4"18'-0"2'-10 1/4"2'-9"6'-0"5'-4"12'-0"3'-11"2'-3"6'-0"F.1 F.1 G G
4.9 4.9
G.51'-1"2'-1 1/2"
10'-0 1/2"
0'-2 3/4"
16'-0"R.O.
1'-7 1/4" 1'-0 3/4"
25'-9 1/4"
19' - 9 1/4"13' - 6 1/4"
1' - 8"1' - 8"27' - 1"25' - 11"1' - 8"6"24' - 5 1/4"19' - 9 1/2" EQEQ
6 8
.
0 0
°
7 7
.
0 0
°
ELEVATOR90.00°6
8 .
0 0
°
30'-0"6'-0"30'-0"18'-0"6'-0" 6'-0"18'-0"6'-0"11'-8"6'-4"12'-0" 6'-0"2'-5"18'-0"R.O.9'-0"9'-0"18'-0"R.O.10 3/4"9'-4 63/256"8'-6 3/32"05.12 0'-3"212' - 10" 1' - 8"56'-4"A8.33
02 07
A3.21
A7.02
18 A8.33
03 A3.03
18 100G
C
B.2
7.4 7.4
2'-5 1/2"2'-4"1'-8"
SD4SD4
SD1
SD1
SN4
A8.32
12 A8.31
06 A8.31
07 A8.31
17 13.02
A8.53
01 15'-7"
2'-5"9'-7"8'-5"
A8.52
12 A8.32
10 A8.52
04 TYP
07.06 07.0607.0607.0607.0607.0607.063'-7"14'-5"2'-8"
A8.53
015'-6"56'-4"4'-10 1/4"BB
EE
FF
A.1
B B
4.24.81.1 1.1
5.2 5.8 6.9
6.9 D.6
AA
CC
DD
11'-1"
102B
A.2
A.3
D.8
D.9 D.9
8.9 8.97.9
7.97.16.76.1 B.1
81 SF
NURSING
ROOM
116 115'-5"5'-10"18'-4"5'-10" 5'-10"18'-4"5'-10" 1'-4"19'-2"7'-6" 2'-0"2'-6" 8'-7"16'-5"2'-6"28'-0"2'-0" 240'-0"1'-6"23'-9"1'-3"30'-0"30'-0"30'-0"30'-0"30'-0"30'-0"30'-0"30'-0" 4'-0"24'-7"25'-10"19'-0"21'-0"25'-0"11'-0"5'-2"4'-10"20'-3"2'-11"1'-10"1'-3 1/2"1'-9 1/2"7'-9"15'-0"19'-2 1/2"17'-11"19'-2 1/2"115 SN4
110
SN4
TYP.
10.09 TYP.
10.09 ALIGN
15'-3"19'-1"10'-0"2'-6" 0'-5" 14'-5"13'-2"
6'-5 1/4"3'-4 1/4"
1'-9"
0'-9"0'-9"1'-3"5'-3 7/8"14'-10"1'-2"
3'-1 3/4"26'-5"116 3'-0"3'-0"
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 1/8" = 1'-0"COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
FIRST FLOOR PLAN
A2.01
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/8" = 1'-0"01FIRST FLOOR PLAN
05.12 ANGLED WALL. REFER TO ELEVATION.
07.03 SHEET METAL FASCIA
07.06 MANUFACTURED METAL DOWNSPOUT
10.09 METAL SHELF. 48 W X 18 D X ?? H
13.02 STEEL BRACE FRAME WITH HIGH
PERFORMANCE EXTERIOR FINISH BY PEMB
MANUFACTURER
23.01 MECHANICAL EQUIPMENT - SEE MECHANICAL
DRAWINGS.PROJECT NORTH
DNOS
DN
A3.03
04 A3.0204
A3.01
04 1
1 2
2 3
3 45 6
6 7
7 8
8 9
9 A A
F F
F.2
F.2
A3.0302
04 A3.12
04 A3.12
02 A3.11
02 A3.11
03 A3.11
03 A3.11
10 10
12 12
H H
A3.04
10 A3.04
16 A3.04
18 A3.0402
A3.02
02 02
A3.12
02 A3.12
6190 SF
OPEN
EXHIBIT
SPACE
200
OPEN TO BELOW
D
E E
17 A3.22
A7.01
03 A7.21
15 10
A7.02
10 A7.02
ROOF ABOVE
13 A3.22
09 A3.22
13 A3.23
1" / 12"1" / 12"
A3.01
02 SS6
SS6
10'-0"12'-6"
07.02 1/2" / 12"
4'-10"24'-3"7'-6" 1'-4"30'-0"3'-1"7'-2" 5'-8"
36' - 6"
59' - 3"
16'-6"14'-11 3/4"
16'-6"14'-0 1/4"
F.1 F.1
G G
4.9 4.9
ELEVATOR
6 8
.
0 0
°
7 7
.
0 0
°90.00°6
8 .
0 0
°3'-1"7'-2"A7.02
03 A3.03
18 02
A8.21
A8.21
17 C
7.4 7.4
82 SF
ROOF
ACCESS
201
201
SA4
SA4
8'-6"8'-0 1/2"BB
EE
FF
B B
4.24.81.1 1.1
5.2 5.8 6.9
6.9 D.6
11 1/2"
1'-6"
AA
CC
DD
D.9 D.9
8.9 8.9
B.1
5'-10"18'-4"5'-10" 5'-10"18'-4"5'-10"2'-0"28'-0"2'-0"
240'-0"
30'-0"30'-0"30'-0"30'-0"30'-0"30'-0"30'-0"30'-0"
4'-0"115'-5"24'-7"25'-10"19'-0"21'-0"25'-0"1'-3 1/2"15'-0"1'-6"1' - 8"27' - 1"25' - 11"1' - 8"6"56'-4"19' - 9 1/4"13' - 6 1/4"11'-9"0'-4 1/2"0'-5 1/2"KEYNOTESLEGEND SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.0X SERIES.
STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.0X SERIES.
REFER TO S0.91 FOR INTERIOR STUD WALL SCHEDULE
METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION
INSULATED METAL PANEL WALL CONSTRUCTION
CASEWORK/ MILLWORK - REF. FINISH PLANS
DOOR TAG - REF. DOOR SCHEDULE/ DOOR TYPES SHEET, A6.11
WINDOW TAG - SIDELITE ADJACENT TAGGED DOOR.
REF. DOOR SCHEDULE/ DOOR TYPES SHEET. A6.11
###
D#
KEYNOTE?
TYP
FIRE EXTINGUISHER CABINET, SEMI-RECESSED.
INCLUDED FIRE EXTINGUISHER (10LBS, 4A-80B;C)
PER SPECIFICATION SECTIO104400 AND SEE DETAIL
03/ A9.15
STAINLESS STEEL CORNER GUARD. 48" MOUNTED
ABOVE BASE. SEE SPEC SECTIOLN 10 26 00
FEC
CG
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
11. 12.
13. 14.
15. 16.
17. 18.
19. 20.
21. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION
SEE SHEETS G0.31 AND G0.32 FOR ACCESSIBLE DIMENSIONAL REQUIREMENTS.
SEE FINISH PLANS FOR INTERIOR ELEVATION TAGS.
SEE EQUIPMENT PLANS AND LEGEND FOR RESPONSIBILITY.
SEE A9.01 SERIES FOR WALL TYPES
PLAN DIMENSIONS ARE TO CENTERLINE OF JOINT OR GRID AND/OR MODULE, UNLESS NOTED OTHERWISE (U.N.O.).
EDGE OF DOOR FRAME TO BE 4" FROM PERPENDICULAR WALL UNO
DIMENSIONS ARE TO FACE OF STUD UNO
ACCESSIBLE DOORS SHALL COMPLY WITH CBC SECTION 11B-404.
MEZZANINE FRAMING NO LARGER THAN 8"X8" COLUMNS. LARGEST BRACING ANGLES TO HAVE 5" LEGS. REFER TO PEMB DRAWINGS.
PROVIDE CONTINUOUS FIRESTOPPING AT ALL RATED WALL PENETRATIONS AND AT TOP AND BASE OF RATED WALLS. INSTALLATION SHALL CONFORM TO UL ASSEMBLIES.
WALL RATING SHALL CONTINUE AROUND BEAM PENETRATIONS.
MOISTURE RESISTANT GYPSUM BOARD SHALL BE USED AT RESTROOM AND JANITOR WALLS WHERE TILE IS NOT PROVIDED, INCLUDING CEILING.
PROVIDE "J" MOLDING AT ALL EXPOSED EDGE CONDITIONS.
SIGNS TO IDENTIFY PERMANENT ROOMS SHALL COMPLY WITH CBC SECTIONS 11B-703.
THE MEANS OF EGRESS, INCLUDING THE EXIT DISCHARGE, WILL BE ILLUMINATED TO A LEVEL OF NOT LESS THAN
ONE FOOT-CANDLE AT THE WALKING SURFACE AT ALL TIMES THE BUILDING SPACE SERVED BY THE MEANS OF EGRESS IS OCCUPIED.
EXIT SIGNS SHALL BE INTERNALLY OR EXTERNALLY ILLUMINATED AT ALL TIMES. EXTERANLLY ILLUMINATED EXIT
SIGNS SHALL BE CONNECTED TO AN EMERGENCY POWER SYSTEM (BATTERIES, UNIT EQUIPMENT OR AN ON-SITE GENERATOR) THAT WILL AUTOMATICALLY ILLUMINATE THE EXIT SIGNS FOR A DURATION OF NOT LESS THAN 90 MINUTES IN CASE OF PRIMARY POWER LOSS.
DOORS AT EXIT PASSAGEWAYS, EXIT DISCHARGE, AND EXIT STAIRWAYS SHALL BE IDENTIFIED BY TACTILE SIGNS.
SIGNS TO IDENTIFY PERMANENT ROOMS SHALL COMPLY WITH CBC SECTIONS 11B-703.
THE BUILDING SHALL BE EQUIPPED WITH AN EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM IN ACCORDANCE WITH CBC 1009.12 AND NFPA 72. EVIDENCE OF COMPLIANCE SHALL BE PROVIDED TO AHJ OR BUILDING DEPARTMENT, AS APPLICABLE, PRIOR TO OCCUPANCY (CFC 510).
THE BUILDING SHALL BE EQUIPPED WITH A 2-WAY COMMUNICATION SYSTEM COMPLYING WITH CBC 1009.8.1 AND 1009.8.2 AT THE LANDING SERVING EACH ELEVATOR ON EACH ACCESSIBLE FLOOR THAT IS ONE OR MORE STORIES ABOVE OR BELOW THE LEVEL OF EXIT DISCHARGE (CBC 1009.8).
SEE SHEET A2.03 FOR ADDITIONAL ROOF PLAN GENERAL NOTES
GENERAL NOTES
ROOF ASSEMBLY (R1A)
STANDING SEAM METAL ROOF
REFER TO SHEET A8.11
ROOF ASSEMBLY (R1B)
CANOPY STANDING SEAM METAL ROOF
REFER TO SHEET A8.11
ROOF ASSEMBLY (R2A)
STANDING SEAM METAL ROOF
REFER TO SHEET A8.11
ROOF ASSEMBLY (R2B)
CANOPY STANDING SEAM METAL ROOF
REFER TO SHEET A8.11
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 1/8" = 1'-0"COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
SECOND FLOOR
PLAN AND STEM
ROOF PLAN
A2.02
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/8" = 1'-0" A2.02 01SECOND FLOOR PLAN AND STEM ROOF PLAN
07.02 SHEET METAL GUTTER
PROJECT NORTH
HOS
HOS
HOSHOS HOS OS OS
HOS OS OS
HOS HOS OS OSHOS
UNITOUCH
A3.03
04 A3.0204
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
A A
F F
A3.0302
04 A3.12
04 A3.12
02 A3.11
02 A3.11
03 A3.11
03 A3.11
10 10 1/2" / 12"D D
E E
13 A3.23
A3.01
02 54'-8"
49'-6 3/4"
54'-8"
49'-6 3/4"6'-10"24'-7"25'-10"0'-3"07.0222.06
A8.21
19 8'-7"30'-0"30'-0"30'-0"30'-0"30'-0"30'-0"30'-0"30'-0" 1'-5"250'-0"
07.03 CC
B B122'-6"19'-0"21'-0"25'-0"14'-6"
TYP.07.50 TYP.10.03
KEYNOTESLEGEND
ROOF ASSEMBLY (R1A)
STANDING SEAM METAL ROOF
REFER TO SHEET A8.11
KEYNOTE?
ROOF ASSEMBLY (R1B)
CANOPY STANDING SEAM METAL ROOF
REFER TO SHEET A8.11
ROOF ASSEMBLY (R2A)
STANDING SEAM METAL ROOF
REFER TO SHEET A8.11
ROOF ASSEMBLY (R2B)
CANOPY STANDING SEAM METAL ROOF
REFER TO SHEET A8.11
GENERAL NOTES
1. 2.
3. 4.
5. 6.
7. 8.
REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION
INSTALLATION OF ROOFING SHALL BE IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS AND INSTALLATION PROCEDURES.
ROOF SLOPE TO BE A MIN. OF 1/4" PER FOOT INCLUDING AT VALLEYS. CRICKETS TO SLOPE AT 1/2" PER FOOT, MIN.
REFER TO PLUMBING DRAWINGS FOR ALL LOCATIONS OF VENTS.
ROOF TO BE CLASS A PER CBC 1505.1, TABLE 1501.1 AND IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION REPORTS.
ROOF GUTTERS SHALL BE PROVIDED WITH THE MEANS TO PREVENT THE ACCUMULATION OF LEAVES AND DEBRIS IN THE GUTTER. ALL ROOF GUTTERS AN DOWNSPOUTS SHALL BE CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS (CBC 705A.4).
ALL EXPOSED STEEL TO BE HOT DIP GALVANIZED.
ALL ROOF PENETRATIONS INCLUDING PIPES AND CONDUIT SHALL BE FLASHED AND TREATED PER ROOFING MANUFACTURER'S STANDARD DETAILS AND INSTALLATION PROCEDURES.
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 1/8" = 1'-0"COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
ROOF PLAN
A2.03
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/8" = 1'-0" A2.03 01ROOF PLAN
07.02 SHEET METAL GUTTER
07.03 SHEET METAL FASCIA
07.50 ROOF ACCESS HATCH WITH PERMANENT GUARDRAIL BY PEMB
10.03 ROOF TIE BACK ANCHOR
22.06 PLUMBING VENT THROUGH ROOF
PROJECT NORTH
1 1
2 2
3 3
45 6
6 7
7 8
8 9
9 A A
F F
F.2
F.2
10 10
12 12
H H
B.5
D
E E
-5'-0"6" CURB, TYP.ELEVATOR
03.04 03.04F.1 F.1
G G
4.9 4.9
G.5
03.04 10'-11 7/8"1'-0"1'-0"
1'-1"9'-6"9'-8 1/2"0'-9 1/2"11'-10"9'-8 1/2"5'-2"30'-0"ALIGN27'-1"25'-11"19'-9 1/4" 27'-10 1/2"
1'-0 3/4"
4'-2"10'-7 255/256"17'-10 1/8"
17'-10 1/8"0'-10 1/8"0'-10 1/8"3'-2"
13'-4 3/8"
22.04 25'-10"53'-0"13'-6 1/4"
2'-1 1/2"
10'-0 1/2"17'-10"26'-10"
C
B.2
7.4 7.4
VERIFY WITH MFR
4'-10" 8'-0"VERIFY WITH MFR13'-0"VERIFY WITH MFR
7'-6" 5'-2 15/64"VERIFY WITH MFR13'-0"1/2"2"23'-9 3/4"0'-1 1/8" 1'-5"
BB
EE
FF
B B
4.24.81.1 1.1
5.2 5.8 6.9
6.9 D.6
AA
CC
DD
A.2
A.3
D.8
D.9 D.9
8.9 8.97.9
7.97.16.76.1 B.1
CONCRETE SLAB ON GRADE OR
CONCRETE FILLED METAL DECK
CONCRETE CURB OR EQUIPMENT PAD - 6" HIGH AFF, UNO
DEPRESSED CONCRETE SLAB
LEGEND KEYNOTES
EQEQEQ EQ
LOCALIZED DEPRESSION. SLOPE TO DRAIN AREA.
(NOTE DASHED BOX INDICATES APPROXIMATE START
OF 2% SLOPE TOWARDS DRAIN)4'-0"4'-0"
GENERAL NOTES
1. 2.
3. 4.
5. 6.
7. 8.
9. MAIN TOP OF SLAB ELEVATION OF 0'-0" IS EQUAL TO 97.50 FFE PER CIVIL DRAWINGS.
REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
GENERAL CONTRACTOR TO COORDINATE FINAL TOP OF SLAB HEIGHTS AND SLAB DEPRESSIONS WITH FINAL FLOORING SELECTION.
GENERAL CONTRACTOR TO COORDINATE FINAL CURB LOCATIONS WITH WALL
WIDTHS AND ALL FLOOR DEVICES WITH ARCHITECTURAL AND ELECTRICAL DRAWINGS.
ALL DIMENSIONS SHOWN ARE TO EDGE OF SLAB AND CURBS.
CONTRACTOR SHALL VERIFY EQUIPMENT SIZES PRIOR TO POURING CONCRETE HOUSEKEEPING PADS.
PLACEMENT OF ALL CONCRETE JOINTS WILL BE DETERMINED DURING THE SUBMITTALPROCESS.
FOR CURB SIZE AND EXACT LOCATION REFER TO CURB DETAILS ON SHEET XXX & FLOOR PLANS. CONTRACTOR TO VERIFY WALL LOCATIONS AND CURB
DETAILS AS INDICATED ABOVE, TO DETERMINE EXACT CURB LOCATION AND WIDTH.
FOR WALL BASE CONDITIONS AT DEPRESED SLAB TRANSITIONS, REFER TO DETAILS ON SHEET XXX. WALL LOCATIONS ON FLOOR PLANS. CONTRACTOR
TO VERIFY WALL LOCATIONS AND EDGE OF SLAB TRANSITION LOCATIONS AS INDICATED IN THESE DETAILS AND PLANS.
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 1/8" = 1'-0"COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
FIRST FLOOR EDGE
OF SLAB PLAN
A2.11
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/8" = 1'-0" A2.11 01FIRST FLOOR EDGE OF SLAB PLAN
03.04 CONCRETE PAD. REFER TO STRUCTURAL DRAWINGS.
22.04 JANITORIAL SINK; REFER TO PLUMBING DRAWINGS.PROJECT NORTH
CONCRETE SLAB ON GRADE OR
CONCRETE FILLED METAL DECK
CONCRETE CURB OR EQUIPMENT PAD - 6" HIGH AFF, UNO
DEPRESSED CONCRETE SLAB
LEGEND KEYNOTES
EQEQEQ EQ
LOCALIZED DEPRESSION. SLOPE TO DRAIN AREA.
(NOTE DASHED BOX INDICATES APPROXIMATE START
OF 2% SLOPE TOWARDS DRAIN)4'-0"4'-0"
GENERAL NOTES
1. 2.
3. 4.
5. 6.
7. 8.
9. MAIN TOP OF SLAB ELEVATION OF 0'-0" IS EQUAL TO 97.50 FFE PER CIVIL DRAWINGS.
REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
GENERAL CONTRACTOR TO COORDINATE FINAL TOP OF SLAB HEIGHTS AND SLAB DEPRESSIONS WITH FINAL FLOORING SELECTION.
GENERAL CONTRACTOR TO COORDINATE FINAL CURB LOCATIONS WITH WALL
WIDTHS AND ALL FLOOR DEVICES WITH ARCHITECTURAL AND ELECTRICAL DRAWINGS.
ALL DIMENSIONS SHOWN ARE TO EDGE OF SLAB AND CURBS.
CONTRACTOR SHALL VERIFY EQUIPMENT SIZES PRIOR TO POURING CONCRETE HOUSEKEEPING PADS.
PLACEMENT OF ALL CONCRETE JOINTS WILL BE DETERMINED DURING THE SUBMITTALPROCESS.
FOR CURB SIZE AND EXACT LOCATION REFER TO CURB DETAILS ON SHEET XXX & FLOOR PLANS. CONTRACTOR TO VERIFY WALL LOCATIONS AND CURB
DETAILS AS INDICATED ABOVE, TO DETERMINE EXACT CURB LOCATION AND WIDTH.
FOR WALL BASE CONDITIONS AT DEPRESED SLAB TRANSITIONS, REFER TO DETAILS ON SHEET XXX. WALL LOCATIONS ON FLOOR PLANS. CONTRACTOR
TO VERIFY WALL LOCATIONS AND EDGE OF SLAB TRANSITION LOCATIONS AS INDICATED IN THESE DETAILS AND PLANS.
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
A A
F F
10 10
D
E E
OPEN TO BELOW 25'-10"24'-3"7'-6" 1'-4" 12'-0"18'-0"12'-0" 0'-0"30'-0"5'-8"7'-2"3'-1"C
7.4 7.4
BB
EE
FF
B B
4.2 4.2
4.8 4.8
1.1 1.1
5.2 5.2
5.8 5.8
6.9 6.9
D.6
AA
CC
DD
D.9 D.9
8.9 8.9
B.1
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/202230% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 1/8" = 1'-0"COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
EDGE OF DECK
SECOND FLOOR
A2.12
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/8" = 1'-0" A2.12 01SECOND FLOOR EDGE OF DECK PLAN PROJECT NORTH
UP
UP
CG1
1 2
2 3
3 45 6
6 7
7 8
8 9
9 A A
F F
F.2
F.2
10 10
12 12
H H
B.5
D
E E
EXHIBIT
SPACE
100
STORAGE
101
STAFF
ROOM
102
MECHANICAL
ROOM
103
IDF
ROOM
105
FAMILY
RESTROOM
108
WOMEN'S
RESTROOM
107
MEN'S
RESTROOM
106
STEM
CLASSROOM
113
STEM
CLASSROOM
112
ELECTRICAL
ROOM
104
ELEVATOR
MACHINE
ROOM
110ELEVATOR
111
JANITOR'S
ROOM
109
A4.01
11 A7.01
02 A7.21
14 STAFF
RESTROOM
114
FIRE
RISER
115
A5.08
02 A5.03 02
A5.05
F.1 F.1
G G
4.9 4.9
G.5
A7.02
18 C
B.2
7.4 7.4
BB
EE
FF
B B
4.24.81.1 1.1
5.2 5.8 6.9
6.9 D.6
02 AA
CC
DD
A.2
A.3
D.8
D.9 D.9
8.9 8.97.9
7.97.16.76.1 B.1
A5.04
02 A5.06
02 A5.0613
A5.07
1 A5.09
12 04
C-1
PC-1
PC-1
PC-1
SC-1
SC-1
PC-1 C-2
A5.09
14 A5.0902A5.09
10 A5.09
18 A5.09
15 A5.0903A5.09
11 A5.09
19 A5.0920
PC-1
PC-1
RF-1
NURSING
ROOM
116
PC-1
A5.02 20
24 GENERAL NOTES
1. 2.
3. 4.
5. 6.
7. 8.
GENERAL FINISHES: ALL WALLS, EXPOSED GALVANIZED FRAMING, BRACING, PIPES, AND EXPOSED UTILITIES LESS EXPOSED MECHANICAL DUCT IN MAIN EXHIBIT AREA. SEE MECHANICAL, TO BE PAINTED (P-1), U.N.O. ALL FLOORING TO BE (C-1), U.N.O. ALL BASE TO BE (B-1), U.O.N.
FLOOR PREPARATION: PERFORM MOISTURE AND ALKALINITY (PH) FLOORING TEST
THROUGHOUT AND REPORT FINDINGS AND MITIGATION METHOD OPTIONS TO ARCHITECT/LANDLORD/CLIENT, PRIOR TO ORDERING/INSTALLATION OF MATERIALS. SEE SPECIFICATION SECTION 090561.
TILE APPLICATION: SEAL ALL FLOOR AND WALL GROUT AROUND PLUMBING AND WET AREAS.
TILE APPLICATION: LAY TILE ACCORDING TO PATTERN INDICATED ON CONSTRUCTION DOCUMENTS. IF THERE IS A CONFLICT WITH THE MANUFACTURER'S RECOMMENDATIONS, THE MANUFACTURER'S RECOMMENDATIONS WILL GOVERN THE INSTALLATION METHOD.
LARGE FORMAT TILES [ANY TILE WITH AN EDGE DIMENSION EQUAL OR GREATER THAN 15"] WILL HAVE A 30% OFFSET AS OPPOSED TO A 50% OFFSET. VERIFY TILE TO TILE JOINT RELATIONSHIP WITH MANUFACTURER TO AVOID "LIPPAGE". DO NOT INTERRUPT TILE PATTERN THROUGH OPENINGS.
FLOOR: CONTINUE FLOOR FINISH UNDER/INTO ACCESSIBLE SINK LOWER CABINET.
FLOOR: PROVIDE 'FEATHER UP' TRANSITION AT ALL DOORS WHEN THERE IS A DIFFERENCE OF 1/ 4" OR MORE TO MEET ACCESSIBLE REQUIREMENTS AT A MINIMUM.
MATERIAL DIRECTIONAL INSTALLATION: IF INSTALLATION DIRECTION IS NOT INDICATED ON PLANS, CONTACT ARCHITECT FOR CLARIFICATION PRIOR TO INSTALLATION.
ACCESS PANEL: PAINT TO MATCH ADJACENT WALL/SOFFIT COLOR, WHERE OCCURS OR UNLESS SPECIFIED AS A PREFINISHED MATERIAL SUCH AS STAINLESS STEEL.
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 1/8" = 1'-0"COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
FIRST FLOOR
FINISH PLAN
A2.21
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/8" = 1'-0"01FIRST FLOOR FINISH PLAN PROJECT NORTHSPEC SECTION: 06 41 16 COLOR: TBD
PL-2 PLASTIC LAMINATE MANUFACTURER: WILSONART
SPEC SECTION: 06 41 16
COLOR: TBD
PL-1 PLASTIC LAMINATE MANUFACTURER: WILSONART
SPEC SECTION: 03 35 42
MID LEVEL, POLISH AND SEAL
PC-1 POLISHED CONCRETE FINISH: CLEAR MATTE SEALER, DIAMOND GRIND, SPEC SECTION:
FINISH:
COLOR:
P-2 PAINT - METAL MANUFACTURER: DUNN EDWARDS
SPEC SECTION:
FINISH: EGGSHELL
COLOR: WARM WHITE DEW380
P-1 PAINT MANUFACTURER: DUNN EDWAFS
SPEC SECTION: 68 82 00
FINISH: SMOOTH
COLOR: WHITE
SIZE: 4' ABOVE BASE, CAP PER MANUFACTURER
FRP-1 FIBER REINFORCED POLYMER MANUFACTURER: MARLITE
SPEC SECTION: 09 68 00
INSTALL:
SIZE:
COLOR:
C-2 WALK OFF MANUFACTURER:
SPEC SECTION: 09 68 00
INSTALL: MONOLITHIC
SIZE: 18" X 36"
COLOR: TBD
C-1 CARPET TILE MANUFACTURER: SHAW CONTRACT
SPEC SECTION: 09 00 00
GROUT: TBD, LARGE FORMAT
SIZE; 6" X 24"
COLOR: TBD
STYLE: PORTFOLIO
B-2 BASE TILE MANUFACTURER: DALTILE
SPEC SECTION: 09 65 13
AND RESILIENT FLOORING
NOTES: 4" STRAIGHT AT CARPET, COVED AT CONCRETE
COLOR: TBD
STYLE: JOHNSONITE
B-1 RUBBER BASE MANUFACTURER: TARKETT
TAG DESCRIPTION SPECIFICATION
FINISH SCHEDULE
SPEC SECTION: 09 30 00
GROUT: TBD, LARGE FORMAT
SIZE: 12" X 24"
COLOR: TBD
STYLE: PORTFOLIO
T-2 TILE MANUFACTURER: DALTILE
SPEC SECTION: 09 30 00
GROUT: TBD, LARGE FORMAT
SIZE: 24" X 24"
COLOR: TBD
STYLE: PORTFOLIO
T-1 TILE MANUFACTURER: DALTILE
SPEC SECTION: 12 36 66
THICKNESS: 3/4"
COLOR: TBD
SS-1 SOLID SURFACE MANUFACTURER: WILSONART
SPEC SECTION: 03 35 42
MID LEVEL, AND SEAL
SC-1 SEALED CONCRETE FINISH: CLEAR MATTE SEALER, DIAMOND GRIND, SPEC SECTION: 09 30 00
GROUT: TBD 1/16"
SIZE: 4" X 12"
COLOR: TITAN
STYLE: MYTHOLOGY, WAVE CREST
T-3 TILE MANUFACTURER: DALTILE
SPEC SECTION: 09 30 00
GROUT: TBD, 1/16"
SIZE: 4" X 12"
COLOR: ARCTIC WHITE GLOSS
STYLE: COLOR WHEEL LINEAR
T-2 TILE MANUFACTURER: DALTILE
SPEC SECTION: 09 30 00
GROUT: TBD, LARGE FORMAT
SIZE: 24" X 24"
COLOR: TBD
STYLE: PORTFOLIO
T-1 TILE MANUFACTURER: DALTILE
SPEC SECTION: 12 36 66
THICKNESS: 3/4"
COLOR: TBD
SS-1 SOLID SURFACE MANUFACTURER: WILSONART
COLOR: TBD
THICKNESS: TBD
STYLE: MARMOLIUM REAL
RF-2 RESILIENT FLOORING MANUFACTURER: FORBO
SPEC SECTION: XX XX XX
FINISH: 24" X 24"
STYLE: ECLIPSE
RF-1 STATIC DISSIPATIVE TILE MANUFACTURER: STATICWORX
TAG DESCRIPTION SPECIFICATION
DN
DN
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
A A
F F
10 D
E E
OPEN
EXHIBIT
SPACE
200
A7.01
03 A5.08
02 A5.03 02
A5.05
OPEN TO BELOW
A7.02
03 C
7.4 7.4
BB
EE
FF
B B
4.2 4.2
4.8 4.8
1.1 1.1
5.2 5.2
5.8 5.8
6.9 6.9
D.6
02 AA
CC
DD
D.9 D.9
8.9 8.9
B.1
A8.22
01 05
A5.04
02 A5.06
02 A5.0613
A5.07
1 A5.09 04
A5.0920
PC-1
SG4.0214
GENERAL NOTES
1. 2.
3. 4.
5. 6.
7. 8.
GENERAL FINISHES: ALL WALLS, EXPOSED GALVANIZED FRAMING, BRACING, PIPES, AND EXPOSED UTILITIES LESS EXPOSED MECHANICAL DUCT IN MAIN EXHIBIT AREA. SEE MECHANICAL, TO BE PAINTED (P-1), U.N.O. ALL FLOORING TO BE (C-1), U.N.O. ALL BASE TO BE (B-1), U.O.N.
FLOOR PREPARATION: PERFORM MOISTURE AND ALKALINITY (PH) FLOORING TEST
THROUGHOUT AND REPORT FINDINGS AND MITIGATION METHOD OPTIONS TO ARCHITECT/LANDLORD/CLIENT, PRIOR TO ORDERING/INSTALLATION OF MATERIALS. SEE SPECIFICATION SECTION 090561.
TILE APPLICATION: SEAL ALL FLOOR AND WALL GROUT AROUND PLUMBING AND WET AREAS.
TILE APPLICATION: LAY TILE ACCORDING TO PATTERN INDICATED ON CONSTRUCTION DOCUMENTS. IF THERE IS A CONFLICT WITH THE MANUFACTURER'S RECOMMENDATIONS, THE MANUFACTURER'S RECOMMENDATIONS WILL GOVERN THE INSTALLATION METHOD.
LARGE FORMAT TILES [ANY TILE WITH AN EDGE DIMENSION EQUAL OR GREATER THAN 15"] WILL HAVE A 30% OFFSET AS OPPOSED TO A 50% OFFSET. VERIFY TILE TO TILE JOINT RELATIONSHIP WITH MANUFACTURER TO AVOID "LIPPAGE". DO NOT INTERRUPT TILE PATTERN THROUGH OPENINGS.
FLOOR: CONTINUE FLOOR FINISH UNDER/INTO ACCESSIBLE SINK LOWER CABINET.
FLOOR: PROVIDE 'FEATHER UP' TRANSITION AT ALL DOORS WHEN THERE IS A DIFFERENCE OF 1/ 4" OR MORE TO MEET ACCESSIBLE REQUIREMENTS AT A MINIMUM.
MATERIAL DIRECTIONAL INSTALLATION: IF INSTALLATION DIRECTION IS NOT INDICATED ON PLANS, CONTACT ARCHITECT FOR CLARIFICATION PRIOR TO INSTALLATION.
ACCESS PANEL: PAINT TO MATCH ADJACENT WALL/SOFFIT COLOR, WHERE OCCURS OR UNLESS SPECIFIED AS A PREFINISHED MATERIAL SUCH AS STAINLESS STEEL.
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 1/8" = 1'-0"COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
SECOND FLOOR
FINISH PLAN
A2.22
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/8" = 1'-0"01SECOND FLOOR FINISH PLAN PROJECT NORTHSPEC SECTION: 06 41 16 COLOR: TBD
PL-2 PLASTIC LAMINATE MANUFACTURER: WILSONART
SPEC SECTION: 06 41 16
COLOR: TBD
PL-1 PLASTIC LAMINATE MANUFACTURER: WILSONART
SPEC SECTION: 03 35 42
MID LEVEL, POLISH AND SEAL
PC-1 POLISHED CONCRETE FINISH: CLEAR MATTE SEALER, DIAMOND GRIND, SPEC SECTION:
FINISH:
COLOR:
P-2 PAINT - METAL MANUFACTURER: DUNN EDWARDS
SPEC SECTION:
FINISH: EGGSHELL
COLOR: WARM WHITE DEW380
P-1 PAINT MANUFACTURER: DUNN EDWAFS
SPEC SECTION: 68 82 00
FINISH: SMOOTH
COLOR: WHITE
SIZE: 4' ABOVE BASE, CAP PER MANUFACTURER
FRP-1 FIBER REINFORCED POLYMER MANUFACTURER: MARLITE
SPEC SECTION: 09 68 00
INSTALL:
SIZE:
COLOR:
C-2 WALK OFF MANUFACTURER:
SPEC SECTION: 09 68 00
INSTALL: MONOLITHIC
SIZE: 18" X 36"
COLOR: TBD
C-1 CARPET TILE MANUFACTURER: SHAW CONTRACT
SPEC SECTION: 09 00 00
GROUT: TBD, LARGE FORMAT
SIZE; 6" X 24"
COLOR: TBD
STYLE: PORTFOLIO
B-2 BASE TILE MANUFACTURER: DALTILE
SPEC SECTION: 09 65 13
AND RESILIENT FLOORING
NOTES: 4" STRAIGHT AT CARPET, COVED AT CONCRETE
COLOR: TBD
STYLE: JOHNSONITE
B-1 RUBBER BASE MANUFACTURER: TARKETT
TAG DESCRIPTION SPECIFICATION
FINISH SCHEDULE
SPEC SECTION: 09 30 00
GROUT: TBD, LARGE FORMAT
SIZE: 12" X 24"
COLOR: TBD
STYLE: PORTFOLIO
T-2 TILE MANUFACTURER: DALTILE
SPEC SECTION: 09 30 00
GROUT: TBD, LARGE FORMAT
SIZE: 24" X 24"
COLOR: TBD
STYLE: PORTFOLIO
T-1 TILE MANUFACTURER: DALTILE
SPEC SECTION: 12 36 66
THICKNESS: 3/4"
COLOR: TBD
SS-1 SOLID SURFACE MANUFACTURER: WILSONART
SPEC SECTION: 03 35 42
MID LEVEL, AND SEAL
SC-1 SEALED CONCRETE FINISH: CLEAR MATTE SEALER, DIAMOND GRIND, SPEC SECTION: 09 30 00
GROUT: TBD 1/16"
SIZE: 4" X 12"
COLOR: TITAN
STYLE: MYTHOLOGY, WAVE CREST
T-3 TILE MANUFACTURER: DALTILE
SPEC SECTION: 09 30 00
GROUT: TBD, 1/16"
SIZE: 4" X 12"
COLOR: ARCTIC WHITE GLOSS
STYLE: COLOR WHEEL LINEAR
T-2 TILE MANUFACTURER: DALTILE
SPEC SECTION: 09 30 00
GROUT: TBD, LARGE FORMAT
SIZE: 24" X 24"
COLOR: TBD
STYLE: PORTFOLIO
T-1 TILE MANUFACTURER: DALTILE
SPEC SECTION: 12 36 66
THICKNESS: 3/4"
COLOR: TBD
SS-1 SOLID SURFACE MANUFACTURER: WILSONART
COLOR: TBD
THICKNESS: TBD
STYLE: MARMOLIUM REAL
RF-2 RESILIENT FLOORING MANUFACTURER: FORBO
SPEC SECTION: XX XX XX
FINISH: 24" X 24"
STYLE: ECLIPSE
RF-1 STATIC DISSIPATIVE TILE MANUFACTURER: STATICWORX
TAG DESCRIPTION SPECIFICATION
B
WP
WPWPWPWPF Zc
Zc
Zc
Zm
F
FWPWPFFF
WP
FF
FF
Zc
Zc
Zc
Zc
LEDLEDLED LED LED LED LED LED LEDLEDLEDLED LED LED LED LED LED LEDLEDLEDLED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED LED T
W
A3.03
04 A3.0204
A3.01
04 1
1 2
2 3
3 45 6
6 7
7 8
8 9
9 A A
F F
F.2
F.2
A3.0302
04 A3.12
04 A3.12
02 A3.11
02 A3.11
03 A3.11
03 A3.11
10 10
12 12
H H
A3.04
10 A3.04
16 A3.04
18 A3.0402
A3.02
02 02
A3.12
02 A3.12
B.5
D
E E
17 A3.22
A4.01
19 A7.01
02 A7.21
14 10
A7.02
10 A7.02
13 A3.22
09 A3.22
13 A3.23
10' - 0"
CL-1
OPEN TO ABOVE
A3.01
02 EXHIBIT
SPACE
100
ELEVATOR
MACHINE
ROOM
110
STORAGE
101
JANITOR'S
ROOM
109
FAMILY
RESTROOM
108
WOMEN'S
RESTROOM
107
MEN'S
RESTROOM
106
IDF
ROOM
105
ELECTRICAL
ROOM
104
MECHANICAL
ROOM
103
FIRE
RISER
115
STAFF
RESTROOM
114
13' - 1"
MTL-1
11' - 0"
CL-1
11' - 0"
CL-1
ROOF BEYOND
23.01 26.06
23.01 26.06
26.06 F.1 F.1
G G
4.9 4.9
G.5
STAFF
ROOM
102
STEM
CLASSROOM
113
STEM
CLASSROOM
112
ELEVATOR
07 A3.21
A7.02
18 A3.03
18 C
B.2
7.4 7.4
BB
EE
FF
B B
4.24.81.1 1.1
5.2 5.8 6.9
6.9 D.6
1-A3.01
04 1-A3.01
02 1-A3.03
06 1-A3.0304
1-A3.02
04 1-A3.0202
AA
1-A3.0302
CC
DD
A.2
A.3
D.8
D.9 D.9
8.9 8.97.9
7.97.16.76.1 B.1
8' - 0"
GYP-1
NURSING
ROOM
116
10.11 10.11
10.11 KEYNOTESLEGEND
CL-1
2 X 4 SUSPENDED ACOUSTICAL CEILING TILE,
ARMSTRONG, CALLA, VECTOR
GYP-1
FRAMED GYPSUM BOARD CEILING
GYP-2
FRAMED GYPSUM BOARD, MOISTURE RESISTANT,
SEMI-GLOSS PAINT (WET LOCATIONS)
MTL-1
LINEAR METAL CEILING PANEL [MANUFACTURER,
PRODUCT LINE, SIZE, COLOR: TBD, TO MATCH
INSULATED METAL PANEL INSIDE FACE] (EXTERIOR)
OPEN TO STRUCTURE ABOVE
ALL EXPOSED SURFACES PAINTED P-1
TEC-1
TECTUM CEILING PANELS ATTACHED TO ROOF
PURLINS
TYPICAL CEILING HEIGHT, UNO10'-0"
CL-1TYPICAL CEILING TYPE, UNO.
KEYNOTE?
?FINISH SYMBOL
GENERAL NOTES
1. 2.
3. 4.
5. MECHANICAL: REFER TO MECHANICAL DRAWINGS FOR SUPPLY AND RETURN AIR SPECIFICATIONS.
LIGHTING: REFER TO EELCTRICAL ENGINEERING NOTES FOR ALL SWITCHING, LIGHT CONTROLS, AND SPECIFICATIONS.
CONFIRM MOUNTING HEIGHTS WITHA RCHITECT IN FIELD PRIOR TO INSTALLATION FOR ALL NON-RECESSED FIXTURES.
SEE ELEVATIONS FOR ALL FACE OF SOFFIT FINISHES.
SEE AV AND SECURITY DRAWINGS FOR ADDITIONAL CEILING ELEMENTS.
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 1/8" = 1'-0"COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
FIRST FLOOR
REFLECTED
CEILING PLAN
A2.31
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/8" = 1'-0"01FIRST FLOOR REFLECTED CEILING PLAN
10.11 ROLLER WINDOW SHADES, MANUAL, MECHOSHADE, SINGLE ROLL, SURFACE MOUNTED ABOVE INTERIOR MULLIONS, FABRIC: ECOVEIL OPACITY 1%, COLOR: TBD.
23.01 MECHANICAL EQUIPMENT - SEE MECHANICAL DRAWINGS.
26.06 LIGHTING FIXTURE. REFER TO LIGHTING DRAWINGS.PROJECT NORTH
Zc
Zc
A3.03
04 A3.0204
A3.01
04 1
1 2
2 3
3 4
4 5
5 6
6 7
7 8
8 9
9 A A
F F
A3.0302
04 A3.12
04 A3.12
02 A3.11
02 A3.11
03 A3.11
03 A3.11
10 10
A3.02
02 D
E E
17 A3.22
13 A3.22
09 A3.22
13 A3.23
A3.01
02 OPEN
EXHIBIT
SPACE
200
30'-0"30'-0"30'-0"30'-0"30'-0"30'-0"30'-0"30'-0"
ELEVATOR
30'-0"15'-0"15'-0"30'-0"15'-0"15'-0"30'-0"15'-0"15'-0"30'-0"15'-0"15'-0"6'-10"24'-7"90'-10"122'-3"TEC-1 1/2" / 12"TEC-1
1/2" / 12"TEC-1
1/2" / 12"TEC-1
1/2" / 12"TEC-1
1/2" / 12"TEC-1
1/2" / 12"TEC-1
1/2" / 12"TEC-1
1/2" / 12"44'-0"
44'-0"
23.03 A3.03
18 C
7.4 7.4
10.06 26.12
10.07 BB
EE
FF
A.1
B B
4.2 4.2
4.8 4.8
1.1 1.1
5.2 5.2
5.8 5.8
6.9 6.9
D.6
1-A3.01
04 1-A3.01
02 1-A3.03
06 1-A3.0304
1-A3.02
04 1-A3.0202
AA
1-A3.0302
CC
DD
D.9 D.9
8.9 8.9
B.1
KEYNOTESLEGEND
CL-1
2 X 4 SUSPENDED ACOUSTICAL CEILING TILE,
ARMSTRONG, CALLA, VECTOR
GYP-1
FRAMED GYPSUM BOARD CEILING
GYP-2
FRAMED GYPSUM BOARD, MOISTURE RESISTANT,
SEMI-GLOSS PAINT (WET LOCATIONS)
MTL-1
LINEAR METAL CEILING PANEL [MANUFACTURER,
PRODUCT LINE, SIZE, COLOR: TBD, TO MATCH
INSULATED METAL PANEL INSIDE FACE] (EXTERIOR)
OPEN TO STRUCTURE ABOVE
ALL EXPOSED SURFACES PAINTED P-1
TEC-1
TECTUM CEILING PANELS ATTACHED TO ROOF
PURLINS
TYPICAL CEILING HEIGHT, UNO10'-0"
CL-1TYPICAL CEILING TYPE, UNO.
KEYNOTE?
?FINISH SYMBOL
GENERAL NOTES
1. 2.
3. 4.
5. MECHANICAL: REFER TO MECHANICAL DRAWINGS FOR SUPPLY AND RETURN AIR SPECIFICATIONS.
LIGHTING: REFER TO EELCTRICAL ENGINEERING NOTES FOR ALL SWITCHING, LIGHT CONTROLS, AND SPECIFICATIONS.
CONFIRM MOUNTING HEIGHTS WITHA RCHITECT IN FIELD PRIOR TO INSTALLATION FOR ALL NON-RECESSED FIXTURES.
SEE ELEVATIONS FOR ALL FACE OF SOFFIT FINISHES.
SEE AV AND SECURITY DRAWINGS FOR ADDITIONAL CEILING ELEMENTS.
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 1/8" = 1'-0"COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
SECOND FLOOR
REFLECTED
CEILING PLAN
A2.32
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/8" = 1'-0" A2.32 01SECOND FLOOR REFLECTED CEILING PLAN
10.06 PROJECTOR SCREEN.
10.07 PROJECTOR
23.03 CEILING FANS. SEE MECHANICAL DRAWINGS.
26.12 THEATRICAL LIGHTING. REFER TO LIGHTING DRAWINGS.PROJECT NORTH
................................................UP
UP
1 1
2 2
3 3
45 6
6 7
7 8
8 9
9 A A
F F
F.2
F.2
10 10
12 12
H H
D
E E
F.1 F.1
G G
4.9 4.9
G.5
CBB
EE
FF
B B
4.24.81.1 1.1
5.2 5.8
AA
CC
DD
D.9 D.9
B.1
EXHIBIT
SPACE
100
STORAGE
101
STAFF
ROOM
102
MECHANICAL
ROOM
103
IDF
ROOM
105
FAMILY
RESTROOM
108
WOMEN'S
RESTROOM
107
MEN'S
RESTROOM
106
STEM
CLASSROOM
113
STEM
CLASSROOM
112
ELECTRICAL
ROOM
104
ELEVATOR
MACHINE
ROOM
110
ELEVATOR
111
JANITOR'S
ROOM
109
STAFF
RESTROOM
114
FIRE
RISER
115
NURSING
ROOM
116
04 KEYNOTES
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
11. SEE FLOOR PLANS FOR WALL TYPES
SEE ELECTRICAL AND LOW VOLTAGE DRAWINGS.
CLIENT TO PURCHASE FURNITURE SHOWN, NOT TAGGED.
GENERAL CONTRACTOR TO COORDINATE ALL FURNITURE, FIXTURES AND
EQUIPMENT FOR ITEMS LISTED UNDER KEYNOTE CSI DIVISIONS AND PROJECT
MANUAL SPECIFICATION, GO TO COORDINATE PROCUREMENT AND
INSTALLATION INCLUDING ALL UTILITY INFRASTRUCTURE AND CONNECTIONS.
REACH RANGES SEE REQUIREMENTS ON G0.32 AND 04/A9.30. ALL EQUIPMENT TO COMPLY WITH ACCESSIBLE REACH RANGES PER SECTION 11B-308.
APPLIANCE OPERABLE PARTS SHALL COMPLY WITH CBC 11B-309.
FOR WORK SURFACES ACCESSIBILITY COMPLIANCE, REFER TO DETAIL 15A/G0.32
OPERABLE PARTS SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING OR TWISTING OF THE WRIST.
WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, ATLEAST 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL COMPLY WITH 11B-902.
DINING SURFACES REQUIRED TO COMPLY WITH SECTION 11B-902 SHALL BE
DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
SURFACES FOR EACH TYPE OF SEATING IN A FUNCTIONAL AREA, SEE ASSISTIVE LISTENING SYSTEM REQUIREMENTS ON SHEET G2.01.
LEGENDGENERAL NOTES
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 1/8" = 1'-0"COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
FIRST FLOOR
EQUIPMENT &
FURNITURE PLAN
A2.41
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDINGPROJECT NORTH 1/8" = 1'-0"01FIRST FLOOR EQUIPMENT & FURNITURE PLAN
EQUIPMENT SCHEDULE
TAG TYPE OF EQUIPMENT DESCRIPTION OF EQIPMENT CFCI OFCI 01 COFFEE MAKER COUNTER TOP(WATER?)Yes
02 MICROWAVE BUILT IN DRAWER Yes
03 REFRIGERATOR RESIDENTAL(ICE?)Yes
04 COPY/ PRINTER DATA AND ELECTRICITY?Yes
05 TV TV NEEDS DATA, ELECTRICAL AND BACKING No Yes
06 PRINTER DATA AND ELECTRICAL
07 COMPUTER DATA AND ELECTRICAL
DN
DN
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
A A
F F
10 D
E E
CBB
EE
FF
B B
4.2 4.2
4.8 4.8
1.1 1.1
5.2 5.2
5.8 5.8
AA
CC
DD
D.9 D.9
B.1 OPEN
EXHIBIT
SPACE
200
OPEN TO BELOW
KEYNOTESLEGENDGENERAL NOTES
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
11. SEE FLOOR PLANS FOR WALL TYPES
SEE ELECTRICAL AND LOW VOLTAGE DRAWINGS.
CLIENT TO PURCHASE FURNITURE SHOWN, NOT TAGGED.
GENERAL CONTRACTOR TO COORDINATE ALL FURNITURE, FIXTURES AND
EQUIPMENT FOR ITEMS LISTED UNDER KEYNOTE CSI DIVISIONS AND PROJECT
MANUAL SPECIFICATION, GO TO COORDINATE PROCUREMENT AND
INSTALLATION INCLUDING ALL UTILITY INFRASTRUCTURE AND CONNECTIONS.
REACH RANGES SEE REQUIREMENTS ON G0.32 AND 04/A9.30. ALL EQUIPMENT TO COMPLY WITH ACCESSIBLE REACH RANGES PER SECTION 11B-308.
APPLIANCE OPERABLE PARTS SHALL COMPLY WITH CBC 11B-309.
FOR WORK SURFACES ACCESSIBILITY COMPLIANCE, REFER TO DETAIL 15A/G0.32
OPERABLE PARTS SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, PINCHING OR TWISTING OF THE WRIST.
WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, ATLEAST 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL COMPLY WITH 11B-902.
DINING SURFACES REQUIRED TO COMPLY WITH SECTION 11B-902 SHALL BE
DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
SURFACES FOR EACH TYPE OF SEATING IN A FUNCTIONAL AREA, SEE ASSISTIVE LISTENING SYSTEM REQUIREMENTS ON SHEET G2.01.
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 1/8" = 1'-0"COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
SECOND FLOOR
EQUIPMENT &
FURNITURE PLAN
A2.42
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDINGPROJECT NORTH 1/8" = 1'-0"01SECOND FLOOR EQUIPMENT & FURNITURE PLAN
EQUIPMENT SCHEDULE
TAG TYPE OF EQUIPMENT DESCRIPTION OF EQIPMENT CFCI OFCI 01 COFFEE MAKER COUNTER TOP(WATER?)Yes
02 MICROWAVE BUILT IN DRAWER Yes
03 REFRIGERATOR RESIDENTAL(ICE?)Yes
04 COPY/ PRINTER DATA AND ELECTRICITY?Yes
05 TV TV NEEDS DATA, ELECTRICAL AND BACKING No Yes
06 PRINTER DATA AND ELECTRICAL
07 COMPUTER DATA AND ELECTRICAL
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
123456789
04 A3.12
02 A3.11
08.02 08.02 08.06
13 A3.22
09 A3.22
46' - 0" R.O.2'-0"8'-0"8'-0" 4'-0" 8'-0"8'-0"8'-0"23.04 1'-6"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"18'-0"18'-0"18'-0"18'-0"18'-0" 10 A8.51
05 A8.51
09 A8.51
09 A8.52
12 A8.32
07 A8.32
04 A8.32
A8.31
11 TYP
TYP.28.02 52'-0"4.24.8 1.15.25.8
VARIES
T.O. EAVE
TYP.28.03
TYP.23.05
TYP.07.50TYP.10.03TYP.13.03
TYP.10.01
TYP.28.02
TYP.26.11
01 - FLOOR
0'-0"
123456789
04 A3.12
02 A3.11
4.9 G.54.24.8 1.15.25.8
VARIES
T.O. EAVE
TYP.13.06TYP.13.02
KEYNOTESLEGENDGENERAL NOTES
1. 2.
3. GLAZING (1) WITHIN 24" OF EITHER SIDE OF ANY DOOR; (2) GREATER THAN 9 SQ. FT. IN AREA WITH BOTTOM EDGE LESS THAN 18" ABOVE (AND HORIZONTALLY, WITHIN 36") OF A WALKING SURFACE SHALL BE SAFETY GLAZED (I.E., TEMPERED). CBC 2406 SAFETY GLAZING USED IN THE HAZARDOUS LOCATIONS INDICATED SHALL BE TESTED IN ACCORDANCE WITH CPSC CFR PART 1201 AND SHALL BE IDENTIFIED BY A
MANUFACTURER'S DESIGNATION SPECIFYING WHO APPLIED THE DESIGNATION, THE MANUFACTURER OR INSTLALER, AND THE SAFETY GLAZING STANDARD WITH WHICH IT COMPLIES (CBC 2406.2, CBC 2406.3).
BUILDING TO RECEIVE ANTI-GRAFFITI COATING ALL AROUND UP TO 8'0".
INSULATED METAL WALL PANELS, 24" WIDE,
HORIZONTAL ORIENTATION, 3" THICKNESS
MANUFACTURER: KING SPAN OR SIMILAR
SURFACE PROFILE: QUADCORE, OPTIMO
COLOR: TBC
R VALUE: 24 MIN.
1" INSULATED GLAZING UNIT
SOLARBAN 70
U VALUE:
SHGC:
ALUMINIUM MULLION COLOR TO BE
ANODIZED STANDARD
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 1/8" = 1'-0"COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
EXTERIOR
ELEVATIONS
A3.01
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/8" = 1'-0"04EXHIBIT HALL ELEVATION - NORTH 1/8" = 1'-0"02EXHIBIT HALL FRAME ELEVATION - NORTH
07.50 ROOF ACCESS HATCH WITH PERMANENT GUARDRAIL BY PEMB
08.02 GLASS SECTIONAL OVERHEAD ROLL UP DOOR. REFER TO DOOR SCHEDULE.
08.06 ALUMINUM CURTAIN WALL SYSTEM WITH 1" INSULATED GLAZING UNIT
10.01 SIGNAGE. REFER TO SIGNAGE DRAWINGS.
10.03 ROOF TIE BACK ANCHOR
13.02 STEEL BRACE FRAME WITH HIGH PERFORMANCE EXTERIOR FINISH BY PEMB
MANUFACTURER
13.03 STEEL BEAM WITH HIGH PERFORMANCE FINISH BY PEMB MANUFACTURER
13.06 PRIMARY STRUCTURAL STEEL FRAME BY PEMB MANUFACTURER
23.04 PAD MOUNTED CONDENSING UNIT. SEE MECHANICAL DRAWINGS.
23.05 VENT CAP. SEE MECHANICAL DRAWINGS.
26.11 WALL RECEPTACLE. REFER TO ELECTRICAL DRAWINGS.
28.02 FIRE ALARM HORN. REFER TO ELECTRICAL DRAWINGS.
28.03 FIRE BELL. REFER TO ELECTRICAL DRAWINGS.
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
AF
03 A3.11
DE
07.01 26.11
OPEN TO
BEYOND
C A.1BD.9 B.1
49'-6 3/4"
T.O. LOW EAVE
54'-8"
T.O. HIGH EAVE
TYP.26.13
TYP.10.01
TYP.28.02
KEYNOTESLEGENDGENERAL NOTES
1. 2.
3. GLAZING (1) WITHIN 24" OF EITHER SIDE OF ANY DOOR; (2) GREATER THAN 9 SQ. FT. IN AREA WITH BOTTOM EDGE LESS THAN 18" ABOVE (AND HORIZONTALLY, WITHIN 36") OF A WALKING SURFACE SHALL BE SAFETY GLAZED (I.E., TEMPERED). CBC 2406 SAFETY GLAZING USED IN THE HAZARDOUS LOCATIONS INDICATED SHALL BE TESTED IN ACCORDANCE WITH CPSC CFR PART 1201 AND SHALL BE IDENTIFIED BY A
MANUFACTURER'S DESIGNATION SPECIFYING WHO APPLIED THE DESIGNATION, THE MANUFACTURER OR INSTLALER, AND THE SAFETY GLAZING STANDARD WITH WHICH IT COMPLIES (CBC 2406.2, CBC 2406.3).
BUILDING TO RECEIVE ANTI-GRAFFITI COATING ALL AROUND UP TO 8'0".
INSULATED METAL WALL PANELS, 24" WIDE,
HORIZONTAL ORIENTATION, 3" THICKNESS
MANUFACTURER: KING SPAN OR SIMILAR
SURFACE PROFILE: QUADCORE, OPTIMO
COLOR: TBC
R VALUE: 24 MIN.
1" INSULATED GLAZING UNIT
SOLARBAN 70
U VALUE:
SHGC:
ALUMINIUM MULLION COLOR TO BE
ANODIZED STANDARD
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
08.01 TYP.08.06
17 A3.22
6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"1'-6" 12 A8.32
04 A8.32
01 A8.32
15 A8.53
13 A8.538'-0"2'-0"8'-0"8'-0" 4'-0" 8'-0"8'-0"67'-6"
1/2"
12"43'-1 3/4"BBEEFF AACCDD
VARIES
T.O. EAVE
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 1/8" = 1'-0"COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
EXTERIOR
ELEVATIONS
A3.02
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/8" = 1'-0" A3.02 04EXTERIOR ELEVATION - WEST
07.01 STANDING SEAM METAL ROOF
08.01 GLASS HANGER DOOR SYSTEM. REFER TO DOOR SCHEDULE.
08.06 ALUMINUM CURTAIN WALL SYSTEM WITH 1" INSULATED GLAZING UNIT
10.01 SIGNAGE. REFER TO SIGNAGE DRAWINGS.
26.11 WALL RECEPTACLE. REFER TO ELECTRICAL DRAWINGS.
26.13 EXTERIOR COLUMN MOUNTED LIGHT FIXTURE. REFER TO ELECTRICAL DRAWINGS.
28.02 FIRE ALARM HORN. REFER TO ELECTRICAL DRAWINGS.
1/8" = 1'-0"
A3.02 02EXTERIOR ELEVATION - NORTHWEST
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
12345 6 7 8 9
04 A3.12 02
A3.11
07.01 13
A3.22
09 A3.22
23.04 23.02
1'-8"
19 A8.51
82.00°18
A8.51
17 A8.51
18 A8.51
17 A8.51
10 A8.51
11 A8.51
09 A8.51
TYP.26.11 28.02
19 A8.51
PANEL JOINT
15'-7"
PANEL JOINT
8'-5"
07.06 07.0607.0607.0607.0607.06 07.06
4.24.81.1 5.2 5.8
VARIES
T.O. EAVE
TYP.07.50TYP.10.03 TYP.22.06
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
A F03
A3.11
D E
07.03 08.02
13 A3.23
08.044'-0" R.O.07.03
OPEN TO
BEYOND
27'-0"7'-4"
C
14 A8.51
13 A8.51
15 A8.51
12 A8.52
09 A8.52
23.02 TYP.26.11
TYP.28.02
TYP.23.0510
A8.52
TYP.26.09
B D.9
54'-8"
T.O. HIGH EAVE
49'-6 3/4"
T.O. LOW EAVE
9'-0"9'-0"
TYP.10.03
TYP.26.13
TYP.10.01
KEYNOTESLEGENDGENERAL NOTES
1. 2.
3. GLAZING (1) WITHIN 24" OF EITHER SIDE OF ANY DOOR; (2) GREATER THAN 9 SQ. FT. IN AREA WITH BOTTOM EDGE LESS THAN 18" ABOVE (AND HORIZONTALLY, WITHIN 36") OF A WALKING SURFACE SHALL BE SAFETY GLAZED (I.E., TEMPERED). CBC 2406 SAFETY GLAZING USED IN THE HAZARDOUS LOCATIONS INDICATED SHALL BE TESTED IN ACCORDANCE WITH CPSC CFR PART 1201 AND SHALL BE IDENTIFIED BY A
MANUFACTURER'S DESIGNATION SPECIFYING WHO APPLIED THE DESIGNATION, THE MANUFACTURER OR INSTLALER, AND THE SAFETY GLAZING STANDARD WITH WHICH IT COMPLIES (CBC 2406.2, CBC 2406.3).
BUILDING TO RECEIVE ANTI-GRAFFITI COATING ALL AROUND UP TO 8'0".
INSULATED METAL WALL PANELS, 24" WIDE,
HORIZONTAL ORIENTATION, 3" THICKNESS
MANUFACTURER: KING SPAN OR SIMILAR
SURFACE PROFILE: QUADCORE, OPTIMO
COLOR: TBC
R VALUE: 24 MIN.
1" INSULATED GLAZING UNIT
SOLARBAN 70
U VALUE:
SHGC:
ALUMINIUM MULLION COLOR TO BE
ANODIZED STANDARD
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
1 07.05
VARIES
T.O. EAVE
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 1/8" = 1'-0"COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
EXTERIOR
ELEVATIONS
A3.03
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/8" = 1'-0" A3.03 04EXTERIOR ELEVATION - SOUTH
1/8" = 1'-0"
A3.03 02EXTERIOR ELEVATION - EAST
07.01 STANDING SEAM METAL ROOF
07.03 SHEET METAL FASCIA
07.05 INSULATED METAL WALL PANELS
07.06 MANUFACTURED METAL DOWNSPOUT
07.50 ROOF ACCESS HATCH WITH PERMANENT GUARDRAIL BY PEMB
08.02 GLASS SECTIONAL OVERHEAD ROLL UP DOOR. REFER TO DOOR SCHEDULE.
08.04 STOREFRONT WINDOW SYSTEM.
10.01 SIGNAGE. REFER TO SIGNAGE DRAWINGS.
10.03 ROOF TIE BACK ANCHOR
13.04 STEEL COLUMN BY METAL BUILDING MANUFACTURER
22.06 PLUMBING VENT THROUGH ROOF. SEE PLUMBING DRAWINGS.
23.01 MECHANICAL EQUIPMENT - SEE MECHANICAL DRAWINGS.
23.02 MECHANICAL LOUVER. SEE MECHANICAL DRAWINGS.
23.04 PAD MOUNTED CONDENSING UNIT. SEE MECHANICAL DRAWINGS.
23.05 VENT CAP. SEE MECHANICAL DRAWINGS.
26.09 EXTERIOR WALL MOUNTED LIGHT FIXTURE. REFER TO ELECTRICAL DRAWINGS.
26.11 WALL RECEPTACLE. REFER TO ELECTRICAL DRAWINGS.
26.13 EXTERIOR COLUMN MOUNTED LIGHT FIXTURE. REFER TO ELECTRICAL DRAWINGS.
28.02 FIRE ALARM HORN. REFER TO ELECTRICAL DRAWINGS.
1/8" = 1'-0"
A3.0318EXHIBIT HALL ELEVATION NORTH - WING WALL
01 - FLOOR
0'-0"
345
04 A3.12
TYP.07.05
OPEN TO BEYOND
4.9 G.5
SG4.02
06 TYP.26.11
4.24.8 05.01
16'-6"
T.O. HIGH EAVE
14'-0"
T.O. LOW EAVE
2'-0"01 - FLOOR
0'-0"
07.05 TYP.23.04TYP.26.08
TYP.23.05
SG4.02
05 07.02
VARIES
T.O. EAVE
TYP.22.07
TYP.23.0505.18
01 - FLOOR
0'-0"
34 04
A3.12
TYP.07.0508.03
05.01 4.9G.5
OPEN TO BEYOND
05.02 4.24.8
16'-6"
T.O. HIGH EAVE
14'-0"
T.O. LOW EAVE
05.19 01 - FLOOR
0'-0"
TYP.07.0508.03 TYP.08.03
07 A3.21
TYP.28.02
TYP.26.11
VARIES
T.O. EAVE
KEYNOTESLEGENDGENERAL NOTES
1. 2.
3. GLAZING (1) WITHIN 24" OF EITHER SIDE OF ANY DOOR; (2) GREATER THAN 9 SQ. FT. IN AREA WITH BOTTOM EDGE LESS THAN 18" ABOVE (AND HORIZONTALLY, WITHIN 36") OF A WALKING SURFACE SHALL BE SAFETY GLAZED (I.E., TEMPERED). CBC 2406 SAFETY GLAZING USED IN THE HAZARDOUS LOCATIONS INDICATED SHALL BE TESTED IN ACCORDANCE WITH CPSC CFR PART 1201 AND SHALL BE IDENTIFIED BY A
MANUFACTURER'S DESIGNATION SPECIFYING WHO APPLIED THE DESIGNATION, THE MANUFACTURER OR INSTLALER, AND THE SAFETY GLAZING STANDARD WITH WHICH IT COMPLIES (CBC 2406.2, CBC 2406.3).
BUILDING TO RECEIVE ANTI-GRAFFITI COATING ALL AROUND UP TO 8'0".
INSULATED METAL WALL PANELS, 24" WIDE,
HORIZONTAL ORIENTATION, 3" THICKNESS
MANUFACTURER: KING SPAN OR SIMILAR
SURFACE PROFILE: QUADCORE, OPTIMO
COLOR: TBC
R VALUE: 24 MIN.
1" INSULATED GLAZING UNIT
SOLARBAN 70
U VALUE:
SHGC:
ALUMINIUM MULLION COLOR TO BE
ANODIZED STANDARD
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 1/8" = 1'-0"COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
EXTERIOR
ELEVATIONS
A3.04
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/8" = 1'-0" A3.04 10STEM BUILDING - EXTERIOR ELEVATION - NORTH
1/8" = 1'-0"16STEM BUILDING - EXTERIOR ELEVATION - WEST 1/8" = 1'-0"
A3.0418STEM BUILDING - EXTERIOR ELEVATION - SOUTH 1/8" = 1'-0" A3.04 02STEM BUILDING - EXTERIOR ELEVATION - EAST
05.01 TUBE STEEL COLUMN WITH HIGH PERFORMANCE FINISH. REFER TO STRUCTURAL DRAWINGS.
05.02 SHEET METAL FASCIA
05.18 METAL COPING, FINISH TO MATCH ADJACENT PANELS
05.19 SHEET METAL FASCIA JOINT TO MATCH AND CONTINUE FROM ADJACENT
WALL PANEL
07.02 SHEET METAL GUTTER
07.05 INSULATED METAL WALL PANELS
08.03 GLASS BI-FOLD DOOR SYSTEM WITH INTEGRATED EGRESS PANEL. REFER TO DOOR SCHEDULE.
22.07 FIRE RISER. REFER TO PLUMBING DRAWINGS.
23.04 PAD MOUNTED CONDENSING UNIT. SEE MECHANICAL DRAWINGS.
23.05 VENT CAP. SEE MECHANICAL DRAWINGS.
26.08 PANELBOARD. REFER TO ELECTRICAL DRAWINGS.
26.11 WALL RECEPTACLE. REFER TO ELECTRICAL DRAWINGS.
28.02 FIRE ALARM HORN. REFER TO ELECTRICAL DRAWINGS.
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
12345 6 7 8 9
04 A3.12
02 A3.11
6190 SF
OPEN
EXHIBIT
SPACE
200
8950 SF
EXHIBIT
SPACE
100 320 SF
WOMEN'S
RESTROOM
107 207 SF
IDF
ROOM
105 502 SF
MECHANICAL
ROOM
103
10 A7.02
A3.23
17 4.24.81.15.2 5.8
VARIES
T.O. EAVE
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
AF
03 A3.11
DE
6190 SF
OPEN
EXHIBIT
SPACE
200
255 SF
ELECTRICAL
ROOM
104207 SF
IDF
ROOM
1051731 SF
STORAGE
101
808 SF
STAFF
ROOM
102
A3.23
05A3.22
05 10'-0"A8.21
11 C BD.9
49'-6 3/4"
T.O. LOW EAVE
54'-8"
T.O. HIGH EAVE
2'-8 1/4"TYP.23.06TYP.26.06
TYP.26.06
KEYNOTESLEGENDGENERAL NOTES
1.PROVIDE BELOW GRADE WATERPROOFING AT ALL BUILDING WALLS, SITE RETAINING WALLS AND ELEVATOR PIT.METAL STUD WALL CONSTRUCTION 1 HOUR RATED METAL STUD WALL CONSTRUCTION
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 1/8" = 1'-0"COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
BUILDING
SECTIONS
A3.11
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/8" = 1'-0" A3.11 03BUILDING SECTION C
1/8" = 1'-0"
A3.11 02BUILDING SECTION B
23.06 MECHANICAL DUCTWORK. REFER TO MECHANICAL DRAWINGS.
26.06 LIGHTING FIXTURE. REFER TO LIGHTING DRAWINGS.
01 - FLOOR
0'-0"
3 4 5
04 A3.12
751 SF
STEM
CLASSROOM
112
4.9G.5
08.03 A8.21
01 A3.21
07 4.2 4.8 5.2
16'-6"
T.O. HIGH EAVE
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
AF
03 A3.11
H
02 A3.12
DE
751 SF
STEM
CLASSROOM
112652 SF
STEM
CLASSROOM
113
8950 SF
EXHIBIT
SPACE
100
A3.21
05 A3.21
13 F.1G
A3.21
09 C
A3.22
09 SIM
A3.23
05 SIM
A8.21
11 BD.9
49'-6 3/4"
T.O. LOW EAVE
54'-8"
T.O. HIGH EAVE
KEYNOTESLEGENDGENERAL NOTES
1.PROVIDE BELOW GRADE WATERPROOFING AT ALL BUILDING WALLS, SITE RETAINING WALLS AND ELEVATOR PIT.METAL STUD WALL CONSTRUCTION 1 HOUR RATED METAL STUD WALL CONSTRUCTION
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 1/8" = 1'-0"COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
BUILDING
SECTIONS
A3.12
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/8" = 1'-0" A3.12 02BUILDING SECTION D
1/8" = 1'-0"
A3.12 04BUILDING SECTION A
08.03 GLASS BI-FOLD DOOR SYSTEM WITH INTEGRATED EGRESS PANEL. REFER TO DOOR SCHEDULE.
01 - FLOOR
0'-0"
F
STEM
CLASSROOM
112R2A 08.03
F.1
EDGE OF
COLUMNS
BEYOND
(EXHIBIT
BUILDING)
0'-6"
A8.21
10 A8.51
05 A8.51
06 W2
VARIES
T.O. EAVE
H
STEM
CLASSROOM
113R2AA8.21
10 W2
A8.31
01 KEYNOTES
1. 2.
SEE A9.0X SERIES FOR WALL TYPES
SEE 8.10 FOR EXTERIOR ASSEMBLIES
LEGEND
GENERAL NOTES
KEYNOTE, SEE KEYNOTE SCHEDULEXX.XX
XX EXTERIOR ASSEMBLY TAG
G
R2AA9.11
16 A9.11
14 STEM
CLASSROOM
112
STEM
CLASSROOM
113
01 - FLOOR
0'-0"
12 R2AW2R2B
A8.51
05 A8.51
06 STEM
CLASSROOM
112
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
WALL SECTIONS
A3.21
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/2" = 1'-0"05STEM WALL A 1/2" = 1'-0"13STEM WALL B
08.03 GLASS BI-FOLD DOOR SYSTEM WITH INTEGRATED EGRESS PANEL.
REFER TO DOOR SCHEDULE.
1/2" = 1'-0"09WALL SECTION - STEM DIVIDING
WALL
1/2" = 1'-0"07WALL SECTION E
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
10 EXHIBIT
SPACE
100
W2
GA1R2BR2A05.10
A8.53
15 A8.32
04 A8.31
12 A8.32
02 A8.53
13 01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
E
STAFF
ROOM
102
W1 R1AR1B05.10
05.10 05.10
09.04 OPEN
EXHIBIT
SPACE
200
A8.31
02 A8.31
04 D.9
13.02 01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
E
EXHIBIT
SPACE
100
W1
GA1
05.10 08.02
A8.31
04 R1AR1BA8.52
09 A8.52
01 D.9
KEYNOTES
1. 2.
SEE A9.0X SERIES FOR WALL TYPES
SEE 8.10 FOR EXTERIOR ASSEMBLIES
LEGEND
GENERAL NOTES
KEYNOTE, SEE KEYNOTE SCHEDULEXX.XX
XX EXTERIOR ASSEMBLY TAG
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
E
A8.32
04 A8.32
02 A8.32
01 W2
A8.31
04R1AR1B
EXHIBIT
SPACE
100
D.9
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
WALL SECTIONS
A3.22
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/2" = 1'-0"17FOLDING DOOR AT CURTAIN WALL 1/2" = 1'-0"05SECOND FLOOR AT IMP WALL 1/2" = 1'-0"09ROLLUP DOOR AT CURTAIN WALL
05.10 HOLLOW STEEL SECTION. REFER TO STRUCTURAL DRAWINGS.
08.02 GLASS SECTIONAL OVERHEAD ROLL UP DOOR. REFER TO DOOR SCHEDULE.
09.04 CEILING. REFER TO REFLECTED CEILING PLAN.
13.02 STEEL BRACE FRAME WITH HIGH PERFORMANCE EXTERIOR FINISH
BY PEMB MANUFACTURER
1/2" = 1'-0"13EXHIBIT HALL CURTAINWALL
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
A
ELECTRICAL
ROOM
104
OPEN
EXHIBIT
SPACE
200 R1A23.01
A8.21
03 A8.51
18 A8.51
17 W1
A8.33
09 TYP.23.02
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
9 STAFF
ROOM
102
OPEN
EXHIBIT
SPACE
200R2A
26.06 23.01
08.04 A8.33
09 A8.51
14 A8.51
13 A8.31
02 A8.21
04 W1
13.02 KEYNOTES
1. 2.
SEE A9.0X SERIES FOR WALL TYPES
SEE 8.10 FOR EXTERIOR ASSEMBLIES
LEGEND
GENERAL NOTES
KEYNOTE, SEE KEYNOTE SCHEDULEXX.XX
XX EXTERIOR ASSEMBLY TAG
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
9 A8.33
11 A8.33
12 A8.33
20 A8.51
10 A8.51
09 A8.21
04 W1
MECHANICAL
ROOM
103
TYP.23.01
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
WALL SECTIONS
A3.23
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/2" = 1'-0"05DOOR AT IMP WALL 1/2" = 1'-0"13WINDOW AT IMP WALL
08.04 STOREFRONT WINDOW SYSTEM.
13.02 STEEL BRACE FRAME WITH HIGH PERFORMANCE EXTERIOR FINISH BY PEMB
MANUFACTURER
23.01 MECHANICAL EQUIPMENT - SEE MECHANICAL DRAWINGS.
23.02 MECHANICAL LOUVER. SEE MECHANICAL DRAWINGS.
26.06 LIGHTING FIXTURE. REFER TO LIGHTING DRAWINGS.
1/2" = 1'-0"17MECHANICAL SHAFT
FCG30" X 48"CLR. FLR.SPACE30" X 48"CLR. FLR.SPACE30" X 48" CLR. FLR.
SPACE
30" X 48"CLR. FLR.SPACE30" X 48"CLR. FLR.SPACE30" X 48"CLR. FLR.SPACE30" X 48" CLR. FLR.
SPACE
30" X 48"CLR. FLR.SPACE30" X 48"
CLR. FLR.
SPACE
CGOS
OS
OS
OSOOSZ-3BK
KOS
OOS
7 7
8 8
A A
JANITOR'S
ROOM
109
FAMILY
RESTROOM
108
STAFF
RESTROOM
114
WOMEN'S
RESTROOM
107
MEN'S
RESTROOM
106
44" MIN. CLR4'-2" F.O.F.44" MIN. CLR4'-2" F.O.F.SA8
SA8
SD4
SD4
SA4
SA4
SA4
SA4
SD4
SD4
SA8
SA4
SA8
SD4SD4
SA4
1'-7"10'-9"6'-9"2'-7"2'-11"5'-8 1/4"8'-1"10'-10 3/4"7'-5"1'-6"7'-4 1/2"1'-6" 1'-7"
0'-8"
3'-11 141/256" 7'-1 115/256"ALIGN22.04
23.01 22.05
SA4
6'-9 115/256"
A8.33
01 SD8
FOF
1'-5 1/2".ø 5'-0"ø 5'-0"
22.05 22.05
CC
B B
36" X 48" CLR. FLR. SPACE8'-5"5'-0" MIN. CLR.
5'-4 1/8" FOFEQ. EQ.MIN1'-6".FOF1'-5 1/2".NURSING
ROOM
116 MIN1-6".22.05
FOF4'-2"FOF
1'-6"
22.08 EQ. EQ.EQ. EQ.EQ. EQ.
4 EQUAL
11'-2 1/2"FOF5'-11"22.05
SA8
FOF
2'-0"
FOF
2'-0"
FOF
2'-0"
6'-9 1/2"
FOF
2'-0"SA6
SD4SA65'-11"7
7 JANITOR'S
ROOM
109
FAMILY
RESTROOM
108
WOMEN'S
RESTROOM
107
MEN'S
RESTROOM
106
STAFF
RESTROOM
114
A5.01
08 A5.08
02 A5.01
18 02
06 14
A5.01
07 03
19 15
04 16
12A5.02
16 04
08 12
T-1
T-1
T-1
A5.01 5
A5.01 1
CC
B B
A5.0920
NURSING
ROOM
116
RF-2
B-2
PC-1
B-2
FRP
T-1
A5.0220
24 TILE
START
POINT
TILE
START
POINT
TILE
START
POINT
TILE
START
POINT
7 7
10' - 0"
GYP-2
10' - 0"
GYP-2
10' - 0"
GYP-2
10' - 0"
GYP-2
JANITOR'S
ROOM
109
FAMILY
RESTROOM
108
WOMEN'S
RESTROOM
107
MEN'S
RESTROOM
106
STAFF
RESTROOM
114
26.06 23.01
10' - 0"
GYP-1
CC
BB
10' - 0"
GYP-1
NURSING
ROOM
116
10' - 0"
CL-1
KEYNOTES
1. 2.
1. SEE A9.01 SERIES FOR WALL TYPES
EDGE OF DOOR FRAME TO BE 4" FROM PERPENDICULAR WALL UNO
DIMENSIONS ARE TO FACE OF STUD UNO
LEGENDGENERAL NOTES
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.0X SERIES.
STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.0X SERIES.
REFER TO S0.91 FOR INTERIOR STUD WALL SCHEDULE
METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION
2 HOUR RATED METAL STUD WALL CONSTRUCTION
GYP-2
FRAMED GYPSUM BOARD, MOISTURE RESISTANT,
SEMI-GLOSS PAINT (WET LOCATIONS)
FLOORING TRANSITION. SEE 01/A9.51
CL-1
2 X 4 SUSPENDED ACOUSTICAL CEILING TILE,
ARMSTRONG, CALLA, VECTOR
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
ENLARGED
RESTROOM PLANS
A4.01
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/4" = 1'-0"03RESTROOM PLAN 1/4" = 1'-0"11RESTROOM FINISH PLAN 1/4" = 1'-0"19RESTROOM REFLECTED CEILING PLAN
22.04 JANITORIAL SINK; REFER TO PLUMBING DRAWINGS.
22.05 FLOOR DRAIN. REFER TO PLUMBING DRAWINGS.
22.08 CHILLED HI-LO DRINKING FOUNTAIN WITH WATER BOTTLE FILLER, RECESSED MECHANICAL PUSH BAR ACTUATOR, SEE PLUMBING.
23.01 MECHANICAL EQUIPMENT - SEE MECHANICAL DRAWINGS.
26.06 LIGHTING FIXTURE. REFER TO LIGHTING DRAWINGS.
KEYNOTESLEGENDGENERAL NOTES
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
11. 12.
13. 14.
15. 16.
17. FOR WALL TYPES, REFER TO FLOOR PLANS.
SEE FINISH SCHEDULES AND SPECIFICATIONS ON SHEET 1-A900.
SEE RCP FOR CEILING FINISHES AND SEE DOOR SCHEDULE FOR DOOR FINISHES.
ALL INTERIOR WALL AND CEILING FINISH MATERIALS TO COMPLY WITH SECTION 803 - IN ACCORDANCE WITH ASTM E-84 NFPA 286 WITH ALL FINISHES CLASSIFIED AS CLASS "A".INTERIOR EXIT STAIRWAYS AND RAMPS AND EXIT PASSAGEWAYS ARE NOT TO EXCEED CLASS "B." CORRIDORS AND ENCLOSURE FOR EXIT ACCESS STAIRWAYS AND RAMPS ARE TO NOT TO EXCEED CLASS "C."
INTERIOR WALL AND CEILING FINISH MATERIAL CLASS PER 803.13 IS TO MEET FLAME SPREAD AND SMOKE DENSITY IN ACCORDANCE WITH CBC TABLE 803.1.2.
PREPARE SLAB AS REQUIRED BY MANUFACTURERS' RECOMMENDATION FOR EACH SPECIFIED FINISH.
ACCESS PANELS SHALL BE PAINTED TO MATCH ADJACENT WALL, WHERE OCCURS.
ALL GYPSUM BOARD WALLS AND SOFFITS TO BE PAINTED.
CONTINUE FLOORING UNDER ACCESSIBLE SINK CABINET AND EQUIPMENT NICHE.
PROVIDE LOW VOC PAINTS AND ADHESIVES THROUGHOUT.
PROVIDE 'FEATHER UP' TRANSITION AT ALL DOORS FOR SMOOTH TRANSITION.
PROVIDE THRESHOLDS AT ALL FLOORING TRANSITIONS.
MOISTURE TEST: PROVIDE MOISTURE TEST THROUGHOUT. VERIFY MOISTURE LEVELS WITHIN PRODUCT MANUFACTURERS ACCEPTABLE LEVELS, PER WARRANTY RESTRICTIONS.
PROVIDE CHUNTER AT WALL TILE EXPOSED EDGES SPECIFICATION: SCHLUTER SYSTEM, JOLLY BRUSHED FINISH, ANODIZED ALUMINUM.
FLOOR COVERING MATERIALS SHALL COMPLY WITH ASTM E 648, AND HAVE A SMOKE DENSITY RATING OF LESS THAN 450 PER ASTM E 84. CBC 804.4.1.
DO NOT PLACE UTILITY ITEMS SUCH AS THERMOSTATS, POWER OUTLETS, SWITCHES, AND CABINETS, FIRE EXTINGUISHERS, FIRESTROBES ON ACCENT AND GRAPHIC WALLS.
TILE APPLICATION: LAY TILE ACCORDING TO PATTERN INDICATED ON CONSTRUCTION DOCS. IF THERE IS A CONFLICT WITH THE MFGR'S RECOMMENDATIONS, THE MFGR'S RECOMMENDATIONS WILL GOVERN THE INSTALLATION METHOD. LARGE FORMAT TILES [ANY TILE WITH/ AN EDGE DIMENSION EQUAL OR GREATER THAN 15"] WILL HAVE A 30% OFFSET AS OPPOSED TO A 50% OFFSET. VERIFY TILE TO TILE JOINT RELATIONSHIP WITH/ MFGR TO AVOID "LIPPAGE". DO NOT INTERRUPT TILE PATTERN THROUGHOUT OPENINGS. .
#EQUIPMENT TAG, REFER TO SHEET A2.51
FINISH SYMBOL
FINISH CODE - REFER TO FINISH SCHEDULE ON A2.21.
ALIGN FINISHES
CASEWORK TAG, REFER TO 03/A9.31 FOR SECTIONS
WIDTH
#
30" 36"
42"
HEIGHT
DEPTH
WOOD INSTITUTE NUMBER
TEMPERED GLAZING SYMBOLT
?
RESTROOM ACCESSORY TAGX-X
EQUIPMENT TAG - REFER TO EQUIPMENT SCHEDULE ON AX.XXX-X
KEYNOTEX-X
T-3E
B
4'-11"
OPEN TO
BEYOND
T-2
2'-10"TYP.22.02
TYP.22.01
10 A9.31
T-2
B
SS-1
PL-1 MAX1'-5".T-2
OPEN TO
BEYOND
T-2ET-3
B
2'-4 1/4"4'-2 1/2"
T-2
TYP.22.01
10 A9.31T-2
A42B
SS-1
PL-12'-10"MAX1'-7".3'-0" MAX22.03 22.01
T-2
A42 1'-6"3'-0" MAXT-2T-2
1'-7 1/2"1'-10"
22.01 T-3
A421'-6"3'-0" MAXT-2
B22.01 1'-0" 6'-0"
T-2
A42B 3'-0" MAX1'-6"1'-0" 6'-0"
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
INTERIOR
RESTROOM
ELEVATIONS
A5.01
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/4" = 1'-0" A5.0118MEN'S RESTROOM ELEVATION SOUTH 1/4" = 1'-0"02MEN'S RESTROOM ELEVATION EAST 1
1/4" = 1'-0"06MEN'S RESTROOM ELEVATION
NORTH
1/4" = 1'-0"14MEN'S RESTROOM ELEVATION
WEST
1/4" = 1'-0"03WOMEN'S RESTROOM ELEVATION
EAST 1
1/4" = 1'-0"07WOMEN'S RESTROOM ELEVATION NORTH 1/4" = 1'-0"15WOMEN'S RESTROOM ELEVATION WEST
1/4" = 1'-0"
A5.0119WOMEN'S RESTROOM ELEVATION SOUTH
1/4" = 1'-0"04FAMILY RESTROOM ELEVATION
EAST
1/4" = 1'-0"08FAMILY RESTROOM ELEVATION
NORTH
1/4" = 1'-0"12FAMILY RESTROOM ELEVATION
WEST
1/4" = 1'-0"16FAMILY RESTROOM ELEVATION
SOUTH
N BOBRICK B-353 RECESSED SANITARY NAPKIN DISPOSAL
M BRADLEY 2B1-11000
0 ELVARI SURFACE MOUNTED TOWEL DISPENSER.
MEDIUM CAPACITY, PROVIDE BACKING
L BRADLEY 3B1-000... WASTE RECEPTACLE - RECESSED
K BOBRICK B-2111 SURFACE-MOUNTED SOAP DISPENSER
J BOBRICK B-212 PARTITION MOUNTED COAT HOOK WITH BUMPER I BOBRICK B-2116 HEAVY DUTY HOOK WITH CONCEALED MOUNTING WITHSTAND 300 LBS. PROVIDE BACKING.
H SLOAN VALVE ESD-410... SLOAN DECK MOUNTED FOAM SOAP DISPENSER,...
G BOBRICK B-357 SHARED PARTITION MOUNTED TOILET SEAT COVER DISPENSER, WASTE DISPOSAL, AND TOILET TISSUE...
F BOBRICK B-3091 OR
B-3092
RECESSED TOILET SEAT COVER, WASTE DISPOSAL AND
TOILET TISSUE DISPENSER.
E KOALA CARE KB110-SS
WM
BABY CHANGING STATION - SURFACE MOUNTED
STAINLESS STEEL; PROVIDE BACKING PER XX/XXX
D2 BOBRICK B-290-24... MIRROR - 24" X 72" STAINLESS STEEL MIRROR D1 BOBRICK B-290-24... MIRROR - 24" X 36" STAINLESS STEEL MIRROR C HADRIAN ??? URINAL SCREEN - WALL BRACED STAINLESS STEEL 5WL TEXTURED FINISH; SEE DETAIL XX/XXX
B HADRIAN ??? ELITE
SERIES
RESTROOM PARTITION - FLOOR SUPPORTED
OVERHEAD BRACED STAINLESS STEEL 5WL TEXTURE...
A42 BOBRICK B-6806 GRAB BARS - 1 1/2" DIAMETER STAINLESS STEEL BARS WITH SNAP FLANGE/ REFER TO XX/XXX. PROVIDE...
A36 BOBRICK B-6806 GRAB BARS - 1 1/2" DIAMETER STAINLESS STEEL BARS
WITH SNAP FLANGE/ REFER TO XX/XXX
TYPE
MA...
MANUFACTUR
ER
MODEL # DESCRIPTION
RESTROOM ACCESSORIES SCHEDULE
22.01 WALL MOUNTED TOILET; REFER TO PLUMBING DRAWINGS.
22.02 WALL MOUNTED URINAL; REFER TO PLUMBING DRAWINGS.
22.03 ADA WALL MOUNTED SINK; REFER TO PLUMBING DRAWINGS. 1/4" = 1'-0"1MENS RESTROOM ELEVATION
EAST 2
1/4" = 1'-0"5WOMENS RESTROOM ELEVATION
EAST 2
KEYNOTESLEGENDGENERAL NOTES
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
11. 12.
13. 14.
15. 16.
17. FOR WALL TYPES, REFER TO FLOOR PLANS.
SEE FINISH SCHEDULES AND SPECIFICATIONS ON SHEET 1-A900.
SEE RCP FOR CEILING FINISHES AND SEE DOOR SCHEDULE FOR DOOR FINISHES.
ALL INTERIOR WALL AND CEILING FINISH MATERIALS TO COMPLY WITH SECTION 803 - IN ACCORDANCE WITH ASTM E-84 NFPA 286 WITH ALL FINISHES CLASSIFIED AS CLASS "A".INTERIOR EXIT STAIRWAYS AND RAMPS AND EXIT PASSAGEWAYS ARE NOT TO EXCEED CLASS "B." CORRIDORS AND ENCLOSURE FOR EXIT ACCESS STAIRWAYS AND RAMPS ARE TO NOT TO EXCEED CLASS "C."
INTERIOR WALL AND CEILING FINISH MATERIAL CLASS PER 803.13 IS TO MEET FLAME SPREAD AND SMOKE DENSITY IN ACCORDANCE WITH CBC TABLE 803.1.2.
PREPARE SLAB AS REQUIRED BY MANUFACTURERS' RECOMMENDATION FOR EACH SPECIFIED FINISH.
ACCESS PANELS SHALL BE PAINTED TO MATCH ADJACENT WALL, WHERE OCCURS.
ALL GYPSUM BOARD WALLS AND SOFFITS TO BE PAINTED.
CONTINUE FLOORING UNDER ACCESSIBLE SINK CABINET AND EQUIPMENT NICHE.
PROVIDE LOW VOC PAINTS AND ADHESIVES THROUGHOUT.
PROVIDE 'FEATHER UP' TRANSITION AT ALL DOORS FOR SMOOTH TRANSITION.
PROVIDE THRESHOLDS AT ALL FLOORING TRANSITIONS.
MOISTURE TEST: PROVIDE MOISTURE TEST THROUGHOUT. VERIFY MOISTURE LEVELS WITHIN PRODUCT MANUFACTURERS ACCEPTABLE LEVELS, PER WARRANTY RESTRICTIONS.
PROVIDE CHUNTER AT WALL TILE EXPOSED EDGES SPECIFICATION: SCHLUTER SYSTEM, JOLLY BRUSHED FINISH, ANODIZED ALUMINUM.
FLOOR COVERING MATERIALS SHALL COMPLY WITH ASTM E 648, AND HAVE A SMOKE DENSITY RATING OF LESS THAN 450 PER ASTM E 84. CBC 804.4.1.
DO NOT PLACE UTILITY ITEMS SUCH AS THERMOSTATS, POWER OUTLETS, SWITCHES, AND CABINETS, FIRE EXTINGUISHERS, FIRESTROBES ON ACCENT AND GRAPHIC WALLS.
TILE APPLICATION: LAY TILE ACCORDING TO PATTERN INDICATED ON CONSTRUCTION DOCS. IF THERE IS A CONFLICT WITH THE MFGR'S RECOMMENDATIONS, THE MFGR'S RECOMMENDATIONS WILL GOVERN THE INSTALLATION METHOD. LARGE FORMAT TILES [ANY TILE WITH/ AN EDGE DIMENSION EQUAL OR GREATER THAN 15"] WILL HAVE A 30% OFFSET AS OPPOSED TO A 50% OFFSET. VERIFY TILE TO TILE JOINT RELATIONSHIP WITH/ MFGR TO AVOID "LIPPAGE". DO NOT INTERRUPT TILE PATTERN THROUGHOUT OPENINGS. .
#EQUIPMENT TAG, REFER TO SHEET A2.51
FINISH SYMBOL
FINISH CODE - REFER TO FINISH SCHEDULE ON A2.21.
ALIGN FINISHES
CASEWORK TAG, REFER TO 03/A9.31 FOR SECTIONS
WIDTH
#
30" 36"
42"
HEIGHT
DEPTH
WOOD INSTITUTE NUMBER
TEMPERED GLAZING SYMBOLT
?
RESTROOM ACCESSORY TAGX-X
EQUIPMENT TAG - REFER TO EQUIPMENT SCHEDULE ON AX.XXX-X
KEYNOTEX-X
T-2T-2
T-3
A4222.01MAX1'-7".3'-0" MAX22.01 22.03
T-2
A42 2'-10"2'-10"PER PLAN
1'-6"4'-0"
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
INTERIOR
RESTROOM
ELEVATIONS
A5.02
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/4" = 1'-0"04STAFF RESTROOM ELEVATION EAST
1/4" = 1'-0"08STAFF RESTROOM ELEVATION
NORTH
1/4" = 1'-0"16STAFF RESTROOM ELEVATION
SOUTH
1/4" = 1'-0"12STAFF RESTROOM ELEVATION
WEST
22.01 WALL MOUNTED TOILET; REFER TO PLUMBING DRAWINGS.
22.03 ADA WALL MOUNTED SINK; REFER TO PLUMBING DRAWINGS.
N BOBRICK B-353 RECESSED SANITARY NAPKIN DISPOSAL
M BRADLEY 2B1-11000
0 ELVARI SURFACE MOUNTED TOWEL DISPENSER.
MEDIUM CAPACITY, PROVIDE BACKING
L BRADLEY 3B1-000... WASTE RECEPTACLE - RECESSED
K BOBRICK B-2111 SURFACE-MOUNTED SOAP DISPENSER
J BOBRICK B-212 PARTITION MOUNTED COAT HOOK WITH BUMPER I BOBRICK B-2116 HEAVY DUTY HOOK WITH CONCEALED MOUNTING WITHSTAND 300 LBS. PROVIDE BACKING.
H SLOAN VALVE ESD-410... SLOAN DECK MOUNTED FOAM SOAP DISPENSER,...
G BOBRICK B-357 SHARED PARTITION MOUNTED TOILET SEAT COVER DISPENSER, WASTE DISPOSAL, AND TOILET TISSUE...
F BOBRICK B-3091 OR
B-3092
RECESSED TOILET SEAT COVER, WASTE DISPOSAL AND
TOILET TISSUE DISPENSER.
E KOALA CARE KB110-SS
WM
BABY CHANGING STATION - SURFACE MOUNTED
STAINLESS STEEL; PROVIDE BACKING PER XX/XXX
D2 BOBRICK B-290-24... MIRROR - 24" X 72" STAINLESS STEEL MIRROR D1 BOBRICK B-290-24... MIRROR - 24" X 36" STAINLESS STEEL MIRROR C HADRIAN ??? URINAL SCREEN - WALL BRACED STAINLESS STEEL 5WL TEXTURED FINISH; SEE DETAIL XX/XXX
B HADRIAN ??? ELITE
SERIES
RESTROOM PARTITION - FLOOR SUPPORTED
OVERHEAD BRACED STAINLESS STEEL 5WL TEXTURE...
A42 BOBRICK B-6806 GRAB BARS - 1 1/2" DIAMETER STAINLESS STEEL BARS WITH SNAP FLANGE/ REFER TO XX/XXX. PROVIDE...
A36 BOBRICK B-6806 GRAB BARS - 1 1/2" DIAMETER STAINLESS STEEL BARS
WITH SNAP FLANGE/ REFER TO XX/XXX
TYPE
MA...
MANUFACTUR
ER
MODEL # DESCRIPTION
RESTROOM ACCESSORIES SCHEDULE
1/4" = 1'-0"20NURSING ROOM ELEVATION
EAST
1/4" = 1'-0"24NURSING ROOM ELEVATION
NORTH
KEYNOTESLEGENDGENERAL NOTES
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
11. 12.
13. 14.
15. 16.
17. FOR WALL TYPES, REFER TO FLOOR PLANS.
SEE FINISH SCHEDULES AND SPECIFICATIONS ON SHEET 1-A900.
SEE RCP FOR CEILING FINISHES AND SEE DOOR SCHEDULE FOR DOOR FINISHES.
ALL INTERIOR WALL AND CEILING FINISH MATERIALS TO COMPLY WITH SECTION 803 - IN ACCORDANCE WITH ASTM E-84 NFPA 286 WITH ALL FINISHES CLASSIFIED AS CLASS "A".INTERIOR EXIT STAIRWAYS AND RAMPS AND EXIT PASSAGEWAYS ARE NOT TO EXCEED CLASS "B." CORRIDORS AND ENCLOSURE FOR EXIT ACCESS STAIRWAYS AND RAMPS ARE TO NOT TO EXCEED CLASS "C."
INTERIOR WALL AND CEILING FINISH MATERIAL CLASS PER 803.13 IS TO MEET FLAME SPREAD AND SMOKE DENSITY IN ACCORDANCE WITH CBC TABLE 803.1.2.
PREPARE SLAB AS REQUIRED BY MANUFACTURERS' RECOMMENDATION FOR EACH SPECIFIED FINISH.
ACCESS PANELS SHALL BE PAINTED TO MATCH ADJACENT WALL, WHERE OCCURS.
ALL GYPSUM BOARD WALLS AND SOFFITS TO BE PAINTED.
CONTINUE FLOORING UNDER ACCESSIBLE SINK CABINET AND EQUIPMENT NICHE.
PROVIDE LOW VOC PAINTS AND ADHESIVES THROUGHOUT.
PROVIDE 'FEATHER UP' TRANSITION AT ALL DOORS FOR SMOOTH TRANSITION.
PROVIDE THRESHOLDS AT ALL FLOORING TRANSITIONS.
MOISTURE TEST: PROVIDE MOISTURE TEST THROUGHOUT. VERIFY MOISTURE LEVELS WITHIN PRODUCT MANUFACTURERS ACCEPTABLE LEVELS, PER WARRANTY RESTRICTIONS.
PROVIDE CHUNTER AT WALL TILE EXPOSED EDGES SPECIFICATION: SCHLUTER SYSTEM, JOLLY BRUSHED FINISH, ANODIZED ALUMINUM.
FLOOR COVERING MATERIALS SHALL COMPLY WITH ASTM E 648, AND HAVE A SMOKE DENSITY RATING OF LESS THAN 450 PER ASTM E 84. CBC 804.4.1.
DO NOT PLACE UTILITY ITEMS SUCH AS THERMOSTATS, POWER OUTLETS, SWITCHES, AND CABINETS, FIRE EXTINGUISHERS, FIRESTROBES ON ACCENT AND GRAPHIC WALLS.
TILE APPLICATION: LAY TILE ACCORDING TO PATTERN INDICATED ON CONSTRUCTION DOCS. IF THERE IS A CONFLICT WITH THE MFGR'S RECOMMENDATIONS, THE MFGR'S RECOMMENDATIONS WILL GOVERN THE INSTALLATION METHOD. LARGE FORMAT TILES [ANY TILE WITH/ AN EDGE DIMENSION EQUAL OR GREATER THAN 15"] WILL HAVE A 30% OFFSET AS OPPOSED TO A 50% OFFSET. VERIFY TILE TO TILE JOINT RELATIONSHIP WITH/ MFGR TO AVOID "LIPPAGE". DO NOT INTERRUPT TILE PATTERN THROUGHOUT OPENINGS. .
#EQUIPMENT TAG, REFER TO SHEET A2.51
FINISH SYMBOL
FINISH CODE - REFER TO FINISH SCHEDULE ON A2.21.
ALIGN FINISHES
CASEWORK TAG, REFER TO 03/A9.31 FOR SECTIONS
WIDTH
#
30" 36"
42"
HEIGHT
DEPTH
WOOD INSTITUTE NUMBER
TEMPERED GLAZING SYMBOLT
?
RESTROOM ACCESSORY TAGX-X
EQUIPMENT TAG - REFER TO EQUIPMENT SCHEDULE ON AX.XXX-X
KEYNOTEX-X
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
ADE
EXHIBIT
SPACE
100
C
A7.11
16TYP.
A7.11
24TYP.
BD.9
OPEN TO BEYOND
OPEN TO BEYOND
OPEN TO BEYOND
05.17 26.06
26.06 23.06
28.01 28.04
22.0828.0205.13
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
INTERIOR
ELEVATIONS
A5.03
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/4" = 1'-0"02EXHIBIT HALL ELEVATION EAST
05.13 STAINLESS STEEL CANE DETECTION RAIL. REFER TO 20/G0.32.
05.17 STAIRS AND GUARD RAIL BEYOND
22.08 CHILLED HI-LO DRINKING FOUNTAIN WITH WATER BOTTLE FILLER, RECESSED MECHANICAL PUSH BAR ACTUATOR, SEE PLUMBING.
23.06 MECHANICAL DUCTWORK. REFER TO MECHANICAL DRAWINGS.
26.06 LIGHTING FIXTURE. REFER TO LIGHTING DRAWINGS.
28.01 FIRE ALARM ANNUNCIATOR. REFER TO ELECTRICAL AND FIRE ALARM DRAWINGS.
28.02 FIRE ALARM HORN. REFER TO ELECTRICAL DRAWINGS.
28.04 FIRE ALARM PULL. REFER TO ELECTRICAL DRAWINGS.
KEYNOTESLEGENDGENERAL NOTES
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
11. 12.
13. 14.
15. 16.
17. FOR WALL TYPES, REFER TO FLOOR PLANS.
SEE FINISH SCHEDULES AND SPECIFICATIONS ON SHEET 1-A900.
SEE RCP FOR CEILING FINISHES AND SEE DOOR SCHEDULE FOR DOOR FINISHES.
ALL INTERIOR WALL AND CEILING FINISH MATERIALS TO COMPLY WITH SECTION 803 - IN ACCORDANCE WITH ASTM E-84 NFPA 286 WITH ALL FINISHES CLASSIFIED AS CLASS "A".INTERIOR EXIT STAIRWAYS AND RAMPS AND EXIT PASSAGEWAYS ARE NOT TO EXCEED CLASS "B." CORRIDORS AND ENCLOSURE FOR EXIT ACCESS STAIRWAYS AND RAMPS ARE TO NOT TO EXCEED CLASS "C."
INTERIOR WALL AND CEILING FINISH MATERIAL CLASS PER 803.13 IS TO MEET FLAME SPREAD AND SMOKE DENSITY IN ACCORDANCE WITH CBC TABLE 803.1.2.
PREPARE SLAB AS REQUIRED BY MANUFACTURERS' RECOMMENDATION FOR EACH SPECIFIED FINISH.
ACCESS PANELS SHALL BE PAINTED TO MATCH ADJACENT WALL, WHERE OCCURS.
ALL GYPSUM BOARD WALLS AND SOFFITS TO BE PAINTED.
CONTINUE FLOORING UNDER ACCESSIBLE SINK CABINET AND EQUIPMENT NICHE.
PROVIDE LOW VOC PAINTS AND ADHESIVES THROUGHOUT.
PROVIDE 'FEATHER UP' TRANSITION AT ALL DOORS FOR SMOOTH TRANSITION.
PROVIDE THRESHOLDS AT ALL FLOORING TRANSITIONS.
MOISTURE TEST: PROVIDE MOISTURE TEST THROUGHOUT. VERIFY MOISTURE LEVELS WITHIN PRODUCT MANUFACTURERS ACCEPTABLE LEVELS, PER WARRANTY RESTRICTIONS.
PROVIDE CHUNTER AT WALL TILE EXPOSED EDGES SPECIFICATION: SCHLUTER SYSTEM, JOLLY BRUSHED FINISH, ANODIZED ALUMINUM.
FLOOR COVERING MATERIALS SHALL COMPLY WITH ASTM E 648, AND HAVE A SMOKE DENSITY RATING OF LESS THAN 450 PER ASTM E 84. CBC 804.4.1.
DO NOT PLACE UTILITY ITEMS SUCH AS THERMOSTATS, POWER OUTLETS, SWITCHES, AND CABINETS, FIRE EXTINGUISHERS, FIRESTROBES ON ACCENT AND GRAPHIC WALLS.
TILE APPLICATION: LAY TILE ACCORDING TO PATTERN INDICATED ON CONSTRUCTION DOCS. IF THERE IS A CONFLICT WITH THE MFGR'S RECOMMENDATIONS, THE MFGR'S RECOMMENDATIONS WILL GOVERN THE INSTALLATION METHOD. LARGE FORMAT TILES [ANY TILE WITH/ AN EDGE DIMENSION EQUAL OR GREATER THAN 15"] WILL HAVE A 30% OFFSET AS OPPOSED TO A 50% OFFSET. VERIFY TILE TO TILE JOINT RELATIONSHIP WITH/ MFGR TO AVOID "LIPPAGE". DO NOT INTERRUPT TILE PATTERN THROUGHOUT OPENINGS. .
#EQUIPMENT TAG, REFER TO SHEET A2.51
FINISH SYMBOL
FINISH CODE - REFER TO FINISH SCHEDULE ON A2.21.
ALIGN FINISHES
CASEWORK TAG, REFER TO 03/A9.31 FOR SECTIONS
WIDTH
#
30" 36"
42"
HEIGHT
DEPTH
WOOD INSTITUTE NUMBER
TEMPERED GLAZING SYMBOLT
?
RESTROOM ACCESSORY TAGX-X
EQUIPMENT TAG - REFER TO EQUIPMENT SCHEDULE ON AX.XXX-X
KEYNOTEX-X
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
567 8 94.85.25.8
MATCH LINE6190 SF
OPEN
EXHIBIT
SPACE
200
8950 SF
EXHIBIT
SPACE
100
28.02 28.0428.02
13.07 23.06
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
INTERIOR
ELEVATIONS
A5.04
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/4" = 1'-0"02EXHIBIT HALL ELEVATION NORTH - B
13.07 EXPOSED STRUCTURAL FRAMING BY PEMB MANUFACTURER
23.06 MECHANICAL DUCTWORK. REFER TO MECHANICAL DRAWINGS.
28.02 FIRE ALARM HORN. REFER TO ELECTRICAL DRAWINGS.
28.04 FIRE ALARM PULL. REFER TO ELECTRICAL DRAWINGS.
KEYNOTESLEGENDGENERAL NOTES
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
11. 12.
13. 14.
15. 16.
17. FOR WALL TYPES, REFER TO FLOOR PLANS.
SEE FINISH SCHEDULES AND SPECIFICATIONS ON SHEET 1-A900.
SEE RCP FOR CEILING FINISHES AND SEE DOOR SCHEDULE FOR DOOR FINISHES.
ALL INTERIOR WALL AND CEILING FINISH MATERIALS TO COMPLY WITH SECTION 803 - IN ACCORDANCE WITH ASTM E-84 NFPA 286 WITH ALL FINISHES CLASSIFIED AS CLASS "A".INTERIOR EXIT STAIRWAYS AND RAMPS AND EXIT PASSAGEWAYS ARE NOT TO EXCEED CLASS "B." CORRIDORS AND ENCLOSURE FOR EXIT ACCESS STAIRWAYS AND RAMPS ARE TO NOT TO EXCEED CLASS "C."
INTERIOR WALL AND CEILING FINISH MATERIAL CLASS PER 803.13 IS TO MEET FLAME SPREAD AND SMOKE DENSITY IN ACCORDANCE WITH CBC TABLE 803.1.2.
PREPARE SLAB AS REQUIRED BY MANUFACTURERS' RECOMMENDATION FOR EACH SPECIFIED FINISH.
ACCESS PANELS SHALL BE PAINTED TO MATCH ADJACENT WALL, WHERE OCCURS.
ALL GYPSUM BOARD WALLS AND SOFFITS TO BE PAINTED.
CONTINUE FLOORING UNDER ACCESSIBLE SINK CABINET AND EQUIPMENT NICHE.
PROVIDE LOW VOC PAINTS AND ADHESIVES THROUGHOUT.
PROVIDE 'FEATHER UP' TRANSITION AT ALL DOORS FOR SMOOTH TRANSITION.
PROVIDE THRESHOLDS AT ALL FLOORING TRANSITIONS.
MOISTURE TEST: PROVIDE MOISTURE TEST THROUGHOUT. VERIFY MOISTURE LEVELS WITHIN PRODUCT MANUFACTURERS ACCEPTABLE LEVELS, PER WARRANTY RESTRICTIONS.
PROVIDE CHUNTER AT WALL TILE EXPOSED EDGES SPECIFICATION: SCHLUTER SYSTEM, JOLLY BRUSHED FINISH, ANODIZED ALUMINUM.
FLOOR COVERING MATERIALS SHALL COMPLY WITH ASTM E 648, AND HAVE A SMOKE DENSITY RATING OF LESS THAN 450 PER ASTM E 84. CBC 804.4.1.
DO NOT PLACE UTILITY ITEMS SUCH AS THERMOSTATS, POWER OUTLETS, SWITCHES, AND CABINETS, FIRE EXTINGUISHERS, FIRESTROBES ON ACCENT AND GRAPHIC WALLS.
TILE APPLICATION: LAY TILE ACCORDING TO PATTERN INDICATED ON CONSTRUCTION DOCS. IF THERE IS A CONFLICT WITH THE MFGR'S RECOMMENDATIONS, THE MFGR'S RECOMMENDATIONS WILL GOVERN THE INSTALLATION METHOD. LARGE FORMAT TILES [ANY TILE WITH/ AN EDGE DIMENSION EQUAL OR GREATER THAN 15"] WILL HAVE A 30% OFFSET AS OPPOSED TO A 50% OFFSET. VERIFY TILE TO TILE JOINT RELATIONSHIP WITH/ MFGR TO AVOID "LIPPAGE". DO NOT INTERRUPT TILE PATTERN THROUGHOUT OPENINGS. .
#EQUIPMENT TAG, REFER TO SHEET A2.51
FINISH SYMBOL
FINISH CODE - REFER TO FINISH SCHEDULE ON A2.21.
ALIGN FINISHES
CASEWORK TAG, REFER TO 03/A9.31 FOR SECTIONS
WIDTH
#
30" 36"
42"
HEIGHT
DEPTH
WOOD INSTITUTE NUMBER
TEMPERED GLAZING SYMBOLT
?
RESTROOM ACCESSORY TAGX-X
EQUIPMENT TAG - REFER TO EQUIPMENT SCHEDULE ON AX.XXX-X
KEYNOTEX-X
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
23 4 54.2 4.8 5.2
MATCH LINE8950 SF
EXHIBIT
SPACE
100
28.0213.07 08.05
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
INTERIOR
ELEVATIONS
A5.05
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/4" = 1'-0"02EXHIBIT HALL ELEVATION NORTH - A
08.05 DOOR. REFER TO DOOR SCHEDULE.
13.07 EXPOSED STRUCTURAL FRAMING BY PEMB MANUFACTURER
28.02 FIRE ALARM HORN. REFER TO ELECTRICAL DRAWINGS.
KEYNOTESLEGENDGENERAL NOTES
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
11. 12.
13. 14.
15. 16.
17. FOR WALL TYPES, REFER TO FLOOR PLANS.
SEE FINISH SCHEDULES AND SPECIFICATIONS ON SHEET 1-A900.
SEE RCP FOR CEILING FINISHES AND SEE DOOR SCHEDULE FOR DOOR FINISHES.
ALL INTERIOR WALL AND CEILING FINISH MATERIALS TO COMPLY WITH SECTION 803 - IN ACCORDANCE WITH ASTM E-84 NFPA 286 WITH ALL FINISHES CLASSIFIED AS CLASS "A".INTERIOR EXIT STAIRWAYS AND RAMPS AND EXIT PASSAGEWAYS ARE NOT TO EXCEED CLASS "B." CORRIDORS AND ENCLOSURE FOR EXIT ACCESS STAIRWAYS AND RAMPS ARE TO NOT TO EXCEED CLASS "C."
INTERIOR WALL AND CEILING FINISH MATERIAL CLASS PER 803.13 IS TO MEET FLAME SPREAD AND SMOKE DENSITY IN ACCORDANCE WITH CBC TABLE 803.1.2.
PREPARE SLAB AS REQUIRED BY MANUFACTURERS' RECOMMENDATION FOR EACH SPECIFIED FINISH.
ACCESS PANELS SHALL BE PAINTED TO MATCH ADJACENT WALL, WHERE OCCURS.
ALL GYPSUM BOARD WALLS AND SOFFITS TO BE PAINTED.
CONTINUE FLOORING UNDER ACCESSIBLE SINK CABINET AND EQUIPMENT NICHE.
PROVIDE LOW VOC PAINTS AND ADHESIVES THROUGHOUT.
PROVIDE 'FEATHER UP' TRANSITION AT ALL DOORS FOR SMOOTH TRANSITION.
PROVIDE THRESHOLDS AT ALL FLOORING TRANSITIONS.
MOISTURE TEST: PROVIDE MOISTURE TEST THROUGHOUT. VERIFY MOISTURE LEVELS WITHIN PRODUCT MANUFACTURERS ACCEPTABLE LEVELS, PER WARRANTY RESTRICTIONS.
PROVIDE CHUNTER AT WALL TILE EXPOSED EDGES SPECIFICATION: SCHLUTER SYSTEM, JOLLY BRUSHED FINISH, ANODIZED ALUMINUM.
FLOOR COVERING MATERIALS SHALL COMPLY WITH ASTM E 648, AND HAVE A SMOKE DENSITY RATING OF LESS THAN 450 PER ASTM E 84. CBC 804.4.1.
DO NOT PLACE UTILITY ITEMS SUCH AS THERMOSTATS, POWER OUTLETS, SWITCHES, AND CABINETS, FIRE EXTINGUISHERS, FIRESTROBES ON ACCENT AND GRAPHIC WALLS.
TILE APPLICATION: LAY TILE ACCORDING TO PATTERN INDICATED ON CONSTRUCTION DOCS. IF THERE IS A CONFLICT WITH THE MFGR'S RECOMMENDATIONS, THE MFGR'S RECOMMENDATIONS WILL GOVERN THE INSTALLATION METHOD. LARGE FORMAT TILES [ANY TILE WITH/ AN EDGE DIMENSION EQUAL OR GREATER THAN 15"] WILL HAVE A 30% OFFSET AS OPPOSED TO A 50% OFFSET. VERIFY TILE TO TILE JOINT RELATIONSHIP WITH/ MFGR TO AVOID "LIPPAGE". DO NOT INTERRUPT TILE PATTERN THROUGHOUT OPENINGS. .
#EQUIPMENT TAG, REFER TO SHEET A2.51
FINISH SYMBOL
FINISH CODE - REFER TO FINISH SCHEDULE ON A2.21.
ALIGN FINISHES
CASEWORK TAG, REFER TO 03/A9.31 FOR SECTIONS
WIDTH
#
30" 36"
42"
HEIGHT
DEPTH
WOOD INSTITUTE NUMBER
TEMPERED GLAZING SYMBOLT
?
RESTROOM ACCESSORY TAGX-X
EQUIPMENT TAG - REFER TO EQUIPMENT SCHEDULE ON AX.XXX-X
KEYNOTEX-X
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
BB EE FFAACCDD
28.02 26.1426.06
13.04 13.07
08.01 13.03
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
BB.1
28.02 13.07
23.06 NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
INTERIOR
ELEVATIONS
A5.06
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/4" = 1'-0"02EXHIBIT HALL ELEVATION NORTH WEST 1/4" = 1'-0"13EXHIBIT HALL ELEVATION WEST
08.01 GLASS HANGER DOOR SYSTEM. REFER TO DOOR SCHEDULE.
13.03 STEEL BEAM WITH HIGH PERFORMANCE FINISH BY PEMB MANUFACTURER
13.04 STEEL COLUMN BY METAL BUILDING MANUFACTURER
13.07 EXPOSED STRUCTURAL FRAMING BY PEMB MANUFACTURER
23.06 MECHANICAL DUCTWORK. REFER TO MECHANICAL DRAWINGS.
26.06 LIGHTING FIXTURE. REFER TO LIGHTING DRAWINGS.
26.14 PROJECTOR SCREEN JUNCTION BOX. REFER TO ELECTRICAL DRAWINGS.
28.02 FIRE ALARM HORN. REFER TO ELECTRICAL DRAWINGS.
KEYNOTESLEGENDGENERAL NOTES
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
11. 12.
13. 14.
15. 16.
17. FOR WALL TYPES, REFER TO FLOOR PLANS.
SEE FINISH SCHEDULES AND SPECIFICATIONS ON SHEET 1-A900.
SEE RCP FOR CEILING FINISHES AND SEE DOOR SCHEDULE FOR DOOR FINISHES.
ALL INTERIOR WALL AND CEILING FINISH MATERIALS TO COMPLY WITH SECTION 803 - IN ACCORDANCE WITH ASTM E-84 NFPA 286 WITH ALL FINISHES CLASSIFIED AS CLASS "A".INTERIOR EXIT STAIRWAYS AND RAMPS AND EXIT PASSAGEWAYS ARE NOT TO EXCEED CLASS "B." CORRIDORS AND ENCLOSURE FOR EXIT ACCESS STAIRWAYS AND RAMPS ARE TO NOT TO EXCEED CLASS "C."
INTERIOR WALL AND CEILING FINISH MATERIAL CLASS PER 803.13 IS TO MEET FLAME SPREAD AND SMOKE DENSITY IN ACCORDANCE WITH CBC TABLE 803.1.2.
PREPARE SLAB AS REQUIRED BY MANUFACTURERS' RECOMMENDATION FOR EACH SPECIFIED FINISH.
ACCESS PANELS SHALL BE PAINTED TO MATCH ADJACENT WALL, WHERE OCCURS.
ALL GYPSUM BOARD WALLS AND SOFFITS TO BE PAINTED.
CONTINUE FLOORING UNDER ACCESSIBLE SINK CABINET AND EQUIPMENT NICHE.
PROVIDE LOW VOC PAINTS AND ADHESIVES THROUGHOUT.
PROVIDE 'FEATHER UP' TRANSITION AT ALL DOORS FOR SMOOTH TRANSITION.
PROVIDE THRESHOLDS AT ALL FLOORING TRANSITIONS.
MOISTURE TEST: PROVIDE MOISTURE TEST THROUGHOUT. VERIFY MOISTURE LEVELS WITHIN PRODUCT MANUFACTURERS ACCEPTABLE LEVELS, PER WARRANTY RESTRICTIONS.
PROVIDE CHUNTER AT WALL TILE EXPOSED EDGES SPECIFICATION: SCHLUTER SYSTEM, JOLLY BRUSHED FINISH, ANODIZED ALUMINUM.
FLOOR COVERING MATERIALS SHALL COMPLY WITH ASTM E 648, AND HAVE A SMOKE DENSITY RATING OF LESS THAN 450 PER ASTM E 84. CBC 804.4.1.
DO NOT PLACE UTILITY ITEMS SUCH AS THERMOSTATS, POWER OUTLETS, SWITCHES, AND CABINETS, FIRE EXTINGUISHERS, FIRESTROBES ON ACCENT AND GRAPHIC WALLS.
TILE APPLICATION: LAY TILE ACCORDING TO PATTERN INDICATED ON CONSTRUCTION DOCS. IF THERE IS A CONFLICT WITH THE MFGR'S RECOMMENDATIONS, THE MFGR'S RECOMMENDATIONS WILL GOVERN THE INSTALLATION METHOD. LARGE FORMAT TILES [ANY TILE WITH/ AN EDGE DIMENSION EQUAL OR GREATER THAN 15"] WILL HAVE A 30% OFFSET AS OPPOSED TO A 50% OFFSET. VERIFY TILE TO TILE JOINT RELATIONSHIP WITH/ MFGR TO AVOID "LIPPAGE". DO NOT INTERRUPT TILE PATTERN THROUGHOUT OPENINGS. .
#EQUIPMENT TAG, REFER TO SHEET A2.51
FINISH SYMBOL
FINISH CODE - REFER TO FINISH SCHEDULE ON A2.21.
ALIGN FINISHES
CASEWORK TAG, REFER TO 03/A9.31 FOR SECTIONS
WIDTH
#
30" 36"
42"
HEIGHT
DEPTH
WOOD INSTITUTE NUMBER
TEMPERED GLAZING SYMBOLT
?
RESTROOM ACCESSORY TAGX-X
EQUIPMENT TAG - REFER TO EQUIPMENT SCHEDULE ON AX.XXX-X
KEYNOTEX-X
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
2345
A7.11
16 A7.11
24 A7.11
20 4.24.85.2
MATCH LINEA7.11
03 A7.11
04 3'-1"
2'-9"
TYP.26.06
TYP.05.13
A7.11
17 26.06TYP.13.07
TYP.13.02
23.06 28.0205.01
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
INTERIOR
ELEVATIONS
A5.07
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/4" = 1'-0"1EXHIBIT HALL ELEVATION SOUTH - B Copy 1
05.01 TUBE STEEL COLUMN WITH HIGH PERFORMANCE FINISH. REFER TO STRUCTURAL DRAWINGS.
05.13 STAINLESS STEEL CANE DETECTION RAIL. REFER TO 20/G0.32.
13.02 STEEL BRACE FRAME WITH HIGH PERFORMANCE EXTERIOR FINISH BY PEMB
MANUFACTURER
13.07 EXPOSED STRUCTURAL FRAMING BY PEMB MANUFACTURER
23.06 MECHANICAL DUCTWORK. REFER TO MECHANICAL DRAWINGS.
26.06 LIGHTING FIXTURE. REFER TO LIGHTING DRAWINGS.
28.02 FIRE ALARM HORN. REFER TO ELECTRICAL DRAWINGS.
KEYNOTESLEGENDGENERAL NOTES
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
11. 12.
13. 14.
15. 16.
17. FOR WALL TYPES, REFER TO FLOOR PLANS.
SEE FINISH SCHEDULES AND SPECIFICATIONS ON SHEET 1-A900.
SEE RCP FOR CEILING FINISHES AND SEE DOOR SCHEDULE FOR DOOR FINISHES.
ALL INTERIOR WALL AND CEILING FINISH MATERIALS TO COMPLY WITH SECTION 803 - IN ACCORDANCE WITH ASTM E-84 NFPA 286 WITH ALL FINISHES CLASSIFIED AS CLASS "A".INTERIOR EXIT STAIRWAYS AND RAMPS AND EXIT PASSAGEWAYS ARE NOT TO EXCEED CLASS "B." CORRIDORS AND ENCLOSURE FOR EXIT ACCESS STAIRWAYS AND RAMPS ARE TO NOT TO EXCEED CLASS "C."
INTERIOR WALL AND CEILING FINISH MATERIAL CLASS PER 803.13 IS TO MEET FLAME SPREAD AND SMOKE DENSITY IN ACCORDANCE WITH CBC TABLE 803.1.2.
PREPARE SLAB AS REQUIRED BY MANUFACTURERS' RECOMMENDATION FOR EACH SPECIFIED FINISH.
ACCESS PANELS SHALL BE PAINTED TO MATCH ADJACENT WALL, WHERE OCCURS.
ALL GYPSUM BOARD WALLS AND SOFFITS TO BE PAINTED.
CONTINUE FLOORING UNDER ACCESSIBLE SINK CABINET AND EQUIPMENT NICHE.
PROVIDE LOW VOC PAINTS AND ADHESIVES THROUGHOUT.
PROVIDE 'FEATHER UP' TRANSITION AT ALL DOORS FOR SMOOTH TRANSITION.
PROVIDE THRESHOLDS AT ALL FLOORING TRANSITIONS.
MOISTURE TEST: PROVIDE MOISTURE TEST THROUGHOUT. VERIFY MOISTURE LEVELS WITHIN PRODUCT MANUFACTURERS ACCEPTABLE LEVELS, PER WARRANTY RESTRICTIONS.
PROVIDE CHUNTER AT WALL TILE EXPOSED EDGES SPECIFICATION: SCHLUTER SYSTEM, JOLLY BRUSHED FINISH, ANODIZED ALUMINUM.
FLOOR COVERING MATERIALS SHALL COMPLY WITH ASTM E 648, AND HAVE A SMOKE DENSITY RATING OF LESS THAN 450 PER ASTM E 84. CBC 804.4.1.
DO NOT PLACE UTILITY ITEMS SUCH AS THERMOSTATS, POWER OUTLETS, SWITCHES, AND CABINETS, FIRE EXTINGUISHERS, FIRESTROBES ON ACCENT AND GRAPHIC WALLS.
TILE APPLICATION: LAY TILE ACCORDING TO PATTERN INDICATED ON CONSTRUCTION DOCS. IF THERE IS A CONFLICT WITH THE MFGR'S RECOMMENDATIONS, THE MFGR'S RECOMMENDATIONS WILL GOVERN THE INSTALLATION METHOD. LARGE FORMAT TILES [ANY TILE WITH/ AN EDGE DIMENSION EQUAL OR GREATER THAN 15"] WILL HAVE A 30% OFFSET AS OPPOSED TO A 50% OFFSET. VERIFY TILE TO TILE JOINT RELATIONSHIP WITH/ MFGR TO AVOID "LIPPAGE". DO NOT INTERRUPT TILE PATTERN THROUGHOUT OPENINGS. .
#EQUIPMENT TAG, REFER TO SHEET A2.51
FINISH SYMBOL
FINISH CODE - REFER TO FINISH SCHEDULE ON A2.21.
ALIGN FINISHES
CASEWORK TAG, REFER TO 03/A9.31 FOR SECTIONS
WIDTH
#
30" 36"
42"
HEIGHT
DEPTH
WOOD INSTITUTE NUMBER
TEMPERED GLAZING SYMBOLT
?
RESTROOM ACCESSORY TAGX-X
EQUIPMENT TAG - REFER TO EQUIPMENT SCHEDULE ON AX.XXX-X
KEYNOTEX-X
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
56789
MATCH LINEOPEN
EXHIBIT
SPACE
200
EXHIBIT
SPACE
100
26.08 A9.21
09 A7.11
20 TYP.
4.85.25.8 36'-0"TYP.26.06 TYP.13.02
26.06 28.02
13.02 13.02 05.01
23.06 23.02
22.0913.0713.05
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
INTERIOR
ELEVATIONS
A5.08
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/4" = 1'-0"02EXHIBIT HALL ELEVATION SOUTH - A
05.01 TUBE STEEL COLUMN WITH HIGH PERFORMANCE FINISH. REFER TO STRUCTURAL DRAWINGS.
13.02 STEEL BRACE FRAME WITH HIGH PERFORMANCE EXTERIOR FINISH BY PEMB
MANUFACTURER
13.05 PRIMARY STRUCTURAL STEEL FRAME BY METAL BUILDING MANUFACTURER
WITH HIGH PERFORMANCE FINISH
13.07 EXPOSED STRUCTURAL FRAMING BY PEMB MANUFACTURER
22.09 PLUMBING PIPES. SEE PLUMBING DRAWINGS.
23.02 MECHANICAL LOUVER. SEE MECHANICAL DRAWINGS.
23.06 MECHANICAL DUCTWORK. REFER TO MECHANICAL DRAWINGS.
26.06 LIGHTING FIXTURE. REFER TO LIGHTING DRAWINGS.
26.08 PANELBOARD. REFER TO ELECTRICAL DRAWINGS.
28.02 FIRE ALARM HORN. REFER TO ELECTRICAL DRAWINGS.
PL-1
PL-109.0609.06
101
18 24
33102
35 24
33 434
36 24
96 312
36 13
30 ALIGNALIGNALIGN
SS-1
15 A9.31
06 A9.31
03 A9.31
7'-0"12.01
2'-8"2'-10"7 EQUAL
WP-1
PL-1SS-1
PL-1
09.0609.06
102
36 24
33 434
36 24
96 312
36 13
30 05.0112.01
ALIGNALIGNALIGN
15 A9.31
06 A9.31
7'-0"2'-10" 2'-8"
7 EQUAL
WP-1
05.01 05.01
KEYNOTESLEGENDGENERAL NOTES
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
11. 12.
13. 14.
15. 16.
17. FOR WALL TYPES, REFER TO FLOOR PLANS.
SEE FINISH SCHEDULES AND SPECIFICATIONS ON SHEET 1-A900.
SEE RCP FOR CEILING FINISHES AND SEE DOOR SCHEDULE FOR DOOR FINISHES.
ALL INTERIOR WALL AND CEILING FINISH MATERIALS TO COMPLY WITH SECTION 803 - IN ACCORDANCE WITH ASTM E-84 NFPA 286 WITH ALL FINISHES CLASSIFIED AS CLASS "A".INTERIOR EXIT STAIRWAYS AND RAMPS AND EXIT PASSAGEWAYS ARE NOT TO EXCEED CLASS "B." CORRIDORS AND ENCLOSURE FOR EXIT ACCESS STAIRWAYS AND RAMPS ARE TO NOT TO EXCEED CLASS "C."
INTERIOR WALL AND CEILING FINISH MATERIAL CLASS PER 803.13 IS TO MEET FLAME SPREAD AND SMOKE DENSITY IN ACCORDANCE WITH CBC TABLE 803.1.2.
PREPARE SLAB AS REQUIRED BY MANUFACTURERS' RECOMMENDATION FOR EACH SPECIFIED FINISH.
ACCESS PANELS SHALL BE PAINTED TO MATCH ADJACENT WALL, WHERE OCCURS.
ALL GYPSUM BOARD WALLS AND SOFFITS TO BE PAINTED.
CONTINUE FLOORING UNDER ACCESSIBLE SINK CABINET AND EQUIPMENT NICHE.
PROVIDE LOW VOC PAINTS AND ADHESIVES THROUGHOUT.
PROVIDE 'FEATHER UP' TRANSITION AT ALL DOORS FOR SMOOTH TRANSITION.
PROVIDE THRESHOLDS AT ALL FLOORING TRANSITIONS.
MOISTURE TEST: PROVIDE MOISTURE TEST THROUGHOUT. VERIFY MOISTURE LEVELS WITHIN PRODUCT MANUFACTURERS ACCEPTABLE LEVELS, PER WARRANTY RESTRICTIONS.
PROVIDE CHUNTER AT WALL TILE EXPOSED EDGES SPECIFICATION: SCHLUTER SYSTEM, JOLLY BRUSHED FINISH, ANODIZED ALUMINUM.
FLOOR COVERING MATERIALS SHALL COMPLY WITH ASTM E 648, AND HAVE A SMOKE DENSITY RATING OF LESS THAN 450 PER ASTM E 84. CBC 804.4.1.
DO NOT PLACE UTILITY ITEMS SUCH AS THERMOSTATS, POWER OUTLETS, SWITCHES, AND CABINETS, FIRE EXTINGUISHERS, FIRESTROBES ON ACCENT AND GRAPHIC WALLS.
TILE APPLICATION: LAY TILE ACCORDING TO PATTERN INDICATED ON CONSTRUCTION DOCS. IF THERE IS A CONFLICT WITH THE MFGR'S RECOMMENDATIONS, THE MFGR'S RECOMMENDATIONS WILL GOVERN THE INSTALLATION METHOD. LARGE FORMAT TILES [ANY TILE WITH/ AN EDGE DIMENSION EQUAL OR GREATER THAN 15"] WILL HAVE A 30% OFFSET AS OPPOSED TO A 50% OFFSET. VERIFY TILE TO TILE JOINT RELATIONSHIP WITH/ MFGR TO AVOID "LIPPAGE". DO NOT INTERRUPT TILE PATTERN THROUGHOUT OPENINGS. .
#EQUIPMENT TAG, REFER TO SHEET A2.51
FINISH SYMBOL
FINISH CODE - REFER TO FINISH SCHEDULE ON A2.21.
ALIGN FINISHES
CASEWORK TAG, REFER TO 03/A9.31 FOR SECTIONS
WIDTH
#
30" 36"
42"
HEIGHT
DEPTH
WOOD INSTITUTE NUMBER
TEMPERED GLAZING SYMBOLT
?
RESTROOM ACCESSORY TAGX-X
EQUIPMENT TAG - REFER TO EQUIPMENT SCHEDULE ON AX.XXX-X
KEYNOTEX-X
PL-1
SS-1
OPEN
1'-9" 1'-9"2'-2"
PL-1
222
34 24
33 7'-4 1/4"2'-10"
01 A9.32
2'-10" 2'-2"
222
34 24
33 13
A9.31
03 A9.32
PL-1SS-1102
35 24
33 2'-10"ALIGN09.0609.06 P-2 PL-1SS-1 102
34 24
33ALIGN 2'-10"09.0609.06 P-2
1/4" = 1'-0"10STEM 1 NORTH 1/4" = 1'-0"14STEM 1 WEST 1/4" = 1'-0"02STEM 1 EAST 1/4" = 1'-0"18STEM 1 SOUTH 1/4" = 1'-0"15STEM 2 WEST 1/4" = 1'-0"11STEM 2 NORTH 1/4" = 1'-0"03STEM 2 EAST 1/4" = 1'-0"19STEM 2 SOUTH 1/4" = 1'-0"20STORAGE ROOM ELEVATION WEST
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
INTERIOR
ELEVATIONS
A5.09
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/4" = 1'-0"12STAFF ROOM NORTH 1/4" = 1'-0"04STAFF ROOM
05.01 TUBE STEEL COLUMN WITH HIGH PERFORMANCE FINISH. REFER TO STRUCTURAL DRAWINGS.
09.06 CUSTOM FILLER PANEL WITH TOE KICK TO MATCH CASEWORK.
12.01 FLATSCREEN TELEVISION FURNISHED BY OWNER. CONTRACTOR TO PROVIDE SOLID BLOCKING WITHIN WALL.
ABBREVIATIONS
CORE
GL = GLASS (T = TEMPERED)
SC = SOLID CORE
HC = HOLLOW CORE
HCI = HOLLOW CORE INSULATED
HM = HOLLOW METAL
INSUL = INSULATED COILING SLAT
CLOSER
OH = OVERHEAD
FLR = FLOOR
C-OH = CONCEALED OVERHEAD
HO = HOLD OPEN
DOOR PANEL FINISH
PT = PAINT (SEMI-GLOSS)
FF = FACTORY FINISH
PL = PLASTIC LAMINATE
ST = STAIN
FFC = FACTORY FINISH COATED (WHITE)
DOOR PANEL MATERIAL
AL = ALUMINUM
WD = WOOD
HM = HOLLOW METAL
STL = STEEL
DOOR FRAME FINISH
PT = PAINT
FF = FACTORY FINISH
CA = CLEAR ANODIZED
GLASS FINISH
FM = FILM ON DOOR & SIDELIGHT GLAZING
DOOR FRAME MATERIAL
AL = ALUMINUM (FRAMED)
HM = HOLLOW METAL
HMEE = HOLLOW METAL ENERGY-EFFICIENT
KD = KNOCK DOWN
STL = STEEL
REMARKS
BG = BULLET-RESISTANT GLASS
CR = CARD READER
FM = FILM ON DOOR &/OR SIDELIGHT GLAZING
HO = HOLD OPEN
KP = KICKPLATE
OH = OVERHEAD CLOSER
OI = OCCUPANCY INDICATOR
PA = POWER ASSIST DOOR OPERATOR
PH = PANIC HARDWARE
UC = 1" UNDERCUT
WF = WALL FRAMING ADJACENT DOOR PER 22/A9.10
ADB = AUTOMATIC DOOR BOTTOM PER 19/A9.10. AT
CARPET FINISH, TRANSITION FLOORING PER
TRANSITION A1 ON 01/A9.50
ALTERNATE 3
LFL = LOUVER WITH FUSIBLE LINK TO MATCH DOOR RATING
DOOR NOTES
1. 2.
3. 4.
5. 6.
7. 8.
9. 10.
11. 12.
THE OPENING SCHEDULE DEFINES THE ELEMENTS OF EACH DOOR AND WINDOW OPENING IN THE PROJECT.
MATERIALS, FINISHES AND INSTALLATION OF PRODUCTS REFERENCED IN THE OPENING SCHEDULE SHALL BE IN ACCORDANCE WITH REQUIREMENTS SPECIFIED IN THE RESPECTIVE PRODUCT SECTIONS.
REFER TO PARTITION TYPES AS INDICATED ON DRAWINGS TO DETERMINE FRAME DEPTH.
ELECTRIFIED HARDWARE: COORDINATE ALL ELECTRICAL REQUIREMENTS WITH DIVISIONS 26 AND 27.
IF THE OPENING CONTAINS A DOOR AND NO SIDELIGHT, THE RATING OF THE FRAME SHALL MATCH THE RATING OF THE DOOR. IF THE OPENING CONTAINS A DOOR AND A SIDELIGHT, OR IF THE OPENING CONTAINS A WINDOW, THE RATING OF THE FRAME SHALL MATCH THE RATING OF THE GLAZING.
THE AREA OF GLAZING IN FIRE DOORS IN FIRE BARRIERS AND FIRE WALLS ARE LIMITED TO 100 SQUARE INCHES IN DOOR ASSEMBLY RATINGS 90 MIN OR LESS. 2022 CBC 716.1.2 & TABLE 716.1(1) & 716.1(2)
FIRE-RATED DOOR FRAMES SHALL BE INSTALLED STRICTLY IN ACCORDANCE WITH MANUFACTURER'S PRINTED INSTRUCTIONS. MANUFACTURER'S PRINTED INSTRUCTIONS SHALL BE MADE AVAILABLE TO THE INSPECTION AUTHORITY.
LABELS FOR FIRE DOORS USED TO PROTECT OPENINGS INTO EXIT ENCLOSURES SHALL INDICATE THAT THE TEMPERATURE RISE ON THE UNEXPOSED SURFACE SHALL BE TESTED IN ACCORDANCE WITH NFPA 252, UL 10B OR UL 10C. 2022 CBC 716.2 IDENTIFICATION OF FIRE DOORS, FIRE WINDOWS AND FIRE DAMPERS. FIRE DOORS, FIRE WINDOWS AND FIRE DAMPERS
SHALL HAVE AN APPROVAL LABEL OR LISTING MARK, INDICATING THE FIRE-PROTECTION RATING, WHICH IS PERMANENTLY AFFIXED AT THE FACTORY WHERE FABRICATION AND ASSEMBLY ARE DONE. PERIODIC INSPECTIONS SHALL BE MADE BY AN APPROVED INSPECTION AGENCY DURING FABRICATION AND ASSEMBLY. 2022 CBC 716.2.9 & NFPA 80.
ALL DOOR UNDERCUTS FOR VARYING CARPET THICKNESS RUBBER FLOORING ETC. SHALL BE VERIFIED AND PROPERLY COORDINATED. UNDERCUTS AT RATED DOORS TO COMPLY WITH NFPA 80, SECT. 4.8.4.1.
TYPICAL DOOR BEVEL TO BE 1/8" IN 2" U.N.O. BY HARDWARE TEMPLATE REQUIRMENTS.
ADJUST DOOR FRAME OPENING SIZES AS NECESSARY TO REFLECT VARIATIONS IN THE STRUCTURAL SLAB AND VARYING THICKNESSES OF THE FLOOR FINISHES.
13. 14.
15. 16.
17. 18.
19. 20.
21. EXIT DOORS SHALL BE OPENABLE FROM THE INSIDE WITHOUT USE OF A KEY OR ANY SPECIAL KNOWLEDGE OR EFFORT.
MAXIMUM EFFORT TO OPERATE DOORS SHALL NOT EXCEED 5 POUNDS FOR BOTH INTERIOR AND EXTERIOR DOORS. FIRE
RATED DOORS MAY HAVE THE OPERATING FORCE INCREASED BY THE AUTHORITY HAVING JURISDICTION, BUT NOT TO EXCEED 15 POUNDS.
GLAZING TYPE IN GLASS DOORS TO MATCH ADJACENT SIDE LITES AS INDICATED IN WINDOW SCHEDULE.
COORDINATE DOOR TYPES & SCHEDULE WITH WINDOW SCHEDULE.
HOLLOW METAL FRAME ANCHORING PER 01/A8.51.
FOR TYPICAL ACCESSIBLE CLEARANCES AT DOOR REFERENCE 05, 08, & 13/G0.32 EXCEPT AS SPECIFICALLY PERMITTED BY CBC 1008.1.9, EGRESS DOORS SHALL BE READILY OPERABLE FROM THE EGRESS SIDE WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE. (CBC 1010.2) DOORS SERVING ROOMS OR SPACES USED FOR ASSEMBLY PURPOSES WITH AN OCCUPANT LOAD OF 50 OR MORE SHALL NOT BE PROVIDED WITH A LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE INSTALLED IN ACCORDANCE WITH CBC 1010.2.9 GARAGE DOORS AND ROLLING DOORS SHALL BE TESTED IN ACCORDANCE WITH EITHER ASTM E330 OR ANSI/DASMA 108, AND SHALL MEET THE PASS/FAIL CRITERIA OF ANSI/DASMA 108. GARAGE DOORS AND ROLLING DOORS SHALL BE LABELED
WITH A PERMANENT LABEL IDENTIFYING THE DOOR MANUFACTURER, THE DOOR MODEL/SERIES NUMBER, THE POSITIVE
AND NEGATIVE DESIGN WIND PRESSURE RATING, THE INSTALLATION INSTRUCTION DRAWING REFERENCE NUMBER, AND THE APPLICABLE TEST STANDARD. (1709.5.2.1 GARAGE DOORS AND ROLLING DOORS).
AUTOMATIC GARAGE DOOR OPENERS SHALL BE LISTED AND LABELED IN ACCORDANCE WITH UL 325. WHERE PROVIDED, AUTOMATIC VEHICULAR GATES SHALL COMPLY WITH SECTION 3110. SEE HEALTH AND SAFETY CODE SECTIONS 19890 AND 19891 FOR ADDITIONAL PROVISIONS FOR RESIDENTIAL GARAGE DOOR OPENERS. 406.2.1(NOTE: THE HEALTH AND SAFETY CODE SECTION 19892 REQUIRES THE GARAGE OPENER TO HAVE A BATTERY BACKUP FUNCTION WHICH ALLOWS THE GARAGE DOOR OPENER TO BE OPERATIONAL WITHOUT INTERRUPTION DURING AN ELECTRICAL OUTAGE.)
TYPE AA TYPE A
SCHEDULE
SEE DOOR
TYPE GTYPE H
3'-0"
SCHEDULE
SEE DOORSEE DOOR SCHEDULESEE DOOR SCHEDULETYPE J
SEE DOOR SCHEDULE SEE DOOR SCHEDULESEE DOOR SCHEDULE SEE DOOR SCHEDULESEE DOOR SCHEDULESEE DOOR SCHEDULESCHEDULE SEE DOORSEE DOOR SCHEDULETYPE DDTYPE F6 TYPE CSEE DOOR SCHEDULESCHEDULE SEE DOORSEE DOOR SCHEDULESEE DOOR SCHEDULETYPE ETYPE F4SEE DOOR SCHEDULESEE DOOR SCHEDULE
SCHEDULE
SEE DOOR
TYPE BB
DOOR TYPES
DOUBLE PANELDOUBLE PANEL
ALL GLASS DOOR
SINGLE PANEL
WITH PARTIAL
VISION GLASS
DOUBLE PANEL
WITH LOUVERS,
50% OPENESS
FACTOR
BIPARTING SLIDING DOORS
WITH SIDE LITES
FOLDING OPERABLE GLASS
PARITION WITH SINGLE
PANEL SWING DOOR
FOLDING OPERABLE GLASS
PARITION WITH SINGLE
PANEL SWING DOOR
MOTORIZED OVERHEAD COILING DOOR
(EXTERIOR DOOR R VALUE = 10.9)
MOTORIZED GLAZED SECTIONAL VERTICAL RISE ROLLING DOOR
(GLAZING: 1/2" TEMPERED SOLARBAN 70XL ARGON FILLED IGU.
DOOR R VALUE = 4.09)
MOTORIZED HANGAR DOOR
TT
T
SCHEDULE
SEE DOOR
TTTT
TTTTTTTTTT SEE DOOR SCHEDULESEE DOOR SCHEDULENOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 1/4" = 1'-0"COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
DOOR SCHEDULE
AND OPENING
TYPES
A6.11
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDINGDOOR SCHEDULE
DOOR NUMBERDOOR TYPEDETAILS OPENING DOOR PANEL DOOR FRAME FIRE RATINGREMARKSHEADJAMBJAMBTHRESHOLDWIDTHHEIGHTTHICKNESSCOREMATERIALFINISHMATERIALFINISHHARDWARE GROUP100B BB 02/A8.51 03/A8.51 01/A8.51 6'-0" 7'-10" 0'-1 3/4" GL/AL AL GL AL FF 01 PH, CR, PA 100C H 01/A8.52 04/A8.52 18'-0" 18'-0" 0'-1 3/4" GL/AL AL FF AL FF 16 CR, MOTORIZED 100D H 01/A8.52 04/A8.52 18'-0" 18'-0" 0'-1 3/4" GL/AL AL FF AL FF 16 CR, MOTORIZED 100E AA 10/A8.51 11/A8.51 09/A8.51 6'-0" 7'-10" 0'-1 3/4" HCI HM PT HMEE PT 03 PH, PA, OH 100F AA 10/A8.51 11/A8.51 09/A8.51 6'-0" 7'-10" 0'-1 3/4" HCI HM PT HMEE PT 02 PH, OH 100G J 15/A8.53 01/A8.53 13/A8.53 54'-0" 29'-10" 0'-1 3/4" GL/AL AL FF AL FF 15 CR, MOTORIZED 101A AA 17G/A9.41 6'-0" 7'-10" 0'-1 3/4" SC WD1 ST HM PT 09 PH, CR, OH, KP 101B AA 10/A8.51 11/A8.51 09/A8.51 6'-0" 7'-10" 0'-1 3/4" HCI HM PT HMEE PT 07 CR, OH, KP 101C G 10/A8.52 12/A8.52 09/A8.52 12'-0" 12'-0" 0'-1 3/4" INSUL STL FFC STL FF 19 MOTORIZED 102A C 17A/A9.41 3'-0" 7'-10" 0'-1 3/4" SC/GL WD1 ST HM PT 12 102B A 10/A8.51 11/A8.51 09/A8.51 3'-0" 7'-10" 0'-1 3/4" HCI HM PT HMEE PT 05 KP, NO EXTERIOR HARDWARE 103 DD 10/A8.51 11/A8.51 09/A8.51 6'-0" 7'-10" 0'-1 3/4" HM HM PT HM PT 06 CR, OH 104 A 10/A8.51 11/A8.51 09/A8.51 4'-0" 7'-10" 0'-1 3/4" HCI HM PT HMEE PT 04 CR, OH, PH 105 A 17D/A9.41 3'-0" 7'-10" 0'-1 3/4" SC WD1 ST HM PT 10 45 MIN CR, OH 106 A 17E/A9.41 3'-0" 7'-10" 0'-1 3/4" SC WD1 ST HM PT 14 OH, KP 107 A 17E/A9.41 3'-0" 7'-10" 0'-1 3/4" SC WD1 ST HM PT 14 OH, KP 108 A 17E/A9.41 3'-0" 7'-10" 0'-1 3/4" SC WD1 ST HM PT 13 KP, OI 109 A 17G/A9.41 3'-0" 7'-10" 0'-1 3/4" SC WD1 ST HM PT 11 CR, KP 110 A 17G/A9.41 3'-0" 7'-10" 0'-1 3/4" SC WD1 ST HM PT 10 60 MIN CR, OH 112A F6 06/A8.51 07/A8.51 05/A8.51 17'-6" 9'-10" 0'-1 3/4" GL/AL AL FF AL FF 18 CR, PH, OH 112B F4 06/A8.51 07/A8.51 05/A8.51 15'-6" 9'-10" 0'-1 3/4" GL/AL AL FF AL FF 18 CR, PH, OH 112C E 14'-8" 9'-10" 0'-1 3/4" GL/AL AL FF AL FF 17
113 F6 06/A8.51 07/A8.51 05/A8.51 17'-6" 9'-10" 0'-1 3/4" GL/AL AL FF AL FF 18 CR, PH, OH 114 A 17E/A9.41 3'-0" 7'-10" 0'-1 3/4" SC WD1 ST HM PT 13 KP, OI 115 A 10/A8.51 11/A8.51 09/A8.51 3'-0" 7'-10" 0'-1 3/4" HCI HM PT HMEE PT 08 CR, OH 116 A 3'-0" 7'-10" 0'-1 3/4" SC WD1 ST HM PT 13 KP, OI
201 A 3'-0" 7'-10" 0'-1 3/4" SC WD1 ST HM PT 10 CR, OH
UP
DN
7 D
06 A7.01
04 A7.01
07 A7.01
03.03 5'-0"CLEAR
05.04 05.13
05.13 EQ TREADS11'-0"05.11
A7.11
15A7.11
15 Sim
10 A7.01
09.07 7
D
06 A7.01
04 A7.01
07 A7.01
03.02 5'-0"CLEAR
EQ TREADS10'-1"C
A7.11
14 A7.11
13B
A7.11
14 Sim
10 A7.01
09.07 01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
D
04 A7.01
26.06 26.06
05.05 05.11
03.03 05.07
05.06 13.04
05.13 A7.11
18 A7.11
17 04
A7.11
02 A7.11
A7.11
05 01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
7 06
A7.01
07 A7.01
05.13 0'-4"
A7.11
04 A7.11
02 10
A7.01
KEYNOTES
1.SEE A9.0X SERIES FOR WALL TYPES
LEGENDGENERAL NOTES
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.0X SERIES.
STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.0X SERIES.
REFER TO S0.91 FOR INTERIOR STUD WALL SCHEDULE
METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION
2 HOUR RATED METAL STUD WALL CONSTRUCTION
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
D
04 A7.01
05.13 C
A7.11
18 04
A7.11
02 A7.11A7.11
10 A7.11
05 01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
D
04 A7.01
C
A7.11
19 TYP.05.13
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
ENLARGED STAIR
PLANS AND
SECTIONS
A7.01
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/4" = 1'-0"02EAST STAIR PLAN - FIRST FLOOR 1/4" = 1'-0"03EAST STAIR PLAN - SECOND
FLOOR
1/4" = 1'-0"06EAST STAIR SECTION A
1/4" = 1'-0"04EAST STAIR SECTION B
03.02 PRECAST CONCRETE TREADS AND LANDING
03.03 PRECAST CONCRETE TREAD
05.04 PERFORATED METAL PANEL GUARDRAIL WITH STEEL FLAT BAR STOCK FRAME. PROVIDE VERTICAL FLAT BAR STOCK EVERY 4'-0"
05.05 STEEL GUARDRAIL HEIGHT TO BE 3'-6" ABOVE STAIR STRINGER. PROVIDE HIGH PERFORMANCE PAINTED FINISH AND A METAL HANDRAIL.
05.06 TUBE STEEL STRINGER
05.07 STEEL STAIR RISER
05.11 STEEL HANDRAIL
05.13 STAINLESS STEEL CANE DETECTION RAIL. REFER TO 20/G0.32.
09.07 2" CONTRASTING STRIPE.
1/4" = 1'-0"07EAST STAIR SECTION B
1/4" = 1'-0"10STAIR SECTION 2
OS OSOSOSUP
UP
234 5 6
A
04 A3.12
10 A7.02
A5.08
02 04
A7.02
2'-0"
EQ TREADS
8'-3"6'-8"
EQ TREADS
8'-3"15'-1"9'-0"9'-0"30'-0"12'-0"30'-0"
08 A7.11
A7.11
13A
A7.11
12 A7.11
13ASim
A7.11
13A Sim
A7.11
13A Sim
A7.11
13A Sim
A7.11
13A Sim5'-0"10'-0"12'-6"
4.2 4.8 5.2 5.8
14 1-A3.03
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
2 3
4 5 604
A3.12
10 A7.02
05.11 05.04
05.05 05.07
05.0605.04CLEAR6'-9"10'-0"12'-6"5'-0"08
A7.11
A7.11
17 04
A7.11
02 A7.11A7.11
05 A7.11
10 A7.11
19 4.2 4.8 5.2 5.814
1-A3.03
2 A
04 A7.02
05.04 A7.11
15Sim
A7.11
15Sim
05.01 01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
A
05.04 04
A7.02
A7.11
04 A7.11
03 B
TYP.13.01
05.01 KEYNOTES
1.SEE A9.0X SERIES FOR WALL TYPES
LEGENDGENERAL NOTES
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.0X SERIES.
STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.0X SERIES.
REFER TO S0.91 FOR INTERIOR STUD WALL SCHEDULE
METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION
2 HOUR RATED METAL STUD WALL CONSTRUCTION
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202230% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
ENLARGED RAMP
AND STAIR PLANS
AND SECTIONS
A7.02
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/4" = 1'-0" A7.02 03SECOND FLOOR STAIR AND RAMP PLAN
1/4" = 1'-0"
A7.02 04RAMP SECTION 1
1/4" = 1'-0"
A7.0218FIRST FLOOR STAIR PLAN 1/4" = 1'-0"
A7.02 10SPACE SHUTTLE ACCES
05.01 TUBE STEEL COLUMN WITH HIGH PERFORMANCE FINISH. REFER TO STRUCTURAL DRAWINGS.
05.04 PERFORATED METAL PANEL GUARDRAIL WITH STEEL FLAT BAR STOCK FRAME. PROVIDE VERTICAL FLAT BAR STOCK EVERY 4'-0"
05.05 STEEL GUARDRAIL HEIGHT TO BE 3'-6" ABOVE STAIR STRINGER. PROVIDE HIGH PERFORMANCE PAINTED FINISH AND A METAL HANDRAIL.
05.06 TUBE STEEL STRINGER
05.07 STEEL STAIR RISER
05.11 STEEL HANDRAIL
13.01 EXHIBIT BY OTHERS
2" CONTRASTING
STRIP, TYP.
PRECAST CONCRETE
TREAD.
CLIP ANGLE WELDED TO
STRINGER ANCHOR TO
FLOOR WITH EXPANSION
BOLTS.
THICKEN SLAB AT STAIR
BASE. REF TO STRUCT
DWGS.
STEEL ANGLE WELDED TO
STAIR STRINGER AT EACH
SIDE OF STANCHION
PER STRUCTURAL
DRAWINGS
FASTENERS PER
STRUCTURAL DWGS
0' - 0"
FIRST FLOOR
1/2" RADIUS MAX. AT
EDGE, TYPICAL
PRECAST
CONCRETE TREAD
PAINTED TUBE STEEL
STRINGER PER
STRUCTURAL
DRAWINGS
1" MAX 4" MIN (7" MAX)RISER11" MIN.
TREAD PER PLAN
METAL BENT
PLATE 0'-2"PRECAST
CONCRETE
LANDING
HSS BEAM PER
STRUCTURAL
PAINTED TUBE STEEL
STRINGER PER
STRUCTURAL DRAWINGS
2" CONTRASTING
STRIP, TYP.
11" MIN
TREAD PER PLAN
PAINTED TUBE STEEL
STRINGER PER
STRUCTURAL DRAWINGS
CONCRETE
FLOOR SLAB
PRECAST CONCRETE
TREAD
2" CONTRASTING
STRIP, TYP.
PER PLAN
STEEL ANGLE WELDED TO
STAIR STRINGER AT EACH SIDE
OF STANCHION
PER STRUCTURAL DRAWINGS
PRECAST STAIR TREAD
0'-0 3/4"0'-2 1/2"HSS PER STRUCTURAL DRAWINGS
ALIGN
STEEL ANGLE WELDED TO
CLOSURE PLATE AT EACH
SIDE OF STANCHION
PERFORATED
METAL PANEL
2"x1" STEEL BAR
STANCHION
A7.11
10 LANDING
STEEL MESH
S.S. HANDRAIL
S.S. TOP RAIL
A7.11
01 2'-2"3'-0"1'-0"TREAD DEPTH
S.S. TOP RAIL
1 1/2" O.D. S.S.
PIPE HANDRAIL
STEEL MESH
0' - 0"
01 - FLOOR3'-6"1'-0"TREAD DEPTH1 1/2" S.S. TUBE VERTICAL POST BELOW, TYP.
CONTRASTING STRIPPING
S.S. TOP RAIL
S.S. TOP RAIL
CONTRASTING STRIPPING
1 1/2" S.S. TUBE
VERTICAL POST BELOW,
TYP.1'-0"EDGE OF FINISH FLOOR
TOP OF GUARDRAIL
CONTRASTING STRIPPING
S.S. HANDRAIL, 1/8" EDGES
TYPICAL ALL CORNERS
S.S. TOP RAIL
GRIND ALL WELDS SMOOTH
HANDRAIL
BEYOND
HANDRAIL BEYOND
TOP RAIL
HANDRAIL
BEYOND
RAMP LANDING EDGE
S.S. TOP RAIL WITH STEEL
MESH BELOW
1 1/2" S.S. TUBE VERTICAL
POST BELOW, TYP
1 1/2" O.D. S.S. HANDRAIL,
TYP
CONTRASTING STRIPPING
1X1X3/16" STEEL ANGLE
1 1/4X1/4" WELDED PLATE
1/16" Ø WELDED WIRE MESH SCREEN
STEEL TUBE STRINGER. REFER
TO STRUCTURAL DRAWINGS.0'-1 1/2"HANDRAIL ABOVE
HANDRAIL SUPPORT ABOVE
METAL MESH INFILL PANEL
METAL CHANNEL EDGING FRAME
COUNTER SUNK BOLT HOLE
CONTINUOUS L ANGLE
1" X 2" VERTICAL SUPPORTS
STEEL BAR STOCK
2"x3/8" STEEL BAR
STOCK TOP RAIL
METAL MESH INFILL
PANEL WITH
CHANNEL FRAME
2"x1" STEEL BAR
STANCHION
1 1/2" DIA STAINLESS
STEEL HANDRAIL
WHERE OCCURS
HANDRAIL SUPPORT
WHERE OCCURSMIN CLR1 1/2"1 1/2"2"
CLOSURE PLATE
WIRE MESH
2"x1" STEEL BAR
STANCHION
STEEL ANGLE WELDED TO
CLOSURE PLATE AT EACH
SIDE OF STANCHION
0'-7"3'-6"A7.11
04 A7.11
03 3'-0"A7.11
06 15' - 0"
02 - FLOOR2'-2"3'-0"3'-6"STEEL MESH
S.S. HANDRAIL
1'-0"
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
STAIR DETAILS
A7.11
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1 1/2" = 1'-0" A7.11 01PRECAST STAIR TREAD BOTTOM 1 1/2" = 1'-0"
A7.11 05PRECAST TREAD/ RISER DETAIL
1 1/2" = 1'-0"
A7.11 10INTERMEDIATE LANDING DETAIL
1 1/2" = 1'-0"
A7.11 06PRECAST STAIR LANDING AT FLOOR
3" = 1'-0"02STAIR STRINGER SECTION 1" = 1'-0"18HANDRAIL SWITCHBACK 1" = 1'-0"17TYP HANDRAIL BOTTOM LANDING
1 1/2" = 1'-0"15TYP HANDRAIL BOTTOM LANDING
PLAN
1 1/2" = 1'-0"14TYP HANDRAIL TOP LANDING -
PLAN
1 1/2" = 1'-0"13BHANDRAIL AT SWITCHBACK - PLAN
1" = 1'-0"
A7.1116TYP GUARDRAIL AT FLOOR EDGE 1" = 1'-0"
A7.1124TYP GUARDRAIL AT STAIR 1" = 1'-0"
A7.1120TYP GUARDRAIL AT RAMP
1 1/2" = 1'-0"13AHANDRAIL END - PLAN
1" = 1'-0"
A7.11 12SECOND FLOOR RAILING END
3" = 1'-0"09GUARDRAIL PLAN AT BASE
ATTACHMENT
3" = 1'-0"04TOP OF GUARDRAIL
3" = 1'-0"03SECOND FLOOR SLAB EDGE WITH
GUARDRAIL
1" = 1'-0"08SECOND FLOOR HANDRAIL EDGE
1" = 1'-0"19STAIR HANDRAIL AT TOP OF STAIR
7 E
10 A7.21
02 A7.21
SS6SS6ELEV19'-8 1/2" CLEARD.9
CLEAR HOISTWAY
9'-6"CLEAR HOISTWAY7'-6"05.08
7 E
10 A7.21
02 A7.21
ELEV2
SS6
SS6
SS6SD4
SD4
SS6
SD6
SS6
D.9
CLEAR HOISTWAY7'-6"CLEAR HOISTWAY
9'-6"
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
E
02 A7.21
A7.31
15 A7.31
15 A7.31
20 D.9
ELEVATOR
111
OPEN
EXHIBIT
SPACE
200
08.07 23.07
01 - FLOOR
0'-0"
02 - FLOOR
15'-0"
7 10
A7.21
ELEVATOR
MACHINE
ROOM
110
ELEVATOR
111
ROOF
ACCESS
201
EXHIBIT
SPACE
100
26.06 05.20
23.07 KEYNOTES
1.SEE A9.0X SERIES FOR WALL TYPES
LEGENDGENERAL NOTES
SA2U
WALL TYPE. LETTER INDICATES WALL TYPE. SEE A9.0X SERIES.
STUD SIZE. NUMBER INDICATES STUD SIZE. SEE A9.0X SERIES.
REFER TO S0.91 FOR INTERIOR STUD WALL SCHEDULE
METAL STUD WALL CONSTRUCTION
1 HOUR RATED METAL STUD WALL CONSTRUCTION
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
ENLARGED
ELEVATOR PLANS
AND SECTIONS
A7.21
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 1/4" = 1'-0"14ELEVATOR PLAN - FIRST FLOOR 1/4" = 1'-0"15ELEVATOR PLAN - SECOND FLOOR
1/4" = 1'-0"10ELEVATOR SECTION A 1/4" = 1'-0"02ELEVATOR SECTION B
05.08 PITT LADDER
05.20 GUARD RAIL PER MANUFACTURER
08.07 ACCESS PANEL
23.07 ELEVATOR EXHAUST. SEE EXTERIOR ELEVATIONS FOR LOCATION AND MECHANICAL DRAWINGS.
26.06 LIGHTING FIXTURE. REFER TO LIGHTING DRAWINGS.
FINISH FLOOR
5'-4"4' - 0" N.T.S.2'-6"LINE OF CONCRETE PIT WALL
3/8" x 2" STEEL BARS
VERTICAL LADDER
3/8" x 2" BENT PLATE - WELD TO
VERTICAL, TYP.
1/2" ROUND EXPANSION ANCHOR
WITH 2 1/2" MIN. EMBEDMENT, TYP.
1" DIA. x 24" STEEL RUNGS @ 12" O.C.
0'-4 1/2"
PROVIDE 2 - 1/2" DIA. HILTI KWIK TZ BOLT
EXPANSION ANCHOR, EACH SIDE OF
VERTICAL STEEL BAR, MIN. EMBEDMENT
2-1/2" (ICC-ESR 1917)
FINISH FLOOR OF ELEVATOR PIT
NOTE:
PAINT ALL EXPOSED SURFACES
COORDINATE WIDTH OF LADDER AND
LOCATION IN PIT WITH ELEVATOR MFR
LINE OF METAL PANEL SHAFT WALL
LINE OF METAL STUD
3/8" x 2" STEEL BARS
1/2" STAINLESS STEEL BOLTS,
ATTACH TO METAL STUD FRAMING
1' - 0"1' - 0"6"2 1/2"1' - 0"1' - 0"10"3/16 0'-6"0'-6"
SATIN STAINLESS STEEL
PLEXIGLAS MOLDED LENS
FILTERED WHITE - ARROW TO BE
INVERTED AT SECOND FLOOR
1. 2.
NOTES:
VISUAL AND AUDIBLE SIGNAL
TO BE ACTIVATED WHEN
ELEVATOR BECOMES
ACCESSIBLE
THIS DEVICE TO BE MOUNTED
ON THE JAMB ON THE INSIDE
OF THE ELEVATOR CAB
CONDITION AT
FIRST FLOOR
0'-4"0'-6"0'-6"
SATIN STAINLESS STEEL
PLEXIGLAS MOLDED LENS
FILTERED WHITE - ARROW
TO BE INVERTED AT THIRD
FLOOR
CONDITION AT
SECOND FLOOR
0'-4"6' - 0" A.F.F.6' - 0" A.F.F.COMPACTED SUBSTRATE
(85% MODIFIED PROCTOR DENSITY)
FASTENED TERMINATION
BAR, FASTEN 12" O.C.
DRAINAGE BOARD OVER
WATERPROOFING
MEMBRANE
CONCRETE SLAB
MASTIC SEALANT
WATERSTOP, TYP.
MIN 3" (75mm) COVERAGE
1. 2.
NOTE:
SIDE WALL SPRINKLER AT
ELEVATOR PIT.
CASING BLOCKOUT TO BE
SECONDARY POUR.5'-0"0'-8"ELEVATOR PITMAX
0'-1 1/4"
STEEL ANGLE 6"x4"x3/8",
VERIFY EXACT SIZE AND
ATTACHMENT WITH ELEV.
MANUFACTURER PROVIDE ALL
REQUIRED ITEMS AND
ACCESSORIES FOR COMPLETE
INSTALLATION
ELEVATOR DOOR
THRESHOLDELEVATOR
CAR SILL
CONCRETE SLAB
TERMINATION BAR
PROTECTION
COURSE OR
DRAINAGE SYSTEM
WATERPROOFING
MEMBRANE1/4" MAX.MAX0'-0 1/2"2
1 GROUT FILL ± 1/2" MAX.HILTI KB-TZ2 - 3/8" DIA. 2 1/2" MIN. EFF. EMBED @ 16" O.C.
AND 4" FROM ENDS (ICC
ESR-4266)3" MIN0'-2"0'-1 1/4"
SATIN STAINLESS STEEL DOOR
FINISH FLOOR OF ELEVATOR CAR
THRESHOLD
GROUT FILL
SUBFLOOR @ SILL CONDITION
FINISH FLOOR PER FINISH PLANS
STEEL ANGLE L4x4x3/8" VERIFY EXACT
SIZE. ELEV. MANUFACTURER PROVIDE
ALL REQUIRED ITEMS AND
ACCESSORIES FOR COMPLETE
INSTALLATION± 1/2" MAX.1/4 3-12
ANGLE
TO
CLOSURE
CONDITION AT
GROUND FLOOR
CONDITION AT
SECOND FLOOR
0'-0 3/4"0'-2"WALL TYPE PER FLOOR
PLAN
DRYWALL SCREWS
PLACED PER
WALL RATING
REQUIREMENTS
SATIN STAINLESS STEEL
ELEVATOR DOOR AND
FRAME
0'-0 3/4"0'-2"WALL TYPE PER FLOOR
PLAN
DRYWALL SCREWS
PLACED PER
WALL RATING
REQUIREMENTS
SATIN STAINLESS STEEL
ELEVATOR DOOR AND
FRAME
6"1' - 4"3'-6" A.F.F.IN CASE OF
EMERGENCY
TO NOT USE
ELEVATORS
DESIGN NOTES
1. 1/8" THICK BRUSHED
STAINLESS PANE (VERTICAL
GRAIN) WITH ETCHED AND FILLED
GRAPHICS (BLACK)
2. FONT TO MATCH PROJECT.
ART- WORK TO BE APPROVED BY
JOHN BISHOP DESIGN PRIOR TO
FABRICATION. INSTALLATION BY
THE ELEVATOR CONTRACTOR
BUTTON ARROW TO BE INVERTED
AT SECOND FLOOR
KEY SWITCH AND 1/4" TEXT TO BE
APPLIED AT FIRST FLOOR ONLY
FIRE OR EMERGENCY
ELEVATOR OPERATION
KEY OFF:
NORMAL OPERATION
KEY ON:
RECALL ELEVATOR TO THIS
FLOOR. KEY CAN BE
REMOVED IN THIS POSITION.
KEY BY-PASS:
OVERRIDES HEAT AND
SMOKE SENSORS TO ALLOW
NORMAL ELEVATOR
OPERATION.
MAINTENANCE KEY
4"
EQ EQ
4"2" MIN.5'-0" A.F.F.ELEVATOR JAMB
PROVIDE RAISED 5-POINT
STAR OF EQUAL LENGTH AT
GROUND FLOOR, OUTSIDE
DIAMATER OF STAR TO BE 2"
RAISED GRADE 2 BRAILLE
BELOW NUMBERAL,
CONFORM TO SECTION
11B-703.3
FLOOR LANDING NUMBER,
ARABIC NUMERAL, RAISED
1/32" MIN. & COMPLIES W/
SECTIONS 11B-407.2.3 &
11B-703.2
1. 2.
NOTES:
PROVIDE FLOOR LANDING
IDENTIFICATION AT BOTH
ELEVATOR JAMBS.
RAISED CHARACTERS,
INCLUDING THE STAR,
SHALL BE WHITE ON
BLACK BACKGROUND.
NOTE:
THE AUTOMATIC DOOR REOPENING DEVICE IS ACTIVATED IF AN OBJECT PASSES THROUGH EITHER LINE A OR B. LINE A AND LINE B REPRESENT THE VERTICAL LOCATIONS OF THE DOOR REOPENING DEVICE NOT REQUIRING CONTACT.
INDICATOR LANTERN, ELEVATOR SIGN, CALL BUTTON TO BE LOCATED TO THE LEFT HAND
SIDE OF THE FIRST AND SECOND FLOORS AS INDICATED HERE
BRAILLE PLATE ON
BOTH SIDES OF JAMB,
SEE
INDICATOR LANTERN, SEE
ELEVATOR SIGN, SEE
CALL BUTTON, SEE
1'-0"5"29"34"5'-0"LINE
B
LINE
A
08 A7.31
07 A7.31
11 A7.31
08 A7.31
PER DETAILSTAR OF LIFE SYMBOL,
SEE
12 A7.31
2-WAY COMMUNICATION
SYSTEM
15 SG4.02
1. 2.
3. A.
B.
C.
D.
E.
F.
4. A.
B.
C.
5. A.
6. A.
B.
C.
a.
b.
c.
D.
E.
F.
7. A.
B.
C.
D.
E.
F.
a.
b.
•
•
•
•
c.
d.
•
•
G.
a.
•
•
•
•
•
8. A.
a.
b.
c.
B.
a.
b.
c.
9. A.
10. A.
B.
C.
11. 12.
GENERAL. ELEVATORS SHALL COMPLY WITH SECTION 11B-407 AND WITH ASME A17.1. THEY SHALL BE PASSENGER ELEVATORS AS CLASSIFIED BY ASME A17.1. ELEVATOR OPERATION SHALL BE AUTOMATIC.
ELEVATOR LANDING REQUIREMENTS. (CBC SECTION 11B-407.2) CALL CONTROLS. (CBC SECTION 11B-407.2.1 AND 11B-309.4) HEIGHT. CALL BUTTONS AND KEYPADS SHALL BE LOCATED WITHIN ONE OF THE REACH RANGES SPECIFIED IN SECTION 11B-308, MEASURED TO THE CENTERLINE OF THE HIGHEST OPERABLE PART. (CBC SECTION 11B-407.2.1.1)
SIZE AND SHAPE. CALL BUTTONS SHALL HAVE SQUARE SHOULDERS, BE 3/4 INCH (19.1 MM) MINIMUM IN THE SMALLEST DIMENSION AND SHALL BE RAISED 1/8 INCH (3.2 MM) PLUS OR MINUS 1/32 INCH (0.8 MM) ABOVE THE SURROUNDING SURFACE. THE BUTTONS SHALL BE ACTIVATED BY A MECHANICAL MOTION THAT IS DETECTABLE. (CBC SECTION 11B-407.2.1.2)
CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH SECTION 11B-3.05 SHALL BE PROVIDED AT ALL CALL CONTROLS. (CBC SECTION 11B-407.2.1.3) LOCATION. THE CALL BUTTON THAT DESIGNATES THE UP DIRECTION SHALL BE LOCATED ABOVE THE CALL BUTTON THAT DESIGNATES THE DOWN DIRECTION (CBC SECTION 11B-407.2.1.4) SIGNALS. CALL BUTTONS SHALL HAVE VISIBLE SIGNALS THAT WILL ACTIVATE WHEN EACH CALL IS REGISTERED AND WILL EXTINGUISH WHEN EACH CALL IS ANSWERED. CALL BUTTONS SHALL BE INTERNALLY ILLUMINATED WITH A WHITE LIGHT OVER THE ENTIRE SURFACE OF THE BUTTON. (CBC SECTION 11B-407.2.1.4)
KEYPADS. WHERE KEYPADS ARE PROVIDED, KEYPADS SHALL BE IN A STANDARD TELEPHONE KEYPAD ARRANGEMENT AND SHALL COMPLY WITH SECTION 11B- 407.4.7.2. (CBC SECTION 11B-407.2.1.6) HALL SIGNALS. (CBC SECTION 11B-407.2.2)
VISIBLE AND AUDIBLE SIGNALS. A VISIBLE AND AUDIBLE SIGNAL SHALL BE PROVIDED AT EACH
HOISTWAY ENTRANCE TO INDICATE WHICH CAR IS ANSWERING A CALL AND THE CAR'S DIRECTION OF TRAVEL. WHERE IN-CAR SIGNALS ARE PROVIDED, THEY SHALL BE VISIBLE FROM THE FLOOR AREA ADJACENT TO THE HALL CALL BUTTONS. (CBC SECTION 11B-407.2.2.1) VISIBLE SIGNALS. VISIBLE SIGNAL FIXTURES SHALL BE CENTERED AT 72 INCHES (1829 MM) MINIMUM ABOVE THE FINISH FLOOR OR GROUND. THE VISIBLE SIGNAL ELEMENTS SHALL BE A MINIMUM 2 1/2 INCHES (64 MM) HIGH BY 2 1/2 INCHES (64 MM) WIDE. SIGNALS SHALL BE VISIBLE FROM THE FLOOR AREA ADJACENT TO THE HALL CALL BUTTON. (CBC SECTION 11B-407.2.2.2) AUDIBLE SIGNALS. AUDIBLE SIGNALS SHALL SOUND ONCE FOR THE UP DIRECTION AND TWICE FOR
THE DOWN DIRECTION, OR SHALL HAVE VERBAL ANNUNCIATORS THAT INDICATE THE DIRECTION OF ELEVATOR CAR TRAVEL. AUDIBLE SIGNALS SHALL HAVE A FREQUENCY OF 1500 HZ MAXIMUM. VERBAL ANNUNCIATORS SHALL HAVE A FREQUENCY OF 300 HZ MINIMUM AND 3000 HZ MAXIMUM. THE AUDIBLE SIGNAL AND VERBAL ANNUNCIATOR SHALL BE 10 DB MINIMUM ABOVE AMBIENT, BUT SHALL NOT EXCEED 80 DB, MEASURED AT THE HALL CALL BUTTON. (CBC SECTION 11B-407.2.2.3) HOISTWAY SIGNS. (CBC SECTION 11B-407.2.3)
FLOOR DESIGNATION. FLOOR DESIGNATIONS COMPLYING WITH SECTIONS 11B-703.2 AND 11B-703.4.1 SHALL BE PROVIDED ON BOTH JAMBS OF ELEVATOR HOISTWAY ENTRANCES. FLOOR DESIGNATIONS SHALL BE PROVIDED IN BOTH RAISED CHARACTERS AND BRAILLE. RAISED CHARACTERS SHALL BE 2 INCHES (51 MM) HIGH. A RAISED STAR, PLACED TO THE LEFT OF THE FLOOR DESIGNATION, SHALL BE PROVIDED ON BOTH JAMBS AT THE MAIN ENTRY LEVEL. THE OUTSIDE DIAMETER OF THE STAR SHALL BE 2 INCHES (51 MM) AND ALL POINTS SHALL BE OF EQUAL LENGTH. RAISED CHARACTERS, INCLUDING THE STAR, SHALL BE WHITE ON A BLACK BACKGROUND. BRAILLE COMPLYING WITH SECTION 11B-703.3 SHALL BE PLACED BELOW THE CORRESPONDING RAISED CHARACTERS AND THE STAR. THE BRAILLE TRANSLATION FOR THE STAR SHALL BE "MAIN". APPLIED PLATES ARE ACCEPTABLE IF THEY ARE PERMANENTLY FIXED TO THE JAMB. (CBC SECTION 11B-407.2.3.1) ELEVATOR DOOR REQUIREMENTS. (CBC SECTION 11B-407.3)
TYPE. ELEVATOR DOORS SHALL BE THE HORIZONTAL SLIDING TYPE. CAR GATES SHALL BE PROHIBITED. (CBC SECTION 11B-407.3.1)
OPERATION. ELEVATOR HOISTWAY AND CAR DOORS SHALL OPEN AND CLOSE AUTOMATICALLY. (CBC SECTION 11B-407.3.2)
REOPENING DEVICE. ELEVATOR DOORS SHALL BE PROVIDED WITH A REOPENING DEVICE COMPLYING WITH SECTION 11B-407.3.3 THAT SHALL STOP AND REOPEN A CAR DOOR AND HOISTWAY DOOR AUTOMATICALLY IF THE DOOR BECOMES OBSTRUCTED BY AN OBJECT OR PERSON. (CBC SECTION 11B-407.3.3)
HEIGHT. THE DEVICE SHALL BE ACTIVATED BY SENSING AN OBSTRUCTION PASSING THROUGH THE OPENING AT 5 INCHES (127 MM) NOMINAL AND 29 INCHES (737 MM) NOMINAL ABOVE THE FINISH FLOOR. (CBC SECTION 11B-407.3.3.1)
CONTACT. THE DEVICE SHALL NOT REQUIRE PHYSICAL CONTACT TO BE ACTIVATED, ALTHOUGH CONTACT IS PERMITTED TO OCCUR BEFORE THE DOOR REVERSES. (CBC SECTION 11B-407.3.3.2) DURATION. DOOR REOPENING DEVICES SHALL REMAIN EFFECTIVE FOR 20 SECONDS MINIMUM. (CBC SECTION 11B-407.3.3.3)
DOOR AND SIGNAL TIMING. THE MINIMUM ACCEPTABLE TIME FROM NOTIFICATION THAT A CAR IS
ANSWERING A CALL UNTIL THE DOORS OF THAT CAR START TO CLOSE SHALL BE CALCULATED FROM THE FOLLOWING EQUATION:
T = D/(1.5 FT/S) OR T = D/(457 MM/S) = 5 SECONDS MINIMUM
WHERE T EQUALS THE TOTAL TIME IN SECONDS AND D EQUALS THE DISTANCE (IN FEET OR MILLIMETERS) FROM THE POINT IN THE LOBBY OR CORRIDOR 60 INCHES (1524 MM) DIRECTLY IN FRONT
OF THE FARTHEST CALL BUTTON CONTROLLING THAT CAR TO THE CENTERLINE OF ITS HOISTWAY DOOR. (CBC SECTION 11B-407.3.4)
DOOR DELAY. ELEVATOR DOORS SHALL REMAIN FULLY OPEN IN RESPONSE TO A CAR CALL FOR 5 SECONDS MINIMUM. (CBC SECTION 11B-407.3.5)
WIDTH. THE WIDTH OF ELEVATOR DOORS SHALL COMPLY WITH TABLE 11B-407.4.1.
ELEVATOR CAR REQUIREMENTS. (CBC SECTION 11B-407.4)
CAR DIMENSIONS. INSIDE DIMENSIONS OF ELEVATOR CARS AND CLEAR WIDTH OF ELEVATOR DOORS SHALL COMPLY WITH TABLE 11B-407.4.1. (CBC SECTION 11B-407.4.1) FLOOR SURFACES. FLOOR SURFACES IN ELEVATOR CARS SHALL COMPLY WITH SECTIONS 11B-302 AND 11B-303. (CBC SECTION 11B-407.4.2)
PLATFORM TO HOISTWAY CLEARANCE. THE CLEARANCE BETWEEN THE CAR PLATFORM SILL AND THE EDGE OF ANY HOISTWAY LANDING SHALL BE 11/4 INCH (32 MM) MAXIMUM. (CBC SECTION 11B-407.4.3) LEVELING. EACH CAR SHALL BE EQUIPPED WITH A SELF-LEVELING FEATURE THAT WILL AUTOMATICALLY BRING AND MAINTAIN THE CAR AT FLOOR LANDINGS WITHIN A TOLERANCE OF 1/2 INCH (12.7 MM) UNDER RATED LOADING TO ZERO LOADING CONDITIONS. (CBC SECTION 11B-407.4.4) ILLUMINATION. THE LEVEL OF ILLUMINATION AT THE CAR CONTROLS, PLATFORM, CAR THRESHOLD AND CAR LANDING SILL SHALL BE 5 FOOTCANDLES (54 LUX) MINIMUM. (CBC SECTION 11B-407.4.5) ELEVATOR CAR CONTROLS. WHERE PROVIDED, ELEVATOR CAR CONTROLS SHALL COMPLY WITH SECTIONS 11B-407.4.6 AND 11B-309.4. (CBC SECTION 11B-407.4.6) LOCATION. CONTROLS SHALL BE LOCATED WITHIN ONE OF THE REACH RANGES SPECIFIED IN SECTION 11B-308. (CBC SECTION 11B-407.4.6.1)
BUTTONS. CAR CONTROL BUTTONS WITH FLOOR DESIGNATIONS SHALL COMPLY WITH SECTION 11B-407.4.6.2.
SIZE AND SHAPE. BUTTONS SHALL HAVE SQUARE SHOULDERS, BE 3/4 INCH (19.1 MM) MINIMUM IN THEIR SMALLEST DIMENSION AND BE RAISED 1/8 INCH (3.2 MM) PLUS OR MINUS 1/32 INCH (0.8 MM) ABOVE THE SURROUNDING SURFACE. (CBC SECTION 11B-407.4.6.2.1) ARRANGEMENT. BUTTONS SHALL BE ARRANGED WITH NUMBERS IN ASCENDING ORDER.
WHEN TWO OR MORE COLUMNS OF BUTTONS ARE PROVIDED THEY SHALL READ FROM LEFT TO RIGHT. (CBC SECTION 11B-407.4.6.2.2)
ILLUMINATION. CAR CONTROL BUTTONS SHALL BE ILLUMINATED.(CBC SECTION 11B-407.4.6.2.3)
OPERATION. CAR CONTROL BUTTONS SHALL BE ACTIVATED BY A MECHANICAL MOTION THAT IS DETECTABLE. (CBC SECTION 11B-407.4.6.2.4)
KEYPADS. CAR CONTROL KEYPADS SHALL BE IN A STANDARD TELEPHONE KEYPAD ARRANGEMENT AND SHALL COMPLY WITH SECTION 11B-407.4.7.2.
EMERGENCY CONTROLS. EMERGENCY CONTROLS SHALL COMPLY WITH SECTION 11B-407.4.6.4.
HEIGHT. EMERGENCY CONTROL BUTTONS SHALL HAVE THEIR CENTERLINES 35 INCHES (889 MM) MINIMUM ABOVE THE FINISH FLOOR. (CBC SECTION 407.4.6.4.1) LOCATION. EMERGENCY CONTROLS, INCLUDING THE EMERGENCY ALARM, SHALL BE GROUPED AT THE BOTTOM OF THE PANEL. (CBC SECTION 407.4.6.4.2) DESIGNATIONS AND INDICATORS OF CAR CONTROLS. (CBC SECTION 407.4.7) BUTTONS. CAR CONTROL BUTTONS SHALL COMPLY WITH SECTION 11B-407.4.7.1 .
TYPE. CONTROL BUTTONS SHALL BE IDENTIFIED BY RAISED CHARACTERS OR SYMBOLS, WHITE ON A BLACK BACKGROUND, COMPLYING WITH SECTION 11B-703.2 AND BRAILLE COMPLYING WITH SECTION 11B-703.3. (CBC SECTION 11B-407.4.7.1.1) LOCATION. RAISED CHARACTERS OR SYMBOLS AND BRAILLE DESIGNATIONS SHALL BE
PLACED IMMEDIATELY TO THE LEFT OF THE CONTROL BUTTON TO WHICH THE DESIGNATIONS APPLY. (CBC SECTION 11B-407.4.7.1.2)
SYMBOLS. THE CONTROL BUTTON FOR THE EMERGENCY STOP, ALARM, DOOR OPEN, DOOR
CLOSE, MAIN ENTRY FLOOR, AND PHONE, SHALL BE IDENTIFIED WITH RAISED SYMBOLS AND BRAILLE AS SHOWN IN TABLE 11B-407.4.7.1.3. (CBC SECTION 11B-407.4.7.1.3) VISIBLE INDICATORS. BUTTONS WITH FLOOR DESIGNATIONS SHALL BE PROVIDED WITH VISIBLE INDICATORS TO SHOW THAT A CALL HAS BEEN REGISTERED. THE VISIBLE INDICATION SHALL EXTINGUISH WHEN THE CAR ARRIVES AT THE DESIGNATED FLOOR. (CBC SECTION 11B-407.4.7.1.4)
BUTTON SPACING. A MINIMUM CLEAR SPACE OF 3/8 INCH (9.5 MM) OR OTHER SUITABLE MEANS OF SEPARATION SHALL BE PROVIDED BETWEEN ROWS OF CONTROL BUTTONS. (CBC SECTION 11B-407.4.7.1.5)
KEYPADS. KEYPADS SHALL BE IDENTIFIED BY CHARACTERS COMPLYING WITH SECTION 11B-703.5 AND SHALL BE CENTERED ON THE CORRESPONDING KEYPAD BUTTON. THE NUMBER FIVE KEY SHALL HAVE A SINGLE RAISED DOT. THE DOT SHALL BE 0.118 INCH (3 MM) TO 0.120 INCH (3.05 MM) BASE DIAMETER AND IN OTHER ASPECTS COMPLY WITH TABLE 11B-703.3.1. (CBC SECTION 11B-407.4.7.2)CAR POSITION INDICATORS.
AUDIBLE AND VISIBLE CAR POSITION INDICATORS SHALL BE PROVIDED IN ELEVATOR CARS. (CBC SECTION 407.4.8)
VISIBLE INDICATORS. (CBC SECTION 407.4.8.1)
SIZE. CHARACTERS SHALL BE 1/2 INCH (12.7 MM) HIGH MINIMUM. (CBC SECTION 407.4.8.1.1) LOCATION. INDICATORS SHALL BE LOCATED ABOVE THE CAR CONTROL PANEL OR ABOVE THE DOOR. (CBC SECTION 407.4.8.1.2)
FLOOR ARRIVAL. AS THE CAR PASSES A FLOOR AND WHEN A CAR STOPS AT A FLOOR SERVED BY THE ELEVATOR, THE CORRESPONDING CHARACTER SHALL ILLUMINATE. (CBC SECTION 407.4.8.1.3) AUDIBLE INDICATORS. (CBC SECTION 407.4.8.2)
SIGNAL TYPE. THE SIGNAL SHALL BE AN AUTOMATIC VERBAL ANNUNCIATOR WHICH ANNOUNCES THE FLOOR AT WHICH THE CAR IS ABOUT TO STOP. (CBC SECTION 407.4.8.2.1) SIGNAL LEVEL. THE VERBAL ANNUNCIATOR SHALL BE 10 DB MINIMUM ABOVE AMBIENT, BUT SHALL NOT EXCEED 80 DB, MEASURED AT THE ANNUNCIATOR. (CBC SECTION 407.4.8.2.2) FREQUENCY. THE VERBAL ANNUNCIATOR SHALL HAVE A FREQUENCY OF 300 HZ MINIMUM TO 3000 HZ MAXIMUM. (CBC SECTION 407.4.8.2.3
EMERGENCY COMMUNICATION. EMERGENCY TWO-WAY COMMUNICATION SYSTEMS SHALL COMPLY WITH SECTION 11B-308. RAISED SYMBOLS OR CHARACTERS, WHITE ON A BLACK BACKGROUND, AND BRAILLE SHALL BE PROVIDED ADJACENT TO THE DEVICE AND SHALL COMPLY WITH SECTIONS 11B-703.2 AND 11B-703.3. EMERGENCY TWO-WAY COMMUNICATION SYSTEMS BETWEEN THE ELEVATOR AND A POINT OUTSIDE THE HOISTWAY SHALL COMPLY WITH ASME A17.1. (CBC SECTION 11B-407.4.9)
AN EMERGENCY ELEVATOR TWO-WAY COMMUNICATION SYSTEM SHALL BE PROVIDED THAT INCLUDES VISIBLE TEXT AND AUBILE MODES THAT MEET THE REQUIRMENTS OF CBC 3001.2 SUPPORT RAIL. SUPPORT RAILS SHALL BE PROVIDED ON AT LEAST ONE WALL OF THE CAR. (CBC SECTION 11B-407.4.10)
LOCATION. CLEARANCE BETWEEN SUPPORT RAILS AND ADJACENT SURFACES SHALL BE 11/2 INCHES (38 MM) MINIMUM. TOP OF SUPPORT RAILS SHALL BE 31 INCHES (787 MM) MINIMUM TO 33 INCHES (838 MM) MAXIMUM ABOVE THE FLOOR OF THE CAR. THE ENDS OF THE SUPPORT RAIL SHALL BE 6 INCHES (152 MM) MAXIMUM FROM ADJACENT WALLS. (CBC SECTION 11B-407.4.10.1) SURFACES. SUPPORT RAILS SHALL BE SMOOTH AND ANY SURFACE ADJACENT TO THEM SHALL BE FREE OF SHARP OR ABRASIVE ELEMENTS. (CBC SECTION 11B-407.4.10.2) STRUCTURAL STRENGTH. ALLOWABLE STRESSES SHALL NOT BE EXCEEDED FOR MATERIALS USED WHEN A VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS (1112 N) IS APPLIED AT ANY POINT ON THE SUPPORT RAIL, FASTENER, MOUNTING DEVICE, OR SUPPORTING STRUCTURE. (CBC SECTION 11B-407.4.10.3)
HOISTWAY DOORS. THE HOISTWAY LANDING OPENINGS SHALL BE PROVIDED WITH POWER-OPERATED DOORS. (CBC SECTION 3002.4.2a)
ELEVATOR RECALL. THE ELEVATOR(S) DESIGNAGED THE MEDICAL EMERGENCY ELEVATOR SHALL BE EQUIPPED WITH A KEY SWITCH TO RECALL THE ELEVATOR NONSTOP TO THE MAIN FLOOR. FOR THE PURPOSE OF THIS SECTION, ELEVATORS IN COMPLIANCE WITH SECTION 3003.2 SHALL BE ACCEPTABLE. (CBC 3002.4.3a)
GENERAL NOTES
2ND FLOOR
1ST FLOOR
2 1
FLOOR LEVEL NUMBER
BRAILLE DOTS
5/8" COPY SIZE RAISED 1/32" FROM
BACKGROUND
3/4" MIN. CONTROL BUTTON,
SQUARE SHOULDER AND RAISED
1/8" +/- 1/32" ABOVE THE
SURROUNDING SURFACE, TYP.
ALL CONTROL BUTTONS
STAR SYMBOL AT STAIR AT MAIN ENTRY
LEVEL, ALL POINTS OF STAR SHALL HAVE
EQUAL LENGTH
EMERGENCY CALL BUTTON
NOTE:
CONTROL PANEL DESIGN MAY VARY BY MANUFACTURER. LAYOUT AND FEATURES SHALL CONFORM TO CALIFORNIA BUILDING CODE 11B-407.4.6.2, 11B-407.4.6.3, 11B-407.4.7.1, AND 11B-407.4.8.1.6'-8" MIN.4'-0" MIN.35" MIN. A.F.F.3/8" MIN.3/16" MIN. SEPARATION BETWEEN BRAILLE DOTS AND RAISED CHARACTERS1
EMERGENCY STOP BUTTON
RAISED SYMBOLS W/ BRAILLE, TYP. ALL
(4) CONTROL BUTTONS
3'-6" A.F.F.
6'-0" A.F.F.
FRONTSIDEBACK SIDE
1 1/2" DIA. STAINLESS STEEL HANDRAIL
TO BE 1 1/2" CLEAR FROM WALL FINISH
AND 32" ABOVE CAB FINISH FLOOR
PLASTIC LAMINATE
PANELS (PL-1)
ELEVATOR CONTROL PANEL IN CAB
ELEVATOR DOORS TO REMAIN OPEN FOR
MINIMUM OF 3 SECONDS AFTER OPENING
CLR
1 1/2"32"CEILING PLAN
REMOVABLE ACCESS
PANEL
STAINLESS STEEL PANELS
WITH INCANDESCENT
DOWN-LIGHTS SIGN6'-9" A.F.F.JAMB & SIGN
ELEVATOR JAMB3" MIN1.
2. 3.
NOTES:
RAISED SYMBOL SHALL BE ON CONTRASTING BACKGROUND
THE SYMBOL SHALL NOT BE LESS THAN 3 INCHES (76MM) IN SIZE. (CBC 3002.4.5a)
A SYMBOL SHALL BE PERMANENTLY ATTACHED TO EACH SIDE OF THE
HOISTWAY DOOR FRAME ON THE PORTION OF THE FRAME AT RIGHT ANGLES TO THE HALLWAY OR LANDING AREA. EACH SYMBOL SHALL BE NOT LESS THAN 78 INCHES (1981 MM) AND NOT MORE THAN 84 INCHES (2134MM) ABOVE THE FLOOR LEVEL AT THE THRESHOLD.
(CBC 3002.4.6a)
DIM
PT.
PLAN
1" SHAFT LINER
TUBE STEEL PER
STRUCTURAL
TYP.
1/2"
ALIGN
2 1/2" E-STUDS
2 LAYERS OF 5'8"
TYPE 'X' GYP. BD.
LINE OF TUBE
STEEL BELOW
LINE OF FIREPROOFING
BELOW2"NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
ELEVATOR DETAILS
A7.31
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 3/4" = 1'-0" A7.3118ELEVATOR PIT LADDER DETAIL
3" = 1'-0"07ELEVATOR LANTERN DETAIL
1" = 1'-0"
A7.3114ELEVATOR PIT DETAIL
3" = 1'-0"
A7.3115ELEVATOR DOOR SILL
3" = 1'-0"20ELEVATOR HEAD 3" = 1'-0"16ELEVATOR JAMB
3" = 1'-0"
A7.31 11ELEVATOR CALL BUTTON
3" = 1'-0"08FLOOR LANDING IDENTIFICATION
1/4" = 1'-0"06TYPICAL ELEVATOR INFORMATION 1/4" = 1'-0"10CONTROL PANEL 1/2" = 1'-0"
A7.31 05ELEVATOR DOOR ELEVATION 1/2" = 1'-0"
A7.31 09ELEVATOR CAB ELEVATIONS 1/2" = 1'-0"
A7.3121ELEVATOR CAB CEILING
3" = 1'-0"12STAR OF LIFE
1 1/2" = 1'-0"
A7.3122TUBE STEEL AT ELEVATOR SHAFT
24ELEVATOR CAB CONTROL BUTTONS
FLOOR LEVEL
SLAB ON GRADE
PER STRUCTURAL
DRAWINGS
VAPOR BARRIER
PREPARED PAD &
SUBGRADE PER
GEOTECHNICAL
REPORT
CONCRETE CURB
FINISH GRADE PER
CIVIL DRAWINGS
VAPOR BARRIER
CONC BONDING
TAPE
FLOOR LEVEL
SLAB ON GRADE
PER STRUCTURAL
DRAWINGS
VAPOR BARRIER
PREPARED PAD &
SUBGRADE PER
GEOTECHNICAL REPORT
GRADE BEAM PER
STRUCTURAL
DRAWINGS
VAPOR BARRIER
CONC BONDING
TAPE
PREPARED SOILS PER GEOTECHNICAL REPORT
FASTENED TERMINATION
BAR, FASTEN 12" OC
DRAINAGE BOARD OVER
WATERPROOFING
MEMBRANE
SLAB ON GRADE PER
STRUCTURAL DRAWINGS
MASTIC SEALANT
WATERSTOP, TYP
MIN 3" (75MM) COVERAGE
1. 2.
NOTE:
SIDE WALL SPRINKLER AT ELEVATOR PIT.
CASING BLOCKOUT TO BE SECONDARY POUR.VERIFY WITH ELEVATOR MFR5' - 0" NTSSECTION VIEW
ELEVATOR PIT WALL
STRUCTURAL FOOTING ELEVATOR
PIT
CONTINUOUS VAPOR
BARRIER UNDERNEATH SLAB
AT VERICAL PIT WALLS
PARTIAL PLAN VIEW
3'-0" MIN.
3'-0" MINCONCRETE WALL
WATERPROOFING MEMBRANE,
WRAP ENTIRE FOOTING
PROVIDE MANUFACTURER
APPROVED HORIZONTAL
TERMINATION, TYP
PROVIDE MANUFACTURER APPROVED
VERTICAL TERMINATION, TYP
BENTONITE
WATERSTOP, TYP
3" (75MM) COVERAGE
FIRST FLOOR
FIRST FLOOR
SLAB ON GRADE
PER STRUCTURAL
DRAWINGS
VAPOR BARRIER
PREPARED PAD &
SUBGRADE PER
GEOTECHNICAL
REPORT
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.95% CONSTRUCTION DOCS 08/01/2025
3" = 1'-0"COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
FOUNDATION AND
UNDERGROUND
WATERPROOFING
DETAILS
A8.01
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 3" = 1'-0"01PERIMETER THICKENED SLAB VAPOR BARRIER 3" = 1'-0"02GRADE BEAM VAPOR BARRIER
3" = 1'-0"03ELEVATOR PIT DETAIL
3" = 1'-0"09SLAB ON GRADE VAPOR BARRIER
STANDING SEAM
METAL ROOF
SUSPENDED
ACOUSTIC
CEILING. REFER TO
PAGE A9.21
R2A: ROOF ASSEMBLY AT STEM BUILDING ENVELOPE
INTERIOR
EXTERIOR
INTERIOR
EXTERIOR
WEATHER RESISTIVE
BARRIER
ROOF PROTECTION
BOARD
METAL DECKING
PER STRUCTURAL
DRAWINGS
R-30 BATT
INSULATION
STEEL BEAM PER
STRUCTURAL
DRAWINGS
2'-0"
ACOUSTIC CEILING
TILE SUSPENSION
SYSTEM. REFER TO
PAGE A9.21
ACOUSTIC CEILING
TILE SUSPENSION
SYSTEM. REFER TO
PAGE A9.21
STANDING SEAM
METAL ROOF
SUSPENDED
ACOUSTIC CEILING.
REFER TO PAGE
A9.21
WEATHER RESISTIVE
BARRIER
ROOF PROTECTION
BOARD
METAL DECKING
PER STRUCTURAL
DRAWINGS
R-30 BATT
INSULATION
STEEL BEAM PER
STRUCTURAL
DRAWINGS
5/8" TYPE 'X' GYPSUM BOARD,
WHERE OCCURS
PLAN
SECTION
INTERIOR
EXTERIOR
6" METAL STUD
INSULATED METAL PANEL
5/8" TYPE 'X' GYPSUM BOARD,
WHERE OCCURS
6" METAL STUD
INSULATED METAL PANEL
DIM PT
INTERIOREXTERIOR
1" INSULATED LOW-
E GLASS
CURTAIN WALL
MULLION
CURTAIN WALL
MULLION BEYOND
SECTION
1" INSULATED LOW-E GLASS
CURTAIN WALL MULLION
CURTAIN WALL MULLION
BEYOND
PLAN0'-10"0'-2 1/4"
0'-10"0'-2 1/4"INTERIOREXTERIOR
INTERIOR
EXTERIOR
PLAN
SECTION
INTERIOR
EXTERIOR
9 1/2" METAL Z SECTIONS
INSULATED METAL PANEL
9 1/2" Z GIRT
INSULATED METAL PANEL
METAL BACKING
5/8" TYPE 'X' GYPSUM BOARD,
WHERE OCCURS
METAL BACKING, AS OCCURS
5/8" TYPE 'X' GYPSUM BOARD,
AS OCCURS
INTERIOREXTERIOR
DIM PT
STEEL COLUMN FLANGE BEYOND
2'-0"
TECTUM CEILING PANEL
SYSTEM PER 09/A9.21
R1A: ROOF ASSEMBLY AT EXHIBIT BUILDING ENVELOPE
EXTERIOR
EXTERIOR
METAL PURLIN PER
MANUFACTURER
PANEL CLIP
THERMAL BLOCKS
BATT INSULATION
TRAPIZODIAL RIB STANDING
SEAM ROOF SYSTEM:
INTERLOCKING ROOF PANEL
METAL PURLIN PER
MANUFACTURER
STEEL BEAM PER PEMB
MANUFACTURER
R-38 BLACK VINYL FACED
BATT INSULATION
FLANGE OF STEEL
BEAM BEYOND
PANEL CLIP
THERMAL BLOCKS
BATT INSULATION
TRAPIZODIAL RIB
STANDING SEAM ROOF
SYSTEM: INTERLOCKING
ROOF PANEL
TECTUM CEILING PANEL
SYSTEM PER 09/A9.21
R-38 BLACK VINYL FACED
BATT INSULATION
BRACING PER PEMB
STRUCTURE WHERE
OCCURS BRACING PER PEMB
STRUCTURE WHERE OCCURS
INTERIOR INTERIOR
R1B: ROOF ASSEMBLY AT EXHIBIT BUILDING CANOPY
METAL CEILING PANEL
SYSTEM; MFR:
STRUKTUROC PANELS
OR SIMILAREXTERIOREXTERIOR
METAL CEILING
PANEL SYSTEM;
MFR: STRUKTUROC
PANELS OR SIMILAR
FLANGE OF STEEL
BEAM BEYOND
2'-0"
EXTERIOR PANEL CLIP
THERMAL BLOCKS
BATT INSULATION
TRAPIZODIAL RIB STANDING
SEAM ROOF SYSTEM:
INTERLOCKING ROOF PANEL
METAL PURLIN PER
MANUFACTURER
R-38 BLACK VINYL FACED
BATT INSULATION
EXTERIOR
PANEL CLIP
THERMAL BLOCKS
BATT INSULATION
TRAPIZODIAL RIB
STANDING SEAM ROOF
SYSTEM: INTERLOCKING
ROOF PANEL
BRACING PER PEMB
STRUCTURE WHERE OCCURS
METAL CEILING
PANEL SYSTEM;
MFR: MCELROY
PANELS OR SIMILARR2B: ROOF ASSEMBLY AT STEM BUILDING CANOPY 2'-0"
STANDING SEAM
METAL ROOF
EXTERIOREXTERIOR
WEATHER
RESISTIVE BARRIER
ROOF PROTECTION
BOARD
METAL DECKING
PER STRUCTURAL
DRAWINGS
STEEL BEAM PER
STRUCTURAL
DRAWINGS
METAL FURRING
CHANNEL
EXTERIOREXTERIOR
METAL CEILING
PANEL SYSTEM;
MFR: MCELROY
PANELS OR SIMILAR
STANDING SEAM
METAL ROOF
WEATHER
RESISTIVE BARRIER
ROOF PROTECTION
BOARD
METAL DECKING
PER STRUCTURAL
DRAWINGS
METAL FURRING
CHANNEL
STEEL BEAM PER
STRUCTURAL
DRAWINGS
NOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202250% DESIGN DEVELOPMENT 12/02/2022100% DESIGN DEVELOPMENT 01/06/202330% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 3" = 1'-0"COLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
BUILDING SYSTEMS
A8.11
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 3" = 1'-0" A8.11R2AR2A - STANDING SEAM METAL ROOF AT STEM BUILDING 3" = 1'-0"W2STEM BUILDING EXTERIOR ASSEMBLY 3" = 1'-0"GA1GLAZING 3" = 1'-0"W1EXHIBIT BUILDING EXTERIOR ASSEMBLY 3" = 1'-0"
A8.11 R1AR1A - STANDING SEAM METAL ROOF AT EXHIBIT BUILDING 3" = 1'-0"
A8.11 R1BR1B - STANDING SEAM METAL CANOPY OVERHANG AT EXHIBIT BUILDING 3" = 1'-0" A8.11R2BR2B - STANDING SEAM METAL CANOPY OVERHANG AT STEM BUILDING
SHEET METAL GUTTER
INSULATED METAL PANEL
HORIZONTAL GIRTS
PURLINS
STANDING SEAM RIB
THERMAL BLOCK
BATT INSULATION
EAVE STRUT
PANEL VOID CLOSURE
EAVE FLASHINGR2A
W1
STRUCTURAL FLANGE
EXTENSION
CEILING PANEL
Z-CLOSURE CUT TO
FIT BETWEEN SEAMS
STANDING SEAM RIB
R2BSHEET METAL
FASCIAR2A
0'-1 1/2"METAL PANEL
CEILING R1ASHEET METAL
FASCIA
W1
ROOFING SYSTEM SEALANT
SS STL HOSE CLAMP
6"
M
I
N
CHEMICALLY RESISTANT PVC
FLASHING COMPONENT OF
ROOFING SYSTEM
1/4" MIN CLEARANCE BETWEEN
FLASHING COLLAR AND ROOF
PENETRATION MEMBER
ROOF PENETRATION (STL PIPE,
TUBE, OR SIMILAR ITEM)8" MINNOTE:
VENT STACKS AND
OTHER PIPES SHALL
HAVE A MIN OF 12"
OF CLEARANCE ON
ALL SIDES FROM
WALLS, CURBS, AND
OTHER PROJECTIONS.
MEMBRANE BOOT FLASHING
HOT-AIR WELDED TO BASE
FLASHING
MEMBRANE BASE FLASHING
HOT-AIR WELDED TO SINGLE PLY
ROOFING
STANDING SEAM METAL ROOF OVER
ROOFING BD OVER COMPOSITE
MTL DECK 1" MINEND CLOSURE PLATE, PER
STRUCTURAL 4/S1.22
HIGH EAVE FASCIA PER
PEMB, PREFINISHED TO
MATCH ROOF PANELR2BSLOPE
DRIP EDGE
1/4" DIA WEEP HOLES
AT 24" OC
METAL CEILING PANEL
STANDING SEAM TRIM
PER PEMB
STANDING SEAM
CLOSURE STRIP PER
PEMBR2AW2
METAL COPING,
PREFINISHED TO
MATCH ADJACENT
PANELS
BLOCKING
1"SLOPE
SHEET METAL
GUTTER
W2 R2AGUTTER
BRACKET
FLASHING
RAKE FASCIA, PREFINISHED
TO MATCH ROOF PANELR2B
METAL CEILING PANEL
SIGNAGE WHERE OCCURS
SEE DETAIL XX/SG.XX
STANDING STEAM TRIM
SUPPORTR2APER MECHANICAL OR
PLUMBING DWGS
INTERIOR
EXTERIOR
PVC MEMBRANE BOOT
FLASHING; HOT-AIR
WELDED TO BASE
FLASHING
SS STL DRAW BAND
CONT SEALANT BEAD
FASTENER BY
ROOFING MFR, TYP
STRUCTURAL STL; PER
STRUCTURAL DWGS, PROVIDE
CONT LEVEL SURFACE FOR ATT
CONT SEALANT
BEAD
SS STL DRAW
BAND
PVC SKIRT
FLASHING
0'-8"MINDIM POINT ℄
NOTE: ALL BLOW HOLES TO BE SEALED
WATERTIGHT. ALL EXPOSED STL SURFACES
ARE TO BE PAINTED.
STL BEAM PER PEMB
U-BAR SAFETY ANCHOR
3'-0" MAXPVC MEMBRANE BOOT
FLASHING; HOT-AIR
WELDED TO BASE
FLASHING
SS STL DRAW BAND
CONT SEALANT BEAD
FASTENER BY
ROOFING MFR, TYP
STRUCTURAL STL; PER
STRUCTURAL DWGS, PROVIDE
CONT LEVEL SURFACE FOR ATT
0'-8"MINDIM POINT ℄ 3'-0" MAXNOT FOR REGULATORY APPROVAL,
PERMITTING OR CONSTRUCTION
Developed forJob Number
Date Published
Checked By
ScaleRevisionDateARCHITECTURE ENGINEERING INTERIORS
LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
949-260-1190 Fax
LPADesignStudios.com
5301 California Avenue,
Suite 100
Irvine, California 92617
SubmittalDateThis document and all other project documents, ideas, aesthetics and designs incorporated
therein are instruments of service. All project
documents are copyright protected, are the
property of LPA, Inc. (LPA) and cannot be lawfully
used in whole or in part for any project or purpose
except as set forth in the contractual agreement
between LPA and its Client. The unauthorized
disclosure and/or use of the project documents
(including the creation of derivative works), may
give rise to liability for copyright infringement,
unlawful disclosure, use or misappropriation of
property rights held by LPA. The unauthorized
use of the project documents will give rise to the
recovery of monetary losses and damages
including attorney fees and costs for which the
unauthorized user will be held liable.
Project documents describe the design intent of
the work and are not a representation of as-built
or existing conditions. LPA is not responsible for
any discrepancies between the project documents
and the existing conditions.
© LPA, Inc.SCHEMATIC DESIGN10/27/202230% CONSTRUCTION DOCS 02/10/202395% CONSTRUCTION DOCS 08/01/2025 As indicatedCOLUMBIA WAYDOWNEY, CA 90242CITY OF DOWNEY3055401
ROOF AND CANOPY
DETAILS
A8.21
03/20/2023
CheckerSPACE SHUTTLE EXHIBIT AND EDUCATIONBUILDING 3" = 1'-0" A8.21 03R1A & R2B EXHIBIT BUILDING ROOF - LOW EAVE GUTTER 3" = 1'-0" A8.21 11R1 R2 - HIGH EAVE AT CANOPY
3" = 1'-0"
A8.21 08R1 R2 - RAKE AT CANOPY 3" = 1'-0"
A8.21 04R1 - RAKE AT EXT WALL
12" = 1'-0"
A8.2117TYPICAL ROOF PIPE - PLUMBING VENT PENETRATION AT METAL DECK 3" = 1'-0" A8.21 01R2B STEM ROOF - HIGH EAVE AT CANOPY
3" = 1'-0"
A8.21 10R2A STEM ROOF - RAKE AT EXT WALL
3" = 1'-0"
A8.21 09R2A STEM ROOF - LOW EAVE GUTTER
3" = 1'-0"
A8.21 02R2B STEM ROOF - RAKE AT CANOPY
3" = 1'-0"
A8.2119R1 R2 - PIPE PENETRATION DETAIL
3" = 1'-0"
A8.2120ROOF SAFETY TIE BACK
3" = 1'-0"
A8.2118ROOF ANCHOR RIGGING SLEEVE
02 - FLOOR
15'-0"
NOTE:
ALL ROOF ACCESS LADDER AND INTERMEDIATE PLATFORM COMPONENTS
SHOWN ARE FOR REFERENCE ONLY TO DEMONSTRATE MINIMUM CODE REQUIREMENTS AND GENERAL DESIGN INTENT. THE FINAL DESIGN AND ANALYSIS SHALL BE SUBMITTED TO THE CITY AS A DEFERRED SUBMITTAL.
CITY APPROVAL IS REQUIRED PRIOR TO FABRICATION AND INSTALLATION.15'-0"13 A8.22
14 A8.22
22 A8.22
BENT PLATE PER MFR
WALL TYPE PER PLAN
4'-0"2'-3"
STEEL FLAT BARS, CONTINUOUS
FROM BOTTOM SAFETY HOOP TO
TOP OF CAGE OMIT BARS AND
LANDING SIDE OF CAGE ABOVE
LANDING FLOOR LEVEL WHERE
LATERAL ACCESS IS REQUIRED.
09B
A8.22
09B. PLAN
09A. ELEVATION
9" MAX
9" MAX
2'-7"3'-6" MIN.STEEL FLAT BARS TO EXTEND
AS REQUIRED TO MEET TOP
SURFACE OF GUARDRAIL.
7'-0" ABOVE LANDING SURFACE.
BACKING TRACK AND
SUPPORT
LADDER RUNGS &
STRINGER PER 13/A8.22
LADDER PER 21/A8.22
VERTICAL LADDER PER MFR
FINISH FLOOR
NOTE:
PAINT ALL EXPOSED
SURFACES1'-0"1'-0"(14" MAX)0'-10"PER MFR.WALL TYPE PER PLAN 1/2 DIA. HILTI KB-TZ2 W/ 3 1/4"
EMBED PER ICC ESR-4266
BRACKETS PER MFR.
STEEL RUNG PER MFR
1/4" DIA. HILTI KWIK FLEX
AT EACH BRACKET PER
ICC ESR-3332.
BACKING TRACK AND
SUPPORT
VERTICAL LADDER
ROOF ACCESS PLATFORM
WALL TYPE PER PLAN
(14" MAX)10"STEEL GUARDRAIL
ROOF ACCESS
PLATFORM SUPPORTSEQEQ2'-0" MAXBENT PLATE
STEEL RUNG, 3/4" MIN. DIAM.
BACKING TRACK AND SUPPORT
2'-0" CLR.0'-7"
BOXED STUD COLUMN AT
METAL STUD WALLS PER
SCHEDULE 'A' BELOW
WALL TYPE PER PLAN
STEEL RUNG PER MFR.
SCHEDULE 'A'
LADDER
HEIGHT
H<20'
20'<H<30'
(2) 600S162-97 EA LEG
(3) 600S162-97 EA LEG
BOXED COLUMN DESC
30'<H<40'(2) 800S162-97 EA LEG
1/4" DIA. HILTI KWIK FLEX AT
EACH BRACKET PER ICC
ESR-3332.
BACKING TRACK
ROOF HATCH ASSEMBLY
18 GA. CURB LINED WITH
WOD. ATTACH TO