Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 8

Page 8 ends

Storm runoff from the exterior vehicle washdown area will be directed to the onsite storm drain system with a Fox Drain system.

Onsite storm drain conveyance shall be PVC SDR 35 for pipe sizes 4” to 10” and HDPE for pipe sizes 12” and up. Drain inlets shall be precast concrete or HDPE and will range from 6 -inch round to 24” square grates. Planter drains shall be 4 -inch or 6 -inch round black atrium drains. Storm drain cleanouts shall be installed at changes in pipe direction and at intervals of 100 feet maximum. Drain basins shall be installed in lieu of cleanouts for pipes larger than 12”.

F. EROSION CONTROL
BMP’s (Best Management Practices) and erosion control requirements will be stipulated on the Erosion Control Plan, to be prepared by the design consultant.

Since the limits of disturbance exceed 1 -acre, a Storm Water Pollution Prevention Plan (SWPPP) will be required, to be prepared by the design consultant.

The Design -Build Entity shall be required to employ the services of a Qualified SWPPP Practitioner (QSP). The QSP shall be required to download copies of the approved SWPPP from the State and will be responsible for implementation and enforcement of the SWPPP and the Erosion Con trol Plan during construction.

Within 90 days of construction completion, the Design -Build Entity 's QSP shall electronically file a Notice of Termination, NOT, to the State Water Board's SMARTS system.

END OF SITE PLANNING SECTION
004 STRUCTURAL SYSTEMS
A. GENERAL

1. The building must be designed to meet the requirements for an essential services building (risk category IV) as required by the 2025 CBC. While the below provides suggested structural systems, the design team is responsible for choosing a system that adequately addresses the final design with consideration of long -term serviceability and structural durability. Wood structural systems ar e not considered an acceptable alternative.

B. GRAVITY SYSTEMS

1. Foundation System
Refer to the owner-provided , draft geotechnical investigation report by Geocon Consult ants Inc., Project No . E9213-04 -06 dated January 09 , 2026. The building may be supported by shallow foundations designed to allowable pressures provided in the geotechnical report. However, the final building layout and loading should be evaluated by the geotechnical engineer to ensure the recommendations provided in the report are adequate. The ground floor slab -on-grade is expected to be a conventional reinforced 5” slab -on-grade typical and 10” thick in the apparatus bays but should be confirmed by the structural engineer.

Page 191 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 9

Page 9 ends

2. Framing System
It is anticipated that the roof framing will be constructed out of light-gauge steel and structural steel supporting metal deck. However, alternative framing systems may be chosen based on the final layout and design of the new building and should include consideration of life -cycle costs, resilience, and constructability. Wood construction is not an acceptable alternative.

C. LATERAL SYSTEMS
The primary lateral system is anticipated to be light -framed metal framing with steel sheets or Special Steel Moment Frames. However, alternative framing systems may be chosen based on the final layout and design of the new building and should include consideration of life -cycle costs, resilience, and constructability. Wood construction is not an acceptable alternative.

D. NONSTRUCTURAL COMPONENTS
Nonstructural components are to be designed and anchored per the requirements of the 2025 CBC and ASCE 7 -22 Chapter 13. All architectural, mechanical, electrical, plumbing, fire protection , audio/visual systems , etc., must be anchored per code requirements and utilizing an importance factor equal to 1.5.

E. LOAD S

LIVE LOADS
Per CBC, Section 1607.

WIND LOADS
Per CBC, Section 1609
Risk Category IV

LOAD COMBINATIONS
Per CBC, Section 1605

SEISMIC LOADS
Per CBC, Section 1613

Page 192 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 10

Page 10 ends

SEISMIC LOADS DESIGN FACTORS
(PER GEOTECHNICAL REPORT)
Ss 1.83g
S 1 0.68g
SDS 1.32g
SD1 1.34g
Site Class Default
Risk Category IV
Importance Factor, I 1.5
F. MATERIAL PROPERTIES

1. Concrete: All Structural concrete mixes shall be Type II/V cement. All structural concrete shall have a minimum compressive strength at 28 days as follows:

CONCRETE
Foundations f’c = 4,000 psi minimum (145 pcf)
Concrete on metal
decks
f’c = 3,000 psi minimum (115 pcf)
Slab -on-Grade f’c = 4,000 psi minimum (145 pcf)
Columns, Slabs,
Beams & Shea r
Walls
f’c = 4,000 psi minimum (145 pcf)
(145 f
)

2. Structural Steel: All Structural steel shall be ASTM A992, Grade 50, unless noted otherwise.

STRUCTURAL STEEL
Steel Angles and
Channels
ASTM A 992, Grade 50 (Fy = 50 ksi)
Structural Tubes
(Rectangular and
Round)
ASTM A500, Grade C (Fy = 50 ksi)
Structural Pipes ASTM A53, Grade B (Fy = 35 ksi)

Page 193 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 11

Page 11 ends

BOLTS
Structural Bolt Bolt connections shall be A325X bolts
unless noted otherwise.

Gravity Column
Anchor Bolts
ASTM F1554, Grade 36
Seismic Column
Anchor Bolts
ASTM F1554, Grade 55

ELECTRODE STRENGTH
E80XX (Reinforcing Steel)
E70XX (Structural Steel)

END OF STRUCTURAL SYSTEMS SECTION
005 BUILDING EXTERIOR
A. EXTERIOR WALL S

1. Exterior walls shall conform to structural engineering criteria for framing . All framed exterior wall s shall have full thickness batt insulation with 1" foil faced polyiso continuous insulation (CI) with 16 GA Zee girts with 5/8" exterior gyp sheathing at the exterior wall face , or equal. Exterior wall assemblies shall have R21min insu lation.

2. CMU wall construction b asis of design:
a. Manufacturer: Orco Block
b. Product: 8x4x16 Shot Blast Block
c. Finish: Indio Gray

3. CMU wall mounted signage:
a. 10” high metal pan channel letters for building identification . b. Color: Black Stone (MP33348) by Matthews Paint Company.

4. Exterior Plaster. Design based on smooth texture applied over metal lath.

Plaster system basis of design: Parex Armourwall 300 Krak -Shield with WaterMaster a. WRB : WeatherSeal Spray & Roll -on
b. Plaster Slip Sheet : Building paper, JumboTex 60 min. c. Base Coat : Parex Fiber -47
d. Admixture : Parex Adacryl
e. Primer: Parex PrimeShield
f. Coating : Parex DPR Coating
g. Finish : Parex Image Smooth (VE Alternate - Parex DPR Standard Finish 533 Sand Smooth.) h. Paint Color: Reserved White (SW7056 ) by Sherwin Williams . i. System Warranty: 10 years min.

Page 194 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 12

Page 12 ends

5. Aluminum window wall & storefront system s. Factory finish Arcadia. Pre-finished frame color: (AB -8) Black.
a. Glazing ( GL -1) basis of design : High performance Low -E insulated glazing (1” thick) : U=0.29, SHGC=0.24, Viracon VZRE1 -46 or similar.
b. Storefront System basis of design : Arcadia System AFG451T (2”x4 1/2” Offset Glazing) c. Operable Casement and Fixed Window system basis of design : Arcadia System T200 E.

B. ROOF

1. Roofing assembly basis of design is metal roof over roof underlayment over the roof deck assembly . a. Manufacturer: AEP Span Span -lok with SpanSeam 180 O Seam, 12” coverage, 22 GA , b. Color: Cool Matte Black ,
c. Finish: Fluropon.
d. Roof underlayment: AEP Span “Underlayment HT”,

2. Roof mechanical wells: Fully adhered single -ply PVC roof over roof deck assembly . Roof covering Fire Resistance Classification: Class A. California Cool Roof System insulation thermal value (R) minimum of 30 using rigid insulation . Sarnafil G410-18 Feltback fiberglass reinforced membrane .

3. Manufacturer will supply to the owner a 30 years non -dollar limit edge warrantee. Warrantee must be non-pro-rated and must cover all labor and all material installed from the deck up.

4. Flashing, fascia, gutter assembly and miscellaneous roof metals to be prefinished to match Black Stone (MP33348) by Matthews Paint Company.

5. Min R value at roof: R30
C. DOORS/FRAMES

1. Exterior Doors
a. Entrance doors with sidelight are a 8’-0” tall aluminum storefront window system with 1" insulated glazing .
b. Entrance doors to be pre -finished 8’-0” tall aluminum framed doors, with wide stile (5” wide) c. Fire Apparatus Bay front and rear doors shall be motorized sectional steel doors with Lift Clearance Track , prefinished ( equal to Overhead Door Corp. Model 521 with SolarBan 70XL Argon Filled glazing ).
1) Controls for the doors shall be installed in common control panels with controls at two locations for parallel control arrangement. Front doors shall have both individual controls and a single button to open both front doors simultaneously. 2) Motor shall be equal to Overhead Door Corp. Model RSX with the fastest available opening speed for front App Bay doors.

2. Interior Doors
a. Interior doors to be 8’-0” tall aluminum knock down frames with solid -core, flush wood, custom grade, closed -grain hardwood veneer face with clear sealer. b. Knockdown door frames to be clear anodized finish.
c. Sidelites at interior doors shall have ¼” clear tempered glazing , set in aluminum knock down frame, to match door frames.

3. Door Hardware
a. All door hardware shall meet ADA requirements and shall have a brushed aluminum finish or satin chrome finish as available on each item .
b. All exterior entrance doors shall have card reader s for access control. c. Doors in stipulated STC rated walls shall be provided with automatic door bottoms.

END OF BUILDING EXTERIOR SECTION

Page 195 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 13

Page 13 ends

006 BUILDING INTERIOR
A. GENERAL DESCRIPTION

1. The building will be designed in accordance with the Essential Services Seismic Safety Act and is classified under Risk Category 4. All detailing for ceilings, millwork, partition types, and equipment installation will be designed to comply with the requir ed increased importance factor (similar to Healthcare or DSA project, not a typical Office project).

2. All interior walls shall be 5/8” Type ‘X’ gyp board with level 4 painted finish, over 4” metal studs typically, unless noted otherwise.
a. Provide cement backer board at tile installations. If interior partitions are full height, studs & gypsum board to be on both sides full height, with sound attenuation insulation. b. Provide moisture-resistant gypsum board in restrooms, shower rooms, and decontamination room where tile is not specified .
c. At all Corridor/Hallway walls and other high -traffic locations, gypsum board shall be high - Impact type to 8’ -0” min. Corners to be square with corner bead and corner guards to be provided as noted on the Finish Plan .
d. Dorm rooms shall be separated from other spaces by providing wall and ceiling construct ion with min 50 STC rating.

B. FLOORING FINISH MATERIALS

1. Polished Concrete (PC -1):

Location: Dorms, Day Room, Laundry, Kitchen , All Offices, Storage Rooms , Corridors , Restrooms.

Specification Requirements: CPC (Concrete Polishing Council) Aggregate Exposure: B .

CPC Finish Gloss Finish: Satin
Provide PROSOCO "Consolideck System", or equal.

DCOF (wet) : 0.42 min

2. Polished Concrete (PC -2):

Location: Apparatus Bays , Turnout Gear, Workshop, Medical Storage.

Specification Requirements: CPC Aggregate Exposure: ACPC Finish Gloss Finish: Flat Provide PROSOCO "Consolideck System", or equal.

DCOF (wet): 0.42 min

3. Sheet Resilient Flooring (RF -1):

Location: Shower s / Decontamination
Specification requirements: Sheet Width: At least 78 inches wide, Thickness: 0.08 -inch (2.0mm) and

0.12-inch (3.0mm) Shore A Hardness: At least 85, when measured in conformance with ASTM D 2240. Color: Product Options indicated on the Drawings or selected by the Architect. Seaming Method: Heat welded. Weld Rods: Manufacturer’s standard solidified adhesive welding rod. Base:

Integral flash cove. Finish: Equal to Altro Aquarius Wet Room Flooring.

4. Rubber Sports Flooring (RB -1):

Locations: Weight Room
Specification requirement: 24” square x 3/8” thick 2/3 of total area. Equal to Johnsonite Triumph sports flooring.

5. Sealed Concrete (SC -1)
Location s: Electrical Room, Fire Riser, and Air Compressor .

Page 196 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 14

Page 14 ends

Specification requirements: Concrete sealer shall be a water -based non -staining dissipating translucent resin conforming to ASTM C309, Type 1, Class B , and ASTM C1315, Type 1, Class B Provide Euclid Chemical “Super Aqua -Cure Vox ", or equal.

6. Static Dissipative Flooring with Electrical Grounding (SDT) :

Location : MDF.

Specification requirements: Armstrong Excelon SDT 12” x 12”.

C. BASE TYPES

1. Everywhere U.N.O. (B -1)- 4” rubber cove base

2. Apparatus Bays and Turnout (B -2) - 4” Metal cove base

3. Showers / Restrooms (B -3) - 4-6" coved / bullnose tile base D. WALL FINISHES

1. Eggshell - Gloss Paint (P -1, P-2, P-3) TYP – Eggshell finish , typical; allow for ( 2) accent colors. Dark wall colors to have Level 5 Finish, all other walls Level 4. Semi -gloss paint at Restrooms. Gloss paint at trim.

2. Porcelain Wall Tile (T -1) – Kitchen –Tile at backsplash, see finish plan for locations . Mfg: Cross ville, Series: Size: 4” x 16”.

3. Wall Protection Systems (WP -1) - at Apparatus Bay and Turnout Gear walls. Inpro, Koroseal or C/S Group Acrovyn or equal. 4” to 48” AFF. Include all trim pieces for installation.

4. Shower Wall Panels (WP -2):

Locations: Restrooms / Shower s - 8’-0” high at all walls. Altro Prism Decorative S hower Walls. Trim per manufacturer.

5. Mirrors:

Fitness room –starting at +4” to +8’ -0” on one (1) wall.

Corner Guards (CG) – Provide at each location per plan - 2”x2” Stainless Steel corner guards to 8’ -0” high.

6. Acoustical Wall Paneling (AWP -1)– 1” thick Upholstered wall Treatment in the Weight Room and Day Room. Specification by Fabritrak or equal.

7. Janitor closet and Decontamination (FRP) – Fiberglass reinforced plastic wall protection panels at all walls, unless otherwise noted. Provide full height.

E. CEILING FINISHES

1. ACT -1 Acoustical Suspended Ceiling System:

Location : Per Plan
Specification requirements: Moderate acoustical performance such as Armstrong Fine Fissured or USG Mars, 2’x4’ with 15 /16” Suspension grids at 10’ -0” high. All walls will penetrate grids.

2. Exposed Metal Deck:

Location : Per Plan

Page 197 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 15

Page 15 ends

Specification requirements: Paint all exposed elements white

3. GYP -1 Gypsum Board Ceilings and Soffits:

Location : Per Plan
Finish is eggshell paint, match P -1.

4. GYP -2 Water and Mold Resistant Gypsum Board:

Location : Per Plan (at Restrooms & Showers , and other wet areas ) Specification requirements: Finish is semi-gloss paint, match P -1.

F. CASEWORK

1. Kitchen 104:
a. Wood base , upper and tall cabinets, stainless steel countertops with front edge lip to catch water and integral backsplash. Combination adjustable shelves and storage drawers, and custom pull out trash hardware. See Floor Plan for additional casework information.

2. Laundry/Janitor 108:
a. Plastic laminate all base and upper cabinets, solid surface countertops with front edge lip to catch water and integral backsplash. Combination adjustable shelves and storage drawers.

3. Non-rated Corridor 107 :
a. Plastic Laminate all base and upper cabinets, Plastic Laminate Tops. Combination Adjustable shelves and storage drawers.

4. All restrooms:
a. Restroom countertops , Solid surface with undermount porcelain sink and removable plumbing shield.

5. Dorms 112, 113, 114, 115, and 116:
a. Plastic laminate countertop and tall storage closets with clothing rod and adjustable shelves.

G. RESTROOM ACCESSORIES

1. Restroom accessories:
a. Bobrick or eq.
b. Full WIDTH MIRRORS AT SINKS .

2. Phenolic shower benches - ACCESSIBLE AND STANDARD, SHOWER RODS/CURTAINS.

3. Utility shelves in each restroom. 5” x 16”.

H. FIXTURES AND EQUIPMENT

1. See Equipment plan and schedule , OFOI, CFCI as noted.

2. All residential appliances to be Energy Star Certified.

3. Metal Shelving: Per Plan
I. ARCHITECTURAL MISCELLANEOUS

4. Window shades: See locations on Equipment / Furniture Plan

5. Metal Shelving: See locations on Equipment / Furniture Plan

6. Marker Boards : See locations on Equipment / Furniture Plan

END OF BUILDING INTERIOR SECTION

Page 198 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 16

Page 16 ends

007 MECHANICAL SYSTEMS
A. GENERAL DESCRIPTION
The new mechanical systems for this project are anticipated to be all -electric and will primarily provide conditioning via variable refrigerant flow (VRF) heat recovery condensing units coupled with indoor fan coils serving the various zones.

1. Design Criteria/Design Calculation Guidelines
a. Project Location & Climate
Gilroy , CA
California Climate Zone: 4
Latitude: 37° North
Longitude: 121.6° West
Elevation: 194’
Cooling Design Temperature: 105°, 70° MCWB (0.1%)
Wetbulb Design Temperature: 72° (0.1%)
Heating Design Temperature: 28° (0.2%)
b. Indoor Design Conditions, Office Areas
People: 250 gross square feet per person
Lights: 0.60 watts/square foot
Equipment: 0.75 watts/square foot
Temperature: Summer – 74°F ( ± 2°F)
Winter – 70°F ( ± 2°F)
Humidity: No direct humidity control required.

Ventilation: 30% greater than required by CMC (ASHRAE 62.1) c. Indoor Design Conditions, Main Entry Lobby
People: 100 gross square feet per person
Lights: 0.70 watts/square foot
Equipment: 0.25 watts/square foot
Temperature: Summer – 74°F ( ± 2°F)
Winter – 70°F ( ± 2°F)
Humidity: No direct humidity control required.

Ventilation: 30% greater than required by CMC (ASHRAE 62.1) Exhaust: Space to be negative relative to adjacent spaces. d. Indoor Design Conditions, Dorm Rooms
People: 120 gross square feet per person
Lights: 0.40 watts/square foot
Equipment: 0.25 watts/square foot
Temperature: Summer – 74°F (± 2°F)
Winter – 70°F (± 2°F)
Humidity: No direct humidity control required.

Ventilation: 30% greater than required by CMC (ASHRAE 62.1) Interlock: Provide new window sensor for operable window to setback VRF fan coil temperature setpoint when window is in open position.

Page 199 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 17

Page 17 ends

e. Indoor Design Conditions, Weight Room
People: 100 gross square feet per person
Lights: 0.50 watts/square foot
Equipment: 0.25 watts/square foot
Temperature: Summer – 74°F ( ± 2°F)
Winter – 70°F ( ± 2°F)
Humidity: No direct humidity control required.

Ventilation: 30% greater than required by CMC (ASHRAE 62.1) Exhaust: Space to be negative relative to adjacent spaces.

Interlock: Provide door sensor for sectional door to reduce HVAC flow and temperature setpoints when door is in open position.
f. Indoor Design Conditions, Kitchen
People: 40 gross square feet per person
Lights: 0.95 watts/square foot
Equipment: 1.00 watts/square foot
Temperature: Summer – 74°F ( ± 2°F)
Winter – 70°F ( ± 2°F)
Humidity: No direct humidity control required.

Ventilation: 30% greater than required by CMC (ASHRAE 62.1) Exhaust: Space to be negative relative to adjacent spaces. g. Indoor Design Conditions, Dining / Day Room Area s
People: 35 gross square feet per person
Lights: 0.40 watts/square foot
Equipment: 0.50 watts/square foot
Temperature: Summer – 78°F ( ± 2°F)
Winter – 62°F ( ± 2°F)
Humidity: No direct humidity control required
Ventilation: 30% greater than required by CMC (ASHRAE 62.1) h. Indoor Design Conditions, Laundry /Janitor
People: 100 gross square feet per person
Lights: 0.45 watts/square foot
Equipment: 0.75 watts/square foot
Temperature: Summer – 74°F ( ± 2°F)
Winter – 70°F ( ± 2°F)
Humidity: No direct humidity control required.

Ventilation: 30% greater than required by CMC (ASHRAE 62.1) Exhaust: Space to be negative relative to adjacent spaces. i. Indoor Design Conditions, Decontamination
People: 100 gross square feet per person
Lights: 0.45 watts/square foot
Equipment: 0.75 watts/square foot
Temperature: Summer – 78°F ( ± 2°F)
Winter – 70°F ( ± 2°F)
Humidity: No direct humidity control required.

Ventilation: 100% OSA
Exhaust: 100% exhaust from space sized for 10 air changes per hour. j. Indoor Design Conditions, Turnout Gear

Page 200 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 18

Page 18 ends

Lights: 0.45 watts/square foot
Exhaust: 10 air changes per hour
Makeup Air: 100% of exhaust air, make -up from gravity intake hoods . k. Indoor Design Conditions, Apparatus Bay
Lights: 0.65 watts/square foot
Exhaust: Direct connections to truck exhaust (Plymovent system, or similar) Makeup Air: 100% of exhaust air, make -up from gravity intake hoods .

Heat: Provided by i nfrared heaters (Infratech WD -60, or similar ). l. Indoor Design Conditions, Restrooms
Lights: 0.60 watts/square foot
Exhaust: Greater of 100 cfm/fixture or 10 air changes per hour Makeup Air: 100% of exhaust air, make -up from adjacent spaces . Restrooms with door sweepers to have transfer boots with ceiling grilles on each side of the full height wall to allow transfer air .

2. Zoning
Each fan coil unit (zone) will be dedicated to a unique room, building orientation, floor level, and interior use. On average, there will be one fan coil zone per 1000 sf. Dorm rooms, offices, and unique uses will have dedicated fan coil zones. Up to three perimeter offices will be served by a single, shared fan coil zone.

3. Energy Conservation Calculations
The HVAC design shall utilize the above design criteria as a basis and shall also comply with the 202 5 State of California Energy Code California Code of Regulations (CCR), Title 24 and Building Standards. The performance based “whole building” model compliance approach shall be used.

4. HVAC Equipment
The building will be conditioned by a dedicated VRF heat recovery system with ducted and ductless fan coils throughout the various spaces. Building ventilation to be provided through an energy recovery ventilator unit. All of the mechanical equipment in the building is anticipated to be on emergency power .

Alternate mechanical system types will be considered for the building if the above noted design criteria and zoning conditions can be met.
a. Electrical service connections to HVAC equipment will be from dedicated HVAC electrical panels. b. VRF -1:The building will be conditioned by an approximately 12ton variable refrigerant flow (VR F) heat recovery condensing unit located on the ground near the electrical room. VRF -1, serving the building fan coil units, will consist of a single condensing module with R-32 refrigerant (Daikin, or similar). The module will be independently powered, anchored and externally isolated using neoprene waffle pads (Mason Super W, or similar) , and will have a master controller with BACnet compatibility.
c. ERV -1:The building will have ventilation and exhaust air provided by a 950 cfm energy recovery ventilator unit (Greenheck model ECV , or similar) located on the roof. Ventilation air ducts will be ducted through the building and be coupled with various VRF fan coils in each thermal zone throughout the space. ERV -1 will be paired with VRF-1fan coils. Return/exhaust air back to the unit shall be fully ducted in the ceiling space via l ow pressure return ducts to the dedicated outdoor air systems where it will pass over the heat recovery core before being exhausted. ERV -1 will include ECM supply and exhaust fans, heat recovery core, MERV 13 filtration, and BACNet controls. Unit should also be mounted on an acoustic vibration isolation curb (Vibrex VIC-EQ, or similar)

Page 201 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 19

Page 19 ends

d. VRF Fan Coils (VFC -1 to VFC -11): Each thermal zone in the new building will include a VRF fan coil (Daikin model FXZQ, FXMQ, FXAQ, or equal). The type of fan coil provided in each zone will depend on the requirements of the space – ceiling cassette type for small spaces requiring separate zone control, highwall type for utility spaces with no ceiling, and ducted fan coils for units for large spaces.

Each fan coil will have a ventilation air duct coupled with the unit, washable filter (cassettes), MERV 13 filter (ducted units with MERV 13 Air Filter and Cabinet Kit, or similar), factory integral condensate pumps for cassette & ducted units, field mounted condensate pumps for highwall units (Aspen DACA -CP1-1, or similar), 2-row cooling coil, and BACnet controls. e. Process Cooling Equipment (1-to-1 split systems) : Air-cooled mini split systems will provide 24/7 conditioning of MDF and Electrical rooms. Units to use R-32 or R-454B refrigerant. i. FC -1 / CU-1:Electrical 121 will be served by an approximately 3 ton highwall ductless fan coil unit (Daikin FTXV36AVJU9 / RXV36AVJU 9, or similar).
ii. FC -2 / CU -2: MDF 123 will be served by an approximately 3 ton highwall ductless fan coil unit (Daikin FTXV36AVJU9 / RXV36AVJU9 , or similar).
iii. FC -3 / CU -3: Decontamination 130 will be served by an approximately 4 ton 100% O/A ducted fan coil unit (Daikin FXMQ48MFVJU / RX TQ48TB VJU B, or similar). This unit will need to be updated to the equivalent R-32 unit as soon as it is available from the manufacturer.
iv. Condensing units will be located on the roof .
f. Refrigerant Leak Detect ion: Each VRF zone indicated on the plans shall have a VRF refrigerant leak sensor mounted on a wall within 12” of the finished floor level (Macurco model RD-VRF, or similar). g. Multi Port Branch Selector Boxes (BS): The building heat will be provided by the VRF system in conjunction with various BS boxes throughout the space (Daikin model BSQ , or similar). The BS boxes will be interlocked with the main VRF system and will have control boards to communicate with the VRF main controller .
h. Refrigerant Safety Shut-Off Boxes (SOV): The refrigerant piping branches of the VRF system will include safety shut-off boxes to limit the amount of potential R32 refrigerant released into the building in the event of a pipe leak in the system (Daikin model SVA , or similar). The SOV boxes will be interconnected with the main VRF system and will have control boards to communicate with the VRF main controller if they have closed due to leakage being detected . The quantity of SOVs required will be determined by the size of the rooms and the amount of refrigerant in each branch. i. Exhaust Systems:

1. EF -1:Dryer booster fan, approximately 80 cfm, will be provided for the dryer exhaust in the laundry room (Fantech DBF 4XLT, or similar) . Dryer to be controlled via a pressure sensor mounted in the ductwork.

2. EF -2: Rooftop exhaust fan, approximately 200 cfm, will be provided for the Turnout Gear exhaust (Greenheck CUE or similar).

3. EF -3: Rooftop exhaust fan, approximately 40 0 cfm, will be provided for the Decontamination room, restroom 131, and storage 128. (Greenheck CUE or similar).

4. EF -4: Rooftop exhaust fan, approximately 300 cfm, will be provided for the drying cabinet in the decontamination room. (Greenheck CUE or similar). Fan to be interlocked with drying cabinet.

5. Apparatus Bay Vehicle Extraction System (VEF -1): The apparatus bay will be equipped with a vehicle extraction system (Plymovent, or similar). The extraction system shall include the following:
(i) Roof mounted exhaust fan (Plymovent model TEV, or similar). Fan to be equipped with a weatherproof enclosure and pressure sensors for fan activation. (ii) A filter housing with MERV 8 pre -filters and 95% final filters

Page 202 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 20

Page 20 ends

(iii) One long straight rail in each apparatus bay to run the full length of the bay outfitted with 2 hoses per rail, crab return assemblies, balancer, saddle & hose loop for 25ft 4ӯ hose, pneumatic fill valve and grabber nozzle and complete pneumatic circuit for pa ssive release auto crab/trolley return with safety switch. System to be designed for two apparatuses stored in tandem in each bay with the ability to add a third hose to each rail to be able to store three tandem or remove a hose for a single long app aratus. (iv) Control panel provided to control the vehicle exhaust system. Controls to allow for manual or automatic control of the fan. Control box to also include an alarm device that can be used for status control of the airflow in the exhaust system. j. Gravity Intake Units:

1. IH-1: Rooftop gravity intake hood, approximately 2,000 cfm, will be provided for apparatus bay exhaust air makeup (Greenheck GRSI or similar).

2. IH-2: Rooftop gravity intake hood, approximately 200 cfm, will be provided for the Turnout Gear exhaust air makeup (Greenheck GRSI or similar).

3. IH-3: Rooftop gravity intake hood, approximately 200 cfm, will be provided for the Decontamination room exhaust air makeup (Greenheck GRSI or similar). k. Infrared Heaters (IR-1 to IR-6):

1. Infrared heaters to be provided in apparatus bay along sides of apparatus bay (Infratech WD - 60, or similar). A total of 6 heaters anticipated (3 on each side) , equally spaced across the length of the bay, and mounted at 12ft above the finished floor. l. Ceiling Fans:

1. CF -1: Ceiling fan, 60” diameter, will be provided for the Weight Room ( Big Ass Fan Haiku L , or similar). Ceiling fan to include wall controller.

5. HVAC Equipment Additional Notes
a. The fire station building is considered an essential facility and will have the majority of the mechanical systems on emergency power.
b. HVAC testing, adjusting and balancing agent will be certified by AABC or NEBB. c. HVAC systems commissioning will be provided in accordance with California Energy Code.

6. HVAC Ductwork and Accessories
a. Comply with SMACNA HVAC Duct construction Standards, Metal and Flexible (SMACNA), Fourth Edition, 2021 and NFPA 90A.
b. Ductwork shall be galvanized steel with G -90 zinc coating, ASTM A 653, minimum 26 gauge, unless otherwise noted. Assume plenum return air system with limited return air ductwork. c. Concealed HVAC supply air ductwork shall be insulated with mineral fiber insulation and ASJ jacket per California Energy Code standards.
d. Duct silencers shall be provided at main supply and return /exhaust to each ERV unit. e. Combination fire/smoke dampers, integrated with area -wide fire alarm, will be provided as required at occupancy separations.
f. Flexible ductwork shall be provided for final 5 -foot connection to supply air diffusers.

Page 203 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 21

Page 21 ends

7. Grilles and Diffusers
a. General ceiling supply diffusers to be steel, plaque faced. Ceiling mounted return and exhaust grilles to be steel, louver face. Diffusers and grilles to be compatible with ceiling and wall conditions, field painted where required to match custom wall colo rs.
b. Grilles and diffusers located in locker rooms, restrooms, and shower rooms to be aluminum. c. Supply diffusers in exposed ceiling areas to be spiral duct mounted type. Return air in exposed ceiling areas to be minimized to large open -ended ducts covered with wire mesh. d. Air distribution in all lay-in T-bar ceiling areas will be plaque face type. Air distribution in hard lid areas will be linear diffusers (Price, Titus, Krueger or equal).

8. Volume Dampers
Manual volume dampers will be provided in branch ducts to each diffuser. In areas with hard ceilings and non - accessible areas, remote balancing damper controllers (Young Regulator EBD, or similar) will be provided at each inlet or outlet in lieu of manual dampers.

9. Refrigerant Piping and Accessories
Type L copper tubing with soldered joints shall be provided for refrigerant piping distribution. Refrigerant piping shall be insulated with 1” elastomeric foam pipe insulation.

10. HVAC Controls
a. A Building Management System (BMS) is not anticipated to be utilized in the facility and all units are to be provided with programmable thermostats. Equipment to be provided with BACnet provisions to accommodate potential future BMS installation.

11. Seismic Restraints
HVAC ductwork and pipe support to comply with SMACNA Seismic Restraint Manual, Guidelines for Mechanical Systems, Third Edition 2008.

END OF MECHANICAL SYSTEMS SECTION
008 PLUMBING SYSTEMS
A. OVERVIEW
The plumbing scope of service for this project is to provide complete plumbing design for a new single -story fire station. The new building shall be provided with complete domestic hot and cold water, sanitary soil, waste, vent, and storm drainage piping systems.

B. CODES AND GUIDELINES
All aspects of the design shall follow the requirements of the current California Plumbing Code and CalGreen standards for plumbing fixtures. Additional Regulations and Standards shall include as a minimum:
• ANSI ‐ American National Standards Institute Inc.
• ASHRAE ‐ American Society of Heating Refrigerating and Air Conditioning Engineers Handbooks
• ASME ‐ American Society of Mechanical Engineers Guidelines and Standards • AWS ‐ American Welding Society
• CAL/OSHA ‐ California Occupational Safety and Health Administration • CBC ‐ California Building Code
• CCR ‐Title 24 California Code of Regulations
• CFC ‐ California Fire Code

Page 204 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 22

Page 22 ends

• CPC ‐ California Plumbing Code
• NFPA ‐ National Fire Protection Association Guidelines and Standards • SFM ‐ California State and local Fire Marshal
C. PLUMBING FIXTURE Water Efficiency
Plumbing fixtures installed in the project will meet or exceed the water efficiency requirements of the 2025 California Green Building Standards (CalGreen) code. The maximum water uses for each indoor plumbing fixture type installed in the project shall be:
• Water closets: 1.28 GPF
• Urinals: 0.125 GPF
• Lavatories: 0.5 GPM
• Sinks 1.8 GPM
• Showers 1.8GPM
D. ACCESSIBILITY
Accessible plumbing fixtures in each restroom will comply with the requirements of the Americans with Disabilities Act (ADA) and all California requirements for accessibility.

E. CALIFORNIA AB 1953 COMPLIANCE
Potable water system fixtures, materials, valves, and appurtenances to be in compliance with California Assembly Bill 1953, which limits the allowable lead content in certain domestic water system components.

F. SITE UTILITIES
Refer to “003 – SITE PLANNING” for site domestic water, sewer, and storm drain basis of design.

G. PLUMBING PIPING MATERIALS

1. DOMESTIC WATER PIPING
Piping within the building and above grade shall be Type "L" ASTM B88, hard drawn copper tubing with wrought copper sweat fittings per ANSI B16.18 and B16.22. Below grade piping outside of the building within five feet (5') of the foundation shall be Type "K" ASTM B88, hard drawn copper with wrought copper sweat fittings per ANSI B16.18 and B16.22. Below slab piping shall be Type "K" soft annealed copper tubing with no fittings below the slab.

2. SANITARY SOIL, WASTE PIPING
Soil and waste piping within the building and outside within five feet (5') of the foundation shall be no -hub cast iron pipe and fittings conforming to CISPI Standard 301 -04 or ASTM A -888-04 with Heavy -Duty No-Hub Couplings conforming to ASTM C -1540 and AS TM C-564.

Plumbing fixtures above grade shall be drained by gravity to the site sanitary drainage system. Gravity drainage system shall maintain a minimum slope down of 2% in the direction of flow except where indicated otherwise.

3. SANITARY VENT PIPING
Same as specified for sanitary soil and waste piping except with Standard Duty No -Hub Couplings conforming to CISPI Standard 310 and ASTM C -564.

Vents from fixture traps shall be extended through and terminate a minimum 12” above roof and shall be located a minimum of 10 feet from building outside air intakes. Exposed vent piping shall be Schedule 40 galvanized steel pipe, ASTM A53.

Page 205 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 23

Page 23 ends

4. FACILITY STORM DRAINAGE PIPING
Storm drain piping within the building and outside within five feet (5') of the foundation, and overflow drain piping within the building shall be no -hub cast iron pipe and fittings conforming to CISPI Standard 301 -04 or ASTM A-888-04 with Heavy -Duty No-Hub Couplings conforming to ASTM C -1540 and ASTM C -564.

Roof drains, overflow drains and leaders shall be designed for a minimum of 2‐inch per hour rainfall unless directed otherwise by the local building authority. Overflow drain piping shall "daylight" to the building exterior and be provided with downspout covers as indicated on the plumbing plans.

Perimeter Gutters and Downspouts will be provided as required, materials to be determined. Coordinate with architectural plans.

5. CONDENSATE DRAINAGE PIPING
Condensate drain piping shall be Type "M" ASTM B88, hard drawn copper tubing with wrought copper sweat fittings.

6. INDIRECT WASTE
Indirect waste piping shall be Type ”L” ASTM B88, hard drawn copper tubing with wrought copper fittings as specified for water piping.

7. PLUMBING INSULATION
Piping for service hot water systems shall be insulated with preformed fiberglass pipe insulation with all service jacket, per California Title -24 standards.

H. PLUMBING FIXTURES

1. Plumbing fixtures by Sloan, Zurn, Kohler, American Standard or approved equal.

2. Water closets shall be water efficient 1.28 GPF manual flushometer valves, wall mount vitreous china with siphon jet action, elongated bowl with open front seat, in both ADA and non -ADA compliant configurations as applicable.

3. Restroom lavatories shall be undermounted vitreous china with manual 0.5 GPM faucet, with prewrapped trap and supply covers, loose key stops, and rigid supplies. ADA compliant.

4. Kitchen area sinks shall be undermount stainless-steel ADA single bowl for use with solid surface countertops, HW/CW with 1.5 GPM kitchen faucet with prewrapped trap and supply covers, loose key stops, rigid supplies, and garbage disposal.

5. Kitchen areas to be provided with connections for dishwasher, filtered water dispenser and coffee machine(s).

6. Icemaker supply box with shut -off valve will be provided at all refrigerators.

7. Interior bottle fillers shall be stainless steel, refrigerated and filtered with recessed compressor.

8. Showers shall be recessed mount, thermostatic mixing valve actuation, with HW/CW, 1.8 gpm showerheads, ADA compliant showers to include in addition a fixed showerhead and control valve. Floor drains shall be cast iron body with flashing collar and nickel -bronze adjustable strainer.

9. Service sinks shall be free standing stainless steel with HW/CW wall mount faucet with integral vacuum breaker, hose, pail hook, and vinyl rim guard.

10. Floor drains with trap primers shall be provided in all restrooms and laundry / decontamination rooms.

11. Provide a wall mounted hose bibb in restrooms for wash down.

12. Provide floor drains with trap primers in the Laundry Room and the Decontamination Room.

13. Provide floor sinks with trap primers at Decontamination Room and as indicated on plans and as required.

14. Provide two -compartment stainless steel, floor-mounted utility sink HW/CW with 1.5 GPM with goose neck faucet with wrist blade handles in Decontamination Room.

15. Provide additional one -compartment stainless steel, floor-mounted utility sink, HW/CW with 1.5 GPM with goose neck faucet with foot pedal activation located adjacent to Decontamination Room.

16. Provide wall mounted clothes washer supply box in the Laundry Room and an indirect drain to a floor trough drain with lint trap at extractor in the Decontamination Room.

Page 206 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 24

Page 24 ends

17. Provide downspout covers to the overflow drain pipe termination. Coordinate with architecture the height location of the fixtures.

18. Provide trench drains at Apparatus Bays running the length of the bay as indicated on plans. Coordinate exact length and location with Architectural design. P -traps shall be provided with a trap primer connection.

Drainage from Apparatus Bay trench drain s shall extend to the site and discharge to a Sand and Oil Interceptor and Sample Box before continuing to the city sanitary sewer connection.

19. Provide icemaker with floor sink, as indicated on plans, adjacent to the Apparatus Bay .

20. Floor sinks will be provided in the Air Compressor room and the ice machines .

21. Exterior hose bibbs around the building shall be recessed lockable box type with integral vacuum breaker.

Rooftop hose bibbs shall be free standing with integral vacuum breaker.

22. Provide hub drain with electric trap primer will be installed for fire riser test drain.

23. Provide hose reels with quick disconnect adaptors. Hose reels to be located in the Apparatus Bay and mounted at a minimum 9’-0” above finished floor.

I. PLUMBING EQUIPMENT

1. Domestic Water Heating
a. This project will include a tank type electric water heating system with expansion tank, drain pan and drain to receptor located in the Laundry/Janitor room . Hot water will be controlled to a supply temperature no more than 140 degrees Fahrenheit to serve all lavatories, sinks, and service sinks. Point of use thermostatic mixing valves located at the lavatories will provide tempered water. The hot water system will be fully circulated with a pump interlocked to an aquastat allowing for control of the circulating system. Water heater(s) shall be a A.O. Smith or approved equal. b. Electric instantaneous point of use water heaters may be provided as required to serve remote fixtures requiring hot water. Water heaters shall be Eemax, Chronomite or equal.

2. Compressed Air System:
a. The Air Compressor shall be sized per owner equipment requirements. DBE shall provide the Air Compressor, compressed air piping to equipment and provide a floor sink for indirect drainage from the Air Compressor. All compressed air piping shall terminate with quick disconnect adaptors per owner specified connection type. Refer to plumbing plans for specification

3. Domestic Water Anti -Scale Filtration
a. The anti-scale shall be sized per GPM demand of the building. Domestic water to be routed through the anti-scale system prior to the final plumbing fixture location.

J. PIPE TESTING

1. All piping systems shall be tested in accordance with the applicable service as indicated in the California Plumbing Code.

2. All new water piping shall be disinfected/sterilized as directed by the California Plumbing Code.

END OF PLUMBING SYSTEMS SECTION

Page 207 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 25

Page 25 ends

009 ELECTRICAL SYSTEMS
A. MAIN SWITCHBOARD MSB
A new MSB at 800A -120/208V -3PH-4W shall be located in the main electrical room and served from the PG&E transformer located on the site.

B. EMERGENCY GENERATOR
A new 350kW emergency generator with 2000 gallon base mounted fuel tank shall be located on the site. The generator will serve as emergency back -up for the entire building for 72 -hours. The generator will serve the building through an 800A automatic transfer switc h and emergency distribution board.

The generator will be located outdoors in a weatherproof enclosure , sound attenuating muffler system and diesel particulate filter . The base fuel tank will hold enough diesel fuel to power the station for three days. T he basis of design is Rehlko Generators.

Comply with federal (EPA), state, and local regulations applicable at the time of commissioning; include factory emissions certification with submittals.

C. FUTURE SOLAR READY
The MSB will have a section reserved for Solar Readiness and Battery Energy Storage System (BESS) connection dedicated to Solar PV .

D. POWER

1. GENERAL REQUIREMENTS
a. Multiple power and lighting panelboards will be provided as required. Lighting loads will be connected at 120 volts, single-phase, HVAC /Plumbing loads will be connected at 120 volts, single-phase or 208-volt, 3- phase, Receptacle loads will be connected at 120 volts, single -phase. b. Typical receptacles, switches and wiring devices to be specification grade, white in color, decora type with specification grade stainless steel faceplates.
c. Dedicated GFI receptacles shall be provided in restrooms and on the exterior of the building. d. EV charging stations will be based on the number of parking spaces provided on site .

E. LIGHTING

1. GENERAL REQUIREMENTS
a. Lighting system shall be designed to comply with the California Energy Code and Title 24. b. All lighting shall conform to the latest IES Recommended Practices (RP s) and IES G -1-22 “Guide for Security Lighting for People, Property, and Crit ical Infrastructure”. c. Lighting shall conform to City of Gilroy Zoning Code, including the Glen Loma Ranch Specific Plan, and Resolution No 2014-19; and amendments to the California Building code, including Ordinance 2025 -06. d. All fixtures shall be dimmable LED.
e. All illumination to be on emergency power.

2. INTERIOR LIGHTING
a. General Requirements
1) Color Rendering: 90 CRI minimum
2) Color Temperature: 3500K typical, with exception to specific fixtures where warmer color temperatures are beneficial to night -time activities such as sleeping . 3) Controls: All interior spaces shall have on/off/dimming controls . Where multiple layers of light are provided, individual zone control shall be provid ed for flexibility. Controls shall be accessible

Page 208 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 26

Page 26 ends

to occupants, except in publicly occupied spaces such as lobbies, where controls shall be accessible to authorized personnel only.
b. Scope / Design Considerations:
1) Offices, Conference Rooms, Corridors & Typical Spaces Throughout: 2x2 or 2x4 troffers. 2) Utility Spaces: Troffers or utility strip lights.
3) Lobbies/Reception: Fixtures shall be vandal resistant. Design shall include vertical illumination at specialty signage/wall graphics.
4) Dorms: Lighting design shall include a minimum of (2) layers of light, including a reading light with local switch control, and general overhead lighting . General overhead lighting shall provide sufficient illumination per IES recommendations, while balancing budget and visual comfort (either through a low UGR rating, indirect illumination , or other methods to soften the lighting and balance vertical and horizontal illumination).
5) Restrooms/Showers : Fixtures shall be shower rated, with dead front trims where applicable. 6) Dining/Kitchen : Design shall include direct and indirect illumination with multi -zone control.

Design shall also include decorative pendant over kitchen island. 7) Weight Room : Design shall include direct and indirect illumination with mutli -zone control. Direct fixtures shall not be located directly above fans and fixtures shall be placed such that they do not cause str obing .
8) Apparatus Bays : High volume linear fixtures or linear wraparounds . Fixtures shall be laid out between apparatus bays such that there is ample vertical illumination on the sides of fire trucks and equipment.
9) Decontamination : Fixtures shall be sealed and wash-down rated.

3. EXTERIOR LIGHTING
a. General Requirements
1) Color Rendering: 80 CRI minimum
2) Color Temperature: 3000K
3) Heights: Fixtures shall be at a maximum height of 20’ per City of Gilroy, Glen Loma Ranch Specific Plan, and Resolution 2014 -19.
4) Light Pollution: Design shall be sensitive to surrounding residential neighborhood. In addition to complying with all applicable CalGreen requirements, fixtures shall incorporate back -light, uplight, and glare control/shields where relevant to minimize light trespass and pollution.
b. Illuminance and Control
1) Lighting design shall be capable of providing a maintained average illuminance of 5fc with an average -to-minimum uniformity ratio not greater than 3:1 per IES standards. 2) Exterior illumination shall be controlled by timeclock and/or photosensors such that lights are automatically turned off during the day, and automatically turned on at night. 3) Poles shall be equipped with occupancy sensors for additional energy savings and to reduce light pollution within the neighborhood when the site is unoccupied. 4) Control shall be designed such that site lighting has a minimum of three settings. a) Emergency Response: During preparation and response to an emergency call for service, parking and station exit area lighting shall be raised to full output, providing the 5fc maintained average.
b) Stand -by Mode: Five minutes after all responding personnel and equipment have departed and the building is secured, illumination shall return to stand -by mode, to

Page 209 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 27

Page 27 ends

provide 1fc along paths of travel and egress, and a minimum of 0.5fc in parking and roadway areas. Stand -by mode shall be the primary mode when the site is occupied during night -time hours.
c) Unoccupied : After occupancy sensors sense 20 minutes of vacancy, lighting output shall be reduced to 50% of stand -by mode. Occupancy of the exterior site shall automatically raise the illumination back to Stand -by Mode levels, except when the Emergency Response mode is triggered.
c. Scope
1) Parking/Roadways: 20’ max, full-cutoff, dimmable poles with integral occupancy sensors 2) Pedestrian Paths: 40” bollards and/or step lights.
3) Entry Stairs: Integral handrail lighting, with integral driver post. Lighting and rails to be specified as one complete system (handrail, lighting, posts, and drivers provided by one manufacturer).
4) Entry Doorway: Recessed 3” downlight.
5) Flag Poles and Tree Accents : Ingrade, vandal and impact -resistant, adjustable uplights . 6) Wall Area Light s: Vandal, impact -resistant area lights. 7) Signage: Integral signage lighting by signage manufacture r. (Note: address number must also be illuminated).

END OF ELECTRICAL SYSTEMS SECTION
010 STRUCTURED CABLING SYSTEM
A. Telecommunications Service Entrance Room (MDF)

1. One (1) MDF room shall be provided per plan. The MDF room shall be air-conditioned and humidity controlled 24/7/365 and shall be equipped with a dedicated 100 Amp panel board (or higher depending on other equipment the department will be installing). The MDF room shall have a minimum of (3) 120v dedicated 20 -amp circuits and (2) 208 -volt 30 -amp circuits routed to outlets attached to overhead ladder tray (outlet types TBD). (2) 3” conduits will be installed from the MDF room to the roof with a weather head, in addition one 2” conduit to roof with weather head connection for GPS repeater system. (2) 2” conduits shall be installed over the apparatus bay to facilitate low voltage cabling pathways from one side of the bay to the other in both .

2. Provide (2) 4" conduit to from tel. company POC pull box and (2) 3" conduit from cable provider POC pull box to MPOE (MDF). Coordinate with local providers engineering departments for pathway requirements.

3. MDF room will have two walls covered with ¾” fire rated plywood finished and painted on one side.

4. The telecom will be designed using UL listed 19” X 7’ equipment racks with minimum 10” wide vertical cable management on both sides to hold patch panels and City of Gilroy provided data switch equipment . Voice and data terminations shall be on rack mounted patch panels. Panels to RJ45 patch cables will be used to connect data ports to switches. Patch cables will be used to connect voice ports to phone switch tail connections. Multi -pair voice grade cable will be run from the rack mounte d panels for cross -connection of phone switch tails and phone backbone cables.

CATV equipment will also be included in the racks. Overhead UL listed Telco style ladder tray will be used to hold and distribute all cables entering or leaving the room.

Page 210 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 28

Page 28 ends

B. Signal Grounding System

5. An appropriate ground bus bar shall be designed for the telecom room with a #2/0 green -insulated copper ground conductor to be connected to the Main Building Ground and #6 AWG conductor to building steel per TIA 607 standards. All cabinets, racks, conduits, AC units, UPSs, and electronics shall be bonded to the ground busbar with dedicated #6 AWG solid conductor green insulated wire and 2-hole compression lugs.

C. Cable System

1. Appropriately sized conduits shall be used to transition over closed gypsum board ceilings. Outlets for telecom service will have 1 ¼” conduits stubbed 6” above accessible ceiling for the horizontal cables. In inaccessible areas, conduits shall be designed to go directly to the cable tray or to the telecom room depending on the exact circumstance. 3” or 4” EZ Path UL listed firewall penetration systems shall be installed where required for cable access through fire -rated walls.

2. Category 6 cables for voice and data using a Structured Cabling Solution per City of Gilroy standard shall be installed. Horizontal CATV cables will be RG6.

D. Horizontal Cabling

1. All horizontal data/voice and CATV cables shall originate from the MDF.

E. Wireless Access

1. The building shall be provided with interior and exterior wireless access coverage utilizing City of Gilroy standard wireless access points (WAP’s). Provide complete design, engineering, installation , and conf iguration of the wireless netw ork to ensure continuous and reliable coverage with strong signal strength throughout the ent ire secured ar ea and extending a minimum of 15 feet beyond the secure perimeter fenc eline.

F. Station Outlet Configuration

1. Typical outlet configurations shall be one voice and two data jacks. Alternate outlet configurations to be used based on type of space will be 1) one voice, two data and one coaxial jacks, 2) one voice, two data and two multi -mode optics, 3) Voice wall jack and 4) all data jacks. Future wireless access point locations shall be cabled each with (2) Category 6 cables to a ceiling mounted enclosure. Electronics will be provided by City of Gilroy /IT.

G. Structured Cable Warranty and Testing

1. All Category 6, Category 3 (voice feeder) and coax cabling shall be tested utilizing a Fluke DTX 1800 or equivalent. All Fiber Optic cables shall be tested utilizing Fluke Networks OFP -100 or equivalent.

Test results shall be provided to City of Gilroy via unedited softcopy version of LinkWare.

2. Design -Build Entity shall provide 25 -year System Warranty.

END OF STRUCTURED CABLING SYSTEM SECTION

Page 211 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 29

Page 29 ends

011 SECURITY SYSTEMS
A. ACCESS CONTROL SYSTEM

1. Provide access control card readers at all exterior door s into the facility . Provide access control card readers and a localized mechanical pushbutton lock (basis of design: Simplex 5000 Series) at site pass gates.

B. SECURITY VIDEO SURVEILLANCE SYSTEM

1. Provide a security surveillance system and include all equipment for a complete and operable system, including the required servers, video recorder, cameras, camera accessories, camera mounting accessories, camera onboard storage (SD/micro -SD card, if applicable), applications/programs, licensing configurations/programming .

2. Provide (8) exterior secu rity video s urveillance cameras . Confirm all camera locations with City .

3. Cameras are IP -based with category 6A cabling.

END OF SECURITY SYSTEMS SECTION
012 AUDIO -VISUAL
A. GOALS AND PROJECT REQUIREMENTS

1. The purpose of the basis of design is to provide the proposed description of the Audio -Visual systems design, engineering, installation, and start -up for a complete, fully operational Audio - Visual systems for the project addressing the design assumptions based on the following standards.

2. Technologies listed below are options for review and incorporated as required. a. Speakers in Day Room , with integral cabling to the monitor in the room. b. Speakers in Dining, with integral cabling to the monitor in the room. c. Speakers in Shared Office, with integral cabling to the monitor in the room. d. Speakers in Captain’s Office , with integral cabling to the monitor in the room.

B. APPLICABLE CODES AND STANDARDS GUIDELINES

1. California Electrical Code

2. INFOCOM - Avixa Audio – Visual Design Standards.

3. Accessibility requirements per California Building Codes – Chapter 11B Accessibility to Public Buildings, Public Accommodations, Commercial Building and Public Housing

END OF AUDIO -VISUAL SECTION
013 FIRE PROTECTION SYSTEMS
A. OVERVIEW
The fire protection systems shall be designed responding to the building plan diagrams and complying with the current version of NFPA 13, NFPA 14 and NFPA 24. This will be a design build process , and the scope will be addressed by the bidding Design-Build Entity and their subcontractors.

B. FIRE WATER SUPPLY
Sprinkler heads shall be as follows:

1. Sprinkler heads in suspended ceiling areas shall be pendent quick response sprinkler, white finish with adjustable semi -recessed white finish escutcheon . Head shall be in the center of the half ACP panel.

Page 212 of 256 ends

Basis of Design Narrative | City of Gilroy, Santa Teresa Fire Station | April 3, 2026 LPA Project No.: 33236 | Page 30

Page 30 ends

2. Sprinkler heads in gyp board or other non -suspended ceiling areas shall be quick response concealed pendent sprinkler with white or custom color cover plate to match adjacent ceiling surfaces as applicable. Sprinkler heads shall be installed align ed in each ceiling area.

3. Areas with no ceiling shall be provided with sprinkler coverage using brass finish upright quick response sprinklers.

END OF FIRE PROTECTION SYSTEMS SECTION
014 FIRE ALARM SYSTEMS
C. OVERVIEW
The building shall be equipped with a fire alarm system to notify occupants of smoke or fire detected in the building complying with NFPA 72 .

END OF FIRE ALARM SYSTEMS SECTION
015 FIRE STATION ALERTING SYSTEMS
A. OVERVIEW
The building shall be equipped with a fire station alerting system to notify the fire crew of emergency calls throughout.

1. The S tation Controller :
a. Locate t he controller in the MDF room and include a compatible amplifier and UPS for th is specific system.
b. Provide station controller expansion modules as required. c. Provide system to provide a signal to other Design -Build Entity provided systems including gas/fuel shut -off system , lighting control system .
d. Provide connection between controller’s line -level audio output and house audio amplifier , if applicable per owner AV requirements.
e. System shall send alerts to fire personnel ’s smartphones while off-site.

2. System components :
a. LED Message signs : Each side of each App Bay, entrances to App Bay s, Dining , Day Room, Kitchen, Shared Office, Captain’s Office, and Weight Room . b. Strobe Lights: Each side of each App Bay, Shared Crew Office, Weight Room, Workshop. c. Dorm Light: Each dorm room.
d. Speaker s, flush mount : Each occupied room .
e. Speakers, W eather-proof: App Bays, outside front and rear of App Bays and outdoor patio. f. System remote relay s: As required.

3. Design -Build Entity to provide the following for the complete system. a. Conduit
b. Back boxes
c. Cable trays .
d. Mounting fasteners .

END OF FIRE STATION ALERTING SYSTEMS SECTION

END OF DOCUMENT

Page 213 of 256 ends

408-780-7200 Office
60 South Market Street, Suite 1250
San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIORS

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com

PROJECT NUMBER
Submittal Date
70% SCHEMATIC DESIGN 03/10/2026
100% SD / BRIDGING DOCS 03/26/2026
33236

SANTA TERESA FIRE STATION
1330 WEST LUCHESSA AVENUE
GILROY, CA 95020
G0.00

COVER SHEET

Page 214 of 256 ends

11B-201.4 CONSTRUCTION SUPPORT FACILITIES. These requirements shall apply to temporary or permanent construction support facilities for uses and activities not directly associated with the actual processes of construction, including but not limited to offices, meeting rooms, plan rooms, other administrative or support functions. When provided, toilet and bathing facilities serving construction support facilities shall comply with 11B-213. When toilet and bathing facilities serving construction support facilities are provided by portable units, at least one of each type shall be accessible and connected to the construction support facilities it serves by an accessible route.

EXCEPTION: During construction an accessible route shall not be required between site arrival points or the boundary of the area of construction and the entrance to the construction support facilities if the only means of access between them is a vehicular way not providing pedestrian access.

TEL: 408/846-0277

PUBLIC WORKS, PROJECT MANAGER
NAME: CITY OF GILROY

CLIENT INFORMATION
CITY,STATE, ZIP: GILROY, CA 95020
ADDRESS: 7351 ROSANNA STREET
CONTACT: RYAN OSENTON E-MAIL: [email protected] TEL: 408/780-7200
NAME: LPA, INC.

ARCHITECT
CITY,STATE, ZIP: SAN JOSE, CA 95113
ADDRESS: 60 S MARKET ST #1250
CONTACT: CHARLIE WILLIAMS E-MAIL: [email protected] TEL: 916/287-2400
NAME: LPA, INC.

LANDSCAPE ARCHITECT
CITY,STATE, ZIP: SACRAMENTO, CA 95814
ADDRESS: 431 I ST #107
CONTACT: RITA FRINK E-MAIL: [email protected] TEL: 949/261-1001
NAME: LPA, INC.

CIVIL ENGINEER
CITY,STATE, ZIP: IRVINE, CA 92617
ADDRESS: 5301 CALIFORNIA AVE, SUITE 100
CONTACT: ANTHONY TSUI E-MAIL: [email protected] TEL: 925/371-5900
NAME: GEOCON CONSULTANTS, INC.

GEOTECHNICAL ENGINEER
CITY,STATE, ZIP: LIVERMORE, CA 94550
ADDRESS: 6671 BRISA STREET
CONTACT: ADAM KNOX E-MAIL: [email protected]
TEL: 949/261-1001
NAME: LPA, INC.

STRUCTURAL ENGINEER
CITY,STATE, ZIP: IRVINE, CA 92617
ADDRESS: 5301 CALIFORNIA AVE, SUITE 100
CONTACT: JOHN WILSON E-MAIL: [email protected] TEL: 949/261-1001
NAME: LPA, INC.

MECHANICAL ENGINEER
CITY,STATE, ZIP: IRVINE, CA 92617
ADDRESS: 5301 CALIFORNIA AVE, SUITE 100
CONTACT: KRISTY NELSON E-MAIL: [email protected] TEL: 949/261-1001
NAME: LPA, INC.

ELECTRICAL ENGINEER
CITY,STATE, ZIP: IRVINE, CA 92617
ADDRESS: 5301 CALIFORNIA AVE, SUITE 100
CONTACT: FRANK TRAN E-MAIL: [email protected]
TEL: 949/261-1001
NAME: LPA, INC.

PLUMBING ENGINEER
CITY,STATE, ZIP: IRVINE, CA 92617
ADDRESS: 5301 CALIFORNIA AVE, SUITE 100
CONTACT: JARED PLUMMER E-MAIL: [email protected] TEL: 949/497-9000
NAME: GRIFFIN STRUCTURES, INC.

CONSTRUCTION MANAGER
CITY,STATE, ZIP: IRVINE, CA 92618
ADDRESS: 1 TECHNOLOGY, BUILDING I, SUITE 829
CONTACT: DUSTIN ALAMO E-MAIL: [email protected] ADDRESS:
1330 WEST LUCHESSA AVENUE
GILROY, CA 95020
APN: 808-58-004
P
N
ROJECT
ORTH
N
THE PROJECT CONSISTS OF A NEW 6,500-7,000 SQUARE FOOT ONE-STORY FIRE

STATION BUILDING WHICH INCLUDES TWO FIRE TRUCK BAYS, ADMINISTRATIVE

OFFICES, INDIVIDUAL DORMITORY ROOMS, KITCHEN, SHARED LIVING AREA, FITNESS AND SUPPORT SPACES ON AN APPROXIMATELY 1.36 ACRE SITE AT THE

SOUTHEASTERN CORNER OF WEST LUCHESSA AVENUE AND MILLER AVENUE IN GILROY, CA. SITE IMPROVEMENTS INCLUDE SECURED STAFF PARKING, PUBLIC/

VISITOR PARKING, AN EMERGENCY GENERATOR, A TRASH ENCLOSURE, PERIMETER WALL, AND VEHICULAR GATES.

THE INTENT OF THE LIMIT OF WORK LINE IS TO DESCRIBE IN GENERAL THE AREAS AFFECTED BY PROJECT CONSTRUCTION. IT IS NOT INTENDED TO BE AN EXACT INDICATION OR EDGE OF THE CONSTRUCTION AREA. THE DBE SHOULD

VISIT THE SITE & BECOME FAMILIAR W/ EXG CONDITIONS & THEIR RELATIONSHIP TO THE WORK PROPOSED IN THE CONTRACT DOCUMENTS. ALL ITEMS

NECESSARY FOR THE PROPER EXECUTION & COMPLETION OF THE WORK SHALL BE INCLUDED. THE CONTRACT DOCUMENTS ARE COMPLEMENTARY &

WHAT IS REQ BY ONE SHALL BE BINDING AS IF REQ BY ALL TO THE EXTENT

THAT IT IS REASONABLY INFERABLE FROM THEM AS BEING NECESSARY TO PRODUCE THE INTENDED RESULTS.

THESE BRIDGING DOCUMENTS ESTABLISH THE BASIS OF DESIGN FOR THE PROJECT. ITEMS SHOWN, DEPICTED, DESCRIBED, SUGGESTED, IMPLIED,

REFERENCED, OR OTHERWISE CONVEYED IN ANY MANNER WITHIN THESE DOCUMENTS SHALL BE INCORPORATED INTO THE DESIGN-BUILD ENTITY’S (DBE)

FINAL DESIGN, ENGINEERING, AND CONSTRUCTION WITHOUT ADDITIONAL COST TO THE CITY. THE DBE SHALL RESOLVE ALL DISCREPANCIES, OMISSIONS,

SCHEMATIC DETAILS, OR CONFLICTS IN A MANNER CONSISTENT WITH THE OWNER’S PROGRAM, SPATIAL, AND FUNCTIONAL INTENT, WHETHER EXPRESSLY SHOWN OR IMPLIED IN THE BRIDGING DOCUMENTS. AT NO POINT SHALL THE DBE’S FINAL DESIGN OMIT, REDUCE, SUBSTITUTE, OR ALTER ANY SPACE,

FURNISHING, SYSTEM, FEATURE, OR ELEMENT DEPICTED, DESCRIBED,

REFERENCED, OR OTHERWISE CONVEYED IN THE BRIDGING DOCUMENTS,

EXCEPT WITH THE PRIOR WRITTEN APPROVAL OF THE CITY ENGINEER SPECIFIC

TO SAID ITEM, AND SUCH APPROVAL SHALL NOT CONSTITUTE GROUNDS FOR

ADDITIONAL COMPENSATION OR TIME UNLESS EXPRESSLY AUTHORIZED IN WRITING BY THE CITY. WHERE DISCREPANCIES EXIST AMONG THE BRIDGING

DOCUMENTS, THE DBE SHALL ASSUME AND CARRY THE MOST STRINGENT AND

COMPREHENSIVE INTERPRETATION OF THE REQUIREMENT AND SHALL NOT

HAVE GROUNDS TO REQUEST ADDITIONAL COMPENSATION OR TIME FOR DOING SO. THE DBE SHALL NOT RELY UPON THE PRELIMINARY NATURE OF THESE DOCUMENTS TO ASSERT CLAIMS FOR ADDITIONAL COMPENSATION OR TIME.

THE DBE IS SOLELY RESPONSIBLE FOR ENSURING THAT THE FINAL DESIGN IS

FULLY COMPLIANT WITH ALL APPLICABLE CODES AND REQUIREMENTS OF

AUTHORITIES HAVING JURISDICTION, CONSTRUCTIBLE, COORDINATED ACROSS ALL DISCIPLINES, AND CONSISTENT WITH THE OWNER’S PROGRAM INTENT.

UTILITY LAYOUTS DEPICTED IN THE BRIDGING DOCUMENTS ARE DIAGRAMMATIC ONLY. THE DBE IS FULLY RESPONSIBLE FOR FINALIZING THE DESIGN,

ENGINEERING, AND COORDINATION OF ALL UTILITY SERVICES DIRECTLY WITH

THE PROVIDER, INCLUDING SUBMITTING COMPLETE APPLICATIONS AND

SECURING APPROVALS AND PERMITS FROM THE SERVING UTILITIES AND AUTHORITIES HAVING JURISDICTION (PERMIT FEES TO BE PAID BY THE CITY).

THE DBE SHALL ENSURE THAT ALL UTILITY SERVICES ARE DESIGNED,

COORDINATED, AND INSTALLED IN A MANNER THAT MEETS THE PROJECT SCHEDULE AND SUPPORTS TIMELY OCCUPANCY.IN THE EVENT OF CONFLICTS

BETWEEN THESE DOCUMENTS, THE INTERPRETATION MOST CONSISTENT WITH THE OWNER’S PROGRAM INTENT SHALL GOVERN. THE DBE SHALL PROVIDE ALL

DESIGN, LABOR, MATERIALS, EQUIPMENT, SUPERVISION, AND SYSTEMS

REQUIRED TO FURNISH AND INSTALL THE PROJECT CONSISTENT WITH THESE REQUIREMENTS. NO OMISSION OR AMBIGUITY IN THE BRIDGING DOCUMENTS

SHALL RELIEVE THE DBE OF ITS OBLIGATION TO DELIVER A COMPLETE, FULLY FUNCTIONING, AND CODE-COMPLIANT FACILITY. FOR PURPOSES OF THIS DISCLAIMER, “BRIDGING DOCUMENTS” MEANS ALL PLANS, SPECIFICATIONS,

BASIS OF DESIGN NARRATIVES, REPORTS, AND EXHIBITS ISSUED BY THE OWNER AS PART OF THE PROCUREMENT PACKAGE.

CAB CABINET

CB CATCH BASIN

CEM CEMENT

CER CERAMIC

CI CAST IRON

CIP CAST IN PLACE

CIV ENG CIVIL ENGINEER

CG CORNER GUARD

CJ CONTROL JOINT

CLG CEILING

CLKG CAULKING

CLO CLOSET

CLR CLEAR

CNTR COUNTER

CO CASED OPENING

COL COLUMN

CONC CONCRETE

CONN CONNECTION

CONSTR CONSTRUCTION

CONT CONTINUOUS

CORR CORRIDOR

CT CERAMIC TILE

CTR CENTER

CTSK COUNTERSUNK

DA DISABLED ACCESS

DBE DESIGN-BUILD ENTITY

DBL DOUBLE
DEPT. DEPARTMENT

DESC DESCRIPTION

DF DRINKING FOUNTAIN

DET DETAIL

DIA DIAMETER

DIM DIMENSION

DISP DISPENSER

DN DOWN

DO DOOR OPENING

DR DOOR

DWR DRAWER

DS DOWNSPOUT

DSP DRY STANDPIPE

DWG DRAWING
E EAST

EA EACH

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRICAL

ELEV ELEVATOR

EMER EMERGENCY

ENCL ENCLOSURE

EP ELECTRICAL PANELBOARD

EQ EQUAL

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXIST EXISTING

EXPO EXPOSED

EXP EXPANSION

EXT EXTERIOR

FA FIRE ALARM

FB FLAT BAR

FD FLOOR DRAIN

FDN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER

CABINET

FHC FIRE HOSE CABINET

FIN FINISH

FLR FLOOR

FLASH FLASHING

FLUOR FLUORESCENT

FOC FACE OF CONCRETE

FOF FACE OF FINISH

FOM FACE OF MASONRY

FOS FACE OF STUD

FOV FACE OF VENEER (BRICK OR

PRECAST)

FOW FACE OF WALL

FR FIRE RETARDANT

FPRF FIREPROOF

FS FINISH SURFACE

FT FOOT OR FEET

FTG FOOTING

FURR FURRING

FUT FUTURE

GA GAUGE

GALV GALVANIZED

GB GRAB BAR

GC GENERAL CONTRACTOR

GI GALVANIZED IRON

GL GLASS

GND GROUND

GR GRADE

GYP GYPSUM

HB HOSE BIB

HC HOLLOW CORE

HDWD HARDWOOD

HDW HARDWARE

HM HOLLOW METAL

HORIZ HORIZONTAL

HR HOUR

HGT/HT HEIGHT

ID INSIDE DIAMETER

INSUL INSULATION

INT INTERIOR

JAN JANITOR

JT JOINT

KIT KITCHEN

LAB LABORATORY

LAM LAMINATE

LAND ARCH LANDSCAPE ARCHITECT

LAV LAVATORY

LKR LOCKER

LT LIGHT

MATL MATERIAL

MAX MAXIMUM

MC MEDICINE CABINET

MECH MECHANICAL

MEMB MEMBRANE

MET METAL

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MIR MIRROR

MISC MISCELLANEOUS

MO MASONRY OPENING

MTD MOUNTED

MUL MULLION

N NORTH

NIC NOT IN CONTRACT
NO/# NUMBER

NOM NOMINAL

NTS NOT TO SCALE

OA OVERALL

OA OUTSIDE AIR

OBS OBSCURE

OC ON CENTER

OD OUTSIDE DIAMETER

OFF OFFICE

OPNG OPENING

OPP OPPOSITE

OSA OUTSIDE AIR

PA PLANTING AREA

PRCST PRECAST

PH PANIC HARDWARE

PL PLATE

P LAM PLASTIC LAMINATE

PLAS PLASTER

PLYWD PLYWOOD

POT PATH OF TRAVEL

PR PAIR

PT PAINT

PTD PAPER TOWEL

DISPENSER

PTD/R COMBINATION PAPER

TOWEL DISPENSER
& RECEPTACLE

PTN PARTITION

PTR PAPER TOWEL

RECEPTACLE

QT QUARRY TILE

R RISER

RAD RADIUS

RD ROOF DRAIN

REF REFERENCE

REFR REFRIGERATOR

RGTR REGISTER

REINF REINFORCED

REQD REQUIRED

RESIL RESILIENT

RM ROOM

RO ROUGH OPENING

ROW RIGHT OF WAY

RWD REDWOOD

RWL RAIN WATER LEADER

S SOUTH

SC SOLID CORE

SCD SEAT COVER

DISPENSER

SCHED SCHEDULE

SD SOAP DISPENSER

SECT SECTION

SF SQUARE FEET

SH SHELF

SHR SHOWER

SHT SHEET

SIM SIMILAR

SND SANITARY NAPKIN

DISPENSER

SNR SANITARY NAPKIN

RECEPTACLE

SPEC SPECIFICATION(S)

SQ SQUARE

SS STAINLESS STEEL

S SK SERVICE SINK

STA STATION

STD STANDARD

STL STEEL

STOR STORAGE

STR STRUCTURAL

SUSP SUSPENDED

SYM SYMMETRICAL

T TREAD

TB TOWEL BAR

TC TOP OF CURB

TEL TELEPHONE

TER TERRAZZO

T&G TONGUE & GROOVE

THK THICK

TOB TOP OF BEAM

TOC TOP OF CONCRETE

TOW TOP OF WALL

TOP TOP OF PARAPET

TPD TOILET PAPER

DISPENSER

TS TOP OF SLOPE

TV TELEVISION

TYP TYPICAL

UNF UNFINISHED

UNO UNLESS NOTED

OTHERWISE

UR URINAL

VCT VINYL COMPOSITION
TILE

VERT VERTICAL

VEST VESTIBULE
W WEST

W/ WITH

WC WATER CLOSET

WD WOOD

W/O WITHOUT

WP WATERPROOF

WR WATER RESISTANT

WSCT WAINSCOT

WT WEIGHT

WWF WELDED WIRE FABRIC
& AND
∠ ANGLE
@ AT
℄ CENTERLINE
∅ DIAMETER OR ROUND
# POUND OR NUMBER
(E) EXISTING
(P) PAINT
(R) REMOVE
+/- DIM TOLERANCE

AC ASPHALTIC CONCRETE

ACC ACCESSIBLE

ACOUS ACOUSTICAL

ACM ALUM COMPOSITE MATERIAL

ACT ACOUS CLG TILE

AD AREA DRAIN

AED AUTO EXT DEFIBRILLATOR

ADJ ADJUSTABLE

AFF ABOVE FINISH FLOOR

AGGR AGGREGATE

AHJ AUTHORITY HAVING

JURISDICTION

ALUM ALUMINUM

APPROX APPROXIMATE

ARCH ARCHITECTURAL

ASF ASSIGNABLE SF

ASPH ASPHALT

BD BOARD

BITUM BITUMINOUS

BLDG BUILDING

BLK BLOCK

BLK'G BLOCKING

BM BEAM

BOC BACK OF CURB

BOT BOTTOM

BO BOTTOM OF

BOC BACK OF CURB

BOW BOTTOM OF WALL

BS BOTTOM OF SLOPE

COLUMN LINES
0 0

SURFACE DRAINAGE

ARROW INDICATES

DIRECTION OF FLOW
N

PROJECT NORTH

BUILDING SECTION

SECTION ID

SHEET NUMBER

WALL SECTION

SECTION ID

SHEET NUMBER

DETAIL CALLOUTS

DETAIL ID

SHEET NUMBER

DETAIL SECTION

DETAIL ID

SHEET NUMBER

DETAIL REFERENCE

DETAIL ID

SHEET NUMBER

INTERIOR ELEVATIONS

DETAIL ID

SHEET NUMBER
A
C
SIM
D A101 B

DOOR DESIGNATION

ROOM DESIGNATION

ROOM NUMBER

ROOM AREA
REVISION CLOUD & 1

TAG (OPTIONAL)
SA2U
1t

SHADED PORTION POINTS

TO SIDE REFERENCED

DATUM POINT

KEYNOTE

WALL TYPE

OPENING DESIGNATION
TYP.
?

MATCH LINE
SEE SHEET A101

LEVEL LINE, CONTROL POINT
EL: 12'-8" = ELEVATION/SECTION

STAIR DIRECTION
DN
UP

CENTER LINES, LEVEL LINES

HIDDEN CONSTRUCTION FEATURE

BREAK LINE
####
FINISH TAG XX-##
EQUIPMENT TAG 1i
N

TRUE NORTH

NORTH ARROW

EXTERIOR ASSEMBLY
REFER TO A8.11 R1
Room
101
150 SF
1 A101
TYP
1 A101
TYP
1 A101
SIM
1 A101
SIM
1 A101
SIM

LIST OF APPLICABLE CODES
2025 CALIFORNIA ADMINISTRATIVE CODE (CAC), PART 1, TITLE 24 CCR 2025 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 CCR 2025 CALIFORNIA RESIDENTIAL CODE (CBC), PART 2.5, TITLE 24 CCR 2025 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 CCR 2025 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 CCR 2025 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 CCR 2025 CALIFORNIA ENERGY CODE, PART 6, TITLE 24 CCR
2025 CALIFORNIA FIRE CODE (CFC), PART 9, TITLE 24 CCR
2025 CALIFORNIA EXISTING BUILDING CODE (CEBC), PART 10, TITLE 24 CCR 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE (CAL GREEN), PART 11, TITLE 24 CCR
2025 CALIFORNIA REFERENCED STANDARDS CODE, PART 12, TITLE 24 CCR TITLE 19 CCR, PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS

APPLICABLE STANDARDS

FOR A LIST OF APPLICABLE STANDARDS, INCLUDING CALIFORNIA AMENDMENTS TO THE NFPA STANDARDS, REFER TO CBC CHAPTER 35 AND CFC CHAPTER 80.

1. PLANS FOR THE FIRE SPRINKLER SYSTEMS MUST BE APPROVED BY THE AUTHORITY HAVING JURISDICTION (AHJ) PRIOR TO INSTALLATION. SUBMIT

PLANS IN A MANNER WHICH WILL NOT IMPEDE THE PROGRESS OF CONSTRUCTION.

2. FIRE SPRINKLER SYSTEMS & INSTALLATION SHALL CONFORM W/ THE APPLICABLE STANDARDS AND CODES.

3. FIRE SPRINKLER SYSTEMS TO BE TIED INTO THE ALARM SYSTEM PER THE APPLICABLE CODES.

4. AUTOMATIC SPRINKLER SYSTEM(S) SHALL BE SUPERVISED BY AN APPROVED

CENTRAL OR REMOTE STATION SERVICE, AND/OR SHALL BE PROVIDED W/ A LOCAL ALARM WHICH WILL GIVE AN AUDIBLE SIGNAL.

5. FIRE SPRINKLER SYSTEM(S) & ALL CONTROL VALVES SHALL BE SUPERVISED BY A U.L. LISTED CENTRAL ALARM STATION OR PER THE APPLICABLE CODES.

6. FIRE HYDRANT & FIRE SPRINKLER SYSTEM(S) SHALL BE FLUSHED

THOROUGHLY BEFORE CONNECTION IS MADE TO EXISTING SYSTEM STUBOUTS & WITNESSED BY THE PROJECT INSPECTOR.

7. A HYDROSTATIC TEST (200 PSI PRESSURE FOR 2 HRS. OR @ 50 PSI IN EXCESS OF THE MIN. STATIC PRESSURE WHEN IT IS IN EXCESS OF 150 PSI) SHALL BE

WITNESSED BY THE PROJECT INSPECTOR PRIOR TO COVERING PIPING JOINTS.

8. A 3' CLR SPACE SHALL BE MAINTAINED AROUND THE CIRCUMFERENCE OF FIRE

HYDRANTS EXCEPT AS OTHERWISE REQ OR APPROVED PER THE APPLICABLE CODES.

9. THRUST BLOCKS SHALL BE PROVIDED WHEREVER PIPE CHANGES DIRECTION.

10. ALL PIPE SHALL BE UL LISTED FOR FIRE SERVICE SYSTEMS, CLASS 200 MIN.

11. FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED W/I 100' FROM A PUBLIC FIRE HYDRANT PER THE APPLICABLE STANDARDS AND CODES.

12. FIRE SPRINKLER RISER SHALL BE LOCATED WITHIN 5 FT OF THE EXT WALL (OR AS REQ BY THE AHJ) AND TERMINATE 6" ABV FF

13. AN ALL-WEATHER FIRE ACCESS ROAD SHALL BE IN PLACE BEFORE ANY COMBUSTIBLE MATERIALS ARE PLACED ON THE SITE OR AS REQ BY THE AHJ.

14. STORAGE, DISPENSING, OR USE OF ANY FLAMMABLE & COMBUSTIBLE LIQUIDS,

FLAMMABLE & COMPRESSED GASES & OTHER HAZARDOUS MATERIALS SHALL COMPLY W/ THE APPLICABLE CODES.

15. EXIT SIGNS SHALL BE POSTED OVER EXIT DOORS & DIRECTIONAL EXIT SIGNS SHALL BE LOCATED TO DIRECT PERSONS TOWARD EXIT DOORS.

16. EXIT SIGNS SHALL BE SELF-LUMINOUS TYPE OR ELECTRONICALLY

ILLUMINATED & ENERGIZED FROM SEPARATE CIRCUITS, ONE OF WHICH SHALL

BE FROM STORAGE BATTERIES OR AN ON-SITE GENERATOR, FOR A DURATION OF 90 MINUTES PER THE APPLICABLE CODES.

17. EXIT DOORS SHALL BE OPENABLE FROM THE INSIDE WITHOUT THE USE OF A KEY OR ANY SPECIAL KNOWLEDGE OR EFFORT.

18. ACCESS GATE(S) SHALL BE OPENABLE W/ FIRE DEPT MASTER KEY FROM THE EXTERIOR.

19. CURBS ALONG FIRE LANES SHALL BE PAINTED SAFETY RED & MARKED "FIRE LANE NO PARKING" W/ 3" WHITE LETTERS ON THE TOP OF CURBING EVERY 30' AS INDICATED ON THE APPROVED DRAWINGS.

20. APPROVED NUMBERS OR ADDRESSES SHALL BE PROVIDED FOR ALL NEW &

EXG BLDGS IN SUCH A POSITION AS TO BE PLAINLY VISIBLE & LEGIBLE FROM

THE STREET OR ROAD FRONTING THE PROPERTY PER THE APPLICABLE CODES.

21. PROVIDE PERMANENT OR TEMPORARY STANDPIPES WHILE BUILDING IS UNDER CONSTRUCTION PER THE APPLICABLE CODES.

22. PROVIDE FIRE EXTINGUISHERS PER THE REQ THE APPLICABLE STANDARDS AND CODES.

1. ALL CONSTRUCTION & MATERIALS SHALL BE AS SPECIFIED & IN ACCORDANCE

WITH ALL APPLICABLE CODES, ORDINANCES, LAWS, PERMITS & THE CONTRACT DOCUMENTS.

2. THE DESIGN-BUILD ENTITY (DBE) SHALL BE RESPONSIBLE FOR THE ACCURATE PLACEMENT OF ALL NEW CONSTRUCTION ON THE SITE.

3. THE DBE IS RESPONSIBLE FOR ALL EXG SURVEY MONUMENTS WHICH MAY BE

DISTURBED THROUGH CONSTRUCTION ACTIVITIES DEEMED NECESSARY FOR PRESERVATION BY THE CIVIL ENGINEER. IF SUCH MONUMENTS WERE

DISTURBED, THE APPLICANT SHALL HAVE A LICENSED LAND SURVEYOR

QUALIFIED CIVIL ENGINEER REESTABLISH ANY SUCH MONUMENTATION

DAMAGED OR DESTROYED DURING THE CONSTRUCTION OF THE PROJECT & SUBMIT "PRELIMINARY CORNER RECORDS" TO THE CIVIL ENGINEER AFTER REPLACEMENT. AFTER APPROVAL BY THE CIVIL ENGINEER, THE APPLICANT SHALL FILE THE CORNER RECORDS WITH THE COUNTY SURVEYOR. PRIOR TO

THE EXONERATION OF ANY SECURITY, EVIDENCE OF SUCH FILING SHALL BE FURNISHED TO THE CIVIL ENGINEER.

4. THE DBE IS RESPONSIBLE TO INSURE THAT TRUCK ROUTES SHALL BE STEERED AWAY FROM RESIDENTIAL AREAS.

5. THE DBE SHALL ENSURE THAT TRUCKS HAULING DIRT ON PUBLIC ROADS TO & FROM THE SITE SHALL BE COVERED OR WILL MAINTAIN A 6" DIFFERENTIAL

BETWEEN THE MAX HGT OF ANY HAULED MATERIAL & THE TOP OF THE HAUL TRAILER. HAUL TRUCK DRIVERS SHALL WATER THE LOAD PRIOR TO LEAVING THE SITE TO PREVENT SOIL LOSS DURING TRANSPORT.

6. THE DBE SHALL ENSURE THAT GRADED SURFACES USED FOR OFF ROAD

PARKING, MATERIALS LAY-DOWN, OR AWAITING FUTURE CONSTRUCTION SHALL BE STABILIZED FOR DUST CONTROL AS NEEDED. FREQUENTLY ACCESSED

UNPAVED AREAS SHALL BE PAVED AS EARLY AS POSSIBLE TO MINIMIZE DIRT TRACKOUT TO PUBLIC RIGHTS-OF-WAY.

7. THE CONSTRACTOR SHALL COORDINATE ANY LANE CLOSURES OR DETOURS WITH THE CITY/COUNTY. FLAG PERSONS & APPROPRIATE TRAFFIC CONTROL

DEVICES SHALL BE USED AS NEEDED TO MINIMIZE CONSTRUCTION ACTIVITY INTERFERENCE WITH OFF-SITE-TRAFFIC.

8. THE DBE SHALL VERIFY ALL DIMENSIONS & SITE CONDITIONS BEFORE STARTING WORK. SHOULD A DISCREPANCY APPEAR IN THE CONTRACT

DOCUMENTS OR BETWEEN THE CONTRACT DOCUMENTS & EXISTING

CONDITIONS, NOTIFY THE ARCHITECT AT ONCE FOR INSTRUCTION ON HOW TO PROCEED.

9. SHOULD A CONFLICT OCCUR BETWEEN DWGS & SPECIFICATIONS, THE MORE

COSTLY CONDITION SHALL TAKE PRECEDENCE, UNLESS A WRITTEN DECISION

FROM THE ARCHITECT HAS BEEN OBTAINED WHICH DESCRIBES A
CLARIFICATION OR ALTERNATE METHOD AND/OR MATERIALS.

10. THE DBE SHALL CONFINE HIS OPERATION ON THE SITE TO AREAS PERMITTED BY OWNER.

11. THE JOBSITE SHALL BE MAINTAINED IN A CLEAN, ORDERLY CONDITION FREE OF

DEBRIS & LITTER & SHALL NOT BE UNREASONABLY ENCUMBERED WITH ANY MATERIALS OR EQUIPMENT. EACH SUBDBE IMMEDIATELY UPON COMPLETION

OF EACH PHASE OF HIS WORK SHALL REMOVE ALL TRASH & DEBRIS AS A RESULT OF HIS OPERATION.

12. ALL MATERIAL STORED ON THE SITE SHALL BE PROPERLY STACKED & PROTECTED TO PREVENT DAMAGE & DETERIORATION. FAILURE TO PROTECT MATERIALS MAY BE CAUSE FOR REJECTION OF WORK.

13. THE DBE SHALL DO ALL CUTTING, FITTING, AND/OR PATCHING OF HIS WORK

THAT MAY BE REQ TO MAKE ITS SEVERAL PARTS FIT TOGETHER PROPERLY &

SHALL NOT ENDANGER ANY OTHER WORK BY CUTTING, EXCAVATING, OR OTHERWISE ALTERING THE TOTAL WORK OR ANY PART OF IT. ALL PATCHING,

REPAIRING AND REPLACING OF MATERIALS AND SURFACES, CUT OR DAMAGED

IN EXECUTION OF WORK, SHALL BE DONE WITH APPLICABLE MATERIALS SO

THAT SURFACES REPLACED WILL, UPON COMPLETION, MATCH SURROUNDING SIMILAR SURFACES.

14. STRUCTURAL OBSERVATION WILL BE PERFORMED BY THE STRUCTURAL ENGINEER. WHEN REQ, A STATEMENT IN WRITING SHALL BE GIVEN TO THE

BUILDING OFFICIAL, STATING THAT THE SITE VISITS HAVE BEEN MADE &

WHETHER OR NOT ANY OBSERVED DEFICIENCIES HAVE BEEN CORRECTED TO CONFORM TO THE APPROVED PLANS & SPECIFICATIONS.

15. SUBMITTAL DOCUMENTS FOR DEFERRED SUBMITAL ITEMS SHALL BE

SUBMITTED TO THE ARCHITECT OR ENGINEER OF RECORD, WHO SHALL

REVIEW THEM & RETURN THEM TO THE DBE (WITH A NOTIFICATION INDICATING

THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED & THAT

THEY HAVE BEEN FOUND TO BE IN GENERAL CONFORMANCE WITH THE DESIGN OF THE BUILDING) FOR PLAN CHECK APPROVAL. THE DEFERRED SUBMITTAL

ITEMS SHALL NOT BE INSTALLED UNTIL THEIR DESIGN & SUBMITTAL

DOCUMENTS HAVE BEEN APPROVED BY THE AUTHORITY HAVING
JURISDICTION.

16. PROVIDE ALL ACCESS PANELS AS REQ BY GOVERNING CODES TO ALL CONCEALED SPACES, VOIDS, ATTICS, ETC. VERIFY TYPE REQ WITH ARCHITECT PRIOR TO INSTALLATION.

17. NO PORTION OF WORK REQ A SHOP DWG OR SAMPLE SUBMISSION SHALL BE COMMENCED UNTIL THE SUBMISSION HAS BEEN REVIEWED BY THE ARCHITECT.

ALL SUCH PORTIONS OF THE WORK SHALL BE IN ACCORDANCE WITH CORRECTED SHOP DWGS. AND SAMPLES.

18. DIMENSIONS:

A. ALL DIMS SHALL TAKE PRECEDENCE OVER SCALE.

B. ALL DIMS ARE TO FACE OF STUD / CONCRETE / MASONRY UNO C. CLG HGT DIMS ARE FROM FACE OF SLAB TO FACE OF FIN CLG MATERIAL UNO

19. DO NOT SCALE DRAWINGS

20. PROVIDE ALL NECESSARY BLOCKING, BACKING, & FRAMING FOR LIGHT

FIXTURES, ELECTRIC UNITS, AC EQUIP, RECESSED ITEMS, AND ALL OTHER ITEMS AS REQ.

21. WHERE LARGER STUDS OR FURRING ARE REQ TO COVER PIPING AND

CONDUITS, THE LARGER STUD SIZE OR FURRING SHALL EXTEND THE FULL

SURFACE OF THE WALL WIDTH AND LENGTH WHERE THE FURRING OCCURS, UNO.

22. ALL DOORS SHALL BE OPERABLE FROM THE INSIDE W/O THE USE OF A KEY OR SPECIAL KNOWLEDGE OF EFFORT. EXIT SIGNS SHALL BE PROVIDED AT ALL EXITS AS REQ BY THE APPLICABLE CODES. ALL DOOR SWINGS SERVING AN OCCUPANT LOAD OF 50 OR GREATER SHALL SWING IN THE DIRECTION OF TRAVEL.

23. ALL GLASS AND GLAZING SHALL COMPLY WITH THE APPLICABLE CODES.

24. WALL AND CLG MATERIALS SHALL NOT EXCEED THE FLAME SPREAD CLASSIFICATIONS IN THE APPLICABLE CODES.

25. SURVEYORS CERTIFICATE REQ PRIOR TO FINAL COMPLETION.

26. THE DBE SHALL COMPLY WITH THE APPLICABLE CODES FOR FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION.

1. PROVIDE COMPLETE PHOTOVOLTAIC ARRAY SYSTEM OVER PARKING CANOPY.

SEE KEYNOTE 26.01 ON ARCHITECTUAL SITE PLAN, AND SEE KEYNOTE ON ELECTRICAL SITE PLAN.

2. EXTEND ELECTRICAL, DOMESTIC WATER, AND SEWER SYSTEM
INFRASTRUCTURE TO OPEN GREEN FEILD. SEE KEYNOTE ON CIVIL UTILITY PLAN, AND SEE KEYNOTE ON ELECTRICAL SITE PLAN.

Revision Date
408-780-7200 Office
60 South Market Street, Suite 1250
San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked By
Scale
Job Number Submittal Date 70% SCHEMATIC DESIGN 03/10/2026 100% SD / BRIDGING DOCS 03/26/2026 This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
1/8" = 1'-0"

SANTA TERESA FIRE STATION
1330 WEST LUCHESSA AVENUEGILROY, CA 95020
GRIFFIN STRUCTURES, INC.

GENERAL PROJECT

INFORMATION & SHEET
INDEX
G0.20
33236

MG / TP

ADA CONSTRUCTION SUPPORT FACILITIES

PROJECT DIRECTORY

PROJECT SCOPE VICINITY MAP

LIMIT OF WORK

BASIS OF DESIGN NOTE

SYMBOLS ABBREVIATIONS SHEET INDEX SHEET NUMBER

SHEET NAME

GENERAL
G0.00 COVER SHEET
G0.20 GENERAL PROJECT INFORMATION & SHEET INDEX
G0.40 CALGREEN 1
G0.41 CALGREEN 2
G0.42 CALGREEN 3
G0.43 CALGREEN 4
G1.01 SITE CODE & FIRE ACCESS PLAN
G2.01 CODE ANALYSIS & EGRESS PLAN
CIVIL
C0.01 CIVIL NOTES
C0.02 EXISTING CONDITIONS PLAN
C1.01 DEMOLITION PLAN
C2.01 CONCEPTUAL GRADING PLAN
C3.01 CONCEPTUAL STORM DRAIN PLAN
C4.01 CONCEPTUAL UTILITY PLAN

LANDSCAPE
L0.01 LANDSCAPE NOTES AND LEGENDS
L1.01 MATERIALS PLAN
L7.01 PLANTING PLAN

ARCHITECTURE
A0.21 SITE PLAN
A2.01 FLOOR PLAN
A2.02 ROOF PLAN
A2.21 FLOOR FINISHES PLAN
A2.31 REFLECTED CEILING PLAN
A2.41 EQUIPMENT/ FURNITURE PLAN
A3.01 EXTERIOR ELEVATIONS
A3.11 BUILDING SECTIONS

MECHANICAL
M0.01 MECHANICAL LEGENDS AND GENERAL NOTES
M5.01 MECHANICAL ZONING PLANS
M5.02 MECHANICAL ZONING PLANS

PLUMBING
P0.10 PLUMBING LEGENDS AND GENERAL NOTES
P1.00 PLUMBING SITE PLANS
P2.01 PLUMBING FLOOR PLAN
P2.02 PLUMBING ROOF PLAN
P4.01 PLUMBING ENLARGED PLANS
P6.00 PLUMBING SCHEDULES

ELECTRICAL
E0.01 ELECTRICAL LEGEND & GENERAL NOTES
E0.02 ELECTRICAL GENERAL NOTES
E0.21 ELECTRICAL SITE PLANS
E0.31 LIGHTING SITE PLAN
E2.01 ELECTRICAL POWER PLANS
E2.13 ELECTRICAL MECHANICAL POWER ROOF PLANS
E5.00 ELECTRICAL SINGLE LINE DIAGRAMS
TOTAL NUMBER OF SHEETS: 41

APPLICABLE CODES

CONSTRUCTION NOTES FIRE LIFE AND SAFETY NOTES

ALTERNATES

Page 215 of 256 ends

Revision Date
408-780-7200 Office
60 South Market Street, Suite 1250
San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked By
Scale
Job Number Submittal Date 70% SCHEMATIC DESIGN 03/10/2026 100% SD / BRIDGING DOCS 03/26/2026 This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc. SANTA TERESA FIRE STATION
1330 WEST LUCHESSA AVENUEGILROY, CA 95020
GRIFFIN STRUCTURES, INC.

CALGREEN 1
G0.40
33236
Checker

Page 216 of 256 ends

Revision Date
408-780-7200 Office
60 South Market Street, Suite 1250
San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked By
Scale
Job Number Submittal Date 70% SCHEMATIC DESIGN 03/10/2026 100% SD / BRIDGING DOCS 03/26/2026 This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc. SANTA TERESA FIRE STATION
1330 WEST LUCHESSA AVENUEGILROY, CA 95020
GRIFFIN STRUCTURES, INC.

CALGREEN 2
G0.41
33236
Checker

Page 217 of 256 ends

Revision Date
408-780-7200 Office
60 South Market Street, Suite 1250
San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked By
Scale
Job Number Submittal Date 70% SCHEMATIC DESIGN 03/10/2026 100% SD / BRIDGING DOCS 03/26/2026 This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc. SANTA TERESA FIRE STATION
1330 WEST LUCHESSA AVENUEGILROY, CA 95020
GRIFFIN STRUCTURES, INC.

CALGREEN 3
G0.42
33236
Checker

Page 218 of 256 ends

Revision Date
408-780-7200 Office
60 South Market Street, Suite 1250
San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked By
Scale
Job Number Submittal Date 70% SCHEMATIC DESIGN 03/10/2026 100% SD / BRIDGING DOCS 03/26/2026 This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc. SANTA TERESA FIRE STATION
1330 WEST LUCHESSA AVENUEGILROY, CA 95020
GRIFFIN STRUCTURES, INC.

CALGREEN 4
G0.43
33236
Checker

Page 219 of 256 ends

AC
NO

PARKING
EV

CHARGING
ONLY
EV

CHARGING
ONLY
NO

PARKING
1 EVCS
1 EVCS
1 1 ADA
1 ADA
TYP.

02.01 PROPOSED NEW

BUILDING FIRE STATION
W LUCHESSA AVE.

MILLER AVE.

PUBLIC PARKING SPACES
14'-4 3/8"
99'-6"
63'-6 1/8"
S
S
3 5
4 0'-3 1/4"

1. SITE DIMENSIONS ARE SHOWN FOR REFERENCE ONLY. REFER TO CIVIL DRAWINGS FOR SPECIFIC DIMENSION INFORMATION.

2. ALL PARKING SHALL COMPLY WITH THE GILROY MUNICIPAL CODE.

3. MOTORIZED ROLLING GATES: IN THE EVENT OF LOSS OF NORMAL POWER TO

THE GATE OPERATING MECHANISMS, IT SHALL BE AUTOMATICALLY

TRANSFERRED TO A FAIL-SAFE MODE ALLOWING THE GATE TO BE PUSHED OPEN

BY A SINGLE FIREFIGHTER WITHOUT ANY OTHER ACTIONS, KNOWLEDGE, OR

MANIPULATION OF THE OPERATING MECHANISM BEING NECESSARY AND WITHOUT THE USE OF BATTERY BACK-UP POWER. THE GATE SHALL BE

CONNECTED TO THE BUILDING EMERGENCY POWER SOURCE

4. THE GATE CONTROL FOR ELECTRONIC GATES SHALL BE OPERABLE BY A KNOX EMERGENCY OVERRIDE KEY SWITCH (WITH DUST COVER). THE KEY SWITCH SHALL BE PLACED BETWEEN 42" AND 48" ABOVE THE ROADWAY

SURFACE AT THE RIGHT SIDE OF THE ACCESS GATE WITHIN TWO FEET OF THE EDGE OF THE ROADWAY. THE KEY SWITCH SHALL BE READILY

VISIBLE AND UNOBSTRUCTED FROM THE FIRE LANE LEADING TO THE GATE. THE KEY SWITCH SHALL BE CLEARLY LABELED "FIRE DEPT."

5. VERIFY ALL SIGN TEXT, COLOR, AND GRAPHICS WITH THE ARCHITECT PRIOR TO FABRICATION.

ACCESSIBLE BUILDING ENTRANCE
ACCESSIBLE PATH OF TRAVEL*
1 PARKING STALL COUNT

APPROXIMATE ROADWAY CENTERLINE

PROPERTY LINE
*ACCESSIBLE PATH OF TRAVEL (P.O.T. BARRIER-FREE ACCESS ROUTE WITHOUT ANY ABRUPT VERTICAL CHANGES EXCEEDING 1/2" BEVELED AT 1:2 MAXIMUM SLOPE, EXCEPT THAT LEVEL CHANGES DO NOT EXCEED 1/4" VERTICAL AND IS AT LEAST 48" WIDE. SURFACE IS SLIP RESISTANT, STABLE, FIRM, AND SMOOTH.

CROSS-SLOPE DOES NOT EXCEED 2% AND SLOPE IN THE DIRECTION OF TRAVEL IS LESS THAN 5% UNLESS OTHERWISE INDICATED. P.O.T. SHALL MAINTAIN FREE OF OVERHANG OBSTRUCTIONS TO 80" MINIMUM (11B-307.4) AND PROTRUDING OBJECTS GREATER THAN 4" PROJECTION FROM WALL AND ABOVE 27" AND LESS THAN 80" (11B-204 AND 11B-307). ARCHITECT TO VERIFY THAT ALL BARRIERS IN THE

PATH OF TRAVEL HAVE BEEN REMOVED OR WILL BE REMOVED UNDER THIS PROJECT, AND PATH OF TRAVEL COMPLIES WITH CBC 11B-206 PER 11B-201.4.

CONSTRUCTION SUPPORT FACILITIES, RELATED PARKING, AND TOILETS SHOULD BE INCLUDED IN THE PATH OF TRAVEL (EXCEPT AS NOTED IN 11B-203.2)

S KNOX SWITCH FOR GATE ENTRY

RECESSED KNOX BOX

FIRE HYDRANT
FIRE LANE- 20' WIDE U.N.O. WITH 17' RAD. MIN.

ADJACENT CURBS TO BE PAINTED RED FROM BASE OF

CURB RISER TO BACK OF THE CURB, WHERE
REQUIRED. LETTERING SHALL BE WHITE, 3" IN HEIGHT
AND HAVE A 3/4" STROKE. CURB LETTERING SHALL
STATE "NO PARKING- FIRE LANE," CVC 225000.1, AND
SHALL OCCUR AT NOT LESS THAN 25 FOOT INTERVALS.

FDC
EXISTING PATH OF TRAVEL (N.I.C.

EXISTING TO REMAIN)
LIMIT OF WORK (L.O.W.)
SITE PARKING CALCULATIONS TOTAL *NOTES
TOTAL PARKING 13 *TOTAL USER PARKING
TOTAL: 13
ADA PARKING 2
EVCS-FUTURE (TOTAL) 2
EVCS (TOTAL) 2
BIKE PARKING- SHORT TERM 3
BIKE PARKING- LONG TERM 2
1 PARKING STALL COUNT
1" = 20'-0"
SITE ACCESSIBILITY PLAN G1.01 05
Revision Date
408-780-7200 Office
60 South Market Street, Suite 1250
San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked By
Scale
Job Number Submittal Date 70% SCHEMATIC DESIGN 03/10/2026 100% SD / BRIDGING DOCS 03/26/2026 This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.

As indicated

SANTA TERESA FIRE STATION
1330 WEST LUCHESSA AVENUEGILROY, CA 95020
GRIFFIN STRUCTURES, INC.

SITE CODE & FIRE

ACCESS PLAN
G1.01
33236
Checker

KEYNOTES

02.01 BUILDING OVERHANG

GENERAL NOTES
LEGEND

PARKING

PROJECT
NORT
N
H

Page 220 of 256 ends

WP WP
WP
WP
WP
WP
J
M
M
M
M
M
M
M
M
M
M
M
M
M
M
J
J
J
J
J
J
J
CLNG
J J J
J J J
WP WP
J
J
CLNG
CLNG

CLNG CLNG CLNG
FIRE-RESISTANCE RATING REQ FOR BLDG ELEMENTS (CBC TABLE 601):

STRUCTURAL FRAME:

EXTERIOR BEARING WALLS:

INTERIOR BEARING WALLS:

EXTERIOR NONBEARING WALLS:

INTERIOR NONBEARING WALLS:

FLOOR CONSTRUCTION:

ROOF CONSTRUCTION:

FIRE-RESISTANCE RATING REQ FOR EXTERIOR WALLS (CBC TABLE 705.5) 1-HR PROTECTED:

NO PROTECTION REQ:

BUILDING USE:

CONSTRUCTION CLASSIFICATION
(CBC 602):

OCCUPANCY CLASSIFICATION
(CBC 302 & 508.3):

FIRE PROTECTION:

ACCESSORY OCCUPANCY (CBC 508.2):

INCIDENTAL USES (CBC 509):

ALLOWABLE BUILDING HEIGHT AND
NUMBER OF STORIES (BASED ON S-1

AREA INCREASE WITH SPRINKLERS)
(CBC 504 & TABLE 504.3, CBC 504 &
TABLE 504.4):

ALLOWABLE BUILDING AREA
(CBC 506.2.3 & TABLE 506.2):

ACTUAL BUILDING HEIGHT:

ACTUAL NUMBER OF STORIES:

FIRST FLOOR BUILDING AREA1:

EXTERIOR ROOF PROJECTION
(UNCONDITIONED)
1 :

OVERALL BUILDING AREA1:

FIRE STATION

TYPE V-B
B, R-2, S-2 (NONSEPARATED

OCCUPANCIES - MOST RESTRICTIVE

OCCUPANCY ALLOWABLE AREA, HEIGHT
& STORIES)

AUTOMATIC FIRE SPRINKLER SYSTEM
PER NFPA 13
F-2: FACTORY (WORK ROOM): 99 SF

ACCESSORY FLOOR AREA/ TOTAL FLOOR
AREA
99 SF/ 6,687 SF = 0.014 = 1.4%

1.4% < 10% FLOOR AREA
B: 60'/ 3 STORIES
R-2: 40'/ 2 STORIES
S-2: 60'/ 3 STORIES
B: 36,000 SF
R-2: 28,000 SF
S-2: 54,000 SF
26'-6<40' - OK
26'-6" - OK
1 STORY - OK
6,687 SF
6,687 SF < 2,226 SF
8,939 SF < 28,000 - OK
8,939 SF
OLF
1:50 GROSS =
1:200 GROSS =
1:150 GROSS =
1:200 GROSS =
1:300 GROSS =
1:50 GROSS =
1:50 GROSS =
1:300 GROSS =
1:100 GROSS =
TOTAL

FUNCTION

RESIDENTIAL
2 DORMITORIES

BUSINESS AREAS
PARKING GARAGES2
STORAGE2
EXCERCISE ROOMS2
LOCKER ROOM2

MECHANICAL
2 WORK ROOM2
OCCUPANT LOAD PER FLOOR:

LEVEL 1:
1BUILDING AREAS INCLUDE HORIZONTAL PROJECTIONS OF THE ROOF OR FLOOR ABOVE BUT EXCLUDE VENT SHAFTS & COURTS. (CBC 202)
0 0
0 0
0 0
0 < 10'-0"
≥ 10'-0"
71 OCCUPANTS
# OF EXITS REQUIRED = 2
# OF EXITS PROVIDED = 7
AREA
1,127 SF
1,884 SF
356 SF
2,083 SF
443 SF
345 SF
156 SF
194 SF
99 SF
6,687 SF

OCCUPANTS
25 11
4 11
5 7
4 3
1 71
MAX FLOOR AREA ALLOWANCES PER OCCUPANT (CBC TABLE 1004.5):

ELEVATION DISTANCE TO PL ALLOWABLE AREA
NORTH 40'-3" NO LIMIT

EAST NO LIMIT
SOUTH 63'-6" NO LIMIT
WEST 16'-11" 75%
99'-6"

MAXIMUM AREA OF EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION DISTANCE AND DEGREE OF OPENING PROTECTION (TABLE 705.8) FOR UNPROTECTED, SPRINKLERED BUILDINGS.

FIRE SEPARATION

DISTANCE

ALLOWABLE
AREA
15'-0'>FSD>20'-0"
FSD>20'-0"
=75%
=NO LIMIT
MEANS OF EGRESS SIZING (CBC 1005.3):

EGRESS COMPONENTS OTHER THAN STAIRWAYS:
# OCCUPANTS X 0.2 = EGRESS WIDTH
NUMBER OF EXISTS/ EXIT ACCESS DOORWAYS (CBC TABLE 1006.2.1) PROVIDE 2 EXITS IN ALL ROOMS WITH B OCCUPANT LOADS ABOVE 49 PROVIDE 2 EXITS IN ALL ROOMS WITH R-2 OCCUPANT LOADS ABOVE 20 PROVIDE 2 EXITS IN ALL ROOMS WITH S-2 OCCUPANT LOADS ABOVE 29 MAXIMUM COMMON PATH OF TRAVEL (CBC TABLE 1006.2.1):

B & S-2 OCCUPANCY: 100'-0"
R-2 OCCUPANCY: 125'-0"
MAXIMUM EXIT ACCESS TRAVEL DISTANCE (CBC TABLE1017.2):

B & R-2 OCCUPANCY: 250'-0"
S-2 OCCUPANCY: 400'-0"

ROOM NUMBER

SQUARE FOOTAGE

OCCUPANT LOAD

OCCUPANCY LOAD FACTOR

OCCUPANCY GROUP

COMBINED ROOM OCCUPANCY LOAD

INDIVIDUAL ROOM OCCUPANCY LOAD

PATH OF EXIT ACCESS TRAVEL PER CBC
TABLE 1017.2
COMMON PATH OF TRAVEL PER CBC TABLE 1006.2.1

B OCCUPANCY
(OFFICE. ADMIN)
1:150 GROSS

ROOF OVERHANG
(NO OCCUPANT LOAD)
S-2 OCCUPANCY
(APPARATUS BAY)
1:200 GROSS
F-2 OCCUPANCY
(WORK ROOM)
1:300 GROSS
1 HOUR RATED PARTITION

FIRE EXTINGUISHER CABINET

INDICATES PANIC HARDWARE REQUIRED
FE
PH

REQUIRED
PROVIDED 0"
0" EGRESS WIDTH REQUIRED

EGRESS WIDTH PROVIDED
### SF
Occ-Load OCC.

Room Name
###
# 1:OLF
0 0
R-2 OCCUPANCY
(LIVING QUARTERS)
1:200 GROSS
1 1
A A
2 2
3 3
4 4
5 5
6 6
B B
C C
D D
E E
F F
7 7
8 8
97 SF
1 OCC.

ACCESSIBLE

RESTROOM/
SHOWER
111
R-2 1:200
79 SF
1 OCC.

RESTROOM/
SHOWER
110
R-2 1:200
79 SF
1 OCC.

RESTROOM/
SHOWER
109
R-2 1:200
153 SF
1 OCC.

LAUNDRY/

JANITOR
108
R-2 1:200
131 SF
1 OCC.

ELECTRICAL
121
S-2 1:300
111 SF
1 OCC.

DORM
112
R-2 1:200
111 SF
1 OCC.

DORM
113
R-2 1:200
111 SF
1 OCC.

DORM
114
R-2 1:200
111 SF
1 OCC.

DORM
115
R-2 1:200
111 SF
1 OCC.

DORM
116
R-2 1:200
234 SF
2 OCC.

NON- RATED

CORRIDOR
119
R-2 1:200
81 SF
2 OCC.

NON-RATED

CORRIDOR
107
R-2 1:50
156 SF
4 OCC.

TURNOUT
122
S-2 1:50
69 SF
1 OCC.

MEDICAL

STORAGE
124
S-2 1:300
84 SF
1 OCC.

MDF
123
S-2 1:300
302 SF
7 OCC.

DAY ROOM
106
R-2 1:50
340 SF
7 OCC.

DINING
104
R-2 1:50
345 SF
7 OCC.

WEIGHT ROOM
102
B 1:50
203 SF
2 OCC.

SHARED
OFFICE
101
B 1:150
122 SF
1 OCC.

CAPTAIN'S
OFFICE
117
B 1:150
2087 SF
11 OCC.

APPARATUS
BAY
125
S-2 1:200
55 SF
1 OCC.

ACCESSIBLE

RESTROOM
131
S-2 1:300
184 SF
1 OCC.

DECONTAMINATION
130
S-2 1:300
98 SF
1 OCC.

WORK ROOM
126
F-2 1:300
26 SF
1 OCC.

FIRE RISER
129
S-2 1:300
37 SF
1 OCC.

AIR COMP.
127
S-2 1:300
212 SF
5 OCC.

KITCHEN
103
R-2 1:50
50 SF
1 OCC.

STOR.
128
S-2 1:300
31 SF
1 OCC.

STOR. CLOSET
118
B 1:150
180 SF
4 OCC.

NON-RATED

CORRIDOR
105
R-2 1:50

TO CLOSEST OPENING
16'-11"

PROPERTY LINE
1 1
1 1
1 1
1 1
1 8
1 1
4 08.01

08.01 08.01

08.01 08.01
1 4
7 68'-1 3/4"
65'-6"
19 1
1 7
64'-7"
23'-0"
14'-2"
80'-8"
1 1
1 2
7 1
7HOSE STORAGE
PH
PH
PH
21 OCCUPANTS

LAVATORIES

DRINKING

FOUNTAIN
MEN
WOMEN

REQUIRED FIXTURES

WATER CLOSET URINALS

PROVIDED FIXTURES
MINIMUM PLUMBING FACILITIES:

OCCUPANT LOAD FACTOR (IN ACCORDANCE WITH CBC):
71 TOTAL OCCUPANTS = 36 MALES & 35 FEMALES
R-2 OCCUPANCY
37 TOTAL OCCUPANTS = 19 MALES & 18 FEMALES
MINIMUM PLUMBING FACILITIES (CPC TABLE 422.1): R-2 OCCUPANCY

SERVICE SINK
2 2
X*
-
2 2
1 1

LAVATORIES

DRINKING

FOUNTAIN
MEN
WOMEN

WATER CLOSET URINALS SERVICE SINK
2 3
1 -
2 2
1 1
2BUILDING OCCUPANTS WILL BE FIVE (5) MAX. REGULAR DORMITORY OCCUPANTS FOR 48 HOUR SHIFTS. ALL OTHER SPACES ARE ACCESSORY TO THE R-2 DORMITORY OCCUPANTS.
3RESTROOM FACILITIES ARE UNISEX RESTROOMS
4URINAL COUNTS INCLUDE TOILETS AT GENDER NEUTRAL RESTROOMS.

PROPOSED BUILDING AREA: 8,939 SF

BASIC REQUIRED FLOW (DURATION)
1 : 2,500 GPM (2 HOURS)
HYDRANT REQUIREMENTS PER CFC APPENDIX SECTION B105.2:

NUMBER OF HYDRANTS MIN. 1

HYDRANT SPACING
(ONSITE / TO ROAD)
4 500' / 250'

1. PER 2025 CFC APPENDIX B, SECTION B105.1, TABLE B105.1(2).

2. REDUCTION TO 25% OF REQUIRED FIRE-FLOW PRESCRIBED IN TABLE B105.1(2) OF WITH A MINIMUM FIRE-FLOW RATE OF 1,000 GPM, FOR THE PRESCRIBED DURATION IN TABLE B105.1(2) PER 2022 CFC TABLE B105.2.

3. REDUCTION OF FIRE FLOW LIMITED TO 50% MAX. REDUCTION PER CITY OF GILROY ORDINANCE NO 2025-07.

4. NUMBER OF HYDRANTS PROVIDED PER SPACING REQUIREMENTS IN 2025 CFC APPENDIX C, TABLE C102.1.

NOTES:

ADJUSTED REQUIRED FLOW
2,3
: 1,250 GPM (2 HOURS)

FIRE FLOW ANALYSIS
CONSTRUCTION TYPE: TYPE V-B, FULLY SPRINKLERED
Revision Date
408-780-7200 Office
60 South Market Street, Suite 1250
San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked By
Scale
Job Number Submittal Date 70% SCHEMATIC DESIGN 03/10/2026 100% SD / BRIDGING DOCS 03/26/2026 This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
1/8" = 1'-0"

SANTA TERESA FIRE STATION
1330 WEST LUCHESSA AVENUEGILROY, CA 95020
GRIFFIN STRUCTURES, INC.

CODE ANALYSIS &

EGRESS PLAN
G2.01
33236
Checker

KEYNOTES

08.01 EMERGENCY ESCAPE CASEMENT WINDOW WITH MINIMUM 5 SF NET CLEAR OPENING AND COMPLIANT PER CBC R310.

CODE ANALYSIS
LEGEND
1/8" = 1'-0"
CODE ANALYSIS & EGRESS PLAN G2.01 05 PROJECT NORTH
N

PLUMBING ANALYSIS

Page 221 of 256 ends

E E FW FW SD SD
W
W 1. THE INTENT OF THE DEMOLITION PLAN IS TO DESCRIBE IN GENERAL THE DEMOLITION AREAS AFFECTED BY THE PROJECT CONSTRUCTION. IT IS NOT INTENDED AS A DETAILED DESCRIPTION OF EXISTING ITEMS OR ELEMENTS TO BE REMOVED. THE DESIGN-BUILD ENTITY (DBE) SHALL VISIT THE SITE AND REVIEW ANY AVAILABLE RECORD DOCUMENTS TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS AND SHOULD INCLUDE THE REMOVAL OF ALL ITEMS NECESSARY FOR THE PROPER EXECUTION AND COMPLETION OF THE WORK. THE CONTRACT DOCUMENTS ARE COMPLEMENTARY, AND WHAT IS REQUIRED BY ONE SHALL BE BINDING AS IF REQUIRED BY ALL TO THE EXTENT THAT IT IS REASONABLY INFERABLE FROM THEM AS BEING NECESSARY TO PRODUCE THE INTENDED RESULTS. 2. REMOVE EXISTING BUILDINGS, FOUNDATIONS AND SERVICE UTILITIES AS INDICATED ON PLANS. CAP ALL UTILITIES AT APPROPRIATE POINTS. ALL EXISTING ELECTRICAL / TELEPHONE / CATV UTILITIES SHALL BE REMOVED AS INDICATED OR BACK TO THE POINT WHERE THE SPECIFIC UTILITY SYSTEM ENTERS THE WORK AREA. COORDINATE DEMOLITION OF ALL UTILITIES WITH THE OWNER. ALL UTILITIES CONNECTED TO EXISTING BUILDINGS TO REMAIN SHALL CONTINUE TO BE OPERATIONAL DURING THE DEMOLITION PROCESS. DOMESTIC AND FIRE SERVICE WATER AND NATURAL GAS SHALL BE REMOVED TO A POINT OUTSIDE THE PERIMETER OF PROPOSED NEW CONSTRUCTION TO EXISTING VALVES OR SIMILAR SHUT-OFF DEVICES. IF A SHUT-OFF DEVICE IS NOT REASONABLY ADJACENT TO THE PERIMETER OF THE PROPOSED NEW CONSTRUCTION, PROVIDE A SHUT-OFF DEVICE IN BELOW-GRADE YARD BOX. CONFIRM LOCATION OF NEW DEVICES WITH OWNER PRIOR TO INSTALLATION. SANITARY SEWER AND STORM DRAINAGE SHALL BE CAPPED TO A POINT OUTSIDE THE PERIMETER OF THE PROPOSED NEW CONSTRUCTION. OTHER UTILITIES NOT SPECIFICALLY IDENTIFIED IN THESE DOCUMENTS AND NOT ANTICIPATED FOR REUSE SHALL BE REMOVED IN ENTIRETY. 3. FOR ALL EXISTING MATERIALS THAT CAN BE SALVAGED, OWNER HAS FIRST RIGHT OF REFUSAL FOR REMOVED ITEMS THAT MAY HAVE RESIDUAL COMMERCIAL OR HISTORIC VALUE INCLUDING HARDWARE, GLASS, CORNER STONES, TIME CAPSULES, LIGHT STANDARDS, SIGNS, FENCING, BENCHES, WATER FOUNTAINS, TRASH CONTAINERS, ETC. SHALL REMAIN AS PROPERTY OF THE OWNER. ALL ITEMS TO BE SALVAGED FOR REUSE/REINSTALLATION MUST MEET CURRENT CODE REQUIREMENTS. COORDINATE ITEMS TO BE RETAINED WITH OWNER AND REMOVE FROM CONSTRUCTION SITE TO A LOCATION APPROVED BY OWNER. REMOVED MATERIALS, NOT INDICATED OR DIRECTED TO BE SALVAGED FOR THE OWNER'S BENEFIT ARE DEBRIS AND BECOME THE DBE'S PROPERTY UPON REMOVAL. 4. THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITY PIPES OR STRUCTURES SHOWN ON THESE PLANS ARE OBTAINED BY SEARCH OF THE AVAILABLE RECORDS AND FIELD SURVEYS. THE DBE SHALL CONTACT UNDERGROUND SERVICE ALERT, UTILITY COMPANIES, AND/OR FIELD VERIFY AND LOCATE ALL UTILITIES BEFORE PROCEEDING WITH WORK. THE DBE IS ALSO REQUIRED TO TAKE DUE PRECAUTIONARY MEASURES TO PROTECT THE UTILITY LINES SHOWN AND ANY OTHER LINES NOT OF RECORD OR NOT SHOWN ON THESE PLANS. NOTIFY THE ENGINEER IF ADDITIONAL UTILITIES ARE LOCATED OR IF CONFLICTS ARE FOUND WITH EXISTING CONDITIONS. 5. ALL TREES TO BE REMOVED SHALL BE MARKED BY DBE AND APPROVED FOR REMOVAL BY THE OWNER OR OWNER'S REPRESENTATIVE PRIOR TO REMOVING OR CUTTING TREE(S). EXISTING ROOTS SHALL BE GRINDED TO A DEPTH OF APPROXIMATELY 3-FEET. USE CAUTION WHILE GRINDING WHEN EXISTING UTILITIES ARE IN CLOSE PROXIMITY TO TREES. ALL TREES TO REMAIN WITHIN THE LIMIT OF WORK SHALL BE PROTECTED AND MAINTAINED PER SPECIFICATIONS AND DETAILS. 6. SAWCUT EXISTING CONCRETE AND ASPHALT TO AN EXISTING CONTROL JOINT WHERE POSSIBLE, AT MINIMUM TO A NEAT-STRAIGHT LINE. ALL DEBRIS SHALL BE HAULED OFFSITE TO A LEGAL DUMPING SITE OR SALVAGED FOR REUSE ON PROJECT AS NOTED. 7. WORK WITHIN CITY, COUNTY, OR STATE RIGHT-OF-WAY REQUIRES A SEPARATE ENCROACHMENT PERMIT WHICH THE DBE IS RESPONSIBLE FOR OBTAINING PRIOR TO STARTING WORK WITHIN RIGHT-OF-WAY. 8. DBE TO COORDINATE UTILITY DEMOLITION WITH DRAINAGE AND UTILITY WORK SHOWN IN THIS PLAN SET. ALL UTILITY SHUTDOWNS SHALL BE COORDINATED PER PROJECT SPECIFICATIONS. 9. EXISTING DRY UTILITIES SHOWN FOR DEMOLITION ARE SHOWN FOR COORDINATION ONLY. REFER TO OTHER DISCIPLINES FOR LIMITS AND DETAILS OF DEMOLITION. 10. THE DBE SHALL RECYCLE CONSTRUCTION DEBRIS, ASPHALT, AND CONCRETE GENERATED FROM REMOVALS REQUIRED TO CONSTRUCT THE PROJECT. THE DBE IS TO RECYCLE THE WASTE MATERIAL THROUGH AN APPROVED RECYCLING PLANT. 11. A LIST OF FACILITIES THAT ACCEPT CONSTRUCTION & DEMOLITION DEBRIS CAN BE FOUND ON THE CALRECYCLE WEBSITE AT: HTTPS://WWW.CALRECYCLE.CA.GOV/CONDEMO 1. THE DBE SHALL CONTACT THE RESPECTIVE UTILITY OWNERS FOR LOCATION, REMOVAL, AND/OR RELOCATION OF ANY UTILITY SERVICES AFFECTED BY CONSTRUCTION. THE DBE SHALL TAKE ALL NECESSARY PRECAUTIONARY MEASURES TO PROTECT UNDERGROUND OR OVERHEAD STRUCTURES WHETHER OR NOT THEY ARE SHOWN ON THESE DRAWINGS. 2. THE DBE SHALL NOTIFY THE PROJECT INSPECTOR AND THE RESPECTIVE UTILITY OWNERS AND OTHER AGENCIES AT LEAST TWO WORKING DAYS PRIOR TO START OF CONSTRUCTION. 3. THE DBE SHALL BE RESPONSIBLE FOR EXPOSING, VERIFYING LOCATIONS (BOTH HORIZONTAL AND VERTICAL), AND MAINTAINING ALL EXISTING UNDERGROUND UTILITIES, BOTH SHOWN ON THE PLANS AND/OR NOT SHOWN ON THE PLANS DURING CONSTRUCTION. REPAIR DAMAGED UTILITIES TO THE SATISFACTION OF THE ENGINEER. THE DBE SHALL LOCATE EXISTING UNDERGROUND UTILITIES SUFFICIENTLY AHEAD OF CONSTRUCTION TO PERMIT REVISIONS TO PLANS BECAUSE OF LOCATIONS OF EXISTING FACILITIES AND SHALL REPORT ALL DISCREPANCIES TO THE ENGINEER PRIOR TO THE COMMENCEMENT OF WORK. 4. THE EXISTENCE AND LOCATION OF ANY UNDERGROUND UTILITIES AND/OR STRUCTURES SHOWN ON THESE PLANS WERE OBTAINED BY A SEARCH OF THE AVAILABLE RECORDS. APPROVAL OF THESE PLANS DOES NOT CONSTITUTE A REPRESENTATION AS TO THE ACCURACY OR COMPLETENESS OF THE LOCATION OR THE EXISTENCE, OR NON-EXISTENCE OF ANY UTILITY AND/OR STRUCTURE WITHIN THE LIMITS OF THIS PROJECT. THE DBE IS REQUIRED TO TAKE ALL DUE PRECAUTIONARY MEASURES TO PROTECT THE UTILITIES OF RECORD AND/OR NOT OF RECORD SHOWN OR NOT SHOWN AND ANY OTHER LINE(S) OR STRUCTURE(S) NOT SHOWN ON THESE PLANS. THE DBE IS RESPONSIBLE FOR THE PROTECTION OF, AND/OR DAMAGE TO THESE LINE(S) AND/OR STRUCTURE(S). 5. THE DBE SHALL BE RESPONSIBLE FOR TEMPORARY SHORING AT PROPOSED BUILDING FOUNDATIONS, FOOTINGS, AND WALLS TO PROTECT EXISTING UTILITIES IN PLACE. 6. UNAUTHORIZED CHANGES AND USES - CAUTION: THE ENGINEER PREPARING THESE PLANS WILL NOT BE RESPONSIBLE FOR, OR LIABLE FOR, UNAUTHORIZED CHANGES TO OR USES OF THESE PLANS. ALL CHANGES TO THE PLANS MUST BE IN WRITING AND MUST BE APPROVED BY THE PREPARER OF THESE PLANS. 7. THE DBE SHALL MAINTAIN THE EXISTING ACCESSIBLE ROUTE CLEAR OR PROVIDE AN ALTERNATE ACCESSIBLE ROUTE OF TRAVEL DURING DEMOLITION AND/OR CONSTRUCTION. 8. THE DBE SHALL MAINTAIN THE EXISTING FIRE EXITS AND STAIRS CLEAR AND USABLE OR PROVIDE ALTERNATE FIRE EXITS DURING DEMOLITION AND/OR CONSTRUCTION. PORTIONS OF DEMOLITION MAY REQUIRE BLOCKING AND/OR OBSTRUCTING THROUGH ACCESS TO EMERGENCY / FIRE ACCESS VEHICLES. IT SHALL BE THE SOLE RESPONSIBILITY OF THE DESIGN-BUILD ENTITY (DBE) TO PROVIDE A FIRE WATCH SPECIALIST SERVICE FOR THE DURATION OF TIME THAT EMERGENCY / FIRE ACCESS VEHICLES ARE BLOCKED AND/OR OBSTRUCTED DURING CONSTRUCTION UNLESS EQUIVALENT ALTERNATE MEASURES ARE TAKEN TO ENSURE CONTINUOUS ACCESS TO EMERGENCY / FIRE ACCESS VEHICLES. DBE TO COORDINATE THROUGH ACCESS TO EMERGENCY / FIRE ACCESS VEHICLES WITH THE LOCAL FIRE AUTHORITY HAVING JURISDICTION. FOR SITE PREPARATION, OVEREXCAVATION, FOUNDATION RECOMMENDATIONS, PAVEMENT, SUBGRADE, AND GRADATION REQUIREMENTS SEE DRAFT GEOTECHNICAL INVESTIGATION REPORT ENTITLED: "GEOTECHNICAL INVESTIGATION SANTA TERESA FIRE STATION SOUTHEAST CORNER OF WEST LUCHESSA AVENUE AND MILLER AVENUE GILROY, CALIFORNIA" PREPARED BY: GEOCON CONSULTANTS, INC 6671 BRISA STREET LIVERMORE, CA 94550 PROJECT NO: E9213-04-06 DATED: JANUARY 9, 2026 1. IT IS THE DESIGN-BUILD ENTITY'S (DBE) RESPONSIBILITY TO REVIEW THE GRADING PLANS AND SOILS REPORT THOROUGHLY PRIOR TO SITE MOBILIZATION. IT IS ALSO THE GRADING DBE'S RESPONSIBILITY TO NOTIFY THE CIVIL AND SOILS ENGINEERS IF ONSITE DISCREPANCIES ARE OBSERVED THAT WOULD AFFECT THE EARTHWORK QUANTITIES. 2. THE EXISTING TOPOGRAPHY AS DELINEATED ON THESE DRAWINGS SHALL BE UTILIZED AS THE BASIS FOR ALL EARTHWORK COMPUTATIONS. SAID TOPOGRAPHY SHALL BE PRESUMED TO BE ACCEPTABLE TO ALL INTERESTED PARTIES UNLESS A DEVIATION IS FOUND PRIOR TO THE START OF GRADING IN ANY SPECIFIC AREAS. ANY DEVIATION SO DETERMINED SHALL BE PROMPTLY TRANSMITTED TO ALL INTERESTED PARTIES. 3. THE DBE IS REQUIRED TO ESTIMATE THE QUANTITIES OF GRADING WORK TO BE DONE AND INCLUDE ALL COSTS THEREFROM WITH HIS BID, AS NO ADDITIONAL ALLOWANCE WILL BE MADE WITHOUT PRIOR CONSENT FROM THE OWNER. 4. OVER-EXCAVATION AND/OR EXCESS BACKFILLING OR DUPLICATION OF GRADING ACTIVITIES IS NOT A BASIS FOR ADDITIONAL COMPENSATION. THIS ALSO APPLIES WHERE MATERIAL IS TO BE REMOVED AND REPLACED TO REDUCE MOISTURE CONTENT. 5. OFF-SITE DISPOSAL OF EXCAVATION MATERIAL IS THE RESPONSIBILITY OF THE DBE AND SHALL BE INCLUDED IN THE BID. THE DBE SHALL HOLD THE OWNER AND ENGINEER HARMLESS AS A RESULT OF ANY CLAIMS ARISING FROM THE ACTIONS ENROUTE OR AWAY FROM THE SITE. 6. EARTH VOLUMES SHOWN HEREON ARE ESTIMATES BASED UPON THE GEOTECHNICAL ANALYSIS PERFORMED BY THE NAMED SOILS ENGINEER AND TOPOGRAPHIC SURVEY OF THE EXISTING GROUND SURFACE AT THE TIME OF PLAN PREPARATION. EARTHWORK VOLUMES ARE COMPUTED BY METHODS COMMONLY USED IN STANDARD ENGINEERING PRACTICE, AND ARE INTENDED FOR USE IN ESTABLISHING GOVERNING AGENCY FEES. ACTUAL FIELD CONDITIONS MAY VARY FROM OBSERVED OR MEASURED CONDITIONS AT THE TIME OF PLAN PREPARATION. EARTHWORK QUANTITIES MAY VARY AS A RESULT. 7. ANY EXPORT OR IMPORT REQUIRED TO BALANCE THE SITE SHALL BE THE SOLE RESPONSIBILITY OF THE DBE. 8. PAVEMENT AND SUBGRADE RECOMMENDATIONS RELATED TO OVER-EXCAVATION, PAVEMENT SUBGRADE, ETC., PER GEOTECHNICAL REPORT. CADD FILES OF TOPOGRAPHY AND SURVEY PROVIDED BY THE CITY OF GILROY DO NOT CONTAIN VERTICAL AND HORIZONTAL DATUM INFORMATION. DEDICATED PRIVATE FIRE SERVICE REMOVE EXISTING UTILITY SANITARY SEWER LINE DOMESTIC WATER LINE STORM DRAIN LINE (≤8" DIAMETER) FLOW LINE 1. DESIGN-BUILD ENTITY (DBE) SHALL ENSURE THAT THE CONSTRUCTION SITE IS PREPARED PRIOR TO THE START OF CONSTRUCTION. DBE SHALL HAVE ALL EROSION AND SEDIMENT CONTROL MEASURES IN PLACE AT ALL TIMES DURING CONSTRUCTION. 2. ALL EROSION AND SEDIMENT CONTROL MEASURES SHALL BE MAINTAINED UNTIL DISTURBED AREAS ARE STABILIZED. 3. ALL EROSION AND SEDIMENT CONTROL MEASURES SHALL BE CHECKED BEFORE AND AFTER ALL STORMS TO ENSURE MEASURES ARE FUNCTIONING PROPERLY. 4. DBE SHALL MAINTAIN A LOG AT THE SITE OF ALL INSPECTIONS OR MAINTENANCE OF BMPS, AS WELL AS, ANY CORRECTIVE CHANGES TO THE BMPS OR EROSION AND SEDIMENT CONTROL PLAN. 5. IN AREAS WHERE SOIL IS EXPOSED, PROMPT REPLANTING WITH NATIVE COMPATIBLE, DROUGHT-RESISTANT VEGETATION SHALL BE PERFORMED. NO AREAS WILL BE LEFT EXPOSED OVER THE WINTER SEASON. 6. THE DBE SHALL INSTALL THE STABILIZED CONSTRUCTION ENTRANCE PRIOR TO COMMENCEMENT OF GRADING. LOCATION OF THE ENTRANCE MAY BE ADJUSTED BY THE DBE TO FACILITATE GRADING OPERATIONS. ALL CONSTRUCTION TRAFFIC ENTERING THE PAVED ROAD MUST CROSS THE STABILIZED CONSTRUCTION ENTRANCE. 7. ALL SEDIMENT DEPOSITED ON PAVED ROADWAYS SHALL BE SWEPT AT THE END OF EACH WORKING DAY OR MORE OFTEN AS NECESSARY. 8. DBE SHALL PLACE GRAVEL/SAND BAGS AROUND ALL NEW DRAINAGE STRUCTURE OPENINGS IMMEDIATELY AFTER THE STRUCTURE OPENING IS CONSTRUCTED. THESE GRAVEL/SAND BAGS SHALL BE MAINTAINED AND REMAIN IN PLACE UNTIL CONSTRUCTION IS COMPLETED. 9. DBE SHALL IMPLEMENT HOUSEKEEPING PRACTICES AS FOLLOWS: A. SOLID WASTE MANAGEMENT: PROVIDE DESIGNATED WASTE COLLECTION AREAS AND CONTAINERS. ARRANGE FOR REGULAR REMOVAL AND DISPOSAL. CLEAR SITE OF TRASH INCLUDING ORGANIC DEBRIS, PACKAGING MATERIALS, SCRAP OR SURPLUS BUILDING MATERIALS AND DOMESTIC WASTE DAILY. B. MATERIAL DELIVERY AND STORAGE: PROVIDE A DESIGNATED MATERIAL STORAGE AREA WITH SECONDARY CONTAINMENT SUCH AS BERMING. STORE MATERIAL ON PALLETS AND PROVIDE COVERING FOR SOLUBLE MATERIALS. RELOCATE STORAGE AREA INTO BUILDING SHELL WHEN POSSIBLE. INSPECT AREA WEEKLY. C. CONCRETE WASTE: PROVIDE A DESIGNATED AREA FOR A TEMPORARY PIT TO BE USED FOR CONCRETE TRUCK WASH-OUT. CONCRETE WASHOUT CANNOT BE WITHIN 50' MINIMUM OF DRAIN INLETS. DISPOSE OF HARDENED CONCRETE OFFSITE. AT NO TIME SHALL A CONCRETE TRUCK DUMP ITS WASTE AND CLEAN ITS TRUCK INTO THE STORM DRAINS VIA CURB AND GUTTER. INSPECT DAILY TO CONTROL RUNOFF, AND WEEKLY FOR REMOVAL OF HARDENED CONCRETE. D. PAINT AND PAINTING SUPPLIES: PROVIDE INSTRUCTION TO EMPLOYEES AND SUBDBES REGARDING REDUCTION OF POLLUTANTS INCLUDING MATERIAL STORAGE, USE, AND CLEAN UP. INSPECT SITE WEEKLY FOR EVIDENCE OF IMPROPER DISPOSAL. E. VEHICLE FUELING, MAINTENANCE AND CLEANING: PROVIDE A DESIGNATED FUELING AREA WITH SECONDARY CONTAINMENT SUCH AS BERMING. DO NOT ALLOW MOBILE FUELING OF EQUIPMENT. PROVIDE EQUIPMENT WITH DRIP PANS. RESTRICT ONSITE MAINTENANCE AND CLEANING OF EQUIPMENT TO A MINIMUM. INSPECT AREA WEEKLY. F. HAZARDOUS WASTE MANAGEMENT: PREVENT THE DISCHARGE OF POLLUTANTS FROM HAZARDOUS WASTES TO THE DRAINAGE SYSTEM THROUGH PROPER MATERIAL USE, WASTE DISPOSAL AND TRAINING OF EMPLOYEES. HAZARDOUS WASTE PRODUCTS COMMONLY FOUND ON-SITE INCLUDE BUT ARE NOT LIMITED TO PAINTS & SOLVENTS, PETROLEUM PRODUCTS, FERTILIZERS, HERBICIDES & PESTICIDES, SOIL STABILIZERS, STABILIZATION PRODUCTS, ASPHALT PRODUCTS AND CONCRETE CURING PRODUCTS. 11. DBE SHALL HYDROSEED ALL GRADED SLOPES. NATIVE SEED MIX SHALL BE 20% LANA PUBESCENT WHEAT GRASS, 40% BLANDO BROME, AND 40% ANNUAL RYE GRASS AND SHALL BE APPLIED AT A RATE OF 200 POUNDS PER ACRE. SOIL BINDING AGENT SHALL BE VERDYOL, SENTINEL, OR EQUAL, APPLIED AT A RATE OF 110 POUNDS PER ACRE. MULCH SHALL BE SILVER-FIBER, CONWED, OR EQUAL, APPLIED AT A RATE OF 1,000 POUNDS PER ACRE. FERTILIZER SHALL BE AGRI-FORM 16-7-12, BEST 16-6-8, OR EQUAL, APPLIED AT A RATE OF 500 POUNDS PER ACRE. THE DBE SHALL WATER SEEDED AREAS OR RESEED AS NECESSARY TO ENSURE SUFFICIENT PLANT DEVELOPMENT FOR EROSION CONTROL. 12. NO GRADING SHALL BE DONE UNTIL SITE- AND SEASON-SPECIFIC SOIL LOSS AND HOUSEKEEPING STORMWATER BMPs HAVE BEEN APPROVED BY THE INSPECTOR. THE DBE SHOULD EMPLOY THE DESIGN BMPs AND ANY OTHERS NEEDED AS SITUATIONS ARISE. DBE SHOULD CONDUCT SITE INSPECTIONS BEFORE, DURING AND AFTER EACH EXTENDED STORM EVENT TO IDENTIFY CONDITIONS THAT MAY CONTRIBUTE TO EROSION AND SEDIMENT PROBLEMS OR ANY OTHER POLLUTANT DISCHARGES. IF ADDITIONAL CONTROL MEASURES ARE NEEDED, DBE SHOULD IMPLEMENT THEM IMMEDIATELY. RIGHT OF WAY/ PROPERTY LINE FENCE APPROXIMATE CUT: 16 CY APPROXIMATE FILL: 2,684 CY NOTES: 1. PRELIMINARY EARTHWORK QUANTITIES INDICATED ARE BASED ON COMPARING PROPOSED GROUND TO EXISTING GROUND. SHRINKAGE FACTOR, UNDERCUT OF BUILDING SLAB/PAVEMENT, TRENCH SPOILS AND OVER-EXCAVATION ARE NOT TAKEN INTO ACCOUNT. 2. EARTHWORK QUANTITIES INDICATED ARE FOR REFERENCE ONLY. DESIGN-BUILD ENTITY (DBE) IS RESPONSIBLE FOR ACTUAL QUANTITIES. AB AGGREGATE BASE AC ASPHALT CONCRETE PAVEMENT AE ACCESS EASEMENT ASPH ASPHALT PAVING BC BEGIN CURVATURE BCR BEGIN CURB RETURN BFP BACK FLOW PREVENTER BI BOX INLET BM BENCHMARK BOP BOTTOM OF PIPE BOR BOTTOM OF RAMP BS BOTTOM OF STAIRS BVC BEGIN VERTICAL CURVATURE BW BOTTOM OF WALL C&G CURB AND GUTTER C/L,CL CENTER LINE CB CATCH BASIN CONST CONSTRUCT CR CURB RETURN CT COURT CUL CULVERT DI DROP INLET DIP DUCTILE IRON PIPE DW DOMESTIC WATER D/W DRIVEWAY DE DRAINAGE EASEMENT DR DRIVE (E) EXISTING

E EAST EC END CURVATURE ECR END CURB RETURN EG EXISTING GRADE ELEV ELEVATION EOC EDGE OF CONCRETE EP EDGE OF PAVEMENT EQ EQUAL ESMT EASEMENT EVC END OF VERTICAL CURVATURE FF FINISHED FLOOR FFE FINISHED FLOOR ELEVATION FG FINISHED GRADE FH FIRE HYDRANT FL FLOWLINE FS FINISHED SURFACE FW FIRE PROTECTION SERVICE WATER GB GRADE BREAK GFL GUTTER FLOWLINE GSL LIMITS OF GRAVITY SEWER GR GRATE GV GAS VALVE HB HOSE BIB HP HIGH POINT ICV IRRIGATION CONTROL VALVE INTX POINT OF INTERSECTION INV INVERT JP JOINT POLE LE LANDSCAPE EASEMENT LF LINEAR FEET LIP LIP OF GUTTER LP LOW POINT LT LEFT MAX MAXIMUM MH MANHOLE MIN MINIMUM MOC MIDDLE OF CURVATURE

N NORTH NG NATURAL GRADE NTS NOT TO SCALE OC ON CENTER (P) PROPOSED, NEW PA PLANTING AREA PBC PULL BOX CABLE PBE PULL BOX ELECTRIC PBT PULL BOX TELEPHONE PBW PULL BOX WATER PCC POINT OF COMPOUND CURVATURE PE PEDESTRIAN EASEMENT PI POINT OF INTERSECTION PIVC POINT OF INTERSECTION VERTICAL CURVATURE PL PROPERTY LINE POC POINT OF CONNECTION PP POWER POLE PRC POINT OF REVERSE CURVATURE PVC POLYVINYL CHLORIDE PVMT PAVEMENTR RADIUS RCP REINFORCED CONCRETE PIPE RIM TOP RIM OF STRUCTURE ROW HIGHWAY EASEMENT RT RIGHT RW RECLAIMED WATER R/W RIGHT OF WAY

S SOUTH OR SLOPE SBE SETBACK EASEMENT SCO SANITARY SEWER CLEANOUT SD STORM DRAIN SDMH STORM DRAIN MANHOLE SF SQUARE FEET SHT SHEET STA STATION SMH SANITARY SEWER MANHOLE SS SANITARY SEWER SWPPP STORM WATER POLLUTION PREVENTION PLAN S/W SIDEWALK

T TANGENT TB TOP OF BERM TBC TOP BACK OF CURB TBW TOP BACK OF WALK TC TOP OF CURB TF TOP OF FOOTING TG TOP OF GRATE TOE TOE OF SLOPE TOP TOP OF PIPE TOR TOP OF RAMP TOS TOP OF SLOPE TP TOP OF PLANTER TS TOP OF STAIRS TW TOP OF WALL TYP TYPICAL TP TELEPHONE POLE VC VERTICAL CURVATURE W WEST WM WATER MAIN WV WATER VALVE EXISTING ELECTRICAL LINE / CONDUIT EXISTING DEDICATED PRIVATE FIRE SERVICE EXISTING STORM DRAIN LINE EXISTING WATER LINE EXISTING SEWER LINE GRADE BREAK LINE TOTAL DISTURBED AREA = 1.2± ACRES PURSUANT TO THE CALIFORNIA GOVERNMENT CODE SECTION 4216, NO EXCAVATION PERMIT IS VALID UNLESS DIG ALERT HAS BEEN CONTACTED AT LEAST TWO (2) WORKING DAYS PRIOR TO THE COMMENCEMENT OF EXCAVATION AND AN INQUIRY IDENTIFICATION NUMBER HAS BEEN ISSUED. INQUIRY ID# 1. ALL ASBESTOS CEMENT PIPE TO BE REMOVED SHALL BE SNAPPED, ENCAPSULATED, AND DISPOSED OF PER LOCAL, STATE, AND FEDERAL REGULATIONS. 2. DOMESTIC WATER SERVICE AND FIRE PROTECTION SHALL BE MAINTAINED DURING CONSTRUCTION. PROVIDE BYPASS LINES DURING CONSTRUCTION INCLUDING TIE-IN. COORDINATE ALL SHUT DOWNS OF WATER AND POWER WITH OWNER PRIOR TO CONSTRUCTION. 3. PURSUANT TO CALIFORNIA ASSEMBLY BILL 1953 ALL PIPE, FITTINGS, AND FIXTURES INTENDED TO CONVEY OR DISPENSE WATER FOR HUMAN CONSUMPTION THROUGH DRINKING WATER OR COOKING SHALL BE "LEAD FREE" AS OF JANUARY 1, 2010. IN ORDER TO MEET THE REQUIREMENTS OF THE NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM (NPDES) PROGRAM FOR CONSTRUCTION, DESIGN-BUILD ENTITY SHALL INSTALL AND MAINTAIN APPROPRIATE BEST MANAGEMENT PRACTICES (BMPS), AS SHOWN IN THE EROSION CONTROL PLAN AND IN ACCORDANCE WITH THE SWPPP (STORM WATER POLLUTION PREVENTION PLAN), ON ALL CONSTRUCTION PROJECTS. BMPS SHALL BE INSTALLED IN ACCORDANCE WITH INDUSTRY RECOMMENDED STANDARDS, AND/OR IN ACCORDANCE WITH ANY GENERAL CONSTRUCTION PERMIT ISSUED BY THE STATE FOR THE PROJECT TO PREVENT ANY DISCHARGES FROM THE PROJECT SITE OR INTO ANY STORM DRAIN FACILITIES. ALL SEDIMENTS, CONSTRUCTION MATERIALS, DEBRIS AND WASTES, AND OTHER POLLUTANTS MUST BE RETAINED ON SITE AND MAY NOT BE TRANSPORTED FROM THE SITE VIA SHEET FLOW, SWALES, AREA DRAINS, NATURAL DRAINAGE COURSES, WIND, OR VEHICLE TRACKING. UNDER DIRECTION OF THE ENGINEER OF RECORD, EROSION AND/OR SEDIMENT CONTROL DEVICES SHALL BE MODIFIED AS NEEDED AS THE PROJECT PROGRESSES TO ENSURE EFFECTIVENESS. NTS C0.01 CIVIL NOTES C0.02 EXISTING CONDITIONS PLAN C1.01 DEMOLITION PLAN C2.01 CONCEPTUAL GRADING PLAN C3.01 CONCEPTUAL STORM DRAIN PLAN C4.01 CONCEPTUAL UTILITY PLAN PERFORATED STORM DRAIN LINE G

G EXISTING NATURAL GAS SERVICE
T
T EXISTING TELECOMMUNICATIONS LINE / CONDUIT 1. FOLLOWING OWNER ACCEPTANCE OF CONSTRUCTION WORK, POST CONSTRUCTION BEST MANAGEMENT PRACTICE (BMP) MEASURES SHALL BE MAINTAINED BY THE PROPERTY OWNER, INCLUDING BUT NOT LIMITED TO: 1.1. ANNUAL INSPECTION, REPLACEMENT, AND/OR SEDIMENTATION REMOVAL OF VEGETATED SWALES, TREATMENT PONDS, AND OTHER SURFACE STORMWATER TREATMENT MEASURES AS REQUIRED WITH AN INCREASED FREQUENCY BASED ON SITE CONDITIONS. 1.2. MAINTENANCE SERVICE AGREEMENT(S) OF STORMWATER TREATMENT VAULTS, INLETS, MANHOLES, AND OTHER DEVICES BASED ON MANUFACTURES' RECOMMENDATIONS AND FREQUENCY. 1.3. ANNUAL INSPECTION OF PERMEABLE PAVEMENT AND REMOVAL OF SEDIMENT AS NEEDED. 1.4. ANNUAL INSPECTION OF STORMWATER INLETS AND MAINTENANCE AS REQUIRED TO CLEAR GRATES AND INLETS OF DEBRIS. 1.5. THE PROJECT STORMWATER POLLUTION PREVENTION PLAN (SWPPP) AND WATER QUALITY MANAGEMENT PLAN (WQMP) MAY CONTAIN ADDITIONAL OR MORE STRINGENT MAINTENANCE REQUIREMENTS. 2. BMP DETAILS MAY BE FOUND IN APPENDIX H OF THE PROJECT SWPPP DOCUMENT. BMP DETAILS PER CALIFORNIA STORMWATER QUALITY ASSOCIATION (CASQA) AND ARE AVAILABLE AT www.casqa.org. 3. FOR PROJECTS GREATER THAN 1 ACRE: THE DBE SHALL VERIFY THE STATUS OF THE SWPPP/NOI/WDID PRIOR TO EARTHMOVING ACTIVITIES. A STORMWATER POLLUTION PREVENTION PLAN (SWPPP) SHALL BE PREPARED AND A NOTICE OF INTENT (NOI) SHALL BE FILED WITH THE STATE WATER RESOURCES CONTROL BOARD (SWRCB) IN ACCORDANCE WITH THE REQUIREMENTS OF CALIFORNIA GENERAL PERMIT FOR STORMWATER DISCHARGES ASSOCIATED WITH CONSTRUCTION ACTIVITY (PERMIT NO.

CAS000002) FOR ALL OPERATIONS ASSOCIATED WITH THESE PLANS. THE DBE SHALL KEEP A COPY OF THE SWPPP ON SITE AND AVAILABLE FOR REVIEW. 1. FIRE WATER PIPE, FITTINGS, AND APPURTENANCES SHALL COMPLY WITH NFPA 24 INCLUDING BUT NOT LIMITED TO THE FOLLOWING: 1.1. FIRE DEPARTMENT CONNECTIONS (FDC) SHALL BE PER NFPA 24-5.9. 1.2. FDC LOCATION AND SIGNAGE SHALL BE PER NFPA 24-5.9.5. 1. PRIOR TO INSTALLATION, ALL PLANS AND SPECIFICATIONS SHALL BE APPROVED BY GOVERNING AGENCY. 2. INSPECTIONS ARE REQUIRED: 1) PRIOR TO POURING THRUST BLOCKS 2) FOR HYDROSTATIC TESTING 3) FOR FLUSH 3. INSTALLATION, INSPECTION, AND TESTING SHALL CONFORM TO 2022 NFPA 13 AND 2019 NFPA 24. 4. PRIVATE FIRE HYDRANTS SHALL BE APPROVED WET BARREL STYLE WITH A MINIMUM OF ONE 2 1 2" AND ONE 4" OUTLET. THE 4" OUTLET SHALL FACE THE FIRE DEPARTMENT ACCESS ROAD. ALL OUTLETS SHALL BE PROVIDED WITH NATIONAL STANDARD THREADS (NST). 5. FIRE HYDRANT SUPPLY PIPING SHALL BE A MINIMUM OF SIX INCHES IN DIAMETER. THE LOWEST OPERATING NUT SHALL BE MINIMUM OF 18" ABOVE GRADE AND THE FIRE HYDRANT FLANGE SHALL BE A MINIMUM OF 2" ABOVE GRADE. 6. FIRE HYDRANTS SHALL BE A MINIMUM OF 40 FEET FROM ALL STRUCTURES. A KEYED GATE VALVE SHALL BE PROVIDED FOR EACH FIRE HYDRANT IN AN ACCESSIBLE LOCATION. VALVES SHALL NOT BE LOCATED IN PARKING STALLS. 7. ALL PIPES SHALL BE APPROVED FOR USE IN FIRE SERVICE SYSTEMS (CLASS 900 DR-18 MINIMUM). CLASS 900 DR-14 PIPES SHALL BE USED WHERE THE PRESSURES MAY EXCEED 150 PSI. 8. ALL FERROUS PIPE AND FITTINGS SHALL BE PROTECTED WITH LOOSE 8-MIL POLYETHYLENE TUBE. THE ENDS OF THE TUBE AND ANY SPLICES MADE FOR T's OR OTHER PIPING COMPONENTS SHALL BE SEALED WITH 2" TAPE, APPROVED FOR UNDERGROUND USE. ALL BOLT JOINTS SHALL BE CLEANED AND THOROUGHLY COATED WITH ASPHALT OR OTHER CORROSION RETARDING MATERIAL AFTER ASSEMBLY AND PRIOR TO POLY-TUBE INSTALLATION. 9. A BED OF CLEAN FILL SAND SHALL BE PROVIDED ABOVE AND BELOW THE PIPE, A MINIMUM OF 12" ABOVE AND 6" BELOW. 10. ALL BOLTS USED FOR UNDERGROUND CONNECTIONS SHALL BE STAINLESS STEEL. 11. A MINIMUM OF 30" OF COVER, FROM FINISHED GRADE TO THE TOP OF THE PIPE SHALLBE PROVIDED. WHEN SURFACE LOADS ARE EXPECTED, A MINIMUM OF 36" COVER SHALL BE PROVIDED. 12. THRUST BLOCKS, OR OTHER APPROVED METHOD OF THRUST RESTRAINT, SHALL BE PROVIDED WHEREVER PIPE CHANGES DIRECTION. 13. THE TRENCH SHALL BE EXCAVATED FOR THRUST BLOCKS AND INSPECTED PRIOR TO POUR. ALL CORROSION PROTECTION SHALL BE IN PLACE. 14. A HYDROSTATIC TEST (200 PSI FOR TWO HOURS OR 50 PSI OVER MAXIMUM STATICPRESSURE, WHICHEVER IS GREATER) SHALL BE PERFORMED. BACKFILL BETWEEN THE JOINTS TO PREVENT MOVEMENT OF THE PIPE. 15. THE SYSTEM SHALL BE THOROUGHLY FLUSHED BEFORE CONNECTION IS MADE TO OVERHEAD PIPING. FLOW SHALL BE THROUGH A MINIMUM 4" HOSE PIPE. 16. PRIVATE HYDRANTS, SPRINKLER CONTROL VALVES, DETECTOR CHECK ASSEMBLIES, POST INDICATING VALVES AND FIRE DEPARTMENT CONNECTIONS SHALL BE PAINTED OSHA RED, UNLESS NOTED OTHERWISE. 17. THE CONTROL VALVES SHALL BE LOCKED IN THE OPEN POSITION. VALVES SHALL BE MONITORED IF THEY SERVE 6 OR MORE SPRINKLER HEADS. FIRE PROTECTION SYSTEM NOTES SS SS LINE TYPE DESCRIPTION DAYLIGHT LINE STORM DRAIN LINE (>8" DIAMETER) ABBREVIATIONS GENERAL EROSION AND SEDIMENT CONTROL NOTES DEMOLITION NOTES EARTHWORK NOTES PRELIMINARY EARTHWORK QUANTITIES LEGEND SYMBOL DESCRIPTION ROOF DRAIN POC 5' FROM BUILDING GAS POC 5' FROM BUILDING FIRE WATER POC 5' FROM BUILDING DOMESTIC WATER POC 5' FROM BUILDING SANITARY SEWER POC 5' FROM BUILDING STORM DRAIN MANHOLE SANITARY SEWER MANHOLE DRAIN INLET AREA DRAIN TRENCH DRAIN CLEANOUT BLOW OFF FIRE HYDRANT VALVE POST INDICATOR VALVE (PIV)/CHECK VALVE (CHK VLV)/FIRE DEPARTMENT CONNECTION (FDC) CHECK VALVE (CHK VLV) FIRE DEPARTMENT CONNECTION (FDC) DOUBLE DETECTOR CHECK (DBL CHK) REDUCED PRESSURE (BFP) POST INDICATOR VALVE (PIV) THRUST BLOCK BENDS, TEE AND CROSS WATER METER BENCHMARK LOCATION MAP GEOTECHNICAL INFORMATION FIRE WATER GENERAL NOTES: IMPORTANT NOTICE DEDICATED FIRE ACCESS DIG ALERT NOTICE GENERAL NOTES TO DESIGN-BUILD ENTITY (DBE) POLLUTION PREVENTION NOTES BMP MAINTENANCE NOTES AREA SUMMARY CIVIL SHEET INDEX AD XXLF S=X.XXX XXLF PVC XXLF S=X.XXX XXLF S=X.XXX GB XXLF PVC co M
DS 6"SS 8"FW6"SD 6"DW12"SD
N RDG
FWSS

N PROJECT LOCATION

SANTA TERESA BLVD LIMIT OF WORK

LUCHESSA
AVENUE

MILLER AVENUE
W. 10TH STREET

GREENFIELD DRIVE

CIMINO STREET
LOMA
RANCH STREET N/A C0.01 CIVIL NOTES
Revision Date
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION ARCHITECTURE ENGINEERING INTERIORS LANDSCAPE ARCHITECTURE PLANNING 408-780-7200 Office LPADesignStudios.com 60 South Market Street, Suite 1250 San Jose, California 95113 Developed for
Checked By Scale Job Number
Submittal Date
70% SCHEMATIC DESIGN 03/10/2026
This document and all other project documents, ideas
aesthetics and designs incorporated therein are instrumentsof service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of propertyrights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary lossesand damages including attorney fees and costs for which the unauthorized user will be held liable. Project documents describe the design intent of the workand are not a representation of as-built or existing conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
100% SD/BRIDGING DOCS 03/26/2026

SANTA TERESA FIRE STATION
GILROY, CA 95020
GRIFFIN STRUCTURES, INC. 33236.10 KS
1330 WEST LUCHESSA AVENUE

Page 222 of 256 ends

(E) PL
(E) PL
(E) R/W
(E) R/W W. LUCHESSA AVENUE

MILLER AVENUE
Revision Date
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION ARCHITECTURE ENGINEERING INTERIORS LANDSCAPE ARCHITECTURE PLANNING 408-780-7200 Office LPADesignStudios.com 60 South Market Street, Suite 1250 San Jose, California 95113 Developed for
Checked By Scale Job Number
Submittal Date
70% SCHEMATIC DESIGN 03/10/2026
This document and all other project documents, ideas
aesthetics and designs incorporated therein are instrumentsof service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of propertyrights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary lossesand damages including attorney fees and costs for which the unauthorized user will be held liable. Project documents describe the design intent of the workand are not a representation of as-built or existing conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
100% SD/BRIDGING DOCS 03/26/2026

SANTA TERESA FIRE STATION
GILROY, CA 95020
GRIFFIN STRUCTURES, INC. 33236.10 KS
1330 WEST LUCHESSA AVENUE EXISTING CONDITIONS PLAN 1"=20' 0 10 20 40 1"=20' EXISTING CONDITIONS PLAN C0.02 05

Page 223 of 256 ends

CLEAR AND GRUB (E) PL
(E) PL
(E) R/W PROTECT IN PLACE (E) SIDEWALK REMOVE (E) DRAIN INLET (297.39)TG PROTECT IN PLACE (E) SD INLET (298.36)TG (288.51)INV PROTECT IN PLACE (E) SD INLET (298.44)TG (288.54)INV PROTECT IN PLACE (E) SIDEWALK AND DRIVEWAY PROTECT IN PLACE (E) SIDEWALK AND DRIVEWAY (E) R/W W. LUCHESSA AVENUE

MILLER AVENUE
CONNECT (E) SD PIPE TO NEW DRAIN INLET PER SHEET C3.01
Revision Date
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION ARCHITECTURE ENGINEERING INTERIORS LANDSCAPE ARCHITECTURE PLANNING 408-780-7200 Office LPADesignStudios.com 60 South Market Street, Suite 1250 San Jose, California 95113 Developed for
Checked By Scale Job Number
Submittal Date
70% SCHEMATIC DESIGN 03/10/2026
This document and all other project documents, ideas
aesthetics and designs incorporated therein are instrumentsof service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of propertyrights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary lossesand damages including attorney fees and costs for which the unauthorized user will be held liable. Project documents describe the design intent of the workand are not a representation of as-built or existing conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
100% SD/BRIDGING DOCS 03/26/2026

SANTA TERESA FIRE STATION
GILROY, CA 95020
GRIFFIN STRUCTURES, INC. 33236.10 KS
1330 WEST LUCHESSA AVENUE DEMOLITION PLAN 1"=20' 0 10 20 40 1"=20' DEMOLITION PLAN C1.01 05

Page 224 of 256 ends

JOIN (299.05)BW JOIN (298.86)BW
(0.54%) JOIN (305.69)BW
(5.04%) JOIN (304.59)BW JOIN (304.20)BW
(4.68%) 300.20TC 299.70FS 305.76TC 305.26FS

2.70% 305.30TC 304.80FS 304.77TC 304.27FS 300.01TC 299.51FS 2.03% 1.71% (307.0)FG (306.0)FG (305.0)FG (304.0)FG (303.0)FG (302.2)FG (302.0)FG 303.00TC 302.50FS 4.87% (301.0)FG
(300.0)FG
(E) R/W
(E) PL
(E) PL
(E) R/W 303.43FS 303.43FS 303.43FS 303.45FS 303.45FS 303.43FS (300.40)BW

0.10% 2.00% 303.43FS 303.43FS 303.43FS303.43FS 304.50TC 304.00FS 1.54% 304.95TC 304.45FS 303.01FS 3.00% 303.45FS 303.45FS 3.00% 303.20FS 0"CF (300.34)BW 303.00TC 302.50FS 6.04% 0.56% 1.10% 303.30TC 302.80FS 303.20FS (E) SD INLET (298.36)TG (288.51)INV 303.30TC 302.80FS0.50% 303.20FS 0"CF 303.30TC 302.80FS 303.43FS 1.03% 302.86TC 302.36FL 301.50TC 301.00FL 303.35TC 302.85FS 303.65TC 303.15FS 1.20% 1.00% 2.00% (TYP)

1.20%
(TYP)

1.20%
(TYP)

2.00% 302.58TC 303.17TS 302.08FS 301.09BS 1.72%

1.41%
(E) SD INLET
(298.44)TG(288.54)INV 304.15TW 301.05FS 305.15TW 303.29FS 302.29FS 302.05FS 302.19FS 3.13% 3.13% 1.65% 1.72% 1.41% 302.07FS 301.93FS 5 STEPS @ 5" 307.95TW 307.95TW 308.95TW 308.95TW 309.45TW 309.45TW 309.45TW 309.45TW 309.45TW 311.45TW 303.15TW 303.15 TW 303.95TW 304.15TW (302.35)BW (300.93)BW (300.55)BW (300.31)BW 305.15TW 305.15TW 304.15TW 304.15TW 311.00TW 305.0FG W. LUCHESSA AVENUE MILLER AVENUE302.95TC FIRE STATION 302.45FS 303.45FF 305.15 TW 4"FW
4"SS 4"SS 4"SS
4"SS
3"DW
4"FW
4"FW
3"DW co co co 3/4"DW co co co 3"DW NO PARKING EV CHARGING ONLY EV CHARGING ONLY NO PARKING 8"SD 4"SD 4"SD 4"SD 8"SD 4"SD 8"SD8"SD 12"SD12"SD
12"SD
4"SD
4"SD
4"SD
8"SD
Revision Date
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION ARCHITECTURE ENGINEERING INTERIORS LANDSCAPE ARCHITECTURE PLANNING 408-780-7200 Office LPADesignStudios.com 60 South Market Street, Suite 1250 San Jose, California 95113 Developed for
Checked By Scale Job Number
Submittal Date
70% SCHEMATIC DESIGN 03/10/2026
This document and all other project documents, ideas
aesthetics and designs incorporated therein are instrumentsof service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of propertyrights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary lossesand damages including attorney fees and costs for which the unauthorized user will be held liable. Project documents describe the design intent of the workand are not a representation of as-built or existing conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
100% SD/BRIDGING DOCS 03/26/2026

SANTA TERESA FIRE STATION
GILROY, CA 95020
GRIFFIN STRUCTURES, INC. 33236.10 KS
1330 WEST LUCHESSA AVENUE CONCEPTUAL GRADING PLAN 1"=20' 0 10 20 40 1"=20' CONCEPTUAL GRADING PLAN C2.01 05

Page 225 of 256 ends

NO PARKING EV CHARGING ONLY EV CHARGING ONLY NO PARKING 4"FW
4"SS 4"SS 4"SS
4"SS
3"DW
4"FW
4"FW
3"DW
3/4"DW
3"DW
(E) PL
(E) PL
(E) R/W
(E) R/W
8"SD
(E) SD INLET
(298.36)TG(288.51)INV
(E) SD INLET(298.44)TG
(288.54)INV co W. LUCHESSA AVENUE
MILLER AVENUE 4" SD POC 300.95INV 4" SD POC 300.95INV 4" SD POC 300.95INV 4" SD POC 300.95INV 4" SD POC 300.95INV 4" SD POC 301.03INV 4" SD POC 300.95INV 4" SD POC 303.00INV 4" SD POC 303.70INV 4" SD POC 303.70INV 4" SD POC 303.70INV 4" SD POC 300.95INV 4" SD POC 300.95INV FIRE STATION 303.45FF 4"SD 4"SD 298.00INV 302.88INV298.00INV 299.30INV 299.30INV co 299.50INV co co 299.30INV co 299.20INV 4"SD 8"SD 4"SD 8"SD8"SD 12"SD12"SD 12"SD
4"SD
4"SD
4"SD
8"SD

CONNECT (E) SD PIPE TO NEW DRAIN INLET FIELD VERIFY LOCATION OF (E) PIPE, SIZE AND MATERIAL Revision Date
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION ARCHITECTURE ENGINEERING INTERIORS LANDSCAPE ARCHITECTURE PLANNING 408-780-7200 Office LPADesignStudios.com 60 South Market Street, Suite 1250 San Jose, California 95113 Developed for
Checked By Scale Job Number
Submittal Date
70% SCHEMATIC DESIGN 03/10/2026
This document and all other project documents, ideas
aesthetics and designs incorporated therein are instrumentsof service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of propertyrights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary lossesand damages including attorney fees and costs for which the unauthorized user will be held liable. Project documents describe the design intent of the workand are not a representation of as-built or existing conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
100% SD/BRIDGING DOCS 03/26/2026

SANTA TERESA FIRE STATION
GILROY, CA 95020
GRIFFIN STRUCTURES, INC. 33236.10 KS
1330 WEST LUCHESSA AVENUE CONCEPTUAL STORM DRAIN PLAN 1"=20' 0 10 20 40 1"=20' CONCEPTUAL STORM DRAIN PLAN C3.01 05

Page 226 of 256 ends

NO PARKING EV CHARGING ONLY EV CHARGING ONLY NO PARKING JOIN (E) 4" SS (290.50)INV JOIN (E) 2" IRR W JOIN (E) 2" DW
JOIN (E) 4" FW (E) FH
(E) PL
(E) PL
(E) R/W
(E) R/W
(E) FH
(E) FH
4"FW 4" DCDA WITH 2-WAY FDC 2" WATER METER 4"SS 4"SS 4"SS 4"SS 4" SS POC 299.95INV 3"DW 2" RPBP 4"FW 4"FW SAND/OIL INTERCEPTER AND SAMPLING BOX PER PLUMBING PLAN 2" DW POC 3" FW POC 3"DW co co co 3/4"DW (E) SD INLET(298.36)TG
(288.51)INV
(E) SD INLET(298.44)TG
(288.54)INV 4" SS POC 299.95INV 4" SS POC 299.95INV co co W. LUCHESSA AVENUE MILLER AVENUEFOX DRAIN AT VEHICLE WASHDOWN AREA FIRE STATION 303.45FF co ALTERNATE 2: EXTENSION OF DOMESTIC WATER AND SANITARY SEWER INFRASTRUCTURE 3"DW 3/4" DW POC 4" SS POC 299.95INV 8"SD 4"SD 4"SD 4"SD 8"SD 4"SD 8"SD8"SD 12"SD12"SD
12"SD
4"SD
4"SD
4"SD
8"SD
Revision Date
NOT FOR REGULATORY APPROVAL, PERMITTING OR CONSTRUCTION ARCHITECTURE ENGINEERING INTERIORS LANDSCAPE ARCHITECTURE PLANNING 408-780-7200 Office LPADesignStudios.com 60 South Market Street, Suite 1250 San Jose, California 95113 Developed for
Checked By Scale Job Number
Submittal Date
70% SCHEMATIC DESIGN 03/10/2026
This document and all other project documents, ideas
aesthetics and designs incorporated therein are instrumentsof service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of propertyrights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary lossesand damages including attorney fees and costs for which the unauthorized user will be held liable. Project documents describe the design intent of the workand are not a representation of as-built or existing conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
100% SD/BRIDGING DOCS 03/26/2026

SANTA TERESA FIRE STATION
GILROY, CA 95020
GRIFFIN STRUCTURES, INC. 33236.10 KS
1330 WEST LUCHESSA AVENUE CONCEPTUAL UTILITY PLAN 1"=20' 0 10 20 40 1"=20' CONCEPTUAL UTILITY PLAN C4.01 05

Page 227 of 256 ends

0 LC
I
L0.01 LANDSCAPE NOTES AND LEGENDS
L1.01 MATERIALS PLAN
L7.01 PLANTING PLAN

1. REFER TO CIVIL ENGINEER'S DRAWINGS FOR UTILITY LOCATIONS, TREE SUBDRAINAGE STUBOUTS, (IF REQUIRED), AND FINAL GRADING. IF ACTUAL

SITE CONDITIONS VARY FROM WHAT IS SHOWN ON THE LANDSCAPE

ARCHITECT'S DRAWINGS, THE DESIGN-BUILD ENTITY (DBE) SHALL CONTACT

THE OWNER'S AUTHORIZED REPRESENTATIVE AND LANDSCAPE ARCHITECT FOR DIRECTION AS TO HOW TO PROCEED.

2. VERIFY LOCATIONS OF ALL PERTINENT EXISTING AND PROPOSED SITE IMPROVEMENTS. IF ANY PART OF THIS PLAN CANNOT BE FOLLOWED DUE TO

SITE CONDITIONS, CONTACT THE LANDSCAPE ARCHITECT FOR INSTRUCTION PRIOR TO COMMENCING WORK.

3. EXACT LOCATIONS OF PLANT MATERIALS SHALL BE REVIEWED BY THE LANDSCAPE ARCHITECT IN THE FIELD PRIOR TO INSTALLATION. LANDSCAPE

ARCHITECT RESERVES THE RIGHT TO ADJUST PLANTS TO EXACT LOCATION IN FIELD.

4. DBE SHALL BE RESPONSIBLE FOR VERIFYING ALL PLANT COUNTS AND SQUARE FOOTAGES. QUANTITIES SHOWN ON PLANS TAKE PRECEDENCE OVER WRITTEN QUANTITIES IN "PLANTING LEGEND."

5. PROVIDE MATCHING FORMS AND SIZES FOR ALL PLANT MATERIALS WITHIN EACH SPECIES AND SIZE DESIGNATED ON THE DRAWINGS.

6. PRUNE NEWLY PLANTED TREES ONLY AS DIRECTED BY LANDSCAPE ARCHITECT.

7. ALIGNED AND EQUALLY SPACED, IN ALL DIRECTIONS, ALL SHRUBS TO BE AS DESIGNATED PER THESE NOTES AND DRAWINGS.

8. ALL TREES IN ROWS TO BE ALIGNED. (UNLESS NOTED OTHERWISE ON PLANS)

9. TREES SHALL BEAR SAME RELATION TO FINISH GRADE AS AT PLACE OF GROWTH.

10. FINISH GRADES OF ALL TURF AREAS SHALL BE (1") BELOW ADJACENT CURB OR PAVEMENT. FINISH GRADES OF ALL SHRUB AREAS SHALL BE (2-1/2") BELOW ADJACENT CURB, PAVEMENT OR HEADER.

11. DBE SHALL SUBMIT FOR APPROVAL COLOR PHOTOS OF ALL TREES, SHRUBS, AND GROUNDCOVER. PHOTOS SHOULD INCLUDE A PERSON FOR SCALE

PURPOSES, PHOTOS SHALL BE OF THE ACTUAL PLANT MATERIAL TO BE USED ON THE PROJECT. ALL PLANT MATERIAL SHALL BE OF A QUALITY AS DETERMINED BY THE LANDSCAPE ARCHITECT. MATERIAL FOUND UNSUITABLE FOR THE DESIGN OR SPECIFICATION INTENT WILL BE REJECTED.

12. PROVIDE A (3") LAYER OF MULCH AT PROPOSED TREE, SHRUB, AND GROUNDCOVER PLANTING AREAS, EXCEPT AREAS WITH JUTE MESHING.

13. DBE SHALL CONDUCT AGRICULTURAL SUITABILITY AND FERTILITY SOILS TESTING PER SOIL PREPARATION SPECIFICATION. ANALYSIS SHALL INCLUDE

RECOMMENDATIONS FOR SOIL PREPARATION AND BACKFILL MIX AS WELL AS RECOMMENDATIONS FOR POST MAINTENANCE FERTILIZATION. SUBMIT SOILS

ANALYSES AND SAMPLES OF AMENDMENTS TO LANDSCAPE ARCHITECT FOR REVIEW PRIOR TO SOIL PREPARATION.

14. QUANTITIES LISTED ON PLANT LEGEND ARE PER SHEET. DBE MUST VERIFY QUANTITIES GIVEN ON THE PLANS WITH ACTUAL QUANTITIES SHOWN.

15. PROVIDE ROOT BARRIERS IN ADDITION TO THOSE INDICATED ON THE PLANS FOR ALL TREES WITHIN 5' OF ANY HARDSCAPE.

16. NOT INSTALL WATERING BASINS AROUND TREES WHEN PLANTED IN TURF.

PROVIDE A CIRCULAR TURF-FREE ZONE TO OUTSIDE EDGE OF ROOTBALL.

PLACE ONLY 2-INCHES OF WOOD MULCH IN THIS AREA AND NO CLOSER THAN 4-INCHES FROM TRUNK.

17. PLANT ALL TREES A MIN. OF 5' FROM ANY UTILITIES. THE LANDSCAPE DBE

SHALL VERIFY THE LOCATION OF ALL UTILITIES PRIOR TO COMMENCING WORK.

18. TREES ARE TO BE A MINIMUM OF 5' AWAY FROM ANY HARDSCAPE SUCH AS CURBS, WALKS, ETC.

19. LANDSCAPE MAINTENANCE PERIOD IS 90 DAYS.

20. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

1. THE DESIGN-BUILD ENTITY (DBE) SHALL LAYOUT AND FIELD VERIFY ALL

DIMENSIONS OF DRIVEWAY, PLANTERS, WALKS, SLOPES AND RELATED WORK PRIOR TO CONSTRUCTION. ANY DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER'S AUTHORIZED REPRESENTATIVE.

2. VERIFY LOCATIONS OF ALL PERTINENT EXISTING AND PROPOSED SITE IMPROVEMENTS. IF ANY PART OF THIS PLAN CANNOT BE FOLLOWED DUE TO

SITE CONDITIONS, CONTACT THE LANDSCAPE ARCHITECT FOR INSTRUCTION PRIOR TO COMMENCING WORK.

3. WRITTEN DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALE.

4. THIS DRAWING INCLUDES THE LOCATION OF AREA DRAINS FOR REFERENCE.

REFER TO RELATED CIVIL ENGINEER'S DRAWINGS FOR CONSTRUCTION DETAILS AND UTILITY CONNECTIONS.

5. REFER TO ELECTRICAL ENGINEER'S DRAWINGS FOR LIGHT FIXTURE SCHEDULE AND CIRCUITRY AS NECESSARY.

6. REFER TO SOIL ENGINEER'S GEOTECHNICAL REPORT FOR SUB-BASE MATERIALS AND COMPACTION.

7. WHERE DIMENSIONS ARE CALLED AS "EQUAL", ALL REFERENCED ITEMS SHALL BE SPACED EQUALLY, MEASURED TO THEIR CENTERLINES.

8. ALL MEASUREMENTS ARE TO FACE OF WALL, CURB OR OTHER FIXED SITE IMPROVEMENT, UNLESS OTHERWISE NOTED. DIMENSIONS TO CENTERLINES AS INDICATED.

9. INSTALL ALL INTERSECTING ELEMENTS AT 90 DEGREES TO EACH OTHER UNLESS OTHERWISE NOTED.

10. ALL DRAINS/ BASINS SHOULD HAVE BLACK ATRIUM TYPE GRATES WITHIN

SHRUBS/GROUNDCOVER AREAS AND BLACK FLAT TYPE GRATES IN TURF AREAS.

1. BASE INFORMATION INCLUDING THE LOCATION OF PROPERTY LINES,

EASEMENTS, BUILDINGS, ROADS AND CURBS HAVE BEEN TAKEN FROM THE CIVIL ENGINEER'S DRAWINGS. REFER TO CIVIL ENGINEER'S DRAWINGS FOR ADDITIONAL INFORMATION.

2. REFER TO THE CIVIL ENGINEER'S DRAWINGS FOR PROPOSED UTILITY

INFORMATION INCLUDING STORM DRAIN, SEWER, WATER, ELECTRICAL, GAS, TELEPHONE AND CABLE TV.

3. REFER TO CITY AND/OR COUNTY STANDARD PLANS AND SPECIFICATIONS WHERE APPLICABLE.

4. VERIFY SITE INFORMATION, INCLUDING PROPERTY LINES, EXISTING ABOVE

GROUND AND BELOW GROUND UTILITIES AND STRUCTURES, AND OTHER

INFORMATION AFFECTING THE SCOPE OF WORK INCLUDED ON THESE DRAWINGS. IF ACTUAL SITE CONDITIONS VARY FROM WHAT IS SHOWN ON

THE LANDSCAPE ARCHITECT'S DRAWINGS, THE DESIGN-BUILD ENTITY (DBE)

SHALL CONTACT THE OWNER'S AUTHORIZED REPRESENTATIVE AND THE LANDSCAPE ARCHITECT FOR DIRECTION ON HOW TO PROCEED.

5. EXCAVATION IN THE VICINITY OF UTILITIES AND EXISTING MATERIALS SHALL BE UNDERTAKEN WITH CARE. THE DBE BEARS FULL RESPONSIBILITY FOR THIS WORK. ANY DAMAGE CAUSED BY ANY PERSON, VEHICLE, EQUIPMENT,

OR TOOL RELATED TO THE EXECUTION OF THE CONTRACT SHALL BE REPAIRED IMMEDIATELY AT NO EXPENSE TO THE OWNER.

6. DBE SHALL BE RESPONSIBLE FOR ANY COORDINATION REQUIRED TO ACCOMPLISH ALL CONSTRUCTION OPERATIONS. ALL PIPING, CONDUIT, SLEEVES, ETC., SHALL BE SET IN PLACE PRIOR TO INSTALLATION OF CONSTRUCTION ITEMS.

7. DBE SHALL BE RESPONSIBLE TO CONSULT WITH SITE SUPERINTENDENT,

APPROPRIATE AGENCIES AND PLANS, FOR THE LOCATIONS OF ALL UNDER-GROUND UTILITIES, PIPES AND STRUCTURES. CONTRACTOR SHALL

TAKE SOLE RESPONSIBILITY FOR ANY COST INCURRED DUE TO DAMAGE OF SAID UTILITIES.

8. DBE SHALL NOT WILLFULLY PROCEED WITH CONSTRUCTION AS DESIGNED

WHEN IT IS OBVIOUS THAT UNKNOWN OBSTRUCTIONS, AREA DISCREPANCIES

AND/OR GRADE DIFFERENCES EXIST THAT MAY NOT HAVE BEEN KNOWN DURING DESIGN. SUCH CONDITIONS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE OWNER'S AUTHORIZED REPRESENTATIVE. THE DBE

SHALL ASSUME FULL RESPONSIBILITY FOR ALL NECESSARY REVISIONS DUE TO FAILURE TO GIVE SUCH NOTIFICATIONS.

9. DBE IS RESPONSIBLE FOR REPLACEMENT OF ANY EXISTING MATERIALS THAT ARE DAMAGED DURING CONSTRUCTION.

10. PRIOR TO INSTALLATION OF ANY CONSTRUCTION ITEM, FORMS WITH STEEL IN

PLACE AND COMPACTED SUBGRADE COMPLETE, SHALL BE OBSERVED AND REVIEWED BY THE LANDSCAPE ARCHITECT.

11. ALL WALLS AND WALKS SHOULD HAVE SMOOTH, CONTINUOUS CURVES AS INDICATED ON PLANS.

12. ALL PROPERTY LINES, LOT LINES, AND TOP OF SLOPE LINES SHALL BE VERIFIED PRIOR TO COMMENCING WORK.

13. ALL ELECTRICAL JUNCTION BOXES FOR LIGHTS SHALL BE IN PLANTING AREAS AND LOCATION REVIEWED BY THE LANDSCAPE ARCHITECT. STAKE LOCATION PRIOR TO INSTALLATION.

14. SEE CIVIL ENGINEER'S DRAWINGS FOR CURBS AND A/C PAVING.

15. REFER TO CIVIL ENGINEER'S DRAWINGS FOR ELEVATIONS AND LOCATION OF

DRAINAGE STRUCTURES PRIOR TO INSTALLATION OF WALKS, FOOTINGS AND OTHER STRUCTURES.

16. REFER TO GEOTECHNICAL REPORT FOR ADDITIONAL INFORMATION. IF NOTES

ON THE PLANS DIFFER FROM THE GEOTECHNICAL REPORT, PROVIDE THE MOST STRINGENT REQUIREMENT.

17. RAISE ALL VAULTS/UTILITIES BOXES TO GRADE WITHIN LIMITS OF WORK.

FIELD VERIFY PRIOR TO BID.

1. REFER TO CIVIL ENGINEER'S GRADING PLANS FOR SITE GRADING, DRAINAGE, AND UTILITY LOCATIONS. IF ACTUAL SITE CONDITIONS VARY FROM WHAT IS

SHOWN ON THE LANDSCAPE ARCHITECT'S DRAWINGS, THE DESIGN-BUILD

ENTITY (DBE) SHALL CONTACT THE OWNER'S AUTHORIZED REPRESENTATIVE AND LANDSCAPE ARCHITECT FOR DIRECTION AS TO HOW TO PROCEED.

2. REFER TO CIVIL ENGINEER'S DRAWINGS FOR SUBDRAINAGE POINT OF IN CONNECTION TO STORM DRAIN.

3. THE DBE SHALL REQUEST OBSERVATION AS REQUIRED 48 HOURS ADVANCE OF PERFORMING WORK.

4. THE DBE SHALL NOTIFY UNDERGROUND SERVICE ALERT (USA 800/227-2600) OR DIG ALERT (800-422-4133) 48 HOURS PRIOR TO ANY EXCAVATION.

5. ALL GRADING OPERATIONS SHALL CONFORM TO LOCAL GUIDELINES.

6. FIELD VERIFY EXISTING UNDERGROUND UTILITIES. THE DBE SHALL BE

RESPONSIBLE FOR VERIFYING THE ACTUAL LOCATION AND ELEVATION IN THE FIELD PRIOR TO BEGINNING CONSTRUCTION. THE DBE SHALL PROTECT ALL

EXISTING UTILITIES AND SHALL BE RESPONSIBLE FOR ANY DAMAGE TO EXISTING UTILITIES ENCOUNTERED DURING CONSTRUCTION.

7. NO CHANGE IN CONTRACT PRICE WILL BE ALLOWED FOR ACTUAL OR CLAIMED

DISCREPANCY BETWEEN EXISTING GRADE AND THOSE SHOWN ON PLANS AFTER DBE HAS ACCEPTED EXISTING GRADES AND MOVED ONTO THE SITE.

8. ALL PROPOSED GRADES ARE TO MEET AND BLEND IN WITH EXISTING GRADING AT PROJECT LIMIT AND EXISTING SIDEWALK. PRECISE ELEVATIONS INDICATED ON PLANS TO BE VERIFIED IN FIELD TO AS-BUILT CONDITION.

9. THE DEBRIS CREATED BY LANDSCAPE GRADING OPERATIONS SHALL BECOME THE PROPERTY OF THE DBE AND SHALL BE LEGALLY DISPOSED OF OFF-SITE.

10. FINAL LANDSCAPE GRADING SHALL BE REVIEWED BY THE LANDSCAPE ARCHITECT IN THE FIELD PRIOR TO INSTALLATION OF PLANTING.

GA. GAUGE
GALV. GALVANIZED
GND. GROUND
GR. GRADE

HDR HEADER
HT. HEIGHT
LT. LIGHT
MAX. MAXIMUM
MET. METAL
MFR. MANUFACTURER
MIN. MINIMUM
MTD. MOUNTED
MTL. MATERIAL
N.I.C. NOT IN CONTRACT
N.T.S. NOT TO SCALE
O.C. ON CENTER
O.D. OUTSIDE DIAMETER (DIM.)

PA PLANTING AREA
PED. PEDESTRIAN
PRCST. PRECAST
P.I.P. POURED IN PLACE
P.O.T. POINT OF TANGENCY
P.T.S. POST TENSION SLAB

QTY QUANTITY
R. RISER
RAD. RADIUS
REINF. REINFORCED
REQ. REQUIRED
SCHED. SCHEDULE
SHT. SHEET
SPEC. SPECIFICATION
S.S. STAINLESS STEEL
STD. STANDARD
STRL. STRUCTURAL
T. TREAD
T.C. TOP OF CURB
T.O.S. TOP OF SLOPE
T.O.W. TOP OF WALL
TYP. TYPICAL
TBD. TO BE DETERMINED
VEH. VEHICULAR
VERT. VERTICAL

W/ WITH

W/O WITHOUT
& AND
ANGLE
@ AT

CENTERLINE

DIAMETER OR ROUND
# POUND OR NUMBER
ADJ. ADJACENT
AGGR. AGGREGATE
AL. ALUMINUM
APPROX. APPROXIMATE
ARCH. ARCHITECTURAL
AC. ASPHALT
ACC. ACCESSIBLE
B.C.R. BEGINNING OF CURVE RADIUS
B.O.C. BACK OF CURB
B.O.W. BOTTOM OF WALL
B.O.S. BOTTOM OF SLOPE
BLDG. BUILDING
BLK. BLOCK
C.E. CIVIL ENGINEER
C.I.P. CAST IN PLACE
CLKG. CAULKING
CMU. CONCRETE MASONRY UNIT
CONC. CONCRETE
CONSTR. CONSTRUCTION
CONT. CONTINUOUS
CTR. CENTER
D.A. DISABLED ACCESS
DET. DETAIL
DIA. DIAMETER
DIM. DIMENSION
DN. DOWN
DWGS. DRAWINGS
E.J. EXPANSION JOINT
EL. ELEVATION
ELEC. ELECTRICAL
EQ. EQUAL
EXP. EXPANSION
EXT. EXTERIOR
F.G. FINISH GRADE
F.S. FINISH SURFACE
F.O.B. FACE OF BUILDING
F.O.C. FACE OF CURB
F.O.W. FACE OF WALL

1. SUBMIT SHOP DRAWINGS TO LANDSCAPE ARCHITECT OF ALL FENCE AND

GATE COMPONENTS INCLUDING PLANS, ELEVATIONS AND DETAILS AS NECESSARY FOR COMPLETE INSTALLATION.

2. ALL WELDS PER DETAILS. COLD GALVANIZE ALL FIELD WELDS.

3. ALL POSTS SHALL HAVE WELDED METAL CAPS.

4. ALL MEMBERS TO BE 12 GA. WALL THICKNESS MINIMUM, UNLESS NOTED

OTHERWISE

5. ALL GATES AND FENCES, INCLUDING CORRUGATED METAL PANEL TO BE PAINTED, SEE MATERIALS PLAN FOR COLOR.

6. SUBMIT SAMPLES OF ALL COMPONENTS AND MATERIALS TO LANDSCAPE ARCHITECT FOR REVIEW PRIOR TO FABRICATION.

7. GATE HARDWARE FINISH AND COLOR TO MATCH GATE/FENCE.

8. ANY COMPONENTS REQUIRED FOR A COMPLETE FENCE/GATE SYSTEM, BUT

NOT SHOWN, SHOULD BE CONSIDERED A PART OF THESE DRAWINGS AND INCLUDED IN THE FINAL INSTALLED SYSTEM.

9. DESIGN-BUILD ENTIRY (DBE) TO VERIFY ALL ATTACHMENTS AND DIMENSIONS, INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

10. ALL JOINTS TO BE WELDED TO MAKE A SOLID GATE FRAME.

1. CONCRETE HARDSCAPE

2. CMU RETAINING AND SITE WALLS

3. MOTORIZED SLIDING GATES

4. STEEL PEDESTRIAN GATE

5. FLAGPOLE WITH UPLIGHTS

6. LIGHT POLES

7. PLANTING AND IRRIGATION

AS NOTED

GENERAL NOTES SHEET INDEX

LAYOUT AND MATERIALS NOTES

ABBREVIATIONS PLANTING NOTES

GENERAL SCOPE OF WORK

LANDSCAPE GRADING AND DRAINAGE NOTES

FENCE AND GATE NOTES
© LPA, Inc. Developed for
Job Number
Checked By
ScaleRevision Date

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com Submittal Date
5301 California Avenue, Suite 100
Irvine, California 92617
This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. SANTA TERESA FIRE STATION 1330 WEST LUCHESSA AVENUE GILROY, CA 95020 GRIFFIN STRUCTURES, INC. 33236
RF 70% SCHEMATIC DESIGN 03/10/2026 100% SD / BRIDGING DOCS 03/26/2026 L0.01

LANDSCAPE NOTES

AND LEGENDS

NOTE DESCRIPTION COLOR / FINISH
01 DET/
SHT
02 03
04 05
06 07
08 09
10 11
12 13
14 15
16 17
18 19
20 21
DET/

NOTE DESCRIPTION SHT
A
B
C
D
E
F
G
H
J
K
L
M
N
O
P
Q
R
S
T

COMMENTS

EXISTING AC PAVING

PROTECT IN PLACE

EXISTING CONCRETE CURB

PROTECT IN PLACE

EXISTING CONCRETE GUTTER

PROTECT IN PLACE

EXISTING UTILITY

PROTECT IN PLACE

AC PAVING
PER
CIVIL

CONCRETE CURB AND GUTTER
PER
CIVIL

CONCRETE CURB RAMP
PER
CIVIL

PAVEMENT STRIPING
PER
CIVIL

WHEEL STOP
PER
CIVIL

ACCESSIBLE PARKING SIGNAGE
PER
CIVIL

EV CHARGER
PER
ELEC

BIORETENTION BASIN
PER
CIVIL

ELECTRICAL VAULT PER
ELEC

NATURAL GRAY/

MEDIUM BROOM

DAVIS COLORS TBD/
TOPCAST O5

FEDERAL YELLOW/
WAUSAU TILE ADA-2 PAVERS
COLOR/
FINISH
COLOR/
FINISH

REFER TO SITE FURNISHINGS
LEGEND IN L0.01

CONCRETE PAVING

CONCRETE ACCENT PAVING

PRECAST TRUNCATED DOME PAVERS
COBBLE

CONCRETE STAIR

CMU RETAINING WALL

ALUMINUM EDGING

HANDRAIL AT STAIR

MOTORIZED SLIDING STEEL GATE

BIKE RACK

BIKE LOCKER

FLAGPOLE WITH UPLIGHTS

SITE LIGHTING

REFER TO SITE FURNISHINGS
LEGEND IN L0.01

REFER TO SITE FURNISHINGS
LEGEND IN L0.01

REFER TO SITE FURNISHINGS
LEGEND IN L0.01

REFERENCE KEYNOTE LEGEND

MATERIALS KEYNOTE LEGEND

EXISTING CONCRETE PAVING

PROTECT IN PLACE

CONCRETE CURB
PER
CIVIL

SINGLE PEDESTRIAN GATE

DOUBLE GATES AT EMERGENCY GENERATOR

TOURNESOL KITSAP - ALUM

FROM STANDARD COLORS METAL MODULAR RAISED PLANTERS

EXISTING STREET LIGHT PROTECT IN PLACE

SLIDING GATE OPERATOR
SLIDEDRIVER II SD50

HYSECURITY

GATE OPERATOR UPS BATTERY BACKUP

DAVIS COLORS TBD
TOPCAST 05
COLOR/
FINISH

CMU FREESTANDING WALL

CONCRETE PAVING AT RAMP

COLOR TBD/

HIGH PERF COATING

HANDRAIL AT RAMP

NATURAL GRAY/

MEDIUM BROOM

COLOR TBD/

HIGH PERF COATING

EXPANDED METAL, COLOR

TBD / HIGH PERF COATING
-
-

EMERGENCY GENERATOR
PER
ELEC

EXPANDED METAL, COLOR

TBD / HIGH PERF COATING

EXPANDED METAL, COLOR

TBD / HIGH PERF COATING

ANODIZED
8" THICK

CARPORT STRUCTURE
PER
ARCH

MECHANICAL UNIT PER

MECHANICAL

SITE FURNISHINGS LEGEND
SYM. DESCRIPTION MFR. MODEL # COLOR
FIN/
PTRN QTY.

BIKE RACK

BIKE LOCKER

FLAG POLE
3 2
3 SATIN
MANU.

PWDRCOAT
CLEAR

ANODIZED

STAINLESS
STEEL

ALUMINUM
RING
DL2
ICC30D61-AA

LANDSCAPE
FORMS
DURA
BIKE
LOCKER

CONCORD

AMERICAN

FLAGPOLE
FROM
MANU.

STANDARD
COLORS

SITE LIGHTING LEGEND
SYM.

BOLLARD LIGHT PER ELEC. PLANS

DESCRIPTION
DET/

SHT COMMENTS

PARKING LOT LIGHT POLE
PER ELEC. PLANS
NOTE: SEE ELECTRICAL PLANS FOR FIXTURES, LAMPS, AND SPECS.

FLAGPOLE UPLIGHTS
PER ELEC. PLANS

TREE UPLIGHTS
PER ELEC. PLANS
WALL RECESSED STEP LIGHT PER ELEC. PLANS

SITE SYMBOLS LEGEND
SYM. DESCRIPTION SYM. DESCRIPTION DET.

EXISTING FIRE HYDRANT
NOTE: UTILITIES SHOWN ARE FOR REFERENCE ONLY. SEE CIVIL AND ELEC DWGS FOR DETAILS AND EXACT LOCATIONS. FINAL LOCATIONS TO BE REVIEWED BY LANDSCAPE ARCHITECT.

CATCH BASIN - PER CIVIL

CLEAN OUT - PER CIVIL
DIRECTION OF RAMP;

DOWN SLOPE

PLANTING AREA

SAWCUT JOINT

EXPANSION JOINT

PROPERTY LINE/
RIGHT OF WAY co
PA
REDUCED PRESSURE BACKFLOW PREV.

DOUBLE CHECK DETECTOR ASSEMBLY

FIRE DEPARTMENT CONNECTION

Page 228 of 256 ends

co co co co co co co co co co co co NO PARKING EV CHARGING ONLY EV CHARGING ONLY NO PARKING L1.01 MATERIALS PLAN AS NOTED © LPA, Inc.

Developed for Job Number Checked By Scale
Revision Date ARCHITECTURE ENGINEERING INTERIOR DESIGN LANDSCAPE ARCHITECTURE PLANNING 949-261-1001 Office LPADesignStudios.comSubmittal Date 5301 California Avenue, Suite 100 Irvine, California 92617 This document and all other project documents, ideas, aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable. Project documents describe the design intent of the work and are not a representation of as-built or existing conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions.

SANTA TERESA FIRE STATION
1330 WEST LUCHESSA AVENUE
GILROY, CA 95020
GRIFFIN STRUCTURES, INC. 33236 RF
70% SCHEMATIC DESIGN 03/10/2026
100% SD / BRIDGING DOCS 03/26/2026 NOTE DESCRIPTION COLOR / FINISH 01 DET/ SHT 0203040506070809101112131415161718192021 DET/ NOTE DESCRIPTION SHT ABCDEFGHJKLMNOPQRST COMMENTS EXISTING AC PAVING PROTECT IN PLACE EXISTING CONCRETE CURB PROTECT IN PLACE EXISTING CONCRETE GUTTER PROTECT IN PLACE EXISTING UTILITY PROTECT IN PLACE AC PAVING PER CIVIL CONCRETE CURB AND GUTTER PER CIVIL CONCRETE CURB RAMP PER CIVIL PAVEMENT STRIPING PER CIVIL WHEEL STOP PER CIVIL ACCESSIBLE PARKING SIGNAGE PER CIVIL EV CHARGER PER ELEC BIORETENTION BASIN PER CIVIL ELECTRICAL VAULT PER ELEC NATURAL GRAY/ MEDIUM BROOM DAVIS COLORS TBD/ TOPCAST O5 FEDERAL YELLOW/ WAUSAU TILE ADA-2 PAVERS COLOR/ FINISH COLOR/ FINISH REFER TO SITE FURNISHINGS LEGEND IN L0.01 CONCRETE PAVING CONCRETE ACCENT PAVING PRECAST TRUNCATED DOME PAVERS COBBLE CONCRETE STAIR CMU RETAINING WALL ALUMINUM EDGING HANDRAIL AT STAIR MOTORIZED SLIDING STEEL GATE BIKE RACK BIKE LOCKER FLAGPOLE WITH UPLIGHTS SITE LIGHTING REFER TO SITE FURNISHINGS LEGEND IN L0.01 REFER TO SITE FURNISHINGS LEGEND IN L0.01 REFER TO SITE FURNISHINGS LEGEND IN L0.01 REFERENCE KEYNOTE LEGEND MATERIALS KEYNOTE LEGEND EXISTING CONCRETE PAVING PROTECT IN PLACE CONCRETE CURB PER CIVIL SINGLE PEDESTRIAN GATE DOUBLE GATES AT EMERGENCY GENERATOR TOURNESOL KITSAP - ALUM FROM STANDARD COLORS METAL MODULAR RAISED PLANTERS EXISTING STREET LIGHT PROTECT IN PLACE SLIDING GATE OPERATOR SLIDEDRIVER II SD50 HYSECURITY GATE OPERATOR UPS BATTERY BACKUP DAVIS COLORS TBD TOPCAST 05 COLOR/ FINISH CMU FREESTANDING WALL CONCRETE PAVING AT RAMP COLOR TBD/ HIGH PERF COATING HANDRAIL AT RAMP NATURAL GRAY/ MEDIUM BROOM COLOR TBD/ HIGH PERF COATING EXPANDED METAL, COLOR TBD / HIGH PERF COATING -- EMERGENCY GENERATOR PER ELEC EXPANDED METAL, COLOR TBD / HIGH PERF COATING EXPANDED METAL, COLOR TBD / HIGH PERF COATING ANODIZED 8" THICK CARPORT STRUCTURE PER ARCH MECHANICAL UNIT PER MECHANICAL MATERIALS PLAN 1" = 20'-0" 05 SITE SYMBOLS LEGEND SYM. DESCRIPTION SYM. DESCRIPTION DET. EXISTING FIRE HYDRANT NOTE: UTILITIES SHOWN ARE FOR REFERENCE ONLY. SEE CIVIL AND ELEC DWGS FOR DETAILS AND EXACT LOCATIONS. FINAL LOCATIONS TO BE REVIEWED BY LANDSCAPE ARCHITECT. CATCH BASIN - PER CIVIL CLEAN OUT - PER CIVIL DIRECTION OF RAMP; DOWN SLOPE PLANTING AREA SAWCUT JOINT EXPANSION JOINT PROPERTY LINE/ RIGHT OF WAY co PA REDUCED PRESSURE BACKFLOW PREV. DOUBLE CHECK DETECTOR ASSEMBLY FIRE DEPARTMENT CONNECTION PA NEW FIRE STATION WEST LUCHESSA AVENUE LIMIT OF WORK

MILLER AVENUE N

LIMIT OF WORK LIMIT OF WORK
LIMIT OF WORK PA PA PA PA PA PA PA PA PA PA PA PA PA PA PA PA PA PA PA PA PA PA PA PA 11 06 TYPM N 01 T 01 S L 13 08 L 01 08 16 15 01 H 01 01 1516 10 17 TYPK 09 08 HTYPL VEH H VEH 01 01 TYP 03 G G G N S 08 TYP 21 14 TYP 21 05 W/ INTEG. LIGHT 10 S (FUTURE) PL O 07 07 TYP 19 21 VEH 13 01 PA PA PA PA 12 12 02 18 20 17 08 TYP21 17 17 TYP03 TYPK K Q OF 7 PA A A F D C B BDC F E O O O B 01 J 04 TYP 04 04 TYP 04

Page 229 of 256 ends

co
co
co
co
co
co
co
co
co
co
co
co
NO

PARKING

EV CHARGING
ONLY

EV CHARGING

ONLY NO

PARKING
L7.01

PLANTING PLAN

AS NOTED
© LPA, Inc. Developed for
Job Number
Checked By
ScaleRevision Date

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
949-261-1001 Office
LPADesignStudios.com Submittal Date
5301 California Avenue, Suite 100
Irvine, California 92617
This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. SANTA TERESA FIRE STATION 1330 WEST LUCHESSA AVENUE GILROY, CA 95020 GRIFFIN STRUCTURES, INC. 33236
RF 70% SCHEMATIC DESIGN 03/10/2026 100% SD / BRIDGING DOCS 03/26/2026 PLANTING PLAN 1" = 20'-0" 05

SHRUB LIST
S1 ARCTOSTAPHYLOS DENSIFLORA 'HOWARD MCMINN' /

HOWARD MCMINN MANZANITA

BACCHARIS PILULARIS 'TWIN PEAKS'/

TWIN PEAKS DWARF COYOTE BRUSH

CEANOTHUS GRISEUS HORIZONTALIS 'YANKEE POINT'/

YANKEE POINT CEANOTHUS

ILEX VOMITORIA 'NANA'/

DWARF YAUPON HOLLY

LANTANA MONTEVIDENSIS/

TRAILING LANTANA

LEUCOPHYLLUM FRUTESCENS/

TEXAS SAGE

LOMANDRA LONGIFOLIA 'BREEZE'/

DWARF MAT RUSH

LOROPETALUM CHINENSE/

CHINESE FRINGE FLOWER

MUHLENBERGIA CAPILLARIS/

PINK MUHLY

MYOPORUM PARVIFOLIUM/

CREEPING MYOPORUM

MYRTUS COMMUNIS 'COMPACTA'/

DWARF MYRTLE, GREEK OLIVE

OLEA EUROPAEA 'MONTRA'/

LITTLE OLLIE DWARF OLIVE

PHORMIUM TENAX 'BRONZE BABY'/

NEW ZEALAND FLAX

RHAMNUS CALIFORNICA 'EVE CASE'/

EVE CASE COFFEEBERRY

RHAPHIOLEPIS INDICA/

NDIAN HAWTHORN

SALVIA GREGGII/

AUTUMN SAGE

SALVIA LEUCANTHA 'SANTA BARBARA'/

SANTA BARBARA MEXICAN BUSH SAGE

WESTRINGIA FRUTICOSA 'MORNING LIGHT'/

MORNING LIGHT COAST ROSEMARY

ZAUSCHNERIA CALIFORNICA/

CALIFORNIA FUCHSIA
S2 ACHILLEA 'MOONSHINE'

YARROW 'MOONSHINE'

IRIS DOUGLASIANA

DOUGLAS IRIS

NEPETA X FAASSENII

CATMINT

SALVIA LEUCANTHA

MEXICAN BUSH SAGE

SALVIA SPATHACEA

HUMMINGBIRD SAGE

SANTOLINA CHAMECYPARISSUS

LAVENDER COTTON
75% TO BE 1 GAL
@ 24" O.C.
25% TO BE 5 GAL
@ 36" O.C.

TREE LIST (NCN.)- NO COMMON NAME (*)- UNLESS NOTED ON PLAN REF. SYM. COMMON NAME SPACING COMMENTS

BOTANICAL NAME/ SIZE/
WUCOLS

MEXICAN REDBUD

CERCIS CANADENSIS 'MEXICANA'/

L STANDARD
36" BOX/

MUSKOGEE CRAPE MYRTLE

LAGERSTROEMIA I 'MUSKOGEE'/

L MULTI TRUNK
36" BOX/

COAST LIVE OAK

QUERCUS AGRIFOLIA

L STANDARD
36" BOX/

CORK OAK
QUERCUS SUBER/ L STANDARD36" BOX/

PLANTING LEGEND
'DRAKE' CHINESE ELM
ULMUS P. 'DRAKE'/

L STANDARD
36" BOX/
T2
T1

RAISED PLANTERS
15% TO BE 1 GAL
@ 3' O.C.
70% TO BE 5 GAL
@ 4' O.C.
15% TO BE 15
GAL @ 6' O.C.

B1 CAREX TUMULICOMA

BERKELEY SEDGE

CHONDROPETALUM TECTORUM

CAPE RUSH

JUNCUS PATENS 'ELK BLUE'

GRAY RUSH
1 GAL @ 18" O.C.

BIORETENTION BASINS
H1 CALIFORNIA NATIVE NO MOW GRASS SEED MIXTURE
BY STOVER SEED (1.5 LBS / 1000SF)

HYDROSEED

NEW FIRE STATION
T1
T2
T1
S1
B1
S1
S1 S1 S1
N
B1
S2
B1 S1 B1
S2
S1
T1
T1
S1
S1
S2 S2
TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

S1
S1
TYP.

TYP.

TYP.

H1

Page 230 of 256 ends

AC
NO

PARKING
EV

CHARGING
ONLY
EV

CHARGING
ONLY
NO

PARKING

04.01 04.01

04.01 04.01

32.02 32.02
1 EVCS
3 5
1 EVCS
1 1 ADA
1 ADA
W LUCHESSA AVE.

MILLER AVE.

PROPOSED NEW

BUILDING FIRE STATION

32.03 32.04

22.04 32.01

05.06 05.06

05.01 26.01
LIMIT OF WORK (L.O.W.)
# PARKING STALL COUNT

APPROXIMATE ROADWAY

CENTERLINE

PROPERTY LINE

1. SEE GENERAL NOTES ON G1.01.

2. FOR PARKING COUNTS, SEE G1.01.
1" = 20'-0"
SITE PLAN A0.21 05
Revision Date
408-780-7200 Office
60 South Market Street, Suite 1250
San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked By
Scale
Job Number Submittal Date 70% SCHEMATIC DESIGN 03/10/2026 100% SD / BRIDGING DOCS 03/26/2026 This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.

As indicated

SANTA TERESA FIRE STATION
1330 WEST LUCHESSA AVENUEGILROY, CA 95020
GRIFFIN STRUCTURES, INC.

SITE PLAN
A0.21
33236

MG / TP

KEYNOTES

04.01 4X16 CMU BLOCK SITE WALL.

05.01 CANTILEVERED COLUMN VEHICLE COVER, 13'-6" MIN, VERTICAL

CLEARANCE

05.06 CUSTOM METAL SLIDING GATE WITH PREFINISHED EXPANDED METAL PANELS (6'-0" H X 40'-0" L). GATE FRAME SHALL BE HSS 6X4 PERIMETER & AT PANEL JOINTS AND HSS 4X4 VERTICAL
INTERMEDIATE SUPPORTS.

22.04 OIL INTERCEPTOR PER PLUMBING DRAWINGS

26.01 ALTERNATE 1: PROVIDE COMPLETE PHOTOVOLTAIC ARRAY SYSTEM OVER PARKING CANOPY.

32.01 TRASH ENCLOSURE WITH ROOF COMPLIANT WITH LOCAL WASTE MANAGEMENT VENDOR REQUIREMENTS.

32.02 AC PAVING, SEE CIVIL DRAWINGS

32.03 APPARATUS VEHICLE WASH AREA

32.04 DRAIN FOR WASH AREA. CONNECTED TO FOX DRAIN SYSTEM TO DIVERT WATER TO SEWER WHEN HOSE BIB IS ACTIVATED.

LEGEND

GENERAL NOTES

PROJECT
NORT
N
H

TRASH ENCLOSURE WITH ROOF

IN COMPLIANCE WITH LOCAL

WASTE MANAGEMENT AND AHJ

REQUIREMENTS GENERATOR ENCLOSURE

Page 231 of 256 ends

W D
DW
REF.

MW
CM
HOSE

STORAGE
TVTV
MIRROR
MB
TV
TV
WH

EXTRACTOR
DRYING
RACK
.

RH
.

TV
AC
TV
MB
REF.

ICE
1 HOUR RATED WALL CONSTRUCTION

DENOTES MILLWORK

NON-RATED STUD WALL CONSTRUCTIONS

MASONRY BLOCK WALL CONSTRUCTION

1. ALL WALLS TO BE 6" STUD FRAMING AT PERIMETER WALLS WITH PLASTER OR METAL PANEL AND 4" STUD FRAMING AT INTERIOR WALLS WITH GYP AT

BOTH SIDES AND FULL THICKNESS BATT INSULATION, UNO

2. PROVIDE 6" HIGH CONCRETE CURBS @ ALL RESTROOMS, CUSTODIAL

CLOSETS, WATER HEATER CLOSETS, & SHOWER COMPARTMENTS, UNO

3. PROVIDE MOISTURE RESISTANT GYP BD IN ALL WET LOCATIONS, UNO.

4. PROVIDE CEMENTITIOUS BACKER BOARD @ ALL TILE WALL LOCATIONS, UNO

5. PROVIDE IMPACT RESISTANT GYP BOARD AT CORRIDORS AND HALLWAYS TO 4' A.F.F.

6. PENETRATIONS THROUGH RATED WALL CONDITIONS TO BE PROTECTED AS REQUIRED BY THE CBC. PROVIDE THE PENETRATIONS THROUGH RATED WALL CONDITIONS. FOR ALL RATED WALLS, PROVIDE THE FOLLOWING MARKINGS & IDENTIFICATIONS PER THE APPLICABLE CODES:

A. BE LOCATED WITHIN 15 FT OF THE END OF EA WALL & @ INTERVALS NOT EXCEEDING 30 FT MEASURED HORIZ ALONG THE WALL OR PARTITION.

B. INCLUDE LETTERING NOT LESS THAN 3" IN HEIGHT WITH A MIN 3/8"

STROKE IN A CONTRASTING COLOR INCORPORATING THE SUGGESTED WORDING, "FIRE &/OR SMOKE BARRIER - PROTECT ALL OPENINGS", OR OTHER WORDING.
1 1
A A
A3.01
08 07 A3.01
A3.01
06 A3.01 05
5'-8"
2 2
3 3
4 4
5 5
6 6
B B
C C
D D
E E
F F
7 7
107'-4"

ACCESSIBLE

RESTROOM/
SHOWER
111

RESTROOM/
SHOWER
110

RESTROOM/
SHOWER
109

LAUNDRY/

JANITOR
108

ELECTRICAL
121
DORM
112
DORM
113
DORM
114
DORM
115
DORM
116 NONRATED

CORRIDOR
119

NON-RATED

CORRIDOR
107

TURNOUT
122

MEDICAL

STORAGE
124
DAY
ROOM
106
DINING
104
WEIGHT
ROOM
102
SHARED
OFFICE
101

CAPTAIN'S
OFFICE
117

APPARATUS
BAY
125

ACCESSIBLE

RESTROOM
131

DECONTAMINATION
130
WORK
ROOM
126
FIRE
RISER
129
AIR
COMP.
127
22'-0" 17'-9" 37'-1" 12'-8" 10'-0"
5'-8"

KITCHEN
103
STOR.
128
99'-6"
STOR.

CLOSET
118
05 A3.11
8 8
10'-3"
4'-0" 29'-6" 11'-0" 6'-4 1/2" 18'-8 3/4" 18'-8 3/4" 19'-0" 99'-6"
22'-0" 17'-9" 37'-1" 12'-8" 10'-0"
10'-3" 9'-5 5/8"
107'-4"
4'-0" 29'-6" 11'-0" 6'-4 1/2" 18'-8 3/4" 18'-8 3/4" 19'-0" EQ. EQ.

EQ. EQ.
07 A3.11
06 A3.11
5'-10"
4'-0" 2'-0" 2'-0"
3'-6"
EQ. EQ. 34'-1"
3'-6"
16'-6"
3'-10 1/2" 4'-0" 6'-0" 4'-0" 6'-0" 4'-0" 6'-0" 4'-0" 6'-0" 4'-0" 2'-1 1/2"
3'-0"
1'-5"
2'-3 1/2"
3'-0"
9'-4 1/2" 2'-1 1/2"
2'-8"
2'-0"
2'-8"
2'-0"
2'-8"
2'-0"
2'-8"
2'-0"
2'-8"
14'-9" EQ. 4'-0" EQ.

06.01 08.02

08.12 09.01

09.01 09.01
TYP.

11.01 22.01

12.01 09.01
1'-2 1/4"

05.05 09.01

09.01 12.01

08.01 08.01

08.01 08.01

08.01 MDF
123

10.01 09.04

05.05 06.02

08.09 08.10

NON-RATED

CORRIDOR
105

TO TOP OF HIGHEST OPERABLE PART
3'-4".

CUSTOM 18 GA BRUSHED
ST. STL. COVER FOR A

LARGE CONTROLLER
RECESSED J-BOX.

STANDARD 3 BUTTON DOOR
CONTROL PAD, TYP.

KEY LOCKOUT, TYP.

EQ.
10"
1'-0"
EQ.

FIN. FLR.

TO TOP OF HIGHEST OPERABLE PART
3'-4"
RED ACTIVATION BUTTON.

OPENS ALL 3 DOORS

SIMULTANEOUSLY
CUSTOM 18 GA BRUSHED
ST. STL. COVER FOR A

LARGE CONTROLLER
RECESSED J-BOX.

STANDARD 3 BUTTON DOOR
CONTROL PAD, TYP.

KEY LOCKOUT, TYP.

EQ. EQ.

EQ. EQ.
1'-2"
1'-2"
FIN. FLR.

OPERATIONAL NOTE: THE 3RD

DOOR CONTROL SERVES TO OPEN

VEHICULAR EGRESS SITE GATE
Revision Date
408-780-7200 Office
60 South Market Street, Suite 1250
San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked By
Scale
Job Number Submittal Date 70% SCHEMATIC DESIGN 03/10/2026 100% SD / BRIDGING DOCS 03/26/2026 This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.

As indicated

SANTA TERESA FIRE STATION
1330 WEST LUCHESSA AVENUEGILROY, CA 95020
GRIFFIN STRUCTURES, INC.

FLOOR PLAN
A2.01
33236

MG / TP

KEYNOTES

05.05 ROOF ACCESS LADDER.

06.01 PULLOUT TRASH/ RECYCLE/ COMPOST MILLWORK

06.02 3 SEPARATE TALL CABINETS, LOCKABLE FOR PANTRY STORAGE.

08.01 EMERGENCY ESCAPE CASEMENT WINDOW WITH MINIMUM 5 SF NET CLEAR OPENING AND COMPLIANT PER CBC R310.

08.02 TEMPERED MIRRORS.

08.09 FRONT DOOR COMMON CONTROL PANEL, SEE 08/A2.01

08.10 REAR DOOR COMMON CONTROL PANEL, SEE 12/A2.01

08.12 STOREFRONT WINDOW SYSTEM

09.01 PROVIDE BACKING FOR TV MONITORS.

09.04 LEVEL 5 FINISH.

10.01 CUSTOM SIGNAGE PIECE, $3,000 HOLD

11.01 GEARGRID STANDARD TURNOUT LOCKERS.

12.01 4' X 6' BACK PAINTED MAGNETIC GLASS BOARD.

22.01 WATER BOTTLE FILLING STATION, RECESSED MECHANICAL PUSH BAR ACTUATOR.

LEGEND

GENERAL NOTES
1/8" = 1'-0"
FLOOR PLAN A2.01 05 PROJECT NORTH
N
1" = 1'-0"
COILING DOOR CONTROLS - REAR A2.01 12
1" = 1'-0"
A2.01 08

COILING DOOR CONTROLS -
FRONT
NTS

Page 232 of 256 ends

M M
M
WP
WP
J
J
1 1
A A
A3.01
08 07 A3.01
A3.01
06 A3.01 05
2 2
3 3
4 4
5 5
6 6
B B
C C
D D
E E
F F
7 7
05 A3.11
8 8
07 A3.11
06 A3.11
53'-4"
107'-8"
42'-4" 11'-0"
66'-0"
45'-8 1/2"
18'-1"

07.03 07.05
15'-0" TOP OF WALL
2" / 12" 2" / 12"
2" / 12"
2" / 12"
2" / 12"
2" / 12"
2" / 12"
2" / 12" 2" / 12" 2" / 12" 2" / 12"

07.05 11'-6"

07.08 1'-10 1/2"
1'-10 1/2"
1'-2 1/2"

08.03 18'-0" TO B.O. SOFFIT
18'-0" TO B.O. SOFFIT
10'-8" TO B.O. SOFFIT
10'-8" TO B.O. SOFFIT
10'-8" TO B.O. SOFFIT

07.01 07.02

07.02 48'-7"
15'-11"

07.02 07.01
3/8"/ 12" 3/8"/ 12"

07.02 07.02

07.02 07.02

07.01 3/8"/ 12"
3/8"/ 12"
1/4"/ 12"
1/4"/ 12"
1/4"/ 12" 1/4"/ 12"

08.03 4'-0"
4'-0"
8'-0"
4'-0"
8'-0"
4'-0"
8'-0"
4'-0"
4'-0"
4'-0"
8'-0"
4'-0"
3/8"/ 12"
3/8"/ 12"
1'-1" 5'-4 3/8"

07.06 07.07 07.01

07.07 26.02

26.02 05.07

05.07 2'-9 3/4"
2'-6 3/8"

07.04 07.04

23.02 INSULATED METAL PANEL ROOFING
BASIS OF DESIGN: AEP SPAN SPAN-LOK, COLOR SLATE GRAY
SINGLE PLY ROOFING OVER R30 RIGID

INSULATION (POLYISO) OVER ROOF DIAPHRAGM

EDGE OF EXTERIOR WALL BELOW

EDGE OF ROOF BELOW

ROOF CRICKET
3/8" / FOOT SLOPE

ROOF DRAIN

1. EXTERIOR WALL INSULATION TO BE MIN R-30.

2. ROOF INSULATION TO BE MIN R-18.
1/8" = 1'-0"
ROOF PLAN A2.02 05
Revision Date
408-780-7200 Office
60 South Market Street, Suite 1250
San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked By
Scale
Job Number Submittal Date 70% SCHEMATIC DESIGN 03/10/2026 100% SD / BRIDGING DOCS 03/26/2026 This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
1/8" = 1'-0"

SANTA TERESA FIRE STATION
1330 WEST LUCHESSA AVENUEGILROY, CA 95020
GRIFFIN STRUCTURES, INC.

ROOF PLAN
A2.02
33236

MG / TP

KEYNOTES

05.07 PROVIDE 2 ROWS OF 12' L UNISTRUT RAIL ATTACHED TO INSIDE OF ROOF WELL PARAPET WALLS. CONFIRM LOCATION WITH CITY FOR

ANTENNA LOCATION & AIMING DIRECTION

07.01 4" MIN. WIDE GUTTER WITH 1/8" PER FOOT SLOPE, PER 19/A3.01

07.02 3" MIN. DIAMETER DOWNSPOUT.

07.03 FLAT ROOF ASSEMBLY.

07.04 SHEET METAL FASCIA PREFINISHED TO MATCH STANDING SEAM METAL ROOF (22 GA MIN) PER 19/A3.01 DETAIL A

07.05 20 GA. PREFINISHED SHEET METAL WALL CAP.

07.06 SHEET METAL ROOF DIVERTER

07.07 5/16" BLACK OXIDE CHAIN DOWNSPOUT

07.08 FLAT ROOF ASSEMBLY. SLOPE STRUCTURE TO PROVIDE DRAINAGE.

08.03 ROOF ACCESS HATCH.

23.02 MECHANICAL HVAC EQUIPMENT.

26.02 PROVIDE WEATHERPROOF GFCI ROOF TOP RECEPTACLE AS
REQUIRED. VERIFY EXACT MOUNTING LOCATIONS WITH OWNER
LEGEND

GENERAL NOTES

PROJECT NORTH
N

Page 233 of 256 ends

W D
DW
REF.

CM
WH
.

RH
.

AC
REF.

ICE
CG
CG
CGCG
CGCG
CG CG

CGCG CG
CG
CG
CG
CG
CGCG
CGCGCG
CGCG

CGCGCG CG
CG
CG
CG CG

DENOTES MILLWORK - SEE BOD NARRATIVE

FINISH TAG

FINISH CODE

FLOOR TRANSITION

CORNER GUARD
CG
?
GENERAL FINISHES: ALL WALLS TO BE PAINTED (P-1), UNO ALL FLOORING TO BE (PC-1), UNO ALL BASE TO BE (B-1), UNO.

1. DESIGN-BUILD ENTITY SHALL PROVIDE SHOP DRAWINGS FOR EDGE CONDITIONS AND DIRECTION OF INSTALLATION OF ALL FLOOR FINISHES.

2. ACCESS PANELS: PAINT TO MATCH ADJACENT WALL/SOFFIT, WHERE OCCURS.

3. WINDOW COVERINGS: SEE REFLECTED CEILING PLAN FOR LOCATIONS AND TYPE.

4. TILE APPLICATION: SEAL ALL FLOOR AND WALL GROUT AROUND PLUMBING AND WET AREAS. SEAL GROUT PER MANUFACTURER’S SPECIFICATIONS.

ARCHITECT TO APPROVE TILE MOCK-UP BEFORE INSTALLATION.

5. FLOOR: CONTINUE FLOOR FINISH UNDER COUNTERS WHERE BASE CABINETS

ARE NOT SHOWN, UNDER ACCESSIBLE SINK CABINETS, AND INTO EQUIPMENT AREAS UNDER UPPER CABINETS.

6. FLOOR: PROVIDE 'FEATHER UP' TRANSITION AT ALL DOORS WHEN THERE IS A DIFFERENCE OF 1/4" OR MORE TO MEET ACCESSIBLE REQUIREMENTS AT A MINIMUM.

7. MATERIAL DIRECTIONAL INSTALLATION: IF THE INSTALLATION DIRECTION IS

NOT INDICATED ON PLANS, CONTACT ARCHITECT FOR CLARIFICATION PRIOR TO INSTALLATION.

8. ALL INTERIOR WALL, FLOOR, AND CEILING FINISH MATERIALS TO COMPLY WITH SECTION 803 - IN ACCORDANCE WITH ASTM E-84 NFPA 286 WITH ALL FINISHES IN RATED CONDITIONS CLASSIFIED AS CLASS "A" FLAME SPREAD AND SMOKE DENSITY. INTERIOR EXIT STAIRWAYS AND RAMPS AND EXIT PASSAGEWAYS ARE NOT TO EXCEED CLASS "B." CORRIDORS AND

ENCLOSURE FOR EXIT ACCESS STAIRWAYS AND RAMPS ARE TO NOT TO EXCEED CLASS "C."

9. INTERIOR WALL AND CEILING FINISH MATERIAL CLASS PER 803.13 IS TO MEET

FLAME SPREAD AND SMOKE DENSITY IN ACCORDANCE WITH CBC TABLE 803.1.2.

10. CURTAIN, DRAPERIES, FABRIC HANGINGS AND SIMILAR COMBUSTIBLE

DECORATIVE MATERIALS SUSPENDED FROM WALLS OR CEILINGS SHALL COMPLY WITH FIRE CODE SECTION 807 AND MEET THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701.
11 AA
2233445566
BB
CC
DD
EE
FF
77 FIRE
RISER
129

DECONTAMINATION
130

ACCESSIBLE

RESTROOM
131
WORK
ROOM
126
AIR
COMP.
127

CAPTAIN'S
OFFICE
117
WEIGHT
ROOM
102
MDF
123

MEDICAL

STORAGE
124
SHARED
OFFICE
101
DORM
116
DORM
115
DORM
114
DORM
113
DORM
112

LAUNDRY/

JANITOR
108

RESTROOM/
SHOWER
109

RESTROOM/
SHOWER
110

ACCESSIBLE

RESTROOM/
SHOWER
111

TURNOUT
122

ELECTRICAL
121
DAY
ROOM
106

KITCHEN
103
DINING
104

APPARATUS
BAY
125
NONRATED

CORRIDOR
119

NON-RATED

CORRIDOR
107

NON-RATED

CORRIDOR
105
88 STOR.
128
STOR.

CLOSET
118
SDT
RB-1
PC-1
AWP-1
P-3
PC-1
PC-1
T-1
PC-1
PC-1
PC-1
PC-1
PC-1
PC-1
PC-1
PC-1
PC-1
PC-1
PC-1
SC-1
PC-1
PC-1
PC-2
PC-2
PC-2
SC-1
PC-2 SC-1
PC-2
WP-1
B-2
WP-1
WP-1 WP
-1
WP-1
WP-1
WP-1
WP-1 WP-1
WP-1
WP-1
PC-2
FRP
PC-2
WP-2
FRP
B-2
P-2
P-2P3 P-3 P-3 P-3 P-3
RF-1
RF-1
WP-2
WP-2
B-3
PC-1
WP-2
RF-1
B-3
PC-1
WP-2
RF-1
B-3
B-3

09.05 Revision Date
408-780-7200 Office
60 South Market Street, Suite 1250
San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked By
Scale
Job Number Submittal Date 70% SCHEMATIC DESIGN 03/10/2026 100% SD / BRIDGING DOCS 03/26/2026 This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
1/8" = 1'-0"

SANTA TERESA FIRE STATION
1330 WEST LUCHESSA AVENUEGILROY, CA 95020
GRIFFIN STRUCTURES, INC.

FLOOR FINISHES PLAN
A2.21
33236

MG / TP

KEYNOTES

09.05 PROVIDE FULL HEIGHT STAINLESS STEEL BACKSPLASH AT FULL WIDTH OF RANGE HOOD.

LEGEND

GENERAL NOTES
1/8" = 1'-0"
FLOOR FINISHES PLAN A2.21 05 PROJECT NORTH N

Page 234 of 256 ends

CLNG CLNG
GYP-1 - FRAMED GYP
BD CLG
ACT-1
2 X 2 SUSPENDED ACOUSTICAL CEILING TILE
GYP-2 - FRAMED

MOISTURE-RESISTANT
GYP BD CLG.

CENTER DEVICES ON CLG TILE - TYP
INCLUDED BUT NOT LIMITED TO THE FOLLOWING:

SPRINKLER, FIRE STROBE, SPEAKERS, DAYLIGHT &
OCCUPANCY SENSORS.

EXIT SIGN. REFER TO ELEC.
9'-0"
XXX-1

TYP CLG HEIGHT, UNO

TYP CLG TYPE, UNO
EQ EQ
EQ EQ

ACCESS PANEL
1 1
A A
2 2
3 3
4 4
5 5
6 6
B B
C C
D D
E E
F F
7 7

ACCESSIBLE

RESTROOM
131
WORK
ROOM
126
AIR
COMP.
127

CAPTAIN'S
OFFICE
117
WEIGHT
ROOM
102
MDF
123

MEDICAL

STORAGE
124
DORM
116
DORM
115
DORM
114
DORM
113
DORM
112

LAUNDRY/

JANITOR
108

RESTROOM/
SHOWER
109

RESTROOM/
SHOWER
110

ACCESSIBLE

RESTROOM/
SHOWER
111

TURNOUT
122

ELECTRICAL
121
DAY
ROOM
106

KITCHEN
103
DINING
104

APPARATUS
BAY
125
NONRATED

CORRIDOR
119

NON-RATED

CORRIDOR
105
FIRE
RISER
129

DECONTAMINATION
130
SHARED
OFFICE
101

NON-RATED

CORRIDOR
107
8 8
STOR.
128
STOR.

CLOSET
118
10' - 0"
ACT-1
8' - 0"
GYP-1
8' - 0"
ACT-1
8' - 0"
ACT-1 8' - 0"
ACT-1
8' - 0"
GYP-1
9' - 0"
ACT-1 8' - 0"
ACT-1
8' - 0"
ACT-1
8' - 0"
ACT-1
8' - 0"
ACT-1
8' - 0"
ACT-1
8' - 0"
ACT-1
8' - 0"
ACT-1
8' - 0"
ACT-1
8' - 0"
GYP-2
8' - 0"
GYP-1
8' - 0"
GYP-2
8' - 0"
GYP-2
8' - 0"
GYP-2
8' - 3"
GYP-2
8' - 0"
GYP-2
8' - 0"
GYP-1
8' - 0"
GYP-1
9' - 0"
GYP-1
9' - 0"
ACT-1

08.03 05.05

05.05 08.03

09.03 09.02

09.02 09.02

09.02 09.02

09.02 12.07

12.07 12.07

12.07 12.07
8' - 0"
GYP-1
8' - 0"
GYP-1
8' - 2"
GYP-1
Revision Date
408-780-7200 Office
60 South Market Street, Suite 1250
San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked By
Scale
Job Number Submittal Date 70% SCHEMATIC DESIGN 03/10/2026 100% SD / BRIDGING DOCS 03/26/2026 This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
1/8" = 1'-0"

SANTA TERESA FIRE STATION
1330 WEST LUCHESSA AVENUEGILROY, CA 95020
GRIFFIN STRUCTURES, INC.

REFLECTED CEILING
PLAN
A2.31
33236

MG / TP

KEYNOTES

05.05 ROOF ACCESS LADDER.

08.03 ROOF ACCESS HATCH.

09.02 OPEN CEILING, PAINT EXPOSED STRUCTURE.

09.03 ALL EXPOSED DUCTWORK, PIPING, CONDUIT, CABLE TRAYS,

SUSPENSION WIRES, STRUTS, FRAMING, STUDS, EQUIPMENT AND DEVICES ABOVE 10'-0" TO ORGANIZED/ BUNDLED TOGETHER IN
CLEAN PATHS AND MOUNTING SUPPORTS. TO BE PAINTED.

12.07 MANUAL WINDOW SHADES.

LEGEND

GENERAL NOTES
1/8" = 1'-0"
FIRST FLOOR REFLECTED CEILING PLAN A2.31 05 PROJECT NORTH N

Page 235 of 256 ends

WP WP
WP
WP
WP
WP
J
M
M
M
M
M
M
M
M
M
M
M
M
M
M
J
J
J
J
J
J
J
CLNG
J J J
J J J
WP WP
J
J
CLNG
CLNG

CLNG CLNG CLNG
W D
DW
REF.

MW
CM
HOSE

STORAGE
TVTV
MIRROR
COMP
MB
TV

PRINTER

PRINTER
TV
COMP
COMP
COMP
COMP
WH

EXTRACTOR
DRYING
RACK
COMP
. RH
. TV
AC
TV
MB
REF.

ICE
1 1
A A
2 2
3 3
4 4
5 5
6 6
B B
C C
D D
E E
F F
7 7
WEIGHT
ROOM
102
8 8

CHARGING
FIRE
RISER
129

DECONTAMINATION
130

ACCESSIBLE

RESTROOM
131
WORK
ROOM
126
AIR
COMP.
127

CAPTAIN'S
OFFICE
117
MDF
123

MEDICAL

STORAGE
124
SHARED
OFFICE
101
DORM
116
DORM
115
DORM
114
DORM
113
DORM
112

LAUNDRY/

JANITOR
108

RESTROOM/
SHOWER
109

RESTROOM/
SHOWER
110

ACCESSIBLE

RESTROOM/
SHOWER
111

TURNOUT
122

ELECTRICAL
121
DAY
ROOM
106

KITCHEN
103
DINING
104

APPARATUS
BAY
125
NONRATED

CORRIDOR
119

NON-RATED

CORRIDOR
107

NON-RATED

CORRIDOR
105
STOR.

CLOSET
118
STOR.
128
08 09
14 14
14 14
14 16
14 16
22 22
20 18
21 19
17 23
07 01
05 03
06 02
04 28
10 22 26
22 29
30 31
13 26.03
TYP.

12.06 TYP.

12.06 09.04

12.09 22
22 12.10

12.10 02

10.01 12

11.03 11.04

11.03 11.04

27.04 27.05

11.03 11.04

11.03 11.04

27.03 EQUIPMENT TAG - SEE SCHEDULE ON THIS SHEET

KEYNOTE - DESIGN-BUILD ENTITY FURNISHED AND

DESIGN-BUILD ENTITY INSTALLED
1i
?
Revision Date
408-780-7200 Office
60 South Market Street, Suite 1250
San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked By
Scale
Job Number Submittal Date 70% SCHEMATIC DESIGN 03/10/2026 100% SD / BRIDGING DOCS 03/26/2026 This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
1/8" = 1'-0"

SANTA TERESA FIRE STATION
1330 WEST LUCHESSA AVENUEGILROY, CA 95020
GRIFFIN STRUCTURES, INC.

EQUIPMENT/

FURNITURE PLAN
A2.41
33236

MG / TP

KEYNOTES

09.04 LEVEL 5 FINISH.

10.01 CUSTOM SIGNAGE PIECE, $3,000 HOLD

11.03 CORD REEL ASSEMBLY AT +10' A.F.F., PROVIDE BACKING AS REQUIRED. BOD REELCRAFT, MODEL L 4545 123 9G

11.04 COMPRESSED AIR HOSE REEL AT +10' A.F.F., PROVIDE BACKING AS REQUIRED. BOD REELCRAFT RS7650 OLP

12.06 HEAVY DUTY STEEL SHELVING. 48"WX16"D

12.09 MIRROR FULL HEIGHT

12.10 MARKER BOARD

26.03 PROVIDE POWER AND DATA FOR OFOI RADIO CHARGING
EQUIPMENT (2 DOUBLE
DUPLEX OUTLETS & 2 DOUBLE DATA OUTLETS, MIN. EACH

LOCATION)

27.03 GPS REPEATER AT 12' AFF, POWER & RACEWAY TO ROOF WELL

ABOVE WITH WEATHER HEAD

27.04 PROVIDE (3) 3" CONDUIT, BUSHING, AND WEATHERHEAD WITH

PULLSTRING TO ROOF FOR WIRELESS REPEATER PROVISIONS
MOUNTED AT 16' AFF. COORDINATE

EXACT LOCATION OF CONDUIT STUB UPS WITH OWNER PRIOR TO
ROUGH IN AND INSTALLATION. COORDINATE TERMINATION WITH
OWNER FOR LOCATION & DIRECTION FOR ANTENNA.

27.05 FIRE STATION ALERTING SCREEN, PROVIDE POWER AND C.O. FOR

DATA CABLING PER STATION ALERTING REQUIREMENTS

GENERAL NOTES
1/8" = 1'-0"
EQUIPMENT PLAN A2.41 05
LEGEND

FURNITURE & EQUIPMENT SCHEDULE
TAG # EQUIPMENT DESCRIPTION OFOI CFCI
01 DISHWASHER BUILT IN WITH TRIM KIT - ADA HT. ASKO 24" 30 SERIES DB 16631S X 02 REFRIGERATOR 25 CU FT FRENCH DOOR WRF535SWH X
03 MICROWAVE DRAWER WITH BUILT IN WITH TRIM KIT HMB30155UC X 04 WATER BOTTLE
FILLER

PROVIDE WATER LINE & BOTTLE FILLING STATION PER PLUMBING X 05 ELECTRIC RANGE WOLF 36" PROFESSIONAL INDUCTION RANGE, IR36551/S/P X 06 RANGE HOOD WOLF 36" PRO WALL HOOD - 27" DEPTH WITH 1200 CFM INTERNAL BLOWER.

PROVIDE DUCTED VENTILATION TO ROOF.

X
07 COFFEE MAKER DBE TO PROVIDE WATER CONNECTION PER PLUMBING X 08 WASHER LG-WM8980HVA WASHER, GC TO VERIFY SIZE AND PROVIDE POWER/ DATA

CONNECTION
X
09 DRYER LG-DLEX8900B DRYER, GC TO VERIFY SIZE AND PROVIDE POWER/ DATA

CONNECTION
X
10 HEAVY DUTY

EXTRACTOR

VERIFY SIZE, CLEARANCES, AND PROVIDE POWER/ DATA CONNECTION READY RACK, EW35G SOFT-MOUNT EXTRACTOR 5.2 CU FT.

X
12 ICE MAKER VERIFY SIZE, CLEARANCES, AND PROVIDE POWER CONNECTION X 13 AIR COMPRESSOR VERIFY SIZE, CLEARANCES, AND PROVIDE POWER CONNECTION X 14 COMPUTER DBE TO PROVIDE POWER AND DATA CONNECTIONS X 16 PRINTER DBE TO PROVIDE POWER AND DATA CONNECTIONS X
17 PRESS BENCH EXERCISE EQUIPMENT X
18 LIFTING BENCH EXERCISE EQUIPMENT X
19 ELLIPTICAL BIKE DBE TO PROVIDE POWER CONNECTION X
20 TREADMILL DBE TO PROVIDE POWER CONNECTION X
21 ROW MACHINE EXERCISE EQUIPMENT X
22 TELEVISION PROVIDE WALL POWER AND AV/DATA CONNECTIONS. X 23 WEIGHT RACK EXERCISE EQUIPMENT X
26 HOSE STORAGE RACK GROVES FIRE HOSE STORAGE RACK: MOBILE FIRE HOSE RACK, 3000 FT, 104 IN X 87 IN
X
28 DRYER CABINET READY RACK, SMART-DRY 6 ALL-PURPOSE DRYING CABINET X 29 TRASH BIN X
30 RECYCLE BIN X
31 COMPOST BIN X
NOTE: DBE TO PROVIDE "CFCI" EQUIPMENT.

Page 236 of 256 ends

FIRST FLOOR
0'-0"
1 LOW EAVE
10'-8"
7 6 5 4 3 2

HIGH EAVE
18'-0"
8 07
A3.11
06 A3.11

PARAPET
15'-0"

07.05 08.07 08.07 07.01 08.12

07.01 19
A3.01

07.02 07.02 08.12
EQ. EQ.

C.L.

07.07 EQ EQ
C.L.

FIRST FLOOR
0'-0"
1 LOW EAVE
10'-8"
2 3 4 5 6 7

HIGH EAVE
18'-0"
07 8
A3.11
06 A3.11

FLAT ROOF
2"15'-0"
/ 12"
2" / 12"
2" / 12"
2" / 12"
2" / 12"

07.01 07.05

07.01 07.05

08.07 08.07 08.12

08.12 EQEQ

07.02 C.L.

POLYMER MODIFIED FIBERGLASS REINFORCED
PLASTER (PL-1); PAINTED

INSULATED METAL PANEL ROOFING
BASIS OF DESIGN: AEP SPAN APAN-LOK, COLOR SLATE GRAY
INSULATED LOW-E VISION GLAZING (GL-1)

DRIFT JOINT
4X16X8 CMU BLOCK

1. EXTERIOR WALL ASSEMBLY INSULATION TO BE MIN R-19.

2. ROOF ASSEMBLY INSULATION TO BE MIN R-30.

FIRST FLOOR
0'-0"
A

LOW EAVE
10'-8"

F E D C B

HIGH EAVE
18'-0"
05 A3.11

FLAT ROOF
2 15'-0"
" / 12"
2" / 12"
2" / 12"
2" / 12"
2" / 12"

07.01 07.01

07.01 08.12

07.02 07.02

FIRST FLOOR
0'-0"
A

LOW EAVE
10'-8"

B C D E F

HIGH EAVE
18'-0"
05 A3.11
2" / 12"
2" / 12"
2" / 12"
2" / 12"
2" / 12"

07.04 07.04

10.03 07.05

07.05 8'-0"

10.02 3'-0"
TYP.

08.06 08.01
TYP.

08.06 17
A3.01
18 A3.01

07.07 07.07

07.04 07.02

SEALANT & BACKER ROD

EXTERIOR INTERIOR

CMU W/ WEATHERED JOINT
(TYP)
1/4"/ 1'
1"
1"
2 1/2"
5/8" GYP BD

METAL STUD FRAMED WALL W/

FULL THICKNESS BATT

INSULATION
1/2"
1/2"

OPERTABLE/ FIXED WINDOW
ASSEMBLY, AS OCCURS. SHIM
18 GA. PREFINISHED SHEET AS REQUIRED

METAL SILL FLASHING W/

DAM AT WINDOW SILL &
HEMMED DRIP 16 GA. CLEAT

SEALANT & BACKER ROD

EXTERIOR INTERIOR

WEATHER BARRIER EXTEND

OVER EDGE OF FLASHING
MEMBRANE, LAP 2" MIN. OVER

FLASHING
1/4"/ 1'

OPERABLE/ FIXED WINDOW
ASSEMBLY, AS OCCURS.

SHIM AS REQUIRED
1/4"

LINE OF JAMB SHEET METAL

FLASHING BEYOND, SIM TO
HEAD
LINE OF C.M.U. BEYOND
18 GA. PREFINISHED SHEET

METAL HEAD EXTENDING

BEYOND & JAMB FLASHING
SILL & HEMMED DRIP 16 GA.

CLEAT

EXTERIOR PLASTER SYSTEM
O/ WRB SYSTEM O/ EXT. GYP.
& C.I.

EXTERIOR PLASTER SYSTEM
O/ WRB SYSTEM O/ EXT. GYP.
& C.I.

VARIES PER PLAN

FRY REGLET VENTED
REVEAL FPM-75-V-100,

PREFINISHED TO MATCH

PLASTER

STANDING SEAM METAL ROOF, WITH

DOWNTURNED EAVE EDGE, OVER

ROOF UNDERLAYMENT
22 GA. SHEET METAL GUTTER LINER
PREFINISHED WHITE. VARIABLE SLOPE
TO DRAIN 1/8" / FT MIN SLOPE
20 GA. SHEET METAL GUTTER

PREFINISHED TO MATCH ROOF PANEL

CHAIN DOWNSPOUT WHERE OCCURS
16 GA CONT.

CLEAT
SHEET
METAL

FLASHING

TO MATCH
GUTTER

SEE DETAIL A FOR

CONDITION WHERE

GUTTER DOES NOT
OCCUR

DETAIL A
1" W X 20 GA. SHEET METAL GUTTER
BRACKET AT 36" O.C., PREFINISHEF TO

MATCH ROOF
1/8" = 1'-0"
EXT ELEVATION - NORTH A3.01 08
1/8" = 1'-0"
EXT ELEVATION - SOUTH A3.01 06
Revision Date
408-780-7200 Office
60 South Market Street, Suite 1250
San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked By
Scale
Job Number Submittal Date 70% SCHEMATIC DESIGN 03/10/2026 100% SD / BRIDGING DOCS 03/26/2026 This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.

As indicated

SANTA TERESA FIRE STATION
1330 WEST LUCHESSA AVENUEGILROY, CA 95020
GRIFFIN STRUCTURES, INC.

EXTERIOR ELEVATIONS
A3.01
33236

MG / TP

KEYNOTES

07.01 4" MIN. WIDE GUTTER WITH 1/8" PER FOOT SLOPE, PER 19/A3.01

07.02 3" MIN. DIAMETER DOWNSPOUT.

07.04 SHEET METAL FASCIA PREFINISHED TO MATCH STANDING SEAM METAL ROOF (22 GA MIN) PER 19/A3.01 DETAIL A

07.05 20 GA. PREFINISHED SHEET METAL WALL CAP.

07.07 5/16" BLACK OXIDE CHAIN DOWNSPOUT

08.01 EMERGENCY ESCAPE CASEMENT WINDOW WITH MINIMUM 5 SF NET CLEAR OPENING AND COMPLIANT PER CBC R310.

08.06 FIXED WINDOW OF SIMILAR TYPE TO OPERABLE WINDOWS.

08.07 SECTIONAL HIGH RISE DOOR, WITH GLAZED PANELS. MOTORIZED

WITH CENTRAL COMMON DOOR OPENING CONTROL PANEL FOR
FRONT DOORS.

08.12 STOREFRONT WINDOW SYSTEM

10.02 12" TALL X 2" DEEP PIN-MOUNTED ALUMINUM BUILDING ADDRESS.

PROVIDE HALO-LIT, INTERNALLY ILLUMINATED COPY. COORDINATE FINAL LOCATION AND QUANTITIES WITH AHJ.

10.03 12" TALL X 1/2" THICK ALUMINUM PIN-MOUNTED (1" OFF MOUNTING SURFACE) BUILDING SIGNAGE. PROVIDE EXTERNAL ILLUMINATION FROM PLANTER BELOW.

LEGEND

GENERAL NOTES
1/8" = 1'-0"
EXT ELEVATION - EAST A3.01 07
1/8" = 1'-0"
EXT ELEVATION - WEST A3.01 05 3" = 1'-0"WINDOW SILL A3.01 17 3" = 1'-0"
WINDOW HEAD A3.01 18
3" = 1'-0"
CONCEALED GUTTER A3.01 19

Page 237 of 256 ends

1. EXTERIOR WALL ASSEMBLY INSULATION TO BE MIN R-19.

2. ROOF ASSEMBLY INSULATION TO BE MIN R-30.

FIRST FLOOR
0'-0"
1 LOW EAVE
10'-8"
2 3 4 5 6 7

HIGH EAVE
18'-0"
8 07
A3.11
06 A3.11

DECONTAMINATION
130

APPARATUS
BAY
125 MDF
123
DAY
ROOM
106

NON-RATED

CORRIDOR
105
SHARED
OFFICE
101
10'-6"

FIRST FLOOR
0'-0"
A

LOW EAVE
10'-8"

F E D C B

HIGH EAVE
18'-0"
05 A3.11

APPARATUS
BAY
125

FIRST FLOOR
0'-0"
A

LOW EAVE
10'-8"

F E D C B

HIGH EAVE
18'-0"
05 A3.11

KITCHEN
103
DINING
104
DAY
ROOM
106

NON-RATED

CORRIDOR
107

LAUNDRY/

JANITOR
108

RESTROOM/
SHOWER
109

RESTROOM/
SHOWER
110

ACCESSIBLE

RESTROOM/
SHOWER
111
Revision Date
408-780-7200 Office
60 South Market Street, Suite 1250
San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked By
Scale
Job Number Submittal Date 70% SCHEMATIC DESIGN 03/10/2026 100% SD / BRIDGING DOCS 03/26/2026 This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
1/8" = 1'-0"

SANTA TERESA FIRE STATION
1330 WEST LUCHESSA AVENUEGILROY, CA 95020
GRIFFIN STRUCTURES, INC.

BUILDING SECTIONS
A3.11
33236

MG / TP

KEYNOTES
LEGEND

GENERAL NOTES
1/8" = 1'-0"
LONGITUDINAL SECTION A3.11 05
1/8" = 1'-0"
TRANSVERSE SECTION 02 A3.11 07
1/8" = 1'-0"
TRANSVERSE SECTION 01 A3.11 06

Page 238 of 256 ends

1. ALL CONSTRUCTION & MATERIALS SHALL BE AS SPECIFIED & IN ACCORDANCE

W/ ALL APPLICABLE CODES, ORDINANCES, LAWS, PERMITS, & THE CONTRACT DOCUMENTS.

2. THE DESIGN-BUILD ENTITY (DBE) SHALL BE RESPONSIBLE FOR THE ACCURATE PLACEMENT OF ALL NEW CONSTRUCTION ON THE SITE.

3. THE DBE SHALL VERIFY ALL SITE CONDITIONS & DIMENSIONS, & EXACT LOCATIONS & ELEVATIONS OF PIPING BEFORE STARTING WORK. SHOULD A

DISCREPANCY APPEAR IN THE CONTRACT DOCUMENTS, OR BETWEEN THE

CONTRACT DOCUMENTS & EXG CONDITIONS, NOTIFY THE ARCHITECT AT ONCE FOR INSTRUCTION ON HOW TO PROCEED.

4. THE DBE SHALL ACQUIRE & PAY FOR ALL PERMITS & FEES.

5. COORDINATE MECHANICAL WORK W / ALL OTHER TRADES (ELECTRICAL, ARCHITECTURAL, STRUCTURAL, CIVIL, & LANDSCAPE). REFER TO ELECTRICAL,

ARCHITECTURAL,STRUCTURAL, CIVIL, & LANDSCAPE DWGS & SPECIFICATIONS FOR DETAILS. COORDINATION SHALL OCCUR PRIOR TO FABRICATION, PURCHASE, &/OR INSTALLATION OF ALL WORK.

6. COORDINATE MECHANICAL, ELECTRICAL, PLUMBING, & FIRE PROTECTION SYSTEM ROUTING PRIOR TO INSTALLATION. DUCTWORK ROUTING TAKES PRECEDENCE OVER OTHER DISCIPLINES INCLUDING FIRE PROTECTION. DWGS ARE DIAGRAMMATIC IN NATURE. PROVIDE ALL FITTINGS, TRANSITIONS &/OR OFFSETS AS REQ FOR A COMPLETE SYSTEM.

7. PRIOR TO COMMENCING ANY WORK VERIFY ALL EQUIPMENT LOCATIONS W/ THE DBE, OTHER TRADES, ARCHITECT & STRUCTURAL ENGINEER.

8. MECHANICAL SYSTEMS SEISMIC RESTRAINTS SHALL CONFORM TO "SEISMIC RESTRAINT MANUAL: GUIDELINES FOR MECHANICAL SYSTEMS" AS PUBLISHED BY SMACNA 3RD EDITION 2008, ANSI/SMACNA 001-2008.

9. THE DBE IS RESPONSIBLE FOR THE SAFE KEEPING OF HIS OWN PROPERTY ON THE JOB SITE. OWNER ASSUMES NO RESPONSIBILITY FOR THE PROTECTION

OF PROPERTIES AGAINST, FIRE, SMOKE, THEFT, & ENVIRONMENTAL CONDITIONS.

10. MECHANICAL MATERIALS, EQUIPMENT, DUCTWORK & PIPING SHALL BE STORED IN ORDERLY PROFESSIONAL FASHION. ALL ITEMS SHALL BE COVERED & PROTECTED FROM RAIN & ALL OTHER ENVIRONMENTAL CONDITIONS.

11. VERIFY & COORDINATE THE MAINTENANCE ACCESS & CODE REQ CLEARANCES FOR ALL MECHANICAL EQUIPMENT. INSTALL ALL WORK &

COORDINATE THE W ORK OF OTHER TRADES TO MAINTAIN CODE REQ CLEARANCE & ACCESS FOR PROPER MAINTENANCE OF EQUIPMENT.

12. PROVIDE EQUIPMENT TAGS FOR ALL MECHANICAL EQUIPMENT. TAG SHALL BE MADE OF BAKELITE W/ ETCHED 1/2" HIGH LETTERS. LOCATE TAG ON EQUIPMENT NEAR MFRS NAMEPLATE.

13. PROVIDE DUCTWORK THAT CONFORMS TO THE "HVAC DUCT CONSTRUCTION STANDARDS - METAL & FLEXIBLE" AS PUBLISHED IN THE LATEST EDITION OF THE CALIFORNIA MECHANICAL CODE. ACOUSTICAL LINING SHALL CONFORM TO SMACNA 2006 EDITION (ANSI / SMACNA 006-2006) STANDARDS.

14. FLEXIBLE DUCTWORK SHALL BE USED FOR CONNECTIONS TO AIR TERMINAL

DEVICES IN CONCEALED, LOW PRESSURE, ENVIRONMENTAL AIR DUCT SYSTEMS. FLEXIBLE DUCT CONNECTIONS SHALL BE 5’-0” MAX LENGTH & SHALL

BE INSTALLED IN ACCORDANCE W/ SMACNA HVAC DUCT CONSTRUCTION STANDARDS.

15. REFRIGERANT PIPING SHALL BE SIZED & ROUTED IN ACCORDANCE W/ MFR’S REQUIREMENTS. REFRIGERANT SYSTEM SHALL INCLUDE ALL ADDITIONAL

TRAPS, VALVES, & ACCESSORIES REQ BY THE MFR FOR THE INSTALLED PIPE ROUTING. PROVIDE MIN 1” CLOSED CELL FOAM INSULATION FOR ALL REFRIGERANT PIPING, ARMACELL “ARMAFLEX” OR SIMILAR. REFER TO SPECIFICATIONS.

16. THE DBE SHALL PROVIDE ALL CONTROL W IRING IN CONDUIT.

17. THERMOSTATS SHALL BE MOUNTED 48" ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE.

18. THE DBE SHALL PROVIDE AS-BUILT DW GS. DWGS SHALL BE SUBMITTED IN AUTO CAD FORMAT. AS-BUILT DWGS SHALL BE COMPLETED & SUBMITTED TO ENGINEER/ARCHITECT PRIOR TO SUBSTANTIAL COMPLETION. ENGINEER WILL NOT PERFORM PUNCH LIST UNTIL AS-BUILT DW GS ARE RECEIVED.

19. PROVIDE COMPLETE AIR & WATER BALANCE FOR ALL MECHANICAL SYSTEMS.

BALANCING CONTRACTOR SHALL BE AN INDEPENDENT THIRD PARTY & A MEMBER OF "AABC" OR THE "NEBB". DBE SHALL PROVIDE ALL NECESSARY

BELTS SHEAVES & PULLEYS AS REQ BY THE BALANCING CONTRACTOR TO COMPLETE THE BALANCING OF THE SYSTEM.

20. DUCT SIZES INDICATED ON PLANS ARE THE "FREE" INSIDE DIMENSION OF THE DUCT. THE DBE SHALL INCREASE THE SIZE OF THE DUCT TO ACCOMMODATE ACOUSTICAL &/OR PERFORATED LINERS.

21. SEAL ALL DUCT SYSTEMS AIRTIGHT USING MASTIC &/OR LIQUID ELASTIC SEALANT. "DUCT TAPE" SHALL NOT BE USED.

22. PROVIDE VOLUME DAMPERS FOR EA SUPPLY DIFFUSER AS WELL AS FOR

RETURN & EXHAUST OPENINGS AS REQ BY THE BALANCING CONTRACTOR TO BALANCE THE SYSTEM. LOCATE DAMPER AS FAR UPSTREAM AS POSSIBLE.

FOR ALL VOLUME DAMPERS LOCATED ABOVE CEILINGS PROVIDE 12" LONG 1/2" WIDE FLUORESCENT ORANGE TAPE TO MARK DAMPER LOCATIONS.

23. PROVIDE "PETE'S PLUG" TYPE TEST WELLS BEFORE & AFTER EA PIECE OF

EQUIPMENT REQ BALANCING OR MONITORING IN THE HYDRONIC SYSTEMS

INCL BUT NOT LIMITED TO COILS, HEAT EXCHANGERS, CONTROL VALVES, TEMPERATURE & / OR PRESSURE SENSORS, ETC. PROVIDE ADDL TEST WELLS AS REQ BY THE COMMISSIONING AGENT.

24. DUCT SYSTEMS USED W/ BLOW ER TYPE EQUIPMENT WHICH ARE PORTIONS

OF HEATING COOLING, ABSORPTION, EVAPORATIVE COOLING OR OUTDOOR AIR VENTILATION SYSTEM SHALL BE SIZED IN ACCORDANCE W/ CHAPTER 17 OF THE CALIFORNIA MECHANICAL CODE.

25. AIR-MOVING SYSTEMS SUPPLYING AIR IN EXCESS OF 2000 CFM SHALL BE INTERLOCKED TO & SHUTDOWN BY AREA W IDE FIRE ALARM SYSTEM SIGNAL.

FOR BUILDINGS W/O AREA WIDE SYSTEM THE EQUIPMENT SHALL BE

EQUIPPED W/ AN AUTOMATIC SHUTOFF ACTIVATED BY SMOKE DETECTOR LOCATED IN THE MAIN SUPPLY-AIR DUCT.

26. PROVIDE TURNING VANES IN ALL 90° MITERED ELBOWS

27. DUCT SYSTEMS SHALL BE LEAK TESTED IN ACCORDANCE WITH THE REQUIREMENTS OF 2022 CALIFORNIA ENERGY CODE SECTION 120.4(g).

28. ALL MECHANICAL EQUIPMENT SHALL BE INSTALLED W / ADEQUATE CLEARANCE FOR MAINTENANCE ACCESS, PER MFR'S REQUIREMENTS.

29. REFER TO ARCHITECTURAL PLANS FOR LOCATION OF FIRE &/OR SMOKE SEPARATION W ALLS. THE DBE SHALL PROVIDE FIRE &/OR SMOKE DAMPERS FOR ALL RATED W ALLS/CEILINGS/ASSEMBLIES.
2025 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1, TITLE 24 C.C.R.
2025 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 C.C.R.; (2024 INTERNATIONAL BUILDING CODE OF THE INTERNATIONAL CODE

COUNCIL, WITH CALIFORNIA AMENDMENTS)
2025 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R.; (2023 NATIONAL ELECTRICAL CODE OF THE NATIONAL FIRE PROTECTION

ASSOCIATION, NFPA)
2025 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R.; (2024 UNIFORM MECHANICAL CODE OF THE INTERNATIONAL ASSOCIATION OF

PLUMBING AND MECHANICAL OFFICIALS, IAPMO)
2025 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R.; (2024 UNIFORM PLUMBING CODE OF THE INTERNATIONAL ASSOCIATION OF

PLUMBING AND MECHANICAL OFFICIALS, IAPMO)
2025 ENERGY CODE (CEC), PART 6, TITLE 24 C.C.R.;
2025 CALIFORNIA FIRE CODE, PART 9, TITLE 24 C.C.R.;
(2024 INTERNATIONAL FIRE CODE OF THE INTERNATIONAL CODE COUNCIL) 2025 CALIFORNIA GREEN BUILDING CODE (CAL GREEN), PART 11, TITLE 24 C.C.R. 2025 CALIFORNIA REFERENCED STANDARDS, PART 12, TITLE 24 C.C.R. 2025 TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS.

PARTIAL LIST OF APPLICABLE STANDARDS
ASHRAE 62.1 VENTILATION FOR ACCEPTABLE INDOOR AIR VERSION 2022

QUALITY
ASHRAE 55 THERMAL COMFORT FOR HUMAN OCCUPANCY VERSION 2023 ASHRAE G36 HIGH PERFORMANCE SEQUENCE OF OPERATIONS
FOR HVAC SYSTEMS VERSION 2024
2019 CALIFORNIA BUILDING CODE (FOR SFM) REFERENCED STANDARDS CH. 35 NFPA 13 AUTOMATIC SPRINKLER SYSTEMS 2025 EDITION
(CALIFORNIA AMENDED)
NFPA 14 STANDPIPE SYSTEMS 2019 EDITION
(CALIFORNIA AMENDED)
NFPA 17 DRY CHEMICAL EXTINGUISHING SYSTEMS 2025 EDITION NFPA 17A WET CHEMICAL EXTINGUISHING SYSTEMS 2024 EDITION NFPA 20 STATIONARY PUMPS 2025 EDITION
NFPA 24 PRIVATE FIRE SERVICE MAINS 2025 EDITION
(CALIFORNIA AMENDED)
NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE 2025 EDITION (CALIFORNIA AMENDED)
(NOTE: SEE UL STANDARD 1971 FOR "VISUAL
DEVICES")
NFPA 80 FIRE DOOR AND OTHER OPENING PROTECTIVES 2025 EDITION NFPA 253 CRITICAL RADIANT FLUX OF FLOOR COVERING 2023 EDITION

SYSTEMS
NFPA 2001 CLEAN AGENT FIRE EXTINGUISHING SYSTEMS 2025 EDITION (CALIFORNIA AMENDED)
BUILDING CODES: (APPLICABLE AS OF JANUARY 1, 2026)

ABBREVIATION DESCRIPTION

A AIR, AMPS

AAV AUTOMATIC AIR VENT

ABV ABOVE

AC AIR CONDITIONING

ACT ACOUSTICAL CEILING TILE

AD ACCESS DOOR

AFF ABOVE FINISH FLOOR

AFUE ANNUAL FUEL UTILIZATION EFFICIENCY

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AMB AMBIENT

APD AIR PRESSURE DROP

ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATION
AND AIR-CONDITIONING ENGINEERS, INC.

ASSY ASSEMBLY

ATM ATMOSPHERE

B BOILER

BFF BELOW FINISHED FLOOR

BHP BRAKE HORSE POWER

BEL BELOW

BOD BOTTOM OF DUCT

BOP BOTTOM OF PIPE

BTUH BRITISH THERMAL UNIT PER HOUR

BV BALL VALVE

C CONDENSATE PIPING

CA COMPRESSED AIR

CAP CAPACITY

CD CEILING DIFFUSER, CONDENSATE DRAIN

CFG CEILING FIRE DAMPER

CFM CUBIC FEET PER MINUTE

CG CEILING GRILLE

CH CHILLER

CHR CHILLED W ATER RETURNED

CHS CHILLED W ATER SUPPLY

CV CHECK VALVE

CLG CEILING, COOLING

CO CARBON MONOXIDE SENSOR
CO2 CARBON DIOXIDE SENSOR

COMB COMBINATION, COMBUSTION

COND CONDENSER, CONDENSATE

CONT CONTINUE, CONTROL

COP COEFFICIENT OF PERFORMANCE

CR CONDENSER WATER RETURN

CS CONDENSER WATER SUPPLY
Cx COMISSIONING
CxA COMISSIONING AGENT
(D) DEMOLISH

DB DRY BULB
dB DECIBEL

DDC DIRECT DIGITAL CONTROL

DIA DIAMETER

DN DOW N
Ø DIAMETER

EXIST EXISTING
(E) EXISTING

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EG EXHAUST GRILLE

ELEC ELECTRICAL

EMS ENERGY MANAGEMENT SYSTEM

EQUIV EQUIVALENT

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

EVAP EVAPORATOR, EVAPORATIVE

EWT ENTERING WATER TEMPERATURE

F FAHRENHEIT

FC FLUID COOLER

FCU FAN COIL UNIT

FD FIRE DAMPER

FLA FULL LOAD AMPS

FLR FLOOR

FLTR FILTER

FPM FEET PER MINUTE

FPS FEET PER SECOND

FSD COMBINATION FIRE SMOKE DAMPER

FT FOOT, FEET

FV FACE VELOCITY

GA GAGE

GAL GALLONS

GPM GALLONS PER MINUTE

GRD GRILLES, REGISTERS, AND DIFFUSERS

GWR GLYCOL WATER RETURN PIPING

GWS GLYCOL WATER SUPPLY PIPING

H HUMIDISTAT, HEIGHT

HD HEAD

HORIZ HORIZONTAL

HP HORSE POWER, HEAT PUMP

HTG HEATING

HVAC HEATING VENTILATION AND AIR CONDITIONING

HHR HEATING WATER RETURN

HHS HEATING WATER SUPPLY

HZ HERTZ

IAQ INDOOR AIR QUALITY

IN INCHES

IN WC INCHES WATER COLUMN

KW KILOWATT

LAT LEAVING AIR TEMPERATURE

LBS POUNDS

LRA LOCKED ROTOR AMPS

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

MAT MIXED AIR TEMPERATURE

MBH THOUSAND BRITISH THERMAL UNITS PER HOUR

MECH MECHANICAL

MERV MINIMUM EFFICIENCY REPORTING VALUE

MC MECHANICAL CONTRACTOR

MCA MINIMUM CIRCUIT AMPACITY

MOCP MAXIMUM OVER CURRENT PROTECTION

NA NOT APPLICABLE

NC NORMALLY CLOSED, NOISE CRITERIA

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

OA OUTSIDE AIR

OBD OPPOSED BLADE DAMPER

OC ON CENTER

OD OUTSIDE DIAMETER
P PUMP

PD PRESSURE DROP

POC POINT OF CONNECTION

POD POINT OF DISCONNECTION

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

RA RETURN AIR, RELIEF AIR

REF REFRIGERANT

RG RETURN GRILLE

RH RELATIVE HUMIDITY

RL REFRIGERANT LIQUID LINE

RLA RATED LOAD AMPS

RPM REVOLUTIONS PER MINUTE

RTU ROOF TOP UNIT

S SENSOR

SA SUPPLY AIR, SOUND ATTENUATOR

SAT SUPPLY AIR TEMPERATURE

SF SUPPLY FAN, SQUARE FOOT

SG SUPPLY GRILLE

SIM SIMILAR

SL REFRIGERANT SUCTION LINE

SMACNA SHEET METAL AND AIR-CONDITIONING

CONTRACTOR NATIONAL ASSOCIATION

SOO SEQUENCE OF OPERATION

ST SOUND TRAP

TD TEMPERATURE DIFFERENCE

TDH TOTAL DYNAMIC HEAD

TEMP TEMPERATURE

TG TRANSFER GRILLE

TOD TOP OF DUCT

TOP TOP OF PIPE

TOS TOP OF STEEL / STRUCTURE

TSP TOTAL STATIC PRESSURE

T'STAT THERMOSTAT

TU TERMINAL UNIT

TYP TYPICAL

UH UNIT HEATER
V VOLT

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

VEL VELOCITY

VENT VENTILATION, VENTILATOR

VFD VARIABLE FREQUENCY DRIVE

W WATT, WIDE, WATER

W/ WITH

W/O WITHOUT

WB WET BULB TEMPERATURE

WT WEIGHT

MOTORIZED DAMPER
SP
BP
SD
AF
A
T
MD

OPERABLE WINDOW

CONTACT
WC

DC OPERABLE DOOR

CONTACT
DP

DUCT SMOKE DETECTOR

TEMPERATURE TRANSMITTER

AQUASTAT

AIRFLOW MEASURING UNIT

DUCT STATIC PRESSURE

TRANSMITTER

BUILDING PRESSURE

TRANSMITTER

DIFFERENTIAL

PRESSURE

TRANSMITTER
VFD
DDC

VARIABLE FREQUENCY DRIVE

MAIN BUILDING DIRECT DIGITAL CONTROL PANEL
AUTOMATIC CONTROL VALVE, 2-WAY
AUTOMATIC CONTROL VALVE, 3-WAY
----
TYPE

TYPE DESCRIPTION

T THERMOSTAT

Z ZONE TEMPERATURE SENSOR - W/ LOCAL OVERRIDE / DISPLAY

S SPACE TEMPERATURE SENSOR- STAINLESS STEEL FLAT PLATE

R HUMIDISTAT OR HUMIDITY SENSOR

C CARBON DIOXIDE SENSOR

CO CARBON MONOXIDE SENSOR

EXAMPLE
TCR = THERMOSTAT W / CO2 & HUMIDISTAT SENSOR

GENERAL CONTROL NOTES

1. BUILDING BMS NOT ANTICIPATED FOR THE FACILITY.

2. EQUIPMENT TO BE PROVIDED WITH BACNET PROVISIONS TO ACCOMMODATE POTENTIAL FUTURE BMS INSTALLATION.

3. MOTOR STARTERS SHALL BE PROVIDED BY DBE. STARTERS SHALL BE EQ TO CERUS MODEL 'BAS'.

DEFINITION:

THERMOSTAT - FACTORY PROVIDED W/ ON-BOARD CONTROL LOGIC & LOCAL USEABILITY CONTROLS. CONNECT TO EMS FOR MONITORING ONLY.

ZONE TEMPERATURE SENSOR W/ LOCAL OVERRIDES - FIELD PROVIDED SENSOR W/ WIRING TO CENTRAL EMS W/ LOCAL USER OVERRIDE CONTROLS. MOUNT FLUSH & AT EQ HEIGHT W/ LIGHT SW ITCHES & OTHER DEVICES. SENSOR MODEL TO BE APPROVED BY THE ARCHITECT.

SPACE TEMPERATURE SENSOR W/O LOCAL OVERRIDES - FIELD PROVIDED

SENSOR W / WIRING TO CENTRAL EMS W/O LOCAL USER OVERRIDE CONTROLS EQ TO KELE ST-S. EXACT SENSOR TYPE TO MATCH ARCHITECTURAL FEATURES & TO BE APPROVED BY THE ARCHITECT.
24x10

TRANSITION - ECCENTRIC
DUCT RISE / DROP W/ 90° ELBOWS
(RECTANGULAR DUCTS)
45° ELBOW, R/D OR R/W=1.5
DUCT RISE / DROP W/ 90° ELBOWS
(ROUND AND / OR OVAL DUCT)
DUCT RISE / DROP W/ 45° ELBOWS
(RECTANGULAR DUCTS)
DUCT RISE / DROP W/ 45° ELBOWS
(ROUND AND / OR OVAL DUCTS)
90° ELBOW, R/D OR R/W=1.5

TRANSITION OR REDUCER

SOUNDLINED DUCTWORK

RECTANGULAR DUCT DN

RECTANGULAR DUCT UP

ROUND OR OVAL DUCT DN

ROUND OR OVAL DUCT UP

FLEXIBLE CONNECTION

DUCT SIZE (CLEAR INSIDE DIMENSION IN INCHES)

TRANSITION - RECTANGULAR TO ROUND

RADIUS TEE

SQUARE TEE W/ TURNING VANES

RADIUS TAP IN

BULLHEAD TEE

MITERED ELBOW WITH TURNING
VANES
90° CONICAL TAP
90° STRAIGHT TAP
45° TAP
90° TAP WITH 45° BEVEL

WYE FITTING

RETURN AIR DUCT UP AND DOWN

SUPPLY AIR DUCT UP AND DOW N

RETURN DUCT ROOF PENETRATION

SUPPLY DUCT ROOF PENETRATION

EXHAUST AIR DUCT UP AND DOWN

EXHAUST DUCT ROOF PENETRATION
WYE AND 45° ELBOW W/ REDUCER
(ROUND AND / OR OVAL DUCT)

CHILLED WATER SUPPLY PIPING

CHILLED WATER RETURN PIPING

HEATING WATER SUPPLY PIPING

HEATING WATER RETURN PIPING
CHS
CHR
HHS
HHR

CONTINUATION OF PIPING

DUCT SMOKE DETECTOR

SHUT-OFF VALVE ABOVE GRADE

MANUAL VOLUME DAMPER

SMOKE DAMPER

FIRE DAMPER

FIRE / SMOKE DAMPER

BACK DRAFT DAMPER

SYMBOL DESCRIPTION
SD

SUPPLY DIFFUSER

RETURN GRILLE

EXHAUST GRILLE

ELECTRONIC REMOTE DAMPER

MECHANICAL REMOTE DAMPER

RDCL REMOTE DAMPER CONTROL LOCATION

POINT OF CONNECTION

POINT OF DISCONNECTION

REFRIGERANT PIPING REF

CONTINUATION OF DUCT
(NOT TO SCALE)
1 M7.01

DOOR LOUVER

TRANSOM LOUVER

UNDERCUT DOOR

SUPPLY AIR FLOW DIRECTION

OUTSIDE AIR FLOW DIRECTION

EXHAUST AIR FLOW DIRECTION

RETURN AIR FLOW DIRECTION

KEYNOTE SYMBOL

EQUIPMENT TAG SYMBOL

DETAIL NUMBER

SHEET NUMBER

DIFFUSER IDENTIFICATION, NECK SIZE

AIR FLOW, NUMBER OF OCCURRENCES
D/L
T/L
U/C
EA
OA
?
?
RA
SA
S-1: 12"
200
TYP.3
(NOT TO SCALE)

1. ALL EQUIPMENT, PIPING, UTILITIES, & THEIR CONNECTIONS SHALL BE

SEISMICALLY BRACED PER LATEST CBC & LATEST EDITION OF SMACNA SEISMIC RESTRAINT MANUAL, BASED ON SEISMIC HAZARD LEVEL A. MAINTAIN A COPY OF SMACNA SEISMIC RESTRAINT MANUAL ON SITE.

2. LIMITS TO NON-STRUCTURAL ITEMS SUSPENDED FROM CONCRETE FILLED METAL DECKING: HANGERS SUPPORTED BY METAL DECKING W/ STRUCTURAL

CONCRETE FILL MAY BE INSTALLED USING ICC-ES APPROVED ANCHORAGE SYSTEMS. DO NOT SUPPORT UTILITIES FROM METAL DECK W/O CONCRETE.

HANGERS FROM CONCRETE FILLED DECK, WHERE OCCURS, ARE LIMITED TO 4" DIA PIPE MAX. LOCATE HANGERS TW O FLUTES APART ON SAME DECK SPAN.

SUPPORT LARGER PIPING FROM STRUCTURAL BEAMS OR COLUMNS. ADD DOUBLE UNISTRUT SPREADERS AS NECESSARY.

3. PROVIDE SHOP DWG W/ LARGE SCALE PLANS & SECTIONS SHOWING HANGERS & BRACING LOCATIONS. SHOP DWG SHALL BE PREPARED BY A

STRUCTURAL ENGINEER LICENSED IN THE STATE OF CALIFORNIA & SHALL BE STAMPED & SIGNED. INDICATE HANGERS & BRACING LOADS ON STRUCTURAL FRAMING PLANS. REFERENCE RELEVANT DETAILS FROM SMACNA SEISMIC RESTRAINT MANUAL.

4. EXPANSION ANCHORS & EPOXY ANCHORS, WHERE USED, SHALL HAVE A MIN EMBEDMENT OF 8 TIMES THE ANCHOR DIA & A MIN EDGE DISTANCE OF 10 TIMES THE DIA. EXPANSION ANCHORS & EPOXY ANCHORS MUST HAVE CURRENT & VALID ICC REPORT. SHOT PINS ARE NOT ACCEPTABLE.

5. UNLESS SPECIFIED ON STRUCTURAL DWG, ANY ALTERATIONS OR

MODIFICATIONS TO A STRUCTURAL ELEMENT BY CUTTING, DRILLING, BORING,

BRACING, WELDING, ETC SHALL HAVE WRITTEN APPROVAL BY THE STRUCTURAL ENGINEER OF RECORD & DSA PRIOR TO STARTING WORK.

6. SEE GENERAL NOTES ON STRUCTURAL DWG FOR ADDL REQUIREMENTS.

5.201.1

5.504.3

5.504.5.3

5.504.5.3.1

5.410.3

5.410.4.3.1

5.410.4.4

5.410.4

5.410.4.5

5.504.4.1

5.506.1

5.506.2
702.1
702.2
703.1

COMPLY W/ REQ OF CALIFORNIA ENERGY CODE (CCR
TITLE-24, PART 6, 2022)

PERFORM TESTING & ADJ PROCEDURES IN

ACCORDANCE W/ INDUSTRY BEST PRACTICES &
APPLICABLE NATIONAL STANDARDS ON EA SYSTEM.

TESTING & ADJUSTING OF SYSTEMS SHALL BE REQ
FOR BUILDINGS LESS THAN 10,000 SQ FT OR NEW SYSTEMS
TO SERVE AN ADDITION OR ALTERATION.

BEFORE A NEW SPACE-CONDITIONING SYSTEM SERVING A

BUILDING OR SPACE IS OPERATED FOR NORMAL USE, THE

SYSTEM SHALL BE BALANCED IN ACCORDANCE W/ THE

PROCEDURES DEFINED BY THE TESTING, ADJUSTING, AND
BALANCING BUREAU NATIONAL STANDARDS; THE NATIONAL

ENVIRONMENTAL BALANCING BUREAU PROCEDURAL
STANDARDS; OR ASSOCIATED AIR BALANCE COUNCIL
NATIONAL STANDARDS.

AFTER COMPLETION OF TESTING, ADJUSTING &

BALANCING, PROVIDE A FINAL REPORT OF TESTING SIGNED

BY THE INDIVIDUAL RESPONSIBLE FOR PERFORMING THESE
SERVICES.

BUILDING OWNER SHALL BE PROVIDED W/ DETAILED

OPERATING & MAINTENANCE INSTRUCTIONS & COPIES OF

GUARANTEES & WARRANTIES FOR EA SYSTEM PRIOR TO
FINAL INSPECTION.

ADHESIVES, ADHESIVE BONDING PRIMERS, ADHESIVE

PRIMERS, SEALANTS, SEALANT PRIMERS & CAULKS SHALL

COMPLY W/ LOCAL OR REGIONAL AIR POLLUTION

CONTROL OR AIR QUALITY MANAGEMENT DISTRICT RULES
WHERE APPLICABLE OR SCAQMD RULE 1168 VOC LIMITS, AS
SHOW N IN TABLES 5.504.4.1 & 5.504.4.2.

AEROSOL ADHESIVES & SMALLER UNIT SIZES OF

ADHESIVES AND SEALANT OR CAULKING COMPOUNDS (IN

UNITS OF PRODUCT, LESS PACKAGING, WHICH DO NOT

WEIGH MORE THAN ONE LB & DO NOT CONSIST OF MORE
THAN 16 FLUID OZ) SHALL COMPLY WITH STATEWIDE VOC

STANDARDS & OTHER REQ, INCL PROHIBITIONS ON USE OF

CERTAIN TOXIC COMPOUNDS, OF CALIFORNIA CODE OF
REGULATIONS, TITLE 17, COMMENCING W / SECTION 94507.

AT THE TIME OF ROUGH INSTALLATION & DURING STORAGE

ON THE CONSTRUCTION SITE UNTIL FINAL STARTUP OF THE

HEATING, COOLING, & VENTILATION EQUIPMENT, ALL DUCT
& OTHER AIR DISTRIBUTION COMPONENT OPENINGS SHALL

BE COVERED W / TAPE, PLASTIC, SHEETMETAL, OR OTHER

METHODS ACCEPTABLE TO THE ENFORCING AGENCY TO

REDUCE THE AMOUNT OF DUST, W ATER, & DEBRIS WHICH
MAY ENTER THE SYSTEM.

IN MECHANICALLY VENTILATED BUILDINGS, PROVIDE

REGULARLY OCCUPIED AREAS OF THE BUILDINGS W / AIR

FILTRATION MEDIA FOR OUTSIDE & RETURN AIR THAT
PROVIDES AT LEAST A MERV 13. MERV 13 FILTERS SHALL BE

INSTALLED PRIOR TO OCCUPANCY & RECOMMENDATIONS

FOR MAINTENANCE W/ FILTERS OF THE SAME VALUE SHALL
BE INCLUDED IN THE M&O MANUAL.

INSTALLED FILTERS SHALL BE CLEARLY LABELED BY THE
MANUFACTURER INDICATING THE MERV RATING.

FOR MECHANICALLY OR NATURALLY VENTILATED SPACES
IN BUILDINGS, MEET THE MIN REQ OF SECTION 120.1 OF THE
CALIFORNIA ENERGY CODE, CCR TITLE 24, PART 6 &
CHAPTER 4 OF CCR, TITLE 8 OR THE APPLICABLE LOCAL
CODE WHICHEVER IS MORE STRINGENT.

FOR BUILDINGS EQUIPPED W/ DEMAND CONTROL
VENTILATION, CO2 SENSORS & VENTILATION CONTROLS

SHALL BE SPECIFIED & INSTALLED IN ACCORDANCE W/

THE REQ OF THE LATEST EDITION OF THE CALIFORNIA
ENERGY CODE, CCR, TITLE 24, PART 6, SECTION 120.1(c).1.

HVAC SYSTEM INSTALLERS SHALL BE TRAINED &

CERTIFIED IN THE PROPER INSTALLATION OF HVAC

SYSTEMS INCL DUCTS & EQUIPMENT BY A NATIONALLY OR

REGIONALLY RECOGNIZED TRAINING OR CERTIFICATION
PROGRAM. UNCERTIFIED PERSONS MAY PERFORM HVAC

INSTALLATIONS WHEN UNDER THE DIRECT SUPERVISION &

RESPONSIBILITY OF A PERSON TRAINED & CERTIFIED TO

INSTALL HVAC SYSTEMS OR CONTRACTOR LICENSED TO
INSTALL HVAC SYSTEMS. ACCEPTABLE HVAC TRAINING &

CERTIFICATION PROGRAMS INCLUDE BUT ARE NOT LIMITED
TO THE FOLLOWING: 1) STATE CERTIFIED APPRENTICESHIP
PROGRAMS, 2) PUBLIC UTILITY TRAINING PROGRAMS, 3)

TRAINING PROGRAMS SPONSORED BY TRADE, LABOR, OR

STATEWIDE ENERGY CONSULTING OR VERIFICATION
ORGANIZATIONS, 4) PROGRAMS SPONSORED BY MFR
ORGANIZATIONS, 5) OTHER PROGRAMS ACCEPTABLE TO
THE ENFORCING AGENCY.

SPECIAL INSPECTORS MUST BE QUALIFIED & ABLE TO

DEMONSTRATE COMPETENCE IN THE DISCIPLINE THEY ARE
INSPECTING.

THE BUILDING OWNER SHALL BE PROVIDED W/ THE FINAL

REPORT OF ALL INSPECTION VERIFICATIONS & REPORTS
REQ BY THE ENFORCING AGENCY.

ANY APPLIANCE FOR WHICH THERE IS A CALIFORNIA

STANDARD ESTABLISHED IN THE APPLIANCE EFFICIENCY

REGULATIONS SHALL COMPLY WITH THE APPLIANCE
STANDARD.

COVERED PROCESS

REFRIGERATED WAREHOUSES, COMMERCIAL

REFRIGERATION, ENCLOSED PARKING GARAGES, PROCESS

BOILERS, AND COMPRESSED AIR SYSTEMS SHALL MEET THE
REQUIREMENTS WITHIN THIS SECTION.

BUILDING COMMISSIONING

PROCEDURES, REVIEWS, AND REPORTS SHALL BE FOLLOWED
AS DESCRIBED WITHIN THIS SECTION.

EQUIPMENT EFFICIENCY

HEATING AND COOLING EQUIPMENT EFFICIENCY

ANY SPACE-CONDITIONING EQUIPMENT SHALL BE INSTALLED

ONLY IF THE MANUFACTURER HAS CERTIFIED THAT THE

EQUIPMENT COMPLIES WITH ALL THE APPLICABLE

REQUIREMENTS OF THE CALIFORNIA BUILDING ENERGY
EFFICIENCY STANDARDS.

PIPE INSULATION

ALL HVAC PIPING CONVEYING LIQUIDS OR LOCATED WITHIN

HVAC EQUIPMENT SHALL BE INSULATED IN ACCORDANCE
WITHIN THIS SECTION.

WATER HEATER CERTIFICATION

ANY SERVICE WATER-HEATING SYSTEM OR EQUIPMENT MAY

BE INSTALLED ONLY IF THE MANUFACTURER HAS CERTIFIED

THAT THE SYSTEM OR EQUIPMENT COMPLIES WITH ALL OF

THE REQUIREMENTS OF THE CALIFORNIA BUILDING ENERGY
EFFICIENCY STANDARDS.

SERVICE W ATER HEATING INSTALLATION

ON SYSTEMS THAT HAVE A TOTAL CAPACITY GREATER THAN
167,000 BTU/HR. OUTLETS THAT REQUIRE HIGHER SERVICE

WATER TEMPERATURES SHALL HAVE SEPARATE REMOTE
HEATERS, HEAT EXCHANGERS, OR BOOSTERS. CIRCULATING

SERVICE W ATER-HEATING SYSTEMS SHALL HAVE A CONTROL

CAPABLE OF AUTOMATICALLY TURNING OFF THE
CIRCULATING PUMP WHEN HOT WATER IS NOT REQUIRED.

CONTROLS SHALL LIMIT THE OUTLET TEMPERATURE TO 110°F
FOR PUBLIC LAVATORIES.

POOL AND SPA EFFICIENCY AND CONTROL

A READILY ACCESSIBLE ON-OFF SWITCH, MOUNTED ON THE

OUTSIDE OF THE HEATER THAT ALLOWS SHUTTING OFF THE
HEATER W ITHOUT ADJUSTING THE THERMOSTAT SETTING; A

PERMANENT, EASILY READABLE, AND WEATHERPROOF PLATE

OR CARD THAT GIVES INSTRUCTION FOR THE ENERGY

EFFICIENT OPERATION OF THE POOL OR SPA AND FOR THE

PROPER CARE OF POOL OR SPA WATER WHEN A COVER IS
USED. NO ELECTRIC RESISTANCE HEATING.

POOL AND SPA INSTALLATION

ANY POOL OR SPA HEATING SYSTEM OR EQUIPMENT SHALL
BE INSTALLED WITH ALL OF THE FOLLOW ING: AT LEAST 36

INCHES OF PIPE BETWEEN THE FILTER AND THE HEATER TO

ALLOW FOR THE FUTURE ADDITION OF SOLAR HEATING
EQUIPMENT; A COVER FOR OUTDOOR POOLS OR OUTDOOR
SPAS; THE POOL SHALL HAVE DIRECTIONAL INLETS THAT
ADEQUATELY MIX THE POOL WATER; THE CIRCULATION PUMP

SHALL HAVE A TIME SWITCH THAT ALLOWS THE PUMP TO BE
SET TO RUN IN THE OFF-PEAK ELECTRIC DEMAND PERIOD.

POOL HEATERS SHALL NOT HAVE A PILOT LIGHT.

SPA HEATERS SHALL NOT HAVE A PILOT LIGHT.

GENERAL

WATER-SIDE SYSTEMS

SERVICE HOT WATER SYSTEMS
110.1
120.6
120.8
110.2(d)
120.1(c.2)
120.1(d.1)
120.1(d.2)
120.1(d.3)
120.2(e.1)
120.2(e.2)
120.2(f)
120.2(g)
120.2(i)
120.4
110.2(a)
120.3
110.3(a)
110.3(b)
110.3(c)
110.4(a)
110.4(b)
110.5(c)
110.5(d)

AIR-SIDE SYSTEMS

HEATING AND COOLING EQUIPMENT EFFICIENCY

ANY SPACE-CONDITIONING EQUIPMENT SHALL BE INSTALLED

ONLY IF THE MANUFACTURER HAS CERTIFIED THAT THE

EQUIPMENT COMPLIES WITH ALL THE APPLICABLE

REQUIREMENTS OF THE CALIFORNIA BUILDING ENERGY
EFFICIENCY STANDARDS.

HEAT PUMP CONTROLS

HEAT PUMPS WITH SUPPLEMENTARY ELECTRIC RESISTANCE
HEATERS SHALL HAVE CONTROLS: 1. THAT PREVENT

SUPPLEMENTARY HEATER OPERATION WHEN THE HEATING
LOAD CAN BE MET BY THE HEAT PUMP ALONE; AND 2. IN

WHICH THE CUT-ON TEMPERATURE FOR COMPRESSION

HEATING IS HIGHER THAN THE CUT-ON TEMPERATURE FOR

SUPPLEMENTARY HEATING, AND THE CUT-OFF

TEMPERATURE FOR COMPRESSION HEATING IS HIGHER THAN

THE CUT-OFF TEMPERATURE FOR SUPPLEMENTARY
HEATING.

THERMOSTATS

ALL UNITARY HEATING OR COOLING SYSTEMS, INCLUDING

HEAT PUMPS, NOT CONTROLLED BY A CENTRAL ENERGY

MANAGEMENT SYSTEM SHALL HAVE A SETBACK
THERMOSTAT.

FURNACE CONTROLS

GAS-FIRED AND OIL-FIRED FORCED AIR FURNACES WITH
INPUT RATINGS 225,000 BTU/H SHALL NOT HAVE A PILOT

LIGHT, AND SHALL HAVE EITHER POWER VENTING OR A FLUE
DAMPER.

NATURAL VENTILATION

NATURALLY VENTILATED SPACES SHALL BE PERMANENTLY
OPEN TO AND WITHIN 20 FEET OF OPERABLE WALL OR ROOF
OPENINGS TO THE OUTDOORS; THE OPENABLE AREA OF
WHICH IS NOT LESS THAN 5% OF THE CONDITIONED FLOOR
AREA OF THE NATURALLY VENTILATED SPACE. WHERE

OPENINGS ARE COVERED WITH LOUVERS OR OTHERWISE

OBSTRUCTED, OPENABLE AREA SHALL BE BASED ON THE
FREE UNOBSTRUCTED AREA THROUGH THE OPENING. THE

MEANS TO OPEN REQUIRED OPERABLE OPENINGS SHALL BE

READILY ACCESSIBLE TO BUILDING OCCUPANTS WHENEVER
THE SPACE IS OCCUPIED.

MINIMUM VENTILATION

EACH SPACE THAT IS NOT NATURALLY VENTILATED SHALL BE

VENTILATED WITH A MECHANICAL SYSTEM CAPABLE OF

PROVIDING AN OUTDOOR AIR RATE NO LESS THAN AS

REQUIRED BY THE CALIFORNIA ENERGY EFFICIENCY
STANDARDS.

PRE-OCCUPANCY VENTILATION PURGE

THE MINIMUM RATE OF OUTDOOR AIR OR THREE COMPLETE

AIR CHANGES SHALL BE SUPPLIED TO THE ENTIRE BUILDING

DURING THE ONE-HOUR PERIOD IMMEDIATELY BEFORE THE
BUILDING IS NORMALLY OCCUPIED.

DEMAND CONTROL VENTILATION

HVAC SINGLE ZONE SYSTEMS WITH AN OUTDOOR AIR

ECONOMIZER AND WITH A DESIGN OCCUPANT DENSITY, OR A

MAXIMUM OCCUPANT LOAD FACTOR FOR EGRESS PURPOSES
GREATER THAN OR EQUAL TO 25 PEOPLE PER 1000 SF SHALL

HAVE DEMAND CONTROL VENTILATION OR OCCUPANT
SENSOR VENTILATION CONTROLS.

TIME CONTROL

EACH SPACE-CONDITIONING SYSTEM SHALL BE INSTALLED

WITH CONTROLS THAT ARE CAPABLE OF AUTOMATICALLY

SHUTTING OFF THE SYSTEM DURING PERIODS OF NON-USE

AND SHALL HAVE EITHER AN AUTOMATIC TIME SWITCH

CONTROL DEVICE WITH AN ACCESSIBLE MANUAL OVERRIDE

THAT ALLOWS OPERATION OF THE SYSTEM FOR UP TO FOUR
HOURS; OR AN OCCUPANCY SENSOR; OR A FOUR-HOUR
TIMER THAT CAN BE MANUALLY OPERATED.

SETBACK AND SETUP CONTROL

THE CONTROL SHALL AUTOMATICALLY RESTART AND

TEMPORARILY OPERATE THE SYSTEM AS REQUIRED TO
MAINTAIN A SETBACK HEATING THERMOSTAT SETPOINT.

IF THE SYSTEM PROVIDES MECHANICAL HEATING AND A

SETUP COOLING THERMOSTAT SETPOINT IF THE SYSTEM
PROVIDES MECHANICAL COOLING.

OUTDOOR DAMPER CONTROL

OUTDOOR AIR SUPPLY AND EXHAUST EQUIPMENT SHALL BE

INSTALLED WITH DAMPERS THAT AUTOMATICALLY CLOSE
UPON FAN SHUTDOWN.

ISOLATION ZONES

EACH SPACE-CONDITIONING SYSTEM SERVING MULTIPLE

ZONES WITH A COMBINED CONDITIONED FLOOR AREA OF
MORE THAN 25,000 SQUARE FEET SHALL BE DESIGNED,
INSTALLED, AND CONTROLLED TO SERVE ISOLATION AREAS.

AUTOMATIC DEMAND SHED CONTROLS

HVAC SYSTEMS WITH DDC TO ZONE LEVEL SHALL BE

PROGRAMMED TO ALLOW CENTRALIZED DEMAND SHED FOR
NON-CRITICAL ZONES.

ECONOMIZER FAULT DETECTION AND DIAGNOSTICS (FDD)

AIR-COOLED UNITARY DIRECT-EXPANSION UNITS EQUIPPED

WITH AN ECONOMIZER AND MECHANICAL COOLING AT AHRI
CONDITIONS OF GREATER THAN OR EQUAL TO 54.0 MBH
SHALL INCLUDE A FDD SYSTEM.

DUCT INSULATION

ALL AIR DISTRIBUTION SYSTEM DUCTS AND PLENUMS SHALL

BE INSTALLED, SEALED AND INSULATED TO MEET THE
REQUIREMENTS OF THE 2022 CMC SECTIONS 601, 602, 603,
604, 605.
110.2(a)
110.2(b)
110.2(c)
120.2(h)
Revision Date
408-780-7200 Office
60 South Market Street, Suite 1250
San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked By
Scale
Job Number Submittal Date 70% SCHEMATIC DESIGN 03/10/2026 100% SD / BRIDGING DOCS 03/26/2026 This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.

As indicated

SANTA TERESA FIRE STATION
1330 W EST LUCHESSA AVENUEGILROY, CA 95020
GRIFFIN STRUCTURES, INC.

MECHANICAL LEGENDS

AND GENERAL NOTES
M0.01
33236
KN

GENERAL NOTES

APPLICABLE CODES

ABBREVIATIONS

CONTROL DIAGRAM

CONTROL SYSTEM (PLAN VIEW )

MECH LEGEND

ANNOTATION SYMBOLS

GENERAL STRUCTURAL NOTES

CALGREEN BUILDING STANDARDS

NON-RESIDENTIAL MANDATORY MEASURES
TITLE-24 MECHANICAL MANDATORY MEASURES

Page 239 of 256 ends

W D
DW
REF.

MW
CM
HOSE

STORAGE
TVTV
MIRROR
COMP
MB
TV

PRINTER

PRINTER
TV
COMP
COMP
COMP
COMP
WH

EXTRACTOR
DRYING
RACK
COMP
.

RH
.

TV
AC
TV
MB
REF.

ICE
CG
CG
CGCG
CGCG
CG CG

CGCG CG
CG
CG
CG
CG
CGCG
CGCGCG
CGCG

CGCGCG CG
CG
CG
T
CG CG
VFC-4
T
VFC-2
T
VFC-1
T
VFC-3
T
VFC-5
T
VFC-6
T
VFC-7
T
VFC-8
T
VFC-9
T
VFC-10
T
FC-1
T
FC-2
T
VFC-11
T
FC-3
1 A
2 3 4 5 6
B
C
D
E
F
7 8

TURNOUT
122
NONRATED

CORRIDOR
119
DORM
112
DORM
113
DORM
114
DORM
115
DORM
116

ACCESSIBLE

RESTROOM
131

ACCESSIBLE

RESTROOM/
SHOWER
111

DECONTAMINATION
130
FIRE
RISER
129
AIR
COMP.
127
STOR.
128
STOR.

CLOSET
118 CAPTAIN'S
OFFICE
117
MDF
123
DAY
ROOM
106
DINING
104

NON-RATED

CORRIDOR
105

NON-RATED

CORRIDOR
107

KITCHEN
103

ELECTRICAL
121

LAUNDRY/

JANITOR
108

RESTROOM/

SHOW ER
109

RESTROOM/

SHOW ER
110

APPARATUS
BAY
125
WEIGHT
ROOM
102
SHARED
OFFICE
101

MEDICAL

STORAGE
124
WORK
ROOM
126
VEF
1 VFC
2 VFC
1 VFC
4 VFC
3 VFC
5 VFC
6 VFC
7 VFC
8 VFC
9 VFC
10 FC
1 FC
2 EF
2 EF
1 EF
3 EF
4 VFC
11 FC
3 IR
1 IR
2 IR
3 IR
4 IR
5 IR
6 IH
3 IH
1 IH
2 VRF
1 M-0002

STUD WALL CONSTRUCTION
1 HOUR RATED WALL CONSTRUCTION

MASONRY WALL CONSTRUCTION

INDIRECTLY CONDITIONED SPACES
Revision Date
408-780-7200 Office
60 South Market Street, Suite 1250
San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked By
Scale
Job Number Submittal Date 70% SCHEMATIC DESIGN 03/10/2026 100% SD / BRIDGING DOCS 03/26/2026 This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
1/8" = 1'-0"

SANTA TERESA FIRE STATION
1330 W EST LUCHESSA AVENUEGILROY, CA 95020
GRIFFIN STRUCTURES, INC.

MECHANICAL ZONING
PLANS
M5.01
33236
KN
1/8" = 1'-0"
1 - FLOOR - MECHANICAL ZONING 05
LEGEND

KEYNOTES

ITEM DESCRIPTION
M-0002 MECHANICAL ZONE ANTICIPATED FOR VRF-1. UNIT TO BE MOUNTED

CLEAR OF ROOF OVERHANG

Page 240 of 256 ends

1 A
2 3 4 5 6
B
C
D
E
F
7 8

ROOFTOP

MECHANICAL

EQUIPMENT ZONE

ROOFTOP

MECHANICAL

EQUIPMENT ZONE
M-0001
M-0001

STUD WALL CONSTRUCTION
1 HOUR RATED WALL CONSTRUCTION

MASONRY WALL CONSTRUCTION

INDIRECTLY CONDITIONED SPACES
Revision Date
408-780-7200 Office
60 South Market Street, Suite 1250
San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked By
Scale
Job Number Submittal Date 70% SCHEMATIC DESIGN 03/10/2026 100% SD / BRIDGING DOCS 03/26/2026 This document and all other project documents, ideas,
aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the
project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.

Project documents describe the design intent of the work and are not a representation of as-built or existing
conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions. © LPA, Inc.
1/8" = 1'-0"

SANTA TERESA FIRE STATION
1330 W EST LUCHESSA AVENUEGILROY, CA 95020
GRIFFIN STRUCTURES, INC.

MECHANICAL ZONING
PLANS
M5.02
33236
KN
1/8" = 1'-0"
LR - LOW ROOF - MECHANICAL ZONING 05
LEGEND

KEYNOTES

ITEM DESCRIPTION
M-0001 ROOF ACCESS

Page 241 of 256 ends

1. ALL CONSTRUCTION AND MATERIALS SHALL BE AS SPECIFIED AND IN ACCORDANCE WITH ALL APPLICABLE CODES, ORDINANCES, LAWS, PERMITS, AND THE CONTRACT DOCUMENTS.

2. THE DESIGN-BUILD ENTITY SHALL BE RESPONSIBLE FOR THE ACCURATE PLACEMENT OF ALL NEW CONSTRUCTION ON THE SITE.

3. THE DBE SHALL VERIFY ALL SITE CONDITIONS AND DIMENSIONS, AND EXACT LOCATIONS AND ELEVATIONS OF PIPING BEFORE STARTING WORK. SHOULD A DISCREPANCY APPEAR IN THE CONTRACT DOCUMENTS, OR BETWEEN THE CONTRACT DOCUMENTS AND EXISTING CONDITIONS, NOTIFY THE ARCHITECT AT ONCE FOR INSTRUCTION ON HOW TO PROCEED.

4. SEWER, WATER, AND STORM DRAIN SYSTEMS INDICATED IN THESE DRAWINGS SHALL EXTEND TO PLUMBING/CIVIL POINTS OF CONNECTION AT 5'-0" OUTSIDE OF THE BUILDING(S) UNLESS NOTED OTHERWISE. CONTINUATION OF THESE PIPING SYSTEMS ARE INDICATED ON THE CIVIL DRAWINGS W ITH CORRESPONDING ASSOCIATED MATERIALS SPECIFIED UNDER A SEPARATE SECTION OF THE PROJECT SPECIFICATIONS. ALL SUCH PIPING SHALL BE INSTALLED IN A MANNER TO PROVIDE PROPER CONNECTION TO INVERT ELEVATIONS INDICATED ON CIVIL DRAWINGS. WHERE SIZES DIFFER BETWEEN PLUMBING AND CIVIL DRAWINGS, DBE SHALL PROVIDE TRANSITION FITTINGS AS NECESSARY TO ALLOW FOR PROPER CONNECTION.

5. TRAPS FOR ALL LAVATORIES AND SINKS SHALL TRAP STRAIGHT BACK TO WALL WITH ALL REQUIRED OFFSETS HAPPENING WITHIN THE WALL.

6. HORIZONTAL SOIL, WASTE AND TRAP PRIMER PIPING WITHIN THE BUILDING SHALL BE INSTALLED CONCEALED WITHIN WALLS, BELOW FINISH FLOOR, OR BELOW FINISH SLAB AS APPLICABLE UNLESS NOTED OTHERWISE. ALL OTHER HORIZONTAL PIPING WITHIN THE BUILDING SHALL BE INSTALLED CONCEALED

ABOVE CEILING OR WITHIN W ALLS AS APPLICABLE UNLESS NOTED OTHERWISE. ALL VERTICAL PIPING SHALL BE INSTALLED CONCEALED WITHIN WALLS UNLESS NOTED OTHERWISE. NO PIPING SHALL BE INSTALLED IN EXPOSED LOCATIONS UNLESS SPECIFICALLY NOTED AS SUCH ON PLANS.

7. HORIZONTAL SOIL AND WASTE PIPING 4" AND GREATER IN SIZE SHALL SLOPE AT 1/8" PER FOOT UNLESS OTHERWISE NOTED. ALL SUCH PIPING 3" AND LESS IN SIZE SHALL SLOPE AT 1/4" PER FOOT UNLESS NOTED OTHERW ISE.

8. HORIZONTAL STORM DRAIN AND OVERFLOW PIPING SHALL SLOPE AT 1/8" PER FOOT UNLESS NOTED OTHERWISE.

9. HORIZONTAL CONDENSATE PIPING SHALL SLOPE AT 1/8" PER FOOT UNLESS NOTED OTHERWISE.

10. PRIOR TO COMMENCING ANY WORK VERIFY ALL EQUIPMENT LOCATIONS WITH THE DBE, OTHER TRADES, ARCHITECT AND STRUCTURAL ENGINEER. EXACT ROUGH-IN LOCATIONS AND REQUIREMENTS SHALL BE COORDINATED IN THE FIELD.

11. PIPING BETWEEN EACH PLUMBING FIXTURE AND THE NEAREST BRANCH OR MAIN PIPING RUN SHALL BE SIZED TO MATCH THE CORRESPONDING FIXTURE SCHEDULE CONNECTION SIZE AT A MINIMUM UNLESS NOTED AS A LARGER SIZE ON PLANS. PIPE HEADERS IN WALLS SERVING BANKS OF FIXTURES SHALL BE FULL LINE SIZE FROM THE UPSTREAM END OF THE BRANCH LINE TO THE END TERMINAL UNLESS NOTED OTHERWISE.

12. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS, ROUGH IN

DIMENSIONS, AND MOUNTING HEIGHTS OF ALL FIXTURES, EQUIPMENT,

ACCESS PANELS, HOSE BIBBS, RECESSED HOSE BIBBS, OVERFLOW DRAIN TERMINATION POINTS, AND OTHER EXPOSED PLUMBING ELEMENTS. WHERE DIMENSIONS ARE NOT INDICATED, SEEK ARCHITECT'S DIRECTION AND/OR APPROVAL PRIOR TO INSTALLATION.

13. ACCESS PANELS
A. WHERE POSSIBLE, USE SAME ACCESS PANEL FOR SHUT-OFF VALVES, MIXING VALVES, TRAP PRIMERS AND WATER HAMMER ARRESTORS AND/OR OTHER INTERIOR WALL COMPONENTS WHEN LOCATED DIRECTLY ADJACENT IN SAME IMMEDIATE VICINITY. SEE ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHTS. B. SEE SPECIFICATIONS FOR ACCESS PANEL REQUIREMENTS. 14. CLEANOUTS.

A. INTERIOR CLEANOUTS SHALL BE WALL CLEANOUTS RATHER THAN FLOOR

CLEANOUTS UNLESS OTHERWISE INDICATED, SHALL BE READILY ACCESSIBLE,

AND SHALL BE CAREFULLY COORDINATED W ITH CASEWORK, EQUIPMENT, AND OTHER ITEMS TO AVOID CONFLICT. NOT ALL REQUIRED CLEANOUTS ARE INDICATED ON PLANS. WALL CLEANOUTS IN FINISHED SPACES SHALL BE INSTALLED IN ACCESS PANELS. B. SEE SPECIFICATIONS FOR ACCESS PANEL REQUIREMENTS. 15. YARD BOX AND CLEANOUT COVERS SHALL BE CLEARLY STAMPED WITH "WATER", "GAS", OR "SEWER" AS APPLICABLE. VALVES SHALL BE INSTALLED

AND PROPERLY POSITIONED W ITHIN YARD BOX TO ALLOW FOR FULL RANGE OF OPERATION, MAINTENANCE, REPAIR, AND REPLACEMENT. ALL YARD BOXES

AND CLEANOUT COVERS SHALL ALIGN WITH SCORED HARDSCAPE JOINTS PER LANDSCAPE PLANS. YARD BOX COVERS SHALL BE CONCRETE. SEWER CLEANOUT COVERS SHALL BE BRASS. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

16. VERIFY EXACT LOCATIONS OF ALL MECHANICAL AND/OR OTHER EQUIPMENT INSTALLED BY OTHERS AND REQUIRING PLUMBING CONNECTIONS PRIOR TO ORDERING OF MATERIALS OR INSTALLATION. COORDINATE EXACT ROUGH-IN LOCATIONS AND REQUIREMENTS WITH OTHER INSTALLING CONTRACTORS AS APPLICABLE PRIOR TO INSTALLATION.

17. ADA LAVATORIES AND SINKS SHALL BE PROVIDED WITH ADA INSULATED TRAP AND SUPPLY COVERS AS SPECIFIED.

18. ADA WATER CLOSETS SHALL BE INSTALLED WITH FLUSH VALVE ACTUATOR HANDLE LOCATED ON THE WHEEL CHAIR ACCESS SIDE.

19. ALL VALVES, UNIONS, CLEANOUTS, ETC. TO BE SAME SIZE AS PIPE UNLESS NOTED OTHERWISE.

20. REFER TO MECHANICAL DRAWINGS FOR MECHANICAL MANDATORY MEASURES AND ASSOCIATED REQUIREMENTS.

21. REFER TO ARCHITECTURAL DRAWINGS FOR LOCATIONS OF ALL FIRE RATED ASSEMBLIES. PROVIDE FIRESTOPPING AT PENETRATIONS THROUGH FIRE RETARDANT CONSTRUCTION IN ACCORDANCE WITH SPECIFICATIONS.

22. NO PIPING SHALL BE INCASED IN THE CONCRETE SLAB.23. ALL VALVES, TRAP PRIMERS, W ATER HAMMER ARRESTERS OR OTHER EQUIPMENT SHOWN IN WALLS OR ABOVE NON-ACCESSIBLE CEILINGS SHALL BE INSTALLED BEHIND AN ACCESS PANEL.

24. ALL PLUMBING FIXTURES AND EQUIPMENT SHALL BE CERTIFIED BY THE CALIFORNIA STATE ENERGY COMMISSION TO COMPLY W ITH EFFICIENCY STANDARDS PER SECTION 2-5314(A) OF THE TITLE-24 REGULATIONS.

25. PIPING THROUGH FIRE RATED WALLS SHALL BE PER U.L. FIRE RESISTANCE SYSTEM NO. W1001. SEE ARCHITECTURAL PLANS FOR WALL LOCATIONS.

26. ALL UNDERGROUND IRON, COPPER OR STEEL PIPING LOCATED BOTH INSIDE AND OUTSIDE OF BUILDING SHALL BE ENCASED WITHIN A MINIMUM 10 MIL POLYETHYLENE PLASTIC SLEEVE SEALED WATER TIGHT W ITH POLYVINYL CHLORIDE TAPE.

27. ALL POINTS OF CONNECTION SHALL BE COORDINATED WITH THE DBE PRIOR TO BID.

28. ALL HORIZONTAL PIPING LINES EXTENDED AND CONNECTED TO EQUIPMENT SHALL BE RUN AT THE HIGHEST POSSIBLE ELEVATIONS AND NOT LESS THAN 6" ABOVE THE FLOOR TO PROVIDE CLEARANCE FOR CLEANING. AT WALL OR COLUMN LOCATIONS, PIPING ROUGH-IN SHALL BE STUBBED IN WALLS WHENEVER POSSIBLE.

29. ABOVE GROUND PIPING SYSTEMS SHALL BE MARKED IN ACCORDANCE WITH ASME A13.1.

30. UNLESS SPECIFICALLY SHOWN ON THESE PLANS NO STRUCTURAL MEMBERS

SHALL BE CUT, DRILLED OR NOTCHED WITHOUT PRIOR WRITTEN
AUTHORIZATION FROM THE STRUCTURAL ENGINEER.

31. ALL CONCEALED CONDENSATE DRAIN PIPING ABOVE CEILING SHALL BE INSULATED WITH 3/4" CLOSED CELL FOAM. INSULATION SHALL BE EQUAL TO ARMACELL "ARMAFLEX".

32. VENT PIPING SHALL TERMINATE NOT LESS THAN 10 FEET FROM, OR NOT LESS THAN 3 FEET ABOVE, AN OPENABLE WINDOW, DOOR, OPENING, AIR INTAKE, OR VENT SHAFT.

33. PROVIDE DOMESTIC HOT WATER PIPING INSULATION IN ACCORDANCE WITH THE CALIFORNIA ENERGY EFFICIENCY STANDARDS.
2025 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE, PART 1, TITLE 24 C.C.R.
2025 CALIFORNIA BUILDING CODE (CBC), PART 2, TITLE 24 C.C.R.; (2021 INTERNATIONAL BUILDING CODE OF THE INTERNATIONAL CODE COUNCIL, WITH CALIFORNIA AMENDMENTS) 2025 CALIFORNIA ELECTRICAL CODE (CEC), PART 3, TITLE 24 C.C.R.; (2023 NATIONAL ELECTRICAL CODE OF THE NATIONAL FIRE PROTECTION

ASSOCIATION, NFPA)
2025 CALIFORNIA MECHANICAL CODE (CMC), PART 4, TITLE 24 C.C.R.; (2021 UNIFORM MECHANICAL CODE OF THE INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS, IAPMO) 2025 CALIFORNIA PLUMBING CODE (CPC), PART 5, TITLE 24 C.C.R.; (2021 UNIFORM PLUMBING CODE OF THE INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS, IAPMO) 2025 ENERGY CODE (CEC), PART 6, TITLE 24 C.C.R.;2025 CALIFORNIA FIRE CODE, PART 9, TITLE 24 C.C.R.; (2024 INTERNATIONAL FIRE CODE OF THE INTERNATIONAL CODE COUNCIL) 2025 CALIFORNIA GREEN BUILDING CODE (CAL GREEN), PART 11, TITLE 24 C.C.R.2025 CALIFORNIA REFERENCED STANDARDS, PART 12, TITLE 24 C.C.R.TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS.

PARTIAL LIST OF APPLICABLE STANDARDS
2025 CALIFORNIA BUILDING CODE (FOR SFM) REFERENCED STANDARDS CH. 35NFPA 13 AUTOMATIC SPRINKLER SYSTEMS 2025 EDITION (CALIFORNIA AMENDED)
NFPA 14 STANDPIPE SYSTEMS 2019 EDITION
(CALIFORNIA AMENDED)
NFPA 17 DRY CHEMICAL EXTINGUISHING SYSTEMS 2025 EDITIONNFPA 17A WET CHEMICAL EXTINGUISHING SYSTEMS 2024 EDITIONNFPA 20 STATIONARY PUMPS 2025 EDITIONNFPA 22 STANDARD FOR WATER TANKS FOR PRIVATE FIRE PROTECTION 2016 EDITION
NFPA 24 PRIVATE FIRE SERVICE MAINS 2025 EDITION
(CALIFORNIA AMENDED)
NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE 2025 EDITION (CALIFORNIA AMENDED)(NOTE: SEE UL STANDARD 1971 FOR "VISUAL DEVICES") NFPA 80 FIRE DOOR AND OTHER OPENING PROTECTIVES 2025 EDITIONNFPA 253 CRITICAL RADIANT FLUX OF FLOOR COVERING 2023 EDITION

SYSTEMS
NFPA 2001 CLEAN AGENT FIRE EXTINGUISHING SYSTEMS 2025 EDITION (CALIFORNIA AMENDED)
BUILDING CODES: (APPLICABLE AS OF JANUARY 1, 2026)
ABBREVIATION DESCRIPTION& AND@ ATABV ABOVEA/C AIR CONDITIONINGACC ACCESSIBLEADA AMERICANS W ITH DISABILITIES ACTAFF ABOVE FINISH FLOORAHJ AUTHORITY HAVING JURISDICTIONAP ACCESS PANELAPPROX APPROXIMATELYARCH ARCHITECTASD AUTOMATIC SPRINKLER DRAINASTM AMERICAN SOCIETY FOR TESTING AND MATERIALSAVTR ACID VENT THRU ROOFBEL BELOWBFF BELOW FINISHED FLOORBFG BELOW FINISHED GRADEBFP BACKFLOW PREVENTERBLDG BUILDINGBTUH BRITISH THERMAL UNIT PER HOURCA COMPRESSED AIRCBC CALIFORNIA BUILDING CODE, CURRENT EDITIONCD CONDENSATE DRAINCEC CALIFORNIA ELECTRICAL CODE, CURRENT EDITIONCFC CALIFORNIA FIRE CODE, CURRENT EDITIONCFM CUBIC FEET PER MINUTECFH CUBIC FEET PER HOURCLG CEILINGCMC CALIFORNIA MECHANICAL CODE, CURRENT EDITIONCO CLEANOUTCOMB COMBUSTIONCONT CONTINUATIONCONTR CONTRACTORCPC CALIFORNIA PLUMBING CODE, CURRENT EDITIONCVTR CONCENTRIC VENT THRU ROOFCWD CAN WASH DRAIN(D) DEMOLISHDET DETAILDEPT DEPARTMENTDIA DIAMETERDN DOW NDWG DRAWING Ø DIAMETER

E EASTEA EACHEXIST EXISTING(E) EXISTINGELEC ELECTRICALENGR ENGINEEREOR ENGINEER ON RECORDET EXPANSION TANKEXH EXHAUSTF FAHRENHEITFD FLOOR DRAINFFE FINISH FLOOR ELEVATIONFIN FLR FINISH FLOORFIN GR FINISH GRADEFLR FLOORFM FACTORY MANUALFPS FEET PER SECONDFT FOOT, FEETFV FLUSH VALVEGA GAUGEGAL GALLONSGPM GALLONS PER MINUTEGV GREASE VENTGVBF GREASE VENT BELOW FLOORGVTR GREASE VENT THRU ROOFHDR HEADERHORIZ HORIZONTALHBD HOSE BIBB DRAINAGEHP HORSE POWERHVAC HEATING VENTILATION AND AIR CONDITIONINGHZ HERTZICW INDUSTRIAL COLD WATERIE INVERT ELEVATIONIN INCHESIN WC INCHES WATER COLUMNINT INTEGRALIRR IRRIGATIONKW KILOWATTLBS POUNDSMAX MAXIMUMMBH THOUSAND BRITISH THERMAL UNITS PER HOURMC MECHANICAL CONTRACTORMECH MECHANICALMFR MANUFACTURERMIN MINIMUMN NORTHNA NOT APPLICABLENIC NOT IN CONTRACTNFPA NATIONAL FIRE PROTECTION ASSOCIATIONNO NUMBERNTS NOT TO SCALEOC ON CENTEROCD OVERFLOW CONDENSATE DRAINOD OVERFLOW DRAIN, OUTSIDE DIAMETERP PUMPPCD PUMPED CONDENSATE DRAINPH PHASEPLBG PLUMBINGPOC POINT OF CONNECTIONPOD POINT OF DISCONNECTIONPRV PRESSURE REDUCING VALVEPSI POUNDS PER SQUARE INCHRNV RADON VENTINGRO REVERSE OSMOSISRPM REVOLUTIONS PER MINUTERW RECLAIMED WATERS SOUTHSD STORM DRAINSF SQUARE FOOTSHD SHOWER DRAINSIM SIMILARSPKLR SPRINKLERSCW SOFT COLD WATERSS SERVICE SINKSST STAINLESS STEELSTD STANDARDSTRUCT STRUCTURALSYS SYSTEMTD TRENCH DRAINTEMP TEMPERATURETHRU THROUGHT'STAT THERMOSTATTP TRAP PRIMERTYP TYPICALUL UNDERW RITER'S LABORATORYUNO UNLESS NOTED OTHERWISEVA VACUUMV VOLTVBF VENT BELOW FLOORVBG VENT BELOW GRADEVTR SANITARY VENT THRU ROOFW WESTW/ WITHW/O WITHOUTWCO WALL CLEANOUTWC WATER COLUMNWT WEIGHTYB YARD BOX CS
RPBP
FSPS

SYMBOL ABBREVIATION DESCRIPTION

AV ACID VENT PIPING

WALL CLEANOUTHOSE BIBB
/

PRESSURE REDUCING VALVE

CHECK VALVE

SOV / SOC IN WALL APWCO
PRV
CV

RPBP REDUCED PRESSURE BACKFLOW PREVENTER

FCO FLOOR CLEANOUT

COTG CLEANOUT TO GRADE

FLOOR DRAIN OR AREA DRAIN
HB
UNION

SLEEVESTRAINER
PUMP

PRESSURE GAUGETEMPERATURE GAUGE

TPV TEMPERATURE AND PRESSURE RELIEF VALVE

CAP ON END OF PIPE

PIPE RISER DOWN (ELBOW)PIPE RISER UP (ELBOW)PIPE RISE OR DROPBRANCH LINE TOP CONNECTIONBRANCH LINE BOTTOM CONNECTIONFLOW IN DIRECTION OF ARROW

WATER HAMMER ARRESTOR IN WALL ACCESS PANEL

FLOW SWITCHPRESSURE SWITCHAQUASTAT

SEISMIC JOINT

TP W/ SOV TRAP PRIMER WITH SOV IN WALL ACCESS PANEL

WHA IN WALL AP

BLV BALANCING VALVE

SHUT-OFF VALVE / SHUT-OFF COCK IN WALL ACCESS PANEL

SOV SHUT-OFF VALVE ABOVE FINISHED GRADE

CONTINUATION OF PIPING

RHB RECESSED HOSE BIBB

FLOOR SINK

CONTROL STATION

DRYW ELL

OVERFLOW DRAIN (SPILL TO GRADE)ROOF RECEPTOR
P1T1

FLOOR DRAIN OR AREA DRAIN

HATCH INDICATES ITEM(S) TO BE DEMOLISHED

SOC SHUT-OFF COCK ABOVE FINISHED GRADE
AP ACCESS PANELWB WASHING MACHINE OUTLET BOX WITH 1/4 TURN VALVESIB ICE MAKER OUTLET BOX WITH 1/4 TURN VALVESV SOLENOID VALVE

GAS TURRET

SOV INCLG AP SHUT-OFF VALVE IN CEILING ACCESS PANELSOV IN YB SHUT-OFF VALVE BELOW FINISHED GRADE IN YARD BOXSOC IN YB SHUT-OFF COCK BELOW FINISHED GRADE IN YARD BOXSOC INCLG AP SHUT-OFF COCK IN CEILING ACCESS PANEL

GPR GAS PRESSURE REGULATOR

MV / TMV MIXING VALVE / THERMOSTATIC MIXING VALVE
AW ACID WASTE PIPING ABOVE FINISHED FLOORAW-U ACID WASTE PIPING UNDERGROUNDGV GREASE VENT PIPINGGW GREASE WASTE PIPING ABOVE FINISHED FLOORGW-U GREASE WASTE PIPING UNDERGROUNDV SANITARY VENT PIPINGSS SANITARY SOIL OR WASTE PIPING ABOVE FINISHED FLOORSS-U SANITARY SOIL OR WASTE PIPING UNDERGROUNDOD OVERFLOW DRAIN PIPINGSD STORM DRAIN PIPING ABOVE FINISHED FLOORSD-U STORM DRAIN PIPING UNDERGROUNDCD CONDENSATE DRAIN PIPINGOCD OVERFLOW CONDENSATE DRAIN PIPINGHBD HOSE BIBB DRAINAGE PIPINGRW RECLAIMED WATER PIPINGIRR IRRIGATION PIPINGICW INDUSTRIAL COLD WATER PIPINGRO REVERSE OSMOSIS BLENDED W ATER PIPINGCW DOMESTIC COLD WATER PIPINGHW DOMESTIC HOT WATER PIPINGHWR DOMESTIC HOT WATER RETURN PIPINGTW DOMESTIC TEMPERED WATER PIPINGTW R DOMESTIC TEMPERED WATER RETURN PIPINGSCW DOMESTIC SOFT COLD W ATER PIPINGSHWR DOMESTIC SOFT HOT WATER RETURN PIPINGSSD SUBSOIL DRAINAGE PIPINGVAC VACUUM PIPINGCA COMPRESSED AIR PIPINGG STANDARD PRESSURE GAS PIPING (8" W.C.)MPG MEDIUM PRESSURE GAS PIPING (5 PSI)MPG-U MEDIUM PRESSURE GAS PIPING UNDERGROUND (5 PSI)COMB AIR WATER HEATER COMBUSTION AIREXH. AIR WATER HEATER EXHAUST AIRCVTR WATER HEATER CONCENTRIC VENT THRU ROOF

FDFDFSGTRR
DW
OD
CS

REVISION
DETAIL

DEMOLITION KEYNOTE

PLAN IDENTIFICATION

SHEET WHERE PLAN IS DRAW N

CONTINUATION

PLAN IDENTIFICATION

SHEET WHERE PLAN IS DRAW N

ENLARGED PLAN

CLOUD AROUND REVISED AREA OPTIONAL

KEYNOTE IDENTIFICATION

OCCURANCE

SPECIFIC INFORMATION

DEMOLITION KEYNOTE IDENTIFICATION

OCCURANCE

DETAIL IDENTIFICATION

SHEET W HERE DETAIL IS DRAWN

OCCURANCE

FIXTURE IDENTIFICATION

OCCURANCE

SPECIFIC INFORMATION

FIXTURE OR EQUIPMENT IDENTIFICATION
1 FOOD SERVICE SCHEDULE REFERENCE NO.

OCCURANCE

SPECIFIC INFORMATION
SEE 1
P8.01
TYP
1 P4.01
SEE 1 P2.01 FOR CONT
RD-1 3", 900 SF
TYP OF 4
109 IW TO FS-1
TYP OF 2
0101 1", 150 CFH
TYP OF 3
0101
TYP OF 4

1. ALL EQUIPMENT, PIPING, UTILITIES, AND THEIR CONNECTIONS SHALL BE SEISMICALLY BRACED PER LATEST CBC AND EQUIPMENT ANCHORAGE FOR PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM BRACING NOTES PER STRUCTURAL DRAWINGS.

2. LIMITS TO NON-STRUCTURAL ITEMS SUSPENDED FROM CONCRETE FILLED METAL DECKING: HANGERS SUPPORTED BY METAL DECKING WITH STRUCTURAL CONCRETE FILL MAY BE INSTALLED USING ICC-ES APPROVED ANCHORAGE SYSTEMS. DO NOT SUPPORT UTILITIES FROM METAL DECK WITHOUT CONCRETE. HANGERS FROM CONCRETE FILLED DECK, WHERE OCCURS, ARE LIMITED TO 4-INCH DIAMETER PIPE MAXIMUM. LOCATE HANGERS TW O FLUTES APART ON SAME DECK SPAN. SUPPORT LARGER PIPING FROM STRUCTURAL BEAMS OR COLUMNS. ADD DOUBLE UNISTRUT SPREADERS AS NECESSARY.

3. PROVIDE SHOP DRAWINGS WITH LARGE SCALE PLANS AND SECTIONS SHOW ING HANGERS AND BRACING LOCATIONS. SHOP DRAWINGS SHALL BE PREPARED BY A STRUCTURAL ENGINEER LICENSED IN THE STATE OF CALIFORNIA AND SHALL BE STAMPED AND SIGNED. INDICATE HANGERS AND BRACING LOADS ON STRUCTURAL FRAMING PLANS.

4. EXPANSION ANCHORS AND EPOXY ANCHORS, WHERE USED, SHALL HAVE A MINIMUM EMBEDMENT OF EIGHT TIMES THE ANCHOR DIAMETER AND A MINIMUM EDGE DISTANCE OF 10 TIMES THE DIAMETER. EXPANSION ANCHORS AND EPOXY ANCHORS MUST HAVE CURRENT AND VALID ICC REPORT. SHOT PINS ARE NOT ACCEPTABLE.

5. UNLESS SPECIFIED ON STRUCTURAL DRAWINGS, ANY ALTERATIONS OR MODIFICATIONS TO A STRUCTURAL ELEMENT BY CUTTING, DRILLING, BORING, BRACING, WELDING, ETC. SHALL HAVE WRITTEN APPROVAL BY THE STRUCTURAL ENGINEER OF RECORD PRIOR TO STARTING WORK.

6. REFER TO ARCHITECTURAL AND STRUCTURAL DRAW INGS FOR LOCATIONS OF BUILDING SEISMIC/EXPANSION JOINTS. PROVIDE SEISMIC/EXPANSION JOINTS FOR ALL PIPES CROSSING THESE LOCATIONS.

7. SEE GENERAL NOTES ON STRUCTURAL DRAWINGS FOR ADDITIONAL REQUIREMENTS.

Revision Date
408-780-7200 Office 60 South Market Street, Suite 1250 San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked ByScaleJob Number
Submittal Date
70% SCHEMATIC DESIGN 03/10/2026
100% SD / BRIDGING DOCS 03/26/2026
This document and all other project documents, ideas, aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.Project documents describe the design intent of the work and are not a representation of as-built or existing conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions.© LPA, Inc.

SANTA TERESA FIRE STATION
1330 W EST LUCHESSA AVENUE
GILROY, CA 95020
GRIFFIN STRUCTURES, INC.

PLUMBING LEGENDS

AND GENERAL NOTES
P0.10
33236Checker

GENERAL NOTES

APPLICABLE CODES

PLUMB ANNOTATION SYMBOLS PLUMBING LEGEND GENERAL STRUCTURAL NOTES ABBREVIATIONS

Page 242 of 256 ends

NO

PARKING

EV CHARGING ONLY
EV

CHARGING
ONLY
NO

PARKING
AC
MILLER AVE.

W LUCHESSA AVE.

PROPOSED NEW BUILDING FIRE STATION
COTG
4" SS-UI.E = -3' - 6" BFF
4" SD-UI.E = -2' - 5" BFF
4" SS-UI.E = -3' - 6" BFF
4" SD-UI.E = -2' - 6" BFF
4" SS-UI.E = -3' - 6" BFF
4" FI.E = -3' - 6" BFF
2" CWI.E = -3' - 0" BFF
4" SD-UI.E = -2' - 6" BFF
4" SD-UI.E = -2' - 6" BFF
4" SD-U
I.E = -2' - 6" BFF
4" SD-U
I.E = -2' - 6" BFF
4" SD-U
I.E = -2' - 6" BFF
4" SD-U
I.E = -2' - 6" BFF
4" SD-U
I.E = -2' - 6" BFF
4" SD-U
I.E = -2' - 6" BFF
4" SD-U
I.E = -2' - 6" BFF
4" SD-U
I.E = -2' - 6" BFF
4" SD-U
I.E = -2' - 6" BFF
OI-1
COTG
P-0001
P-0001
P-0001
P-0001
P-0001
P-0001
P-0001
P-0001
P-0001
P-0001
P-0001
P-0001
P-0001
P-0001
P-0001
P-0001
P-0001
FFE = 303.45
4" SS-UI.E = -3' - 6" BFF
P-0001
3/4" CWI.E = -3' - 0" BFF
P-0001
ETP-4 FD-1

GENERAL NOTES
LEGEND

1. REFER TO THE GENERAL NOTES SECTION OF SHEET P0.10 FOR OVERALL GENERAL NOTES REGARDING THIS PROJECT.

2. ALL PLUMBING WORK SHALL BE INSTALLED SO AS TO AVOID INTERFERENCE WITH ELECTRICAL AND MECHANICAL EQUIPMENT AND STRUCTURAL FRAMING.

3. THE CONTRACTOR SHALL COORDINATE PLACEMENT OF ALL UNDERGROUND PIPING WITH THE STRUCTURAL ENGINEER PRIOR TO CONSTRUCTION.

4. REFER TO CIVIL SITE PLANS FOR CONTINUATION OF ALL PLUMBING SYSTEM POINTS OF CONNECTION NOTED ON THIS SHEET.

5. ALL POINTS OF CONNECTION SHALL BE COORDINATED WITH THE GENERAL CONTRACTOR PRIOR TO BID.

LIMIT OF WORK (L.O.W .)APPROXIMATE ROADWAY CENTERLINEPROPERTY LINE PLAN
INSTALL DRIVE LINE WITH 90° BEND TO ENABLE DISCONNECTION AT VALVE.

ALL W ASHDOWN POINTS MUST
COME FROM THIS POINT. NON WASHDOW N POINTS SHOULD BE FROM BEFORE DEMAND VALVE. COLD WATER SUPPLY. MIN 100kPa OTHERS MUST BE PROTECTED BY RPZ. (SUPPLIED ON REQUEST)
DRIVE LINE (BY OTHERS) 1/2"ØD COPPER TUBE

FOX DEMAND VALVEMEDIUM DUTY GRATE
SPECIFICATIONSCHAMBER 0.25" MDPEDIVERSION VALVE FLOW RATE 317 GALLONS/MIN @ 1' 7.7" HEAD
MAXIMUM INLET PRESSURE 1400kPaSTONE BASKET 0.4" HOLES GALVANIZEDGRATE MEDIUM DUTY GALVANIZED SCHEMATIC DETAIL OF DD400 SYSTEM

ELEVATION

FOX DIVERSION VALVE
4"Ø OUTLET TO

SANITARY WASTE
4"Ø OUTLET TO STORM W ATER

BUNDED WASH AREA
(USUALLY LESS THAT 32' 10" ²)
Revision Date
408-780-7200 Office 60 South Market Street, Suite 1250 San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked ByScaleJob Number
Submittal Date
70% SCHEMATIC DESIGN 03/10/2026
100% SD / BRIDGING DOCS 03/26/2026
This document and all other project documents, ideas, aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.Project documents describe the design intent of the work and are not a representation of as-built or existing conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions.© LPA, Inc.

SANTA TERESA FIRE STATION
1330 W EST LUCHESSA AVENUE
GILROY, CA 95020
GRIFFIN STRUCTURES, INC.

PLUMBING SITE PLANS
P1.00
33236Checker

PROJECT NORTH N
1" = 20'-0"
PLUMBING SITE PLAN 05

KEYNOTES

ITEM DESCRIPTION
P-0001 POINT OF CONNECTION. SEE CIVIL PLAN FOR CONTINUATION.

NTS 22 CAN W ASH DETAIL (FOX DRAIN DD400)NTS
Fox Drain Detail 23

Page 243 of 256 ends

W
D
DW
REF.

MW
CM
HOSE

STORAGE
TVTV
MIRROR
MB
TV
TV
WH

EXTRACTOR
DRYING
RACK .

RH .

TV
AC
TV
MB
REF.

ICE
1 A
2 3 4 5 6
B
CD
E
F
7 8

TURNOUT
122

NON- RATED

CORRIDOR
119
DORM
112
DORM
113
DORM
114
DORM
115
DORM
116

ACCESSIBLE

RESTROOM
131

ACCESSIBLE

RESTROOM/
SHOWER
111

DECONTAMINATION
130
FIRE
RISER
129
AIR
COMP.
127
STOR.
128
STOR.

CLOSET
CAPTAIN'S 118
OFFICE
117
MDF
123
DAY
ROOM
106
DINING
104

NON-RATED

CORRIDOR
105

NON-RATED

CORRIDOR
107

KITCHEN
103

ELECTRICAL
121

LAUNDRY/

JANITOR
108

RESTROOM/

SHOW ER
109

RESTROOM/

SHOW ER
110

APPARATUS
BAY
125
WEIGHT
ROOM
102
SHARED
OFFICE
101

MEDICAL

STORAGE
124
WORK
ROOM
126
P4.01
07 P4.01
11 P4.01
13 P4.01
05 S-1
BF-1
COTG
4" SS-U
4" SS-U
1 1/2" HW
1" CW
1 1/2" HW
3/4" HW R1 1/2" HW2" CW
TD-1 TD-1
ETP-2
FS-1
4" SS-U
FCO
4" SD-U
4" SS-U
4" F
2" CW
4" SD-U
4" SS-U WS-1
1/2" PD
3/4" HW R
1 1/2" HW
2" CW
RHB-1
4" SD
RHB-1
WCO
4" SD-U
P-0003
P-0004
DSB-1
DSB-1
DSB-1
DSB-1
DSB-1
DSB-1
DSB-1
DSB-1 COTG
OI-1
P-0002
P-0002
P-0002
P-0002P-0002
P-0002
P-0002
P-0002
P-0002
WCO
DSB-1
P-0002
P-0002
3/4" HW R
1 1/2" HW
2" CW
DSB-1
1/2" CA
1/2" CA
HR-1HR-1
P-0002
HB-2
P-0005
RPBF-1
3/4" CW
1/2" CA
IMB-1IMB-1
P-0002
4" OD
4" OD
4" OD
4" SD
4" SD GENERAL NOTES
LEGEND

1. REFER TO THE GENERAL NOTES SECTION OF SHEET P0.10 FOR OVERALL GENERAL NOTES REGARDING THIS PROJECT.

2. ALL PLUMBING WORK SHALL BE INSTALLED SO AS TO AVOIDE INTERFERENCE WITH ELECTRICAL AND MECHANICAL EQUIPMENT AND STRUCTURAL FRAMING.

3. THE CONTRACTOR SHALL COORDINATE PLACEMENT OF ALL UNDERGROUND PIPING WITH THE STRUCTURAL ENGINEER PRIOR TO CONSTRUCTION.

4. REFER TO CIVIL SITE PLANS FOR CONTINUATION OF ALL PLUMBING SYSTEM POINTS OF CONNECTION NOTED ON THIS SHEET.

5. ALL POINTS OF CONNECTION SHALL BE COORDINATED WITH THE GENERAL CONTRACTOR PRIOR TO BID.

6. EXACT LOCATIONS AND MOUNTING HEIGHTS OF PLUMBING FIXTURES SHALL BE OBTAINED FROM THE ARCHITECTURAL PLANS.

7. BEFORE FABRICATION OR INSTALLATION, THE CONTRACTOR SHALL VERIFY EXACT LOCATIONS OF ALL MECHANICAL EQUIPMENT AND EQUIPMENT PROVIDED UNDER ANOTHER SECTION OF SPECIFICATIONS. EXACT ROUGH-IN LOCATIONS AND REQUIREMENTS SHALL BE COORDINATED IN FIELD.

8. AL INDIRECT WASTE PIPING SHALL BE SLOPED TO AND TERMINATED AT AN APPROVED RECEPTOR.

STUD WALL CONSTRUCTION1 HOUR RATED WALL CONSTRUCTIONMASONRY WALL CONSTRUCTION Revision Date
408-780-7200 Office 60 South Market Street, Suite 1250 San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked ByScaleJob Number
Submittal Date
70% SCHEMATIC DESIGN 03/10/2026
100% SD / BRIDGING DOCS 03/26/2026
This document and all other project documents, ideas, aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.Project documents describe the design intent of the work and are not a representation of as-built or existing conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions.© LPA, Inc. 1/8" = 1'-0"

SANTA TERESA FIRE STATION
1330 W EST LUCHESSA AVENUE
GILROY, CA 95020
GRIFFIN STRUCTURES, INC.

PLUMBING FLOOR PLAN
P2.01
33236Checker
1/8" = 1'-0"
1ST FLOOR PLUMBING PLAN 05

KEYNOTES

ITEM DESCRIPTION
P-0002 PROVIDE CONDENSATE PIPING TO MECHANICAL UNIT.P-0003 PROVIDE COLD WATER CONNECTION TO COFFEE MAKER. REFER TO ARCHITECTURE FOR EXACT LOCATION.

P-0004 PROVIDE HOT WATER CONNECTION TO DISH WASHER. REFER TO ARCHITECTURE FOR EXACT LOCATION.

P-0005 FOX DRAIN FOR REFERENCE ONLY. REFER TO CIVIL PLAN FOR EXACT LOCATION.

Page 244 of 256 ends

1 A
2 3 4 5 6
B
CD
E
F
7 8
RD/OD
RD/OD
RD/OD
HB-1
HB-1 4" V
4" V
4" V
2" V

GENERAL NOTES
LEGEND

1. REFER TO THE GENERAL NOTES SECTION OF SHEET P0.10 FOR OVERALL GENERAL NOTES REGARDING THIS PROJECT.

2. STORM DRAIN ARE SIZED IN ACCORDANCE WITH THE 2025 CALIFORNIA PLUMBING CODE, TABLE 1103.2, AND IS BASED ON A RAINFALL RATE OF 4" (IN) PER HOUR.

3. RAINWATER ON SLOPED ROOF AREAS TO SHEET FLOW TO ARCHITECTURAL GUTTERS. SEE SHEET P2.01 FOR CONTINUATION.

4. EXACT LOCATIONS AND MOUNTING HEIGHTS OF PLUMBING FIXTURES SHALL BE OBTAINED FROM THE ARCHITECTURAL DRAWINGS.

5. BEFORE FABRICATION OR INSTALLATION. THE CONTRACTOR SHALL VERIFY EXACT LOCATIONS OF ALL MECHANICAL EQUIPMENT AND EQUIPMENT. PROVIDED UNDER ANOTHER SECTION OF SPECIFICATIONS. EXACT ROUGH-IN LOCATIONS AND REQUIREMENTS SHALL BE COORDINATED IN FIELD.

Revision Date
408-780-7200 Office 60 South Market Street, Suite 1250 San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked ByScaleJob Number
Submittal Date
70% SCHEMATIC DESIGN 03/10/2026
100% SD / BRIDGING DOCS 03/26/2026
This document and all other project documents, ideas, aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.Project documents describe the design intent of the work and are not a representation of as-built or existing conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions.© LPA, Inc. 1/8" = 1'-0"

SANTA TERESA FIRE STATION
1330 W EST LUCHESSA AVENUE
GILROY, CA 95020
GRIFFIN STRUCTURES, INC.

PLUMBING ROOF PLAN
P2.02
33236Checker
1/8" = 1'-0"
PLUMBING ROOF PLAN 05

KEYNOTES

ITEM DESCRIPTION

Page 245 of 256 ends

W
D
WH
CG
CGCG
CG CG
CGCG
WD
WH
CG
CGCG
CG CG
CGCG
HOSE

STORAGE

EXTRACTOR
DRYING
RACK
AC
CG
CGCG
CGCG
CG CG
HOSE

STORAGE

EXTRACTOR
DRYING
RACK
AC
CG
CGCG
CGCG
CG CG
3 D
E
EWH-1
CP-1
SS-1
L-1
L-1L-1
SH-2
TMV-1
L-1
WC-1
WHA-1 TP-1
FD-1
FD-2
WC-1 FD-2WC-1
FD-1
FD-2
TMV-1TMV-1
TP-1
WHA-1
TP-1
WHA-1
FD-1
FD-1

ACCESSIBLE

RESTROOM/
SHOWER
111

RESTROOM/

SHOW ER
109

LAUNDRY/

JANITOR
108

NON-RATED

CORRIDOR
107

TURNOUT
122

ELECTRICAL
121
ET-1
CWB-1
3 D
E
EWH-1
CP-1
SS-1
L-1
L-1L-1
SH-2
TMV-1
L-1
WC-1
WHA-1 TP-1
FD-1
FD-2
WC-1 FD-2WC-1
FD-1
FD-2
TMV-1TMV-1
TP-1
WHA-1
TP-1
WHA-1
FD-1
FD-1

RESTROOM/

SHOW ER
110

ACCESSIBLE

RESTROOM/
SHOWER
111

RESTROOM/

SHOW ER
109

LAUNDRY/

JANITOR
108

NON-RATED

CORRIDOR
107

TURNOUT
122

ELECTRICAL
121
ET-1
2" CW
1 1/2" HW
2" CW
1 1/2" HW
SH-2SH-2
RHB-1
CWB-1
C
7 8
SS-2
WCO L-1
WC-1
FD-2 SH-3
FD-1
TD-2
AC-1
ETP-1
WHA-1
TP-1
FD-1

APPARATUS
BAY
125

DECONTAMINATION
130
STOR.
128
WORK
ROOM
126
AIR
COMP.
127
FIRE
RISER
129 APPARATUS
BAY
125
TMV-1
4" SS-U
FD-1
ASW F-1
P-0006
P-0002
P-0011
C
7 8
SS-2
L-1
WC-1
SH-3
FD-2
FD-1
TD-2
AC-1
ETP-1
WHA-1
TP-1
FD-1

APPARATUS
BAY
125

DECONTAMINATION
130
STOR.
128
WORK
ROOM
126
AIR
COMP.
127
FIRE
RISER
129 APPARATUS
BAY
125
TMV-1
2" CW
1 1/2" HW
3/4" HW R
4" F
ASW F-1
FD-1
RHB-1
2" CW
1/2" CA
FS-1
P-0007
P-0008 P-0009
P-0010
HR-1HR-1
P-0011

GENERAL NOTES
LEGEND

1. REFER TO THE GENERAL NOTES SECTION OF SHEET P0.10 FOR OVERALL GENERAL NOTES REGARDING THIS PROJECT.

2. ALL PLUMBING WORK SHALL BE INSTALLED SO AS TO AVOIDE INTERFERENCE WITH ELECTRICAL AND MECHANICAL EQUIPMENT AND STRUCTURAL FRAMING.

3. THE CONTRACTOR SHALL COORDINATE PLACEMENT OF ALL UNDERGROUND PIPING WITH THE STRUCTURAL ENGINEER PRIOR TO CONSTRUCTION.

4. REFER TO CIVIL SITE PLANS FOR CONTINUATION OF ALL PLUMBING SYSTEM POINTS OF CONNECTION NOTED ON THIS SHEET.

5. ALL POINTS OF CONNECTION SHALL BE COORDINATED WITH THE GENERAL CONTRACTOR PRIOR TO BID.

6. EXACT LOCATIONS AND MOUNTING HEIGHTS OF PLUMBING FIXTURES SHALL BE OBTAINED FROM THE ARCHITECTURAL PLANS.

7. BEFORE FABRICATION OR INSTALLATION, THE CONTRACTOR SHALL VERIFY EXACT LOCATIONS OF ALL MECHANICAL EQUIPMENT AND EQUIPMENT PROVIDED UNDER ANOTHER SECTION OF SPECIFICATIONS. EXACT ROUGH-IN LOCATIONS AND REQUIREMENTS SHALL BE COORDINATED IN FIELD.

8. AL INDIRECT WASTE PIPING SHALL BE SLOPED TO AND TERMINATED AT AN APPROVED RECEPTOR.

STUD WALL CONSTRUCTION1 HOUR RATED WALL CONSTRUCTIONMASONRY WALL CONSTRUCTION Revision Date
408-780-7200 Office 60 South Market Street, Suite 1250 San Jose, California 95113

NOT FOR REGULATORY APPROVAL,

PERMITTING OR CONSTRUCTION

ARCHITECTURE ENGINEERING INTERIOR DESIGN

LANDSCAPE ARCHITECTURE PLANNING
LPADesignStudios.com
Developed for
Checked ByScaleJob Number
Submittal Date
70% SCHEMATIC DESIGN 03/10/2026
100% SD / BRIDGING DOCS 03/26/2026
This document and all other project documents, ideas, aesthetics and designs incorporated therein are instruments of service. All project documents are copyright protected, are the property of LPA, Inc. (LPA) and cannot be lawfully used in whole or in part for any project or purpose except as set forth in the contractual agreement between LPA and its Client. The unauthorized disclosure and/or use of the project documents (including the creation of derivative works), may give rise to liability for copyright infringement, unlawful disclosure, use or misappropriation of property rights held by LPA. The unauthorized use of the project documents will give rise to the recovery of monetary losses and damages including attorney fees and costs for which the unauthorized user will be held liable.Project documents describe the design intent of the work and are not a representation of as-built or existing conditions. LPA is not responsible for any discrepancies between the project documents and the existing conditions.© LPA, Inc.

As indicated

SANTA TERESA FIRE STATION
1330 W EST LUCHESSA AVENUE
GILROY, CA 95020
GRIFFIN STRUCTURES, INC.

PLUMBING ENLARGED
PLANS
P4.01
33236Checker
1/4" = 1'-0" 07 ENLARGED - DRAINAGE - RESTROOM/SHOW ER/ LAUNDRY 1/4" = 1'-0" 11 ENLARGED - W ATER - RESTROOM/SHOW ER/ LAUNDRY 1/4" = 1'-0"
ENLARGED - DRAINAGE - DECONTAMINATION/ FIRE RISER 05 1/4" = 1'-0" ENLARGED - W ATER - DECONTAMINATION/ FIRE RISER 13

KEYNOTES

ITEM DESCRIPTION
P-0002 PROVIDE CONDENSATE PIPING TO MECHANICAL UNIT.P-0006 FIRE RISER STANDPIPE DRAIN.P-0007 WATER FILTRATION BYPASS LINE WITH ISOLATION SHUT OFF VALVES.

P-0008 PRIMARY COLD WATER LINE TO WATER FILTRATION UNIT WITH ISOLATION SHUT OFF VALVES.

P-0009 PRIMARY COLD WATER SUPPLY TO WATER FILTRATION UNIT.

INSTALL PER MANUFACTURERS INSTALLATION REQUIREMENTS. P-0010 FILTERED WATER WITH VACUUM RELIEF VALVE.

P-0011 REFER TO AIR COMPRESSOR SCHEDULE ON P6.00 FOR ADDITIONAL EQUIPMENT.

Page 246 of 256 ends