Table 22.1-8. Electrical Characteristics of Circuit Breakers (Continued) Circuit Breaker Ratings UL Listed Interrupting Ratings (kA rms Symmetrical) Type Ampere
Rating
Number
of Poles
Voltage AC Rating, Volts DC Rating, Volts a
AC DC 120/240 240 277 480 600 125 250 600
High Interrupting Capacity Circuit Breakers
PDG2xM 15–150
15–225
1 2, 3
277
600
—
—
—
—
—
100
65 —
—
65 —
25 10
—
—
22 —
—
PDD2xM
PDG3xM bc, PDF3xM d
100–225
100–400
2, 3
2, 3
240
600
—
—
—
—
100
100
—
—
—
65 —
35 10
—
—
22 —
—
Current-Limiting Circuit Breakers
PDG2xP 15–225
100–225
2, 3
2, 3
600
240
—
—
—
—
200
200
—
—
100
—
35 —
—
10 22
—
—
—
PDG3xP bce 100–400
250–600
2, 3
2, 3
600
600
—
—
—
—
200
200
—
—
100
100
65 50
—
—
22 42
—
—
Current Limit-RT Circuit Breakers
FCL 15–100 2, 3 480 — — 200 — 150 — — — —
TRI-PACT Current-Limiting Circuit Breakers
FB-P 15–100 2, 3 600 — — 200 — 200 200 — f —
a DC ratings apply to substantially non-inductive circuits. b The 400 A frame must use trip units of ratings 100–400, while the 600 A frame must use trip units of ratings 500, 600 or designated by H, such as H250.
The H as the leading character of the ampacity indicates a high instantaneous version of the breaker for coordination purposes. H ratings must use 600 A frame. c Available with integral ground fault protection.
d 100k based on NEMA test procedure.
e DC rating not available with PXR trip units.
f Non-interrupting trip type.
Design Guide DG014001EN
Effective November 2024
22.1-12
Pow-R-Line 1X, 2X and 3X
Panelboards
Devices
EATON www.eaton.com Page 269 of 1066
Terminal Wire Ranges, Pressure-Type Al/Cu Terminals Except as Noted Where copper-aluminum terminals are supplied on designated panelboard types, best results are obtained if a suitable joint compound is applied when aluminum conductors are used.
Table 22.1-9. Standard Main Lug Terminals
Panel
Type
Wire Size Ranges for Ampere Capacity
100 A 225 A 250 A 400 A 600 A 800 A 1200 A
Pow-R-Line 1X, 1XF, 1RX
Pow-R-Line 2X, 2XF, 2RX
Pow-R-Line 3X
#12–1/0
#12–1/0
#12–1/0
#6–300 kcmil
#6–300 kcmil
—
—
—
#6–350 kcmil
(2) #4–500 kcmil
(2) #4–500 kcmil
(2) #4–500 kcmil
(2) #4–500 kcmil a
(2) #4–500 kcmil a
(2) #4–500 kcmil
—
—
(3) #4–500 kcmil
—
—
—
Pow-R-Command #12–1/0 #6–300 kcmil — #4–500 kcmil — — — PRCE
PRC100
PRC25
#12–1/0
#12–1/0
#12–1/0
#6–300 kcmil
—
#6–300 kcmil
—
#6–350 kcmil
—
(2) #4–500 kcmil
(2) #4–500 kcmil
(2) #4–500 kcmil
—
—
—
—
—
—
—
—
—
a Not applicable PRL 1XF, 1RX, PRL 2XF, 2RX.
Note: Optional 750 kcmil mechanical screw-type terminals are available upon request. Panelboard dimensions may be affected. Refer to Eaton.
Table 22.1-10. Standard Main Breaker and Branch Breaker Terminals Breaker Type Ampere Rating Wire Size Ranges
BAB, QBHW, BABRSP
HQP, QPHW
15–70
90–100
#14–#4
#8–1/0
PDD2xF, PDD2xG
PDD2xM, PDD2xM b
100–225 #4–4/0 or
#6–300 kcmil
EGB, EGE, EGS, EGH 15–50
60–125
#14–3/0 Al/Cu
#6–3/0 Al/Cu
PDG2xF, PDG2xG
PDG2xM, PDG2xP b, HFDDC c
15–100
125–225
#14–1/0
#4–4/0
FCL 15–100 #14–1/0
GHB, HGHB, GHQ,
GHQRSP
15–50
25–100
#14–1/0
#10–1/0
HJDDC c 70–250 #4–350 kcmil
PDD3xG 250–350
400
250–500 kcmil
(2) 3/0–250 kcmil or
(1) 3/0–500 kcmil
PDG3xG d
PDG3xM d, PDG3xP d
HKDDC c, PDF3xG b
PDF3xM b
225
350
400
(1) #3–350 kcmil
(2) 3/0–250 kcmil or
(2) 3/0–250 kcmil or
(1) 3/0–500 kcmil
LHH 150–400 #2–500 kcmil
(2) #2–500 kcmil or
(1) 500–750 kcmil
PDG3xG d, PDG3xM d,
PDG3xM d
250–400
500–600
(1) #2–500 kcmil
(2) #2–500 kcmil
b Suitable for DC applications only.
c LHH is 400 A maximum.
d The 400 A frame must use trip units of ratings 100–400, while the 600 A frame must use trip units of ratings 500, 600 or designated by H, such as H250. The H as the leading character of the ampacity indicates a high instantaneous version of the breaker for coordination purposes. H ratings must use 600 A frame.
Table 22.1-11. Fusible Switch Terminals
Ampere Rating Wire Size Ranges
30 60
100
#14–1/0
#14–1/0
#14–1/0
200 #4–300 kcmil
400 250–750 kcmil or
(2) 3/0–250 kcmil
600 (2) #4–600 kcmil or (4) 3/0–250 kcmil
Design Guide DG014001EN
Effective November 2024
22.1-13
Pow-R-Line 1X, 2X and 3X
Panelboards
Devices
EATON www.eaton.com Page 270 of 1066
Power Xpert Release
Trip Unit for Molded Case
Circuit Breakers
Description
Eaton’s Power Xpert Release (PXR) trip
units are programmable communicating
microprocessor-based low-voltage
electronic trip unit systems for Eaton
molded case circuit breakers. PXR trip
units are available in three models:
PXR 10, PXR 20 and PXR 25.
Standards and Certifications
The PXR trip units are listed by
Underwriters Laboratories (UL) and
Canadian Standards Association (CSA)
for use in Power DefenseE Frame 2, 3, 4,
5 and 6 molded case circuit breakers.
All PXR units have also passed the
IEC 60947-2 test program that includes
EMC testing. All trip units meet the
low-voltage and EMC directives and
carry the CE mark.
Features
The PXR electronic trip units provide
an enhanced and easy-to-use interface
that enables end users and maintenance
engineers to more easily change set
points, test and configure circuit breakers,
and review energy and power information.
The Power Xpert Protection Manager
(PXPM) software also provides the
capability of secondary injection tests
and reports on-demand without the
need of expensive test kits.
Advanced features include:
■ Industry-first breaker health algorithms
provide real-time monitoring and
communication of breaker condition
■ Cause of trip LED indication and trip
event data storage
■ Zone selective interlocking (ZSI)
verification and testing indication
■ Adjustable Arcflash Reduction
Maintenance System settings
■ LCD display with programmable
settings
PXR 25 Trip Unit
PXR 10 PXR 20
Table 22.1-12. PXR Features
Features PXR 10 PXR 20 PXR 25
Protection types LSI LSI/LSIG LSI/LSIG
Status indication ● ● ●
USB secondary injection testing ● ● ●
Programmable by USB port (PXPM) ● ● ●
Independent instantaneous adjustment ● ● ●
Adjustable L, S, I, G pickup and time ● ●
Cause of trip indication ▲ ● ●
Load alarm indication with 2 levels ● ●
Programmable load alarm levels ●
Ground fault protection and alarm ● ●
Arcflash Reduction Maintenance SystemE
Available PD3, PD4, PD5, PD6 to meet NEC 240.87 requirements ● ●
Zone selective interlocking (ZSI) with indication ● ●
Programmable relays ● ●
Modbus RTU communication ● ●
CAM module communication ● ●
Rotatable LCD display ●
Breaker health and diagnostic monitoring ▲ ●
Current metering accuracy 2.0% 0.5%
Voltage metering accuracy 0.5%
Power and energy metering accuracy 1.0%
Legend:
● Standard
● Optional
▲ Available through USB port (PXPM)
Fully Programmable
Metering Capability
Enhanced GF
Protection
Versatile
Communication
Arcflash
Reduction
Maintenance
System
ZSI
Verification
and Testing
USB for PXPM
Interface
Breaker
Health
LCD Display
Cause of
Trip LEDs
Design Guide DG014001EN
Effective November 2024
22.1-14
Pow-R-Line 1X, 2X and 3X
Panelboards
Devices
EATON www.eaton.com Page 271 of 1066
Metering, Monitoring and Surge Protective Devices
Power Xpert Meter 350
Power Xpert Meter 350
The Power Xpert Meter 350 (PXM350) is a
revenue grade energy meter that delivers
a cost-effective solution for energy and
submetering applications. This DIN rail
mounted, three-phase energy meter
provides high accuracy in a small form
factor. The user-friendly LCD display is
ideal for building energy management,
energy monitoring and metering systems.
Meter features include:
■ Data collection and management
for energy and multi-parameters
measurement
■ Demand measurement and forecasting
of current, active power, reactive power
and apparent power
■ Standard with Modbus RTU, BACnet
MSTP and pulse output
■ Multiple current sensors options are
available—5 A/1 A, 333 mV and
Rogowski coil system event logging
with configurable parameter alarms
■ LCD display with backlight support
■ Electronic and physical sealing to
prevent tampering
Power Xpert Branch Circuit Monitor
Power Xpert Branch Circuit Monitor
Eaton’s Power Xpert Branch Circuit
Monitor (PXBCM) provides remote access
to live energy readings and facilitates
data integration for data center intensive
industries, facilities working to optimize
server capacity and companies with a
critical need to maintain uptime. By
combining monitoring capabilities down
to the plug level with overload alerts,
which indicate when circuits are close to
exceeding thresholds, the PXBCM helps
minimize or prevent downtime.
■ ANSI C12.20 0.5% revenue accuracy
for panelboard applications
■ Satisfies energy code requirements
to meter energy by branch circuit
and report energy consumption by
load group
■ Modular form factor supports either
pre-mounted CTs (PXBCM-MMS) or
loose CTs (PXBCM-MME) and makes
it easy to scale for 18-, 30-, 42- and
84-circuit panelboard applications
For more information, visit
www.eaton.com/meters.
Integrated Surge Protective Devices
Integrated Surge Protective Devices
Eaton integrates our industry-leading
surge protective devices (SPD) into
panelboards. Lead length is kept to a
minimum to maximize SPD performance.
SPD units are available with ratings up
through 400k, and are UL listed and
labeled to UL 1449 3rd Edition.
All panelboards with integrated SPD units
are connected to a lineside overcurrent
protective device for disconnecting
means. When applied on the lineside of a
service entrance main, the disconnecting
means does not count as a service
disconnect per National Electrical Code
Article 230.71[A].
Refer to Table 22.1-13 for side-by-side
comparison of integrated SPD offerings.
For complete SPD product
description, application and ratings,
visit www.eaton.com/spd.
Design Guide DG014001EN
Effective November 2024
22.1-15
Pow-R-Line 1X, 2X and 3X
Panelboards
Devices
EATON www.eaton.com Page 272 of 1066
Metering, Monitoring and Surge Protective Devices, Continued Table 22.1-13. Side-by-Side Comparison of the SPD Series’ Available Feature Packages Feature package comparison Basic Standard Standard with Surge Counter
Power Xpert
SPD
Surge protection using thermally protected MOV technology n n n n Dual-colored protection status indicators for each phase n n n n Dual-colored protection status indicators for the neutral-ground protection mode a n n n Tri-colored protection status indicators for each phase and the neutral-ground protection mode a n Audible alarm with silence button n n n
Form C relay contact n n n
EMI/RFI filtering, providing up to 50 dB of noise attenuation from 10 kHz to 100 MHz n n n Surge counter with reset button n n
Percentage protection remaining status n
RJ45 Ethernet port for LAN connection, Modbus TCP/IP or BACnet/IP n UI webpage and programmable settings n
Time-and-date stamped surge log and surge categorization n a Neutral-ground protection mode available in applicable voltage configurations only.
Pow-R-Line Metering and Monitoring Options
Device Pow-R-Line 1X Pow-R-Line 2X Pow-R-Line 3E Pow-R-Line 3X Pow-R-Line 4X / 4F Power Defense molded case
circuit breakers with Power Xpert
Release trip units
n n n n n
Power Xpert Meter 350 n n n n
Veris E30 Branch Circuit Monitor n n n
Power Xpert Branch Circuit Monitor n n n n n (Type PRL4X only) Power Xpert Meter 1000 n
Power Xpert Meter 2000 n
Power Xpert Meter 3000 n
Power Xpert Gateway n
Power Distribution Monitoring
and Control
n
Design Guide DG014001EN
Effective November 2024
22.1-16
Pow-R-Line 1X, 2X and 3X
Panelboards
Devices
EATON www.eaton.com Page 273 of 1066
PRL1X Layout Guide
Pow-R-Line 1X
Technical Data and Specifications
Bussing
100–400 A: Tin-plated aluminum
is standard, copper is available
as an option.
600 A: Only copper density is available
for these applications.
Boxes
Boxes are made from code-gauge steel.
Blank ends are supplied as standard,
knockouts are available upon request.
EZ Trim
Trims are made from code-gauge steel
and painted ANSI 61 gray.
All panelboards have door-in-door
as standard with multi-point
catch and lock, and concealed
mounting hardware.
Modifications
Table 22.1-14. Sub-Feed Lugs (Main Lugs Only)
Ampere
Rating
Panel Height
Addition
100
225
0 Inches (0 mm)
0 Inches (0 mm)
Table 22.1-15. Through-Feed Lugs
Ampere
Rating
Information
100
225
400
600
See Table 22.1-17
See Table 22.1-17
See Table 22.1-17
See Table 22.1-17
Table 22.1-16. Sub-Feed Breakers (One Per Panel)
Ampere
Rating
Breaker
Type
Interrupting Rating
(kA Symmetrical)
at 240 V
225
225
225
225
225
225
225
PDD2xF
PDD2xG
PDD2xM
PDD3xP
PDG2xG
PDG2xM
PDG2xP
22 65
100
200
65 100
200
400
400
400
400
PDD3xG
PDG3xG a
PDG3xM a
PDG3xP a
65 65
100
200
600
600
600
PDG3xG a
PDG3xM a
PDD3xP
65 100
100
a The 400 A frame must use trip units of ratings
100–400, while the 600 A frame must use trip
units of ratings 500, 600 or designated by H,
such as H250. The H as the leading character of
the ampacity indicates a high instantaneous
version of the breaker for coordination
purposes. H ratings must use 600 A frame.
Shunt Trips
Shunt trips are available on breakers.
BAB, HQP, QBHW and QPHW require
one additional pole space for shunt trip,
i.e., single-pole is two-pole size, two-pole
is three-pole size and three-pole is
four-pole size.
Ground Bar
Standard bolted in box. Aluminum is
standard, copper is available as an option.
Enclosures
Types 1, 12, 3R, 4 and 4X.
Surge Protective Device (SPD)
Integrated onto panelboard chassis.
For complete product description
and available ratings, refer to Surge
Protection (SPD) and Power Conditioning
Products Design Guides.
Box Sizing and Selection
Box size for all Type 1 panelboards
are available from Table 22.1-17.
Instructions
1. Select the rating and type of
mains required.
2. Count total number of branch circuit
poles (including spaces) required in
the panelboard. Do not count main
breaker poles. Convert two- or
three-pole branch breakers to
single-poles, i.e., three-pole breaker,
count as three poles.
Note: For horizontal mounted mains
(BAB Type), use main lug table, include
space in branch section for mains.
3. Using correct table, type of mains and
ampere rating per Step 1, find total
number of poles.
Note: Where total number of poles (Step 2)
fall between number in table, use the next
higher number.
4. Read box size across columns to
the right.
Top and Bottom Gutters (Minimum)
5.50 inches (139.7 mm).
Side Gutters
20.00-inch (508.0 mm) wide box:
6.50 inches (165.1 mm).
Design Guide DG014001EN
Effective November 2024
22.1-17
Pow-R-Line 1X, 2X and 3X
Panelboards
EATON www.eaton.com
Layout and Dimensions
Table 22.1-17. Type 1 Panelboards—Dimensions in Inches (mm) Panelboard
Types
Types and Mounting Position
(H) = Horizontal / (V) = Vertical
Maximum
Number
of Branch
Circuits
Including
Provisions
Box Dimensions abc Catalog Number
Main
Breaker
Sub-Feed
Breaker
Dual
Sub-Feed
Breaker
Height Width Depth YS Box LT Trim EZ Box EZ Trim
100 A
Main
breaker
BAB,
QBHW
(H)
—
—
—
—
—
—
—
—
15 27
39 42
36.00 (914.4)
48.00 (1219.2)
48.00 (1219.2)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
YS2036
YS2048
YS2048
YS2060
LT2036S or F
LT2048S or F
LT2048S or F
LT2060S or F
EZB2036R
EZB2048R
EZB2048R
EZB2060R
EZT2036S or F
EZT2048S or F
EZT2048S or F
EZT2060S or F
Main
lugs
—
—
—
—
—
—
—
—
—
—
—
—
18 30
42 48
36.00 (914.4)
36.00 (914.4)
48.00 (1219.2)
48.00 (1219.2)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
YS2036
YS2036
YS2048
YS2048
LT2036S or F
LT2036S or F
LT2048S or F
LT2048S or F
EZB2036R
EZB2036R
EZB2048R
EZB2048R
EZT2036S or F
EZT2036S or F
EZT2048S or F
EZT2048S or F
—
—
—
—
—
—
—
—
—
—
—
—
54 60
72 84
48.00 (1219.2)
60.00 (1524.0)
60.00 (1524.0)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
YS2048
YS2060
YS2060
YS2072
LT2048S or F
LT2060S or F
LT2060S or F
LT2072S or F
EZB2048R
EZB2060R
EZB2060R
EZB2072R
EZT2048S or F
EZT2060S or F
EZT2060S or F
EZT2072S or F
Main
breaker
PDG2xF
PDD3xG
PDG2xM
PDG2xP
(V)
—
—
—
—
—
—
—
—
18 30
42 48
36.00 (914.4)
48.00 (1219.2)
48.00 (1219.2)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
YS2036
YS2048
YS2048
YS2060
LT2036S or F
LT2048S or F
LT2048S or F
LT2060S or F
EZB2036R
EZB2048R
EZB2048R
EZB2060R
EZT2036S or F
EZT2048S or F
EZT2048S or F
EZT2060S or F
—
—
—
—
—
—
—
—
54 60
72 84
60.00 (1524.0)
60.00 (1524.0)
72.00 (1828.8)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2060
YS2072
YS2072
LT2060S or F
LT2060S or F
LT2072S or F
LT2072S or F
EZB2060R
EZB2060R
EZB2072R
EZB2072R
EZT2060S or F
EZT2060S or F
EZT2072S or F
EZT2072S or F
Main lugs
with 100 A
throughfeed lugs
or sub-feed
breaker
— PDG2xF
PDG2xG
PDG3xG e
PDG2xM
PDG2xP
(V)
—
—
—
—
18 30
42 48
48.00 (1219.2)
48.00 (1219.2)
60.00 (1524.0)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
YS2048
YS2048
YS2060
YS2060
LT2048S or F
LT2048S or F
LT2060S or F
LT2060S or F
EZB2048R
EZB2048R
EZB2060R
EZB2060R
EZT2048S or F
EZT2048S or F
EZT2060S or F
EZT2060S or F
—
—
—
—
54 60
72 84
60.00 (1524.0)
60.00 (1524.0)
72.00 (1828.8)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2060
YS2072
YS2072
LT2060S or F
LT2060S or F
LT2072S or F
LT2072S or F
EZB2060R
EZB2060R
EZB2072R
EZB2072R
EZT2060S or F
EZT2060S or F
EZT2072S or F
EZT2072S or F
Main
breaker
with 100 A
throughfeed lugs
or sub-feed
breaker
PDG2xF
PDG2xF
PDG3xG e
PDG2xM
(V)
PDG2xG
PDG2x
PDG3xG e
PDG2xM
PDG2xP
(V)
—
—
—
—
18 30
42 48
48.00 (1219.2)
48.00 (1219.2)
60.00 (1524.0)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
YS2048
YS2048
YS2060
YS2060
LT2048S or F
LT2048S or F
LT2060S or F
LT2060S or F
EZB2048R
EZB2048R
EZB2060R
EZB2060R
EZT2048S or F
EZT2048S or F
EZT2060S or F
EZT2060S or F
—
—
—
54 60
72 72.00 (1828.8)
72.00 (1828.8)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
YS2072
YS2072
YS2072
LT2072S or F
LT2072S or F
LT2072S or F
EZB2072R
EZB2072R
EZB2072R
EZT2072S or F
EZT2072S or F
EZT2072S or F
225 A
Main
lugs a
—
—
—
—
—
—
—
—
—
—
—
—
18 30
42 48
36.00 (914.4)
36.00 (914.4)
48.00 (1219.2)
48.00 (1219.2)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
YS2036
YS2036
YS2048
YS2048
LT2036S or F
LT2036S or F
LT2048S or F
LT2048S or F
EZB2036R
EZB2036R
EZB2048R
EZB2048R
EZT2036S or F
EZT2036S or F
EZT2048S or F
EZT2048S or F
—
—
—
—
—
—
—
—
—
—
—
—
54 60
72 84
48.00 (1219.2)
60.00 (1524.0)
60.00 (1524.0)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
YS2048
YS2060
YS2060
YS2072
LT2048S or F
LT2060S or F
LT2060S or F
LT2072S or F
EZB2048R
EZB2060R
EZB2060R
EZB2072R
EZT2048S or F
EZT2060S or F
EZT2060S or F
EZT2072S or F
Main
breaker d
PDD2xF
PDD2xG,
PDD2xM
PDG2xG
PDG2xM
PDG2xP
PDG3xG e
(V)
—
—
—
—
—
—
—
—
18 30
42 48
36.00 (914.4)
48.00 (1219.2)
48.00 (1219.2)
60.00 (1524.0)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
YS2036
YS2048
YS2048
YS2060
LT2036S or F
LT2048S or F
LT2048S or F
LT2060S or F
EZB2036R
EZB2048R
EZB2048R
EZB2060R
EZT2036S or F
EZT2048S or F
EZT2048S or F
EZT2060S or F
—
—
—
—
—
—
—
—
54 60
72 84
60.00 (1524.0)
60.00 (1524.0)
72.00 (1828.8)
72.00 (1828.8)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
20.00 (508.0)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
5.75 (146.1)
YS2060
YS2060
YS2072
YS2072
LT2060S or F
LT2060S or F
LT2072S or F
LT2072S or F
EZB2060R
EZB2060R
EZB2072R
EZB2072R
EZT2060S or F
EZT2060S or F
EZT2072S or F
EZT2072S or F
a Smaller panelboard box sizes are available if required. Contact Eaton for application information. b For applications with SPD, contact Eaton.
c 28.00 inches (711.2 mm) optional width is available for panelboards with high circuit counts. d JD, JDC is same space requirement as 400 A PDD3xG, PDG3xM*, PDG3xP* (see footnote 5 for PDG3 breaker information). e The 400 A frame must use trip units of ratings 100–400, while the 600 A frame must use trip units of ratings 500, 600 or designated by H, such as H250.
The H as the leading character of the ampacity indicates a high instantaneous version of the breaker for coordination purposes. H ratings must use 600 A frame.
Design Guide DG014001EN
Effective November 2024
22.1-18
Pow-R-Line 1X, 2X and 3X
Panelboards
Layout and Dimensions
EATON www.eaton.com Page 275 of 1066
Low-voltage power distribution and control systems > Panelboards > Pow-R-Line 4X panelboards
Contents
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.3-2 Lighting and Distribution Panelboards Overview . . . . 22.3-2 Application Considerations and Definitions . . . . . . . . 22.3-4 Pow-R-Line 4X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.3-7 Pow-R-Line 4DX Drawout Panelboard . . . . . . . . . . . . 22.3-8 Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.3-9 Circuit Breaker Technical Data . . . . . . . . . . . . . . . . . . 22.3-9 Power Xpert Release Trip Unit for
Molded Case Circuit Breakers . . . . . . . . . . . . . . . . . . 22.3-12 Metering, Monitoring and Surge Protective Devices . 22.3-13 Pow-R-Line Metering and Monitoring Options . . . . . 22.3-16 Layouts and Dimensions . . . . . . . . . . . . . . . . . . . . . . 22.3-17 PRL4X Layout Guide . . . . . . . . . . . . . . . . . . . . . . . . . 22.3-17 PRL4DX Layout Guide . . . . . . . . . . . . . . . . . . . . . . . . 22.3-23 Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . 22.3-24 Series Rated Combinations . . . . . . . . . . . . . . . . . . . . 22.3-24 Panelboard Selection Guide . . . . . . . . . . . . . . . . . . . . 22.3-26 Type PRL4X Modifications . . . . . . . . . . . . . . . . . . . . . 22.3-29 More about this product
Eaton.com/panelboards
Complete library of design guides
Eaton.com/designguides
Design Guide DG014003EN Effective March 2025
Lighting and Distribution
Panelboards Overview
■ Designed for sequence phase
connection of branch circuit devices
■ Enables single-, two- or three-pole
arrangements for a balanced electrical
load on each phase
■ Sturdy, rigid chassis assembly ensures
accurate alignment of interior with
panel front
■ Assembly also prevents flexing and
minimizes loosening or damage to
current-carrying parts
■ Four-point in-and-out adjustment of
panel interior meets critical depth
dimensions on flush installations
■ Main lugs are approved for copper or
aluminum conductors
Available Ratings
■ Rated at 240 Vac, 480 Vac and 600 Vac
■ Fault current available up to 200 kAIC
at 240 Vac, 100 kAIC at 480 Vac and
65 kAIC at 600 Vac
Panelboard Options
■ Aluminum, copper, silver-plated copper
or tin-plated copper bus
■ Aluminum or copper lugs
■ Density-rated bus
■ Ground bars
■ Customer-owned meters
■ Service entrance equipment
construction
■ Surge protective devices
■ Seismically qualified panelboards
From left to right: Pow-R-Line 1X, Pow-R-Line 2X, Pow-R-Line 4X and Pow-R-Line 3X panelboards Enclosures
■ Boxes are code-gauge galvanized
steel, available unfinished or painted
ANSI-61 light gray
■ Standard panelboard cabinets are
designed for indoor use
■ Alternate types are available for
special-purpose applications
■ All enclosures meet ULT standards
and include wiring gutters with proper
wire bending space
■ Box dimensions shown are inside
dimensions—for outside dimensions,
add 0.25 inch (6.4 mm)
■ Standard panelboard boxes
are supplied without knockouts
(blank endwalls)
The Three-Piece Trim for Larger Power
Distribution Panelboards Provides for
Easy Handling and Installation
Design Guide DG014003EN
Effective March 2025
22.3-2
Pow-R-Line 4X
Panelboards
EATON www.eaton.com
General Description
Fronts
■ Made of code-gauge steel with
a high-durability ANSI-61 light
gray finish
■ Branch circuit and small power
distribution panelboards include
a door and concealed hinges
■ Flush-type latch and lock
assembly included
■ All locks are keyed alike
■ Trims available in both surfaceand flush-mounted designs Power Distribution Panelboard
Fronts Only
■ Utilize a breaker front cover design
providing each device with a dedicated
bolt-on steel cover
■ Individual covers form a single
deadfront used with two wiring gutter
covers to complete the trim
■ A door is not finished but can be
provided for an additional charge
using a deeper-than-standard box
EZ BoxE and EZ TrimE
Provided standard for:
■ Pow-R-Line 1X and Pow-R-Line 2X
lighting panelboards
■ Pow-R-Line 3X, Pow-R-Line 3E
and Pow-R-Line 3XF mid-range
panelboards
EZ Box and EZ Trim
Features
■ Virtually eliminates sharp edges
■ Trim installs quickly
■ Door-in-door is standard
■ Ability to adjust flush box to wall
irregularities
■ Trim installs without the need for tools
■ No exposed hardware (because there
is none)
EZ Box
■ Flanges are bent and painted, and
without sharp edges
■ All steel panelboard chassis parts
are painted to reduce injuries during
handling and installation
■ Each flange adjusts outward up to
0.75 inch (19.1 mm), enabling installer
to flush the box with a wall after wall
material is installed
■ Flanges also provide means for
attaching EZ Trim
EZ Trim
■ Design installs in seconds
■ Standard trim includes door-in-door
construction and no exposed hardware
■ No tools required for installation
■ Includes hangers attached on the
right side
■ Bottom trim hanger with notch in base
inserts into the bottom right side box
flange opening, resting the notch on
the flange
Standalone Trim and Bottom Flange
Hanger with Notch
Standards and Certifications
When used with Eaton’s panelboard
chassis, EZ Box and EZ Trim meet the
following applicable industry standards:
■ UL 50 Listed
■ NEMAT Standard PB1
■ Federal specifications
■ National Electrical CodeT (NECT)
Design Guide DG014003EN
Effective March 2025
22.3-3
Pow-R-Line 4X
Panelboards
General Description
EATON www.eaton.com Page 279 of 1066
Application Considerations
and Definitions
Standards
All Eaton panelboards meet the following
applicable industry standards, except
where noted:
■ UL
❏ Panelboards: UL 67
q Cabinets, boxes and trims: UL 50
Note: Only panelboards containing UL Listed
devices can be UL labeled.
■ NEC
■ NEMA PB 1
■ Federal Specification W-P-115c
❏ Circuit breaker—Type I Class 1
q Fusible switch—Type II Class 1
Panelboard Selection Factors
In selecting a panelboard, the following
factors must be considered:
■ Service (voltage and frequency)
■ Interrupting capacity (fully or
series rated)
■ Ampere rating of main
■ Ampere ratings of branches
■ Installation environment
■ Codes and standards mandates
Panelboard Short-Circuit Rating
■ Eaton’s assembled panelboards are test
verified by, and listed with, UL
■ Ratings are generally that of the lowest
interrupting rated device in the panel
■ Where branch devices have been UL
tested in combination with specific
main devices having a higher
interrupting rating, the series shortcircuit rating of the assembled panelboard will be the same as the
series tested rating of the approved
rated main breaker
■ Series ratings apply to panels having
main devices, or main-lug-only
panelboards fed remotely by the
device listed in the series ratings
chart as the main, for which UL Listed
tests were conducted
Selective Coordination
Refer to Molded Case Circuit Breakers
Design Guides for information on
overcurrent protective device
combinations used in selectively
coordinated systems.
Service Entrance Equipment
Service Entrance Equipment NEC Articles
230.62 and 230.71, and UL, require that:
■ Panelboards used as service entrance
equipment must be located near the
point where the supply conductors
enter the building
■ A single service disconnect within
the panelboard
■ Must include service disconnect
barrier, connector for bonding and
grounding neutral conductor
■ A service-entrance-type UL label must
be factory installed
■ Ground fault protection of equipment
shall be provided for solidly grounded
wye electrical services of more than
150 V to ground, but not exceeding
600 V phase-to-phase for each service
disconnecting means rated 1000 A
or more
■ Service entrance panels must be
identified as such on the order entry
to the manufacturing location
Table 22.3-1. Service Entrance Main Breaker Kits
Description Circuit
Breaker
Frame
Catalog
Number
Service entrance
barrier for PD5
PD5 PRLSEBPD5
Service entrance
barrier for PD4
PD4 PRLSEBPD4
Service entrance
barrier for PD3
PD3 PRLSEBPD3
Service entrance
barrier for PD2
PD2 PRLSEBPD2
Service entrance
barrier for GHB
GHB PRLSEBGHB
Service entrance
barrier for BAB
BAB PRLSEBBAB
Column Type Panelboards
The same general code restrictions apply
as for standard-width panels except
where trough extensions are used.
Multi-Section Panelboards
■ When more than 42 overcurrent
protective devices are required,
two or more separate enclosures
may be required
■ Separate fronts for each box
are standard
Interconnecting Multi-Section
Panelboards
■ When a panelboard must be furnished
in more than one section (box) for
connection to one feeder, each section
must be furnished with main bus and
terminals of the same rating unless a
main overcurrent device is provided
in each section
■ Sub-feed or through-feed
provisions must also be added
to provide connection capability
to the second section
Note: Sub-feed or through-feed lugs cannot
be used on any panelboard not protected by
a single main overcurrent device either in
the panelboard or immediately upstream,
i.e., service entrance panelboards with
main-lug-only using the six disconnect rule.
Sub-Feed Lugs (Figure 22.3-1)
■ Sub-feed (second set of) lugs
interconnect multi-section panels
■ Mounted directly beside the main lugs
■ Required in each section except the last
panel in the lineup
■ Feeder cables are brought into the
wiring gutter of the first section and
connected to the main lugs
■ Another set of same-size cables
connect to the sub-feed lugs (Section 1)
and are carried over to the main lugs of
the adjacent panel
■ Cross connection cables are not
furnished by Eaton
■ Sub-feed lugs are only available on
main-lug-only panels
Note: Sub-feed lugs may not be used on
main-lug-only (six disconnect rule) service
entrance panels.
Figure 22.3-1. Sub-Feed Lugs
Box Box
Conduit
Neutral
Panel
Neutral
Panel
Section 1Section 2
Neutral Neutral
Panel
Panel
Box Box
Taps
Conduit
Incoming Feeder Cables
Design Guide DG014003EN
Effective March 2025
22.3-4
Pow-R-Line 4X
Panelboards
General Description
EATON www.eaton.com Page 280 of 1066
Through-Feed Lugs (Figure 22.3-2)
■ Another method to interconnect
multi-section panelboards
■ Incoming feeder cables connect to
main lugs or main breaker at the
bottom of panel (Section 1)
■ Another set of lugs (through-feed)
are located at the opposite end of the
main bus
■ Interconnecting cables connect to
the through-feed lugs in Section 1
and are carried over to the main lugs
in Section 2
■ Connection arrangement is reversible,
with main lugs at top and through-feed
lugs at bottom end of panel
■ Cross connection cables are not
furnished by Eaton
Note: Through-feed lugs may not be used on
main-lug-only (six disconnect rule) service
entrance panels.
Figure 22.3-2. Through-Feed Lugs
Multiple Section Panelboard—
Flush Mounted
Shown below is the standard method for
flush mounting multiple section lighting
and distribution panelboards using
standard flush trims.
Figure 22.3-3. Multiple Section Panelboard—
Flush Mounted—Dimensions in Inches (mm)
Branch Circuit Loading for
Lighting Panels
The size of mains and branches should
be selected based on the following:
■ Lighting circuits: NEC Article 210, 215,
220 and 240
■ Distribution circuits, actual or
continuous loads: NEC Article 384.16
■ Motor circuits: NEC Article 430
■ Diversity factor
■ Provision for future loading
Overcurrent Protection
■ NEC Article 408 states a panelboard
shall be protected by an overcurrent
protective device having a rating not
greater than that of the panelboard
■ The overcurrent protective device shall
be located within, or at any point on the
supply side of, the panelboard
■ Exceptions to Article 408 selectively
apply—refer to it for specifics
Ground Fault Protection
May be added to most panelboards
using Eaton’s integral molded case
circuit breaker and included feeder
devices on:
■ Power panelboards
■ Mains on all panelboards
Arcflash Reduction
Maintenance SystemE
■ Available on many molded case circuit
breakers from 70 A to air power circuit
breakers at 5000 A
■ Enables breakers to trip quickly,
significantly reducing the available
arc flash potential
■ Recognized by the 2011 NEC and the
National Electrical Safety CodeT
(NFPA 70ET)
Combination AFCI Circuit Breakers
■ Eaton’s 125 Vac AFCI single- and
two-pole, 15 A and 20 A bolt-on
breakers in panelboards meet
NEC Article 210.12
■ See the NEC for definitions and details
Section 1 Section 2
Box Box
Conduit
Neutral
Panel
Panel
Neutral
Main Lugs
Thru- Feed
Lugs
Main
Lugs
Cross Cables
Incoming Feeder Cables
Contractor to Mount Boxes
1-1/2-inch (38.1 mm) Apart to
Allow for 3/4-inch (19.1 mm)
Extension on Both Flush Trims
Two Section Panelboard
(Flush Mounting)
Flush Trim Extends 3/4-inch
(19.1 mm) Beyond Outside
of Box on All Four Sides
Outside Edge of Box Trim
Wall Wall Trim Trim
Conduit Nipple for Cross Wiring by Contractor
0.75 (19.1) 1.50
(38.1)
Top Section
View
0.75 (19.1) 0.75
(19.1)
0.75 (19.1)
0.75 (19.1)
0.75 (19.1)
0.75 (19.1)
0.75 (19.1) 0.75
(19.1)
0.75 (19.1)
Design Guide DG014003EN
Effective March 2025
22.3-5
Pow-R-Line 4X
Panelboards
General Description
EATON www.eaton.com Page 281 of 1066
Ambient Temperatures
The primary function of an overcurrent
device is to protect the conductor and
its insulation against overheating. In
selecting the size of the devices and
conductors, consideration should be
given to the ambient temperature
surrounding the conductors within and
external to the panelboard. Cumulative
heating within the panelboard may cause
premature operation of overcurrent
protective devices.
■ UL test procedures are based, in part,
on 80% loading of panelboard branch
circuit devices
■ NEC Article 408 limits the loading of
overcurrent devices in panelboards
to 80% of rating where in normal
operation, the load will continue for
three hours or more
■ Further derating may be required,
depending on ambient temperature,
duty cycle, frequency or altitude
■ An exception applies to assemblies
and overcurrent devices approved for
continuous duty at 100% of their rating
and is covered in NEC 210.20 (a)—for
additional information, see Molded
Case Circuit Breakers Design Guides
Special Conditions
Standard panelboards, assembled with
standard components, are adequate for
most applications. However, special
consideration should be given to those
required for application under special
conditions, such as:
■ Excessive vibration or shock
■ Frequencies above 60 cycles
■ Altitudes above 6600 feet (2012 m)
■ Damp environment (possible
fungus growth)
■ Compliance with federal, state
and municipal electrical codes
and standards
Seismic Qualification
Refer to Power Distribution Systems
Design Guides for information on
seismic qualification for this and other
Eaton products.
Harmonic Currents
■ Standard panelboard neutrals are rated
for 100% of the panelboard current
■ Because harmonic currents can cause
overheated neutrals, an option is
provided for neutrals to be rated at
200% (1200 A maximum neutral for
600 A main bus) of the panelboard
phase current
■ Panelboards with the 200% rated
neutral are UL Listed as suitable for
use with nonlinear loads
■ Prior to specifying the 200% rated
neutral, a harmonic survey of the
distribution system is recommended
Surge Protective Devices (SPD)
The quality of power feeding sensitive
electronic loads is critical to the reliable
operation of any modern facility. The most
frequent causes of microprocessor-based
equipment downtime and damage are
voltage transients and electrical noise.
■ High-energy transients include
lightning-induced surges and power
company switching that can destroy
components instantly
■ Continual low-energy transients and
high-frequency noise, which are more
frequent, can cause erratic equipment
performance or sudden failure of
electronic circuit board components
Eaton’s SPD provides protective and
diagnostic systems that are integral
to panelboards:
■ Safeguards sensitive electronic
equipment from the damaging effects
of high- and low-energy transients
■ Integrates into the panelboards using
a “zero lead length” direct busbar
connection
■ Uses integral disconnect on all
panelboards
For complete product description
and available ratings, refer to Surge
Protection (SPD) & Power Conditioning
Products Design Guides.
Eaton SPDs May be Integrated
into Most Panelboards
Compact Panelboard Meter
Most Eaton panelboards can integrate a
meter for reading the panelboard power
and energy usage. Our Power XpertE
Meter 350 offers:
■ ANSI 12.20 0.5% accuracy
■ A bright backlit LCD display
■ Real energy pulse output
■ Phase loss alarm
■ Optional RS-485 communication
capability
Design Guide DG014003EN
Effective March 2025
22.3-6
Pow-R-Line 4X
Panelboards
General Description
EATON www.eaton.com Page 282 of 1066
Pow-R-Line 4X
PRL4X Circuit Breaker
Panelboard
General Description
Panelboard Ratings
Voltage
■ 240 V, 480 V or 600 Vac maximum
■ 600 Vdc maximum
Main Lugs
■ 250–1200 A
Main Breakers
■ 250–1200 A
Branches
■ Breakers 15–1200 A, bolt-on
■ Breakers 20–600 A drawout
■ Fusible switches 30–1200 A, bolt-on
Short-Circuit Current Ratings (Symmetrical)
■ 240 Vac: 10–200 kA fully rated
■ 240 Vac: 22–200 kA series rated
■ 480 Vac: 14–200 kA fully rated
■ 480 Vac: 22–150 kA series rated
■ 250 Vdc: 10–22 kA fully rated
Service
■ Three-phase, four-wire 208Y/120 V,
240/120 V delta and 480Y/277 V
■ Single-phase, three-wire 120/240 V
■ Single-phase, two-wire 120 V
■ Three-phase, three-wire 120, 240,
480 and 600 V
■ Two-wire 125 Vdc
■ Two-wire 250 Vdc
■ Two-wire 600 Vdc
Suitable for service entrance applications
when specified.
Bussing
250–1200 A tin-plated aluminum is
standard; copper is available as an option.
Density rated bus is also available as an
option.
Main Lugs Only
The short-circuit rating of the MLO
assembled panelboard will be fully rated
based upon the lowest rated branch
device or may be series rated with an
approved upstream device.
Main lugs only ampere ratings:
250, 400, 600, 800 and 1200.
Main Circuit Breakers
The short-circuit rating shown is that of
the main breaker only. The short-circuit
rating of the assembled panelboard is
the rating of the lowest fully rated main
or branch device, or the rating of an
approved series rated combination.
Series Rating Combinations
For more information on product series
ratings, please refer to the Eaton website
at https://www.eaton.com/us/en-us/
products/low-voltage-power-distributioncontrol-systems/series-rating.html or download Eaton Information Manual
1C96944H02.
Design Guide DG014003EN
Effective March 2025
22.3-7
Pow-R-Line 4X
Panelboards
General Description
EATON www.eaton.com Page 283 of 1066
Pow-R-Line 4DX Drawout
Panelboard
Type PRL4DX Drawout Molded Case
Circuit Breaker Power Panelboard
General Description
■ Drawout molded case circuit breaker
power panelboard
■ Front accessible
■ Front connected
■ Through-the-door design drawout
mechanism
■ Visual indication of breaker status and
position
■ Large grab handles for easy removal
■ 600 Vac maximum
■ 1200 A maximum mains
■ 600 A maximum drawout molded case
feeder breakers
Application Description
■ Interrupting ratings up to 200 kAIC
symmetrical
■ Feeder power panelboard
■ Rated as service entrance equipment
when appropriately equipped
■ Ideal for:
❏ Data centers
❏ Industrial facilities
❏ Process equipment manufacturing
❏ Anywhere that requires quick change
of feeder devices is needed
Benefits
■ Ease of maintenance
■ Faster to remove and install
■ Less downtime
Standards and Certifications
■ UL 67 Listed chassis
■ UL 50 Listed box and trim
Series Rating Combinations
For more information on product series
ratings, please refer to the Eaton website
at https://www.eaton.com/us/en-us/
products/low-voltage-power-distributioncontrol-systems/series-rating.html or download Eaton Information Manual
1C96944H02.
Design Guide DG014003EN
Effective March 2025
22.3-8
Pow-R-Line 4X
Panelboards
General Description
EATON www.eaton.com Page 284 of 1066
Circuit Breaker Technical Data
Table 22.3-2. Electrical Characteristics of Circuit Breakers Circuit Breaker Ratings UL Listed Interrupting Ratings (kA rms Symmetrical) Type Ampere
Rating
Number
of Poles
Volts
AC
AC Rating, Volts DC Rating, Volts a
120/240 240 277 480 600 125 250
BAB, HQP 15–70
15–100
1 2
120
120/240
10 10
—
—
—
—
—
—
—
—
—
—
—
—
BAB-H, HQP-H 15–100 2, 3 240 — 10 — — — — —
BABRP, BABRSP 15–30
15–30
1 2
120
120/240
10 10
—
—
—
—
—
—
—
—
—
—
—
—
QBGF, QPGF, QPGFEP
QBGFEP
15–50
15–50
1 2
120
120/240
10 10
—
—
—
—
—
—
—
—
—
—
—
—
QBAF, QBAG 15–20
15–20
1 2
120
120/240
10 10
—
—
—
—
—
—
—
—
—
—
—
—
QBHW, QPHW 15–70
15–100
1 2
120
120/240
22 22
—
—
—
—
—
—
—
—
—
—
—
—
QBHW-H, QPHW-H 15–100 2, 3 240 — 22 — — — — —
QBHGF, QPHGF, QPHGFEP
QBHGFEP
15–30
15–30
1 2
120
120/240
22 22
—
—
—
—
—
—
—
—
—
—
—
—
QBHAF, QBHAG 15–20
15–20
1 2
120
120/240
22 22
—
—
—
—
—
—
—
—
—
—
—
—
GHB 15–100 b
15–100
1 2, 3
277
480Y/277
65 —
—
65 14
—
—
14 c
—
—
14 —
—
14 GHQ 15–30 1, 2 277 65 — 14 — — — —
HGHB 15–30 1 277 65 — 25 — — — —
GHBGFEP 15–60 1 277 — — 14 — — — —
GHQRSP 15–100
15–100
1 2
277
480Y/277
65 —
—
65 14
14 —
14 c
—
—
—
—
—
—
EGB 15–125
15–125
1 2, 3
277
480
35 —
35 35
18 —
—
18 —
—
10 —
—
10 EGS 15–125
15–125
1 2, 3
277
480
100
—
—
100
35 —
—
35 —
—
35 —
—
35 EGH 15–125
15–125
1 2, 3
277
480
200
—
—
200
65 —
—
65 —
—
42 —
—
42 PDG2xF 15–100
15–100
1 2, 3
277
480
—
—
—
18 14
—
—
14 —
—
10 —
—
10 PDG2xG, PDG3xG d 15–150
15–225
1 2, 3
277
600
—
—
—
65 35
—
—
35 —
18 10
—
—
10 PDD2xF
PDD2xG
PDD3xG
100–225
100–225
250–400
2, 3
2, 3
2, 3
240
240
240
—
—
—
22 65
65 —
—
—
—
—
—
—
—
—
10 10
—
—
—
10 PDG3xG de, PDF3xG f
LHH g
NHH
PDG3xG d
CLD ef
PDG4xG e, PDF4xG ef
CND ef
100–400
150–400
150–350
250–600
300–600
300–800
400–1200
2, 3
2, 3
3 3
2, 3
2, 3
2, 3
600
480
600
600
600
600
600
—
—
—
—
—
—
—
65 100
100
65 65
65 65
—
—
—
—
—
—
—
35 65
65 35
35 50
50 25
35 35
18 25
25 25
—
—
—
—
—
—
—
10 42
—
22 22 g
22 —
CNGC
CNGH
CNGS
PDG5xP
PDG5xM
NGS
800, 1200
800, 1200
800, 1200
800, 1200
800, 1200
800, 1200
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
200
100
85 200
100
85 —
—
—
—
—
—
100
65 50
100
65 50
65 35
25 65
35 25
—
—
—
—
—
—
—
—
—
—
—
—
a DC ratings apply to substantially non-inductive circuits. b DC rated single-pole, 15–70 A only.
c Rating 480Y/277 Vac maximum.
d The 400 A frame must use trip units of ratings 100–400, while the 600 A frame must use trip units of ratings 500, 600 or designated by H, such as H250.
The H as the leading character of the ampacity indicates a high instantaneous version of the breaker for coordination purposes. H ratings must use 600 A frame. e Available with integral ground fault protection.
f 100% rated breaker.
g DC rating not available with PXR trip units.
Design Guide DG014003EN
Effective March 2025
22.3-9
Pow-R-Line 4X
Panelboards
EATON www.eaton.com
Devices
Table 22.3-2. Electrical Characteristics of Circuit Breakers (Continued) Circuit Breaker Ratings UL Listed Interrupting Ratings (kA rms Symmetrical) Type Ampere
Rating
Number
of Poles
Voltage AC Rating, Volts DC Rating, Volts a
AC DC 120/240 240 277 480 600 125 250 600
High Interrupting Capacity Circuit Breakers
PDG2xM 15–150
15–225
1 2, 3
277
600
—
—
—
—
—
100
65 —
—
65 —
25 10
—
—
22 —
—
PDD2xM
PDG3xM bc, PDF3xM d
PDG3xM bc
100–225
100–400
250–600
2, 3
2, 3
2, 3
240
600
600
—
—
—
—
—
—
100
100
100
—
—
—
—
65 65
—
35 35
10 —
—
—
22 22
—
—
—
PDG4xM c, PDF4xM cd
PDG5xM c
300–800
400–1200
2, 3
2, 3
600
600
—
—
—
—
100
100
—
—
65 65
35 35
—
—
25 —
—
—
Current-Limiting Circuit Breakers
PDD2xP
PDG2xP
100–225
15–225
2, 3
2, 3
240
600
—
—
—
—
200
200
—
—
—
100
—
35 10
—
—
22 —
—
PDG3xP bc
PDG3xP be
PDG5xP c
100–400
250–600
400–1200
2, 3
2, 3
2, 3
600
600
600
—
—
—
—
—
—
200
200
200
—
—
—
100
100
100
65 50
65 —
—
—
22 42
—
—
—
—
Current Limit-RT Circuit Breakers
FCL 15–100 2, 3 480 — — 200 — 150 — — — —
TRI-PACT Current-Limiting Circuit Breakers
FB-P
NB-P
15–100
300–800
2, 3
2, 3
600
600
—
—
—
—
200
200
—
—
200
200
200
200
—
—
g
g
—
—
Direct Current (DC) Rated Breakers
HFDDC fg
HJDDC fh
HKDDC fh
15–150
70–250
100–400
2, 3
2, 3
2, 3
—
—
—
600
600
600
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
42 42
42 42
42 42
35 35
35 HLDDC fh
HMDLDC fh
NBDC fh
300–600
300–800
700–1200
2, 3
2, 3
2, 3
—
—
—
600
600
600
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
42 42
42 42
42 42
35 35
35 a DC ratings apply to substantially non-inductive circuits. b The 400 A frame must use trip units of ratings 100–400, while the 600 A frame must use trip units of ratings 500, 600 or designated by H, such as H250.
The H as the leading character of the ampacity indicates a high instantaneous version of the breaker for coordination purposes. H ratings must use 600 A frame. c Available with integral ground fault protection.
d 100k based on NEMA test procedure.
e DC rating not available with PXR trip units.
f For use on DC systems only.
g Non-interrupting trip type.
h Interrupting trip type.
Design Guide DG014003EN
Effective March 2025
22.3-10
Pow-R-Line 4X
Panelboards
Devices
EATON www.eaton.com Page 286 of 1066
Terminal Wire Ranges, Pressure-Type Al/Cu Terminals Except as Noted Where copper-aluminum terminals are supplied on designated panelboard types, best results are obtained if a suitable joint compound is applied when aluminum conductors are used.
Table 22.3-3. Standard Main Lug Terminals
Panel
Type
Wire Size Ranges for Ampere Capacity
100 A 225 A 250 A 400 A 600 A 800 A 1200 A
Pow-R-Line 4X — — #4–500 kcmil (2) #4–500 kcmil (2) #4–500 kcmil (3) #4–500 kcmil (4) #4–500 kcmil Note: Optional 750 kcmil mechanical screw-type terminals are available upon request. Panelboard dimensions may be affected. Refer to Eaton.
Table 22.3-4. Standard Main Breaker and Branch Breaker Terminals Breaker Type Ampere Rating Wire Size Ranges
BAB, QBHW, BABRSP
HQP, QPHW
15–70
90–100
#14–#4
#8–1/0
PDD2xF, PDD2xG
PDD2xM, PDD2xP a
100–225 #4–4/0 or
#6–300 kcmil
EGB, EGE, EGS, EGH 15–50
60–125
#14–3/0 Al/Cu
#6–3/0 Al/Cu
PDG2xF, PDG2xG
PDG2xM, PDG2xP a, HFDDC b
15–100
125–225
#14–1/0
#4–4/0
FCL 15–100 #14–1/0
GHB, HGHB, GHQ,
GHQRSP
15–50
25–100
#14–1/0
#10–1/0
HJDDC b 70–250 #4–350 kcmil
PDD3xG 250–350
400
250–500 kcmil
(2) 3/0–250 kcmil or
(1) 3/0–500 kcmil
PDG3xG c
PDG3xM c, PDG3xP c
HKDDC b, PDF3xG a
PDF3xM a
225
350
400
(1) #3–350 kcmil
(2) 3/0–250 kcmil or
(2) 3/0–250 kcmil or
(1) 3/0–500 kcmil
LHH 150–400 #2–500 kcmil
(2) #2–500 kcmil or
(1) 500–750 kcmil
PDG3xG c, PDG3xM c,
PDG3xM c
250–400
500–600
(1) #2–500 kcmil
(2) #2–500 kcmil
CLD a 300–500 (2) 250–350 kcmil
PDG4xG, PDG4xM, HMDLDC a
PDF4xG, PDF4xM
400–600
700–800
(2) #1–500 kcmil
(3) 3/0–400 kcmil
PDG5xM, CND
PDG5xP, CLD a
800–1000
1200
(3) 3/0–400 kcmil
(4) 4/0–500 kcmil
NGS, PDG5xM, PDG5xP
CNGS, CNGH, CNGC
400–1200 (4) 4/0–500 kcmil or
(3) 500–750 kcmil
a Suitable for DC applications only.
b LHH is 400 A maximum.
c The 400 A frame must use trip units of ratings 100–400, while the 600 A frame must use trip units of ratings 500, 600 or designated by H, such as H250. The H as the leading character of the ampacity indicates a high instantaneous version of the breaker for coordination purposes. H ratings must use 600 A frame.
Table 22.3-5. Fusible Switch Terminals
Ampere Rating Wire Size Ranges
30 60
100
#14–1/0
#14–1/0
#14–1/0
200 #4–300 kcmil
400 250–750 kcmil or
(2) 3/0–250 kcmil
600 (2) #4–600 kcmil or (4) 3/0–250 kcmil
800 (3) 250–750 kcmil or (6) 3/0–250 kcmil
1200 (4) 250–750 kcmil or (8) 3/0–250 kcmil
Design Guide DG014003EN
Effective March 2025
22.3-11
Pow-R-Line 4X
Panelboards
Devices
EATON www.eaton.com Page 287 of 1066
Power Xpert Release
Trip Unit for Molded Case
Circuit Breakers
Description
Eaton’s Power Xpert Release (PXR) trip
units are programmable communicating
microprocessor-based low-voltage
electronic trip unit systems for Eaton
molded case circuit breakers. PXR trip
units are available in three models:
PXR 10, PXR 20 and PXR 25.
Standards and Certifications
The PXR trip units are listed by
Underwriters Laboratories (UL) and
Canadian Standards Association (CSA)
for use in Power DefenseE Frame 2, 3, 4,
5 and 6 molded case circuit breakers.
All PXR units have also passed the
IEC 60947-2 test program that includes
EMC testing. All trip units meet the
low-voltage and EMC directives and
carry the CE mark.
Features
The PXR electronic trip units provide
an enhanced and easy-to-use interface
that enables end users and maintenance
engineers to more easily change set
points, test and configure circuit breakers,
and review energy and power information.
The Power Xpert Protection Manager
(PXPM) software also provides the
capability of secondary injection tests
and reports on-demand without the
need of expensive test kits.
Advanced features include:
■ Industry-first breaker health algorithms
provide real-time monitoring and
communication of breaker condition
■ Cause of trip LED indication and trip
event data storage
■ Zone selective interlocking (ZSI)
verification and testing indication
■ Adjustable Arcflash Reduction
Maintenance SystemE settings
■ LCD display with programmable
settings
PXR 25 Trip Unit
PXR 10 PXR 20
Table 22.3-6. PXR Features
Features PXR 10 PXR 20 PXR 25
Protection types LSI LSI/LSIG LSI/LSIG
Status indication ● ● ●
USB secondary injection testing ● ● ●
Programmable by USB port (PXPM) ● ● ●
Independent instantaneous adjustment ● ● ●
Adjustable L, S, I, G pickup and time ● ●
Cause of trip indication ▲ ● ●
Load alarm indication with 2 levels ● ●
Programmable load alarm levels ●
Ground fault protection and alarm ● ●
Arcflash Reduction Maintenance System
Available PD3, PD4, PD5, PD6 to meet NEC 240.87 requirements ● ●
Zone selective interlocking (ZSI) with indication ● ●
Programmable relays ● ●
Modbus RTU communication ● ●
CAM module communication ● ●
Rotatable LCD display ●
Breaker health and diagnostic monitoring ▲ ●
Current metering accuracy 2.0% 0.5%
Voltage metering accuracy 0.5%
Power and energy metering accuracy 1.0%
Legend:
● Standard
● Optional
▲ Available through USB port (PXPM)
Fully Programmable
Metering Capability
Enhanced GF
Protection
Versatile
Communication
Arcflash
Reduction
Maintenance
System
ZSI
Verification
and Testing
USB for PXPM
Interface
Breaker
Health
LCD Display
Cause of
Trip LEDs
Design Guide DG014003EN
Effective March 2025
22.3-12
Pow-R-Line 4X
Panelboards
Devices
EATON www.eaton.com Page 288 of 1066
Metering, Monitoring and Surge Protective Devices
Power Xpert Meter 1000
Power Xpert 1000 Meter
The Power Xpert Meter 1000 (PXM1000)
series power and energy meters monitor
the most critical aspects of an electrical
distribution system. This premier metering
instrument uses advanced technology to
make it simple to use, powerful, scalable
and highly flexible.
The PXM1000 is a revenue grade power
and energy meter that delivers a costeffective solution for energy and submetering applications. This three-phase meter provides high accuracy and
advanced features in the standard 4-inch
form factor and can be expanded with
multiple modular I/O options.
Meter features include:
■ ANSI C12.20 and IEC 62053-22 utility
billing accuracy will help meet
stringent customer specifications
■ Available in 5 A and 333 mV CT
type inputs, allowing ease of use
in multiple applications
■ Rogowski coils allow for ease of use in
retrofit applications
■ Multiple protocols including Modbus
TCP and BACnet/IP and with available
HTTP push, allowing data to be sent
to the cloud to help meet energy code
data storage requirements
Power Xpert Meter 2000
Power Xpert 2250 Meter
The Power Xpert 2250 meter provides all
the core functions for monitoring power
consumption and power quality, ethernet
connectivity and onboard gateway card
limits. This unit uses D/A technology to
sample circuits at 400 samples per cycle
for extremely accurate measurement of
power factor and energy consumption.
In addition, the meter has 256 MB for
logging meter data.
Power Xpert 2260 Meter
The Power Xpert 2260 meter adds
the ability to monitor total harmonic
distortion and the ability to set onboard
meter limits. The meter also will
illuminate LEDs on the faceplate,
indicating that a limit has been exceeded
and provides 512 MB for data logging.
Power Xpert 2270 Meter
The Power Xpert 2270 meter adds the
ability to monitor individual harmonics
and visualize waveforms on your
desktop using the embedded web
server and raises the storage to
768 MB for data logging.
Meter features include:
■ Data provided to fully understand your
facility’s power quality
■ Detailed event information; pinpoint
the root causes of problems—or
prevent them from occurring
■ Measure, trend and analyze power
via information from onboard web
and comma separated values (CSV)
exporting capabilities
■ Up to 768 MB of storage; typically
15 years of storage capability
depending on the meter model
and frequency of events
■ Local or remote configuration
Power Xpert Meter 3000
Power Xpert Meter 3000
The Power Xpert Meter 3000 Series power
quality and energy meter monitors the
most critical aspects of an electrical
distribution system. This premier metering
instrument uses advanced technology to
make it simple to use, powerful, scalable
and highly flexible.
Meter features include:
■ ANSI C12.20 and IEC 62053-22 revenue
grade accuracy will help meet stringent
customer specifications
■ Combines state-of-the-art technology
with harmonic viewing, data trending,
performance benchmarking and sag/
swell waveform recording through an
embedded web server accessible from
any location via a standard web browser
■ The embedded web server supports
viewing of triggered waveforms one
channel at a time, including the ability
to zoom and scroll horizontally using a
slider bar. Waveforms are stored in the
meter’s nonvolatile flash memory
using an industry standard COMTRADE
format, allowing you to view and
analyze the waveforms in any standard
free-of-charge or commercial
COMTRADE file viewer
■ Offers maximum flexibility in
waveform recording by allowing the
number of recorded waveform cycles,
number of pre- and post-event cycles,
and sampling rate to be configured to
your system requirements
■ Standard protocol Modbus TCP
and BACnet/IP
■ Available in 1 A / 5 A current
transformer (CT) type inputs for
ease of use in traditional installations
For information on other available power
meters, visit www.eaton.com/meters.
Design Guide DG014003EN
Effective March 2025
22.3-13
Pow-R-Line 4X
Panelboards
Devices
EATON www.eaton.com Page 289 of 1066
Metering, Monitoring and Surge Protective Devices, Continued Power Xpert Multi-Point Meter
Power Xpert Multi-Point Meter
Eaton Power Xpert Multi-Point meter
(PXMP) helps facility managers track
and accurately allocate energy usage
among tenants or departments in office
buildings, shopping malls, industrial sites,
universities, campuses and apartment and
condominium complexes. Power Xpert
Multi-Point Meters monitor, quantify
and help benchmark energy usage.
Meter features include:
■ Meets rigid ANSI C12.20 and IEC
62053-22 accuracy specifications for
revenue meters
■ Quick connect terminals for current
sensors, Modbus communication
and bus voltages
■ Monitors power and energy for up
to 60 current sensors; scalable from
6 to 60 circuits
■ 256 MB of standard memory for up to
two years of 15-minute interval data
■ Extensive LEDs for verification of
sensor connections, communication
status and equipment status
■ Automatically detects rating of each
current sensor; current sensors are
self-protecting in the event of an open
circuit condition under load for added
safety and reliability
Power Xpert Branch Circuit Monitor
Power Xpert Branch Circuit Monitor
Eaton’s Power Xpert Branch Circuit
Monitor (PXBCM) provides remote access
to live energy readings and facilitates
data integration for data center intensive
industries, facilities working to optimize
server capacity and companies with a
critical need to maintain uptime. By
combining monitoring capabilities down
to the plug level with overload alerts,
which indicate when circuits are close to
exceeding thresholds, the PXBCM helps
minimize or prevent downtime.
■ ANSI C12.20 0.5% revenue accuracy
for panelboard applications
■ Satisfies energy code requirements
to meter energy by branch circuit
and report energy consumption by
load group
■ Modular form factor supports either
pre-mounted CTs (PXBCM-MMS) or
loose CTs (PXBCM-MME) and makes
it easy to scale for 18-, 30-, 42- and
84-circuit panelboard applications
Power Xpert Gateway
Power Xpert Gateway
Eaton’s Power Xpert Gateway (PXG)
bridges the IT and facilities management
worlds by bringing disparate panelboards,
other power equipment onto the network.
The PXG takes the complexity out of
connecting power equipment to the
network. The out-of-the-box device can
support up to 96 devices, translate most
industrial communication protocols, and
offer user-selectable events and real-time
trending. It also features email notification
of events, waveform capture and data/
event logging—all with no special
software. Adding basic meters or the
utility’s meter, the PXG assists in tracking
energy usage. The PXG recognizes the
interdependence of IT systems and power
systems, and delivers what organizations
need to bring these worlds together for
seamless, end-to-end system reliability.
The PXG consolidates data available
breakers, meters, motor controllers
and protective relays, and presents
the information in a variety of ways
(a web browser being the most widely
used method). The PXG is a stand-alone
solution, but as needs change and grow,
the PXG can be integrated through Power
Xpert Software into a broader solution
that encompasses other intelligent
hardware and can integrate with thirdparty network management systems (NMS) or building management systems
(BMS) for system-wide monitoring and
reporting of power and IT.
For more information, visit
www.eaton.com/meters.
Design Guide DG014003EN
Effective March 2025
22.3-14
Pow-R-Line 4X
Panelboards
Devices
EATON www.eaton.com Page 290 of 1066
Metering, Monitoring and Surge Protective Devices, Continued Power Distribution Monitoring and Control
Power Distribution Monitoring and Control
Power Distribution Monitoring and
Control helps keep your critical facilities
up and running by enabling interaction
with low-voltage panelboards and
switchboards through intelligent
component control, communications and
monitoring. Use of Power Distribution
Monitoring and Control may simplify
installation and maintenance efforts
while also reducing exposure to arc
flash and providing access to aggregate
device data from electronic meters and
Eaton’s Power Xpert Release (PXR) trip
units installed in our globally rated,
Power Defense molded case circuit
breakers (MCCBs).
For more information, visit
www.eaton.com/meters.
Integrated Surge Protective Devices
Integrated Surge Protective Devices
Eaton integrates our industry-leading
surge protective devices (SPD) into
panelboards. Lead length is kept to a
minimum to maximize SPD performance.
SPD units are available with ratings up
through 400k, and are UL listed and
labeled to UL 1449 3rd Edition.
All panelboards with integrated
SPD units are connected to a lineside
overcurrent protective device for
disconnecting means. When applied on
the lineside of a service entrance main,
the disconnecting means does not count
as a service disconnect per National
Electrical Code Article 230.71[A].
For complete SPD product
description, application and ratings,
visit www.eaton.com/spd.
Table 22.3-7. Side-by-Side Comparison of the SPD Series’ Available Feature Packages Feature package comparison Basic Standard Standard with Surge Counter
Power Xpert
SPD
Surge protection using thermally protected MOV technology n n n n Dual-colored protection status indicators for each phase n n n n Dual-colored protection status indicators for the neutral-ground protection mode a n n n Tri-colored protection status indicators for each phase and the neutral-ground protection mode a n Audible alarm with silence button n n n
Form C relay contact n n n
EMI/RFI filtering, providing up to 50 dB of noise attenuation from 10 kHz to 100 MHz n n n Surge counter with reset button n n
Percentage protection remaining status n
RJ45 Ethernet port for LAN connection, Modbus TCP/IP or BACnet/IP n UI webpage and programmable settings n
Time-and-date stamped surge log and surge categorization n a Neutral-ground protection mode available in applicable voltage configurations only.
Design Guide DG014003EN
Effective March 2025
22.3-15
Pow-R-Line 4X
Panelboards
Devices
EATON www.eaton.com Page 291 of 1066
Pow-R-Line Metering and Monitoring Options
Device Pow-R-Line 1X Pow-R-Line 2X Pow-R-Line 3E Pow-R-Line 3X Pow-R-Line 4X / 4F Power Defense Molded Case
Circuit Breakers with Power Xpert
Release trip units
n n n n n
Power Xpert Meter 350 n n n n
Veris E30 Branch Circuit Monitor n n n
Power Xpert Branch Circuit Monitor n n n n n (Type PRL4X only) Power Xpert Meter 1000 n
Power Xpert Meter 2000 n
Power Xpert Meter 3000 n
Power Xpert Gateway n
Power Distribution Monitoring
and Control
n
Design Guide DG014003EN
Effective March 2025
22.3-16
Pow-R-Line 4X
Panelboards
Devices
EATON www.eaton.com Page 292 of 1066
Technical Data TD01005006E Effective September 2023
Supersedes October 2022
Eaton’s SPD Series for integration into
electrical distribution equipment
Contents
Description Page
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Standards and certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Feature package options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Remote display mounting option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Performance data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Catalog number selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2 Technical Data TD01005006E
Effective September 2023
Eaton’s SPD Series for integration into
electrical distribution equipment
EATON www.eaton.com
Introduction
Eaton’s SPD Series surge protective devices
Eaton’s SPD Series surge protective devices are the latest and most advanced ULT 1449 5th Edition certified surge protectors. Units are available integrated within Eaton electrical assemblies, including panelboards, switchboards, motor control centers, switchgear, and bus plugs. Side-mount versions of the SPD Series are also available for installation external to an electrical assembly. Application of SPD Series units throughout a facility will ensure that equipment is protected with the safest and most reliable surge protective devices available.
SPD Series units are available in all common voltages and configurations and also in a variety of surge current capacity ratings from 50 kA through 400 kA. Four feature package options are also available to choose from. The breadth of the SPD Series’ features, options, and configurations ensures that the correct unit is available for all electrical applications, including service entrances, distribution switchboards, panelboards, and point-of-use applications.
Applications
The SPD Series is available as an integrated device within the following Eaton electrical assemblies:
• Panelboards
• Switchboards
• Motor control centers
• Switchgear
• Automatic transfer switches
• Bus plugs
Features
• Uses thermally protected metal oxide varistor (MOV) technology • 20 kA nominal discharge current (In) rating (maximum rating assigned by UL)
• 50 kA through 400 kA surge current capacity ratings
• Four feature package options
• 200 kA short circuit current rating (SCCR)
• Can be used for UL 96A compliance
• Can be used for NFPAT compliance
• Can be used for RoHS compliance
• 10-year warranty
Standards and certifications
• UL 1449 5th Edition listed device
• UL 1283 7th Edition listed device
• Canadian Standards AssociationT (CSAT)
• Can be used for UL 96A compliance
• Can be used for NFPAT 780 compliance a
• PXSPD tested to UL 2900-1 cybersecurity standard
• Complete agency certifications can be found in Table 12 a Models must meet maximum allowable VPR in NFPA Table 4.20.4 SPD Series unit integrated within an Eaton panelboard
3 Technical Data TD01005006E
Effective September 2023
Eaton’s SPD Series for integration into
electrical distribution equipment
EATON www.eaton.com
Feature package options
The SPD Series provides users with the option of selecting between four feature packages. These feature packages are the basic, standard, standard with surge counter, and Power XpertT SPD. The proper feature package can be selected based on the requirements of the application or specification.
Table 1. Feature package comparison
Feature Basic Standard
Standard with
surge counter
Power
Xpert SPD
Surge protection using
thermally protected MOV
technology
■ ■ ■ ■
Dual-colored protection
status indicators for each
phase and the neutralground protection mode a
■ ■ ■
Audible alarm with
silence button
■ ■ ■
Form C relay contact ■ ■ ■
EMI/RFI filtering, providing up
to 50 dB of noise attenuation
from 10 kHz to 100 MHz
■ ■ ■
Surge counter with reset ■ ■
Tri-colored protection
status indicators for each
phase and the neutralground protection mode a
■
Percentage protection
remaining status
■
RJ45 Ethernet port for LAN
connection, ModbusT TCP/IP,
or BACnet/IP
■
UI webpage and
programmable settings
■
Time-and-date stamped surge
log and surge categorization
■
a Neutral-ground protection mode available in applicable voltage configurations only.
Remote display mounting option
The SPD Series offers the option of mounting its display remotely from the device. This is useful for applications where OEMs or other integrators would like to embed the unit within a piece of equipment and still be able to view its display.
SPD Series unit catalog numbers ending with ‘B’ (refer to catalog number configuration on page 8) should be ordered for applications where the display is to be mounted remotely. These units include the SPD Series unit and the remote display panel.
In addition to the unit itself, a remote display cable will have to be purchased. Remote display cables are available in 4, 8, and 12 foot lengths.
Table 2. Remote display cables
Description Catalog number Power Xpert SPD Catalog number 4 ft remote display cable SPDRDCAB04 PXSPDRDCAB04
8 ft remote display cable SPDRDCAB08 PXSPDRDCAB08
12 ft remote display cable SPDRDCAB12 PXSPDRDCAB12
Note: Integrated units factory-installed with Eaton switchgear assemblies do not require the purchase of a remote display cable. The cable is provided and all required mounting is performed at the factory.
Existing SPD Series units previously installed without a remote display also have the capability of mounting their displays remotely from the device. Complete remote display kits are available that contain all items required to mount the display remotely, including the remote display cable. Remote display kits are available in 4, 8, and 12 foot cable length options.
Table 3. Remote display kits
Description Catalog number Power Xpert SPD Catalog number Remote display kit with
4 ft remote display cable
SPDRDKIT04 PXSPDRDKIT04
Remote display kit with
8 ft remote display cable
SPDRDKIT08 PXSPDRDKIT08
Remote display kit with
12 ft remote display cable
SPDRDKIT12 PXSPDRDKIT12
For the dimensions of the cutout required to accommodate the remote display panel, see Figure 1 below.
Dimensions
2.69 (68.3)
5.38 (136.7)
8.90 (226.1)
4.45 (113.0)
4x R0.06 (1.6)
2.53 (64.3)
5.06 (128.6)
6x 0.13 (3.3)
9.38 (238.3)
4.69 (119.1)
Figure 1. Dimensions of the cutout required to accommodate the optional remote display panel
4 Technical Data TD01005006E
Effective September 2023
Eaton’s SPD Series for integration into
electrical distribution equipment
EATON www.eaton.com
4x Mounting 0.19 (4.8)
Bus 0.34 (8.6)
3.42 (86.9)
2.52(64.0)
3.45 (87.6)
0.95 (24.1)
Mounting 8.80 (223.5)
4.40 (111.8)
2.02 (51.2) 0.04 (1.0) 2.02 (51.2)
5.40 (137.2)
4.66 (118.4)
4x 0.22 (5.6) Mounting
4x #10–32 x 0.38 DP
Brass Terminals
3.42 (86.9)
Terminals 8.74 (222.0)
9.50 (241.3)
0.26 (6.6)
Mounting
3.42 (86.9)
3x 0.22 (5.6)
Bus Mounting
Figure 2. Dimensions of 50 kA through 200 kA integrated units for feature package 1 through 3
5.78 (146.8)
4.85 (123.2)
1.71 (43.4)
3.42 (86.9)
4x Mounting 2.52 (64.0)
9.50 (241.3)
Terminals 8.74 (222.0)
Mounting 8.80 (223.5)
3.42 (86.9)
5.40 (137.2)
4.66 (118.4)
4x 0.22 (5.6) Mounting
4x #10–32 x 0.38 DP
Brass Terminals
Mounting
3.42 (86.9)
Figure 3. Dimensions of 250 kA through 400 kA integrated units for feature package 1 through 3
5 Technical Data TD01005006E
Effective September 2023
Eaton’s SPD Series for integration into
electrical distribution equipment
EATON www.eaton.com
3.04 (77.2)
2.02 (51.2)
2.02 (51.2)
4.40 (111.8)
Mounting 8.80 (223.5)
3.42 (86.9)
Terminals 8.74 (222.0)
9.50 (241.3)
4.66 (118.4)
5.40 (137.1) Mounting
3.42 (86.9)
0.04 (1.0)
0.95 (24.1)
Bus 0.34 (8.5)
4X Mounting
0.19 (4.8)
2.52 (64.0)
3.45 (87.7)
0.26 (6.7)
3.42 (86.9)
3X 0.221 (5.6)
Bus mounting
4X #10–32 x 0.38 DP
Brass terminals
4X 0.218 (5.5)
Mounting
Ethernet port
Power Xpert SPD only
Figure 4. Dimensions of 50 kA through 200 kA integrated Power Xpert SPD units
3.04 (77.2) 3.42 (86.9)
Terminals 8.74 (222.0)
9.50 (241.3)
Mounting 8.80 (223.5)
Mounting
3.42 (86.9)
4.66 (118.4)
5.40 (137.1)
4X 0.22 (5.54)
Mounting
4X #10-32 x 0.38 DP
Brass terminals
4X Mounting
2.52 (63.9)
3.42 (86.9)
0.26 (6.7) 4.85 (123.1)
5.78 (146.8)
Ethernet port
Power Xpert SPD only
Figure 5. Dimensions of 250 kA through 400 kA integrated Power Xpert SPD units
6 Technical Data TD01005006E
Effective September 2023
Eaton’s SPD Series for integration into
electrical distribution equipment
EATON www.eaton.com
Performance data
ANSI/UL 1449 5th Edition voltage protection ratings
Voltage protection rating (VPR) data is included for both direct bus mounted units (catalog number ending with ‘A’) and units interfaced to the electrical assembly via a circuit breaker (catalog number ending with ‘B,’ ‘C,’ or ‘J’). Direct bus mounted units are available for installation within Eaton PRL1a, 2a, 3a, and 3e panelboards only.
Table 4. 50 kA direct bus mounted integrated unit VPR
Voltage code
Protection mode
L-N L-G N-G L-L
230L 1000 2000 1000 N/A
240S 500 1000 500 1000
208Y and 220Y
400Y and 480Y
600Y
500
1000
1200
1000
2000
2500
500
1000
1200
1000
2000
2500
240D
480D
600D
N/A
N/A
N/A
1000
2000
2500
N/A
N/A
N/A
900
2000
2500
240H 500 1000 500 1000
Table 5. 80–100 kA direct bus mounted integrated unit VPR Voltage code
Protection mode
L-N L-G N-G L-L
230L 1000 1200 1000 N/A
240S 500 600 500 900
208Y and 220Y
400Y and 480Y
600Y
500
1000
1200
600
1200
1500
500
1000
1200
900
1800
2500
240D
480D
600D
N/A
N/A
N/A
1000
1800
2500
N/A
N/A
N/A
900
1800
2500
240H 500 600 500 900
Table 6. 120–200 kA direct bus mounted integrated unit VPR Voltage code
Protection mode
L-N L-G N-G L-L
230L 900 1000 900 N/A
240S 500 600 500 800
208Y and 220Y
400Y and 480Y
600Y
500
900
1200
600
1000
1200
500
900
1200
800
1800
2500
240D
480D
600D
N/A
N/A
N/A
900
1800
2500
N/A
N/A
N/A
900
1800
2500
240H 500 600 500 800
Table 7. 250–300 kA circuit breaker interfaced integrated unit VPR Voltage code
Protection mode
L-N L-G N-G L-L
230L 1200 1200 900 N/A
240S 600a 700 600 1000
208Y and 220Y
400Y and 480Y
600Y
600a
1000
1500
700
1200
1500
600
900
1200
1000
1800
2500
240D
480D
600D
N/A
N/A
N/A
1000
1800
2500
N/A
N/A
N/A
1000
1800
2500
240H 600a 700 600 1000
a L-N VPR for 250–300 kA units containing the standard and standard with surge counter feature packages is 600 V. L-N VPR for units containing the basic feature package is 700 V.
All other VPR numbers reported in all tables represent the VPR for all feature packages.
Table 8. 50 kA circuit breaker interfaced integrated unit VPR Voltage code
Protection mode
L-N L-G N-G L-L
230L 1200 2000 1200 N/A
240S 700 1200 700 1200
208Y and 220Y
400Y and 480Y
600Y
700
1200
1500
1200
2000
2500
700
1200
1500
1200
2000
2500
240D
480D
600D
N/A
N/A
N/A
1200
2000
2500
N/A
N/A
N/A
1200
2000
2500
240H 700 1200 700 1200
Table 9. 80–100 kA circuit breaker interfaced integrated unit VPR Voltage code
Protection mode
L-N L-G N-G L-L
230L 1200 1200 1200 N/A
240S 700 700 700 1000
208Y and 220Y
400Y and 480Y
600Y
700
1200
1500
700
1200
1500
700
1200
1500
1000
1800
2500
240D
480D
600D
N/A
N/A
N/A
1200
2000
2500
N/A
N/A
N/A
1200
2000
2500
240H 700 700 700 1000
Table 10. 120–200 kA circuit breaker interfaced integrated unit VPR
Voltage code
Protection mode
L-N L-G N-G L-L
230L 1000 1200 1000 N/A
240S 700 700 600 1000
208Y and 220Y
400Y and 480Y
600Y
700
1000
1500
700
1200
1500
600
1000
1200
1000
1800
2500
240D
480D
600D
N/A
N/A
N/A
1000
2000
2500
N/A
N/A
N/A
1000
1800
2500
240H 700 700 600 1000
Table 11. 400 kA circuit breaker interfaced integrated unit VPR Voltage code
Protection mode
L-N L-G N-G L-L
230L 1000 1200 900 N/A
240S 700 700 600 1000
208Y and 220Y
400Y and 480Y
600Y
700
1000
1500
700
1200
1500
600
900
1200
1000
1800
2500
240D
480D
600D
N/A
N/A
N/A
1000
1800
2500
N/A
N/A
N/A
1000
1800
2500
240H 700 700 600 1000
7 Technical Data TD01005006E
Effective September 2023
Eaton’s SPD Series for integration into
electrical distribution equipment
EATON www.eaton.com
Specifications
Table 12. SPD Series specifications
Description Specification
Surge capacity ratings available 50, 80, 100, 120, 160, 200, 250, 300, 400 kA ratings available Nominal discharge current (In) 20 kA
Short circuit current rating (SCCR) 200 kA
SPD type Basic feature package = Type 1 (can also be used in Type 2 applications) Standard, standard with surge counter, and Power Xpert SPD feature packages = Type 2 Standard split-phase voltages available 120/240
Single-phase 230
Three-phase wye system voltages available 120/208, 127/220, 230/400, 277/480, 347/600 Three-phase delta system voltages available 240, 480, 600 Three-phase high-leg delta system voltages 120/240
Input power frequency 50/60 Hz, Power Xpert SPD tested to 60 Hz only Power consumption (basic units):
208Y, 220Y, 240S, 240D, and 240H voltage codes
400Y, 480Y, and 480D voltage codes
600Y and 600D voltage codes
0.5 W
1.1 W
1.3 W
Power consumption (standard and standard with surge counter units):
208Y, 220Y, 230L, 240S, 240D, and 240H voltage codes
400Y, 480Y, and 480D basic voltage codes
600Y and 600D voltage codes
0.6 W
1.7 W
2.1 W
Power consumption (Power Xpert SPD units):
208Y, 220Y, 230L, 240S, 240D, and 240H voltage codes
400Y, 480Y, and 480D voltage codes
600Y and 600D voltage codes
4 W
4 W
4 W
Phase protection:
208Y, 220Y, 230L, 240S, 240D, and 240H voltage codes
400Y, 480Y, and 480D voltage codes
600Y and 600D voltage codes
Single split-phase. . . . . . . . . . . L-N, L-G, N-G, L-L Single-phase. . . . . . . . . . . . . . . . L-N, L-G, N-G Three-phase wye. . . . . . . . . . . . L-N, L-G, N-G, L-L Three-phase delta. . . . . . . . . . . L-G, L-L
Three-phase high-leg delta. . . . L-N, L-G, N-G, L-L, H-N, H-G, H-L Maximum continuous operating voltage (MCOV):
208Y, 220Y, 240S voltage codes
230L
240H
400 and 480Y voltage codes
600Y
240D
480D
600D
150 L-N, 300 L-G, 150 N-G, 300 L-L
320 L-N, 640 L-G, 320 N-G
150 L-N, 300 L-G, 150 N-G, 300 L-L, 320 H-N, 470 H-G, 470 H-L 320 L-N, 640 L-G, 320 N-G, 640 L-L
420 L-N, 420 L-G, 420 N-G, 840 L-L
300 L-G, 300 L-L
640 L-G, 640 L-L
840 L-G, 840 L-L
Ports 1
Operating temperature –40 °F to +122 °F (–40 °C to +50 °C) Operating humidity 5% through 95%, noncondensing
Operating altitude Up to 16,000 ft (5000 m) Power Xpert SPD up to 6561 ft (2000 m) Seismic withstand capability Meets or exceeds the requirements specified in IBCT 2018, CBC 2007, and UBCT Zone 4 Weight 50–200 kA units approximately 3.5 lb (1.6 kg)
250–400 kA units approximately 7.0 lb (3.2 kg)
Form C relay contact ratings 150 Vac at 0.46 A, 30 Vdc at 1 A, terminal block connector rated 300 V, 16 A suitable for use with 30–12 AWG solid or stranded copper wire. Torque 5–7 lb-in Form C relay contact logic Power on, normal state—NO contact = OPEN, NC contact = CLOSED Power off, fault state—NO contact = CLOSED, NC contact = OPEN Real-time clock accuracy, Power Xpert SPD Synchronized when connected to a network via an ethernet cable, ±2 min/month at 25 °C when not connected to a network
EMI/RFI filtering attenuation (standard and standard with surge counter, and Power Xpert SPD)
Up to 50 dB from 10 kHz to 100 MHz
Ethernet port Data rate 100/10 Mbps, wire type: equal or exceed 5 UTP category 5, use of STP (shielded twisted pair) will improve EMI performance. Connector type: RJ45 modular, ground metal shield
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2023 Eaton
All Rights Reserved
Printed in USA
Publication No. TD01005006E / Z27889
September 2023
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
Eaton’s SPD Series for integration into
electrical distribution equipment
Technical Data TD01005006E
Effective September 2023
Table 12. SPD Series specifications (continued)
Description Specification
Agency certifications and approvals UL 1449 Standard for surge protective devices—Edition 5 UL 1283 Standard for electromagnetic interference filters—Edition 7 CSA C22.2 No. 269.2-17 Surge protective devices—Type 2—permanently connected—Edition 2 CSA C22.2 No. 269.4-17 Surge protective devices—Type 4—component assemblies—Edition 2 CSA C22.2 No. 8-13 Electromagnetic interference (EMI) filters—Edition 5 CSA C22.2 No. 60950-1-07 + AMD 1 AMD 2 Information technology equipment—safety. PT. 1, general requirements—Edition 2 UL 60950-1+ AMD 1 AMD 2 Information technology equipment—safety. PT. 1, general requirements—Edition 2 ICES and FCC part 15 subpart B Conducted & Radiated Emissions Class A Limits Tested to UL2900-1, Software Cybersecurity for Network-connected Products, in Eaton’s Cybersecurity test lab IEC 255-21-1 and IEC 255-21-2
IEEE 693-2018
Warranty 10 years, 15 years if you register on www.eaton.com/spd and click the warranty registration icon UL 96A compliant Yes
NFPA 780 compliant Yes —Models must meet maximum allowable VPR in NFPA Table 4.20.4 ROHS compliant Yes
Wire length and AWG Factory prewired with 18 inches of #10 AWG wire for mounting suffix B, C, and J Catalog number selection
Table 13. SPD Series catalog number configuration for units integrated into electrical distribution equipment SPD 250 480D 2 J
Series
SPD = Surge
protective
device
kA rating
050 = 50 kA per phase
080 = 80 kA per phase
100 = 100 kA per phase
120 = 120 kA per phase
160 = 160 kA per phase
200 = 200 kA per phase
250 = 250 kA per phase
300 = 300 kA per phase
400 = 400 kA per phase
Voltage code
230L = 230 single-phase (2W + G)
240S = 120/240 single split-phase
208Y = 120/208 wye (4W + G)
220Y = 127/220 wye (4W + G)
400Y = 230/400 wye (4W + G)
480Y = 277/480 wye (4W + G)
600Y = 347/600 wye (4W + G)
240D = 240 delta (3W + G)
480D = 480 delta (3W + G)
600D = 600 delta (4W + G)
240H = 240 high-leg delta (4W + G)
on 'B' phase a
Feature package
1 = Basic
2 = Standard
3 = Standard +
surge counter
4 = Power Xpert SPD
Application—integrated units b
A = Panelboards (PRL1a, 2a, 3a, 3e), direct bus mounted B = Switchgear (includes remote display) and will require a display cable referenced in Table 2
C = Panelboards (PRL1a, 2a, 3a, 3e, 4), switchboards, busway J = Motor control centers
Example: SPD250480D2J = SPD Series, 250 kA per phase, 480D voltage, standard feature package, motor control center application a Please consult the factory for 240 high-leg delta (4W + G) applications with high leg on ‘C’ phase. b Units used in PRL1a, 2a, 3a, and 3e panelboard applications are available in 50–200 kA ratings only. Use the ‘C’ option for PRL1a, 2a, 3a, and 3e panelboard applications when unit is connected through a circuit breaker.
Note: Please be aware that the Power Xpert SPD will not work in corner grounded Delta systems. The PXSPD needs voltage on each phase in order to operate properly.
If you have any questions or need additional
information, please contact the Eaton Technical
Resource Center at Eaton.com/SPD
or call 1-800-809-2772. You may also
submit inquiries via email: [email protected]
185 Lombardy Lane
Orinda, CA 94563
925-948-5360
Submittal for:
Project Name:
Product Description:
Bank of America Ukiah
Eaton 93PM UPS-L 208V 20 kW
Quantity: One
Date: October 20, 2025
Purchaser: OneSource
Job: TBD
Purchase Order: TBD
Submitted By: Jim Lyding (925) 948-5360
[email protected]
1 of 92
UPS REJECTED, UNIT TO BE AS
INDICATED ON DRAWINGS AND
INTEGRAL TO RACK SYSTEM AND
COOLING AS SHOWN ON
DRAWINGS. COORDINATE WITH
CLIENT IT
Table of Contents
Tab 1
Tab 2
Tab 3
Tab 4
Tab 5
Tab 6
Tab 7
Tab 8
Tab 9
Tab 10
Tab 11
Tab 12
Eaton Bill of Materials
Single Line Drawings
Outline Drawings
Input / Output Wiring Requirements
Battery Information
Input / Output Breaker Information
Control Wiring
Monitoring Information
Startup and Testing Scope of Work
Specifications
Warranties and Terms & Conditions
Product Brochure
2 of 92
Tab 1
Eaton
Bill of Materials
3 of 92
Bill of Material
One ( 1 ) Eaton Powerware 93PM-L 20 kVA / 20 kW (1 x 20 kW UPM) Uninterruptible Power Supply in 60 kW Frame.
Dimensions: 34.5” W x 44.3” D x 74.0” H (With Seismic Mounting Brackets) Weight: 1,819 lbs.
Notes:
Input Voltage: 208 VAC, 3W + G Into Rectifier / 4W + G Into Bypass Output Voltage: 208 VAC, 4W + G
DC Bus Voltage: 480 VDC
Input Current: 71 Amps Maximum Including Battery Recharge Output Current: 56 Amps
Static Switch: 100% Rated Continuous Duty
Cable Access: Top or Bottom
Up to 95% Efficiency in Double Conversion Mode
99% Efficiency in Energy Saver System Mode
Seismic Mounting Brackets
Gigabit Industrial Gateway Minislot SNMP Card
Industrial Relay Minislot Card
Environmental Monitoring Probe
Factory Test Report (Not Witnessed)
Heat Rejection: 6,125 BTU/Hour
One (1) Eaton 93PM SIAC-B Sidecar Integrated Accessory Cabinet - Bypass Dimensions: Included in UPS Dimensions Above
Weight: Included UPS Weight Above
Accessories:
Breakers Sized to Enable Field Upgrade up to 60 kW
Three Breaker Configuration
Bypass Input Breaker (BIB): 300A/3P, Eaton JG Series, 65Kaic, Part# KD3300WA06 Maintenance Bypass Breaker (MBP): 225A/3P, Eaton JG Series, 65kAIC, Part# FD3225L Maintenance Isolation Breaker (MIS): 225A/3P, Eaton JG Series, 65kAIC, Part# FD3225L 65 kAIC
Ships Attached to Left Side of UPS
Seismic Mounting Brackets
4 of 92
Onsite Services:
One ( 1 ) 7 x 24 Anytime Onsite Startup by Eaton; Includes Verification of Network Connectivity One ( 1 ) 7 x 24 Anytime Onsite Load Bank Test by Eaton; Includes Power Quality Metering of Output and IR Scanning. Includes 100' of Cable Rental.
One ( 1 ) Year Eaton PredictPulse Remote Monitoring
One ( 1 ) Year Warranty Parts and Labor for UPS, Batteries and Accessories; 7 x 24 Coverage and 8-Hour Response.
Factory Services:
Freight Prepaid and Included
F.O.B. Destination
Standard O&M Manual (Custom O&M per Specifications Which Have Not Been Contemplated Is Not Available)
Notes and Exceptions
• This UPS Does Not Include an Input Circuit Breaker
• This UPS Does Not Include a L21-20R Output Receptacle • This UPS Does Not Include an Integral Panel
5 of 92
Tab 2
Single Line
Drawings
6 of 92
56 Eaton 93PM-L SIAC Installation and Operation Manual P-164000822—Rev 03 Figure 23. Eaton 93PM-L 60 kW UPS with SIAC-B (Bypass Sidecar) System Oneline UPM 2 UPM 1
FUSE
UPS CABINET
BATTERY
SWITCHGEAR
BATTERY
CONVERTER
FUSE
FUSE
RECTIFIER
INVERTER
RECTIFIER
SWITCHGEAR
INVERTER
SWITCHGEAR
OPTIONAL
SINGLE-FEED
JUMPER
(UPS)
EXTERNAL
BATTERY
CABINET
BATTERY
BREAKER
STATIC
SWITCH
FUSE
E1,E2,E3
E6,E7,
E8,E12
E9,E10,
E11,E12
E4,E5
FUSE
BATTERY
SWITCHGEAR
BATTERY
CONVERTER
FUSE
FUSE
RECTIFIER
INVERTER
RECTIFIER
SWITCHGEAR
INVERTER
SWITCHGEAR
UPM 3
FUSE
BATTERY
SWITCHGEAR
BATTERY
CONVERTER
FUSE
FUSE
RECTIFIER
INVERTER
RECTIFIER
SWITCHGEAR
INVERTER
SWITCHGEAR
MAINTENANCE
ISOLATION
BREAKER
(2, 3, OR 4-BKR)
BYPASS
CABINET
AC INPUT TO
BYPASS
(SOURCE 2)
(SEE NOTE 2)
MAINTENANCE
BYPASS
BREAKER
AC
OUTPUT
TO
LOAD
BYPASS
INPUT
BREAKER
W/SHUNT
TRIP
RECTIFIER
INPUT
BREAKER
AC INPUT TO
RECTIFIER
(SOURCE 1)
E6,E7,
E8,E12
TIE BUS
E9, E10,
E11, E12
TIE BUS
SINGLE-FEED
JUMPER
(SIAC-B)
CB2 BATT
BREAKER
INTERNAL
BATTERY
4 STRINGS MAX
A B
D
C
NOTES:
1. AC INPUT TO RECTIFIER IS NOT USED IN SINGLE FEED CONFIGURATION.
2. DASHED LINES INSIDE OF UPS BOX INDICATE OPTIONAL UPM'S OR INTERNAL BATTERIES. CONFIGURABLE FROM 1-3 UPMS.
3. DASHED LINES INSIDE OF SIAC-B BOX INDICATE OPTIONAL COMPONENTS OR BYPASS JUMPER.
4. DASHED LINES OUTSIDE OF UPS OR SIAC-B BOX INDICATE OPTIONAL EQUIPMENT CABINETS.
5. BACKFEED PROTECTION IS NOT PROVIDED AS A PART OF UPS. CUSTOMER SUPPLIED BYPASS INPUT BREAKER WITH 48-60VDC SHUNT TRIP IS REQUIRED IF BYPASS SIDE CAR DOES NOT INCLUDE BIB BREAKER.
6. THE SINGLE-FEED JUMPER (UPS) IS FACTORY INSTALLED WHEN THE UPS IS ORDERED WITH A 2 OR 3 BREAKER SIDE CAR.
7. THE SINGLE FEED JUMPER (SIAC-B) IS FACTORY INSTALLED WHEN THE UPS IS ORDERED WITH A 4-BREAKER SIDE CAR. THE JUMPER MUST BE REMOVED FOR A DUAL FEED INSTALLATIONS. THE 4-BREAKER SIDE CAR IS ONLY AVAILABLE WITH A DUAL FEED UPS. ( SEE NOTE 7 )
UPS with Sidecar Oneline Schematics
7 of 92
Single-Feed
Jumper Included
BIB Breaker
Included in Bypass
SidecarPage 308 of 1066
Tab 3
Outline Drawings
8 of 92
UPS Installation Plan and Unpacking
3-6 Eaton 93PM-L UPS (20–60 kW, 208V) Installation and Operation Manual P-164000711—Rev 01 www.eaton.com/powerquality The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the front of the cabinet and outlets are on top or in the back of the cabinet. Allow clearance in front of and on top or in back of the cabinet for proper air circulation. The clearances required around the UPS cabinet are shown in Table 3-5.
Table 3-5. UPS Cabinet Clearances
From Front of Cabinet 914 mm (36") working space
From Top of Cabinet 457mm (18”)
From Top of Cabinet with Top Exhaust 457 mm (18") minimum clearance for ventilation From Back of Cabinet with Rear Exhaust 254 mm (10") minimum clearance for ventilation From Back of Cabinet with Top Exhaust None Required
From Right Side of Cabinet None Required
From Left Side of Cabinet None Required
9 of 92
18 Eaton 93PM-L SIAC Installation and Operation Manual P-164000822—Rev 03 Figure 7. 93PM-L 60 kW and 120 kW UPS with SIAC-B Dimensions (Front View) Dimensions are in millimeters [inches]
560 [22.0] 560 [22.0]
875 [34.45] 875 [34.45]
1880
[74.0]
Preparing the Site
10 of 92
Eaton 93PM-L SIAC Installation and Operation Manual P-164000822—Rev 03 21 Figure 10. 93PM-L 60 and 120 kW UPS with SIAC Floor Mounting Bracket Mounting Dimensions (Top View)
60 and 120 kW UPS with Bypass Sidecar (SIAC-B)
or 120 kW UPS with Top Entry Wiring Sidecar
(Top Exhaust Option Shown)
(Dimensions Mirrored for Sidecar Opposite Side)
60 kW UPS with Top Entry Sidecar
(Top Exhaust Option Shown)
(Dimensions Mirrored for Sidecar Opposite Side)
Dimensions are in millimeters [inches]
BOLTS
(12X) FRONT & REAR
M12 CLASS 8.8
TORQUE 87 Nm
or
1/2” GRADE 5
TORQUE 64 lb-ft
Bolts (12x) Front & Rear
M12 Class 8.8
Torque 87 Nm
or
1/2” Grade 5
Torque 64 lb-ft
11 of 92
Bypass Sidecar
(SIAC-B) to Ship
on Left Side of
UPS
Eaton 93PM-L UPS – 60 kW and 120 kW (208V) with Large Sidecar Floor Mounting Bracket Install Instructions P-164000866—Rev 02 1 Eaton 93PM-L UPS - 60 kW and 120 kW (208V) with Large Sidecar Floor Mounting Bracket Installation Instructions
Use these instructions to install front and rear floor mounting brackets to secure the Uninterruptible Power Supply (UPS) to the facility floor.
NOTE 1 This kit is used to support seismic installations where applicable.
NOTE 2 Refer to the applicable installation and operation manual supplied with UPS for dimensions and required clearances.
Floor Mounting Bracket Kit Contents
Front Mounting Brackets 2
Rear Mounting Brackets 2
Hex Bolts: Class 8.8, M12 or 1/2” Bolt = 87 Nm [64 lb-ft.] 12 NOTE The bracket-to-cabinet connecting bolts are Class 8.8, M8 Bolt = 27 Nm [20 lb-ft.] To install the brackets:
1. Unload and mechanically install the UPS according to the instructions in the applicable installation and operation manual.
2. Drill holes in the floor for the mounting brackets. Size the holes for the type of customer-supplied hardware being used to secure the bracket to the floor. See Figure 1 for the bracket mounting hole locations.
3. Remove the front floor mounting brackets from the kit and secure to the UPS and sidecar cabinet bases using the bolts supplied with the kit. See Figure 2 for mounting bracket installation location.
4. Remove the rear floor mounting brackets from the kit and secure to the UPS and sidecar cabinet bases using the bolts supplied with the kit. See Figure 3 for mounting bracket installation location.
5. Secure the cabinet to the floor with customer-supplied hardware.
For More Information
Refer to the Eaton 93PM-L UPS 20–60 kW (208V) Installation and Operation Manual, or the Eaton 93PM-L UPS 20-120 kW (208V) Installation and Operation Manual, for the following additional information:
• Installation instructions, including site preparation, planning for installation, wiring and safety information, and detailed illustrations of cabinets with dimensional and connection point drawings Visit www.eaton.com/powerquality or contact an Eaton service representative for information on how to obtain copies of these manuals.
12 of 92
2 Eaton 93PM-L UPS – 60 kW and 120 kW (208V) with Large Sidecar Floor Mounting Bracket Install Instructions P-164000866—Rev 02 Reference Images
Figure 1. Floor Mounting Bracket Mounting Hole Locations (Top and Bottom Views) 93PM-L with Left-Mounted Large Sidecar 93PM-L with Right-Mounted Large Sidecar Dimensions are in millimeters [inches]
NOTE: 93PM-L 60 kW and 120 kW UPS floor mounting brackets and locations are identical. 12X M12 OR
(12X 1/2” BOLT)
(6EA FRONT & REAR)
12X M12 OR
(12X 1/2” BOLT)
(6EA FRONT & REAR)
13 of 92
Eaton 93PM-L UPS – 60 kW and 120 kW (208V) with Large Sidecar Floor Mounting Bracket Install Instructions P-164000866—Rev 02 3 Figure 2. Floor Mounting Bracket Installation (Front View) 93PM-L with Left-Mounted Large Sidecar 93PM-L with Right-Mounted Large Sidecar NOTE: 93PM-L 120kW UPS with Large Sidecar shown
93PM-L 60 kW and 120 kW UPS floor mounting brackets and locations are identical 14 of 92
4 Eaton 93PM-L UPS – 60 kW and 120 kW (208V) with Large Sidecar Floor Mounting Bracket Install Instructions P-164000866—Rev 02 Figure 3. Floor Mounting Bracket Installation (Rear View) 93PM-L with Left-Mounted Large Sidecar 93PM-L with Right-Mounted Large Sidecar NOTE 1: 93PM-L 120kW UPS with Large Sidecar shown
NOTE 2: 93PM-L 60 kW and 120 kW UPS floor mounting
brackets and locations are identical
Getting Help
If help is needed with any of these instructions, please call the Customer Reliability Center at:
United States: 1-800-843-9433
Canada: 1-800-461-9166 ext 260
All other countries: Call your local service representative Please use the following e-mail address for comments, suggestions, or to report an error in these instructions:
[email protected]
Eaton is a registered trademark of Eaton or its subsidiaries and affiliates. All other trademarks are property of their respective companies.
©Copyright 2019–2020 Eaton, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton. 15 of 92
32 Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 06 Figure 14. UPS with Left or Right-Mounted SIAC-B Center of Gravity “C”
“A”
“B”
Table 9. UPS with Bypass Sidecar (SIAC-B) - Center of Gravity dimensions Weight and Center of Gravity
Dimensions mm [in]
See Figure 14.
Weight
Model kg [lb]
Number
of
UPMs
Number of Battery
Strings A B C
Eaton 93PM-L
60 kW UPS with
Left-Mounted
Sidecar
(2 Breakers)
1 UPM
Installed
0 Battery Strings 940 [37.0] 563 [22.2] 438 [17.2] 405
(892)
2 Battery Strings 959 [37.8] 561 [22.1] 494 [19.4] 630
(1387)
3 Battery Strings 986 [38.8] 559 [22.0] 507 [20.0] 719
(1582)
4 Battery Strings 1023 [40.3] 557 [21.9] 516 [20.3] 808 (1777)
2 UPMs
Installed
0 Battery Strings 986 [38.8] 564 [22.2] 450 [17.7] 437
(961)
(1+1), 2 Battery Strings 988 [38.9] 562 [22.1] 499 [19.6] 662 (1456)
3 Battery Strings 1011 [39.8] 559 [22.0] 510 [20.1] 750 (1651)
UPS Installation Plan and Unpacking
16 of 92
34 Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 06 Table 9. UPS with Bypass Sidecar (SIAC-B) - Center of Gravity dimensions (Continued) Weight and Center of Gravity
Dimensions mm [in]
See Figure 14.
Weight
Model kg [lb]
Number
of
UPMs
Number of Battery
Strings A B C
Left-Mounted
Sidecar
(3 Breakers)
2 Battery Strings 960 [37.8] 558 [22.0] 483 [19.0] 650
(1429)
3 Battery Strings 987 [38.9] 556 [21.9] 496 [19.5] 738
(1624)
4 Battery Strings 1022 [40.2] 556 [21.9] 507 [20.0] 827 (1819)
2 UPMs
Installed
0 Battery Strings 987 [38.9] 559 [22.0] 435 [17.1] 456
(1003)
(1+1), 2 Battery Strings 989 [38.9] 559 [22.0] 488 [19.2] 681 (1498)
3 Battery Strings 1011 [39.8] 557 [21.9] 500 [19.7] 770 (1693)
4 Battery Strings 1043 [41.1] 555 [21.9] 510 [20.1] 858 (1888)
3 UPMs
Installed
0 Battery Strings 1034 [40.7] 560 [22.0] 446 [17.6] 487 (1072)
(2+1), 3 Battery Strings 1039 [40.9] 558 [22.0] 504 [19.8] 801 (1762)
4 Battery Strings 1066 [42.0] 556 [21.9] 513 [20.2] 890 (1957)
Eaton 93PM-L
60 kW UPS with
Right-Mounted
Sidecar
(3 Breakers)
1 UPM
Installed
0 Battery Strings 943 [37.1] 558 [22.0] 451 [17.8] 425
(934)
2 Battery Strings 960 [37.8] 558 [22.0] 392 [15.4] 650
(1429)
3 Battery Strings 987 [38.9] 556 [21.9] 379 [14.9] 738
(1624)
4 Battery Strings 1022 [40.2] 556 [21.9] 368 [14.5] 827 (1819)
2 UPMs
Installed
0 Battery Strings 987 [38.9] 559 [22.0] 440 [17.3] 456
(1003)
(1+1), 2 Battery Strings 989 [38.9] 559 [22.0] 387 [15.2] 681 (1498)
3 Battery Strings 1011 [39.8] 557 [21.9] 375 [14.8] 770 (1693)
4 Battery Strings 1043 [41.1] 555 [21.9] 365 [14.4] 858 (1888)
UPS Installation Plan and Unpacking
17 of 92
S DS = 1.83 g
S DS = 1.83 g
I P = 1.5
TRU Compliance, by Structural Integrity Associates, Inc. 5215 Hellyer Ave., Suite 210
San Jose, CA 95138
844-TRU-0200
[email protected]
Telephone:
Decision Maker:
Company:
License Number:
Address:
For more information, please contact the Equipment Manufacturer or the Seismic Certification Agency.
Seismic Certification Parameters:
Compliance Report Notes:
Importance Factor:
Mounting:
Seismic Level(s):
CBC 2019, IBC 2018
Shake table testing
Base mounted - rigid
Refer to 1800524-CR-001 for all requirements, limitations, and special conditions of approval.
Seismic Certification Agency:
This ISO 17065 Certification fulfills the requirements of the TRU Compliance Certification Standard for Seismic, Wind, and Physical Security Performance, Revision 4, dated October 2, 2019 plus the standards referenced above.
Building Code:
ICC-ES AC156 (2015)
for z/h = 1.0 (rooftop installation)
for z/h = 0.0 (ground level installation)
Andy Coughlin, SE
S6082 (California)
Structural integrity and functional compliance verified following testing.
Specific products included in this special seismic certification are outlined in 1800524-CR-001, issued by TRU Compliance, a division of Structural Integrity Associates, Inc. Detailed information relating to certification levels, construction details, options, and mounting arrangements are included therein.
This compliance report is limited by, and necessarily dependent on, the construction of the product and the accuracy of the information provided by the Equipment Manufacturer. Therefore, this report is valid only for the components and systems as they were configured and manufactured at the time of testing or evaluation. Any alterations to the product or its components could result in a decrease in seismic performance and thus render the resultant conclusions void.
SPECIAL SEISMIC CERTIFICATION
COMPLIANCE REPORT SUMMARY
1800524-CRS-001 R4
Manufacturer:
Model Line:
Product Type:
Equipment Manufacturer:
Eaton
93 PM, 93 PM-L, 93 PM IAC, 93 PM IBC Uninterruptible Power Supply (UPS) For specific models included in this seismic certification, see 1800524-CR-001.
UPS
Certification Basis:
Test Criteria:
Verify current listings at www.trucompliance.com/certification-database Issue Date: July 30, 2020
Expiration Date: December 31, 2025
E-mail:
Company:
Telephone:
Website:
Eaton
3301 Spring Forest Road
Raleigh, NC 27616
Address:
919-878-6081
www.eaton.com
TRU Compliance, by Structural Integrity Associates, Inc. 18 of 92
844-TRU-0200 | [email protected]
Tab 4
Input / Output
Wiring
Requirements
19 of 92
72 Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 06 Figure 29. UPS with Bypass Sidecar (SIAC-B) Conduit and Wire Entry Locations Top View
(Top Vent Option)
Front
Conduit Plates:
Interface Wiring
Conduit Plate:
AC Input/Output
and
DC Input
Bottom View
Conduit Plate:
DC Input
Conduit Plate:
AC Input/Output
NOTE: Remove panels to drill or punch conduit holes.
UPS System Installation
Bypass Sidecar Will Ship on LEFT Side of UPS -- Right Side Shown Here 20 of 92
Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 06 75 Figure 31. Eaton 93PM-L with SIAC-B (3-Breaker) Power Terminal Locations
MBP MIS
MAINTENANCE
BYPASS
BREAKER
MAINTENANCE
ISOLATION
BREAKER
GROUND
COMPRESSION
LUGS
BYPASS INPUT
PHASE A (E6)
PHASE B (E7)
PHASE C (E8)
OUTPUT NEUTRAL (E12)
BYPASS NEUTRAL (E12)
BYPASS INPUT
BREAKER (BIB)
W/ SHUNT TRIP
BIB
E9
E10
E11
E6
E7
E8
AC OUTPUT TO LOAD
PHASE A (E9)
PHASE B (E10)
PHASE C (E11)
BATTERY BREAKER
PRESENT ONLY WITH
INTERNAL BATTERIES
INTERNAL BATTERIES
QTY 0 OR 2-4 STRINGS
CONFIGURABLE
BATTERY INPUT
E4 (+)
BATTERY INPUT
E5 (-)
( 2X ) GROUND STUDS
FOR CABINET TO
CABINET WIRING
UPS System Installation
21 of 92
Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 06 69 Figure 27. Power Terminal Locations
E1/E2/E3
AC INPUT
TO UPS
RECTIFIER
E6/E7/E8/E12
AC INPUT
TO BYPASS
E9/E10/E11/E12
AC OUTPUT
TO LOAD
BATTERY INPUT
E4 (+)
BATTERY INPUT
E5 (-)
(2X) GROUND STUDS
FOR CABINET TO
CABINET WIRING
BATTERY BREAKER
PRESENT ONLY WITH
INTERNAL BATTERIES
BATTERY SECTION
0 OR 2-4 BATT STRINGS
CONFIGURABLE
GROUND
COMPRESSION
LUGS
UPS System Installation
22 of 92
70 Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 06 Figure 28. Eaton 93PM-L UPS Power Terminal Detail
Phase A (E1)
Phase B (E2)
Phase C (E3)
Neutral (E12)
Phase C (E8)
Phase B (E7)
Phase A (E6)
AC Input to
UPS Rectifier
AC Input to
UPS Bypass
AC Output to
Critical Load
Phase A (E9)
Phase B (E10)
Phase C (E11)
Neutral (E12)
DC Input from Battery - (E5)
DC Input from Battery + (E4)
Cabinet Equipment Cabinet
Bonding Post Ground Terminals Bonding Post
UPS System Installation
23 of 92
Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 05 33 Figure 15. Remote EPO Switch Dimensions
115.8
[4.56]
114.3
[4.50]
0.87 [0.22] 88.9
[3.50]
1.57 [0.40]
95.3 [3.57]
1/2” Knockout Pattern
(Typical 5 sides)
Needed to
remove key
Dimensions are in millimeters (inches)
3.3 UPS System Power Wiring Preparation
Read and understand the following notes while planning and performing the installation:
WARNING
As a result of the connected loads high leakage current is possible. Connection to earth ground is required for safety and proper product operation. Do not check UPS operation by any action that includes removal of the earth (ground) connection with loads attached.
• Refer to national and local electrical codes for acceptable external wiring practices. • To allow for future power upgrades, Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated UPS kW frame size instead of the derated kW ordered. Wiring for the maximum kW frame size will allow a full power rating upgrade without having to modify the site wiring infrastructure.
• For external wiring, use 75°C copper wire.
!
IMPORTANT
This product has been evaluated for use with copper wire only. For external wiring, use only 75°C copper wire.
Wire sizes listed in Table 9 through are for copper wiring only. If wire is run in an ambient temperature greater than 40°C, larger size wire may be necessary. Wire sizes are based on using the specified breakers.
• The AC output and output ground wiring to the critical load should be sized the same as the UPS rectifier, bypass, and rectifier and bypass ground wiring if the recommended output breaker listed in Table 18 is not installed in the system.
UPS Installation Plan and Unpacking
24 of 92
34 Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 05 • Recommended wire sizes are based on NFPA National Electrical Code® (NEC®)70 Table 310.15(B)(16) 75° C ampacity with 40°C ambient correction factors.
• The neutral conductor is sized the same as the phase conductor for balanced and resistive loads. Nonlinear loads, up to the maximum of 1.5x the load current, require a larger neutral conductor and should be sized in accordance with NFPA NEC 70 Article 310.15(B)(5). • Connect rectifier input to a 3 wire, grounded Wye source. A neutral conductor is not used from the rectifier source.
• Supported single source, single or dual feed power sources:
– 3-wire grounded Wye (TN,TT) – Rectifier Input
– 4-wire grounded Wye (TN,TT) – Bypass Input
• Supported dual source, dual feed power sources:
– 3-wire grounded Wye (TN, TT) – Rectifier Input
– 4-wire grounded Wye (TN, TT) – Bypass Input
CAUTION
SINGLE HIGH IMPEDANCE GROUND SOURCE – In North American installations, the neutral conductor from the high impedance ground source of supply CANNOT be used. • Phase rotation must be clockwise starting with phase A (rotation A, B, C). • If installing an external maintenance bypass, all feeds to the UPS including the Rectifier Input Breaker (RIB) (if installed) must have a service disconnect independent of the maintenance bypass power path. Most maintenance bypass solutions provide UPS input feeds derived from but isolated from the maintenance bypass power path. If the maintenance bypass solution being installed does not provide such functionality, DO NOT use a single feeder breaker to supply both the UPS and the maintenance bypass. • The Eaton 93PM-L UPS provides backfeed detection and protection through a shunt trip mechanism of the bypass input breaker.
!
IMPORTANT
If an Eaton 93PM-L UPS is ordered with:
– a 3 or 4 breaker SIAC-B, the system as shipped from the factory will have the bypass protection pre-wired and tested.
– a 3 or 4 breaker wall-mount or floor mount bypass optional accessory kit; it will be packaged with all of the accessories for the bypass input breaker (BIB) but must be field installed.
NOTE During installation, the installer needs to connect the Bypass Shunt Trip interface connections. See paragraph 4.6.5 Bypass Shunt Trip Connections. – a 2-breaker bypass, the customer must provide their own bypass, or if the customer does not use a bypass, the upstream bypass input source must have a 48VDC shunt trip installed and wired back to the UPS to provide backfeed protection. The customer is also required to provide special electrical labeling outlined in the electrical code.
NOTE During installation, the installer needs to connect the Bypass Shunt Trip interface connections. See paragraph 4.6.5 Bypass Shunt Trip Connections.
UPS Installation Plan and Unpacking
25 of 92
40 Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 06 For external wiring recommendations, including the minimum AWG size of external wiring, see Table 10 through Table 13. Wire sizes listed are for copper wiring only. For external wiring, use only 75°C copper wire.
Table 10. Input/Output Ratings and Wiring Recommendations: 10– 30 kW (208/208) Basic Unit Rating
Units Rating 50/60 Hz
kW 10 20 30
Input and Output Voltage Volts 208/208 208/208 208/208
AC Input to UPS Rectifier (0.99 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground A
Amps 36 71 107
Minimum Conductor Size (Phase A, B, and C)
Number per Phase
AWG or kcmil
(each)
8 (1)
3 (1)
1/0
(1)
Minimum Conductor Size (Ground)
Number
– AWG or kcmil
(each)
10 (1)
8 (1)
6 (1)
AC Input to UPS Bypass (Four-Wire, Dual-Feed)
Full Load Current (3) Phases – see Note, (1) Ground
B
Amps 36 71 107
Neutral Current Amps 36 71 107
Minimum Conductor Size (Phase A, B, and C)
Number per Phase
AWG or kcmil
(each)
6 (1)
2 (1)
2/0
(1)
Neutral Wire Size
Number
AWG or kcmil
(each)
6 (1)
2 (1)
2/0
(1)
Minimum Conductor Size (Ground)
Number
– AWG or kcmil
(each)
10 (1)
8 (1)
6 (1)
DC Input from External Battery (Line-Up-and-Match Eaton 93PM-L IBC-SW, IBC-LW or IBC-LHW) For Line-Up-and-Match wiring refer to Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded or Eaton 93PM Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate DC Input from External Battery (Standalone
Eaton 93PM-L IBC)
(1) Positive, (1) Negative, (1) Ground
C
Total Amps 23 45 68
Minimum Conductor Size (Phase Positive and
Negative)
Number per Pole
AWG or kcmil
(each)
10 (1)
6 (1)
4 (1)
Minimum Conductor Size (Ground)
Number
– AWG or kcmil
(each)
10 (1)
10 (1)
8 (1)
AC Output to Critical Load (Four-Wire)
Full Load Current (3) Phases – see Note, (1) Ground
D
Amps 28 56 83
Neutral Current Amps 28 56 83
Minimum Conductor Size (Phase A, B, and C)
Number per Phase
AWG or kcmil
(each)
8 (1)
4 (1)
1 (1)
Neutral Wire Size
Number
AWG or kcmil
(each)
8 (1)
4 (1)
1 (1)
UPS Installation Plan and Unpacking
26 of 92
Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 06 41 Table 10. Input/Output Ratings and Wiring Recommendations: 10– 30 kW (208/208) (Continued) Minimum Conductor Size (Ground)
Number
– AWG or kcmil
(each)
10 (1)
8 (1)
6 (1)
NOTE Callout letters A, B, C and D map to Figure 54, Figure 55, and Figure 56 93PM-L System Oneline Schematics.
Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM-L Integrated Battery Cabinet (IBC).
Eaton recommends installing the UPS using wiring and external overcurrent protection breakers sized for the fully rated UPS kW frame size installed.
UPS Installation Plan and Unpacking
27 of 92
Eaton 93PM-L SIAC Installation and Operation Manual P-164000822—Rev 03 27 Table 8. External Input Power Cable Terminations for the 93PM-L 60 kW and 120 kW SIAC-B Terminal
Function Terminal Function
Bus Landings
(using back-to-back
lugs)
Tightening
Torque
Nm (lb in)
Screw Size
and Type
AC Input to RIB
–
Source 1
(4–breaker
Dual-Feed
version only)
E1
(RIB-1)
Phase
A
60 kW UPS
(See Note)
2 – 2/0 to 250
or
31 (275) 5/16" Hex
1 – 2/0 to 500 42 (375) 3/8" Hex
120 kW UPS 2 – 2 to 500 42 (375) 5/16" Hex
E2
(RIB-3)
Phase
B
60 kW UPS
(See Note)
2 – 2/0 to 250
or
31 (275) 5/16" Hex
1 – 2/0 to 500 42 (375) 3/8" Hex
120 kW UPS 2 – 2 to 500 42 (375) 5/16" Hex
E3
(RIB-5)
Phase
C
60 kW UPS
(See Note)
2 – 2/0 to 250
or
31 (275) 5/16" Hex
1 – 2/0 to 500 42 (375) 3/8" Hex
120 kW UPS 2 – 2 to 500 42 (375) 5/16" Hex
AC Input to
Maintenance
Bypass —
Source 2
E6 Phase A 4 – 2 bolt mounting 35 (310) M12 Hex
E7 Phase B 4 – 2 bolt mounting 35 (310) M12 Hex
E8 Phase C 4 – 2 bolt mounting 35 (310) M12 Hex
E12 Neutral 8 – 2 bolt mounting 35 (310) M12 Hex
AC Output to
Critical Load
E9 Phase A 4 – 2 bolt mounting 35 (310) M12 Hex
E10 Phase B 4 – 2 bolt mounting 35 (310) M12 Hex
E11 Phase C 4 – 2 bolt mounting 35 (310) M12 Hex
E12 Neutral 8 – 2 bolt mounting 35 (310) M12 Hex
Building, InterCabinet, and
Load Ground
Ground Ground 14 - #14-1/0 pressure
termination
5.1 (45) Slotted
NOTE The RIB breaker has 2 holes (or bores) to accept the input wiring; each with a set screw to secure the wiring. The 60 kW RIB breaker has a small bore with a 5/16” set screw which can accept wiring from 2/0 to 250 MCM. The larger bore with a 3/8” set screw can accept wiring from 2/0 to 500 MCM. The 120 kW RIB breaker has two same sized bores with 5/16” set screws.
The power wiring terminals for the Eaton 93PM-L 60 kW and 120 kW SIAC-B are pressure terminations. The power wiring connections for this equipment are UL and CSA rated. See Table 8 for external power cable terminations.
Figure 14 shows the locations of the SIAC-B power cable terminals.
Preparing the Site
Input and Output for Bypass Sidecar
28 of 92
44 Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 05 !
IMPORTANT
If a 4-pole Automatic Transfer Switch (ATS) is used to connect the UPS to a generator or alternative input source, it may interrupt the UPS input neutral during its transition between sources. This UPS should always have an input source neutral connected at the bypass input terminals. This neutral must be continuous and uninterrupted; even if there are no phase-to-neutral loads connected to the UPS output. If the UPS is fed from a 4-pole ATS that interrupts the neutral, a delta-to-wye isolation transformer, with its secondary neutral bonded to ground, must be placed in line with the bypass input of the UPS. This will provide an uninterrupted neutral to the UPS, regardless of the position of the ATS neutral contact.
Note: if an overlapping neutral or make-before-break ATS switch is used, the neutrals must overlap for a minimum of 50 msec during the transition. In these cases, a transformer is not needed.
Power wiring terminals E1 through E11 are 2-hole bus bar mountings for standard NEMA 2-hole barrel lugs.
The power wiring connections for this equipment are rated at 90°C. See Table 13 for external power cable terminations, Table 14 for supplied external wiring terminal hardware, and Table 15 for recommended installation parts and tools not supplied by Eaton.
Figure 27 and Figure 28, show the location of the UPS power cable terminals.
For a detailed view of the power terminals for the 2, 3 and 4-Breaker SIAC-B configurations, see Figure 30 for the 2–Breaker SIAC-B, Figure 31 for the 3–Breaker SIAC-B, and Figure 32 for the 4–Breaker SIAC-B.
Table 13. UPS External Power Cable Terminations
Terminal Function Terminal Function
Bus Landings
(using back-toback lugs)
Tightening Torque
Nm (lb in)
Screw Size and
Type
AC Input to UPS
Rectifier
E1 Phase A 4 – 2 bolt mounting 35 (310) M12 Hex
E2 Phase B 4 – 2 bolt mounting 35 (310) M12 Hex
E3 Phase C 4 – 2 bolt mounting 35 (310) M12 Hex
AC Input to Bypass E6 Phase A 4 – 2 bolt mounting 35 (310) M12 Hex E7 Phase B 4 – 2 bolt mounting 35 (310) M12 Hex
E8 Phase C 4 – 2 bolt mounting 35 (310) M12 Hex
E12 Neutral 8 – 2 bolt mounting 35 (310) M12 Hex
AC Output to Critical
Load
E9 Phase A 4 – 2 bolt mounting 35 (310) M12 Hex
E10 Phase B 4 – 2 bolt mounting 35 (310) M12 Hex
E11 Phase C 4 – 2 bolt mounting 35 (310) M12 Hex
E12 Neutral 8 – 2 bolt mounting 35 (310) M12 Hex
DC Input from Battery E4 Battery (+) 4 – 2 bolt mounting 35 (310) M12 Hex E5 Battery (-) 4– 2 bolt mounting 35 (310) M12 Hex
Customer Ground Ground Ground 14 - #14-1/0
pressure termination
5.1 (45) Slotted
NOTE Customer ground, sized in accordance with NEC Table 250.122, can be run in any conduit listed in Table 16.
UPS Installation Plan and Unpacking
Input and Output for UPS
29 of 92
Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 05 45 Table 14. Supplied External Wiring Terminal Hardware Kit Part Size Quantity Terminal Used On
Bolt, Grade 5 M12 x 35 mm 60 Rectifier Input, Bypass Input, Battery Input, and Output to Critical Load Flat Washer M12 60 Rectifier Input, Bypass Input, Battery Input, and Output to Critical Load Conical
Washer
M12 60 Rectifier Input, Bypass Input, Battery Input, and Output to Critical Load NOTE For additional information (including part numbers and manufacturer information) and/or assistance contact an Eaton service representative (see paragraph 1.9 Getting Help).
Table 15. Recommended Installation Parts and Tools (Not Supplied by Eaton) Part Size Quantity Notes
Long Barrel 2-Hole Lug
6 AWG
As Required Copper wire only
4 AWG
2 AWG
1 AWG
1/0 AWG
2/0 AWG
3/0 AWG
4/0 AWG
250 MCM
300 MCM
350 MCM
500 MCM
Manual Hydraulic Crimp Tool 14 Ton 1
Die Set N/A 1
NOTE For additional information (including part numbers and manufacturer information) and/or assistance contact an Eaton service representative (see paragraph 1.9 Getting Help).
Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See Table 16 for conduit recommendations.
Per NEC article 300, 3(B), all three-phase conductors must be run in the same conduit. A ground wire must be run in the same conduit as the phase conductors.
When running parallel wires in multiple conduits a ground wire must be run in each conduit in accordance with NEC Table 250.122.
Conduit is sized to accommodate one ground conductor per conduit, sized in accordance with NEC Table 250.122.
Conduit sizes listed are for copper wiring only.
UPS Installation Plan and Unpacking
30 of 92
UPS Installation Plan and Unpacking
Eaton 93PM-L UPS (20–60 kW, 208V) Installation and Operation Manual P-164000711—Rev 01 www.eaton.com/powerquality 3-27 Table 3-12. UPS External Power Cable Terminations for the Eaton 93PM-L 60 Terminal Function Terminal Function
Bus Landings
(using back-to-back lugs)
Tightening Torque
Nm (lb in) Screw Size and Type
AC Input to UPS Rectifier - UPS E1 E1 2 – 2 bolt mounting 35 (310) M12 Hex E2 E2 2 – 2 bolt mounting 35 (310) M12 Hex
E3 E3 2 – 2 bolt mounting 35 (310) M12 Hex
AC Input to RIB - SIAC-B
(4 Breaker SIAC-B Dual Feed Only)
RIB-1 Phase A Breaker - Step Lug 42 (375) 5/16” Hex
RIB-3 Phase B Breaker - Step Lug 42 (375) 5/16” Hex
RIB-5 Phase C Breaker - Step Lug 42 (375) 5/16” Hex
AC Input to Bypass E6 Phase A 2 – 2 bolt mounting 35 (310) M12 Hex E7 Phase B 2 – 2 bolt mounting 35 (310) M12 Hex
E8 Phase C 2 – 2 bolt mounting 35 (310) M12 Hex
E12 Neutral 4 – 2 bolt mounting 35 (310) M12 Hex
AC Output to Critical Load E9 Phase A 2 – 2 bolt mounting 35 (310) M12 Hex E10 Phase B 2 – 2 bolt mounting 35 (310) M12 Hex
E11 Phase C 2 – 2 bolt mounting 35 (310) M12 Hex
E12 Neutral 4 – 2 bolt mounting 35 (310) M12 Hex
DC Input from Battery E4 Battery (+) 4 – 2 bolt mounting 35 (310) M12 Hex E5 Battery (-) 4 – 2 bolt mounting 35 (310) M12 Hex
Customer Ground Ground Ground 6 - #14-1/0 pressure termination 5.1 (45) Slotted NOTE Customer ground, sized in accordance with NEC Table 250.122, can be run in any conduit listed in Table 3-15.
Table 3-13. Supplied External Wiring Terminal Hardware Kit Part Size Quantity Terminal Used On Eaton Part Number
Bolt, Grade 5 M12 x 35 mm 34 Rectifier Input, Bypass Input, Battery Input, and Output to Critical Load 180190078-110 Flat Washer M12 34 Rectifier Input, Bypass Input, Battery Input, and Output to Critical Load 180500036-120 Conical Washer M12 34 Rectifier Input, Bypass Input, Battery Input, and Output to Critical Load 180500037-120 31 of 92
Tab 5
Battery Information
32 of 92
Powerware series
Eaton 12V 27W Battery
PWHR1227W2
Features
• Designed for high power density applications
• Small volume, lightweight and high discharge efficiency • Can be used for more than 260 cycles at 100% discharge in cycle service
• UL-recognized components under UL924 and certified by ISO 9001 and ISO 14001
• Exclusive two-year battery parts coverage and one-year battery labor coverage
CONSTANT POWER DISCHARGE CHARACTERISTICS: WATTS/CELL (77°F, 25°C) End point volts/cell 2 min 4 min 6 min 8 min 10 min 15 min 20 min 30 min 60 min 90 min
1.85V 63 48 40 35 31 24 19 14 8 6
1.80V 67 52 43 36 32 26 20 15 9 6
1.75V 71 55 45 38 33 26 21 15 9 6
1.70V 76 58 47 39 34 27 21 15 9 6
1.67V 78 60 48 40 35 27 21 15 9 6
1.60V 84 64 51 42 37 27 21 15 9 6
All mentioned values are average values per battery per cell.
Tolerance: X <6 min (+15% ~ -15%), 6 min X < 10 min (+12%~ -12%), 10 min X < 60 min (+8% ~ -8%), X 60 min (+5% ~ -5%) DIMENSIONS [H x W x D, in (mm)]
33 of 92
Eaton, Powerware and PowerChain
Management are trade names, trademarks,
and/or service marks of Eaton Corporation
or its subsidiaries and affiliates. All other
trademarks are the property of their respective owners. © 2008 Eaton Corporation
All Rights Reserved
Printed in USA
BAT13FXA
December 2008
UNITED STATES
8609 Six Forks Road
Raleigh, NC 27615 U.S.A.
Toll Free: 1.800.356.5794
or 919.872.3020
www.powerware.com/batteries
CANADA
Ontario: 416.798.0112
Toll free: 1.800.461.9166
LATIN AMERICA
Argentina: 54.11.4124.4000
Brazil: 55.11.3616.8500
México: 52.55.9000.5252
Portugal: 55.11.3616.8500
EUROPE/MIDDLE EAST/AFRICA
Denmark: 45.3686.7910
Finland: 358.94.52.661
France: 33.1.6012.7400
Germany: 49.0.7841.604.0
Italy: 39.02.66.04.05.40
Norway: 47.23.03.65.50
Sweden: 46.8.598.940.00
United Kingdom: 44.1753.608.700
ASIA PACIFIC
Australia: 61.2.9693.9366
New Zealand: 64.0.3.343.3314
China: 86.21.6361.5599
HK/Korea/Taiwan: 852.2745.6682
India: 91.11.2649.9414 to 18
Singapore/SEA: 65.6825.1668
Technical specifications
Cells per unit 6
Voltage per unit 12
Capacity 27W @ 15-minute rate to 1.67V per cell @ 77°F (25°C) Weight Approximately 4.34 lb (1.97 kg)
Maximum 130A (5 sec)
discharge current
Internal Approximately 19 mΩ
resistance
Operating Discharge: 5°F~122°F (-15°C~50°C)
temperature Charge: 5°F~104°F (-15°C~40°C)
range Storage: 5°F~104°F (-15°C~40°C)
Nominal 77°F ± 5°F (25°C ± 3°C)
operating
temperature range
Float charging 13.5 to 13.8 Vdc/unit
voltage Average at 77°F (25˚C)
Recommended 2.7A
maximum
charging current
limit
Equalization and 14.4 to 15.0 Vdc/unit
cycle service Average at 77°F (25˚C)
Self discharge Batteries can be stored for six months at 77°F (25°C).
Please charge batteries before using. For higher
temperatures the time interval will be shorter. Voltage test prior to battery installation is recommended.
Terminal F2- Faston Tab 250
Container ABS UL94-HB/File E50263
material Flammability resistance of UL94-V0/File E88637 is available upon request.
34 of 92
Spec sheet
Physical properties of Eaton batteries
Battery type 93PML Internal 93PM Internal E12 E20 E28 E33 E39 E54 E57 E65 Eaton listed part numbers: HR1227W PWHR1234W2FR PWHR12120W3FR PWHR12200W4FR PWHR12280W4FR PWHR12330W4FR PWHR12390W4FR PWHR12540W4FR PWXP502W4FR PWXP651W4FR Internal part numbers: 58700033 58700036-001 153302078-002 153302090-002 153302086-002 153302088-002 153302085-002 P-153700004-002 P-153000034-002 P-153000036-002 Electrolyte (gal / battery) 0.070 0.099 0.368 0.821 1.086 1.463 1.520 2.058 1.515 1.975 H2SO4 Weight (lb / cell) 0.057 0.073 0.296 0.438 0.579 0.816 0.849 1.149 0.807 1.052 Lead (lb / cell) 0.516 0.722 2.532 4.439 6.851 7.433 8.526 11.301 9.932 12.980 Battery weight (lbs) 4.41 5.95 22.49 38.14 56.88 65.26 72.75 96.78 81.35 105.60 Connection 0.250 inch
(6.35 mm) tab
0.250 inch
(6.35 mm) tab
M5 M6 M6 M6 M6 M6 M6 M6
Tightening torque (max) N/A N/A 26.4 lb in 44.9 lb in 44.9 lb in 44.9 lb in 44.9 lb in 44.9 lb in 44.9 lb in 44.9 lb in 15 min rating (w / cell)
5 min rating (w / cell)
27 53
36 75
123
232
218
384
283
506
355
627
414
700
542
838
503
912
652
1055
Energy/battery (kWh) 15 min rating
Energy/battery (kWh) 5 min rating
0.486
0.318
0.639
0.452
2.214
1.393
3.924
2.306
5.1 3.036
6.396
3.761
7.449
4.197
9.75 5.026
9.051
5.473
11.733
6.329
Nameplate capacity (AH) 6.8 8.5 30.0 55.0 70.0 100.0 105.0 135.0 110.0 150.0 Gassing rate
(cm3/hour) 2.3 V/cell,
99% recombination efficiency
0.1274825 0.1605335 0.5665887 0.9443145 1.3220403 1.8886290 1.8414133 2.5496492 2.0774919 2.8329435 For additional information on Eaton’s private-labeled batteries, contact Battery Service Sales Support at: 800.843.9433 or Eaton.com/UPSbatteries Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
© 2024 Eaton
All Rights Reserved
Printed in USA
TD162003EN / GG
January 2024
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
NOTE:
1. It is recommended to keep the ambient air temperature the battery is used in at 25°C (77°F) for optimal battery life and discharge performance.
2. If the Whr ratings above are going to be used to satisfy the requirements of the International Fire Code (IFC), a request must be submitted to Eaton for application specific calculations. *Rates are at 1.67 end voltage
The rate used is up to AHJ’s discretion
35 of 92
Qty. (160) Batteries
Internal to UPS
PS455001EN December 2015
SDS (Safety Data Sheet) Updated: 2015/12/03
Section 1: Identification of the substance/mixture and of the company/undertaking
1.1 Product identifier
Trade name/designation: Valve Regulated Lead Acid Battery
1.2 Relevant identified uses of the substance or mixture and uses advised against Relevant identified uses: Rechargeable Storage Batteries
1.3 Details of the supplier
Supplier’s name: Eaton Corporation
Website: www.Eaton.com/UPSBatteries
Relevant identified uses: Rechargeable Storage Batteries Information contact: 8609 Six Forks Rd. Raleigh, NC 27615
1.4 Emergency telephone number
Contact number:
United States:
Three-phase applications: 800-843-9433
Single-phase applications: 800-356-5794
Section 2: Hazards identification
2.1 Classification of the substance or mixture
Classification according to Regulation (EC) No 1272/2008 [CLP/GHS] Material is an article. No health effects are expected during normal use of this product as sold. Hazardous exposure may occur when the product is heated, oxidized or otherwise processed, damaged or subjected to misuse. Follow manufacturer’s instructions for installation, service and use.
No hazards occur during the normal operation of a Lead acid battery as it is described in the instructions for use that are provided with the battery. Lead acid batteries have three significant characteristics:
They contain an electrolyte which contains diluted sulphuric acid. Sulphuric acid may cause severe chemical burns. During the charging process or during operation they might develop hydrogen gas and oxygen, which under certain circumstances may result in an explosive mixture.
They can contain a considerable amount of energy, which may be a source of high electrical current and a severe electrical shock in the event of a short circuit.
Note: The batteries have to be marked with the symbols listed under section 15.
2.2 Other hazards
Adverse human health effects and symptoms:
Acute Chronic
Inhalation Under normal conditions of use, no health effects are expected.
Contents of an open battery can cause respiratory irritation.
Repeated and prolonged exposure may cause
irritation.
Skin Under normal conditions of use, no health effects are expected. No data available Eye Under normal conditions of use, no health effects are expected.
Exposure to dust may cause irritation. No data available.
Ingestion
Under normal conditions of use, no health effects are expected.
Lead ingestion may cause abdominal pain, nausea, vomiting, diarrhea and severe cramping.
No data available
HMIS rating for sulfuric acid: Health: 3 Flammability: 0 Reactivity: 2 Other: 0 Rating Codes:
0 = Insignificant, 1 = Slight,
NFPA rating for sulfuric a 2 = Moderate 3 = High 4 = Extreme cid: Health: 3 Flammability: 0 Reactivity: 2 Other: 0 36 of 92
PS455001EN December 2015
1) Contents may vary due to performance data of the battery 2) As result of the harm to the unborn children Lead compounds are classified as toxic for reproduction, Category 1. As this category is not described with a specific hazard symbol, Lead compounds have to be labeled with the “skull” symbol. Lead compounds are not classified “toxic“.
3) See Section 12 – Ecological Information
4) Density of the electrolyte varies in accordance to the state of charge 5) Composition of the plastic may vary due to different customer requirements Section 4: First Aid Measures
4.1 Description of first aid measures:
Electrolyte (diluted sulphuric acid): sulphuric acid acts corrosively and damages skin Lead compounds: lead compounds are classified as toxic for reproduction (if swallowed)
4.1.1 Electrolyte (sulphuric acid)
After skin contact: rinse with water, remove and wash wetted clothing After inhalation of acid mist: inhale fresh air, seek advice of a medical doctor After contact with the eyes: rinse under running water for several minutes, seek advice of a medical doctor After swallowing: drink lot of water immediately, swallow activated carbon, do not induce vomiting, seek advice of a medical doctor
4.1.2 Lead compounds
After skin contact: clean with water and soap
After inhalation: inhale fresh air, seek advice of a medical doctor After contact with the eyes: rinse under running water for several minutes, seek advice of a medical doctor After swallowing: wash mouth with water, seek advice of a medical doctor Section 5: Firefighting measures
Unusual fire and explosion hazards: Hydrogen and Oxygen gases are produced in cells during normal battery operation and expel into air through vent caps.
Suitable fire extinguishing agents: CO2 or dry powder extinguishing agents Unsuitable fire extinguishing agents: Water, if the battery voltage is above 120 V Special protective equipment:
Protective goggles, respiratory protective equipment, acid protective equipment, acid proof clothing in case of larger stationary battery plants or where larger quantities are stored.
Special firefighter procedures Use Positive Pressure, self-contained breathing apparatus.
Note:
Hydrogen flash point: -259°C. Hydrogen Auto ignition point: 580°C Hydrogen Flammable Limits in Air (% by Volume): Lower Explosion Limit (LEL) : 4.1 ; Upper Explosion Limit (UEL) : 74.2 Section 3: Composition/information on ingredients3
Material CAS No EC No OSHA PEL ACGIH
TLV
1By
weight%
Classification
according to
CLP(1272/2008)
Specific chemical identity:
LEAD 7439-92-1 231-100-4 50 μg/m3
150 μg/m3~57%
2 T,R60, R61,S1, S2,
Common name: S13, S35, S45, S53,
GRID
Specific chemical identity:
Lead Dioxide 1309-60-0 215-174-5 50 μg/m3
150 μg/m3~ 22%
2 T,R20/22, R33,
R50/R53, R61, S53,
S45, S60, S61 Common name:
Lead Oxide
Specific chemical identity:
Sulfuric Acid 7664-93-9 231-639-5 1mg/m3
1.0 mg/m3~14% C; R35; S1/2, S26,
Common name: S30, S45
4Battery Electrolyte (Acid)
5 Plastic container/plastic parts -- ~7% --
37 of 92
PS455001EN December 2015
Section 7: Handling and storage
7.1 Precautions for safe handling
Handling:
Keep away from heat and sources of ignition.
Wash hands thoroughly after use.
Do not use organic solvents; use only manufacturer recommended cleaners on the batteries.
Avoid sparks.
Do not remove vent caps.
Do not double stack industrial batteries, it may cause damage.
Storage:
Store batteries in a cool, dry area. Store batteries in a covered area that protects against adverse weather conditions. Protect batteries from coming into contact with conductive materials to prevent fire or battery failures. Don’t store or charge batteries in temperatures under -4o F (-20o C). Keep away from fire, sparks and heat sources. Protect from damage to prevent possible leaks or spills. It is imperative that these instructions be followed if the batteries are being stored.
Section 8: Exposure controls/personal protection
8.1 Appropriate engineering controls
Store batteries with adequate ventilation. Room ventilation is also required for batteries utilized for standby power generation. Never recharge batteries in an unventilated, enclosed space.
Substance name EC-No. CAS-No Description
Lead 231-100-4 7439-92-1 No exposure to lead and lead containing battery paste during normal conditions of use.
Sulfuric Acid 231-639-5 7664-93-9 R-phrases: R35 causes severe chemical burns S-phrases:
S2:Keep out of reach of children
S16:Keep away from sparks or naked flame, No smoking
S26:In case of contact with eyes rinse immediately with plenty of water and seek medical advice
S45:In case of accident or if you feel unwell seek medical advice immediately (show the label where possible).
8.2 Individual protection measures
Personal protective equipment:
During installation under normal conditions there is no exposure to lead or sulphuric acid. In the event of battery breakage, exposure to sulphuric acid and lead may occur. During high rate charges or overcharging acid mist may occur.
Eye/face protection: Chemical goggles, safety glasses with side shields and or a full-face shield.
Protective gloves: Rubber, PVC or neoprene
Respiratory protection: NIOSH approved acid mist/organic vapor respirator, if OSHA PEL is exceeded.
Other protective equipment: Acid resistant apron or clothes.
Work practices:
Use standard lead-acid battery practices. Do not wear metallic jewelry when working with batteries. Use non-conductive tools only.
Discharge static electricity prior to working on a battery. Maintain eyewash, fire extinguisher and emergency communication device in the work area.
Section 6: Accidental release measures
6.1 Personal precautions, protective equipment and emergency procedures Eye Protection Chemical goggles, safety glasses with side shields and or a full-face shield.
Protective gloves Rubber, PVC or neoprene
Respiratory Protection NIOSH approved acid mist/organic vapor respirator, if OSHA PEL is exceeded.
Other Protective Equipment Acid resistant apron or clothes.
Note: Personal protective equipment advice is contained in section 8 of the SDS.
6.2 Environmental precautions.
Prevent entry into waterways, sewers, basements or confined areas. Runoff from fire control and dilution water may be toxic and corrosive and may cause adverse environmental impacts.
6.3 Methods and materials for containment and cleaning up.
6.3.1 For Containment In the event of a battery rupturing; stop the leak if you can do it without risk. Absorb with earth, sand or other non-combustible material. Cautiously neutralize spilled liquid.
6.3.2 For Cleaning up Dispose of in accordance with local, State, and national regulations. 38 of 92
PS455001EN December 2015
Section 10: Stability and reactivity
10.1 Reactivity:
Broken batteries may result in small amounts of spilled electrolyte. Electrolyte is a corrosive, nonflammable liquid. Electrolyte can destroy organic materials such as cardboard, wood, textiles. Electrolyte may produce hydrogen as a reaction with some metals.
10.2 Chemical Stability: The battery and contents are stable under normal conditions.
10.3 Possibility of hazardous reactions: Hazardous polymerization will not occur.
10.4 Conditions to avoid: Overheating or overcharging the battery may results in acid mist and hydrogen generation.
10.5 Incompatibility (materials to avoid): Strong alkaline materials, conductive metals, organic solvents, spark or open flame.
10.6 Hazardous decomposition products: Hydrogen gas may be generated in an overcharged condition, in fire or at very high temperatures. In fire, may emit CO, CO2 and Sulfur Oxides.
Section 11: Toxicological information
11.1 Information on toxicological effects:
CSB VRLA batteries are sealed, recombinant design that require no water replacement throughout their service life, thus no contact is made with the battery’s internal components or chemical hazards. Under normal use and handling, these batteries do not emit regulated or hazardous substances.
Sulfuric acid (7664-93-9)
Administration route Method Dose Test Animal
Acute oral toxicity LD50 2140 mg/kg Rat
Acute inhalative toxicity (vapor) LC50 510 mg/m3 Rat
11.2 Routes of exposure:
Acute Chronic
Inhalation Under normal conditions of use, no health effects are expected.
Contents of an open battery can cause respiratory irritation.
Repeated and prolonged exposure
may cause irritation.
Skin Under normal conditions of use, no health effects are expected. No data available Eye Under normal conditions of use, no health effects are expected.
Exposure to dust may cause irritation. No data available.
Ingestion
Under normal conditions of use, no health effects are expected. Lead ingestion may cause abdominal pain, nausea, vomiting, diarrhea and severe cramping.
No data available
Carcinogenicity: The International Agency on Cancer (IARCC) has classified “strong inorganic acid mists containing sulfuric acid” as a category 1 carcinogen (inhalation), a substance that is carcinogenic to humans. This classification does not apply to the liquid forms of sulfuric acid contained within the battery. Misuse of the product, such as overcharging, may result in the generation of sulfuric acid mist at high levels.
Section 9: Physical and chemical properties
Item Lead and lead compounds Electrolyte
Appearance
Form: Solid Liquid
Color: Grey Colorless
Odor: Odorless
PH N/A
Melting point/freezing point. 327.4 °C(melting point) -35 to -60 °C Initial boiling point and boiling range. 1740 °C(lit.) Approx. 108~114℃ Flash point. N/A
Evaporation rate. N/A
Vapor pressure. (mm Hg at 20°C) N.A. < 0.3 mmHg
Vapor density.(Air=1) 7.1 3.4
Density(20°C) 11.35 g/cm³ 1.2 to 1.3 g/cm³
solubility in water : Very low (0.15mg/l) Fully soluble Partition coefficient: n-octanol/water. N/A
Decomposition temperature. N/A
Lead and Lead compounds used in Lead Acid batteries are poorly soluble in water; Lead can be dissolved in an acidic or alkaline environment only
39 of 92
PS455001EN December 2015
Section 13: Disposal considerations
Spent lead acid batteries (EWC 160601) are subject to regulation of the EU Battery Directive and its adoptions into national legislation on the composition and end of life management of batteries.
Spent Lead Acid batteries are recycled in lead refineries (secondary lead smelters). The components of a spent Lead Acid battery are recycled or reprocessed.
At the points of sale, the manufacturers and importers of batteries, respectively the metal dealers take back spent batteries, and render them to the secondary lead smelters for processing.
To simplify the collection and recycling or reprocessing process spent Lead Acid batteries must not be mixed with other batteries.
By no means may the electrolyte (diluted sulphuric acid) be emptied in an inexpert manner. This process is to be carried out by the processing companies only.
Section 14: Transport information
All CSB batteries are identified as “Battery, Electric Storage, Wet, Nonspillable” when transported by air, sea or by land transportation. The battery(s) must be identified as above on the Bill of Lading and properly packaged with their terminals protected from short circuit. NA or UN numbers do not apply. CSB battery(s) warning label identifies each battery as NONSPILLABLE.
CSB seal lead-acid batteries are classified as “Nonspillable” for the purpose of transportation by DOT, and IATA/ICAO as result of passing the Vibration and Pressure Differential Test described in DOT [49 CFR 173.159 (f)] and IATA/ICAO [Special Provision A67].CSB seal lead-acid batteries can be safely transported on deck, or under deck stored on either a passenger or cargo vessel as result of passing the Vibration and Pressure Differential Tests as described in the IMDG regulations(Special Article 238).
To transport these batteries as “non-spillable” they must be shipped in a condition that would protect them from short-circuits and be securely packaged so as to withstand conditions normal to transportation by a consumer, in or out of a device, they are unregulated thus requiring no additional special handling or packaging.
For all modes of transportation, each battery and outer package is labeled “NON-SPILLABLE” per 49 CFR 173.159(f) and 49 CFR 173.159a. If you repackage our batteries either as batteries or as a component of another product you must label the outer package “NON-SPILLABLE” per 49 CFR 173.159(f) and 49 CFR 173.159a.
Section 12: Ecological information
This information is of relevance if the battery is broken and the ingredients are released to environment.
12.1 Electrolyte (diluted sulphuric acid)
In order to avoid damage to the sewage system, the acid has to be neutralized by means of time or sodium carbonate before disposal. Ecological damage is possible by change of pH. The electrolyte solution reacts with water and organic substances, causing damage to flora and fauna. The electrolyte may also contain soluble components of lead that can be toxic to aquatic environments.
12.2 Lead and Lead compounds
Chemical and physical treatment is required for the elimination from water. Waste water containing lead must not be disposed of in an untreated condition. The former classification of Lead compounds as toxic for the aquatic environment R50/53 had been triggered from test results generated in the 80’s for soluble Lead compounds (Lead Acetate). The hardly soluble Lead compounds such as Battery Lead Oxide were not tested at this time. Tests on Battery Lead Oxide were carried out in 2001 and 2005. The respective test results conclude that Battery Lead Oxide is not toxic for the environment, neither R50 nor R50/53 nor R51/53. From this it follows that the general classification for Lead compounds (R50/53) does not apply to Battery Lead Oxide. As the result of this the Risk Phrase R52/53 (Harmful to aquatic organisms, may cause longterm adverse effects in the aquatic environment) applies to Battery Lead Oxide.
Effects of Battery Lead Oxide in the aquatic environment:
Toxicity for fish: 96 h LC 50 > 100 mg/l
Toxicity for daphnia: 48 h EC 50 > 100 mg/l
Toxicity for alga: 72 h IC 50 > 10 mg/l
The results demonstrate these Battery Lead Oxide compounds in a concentration of 100 mg/l have no adverse effect on fish and daphnia. A concentration of these Battery Lead Oxide of 10 mg/l has no adverse effect on the rate of growth and the biomass. For the classification according to Directive 67/548/EEC the most sensitive adverse effect has to be considered. As a result of the toxicity for alga at > 10 mg/l Battery Lead Oxide has to be classified according to the R-Phrases 52/53 (Harmful to aquatic organisms, may cause long term adverse effects in the aquatic environment). 40 of 92
PS455001EN December 2015
Section 15: Regulatory information
In accordance with EU Battery Directive and the respective national legislation, Lead Acid batteries have to be marked by a crossed out dust bin with the chemical symbol for lead shown below, together with the ISO return/recycling symbol.
In addition some of the following hazard symbols described below might apply:
Corrosive Explosive gas mixture Read Instructions
Keep out of reach of children No Smoking, no open flames, no sparks. Wear Safety Goggles.
15.1 STATE REGULATIONS (US):
California proposition 65 warning:
Battery posts, terminals and related accessories contain lead and lead compounds chemical know to the state of California to cause cancer and reproductive harm. Battery also contain other chemical know to the state California to cause cancer. Wash hands after handling.
15.2 INTERNATIONAL REGULATIONS (Non-US):
National regulations(Canada):
Canadian Domestic Substanc List (DSL):
All ingredients remaining in the finished product as distributed into commerce are included on the Domestic Substances List.
Canada NDSL:
None of the components on this SDS are listed on the Canadian NDSL WHMIS Classifications:
Class E: Corrosive materials present at greater than 1% This product has been classified in accordance with the hazard criteria of the Controlled Products Regulations (CPR) and the SDS contains all the information required by the Controlled Products Regulations.
About Battery Handling, please see the OSHA 29 CFR 1910.268(b) as below:
910.268(b)(2)(i)
Eye protection devices which provide side as well as frontal eye protection for employees shall be provided when measuring storage battery specific gravity or handling electrolyte and the employer shall ensure that such devices are used by the employees. The employer shall also ensure that acid resistant gloves and aprons shall be worn for protection against spattering. Facilities for quick drenching or flushing of the eyes and body shall be provided unless the storage batteries are of the enclosed type and equipped with explosion proof vents, in which case sealed water rinse or neutralizing packs may be substituted for the quick drenching or flushing facilities. Employees assigned to work with storage batteries shall be instructed in emergency procedures such as dealing with accidental acid spills. 1910.268(b)(2)(ii)
Electrolyte (acid or base, and distilled water) for battery cells shall be mixed in a well ventilated room. Acid or base shall be poured gradually, while stirring, into the water. Water shall never be poured into concentrated (greater than 75 percent) acid solutions. Electrolyte shall never be placed in metal containers nor stirred with metal objects. 1910.268(b)(2)(iii)
When taking specific gravity readings, the open end of the hydrometer shall be covered with an acid resistant material while moving it from cell to cell to avoid splashing or throwing the electrolyte. 41 of 92
PS455001EN December 2015
Section 16: Other information
Products such as Batteries are not in the scope of regulation which requires the publication of an EU Safety Data Sheet (91/155/EEC).
The information given above is provided in good faith based on existing knowledge and does not constitute an assurance of safety under all conditions. It is the user’s responsibility to observe all laws and regulations applicable for storage, use, maintenance or disposal of the product. If there are any queries, the supplier should be consulted.
However, this shall not constitute a guarantee for any specific product features and shall not establish a legally valid contractual relationship.
The contents and format of this SDS are in accordance with EEC Commission Directive 1999/45/EC, 67/548/EC, 1272/2008/EC and EEC Commission Regulation 1907/2006/EC (REACH) Annex II. 42 of 92
Tab 6
Input / Output
Breaker Information
43 of 92
48 Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 05 Table 17. Recommended Input and Bypass Circuit Breaker Ratings Input Rating
UPS Model UPS Rating Load Rating 208V 220V
Eaton 93PM-L 60-1
Eaton 93PM-L 60-2 (N+1) 10 kW
80% Rated 45A 45A
100% Rated 40A 35A
Eaton 93PM-L 60-1
Eaton 93PM-L 60-2 (N+1) 20 kW
80% Rated 90A 90A
100% Rated 80A 70A
Eaton 93PM-L 60-2
Eaton 93PM-L 60-3 (N+1) 30 kW
80% Rated 150A 150A
100% Rated 110A 110A
Eaton 93PM-L 60-2
Eaton 93PM-L 60-3 (N+1) 40 kW
80% Rated 200A 175A
100% Rated 150A 150A
Eaton 93PM-L 60-3 50 kW
80% Rated 225A 225A
100% Rated 200A 175A
Eaton 93PM-L 60-3 60 kW
80% Rated 300A 300A
100% Rated 225A 225A
CAUTION
To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings from Table 18 in accordance with the NEC, ANSI/NFPA 70.
The line-to-line unbalanced output capability of the UPS is limited only by the full load per phase current values for AC output to critical load shown in Table 9 through . The recommended line-to-line load unbalance is 50% or less.
Output overcurrent protection and Output disconnect switches are to be supplied by the customer. Table 18 lists the recommended rating for output circuit breakers. !
IMPORTANT
If an output breaker is not provided, the wire between the output and the load must be sized the same as the bypass input wire.
UPS Installation Plan and Unpacking
44 of 92
Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 05 49 Table 18. Recommended Output Circuit Breaker Ratings
Output Rating
UPS Model UPS Rating Load Rating 208V 220V
Eaton 93PM-L 60-1
Eaton 93PM-L 60-2 (N+1) 10 kW
80% Rated 35A 35A
100% Rated 30A 30A
Eaton 93PM-L 60-1
Eaton 93PM-L 60-2 (N+1) 20 kW
80% Rated 70A 70A
100% Rated 60A 60A
Eaton 93PM-L 60-2
Eaton 93PM-L 60-3 (N+1) 30 kW
80% Rated 110A 100A
100% Rated 90A 80A
Eaton 93PM-L 60-2
Eaton 93PM-L 60-3 (N+1) 40 kW
80% Rated 150A 150A
100% Rated 125A 110A
Eaton 93PM-L 60-3 50 kW
80% Rated 175A 175A
100% Rated 150A 150A
Eaton 93PM-L 60-3 60 kW
80% Rated 225A 200A
100% Rated 175A 175A
There is no manual DC disconnect device within the UPS.
Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current is computed based on 2 volts per cell.
If required, external DC input overcurrent protection and disconnect switch is to be supplied by the customer.
Table 19 lists the recommended ratings for circuit breakers satisfying the criteria for each battery voltage.
Recommended disconnect size is based on a maximum full load discharge time less than 3 hours. For longer discharge times a larger disconnect may be required.
Table 19. Recommended DC Input Battery Disconnect Circuit Breaker Ratings Output Rating
UPS Model UPS Rating 208V or 220V
Eaton 93PM-L 60-1
Eaton 93PM-L 60-2 (N+1) 10 kW 25A
Eaton 93PM-L 60-1
Eaton 93PM-L 60-2 (N+1) 20 kW 45A
Eaton 93PM-L 60-2
Eaton 93PM-L 60-3 (N+1) 30 kW 70A
Eaton 93PM-L 60-2
Eaton 93PM-L 60-3 (N+1) 40 kW 90A
Eaton 93PM-L 60-3 50 kW 125A
Eaton 93PM-L 60-3 60 kW 150A
UPS Installation Plan and Unpacking
45 of 92
UPS System Installation
4-24 Eaton 93PM-L UPS (20–60 kW, 208V) Installation and Operation Manual P-164000711—Rev 01 www.eaton.com/powerquality Figure 4-15. Interface Terminal Locations
MINI SLOT
COMMUNICATION
BAYS
INTERFACE
TERMINALS
46 of 92
Tab 7
Control Wiring
47 of 92
50 Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 05
3.5 UPS System Interface Wiring Preparation
Control wiring for features and options should be connected at the customer interface terminal blocks located inside the UPS.
WARNING
Do not directly connect relay contacts to the mains related circuits.
Reinforced insulation to the mains is required.
Read and understand the following notes while planning and performing the installation:
• Use Class 1 wiring methods (as defined by the NEC) for interface wiring from 30V to 600V. The wire should be rated for 600V, 1A minimum. 12 AWG maximum wire size. • Use Class 2 wiring methods (as defined by the NEC) for interface wiring up to 30V. Class 2 circuit wiring must be segregated from Class 1 wiring. The Class 2 wire should be rated for 150V, 1A minimum. • Because of the battery shunt trip wiring route in the UPS cabinet, the wire should be rated for a minimum of 600V.
• Use twisted-pair wires for each input and return or common. • All interface wiring and conduit is to be supplied by the customer. • When installing external interface wiring between a building alarm, relay output, battery breaker trip, or Minislot and the UPS interface terminals, conduit must be installed between each device and the UPS cabinet.
• If using conduit, install the interface wiring in separate conduit from the power wiring. • All building alarm inputs require an isolated normally-open contact or switch (rated at 24 Vdc, 20 mA minimum) connected between the alarm input and common terminal. All control wiring and switch contacts are customer-supplied.
• LAN and telephone drops for use with Minislot connectivity cards must be supplied by the customer. • The UPS battery detect signal wiring from a UPS building alarm must be connected to the battery disconnect device.
• Program the battery detect building alarm to read battery open and for normally open contacts. • A supplemental 48 Vdc shunt trip signal for the battery disconnect device is provided, but is not required for normal operation.
• Battery detect and 48 Vdc shunt trip wiring should be a minimum of 18 AWG. • The REPO feature opens all switchgear in the UPS cabinet and isolates power from your critical load. Local electrical codes may also require tripping upstream protective devices to the UPS. • The REPO switch must be a latching-type switch not tied to any other circuits. • A jumper wire must be connected between pins 3 and 4 on the REPO terminal block if using a normallyclosed REPO switch. • REPO wiring should be a minimum of 18 AWG and a maximum of 16 AWG. • The REPO switch wiring must be in accordance with NEC Article 725 Class 2 requirements. • The maximum distance between the REPO and the UPS cannot exceed 150m (500 ft). • Alarm relay contacts have a maximum current rating of 5A and a switched voltage rating of 30 Vac or 28 Vdc.
• Recommended alarm relay wiring size is 18 AWG.
UPS Installation Plan and Unpacking
48 of 92
Eaton 93PM-L 20–60kW (208V) UPS Installation and Operation Manual P-164000711—Rev 02 87
5. Bottom Entry Wiring. Route the bypass shunt trip wiring through the bottom of the UPS to the UPS bypass shunt trip terminals. See Figure 24, Figure 25, or Figure 29 for UPS wiring access information, and Figure 34 and Figure 35 for UPS terminal locations.
6. Proceed to Step 8.
7. Top Entry Wiring. Route the bypass shunt trip wiring through the top of the UPS and the bottom UPS inter-cabinet wiring access pass-through to the UPS bypass shunt trip terminals.
8. Connect the wiring to the bypass shunt trip terminals. See paragraph
3.5 UPS System Interface Wiring Preparation and Table 26 for wiring and termination requirements, and Figure 41 for terminal assignments.
9. If wiring additional interface or control wiring options, see for next option to install; otherwise, proceed to Step 10.
10. If removed, reinstall all safety shield panels previously removed and secure with the retained hardware.
11. If removed, reinstall the sidecar front panel and secure with the retained hardware.
12. Close the UPS outside door and secure the latch.
4.6.6 Generaa tor Interfaa ce Connections
If ESS is enabled and the UPS will be fed by a site generator at any time, the On Generator building alarm must be wired and configured to a Building Alarm Input. Wiring the On Generator sensing circuit to a building alarm allows the UPS to optimize its operation with the generator by transferring the UPS from ESS mode to Normal (double conversion) mode.
NOTE 1 An UPS building alarm input is used to indicate On Generator.
NOTE 2 Any pair of unused building alarm terminals may be used for On Generator connections.
NOTE 3 Program the building alarm to read On Generator and for either Normally Open (default) or Normally Closed as required by the generator sensing output.
NOTE 4 If installing interface wiring connections between standalone cabinets, conduit must be installed between cabinets.
NOTE 5 Disconnect terminal block plugs from terminal blocks to wire plugs.
To Install wiring:
1. Verify the UPS system is turned off and all power sources are removed. See Chapter 6 UPS Operating Instructions, for shutdown instructions.
2. If not already opened, open the front door by lifting the latch from the bottom and turning to the right (counterclockwise) and swing the door open.
3. If wiring the interface terminals from the bottom of the UPS, proceed to Step 8; otherwise, proceed to Step 4.
4. Top Entry Wiring. Remove the top interface entry conduit landing plates to drill or punch holes (see Figure 24, Figure 25, or Figure 29).
5. Reinstall the interface entry plates and install the conduit.
6. Route the UPS building alarm interface wiring through the top interface entry conduit landing plates to the UPS building alarm terminals. See Figure 34 and Figure 35 for UPS interface terminal locations.
7. Proceed to Step 13.
8. Bottom Entry Wiring. Remove the bottom interface entry conduit landing plates to drill or punch holes (see Figure 36).
UPS System Installation
49 of 92
Generator Interface Connections Page 350 of 1066
Eaton 93PM-L UPS (20–60 kW, 208V) Installation and Operation Manual P-164000711—Rev 01 www.eaton.com/powerquality 6-1 Chapter 6 UPS Operating Instructions
This section describes how to operate the UPS.
6.1 UPS Controls and Indicators
The controls and indicators identified and described in this section are used to set up, control, and monitor UPS operation. Figure 6-1 shows the control panel location on the front door of the UPS. For a description of the UPS control panel functions, and how to control and monitor UPS operation, see paragraph 6.2.
Figure 6-1. UPS Controls and Indicators
NOTE 1 Before starting the UPS, ensure all installation tasks are complete and a preliminary startup has been performed by authorized service personnel. The preliminary startup verifies all electrical interconnections to ensure the installation was successful and the system operates properly.
NOTE 2 Read this section of the manual and have thorough knowledge of UPS operation before attempting to operate any of the controls.
CONTROL PANEL
DOOR LATCH
50 of 92
UPS Operating Instructions
Eaton 93PM-L UPS (20–60 kW, 208V) Installation and Operation Manual P-164000711—Rev 01 www.eaton.com/powerquality 6-3
6.2 Using the Control Panel
The following paragraphs describe the UPS control panel, including controls and indicators, and how to monitor UPS operation. The control panel is shown in Figure 6-3.
Figure 6-3. UPS Control Panel
The control panel consists of:
A color liquid crystal touch screen display (1).
A horizontal row of status indicators (2). See paragraph 6.2.1.
The following paragraphs describe using the UPS control panel to monitor the UPS. See paragraph 6.3 for use of the operational controls.
When the unit powers up, the screen displays the as shown in Figure 6-3. 51 of 92
UPS Operating Instructions
6-4 Eaton 93PM-L UPS (20–60 kW, 208V) Installation and Operation Manual P-164000711—Rev 01 www.eaton.com/powerquality
6.2.1 Status Indicators
The four symbols on the bottom of the control panel are status indicators. These colored light emitting diode (LED) lamps work with the alarm horn to provide the operating status of the UPS.
Table 6-1 describes the status indicators.
6.2.2 System Events
When the UPS system is running in Double Conversion mode, it continually monitors itself and the incoming utility power. In Battery or Bypass modes, the UPS may issue alarms to let you know exactly what event caused the change from Double Conversion mode. System events on the UPS can be indicated by horns, lights, messages, or all three.
Select the LOGS tab from the navigation bar on main menu screen to display the active events screen. This screen shows any currently active alarms, notices, or commands. For more information on using the events screen, see paragraph 6.2.6.
System Event Horns – The system event horn beeps to alert an operator that an event needing attention is taking place. The horn cycles at a half-second rate. To silence the horn, touch any control panel button.
System Event Indicators – The status indicators on the UPS control panel work with the event horn to let the operator know when the UPS is operating in any mode other than double conversion. Only the normal mode indicator is illuminated during normal UPS system operation. The other indicators illuminate to indicate alarms or events. When an alarm occurs, first check these indicators to see what type of event has taken place. For descriptions of the status indicators, see paragraph 6.2.1.
System Event Messages – When a system event occurs, a message appears on the LCD in the UPS status area. This message is also written to the Events Log and may be added to the History Log. The messages are divided into four categories: alarms, notices, status, and commands.
Table 6-1. Status Indicators
Indicator Status Description
On The UPS is in Double Conversion mode. The power module is supplying power to the critical load.
Off The UPS is turned off.
On The UPS is in Battery mode. Because Battery mode is a normal condition of the UPS, the normal indicator also remains illuminated.
On The UPS is in Bypass mode. The critical load is supported by the bypass source. The normal indicator is not illuminated when the system is in Bypass mode.
On The UPS has an active alarm and requires immediate attention. The LCD shows the highest priority active alarms.
All alarms are accompanied by an audible horn. To silence the horn, touch any control panel button. The Alarm indicator may be illuminated along with other indicators.
Flashing There is a new UPS alarm condition. The indicator flashes until acknowledged by touching any control panel button once.
Green
Yellow
Yellow
Red
52 of 92
UPS Operating Instructions
Eaton 93PM-L UPS (20–60 kW, 208V) Installation and Operation Manual P-164000711—Rev 01 www.eaton.com/powerquality 6-5
6.2.3 Using the LCD Touch Screen
The LCD touch screen on the control panel provides an operator interface with the UPS system. Figure 6-4 identifies the display areas discussed in the following sections.
All functions and commands are accessed by touching or tapping the screen tabs or buttons. When text input is required, either a Qwerty keyboard or numeric keypad will be displayed.
Figure 6-4. Parts of the LCD
A Status Bar displays the UPS name, UPS state, current date and time, meter information, active alarms and notices, and a sign in/sign out button. For more information about alarms and notices, see paragraph
6.2.2. B Main Menu Navigation Bar displays main menu functions and selections as tab buttons. To select a screen function touch the tab name.
C Secondary Menu Navigation Bar displays functions and selections related to the current screen as tab buttons. To select a screen function touch the tab name.
D Information Area contains status data, operational controls, acknowledgments, action confirmations, and screen prompts.
You can use the LCD touch screen to:
Look at a log of UPS events (alarms, notices, and commands) (see paragraph 6.2.6) Monitor UPS operation (see paragraph 6.2.6)
Set UPS parameters (see paragraph 6.2.6)
Control UPS operation (see paragraphs 6.2.6 and 6.2.8)
A
B
C
D
53 of 92
UPS System Installation
4-32 Eaton 93PM-L UPS (20–60 kW, 208V) Installation and Operation Manual P-164000711—Rev 01 www.eaton.com/powerquality
10. If wiring generator interface connections, proceed to paragraph 4.6.6; if wiring Minislot connections, proceed to paragraph 4.6.7; if wiring REPO connections, proceed to paragraph 4.7; otherwise, proceed to Step 13.
11. Reinstall all safety shield panels previously removed and secure with the retained hardware.
12. If removed, reinstall the sidecar front panel and secure with the retained hardware.
13. Close the UPS outside door and secure the latch.
Figure 4-22. Shunt Trip Terminals Location
SHUNT TRIP
TERMINALS
54 of 92
UPS System Installation
Eaton 93PM-L UPS (20–60 kW, 208V) Installation and Operation Manual P-164000711—Rev 01 www.eaton.com/powerquality 4-33 Figure 4-23. Shunt Trip Terminal Detail
Shunt Trip Terminals
(See Figure for terminal
assignments.)
Table 4-4. Bypass and Battery Shunt Trip Connections and Wire Terminations Terminal Name Description
Recommended
Minimum Wire Size
Size of Pressure
Termination Tightening Torque
1 48 Vdc Bypass Shunt Trip (–) Output: Contacts used to open bypass breaker or disconnect
Twisted Pair Wires #18
AWG #1430 AWG
2 lb in
(0.22-0.25 Nm) 2 48 Vdc Bypass Shunt Trip (+)
5 48 Vdc Battery Shunt Trip (–) Output: Contacts used to open battery breaker or disconnect
Twisted Pair Wires #18
AWG #1430 AWG
2 lb in
(0.22-0.25 Nm) 6 48 Vdc Battery Shunt Trip (+)
55 of 92
UPS System Installation
Eaton 93PM-L UPS (20–60 kW, 208V) Installation and Operation Manual P-164000711—Rev 01 www.eaton.com/powerquality 4-37 Figure 4-24. REPO Switch
11. Route the REPO wiring through the bottom interface entry conduit landing plate to the bottom access interface wiring channel along the inside of the front door (see Figure 4-17).
12. Route the wiring along the interface wiring channel (see Figure 4-17) to the REPO terminals. See Figure 4-15 and Figure 4-16 for UPS interface terminal locations.
13. Secure the wiring to the wire tie anchors provided (see Figure 4-18) using Zip ties.
14. Connect the REPO wiring as shown in Table 4-5 and Figure 4-26 for a normally-open REPO or, Table 4-6 and Figure 4-27 for a normally-closed REPO. See paragraph 3.2.3 for wiring and termination requirements, and Figure 4-25 for terminal assignments.
15. If using a normally-closed REPO switch, connect a jumper wire between pins 3 and 4 on the REPO terminal block.
16. If you are installing multiple REPO switches, wire additional switches in parallel with the first REPO.
17. If required, install wiring from the REPO switch to the trip circuitry of the upstream protective devices. A second contact block is provided on the REPO switch for this function (see Figure 4-24). The REPO switch wiring must be in accordance with NEC Article 725 Class 2 requirements.
18. Close the UPS outside door and secure the latch.
Figure 4-25. REPO Terminal Block Connector Assignments
REPO Switch (Front View) Contact Block (Back View, Faceplate Removed) Normally Closed
REPO Contacts
Normally Open
REPO Contacts
UPS REPO
123 4
GND-ISO
EPO_A_B
EPO_B
EPO_A
REPO Switch Not Included
56 of 92
UPS System Installation
4-38 Eaton 93PM-L UPS (20–60 kW, 208V) Installation and Operation Manual P-164000711—Rev 01 www.eaton.com/powerquality Figure 4-26. Normally-Open REPO Switch Wiring
Figure 4-27. Normally-Closed REPO Switch Wiring
Table 4-5. Normally-Open REPO Connections and Wire Terminations From REPO Station
Switch Contact
Block
(Either Block)
UPS REPO
Terminal Name Description
Recommended
Minimum Wire
Size
Size of Wire
Termination
Tightening
Torque
3 NO 3 EPO_A Input: Normally-open dry contact used to activate UPS EPO from a remote switch
Twisted Pair Wires
#18 AWG #1630 AWG
2 lb in
(0.22-0.25 Nm) 4 NO 4 EPO_B
3 1
2 4
3 4
REPO
Switch
(NO)
Twisted
Wires
REPO TB
NOTE REPO switch rating is 24 Vdc, 1A minimum.
NOTE The REPO switch must be a latching-type switch not tied to any other circuits.
Table 4-6. Normally-Closed REPO Connections and Wire Terminations From REPO Station
Switch Contact
Block
(Either Block)
UPS REPO
Terminal Name Description
Recommended
Minimum Wire
Size
Size of Wire
Termination
Tightening
Torque
3 NO 1 EPO_A_B Input: Normally-closed dry contact used to activate UPS EPO from a remote switch.
Twisted Pair Wires
#18 AWG #1630 AWG
2 lb in
(0.22-0.25 Nm) 4 NO 2 GND-ISO
3 1
2 4
1 2
REPO
Switch
(NC)
Twisted
Wires
REPO TB
NOTE REPO switch rating is 24 Vdc, 1A minimum.
NOTE The REPO switch must be a latching-type switch not tied to any other circuits. 57 of 92
Tab 8
Monitoring
Information
58 of 92
UPS System Installation
Eaton 93PM-L UPS (20–60 kW, 208V) Installation and Operation Manual P-164000711—Rev 01 www.eaton.com/powerquality 4-25 Figure 4-16. Interface Terminal Detail
Figure 4-17. Bottom Access Interface Wiring Location
Minislot Communication Bay 2
Minislot Communication Bay 1
Minislot Communication Bay 3
Minislot Communication Bay 4
Building Alarm Terminals
(See Figure 4-19 for
terminal assignments.)
Device USB
RS-232
Host USB
REPO Terminals
(See Figure 4-25 for
terminal assignments.)
Relay Output Terminals
(See Figure 4-20 for
terminal assignments.)
Cabinet Stiffener Bar
Pull Chain and CAN Terminals
Accessory
Communication
Power
Wire Tie Anchors
Bottom Access
Interface
Wiring Channel
Bottom Entry Conduit Landings
for Customer Interface Wiring
59 of 92
UPS System Installation
4-26 Eaton 93PM-L UPS (20–60 kW, 208V) Installation and Operation Manual P-164000711—Rev 01 www.eaton.com/powerquality Figure 4-18. Wire Tie Anchors
Figure 4-19. Building Alarm Terminal Block Connector Assignments Wire Tie Anchors
Table 4-1. Building Alarm Connections and Wire Terminations Terminal Name Description
Recommended
Wire Size
Size of Pressure
Termination Tightening Torque
10 Building Alarm 1 Input: Programmable UPS alarm, activated by a remote dry contact closure
Twisted Pair Wires
#18 AWG #1430 AWG
2 lb in
(0.22-0.25 Nm) 9 Building Alarm 1 Return
8 Building Alarm 2 Input: Programmable UPS alarm, activated by a remote dry contact closure
Twisted Pair Wires
#18 AWG #1430 AWG 2 lb in
7 Building Alarm 2 Return (0.22-0.25 Nm)
6 Building Alarm 3 Input: Programmable UPS alarm, activated by a remote dry contact closure
Twisted Pair Wires
#18 AWG #1430 AWG
2 lb in
(0.22-0.25 Nm) 5 Building Alarm 3 Return
4 Building Alarm 4 Input: Programmable UPS alarm, activated by a remote dry contact closure
Twisted Pair Wires
#18 AWG #1430 AWG
2 lb in
(0.22-0.25 Nm) 3 Building Alarm 4 Return
2 Building Alarm 5 Input: Programmable UPS alarm, activated by a remote dry contact closure
Twisted Pair Wires
#18 AWG #1430 AWG
2 lb in
(0.22-0.25 Nm) 1 Building Alarm 5 Return
UPS Building Alarms
1234 56 7 8 9 10
Building Alarm 5
Building Alarm 5 Return
Building Alarm 4
Building Alarm 4 Return
Building Alarm 1 Return
Building Alarm 1
Building Alarm 2 Return
Building Alarm 2
Building Alarm 3 Return
Building Alarm 3
60 of 92
UPS System Installation
Eaton 93PM-L UPS (20–60 kW, 208V) Installation and Operation Manual P-164000711—Rev 01 www.eaton.com/powerquality 4-27 Figure 4-20. Relay Contact Terminal Block Connector Assignments
4.6.2 Installing Sidecar MIS and RIB Breaker Monitoring Connections To install wiring:
1. Verify the UPS system is turned off and all power sources are removed. See Chapter 6, “UPS Operating Instructions,“ for shutdown instructions.
2. If not already removed, loosen the bottom screws and completely remove the top screws securing the sidecar front panel. Lift the panel upwards and remove from the unit. Retain the hardware for later use.
3. Route the wiring along the sidecar interface wiring channel to the sidecar terminals, TB1 and TB2.
4. Secure the wiring to the wire tie anchors provided using Zip ties.
5. If 2, 3 or 4 Breaker Sidecar and monitoring of the Maintenance Isolation Breaker (MIS) is required, connect the building alarm interface wiring to TB1. See paragraph 3.2.3 and Table 4-3 for wiring and termination requirements, and Figure 4-21 for terminal assignments.
6. If 4 Breaker Sidecar and monitoring of the Rectifier Input Breaker (RIB) is required, connect the building alarm interface wiring to TB2. See paragraph 3.2.3 and Table 4-3 for wiring and termination requirements, and Figure 4-21 for terminal assignments.
7. Reinstall the sidecar front panel and secure with the retained hardware.
8. Close the UPS outside door and secure the latch.
Table 4-2. Relay Contact Connections and Wire Terminations Terminal Name Description
Recommended
Wire Size
Size of Pressure
Termination Tightening Torque
1 Relay Contact NC Output: General purpose normally-closed (NC) relay contact
Twisted Pair Wires
#18 AWG #1430 AWG
2 lb in
(0.22-0.25 Nm) 3 Relay Contact Common
2 Relay Contact NO Output: General purpose normally-closed (NO) relay contact
Twisted Pair Wires
#18 AWG #1430 AWG 2 lb in
3 Relay Contact Common (0.22-0.25 Nm)
NOTE 1 In a 2 Breaker Sidecar; only the Maintenance Bypass Breaker (MBP) is pre-wired for monitoring.
NOTE 1 In a 3 or 4 Breaker Sidecar; both the Maintenance Bypass Breaker (MBP) and the Bypass Input Breaker (BIB) are pre-wired for monitoring.
UPS Relay Output
123
NO_Out
NC_Out
Com
61 of 92
Eaton Gigabit Industrial Gateway Card
Industrial gateway card
The Eaton Gigabit Industrial
Gateway Card (INDGW-M2) is
Eaton’s latest UPS connectivity
device that delivers industrial
professionals with new and
exciting capabilities and features.
The first UPS network card
to meet both UL 2900-1 and
IEC 62443-4-2 cybersecurity
standards, the Gigabit Industrial
Gateway Card improves power
system reliability by providing
warnings of pending issues
to administrators and helping
to perform orderly graceful
shutdown of servers and
storage. The new network card
works with Intelligent Power
Manager (IPM) v1.61 (and
higher) to improve business
continuity by triggering policies
configured to keep mission
critical applications running in the
event of power or environmental
anomalies, including virtual
machine relocation or automated
disaster recovery action.
Details
• Gigabit speed: compatible
with better performing, cost
effective and widely deployed
gigabit network switches
• Compliance with Gigabit only
data center networks
• Cybersecurity enhancements
for UL 2900-1 and IEC
62443-4-2 certifications,
including stronger encryption,
configurable password
policy and X.509 Public Key
Infrastructure
• Real-time clock with battery
backup and linkage to NTP
(Network Time Protocol)
server
• Increased memory for
improved operation and
larger data storage
• Advanced Management with
RESTful API over HTTPS
• Secure SMTP for email alerts
Eaton Gigabit Industrial
Gateway Card (installed)
Eaton Gigabit Industrial
Gateway Card (front)
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2021 Eaton
All Rights Reserved
Printed in USA
BR152074EN / GG
June 2021
Eaton is a registered trademark.
All other trademarks are property of their
respective owners.
Optional monitoring probe
Eaton is also offering a new Environmental Monitoring
Probe (EMP) Gen 2 (EMPDT1H1C2), an environmental
monitoring probe with sensors (temperature, humidity
and dry-contact monitoring) and the ability to be daisychained (up to 3 per host), allowing multiple sensor connection to a single host. The probe is compatible with the Gigabit Industrial Gateway Card and Eaton rack PDUs including G3 (firmware 4.x or later), G3HD and G3+.
Technical specifications1
Eaton Gigabit Industrial Network Card
Function Web/Industrial communications
Hardware compatibility 5P, 5PX, 9130, 9PX, 9PXM, 9SX, 93PM, 93E Compatible with IPv4/IPv6 TLS 1.2
Catalog number INDGW-M2
Protocol support HTTPS, TLS 1.2, SNMPv1, SNMPv3, NTP, TFTP, SMTP, SMTPS, BOOTP, DHCP, SLAAC, SSH, MQTTS, ModbusTCP, Modbus RTU,
BACnet IP, BACnet BBMD
UPS slot type Mini-Slot
Network support Ethernet 10/100/1000BaseT
Temperature and Yes, only with the Eaton Environmental Monitoring humidity monitoring Probe Gen 2
Software support Intelligent Power Manager 1.61 and higher (visit Eaton.com/IPM for all power management capabilities including hyperconverged infrastructure), Intelligent Power Protector 1.61 and higher (visit Eaton.com/IPP for a full compatibility operating system matrix), any SNMP compliant Network Management System (NMS)
Supported MIB MIB II – Standard IETF UPS MIB (RFC 1628) – Eaton xUPS MIB Supported browsers Chrome and Firefox
Local language support English, French, German, Italian, Spanish, Chinese Simplified, Chinese Traditional, Japanese, Russian
Operating temperature 32 to 104° F (0 to 40° C)
Operating humidity 90% RH max. without condensation
Power input 5 V – 12 V
Current consumption 500/1000mA max. depending on UPS
Dimensions (H x W x D) 5.2 x 2.6 x 1.7 in. (132.08 x 66.04 x 43.18 mm) Weight 2.5 oz. (71 g)
Regulatory Same as UPS
For more information, please visit:
Eaton.com/INDGW-M2
1. Due to continuous product improvements, program specifications are subject to change without notice.
Follow us on social media to get the
latest product and support information.
Product brochure
62 of 92
Specifications/Technical characteristics
Information – 164
6.3 Specifications/Technical characteristics
Physical characteristics
Dimensions (wxdxh) 132 x 66 x 42 mm | 5.2 x 2.6 x 1.65 in Weight 70 g | 0.15 lb
RoHS 100% compatible
Storage
Storage temperature -25°C to 70°C (14°F to 158°F)
Ambient conditions
Operating temperature 0°C to 70°C (32°F to 158°F)
Relative humidity 5%-95%, noncondensing
Module performance
Module input power 5V-12V ±5% | 1A
AUX output power 5V ±5% | 200mA
Date/Time backup CR1220 battery coin cell | The RTC is able to keep the date and the time when Network Module is OFF
Functions
Languages English, French, Italian, German, Spanish, Japanese, Alarms/Log Email, SNMP trap, web interface / Log on events Network Gigabit ETHERNET, 10/100/1000Mb/s, auto negotiation, HTTP 1.1, SNMP V1, SNMP V3,
NTP, SMTP, DHCP
Security Restricted to TLS 1.2
Supported MIBs xUPS MIB | Standard IETF UPS MIB (RFC 1628) | Sensor MIB Browsers Internet Explorer, Google Chrome, Firefox, Safari Settings (default values)
IP network DHCP enabled | NTP server: pool.ntp.org
Port 443 (https), 22 (ssh), 161 (snmp), 162 (snmp trap), 25 (smtp), 8883 (mqtts), 123 (ntp), 5353 (mdns-sd), 80 (http), 514 (syslog),636 (LDAP), 1812 (RADIUS) 63 of 92
List of event codes
Information – 165
Web interface access control User name: admin | Password: admin Settings/UPS data connector USB RNDIS Apipa compatible | IP address: 169.254.0.1 | Subnet mask: 255.255.0.0
6.4 List of event codes
To get access to the Alarm log codes or the System log codes for email subscription, see the Alarm log codes and System log codes sections.
6.5 Alarm log codes
6.5.1 Critical
Code Severity Active message Non-active message Advice
002 Critical Internal failure End of internal failure Service required 004 Critical Temperature alarm Temperature OK Check air conditioner 007 Critical Fan fault Fan OK Service required
00F Critical Parallel UPS not compatible Parallel UPS compatibility OK Service required 010 Critical UPS power supply fault UPS power supply OK Service required 011 Critical Parallel UPS protection lost Parallel UPS protection OK Reduce output load 012 Critical Parallel UPS measure
inconsistent
Parallel UPS measure OK Service required
100 Critical Rectifier fuse fault Rectifier fuse OK Service required 105 Critical Input AC module failure Input AC module OK Service required 110 Critical Building alarm (through dry
contact)
Building alarm OK - 11F Critical Building alarm (through Network module)
Building alarm OK - 202 Critical Bypass thermal overload Bypass thermal OK Reduce output load 203 Critical Bypass temperature alarm Bypass temperature OK Check air conditioner 207 Critical Bypass AC module failure Bypass AC module OK - 208 Critical Bypass overload No bypass overload - 305 Critical Rectifier failure Rectifier OK Service required To retrieve Alarm logs, navigate to Alarm section and press the Download alarms button. 64 of 92
Alarm log codes
Information – 166
306 Critical Rectifier overload Rectifier OK Reduce output load 308 Critical Rectifier short circuit Rectifier OK Reduce output load 400 Critical DCDC converter failure DCDC converter OK Service required 500 Critical Battery charger fault Battery charger OK Service required 600 Critical Battery fuse fault Battery fuse OK Service required 602 Critical Battery fuse fault Battery fuse OK Service required 604 Critical Battery low Battery OK - 607 Critical Battery test failed Battery test OK Check battery 60D Critical No battery Battery present Check battery
629 Critical Battery voltage low critical Battery voltage OK Check battery 62B Critical Battery voltage high critical Battery voltage OK Check battery 62D Critical Battery charge current low
critical
Battery charge current OK Check battery
62F Critical Battery charge current high
critical
Battery charge current OK Check battery
631 Critical Battery discharge current low
critical
Battery discharge current OK Check battery
633 Critical Battery discharge current
high critical
Battery discharge current OK Check battery
635 Critical Battery temperature low
critical
Battery temperature OK Check battery
637 Critical Battery temperature high
critical
Battery temperature OK Check battery
63E Critical Battery fault Battery OK Check battery
700 Critical Inverter limitation No current limitation Reduce output load 701 Critical Inverter fuse fault Inverter fuse OK Service required 704 Critical Inverter internal failure UPS OK Service required 705 Critical Inverter overload No power overload Reduce output load 706 Critical Temperature alarm Temperature OK Check air conditioner 70A Critical Inverter thermal overload No power overload Reduce output load 70B Critical Inverter short circuit End of inverter short circuit Service required 65 of 92
Alarm log codes
Information – 167
802 Critical Shutdown imminent Shutdown canceled - 805 Critical Output short circuit Output OK Reduce output load 806 Critical Emergency power OFF No emergency OFF - 811 Critical Parallel negative power Parallel power OK Reduce output load 814 Critical Firmware watchdog reset Firmware watchdog OK Service required 815 Critical Calibration fault Calibration OK Service required 81E Critical Load unprotected Load protected - 900 Critical Maintenance bypass Not on maintenance bypass - 1201 Critical Temperature is critically low
(EMP)
Temperature is back to low
(EMP) - 1204 Critical Temperature is critically high
(EMP)
Temperature is back to high
(EMP) - 1211 Critical Humidity is critically low
(EMP)
Humidity is back to low (EMP) - 1214 Critical Humidity is critically high (EMP)
Humidity is back to high
(EMP) - 6.5.2 Warning
Code Severity Active message Non-active message Advice
001 Warning On battery No more on battery - 00B Warning Parallel UPS redundancy lost Parallel UPS redundancy OK Reduce output load 00E Warning Parallel UPS communication
lost
Parallel UPS communication
OK
Service required
103 Warning Utility breaker open Utility breaker closed - 104 Warning Input AC frequency out of
range
Input AC frequency in range -
106 Warning Input AC not present Input AC present - 107 Warning Input bad wiring Input wiring OK Check input wiring 108 Warning Input AC voltage out of range
(-)
Input AC voltage in range -
66 of 92
Alarm log codes
Information – 168
109 Warning Input AC voltage out of range
(+)
Input AC voltage in range -
10A Warning Input AC unbalanced End of input AC unbalanced - 200 Warning Bypass phase out range Bypass phase in range - 201 Warning Bypass not available Bypass available Service required 204 Warning Bypass breaker open Bypass breaker closed - 205 Warning Bypass mode No more on bypass - 206 Warning Bypass frequency out of range
Bypass frequency in range -
209 Warning Bypass voltage out of range Bypass voltage in range - 20A Warning Bypass AC over voltage End of bypass AC over voltage
- 20B Warning Bypass AC under voltage End of bypass AC under voltage
- 20C Warning Bypass bad wiring Bypass wiring OK Check bypass wiring 300 Warning DC bus + too high DC bus + voltage OK Service required 301 Warning DC bus - too high DC bus - voltage OK Service required 302 Warning DC bus + too low DC bus + voltage OK Service required 303 Warning DC bus - too low DC bus - voltage OK Service required 304 Warning DC bus unbalanced DC bus OK Service required 501 Warning Charger temperature alarm Charger temperature OK Service required 502 Warning Max charger voltage Charger voltage OK Service required 503 Warning Min charger voltage Charger voltage OK Service required 603 Warning Battery discharging End of UPS battery discharge - 605 Warning Battery temperature alarm Battery temperature OK Service required 606 Warning Battery breaker open Battery breaker closed Service required 610 Warning Battery low voltage Battery voltage OK Check battery 613 Warning Battery voltage too high Battery voltage OK Check battery 616 Warning Battery voltage unbalanced Battery voltage OK Check battery 61C Warning Communication with battery
lost
Communication with battery
recovered
Check battery
67 of 92
Alarm log codes
Information – 169
61E Warning At least one breaker in
battery is open
All battery breakers are
closed
Check battery
61F Warning Battery State Of Charge
below limit
Battery State Of Charge OK -
620 Warning Battery State Of Health
below limit
BatteryState Of Health OK Check battery
628 Warning Battery voltage low warning Battery voltage OK Check battery 62A Warning Battery voltage high warning Battery voltage OK Check battery 62C Warning Battery charge current low
warning
Battery charge current OK Check battery
62E Warning Battery charge current high
warning
Battery charge current OK Check battery
630 Warning Battery discharge current
low warning
Battery discharge current OK Check battery
632 Warning Battery discharge current
high warning
Battery discharge current OK Check battery
634 Warning Battery temperature low
warning
Battery temperature OK Check battery
636 Warning Battery temperature high
warning
Battery temperature OK Check battery
638 Warning Battery BMS failure Battery BMS OK Check battery 639 Warning Battery temperature
unbalanced
Battery temperature OK Check battery
63D Warning Battery warning Battery OK Check battery
70C Warning Inverter voltage too low Inverter voltage OK Service required 70D Warning Inverter voltage too high Inverter voltage OK Service required 801 Warning Load not powered Load powered - 803 Warning Output breaker open Output breaker closed - 808 Warning Power overload No power overload Reduce output load 80D Warning Internal configuration failure Internal configuration OK Service required 80E Warning Overload pre-alarm No overload pre-alarm Reduce output load 810 Warning Overload alarm No overload Reduce output load 816 Warning Compatibility failure Compatibility OK Service required 68 of 92
Alarm log codes
Information – 170
817 Warning Output over current No output over current Reduce output load 818 Warning Output frequency out of
range
Output frequency in range Service required
819 Warning Output voltage too high Output voltage OK Service required 81A Warning Output voltage too low Output voltage OK Service required 81B Warning UPS Shutoff requested End of UPS shutoff requested Service required 81D Warning Load not powered Load protected - 901 Warning Maintenance bypass breaker closed
Maintenance bypass breaker
open
- B00 Warning End of warranty End of warranty cleared - B01 Warning Batteries are aging. Consider
replacement
Batteries aging condition
cleared
- 1032 Warning Protection: immediate
shutdown in progress
Protection: immediate
shutdown completed
- 1053 Warning Protection: communication
lost with agent
Protection: communication
recovered with agent - 1200 Warning Communication lost (with EMP)
Communication recovered
(EMP) - 1202 Warning Temperature is low (EMP) Temperature is back to normal (EMP) - 1203 Warning Temperature is high (EMP) Temperature is back to normal (EMP) - 1212 Warning Humidity is low (EMP) Humidity is back to normal (EMP) - 1213 Warning Humidity is high (EMP) Humidity is back to normal (EMP) - 6.5.3 Info
Code Severity Active message Non-active message Advice
005 Info Communication lost (with
UPS)
Communication recovered
(with UPS)
Service required
009 Info On high efficiency High efficiency disabled -
013 Info Upgrading: limited
communication
End of upgrade mode -
69 of 92
Alarm log codes
Information – 171
101 Info On AVR (Boost) End of AVR (Boost) - 102 Info On AVR (Buck) End of AVR (Buck) - 63C Info Battery information Battery OK - A00 Info Group 1 is OFF Group 1 is ON - A01 Info Group 2 is OFF Group 2 is ON - A0F Info Group is OFF Group is ON - 1016 Info Protection: sequential shutdown scheduled
Protection: sequential
shutdown canceled
- 1017 Info Protection: sequential
shutdown in progress
Protection: sequential
shutdown completed
- 1054 Info Protection: agent is in
unknown state
Protection: agent is in service -
1055 Info Protection: agent is starting Protection: agent is in service - 1056 Info Protection: agent is
stopping
Protection: agent is in service -
1057 Info Protection: agent is stopped Protection: agent is in service - 1100 Info Schedule: shutdown date
reached
Schedule: shutdown initiated -
1101 Info Schedule: restart date
reached
Schedule: restart initiated -
1300 Info No UPS connected Communication recovered
(with UPS) - 1301 Info UPS not supported Communication recovered (with UPS) - 6.5.4 With settable severity
Code Severity Active message Non-active message Advice
1221 Settable Contact is active (EMP) Contact is back to normal (EMP) - 70 of 92
Eaton Environmental Monitoring Probe Gen 2
The Eaton Environmental Monitoring Probe (EMP) Gen 2
(EMPDT1H1C2) is a second-generation environmental monitoring probe for the Eaton Gigabit Network Card and Eaton rack PDUs including G3 (firmware 4.x or later), G3HD and G3+. The new EMP maintains all the functionality of the previous generation of sensors (temperature, humidity and dry-contact monitoring) while adding the ability to be daisy-chained (up to 3 per host), allowing multiple sensors to connect to a single host. For optimum air intake measurement within an enclosure, the EMP Gen 2 provides tie wrap mounting options for front and rear door perforation to specifically measure air flow at the intake point. This enhances the richness of rack-level environmental data for the top, middle and bottom of the rack.
Eaton EMP Gen 2 installed on UPS
Technical specifications1
Eaton Environmental Monitoring Probe Gen 2
Type Environmental monitoring device
Compatible with Network-M2 and Eaton rack PDUs including G3 (firmware 4.x or later), G3HD and G3+
Mounting options The EMP Gen 2 includes bottom and side mounting capabilities for both UPS and PDU installation – see diagram below
Sensor capability Temperature, humidity and two dry-contact sensors for expansion Measurement accuracy Measure temperatures from 0°C to 70°C with an accuracy of ±2°C and relative humidity from 10% to 90% with an accuracy of ±5% Catalog number EMPDT1H1C2
Dimensions (H x W x D) 2.26 x 1.48 x 1.15 in. (57.6 x 37.6 x 29.3 mm) Weight 1.19 oz. (34 g)
Eaton EMP Gen 2 daisy chained on
rack PDU
1. Due to continuing improvements, specifications are subject to change without notice. 1 1
2 2 2
2 2
2 2
2 3
3 3 4
4 3
Mounting options
1 2
3 4
Nylon fastener location
Tie wrap holes
Magnets
Keyholes
Product brochure
71 of 92
Default configuration
Industrial Relay Card-MS
(INDRELAY-MS)
P-164000296 Rev 6
Quick Start Guide
The Industrial relay Card-MS (INDRELAY-MS) provides a
simple way to remotely input UPS information to an alarm system, PLC or a computer system via dry contacts.
It offers five isolated dry contact outputs and one isolated dry contact input.
Relays K1 through K5 are identical in function. In some UPS each output contact function can be assigned by the customer. Please refer to the UPS manual for details.
To Install the INDRELAY-MS:
1. Verify that the ancillary equipment system is turned off and all power sources are removed. Refer to the
appropriate ancillary equipment operation manual for
shutdown instructions.
2. Install wiring from the card to the monitoring equipment using appropriate conduits through the cable exit
opening in the cover plate of the card.
3. Connect wiring between the card’s terminal blocks
and the customer's monitoring equipment using
terminations. Connect one wire to COM (Common)
and another to either NC or NO to select the
Normally Open or Normally Closed option.
4. Install the card into an open MiniSlot
communication bay in the UPS. Refer to the
appropriate UPS installation and operation manual
for the location of the MiniSlot bays.
5. To check the operation of the INDRELAY-MS, ensure
that the UPS system is supplying the load via inverter
or bypass. Refer to the operation section of the
appropriate UPS installation and operation manual
for operating instructions and output configuration.
If the indicators on the monitoring equipment show
the appropriate status, then it is operating correctly.
If the INDRELAY-MS is not operating correctly, check
the wiring and the connections for proper seating. If
all connections are secure but the card still does not
operate correctly contact your Eaton service
representative. Cable Exit Opening for
up to 12.7mm (1/2”)
Conduit NOTE Maximum contact rating: 250 Vac, 30 Vdc @ 8A Wire Range: 12–22 AWG (0.5-2.5mm2
)
K1 thru K5 Terminal
Connections from Relay
Contacts to Customer's
Monitoring Equipment
Signal Input Connector
with Voltage Supply.
Wire this voltage supply to
the signal input through a
dry contact or switch to
activate the input signal.
K1 Active when Normal indicator is lit.
K2 Active when On Battery Indicator is lit.
K3 3 phase: Active when Alarm Indicator is lit.
1 phase: Active on battery failure.
K4 Active when On Bypass Indicator is lit
K5 Active when Low battery warning is active
This card may contain LETHAL VOLTAGES. All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY. This card is not user serviceable.
72 of 92
Tab 9
Startup and Testing
Scope of Work
73 of 92
Scope of Work Attachment L-2
Revised 7/19
Start-Up Scope of Work
Attachment L-2
This scope of work is shared by UPS, Eaton DC, Eaton PDU/PDR/RPP/STS, Flywheel, Non-Eaton UPS and Distributed Bypass. The following is an outline of general procedures and tests, if applicable, that are normally performed by Field Service Personnel during a standard start-up for new units or to recertify and restart a previously started UPS. All checks and processes may not be applicable to all equipment models.
Start-up does not include special entrance requirements (ex. site specific training; background / drug screening), working in confined space installations, those that require fall protection or exposure to hazardous environmental conditions. Contact your local Service management if any of these conditions apply.
UPS/PDU/RPP/STS START-UP PROCEDURE
1. VISUAL INSPECTION
1.1. Visually inspect all equipment for signs of shipping damage and/or foreign materials.
1.2. Check all battery cells for proper electrolyte levels.
1.3. Observe type of ventilation, room cleanliness, use of proper signs and any safety related items that may be noteworthy
2. MECHANICAL INSPECTION
2.1. Check internal power connections in UPS module for tightness while observing proper safety precautions.
2.2. Check all control wiring terminations and plugs in UPS module for tightness and/or proper setting.
2.3. Check to see that all factory connections, power modules, subassembly pans and legs are secure.
2.4. Inspect the ISBM or IOM (inspect auxiliary connections)
3. ELECTRICAL PRECHECK
3.1. Check system for ground faults at all power inputs and outputs
3.2. Check DC bus for short circuits and proper polarity.
3.3. Checks input and bypass power terminations for proper voltages and phase rotation inside all modules.
3.4. Check and adjust, if necessary, all power supply voltages.
3.5. Verify CTO and Serial numbers programmed into system match the equipment labels
4. INITIAL UPS, PDU ENERGIZATION
4.1. Verify all system annunciations are in "go" condition.
4.2. Energize unit(s) and verify proper DC walkup and AC phase on.
4.3. Check DC link holding voltage, AC output voltages and output waveforms.
4.4. Check final DC link voltage and inverter AC output. Adjust if required.
4.5. Check for proper synchronization with bypass source.
4.6. Check voltage differences between inverter outputs and bypass source.
5. INITIAL DC SYSTEM ENERGIZING
5.1. Installation of one rectifier
74 of 92
Scope of Work Attachment L-2
Revised 7/19
5.2. Initial power up of equipment
5.3. Verification of correct voltage / polarity for rectifiers
5.4. Installation of all rectifiers
5.5. Verification of proper operation of rectifiers
5.6. Verification of proper operation of the system controller
6. BATTERY SET-UP
6.1. Determine common or separate battery set-up process and settings
6.2. Check for proper cell interconnections with respect to polarity throughout battery.
6.3. Check battery configuration matches required unit configuration (voltage, polarity, number of cells per string)
7. BRANCH CIRCUIT MONITORING SET-UP (if optionally purchased)
7.1. Ensure installation configuration matches application
7.2. Perform branch circuit breaker scheduling
7.3. Check voltage and current calibrations
8. OPERATIONAL INSPECTION
8.1. Check proper system operation in Normal Mode, Bypass Mode, and Battery Mode
8.2. Check system transitions between operating modes
8.3. Check multi-module operations
8.4. Verify system calibrations and adjust as necessary
9. FUNCTIONAL TEST
9.1. Test Battery mode
9.2. Simulate the loss of bypass when on battery testing
9.3. Perform ISBM loss of logic power testing
9.4. Emergency transfer testing
9.5. Local and Remote Emergency Power Off testing
9.6. Mini CSB Failure testing
9.7. Fan Failure Test (ONLY PERFORM IF NO LOAD IS APPLIED)
9.8. Building Alarms testing
9.9. Basic Easy Capacity testing
10. INSTALL PREDICTPULSETM REMOTE MONITORING SERVICE
10.1. PredictPulse Service Description and Customer Requirements
10.1.1. Contractor will provide the PredictPulse Service on subscribed Covered Equipment. The PredictPulse Service shall include alarm notifications via a dashboard, mobile application, and monthly report summarizing alarms and Equipment Data.
10.1.1.1. Access to the PredictPulse Service shall be from Contractor’s web portal and include Covered Equipment status, alarms, reports and service history.
10.1.1.2. Contractor’s obligation shall be to enable enrollment in the PredictPulse Service by Customer, validation of the PredictPulse Service, and to notify Customer contact when a critical alarm occurs.
10.1.1.3. Contractor will remotely diagnose critical alarms and if appropriate, resolve emergency events as if Customer has requested Covered Equipment Service, enabling Contractor to arrive at the location of the Covered Equipment per the contracted CPM hours. If subscribed Covered Equipment has no contracted Covered 75 of 92
104 Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 06 After the installation is complete, an Eaton Customer Service Engineer must verify the operation of the UPS system and commission it to support the critical load. The service representative cannot perform any installation tasks other than verifying software and operating setup parameters. Service personnel may request a copy of the completed Installation Checklist to verify all applicable equipment installations have been completed.
NOTE The Installation Checklist MUST be completed prior to starting the UPS system for the first time.
4.10 Installation Checklist
o All packing materials and restraints have been removed from each cabinet. o The UPS cabinet is placed in its installed location.
o All conduits and cables are properly routed to the UPS and any ancillary cabinets. o All power cables are properly sized and terminated.
o Battery cables are terminated on E4 (+) and E5 (–).
o Battery shunt trip signal wiring is connected from the UPS to the battery disconnect. o Battery detect signal wiring is connected from the UPS to the battery disconnect. o A ground conductor is properly installed.
o Building alarms and alarm relays are wired appropriately. (Optional) o LAN drops are installed. (Optional)
o LAN connections have been completed. (Optional)
o The REPO device is mounted in its installed location and its wiring is terminated inside the UPS cabinet. (Optional)
o A jumper wire is connected between pins 3 and 4 on the REPO terminal block if using a normally-closed REPO switch. (Optional)
o All internal safety shields are installed.
o Accessories are mounted in installed locations and wiring is terminated inside the UPS cabinet. (Optional) o Air conditioning equipment is installed and operating correctly. o The area around the installed UPS system is clean and dust-free. (Eaton recommends that the UPS be installed on a level floor suitable for computer or electronic equipment.) o Adequate workspace exists around the UPS and other cabinets. o Adequate lighting is provided around all UPS equipment. o A 120 Vac service outlet is located within 7.5m (25 ft) of the UPS equipment. o Startup and operational checks are performed by an authorized Eaton Customer Service Engineer for parallel systems or installations with accessory cabinets.
o Visit www.eaton.com/pq/register to register your new Eaton UPS / Eaton UPS Accessory.
UPS System Installation
76 of 92
Performance Testing
Scope of Work
Attachment L-5
This scope of work is shared by UPS, Eaton DC, Eaton PDU/PDR/RPP/STS, Flywheel, Non Eaton UPS and Distributed Bypass. The following is an outline of general procedures and tests, if applicable, that are normally performed by Field Service Personnel during the course of Performance Testing. All checks and processes may not be applicable to all equipment models. Method of procedure is written assuming a UPS is being tested.
LOAD BANK
Eaton will supply a load bank and a technical resource to test the UPS’s performance at various load steps. It is important to locate the load bank in an area suitable for heat rejection. 50 feet of cabling will be provided to position the load bank in an area where heat can safely be dissipated away from sensitive equipment. Additional cabling can be added upon request to allow heat to dissipate in a suitable location.
A certified electrician is required to make connections from the load bank to the UPS before testing. It is the responsibility of the electrician to unload/load the load bank and layout/pickup cable associated with the load bank.
IR SCAN
During the course of the testing an infrared (IR) camera will be used to identify any hotspots within the UPS and battery cabinets that show a higher temperature than normal. Any visible hotspots will be noted, and the actual temperatures are recorded for future reference. Thermographs (infrared photographs) will be taken and included in a subsequent written report.
PQ METER
During the course of the testing a PQ metering device will be used to record voltages, currents, and harmonic content at the output of the UPS. Any irregularities will be noted and included in a subsequent written report.
METHOD OF PROCEDURE
1. Verify the electrical infrastructure can support both critical load and the artificial load from the load bank simultaneously.
2. Receive approval from the electrician and/or site personnel to proceed with testing based on the infrastructure verification.
3. Transfer critical load to bypass.
4. Transfer critical load to maintenance bypass (if applicable).
5. Shut down UPS module(s)
6. Lockout tag-out performed (if applicable).
7. Electrician connects load bank to the output of the system.
8. Restart UPS module(s) and transfer to system normal.
9. Apply 50% load for a duration of one hour.
10. Perform IR scan to identify any hotspots
11. Observe the voltage, current, power regulation, harmonic content and the like for abnormalities.
12. Apply 100% load for a period of 3 hours.
13. Perform IR scan to identify any hotspots
14. Observe the voltage regulation, harmonic content and the like for abnormalities with PQ Meter.
15. Perform a battery discharge (for up to 4 minutes is recommended) by opening the rectifier input to the UPS system.
77 of 92
16. Perform IR scan to identify any hotspots during the battery discharge.
17. Monitor the UPS operating parameters during the battery discharge.
18. Restore rectifier input to the UPS system and allow for battery recharge.
19. Transfer UPS system to bypass.
20. Transfer UPS system to normal.
21. Repeat transfer 3X.
22. Transfer UPS to bypass.
23. Remove load from load bank.
24. Isolate power to load bank and electrician should remove connections to load bank.
25. Remove lockout tag-out (if applicable).
26. Transfer load from maintenance bypass back to bypass.
27. Transfer critical load to normal.
28. Procedure is complete.
A report shall be provided to the customer documenting test results. 78 of 92
Tab 10
Specifications
79 of 92
16 Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 06 Table 2. Air Conditioning or Ventilation Requirements During Full Load Operation Model UPS Rating
Max Heat Dissipation at 100%
Load
KW (BTU/Hr)
Minimum Required
Cooling Air Flow
Eaton 93PM-L 60-1
Eaton 93PM-L 60-2 (N+1) 10 kW .90 (3063) 130 liter/sec (275 cfm) 212 liter/sec (450 cfm)
Eaton 93PM-L 60-1
Eaton 93PM-L 60-2 (N+1) 20 kW 1.80 (6125) 130 liter/sec (275 cfm) 212 liter/sec (450 cfm)
Eaton 93PM-L 60-2
Eaton 93PM-L 60-3 (N+1) 30 kW 2.69 (9188) 212 liter/sec (450 cfm) 295 liter/sec (625 cfm)
Eaton 93PM-L 60-2
Eaton 93PM-L 60-3 (N+1) 40 kW 3.59 (12250) 212 liter/sec (450 cfm) 295 liter/sec (625 cfm)
Eaton 93PM-L 60-3 50 kW 4.49 (15313) 295 liter/sec (625 cfm) Eaton 93PM-L 60-3 60 kW 5.39 (18375) 295 liter/sec (625 cfm) The UPS equipment operating environment must meet the weight requirements shown inTable 3 through Table 5 and the size requirements shown in Figure 4 through Figure 15. Dimensions are in millimeters (inches).
Table 3. 93PM-L 60 kW UPS Cabinet Weights
Model
Number
of UPMs
Number of
Battery Strings
Weight kg (lb)
Shipping Installed Point Loading
Eaton 93PM-L
60 kW UPS
1 UPM Installed
0 Battery Strings 290 (637) 259 (570) 4 at 65 (143)
2 Battery Strings 515 (1132) 484 (1065) 4 at 121 (266)
3 Battery Strings 604 (1327) 573 (1260) 4 at 143 (315)
4 Battery Strings 692 (1522) 661 (1455) 4 at 165 (364)
2 UPMs Installed
0 Battery Strings 321 (706) 290 (639) 4 at 73 (160)
(1+1), 2 Battery Strings 546 (1396) 515 (1134) 4 at 129 (284) 3 Battery Strings 635 (1396) 604 (1329) 4 at 151 (332)
4 Battery Strings 724 (1591) 693 (1524) 4 at 173 (381)
3 UPMs Installed
0 Battery Strings 353 (775) 322 (708) 4 at 81 (177)
(2+1), 3 Battery Strings 666 (1465) 635 (1398) 4 at 159 (350) 4 Battery Strings 755 (1660) 724 (1593) 4 at 181 (398)
UPS Installation Plan and Unpacking
80 of 92
Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 05 151 Chapter 9 Product Specifications
9.1 Models
The UPS is housed in a free-standing cabinet with safety shields behind the door. The UPS is available in 50 or 60 Hz with various output power ratings.
Model Power Rating
Eaton 93PM-L 60-1
Eaton 93PM-L 60-2 (N+1) 10 kW
Eaton 93PM-L 60-1
Eaton 93PM-L 60-2 (N+1) 20 kW
Eaton 93PM-L 60-2
Eaton 93PM-L 60-3 (N+1) 30 kW
Eaton 93PM-L 60-2
Eaton 93PM-L 60-3 (N+1) 40 kW
Eaton 93PM-L 60-3 50 kW
Eaton 93PM-L 60-3 60 kW
9.2 Specifications
The following sections detail the input, output, environmental, and battery specifications for the UPS.
9.2.1 UPS Input
Operating Input Voltage
Rectifier: 208 or 220 Vac Wye, 3W + ground. Neutral not used.
Bypass: 208 or 220 Vac Wye, 4W + ground.
Operating Input Frequency Range 50/60 Hz
Operating Input Current See Table 9 through .
Reduced for Generator
Adjustable
Input Current Harmonic Content ≤ 3.5% THD at full load
Power Factor Minimum 0.99
Line Surges 6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801 4 Battery Voltage 240 cell – 480Vdc
Battery Charging Capacity 17 A maximum per 20 kW module at full load at nominal input voltage
9.2.2 UPS Output
UPS Output Capacity 100% rated current
Output Voltage Regulation ± 1% (10% to 100% load)
81 of 92
152 Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 05 Output Voltage 208 or 220 Vac Wye, 3W or 4W + ground
Output Voltage Harmonic Content < 1.6% maximum THD (linear load) 5% maximum THD (nonlinear load)
Output Current See Table 9 through .
Output Voltage Balance < 2% for 100% maximum load imbalance (linear load) Output Voltage Phase Displacement < 2.5° for 100% maximum load imbalance (linear load) Frequency Regulation 0.1 Hz free running
Synchronous to Bypass ± 4 Hz (default setting)
Frequency Slew Rate 1 Hz per second (default setting)
Load Compatibility 0.8 pF Leading
0.8 pF Lagging
Overload Capability <110% for 10 minutes
<125% for 60 seconds
<150% for 10 seconds
>150% for 300 milliseconds
9.2.3 UPS Environmental
Operating Temperature 5 to 40° C (41 to 104° F) without derating. The recommended operating temperature is 25° C (77 °F).
Operating Altitude Maximum 1500m (5000 ft) at 40° C without derating Storage Temperature -25 to +55° C, excluding batteries (prolonged storage above 40° C causes rapid battery self-discharge)
Relative Humidity (operating and
storage)
5 to 95%, noncondensing
Acoustical Noise 60 kW at 100% load – 65 dBA at a 1m distance, per ISO 7779 Agency Markings Safety: UL1778 5th Ed./CSA22.2 No. 107.3–14 3rd Ed.
EMI Emissions Meets IEC 62040-2 C2, CISPR 22, VCCI and FCC Part 15 Subpart B Class A limits.
Immunity / Electrostatic Discharge
(ESD)
Meets IEC 61000-4-2 Level 3 specifications and CISPR 24. Withstands up to 4 kV contact pulse without damage and with no disturbance or adverse effect to the critical load.
Product Specifications
82 of 92
Tab 11
Warranties and
Terms & Conditions
83 of 92
Eaton 93PM UPS (20–100 kW, 480V – 100 kW Frame) Installation and Operation Manual P-164000227—Rev 5 www.eaton.com/powerquality W-1 Warranty
LIMITED FACTORY WARRANTY FOR THREE-PHASE EATON® 93PM UPS AND 93PM UPS ACCESSORY PRODUCTS WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Corporation, an Ohio Corporation (”Eaton”).
LIMITED WARRANTY: This limited warranty (this ”Warranty”) applies only to the original end-user (the ”End-User”) of the Eaton Three-Phase 93PM UPS and 93PM UPS Accessory Products (the ”Product”) and cannot be transferred. This restriction applies even in the event that the Product is initially sold by Eaton for resale to an EndUser. This Warranty gives you specific legal rights, and you may also have other rights which vary from State to State (or jurisdiction to jurisdiction).
WHAT THIS LIMITED WARRANTY COVERS: The warrantor warrants, with the terms of this Warranty, that the Eaton three-phase UPS electronics, Eaton-built accessories, and Eaton -built battery cabinets (individually and collectively, the ”Warranted Items”) are free from defects in material and workmanship.
For Product installed (and currently located) in the fifty (50) United States and the District of Columbia, if, in the opinion of Eaton, a Warranted Item is defective, Eaton's sole obligation, at the option of Eaton, will be to refurbish or replace such defective Warranted Item (including the costs of providing diagnosis, service, and labor [“labor coverage”]). The defective Warranted Item will be refurbished or replaced onsite at the End-User's location or such other location as determined by Eaton. Any parts that are replaced may be new or reconditioned. All parts replaced by Eaton shall become the property of Eaton.
For Product installed (and currently located) outside the fifty (50) United States and the District of Columbia, if, in the opinion of Eaton, a Warranted Item is defective, Eaton's sole obligation, at the option of Eaton, will be to refurbish or replace such defective Warranted Item (not including the costs of labor coverage). The defective Warranted Item will be refurbished or replaced onsite at the End-User's location or such other location as determined by Eaton. Any parts that are replaced may be new or reconditioned. All parts replaced by Eaton shall become the property of Eaton.
LIMITED WARRANTY PERIOD: The period covered by this Warranty for Product installed (and currently located) in the fifty (50) United States and the District of Columbia is six (6) months from the date of Product purchase for labor coverage when no startup is performed by an authorized Eaton Customer Service Engineer or Agent or twelve (12) months from the date of Product purchase with startup performed by an authorized Eaton Customer Service Engineer or Agent and twelve (12) months from the date of Product purchase or eighteen (18) months from date of Product shipment, whichever occurs first, for the refurbishment/ replacement of parts.
The period covered by this Warranty for Product installed (and currently located) outside the fifty (50) United States and the District of Columbia is twelve (12) months from the date of Product purchase or eighteen (18) months from the date of Product shipment, whichever occurs first, for the refurbishment/replacement of parts.
WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages caused by: (a) failure to properly store the Product before installation, including the ”trickle charge” of batteries no later than the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect, accident, fire, flood, lightning, vandalism, acts of God, Customer's neglect, abuse, misuse, misapplication, incorrect installation; (d) repair or alteration not authorized in writing by Eaton personnel or performed by an authorized Eaton Customer Service Engineer or Agent; or (e) improper testing, operation, maintenance, adjustment, or any modification of any kind not authorized in writing by Eaton personnel or performed by an authorized Eaton Customer Service Engineer or Agent.
This Warranty is not valid: if the Product's serial numbers have been removed or are illegible. Any Warranted Items repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the original Warranty subject to all the terms thereof. Eaton does not provide a labor warranty for Product located outside of the fifty (50) United States or the District of Columbia. Any equipment, parts, or materials included in the Product and not manufactured by Eaton are warranted solely by the manufacturer of such equipment, parts, or materials and are not included as part of this Warranty. Batteries are not warranted by Eaton. 84 of 92
Warranty
W-2 Eaton 93PM UPS (20–100 kW, 480V – 100 kW Frame) Installation and Operation Manual P-164000227—Rev 5 www.eaton.com/powerquality THIS WARRANTY IS THE ENDUSER'S SOLE REMEDY AND IS EXPRESSLY IN LIEU OF, AND THERE ARE
NO OTHER, EXPRESSED OR IMPLIED GUARANTEES OR WARRANTIES (INCLUDING ANY IMPLIED
WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PURPOSE, WHICH ARE EXPRESSLY DISCLAIMED). SOME STATES OR JURISDICTIONS DO NOT ALLOW THE EXCLUSION OF EXPRESS OR IMPLIED WARRANTIES, SO THE ABOVE EXCLUSION MAY NOT APPLY TO YOU. IN THAT EVENT, SUCH WARRANTIES ARE LIMITED IN DURATION TO THE LIMITED WARRANTY PERIOD. SOME STATES OR
JURISDICTIONS DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS OR
THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATIONS AND/OR EXCLUSIONS MAY NOT APPLY TO YOU.
LIMITATION OF LIABILITY: In no event shall Eaton be liable for any indirect, incidental, special or consequential damages of any kind or type whatsoever, resulting from or in connection with any claim or cause of action, whether brought in contract or in tort (including negligence and strict liability). Some States or jurisdictions do not allow the exclusion of limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. Eaton shall not be responsible for failure to provide service or parts due to causes beyond Eaton's reasonable control. In no case will Eaton's liability under this Warranty exceed the replacement value of the Warranted Items.
END-USER'S OBLIGATIONS: In order to receive the benefits of this Warranty, the End-User must register the product warranty (via mail or online at www.powerquality.eaton.com/ProductRegistration “product registration”); use the Product in a normal way; follow the Product's user's guide; and protect against further damage to the Product if there is a covered defect.
OTHER LIMITATIONS: Eaton's obligations under this Warranty are expressly conditioned upon receipt by Eaton of all payments due to it (including interest charges, if any). During such time as Eaton has not received payment of any amount due to it for the Product, in accordance with the contract terms under which the Product is sold, Eaton shall have no obligation under this Warranty. Also during such time, the period of this Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts.
COSTS NOT RELATED TO WARRANTY: The End-User shall be invoiced for, and shall pay for, all services not expressly provided for by the terms of this Warranty, including without limitation site calls involving an inspection that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials, freight charges, travel expenses, or labor of Eaton representatives outside the terms of this Warranty will be borne by the End-User.
OBTAINING WARRANTY SERVICE: In the USA, call the Eaton Customer Reliability Center 7x24 at 800-843-9433. Outside of the USA, call your local Eaton sales or service representative, or call the Eaton Customer Reliability Center in the United States at 919845-3633. For comments or questions about this Limited Factory Warranty, write to the Customer Quality Representative, 8609 Six Forks Road, Raleigh, North Carolina 27615 USA.
85 of 92
Eaton Corporation
W-1 Eaton Battery Limited Factory Warranty
Revised date: January 22, 2013
LIMITED FACTORY WARRANTY FOR EATON BATTERY PRODUCTS
WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Corporation, an Ohio Corporation (“Eaton”).
LIMITED WARRANTY: This limited warranty (this “Warranty”) applies only to the original Purchaser (the “End-User”) of the Eaton brand VRLA Battery Products (the “Product”) and cannot be transferred. This restriction applies even in the event that the Product is initially sold by Eaton for resale to an End-User. This Warranty gives you specific legal rights, and you may also have other rights which vary from State to State (or jurisdiction to jurisdiction).
WHAT THIS LIMITED WARRANTY COVERS: Eaton warrants, within the terms of this Warranty, that the Eaton brand VRLA Battery Products, (individually and collectively, the “Warranted Items”) are free from defects in material and workmanship. A battery will not be considered defective or nonconforming if it has delivered at least eighty percent (80%) of its rated capacity during the Warranty Period. If a properly maintained battery fails to meet 80% of its rated capacity, Eaton will replace the battery part or apply credit towards the purchase of a new battery.
For Product installed (and currently located) in the fifty (50) United States and the District of Columbia, if, in the opinion of Eaton, a Warranted Item is defective, Eaton’s sole obligation, at the option of Eaton, will be to refurbish or replace such defective Warranted Item (including the costs of providing diagnosis, service, and labor [“labor coverage”]). The defective Warranted Item will be replaced onsite at the End-User’s location or such other location as determined by Eaton. Any parts that are replaced may be new or reconditioned. In any replacement endeavor, all parts removed by Eaton shall become the property of Eaton.
For Product installed (and currently located) outside the fifty (50) United States and the District of Columbia, if, in the opinion of Eaton, a Warranted Item is defective, Eaton’s sole obligation, at the option of Eaton, will be to refurbish or replace such defective Warranted Item (not including the costs of labor coverage). The defective Warranted Item will be refurbished or replaced onsite at the End-User’s location or such other location as determined by Eaton. Any parts that are replaced may be new or reconditioned. In any replacement endeavor, all parts removed by Eaton shall become the property of Eaton.
LIMITED WARRANTY PERIOD: The period covered by this Warranty for Product installed (and currently located) in the fifty (50) United States and the District of Columbia is twelve (12) months from the date of Product installation for labor coverage and for (a) Eaton brand batteries, two hundred (200) watts per cell and greater, thirty-six (36) months from the date of installation or forty-two (42) months from the manufacturing date code listed on the battery, whichever occurs first, or, (b) Eaton brand batteries less than 200 watts per cell, twenty-four (24) months from the date of installation or thirty (30) months from the manufacturing date code listed on the battery, whichever occurs first for the refurbishment/replacement of parts.
The period covered by this Warranty for Product installed (and currently located) outside of the fifty (50) United States and the District of Columbia is twelve (12) months from the date of Product purchase or eighteen (18) months from date of Product shipment, whichever occurs first, for the refurbishment/replacement of parts.
WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages caused by: (a) failure to properly store the Product before installation, including the "trickle charge" of batteries no later than the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c) neglect, accident, fire, flood, lightning, vandalism, acts of God, End-User’s neglect, abuse, misuse, misapplication, incorrect installation; (d) repair or alteration, not authorized in writing by Eaton personnel or performed by an authorized Eaton Customer Service Engineer or Agent; (e) improper testing, operation, maintenance, adjustment, or any modification of any kind not authorized in writing by Eaton personnel or performed by an authorized Eaton Customer Service Engineer or Agent; (f) Claims for full replacement not made within three (3) months of failure; (g) failure to have both the initial and replacement batteries installed by an authorized Eaton Corporation Service Engineer (in USA) or Agent (outside of USA); (h) claims resulting from an epidemic part failure by the battery OEM.
This Warranty is not valid: if the Product’s serial numbers or manufacturing date codes have been removed or are illegible; if each battery is not the proper size, design, and capacity for its intended applications at 25°C (77°F); if the product discharge depth and frequency exceed during the warranty period 225 Cycles at 30% depth, 185 Cycles at 50% depth or 100 Cycles at 100% depth.
86 of 92
Eaton Corporation
W-1 Eaton Battery Limited Factory Warranty
Revised date: January 22, 2013
Warranty period shall be adjusted based on operating temperatures, frequency, and depth of discharge. For every 10°C (18°F) increase in operating temperature above 25°C (77°F), the coverage period will be reduced by 50%. If the discharge rate is in excess of 4 complete discharges per month (96 or 144 complete discharges over the Coverage period), this will be considered cyclical service and thus void the warranty period. Any Warranted Items repaired or replaced pursuant to this Warranty will be warranted for the remaining portion of the original Warranty subject to all the terms thereof. Eaton does not provide a labor warranty for Product located outside of the fifty (50) United States or the District of Columbia. Non Eaton brand batteries shall pass the original manufacturer’s warranty through to the Purchaser.
THIS WARRANTY IS THE END-USER'S SOLE REMEDY AND IS EXPRESSLY IN LIEU OF, AND THERE ARE NO
OTHER, EXPRESSED OR IMPLIED GUARANTEES OR WARRANTIES (INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PURPOSE, WHICH ARE EXPRESSLY DISCLAIMED). SOME STATES OR
JURISDICTIONS DO NOT ALLOW THE EXCLUSION OF EXPRESS OR IMPLIED WARRANTIES, SO THE ABOVE EXCLUSION MAY NOT APPLY TO YOU. IN THAT EVENT, SUCH WARRANTIES ARE LIMITED IN DURATION TO THE LIMITED WARRANTY PERIOD. SOME STATES OR JURISDICTIONS DO NOT ALLOW LIMITATIONS ON HOW LONG
AN IMPLIED WARRANTY LASTS OR THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATIONS AND/OR EXCLUSIONS MAY NOT APPLY TO YOU.
LIMITATION OF LIABILITY: In no event shall Eaton be liable for any indirect, incidental, special or consequential damages of any kind or type whatsoever, resulting from or in connection with any claim or cause of action, whether brought in contract or in tort (including negligence and strict liability). Some States or jurisdictions do not allow the exclusion of limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. Eaton shall not be responsible for failure to provide service or parts due to causes beyond Eaton's reasonable control. In no case will Eaton's liability under this Warranty exceed the replacement value of the Warranted Items.
END-USER’S OBLIGATIONS: In order to receive the benefits of this Warranty, the End-User must; use the Product in a normal way; follow the Product’s operators and maintenance manual; and protect against further damage to the Product if there is a covered defect.
OTHER LIMITATIONS: Eaton’s obligations under this Warranty are expressly conditioned upon receipt by Eaton of all payments due from End-User (including interest charges, if any). During such time as Eaton has not received payment of any amount due to it for the Product, in accordance with the contract terms under which the Product is sold, Eaton shall have no obligation under this Warranty. Also during such time, the period of this Warranty shall continue to run and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts.
COSTS NOT RELATED TO WARRANTY: The End-User shall be invoiced for, and shall pay for, all services not expressly provided for by the terms of this Warranty, including without limitation, site calls involving an inspection that determines no corrective maintenance is required. Any costs for replacement equipment, installation, materials, freight charges, travel expenses or labor of Eaton representatives outside the terms of this Warranty will be borne by the End-User.
OBTAINING WARRANTY SERVICE: In the United States, call the Eaton Customer Reliability Center 7x24 at 800-843- 9433. Outside of the United States, call your local Eaton sales or service representative, or call the Eaton Customer Reliability Center in the United States at 919-870-3028. For comment or questions about this Limited Factory Warranty, write to the Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA. 87 of 92
COMMENTS & GENERAL CONDITIONS
Note: Your purchase order must include the following items in order for it to be processed:
• Correct vendor per the quote.
• Net 30 payment terms.
• F.O.B. terms per the quote.
1. Purchase orders issued to Eaton Corporation and/or eReps, Inc. is contingent upon Purchaser’s acceptance of the terms presented within this proposal and Eaton Corporation Terms and Conditions of Sale.
2. Eaton Corporation and/or eReps, Inc. are not responsible for the design or implementation of this job. It is the Purchaser’s responsibility to verify all equipment dimensions, lug sizes, and system requirements.
3. Standard Eaton Corporation warranty is applicable. Eaton Corporation will not extend its warranty, however, additional coverage is offered for additional cost by the means of Service packages and/or Flex packages to cover “substantial completion” or “acceptance by Owner” time period. Please inquire.
4. The following items are excluded unless specifically included in Bill of Material:
• Listed device or other approved method to preclude, detect and control thermal runaway. (CFC 608.3) • Job specific designation nameplates.
• Spare parts or extra material, unless listed in quotation. This includes but is not limited to touch-up paint, fuses, spare circuit breakers, accessory kits, test kits, and/or storage cabinet(s) for spare parts. • Seismic brackets and calculations
• Spill containment
• Floor stands
• Commissioning other than standard start-up
• Load bank testing
• Branch circuit breakers
• Battery monitoring system (i.e. Cellwatch, Alber)
• Sales Tax
• Custom O&M manuals -- O&M manuals shall be per eReps, Inc. standard
5. Proposed equipment is finished using Eaton’s standard application process and colors.
6. Freight charges are prepaid add. F.O.B. Origin. Standard Ground Shipment.
7. Delivery of equipment to any common carrier shall constitute delivery to the purchaser; and all risk of loss and damage during shipment shall pass to the purchaser at that time.
8. FOB Job Site available for an additional 2% of net cost.
9. Freight by common carrier – specific delivery windows can not be guaranteed. Additional costs will be incurred for specific delivery windows or other forms of delivery including but not limited to flat bed and lift gate.
10. Battery cabinets will ship with batteries jars installed. If Purchaser wishes to receive empty battery cabinets ahead with battery jars following at a later date, special arrangements must be made ahead of time and additional costs will be incurred (this service offering is not guaranteed with all battery and battery cabinet models and types). Dependent upon time frame of battery shipment, Eaton Corporation reserves the right to impose escalation costs.
11. When applicable, Eaton’s Three Phase Pre-Startup Checklist must be completed by the Purchaser at least ten (10) working days prior to desired start-up date and sent directly by Purchaser to Eaton Service Dispatch team via email:
[email protected] or by fax at: 919-654-7185. Expedited start-up scheduling may incur additional cost. A completed checklist returned to eReps does not commence the ten (10) working day lead time. 88 of 92
COMMENTS & GENERAL CONDITIONS continued
12. Standard factory start-up includes familiarization training to be performed at time of start-up. If training shall occur at a later date other time than start-up, additional costs will be incurred. Videotaping of training session is strictly prohibited. Videotaping cannot be performed by Eaton, electrical contractor, general contractor, end user, owner, and/or 3rd party.
89 of 92
Tab 12
Eaton Powerware
93PM Product
Brochure
90 of 92
The Eaton® 93PM UPS combines high efficiency and reliability with an eye-catching design. A space-saving, scalable and flexible device that’s as easy to deploy as it is to manage; it’s the perfect three-phase white or grey space solution for today’s data center.
Lowest TCO (total cost of ownership)
• Conserve valuable data center floor space with the compact footprint and optional maintenance bypass
• Grow effortlessly with vertical scalability, reducing cost and unexpected future growth risks
• Reduce power and cooling OPEX through industry-leading energy efficiency
– Up to 98.5 percent efficiency with Energy Saver System (ESS)
– Up to 95 percent efficiency in double-conversion mode Easy deployment
• Provides flexible
configurability
• Includes swappable
technology to scale in
minutes and minimize
downtime
Easy management
• Track statistics on energy savings, battery time and outages • Profile your load and much more with the friendly graphical LCD touchscreen interface
• View system status from a distance with the green/yellow/ red LED light bars
Advanced IT integration
• Supports optional communication cards that allow remote access via the HTTP(S), SNMP, MODBUS TCP/IP, Modbus
RTU and BACnet IP protcols
• Manage your power devices in your physical or virtual environment with Eaton’s Power Xpert® software and
Intelligent Power™ Software Suite
• Increase uptime through 24x7 remote monitoring and
reporting capabilities using Eaton’s PredictPulse™ service that alerts technicians during critical events and results in faster resolutions when a problem is detected; learn more at Eaton.com/PredictPulse
Eaton 93PM 60 kW UPS
Efficient. Scalable. Innovative.
Eaton 93PM
efficiency in doubleconversion and ESS
The 93PM ESS energy cost savings pay for the UPS in less than 3 years. Calculate your 93PM savings with ESS at
Eaton.com/ESS.
UPS load (%)
UPS efficiency (%)
10 20 30 40 50 60 70 80 90 100
100
90 80
70 Double-conversion mode
Legacy UPS
Typical Operating Range
ESS
Product Brochure 10–60 kW
91 of 92
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 208 Eaton
All Rights Reserved
Printed in USA
BR153076EN / GG
January 2018
Learn more at: Eaton.com/93PM
Battery
Battery voltage 480V
Charging method ABM® or float technology
Internal batteries 2, 3, or 4 strings available
B
A
D
E
G
H
A
B
C
D
E
F
G
H
Bottom cable entry
Bottom cable entry is standard
with top cable entry available
via optional sidecar
Communications and connectivity
• Built-in device and host USB
• Five alarm inputs and dedicated EPO
• Alarm relay output
• Four communication slots
Color touchscreen LCD interface
Swappable (replacement)
power modules (20 kW) with
independent control and power
Internal battery DC disconnect
Internal batteries
Static Switch assembly
Input/output connections
42"D
22"W
The functional core
of the 93PM UPS
Eaton 93PM UPS technical specifications*
Power modules for 60 kW frame
Power offering (kW) 10, 15, 20, 25, 30, 35, 40, 45, 50, 55, 60 kW with optional internal N+1 redundancy
through 40 kW
General characteristics
Efficiency in Energy Saver System (ESS) Up to 98.5%
Efficiency in double-conversion mode Up to 95%
Parallel capability Four distributed
Height x depth x width 74" x 42" x 22"
Input characteristics
Voltage 208V or 220V 3-phase 4-wire
Voltage range +15%/-15% @ 208V, +10%/-15% @ 220V
Frequency range 50/60 Hz
Power factor > .99
Input current distortion ≤ 3.5% @ 100% load capacity
*Due to continued improvements, specifications are subject to change. 74"H
• Up to 98.5%
ESS efficiency
• Up to 95%
doubleconversion
efficiency
Open front view of the unit Front view
Battery “torpedo” pack
without cover
C
Eaton, PredictPulse, ABM, Intelligent Power and
Power Xpert are registered trademarks.
All other trademarks are property of their
respective owners.
Battery “torpedo” pack
with cover
F
Output
Voltage 208V or 220V 3-phase 3-wire or 4-wire
Frequency range 50/60 Hz
Regulation ±1% steady state
Voltage THD <1.6% (100% linear load);
<5% (non-linear load)
Load power factor range Unity with the ability to support 0.8 leading to 0.8 lagging without de-rating
Certification
Safety UL 1778, cULus
EMC FCC Part 15 subpart B class A
Surge IEC 61000-4-5
Optional accessories
• Integrated slim maintenance bypass
• Integrated power distribution cabinet
• Integrated battery cabinet (small and large)
92 of 92
Date: 3/2/2026 PCO# 13.0
Project: Contractor:
Owner: Customer:
Item # Amount
$ 5,196.45
$ 779.46
$ 5,975.91
Original contract sum: $ 3,487,850.00
Allowance: $ -
Previous change order amount: $ 191,426.81
Original contract amount plus/minus previous change orders: $ 3,679,276.81 Total amount of this change order: $ 5,975.91
Adjusted contract amount including this change order will be: $ 3,685,252.72 Additional contract days: 3 working days
Accepted: Customer Approval:
By: By:
Date: Date:
TOTAL THIS CHANGE ORDER
DMR Builders City of Ukiah
Santa Rosa, Ca 95401
300 Seminary Ave.
Ukiah, Ca 95482
2725 Guerneville Rd.
PROPOSED CHANGE ORDER
DMR Builders
501 South State St. 2725 Guerneville Rd.
Santa Rosa, Ca 95401
Description
Remodel of 501 South State St.
Ukiah, Ca 95482
City of Ukiah
300 Seminary Ave.
City of Ukiah
300 Seminary Ave.
Ukiah, Ca 95482 Ukiah, Ca 95482
CORE Electrical Services, Inc.
Estimate for work to repair / re-pipe and re-wire the exterior pole lights - infrastructure was demolished with the
concrete. Includes investigatory work to assess the damage and scope (see attached tag).
P/O/B/I @ 15%
CORE Electrical Services, INC.
3250 Dutton Ave
Santa Rosa CA 95407
CA License: 1041970
DATE SPEC. NO:
2/27/2026
ORGINAL AGREEMENT DATE: PAGE S: CHANGE NO:
PCO 3
ITEM Price
Subcontrator SubTotal $0.00
15% Markup $0.00
Total Subcontractor $0.00
Hours Rate PRICE
28 $135.80 $3,802.40
$0.00
$0.00
Labor SubTotal $3,802.40
15% Markup $570.36
Labor Total $4,372.76
ITEM COST QUAN. PRICE
$0.00
$0.00
$0.00
Equipment Subtotal $0.00
10% Markup $0.00
Equipment Total $0.00
Estimate for work to repair / re-pipe and re-wire the exterior pole lights - infrastructure was demolished with the concrete. Includes investigatory work to assess the damage and scope (see attached tag).
PROJECT LOCATION
501 S State St Ukiah CA 95482
SUBCONTRACTORS:
NAME
DESCRIPTION
EQUIPMENT
3,802.40
Proposed Project Cost Change Form
This is not a new agreement. The items below enumerate changes order necessary for the completion of the subject project All Provisions of the original Contract Documents shall remain unchanged except as specifically modified by the Change Order. This document is made with the reservation of a claim for attendant field costs, general administration costs, and ripple effect costs for extension of time. Unless written objection to this change order is received within ten days, acceptance of this change order shall be effective by all parties.
Name: Proj #TT15019 501 S State St Ukiah
Date: 2/27/2026
0.00 DESCRIPTION
0.00 Journeyman Straight Time
Cost DESCRIPTION
LABOR
YOUR AGREEMENT NO: PROJECT THE CONSTRUCTION OF:
City of Ukiah BofA ADA Barrier Removal
ITEM COST QUAN. PRICE
$139.63 1 $139.63
$158.45 3 $475.35
$33.72 1 $33.72
$10.25 1 $10.25
$0.00
$0.00
Material Subtotal $658.95
Tax on Material 10% $65.90
15% Markup Material
Subtotal $98.84
Material Total $823.69
ITEM Price
Sub $0.00
Labor $4,372.76
Equip $0.00
Material $823.69
Total $5,196.45
Total PCO Amount $5,196.45
$0.00
Subcontractor Signature
Owner Signature
Project Cost Change Proposal
Date
PVC Conduit, Couplings, Hardware
#10 THHN Stranded Wire - 500 roll minimum x3
3/4" Rigid Compression Connector
3/4" Rigid Coupling
Contractor Signature
COST DESCRIPTION
$4,372.76
$0.00
$823.69
We hereby agree to make the changes specified at this price.
DESCRIPTION
Materials
Date: 4/2/2026 PCO# 14.0
Project: Contractor:
Owner: Customer:
Item # Amount
$ 7,703.12
$ 1,155.47
$ 8,858.59
Original contract sum: $ 3,487,850.00
Allowance: $ -
Previous change order amount: $ 251,067.13
Original contract amount plus/minus previous change orders: $ 3,738,917.13 Total amount of this change order: $ 8,858.59
Adjusted contract amount including this change order will be: $ 3,747,775.72 Additional contract days: 0 working days
Accepted: Customer Approval:
By: By:
Date: Date:
300 Seminary Ave.
Ukiah, Ca 95482 Ukiah, Ca 95482
RG Plumbing Group
Labor and materila to relocate exisiting 4" santitray sewer. Provide labor and materila to install seismic bracing on new santiary sewer.
Per RFI 37.1 response.
P/O/B/I @ 15%
Santa Rosa, Ca 95401
Description
Remodel of 501 South State St.
Ukiah, Ca 95482
City of Ukiah
300 Seminary Ave.
City of Ukiah
PROPOSED CHANGE ORDER
DMR Builders
501 South State St. 2725 Guerneville Rd.
TOTAL THIS CHANGE ORDER
DMR Builders City of Ukiah
Santa Rosa, Ca 95401
300 Seminary Ave.
Ukiah, Ca 95482
2725 Guerneville Rd.
1
Today’s Date:
From:
References:
RFI #:
To:
Response
Signature: Date:
:
Information Requested:
Location & Limits:
Description:
RFI
RG Plumbing (RGP RFI#4) Schedule Impact:
Project: Bank of America ADA Barrier Removal
501 S. State Street, Ukiah
JR Da Silva
37.1 Cost Impact_____ Yes No 4" SS Pipe Routing 3/30/2026 The KPA Group
& City of Ukiah 3/30/2026
P102 Plan Mark-up Attached.
The plans call to tie into existing 4" Sanitary Sewer above the first floor ceiling.
In reality, this pipe comes up in the wall of the existing dumbwaiter that is being removed. The piping runs underground through the new elevator pit & under the current stairs.
Since we will have to cut the existing 4” cast iron underground back to underneath the new stairway and then run up and around the back of the elevator shaft, this will require an extra 30 feet of piping, 8 new hangers, and an extra inspection for the tie-in underground.
Please confirm that the pipe route shown in GREEN on the following page is acceptable.
KPA Response:
Confirmed, "No Exceptions Taken".
R G Plumbing Group, Inc.
Lic. #802006
461 Todd Road
Santa Rosa, CA 95407
Tel: 707-571-1195
Request For Information
TO: DMR. Date: 3/30/2026
Re: Reroute of existing sewer through elevator pit
Job Name: City of Ukiah B of A
Page: P102
Job Number: Phone: (707) 571-1195
Requested Information: We will have to cut the existing 4” cast iron underground back to underneath the new stairway and then run up and around the back of the elevator shaft.
This will take an extra 30 feet of piping, 8 new hangers, and an extra inspection for the tie-in underground
Please Advise
Date: 4/2/2026 PCO# 15.0
Project: Contractor:
Owner: Customer:
Item # Amount
$ 3,147.49
$ 472.12
$ 3,619.61
Original contract sum: $ 3,487,850.00
Allowance: $ -
Previous change order amount: $ 251,067.13
Original contract amount plus/minus previous change orders: $ 3,738,917.13 Total amount of this change order: $ 3,619.61
Adjusted contract amount including this change order will be: $ 3,742,536.74 Additional contract days: 0 working days
Accepted: Customer Approval:
By: By:
Date: Date:
300 Seminary Ave.
Ukiah, Ca 95482 Ukiah, Ca 95482
RG Plumbing Group
Proivde carrier not included with drinking fountains
P/O/B/I @ 15%
Santa Rosa, Ca 95401
Description
Remodel of 501 South State St.
Ukiah, Ca 95482
City of Ukiah
300 Seminary Ave.
City of Ukiah
PROPOSED CHANGE ORDER
DMR Builders
501 South State St. 2725 Guerneville Rd.
TOTAL THIS CHANGE ORDER
DMR Builders City of Ukiah
Santa Rosa, Ca 95401
300 Seminary Ave.
Ukiah, Ca 95482
2725 Guerneville Rd.
1
Date: 5/8/2026 PCO# 16.0
Project: Contractor:
Owner: Customer:
Item # Amount
$ 7,473.85
$ 1,121.08
$ 8,594.93
Original contract sum: $ 3,487,850.00
Allowance: $ -
Previous change order amount: $ 251,067.13
Original contract amount plus/minus previous change orders: $ 3,738,917.13 Total amount of this change order: $ 8,594.93
Adjusted contract amount including this change order will be: $ 3,747,512.06 Additional contract days: 0 working days
Accepted: Customer Approval:
By: By:
Date: Date:
300 Seminary Ave.
Ukiah, Ca 95482 Ukiah, Ca 95482
Per the returned shop drawings, Architect deleted S-2 and changed all tops and sills to S-1.
JR Stephens
P/O/B/I @ 15%
Santa Rosa, Ca 95401
Description
Remodel of 501 South State St.
Ukiah, Ca 95482
City of Ukiah
300 Seminary Ave.
City of Ukiah
PROPOSED CHANGE ORDER
DMR Builders
501 South State St. 2725 Guerneville Rd.
TOTAL THIS CHANGE ORDER
DMR Builders City of Ukiah
Santa Rosa, Ca 95401
300 Seminary Ave.
Ukiah, Ca 95482
2725 Guerneville Rd.
1
DATE: May 7, 2026
TO: Alexis Levesque
COMPANY: DMR Builders
EMAIL: [email protected]
# OF PAGES: 1
PROJECT: 501 S, State St QUOTE #: 25-12-002
SUBJECT: S-2 color change
Below please find the quote for the above referanced change Price to change 126 Breakroom, 210 Lactation & 7 sills to S-1 $ 6,499.00 Materials/Fabrication $ 6,149.00
Added Installation $ 350.00
Subtotal $ 6,499.00
15%Markup $ 974.85
Total $ 7,473.85
Once approved please issue a change order for $ 7,473.85 If you have any questions please don't hesitate to contact me.
Thanks,
Josh Stephens
Vice President
QUOTATION
5208 Boyd Road
Arcata, Ca 95521
(P) 707-825-0100
(F) 707-825-0400
Date: 7/7/2026 PCO# 17.1
Project: Contractor:
Owner: Customer:
Item # Amount
$ 23,459.15
$ 3,518.87
$ 26,978.02
Original contract sum: $ 3,487,850.00
Allowance: $ -
Previous change order amount: $ 286,412.24
Original contract amount plus/minus previous change orders: $ 3,774,262.24 Total amount of this change order: $ 26,978.02
Adjusted contract amount including this change order will be: $ 3,801,240.26 Additional contract days: 3 working days
Accepted: Customer Approval:
300 Seminary Ave.
Ukiah, Ca 95482 Ukiah, Ca 95482
P/O/B/I @ 15%
CORE Electrical Services
Per RFI 34.1 response (E200 Note F - "Contractor shall terminate all cables each end per all related standards in coordination with owner's IT etc.." see Cable Tray Reroute attached and price clarification in attached quote and below
text. 20 hrs Core labor and material for data drops in 4" conduit. 'Original bid scope had cable tray and associated hardware built into stated price.
Additional cable tray has been removed from this change order so as not to charge twice for the same amount of material.
The only additional cable tray parts necessary to accommodate requested changes is Two (2) waterfall tray adapters to transition into the three 4” chases being installed in the IDF room, and are reflected on the attached backup sheet.' Santa Rosa, Ca 95401
Description
Remodel of 501 South State St.
Ukiah, Ca 95482
City of Ukiah
300 Seminary Ave.
City of Ukiah
PROPOSED CHANGE ORDER
DMR Builders
501 South State St. 2725 Guerneville Rd.
TOTAL THIS CHANGE ORDER
DMR Builders City of Ukiah
1
CORE Electrical Services, INC.
3250 Dutton Ave
Santa Rosa CA 95407
CA License: 1041970
DATE SPEC. NO:
6/12/2026
ORGINAL AGREEMENT DATE: PAGE S: CHANGE NO:
PCO 7.1
ITEM Price
$17,025.00
Subcontrator SubTotal $17,025.00
15% Markup $2,553.75
Total Subcontractor $19,578.75
Hours Rate PRICE
20 $140.10 $2,802.00
$0.00
$0.00
Labor SubTotal $2,802.00
15% Markup $420.30
Labor Total $3,222.30
ITEM COST QUAN. PRICE
$0.00
$0.00
$0.00
Equipment Subtotal $0.00
10% Markup $0.00
Scope Change per E-200 Note F & Cable Tray Reroute - See quote & Drawing Per RFI 34.1 response (E200 Note F - "Contractor shall terminate all cables each end per all related standards in coordination with owner's IT etc.." see Cable Tray Reroute attached and price clarification in attached quote and below text. 20 hrs Core labor and material for data drops in 4" conduit. 'Original bid scope had cable tray and associated hardware built into stated price. Additional cable tray has been removed from this change order so as not to charge twice for the same amount of material. The only additional cable tray parts necessary to accommodate requested changes is Two (2) waterfall tray adapters to transition into the three 4” chases being installed in the IDF room, and are reflected on the attached backup sheet.'
PROJECT LOCATION
501 S State St Ukiah CA 95482
SUBCONTRACTORS:
NAME
TelCon
DESCRIPTION
EQUIPMENT
2,802.00
Proposed Project Cost Change Form
This is not a new agreement. The items below enumerate changes order necessary for the completion of the subject project All Provisions of the original Contract Documents shall remain unchanged except as specifically modified by the Change Order. This document is made with the reservation of a claim for attendant field costs, general administration costs, and ripple effect costs for extension of time. Unless written objection to this change order is received within ten days, acceptance of this change order shall be effective by all parties.
Name: Proj #TT15019 501 S State St Ukiah
Date: 6/12/2026
0.00 DESCRIPTION
0.00 Journeyman Straight Time
Cost DESCRIPTION
LABOR
YOUR AGREEMENT NO: PROJECT THE CONSTRUCTION OF:
City of Ukiah BofA ADA Barrier Removal
ITEM COST QUAN. PRICE
$246.80 1 $246.80
$215.04 1 $215.04
$64.64 1 $64.64
$0.00 $0.00
$0.00 $0.00
$0.00 $0.00
Material Subtotal $526.48
Tax on Material 10% $52.65
15% Markup Material
Subtotal $78.97
Material Total $658.10
ITEM Price
Sub $19,578.75
Labor $3,222.30
Equip $0.00
Material $658.10
Total $23,459.15
Total PCO Amount $23,459.15
$19,578.75
Subcontractor Signature
Owner Signature
Project Cost Change Proposal
Date
4" PVC Conduit 20 ft
1-5/8 Strut, Allthread, 3/8" Hardware
4" Bushings x8
Contractor Signature
COST DESCRIPTION
$3,222.30
$0.00
$658.10
We hereby agree to make the changes specified at this price.
DESCRIPTION
Materials
LIC: 612917
Core Electric Inc. June 11, 2026
3250 Dutton Ave. Suite B
Santa Rosa, CA 95407
RE: E-200 Note F changes RCO: 001
Nick,
As requested, we are providing pricing for termination of 218 Category 6A cables and associated cable/ladder routing to R/A-2 per instruction of sheet E-200 note F. This change order assumes adequate wire management and termination space exists in R/A-2 rack per Joel Hughes of HWA Power. Any additional wire management needed will be billed separately.
Original bid scope had cable tray and associated hardware built into stated price. Additional cable tray has been removed from this change order so as not to charge twice for the same amount of material. The only additional cable tray parts necessary to accommodate requested changes is Two (2) waterfall tray adapters to transition into the three 4” chases being installed in the IDF room, and are reflected on the attached backup sheet.
At this time, we are requesting a change order in the amount of $17,025.00 for providing and installing material outlined above.
We trust this is acceptable to all concerned and shall look for your advice regarding same as soon as convenient. Please see attached backup sheet for your convenience.
Thank You,
Neal Jackson
Tel-Con Project Management
The prices quoted herein are subject to increase due to supply shortages, governmental tariffs, or labor escalations. Customer agrees that Tel-Con Communications reserves the right to seek additional costs incurred by such occurrences via change order submitted to contractor.
Approved by:__________________________________ Date:___________
QTY.
MATERIAL
PRICE
MATERIAL
TOTAL
LABOR LABOR
TOTAL
218 $6,740.00 0.064 14.00
4 $493.00 0.083 0.33
1 $134.00 0.083 0.08
1 $467.00 0.500 0.50
1 $228.00 0.160 0.16
1 $389.00 0.130 0.13
4 $1,328.00 0.083 0.08
1 $156.00 0.250 0.25
Lot $58.00 0.470 0.47
218 0.073 16.00
1 $127.00 0.250 0.25
2 $385.00 0.375 0.75
Non Productive Labor (A):
Hours 33.00 Subtotals: ###### 33.00
Hours Labor @ 125.00 4,125.00
Hours Labor @
Hours Labor @
Labor Cost Total: 4,125.00
Job Expense (B):
Dollars Material Cost: 10,505.00
Subtotal: 14,630.00
10% Overhead/Profit: 1,463.00
Subtotal: 16,093.00
Subtotal: 16,093.00
8.875% Sales Tax: 932.32
Subtotal: 17,025.32
Bond:
Total: 17,025.32
10' x 18" cable ladder
18" ladder mounting plate
48-port Category 6A modular frames
Cable tray splice kit
DATE
6/11/2026
JOB / RCO NUMBER
1 24-port category 6A modular frames
JOB NAME AND ADDRESS
501 S. State St. Remodel
[email protected]
501 S. State St. Ukiah, CA 95482
Category 6A terminations
Core Electric Inc.
CONTATCT'S NAME
Nick Russ
CONTRACTOR
MATERIAL
Total (B)
Handling Material
Non Productive labor
ASPHALT PATCH BACK
DRILL FOR FOUNDATIONS
PrintingInspection/Permit Fees
Storage
COMMUNICATIONS
FIRE ALARM
Total (A)
Job Expense
COMMUNICATIONS
Superintendent
Job Clerk
Traveling Time
CONTACT'S NUMBER CONTACT'S EMAIL LOCAL
707-899-8918 551
Ladder elevation kit
2U Horizontal wire managers
18" ladder wall mount bracket
Waterfall adapters
Velcro cable retainers
Cable certifications
GENERAL NOTES (ALL NOTES MAY NOT APPLY TO THIS SHEET) - POWER/SYSTEMS: KEYNOTES - POWER/SYSTEMS: (ALL NOTES MAY NOT APPLY TO THIS SHEET) THE KPA GROUP E N G I N EE R S ARCHITECTS 6700 KOLL CENTER PARKWAY SUITE 125 P L E A S A N T O N , C A L I F O R N I A 9 4 5 6 6 TEL 925.223.8217 www.thekpagroup.com C engineers surveyors planners scientists Morrison Maierle PHARIS ENGINEERING 12/15/23 -NOTE: THE COMPANY THAT PROVIDES ELECTRIC SERVICEFOR THIS PROJECT IS THE "CITY OF UKIAH ELECTRIC UTILITY". -NOTE: THE COMPANY THAT PROVIDES ELECTRIC SERVICEFOR THIS PROJECT IS THE "CITY OF UKIAH ELECTRIC UTILITY". E N G I N E E R S ARCHITECTS CTHE KPA GROUP 1 8 4 0 F o u r t h S t r e e t , 2 n d F l o o r L i v e r m o r e , C A L I F O R N I A 9 4 5 5 0 TEL 925.223.8217 www.thekpagroup.com
Today’s Date:
From:
References:
RFI #:
To:
Response
Signature: Date:
:
Information Requested:
Location & Limits:
Description:
RFI
CORE Electrical Services INC.
3250 Dutton Ave Suite B
Santa Rosa, Ca 95407
REQUEST FOR INFORMATION
DATE:
TO:
COMPANY:
FROM:
CC:
PROJECT: Job No.
LOCATION:
RFI NO.:
SUBJECT:
DRAWING REFERENCE:
SPEC REFERENCE:
PLEASE RESPOND BY:
QUESTION:
RESPONSE: By: Date:
ANSWER:
LIC: 612917
957 B Piner Place
Santa Rosa, CA 95403
Office (707) 578-3413
Fax (707) 578-8841
Request For Information
To: Nick Russ RFI No.: 002
From: Neal Jackson Job Name: 501 South State St.
Date: 4/9/26
Description:
Questions about the change of scope in regards to the request to change note F on sheet E200 of plans:
No IT room detail provided on plans on where or what rack data cable runs are to be terminated in.
No detail on how data cable runs are to be routed into aforementioned rack.
No spec on patch panels or wire management to be used for terminations.
Please advise.
CC:
GENERAL NOTES (ALL NOTES MAY NOT APPLY TO THIS SHEET) - POWER/SYSTEMS: KEYNOTES - POWER/SYSTEMS: (ALL NOTES MAY NOT APPLY TO THIS SHEET) THE KPA GROUP E N G I N E E R S ARCHITECTS 6700 KOLL CENTER PARKWAY SUITE 125 P L E A S A N T O N , C A L I F O R N I A 9 4 5 6 6 TEL 925.223.8217 www.thekpagroup.com C THE KPA GROUP 2023 engineers surveyors planners scientists Morrison Maierle 12/15/23 C:\H\OneDrive - pharisengineering.com\Engineering\2023\23580 Ukiah Phase 2\Elec\23580 Ukiah Full Reno Final.dwg, 4/9/2026 7:28:37 PM, DWG To PDF.pc3
By: By:
Date: Date:
Santa Rosa, Ca 95401
300 Seminary Ave.
Ukiah, Ca 95482
2725 Guerneville Rd.
1
Date: 5/15/2026 PCO# 18.0
Project: Contractor:
Owner: Customer:
Item # Amount
$ 11,249.25
$ 1,687.39
$ 12,936.64
Original contract sum: $ 3,487,850.00
Allowance: $ -
Previous change order amount: $ 250,230.64
Original contract amount plus/minus previous change orders: $ 3,738,080.64 Total amount of this change order: $ 12,936.64
Adjusted contract amount including this change order will be: $ 3,768,319.94 Additional contract days: 3 working days
Accepted: Customer Approval:
By: By:
Date: Date:
300 Seminary Ave.
Ukiah, Ca 95482 Ukiah, Ca 95482
Per ATS location change - rerouting of 3" UG conduits and feeder wire - additional footage. Reconfigure previously
installed gutters and wireways. See attached drawing.
CORE Electrical
P/O/B/I @ 15%
Santa Rosa, Ca 95401
Description
Remodel of 501 South State St.
Ukiah, Ca 95482
City of Ukiah
300 Seminary Ave.
City of Ukiah
PROPOSED CHANGE ORDER
DMR Builders
501 South State St. 2725 Guerneville Rd.
TOTAL THIS CHANGE ORDER
DMR Builders City of Ukiah
Santa Rosa, Ca 95401
300 Seminary Ave.
Ukiah, Ca 95482
2725 Guerneville Rd.
1
CORE Electrical Services, INC.
3250 Dutton Ave
Santa Rosa CA 95407
CA License: 1041970
DATE SPEC. NO:
4/13/2026
ORGINAL AGREEMENT DATE: PAGE S: CHANGE NO:
PCO 6
ITEM Price
Subcontrator SubTotal $0.00
15% Markup $0.00
Total Subcontractor $0.00
Hours Rate PRICE
48 $135.80 $6,518.40
$0.00
$0.00
Labor SubTotal $6,518.40
15% Markup $977.76
Labor Total $7,496.16
ITEM COST QUAN. PRICE
$0.00
$0.00
$0.00
Equipment Subtotal $0.00
10% Markup $0.00
Equipment Total $0.00
Proposed Project Cost Change Form
This is not a new agreement. The items below enumerate changes order necessary for the completion of the subject project All Provisions of the original Contract Documents shall remain unchanged except as specifically modified by the Change Order. This document is made with the reservation of a claim for attendant field costs, general administration costs, and ripple effect costs for extension of time. Unless written objection to this change order is received within ten days, acceptance of this change order shall be effective by all parties.
Name: Proj #TT15019 501 S State St Ukiah
Date: 4/13/2026
0.00 DESCRIPTION
0.00 Journeyman Straight Time
Cost DESCRIPTION
LABOR
YOUR AGREEMENT NO: PROJECT THE CONSTRUCTION OF:
City of Ukiah BofA ADA Barrier Removal
6,518.40
DESCRIPTION
EQUIPMENT
PROJECT LOCATION
501 S State St Ukiah CA 95482
SUBCONTRACTORS:
NAME
Per ATS location change - rerouting of 3" UG conduits and feeder wire - additional footage. Reconfigure previously installed gutters and wireways. See attached drawing. Floor sink will have to be moved to make space for ATS and conduits.
ITEM COST QUAN. PRICE
$461.86 1 $461.86
$2,492.62 1 $2,492.62
$47.99 1 $47.99
$0.00
$0.00
$0.00
Material Subtotal $3,002.47
Tax on Material 10% $300.25
15% Markup Material
Subtotal $450.37
Material Total $3,753.09
ITEM Price
Sub $0.00
Labor $7,496.16
Equip $0.00
Material $3,753.09
Total $11,249.25
Total PCO Amount $11,249.25
Materials
DESCRIPTION
Contractor Signature
COST DESCRIPTION
$7,496.16
$0.00
$3,753.09
We hereby agree to make the changes specified at this price. 3" PVC Conduit (60 ft), Elbows, Fittings
350 MCM, #1 THHN Wire, pull string
1" EMT Conduit (20 ft), Fittings and straps
$0.00
Subcontractor Signature
Owner Signature
Project Cost Change Proposal
Date
ELECTRICAL ROOM REVISIONS
OR MOVE ATS INTO ROOM WITH MDP AND MOVE M1 & L1 INTO ELECT MAIN ROOM, SEE NEXT PAGE
UG CONDUIT FROM ATS TO GENERATOR
UG CONDUIT FROM ATS TO MSW
UG CONDUIT FROM ATS TO PNL MDP
Date: 5/19/2026 PCO# 19.1
Project: Contractor:
Owner: Customer:
Item # Amount
$ 220.28
$ 33.04
$ 253.32
Original contract sum: $ 3,487,850.00
Allowance: $ -
Previous change order amount: $ 250,230.64
Original contract amount plus/minus previous change orders: $ 3,738,080.64 Total amount of this change order: $ 253.32
Adjusted contract amount including this change order will be: $ 3,738,333.96 Additional contract days: 0 working days
Accepted: Customer Approval:
By: By:
Date: Date:
TOTAL THIS CHANGE ORDER
DMR Builders City of Ukiah
Santa Rosa, Ca 95401
300 Seminary Ave.
Ukiah, Ca 95482
2725 Guerneville Rd.
PROPOSED CHANGE ORDER
DMR Builders
501 South State St. 2725 Guerneville Rd.
Santa Rosa, Ca 95401
Description
Remodel of 501 South State St.
Ukiah, Ca 95482
City of Ukiah
300 Seminary Ave.
City of Ukiah
300 Seminary Ave.
Ukiah, Ca 95482 Ukiah, Ca 95482
Per Submittal #43.1- Design team comments on submittal return SJP Signs, Inc.
P/O/B/I @ 15%
1
SUBMITTAL
Job:
Spec Section Title:
Submittal Title:
Spec Section No:
Submittal No:
Revision No:
Sent Date:
Contractor’s Stamp
Architect’s Stamp
Engineer’s Stamp
Contractor:
Architect:
Engineer:
Electrical: Keith Pharis Engineering
7110 Austinwood Road
Louisville, KY 40214
Mechanical/Plumbing: Morrison-Maierle
315 N. 25th Street, Suite 102
Kalispell, MT 59101
Architect/Structural/Civil: The KPA Group
6700 Koll Center Parkway, Suite 125
Pleasanton, CA 94566
City of Ukiah, 501 South State Street
Ukiah, CA 95482 Alexis Levesque 4/13/2026 43.1 Signage Revised X X
** Please confirm the material (Page 18 & 19)
Architect’s Stamp
Engineer’s Stamp
THE KPA GROUP
1840 FOURTH STREET, SUITE 200, LIVERMORE, CA 94550 11/13/2025 Jessica Tyler, AIA KPA Response:
No exceptions taken.
04/21/2026 No re-submittal required.
PAGE 1
SIGNAGE FOR REMODEL OF
501 S. STATE ST. - UKIAH
[ALL SIGNAGE]
Fabrication By SJP Signs
501 South State St. Ukiah, CA 95482
Sign Type: Interior Signage
Date: 04/13/2026
Version: v1
Design By: Pedro
Reviewed By: Christy
1752 Junction Avenue Unit C
San Jose CA 95112
(408) 971-6643
C45 License# 945852
[email protected]
PAGE 2
DESIGNER / PM:
04/13/2026
Pedro / Christy
v1
SIGNAGE FOR REMODEL OF
501 S. STATE ST. - UKIAH [ALL SIGNAGE]
501 South State St. Ukiah,
CA 95482
SALES REP:
DATE:
CLIENT NAME:
LOCATION:
REVISION:
Harry Singh
Customer Signature
Date Place
PROJECT DESCRIPTION FOR CLIENT USE ONLY
APPROVED BY CLIENT
APPROVED SUBJECT TO COMMENTS
REVISE & RESUBMIT FOR APPROVAL
GOOD FOR CONSTRUCTION/PERMITS
This document belongs to
SJP SIGNS, INC. and
becomes the property of
the customer only upon
completion of the order and
is otherwise not to be used
in whole or in part without
written permission of
SJP SIGNS, INC.
Signature indicates approval
of this design and data
as is, and Client assumes
the responsibility for any
and all incorrect information
shown in this proposal.
Please review contents
carefully.
This rendering is computer generated. Drawings are to scale using colors, but images may appear slightly different on your monitor or printer depending on the model. We have made every effort to make this to your specifications, but please take a moment and make sure we have it right. This is an art proof that is designed to meet the approval of the customer. Once approval is granted, we SJP SIGNS, INC. are no longer liable for typographical and/or design layout errors. Please do not give approval until it meets your requirements.
You will be held financially responsible for this order when we receive your approval.
PROJECT NAME
SPECIFICATION SECTION 10.14.00
RETURNED SUBMITTAL
(DATE & NUMBER)
ATTACHMENT
FILE NAME
SJP VERSION
(DATE & VERSION) RETURNED SUBMITTAL COMMENTS CLARIFICATIONS N/A N/A 3/18/2026 - v0 N/A Please confirm sign dimensions, mounting method and material (Page 5) Please confirm sign dimensions, mounting method and material (Page 16) Please confirm sign dimensions, mounting method and material (Page 18) Please confirm COLOR of all Signs (Pantone Code)
v0 clarifications addressed
3/19/2026 - v0 N/A 3/24/2026 - v1 Revised v1 design submittal based on feedback received on v0 submittal Please confirm sign dimensions, mounting method and material (Page 18 & 19) Please confirm verbiage for each room ID (Page 10 & 11) N/A 4/13/2026 - v1 RFI response received - update v1 as per feedback Please confirm the material (Page 18 & 19)
PAGE 3
DESIGNER / PM:
04/13/2026
Pedro / Christy
v1
SIGNAGE FOR REMODEL OF
501 S. STATE ST. - UKIAH [ALL SIGNAGE]
501 South State St. Ukiah,
CA 95482
SALES REP:
DATE:
CLIENT NAME:
LOCATION:
REVISION:
Harry Singh
Customer Signature
Date Place
PROJECT DESCRIPTION FOR CLIENT USE ONLY
APPROVED BY CLIENT
APPROVED SUBJECT TO COMMENTS
REVISE & RESUBMIT FOR APPROVAL
GOOD FOR CONSTRUCTION/PERMITS
This document belongs to
SJP SIGNS, INC. and
becomes the property of
the customer only upon
completion of the order and
is otherwise not to be used
in whole or in part without
written permission of
SJP SIGNS, INC.
Signature indicates approval
of this design and data
as is, and Client assumes
the responsibility for any
and all incorrect information
shown in this proposal.
Please review contents
carefully.
This rendering is computer generated. Drawings are to scale using colors, but images may appear slightly different on your monitor or printer depending on the model. We have made every effort to make this to your specifications, but please take a moment and make sure we have it right. This is an art proof that is designed to meet the approval of the customer. Once approval is granted, we SJP SIGNS, INC. are no longer liable for typographical and/or design layout errors. Please do not give approval until it meets your requirements.
You will be held financially responsible for this order when we receive your approval.
PRIMARY FONT - FUTURA CONDENSED BOLD
SYMBOLS
COLOR PALETTE
ABCDEFGHIJKLMNOPQRSTUVWXYZ
abcdefghijklmnopqrstuvwxyz
0123456789?!
PANTONE 000C
WHITE PANTONE BLACK C FS15090 BLUE
(TBD CODE)
RED
FONTS & COLOR DETAILS
PAGE 4
DESIGNER / PM:
04/13/2026
Pedro / Christy
v1
SIGNAGE FOR REMODEL OF
501 S. STATE ST. - UKIAH [ALL SIGNAGE]
501 South State St. Ukiah,
CA 95482
SALES REP:
DATE:
CLIENT NAME:
LOCATION:
REVISION:
Harry Singh
Customer Signature
Date Place
PROJECT DESCRIPTION FOR CLIENT USE ONLY
APPROVED BY CLIENT
APPROVED SUBJECT TO COMMENTS
REVISE & RESUBMIT FOR APPROVAL
GOOD FOR CONSTRUCTION/PERMITS
This document belongs to
SJP SIGNS, INC. and
becomes the property of
the customer only upon
completion of the order and
is otherwise not to be used
in whole or in part without
written permission of
SJP SIGNS, INC.
Signature indicates approval
of this design and data
as is, and Client assumes
the responsibility for any
and all incorrect information
shown in this proposal.
Please review contents
carefully.
This rendering is computer generated. Drawings are to scale using colors, but images may appear slightly different on your monitor or printer depending on the model. We have made every effort to make this to your specifications, but please take a moment and make sure we have it right. This is an art proof that is designed to meet the approval of the customer. Once approval is granted, we SJP SIGNS, INC. are no longer liable for typographical and/or design layout errors. Please do not give approval until it meets your requirements.
You will be held financially responsible for this order when we receive your approval.
SIGNAGES OVERVIEW
SIGN TYPE A
ALL GENDER & ASI RESTROOM SIGN
SIGN TYPE B1
ALL GENDER & ASI RESTROOM ROOM ID
SIGN TYPE B2
TOILET ROOM ID
SIGN TYPE C
ROOM IDENTIFICATION SIGN
SIGN TYPE D
TACTILE EXIT SIGN
SIGN TYPE E
ISA DECAL
SIGN TYPE F
FIRE EXTINGUISHER SIGN
SIGN TYPE G
EXIT SIGN
SIGN TYPE H
TACTILE EGRESS SIGN
RESTROOM RESTROOM RESTROOM ELEVATOR EQUIPMENT
EQUIPMENT
ELEVATOR
EXIT
EXIT
FIRE
EXTINGUISHER IN CASE OF FIRE
USE STAIRWAY
IN CASE OF FIRE
USE STAIRWAY THIS DOOR SHALL REMAIN UNLOCKED
WHEN THIS SPACE IS OCCUPIED
PAGE 5
DESIGNER / PM:
04/13/2026
Pedro / Christy
v1
SIGNAGE FOR REMODEL OF
501 S. STATE ST. - UKIAH [ALL SIGNAGE]
501 South State St. Ukiah,
CA 95482
SALES REP:
DATE:
CLIENT NAME:
LOCATION:
REVISION:
Harry Singh
Customer Signature
Date Place
PROJECT DESCRIPTION FOR CLIENT USE ONLY
APPROVED BY CLIENT
APPROVED SUBJECT TO COMMENTS
REVISE & RESUBMIT FOR APPROVAL
GOOD FOR CONSTRUCTION/PERMITS
This document belongs to
SJP SIGNS, INC. and
becomes the property of
the customer only upon
completion of the order and
is otherwise not to be used
in whole or in part without
written permission of
SJP SIGNS, INC.
Signature indicates approval
of this design and data
as is, and Client assumes
the responsibility for any
and all incorrect information
shown in this proposal.
Please review contents
carefully.
This rendering is computer generated. Drawings are to scale using colors, but images may appear slightly different on your monitor or printer depending on the model. We have made every effort to make this to your specifications, but please take a moment and make sure we have it right. This is an art proof that is designed to meet the approval of the customer. Once approval is granted, we SJP SIGNS, INC. are no longer liable for typographical and/or design layout errors. Please do not give approval until it meets your requirements.
You will be held financially responsible for this order when we receive your approval.
FLAG MOUNTED
84" MAX AFF
80" MIN AFF
BOTTOM LINE
OF THE SIGN
SIGN TYPE A - HANDICAP UNISEX DOOR RESTROOM ID
INSTALLATION
1:20 SCALE
SIGN TYPE A - HANDICAP UNISEX DOOR RESTROOM ID FRONT ELEVATION 1:4 SCALE
SIGN TYPE A - HANDICAP UNISEX DOOR RESTROOM ID TOP VIEW 8"
1"
1/8"
1/2" MOUNTING
ALUMINUM BRACKET w/ SATIN FINISH,
MECHANICALLY FASTENED TO WALL.
ATTACHMENT HARDWARE WILL MATCH
THE BRACKET FINISH
BACKGROUND
1/4" PANEL, WHITE FINISH,
WILL BE MOUNTED SECURELY INTO THE
BRACKET USING SILICONE ADHESIVE
LETTERS & PICTOGRAM
FIRST SURFACE IN PMS BLACK C,
w/ UV CURED GRAPHICS
(FONT: FUTURA CONDENSED BOLD)
2 1/2"
1" 1/2" 1"
1 1/8" 12"
1 5/16"
13 1/8"
3"
3"
6"
1 1/2"
12"
4"
1 1/4"
1 1/4"
16"
RESTROOM
RESTROOM
NOTE (SJP): ARCHITECT TO CONFIRM THE MOUNTING DETAILS.
SIGN TYPE A - HANDICAP UNISEX DOOR RESTROOM ID / TYPICAL QUANTITY - 03
PROVIDE BACKING IN
WALL FOR SCREW
ANCHORAGE
PAGE 6
DESIGNER / PM:
04/13/2026
Pedro / Christy
v1
SIGNAGE FOR REMODEL OF
501 S. STATE ST. - UKIAH [ALL SIGNAGE]
501 South State St. Ukiah,
CA 95482
SALES REP:
DATE:
CLIENT NAME:
LOCATION:
REVISION:
Harry Singh
Customer Signature
Date Place
PROJECT DESCRIPTION FOR CLIENT USE ONLY
APPROVED BY CLIENT
APPROVED SUBJECT TO COMMENTS
REVISE & RESUBMIT FOR APPROVAL
GOOD FOR CONSTRUCTION/PERMITS
This document belongs to
SJP SIGNS, INC. and
becomes the property of
the customer only upon
completion of the order and
is otherwise not to be used
in whole or in part without
written permission of
SJP SIGNS, INC.
Signature indicates approval
of this design and data
as is, and Client assumes
the responsibility for any
and all incorrect information
shown in this proposal.
Please review contents
carefully.
This rendering is computer generated. Drawings are to scale using colors, but images may appear slightly different on your monitor or printer depending on the model. We have made every effort to make this to your specifications, but please take a moment and make sure we have it right. This is an art proof that is designed to meet the approval of the customer. Once approval is granted, we SJP SIGNS, INC. are no longer liable for typographical and/or design layout errors. Please do not give approval until it meets your requirements.
You will be held financially responsible for this order when we receive your approval.
MARK NO.: 1.103-A
RESTROOM VESTIBULE - 103
MARK NO.: 2.200-A
UNISEX TOILET - 205/206
MARK NO.: 2.208-A
UNISEX TOILET - 208
RESTROOM RESTROOM RESTROOM
SIGN TYPE A - HANDICAP UNISEX DOOR RESTROOM ID
QUANTITY - 03