AUTOMATED GATES POLICY
SECTION 1 - PURPOSE
This policy establishes uniform rules for automated vehicular gate operations, including days open, public access hours, Daylight Saving Time adjustments, and procedures for after-hours access to protect visitors, funeral operations, and cemetery property.

SECTION 2 - SCOPE
Applies to all vehicular entrances controlled by automated gates and all persons entering cemetery grounds by vehicle.

SECTION 3 - DEFINITIONS • Automated Gate System: Motorized gate(s) that open/close on a programmed schedule and may include sensors, loops, keypads, card/fob readers, and safety devices.
• Public Access Hours: Hours when the public may drive into the cemetery grounds. • Standard Time / Daylight Saving Time (DST): The cemetery observes Pacific Time with the DST schedule used in California.

SECTION 4 - DAYS OPEN

1. Grounds access by vehicle is available 7 days per week, 365 days per year, including holidays, subject to temporary closures described in Section 8.

2. Office hours are maintained separately and are not governed by this gate policy.

SECTION 5 - PUBLIC VEHICULAR GATE HOURS
The automated gates will be programmed for the following schedule:

A. Standard Time Schedule (Pacific Standard Time)
• Gates open: 6:30 a.m.
• Gates close (no entry after): 5:30 p.m.

B. Daylight Saving Time Schedule (Pacific Daylight Time) • Gates open: 6:30 a.m.
• Gates close (no entry after): 6:30 p.m.

SECTION 6 - “NO ENTRY AFTER” AND “CLEARING THE GROUNDS.” 1. No vehicle entry is permitted after the posted closing time. The system will stop admitting vehicles at the closing time.

2. Visitors already inside should begin exiting at least 15 minutes before closing.

SECTION 7 - OPERATING RULES

1. Tailgating (following another vehicle through the gate) is prohibited.

2. Vehicles must yield to funeral processions and maintenance operations. Speed limits and safe driving rules apply.
201

WILDOMAR CEMETERY DISTRICT
21400 Palomar Street, P.O. Box 82
Wildomar, CA. 92595
(951) 678-2451

Page 2 ends

SECTION 8 - TEMPORARY CLOSURES
The cemetery may temporarily close one or more gates (or the entire grounds) due to:
• Maintenance activities (e.g., asphalt work, irrigation repairs, tree work) • Power outages or gate malfunction
• Large services or events requiring traffic control
• Damage, vandalism, or security incidents
• Severe weather, fire, police activity, or other public-safety threats When feasible, staff will post signage at entrances.

SECTION 9 - AUTHORIZED AFTER-HOURS ACCESS

1. After-hours access may be granted only to:
o On-duty cemetery staff and approved contractors
o Public safety and emergency responders

2. Unauthorized after-hours entry is trespassing and may be referred for enforcement.

3. Exceptions may be granted on a case-by-case basis at the discretion of the City Manager or the City Manager’s designee.

SECTION 10 - GATE FAILURE AND EMERGENCY EXIT PROCEDURES

1. If a visitor is unable to exit due to a malfunction, they should call the posted emergency number at the gate.

2. The cemetery will maintain an emergency release procedure and ensure designated personnel are trained.

3. If immediate risk exists, visitors should call 911.

SECTION 11 - SIGNAGE
At each vehicular entrance, post:
• “Gates Open/Close Automatically.”
• Public access hours
• “No Entry After Closing.”
• Emergency contact number
-■-
202

CITY OF WILDOMAR

CITY COUNCIL REGULAR MEETING

CONSENT CALENDAR
Agenda Staff Report # 1.12
Meeting Date: March 11, 2026
SUBJECT: Resolution Authorizing Submittal of Applications for all CalRecycle Grants for which the City of Wildomar is Eligible SUBMITTED BY: Jason Farag, Public Works Director/City Engineer PREPARED BY: Cameron Luna, Associate Engineer
ACTION:

Adopt a Resolution entitled:

RESOLUTION NO. 2026 - _______

A RESOLUTION OF THE CITY COUNCIL OF THE CITY OF WILDOMAR, CALIFORNIA,

AUTHORIZING SUBMITTAL OF APPLICATION(S) FOR ALL CALRECYCLE GRANTS FOR

WHICH THE CITY OF WILDOMAR IS ELIGIBLE
SUMMARY:

For the City to be eligible to submit various grant applications to CalRecycle, the State requires that the City periodically adopt a resolution authorizing the submittal of those grant applications.

BACKGROUND:

The California Department of Resources Recycling and Recovery (CalRecycle) offers funding opportunities to assist public and private entities in the safe and effective management of the waste stream. Public Resources Code sections 40000 et seq. authorizes CalRecycle to administer various grant programs in furtherance of the State's efforts to reduce, recycle, and reuse solid waste generated in the State, thereby preserving landfill capacity and protecting public health and safety and the environment.

Grant funding resources provided by CalRecycle include the Rubberized Pavement Grant Program which promotes the use of recycled-content surface pavement derived from waste tires generated in California, grant funding to assist with compliance with organic waste diversion requirements under SB 1383, and recycling programs for beverage containers, used oil, oil filter recycling, and other household hazardous waste products. CalRecycle grant application procedures require, among other things, an Applicant's governing body to declare by Resolution, certain authorizations related to the administration of the CalRecycle grants.

CalRecycle recommends that government bodies approve a general resolution authorizing the application of all CalRecycle grants in order to streamline and guarantee a City's ability to apply for all grants that they are eligible for in timely manner.

DISCUSSION:

CalRecycle grant funding is essential in meeting the City's goals and objectives. City staff actively seek competitive grant opportunities that the City may be eligible for, which often 203
require authorization to apply for by adopting a resolution. Obtaining this authorization would allow for applications to be submitted to CalRecycle for future grant opportunities for the next five years. Since 2023, Engineering staff have been able to implement advanced pavement repair strategies utilizing Asphalt Rubber Hot Mix (ARHM) which incorporates recycling used tires derived from California. ARHM is superior to traditional asphalt concrete (AC), adding to a longer life span and the added benefit of road noise reduction. Based on the successful application of this pavement repair strategy, the City is able to receive grant funds from CalRecycle in the amount of $15/ton of ARHM material placed in our CIP Projects. This credit greatly reduces the added cost of using AHRM for pavement repair versus traditional AC. The City has also successfully applied for and received grant funding to assit with SB 1383 compliance, including funding to procure mulch and/or compost to meet the State's procurement requirements under SB 1383. For these reasons, staff recommends renewing this authorization allowing staff to applying for all CalRecycle Grants for which the City of Wildomar is eligible.

The City previously adopted Resolution 2021-10 on April 14, 2021, providing the authorizations required by CalRecycle. The authorizations approved were effective for five (5) years from the date of adoption of the resolution (April 14, 2026). Since the term of the prior authorizations is almost complete, staff recommends that the City Council adopt the attached Resolution to re-authorize the required authorizations.

FISCAL IMPACT:

There is no fiscal impact at this time. If any grants that are applied for require a local funding match, the specific funding source will be identified at the time of application and/or at the time a contract is awarded to complete the grant funded work.

ATTACHMENTS:
1 - Resolution
204
RESOLUTION NO. 2026 - _____

RESOLUTION OF THE CITY COUNCIL OF THE CITY OF WILDOMAR,

CALIFORNIA AUTHORIZING SUBMITTAL OF APPLICATION(S) FOR

ALL CALRECYCLE GRANTS FOR WHICH THE CITY OF WILDOMAR IS

ELIGIBLE
WHEREAS, Public Resources Code sections 48000 et seq. authorize the Department of Resources Recycling and Recovery (CalRecycle) to administer various grant programs (grants) in furtherance of the State of California’s (state) efforts to reduce, recycle and reuse solid waste generated in the state thereby preserving landfill capacity and protecting public health and safety and the environment; and WHEREAS, in furtherance of this authority CalRecycle is required to establish procedures governing the application, awarding, and management of the grants; and WHEREAS, CalRecycle grant application procedures require, among other things, an applicant’s governing body to declare by resolution certain authorizations related to the administration of CalRecycle grants.

NOW, THEREFORE, BE IT RESOLVED, that the City Council of the City of Wildomar, California authorizes the submittal of application(s) to CalRecycle for all grants for which the City of Wildomar is eligible; and
BE IT FURTHER RESOLVED that the Public Works Director, or his/her designee is hereby authorized and empowered to execute in the name of the City of Wildomar all grant documents, including but not limited to, applications, agreements, amendments, and requests for payment, necessary to secure grant funds and implement the approved grant project; and
BE IT FURTHER RESOLVED that these authorizations are effective for five (5) years from the date of adoption of this resolution.

PASSED, APPROVED, AND ADOPTED this 11
th day of March, 2026.
______________________________
Carlos Marquez
Mayor
205
APPROVED AS TO FORM: ATTEST:
______________________________ ______________________________ Thomas D. Jex Janet Morales Garcia, CMC
City Attorney City Clerk
206

CITY OF WILDOMAR

CITY COUNCIL REGULAR MEETING

CONSENT CALENDAR
Agenda Staff Report # 1.13
Meeting Date: March 11, 2026
SUBJECT: Proposed 2026 Calendar for City-Sponsored Events, Partnerships, and Pop-Ups
SUBMITTED BY: Cory Gorham, Assistant to the City Manager PREPARED BY: Daniel Torres, Public Works Manager
ACTION:

The Community Engagement Committee recommends that the City Council approve the proposed list of City-Sponsored Events, Partnerships, and Pop-Ups for the 2026 Calendar Year.

SUMMARY:

The special events calendar for 2026 is presented to the City Council for approval. The events listed include those hosted by the City, events that the City partners in, and pop-up events primarily hosted in local communities governed by a homeowners' association.

BACKGROUND:

The City of Wildomar hosts and produces multiple city-led special events throughout the year to promote community engagement, strengthen neighborhood connections, and enhance the overall quality of life for residents. These events are strategically designed to encourage civic pride and create meaningful in-person interactions between residents, City Council members, and staff. Through a diverse mix of family-friendly programs, cultural celebrations, and neighborhood pop-ups, the City continues to foster social cohesion, support physical and mental well-being, and activate public spaces in a safe and welcoming manner.

Each year, the City receives requests from community groups to hold and partner in special events and activities that often require City resources. The City has an established Community Event Partnership Policy which outlines eligibility, criteria, and the process in which these requests are evaluated. Event organizers are required to complete a Temporary Event Permit (TEP) application and submit it to the City for approval. Based on TEPs that have already been submitted for this calendar year as well as expected applications for prior events that have been held annually, five partnership events are included on the Proposed 2026 Special Events Calendar. All prospective partnerships will be formalized through a Memorandum of Understanding (MOU) and will be managed within existing approved budget allocations.

In recent years, the City has proactively engaged residential HOA communities to host community events in HOA-managed parks as part of its broader effort to expand access to neighborhood-based programming. Staff has strategically focused on communities with suitable infrastructure, especially those east of I-15 and at least one mile from Marna O’Brien Park, to diversify participation and manage event capacity. Building on the success of previous 207
events—such as Movie in the Park and Popsicles in the Park—which typically attract 50–150 attendees and have proven especially effective at locations like Windsong Park, the City aims to strengthen community bonds, promote physical and mental well-being, and improve direct engagement between residents and City officials. The City and corresponding HOA will enter into a Joint Park Use License Agreement outlining terms, insurance requirements, notice provisions, and mutual indemnification, enabling the City and participating HOAs to host these neighborhood-focused events safely and collaboratively.

DISCUSSION:

On March 3, 2026 the City's Community Engagement Committee met to review the proposed list of special events for the 2026 Calendar Year. After review and discussion, the Committee is recommending the included 2026 Special Events Calendar for approval by City Council.

The City of Wildomar continues to produce a variety of special events designed to promote community engagement, strengthen neighborhood connections, and enhance overall quality of life. The calendar reflects the City’s strategy to include neighborhood-based programming, including Tier IV events in HOA-managed parks supported through Joint Park Use License Agreements. Staff will also continue implementing the Community Event Partnership Policy and case-by-case evaluation process for partnership requests, with approved efforts formalized through MOUs.

ACCOUNT CODE:
100-4610-52115
FISCAL IMPACT:

Funding for events scheduled in Fiscal Year 2025/26 is fully supported within the currently approved budget. Events projected to occur after July 1 are programmed and budgeted as part of the Fiscal Year 2026/27 Biennial Budget.

ATTACHMENTS:

Proposed 2026 Special Events Calendar.pdf
Community_Event_Partnership_Policy.pdf
208

CITY OF WILDOMAR
Proposed 2026 Special Events Calendar
Event Name Date Time Location Address Type Target Attendance Organization Eggstravaganza Saturday, March 28, 2026 9:00 am to 11:00 am Marna O'Brien Park 20505 Palomar Street City Sponsored 800 City of Wildomar Teen Egg Hunt Saturday, March 28, 2026 7:00 pm to 8:30 pm Marna O'Brien Park 20505 Palomar Street City Sponsored 300 City of Wildomar Wildomar City Birthday Saturday, July 18, 2026 7:00 pm to 10:00 pm Marna O'Brien Park 20505 Palomar Street City Sponsored 1000+ City of Wildomar Mariachi Night Saturday, September 19, 2026 7:00 pm to 10:00 pm Marna O'Brien Park 20505 Palomar Street City Sponsored 1000+ City of Wildomar Breakfast with Santa Saturday, December 05, 2026 8:00 am to 11:00 am Marna O'Brien Park 20505 Palomar Street City Sponsored 500 City of Wildomar Event Name Date Time Location Address Type Target Attendance Event Tier Organization Earth Day Saturday, April 18, 2026 8:00 am to 12:00 pm Marna O'Brien Park 20505 Palomar Street Partnership/ TEP 300-500 Tier III Wildomar Community and Parks Foundation Memorial Day Monday, May 25, 2026 10:00 AM Wildomar Cemetery 21400 Palomar Street Partnership/ TEP 300 Tier III American Legion 200 and VFW Post 1508 Kids Ride into Nature Car Show Saturday, May 30, 2026 10:00 am to 3:00 pm Marna O'Brien Park 20505 Palomar Street Partnership/ TEP 500-1000 Tier III The Nature Education Foundation National Night Out Tuesday, August 4, 2026 6:00 pm to 8:00 pm City of Lake Elsinore Partnership 1000 Tier II RSO Contract Agencies Fall Family Fun Fair Saturday. October 17, 2026 5:00 pm to 8:00 pm Marna O'Brien Park 20505 Palomar Street Partnership/TEP 3500 Tier 1 Southwest Healthcare Inland Valley Organization Target Attendance Event Tier Address
RSO 50-150 Tier IV Citywide
Briarwood 50-150 Tier IV APN 380452005
The Farm 50-150 Tier IV 33379B Mill Pond Drive
Wind Stone Ranch 50-150 Tier IV 33127 Pumice Lane

CITY SPONSORED EVENTS

PARTNERSHIP EVENTS

POP UP EVENTS
209
1 City of Wildomar
Community Event
Partnership Policy
210
2 INTRODUCTION
The City of Wildomar receives request from community groups to hold and partner in special events and activities that often require resources from the Community Services and Public Works Departments. The City Council encourages the Community Services Department to coordinate with local organizations where the efforts or activities of the organizations aligns, compliments, elevates or supports City services to the community.

Community Event Partnerships can be very lucrative for both parties creating a way to collaborate and improve the event experience by utilizing both parties’ resources. The purpose of this policy is to establish evaluation standards for requests for partnerships and assistance through in-kind services that will better serve Wildomar residents.

ELIGIBILITY
501(c)(3) Recognized– Organizations that meet the following criteria may be recognized as a Non-Profit Organization by the City.

1. Non-profit organization must provide documentation. Employer Identification Number (EIN) and Determination Letter. City will verify the status of documentation.

2. The organization must have filed for incorporation and be currently registered with the Registry of Charitable Trust. Organization must provide the Registry of Charitable Trust (RCT) Registration Number. City will verify the status of documentation.

Commercial Business- Business that meet the following criteria may be recognized by the City:

1. Registered Business with the City of Wildomar.

2. Provides services to the City of Wildomar Residents.

3. Business must not have any open cases with Code Enforcement.

CRITERIA
To consider a request an organization would be required to meet all of the following criteria:

1. Event or activity must be open to the general public.

2. Event or activity must offer a service or benefit to the community.

3. Event or activity must align, compliment, elevate or support a current city event or service.

4. Organization must not be financially dependent on receiving City of Wildomar support.

5. Organizations must obtain all appropriate permits, insurance, and agree to follow all City regulations.

6. Request must be submitted a minimum of sixty (60) days prior to the date of the event or activity to allow City Staff to determine if request can be met.

7. An individual organization may apply for a maximum of four (4) events per calendar year.

8. A Memorandum of Understating will need to be approved by City Council during a scheduled meeting.

9. Organization must submit a Post Event Report to the City within 30 days following the event.
211
3 BENEFITS OF PARTNERSHIPS

1. Priority reservation of facilities as part of the departments’ planning process.

2. Use of facilities for storage of equipment and supplies that align with approved activities.

3. Assignment of a staff liaison as a primary point of contact. Liaisons will facilitate communications between the City and Event Partner.

4. Advertisement or recognition within the city website and other city publications as may be approved by the Community Services Director.

5. Waiver of permit fees, facility use, and limited in-kind services based on qualified activities within event tier as approved by City Council.

EVENT TIERS
Tier I: Premier scale (1,500+ attendees) events that involves offsite parking, traffic control and multiple days for set up and breakdown.

Tier II: Large scale (1,000 – 1,500 attendees) events that involve traffic control and higher levels of public safety and sanitation.

Tier III: Medium scale (150 – 1,000 attendees) events that do involve public safety.

Tier IV: Small scale (50 – 150 attendees) with all activities completed within few hours.

APPLICATION
All eligible entities must complete a Temporary Event Packet. The packet provides instructions to guide and assist in the preparation and processing a Temporary Event Permit. Temporary events are permitted in accordance with the use and operational regulations outlined in Chapter 17.256 of the Wildomar Municipal Code (WMC). Other permits from other agencies such as the Riverside County Health Department, Alcohol Beverage Control, or Fire Department may be required.

APPLICATION REVIEW/APPROVAL
Partnership applications will be accepted and reviewed on an on-going basis. The City Council allocates a limited budget for special events. Approval of partnership is determined on a case-by-case basis related to the eligibility requirements, purpose and goals of each independent event. Approval for partnership in one year does not imply or guarantee approval in subsequent years for an organization or an event. Partnership applications will be reviewed by the Community Services Director and/or staff and will make a recommendation to the City Manager for City Council approval.

INDEMNIFICATION AND INSURANCE
Applicant must agree to defend, indemnify and hold harmless the City, its officials, officers, employees, and agents from any and all claims, demands, causes of action, costs, expenses, liabilities, losses, damages or injuries as it relates to applicants services provided to the City.

Applicant must provide a certificate of insurance providing evidence of general liability insurance coverage in the minimum amount of $1,000,000 combined single limit and an additional insured endorsement naming the City of Wildomar, its officers, employees, 212
4 and agents as additional insured. The insurance provided to the City of Wildomar as an additional insured must apply on a primary and non-contributory basis and include a waiver of subrogation. The certificate of insurance must be submitted no later than 10 days prior to the event. Insurance is also available for purchase through the City’s insurance provider. Submit the Coverage Request form with your application to receive a quote.

If applicable, Workers' Compensation Insurance with statutory limits as required by the State of California Labor Code. The Workers' Compensation policy shall be endorsed with a waiver of subrogation in favor of the City.

USE OF CITY NAME, IDENTITY OR LOGOS
Use of the City name, identity or logo in relation to any activity held at city facilities or supported by the City through any Community Event Partnership, must be approved by the Community Services Director. Event partners shall acknowledge the City’s support in all publicity relating to the event or activity. This includes logos and statements in all advertising and promotional material, media releases and in other promotional contexts.

Promotional opportunities should be detailed in the event application.

POLITICAL/RELIGIOUS ACTIVITIES
Political activities may not be held on park property under any type of City coordinated event. In like manner, no religious church, creed or sectarian organization to promote religious purposes will be approved under the partnership. Religious organizations are not excluded from partnerships. Organizations which participate in the program partnership may not associate political or religious activities with the programs or activities for which they have applied. Activities of a political or religious nature may be scheduled through the normal park reservation or temporary event permit process.

BANNERS
All banners must be in compliance with the City Sign Ordinance. User group must submit a Temporary Sign/Banner Application to the Community Services Department specifying the Promotional Banner requirements. All banners must be maintained in good condition and hanging properly. All banners must be of appropriate nature. The city can request banners be removed for any reason. Banners are to be provide to the Community Services Department for placement.

GENERAL REGULATIONS
The applicant is subject to all City of Wildomar Municipal Codes. 213

CITY OF WILDOMAR

CITY COUNCIL REGULAR MEETING

CONSENT CALENDAR
Agenda Staff Report # 1.14
Meeting Date: March 11, 2026
SUBJECT:

First Amendment to Professional Services Agreement for On-Call Geotechnical and Materials Testing Services with Geocon West, Inc.

SUBMITTED BY: Jason Farag, Public Works Director / City Engineer PREPARED BY: Jason Farag, Public Works Director/City Engineer ACTION:

Authorize the City Manager to execute a First Amendment to the Professional Services Agreement with Geocon West, Inc. for On-Call Geotechnical and Materials Testing Services SUMMARY:

This First Amendment includes an increase in hourly rates for various Public Works/Engineering geotechnical services provided to the City by Geocon West ("Geocon").

BACKGROUND:

The City requires geotechnical engineering services for specific projects, to provide quality assurance during construction of Capital Improvement Projects and to provide technical review services for private development projects. In 2018, the City issued an RFP for Geotechnical and Materials testing services.

Geocon West, Inc. (“Geocon”) submitted a proposal and was selected for these services. The City entered into an agreement with Geocon on July 11, 2018 for these services.

On July 13, 2022, the City Council authorized the City Manager to execute a new contract with Geocon for On-Call Geotechnical and Materials Testing (Agreement). The existing Agreement is included as Attachment B.

Hourly billing rates charged by Geocon for services provided have not been adjusted since the current Agreement was executed in 2022.

DISCUSSION:

Due to ongoing needs of the Public Works/Engineering Department for geotechnical services, the City relies on support from an on-call consultant to help provide these services. Geocon has requested a rate adjustment for their hourly billing rates for 2026. As previously noted, the rates have not been adjusted since July 13, 2022. To adjust the rates, it is necessary to amend the City's current On-Call Consultant Agreement to reflect the new hourly rates. A proposed First Amendment (Attachment A) has been prepared that includes the new proposed billing rates. Increases to Prevailing Wage Rates, insurance, legal costs, labor rates, and a desire to retain well qualified quality staff by paying them in line with industry rates were cited by Geocon as the factors for this rate adjustment to their Schedule of Fees. The adjustment to the hourly fee rate schedule is based on the cumulative Consumer Price Index (CPI) 214
percentages from July 2022 through December 2025 (9%). Inspections for projects requiring prevailing wage rates will exceed the 9% increase by adding an additional $55/hour due to prevailing wage requirements, plus Department of Industrial Relations rate increases after January 1, 2026. If approved, the changes would become effective on March 16, 2026.

FISCAL IMPACT:

The cost for On-Call/Staff Augmentation services will increase by about 9% effective March 16, 2026, as compared to the latest amended agreement. Inspections for projects requiring prevailing wage rates will exceed the 9% increase by adding an additional $55/hour due to prevailing wage requirements, plus Department of Industrial Relations rate increases after January 1, 2026. Costs associated with this amendment will be charged to the applicable fund accounts for the projects for which Geocon staff are providing services.

ATTACHMENTS:

A - First Amendment
215

FIRST AMENDMENT TO

AGREEMENT FOR SERVICES
by and between
the

CITY OF WILDOMAR
and
GEOCON WEST, INC.

Dated March 11, 2026
216

FIRST AMENDMENT TO PROFESSIONAL SERVICES AGREEMENT FOR

ON-CALL GEOTECHNICAL AND MATERIAL TESTING SERVICES
This First Amendment to Agreement for Professional Services (“First Amendment”), which is dated March 11, 2026, is hereby entered into by and between the CITY OF WILDOMAR, a California general law city (“City”), and Geocon West, Inc., a California Corporation (“Service Provider”), as follows:

RECITALS
A. City and Service Provider entered in an agreement for Professional Services on July 13, 2022 (“Agreement”). The Agreement provides that Service Provider would continue to perform On-Call Geotechnical and Material Testing services for the City as described in Exhibit A, Scope of Services of the original Agreement.

B. This First Amendment amends the hourly billing rate for services provided under the Agreement.

OPERATIVE PROVISIONS
NOW, THEREFORE, in consideration of the promises made and recited herein, the parties do hereby enter into this First Amendment which amends the Agreement as follows:

1. AMENDMENT. The Agreement is hereby modified and amended as follows:

1.1.EXHIBIT “B” COMPENSATION of the Agreement is hereby modified to the rates attached hereto effective March 16, 2026.

GENERAL PROVISIONS

1. Remainder Unchanged. Except as specifically modified and amended in this First Amendment, the Agreement remains in full force and effect and binding upon the parties.

2. Integration. This First Amendment constitutes the entire understanding and agreement of the parties and supersedes all negotiations or previous agreements between the parties with respect to all or any part of the transaction discussed in this First Amendment.

3. Effective Date. This First Amendment shall not become effective until the date it has been formally approved by the City Council and executed by the appropriate authorities of the City and Service Provider.

4. Applicable Law. The laws of the State of California shall govern the interpretation and enforcement of this First Amendment.

5. References. All references to the Agreement include all their respective 217
terms and provisions. All defined terms utilized in this First Amendment have the same meaning as provided in the Agreement, unless expressly stated to the contrary in this First Amendment.

IN WITNESS WHEREOF, the parties hereto have caused this First Amendment to the Agreement to be executed on the date and year first above written.

CITY
By:

Chris Mann, City Manager
ATTEST:

Janet Morales Garcia, CMC, City Clerk

APPROVED AS TO FORM
_____________________________________
Thomas D. Jex, City Attorney

SERVICE PROVIDER
Geocon West, Inc.

By:

Name:

Title:

By:

Name:

Title:
218

ATTACHMENT A

AMENDED HOURLY RATES
219
$ 90.47
$ 101.37
$ 81.75
$ 92.65
$ 92.65
$ 130.80
$ 130.80
$ 130.80
$ 136.25
$ 147.15
$ 158.05
$ 168.95
$ 179.85
$ 272.50
$ 381.50
$ 436.00
$ 272.50
$ 0.65
$ 10.90 Coring Machine (concrete, asphalt, masonry) (/Day) $ 310.65 $ 10.90 Generator (/Day) $ 114.45
$ 5.45 Mobile Laboratory with Lab Technician (/Day) $ 1,798.50 $ 32.70 Schmidt Hammer (/Day) $ 109.00
$ 147.15 Perforated 3" PVC Pipe (/10ft.) $ 49.05
$ 190.75 Gravel $ 32.70
$ 163.50 Sand $ 27.25
$ 81.75 Quick Set PCC Patch $ 32.70
$ 272.50 Temporary Marking Paint $ 10.90
$ 54.50 Lath $ 109.00
$ 109.00 Air Compressor (/Day) $ 109.00
$ 54.50 Soil Sample Tube $ 10.90
Percussion Hammer Drill (/Day) $ 109.00

EQUIPMENT, MATERIALS, & ANALYTICAL TESTS
TRAVEL
Subsistence (Per Diem/Day)
Vehicle Mileage (/Mile)
Personnel Regular Hourly Rate
Battery-Powered Pump (/Day)
Water Level Indicator (/Day)
Double Ring Infiltrometer Equipment (/Day)
GPS Unit (/Day)
Pick-up Truck (/Day)
Water Buffalo (/Day)
Dynamic Cone Penetrometer (/Day)
Hand-Auger (/Day)

EQUIPMENT, MATERIALS, & ANALYTICAL TESTS
Nuclear Density Gauge / Sand Cone Testing Equipment (/Hr) Vehicle (/Hr)
Special Inspection Equipment (/Hr)
Asphalt Cold Patch or Concrete, 60-lb. sack
Short-Notice Cancellation, 4 Hours (if after 4 pm the day before the scheduled inspection or upon/after arrival at the job site) *Prevailing Wage (PW) – California Labor Code §1720 et seq.: add $55/hr. + cumulative DIR rate increases after January 1, 2026 Deposition or Court Appearance (/Hr)
Overtime/Saturday Rate/Night Rate (6 pm – 6 am w/ 8-Hour minimum per call out) 1.5 X Regular Hourly Rate Sunday and Holiday Rate 2 X Regular Hourly Rate
Minimum Fee per call-out (if 4 hours or less): 4-Hour minimum, (if more than 4 hours and less than 8 Hours): 8-Hour minimum Project Engineer/Geologist (/Hr) *
Senior Project Engineer/Geologist (/Hr) *
Senior Engineer/Geologist (/Hr) *
Associate Engineer/Geologist (/Hr) *
Principal Engineer/Geologist/Litigation Support (/Hr)
Attorney Fees (General) (/Hr)
Special Inspector (Concrete/Rebar/Masonry/Welding/etc) (/Hr) * Engineering Inspector (Bottom Approval / Shoring / Foundations / Piles) (/Hr) * LA City Deputy Grading Inspector (Bottom Approval / Shoring / Foundations / Piles) (/Hr) * Field Supervisor/Public Works Inspector/Building Inspector * Staff Engineer/Geologist (/Hr) *
Senior Staff Engineer/Geologist (/Hr) *
Wildomar
2026 Schedule of Fees

PROFESSIONAL SERVICES
Word Processor / Non-Technical Assistant / Draftsman / Dispatcher (/Hr) Engineering Assistant/Lab Technician. (/Hr)
Engineering Field Technician (Earthwork/Compaction Testing/Backfill) (/Hr) * 1 of 4 WILDOMAR CPI 2026 SOF 220
(A370) Tensile – Electric Resist. Butt Splice w/ Control $ 163.50 $ 239.80 (A370) Straightening of bar (if required) $ 27.25 $ 250.70 Structural Steel Tests:
$ 250.70
$ 109.00 (A370) Tensile Strength & Elongation
$ 163.50 Up to 200,000 lbs $ 109.00
$ 54.50 200,000 – 300,000 lbs $ 136.25
$ 327.00 300,000 – 400,000 lbs $ 163.50
$ 109.00 SOIL AND AGGREGATE PROPERTIES
(D422/T88) Particle Size Analysis, Hydrometer $ 179.85
$ 316.10 (C136/D6913/T27) Sieve, Coarse to Fine w/ #200 Wash $ 163.50 $ 321.55 (C136/D6913/T27) Sieve, Coarse or Fine w/ #200 Wash $ 125.35 $ 577.70 (C136/D6913/T27) Sieve, Coarse or Fine No #200 Wash $ 109.00 $ 201.65 (C117/D1140/T11) Materials Finer than #200 $ 98.10 $ 114.45 (D2216/T265/CT226) Moisture Content $ 32.70
(D2487/D2488) Visual Soil Classification $ 32.70
$ 147.15 (D2937) Density of In-Place Soil, Drive-Cyl. Method $ 49.05 $ 32.70 (D4943) Shrinkage Factors of Soils, Wax Method $ 59.95 $ 109.00 (C131/C535/CT211) L.A. Abrasion Resistance $ 218.00 $ 59.95 (C142/T112) Clay Lumps and Friable Particles $ 185.30 $ 54.50 (C123/T113) Light Weight Particles $ 267.05
(D3744/CT229/T210) Durability Index Fine $ 207.10
$ 294.30 (D3744/CT229/T210) Durability Index Coarse $ 245.25 $ 283.40 (CT227) Cleanness Value $ 185.30
$ 305.20 (D4791) Flat & Elongated Particles $ 179.85
$ 119.90 (D693/CT205) Percent Crushed Particles $ 158.05 $ 54.50 (D5821) Percent. of Fractured Particles, Coarse Aggregate $ 152.60 $ 381.50 (C40/CT213/T21) Organic Impurities $ 76.30
$ 70.85 (C235) Soft Hardness (Scratch Hardness) $ 109.00 $ 1,090.00 (C88/CT214/T104) Sulfate Soundness $ 446.90
$ 218.00 (C1252/T304) Uncompact. Void Content, Fine Aggregate $ 163.50 $ 130.80 (C127/CT206/T85) Coarse Specific Gravity $ 136.25 $ 87.20 (C128/CT207/T84) Fine Specific Gravity $ 163.50 $ 109.00 (D854/CT209/T100) Specific Gravity of Soil $ 163.50 $ 98.10 (C29/CT212/T19) Unit Weight & Percent Voids $ 98.10 $ 174.40 (D2419/CT217/T176) Sand Equivalent $ 119.90
(D4318/CT204/T89/T90) Plastic Index (Plastic/Liq. Limit) $ 179.85 (D4318/CT204/T89) Liquid Limit $ 103.55
(D4318/CT204/T90) Plastic Limit $ 103.55
$ 109.00 (C330) Spec. for Lightweight Aggregates, Struc. Concrete Quote $ 136.25 SHEAR STRENGTH
$ 136.25 (D2166) Unconfined Compression $ 109.00
(D3080/T236) Direct Shear (3 Points) $ 321.55
(D3080/T236) Remolded Direct Shear (3 points) $ 327.00
#11 Bar & Smaller $ 163.50
#14 Bar & Larger $ 207.10
(A370/A1034) Tensile - Mechanically Spliced Bar
Reinforcing Steel Tests:
(A370/A615/A706) Tensile Strength & Elongation
#11 Bar & Smaller
#14 Bar
#18 Bar (Proof Test)
(A370/A615/A706) Bend Test
(D4546) Swell/Compression Testing & Density
(D4546) Swell/Settlement Testing & Density (ea. addtl. pt.) (D4546) Swell/Settlement Testing & Density (County)
(D4546) Swell/Settlement Testing & Density (FHA)
(D4829) Expansion Index of Soils

STEEL TESTING
(D2434) Permeability, FHA Slab-on-Grade
(D2434) Permeability, Hourly
(D2435/T216) Consolidation (6 pts. w/ Unload)
(D2435/T216) Consolidation Additional Point w/ Unload
(D2435/T216) Time Rate Consol. (6 pts. w/Unload)
(D2435/T216) Time Rate Consol. Add’l. Point w/Unload
(CT422/T291) Chloride Content
(D2974) Organic Content

PERMEABILITY, CONSOLIDATION, AND EXPANSION
(D5084) Permeability, Flexible Wall
(D5856) Permeability, Rigid Wall
(D2434) Permeability, Constant Head
(C977) Stabilization Ability of Lime
(D1883) Calif. Bearing Ratio (Army Corps of Engineers)

CHEMICAL ANALYSIS
(G187/CT643/T288) pH and Resistivity
(D4972/T289) pH Only
(CT417/T290) Sulfate Content
(D1633/CT312) Soil Cement Comp. Strength (Set of 3)
(D1633/CT312) Soil Cement Comp. Strength (Addtl. Spec.)

SOIL AND AGGREGATE STABILITY
(D2844/CT301) Resistance Value
(D2844/CT301) Resistance Value, Treated
(D1883) California Bearing Ratio
(D698/D1557/T99/T180) 6-inch mold
(CT 216) California Impact
Check Point
(D1632/CT312) Soil Cement Cyl. Fabrication (Set of 3)
(D1632/CT312) Soil Cement Cyl. Fabrication (Addtl. Spec.) (A370) Machining & Prep of Test Specimen Cost + 20%

LABORATORY TESTS LABORATORY TESTS

COMPACTION CURVES
(D698/D1557/T99/T180) 4-inch mold
2 of 4 WILDOMAR CPI 2026 SOF 221
$ 125.35
$ 174.40 UTM with One Operator $ 348.80
$ 174.40
$ 288.85 Spray Applied Fireproofing:
$ 370.60 (E605/E736) Fireproofing Oven Dry Density/Thickness $ 98.10 $ 408.75 Brick Test (Set of 5 Specimens):
$ 523.20 (C67) 24-Hour Absorption, Cold Water (/set) $ 245.25 (C67) 5-Hour Absorption, Boiling Water (/set) $ 245.25
(C67) Compression Test or Modulus of Rupture (/set) $ 277.95 $ 212.55 (C67) Each Additional Specimen $ 49.05
$ 70.85 CONCRETE**
$ 212.55 Mix Designs:
$ 70.85 (ACI211/ACI214) Concrete Mix Design $ 381.50
$ 310.65 (ACI211/ACI214) Review of Concrete Mix Design $ 381.50 $ 32.70 (C192) Concrete Trial Mix (includes equipment & labor) $ 539.55 $ 38.15 Concrete Properties:
(C39/CT521/T22) Comp. Strength, Concrete Cyl. $ 32.70
$ 218.00 (C42/CT521/T22) Comp. Strength, Concrete/Gunite Core $ 65.40 $ 245.25 (C78/CT523) Flex. Strength of 6”x6”x21” Concrete Beam $ 179.85 $ 272.50 (C174) Length Measuring of Drilled Cores $ 81.75 Quote (C1140) Shotcrete Panel-Coring & Testing (Set of 3) $ 316.10 (C1140) Shotcrete Panel (each addtl. specimen) $ 98.10
$ 163.50 (C469) Static Modulus of Elasticity $ 218.00
$ 190.75 (C426) Drying Shrinkage (Set of 3, up to 28 days) $ 430.55 (C642) Spec. Gravity, Absorp., Voids in Hardened Concrete $ 103.55 $ 109.00 (F1869) Vapor Emission Rate, Concrete Subfloor $ 54.50 $ 109.00
$ 54.50 *2X Surcharge on rush turnaround for laboratory testing. $ 54.50 **Fee applies for sample storage, testing, or disposal. $ 54.50 VIBRATION MONITORING SERVICES
Initial Set-Up & Baseline Readings (Each) $ 3,000.00
Quote Installation (Two Stations) $ 3,500.00
Installation (Each Additional Station) $ 2,000.00
$ 386.95 Meetings, Additional Reporting (Hourly) $ 160.00 ASPHALT TESTING Monitoring (Monthly) $ 6,000.00
Monitoring (Weekly) $ 2,000.00
$ 109.00 Monitoring (Daily) $ 500.00
$ 158.05 Emergency Site Visit $ 640.00
$ 163.50
$ 163.50
$ 163.50
$ 70.85 · Utility Locating
MISCELLANEOUS TESTING SERVICES · Seismic Remi Study
· Multichannel Analysis of Surface Waves
$ 218.00 · Electrical Resistivity Tomography
$ 327.00 · Refraction Study
· Underground Storage Tank Evaluation
Calibration of Hydraulic Ram:
100 Ton & Under
101 Tons – 200 Tons
(D1560/CT366) Stabilometer Value (HVEEM)
(D6307) Asphalt Ignition
(D5444) Sieve Analysis of Extracted Asphalt UTILITY LOCATION/GEOPHYSICAL SERVICES (D6307/CT382) Percent Asphalt, Ignition Method (REQUEST QUOTATION) (D1188) Unit Weight of Asphalt Core
Weld Specimen Tests:
(E164) Ultrasonic Examination
Machining & Prep of Test Specimen Cost + 20%
(E381) Macrotech Test (3 Faces)
Asphalt Properties:
(D2726/CT308/T166) Bulk Spec. Grav. Compacted HMA
High Strength Bolt, Nut, & Washer Tests:
(F3125/A325/A490) Tensile Test on Bolts
(F3125/A563) Proof Load Test on Nuts
(F3125/A325/A490) Hardness Test on Bolts
(F3125/A536) Hardness Test on Nuts
(F3125/F436) Hardness Test on Washers
(C1314) 8”x16”x16” – 10”x12”x16”
(C1314) 12”x12”x16” – 12”x16”x16”
(C1314) Larger than 12”x16”x16”
Pre-stressing Wire & Tendon Tests:
(A421) Tensile Strength, Single Wire
(A416) Tensile Strength, 7-Wire Strand
(C140) Compression Test (ea. addtl. specimen)
(C426) Linear Drying Shrinkage
(C109/UBC 21-16) Mortar Cylinder (2”x4”)
(C1019/UBC 21-19) Grout Prism (3”x3”x6”), trim included Masonry Prism (Assemblage):
(C1314) 8”x8”x16” – 8”x12”x16”
(EM1110) Consolidated-Drained Triaxial Staged
MASONRY**
Concrete Block Test (Sets of 3 Required):
(C140) Unit Weight Moisture Content & Absorption $350/ea (C140) Moisture Content/Absorption (ea. addtl. specimen) (C140) Compression Test
(D2850) Unconsolidated-Undrained Triaxial Shear
(D2850) Unconsolidated-Undrained Triaxial Staged Additional Technician Regular Tech Rate (D4767) Consolidated-Undrained Triaxial Shear
(D4767) Consolidated-Undrained Triaxial Staged
(EM1110) Consolidated-Drained Triaxial Shear

LABORATORY TESTS LABORATORY TESTS
(D3080/T236) Direct Shear Addtl.Points/ea. residual pass Use of Universal Testing Machine:
3 of 4 WILDOMAR CPI 2026 SOF 222

1. 2.

3. 4.

5. 6.

7. Sampling and testing are conducted in substantial conformance with the latest applicable or designated specifications of the American Society for Testing and Materials, Caltrans, American Association of State Highway and Transportation Officials, or other pertinent agencies.

Saturday, night work, and overtime hours are charged at time and one-half; Sundays and holidays at double time. Per diem is $305.00 per day when the location of work dictates.

Equipment and materials will be billed at cost plus 15%. Outside services, including subcontractors and rental of special equipment, are billed at cost plus 15%.

Hourly services are billed portal to portal from the closest office in accordance with the stated hourly rates herein, with a minimum two-hour charge.

Invoices will be submitted at four-week intervals. Terms of payment are met upon presentation of the invoice. Invoices become delinquent thirty (30) days from invoice date and subject to one and one-half percent (1-1/2%) service charge per month, or the maximum rate allowed by law, whichever is lower. If Client objects to all or any portion of any invoice, Client will so notify Geocon in writing within fourteen (14) calendar days of the invoice date, identify the cause of disagreement, and pay that portion of the invoice not in dispute. The parties will immediately make every effort to settle the disputed portion of the invoice. Payment on delinquent invoices will first be applied to accrued interest and then to the principal amount. All time spent and expenses incurred (including any attorney's fees and costs) in connection with the collection of any delinquent amount will be paid by Client to Geocon per Geocon's current fee schedule.

Client and Geocon shall allocate certain of the risks so that, to the fullest extent permitted by law, Geocon’s (the term “Geocon” includes Geocon’s partners, officers, directors, employees, agents, affiliates, subcontractors and subconsultants) total aggregate liability to Client is limited to the greater of $10,000 or the total compensation received from Client by Geocon for services rendered on this project, for any and all of Client’s injuries, damages, claims, losses, expenses, or claim expenses arising out of this Agreement from any cause or causes, including attorneys’ fees and costs which may be awarded to the prevailing party, and Client agrees to indemnify and hold harmless Geocon from and against all liabilities in excess of the monetary limit established above.

Client and Geocon shall allocate certain of the other risks so that, to the fullest extent permitted by law, Client shall limit Geocon’s total aggregate liability to all third parties, including contractors, subcontractors of all tiers, materialmen, and others involved in Client’s project, as well as persons and other entities not involved in the project, to the greater of $20,000 or the total compensation received from Client by Geocon for services rendered on this project, for any and all injuries, damages, cause or causes, including attorneys’ fees and costs which may be awarded to the prevailing party, and Client agrees to indemnify and hold harmless Geocon from and against all liabilities in excess of the monetary limit established above, including all liability incurred by Geocon for acts, errors, or omissions, pursuant to entering into agreements with third parties on behalf of Client in order to obtain access or entry onto property not owned by Client. Client agrees to notify all contractors and subcontractors of any limitation of Geocon’s liability to them, and require them to abide by such limitation for damages suffered by any contractor or subcontractor arising from Geocon’s actions or inactions. Neither the contractor nor any subcontractor assumes any liability for damages to others that may arise on account of Geocon’s actions or inactions.

TERMS AND CONDITIONS
Listed are typical charges for the services most frequently performed by Geocon. Prices for unlisted services, as well as special quotations for programs involving volume work, will be provided upon request. Laboratory test prices shown are for laboratory work only, and include reporting of routine results not calling for comments, recommendations, or conclusions.
4 of 4 WILDOMAR CPI 2026 SOF 223

CITY OF WILDOMAR

CITY COUNCIL REGULAR MEETING

CONSENT CALENDAR
Agenda Staff Report # 1.15
Meeting Date: March 11, 2026
SUBJECT: Second Amendment to Agreement for Services with CivicPlus, LLC, to add API for Integration between SeeClickFix and Comcate
SUBMITTED BY: Jason Farag, Public Works Director
PREPARED BY: Terri Abercrombie, Senior Management Analyst ACTION:

Authorize the City Manager to execute the Second Amendment to Agreement for Services with CivicPlus, LLC
SUMMARY:

Under an existing agreement with the City, CivicPlus, LLC, provides the City with municipal website services. A First Amendment to the Agreement added separate municipal software applications for Community Services (CivicRec) and for Public Works Service Requests (SeeClickFix). This Second Amendment will add an Application Programming Interface ( API) necessary for the SeeClickFix software to integrate with Code Enforcement's case management software, Comcate.

BACKGROUND:

On November 9, 2022, the City of Wildomar entered into an Agreement with CivicPlus, LLC, (CivicPlus) for municipal website services (Agreement). On October 13, 2025, the City of Wildomar and CivicPlus, LLC entered into the First Amendment to the Agreement (First Amendment) adding municipal software applications for Community Services (CivicRec) and for Public Works Service Requests (SeeClickFix).

DISCUSSION:

The City’s Code Enforcement Division uses an application known as Comcate for case management of Code Enforcement cases. Code Enforcement complaints are submitted by the public to the Code Enforcement Division directly using the Comcate application. Currently, Public Works Service Requests are separately submitted to the Public Works Department via a form on the City’s website. Once SeeClickFix is in operation, Public Works Service Requests will be submitted through the SeeClickFix application, either on the City’s website or through a mobile application. Since approval of the First Amendment, the City has been working with CivicPlus to set-up and implement SeeClickFix.

To allow the public to report Public Works Service Requests and Code Enforcement complaints through a single platform instead of two separate platforms, an Application Programming Interface (API) is necessary to integrate the two applications. With this API, Code Enforcement matters can be reported through the SeeClickFix application and will integrate directly with Code Enforcement's case management software, Comcate. This 224
feature will significantly reduce the amount of staff time spent manually re-entering Code Enforcement complaint information into the Comcate database. This will also allow for simpler and more efficient reporting and processing of public service requests and code complaints, providing residents with a unified process to submit concerns regarding items observed in the field.

Included in Attachment A is a proposed Second Amendment with CivicPlus to add the necessary API to allow the SeeClickFix application to integrate with the Comcate application.

Staff recommends that the City Council authorize the City Manager to execute the Second Amendment.

ACCOUNT CODE:
100-4350-58110
FISCAL IMPACT:

Adequate funds for this API are available in the adopted FY 25/26 budget. The total annual cost for the API is $1,500. The Prorated Cost for the initial term will be due upon signing the Second Amendment. The Annually Recurring cost will be due with future annual costs and will be subject to the same escalation rate in the Agreement.

ATTACHMENTS:

A - Second Amendment
225
Second Amendment to Agreement for
Services
This Second Amendment to Agreement for Services (“Second Amendment”), which is dated as of March 11, 2026, is hereby entered into by and between the CITY OF WILDOMAR, a California municipal corporation (“City”), and CIVICPLUS, LLC, a Kansas limited liability company (“Service Provider” or “CivicPlus”), as follows:

RECITALS
A. City and Service Provider entered into an agreement for Services dated November 9, 2022 (“Agreement”) for the provision of CivicEngage Services.

B. City and Service Provider entered into a First Amendment to the Agreement dated October 13, 2025, to obtain additional products and services.

C. City desires to obtain, and Service Provider desires to provide, additional products and services described in the Statement of Work dated January 14, 2026 (the “SOW”), attached hereto as Exhibit A and incorporated by reference, on the terms and conditions set forth in the Agreement and as amended by the First Amendment.

D. The Parties wish to amend the Agreement to update the scope of services, compensation, and related provisions to incorporate the additional product and services, and to co-term such products with the Agreement’s existing term.

OPERATIVE PROVSIONS
NOW, THEREFORE, in consideration of the promises made and recited herein, the parties do hereby enter into this Second Amendment which modifies and amends the Agreement as follows:

1. AMENDMENT. The Agreement is hereby modified and amended as follows:

SECTION 2. SCOPE OF SERVICES
The Scope of Services in the Agreement is hereby amended to include the SeeClickFix 311 CRM Organization API product services as described in Exhibit A. These products and services shall be provided in accordance with the terms of the Agreement. The Statement of Work (SOW) attached hereto as Exhibit A shall be deemed an additional exhibit to the Agreement.

SECTION 4. COMPENSATION AND METHOD OF PAYMENT
The Compensation provisions of the Agreement are hereby amended to include the pricing and payment terms for the additional products and services described in Exhibit A to this Amendment, as set forth in the Statement of Work (SOW) dated January 14, 226
2026. Such pricing includes all applicable annual recurring fees for the SeeClickFix 311 CRM Organization API product services.

GENERAL PROVISIONS

1. REMAINDER UNCHANGED. Except as specifically modified and amended in this Second Amendment, the Agreement remains in full force and effect and binding upon the parties.

2. INTEGRATION. This Second Amendment consists of five pages and constitutes the entire understanding of the parties and supersedes all negotiations or previous agreements between the parties with respect to all or any part of the transaction discussed in this Second Amendment.

3. EFFECTIVE DATE. This Second Amendment shall not become effective until the date it has been formally approved by the City Council and executed by the appropriate authorities of the City and Service Provider.

4. REFERENCES. All references to the Agreement include all its respective terms and provisions. All defined terms utilized in this Second Amendment have the same meaning as assigned to such terms in the Agreement.

IN WITNESS WHEREOF, the parties hereto have caused this Second Amendment to be executed the day and year first above written.

CITY OF WILDOMAR CIVICPLUS, LLC
__________________________ __________________________
Chris Mann Name:

City Manager Title:
227

EXHIBIT A

STATEMENT OF WORK
228
CivicPlus
302 South 4th St. Suite 500
Manhattan, KS 66502
US
Statement of Work
Quote #: Q-115158-1
Date: 1/14/2026 3:20 PM
Expires On: 3/15/2026
Client:

City of Wildomar, CA
Bill To:

WILDOMAR CITY, CALIFORNIA
SALESPERSON Phone EMAIL DELIVERY METHOD PAYMENT METHOD
Ryan Cole 203-349-6678 [email protected] Net 30
Recurring Service(s)
QTY PRODUCT NAME DESCRIPTION 12 Month
Value

1.00 SeeClickFix 311 CRM
Organization API
License for access to the private SeeClickFix 311 CRM
Organizational API. This does not include custom
development or consultation services.

USD 1,500.00
Total Investment - Prorated Year 1 USD 1,340.41
Annual Recurring Services (Subject to Uplift) USD 1,500.00 Total Days of Quote:326
Initial Term Beginning at signing and ending 12/5/2026, Renewal Term 12/6 each calendar year
Initial Term Invoice Schedule 100% invoiced at signing, to be prorated based on signature date.

The Annual Recurring Services subscription fee for the Products (as described above) included in this SOW are prorated and co-termed to align with the Client’s current billing schedule and the Annual Recurring Services amount will subsequently be added to Client's Term and regularly scheduled annual invoices under the terms of the Agreement.

This Statement of Work ("SOW") shall be subject to the terms and conditions of the Agreement signed by and between the Parties on November 9, 2022 and the First Amendment to Agreement for Services dated October 13, 2025 (collectively, the "Agreement"). By signing this SOW, Client expressly agrees to the terms and conditions of the Agreement, as though set forth herein.

Please note that this document is a SOW and not an invoice. Upon signing and submitting this SOW, Client will receive the applicable invoice according to the terms of the invoicing schedule outlined herein.

Page 1 of 2 ends

229
Client may issue purchase orders for its internal, administrative use only, and not to impose any contractual terms. Any terms contained in any such purchase orders issued by the Client are considered null and will not alter the Binding Terms, the Agreement or this SOW.

Page 2 of 2 ends

230

CITY OF WILDOMAR

CITY COUNCIL REGULAR MEETING

GENERAL BUSINESS
Agenda Staff Report # 3.1
Meeting Date: March 11, 2026
SUBJECT: Resolution Approving the Establishment of a Public Agency Post-Employment Benefits Trust
SUBMITTED BY: Adam Jantz, Finance Manager
PREPARED BY: Adam Jantz, Finance Manager
ACTION:

1. Adopt a resolution entitled:

RESOLUTION NO. 2026 - ______

RESOLUTION OF THE CITY COUNCIL OF THE CITY OF WILDOMAR APPROVING THE

ADOPTION OF THE PUBLIC AGENCIES POST-EMPLOYMENT BENEFITS TRUST

ADMINISTERED BY PUBLIC AGENCY RETIREMENT SERVICES (PARS)

2. Authorize the City to enter into an administrative services agreement with Public Agency Retirement Services.

SUMMARY:

Resolution Approving the Establishment of a PARS 115 Trust BACKGROUND:

In 2012, the Government Accounting Standards Board (GASB) issued Statement No. 68, Accounting and Financial Reporting for Pensions. GASB 68 requires that governmental employers that sponsor Defined Benefit plans (i.e., CalPERS) must recognize a net pension liability (unfunded accrued liability) on their balance sheet. This is the difference between the City’s total pension liability (actuarial accrued liability) and actual plan assets. GASB 68 became effective for fiscal years starting after June 15, 2014.

To reduce the GASB 68 net pension liability figure, the City’s only prior option was to commit additional funds to CalPERS (in excess of its annual required contributions) to reduce its unfunded liability. However, a private letter ruling received by PARS from the IRS established that the City could create a separate trust to "pre-fund" its CalPERS unfunded liability. This would provide the City with an alternative to sending funds to CalPERS that will allow for greater local control over assets, and investment by a professional fund management team selected and monitored by the City, with future excess contributions transferred to CalPERS at the City's discretion.

To date, over 320 agencies have adopted the Pension Rate Stabilization Program (PRSP) through PARS including nearby agencies such as cities of Temecula, Murrieta, San Jacinto, Moreno, Beaumont, WRCOG and County of Riverside.
231
Expected benefits offered by the PARS PRSP include:
• Contributions placed in an exclusive benefit trust could address the City’s Net Pension Liability
• Investment flexibility with Section 115 Trust compared to restrictions on general fund investments (Govt. Code 53216)
• Increased risk diversification of plan assets through different asset management • Investments can be tailored to the City’s unique demographics • Oversight and control of fund management selection, monitoring of performance and ability to replace fund management based on
performance criteria
• Increased flexibility on use of trust assets (i.e., trust assets can be accessed at anytime as long as the assets are used to fund the City’s
pension obligations and defray reasonable expenses associated therewith) • Lower investment management and administrative expenses compared to CalPERS • Potential for positive rating agency and investor consideration.

In an effort to help public agencies address and manage their GASB 68 liability, PARS has developed the PARS Post-Employment Benefits Trust Program. PARS has assembled leading professionals to provide the City with the necessary services required under one program to pre-fund pension and retiree health care liabilities through an IRS reviewed program. The program has been established as a multiple employer trust so that public agencies regardless of size can join the program to receive the necessary economies of scale to keep administrative fees low and avoid any setup costs. To properly offset liabilities, funds must be set aside in an exclusive benefit, irrevocable trust that cannot be accessed by creditors in order to be accounted for as assets to fund the liability on the City’s financial statements. The trust permits the City, under federal and state law, to invest in a more diversified array of investments to maximize investment returns long term and reduce the City’s liability.

PARS has partnered with US Bank to serve as trustee and its sub-adviser PFM Asset Management, LLC, to provide investment management services for the program.

DISCUSSION:

The completion of the FY2023-24 Annual Comprehensive Financial Report recognized a substantial surplus in the General Fund. In the interest of financial prudence, the Council authorized the City to set aside $900,000 of the surplus to be deposited into a postemployment benefits trust at the FY2024-25 mid-year budget report. The City established a new fund, 103 Pension Liability Fund, and transferred the funds into it. The City is now moving forward with the establishment of the trust.

The City plans to use the trust for the City’s Unfunded Accrued Liability (UAL) payments. The City is not planning on establishing an Other Post-Employment Benefits (OPEB) trust at this time. The Cemetery is considered a separated entity and will continue to fund its own UAL payments.

The City’s Unfunded Accrued Liability is $813,800 with annual payments projected until 2043 averaging approximately $76,000 per year. By achieving returns in the 8-10% range, the trust can fund the City’s UAL payments in perpetuity.

ACCOUNT CODE:
232
Fund 103
FISCAL IMPACT:

The City plans on depositing $900,000 into the trust. The administrative fees and trustee fees for this amount of assets under management are 0.06% annually. This equates to approximately $5,400 per year for plan management fees.

ATTACHMENTS:

City of Wildomar - PARS Presentation.pdf
Resolution- PARS 115 trust
Agreement for Administrative Services.pdf
233
City of wildomar 0
City of wildomar
PARS 115 Trust – Pension Rate Stabilization Program (PRSP) & OPEB Prefunding Program March 11, 2026
234
City of wildomar 1
Pars 115 Trust Team
Trust Administrator & Consultant*
40+
Years of Experience
(1984-2026)
2,300+
Plans under
Administration
1,100+
Public Agency
Clients
$10.8 B+
Assets under
Administration
Investment Manager
• A division of U.S. Bancorp Asset Management, Inc.
• Fixed income and multi asset portfolios
• Strategic Blend and Index platform options
• Customized portfolios (with minimum asset level)
41 Years of Investment
Experience
(As of 12/31/2025)
$254.9B *
Assets under Management
& Advisement
Trustee
• 5th largest commercial bank and one of the
nation’s largest trustees for Section 115 trusts
• Safeguard plan assets
• Oversight protection as plan fiduciary
• Custodian of assets
163
Years of Experience
(1863-2026)
$11.0T
Assets under
Administration
550+
115 Trust Clients
• Serves as record-keeper, consultant,
and central point of contact
• Sub-trust accounting
• Coordinates all agency services
• Monitors plan compliance
(IRS/GASB/State Government Code)
• Processes contributions/disbursements
• Hands-on, dedicated support teams
750 K+
Plan Participants
*Please see disclosures at the end of this presentation * See important information regarding PARS in the Disclaimer page at the end of the presentation. 235
City of wildomar 2
Sampling of pars 115 Trust clients

CITIES & COUNTIES
Alhambra
Anaheim
Calabasas
Canyon Lake
Chino Hills
Commerce
Costa Mesa
Cudahy
Cypress
Dana Point
Duarte
Fountain Valley
Fullerton
Garden Grove
Glendale
Glendora
Grand Terrace
Hawthorne
Hemet
Huntington Beach
La Habra
Laguna Niguel
Lake Forest
Lakewood
Los Alamitos
Manhattan Beach
Monrovia
Murrieta
Newport Beach
Ontario
Palmdale
Pasadena
Perris
Pico Rivera
Pomona
Rancho Cucamonga
Rialto
Riverside County
Rolling Hills
Rosemead
San Clemente
San Jacinto
Santa Ana
Santa Clarita
South El Monte
Temecula
Temple City
Tustin
Twentynine Palms
Villa Park
West Covina
Westminster
Yucca Valley

SPECIAL DISTRICTS
Agoura Hills/Calabasas Community Center
Authority
Bighorn-Desert View Water Agency
California Joint Powers Insurance Authority
Coastline Regional Occupational Program
County Sanitation District No. 2 of Los Angeles
County
Crestline Village Water District
East Orange County Water District
Fallbrook Public Utility District
Housing Authority of the County of San Bernardino
Mesa Water District
Mojave Desert Air Quality Management District
Municipal Water District of Orange County
Orange County Fire Authority
Orange County LAFCO
Orange County Mosquito and Vector Control District
Orange County Sanitation District
Orange County Water District
Orchard Dale Water District
Placentia Library District
Rancho Cucamonga Fire Protection District
Rowland Water District
South Coast Water District
South Orange County Wastewater Authority
Superior Court of CA, County of Orange
Twentynine Palms Water District
Walnut Valley Water District
Western Riverside Council of Governments
Yorba Linda Water District

EDUCATION
Alta Loma School District
Bellflower Unified School District
Beverly Hills Unified School District
Brea Olinda Unified School District
Citrus CCD
Coast CCD
Compton Unified School District
Copper Mountain CCD
El Monte Union High School District
Fontana Unified School District
Hermosa Beach City School District
Hesperia Unified School District
Hughes-Elizabeth Lakes Union ESD
Moreno Valley Unified School District
Newport-Mesa Unified School District
Ontario-Montclair School District
Palmdale School District
Palos Verdes Peninsula USD
Paramount Unified School District
Pasadena Area CCD
Rancho Santiago CCD
Rio Hondo CCD
San Bernardino CCD
San Marino Unified School District
Savanna School District
South Pasadena USD
Trona Joint Unified School District
Upland Unified School District
Victor Valley CCD
Westminster School District
Westside Union School District
Whittier City School District
Wilsona School District
236
City of wildomar 3
Subaccounts
OPEB and Pension assets are
individually sub-accounted,
and can be divided by dept.,
bargaining group, or cost center
Assets in the PARS Section 115
Combination Trust can be used
to address unfunded liabilities.

Financial Stability
Allows separate investment
strategies for OPEB and
Pension subaccounts.

Flexible Investing
OPEB and Pension assets
aggregate and reach lower fees
on tiered schedule sooner –
saving money!
Anytime Access Economies-of-Scale
Trust funds are available
anytime; OPEB for OPEB
and Pension for Pension.

No set-up costs, no minimum
annual contribution amounts,
and no fees until assets are added.

No Set Up Cost or Minimums
Retiree Medical Benefits
Prefund OPEB GASB 75
OPEB
Reimburse agency; or
Pay benefits provider
Pension Rate Stabilization Program
Prefund Pension (PRSP) GASB 68
Pension
Reimburse agency; or
Pay retirement system
Assets can be used to: Assets can be used to:
prefund
either or both
General Fund
PARS IRS-Approved Section 115 Trust
237
City of wildomar 4
OPEB Actuarial Results
Data from 2024 ACFR
Measurement Date:

June 30, 2024
Pay-as-you-Go
Discount Rate: 4.21% Percent Change Prefunding Discount Rate: 7.21% Total OPEB Liability (TOL) $902,495 30-36%▼ ?
Fiduciary Net Position $0 -- ?
Net OPEB Liability (NOL) $902,495 30-36%▼ ?
Service Cost
for FY 2023-24 $84,642 30-36%▼ ?
Annual Benefit Payments
(Pay-as-you-Go)
for FY 2023-24
$46,618 -- $46,618
Rule of thumb: For every one percent increase in the discount rate, the unfunded liability is lowered by 10-12%. 238
City of wildomar 5
Why Prefund OPEB?
Potential Greater Return
Diversification of trust assets can result in a greater rate of return, which can be helpful in addressing your Agency’s liability
1 Rule of Thumb
For every 1% increase in return, your Agency’s liability will be lowered about 10-12%.

A typical unfunded Agency has a ~4% discount rate and OPEB prefunding could lower liabilities by 20-30%.
2 GASB 75
GASB 75 requires OPEB liabilities to be placed directly on your balance sheet, like pension liabilities under GASB 68
3 Assets which Reduce Liabilities
Contributions into the trust are considered “assets” which reduce liabilities on your Agency’s financial statements
4 239
City of wildomar 6
PARS Pension Rate
Stabilization Program
for prefunding pension obligations
The
240
City of wildomar 7
Combined
Miscellaneous Groups *
Valuation as of
June 30, 2023
Valuation as of
June 30, 2024
Change
Actuarial Liability $5.3 M $6.2 M 16.8% ↑
Assets $4.5 M $5.4 M 20.4% ↑
Unfunded Liability $835.8 K $813.8 K 2.6% ↓
Funded Ratio 84.3% 86.9% 3.1% ↑
Employer Contribution Amount
$346.7 K $388.7 K 12.1% ↑
(FY 24-25) (FY 25-26)
Employer Contribution Amount – Projected *
---
$479.3 K 23.3% ↑
(FY 31-32)
Pension Funding Status
As of June 30, 2024, the City of Wildomar’s CalPERS pension plan is funded as follows:
* Data through 2031-32 from City’s latest CalPERS actuarial valuation. 241
City of wildomar 8
Why Prefund Pension Obligations?
Complete Local Control over Assets
City has complete control over assets, including contributions, disbursements and the timing, amount, and risk tolerance level of investments

1. Pension Rate Stabilization
Assets can be transferred to the retirement system at the City’s direction, potentially reducing/eliminating large fluctuations in employer contribution amounts

2. Rainy Day Fund
Emergency source of funds when employer revenues are strained in difficult budgetary or economic times

3. Diversification
Allows for investment flexibility and offers the potential for assets to earn greater returns than the general fund; spread the risk vs. sending additional money to CalPERS

4. 242
City of wildomar 9
Investment OPTIONS
243
City of wildomar 10
• Agency maintains oversight of the investment
manager and the portfolio’s risk tolerance level
• Investment restrictions that apply to the
general fund (CA Government Code 53601)
are not applicable to assets held in the
PARS Section 115 Irrevocable Trust
• Assets held in the PARS Section 115
Irrevocable Trust can be invested per
Government Code Sections 53216 (Pension)
and 53620 (OPEB)
• Investments can be diversified and invested
in a prudent fashion
• Investments can be tailored to the Agency’s unique demographics and needs • Increased risk diversification
Investment Flexibility
Diversified Investing
Assets held in The PARS Section
115 Irrevocable Trust can be
diversely invested in a prudent
fashion per Government Code
Sections 53216 (Pension)
and 53620 (OPEB).

GOV § 53216 (Pension)
GOV § 53620 (OPEB)
244
City of wildomar 11
PFMAM Managed Strategies
Moderate
Balanced Capital Appreciation
Domestic
Equity

36.0%
Int'l Equity

18.0%
Listed Real
Assets

6.0%
Cash

2.0%
Fixed
Income

38.0%
Domestic
Equity

30.0%
Int'l Equity

15.0%
Listed
Real
Assets

5.0%
Cash

2.0%
Fixed
Income

48.0%
Domestic
Equity

45.0%
Int'l Equity

22.5%
Listed
Real
Assets

7.5%
Cash

2.0%
Fixed
Income

23.0%
Expected
Returns *
5-Year, 6.1%
30-Year, 6.3%
Expected
Returns *
5-Year, 6.5%
30-Year, 6.6%
Expected
Returns *
5-Year, 6.9%
30-Year, 7.0%
* Data from PFMAM Managed Strategies: Asset Allocation Summary. Representative as of 2026. Asset allocations and assumptions are subject to change. Please see important disclosures at the end of this presentation for additional information.

Moderately Conservative
Domestic
Equity

18.0%
Int'l Equity

9.0%
Listed Real Assets

3.0%
Cash

2.0%
Fixed
Income

68.0%
Expected
Returns *
5-Year, 5.4%
30-Year, 5.6%
Conservative
Domestic
Equity

9.0%
Int'l Equity

4.5%
Listed Real
Assets

1.5%
Cash

2.0%
Fixed
Income

83.0% Expected
Returns *
5-Year, 4.8%
30-Year, 5.1%
The following strategies, actively managed by PFM Asset Management (PFMAM), may be structured with blend of active and passive funds (strategic blend) or passive funds only (index):
245
City of wildomar 12

1. Input Phase
– Target discount rate
– Risk tolerance
– Investment philosophy
– Asset allocation
– Timing on use of funds

2. Model Portfolios 3. Dedicated Portfolio Manager/
Investment Specialist
– Makes recommendation
– Fiduciary responsibility
– Investment policy statement
– Periodic reviews
– Cell phone access
Strategy Equity 10-YR Returns*
Capital Appreciation 65-85% 9.43%
Balanced 50-70% 8.06%
Moderate 40-60% 7.17%
Moderately Conservative 20-40% 5.07%
Conservative 5-20% 3.86%
vs. LAIF 0% 2.10%**
Simple Investment Approach
*10-Year Index Portfolio annualized returns as of December 31, 2025 (Gross of Investment Management Fees, but Net of Embedded Fund Fees). Conservative Index does not yet have 10-year history ; for illustrative purposes Conservative Strategic Blend 10-year return is used. Please see complete Investment Strategy Sheets for more information.
**Avg. LAIF apportionment rate (released quarterly) over the 10-Year period ending December 31, 2025 Please see important additional disclosures to the PARS portfolios included in the individual strategy fact sheets. 246
City of wildomar 13
Strategy Equity (%) 1 Year 3 Years 5 Years 10 Years
Capital
Appreciation 65-85% 16.15% 15.49% 8.80% 9.43%
Balanced 50-70% 14.10% 13.49% 6.95% 8.06%
Moderate 40-60% 12.92% 11.87% 5.81% 7.17%
Moderately
Conservative 20-40% 10.76% 9.08% 3.52% 5.07%
Conservative 5-20% 9.00% 6.99% 1.89% 3.86%
Managed Strategies Investment Returns As of December 31, 2025 INDEX PORTFOLIO ANNUALIZED RETURNS* (Gross of Investment Management Fees, but Net of Embedded Fund Fees) Please see complete Investment Strategy Sheets for more information. *The1, 3, and 5 year returns reflect the actual returns of the respective PARS/115P Strategic Blend portfolios, which have not reached 10 years since inception. The 10-year returns reflect the actual returns of the respective PARS/PRHCP Strategic Blend portfolios, except for the 10-year return for the Capital Appreciation portfolio, which reflects the actual return of the PARS/PRHCP Capital Appreciation Index portfolio. The returns provided are gross of investment advisory fees and net of mutual fund fees.

Subject to change due to rebalancing; Past performance does not guarantee future results.

Please see important additional disclosures to the PARS portfolios included in the individual strategy fact sheets. 247
City of wildomar 14
Plan Set-Up Fee: Ongoing Fees Paid to U.S. Bank:

None 0.35% for assets under $5 million

0.25% for assets $5-10 million

0.20% for assets $10-15 million

0.15% for assets $15-50 million

0.10% for assets over $50 million
Managed tactical strategies -Program Fees
Plan Set-Up Fee: Ongoing Fees:

None 0.25% for assets $0-10 million

0.20% for assets $10-15 million

0.15% for assets $15-50 million

0.10% for assets over $50 million
Trust Administration/Consulting Fees *
Discretionary Trustee/Investment Management Fees **
Please note that OPEB and pension assets will be combined for fee calculation purposes. * PARS does not receive any compensation from the investments or any commissions, back-end loads, or any other forms of compensation. ** Subject to change due to rebalancing. Additional information on U.S. Bancorp Asset Management, Inc. and a description of its fees are described in its ADV which is available on the SEC’s website at www.adviserinfo.sec.gov. Fees charged by U.S. Bank N.A. for Discretionary Trustee/Investment Management services are based on individual agency assets. U.S. Bank N.A. compensates the sub-adviser for these services from its own fees, as detailed above. See disclosures at the end of this presentation for more information. 248
City of wildomar 15
Steps to Implementation
1 City authorizes establishment of the PARS Trust through Council Resolution and appoints a Plan Administrator*
2 PARS provides legal documents for signature by Plan Administrator to set up the Trust
3 City works with Portfolio Manager to select investment strategy 4 After receipt of signed documents, City’s account is set up and available for receipt of contributions
5 City makes initial deposit to the PARS Trust (no minimum contribution nor timeframe requirement for the first contribution)
6 PARS and Portfolio Manager conducts an annual review of investment performance with City and discuss future contribution and disbursement requirements
*The Council resolution must adopt the PARS Trust by name, "Public Agencies Post-Employment Benefits Trust" and appoint a position of employment as Plan Administrator. 249
City of wildomar 16
questions
Rachael Sanders, CEBS
Vice President, Consulting
(800) 540-6369 x121
[email protected]
250
City of wildomar 17

APPENDIX
251
The information provided reflects standard risk and return metrics for the portfolio depicted and are derived by running Monte Carlo simulations using PFMAM’s Capital Market Assumptions and target asset class allocations based on the specific scenario within this presentation. Please refer to PFMAM’s Capital Market Assumptions for key assumptions and the methodology utilized. PFMAM’s Capital Market Assumptions are available upon request.

The return data is representative in nature and should not be relied upon as independently verifiable information. There is no guarantee that the projected returns can or will be achieved. Results may vary with each use and over time. This material does not purport to contain all of the information that a prospective investor may wish to consider and is not to be relied upon or used in substitution for the exercise of independent judgement.

Past performance is not a guarantee of future results. Prior to investing, you should consult your accounting, tax, and legal advisors to understand the implications of such an investment. Asset class and risk return analytics are run through FactSet.

The returns presented in this simulation are not actual returns experienced by a real investor, but rather simulated returns that we believe could have been achieved under controlled circumstances using a number of assumptions. No representation or warranty is made to the reasonableness of the assumptions made or that all assumptions used in achieving the returns have been stated or fully considered.

No assurance can be given as to whether the information and/or assumptions upon which this hypothetical performance is based reflect present market conditions or future market performance. Actual performance results may differ from this hypothetical performance presented. Changes in the assumptions may have a material impact on the hypothetical performance presented. Past performance is not a guarantee of future results.

The material is provided to you on the understanding that, as a sophisticated investor, you will understand and accept its inherent limitations.
19 Important Disclaimers for Return Projections
(Intermediate and Long-Term)
252
Disclosures Disclaimer
Public Agency Retirement Services (“PARS”) is a third-party and not affiliated with PFMAM, USBAM or U.S. Bank. PARS serves as the trust administrator to the Public Agencies Post-Employment Benefits Trust, Public Agencies Post-Retirement Health Care Plan Trust, and the Public Agency Retirement System Trust (the “Trusts”). U.S. Bank N.A. serves as the discretionary trustee to the Trusts. In its capacity as discretionary trustee, U.S. Bank N.A. delegates the investment management of the Trusts to its affiliate USBAM through a sub-advisory agreement. PARS is serviced by PFMAM, a division of USBAM.

U.S. Bank N.A. pays the sub-adviser up to 67% of the annual management fee for assets sub-advised under its sub-advisory agreement with U.S. Bank N.A. Refer to your U.S. Bank N.A. fee schedule for investment management fees applied to your specific portfolio. U.S. Bank N.A. compensates the sub-adviser for these services from its own fees.

The views expressed within this material constitute the perspective and judgment of U.S. Bancorp Asset Management, Inc. (USBAM) at the time of distribution and are subject to change. Any forecast, projection, or prediction of the market, the economy, economic trends, and equity or fixed-income markets are based upon current opinion as of the date of issue and are also subject to change.

Opinions and data presented are not necessarily indicative of future events or expected performance. Information contained herein is based on data obtained from recognized statistical services, issuer reports or communications, or other sources, believed to be reliable. No representation is made as to its accuracy or completeness.

Additional information on U.S. Bancorp Asset Management, Inc. and a description of its fees are described in its ADV which is available at www.adviserinfo.sec.gov.

PFM Asset Management (PFMAM) serves clients in the public sector and is a division of U.S. Bancorp Asset Management, Inc. which is the legal entity providing investment advisory services. U.S. Bancorp Asset Management, Inc. is a registered investment adviser, a direct subsidiary of U.S. Bank N.A. and an indirect subsidiary of U.S. Bancorp. U.S. Bank N.A. is not responsible for and does not guarantee the products, services, or performance of U.S. Bancorp Asset Management, Inc.

NOT FDIC INSURED : NO BANK GUARANTEE : MAY LOSE VALUE
20 253
RESOLUTION NO. 2026 - ______

RESOLUTION OF THE CITY COUNCIL OF THE CITY OF WILDOMAR
APPROVING THE ADOPTION OF THE PUBLIC AGENCIES POSTEMPLOYMENT BENEFITS TRUST ADMINISTERED BY PUBLIC

AGENCY RETIREMENT SERVICES (PARS)
WHEREAS, PARS has made available the PARS Public Agencies PostEmployment Benefits Trust (the “Program”) for the purpose of prefunding pension obligations and/or OPEB obligations; and
WHEREAS, the City of Wildomar (“City”) is eligible to participate in the Program, a tax-exempt trust performing an essential governmental function within the meaning of Section 115 of the Internal Revenue Code, as amended, and the Regulations issued there under, and is a tax-exempt trust under the relevant statutory provisions of the State of California; and
WHEREAS, the City’s adoption and operation of the Program has no effect on any current or former employee’s entitlement to post-employment benefits; and WHEREAS, the City reserves the right to make contributions, if any, to the Program.

NOW, THEREFORE, BE IT RESOLVED, that:

1. The City Council hereby adopts the PARS Public Agencies Post-Employment Benefits Trust; and

2. The City Council hereby appoints the Finance Manager or his/her successor or his/her designee as the City’s Plan Administrator for the Program; and

3. The City’s Plan Administrator is hereby authorized to execute the PARS legal and administrative documents on behalf of the City and to take whatever additional actions are necessary to maintain the City’s participation in the Program and to maintain compliance of any relevant regulation issued or as may be issued; therefore, authorizing him/her to take whatever additional actions are required to administer the City’s Program.

PASSED, APPROVED, AND ADOPTED this 11
th day of March 2026.
______________________________
Carlos Marquez
Mayor
254
APPROVED AS TO FORM: ATTEST:
______________________________ ______________________________ Thomas D. Jex Janet Morales Garcia, CMC
City Attorney City Clerk
255

Page 1 ends

AGREEMENT FOR ADMINISTRATIVE SERVICES
This agreement (“Agreement”) is made this _____ day of _____________, 2026, between Phase II Systems, a corporation organized and existing under the laws of the State of California, doing business as Public Agency Retirement Services and PARS (hereinafter “PARS”) and the City of Wildomar (“Agency”).

WHEREAS, the Agency has adopted the PARS Public Agencies Post-Employment Benefits Trust for the purpose of prefunding pension obligations and/or Other Post-Employment Benefits (“OPEB”) obligations (“Plan”) and is desirous of retaining PARS as Trust Administrator to the Trust, to provide administrative services.

NOW THEREFORE, the parties agree:

1. Services. PARS will provide the services pertaining to the Plan as described in the exhibit attached hereto as “Exhibit 1A” (“Services”) in a timely manner, subject to the further provisions of this Agreement.

2. Fees for Services. PARS will be compensated for performance of the Services as described in the exhibit attached hereto as “Exhibit 1B”.

3. Payment Terms. Payment for the Services will be remitted directly from Plan assets unless the Agency chooses to make payment directly to PARS. In the event that the Agency chooses to make payment directly to PARS, it shall be the responsibility of the Agency to remit payment directly to PARS based upon an invoice prepared by PARS and delivered to the Agency. If payment is not received by PARS within thirty (30) days of the invoice delivery date, the balance due shall bear interest at the rate of 1.5% per month. If payment is not received from the Agency within sixty (60) days of the invoice delivery date, payment plus accrued interest will be remitted directly from Plan assets, unless PARS has previously received written communication disputing the subject invoice that is signed by a duly authorized representative of the Agency.

4. Fees for Services Beyond Scope. Fees for services beyond those specified in this Agreement will be billed to the Agency at the rates indicated in the PARS’ standard fee schedule in effect at the time the services are provided and shall be payable as described in Section 3 of this Agreement. Before any such services are performed, PARS will provide the Agency with a detailed description of the services, terms, and applicable rates for such services. Such services, terms, and applicable rates shall be agreed upon in writing and executed by both parties.

5. Information Furnished to PARS. PARS will provide the Services contingent upon the Agency providing PARS the information specified in the exhibit attached hereto as “Exhibit 1C” (“Data”). It shall be the responsibility of the Agency to certify the accuracy, content, and completeness of the Data so that PARS may rely on such information without further audit. It shall further be the responsibility of the Agency to deliver the Data to PARS in such a manner that allows for a reasonable amount of time for the Services to be performed. Unless specified in Exhibit 1A, PARS shall be under no duty to question Data received from the Agency, to compute contributions made to the 256

Page 2 ends

Plan, to determine or inquire whether contributions are adequate to meet and discharge liabilities under the Plan, or to determine or inquire whether contributions made to the Plan are in compliance with the Plan or applicable law. In addition, PARS shall not be liable for nonperformance of Services to the extent such nonperformance is caused by or results from erroneous and/or late delivery of Data from the Agency. In the event that the Agency fails to provide Data in a complete, accurate and timely manner and pursuant to the specifications in Exhibit 1C, PARS reserves the right, notwithstanding the further provisions of this Agreement, to terminate this Agreement upon no less than ninety (90) days’ written notice to the Agency.

6. Records. Throughout the duration of this Agreement, and for a period of five (5) years after termination of this Agreement, PARS shall provide duly authorized representatives of Agency access to all records and material relating to calculation of PARS’ fees under this Agreement. Such access shall include the right to inspect, audit and reproduce such records and material and to verify reports furnished in compliance with the provisions of this Agreement. All information so obtained shall be accorded confidential treatment as provided under applicable law.

7. Confidentiality. Without the Agency’s consent, PARS shall not disclose any information relating to the Plan except to duly authorized officials of the Agency, subject to applicable law, and to parties retained by PARS to perform specific services within this Agreement. The Agency shall not disclose any information relating to the Plan to individuals not employed by the Agency without the prior written consent of PARS, except as such disclosures may be required by applicable law.

8. Independent Contractor. PARS is and at all times hereunder shall be an independent contractor. As such, neither the Agency nor any of its officers, employees or agents shall have the power to control the conduct of PARS, its officers, employees, or agents, except as specifically set forth and provided for herein. PARS shall pay all wages, salaries, and other amounts due its employees in connection with this Agreement and shall be responsible for all reports and obligations respecting them, such as social security, income tax withholding, unemployment compensation, workers’ compensation, and similar matters.

9. Indemnification. PARS and Agency hereby indemnify each other and hold the other harmless, including their respective officers, directors, and employees, from any claim, loss, demand, liability, or expense, including reasonable attorneys’ fees and costs, incurred by the other as a consequence of, to the extent, PARS’ or Agency’s, as the case may be, negligent acts, errors or omissions with respect to the performance of their respective duties hereunder.

10. Compliance with Applicable Law. The Agency shall observe and comply with federal, state, and local laws in effect when this Agreement is executed, or which may come into effect during the term of this Agreement, regarding the administration of the Plan.

PARS shall observe and comply with federal, state, and local laws in effect when this Agreement is executed, or which may come into effect during the term of this Agreement, regarding Plan administrative services provided under this Agreement. 257

Page 3 ends

11. Applicable Law. This Agreement shall be governed by and construed in accordance with the laws of the State of California. In the event any party institutes legal proceedings to enforce or interpret this Agreement, venue and jurisdiction shall be in any state court of competent jurisdiction.

12. Force Majeure. When a party’s nonperformance hereunder was beyond the control and not due to the fault of the party not performing, a party shall be excused from performing its obligations under this Agreement during the time and to the extent that its performance is prevented by such cause. Such cause shall include, but not be limited to:
any incidence of fire, flood, acts of God or unanticipated communicable disease, acts of terrorism or war commandeering of material, products, plants or facilities by the federal, state or local government, a material act or omission by the other party or any law, ordinance, rule, guidance or recommendation by the federal, state or local government, or any agency thereof, which becomes effective after the date of this Agreement that delays or renders impractical either party’s performance under the Agreement.

13. Ownership of Reports and Documents. The originals of all letters, documents, reports, and data produced for the purposes of this Agreement shall be delivered to and become the property of the Agency. Copies may be made for PARS but shall not be furnished to others without written authorization from Agency.

14. Designees. The Plan Administrator of the Agency, or their designee, shall have the authority to act for and exercise any of the rights of the Agency as set forth in this Agreement, subsequent to and in accordance with the written authority granted by the Governing Body of the Agency, a copy of which writing shall be delivered to PARS.

Any officer of PARS, or his or her designees, shall have the authority to act for and exercise any of the rights of PARS as set forth in this Agreement.

15. Notices. All notices hereunder and communications regarding the interpretation of the terms of this Agreement, or changes thereto, shall be effected by delivery of the notices in person or by depositing the notices in the U.S. mail, registered or certified mail, return receipt requested, postage prepaid and addressed as follows:
(A) To PARS: PARS; 4350 Von Karman Avenue, Suite 100, Newport Beach, CA 92660; Attention: President
(B) To Agency: [Agency]; [Agency Address]; Attention: [Plan Administrator Title] Notices shall be deemed given on the date received by the addressee.

16. Term of Agreement. This Agreement shall remain in effect for the period beginning _______________, 2026 and ending _____________, 2029 (“Term”). This Agreement may be terminated at any time by giving thirty (30) days written notice to the other party of the intent to terminate. Absent a thirty (30) day written notice to the other party of the intent to terminate, this Agreement will continue unchanged for successive twelve-month periods following the Term.

17. Amendment. This Agreement may not be amended orally, but only by a written instrument executed by the parties hereto.
258

Page 4 ends

18. Entire Agreement. This Agreement, including exhibits, contains the entire understanding of the parties with respect to the subject matter set forth in this Agreement.

In the event a conflict arises between the parties with respect to any term, condition or provision of this Agreement, the remaining terms, conditions, and provisions shall remain in full force and legal effect. No waiver of any term or condition of this Agreement by any party shall be construed by the other as a continuing waiver of such term or condition.

19. Attorneys’ Fees. In the event any action is taken by a party hereto to enforce the terms of this Agreement the prevailing party herein shall be entitled to receive its reasonable attorneys’ fees.

20. Counterparts. Electronic Signatures. This Agreement may be executed in any number of counterparts, and in that event, each counterpart shall be deemed a complete original and be enforceable without reference to any other counterpart. The words “execution,” “signed,” “signature,” and words of like import in this Agreement or in any other certificate, agreement or document related to this Agreement, shall include digital electronic signatures (e.g., DocuSign). The use of digital electronic signatures and electronic records (including, without limitation, any contract or other record created, generated, sent, communicated, received, or stored by electronic means) shall be of the same legal effect, validity and enforceability as a manually executed signature or use of a paper-based record-keeping system to the fullest extent permitted by applicable law.

21. Headings. Headings in this Agreement are for convenience only and shall not be used to interpret or construe its provisions.

22. Effective Date. This Agreement shall be effective on the date first above written and also shall be the date the Agreement is executed.

AGENCY:

BY:

Plan Administrator Name
TITLE:

DATE:

PARS:

BY:

Tod Hammeras
TITLE: Chief Financial Officer
DATE:
259

Page 5 ends

EXHIBIT 1A

SERVICES
PARS will provide the following services for the City of Wildomar Public Agencies Post-Employment Benefits Trust:

1. Plan Installation Services:
(A) Meeting with appropriate Agency personnel to discuss plan provisions, implementation timelines, actuarial valuation process, funding strategies, benefit communication strategies, data reporting, and submission requirements for contributions/reimbursements/distributions;
(B) Providing the necessary analysis and advisory services to finalize these elements of the Plan;
(C) Providing the documentation needed to establish the Plan to be reviewed and approved by Agency legal counsel. Resulting final Plan documentation must be approved by the Agency prior to the commencement of PARS Plan Administration Services outlined in Exhibit 1A, paragraph 2 below.

2. Plan Administration Services:
(A) Monitoring the receipt of Plan contributions made by the Agency to the trustee of the PARS Public Agencies Post-Employment Benefits Trust (“Trustee”), based upon information received from the Agency and the Trustee;
(B) Performing periodic accounting of Plan assets, reimbursements/distributions, and investment activity, based upon information received from the Agency and/or Trustee;
(C) Coordinating the processing of distribution payments pursuant to authorized direction by the Agency, and the provisions of the Plan, and, to the extent possible, based upon Agency-provided Data;
(D) Coordinating actions with the Trustee as directed by the Plan Administrator within the scope of this Agreement;
(E) Preparing and submitting a monthly report of Plan activity to the Agency, unless directed by the Agency otherwise;
(F) Preparing and submitting an annual report of Plan activity to the Agency; (G) Facilitating actuarial valuation updates and funding modifications for compliance with the applicable GASB pronouncements and/or statements, if prefunding OPEB obligations;
(H) Coordinating periodic audits of the Trust;
(I) Monitoring Plan and Trust compliance with federal and state laws.

3. PARS is not licensed to provide and does not offer tax, accounting, legal, investment or actuarial advice.
260

Page 6 ends

EXHIBIT 1B

FEES FOR SERVICES
PARS will be compensated for performance of Services, as described in Exhibit 1A based upon the following schedule:

An annual asset fee shall be paid from Plan assets based on the following schedule:

For Plan Assets from: Annual Rate:
$1 to $10,000,000 0.25%
$10,000,001 to $15,000,000 0.20%
$15,000,001 to $50,000,000 0.15%
$50,000,001 and above 0.10%
Annual rates are prorated and paid monthly. The annual asset fee shall be calculated by the following formula [Annual rate divided by 12 (months of the year) multiplied by the Plan asset balance at the end of the month]. Trustee and Investment Management Fees are not included.
261

Page 7 ends

EXHIBIT 1C

DATA REQUIREMENTS
PARS will provide the Services under this Agreement contingent upon receiving the following information. Agency is solely responsible for ensuring that all information and documentation provided to PARS is true, correct, and authorized:

1. Executed Legal Documents:
(A) Certified Resolution
(B) Adoption Agreement to the Public Agencies Post-Employment Benefits Trust (C) Trustee Investment Forms

2. Contribution – completed Contribution Transmittal Form signed by the Plan Administrator (or authorized Designee) which contains the following information:
(A) Agency name
(B) Contribution amount
(C) Contribution date
(D) Contribution method (Check, ACH, Wire)

3. Distribution – completed Payment Reimbursement/Distribution Form signed by the Plan Administrator (or authorized Designee) which contains the following information:
(A) Agency name
(B) Payment reimbursement/distribution amount
(C) Applicable statement date
(D) Copy of applicable premium, claim, statement, warrant, and/or administrative expense evidencing payment
(E) Signed certification of reimbursement/distribution from the Plan Administrator (or authorized Designee)

4. Other information pertinent to the Services as reasonably requested by PARS and Actuarial Provider.
262

CITY OF WILDOMAR

CITY COUNCIL REGULAR MEETING

GENERAL BUSINESS
Agenda Staff Report # 3.2
Meeting Date: March 11, 2026
SUBJECT: Pre-Approved ADU Architectural Plans (PRADU) and ADU Guidebook Approval
SUBMITTED BY: Abdu Lachgar, Principal Planner
PREPARED BY: Abdu Lachgar, Principal Planner
ACTION:

Adopt a Resolution entitled:

RESOLUTION NO. 2026-_____

A RESOLUTION OF THE CITY COUNCIL OF THE CITY OF WILDOMAR, CALIFORNIA,

ACCEPTING THE PRE-APPROVED ACCESSORY DWELLING UNIT ARCHITECTURAL

PLANS AND APPROVING AN ASSOCIATED ADU GUIDEBOOK THAT MAY BE

ADMINISTRATIVELY AMENDED AS REASONABLY NEEDED
SUMMARY:

Over the past year, the City has received assistance from The Southern California Association of Governments (SCAG), in collaboration with the Western Riverside Council of Governments (WRCOG) through the Regional Early Action Planning (REAP) Local Staff Assistance Program to develop a full range of pre-approved ADU architectural plans and associated guidebook.

This process is now completed, and the pre-approved plans and guidebook are ready for release to the public. However, per the grant that funded this effort, the City Council must accept the plans and approve the guidebook (bilingual) for official release. The attached resolution fulfills grant requirements.

DISCUSSION:

Architect fees for ADU plans can range anywhere from $5,000-$15,000, which is a major obstacle to affordability. Therefore, the Western Riverside Council of Governments ("WRCOG") and the City of Wildomar ("City") partnered in the development of pre-approved ADU architectural plans and an ADU Guidance Handbook to help facilitate and streamline the process for ADU development. These pre-approved architectural plans will be available, free of charge, for public use to obtain building permits for ADUs. The ADU Guidance Handbook will serve as a user-friendly guide, providing the public with information on the pre-approved architecture plans and ADUs in general, in English and Spanish.

The team has prepared and completed 6 pre-approved ADU architectural plan sets that will be available to the public for an expedited, ministerial process for permitting of an ADU on residential zoned properties with an existing or proposed residential dwelling(s). The ADUs provided by the plans vary in size from 500 to 1,200 square feet, including studio, onebedroom, two-bedroom and three-bedroom options. Each floor plan option will include three exterior architectural styles with varied exterior materials and a reverse plan option with some 263
floor plans including porch/patio options as well. The technical plans have been approved by the Community Development Department's Building Department/Building Official. A copy of the plans and guidebook are provided as attachments to this staff report.

If approved and accepted, staff anticipates releasing the plans and guidebook to the public by mid-March 2026.

FISCAL IMPACT:

There will be no fiscal impact to the city's department budget and general fund to develop these plans and the guidebook. WRCOG is administering the program and paying all consultants fees for this effort, with no cost to the city for any work being done. The funding is coming from the Southern California Association of Governments ("SCAG").

ATTACHMENTS:

Attach A - CC Resolution [3-11-26].docx
Attach A Ex. 1 Wildomar_Studio-Final.pdf
Attach A Ex. 2 Wildomar_1BR-Final.pdf
Attach A Ex. 3 Wildomar_2BR.a-Final.pdf
Attach A Ex. 4 Wildomar_2BR.b-Final.pdf
Attach A Ex. 5 Wildomar_3BR.a-Final.pdf
Attach A Ex. 6 Wildomar_3BR.b-Final.pdf
Attach A Ex. 7 Wildomar ADU Guidebook_English.pdf
Attach A Ex. 8 Wildomar ADU Guidebook_Spanish.pdf
Attach B - PRADU Presentation.pdf
264
RESOLUTION NO. 2026 - _____

A RESOLUTION OF THE CITY COUNCIL OF THE CITY OF WILDOMAR,

CALIFORNIA, ACCEPTING THE PRE-APPROVED ACCESSORY

DWELLING UNIT ARCHITECTURAL PLANS AND APPROVING AN

ASSOCIATED ADU GUIDEBOOK THAT MAY BE ADMINISTRATIVELY

AMENDED AS REASONABLY NEEDED
WHEREAS, the City of Wildomar has received assistance from the Southern California Association of Governments (SCAG) through the Western Riverside Council of Governments (WRCOG) for the Regional Early Action Planning (REAP) Local Staff Assistance Program to develop a full range of pre-approved ADU architectural plans and an associated guidebook; and
WHEREAS, City staff have been working alongside SCAG, WRCOG, Michael Baker International, and various subconsultants to develop 2022 code-compliant preapproved ADU architectural plans for permitting and construction and an associated ADU Guidebook in English and Spanish; and

NOW THEREFORE, THE CITY COUNCIL OF THE CITY OF WILDOMAR,

CALIFORNIA, DOES RESOLVE, DECLARE, DETERMINE, AND ORDER AS FOLLOWS:

SECTION 1. The recitals above are incorporated into the body of this Resolution by reference.

SECTION 2. The City Council approves and accepts the Pre-Approved ADU Architectural Plans for release for public use and approves the associated ADU Guidebook.

SECTION 3. The Community Development Director, or designee, is authorized to administratively modify the ADU Guidebook from time to time as reasonably needed.

PASSED, APPROVED, AND ADOPTED this 11th day of March, 2026. ____________________________
Carlos Marquez
Mayor
265
APPROVED AS TO FORM: ATTEST:
______________________________ ______________________________ Thomas D. Jex Janet Morales Garcia, CMC
City Attorney City Clerk
266
Sheet #
D
C
B
A
1 2 3 4 5
1 2 3 4 5
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

APPLICANT AGREEMENT
Consultant

AS NOTED

PROJECT DIRECTORY SHEET INDEX

BUILDING INFORMATION

PROJECT DESCRIPTION

PROJECT INFORMATION PROJECT CHECKLIST STYLE AND OPTION SELECTIONS

WILDOMAR, CALIFORNIA

APPLICANT
NAME:

ADDRESS:

PHONE:

EMAIL:

OWNER
NAME:

ADDRESS:

PHONE:

EMAIL:

SITE PLAN & TITLE SHEET PREPARATION
COMPANY:

CONTACT:

PHONE:

EMAIL:

ADDRESS:

CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT
23300 WILDOMAR TRAIL
WILDOMAR, CA 92595
(951) 677-4400
ZONING:

SETBACKS
FRONT:

REAR:

SIDE (INTERIOR):

SIDE (STREET):

ALLOWABLE PROPOSED

DISTANCE BETWEEN STRUCTURES

ALLOWABLE PROPOSED

PARKING

REQUIRED PROVIDED
SIDE (CORNER):

LOT COVERAGE

ALLOWABLE PROPOSED
LOT SIZE:

APPLICANT AGREES TO PROVIDE ALL NECESSARY INFORMATION REQUIRED TO COMPLETE THESE CONSTRUCTION DOCUMENTS. MODIFICATIONS TO THE PERMIT-READY DOCUMENTS PROVIDED BY

MICHAEL BAKER INTERNATIONAL ARE TO BE DISCLOSED BY THE APPLICANT AND APPROVED BY THE AUTHORITY HAVING JURISDICTION. ANY MODIFICATIONS TO THESE CONSTRUCTION DOCUMENTS REQUIRE EACH SHEET TO BE SIGNED BY THE PERSON WHO MADE THE CHANGES. ANY ADDITIONAL

SHEETS INCORPORATED INTO THESE DOCUMENTS ALSO REQUIRES A SIGNATURE BY THE PERSON WHO PREPARED THE INFORMATION. THE FOUNDATION DESIGN FOR THESE PERMIT-READY CONSTRUCTION DOCUMENTS ASSUMES STANDARD SOILS CONDITIONS AND LEVEL TOPOGRAPHY. IF SITE SPECIFIC

CONDITIONS REQUIRE A FOUNDATION DESIGN BEYOND WHAT IS PROVIDED IN THESE DOCUMENTS THE

THE APPLICANT IS TO PROVIDE A NEW FOUNDATION DESIGN THAT COMPLIES WITH THE RECOMMENDATION OF THE GEOGRAPHIC ENGINEER ’S REPORT.

BY SIGNING BELOW THE APPLICANT AGREES TO THE STATEMENT ABOVE AND WILL COMPLY WITH ALL LOCAL CODE REQUIREMENTS.

SIGNATURE: DATE:

VICINITY MAP

APPLICABLE CODES
AND STANDARDS:

WILDOMAR MUNICIPAL CODE
2022 CALIFORNIA ADMINISTRATIVE CODE (CAC)

WILDOMAR ADMINISTRATIVE PROVISIONS
2022 CALIFORNIA BUILDING CODE (CBC)
2022 CALIFORNIA RESIDENTIAL CODE (CRC)
2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN) 2022 CALIFORNIA ENERGY CODE (CEEC)
2022 CALIFORNIA ELECTRICAL CODE (CEC)
2022 CALIFORNIA MECHANICAL CODE (CMC)
2022 CALIFORNIA PLUMBING CODE (CPC)
2022 CALIFORNIA FIRE CODE (CFC)
SITE ADDRESS:

OCCUPANCY GROUP: R3
CONSTRUCTION TYPE: VB
STORIES: 1
HEIGHT:

OWNER OR APPLICANT TO SELECT ONE OF THE FOLLOWING STYLES AND ONE OF EACH OF THE SUBSEQUENT OPTIONS WITHIN THE SELECTED STYLE. MARK SELECTIONS WITH "X". FINISH COLORS OF ADU TO MATCH PRINAICPAL DWELLING UNIT.

CRAFTSMAN

FIBER CEMENT LAP SIDING

STONE VENEER

FIBER CEMENT TRIM
COLOR:

COLOR:

COLOR:

ASPHALT SHINGLE ROOF
COLOR:

EXTERIOR SOFFITS, RAKES & EAVES
COLOR:

OPTION A - EXTERIOR GRADE TONGUE & GROOVE

OPTION B - FIBER CEMENT

MONTEREY
STUCCO

FIRE CEMENT TRIM
COLOR:

COLOR:

CONCRETE TILE ROOF
COLOR:

EXTERIOR SOFFITS, RAKES & EAVES
COLOR:

OPTION A - EXTERIOR GRADE TONGUE & GROOVE

OPTION B - FIBER CEMENT

MODERN FARMHOUSE

BOARD AND BATTEN FIBER CEMENT PANEL SIDING

EXTERIOR FIBER CEMENT TRIM
COLOR:

COLOR:

EXTERIOR SOFFITS, RAKES & EAVES
COLOR:

OPTION A - EXTERIOR GRADE TONGUE & GROOVE

OPTION B - FIBER CEMENT

ROOF MATERIAL
COLOR:

OPTION A - ASPHALT SHINGLE ROOF

OPTION B - STANDING SEAM METAL ROOF

WINDOWS
COLOR:

WINDOWS
COLOR:

WINDOWS
COLOR:

WASTE WATER

FIRE SPRINKLERS

GAS SERVICE

ADDITIONAL PERMITS TO BE OBTAINED BY APPLICANT

ADU TO HAVE NEW CONNECTION TO CITY SEWER MAIN

ADU TO CONNECTO EXISTING RESIDENCE SEWER LATERAL

SEPTIC (REQUIRES HEALTH DEPARTMENT APPROVAL)

UPGRADED SERVICE

EXISTING SERVICE TO REMAIN

NEW SERVICE
SIZE OF EXISTING SERVICE:

SIZE OF PROPOSED SERVICE:

EXISTING PRIMARY RESIDENCE CURRENTLY HAS FIRE SPRINKLERS

EXISTING PRIMARY RESIDENCE DOES NOT CURRENTLY HAVE FIRE SPRINKLERS

PROPERTY IS LOCATED IN THE VERY HIGH FIRE HAZARD SEVERITY ZONE (VHFSZ)

PROPERTY IS NOT LOCATED IN THE VERY HIGH FIRE HAZARD SEVERITY ZONE

PROPOSED ADU IS REQUIRED TO HAVE FIRE SPRINKLERS IF THE EXISTING PRIMARY

RESIDENCE HAS FIRE SPRINKLERS
SPRINKLERS REQUIRED:

OPTION A - YES

OPTION B - NO

FIRE RATED DETAILS

1. 2.

3. 4.

FIRE RATED DETAILS ARE REQUIRED WHEN:

THE PROPERTY IS LOCATED IN THE VHFSV
BUILDING WALLS AND/OR ROOF EAVES ARE LESS THAN 5 FT FROM THE PROPERTY

LINE IN AN UNSPRINKLERED BUILDING
BUILDING WALLS AND/OR EAVES ARE LESS THAN 3 FT FROM THE PROPERTY LINE IN A SPRINKLERED BUILDING.

BUILDING WALLS AND/OR ROOF EAVES ARE LESS THAN 10 FT FROM THE MAIN

DWELLING OR ADJACENT BUILDING/STRUCTURE UNIT IN AN UNSPRINKLERED BUILDINGBUILDING WALLS AND/OR ROOF EAVES ARE LESS THAN 6 FT FROM THE

MAIN DWELLING UNIT ADJACENT BUILDING/STRUCTUREIN A SPRNKLERED BUILDING

OPTION A - YES

OPTION B - NO
FIRE RATED DETAILS REQUIRED:

HERS NOTES

ELECTRICAL SERVICE

UPGRADED SERVICE

EXISTING SERVICE TO REMAIN

NEW SERVICE
SIZE OF EXISTING SERVICE:

SIZE OF PROPOSED SERVICE:

APN:

ADDITIONAL PERMITS

FIRE SPRINKLERS (WHEN REQUIRED)

1. 2.

PHOTOVOLTAIC SYSTEM

SYSTEM MUST BE INSTALLED AND OPERATIONAL PRIOR TO FINAL BUILDING INSPECTION AND APPROVAL FOR ADU (WHEN REQUIRED).

FOR AN EXISTING PHOTOVOLATIC SYSTEM OF SUFFICIENT SIZE ON THE

PRIMARY RESIDENCE TO ACCOMODATE THE NEW ADU, THE

OWNER/APPLICANT IS TO PROVIDE A REPORT INDICATING THE
EXISTING SIZE OF THE PV PANEL.

OWNER OR APPLICANT TO MARK SELECTIONS WITH "X"

ROOF FRAMING

ROOF FRAMING PER DRAWINGS

ROOF TRUSSES

IN LIEU OF ROOF DETAILS PROVIDED ON THESE PLANS, OWNER IS TO CONTRACT

WITH AN INDEPENDENT TRUSS COMPANY AND SUBMIT TRUSS CALCULATIONS TO THE CITY OF WILDOMAR FOR APPROVAL. INDICATE ON THE CHECKLIST BELOW IF TRUSS PACKAGE WILL BE PROVIDED AS A SEPARATE SUBMITTAL.

ADDITIONAL SUPPORTING DOCUMENTS (BY APPLICANT)
COMPLETED COVER SHEET (G-0.0)
SITE PLAN SHEET (AS-1.1) FOR CITY OF

WILDOMAR REVIEW

DEMOLITION PERMIT IF REQUIRED HOLD HARMLESS AGREEMENT
TITLE 24 ENERGY CALCULATION REPORT

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR WHICH IT WAS

PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER TIME

AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR REDUCE THE RECIPIENT'S RESPONSIBILITY TO

VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO

WARRANTIES OF ANY NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY.

FURTHERMORE, THE RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS HARMLESS FROM ANY AND

ALL CLAIMS, SUITS, LIABILITY, DEMANDS, JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING

THERE FROM ANY USE OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

1. 2.

3. 4.

5. 6.

7. PROPERLY COMPLETED AND ELECTRONICALLY SIGNED CERTIFICATE OF INSTALLATION (CF2R FORMS) SHALL BE POSTED WEATHER PROTECTED WITHIN BUILDING FOR REVIEW BY INSPECTORS - EES 10-103( A)3, 10-103(B )1.A - BY THE

INSTALLING CONTRACTOR AND SUBMITTED TO THE FIELD INSPECTOR DURING CONSTRUCTION AT THE SITE. FOR PROJECTS REQUIRING HERS VERIFICATION, THE CF2R FORMS SHALL BE REGISTERED WITH A CALIFORNIA APPROVED HERS PROVIDER DATA REGISTRY WITH ITS OWN UNIQUE 21 DIGIT REGISTRATION NUMBER LOCATED AT THE BOTTOM OF EACH PAGE. THE FIRST 12 DIGITS WILL MATCH THE REGISTRATION NUMBER ASSOCIATED WITH THE CF1 R FORM. CERTIFICATE OF OCCUPANCY WILL NOT BE ISSUED UNTIL THE CF2R FORMS ARE REVIEWED AND APPROVED.

PROPERLY COMPLETED & ELECTRONICALLY SIGNED AND REGISTERED CERTIFICATE(S) OF FIELD VERIFICATION AND DIAGNOSTIC TESTING (CF3R) SHALL BE

POSTED WEATHER PROTECTED WITHIN THE BUILDING SITE BY A CERTIFIED HERS RATER. A REGISTERED CF3R WILL HAVE A UNIQUE 25 DIGIT REGISTRATION NUMBER LOCATED AT THE BOTTOM OF EACH PAGE. THE FIRST 20 DIGITS OF THE NUMBER WILL MATCH THE REGISTRATION NUMBER ASSOCIATED WITH THE CF2R. CERTIFICATE OF OCCUPANCY WILL NOT BE ISSUED UNTIL THE CF3R IS REVIEWED AND APPROVED. EES 10-103(0)3, 10-103(B)1.A.

CF1 R REGISTRATION FORMS ARE LOCATED ON THE PLANS. IF REGISTRATION IS REQUIRED, A WATER-MARK AND REGISTRATION NUMBER WILL BE VISIBLE. QUALITY INSULATION INSPECTION - HIRE HERS RATER EARLY BEFORE DRYWALL. VARIABLE

CAPACITY HEAT PUMP - DUCTLESS UNITS ENTIRELY LOCATED IN CONDITIONED

SPACE, AIRFLOW IN HABITABLE ROOMS, WALL MOUNTED THERMOSTAT IN ZONES GREATER THAN 150 S. F., VERIFY HEAT PUMP RATED CAPACITY, AND REFRIGERANT CHARGE. AT ADU -STUDIO, 1 BED, 2 BED & 2 BED 2 BATH - R-6 DUCTS IN CONDITIONED SPACE, VERIFIED EER/EER2, SEER/SEER2, HSPF, HEAT PUMP RATED HEATING CAPACITY, MIN AIRFLOW, REFRIGERANT CHARGE, & FAN WATT DRAW/FAN EFFICACY.

REFERENCE KEYNOTE MP14 ON SHEET MEP.1 FOR KITCHEN RANGE HOOD CFM REQUIREMENTS.

FOR IAQ FAN - PLEASE SEE SITE SPECIFIC CALCULATIONS FOR CFM REQUIRED FOR A CONTINUOUSLY OPERATING EXHAUST FAN. PROVIDE A TIMER SWITCH WITH A MANUAL OFF AND A SOUND RATING OF 1 SONE (3 SONES MAX FOR AN INTERMITTENT FAN). THIS FAN TO PROVIDE A WHOLE BUILDING INDOOR AIR QUALITY VENTILATION WITH OUTDOOR AIR IN COMPLIANCE WITH ASHRAE STANDARD 62.2 AS ADOPTED BY THE CALIFORNIA ENERGY COMMISSION.

PV SYSTEM SOLAR: SEE SITE SPECIFIC T24 SHEETS FOR KWDC REQUIRED. POSSIBLE PV EXCEPTION 2: NO PV REQUIRED WHEN MINIMUM PV SIZE < 1.8 KWDC(SECTION 150.1 (C)14) PV EXEMPTION BASED IN UPDATED ENERGY CALCULATIONS WITH SITE SPECIFIC INFORMATION.

SPECIAL FEATURES: VCHP REQUIRED ITEMS LISTED ABOVE, EXPOSED SLAB FLOORING, AND NEEA RATED HEAT PUMP WATER HEATER; SPECIFIC BRAND/MODEL OR EQ., AND SOLAR EXEMPTION 2 WAS TAKEN AT STUDIO & 1 BED NEW 2022 ELECTRIC READY REQUIREMENTS FOR NEW CONSTRUCTION: IF HEAT

PUMP WATER HEATER IS NOT INSTALLED, PROVIDE SPACE FOR THIS TYPE OF WATER HEATER. A 240V OUTLET IS REQUIRED FOR WATER HEATER, DRYER, AUTO CHARGING, AND STOVE INCLUDING BREAKER SPACE. ENERGY STORAGE SYSTEM FOR A FUTURE

BATTERY SYSTEM (BATTERY READY) IS REQUIRED IF FULL SYSTEM IS NOT INSTALLED.

GRADING PERMIT IF REQUIRED AS

DETERMINED BY CITY OF WILDOMAR

ENGINEERING DEPARTMENT

CONSTRUCTION WASTE MANAGEMENT
PLAN

COVER SHEET
G-0.0
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
FINAL DESIGN - 02/27/2026
STUDIO
AS-1.1 ARCHITECTURAL - SITE PLAN
A-1.0 GENERAL NOTES, ABBREVIATIONS, AND SYMBOLS
A-1.1 STUDIO - FLOOR PLAN AND ROOF PLAN (CRAFTSMAN)
A-1.2 STUDIO - FLOOR PLAN AND ROOF PLAN (MONTEREY)
A-1.3 STUDIO - FLOOR PLAN AND ROOF PLAN (MODERN FARMHOUSE) A-2.1 STUDIO - EXTERIOR ELEVATIONS (CRAFTSMAN)
A-2.2 STUDIO - EXTERIOR ELEVATIONS (MONTEREY)
A-2.3 STUDIO - EXTERIOR ELEVATIONS (MODERN FARMHOUSE)
A-3.1 STUDIO - BUILDING SECTIONS (CRAFTSMAN)
A-3.2 STUDIO - BUILDING SECTIONS (MONTEREY)
A-3.3 STUDIO - BUILDING SECTIONS (MODERN FARMHOUSE)
A-5.1 DETAILS
A-5.2 ROOF DETAILS
A-6.1 WINDOW AND DOOR SCHEDULES & DETAILS
G-0.0 COVER SHEET
G-0.1 EXTERIOR VIEWS - STYLE OPTIONS
G-0.2 CALGREEN RESIDENTIAL CHECKLIST
G-0.3 CALGREEN RESIDENTIAL CHECKLIST
NEW CONSTRUCTION OF A ONE STORY 493 SF DETACHED STUDIO ACCESSORY DWELLING UNIT.

MEP.0 MECHANICAL/ELECTRICAL/PLUMBING GENERAL NOTES
MEP.1 MECHANICAL/ELECTRICAL/PLUMBING PLANS
S0.1 STRUCTURAL NOTES & SPECIFICATIONS
S1.1 CRAFTSMAN FOUNDATION & FRAMING PLAN
S1.2 MONTEREY FOUNDATION & FRAMING PLAN
S1.3 FARMHOUSE FOUNDATION & FRAMING PLAN
S2.1 STRUCTURAL DETAILS
S2.2 STRUCTURAL DETAILS
T24.1 EXAMPLE TITLE 24 CALCULATIONS
T24.2 EXAMPLE TITLE 24 CALCULATIONS
T24.3 EXAMPLE TITLE 24 CALCULATIONS
11' - 9"

REVISIONS
NO. DATE DESCRIPTION
267

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

EXTERIOR VIEWS - STYLE OPTIONS
G-0.1
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026

REVISIONS
NO. DATE DESCRIPTION
SCALE: 12" = 1'-0"

EXTERIOR PERSPECTIVE - MONTEREY
2 SCALE: 12" = 1'-0"

EXTERIOR PERSPECTIVE - MODERN FARMHOUSE
3 SCALE: 12" = 1'-0"

EXTERIOR PERSPECTIVE - CRAFTSMAN
1 268
Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

CALGREEN RESIDENTIAL CHECKLIST
G-0.2
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026

REVISIONS
NO. DATE DESCRIPTION
CHAPTER 4

RESIDENTIAL MANDATORY MEASURES
DIVISION 4.1 PLANNING AND DESIGN
DIVISION 4.3 WATER EFFICIENCY AND CONSERVATION

4.406 ENHANCED DURABILITY AND REDUCED MAINTENANCE

4.406.1 RODENT PROOFING. Annular spaces around pipes, electric cables, conduits or other openings in sole/bottom plates at exterior walls shall be protected against the passage of rodents by closing such openings with cement mortar, concrete masonry or a similar method acceptable to the enforcing agency.

4.408 CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RECYCLING

4.408.1 CONSTRUCTION WASTE MANAGEMENT. Recycle and/or salvage for reuse a minimum of 65 percent of the non-hazardous construction and demolition waste in accordance with either Section

4.408.2, 4.408.3 or 4.408.4, or meet a more stringent local construction and demolition waste management ordinance.

Exceptions:

1. Excavated soil and land-clearing debris.

2. Alternate waste reduction methods developed by working with local agencies if diversion or recycle facilities capable of compliance with this item do not exist or are not located reasonably close to the jobsite.

3. The enforcing agency may make exceptions to the requirements of this section when isolated jobsites are located in areas beyond the haul boundaries of the diversion facility.

4.408.2 CONSTRUCTION WASTE MANAGEMENT PLAN. Submit a construction waste management plan in conformance with Items 1 through 5. The construction waste management plan shall be updated as necessary and shall be available during construction for examination by the enforcing agency.

1. Identify the construction and demolition waste materials to be diverted from disposal by recycling, reuse on the project or salvage for future use or sale.

2. Specify if construction and demolition waste materials will be sorted on-site (source separated) or bulk mixed (single stream).

3. Identify diversion facilities where the construction and demolition waste material collected will be taken.

4. Identify construction methods employed to reduce the amount of construction and demolition waste generated.

5. Specify that the amount of construction and demolition waste materials diverted shall be calculated by weight or volume, but not by both.

4.408.3 WASTE MANAGEMENT COMPANY. Utilize a waste management company, approved by the enforcing agency, which can provide verifiable documentation that the percentage of construction and demolition waste material diverted from the landfill complies with Section 4.408.1.

Note: The owner or contractor may make the determination if the construction and demolition waste materials will be diverted by a waste management company.

4.408.4 WASTE STREAM REDUCTION ALTERNATIVE [LR]. Projects that generate a total combined weight of construction and demolition waste disposed of in landfills, which do not exceed 3.4 lbs./sq.ft. of the building area shall meet the minimum 65% construction waste reduction requirement in Section 4.408.1

4.408.4.1 WASTE STREAM REDUCTION ALTERNATIVE. Projects that generate a total combined weight of construction and demolition waste disposed of in landfills, which do not exceed 2 pounds per square foot of the building area, shall meet the minimum 65% construction waste reduction requirement in Section 4.408.1

4.408.5 DOCUMENTATION. Documentation shall be provided to the enforcing agency which demonstrates compliance with Section 4.408.2, items 1 through 5, Section 4.408.3 or Section 4.408.4..

Notes:1. Sample forms found in "A Guide to the California Green Building Standards Code (Residential)" located at www.hcd.ca.gov/CALGreen.html may be used to assist in documenting compliance with this section.

2. Mixed construction and demolition debris (C & D) processors can be located at the California Department of Resources Recycling and Recovery (CalRecycle).

4.410 BUILDING MAINTENANCE AND OPERATION

4.410.1 OPERATION AND MAINTENANCE MANUAL. At the time of final inspection, a manual, compact disc, web-based reference or other media acceptable to the enforcing agency which includes all of the following shall be placed in the building:

1. Directions to the owner or occupant that the manual shall remain with the building throughout the life cycle of the structure.

2. Operation and maintenance instructions for the following:
a. Equipment and appliances, including water-saving devices and systems, HVAC systems, photovoltaic systems, electric vehicle chargers, water-heating systems and other major appliances and equipment.
b. Roof and yard drainage, including gutters and downspouts. c. Space conditioning systems, including condensers and air filters. d. Landscape irrigation systems.
e. Water reuse systems.

3. Information from local utility, water and waste recovery providers on methods to further reduce resource consumption, including recycle programs and locations.

4. Public transportation and/or carpool options available in the area.

5. Educational material on the positive impacts of an interior relative humidity between 30-60 percent and what methods an occupant may use to maintain the relative humidity level in that range.

6. Information about water-conserving landscape and irrigation design and controllers which conserve water.

7. Instructions for maintaining gutters and downspouts and the importance of diverting water at least 5 feet away from the foundation.

8. Information on required routine maintenance measures, including, but not limited to, caulking, painting, grading around the building, etc.

9. Information about state solar energy and incentive programs available.

10. A copy of all special inspections verifications required by the enforcing agency or this code.

11. Information from the Department of Forestry and Fire Protection on maintenance of defensible space around residential structures.

12. Information and/or drawings identifying the location of grab bar reinforcements.

4.410.2 RECYCLING BY OCCUPANTS. Where 5 or more multifamily dwelling units are constructed on a building site, provide readily accessible area(s) that serves all buildings on the site and are identified for the depositing, storage and collection of non-hazardous materials for recycling, including (at a minimum) paper, corrugated cardboard, glass, plastics, organic waster, and metals, or meet a lawfully enacted local recycling ordinance, if more restrictive.

Exception: Rural jurisdictions that meet and apply for the exemption in Public Resources Code Section 42649.82 (a)(2)(A) et seq. are note required to comply with the organic waste portion of this section.

DIVISION 4.4 MATERIAL CONSERVATION AND RESOURCE

EFFICIENCY
DIVISION 4.5 ENVIRONMENTAL QUALITY

4.303 INDOOR WATER USE

4.303.1 WATER CONSERVING PLUMBING FIXTURES AND FITTINGS. Plumbing fixtures (water closets and urinals) and fittings (faucets and showerheads) shall comply with the sections 4.303.1.1, 4.303.1.2, 4.303.1.3, and 4.303.4.4.

Note: All noncompliant plumbing fixtures in any residential real property shall be replaced with water-conserving plumbing fixtures. Plumbing fixture replacement is required prior to issuance of a certificate of final completion, certificate of occupancy, or final permit approval by the local building department. See Civil Code Section 1101.1, et seq., for the definition of a noncompliant plumbing fixture, types of residential buildings affected and other important enactment dates.

4.303.1.1 Water Closets. The effective flush volume of all water closets shall not exceed 1.28 gallons per flush. Tank-type water closets shall be certified to the performance criteria of the U.S. EPA WaterSense Specification for Tank-type Toilets.

Note: The effective flush volume of dual flush toilets is defined as the composite, average flush volume of two reduced flushes and one full flush.

4.303.1.2 Urinals. The effective flush volume of wall mounted urinals shall not exceed 0.125 gallons per flush.

The effective flush volume of all other urinals shall not exceed 0.5 gallons per flush.

4.303.1.3 Showerheads.

4.303.1.3.1 Single Showerhead. Showerheads shall have a maximum flow rate of not more than 1.8 gallons per minute at 80 psi. Showerheads shall be certified to the performance criteria of the U.S. EPA WaterSense Specification for Showerheads.

4.303.1.3.2 Multiple showerheads serving one shower. When a shower is served by more than one showerhead, the combined flow rate of all the showerheads and/or other shower outlets controlled by a single valve shall not exceed 1.8 gallons per minute at 80 psi, or the shower shall be designed to only allow one shower outlet to be in operation at a time.

Note: A hand-held shower shall be considered a showerhead.

4.303.1.4 Faucets.

4.303.1.4.1 Residential Lavatory Faucets. The maximum flow rate of residential lavatory faucets shall not exceed 1.2 gallons per minute at 60 psi. The minimum flow rate of residential lavatory faucets shall not be less than 0.8 gallons per minute at 20 psi.

4.303.1.4.2 Lavatory Faucets in Common and Public Use Areas. The maximum flow rate of lavatory faucets installed in common and public use areas (outside of dwellings or sleeping units) in residential buildings shall not exceed 0.5 gallons per minute at 60 psi.

4.303.1.4.3 Metering Faucets. Metering faucets when installed in residential buildings shall not deliver more than 0.2 gallons per cycle.

4.303.1.4.4 Kitchen Faucets. The maximum flow rate of kitchen faucets shall not exceed 1.8 gallons per minute at 60 psi. Kitchen faucets may temporarily increase the flow above the maximum rate, but not to exceed 2.2 gallons per minute at 60 psi, and must default to a maximum flow rate of 1.8 gallons per minute at 60 psi.

Note: Where complying faucets are unavailable, aerators or other means may be used to achieve reduction.

4.303.1.4.5 Pre-rinse spray valves.

When installed, shall meet the requirements in the California Code of Regulations, Title 20 (Appliance Efficiency Regulations), Sections 1605.1 (h)(4) Table H-2, Section 1605.3 (h)(4)(A), and Section 1607 (d)(7) and shall be equipped with an integral automatic shutoff.

FOR REFERENCE ONLY: The following table and code section have been reprinted from the California Code of Regulations, Title 20 (Appliance Efficiency Regulations),Section 1605.1 (h)(4) and Section 1605.3 (h)(4)(A).

Title 20 Section 1605.3 (h)(4)(A): Commercial prerinse spray values manufactured on or after January 1, 2006, shall have a minimum spray force of not less than 4.0 ounces-force (ozf)[113 grams-force(gf)]

4.303.2 Submeters for multifamily buildings and dwelling units in mixed-used residential/commercial buildings.

Submeters shall be installed to measure water usage of individual rental dwelling units in accordance with the California Plumbing Code. 4.303.3 Standards for plumbing fixtures and fittings. Plumbing fixtures and fittings shall be installed in accordance with the California Plumbing Code, and shall meet the applicable standards referenced in Table 1701.1 of the California Plumbing Code.

TABLE - MAXIMUM FIXTURE WATER USE

FIXTURE TYPE FLOW RATE
SHOWER HEADS (RESIDENTIAL) 1.8 GMP @ 80 PSI
LAVATORY FAUCETS (RESIDENTIAL) MAX. 1.2 GPM @ 60 PSI MIN. 0.8 GPM @ 20 PSI

LAVATORY FAUCETS IN COMMON & PUBLIC

USE AREAS

0.5 GPM @ 60 PSI
KITCHEN FAUCETS 1.8 GPM @ 60 PSI
METERING FAUCETS 0.2 GAL/CYCLE
WATER CLOSET 1.28 GAL/FLUSH
URINALS 0.125 GAL/FLUSH

4.304 OUTDOOR WATER USE

4.304.1 OUTDOOR POTABLE WATER USE IN LANDSCAPE AREAS. Residential developments shall comply with a local water efficient landscape ordinance or the current California Department of Water Resources' Model Water Efficient Landscape Ordinance (MWELO), whichever is more stringent.

NOTES:

1. The Model Water Efficient Landscape Ordinance (MWELO) is located in the California Code Regulations, Title 23, Chapter 2.7, Division 2. MWELO and supporting documents, including water budget calculator, are available at: https://www.water.ca.gov/
ABBREVIATION DEFINITIONS:

HCD Department of Housing and Community Development
BSC California Building Standards Commission
DSA-SS Division of the State Architect, Structural Safety OSHPD Office of Statewide Health Planning and Development LR Low Rise
HR High Rise
AA Additions and Alterations N New
NOTE:

THIS TABLE COMPILES THE DATA IN SECTION 4.303.1, AND IS INCLUDED AS A CONVENIENCE FOR THE USER.

SECTION 4.102 DEFINITIONS

4.102.1 DEFINITIONS
The following terms are defined in Chapter 2 (and are included here for reference) FRENCH DRAIN. A trench, hole or other depressed area loosely filled with rock, gravel, fragments of brick or similar pervious material used to collect or channel drainage or runoff water.

WATTLES. Wattles are used to reduce sediment in runoff. Wattles are often constructed of natural plant materials such as hay, straw or similar material shaped in the form of tubes and placed on a downflow slope. Wattles are also used for perimeter and inlet controls.

4.106 SITE DEVELOPMENT

4.106.1 GENERAL. Preservation and use of available natural resources shall be accomplished through evaluation and careful planning to minimize negative effects on the site and adjacent areas. Preservation of slopes, management of storm water drainage and erosion controls shall comply with this section.

4.106.2 STORM WATER DRAINAGE AND RETENTION DURING CONSTRUCTION. Projects which disturb less than one acre of soil and are not part of a larger common plan of development which in total disturbs one acre or more, shall manage storm water drainage during construction. In order to manage storm water drainage during construction, one or more of the following measures shall be implemented to prevent flooding of adjacent property, prevent erosion and retain soil runoff on the site.

1. Retention basins of sufficient size shall be utilized to retain storm water on the site.

2. Where storm water is conveyed to a public drainage system, collection point, gutter or similar disposal method, water shall be filtered by use of a barrier system, wattle or other method approved by the enforcing agency.

3. Compliance with a lawfully enacted storm water management ordinance.

Note: Refer to the State Water Resources Control Board for projects which disturb one acre or more of soil, or are part of a larger common plan of development which in total disturbs one acre or more of soil. (Website: https://www.waterboards.ca.gov/water_issues/programs/stormwater/construction.html)

4.106.3 GRADING AND PAVING. Construction plans shall indicate how the site grading or drainage system will manage all surface water flows to keep water from entering buildings. Examples of methods to manage surface water include, but are not limited to, the following:

1. Swales

2. Water collection and disposal systems

3. French drains

4. Water retention gardens

5. Other water measures which keep surface water away from buildings and aid in groundwater recharge.

Exception: Additions and alterations not altering the drainage path.

4.106.4 Electric vehicle (EV) charging for new construction. New construction shall comply with Section 4.106.4.1 or 4.106.4.2. Electric vehicle supply equipment (EVSE) shall comply with the California Electrical Code. Exceptions:

1. On a case-by-case basis, where the local enforcing agency has determined EV charging and infrastructure are not feasible based upon one or more of the following conditions:

1.1 Where there is no local utility power supply or the local utility is unable to supply adequate power.

1.2 Where there is evidence suitable to the local enforcing agency substantiating that additional local utility infrastructure design requirements, directly related to the implementation of Section

4.106.4, may adversely impact the construction cost of the project.

2. Accessory Dwelling Units (ADU) and Junior Accessory Dwelling Units (JADU) without additional parking facilities.

4.106.4.1 New one- and two-family dwellings and townhouses with attached private garages. For each dwelling unit, install a listed raceway to accommodate a dedicated 208/240-volt branch circuit. The raceway shall not be less than trade size 1 (nominal 1-inch inside diameter). The raceway shall originate at the main service or subpanel and shall terminate into a listed cabinet, box or other enclosure in close proximity to the proposed location of an EV charger. Raceways are required to be continuous at enclosed, inaccessible or concealed areas and spaces. The service panel and/or subpanel shall provide capacity to install a 40-ampere 208/240-volt minimum dedicated branch circuit and space(s) reserved to permit installation of a branch circuit overcurrent protective device.

Exemption: A raceway is not required if a minimum 40-ampere 208/240-volt dedicated EV branch circuit is installed in close proximity to the proposed location of an EV charger at the time of original construction in accordance with the California Electrical Code. 4.106.4.1.1 Identification. The service panel or subpanel circuit directory shall identify the overcurrent protective device space(s) reserved for future EV charging as "EV CAPABLE". The raceway termination location shall be permanently and visibly marked as "EV CAPABLE".

CHAPTER 3

GREEN BUILDING
SECTION 301 GENERAL
301.1 SCOPE. Buildings shall be designed to include the green building measures specified as mandatory in the application checklists contained in this code. Voluntary green building measures are also included in the application checklists and may be included in the design and construction of structures covered by this code, but are not required unless adopted by a city, county, or city and county as specified in Section 101.7. 301.1.1 Additions and alterations. [HCD] The mandatory provisions of Chapter 4 shall be applied to additions or alterations of existing residential buildings where the addition or alteration increases the building's conditioned area, volume, or size. The requirements shall apply only to and/or within the specific area of the addition or alteration.

The mandatory provision of Section 4.106.4.2 may apply to additions or alterations of existing parking facilities or the addition of new parking facilities serving existing multifamily buildings. See Section

4.106.4.3 for application.

Note: Repairs including, but not limited to, resurfacing, restriping and repairing or maintaining existing lighting fixtures are not considered alterations for the purpose of this section.

Note: On and after January 1, 2014, residential buildings undergoing permitted alterations, additions, or improvements shall replace noncompliant plumbing fixtures with water-conserving plumbing fixtures.

Plumbing fixture replacement is required prior to issuance of a certificate of final completion, certificate of occupancy or final permit approval by the local building department. See Civil Code Section 1101.1, et seq., for the definition of a noncompliant plumbing fixture, types of residential buildings affected and other important enactment dates.
301.2 LOW-RISE AND HIGH-RISE RESIDENTIAL BUILDINGS. [HCD] The provisions of individual sections of CALGreen may apply to either low-rise residential buildings high-rise residential buildings, or both. Individual sections will be designated by banners to indicate where the section applies specifically to low-rise only (LR) or high-rise only (HR). When the section applies to both low-rise and high-rise buildings, no banner will be used.

SECTION 302 MIXED OCCUPANCY BUILDINGS
302.1 MIXED OCCUPANCY BUILDINGS. In mixed occupancy buildings, each portion of a building shall comply with the specific green building measures applicable to each specific occupancy.

Exceptions:

1. [HCD] Accessory structures and accessory occupancies serving residential buildings shall comply with Chapter 4 and Appendix A4, as applicable.

2. [HCD] For purposes of CALGreen, live/work units, complying with Section 419 of the California Building Code, shall not be considered mixed occupancies. Live/Work units shall comply with Chapter 4 and Appendix A4, as applicable.

4.106.4.2 New multifamily dwellings, hotels and motels and new residential parking facilities.

When parking is provided, parking spaces for new multifamily dwellings, hotels and motels shall meet the requirements of Section 4.106.4.2.2. Calculations for spaces shall be rounded up to the nearest whole number. A parking space served by electric vehicle supply equipment or designed as an EV charging space shall count as at least one standard automobile parking space only for the purpose of complying with any applicable minimum parking space requirements established by a local jurisdiction. See Vehicle Code Section 22511.2 for further details.

4.106.4.2.1 Reserved.

4.106.4.2.2 Multifamily dwellings, hotels and motels

1. EV ready parking spaces with receptacles.
a. Hotels and motels. Forty (40) percent of the total number of parking spaces shall be equipped with low power Level 2 EV charging receptacles.
b. Multifamily parking facilities. Forty (40) percent of the total number of parking spaces shall be equipped with low power Level 2 EV charging receptacles. EV charging receptacles required by this section shall be located in at least one assigned parking space per dwelling unit where assigned parking is provided but need not exceed forty (40) percent of the total number of assigned parking spaces provided on the site.

Exception: Areas of parking facilities served by parking lifts, including but not limited to automated mechanical-access open parking garages as defined in the California Building Code; or parking facilities otherwise incapable of supporting electric vehicle charging. c. Receptacle power source. EV charging receptacles in multifamily parking facilities shall be provided with a dedicated branch circuit connected to the dwelling unit’s electrical panel, unless determined as infeasible by the project builder or designer and subject to concurrence of the local enforcing agency.

Exception: Areas of parking facilities served by parking lifts, including but not limited to automated mechanical-access open parking garages as defined in the California Building Code; or parking facilities otherwise incapable of supporting electric vehicle charging. d. Receptacle configurations. 208/240V EV charging receptacles shall comply with one of the following configurations:

1. For 20-ampere receptacles, NEMA 6-20R

2. For 30-ampere receptacles, NEMA 14-30R

3. For 50-ampere receptacles, NEMA 14-50R

2. EV ready parking spaces with EV chargers.
a. Hotels and motels. Ten (10) percent of the total number of parking spaces shall be equipped with Level 2 EV chargers. At least fifty (50) percent of the required EV chargers shall be equipped with J1772 connectors.
b. Multifamily parking facilities. Ten (10) percent of the total number of parking spaces shall be equipped with Level 2 EV chargers. At least fifty (50) percent of the required EV chargers shall be equipped with J1772 connectors. Where common use parking or unassigned parking is provided, EV chargers shall be located in common use or unassigned parking areas and shall be available for use by all residents or guests.

Where low power Level 2 EV charging receptacles or Level 2 EV chargers are installed beyond the minimum required, an automatic load management system (ALMS) may be used to reduce the maximum required electrical capacity to each space served by the ALMS. The electrical system and any on-site distribution transformers shall have sufficient capacity to deliver at least 3.3 kW simultaneously to each EV charging station (EVCS) served by the ALMS. The branch circuit shall have a minimum capacity of 40 amperes, and installed EV chargers shall have a capacity of not less than 30 amperes.

4.106.4.2.2.1 Electric vehicle charging stations (EVCS).

Electric vehicle charging stations required by Section 4.106.4.2.2, Item 2, with EV chargers installed shall comply with Section 4.106.4.2.2.1.1.

Exception: Electric vehicle charging stations serving public accommodations, public housing, motels and hotels shall not be required to comply with this section. See California Building Code, Chapter 11B, for applicable requirements.

4.106.4.2.2.1.1 Electric vehicle charging stations (EVCS) spaces with EV chargers installed; dimensions and location.

EVCS spaces shall be designed to comply with the following:

1. The minimum length of each EVCS space shall be 18 feet (5486 mm).

2. The minimum width of each EVCS space shall be 9 feet (2743 mm).

3. One in every 25 EVCS spaces, but not less than one, shall also have an 8-foot (2438 mm) wide minimum aisle. A 5-foot (1524 mm) wide minimum aisle shall be permitted provided the minimum width of the EVCS space is 12 feet (3658 mm). Surface slope for this EVCS space and the aisle shall not exceed 1 unit vertical in 48 units horizontal (2.083 percent slope) in any direction. These EVCS spaces shall also comply with at least one of the following:
a. The EVCS space shall be located adjacent to an accessible parking space meeting the requirements of the California Building Code, Chapter 11A, to allow use of the EV charger from the accessible parking space.
b. The EVCS space shall be located on an accessible route, as defined in the California Building Code, Chapter 2, to the building.

Exception: Electric vehicle charging stations designed and constructed in compliance with the California Building Code, Chapter 11B, are not required to comply with Section 4.106.4.2.2.1.1.

4.106.4.2.2.1.2 Accessible electric vehicle charging station spaces.

In addition to the requirements in Section 4.106.4.2.2.1.1, all EV chargers, where installed, shall comply with the accessibility provisions for EV chargers in the California Building Code, Chapter 11B. EV ready spaces and EVCS in multifamily developments shall comply with California Building Code, Chapter 11A, Section 1109A.

4.106.4.2.3 Reserved.

4.106.4.2.4 Reserved.

4.106.4.2.5 Electric vehicle ready space signage.

Electric vehicle ready spaces shall be identified by signage or pavement markings, in compliance with Caltrans Traffic Operations Policy Directive 13-01 (Zero Emission Vehicle Signs and Pavement Markings) or its successor(s).

4.106.4.3 Electric vehicle charging for additions and alterations of parking facilities serving existing multi-family buildings.

Where new parking facilities are added, or electrical systems or lighting of existing parking facilities are added or altered and the work requires a building permit, ten (10) percent of the total number of parking spaces added or altered shall be EV capable spaces to support future Level 2 electric vehicle supply equipment. The service panel or subpanel circuit directory shall identify the overcurrent protective device space(s) reserved for future EV charging purposes as “EV CAPABLE.”
Notes:

1.Construction documents are intended to demonstrate the project’s capability and capacity for facilitating future EV charging.

2.There is no requirement for EV spaces to be constructed or available until EV chargers are installed for use.

SECTION 4.501 GENERAL

4.501.1 Scope
The provisions of this chapter shall outline means of reducing the quality of air contaminants that are odorous, irritating and/or harmful to the comfort and well being of a building's installers, occupants and neighbors.

SECTION 4.502 DEFINITIONS

5.102.1 DEFINITIONS
The following terms are defined in Chapter 2 (and are included here for reference) AGRIFIBER PRODUCTS. Agrifiber products include wheatboard, strawboard, panel substrates and door cores, not including furniture, fixtures and equipment (FF&E) not considered base building elements.

COMPOSITE WOOD PRODUCTS. Composite wood products include hardwood plywood, particleboard and medium density fiberboard. "Composite wood products" does not include hardboard, structural plywood, structural panels, structural composite lumber, oriented strand board, glued laminated timber, prefabricated wood I-joists or finger-jointed lumber, all as specified in California Code of regulations (CCR), title 17, Section 93120.1.

DIRECT-VENT APPLIANCE. A fuel-burning appliance with a sealed combustion system that draws all air for combustion from the outside atmosphere and discharges all flue gases to the outside atmosphere. Y N/A RESPON. Y N/A Y N/A Y N/A PARTY RESPON. PARTY RESPON. PARTY RESPON. PARTY 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE RESIDENTIAL MANDATORY MEASURES, SHEET 1 (July 2024 Supplement) Y = YES N/A = NOT APPLICABLE RESPON. PARTY = RESPONSIBLE PARTY (ie: ARCHITECT, ENGINEER, OWNER, CONTRACTOR, INSPECTOR ETC.)

4.201 GENERAL

4.201.1 SCOPE. For the purposes of mandatory energy efficiency standards in this code, the California Energy Commission will continue to adopt mandatory standards.

DIVISION 4.2 ENERGY EFFICIENCY
TABLE H-2

STANDARDS FOR COMMERCIAL PRE-RINSE SPRAY
VALUES MANUFACTURED ON OR AFTER JANUARY 28, 2019

PRODUCT CLASS
[spray force in ounce force (ozf)] MAXIMUM FLOW RATE (gpm) Product Class 1 (≤ 1.00
Product Class 2 (> 5.0 ozf and ≤ 1.20
Product Class 3 (> 8.0 ozf) 1.28
269
Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

CALGREEN RESIDENTIAL CHECKLIST
G-0.3
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026

REVISIONS
NO. DATE DESCRIPTION
MAXIMUM INCREMENTAL REACTIVITY (MIR). The maximum change in weight of ozone formed by adding a compound to the "Base Reactive Organic Gas (ROG) Mixture" per weight of compound added, expressed to hundredths of a gram (g O³/g ROC).

Note: MIR values for individual compounds and hydrocarbon solvents are specified in CCR, Title 17, Sections 94700 and 94701.

MOISTURE CONTENT. The weight of the water in wood expressed in percentage of the weight of the oven-dry wood.

PRODUCT-WEIGHTED MIR (PWMIR). The sum of all weighted-MIR for all ingredients in a product subject to this article. The PWMIR is the total product reactivity expressed to hundredths of a gram of ozone formed per gram of product (excluding container and packaging).

Note: PWMIR is calculated according to equations found in CCR, Title 17, Section 94521 (a).

REACTIVE ORGANIC COMPOUND (ROC). Any compound that has the potential, once emitted, to contribute to ozone formation in the troposphere.

VOC. A volatile organic compound (VOC) broadly defined as a chemical compound based on carbon chains or rings with vapor pressures greater than 0.1 millimeters of mercury at room temperature. These compounds typically contain hydrogen and may contain oxygen, nitrogen and other elements. See CCR Title 17, Section 94508(a).

4.503 FIREPLACES

4.503.1 GENERAL. Any installed gas fireplace shall be a direct-vent sealed-combustion type. Any installed woodstove or pellet stove shall comply with U.S. EPA New Source Performance Standards (NSPS) emission limits as applicable, and shall have a permanent label indicating they are certified to meet the emission limits. Woodstoves, pellet stoves and fireplaces shall also comply with applicable local ordinances.

4.504 POLLUTANT CONTROL

4.504.1 COVERING OF DUCT OPENINGS & PROTECTION OF MECHANICAL EQUIPMENT DURING CONSTRUCTION. At the time of rough installation, during storage on the construction site and until final startup of the heating, cooling and ventilating equipment, all duct and other related air distribution component openings shall be covered with tape, plastic, sheet metal or other methods acceptable to the enforcing agency to reduce the amount of water, dust or debris which may enter the system.

4.504.2 FINISH MATERIAL POLLUTANT CONTROL. Finish materials shall comply with this section.

4.504.2.1 Adhesives, Sealants and Caulks. Adhesives, sealant and caulks used on the project shall meet the requirements of the following standards unless more stringent local or regional air pollution or air quality management district rules apply:

1. Adhesives, adhesive bonding primers, adhesive primers, sealants, sealant primers and caulks shall comply with local or regional air pollution control or air quality management district rules where applicable or SCAQMD Rule 1168 VOC limits, as shown in Table 4.504.1 or 4.504.2, as applicable.

Such products also shall comply with the Rule 1168 prohibition on the use of certain toxic compounds (chloroform, ethylene dichloride, methylene chloride, perchloroethylene and tricloroethylene), except for aerosol products, as specified in Subsection 2 below.

2. Aerosol adhesives, and smaller unit sizes of adhesives, and sealant or caulking compounds (in units of product, less packaging, which do not weigh more than 1 pound and do not consist of more than 16 fluid ounces) shall comply with statewide VOC standards and other requirements, including prohibitions on use of certain toxic compounds, of California Code of Regulations, Title 17, commencing with section 94507.

4.504.2.2 Paints and Coatings. Architectural paints and coatings shall comply with VOC limits in Table 1 of the ARB Architectural Suggested Control Measure, as shown in Table 4.504.3, unless more stringent local limits apply. The VOC content limit for coatings that do not meet the definitions for the specialty coatings categories listed in Table 4.504.3 shall be determined by classifying the coating as a Flat, Nonflat or Nonflat-High Gloss coating, based on its gloss, as defined in subsections 4.21, 4.36, and 4.37 of the 2007 California Air Resources Board, Suggested Control Measure, and the corresponding Flat, Nonflat or Nonflat-High Gloss VOC limit in Table 4.504.3 shall apply.

4.504.2.3 Aerosol Paints and Coatings. Aerosol paints and coatings shall meet the Product-weighted MIR Limits for ROC in Section 94522(a)(2) and other requirements, including prohibitions on use of certain toxic compounds and ozone depleting substances, in Sections 94522(e)(1) and (f)(1) of California Code of Regulations, Title 17, commencing with Section 94520; and in areas under the jurisdiction of the Bay Area Air Quality Management District additionally comply with the percent VOC by weight of product limits of Regulation 8, Rule 49.

4.504.2.4 Verification. Verification of compliance with this section shall be provided at the request of the enforcing agency. Documentation may include, but is not limited to, the following:

1. Manufacturer's product specification.

2. Field verification of on-site product containers.

CHAPTER 7

INSTALLER & SPECIAL INSPECTOR QUALIFICATIONS
702 QUALIFICATIONS
702.1 INSTALLER TRAINING. HVAC system installers shall be trained and certified in the proper installation of HVAC systems including ducts and equipment by a nationally or regionally recognized training or certification program. Uncertified persons may perform HVAC installations when under the direct supervision and responsibility of a person trained and certified to install HVAC systems or contractor licensed to install HVAC systems.

Examples of acceptable HVAC training and certification programs include but are not limited to the following:

1. State certified apprenticeship programs.

2. Public utility training programs.

3. Training programs sponsored by trade, labor or statewide energy consulting or verification organizations.

4. Programs sponsored by manufacturing organizations.

5. Other programs acceptable to the enforcing agency.
702.2 SPECIAL INSPECTION [HCD]. When required by the enforcing agency, the owner or the responsible entity acting as the owner's agent shall employ one or more special inspectors to provide inspection or other duties necessary to substantiate compliance with this code. Special inspectors shall demonstrate competence to the satisfaction of the enforcing agency for the particular type of inspection or task to be performed. In addition to other certifications or qualifications acceptable to the enforcing agency, the following certifications or education may be considered by the enforcing agency when evaluating the qualifications of a special inspector:

1. Certification by a national or regional green building program or standard publisher.

2. Certification by a statewide energy consulting or verification organization, such as HERS raters, building performance contractors, and home energy auditors.

3. Successful completion of a third party apprentice training program in the appropriate trade.

4. Other programs acceptable to the enforcing agency.

Notes:

1. Special inspectors shall be independent entities with no financial interest in the materials or the project they are inspecting for compliance with this code.

2. HERS raters are special inspectors certified by the California Energy Commission (CEC) to rate homes in California according to the Home Energy Rating System (HERS). [BSC] When required by the enforcing agency, the owner or the responsible entity acting as the owner's agent shall employ one or more special inspectors to provide inspection or other duties necessary to substantiate compliance with this code. Special inspectors shall demonstrate competence to the satisfaction of the enforcing agency for the particular type of inspection or task to be performed. In addition, the special inspector shall have a certification from a recognized state, national or international association, as determined by the local agency. The area of certification shall be closely related to the primary job function, as determined by the local agency.

Note: Special inspectors shall be independent entities with no financial interest in the materials or the project they are inspecting for compliance with this code. 703 VERIFICATIONS
703.1 DOCUMENTATION. Documentation used to show compliance with this code shall include but is not limited to, construction documents, plans, specifications, builder or installer certification, inspection reports, or other methods acceptable to the enforcing agency which demonstrate substantial conformance. When specific documentation or special inspection is necessary to verify compliance, that method of compliance will be specified in the appropriate section or identified applicable checklist.

4.505 INTERIOR MOISTURE CONTROL

4.505.1 General. Buildings shall meet or exceed the provisions of the California Building Standards Code. 4.505.2 CONCRETE SLAB FOUNDATIONS. Concrete slab foundations required to have a vapor retarder by California Building Code, Chapter 19, or concrete slab-on-ground floors required to have a vapor retarder by the California Residential Code, Chapter 5, shall also comply with this section.

4.505.2.1 Capillary break. A capillary break shall be installed in compliance with at least one of the following:

1. A 4-inch (101.6 mm) thick base of 1/2 inch (12.7mm) or larger clean aggregate shall be provided with a vapor barrier in direct contact with concrete and a concrete mix design, which will address bleeding, shrinkage, and curling, shall be used. For additional information, see American Concrete Institute, ACI 302.2R-06.

2. Other equivalent methods approved by the enforcing agency.

3. A slab design specified by a licensed design professional.

4.505.3 MOISTURE CONTENT OF BUILDING MATERIALS. Building materials with visible signs of water damage shall not be installed. Wall and floor framing shall not be enclosed when the framing members exceed 19 percent moisture content. Moisture content shall be verified in compliance with the following:

1. Moisture content shall be determined with either a probe-type or contact-type moisture meter.Equivalent moisture verification methods may be approved by the enforcing agency and shall satisfy requirements found in Section 101.8 of this code.

2. Moisture readings shall be taken at a point 2 feet (610 mm) to 4 feet (1219 mm) from the grade stamped end of each piece verified.

3. At least three random moisture readings shall be performed on wall and floor framing with documentation acceptable to the enforcing agency provided at the time of approval to enclose the wall and floor framing.

Insulation products which are visibly wet or have a high moisture content shall be replaced or allowed to dry prior to enclosure in wall or floor cavities. Wet-applied insulation products shall follow the manufacturers' drying recommendations prior to enclosure.

4.506 INDOOR AIR QUALITY AND EXHAUST

4.506.1 Bathroom exhaust fans. Each bathroom shall be mechanically ventilated and shall comply with the following:

1. Fans shall be ENERGY STAR compliant and be ducted to terminate outside the building.

2. Unless functioning as a component of a whole house ventilation system, fans must be controlled by a humidity control.
a. Humidity controls shall be capable of adjustment between a relative humidity range less than or equal to 50% to a maximum of 80%. A humidity control may utilize manual or automatic means of adjustment.
b. A humidity control may be a separate component to the exhaust fan and is not required to be integral (i.e., built-in)
Notes:

1. For the purposes of this section, a bathroom is a room which contains a bathtub, shower or tub/shower combination.

2. Lighting integral to bathroom exhaust fans shall comply with the California Energy Code.

4.507 ENVIRONMENTAL COMFORT

4.507.2 HEATING AND AIR-CONDITIONING SYSTEM DESIGN. Heating and air conditioning systems shall be sized, designed and have their equipment selected using the following methods:

1. The heat loss and heat gain is established according to ANSI/ACCA 2 Manual J - 2011 (Residential Load Calculation), ASHRAE handbooks or other equivalent design software or methods.

2. Duct systems are sized according to ANSI/ACCA 1 Manual D - 2014 (Residential Duct Systems), ASHRAE handbooks or other equivalent design software or methods.

3. Select heating and cooling equipment according to ANSI/ACCA 3 Manual S - 2014 (Residential Equipment Selection), or other equivalent design software or methods.

Exception: Use of alternate design temperatures necessary to ensure the system functions are acceptable.

TABLE 4.504.1 - ADHESIVE VOC LIMIT1,2
(Less Water and Less Exempt Compounds in Grams per Liter)

ARCHITECTURAL APPLICATIONS VOC LIMIT
INDOOR CARPET ADHESIVES 50
CARPET PAD ADHESIVES 50
OUTDOOR CARPET ADHESIVES 150
WOOD FLOORING ADHESIVES 100
RUBBER FLOOR ADHESIVES 60
SUBFLOOR ADHESIVES 50
CERAMIC TILE ADHESIVES 65
VCT & ASPHALT TILE ADHESIVES 50
DRYWALL & PANEL ADHESIVES 50
COVE BASE ADHESIVES 50
MULTIPURPOSE CONSTRUCTION ADHESIVE 70
STRUCTURAL GLAZING ADHESIVES 100
SINGLE-PLY ROOF MEMBRANE ADHESIVES 250
OTHER ADHESIVES NOT LISTED 50

SPECIALTY APPLICATIONS
PVC WELDING 510
CPVC WELDING 490
ABS WELDING 325
PLASTIC CEMENT WELDING 250
ADHESIVE PRIMER FOR PLASTIC 550
CONTACT ADHESIVE 80
SPECIAL PURPOSE CONTACT ADHESIVE 250
STRUCTURAL WOOD MEMBER ADHESIVE 140
TOP & TRIM ADHESIVE 250

SUBSTRATE SPECIFIC APPLICATIONS
METAL TO METAL 30
PLASTIC FOAMS 50
POROUS MATERIAL (EXCEPT WOOD) 50
WOOD 30
FIBERGLASS 80

1. IF AN ADHESIVE IS USED TO BOND DISSIMILAR SUBSTRATES TOGETHER, THE ADHESIVE WITH THE HIGHEST VOC CONTENT SHALL BE ALLOWED.

2. FOR ADDITIONAL INFORMATION REGARDING METHODS TO MEASURE

THE VOC CONTENT SPECIFIED IN THIS TABLE, SEE SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT RULE 1168.

TABLE 4.504.2 - SEALANT VOC LIMIT
(Less Water and Less Exempt Compounds in Grams per Liter)

SEALANTS VOC LIMIT
ARCHITECTURAL 250
MARINE DECK 760
NONMEMBRANE ROOF 300
ROADWAY 250
SINGLE-PLY ROOF MEMBRANE 450
OTHER 420

SEALANT PRIMERS

ARCHITECTURAL
NON-POROUS 250
POROUS 775
MODIFIED BITUMINOUS 500
MARINE DECK 760
OTHER 750
TABLE 4.504.5 - FORMALDEHYDE LIMITS1 MAXIMUM FORMALDEHYDE EMISSIONS IN PARTS PER MILLION

PRODUCT CURRENT LIMIT
HARDWOOD PLYWOOD VENEER CORE 0.05
HARDWOOD PLYWOOD COMPOSITE CORE 0.05
PARTICLE BOARD 0.09
MEDIUM DENSITY FIBERBOARD 0.11
THIN MEDIUM DENSITY FIBERBOARD2 0.13

1. VALUES IN THIS TABLE ARE DERIVED FROM THOSE SPECIFIED BY THE CALIF. AIR RESOURCES BOARD, AIR TOXICS CONTROL

MEASURE FOR COMPOSITE WOOD AS TESTED IN ACCORDANCE
WITH ASTM E 1333. FOR ADDITIONAL INFORMATION, SEE CALIF.

CODE OF REGULATIONS, TITLE 17, SECTIONS 93120 THROUGH
93120.12.

2. THIN MEDIUM DENSITY FIBERBOARD HAS A MAXIMUM
THICKNESS OF 5/16" (8 MM).

TABLE 4.504.3 - VOC CONTENT LIMITS FOR
ARCHITECTURAL COATINGS2,3

GRAMS OF VOC PER LITER OF COATING, LESS WATER & LESS EXEMPT

COMPOUNDS

COATING CATEGORY VOC LIMIT
FLAT COATINGS 50
NON-FLAT COATINGS 100
NONFLAT-HIGH GLOSS COATINGS 150

SPECIALTY COATINGS
ALUMINUM ROOF COATINGS 400
BASEMENT SPECIALTY COATINGS 400
BITUMINOUS ROOF COATINGS 50
BITUMINOUS ROOF PRIMERS 350
BOND BREAKERS 350
CONCRETE CURING COMPOUNDS 350
CONCRETE/MASONRY SEALERS 100
DRIVEWAY SEALERS 50
DRY FOG COATINGS 150
FAUX FINISHING COATINGS 350
FIRE RESISTIVE COATINGS 350
FLOOR COATINGS 100
FORM-RELEASE COMPOUNDS 250
GRAPHIC ARTS COATINGS (SIGN PAINTS) 500
HIGH TEMPERATURE COATINGS 420
INDUSTRIAL MAINTENANCE COATINGS 250
LOW SOLIDS COATINGS1 120
MAGNESITE CEMENT COATINGS 450
MASTIC TEXTURE COATINGS 100
METALLIC PIGMENTED COATINGS 500
MULTICOLOR COATINGS 250
PRETREATMENT WASH PRIMERS 420
PRIMERS, SEALERS, & UNDERCOATERS 100
REACTIVE PENETRATING SEALERS 350
RECYCLED COATINGS 250
ROOF COATINGS 50
RUST PREVENTATIVE COATINGS 250

SHELLACS
CLEAR 730
OPAQUE 550

SPECIALTY PRIMERS, SEALERS &
UNDERCOATERS 100
STAINS 250
STONE CONSOLIDANTS 450
SWIMMING POOL COATINGS 340
TRAFFIC MARKING COATINGS 100
TUB & TILE REFINISH COATINGS 420
WATERPROOFING MEMBRANES 250
WOOD COATINGS 275
WOOD PRESERVATIVES 350
ZINC-RICH PRIMERS 340

1. GRAMS OF VOC PER LITER OF COATING, INCLUDING WATER &

EXEMPT COMPOUNDS

2. THE SPECIFIED LIMITS REMAIN IN EFFECT UNLESS REVISED LIMITS ARE LISTED IN SUBSEQUENT COLUMNS IN THE TABLE.

3. VALUES IN THIS TABLE ARE DERIVED FROM THOSE SPECIFIED BY

THE CALIFORNIA AIR RESOURCES BOARD, ARCHITECTURAL COATINGS SUGGESTED CONTROL MEASURE, FEB. 1, 2008. MORE INFORMATION IS AVAILABLE FROM THE AIR RESOURCES BOARD.

DIVISION 4.5 ENVIRONMENTAL QUALITY (continued)

4.504.3 CARPET SYSTEMS. All carpet installed in the building interior shall meet the requirements of the California Department of Public Health, "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers," Version 1.2, January 2017 (Emission testing method for California Specification 01350)
See California Department of Public Health's website for certification programs and testing labs. https://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx.

4.504.3.1 Carpet cushion. All carpet cushion installed in the building interior shall meet the requirements of the California Department of Public Health, "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers," Version 1.2, January 2017 (Emission testing method for California Specification 01350) See California Department of Public Health's website for certification programs and testing labs. https://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx.

4.504.3.2 Carpet adhesive. All carpet adhesive shall meet the requirements of Table 4.504.1.

4.504.4 RESILIENT FLOORING SYSTEMS. Where resilient flooring is installed , at least 80% of floor area receiving resilient flooring shall meet the requirements of the California Department of Public Health, "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers," Version 1.2, January 2017 (Emission testing method for California Specification 01350) See California Department of Public Health's website for certification programs and testing labs. hhtps://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx.

4.504.5 COMPOSITE WOOD PRODUCTS. Hardwood plywood, particleboard and medium density fiberboard composite wood products used on the interior or exterior of the buildings shall meet the requirements for formaldehyde as specified in ARB's Air Toxics Control Measure for Composite Wood (17 CCR 93120 et seq.), by or before the dates specified in those sections, as shown in Table 4.504.5

4.504.5.1 Documentation. Verification of compliance with this section shall be provided as requested by the enforcing agency. Documentation shall include at least one of the following:

1. Product certifications and specifications.

2. Chain of custody certifications.

3. Product labeled and invoiced as meeting the Composite Wood Products regulation (see CCR, Title 17, Section 93120, et seq.).

4. Exterior grade products marked as meeting the PS-1 or PS-2 standards of the Engineered Wood Association, the Australian AS/NZS 2269, European 636 3S standards, and Canadian CSA 0121, CSA 0151, CSA 0153 and CSA 0325 standards.

5. Other methods acceptable to the enforcing agency. Y N/A RESPON. Y N/A Y N/A Y N/A PARTY RESPON. PARTY RESPON. PARTY RESPON. PARTY 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE RESIDENTIAL MANDATORY MEASURES, SHEET 2 (July 2024 Supplement) Y = YES N/A = NOT APPLICABLE RESPON. PARTY = RESPONSIBLE PARTY (ie: ARCHITECT, ENGINEER, OWNER, CONTRACTOR, INSPECTOR ETC.)
270

EXISTING MAIN DWELLING

STREET NAME

ADDRESS

FOOTPRINT AREA (SF)
F.F. ELEV

XXX' (DISTANCE)
N XX°XX'XX" W

XXX' (DISTANCE)
S XX°XX'XX" E

XXX' (DISTANCE)
N XX°XX'XX" W

XXX' (DISTANCE)
S XX°XX'XX" E

EXISTING SIDEWALK
CL
XX' - XX" XX' - XX" XX' - XX"
XX' - XX" XX' - XX" XX' - XX"
XX' - XX"

SETBACK
XX' - XX"

SETBACK

SETBACK
XX' - XX"

SETBACK
XX' - XX"
X

PROPOSED ADU

EXAMPLE

FOOTPRINT AREA (SF)
F.F. ELEV
XX' - XX"

ADU LENGTH
XX' - XX" XX' - XX"
XX' - XX"

ADU WIDTH
X' - X" XX' - XX"

INDICATE ROOF

OVERHANGS AND

PORCHES

EXISTING DRIVEWAY
SLOPE (2% MIN, 12% MAX)

SLOPE DN

EXISTING
SHED
XX' - XX"

XXXXXXXXXXX

EXISTING

RETAINING WALL

PROPERTY
LINE, TYP.

SETBACK
LINE, TYP.

XXX
XXX
PLAN
NORTH
N

EXISTING FENCE
XX' - XX"

EASEMENT
XX' - XX"
0 SCALE:
5' - 0" 10' - 0" 20' - 0"
1" = 10' - 0"

EXISTING

HARDSCAPE PATIO

EXISTING
CURB
XX' - XX"
G G G
G
G

GE E E E E
W

SS SS SS SS SS SS SS SS SS
E

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

1. 2.

3. 4.

5. 6.

7. 8.

9. REFER TO GENERAL NOTES SHEET A1.0 FOR ADDITIONAL
REQUIREMENTS.

CALL BEFORE YOU DIG! CONTACT UNDERGROUND SERVICE

ALERT OF CALIFORNIA AT LEAST TWO WORKING DAYS PRIOR TO
EXCAVATING, NOT INCLUDING THE DATE OF NOTIFICATION.

LOT SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
FOUNDATION WALLS. THE GRADE SHALL FALL NOT FEWER THAN
6 IN WITHIN THE FIRST 10 FT (5% MIN).

WHERE LOT LINES, WALLS, SLOPES, OR OTHER PHYSICAL
BARRIER PROHIBIT 6 IN OF FALL WITHIN 10 FT, DRAINS OR

SWALES SHALL BE CONSTRUCTED TO ENSURE DRAINAGE AWAY
FROM THE STRUCTURE.

IMPERVIOUS SURFACES WITHIN 10 FT OF THE BUILDING
FOUNDATION SHALL BE SLOPED NOT LESS THAN 2% AWAY FROM
THE BUILDING.

DWELLING UNITS 150 FT OR MORE FROM A PUBLIC RIGHT-OFWAY SHALL BE REQUIRED TO PROVIDE "ALL-WEATHER ACCESS"

FOR EMERGENCY VEHICLES AS REQUIRED BY THE RIVERSIDE
COUNTY FIRE DEPARTMENT.

EACH HORIZONTAL DRAINAGE PIPE SHALL BE PROVIDED WITH A

CLEAN OUT AT ITS UPPER TERMINAL, AND EACH RUN OF PIPING THAT IS MORE THAN100 FEET IN TOTAL DEVELOPED LENGTH
SHALL BE PROVIDED WITH A CLEAN OUT FOR EACH 100 FEET, OR FRACTION THEREOF, IN LENGTH OF SUCH PIPING. AN

ADDITIONAL CLEANOUT SHALL BE PROVIDED IN A DRAINAGE LINE

FOR EACH AGGREGATE HORIZONTAL CHANGE IN DIRECTION
EXCEEDING 135 DEGREES. [CPC 2022 SECTION 707.4]

PLUMBING FIXTURES AND FITTINGS INSTALLED IN RESIDENTIAL

BUILDINGS SHALL COMPLY WITH THE PRESCRIPTIVE
REQUIREMENTS OF SECTIONS 4.303.1.1 - 4.303.1.4.4 OF CRC 2022.

PLUMBING FIXTURES AND FITTINGS REQUIRED IN SECTION

4.303.1 SHALL BE INSTALLED IN ACCORDANCE WITH CPC 2022
AND SHALL MEET THE APPLICABLE REFERENCE STANDARDS.

SITE PLAN GENERAL SHEET NOTES

SITE PLAN CHECKLIST REQUIREMENTS

APPLICANT NAME, ADDRESS, AND CONTACT INFORMATION

PROPERTY OWNER NAME, ADDRESS, AND CONTACT

INFORMATION IF DIFFERENT FROM APPLICANT

ACCESSOR'S PARCEL NUMBER OF PROPERTY WHERE THE ADU

IS PROPOSED

PROPERTY LINE METES AND BOUNDS

FOOTPRINT AND AREA OF EXISTING AND PROPOSED BUILDINGS

AND STRUCTURES

BUILDING SEPARATION DIMENSIONS BETWEEN THE PROPOSED

ADU AND ANY EXISTING BUILDING AND STRUCTURES

LOCATION AND HEIGHT OF ALL FENCES AND RETAINING WALLS

INDICATE AND DIMENSION ALL REQUIRED AND PROPOSED

SETBACKS AND LABEL YARDS

PROVIDE LOT AREA

LOT COVERAGE CALCULATION

LOCATION AND SIZE OF EXISTING AND NEW UTILITIES

INCLUDING LATERAL LINES, WELLS, SEPTIC TANKS, LEACH
LINES, EXISTING SEEPAGE PITS, AND DRAINAGE STRUCTURES.

PROVIDE LOCATION OF SEWER CLEANOUTS.

IDENTIFY THE PIPING MATERIALS FOR EACH PLUMBING
SYSTEM.

LOCATION AND DIMENSIONS OF ALL EASEMENTS

INDICATE ALL METHODS OF CIRCULATION INCLUDING

SIDEWALKS, STREETS, DRIVEWAYS, OFF-STREET PARKING,
PATHWAYS, AND ANY HARDSCAPING.

LOCATION OF EXISTING AND NEW METERS

INDICATE SUBPANEL SIZE AND PROVIDE AN ELECTRICAL LOAD

CALCULATION FOR THE EXISTING PANEL TO VERIFY THE

CAPCITY OF THE EXISTING PANEL IS SUFFICIENT TO CARRY
THE LOAD OF THE EXISTING LOAD AND NEW SUBPANEL.

SITE CONTOURS, SPOT ELEVATIONS AT ALL STAIRS, RAMPS &

LANDINGS, AND FINISH FLOOR ELEVATIONS

LOCATION OF PROPOSED VEGETATION

LEGEND OF SYMBOLS, LINE TYPES, AND ABBREVIATIONS

DRAWING SCALE

NORTH ARROW
LEGEND

CONCRETE PAVING

LANDSCAPE AREA

PROPERTY LINE

SETBACK

EXISTING CONTOURS

NEW CONTOURS

RETAINING WALL

XX FENCE LINE

EASEMENT

ELECTRICAL UTILITY LINE

GAS UTILITY LINE

WATER UTILITY LINE

SEWER LINE

SPOT ELEVATION
EGW

XXX' SS
XXX'

ELECTRICAL PANEL
(SIZE)

GAS METER

W WATER METER EG
Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

ARCHITECTURAL - SITE PLAN
AS-1.1
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026
SCALE: 1" = 10'-0"

SAMPLE SITE PLAN
1 REVISIONS
NO. DATE DESCRIPTION
271

ARCHITECTURAL MATERIALS LEGEND

CONCRETE
EARTH

BATT INSULATION

ROOF, TAPERED, CAVITY OR RIGID INSULATION

PLYWOOD

HORIZONTAL FIBER CEMENT SIDING

BOARD AND BATTEN SIDING

STONE VENEER
STUCCO

TILE ROOF

STANDING SEAM METAL ROOF

SHINGLE ROOF

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

1. 2.

3. 4.

5. 6.

7. 8.

9. 10.

11. 12.

13. 14.

15. 16.

17. 18.

19. CONSTRUCTION AND CONSTRUCTION DOCUMENTATION MUST COMPLY WITH APPLICABLE CODES AND ORDINANCES, LAWS AND SAFETY ORDERS AS DIRECTED BY LOCAL JURISDICTION.

APPLICATIONS FOR WHICH NO PERMIT IS ISSUED WITHIN 180 DAYS FOLLOWING THE DATE OF APPLICATION SHALL AUTOMATICALLY EXPIRE. [CRC R105.3.2]

EVERY PERMIT ISSUED SHALL BECOME INVALID UNLESS THE WORK AUTHORIZED COMMENCES WITHIN 180 DAYS AFTER ITS ISSUANCE OR IF THE WORK AUTHORIZED IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS. A SUCCESSFUL INSPECTION MUST BE OBTAINED WITHIN 180 DAYS. [CRC R105.5]
ALL DIMENSIONS ARE IN FEET / INCHES UNLESS NOTED OTHERWISE.

DO NOT SCALE DIMENSIONS FROM DRAWINGS. THE CONTRACTOR SHALL NOTIFY THE OWNER IF A DISCREPANCY IS FOUND.

ALL DIMENSIONS ARE TO FACE OF STUD UNLESS NOTED OTHERWISE.

ALL NON-DIMENSIONED DOOR LOCATIONS SHALL BE LOCATED 3 ½ ” FROM THE ADJACENT WALL TO THE HINGE SIDE OF THE DOOR OPENING.

DETAILS SHOWN ON DRAWINGS ARE TYPICAL FOR ALL SIMILAR CONDITIONS.

DETAILS ARE INTENDED TO SHOW METHOD AND MANNER OF ACCOMPLISHING WORK. MINOR

MODIFICATIONS MAY BE REQUIRED TO SUIT THE JOB DIMENSIONS OR CONDITIONS AND ARE TO BE REVIEWED AND APPROVED BY THE CTIY OF WILDOMAR.

VERIFY ALL DIMENSIONS IN THE FIELD AND COORDINATE DIMENSIONS SHOWN ON THE CONTRACT DRAWINGS WITH FABRICATION AND FIELD CONDITIONS. STAKE OUT STRUCTURE FOR OWNER ’S APPROVAL PRIOR TO STARTING ANY WORK.

CONTRACTOR SHALL PROTECT ALL MONUMENTS, IRON PINS, AND PROPERTY CORNERS DURING CONSTRUCTION.

CONTRACTOR SHALL PREPARE ALL WALLS AND PARTITIONS AS REQUIRED BY THE FINISH MANUFACTURER TO RECEIVE THE FINISHES SPECIFIED.

CONTRACTOR SHALL CLEAN, PATCH AND REPAIR ALL SURFACES DAMAGED BY DEMOLITION, ALTERATION OR INSTALLATION OF THE WORK.

CONTRACTOR AND SUBCONTRACTOR SHALL ALL BE LICENSED TO PERFORM THEIR REQUESTED DUTIES AS REQUIRED IN ACCORDANCE WITH LOCAL STANDARDS.

PRINCIPAL OPENINGS IN THE STRUCTURE ARE SHOWN ON THESE DRAWINGS. THE GENERAL

CONTRACTOR SHALL EXAMINE THE ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR REQUIRED OPENINGS. GENERAL CONTRACTOR SHALL VERIFY SIZE AND LOCATION OF ALL OPENINGS WITH ALL SUB-CONTRACTORS PRIOR TO CONSTRUCTION.

APPLICANT IS RESPONSIBLE FOR PROVIDING SITE PLAN TO THE CITY FOR REVIEW AND APPROVAL.

PHOTOVOLTAIC SYSTEM (PV) SHALL BE SUBMITTED UNDER A SEPARATE PERMIT APPLICATION.

AN ENCROACHMENT PERMIT WILL BE REQUIRED FOR ANY CONSTRUCTION ACTIVITY WITHIN A PUBLIC STREET RIGHT-OF-WAY.

PROVIDE CONSTRUCTION WASTE MANAGEMENT PLAN PER 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE.

GENERAL NOTES

1. 2.

3. 4.

5. 6.

7. 1.

2. 3.

4. 5.

8. 9.

10. 11.

1. 2.

12. 13.

14. 15.

DIFFUSERS AND GRILLS TO MATCH COLOR OF SURFACE AT WHICH THEY ARE MOUNTED, UNLESS OTHERWISE NOTED.

PLUMBING, ELECTRICAL, AND SPRINKLER EQUIPMENT, IF REQUIRED, TO BE PAINTED TO MATCH COLOR OF ADJACENT SURFACE.

FLOOR FINISH TO CONTINUE UNDER MILLWORK WHERE FLOOR IS VISIBLE.

SILICONE SEALANT AT GLAZING TO BE CLEAR, UNLESS OTHERWISE NOTED.

TRANSITION OF FLOOR MATERIALS OCCURRING IN OPENINGS WITH DOORS TO BE LOCATED UNDER THE CENTER OF THE DOOR IN THE CLOSED POSITION. TRANSITION OF FLOOR MATERIAL OCCURRING WITH NO DOOR TO BE LOCATED TO ALIGN WITH THE FACE OF THE PARTITION, U.O.N ALL WALL AND CEILING FINISHES SHALL COMPLY WITH CRC 803.13 FOR MAXIMUM FLAME SPREAD AND SMOKE DENSITY. ALL FINISHES MUST COMPLY WITH ALL APPLICABLE FIRE, LIFE SAFETY, AND BUILDING CODES.

PROVIDE REINFORCEMENT FOR GRAB BARS IN AT LEAST ONE BATHROOM [CRC SECTION R327.1.1, AGING-IN-PLACE DESIGN AND FALL PREVENTION]

REINFORCEMENT SHALL BE SOLID LUMBER OR OTHER CONSTRUCTION MATERIALS APPROVED BY THE ENFORCING AGENCY.

REINFORCEMENT SHALL NOT BE LESS THAN 2 BY 8 INCH NOMINAL LUMBER OR OTHER MATERIAL PROVIDING EQUAL HEIGHT AND LOAD CAPACITY. REINFORCEMENT SHALL BE LOCATED BETWEEN 32 INCHES AND 39 ¼” INCHES ABOVE THE FINISHED FLOOR FLUSH WITH THE WALL FRAMING.

WATER CLOSET REINFORCEMENT SHALL BE INSTALLED ON BOTH SIDE WALLS OF THE FIXTURE, OR ONE SIDE WALL AND THE BACK WALL.

SHOWER REINFORCEMENT SHALL BE CONTINUOUS WHERE WALL FRAMING IS PROVIDED.

BATHTUB AND COMBINATION BATHTUB/SHOWER REINFORCEMENT SHALL BE CONTINUOUS ON EACH END OF THE BATHTUB AND THE BACK WALL. ADDITIONALLY, BACK WALL REINFORCEMENT

FOR A LOWER GRAB BAR SHALL BE PROVIDED WITH THE BOTTOM EDGE LOCATED NO MORE THAN 6 INCHES ABOVE THE BATHTUB RIM.

PROVIDE ADEQUATE BLOCKING IN WALLS FOR CABINETS AND OTHER WALL MOUNTED ACCESSORIES INCLUDING BUT NOT LIMITED TO SHELVING AND BATHROOM FIXTURES.

PROVIDE REQUIRED CLEARANCES FOR BATHROOM FIXTURES, INCLUDING WATER CLOSETS AND SHOWER COMPARTMENTS AS ILLUSTRATED ON SHEET A5.1 [CPC 402.5 AND CPC 408]

SEE DETAILS FOR LOCATIONS OF MISCELLANEOUS IRON AND STEEL WORK, INCLUDING BUT NOT LIMITED TO ASSORTED CLIPS, BRACKETS, ANGLES, STRAPS, AND POST ANCHORS. FURNISH AND

INSTALL ALL SUCH ITEMS NECESSARY TO PROVIDE A COMPLETE INSTALLATION, WHETHER OR NOT SPECIFICALLY DETAILED OR NOTED ON THE DRAWINGS. ALL EXTERIOR METAL AND HARDWARE IS TO BE GALVANIZED. STEEL IS TO COMPLY WITH ASTM A3.

ATTIC ACCESS [CRC R807.1]

BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF CONSTRUCTION SHALL HAVE AN ATTIC ACCESS OPENINGS TO ATTIC AREAS THAT HAVE A VERTICAL HEIGHT OF 30 INCHES OR GREATER OVER AN AREA OF NOT LESS THAN 30 SF. THE VERTICAL HEIGHT SHALL BE

MEASURED FROM THE TOP OF THE CEILING FRAMING MEMBERS TO THE UNDERSIDE OF THE

ROOF FRAMING MEMBERS
THE ROUGH-FRAMED OPENING SHALL BE NOT LESS THAN 22 IN BY 30 IN AND SHALL BE LOCATED IN A HALLWAY OR OTHER LOCATION WITH READY ACCESS. WHERE THE ACCESS IS LOCATED IN A CEILING, MINIMUM UNOBSTRUCTED HEADROOM IN THE ATTIC SPACE SHALL BE 30

IN AT SOME POINT ABOVE THE ACCESS MEASURED VERTICALLY FROM THE BOTTOM OF CEILING FRAMING MEMBERS.

WOOD SOFFIT/CEILING, SIDING & TRIM
ALL NAILS, FASTENERS AND HARDWARE MUST BE STAINLESS STEEL OR HOT-DIPPED GALVANIZED.

STAPLES ARE NOT PERMITTED.

PROVIDE A WATER-RESISTIVE BARRIER APPLIED OVER STUD OR SHEATHING OF ALL EXTERIOR

WALLS WITH FLASHING, IN SUCH A MANNER AS TO PROVIDE A CONTINUOUS BARRIER BEHIND THE EXTERIOR WALL VENEER [CRC SECTION R703.2]

APPROVED CORROSION-RESISTANT FLASHING SHALL BE APPLIED SHINGLE-FASHION IN A MANNER

TO PREVENT ENTRY OF WATER INTO THE WALL CAVITY OR PENETRATION OF WATER TO THE BUILDING STRUCTURAL FRAMING COMPONENT AND COMPLY WITH CRC SECTION 703.4.

FLASHING AND SHEET METAL

ALL FLASHING AND COUNTER FLASHING SHALL BE GALVANIZED AND INSTALLED PER SMACNA STANDARDS. ALL PROPOSED FLASHING AND SHEET METAL MATERIALS, GAUGE, AND INSTALLATION IS TO BE IN ACCORDANCE WITH SMACNA MANUAL STANDARDS.

1. 2.

3. A.

B.
a.
b.

C.
a.
b.

D.
a.
b.

1. 2.

INSTALL CLASS A ROOF ASSEMBLY PER SPECIFICATION BELOW. (CLASS A ROOF ASSEMBLY SHALL BE INSTALLED. IF THE APPLICANT DEVIATES FROM THE ROOF SPECIFICATIONS THE APPLICANT

SHALL PROVIDE A COPY OF THE ICC/UL LISTING)
ROOF COVERING SHALL COMPLY WITH CRC R902 AND CRC R905.

ROOF MATERIAL SPECIFICATIONS
ALL ROOFING MATERIALS TO BE INSTALLED PER MANUFACTURER ’S SPECIFICATIONS ASPHALT SHINGLE ROOF - CERTAINTEED (ICC-ES ER ESR-3537) 2”/12” SLOPE (17%) MINIMUM
FOR ROOF SLOPES 2 ”/12” (17%) UP TO 4”/12” (33%), DOUBLE UNDERLAMENT APPLICATION IS REQUIRED [CRC R905.1.1]
STANDING SEAM METAL ROOF - METAL SALES MAGNA-LOC (ICC ES REPORT ESR-2385) ¼”/12” SLOPE (2%) MINIMUM
24 GA
CONCRETE TILE ROOF - EAGLE ROOF PRODUCTS (IAMP UES-ER 1900) 2 ½”/12” SLOPE (25%) MINIMUM
FOR ROOF SLOPES 2 ½”/12” (2%) UP TO 4”/12” (33%), INSTALL DOUBLE UNDERLAYMENT APPLICATION [CRC R905.3.3]

4. ROOF GUTTERS AND DOWNSPOUTS SHALL BE INSTALLED AND DESIGNED IN ACCORDANCE WITH SMACNA MANUAL. SIZE AS REQUIRED TO HANDLE THE AMOUNT OF ROOF WATER FOR MAXIMUM STORMS.

5. PROVIDE PLAIN RECTANGULAR ROOF GUTTER.

6. GUTTERS SHALL BE PROVIDED WITH THE MEANS TO PREVENT THE ACCUMULATION OF LEAVES AND DEBRIS IN THE GUTTER IN HIGH FIRE SEVERITY ZONES.

7. ROOF VENTS

ROOF VENTS SHALL BE INSTALLED PER MANUFACTURERS SPECIFICATIONS OPENINGS FOR VENTILATION HAVING A LEAST DIMENSION LARGER THAN 1/4 INCH SHALL BE

PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH SCREENING, HARDWARE CLOTH,

PERFORATED VINYL OR SIMILAR MATERIAL WITH OPENINGS HAVING A LEAST DIMENSION OF NOT LESS THAN 1/16 INCH AND NOT MORE THAN 1/4 INCH.

GENERAL ARCHITECTURAL NOTES

GENERAL ARCHITECTURAL ROOF NOTES

ABBREVIATIONS

1. 2.

3. 4.

8. FLASHINGS SHALL BE INSTALLED IN A MANNER THAT PREVENTS MOISTURE FROM ENTERING THE

WALL AND ROOF THROUGH JOINTS IN COPINGS, THROUGH MOISTURE PERMEABLE MATERIALS AND

AT INTERSECTIONS WITH WALLS AND OTHER PENETRATIONS THROUGH THE ROOF PLANE PER CRC SECTION 903.2.

9. NOT LESS THAN 1-INCH SPACE SHALL BE PROVIDED BETWEEN THE INSULATION AND THE ROOF SHEATHING AND AT THE LOCATION OF VENTS [CRC SECTION R806.3].

10. INSTALL INSULATION PER CRC SECTION R806.5:
(REFER TO DETAILS A, B, AND C ON SHEET A5.2)

WHERE ONLY AIR-IMPERMEABLE INSULATION IS PROVIDED, IT SHALL BE APPLIED IN DIRECT CONTACT WITH UNDERSIDE OF THE STRUCTURAL ROOF SHEATHING.

WHERE AIR-PERMEABLE INSULATION IS INSTALLED DIRECTLY BELOW THE STRUCTURAL

SHEATHING, RIGID BOARD OR SHEET INSULATION SHALL BE INSTALLED DIRECTLY ABOVE THE

STRUCTURAL ROOF SHEATHING IN ACCORDANCE WITH R-VALUES BASED ON CLIMATE ZONE PER TABLE R806.5 FOR CONDENSATION CONTROL.

WHERE BOTH AIR-IMPERMEABLE INSULATION AND AIR-PERMEABLE INSULATION ARE PROVIDED,

THE AIR-IMPERMEABLE INSULATION SHALL BE APPLIED IN DIRECT CONTACT WITH THE

UNDERSIDE OF THE STRUCTURAL ROOF SHEATHING IN ACCORDANCE WITH R-VALUES BASED ON CLIMATE ZONE PER TABLE R806.5 FOR CONDENSATION CONTROL. THE AIR-PERMEABLE

INSULATION SHALL BE INSTALLED DIRECTLY UNDER THE AIR-IMPERMEABLE INSULATION

ALTERNATIVELY, SUFFICIENT RIGID BOARD OR SHEET INSULATION SHALL BE INSTALLED

DIRECTLY ABOVE THE STRUCTURAL ROOF SHEATHING TO MAINTAIN THE MONTHLY AVERAGE TEMPATURE OF THE UNDERSIDE OF THE STRUCTURAL ROOF SHEATHIGN ABOVE 45 DEG F. FOR CLACULATION PURPOSES, AN INTERIOR AIR TEMPATURE OF 68 DEG IS ASSUMED AND THE

EXTERIOR AIR TEMPERATURE IS ASSUMED TO BE THE MONTHLY AVERAGE OUTSIDE AIR TEMEPRATURE OF THE THREE COLDEST MONTHS.

GENERAL ARCHITECTURAL ROOF NOTES CONTINUED

GENERAL FIRE NOTES

1. 2.

3. 4.

WHERE RECESSED FIXTURES OCCUR IN WALLS OR HORIZONTAL ASSEMBLIES, THE FIRE RATING OF

THOSE ASSESMBLIES SHALL BE MAINTAINED

AT ALL PENETRATIONS AND INTERSECTIONS OF FIRE RATED PARTITIONS, PROVIDE FIRE SEALANT AND/OR FIRE STOPPING TO MAINTAIN CONTINUITY OF PARTITION RATING.

SEE SHEET A-6.1 FOR FIRE RATED GLAZING REQUIREMENTS.

THE ADU SHALL COMPLY WITH CHAPTER 7A MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR WILDFIRE EXPOSURE OF THE 2022 CALIFORNIA BUILDING CODE IF IT IS IN THE VERY HIGH FIRE HAZARD SEVERITY ZONE (VHFHSZ).

1. 2.

3. 4.

1. 2.

3. 5.

1. 2.

3. 6.

1. 2.

3. 7.

8. 1.

2. 3.

4. 5.

6. 7.

1. 2.

3. 4.

5. 6.

REQUIREMENTS OF CHAPTER 7A OF THE 2022 CALIFORNIA BUILDING CODE INCLUDE:
705A.2 ROOF COVERINGS. WHERE THE ROOF PROFILE HAS AN AIRSPACE UNDER THE ROOF COVERING, INSTALLED OVER A COMBUSTIBLE DECK, A 72 LB. (32.7 KG) CAP SHEET COMPLYING WITH ASTM D3909 STANDARD SPECIFICATION FOR "ASPHALT ROLLED ROOFING (GLASS FELT) SURFACED WITH MINERAL GRANULES," SHALL BE INSTALLED OVER THE ROOF DECK. BIRD STOPS SHALL BE USED AT THE EAVES WHEN THE PROFILE FITS. TO PREVENT DEBRIS AT THE EAVE. HIP AND RIDGE CAPS SHALL BE MUDDED IN TO PREVENT INTRUSION OF FIRE OR EMBERS. EXCEPTION:

CAP SHEET IS NOT REQUIRED WHEN NO LESS THAN 1" OF MINERAL WOOL BOARD OR OTHER

NONCOMBUSTIBLE MATERIAL IS LOCATED BETWEEN THE ROOFING MATERIAL AND WOOD FRAMING OR DECK. ALTERNATELY, A CLASS A FIRE RATED ROOF UNDERLAYMENT, TESTED IN ACCORDANCE WITH ASTM E108, SHALL BE PERMITTED TO BE USED. IF THE SHEATHING CONSISTS

OF EXTERIOR FIRE-RETARDANT TREATED WOOD, THE UNDERLAYMENT SHALL NOT BE REQUIRED TO COMPLY WITH A CLASS A CLASSIFICATION. BIRD STOPS SHALL BE USED AT THE EAVES WHEN THE PROFILE FITS, TO PREVENT DEBRIS AT THE EAVE. HIP AND RIDGE CAPS SHALL BE MUDDED IN TO PREVENT INTRUSION OF FIRE OR EMBERS.
705.A.3 ROOF VALLEYS. WHERE VALLEY FLASHING IS INSTALLED, THE FLASHING SHALL BE NOT LESS THAN 0.019-INCH NO. 26 GAGE GALVANIZED SHEET CORROSION-RESISTANT METAL INSTALLED OVER NOT LESS THAN ONE LAYER OF MIN. 72 POUND MINERAL-SURFACED NON PERFORATED CAP SHEET COMPLYING WITH ASTM D 3909. AT LEAST 36-INCH -WIDE RUNNING THE FULL LENGTH OF THE VALLEY.
705A.4 ROOF GUTTERS SHALL BE PROVIDED WITH THE MEANS TO PREVENT THE ACCUMULATION OF LEAVES AND DEBRIS IN THE GUTTER.
706A.2 VENTILATION OPENINGS SHALL BE FULLY COVERED WITH WILDFIRE FLAME AND EMBER

RESISTANT VENTS APPROVED AND LISTED BY THE CALIFORNIA STATE FIRE MARSHAL, OR WUI VENTS TESTED TO ASTM E2886 AND LISTED, BY COMPLYING WITH ALL OF THE FOLLOWING REQUIREMENTS:

THERE SHALL BE NO FLAMING IGNITION OF THE COTTON MATERIAL DURING THE EMBER

INTRUSION TEST

THERE SHALL BE NO FLAMING IGNITION DURING THE INTEGRITY TEST PORTION OF THE FLAME

INTRUSION TEST

THE MAXIMUM TEMPERATURE OF THE UNEXPOSED SIDE OF THE VENT SHALL NOT EXCEED 662 F
706A.2.1 VENTS THAT ARE INSTALLED ON A SLOPED ROOF, SUCH AS DORMER VENTS, SHALL COMPLY WITH ALL THE FOLLOWING:

VENTS SHALL BE COVERED WITH A MESH WHERE THE DIMENSIONS OF THE MESH THEREIN SHALL BE A MINIMUM OF 1/16 - INCH AND SHALL NOT EXCEED 1/8 - INCH IN DIAMETER

THE MESH MATERIAL SHALL BE NONCOMBUSTIBLE
THE MESH MATERIAL SHALL BE CORROSION RESISTANT.
707A.3 EXTERIOR WALLS COVERINGS. THE EXTERIOR WALL COVERING SHALL COMPLY WITH ONE

OR MORE OF THE FOLLOWING REQUIREMENTS, EXCEPT AS PERMITTED FOR EXTERIOR WALL ASSEMBLIES COMPLYING WITH SECTION 707A.4:

NONCOMBUSTIBLE MATERIAL
IGNITION- RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 704A.2.

FIRE-RETARDANT-TREATED WOOD. THE FIRE-RETARDANT-TREATED WOOD SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2. 707A.3.1 EXTENT OF EXTERIOR WALL COVERING. EXTERIOR WALL COVERINGS SHALL EXTEND FROM THE TOP OF THE FOUNDATION TO THE ROOF AND TERMINATE AT 2" NOMINAL SOLID WOOD

BLOCKING BETWEEN RAFTERS AT ALL ROOF OVERHANGS, OR IN THE CASE OF ENCLOSED EAVES, TERMINATE AT THE ENCLOSURE.
707A.4 EXTERIOR WALL ASSEMBLIES. EXTERIOR WALL ASSEMBLIES OF BUILDINGS OR

STRUCTURES SHALL BE CONSTRUCTED USING ONE OR MORE OF THE FOLLOWING METHODS, UNLESS THEY ARE COVERED BY AN EXTERIOR WALL COVERING COMPLYING WITH SECTION 707A.3:

ASSEMBLY OF SAWN LUMBER OR GLUE LAMINATED WOOD WITH THE SMALLEST MINIMUM NOMINAL DIMENSION OF 4 INCHES. SAWN OR GLUE-LAMINATED PLANKS SPLINED, TONGUEAND-GROVE , OR SET CLOSE TOGETHER AND WELL SPIKED.

LOG WALL CONSTRUCTION ASSEMBLY
ASSEMBLY THAT HAS BEEN TESTED IN ACCORDANCE WITH THE TEST PROCEDURES FOR A 10 MINUTE DIRECT FLAME CONTACT EXPOSURE SET FORTH IN ASTM E2707 WITH THE CONDITIONS OF ACCEPTANCE SHOWN IN SECTION 707A.4.1.

ASSEMBLY THAT MEET THE PERFORMANCE CRITERIA IN ACCORDANCE WITH THE TEST

PROCEDURES FOR A TEN MINUTE DIRECT FLAME CONTACT EXPOSURE TEST SET FORTH IN SFM STANDARD 12-7A-1
ASSEMBLY SUITABLE FOR EXTERIOR FIRE EXPOSURE WITHA 1-HOUR FIRE RESISTANCE RATING, RATED FROM THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL263
ASSEMBLY SUITABLE FOR EXTERIOR FIRE EXPOSURE CONTAINING ONE LAYER OF 5/8 -INCH

TYPE X GYPSUM SHEATHING APPLIED BEHIND THE EXTERIOR WALL COVERING OR CLADDING ON THE EXTERIOR SIDE OF THE FRAMING.

ASSEMBLY SUITABLE FOR EXTERIOR EXPOSURE CONTAINING ANY OF THE GYPSUM PANEL

AND SHEATHING PRODUCTS LISTED IN THE GYPSUM ASSOCIATION FIRE RESISTANCE DESIGN MANUEL AS COMPLYING WITH A1-HOUR FIRE-RESISTANCE RATING, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263

9. 707A.5 OPEN ROOF EAVES. THE EXPOSED ROOF DECK ON THE UNDERSIDE OF ENCLOSED ROOF EAVES SHALL CONSIST OF ONE OR MORE OF THE FOLLOWING:

NON COMBUSTIBLE MATERIAL
IGNITION- RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR EXTERIOR USE AN SHALL MEET THE REQUIREMENTS OF SECTION 704A.2 FIRE-RETARDANT-TREATED WOOD. THE FIRE-RETARDANT-TREATED WOOD SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2 MATERIALS APPROVED FOR NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION ON THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263
ONE LAYER OF 5/8" TYPE X GYPSUM SHEATHING APPLIES BEHIND AN EXTERIOR COVERING ON THE UNDERSIDE EXTERIOR OF THE ROOFDECK.

THE EXTERIOR PORTION A 1- HOUR FIRE RESISTIVE EXTERIOR ASSEMBLY, APPLIES AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263, APPLIED TO THE UNDERSIDE OF THE

ROOF DECK DESIGNED FOR THE EXTERIOR FIRE EXPOSURE, INCLUDING ASSEMBLES USING

THE GYPSUM PANEL AND SHEATHING PRODUCTS LISTED IN THE GYPSUM ASSOCIATION FIRE RESISTANCE DEIGN MANUAL. EXCEPTION TO SECTION 707A.5: THE FOLLOWING MATERIALS DO NOT REQUIRE PROTECTION: FASCIA AND OTHER ARCHITECTURAL TRIM BOARDS

1. 2.

3. 4.

5. 6.

7. 8.

1. 2.

3. 4.

5. 6.

7. 8.

1. 2.

3. 4.

5. 6.

7. 8.

1. 2.

3. 4.

5. 6.

7. 8.

1. 2.

3. 4.

5. 6.

7. 8.

10. 707A.6 ENCLOSED ROOF EAVES AND ROOF EAVE SOFFITS. THE EXPOSED UNDERSIDE OF ENCLOSED

ROOF EAVES HAVING EITHER A BOXED-IN ROOF EAVE SOFFIT WITH A HORIZONTAL UNDERSIDE,OR

SLOPING RAFTER TAILS WITH AN EXTERIOR COVERING APPLIED TO THE UNDERSIDE OF THE RAFTER TAILS, SHALL BE PROTECTED BY ONE OR MORE OF THE FOLLOWING:

NONCOMBUSTIBLE MATERIAL
IGNITION- RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 704A.2 FIRE-RETARDANT-TREATED-WOOD. THE FIRE-RETARDANT TREATED WOOD SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2 MATERIALS APPROVED FOR NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION ON THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263 ONE LAYER OF 5/8" TYPE X GYPSUM SHEATHING APPLIED BEHIND AN EXTERIOR COVERING ON THE UNDERSIDE OF FLOOR PROJECTION.

THE EXTERIOR PORTION A 1- HOUR FIRE RESISTIVE EXTERIOR ASSEMBLY, APPLIED TO THE

UNDERSIDE OF THE RAFTER TAIS OR SOFFIT, INCLUDING ASSEMBLES USING THE GYPSUM

PANEL AND SHEATHING PRODUCTS LISTED IN THE GYPSUM ASSOCIATION FIRE RESISTANCE

DESIGN MANUAL

BOXED-IN ROOF EAVE SOFFIT ASSEMBLIES WITH A HORIZONTAL UNDERSIDE THAT MEET THE PERFORMANCE CRITERIA IN SECTION 707A.11 WHEN TESTED IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN ASTM E2957

BOXED-IN ROOF EAVE SOFFIT ASSEMBLIES WITH A HORIZONTAL UNDERSIDE THAT MEET THE PERFORMANCE CRITERIA IN SECTION 707A.11 WHEN TESTED IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN SFM STANDARD 12-7A-3 EXCEPTION TO SECTION 707A.6: THE FOLLOWING MATERIALS DO NOT REQUIRE PROTECTION: FASCIA AND OTHER ARCHITECTURAL TRIM BOARDS.

11. 707A.7 EXTERIOR PORCH CEILINGS. THE EXPOSED UNDERSIDE OF THE EXTERIOR PORCH CEILINGS SHALL BE PROTECTED BY ONE OF THE FOLLOWING:

NON COMBUSTIBLE MATERIAL
IGNITION- RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 704A.2 FIRE-RETARDANT-TREATED-WOOD. THE FIRE-RETARDANT TREATED WOOD SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2 MATERIALS APPROVED FOR NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION ON THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263 ONE LAYER OF 5/8" TYPE X GYPSUM SHEATHING APPLIED BEHIND THE EXTERIOR COVERING OR CLADDING ON THE UNDERSIDE OF THE RAFTER TAILS OR SOFFIT.

THE EXTERIOR PORTION A 1- HOUR FIRE RESISTIVE EXTERIOR ASSEMBLY, AS TESTED IN ACCORDANCE WITH ASTM E119, APPLIED TO THE UNDERSIDE OF THE CEILING ASSEMBLY,

INCLUDING ASSEMBLES USING THE GYPSUM PANEL AND SHEATHING PRODUCTS LISTED IN THE GYPSUM ASSOCIATION FIRE RESISTANCE DESIGN MANUAL.

PORCH CEILING ASSEMBLIES WITH A HORIZONTAL UNDERSIDE THAT MEET THE PERFORMANCE CRITERIA IN SECTION 707A.11 WHEN TESTED IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN ASTM E2957

PORCH CEILING ASSEMBLIES WITH A HORIZONTAL UNDERSIDE THAT MEET THE PERFORMANCE CRITERIA IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN SFM STANDARD 12-7A-3 EXCEPTION TO SECTION 707A.7: ARCHITECTURAL TRIM BOARDS DO NOT REQUIRE PROTECTION

12. 707A.8 FLOOR PROJECTIONS. THE EXPOSED UNDERSIDE OF A CANTILEVER FLOOR PROJECTION

WHERE A FLOOR ASSEMBLY EXTENDS OVER AN EXTERIOR WALL SHALL BE PROTECTED BY ON OF THE FOLLOWING:

NONCOMBUSTIBLE MATERIAL
IGNITION- RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 704A.2 FIRE-RETARDANT-TREATED-WOOD. THE FIRE-RETARDANT TREATED WOOD SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2 MATERIALS APPROVED FOR NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION ON THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263 ONE LAYER OF 5/8" TYPE X GYPSUM SHEATHING APPLIED BEHIND AND EXTERIOR COVERING ON

THE UNDERSIDE OF THE CEILING
THE EXTERIOR PORTION A 1- HOUR FIRE RESISTIVE EXTERIOR ASSEMBLY, AS TESTED IN ACCORDANCE WITH ASTM E119, APPLIED TO THE UNDERSIDE OF THE CEILING ASSEMBLY,

INCLUDING ASSEMBLES USING THE GYPSUM PANEL AND SHEATHING PRODUCTS LISTED IN THE GYPSUM ASSOCIATION FIRE RESISTANCE DESIGN MANUAL.

THE UNDERSIDE OF A FLOOR PROJECTIONS ASSEMBLY THAT MEETS THE PERFORMANCE CRITERIA IN SECTION 707A.10 WHEN TESTED IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN ASTM E2957.

THE UNDERSIDE OF A FLOOR PROJECTIONS ASSEMBLY THAT MEETS THE PERFORMANCE CRITERIA IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN THE SFM STD 12-7A-3.

EXCEPTION TO SECTION 707A.8: ARCHITECTURAL TRIM BOARDS DO NOT REQUIRE PROTECTION

13. 707A.9 UNDERFLOOR PROTECTION. THE UNDERFLOOR AREA OF ELEVATED OR OVERHANGING

BUILDINGS SHALL BE ENCLOSED TO GRADE IN ACCORDANCE WITH THE REQUIREMENTS OF

THIS CHAPTER OR THE UNDERSIDE OF THE EXPOSED UNDERFLOOR SHALL BE PROTECTED BY ONE OR MORE OF THE FOLLOWING:

NONCOMBUSTIBLE MATERIAL
IGNITION- RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 704A.2 FIRE-RETARDANT-TREATED-WOOD. THE FIRE-RETARDANT TREATED WOOD SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2 MATERIALS APPROVED FOR NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION ON THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263 ONE LAYER OF 5/8" TYPE X GYPSUM SHEATHING APPLIED BEHIND AND EXTERIOR COVERING ON

THE UNDERSIDE OF THE FLOOR PROJECTION
THE EXTERIOR PORTION A 1- HOUR FIRE RESISTIVE EXTERIOR ASSEMBLY, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263, APPLIED TO THE UNDERSIDE OF THE FLOOR,

INCLUDING ASSEMBLES USING THE GYPSUM PANEL AND SHEATHING PRODUCTS LISTED IN THE GYPSUM ASSOCIATION FIRE RESISTANCE DESIGN MANUAL.

THE UNDERSIDE OF A FLOOR ASSEMBLY THAT MEETS THE PERFORMANCE CRITERIA IN SECTION 707A.11 WHEN TESTED IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN ASTM E2957.

THE UNDERSIDE OF A FLOOR ASSEMBLY THAT MEETS THE PERFORMANCE CRITERIA IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN SFM STANDARD 12-7A-3. EXCEPTION TO SECTION 707A.9: STRUCTURAL COLUMNS AND BEAMS DO NOT REQUIRE PROTECTION WHEN

CONSTRUCTED WITH SAWN LUMBER OR GLUE-LAMINATED WOOD WITH THE SMALLEST MINIMUM NOMINAL DIMENSION OF 4 INCHES. SAWN OR GLUE-LAMINATED PLANKS SHALL BE SPLINED, TONGUE-AND-GROOVE, OR SET CLOSE TOGETHER AND WELL SPIKED.

14. 707A.10 UNDERSIDE OF APPENDAGES. WHEN REQUIRED BY THE ENFORCING AGENCY THE

UNDERSIDE OF OVERHANGING APPENDAGES SHALL BE ENCLOSED TO GRADE IN ACCORDANCE

WITH THE REQUIREMENTS OF THIS CHAPTER OR THE UNDERSIDE OF THE EXPOSED UNDER FLOOR SHALL CONSIST OF ONE OF THE FOLLOWING:

NONCOMBUSTIBLE MATERIAL
IGNITION- RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 704A.2 FIRE-RETARDANT-TREATED-WOOD. THE FIRE-RETARDANT TREATED WOOD SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2 MATERIALS APPROVED FOR NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION ON THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263 ONE LAYER OF 5/8" TYPE X GYPSUM SHEATHING APPLIED BEHIND THE EXTERIOR COVERING ON

THE UNDERSIDE OF THE APPENDAGE PROJECTION
THE EXTERIOR PORTION A 1- HOUR FIRE RESISTIVE EXTERIOR ASSEMBLY, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263, APPLIED TO THE UNDERSIDE OF THE APPENDAGE,

INCLUDING ASSEMBLES USING THE GYPSUM PANEL AND SHEATHING PRODUCTS LISTED IN THE GYPSUM ASSOCIATION FIRE RESISTANCE DESIGN MANUAL.

THE UNDERSIDE OF AN APPENDAGE ASSEMBLY THAT MEETS THE PERFORMANCE CRITERIA IN SECTION 707A.11 WHEN TESTED IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN ASTM E2957.

THE UNDERSIDE OF AN APPENDAGE ASSEMBLY THAT MEETS THE PERFORMANCE CRITERIA IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN SFM STANDARD 12-7A-3.EXCEPTION TO SECTION 707A.10: STRUCTURAL COLUMNS AND BEAMS DO NOT REQUIRE PROTECTION WHEN

CONSTRUCTED WITH SAWN LUMBER OR GLUE-LAMINATED WOOD WITH THE SMALLEST MINIMUM NOMINAL DIMENSION OF 4 INCHES. SAWN OR GLUE-LAMINATED PLANKS SHALL BE SPLINED, TONGUE-AND-GROOVE, OR SET CLOSE TOGETHERAND WELL SPIKED.

GENERAL FIRE NOTES CONTINUED

ARCHITECTURAL SYMBOLS

CALLOUT PLAN,

SECTION OR DETAIL
#

BUILDING SECTION

ELEVATIONS

VIEW TITLE
# SCALE:

VIEW CALLOUT
COLUMN GRID #
#

DOOR TAG - SEE

SCHEDULE
##.## KEYNOTE

DENOTES ABOVE,

BELOW, OR BEHIND
# WINDOW TYPE

LEVEL LINE

CENTER LINE
#
#
#

GLAZING
#
#
Sheet #
D
C
B
A
1 2 3 4 5
1 2 3 4 5
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

GENERAL NOTES, ABBREVIATIONS, AND SYMBOLS
A-1.0
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026

ABB DESCRIPTION
__________ A __________
& AND
< ANGLE
@ AT

ADJ ADJACENT, ADJUSTABLE

AFF ABOVE FINISHED FLOOR

AP ACCESS PANEL

APPROX APPROXIMATE(LY)

ARCH ARCHITECT OR ARCHITECTURAL

ASTM AMERICAN SOCIETY FOR TESTING MATERIAL

AVG AVERAGE
__________ B __________

BC BASE CABINET

BD BOARD

BLDG BUILDING

BO BOTTOM OF
__________ C __________

C/ CENTER OF

CAB CABINET

CL CENTER LINE

CLG CEILING

CLG HT CEILING HEIGHT

CLO CLOSET

CLR CLEAR

CMU CONCRETE MASONRY UNIT

COL COLUMN

CONC CONCRETE

CONT CONTINUOUS
__________ D __________

DIA DIAMETER

DIM DIMENSION

DN DOWN

DW DISHWASHER

DWG DRAWING
__________ E __________
E EAST

EA EACH

ELEC ELECTRICAL

EMER EMERGENCY

ENCL ENCLOSE(URE)

EP ELECTRICAL PANEL

EQ EQUAL

EQUIP EQUIPMENT

EXIST EXISTING

EXT EXTERIOR
__________ F __________

F/F FACE TO FACE

FL FLOOR

FP FIRE PROTECTION

FPRF FIREPROOF(ING)

FR FIRE RATED OR FRAME

FT FOOT/FEET
__________ G __________

GA GAUGE

GL GLASS OR GLAZING

GRD GROUND

GWB GYPSUM WALL BOARD
__________ H __________

HB HOSE BIBB

HDW HARDWARE

HM HOLLOW METAL

HOR HORIZONTAL

HP HIGH POINT

HTR HEATER
__________ I __________

ID INSIDE DIAMETER

IN INCH(ES)

INT INTERIOR
__________ J __________

JB JAMB

JST JOIST

JT JOINT
__________ L __________

LAM LAMINATE

LAN LOCAL AREA NETWORK CONNECTION

LAV LAVATORY

LB POUND

LF LINEAL FOOT

LP LOW POINT

LTL LINTEL
__________ M __________

MAX MAXIMUM

MDF MEDIUM DENSITY FIBERBOARD

MECH MECHANICAL

ABB DESCRIPTION

MFR MANUFACTURE

MIN MINIMUM

MISC MISCELLANEOUS

MO MASONRY OPENING

MTD MOUNTED

MTL METAL
__________ N __________

N NORTH

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NOM NOMINAL

NTS NOT TO SCALE
__________ O __________

OC ON CENTER

OD OUTSIDE DIAMETER

OPNG OPENING

OPP OPPOSITE
__________ P __________

PART PARTITION

PL PLATE

PLAM PLASTIC LAMINATE

PLAS PLASTER

PLYWD PLYWOOD

PNL PANEL

PREFAB PREFABRICATED

PROP PROPERTY

PSI POUNDS PER SQUARE INCH

PTD PAINTED
__________ Q __________

QTY QUANTITY
__________ R __________

R RISER OR RADIUS

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

REF REFRIGERATOR

REG REGISTER

REINF REINFORCING

REQ'D REQUIRED

REQMT REQUIREMENTS

RG RANGE

RM ROOM

RO ROUGH OPENING

RTS RUBBER TRANSITION STRIP

RWC RAIN WATER CONDUCTOR
__________ S __________

S SOUTH

SAN SANITARY

SCHD SCHEDULE

SEC SECTION

SF SQUARE FOOT

SIM SIMILAR

SPEC SPECIFY, SPECIFIED OR SPECIFICATIONS

SPKLR SPRINKLER

SQ SQUARE

SQ FT SQUARE FOOT

SS STAINLESS STEEL

STD STANDARD

STL STEEL

STN STAINED

STOR STORAGE

STRUCT STRUCTURAL

SUSP SUSPEND, SUSPENDED, OR SUSPENSION

SYS SYSTEM
__________ T __________
"T" TEE (BAR OR W)

T/ TOP OF

TEMP TEMPERED OR TEMPERATURE

THRESH THRESHOLD

TLT TOILET

TYP TYPICAL
__________ U __________

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

UNO UNLESS NOTED OTHERWISE
__________ V __________

VIF VERIFY IN FIELD
__________ W __________
W WEST

W/ WITH

W/O WITHOUT

WC WATER CLOSET

WP WATERPROOF(ING)

WT WEIGHT

REVISIONS
NO. DATE DESCRIPTION
272
REF.

DW
A-2.1 2
A-2.1 1
A-2.1 4
A-2.1 3
1 A-3.1
2 A-3.1

1.02 12
AB
2' - 0" 2' - 0"
2' - 0" 3' - 0"

1.18 1.18
SLOPE
4"/12"
SLOPE
4"/12"

RIDGE SETBACK
3' - 0" REQ'D

1.21A
A-2.1 2
A-2.1 1
A-2.1 4
A-2.1 3
LIVING
1 A-3.1
2 A-3.1
CLOSET
17' - 0"
29' - 0"
12' - 2" 3' - 0" 1' - 10" 10' - 8" 2' - 1"
6' - 3 1/2"
10' - 3"
8' - 2"
5' - 6 1/2"
11' - 4 1/2"
19' - 5 1/2"

KITCHEN

1.01 PATIO
W/D
16' - 1"
1 2
5A
A
BAAA
A
A
3 4
3' - 1" 2' - 11"
2' - 0"
12 AB

1.03 1.06 1.04 1.07

1.08 1.10 1.12

1.13 1.14

1.15 1.16

1.19 1.09
1' - 10" 3' - 0" 15' - 0" 3' - 0" 6' - 2"

1.04 3' - 3" 2' - 8" 5' - 5 1/2" 3' - 0" 5' - 5 1/2" 3' - 0" 1' - 4" 4' - 10"

1.17 BATH
SLOPE
DOWN

SLOPEDOWN
SLOPE
DOWN
DOWN
SLOPE
2' - 7"

1.05 CLO.

1.17 1.17

1.17 LINE ABOVE,
TYP.

1.11 1' - 10" 3' - 0" 3' - 10" 3' - 4" 5' - 0"
3' - 8"

1.20 1.22

1.22 1.23
A-5.1
3A
A-5.1
1B
TYP.

1. 2.

3. 4.

5. 6.

7. REFER TO GENERAL NOTES SHEET A1.0 FOR ADDITIONAL
REQUIREMENTS.

REFER TO STRUCTURAL DRAWINGS FOR ROOF FRAMING
INFORMATION.

ALL FURNITURE AND EQUIPMENT IS BY OWNER AND IS SHOWN
FOR COORDINATION PURPOSES ONLY.

SEE STRUCTURAL FOR EXTERIOR STUD WALL SIZE.

ONE (MIN.) SIDE-HINGED EGRESS DOOR SHALL BE PROVIDED
WITH A CLEAR WIDTH OF NOT LESS THAN 32” WHERE MEASURED

BETWEEN THE FACE OF THE DOOR AND THE STOP, WITH THE
DOOR OPEN 90°. THE CLEAR HEIGHT OF THE DOOR OPENING
SHALL BE NOT LESS THAN 78” IN HEIGHT MEASURED FROM THE
TOP OF THE THRESHOLD TO THE BOTTOM OF THE STOP.

REFER TO MECHANICAL AND PLUMBING PLAN FOR WATER
EFFICIENCY REQUIREMENTS FOR ALL PLUMBING FIXTURES.

ROOF OVERHANG DIMENSIONS ARE FROM FACE OF EXTERIOR

WALL FRAMING TO EDGE OF ROOF

FLOOR AND ROOF PLAN GENERAL SHEET NOTES

1. 2.

3. SOLAR READY ROOF MINIMUM AREA: 250 SF

THE SOLAR ZONE TOTAL ARE SHALL BE COMPRISED OF AREAS
THAT HAVE NO DIMENSION LESS THAN 5 FT. THE SOLAR ZONE

SHALL BE LOCATED ON THE ROOF OR OVERHANG OF THE
BUILDING. [CEC 2022 SECTION 110.10.(b)]
FOR PHOTOVOLTAIC ARRAYS OCCUPYING NOT MORE THAN 33

PERCENT OF THE PLAN VIEW TOTAL ROOF AREA, NOT LESS
THAN AN 18-INCH CLEAR SETBACK IS REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE. FOR PHOTOVOLTAIC ARRAYS
OCCUPYING MORE THAN 33 PERCENT OF THE PLAN VIEW TOTAL
ROOF AREA, NOT LESS THAN A 36-INCH CLEAR SETBACK IS
REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE. [CRC
R329.6.2]

THE SOLAR ZONE SHALL COMPLY WITH ACCESS, PATHWAY,

SMOKE VENTILATION, AND SPACING REQUIREMENTS AS
SPECIFIED IN TILE 24, PART 9 OR OTHER PARTS OF TITLE 24 OR IN ANY REQUIREMENTS ADOPTED BY LOCAL JURISDICTION.

SOLAR READY GENERAL NOTES

SOLAR ZONE

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

NET FREE VENTING AREA REQUIRED = (ENCLOSED AREA / 150)
[CRC R806.2]

ENCLOSED ATTIC SPACE
(174 SF / 150) = 1.16 SF MIN. [168 SQ. IN.]
WALLS AND PROJECTIONS LESS THAN 5 FEET FROM THE PROPERTY LINE SHALL COMPLY WITH CRC TABLES R302.1(1) AND (2).

ENCLOSED RAFTER SPACE 1
(118 SF / 150) = .79 SF MIN. [114 SQ. IN.]
ENCLOSED RAFTER SPACE 2
(201 SF / 150) = 1.34 SF MIN. [193 SQ. IN.]

ROOF VENTING CALCULATIONS
PROVIDE 3 1/2" X 14" (24 SQ. IN. VENTING AREA), EQUALLY SPACED.

VULCAN FIRE STOPPING SOFFIT VENT OR EQUIVALENT.
7 VENTS
5 VENTS
9 VENTS

ROOF VENTING KEY PLAN

ATTIC SPACE

ENCLOSED
RAFTER SPACE 1

ENCLOSED
RAFTER SPACE 2
N.T.S
LEGEND
INDICATES LOCATION OF REINFORCEMENT FOR AGING-INPLACE DESIGN AND FALL PROVENTION. SEE 9/A-5.1 FOR ADDITIONAL INFORMATION.

Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

STUDIO - FLOOR PLAN AND ROOF PLAN (CRAFTSMAN)
A-1.1
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026
0 SCALE:
2' - 0" 4' - 0" 8' - 0"
1/4" = 1' - 0"
SCALE: 1/4" = 1'-0"

ROOF PLAN - CRAFTSMAN
2 KEYNOTES

1.01 LINE OF ROOF ABOVE

1.02 LINE OF BUILDING

1.03 EMEREGENCY EGRESS WINDOW AT SLEEPING ROOM

1.04 LANDING OR FLOOR REQUIRED AT EACH SIDE OF EXTERIOR

DOOR WITH MINIMUM WIDTH EQUAL TO THE WIDTH OF THE
DOOR SERVED AND MINIMUM DEPTH OF 36”. AND 36” MINIMUM
DEPTH MEASURED IN THE DIRECTION OF TRAVEL. LANDING OR
FINISHED FLOOR SHALL NOT BE MORE THAN 1 ½” LOWER THAN
THE TOP OF THE THRESHOLD. THE LANDING ON THE EXTERIOR
SIDE SHALL BE NOT MORE THAN 7 ¾” BELOW THE TOP OF THE

THRESHOLD PROVIDED THAT THE DOOR DOES NOT SWING OVER
THE LANDING OR FLOOR.

1.05 EXTERIOR LANDING SURFACE SLOPE NOT TO EXCEED ¼”/FOOT

AWAY FROM BUILDING

1.06 DOOR BELL, 48” MAX ABOVE EXTERIOR LANDING.

1.07 DOOR MUST PROVIDE NET CLEAR OPENING OF 32”

1.08 36” HIGH COUNTERTOP

1.09 SHELF AND HANGING ROD AT CLOSET

1.10 WALLS AND FLOORS AT BATHTUB AND SHOWER SPACES SHALL BE FINISHED WITH NON-ABSORBENT SURFACES. SUCH WALL
SURFACES SHALL EXTEND TO 72” MIN.

1.11 PROVIDE TEMPERED GLAZED ENCLOSURE AT OR ADJACENT TO

BATHTUBS AND/OR SHOWERS WHERE THE BOTTOM EXPOSED
EDGE OF GLAZING IS LESS THAN 60” ABOVE ANY STANDING OR
WALKING SURFACE.

1.12 PROVIDE REINFORCEMENT FOR GRAB BARS [CRC R327.1]. SEE

FLOOR PLAN GENERAL NOTES FOR ADDITIONAL INFORMATION
AND REQUIREMENTS.

1.13 PROVIDE FURRING AS NEEDED FOR STANDARD BATHTUB AND SHOWER LENGTH.

1.14 DRYER VENT AT EXTERIOR WALL MIN. 3 FT FROM ANY OPENING

1.15 2X6 STUD WALL

1.16 STACKED WASHER/DRYER MACHINE LOCATION

1.17 CEILING AT 8'-0" A.F.F.

1.18 GUTTER AND DOWNSPOUTS. PROVIDE DOWNSPOUT LOCATIONS AS REQUIRED BY SITE SPECIFIC CONDITIONS.

1.19 WATER HEATER, REFER TO MEP.

1.20 A CONDENSING UNIT SUPPORTED FROM THE GROUND SHALL

REST ON A CONCRETE OR OTHER APPROVED BASE EXTENDING
NOT LESS THAN 3 INCHES ABOVE THE ADJOINING GROUND
LEVEL [CMC 1105.2]

1.21A ASPHALT SHINGLE ROOF

1.22 INDOOR UNIT, REFER TO MEP.

1.23 ELECTRICAL SUBPANEL, REFER TO MEP.

AREA: 493 SF
SCALE: 1/4" = 1'-0"

FLOOR PLAN - CRAFTSMAN
1 REVISIONS
NO. DATE DESCRIPTION
273
REF.

DW
A-2.2 2
A-2.2 3
A-2.2 4
A-2.2 1
1 A-3.2
2 A-3.2
BATH
LIVING
CLOSET

KITCHEN
5 4
3 1
A
A
A
A
A
AAB
10' - 8" 2' - 1"
6' - 3 1/2"
10' - 3"
8' - 2"
5' - 6 1/2"
11' - 4 1/2"
19' - 5 1/2"
16' - 1"
3' - 1" 2' - 11"
2' - 0"
12 AB
17' - 0"
29' - 0"
12' - 2" 3' - 0" 1' - 10"
1' - 10" 3' - 0" 15' - 0" 3' - 0" 6' - 2"
3' - 3" 2' - 8" 5' - 5 1/2" 3' - 0" 5' - 5 1/2" 3' - 0" 1' - 4" 4' - 10"

1.05 1.07

1.08 1.10

1.17 1.12

1.13 1.15

1.04 1.01

1.05 1.14

1.19 1.09
2 PATIO

1.17 SLOPE
DOWN

SLOPEDOWN
SLOPE
DOWN
DOWN
SLOPE
2' - 7"
CLO.

1.16 1.17

1.17 1.17

LINE ABOVE,
TYP.

1.06 1' - 10" 3' - 0" 3' - 10" 3' - 4" 5' - 0"
17' - 0"

1.04 1.20

1.22 1.22

1.23 A-5.1
2B
TYP.

A-2.2 2
A-2.2 3
A-2.2 4
A-2.2 1
1 A-3.2
2 A-3.2
SLOPE
4"/12"

1.02 12
AB
8" 8"
8" 8"
6' - 8"
AWNING
7' - 0" 3' - 4"

1.18 1.18
SLOPE
4"/12"
SLOPE
4"/12"

RIDGE SETBACK
3' - 0" REQ'D
3' - 10"

1.21B

1. 2.

3. 4.

5. 6.

7. REFER TO GENERAL NOTES SHEET A1.0 FOR ADDITIONAL
REQUIREMENTS.

REFER TO STRUCTURAL DRAWINGS FOR ROOF FRAMING
INFORMATION.

ALL FURNITURE AND EQUIPMENT IS BY OWNER AND IS SHOWN
FOR COORDINATION PURPOSES ONLY.

SEE STRUCTURAL FOR EXTERIOR STUD WALL SIZE.

ONE (MIN.) SIDE-HINGED EGRESS DOOR SHALL BE PROVIDED
WITH A CLEAR WIDTH OF NOT LESS THAN 32” WHERE MEASURED

BETWEEN THE FACE OF THE DOOR AND THE STOP, WITH THE
DOOR OPEN 90°. THE CLEAR HEIGHT OF THE DOOR OPENING
SHALL BE NOT LESS THAN 78” IN HEIGHT MEASURED FROM THE
TOP OF THE THRESHOLD TO THE BOTTOM OF THE STOP.

REFER TO MECHANICAL AND PLUMBING PLAN FOR WATER
EFFICIENCY REQUIREMENTS FOR ALL PLUMBING FIXTURES.

ROOF OVERHANG DIMENSIONS ARE FROM FACE OF EXTERIOR

WALL FRAMING TO EDGE OF ROOF

FLOOR AND ROOF PLAN GENERAL SHEET NOTES

1. 2.

3. SOLAR READY ROOF MINIMUM AREA: 250 SF

THE SOLAR ZONE TOTAL ARE SHALL BE COMPRISED OF AREAS
THAT HAVE NO DIMENSION LESS THAN 5 FT. THE SOLAR ZONE

SHALL BE LOCATED ON THE ROOF OR OVERHANG OF THE
BUILDING. [CEC 2022 SECTION 110.10.(b)]
FOR PHOTOVOLTAIC ARRAYS OCCUPYING NOT MORE THAN 33

PERCENT OF THE PLAN VIEW TOTAL ROOF AREA, NOT LESS
THAN AN 18-INCH CLEAR SETBACK IS REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE. FOR PHOTOVOLTAIC ARRAYS
OCCUPYING MORE THAN 33 PERCENT OF THE PLAN VIEW TOTAL
ROOF AREA, NOT LESS THAN A 36-INCH CLEAR SETBACK IS
REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE. [CRC
R329.6.2]

THE SOLAR ZONE SHALL COMPLY WITH ACCESS, PATHWAY,

SMOKE VENTILATION, AND SPACING REQUIREMENTS AS
SPECIFIED IN TILE 24, PART 9 OR OTHER PARTS OF TITLE 24 OR IN ANY REQUIREMENTS ADOPTED BY LOCAL JURISDICTION.

SOLAR READY GENERAL NOTES

SOLAR ZONE

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

NET FREE VENTING AREA REQUIRED = (ENCLOSED AREA / 150)
[CRC R806.2]

ENCLOSED ATTIC SPACE
(174 SF / 150) = 1.16 SF MIN. [168 SQ. IN.]
WALLS AND PROJECTIONS LESS THAN 5 FEET FROM THE PROPERTY LINE SHALL COMPLY WITH CRC TABLES R302.1(1) AND (2).

ENCLOSED RAFTER SPACE 1
(118 SF / 150) = .79 SF MIN. [114 SQ. IN.]
ENCLOSED RAFTER SPACE 2
(201 SF / 150) = 1.34 SF MIN. [193 SQ. IN.]

ROOF VENTING CALCULATIONS
PROVIDE 3 1/2" X 14" (24 SQ. IN. VENTING AREA), EQUALLY SPACED.

VULCAN FIRE STOPPING SOFFIT VENT OR EQUIVALENT.
7 VENTS
5 VENTS
9 VENTS

ROOF VENTING KEY PLAN

ATTIC SPACE

ENCLOSED
RAFTER SPACE 1

ENCLOSED
RAFTER SPACE 2
N.T.S
LEGEND
INDICATES LOCATION OF REINFORCEMENT FOR AGING-INPLACE DESIGN AND FALL PROVENTION. SEE 9/A-5.1 FOR ADDITIONAL INFORMATION.

Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

STUDIO - FLOOR PLAN AND ROOF PLAN (MONTEREY)
A-1.2
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026
0 SCALE:
2' - 0" 4' - 0" 8' - 0"
1/4" = 1' - 0"
SCALE: 1/4" = 1'-0"

FLOOR PLAN - MONTEREY
1 SCALE: 1/4" = 1'-0"

ROOF PLAN - MONTEREY
2 KEYNOTES

1.01 LINE OF ROOF ABOVE

1.02 LINE OF BUILDING

1.04 LANDING OR FLOOR REQUIRED AT EACH SIDE OF EXTERIOR

DOOR WITH MINIMUM WIDTH EQUAL TO THE WIDTH OF THE
DOOR SERVED AND MINIMUM DEPTH OF 36”. AND 36” MINIMUM
DEPTH MEASURED IN THE DIRECTION OF TRAVEL. LANDING OR
FINISHED FLOOR SHALL NOT BE MORE THAN 1 ½” LOWER THAN
THE TOP OF THE THRESHOLD. THE LANDING ON THE EXTERIOR
SIDE SHALL BE NOT MORE THAN 7 ¾” BELOW THE TOP OF THE

THRESHOLD PROVIDED THAT THE DOOR DOES NOT SWING OVER
THE LANDING OR FLOOR.

1.05 EXTERIOR LANDING SURFACE SLOPE NOT TO EXCEED ¼”/FOOT

AWAY FROM BUILDING

1.06 DOOR BELL, 48” MAX ABOVE EXTERIOR LANDING.

1.07 DOOR MUST PROVIDE NET CLEAR OPENING OF 32”

1.08 36” HIGH COUNTERTOP

1.09 SHELF AND HANGING ROD AT CLOSET

1.10 WALLS AND FLOORS AT BATHTUB AND SHOWER SPACES SHALL BE FINISHED WITH NON-ABSORBENT SURFACES. SUCH WALL
SURFACES SHALL EXTEND TO 72” MIN.

1.12 PROVIDE REINFORCEMENT FOR GRAB BARS [CRC R327.1]. SEE

FLOOR PLAN GENERAL NOTES FOR ADDITIONAL INFORMATION
AND REQUIREMENTS.

1.13 PROVIDE FURRING AS NEEDED FOR STANDARD BATHTUB AND SHOWER LENGTH.

1.14 DRYER VENT AT EXTERIOR WALL MIN. 3 FT FROM ANY OPENING

1.15 2X6 STUD WALL

1.16 STACKED WASHER/DRYER MACHINE LOCATION

1.17 CEILING AT 8'-0" A.F.F.

1.18 GUTTER AND DOWNSPOUTS. PROVIDE DOWNSPOUT LOCATIONS AS REQUIRED BY SITE SPECIFIC CONDITIONS.

1.19 WATER HEATER, REFER TO MEP.

1.20 A CONDENSING UNIT SUPPORTED FROM THE GROUND SHALL

REST ON A CONCRETE OR OTHER APPROVED BASE EXTENDING
NOT LESS THAN 3 INCHES ABOVE THE ADJOINING GROUND
LEVEL [CMC 1105.2]

1.21B TILE ROOF

1.22 INDOOR UNIT, REFER TO MEP.

1.23 ELECTRICAL SUBPANEL, REFER TO MEP.

AREA: 493 SF

REVISIONS
NO. DATE DESCRIPTION
274
REF.

DW
A-2.3 2
A-2.3 3
A-2.3 4
A-2.3 1
1 A-3.3
2 A-3.3
BATH
LIVING
CLOSET

KITCHEN
1 3
5 4
AA
A
AAAB
A
10' - 8" 2' - 1"
6' - 3 1/2"
10' - 3"
8' - 2"
5' - 6 1/2"
11' - 4 1/2"
19' - 5 1/2"
16' - 1"
3' - 1" 2' - 11"
2' - 0"
12 AB

1.05 1.07

1.08 1.10

1.17 1.12

1.13 1.15

1.04 12' - 2" 3' - 0" 1' - 10"
1' - 10" 3' - 0" 15' - 0" 3' - 0" 6' - 2"
3' - 3" 2' - 8" 5' - 5 1/2" 3' - 0" 5' - 5 1/2" 3' - 0" 1' - 4" 4' - 10" 17' - 0"
29' - 0"

1.01 1.05

1.14 1.19

1.09 2

1.17 SLOPE
DOWN

SLOPEDOWN
SLOPE
DOWN
DOWN
SLOPE
2' - 7"
CLO.

1.16 1.17

1.17 1.17

LINE ABOVE,
TYP.

1.06 1' - 10" 3' - 0" 3' - 10" 3' - 4" 5' - 0"
17' - 0"

1.04 1.20
PATIO

1.22 1.22

1.23 A-5.1
1B
TYP.

A-2.3 2
A-2.3 3
A-2.3 4
A-2.3 1
1 A-3.3
2 A-3.3
SLOPE
4"/12"
SLOPE
4"/12"

1.02 12
AB
2' - 0" 2' - 0"
2' - 0" 3' - 0"

1.18 1.18

RIDGE SETBACK
3' - 0" REQ'D

1.21C

1. 2.

3. 4.

5. 6.

7. REFER TO GENERAL NOTES SHEET A1.0 FOR ADDITIONAL
REQUIREMENTS.

REFER TO STRUCTURAL DRAWINGS FOR ROOF FRAMING
INFORMATION.

ALL FURNITURE AND EQUIPMENT IS BY OWNER AND IS SHOWN
FOR COORDINATION PURPOSES ONLY.

SEE STRUCTURAL FOR EXTERIOR STUD WALL SIZE.

ONE (MIN.) SIDE-HINGED EGRESS DOOR SHALL BE PROVIDED
WITH A CLEAR WIDTH OF NOT LESS THAN 32” WHERE MEASURED

BETWEEN THE FACE OF THE DOOR AND THE STOP, WITH THE
DOOR OPEN 90°. THE CLEAR HEIGHT OF THE DOOR OPENING
SHALL BE NOT LESS THAN 78” IN HEIGHT MEASURED FROM THE
TOP OF THE THRESHOLD TO THE BOTTOM OF THE STOP.

REFER TO MECHANICAL AND PLUMBING PLAN FOR WATER
EFFICIENCY REQUIREMENTS FOR ALL PLUMBING FIXTURES.

ROOF OVERHANG DIMENSIONS ARE FROM FACE OF EXTERIOR

WALL FRAMING TO EDGE OF ROOF

FLOOR AND ROOF PLAN GENERAL SHEET NOTES

1. 2.

3. SOLAR READY ROOF MINIMUM AREA: 250 SF

THE SOLAR ZONE TOTAL ARE SHALL BE COMPRISED OF AREAS
THAT HAVE NO DIMENSION LESS THAN 5 FT. THE SOLAR ZONE

SHALL BE LOCATED ON THE ROOF OR OVERHANG OF THE
BUILDING. [CEC 2022 SECTION 110.10.(b)]
FOR PHOTOVOLTAIC ARRAYS OCCUPYING NOT MORE THAN 33

PERCENT OF THE PLAN VIEW TOTAL ROOF AREA, NOT LESS
THAN AN 18-INCH CLEAR SETBACK IS REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE. FOR PHOTOVOLTAIC ARRAYS
OCCUPYING MORE THAN 33 PERCENT OF THE PLAN VIEW TOTAL
ROOF AREA, NOT LESS THAN A 36-INCH CLEAR SETBACK IS
REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE. [CRC
R329.6.2]

THE SOLAR ZONE SHALL COMPLY WITH ACCESS, PATHWAY,

SMOKE VENTILATION, AND SPACING REQUIREMENTS AS
SPECIFIED IN TILE 24, PART 9 OR OTHER PARTS OF TITLE 24 OR IN ANY REQUIREMENTS ADOPTED BY LOCAL JURISDICTION.

SOLAR READY GENERAL NOTES

SOLAR ZONE

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

NET FREE VENTING AREA REQUIRED = (ENCLOSED AREA / 150)
[CRC R806.2]

ENCLOSED ATTIC SPACE
(174 SF / 150) = 1.16 SF MIN. [168 SQ. IN.]
WALLS AND PROJECTIONS LESS THAN 5 FEET FROM THE PROPERTY LINE SHALL COMPLY WITH CRC TABLES R302.1(1) AND (2).

ENCLOSED RAFTER SPACE 1
(118 SF / 150) = .79 SF MIN. [114 SQ. IN.]
ENCLOSED RAFTER SPACE 2
(201 SF / 150) = 1.34 SF MIN. [193 SQ. IN.]

ROOF VENTING CALCULATIONS
PROVIDE 3 1/2" X 14" (24 SQ. IN. VENTING AREA), EQUALLY SPACED.

VULCAN FIRE STOPPING SOFFIT VENT OR EQUIVALENT.
7 VENTS
5 VENTS
9 VENTS

ROOF VENTING KEY PLAN

ATTIC SPACE

ENCLOSED
RAFTER SPACE 1

ENCLOSED
RAFTER SPACE 2
N.T.S
LEGEND
INDICATES LOCATION OF REINFORCEMENT FOR AGING-INPLACE DESIGN AND FALL PROVENTION. SEE 9/A-5.1 FOR ADDITIONAL INFORMATION.

Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

STUDIO - FLOOR PLAN AND ROOF PLAN (MODERN FARMHOUSE)
A-1.3
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026
0 SCALE:
2' - 0" 4' - 0" 8' - 0"
1/4" = 1' - 0"
SCALE: 1/4" = 1'-0"

FLOOR PLAN - MODERN FARMHOUSE
1 SCALE: 1/4" = 1'-0"

ROOF PLAN - MODERN FARMHOUSE
2 KEYNOTES

1.01 LINE OF ROOF ABOVE

1.02 LINE OF BUILDING

1.04 LANDING OR FLOOR REQUIRED AT EACH SIDE OF EXTERIOR

DOOR WITH MINIMUM WIDTH EQUAL TO THE WIDTH OF THE
DOOR SERVED AND MINIMUM DEPTH OF 36”. AND 36” MINIMUM
DEPTH MEASURED IN THE DIRECTION OF TRAVEL. LANDING OR
FINISHED FLOOR SHALL NOT BE MORE THAN 1 ½” LOWER THAN
THE TOP OF THE THRESHOLD. THE LANDING ON THE EXTERIOR
SIDE SHALL BE NOT MORE THAN 7 ¾” BELOW THE TOP OF THE

THRESHOLD PROVIDED THAT THE DOOR DOES NOT SWING OVER
THE LANDING OR FLOOR.

1.05 EXTERIOR LANDING SURFACE SLOPE NOT TO EXCEED ¼”/FOOT

AWAY FROM BUILDING

1.06 DOOR BELL, 48” MAX ABOVE EXTERIOR LANDING.

1.07 DOOR MUST PROVIDE NET CLEAR OPENING OF 32”

1.08 36” HIGH COUNTERTOP

1.09 SHELF AND HANGING ROD AT CLOSET

1.10 WALLS AND FLOORS AT BATHTUB AND SHOWER SPACES SHALL BE FINISHED WITH NON-ABSORBENT SURFACES. SUCH WALL
SURFACES SHALL EXTEND TO 72” MIN.

1.12 PROVIDE REINFORCEMENT FOR GRAB BARS [CRC R327.1]. SEE

FLOOR PLAN GENERAL NOTES FOR ADDITIONAL INFORMATION
AND REQUIREMENTS.

1.13 PROVIDE FURRING AS NEEDED FOR STANDARD BATHTUB AND SHOWER LENGTH.

1.14 DRYER VENT AT EXTERIOR WALL MIN. 3 FT FROM ANY OPENING

1.15 2X6 STUD WALL

1.16 STACKED WASHER/DRYER MACHINE LOCATION

1.17 CEILING AT 8'-0" A.F.F.

1.18 GUTTER AND DOWNSPOUTS. PROVIDE DOWNSPOUT LOCATIONS AS REQUIRED BY SITE SPECIFIC CONDITIONS.

1.19 WATER HEATER, REFER TO MEP.

1.20 A CONDENSING UNIT SUPPORTED FROM THE GROUND SHALL

REST ON A CONCRETE OR OTHER APPROVED BASE EXTENDING
NOT LESS THAN 3 INCHES ABOVE THE ADJOINING GROUND
LEVEL [CMC 1105.2]

1.21C STANDING SEAM METAL ROOF

1.22 INDOOR UNIT, REFER TO MEP.

1.23 ELECTRICAL SUBPANEL, REFER TO MEP.

AREA: 493 SF

REVISIONS
NO. DATE DESCRIPTION
275

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
2 A-3.1

2.05 2.03

2.08 2.09
1 2
1 A
4"
1'-0"
4"
1'-0" T.O. SHEATING
± 11' - 9"

2.08 AT EA. SIDE
TYP.
38"

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
1 A-3.1

2.05 2.02

2.03 B A
A A
T.O. SHEATING
± 11' - 9"

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
2 A-3.1

2.05 2.02

2.03 2.08
2 1
A
4"
1'-0"
4"
1'-0"
T.O. SHEATING
± 11' - 9"

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
1 A-3.1

2.05 2.02

2.03 A B
A A A
B
T.O. SHEATING
± 11' - 9"

2.08 1.

2. 3.

4. 5.

6. 7.

8. REFER TO GENERAL NOTES SHEET A1.1 FOR ADDITIONAL

REQUIREMENTS

REFERENCE DETAILS FOR ADDITIONAL INFORMATION AND
REQUIREMENTS.

REFERENCE DOOR AND WINDOW SCHEDULES FOR HEIGHT AND
SILL INFORMATION.

REFERENCE FLOOR PLANS AND FRAMING PLANS FOR
LOCATIONS OF DOORS AND WINDOWS.

CONTRACTOR TO VERIFY COLOR OF FINISH MATERIALS PRIOR
TO COMMENCING WORK.

REFER TO ROOF PLAN FOR ROOF OVERHANG DIMENSIONS.

PROVIDE ALUMINUM GUTTERS.

BUILDINGS SHALL HAVE APPROVED ADDRESS IDENTIFICATION

THAT IS LEGIBLE AND PLACED IN A POSITION THAT IS VISIBLE FROM THE STREET OR ROAD FRONTING THE PROPERTY.

ADDRESS IDENTIFICATION CHARACTERS SHALL CONTRAST WITH
THEIR BACKGROUND. ADDRESS NUMBERS SHALL BE ARABIC
NUMBERS OR ALPHABETICAL LETTERS. LETTERS SHALL NOT BE
SPELLED OUT. EACH CHARACTER SHALL BE NOT LESS THAN 4
INCHES IN HEIGHT WITH A STROKE WIDTH OF NOT LESS THAN ½ INCH. WHERE ACCESS IS BY MEANS OF A PRIVATE ROAD AND

THE BUILDING ADDRESS CANNOT BE VIEWED FROM THE PUBLIC

WAY, A MONUMENT, POLE OR OTHER SIGN OR MEANS SHALL BE
USED TO IDENTIFY THE STRUCTURE. ADDRESS IDENTIFICATION
SHALL BE MAINTAINED. [CRC R391.1]

ELEVATION GENERAL SHEET NOTES

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

Sheet #
D
C
B
A
1 2 3 4 5
1 2 3 4 5
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

STUDIO - EXTERIOR ELEVATIONS (CRAFTSMAN)
A-2.1
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026

KEYNOTES

2.02 HORIZONTAL FIBER CEMENT SIDING

2.03 STONE VENEER, MATERIAL SHALL COMPLY WITH CRC R703.8

2.05 ASPHALT SHINGLES

2.08 TRIM

2.09 EXPOSED WOOD FRAMING - PRIMER & 2 COATS EXTERIOR
GRADE PAINT, REQUIRED.

SCALE: 1/4" = 1'-0"
ELEVATION A 1 SCALE: 1/4" = 1'-0"ELEVATION B 2
SCALE: 1/4" = 1'-0"
ELEVATION C 3 SCALE: 1/4" = 1'-0"ELEVATION D 4
0 SCALE:
2' - 0" 4' - 0" 8' - 0"
1/4" = 1' - 0"

REVISIONS
NO. DATE DESCRIPTION
276

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
2 A-3.2

2.06 2.01

2.08 1 2
4"
1'-0"
4"
1'-0"
T.O. SHEATING
± 11' - 9"
A
1 7' - 0"

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
1 A-3.2

2.01 2.08

2.06 2.06
B A
4"
1'-0"
T.O. SHEATING
± 11' - 9"
A A

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
2 A-3.2

2.06 2.01

2.08 2 1
4"
1'-0"
4"
1'-0"
T.O. SHEATING
± 11' - 9"
A

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
1 A-3.2

2.06 2.08

2.01 A B
T.O. SHEATING
± 11' - 9"
A A A
B
7' - 0"

1. 2.

3. 4.

5. 6.

7. 8.

REFER TO GENERAL NOTES SHEET A1.1 FOR ADDITIONAL

REQUIREMENTS

REFERENCE DETAILS FOR ADDITIONAL INFORMATION AND
REQUIREMENTS.

REFERENCE DOOR AND WINDOW SCHEDULES FOR HEIGHT AND
SILL INFORMATION.

REFERENCE FLOOR PLANS AND FRAMING PLANS FOR
LOCATIONS OF DOORS AND WINDOWS.

CONTRACTOR TO VERIFY COLOR OF FINISH MATERIALS PRIOR
TO COMMENCING WORK.

REFER TO ROOF PLAN FOR ROOF OVERHANG DIMENSIONS.

PROVIDE ALUMINUM GUTTERS.

BUILDINGS SHALL HAVE APPROVED ADDRESS IDENTIFICATION

THAT IS LEGIBLE AND PLACED IN A POSITION THAT IS VISIBLE FROM THE STREET OR ROAD FRONTING THE PROPERTY.

ADDRESS IDENTIFICATION CHARACTERS SHALL CONTRAST WITH
THEIR BACKGROUND. ADDRESS NUMBERS SHALL BE ARABIC
NUMBERS OR ALPHABETICAL LETTERS. LETTERS SHALL NOT BE
SPELLED OUT. EACH CHARACTER SHALL BE NOT LESS THAN 4
INCHES IN HEIGHT WITH A STROKE WIDTH OF NOT LESS THAN ½ INCH. WHERE ACCESS IS BY MEANS OF A PRIVATE ROAD AND

THE BUILDING ADDRESS CANNOT BE VIEWED FROM THE PUBLIC

WAY, A MONUMENT, POLE OR OTHER SIGN OR MEANS SHALL BE
USED TO IDENTIFY THE STRUCTURE. ADDRESS IDENTIFICATION
SHALL BE MAINTAINED. [CRC R391.1]

ELEVATION GENERAL SHEET NOTES

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

Sheet #
D
C
B
A
1 2 3 4 5
1 2 3 4 5
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

STUDIO - EXTERIOR ELEVATIONS (MONTEREY)
A-2.2
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026
SCALE: 1/4" = 1'-0"
ELEVATION A 1 SCALE: 1/4" = 1'-0"ELEVATION B 2
SCALE: 1/4" = 1'-0"
ELEVATION C 3 SCALE: 1/4" = 1'-0"ELEVATION D 4

KEYNOTES

2.01 STUCCO. PROVIDE 2 LAYERS OF GRADE D PAPER UNDER
STUCCO WHEN OVER WOOD SHEATHING. [CRC R703.7.3]

2.06 TILE ROOF

2.08 TRIM
0 SCALE:
2' - 0" 4' - 0" 8' - 0"
1/4" = 1' - 0"

REVISIONS
NO. DATE DESCRIPTION
277

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
2 A-3.3

2.07 ALTERNATE:

SHINGLE ROOF

2.04 2.08 2.09
1 2
4"
1'-0"
4"
1'-0"
T.O. SHEATING
± 11' - 9"
A
1 FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
1 A-3.3

2.07 2.04
ALTERNATE:

SHINGLE ROOF

2.08 B A
T.O. SHEATING
± 11' - 9"
A A

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
2 A-3.3

2.07 2.04

2.08 ALTERNATE:

SHINGLE ROOF
2 1
4"
1'-0"
4"
1'-0"
T.O. SHEATING
± 11' - 9"
A

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
1 A-3.3

2.07 2.04

2.08 ALTERNATE:

SHINGLE ROOF
A B
T.O. SHEATING
± 11' - 9"
A A A
B

1. 2.

3. 4.

5. 6.

7. 8.

REFER TO GENERAL NOTES SHEET A1.1 FOR ADDITIONAL

REQUIREMENTS

REFERENCE DETAILS FOR ADDITIONAL INFORMATION AND
REQUIREMENTS.

REFERENCE DOOR AND WINDOW SCHEDULES FOR HEIGHT AND
SILL INFORMATION.

REFERENCE FLOOR PLANS AND FRAMING PLANS FOR
LOCATIONS OF DOORS AND WINDOWS.

CONTRACTOR TO VERIFY COLOR OF FINISH MATERIALS PRIOR
TO COMMENCING WORK.

REFER TO ROOF PLAN FOR ROOF OVERHANG DIMENSIONS.

PROVIDE ALUMINUM GUTTERS.

BUILDINGS SHALL HAVE APPROVED ADDRESS IDENTIFICATION

THAT IS LEGIBLE AND PLACED IN A POSITION THAT IS VISIBLE FROM THE STREET OR ROAD FRONTING THE PROPERTY.

ADDRESS IDENTIFICATION CHARACTERS SHALL CONTRAST WITH
THEIR BACKGROUND. ADDRESS NUMBERS SHALL BE ARABIC
NUMBERS OR ALPHABETICAL LETTERS. LETTERS SHALL NOT BE
SPELLED OUT. EACH CHARACTER SHALL BE NOT LESS THAN 4
INCHES IN HEIGHT WITH A STROKE WIDTH OF NOT LESS THAN ½ INCH. WHERE ACCESS IS BY MEANS OF A PRIVATE ROAD AND

THE BUILDING ADDRESS CANNOT BE VIEWED FROM THE PUBLIC

WAY, A MONUMENT, POLE OR OTHER SIGN OR MEANS SHALL BE
USED TO IDENTIFY THE STRUCTURE. ADDRESS IDENTIFICATION
SHALL BE MAINTAINED. [CRC R391.1]

ELEVATION GENERAL SHEET NOTES

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

Sheet #
D
C
B
A
1 2 3 4 5
1 2 3 4 5
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

STUDIO - EXTERIOR ELEVATIONS (MODERN FARMHOUSE)
A-2.3
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026
SCALE: 1/4" = 1'-0"
ELEVATION A 1 SCALE: 1/4" = 1'-0"ELEVATION B 2
SCALE: 1/4" = 1'-0"
ELEVATION C 3 SCALE: 1/4" = 1'-0"ELEVATION D 4

KEYNOTES

2.04 BOARD AND BATTEN FIBER CEMENT SIDING

2.07 STANDING SEAM METAL ROOF

2.08 TRIM

2.09 EXPOSED WOOD FRAMING - PRIMER & 2 COATS EXTERIOR
GRADE PAINT, REQUIRED.
0 SCALE:
2' - 0" 4' - 0" 8' - 0"
1/4" = 1' - 0"

REVISIONS
NO. DATE DESCRIPTION
278

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
2 A-3.1
LIVING
12 T.O. SHEATING
± 11' - 9"

3.01 3.03

3.02 3.06

3.07 3.03

3.05 A-5.2

1.1 A-5.1
6B
TYP.

3.09 FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
1 A-3.1
LIVING
AB
T.O. SHEATING
± 11' - 9"

3.01 3.01

3.02 3.03

3.06 3.07

3.08 3.04
A-5.2

2.1 A-5.2

3.1 A-5.1
6A

3.09 TYP.

1. 2.

3. 4.

1. 2.

3. 4.

5. 6.

7. 8.

9. REFER TO GENERAL NOTES SHEET A-1.0 FOR ADDITIONAL
REQUIREMENTS.

REFERENCE DETAILS FOR ADDITIONAL INFORMATION AND
REQUIREMENTS.

THE PURPOSE OF THESE DRAWINGS IS TO SHOW
CONSTRUCTION MATERIALS/ASSEMBLIES. FOR SPECIFIC SIZES

AND DETAILS REFER TO ARCHITECTURAL PLANS, ELEVATIONS,
DETAILS, AND STRUCTURAL PLANS.

FIREBLOCKING TO BE LOCATED PER CRC SECTION R302.11:

A. SECTION R302.11 -1.

1. FIREBLOCKING SHALL BE PROVIDED IN CONCEALED SPACES

OF STUD WALLS AND PARTITIONS, INCLUDING FURRED SPACES

AND PARALLEL ROWS OF STUDS OR STAGGERED STUDS, AS
FOLLOWS:

1.1 VERTICALLY AT CEILING AND FLOOR LEVELS

1.2 HORIZONTALLY AT INTERVALS NOT EXCEEDING 10 FT.

2. AT INTERCONNECTIONS BETWEEN CONCEALED VERTICAL

AND HORIZONTAL SPACES SUCH AS SOFFITS, DROP CEILINGS
AND COVE CEILINGS.

3. IN CONCEALED SPACES BETWEEN STAIR STRINGERS AT
THE TOP AND BOTTOM OF THE RUN. ENCLOSED SPACES UNDER
STAIRS SHALL COMPLY WITH SECTION R302.7.

4. AT OPENINGS AROUND VENTS, PIPES, DUCTS, CABLES AND

WIRES AT CEILINGS AND FLOOR LEVEL, WITH AN APPROVED

MATERIAL TO RESIST THE FREE PASSAGE OF FLAME PRODUCTS
OF COMBUSTION. THE MATERIAL FILLING THIS ANNULAR SPACE
SHALL NOT BE REQUIRED TO MEET THE ASTM E136
REQUIREMENTS.

5. FOR THE FIREBLOCKING OF CHIMNEYS AND FIREPLACES,
SEE SECTION R1003.19.

B. SECTION R302.11.1 - FIREBLOCKING MATERIALS SHALL
CONSIST OF THE FOLLOWING MATERIALS:

TWO-INCH NOMINAL LUMBER

TWO THICKNESSES OF ONE-INCH NOMINAL LUMBER WITH

BROKEN LAP JOINTS
THE THICKNESS OF 0.719-INCH WOOD STRUCTURAL PANELS
WITH JOINTS BACKED BY 0.719-INCH WOOD STRUCTURAL
PANELS
THE THICKNESS OF 0.75-INCH PARTICLE BOARD WITH
JOINTS BACKED BY 0.75-INCH PARTICLE BOARD

ONE-HALF-INCH GYPSUM BOARD

ONE-FOURTH-INCH CEMENT-BASED MILLBOARD

BATTS OR BLANKETS OF MINERAL WOOL, MINERAL FIBER

OR OTHER APPROVED MATERIAL INSTALLED IN SUCH A

MANNER AS TO BE SECURELY RETAINED IN PLACE

CELLULOSE INSULATION INSTALLED AS TESTED IN
ACCORDANCE WITH ASTM E119 OR UL 263, FOR THE
SPECIFIC APPLICATION.

THE PURPOSE OF THESE DRAWINGS IS TO SHOW
CONSTRUCTION MATERIALS/ASSEMBLIES. FOR SPECIFIC

SIZES AND DETAILS REFER TO ARCHITECTURAL PLANS,
ELEVATIONS, DETAILS, AND STRUCTURAL PLANS.

5. PROVIDE BLOCKING FOR ALL WALLS WHERE WALL HUNG
EQUIPMENT AND FIXTURES OCCUR.

6. REFERENCE DOOR AND WINDOW SCHEDULES FOR HEIGHT AND
SILL INFORMATION.

7. REFERENCE FLOOR PLANS AND FRAMING PLANS FOR
LOCATIONS OF DOORS AND WINDOWS.

8. REFER TO TITLE 24 REPORT FOR INSULATION INFORMATION
AND REQUIREMENTS.

9. PROVIDE SOUND INSULATION AT BATHROOMS, LAUNDRY
ROOMS, AND PRIMARY BATHROOMS.

SECTION GENERAL SHEET NOTES

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

STUDIO - BUILDING SECTIONS (CRAFTSMAN)
A-3.1
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026

KEYNOTES

3.01 WALL INSULATION, REFER TO TITLE 24 REPORT

3.02 ROOF INSULATION, REFER TO TITLE 24 REPORT. REFER TO DETAILS A, B, AND C ON SHEET A5.2

3.03 WOOD STUD WALL, REFER TO STRUCTURAL DRAWINGS.

3.04 RAFTERS, REFER TO STRUCTURAL DRAWINGS.

3.05 RIDGE BEAM, REFER TO STRUCTURAL DRAWINGS.

3.06 CONCRETE SLAB ON GRADE, REFER TO STRUCTURAL

DRAWINGS

3.07 STRUCTURAL CONCRETE FOOTING, REFER TO STRUCTURAL
DRAWINGS.

3.08 WOOD FRAMING, SEE STRUCTURAL.

3.09 FINISHED GRADE, TYP. FOUNDATION WALLS SHALL EXTEND

ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION
AT ALL POINTS NOT LESS THAN 4 INCHES WHERE MASONRY
VENEER IS USED AND NOT LESS THAN 6 INCHES ELSEWHERE.
[CRC R404.1.6] 0
SCALE:
2' - 0" 4' - 0" 8' - 0"
1/4" = 1' - 0"
SCALE: 1/4" = 1'-0"

SECTION A
1 SCALE: 1/4" = 1'-0"

SECTION B
2 REVISIONS
NO. DATE DESCRIPTION
279

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
2 A-3.2
LIVING
12 T.O. SHEATING
± 11' - 9"
A-5.2

1.2 A-5.1
5B

3.03 3.01

3.03 3.02

3.06 3.07

3.05 TYP. 3.09

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
1 A-3.2
LIVING
AB
T.O. SHEATING
± 11' - 9"
A-5.2

2.2 A-5.2

2.2 A-5.2 4

3.01 3.01

3.02 3.03

3.06 3.07

3.04 A-5.1
5A

3.09 TYP.

1. 2.

3. 4.

1. 2.

3. 4.

5. 6.

7. 8.

9. REFER TO GENERAL NOTES SHEET A-1.0 FOR ADDITIONAL
REQUIREMENTS.

REFERENCE DETAILS FOR ADDITIONAL INFORMATION AND
REQUIREMENTS.

THE PURPOSE OF THESE DRAWINGS IS TO SHOW
CONSTRUCTION MATERIALS/ASSEMBLIES. FOR SPECIFIC SIZES

AND DETAILS REFER TO ARCHITECTURAL PLANS, ELEVATIONS,
DETAILS, AND STRUCTURAL PLANS.

FIREBLOCKING TO BE LOCATED PER CRC SECTION R302.11:

A. SECTION R302.11 -1.

1. FIREBLOCKING SHALL BE PROVIDED IN CONCEALED SPACES

OF STUD WALLS AND PARTITIONS, INCLUDING FURRED SPACES

AND PARALLEL ROWS OF STUDS OR STAGGERED STUDS, AS
FOLLOWS:

1.1 VERTICALLY AT CEILING AND FLOOR LEVELS

1.2 HORIZONTALLY AT INTERVALS NOT EXCEEDING 10 FT.

2. AT INTERCONNECTIONS BETWEEN CONCEALED VERTICAL

AND HORIZONTAL SPACES SUCH AS SOFFITS, DROP CEILINGS
AND COVE CEILINGS.

3. IN CONCEALED SPACES BETWEEN STAIR STRINGERS AT
THE TOP AND BOTTOM OF THE RUN. ENCLOSED SPACES UNDER
STAIRS SHALL COMPLY WITH SECTION R302.7.

4. AT OPENINGS AROUND VENTS, PIPES, DUCTS, CABLES AND

WIRES AT CEILINGS AND FLOOR LEVEL, WITH AN APPROVED

MATERIAL TO RESIST THE FREE PASSAGE OF FLAME PRODUCTS
OF COMBUSTION. THE MATERIAL FILLING THIS ANNULAR SPACE
SHALL NOT BE REQUIRED TO MEET THE ASTM E136
REQUIREMENTS.

5. FOR THE FIREBLOCKING OF CHIMNEYS AND FIREPLACES,
SEE SECTION R1003.19.

B. SECTION R302.11.1 - FIREBLOCKING MATERIALS SHALL
CONSIST OF THE FOLLOWING MATERIALS:

TWO-INCH NOMINAL LUMBER

TWO THICKNESSES OF ONE-INCH NOMINAL LUMBER WITH

BROKEN LAP JOINTS
THE THICKNESS OF 0.719-INCH WOOD STRUCTURAL PANELS
WITH JOINTS BACKED BY 0.719-INCH WOOD STRUCTURAL
PANELS
THE THICKNESS OF 0.75-INCH PARTICLE BOARD WITH
JOINTS BACKED BY 0.75-INCH PARTICLE BOARD

ONE-HALF-INCH GYPSUM BOARD

ONE-FOURTH-INCH CEMENT-BASED MILLBOARD

BATTS OR BLANKETS OF MINERAL WOOL, MINERAL FIBER

OR OTHER APPROVED MATERIAL INSTALLED IN SUCH A

MANNER AS TO BE SECURELY RETAINED IN PLACE

CELLULOSE INSULATION INSTALLED AS TESTED IN
ACCORDANCE WITH ASTM E119 OR UL 263, FOR THE
SPECIFIC APPLICATION.

THE PURPOSE OF THESE DRAWINGS IS TO SHOW
CONSTRUCTION MATERIALS/ASSEMBLIES. FOR SPECIFIC

SIZES AND DETAILS REFER TO ARCHITECTURAL PLANS,
ELEVATIONS, DETAILS, AND STRUCTURAL PLANS.

5. PROVIDE BLOCKING FOR ALL WALLS WHERE WALL HUNG
EQUIPMENT AND FIXTURES OCCUR.

6. REFERENCE DOOR AND WINDOW SCHEDULES FOR HEIGHT AND
SILL INFORMATION.

7. REFERENCE FLOOR PLANS AND FRAMING PLANS FOR
LOCATIONS OF DOORS AND WINDOWS.

8. REFER TO TITLE 24 REPORT FOR INSULATION INFORMATION
AND REQUIREMENTS.

9. PROVIDE SOUND INSULATION AT BATHROOMS, LAUNDRY
ROOMS, AND PRIMARY BATHROOMS.

SECTION GENERAL SHEET NOTES

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

STUDIO - BUILDING SECTIONS (MONTEREY)
A-3.2
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026

KEYNOTES

3.01 WALL INSULATION, REFER TO TITLE 24 REPORT

3.02 ROOF INSULATION, REFER TO TITLE 24 REPORT. REFER TO DETAILS A, B, AND C ON SHEET A5.2

3.03 WOOD STUD WALL, REFER TO STRUCTURAL DRAWINGS.

3.04 RAFTERS, REFER TO STRUCTURAL DRAWINGS.

3.05 RIDGE BEAM, REFER TO STRUCTURAL DRAWINGS.

3.06 CONCRETE SLAB ON GRADE, REFER TO STRUCTURAL

DRAWINGS

3.07 STRUCTURAL CONCRETE FOOTING, REFER TO STRUCTURAL
DRAWINGS.

3.09 FINISHED GRADE, TYP. FOUNDATION WALLS SHALL EXTEND

ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION
AT ALL POINTS NOT LESS THAN 4 INCHES WHERE MASONRY
VENEER IS USED AND NOT LESS THAN 6 INCHES ELSEWHERE.
[CRC R404.1.6] 0
SCALE:
2' - 0" 4' - 0" 8' - 0"
1/4" = 1' - 0"
SCALE: 1/4" = 1'-0"

SECTION A
1 SCALE: 1/4" = 1'-0"

SECTION B
2 REVISIONS
NO. DATE DESCRIPTION
280

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
2 A-3.3
LIVING
12 T.O. SHEATING
± 11' - 9"
A-5.2

1.1 A-5.1
4B

3.03 3.01

3.03 3.02

3.06 3.07

3.05 TYP. 3.09

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
1 A-3.3
LIVING
AB
T.O. SHEATING
± 11' - 9"
A-5.2

2.1 A-5.2

3.3 3.01 3.01

3.02 3.03

3.06 3.07

3.08 3.04
A-5.1
4A

3.09 TYP.

1. 2.

3. 4.

1. 2.

3. 4.

5. 6.

7. 8.

9. REFER TO GENERAL NOTES SHEET A-1.0 FOR ADDITIONAL
REQUIREMENTS.

REFERENCE DETAILS FOR ADDITIONAL INFORMATION AND
REQUIREMENTS.

THE PURPOSE OF THESE DRAWINGS IS TO SHOW
CONSTRUCTION MATERIALS/ASSEMBLIES. FOR SPECIFIC SIZES

AND DETAILS REFER TO ARCHITECTURAL PLANS, ELEVATIONS,
DETAILS, AND STRUCTURAL PLANS.

FIREBLOCKING TO BE LOCATED PER CRC SECTION R302.11:

A. SECTION R302.11 -1.

1. FIREBLOCKING SHALL BE PROVIDED IN CONCEALED SPACES

OF STUD WALLS AND PARTITIONS, INCLUDING FURRED SPACES

AND PARALLEL ROWS OF STUDS OR STAGGERED STUDS, AS
FOLLOWS:

1.1 VERTICALLY AT CEILING AND FLOOR LEVELS

1.2 HORIZONTALLY AT INTERVALS NOT EXCEEDING 10 FT.

2. AT INTERCONNECTIONS BETWEEN CONCEALED VERTICAL

AND HORIZONTAL SPACES SUCH AS SOFFITS, DROP CEILINGS
AND COVE CEILINGS.

3. IN CONCEALED SPACES BETWEEN STAIR STRINGERS AT
THE TOP AND BOTTOM OF THE RUN. ENCLOSED SPACES UNDER
STAIRS SHALL COMPLY WITH SECTION R302.7.

4. AT OPENINGS AROUND VENTS, PIPES, DUCTS, CABLES AND

WIRES AT CEILINGS AND FLOOR LEVEL, WITH AN APPROVED

MATERIAL TO RESIST THE FREE PASSAGE OF FLAME PRODUCTS
OF COMBUSTION. THE MATERIAL FILLING THIS ANNULAR SPACE
SHALL NOT BE REQUIRED TO MEET THE ASTM E136
REQUIREMENTS.

5. FOR THE FIREBLOCKING OF CHIMNEYS AND FIREPLACES,
SEE SECTION R1003.19.

B. SECTION R302.11.1 - FIREBLOCKING MATERIALS SHALL
CONSIST OF THE FOLLOWING MATERIALS:

TWO-INCH NOMINAL LUMBER

TWO THICKNESSES OF ONE-INCH NOMINAL LUMBER WITH

BROKEN LAP JOINTS
THE THICKNESS OF 0.719-INCH WOOD STRUCTURAL PANELS
WITH JOINTS BACKED BY 0.719-INCH WOOD STRUCTURAL
PANELS
THE THICKNESS OF 0.75-INCH PARTICLE BOARD WITH
JOINTS BACKED BY 0.75-INCH PARTICLE BOARD

ONE-HALF-INCH GYPSUM BOARD

ONE-FOURTH-INCH CEMENT-BASED MILLBOARD

BATTS OR BLANKETS OF MINERAL WOOL, MINERAL FIBER

OR OTHER APPROVED MATERIAL INSTALLED IN SUCH A

MANNER AS TO BE SECURELY RETAINED IN PLACE

CELLULOSE INSULATION INSTALLED AS TESTED IN
ACCORDANCE WITH ASTM E119 OR UL 263, FOR THE
SPECIFIC APPLICATION.

THE PURPOSE OF THESE DRAWINGS IS TO SHOW
CONSTRUCTION MATERIALS/ASSEMBLIES. FOR SPECIFIC

SIZES AND DETAILS REFER TO ARCHITECTURAL PLANS,
ELEVATIONS, DETAILS, AND STRUCTURAL PLANS.

5. PROVIDE BLOCKING FOR ALL WALLS WHERE WALL HUNG
EQUIPMENT AND FIXTURES OCCUR.

6. REFERENCE DOOR AND WINDOW SCHEDULES FOR HEIGHT AND
SILL INFORMATION.

7. REFERENCE FLOOR PLANS AND FRAMING PLANS FOR
LOCATIONS OF DOORS AND WINDOWS.

8. REFER TO TITLE 24 REPORT FOR INSULATION INFORMATION
AND REQUIREMENTS.

9. PROVIDE SOUND INSULATION AT BATHROOMS, LAUNDRY
ROOMS, AND PRIMARY BATHROOMS.

SECTION GENERAL SHEET NOTES

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

STUDIO - BUILDING SECTIONS (MODERN FARMHOUSE)
A-3.3
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026

KEYNOTES

3.01 WALL INSULATION, REFER TO TITLE 24 REPORT

3.02 ROOF INSULATION, REFER TO TITLE 24 REPORT. REFER TO DETAILS A, B, AND C ON SHEET A5.2

3.03 WOOD STUD WALL, REFER TO STRUCTURAL DRAWINGS.

3.04 RAFTERS, REFER TO STRUCTURAL DRAWINGS.

3.05 RIDGE BEAM, REFER TO STRUCTURAL DRAWINGS.

3.06 CONCRETE SLAB ON GRADE, REFER TO STRUCTURAL

DRAWINGS

3.07 STRUCTURAL CONCRETE FOOTING, REFER TO STRUCTURAL
DRAWINGS.

3.08 WOOD FRAMING, SEE STRUCTURAL.

3.09 FINISHED GRADE, TYP. FOUNDATION WALLS SHALL EXTEND

ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION
AT ALL POINTS NOT LESS THAN 4 INCHES WHERE MASONRY
VENEER IS USED AND NOT LESS THAN 6 INCHES ELSEWHERE.
[CRC R404.1.6] 0
SCALE:
2' - 0" 4' - 0" 8' - 0"
1/4" = 1' - 0"
SCALE: 1/4" = 1'-0"

SECTION A
1 SCALE: 1/4" = 1'-0"

SECTION B
2 REVISIONS
NO. DATE DESCRIPTION
281

INTERIOR

INTERIOR EXTERIOR

SHEATHING

EXTERIOR SHEATHING

INSULATION
SIDING

WOOD FRAMING, SEE
STRUCT.

CORNER TRIM

SIDING AT INSIDE CORNER

SEALANT, EA SIDE
2 LAYERS WEATHER

RESISTIVE BARRIER

STONE VENEER AT OUTSIDE CORNER

EXTERIOR SHEATHING

INSULATION

WOOD FRAMING, SEE
STRUCT.

INTERIOR

SHEATHING

STONE VENEER
2 LAYERS WEATHER

RESISTIVE BARRIER

EXTERIOR INTERIOR

MORTAR SETTING BED

OVER SCRATCH COAT

METAL LATH

EXTERIOR SHEATHING

INSULATION
7/8" THICK STUCCO FINISH:

METAL LATH BELOW

SCRATCH, BROWN AND FINISH
COAT PER CRC R703.7

WOOD FRAMING, SEE
STRUCT.

INTERIOR

SHEATHING

CORNER BEAD

STUCCO AT OUTSIDE CORNER
2 LAYERS WEATHER

RESISTIVE BARRIER

EXTERIOR INTERIOR
NOTE: PROVIDE 2 LAYERS OF GRADE D PAPER UNDER STUCCO WHEN OVER WOOD SHEATHING. [CRC R703.7.3]

INSULATION

INTERIOR

SHEATHING

BASE TRIM

FLASHING
SIDING

FLASHING AND SEALANT
2 LAYERS OF WEATHER

RESISTIVE BARRIER

OVER PLYWOOD
GRADE, MIN 5% SLOPE

WOOD FRAMING,
SEE STRUCT.
8" MIN.

STRUCTURAL CONCRETE

FOUNDATION, SEE
STRUCT.

EXTERIOR SHEATHING

INSULATION

INTERIOR

SHEATHING

FLASHING
2 LAYERS OF WEATHER

RESISTIVE BARRIER

OVER PLYWOOD WOOD FRAMING,
SEE STRUCT.

STRUCTURAL CONCRETE

FOUNDATION, SEE
STRUCT.

EXTERIOR SHEATHING
7/8" THICK STUCCO FINISH:

METAL LATH BELOW

SCRATCH, BROWN AND FINISH
COAT PER CRC R703.7
GRADE, MIN 5% SLOPE
8" MIN.

NOTE: PROVIDE 26 GA (MIN) CORROSION RESISTANT OR PLASTIC WEEP SCREED WITH MINIMUM VERTICAL FLANGE. THE WEEP SCREEN SHALL BE OF A TYPE THAT WILL ALLOW TRAPPED WATER TO DRAIN TO THE EXTERIOR OF THE BUILDING [CRC R703.7.2.1]

INSULATION

INTERIOR

SHEATHING

FLASHING
2 LAYERS OF WEATHER

RESISTIVE BARRIER

WOOD FRAMING, OVER PLYWOOD
SEE STRUCT.

STRUCTURAL CONCRETE

FOUNDATION, SEE
STRUCT.

EXTERIOR SHEATHING

MORTAR SETTING BED

OVER SCRATCH COAT

STONE VENEER
GRADE, MIN 5% SLOPE
MIN.
8"

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

THROUGH PENTRATION @ WALL

GYPSUM BOARD

FILL, VOID OR CAVITY

MATERIALS, RATED TO

MATCH WALL RATING

THROUGH

PENETRANTS
DESIGN NO. U356
BEARING WALL RATING - 1 HR RATING 1 2 3 5 4
1 WOOD STUDS
NOMINAL 2X6 SPACED 16" O.C. WITH (2) 2X4 TOP PLATES (1) 2X4 BOTTOM PLATE. STUDS LATERALLY-BRACED BY WOOD
STRUCTURAL PANEL SHEATHING (ITEM 5) AND

EFFECECTIVELY FIRE STOPPED AT TOP AND BOTTOM OF
WALL.
2 GYPSUM BOARD
ANY 5/8 IN. THICK UL CLASSIFIED GYPSUM BOARD THAT IS
ELIGIBLE FOR USE IN DESIGN NOS. L501, G512 OR U305. NOM 5/8 IN. THICK, 4 FT WIDE, APPLIED VERTICALLY AND NAILED TO STUDS AND BEARING PLATES 7 IN. OC WITH 6D CEMENTCOATED NAILS, 1-7/8 IN. LONG WITH 1/4 IN. DIAM HEAD. 4 BATTS AND BLANKETS
MINERAL FIBER OR GLASS FIBER INSULATION, 3-1/2 IN.

THICK, PRESSURE FIT TO FILL WALL CAVITIES BETWEEN
STUDS AND PLATES. MINERAL FIBER INSULATION TO BE
UNFACED AND TO HAVE A MIN DENSITY OF 3 PCF. GLASS

FIBER INSULATION TO BE FACED WITH ALUMINUM FOIL OR
KRAFT PAPER AND TO HAVE A MIN DENSITY OF 0.9 PCF
(MIN R-13 THERMAL INSULATION RATING)
5 WOOD STRUCTURAL PANEL SHEATHING
MIN 7/16 IN. THICK, 4 FT WIDE WOOD STRUCTURAL PANELS,
MIN GRADE "C-D" OR "SHEATHING". INSTALLED WITH LONG

DIMENSION OF SHEET (STRENGTH AXIS) OR FACE GRAIN OF
PLYWOOD PARALLEL WITH OR PERPENDICULAR TO STUDS.

VERTICAL JOINTS CENTERED ON STUDS. HORIZONTAL JOINTS
BACKED WITH NOM 2 BY 4 IN. WOOD BLOCKING. ATTACHED TO
STUDS ON EXTERIOR SIDE OF WALL WITH 6D CEMENT
COATED BOX NAILS SPACED 6 IN. OC AT PERIMETER OF
PANELS AND 12 IN. OC ALONG INTERIOR STUDS.
6 EXTERIOR FACINGS

INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
INSTALLATION INSTRUCTIONS. ONE OF THE FOLLOWING
EXTERIOR FACINGS IS TO BE APPLIED OVER THE SHEATHING:

D. CEMENTITIOUS STUCCO — PORTLAND CEMENT OR

SYNTHETIC STUCCO SYSTEMS WITH SELF-FURRING METAL
LATH OR ADHESIVE BASE COAT. THICKNESS FROM 3/8 TO 3/4
IN., DEPENDING ON SYSTEM.

H. FIBER-CEMENT SIDING — FIBER-CEMENT EXTERIOR

SIDINGS INCLUDING SMOOTH AND PATTERNED PANEL OR LAP
SIDING.

I. WALL AND PARTITION FACINGS AND ACCESSORIES* —

STONE VENEER IS MORTAR BONDED TO A LATH, SCRATCH

COAT AND WATER RESISTANT BARRIER APPLIED TO

SHEATHING, INSTALLED IN ACCORDANCE WITH THE

MANUFACTURERS INSTALLATION INSTRUCTIONS, AND
MEETING THE REQUIREMENTS OF LOCAL CODE AGENCIES.

NON-BEARING WALL PARTITION INTERSECTION—
(OPTIONAL) TWO NOMINAL 2 BY 4 IN. STUD OR NOMINAL 2 BY
6 IN. STUD NAILED TOGETHER WITH TWO 3IN. LONG 10D
NAILS SPACED A MAX. 16 IN. OC. VERTICALLY AND FASTENED
TO ONE SIDE OF THE MINIMUM 2 BY 4 IN. STUD WITH 3 IN.

LONG 10D NAILS SPACED A MAX 16 IN. OC. VERTICALLY.

INTERSECTION BETWEEN PARTITION WOOD STUDS TO BE
FLUSH WITH THE 2 BY 4 IN. STUDS. THE WALL PARTITION
WOOD STUDS ARE TO BE FRAMED BY WITH A SECOND 2 BY 4
IN. WOOD STUD FASTENED WITH 3 IN. LONG 10D NAILS
SPACED A MAX. 16 IN. OC. VERTICALLY. MAXIMUM ONE NONBEARING WALL PARTITION INTERSECTION PER STUD CAVITY.

NON-BEARING WALL PARTITION STUD DEPTH SHALL BE AT A
MINIMUM EQUAL TO THE DEPTH OF THE BEARING WALL.
3 JOINTS AND FASTENER HEADS

GYPSUM BOARD JOINTS COVERED WITH TAPE AND JOINT
COMPOUND. FASTENER HEADS COVERED WITH JOINT
COMPOUND.

THROUGH PENTRATION @ WALL

FRAMING
6 INSULATION

INTERIOR

SHEATHING

BASE TRIM

FLASHING
SIDING

FLASHING AND SEALANT
2 LAYERS OF WEATHER

RESISTIVE BARRIER

OVER PLYWOOD

CONCRETE WALK SURFACE,
MIN 2% SLOPE

WOOD FRAMING,
SEE STRUCT.

STRUCTURAL CONCRETE

FOUNDATION, SEE
STRUCT.

EXTERIOR SHEATHING
2"
1/2" EXPANSION JOINT

INSULATION

INTERIOR

SHEATHING

FLASHING
2 LAYERS OF WEATHER

RESISTIVE BARRIER

OVER PLYWOOD

CONCRETE WALK SURFACE,
MIN 2% SLOPE

WOOD FRAMING,
SEE STRUCT.

STRUCTURAL CONCRETE

FOUNDATION, SEE
STRUCT.

EXTERIOR SHEATHING
2"
7/8" THICK STUCCO FINISH:

METAL LATH BELOW

SCRATCH, BROWN AND FINISH
COAT PER CRC R703.7
1/2" EXPANSION JOINT
NOTE: PROVIDE 26 GA (MIN) CORROSION RESISTANT OR PLASTIC WEEP SCREED WITH MINIMUM VERTICAL FLANGE. THE WEEP SCREEN SHALL BE OF A TYPE THAT WILL ALLOW TRAPPED WATER TO DRAIN TO THE EXTERIOR OF THE BUILDING [CRC R703.7.2.1]

INSULATION

INTERIOR

SHEATHING

FLASHING
2 LAYERS OF WEATHER

RESISTIVE BARRIER

OVER PLYWOOD

CONCRETE WALK SURFACE,
MIN 2% SLOPE

WOOD FRAMING,
SEE STRUCT.

STRUCTURAL CONCRETE

FOUNDATION, SEE
STRUCT.

EXTERIOR SHEATHING
2"

MORTAR SETTING BED

OVER SCRATCH COAT
1/2" EXPANSION JOINT

STONE VENEER
39 1/4"
32"
39 1/4"
32"
SHOWER

SIDE WALLS BACK WALL
TOILET
39 1/4"
32"
39 1/4"
32"
36" MIN. 54" MIN.

1. 2.

NOTES:

PROVIDE REINFORCEMENT FOR AGING-IN-PLACE DESIGN
AND FALL PREVENTION AS REQUIRED BY CRC R327.1.1

INFORMATION AND/OR DRAWINGS IDENTIFYING THE

LOCATION OF GRAB BAR REINFORCEMENT SHALL BE

PLACED IN THE OPERATION AND MAINTENANCE MANUAL

IN ACCORDANCE WITH THE CALIFORNIA GREEN BUILDING
STANDARDS CODE, CHAPTER 4, DIVISION 4.4.
[R327.1.1.1 CRC]

FRONT SIDE
39 1/4"
32"
39 1/4"
6"

BATHTUB

SIDE WALLS BACK WALL

REINFORCEMENT AREA,
TYP.

1. 2.

NOTES:

WATER CLOSETS SHALL HAVE 15 INCHES TO ANY WALL OR
OBSTRUCTION ON EACH SIDE OF ITS CENTERLINE AND 24-
INCH CLEAR SPACE IN FRONT. [ 402.5 CPC]
SHOWER COMPARTMENTS SHALL BE NOT LESS THAN 1,024

SQUARE INCHES AND ALSO BE CAPABLE OF
ENCOMPASSING A 30-INCH DIAMETER CIRCLE. [ 408.6 CPC]
MIN.
15"
MIN.
15"
ø 2' - 6"
24"

EXTERIOR SHEATHING

INSULATION
SIDING

WOOD FRAMING, SEE
STRUCT.

INTERIOR

SHEATHING

CORNER TRIM

SIDING AT OUTSIDE CORNER
2 LAYERS WEATHER

RESISTIVE BARRIER

EXTERIOR INTERIOR

INTERIOR

INTERIOR EXTERIOR

SHEATHING

EXTERIOR SHEATHING

INSULATION
7/8" THICK STUCCO FINISH:

METAL LATH BELOW SCRATCH,

BROWN AND FINISH COAT PER
CRC R703.7

WOOD FRAMING, SEE
STRUCT.
2 LAYERS WEATHER

RESISTIVE BARRIER

STUCCO AT INTSIDE CORNER
NOTE: PROVIDE 2 LAYERS OF GRADE D PAPER UNDER STUCCO WHEN OVER WOOD SHEATHING. [CRC R703.7.3]

INTERIOR

EXTERIOR INTERIOR

SHEATHING

EXTERIOR SHEATHING

INSULATION

STONE VENEER

WOOD FRAMING, SEE
STRUCT.

STONE VENEER AT INSIDE CORNER
2 LAYERS WEATHER

RESISTIVE BARRIER

MORTAR SETTING BED

OVER SCRATCH COAT
Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

DETAILS
A-5.1
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026
SCALE: 1 1/2" = 1'-0"
PLAN DETAIL - SIDING (INSIDE CORNER) 1A
SCALE: 1 1/2" = 1'-0"

PLAN DETAIL - STONE VENEER (OUTSIDE CORNER)
SCALE: 1 1/2" = 1'-0" 3B PLAN DETAIL - STUCCO (OUTSIDE CORNER) 2B SCALE: 1 1/2" = 1'-0"
BASE DETAILS - SIDING AT GRADE 4B SCALE: 1 1/2" = 1'-0"BASE DETAILS - STUCCO AT GRADE 5B SCALE: 1 1/2" = 1'-0"BASE DETAILS - STONE VENEER AT GRADE 6B

REVISIONS
NO. DATE DESCRIPTION
0 SCALE:
6" 1' - 0" 2' - 0"
1 1/2" = 1' - 0"
SCALE: 1 1/2" = 1'-0"
7 FIRE RESISTIVE 1- HOUR

WOOD FRAMED WALLS
SCALE: 1 1/2" = 1'-0"
BASE DETAILS - SIDING AT PAVED WALK 4A SCALE: 1 1/2" = 1'-0"BASE DETAILS - STUCCO AT PAVED WALK 5A SCALE: 1 1/2" = 1'-0"BASE DETAILS - STONE VENEER AT PAVED WALK 6A SCALE: 1/4" = 1'-0"
9 REINFORCEMENT DETAILS
SCALE: 1/4" = 1'-0"

BATHROOM CLEARANCE DIAGRAMS
8 SCALE: 1 1/2" = 1'-0"
PLAN DETAIL - SIDING (OUTSIDE CORNER) 1B
SCALE: 1 1/2" = 1'-0"
PLAN DETAIL - STUCCO (INSIDE CORNER) 2A SCALE: 1 1/2" = 1'-0"PLAN DETAIL - STONE VENEER (INSIDE CORNER) 3A 282

ROOF SHEATHING

GUTTER WITH GUARD
1"X 12" FASCIA BOARD

TONGUE AND GROOVE SOFFIT

ROOFING FINISH MATERIAL

EXTERIOR WALL FINISH PER

ELEVATION

WEATHER RESISTIVE BARRIER

SHEATHING
CL
26 GA GSM EDGE FLASHING 3"
MIN. LAP OVER UNDERLAYMENT
AND 1" MIN. VERTICAL LAP

OVER EDGEBOARD

PER ROOF PLAN
BLOCKING, TYP.

TRIM (AT CRAFTSMAN STYLE)

GUTTER WITH GUARD
1"x 6" FASCIA BOARD

ROOFING FINISH MATERIAL
CL
PLAN

PER ROOF
26 GA GSM EDGE FLASHING 3"
MIN. LAP OVER UNDERLAYMENT
AND 1" MIN. VERTICAL LAP

OVER EDGEBOARD
BLOCKING, TYP.

EXTERIOR WALL FINISH PER

ELEVATION

WEATHER RESISTIVE BARRIER

SHEATHING

SHEATHING & FRAMING PER

STRUCTURAL
2 X BLOCKING

FASCIA BOARD

ROOFING FINISH

MATERIAL
SOFFIT

PER ROOF PLAN
26 GA GSM EDGE
FLASHING 3" MIN. LAP

OVER UNDERLAYMENT
AND 1" MIN. VERTICAL

LAP OVER EDGEBOARD

EXTERIOR WALL FINISH PER

ELEVATION

WEATHER RESISTIVE

BARRIER

SHEATHING
CL

SHEATHING & FRAMING PER

STRUCTURAL
2 X BLOCKING
1" X 6" FASCIA BOARD
26 GA GSM EDGE
FLASHING 3" MIN. LAP

OVER UNDERLAYMENT
AND 1" MIN. VERTICAL

LAP OVER EDGEBOARD

ROOFING FINISH

MATERIAL
CL

SHEATHING & FRAMING PER

STRUCTURAL
2 X BLOCKING
1"x12" FASCIA BOARD
26 GA GSM EDGE
FLASHING 3" MIN. LAP

OVER UNDERLAYMENT
AND 1" MIN. VERTICAL

LAP OVER EDGEBOARD

ROOFING FINISH MATERIAL
SOFFIT

PER ROOF PLAN

EXTERIOR WALL FINISH PER

ELEVATION

WEATHER RESISTIVE

BARRIER

SHEATHING
CL

SHEATHING & FRAMING PER

STRUCTURAL
2 X BLOCKING
1"x12" FASCIA BOARD
26 GA GSM EDGE
FLASHING 3" MIN. LAP

OVER UNDERLAYMENT
AND 1" MIN. VERTICAL

LAP OVER EDGEBOARD

ROOFING FINISH MATERIAL
SOFFIT

PER ROOF PLAN

EXTERIOR WALL FINISH PER

ELEVATION

WEATHER RESISTIVE

BARRIER

SHEATHING
MAX.
9"
CL

ROOFING FINISH MATERIAL

ROOF SHEATHING AND

FRAMING PER STRUCTURAL
26 GA GSM EDGE FLASHING 3" MIN. LAP
OVER UNDERLAYMENT AND 1" MIN.

VERTICAL LAP OVER EDGEBOARD

FASCIA BOARD
LEDGER BOARD, TYP.

REFER TO STRUCT.
4" MIN.

METAL FLASHING, RETURN UP

WALL BEHIND WEATHER

RESISTIVE BARRIER

EXTERIOR WALL FINISH PER

ELEVATION

SHEATHING

WEATHER RESISTIVE BARRIER

DRIP EDGE
6' -8" MIN

WHEN WALKING SURFACE BELOW
6' -8" MIN

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

ROOF RAFTERS, REF STRUCT.

ROOF SHEATHING

AIR- IMPERMEABLE INSULATION IN

CONTACT WITH SHEATHING WITH

REQ'D R-VALUE

GYPSUM BOARD, REF PLANS
ROOF RAFTERS, REF STRUCT.

ROOF SHEATHING

AIR- IMPERMEABLE INSULATION IN

CONTACT WITH SHEATHING WITH

REQ'D R-VALUE

GYPSUM BOARD, REF PLANS

AIR-PERMEABLE INSULATION

INSTALLED DIRECTLY UNDER THE

STRUCTURAL SHEATHING
ROOF RAFTERS, REF STRUCT.

ROOF SHEATHING

AIR- IMPERMEABLE INSULATION IN

CONTACT WITH SHEATHING WITH
REQ. R-VALUE

GYPSUM BOARD, REF PLANS
Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

ROOF DETAILS
A-5.2
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026
SCALE: 1" = 1'-0"
CRAFTSMAN/ MODERN FARMHOUSE EAVE 1.1
SCALE: 1" = 1'-0"
MONTEREY EAVE 1.2
SCALE: 1" = 1'-0"
CRAFTSMAN/ MODERN FARMHOUSE GABLE 2.1
SCALE: 1" = 1'-0"
MONTEREY GABLE 2.2
SCALE: 1" = 1'-0"
CRAFTSMAN GABLE (FRONT) 3.1
SCALE: 1" = 1'-0"
3 - MODERN FARMHOUSE GABLE (FRONT) 3.3
SCALE: 1" = 1'-0"
4 - MONTEREY AWNING
4 REVISIONS
NO. DATE DESCRIPTION
0 SCALE:
6" 1' - 0" 2' - 0"
1" = 1' - 0"
B SCALE: 1" = 1'-0"

INSULATION AT UNVENTED ROOF ASSEMBLY -

IMPERMEABLE INSULATION ONLY
SCALE: 1" = 1'-0"
INSULATION @ UNVENTED ROOF ASSEMBLY - BOTH TYPES
A
SCALE: 1" = 1'-0"
INSULATION @ UNVENTED ROOF ASSEMBLY - OVER/ UNDER
C
283
B
CD
A
(CRAFTSMAN)
A
(MONTEREY)
A
(MODERN

FARMHOUSE)
6' - 8"
5 1/2" 3' - 0" 5 1/2"
6' - 8"6' - 8"
4 1/2" 3' - 0" 4 1/2" 5 1/2" 3' - 0" 5 1/2"
6' - 8"6' - 8"6' - 8"
1 3/4"
SCHDL
REF 1 3/4" 1 3/4"
SCHDL
REF 1 3/4" 1 3/4"
SCHDL
REF 1 3/4"
TRIM,
TYP.

TRIM,
TYP.

TRIM,
TYP.
4/A-6.1
5/A-6.1
4/A-6.1
5/A-6.1
4/A-6.1
5/A-6.1
A
(MONTEREY)
A
(MODERN FARMHOUSE)
3' - 6" 5 1/2"
A
(CRAFTSMAN)
3 1/2" 3' - 0" 3 1/2"
3 1/2"
3' - 6" 3 1/2"
5 1/2"
3' - 0"
5 1/2"
5 1/2" 3' - 6" 5 1/2"
B
(MONTEREY)
B
(MODERN FARMHOUSE)

HEAD HEIGHT
6' - 8" TYP.

B
(CRAFTSMAN)
5 1/2" 3' - 0" 5 1/2"
5 1/2" 2' - 8"
5 1/2"
3 1/2" 2' - 8" 3 1/2"
3 1/2" 1' - 6" 3 1/2"
5 1/2" 2' - 8" 5 1/2"
5 1/2" 1' - 6" 5 1/2"
5 1/2"
1' - 6"
5 1/2"

HEAD HEIGHT
6' - 8" TYP.

TRIM, TYP.

TRIM, TYP.
1/A-6.1
6/A-6.1
2/A-6.1
1/A-6.1
3/A-6.1
2/A-6.1
1/A-6.1
3/A-6.1
2/A-6.1
1/A-6.1
3/A-6.1
2/A-6.1
1/A-6.1
3/A-6.1
2/A-6.1
1/A-6.1
3/A-6.1
2/A-6.1
NOTE: EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE CLEAR OPENING NOT GREATER THAN 44 INCHES MEASURED FROM THE FINISH FLOOR. [CRC R310.2] SILL 3' - 2" TYP.

1. 2.

3. 4.

5. 6.

A.

B.

C.
a.
b.

D.

E.

F.

7. REFER TO GENERAL NOTES SHEET A1.0 FOR ADDITIONAL
REQUIREMENTS.

REFER TO FLOOR PLANS FOR LOCATION OF DOORS AND
DIRECTION OF DOOR SWING.

CONTRACTOR TO VERIFY EXACT ROUGH OPENING SIZES PRIOR
TO FABRICATION OF ROUGH OPENINGS.

ALL GLAZING, INCLUDING GLAZED DOORS AND GLAZED

OPENINGS WITHIN EXTERIOR DOORS, SHALL BE INSULATING
GLASS UNITS WITH A MINIMUM OF ONE TEMPERED PANE.

TEMPERED GLASS SHALL BE PERMENENTLY IDENTIFIED AND
VISIBLE WHEN THE UNIT IS GLAZED.

EXTERIOR FIRE RATED DOORS SHALL COMPLY WITH ONE OF
THE FOLLOWING PER CBC 2022 708A.3:

THE EXTERIOR SURFACE OR CLADDING SHALL BE OF

NONCUMBUSTIBLE MATERIAL

THE EXTERIOR SURFACE CLADDING SHALL BE OF

IGNITION-RESISTANT MATERIALS

THE EXTERIOR DOOR SHALL BE CONSTRUCTED OF SOLID

CORE WOOD THAT COMPLIES WITH THE FOLLOWING
REQUIREMENTS:

THICK
PANELS SHALL NOT BE LESS THAN 1 ¼” THICK,

EXCEPT FOR THE EXTERIOR PERIMETER OF THE

PANEL THAT SHALL BE PERMITTED TO TAPER TO
A TONGUE NOT LESS THAN 3/8” THICK.

THE EXTERIOR DOOR ASSEMBLY SHALL HAVE A FIRERESISTANCE RATING OF NOT LESS THAN 30 MINUTES WHEN TEST ACCORDING TO NFPA 252.

THE EXTERIOR SURFACE CLADDING SHALL BE TESTED TO

MEET THE PERFORMANCE REQUIREMENTS WHEN TESTED
IN ACCORDANCE WITH ASTM E2707

THE EXTERIOR SURFACE OR CLADDING SHALL BE TESTED

TO MEET THE PERFORMANCE REQUIREMENTS OF SFM
STANDARD 12-7A-1.

GLAZING IN FIXED AND OPERABLE PANELS OF SWINGING,

SLIDING, AND BIFOLD DOORS SHALL BE CONSIDERED TO BE A
HAZARDOUS LOCATION [CRC SECTION R308.4]. PROVIDE
SAFETY GLAZING.

GENERAL DOOR NOTES

1. 2.

3. 4.

5. 6.

7. 8.

9. 10.

11. 12.

13. 14.

A.

B.

C.

D.

REFER TO GENERAL NOTES SHEET A-1.0 FOR ADDITIONAL
REQUIREMENTS.

REFER TO FLOOR PLANS FOR WINDOW LOCATIONS.

REFER TO ELEVATIONS FOR DIRECTION OF OPERATION OF
WINDOWS.

PROVIDE ALL OPERABLE WINDOWS WITH SCREENS.

CONTRACTOR TO VERIFY EXACT ROUGH OPENING SIZES PRIOR
TO FABRICATION OF ROUGH OPENINGS.

REFER TO ENERGY COMPLIANCE REPORTS FOR U-FACTOR,
SHGC AND ADDITIONAL WINDOW REQUIREMENTS.

WINDOWS MUST HAVE A FRAME AND SASH COMPRISED OF

WELDED CORNERS, METAL REINFORCEMENT IN THE INTERLOCK
AREA.

ALL GLAZING SHALL BE INSULATING GLASS UNITS WITH A
MINIMUM OF ONE TEMPERED PANE.

TEMPERED GLASS SHALL BE PERMENENTLY IDENTIFIED AND
VISIBLE WHEN THE UNIT IS GLAZED.

GLAZING IN WALLS ADJACENT TO BATHTUB AND OR SHOWER,

WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS LESS
THAN 60" MEASURED VERTICALLY ABOVE ANY STANDING OR
WALKING SURFACE, SHALL BE SAFETY GLAZING. [CRC SECTION
R308.4.5]

EMERGENCY ESCAPE AND RESCUE WINDOWS SHALL HAVE A

CLEAR OPENING WITH THE BOTTOM OF THE CLEAR OPENING
NOT GREATER THAN 44" AFF, MIN. THE NET CLEAR OPENING FOR EMERGENCY ESCAPE SHALL BE 5.7 S.F. (5 S.F. MIN. AT GROUND FLOOR). MINIMUM NET CLEAR OPENING DIMENSIONS: HEIGHT:
24", WIDTH: 20". [CRC SECTION R310.2]

EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL OPEN

DIRECTLY INTO A PUBLIC WAY, OR TO A YARD OR COURT HAVING A MINIMUM WIDTH OF 36” THAT OPENS TO A PUBLIC WALL [CRC SECTION 310.1]
ALL GLAZING SHALL MEET TITLE 24 ENERGY REQUIREMENTS.

FIRE RATED EXTERIOR WINDOWS AND EXTERIOR GLAZED DOOR

ASSEMBLIES SHALL COMPLY WITH ONE OF THE FOLLOWING
REQUIRMENTS PER CBC 708A.2.1:

BE CONSTRUCTED OF MULTIPANE GLAZING WITH A MINIMUM

OF ONE TEMPERED PANE MEETING THE REQUIREMENTS OF
SECTION 2406 SAFETY GLAZING

BE CONSTRUCTED OF GLASS BLOCK UNITS
HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 20
MINUTES WHEN TESTED ACCORDING TO NFPA 257

BE TESTED TO MEET THE PERFORMANCE REQUIREMENTS
OF SFM STANDARD 12-7A-2.

15. THE LOAD RESISTANCE OF GLASS UNDER UNIFORM LOAD SHALL BE DETERMINED IN ACCORDANCE WITH ASTM E1300.

GENERAL WINDOW NOTES

EXTERIOR SHEATHING
WALL FRAMING. SEE
STRUCT.

EXTERIOR FINISH

MATERIAL

WATER RESISTIVE
BARRIER, MIN 6" OVER

FLASHING
WINDOW

EXTERIOR TRIM

SEALANT AND

BACKER ROD

EXTERIOR INTERIOR

EXTERIOR SHEATHING

WALL FRAMING, SEE
STRUCT.

EXTERIOR FINISH

MATERIAL

WATER RESISTIVE
BARRIER, MIN 6" OVER

FLASHING

DOOR AND FRAME

EXTERIOR TRIM

SEALANT, ALL

SIDES OF TRIM

EXTERIOR INTERIOR

EXTERIOR

SHEATHING

WALL FRAMING
(SEE STRUCT.)

EXTERIOR FINISH

MATERIAL

WATER RESISTIVE

BARRIER
WINDOW

TRIM, SEALANT

ALL SIDES

SEALANT AND

BACKER ROD

EXTERIOR

INTERIOR
DOOR

EXTERIOR

SHEATHING

WALL FRAMING
(SEE STRUCT.)

EXTERIOR FINISH

MATERIAL

WATER RESISTIVE

BARRIER TRIM, SEALANT

ALL SIDES

SEALANT AND

BACKER ROD

EXTERIOR

SHEATHING

WALL FRAMING

EXTERIOR FINISH

MATERIAL

WATER RESISTIVE

BARRIER
WINDOW

SLOPED TRIM

SEALANT AND

BACKER ROD

SILL FLASHING

EXTERIOR

SHEATHING

WALL FRAMING

EXTERIOR FINISH

MATERIAL

WATER RESISTIVE

BARRIER
WINDOW

CONCRETE OR

STONE SILL

SEALANT AND

BACKER ROD

SILL FLASHING

EXTERIOR INTERIOR BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

SHEET METAL FLASHING,

SOLDER ALL JOINTS
TYP.
4" LAP
2" MIN.
1/4"
6" MIN.

FLASHING PAPER, MOISTOP
FLASHING OR EQUAL (9" WIDE
MIN.) O/ NAILING FIN @ TOP OF
WINDOWS (HEAD) TYP. TWO

CONTINUOUS BEADS OF

MOISTOP SEALANT OR EQUAL
UNDER FLASHING PAPER (1) O/
NAILING FIN AND (1) AT TOP OF
FLSHING PAPER TYP.

FLASHING PAPER, SELF
SEALING MEMBRANE, (9" WIDE
MIN., 12" WIDE TYP. AT JAMBS)

O/ WOOD FRAMING AND UNDER

NAILING FIN AT SIDE OF
WINDOWS (JAMB) TYP.

WINDOW
NAILING FIN.
31 22
••••••••9" MOIST STOP FLASHING PAPER TYP. OF FLASHING PAPER

THE ACTUAL NUMBER OF FLASHING PIECES REQUIRED IS DETERMINED BY THE RADIUS OF THE OPENING AND THE SIZE OF THE FLASHING. (9" WIDE FLASHING MIN.) APPLY A CONTINUOUS BEAD OF SEALANT COMPLYING WITH AAMA 800 TO THE BACKSIDE (INTERIOR) OF THE WINDOW MOUNTING FLANGES

AT WINDOW HEAD, JAMBS AND SILL ALL CORROSIVE RESISTANT FASTENERS ARE TO BE NAILED THROUGH FIN NO CLOSER THAN 3" O.C. AND NOT MORE THAN 16" O.C.

FASTENERS SHALL BE WITHIN 10" FROM CORNERS.

NO NAILS SHALL BE BENT OVER THE NAILING FIN TO SECURE WINDOW REFER TO AAMA 2400-10 STANDARD PRACTICE FOR INSTALLATION OF WINDOWS WITH

MOUNTING FLANGES IN STUD CONSTRUCTION FOR ADDITIONAL REQUIREMENTS

PROVIDE SOLID BLOCKING AT ALL FLASHING LOCATIONS
NOTES:
# INDICATES SEQUENCE

FOR INSTALLATION

SHEET METAL FLASHING,

SOLDER ALL JOINTS OR

PROVIDE SELF ADHERING

WATERPROOFING
TYP.
4" LAP
1"
6" 6"
6 3/4"
1/2"

WATER RESISTIVE

BARRIER/ LATH PAPER UP

AND UNDER FLASHING
(6" LAP MIN).
* LOUVER SHALL PROVIDE MINIMUM 100 SQUARE INCHES FOR MAKEUP AIR (CMC 504.4.1) Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

WINDOW AND DOOR SCHEDULES & DETAILS
A-6.1
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026

DOOR SCHEDULE
DOOR

NUMBER TYPE
SIZE
THICK. DOOR MATERIAL
FRAME

HEIGHT WIDTH MATERIAL U-FACTOR SHGC COMMENTS
1A 6' - 8" 3' - 0" 1 3/4" VINYL/GLASS VINYL 0.300 0.23 EXTERIOR, REF GENERAL DOOR NOTE #7 2B 6' - 8" 3' - 0" 1 3/4" HOLLOW WD WD
3C 6' - 8" 2' - 6" 1 3/4" HOLLOW WD WD LOUVERED*
4C 6' - 8" 2' - 8" 1 3/4" HOLLOW WD WD LOUVERED*
5D 6' - 8" 5' - 0" 1 3/4" HOLLOW WD WD

WINDOW SCHEDULE

TYPE HEIGHT WIDTH
HEAD
HEIGHT
FRAME

MATERIAL OPERATION U-FACTOR SHGC COMMENTS
A 3' - 6" 3' - 0" 6' - 8" VINYL CASEMENT 0.300 0.23 B 1' - 6" 2' - 8" 6' - 8" VINYL AWNING 0.300 0.23 SCALE: 1/4" = 1'-0"

DOOR ELEVATIONS
SCALE: 1/4" = 1'-0"

WINDOW ELEVATIONS
0 SCALE:
3" 6" 1' - 0"
3" = 1' - 0"
SCALE: 3" = 1'-0"

WINDOW HEAD
1 SCALE: 3" = 1'-0"

DOOR HEAD
4 SCALE: 3" = 1'-0"

WINDOW JAMB
2 SCALE: 3" = 1'-0"

DOOR JAMB
5 SCALE: 3" = 1'-0"

WINDOW SILL
3 SCALE: 3" = 1'-0"

WINDOW SILL - CRAFTSMAN
6 REVISIONS
NO. DATE DESCRIPTION
SCALE: 3" = 1'-0"

DOOR THRESHOLD FLASHING
8 SCALE: 3" = 1'-0"

WINDOW FLASHING
9 SCALE: 3" = 1'-0"

WINDOW SILL FLASHING
7 284
MECHANICAL/PLUMBING NOTES EXHAUST DUCTS AND DRYER VENTS SHALL BE EQUIPPED WITH BACK DRAFT DAMPERS INSULATE ALL HOT WATER PIPES. CAL ENERGY CODE 150.0(j) (2), and CPC 609.11) SMOKE DETECTORS MUST BE PERMANENTLY WIRED. IN NEW CONSTRUCTION, REQUIRED SMOKE ALARMS SHALL RECEIVE THEIR PRIMARY POWER FROM THE BUILDING WIRING WHERE SUCH WIRING IS SERVED FROM A COMMERCIAL SOURCE AND SHALL BE EQUIPPED WITH A BATTERY BACK-UP. SMOKE ALARMS SHALL EMIT A SIGNAL WHEN THE BATTERIES ARE LOW. WIRING SHALL BE PERMANENT AND WITHOUT A DISCONNECTING SWITCH OTHER THAN AS REQUIRED FOR OVER CURRENT PROTECTION. WHERE WATER CLOSET COMPARTMENT IS INDEPENDENT OF THE BATHROOM OR SHOWER AREA, A FAN WILL BE REQ. IN EACH AREA. BATHROOMS SHALL HAVE AN EXHAUST FAN WITH HUMIDITY CONTROL SENSOR, MIN. 50 CFM CAPACITY. (CRC R303.3.1) THE MAX. AMOUNT OF WATER CLOSETS ON A 3" HORIZONTAL DRAINAGE SYSTEM LINE IS 5 (CPC TABLE 703.2) PROVIDE GAS LINES WITH A MN. CAPACITY OF 200,000BTU FOR WATER HEATER. (CAL ENERGY CODE 150.0(N)). WHERE WHOLE HOUSE FANS ARE USED IN BATHROOM AREAS, THE FAN MUST RUN CONTINUOUSLY AND SHALL NOT BE TIED TO HUMIDITY CONTROL SENSOR. (CAL GREEN 4.506.1) ROOMS CONTAINING BATHTUBS, SHOWERS, SPAS AND SIMILAR FIXTURES SHALL BE PROVIDED WITH AN EXHAUST FAN WITH HUMIDITY CONTROL SENSOR HAVING A MIN. CAPACITY OF 50 CFM DUCTED TO TERMINATE OUTSIDE THE BLDG. ( CRC R303.3, CAL GREEN 4.505.1, CBC 1203 .5.2.1, CMC 402.5 1. 2. 3. 4. 5. 6. 7. 8. 9. 11. 12. SUPPLY AND RETURN AIR DUCTS TO BE INSULATED AT A MIN. OF R-6. (CAL ENERGY CODE TABLE 150.1-A) ENVIRONMENTAL AIR DUCTS SHALL TERMINATE MIN. 3 FEET FROM PROPERTY LINE OR OPENINGS INTO BLDG., AND 10' FROM A FORCED AIR INLET. (CMC 502.2.1) ALL HOSE BIBS ARE TO HAVE VACUUM BREAKERS. (CPC603.5.7) THE MAX. AMOUNT OF WATER CLOSETS ON A 3" VERTICAL DRAINAGE LINE IS 5. (CPC TABLE 703.2) PROVIDE A CONDENSATE DRAIN NO MORE THAN 2" ABOVE THE BASE OF THE WATER HEATER SPACE. (CAL ENERGY CODE 150.0 (N). 10. ISOLATION VALVES ARE REQ. FOR TANKLESS WATER HEATERS ON THE HOT AND COLD SUPPLY LINES WITH HOSE BIBS ON EACH VALVE, TO FLUSH THE HEAT EXCHANGER. (CAL ENERGY CODE 110.3(7). 13. 14. 15. ALL EXHAUST FANS SHALL BE SWITCHED SEPARATELY FROM LIGHTING SYSTEMS. (CENC 150(K) 2B) PLUMBING FIXTURES AND FITTINGS INSTALLED IN RESIDENTIAL BUILDINGS SHALL COMPLY WITH THE PRESCRIPTIVE REQ. OF SECTIONS 4.303.1.1 THROUGH 4.303.1.4.4. PLUMBING FIXTURES AND FITTINGS REQ. IN SECTION 4.303.1 SHALL BE INSTALLED IN ACCORDANCE WITH THE CALIFORNIA PLUMBING CODE AND SHALL MEET THE THE APPLICABLE REFERENCE STANDARDS. 16. 17. 10. 11. 12. 13. 15. 17. WHERE MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE INSTALLED, THE SMOKE ALARMS SHALL BE INTERCONNECTED IN SUCH A MANNER THAT THE ACTIVATION OF ONE ALARM WILL ACTIVATE ALL THE ALARMS IN THE INDIVIDUAL DWELLING UNIT. THE ALARM SHALL BE CLEARLY AUDIBLE IN ALL BEDROOMS OVER BACKGROUND NOISE LEVELS WITH ALL INTERVENING DOORS CLOSED. ALL EXHAUST FANS SHALL BE SWITCHED SEPARATELY FROM LIGHTING SYSTEMS. (CENC 150(K) 2B) A MINIMUM OF ONE HIGH EFFICIENCY LUMINAIRE SHALL BE INSTALLED IN BATHROOM CONTROLLED BY AN OCCUPANT AND VACANCY SENSOR PROVIDING AUTOMATIC -OFF FUNCTIONALLY (CENC 150 .0(K)21) LAUNDRY AREA SHALL AT LEAST 1-20 AMP DEDICATED BRANCH CIRCUIT (CEC 210 .11 (C)(2) A DEDICATED 125V, 20AMP ELECTRICAL RECEPTACLE THAT IS CONNECTED TO THE ELECTRICAL PANEL WITH A 120 240 -VOLT 3 CONDUCTOR, 10 AWG COPPER BRANCH CIRCUIT, WITHIN 3 FEET FROM THE WATER HEATER AND ACCESSIBLE TO THE WATER HEATER WITH NO OBSTRUCTIONS (CENC 150.0(N)1A) ELECTRICAL RECEPTACLE OUTLETS IN BATHROOM MUST BE NO MORE THAN 48 INCHES OR LESS THAN 15-INCHES MEASURE FROM THE FINISHED FLOOR. DOORBELL BUTTON MUST BE INSTALLED NO MORE THAN 48 INCHES FROM EXTERIOR FLOOR. 18. 14. PROVIDE A DEDICATED CIRCUIT FOR THE A.C./FAU (CEC 422.12) LUMINAIRE EFFICACY - ALL INSTALLED LUMINAIRES SHALL MEET THE REQUIREMENTS OF 2022 BUILDING ENERGY EFFICIENCY STANDARDS TABLE 150.0-A PER SECTION 150.0(K). 19. (S) ENERGY STORAGE SYSTEMS (ESS) READY. ALL SINGLE-FAMILY RESIDENCES THAT INCLUDE ONE OR TWO DWELLING UNITS SHALL MEET THE FOLLOWING. ALL ELECTRICAL COMPONENTS SHALL BE INSTALLED IN ACCORDANCE WITH THE CALIFORNIA ELECTRICAL CODE: 1. AT LEAST ONE OF THE FOLLOWING SHALL BE PROVIDED: A. ESS READY INTERCONNECTION EQUIPMENT WITH A MINIMUM BACKED-UP CAPACITY OF 60 AMPS AND A MINIMUM OF FOUR ESS-SUPPLIED BRANCH CIRCUITS, OR B. A DEDICATED RACEWAY FROM THE MAIN SERVICE TO A PANELBOARD (SUBPANEL) THAT SUPPLIES THE BRANCH CIRCUITS IN SECTION 150.0(S)(2). ALL BRANCH CIRCUITS ARE PERMITTED TO BE SUPPLIED BY THE MAIN SERVICE PANEL PRIOR TO THE INSTALLATION OF AN ESS. THE TRADE SIZE OF THE RACEWAY SHALL BE NOT LESS THAN ONE INCH. THE PANELBOARD THAT SUPPLIES THE BRANCH CIRCUITS (SUBPANEL) MUST BE LABELED “SUBPANEL SHALL INCLUDE ALL BACKED-UP LOAD CIRCUITS.” 2. A MINIMUM OF FOUR BRANCH CIRCUITS SHALL BE IDENTIFIED AND HAVE THEIR SOURCE OF SUPPLY COLLOCATED AT A SINGLE PANELBOARD SUITABLE TO BE SUPPLIED BY THE ESS. AT LEAST ONE CIRCUIT SHALL SUPPLY THE REFRIGERATOR, ONE LIGHTING CIRCUIT SHALL BE LOCATED NEAR THE PRIMARY EGRESS, AND AT LEAST ONE CIRCUIT SHALL SUPPLY A SLEEPING ROOM RECEPTACLE OUTLET. 3. THE MAIN PANELBOARD SHALL HAVE A MINIMUM BUSBAR RATING OF 225 AMPS. 4. SUFFICIENT SPACE SHALL BE RESERVED TO ALLOW FUTURE INSTALLATION OF A SYSTEM ISOLATION EQUIPMENT/TRANSFER SWITCH WITHIN 3 FEET OF THE MAIN PANELBOARD. RACEWAYS SHALL BE INSTALLED BETWEEN THE PANELBOARD AND THE SYSTEM ISOLATION EQUIPMENT/TRANSFER SWITCH LOCATION TO ALLOW THE CONNECTION OF BACKUP POWER SOURCE. (U) ELECTRIC COOKTOP READY. SYSTEMS USING GAS OR PROPANE COOKTOP TO SERVE INDIVIDUAL DWELLING UNITS SHALL INCLUDE THE FOLLOWING: 1. A DEDICATED 240 VOLT BRANCH CIRCUIT WIRING SHALL BE INSTALLED WITHIN 3 FEET FROM THE COOKTOP AND ACCESSIBLE TO THE COOKTOP WITH NO OBSTRUCTIONS. THE BRANCH CIRCUIT CONDUCTORS SHALL BE RATED AT 50 AMPS MINIMUM. THE BLANK COVER SHALL BE IDENTIFIED AS “240V READY.” ALL ELECTRICAL COMPONENTS SHALL BE INSTALLED IN ACCORDANCE WITH THE CALIFORNIA ELECTRICAL CODE. 2. THE MAIN ELECTRICAL SERVICE PANEL SHALL HAVE A RESERVED SPACE TO ALLOW FOR THE INSTALLATION OF A DOUBLE POLE CIRCUIT BREAKER FOR A FUTURE ELECTRIC COOKTOP INSTALLATION. THE RESERVED SPACE SHALL BE PERMANENTLY MARKED AS “FOR FUTURE 240V USE.” (V) ELECTRIC CLOTHES DRYER READY. CLOTHES DRYER LOCATIONS WITH GAS OR PROPANE PLUMBING TO SERVE INDIVIDUAL DWELLING UNITS SHALL INCLUDE THE FOLLOWING: 1. A DEDICATED 240 VOLT BRANCH CIRCUIT WIRING SHALL BE INSTALLED WITHIN 3 FEET FROM THE CLOTHES DRYER LOCATION AND ACCESSIBLE TO THE CLOTHES DRYER LOCATION WITH NO OBSTRUCTIONS. THE BRANCH CIRCUIT CONDUCTORS SHALL BE RATED AT 30 AMPS MINIMUM. THE BLANK COVER SHALL BE IDENTIFIED AS “240V READY.” ALL ELECTRICAL COMPONENTS SHALL BE INSTALLED IN ACCORDANCE WITH THE CALIFORNIA ELECTRICAL CODE. 2. THE MAIN ELECTRICAL SERVICE PANEL SHALL HAVE A RESERVED SPACE TO ALLOW FOR THE INSTALLATION OF A DOUBLE POLE CIRCUIT BREAKER FOR A FUTURE ELECTRIC CLOTHES DRYER INSTALLATION. THE RESERVED SPACE SHALL BE PERMANENTLY MARKED AS “FOR FUTURE 240V USE.” (T) HEAT PUMP SPACE HEATER READY. SYSTEMS USING GAS OR PROPANE FURNACE TO SERVE INDIVIDUAL DWELLING UNITS SHALL INCLUDE THE FOLLOWING: 1. A DEDICATED 240 VOLT BRANCH CIRCUIT WIRING SHALL BE INSTALLED WITHIN 3 FEET FROM THE FURNACE AND ACCESSIBLE TO THE FURNACE WITH NO OBSTRUCTIONS. THE BRANCH CIRCUIT CONDUCTORS SHALL BE RATED AT 30 AMPS MINIMUM. THE BLANK COVER SHALL BE IDENTIFIED AS “240V READY.” ALL ELECTRICAL COMPONENTS SHALL BE INSTALLED IN ACCORDANCE WITH THE CALIFORNIA ELECTRICAL CODE. 2. THE MAIN ELECTRICAL SERVICE PANEL SHALL HAVE A RESERVED SPACE TO ALLOW FOR THE INSTALLATION OF A DOUBLE POLE CIRCUIT BREAKER FOR A FUTURE HEAT PUMP SPACE HEATER INSTALLATION. THE RESERVED SPACE SHALL BE PERMANENTLY MARKED AS “FOR FUTURE 240V USE.” ELECTRIC READY NOTES: 2022 ENERGY EFFICIENCY STANDARDS 150.0 PER CEC 2022 150.0(N).1.A.: IF THE DESIGNATED SPACE IS WITHIN 3 FEET FROM THE WATER HEATER, THEN THIS SPACE SHALL INCLUDE THE FOLLOWING:A DEDICATED 125 VOLT, 20 AMP ELECTRICAL RECEPTACLE THAT IS CONNECTED TO THE ELECTRIC PANEL WITH A 120/240 VOLT 3 CONDUCTOR, 10 AWG COPPER BRANCH CIRCUIT, WITHIN 3 FEET FROM THE WATER HEATER AND ACCESSIBLE TO THE WATER HEATER WITH NO OBSTRUCTIONS; AND · BOTH ENDS OF THE UNUSED CONDUCTOR SHALL BE LABELED WITH THE WORD "SPARE" AND BE ELECTRICALLY ISOLATED; AND· A RESERVED SINGLE POLE CIRCUIT BREAKER SPACE IN THE ELECTRICAL PANEL ADJACENT TO THE CIRCUIT BREAKER FOR THE BRANCH CIRCUIT IN A ABOVE AND LABELED WITH THE WORDS "FUTURE 240V USE"; AND· A CONDENSATE DRAIN THAT IS NO MORE THAN 2 INCHES HIGHER THAN THE BASE OF THE INSTALLED WATER HEATER, AND ALLOWS NATURAL DRAINING WITHOUT PUMP ASSISTANCE. 16. ELECTRICAL NOTES (CONT'D) ALL HOSE CONNECTIONS SHALL BE EQUIPPED WITH NON-REMOVABLE BACK FLOW PREVENTERS. [CPC 603.3.3] 18. ELECTRICAL NOTES 1. 2. 3. 4. 5. 6. 7. RECEPTACLE OUTLET LOCATIONS WILL COMPLY WITH CEC ARTICLE 210.52. & CRC SECTION R327.1.2. TAMPER RESISTANT RECEPTACLE OUTLET LOCATIONS SHALL COMPLY W/ NEC ART. 210-52 AND 550.13 (I.E. ALL RECEPTACLES IN A DWELLING). PER LIGHTING MEASURES 150(K)4 N T-24, THE BEDROOMS, HALLWAY, LIVING ROOM AND OFFICE ARE REQUIRED TO HAVE ANY INSTALLED FIXTURE TO BE ON A DIMMER SWITCH AND THE FIXTURE NEEDS TO BE HIGH EFFICACY. OUTDOOR LIGHTING FIXTURES ARE REQUIRED TO BE HIGH EFFICACY AND CONTROLLED BY A COMBINATION PHOTOCONTROL / MOTION SENSOR. ARC-FAULT PROTECTION FOR ALL OUTLETS (NOT JUST RECEPTACLES) LOCATED IN ROOMS DESCRIBED IN NEC 210.12(A): KITCHENS, LAUNDRY AREAS, FAMILY, LIVING, BEDROOMS, DINING, HALLS, ETC. ALL BRANCH CIRCUITS WILL BE ARC FAULT CIRCUIT PROTECTED PER NEC ART. 210-12(B). MINIMUM OF 2–20-AMP CIRCUITS ARE REQUIRED TO SERVE THE KITCHEN COUNTERTOP OUTLETS. THESE CIRCUITS MAY ALSO SERVE THE PANTRY, BREAKFAST ROOM, DINING ROOM OR OTHER SIMILAR AREAS (210.52(B)(1) CEC) BATHROOM CIRCUITING SHALL BE EITHER: a) A 20 AMPERE CIRCUIT DEDICATED TO EACH BATHROOM. b) AT LEAST ONE 20 AMPERE CIRCUIT SUPPLYING ONLY BATHROOM RECEPTACLE OUTLETS PER NEC ART. 210-11(c)3. ALL 125-VOLT, SINGLE-PHASE, 15- AND 20- AMPERE RECEPTACLES INSTALLED IN BATHROOMS, GARAGES, BASEMENTS, OUTDOORS, LAUNDRY AREA, KITCHEN DISHWASHERS, KITCHEN COUNTERS AND AT WET BAR SINKS, WITHIN 6' OF A SINK, SHALL BE GFCI PROTECTED PER NEC ART. 210-8(A). WEATHER RESISTANT TYPE FOR RECEPTACLES INSTALLED IN DAMP OR WET LOCATIONS (OUTSIDE) NEC 406.4(D)(6) 8. 9. SMOKE DETECTORS MUST BE PERMANENTLY WIRED. IN NEW CONSTRUCTION, REQUIRED SMOKE ALARMS SHALL RECEIVE THEIR PRIMARY POWER FROM THE BUILDING WIRING WHERE SUCH WIRING IS SERVED FROM A COMMERCIAL SOURCE AND SHALL BE EQUIPPED WITH A BATTERY BACK-UP. SMOKE ALARMS SHALL EMIT A SIGNAL WHEN THE BATTERIES ARE LOW. WIRING SHALL BE PERMANENT AND WITHOUT A DISCONNECTING SWITCH OTHER THAN AS REQUIRED FOR OVERCURRENT PROTECTION. A RECEPTACLE OUTLET MUST BE INSTALLED IN EVERY ROOM SO THAT NO POINT ALONG THE WALL SPACE IS MORE THAN 6 FEET, MEASURED HORIZONTALLY ALONG THE FLOOR LINE FROM A RECEPTACLE OUTLET CEC 210.52(A) gas service information:

X SELECTION UPGRADED SERVICE EXISTING SERVICE TO REMAIN NEW SERVICE ALL ELECTRICAL PROPANE "FIRE CLEARANCE REQUIRED" SIZE OF EXISTING SERVICE______________ SIZE OF NEW SERVICE______________________ electrical service information:X SELECTION UPGRADED SERVICE EXISTING SERVICE TO REMAIN (LOAD CALCS FOR THE EXISTING DWELLING IS REQUIRED) NEW SERVICE (NEW ADDRESS REQUIRED) SIZE OF EXISTING SERVICE______________ SIZE OF NEW SERVICE______________________ CONTACT SERVICE PROVIDER, REGARDING ELECTRIC SERVICES TO THIS DETACHED ADU. EXISTING SERVICE UPGRADE OR NEW SERVICE WILL REQUIRE A SEPARATE PERMIT FROM THE CITY OF EASTVALE. SPECIFICATIONS FOR EQUIPMENT SHALL BE KEPT ON SITE TO PROVIDE TO THE CITY OF EASTVALE BUILDING INSPECTOR ELECTRICAL SERVICE CHECKLIST GAS SERVICE CHECKLIST EXAMPLE GAS PIPE DIAGRAM DRAINAGE AND VENT PIPE DIAGRAM 2025_Wildomar revisions project no. sheet no. drawn by date description project City of Wildomar Accessory Dwelling Units 30 January 2026 YSP/CRP/JDJG SEAL 40810 COUNTY CENTER DRIVE SUITE 200 TEMECULA, CA 92591 Consultant MEP.0 Mechanical/ Electrical/ Plumbing General Notes 27 February 2026 285
MECHANICAL / PLUMBING PLAN 1/4"=1'-0" REF.

DW BATHLIVING CLOSET KITCHEN W/D WH MP1 MP1 MP2 MP7 MP6 MP5 MP16 MP13 MP3 MP6 MP14 MP9 MP6 MP8 MP10 MP11 MP4 MP12 MP15 MP9 MP2 MP16 IAQ FAN REF.

DW BATHLIVING CLOSET KITCHEN W/D WH ELECTRICAL PLAN 1/4"=1'-0"E1 E1 E5 E5 E7 E10 E3E8E9 E14 E15 E4 E11 E16 E2 E7 E13 E12 E4 E11 E4 E6 E7 E7 E19 E20 E18 EXHAUST HOOD ABOVE/ TO BE SMOOTH METALLIC INTERIOR SURFACE (CMC 504.3) HOSE BIB CONTROL VALVES IN SHOWERS, BATHTUBS, & BIDETS MUST BE PRESSURE BALANCED OR THERMOSTATIC MIX VALVES WATER CONSERVING FIXTURES: NEW WATER CLOSETS SHALL USE NO MORE THAN 1.28 GAL. OF WATER PER FLUSH, LAVATORIES LIMITED TO 1.2 GPM, KITCHEN FAUCETS NOT TO EXCEED 1.8 GPM AT 60 PSI THEY CAN INCREASE THE FLOW MOMENTARILY BUT CANT EXCEED 2.2GALLONS PER MIN. AT 60 PSI AND MUST DEFAULT TO A MAX. FLOW RATE OF 1.8GALLONS PER MIN AT 60 PSI., AND SHOWERS NOT EXCEED 1.8 GPM. AT 80 PSI AND ALL SHALL BE CERTIFIED TO MEET THE PERFORMANCE CRITERIA OF THE EPA WATERSENCE SPECIFICATIONS FOR SHOWERHEADS. CPC SECTIONS 407, 408, 411, 412 AND SECTION 301.1.1 CALGREEN CODE AND CIVIL CODE 1101.3(c) MINIMUM OF 3 FT CLEARANCE TO ANY OPENING INTO BUILDING FOR EXHAUST FAN TERMINATIONS MP1 CLEARANCE FOR WATER CLOSET TO BE A MIN. OF 24" IN FRONT, AND 15" FROM ITS CENTER TO ANY SIDE WALL OR OBSTRUCTION. (CPC 402.5) NEW NEEA RATED 40 GAL. HEAT PUMP WATER HEATER, RHEEM PROPH40-T2-RH375-SO (40 GA, JA13), TO HAVE CONDENSATE DRAIN INSTALLED NO HIGHER THAN 2' ABOVE THE BASE OF THE HEATER THAT ALSO ALLOWS GRAVITY DRAINAGE INDOOR UNIT MINI SPLIT SYSTEM. OUTDOOR CONDENSING UNIT ON A CONCRETE OR OTHER APPROVED BASE EXTENDING NOT LESS THAN 3 INCHES ABOVE THE ADJOINING GROUND LEVEL TO BE PIPED TO INDOOR HVAC UNIT THE 1/2" SIZE HOT WATER PIPE TO THE KITCHEN SINK AND THE COLD WATER PIPE WITHIN 5' OF WATER HEATER BOTH REQUIRE 1" INSULATION ALL DOMESTIC HOT WATER PIPING TO HAVE THE FOLLOWING MINIMUM INSULATION INSTALLED: 12" PIPE (12" INSULATION); 34" PIPE (1" INSULATION); 1" TO 1-1/2" PIPE (1-1/2" INSULATION) DRYER EXHAUST OUTLET FROM DRYER TO EXHAUST DIRECTLY TO EXTERIOR MAX LENGTH 14' WITH MAXIMUM OF TWO 90° ELBOWS. A LENGTH OF 2 FEET SHALL BE DEDUCTED FOR EACH 90-DEGREE ELBOW IN EXCESS OF TWO. EXHAUST VENT MUST TERMINATE A MIN. OF 3' FROM ANY OPENING. MIN. TYPE 1 CLOTHES DRYER EXHAUST DUCTS SHALL BE OF RIGID METAL & SHALL HAVE SMOOTH INTERIOR SURFACES. THE DIAMETER SHALL BE NOT LESS THAN 4 INCHES NOMINAL (100 MM), & THE THICKNESS SHALL BE NOT LESS THAN 0.016 OF AN INCH (0.406 MM). EXHAUST DUCTS & DRYER VENTS SHALL BE EQUIPPED WITH BACK DRAFT DAMPERS NEW WATER HEATER TO BE INSTALLED ACCORDING TO MANUFACTURER'S REQUIREMENTS WITH T&P RELIEF VALVE AND DISCHARGE PIPE AT EXTERIOR. PROVIDE COMBUSTION AIR, CLEARANCES EQUAL TO ONE OPENING WITHIN 12 INCHES OF THE TOP OF THE ENCLOSURE AND ONE OPENING WITHIN 12 INCHES OF THE BOTTOM OF THE ENCLOSURE. EACH OPENING SHALL HAVE A MINIMUM FREE AREA OF 1 IN2 PER 1,000 BTU, BUT NOT LESS THAN 100 IN2, FOR ENCLOSURES OPENING INDOORS. (506.3 (1) CPC), AND ALL OTHER SPECIFICATIONS PER MANUFACTURER REQUIREMENTS. NEW WATER HEATERS SHALL HAVE ISOLATION VALVES ON BOTH THE COLD AND THE HOT WATER PIPING LEAVING THE WATER HEATER COMPLETE WITH HOSE BIBS OR OTHER FITTINGS ON EACH VALVES FOR FLUSHING THE WATER HEATER WHEN THE VALVES ARE CLOSED MECHANICAL / PLUMBING KEYNOTES MECHANICAL LEGEND EXHAUST FAN: MINIMUM 50 CFM TO BE DUCTED TO THE EXTERIOR AND SHALL PROVIDE FIVE AIR CHANGES PER HOUR; SECTION 1203.3. CFM AND NOISE RATING MAXIMUM 3 SONE FOR INTERMITTENT USE. SHALL BE ENERGY STAR RATED AND CONTROLLED BY A HUMIDISTAT CAPABLE OF AN ADJUSTMENT BETWEEN 50-80% HUMIDITY. ONE OR MORE FANS TO OPERATE CONTINUOUSLY AT REQUIRED CFM PER HERS NOTES ON T1.1(OR GREATER) TO PROVIDE INDOOR AIR QUALITY. AT THE IAQ FAN SWITCH, A LABEL CLEARLY DISPLAYING THE FOLLOWING OR EQUIVALENT TEXT IS REQUIRED: "THIS SWITCH CONTROLS THE INDOOR AIR QUALITY VENTILATION FOR THE HOME. LEAVE IT ON UNLESS THE OUTDOOR AIR QUALITY IS VERY POOR. MECHANICAL DUCT SYSTEMS ARE SIZED, DESIGNED AND EQUIPMENT IS SELECTED USING THE FOLLOWING METHODS.: 1. ESTABLISH HEAT LOSS AND HEAT GAIN VALUES ACCORDING TO ANSI/ ACCA 2 MANUAL J-2011 OR EQUIVALENT. 2. SIZE DUCT SYSTEMS ACCORDING TO ANSI/ ACCA I MANUEL D-2014 OR EQUIVALENT. 3. SELECT HEATING AND COOLING EQUIPMENT ACCORDING TO ANSI/ ACCA 3 MANUAL S-2014 OR EQUIVALENT . RETURN AIR GRILLE, WALL MOUNTED SUPPLY AIR DIFFUSER, WALL MOUNTED THERMOSTAT ELECTRICAL KEYNOTES SUBPANEL LOCATION. ALTERNATE LOCATION TO BE DETERMINED BY OWNER OUTLET AT COUNTER HEIGHT - SHALL COMPLY WITH CEC ARTICLE 210.52(C): IN KITCHENS A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH COUNTER SPACE 12" OR WIDER; SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL IS MORE THAN 24"; ISLAND IN PENINSULAR COUNTERTOPS 12" X 24" LONG (OR GREATER) SHALL HAVE AT LEAST ONCE RECEPTACLE OUTDOOR LIGHTING FIXTURES ARE REQUIRED TO BE HIGH EFFICACY CONTROLLED BY A COMBINATION PHOTOCONTROL / MOTION SENSOR. DEDICATED DUAL GFCI AND AFCI 30 AMP/ 240V POWER FOR ELECTRIC DRYER AND 50 AMP MINIMUM FOR DEDICATED COOKTOP BRANCH CIRCUIT CONDUCTOR. EACH APPLIANCE COVER PLATE IS TO BE LABELED AS ELECTRIC READY. VERIFY REQUIREMENTS WITH APPLIANCE SPECIFICATIONS - ELECTRIC COOKTOP READY REQUIREMENTS ARE TO BE IMPLEMENTED, SEE SHEET MEP.0, ELECTRIC READY 150.0(u) FOR REQUIREMENTS OUTLET DEDICATED FOR INDOOR MINISPLIT UNIT WEATHER RESISTANT TYPE RECEPTACLES GFCI PROTECTED AND SHALL HAVE EXTRA DUTY COVERS OVER-CURRENT FEEDER TO EXTEND TO EXISTING PANEL- ALUMINUM CONDUCTOR BURIED UNDER GROUND WITH AWG ALLOWABLE VOLTAGE DROP PER CEC 250.4 OUTLET FOR NEW ELECTRIC HYBRID HEAT PUMP WATER HEATER WITHIN 3' OF WATER HEATER. SEE ELECTRICAL NOTE #16 ON MEP.0 FOR MORE INFORMATION SEPARATE GROUND ELECTRODE SYSTEM PER CEC 250.4 OUTDOOR CONDENSING UNIT RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE SERVICING OF THE HEATING AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT AND SHALL BE LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET OF THE EQUIPMENT. THIS RECEPTACLE SHALL BE 125-VOLT, SINGLE PHASE, 15 OR 20 AMP RATED GFCI-WP PROTECTED. A DISCONNECTING MEANS CAPABLE OF DISCONNECTING AIR-CONDITIONING AND REFRIGERATING EQUIPMENT, INCLUDING MOTOR-COMPRESSORS AND CONTROLLERS FROM THE CIRCUIT CONDUCTOR IS REQUIRED WITHIN SIGHT FROM THE EQUIPMENT LOCATION PER CEC SECTION 440.11 ELECTRICAL LEGEND SD 3 SWITCHING POWER/DATA FIRE DETECTION LIGHTING TAMPER RESISTANT RECEPTACLE WALL MOUNTED, 110 V DUPLEX U.O.N. ELECTRICAL RECEPTACLE OUTLETS, SWITCHES AND CONTROLS (INCLUDING CONTROLS FOR HEATING, VENTILATION AND AIR CONDITIONING) INTENDED TO BE USED BY OCCUPANTS SHALL BE LOCATED NO MORE THAN 48 INCHES MEASURED FROM THE TOP OF THE OUTLET BOX AND NOT LESS THAN 15 INCHES MEASURED FROM THE BOTTOM OF THE OUTLET BOX ABOVE THE FINISH FLOOR SWITCH, MOUNT AT 43" AFF THREE-WAY SWITCH CEILING FAN/LIGHT COMBO PHONE / DATA / MEDIA CIRCUIT WIRING CEILING, RECESSED, ZERO CLEARANCE IC RATED LED BULB R CEILING, WATERPROOF OUTLET MISC. 4 FOUR-WAY SWITCH CM CARBON MONOXIDE ALARM PERMANENTLY WIRED WITH BATTERY BACKUP PER SECTION R315. ALARMS SHALL BE INTERCONNECTED IN SUCH A MANNER THAT THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL O F THE ALARMS IN THE UNIT. GFI = WATER PROOF GFCI J JUNCTION BOX FLUSH CEILING MOUNTED WALL MOUNTED LIGHT CT = COOKTOP/ GRILL 240 V O = OVEN 240 V MW = MICROWAVE 110 V GD = GARBAGE DISPOSAL 110 V R = RANGE 220V C = COUNTER HEIGHT 6" ABV COUNTER FLOOR MOUNTED DUPLEX RECEPTACLE, VERIFY LOCATION IN FIELD. SPECIAL PURPOSE CONNECTION (VOLTAGE SHALL MATCH APPLIANCE REQ.) D DIMMER SWITCH C MOUNT 6" ABV COUNTER SUB PANEL CEILING, RECESSED, DIRECTIONAL, ZERO CLEARANCE IC RATED LED BULB R IDU = INDOOR UNIT POWER 84" AFF CEILING, RECESSED, ZERO CLEARANCE IC RATED, WATER RESISTANT, LED BULB R W/D = WASHER/DRYER 30AMP/ 240AMP SMOKE DETECTORS PER SECTION R314 DETECTORS SHALL BE PERMANENTLY WIRED WITH BATTERY BACKUP. SOUND AN ALARM AUDIBLE IN ALL SLEEPING AREAS. ALARM DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL O F THE ALARMS IN THE UNIT. SHALL COMPLY WITH THE FOLLOWING: · AT LEAST 3' FROM THE TIP OF THE BLADE OF A CEILING-MOUNTED FAN · NOT LESS THAN 3' FROM THE DOOR OPENING OF A BATHROOM · AT LEAS 20' FROM A COOKING APPLIANCE OR 10' FROM COOKING APPLIANCE WHEN THE ALARM IS AN IONIZING SMOKE ALARM PER NFPA 72 SECTION 29.8.3.4 ITEM 4 · AT LEAST 3' FROM SUPPLY REGISTERS OF A HEATING /COOLING SYSTEM LS LOW VOLTAGE, LANDSCAPE LIGHT FLUORESCENT FIXTURE (USE SHALLOW TYPE WHEN UNDER COUNTER) UNDER COUNTER LIGHTING PER CEC 2022 150.0(N).1.A.: THE DESIGNATED SPACE IS WITHIN 3 FEET FROM THE WATER HEATER AND IS TO COMPLY WITH ELECTRICAL NOTES 15&16 ON SHEET MEP.0 MAIN PANELBOARD LOCATION SHALL HAVE A MINIMUM BUSBAR RATING OF 225 AMPS. DOOR BELL BUTTON MP2 MP3 MP4 MP5 MP6 MP7 MP8 MP9 MP10 MP11 MP12 MP13 MP14 E1E2E3E4E5E6E7E8E9 E10 E11 E12 E13 ALL SINGLE-FAMILY RESIDENCES THAT INCLUDE ONE OR TWO DWELLING UNITS SHALL MEET THE FOLLOWING ENERGY STORAGE SYSTEMS (ESS) READY REQUIREMENTS. ALL ELECTRICAL COMPONENTS SHALL BE INSTALLED IN ACCORDANCE WITH THE CEC. SEE SHEET MEP.0, ELECTRIC READY 150.0(s) FOR REQUIREMENTS E14 E15 SUFFICIENT SPACE SHALL BE RESERVED TO ALLOW FUTURE INSTALLATION OF A SYSTEM ISOLATION EQUIPMENT/TRANSFER SWITCH WITHIN 3FT OF THE MAIN PANELBOARD. RACEWAYS SHALL BE INSTALLED BETWEEN THE PANELBOARD & THE SYSTEM ISOLATION EQUIPMENT/TRANSFER SWITCH LOCATION TO ALLOW THE CONNECTION OF BACKUP POWER SOURCE. RESIDENTIAL ENERGY LIGHTING REQUIREMENTS:ES 150.0(K)/160.5(a) *IN THE KITCHEN, ALL OF THE WATTAGE RATING OF THE FIXTURES MUST BE HIGH EFFICACY. *BATHROOMS, GARAGES, LAUNDRY ROOMS, UTILITY ROOMS AND WALK-IN CLOSETS, AT LEAST ONE INSTALLED LUMINAIRE SHALL BE CONTROLLED BY AN OCCUPANCY OR VACANCY SENSOR PROVIDING AUTOMATIC-OFF FUNCTIONALITY. *ALL THROUGHOUT THE RESIDENCE, INCLUDING THE GARAGE AND EXTERIOR, SHALL BE HIGH EFFICACY. *OUTDOOR LIGHTING: ALL LUMINAIRES MOUNTED TO THE BUILDING OR TO OTHER BUILDINGS ON THE SAME LOT SHALL BE HIGH EFFICACY LUMINAIRES AND SHALL BE CONTROLLED BY A PHOTOCONTROL/MOTION SENSOR COMBINATION (W/ OVERIDE). BATHROOM EXHAUST FAN REQUIREMENTS:PER CGBC 4.506.1- EACH BATHROOM SHALL BE MECHANICALLY VENTILATED AND SHALL COMPLY WITH THE FOLLOWING: 1. FANS SHALL BE ENERGY STAR COMPLIANT AND BE DUCTED TO TERMINATE OUTSIDE THE BUILDING. 2. UNLESS FUNCTIONING AS A COMPONENT OF A WHOLE HOUSE VENTILATION SYSTEM, FANS MUST BE CONTROLLED BY A HUMIDITY CONTROL. A. HUMIDITY CONTROLS SHALL BE CAPABLE OF ADJUSTMENT BETWEEN A RELATIVE HUMIDITY RANGE OF </= 50 % TO A MAXIMUM OF 80 %. A HUMIDITY CONTROL MAY UTILIZE MANUAL OR AUTOMATIC MEANS OF ADJUSTMENT. B. A HUMIDITY CONTROL MAY BE A SEPARATE COMPONENT TO EXHAUST FAN AND IS NOT REQUIRED TO BE INTEGRAL(I.E. BUILT IN) S OCCUPANCY/VACANCY SENSOR A MINIMUM RATING HOOD OVER ELECTRICAL RANGE. INDOOR AIR QUALITY FAN IS REQUIRED IN THE KITCHEN AND SHALL BE HERS VERIFIED PER CEC TABLE 150.0-G: 160 cfm OR 65% CE AT <750 s.f, 130 cfm OR 55% CE AT 750-1000 s.f., 110 cfm OR 50% CE AT 1000-1500 s.f., OR 110 cfm OR 50% CE AT >1500 s.f. PROVIDE PLACARD AT THE IAQ SWITCH WHICH STATES "THIS FAN TO REMAIN ON DURING ALL HOURS THE HOUSE IS OCCUPIED" MP15 WATER HEATERS WITH STORAGE TANKS SHALL BE ANCHORED OR STRAPPED TO RESIST HORIZONTAL DISPLACE DUE TO EARTHQUAKE MOTION. STRAPPING SHALL BE AT POINTS WITH THE UPPER ONE-THIRD AND LOWER ONE-THIRD OF ITS VERTICAL DIMENSIONS. AT THE LOWER POINT, A MIN DISTANCE OF 4 IN SHALL BE MAINTAINED ABOVE THE CONTROLS WITH THE STRAPPING. E16 LIGHTS OVER TUBS AND SHOWERS ARE TO BE MARKED FOR DAMP/WET LOCATIONS WHERE SUBJECT TO SHOWER SPRAY MP16 MAKEUP AIR SHALL BE PROVIDED FOR TYPE I CLOTHES DRYERS IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS AFCI ARC-FAULT CIRCUIT INTERRUPTEPER CEC 210.12 (A) ARC-FAULT CIRCUIT INTERRUPTER CEC 210.12 (A) R AFCI = ARC FAULT CIRCUIT INTERRUPTER 120-VOLT SINGLE PHASE, 15- AND 20 20-AMP BRANCH CIRCUIT PER CEC 210.12 (A) E17 LIGHTING OUTLET CONTAINING A SWITCH OR CONTROLLED BY A WALL SWITCH OR WALL MOUNTED CONTROL DEVICE AT EACH ATTIC ACCESS (210.70 (C) CEC) ATTIC ACCESS PANEL MIN SIZE TO BE 22"X30" AND TO HAVE ONE LIGHTING OUTLET WITH A SWITCH OR CONTROLLED BY A WALL SWITCH OR LISTED WALL MOUNTED CONTROL DEVICE E18 THE ELECTRICAL SERVICE PANEL SHALL HAVE A RESERVED SPACE TO ALLOW FOR THE INSTALLATION OF A DOUBLE POLE CIRCUIT BREAKER FOR THE FUTURE SOLAR ELECTRIC INSTALLATION. (CEnC 110.10 (b)B 4(e)) E19 LOCATION RESERVED FOR ROUTING OF CONDUIT FOR SOLAR ZONE E20 DRWR AFCI UCLV 2025_Wildomar revisions project no. sheet no. drawn by date description project City of Wildomar Accessory Dwelling Units 30 January 2026 YSP/CRP/JDJG SEAL 40810 COUNTY CENTER DRIVE SUITE 200 TEMECULA, CA 92591 Consultant MEP.1 Mechanical/ Electrical/ Plumbing Plans 27 February 2026 286
700. BUILDING CODE: 2022 CALIFORNIA BUILDING CODE AND 2022 CALIFORNIA RESIDENTIAL CODE. 701. SEISMIC DESIGN CRITERIA: SOIL BEARING VALUE 1,500 psf SITE CLASS D (Default) SEISMIC DESIGN CATEGORY D RISK CATEGORY II SEISMIC IMPORTANCE FACTOR 1 Ss: 1.850 Sds: 1.480 Cs: 0.207 S1: 0.670 Sd1: 0.759 R: 6.5 BASIC SEISMIC FORCE RESISTING SYSTEM:BEARING WALL ANALYSIS METHOD: EQUIVALENT LATERAL FORCE PROCEDURE SEE STRUCTURAL CALCULATIONS FOR SD1, SDS, DESIGN BASE SHEAR, Cs, & R FACTORS. 702. WIND DESIGN CRITERIA : WIND SPEED 126 mph RISK CATEGORY II EXPOSURE C INTERNAL PRESSURE COEF 0.18 703. DESIGN LOADING - WORST CASE LOADING: ROOF DL 18 psf l ROOF LL 20 psf PORCH DL 26 psf l PORCH LL 20 psf TRELLIS DL 6 psf l TRELLIS LL 10 psf SOLAR PANELS 3 psf 800. RETROFIT ANCHOR BOLTS FOR MISPLACED HOLDOWNS WITH ALL-THREAD ROD AND SIMPSON SET-XP EPOXY REQUIRE SPECIAL INSPECTION. (NO SPECIAL INSPECTION IS REQUIRED FOR RETROFIT ANCHOR BOLTS OR TITEN HD's WITHOUT A HOLDOWN ATTACHED.) 801. PER CBC 1705.3 SPECIAL INSPECTION IS NOT REQUIRED FOR NON-STRUCTURAL SLABS ON GRADE NOR FOR CONCRETE FOOTINGS THAT SUPPORT 3 STORIES ABOVE GRADE OR LESS. 802. PER CBC 1705.13 SPECIAL INSPECTION IS NOT REQUIRED FOR SEISMIC COMPONENTS FOR DETTACHED ONE- AND TWO-FAMILY DWELLINGS NOT EXCEEDING 2 STORIES ABOVE GRADE. 2. CONCRETE FOUNDATION CONSTRUCTION TYPE SHEARWALL SHEARWALL OR NON-SHEAR NON-SHEAR REPLACEMENT 58 " ALL-THREAD, EPOXY, EMBED 3" OR 5
8 " TITEN HD, EMBED 5
1 2 " MIN. 5
8 " TITEN HD, EMBED 5
1 2" MIN. 0.145 DIA. SHOT PINS SPACED 4 INCHES APART ON SILL. (2) FOR EACH MISSING ANCHOR BOLT. MAX. OF (6) SHOT PINS EVERY 6 FT. 200. 201. 202. 203. 204. 205. 206. 207. 208. 209. 210. 211. 212. 213. 214. 215. 216. THE FIELD INSPECTOR SHALL VERIFY FOUNDATION REQUIREMENTS DURING FOUNDATION INSPECTION. CONCRETE STRENGTH SHALL BE NO LESS THAN 2,500 PSI @ 28 DAYS, OR HIGHER STRENGTH IF NOTED ON THE PLANS. SLAB REINFORCEMENT & FOOTINGS SHALL BE PER STRUCTURAL DETAILS ON SHEET S2.1, CENTERED IN SLAB. REINFORCING BARS TO BE GRADE 40 FOR #3 BARS, GRADE 60 FOR #4 BARS & LARGER PROVIDE WEAKENED PLANE JOINTS FOR CRACK CONTROL (SAWCUT OR TOOLED JOINT) AT 14'-0" O/C MAX. SILL ANCHORAGE AT ALL SHEARWALL LOCATIONS SHALL BE PER THE SHEARWALL SCHEDULE. ALL SHEARWALL ANCHOR BOLTS SHALL RECEIVE A 3" SQUARE X 0.229" THICK WASHER. THE WASHER MAY BE DIAGONALLY SLOTTED (WIDTH >= BOLT DIAMETER + 316", LENGTH<=1 3 4") PROVIDED THAT A STANDARD CUT WASHER IS USED ON TOP OF THE SQUARE WASHER. SHEARWALL ANCHORS SHALL BE PLACED A MIN. OF 1 3 4" FROM THE EDGE OF CONCRETE. EMBEDDED SILL ANCHOR BOLTS AT TYPICAL NON-SHEARWALL CONDITIONS SHALL BE 58 " DIA. MIN. ANCHOR BOLTS WITH A STANDARD CUT WASHER. SPACING SHALL NOT EXCEED 48 INCHES O/C. LOCATE AN ANCHOR BOLT NOT MORE THAN 9 INCHES, OR LESS THAN 4" FROM ENDS AND SPLICES. EACH SILL SHALL HAVE (2) SILL BOLTS MIN. ANCHOR BOLTS SHALL BE EMBEDDED A MIN. OF 7 INCHES INTO CONCRETE. IN A TWO-POUR SYSTEM, ANCHOR BOLTS TO BE EMBEDDED 5 INCHES MIN. INTO FIRST POUR. SEE WOOD FRAMING CONSTRUCTION NOTES FOR ALTERNATE SILL ANCHORAGE. ALL HOLDOWNS SHALL BE PLACED A MINIMUM DIM AS SHOWN IN DETAIL 3&4/S2.1 FROM EXTERIOR CORNER OF SLAB. VERIFY ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS. SUBCONTRACTOR TO VERIFY ALL DIMENSIONS PRIOR TO CONSTRUCTION. IMMEDIATELY NOTIFY HOMEOWNER AND CITY OF WILDOMAR OF ANY DISCREPANCY, TYPICAL. PROVIDE A UFER GROUND FOR ELECTRICAL SYSTEM PER ARTICLE 250.52 N.E.C. ALL SURROUNDING FLAT WORK SHALL BE VERIFIED WITH HOMEOWNER FOR LOCATION AND AMOUNT TO BE POURED. RETROFIT MISPLACED HOLDOWNS AS NOTED BELOW. AT EPOXY ANCHORS USE SIMPSON SET-3G EPOXY PER MANUFACTURERS INSTALLATION REQUIREMENTS AS FOLLOWS: MISPLACED HOLDOWN HDU2 HDU4 HDU5 HDU8 HDU11 RETROFIT  5 8 " EMBEDDED ANCHOR BOLTS AS NOTED BELOW. AT EPOXY ANCHORS USE SIMPSON SET-3G EPOXY PER SIMPSON'S INSTALLATION REQUIREMENTS. LOCATION SLAB EDGE, 1 3/4" DIST. INTERIOR > 6‚" EDGE DIST. ANY OTHER WHEN REQUESTING A BUILDING DEPARTMENT FOUNDATION INSPECTION, HAVE CONTRACTOR DOCUMENTATION IN WRITING FOR THE FOLLOWING: A) THE PAD WAS PREPARED IN ACCORDANCE WITH THE SITE REQUIREMENTS AND CITY OF WILDOMAR APPROVAL. B) THE UTILITY TRENCHES HAVE BEEN PROPERLY BACKFILLED & COMPACTED. C) THE FOUNDATION EXCAVATIONS, EXPANSIVE CHARACTERISTICS AND BEARING CAPACITY COMPLIES WITH THE CITY OF WILDOMAR RECOMMENDATIONS . ALL HOLDOWN ANCHORS & HARDWARE MUST BE TIED IN PLACE PRIOR TO CALLING FOR A FOUNDATION INSPECTION. 3. WOOD FRAMING CONSTRUCTION (CONT.) 312. 313. 314. 315. 316. 305. 306. 307. 308. 309. 310. 311.HOLES, CUTOUTS, AND NOTCHES IN FRAMING MEMBERS: BY VIRTUE OF CODE COMPLIANCE WITH ELECTRICAL AND PLUMBING CODES, HOLES AND NOTCHES WILL INEVITABLY BE MADE IN FRAMING MEMBERS. THE CODE RECOGNIZES AND APPROVES VARIOUS HOLES AND NOTCHES WITHOUT ENGINEERING JUSTIFICATION IN CBC SECTION 2308.8.2. ENGINEERED (PSL, LSL) RECTANGULAR LUMBER BEAMS BEHAVE LIKE ANY OTHER RECTANGULAR SHAPE WHEN NOTCHED OR BORED, SO THE ENGINEER OR ARCHITECT MAY SPECIFY LIMITS WITHOUT MANUFACTURER APPROVAL OTHER HOLES AND NOTCHES ARE ALLOWED AS NOTED BELOW: PSL AND LVL BEAMS: A HOLE 1 INCH IN DIAMETER CAN BE DRILLED ANYWHERE, AND A 2 INCH DIA. HOLE CAN BE DRILLED IN THE MIDDLE THIRD OF THE SPAN IN THE MIDDLE THIRD OF THE DEPTH OF THE BEAM FOR ANY PSL OR LVL BEAM, EXCEPT CANTILEVERED BEAMS AND BEAMS SUPPORTING CONCENTRATED LOADS. HOLES IN THOSE CONDITIONS REQUIRE APPROVAL IN WRITING FROM THE ENGINEER. PSL AND LVL BEAMS: A RAKE CUT (TAPER) AT THE TOP OF THE BEAM AT THE END OF THE SUPPORT IS ALLOWED IF NOTED ON PLANS, TO A MINIMUM OF 4-3/8" AT INSIDE FACE OF SUPPORT. RAKE CUT (TAPER) THAT RESULTS IN A DEPTH AT THE INSIDE FACE OF THE SUPPORT OF 2/3RDS THE BEAM DEPTH IS ALLOWED AT CONDITIONS NOT SPECIFIED. OTHER TAPERED ENDS AND SQUARE NOTCHES IN TOP OR BOTTOM FACE REQUIRE APPROVAL IN WRITING FROM THE ENGINEER OR ARCHITECT. STUDS AND PLATES: SEE STRUCTURAL DETAILS 14 & 15 ON SHEET S2.1 FOR NOTCHING AND BORING. PROVIDE 2X4 TRIMMER & 2X4 KING STUD EACH END OF EACH 4X DROPPED BEAM OR HEADER. PROVIDE DOUBLE TRIMMERS AT EACH 4X10 OR LARGER. PROVIDE DOUBLE TRIMMERS AT EACH 3-1/2 X 7-1/2 PSL OR LSL OR LARGER. PROVIDE 2X6 TRIMMER & 2X6 KING STUD EACH END OF EACH 6X DROPPED BEAM OR HEADER. PROVIDE DOUBLE TRIMMERS AT EACH 6X8 OR LARGER. PROVIDE DOUBLE TRIMMERS AT EACH 5-1/4 X 7-1/2 PSL OR LSL OR LARGER. PROVIDE DOUBLE KING STUDS AT ALL OPENINGS 8'-1" WIDE AND WIDER OR PER PLAN. PROVIDE MINIMUM 2-1/4" BEARING @ EACH END OF EACH FLUSH BEAM OR HEADER WHERE BEARING IS ON TOP PLATE. PROVIDE 2X4 STUD WITHIN 3" OF BEARING POINT. PROVIDE (2) 2X STUDS @ 6X OR LSL OR PSL BEAMS. TYPICAL SHEAR TRANSFER: ROOF TO WALL: CONNECT ROOF FRAMING TO TOP PLATE W/ SIMPSON H1 @ 24" O/C OR A35 OR RBC @ 24" O/C OR PER SHEAR TRANSFER DETAILS. SILL PLATE ANCHORS: GROUND FLOOR / SLAB ON GRADE WALLS: PROVIDE 2X (MIN.) PTDF SILL PLATES. SEE CONCRETE FOUNDATION CONSTRUCTION NOTES 206, 207 & 208 FOR ANCHOR BOLTS. AT INTERIOR NON-SHEAR CONDITIONS, 0.145 SHOT PIN ANCHORS @ 32" O/C MAY BE USED TO CONNECT PARTITIONS AND BEARING WALLS TO SLAB. ALL WOOD SILL PLATES AND ALL WOOD MEMBERS DIRECTLY AGAINST CONCRETE OR MASONRY SHALL BE FOUNDATION GRADE REDWOOD SILLS OR PTDF SILLS, TREATED WITH SODIUM BORATE (SBX/DOT) WHEN INSTALLED IN A DRY OR ENCLOSED ENVIRONMENT. (SODIUM BORATE TREATMENT DOES NOT REQUIRE CORROSION RESISTANT CONNECTORS.) IF OTHER TREATMENTS ARE USED, SEE NOTE 309. FASTENERS IN CONTACT WITH PRESSURE TREATED WOOD: ALL NAILS AND FASTENERS IN CONTACT WITH PRESSURE TREATED LUMBER TREATED WITH ACQ-C, ACQ-D, CA-B, AND CBA-A WITHOUT AMMONIA SHALL BE GALVANIZED PER ASTM A153. ALL NAILS AND FASTENERS IN CONTACT WITH PRESSURE TREATED LUMBER TREATED WITH ACQ-C, ACQ-D, CA-B, AND CBA-A WITH AMMONIA SHALL BE TYPE 303, 304, 305, OR 316 STAINLESS STEEL. WHERE PRESSURE TREATED LUMBER IS INSTALLED IN AN EXTERIOR WET ENVIRONMENT, ALL NAILS AND FASTENERS IN CONTACT WITH THE PRESSURE TREATED LUMBER SHALL BE TYPE 303, 304, 305, OR 316 STAINLESS STEEL. RE-TIGHTEN ALL HOLDOWN ANCHORS JUST PRIOR TO COVERING THE WALL FRAMING. ENGINEERED BEAMS ARE AS FOLLOWS: "PSL" REFERS TO PARALLEL STRAND LUMBER (E=2.0, FB=2900). "LSL" REFERS TO LAMINATED STRAND LUMBER (E=1.55, FB=2325). (E=1.3 & FB=1700 AT LSL CONDITIONS WITH D (DEPTH) < 9" ) "LVL" REFERS TO LAMINATED VENEER LUMBER (E=2.0, FB=2800). "GLB" REFERS TO 24F-1.8E GLU-LAM WITH STANDARD CAMBER, U.N.O. "IJC" ENGINEERED GLU-LAM BEAM MAY BE USED UPON ENGINEER APPROVALS. AN A.I.T.C CERTIFICATE OF COMPLIANCE ISSUED BY A CURRENT ICC APPROVED QUALITY CONTROL AGENCY FOR GLUED LAMINATED WOOD MEMBERS SHALL BE GIVEN TO THE BUILDING INSPECTOR PRIOR TO INSTALLATION. LUMBER SPECIFICATIONS: ALL FRAMING LUMBER SHALL BE DOUGLAS FIR-LARCH. STUDS, PLATES & BLOCKING: 2X4 FRAMING LUMBER NOT LISTED BELOW 92-1/4", 104-1/4", & 116-1/4" 2X4 STUDS 2X4 STUDS OVER 10' 2X4 SILLS & PLATES 2X6 STUDS, SILLS, & PLATES 4X4 STUDS & POSTS 4X6, 6X6, & LARGER STUDS & POSTS 4X4, 4X6 BEAMS & HEADERS 4X8, 4X10, 4X12, 4X14 BEAMS & HEADERS 6X4 BEAMS & HEADERS 6X6 & LARGER BEAM & HEADERS 2X10 AND LARGER RAFTERS AND JOISTS STANDARD GRADE OR BETTER STUD GRADE OR BETTER #2 OR BETTER STANDARD OR BETTER #2 OR BETTER STANDARD OR BETTER OR #1 #1 OR BETTER #2 OR BETTER #1 OR BETTER #2 OR BETTER #1 OR BETTER #1 OR BETTER 3. WOOD FRAMING CONSTRUCTION (CONT.) 3. WOOD FRAMING CONSTRUCTION 300. 301. 302. ROOFING MATERIALS SHALL BE PER ARCHITECTURAL DRAWINGS. ROOF SHEATHING SHALL BE 1932 " OR 5 8 " C-D GRADE, INTERIOR TYPE PLYWOOD WITH EXTERIOR GLUE, OR OSB PANELS. IDENTIFICATION INDEX (24/0) W/ 10D COMMON NAILS @ 6" O/C @ ALL PERIMETER EDGES AND ALL INTERIOR SUPPORTED EDGES AND @ 12" O/C @ ALL INTERMEDIATE SUPPORTS. SEE DETAILS FOR SHEAR AND DRAG NAILING. TYPICAL WALL SHEATHING: INTERIOR SURFACES: WHERE DRYWALL IS SPECIFIED, PROVIDE MIN. 5 8" GYPSUM WALLBOARD W/ 5D COOLER NAILS OR EQUAL @ 6" O/C TO ALL STUDS AND TO TOP & BOTTOM PLATES (UNBLOCKED) AT INTERIOR SIDE OF EXTERIOR WALLS AND AT BOTH SIDES OF ALL INTERIOR WALLS. EXTERIOR SURFACES: SEE PLANS. WHERE "STUCCO" IS SPECIFIED PROVIDE 7 8 " EXTERIOR CEMENT PLASTER OVER WIRE LATH OVER TYPE 15 BUILDING PAPER. LATH ATTACHED TO ALL STUDS AND TOP AND BOTTOM PLATES (OR BLOCKING AS OCCURS) W/ 16 GAGE X 716 " STAPLES @ 6" O/C OR NO. 11 GAGE X 1-1/2" FURRING NAILS WHERE INDICATED ON ELEVATIONS. 303. STRUCTURAL SHEATHING MAY BE EITHER OSB OR PLYWOOD. ANY NOTES REFERRING TO PLYWOOD ALSO APPLIES TO OSB. SHEATHING (WOOD STRUCTURAL PANELS) MUST MEET THE REQUIREMENTS OF DOC PS1 OR PS2 IN ACCORDANCE WITH NDS SDPWS. TOP PLATES SHALL BE DOUBLE 2X W/ WIDTH EQUAL TO STUDS BELOW, W/ (21)16D NAILS MIN. @ MINIMUM 4'-0" LAP SPLICES. USE SIMPSON RPS OR CS16 STRAP EACH SIDE OR ONE SIDE AND TOP WHERE LAP SPLICE IS NOT POSSIBLE. SEE DETAILS FOR NOTCHES, CUT-OUTS AND COMPLETE PLATE BREAKS AT HEATING, VENTING, AND PLUMBING. 6. NAILING SCHEDULE, MINIMUMS (CBC CHAPTER 23, TABLE 2304.10.2) 7. DESIGN CRITERIA 8. STATEMENT OF SPECIAL INSPECTIONS 9. SOILS REPORT 304. 317. 318. 319. ROOF RAFTERS SHALL BE 2X RAFTERS AS NOTED ON STRUCTURAL DRAWINGS EAVES SHALL BE PER ARCHITECTURAL PLANS W/ APPLIED TAILS PER ARCHITECTURAL PLANS. OVERHANG DETAILS ARE NOT SHOWN ON STRUCTURAL PLANS. SEE THE ARCHITECTURAL ROOF PLANS FOR ROOF PITCH AND ADDITIONAL INFORMATION. 320. COMBINE AND GROUP PLUMBING VENTS WHENEVER POSSIBLE TO MINIMIZE ROOF PENETRATIONS. WOOD STRUCT. PANELS, SUBFLOOR, ROOF AND INTERIOR WALL SHTNG TO FRMG AND BLKNG AT CEILING JOISTS, RAFTERS, OR TRUSSES TO TOP PLATE OR OTHER FRAMING, T.N. 4-8d Box, 3-8d Com, 3-10d box, 3-3" x 0.131" nails, 3-3" 14 gage staples BLKNG AT CEILING RAFTERS OR TRUSSES NOT AT WALL TOP PLATE TO RAFTER OR TRUSS, E.N. 2-16d Com, 3-3" x 0.131" nails, 3-3" 14 gage staples FLAT BLKNG TO TRUSS AND WEB, F.N. 16d Com, 3"x.131" nails, 3"x14 gage staples @ 6" o.c BLKNG AT CEILING RAFTERS OR TRUSSES NOT AT WALL TOP PLATE TO RAFTER OR TRUSS, T.N. 2-8d Com, 2-3" x 0.131" nails, 2-3" 14 gage staples CEILING JOISTS TO TOP PLATE, T.N. 4-8d box, 3-8d Com, 3-10d box, 3-3"x.131 nails, 3-3" 14 gage staples CEILING JOISTS NOT ATTACHED TO PARALLEL RAFTER, LAPS OVER PARTITIONS, F.N. PER 2308.7.3.1 3-16d Com, 4-10d box, 4-3" x 0.131" nails, 4-3" 14 gage staples CEILING JOISTS ATTACHED TO PARALLEL RAFTER (HEEL JOINT), F.N. PER 2308.7.3.1 3-16d Com, 4-10d box, 4-3" x 0.131" nails, 4-3" 14 gage staples COLLAR TIE TO RAFTER, F.N. 3-10d Com, 4-10d box, 4-3"x0.131" nails, 4-3" 14 gage staples RAFTER/TRUSS TO TOP PLATE, T.N. PER TABLE 2308.7.3.5 3-10d Com, 3-16d or 4-10d box, 4-3" x 0.131" nails, 4-3" 14 gage staples RAFTERS TO RIDGE VALLEY OR HIP; OR FATER TO 2" RIDGE BEAM TOENAIL 4-16d box, 3-10d Com, 3-16d or 4-10d box, 4-3" x 0.131" nails, 4-3" 14 gage staples ENDNAIL 2-16d Com, 3-16d box, 3-10d box, 3-3" x 0.131" nails, 3-3" 14 gage staples STUD TO STUD (NOT AT BRACED WALL PANELS) 16d Com @ 24" o.c. FN OR 2-10d box, 3" x 0.131" nails, 3-3" 14 gage staples @ 16" o.c. FN STUD TO STUD AT INTERSECTING WALL CORNERS (BRACED WALL) 16d Com @ 16" o.c. FN OR 16d Box, 3" x 0.131" nails, 3-3" 14 gage staples @ 12" o.c. FN BUILT-UP HEADER (2" TO 2"), FN EA. EDGE 16d Com @ 16" o.c OR 16d Box @ 12" o.c. CONT. HEADER TO STUD, T.N. 4-8d Com, 4-10d Box, 5-8d box TOP PLATE TO TOP PLATE 16d Com @ 16" o.c. FN OR 10d Box, 3" x 0.131" nails, 3" 14 gage staples @ 12 o.c. FN TOP PLATE TO TOP PLATE, AT END JOINTS (EACH SIDE OF END JOINT), FACENAIL 24" MIN LAP SPLICE EA. SIDE 8-16d Com, 12-16d Box, 12-10d Box, 12-3" x 0.131" nails, 12-3" 14 gage staples BOTTOM PLATE TO JOIST, RIM, OR BLKG, FACENAIL UNBRACED WALL: 16" o.c. FN 16d Com UNBRACED WALL: 12" o.c. FN 16d Box, 3" x 0.131" nails, 3" 14 gage staples BRACED WALL: 16"o.c. FN 2-16d Com, 3-16d Box,4-3"x.131" nails,4-3" 14 gage staples STUD TO TOP OR BOTTOM PLATE TOENAIL 4-8d Box, 4x10d Box, 4-8d Com, 3-16d Box, 4-3"x0.131" nails, 4-3" 14 gage staples ENDNAIL 3-16d Box, 2-16d Com, 3-10d Box, 3-3"x0.131" nails, 3-3" 14 gage staples TOP PLATES, LAPS AT CORNERS AND INTERSECTION, F.N. 2-16d Com, 3-10d box, 3-3" x 0.131" nails, 3-3" 14 gage staples 1" BRACE TO EACH STUD AND PLATE, F.N. 3-8d Box, 2-8d Com, 2-10d Box, 2-3" x 0.131" nails, 2-3" 14 gage staples 1"x6" SHEATHING TO EACH BEARING, F.N. 3-8d Box, 2-1.75" 16 Gage staples, 2-8d Com, 2-10d Box 1"x8" SHEATHING AND WIDER TO EACH BEARING, F.N. 4-8d box, 4-1.75" 16 Gage staples, 3-8d Com, 3-10d Box JOIST TO SILL, TOP PLATE, OR GIRDER, T.N. 4-8d box, 3-8d Com, 3-10d Box, 3-3" x 0.131" nails, 3-3" 14 gage staples RIM JOIST, BAND JOIST, OR BLOCKING TO TOP PLATE, SILL OR OTHER 8d Box @ 4" o.c. TN OR 8d Com, 10d Box, 3" x 0.131" nails, 3" 14 gage staples @ 6" o.c. TN 1"x6" SUBFLOOR OR LESS TO EACH JOIST, F.N. 2-1.75" Gage Staples, 2-8d Com, 3-10d Box 2" SUBFLOOR TO JOIST OR GIRDER, F.N. or BLIND 3-16d Box, 2-16d Com 2" PLANKS (PLANK & BEAM - FLOOR & ROOF), FACENAIL & EACH BEARING 3-16d Box, 2-16d Com BUILT-UP GIRDERS AND BEAMS, 2" LUMBER LAYERS 32" o.c. FN Top & BTTM STAGGERED ON OPPOSITE SIDES 20d Com 24" o.c. FN Top & BTTM 10d Box, 3"x0.131" nails, 3" 14 gage staples ENDS & SPLICES, FN 2-20d Com, 3-10d Box, 3-3"x0.131" nails, 3-3" 14 gage staples LEDGER SUPPORTING JOISTS/RAFTERS 4-16d Box, 3-16d Com, 4-10d Box, 4-3"X0.131, 4-3" 14ga. STAPLES JOIST TO BAND OR RIM JOIST, END NAIL 3-16d Com, 4-10d Box, 4-3"X0.131, 4-3" 14ga. STAPLES BRIDGING OR BLOCKING TO JOIST, RAFTER OR TRUSS EACH END, T.N. 2-8d Com, 2-10d box, 2-3" x 0.131" nails, 2-3" 14 gage staples FOOTNOTES: a. Nails spaced at 6 inches at intermediate supports where spans are 48 inches or more. For nailing of wood structural panel and particleboard diaphragms and shear walls, refer to Section 2305. Nails for wall sheathing are permitted to be common, box or casing. b. Spacing shall be 6 inches on center on the edges and 12 inches on center at intermediate supports for nonstructural applications. Panel supports at 16 inches (20 inches if strength axis in the long direction of the panel, unless otherwise marked). c. Where a rafter is fastened to an adjacent parallel ceiling joist in accordance with this schedule and the ceiling joist is fastened to the top plate in accordance with this schedule, the number of toenails in the rafter shall be permitted to be reduced by one nail. d. RSRS-01 is a Roof Sheathing Ring Shank nail meeting the specifications in ASTM F1667. e. Tabulated fastener requirements apply where the ultimate design wind speed is less than 140 mph. For wood structural panel roof sheathing attached to gable-end roof framing and to intermediate supports within 48 inches of roof edges and ridges, nails shall be spaced at 4 inches on center where the ultimate design wind speed is greater than 130 mph in Exposure B or greater than 110 mph in Exposure C. Spacing exceeding 6 inches on center at intermediate supports shall be permitted where the fastening is designed per the AWC NDS. e. Fastening is only permitted where the ultimate design wind speed is less than or equal to 110 mph g. Nails and staples are carbon steel meeting the specifications of ASTM F1667. Connections using nails and staples of other materials, such as stainless steel, shall be designed by acceptable engineering practice or approved under Section 104.11. e 16d Com or deformed; or 2
38"x.113" nail (subfloor and wall) 8d Com or deformed (roof) or 2 38" x.113" nail (roof)d 1
3 4" 16 Ga Staple, 716" crown (subfloor and wall) 2
38" x.113"x.266" head nail (roof) 1
3 4" 16 Ga Staple, 716" crown (roof) EDGES (IN) INTERMEDIATE SUPPORTS (IN) 6 6 4
33 f
f e 12
6 833
f
f e 8d Com or deformed (subfloor and wall) 8d Com or deformed (roof) or 2 38" x.113" nail (roof) 2
38" x.113"x.266" head nail, 2"16 Gage staple, 716" crown 6 6 4
e 12
6 8
38"-1
2 " 1932"-3
4 " d
7 8"-1
1 4
" 10d Com or (3"x0.148"); or deformed (2
1 2 x.131"x.281 head) 6 12 OTHER EXTERIOR WALL SHEATHING (FIBERBOARD) 1 1 2" x0.120", galvanized roofing nail ( 716" head dia) or 1 1 4" 16 Ga Staple w/ 716" or 1" crown 1 3 6
2 "b 1
3 4" x0.120", galvanized roofing nail ( 716" head dia) or 1 1 2" 16 Ga Staple w/ 716 25 " or 1" crown 32
"b 3 6 WOOD STRUCTURAL PANELS, COMBINATION SUBFLOOR UNDERLAYMENT TO FRAMING 3 4" & LESS 8d COMMON (2 1
2"x0.131"); or deformed (2"x0.113"); or deformed (2"x0.120") 6 12 78"-1" 8d COMMON (2 1
2"x0.131"); or deformed (2"x0.113"); or deformed (2"x0.120") 6 12 1 1
8"-1
1 4
" 10d COMMON (3"x0.148"); or deformed (2
1 2"x0.131"); or deformed (2
1 2"x0.120") 6 12 PANEL SIDING TO FRAMING
1 2" & LESS 6d corrosion-resistant siding (1
78"x.106"); or 6d corrosion-resistant (2"x.099") 6 12
58 " 8d corrosion-resistant siding (2
38"x0.128"); or 8d corrosion-resistant casing (2
1 2"x0.113") 6 12 INTERIOR PANELING
1 4
" 4d casing (1
1 2"x0.080"); or 4d finish (1
1 2"x0.072") 6 12
38 " 6d casing (2"x0.099"); or 6d finish (2"x.092") - (Panel supports at 24 inches) 6 12 PARTICLEBOARD WALL SHEATHING TO FRAMING BEAM OR JOIST I-JOIST FLOOR JOISTS 1.75 X LSL AND LVL 2.69 X PSL AND LVL 3.5 X PSL AND LVL 5.25 X PSL AND LVL 7 X PSL AND LVL SIMPSON/USP HANGER IUS, IUT, OR ITT HANGERS HU, HUS, OR WPU HU OR HWU HHUS OR HWU HHUS OR HWU HHUS OR HWU 321. 322. 323. 324. 325. WOOD TO WOOD CONNECTORS SHALL BE SIMPSON STRONG TIE OR USP STRUCTURAL CONNECTORS. ALL SPECIFIED CONNECTOR CALL-OUTS ARE SIMPSON CATALOG CALL-OUTS. USP SUBSTITUTIONS SHALL HAVE A CAPACITY EQUAL TO OR GREATER THAN THE SIMPSON CATALOG VALUES. ANY OTHER ICC APPROVED METAL CONNECTOR MAY BE USED UPON APPROVAL BY THE ENGINEER OR ARCHITECT. ICC APPROVED CONNECTORS SHALL BE USED WHERE CONNECTORS ARE SPECIFIED. UNLESS OTHERWISE NOTED, THE FOLLOWING BEAM AND JOIST HANGERS SHALL BE USED: AT BEAM HANGER CALLOUTS, IE HGUS OR HU BEAMS, THE CALLOUT IS ABBREVIATED. THE HANGER WIDTH MAY BE OMITTED TO ALLOW FLEXIBILITY IN ORDERING. EXAMPLE: 2.69 PSL THE CALLOUT MAY READ HGUS12. AN HGUS2.75/12 OR HGUS412 (WITH FILLERS) ARE APPLICABLE. WHERE HANGERS OFFER (MIN) OR (MAX), NAIL TO APPLY (MAX) LOADS. WHERE SHEARWALL LENGTHS ARE SPECIFIED ON THE PLANS, THE LENGTH SHOWN IS A MINIMUM DIMENSION. THE SHEARWALL MAY BE LENGTHENED FOR CONSTRUCTION PURPOSES, BUT SHALL NOT BE REDUCED UNLESS OTHERWISE NOTED. ALL ENGINEERED WOOD PANEL SHEAR (PLYWOOD OR OSB) SHALL BE BLOCKED. THE FOLLOWING HOLES IN SHEARWALLS ARE ALLOWED: A) APPROXIMATELY SQUARE HOLES NOTCHED, PUNCHED, OR CUT THAT ARE LESS THAN 25 SQ. INCHES B) APPROXIMATELY SQUARE HOLES CLEAN CUT OR BORED IN SHEARWALLS THAT ARE LESS THAN 64 SQ. INCHES (ONE HOLE PER 4' OF SHEARWALL.) C) APPROXIMATELY SQUARE HOLES, LESS THAN 64 SQ. INCHES (ONE HOLE PER 8' OF SHEARWALL) WITH ALL EDGES BLOCKED & EDGE NAILED. D) HOLES INDIVIDUALLY APPROVED BY THE ENGINEER OR ARCHITECT OF RECORD. STUDS SHALL BE SPACED @ 16" O/C MAX. UNLESS OTHERWISE SPECIFIED. USE STUD GRADE FULL REPORTS FOUND AT: HTTP://WWW.ICC-ES.ORG 400. 401. 402. 403. PLYWOOD AND OSB PANELS: APA PLYWOOD & OSB--ESR-2586 JOISTS AND RAFTERS AND BEAMS: TRUS-JOIST TJI JOISTS AND PSL, LSL, & LVL--ICC-ES ESR-1387, 1153, BOISE CASCADE BCI JOISTS, VERSA-LAM, & VERSA-STRAND--ICC-ESR-1040, 1336 LOUISIANA PACIFIC JOISTS & BEAMS--ESR-1305, 2403 ROSEBURG JOISTS & BEAMS--ESR-1210, 1251 GLU-LAM BEAMS-- ESR-1940 PACIFIC WOOD TECH - ESR 2909 WOOD CONNECTORS: SIMPSON CONNECTORS--ICC-ES ESR #S 1161, 1622, 1866, 2105, 2203, 2236, 2320, 2549, 2551, 2552, 2553, 2330, 2554, 2555, 2604, 2605, 2606, 2607, 2608, 2611, 2613, 2614, 2615, 2616, 2877, 2920, 3046 IAPMO ER-112, 130, 143, 192, 262 USP LUMBER CONNECTORS--ICC-ES ESR #S 1178, 1280, 1575, 1702, 1781, 1881, 1970, 2104, 2685, 1831, 1465, 2761, 2787, IAPMO ER-200 QUICK DRIVE WOOD SCREWS--ICC-ES ESR-1472 ADHESIVES & ANCHORS: SIMPSON EPOXY-TIE HIGH STRENGTH EPOXY (SET-XP)--ICC-ES ESR-1772, 2508. SIMPSON WEDGE-ALL (WA) WEDGE ANCHORS--ICC-ES ES-1771 SIMPSON TITEN HD--ICC-ESR-1056, 2713 SIMPSON SHOT PINS ICC-ES ESR-2138 HILTI X-DN, X-ZF, X-CF SHOT PINS--ICC-ES ER-1663, 1752, 2269 5. NAILING & FASTENING 16D NAILS AS SHOWN ON THE DETAILS MAY BE COMMON, BOX, OR SINKER NAILS (0.135" MIN. DIA) AS AN ALTERNATE TO THE COMMON AND BOX NAILS SPECIFIED IN THE STRUCTURAL PLANS, THE FOLLOWING "CUTLER" GUN NAILS (OR EQUAL) ARE ACCEPTABLE ALTERNATIVES. ALTERNATE NAILING FOR ROOF SHEATHING: 8D 2 1 2 " X 0.135 WIRE BARBED NAILS BY CUTLER OR EQUAL. ALTERNATE NAILING FOR FLOOR SHEATHING: #8 X 2" SELF SETTING WOOD SCREWS, OR 8D 2 12 " X 0.135 OR 0.148 SCREW SHANK FLOOR NAILS BY CUTLER OR EQUAL SHEAR PANELS WHERE 8D COMMON NAILS ARE SPECIFIED: 10D 2 1 2 " X 0.148" WIRE BARBED NAILS BY CUTLER OR EQUAL 500. 501. 502. 503. 504. NAIL SIZES WIRE GAUGE 1211  101010 911  10998 SIZE OF NAIL 6D8D10D 12D 16D 16D SINKER 6D8D10D 12D 16D SIZE (INCHES) 0.099 0.113 0.128 0.128 0.135 0.148 0.113 0.131 0.148 0.148 0.162 PENETRATION REQUIRED 1" 1" 1" 1" 1" 1" 1" 1" 1 1 4
" 1
1 4
" 1
1 2
" BOX NAILS COMMON NAILS STANDARD LENGTH 2" 2" 3" 3" 3" 3" 2" 2 1 2 " 3" 3" 3" 326. ALL FINISHES, WATERPROOFING, DRAINAGE, AND FIRE-RELATED ELEMENTS ARE BY THE ARCHITECT OF RECORD AND ARE REQUIRED EVEN THOUGH THEY MAY NOT BE SHOWN ON THE STRUCTURAL PLANS AND DETAILS. 4. ICC-ES AND NER APPROVALS EXCEPT AT PLATE HEIGHTS HIGHER THAN 10'-0", THEN USE DF#2 OR BETTER 327. REDWOOD OR PRESSURE-TREATED LUMBER IS TO BE USED AT STRUCTURAL MEMBERS FOR BUILDING, BALCONIES, PORCHES OR SIMILAR APPURTENANCES WHEN EXPOSED TO THE WEATHER WITHOUT ADEQUATE PROTECTION OF A ROOF, EAVE, OVERHANG, OR OTHER COVERING TO PREVENT MOISTURE OR WATER ACCUMULATION. C&C PRESSURES ROOF: GABLE ROOF, PITCH α = 18.3° (-) ZONE 1 (-) ZONE 2 (-) ZONE 3 (+) ALL ZONES AEFFECTIVE = 10 sf 28 sf 30 sf -42.0 psf -39.5 psf -39.3 psf -50.6 psf -87.5 psf 16.5 psf -45.5 psf -76.0 psf 16.0 psf 16.0 psf -75.2 psf -45.1 psf WALLS (-) ZONE 4 (-) ZONE 5 (+) ZONE 4&5 AEFFECTIVE = 10 sf 21 sf 48 sf -1.28 psf -34.7 psf -32.9 psf -1.58 psf 1.00 psf -41.6 psf 31.9 psf 30.1 psf -38.0 psf A SOILS REPORT MAY BE REQUIRED BY THE BUILDING OFFICIAL. IN-LIEU OF THE SOILS REPORT A CONSERVATIVE VALUE FOR THE SOIL BEARING ALLOWABLE OF 1500 PSF HAS BEEN USED IN DESIGN OF THE BUILDING. REPLACEMENT HD HDU2 HDU4 HDU5 HDU8 HDU11 RETROFIT BOLT 5/8" ALL-THREAD, EMBED 6" 5/8" ALL-THREAD, EMBED 6" 5/8" ALL-THREAD, EMBED 9" 7/8" ALL-THREAD, EMBED 9" 1" ALL-THREAD, EMBED 12" MIN EDGE DISTANCE 2" 4.5" 6" 6" 7" 2025_Wildomar revisions project no. sheet no. drawn by date description project City of Wildomar Accessory Dwelling Units 30 January 2026 YSP/CRP/JDJG SEAL 40810 COUNTY CENTER DRIVE SUITE 200 TEMECULA, CA 92591 Consultant Structural Notes & Specifications S0.1 27 February 2026 30 January 2026 30 January 2026 30 January 2026 287
1 2 AB 2x12's @ 24" o/c 2x12's @ 24" o/c
4x12 DF#1 RIDGE BEAM
6x4 5.3' 8' 12' 4x6 POST ECCQ46 1/4"=1'-0" ROOF FRAMING PLAN 6x4 4x6 POST ECCQ46 4 CRAFTSMAN 4 23 S2.2 21 S2.2 22 S2.2 21 S2.2 22S6 24 S2.2 24 S2.2 4 2x12's @ 24" o/c 2x12's @ 24" o/c 2x10's CJ @ 24" o/c 5.2' 6 6x4 33 S2.2 27 S2.2 18 S2.1 TYP. 6x4 6x4 6x4 6x4 6x4
6x4 33 S2.2 5.6' 4 21 S2.2 312x14 LVL CEILING BEAM 4x4 KING POST 24 S2.2 4x12 DF#1 RIDGE BEAM 37 S2.2 4x6 POST 4x6 POST 19 S2.1 5'-0" MIN. BACKSPAN 5'-0" MIN. BACKSPAN 6x8 (MIN.)
6x8 (MIN.)
LUS210 HGRS
2x10 CJ @ 16" o.c. DBL 2x10 19 S2.1 24 S2.2 INSPECTION NOTE: PER HERS SUMMARY FEATURES A QII (QUALITY INSULATION INSTALLATION) INSPECTION IS REQUIRED PRIOR TO DRYWALL INSTALLATION. 11 S2.1 TYP. BOLT TYPE HOLDOWN BEARING OR EXTENT HANGER TO BEAM/LEDGER SHEARWALL & A.B. SPACING PER SCHEDULE OF RAFTERS LEGEND BEARING OR EXTENT OF JOISTS X' * PLEASE REFER TO NOTES 311 & 401 ON S0.1 FOR LUMBER GRADE SPECIFICATIONS. X SHEAR WALL SCHEDULE (ASD VALUES) SHEARWALL DESCRIPTION (See footnotes 1& 4) SHEAR VALUE (PLF) ANCHOR BOLT SPACING 260* 5 8" @ 48" or 12" @ 32" 5 8" @ 32" or 12" @ 24" 5 8" @ 24" or 12" @ 16" 5 8" @ 24" or 12" @ 16" 5 8" @ 16" or 12" @ 12" 5 8" @ 12" or 12" @ 8" SHEAR WALL FOOTNOTES (1) AT PLYWOOD OR OSB PS-1 OR PS-2 RATED PANELS USE COMMON NAILS OR GALVANIZED BOX NAILS (2) LAYERS OF PAPER EXTERIOR PLYWOOD REQUIRED. SHEARSHALL BE APPLIED OVER STUDS @ 16" O/C. GALVANIZED NAILS SHALL NOT BE HOT-DIPPED OR TUMBLED. (2) SILL PLATES & WASHERS SHALL COMPLY WITH THE CONCRETE FOUNDATION CONSTRUCTION AND WOOD FRAMING CONSTRUCTION NOTES. (SEE NOTES #206, 208, 209. 307, 308, 309, ETC.) (3) IN PLYWOOD SHEARWALLS, THE EDGE OF THE 3" SQUARE WASHERS (SEE NOTE #206) SHALL BE 12" OR LESS FROM THE EDGE OF THE SILL PLATE ON THE SIDE OF THE SHEATHING. ALL NAILING SHALL BE 3 8" MIN. FROM THE EDGE OF SHEATHING. (4) WHERE ALLOWABLE SHEAR VALUES EXCEED 350 PLF (SHEARWALL TYPES 6, 7, 8, & 9) ALL FRAMING RECEIVING NAILING FROM ABUTTING PANEL EDGES SHALL NOT BE LESS THAN A SINGLE 3" NOMINAL MEMBER OR (2) 2X MEMBERS NAILED WITH 10D , SPACING EQUAL TO THE E.N. SPACING. PLYWOOD JOINT AND SILL NAILING SHALL BE STAGGERED. (5) IN SHEARWALL TYPES 8 & 9, SILL PLATE NAILING SHALL BE STAGGERED. AT SECOND FLOOR CONDITIONS, PROVIDE ADEQUATE RIM OR BLOCKING TO PREVENT SPLITTING. (*) ALLOWABLE SHEAR VALUES FOR PLYWOOD SHEARWALLS MAY BE INCREASED BY 40% UNDER WIND LOADING. 375* 490* 550* 665* 870* SPACING OF A35/LTP4 FRAMING TO TOP PLATE 32" O.C. 16" O.C. 12" O.C. 12" O.C. 8" O.C. 8" O.C. 3 8" ply. C-D or C-C sheathing, (1) side w/ 8d @ 4" o/c edge, 12" o/c field, blocked (See footnote 3) 3 8" ply. C-D or C-C sheathing, (1) side w/ 8d @ 3" o/c edge, 12" o/c field 3x abutting panel studs blocked (See footnote 3 & 4) 3 8" rated STRUCT 1 panel, (1) side w/ 8d @ 3" o/c edge, 12" o/c field 3x abutting panel studs blocked (See footnote 3 & 4) 15 32" rated STRUCT 1 panel, (1) side w/ 10d @ 3" o/c edge, 12" o/c field 3x abutting panel studs blocked (See footnote 3, 4, & 5) 15 32" rated STRUCT 1 panel, (1) side w/ 10d @ 2" o/c edge, 12" o/c field 3x abutting panel studs blocked (See footnote 3, 4, & 5) 38" ply. C-D or C-C sheathing, (1) side w/ 8d @ 6" o/c edge, 12" o/c field, blocked (See footnote 3 ) 4 5 6 7 8 9 1. 2. 3.5. THE MINIMUM NOMINAL ANCHORBOLT DIAMETER SHALL BE 5/8 INCH NOTE: THIS WILL REQUIRE A MINIMUM DISTANCE FROM THE ENDS OF SILL PLATES TO BE 4" (AND A MAXIMUM OF 12") PLATE WASHERS (MINIMUM SIZE OF 3" x 3" x 1/4") SHALL BE USED ON EACH ANCHOR BOLT. ALL ANCHOR BOLTS, HOLDOWN ANCHORS, & REINF. MUST BE SECURELY TIED IN PLACE PRIOR TO FDTN. INSP. 6. SEE SHT S2.1 FOR TYP. CONCRETE & SLAB DETAILS 1-8 POSTS W/O SPECIFIED BASE SHALL BE NAILED TO BOLTED SILL PLATES W/ (2) 16d T.N. EA SIDE, TYP. PROVIDE CONC SLAB JOINTS AT NO MORE THAN 15 FT EA. WAY 4. 7. FOOTINGS ADJACENT TO SLOPES GREATER THAN OR EQUAL TO 33.3% SHALL COMPLY WITH SETBACK REQUIREMENTS DEFINED IN CBC 1808.7. 8. ALL EXTERIOR STUDS TO BE 2x6 @ 16" O.C. FOUNDATION NOTES INTERIOR HEADER SCHEDULE MAX OPENING MIN. HEADER MIN. GRADE 7'-0" 2x4 DF#2 9'-6" DBL 2x4 11'-0" 4x4 DF#2 DF#2 1 2 AB HDU2 HDU2 HDU2 1'-0" 1'-0"
1'-0" 1'-0" 1/4"=1'-0" 4x6 POST 4" CONC SLAB W/ #4 @ 18" O.C. AT MID-DEPTH OR OVER 10 MIL VAPOR BARRIER OVER 4" BASE ON PAD GRADE fc - 2500 PSI MIN (SPEC INSP NOT REQ'D). A 4-INCH-THICK (101.6 MM) BASE OF 1/2 INCH (12.7 MM) OR LARGER CLEAN AGGREGATE SHALL BE PROVIDED WITH A VAPOR RETARDER IN DIRECT CONTACT WITH CONCRETE AND A CONCRETE MIX DESIGN, WHICH WILL ADDRESS BLEEDING, SHRINKAGE, AND CURLING, SHALL BE USED. FOR ADDITIONAL INFORMATION, SEE AMERICAN CONCRETE INSTITUTE, ACI 302.2R-06. 4 FOUNDATION PLAN CRAFTSMAN 4x6 POST 1 S2.1 1 S2.1 1 S2.1 1 S2.1 8S4 4 3 S2.1 3 S2.1 3 S2.1 3 S2.1 TYP. 4 6 HDU2 HDU2 3 S2.14 HDU2 HDU2 HDU4 HDU4 HDU2 2025_Wildomar revisions project no. sheet no. drawn by date description project City of Wildomar Accessory Dwelling Units 30 January 2026 YSP/CRP/JDJG SEAL 40810 COUNTY CENTER DRIVE SUITE 200 TEMECULA, CA 92591 Consultant CRAFTSMAN FOUNDATION & FRAMING PLANS1.1 27 February 2026 30 January 2026 30 January 2026 30 January 2026 288
1 2 AB 2x12's @ 24" o/c 2x12's @ 24" o/c
4x12 DF#1 RIDGE BEAM
6x4 5.3' 8' 12' 4x6 POST ECCQ46 1/4"=1'-0" ROOF FRAMING PLAN 6x4 4x6 POST ECCQ46 4 4 23 S2.2 21 S2.2 22 S2.2 21 S2.2 22S6 24 S2.2 24 S2.2 FARMHOUSE 4 2x10's CJ @ 24" o/c 5.2' 6 6x4 18 S2.1 TYP. 33 S2.2 6x4 6x4 6x4 6x4 6x4
6x4 5.6' 4 21 S2.2 312x14 LVL CEILING BEAM 4x4 KING POST 24 S2.2 4x12 DF#1 RIDGE BEAM 37 S2.2 4x6 POST 4x6 POST
4x8 (MIN.)
4x8 (MIN.) 5'-0" MIN. BACKSPAN 5'-0" MIN. BACKSPAN 19 S2.1 2x12's @ 24" o/c 2x12's @ 24" o/c 33 S2.2 LUS210 HGRS 2x10 CJ @ 16" o.c. DBL 2x10 19 S2.1 24 S2.2 27 S2.2 4x8 4x4 KP HUC48 HUC48 INSPECTION NOTE: PER HERS SUMMARY FEATURES A QII (QUALITY INSULATION INSTALLATION) INSPECTION IS REQUIRED PRIOR TO DRYWALL INSTALLATION. 11 S2.1 TYP. BOLT TYPE HOLDOWN BEARING OR EXTENT HANGER TO BEAM/LEDGER SHEARWALL & A.B. SPACING PER SCHEDULE OF RAFTERS LEGEND BEARING OR EXTENT OF JOISTS X' * PLEASE REFER TO NOTES 311 & 401 ON S0.1 FOR LUMBER GRADE SPECIFICATIONS. X SHEAR WALL SCHEDULE (ASD VALUES) SHEARWALL DESCRIPTION (See footnotes 1& 4) SHEAR VALUE (PLF) ANCHOR BOLT SPACING 260* 5 8" @ 48" or 12" @ 32" 5 8" @ 32" or 12" @ 24" 5 8" @ 24" or 12" @ 16" 5 8" @ 24" or 12" @ 16" 5 8" @ 16" or 12" @ 12" 5 8" @ 12" or 12" @ 8" SHEAR WALL FOOTNOTES (1) AT PLYWOOD OR OSB PS-1 OR PS-2 RATED PANELS USE COMMON NAILS OR GALVANIZED BOX NAILS (2) LAYERS OF PAPER EXTERIOR PLYWOOD REQUIRED. SHEARSHALL BE APPLIED OVER STUDS @ 16" O/C. GALVANIZED NAILS SHALL NOT BE HOT-DIPPED OR TUMBLED. (2) SILL PLATES & WASHERS SHALL COMPLY WITH THE CONCRETE FOUNDATION CONSTRUCTION AND WOOD FRAMING CONSTRUCTION NOTES. (SEE NOTES #206, 208, 209. 307, 308, 309, ETC.) (3) IN PLYWOOD SHEARWALLS, THE EDGE OF THE 3" SQUARE WASHERS (SEE NOTE #206) SHALL BE 12" OR LESS FROM THE EDGE OF THE SILL PLATE ON THE SIDE OF THE SHEATHING. ALL NAILING SHALL BE 3 8" MIN. FROM THE EDGE OF SHEATHING. (4) WHERE ALLOWABLE SHEAR VALUES EXCEED 350 PLF (SHEARWALL TYPES 6, 7, 8, & 9) ALL FRAMING RECEIVING NAILING FROM ABUTTING PANEL EDGES SHALL NOT BE LESS THAN A SINGLE 3" NOMINAL MEMBER OR (2) 2X MEMBERS NAILED WITH 10D , SPACING EQUAL TO THE E.N. SPACING. PLYWOOD JOINT AND SILL NAILING SHALL BE STAGGERED. (5) IN SHEARWALL TYPES 8 & 9, SILL PLATE NAILING SHALL BE STAGGERED. AT SECOND FLOOR CONDITIONS, PROVIDE ADEQUATE RIM OR BLOCKING TO PREVENT SPLITTING. (*) ALLOWABLE SHEAR VALUES FOR PLYWOOD SHEARWALLS MAY BE INCREASED BY 40% UNDER WIND LOADING. 375* 490* 550* 665* 870* SPACING OF A35/LTP4 FRAMING TO TOP PLATE 32" O.C. 16" O.C. 12" O.C. 12" O.C. 8" O.C. 8" O.C. 3 8" ply. C-D or C-C sheathing, (1) side w/ 8d @ 4" o/c edge, 12" o/c field, blocked (See footnote 3) 3 8" ply. C-D or C-C sheathing, (1) side w/ 8d @ 3" o/c edge, 12" o/c field 3x abutting panel studs blocked (See footnote 3 & 4) 3 8" rated STRUCT 1 panel, (1) side w/ 8d @ 3" o/c edge, 12" o/c field 3x abutting panel studs blocked (See footnote 3 & 4) 15 32" rated STRUCT 1 panel, (1) side w/ 10d @ 3" o/c edge, 12" o/c field 3x abutting panel studs blocked (See footnote 3, 4, & 5) 15 32" rated STRUCT 1 panel, (1) side w/ 10d @ 2" o/c edge, 12" o/c field 3x abutting panel studs blocked (See footnote 3, 4, & 5) 38" ply. C-D or C-C sheathing, (1) side w/ 8d @ 6" o/c edge, 12" o/c field, blocked (See footnote 3 ) 4 5 6 7 8 9 1. 2. 3.5. THE MINIMUM NOMINAL ANCHORBOLT DIAMETER SHALL BE 5/8 INCH NOTE: THIS WILL REQUIRE A MINIMUM DISTANCE FROM THE ENDS OF SILL PLATES TO BE 4" (AND A MAXIMUM OF 12") PLATE WASHERS (MINIMUM SIZE OF 3" x 3" x 1/4") SHALL BE USED ON EACH ANCHOR BOLT. ALL ANCHOR BOLTS, HOLDOWN ANCHORS, & REINF. MUST BE SECURELY TIED IN PLACE PRIOR TO FDTN. INSP. 6. SEE SHT S2.1 FOR TYP. CONCRETE & SLAB DETAILS 1-8 POSTS W/O SPECIFIED BASE SHALL BE NAILED TO BOLTED SILL PLATES W/ (2) 16d T.N. EA SIDE, TYP. PROVIDE CONC SLAB JOINTS AT NO MORE THAN 15 FT EA. WAY 4. 7. FOOTINGS ADJACENT TO SLOPES GREATER THAN OR EQUAL TO 33.3% SHALL COMPLY WITH SETBACK REQUIREMENTS DEFINED IN CBC 1808.7. 8. ALL EXTERIOR STUDS TO BE 2x6 @ 16" O.C. FOUNDATION NOTES INTERIOR HEADER SCHEDULE MAX OPENING MIN. HEADER MIN. GRADE 7'-0" 2x4 DF#2 9'-6" DBL 2x4 11'-0" 4x4 DF#2 DF#2 1 2 AB HDU2 HDU2 HDU2 1'-0" 1'-0"
1'-0" 1'-0" 1/4"=1'-0" 4x6 POST 4" CONC SLAB W/ #4 @ 18" O.C. AT MID-DEPTH OR OVER 10 MIL VAPOR BARRIER OVER 4" BASE ON PAD GRADE fc - 2500 PSI MIN (SPEC INSP NOT REQ'D). A 4-INCH-THICK (101.6 MM) BASE OF 1/2 INCH (12.7 MM) OR LARGER CLEAN AGGREGATE SHALL BE PROVIDED WITH A VAPOR RETARDER IN DIRECT CONTACT WITH CONCRETE AND A CONCRETE MIX DESIGN, WHICH WILL ADDRESS BLEEDING, SHRINKAGE, AND CURLING, SHALL BE USED. FOR ADDITIONAL INFORMATION, SEE AMERICAN CONCRETE INSTITUTE, ACI 302.2R-06. 4 FOUNDATION PLAN 4x6 POST 1 S2.1 1 S2.1 1 S2.1 1 S2.1 8S4 4 3 S2.1 3 S2.1 3 S2.1 3 S2.1 TYP. FARMHOUSE 4 6 HDU2 HDU2 3 S2.14 HDU2 HDU2 HDU4 HDU4 HDU2 2025_Wildomar revisions project no. sheet no. drawn by date description project City of Wildomar Accessory Dwelling Units 30 January 2026 YSP/CRP/JDJG SEAL 40810 COUNTY CENTER DRIVE SUITE 200 TEMECULA, CA 92591 Consultant FARMHOUSE FOUNDATION & FRAMING PLANS1.3 27 February 2026 30 January 2026 30 January 2026 30 January 2026 289
1 2 AB 2x12's @ 24" o/c 2x12's @ 24" o/c
4x12 DF#1 RIDGE BEAM
6x4 5.3' 8' 12' 4x6 POST ECCQ46 1/4"=1'-0" ROOF FRAMING PLAN 6x4 4x6 POST ECCQ46 4 4 23 S2.2 21 S2.2 22 S2.2 21 S2.2 22S6 24 S2.2 24 S2.2 MONTEREY 4 2x10's CJ @ 24" o/c 2x6's @
24" o/c5.2' 6 6x4 21 S2.2 18 S2.1 TYP. 6x4
6x4 6x4 6x4 6x4
6x4 5.6' 4 21 S2.2 312x14 LVL CEILING BEAM 4x4 KING POST 24 S2.2 4x12 DF#1 RIDGE BEAM 37 S2.2 4x6 POST 4x6 POST 19 S2.1 32 S2.2 4x6 KNEE
BRACE 4x4
4x6 KNEE
BRACE
LUS210 HGRS
2x10 CJ @ 16" o.c. DBL 2x10 19 S2.1 24 S2.2 INSPECTION NOTE: PER HERS SUMMARY FEATURES A QII (QUALITY INSULATION INSTALLATION) INSPECTION IS REQUIRED PRIOR TO DRYWALL INSTALLATION. 11 S2.1 TYP. BOLT TYPE HOLDOWN BEARING OR EXTENT HANGER TO BEAM/LEDGER SHEARWALL & A.B. SPACING PER SCHEDULE OF RAFTERS LEGEND BEARING OR EXTENT OF JOISTS X' * PLEASE REFER TO NOTES 311 & 401 ON S0.1 FOR LUMBER GRADE SPECIFICATIONS. X SHEAR WALL SCHEDULE (ASD VALUES) SHEARWALL DESCRIPTION (See footnotes 1& 4) SHEAR VALUE (PLF) ANCHOR BOLT SPACING 260* 5 8" @ 48" or 12" @ 32" 5 8" @ 32" or 12" @ 24" 5 8" @ 24" or 12" @ 16" 5 8" @ 24" or 12" @ 16" 5 8" @ 16" or 12" @ 12" 5 8" @ 12" or 12" @ 8" SHEAR WALL FOOTNOTES (1) AT PLYWOOD OR OSB PS-1 OR PS-2 RATED PANELS USE COMMON NAILS OR GALVANIZED BOX NAILS (2) LAYERS OF PAPER EXTERIOR PLYWOOD REQUIRED. SHEARSHALL BE APPLIED OVER STUDS @ 16" O/C. GALVANIZED NAILS SHALL NOT BE HOT-DIPPED OR TUMBLED. (2) SILL PLATES & WASHERS SHALL COMPLY WITH THE CONCRETE FOUNDATION CONSTRUCTION AND WOOD FRAMING CONSTRUCTION NOTES. (SEE NOTES #206, 208, 209. 307, 308, 309, ETC.) (3) IN PLYWOOD SHEARWALLS, THE EDGE OF THE 3" SQUARE WASHERS (SEE NOTE #206) SHALL BE 12" OR LESS FROM THE EDGE OF THE SILL PLATE ON THE SIDE OF THE SHEATHING. ALL NAILING SHALL BE 3 8" MIN. FROM THE EDGE OF SHEATHING. (4) WHERE ALLOWABLE SHEAR VALUES EXCEED 350 PLF (SHEARWALL TYPES 6, 7, 8, & 9) ALL FRAMING RECEIVING NAILING FROM ABUTTING PANEL EDGES SHALL NOT BE LESS THAN A SINGLE 3" NOMINAL MEMBER OR (2) 2X MEMBERS NAILED WITH 10D , SPACING EQUAL TO THE E.N. SPACING. PLYWOOD JOINT AND SILL NAILING SHALL BE STAGGERED. (5) IN SHEARWALL TYPES 8 & 9, SILL PLATE NAILING SHALL BE STAGGERED. AT SECOND FLOOR CONDITIONS, PROVIDE ADEQUATE RIM OR BLOCKING TO PREVENT SPLITTING. (*) ALLOWABLE SHEAR VALUES FOR PLYWOOD SHEARWALLS MAY BE INCREASED BY 40% UNDER WIND LOADING. 375* 490* 550* 665* 870* SPACING OF A35/LTP4 FRAMING TO TOP PLATE 32" O.C. 16" O.C. 12" O.C. 12" O.C. 8" O.C. 8" O.C. 3 8" ply. C-D or C-C sheathing, (1) side w/ 8d @ 4" o/c edge, 12" o/c field, blocked (See footnote 3) 3 8" ply. C-D or C-C sheathing, (1) side w/ 8d @ 3" o/c edge, 12" o/c field 3x abutting panel studs blocked (See footnote 3 & 4) 3 8" rated STRUCT 1 panel, (1) side w/ 8d @ 3" o/c edge, 12" o/c field 3x abutting panel studs blocked (See footnote 3 & 4) 15 32" rated STRUCT 1 panel, (1) side w/ 10d @ 3" o/c edge, 12" o/c field 3x abutting panel studs blocked (See footnote 3, 4, & 5) 15 32" rated STRUCT 1 panel, (1) side w/ 10d @ 2" o/c edge, 12" o/c field 3x abutting panel studs blocked (See footnote 3, 4, & 5) 38" ply. C-D or C-C sheathing, (1) side w/ 8d @ 6" o/c edge, 12" o/c field, blocked (See footnote 3 ) 4 5 6 7 8 9 1. 2. 3.5. THE MINIMUM NOMINAL ANCHORBOLT DIAMETER SHALL BE 5/8 INCH NOTE: THIS WILL REQUIRE A MINIMUM DISTANCE FROM THE ENDS OF SILL PLATES TO BE 4" (AND A MAXIMUM OF 12") PLATE WASHERS (MINIMUM SIZE OF 3" x 3" x 1/4") SHALL BE USED ON EACH ANCHOR BOLT. ALL ANCHOR BOLTS, HOLDOWN ANCHORS, & REINF. MUST BE SECURELY TIED IN PLACE PRIOR TO FDTN. INSP. 6. SEE SHT S2.1 FOR TYP. CONCRETE & SLAB DETAILS 1-8 POSTS W/O SPECIFIED BASE SHALL BE NAILED TO BOLTED SILL PLATES W/ (2) 16d T.N. EA SIDE, TYP. PROVIDE CONC SLAB JOINTS AT NO MORE THAN 15 FT EA. WAY 4. 7. FOOTINGS ADJACENT TO SLOPES GREATER THAN OR EQUAL TO 33.3% SHALL COMPLY WITH SETBACK REQUIREMENTS DEFINED IN CBC 1808.7. 8. ALL EXTERIOR STUDS TO BE 2x6 @ 16" O.C. FOUNDATION NOTES INTERIOR HEADER SCHEDULE MAX OPENING MIN. HEADER MIN. GRADE 7'-0" 2x4 DF#2 9'-6" DBL 2x4 11'-0" 4x4 DF#2 DF#2 1 2 AB HDU2 HDU2 HDU2 1'-0" 1'-0"
1'-0" 1'-0" 1/4"=1'-0" 4x6 POST 4" CONC SLAB W/ #4 @ 18" O.C. AT MID-DEPTH OR OVER 10 MIL VAPOR BARRIER OVER 4" BASE ON PAD GRADE fc - 2500 PSI MIN (SPEC INSP NOT REQ'D). A 4-INCH-THICK (101.6 MM) BASE OF 1/2 INCH (12.7 MM) OR LARGER CLEAN AGGREGATE SHALL BE PROVIDED WITH A VAPOR RETARDER IN DIRECT CONTACT WITH CONCRETE AND A CONCRETE MIX DESIGN, WHICH WILL ADDRESS BLEEDING, SHRINKAGE, AND CURLING, SHALL BE USED. FOR ADDITIONAL INFORMATION, SEE AMERICAN CONCRETE INSTITUTE, ACI 302.2R-06. 4 FOUNDATION PLAN 4x6 POST 1 S2.1 1 S2.1 1 S2.1 1 S2.1 8S4 4 3 S2.1 3 S2.1 3 S2.1 3 S2.1 TYP. MONTEREY 4 6 HDU2 HDU2 3 S2.14 HDU2 HDU2 HDU4 HDU4 HDU2 2025_Wildomar revisions project no. sheet no. drawn by date description project City of Wildomar Accessory Dwelling Units 30 January 2026 YSP/CRP/JDJG SEAL 40810 COUNTY CENTER DRIVE SUITE 200 TEMECULA, CA 92591 Consultant MONTEREY FOUNDATION & FRAMING PLANS1.2 27 February 2026 30 January 2026 30 January 2026 30 January 2026 290
2025_Wildomar City of Wildomar Accessory Dwelling Units YSP/CRP/JDJG revisions project no. sheet no. drawn by date description project SEAL 40810 COUNTY CENTER DRIVE SUITE 200 TEMECULA, CA 92591 Consultant 30 January 2026 S2.1 Structural Details27 February 2026 30 January 2026 30 January 2026 30 January 2026 291
2025_Wildomar City of Wildomar Accessory Dwelling Units YSP/CRP/JDJG revisions project no. sheet no. drawn by date description project SEAL 40810 COUNTY CENTER DRIVE SUITE 200 TEMECULA, CA 92591 Consultant 30 January 2026 Structural DetailsS2.2 27 February 2026 30 January 2026 30 January 2026 30 January 2026 292
2025_Wildomar revisions project no. sheet no. drawn by date description project City of Wildomar Accessory Dwelling Units 30 January 2026 YSP/CRP/JDJG SEAL 40810 COUNTY CENTER DRIVE SUITE 200 TEMECULA, CA 92591 Consultant Example Energy Calculations T24.1 27 February 2026 27 February 2026 30 January 2026 30 January 2026 30 January 2026 30 January 2026 293
2025_Wildomar revisions project no. sheet no. drawn by date description project City of Wildomar Accessory Dwelling Units 30 January 2026 YSP/CRP/JDJG SEAL 40810 COUNTY CENTER DRIVE SUITE 200 TEMECULA, CA 92591 Consultant Example Energy Calculations T24.2 27 February 2026 27 February 2026 30 January 2026 30 January 2026 30 January 2026 30 January 2026 294
2025_Wildomar revisions project no. sheet no. drawn by date description project City of Wildomar Accessory Dwelling Units 30 January 2026 YSP/CRP/JDJG SEAL 40810 COUNTY CENTER DRIVE SUITE 200 TEMECULA, CA 92591 Consultant Example Energy Calculations T24.3 27 February 2026 27 February 2026 30 January 2026 30 January 2026 30 January 2026 30 January 2026 295
Sheet #
D
C
B
A
1 2 3 4 5
1 2 3 4 5
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

APPLICANT AGREEMENT
Consultant

AS NOTED

PROJECT DIRECTORY SHEET INDEX

BUILDING INFORMATION

PROJECT DESCRIPTION

PROJECT INFORMATION PROJECT CHECKLIST STYLE AND OPTION SELECTIONS

WILDOMAR, CALIFORNIA

APPLICANT
NAME:

ADDRESS:

PHONE:

EMAIL:

OWNER
NAME:

ADDRESS:

PHONE:

EMAIL:

SITE PLAN & TITLE SHEET PREPARATION
COMPANY:

CONTACT:

PHONE:

EMAIL:

ADDRESS:

CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT
23300 WILDOMAR TRAIL
WILDOMAR, CA 92595
(951) 677-4400
ZONING:

SETBACKS
FRONT:

REAR:

SIDE (INTERIOR):

SIDE (STREET):

ALLOWABLE PROPOSED

DISTANCE BETWEEN STRUCTURES

ALLOWABLE PROPOSED

PARKING

REQUIRED PROVIDED
SIDE (CORNER):

LOT COVERAGE

ALLOWABLE PROPOSED
LOT SIZE:

APPLICANT AGREES TO PROVIDE ALL NECESSARY INFORMATION REQUIRED TO COMPLETE THESE CONSTRUCTION DOCUMENTS. MODIFICATIONS TO THE PERMIT-READY DOCUMENTS PROVIDED BY

MICHAEL BAKER INTERNATIONAL ARE TO BE DISCLOSED BY THE APPLICANT AND APPROVED BY THE AUTHORITY HAVING JURISDICTION. ANY MODIFICATIONS TO THESE CONSTRUCTION DOCUMENTS REQUIRE EACH SHEET TO BE SIGNED BY THE PERSON WHO MADE THE CHANGES. ANY ADDITIONAL

SHEETS INCORPORATED INTO THESE DOCUMENTS ALSO REQUIRES A SIGNATURE BY THE PERSON WHO PREPARED THE INFORMATION. THE FOUNDATION DESIGN FOR THESE PERMIT-READY CONSTRUCTION DOCUMENTS ASSUMES STANDARD SOILS CONDITIONS AND LEVEL TOPOGRAPHY. IF SITE SPECIFIC

CONDITIONS REQUIRE A FOUNDATION DESIGN BEYOND WHAT IS PROVIDED IN THESE DOCUMENTS THE

THE APPLICANT IS TO PROVIDE A NEW FOUNDATION DESIGN THAT COMPLIES WITH THE RECOMMENDATION OF THE GEOGRAPHIC ENGINEER ’S REPORT.

BY SIGNING BELOW THE APPLICANT AGREES TO THE STATEMENT ABOVE AND WILL COMPLY WITH ALL LOCAL CODE REQUIREMENTS.

SIGNATURE: DATE:

VICINITY MAP

APPLICABLE CODES
AND STANDARDS:

WILDOMAR MUNICIPAL CODE
2022 CALIFORNIA ADMINISTRATIVE CODE (CAC)

WILDOMAR ADMINISTRATIVE PROVISIONS
2022 CALIFORNIA BUILDING CODE (CBC)
2022 CALIFORNIA RESIDENTIAL CODE (CRC)
2022 CALIFORNIA GREEN BUILDING STANDARDS CODE (CALGREEN) 2022 CALIFORNIA ENERGY CODE (CEEC)
2022 CALIFORNIA ELECTRICAL CODE (CEC)
2022 CALIFORNIA MECHANICAL CODE (CMC)
2022 CALIFORNIA PLUMBING CODE (CPC)
2022 CALIFORNIA FIRE CODE (CFC)
SITE ADDRESS:

OCCUPANCY GROUP: R3
CONSTRUCTION TYPE: VB
STORIES: 1
HEIGHT:

OWNER OR APPLICANT TO SELECT ONE OF THE FOLLOWING STYLES AND ONE OF EACH OF THE SUBSEQUENT OPTIONS WITHIN THE SELECTED STYLE. MARK SELECTIONS WITH "X". FINISH COLORS OF ADU TO MATCH PRINAICPAL DWELLING UNIT.

CRAFTSMAN

FIBER CEMENT LAP SIDING

STONE VENEER

FIBER CEMENT TRIM
COLOR:

COLOR:

COLOR:

ASPHALT SHINGLE ROOF
COLOR:

EXTERIOR SOFFITS, RAKES & EAVES
COLOR:

OPTION A - EXTERIOR GRADE TONGUE & GROOVE

OPTION B - FIBER CEMENT

MONTEREY
STUCCO

FIRE CEMENT TRIM
COLOR:

COLOR:

CONCRETE TILE ROOF
COLOR:

EXTERIOR SOFFITS, RAKES & EAVES
COLOR:

OPTION A - EXTERIOR GRADE TONGUE & GROOVE

OPTION B - FIBER CEMENT

MODERN FARMHOUSE

BOARD AND BATTEN FIBER CEMENT PANEL SIDING

EXTERIOR FIBER CEMENT TRIM
COLOR:

COLOR:

EXTERIOR SOFFITS, RAKES & EAVES
COLOR:

OPTION A - EXTERIOR GRADE TONGUE & GROOVE

OPTION B - FIBER CEMENT

ROOF MATERIAL
COLOR:

OPTION A - ASPHALT SHINGLE ROOF

OPTION B - STANDING SEAM METAL ROOF

WINDOWS
COLOR:

WINDOWS
COLOR:

WINDOWS
COLOR:

WASTE WATER

FIRE SPRINKLERS

GAS SERVICE

ADDITIONAL PERMITS TO BE OBTAINED BY APPLICANT

ADU TO HAVE NEW CONNECTION TO CITY SEWER MAIN

ADU TO CONNECTO EXISTING RESIDENCE SEWER LATERAL

SEPTIC (REQUIRES HEALTH DEPARTMENT APPROVAL)

UPGRADED SERVICE

EXISTING SERVICE TO REMAIN

NEW SERVICE
SIZE OF EXISTING SERVICE:

SIZE OF PROPOSED SERVICE:

EXISTING PRIMARY RESIDENCE CURRENTLY HAS FIRE SPRINKLERS

EXISTING PRIMARY RESIDENCE DOES NOT CURRENTLY HAVE FIRE SPRINKLERS

PROPERTY IS LOCATED IN THE VERY HIGH FIRE HAZARD SEVERITY ZONE (VHFSZ)

PROPERTY IS NOT LOCATED IN THE VERY HIGH FIRE HAZARD SEVERITY ZONE

PROPOSED ADU IS REQUIRED TO HAVE FIRE SPRINKLERS IF THE EXISTING PRIMARY

RESIDENCE HAS FIRE SPRINKLERS
SPRINKLERS REQUIRED:

OPTION A - YES

OPTION B - NO

FIRE RATED DETAILS

1. 2.

3. 4.

FIRE RATED DETAILS ARE REQUIRED WHEN:

THE PROPERTY IS LOCATED IN THE VHFSV
BUILDING WALLS AND/OR ROOF EAVES ARE LESS THAN 5 FT FROM THE PROPERTY

LINE IN AN UNSPRINKLERED BUILDING
BUILDING WALLS AND/OR EAVES ARE LESS THAN 3 FT FROM THE PROPERTY LINE IN A SPRINKLERED BUILDING.

BUILDING WALLS AND/OR ROOF EAVES ARE LESS THAN 10 FT FROM THE MAIN

DWELLING OR ADJACENT BUILDING/STRUCTURE UNIT IN AN UNSPRINKLERED BUILDINGBUILDING WALLS AND/OR ROOF EAVES ARE LESS THAN 6 FT FROM THE

MAIN DWELLING UNIT ADJACENT BUILDING/STRUCTUREIN A SPRNKLERED BUILDING

OPTION A - YES

OPTION B - NO
FIRE RATED DETAILS REQUIRED:

HERS NOTES

ELECTRICAL SERVICE

UPGRADED SERVICE

EXISTING SERVICE TO REMAIN

NEW SERVICE
SIZE OF EXISTING SERVICE:

SIZE OF PROPOSED SERVICE:

APN:

ADDITIONAL PERMITS

FIRE SPRINKLERS (WHEN REQUIRED)

1. 2.

PHOTOVOLTAIC SYSTEM

SYSTEM MUST BE INSTALLED AND OPERATIONAL PRIOR TO FINAL BUILDING INSPECTION AND APPROVAL FOR ADU (WHEN REQUIRED).

FOR AN EXISTING PHOTOVOLATIC SYSTEM OF SUFFICIENT SIZE ON THE

PRIMARY RESIDENCE TO ACCOMODATE THE NEW ADU, THE

OWNER/APPLICANT IS TO PROVIDE A REPORT INDICATING THE
EXISTING SIZE OF THE PV PANEL.

OWNER OR APPLICANT TO MARK SELECTIONS WITH "X"

ROOF FRAMING

ROOF FRAMING PER DRAWINGS

ROOF TRUSSES

IN LIEU OF ROOF DETAILS PROVIDED ON THESE PLANS, OWNER IS TO CONTRACT

WITH AN INDEPENDENT TRUSS COMPANY AND SUBMIT TRUSS CALCULATIONS TO THE CITY OF WILDOMAR FOR APPROVAL. INDICATE ON THE CHECKLIST BELOW IF TRUSS PACKAGE WILL BE PROVIDED AS A SEPARATE SUBMITTAL.

ADDITIONAL SUPPORTING DOCUMENTS (BY APPLICANT)
COMPLETED COVER SHEET (G-0.0)
SITE PLAN SHEET (AS-1.1) FOR CITY OF

WILDOMAR REVIEW

DEMOLITION PERMIT IF REQUIRED HOLD HARMLESS AGREEMENT
TITLE 24 ENERGY CALCULATION REPORT

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR WHICH IT WAS

PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER TIME

AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR REDUCE THE RECIPIENT'S RESPONSIBILITY TO

VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO

WARRANTIES OF ANY NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY.

FURTHERMORE, THE RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS HARMLESS FROM ANY AND

ALL CLAIMS, SUITS, LIABILITY, DEMANDS, JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING

THERE FROM ANY USE OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

1. 2.

3. 4.

5. 6.

7. PROPERLY COMPLETED AND ELECTRONICALLY SIGNED CERTIFICATE OF INSTALLATION (CF2R FORMS) SHALL BE POSTED WEATHER PROTECTED WITHIN BUILDING FOR REVIEW BY INSPECTORS - EES 10-103( A)3, 10-103(B )1.A - BY THE

INSTALLING CONTRACTOR AND SUBMITTED TO THE FIELD INSPECTOR DURING CONSTRUCTION AT THE SITE. FOR PROJECTS REQUIRING HERS VERIFICATION, THE CF2R FORMS SHALL BE REGISTERED WITH A CALIFORNIA APPROVED HERS PROVIDER DATA REGISTRY WITH ITS OWN UNIQUE 21 DIGIT REGISTRATION NUMBER LOCATED AT THE BOTTOM OF EACH PAGE. THE FIRST 12 DIGITS WILL MATCH THE REGISTRATION NUMBER ASSOCIATED WITH THE CF1 R FORM. CERTIFICATE OF OCCUPANCY WILL NOT BE ISSUED UNTIL THE CF2R FORMS ARE REVIEWED AND APPROVED.

PROPERLY COMPLETED & ELECTRONICALLY SIGNED AND REGISTERED CERTIFICATE(S) OF FIELD VERIFICATION AND DIAGNOSTIC TESTING (CF3R) SHALL BE

POSTED WEATHER PROTECTED WITHIN THE BUILDING SITE BY A CERTIFIED HERS RATER. A REGISTERED CF3R WILL HAVE A UNIQUE 25 DIGIT REGISTRATION NUMBER LOCATED AT THE BOTTOM OF EACH PAGE. THE FIRST 20 DIGITS OF THE NUMBER WILL MATCH THE REGISTRATION NUMBER ASSOCIATED WITH THE CF2R. CERTIFICATE OF OCCUPANCY WILL NOT BE ISSUED UNTIL THE CF3R IS REVIEWED AND APPROVED. EES 10-103(0)3, 10-103(B)1.A.

CF1 R REGISTRATION FORMS ARE LOCATED ON THE PLANS. IF REGISTRATION IS REQUIRED, A WATER-MARK AND REGISTRATION NUMBER WILL BE VISIBLE. QUALITY INSULATION INSPECTION - HIRE HERS RATER EARLY BEFORE DRYWALL. VARIABLE

CAPACITY HEAT PUMP - DUCTLESS UNITS ENTIRELY LOCATED IN CONDITIONED

SPACE, AIRFLOW IN HABITABLE ROOMS, WALL MOUNTED THERMOSTAT IN ZONES GREATER THAN 150 S. F., VERIFY HEAT PUMP RATED CAPACITY, AND REFRIGERANT CHARGE. AT ADU -STUDIO, 1 BED, 2 BED & 2 BED 2 BATH - R-6 DUCTS IN CONDITIONED SPACE, VERIFIED EER/EER2, SEER/SEER2, HSPF, HEAT PUMP RATED HEATING CAPACITY, MIN AIRFLOW, REFRIGERANT CHARGE, & FAN WATT DRAW/FAN EFFICACY.

REFERENCE KEYNOTE MP14 ON SHEET MEP.1 FOR KITCHEN RANGE HOOD CFM REQUIREMENTS.

FOR IAQ FAN - PLEASE SEE SITE SPECIFIC CALCULATIONS FOR CFM REQUIRED FOR A CONTINUOUSLY OPERATING EXHAUST FAN. PROVIDE A TIMER SWITCH WITH A MANUAL OFF AND A SOUND RATING OF 1 SONE (3 SONES MAX FOR AN INTERMITTENT FAN). THIS FAN TO PROVIDE A WHOLE BUILDING INDOOR AIR QUALITY VENTILATION WITH OUTDOOR AIR IN COMPLIANCE WITH ASHRAE STANDARD 62.2 AS ADOPTED BY THE CALIFORNIA ENERGY COMMISSION.

PV SYSTEM SOLAR: SEE SITE SPECIFIC T24 SHEETS FOR KWDC REQUIRED. POSSIBLE PV EXCEPTION 2: NO PV REQUIRED WHEN MINIMUM PV SIZE < 1.8 KWDC(SECTION 150.1 (C)14) PV EXEMPTION BASED IN UPDATED ENERGY CALCULATIONS WITH SITE SPECIFIC INFORMATION.

SPECIAL FEATURES: VCHP REQUIRED ITEMS LISTED ABOVE, EXPOSED SLAB FLOORING, AND NEEA RATED HEAT PUMP WATER HEATER; SPECIFIC BRAND/MODEL OR EQ., AND SOLAR EXEMPTION 2 WAS TAKEN AT STUDIO & 1 BED NEW 2022 ELECTRIC READY REQUIREMENTS FOR NEW CONSTRUCTION: IF HEAT

PUMP WATER HEATER IS NOT INSTALLED, PROVIDE SPACE FOR THIS TYPE OF WATER HEATER. A 240V OUTLET IS REQUIRED FOR WATER HEATER, DRYER, AUTO CHARGING, AND STOVE INCLUDING BREAKER SPACE. ENERGY STORAGE SYSTEM FOR A FUTURE

BATTERY SYSTEM (BATTERY READY) IS REQUIRED IF FULL SYSTEM IS NOT INSTALLED.

GRADING PERMIT IF REQUIRED AS

DETERMINED BY CITY OF WILDOMAR

ENGINEERING DEPARTMENT

CONSTRUCTION WASTE MANAGEMENT
PLAN

COVER SHEET
G-0.0
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
FINAL DESIGN - 02/27/2026
1 BEDROOM
G-0.0 COVER SHEET
G-0.1 EXTERIOR VIEWS - STYLE OPTIONS
G-0.2 CALGREEN RESIDENTIAL CHECKLIST
G-0.3 CALGREEN RESIDENTIAL CHECKLIST
AS-1.1 ARCHITECTURAL - SITE PLAN
A-1.0 GENERAL NOTES, ABBREVIATIONS, AND SYMBOLS
A-1.1 1 BEDROOM - FLOOR PLAN AND ROOF PLAN (CRAFTSMAN)
A-1.2 1 BEDROOM - FLOOR PLAN AND ROOF PLAN (MONTEREY)
A-1.3 1 BEDROOM - FLOOR PLAN AND ROOF PLAN (MODERN FARMHOUSE) A-2.1 1 BEDROOM - EXTERIOR ELEVATIONS (CRAFTSMAN)
A-2.2 1 BEDROOM - EXTERIOR ELEVATIONS (MONTEREY)
A-2.3 1 BEDROOM - EXTERIOR ELEVATIONS (MODERN FARMHOUSE) A-3.1 1 BEDROOM - BUILDING SECTIONS (CRAFTSMAN)
A-3.2 1 BEDROOM - BUILDING SECTIONS (MONTEREY)
A-3.3 1 BEDROOM - BUILDING SECTIONS (MODERN FARMHOUSE)
A-5.1 DETAILS
A-5.2 ROOF DETAILS
A-6.1 WINDOW AND DOOR SCHEDULES & DETAILS
NEW CONSTRUCTION OF A ONE STORY 1 BEDROOM, 1 BATH, DETACHED 646 SF ACCESSORY DWELLING UNIT.

MEP.0 MECHANICAL/ELECTRICAL/PLUMBING GENERAL NOTES
MEP.1 MECHANICAL/ELECTRICAL/PLUMBING PLANS
S0.1 STRUCTURAL NOTES & SPECIFICATIONS
S1.1 CRAFTSMAN FOUNDATION & FRAMING PLAN
S1.2 MONTEREY FOUNDATION & FRAMING PLAN
S1.3 FARMHOUSE FOUNDATION & FRAMING PLAN
S2.1 STRUCTURAL DETAILS
S2.2 STRUCTURAL DETAILS
T24.1 EXAMPLE TITLE 24 CALCULATIONS
T24.2 EXAMPLE TITLE 24 CALCULATIONS
T24.3 EXAMPLE TITLE 24 CALCULATIONS
11' - 9"

REVISIONS
NO. DATE DESCRIPTION
296

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMANGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

Sheet #
D
C
B
A
1 2 3 4 5
1 2 3 4 5
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

EXTERIOR VIEWS - STYLE OPTIONS
G-0.1
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026
SCALE: 12" = 1'-0"
EXTERIOR PERSPECTIVE - CRAFTSMAN 1 SCALE: 12" = 1'-0"EXTERIOR PERSPECTIVE - MONTEREY 2 SCALE: 12" = 1'-0"EXTERIOR PERSPECTIVE - MODERN FARMHOUSE 3

REVISIONS
NO. DATE DESCRIPTION
297
Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

CALGREEN RESIDENTIAL CHECKLIST
G-0.2
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026

REVISIONS
NO. DATE DESCRIPTION
CHAPTER 4

RESIDENTIAL MANDATORY MEASURES
DIVISION 4.1 PLANNING AND DESIGN
DIVISION 4.3 WATER EFFICIENCY AND CONSERVATION

4.406 ENHANCED DURABILITY AND REDUCED MAINTENANCE

4.406.1 RODENT PROOFING. Annular spaces around pipes, electric cables, conduits or other openings in sole/bottom plates at exterior walls shall be protected against the passage of rodents by closing such openings with cement mortar, concrete masonry or a similar method acceptable to the enforcing agency.

4.408 CONSTRUCTION WASTE REDUCTION, DISPOSAL AND RECYCLING

4.408.1 CONSTRUCTION WASTE MANAGEMENT. Recycle and/or salvage for reuse a minimum of 65 percent of the non-hazardous construction and demolition waste in accordance with either Section

4.408.2, 4.408.3 or 4.408.4, or meet a more stringent local construction and demolition waste management ordinance.

Exceptions:

1. Excavated soil and land-clearing debris.

2. Alternate waste reduction methods developed by working with local agencies if diversion or recycle facilities capable of compliance with this item do not exist or are not located reasonably close to the jobsite.

3. The enforcing agency may make exceptions to the requirements of this section when isolated jobsites are located in areas beyond the haul boundaries of the diversion facility.

4.408.2 CONSTRUCTION WASTE MANAGEMENT PLAN. Submit a construction waste management plan in conformance with Items 1 through 5. The construction waste management plan shall be updated as necessary and shall be available during construction for examination by the enforcing agency.

1. Identify the construction and demolition waste materials to be diverted from disposal by recycling, reuse on the project or salvage for future use or sale.

2. Specify if construction and demolition waste materials will be sorted on-site (source separated) or bulk mixed (single stream).

3. Identify diversion facilities where the construction and demolition waste material collected will be taken.

4. Identify construction methods employed to reduce the amount of construction and demolition waste generated.

5. Specify that the amount of construction and demolition waste materials diverted shall be calculated by weight or volume, but not by both.

4.408.3 WASTE MANAGEMENT COMPANY. Utilize a waste management company, approved by the enforcing agency, which can provide verifiable documentation that the percentage of construction and demolition waste material diverted from the landfill complies with Section 4.408.1.

Note: The owner or contractor may make the determination if the construction and demolition waste materials will be diverted by a waste management company.

4.408.4 WASTE STREAM REDUCTION ALTERNATIVE [LR]. Projects that generate a total combined weight of construction and demolition waste disposed of in landfills, which do not exceed 3.4 lbs./sq.ft. of the building area shall meet the minimum 65% construction waste reduction requirement in Section 4.408.1

4.408.4.1 WASTE STREAM REDUCTION ALTERNATIVE. Projects that generate a total combined weight of construction and demolition waste disposed of in landfills, which do not exceed 2 pounds per square foot of the building area, shall meet the minimum 65% construction waste reduction requirement in Section 4.408.1

4.408.5 DOCUMENTATION. Documentation shall be provided to the enforcing agency which demonstrates compliance with Section 4.408.2, items 1 through 5, Section 4.408.3 or Section 4.408.4..

Notes:1. Sample forms found in "A Guide to the California Green Building Standards Code (Residential)" located at www.hcd.ca.gov/CALGreen.html may be used to assist in documenting compliance with this section.

2. Mixed construction and demolition debris (C & D) processors can be located at the California Department of Resources Recycling and Recovery (CalRecycle).

4.410 BUILDING MAINTENANCE AND OPERATION

4.410.1 OPERATION AND MAINTENANCE MANUAL. At the time of final inspection, a manual, compact disc, web-based reference or other media acceptable to the enforcing agency which includes all of the following shall be placed in the building:

1. Directions to the owner or occupant that the manual shall remain with the building throughout the life cycle of the structure.

2. Operation and maintenance instructions for the following:
a. Equipment and appliances, including water-saving devices and systems, HVAC systems, photovoltaic systems, electric vehicle chargers, water-heating systems and other major appliances and equipment.
b. Roof and yard drainage, including gutters and downspouts. c. Space conditioning systems, including condensers and air filters. d. Landscape irrigation systems.
e. Water reuse systems.

3. Information from local utility, water and waste recovery providers on methods to further reduce resource consumption, including recycle programs and locations.

4. Public transportation and/or carpool options available in the area.

5. Educational material on the positive impacts of an interior relative humidity between 30-60 percent and what methods an occupant may use to maintain the relative humidity level in that range.

6. Information about water-conserving landscape and irrigation design and controllers which conserve water.

7. Instructions for maintaining gutters and downspouts and the importance of diverting water at least 5 feet away from the foundation.

8. Information on required routine maintenance measures, including, but not limited to, caulking, painting, grading around the building, etc.

9. Information about state solar energy and incentive programs available.

10. A copy of all special inspections verifications required by the enforcing agency or this code.

11. Information from the Department of Forestry and Fire Protection on maintenance of defensible space around residential structures.

12. Information and/or drawings identifying the location of grab bar reinforcements.

4.410.2 RECYCLING BY OCCUPANTS. Where 5 or more multifamily dwelling units are constructed on a building site, provide readily accessible area(s) that serves all buildings on the site and are identified for the depositing, storage and collection of non-hazardous materials for recycling, including (at a minimum) paper, corrugated cardboard, glass, plastics, organic waster, and metals, or meet a lawfully enacted local recycling ordinance, if more restrictive.

Exception: Rural jurisdictions that meet and apply for the exemption in Public Resources Code Section 42649.82 (a)(2)(A) et seq. are note required to comply with the organic waste portion of this section.

DIVISION 4.4 MATERIAL CONSERVATION AND RESOURCE

EFFICIENCY
DIVISION 4.5 ENVIRONMENTAL QUALITY

4.303 INDOOR WATER USE

4.303.1 WATER CONSERVING PLUMBING FIXTURES AND FITTINGS. Plumbing fixtures (water closets and urinals) and fittings (faucets and showerheads) shall comply with the sections 4.303.1.1, 4.303.1.2, 4.303.1.3, and 4.303.4.4.

Note: All noncompliant plumbing fixtures in any residential real property shall be replaced with water-conserving plumbing fixtures. Plumbing fixture replacement is required prior to issuance of a certificate of final completion, certificate of occupancy, or final permit approval by the local building department. See Civil Code Section 1101.1, et seq., for the definition of a noncompliant plumbing fixture, types of residential buildings affected and other important enactment dates.

4.303.1.1 Water Closets. The effective flush volume of all water closets shall not exceed 1.28 gallons per flush. Tank-type water closets shall be certified to the performance criteria of the U.S. EPA WaterSense Specification for Tank-type Toilets.

Note: The effective flush volume of dual flush toilets is defined as the composite, average flush volume of two reduced flushes and one full flush.

4.303.1.2 Urinals. The effective flush volume of wall mounted urinals shall not exceed 0.125 gallons per flush.

The effective flush volume of all other urinals shall not exceed 0.5 gallons per flush.

4.303.1.3 Showerheads.

4.303.1.3.1 Single Showerhead. Showerheads shall have a maximum flow rate of not more than 1.8 gallons per minute at 80 psi. Showerheads shall be certified to the performance criteria of the U.S. EPA WaterSense Specification for Showerheads.

4.303.1.3.2 Multiple showerheads serving one shower. When a shower is served by more than one showerhead, the combined flow rate of all the showerheads and/or other shower outlets controlled by a single valve shall not exceed 1.8 gallons per minute at 80 psi, or the shower shall be designed to only allow one shower outlet to be in operation at a time.

Note: A hand-held shower shall be considered a showerhead.

4.303.1.4 Faucets.

4.303.1.4.1 Residential Lavatory Faucets. The maximum flow rate of residential lavatory faucets shall not exceed 1.2 gallons per minute at 60 psi. The minimum flow rate of residential lavatory faucets shall not be less than 0.8 gallons per minute at 20 psi.

4.303.1.4.2 Lavatory Faucets in Common and Public Use Areas. The maximum flow rate of lavatory faucets installed in common and public use areas (outside of dwellings or sleeping units) in residential buildings shall not exceed 0.5 gallons per minute at 60 psi.

4.303.1.4.3 Metering Faucets. Metering faucets when installed in residential buildings shall not deliver more than 0.2 gallons per cycle.

4.303.1.4.4 Kitchen Faucets. The maximum flow rate of kitchen faucets shall not exceed 1.8 gallons per minute at 60 psi. Kitchen faucets may temporarily increase the flow above the maximum rate, but not to exceed 2.2 gallons per minute at 60 psi, and must default to a maximum flow rate of 1.8 gallons per minute at 60 psi.

Note: Where complying faucets are unavailable, aerators or other means may be used to achieve reduction.

4.303.1.4.5 Pre-rinse spray valves.

When installed, shall meet the requirements in the California Code of Regulations, Title 20 (Appliance Efficiency Regulations), Sections 1605.1 (h)(4) Table H-2, Section 1605.3 (h)(4)(A), and Section 1607 (d)(7) and shall be equipped with an integral automatic shutoff.

FOR REFERENCE ONLY: The following table and code section have been reprinted from the California Code of Regulations, Title 20 (Appliance Efficiency Regulations),Section 1605.1 (h)(4) and Section 1605.3 (h)(4)(A).

Title 20 Section 1605.3 (h)(4)(A): Commercial prerinse spray values manufactured on or after January 1, 2006, shall have a minimum spray force of not less than 4.0 ounces-force (ozf)[113 grams-force(gf)]

4.303.2 Submeters for multifamily buildings and dwelling units in mixed-used residential/commercial buildings.

Submeters shall be installed to measure water usage of individual rental dwelling units in accordance with the California Plumbing Code. 4.303.3 Standards for plumbing fixtures and fittings. Plumbing fixtures and fittings shall be installed in accordance with the California Plumbing Code, and shall meet the applicable standards referenced in Table 1701.1 of the California Plumbing Code.

TABLE - MAXIMUM FIXTURE WATER USE

FIXTURE TYPE FLOW RATE
SHOWER HEADS (RESIDENTIAL) 1.8 GMP @ 80 PSI
LAVATORY FAUCETS (RESIDENTIAL) MAX. 1.2 GPM @ 60 PSI MIN. 0.8 GPM @ 20 PSI

LAVATORY FAUCETS IN COMMON & PUBLIC

USE AREAS

0.5 GPM @ 60 PSI
KITCHEN FAUCETS 1.8 GPM @ 60 PSI
METERING FAUCETS 0.2 GAL/CYCLE
WATER CLOSET 1.28 GAL/FLUSH
URINALS 0.125 GAL/FLUSH

4.304 OUTDOOR WATER USE

4.304.1 OUTDOOR POTABLE WATER USE IN LANDSCAPE AREAS. Residential developments shall comply with a local water efficient landscape ordinance or the current California Department of Water Resources' Model Water Efficient Landscape Ordinance (MWELO), whichever is more stringent.

NOTES:

1. The Model Water Efficient Landscape Ordinance (MWELO) is located in the California Code Regulations, Title 23, Chapter 2.7, Division 2. MWELO and supporting documents, including water budget calculator, are available at: https://www.water.ca.gov/
ABBREVIATION DEFINITIONS:

HCD Department of Housing and Community Development
BSC California Building Standards Commission
DSA-SS Division of the State Architect, Structural Safety OSHPD Office of Statewide Health Planning and Development LR Low Rise
HR High Rise
AA Additions and Alterations N New
NOTE:

THIS TABLE COMPILES THE DATA IN SECTION 4.303.1, AND IS INCLUDED AS A CONVENIENCE FOR THE USER.

SECTION 4.102 DEFINITIONS

4.102.1 DEFINITIONS
The following terms are defined in Chapter 2 (and are included here for reference) FRENCH DRAIN. A trench, hole or other depressed area loosely filled with rock, gravel, fragments of brick or similar pervious material used to collect or channel drainage or runoff water.

WATTLES. Wattles are used to reduce sediment in runoff. Wattles are often constructed of natural plant materials such as hay, straw or similar material shaped in the form of tubes and placed on a downflow slope. Wattles are also used for perimeter and inlet controls.

4.106 SITE DEVELOPMENT

4.106.1 GENERAL. Preservation and use of available natural resources shall be accomplished through evaluation and careful planning to minimize negative effects on the site and adjacent areas. Preservation of slopes, management of storm water drainage and erosion controls shall comply with this section.

4.106.2 STORM WATER DRAINAGE AND RETENTION DURING CONSTRUCTION. Projects which disturb less than one acre of soil and are not part of a larger common plan of development which in total disturbs one acre or more, shall manage storm water drainage during construction. In order to manage storm water drainage during construction, one or more of the following measures shall be implemented to prevent flooding of adjacent property, prevent erosion and retain soil runoff on the site.

1. Retention basins of sufficient size shall be utilized to retain storm water on the site.

2. Where storm water is conveyed to a public drainage system, collection point, gutter or similar disposal method, water shall be filtered by use of a barrier system, wattle or other method approved by the enforcing agency.

3. Compliance with a lawfully enacted storm water management ordinance.

Note: Refer to the State Water Resources Control Board for projects which disturb one acre or more of soil, or are part of a larger common plan of development which in total disturbs one acre or more of soil. (Website: https://www.waterboards.ca.gov/water_issues/programs/stormwater/construction.html)

4.106.3 GRADING AND PAVING. Construction plans shall indicate how the site grading or drainage system will manage all surface water flows to keep water from entering buildings. Examples of methods to manage surface water include, but are not limited to, the following:

1. Swales

2. Water collection and disposal systems

3. French drains

4. Water retention gardens

5. Other water measures which keep surface water away from buildings and aid in groundwater recharge.

Exception: Additions and alterations not altering the drainage path.

4.106.4 Electric vehicle (EV) charging for new construction. New construction shall comply with Section 4.106.4.1 or 4.106.4.2. Electric vehicle supply equipment (EVSE) shall comply with the California Electrical Code. Exceptions:

1. On a case-by-case basis, where the local enforcing agency has determined EV charging and infrastructure are not feasible based upon one or more of the following conditions:

1.1 Where there is no local utility power supply or the local utility is unable to supply adequate power.

1.2 Where there is evidence suitable to the local enforcing agency substantiating that additional local utility infrastructure design requirements, directly related to the implementation of Section

4.106.4, may adversely impact the construction cost of the project.

2. Accessory Dwelling Units (ADU) and Junior Accessory Dwelling Units (JADU) without additional parking facilities.

4.106.4.1 New one- and two-family dwellings and townhouses with attached private garages. For each dwelling unit, install a listed raceway to accommodate a dedicated 208/240-volt branch circuit. The raceway shall not be less than trade size 1 (nominal 1-inch inside diameter). The raceway shall originate at the main service or subpanel and shall terminate into a listed cabinet, box or other enclosure in close proximity to the proposed location of an EV charger. Raceways are required to be continuous at enclosed, inaccessible or concealed areas and spaces. The service panel and/or subpanel shall provide capacity to install a 40-ampere 208/240-volt minimum dedicated branch circuit and space(s) reserved to permit installation of a branch circuit overcurrent protective device.

Exemption: A raceway is not required if a minimum 40-ampere 208/240-volt dedicated EV branch circuit is installed in close proximity to the proposed location of an EV charger at the time of original construction in accordance with the California Electrical Code. 4.106.4.1.1 Identification. The service panel or subpanel circuit directory shall identify the overcurrent protective device space(s) reserved for future EV charging as "EV CAPABLE". The raceway termination location shall be permanently and visibly marked as "EV CAPABLE".

CHAPTER 3

GREEN BUILDING
SECTION 301 GENERAL
301.1 SCOPE. Buildings shall be designed to include the green building measures specified as mandatory in the application checklists contained in this code. Voluntary green building measures are also included in the application checklists and may be included in the design and construction of structures covered by this code, but are not required unless adopted by a city, county, or city and county as specified in Section 101.7. 301.1.1 Additions and alterations. [HCD] The mandatory provisions of Chapter 4 shall be applied to additions or alterations of existing residential buildings where the addition or alteration increases the building's conditioned area, volume, or size. The requirements shall apply only to and/or within the specific area of the addition or alteration.

The mandatory provision of Section 4.106.4.2 may apply to additions or alterations of existing parking facilities or the addition of new parking facilities serving existing multifamily buildings. See Section

4.106.4.3 for application.

Note: Repairs including, but not limited to, resurfacing, restriping and repairing or maintaining existing lighting fixtures are not considered alterations for the purpose of this section.

Note: On and after January 1, 2014, residential buildings undergoing permitted alterations, additions, or improvements shall replace noncompliant plumbing fixtures with water-conserving plumbing fixtures.

Plumbing fixture replacement is required prior to issuance of a certificate of final completion, certificate of occupancy or final permit approval by the local building department. See Civil Code Section 1101.1, et seq., for the definition of a noncompliant plumbing fixture, types of residential buildings affected and other important enactment dates.
301.2 LOW-RISE AND HIGH-RISE RESIDENTIAL BUILDINGS. [HCD] The provisions of individual sections of CALGreen may apply to either low-rise residential buildings high-rise residential buildings, or both. Individual sections will be designated by banners to indicate where the section applies specifically to low-rise only (LR) or high-rise only (HR). When the section applies to both low-rise and high-rise buildings, no banner will be used.

SECTION 302 MIXED OCCUPANCY BUILDINGS
302.1 MIXED OCCUPANCY BUILDINGS. In mixed occupancy buildings, each portion of a building shall comply with the specific green building measures applicable to each specific occupancy.

Exceptions:

1. [HCD] Accessory structures and accessory occupancies serving residential buildings shall comply with Chapter 4 and Appendix A4, as applicable.

2. [HCD] For purposes of CALGreen, live/work units, complying with Section 419 of the California Building Code, shall not be considered mixed occupancies. Live/Work units shall comply with Chapter 4 and Appendix A4, as applicable.

4.106.4.2 New multifamily dwellings, hotels and motels and new residential parking facilities.

When parking is provided, parking spaces for new multifamily dwellings, hotels and motels shall meet the requirements of Section 4.106.4.2.2. Calculations for spaces shall be rounded up to the nearest whole number. A parking space served by electric vehicle supply equipment or designed as an EV charging space shall count as at least one standard automobile parking space only for the purpose of complying with any applicable minimum parking space requirements established by a local jurisdiction. See Vehicle Code Section 22511.2 for further details.

4.106.4.2.1 Reserved.

4.106.4.2.2 Multifamily dwellings, hotels and motels

1. EV ready parking spaces with receptacles.
a. Hotels and motels. Forty (40) percent of the total number of parking spaces shall be equipped with low power Level 2 EV charging receptacles.
b. Multifamily parking facilities. Forty (40) percent of the total number of parking spaces shall be equipped with low power Level 2 EV charging receptacles. EV charging receptacles required by this section shall be located in at least one assigned parking space per dwelling unit where assigned parking is provided but need not exceed forty (40) percent of the total number of assigned parking spaces provided on the site.

Exception: Areas of parking facilities served by parking lifts, including but not limited to automated mechanical-access open parking garages as defined in the California Building Code; or parking facilities otherwise incapable of supporting electric vehicle charging. c. Receptacle power source. EV charging receptacles in multifamily parking facilities shall be provided with a dedicated branch circuit connected to the dwelling unit’s electrical panel, unless determined as infeasible by the project builder or designer and subject to concurrence of the local enforcing agency.

Exception: Areas of parking facilities served by parking lifts, including but not limited to automated mechanical-access open parking garages as defined in the California Building Code; or parking facilities otherwise incapable of supporting electric vehicle charging. d. Receptacle configurations. 208/240V EV charging receptacles shall comply with one of the following configurations:

1. For 20-ampere receptacles, NEMA 6-20R

2. For 30-ampere receptacles, NEMA 14-30R

3. For 50-ampere receptacles, NEMA 14-50R

2. EV ready parking spaces with EV chargers.
a. Hotels and motels. Ten (10) percent of the total number of parking spaces shall be equipped with Level 2 EV chargers. At least fifty (50) percent of the required EV chargers shall be equipped with J1772 connectors.
b. Multifamily parking facilities. Ten (10) percent of the total number of parking spaces shall be equipped with Level 2 EV chargers. At least fifty (50) percent of the required EV chargers shall be equipped with J1772 connectors. Where common use parking or unassigned parking is provided, EV chargers shall be located in common use or unassigned parking areas and shall be available for use by all residents or guests.

Where low power Level 2 EV charging receptacles or Level 2 EV chargers are installed beyond the minimum required, an automatic load management system (ALMS) may be used to reduce the maximum required electrical capacity to each space served by the ALMS. The electrical system and any on-site distribution transformers shall have sufficient capacity to deliver at least 3.3 kW simultaneously to each EV charging station (EVCS) served by the ALMS. The branch circuit shall have a minimum capacity of 40 amperes, and installed EV chargers shall have a capacity of not less than 30 amperes.

4.106.4.2.2.1 Electric vehicle charging stations (EVCS).

Electric vehicle charging stations required by Section 4.106.4.2.2, Item 2, with EV chargers installed shall comply with Section 4.106.4.2.2.1.1.

Exception: Electric vehicle charging stations serving public accommodations, public housing, motels and hotels shall not be required to comply with this section. See California Building Code, Chapter 11B, for applicable requirements.

4.106.4.2.2.1.1 Electric vehicle charging stations (EVCS) spaces with EV chargers installed; dimensions and location.

EVCS spaces shall be designed to comply with the following:

1. The minimum length of each EVCS space shall be 18 feet (5486 mm).

2. The minimum width of each EVCS space shall be 9 feet (2743 mm).

3. One in every 25 EVCS spaces, but not less than one, shall also have an 8-foot (2438 mm) wide minimum aisle. A 5-foot (1524 mm) wide minimum aisle shall be permitted provided the minimum width of the EVCS space is 12 feet (3658 mm). Surface slope for this EVCS space and the aisle shall not exceed 1 unit vertical in 48 units horizontal (2.083 percent slope) in any direction. These EVCS spaces shall also comply with at least one of the following:
a. The EVCS space shall be located adjacent to an accessible parking space meeting the requirements of the California Building Code, Chapter 11A, to allow use of the EV charger from the accessible parking space.
b. The EVCS space shall be located on an accessible route, as defined in the California Building Code, Chapter 2, to the building.

Exception: Electric vehicle charging stations designed and constructed in compliance with the California Building Code, Chapter 11B, are not required to comply with Section 4.106.4.2.2.1.1.

4.106.4.2.2.1.2 Accessible electric vehicle charging station spaces.

In addition to the requirements in Section 4.106.4.2.2.1.1, all EV chargers, where installed, shall comply with the accessibility provisions for EV chargers in the California Building Code, Chapter 11B. EV ready spaces and EVCS in multifamily developments shall comply with California Building Code, Chapter 11A, Section 1109A.

4.106.4.2.3 Reserved.

4.106.4.2.4 Reserved.

4.106.4.2.5 Electric vehicle ready space signage.

Electric vehicle ready spaces shall be identified by signage or pavement markings, in compliance with Caltrans Traffic Operations Policy Directive 13-01 (Zero Emission Vehicle Signs and Pavement Markings) or its successor(s).

4.106.4.3 Electric vehicle charging for additions and alterations of parking facilities serving existing multi-family buildings.

Where new parking facilities are added, or electrical systems or lighting of existing parking facilities are added or altered and the work requires a building permit, ten (10) percent of the total number of parking spaces added or altered shall be EV capable spaces to support future Level 2 electric vehicle supply equipment. The service panel or subpanel circuit directory shall identify the overcurrent protective device space(s) reserved for future EV charging purposes as “EV CAPABLE.”
Notes:

1.Construction documents are intended to demonstrate the project’s capability and capacity for facilitating future EV charging.

2.There is no requirement for EV spaces to be constructed or available until EV chargers are installed for use.

SECTION 4.501 GENERAL

4.501.1 Scope
The provisions of this chapter shall outline means of reducing the quality of air contaminants that are odorous, irritating and/or harmful to the comfort and well being of a building's installers, occupants and neighbors.

SECTION 4.502 DEFINITIONS

5.102.1 DEFINITIONS
The following terms are defined in Chapter 2 (and are included here for reference) AGRIFIBER PRODUCTS. Agrifiber products include wheatboard, strawboard, panel substrates and door cores, not including furniture, fixtures and equipment (FF&E) not considered base building elements.

COMPOSITE WOOD PRODUCTS. Composite wood products include hardwood plywood, particleboard and medium density fiberboard. "Composite wood products" does not include hardboard, structural plywood, structural panels, structural composite lumber, oriented strand board, glued laminated timber, prefabricated wood I-joists or finger-jointed lumber, all as specified in California Code of regulations (CCR), title 17, Section 93120.1.

DIRECT-VENT APPLIANCE. A fuel-burning appliance with a sealed combustion system that draws all air for combustion from the outside atmosphere and discharges all flue gases to the outside atmosphere. Y N/A RESPON. Y N/A Y N/A Y N/A PARTY RESPON. PARTY RESPON. PARTY RESPON. PARTY 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE RESIDENTIAL MANDATORY MEASURES, SHEET 1 (July 2024 Supplement) Y = YES N/A = NOT APPLICABLE RESPON. PARTY = RESPONSIBLE PARTY (ie: ARCHITECT, ENGINEER, OWNER, CONTRACTOR, INSPECTOR ETC.)

4.201 GENERAL

4.201.1 SCOPE. For the purposes of mandatory energy efficiency standards in this code, the California Energy Commission will continue to adopt mandatory standards.

DIVISION 4.2 ENERGY EFFICIENCY
TABLE H-2

STANDARDS FOR COMMERCIAL PRE-RINSE SPRAY
VALUES MANUFACTURED ON OR AFTER JANUARY 28, 2019

PRODUCT CLASS
[spray force in ounce force (ozf)] MAXIMUM FLOW RATE (gpm) Product Class 1 (≤ 1.00
Product Class 2 (> 5.0 ozf and ≤ 1.20
Product Class 3 (> 8.0 ozf) 1.28
298
Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

CALGREEN RESIDENTIAL CHECKLIST
G-0.3
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026

REVISIONS
NO. DATE DESCRIPTION
MAXIMUM INCREMENTAL REACTIVITY (MIR). The maximum change in weight of ozone formed by adding a compound to the "Base Reactive Organic Gas (ROG) Mixture" per weight of compound added, expressed to hundredths of a gram (g O³/g ROC).

Note: MIR values for individual compounds and hydrocarbon solvents are specified in CCR, Title 17, Sections 94700 and 94701.

MOISTURE CONTENT. The weight of the water in wood expressed in percentage of the weight of the oven-dry wood.

PRODUCT-WEIGHTED MIR (PWMIR). The sum of all weighted-MIR for all ingredients in a product subject to this article. The PWMIR is the total product reactivity expressed to hundredths of a gram of ozone formed per gram of product (excluding container and packaging).

Note: PWMIR is calculated according to equations found in CCR, Title 17, Section 94521 (a).

REACTIVE ORGANIC COMPOUND (ROC). Any compound that has the potential, once emitted, to contribute to ozone formation in the troposphere.

VOC. A volatile organic compound (VOC) broadly defined as a chemical compound based on carbon chains or rings with vapor pressures greater than 0.1 millimeters of mercury at room temperature. These compounds typically contain hydrogen and may contain oxygen, nitrogen and other elements. See CCR Title 17, Section 94508(a).

4.503 FIREPLACES

4.503.1 GENERAL. Any installed gas fireplace shall be a direct-vent sealed-combustion type. Any installed woodstove or pellet stove shall comply with U.S. EPA New Source Performance Standards (NSPS) emission limits as applicable, and shall have a permanent label indicating they are certified to meet the emission limits. Woodstoves, pellet stoves and fireplaces shall also comply with applicable local ordinances.

4.504 POLLUTANT CONTROL

4.504.1 COVERING OF DUCT OPENINGS & PROTECTION OF MECHANICAL EQUIPMENT DURING CONSTRUCTION. At the time of rough installation, during storage on the construction site and until final startup of the heating, cooling and ventilating equipment, all duct and other related air distribution component openings shall be covered with tape, plastic, sheet metal or other methods acceptable to the enforcing agency to reduce the amount of water, dust or debris which may enter the system.

4.504.2 FINISH MATERIAL POLLUTANT CONTROL. Finish materials shall comply with this section.

4.504.2.1 Adhesives, Sealants and Caulks. Adhesives, sealant and caulks used on the project shall meet the requirements of the following standards unless more stringent local or regional air pollution or air quality management district rules apply:

1. Adhesives, adhesive bonding primers, adhesive primers, sealants, sealant primers and caulks shall comply with local or regional air pollution control or air quality management district rules where applicable or SCAQMD Rule 1168 VOC limits, as shown in Table 4.504.1 or 4.504.2, as applicable.

Such products also shall comply with the Rule 1168 prohibition on the use of certain toxic compounds (chloroform, ethylene dichloride, methylene chloride, perchloroethylene and tricloroethylene), except for aerosol products, as specified in Subsection 2 below.

2. Aerosol adhesives, and smaller unit sizes of adhesives, and sealant or caulking compounds (in units of product, less packaging, which do not weigh more than 1 pound and do not consist of more than 16 fluid ounces) shall comply with statewide VOC standards and other requirements, including prohibitions on use of certain toxic compounds, of California Code of Regulations, Title 17, commencing with section 94507.

4.504.2.2 Paints and Coatings. Architectural paints and coatings shall comply with VOC limits in Table 1 of the ARB Architectural Suggested Control Measure, as shown in Table 4.504.3, unless more stringent local limits apply. The VOC content limit for coatings that do not meet the definitions for the specialty coatings categories listed in Table 4.504.3 shall be determined by classifying the coating as a Flat, Nonflat or Nonflat-High Gloss coating, based on its gloss, as defined in subsections 4.21, 4.36, and 4.37 of the 2007 California Air Resources Board, Suggested Control Measure, and the corresponding Flat, Nonflat or Nonflat-High Gloss VOC limit in Table 4.504.3 shall apply.

4.504.2.3 Aerosol Paints and Coatings. Aerosol paints and coatings shall meet the Product-weighted MIR Limits for ROC in Section 94522(a)(2) and other requirements, including prohibitions on use of certain toxic compounds and ozone depleting substances, in Sections 94522(e)(1) and (f)(1) of California Code of Regulations, Title 17, commencing with Section 94520; and in areas under the jurisdiction of the Bay Area Air Quality Management District additionally comply with the percent VOC by weight of product limits of Regulation 8, Rule 49.

4.504.2.4 Verification. Verification of compliance with this section shall be provided at the request of the enforcing agency. Documentation may include, but is not limited to, the following:

1. Manufacturer's product specification.

2. Field verification of on-site product containers.

CHAPTER 7

INSTALLER & SPECIAL INSPECTOR QUALIFICATIONS
702 QUALIFICATIONS
702.1 INSTALLER TRAINING. HVAC system installers shall be trained and certified in the proper installation of HVAC systems including ducts and equipment by a nationally or regionally recognized training or certification program. Uncertified persons may perform HVAC installations when under the direct supervision and responsibility of a person trained and certified to install HVAC systems or contractor licensed to install HVAC systems.

Examples of acceptable HVAC training and certification programs include but are not limited to the following:

1. State certified apprenticeship programs.

2. Public utility training programs.

3. Training programs sponsored by trade, labor or statewide energy consulting or verification organizations.

4. Programs sponsored by manufacturing organizations.

5. Other programs acceptable to the enforcing agency.
702.2 SPECIAL INSPECTION [HCD]. When required by the enforcing agency, the owner or the responsible entity acting as the owner's agent shall employ one or more special inspectors to provide inspection or other duties necessary to substantiate compliance with this code. Special inspectors shall demonstrate competence to the satisfaction of the enforcing agency for the particular type of inspection or task to be performed. In addition to other certifications or qualifications acceptable to the enforcing agency, the following certifications or education may be considered by the enforcing agency when evaluating the qualifications of a special inspector:

1. Certification by a national or regional green building program or standard publisher.

2. Certification by a statewide energy consulting or verification organization, such as HERS raters, building performance contractors, and home energy auditors.

3. Successful completion of a third party apprentice training program in the appropriate trade.

4. Other programs acceptable to the enforcing agency.

Notes:

1. Special inspectors shall be independent entities with no financial interest in the materials or the project they are inspecting for compliance with this code.

2. HERS raters are special inspectors certified by the California Energy Commission (CEC) to rate homes in California according to the Home Energy Rating System (HERS). [BSC] When required by the enforcing agency, the owner or the responsible entity acting as the owner's agent shall employ one or more special inspectors to provide inspection or other duties necessary to substantiate compliance with this code. Special inspectors shall demonstrate competence to the satisfaction of the enforcing agency for the particular type of inspection or task to be performed. In addition, the special inspector shall have a certification from a recognized state, national or international association, as determined by the local agency. The area of certification shall be closely related to the primary job function, as determined by the local agency.

Note: Special inspectors shall be independent entities with no financial interest in the materials or the project they are inspecting for compliance with this code. 703 VERIFICATIONS
703.1 DOCUMENTATION. Documentation used to show compliance with this code shall include but is not limited to, construction documents, plans, specifications, builder or installer certification, inspection reports, or other methods acceptable to the enforcing agency which demonstrate substantial conformance. When specific documentation or special inspection is necessary to verify compliance, that method of compliance will be specified in the appropriate section or identified applicable checklist.

4.505 INTERIOR MOISTURE CONTROL

4.505.1 General. Buildings shall meet or exceed the provisions of the California Building Standards Code. 4.505.2 CONCRETE SLAB FOUNDATIONS. Concrete slab foundations required to have a vapor retarder by California Building Code, Chapter 19, or concrete slab-on-ground floors required to have a vapor retarder by the California Residential Code, Chapter 5, shall also comply with this section.

4.505.2.1 Capillary break. A capillary break shall be installed in compliance with at least one of the following:

1. A 4-inch (101.6 mm) thick base of 1/2 inch (12.7mm) or larger clean aggregate shall be provided with a vapor barrier in direct contact with concrete and a concrete mix design, which will address bleeding, shrinkage, and curling, shall be used. For additional information, see American Concrete Institute, ACI 302.2R-06.

2. Other equivalent methods approved by the enforcing agency.

3. A slab design specified by a licensed design professional.

4.505.3 MOISTURE CONTENT OF BUILDING MATERIALS. Building materials with visible signs of water damage shall not be installed. Wall and floor framing shall not be enclosed when the framing members exceed 19 percent moisture content. Moisture content shall be verified in compliance with the following:

1. Moisture content shall be determined with either a probe-type or contact-type moisture meter.Equivalent moisture verification methods may be approved by the enforcing agency and shall satisfy requirements found in Section 101.8 of this code.

2. Moisture readings shall be taken at a point 2 feet (610 mm) to 4 feet (1219 mm) from the grade stamped end of each piece verified.

3. At least three random moisture readings shall be performed on wall and floor framing with documentation acceptable to the enforcing agency provided at the time of approval to enclose the wall and floor framing.

Insulation products which are visibly wet or have a high moisture content shall be replaced or allowed to dry prior to enclosure in wall or floor cavities. Wet-applied insulation products shall follow the manufacturers' drying recommendations prior to enclosure.

4.506 INDOOR AIR QUALITY AND EXHAUST

4.506.1 Bathroom exhaust fans. Each bathroom shall be mechanically ventilated and shall comply with the following:

1. Fans shall be ENERGY STAR compliant and be ducted to terminate outside the building.

2. Unless functioning as a component of a whole house ventilation system, fans must be controlled by a humidity control.
a. Humidity controls shall be capable of adjustment between a relative humidity range less than or equal to 50% to a maximum of 80%. A humidity control may utilize manual or automatic means of adjustment.
b. A humidity control may be a separate component to the exhaust fan and is not required to be integral (i.e., built-in)
Notes:

1. For the purposes of this section, a bathroom is a room which contains a bathtub, shower or tub/shower combination.

2. Lighting integral to bathroom exhaust fans shall comply with the California Energy Code.

4.507 ENVIRONMENTAL COMFORT

4.507.2 HEATING AND AIR-CONDITIONING SYSTEM DESIGN. Heating and air conditioning systems shall be sized, designed and have their equipment selected using the following methods:

1. The heat loss and heat gain is established according to ANSI/ACCA 2 Manual J - 2011 (Residential Load Calculation), ASHRAE handbooks or other equivalent design software or methods.

2. Duct systems are sized according to ANSI/ACCA 1 Manual D - 2014 (Residential Duct Systems), ASHRAE handbooks or other equivalent design software or methods.

3. Select heating and cooling equipment according to ANSI/ACCA 3 Manual S - 2014 (Residential Equipment Selection), or other equivalent design software or methods.

Exception: Use of alternate design temperatures necessary to ensure the system functions are acceptable.

TABLE 4.504.1 - ADHESIVE VOC LIMIT1,2
(Less Water and Less Exempt Compounds in Grams per Liter)

ARCHITECTURAL APPLICATIONS VOC LIMIT
INDOOR CARPET ADHESIVES 50
CARPET PAD ADHESIVES 50
OUTDOOR CARPET ADHESIVES 150
WOOD FLOORING ADHESIVES 100
RUBBER FLOOR ADHESIVES 60
SUBFLOOR ADHESIVES 50
CERAMIC TILE ADHESIVES 65
VCT & ASPHALT TILE ADHESIVES 50
DRYWALL & PANEL ADHESIVES 50
COVE BASE ADHESIVES 50
MULTIPURPOSE CONSTRUCTION ADHESIVE 70
STRUCTURAL GLAZING ADHESIVES 100
SINGLE-PLY ROOF MEMBRANE ADHESIVES 250
OTHER ADHESIVES NOT LISTED 50

SPECIALTY APPLICATIONS
PVC WELDING 510
CPVC WELDING 490
ABS WELDING 325
PLASTIC CEMENT WELDING 250
ADHESIVE PRIMER FOR PLASTIC 550
CONTACT ADHESIVE 80
SPECIAL PURPOSE CONTACT ADHESIVE 250
STRUCTURAL WOOD MEMBER ADHESIVE 140
TOP & TRIM ADHESIVE 250

SUBSTRATE SPECIFIC APPLICATIONS
METAL TO METAL 30
PLASTIC FOAMS 50
POROUS MATERIAL (EXCEPT WOOD) 50
WOOD 30
FIBERGLASS 80

1. IF AN ADHESIVE IS USED TO BOND DISSIMILAR SUBSTRATES TOGETHER, THE ADHESIVE WITH THE HIGHEST VOC CONTENT SHALL BE ALLOWED.

2. FOR ADDITIONAL INFORMATION REGARDING METHODS TO MEASURE

THE VOC CONTENT SPECIFIED IN THIS TABLE, SEE SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT RULE 1168.

TABLE 4.504.2 - SEALANT VOC LIMIT
(Less Water and Less Exempt Compounds in Grams per Liter)

SEALANTS VOC LIMIT
ARCHITECTURAL 250
MARINE DECK 760
NONMEMBRANE ROOF 300
ROADWAY 250
SINGLE-PLY ROOF MEMBRANE 450
OTHER 420

SEALANT PRIMERS

ARCHITECTURAL
NON-POROUS 250
POROUS 775
MODIFIED BITUMINOUS 500
MARINE DECK 760
OTHER 750
TABLE 4.504.5 - FORMALDEHYDE LIMITS1 MAXIMUM FORMALDEHYDE EMISSIONS IN PARTS PER MILLION

PRODUCT CURRENT LIMIT
HARDWOOD PLYWOOD VENEER CORE 0.05
HARDWOOD PLYWOOD COMPOSITE CORE 0.05
PARTICLE BOARD 0.09
MEDIUM DENSITY FIBERBOARD 0.11
THIN MEDIUM DENSITY FIBERBOARD2 0.13

1. VALUES IN THIS TABLE ARE DERIVED FROM THOSE SPECIFIED BY THE CALIF. AIR RESOURCES BOARD, AIR TOXICS CONTROL

MEASURE FOR COMPOSITE WOOD AS TESTED IN ACCORDANCE
WITH ASTM E 1333. FOR ADDITIONAL INFORMATION, SEE CALIF.

CODE OF REGULATIONS, TITLE 17, SECTIONS 93120 THROUGH
93120.12.

2. THIN MEDIUM DENSITY FIBERBOARD HAS A MAXIMUM
THICKNESS OF 5/16" (8 MM).

TABLE 4.504.3 - VOC CONTENT LIMITS FOR
ARCHITECTURAL COATINGS2,3

GRAMS OF VOC PER LITER OF COATING, LESS WATER & LESS EXEMPT

COMPOUNDS

COATING CATEGORY VOC LIMIT
FLAT COATINGS 50
NON-FLAT COATINGS 100
NONFLAT-HIGH GLOSS COATINGS 150

SPECIALTY COATINGS
ALUMINUM ROOF COATINGS 400
BASEMENT SPECIALTY COATINGS 400
BITUMINOUS ROOF COATINGS 50
BITUMINOUS ROOF PRIMERS 350
BOND BREAKERS 350
CONCRETE CURING COMPOUNDS 350
CONCRETE/MASONRY SEALERS 100
DRIVEWAY SEALERS 50
DRY FOG COATINGS 150
FAUX FINISHING COATINGS 350
FIRE RESISTIVE COATINGS 350
FLOOR COATINGS 100
FORM-RELEASE COMPOUNDS 250
GRAPHIC ARTS COATINGS (SIGN PAINTS) 500
HIGH TEMPERATURE COATINGS 420
INDUSTRIAL MAINTENANCE COATINGS 250
LOW SOLIDS COATINGS1 120
MAGNESITE CEMENT COATINGS 450
MASTIC TEXTURE COATINGS 100
METALLIC PIGMENTED COATINGS 500
MULTICOLOR COATINGS 250
PRETREATMENT WASH PRIMERS 420
PRIMERS, SEALERS, & UNDERCOATERS 100
REACTIVE PENETRATING SEALERS 350
RECYCLED COATINGS 250
ROOF COATINGS 50
RUST PREVENTATIVE COATINGS 250

SHELLACS
CLEAR 730
OPAQUE 550

SPECIALTY PRIMERS, SEALERS &
UNDERCOATERS 100
STAINS 250
STONE CONSOLIDANTS 450
SWIMMING POOL COATINGS 340
TRAFFIC MARKING COATINGS 100
TUB & TILE REFINISH COATINGS 420
WATERPROOFING MEMBRANES 250
WOOD COATINGS 275
WOOD PRESERVATIVES 350
ZINC-RICH PRIMERS 340

1. GRAMS OF VOC PER LITER OF COATING, INCLUDING WATER &

EXEMPT COMPOUNDS

2. THE SPECIFIED LIMITS REMAIN IN EFFECT UNLESS REVISED LIMITS ARE LISTED IN SUBSEQUENT COLUMNS IN THE TABLE.

3. VALUES IN THIS TABLE ARE DERIVED FROM THOSE SPECIFIED BY

THE CALIFORNIA AIR RESOURCES BOARD, ARCHITECTURAL COATINGS SUGGESTED CONTROL MEASURE, FEB. 1, 2008. MORE INFORMATION IS AVAILABLE FROM THE AIR RESOURCES BOARD.

DIVISION 4.5 ENVIRONMENTAL QUALITY (continued)

4.504.3 CARPET SYSTEMS. All carpet installed in the building interior shall meet the requirements of the California Department of Public Health, "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers," Version 1.2, January 2017 (Emission testing method for California Specification 01350)
See California Department of Public Health's website for certification programs and testing labs. https://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx.

4.504.3.1 Carpet cushion. All carpet cushion installed in the building interior shall meet the requirements of the California Department of Public Health, "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers," Version 1.2, January 2017 (Emission testing method for California Specification 01350) See California Department of Public Health's website for certification programs and testing labs. https://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx.

4.504.3.2 Carpet adhesive. All carpet adhesive shall meet the requirements of Table 4.504.1.

4.504.4 RESILIENT FLOORING SYSTEMS. Where resilient flooring is installed , at least 80% of floor area receiving resilient flooring shall meet the requirements of the California Department of Public Health, "Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers," Version 1.2, January 2017 (Emission testing method for California Specification 01350) See California Department of Public Health's website for certification programs and testing labs. hhtps://www.cdph.ca.gov/Programs/CCDPHP/DEODC/EHLB/IAQ/Pages/VOC.aspx.

4.504.5 COMPOSITE WOOD PRODUCTS. Hardwood plywood, particleboard and medium density fiberboard composite wood products used on the interior or exterior of the buildings shall meet the requirements for formaldehyde as specified in ARB's Air Toxics Control Measure for Composite Wood (17 CCR 93120 et seq.), by or before the dates specified in those sections, as shown in Table 4.504.5

4.504.5.1 Documentation. Verification of compliance with this section shall be provided as requested by the enforcing agency. Documentation shall include at least one of the following:

1. Product certifications and specifications.

2. Chain of custody certifications.

3. Product labeled and invoiced as meeting the Composite Wood Products regulation (see CCR, Title 17, Section 93120, et seq.).

4. Exterior grade products marked as meeting the PS-1 or PS-2 standards of the Engineered Wood Association, the Australian AS/NZS 2269, European 636 3S standards, and Canadian CSA 0121, CSA 0151, CSA 0153 and CSA 0325 standards.

5. Other methods acceptable to the enforcing agency. Y N/A RESPON. Y N/A Y N/A Y N/A PARTY RESPON. PARTY RESPON. PARTY RESPON. PARTY 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE RESIDENTIAL MANDATORY MEASURES, SHEET 2 (July 2024 Supplement) Y = YES N/A = NOT APPLICABLE RESPON. PARTY = RESPONSIBLE PARTY (ie: ARCHITECT, ENGINEER, OWNER, CONTRACTOR, INSPECTOR ETC.)
299

EXISTING MAIN DWELLING

STREET NAME

ADDRESS

FOOTPRINT AREA (SF)
F.F. ELEV

XXX' (DISTANCE)
N XX°XX'XX" W

XXX' (DISTANCE)
S XX°XX'XX" E

XXX' (DISTANCE)
N XX°XX'XX" W

XXX' (DISTANCE)
S XX°XX'XX" E

EXISTING SIDEWALK
CL
XX' - XX" XX' - XX" XX' - XX"
XX' - XX" XX' - XX" XX' - XX"
XX' - XX"

SETBACK
XX' - XX"

SETBACK

SETBACK
XX' - XX"

SETBACK
XX' - XX"
X

PROPOSED ADU

EXAMPLE

FOOTPRINT AREA (SF)
F.F. ELEV
XX' - XX"

ADU LENGTH
XX' - XX" XX' - XX"
XX' - XX"

ADU WIDTH
X' - X" XX' - XX"

INDICATE ROOF

OVERHANGS AND

PORCHES

EXISTING DRIVEWAY
SLOPE (2% MIN, 12% MAX)

SLOPE DN

EXISTING
SHED
XX' - XX"

XXXXXXXXXXX

EXISTING

RETAINING WALL

PROPERTY
LINE, TYP.

SETBACK
LINE, TYP.

XXX
XXX
PLAN
NORTH
N

EXISTING FENCE
XX' - XX"

EASEMENT
XX' - XX"
0 SCALE:
5' - 0" 10' - 0" 20' - 0"
1" = 10' - 0"

EXISTING

HARDSCAPE PATIO

EXISTING
CURB
XX' - XX"
G G G
G
G

GE E E E E
W

SS SS SS SS SS SS SS SS SS
E

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

1. 2.

3. 4.

5. 6.

7. 8.

9. REFER TO GENERAL NOTES SHEET A1.0 FOR ADDITIONAL
REQUIREMENTS.

CALL BEFORE YOU DIG! CONTACT UNDERGROUND SERVICE

ALERT OF CALIFORNIA AT LEAST TWO WORKING DAYS PRIOR TO
EXCAVATING, NOT INCLUDING THE DATE OF NOTIFICATION.

LOT SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
FOUNDATION WALLS. THE GRADE SHALL FALL NOT FEWER THAN
6 IN WITHIN THE FIRST 10 FT (5% MIN).

WHERE LOT LINES, WALLS, SLOPES, OR OTHER PHYSICAL
BARRIER PROHIBIT 6 IN OF FALL WITHIN 10 FT, DRAINS OR

SWALES SHALL BE CONSTRUCTED TO ENSURE DRAINAGE AWAY
FROM THE STRUCTURE.

IMPERVIOUS SURFACES WITHIN 10 FT OF THE BUILDING
FOUNDATION SHALL BE SLOPED NOT LESS THAN 2% AWAY FROM
THE BUILDING.

DWELLING UNITS 150 FT OR MORE FROM A PUBLIC RIGHT-OFWAY SHALL BE REQUIRED TO PROVIDE "ALL-WEATHER ACCESS"

FOR EMERGENCY VEHICLES AS REQUIRED BY THE RIVERSIDE
COUNTY FIRE DEPARTMENT.

EACH HORIZONTAL DRAINAGE PIPE SHALL BE PROVIDED WITH A

CLEAN OUT AT ITS UPPER TERMINAL, AND EACH RUN OF PIPING THAT IS MORE THAN100 FEET IN TOTAL DEVELOPED LENGTH
SHALL BE PROVIDED WITH A CLEAN OUT FOR EACH 100 FEET, OR FRACTION THEREOF, IN LENGTH OF SUCH PIPING. AN

ADDITIONAL CLEANOUT SHALL BE PROVIDED IN A DRAINAGE LINE

FOR EACH AGGREGATE HORIZONTAL CHANGE IN DIRECTION
EXCEEDING 135 DEGREES. [CPC 2022 SECTION 707.4]

PLUMBING FIXTURES AND FITTINGS INSTALLED IN RESIDENTIAL

BUILDINGS SHALL COMPLY WITH THE PRESCRIPTIVE
REQUIREMENTS OF SECTIONS 4.303.1.1 - 4.303.1.4.4 OF CRC 2022.

PLUMBING FIXTURES AND FITTINGS REQUIRED IN SECTION

4.303.1 SHALL BE INSTALLED IN ACCORDANCE WITH CPC 2022
AND SHALL MEET THE APPLICABLE REFERENCE STANDARDS.

SITE PLAN GENERAL SHEET NOTES

SITE PLAN CHECKLIST REQUIREMENTS

APPLICANT NAME, ADDRESS, AND CONTACT INFORMATION

PROPERTY OWNER NAME, ADDRESS, AND CONTACT

INFORMATION IF DIFFERENT FROM APPLICANT

ACCESSOR'S PARCEL NUMBER OF PROPERTY WHERE THE ADU

IS PROPOSED

PROPERTY LINE METES AND BOUNDS

FOOTPRINT AND AREA OF EXISTING AND PROPOSED BUILDINGS

AND STRUCTURES

BUILDING SEPARATION DIMENSIONS BETWEEN THE PROPOSED

ADU AND ANY EXISTING BUILDING AND STRUCTURES

LOCATION AND HEIGHT OF ALL FENCES AND RETAINING WALLS

INDICATE AND DIMENSION ALL REQUIRED AND PROPOSED

SETBACKS AND LABEL YARDS

PROVIDE LOT AREA

LOT COVERAGE CALCULATION

LOCATION AND SIZE OF EXISTING AND NEW UTILITIES

INCLUDING LATERAL LINES, WELLS, SEPTIC TANKS, LEACH
LINES, EXISTING SEEPAGE PITS, AND DRAINAGE STRUCTURES.

PROVIDE LOCATION OF SEWER CLEANOUTS.

IDENTIFY THE PIPING MATERIALS FOR EACH PLUMBING
SYSTEM.

LOCATION AND DIMENSIONS OF ALL EASEMENTS

INDICATE ALL METHODS OF CIRCULATION INCLUDING

SIDEWALKS, STREETS, DRIVEWAYS, OFF-STREET PARKING,
PATHWAYS, AND ANY HARDSCAPING.

LOCATION OF EXISTING AND NEW METERS

INDICATE SUBPANEL SIZE AND PROVIDE AN ELECTRICAL LOAD

CALCULATION FOR THE EXISTING PANEL TO VERIFY THE

CAPCITY OF THE EXISTING PANEL IS SUFFICIENT TO CARRY
THE LOAD OF THE EXISTING LOAD AND NEW SUBPANEL.

SITE CONTOURS, SPOT ELEVATIONS AT ALL STAIRS, RAMPS &

LANDINGS, AND FINISH FLOOR ELEVATIONS

LOCATION OF PROPOSED VEGETATION

LEGEND OF SYMBOLS, LINE TYPES, AND ABBREVIATIONS

DRAWING SCALE

NORTH ARROW
LEGEND

CONCRETE PAVING

LANDSCAPE AREA

PROPERTY LINE

SETBACK

EXISTING CONTOURS

NEW CONTOURS

RETAINING WALL

XX FENCE LINE

EASEMENT

ELECTRICAL UTILITY LINE

GAS UTILITY LINE

WATER UTILITY LINE

SEWER LINE

SPOT ELEVATION
EGW

XXX' SS
XXX'

ELECTRICAL PANEL
(SIZE)

GAS METER

W WATER METER EG
Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

ARCHITECTURAL - SITE PLAN
AS-1.1
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026
SCALE: 1" = 10'-0"

SAMPLE SITE PLAN
1 REVISIONS
NO. DATE DESCRIPTION
300

ARCHITECTURAL MATERIALS LEGEND

CONCRETE
EARTH

BATT INSULATION

ROOF, TAPERED, CAVITY OR RIGID INSULATION

PLYWOOD

HORIZONTAL FIBER CEMENT SIDING

BOARD AND BATTEN SIDING

STONE VENEER
STUCCO

TILE ROOF

STANDING SEAM METAL ROOF

SHINGLE ROOF

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

1. 2.

3. 4.

5. 6.

7. 8.

9. 10.

11. 12.

13. 14.

15. 16.

17. 18.

19. CONSTRUCTION AND CONSTRUCTION DOCUMENTATION MUST COMPLY WITH APPLICABLE CODES AND ORDINANCES, LAWS AND SAFETY ORDERS AS DIRECTED BY LOCAL JURISDICTION.

APPLICATIONS FOR WHICH NO PERMIT IS ISSUED WITHIN 180 DAYS FOLLOWING THE DATE OF APPLICATION SHALL AUTOMATICALLY EXPIRE. [CRC R105.3.2]

EVERY PERMIT ISSUED SHALL BECOME INVALID UNLESS THE WORK AUTHORIZED COMMENCES WITHIN 180 DAYS AFTER ITS ISSUANCE OR IF THE WORK AUTHORIZED IS SUSPENDED OR ABANDONED FOR A PERIOD OF 180 DAYS. A SUCCESSFUL INSPECTION MUST BE OBTAINED WITHIN 180 DAYS. [CRC R105.5]
ALL DIMENSIONS ARE IN FEET / INCHES UNLESS NOTED OTHERWISE.

DO NOT SCALE DIMENSIONS FROM DRAWINGS. THE CONTRACTOR SHALL NOTIFY THE OWNER IF A DISCREPANCY IS FOUND.

ALL DIMENSIONS ARE TO FACE OF STUD UNLESS NOTED OTHERWISE.

ALL NON-DIMENSIONED DOOR LOCATIONS SHALL BE LOCATED 3 ½ ” FROM THE ADJACENT WALL TO THE HINGE SIDE OF THE DOOR OPENING.

DETAILS SHOWN ON DRAWINGS ARE TYPICAL FOR ALL SIMILAR CONDITIONS.

DETAILS ARE INTENDED TO SHOW METHOD AND MANNER OF ACCOMPLISHING WORK. MINOR

MODIFICATIONS MAY BE REQUIRED TO SUIT THE JOB DIMENSIONS OR CONDITIONS AND ARE TO BE REVIEWED AND APPROVED BY THE CTIY OF WILDOMAR.

VERIFY ALL DIMENSIONS IN THE FIELD AND COORDINATE DIMENSIONS SHOWN ON THE CONTRACT DRAWINGS WITH FABRICATION AND FIELD CONDITIONS. STAKE OUT STRUCTURE FOR OWNER ’S APPROVAL PRIOR TO STARTING ANY WORK.

CONTRACTOR SHALL PROTECT ALL MONUMENTS, IRON PINS, AND PROPERTY CORNERS DURING CONSTRUCTION.

CONTRACTOR SHALL PREPARE ALL WALLS AND PARTITIONS AS REQUIRED BY THE FINISH MANUFACTURER TO RECEIVE THE FINISHES SPECIFIED.

CONTRACTOR SHALL CLEAN, PATCH AND REPAIR ALL SURFACES DAMAGED BY DEMOLITION, ALTERATION OR INSTALLATION OF THE WORK.

CONTRACTOR AND SUBCONTRACTOR SHALL ALL BE LICENSED TO PERFORM THEIR REQUESTED DUTIES AS REQUIRED IN ACCORDANCE WITH LOCAL STANDARDS.

PRINCIPAL OPENINGS IN THE STRUCTURE ARE SHOWN ON THESE DRAWINGS. THE GENERAL

CONTRACTOR SHALL EXAMINE THE ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR REQUIRED OPENINGS. GENERAL CONTRACTOR SHALL VERIFY SIZE AND LOCATION OF ALL OPENINGS WITH ALL SUB-CONTRACTORS PRIOR TO CONSTRUCTION.

APPLICANT IS RESPONSIBLE FOR PROVIDING SITE PLAN TO THE CITY FOR REVIEW AND APPROVAL.

PHOTOVOLTAIC SYSTEM (PV) SHALL BE SUBMITTED UNDER A SEPARATE PERMIT APPLICATION.

AN ENCROACHMENT PERMIT WILL BE REQUIRED FOR ANY CONSTRUCTION ACTIVITY WITHIN A PUBLIC STREET RIGHT-OF-WAY.

PROVIDE CONSTRUCTION WASTE MANAGEMENT PLAN PER 2022 CALIFORNIA GREEN BUILDING STANDARDS CODE.

GENERAL NOTES

1. 2.

3. 4.

5. 6.

7. 1.

2. 3.

4. 5.

8. 9.

10. 11.

1. 2.

12. 13.

14. 15.

DIFFUSERS AND GRILLS TO MATCH COLOR OF SURFACE AT WHICH THEY ARE MOUNTED, UNLESS OTHERWISE NOTED.

PLUMBING, ELECTRICAL, AND SPRINKLER EQUIPMENT, IF REQUIRED, TO BE PAINTED TO MATCH COLOR OF ADJACENT SURFACE.

FLOOR FINISH TO CONTINUE UNDER MILLWORK WHERE FLOOR IS VISIBLE.

SILICONE SEALANT AT GLAZING TO BE CLEAR, UNLESS OTHERWISE NOTED.

TRANSITION OF FLOOR MATERIALS OCCURRING IN OPENINGS WITH DOORS TO BE LOCATED UNDER THE CENTER OF THE DOOR IN THE CLOSED POSITION. TRANSITION OF FLOOR MATERIAL OCCURRING WITH NO DOOR TO BE LOCATED TO ALIGN WITH THE FACE OF THE PARTITION, U.O.N ALL WALL AND CEILING FINISHES SHALL COMPLY WITH CRC 803.13 FOR MAXIMUM FLAME SPREAD AND SMOKE DENSITY. ALL FINISHES MUST COMPLY WITH ALL APPLICABLE FIRE, LIFE SAFETY, AND BUILDING CODES.

PROVIDE REINFORCEMENT FOR GRAB BARS IN AT LEAST ONE BATHROOM [CRC SECTION R327.1.1, AGING-IN-PLACE DESIGN AND FALL PREVENTION]

REINFORCEMENT SHALL BE SOLID LUMBER OR OTHER CONSTRUCTION MATERIALS APPROVED BY THE ENFORCING AGENCY.

REINFORCEMENT SHALL NOT BE LESS THAN 2 BY 8 INCH NOMINAL LUMBER OR OTHER MATERIAL PROVIDING EQUAL HEIGHT AND LOAD CAPACITY. REINFORCEMENT SHALL BE LOCATED BETWEEN 32 INCHES AND 39 ¼” INCHES ABOVE THE FINISHED FLOOR FLUSH WITH THE WALL FRAMING.

WATER CLOSET REINFORCEMENT SHALL BE INSTALLED ON BOTH SIDE WALLS OF THE FIXTURE, OR ONE SIDE WALL AND THE BACK WALL.

SHOWER REINFORCEMENT SHALL BE CONTINUOUS WHERE WALL FRAMING IS PROVIDED.

BATHTUB AND COMBINATION BATHTUB/SHOWER REINFORCEMENT SHALL BE CONTINUOUS ON EACH END OF THE BATHTUB AND THE BACK WALL. ADDITIONALLY, BACK WALL REINFORCEMENT

FOR A LOWER GRAB BAR SHALL BE PROVIDED WITH THE BOTTOM EDGE LOCATED NO MORE THAN 6 INCHES ABOVE THE BATHTUB RIM.

PROVIDE ADEQUATE BLOCKING IN WALLS FOR CABINETS AND OTHER WALL MOUNTED ACCESSORIES INCLUDING BUT NOT LIMITED TO SHELVING AND BATHROOM FIXTURES.

PROVIDE REQUIRED CLEARANCES FOR BATHROOM FIXTURES, INCLUDING WATER CLOSETS AND SHOWER COMPARTMENTS AS ILLUSTRATED ON SHEET A5.1 [CPC 402.5 AND CPC 408]

SEE DETAILS FOR LOCATIONS OF MISCELLANEOUS IRON AND STEEL WORK, INCLUDING BUT NOT LIMITED TO ASSORTED CLIPS, BRACKETS, ANGLES, STRAPS, AND POST ANCHORS. FURNISH AND

INSTALL ALL SUCH ITEMS NECESSARY TO PROVIDE A COMPLETE INSTALLATION, WHETHER OR NOT SPECIFICALLY DETAILED OR NOTED ON THE DRAWINGS. ALL EXTERIOR METAL AND HARDWARE IS TO BE GALVANIZED. STEEL IS TO COMPLY WITH ASTM A3.

ATTIC ACCESS [CRC R807.1]

BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF CONSTRUCTION SHALL HAVE AN ATTIC ACCESS OPENINGS TO ATTIC AREAS THAT HAVE A VERTICAL HEIGHT OF 30 INCHES OR GREATER OVER AN AREA OF NOT LESS THAN 30 SF. THE VERTICAL HEIGHT SHALL BE

MEASURED FROM THE TOP OF THE CEILING FRAMING MEMBERS TO THE UNDERSIDE OF THE

ROOF FRAMING MEMBERS
THE ROUGH-FRAMED OPENING SHALL BE NOT LESS THAN 22 IN BY 30 IN AND SHALL BE LOCATED IN A HALLWAY OR OTHER LOCATION WITH READY ACCESS. WHERE THE ACCESS IS LOCATED IN A CEILING, MINIMUM UNOBSTRUCTED HEADROOM IN THE ATTIC SPACE SHALL BE 30

IN AT SOME POINT ABOVE THE ACCESS MEASURED VERTICALLY FROM THE BOTTOM OF CEILING FRAMING MEMBERS.

WOOD SOFFIT/CEILING, SIDING & TRIM
ALL NAILS, FASTENERS AND HARDWARE MUST BE STAINLESS STEEL OR HOT-DIPPED GALVANIZED.

STAPLES ARE NOT PERMITTED.

PROVIDE A WATER-RESISTIVE BARRIER APPLIED OVER STUD OR SHEATHING OF ALL EXTERIOR

WALLS WITH FLASHING, IN SUCH A MANNER AS TO PROVIDE A CONTINUOUS BARRIER BEHIND THE EXTERIOR WALL VENEER [CRC SECTION R703.2]

APPROVED CORROSION-RESISTANT FLASHING SHALL BE APPLIED SHINGLE-FASHION IN A MANNER

TO PREVENT ENTRY OF WATER INTO THE WALL CAVITY OR PENETRATION OF WATER TO THE BUILDING STRUCTURAL FRAMING COMPONENT AND COMPLY WITH CRC SECTION 703.4.

FLASHING AND SHEET METAL

ALL FLASHING AND COUNTER FLASHING SHALL BE GALVANIZED AND INSTALLED PER SMACNA STANDARDS. ALL PROPOSED FLASHING AND SHEET METAL MATERIALS, GAUGE, AND INSTALLATION IS TO BE IN ACCORDANCE WITH SMACNA MANUAL STANDARDS.

1. 2.

3. A.

B.
a.
b.

C.
a.
b.

D.
a.
b.

1. 2.

INSTALL CLASS A ROOF ASSEMBLY PER SPECIFICATION BELOW. (CLASS A ROOF ASSEMBLY SHALL BE INSTALLED. IF THE APPLICANT DEVIATES FROM THE ROOF SPECIFICATIONS THE APPLICANT

SHALL PROVIDE A COPY OF THE ICC/UL LISTING)
ROOF COVERING SHALL COMPLY WITH CRC R902 AND CRC R905.

ROOF MATERIAL SPECIFICATIONS
ALL ROOFING MATERIALS TO BE INSTALLED PER MANUFACTURER ’S SPECIFICATIONS ASPHALT SHINGLE ROOF - CERTAINTEED (ICC-ES ER ESR-3537) 2”/12” SLOPE (17%) MINIMUM
FOR ROOF SLOPES 2 ”/12” (17%) UP TO 4”/12” (33%), DOUBLE UNDERLAMENT APPLICATION IS REQUIRED [CRC R905.1.1]
STANDING SEAM METAL ROOF - METAL SALES MAGNA-LOC (ICC ES REPORT ESR-2385) ¼”/12” SLOPE (2%) MINIMUM
24 GA
CONCRETE TILE ROOF - EAGLE ROOF PRODUCTS (IAMP UES-ER 1900) 2 ½”/12” SLOPE (25%) MINIMUM
FOR ROOF SLOPES 2 ½”/12” (2%) UP TO 4”/12” (33%), INSTALL DOUBLE UNDERLAYMENT APPLICATION [CRC R905.3.3]

4. ROOF GUTTERS AND DOWNSPOUTS SHALL BE INSTALLED AND DESIGNED IN ACCORDANCE WITH SMACNA MANUAL. SIZE AS REQUIRED TO HANDLE THE AMOUNT OF ROOF WATER FOR MAXIMUM STORMS.

5. PROVIDE PLAIN RECTANGULAR ROOF GUTTER.

6. GUTTERS SHALL BE PROVIDED WITH THE MEANS TO PREVENT THE ACCUMULATION OF LEAVES AND DEBRIS IN THE GUTTER IN HIGH FIRE SEVERITY ZONES.

7. ROOF VENTS

ROOF VENTS SHALL BE INSTALLED PER MANUFACTURERS SPECIFICATIONS OPENINGS FOR VENTILATION HAVING A LEAST DIMENSION LARGER THAN 1/4 INCH SHALL BE

PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH SCREENING, HARDWARE CLOTH,

PERFORATED VINYL OR SIMILAR MATERIAL WITH OPENINGS HAVING A LEAST DIMENSION OF NOT LESS THAN 1/16 INCH AND NOT MORE THAN 1/4 INCH.

GENERAL ARCHITECTURAL NOTES

GENERAL ARCHITECTURAL ROOF NOTES

ABBREVIATIONS

1. 2.

3. 4.

8. FLASHINGS SHALL BE INSTALLED IN A MANNER THAT PREVENTS MOISTURE FROM ENTERING THE

WALL AND ROOF THROUGH JOINTS IN COPINGS, THROUGH MOISTURE PERMEABLE MATERIALS AND

AT INTERSECTIONS WITH WALLS AND OTHER PENETRATIONS THROUGH THE ROOF PLANE PER CRC SECTION 903.2.

9. NOT LESS THAN 1-INCH SPACE SHALL BE PROVIDED BETWEEN THE INSULATION AND THE ROOF SHEATHING AND AT THE LOCATION OF VENTS [CRC SECTION R806.3].

10. INSTALL INSULATION PER CRC SECTION R806.5:
(REFER TO DETAILS A, B, AND C ON SHEET A5.2)

WHERE ONLY AIR-IMPERMEABLE INSULATION IS PROVIDED, IT SHALL BE APPLIED IN DIRECT CONTACT WITH UNDERSIDE OF THE STRUCTURAL ROOF SHEATHING.

WHERE AIR-PERMEABLE INSULATION IS INSTALLED DIRECTLY BELOW THE STRUCTURAL

SHEATHING, RIGID BOARD OR SHEET INSULATION SHALL BE INSTALLED DIRECTLY ABOVE THE

STRUCTURAL ROOF SHEATHING IN ACCORDANCE WITH R-VALUES BASED ON CLIMATE ZONE PER TABLE R806.5 FOR CONDENSATION CONTROL.

WHERE BOTH AIR-IMPERMEABLE INSULATION AND AIR-PERMEABLE INSULATION ARE PROVIDED,

THE AIR-IMPERMEABLE INSULATION SHALL BE APPLIED IN DIRECT CONTACT WITH THE

UNDERSIDE OF THE STRUCTURAL ROOF SHEATHING IN ACCORDANCE WITH R-VALUES BASED ON CLIMATE ZONE PER TABLE R806.5 FOR CONDENSATION CONTROL. THE AIR-PERMEABLE

INSULATION SHALL BE INSTALLED DIRECTLY UNDER THE AIR-IMPERMEABLE INSULATION

ALTERNATIVELY, SUFFICIENT RIGID BOARD OR SHEET INSULATION SHALL BE INSTALLED

DIRECTLY ABOVE THE STRUCTURAL ROOF SHEATHING TO MAINTAIN THE MONTHLY AVERAGE TEMPATURE OF THE UNDERSIDE OF THE STRUCTURAL ROOF SHEATHIGN ABOVE 45 DEG F. FOR CLACULATION PURPOSES, AN INTERIOR AIR TEMPATURE OF 68 DEG IS ASSUMED AND THE

EXTERIOR AIR TEMPERATURE IS ASSUMED TO BE THE MONTHLY AVERAGE OUTSIDE AIR TEMEPRATURE OF THE THREE COLDEST MONTHS.

GENERAL ARCHITECTURAL ROOF NOTES CONTINUED

GENERAL FIRE NOTES

1. 2.

3. 4.

WHERE RECESSED FIXTURES OCCUR IN WALLS OR HORIZONTAL ASSEMBLIES, THE FIRE RATING OF

THOSE ASSESMBLIES SHALL BE MAINTAINED

AT ALL PENETRATIONS AND INTERSECTIONS OF FIRE RATED PARTITIONS, PROVIDE FIRE SEALANT AND/OR FIRE STOPPING TO MAINTAIN CONTINUITY OF PARTITION RATING.

SEE SHEET A-6.1 FOR FIRE RATED GLAZING REQUIREMENTS.

THE ADU SHALL COMPLY WITH CHAPTER 7A MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR WILDFIRE EXPOSURE OF THE 2022 CALIFORNIA BUILDING CODE IF IT IS IN THE VERY HIGH FIRE HAZARD SEVERITY ZONE (VHFHSZ).

1. 2.

3. 4.

1. 2.

3. 5.

1. 2.

3. 6.

1. 2.

3. 7.

8. 1.

2. 3.

4. 5.

6. 7.

1. 2.

3. 4.

5. 6.

REQUIREMENTS OF CHAPTER 7A OF THE 2022 CALIFORNIA BUILDING CODE INCLUDE:
705A.2 ROOF COVERINGS. WHERE THE ROOF PROFILE HAS AN AIRSPACE UNDER THE ROOF COVERING, INSTALLED OVER A COMBUSTIBLE DECK, A 72 LB. (32.7 KG) CAP SHEET COMPLYING WITH ASTM D3909 STANDARD SPECIFICATION FOR "ASPHALT ROLLED ROOFING (GLASS FELT) SURFACED WITH MINERAL GRANULES," SHALL BE INSTALLED OVER THE ROOF DECK. BIRD STOPS SHALL BE USED AT THE EAVES WHEN THE PROFILE FITS. TO PREVENT DEBRIS AT THE EAVE. HIP AND RIDGE CAPS SHALL BE MUDDED IN TO PREVENT INTRUSION OF FIRE OR EMBERS. EXCEPTION:

CAP SHEET IS NOT REQUIRED WHEN NO LESS THAN 1" OF MINERAL WOOL BOARD OR OTHER

NONCOMBUSTIBLE MATERIAL IS LOCATED BETWEEN THE ROOFING MATERIAL AND WOOD FRAMING OR DECK. ALTERNATELY, A CLASS A FIRE RATED ROOF UNDERLAYMENT, TESTED IN ACCORDANCE WITH ASTM E108, SHALL BE PERMITTED TO BE USED. IF THE SHEATHING CONSISTS

OF EXTERIOR FIRE-RETARDANT TREATED WOOD, THE UNDERLAYMENT SHALL NOT BE REQUIRED TO COMPLY WITH A CLASS A CLASSIFICATION. BIRD STOPS SHALL BE USED AT THE EAVES WHEN THE PROFILE FITS, TO PREVENT DEBRIS AT THE EAVE. HIP AND RIDGE CAPS SHALL BE MUDDED IN TO PREVENT INTRUSION OF FIRE OR EMBERS.
705.A.3 ROOF VALLEYS. WHERE VALLEY FLASHING IS INSTALLED, THE FLASHING SHALL BE NOT LESS THAN 0.019-INCH NO. 26 GAGE GALVANIZED SHEET CORROSION-RESISTANT METAL INSTALLED OVER NOT LESS THAN ONE LAYER OF MIN. 72 POUND MINERAL-SURFACED NON PERFORATED CAP SHEET COMPLYING WITH ASTM D 3909. AT LEAST 36-INCH -WIDE RUNNING THE FULL LENGTH OF THE VALLEY.
705A.4 ROOF GUTTERS SHALL BE PROVIDED WITH THE MEANS TO PREVENT THE ACCUMULATION OF LEAVES AND DEBRIS IN THE GUTTER.
706A.2 VENTILATION OPENINGS SHALL BE FULLY COVERED WITH WILDFIRE FLAME AND EMBER

RESISTANT VENTS APPROVED AND LISTED BY THE CALIFORNIA STATE FIRE MARSHAL, OR WUI VENTS TESTED TO ASTM E2886 AND LISTED, BY COMPLYING WITH ALL OF THE FOLLOWING REQUIREMENTS:

THERE SHALL BE NO FLAMING IGNITION OF THE COTTON MATERIAL DURING THE EMBER

INTRUSION TEST

THERE SHALL BE NO FLAMING IGNITION DURING THE INTEGRITY TEST PORTION OF THE FLAME

INTRUSION TEST

THE MAXIMUM TEMPERATURE OF THE UNEXPOSED SIDE OF THE VENT SHALL NOT EXCEED 662 F
706A.2.1 VENTS THAT ARE INSTALLED ON A SLOPED ROOF, SUCH AS DORMER VENTS, SHALL COMPLY WITH ALL THE FOLLOWING:

VENTS SHALL BE COVERED WITH A MESH WHERE THE DIMENSIONS OF THE MESH THEREIN SHALL BE A MINIMUM OF 1/16 - INCH AND SHALL NOT EXCEED 1/8 - INCH IN DIAMETER

THE MESH MATERIAL SHALL BE NONCOMBUSTIBLE
THE MESH MATERIAL SHALL BE CORROSION RESISTANT.
707A.3 EXTERIOR WALLS COVERINGS. THE EXTERIOR WALL COVERING SHALL COMPLY WITH ONE

OR MORE OF THE FOLLOWING REQUIREMENTS, EXCEPT AS PERMITTED FOR EXTERIOR WALL ASSEMBLIES COMPLYING WITH SECTION 707A.4:

NONCOMBUSTIBLE MATERIAL
IGNITION- RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 704A.2.

FIRE-RETARDANT-TREATED WOOD. THE FIRE-RETARDANT-TREATED WOOD SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2. 707A.3.1 EXTENT OF EXTERIOR WALL COVERING. EXTERIOR WALL COVERINGS SHALL EXTEND FROM THE TOP OF THE FOUNDATION TO THE ROOF AND TERMINATE AT 2" NOMINAL SOLID WOOD

BLOCKING BETWEEN RAFTERS AT ALL ROOF OVERHANGS, OR IN THE CASE OF ENCLOSED EAVES, TERMINATE AT THE ENCLOSURE.
707A.4 EXTERIOR WALL ASSEMBLIES. EXTERIOR WALL ASSEMBLIES OF BUILDINGS OR

STRUCTURES SHALL BE CONSTRUCTED USING ONE OR MORE OF THE FOLLOWING METHODS, UNLESS THEY ARE COVERED BY AN EXTERIOR WALL COVERING COMPLYING WITH SECTION 707A.3:

ASSEMBLY OF SAWN LUMBER OR GLUE LAMINATED WOOD WITH THE SMALLEST MINIMUM NOMINAL DIMENSION OF 4 INCHES. SAWN OR GLUE-LAMINATED PLANKS SPLINED, TONGUEAND-GROVE , OR SET CLOSE TOGETHER AND WELL SPIKED.

LOG WALL CONSTRUCTION ASSEMBLY
ASSEMBLY THAT HAS BEEN TESTED IN ACCORDANCE WITH THE TEST PROCEDURES FOR A 10 MINUTE DIRECT FLAME CONTACT EXPOSURE SET FORTH IN ASTM E2707 WITH THE CONDITIONS OF ACCEPTANCE SHOWN IN SECTION 707A.4.1.

ASSEMBLY THAT MEET THE PERFORMANCE CRITERIA IN ACCORDANCE WITH THE TEST

PROCEDURES FOR A TEN MINUTE DIRECT FLAME CONTACT EXPOSURE TEST SET FORTH IN SFM STANDARD 12-7A-1
ASSEMBLY SUITABLE FOR EXTERIOR FIRE EXPOSURE WITHA 1-HOUR FIRE RESISTANCE RATING, RATED FROM THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL263
ASSEMBLY SUITABLE FOR EXTERIOR FIRE EXPOSURE CONTAINING ONE LAYER OF 5/8 -INCH

TYPE X GYPSUM SHEATHING APPLIED BEHIND THE EXTERIOR WALL COVERING OR CLADDING ON THE EXTERIOR SIDE OF THE FRAMING.

ASSEMBLY SUITABLE FOR EXTERIOR EXPOSURE CONTAINING ANY OF THE GYPSUM PANEL

AND SHEATHING PRODUCTS LISTED IN THE GYPSUM ASSOCIATION FIRE RESISTANCE DESIGN MANUEL AS COMPLYING WITH A1-HOUR FIRE-RESISTANCE RATING, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263

9. 707A.5 OPEN ROOF EAVES. THE EXPOSED ROOF DECK ON THE UNDERSIDE OF ENCLOSED ROOF EAVES SHALL CONSIST OF ONE OR MORE OF THE FOLLOWING:

NON COMBUSTIBLE MATERIAL
IGNITION- RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR EXTERIOR USE AN SHALL MEET THE REQUIREMENTS OF SECTION 704A.2 FIRE-RETARDANT-TREATED WOOD. THE FIRE-RETARDANT-TREATED WOOD SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2 MATERIALS APPROVED FOR NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION ON THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263
ONE LAYER OF 5/8" TYPE X GYPSUM SHEATHING APPLIES BEHIND AN EXTERIOR COVERING ON THE UNDERSIDE EXTERIOR OF THE ROOFDECK.

THE EXTERIOR PORTION A 1- HOUR FIRE RESISTIVE EXTERIOR ASSEMBLY, APPLIES AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263, APPLIED TO THE UNDERSIDE OF THE

ROOF DECK DESIGNED FOR THE EXTERIOR FIRE EXPOSURE, INCLUDING ASSEMBLES USING

THE GYPSUM PANEL AND SHEATHING PRODUCTS LISTED IN THE GYPSUM ASSOCIATION FIRE RESISTANCE DEIGN MANUAL. EXCEPTION TO SECTION 707A.5: THE FOLLOWING MATERIALS DO NOT REQUIRE PROTECTION: FASCIA AND OTHER ARCHITECTURAL TRIM BOARDS

1. 2.

3. 4.

5. 6.

7. 8.

1. 2.

3. 4.

5. 6.

7. 8.

1. 2.

3. 4.

5. 6.

7. 8.

1. 2.

3. 4.

5. 6.

7. 8.

1. 2.

3. 4.

5. 6.

7. 8.

10. 707A.6 ENCLOSED ROOF EAVES AND ROOF EAVE SOFFITS. THE EXPOSED UNDERSIDE OF ENCLOSED

ROOF EAVES HAVING EITHER A BOXED-IN ROOF EAVE SOFFIT WITH A HORIZONTAL UNDERSIDE,OR

SLOPING RAFTER TAILS WITH AN EXTERIOR COVERING APPLIED TO THE UNDERSIDE OF THE RAFTER TAILS, SHALL BE PROTECTED BY ONE OR MORE OF THE FOLLOWING:

NONCOMBUSTIBLE MATERIAL
IGNITION- RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 704A.2 FIRE-RETARDANT-TREATED-WOOD. THE FIRE-RETARDANT TREATED WOOD SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2 MATERIALS APPROVED FOR NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION ON THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263 ONE LAYER OF 5/8" TYPE X GYPSUM SHEATHING APPLIED BEHIND AN EXTERIOR COVERING ON THE UNDERSIDE OF FLOOR PROJECTION.

THE EXTERIOR PORTION A 1- HOUR FIRE RESISTIVE EXTERIOR ASSEMBLY, APPLIED TO THE

UNDERSIDE OF THE RAFTER TAIS OR SOFFIT, INCLUDING ASSEMBLES USING THE GYPSUM

PANEL AND SHEATHING PRODUCTS LISTED IN THE GYPSUM ASSOCIATION FIRE RESISTANCE

DESIGN MANUAL

BOXED-IN ROOF EAVE SOFFIT ASSEMBLIES WITH A HORIZONTAL UNDERSIDE THAT MEET THE PERFORMANCE CRITERIA IN SECTION 707A.11 WHEN TESTED IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN ASTM E2957

BOXED-IN ROOF EAVE SOFFIT ASSEMBLIES WITH A HORIZONTAL UNDERSIDE THAT MEET THE PERFORMANCE CRITERIA IN SECTION 707A.11 WHEN TESTED IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN SFM STANDARD 12-7A-3 EXCEPTION TO SECTION 707A.6: THE FOLLOWING MATERIALS DO NOT REQUIRE PROTECTION: FASCIA AND OTHER ARCHITECTURAL TRIM BOARDS.

11. 707A.7 EXTERIOR PORCH CEILINGS. THE EXPOSED UNDERSIDE OF THE EXTERIOR PORCH CEILINGS SHALL BE PROTECTED BY ONE OF THE FOLLOWING:

NON COMBUSTIBLE MATERIAL
IGNITION- RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 704A.2 FIRE-RETARDANT-TREATED-WOOD. THE FIRE-RETARDANT TREATED WOOD SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2 MATERIALS APPROVED FOR NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION ON THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263 ONE LAYER OF 5/8" TYPE X GYPSUM SHEATHING APPLIED BEHIND THE EXTERIOR COVERING OR CLADDING ON THE UNDERSIDE OF THE RAFTER TAILS OR SOFFIT.

THE EXTERIOR PORTION A 1- HOUR FIRE RESISTIVE EXTERIOR ASSEMBLY, AS TESTED IN ACCORDANCE WITH ASTM E119, APPLIED TO THE UNDERSIDE OF THE CEILING ASSEMBLY,

INCLUDING ASSEMBLES USING THE GYPSUM PANEL AND SHEATHING PRODUCTS LISTED IN THE GYPSUM ASSOCIATION FIRE RESISTANCE DESIGN MANUAL.

PORCH CEILING ASSEMBLIES WITH A HORIZONTAL UNDERSIDE THAT MEET THE PERFORMANCE CRITERIA IN SECTION 707A.11 WHEN TESTED IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN ASTM E2957

PORCH CEILING ASSEMBLIES WITH A HORIZONTAL UNDERSIDE THAT MEET THE PERFORMANCE CRITERIA IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN SFM STANDARD 12-7A-3 EXCEPTION TO SECTION 707A.7: ARCHITECTURAL TRIM BOARDS DO NOT REQUIRE PROTECTION

12. 707A.8 FLOOR PROJECTIONS. THE EXPOSED UNDERSIDE OF A CANTILEVER FLOOR PROJECTION

WHERE A FLOOR ASSEMBLY EXTENDS OVER AN EXTERIOR WALL SHALL BE PROTECTED BY ON OF THE FOLLOWING:

NONCOMBUSTIBLE MATERIAL
IGNITION- RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 704A.2 FIRE-RETARDANT-TREATED-WOOD. THE FIRE-RETARDANT TREATED WOOD SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2 MATERIALS APPROVED FOR NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION ON THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263 ONE LAYER OF 5/8" TYPE X GYPSUM SHEATHING APPLIED BEHIND AND EXTERIOR COVERING ON

THE UNDERSIDE OF THE CEILING
THE EXTERIOR PORTION A 1- HOUR FIRE RESISTIVE EXTERIOR ASSEMBLY, AS TESTED IN ACCORDANCE WITH ASTM E119, APPLIED TO THE UNDERSIDE OF THE CEILING ASSEMBLY,

INCLUDING ASSEMBLES USING THE GYPSUM PANEL AND SHEATHING PRODUCTS LISTED IN THE GYPSUM ASSOCIATION FIRE RESISTANCE DESIGN MANUAL.

THE UNDERSIDE OF A FLOOR PROJECTIONS ASSEMBLY THAT MEETS THE PERFORMANCE CRITERIA IN SECTION 707A.10 WHEN TESTED IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN ASTM E2957.

THE UNDERSIDE OF A FLOOR PROJECTIONS ASSEMBLY THAT MEETS THE PERFORMANCE CRITERIA IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN THE SFM STD 12-7A-3.

EXCEPTION TO SECTION 707A.8: ARCHITECTURAL TRIM BOARDS DO NOT REQUIRE PROTECTION

13. 707A.9 UNDERFLOOR PROTECTION. THE UNDERFLOOR AREA OF ELEVATED OR OVERHANGING

BUILDINGS SHALL BE ENCLOSED TO GRADE IN ACCORDANCE WITH THE REQUIREMENTS OF

THIS CHAPTER OR THE UNDERSIDE OF THE EXPOSED UNDERFLOOR SHALL BE PROTECTED BY ONE OR MORE OF THE FOLLOWING:

NONCOMBUSTIBLE MATERIAL
IGNITION- RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 704A.2 FIRE-RETARDANT-TREATED-WOOD. THE FIRE-RETARDANT TREATED WOOD SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2 MATERIALS APPROVED FOR NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION ON THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263 ONE LAYER OF 5/8" TYPE X GYPSUM SHEATHING APPLIED BEHIND AND EXTERIOR COVERING ON

THE UNDERSIDE OF THE FLOOR PROJECTION
THE EXTERIOR PORTION A 1- HOUR FIRE RESISTIVE EXTERIOR ASSEMBLY, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263, APPLIED TO THE UNDERSIDE OF THE FLOOR,

INCLUDING ASSEMBLES USING THE GYPSUM PANEL AND SHEATHING PRODUCTS LISTED IN THE GYPSUM ASSOCIATION FIRE RESISTANCE DESIGN MANUAL.

THE UNDERSIDE OF A FLOOR ASSEMBLY THAT MEETS THE PERFORMANCE CRITERIA IN SECTION 707A.11 WHEN TESTED IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN ASTM E2957.

THE UNDERSIDE OF A FLOOR ASSEMBLY THAT MEETS THE PERFORMANCE CRITERIA IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN SFM STANDARD 12-7A-3. EXCEPTION TO SECTION 707A.9: STRUCTURAL COLUMNS AND BEAMS DO NOT REQUIRE PROTECTION WHEN

CONSTRUCTED WITH SAWN LUMBER OR GLUE-LAMINATED WOOD WITH THE SMALLEST MINIMUM NOMINAL DIMENSION OF 4 INCHES. SAWN OR GLUE-LAMINATED PLANKS SHALL BE SPLINED, TONGUE-AND-GROOVE, OR SET CLOSE TOGETHER AND WELL SPIKED.

14. 707A.10 UNDERSIDE OF APPENDAGES. WHEN REQUIRED BY THE ENFORCING AGENCY THE

UNDERSIDE OF OVERHANGING APPENDAGES SHALL BE ENCLOSED TO GRADE IN ACCORDANCE

WITH THE REQUIREMENTS OF THIS CHAPTER OR THE UNDERSIDE OF THE EXPOSED UNDER FLOOR SHALL CONSIST OF ONE OF THE FOLLOWING:

NONCOMBUSTIBLE MATERIAL
IGNITION- RESISTANT MATERIAL. THE IGNITION-RESISTANT MATERIAL SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 704A.2 FIRE-RETARDANT-TREATED-WOOD. THE FIRE-RETARDANT TREATED WOOD SHALL BE LABELED FOR EXTERIOR USE AND SHALL MEET THE REQUIREMENTS OF SECTION 2303.2 MATERIALS APPROVED FOR NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION ON THE EXTERIOR SIDE, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263 ONE LAYER OF 5/8" TYPE X GYPSUM SHEATHING APPLIED BEHIND THE EXTERIOR COVERING ON

THE UNDERSIDE OF THE APPENDAGE PROJECTION
THE EXTERIOR PORTION A 1- HOUR FIRE RESISTIVE EXTERIOR ASSEMBLY, AS TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263, APPLIED TO THE UNDERSIDE OF THE APPENDAGE,

INCLUDING ASSEMBLES USING THE GYPSUM PANEL AND SHEATHING PRODUCTS LISTED IN THE GYPSUM ASSOCIATION FIRE RESISTANCE DESIGN MANUAL.

THE UNDERSIDE OF AN APPENDAGE ASSEMBLY THAT MEETS THE PERFORMANCE CRITERIA IN SECTION 707A.11 WHEN TESTED IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN ASTM E2957.

THE UNDERSIDE OF AN APPENDAGE ASSEMBLY THAT MEETS THE PERFORMANCE CRITERIA IN ACCORDANCE WITH THE TEST PROCEDURES SET FORTH IN SFM STANDARD 12-7A-3.EXCEPTION TO SECTION 707A.10: STRUCTURAL COLUMNS AND BEAMS DO NOT REQUIRE PROTECTION WHEN

CONSTRUCTED WITH SAWN LUMBER OR GLUE-LAMINATED WOOD WITH THE SMALLEST MINIMUM NOMINAL DIMENSION OF 4 INCHES. SAWN OR GLUE-LAMINATED PLANKS SHALL BE SPLINED, TONGUE-AND-GROOVE, OR SET CLOSE TOGETHERAND WELL SPIKED.

GENERAL FIRE NOTES CONTINUED

ARCHITECTURAL SYMBOLS

CALLOUT PLAN,

SECTION OR DETAIL
#

BUILDING SECTION

ELEVATIONS

VIEW TITLE
# SCALE:

VIEW CALLOUT
COLUMN GRID #
#

DOOR TAG - SEE

SCHEDULE
##.## KEYNOTE

DENOTES ABOVE,

BELOW, OR BEHIND
# WINDOW TYPE

LEVEL LINE

CENTER LINE
#
#
#

GLAZING
#
#
Sheet #
D
C
B
A
1 2 3 4 5
1 2 3 4 5
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

GENERAL NOTES, ABBREVIATIONS, AND SYMBOLS
A-1.0
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026

ABB DESCRIPTION
__________ A __________
& AND
< ANGLE
@ AT

ADJ ADJACENT, ADJUSTABLE

AFF ABOVE FINISHED FLOOR

AP ACCESS PANEL

APPROX APPROXIMATE(LY)

ARCH ARCHITECT OR ARCHITECTURAL

ASTM AMERICAN SOCIETY FOR TESTING MATERIAL

AVG AVERAGE
__________ B __________

BC BASE CABINET

BD BOARD

BLDG BUILDING

BO BOTTOM OF
__________ C __________

C/ CENTER OF

CAB CABINET

CL CENTER LINE

CLG CEILING

CLG HT CEILING HEIGHT

CLO CLOSET

CLR CLEAR

CMU CONCRETE MASONRY UNIT

COL COLUMN

CONC CONCRETE

CONT CONTINUOUS
__________ D __________

DIA DIAMETER

DIM DIMENSION

DN DOWN

DW DISHWASHER

DWG DRAWING
__________ E __________
E EAST

EA EACH

ELEC ELECTRICAL

EMER EMERGENCY

ENCL ENCLOSE(URE)

EP ELECTRICAL PANEL

EQ EQUAL

EQUIP EQUIPMENT

EXIST EXISTING

EXT EXTERIOR
__________ F __________

F/F FACE TO FACE

FL FLOOR

FP FIRE PROTECTION

FPRF FIREPROOF(ING)

FR FIRE RATED OR FRAME

FT FOOT/FEET
__________ G __________

GA GAUGE

GL GLASS OR GLAZING

GRD GROUND

GWB GYPSUM WALL BOARD
__________ H __________

HB HOSE BIBB

HDW HARDWARE

HM HOLLOW METAL

HOR HORIZONTAL

HP HIGH POINT

HTR HEATER
__________ I __________

ID INSIDE DIAMETER

IN INCH(ES)

INT INTERIOR
__________ J __________

JB JAMB

JST JOIST

JT JOINT
__________ L __________

LAM LAMINATE

LAN LOCAL AREA NETWORK CONNECTION

LAV LAVATORY

LB POUND

LF LINEAL FOOT

LP LOW POINT

LTL LINTEL
__________ M __________

MAX MAXIMUM

MDF MEDIUM DENSITY FIBERBOARD

MECH MECHANICAL

ABB DESCRIPTION

MFR MANUFACTURE

MIN MINIMUM

MISC MISCELLANEOUS

MO MASONRY OPENING

MTD MOUNTED

MTL METAL
__________ N __________

N NORTH

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NOM NOMINAL

NTS NOT TO SCALE
__________ O __________

OC ON CENTER

OD OUTSIDE DIAMETER

OPNG OPENING

OPP OPPOSITE
__________ P __________

PART PARTITION

PL PLATE

PLAM PLASTIC LAMINATE

PLAS PLASTER

PLYWD PLYWOOD

PNL PANEL

PREFAB PREFABRICATED

PROP PROPERTY

PSI POUNDS PER SQUARE INCH

PTD PAINTED
__________ Q __________

QTY QUANTITY
__________ R __________

R RISER OR RADIUS

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

REF REFRIGERATOR

REG REGISTER

REINF REINFORCING

REQ'D REQUIRED

REQMT REQUIREMENTS

RG RANGE

RM ROOM

RO ROUGH OPENING

RTS RUBBER TRANSITION STRIP

RWC RAIN WATER CONDUCTOR
__________ S __________

S SOUTH

SAN SANITARY

SCHD SCHEDULE

SEC SECTION

SF SQUARE FOOT

SIM SIMILAR

SPEC SPECIFY, SPECIFIED OR SPECIFICATIONS

SPKLR SPRINKLER

SQ SQUARE

SQ FT SQUARE FOOT

SS STAINLESS STEEL

STD STANDARD

STL STEEL

STN STAINED

STOR STORAGE

STRUCT STRUCTURAL

SUSP SUSPEND, SUSPENDED, OR SUSPENSION

SYS SYSTEM
__________ T __________
"T" TEE (BAR OR W)

T/ TOP OF

TEMP TEMPERED OR TEMPERATURE

THRESH THRESHOLD

TLT TOILET

TYP TYPICAL
__________ U __________

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

UNO UNLESS NOTED OTHERWISE
__________ V __________

VIF VERIFY IN FIELD
__________ W __________
W WEST

W/ WITH

W/O WITHOUT

WC WATER CLOSET

WP WATERPROOF(ING)

WT WEIGHT

REVISIONS
NO. DATE DESCRIPTION
301
REF.

DW
A-2.1 2
A-2.1 1
A-2.1 4
A-2.1 3
1 A-3.1
2 A-3.1

BEDROOM
LIVING
BATH
CLOSET

KITCHEN
12' - 2" 3' - 0" 1' - 10"
CLO. W/D
PATIO

1.01 A
AA
A
1 A
A
A
3 2
7 6
45 B
21 AC
17' - 0"
13' - 6" 24' - 6"
B
38' - 0"
SLOPE
DOWN

SLOPEDOWN
SLOPE
DOWN
DOWN
SLOPE
1' - 10" 3' - 0" 20' - 5" 3' - 0" 4' - 11" 3' - 0" 1' - 10" 16' - 6" 2' - 8" 6' - 1" 3' - 0" 4' - 11" 3' - 0" 1' - 10"

1.11 1.10

1.12 1.13

1.15 1.08

1.17 LINE ABOVE,
TYP.

1.17 1.17

1.16 1.09

1.04 1.04 1.05

1.03 1.06

1.07 1.07

1.14 1.19
2' - 7" 8' - 7"
13' - 1"
2' - 1" 13' - 8 1/2"
5' - 6 1/2" 2' - 11" 3' - 1" 3' - 8" 8' - 1 1/2" 15' - 1 1/2" 16' - 1"
1' - 10" 3' - 0" 3' - 10" 3' - 4" 5' - 0"
3' - 8"

1.20 3' - 1"

1.22 1.22 1.23
A-5.1
2B
A-5.1
1B
TYP.

A-2.1 2
A-2.1 1
A-2.1 4
A-2.1 3
1 A-3.1
2 A-3.1
SLOPE
4"/12"
SLOPE
4"/12"

1.02 21
ACB

1.18 1.18 3' - 0" 2' - 0"
2' -0"
2' -0"  SETBACK
3' - 0"

1.21A

1. 2.

3. 4.

5. 6.

7. REFER TO GENERAL NOTES SHEET A1.0 FOR ADDITIONAL
REQUIREMENTS.

REFER TO STRUCTURAL DRAWINGS FOR ROOF FRAMING
INFORMATION.

ALL FURNITURE AND EQUIPMENT IS BY OWNER AND IS SHOWN
FOR COORDINATION PURPOSES ONLY.

SEE STRUCTURAL FOR EXTERIOR STUD WALL SIZE.

ONE (MIN.) SIDE-HINGED EGRESS DOOR SHALL BE PROVIDED
WITH A CLEAR WIDTH OF NOT LESS THAN 32” WHERE MEASURED

BETWEEN THE FACE OF THE DOOR AND THE STOP, WITH THE
DOOR OPEN 90°. THE CLEAR HEIGHT OF THE DOOR OPENING
SHALL BE NOT LESS THAN 78” IN HEIGHT MEASURED FROM THE
TOP OF THE THRESHOLD TO THE BOTTOM OF THE STOP.

REFER TO MECHANICAL AND PLUMBING PLAN FOR WATER
EFFICIENCY REQUIREMENTS FOR ALL PLUMBING FIXTURES.

ROOF OVERHANG DIMENSIONS ARE FROM FACE OF EXTERIOR

WALL FRAMING TO EDGE OF ROOF

FLOOR AND ROOF PLAN GENERAL SHEET NOTES

1. 2.

3. SOLAR READY ROOF MINIMUM AREA: 250 SF

THE SOLAR ZONE TOTAL ARE SHALL BE COMPRISED OF AREAS
THAT HAVE NO DIMENSION LESS THAN 5 FT. THE SOLAR ZONE

SHALL BE LOCATED ON THE ROOF OR OVERHANG OF THE
BUILDING. [CEC 2022 SECTION 110.10.(b)]
FOR PHOTOVOLTAIC ARRAYS OCCUPYING NOT MORE THAN 33

PERCENT OF THE PLAN VIEW TOTAL ROOF AREA, NOT LESS
THAN AN 18-INCH CLEAR SETBACK IS REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE. FOR PHOTOVOLTAIC ARRAYS
OCCUPYING MORE THAN 33 PERCENT OF THE PLAN VIEW TOTAL
ROOF AREA, NOT LESS THAN A 36-INCH CLEAR SETBACK IS
REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE. [CRC
R329.6.2]

THE SOLAR ZONE SHALL COMPLY WITH ACCESS, PATHWAY,

SMOKE VENTILATION, AND SPACING REQUIREMENTS AS
SPECIFIED IN TILE 24, PART 9 OR OTHER PARTS OF TITLE 24 OR IN ANY REQUIREMENTS ADOPTED BY LOCAL JURISDICTION.

SOLAR READY GENERAL NOTES

SOLAR ZONE

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMANGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

NET FREE VENTING AREA REQUIRED = (ENCLOSED AREA / 150)
[CRC R806.2]

ENCLOSED ATTIC SPACE
(152 SF / 150) = 1.02 SF MIN. [147 SQ. IN.]
WALLS AND PROJECTIONS LESS THAN 5 FEET FROM THE PROPERTY LINE SHALL COMPLY WITH CRC TABLES R302.1(1) AND (2).

ENCLOSED RAFTER SPACE 1
(229 SF / 150) = 1.53 SF MIN. [221 SQ. IN.]
ENCLOSED RAFTER SPACE 2
(265 SF / 150) = 1.77 SF MIN. [255 SQ. IN.]

ROOF VENTING CALCULATIONS
PROVIDE 3 1/2" X 14" (24 SQ. IN. VENTING AREA), EQUALLY SPACED.

VULCAN FIRE STOPPING SOFFIT VENT OR EQUIVALENT.
7 VENTS
10 VENTS
11 VENTS

ROOF VENTING KEY PLAN

ATTIC SPACE

ENCLOSED
RAFTER SPACE 1

ENCLOSED
RAFTER SPACE 2
N.T.S
LEGEND
INDICATES LOCATION OF REINFORCEMENT FOR AGING-INPLACE DESIGN AND FALL PROVENTION. SEE 9/A-5.1 FOR ADDITIONAL INFORMATION.

Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED
1 BEDROOM - FLOOR PLAN AND ROOF PLAN (CRAFTSMAN)
A-1.1
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026
0 SCALE:
2' - 0" 4' - 0" 8' - 0"
1/4" = 1' - 0"
SCALE: 1/4" = 1'-0"

FLOOR PLAN - CRAFTSMAN
1 SCALE: 1/4" = 1'-0"

ROOF PLAN - CRAFTSMAN
2 AREA: 646 SF

KEYNOTES

1.01 LINE OF ROOF ABOVE

1.02 LINE OF BUILDING

1.03 EMEREGENCY EGRESS WINDOW AT SLEEPING ROOM

1.04 LANDING OR FLOOR REQUIRED AT EACH SIDE OF EXTERIOR

DOOR WITH MINIMUM WIDTH EQUAL TO THE WIDTH OF THE
DOOR SERVED AND MINIMUM DEPTH OF 36”. AND 36” MINIMUM
DEPTH MEASURED IN THE DIRECTION OF TRAVEL. LANDING OR
FINISHED FLOOR SHALL NOT BE MORE THAN 1 ½” LOWER THAN
THE TOP OF THE THRESHOLD. THE LANDING ON THE EXTERIOR
SIDE SHALL BE NOT MORE THAN 7 ¾” BELOW THE TOP OF THE

THRESHOLD PROVIDED THAT THE DOOR DOES NOT SWING
OVER THE LANDING OR FLOOR.

1.05 EXTERIOR LANDING SURFACE SLOPE NOT TO EXCEED ¼”/FOOT

AWAY FROM BUILDING

1.06 DOOR BELL, 48” MAX ABOVE EXTERIOR LANDING.

1.07 DOOR MUST PROVIDE NET CLEAR OPENING OF 32”

1.08 36” HIGH COUNTERTOP

1.09 SHELF AND HANGING ROD AT CLOSET

1.10 WALLS AND FLOORS AT BATHTUB AND SHOWER SPACES SHALL BE FINISHED WITH NON-ABSORBENT SURFACES. SUCH WALL
SURFACES SHALL EXTEND TO 72” MIN.

1.11 PROVIDE TEMPERED GLAZED ENCLOSURE AT OR ADJACENT TO

BATHTUBS AND/OR SHOWERS WHERE THE BOTTOM EXPOSED
EDGE OF GLAZING IS LESS THAN 60” ABOVE ANY STANDING OR
WALKING SURFACE.

1.12 PROVIDE REINFORCEMENT FOR GRAB BARS [CRC R327.1]. SEE

FLOOR PLAN GENERAL NOTES FOR ADDITIONAL INFORMATION
AND REQUIREMENTS.

1.13 PROVIDE FURRING AS NEEDED FOR STANDARD BATHTUB AND SHOWER LENGTH.

1.14 DRYER VENT AT EXTERIOR WALL MIN. 3 FT FROM ANY OPENING

1.15 2X6 STUD WALL

1.16 STACKED WASHER/DRYER MACHINE LOCATION

1.17 CEILING AT 8'-0" A.F.F.

1.18 GUTTER AND DOWNSPOUTS. PROVIDE DOWNSPOUT LOCATIONS AS REQUIRED BY SITE SPECIFIC CONDITIONS.

1.19 WATER HEATER, REFER TO MEP.

1.20 A CONDENSING UNIT SUPPORTED FROM THE GROUND SHALL

REST ON A CONCRETE OR OTHER APPROVED BASE EXTENDING
NOT LESS THAN 3 INCHES ABOVE THE ADJOINING GROUND
LEVEL [CMC 1105.2]

1.21A ASPHALT SHINGLE ROOF

1.22 INDOOR UNIT, REFER TO MEP.

1.23 ELECTRICAL SUBPANEL, REFER TO MEP.

REVISIONS
NO. DATE DESCRIPTION
302
REF.

DW
1 A-3.2
2 A-3.2
A-2.2 2
A-2.2 3
A-2.2 4
A-2.2 1

BEDROOM
BATH
CLOSET

KITCHEN
CLO. W/D
17' - 0"
13' - 6" 24' - 6"
12' - 2" 3' - 0" 1' - 10"

1.01 3
2 7 6
45 A
AA
A
1 A
A
AB
16' - 1"
21 ACB
38' - 0"
SLOPE
DOWN

SLOPEDOWN
1' - 10" 3' - 0" 20' - 5" 3' - 0" 4' - 11" 3' - 0" 1' - 10" 1' - 10" 3' - 0" 3' - 10" 3' - 4" 5' - 0" DOWN SLOPE
SLOPE
DOWN
16' - 6" 2' - 8" 6' - 1" 3' - 0" 4' - 11" 3' - 0" 1' - 10" PATIO

1.11 1.10

1.12 1.13

1.15 1.08

1.17 1.17

1.17 1.16

1.04 1.04

1.05 1.03

1.07 1.07

1.14 1.19

1.06 LIVING

1.09 13' - 1"
2' - 1" 13' - 8 1/2"
5' - 6 1/2" 2' - 11" 3' - 1" 3' - 8" 8' - 1 1/2" 15' - 1 1/2"

LINE ABOVE,
TYP.

1.20 2' - 7" 8' - 7"
3' - 1"

1.22 1.22 1.23
A-5.1
3B
TYP.
1 A-3.2
2 A-3.2
A-2.2 2
A-2.2 3
A-2.2 4
A-2.2 1 SLOPE
4"/12"
SLOPE
4"/12"
SLOPE
4"/12"
21 ACB

SETBACK
8" 3' - 0" 8"
8" 8"

1.18 1.18

1.02 6' - 8"
AWNING
7' - 0" 3' - 4"
AWNING
3' - 10"

1.21B

1. 2.

3. 4.

5. 6.

7. REFER TO GENERAL NOTES SHEET A1.0 FOR ADDITIONAL
REQUIREMENTS.

REFER TO STRUCTURAL DRAWINGS FOR ROOF FRAMING
INFORMATION.

ALL FURNITURE AND EQUIPMENT IS BY OWNER AND IS SHOWN
FOR COORDINATION PURPOSES ONLY.

SEE STRUCTURAL FOR EXTERIOR STUD WALL SIZE.

ONE (MIN.) SIDE-HINGED EGRESS DOOR SHALL BE PROVIDED
WITH A CLEAR WIDTH OF NOT LESS THAN 32” WHERE MEASURED

BETWEEN THE FACE OF THE DOOR AND THE STOP, WITH THE
DOOR OPEN 90°. THE CLEAR HEIGHT OF THE DOOR OPENING
SHALL BE NOT LESS THAN 78” IN HEIGHT MEASURED FROM THE
TOP OF THE THRESHOLD TO THE BOTTOM OF THE STOP.

REFER TO MECHANICAL AND PLUMBING PLAN FOR WATER
EFFICIENCY REQUIREMENTS FOR ALL PLUMBING FIXTURES.

ROOF OVERHANG DIMENSIONS ARE FROM FACE OF EXTERIOR

WALL FRAMING TO EDGE OF ROOF

FLOOR AND ROOF PLAN GENERAL SHEET NOTES

1. 2.

3. SOLAR READY ROOF MINIMUM AREA: 250 SF

THE SOLAR ZONE TOTAL ARE SHALL BE COMPRISED OF AREAS
THAT HAVE NO DIMENSION LESS THAN 5 FT. THE SOLAR ZONE

SHALL BE LOCATED ON THE ROOF OR OVERHANG OF THE
BUILDING. [CEC 2022 SECTION 110.10.(b)]
FOR PHOTOVOLTAIC ARRAYS OCCUPYING NOT MORE THAN 33

PERCENT OF THE PLAN VIEW TOTAL ROOF AREA, NOT LESS
THAN AN 18-INCH CLEAR SETBACK IS REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE. FOR PHOTOVOLTAIC ARRAYS
OCCUPYING MORE THAN 33 PERCENT OF THE PLAN VIEW TOTAL
ROOF AREA, NOT LESS THAN A 36-INCH CLEAR SETBACK IS
REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE. [CRC
R329.6.2]

THE SOLAR ZONE SHALL COMPLY WITH ACCESS, PATHWAY,

SMOKE VENTILATION, AND SPACING REQUIREMENTS AS
SPECIFIED IN TILE 24, PART 9 OR OTHER PARTS OF TITLE 24 OR IN ANY REQUIREMENTS ADOPTED BY LOCAL JURISDICTION.

SOLAR READY GENERAL NOTES

SOLAR ZONE

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMANGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

NET FREE VENTING AREA REQUIRED = (ENCLOSED AREA / 150)
[CRC R806.2]

ENCLOSED ATTIC SPACE
(152 SF / 150) = 1.02 SF MIN. [147 SQ. IN.]
WALLS AND PROJECTIONS LESS THAN 5 FEET FROM THE PROPERTY LINE SHALL COMPLY WITH CRC TABLES R302.1(1) AND (2).

ENCLOSED RAFTER SPACE 1
(229 SF / 150) = 1.53 SF MIN. [221 SQ. IN.]
ENCLOSED RAFTER SPACE 2
(265 SF / 150) = 1.77 SF MIN. [255 SQ. IN.]

ROOF VENTING CALCULATIONS
PROVIDE 3 1/2" X 14" (24 SQ. IN. VENTING AREA), EQUALLY SPACED.

VULCAN FIRE STOPPING SOFFIT VENT OR EQUIVALENT.
7 VENTS
10 VENTS
11 VENTS

ROOF VENTING KEY PLAN

ATTIC SPACE

ENCLOSED
RAFTER SPACE 1

ENCLOSED
RAFTER SPACE 2
N.T.S
LEGEND
INDICATES LOCATION OF REINFORCEMENT FOR AGING-INPLACE DESIGN AND FALL PROVENTION. SEE 9/A-5.1 FOR ADDITIONAL INFORMATION.

Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED
1 BEDROOM - FLOOR PLAN AND ROOF PLAN (MONTEREY)
A-1.2
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026
0 SCALE:
2' - 0" 4' - 0" 8' - 0"
1/4" = 1' - 0"
SCALE: 1/4" = 1'-0"

FLOOR PLAN - MONTEREY
1 SCALE: 1/4" = 1'-0"

ROOF PLAN - MONTEREY
2 AREA: 646 SF

KEYNOTES

1.01 LINE OF ROOF ABOVE

1.02 LINE OF BUILDING

1.03 EMEREGENCY EGRESS WINDOW AT SLEEPING ROOM

1.04 LANDING OR FLOOR REQUIRED AT EACH SIDE OF EXTERIOR

DOOR WITH MINIMUM WIDTH EQUAL TO THE WIDTH OF THE
DOOR SERVED AND MINIMUM DEPTH OF 36”. AND 36” MINIMUM
DEPTH MEASURED IN THE DIRECTION OF TRAVEL. LANDING OR
FINISHED FLOOR SHALL NOT BE MORE THAN 1 ½” LOWER THAN
THE TOP OF THE THRESHOLD. THE LANDING ON THE EXTERIOR
SIDE SHALL BE NOT MORE THAN 7 ¾” BELOW THE TOP OF THE

THRESHOLD PROVIDED THAT THE DOOR DOES NOT SWING
OVER THE LANDING OR FLOOR.

1.05 EXTERIOR LANDING SURFACE SLOPE NOT TO EXCEED ¼”/FOOT

AWAY FROM BUILDING

1.06 DOOR BELL, 48” MAX ABOVE EXTERIOR LANDING.

1.07 DOOR MUST PROVIDE NET CLEAR OPENING OF 32”

1.08 36” HIGH COUNTERTOP

1.09 SHELF AND HANGING ROD AT CLOSET

1.10 WALLS AND FLOORS AT BATHTUB AND SHOWER SPACES SHALL BE FINISHED WITH NON-ABSORBENT SURFACES. SUCH WALL
SURFACES SHALL EXTEND TO 72” MIN.

1.11 PROVIDE TEMPERED GLAZED ENCLOSURE AT OR ADJACENT TO

BATHTUBS AND/OR SHOWERS WHERE THE BOTTOM EXPOSED
EDGE OF GLAZING IS LESS THAN 60” ABOVE ANY STANDING OR
WALKING SURFACE.

1.12 PROVIDE REINFORCEMENT FOR GRAB BARS [CRC R327.1]. SEE

FLOOR PLAN GENERAL NOTES FOR ADDITIONAL INFORMATION
AND REQUIREMENTS.

1.13 PROVIDE FURRING AS NEEDED FOR STANDARD BATHTUB AND SHOWER LENGTH.

1.14 DRYER VENT AT EXTERIOR WALL MIN. 3 FT FROM ANY OPENING

1.15 2X6 STUD WALL

1.16 STACKED WASHER/DRYER MACHINE LOCATION

1.17 CEILING AT 8'-0" A.F.F.

1.18 GUTTER AND DOWNSPOUTS. PROVIDE DOWNSPOUT LOCATIONS AS REQUIRED BY SITE SPECIFIC CONDITIONS.

1.19 WATER HEATER, REFER TO MEP.

1.20 A CONDENSING UNIT SUPPORTED FROM THE GROUND SHALL

REST ON A CONCRETE OR OTHER APPROVED BASE EXTENDING
NOT LESS THAN 3 INCHES ABOVE THE ADJOINING GROUND
LEVEL [CMC 1105.2]

1.21B TILE ROOF

1.22 INDOOR UNIT, REFER TO MEP.

1.23 ELECTRICAL SUBPANEL, REFER TO MEP.

REVISIONS
NO. DATE DESCRIPTION
303
REF.

DW
A-2.3 2
A-2.3 3
A-2.3 4
A-2.3 1
1 A-3.3
2 A-3.3

BEDROOM
BATH
CLOSET

KITCHEN
CLO. W/D

1.01 3
2 7 6
45 A
AA
A
A
A
AB
21 AC
17' - 0"
13' - 6" 24' - 6"
B
38' - 0"
SLOPE
DOWN

SLOPEDOWN
12' -
2"
3' - 0" 1' - 10"
1' - 10" 3' - 0" 20' - 5" 3' - 0" 4' - 11" 3' - 0" 1' - 10" 1' - 10" 3' - 0" 3' - 10" 3' - 4" 5' - 0" DOWN SLOPE
SLOPE
DOWN
16' - 6" 2' - 8" 6' - 1" 3' - 0" 4' - 11" 3' - 0" 1' - 10" PATIO

1.11 1.10

1.12 1.13

1.15 1.17

1.16 1.04

1.05 1.04

1.03 1.07

1.07 1.14

1.19 1

1.06 2' - 7"
16' - 1"

1.08 1.17

1.17 LIVING

1.09 13' - 1"
2' - 1" 13' - 8 1/2"
5' - 6 1/2" 2' - 11" 3' - 1" 3' - 8" 8' - 1 1/2" 15' - 1 1/2"

LINE ABOVE,
TYP.

1.20 2' - 7" 8' - 7"
3' - 1"

1.22 1.22 1.23
A-5.1
1B
TYP.

A-2.3 2
A-2.3 3
A-2.3 4
A-2.3 1
1 A-3.3
2 A-3.3
SLOPE
4"/12"
SLOPE
4"/12"

1.02 21
ACB

1.18 1.18 3' - 0" 2' - 0"
2' -0" 2' -0"  SETBACK3' - 0"

1.21C

1. 2.

3. 4.

5. 6.

7. REFER TO GENERAL NOTES SHEET A1.0 FOR ADDITIONAL
REQUIREMENTS.

REFER TO STRUCTURAL DRAWINGS FOR ROOF FRAMING
INFORMATION.

ALL FURNITURE AND EQUIPMENT IS BY OWNER AND IS SHOWN
FOR COORDINATION PURPOSES ONLY.

SEE STRUCTURAL FOR EXTERIOR STUD WALL SIZE.

ONE (MIN.) SIDE-HINGED EGRESS DOOR SHALL BE PROVIDED
WITH A CLEAR WIDTH OF NOT LESS THAN 32” WHERE MEASURED

BETWEEN THE FACE OF THE DOOR AND THE STOP, WITH THE
DOOR OPEN 90°. THE CLEAR HEIGHT OF THE DOOR OPENING
SHALL BE NOT LESS THAN 78” IN HEIGHT MEASURED FROM THE
TOP OF THE THRESHOLD TO THE BOTTOM OF THE STOP.

REFER TO MECHANICAL AND PLUMBING PLAN FOR WATER
EFFICIENCY REQUIREMENTS FOR ALL PLUMBING FIXTURES.

ROOF OVERHANG DIMENSIONS ARE FROM FACE OF EXTERIOR

WALL FRAMING TO EDGE OF ROOF

FLOOR AND ROOF PLAN GENERAL SHEET NOTES

1. 2.

3. SOLAR READY ROOF MINIMUM AREA: 250 SF

THE SOLAR ZONE TOTAL ARE SHALL BE COMPRISED OF AREAS
THAT HAVE NO DIMENSION LESS THAN 5 FT. THE SOLAR ZONE

SHALL BE LOCATED ON THE ROOF OR OVERHANG OF THE
BUILDING. [CEC 2022 SECTION 110.10.(b)]
FOR PHOTOVOLTAIC ARRAYS OCCUPYING NOT MORE THAN 33

PERCENT OF THE PLAN VIEW TOTAL ROOF AREA, NOT LESS
THAN AN 18-INCH CLEAR SETBACK IS REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE. FOR PHOTOVOLTAIC ARRAYS
OCCUPYING MORE THAN 33 PERCENT OF THE PLAN VIEW TOTAL
ROOF AREA, NOT LESS THAN A 36-INCH CLEAR SETBACK IS
REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE. [CRC
R329.6.2]

THE SOLAR ZONE SHALL COMPLY WITH ACCESS, PATHWAY,

SMOKE VENTILATION, AND SPACING REQUIREMENTS AS
SPECIFIED IN TILE 24, PART 9 OR OTHER PARTS OF TITLE 24 OR IN ANY REQUIREMENTS ADOPTED BY LOCAL JURISDICTION.

SOLAR READY GENERAL NOTES

SOLAR ZONE

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMANGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

NET FREE VENTING AREA REQUIRED = (ENCLOSED AREA / 150)
[CRC R806.2]

ENCLOSED ATTIC SPACE
(152 SF / 150) = 1.02 SF MIN. [147 SQ. IN.]
WALLS AND PROJECTIONS LESS THAN 5 FEET FROM THE PROPERTY LINE SHALL COMPLY WITH CRC TABLES R302.1(1) AND (2).

ENCLOSED RAFTER SPACE 1
(229 SF / 150) = 1.53 SF MIN. [221 SQ. IN.]
ENCLOSED RAFTER SPACE 2
(265 SF / 150) = 1.77 SF MIN. [255 SQ. IN.]

ROOF VENTING CALCULATIONS
PROVIDE 3 1/2" X 14" (24 SQ. IN. VENTING AREA), EQUALLY SPACED.

VULCAN FIRE STOPPING SOFFIT VENT OR EQUIVALENT.
7 VENTS
10 VENTS
11 VENTS

ROOF VENTING KEY PLAN

ATTIC SPACE

ENCLOSED
RAFTER SPACE 1

ENCLOSED
RAFTER SPACE 2
N.T.S
LEGEND
INDICATES LOCATION OF REINFORCEMENT FOR AGING-INPLACE DESIGN AND FALL PROVENTION. SEE 9/A-5.1 FOR ADDITIONAL INFORMATION.

Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED
1 BEDROOM - FLOOR PLAN AND ROOF PLAN (MODERN FARMHOUSE) A-1.3
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026
0 SCALE:
2' - 0" 4' - 0" 8' - 0"
1/4" = 1' - 0"
SCALE: 1/4" = 1'-0"

FLOOR PLAN - MODERN FARMHOUSE
1 SCALE: 1/4" = 1'-0"

ROOF PLAN - MODERN FARMHOUSE
2 AREA: 646 SF

KEYNOTES

1.01 LINE OF ROOF ABOVE

1.02 LINE OF BUILDING

1.03 EMEREGENCY EGRESS WINDOW AT SLEEPING ROOM

1.04 LANDING OR FLOOR REQUIRED AT EACH SIDE OF EXTERIOR

DOOR WITH MINIMUM WIDTH EQUAL TO THE WIDTH OF THE
DOOR SERVED AND MINIMUM DEPTH OF 36”. AND 36” MINIMUM
DEPTH MEASURED IN THE DIRECTION OF TRAVEL. LANDING OR
FINISHED FLOOR SHALL NOT BE MORE THAN 1 ½” LOWER THAN
THE TOP OF THE THRESHOLD. THE LANDING ON THE EXTERIOR
SIDE SHALL BE NOT MORE THAN 7 ¾” BELOW THE TOP OF THE

THRESHOLD PROVIDED THAT THE DOOR DOES NOT SWING
OVER THE LANDING OR FLOOR.

1.05 EXTERIOR LANDING SURFACE SLOPE NOT TO EXCEED ¼”/FOOT

AWAY FROM BUILDING

1.06 DOOR BELL, 48” MAX ABOVE EXTERIOR LANDING.

1.07 DOOR MUST PROVIDE NET CLEAR OPENING OF 32”

1.08 36” HIGH COUNTERTOP

1.09 SHELF AND HANGING ROD AT CLOSET

1.10 WALLS AND FLOORS AT BATHTUB AND SHOWER SPACES SHALL BE FINISHED WITH NON-ABSORBENT SURFACES. SUCH WALL
SURFACES SHALL EXTEND TO 72” MIN.

1.11 PROVIDE TEMPERED GLAZED ENCLOSURE AT OR ADJACENT TO

BATHTUBS AND/OR SHOWERS WHERE THE BOTTOM EXPOSED
EDGE OF GLAZING IS LESS THAN 60” ABOVE ANY STANDING OR
WALKING SURFACE.

1.12 PROVIDE REINFORCEMENT FOR GRAB BARS [CRC R327.1]. SEE

FLOOR PLAN GENERAL NOTES FOR ADDITIONAL INFORMATION
AND REQUIREMENTS.

1.13 PROVIDE FURRING AS NEEDED FOR STANDARD BATHTUB AND SHOWER LENGTH.

1.14 DRYER VENT AT EXTERIOR WALL MIN. 3 FT FROM ANY OPENING

1.15 2X6 STUD WALL

1.16 STACKED WASHER/DRYER MACHINE LOCATION

1.17 CEILING AT 8'-0" A.F.F.

1.18 GUTTER AND DOWNSPOUTS. PROVIDE DOWNSPOUT LOCATIONS AS REQUIRED BY SITE SPECIFIC CONDITIONS.

1.19 WATER HEATER, REFER TO MEP.

1.20 A CONDENSING UNIT SUPPORTED FROM THE GROUND SHALL

REST ON A CONCRETE OR OTHER APPROVED BASE EXTENDING
NOT LESS THAN 3 INCHES ABOVE THE ADJOINING GROUND
LEVEL [CMC 1105.2]

1.21C STANDING SEAM METAL ROOF

1.22 INDOOR UNIT, REFER TO MEP.

1.23 ELECTRICAL SUBPANEL, REFER TO MEP.

REVISIONS
NO. DATE DESCRIPTION
304

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
2 A-3.1

2.02 2.08

2.05 2.03
2 1
T.O. SHEATING
± 11' - 9"
A
1 4"
1'-0"
4"
1'-0"
3' - 2"
TYP.

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
1 A-3.1

2.05 2.02

2.03 2.08
C B A
T.O. SHEATING
± 11' - 9"
A A A

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
2 A-3.1

2.05 2.08

2.02 2.03
1 2
T.O. SHEATING
± 11' - 9"
A
4"
1'-0"
4"
1'-0"
EA. SIDE

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
1 A-3.1

2.05 2.02

2.03 2.08
A B C
T.O. SHEATING
± 11' - 9"
B
A A

1. 2.

3. 4.

5. 6.

7. 8.

REFER TO GENERAL NOTES SHEET A1.1 FOR ADDITIONAL

REQUIREMENTS

REFERENCE DETAILS FOR ADDITIONAL INFORMATION AND
REQUIREMENTS.

REFERENCE DOOR AND WINDOW SCHEDULES FOR HEIGHT AND
SILL INFORMATION.

REFERENCE FLOOR PLANS AND FRAMING PLANS FOR
LOCATIONS OF DOORS AND WINDOWS.

CONTRACTOR TO VERIFY COLOR OF FINISH MATERIALS PRIOR
TO COMMENCING WORK.

REFER TO ROOF PLAN FOR ROOF OVERHANG DIMENSIONS.

PROVIDE ALUMINUM GUTTERS.

BUILDINGS SHALL HAVE APPROVED ADDRESS IDENTIFICATION

THAT IS LEGIBLE AND PLACED IN A POSITION THAT IS VISIBLE FROM THE STREET OR ROAD FRONTING THE PROPERTY.

ADDRESS IDENTIFICATION CHARACTERS SHALL CONTRAST WITH
THEIR BACKGROUND. ADDRESS NUMBERS SHALL BE ARABIC
NUMBERS OR ALPHABETICAL LETTERS. LETTERS SHALL NOT BE
SPELLED OUT. EACH CHARACTER SHALL BE NOT LESS THAN 4
INCHES IN HEIGHT WITH A STROKE WIDTH OF NOT LESS THAN ½ INCH. WHERE ACCESS IS BY MEANS OF A PRIVATE ROAD AND

THE BUILDING ADDRESS CANNOT BE VIEWED FROM THE PUBLIC

WAY, A MONUMENT, POLE OR OTHER SIGN OR MEANS SHALL BE
USED TO IDENTIFY THE STRUCTURE. ADDRESS IDENTIFICATION
SHALL BE MAINTAINED. [CRC R391.1]

ELEVATION GENERAL SHEET NOTES

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMANGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

Sheet #
D
C
B
A
1 2 3 4 5
1 2 3 4 5
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED
1 BEDROOM - EXTERIOR ELEVATIONS (CRAFTSMAN)
A-2.1
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026

KEYNOTES

2.02 HORIZONTAL FIBER CEMENT SIDING

2.03 STONE VENEER, MATERIAL SHALL COMPLY WITH CRC R703.8

2.05 ASPHALT SHINGLES

2.08 TRIM
0 SCALE:
2' - 0" 4' - 0" 8' - 0"
1/4" = 1' - 0"
SCALE: 1/4" = 1'-0"
ELEVATION A 1 SCALE: 1/4" = 1'-0"ELEVATION B 2
SCALE: 1/4" = 1'-0"
ELEVATION C 3 SCALE: 1/4" = 1'-0"ELEVATION D 4

REVISIONS
NO. DATE DESCRIPTION
305

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
2 A-3.2

2.01 2.08
2 1
T.O. SHEATING
± 11' - 9"
A
1 4"
1'-0"
4"
1'-0"

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
1 A-3.2

2.01 2.08
C B A
T.O. SHEATING
± 11' - 9"
A A A

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
2 A-3.2

2.06 2.01

2.08 1 2
T.O. SHEATING
± 11' - 9"
A
4"
1'-0"
4"
1'-0"

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
1 A-3.2

2.06 2.01

2.08 A B C
T.O. SHEATING
± 11' - 9"
B
A A

1. 2.

3. 4.

5. 6.

7. 8.

REFER TO GENERAL NOTES SHEET A1.1 FOR ADDITIONAL

REQUIREMENTS

REFERENCE DETAILS FOR ADDITIONAL INFORMATION AND
REQUIREMENTS.

REFERENCE DOOR AND WINDOW SCHEDULES FOR HEIGHT AND
SILL INFORMATION.

REFERENCE FLOOR PLANS AND FRAMING PLANS FOR
LOCATIONS OF DOORS AND WINDOWS.

CONTRACTOR TO VERIFY COLOR OF FINISH MATERIALS PRIOR
TO COMMENCING WORK.

REFER TO ROOF PLAN FOR ROOF OVERHANG DIMENSIONS.

PROVIDE ALUMINUM GUTTERS.

BUILDINGS SHALL HAVE APPROVED ADDRESS IDENTIFICATION

THAT IS LEGIBLE AND PLACED IN A POSITION THAT IS VISIBLE FROM THE STREET OR ROAD FRONTING THE PROPERTY.

ADDRESS IDENTIFICATION CHARACTERS SHALL CONTRAST WITH
THEIR BACKGROUND. ADDRESS NUMBERS SHALL BE ARABIC
NUMBERS OR ALPHABETICAL LETTERS. LETTERS SHALL NOT BE
SPELLED OUT. EACH CHARACTER SHALL BE NOT LESS THAN 4
INCHES IN HEIGHT WITH A STROKE WIDTH OF NOT LESS THAN ½ INCH. WHERE ACCESS IS BY MEANS OF A PRIVATE ROAD AND

THE BUILDING ADDRESS CANNOT BE VIEWED FROM THE PUBLIC

WAY, A MONUMENT, POLE OR OTHER SIGN OR MEANS SHALL BE
USED TO IDENTIFY THE STRUCTURE. ADDRESS IDENTIFICATION
SHALL BE MAINTAINED. [CRC R391.1]

ELEVATION GENERAL SHEET NOTES

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMANGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

Sheet #
D
C
B
A
1 2 3 4 5
1 2 3 4 5
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED
1 BEDROOM - EXTERIOR ELEVATIONS (MONTEREY)
A-2.2
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026

KEYNOTES

2.01 STUCCO. PROVIDE 2 LAYERS OF GRADE D PAPER UNDER
STUCCO WHEN OVER WOOD SHEATHING. [CRC R703.7.3]

2.06 TILE ROOF

2.08 TRIM
0 SCALE:
2' - 0" 4' - 0" 8' - 0"
1/4" = 1' - 0"
SCALE: 1/4" = 1'-0"
ELEVATION A 1 SCALE: 1/4" = 1'-0"ELEVATION B 2
SCALE: 1/4" = 1'-0"
ELEVATION C 3 SCALE: 1/4" = 1'-0"ELEVATION D 4

REVISIONS
NO. DATE DESCRIPTION
306

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
2 A-3.3

2.07 2.04

2.08 ALTERNATE:

SHINGLE ROOF

2.09 21
T.O. SHEATING
± 11' - 9"
A
1 2.09
4"
1'-0"
4"
1'-0"

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
1 A-3.3

2.07 2.04
ALTERNATE:

SHINGLE ROOF

2.08 CBA
T.O. SHEATING
± 11' - 9"
AAA

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
2 A-3.3

2.07 2.04

2.08 ALTERNATE:

SHINGLE ROOF
12 T.O. SHEATING
± 11' - 9"
A
4"
1'-0"
4"
1'-0"

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
1 A-3.3

2.07 ALTERNATE:

SHINGLE ROOF

2.08 2.04
ABC
T.O. SHEATING
± 11' - 9"
B
A
A

1. 2.

3. 4.

5. 6.

7. 8.

REFER TO GENERAL NOTES SHEET A1.1 FOR ADDITIONAL

REQUIREMENTS

REFERENCE DETAILS FOR ADDITIONAL INFORMATION AND
REQUIREMENTS.

REFERENCE DOOR AND WINDOW SCHEDULES FOR HEIGHT AND
SILL INFORMATION.

REFERENCE FLOOR PLANS AND FRAMING PLANS FOR
LOCATIONS OF DOORS AND WINDOWS.

CONTRACTOR TO VERIFY COLOR OF FINISH MATERIALS PRIOR
TO COMMENCING WORK.

REFER TO ROOF PLAN FOR ROOF OVERHANG DIMENSIONS.

PROVIDE ALUMINUM GUTTERS.

BUILDINGS SHALL HAVE APPROVED ADDRESS IDENTIFICATION

THAT IS LEGIBLE AND PLACED IN A POSITION THAT IS VISIBLE FROM THE STREET OR ROAD FRONTING THE PROPERTY.

ADDRESS IDENTIFICATION CHARACTERS SHALL CONTRAST WITH
THEIR BACKGROUND. ADDRESS NUMBERS SHALL BE ARABIC
NUMBERS OR ALPHABETICAL LETTERS. LETTERS SHALL NOT BE
SPELLED OUT. EACH CHARACTER SHALL BE NOT LESS THAN 4
INCHES IN HEIGHT WITH A STROKE WIDTH OF NOT LESS THAN ½ INCH. WHERE ACCESS IS BY MEANS OF A PRIVATE ROAD AND

THE BUILDING ADDRESS CANNOT BE VIEWED FROM THE PUBLIC

WAY, A MONUMENT, POLE OR OTHER SIGN OR MEANS SHALL BE
USED TO IDENTIFY THE STRUCTURE. ADDRESS IDENTIFICATION
SHALL BE MAINTAINED. [CRC R391.1]

ELEVATION GENERAL SHEET NOTES

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMANGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED
1 BEDROOM - EXTERIOR ELEVATIONS (MODERN FARMHOUSE)
A-2.3
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026

KEYNOTES

2.04 BOARD AND BATTEN FIBER CEMENT SIDING

2.07 STANDING SEAM METAL ROOF

2.08 TRIM

2.09 EXPOSED WOOD FRAMING – PRIMER & 2 COATS EXTERIOR
GRADE PAINT, REQUIRED. 0
SCALE:
2' - 0" 4' - 0" 8' - 0"
1/4" = 1' - 0"
SCALE: 1/4" = 1'-0"

ELEVATION A
1 SCALE: 1/4" = 1'-0"

ELEVATION B
2 SCALE: 1/4" = 1'-0"

ELEVATION C
3 SCALE: 1/4" = 1'-0"

ELEVATION D
4 REVISIONS
NO. DATE DESCRIPTION
307

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
2 A-3.1
LIVING
21 T.O. SHEATING
± 11' - 9"

3.01 3.02

3.03 3.05

3.06 3.07
A-5.2

1.1 A-5.1
6B
TYP.

3.09 FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
1 A-3.1
BEDROOM CLO. LIVING
ABC
T.O. SHEATING
± 11' - 9"

3.04 3.08

3.02 3.01

3.03 3.06

3.07 A-5.2

2.1 A-5.2

3.1 A-5.1
6A TYP.

3.09 1.

2. 3.

4. 1.

2. 3.

4. 5.

6. 7.

8. 9.

REFER TO GENERAL NOTES SHEET A-1.0 FOR ADDITIONAL
REQUIREMENTS.

REFERENCE DETAILS FOR ADDITIONAL INFORMATION AND
REQUIREMENTS.

THE PURPOSE OF THESE DRAWINGS IS TO SHOW
CONSTRUCTION MATERIALS/ASSEMBLIES. FOR SPECIFIC SIZES

AND DETAILS REFER TO ARCHITECTURAL PLANS, ELEVATIONS,
DETAILS, AND STRUCTURAL PLANS.

FIREBLOCKING TO BE LOCATED PER CRC SECTION R302.11:

A. SECTION R302.11 -1.

1. FIREBLOCKING SHALL BE PROVIDED IN CONCEALED SPACES

OF STUD WALLS AND PARTITIONS, INCLUDING FURRED SPACES

AND PARALLEL ROWS OF STUDS OR STAGGERED STUDS, AS
FOLLOWS:

1.1 VERTICALLY AT CEILING AND FLOOR LEVELS

1.2 HORIZONTALLY AT INTERVALS NOT EXCEEDING 10 FT.

2. AT INTERCONNECTIONS BETWEEN CONCEALED VERTICAL

AND HORIZONTAL SPACES SUCH AS SOFFITS, DROP CEILINGS
AND COVE CEILINGS.

3. IN CONCEALED SPACES BETWEEN STAIR STRINGERS AT
THE TOP AND BOTTOM OF THE RUN. ENCLOSED SPACES UNDER
STAIRS SHALL COMPLY WITH SECTION R302.7.

4. AT OPENINGS AROUND VENTS, PIPES, DUCTS, CABLES AND

WIRES AT CEILINGS AND FLOOR LEVEL, WITH AN APPROVED

MATERIAL TO RESIST THE FREE PASSAGE OF FLAME PRODUCTS
OF COMBUSTION. THE MATERIAL FILLING THIS ANNULAR SPACE
SHALL NOT BE REQUIRED TO MEET THE ASTM E136
REQUIREMENTS.

5. FOR THE FIREBLOCKING OF CHIMNEYS AND FIREPLACES,
SEE SECTION R1003.19.

B. SECTION R302.11.1 - FIREBLOCKING MATERIALS SHALL
CONSIST OF THE FOLLOWING MATERIALS:

TWO-INCH NOMINAL LUMBER

TWO THICKNESSES OF ONE-INCH NOMINAL LUMBER WITH

BROKEN LAP JOINTS
THE THICKNESS OF 0.719-INCH WOOD STRUCTURAL PANELS
WITH JOINTS BACKED BY 0.719-INCH WOOD STRUCTURAL
PANELS
THE THICKNESS OF 0.75-INCH PARTICLE BOARD WITH
JOINTS BACKED BY 0.75-INCH PARTICLE BOARD

ONE-HALF-INCH GYPSUM BOARD

ONE-FOURTH-INCH CEMENT-BASED MILLBOARD

BATTS OR BLANKETS OF MINERAL WOOL, MINERAL FIBER

OR OTHER APPROVED MATERIAL INSTALLED IN SUCH A

MANNER AS TO BE SECURELY RETAINED IN PLACE

CELLULOSE INSULATION INSTALLED AS TESTED IN
ACCORDANCE WITH ASTM E119 OR UL 263, FOR THE
SPECIFIC APPLICATION.

THE PURPOSE OF THESE DRAWINGS IS TO SHOW
CONSTRUCTION MATERIALS/ASSEMBLIES. FOR SPECIFIC

SIZES AND DETAILS REFER TO ARCHITECTURAL PLANS,
ELEVATIONS, DETAILS, AND STRUCTURAL PLANS.

5. PROVIDE BLOCKING FOR ALL WALLS WHERE WALL HUNG
EQUIPMENT AND FIXTURES OCCUR.

6. REFERENCE DOOR AND WINDOW SCHEDULES FOR HEIGHT AND
SILL INFORMATION.

7. REFERENCE FLOOR PLANS AND FRAMING PLANS FOR
LOCATIONS OF DOORS AND WINDOWS.

8. REFER TO TITLE 24 REPORT FOR INSULATION INFORMATION
AND REQUIREMENTS.

9. PROVIDE SOUND INSULATION AT BATHROOMS, LAUNDRY
ROOMS, AND PRIMARY BATHROOMS.

SECTION GENERAL SHEET NOTES

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMANGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED
1 BEDROOM - BUILDING SECTIONS (CRAFTSMAN)
A-3.1
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026

KEYNOTES

3.01 WALL INSULATION, REFER TO TITLE 24 REPORT

3.02 ROOF INSULATION, REFER TO TITLE 24 REPORT. REFER TO DETAILS A, B, AND C ON SHEET A5.2

3.03 WOOD STUD WALL, REFER TO STRUCTURAL DRAWINGS.

3.04 RAFTERS, REFER TO STRUCTURAL DRAWINGS.

3.05 RIDGE BEAM, REFER TO STRUCTURAL DRAWINGS.

3.06 CONCRETE SLAB ON GRADE, REFER TO STRUCTURAL

DRAWINGS

3.07 STRUCTURAL CONCRETE FOOTING, REFER TO STRUCTURAL
DRAWINGS.

3.08 WOOD FRAMING, SEE STRUCTURAL.

3.09 FINISHED GRADE, TYP. FOUNDATION WALLS SHALL EXTEND

ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION
AT ALL POINTS NOT LESS THAN 4 INCHES WHERE MASONRY
VENEER IS USED AND NOT LESS THAN 6 INCHES ELSEWHERE.
[CRC R404.1.6] 0
SCALE:
2' - 0" 4' - 0" 8' - 0"
1/4" = 1' - 0"
SCALE: 1/4" = 1'-0"

SECTION A
1 SCALE: 1/4" = 1'-0"

SECTION B
2 REVISIONS
NO. DATE DESCRIPTION
308

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
2 A-3.2
LIVING
21 T.O. SHEATING
± 11' - 9"

3.01 3.02

3.03 3.05

3.06 3.07
A-5.2

1.2 A-5.1
5B
TYP.

3.09 FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
1 A-3.2

BEDROOM LIVING
ABC
T.O. SHEATING
± 11' - 9"

3.04 3.02

3.03 3.06

3.07 3.01
A-5.2

2.2 A-5.2

2.2 A-5.2 4
CLO.

A-5.1
5A TYP.

3.09 1.

2. 3.

4. 1.

2. 3.

4. 5.

6. 7.

8. 9.

REFER TO GENERAL NOTES SHEET A-1.0 FOR ADDITIONAL
REQUIREMENTS.

REFERENCE DETAILS FOR ADDITIONAL INFORMATION AND
REQUIREMENTS.

THE PURPOSE OF THESE DRAWINGS IS TO SHOW
CONSTRUCTION MATERIALS/ASSEMBLIES. FOR SPECIFIC SIZES

AND DETAILS REFER TO ARCHITECTURAL PLANS, ELEVATIONS,
DETAILS, AND STRUCTURAL PLANS.

FIREBLOCKING TO BE LOCATED PER CRC SECTION R302.11:

A. SECTION R302.11 -1.

1. FIREBLOCKING SHALL BE PROVIDED IN CONCEALED SPACES

OF STUD WALLS AND PARTITIONS, INCLUDING FURRED SPACES

AND PARALLEL ROWS OF STUDS OR STAGGERED STUDS, AS
FOLLOWS:

1.1 VERTICALLY AT CEILING AND FLOOR LEVELS

1.2 HORIZONTALLY AT INTERVALS NOT EXCEEDING 10 FT.

2. AT INTERCONNECTIONS BETWEEN CONCEALED VERTICAL

AND HORIZONTAL SPACES SUCH AS SOFFITS, DROP CEILINGS
AND COVE CEILINGS.

3. IN CONCEALED SPACES BETWEEN STAIR STRINGERS AT
THE TOP AND BOTTOM OF THE RUN. ENCLOSED SPACES UNDER
STAIRS SHALL COMPLY WITH SECTION R302.7.

4. AT OPENINGS AROUND VENTS, PIPES, DUCTS, CABLES AND

WIRES AT CEILINGS AND FLOOR LEVEL, WITH AN APPROVED

MATERIAL TO RESIST THE FREE PASSAGE OF FLAME PRODUCTS
OF COMBUSTION. THE MATERIAL FILLING THIS ANNULAR SPACE
SHALL NOT BE REQUIRED TO MEET THE ASTM E136
REQUIREMENTS.

5. FOR THE FIREBLOCKING OF CHIMNEYS AND FIREPLACES,
SEE SECTION R1003.19.

B. SECTION R302.11.1 - FIREBLOCKING MATERIALS SHALL
CONSIST OF THE FOLLOWING MATERIALS:

TWO-INCH NOMINAL LUMBER

TWO THICKNESSES OF ONE-INCH NOMINAL LUMBER WITH

BROKEN LAP JOINTS
THE THICKNESS OF 0.719-INCH WOOD STRUCTURAL PANELS
WITH JOINTS BACKED BY 0.719-INCH WOOD STRUCTURAL
PANELS
THE THICKNESS OF 0.75-INCH PARTICLE BOARD WITH
JOINTS BACKED BY 0.75-INCH PARTICLE BOARD

ONE-HALF-INCH GYPSUM BOARD

ONE-FOURTH-INCH CEMENT-BASED MILLBOARD

BATTS OR BLANKETS OF MINERAL WOOL, MINERAL FIBER

OR OTHER APPROVED MATERIAL INSTALLED IN SUCH A

MANNER AS TO BE SECURELY RETAINED IN PLACE

CELLULOSE INSULATION INSTALLED AS TESTED IN
ACCORDANCE WITH ASTM E119 OR UL 263, FOR THE
SPECIFIC APPLICATION.

THE PURPOSE OF THESE DRAWINGS IS TO SHOW
CONSTRUCTION MATERIALS/ASSEMBLIES. FOR SPECIFIC

SIZES AND DETAILS REFER TO ARCHITECTURAL PLANS,
ELEVATIONS, DETAILS, AND STRUCTURAL PLANS.

5. PROVIDE BLOCKING FOR ALL WALLS WHERE WALL HUNG
EQUIPMENT AND FIXTURES OCCUR.

6. REFERENCE DOOR AND WINDOW SCHEDULES FOR HEIGHT AND
SILL INFORMATION.

7. REFERENCE FLOOR PLANS AND FRAMING PLANS FOR
LOCATIONS OF DOORS AND WINDOWS.

8. REFER TO TITLE 24 REPORT FOR INSULATION INFORMATION
AND REQUIREMENTS.

9. PROVIDE SOUND INSULATION AT BATHROOMS, LAUNDRY
ROOMS, AND PRIMARY BATHROOMS.

SECTION GENERAL SHEET NOTES

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMANGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED
1 BEDROOM - BUILDING SECTIONS (MONTEREY)
A-3.2
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026

KEYNOTES

3.01 WALL INSULATION, REFER TO TITLE 24 REPORT

3.02 ROOF INSULATION, REFER TO TITLE 24 REPORT. REFER TO DETAILS A, B, AND C ON SHEET A5.2

3.03 WOOD STUD WALL, REFER TO STRUCTURAL DRAWINGS.

3.04 RAFTERS, REFER TO STRUCTURAL DRAWINGS.

3.05 RIDGE BEAM, REFER TO STRUCTURAL DRAWINGS.

3.06 CONCRETE SLAB ON GRADE, REFER TO STRUCTURAL

DRAWINGS

3.07 STRUCTURAL CONCRETE FOOTING, REFER TO STRUCTURAL
DRAWINGS.

3.09 FINISHED GRADE, TYP. FOUNDATION WALLS SHALL EXTEND

ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION
AT ALL POINTS NOT LESS THAN 4 INCHES WHERE MASONRY
VENEER IS USED AND NOT LESS THAN 6 INCHES ELSEWHERE.
[CRC R404.1.6] 0
SCALE:
2' - 0" 4' - 0" 8' - 0"
1/4" = 1' - 0"
SCALE: 1/4" = 1'-0"

SECTION A
1 SCALE: 1/4" = 1'-0"

SECTION B
2 REVISIONS
NO. DATE DESCRIPTION
309

FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
2 A-3.3
LIVING
21 T.O. SHEATING
± 11' - 9"

3.01 3.02

3.03 3.05

3.06 3.07
A-5.2

1.1 A-5.1
4B
TYP.

3.09 FINISHED FLOOR
0"
B.O. ROOF
± 8' - 0"
1 A-3.3
BEDROOM CLO. LIVING
ABC
T.O. SHEATING
± 11' - 9"

3.04 3.08

3.02 3.03

3.06 3.07

3.01 A-5.2

2.1 A-5.2

3.3 A-5.1
4A TYP.

3.09 1.

2. 3.

4. 1.

2. 3.

4. 5.

6. 7.

8. 9.

REFER TO GENERAL NOTES SHEET A-1.0 FOR ADDITIONAL
REQUIREMENTS.

REFERENCE DETAILS FOR ADDITIONAL INFORMATION AND
REQUIREMENTS.

THE PURPOSE OF THESE DRAWINGS IS TO SHOW
CONSTRUCTION MATERIALS/ASSEMBLIES. FOR SPECIFIC SIZES

AND DETAILS REFER TO ARCHITECTURAL PLANS, ELEVATIONS,
DETAILS, AND STRUCTURAL PLANS.

FIREBLOCKING TO BE LOCATED PER CRC SECTION R302.11:

A. SECTION R302.11 -1.

1. FIREBLOCKING SHALL BE PROVIDED IN CONCEALED SPACES

OF STUD WALLS AND PARTITIONS, INCLUDING FURRED SPACES

AND PARALLEL ROWS OF STUDS OR STAGGERED STUDS, AS
FOLLOWS:

1.1 VERTICALLY AT CEILING AND FLOOR LEVELS

1.2 HORIZONTALLY AT INTERVALS NOT EXCEEDING 10 FT.

2. AT INTERCONNECTIONS BETWEEN CONCEALED VERTICAL

AND HORIZONTAL SPACES SUCH AS SOFFITS, DROP CEILINGS
AND COVE CEILINGS.

3. IN CONCEALED SPACES BETWEEN STAIR STRINGERS AT
THE TOP AND BOTTOM OF THE RUN. ENCLOSED SPACES UNDER
STAIRS SHALL COMPLY WITH SECTION R302.7.

4. AT OPENINGS AROUND VENTS, PIPES, DUCTS, CABLES AND

WIRES AT CEILINGS AND FLOOR LEVEL, WITH AN APPROVED

MATERIAL TO RESIST THE FREE PASSAGE OF FLAME PRODUCTS
OF COMBUSTION. THE MATERIAL FILLING THIS ANNULAR SPACE
SHALL NOT BE REQUIRED TO MEET THE ASTM E136
REQUIREMENTS.

5. FOR THE FIREBLOCKING OF CHIMNEYS AND FIREPLACES,
SEE SECTION R1003.19.

B. SECTION R302.11.1 - FIREBLOCKING MATERIALS SHALL
CONSIST OF THE FOLLOWING MATERIALS:

TWO-INCH NOMINAL LUMBER

TWO THICKNESSES OF ONE-INCH NOMINAL LUMBER WITH

BROKEN LAP JOINTS
THE THICKNESS OF 0.719-INCH WOOD STRUCTURAL PANELS
WITH JOINTS BACKED BY 0.719-INCH WOOD STRUCTURAL
PANELS
THE THICKNESS OF 0.75-INCH PARTICLE BOARD WITH
JOINTS BACKED BY 0.75-INCH PARTICLE BOARD

ONE-HALF-INCH GYPSUM BOARD

ONE-FOURTH-INCH CEMENT-BASED MILLBOARD

BATTS OR BLANKETS OF MINERAL WOOL, MINERAL FIBER

OR OTHER APPROVED MATERIAL INSTALLED IN SUCH A

MANNER AS TO BE SECURELY RETAINED IN PLACE

CELLULOSE INSULATION INSTALLED AS TESTED IN
ACCORDANCE WITH ASTM E119 OR UL 263, FOR THE
SPECIFIC APPLICATION.

THE PURPOSE OF THESE DRAWINGS IS TO SHOW
CONSTRUCTION MATERIALS/ASSEMBLIES. FOR SPECIFIC

SIZES AND DETAILS REFER TO ARCHITECTURAL PLANS,
ELEVATIONS, DETAILS, AND STRUCTURAL PLANS.

5. PROVIDE BLOCKING FOR ALL WALLS WHERE WALL HUNG
EQUIPMENT AND FIXTURES OCCUR.

6. REFERENCE DOOR AND WINDOW SCHEDULES FOR HEIGHT AND
SILL INFORMATION.

7. REFERENCE FLOOR PLANS AND FRAMING PLANS FOR
LOCATIONS OF DOORS AND WINDOWS.

8. REFER TO TITLE 24 REPORT FOR INSULATION INFORMATION
AND REQUIREMENTS.

9. PROVIDE SOUND INSULATION AT BATHROOMS, LAUNDRY
ROOMS, AND PRIMARY BATHROOMS.

SECTION GENERAL SHEET NOTES

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMANGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED
1 BEDROOM - BUILDING SECTIONS (MODERN FARMHOUSE)
A-3.3
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026

KEYNOTES

3.01 WALL INSULATION, REFER TO TITLE 24 REPORT

3.02 ROOF INSULATION, REFER TO TITLE 24 REPORT. REFER TO DETAILS A, B, AND C ON SHEET A5.2

3.03 WOOD STUD WALL, REFER TO STRUCTURAL DRAWINGS.

3.04 RAFTERS, REFER TO STRUCTURAL DRAWINGS.

3.05 RIDGE BEAM, REFER TO STRUCTURAL DRAWINGS.

3.06 CONCRETE SLAB ON GRADE, REFER TO STRUCTURAL

DRAWINGS

3.07 STRUCTURAL CONCRETE FOOTING, REFER TO STRUCTURAL
DRAWINGS.

3.08 WOOD FRAMING, SEE STRUCTURAL.

3.09 FINISHED GRADE, TYP. FOUNDATION WALLS SHALL EXTEND

ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION
AT ALL POINTS NOT LESS THAN 4 INCHES WHERE MASONRY
VENEER IS USED AND NOT LESS THAN 6 INCHES ELSEWHERE.
[CRC R404.1.6] 0
SCALE:
2' - 0" 4' - 0" 8' - 0"
1/4" = 1' - 0"
SCALE: 1/4" = 1'-0"

SECTION A
1 SCALE: 1/4" = 1'-0"

SECTION B
2 REVISIONS
NO. DATE DESCRIPTION
310

INTERIOR

INTERIOR EXTERIOR

SHEATHING

EXTERIOR SHEATHING

INSULATION
SIDING

WOOD FRAMING, SEE
STRUCT.

CORNER TRIM

SIDING AT INSIDE CORNER

SEALANT, EA SIDE
2 LAYERS WEATHER

RESISTIVE BARRIER

STONE VENEER AT OUTSIDE CORNER

EXTERIOR SHEATHING

INSULATION

WOOD FRAMING, SEE
STRUCT.

INTERIOR

SHEATHING

STONE VENEER
2 LAYERS WEATHER

RESISTIVE BARRIER

EXTERIOR INTERIOR

MORTAR SETTING BED

OVER SCRATCH COAT

METAL LATH

EXTERIOR SHEATHING

INSULATION
7/8" THICK STUCCO FINISH:

METAL LATH BELOW

SCRATCH, BROWN AND FINISH
COAT PER CRC R703.7

WOOD FRAMING, SEE
STRUCT.

INTERIOR

SHEATHING

CORNER BEAD

STUCCO AT OUTSIDE CORNER
2 LAYERS WEATHER

RESISTIVE BARRIER

EXTERIOR INTERIOR
NOTE: PROVIDE 2 LAYERS OF GRADE D PAPER UNDER STUCCO WHEN OVER WOOD SHEATHING. [CRC R703.7.3]

INSULATION

INTERIOR

SHEATHING

BASE TRIM

FLASHING
SIDING

FLASHING AND SEALANT
2 LAYERS OF WEATHER

RESISTIVE BARRIER

OVER PLYWOOD
GRADE, MIN 5% SLOPE

WOOD FRAMING,
SEE STRUCT.
8" MIN.

STRUCTURAL CONCRETE

FOUNDATION, SEE
STRUCT.

EXTERIOR SHEATHING

INSULATION

INTERIOR

SHEATHING

FLASHING
2 LAYERS OF WEATHER

RESISTIVE BARRIER

OVER PLYWOOD WOOD FRAMING,
SEE STRUCT.

STRUCTURAL CONCRETE

FOUNDATION, SEE
STRUCT.

EXTERIOR SHEATHING
7/8" THICK STUCCO FINISH:

METAL LATH BELOW

SCRATCH, BROWN AND FINISH
COAT PER CRC R703.7
GRADE, MIN 5% SLOPE
8" MIN.

NOTE: PROVIDE 26 GA (MIN) CORROSION RESISTANT OR PLASTIC WEEP SCREED WITH MINIMUM VERTICAL FLANGE. THE WEEP SCREEN SHALL BE OF A TYPE THAT WILL ALLOW TRAPPED WATER TO DRAIN TO THE EXTERIOR OF THE BUILDING [CRC R703.7.2.1]

INSULATION

INTERIOR

SHEATHING

FLASHING
2 LAYERS OF WEATHER

RESISTIVE BARRIER

WOOD FRAMING, OVER PLYWOOD
SEE STRUCT.

STRUCTURAL CONCRETE

FOUNDATION, SEE
STRUCT.

EXTERIOR SHEATHING

MORTAR SETTING BED

OVER SCRATCH COAT

STONE VENEER
GRADE, MIN 5% SLOPE
MIN.
8"

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

THROUGH PENTRATION @ WALL

GYPSUM BOARD

FILL, VOID OR CAVITY

MATERIALS, RATED TO

MATCH WALL RATING

THROUGH

PENETRANTS
DESIGN NO. U356
BEARING WALL RATING - 1 HR RATING 1 2 3 5 4
1 WOOD STUDS
NOMINAL 2X6 SPACED 16" O.C. WITH (2) 2X4 TOP PLATES (1) 2X4 BOTTOM PLATE. STUDS LATERALLY-BRACED BY WOOD
STRUCTURAL PANEL SHEATHING (ITEM 5) AND

EFFECECTIVELY FIRE STOPPED AT TOP AND BOTTOM OF
WALL.
2 GYPSUM BOARD
ANY 5/8 IN. THICK UL CLASSIFIED GYPSUM BOARD THAT IS
ELIGIBLE FOR USE IN DESIGN NOS. L501, G512 OR U305. NOM 5/8 IN. THICK, 4 FT WIDE, APPLIED VERTICALLY AND NAILED TO STUDS AND BEARING PLATES 7 IN. OC WITH 6D CEMENTCOATED NAILS, 1-7/8 IN. LONG WITH 1/4 IN. DIAM HEAD. 4 BATTS AND BLANKETS
MINERAL FIBER OR GLASS FIBER INSULATION, 3-1/2 IN.

THICK, PRESSURE FIT TO FILL WALL CAVITIES BETWEEN
STUDS AND PLATES. MINERAL FIBER INSULATION TO BE
UNFACED AND TO HAVE A MIN DENSITY OF 3 PCF. GLASS

FIBER INSULATION TO BE FACED WITH ALUMINUM FOIL OR
KRAFT PAPER AND TO HAVE A MIN DENSITY OF 0.9 PCF
(MIN R-13 THERMAL INSULATION RATING)
5 WOOD STRUCTURAL PANEL SHEATHING
MIN 7/16 IN. THICK, 4 FT WIDE WOOD STRUCTURAL PANELS,
MIN GRADE "C-D" OR "SHEATHING". INSTALLED WITH LONG

DIMENSION OF SHEET (STRENGTH AXIS) OR FACE GRAIN OF
PLYWOOD PARALLEL WITH OR PERPENDICULAR TO STUDS.

VERTICAL JOINTS CENTERED ON STUDS. HORIZONTAL JOINTS
BACKED WITH NOM 2 BY 4 IN. WOOD BLOCKING. ATTACHED TO
STUDS ON EXTERIOR SIDE OF WALL WITH 6D CEMENT
COATED BOX NAILS SPACED 6 IN. OC AT PERIMETER OF
PANELS AND 12 IN. OC ALONG INTERIOR STUDS.
6 EXTERIOR FACINGS

INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S
INSTALLATION INSTRUCTIONS. ONE OF THE FOLLOWING
EXTERIOR FACINGS IS TO BE APPLIED OVER THE SHEATHING:

D. CEMENTITIOUS STUCCO — PORTLAND CEMENT OR

SYNTHETIC STUCCO SYSTEMS WITH SELF-FURRING METAL
LATH OR ADHESIVE BASE COAT. THICKNESS FROM 3/8 TO 3/4
IN., DEPENDING ON SYSTEM.

H. FIBER-CEMENT SIDING — FIBER-CEMENT EXTERIOR

SIDINGS INCLUDING SMOOTH AND PATTERNED PANEL OR LAP
SIDING.

I. WALL AND PARTITION FACINGS AND ACCESSORIES* —

STONE VENEER IS MORTAR BONDED TO A LATH, SCRATCH

COAT AND WATER RESISTANT BARRIER APPLIED TO

SHEATHING, INSTALLED IN ACCORDANCE WITH THE

MANUFACTURERS INSTALLATION INSTRUCTIONS, AND
MEETING THE REQUIREMENTS OF LOCAL CODE AGENCIES.

NON-BEARING WALL PARTITION INTERSECTION—
(OPTIONAL) TWO NOMINAL 2 BY 4 IN. STUD OR NOMINAL 2 BY
6 IN. STUD NAILED TOGETHER WITH TWO 3IN. LONG 10D
NAILS SPACED A MAX. 16 IN. OC. VERTICALLY AND FASTENED
TO ONE SIDE OF THE MINIMUM 2 BY 4 IN. STUD WITH 3 IN.

LONG 10D NAILS SPACED A MAX 16 IN. OC. VERTICALLY.

INTERSECTION BETWEEN PARTITION WOOD STUDS TO BE
FLUSH WITH THE 2 BY 4 IN. STUDS. THE WALL PARTITION
WOOD STUDS ARE TO BE FRAMED BY WITH A SECOND 2 BY 4
IN. WOOD STUD FASTENED WITH 3 IN. LONG 10D NAILS
SPACED A MAX. 16 IN. OC. VERTICALLY. MAXIMUM ONE NONBEARING WALL PARTITION INTERSECTION PER STUD CAVITY.

NON-BEARING WALL PARTITION STUD DEPTH SHALL BE AT A
MINIMUM EQUAL TO THE DEPTH OF THE BEARING WALL.
3 JOINTS AND FASTENER HEADS

GYPSUM BOARD JOINTS COVERED WITH TAPE AND JOINT
COMPOUND. FASTENER HEADS COVERED WITH JOINT
COMPOUND.

THROUGH PENTRATION @ WALL

FRAMING
6 INSULATION

INTERIOR

SHEATHING

BASE TRIM

FLASHING
SIDING

FLASHING AND SEALANT
2 LAYERS OF WEATHER

RESISTIVE BARRIER

OVER PLYWOOD

CONCRETE WALK SURFACE,
MIN 2% SLOPE

WOOD FRAMING,
SEE STRUCT.

STRUCTURAL CONCRETE

FOUNDATION, SEE
STRUCT.

EXTERIOR SHEATHING
2"
1/2" EXPANSION JOINT

INSULATION

INTERIOR

SHEATHING

FLASHING
2 LAYERS OF WEATHER

RESISTIVE BARRIER

OVER PLYWOOD

CONCRETE WALK SURFACE,
MIN 2% SLOPE

WOOD FRAMING,
SEE STRUCT.

STRUCTURAL CONCRETE

FOUNDATION, SEE
STRUCT.

EXTERIOR SHEATHING
2"
7/8" THICK STUCCO FINISH:

METAL LATH BELOW

SCRATCH, BROWN AND FINISH
COAT PER CRC R703.7
1/2" EXPANSION JOINT
NOTE: PROVIDE 26 GA (MIN) CORROSION RESISTANT OR PLASTIC WEEP SCREED WITH MINIMUM VERTICAL FLANGE. THE WEEP SCREEN SHALL BE OF A TYPE THAT WILL ALLOW TRAPPED WATER TO DRAIN TO THE EXTERIOR OF THE BUILDING [CRC R703.7.2.1]

INSULATION

INTERIOR

SHEATHING

FLASHING
2 LAYERS OF WEATHER

RESISTIVE BARRIER

OVER PLYWOOD

CONCRETE WALK SURFACE,
MIN 2% SLOPE

WOOD FRAMING,
SEE STRUCT.

STRUCTURAL CONCRETE

FOUNDATION, SEE
STRUCT.

EXTERIOR SHEATHING
2"

MORTAR SETTING BED

OVER SCRATCH COAT
1/2" EXPANSION JOINT

STONE VENEER
39 1/4"
32"
39 1/4"
32"
SHOWER

SIDE WALLS BACK WALL
TOILET
39 1/4"
32"
39 1/4"
32"
36" MIN. 54" MIN.

1. 2.

NOTES:

PROVIDE REINFORCEMENT FOR AGING-IN-PLACE DESIGN
AND FALL PREVENTION AS REQUIRED BY CRC R327.1.1

INFORMATION AND/OR DRAWINGS IDENTIFYING THE

LOCATION OF GRAB BAR REINFORCEMENT SHALL BE

PLACED IN THE OPERATION AND MAINTENANCE MANUAL

IN ACCORDANCE WITH THE CALIFORNIA GREEN BUILDING
STANDARDS CODE, CHAPTER 4, DIVISION 4.4.
[R327.1.1.1 CRC]

FRONT SIDE
39 1/4"
32"
39 1/4"
6"

BATHTUB

SIDE WALLS BACK WALL

REINFORCEMENT AREA,
TYP.

1. 2.

NOTES:

WATER CLOSETS SHALL HAVE 15 INCHES TO ANY WALL OR
OBSTRUCTION ON EACH SIDE OF ITS CENTERLINE AND 24-
INCH CLEAR SPACE IN FRONT. [ 402.5 CPC]
SHOWER COMPARTMENTS SHALL BE NOT LESS THAN 1,024

SQUARE INCHES AND ALSO BE CAPABLE OF
ENCOMPASSING A 30-INCH DIAMETER CIRCLE. [ 408.6 CPC]
MIN.
15"
MIN.
15"
ø 2' - 6"
24"

EXTERIOR SHEATHING

INSULATION
SIDING

WOOD FRAMING, SEE
STRUCT.

INTERIOR

SHEATHING

CORNER TRIM

SIDING AT OUTSIDE CORNER
2 LAYERS WEATHER

RESISTIVE BARRIER

EXTERIOR INTERIOR

INTERIOR

INTERIOR EXTERIOR

SHEATHING

EXTERIOR SHEATHING

INSULATION
7/8" THICK STUCCO FINISH:

METAL LATH BELOW SCRATCH,

BROWN AND FINISH COAT PER
CRC R703.7

WOOD FRAMING, SEE
STRUCT.
2 LAYERS WEATHER

RESISTIVE BARRIER

STUCCO AT INTSIDE CORNER
NOTE: PROVIDE 2 LAYERS OF GRADE D PAPER UNDER STUCCO WHEN OVER WOOD SHEATHING. [CRC R703.7.3]

INTERIOR

EXTERIOR INTERIOR

SHEATHING

EXTERIOR SHEATHING

INSULATION

STONE VENEER

WOOD FRAMING, SEE
STRUCT.

STONE VENEER AT INSIDE CORNER
2 LAYERS WEATHER

RESISTIVE BARRIER

MORTAR SETTING BED

OVER SCRATCH COAT
Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

DETAILS
A-5.1
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026
SCALE: 1 1/2" = 1'-0"
PLAN DETAIL - SIDING (INSIDE CORNER) 1A
SCALE: 1 1/2" = 1'-0"

PLAN DETAIL - STONE VENEER (OUTSIDE CORNER)
SCALE: 1 1/2" = 1'-0" 3B PLAN DETAIL - STUCCO (OUTSIDE CORNER) 2B SCALE: 1 1/2" = 1'-0"
BASE DETAILS - SIDING AT GRADE 4B SCALE: 1 1/2" = 1'-0"BASE DETAILS - STUCCO AT GRADE 5B SCALE: 1 1/2" = 1'-0"BASE DETAILS - STONE VENEER AT GRADE 6B

REVISIONS
NO. DATE DESCRIPTION
0 SCALE:
6" 1' - 0" 2' - 0"
1 1/2" = 1' - 0"
SCALE: 1 1/2" = 1'-0"
7 FIRE RESISTIVE 1- HOUR

WOOD FRAMED WALLS
SCALE: 1 1/2" = 1'-0"
BASE DETAILS - SIDING AT PAVED WALK 4A SCALE: 1 1/2" = 1'-0"BASE DETAILS - STUCCO AT PAVED WALK 5A SCALE: 1 1/2" = 1'-0"BASE DETAILS - STONE VENEER AT PAVED WALK 6A SCALE: 1/4" = 1'-0"
9 REINFORCEMENT DETAILS
SCALE: 1/4" = 1'-0"

BATHROOM CLEARANCE DIAGRAMS
8 SCALE: 1 1/2" = 1'-0"
PLAN DETAIL - SIDING (OUTSIDE CORNER) 1B
SCALE: 1 1/2" = 1'-0"
PLAN DETAIL - STUCCO (INSIDE CORNER) 2A SCALE: 1 1/2" = 1'-0"PLAN DETAIL - STONE VENEER (INSIDE CORNER) 3A 311

ROOF SHEATHING

GUTTER WITH GUARD
1"X 12" FASCIA BOARD

TONGUE AND GROOVE SOFFIT

ROOFING FINISH MATERIAL

EXTERIOR WALL FINISH PER

ELEVATION

WEATHER RESISTIVE BARRIER

SHEATHING
CL
26 GA GSM EDGE FLASHING 3"
MIN. LAP OVER UNDERLAYMENT
AND 1" MIN. VERTICAL LAP

OVER EDGEBOARD

PER ROOF PLAN
BLOCKING, TYP.

TRIM (AT CRAFTSMAN STYLE)

GUTTER WITH GUARD
1"x 6" FASCIA BOARD

ROOFING FINISH MATERIAL
CL
PLAN

PER ROOF
26 GA GSM EDGE FLASHING 3"
MIN. LAP OVER UNDERLAYMENT
AND 1" MIN. VERTICAL LAP

OVER EDGEBOARD
BLOCKING, TYP.

EXTERIOR WALL FINISH PER

ELEVATION

WEATHER RESISTIVE BARRIER

SHEATHING

SHEATHING & FRAMING PER

STRUCTURAL
2 X BLOCKING

FASCIA BOARD

ROOFING FINISH

MATERIAL
SOFFIT

PER ROOF PLAN
26 GA GSM EDGE
FLASHING 3" MIN. LAP

OVER UNDERLAYMENT
AND 1" MIN. VERTICAL

LAP OVER EDGEBOARD

EXTERIOR WALL FINISH PER

ELEVATION

WEATHER RESISTIVE

BARRIER

SHEATHING
CL

SHEATHING & FRAMING PER

STRUCTURAL
2 X BLOCKING
1" X 6" FASCIA BOARD
26 GA GSM EDGE
FLASHING 3" MIN. LAP

OVER UNDERLAYMENT
AND 1" MIN. VERTICAL

LAP OVER EDGEBOARD

ROOFING FINISH

MATERIAL
CL

SHEATHING & FRAMING PER

STRUCTURAL
2 X BLOCKING
1"x12" FASCIA BOARD
26 GA GSM EDGE
FLASHING 3" MIN. LAP

OVER UNDERLAYMENT
AND 1" MIN. VERTICAL

LAP OVER EDGEBOARD

ROOFING FINISH MATERIAL
SOFFIT

PER ROOF PLAN

EXTERIOR WALL FINISH PER

ELEVATION

WEATHER RESISTIVE

BARRIER

SHEATHING
CL

SHEATHING & FRAMING PER

STRUCTURAL
2 X BLOCKING
1"x12" FASCIA BOARD
26 GA GSM EDGE
FLASHING 3" MIN. LAP

OVER UNDERLAYMENT
AND 1" MIN. VERTICAL

LAP OVER EDGEBOARD

ROOFING FINISH MATERIAL
SOFFIT

PER ROOF PLAN

EXTERIOR WALL FINISH PER

ELEVATION

WEATHER RESISTIVE

BARRIER

SHEATHING
MAX.
9"
CL

ROOFING FINISH MATERIAL

ROOF SHEATHING AND

FRAMING PER STRUCTURAL
26 GA GSM EDGE FLASHING 3" MIN. LAP
OVER UNDERLAYMENT AND 1" MIN.

VERTICAL LAP OVER EDGEBOARD

FASCIA BOARD
LEDGER BOARD, TYP.

REFER TO STRUCT.
4" MIN.

METAL FLASHING, RETURN UP

WALL BEHIND WEATHER

RESISTIVE BARRIER

EXTERIOR WALL FINISH PER

ELEVATION

SHEATHING

WEATHER RESISTIVE BARRIER

DRIP EDGE
6' -8" MIN

WHEN WALKING SURFACE BELOW
6' -8" MIN

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMAGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

ROOF RAFTERS, REF STRUCT.

ROOF SHEATHING

AIR- IMPERMEABLE INSULATION IN

CONTACT WITH SHEATHING WITH

REQ'D R-VALUE

GYPSUM BOARD, REF PLANS
ROOF RAFTERS, REF STRUCT.

ROOF SHEATHING

AIR- IMPERMEABLE INSULATION IN

CONTACT WITH SHEATHING WITH

REQ'D R-VALUE

GYPSUM BOARD, REF PLANS

AIR-PERMEABLE INSULATION

INSTALLED DIRECTLY UNDER THE

STRUCTURAL SHEATHING
ROOF RAFTERS, REF STRUCT.

ROOF SHEATHING

AIR- IMPERMEABLE INSULATION IN

CONTACT WITH SHEATHING WITH
REQ. R-VALUE

GYPSUM BOARD, REF PLANS
Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

ROOF DETAILS
A-5.2
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026
SCALE: 1" = 1'-0"
CRAFTSMAN/ MODERN FARMHOUSE EAVE 1.1
SCALE: 1" = 1'-0"
MONTEREY EAVE 1.2
SCALE: 1" = 1'-0"
CRAFTSMAN/ MODERN FARMHOUSE GABLE 2.1
SCALE: 1" = 1'-0"
MONTEREY GABLE 2.2
SCALE: 1" = 1'-0"
CRAFTSMAN GABLE (FRONT) 3.1
SCALE: 1" = 1'-0"
3 - MODERN FARMHOUSE GABLE (FRONT) 3.3
SCALE: 1" = 1'-0"
4 - MONTEREY AWNING
4 REVISIONS
NO. DATE DESCRIPTION
0 SCALE:
6" 1' - 0" 2' - 0"
1" = 1' - 0"
B SCALE: 1" = 1'-0"

INSULATION AT UNVENTED ROOF ASSEMBLY -

IMPERMEABLE INSULATION ONLY
SCALE: 1" = 1'-0"
INSULATION @ UNVENTED ROOF ASSEMBLY - BOTH TYPES
A
SCALE: 1" = 1'-0"
INSULATION @ UNVENTED ROOF ASSEMBLY - OVER/ UNDER
C
312

GENERAL WINDOW NOTES

1. 2.

3. 4.

5. 6.

A.

B.

C.
a.
b.

D.

E.

F.

7. REFER TO GENERAL NOTES SHEET A1.0 FOR ADDITIONAL
REQUIREMENTS.

REFER TO FLOOR PLANS FOR LOCATION OF DOORS AND
DIRECTION OF DOOR SWING.

CONTRACTOR TO VERIFY EXACT ROUGH OPENING SIZES PRIOR
TO FABRICATION OF ROUGH OPENINGS.

ALL GLAZING, INCLUDING GLAZED DOORS AND GLAZED

OPENINGS WITHIN EXTERIOR DOORS, SHALL BE INSULATING
GLASS UNITS WITH A MINIMUM OF ONE TEMPERED PANE.

TEMPERED GLASS SHALL BE PERMENENTLY IDENTIFIED AND
VISIBLE WHEN THE UNIT IS GLAZED.

EXTERIOR FIRE RATED DOORS SHALL COMPLY WITH ONE OF
THE FOLLOWING PER CBC 2022 708A.3:

THE EXTERIOR SURFACE OR CLADDING SHALL BE OF

NONCUMBUSTIBLE MATERIAL

THE EXTERIOR SURFACE CLADDING SHALL BE OF

IGNITION-RESISTANT MATERIALS

THE EXTERIOR DOOR SHALL BE CONSTRUCTED OF SOLID

CORE WOOD THAT COMPLIES WITH THE FOLLOWING
REQUIREMENTS:

THICK
PANELS SHALL NOT BE LESS THAN 1 ¼” THICK,

EXCEPT FOR THE EXTERIOR PERIMETER OF THE

PANEL THAT SHALL BE PERMITTED TO TAPER TO
A TONGUE NOT LESS THAN 3/8” THICK.

THE EXTERIOR DOOR ASSEMBLY SHALL HAVE A FIRERESISTANCE RATING OF NOT LESS THAN 30 MINUTES WHEN TEST ACCORDING TO NFPA 252.

THE EXTERIOR SURFACE CLADDING SHALL BE TESTED TO

MEET THE PERFORMANCE REQUIREMENTS WHEN TESTED
IN ACCORDANCE WITH ASTM E2707

THE EXTERIOR SURFACE OR CLADDING SHALL BE TESTED

TO MEET THE PERFORMANCE REQUIREMENTS OF SFM
STANDARD 12-7A-1.

GLAZING IN FIXED AND OPERABLE PANELS OF SWINGING,

SLIDING, AND BIFOLD DOORS SHALL BE CONSIDERED TO BE A
HAZARDOUS LOCATION [CRC SECTION R308.4]. PROVIDE
SAFETY GLAZING.

GENERAL DOOR NOTES

1. 2.

3. 4.

5. 6.

7. 8.

9. 10.

11. 12.

13. 14.

A.

B.

C.

D.

REFER TO GENERAL NOTES SHEET A-1.0 FOR ADDITIONAL
REQUIREMENTS.

REFER TO FLOOR PLANS FOR WINDOW LOCATIONS.

REFER TO ELEVATIONS FOR DIRECTION OF OPERATION OF
WINDOWS.

PROVIDE ALL OPERABLE WINDOWS WITH SCREENS.

CONTRACTOR TO VERIFY EXACT ROUGH OPENING SIZES PRIOR
TO FABRICATION OF ROUGH OPENINGS.

REFER TO ENERGY COMPLIANCE REPORTS FOR U-FACTOR,
SHGC AND ADDITIONAL WINDOW REQUIREMENTS.

WINDOWS MUST HAVE A FRAME AND SASH COMPRISED OF

WELDED CORNERS, METAL REINFORCEMENT IN THE INTERLOCK
AREA.

ALL GLAZING SHALL BE INSULATING GLASS UNITS WITH A
MINIMUM OF ONE TEMPERED PANE.

TEMPERED GLASS SHALL BE PERMENENTLY IDENTIFIED AND
VISIBLE WHEN THE UNIT IS GLAZED.

GLAZING IN WALLS ADJACENT TO BATHTUB AND OR SHOWER,

WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS LESS
THAN 60" MEASURED VERTICALLY ABOVE ANY STANDING OR
WALKING SURFACE, SHALL BE SAFETY GLAZING. [CRC SECTION
R308.4.5]

EMERGENCY ESCAPE AND RESCUE WINDOWS SHALL HAVE A

CLEAR OPENING WITH THE BOTTOM OF THE CLEAR OPENING
NOT GREATER THAN 44" AFF, MIN. THE NET CLEAR OPENING FOR EMERGENCY ESCAPE SHALL BE 5.7 S.F. (5 S.F. MIN. AT GROUND FLOOR). MINIMUM NET CLEAR OPENING DIMENSIONS: HEIGHT:
24", WIDTH: 20". [CRC SECTION R310.2]

EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL OPEN

DIRECTLY INTO A PUBLIC WAY, OR TO A YARD OR COURT HAVING A MINIMUM WIDTH OF 36” THAT OPENS TO A PUBLIC WALL [CRC SECTION 310.1]
ALL GLAZING SHALL MEET TITLE 24 ENERGY REQUIREMENTS.

FIRE RATED EXTERIOR WINDOWS AND EXTERIOR GLAZED DOOR

ASSEMBLIES SHALL COMPLY WITH ONE OF THE FOLLOWING
REQUIRMENTS PER CBC 708A.2.1:

BE CONSTRUCTED OF MULTIPANE GLAZING WITH A MINIMUM

OF ONE TEMPERED PANE MEETING THE REQUIREMENTS OF
SECTION 2406 SAFETY GLAZING

BE CONSTRUCTED OF GLASS BLOCK UNITS
HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 20
MINUTES WHEN TESTED ACCORDING TO NFPA 257

BE TESTED TO MEET THE PERFORMANCE REQUIREMENTS
OF SFM STANDARD 12-7A-2.

15. THE LOAD RESISTANCE OF GLASS UNDER UNIFORM LOAD SHALL BE DETERMINED IN ACCORDANCE WITH ASTM E1300.

BY USING THESE PERMIT READY CONSTRUCTION DOCUMENTS, THE RECIPIENT

ACKNOWLEDGES, ACCEPTS, AND VOLUNTARILY AFFIRMS THE FOLLOWING CONDITIONS:

1. THE USE OF THIS INFORMATION IS RESTRICTED TO THE ORIGINAL PROJECT FOR

WHICH IT WAS PREPARED FOR THE PERMIT READY ACCESSORY DWELLING (ADU) PROGRAM FOR THE CITY OF WILDOMAR ONLY. THIS IS A LIMITED SET OF

STANDARDIZED ADU PLANS AND SPECIFICATIONS APPROVED BY THE CITY OF WILDOMAR BUILDING & SAFETY DEPARTMENT. BUILDING CODES DO CHANGE OVER

TIME AND RECIPIENT SHALL ENSURE FULL COMPLIANCE UNDER ALL CODES THEN IN EFFECT AT THE TIME OF THE SUBJECT PERMIT. THIS DOES NOT ELIMINATE OR

REDUCE THE RECIPIENT'S RESPONSIBILITY TO VERIFY ANY AND ALL INFORMATION RELEVANT TO THE RECIPIENT'S WORK AND RESPONSIBILITY ON THIS PROJECT.

MICHAEL BAKER INTERNATIONAL SHALL NOT BE RESPONSIBLE FOR TRANSLATION ERRORS. DO NOT USE THESE CONSTRUCTION DOCUMENTS IF THE PERMIT HAS EXPIRED OR IS REVOKED AT ALL.

2. THE RECIPIENT RECOGNIZES AND ACKNOWLEDGES THAT THE USE OF THIS

INFORMATION WILL BE AT THEIR SOLE RISK AND WITHOUT LIABILITY OR LEGAL EXPOSURE TO MICHAEL BAKER INTERNATIONAL. NO WARRANTIES OF ANY

NATURE, WHETHER EXPRESS OR IMPLIED, SHALL ATTACH TO THESE DOCUMENTS AND THE INFORMATION CONTAINED THEREIN. ANY USE, REUSE, OR ALTERATION

OF THESE DOCUMENTS BY THE RECIPIENT OR OTHERS WILL BE AT THE RECIPIENT'S RISK AND FULL LEGAL RESPONSIBILITY. FURTHERMORE, THE

RECIPIENT WILL, TO THE FULLEST EXTENT PERMITTED BY THE LAW, DEFEND,

INDEMNIFY AND HOLD MICHAEL BAKER INTERNATIONAL AND ITS ARCHITECTS

HARMLESS FROM ANY AND ALL CLAIMS, SUITS, LIABILITY, DEMANDS,

JUDGEMENTS, OR COSTS ARISING OUT OF OR RESULTING THERE FROM ANY USE

OF THESE CONSTRUCTION DOCUMENTS FOR OR ON ACCOUNT OF ANY INJURY,

DEATH, DAMAGE OR LOSS TO PERSONS OR PROPERTY, DIRECT OF CONSEQUENTIAL DAMANGES IN ANY AMOUNT. THIS INDEMNITY DOES NOT APPLY

TO THE SOLE NEGLIGENCE OR WILLFUL MISCONDUCT OF MICHAEL BAKER INTERNATIONAL OR ITS ARCHITECTS.

3. MICHAEL BAKER INTERNATIONAL REPRESENTED BY THESE PLANS ARE COPYRIGHTED AND ARE SUBJECT TO COPYRIGHT PROTECTION.

4. IF THE RECIPIENT DOES NOT AGREE WITH THE ABOVE CONDITIONS, DO NOT

PROCEED WITH CONSTRUCTION OF AN ADU OR OTHER IMPROVEMENT UNDER THESE PLANS AT ALL.

BCD
6' - 8"6' - 8"6' - 8"
1 3/4"
SCHDL
REF 1 3/4" 1 3/4"
SCHDL
REF 1 3/4" 1 3/4"
SCHDL
REF 1 3/4"
A
(CRAFTSMAN)
A
(MONTEREY)
A
(MODERN

FARMHOUSE)
6' - 8"
5 1/2" 3' - 0" 5 1/2"
6' - 8"6' - 8"
4 1/2" 3' - 0" 4 1/2" 5 1/2" 3' - 0" 5 1/2"
TRIM,
TYP.

TRIM,
TYP.

TRIM,
TYP.
4/A-6.1
5/A-6.1
4/A-6.1
5/A-6.1
4/A-6.1
5/A-6.1
A
(MONTEREY)
A
(MODERN FARMHOUSE)
3' - 6" 5 1/2"
A
(CRAFTSMAN)
3 1/2" 3' - 0" 3 1/2"
3 1/2"
3' - 6" 3 1/2"
5 1/2"
3' - 0"
5 1/2"
5 1/2" 3' - 6" 5 1/2"
B
(MONTEREY)
B
(MODERN FARMHOUSE)

HEAD HEIGHT
6' - 8" TYP.

B
(CRAFTSMAN)
5 1/2" 3' - 0" 5 1/2"
5 1/2" 2' - 8"
5 1/2"
3 1/2" 2' - 8" 3 1/2"
3 1/2" 1' - 6" 3 1/2"
5 1/2" 2' - 8" 5 1/2"
5 1/2" 1' - 6" 5 1/2"
5 1/2"
1' - 6"
5 1/2"

HEAD HEIGHT
6' - 8" TYP.

TRIM, TYP.

TRIM, TYP.
1/A-6.1
6/A-6.1
2/A-6.1
1/A-6.1
3/A-6.1
2/A-6.1
1/A-6.1
3/A-6.1
2/A-6.1
1/A-6.1
3/A-6.1
2/A-6.1
1/A-6.1
3/A-6.1
2/A-6.1
1/A-6.1
3/A-6.1
2/A-6.1
NOTE: EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE CLEAR OPENING NOT GREATER THAN 44 INCHES MEASURED FROM THE FINISH FLOOR. [CRC R310.2] SILL 3' - 2" TYP.

EXTERIOR SHEATHING
WALL FRAMING. SEE
STRUCT.

EXTERIOR FINISH

MATERIAL

WATER RESISTIVE
BARRIER, MIN 6" OVER

FLASHING
WINDOW

EXTERIOR TRIM

SEALANT AND

BACKER ROD

EXTERIOR INTERIOR

EXTERIOR SHEATHING

WALL FRAMING, SEE
STRUCT.

EXTERIOR FINISH

MATERIAL

WATER RESISTIVE
BARRIER, MIN 6" OVER

FLASHING

DOOR AND FRAME

EXTERIOR TRIM

SEALANT, ALL

SIDES OF TRIM

EXTERIOR INTERIOR

EXTERIOR

SHEATHING

WALL FRAMING
(SEE STRUCT.)

EXTERIOR FINISH

MATERIAL

WATER RESISTIVE

BARRIER
WINDOW

TRIM, SEALANT

ALL SIDES

SEALANT AND

BACKER ROD

EXTERIOR

INTERIOR
DOOR

EXTERIOR

SHEATHING

WALL FRAMING
(SEE STRUCT.)

EXTERIOR FINISH

MATERIAL

WATER RESISTIVE

BARRIER TRIM, SEALANT

ALL SIDES

SEALANT AND

BACKER ROD

EXTERIOR

SHEATHING

WALL FRAMING

EXTERIOR FINISH

MATERIAL

WATER RESISTIVE

BARRIER
WINDOW

SLOPED TRIM

SEALANT AND

BACKER ROD

SILL FLASHING

EXTERIOR

SHEATHING

WALL FRAMING

EXTERIOR FINISH

MATERIAL

WATER RESISTIVE

BARRIER
WINDOW

CONCRETE OR

STONE SILL

SEALANT AND

BACKER ROD

SILL FLASHING

EXTERIOR INTERIOR

SHEET METAL FLASHING,

SOLDER ALL JOINTS
TYP.
4" LAP
2" MIN.
1/4"
6" MIN.

FLASHING PAPER, MOISTOP
FLASHING OR EQUAL (9" WIDE
MIN.) O/ NAILING FIN @ TOP OF
WINDOWS (HEAD) TYP. TWO

CONTINUOUS BEADS OF

MOISTOP SEALANT OR EQUAL
UNDER FLASHING PAPER (1) O/
NAILING FIN AND (1) AT TOP OF
FLSHING PAPER TYP.

FLASHING PAPER, SELF
SEALING MEMBRANE, (9" WIDE
MIN., 12" WIDE TYP. AT JAMBS)

O/ WOOD FRAMING AND UNDER

NAILING FIN AT SIDE OF
WINDOWS (JAMB) TYP.

WINDOW
NAILING FIN.
31 22
••••••••9" MOIST STOP FLASHING PAPER TYP. OF FLASHING PAPER

THE ACTUAL NUMBER OF FLASHING PIECES REQUIRED IS DETERMINED BY THE RADIUS OF THE OPENING AND THE SIZE OF THE FLASHING. (9" WIDE FLASHING MIN.) APPLY A CONTINUOUS BEAD OF SEALANT COMPLYING WITH AAMA 800 TO THE BACKSIDE (INTERIOR) OF THE WINDOW MOUNTING FLANGES

AT WINDOW HEAD, JAMBS AND SILL ALL CORROSIVE RESISTANT FASTENERS ARE TO BE NAILED THROUGH FIN NO CLOSER THAN 3" O.C. AND NOT MORE THAN 16" O.C.

FASTENERS SHALL BE WITHIN 10" FROM CORNERS.

NO NAILS SHALL BE BENT OVER THE NAILING FIN TO SECURE WINDOW REFER TO AAMA 2400-10 STANDARD PRACTICE FOR INSTALLATION OF WINDOWS WITH

MOUNTING FLANGES IN STUD CONSTRUCTION FOR ADDITIONAL REQUIREMENTS

PROVIDE SOLID BLOCKING AT ALL FLASHING LOCATIONS
NOTES:
# INDICATES SEQUENCE

FOR INSTALLATION

SHEET METAL FLASHING,

SOLDER ALL JOINTS OR

PROVIDE SELF ADHERING

WATERPROOFING
TYP.
4" LAP
1"
6" 6"
6 3/4"
1/2"

WATER RESISTIVE

BARRIER/ LATH PAPER UP

AND UNDER FLASHING
(6" LAP MIN).
* LOUVER SHALL PROVIDE MINIMUM 100 SQUARE INCHES FOR MAKEUP AIR (CMC 504.4.1) Sheet #
DCBA
1 2345
12345
SEAL
40810 COUNTY CENTER DRIVE
SUITE 200
TEMECULA, CA 92591
Project Number:

Date:

Scale:

Consultant

AS NOTED

WINDOW AND DOOR SCHEDULES & DETAILS
A-6.1
© Baker 2026
208026

CITY OF WILDOMAR - ACCESSORY DWELLING UNITS
02/27/2026
FINAL DESIGN - 02/27/2026

DOOR SCHEDULE
DOOR

NUMBER TYPE
SIZE
THICK. DOOR MATERIAL
FRAME

HEIGHT WIDTH MATERIAL U-FACTOR SHGC COMMENTS
1A 6' - 8" 3' - 0" 1 3/4" VINYL/ GLASS VINYL 0.300 0.23 EXTERIOR, REF GENERAL DOOR NOTE #7 2B 6' - 8" 3' - 0" 1 3/4" HOLLOW WD WD
3B 6' - 8" 3' - 0" 1 3/4" HOLLOW WD WD
4C 6' - 8" 2' - 6" 1 3/4" HOLLOW WD WD LOUVERED*
5C 6' - 8" 2' - 8" 1 3/4" HOLLOW WD WD LOUVERED*
6D 6' - 8" 5' - 0" 1 3/4" HOLLOW WD WD
7D 6' - 8" 5' - 0" 1 3/4" HOLLOW WD WD

WINDOW SCHEDULE

TYPE HEIGHT WIDTH
HEAD
HEIGHT
FRAME

MATERIAL OPERATION U-FACTOR SHGC COMMENTS
A 3' - 6" 3' - 0" 6' - 8" VINYL CASEMENT 0.300 0.23 B 1' - 6" 2' - 8" 6' - 8" VINYL AWNING 0.300 0.23

REVISIONS
NO. DATE DESCRIPTION
SCALE: 1/4" = 1'-0"

DOOR ELEVATIONS
SCALE: 1/4" = 1'-0"

WINDOW ELEVATIONS
SCALE: 3" = 1'-0"

WINDOW HEAD
1 SCALE: 3" = 1'-0"

DOOR HEAD
4 SCALE: 3" = 1'-0"

WINDOW JAMB
2 SCALE: 3" = 1'-0"

DOOR JAMB
5 SCALE: 3" = 1'-0"

WINDOW SILL
3 SCALE: 3" = 1'-0"

WINDOW SILL - CRAFTSMAN
6 SCALE: 3" = 1'-0"

DOOR THRESHOLD FLASHING
8 SCALE: 3" = 1'-0"

WINDOW FLASHING
9 SCALE: 3" = 1'-0"

WINDOW SILL FLASHING
7 313
MECHANICAL/PLUMBING NOTES EXHAUST DUCTS AND DRYER VENTS SHALL BE EQUIPPED WITH BACK DRAFT DAMPERS INSULATE ALL HOT WATER PIPES. CAL ENERGY CODE 150.0(j) (2), and CPC 609.11) SMOKE DETECTORS MUST BE PERMANENTLY WIRED. IN NEW CONSTRUCTION, REQUIRED SMOKE ALARMS SHALL RECEIVE THEIR PRIMARY POWER FROM THE BUILDING WIRING WHERE SUCH WIRING IS SERVED FROM A COMMERCIAL SOURCE AND SHALL BE EQUIPPED WITH A BATTERY BACK-UP. SMOKE ALARMS SHALL EMIT A SIGNAL WHEN THE BATTERIES ARE LOW. WIRING SHALL BE PERMANENT AND WITHOUT A DISCONNECTING SWITCH OTHER THAN AS REQUIRED FOR OVER CURRENT PROTECTION. WHERE WATER CLOSET COMPARTMENT IS INDEPENDENT OF THE BATHROOM OR SHOWER AREA, A FAN WILL BE REQ. IN EACH AREA. BATHROOMS SHALL HAVE AN EXHAUST FAN WITH HUMIDITY CONTROL SENSOR, MIN. 50 CFM CAPACITY. (CRC R303.3.1) THE MAX. AMOUNT OF WATER CLOSETS ON A 3" HORIZONTAL DRAINAGE SYSTEM LINE IS 5 (CPC TABLE 703.2) PROVIDE GAS LINES WITH A MN. CAPACITY OF 200,000BTU FOR WATER HEATER. (CAL ENERGY CODE 150.0(N)). WHERE WHOLE HOUSE FANS ARE USED IN BATHROOM AREAS, THE FAN MUST RUN CONTINUOUSLY AND SHALL NOT BE TIED TO HUMIDITY CONTROL SENSOR. (CAL GREEN 4.506.1) ROOMS CONTAINING BATHTUBS, SHOWERS, SPAS AND SIMILAR FIXTURES SHALL BE PROVIDED WITH AN EXHAUST FAN WITH HUMIDITY CONTROL SENSOR HAVING A MIN. CAPACITY OF 50 CFM DUCTED TO TERMINATE OUTSIDE THE BLDG. ( CRC R303.3, CAL GREEN 4.505.1, CBC 1203 .5.2.1, CMC 402.5 1. 2. 3. 4. 5. 6. 7. 8. 9. 11. 12. SUPPLY AND RETURN AIR DUCTS TO BE INSULATED AT A MIN. OF R-6. (CAL ENERGY CODE TABLE 150.1-A) ENVIRONMENTAL AIR DUCTS SHALL TERMINATE MIN. 3 FEET FROM PROPERTY LINE OR OPENINGS INTO BLDG., AND 10' FROM A FORCED AIR INLET. (CMC 502.2.1) ALL HOSE BIBS ARE TO HAVE VACUUM BREAKERS. (CPC603.5.7) THE MAX. AMOUNT OF WATER CLOSETS ON A 3" VERTICAL DRAINAGE LINE IS 5. (CPC TABLE 703.2) PROVIDE A CONDENSATE DRAIN NO MORE THAN 2" ABOVE THE BASE OF THE WATER HEATER SPACE. (CAL ENERGY CODE 150.0 (N). 10. ISOLATION VALVES ARE REQ. FOR TANKLESS WATER HEATERS ON THE HOT AND COLD SUPPLY LINES WITH HOSE BIBS ON EACH VALVE, TO FLUSH THE HEAT EXCHANGER. (CAL ENERGY CODE 110.3(7). 13. 14. 15. ALL EXHAUST FANS SHALL BE SWITCHED SEPARATELY FROM LIGHTING SYSTEMS. (CENC 150(K) 2B) PLUMBING FIXTURES AND FITTINGS INSTALLED IN RESIDENTIAL BUILDINGS SHALL COMPLY WITH THE PRESCRIPTIVE REQ. OF SECTIONS 4.303.1.1 THROUGH 4.303.1.4.4. PLUMBING FIXTURES AND FITTINGS REQ. IN SECTION 4.303.1 SHALL BE INSTALLED IN ACCORDANCE WITH THE CALIFORNIA PLUMBING CODE AND SHALL MEET THE THE APPLICABLE REFERENCE STANDARDS. 16. 17. 10. 11. 12. 13. 15. 17. WHERE MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE INSTALLED, THE SMOKE ALARMS SHALL BE INTERCONNECTED IN SUCH A MANNER THAT THE ACTIVATION OF ONE ALARM WILL ACTIVATE ALL THE ALARMS IN THE INDIVIDUAL DWELLING UNIT. THE ALARM SHALL BE CLEARLY AUDIBLE IN ALL BEDROOMS OVER BACKGROUND NOISE LEVELS WITH ALL INTERVENING DOORS CLOSED. ALL EXHAUST FANS SHALL BE SWITCHED SEPARATELY FROM LIGHTING SYSTEMS. (CENC 150(K) 2B) A MINIMUM OF ONE HIGH EFFICIENCY LUMINAIRE SHALL BE INSTALLED IN BATHROOM CONTROLLED BY AN OCCUPANT AND VACANCY SENSOR PROVIDING AUTOMATIC -OFF FUNCTIONALLY (CENC 150 .0(K)21) LAUNDRY AREA SHALL AT LEAST 1-20 AMP DEDICATED BRANCH CIRCUIT (CEC 210 .11 (C)(2) A DEDICATED 125V, 20AMP ELECTRICAL RECEPTACLE THAT IS CONNECTED TO THE ELECTRICAL PANEL WITH A 120 240 -VOLT 3 CONDUCTOR, 10 AWG COPPER BRANCH CIRCUIT, WITHIN 3 FEET FROM THE WATER HEATER AND ACCESSIBLE TO THE WATER HEATER WITH NO OBSTRUCTIONS (CENC 150.0(N)1A) ELECTRICAL RECEPTACLE OUTLETS IN BATHROOM MUST BE NO MORE THAN 48 INCHES OR LESS THAN 15-INCHES MEASURE FROM THE FINISHED FLOOR. DOORBELL BUTTON MUST BE INSTALLED NO MORE THAN 48 INCHES FROM EXTERIOR FLOOR. 18. 14. PROVIDE A DEDICATED CIRCUIT FOR THE A.C./FAU (CEC 422.12) LUMINAIRE EFFICACY - ALL INSTALLED LUMINAIRES SHALL MEET THE REQUIREMENTS OF 2022 BUILDING ENERGY EFFICIENCY STANDARDS TABLE 150.0-A PER SECTION 150.0(K). 19. (S) ENERGY STORAGE SYSTEMS (ESS) READY. ALL SINGLE-FAMILY RESIDENCES THAT INCLUDE ONE OR TWO DWELLING UNITS SHALL MEET THE FOLLOWING. ALL ELECTRICAL COMPONENTS SHALL BE INSTALLED IN ACCORDANCE WITH THE CALIFORNIA ELECTRICAL CODE: 1. AT LEAST ONE OF THE FOLLOWING SHALL BE PROVIDED: A. ESS READY INTERCONNECTION EQUIPMENT WITH A MINIMUM BACKED-UP CAPACITY OF 60 AMPS AND A MINIMUM OF FOUR ESS-SUPPLIED BRANCH CIRCUITS, OR B. A DEDICATED RACEWAY FROM THE MAIN SERVICE TO A PANELBOARD (SUBPANEL) THAT SUPPLIES THE BRANCH CIRCUITS IN SECTION 150.0(S)(2). ALL BRANCH CIRCUITS ARE PERMITTED TO BE SUPPLIED BY THE MAIN SERVICE PANEL PRIOR TO THE INSTALLATION OF AN ESS. THE TRADE SIZE OF THE RACEWAY SHALL BE NOT LESS THAN ONE INCH. THE PANELBOARD THAT SUPPLIES THE BRANCH CIRCUITS (SUBPANEL) MUST BE LABELED “SUBPANEL SHALL INCLUDE ALL BACKED-UP LOAD CIRCUITS.” 2. A MINIMUM OF FOUR BRANCH CIRCUITS SHALL BE IDENTIFIED AND HAVE THEIR SOURCE OF SUPPLY COLLOCATED AT A SINGLE PANELBOARD SUITABLE TO BE SUPPLIED BY THE ESS. AT LEAST ONE CIRCUIT SHALL SUPPLY THE REFRIGERATOR, ONE LIGHTING CIRCUIT SHALL BE LOCATED NEAR THE PRIMARY EGRESS, AND AT LEAST ONE CIRCUIT SHALL SUPPLY A SLEEPING ROOM RECEPTACLE OUTLET. 3. THE MAIN PANELBOARD SHALL HAVE A MINIMUM BUSBAR RATING OF 225 AMPS. 4. SUFFICIENT SPACE SHALL BE RESERVED TO ALLOW FUTURE INSTALLATION OF A SYSTEM ISOLATION EQUIPMENT/TRANSFER SWITCH WITHIN 3 FEET OF THE MAIN PANELBOARD. RACEWAYS SHALL BE INSTALLED BETWEEN THE PANELBOARD AND THE SYSTEM ISOLATION EQUIPMENT/TRANSFER SWITCH LOCATION TO ALLOW THE CONNECTION OF BACKUP POWER SOURCE. (U) ELECTRIC COOKTOP READY. SYSTEMS USING GAS OR PROPANE COOKTOP TO SERVE INDIVIDUAL DWELLING UNITS SHALL INCLUDE THE FOLLOWING: 1. A DEDICATED 240 VOLT BRANCH CIRCUIT WIRING SHALL BE INSTALLED WITHIN 3 FEET FROM THE COOKTOP AND ACCESSIBLE TO THE COOKTOP WITH NO OBSTRUCTIONS. THE BRANCH CIRCUIT CONDUCTORS SHALL BE RATED AT 50 AMPS MINIMUM. THE BLANK COVER SHALL BE IDENTIFIED AS “240V READY.” ALL ELECTRICAL COMPONENTS SHALL BE INSTALLED IN ACCORDANCE WITH THE CALIFORNIA ELECTRICAL CODE. 2. THE MAIN ELECTRICAL SERVICE PANEL SHALL HAVE A RESERVED SPACE TO ALLOW FOR THE INSTALLATION OF A DOUBLE POLE CIRCUIT BREAKER FOR A FUTURE ELECTRIC COOKTOP INSTALLATION. THE RESERVED SPACE SHALL BE PERMANENTLY MARKED AS “FOR FUTURE 240V USE.” (V) ELECTRIC CLOTHES DRYER READY. CLOTHES DRYER LOCATIONS WITH GAS OR PROPANE PLUMBING TO SERVE INDIVIDUAL DWELLING UNITS SHALL INCLUDE THE FOLLOWING: 1. A DEDICATED 240 VOLT BRANCH CIRCUIT WIRING SHALL BE INSTALLED WITHIN 3 FEET FROM THE CLOTHES DRYER LOCATION AND ACCESSIBLE TO THE CLOTHES DRYER LOCATION WITH NO OBSTRUCTIONS. THE BRANCH CIRCUIT CONDUCTORS SHALL BE RATED AT 30 AMPS MINIMUM. THE BLANK COVER SHALL BE IDENTIFIED AS “240V READY.” ALL ELECTRICAL COMPONENTS SHALL BE INSTALLED IN ACCORDANCE WITH THE CALIFORNIA ELECTRICAL CODE. 2. THE MAIN ELECTRICAL SERVICE PANEL SHALL HAVE A RESERVED SPACE TO ALLOW FOR THE INSTALLATION OF A DOUBLE POLE CIRCUIT BREAKER FOR A FUTURE ELECTRIC CLOTHES DRYER INSTALLATION. THE RESERVED SPACE SHALL BE PERMANENTLY MARKED AS “FOR FUTURE 240V USE.” (T) HEAT PUMP SPACE HEATER READY. SYSTEMS USING GAS OR PROPANE FURNACE TO SERVE INDIVIDUAL DWELLING UNITS SHALL INCLUDE THE FOLLOWING: 1. A DEDICATED 240 VOLT BRANCH CIRCUIT WIRING SHALL BE INSTALLED WITHIN 3 FEET FROM THE FURNACE AND ACCESSIBLE TO THE FURNACE WITH NO OBSTRUCTIONS. THE BRANCH CIRCUIT CONDUCTORS SHALL BE RATED AT 30 AMPS MINIMUM. THE BLANK COVER SHALL BE IDENTIFIED AS “240V READY.” ALL ELECTRICAL COMPONENTS SHALL BE INSTALLED IN ACCORDANCE WITH THE CALIFORNIA ELECTRICAL CODE. 2. THE MAIN ELECTRICAL SERVICE PANEL SHALL HAVE A RESERVED SPACE TO ALLOW FOR THE INSTALLATION OF A DOUBLE POLE CIRCUIT BREAKER FOR A FUTURE HEAT PUMP SPACE HEATER INSTALLATION. THE RESERVED SPACE SHALL BE PERMANENTLY MARKED AS “FOR FUTURE 240V USE.” ELECTRIC READY NOTES: 2022 ENERGY EFFICIENCY STANDARDS 150.0 PER CEC 2022 150.0(N).1.A.: IF THE DESIGNATED SPACE IS WITHIN 3 FEET FROM THE WATER HEATER, THEN THIS SPACE SHALL INCLUDE THE FOLLOWING:A DEDICATED 125 VOLT, 20 AMP ELECTRICAL RECEPTACLE THAT IS CONNECTED TO THE ELECTRIC PANEL WITH A 120/240 VOLT 3 CONDUCTOR, 10 AWG COPPER BRANCH CIRCUIT, WITHIN 3 FEET FROM THE WATER HEATER AND ACCESSIBLE TO THE WATER HEATER WITH NO OBSTRUCTIONS; AND · BOTH ENDS OF THE UNUSED CONDUCTOR SHALL BE LABELED WITH THE WORD "SPARE" AND BE ELECTRICALLY ISOLATED; AND· A RESERVED SINGLE POLE CIRCUIT BREAKER SPACE IN THE ELECTRICAL PANEL ADJACENT TO THE CIRCUIT BREAKER FOR THE BRANCH CIRCUIT IN A ABOVE AND LABELED WITH THE WORDS "FUTURE 240V USE"; AND· A CONDENSATE DRAIN THAT IS NO MORE THAN 2 INCHES HIGHER THAN THE BASE OF THE INSTALLED WATER HEATER, AND ALLOWS NATURAL DRAINING WITHOUT PUMP ASSISTANCE. 16. ELECTRICAL NOTES (CONT'D) ALL HOSE CONNECTIONS SHALL BE EQUIPPED WITH NON-REMOVABLE BACK FLOW PREVENTERS. [CPC 603.3.3] 18. ELECTRICAL NOTES 1. 2. 3. 4. 5. 6. 7. RECEPTACLE OUTLET LOCATIONS WILL COMPLY WITH CEC ARTICLE 210.52. & CRC SECTION R327.1.2. TAMPER RESISTANT RECEPTACLE OUTLET LOCATIONS SHALL COMPLY W/ NEC ART. 210-52 AND 550.13 (I.E. ALL RECEPTACLES IN A DWELLING). PER LIGHTING MEASURES 150(K)4 N T-24, THE BEDROOMS, HALLWAY, LIVING ROOM AND OFFICE ARE REQUIRED TO HAVE ANY INSTALLED FIXTURE TO BE ON A DIMMER SWITCH AND THE FIXTURE NEEDS TO BE HIGH EFFICACY. OUTDOOR LIGHTING FIXTURES ARE REQUIRED TO BE HIGH EFFICACY AND CONTROLLED BY A COMBINATION PHOTOCONTROL / MOTION SENSOR. ARC-FAULT PROTECTION FOR ALL OUTLETS (NOT JUST RECEPTACLES) LOCATED IN ROOMS DESCRIBED IN NEC 210.12(A): KITCHENS, LAUNDRY AREAS, FAMILY, LIVING, BEDROOMS, DINING, HALLS, ETC. ALL BRANCH CIRCUITS WILL BE ARC FAULT CIRCUIT PROTECTED PER NEC ART. 210-12(B). MINIMUM OF 2–20-AMP CIRCUITS ARE REQUIRED TO SERVE THE KITCHEN COUNTERTOP OUTLETS. THESE CIRCUITS MAY ALSO SERVE THE PANTRY, BREAKFAST ROOM, DINING ROOM OR OTHER SIMILAR AREAS (210.52(B)(1) CEC) BATHROOM CIRCUITING SHALL BE EITHER: a) A 20 AMPERE CIRCUIT DEDICATED TO EACH BATHROOM. b) AT LEAST ONE 20 AMPERE CIRCUIT SUPPLYING ONLY BATHROOM RECEPTACLE OUTLETS PER NEC ART. 210-11(c)3. ALL 125-VOLT, SINGLE-PHASE, 15- AND 20- AMPERE RECEPTACLES INSTALLED IN BATHROOMS, GARAGES, BASEMENTS, OUTDOORS, LAUNDRY AREA, KITCHEN DISHWASHERS, KITCHEN COUNTERS AND AT WET BAR SINKS, WITHIN 6' OF A SINK, SHALL BE GFCI PROTECTED PER NEC ART. 210-8(A). WEATHER RESISTANT TYPE FOR RECEPTACLES INSTALLED IN DAMP OR WET LOCATIONS (OUTSIDE) NEC 406.4(D)(6) 8. 9. SMOKE DETECTORS MUST BE PERMANENTLY WIRED. IN NEW CONSTRUCTION, REQUIRED SMOKE ALARMS SHALL RECEIVE THEIR PRIMARY POWER FROM THE BUILDING WIRING WHERE SUCH WIRING IS SERVED FROM A COMMERCIAL SOURCE AND SHALL BE EQUIPPED WITH A BATTERY BACK-UP. SMOKE ALARMS SHALL EMIT A SIGNAL WHEN THE BATTERIES ARE LOW. WIRING SHALL BE PERMANENT AND WITHOUT A DISCONNECTING SWITCH OTHER THAN AS REQUIRED FOR OVERCURRENT PROTECTION. A RECEPTACLE OUTLET MUST BE INSTALLED IN EVERY ROOM SO THAT NO POINT ALONG THE WALL SPACE IS MORE THAN 6 FEET, MEASURED HORIZONTALLY ALONG THE FLOOR LINE FROM A RECEPTACLE OUTLET CEC 210.52(A) gas service information: