AND SILL OPENING

EXTERIOR SHEATHING
STEP 2

PROVIDE MECHANICALLY

FASTENED CASAM

PREFABRICATED CORNERS

EXTERIOR SHEATHING
STEP 1
EXTERIOR MEMBRANE NOTES N.T.S.

GENERAL NOTES FOR WINDOW AND FLASHING CONDITIONS
A. COLD APPLIED SELF ADHERING(CASAM) MEMBRANE AND WATER RESISTANT BARRIER(WRB) TO BE INSTALLED PER C.B.C. REQUIREMENTS
B. COORDINATE AND SEQUENCE WITH OTHER TRADES FOR PROPER INSTALLATION AND OVERLAP OF S.M.

FLASHING, WATERPROOF MEMBRANE FLASHING AND WRB, WINDOW SEALANT, AND EXTERIOR FINISH MATERIALS TO FORM WATERTIGHT BARRIER.

C. METAL WINDOW FLASHING SHALL BE SET IN A CONTINUOUS BEAD OF SEALANT.

D. METAL WINDOW FLASHING SHALL BE SINGLE UNIT WITH FULLY SOLDERED WELDED SEAMS. IF UNIT MUST BE MORE THAN A SINGLE PIECE, THE SEAMS SHALL BE AT MIDDLE PORTION OF HEAD AND SILL. JOINTS SHALL NOT OCCUR AT INTERSECTIONS OR CORNERS.

E. WINDOW DETAILS HAVE BEEN PROVIDED FOR GENERAL REFERENCE ONLY. SEE SHOP DRAWINGS FOR MORE SPECIFIC, DETAILED AND ADDITIONAL INFORMATION. COORDINATE ALL TRADES WITH WINDOW SHOP DRAWINGS.

F. SIZE AND SHAPE OF FLASHING SHALL BE ADJUSTED AS REQD. TO PROVIDE A MIN. 4" FLANGE BEHIND EXTERIOR

PANEL ASSEMBLY, COLD APPLIED SELF ADHERING WATERPROOF MEMBRANE (CASAM), WRB, AND TO WORK WITH CURTAINWALL OR STOREFRONT MULLION AS APPLICABLE.

SILL FLASHING
A. SHALL HAVE A VERTICAL REAR LEG, SEALED AT END TERMINATION.

B. SHALL HAVE SEALED END DAMS ALL TERMINATIONS
C. SHALL BE SIZED TO ACCOMMODATE VERTICAL FLASHING, WATERPROOF MEMBRANE, AND WRB AT JAMBS D. ALL SPLICES MUST ALLOW FOR THERMAL AND DYNAMIC MOVEMENT AND BE SEALED IN ACCORDANCE WITH ASTM AND MANUFACTURERS REQUIREMENTS. THE SPLICE WILL HAVE A BRIDGE SEAL 1/4" THICK WITH A MIN. OF 1/4" BOND SURFACE TO BOTH SUBSTRATES. THE BRIDGE SEAL MUST NOT BE DISRUPTED WITH THREE SIDED ADHESION OR OTHER OBSTRUCTIONS.

E. ALL PENETRATIONS THROUGH THE SILL FLASHING MUST BE SEALED WATERTIGHT F. ALL ATTACHMENTS MUST ACCOMMODATE THERMAL AND DYNAMIC MOVEMENT G. ALL INTERRUPTIONS IN FLASHING MUST BE SEALED
H. GALV. SHEET METAL SILL FLASHING AND WATERPROOF MEMBRANE SILL FLASHING SHALL EXTEND BEYOND WINDOW FRAME JAMB AT ALL END CONDITIONS AND SHALL TURN UP 6" VERTICAL AT JAMB CONDITIONS.

VERTICAL JAMB AT SILL AND HEAD FLASHING AREAS
A. INSTALL VERTICAL WATERPROOF MEMBRANE FLASHING AT JAMB AND IT SHALL OVERLAP UPTURNED SILL

FLASHING
B. INSTALL WATERPROOF MEMBRANE FLASHING AT HEAD AND OVERLAP VERTICAL PIECES JAMB AND HEAD

FLASHING
C. VERTICAL JAMB FLASHING SHALL RUN CONTINUOUS WITHOUT SPLICE, BREAK OR INTERRUPTION TO EDGE OF SILL FLASHING. IT SHALL BE FULLY SOLDERED/SEALED TO SILL FLASHING, SEAL MUST BE WATERTIGHT AND

ALLOW FOR DYNAMIC AND THERMAL MOVEMENT
D. JAMB FLASHING SHALL MEET THE HEAD FLASHING BY BUTTING INTO THE BOTTOM EDGE. COMBINATION OF

BRIDGE SEAL (AT FACE) AND FILLET BEAD (AT RETURN) MUST OCCUR AT ALL INTERSECTIONS E. ALL FASTENER PENETRATIONS MUST BE SEALED WATERTIGHT
F. ATTACHMENTS MUST ALLOW FOR DYNAMIC AND THERMAL MOVEMENT G. HEAD SPLICES TO BE SEALED WITH BRIDGE SEAL, SEE SILL FLASHING NOTES H. ALL SPLICES MUST ALLOW FOR DYNAMIC AND THERMAL MOVEMENT AND BE SEALED IN ACCORDANCE WITH ASTM AND MANUFACTURERS REQUIREMENTS. THE SPLICE WILL HAVE A BRIDGE SEAL 1/4" THICK WITH A MIN. OF 1/4" BOND SURFACE TO BOTH SUBSTRATES. THE BRIDGE SEAL MUST NOT BE DISRUPTED WITH THREE SIDED ADHESION OR OTHER OBSTRUCTIONS.

PERIMETER SEALANT
A. EXTERIOR WINDOW PERIMETER SEALANT SHALL ALWAYS BE CONTINUOUS AND IN THE SAME PLANE B. INSTALLER SHALL TAKE CARE TO COMPLETE SEALS AROUND ALL BRIDGE AND FILLET BEADS USED TO SEAL

FLASHING
ALIGN
4"

INTERIOR EXTERIOR

GLAZING, TYP REFER TO SPECIFICATIONS

ALUMINUM STOREFRONT

WINDOW SYSTEM
SHIM
EXTERIOR SHEATHING PER STRUCT.

WOOD STUD FRAMING PER STRUCT.

INTERIOR GYPSUM BOARD, FRAMING AND BATT INSULATION.

SEE WALL AND FINISH SCHEDULES FOR TYPE AND FINISH
RIGID INSULATION W/TAPED SEAMS PER T24

INTERLOCKING BRAKE SHAPE ALUMINUM

SILL WITH END DAMS, SLOPE TO DRAIN
12" WIDE CONT. STRIP CASAM FLASHING;
APPLY OVER SHEATHING & UNDER WRB, TYP.
2 LAYERS OF WATER RESISTIVE BARRIER
1/2":12" SLOPE
1/2":12" SLOPE

DRIP EDGE
CMU
1" MIN AIR GAP

SILL FLASHING CUT

INTO CMU WALL
BEYOND

BACKER ROD & SEALANT AT BRAKE METAL TO CMU

CONNECTION BEYOND, SEE JAMB DETAIL

CMU BEYOND

STOREFRONT WINDOW SILL

AT CMU BLOCK
3"=1'-0"

STOREFRONT WINDOW JAMB

AT CMU WALL
3" = 1'-0"

CMU WALL
2 LAYERS WATER RESISTANT BARRIER (WRB), TYP.;

LAP WRB OVER CASAM

RIGID INSULATION W/TAPED SEAMS
1/4" MIN. BACKER ROD & SEALANT, TYP. BOTH SIDES

ALUMINUM STOREFRONT SYSTEM, SHIM AS REQUIRED
ALIGN
GYP. BOARD CASING BEAD
12" WIDE CONT. STRIP CASAM FLASHING; APPLY OVER
SHEATHING & UNDER WRB, TYP.

GLAZING, TYP.; REFER TO SPECIFICATIONS
EXTERIOR SHEATHING PER STRUCT.

ALUMINUM BRAKE METAL CORNER FLASHING, TYP.; FINISH

TO MATCH STOREFRONT SYSTEM
WOOD STUD FRAMING PER STRUCT.

INTERIOR GYPSUM BOARD, FRAMING AND BATT
INSULATION. SEE WALL AND FINISH SCHEDULES

FOR TYPE AND FINISH INTERIOR

EXTERIOR

BRAKE METAL SILL BEYOND
1" MIN AIR GAP

BACKER ROD & SEALANT

SILL FLASHING CUT INTO CMU WALL & SET IN SEALANT

STEP IN SILL FLASHING BELOW, SEE SILL DETAIL

STOREFRONT WINDOW JAMB

AT METAL SIDING - MAIN ENTRY
METAL SIDING, FASTEN PER MFGR., TYP.
2 LAYERS WATER RESISTANT BARRIER (WRB), TYP.;

LAP WRB OVER CASAM

RIGID INSULATION
JAMB TRIM BY METAL SIDING MFGR.
1/4" MIN. BACKER ROD & SEALANT, TYP. BOTH SIDES

ALUMINUM STOREFRONT SYSTEM, SHIM AS REQUIRED
12" WIDE CONT. STRIP CASAM FLASHING; APPLY OVER
SHEATHING & UNDER WRB, TYP.

GLAZING, TYP.; REFER TO SPECIFICATIONS
EXTERIOR SHEATHING PER STRUCT.

ALUMINUM BRAKE METAL CORNER
FLASHING, TYP.; FINISH TO MATCH

METAL WALL PANELS
WOOD STUD FRAMING PER STRUCT.

INTERIOR GYPSUM BOARD, FRAMING AND BATT
INSULATION. SEE WALL AND FINISH SCHEDULES

FOR TYPE AND FINISH

INTERIOR EXTERIOR
ALIGN
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
7/3/2024 12:48:27 PM C:\Users\kaleksandrov\OneDrive - Williams & Paddon\Documents\210015.01_CITY OF ROSEVILLE_DCWWTP ADMIN BLDG_A22_kaleksandrov4T455.rvt A-710

EXTERIOR

STOREFRONT

DETAILS

DCWWTP OPERATIONS

AND LAB BLDG
May 29, 2024
19six 210015.01
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
311 VERNON ST
ROSEVILLE, CA 95768
90% CD - PERMIT SET
16 14
1 2
3 5
12 8 4
7 6
22 10
11 9
15 17
19 24
23 13
NO. DATE DESCRIPTION
2/28/25

BID SET (PRELIMINARY)
1/8"
3/8" CLEAR TEMPERED GLAZING
CLEAR SILICONE JOINT, TYP.

RECESSED ALUM. CHANNEL

BUTT JOINT

AT INTERIOR GLAZING
3" = 1'-0"

FULLY WELDED HOLLOW

METAL FRAME

STUD ANCHOR

TYPICAL DOOR FRAME PROFILE AT WOOD STUD FRAMING

FULLY WELDED HOLLOW

METAL FRAME

FRAME ANCHOR

TYPICAL DOOR FRAME PROFILE AT CONCRETE MASONRY

DRIP AT HEAD CONDITIONS

EXTERIOR DOOR

HOLLOW METAL HEAD / JAMB FRAME
3"=1'-0"
127/128"
2"
1"
5/8" 2"
VARIES1 129/256" 3"
127/128" 1 127/256"
2"
VARIES1 129/256" 3"
2" 2" 5/8"

EXTERIOR HOLLOW METAL DOOR

HEAD AT METAL SIDING
3" = 1'-0"
EXTERIOR SHEATHING PER STRUCT.

INTERIOR GYPSUM BOARD, FRAMING AND
BATT INSULATION. SEE WALL AND FINISH

SCHEDULES FOR TYPE AND FINISH

RIGID INSULATION
HEADER PER STRUCT.
2 LAYERS WATER RESISTANT BARRIER
(WRB), TYP.; WRB SHALL EXTEND
OVER FLANGE OF 'Z' FLASHING, TYP.

METAL SIDING, FASTEN PER MFGR., TYP.

HOLLOW METAL DOOR FRAME, TYP.

HOLLOW METAL DOOR, TYP.

RAIN DRIP, TYP.

COLD APPLIED SELF-ADHERING MEMBRANE
(CASAM) FLASHING; WRAP OPENING, TYP.

TAPE SEALANT BY METAL SIDING MFGR., TYP.

FASTENER PER METAL SIDING MFGR., TYP.

METAL SIDING CLOSURE, TYP.

DRIP/SILL FLASHING BY METAL SIDING MFGR.,
TYP.

EXTERIOR HOLLOW METAL DOOR

THRESHOLD AT CONCRETE
3" = 1'-0"
HOLLOW METAL DOOR; REFER TO

DOOR SCHEDULE

HOLLOW METAL DOOR FRAME
BEYOND, TYP.

CONCRETE FLATWORK, TYP.

AGGREGATE BASE, TYP.

CONCRETE SLAB, TYP.

EXPANSION JOINT
DOOR SWEEP, TYP.; REFER TO DOOR

HARDWARE SPECIFICATIONS
OFFSET SADDLE THRESHOLD, TYP.;

REFER TO DOOR HARDWARE

SPECIFICATIONS
SLOPE: 1.8% MAX.

NOTE: ALL HOLLOW METAL DOORS AND
FRAMES SHALL BE PAINTED; COLOR TO
MATCH ADJACENT WALL SURFACE, U.N.O.

MAX.
1/4"
MAX.
1/4"
MAX.
1/2"

KNOCK DOWN DOORS AND WINDOWS

HEAD, JAMB, AND SILL AT METAL STUD WALLS
3" = 1'-0"
3/8" 1 15/16" VARIES 1 15/16" 3/8"

MULLION

HEAD / JAMB
SILL
3/8" 1 15/16" VARIES 1 15/16" 3/8"
3/8" 1 15/16" VARIES 1 15/16" 3/8"

SNAP ON ALUMINUM CASING
(TA-23 U.O.N.)

SNAP ON ALUMINUM CASING
(TA-23 U.O.N.)
BOX HEADER AT 48" WIDE AND WIDER
OPENING AND AT ALL FULL HEIGHT WALLS.
(ALTERNATE HEADER AT ALL OTHER

LOCATIONS)

GYPSUM BOARD, TYPICAL

METAL STUD FRAMING, TYPICAL

FASTEN PER MANUFACTURER'S

INSTRUCTIONS, TYPICAL

KNOCK DOWN FRAME

DOOR, REFER TO DOOR

SCHEDULE

CEILING WHERE OCCURS
TRACK
STUD
ALTERNATE BUILTUP HEADER AT
OPENINGS <48" IN

NON-RATED WALLS
DIM. PT.

DR. OPNG.

DIM. PT.

DR. OPNG.

GYPSUM BOARD, TYP.
1"x3"x18 GA. PLATE AT 24" O.C. SECURED WITH
(2) #10 SMS AT EA STUD SIDE OF WALL
METAL STUD FRAMING, TYP.

KNOCK DOWN FRAME

DOOR, REFER TO DOOR SCHEDULE

FASTEN PER MANUFACTURER'S INSTRUCTION,

TYPICAL

KNOCK DOWN FRAME
A
GENERAL NOTES:

1. PROVIDE RATED FRAME ASSEMBLY WITH FIRE SEAL WHERE NOTED ON DOOR SCHEDULE.

2. INSTALL DOOR FRAMES WITH FRAME MANUFACTURER'S CLOSER REINFORCING FOR

SPECIFIED CLOSER TYPE

FILL SPACE WITH INSULATION

AT DOORS LISTED W/ STC RATING
2"
1/4" 1 1/2" 1/4"
1 3/4"
1 1/2" 1/4"
1 3/4"
1 1/2" 1/4"

KNOCK DOWN DOOR HEAD
B

KNOCK DOWN DOOR JAMB
C

WALL, WHERE OCCURS
MIN.
3"
GLAZING; REFER TO WINDOW SCHEDULE. PLACE
GLAZING ON SECURED SIDE OF WINDOW/WALL U.O.N.

GLAZING STOP, TYPICAL

SEALANT & NEOPRENE GASKET,

EACH SIDE

KNOCK DOWN FRAME

DOOR, REFER TO DOOR SCHEDULE

KNOCK DOWN DOOR HEAD AT TRANSOM WINDOW
(KNOCK DOWN DOOR JAMB AT SIDELIGHT SIM.)
D
SEALANT & NEOPRENE GASKET, TYP. EACH SIDE.

BOX HEADER AT 48" WIDE AND WIDER
OPENING AND AT ALL FULL HEIGHT WALLS.
(ALTERNATE HEADER AT ALL OTHER

LOCATIONS)

FASTEN PER MANUFACTURER'S

INSTRUCTIONS, TYPICAL

KNOCK DOWN FRAME
GLAZING; REFER TO WINDOW SCHEDULE. PLACE GLAZING
ON SECURED SIDE OF WINDOW/WALL U.O.N.

TRACK
STUD

ALTERNATE BUILT-UP

HEADER AT OPENINGS
<48" IN NON-RATED
WALLS
DIM. PT.

WDW OPNG.

KNOCK DOWN WINDOW HEAD
F

KNOCK DOWN WINDOW JAMB
KNOCK DOWN WINDOW RAISED SILL, SIM.

G

FRICTION FIT BATT INSULATION, TYPICAL

GYPSUM BOARD, TYPICAL

METAL STUD FRAMING, TYPICAL

FRICTION FIT BATT INSULATION, TYPICAL
GLAZING STOP, TYP.

GLAZING; REFER TO WINDOW SCHEDULE. PLACE
GLAZING ON SECURED SIDE OF WINDOW/WALL U.O.N.

GLAZING STOP, TYPICAL

SEALANT & NEOPRENE GASKET,

EACH SIDE

KNOCK DOWN FRAME

KNOCK DOWN WINDOW MULLION
E

CEILING, WHERE OCCURS

WINDOW MANUFACTURER'S FLOOR CHANNEL SECURED

TO FLOOR & SET IN MASTIC, TYPICAL

FINISH FLOOR TO END UNDERNEATH KNOCK DOWN

FRAME TRIM, TYPICAL

CONCRETE SLAB OR CONCRETE FILLED

METAL DECK
POWER ACTIVATED FASTENER AT 16" O.C.

STAGGERED, TYP.; RAMSET OR EQUAL
GLAZING; REFER TO WINDOW SCHEDULE. PLACE
GLAZING ON SECURED SIDE OF WINDOW/WALL U.O.N.

GLAZING STOP, TYPICAL
SEALANT & NEOPRENE GASKET, TYP. EACH SIDE

KNOCK DOWN FRAME
H

KNOCK DOWN WINDOW SILL

FASTEN PER MANUFACTURER'S INSTRUCTION, TYPICAL
FRICTION FIT BATT INSULATION, TYP.

FRICTION FIT BATT INSULATION, TYP.
1"x3"x18 GA. PLATE AT 24" O.C. SECURED WITH
(2) #10 SMS AT EA STUD SIDE OF WALL
METAL STUD FRAMING, TYP.

KNOCK DOWN FRAME

FASTEN PER MANUFACTURER'S INSTRUCTION,

TYPICAL

FILL SPACE WITH INSULATION

AT WINDOWS LISTED W/ STC RATING
GYPSUM BOARD, TYP.

DIM. PT.

WDW. OPNG.

MIN.
3"

GLAZING STOP
GLAZING; REFER TO WINDOW SCHEDULE.

PLACE GLAZING ON SECURED SIDE OF
WINDOW/WALL U.O.N.

SEALANT & NEOPRENE GASKET, TYP. EACH
SIDE

THRESHOLD

CARPET TO SEALED CONCRETE
3"-1'-0"
3/8" U.N.O.

DOOR, WHERE OCCURS,

SEE SCHEDULE
CARPET

SCHLUTER RENO-U COLOR
TBD

SEALED/POLISHED CONCRETE

CHANGE OF FLOORING

UNDER CENTERLINE OF
DOOR

DOOR FRAME

CONCRETE SLAB

THRESHOLD

CARPET TO RESILIENT FLOORING
3"=1'-0"
3/8" U.N.O.

DOOR, WHERE OCCURS,

SEE SCHEDULE

DOOR FRAME
CARPET

SCHLUTER THRESHOLD, COLOR

SATIN COPPER ANODIZED
ALUMINUM (AK) MAX 1/4" HGT.

SHEET VINYL OR LVT

CONCRETE SLAB

THRESHOLD

THIN SET TILE TO SEALED CONCRETE
3"=1'-0"

DOOR, WHERE OCCURS,

SEE SCHEDULE

DOOR FRAME

THIN SET TILE OR

MORTAR SET STONE

SCHLUTER THRESHOLD, COLOR

SATIN COPPER ANODIZED
ALUMINUM (AK) MAX 1/4" HGT.

SEALED/POLISHED CONCRETE

CONCRETE SLAB
3/8" U.N.O.
6 6
7 3
4 4
5 MECHANICALLY FASTEN IN CORNERS THROUGH
CASAM
NOTES:

A. INSTALL IN ORDER AS SHOWN BY NUMBERS.

B. LEAVE RELEASE PAPER ON LOWER HALF OF SILL FLASHING. ADHERE OVER BUILDING PAPER (WRB) ONCE INSTALLED.

CASAM, TYP.

DO NOT FLASH OVER

BOTTOM OF NAIL
FLANGE

SILL PLATE

EXTERIOR

SHEATHING

NAIL FIN WINDOW SET IN BED

OF SEALANT PER MFR REQ'S

OPENING IN
WALL

MEMBRANE CORNER

PATCH PER
1 2
3 EXTERIOR SHEATHING
CASAM, EXTEND 1/2" ONTO FACE OF
SHEATHING AND 1" ONTO JAMB AND

SILL OPENING
STEP 1 & 2
STEP 3
CASAM PER STEP 3 THROUGH 7

PREFABRICATED CORNER CASAM,
MECH. FASTEN AT CORNERS
STEP 3 THROUGH 7

MEMBRANE FLASHING AT EXTERIOR NAIL FIN WINDOWS

COLD APPLIED, SELF ADHERING MEMBRANE (CASAM)
NTS
wp1.1

EXTERIOR

INTERIOR
12" WIDE CONT. STRIP OF CASAM FLASHING

LAPPED UNDER WINDOW FRAME

NAILFIN WINDOW

EXTERIOR

INTERIOR

RIGID INSULLATION

WATER RESISTANT BARRIER

UNDERLAYMENT EXTEND UNDER
WINDOW SYSTEM.

EXTERIOR PLYWOOD SHEATHING, TYP.

INSTALL 6" CONT. STRIP OF CASAM
OVER T.O. FLANGE & W.R.B.

UNDERLAYMENT, TYP. @ TRIM FLANGES
12" WIDE CONT. STRIP OF CASAM

FLASHING LAPPED UNDER WINDOW
FRAME

NAILFIN WINDOW
INSTALL 6" CONT. STRIP OF CASAM OVER
T.O. FLANGE & W.R.B. UNDERLAYMENT, TYP.
@ TRIM FLANGES
12" WIDE CONT. STRIP OF CASAM FLASHING

LAPPED UNDER WINDOW FRAME

NAILFIN WINDOW
GYP. BD. EXTERIOR
GYP. BD.

METAL SIDING, FASTEN PER MFGR., TYP.

EXTERIOR SHEATHING PER STRUCT.

METAL SIDING, FASTEN PER MFGR., TYP.
2 LAYERS WATER RESISTANT BARRIER (WRB),
TYP.; LAP WRB OVER CASAM

RIGID INSULATION
2 LAYERS WATER RESISTANT BARRIER (WRB),
TYP.; LAP WRB OVER CASAM & FLANGE OF

SILL / HEAD TRIM
6" WIDE CONT. STRIP CASAM FLASHING; APPLY

OVER SHEATHING & BRAKE METAL CORNER

FLASHING
EXTERIOR SHEATHING PER STRUCT.

INTERIOR GYPSUM BOARD, FRAMING AND BATT
INSULATION. SEE WALL AND FINISH SCHEDULES

FOR TYPE AND FINISH
METAL SIDING, FASTEN PER MFGR., TYP.

SILL / HEAD TRIM BY METAL SIDING MFGR., TYP.

TAPE SEALANT BY METAL SIDING MFGR., TYP.

FASTENER PER METAL SIDING MFGR., TYP.

METAL SIDING CLOSURE, TYP.

RIGID INSULATION
WINDOW

AT METAL SIDING
3" = 1'-0"

EXTERIOR HOLLOW METAL DOOR

JAMB AT METAL SIDING
3" = 1'-0"

WALL TYPE AND

WALL SCHEDULE

WALL ASSEMBLY PER
WOOD STUD FRAMING PER STRUCT.

HOLLOW METAL DOOR
FRAME, TYP.

INTERIOR GYPSUM BOARD, TYP.

EXTERIOR SHEATHING PER STRUCT.
2 LAYERS WATER RESISTANT BARRIER (WRB), TYP.;
WRB SHALL EXTEND OVER DOOR FRAME FLANGE, TYP.

HOLLOW METAL DOOR, TYP.

COLD APPLIED SELF-ADHERING MEMBRANE
(CASAM) FLASHING; WRAP OPENING, TYP.

METAL SIDING, FASTEN PER MFGR., TYP.

JAMB TRIM BY METAL SIDING MFGR., TYP.
1/4" MIN. BACKER ROD & SEALANT JOINT, TYP.

RIGID INSULATION

STOREFRONT WINDOW HEAD

AT STONE VENEER
3" = 1'-0"
ALIGN
1/4" MIN. BACKER ROD & SEALANT, TYP. BOTH SIDES

ALUMINUM STOREFRONT SYSTEM, SHIM AS

REQUIRED
2 LAYERS WATER RESISTANT BARRIER (WRB), TYP.;

LAP WRB OVER CASAM & FLANGE OF SILL / HEAD
TRIM
6" WIDE CONT. STRIP CASAM FLASHING; APPLY OVER

SHEATHING & BRAKE METAL CORNER FLASHING
EXTERIOR SHEATHING PER STRUCT.

HEADER PER STRUCT.

INTERIOR GYPSUM BOARD, FRAMING AND BATT
INSULATION. SEE WALL AND FINISH SCHEDULES

FOR TYPE AND FINISH
VENEER SIDING OVER 1/2" LATH AND

CEMENT PLASTER SCRATCH COAT
4" X 4" ALUMINUM BRAKE METAL CORNER FLASHING,
TYP.; FINISH TO MATCH STOREFRONT SYSTEM
GYP. BOARD CASING BEAD
GLAZING, TYP.; REFER TO SPECIFICATIONS

SILL / HEAD TRIM

RIGID INSULATION

INTERIOR EXTERIOR

STOREFRONT WINDOW JAMB

AT METAL SIDING
3"=1'-0"

ALUMINUM STOREFRONT
SYSTEM, TYP.

SHIM AS REQUIRED

EXTERIOR

INTERIOR
1/4" MIN. BACKER ROD &
SEALANT, TYP. BOTH SIDES
EXTERIOR SHEATHING PER STRUCT.

WOOD STUD FRAMING PER STRUCT.

INTERIOR GYPSUM BOARD,

FRAMING AND BATT
INSULATION. SEE WALL AND

FINISH SCHEDULES

FOR TYPE AND FINISH
METAL SIDING, FASTEN PER MFGR., TYP.
2 LAYERS WATER RESISTANT BARRIER (WRB),
TYP.

RIGID INSULATION
JAMB TRIM BY METAL SIDING MFGR.

GYP. BOARD CASING BEAD
BACKER ROD & SEALANT, TYP.
.125" ALUMINUM BRAKE METAL -

FINISH TO MATCH STOREFRONT

STOREFRONT DOOR JAMB

AT METAL SIDING
3"=1'-0"

ALUMINUM STOREFRONT
SYSTEM, TYP.

SHIM AS REQUIRED

EXTERIOR

INTERIOR
1/4" MIN. BACKER ROD &
SEALANT, TYP. BOTH SIDES
EXTERIOR SHEATHING PER STRUCT.

WOOD STUD FRAMING PER STRUCT.

INTERIOR GYPSUM BOARD,

FRAMING AND BATT
INSULATION. SEE WALL AND

FINISH SCHEDULES

FOR TYPE AND FINISH
METAL SIDING, FASTEN PER MFGR., TYP.
2 LAYERS WATER RESISTANT BARRIER (WRB),
TYP.

RIGID INSULATION
JAMB TRIM BY METAL SIDING MFGR.

GYP. BOARD CASING BEAD
BACKER ROD & SEALANT, TYP.

STOREFRONT DOOR, REFER

TO DOOR SCHEDULE
.125" ALUMINUM BRAKE METAL -

FINISH TO MATCH STOREFRONT
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
7/3/2024 12:48:30 PM C:\Users\kaleksandrov\OneDrive - Williams & Paddon\Documents\210015.01_CITY OF ROSEVILLE_DCWWTP ADMIN BLDG_A22_kaleksandrov4T455.rvt A-711

DOOR AND

WINDOW DETAILS

DCWWTP OPERATIONS

AND LAB BLDG
May 29, 2024
19six 210015.01
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
311 VERNON ST
ROSEVILLE, CA 95768
90% CD - PERMIT SET
9 12
10 11
8 14
15 16
21 24
13 18
19 20
NO. DATE DESCRIPTION
2/28/25

BID SET (PRELIMINARY)

KNOCK DOWN DOOR

HEAD AT WOOD STUD WALL
3" = 1'-0"
WOOD STUD FRAMING, TYP.

GYPSUM BOARD, TYPICAL
WOOD HEADER, TYP.; REFER TO CHART BELOW U.N.O. ON
STRUCT. DWGS.

FASTEN PER MANUFACTURER'S

INSTRUCTIONS, TYPICAL
KNOCK DOWN FRAME PER DETAIL 8A/A-711

DOOR, REFER TO DOOR

SCHEDULE

CEILING WHERE OCCURS
DIM. PT.

DR. OPNG.

FRICTION FIT BATT INSULATION, TYPICAL

OPENING WIDTH NON-BEARING WALL
UP TO 4'-0" 6" DEEP X FULL WIDTH OF WALL
4'-1" TO 6'-0" 8" DEEP X FULL WIDTH OF WALL
6'-1" TO 8'-0" 10" DEEP X FULL WIDTH OF WALL
8'-1" TO 10'-0" 12" DEEP X FULL WIDTH OF WALL
>10'-0" REFER TO STRUCT. DWGS.

KNOCK DOWN DOOR

JAMB AT WOOD STUD WALL
3" = 1'-0"
DIM. PT.

DR. OPNG.

GYPSUM BOARD, TYP.

KNOCK DOWN FRAME PER DETAIL 8A/A-711

FASTEN PER MANUFACTURER'S INSTRUCTION,

TYPICAL

FILL SPACE WITH INSULATION

AT DOORS LISTED W/ STC RATING

WALL, WHERE OCCURS
MIN.
3"
WOOD STUD FRAMING, TYP.

FRICTION FIT BATT INSULATION, TYP.

DOOR, REFER TO DOOR SCHEDULE
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP
REVISIONS #

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
7/3/2024 12:48:31 PM C:\Users\kaleksandrov\OneDrive - Williams & Paddon\Documents\210015.01_CITY OF ROSEVILLE_DCWWTP ADMIN BLDG_A22_kaleksandrov4T455.rvt A-712

DOOR AND

WINDOW DETAILS

DCWWTP OPERATIONS

AND LAB BLDG
May 29, 2024
19six 210015.01
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
311 VERNON ST
ROSEVILLE, CA 95768
90% CD - PERMIT SET
12 NO. DATE DESCRIPTION
2/28/25

BID SET (PRELIMINARY)

SECTION A-A
SCALE 1 : 1

CEILING JOIST

TUBE SCREW

BOTTOM TUBE ANGLE
ADAPTER 0-30 °

EXTENSION TUBE

TOP TUBE ANGLE
ADAPTER 0-30 °

EXPANSION JOINT SEAL

ROOF ASSEMBLY

CURB ASSEMBLY

LIGHT TRACKER

REFLECTOR
DOME

SHOCK INNER DOME
(OPTIONAL)

DOME RING

DOME RING SEAL
SPACER

FASTENER

SEALANT

ROOFING

MATERIAL

FASTENER

DOME EDGE PROTECTION

BAND (OPTIONAL)

FLASHING

CEILING RING

FASTENING CLAMP

FASTENER

DRESS RING DIFFUSER

DRESS RING SEAL

CEILING RING SEAL

NATURAL EFFECT

LENS CEILING
SEAL
SEAL
402
∅ 15 7/8"
207
8 1/8"
51 2"
102
4"
16 11/16 [424]
∅13 [331]
35/64 [14]
[686]
27"

MINIMUM INSIDE

DIMENSION
204
8"
MIN.

B
C
4 [102]
TYP.
27 3/8 [695]
27 3/8 [695]
4 [102]
TYP.

DETAIL B
SCALE: NTS

DETAIL C
SCALE: NTS

TOP VIEW
SOLATUBE 290 DS
(14 IN / 350 MM)

CURB FLASHING-PITCHED ROOF

HARD CEILING
NOTES:

1. STRUCTURAL ELEMENTS (PLYWOOD, RAFTERS, DRYWALL ETC.) BY OTHERS & SHOWN FOR REFERENCE ONLY.

2. ALL TUBE JOINTS & SEAMS TAPED WITH 2" FOIL TAPE (NOT SHOWN).

3. DIMENSIONS IN BRACKETS ARE METRIC UNLESS OTHERWISE SPECIFIED.

4. 6" MIN. CLEARANCE SHOULD BE MAINTAINED FROM ALL SOLATUBE COMPONENTS AND OTHER PLENUM COMPONENTS.

GALV. SHT. MTL. EXPANSION JOINT
COVER

CONTINUOUS CLEAT

RIVET AND SOLDER
GALV. SHT. MTL. GUTTER

W/SEALED INTERIOR

GUTTER MUST LAP (NO

FASTENERS)
ENDS

SECTION

GUTTER STRAP

GUTTER STRAP
16 GA. x 2" WIDE GUTTER BRACKET AT
ENDS
1 1/4"
1 1/4"
3/8"

GUTTER EXPANSION JOINT

LAP TYPE

NTS GUTTER

PROFILE
3" = 1' - 0"
4" TYP.
1/2" 3"
3/4"
3"
8" TYP.

SEE ROOF CALCS
12" AT TOP AND ABOVE GRADE
1/2"
NOTE:

FOR GUTTER EXPANSION

JOINT DETAIL SEE
2x3 DOWNSPOUT PER ROOF

PLAN W/ STRAPS TO
SUBSTRATE @ 36" O.C. MAX.

TYPICAL AND EQUALLY SPACE
GUTTER STRAP @ 36" O.C
MAX TYPICAL AND 6" FROM ENDS

AT DIRECTION CHANGES

GUTTER FINISH AND COLOR

TO MATCH METAL ROOF,

ALLOW FOR EXPANSION AND

CONTRACTION PER CDA

STANDARDS
2" TALL FLOW DAM, TYPICAL

AT EACH DOWNSPOUT

ON LOW SIDE OF OUTLET
16 GA. x 2" WIDE GUTTER
BRACKET AT 36" O.C.

STRAINER

GUTTER OUTLET
8 A-720

SEE ROOF CALCS

METAL ROOF ASSEMBLY O/RIGID

INSULATION O/WRB
POP RIVETS PER MANUF. REQ.

ROOF UNDERLAYMENT WRB,
LAP O/ FASCIA 3"
ROOF FRAMING PER STRUCT.
2x12 WOOD FASCIA

BUTYL TAPE

HIGH EAVE

METAL ROOFING
3" = 1'-0"

CLEAT PER MANUFACTURER

FLASHING PER ROOFING
MANUFACTURER. FINISH TO

MATCH ROOFING MATERIAL

PANEL CLIP
'Z' CLOSURE PER ROOFING

MANUFACTURER

BUTYL SEALANT
ROOF SHEATHING PER STRUCT.

BLOCKING @ RIGID INSULATION,

WHERE OCCURS
RIGID INSULATION PER T24,

WHERE OCCURS
METAL SOFFIT, FASTEN PER MFGR., TYP.

BRAKE METAL FASCIA WRAP,

MATCH ROOF FINISH

CONTINUOUS SOFFIT VENT

LINE OF RAFTER TAILS BEYOND

BLOCKING WHERE REQUIRED

SEALANT TO INSIDE BOOT

AT CONTACT TO PIPE PRIOR

TO CLOSURE OF DRAW BAND,

TYPICAL

PIPE PENETRATION

METAL ROOFING
1 1/2" = 1'-0"

DRAW BAND, TYPICAL

MEMBRANE COLLAR

FLASHING TP PIPE PRIOR

TO BOOT INSTALLATION
NOTES:

1. ROOFING CONTRACTOR TO MAKE

ALL PENETRATIONS

2. AT HIGH TEMPERATURE PIPE

PENETRATIONS USE SILICONE BOOT,

TYPICAL
MIN.
1"
ROOF
PANEL

MEMBRANE

FLASHING
PIPE

RUBBER BOOT FLASHING TO
ROOF PANEL W/#12X3/4" TEK

SCREWS W/NEOPRENE
WASHERS @ 4" O/C ALL AROUND

SET IN SEALANT BED, TYPICAL

SEALANT TO TOP OF

BOOT AFTER CLOSURE,

TYPICAL

ROOF ASSEMBLY PER ROOF PLAN

AND STRUCTURAL DRAWINGS

RIDGE CAP

ROOF UNDERLAYMENT WRB
ROOF FRAMING PER STRUCT.

ROOF SHEATHING PER STRUCT.

EAVE PLATE BY ROOFING MFR.

DOUBLE BEAD TAPE SEALANT, TYP.
#12 x 1" SD
#10 x 1" PHW, 12" O.C.

CLIP W/ 2-#10 x 1" PHW

Z-CLOSURE

END DAM
1/4"-14 x 7/8" STITCH XL, 3 PER PANEL

METAL ROOFING PANEL

RIDGE CAP

METAL ROOFING
1 1/2" = 1'-0"
RIGID INSULATION PER T24

BLOCKING

RIDGE VENTING

METAL ROOFING
1 1/2" = 1'-0"

METAL ROOF ASSEMBLY O/RIGID

INSULATION O/WRB
ROOF FRAMING PER STRUCT.

RIDGE CAP
ROOF SHEATHING PER STRUCT.
1 1/2" 1 1/2"

CONTINUOUS RIDGE BLOCKING

CONTINUOUS FLAT BLOCKING
WITH E.N., TYP.

VULCAN VENT, VENT SHALL BE

FLAME AND EMBER RESISTANT

LISTED COMPLYING WITH ASTM
E2886 OR CAL FIRE SFM12-7A
RIGID INSULATION PER T24

BLOCKING

METAL ROOFING PANEL
3" MIN.

OFFSET CLEAT ATTACH W/ #10-12 x 1"
PHW AT 12" O.C.

TUBE SEALANT BTW

PANEL RIBS

VALLEY FLASHING

ROOF UNDERLAYMENT WRB
ROOF FRAMING PER STRUCT.

ROOF SHEATHING PER STRUCT.
10"

ROOF VALLEY

METAL ROOFING
3" = 1' - 0"
2"
RIGID INSULATION PER T24

BLOCKING

METAL ROOFING FLASHING

SHED ROOF AT METALSIDING
3" = 1'-0"
SHAPED BLOCKING, TYP.

INTERIOR FINISH

PER PLAN

METAL ROOF

ASSEMBLY
6" MIN.

ROOF FRAMING
PER STRUCT.

WALL FRAMING AND

INSULATION PER FLOOR PLAN
SHEATHING PER STRUCT.

WOOD BLOCKING
WHERE OCCURS, TYP.

ROOF SHEATHING PER STRUCT.

END DAM BY ROOFING MFGR.
6" WIDE CONT. STRIP (CASAM)

FLASHING LAPPED OVER

METAL ROOF FLASHING
2 LAYERS WATER RESISTANT

BARRIER (WRB) OVER SHEATHING

AND LAPPED OVER CASAM AND
SILL / HEAD TRIM, TYP.

FLASHING BY ROOFING MFGR.

ROOF UNDERLAYMENT (WRB)

OVER ROOF SHEATHING,

EXTEND UP WALL BEHIND

METAL ROOF FLASHING

METAL SIDING ASSEMBLY

OVER RIGID INSULATION

METAL SIDING CLOSURE, FASTENER
PER METAL SIDING MFGR., TYP.

SILL / HEAD TRIM BY
METAL SIDING MFGR., TYP.

RIGID INSULATION
PER T24
SOLATUBE 290DS
CURB FLASHING @ PITCHED ROOF & HARD

CEILING CONDITION
NTS
SKYLIGHT FLASHING 1-1/2" = 1'-0"
GENERAL NOTES:

CURB FLASHINGS ARE DESIGNED TO FLOAT WITH EXPANSION AND CONTRACTION OF THE PANELS. A WEATHERTIGHT SEAL IS CRITICAL BETWEEN BASE FLASHING & UNDERSIDE OF PANELS.

COUNTER FLASHING FASTEN TO CURB

HEADWALL FLASHING WITH CLOSURE SYSTEM

USED AT HEAD OF CURB
CURB FLASHING IS TO BE INSTALLED WITH A 1"
CLEARANCE BETWEEN FLASH & MECH. CURB

KEYHOLE RIB CLOSURE
RIVET PANEL TO CURB @ 4" O.C. MAX WITH A

CONTINUOUS BEAD OF SEALANT ON EACH
SIDE OF RIVETS. AT STIFFENING BEADS SEAL

WITH FOAM ROD AND SEALANT
CLIP TO BE INSTALLED AT LEAST 1" FROM

END OF CURB FLASHING
A FLASHING @ LOW END
B FLASHING @ HIGH END
C FLASHING @ RAKE

COUNTER FLASHING BY SKY LIGHT MANUFACTURES
COUNTER FLASHING FASTEN TO MECH. CURB
RIVET PANEL TO CURB @ 4" O.C. MAX.

WITH A CONTINUOUS BEAD OF
EASLANT ON EACH SIDE OF RIVETS.

AT STIFFENING BEADS SEAL WITH
FOAM ROD & SEALANT.

PANEL END CLOSURE

FORMED CRICKET OVER SHAPED

RIGID INSULATION

CURB FLASHING IS TO BE INSTALLED
WITH A 1" CLEARANCE BETWEEN
FLASHING AND MECHANICAL CURB.

COUNTER FLASH BY SKYLIGHT MANUFACTURE
CURB FLASHING IS FABRICATED WITH 1" STIFFENING LEG

CURB FLASH IS TO BE INDEPENDENT FROM
STRUCTURAL CURB. CURB IS POSITIVELY FASTENED

TO PANELS THEREFORE CURB WILL EXPAND AND
CONTRACT WITH PANELS.

FIELD CUT PANELS TO SUIT CURB & RIVET
TOGETHER WITH CONT. SEALANT ON EACH SIDE OF
RIVETS. RIVETS @ 4" O.C. MAX.
10" MIN.
1"
4" MIN.
12" MIN.
10" MIN. HIGH
PT.
4" @
24" MIN.
4" MIN. 8" MIN.
10" MIN.
6" MIN.

EAVE / FASCIA

METAL ROOFING AT OVERHANG
3" = 1'-0"

METAL ROOFING PANEL O/RIGID INSULATION,

WHERE OCCURS
SEALANT PER MFR. REQUIREMENTS

OFFSET CLEAT PER MFR REQUIREMENTS
GUTTER STRAP AT 36" O.C.
2" TALL FLOW DAM AND STRAINER

AT EACH DOWNSPOUT
2" DIA. DOWNSPOUT

METAL GUTTER, COLOR

AND FINISH TO MATCH

METAL ROOFING
ROOF UNDERLAYMENT WRB, LAP O/ FASCIA 3"
2x12 WOOD FASCIA,

CUT TO FIT
ROOF SHEATHING PER STRUCT.
4 A-720
METAL SOFFIT, FASTEN PER MFGR., TYP.
2X10 RAFTER TAILS

CONTINUOUS PERFORATED METAL VENT SEE ROOF CALCS
1/2"

BRAKE METAL FACIA WRAP,

MATCH ROOF FINISH

SEE ROOF CALCS

METAL ROOF ASSEMBLY O/RIGID

INSULATION O/WRB
CONT. TRIM CLEAT

ALIGN W/LINE OF GUTTER AT EAVE
NOTE: ALIGN CLEAT W/BOT OF GUTTER @

ADJACENT EAVE
RAKE CLEAT, FASTEN PER MFGR.

REQUIREMENTS, TYPICAL

VERTICAL SEAM FLOATING RAKE ANGLE

RAKE TRIM W/ HEMMED EDGE, FINISH

TO MATCH ROOF PANEL

FASTENERS PER MANUFACTURER,

TYPICAL

ROOF UNDERLAYMENT WRB,
LAP O/ FASCIA 3" MIN
ROOF SHEATHING PER STRUCT.

RAKE / FASCIA CONDITION

METAL ROOFING
3" = 1'-0"
METAL SOFFIT, FASTEN PER MFGR., TYP.
2x WOOD FASCIA
2X10 RAFTER TAILS FRAMING

BRAKE METAL FACIA WRAP,

MATCH ROOF FINISH
BLOCKING @ RIGID INSLATION,

WHERE OCCURS
RIGID INSULATION PER T24,

WHERE OCCURS

CONTINUOUS SOFFIT VENT

LINE OF RAFTER TAILS BEYOND

BLOCKING WHERE REQUIRED

ROOF UNDERLAYMENT WRB,
LAP O/ FASCIA 3"
2x12 WOOD FASCIA

HIGH EAVE

METAL ROOFING
3" = 1'-0"

CLEAT PER MANUFACTURER

FLASHING PER ROOFING
MANUFACTURER. FINISH TO

MATCH ROOFING MATERIAL
ROOF SHEATHING PER STRUCT.

CONTINUOUS VENT
JAMB TRIM BY METAL SIDING MFGR.

METAL ROOFING PANEL
POP RIVETS PER MANUF. REQ.

BUTYL TAPE

PANEL CLIP
'Z' CLOSURE PER ROOFING

MANUFACTURER

BUTYL SEALANT
2X10 RAFTER TAILS

BRAKE METAL FACIA WRAP,

MATCH ROOF FINISH
METAL SOFFIT, FASTEN PER MFGR., TYP.

RIGID INSULATION PER T24

BLOCKING

BLOCKING, WHERE REQUIRED

METAL ROOF ASSEMBLY

O/RIGID INSULATION O/WRB
CONT. TRIM CLEAT

ALIGN W/LINE OF GUTTER
@ EAVE
RAKE CLEAT, FASTEN PER MFGR.

REQUIREMENTS, TYPICAL

VERTICAL SEAM FLOATING

RAKE ANGLE

RAKE TRIM W/ HEMMED EDGE,

FINISH TO MATCH ROOF PANEL

FASTENERS PER MFG, TYP

ROOF UNDERLAYMENT WRB,
LAP O/ FASCIA 3" MIN
ROOF SHEATHING PER STRUCT.

TIGHT RAKE

METAL ROOFING
3" = 1'-0"
2x BLOCKING

ROOF FRAMING PER STRUCT

BRAKE METAL FASCIA WRAP,

MATCH ROOF FINISH

BLOCKING
RIGID INSULATION PER T24

BLOCKING TO MATCH DEPTH OF SOFFIT
PANEL @ CLERESTORY

SHEATHING PER STRUCT

BACKER ROD AND SEALANT

METAL PANEL O/RIGID INSULATION

METAL SIDING

AT EXTERIOR SOFFIT VENT
3" = 1'-0"
2 LAYERS WATER RESISTANT BARRIER
(WRB), TYP.; LAP WRB OVER CASAM

BATT INSULATION
METAL SOFFIT, FASTEN PER MFGR.,
TYP.

CONTINUOUS SOFFIT VENT

RIGID INSULATION
SHEATHING PER STRUCT.

SOFFIT FRAMING PER STRUCT.

LINE OF SOFFIT FRAMING
BEYOND

SKYLIGHT FLASHING
PLAN
3/4"=1'-0"
4 PIECE CURB

ROOF SLOPE
1" INTERLOCKING HEMS, SEALED AND
RIVETED. DOWNSLOPE HEMS TO RUN
PARALLEL WITH PANELS. HEMS ON

UPSLOPE SIDE TO RUN PERPENDICULAR
TO PANELS.

FORMED CRICKET AT
REAR OF CURB.
1" STIFFENING LEG AT 45
FROM CURB.

FOR FLASHING SECTIONS, REFER TO
FIELD VERIFY =
FIELD VERIFY =
24" MIN.
12" LAP
12" MIN.
10" MIN.
6" MIN.
14 A-720
14 A-720
14 A-720
C
B
A
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
7/3/2024 12:48:35 PM C:\Users\kaleksandrov\OneDrive - Williams & Paddon\Documents\210015.01_CITY OF ROSEVILLE_DCWWTP ADMIN BLDG_A22_kaleksandrov4T455.rvt A-720

METAL ROOF

DETAILS

DCWWTP OPERATIONS

AND LAB BLDG
May 29, 2024
19six 210015.01
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
311 VERNON ST
ROSEVILLE, CA 95768
90% CD - PERMIT SET
8 4
1 7
5 6
9 23 11
14 3
2 20 16 12
15 NO. DATE DESCRIPTION
2/28/25

BID SET (PRELIMINARY)
WALL FRAMING PER STRUCT.

THERMAL BATT WALL INSULATION

ROOFING MEMBRANE,

FULLY ADHERED

TERMINATION BAR
WELDED CONT. TO

BASE MEMBRANE
ROOF SHEATHING PER STRUCT.

THERMAL BATT

ROOF INSULATION
ROOF FRAMING PER STRUCT.

BASE ROOFING MEMBRANE
SHEATHING PER STRUCT.

WALL / PARAPET TRANSITION

SINGLE PLY ROOFING
3" = 1' - 0"

CANT STRIP
ROOF PENETRATION, TYP.

ROOF FRAMING PER STRUCT.

SEALANT, TYP.

THERMAL BATT

ROOF INSULATION
DRAW BAND, TYP.

ROOF MEMBRANE FLASHING, TYP.

ROOF MEMBRANE FLASHING, TYP.; 1"
MINIMUM TURN-UP AT ROOF PENETRATION.

ROOF MEMBRANE ADHESIVE, TYP
FASTENER, TYP.; TYPE, SIZE AND
LOCATION PER ROOFING MFGR.

RECOMMENDATIONS
1-1/2" CONTINUOUS WELD, TYP.

ROOFING MEMBRANE, TYP.

SEALANT, TYP.
1-1/2" CONTINUOUS WELD, TYP.

SEALANT, TYP.

ROOF PENETRATION, TYP.

THERMAL BATT

ROOF INSULATION
SEALANT, TYP.

ROOF FRAMING PER STRUCT.

STAINLESS STEEL CLAMP
FASTENER, TYP.; TYPE, SIZE AND
LOCATION PER ROOFING MFGR.

RECOMMENDATIONS

PREMOLDED BOOT
HEAT WELDED LAP, TYP.

ROOFING MEMBRANE, TYP.

FIELD WRAPPED PENETRATION FLASHING

PREMOLDED PENETRATION FLASHING
6" MIN.

ROOF SHEATHING PER STRUCT.

ROOF SHEATHING PER STRUCT.

ROOF PENETRATIONS

SINGLE PLY ROOFING
3" = 1'-0"

SEALANT

ROOFING MEMBRANE

THERMAL BATT ROOF INSULATION
ROOF FRAMING PER STRUCT.

FASTENER- TYPE, SIZE AND

LOCATION AS RECOMMENDED BY

ROOFING MANUFACTURER

CONTINUOUS HEAT WELD
5" OVERLAP
1 5/8" MIN.

ROOF SHEATHING PER STRUCT.

TYPICAL FASTENER & LAP

SINGLE PLY ROOFING
3" = 1' - 0"
SEALANT PER MFG, TYP.

ROOF MEMBRANE, TYP.

THERMAL BATT ROOF INSULATION
ROOF FRAMING PER STRUCT.

WALKWAY MEMBRANE, BY
ROOFING MFGR.
1-1/2" CONTINUOUS WELD AROUND EDGE OF
WALKWAY; MEMBRANE SHALL BE WATERTIGHT.

ROOF SHEATHING PER STRUCT.

ROOF WALKWAY

SINGLE PLY ROOFING
3" = 1' - 0"

PROVIDE ROSIN PAPER SLIP SHEET BETWEEN
CASAM AND ROOF MEMBRANE, TYP.
1/4":1' SLOPE
NOTE:

FOR COPING JOINT SEE DETAIL

FOR PERPENDICULAR WALL

FLASHING AT COPING SEE DETAIL
METAL SIDING ASSEMBLY, TYP.

SHEATHING PER STRUCT., TYP.

PARAPET FRAMING PER STRUCT.

METAL PARAPET COPING BY SIDING MFGR.,
TYP.; MATERIAL AND FINISH TO
MATCH METAL SIDING PANELS . 12
A-721
12 A-721
11 A-721

PARAPET CAP

AT METAL SIDING (NO RIGID INSULATION)
3" = 1' - 0"
2 LAYERS WATER RESISTANT BARRIER (WRB)

OVER SHEATHING

COLD APPLIED SELF-ADHERING MEMBRANE
(CASAM); APPLY OVER T.O. WALL, DOWN OVER
BOTH LAYERS OF WRB, AND 2" MIN. DOWN F.O.

SHEATHING UNDER ROSIN PAPER AND ROOF
ROOF MEMBRANE, TYP.

MEMBRANE,
EXTEND

OVER ROSIN
PAPER
20 GA. GSM
CLEAT
CONT. SHAPED

WOOD BLOCKING,
TYP.
20 GA. GSM CLEAT
METAL SIDING CLOSURE PER MFGR, TYP.

DIM. POINT
T.O. PARAPET FRAMING

PROVIDE ROSIN PAPER SLIP SHEET BETWEEN
CASAM AND ROOF MEMBRANE, TYP.
1/4":1' SLOPE
NOTE:

FOR COPING JOINT SEE DETAIL

FOR PERPENDICULAR WALL

FLASHING AT COPING SEE DETAIL
METAL SIDING ASSEMBLY, TYP.

SHEATHING PER STRUCT., TYP.

PARAPET FRAMING PER STRUCT.

METAL PARAPET COPING BY SIDING MFGR.,
TYP.; MATERIAL AND FINISH TO
MATCH METAL SIDING PANELS . 12
A-721
12 A-721
11 A-721

PARAPET CAP

AT METAL SIDING
3" = 1' - 0"
2 LAYERS WATER RESISTANT BARRIER (WRB)

OVER SHEATHING

COLD APPLIED SELF-ADHERING MEMBRANE
(CASAM); APPLY OVER T.O. WALL, DOWN OVER
BOTH LAYERS OF WRB, AND 2" MIN. DOWN F.O.

SHEATHING UNDER ROSIN PAPER AND ROOF
ROOF MEMBRANE, TYP.

MEMBRANE,
EXTEND

OVER ROSIN
PAPER
20 GA. GSM
CLEAT
CONT. SHAPED

WOOD BLOCKING,
TYP.
20 GA. GSM CLEAT
METAL SIDING CLOSURE PER MFGR, TYP.

RIGID INSULATION, TYP.

DIM. POINT
T.O. PARAPET FRAMING
RAKE

METAL ROOFING AT METAL SIDING
3" = 1' - 0"
6"
2"

THERMAL BATT

ROOF INSULATION

ROOF FRAMING
PER STRUCT.

SHEATHING PER STRUCT., TYP.
2 LAYERS WATER RESISTANT BARRIER
(WRB), TYP.; WRB SHALL EXTEND OVER

CASAM AND DRIP/SILL FLASHING
COLD APPLIED SELF-ADHERING MEMBRANE (CASAM);

APPLY UNDER WRB AND LAP OVER RAKE FLASHING
METAL SIDING ASSEMBLY, TYP.

RAKE CLEAT
FLASHING TRIM, FASTEN PER MANUFACTURER, TYP.

VERTICAL SEAM FLOATING RAKE ANGLE

METAL ROOF ASSEMBLY OVER ROOF
UNDERLAYMENT WRB. WRB TO CONTINUE
UP WALL 8"
8"

ROOF SHEATHING
PER STRUCT.
2" 4"
DRIP/SILL FLASHING BY METAL SIDING MFGR.

ROOF MEMBRANE OVER SHEATHING

RIGID INSULATION
PER T24, WHERE OCCURS
BLOCKING @ RIGID INSULATION
2-1/2"x2" STEEL STRINGER

FACE OF WALL
GENERAL NOTES:

1. GRIND ALL EDGES SMOOTH

2. PRIME AND PAINT PER SPECS.
3/4" ROUND BAR - WELD ALL AROUND
TO FLAT BAR AT 12" CENTERS (TYP.)
8"x4"x1/2" ANGLE-WELD TO FLAT BAR
AT 4'-0" O.C.
5/8" DIA. BOLTS INTO BLOCKING AT 4'-0" O.C.
2x10 WOOD BACKING PLATE
2x WALL FRAMING
1'-6"
7"

ROOF ACCESS LADDER

AT STUD WALL
1 1/2" = 1'-0"

FINISH FLOOR
GENERAL NOTE:

CENTER STRINGER AT ROOF HATCH OPENING.

LATCH HATCH WITH HINGE SIDE AT OPPOSITE

LOCATION RELATIVE TO LADDER

ROOF HATCH
ROOF FRAMING AND DECKING. REFER TO

STRUCTURAL DOCUMENTS

STEEL LADDER STRINGER
ATTACHMENT ANGLE SUPPORT, 3 PAIR

MINIMUM

PRE MANUFACTURED SAFETY CAGE PER OSHA

REQUIREMENTS AT LADDER

ROOFING MEMBRANE ASSEMBLY INSTALLED
PER MFTR. RECOMMENDATIONS

FRICTION FIT BATT INSULATION
7'-0" AFF.
4'-0" MAX.
1"
12"
6"

TYPICAL
12"
2"
A-721
10 8
A-721
ROOF ACCESS HATCH 1/2" = 1'
-0"

MECHANICALLY FASTEN MEMBRANE
PER ROOFING MFTR. REQUIREMENTS

TPO COATED METAL FLASHING

INSULATED ROOF HATCH CURB
SHEATHING PER STRUCT.

STRUCTURAL REINFORCEMENT PER STRUCT.

THERMAL BATT ROOF INSULATION
6" MIN.

ROOF SCUTTLE

AT ROOF ACCESS HATCH
1 1/2" = 1'-0"
EXTERIOR GYP. SHEATHING, TYP.

ROOF FRAMING PER STRUCT.
4"
BACKER ROD & SEALANT @

TRANSITION TO CAP
SLOPE FLASHING UP UNDER METAL ROOFING 6"
(WALL PARAPET) 20GA GALV'D SHT MTL CAP

FLASHING WITH FULL SOLDERED SEAMS

RECESSED FLANGE (SET BEHIND CEMENT

PLASTER ASSEMBLY)

METAL ROOFING TO EXTEND
12" OVER FLASHING 10"
.

PARAPET FLASHING

AT PERPENDICULAR WALL
1 1/2" = 1'-0"

PROVIDE MASTIC BED BETWEEN

JOINT PROFILE PER SEAM/JOINT AND SUBSTRATE
SMACNA
22 GA. GSM FLASHING COPING PER SMACNA
CHART 12 "COPING DESIGN" TYPE "J9-DRIVE".

SEAM/ JOINT SPACING PER SMACNA
RECOMMENDATIONS. FINISH TO MATCH ROOF
PANEL

SECTION/ELEVATION

AXONOMETRIC

PARAPET COPING

AT SEAM / JOINT
1 1/2" = 1'-0"
SUPPLEMENTAL 2x4 BLK. EA.

DIRECTION. COORD. W/ ROOF
STRUCT. & STRUCT. DWGS..

DRAIN BODY OVERFLOW DRAIN

STRAINER
OVERFLOW w/STRAINER

CLAMPING RING
FLASHING PER TPO ROOF MFTR. SPECS.

ROOFING- SEE SPECS

FLASHING PER TPO ROOF
MANUFACTURER SPECS.

STRUCT. PLYWOOD SHEATHING

FRAMED CRICKET AT DRAIN
ASSEMBLY TO PARAPET W/ 1/2"
PER 1'-0" SLOPE, MIN.

NOTE: COORDINATE AND COMPLY WITH ALL SPECIFIC REQ. OF ROOFING MFTR.

DETAILS TO BE USED IN CONJUNCTION WITH STANDARD GUIDE SPECS CONTAINING REQUIREMENTS FOR NAILERS, INSULATION, SLIPSHEETS, SEALANT ETC..

PARAPET CAP
+6" ABOVE MAIN ROOF
REFER TO PLUMBING DWGS.

SECTION
PLAN N.T.S.
2'-0" TYP.
11" TYP.
5'-0" TYP.
2"
2 1/8"

ROOF DRAIN & OVERFLOW

AT TPO OVER RIGID INSULATION CRICKET
1 1/2" = 1'-0"

MEMBRANE SEALANT PER MFG

ROOFING MEMBRANE,

FULLY ADHERED

TERMINATION BAR
ROOF SHEATHING PER STRUCT.

THERMAL BATT

ROOF INSULATION
ROOF FRAMING PER STRUCT.

BASE ROOFING MEMBRANE

ROOF CURB

SINGLE PLY ROOFING
3" = 1' - 0"

CANT STRIP

EQUIPMENT SUPPORT BRACKET
WELDED CONT. TO

BASE MEMBRANE

EQUIPMENT CURB
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP
REVISIONS #

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
7/3/2024 12:48:38 PM C:\Users\kaleksandrov\OneDrive - Williams & Paddon\Documents\210015.01_CITY OF ROSEVILLE_DCWWTP ADMIN BLDG_A22_kaleksandrov4T455.rvt A-721

TPO ROOF DETAILS

DCWWTP OPERATIONS

AND LAB BLDG
May 29, 2024
19six 210015.01
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
311 VERNON ST
ROSEVILLE, CA 95768
90% CD - PERMIT SET
123456789
10 11
12 14
13 NO. DATE DESCRIPTION
2/28/25

BID SET (PRELIMINARY)
CANOPY SECTION 3"=1'-0"

STEEL ANGLE OUTRIGGER,

REFER TO STRUCTURAL

DRAWINGS

BAR GRATING AT

TRELLIS ASSEMBLY

SUPPORT STEEL ANGLE

AT BAR GRATING

PERIMETER, REFER TO

STRUCTURAL DRAWINGS

SUPPORT STEEL 'T' BAR

AT BAR GRATING

PERIMETER, REFER TO

STRUCTURAL DRAWINGS
CANOPY DETAIL AT ENTRY STOREFRONT 3" = 1'-0" ALIGN
HSS BEAM PER STRUCT.

INTERIOR EXTERIOR ALIGN 10"

STEEL 'T' BAR SUPPORT IN

BETWEEN BAR GRATING

SECTIONS

CANOPY STEEL STRUCTURE FASCIA,

REFER TO STRUCTURAL DRAWINGS

BAR GRATING AT TRELLIS ASSEMBLY

EDGE OF CANOPY SUPPORT STEEL

ANGLE AT CANOPY PERIMETER,

REFER TO STRUCTURAL DRAWINGS

STEEL ANGLE OUTRIGGER BEYOND,

REFER TO STRUCTURAL DRAWINGS

SUPPORT STEEL ANGLE AT BAR

GRATING PERIMETER, REFER TO

STRUCTURAL DRAWINGS

STOREFRONT BRAKE

METAL PER DETAIL
22 A-710
1"
CANOPY FASCIA DETAIL - GRATE 3"=1'-0"

STEEL 'T' BAR SUPPORT IN BETWEEN

BAR GRATING SECTIONS

CANOPY STEEL STRUCTURE FASCIA,

REFER TO STRUCTURAL DRAWINGS

BAR GRATING AT TRELLIS ASSEMBLY

STEEL ANGLE OUTRIGGER BEYOND,

REFER TO STRUCTURAL DRAWINGS

SUPPORT STEEL ANGLE AT BAR

GRATING PERIMETER, REFER TO

STRUCTURAL DRAWINGS
4 A-730
C D G
10 11
F
3 A-730
24 A-730

BAR GRATING

CANOPY STEEL STRUCTURE FASCIA, REFER TO STRUCTURAL DRAWINGS

CANOPY STEEL STRUCTURE

FASCIA, REFER TO
STRUCTURAL DRAWINGS.

CANOPY SUPPORT, REFER
TO STRUCTURAL DRAWINGS.
18'-4 5/8"
20'-8 1/2" 54'-11"
7'-1 1/2" 4'-5 1/4" 4'-7" 4'-6 3/4" 8'-2" 10'-8" 12'-0" 12'-0" 12'-1" 2'-2 1/2" 3'-6 1/2" 3'-0 1/4" 3'-0 1/4" 3'-2 1/4"
15 A-730
2 A-730
24 A-730

DRAIN CHAIN

METAL GUTTER

METAL ROOF
CL
CL
CL
CL
CL
CL
CL CL

CL CL CL
1 22
A-730
22 A-730
SLOPE

GALV METAL GUTTER

DOWNSPOUT
10'-11"
4'-8 1/2"
STEEL CHANNEL (3) SIDES

HSS SUPPORT BEAM PER STRUCT
CANOPY EDGE DETAIL - MTL PANEL 3"=1'-0"

GALV METAL GUTTER

CANOPY STEEL STRUCTURE FASCIA,

REFER TO STRUCTURAL DRAWINGS
1" METAL SOFFIT PANEL BETWEEN HSS BEAMS BEYOND

STEEL BEAM, SEE STRUCT
1" METAL ROOFING

SLOPE TO GUTTER

STEEL BEAM, SEE STRUCT
5 1/2"
4"
A - LAB CANOPY AT METAL SIDING @ SUPPORT HSS BEAM 3" = 1'-0" 1" METAL ROOFING; SLOPE TO DRAIN

ALL CONNECTIONS SET IN SEALANT

GALV METAL GUTTER

STEEL CHANNEL BEYOND

FILL CAVITY W/RIGID INSULATION

BITUTHANE WATERPROOFING O/METAL FLASHING
(2) LAYERS WRB O/SHEATHING

DOWNSPOUT

METAL PANEL
RIGID INSULATION, R-VALUE PER T24

BACKER ROD & SEALANT

HSS PER STRUCTURAL

HSS BEAM PER STRUCT

SUPPORT POST PER STRUCT
B.O. STEEL

SEE SECTION

SEE STRUCT

BITUTHANE WATERPROOFING
B - LAB CANOPY AT METAL SIDING, TYP CONDITION 3" = 1'-0" EDGE OF PERIMETER C-CHANNEL; TERMINATE AT RIGID INSULATION

METAL PANEL
RIGID INSULATION, R-VALUE PER T24

BACKER ROD & SEALANT

HSS PER STRUCTURAL

HSS BEAM BEYOND PER STRUCT
B.O. STEEL

SEE SECTION

SEE STRUCT
1" METAL ROOFING; SLOPE TO DRAIN

ALL CONNECTIONS SET IN SEALANT

GALV METAL GUTTER

STEEL CHANNEL BEYOND

FILL CAVITY W/RIGID INSULATION

BITUTHANE WATERPROOFING O/METAL FLASHING
(2) LAYERS WRB O/SHEATHING

SUPPORT POST PER STRUCT

BITUTHANE WATERPROOFING
EDGE OF C-CHANNEL; TERMINATE AT RIGID INSULATION
2"
4"
SOUTH CANOPY DETAIL AT CMU 3"=1'-0" SOUTH CANOPY DETAIL AT STOREFRONT 3"=1'-0"

CANOPY FASCIA DETAIL
2 A-730
4 A-730

METAL FLASHING

BITUTHANE WATERPROOFING O/METAL FLASHING
(2) LAYERS WRB O/SHEATHING

HEADER & CANOPY CONNECTION PER STRUCTURAL
CONC EMBEDDED RODS @ ANCHOR PLATE

STEEL ANCHOR PLATE

BITUTHANE WATERPROOFING O/METAL FLASHING
(2) LAYERS WRB O/SHEATHING

HEADER & CANOPY CONNECTION PER STRUCTURAL
ALIGN
1/4" MIN. BACKER ROD &
SEALANT, TYP. BOTH SIDES

BLOCKING

CANOPY FASCIA DETAIL
2 A-730
4 A-730
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
7/3/2024 12:48:41 PM C:\Users\kaleksandrov\OneDrive - Williams & Paddon\Documents\210015.01_CITY OF ROSEVILLE_DCWWTP ADMIN BLDG_A22_kaleksandrov4T455.rvt A-730

CANOPY DETAILS

DCWWTP OPERATIONS

AND LAB BLDG
May 29, 2024
19six 210015.01
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
311 VERNON ST
ROSEVILLE, CA 95768
90% CD - PERMIT SET
4 15 3
21 1/4" = 1'-0"
ENLARGED CANOPY PLAN - MAIN ENTRY 5 1/2" = 1'-0"ENLARGED CANOPY - LABORATORY ENTRY 22 2
24 NO. DATE DESCRIPTION
2/28/25

BID SET (PRELIMINARY)

WALL FRAMING AND INSULATION PER PLAN
5/8" TYPE 'X' GYP. BD. EA. SIDE,
(1) SIDE FOR FURRED WALL
(2) #10 SMS AT EACH CLIP
SECURE DIAGONAL BRACES TO WALL FRMG. SEE

PLANS FOR ADDITIONAL INFO

WALL FRAMING TOP TRACK

BLOCKING TYPICAL AT CEILING

FRAMING CLIP AT

EACH BRACE
(2) #10 SMS AT EACH BRACE
3 5/8" X 20 GA METAL STUD
DIA. BRACING AT 8'-0" O.C.

EACH WAY MAX., SEE
6" MIN.

PARTITION WALL
T.O.W. - NON-RATED
3" = 1'-0"
14 A-760
18 A-760

CEILING JOIST FRAMING

GYPSUM SHEATHING AT CEILING

WALL FRAMING AND INSULATION

PER PLAN

PARTITION WALL
T.O.W. AT CEILING JOIST
3" = 1'-0"
5/8" TYPE 'X' GYP. BD. EA. SIDE
CONCRETE SLAB PER STRUCT.

BOTTOM OF FURRED WALL

NON-RATED
3" = 1'-0"
5/8" TYPE 'X' GYPSUM BOARD SHEATHING,
ONE SIDE TYP.

WALL FRAMING AND INSULATION PER PLAN

SEE FINISH PLANS FOR BASE FINISH SEE FINISH PLANS FOR BASE FINISH

CONCRETE CURB, WIDTH TO MATCH

STUD SIZE

A AT FLOOR SLAB B AT CONCRETE CURB

CONTINUOUS SEALANT CONTINUOUS SEALANT
CONCRETE SLAB PER STRUCT.

FASTENER PER STRUCTURAL
3 1/2"

FASTENER PER STRUCTURAL
5/8" TYPE 'X' GYPSUM BOARD SHEATHING,
ONE SIDE TYP.

WALL FRAMING AND INSULATION PER PLAN

BOTTOM OF RESTROOM WALL

NON-RATED
3" = 1'-0"
5/8" TILE BACKER BOARD,
EACH SIDE TYP.

WALL FRAMING AND INSULATION PER PLAN
3 1/2"

A TILE ON BOTH SIDES B TILE ON ONE SIDE
5/8" TILE BACKER BOARD,
ONE SIDE TYP.

WALL FRAMING AND INSULATION PER PLAN

CONCRETE CURB, WIDTH TO MATCH

STUD SIZE
3 1/2"

CONTINUOUS SEALANT

WALL FINISH

WHERE OCCURS
CONCRETE SLAB PER STRUCT.

COVE BASE TRIM, TYP.

CONCRETE CURB, WIDTH TO MATCH

STUD SIZE

FASTENER PER STRUCTURAL

CONTINUOUS SEALANT,

BOTH SIDES

CERAMIC TILE AND GROUT OVER THIN SET
MORTAR

CERAMIC TILE AND GROUT OVER THIN SET

MORTAR, BOTH SIDES
CONCRETE SLAB PER STRUCT.

COVE BASE TRIM, TYP.

FASTENER PER STRUCTURAL

CERAMIC TILE AND GROUT OVER THIN SET
MORTAR

CERAMIC TILE AND GROUT OVER THIN SET

MORTAR, BOTH SIDES

BOTTOM OF WALL

TYPICAL
3" = 1'-0"
5/8" TYPE 'X' GYPSUM BOARD SHEATHING,
EACH SIDE TYP.

WALL FRAMING AND INSULATION PER PLAN

SEE FINISH PLANS FOR BASE FINISH
5/8" TYPE 'X' GYPSUM BOARD SHEATHING,
EACH SIDE TYP.

WALL FRAMING AND INSULATION PER PLAN

SEE FINISH PLANS FOR BASE FINISH

CONCRETE CURB, WIDTH TO MATCH

STUD SIZE

A AT FLOOR SLAB B AT CONCRETE CURB

CONTINUOUS SEALANT,

BOTH SIDES

FASTENER PER STRUCTURAL
3 1/2"

FASTENER PER STRUCTURAL

CONTINUOUS SEALANT,

BOTH SIDES
CONCRETE SLAB PER STRUCT. CONCRETE SLAB PER STRUCT.

TOP OF FULL HEIGHT WALL AT I-JOIST

NON-RATED
3" = 1'-0"

WALL AND INSULATION PER PLAN

I-JOIST BLOCKING
PER STRUCT.

WOOD I-JOIST PER STRUCT.

TOP OF WALL PERPENDICULAR TO I-JOIST TOP OF WALL PARALLEL TO I-JOIST

WALL FRAMING TOP TRACK

WALL AND INSULATION PER PLAN
WOOD I-JOIST PER STRUCT.

FRAMING CLIP AND FASTENER PER STRUCT. FRAMING CLIP AND FASTENER PER STRUCT.

WALL FRAMING TOP TRACK

TOP OF WALL PERPENDICULAR TO ROOF FRAMING TOP OF WALL PARALLEL TO SLOPED ROOF FRAMING

TOP OF FULL HEIGHT WALL AT METAL ROOF

NON-RATED
1 1/2" = 1'-0"

METAL ROOF ASSEMBLY,

REFER TO ROOF PLAN
I-BEAM PER STRUCT.

FRAMING CLIP AND FASTENER
PER STRUCT.

CEILING, REFER TO

REFLECTED CEILING PLAN

WALL AND INSULATION PER PLAN

ROOF INSULATION
2x BLOCKING PER STRUCT.

WALL AND INSULATION PER PLAN

CEILING, REFER TO

REFLECTED CEILING PLAN

METAL ROOF ASSEMBLY,

REFER TO ROOF PLAN
I-BEAM PER STRUCT.

ROOF INSULATION

BEVELED TOP TRACK
PER STRUCT.

WALL FRAMING TOP TRACK
MORTAR SET AT SHOWER 3"=1'-0"
TILE THIN SET OVER 2 COATS OF

WATERPROOF MEMBRANE W/

FIBERGLASS REINFORCING O/ TILE

BACKER BOARD

CONCRETE CURB, SEE

WATERTIGHT SHOWER PAN MEMBRANE O/
CONCRETE SLAB. EXTEND UP FACE OF
CURB AND WALL SHEATHING A MIN. OF 12"

AND TIE INTO WALL WATERPROOF
MEMBRANE.

REINFORCING SET IN SLURRY

BOND COAT
TILE O/ THIN SET O/ 1 LAYER OF
WATERPROOF MEMBRANE 1 1/2"
HYDROPHILIC WATERSTOP BAR.

SEE NOTE BELOW
NOTE: CONTRACTOR OPTION TO POUR

MONOLITHICALLY W/O WATER STOP
P.T. WOOD NAILER
SET IN CURB, TYP.

T.O. SLAB

SOUND ATTENUATION INSULATION, WHERE
OCCURS PER WALL SCHEDULE AND PLAN.

END OF WALL 3"=1'-0"

GYPSUM WALLBOARD

CORNER BEAD
1" x 3" x 18 GA. STRANDS @ BOTH SIDES

OF STUDS & SECURE TO EACH STUD WITH
#10 SMS @ 24" O.C. MAX.

STEEL STUD FRAMING

GYPSUM WALL BOARD

METAL STUD FRAMING
NOTES:

1. AT RATED WALL TO NON-RATED WALL,

CONTINUE RATED WALL PAST
INTERSECTING NON-RATED WALL.

2. AT SOUND WALL TO STANDARD WALL,

CONTINUE ENTIRE SOUND WALL PAST
STANDARD WALL.

WALL FRAMING

INTERSECTION
3"=1'-0"

SOUND ATTENUATION INSULATION, WHERE
OCCURS PER WALL SCHEDULE AND PLAN.
'T' INTERSECTION
GYPSUM WALL BOARD, TYP.

METAL STUD FRAMING

CORNER BEAD

CORNER INTERSECTION

SOUND ATTENUATION INSULATION, WHERE

OCCURS PER WALL SCHEDULE AND PLAN

METAL STUD WALL

AT HEADER - SECTION
3" = 1'-0"
TRACK
20 GA. METAL STUD
20 GA. TRACK
GYP. BD.

ALTERNATE BUILT-UP HEADER @ 48" AND LESS OPENINGS IN NON RATED WALLS
EXPOSED TILE EDGE FINISH 3"=1'-0"

SCHLUTER, JOLLY,

COLOR TBD, AT

EXPOSED EDGE OF
TILE
TILE
PLAN @ EXPOSED EDGE - WALL END

SCHLUTER, JOLLY,

COLOR TBD, AT

EXPOSED EDGE OF
TILE
TILE
SECTION @ EXPOSED EDGE

BACKING AND GRAB BAR ANCHORAGE

AT METAL STUD FRAMED WALLS
3" = 1'-0"
wp1.1

WALL FRAMING
6" x 16 GA. STRAP BACKING; EXTEND STRAP

BACKING ONE BAY MINIMUM PAST LAST

ATTACHMENT TO BACKING,TYPICAL
4 #10 SMS, TYPICAL
STRAP BACKING, TYPICAL U.O.N.

A. BACKING
4 #10 SMS, TYPICAL

WALL FRAMING
6" x 16 GA. TRACK BACKING WITH FLANGE
CUT BACK TO LAY OVER WALL FRAMING;

EXTEND BACKING ONE BAY MINIMUM PAST

LAST ATTACHMENT TO BACKING,TYPICAL

TRACK BACKING, WHERE NOTED
B. GRAB BAR ANCHORAGE

TILE, WHERE OCCURS
GYPSUM BOARD, TYPICAL; REFER TO

SPECIFICATIONS
3-5/8"x16 GA. MTL. BACKING

TRACK OR STUD ATTACHED AT

BOTH END TO WALL STUDS
MIN. 3- #12 TEKS @ EA. BRACKET, PREDRILLED WITH PIPE SPACER, MIN. 2 SCREWS AT TOP AND 1 SCREW AT BOTTOM; 1-1/2"
EMBEDMENT MINIMUM.

GRAB BAR & BRACKET

SNAP-ON ESCUTHEON

SECTION

METAL STUD BRIDGING NTS
B

COLD ROLLED CHANNEL BRIDGING
FOR 4" OR SMALLER STUD WIDTHS
A

STRAP BRIDGING

FOR ANY SIZE STUD

SEE PLANS AND WALL SCHEDULE FOR SIZE AND

SPACING OF STUDS
(2) #10 SMS, TYPICAL
COLD ROLLED CHANNEL 1-1/2" X 18 GA. CONT.

BRIDGING AT 4'-0" O.C. MAX.

ANGLE CLIP 1-1/2" X 1-1/2" X 18 GA. FULL WIDTH OF
STUD TYPICAL; FASTEN TO STUDS WITH (2) #10 SMS,

TYPICAL

METAL STUDS
(4) #10 SMS AT STRAP TO BLOCKING AND #10 SMS

STRAP TO EACH STUD, TYPICAL
METAL STUD TRACK BLOCKING TO MATCH STUD GA.

AT EACH END OF WLL AND 8'-0" O.C. TYPICAL
ANGLE CLIP 2" X 2" TO MATCH STUD GA X STUD
WIDTH LESS 1-1/2"; FASTEN TO STUDS WITH (2) #10

SMS, TYPICAL
1-1/2" X 20 GA
STRAP, CONT. @
4'-0" O.C. MAX. VERT.

SPACING

SPLICE STRAP AT

BLOCKING AS REQ'D
NOTES:

1. BRIDGING FOR 4" AND SMALLER STUDS SHALL BE CONSTRUCTED OF COLD ROLLED CHANNEL, U.O.N.

2. WHERE FULL HEIGHT SHEATHING OR GYP. BOARD. OCCURS ON BOTH SIDES OF METAL STUD FRAMING, THE BRIDGING MAY BE OMITTED, U.O.N.

3. AT CONDITIONS WHERE STRAP BRIDGING IS USED AND WHERE WALL SHEATHING OR GYP. BOARD. OCCURS ON ONE SIDE OF WALL ONLY, STRAP MAY BE OMITTED ON SIDE OF WALL WHERE SHEATHING OR GYP. BOARD.

OCCURS. IF DETAIL (B) IS USED, THEN COLD ROLLED CHANNEL IS REQUIRED.

METAL STUD FRAMING, SEE PLANS FOR WALL
TYPE

METAL STUD FRAMING, AT TOP AND

BOTTOM OF OPENING

RECESSED OR SEMI-RECESSED ACCESSORY

OR EQUIPMENT CABINET - REFER TO

SPECIFICATIONS

GYPSUM BOARD PER FINISH SCHEDULE

GYPSUM BOARD TOP, BOTTOM, & SIDES OF
RECESS

METAL STUD RUNNER AT TOP & BOTTOM

ADDITIONAL FURRING WHERE OCCURS

SHIFT RECESSED EQUIPMENT FLUSH WITH
WALL FINISH OR ADD FURRING IF REQUIRED.

VERIFY WITH ARCHITECT IN FIELD

SHIFT RECESSED EQUIPMENT FLUSH WITH WALL
FINISH, OR ADD FURRING IF REQUIRED. VERIFY

WITH ARCHITECT

ADDITIONAL FURRING WHERE OCCURS

SEMI-RECESSED ACCESSORY OR RECESSED

EQUIPMENT
5/8" TYPE 'X' GYPSUM BOARD TOP, BOTTOM &

SIDES OF RECESS

METAL STUD RUNNER AT TOP AND BOTTOM

METAL STUD FRAMING, SEE PLANS FOR WALL TYPE
ONE LAYER 5/8" TYPE X GYPSUM WALLBOARD OR

GYPSUM VENEER BASE APPLIED PARALLEL TO EACH
SIDE OF 1 5/8" STEEL STUDS 24" O.C. WITH 1" TYPE S
DRYWALL SCREWS 8" O.C. AT EDGES AND 12" O.C. AT

INTERMEDIATE STUDS
JOINTS STAGGERED 24" ON OPPOSITE SIDES.

METAL STUD FRAMING, EACH SIDE

SECTION
PLAN
1 HR RATED CONDITION

NON - RATED CONDITION

PARTITION WALL RECESS

METAL STUD FRAMING
3" = 1'-0"
1/4" CLR. TYP.

SECTION
PLAN
1/4" CLR. TYP.

DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
7/3/2024 12:48:44 PM C:\Users\kaleksandrov\OneDrive - Williams & Paddon\Documents\210015.01_CITY OF ROSEVILLE_DCWWTP ADMIN BLDG_A22_kaleksandrov4T455.rvt A-740

INTERIOR WALL

DETAILS

DCWWTP OPERATIONS

AND LAB BLDG
May 29, 2024
19six 210015.01
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
311 VERNON ST
ROSEVILLE, CA 95768
90% CD - PERMIT SET
5 1
7 6
8 13
14 12
19 15 11
24 16
17 23
NO. DATE DESCRIPTION
2/28/25

BID SET (PRELIMINARY)

BOTTOM OF TILE WALL AT CURB

NON-RATED
3" = 1'-0"
CONCRETE CURB PER STRUCT.
3 1/2"

FRICTION FIT BATT INSULATION PER WALL

SCHEDULE
5/8" TYPE 'X' GYPSUM BOARD SHEATHING,
TYP. BOTH SIDES

WOOD STUD FRAMING PER FLOOR PLAN
SHEATHING PER STRUCT. WHERE OCCURS

CERAMIC TILE AND GROUT OVER

THIN SET MORTAR, ONE SIDE
ANCHOR BOLT PER STRUCT.

CONTINUOUS SEALANT,
TYP. BOTH SIDES
CONCRETE SLAB PER STRUCT.

COVE BASE TRIM, TYP.

CERAMIC TILE AND GROUT OVER

THIN SET MORTAR

BOTTOM OF WALL AT SLAB

NON-RATED
3" = 1'-0"

SEE FINISH PLANS FOR BASE FINISH
SILL PLATE PER STRUCT.

FRICTION FIT BATT INSULATION PER WALL

SCHEDULE
5/8" TYPE 'X' GYPSUM BOARD SHEATHING,
TYP. BOTH SIDES

WOOD STUD FRAMING PER FLOOR PLAN
SHEATHING PER STRUCT. WHERE OCCURS
ANCHOR BOLT PER STRUCT.

CONTINUOUS SEALANT,
TYP. BOTH SIDES
CONCRETE SLAB PER STRUCT.

PARTITION WALL RECESS

WOOD STUD FRAMING
3" = 1'-0"

SECTION / PLAN
CLR. TYP.
1/4"

RECESSED ACCESSORY / EQUIPMENT, TYPICAL INSTALL
FLUSH WITH WALL OR ADD FURRING IF REQUIRED; VERIFY
WITH ARCHITECT IN THE FIELD.
1-HOUR RATED WALL BEHIND RECESSED ACCESSORY PER
PER GA FILE NO. WP3510

GYPSUM BOARD, TYPICAL AT ALL SIDES OF RECESS
1-HOUR RATED WALL ASSEMBLY; REFER TO

FLOOR PLAN FOR LOCATIONS AND ASSEMBLY
GA FILE NO. WP 3510:

ONE LAYER 5/8" TYPE X GYPSUM WALLBOARD OR GYPSUM

VENEER BASE APPLIED PARALLEL OR AT RIGHT ANGLES
TO EACH SIDE OF 2X4 WOOD STUDS 24" O.C. WITH 6d
COATED NAILS, 1-7/8" LONG, 0.0915" SHANK, 1/4" HEADS, 7" O.C.

JOINTS STAGGERED 24" ON OPPOSITE SIDES.

SECTION / PLAN

RECESSED ACCESSORY / EQUIPMENT, TYPICAL INSTALL
FLUSH WITH WALL OR ADD FURRING IF REQUIRED; VERIFY
WITH ARCHITECT IN THE FIELD.

GYPSUM BOARD, TYPICAL AT ALL SIDES OF RECESS 1/4" CLR. (TYP.) 2X WOOD STUD FRAMING, TYPICAL AT TOP, BOTTOM

AND SIDES OF OPENING
WALL ASSEMBLY; REFER TO FLOOR PLAN

FOR LOCATIONS AND ASSEMBLY

FULLY FILL CAVITY WITH UNFACED ACOUSTIC BATT

INSULATION
1 HR RATED CONDITION

NON - RATED CONDITION

WOOD STUD FRAMING, SEE PLANS FOR WALL TYPE

WOOD STUD FRAMING, SEE PLANS FOR WALL TYPE
SHEATHING PER STRUCT. WHERE OCCURS
SHEATHING PER STRUCT. WHERE OCCURS

TYPICAL WALL INTERSECTIONS

PLAN VIEWS
3" = 1'-0"

WALL SURFACE

WOOD STUD FRAMING
GYPSUM BOARD, U.N.O. 5/8"

TYPE 'X'

LC-BEAD

CONTINUOUS BEAD OF PAINTABLE

SEALANT OR FIRE CAULKING AT RATED
WALL

CORNER BEAD, TYPICAL

WOOD STUD JAMB FRAMING
GYPSUM BOARD, U.N.O.
5/8" TYPE 'X'

WOOD STUD FRAMING
GYPSUM BOARD, U.N.O.
5/8" TYPE 'X'

RUN GYPSUM WALL BOARD THROUGH

AT RATED WALLS

INSIDE CORNER BEAD, TYPICAL
GYPSUM BOARD, U.N.O.
5/8" TYPE 'X'

CORNER BEAD, TYPICAL

WOOD STUD FRAMING

INSIDE CORNER BEAD, TYPICAL
A WALL TERMINATIONB END OF WALLC "T" INTERSECTIOND CORNER SHEATHING PER STRUCT. WHERE OCCURS
SHEATHING PER STRUCT. WHERE OCCURS
SHEATHING PER STRUCT. WHERE OCCURS
SHEATHING PER STRUCT. WHERE OCCURS

TOP OF WALL AT PRE-FAB TRUSS

NON-RATED
3" = 1'-0"

PRE-FAB TRUSS - BOTTOM CHORD

TOP OF WALL PERPENDICULAR TO TRUSS
FRAMING CLIP PER STRUCT.

WALL FRAMING TOP PLATE

CEILING, REFER TO CEILING PLAN

FRICTION FIT BATT INSULATION PER WALL

SCHEDULE
5/8" TYPE 'X' GYPSUM BOARD SHEATHING,
TYP. BOTH SIDES

WOOD STUD FRAMING PER FLOOR PLAN
SHEATHING PER STRUCT. WHERE OCCURS

TOP OF WALL PARALLEL TO TRUSS

PRE-FAB TRUSS - BOTTOM CHORD
FRAMING CLIP PER STRUCT.

CEILING, REFER TO CEILING PLAN

FRICTION FIT BATT INSULATION PER WALL

SCHEDULE
5/8" TYPE 'X' GYPSUM BOARD SHEATHING,
TYP. BOTH SIDES

WOOD STUD FRAMING PER FLOOR PLAN
SHEATHING PER STRUCT. WHERE OCCURS

WALL FRAMING TOP PLATE
2X BLOCKING PER STRUCT.

TOP OF FULL HEIGHT SHEAR WALL

AT PRE-FAB TRUSS - NON-RATED
3" = 1'-0"

PRE-FAB TRUSS - BOTTOM CHORD

TOP OF WALL PERPENDICULAR TO TRUSS

BLOCKING

CEILING, REFER TO CEILING PLAN

FRICTION FIT BATT INSULATION PER WALL

SCHEDULE
5/8" TYPE 'X' GYPSUM BOARD SHEATHING,
TYP. BOTH SIDES

WOOD STUD FRAMING PER FLOOR PLAN
SHEATHING PER STRUCT. WHERE OCCURS
SHEATHING PER STRUCT.

ROOF ASSEMBLY PER ROOF
PLAN

PRE-FAB TRUSS - TOP CHORD

CORRIDOR

TOP PLATE PER STRUCT
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP
REVISIONS #

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
7/3/2024 12:48:46 PM C:\Users\kaleksandrov\OneDrive - Williams & Paddon\Documents\210015.01_CITY OF ROSEVILLE_DCWWTP ADMIN BLDG_A22_kaleksandrov4T455.rvt A-741

INTERIOR WALL

DETAILS

DCWWTP OPERATIONS

AND LAB BLDG
May 29, 2024
19six 210015.01
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
311 VERNON ST
ROSEVILLE, CA 95768
90% CD - PERMIT SET
432486
1 NO. DATE DESCRIPTION
2/28/25

BID SET (PRELIMINARY)

FINISH FLOOR

SOLID GRAY FILL REPRESENTS WALL BEHIND
LADDER; CUT OPENING IN GYPSUM BOARD TO

ALLOW ACCESS TO PLATFORM FROM INSIDE
ROOM; OPENING SHALL EXTEND TO UNDERSIDE

OF ROOF DECK ABOVE
CEILING / PLATFORM FRAMING BEYOND; REFER
TO STRUCT. DWGS.

STEEL LADDER STRINGER
ATTACHMENT ANGLE SUPPORT, 3 PAIR

MINIMUM
PLYWOOD PLATFORM; REFER TO STRUCT. DWGS.
4'-0" O.C. MAX. 1'-0"
6"
1" TYPICAL
1'-0"
10 A-7503'-0" MIN. 6"

ACCESS LADDER

ELEVATION
1/2" = 1'-0"
2-1/2"x1/2" CONTINUOUS STEEL FLAT

BAR STRINGER WELDED TO EACH

ANGLE BRACKET

FACE OF WALL
GENERAL NOTES:

1. GRIND ALL EDGES SMOOTH

2. PRIME AND PAINT PER SPECS.
1-1/4" ROUND BAR @ 12" O.C. TYP.;

FULL PERIMETER WELD TO FLAT BAR
8"x4"x1/2" X2" LONG ANGLE-WELD TO
FLAT BAR AT 4'-0" O.C.
5/8" DIA. BOLTS THRU BLOCKING

METAL BACKING TRACK/STUD
7"
1'-6"

ACCESS LADDER

PLAN VIEW
1 1/2" = 1'-0"

WALL ASSEMBLY, SEE

FLOOR PLAN AND WALL

DETAILS FOR MORE

INFORMATION

BACKER ROD AND SEALANT

CONCRETE SLAB

TILE, SEE WALL FINISH

PLAN, ELEVATIONS AND

FINISH LEGEND FOR MORE

DETAILS

SCHULTER SEE SPEC

COVE BASE

CONCRETE TO TILE
3" = 1'-0"
FRP

RADIUS COVE
3/8" MIN

EPOXY FLOORING AND
BASE
4" MIN
Z FLASHING. PAINT TO

MATCH EPOXY
WALL - PER PLAN. SEE
ARCH.

BOTTOM TRIM SET IN SEALANT
STOREFRONT DOOR; REFER TO DOOR

SCHEDULE

ALUMINUM STOREFRONT SYSTEM
FRAME BEYOND, TYP.

CONCRETE
FLATWORK, TYP.

AGGREGATE BASE, TYP.

CONCRETE SLAB, TYP.

EXPANSION JOINT,
REFER TO:

DOOR SWEEP/RAIN GUARD, TYP.; REFER

TO DOOR HARDWARE SPECIFICATIONS
OFFSET SADDLE THRESHOLD, TYP.;

REFER TO DOOR HARDWARE

SPECIFICATIONS

EXTERIOR STOREFRONT DOOR

THRESHOLD AT RECESSED ENTRY MAT
3" = 1'-0"
SLOPE: 1.8% MAX. MAX. 1/2"
MAX.
1/4"

RECESSED

ENTRY MAT,
TYP.; ALIGN T.O.

MAT WITH T.O.

SLAB

THRESHOLD

CARPET TO POLISHED CONCRETE
3" = 1'-0"
3/8" U.N.O.

DOOR, WHERE OCCURS,

SEE SCHEDULE
CARPET

METAL REDUCER
STRIP

POLISHED CONCRETE

CONCRETE SLAB

CHANGE OF FLOORING

UNDER CENTERLINE OF
DOOR

THRESHOLD

CARPET TO VARIOUS RESILIENT FLOORING
3" = 1'-0"
3/8" U.N.O.

DOOR, WHERE OCCURS,

SEE SCHEDULE

DOOR FRAME
CARPET

METAL THRESHOLD
STRIP
V.C.T., A.V.T., V.D.T.,

SHEET VINYL, CORK,

RUBBER, LINOLEUM

CONCRETE SLAB/

RAISED ACCESS

FLOORING

CHANGE OF FLOORING

UNDER CENTERLINE OF
DOOR

DOOR, WHERE OCCURS,

SEE SCHEDULE

DOOR FRAME

THIN SET MANUFACTURED

AGGREGATE TILE

METAL THRESHOLD
STRIP; 1/2" MAX. HT.

POLISHED CONCRETE

CONCRETE SLAB
3/8" U.N.O.
2:1 MAX.

THRESHOLD

THIN SET TILE TO POLISHED CONCRETE
3" = 1'-0"
1/2".

THRESHOLD TRANSITIONS

SOLID POLYMER FABRICATIONS
3"=1'-0"
A. B.

A. B.

MATCH OVERALL DOOR FRAME WIDTH A. B. A. B.

MATCH OVERALL DOOR FRAME WIDTH
MATCH OVERALL DOOR FRAME WIDTH A. B. A. B.

CORK FLOORING

THIN SET TILE

METAL EDGE TRIM
LEVEL

MORTAR SET STONE
METAL EDGE TRIM, TYP.

BOTH SIDES

THIN SET TILE
LEVEL

THIN SET TILE

METAL EDGE TRIM
CARPET
LEVEL
NOTES;
A. 1/4 MAXIMUM HEIGHT SET AT 45 DEGREE ANGLE, TYP.

B. DIMENSION SHALL MATCH INSTALLED HEIGHT OF MATERIAL AND ALLOW FOR INSTALLED HEIGHT OF THRESHOLD TRANSITION SILL.

TILE THIN SET OVER 2 COATS OF

WATERPROOF MEMBRANE W/

FIBERGLASS REINFORCING O/ TILE

BACKER BOARD

CONCRETE CURB, SEE

WATERTIGHT SHOWER PAN MEMBRANE
O/ CONCRETE SLAB. EXTEND UP FACE
OF CURB AND WALL SHEATHING A MIN.

OF 12" AND TIE INTO WALL WATERPROOF

MEMBRANE

REINFORCING SET IN SLURRY

BOND COAT
TILE O/ THIN SET O/ 1 LAYER OF
WATERPROOF MEMBRANE 1 1/2"
HYDROPHILIC WATERSTOP BAR.

SEE NOTE BELOW
NOTE: CONTRACTOR OPTION TO POUR

MONOLITHICALLY W/O WATER STOP
P.T. WOOD NAILER
SET IN CURB, TYP.

T.O. SLAB

SOUND ATTENUATION INSULATION,

WHERE OCCURS PER WALL

SCHEDULE AND PLAN
DILEX-EHKS. STL COVED SCHLUTER
TRIM
MORTAR SET AT SHOWER 3" = 1'-0" FLOOR TRANSITION

CARPET TO POLISHED CONCRETE
3" = 1'-0"
CARPET

METAL REDUCER
STRIP

POLISHED CONCRETE

CONCRETE SLAB

WINDOW SHADE MOUNTING (MOTORIZED)
RECESSED POCKET @ ACOUSTICAL TILE CEILING
3"=1'-0"

BOTTOM OF SOFFIT V
E
RIF
Y
W/ M
F
T
R.

CLR. DEPTH
4"

SUSPENDED ACOUSTICAL
CEILING ASSEMBLY, TYP.
4"X 20 GA. METAL STUD FRAMING
@ 16" O.C.

HATCHED AREA REPRESENTS WALL
ASSEMBLY; REFER TO FLOOR PLANS
AND WALL SCHEDULE.

DASHED LINE REPRESENTS TOP OF
ROUGH WINDOW OPENING; REFER TO

WALL AND WINDOW DETAILS FOR

SPECIFIC ASSEMBLY
CONFIGURATIONS.

SECURE SHADE HOOD W/ (2)
#10 SMS AT EACH STUD

FRAME TYPICAL
WINDOW SYSTEM, WHERE OCCURS;

REFER TO PLANS AND WINDOW
SCHEDULE.

FASTEN JOISTS TO SUSPENDED
WALL FRAMING WITH (4) #10 SMS,

REFER TO STRUCTURAL NOTES

CORNER BEAD
WINDOW SHADE ASSEMBLY, TYP.

ALIGN FACE OF POCKET ROLLER ENCLOSURE W/

FINISH FACE OF CEILING/SOFFIT AND WINDOW

OPENING WHERE OCCURS, COORDINATE WITH
ROLLER SHADE MFGR.

METAL STUD WALL FRAMING, TYP;
SUSPEND FROM DECK SIM. TO:

B.O. CEILING
4"X 20 GA. METAL STUD TRACK
SECURE TRACK W/ (2) #10 SMS AT

EACH STUD TYPICAL SEE STRUCTAL
NOTES

WINDOW SHADE MOUNTING (MOTORIZED)
RECESSED POCKET @ ACOUSTICAL TILE CEILING
3"=1'-0"

BOTTOM OF SOFFIT V
E
RIF
Y
W/ M
F
G
CLR. DEPTH
4"

SUSPENDED ACOUSTICAL
CEILING ASSEMBLY, TYP.
4"X 20 GA. METAL STUD FRAMING
@ 16" O.C.
(E) CONCRETE HEADER

DASHED LINE REPRESENTS TOP OF ROUGH
WINDOW OPENING; REFER TO WALL AND

WINDOW DETAILS FOR SPECIFIC ASSEMBLY
CONFIGURATIONS.

SECURE SHADE HOOD W/ (2) #10

SMS AT EACH STUD FRAME TYPICAL
WINDOW SYSTEM, WHERE OCCURS;

REFER TO PLANS AND WINDOW
SCHEDULE.

FASTEN JOISTS TO SUSPENDED
WALL FRAMING WITH (4) #10 SMS,

REFER TO STRUCTURAL NOTES
WINDOW SHADE ASSEMBLY;
PROVIDE POWER , TYP.

METAL STUD WALL FRAMING, TYP;
SUSPEND FROM DECK SIM. TO:

B.O. CEILING
4"X 20 GA. METAL STUD TRACK

SECURED TO EXISTING WALL
(2) SHOT PINS INTO EXISTING

CONCRETE SEE STRUCTURAL NOTES

CORNER BEAD TYPICAL

WRAP CONCRETE HEADER

WITH GYP BD TYPICAL

CONT BEAD OF SEALANT

WINDOW SHADE

SURFACE MOUNTED TO WALL
3"=1'-0"
T.O. WINDOW OPENING

WINDOW SHADE ASSEMBLY,
REFER TO SPECIFICATIONS.

WALL ASSEMBLY, REFER TO

FLOOR PLANS AND WALL

SCHEDULE

DASHED LINE REPRESENTS TOP
OF ROUGH WINDOW OPENING;

REFER TO WALL AND WINDOW

DETAILS FOR SPECIFIC
ASSEMBLY CONFIGURATIONS.

WINDOW SYSTEM, TYP.; REFER

TO PLANS AND WINDOW
SCHEDULE.

ALIGN BOTTOM OF FASCIA

WITH THE EDGE OF THE

OPENING

FASTEN INTO ---- WITH
(-) ------ FASTENERS @ --- O.C.

LINE OF CEILING, WHERE
OCCURS; REFER TO

REFLECTED CEILING PLAN
WALL MOUNTED TELEVISION 1/2" = 1'-0"
U.N.O. S
E
E IN
T
E
RIO
R
E
L
E
V
A
TIO
N
S
5' - 7 253/256"
CL
CL
FIN. FLR.

MTL STUD WALL FRAMING

SEE PARTITION SCHEDULE

WALL BACKING SHALL

EXTEND FULL WIDTH OF
WALL OR 10'-0" WHICH

EVER IS LESS SEE

INTERIOR ELEVATIONS

TELEVISION BRACKET

TELEVISION

ELECTRICAL / DATA / AV

GANG BOXES AS

REQUIRED SEE
ELECTRICAL DWGS.

WALL FINISH SEE

SCHEDULE

WALL TILE
WALL - PER PLAN. SEE
ARCH.

SCHLUTER-JOLLY PROFILE
(SIZE VARIES PER TILE); FINISH:

STAINLESS STEEL

SEMI-GLOSS PAINT ABOVE
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
7/3/2024 12:48:49 PM C:\Users\kaleksandrov\OneDrive - Williams & Paddon\Documents\210015.01_CITY OF ROSEVILLE_DCWWTP ADMIN BLDG_A22_kaleksandrov4T455.rvt A-750

INTERIOR DETAILS

DCWWTP OPERATIONS

AND LAB BLDG
May 29, 2024
19six 210015.01
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
311 VERNON ST
ROSEVILLE, CA 95768
90% CD - PERMIT SET
11 10
9 FINISH - COVE BASE AT EPOXY 6" = 1'-0" 15
?
1 3
4 5
8 6 2
19 20
18 14
FINISH - TRIM @ TILE 6" = 1'-0" 16
?
NO. DATE DESCRIPTION
2/28/25

BID SET (PRELIMINARY)

WALL LINE

WALL LINE

FIRST BRACING POINT FROM WALL
12 GA. VERTICAL HANGER WIRES AT
4'-0" O.C. AT EACH MAIN RUNNER
4 WAY 45 DEGREE BRACING; USE 12
GA. WIRE AT 12'-0" O.C. x 8'-0" O.C.

CROSS RUNNER

MAIN RUNNER
NOTES

1. ALIGNMENT OF DEVICES IN CEILING

2. T-BAR CEILING NOTES, SEE

TO FIRST BRACE
4'-0" 4'-0" 4'-0" 4'-0" 4'-0" 4'-0"
2'-0" 2'-0" 2'-0" 2'-0" 2'-0" 2'-0" 2'-0"
8" MAX.

TO FIRST BRACE
4'-0"
24'-0"
8" MAX.
4 A-760
2 A-760
6 A-760
A-760
7 6
A-760
11 A-760
9 A-760

DIAGRAMATIC PLAN

AT LAY-IN ACOUSTICAL CEILING
1/4" = 1'-0"

1. NOTES

ALL GAUGES SHALL BE DESIGNED AND

CONFIRMED BY SUSPENDED CEILING
MANUFACTURER.

SLOT END OF TUBE ON MAIN RUNNER
#12 HANGER WIRE -

FASTEN TO STRUCTURE PER

UNDERSIDE OF STRUCTURE
12 A-760

VERTICAL HANGER WIRE

TYPICAL
3" = 1' - 0"

BOTTOM OF STRUCTURE
COMPRESSION STRUT ATTACHMENT W/ (2) #10 SMS
INTO STRUCTURE. 2"x2"x12 GA. ANGLE W/ (2) #10 SMS
AT EA. FLANGE AT EMT TUBING

WIRE ATTACHMENT, REFER TO

SLOT END OF TUBE ON MAIN RUNNER,

ATTACH TO MAIN RUNNER BULB WITH
3/16" DIA. BOLT
12 GAUGE 45 DEGREE SPLAY WIRE

BRACING ATTACHED TO THE MAIN
RUNNER AT 90° ANGLE TO EACH
OTHER AND MAXIMUM 2" DIMENSION

FROM CROSS RUNNER

INTERSECTION
4 TIGHT TURNS IN 1-1/2" TYPICAL

AT SPLAY WIRE CONNECTION TO

MAIN RUNNER

CROSS RUNNER

MAIN RUNNER
12 GAUGE VERTICAL HANGER WIRE
SECURED TO MAIN RUNNER W/ 3 TURNS
IN 1-1/2" AT 4'-0" O.C.

COMPRESSION POST AT INTERSECTION AT
12'-0" O.C. EACH WAY, NOT MORE THAN
6'-0" FROM EA. PERIMETER WALL.

NOTE: COMPRESSION STRUT SHALL NOT REPLACE VERTICAL HANGER WIRE INSTALL 1/4" DIA. BOLT WITH A/C
LOCK NUT THROUGH 9/32" HOLE

IN BOTH TUBES

COMPRESSION STRUT SCHEDULE

HEIGHT NOMINAL
EMT DIA.

AREA (SQ.IN.) RADIUS OF

GYRATION
WALL THICK. (IN) OUTSIDE
DIA. (IN)
UP TO 3'-10" .045 .235 .021 .706
5'-0" .069 .309 .025 .922
6'-6" .096 .391 .027 1.163
8'-6" .151 .511 .033 1.51
9'-10" .174 .604 .033 1.74 12"
45°
12 A-760
1/2"
3/4"
1"
1 1/4"
1 1/2"

COMPRESSION STRUT

AND HANGER/SPLAY WIRES
3" = 1'-0"
T-BAR CEILING NOTES:

1. ALL GAUGES SHALL BE DESIGNED AND

CONFIRMED BY T-BAR MANUFACTURER TO
MEET THE HEAVY DUTY CBC STANDARD.

2. FOR ATTACHMENT TO STRUCTURE, SEE

3. FOR ROOMS WITH SPAN IN EITHER DIRECTION
LESS THAN 25', MAIN RUNNERS AND CROSS

RUNNERS MAY BE ATTACHED TO THE PERMITER
OF TWO ADJACENT WALLS WITH 3/8" CLEARANCE

BETWEEN THE RUNNERS AND THE OTHER TWO
WALLS. WHERE THE SPAN OF THE CEILING
SYSTEM BETWEEN PERIMETER WALLS EXCEED 25'

IN BOTH DIRECTIONS, A MINIMUM WALL ANGLE
SIZE OF AT LEAST 2" HORIZONTAL LEG SHALL BE

USED AT PERIMETER WALLS AND INTERIOR FULL
HEIGHT PARTITION. THE FIRST TILE SHALL BE 3/4"
CLEAR FROM THE WALL SURFACE.

4. THE ENDS OF MAIN RUNNERS AND CROSS
RUNNERS SHALL BE TIED TOGETHER TO PREVENT SPREADING.

5. THE SUSPENDED CEILING GRID MAY BE ATTACHED TO TWO

ADJACENT WALLS, BUT MUST NOT BE ATTACHED AT THE OTHER
TWO WALLS.

T-BAR CEILING NOTES N.T.S.
12 A-760
A. FIXED END
B. FREE END
12 GA. VERTICAL HANGER WIRE AT 4'-0"
O.C. ALONG MAIN RUNNER
#10 S.M.S. AT 16" O.C. INTO STUD OR

BLOCKING
1/8" METAL RIVET WITH STEEL MANDREL
AND 1"x1-1/2"x3/4" WALL ANGLE

POP RIVET

CONTINUOUS WALL MOLDING
#10 S.M.S. AT 16" O.C. INTO STUD OR

BLOCKING

SLOTTED PERIMETER HORIZONTAL
SPACER STRUT WITH HORIZONTAL 6d
RINGSHANK TO PREVENT SPREADING.

SET NAILHEAD TOWARD CENTERLINE
OF SPAN OF SPACER STRUT.

CONTINUOUS WALL MOLDING
NOTES

1. ALL GAUGES SHALL BE DESIGNED
AND CONFIRMED BY T-BAR MANUFACTURER.
12 GA. VERTICAL HANGER WIRE AT 4'-0"
O.C. ALONG MAIN RUNNER
6" MAX.
5/8"

ACT CEILING

AT WALL INTERSECTION
3" = 1' - 0"

FLUSH OR RECESSED FLUORESCENT

LIGHT FIXTURE, AIR TERMINAL OR

ACCESS TERMINAL

T-BAR RUNNER

PROVIDE T-BAR HOLD DOWN AT
EACH CORNER, TYP.

ATTACHMENT TO STRUCTURE

ABOVE, REFER TO

VERTICAL SUPPORT WIRES INSTALLED IN MAIN

RUNNER AT DIAGONAL CORNERS OF SUSPENDED
ITEM. SECURE WITH 3 TIGHT TURNS IN 1-1/2"
12 A-760
SUSPENDED FIXTURE 3" = 1' - 0"
NOTES:

1. FIXTURES AT LESS THAN 56 LBS: INSTALL (2) #12 GA. SAFETY WIRES (SLACK). ONE ON EACH END OF FIXTURE, DIAGONALLY OPPOSED AND CONNECTED TO STRUCTURE ABOVE.

2. FIXTURES AT 56 LBS OR GREATER: INSTALL (4) #12 GA. SUPPORT WIRES (TAUT). ONE ON EACH CORNER OF FIXTURE CONNECTED TO STRUCTURE. WIRES SHALL SUPPORT (4) TIMES THE WEIGHT OF THE FIXTURE.

3. ALL FIXTURES 4'x4' MIN IN SIZE: INSTALL (4) #12 GA. SAFETY WIRES (SLACK) AT EACH CORNER OF THE FIXTURE.

A

AT WOOD FRAMING
12 GA. HANGER WIRE; (4)

TIGHT TURNS OF WIRE IN
1 1/2" MIN. AT STRAP
3"W x 4"L x 12 GA. STEEL STRAP;
"HILTI" TO BEAM WITH #10x1" FASTENERS;

RUN IN DIRECTION OF WIRE

WOOD FRAMING

VERTICAL SPLAYED

CEILING WIRE ATTACHMENT

TO STRUCTURE
3" = 1' - 0"

WOOD JOIST
3"W x 4"L x 12 GA. STEEL STRAP;
"HILTI" TO BEAM WITH #10x1" FASTENERS;

RUN IN DIRECTION OF WIRE
B

AT WOOD JOISTS

VERTICAL SPLAYED
12 GA. HANGER WIRE; (4)

TIGHT TURNS OF WIRE IN
1 1/2" MIN. AT STRAP
F.S.

ROOM WALL OR SOFFIT LINE

ALIGN FIXTURES ALONG CENTERLINES
LIGHT, W.O.

MECHANICAL DIFFUSER, W.O.

FIRE SPRINKLER HEAD, W.O.

LIGHT, W.O.

NOTE:

CLARIFY LOCATIONS WITH ARCHITECT IN FIELD PRIOR TO ROUGH IN.

EQ EQ EQ EQ EQ

CEILING FIXTURE ALIGNMENT

TYPICAL
NTS

VERTICAL HANGER WIRE
2 A-760

CEILING TRANSITION

ACT TO GYPSUM BOARD
1 1/2" = 1'-0"
B.O. CEILING

STAGGER STUDS AROUND STRUCTURE

SUSPENDED ACOUSTICAL CEILING SYSTEM

METAL STUD SOFFIT FRAMING &
DIAGONAL BRACING; REFER TO:

ROOF OR FLOOR DECK, OR STRUCTURE
GYPSUM BD., TYP.

STRAP, BRACE, OR STRONG BACK
WHERE INDICATED; REFER TO:

METAL TRACK STUD FRAMING
CORNER BEAD, TYP.
14 A-760
18 A-760
1 1/2" BUGLE HEAD SCREWS
3/8" PAN HEAD SCREWS
1" BUGLE HEAD SCREWS

SOFFIT & CEILING JOIST/STUD, SEE SIZE NOTES

SOFFIT AND CEILING JOIST SIZES
TYPICAL: (U.N.O.)
-LESS THAN 4'-0" SPAN - 3-5/8" x 1.625" x 20 GA. AT 24" O.C. -4'-1" SPAN TO 12'-0" SPAN - 6" x 1.625" x 20 GA. AT 16" O.C. -12'-1" SPAN TO 18'-0" SPAN - 6" x 1.625" x 18 GA. AT 12" O.C.

RESTROOMS:
-USE 6" x 1.625" x 18 GA. AT 12"O.C.

NOTE: FOR FIXTURE ALIGNMENT, REFER TO DETAIL

WALL FRAMING PER PLAN
11 A-760

JOIST FRAMED GYPSUM BOARD

CEILING AT PARTITION
3" = 1' - 0"

STUD RUNNER CHANNEL

FRAMED GYPSUM BOARD SOFFIT

SECTION
3" = 1' - 0"
METAL STUD 3 5/8" x 20 GA.

AT 24" O.C. U.N.O.
5/8" TYPE "X" GYP. BD.

BOX HEADER
3 5/8" x 1.625" x 20 GA. AT 24" O.C. U.N.O.,

FOR CEILING JOISTS SEE REFLECTED

CEILING PLAN

ANGLE BRACE

AT WOOD STRUCTURE
3"=1'-0"

PARALLEL TO FRAMING MEMBERS

PERPENDICULAR TO FRAMING MEMBERS
2X BLOCKING

NOTCH BLOCKING AS

REQUIRED AT I-JOIST
ATTACH PER STRUCT.
3 5/8" x 20GA. WITH

STRONGBACK STUDS
AT 32" O.C.

WOOD JOIST
3 5/8" x 20GA. WITH

STRONGBACK STUDS
AT 32" O.C.

ATTACH PER STRUCT.
3 5/8" x 20GA. STRONGBACK

AT CLOSE TO MIDSPAN &
NOT MORE THAN 5'-0" O.C.
3 5/8" x 20GA. STRONGBACK

AT CLOSE TO MIDSPAN &
NOT MORE THAN 5'-0" O.C.

VERTICAL BRACE

AT WOOD STRUCTURE
3"=1'-0"

PARALLEL TO FRAMING MEMBERS

PERPENDICULAR TO FRAMING MEMBERS
2X BLOCKING

NOTCH BLOCKING AS

REQUIRED AT I-JOIST
ATTACH PER STRUCT.

I-JOIST WEB STIFFENER
ATTACH PER STRUCT.
3 5/8" x 20GA. METAL STUDS AT 16" O.C.

PROVIDE WALL WITH BRACING AT
FRAMING LONGER THAN 4'-0"
3 5/8" x 20GA. METAL STUDS AT 16" O.C.

PROVIDE WALL WITH BRACING AT
FRAMING LONGER THAN 4'-0"
B
A
B
C
D
E
C
DOUBLE LAYER GYP. BD.

N/A
N/A
1-SPAN
N/A
3'-2"
N/A
3'-5"
3'-8"
4'-3"
2-SPAN
(13 PSF MAX.)
SINGLE LAYER GYP. BD.
2-SPAN
5'-3"
6'-0"
3'-11"
4'-6"
6'-1"4'-6"
7'-0"5'-2"
24 16
(IN. O.C.)

SPACING
24 16
1-SPAN

FURRING

CHANNEL
FC-25
FC-22
(3 PSF MAX.)

ISOMETRIC VIEW

UNLESS OTHERWISE DETAILED

WALL INTERSECTION

CONTROL JOINT - PARALLEL TO FURRING CHANNELS GRILLAGE SUSPENSION

GRILLAGE SUSPENSION - SECTION
8 GA. VERTICAL WIRE
MAIN RUNNER 1 1/2"
COLD ROLLED 16 GA.

CHANNEL @ 3'-0" O.C.

MAX.

METAL FURRING CLIP

CROSS RUNNER HAT
CHANNELS; TIE TO MAIN

RUNNER W/ FURRING

CHANNELS
12 GA. SPLAY WIRE; 4 WAYS
@ 45 DEGREES

JOINT TREATMENT
TYPE "X" GYPSUM BOARD
1 1/2" METAL FURRING CLIP

CROSS RUNNER

METAL FURRING

CHANNEL
TYPE 'X" GYPSUM BOARD
LATERAL FORCE BRACING: RESTRAINING 1 1/2" CHANNELS SPACED AT
12'-0" O.C. MAX, SECURED TO STRUCTURE AS REQUIRED
1 1/2" CHANNEL 3'-0" O.C. MAX.
(MAIN RUNNER)
TYPE 'X' GYP. BD.
8 GA. WIRE HANGER AT 4'-0"
O.C. MAX.
8 GA. WIRE TIES
1 1/2" METAL FURRING

CHANNEL CLIP
1 1/2" FURRING

CHANNEL CLIPS

CONTROL JOINT

JOINT COMPOUND

FLEXIBLE DUST

MEMBRANE

METAL FURRING

CHANNELS

LIMITING SPAN - METAL FURRING CHANNEL MEMBER SCHEDULE
12 4'-11" 6'-7" 4'-0"3'-0"

GENERAL NOTES
INSTALL 16" LENGTH OF TRACK AND FASTEN TO MAIN RUNNER
WITH 2 PAN HEAD SCREWS EACH END OF RUNNER.

INSTALL 6" MIN. LENGTH OF FURRING CHANNEL AND SECURE TO BUTT JOINT OF FURRING CHANNELS WITH WIRE TIES.

1. 2.

A. SPLICE JOINTS

SPACING PER SCHEDULE
7/8"

LAP CHANNELS
2 3/4"
8 GA. VERTICAL WIRE
HANGERS, TYP.
7/8"
6" MAX.

1. MAIN RUNNERS - 1 1/2" COLD ROLLED CHANNELS SPACED AT 3'-0" MAX.

2. LIMITING SPANS FOR 5/8" THICK GYP. BD. MAX. L/360 DEFLECTION PER ASTM C645 AND UNIFORM LOAD SHOWN. INSTALLED CONCENTRATED LOADS SUCH AS LIGHT FIXTURES AND EXHAUST FANS SHALL BE SEPERATELY SUSPENDED.

3. 2 - SPAN INDICATES TWO EQUAL SPANS WITH CHANNELS CONTINUOUS OVER CENTER SUPPORT.

4. DESIGN IN ACCORDANCE WITH THE "METAL STUD MANUFACTURERS ASSOCIATION" (HAT CHANNEL)
SUSPENDED GYPSUM BOARD CEILING 3" = 1'-0"
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
7/3/2024 12:48:53 PM C:\Users\kaleksandrov\OneDrive - Williams & Paddon\Documents\210015.01_CITY OF ROSEVILLE_DCWWTP ADMIN BLDG_A22_kaleksandrov4T455.rvt A-760

CEILING DETAILS

DCWWTP OPERATIONS

AND LAB BLDG
May 29, 2024
19six 210015.01
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
311 VERNON ST
ROSEVILLE, CA 95768
90% CD - PERMIT SET
5 2
4 9
6 7
12 11
10 21
22 18 14
24 NO. DATE DESCRIPTION
2/28/25

BID SET (PRELIMINARY)

BASE CABINET
ANCHORAGE @ FRONT
3" = 1'-0"
wp1.1
TREATED 2x WOOD BASE RIPPED TO SIZE

CABINET PANEL OR DOOR FRONT

BASE AS SCHEDULED
HILTI XC - P POWDER ACTUATED .145" DIA. x
2-7/8" LONG FASTENER (1" MIN PENETRATION)
TREATED 2x WOOD BASE
4"
2 1/2"

UPPER CABINET ANCHORAGE
B.O. CABINET @ WALL
3"=1'-0"
wp1.1
3"
CABINET BOTTOM PANEL; SCRIBE

TO WALL
FASTENERS AT 12" O.C. AND 2" FROM ENDS
TYP; #12 x 3" TEK SCREWS @ METAL STUD
FRAMING AND #10 x 3" WOOD SCREWS WITH
SURFACE BEARING HEAD @ WOOD STUD

FRAMING

PROVIDE BACKING IN WALL AT ATTACHMENT
POINTS; REFER TO:

CABINET BACK PANEL; 1/4" THICK MINIMUM AT
ENCLOSED CABINET AND 1/2" THICK MINIMUM

AT EXPOSED CABINET
@ MTL

FRAMING
@ WOOD

FRAMING
NOTE:

ALL FASTENERS SHALL HAVE A MINIMUM 1-1/2"

PENETRATION INTO WALL STUDS, BLOCKING

OR MASONRY WHERE OCCURS REGARDLESS
OF FASTENERS SHOWN TYPICAL.

COUNTER @ WALL

PLASTIC LAMINATE
3" = 1'-0"
wp1.1

PLASTIC LAMINATE OVER SUBSTRATE

SCRIBE COUNTERTOP TO WALL AND PROVIDE

SEALANT JOINT

PROVIDE BACKING IN WALL AT ATTACHMENT
POINTS; REFER TO:

FASTENERS AT 12" O.C. AND 2" FROM ENDS
TYP; #12 x 3" TEK SCREWS @ METAL STUD
FRAMING AND #10 x 3" WOOD SCREWS WITH
SURFACE BEARING HEAD @ WOOD STUD

FRAMING

BACKSPLASH WHERE OCCURS
7 A-780
@ MTL

FRAMING
@ WOOD

FRAMING
NOTE:

ALL FASTENERS SHALL HAVE A MINIMUM 1-1/2"

PENETRATION INTO WALL STUDS, BLOCKING

OR MASONRY WHERE OCCURS REGARDLESS
OF FASTENERS SHOWN TYPICAL.

COUNTER @ WALL

SOLID SURFACE
3"=1'-0"
wp1.1

SOLID SURFACE OVER SUBSTRATE
SCRIBE COUNTERTOP TO WALL; PROVIDE

SEALANT JOINT WITH COLOR MATCHING

SEALANT

PROVIDE BACKING IN WALL AT ATTACHMENT
POINTS; REFER TO:

FASTENERS AT 12" O.C. AND 2" FROM ENDS
TYP; #12 x 3" TEK SCREWS @ METAL STUD
FRAMING AND #10 x 3" WOOD SCREWS WITH
SURFACE BEARING HEAD @ WOOD STUD

FRAMING
CABINET BACK PANEL; 1/4" THICK MINIMUM AT
ENCLOSED CABINET AND 1/2" THICK MINIMUM

AT EXPOSED CABINET

BACKSPLASH, WHERE OCCURS
7 A-780
@ MTL

FRAMING
@ WOOD

FRAMING
NOTE:

ALL FASTENERS SHALL HAVE A MINIMUM 1-1/2"

PENETRATION INTO WALL STUDS, BLOCKING

OR MASONRY WHERE OCCURS REGARDLESS
OF FASTENERS SHOWN TYPICAL.

BACKSPLASH PROFILES 6" = 1'-0"
wpv1.1

TOP OF BACKSPLASH

BACKSPLASH TRANSITION TO COUNTER
A. SQUARE B. HALF BULLNOSE
EASED EDGE;
1/8" RADIUS MAX.

RADIUS = 1/2 MATERIAL

THICKNESS
RADIUS = MATERIAL

THICKNESS

BACKSPLASH SITS ON TOP

OF COUNTER
C. SQUARE D. COVED

BASE CABINET
ANCHORAGE @ WALL
3" = 1'-0"
wp1.1
PROVIDE BACKING IN WALL @ ATTACHMENT
POINTS; REFER TO:

FASTENERS AT 12" O.C. AND 2" FROM ENDS
TYP; #12 x 3" TEK SCREWS @ METAL STUD
FRAMING AND #10 x 3" WOOD SCREWS WITH
SURFACE BEARING HEAD @ WOOD STUD

FRAMING
2x TREATED WOOD BASE RIPPED TO SIZE
TREATED 2X WOOD BASE 1 3/4"
CABINET BACK PANEL; 1/4" THICK MINIMUM AT
ENCLOSED CABINET AND 1/2" THICK MINIMUM

AT EXPOSED CABINET
@ MTL

FRAMING
@ WOOD

FRAMING

HILTI XC - P POWDER
ACTUATED .145" DIA. x 2-7/8" LONG
FASTENER (1" MIN PENETRATION)
NOTE:

ALL FASTENERS SHALL HAVE A MINIMUM 1-1/2"

PENETRATION INTO WALL STUDS, BLOCKING

OR MASONRY WHERE OCCURS REGARDLESS
OF FASTENERS SHOWN TYPICAL.

UPPER CABINET ANCHORAGE
T.O. CABINET @ WALL
3"=1'-0"
wp1.1
3"

PROVIDE BACKING IN WALL AT ATTACHMENT
POINTS; REFER TO:

FASTENERS AT 12" O.C. AND 2" FROM ENDS
TYP; #12 x 3" TEK SCREWS @ METAL STUD
FRAMING AND #10 x 3" WOOD SCREWS WITH
SURFACE BEARING HEAD @ WOOD STUD

FRAMING

CABINET TOP PANEL
CABINET BACK. 1/4" MIN AT ENCLOSED
CABINET AND 1/2" MIN AT EXPOSED CABINET
@ MTL

FRAMING
@ WOOD

FRAMING
NOTE:

ALL FASTENERS SHALL HAVE A MINIMUM 1-1/2"

PENETRATION INTO WALL STUDS, BLOCKING

OR MASONRY WHERE OCCURS REGARDLESS
OF FASTENERS SHOWN TYPICAL.

BASE TO UPPER CAB ANCHORAGE
FULL HEIGHT CAB @ WALL
3"=1'-0"
wp1.1

PROVIDE BACKING IN WALL AT ATTACHMENT
POINTS; REFER TO:

FASTENERS AT 12" O.C. AND 2" FROM ENDS
TYP; #12 x 3" TEK SCREWS @ METAL STUD
FRAMING AND #10 x 3" WOOD SCREWS WITH
SURFACE BEARING HEAD @ WOOD STUD

FRAMING
COUNTER, OR EXPOSED SHELF, TYP.; REFER

TO INTERIOR ELEVATIONS
@ MTL

FRAMING
@ WOOD

FRAMING
CABINET BACK PANEL; 1/4" THICK MINIMUM AT
ENCLOSED CABINET AND 1/2" THICK MINIMUM

AT EXPOSED CABINET
3 1/4" 4 1/4"
NOTE:

ALL FASTENERS SHALL HAVE A MINIMUM 1-1/2"

PENETRATION INTO WALL STUDS, BLOCKING

OR MASONRY WHERE OCCURS REGARDLESS
OF FASTENERS SHOWN TYPICAL.

UPPER CABINET
T.O. CABINET
3"=1'-0"
wp1.1

CEILING / SOFFIT, WHERE OCCURS

CABINET DOOR

INTERIOR CABINET PANEL SECURED TO
BLOCKING 3/4"
1x SHIM SECURE TO BLOCKING WHERE

CEILING OCCURS
CEILING BLOCKING, TYP. @ CEILINGS WHERE

UPPER CABINETS ABUT CEILING

FINISH FACE AT SHIM

ALTERNATE BLOCKING AT CEILING

UPPER CABINET
T.O. CABINET @ INFILL TO CEILING/SOFFIT
3"=1'-0"
wp1.1

CABINET DOOR

INTERIOR CABINET PANEL

SECURED TO BLOCKING
3/4"
3/4"
CEILING OR SOFFIT, TYP.

CEILING BLOCKING
1x SHIM SECURE TO BLOCKING

FINISH FACE, TYPICAL

INFILL PANEL

UPPER CABINET
B.O. CABINET @ VALANCE
3"=1'-0"
wp1.1

CABINET PANEL

UNDERCOUNTER LED STRIP LIGHT, WHERE
OCCURS; REFER TO ELECTRICAL DWGS
1x NAILER, WHERE OCCURS @ VALANCE;

FINISH ALL EXPOSESD AND SEMI-EXPOSED
FACES
VALANCE, WHERE OCCURS; FINISH ALL FACES

BASE AND UPPER CABINET

FILLER PANEL TO WALL (PLAN VIEW)
3"=1'-0"
wp1.1

FILLER PANEL SCRIBE TO WALL AND PROVIDE

SEALANT JOINT

CABINET PANELS

WALL FINISH

TYPICAL CASEWORK SECTION

BASE AND UPPER CABINET
1" = 1'-0"
wp1.1
COUNTERTOP TYP., REFER TO

INTERIOR ELEVATIONS FOR
MATERIAL. PROVIDE

BACKSPLASH WHERE NOTED ON
THE INTERIOR ELEVATIONS.

CABINET PULL, REFER TO

CASEWORK SPECIFICATIONS
FULLY ADJUSTABLE SHELVES (2
MIN. EACH CABINET U.O.N.)

RECESSED ADJUSTABLE SHELF

STANDARDS
DRAWER, WHERE OCCURS;

PROVIDE FULL EXTENSION SLIDES

AND CENTER PULL ON DRAWER
FACE. REFER TO INTERIOR

ELEVATIONS FOR BASE CABINET
CONFIGURATION.
24" UON

FINISH FLOOR
FULLY ADJUSTABLE SHELVES (2
MIN. EACH CABINET UON)

RECESSED ADJUSTABLE SHELF

STANDARDS

CABINET PULL, REFER TO

CASEWORK SPECIFICATIONS
UON
12" INSIDE CLR
A-780

10. A-780
19 A-780
18 A-780
8 A-780
5,
DOOR, WHERE OCCURS; REFER

TO INTERIOR ELEVATIONS FOR
BASE CABINET CONFIGURATION.

INFILL PANEL OR CROWN
MOULDING, WHERE OCCURS;

REFER TO INTERIOR ELEVATIONS

CEILING OR SOFFIT, WHERE
OCCURS

VALANCE AND UNDER COUNTER

LIGHTING, WHERE OCCURS
A-780
15 14
A-780
-
---
TYP. @ INFILL
PANEL
@ CROWN

MOULDING
A-780
12 REFER TO INT. ELEV.

REFER TO INT. ELEV.

REFER TO INT. ELEV.
@ P-LAM

9. A-780
@ SOLID
SURF.

REFER TO INT. ELEV.

BASE CABINET, WHERE OCCURS
HEIGHT TO B.O. UPPER CABINET; REFER TO INT. ELEV.

REFER TO INT. ELEV.

UPPER CABINET, WHERE OCCURS

FAUCET SHOWN FOR REFERENCE

ONLY (WHERE OCCURS)
COUNTERTOP, TYP.; REFER TO

INTERIOR ELEVATIONS AND INTERIOR

FINISH LEGEND FOR ADDITIONAL

INFORMATION

PROVIDE PROTECTIVE WRAP,
SEE

ADA CLEARANCE SEE
19" MAX.

CABINET PULL, SEE CASEWORK
SPECS
SINK
@ BASE CABINET
1"=1'-0"
wp1.1

FINISH FLOOR

SEE ELEVATION
34" UON
A-780
4 3"
24" UON
1 1/2"

PLASTIC LAMINATE DOOR, PER ELEVATION

INTEGRAL TOE KICK
DOORS @ BASE CABINET WITH DOORS
3" = 1'-0"
wp1.1
2 1/2"
1/2"
4"

SUPPORT CLIP

SCREW / DOWEL PER WI STANDARD

FINISH FLOOR

EXTERIOR STOREFRONT

QUARTZ COUNTERTOP

OVER PLYWOOD

QUARTZ WATERFALL EDGE
BEYOND 3
4" U
O
N
2" 1' - 4"
1/4" x 4" x10" MOUNTING

PLATE WELDED TO THE TOP

PROVIDE CONCEALED C/EC
FLAT BRACKET 12"

SUPPORT ARM

FLOOR FINISH
1/4" X 5" X 5" SECURING

PLATE W/ MOUNTING HOLES

IS WELDED TO THE BOTTOM
2" X 2" X 1/8" TUBE STEEL;

ALIGN W/ STOREFRONT
MULLION. PAINT ALL SIDES TO

MATCH STOREFRONT
2" TYP

COUNTERTOP
@ BREAK ROOM STOREFRONT
1"=1'-0"
1 QUARTZ WATERFALL

EDGE, ADHESIVE
ATTACHED; WRAP ALL
SIDES
2"
3/4" CABINET GRADE

PLYWOOD (BALTIC BIRCH
OR EQ)

FINISH FLOOR
WATERFALL EDGE BRACING 3"=1'-0"
3/4" CABINET GRADE

PLYWOOD (BALTIC BIRCH
OR EQ)
2 CM QUARTZ

COUNTERTOP WATERFALL

EDGE , ADHESIVE
ATTACHED; WRAP ALL
SIDES
2"

CASEWORK
BELOW W.O.

SEE FLOOR PLAN

QUARTZ COUNTER ABOVE

WATERFALL EDGE
@ QUARTZ
3" = 1'-0"
COUNTERTOP TYP., REFER TO

INTERIOR ELEVATIONS FOR
MATERIAL. PROVIDE

BACKSPLASH WHERE NOTED ON
THE INTERIOR ELEVATIONS.

CABINET PULL, REFER TO

CASEWORK SPECIFICATIONS
FULLY ADJUSTABLE SHELVES (2
MIN. EACH CABINET U.O.N.)

RECESSED ADJUSTABLE SHELF

STANDARDS
DRAWER, WHERE OCCURS;

PROVIDE FULL EXTENSION SLIDES

AND CENTER PULL ON DRAWER
FACE. REFER TO INTERIOR

ELEVATIONS FOR BASE CABINET
CONFIGURATION.

FINISH FLOOR
A-780

10. A-780
8 A-780
5,
DOOR, WHERE OCCURS; REFER

TO INTERIOR ELEVATIONS FOR
BASE CABINET CONFIGURATION.

REFER TO INT. ELEV.
4" 2'-0"
CLR
1'-7"
1' - 0"

PLAM OVER PLYWOOD

QUARTZ WATERFALL

EDGE BEYOND

SEE FLOOR PLAN
TYP
2"
12" CONCEALED

COUNTERTOP FLAT

BRACKET BY A&M
HARDWARE, AT 24"
O.C. MAX

BASE AS SCHEDULED

FLOOR FINISH

CANTELEVERED COUNTERTOP
@ KITCHEN
1"=1'-0"

SOLID SURFACE TOP O/
5/8" PLYWD SUBTOP -FINISH

BOTTOM W/ LAMINATE TO MATCH

CABINET PULL, REFER TO

CASEWORK SPECIFICATIONS
FULLY ADJUSTABLE SHELVES (2
MIN. EACH CABINET U.O.N.)

RECESSED ADJUSTABLE SHELF

STANDARDS
DRAWER, WHERE OCCURS;

PROVIDE FULL EXTENSION SLIDES

AND CENTER PULL ON DRAWER
FACE. REFER TO INTERIOR

ELEVATIONS FOR BASE CABINET
CONFIGURATION.

A-780
8 A-780
5,
DOOR, WHERE OCCURS; REFER

TO INTERIOR ELEVATIONS FOR
BASE CABINET CONFIGURATION.

REFER TO INT. ELEV.
4" 2'-0"
CLR
5"

PLAM OVER PLYWOOD

SEE FLOOR PLAN
TYP
2"
QUARTZ

VERTICAL PANEL

BASE AS SCHEDULED

FLOOR FINISH
3'-6"
1'-2 1/8"
PROVIDE 1 1/2" GROMMET. V.I.F.

CLR
10"
1/4" TEMPERED GLASS
CRL Z806BN BRUSHED NICKEL ZSERIES SQUARE TYPE FLAT BASE ZINC CLAMP FOR 1/4" # Z806BN, TYP

RECEPTION DESK
SECTION 1
1"=1'-0"
2" WIDE "L" ANGLED

BRACKET
2"
1/2" PLYWOOD

SOLID SURFACE WRAP O/
PLYWD
1"

CRL BRUSHED STAINLESS
STEEL 36" TALL ROUND

END POST KIT W/ CLAMPS
#PS36EBS
1"
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/2
0/2
0 2
4 11:2
4:2
8 A
M
C:\U
s
ers\k
ale
k
s
a
n
dro
v\O
n
e
Driv
e - Willia
m
s
&
P
a
d
d
o
n\D
o
c
u
m
e
nts\210
015.01_
CIT
Y
O
F
R
O
S
E
VIL
L
E
_
D
C
W
W
T
P
A
D
MIN
B
L
D
G
_A
2 2
_
k
ale
k
s
a
n
dro
v
4 T
4 5

5.rvt
A-780

CASEWORK DETAILS

DCWWTP OPERATIONS

AND LAB BLDG
May 29, 2024
210015.0119six
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
311 VERNON ST
ROSEVILLE, CA 95768
90% CD - PERMIT SET
5,
18 10.

9. 7
8 20 19 15
14 12

11. 2
3 16 4
17 24
23 13.
3" = 1'-0"
?
SOLID SURFACE CORNER 6
NO. DATE DESCRIPTION
1 8/28/24 PC Comments
2/28/25

BID SET (PRELIMINARY)

DOOR PULL TYPICAL, REFER

TO CASEWORK SPECS

FULLY ADJUSTABLE

SHELVES
(2 MIN. EACH CABINET
U.O.N.)

NUMBER OF SHELVES PER

ELEVATION

RECESSED ADJUSTABLE

SHELF STANDARDS

DATUM HEIGHT

COUNTERTOP

OUTLET FOR MICROWAVE

OPEN FOR MICROWAVE

OUTLET FOR MICROWAVE

OPEN FOR MICROWAVE
EXPOSED F.O. CASEWORK
BEYOND; MATERIAL, FINISH

AND COLOR SHALL MATCH

ADJACENT CASEWORK
3"
2' - 10"

VERIFY W/ MFG
1' - 4" 1 1/2"

VERIFY W/ MFG
1' - 4" SEE INTERIOR ELEVATIONS

MICROWAVE STORAGE CABINET
1-1/2" = 1'-0"

DOOR PULLS, REFER TO

CASEWORK SPECIFICATIONS
CA
H
G
K

FAUCET SHOWN FOR REFERENCE

ONLY (WHERE OCCURS)

SOLID SURFACE COUNTERTOP

PROVIDE PROTECTIVE

WRAP, SEE

ADA CLEARANCE, SEE

SINK AT SOLID SURFACE COUNTER

OPEN BELOW
1"=1'-0"
wp1.0

FINISH FLOOR
19" MAX

SEE ELEVATION
34" UON
5"
2' - 0"

PORCELAIN TILE

PORCELAIN TILE

FULLY ADJUSTABLE SHELVES
(2 MIN. EACH CABINET UON)

WRAP ALL SIDES W/ PLAM

RECESSED ADJUSTABLE

SHELF STANDARDS

FINISH CEILING HEIGHT OR

SOFFIT, (WHERE OCCURS)

REFER TO CEILING PLANS

FULL HEIGHT STORAGE

DOUBLE PAIR DOOR
1" = 1'-0"

FINISH FLOOR
A-780
5,
A-780 8
A-780 8
UON
EQ
UON
EQ

FIXED SHELF
1' - 5"

OPEN SHELVING

CASEWORK SECTION
1"=1'-0"
wp1.0

RECESSED LIGHT FIXTURE
WHERE OCCURS. REFER TO
ELEC. DWGS

FINISH CEILING HEIGHT OR
SOFFIT, WHERE OCCURS;

REFER TO CEILING PLANS

FULLY ADJUSTABLE SHELVES
(3 MIN. EACH CABINET UON);

WRAP ALL SIDES W/ PLAM

RECESSED ADJUSTABLE

SHELF STANDARDS

COUNTER TOP TO MATCH
ADJACENT UON. SEE

ELEVATIONS

FULLY ADJUSTABLE SHELVES
(2 MIN. EACH CABINET UON)

WRAP ALL SIDES W/ PLAM

RECESSED ADJUSTABLE

SHELF STANDARDS
24" UON

SEE ELEVATION
A-780 8
A-780
5,
ACOUSTICAL PANEL; SP4

PLASTIC LAMINATE

COUNTERTOP

CABINET PULL, SEE

CASEWORK SPECS

TRASH/RECYCLE CABINET

WITH TOE KICK
1"=1'-0"
wp1.0

FINISH FLOOR
A-780 4
A-780
19 3"

COUNTER OPENING WITH

METAL GROMMET -
MOCKETT TM2C-SSS

RECEPTACLE, BY OTHERS

SEE ELEVATION
34" UON
24" UON
1 1/2"

PLASTIC LAMINATE

CABINET DOOR
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP
REVISIONS #

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
7/5/2024 11:14:49 AM C:\Users\kaleksandrov\OneDrive - Williams & Paddon\Documents\210015.01_CITY OF ROSEVILLE_DCWWTP ADMIN BLDG_A22_kaleksandrov4T455.rvt A-781

CASEWORK DETAILS

DCWWTP OPERATIONS

AND LAB BLDG
May 29, 2024
19six 210015.01
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
311 VERNON ST
ROSEVILLE, CA 95768
90% CD - PERMIT SET
31 45
2 NO. DATE DESCRIPTION
2/28/25

BID SET (PRELIMINARY)

SECTION A-A
A

1. Wall Assembly — The 1 or 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features:

A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.

B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 ft (122 cm) wide, with square or tapered edges. Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Max diam of opening is 8 in. (203 mm). • The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. The hourly T Rating of the firestop system is 1 hr for 2 hr fire rated walls and 0 hr for 1 hr fire rated walls.

2. Through Penetrant — One metallic pipe or tube to be installed eccentrically or concentrically within the firestop system. Pipe or tube to be rigidly supported on both sides of the wall assembly. The following types and sizes of metallic pipes and tubes may be used:

A. Steel Pipe — Nom 4 in. (102 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe.

B. Iron Pipe — Nom 4 in. (102 mm) diam (or smaller) cast or ductile iron pipe.

C. Copper Pipe — Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe.

D. Copper Tube — Nom 4 in. (102 mm) diam (or smaller) Type L (or heavier) copper tube.

3. Pipe Covering* — Nom 1-1/2 in. (38 mm) thick hollow cylindrical heavy density (3.5 pcf or 24 kg/m3) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory-applied self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product. The annular space between the insulated pipe and the periphery of the opening shall be min 0 in. (point contact) to max 7/8 in. (22 mm). • See Pipe Equipment Covering — Materials— (BRGU) Category in the Building Materials Directory for names of manufacturers. Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less may be used.

4. Fill, Void or Cavity Material* — Sealant — Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of wall assembly. At point contact location, min 1/2 in. (13 mm) diam bead of fill material applied at insulated metallic pipe/wall interface on both surfaces of wall. L Ratings apply only when FS-One Sealant is used. • HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant, CP 606 Sealant or CP 601S Sealant *Bearing the UL Classification Mark
A
F RATING - 1 and 2 Hr (See Item 1)
T RATING - 0 and 1 Hr (See Item 1)
L RATING AT AMBIENT - 4 CFM/Sq Ft (See Item 4)
L RATING AT 400F - Less Than 1 CFM/Sq Ft (See Item 4)
System No. W-L-5257
2342
1A
4 1B4
3B

SECTION A-A
AA

1. Wall Assembly — Min 55/8 in. (143 mm) reinforced lightweight or normal weight (100150 pcf or 1600 2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Opening in wall to be 2-1/2 in. (64 mm) diam for nominal 2 in. (51 mm) firestop device and 4 1/2 in. (114 mm) diam for nominal 4 in. (102 mm) firestop device. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.

2. Through Penetrant — One metallic pipe, conduit or tubing to be installed concentrically within the firestop system. Pipe, conduit or tubing to be rigidly supported on both sides of the wall assembly. The following types and sizes of metallic pipes, conduits and tubes may be used:

A. Steel Pipe — Nom 3 in. (76 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe.

B. Iron Pipe — Nom 3 in. (76 mm) diam (or smaller) cast or ductile iron pipe.

C. Conduit — Nom 3 in. (76 mm) diam (or smaller) rigid steel conduit or steel electrical metallic tubing (EMT).

3. Firestop Device* — Firestop device consists of a corrugated steel tube with an inner plastic housing, intumescent material rings, tightly twisted inner fabric smoke seal, flanges and gasketing material (not shown). Firestop device to be installed in accordance with the accompanying installation instructions. Device slid into wall such that ends project an equal distance from the approximate centerline of the wall assembly. The annular space between the device and the periphery of the opening shall be min 0 in. (point contact). Device provided with flanges that are spun clockwise onto device threads, over gasketing material butting tightly to both sides of wall. As an alternate to gasket material, sealant (Item 4) maybe used.
• HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 653 2" Speed Sleeve and CP 653 4" Speed Sleeve

4. Fill, Void or Cavity Material* Sealant — As an alternate to gasket material (see Item 3), min ½ in. (13 mm) thickness of fill material applied within the annulus between firestop device and wall, flush with both surfaces of wall. An additional 1/4 in. (6 mm) bead shall be applied around periphery of device on each side of wall prior to securing device flanges. • HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 606 or FSONE Sealant or FSONE MAX Intumescent Sealant. * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

F RATING - 2 Hr
T RATING - 3/4 Hr
System No. W-J-1215 32 43
1 1. Wall Assembly — The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:

A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 in. (51 mm) by 4 in. (102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.

B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 ft (1219 cm) wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition Design. Opening may be round, rectangular or irregular with a max diam or dimension of 1 in. (25 mm), or round with a max diam of 1-1/8 in. (29 mm). • The hourly F, FH, FT and FTH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed.

2. Through Penetrant — Max one metallic pipe, tubing or conduit installed either concentrically or eccentrically within the firestop system. The annular space between penetrant and periphery of the opening shall be min 0 in. (point contact). When opening dimension exceeds 1 in. (25 mm), the max annular space is 3/8 in. (9.5 mm). Pipe or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of pipes, tubing or conduit may be used:

A. Steel Pipe — Nom 3/4 in. (19 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe.

B. Iron Pipe — Nom 3/4 in. (19 mm) diam (or smaller) cast or ductile iron pipe.

C. Copper Tubing — Nom 1/2 in. (13 mm) diam (or smaller) Type L and Type K (or heavier) copper tubing.

D. Copper Pipe — Nom 1/2 in. (13 mm) diam (or smaller) Regular (or heavier) copper pipe.

E. Conduit — Nom 3/4 in. (19 mm) diam (or smaller) rigid or flexible steel conduit.

F. Conduit — Nom 3/4 in. (19 mm) diam (or smaller) electrical metallic tubing (EMT).

3. Fill, Void or Cavity Material* — Nom 60 mm diam by 3 mm thick putty disc with one seam at radius. Paper-backer of disc to be removed and disc firmly pressed around the penetrant lapping nom 5 mm onto penetrant to completely cover opening and firmly pressed to lap onto the wall around periphery of opening. Disc seam to be firmly pressed and sealed tight, Disc to be installed at both surfaces of wall. • HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CFS-D 1" Firestop Cable Disc * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

F RATING - 1 and 2 Hr (See Item 1)
T RATING - 1 and 2 HR (See Item 1)
L RATING AT AMBIENT - Less than 1 CFM/Opening
L RATING AT 400F - Less than 1 CFM/Opening
System No. W-L-1506 23 23
1B
1A
A

SECTION A-A

1. Wall Assembly -- The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features.

A. Studs -- The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features.

B. Gypsum Board*- -- Nom 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the Fire Resistance Directory.

Max diam of opening is 5 in.
• The hourly F and T Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed.

2. Through Penetrant -- One metallic pipe, conduit or tubing installed concentrically or eccentrically within the firestop system. Pipe, conduit or tubing may be installed at an angle not greater than 45 degrees from perpendicular. Pipe, conduit or tube to be rigidly supported on both sides of wall assembly. The annular space between the pipe or tube and periphery of the opening shall be min 0 in (point contact) to max 1/2 in. The following types and sizes of metallic pipes, conduit or tube may be used:

A. Steel Pipe -- Nom 4 in. diam (or smaller) Schedule 40 (or heavier) steel pipe.

B. Iron Pipe -- Nom 4 in. diam (or smaller) cast or ductile iron pipe.

C. Conduit -- Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT) or steel conduit.

D. Copper Tube -- Nom 4 in. diam (or smaller) Type L (or heavier) copper tube.

E. Copper Pipe -- Nom 4 in. diam (or smaller) Regular (or heavier) copper pipe.

3. Fill, Void or Cavity Material*-Sealant -- Min 5/8 in. thickness of fill material applied within the annulus, flush with both surfaces of wall. At the point contact location between pipe and wall, a min ½ in diam bead of fill material shall be applied at the pipe/wall interface. • HILTI CONSTRUCTION CHEMCIALS, DIV OF HILTI INC -- CP606 Flexible Firestop Sealant *Bearing the UL Classification Mark A
F RATING - 1 and 2 Hr (See Item 1)
T RATING - 0 Hr
L RATING AT AMBIENT - Less than 1 CFM/sq ft
L RATING AT 400F - Less than 1 CFM/sq ft
System No. W-L-1290 1
33 2

SECTION A-A
A
A

1. Wall Assembly — The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:

A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.

B. Gypsum Board* — One or two layers of nom 5/8 in. (16 mm) thick gypsum board as specified in the individual Wall and Partition Design.

Max diam of opening is 5 in. (127 mm).
• The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly.

2. Through penetrants — One metallic pipe or conduit to be installed either concentrically or eccentrically within the firestop system. The annular space shall be 0 in. (point contact) to 1 in. (25 mm). Pipe or conduit to be rigidly supported on the penetrated side of the wall assembly. The following types and sizes of metallic pipes or conduits may be used:

A. Steel pipe — Nom 3 in. (76 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe.

B. Conduit — Nom 3 in. (76 mm) diam (or smaller) steel electrical metallic tubing (EMT), nom 3 in. (76 mm) diam steel conduit or nom 1 in. (25 mm) diam (or smaller) flexible steel conduit.

C. Copper Tubing — Nom 1 in. (25 mm) diam (or smaller) Type L (or heavier) copper tubing.

D. Copper Pipe — Nom 1 in. (25 mm) diam (or smaller) Regular (or heavier) copper pipe.

3. Fill, Void or Cavity Material++— Sealant — Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with surface of wall. Min 1/2 in. (13 mm) diam bead of sealant applied at point contact location. • HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant, FS-ONE MAX Intumescent Sealant, CFS-S-SIL GG Sealant, CP601S Elastomeric Sealant, CP 606 Sealant,or CP618 Putty. ++ Bearing the UL Classification Mark
ANSI/UL 1479 (ASTM E814)
F RATING - 1 and 2 HR (See Item 1)
T RATING - 0 Hr
System No. W-L-1410
323
331
2 AA
3 2
1 1. Wall Assembly — Min 3-3/4 in. and 5 in. (95 and 127 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete for 1 and 2 h rated assemblies, respectively. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of openingis 32-1/4 in. (819 mm).is 32-1/4 in. (819 mm).See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.

2. Through—Penetrants — One metallic pipe, conduit or tubing to be centered within the firestop system. The annular space shall be min 0 in. to max 2-1/4 in. (57 mm). Pipe may be installed with continuous point contact. Pipe, conduit or tube may be installed at an an angle not greater than 45 degrees from perpendicular. Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:

A. Steel Pipe — Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.

B. Iron Pipe — Nom 30 in. (762 mm) diam (or smaller) cast or ductile iron pipe.

C. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing or 6 in. (152 mm) diam (or smaller) steel conduit.

D. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing.

E. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.

3. Fill, Void or Cavity Material* — Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces of wall. At the point or continuous contact locations between pipe and wall, a min 1/2 in. (13 mm) diam bead of fill material shall be applied at the pipe-wall interface on both surfaces of wall. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-One Sealant or FS-ONE MAX Intumescent Sealant
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

ANSI/UL 1479 (ASTM E814)
F RATING - 1 and 2 Hr (See Items 1 and 3)
T RATING - 0 Hr
L RATING AT AMBIENT - Less than 1 CFM/sq ft
L RATING AT 400F - Less than 1 CFM/sq ft
System No. W-L-1065

SECTION A-A
AA

1. Wall Assembly — The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:

A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.

B. Gypsum Board* — One or two layers of nom 5/8 in. (16 mm) thick gypsum board as specified in the individual Wall and Partition Design.

Max diam of opening is 5 in. (127 mm).
• The hourly F, T, FT, FH and FTH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed.

2. Metallic Penetrant - One metallic pipe, conduit or tube to be installed either concentrically or eccentrically, penetrating wall assembly on one side of wall. The annular space between the pipe, conduit or tubing and the periphery of opening shall be min 0 in. (point contact) to max 7/8 in. (22 mm). Pipe, conduit or tubing shall be rigidly supported within the wall and on the penetrated side of the wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:

A. Steel Pipe - Nom 3 in. (76 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe.

B. Iron Pipe - Nom 3 in. (76 mm) diam (or smaller) cast or ductile iron pipe.

C. Conduit - Nom 3 in. (76 mm) diam (or smaller) steel electrical metallic tubing (EMT), nom 3 in. (76 mm) diam steel conduit or nom 1 in. (25 mm) diam (or smaller) flexible steel conduit.

D. Copper Tubing - Nom 1 in. (25 mm) diam (or smaller) Type L (or heavier) copper tubing.

E. Copper Pipe - Nom 1 in. (25 mm) diam (or smaller) Regular (or heavier) copper pipe.

3. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with surfaceof wall assembly.

At point contact location, min 3/8 in. (10 mm) diam bead of fill material to be applied at the penetrant/gypsum board interface.

SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

ANSI/UL 1479 (ASTM E814)
F RATING - 1 and 2 Hr (See Item 1)
T RATING - 1 and 2 Hr (See Item 1)
L RATING AT AMBIENT - Less than 1 CFM/sq ft
L RATING AT 400F - Less than 1 CFM/sq ft
System No. W-L-1527
23 23
1B3
1A
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP
REVISIONS #

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/20/2024 11:24:31 AM C:\Users\kaleksandrov\OneDrive - Williams & Paddon\Documents\210015.01_CITY OF ROSEVILLE_DCWWTP ADMIN BLDG_A22_kaleksandrov4T455.rvt A-790

FIRESTOPPING

PENETRATIONS -

HORIZONTAL PIPES

DCWWTP OPERATIONS

AND LAB BLDG
May 29, 2024
210015.01Author
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
311 VERNON ST
ROSEVILLE, CA 95768
90% CD - PERMIT SET
W-L-5257: PIPE @ WALL ASSEMBLY N.T.S.
6 21.12.14 - 00000
W-J-1215: PIPE @ CONC WALL N.T.S.
8 21.12.14 - 00000
W-L-1506: PIPE @ WALL ASSEMBLY N.T.S.
4 21.12.14 - 00000
W-L-1290: PIPE @ WALL ASSEMBLY N.T.S.
5 21.12.14 - 00000
W-L-1410: PIPE @ MEMBRANE N.T.S.
1 21.12.14 - 00000
W-L-1065: PIPE @ CONC WALL N.T.S.
2 21.12.14 - 00000
W-L-1527: PIPE @ MEMBRANE N.T.S.
3 21.12.14 - 00000
NO. DATE DESCRIPTION
1 8/28/24 PC Comments
1 2/28/25

BID SET (PRELIMINARY)
Firestop
Device
L Rating, CFM/sq ft (CFM/firestop device)
Ambient 400F
Smooth Sleeve 22 (2) 18 (2)
Threaded Sleeve 22 (2) 18 (2)
Split Sleeve 54 (5) 47 (4)

SECTION A-A
A
A

1. Wall Assembly — The 1 or 2 hr fire rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:

A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in. wide and spaced max 24 in. OC.

B. Gypsum Board* — 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 4-1/2 in.

The hourly F rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed.

2. Cables — Aggregate cross-sectional area of cables in steel sleeve to be 45 percent of the aggregate cross-sectional area of the sleeve.

Cables to be rigidly supported on both sides of wall assembly. Any combination of the following types and sizes of copper conductor cable may be used:

A. Max 300 kcmil single conductor Type MTW, THHN, THWN or AWM power cables; cross-linked polyethylene (XLPE) insulation.

B. Max 4 pair No. 24 AWG telephone cable intended for plenum applications.

C. Max 3/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket.

3. Firestop System — The firestop system shall consist of the following:

A. Fill, Void or Cavity Material* — Sealant — (not shown) — Min 1/2 in. diam of sealant shall be applied around the perimeter of the firestop device on each side of the wall.

HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC — FS-ONE Sealant
B. Firestop Device* — One of the following firestop devices may be used:

1. Smooth steel sleeve device incorporating flat washers secured by sliding compression couplers. Device shall be installed in accordance with the accompanying installation instructions.

Device provided in nom 1, 2 and 4 in. sizes. Max diam of opening in wall for 1, 2 and 4 in. sizes are 1-1/8, 2-1/4 and 4-1/2 in., respectively.

UNIQUE FIRE STOP PRODUCTS INC — Smooth Sleeve

2. Threaded steel sleeve device incorporating flat washers secured by threaded couplings.

Device shall be installed in accordance with the accompanying installation instructions. Device provided in nom 1, 2 and 4 in. sizes. Max diam of opening in wall for 1, 2 and 4 in. size devices are 1-5/16, 2-3/8 and 4-1/2 in., respectively.

UNIQUE FIRE STOP PRODUCTS INC — Threaded Sleeve

3. Threaded steel sleeve halves incorporating split nuts and split washers sized to fit the specific diam of the opening. Device shall be installed around cables in accordance with the accompanying installation instructions. Device provided in nom 1, 2 and 4 in. sizes. Max diam of opening in wall for 1, 2 and 4 in size devices are 1-1/4, 2-7/16 and 4-1/2 respectively.

UNIQUE FIRE STOP PRODUCTS INC — Split Sleeve
C. Packing Material - (Optional) — Min 1 in. thickness of min 4.0 pcf mineral wool batt insulation firmly packed into each end of firestop device as a permanent form. Packing material to be recessed from each end of firestop device as required to accommodate the required thickness of fill material.

D. Fill, Void or Cavity Material* — Putty — Min 5/8 in. thickness of fill material applied within the firestop device, flush with both ends.

HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC — CP618 Firestop Putty Stick
*Bearing the UL Classification Mark
The L Rating of the firestop system is dependent upon the type of firestop device as tabulated below:

F RATING - 1 and 2 Hr (See Item 1)
T RATING - 0 Hr
L RATING AT AMBIENT - 22 or 54 CFM / Sq Ft (See Item 3B) L RATING AT 400F - 18 or 47 CFM / Sq Ft (See Item 3B)
System No. W-L-3122
2 3B
1A 3C
3D
1B
R
Classified by
Underwriters Laboratories,
Inc.
to UL 1479 and CAN/ULCS115

SECTION A-A
A
A

1. Wall Assembly — Min 6 in. (152 mm) thick lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 4 in. (102 mm). See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.

2. Cables — Aggregate cross-sectional area of cable in opening to be max 45 percent of the cross-sectional area of the opening. The annular space between the cable bundle and the periphery of the opening to be min 0 in. (point contact) to max 7/8 in. (22 mm) Cables to be tightly bundled and rigidly supported on both sides of the wall assembly.. Any combination of the following types and sizes of copper conductor cables may be used:

A. Max 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket.

B. Max 25 pair No. 24 AWG telephone cable with PVC insulation and jacket.

C. Max 4 pr No. 22 AWG Cat 5 or Cat 6 computer cables.

D. Type RG/U coaxial cable with polyethylene (PE) insulation and PVC jacket having a max outside diameter of ½ in. (13 mm).

E. Max RG 6/U coaxial cable with fluorinated ethylene insulation and jacketing.

F. Multiple fiber optical communication cable jacketed with PVC and having a max OD of 5/8 in. (16 mm).

G. Max three copper conductor No. 8 AWG Metal-Clad Cable+.

H. Max 3/C (with ground) (or smaller) No. 8 AWG copper conductor cable with PVC insulation and jacketing.

I. Through Penetrating Product* — Any cables, Metal-Clad Cable+ or Armored Cable+ currently Classified under the Through Penetrating Products category.

3. Fill, Void or Cavity Material*— Sealant — Fill material applied within the annulus, flush with both surfaces of wall. A min 5/8 in. (16 mm) thickness of sealant is required for 2 hr F Rating. A min 1 in. (25 mm) thickness of sealant is required for the 3 hr F Rating. An additional 1/2 in. (13 mm) diam bead of fill material shall be applied at the point contact location of cable bundle/concrete interface on both surfaces of wall.

HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP606, FS-One Sealant or FS-ONE MAX Intumescent Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.
+Bearing the UL Listing Mark
C

CLASS IF IED
US
ANSI/UL 1479 (ASTM E814)
F RATING - 2 and 3 Hr (See Item 3)
T RATING - 0 Hr
System No. W-J-3190
3 1
2 3
SPECIFIED TECHNOLOGIES INC — FS100, FS200, FS201, FS400 and FS401 SpecSeal Ready-Sleeves

3. Cables — Aggregate cross-sectional area of cables in steel sleeve to be max 33 percent of the aggregate cross-sectional area of the sleeve.

Cables to be rigidly supported on both sides of wall assembly. Any combination of the following types and sizes of copper conductor cable may be used:

A. Max 200 pair No. AWG (or smaller) copper conductor cable with polyvinyl chloride (PVC) jacketing and insulation.

B. Max 3/C No. 2/0 AWG (or smaller) aluminum or copper conductor service entrance cable with PVC insulation and jacket.

C. Max 3/C No. 8 AWG (or smaller) nonmetallic sheathed (Romex) cable with copper conductors, PVC insulation and jacket.

D. Max 7/C No. 2/0 AWG (or smaller) multiconductor power and control cables with XLPE or PVC insulation and XLPE or PVC jacket.

E. Max RG/U (or smaller) coaxial cable with fluorinated ethylene insulation and jacketing.

F. Max 62.5/48 fiber optic cable with PVC insulation and jacketing.

G. Max 4 pair No. 24 AWG (or smaller) copper conductor data cable with PVC insulation and jacket.

H. Max 4/C No. 2/0 aluminum or copper conductor aluminum or steel Metal-Clad# or Armored-Clad# cable. • When Item 3G is used, the L Rating is 11.9 CFM/device at ambient and 5.2 CFM/device at 400F.

4. Fill, Void or Cavity Material* - Putty — Fill material supplied with firestop device (Item 2) applied to 1 in. (25 mm) thickness flush with each end of steel sleeve device. At point contact location, min 3/8 in. (9 mm) diam bead of fill material applied at grouped cable/steel sleeve interface on each side of wall.
• SPECIFIED TECHNOLOGIES INC — SpecSeal Putty
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

1. Wall Assembly — The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:

A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.

B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 ft (1.2 m) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300, U400 or V400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 4-1/2 in. (114 mm). • The hourly F rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed.

2. Firestop Device* — Steel sleeve device centered within opening and installed in accordance with the accompanying installation instructions.

Steel sleeve device secured in place by means of steel escutcheon plates installed with gasketing material supplied with product. Steel escutcheon plates installed on both sides of wall and secured to device by means of steel screws provided with device. Steel sleeve device provided in nom 1, 2 and 4 in. (25, 51 and 102 mm) sizes. The min and max opening sizes for each sleeve device are shown in the table below:

MIN OPENING SIZE MAX OPENING SIZE
1 in. (25mm) 1.12 in. (28mm) 1.25 in. (32mm)
2 in. (51mm) 2.38 in. (60mm) 2.50 in. (64mm)
4 in. (102mm) 4.50 in. (114mm) 4.50 in. (114mm)

DEVICE SIZE
F RATING - 1 and 2 HR (See Item 1)
T RATING - 0 Hr
L RATING AT AMBIENT - 11.92 CFM (See Item 3)
L RATING AT 400F - 5.19 CFM (See Item 3)
System No. W-L-3376
3 4
2 4
1B
1A
1B 1A
3 2
3 A
A

SECTION A-A

1. 1. Wall Assembly — The 1, 2 or 3 fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:

A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.

B. Gypsum Board* — Nom 5/8 in. (16 mm) thick gypsum board, with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition Design in the UL Fire Resistance Directory. Max diam of opening is 4 in. (102 mm).
• The F Rating of the firestop system is equal to the fire rating of the wall assembly.

2. Cables — Aggregate cross-sectional area of cable in opening to be max 45 percent of the cross-sectional area of the opening. The annular space between the cable bundle and the periphery of the opening to be min 0 in. (point contact) to max 7/8 in. (22 mm) Cables to be tightly bundled and rigidly supported on both sides of the wall assembly. Any combination of the following types and sizes of copper conductor cables may be used:

A. Max 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket.

B. Max 25 pair No. 24 AWG telephone cable with PVC insulation and jacket.

C. Max 4 pr No. 22 AWG Cat 5 or Cat 6 computer cables.

D. Type RG/U coaxial cable with polyethylene (PE) insulation and PVC jacket having a max outside diameter of ½ in. (13 mm).

E. Max RG 6/U coaxial cable with fluorinated ethylene insulation and jacketing.

F. Multiple fiber optical communication cable jacketed with PVC and having a max OD of 5/8 in. (16 mm).

G. Max three copper conductor No. 8 AWG Metal-Clad Cable+.

H. Max 3/C (with ground) (or smaller) No. 8 AWG copper conductor cable with PVC insulation and jacketing.

I. Through Penetrating Product* — Any cables, Metal-Clad Cable+ or Armored Cable+ currently Classified under the Through Penetrating Products category.

3. Fill, Void or Cavity Material*— Sealant — Fill material applied within the annulus, flush with both surfaces of wall. A min 5/8 in. (16 mm) thickness of sealant is required for the 1 or 2 hr F Rating. A min 1 in. (25 mm) thickness of sealant is required for the 3 hr F Rating. An additional 1/2 in. (13 mm) diam bead of fill material shall be applied at the point contact location of cable bundle/gypsum board interface on both surfaces of wall.

HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP606 or FS-One Sealant or FS-ONE MAX Intumescent Sealant * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

ANSI/UL 1479 (ASTM E814)
F RATING - 1, 2, and 3 Hr (See item 1)
T RATING - 0 Hr
System No. W-L-3385

1. Wall Assembly — The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:

A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 in. (51 mm) by 4 in. (102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.

B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 ft (1219 cm) wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition Design. Opening may be round, rectangular or irregular with a max diam or dimension of 1 in. (25 mm). • The hourly F, FT, FH and FTH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed.

2. Cables — Single or tight bundle of cables penetrating wall assembly on one side of wall. Aggregate cross-sectional area of cables in opening to have a visual fill of min 0% to max 100%. The annular space between the cable bundle and the periphery of the opening to be min 0 in. (point contact). Cables to be rigidly supported on penetrating side of and within the wall assembly. Any combination of the following types and sizes of cables may be used:

A. Max 3/C No. 8 AWG NM copper conductor cable (Romex) with PVC insulation and jacket.

B. Max 4 pr No. 22 AWG (or smaller) Cat 5 or Cat 6 computer cables with PVC or plenum rated insulation and jacketing.

C. Type RG/U coaxial cable with fluorinated ethylene or PVC insulation and jacketing having a max outside diameter of 1/2 in. (13 mm).

D. Max 24 fiber optic cable with polyvinyl chloride (PVC) or polyethylene (PE) jacket and insulation.

E. Max 25 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) or plenum-rated jacketing and insulation.

F. Through Penetrating Product* — Max two copper conductor No. 18 AWG (or smaller) Power or Non-Power Limited Fire Alarm Cable with or without a jacket under a metal armor.
• AFC CABLE SYSTEMS INC
G. Maximum 3/C No. 10 AWG copper conductor metal-clad cable.

3. Fill, Void or Cavity Material* — Nom 60 mm diam by 3 mm thick putty disc with one seam at radius. Paper-backer of disc to be removed and disc firmly pressed around the cable/cable bundle lapping nom 5 mm onto cables to completely cover opening and firmly pressed to lap onto the wall around periphery of opening. Disc seam to be firmly pressed and sealed tight, Disc to be installed at penetrated side of wall. • HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CFS-D 1" Firestop Cable Disc * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

F RATING - 1 and 2 HR (See Item 1)
T RATING - 1 and 2 HR (See Item 1)
L RATING AT AMBIENT - Less than 1 CFM/Opening
L RATING AT 400F - Less than 1 CFM/Opening
System No. W-L-3415
2 3
2 3
1B
1A
Section A-A
Section B-B
Section C-C
C
C
A
A
B
B
2 (51) or
Type
Cable
0% -Series 22 1.4 1.4
Device
Ambient 400° F
L-Rating (CFM)
1-3/4 x 1-3/4 (44 x 44)
Dimensions, in. (mm)
Opening Size Diam or
Series 22
Series 22
Series 33
Series 33
Series 33
Series 33
1-25%
26-50%
0%
100%
100%
100%
3A
-
3A
3F
Less
Than 1
Less
Than 1
Less
Than 1
Less
Than 1
Less
Than 1
Less
Than 1
Less
Than 1
4 3

1.3 7 2
2 (51) or
1-3/4 x 1-3/4 (44 x 44)
2 (51) or
1-3/4 x 1-3/4 (44 x 44)
4 (102) or
3-1/4 x 3-1/4 (82 x 82)
4 (102) or
3-1/4 x 3-1/4 (82 x 82)
4 (102) or
3-1/4 x 3-1/4 (82 x 82)
4 (102) or
3-1/4 x 3-1/4 (82 x 82)
Series 33 100% 3I 1.8 1.8 4 (102) or
3-1/4 x 3-1/4 (82 x 82)
Series 44+
Series 44+
0% -

2.3 2.3
6 (152) or
4-1/8 x 4-3/4 (120 x 120)
6 (152) or
4-1/8 x 4-3/4 (120 x 120)
Less
Than 1
Less
Than 1
3A-3I
Fill
Cable
Max
Series 22 51-75% Less
Than 1
Less
Than 1
2 (51) or
1-3/4 x 1-3/4 (44 x 44)
Series 22 76-100% Less
Than 1
Less
Than 1
2 (51) or
1-3/4 x 1-3/4 (44 x 44)
Series 22 100% 3F Less
Than 1
Less
Than 1
2 (51) or
1-3/4 x 1-3/4 (44 x 44)
3A
3A
3A
3G,
3H
Series 44+
Series 44+
Series 44+ 1-25%
26-50%
51-75%
76%-
100%
3A-3I
3A-3I
3A-3I

2.3 2.3

2.3 2.3

1.5 1.5
6 (152) or
4-1/8 x 4-3/4 (120 x 120)
6 (152) or
4-1/8 x 4-3/4 (120 x 120)
6 (152) or
4-1/8 x 4-3/4 (120 x 120)

1. Wall Assembly — The 1, 2, 3 or 4 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described within the individual U300, U400, V400 or W400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall incorporate the following construction features:

A. Studs — Wall framing shall consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.

B. Gypsum Board* — Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. See Table for opening sizes.
• The hourly F and FH Ratings are dependent upon the hourly rating of the wall in which it is installed.

2. Firestop Device* — Series 22 EZ Path device modules consist of a 1.4 by 1.4 by 10-1/2 in. (36 by 36 by 267 mm) long galv steel tube with an intumescent material lining. Series 33 EZ Path device modules consist of a 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long galv steel tube with an intumescent material lining. Series 44+ EZ Path device modules consist of a 4 by 4-5/8 by 14 in. (102 by 118 by 356 mm) long galv steel tube with an intumescent material lining. Firestop device modules to be installed in accordance with the accompanying installation instructions. Firestop device modules secured in place by means of steel wall plates installed with gasketing material supplied with product. Steel wall plates installed on both sides of wall and secured to each device by means of steel screws provided with device. Firestop device module is to be installed with ends projecting an equal distance beyond each surface of the wall assembly. The annular space between the device and opening shall be min 0 in. (point contact) to max 1/8 in. (3 mm) for Series 22 device, max 1/2 in. (13 mm) for Series 33 device and max 1/4 in. (6 mm) for Series 44 device.

The opening size and L Ratings for each device vary according to whether device module is blank (no cables) or loaded (with cables) and which cable type and size is used, as tabulated below:

SPECIFIED TECHNOLOGIES INC — EZ PATH Series 22, 33 or 44+ Fire Rated Pathway • Firestop Device* — Extension Module — (Optional, Not Shown) — Module attached to ends of Series 33, Series 44+ firestop device (Item 2) to increase its length to facilitate installation in thicker walls. Each module consists of a galv steel tube with an intumescent material lining. Extension module to be installed in accordance with the accompanying installation instructions. When module is used, firestop device (Item 2) and extension module(s) secured in place by means of steel wall plates installed with gasketing material supplied with product. Steel wall plates installed on both sides of wall and secured to each device or extension module(s) by means of steel set screws provided with wall plates. Firestop device and extension module(s) assembly to be installed with ends projecting an equal distance beyond each surface of the wall assembly.

SPECIFIED TECHNOLOGIES INC — EZ PATH Series 33 or Series 44+ Extension

3. Cables — Cables may represent a 0 to max 100 percent visual fill within the loading area for the firestop device module. Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types of cables may be used:

A. Max 400 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) or plenum-rated jacketing and insulation.

B. Max 750 kcmil single copper conductor power cable with XLPE jacket and insulation C. Max 7/C No. 12 AWG copper conductor control cable with PVC or XLPE jacket and insulation.

D. Max 3/C No. 2/0 AWG metal clad or armored cable with steel or aluminum jacket.

E. Max 3/C No. 8 AWG NM cable (Romex) with PVC insulation and jacket.

F. Max four pair No. 22 AWG (or smaller) copper conductor data cable with PVC or plenum rated jacketing and insulation.

G. Coaxial cable with fluorinated ethylene or PVC insulation and jacketing having a max diam of 5/8 in. (16 mm).

H. Optical fiber cable with PVC or polyethylene (PE) jacket and insulation and having a max diam of 5/8 in. (16 mm).

I. Max RG6/U coaxial cable with fluorinated ethylene, polyethylene (PE), PVC or plenum rated jacketing and insulation.

When Series 22 EZ Path device modules are used and when the hourly rating of the wall assembly is 1 hr, the T, FT and FTH Ratings are 3/4 hr except that for Items 3F, 3G and 3H, the T, FT and FTH Ratings are 1 hr. When the hourly fire rating of the wall assembly is 2 hr or greater, the T, FT and FTH Ratings are 3/4 hr when cables are installed. When no cables are installed within the device module, the T, FT and FTH Ratings are 1 hr in 1 hr walls and 1-1/2 hr for 2, 3 and 4 hr walls. When Item 3A, 3B, 3C, 3D or 3E is used, the maximum F and FH Ratings are 2 hr. When max 200 pair No. 24 AWG telecommunication cable and/or 350 kcmil power cable is used or when Item 3F, 3G, 3H or 3I is used, the maximum F and FH Ratings are 4 hr.

When Series 33 EZ Path device modules are used and when the hourly rating of the wall assembly is 1 hr, the T, FT and FTH Ratings are 3/4 hr.

When the hourly fire rating of the wall assembly is greater than 1 hr, the T, FT and FTH Ratings are 3/4 hr when Item 3A, 3B, 3C, 3D or 3E is used.

Otherwise the T, FT and FTH Ratings are 1 hr. When Item 3A, 3B, 3C, 3D or 3E is used, the maximum F and FH Ratings are 2 hr. When max 200 pair No. 24 AWG telecommunication cable is used or when Item 3F, 3G, 3H or 3I is used, the maximum F and FH Ratings are 4 hr.

When Series 44 + EZ Path device modules are used and when Item 3A, 3B, 3C, 3D or 3E is used, the max F and FH Ratings are 3 hr and the T, FT and FTH Ratings are 1 hr. When Item 3F or 3G is used, the max F and FH Ratings are 4 hr and the T, FT and FTH Ratings are 1-1/2 hr. When Item 3H or 3I is used, the max F and FH Ratings are 4 hr and the T, FT and FTH Ratings are 2 hr. When device empty, the T, FT and FTH Ratings are 1-1/2 Hr.
+Bearing the UL Listing Mark
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

F RATING - 1, 2, 3 and 4 Hr (See Items 1 and 3)
T RATING - 3/4, 1, 1-1/2 and 2 Hr (See Item 3)
FT RATING3/4, 1, 1-1/2 and 2 Hr (See Item 3)
L RATING AT AMBIENT - Less than 1 to 7 CFM/Device Module (See Item 2) L RATING AT 400F - Less than 1 to 3 CFM/Device Module (See Item 2) System No. W-L-3377
2 2
2 3
3 3
2 2
2 3
3 3
1B
1B
1B
1A
1A
1A
EZDR200 50%
Cable Fill
No
Sealant

3.3 Device Max Visual Sleeve Size in. (mm)

3.7 or
Putty
Ambient 400°F
L-Rating (CFM)
2 (51)
2 (51)
2 (51)
2 (51)
2 (51)
2 (51)
4 (102)
4 (102)
4 (102)
4 (102)
4 (102)
4 (102)
EZDR200
EZDR200
EZDR200
EZDR200
EZDR200
EZDR400
EZDR400
EZDR400
EZDR400
EZDR400
EZDR400
No
No
Yes
Yes
Yes
No
No
No
Yes
Yes
Yes
51% - 75%
76% - 100%
50%
51% - 75%
76% - 100%
50%
51% - 75%
76% - 100%
50%
51% - 75%
76% - 100%
4 1.5

1.8 7.8
8 10.7

1.3 3.7

5.2 3.3

3.7 4

1.5 1.8

7.8 8

10.7 1.3

3.7 5.2
A
A Section A-A
W-L-3435
ANSI/UL1479 (ASTM E814)
F Ratings - 1 and 2 Hr (See Item 1)
T Ratings - 0 and 1/2 Hr (See Item 2)
L Rating at Ambient - Less than 1 to 10.7
CFM/Device (Seeitem 4C)
L Rating at 400 F - Less than 1 to 10.7 CFM/Device (See item 4C)
CAN/ULC S115
F Ratings - 1 and 2 Hr (See Item 1)
FT Ratings - 0 and 1/2 Hr (See Item 2)
FH Ratings - 1 and 2 Hr (See Item 1)
FTH Ratings - 0 and 1/2 Hr (See Item 2)
L Rating at Ambient - Less than 0.47 to 5.05 L/s/Device (Seeitem 4C)
L Rating at 204 C- Less than 0.47 to 5.05
L/s/Device (See item 4C)
Less
Than 1
Less
Than 1
3 4A 2
1A
1B 4A
3 1. 1.Wall Assembly - The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, V300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:

A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.

B. Gypsum Board* - Thickness, type, number of layers, fastener type and sheet orientation shall be as specified in the individual U300, V300, U400 , V400 or W400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 5-1/2 in. (140 mm) when sleeve (Item 2) extends from wall surface. When sleeve is flush with wall surface, opening sized to outside diameter of sleeve. Max diam of opening is 4 in. (102 mm) when sleeve is not used.
• The F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall in which it is installed.

2. Steel Sleeve - (Optional) - Nom 1-1/2 in. (38 mm), 2 in. (51 mm), 3 in. (76 mm) or 4 in. (102 mm) diam steel electrical metallic tubing (EMT), steel conduit, Schedule 5 (or heavier) steel pipe sleeve or min 0.016 in. thick (0.41 mm, No. 28 ga) galv sheet steel sleeve installed flush with wall surfaces. The annular space between the steel sleeve and periphery of opening shall be min 0 in. (continuous point contact) to max 1 in. (25 mm). Sheet steel sleeve to be installed in continuous point contact only. When Schedule 5 steel pipe, steel conduit or EMT is used, sleeve may be installed flush with or extend up to 3 in. (76 mm) beyond one or both wall surfaces. When sleeve projects from wall surface, it may be provided with a metallic or nonmetallic conduit bushing. Steel sleeve may be installed at an angle not greater than 45 degrees from perpendicular. Schedule 5 steel pipe, steel conduit or EMT sleeves may extend continuously beyond one wall surface. Sleeve to be rigidly supported when extending from the wall surfaces.
• When sleeve is flush with wall surface in 2 Hr rated assemblies, the T, FT, and FTH Ratings are 1/2 Hr. Otherwise, the T, FT, and FTH Ratings are 0 Hr.

3. Cables - Cables may represent a min 50 to max 100 percent visual fill within the loading area for the sleeve, a nom 2 in. (51 mm) diam opening or a nom 4 in. (102 mm) diam opening. Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types and sizes of cables may be used:

A. Max 400 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) or plenum-rated jacketing and insulation.

B. Max 750 kcmil single copper conductor power cable with XLPE jacket and insulation.

C. Max 7/C No. 12 AWG copper conductor control cable with PVC or XLPE jacket and insulation.

D. Max 3/C No. 2/0 AWG metal clad or armored cable with steel or aluminum jacket.

E. Max 3/C No. 8 AWG NM cable (Romex) with PVC insulation and jacket.

F. Max four pair No. 22 AWG (or smaller) copper conductor data cable with PVC or plenum rated jacketing and insulation.

G. Max four pair No. 22 AWG (or smaller) Cat 5, Cat 5E, Cat 6 or Cat 6A cable with PVC or plenum rated jacketing and insulation.

H. Coaxial cable with fluorinated ethylene or PVC insulation and jacketing having a max diam of 5/8 in. (16 mm).

I. Optical fiber cable with PVC or polyethylene (PE) jacket and insulation and having a max diam of 5/8 in. (16 mm).

J. Max RG6/U coaxial cable with fluorinated ethylene, polyethylene (PE), PVC or plenum rated jacketing and insulation.

4. Firestop System* - The firestop system shall consist of the following:

A. Firestop Device - A firestop device consisting of a rectangular galv steel housing with intumescent curtain sized to the specific diam of the sleeve or opening. Firestop device installed in accordance with the accompanying installation instructions on each side of the wall. Firestop device secured to end of sleeve when sleeve extends from wall surface. When sleeve extends continuously beyond one wall surface, firestop device shall be installed only on the side of the wall with a sleeve termination. When sleeve is flush with wall surface or when sleeve is not used, firestop device secured to assembly using provided anchor tabs by means of 1/8 in. (3.2 mm) diam by 1-3/4 in. (44 mm) long steel molly bolts or toggle bolts in conjunction with min 1-1/4 in. (32 mm) diam steel fender washers.

B. Fill, Void or Cavity Material* - Sealant or Putty - (Optional, Not Shown) Any existing XHHW sealant or putty either partially or fully installed into one or both ends of the steel sleeve. When annular space is present between the sleeve and the periphery of the opening, a min 5/8 in. (16 mm) thickness of any existing XHHW sealant or putty shall be applied within the annulus, flush with both surfaces of wall.

C. Fill, Void or Cavity Material* - Sealant or Putty - (Optional, Not Shown) - Min 1/2 in. (13 mm) thickness of sealant or putty applied within annulus, flush with both ends of sleeve. When annular space is present between the sleeve and the periphery of the opening, a min 1/2 in. (13 mm) thickness of sealant or putty shall be applied within the annulus, flush with both surfaces of the wall. • Firestop Device* - (Not Shown) - When nom 1-1/2 in. (38 mm) or nom 3 in. (76 mm) diam steel sleeve is used, an appropriately sized steel plate adaptor kit shall be used in conjunction with Item 4A. The steel plate shall be installed in accordance with the accompanying installation instructions.

SECTION A-A
A
A

1. Wall Assembly — The 1 or 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:

A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.

B. Gypsum Board* — One or two layers of nom 5/8 in. (16 mm) thick gypsum board as specified in the individual Wall and Partition Design.

Max diam of opening is 5 in. (127 mm).

C. The hourly F, FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly.

2. Sleeve — Nom 3 in. (76 mm) diam (or smaller) steel EMT, steel conduit or Schedule 5 (or heavier) steel pipe. The annular space between sleeve and periphery of opening shall be min. 0 in. (point contact) to max 1 in. (25 mm). Maximum projection from wall is 12 in. (305 mm).

Sleeve to be rigidly supported on penetrated side of the wall assembly.

3. Cables — Aggregate cross-sectional area of cable in opening to be min 0 to max 45 percent of the cross-sectional area of the opening. The annular space between the cable bundle and the periphery of the opening to be min 0 in. (point contact). Cables to be rigidly supported on penetrated side of the wall assembly. Any combination of the following types and sizes of copper conductor cables may be used:

A. Max 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket.

B. Max 25 pair No. 24 AWG telephone cable with PVC insulation and jacket.

C. Type RG/U coaxial cable with polyethylene (PE) insulation and PVC jacket having a max outside diameter of ½ in. (13 mm).

D. Multiple fiber optical communication cable jacketed with PVC and having a max OD of 5/8 in. (16 mm).

E. Multiple fiber optical communication cable jacketed with PVC and having a max OD of 5/8 in. (16 mm).

F. Through Penetrating Products*— Max three copper conductor No. 8 AWG . Metal-Clad Cable+. AFC CABLE SYSTEMS INC G. Max 3/C (with ground) No. 8 AWG (or smaller) copper conductor cable with PVC insulation and jacketing.

H. Max 3/4 in. (19 mm) diam copper ground cable with or without a PVC jacket.

I. Fire Resistive Cables* — Max 1-1/4 in. (32 mm) diam single conductor or multi conductor Type MI cable. A min 1/8 in. (3 mm) separation shall be maintained between MI cables and any other types of cable.

4. Fill, Void or Cavity Material++— Sealant — Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with surface of wall. Min 1/2 in. (13 mm) diam bead of sealant applied at point contact location. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant, FS-ONE MAX Intumescent Sealant, CFS-S SIL GG Sealant, CP601S Elastomeric Sealant, CP 606 Sealant, CP618 Putty

5. Packing Material — (Optional, Not Shown) — Mineral wool forming material may be used as a backer for the sealant. When used, it shall be firmly packed into annular space between cables and sleeve as a permanent form and recessed from end of sleeve to accommodate the required thickness of fill material.
++ Bearing the UL Classification Mark
ANSI/UL 1479 (ASTM E814)
F RATING - 1 & 2 Hr (See Item 1)
T RATING - 0 Hr
System No. W-L-3320
4 2
3 4 4
4 1
2 4
3 DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/2
0/2
0 2
4 11:2
4:3
4 A
M
C:\U
s
ers\k
ale
k
s
a
n
dro
v\O
n
e
Driv
e - Willia
m
s
&
P
a
d
d
o
n\D
o
c
u
m
e
nts\210
015.01_
CIT
Y
O
F
R
O
S
E
VIL
L
E
_
D
C
W
W
T
P
A
D
MIN
B
L
D
G
_A
2 2
_
k
ale
k
s
a
n
dro
v
4 T
4 5

5.rvt
A-791

FIRESTOPPING

PENETRATIONS -

HORIZ CABLES

DCWWTP OPERATIONS

AND LAB BLDG
May 29, 2024
210015.01Author
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
311 VERNON ST
ROSEVILLE, CA 95768
90% CD - PERMIT SET
W-L-3122: CABLES @ WALL ASSEMBLY 3" = 1'-0" 1

21.12.14 - 00000
W-L-3190: CABLES @ WALL ASSEMBLY 12" = 1'-0" 2

21.12.14 - 00000
W-L-3376: CABLES @ WALL ASSEMBLY 1 1/2" = 1'-0" 3

21.12.14 - 00000
W-L-3385: CABLES @ WALL ASSEMBLY 12" = 1'-0" 8

21.12.14 - 00000
W-L-3415: CABLES @ MEMBRANE 3" = 1'-0" 13

21.12.14 - 00000
W-L-3377: EZ PATH 22 12" = 1'-0" 5

21.12.14 - 00000
W-L-3435: EZ PATH RETROFIT N.T.S. 9

21.12.14 - 00000
W-L-3320: CABLES @ MEMBRANE 12" = 1'-0" 4

21.12.14 - 00000
NO. DATE DESCRIPTION
1 8/28/24 PC Comments
1 2/28/25

BID SET (PRELIMINARY)

DOOR HEIGHT

DOOR HEIGHT
EQ EQ
DOOR TYPE '1' DOOR TYPE '2' DOOR TYPE '3' DOOR TYPE '4'

DOOR WIDTH
DOOR TYPE '5'

DOOR WIDTH
DOOR TYPE '6' DOOR TYPE '7'

DOOR WIDTH

DOOR HEIGHT
6"
6"
3'-6"

DOOR WIDTH

DOOR HEIGHT
6" 8"
6" 1'-0"
1'-0" 6"

DOOR HEIGHT
6" 10"

DOOR WIDTH
1'-0" 6"

DOOR HEIGHT
6" 6"

DOOR WIDTH
1'-0" 6"

DOOR HEIGHT
6" 6"

DOOR WIDTH
EQ EQ
DOOR CONSTRUCTION AND MATERIAL:

HM - HOLLOW METAL

AL - ALUMINUM

WD - WOOD
DOOR FACING AND FINISH:

AL - CLEAR ANNODIZED ALUMINUM

K - KYNAR FINISH ON ALUMINUM

SP - STEEL, PAINTED

WS - WOOD VENEER, STAINED
FRAME MATERIAL:

HM - HOLLOW METAL, PAINTED

AL - ALUMINUM
FRAME FINISH:

AL - CLEAR ANNODIZED ALUMINUM

P - PAINTED STEEL

K - KYNAR FINISH ON ALUMINUM
FRAME TYPES:

A, B
GLASS:

ALL GLASS IS TEMPERED (SG - SAFETY GLAZING)
HARDWARE:

P.H. - PANIC HARDWARE

LEGEND - DOOR MATERIALS
A. RATED DOORS SHALL BE POSITIVE LATCHING. RATED DOORS SHALL HAVE A MAXIMUM GAP OF 1/8" ON THE SIDES AND TOP, AND 3/8" ON THE BOTTOM. RATED ASSEMBLIES SHALL BE PROVIDED WITH APPROVED GASKET MATERIAL INSTALLED TO PROVIDE A SEAL WHERE THE DOOR MEETS THE STOPS ON BOTH SIDES AND THE TOP. MANUFACTURERS INSTALLATION INSTRUCTIONS SHALL BE AVAILABLE ON THE JOB SITE. HARDWARE SHALL BE FIRE RATED.

B. DOOR OPENING FORCE - EFFORT OF OPERATION (CBC 11B-404.2.9) * 5 POUNDS FOR INTERIOR & EXTERIOR DOORS
* 15 POUNDS FOR FIRE DOORS.

C. ALL DOOR CLOSERS SHALL BE MOUNTED ON ROOM SIDE OF DOORS, CONCEALED FROM CORRIDORS & COMMON AREAS. THE SWEEP PERIOD SHALL BE 5 SECONDS MINIMUM FROM 90º OPEN TO 12º FROM THE LATCH. CBC 11B-404.2.8.1 D. LATCHING AND LOCKING DOORS THAT ARE HAND ACTIVATED SHALL BE OPERABLE W/ A SINGLE EFFORT BY LEVER TYPE

HARDWARE, BY PANIC BARS, PUSH-PULL ACTIVATING BARS,DESIGNED TO PROVIDE PASSAGE WITHOUT REQUIRING THE ABILITY TO GRASP THE OPENING HARDWARE.

E. EGRESS DOORS SHALL BE READILY OPERABLE FROM THE EGRESS SIDE WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE OR EFFORT. (CBC 11B-404.2.7)
F. 11B-404.2.7 DOOR AND GATE HARDWARE. HANDLES, PULLS, LATCHES, LOCKS, AND OTHER OPERABLE PARTS ON DOORS AND GATES SHALL COMPLY WITH SECTION 11B-309.4. OPERABLE PARTS OF SUCH HARDWARE SHALL BE 34 INCHES (864 MM) MINIMUM AND 44 INCHES (1118 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. WHERE SLIDING DOORS ARE IN THE FULLY OPEN POSITION, OPERATING HARDWARE SHALL BE EXPOSED AND USABLE FROM BOTH SIDES.

G. THE UNLATCHING OF ANY DOOR OR LEAF SHALL NOT REQUIRE MORE THAN ONE OPERATION. (CBC 1010.1.9.5).

H. SPECIFIC FINISHES SHALL BE PER THE INTERIOR DESIGNER.

I. DOOR STOPS SHALL BE PROVIDED ON ALL DOORS. DOOR STOPS ON NON-RATED DOORS SHALL BE HINGE STOPS (HAGER 301D) UNO. DOOR STOPS ON RATED DOORS SHALL BE INTEGRAL WITH THE CLOSING DEVICE.

J. SIGN ADJACENT TO MAIN EXIT DOOR SHALL STATE "DOORS TO REMAIN UNLOCKED DURING BUSINESS HOURS" WITH 1" HIGH CONTRASTING LETTERS.

K. PROVIDE A SIGN ON OR ADJACENT TO EACH BUILDING ENTRANCE OF THE INTERNATIONAL SIGN OF ACCESSIBILITY AT +60" AFF.

MAX.

L. ALL KEYED LOCKS ARE TO BE PER FACILITY STANDARDS.

M. ALL NON-RATED DOORS SHALL HAVE DOOR SILENCERS ON THE DOOR FRAME.

N. ALL DOORS SHALL HAVE STAINLESS STEEL EDGE GUARDS, BEVELED FLUSH WITH LAMINATE 1/2" MAXIMUM RETURN. MOUNT ON BOTH SIDES OF DOOR.

O. DOOR ACCESSORIES
-PROVIDE KICK PLATES WHERE SPECIFIED
-PROVIDE LOUVERS WHERE SPECIFIED
P. DOORS SHALL BE 1-3/4" THICK UNLESS NOTED OTHERWISE.

Q. THE SYMBOL (P) FOLLOWING THE 'DOOR TYPE' DESIGNATION IN THE DOOR SCHEDULE INDICATES PAIR OF DOORS. BOTH LEAVES ARE THE SAME SIZE, U.N.O.

R. ALL DOORS IN BUILDINGS, INCLUDING, BUT NOT LIMITED TO DOORS OF TOILETS AND STORAGE ROOMS, SHALL CONFORM WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE CALIFORNIA BUILDING CODE. a. EXIT DOOR SHALL BE OPERABLE FROM THE INSIDE WITHOUT THE USE OF A KEY OR ANY SPECIAL KNOWLEDGE OR EFFORT. b. HAND ACTIVATED DOOR OPENING HARDWARE SHALL BE CENTERED BETWEEN 34" AND 44" ABOVE FINISH FLOOR. c. DEAD BOLTS ARE NOT PERMITTED UNLESS OPERABLE WITH A SINGLE EFFORT LEVER TYPE HARDWARE. d. ALL ROOMS SERVING AN OCCUPANCY LOAD OF 50 OR GREATER AND DOORS LOCATED ON THE DISCHARGE OF EXIT CORRIDORS ARE REQUIRED TO BE PROVIDED WITH PANIC HARDWARE (CBC 1010.1.10). e. ALL FIRE DOOR LABELS SHALL COMPLY WITH CBC 716.5.7.

S. FIRE ASSEMBLIES REQUIRED TO HAVE A ONE-HOUR FIRE-PROTECTION RATING SHALL BE EITHER AUTOMATIC OR SELFCLOSING FIRE ASSEMBLIES TO BE ACTIVATED BY AN INCREASE IN TEMPERATURE SHALL HAVE HEAT-ACTIVATING DEVICES INSTALLED ON EACH SIDE OF THE WALL AT THE CEILING HEIGHT WHERE THE CEILING IS MORE THAN 3 FEET ABOVE THE TOP OF THE OPENING OR BY A SINGLE FUSIBLE LINK IN THE OPENING INCORPORATED IN THE CLOSING DEVICE.

T. ALL FIRE-RESISTIVE ASSEMBLIES FOR PROTECTED OPENING SHOULD COMPLY WITH SECTION 716 CBC.

U. EXTERIOR: STEELCRAFT "L" SERIES 16 GA HONEYCOMB CORE OR "S" OR "A" SERIES 16 GA TUBULAR FOR FULL GLASS, GALVANIZED, WITH GALVANIZED 14 GA FRAMES. USE MINIMUM 6" WIDE STILE ON ALL STILE & RAIL TYPE DOORS TO ACCOMMODATE EXIT DEVICES.

V. INTERIOR STEEL DOORS: STEELCRAFT "L" SERIES HONEYCOMB CORE, OR "S" OR "A" SERIES FOR FULL GLASS, 18 GA WITH 16 GA FRAMES. USE MINIMUM 6" WIDE STILE ON ALL STILE & RAIL TYPE DOORS TO ACCOMMODATE EXIT DEVICES.

W. ALL INTERIOR HOLLOW METAL DOOR AND FRAMES TO HAVE JAMB AND HEAD GASKETING. PEMKO 319 OR EQUAL.

X. PROVIDE ACCESS CONTROL WIRING AND DOOR SWITCH WIRING PER HARDWARE SCHEDULE.

Y. ALL GLAZING SHALL BE 1/4" CLEAR GLASS UNLESS DOOR IS FIRE-RATED THEN SAFETY GLAZING HALL BE AT CURRENT FEDERAL STANDARDS WHERE GLAZING OCCURS IN RATED DOOR ASSEMBLY. (WIRE GLASS IS NOT ACCEPTABLE)

DOOR GENERAL NOTES
A. ALL GLAZING SHALL BE TEMPERED 1/4" CLEAR GLASS UNLESS DOOR IS FIRE-RATED. THEN SAFETY GLAZING SHALL MEET CURRENT FEDERAL STANDARDS WHERE GLAZING OCCURS IN RATED DOOR ASSEMBLY. (WIRE GLASS IS NOT ACCEPTABLE) B. RATED GLAZING NOTES:
a. FIRE-RESISTANCE-RATED GLAZING SHALL BE PERMITTED IN FIRE DOOR AND FIRE WINDOW ASSEMBLIES WHERE TESTED

AND INSTALLED IN ACCORDANCE WITH THEIR LISTINGS AND WHERE IN COMPLIANCE WITH THE REQUIREMENTS OF CBC SECTION 716.3.
b. CBC 716.3 MARKING FIRE-RATED GLAZING ASSEMBLIES: FIRE-RATED ASSEMBLIES SHALL BE MARKED IN ACCORDANCE WITH TABLES 716.3, 716.5, AND 716.6.
c. CBC 716.3.1 FIRE-RATED GLAZING IDENTIFICATION: FOR FIRE-RATED GLAZING, THE LABEL SHALL BEAR THE IDENTIFICATION REQUIRED IN TABLES 716.3 AND 716.5. "D" INDICATES THAT THE GLAZING IS PERMITTED TO BE USED IN FIRE DOOR ASSEMBLIES AND THAT THE GLAZING MEETS THE FIRE PROTECTION REQUIREMENTS OF NFPA 252. "H" SHALL INDICATE THAT THE GLAZING MEETS THE HOSE STREAM REQUIREMENTS OF NFPA 252. "T" SHALL INDICATE THAT THE GLAZING MEETS THE TEMPERATURE REQUIREMENTS OF SECTION 716.5.5.1. THE PLACEHOLDER "XXX" REPRESENTS THE FIRE-RATING PERIOD IN MINUTES.
d. CBC 716.3.2 FIRE-PROTECTION-RATED GLAZING IDENTIFICATION: FOR FIRE-PROTECTION-RATED GLAZING, THE LABEL SHALL BEAR THE FOLLOWING IDENTIFICATION REQUIRED IN TABLES 7 J 6.3 AND 716.6: "OH-XXX". "OB" INDICATES THAT THE GLAZING MEETS BOTH THE FIRE PROTECTION AND THE HOSE-STREAM REQUIREMENTS OF NFPA 257 OR UL 9 AND IS PERMITTED RO BE USED IN FIRE WINDOW OPENINGS. THE PLACEHOLDER "XXX" REPRESENTS THE FIRE-RATING PERIOD IN MINUTES. e. FIRE BARRIER: 3/4 HOUR GLAZING, MAX SIZE TESTED, MARKED D-H f. NFPA 257 OR CL 9 MEETS FIRE WINDOW ASSEMBLY CRITERIA INCLUDING THE HOSE STREAM TEST g. NFPA 252 OR UL 10B I OR UL 10C D = MEETS FIRE DOOR ASSEMBLY CRITERIA. H = MEETS FIRE DOOR ASSEMBLY HOSE

STREAM TEST
h. RATED GLAZING SHALL BE FIRELITE NT

DOOR GLAZING GENERAL NOTES

DOOR GENERAL NOTES
A. DOORS SHALL BE 1-3/4" THICK UNLESS NOTED OTHERWISE.

B. THE SYMBOL (P) FOLLOWING THE 'DOOR TYPE' DESIGNATION IN THE DOOR SCHEDULE INDICATES PAIR OF DOORS. BOTH LEAVES ARE THE SAME SIZE, UNLESS NOTED OTHERWISE.

C. SEE REMARKS SECTION OF DOOR SCHEDULE FOR GLASS TYPES.

D. ALL EXTERIOR DOORS IN BUILDINGS, INCLUDING, BUT NOT LIMITED TO DOORS OF TOILETS AND STORAGE ROOMS, SHALL CONFORM WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE CALIFORNIA BUILDING CODE. a. EXIT DOOR SHALL BE OPERABLE FROM THE INSIDE WITHOUT THE USE OF A KEY OR ANY SPECIAL KNOWLEDGE OR EFFORT. b. HAND ACTIVATED DOOR OPENING HARDWARE SHALL BE CENTERED BETWEEN 30" AND 44" ABOVE FINISH FLOOR. c. DEAD BOLTS ARE NOT PERMITTED UNLESS OPERABLE WITH A SINGLE EFFORT LEVER TYPE HARDWARE. d. ALL ROOMS SERVING AN OCCUPANCY LOAD OF 50 OR GREATER AND DOORS LOCATED ON THE DISCHARGE OF EXIT CORRIDORS ARE REQUIRED TO BE PROVIDED WITH PANIC HARDWARE (CBC 1008.1.10). e. ALL FIRE DOOR LABELS SHALL COMPLY WITH CBC 716.2.9.

E. FIRE ASSEMBLIES REQUIRED TO HAVE A ONE-HOUR FIRE-PROTECTION RATING SHALL BE EITHER AUTOMATIC OR SELFCLOSING FIRE ASSEMBLIES TO BE ACTIVATED BY AN INCREASE IN TEMPERATURE SHALL HAVE HEAT-ACTIVATING DEVICES INSTALLED ON EACH SIDE OF THE WALL AT THE CEILING HEIGHT WHERE THE CEILING IS MORE THAN 3 FEET ABOVE THE TOP OF THE OPENING OR BY A SINGLE FUSSIBLE LINK IN THE OPENING INCORPORATED IN THE CLOSING DEVICE.

F. ALL FIRE-RESISTIVE ASSEMBLIES FOR PROTECTED OPENING SHOULD COMPLY WITH SECTION 716 CBC.

G. SEE SPECIFICATION SECTION 08 71 00 FOR DOOR HARDWARE INDEX AND DOOR HARDWARE SETS.

H. EXTERIOR: STEELCRAFT "L" SERIES 16 GA HONEYCOMB CORE OR "S" OR "A" SERIES 16 GA TUBULAR FOR FULL GLASS, GALVANIZED, WITH GALVANIZED 14 GA FRAMES. USE MINIMUM 6" WIDE STILE ON ALL STILE & RAIL TYPE DOORS TO ACCOMMODATE EXIT DEVICES.

I. INTERIOR STEEL DOORS: STEELCRAFT "L" SERIES HONEYCOMB CORE, OR "S" OR "A" SERIES FOR FULL GLASS, 18 GA WITH 16 GA FRAMES. USE KNOCKDOWN FRAMES AT INTERIORS. USE MINIMUM 6" WIDE STILE ON ALL STILE & RAIL TYPE DOORS TO ACCOMMODATE EXIT DEVICES.

J. ALL INTERIOR HOLLOW METAL DOOR AND FRAMES TO HAVE JAMB AND HEAD GASKETING. PEMKO 319 OR EQUAL.

K. ALL INTERIOR STORFRONT FRAMES SHOULD PROVIDE GASKETING FOR THE HOLLOW METAL DOORS PER THE DETAILS.

L. PROVIDE ACCESS CONTROL WIRING AND DOOR SWITCH WIRING PER HARDWARE SCHEDULE.

M. PROVIDE DOOR SWITCH WIRING PER HARDWARE SCHEDULE.

N. SEE SHEET A-931 FOR SIGNAGE PLAN.

A. FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION.

B. ALL DOORS AND HARDWARE SHALL BE INSTALLED IN STRICT COMPLIANCE WITH CALIFORNIA TITLE 24 ACCESSIBLE CODE OF REGULATIONS (ACCESS CODE) AND THE FEDERAL AMERICANS WITH DISABILITIES ACT GUIDELINES (2010 ADA STANDARDS).

C. EXIT DOORS SHALL BE ABLE TO BE OPENED FROM THE INSIDE WITHOUT THE USE OF A KEY OR ANY SPECIAL KNOWLEDGE OR EFFORT.

D. THE MAXIMUM EFFORT TO OPERATE DOORS SHALL NOT EXCEED 5 LBS. FOR EXTERIOR AND INTERIOR DOORS, EXCEPT FIRE DOORS WHICH MAY HAVE A MAXIMUM EFFORT OF 15 LBS. OF FORCE APPLIED AT RIGHT ANGLES TO THE DOOR.

E. WHEN ADDITIONAL DOORS ARE PROVIDED FOR EGRESS PURPOSES, THEY SHALL COMPLY WITH ALL PROVISIONS OF CBC 1008.

F. SWINGING DOORS AND GATE SURFACES WITHIN 10 INCHES OF THE FINISH FLOOR OR GROUND MEASURED VERTICALLY SHALL

HAVE A SMOOTH SURFACE ON THE PUSH SIDE EXTENDING THE FULL WIDTH OF THE DOOR OR GATE PER PER CBC SECTION 11B-404.2.10.

G. RATED DOORS MAY BE UNDERCUT A MAXIMUM OF 3/4" PER NFPA80 4.8.4.1, BUT SHALL BE 1/4" U.N.O.

H. FIRE DOORS AND FRAMES SHALL BE LABELED IN ACCORDANCE WITH CBC SECTION 716.5.7.1 AND 716.5.7.4.

I. SMOKE AND DRAFT CONTROL DOORS SHALL HAVE AN APPROVED "S" RATING PER SECTION 716.5.7.3.

J. ALL HARDWARE SHALL BE LEVER TYPE OR PANIC TYPE MOUNTED AT HEIGHT INDICATED IN THE SPECIFICATIONS AND SHALL BE MOUNTED NOT LESS THAN 34" NOR HIGHER THAN 44" ABOVE FINISH FLOOR.

K. DOOR CLOSERS SHALL BE ADJUSTED SUCH THAT FROM AN OPEN POSITION OF 70 DEGREES THE DOOR WILL TAKE A MINIMUM OF THREE SECONDS TO MOVE 3" FROM THE LATCH MEASURED FROM LEADING EDGE OF THE DOOR. FROM AN OPEN POSITION OF 90 DEGREES THE DOOR WILL TAKE A MINIMUM OF FIVE SECONDS TO MOVE 12" FROM THE LATCH MEASURED FROM LEADING EDGE OF THE DOOR.

L. OPERATION OF ELECTRIC EXIT HARDWARE (ELECTRIC PANIC DEVICES) SHALL UNLOCK THE DOOR TO PROVIDE EGRESS.

M. LOSS OF POWER TO ELECTRIC EXIT HARDWARE (ELECTRIC PANIC DEVICES) SHALL AUTOMATICALLY UNLOCK THE DOOR (FAIL SAFE) TO PROVIDE EGRESS.

N. PROVIDE SAFETY GLAZING IN ACCORDANCE WITH CHAPTER 26 OF THE CALIFORNIA BUILDING CODE AND AS HEREIN IDENTIFIED.

O. VISION LIGHTS WITHIN DOORS SHALL BE LOCATED SUCH THAT THE BOTTOM OF THE GLASS DOES NOT EXCEED 43 INCHES ABOVE THE FINISH FLOOR.

P. ALL OVERALL WINDOW DIMENSIONS SHOWN ARE MEASURED TO ROUGH OPENING, TYPICAL.

Q. ALLOW FOR AND PROVIDE SHIM SPACE AT ALL STOREFRONT AND CURTAIN WALL WINDOW FRAMES, REFER TO DETAILS.

R. REFER TO WINDOW DETAILS FOR ROUGH OPENING REFERENCE POINTS.

S. FOR GENERAL EXTERIOR WINDOW AND DOOR FLASHING NOTES, REFER TO:----

DOOR HARDWARE GROUPS
REFER TO DOOR HARDWARE SPECIFICATION SECTION 08 71 00 FOR ADDITIONAL INFORMATION GROUP NO. 01 – EXTERIOR STOREFRONT (SINGLE)
1 EA CONT. HINGE 112XY TWP 628 IVE
1 EA ELEC PANIC HARDWARE RX-QELX-PA-AX-98-NL-OP-110MD 626 VON 1 EA LONG DOOR PULL 9264F 36" 20" O 630 IVE
1 EA OH STOP 100S 630 GLY
1 EA SURFACE CLOSER 4040XP EDA 689 LCN
1 SET SEAL SET WEATHERSTRIP BY DOOR/FRAME MANUFACTURER
1 EA DOOR SWEEP 39A A ZER
1 EA THRESHOLD PER DETAIL A ZER
CARD READER - WORK OF DIVISION 28
POWER SUPPLY - WORK OF DIVISION 28
GROUP NO. 02 – EXTERIOR LAB
1 EA CONT. HINGE 700 EPT 630 IVE
1 EA POWER TRANSFER EPT10 689 VON
1 EA ELEC PANIC HARDWARE RX-QELX-PA-AX-98-L-NL-06 626 VON 1 EA RIM CYLINDER 20-057 626 SCH
1 EA SURF. AUTO OPERATOR 9542 AS REQ (120/240 VAC) ANCLR LCN 2 EA SWITCH 8310-806R LCN
2 EA ACTUATOR, TOUCH 8310-836T 630 LCN
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA GASKETING 188SBK PSA BK ZER
1 EA DOOR SWEEP 39A A ZER
1 EA THRESHOLD PER DETAIL A ZER
CARD READER - WORK OF DIVISION 28
POWER SUPPLY - WORK OF DIVISION 28
GROUP NO. 03 – EXTERIOR LAB EQUIPMENT ROOM
1 EA CONT. HINGE 700 TW8 630 IVE
1 EA ELEC PANIC HARDWARE RX-PA-AX-98-L-M996-06-FSE 626 VON 1 EA RIM CYLINDER 20-057 626 SCH
1 EA SURFACE CLOSER 4040XP SCUSH 689 LCN
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA HEADER RAIN DRIP 142AA DOOR WIDTH + 4" AA ZER
1 EA GASKETING 188SBK PSA BK ZER
1 EA DOOR SWEEP 39A A ZER
1 EA THRESHOLD PER DETAIL A ZER
CARD READER - WORK OF DIVISION 28
POWER SUPPLY - WORK OF DIVISION 28
GROUP NO. 04 – EXTERIOR STOREFRONT
1 EA CONT. HINGE 112XY 628 IVE
1 EA PANIC HARDWARE PA-AX-98-EO 626 VON
1 EA SURFACE CLOSER 4040XP SCUSH 689 LCN
1 SET SEAL SET WEATHERSTRIP BY DOOR/FRAME MANUFACTURER
1 EA DOOR SWEEP 39A A ZER
1 EA THRESHOLD PER DETAIL A ZER
GROUP NO. 05 – EXTERIOR ELECTRICAL ROOM
4 EA HINGE 5BB1 4.5 X 4.5 NRP 630 IVE
1 EA PANIC HARDWARE PA-AX-98-L-NL-06 626 VON
1 EA RIM CYLINDER 20-057 626 SCH
1 EA SURFACE CLOSER 4040XP SCUSH 689 LCN
1 EA HEADER RAIN DRIP 142AA DOOR WIDTH + 4" AA ZER
1 EA GASKETING 188SBK PSA BK ZER
1 EA DOOR SWEEP 39A A ZER
1 EA THRESHOLD PER DETAIL A ZER
GROUP NO. 06 – EXTERIOR WORK ROOM
1 EA CONT. HINGE 700 TW8 630 IVE
1 EA ELEC PANIC HARDWARE RX-PA-AX-98-L-M996-06-FSE 626 VON 1 EA RIM CYLINDER 20-057 626 SCH
1 EA SURFACE CLOSER 4040XP SCUSH 689 LCN
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA GASKETING 188SBK PSA BK ZER
1 EA DOOR SWEEP 39A A ZER
1 EA THRESHOLD PER DETAIL A ZER
CARD READER - WORK OF DIVISION 28
POWER SUPPLY - WORK OF DIVISION 28
GROUP NO. 07 – EXTERIOR FIRE RISER ROOM
4 EA HINGE 5BB1 4.5 X 4.5 NRP 630 IVE
1 EA STOREROOM LOCK L9080R 06A 626 SCH
1 EA SURFACE CLOSER 4040XP SHCUSH 689 LCN
1 EA HEADER RAIN DRIP 142AA DOOR WIDTH + 4" AA ZER
1 EA GASKETING 188SBK PSA BK ZER
1 EA DOOR SWEEP 39A A ZER
1 EA THRESHOLD PER DETAIL A ZER
GROUP NO. 08 – EXTERIOR LOBBY ENTRANCE (DOUBLE)
2 EA CONT. HINGE 112XY EPT 628 IVE
2 EA POWER TRANSFER EPT10 689 VON
1 EA ELEC PANIC HARDWARE RX-QELX-PA-AX-9849-EO-LBL 626 VON 1 EA ELEC PANIC HARDWARE RX-QELX-PA-AX-9849-NL-OP-110MD-LBL 626 VON 1 EA RIM CYLINDER 20-057 626 SCH
2 EA LONG DOOR PULL 9264F 36" 20" O 630 IVE
2 EA OH STOP 100S 630 GLY
2 EA SURFACE CLOSER 4040XP EDA 689 LCN
1 SET SEAL SET WEATHERSTRIP BY DOOR/FRAME MANUFACTURER
2 EA DOOR SWEEP 39A A ZER
1 EA THRESHOLD PER DETAIL A ZER
CARD READER - WORK OF DIVISION 28
POWER SUPPLY - WORK OF DIVISION 28
GROUP NO. 09 – INTERIOR BREAK ROOM
1 EA CONT. HINGE 112XY 628 IVE
1 EA PASSAGE SET ND10S RHO 626 SCH
1 EA FLOOR STOP FS439 682 IVE
1 EA DOOR BOTTOM 364AA AA ZER
1 EA THRESHOLD PER DETAIL A ZER
1 SET BULB SEAL BY AL FRAME MFR
GROUP NO. 10 – MDF ROOM
3 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA EU STOREROOM LOCK ND80RDEU RHO RX CON 12V/24V DC 626 SCH 1 EA SURFACE CLOSER 4040XP 689 LCN
1 EA WALL STOP WS401/402CVX 626 IVE
1 EA GASKETING 188SBK OR BY AL FRAME MFR BK ZER
CARD READER - WORK OF DIVISION 28
POWER SUPPLY - WORK OF DIVISION 28
GROUP NO. 11 – LAB INTERIOR
3 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA EU STOREROOM LOCK ND80RDEU RHO RX CON 12V/24V DC 626 SCH 1 EA SURFACE CLOSER 4040XP EDA 689 LCN
1 EA WALL STOP WS401/402CVX 626 IVE
CARD READER - WORK OF DIVISION 28
POWER SUPPLY - WORK OF DIVISION 28
GROUP NO. 12 – BUNK ROOM
3 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA ENTRANCE/OFFICE LOCK ND50RD RHO 626 SCH
1 EA SURFACE CLOSER 4040XP 689 LCN
1 EA WALL STOP WS401/402CVX 626 IVE
1 EA GASKETING 188SBK OR BY AL FRAME MFR BK ZER
GROUP NO. 13 – MECHANICAL ROOM
3 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA ENTRANCE/OFFICE LOCK ND50RD RHO 626 SCH
1 EA SURFACE CLOSER 4040XP SCUSH 689 LCN
1 EA GASKETING 188SBK OR BY AL FRAME MFR BK ZER
GROUP NO. 14 - OFFICE
3 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA ENTRANCE/OFFICE LOCK ND50RD RHO 626 SCH
1 EA WALL STOP WS401/402CVX 626 IVE
GROUP NO. 15 – CONFERENCE ROOM
4 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA PASSAGE SET ND10S RHO 626 SCH
1 EA WALL STOP WS401/402CVX 626 IVE
GROUP NO. 16 – LOCKER ROOM
4 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA PASSAGE SET ND10S RHO 626 SCH
1 EA SURFACE CLOSER 4040XP 689 LCN
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA WALL STOP WS401/402CVX 626 IVE
GROUP NO. 17 – JANITOR ROOM
3 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA STOREROOM LOCK ND80RD RHO 626 SCH
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
GROUP NO. 18 – STORAGE ROOM
3 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA STOREROOM LOCK ND80RD RHO 626 SCH
1 EA FLOOR STOP FS439 682 IVE\
RECORD ROOM:

CARD READER - WORK OF DIVISION 28
POWER SUPPLY - WORK OF DIVISION 28
GROUP NO. 19 – RESTROOM (UNISEX)
3 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA PRIVACY LOCK W/ OUTSIDE INDICATOR ND40S RHO OS-OCC 626 SCH 1 EA SURFACE CLOSER 4040XP 689 LCN
1 EA WALL STOP WS401/402CVX 626 IVE
GROUP NO. 20 (UNIFORM CLOSET)
6 EA HINGE 5BB1 4.5 X 4.5 652 IVE
1 EA MANUAL FLUSH BOLT FB358 626 IVE
1 EA STOREROOM LOCK ND80RD RHO 626 SCH
2 EA OH STOP 450S 630 GLY
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/2
0/2
0 2
4 11:2
4:3
9 A
M
C:\U
s
ers\k
ale
k
s
a
n
dro
v\O
n
e
Driv
e - Willia
m
s
&
P
a
d
d
o
n\D
o
c
u
m
e
nts\210
015.01_
CIT
Y
O
F
R
O
S
E
VIL
L
E
_
D
C
W
W
T
P
A
D
MIN
B
L
D
G
_A
2 2
_
k
ale
k
s
a
n
dro
v
4 T
4 5

5.rvt
A-801

DOOR SCHEDULE

DCWWTP OPERATIONS

AND LAB BLDG
May 29, 2024
210015.0119six
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
311 VERNON ST
ROSEVILLE, CA 95768
90% CD - PERMIT SET

DOOR SCHEDULE

MARK FIRE RATING

SIZE DOOR FRAME DETAILS

SS TYPE MATERIAL FINISH TYPE MATERIAL FINISH HEAD JAMB SILL PANIC HARDWARE HARDWARE GROUP NOTESWIDTH HEIGHT THICKNE 101.1 NR 6'-0" 8'-0" 1 3/4" 7 AL AL KNOCK DOWN AL AL 14/A-710 14/A-710 16/A-710 P.H. 8 EXT STOREFRONT 101.2 NR 3'-0" 8'-0" 1 3/4" 6 AL AL AL AL - - INT STOREFRONT 102.1 NR 3'-0" 8'-0" 1 3/4" 6 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 14/A-711 - 15 103.1 NR 3'-0" 7'-0" 1 3/4" 3 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 14 104.1 NR 3'-0" 7'-0" 1 3/4" 3 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 14 105.1 NR 3'-0" 7'-0" 1 3/4" 3 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 14 107.1 NR 3'-0" 8'-0" 1 3/4" 6 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 15 INT STOREFRONT 108.1 NR 3'-0" 8'-0" 1 3/4" 6 AL AL KNOCK DOWN AL AL 14/A-710 14/A-710 16/A-710 - 1 EXT STOREFRONT 110.1 NR 3'-0" 7'-0" 1 3/4" 3 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 14 111.1 NR 3'-0" 7'-0" 1 3/4" 3 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 14 112.1 NR 4'-0" 9'-0" 1 3/4" 4 HM SP HM HM P 10/A-711 13/A-711 11/A-711 P.H. 2 112.2 NR 3'-0" 7'-0" 1 3/4" 3 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 11 113.1 NR 3'-0" 8'-0" 1 3/4" 5 HM SP HM HM P 10/A-711 13/A-711 11/A-711 - 6 114.1 NR 3'-0" 7'-0" 1 3/4" 3 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 14 115.1 NR 3'-0" 7'-0" 1 3/4" 3 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 14 116.1 NR 3'-0" 7'-0" 1 3/4" 1 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 18 117.1 NR 3'-0" 7'-0" 1 3/4" 1 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 18 118.1 NR 3'-0" 8'-0" 1 3/4" 6 AL AL KNOCK DOWN AL AL 14/A-710 20/A-711 16/A-710 - 4 EXT STOREFRONT 118.2 NR 6'-0" 7'-0" 1 3/4" 2 WD WS KNOCK DOWN AL AL 1/A-712 2/A-712 - 20 118.3 NR 6'-0" 7'-0" 1 3/4" 2 WD WS KNOCK DOWN AL AL 1/A-712 2/A-712 - 20 118.4 NR 3'-0" 8'-0" 1 3/4" 6 AL AL KNOCK DOWN AL AL 14/A-710 14/A-710 16/A-710 P.H. 1 EXT STOREFRONT 119.1 NR 3'-0" 7'-0" 1 3/4" 1 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 19 120.1 NR 3'-0" 7'-0" 1 3/4" 1 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 19 121.1 NR 3'-0" 7'-0" 1 3/4" 1 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 17 122.1 NR 3'-0" 7'-0" 1 3/4" 1 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 16/A-711 - 16 123.1 NR 3'-0" 7'-0" 1 3/4" 1 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 16/A-711 - 16 126.1 20 MIN. 3'-0" 7'-0" 1 3/4" 1 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 12 127.1 20 MIN. 3'-0" 7'-0" 1 3/4" 1 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 12 128.1 20 MIN. 3'-0" 7'-0" 1 3/4" 1 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 12 129.1 20 MIN. 3'-0" 7'-0" 1 3/4" 1 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 12 130.1 20 MIN. 3'-0" 7'-0" 1 3/4" 1 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 12 131.1 20 MIN. 3'-0" 7'-0" 1 3/4" 1 WD WS KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 12 132.1 NR 3'-0" 7'-0" 1 3/4" 1 HM KNOCK DOWN AL AL 1/A-712 2/A-712 - 13 133.1 NR 3'-0" 7'-0" 1 3/4" 1 HM KNOCK DOWN AL AL 1/A-712 2/A-712 - 10 134.1 NR 3'-0" 8'-0" 1 3/4" 1 HM SP HM HM P 10/A-711 13/A-711 11/A-711 - 5 135.1 NR 3'-0" 8'-0" 1 3/4" 1 HM SP HM HM P 10/A-711 13/A-711 11/A-711 - 7 136.1 NR 4'-0" 8'-0" 1 3/4" 1 HM SP HM HM P 10/A-711 13/A-711 11/A-711 - 3 136.2 NR 3'-0" 1'-0 5/8" ROOF ACCESS HATCH
137.1 NR 3'-0" 8'-0" 1 3/4" 6 AL AL KNOCK DOWN AL AL 14/A-710 14 & 15/A-710 16/A-710 - 1 EXT STOREFRONT 137.2 NR 3'-0" 8'-0" 1 3/4" 6 AL AL KNOCK DOWN AL AL 8B/A-711 8C/A-711 - 2 INT STOREFRONT NO. DATE DESCRIPTION
1 8/28/24 PC Comments
1 1
2/28/25

BID SET (PRELIMINARY)

WINDOW GENERAL NOTES
A. FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION.

B. ALL OVERALL WINDOW DIMENSIONS SHOWN ARE MEASURED TO ROUGH OPENING, TYPICAL.

C. PROVIDE SAFETY GLAZING IN ACCORDANCE WITH CALIFORNIA BUILDING CODE AND AS HEREIN LISTED.

D. ALLOW FOR AND PROVIDE SHIM SPACE AT ALL STOREFRONT AND CURTAIN WALL WINDOW FRAMES, REFER TO DETAILS.

E. REFER TO WINDOW DETAILS FOR ROUGH OPENING REFERENCE POINTS.

F. FOR WINDOW DETAILS REFER TO SHEET...

G. GLAZING IN DOORS, GLAZING WITHIN 18" OF FLOOR, OR GLAZING WITHIN 24" OF A DOOR AND LESS THAN 60" ABOVE WALKING SURFACE SHALL BE TEMPERED SAFETY GLAZING.

GLAZING GENERAL NOTES
A. EXTERIOR WINDOWS, SKYLIGHTS AND EXTERIOR GLAZED DOOR ASSEMBLIES SHALL BE CONSTRUCTED OF MULTI-PANED GLAZING WITH A MINIMUM OF ONE TEMPERED PANE MEETING THE REQUIREMENTS OF SECTION R308 SAFETY GLAZING.

B. EMERGENCY ESCAPE & RESCUE OPENINGS SHALL BE PER CBC 1031.3 a. MINIMUM SIZE PER CBC 1031.3.1
• EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5.7 SF • EXCEPTION: MINIMUM NET CLEAR OPENING FOR GRADEFLOOR EMERGENCY ESCAPE AND RESCUE OPENINGS = 5 SF MIN b. MINIMUM DIMENSIONS PER CBC 1031.3.2
• MINIMUM NET CLEAR OPENING HEIGHT = 24"
• MINIMUM NET CLEAR OPENING WIDTH = 20"
c. MAXIMUM HEIGHT FROM FLOOR PER CBC 1031.3.3
• EMERGENCY ESCAPE OPENINGS SHALL HAVE BOTTOM OF CLEAR OPENING 44" MAXIMUM FROM THE FLOOR

LEGEND - GLAZING
T1 TEMPERED SAFETY GLAZING:

CATEGORY CLASS I PER CPSC 16 SFR 1201 PER CBC TABLE 2406 OR CATEGORY CLASS B PER ANSI Z97.1 PER CBC TABLE 2406(2) T2 TEMPERED SAFETY GLAZING:

CATEGORY CLASS II PER CPSC 16 SFR 1201 PER CBC TABLE 2406 OR CATEGORY CLASS A PER ANSI Z97.1 PER CBC TABLE 2406(2)

FR FIRE RESISTANT GLAZING LOCATIONS
PRODUCT: TECHNICAL GLASS PRODUCTS, FIRE LITE PLUS (FIRE AND SAFETY RATED) IN 20 MIN., 45 MIN. AND/OR 60 MIN. RATING AS INDICATED IN SCHEDULES.

GLAZING TYPES:
1" LOW-E: TYPICAL AT EXTERIOR WINDOWS & DOORS, U.N.O.
1/4" CLEAR: TYPICAL AT INTERIOR WINDOWS & DOORS, U.N.O. 1" LOW-E SPANDREL: WHERE INDICATED ON DRAWINGS
7'-0"
3'-0"
T1
3'-0"
24 A-711
24 A-711
24 A-711
2 6'-0"
(4 EQUAL)
12'-0"
4'-0"
2 A-710
1 A-710
3 A-710
2 A-710
T1 T1 T1 T1 T1 T1 T1
T1 T1
10'-0"
3'-0"
28'-8"
1 1
A-710
2 A-710
4 A-710
T1
12 A-710
12 A-710
14 A-710
14 A-710
2 A-710
(4 EQUAL)
12'-10"

OPENING
DOOR
(4 EQUAL)
6 1/2" 12'-3 1/2"
T1
8'-0" 2'-0"
(2 EQUAL)
6'-0"
2 A-710
1 A-710
3 A-710
2 A-710
8'-0" 2'-0"
(4 EQUAL)
18'-6"
1 A-710
3 A-710
2 A-710
2 A-710
3'-0" 7'-0"
(3 EQUAL)
8'-0"
T1 T1 T1
1 A-710
12 A-710
3 A-710
2 A-710
12 A-710
2 A-710
3'-0"
10'-0"
T1 T1 T1 T1 T1 T1 T1 T1
T1 T1
28'-8"
3'-3" 3'-2" 3'-2" 3'-2"
1 T1 2
A-710
12 A-710
12 A-710
4 A-710
14 A-710
1 A-710
14 A-710
2 A-710
EQ EQ EQ EQ 3'-0 7/8"
1 3'-0" 7'-0"
(2 EQUAL)
5'-4"
5'-2"
23 A-710
12 A-710
12 A-710
1 A-710
24 A-710
23 A-710
2 A-710
3'-0" 7'-0"
2'-8"
5'-2"
23 A-710
24 A-710
1 A-710
12 A-710
T1 T1 T1
8'-4 1/2"
10'-0" 10" 6'-8"
3'-0"
5" 2'-7 1/2" 2'-8" 2'-8" 2'-8" 2'-8"
4'-5 1/4"
13'-3 1/2"
23 A-710
12 A-710
4 A-710
12 A-710
2 A-710
10 A-710
12 A-710
10 A-710
9 A-710
15 A-730

EDGE OF MULLION ALIGN

W/STOREFRONT BELOW
CL CL
T1 T1
3'-0"
10'-0" 10" 6'-8"
T1 T1
12'-3 1/8"
EQ. 3'-1" 3'-1" EQ. 4 1/2"
1 T1
2 A-710
14 A-710
2 A-710
12 A-710
10 A-710
10 A-710
4 A-710
12 A-710
22 A-710
9 A-710
2'-8" 7'-4"
5'-2"
(3 EQUAL)
8'-0"
23 A-710
12 A-710
1 A-710
12 A-710
23 A-710
24 A-710 T1
T1
11'-4"
8'-2"
10'-0"
1 2'-10" 7'-2"
T1
T1 T1

EQ EQ EQ
6 A-710
12 A-710
4 A-710
12 A-710
5 A-710
15 A-710
14 A-710
14 A-710
T1 T1 T1T1
4 A-710
12 A-710
6 A-710
12 A-710
6 A-710
5 A-710
4'-8" 3'-4"
2'-8"
23 A-710
SIM.
23 A-710
SIM.
7 A-710
18 A-711
6'-6" 2'-0"
2'-0"
2 A-710
1 A-710
2 A-710
7 A-710

FROSTED
GLASS
3'-8" 4'-10"
4'-0"
2 A-710
2 A-710
1 A-710
7 A-710
T1
1 T1
10'-0"
8'-2"
5'-7"
5 A-710
12 A-710
4 A-710
20 A-711
19 A-711
14 A-710
10'-4 3/4"
8'-0"
T1
1 T1 T1

EQ EQ EQ
8 A-711
8 A-711
8 A-711
8 A-711
8 A-711
8 A-711
7'-0"
5'-2 1/4"
T1
1 8
A-711
8 A-711
8 A-711
8 A-711
8 A-711
T1
1 8'-0"
5'-5 3/4"
8 A-711
8 A-711
8 A-711
8 A-711
8 A-711
1 8'-0"
12'-0"
T1 T1 T1

EQ EQ EQ
8 A-711
8 A-711
8 A-711
8 A-711
8 A-711
8 A-711
T1
1 7'-0"
5'-0 1/2"
8 A-711
8 A-711
8 A-711
8 A-711
8 A-711
+/- 17'-8 3/16" 2'-0"
28'-8"
3'-0 7/8"
1 A-710
2 A-710
3 A-710
2 A-710
3'-3" EQ EQ EQ EQ EQ EQ EQ
1 1
1'-4 1/4"
4'-6 1/2"
1 T1
1 T1
1'-8 1/4"
8'-0"
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/2
0/2
0 2
4 11:2
4:4
6 A
M
C:\U
s
ers\k
ale
k
s
a
n
dro
v\O
n
e
Driv
e - Willia
m
s
&
P
a
d
d
o
n\D
o
c
u
m
e
nts\210
015.01_
CIT
Y
O
F
R
O
S
E
VIL
L
E
_
D
C
W
W
T
P
A
D
MIN
B
L
D
G
_A
2 2
_
k
ale
k
s
a
n
dro
v
4 T
4 5

5.rvt
A-811
WINDOW

SCHEDULE

DCWWTP OPERATIONS

AND LAB BLDG
May 29, 2024
210015.0119six
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
311 VERNON ST
ROSEVILLE, CA 95768
90% CD - PERMIT SET

KEYNOTES
1/4" = 1'-0"

WINDOW - A
1/4" = 1'-0"

WINDOW - B
1/4" = 1'-0"

WINDOW - C
1/4" = 1'-0"

WINDOW - D
1/4" = 1'-0"

WINDOW - E
1/4" = 1'-0"

WINDOW - F
1/4" = 1'-0"

WINDOW - G
1/4" = 1'-0"

WINDOW - H
1/4" = 1'-0"

WINDOW - I
1/4" = 1'-0"

WINDOW - J
1/4" = 1'-0"

WINDOW - K
1/4" = 1'-0"

WINDOW - L
1/4" = 1'-0"

WINDOW - M
1/4" = 1'-0"

WINDOW - N
1/4" = 1'-0"

WINDOW - O
1/4" = 1'-0"

WINDOW - P
1/4" = 1'-0"

WINDOW - Q
1/4" = 1'-0"

WINDOW - R
1/4" = 1'-0"

WINDOW - S
1/4" = 1'-0"

WINDOW - T
1/4" = 1'-0"

WINDOW - U
1/4" = 1'-0"

WINDOW - V
1/4" = 1'-0"

WINDOW - W
1/4" = 1'-0"

WINDOW - X
SHEET NOTES A-811
1 DOOR OPENING PER DOOR SCHEDULE
2 EMERGENCY ESCAPE & RESCUE OPENINGS SHALL COMPLY W/CBC 1031.3 1/4" = 1'-0"

WINDOW - Y
1/4" = 1'-0"

WINDOW-Z
NO. DATE DESCRIPTION
1 8/28/24 PC Comments
2/28/25

BID SET (PRELIMINARY)
S

S TA TE
O F
CA
L
I

FO R N I A

STRUCTURAL
R
ROF
E
P

ED ER T IS GE
S
I
N

ENGINEER
O
AL
600 Q STREET, SUITE 200
SACRAMENTO, CA 95811
916 443 0303
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP
REVISIONS #

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
WILLIAM B.

RADER
No. 3592
10/23/2024 5:26:06 PM c:\revit\2023-0123_DRY CREEK WWTP_rvt22_CENTRAL_Francisco_O_Rodriguez.rvt S100
COVER

DCWWTP OPERATIONS

AND LAB BLDG
Author 2100 15.01
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP

STRUCTURAL SHEET INDEX
S100 COVER
S101 GENERAL NOTES
S111 STRUCT SPECIAL INSPECTIONS & TESTING
S121 PLAN NOTES
S200 CURB PLAN
S201 FOUNDATION PLAN
S202 ROOF FRAMING PLAN
S301 BUILDING SECTIONS
S302 BUILDING SECTIONS
S501 TYPICAL CONCRETE DETAILS
S511 TYPICAL FRAMING AND NAILING DETAILS
S512 TYPICAL SHEAR WALL AND HOLDOWN DETAIL
S513 INTERIOR TYPICAL NON-STRUCTURAL DETAILS
S514 TYPICAL I-JOIST DETAILS
S515 TYPICAL WOOD TRUSS NOTES AND DETAILS
S516 MISC DETAILS
3D - BUEHLER STRUCTURALNO. DATE DESCRIPTION

BID SET (PRELIMINARY)

DESIGN CRITERIA
100SN002

1. CODES AND STANDARDS
2022 CALIFORNIA BUILDING CODE (CBC)
ASCE 7-16
ACI 318-19
AISC 360-16, 341-16, 358-16
AISI S100-16 w/ S2-20, S240-20, S400-20
TMS 402/602-16
2018 NDS, 2021 SDPWS

2. VERTICAL LOADS
SOLAR ZONE ROOF DEAD LOAD = 4 PSF
(INCLUDES 4 PSF FUTURE PV LOAD)
ROOF LIVE LOAD = 20 PSF

LIVE LOADS ARE REDUCED WHERE
PERMITTED BY CODE.

3. SOILS VALUES

ALLOWABLE SOILS PRESSURE
A. DL + LL 3000 PSF
B. DL + LL + SEISMIC 4000 PSF

FOOTING
MINIMUM DEPTH = 18"
MINIMUM WIDTH = 12"
SEISMIC:

SITE CLASS D
SS = 0.45 ; SDS = 0.43
S1 = 0.22 ; SD1 = 0.473
R = 6.5 ; IE = 1.0
ΩO = 3.0 ; CD = 4.0
IP = 1.0 TYPICAL
IP = 1.5 PER ASCE 7-16 SECT 13.1.3
RISK CATEGORY: II
SEISMIC DESIGN CATEGORY: D

SEISMIC BASE SHEAR
= 26 KIPS (NS DIR.)
= 26 KIPS (EW DIR.)
SEISMIC FORCE RESISTING SYSTEM:

LIGHT FRAMED WOOD BEARING

SHEAR WALL
ANALYSIS PROCEDURE: EQUIVALENT

LATERAL FORCE
WIND:

V = 95 MPH
RISK CATEGORY: II
EXPOSURE CATEGORY: C
GCPI = ±0.18

4. LATERAL LOADS
1 1
2x12 1x8 2x12
FTG
WIDTH
PLAN

FOUNDATIONS
200SN001

1. THE BASIS OF DESIGN AND ALLOWABLE CAPACITIES OF THE FOUNDATION SYSTEM HAVE BEEN

PROPORTIONED IN ACCORDANCE WITH THE RECOMMENDATIONS OF GEOTECHNICAL REPORT # 4438.000.002 BY ENGEO DATED MAY 10,2023. THE CONTRACTOR SHALL OBTAIN THE GEOTECHNICAL REPORT FROM THE OWNER. THE STRUCTURAL ENGINEER IS NOT

RESPONSIBLE FOR THE ACCURACY OF THE INFORMATION PRESENTED IN THE GEOTECHNICAL REPORT.

2. FOUNDATIONS SHALL BEAR ON COMPETENT NATIVE SOIL OR COMPACTED FILL.

SEE NOTES AND DETAILS ON SHEET .

3. ALL FILLING, BACKFILLING AND COMPACTION SHALL BE DONE UNDER THE OBSERVATION OF A

REPRESENTATIVE OF THE GEOTECHNICAL ENGINEER AND MUST BE COMPACTED TO THE

MINIMUM DENSITY SPECIFIED IN ACCORDANCE WITH THE PROCEDURE OUTLINED IN THE GEOTECHNICAL REPORT.

4. BUILDING PAD CONSTRUCTION SHALL CONFORM TO THE REQUIREMENTS OF THE GEOTECHNICAL REPORT. THE EXTENT AND DEPTH OF OVEREXCAVATION AND PLACEMENT OF ENGINEERED FILL SHALL AT A MINIMUM BE AS SHOWN ON THE PLANS. FINAL DEPTH AND

EXTENT OF EXCAVATION AND FILL SHALL BE DETERMINED AT TIME OF CONSTRUCTION BY A REPRESENTATIVE OF THE GEOTECHNICAL ENGINEER. FOUNDATION DEPTHS INDICATED ON PLANS ARE FOR ESTIMATING PURPOSES ONLY.

5. BOTTOMS OF ALL FOUNDATIONS SHALL BE LEVEL. CHANGES IN BOTTOM OF FOUNDATION

ELEVATION SHALL BE MADE ACCORDING TO STEPPED FOOTING DETAIL ON THE TYPICAL DETAIL SHEET.

6. FOUNDATION CONCRETE MAY BE PLACED DIRECTLY INTO NEAT

EXCAVATIONS PROVIDED THE EXCAVATIONS ARE STABLE
(AS DETERMINED BY A REPRESENTATIVE OF THE GEOTECHNICAL
ENGINEER). OTHERWISE, FOUNDATIONS SHALL BE FULLY
FORMED. USE MINIMUM PLANKING SHOWN TO PROTECT
AGAINST SLOUGHING, AS REQUIRED. PLANKING DOES
NOT REPLACE FORMWORK REQUIRED TO STABILIZE EXCAVATION.

7. THE SURFACE OF ALL HORIZONTAL CONSTRUCTION JOINTS SHALL BE CLEANED & ROUGHENED BY EXPOSING CLEAN AGGREGATE SOLIDLY EMBEDDED IN MORTAR MATRIX.

8. NOTIFY THE STRUCTURAL ENGINEER 48 HOURS BEFORE CASTING FOUNDATIONS.

9. A REPRESENTATIVE OF THE GEOTECHNICAL ENGINEER SHALL ADVISE THE BUILDING OFFICIAL IN WRITING THAT:

A. THE BUILDING PAD WAS PREPARED IN ACCORDANCE WITH THE GEOTECHNICAL REPORT.

B. THE UTILITY TRENCHES HAVE BEEN PROPERLY BACKFILLED AND COMPACTED.

C. THE FOUNDATION EXCAVATION DEPTH AND MATERIAL ARE ADEQUATE TO ACHIEVE DESIGN BEARING CAPACITY.

D. FORMING COMPLIES WITH THE GEOTECHNICAL REPORT AND APPROVED PLAN.

S501

CONCRETE
300SN001

1. CONCRETE SHALL ATTAIN 28 DAY COMPRESSIVE STRENGTH AS REQUIRED IN NOTE #28.

MAXIMUM SLUMP SHALL NOT EXCEED 4 INCHES.

2. CONCRETE MIX DESIGNS SHALL BE PREPARED ACCORDING TO ACI 318-14 CHAPTER 26.4 AND ACI 301-10 SECTION 4, REVIEWED BY OWNER'S TESTING LABORATORY AND SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW.

3. CEMENTITIOUS MATERIALS:

CEMENT SHALL CONFORM TO ASTM C-150 TYPE II OR V.

FLY ASH SHALL CONFORM TO ASTM C-618. MAX. QUANTITY OF FLY ASH SHALL BE 25% OR AS GIVEN IN SPECS.

4. CONCRETE AGGREGATES SHALL CONFORM TO ASTM C-33 FOR NORMAL WEIGHT CONCRETE AND ASTM C-330 FOR LIGHTWEIGHT CONCRETE.

5. NON-SHRINK GROUT OR DRYPACK SHALL CONSIST OF A PREMIXED NONMETALLIC FORMULA.

6. REINFORCING STEEL SHALL CONFORM TO ASTM A-615 GRADE 60 UNO. REINFORCING STEEL TO BE WELDED SHALL CONFORM TO ASTM A-706 GRADE 60. CONTRACTOR SHALL SUBMIT REBAR MILL CERTIFICATES. REINFORCING STEEL IN SPECIAL REINFORCED SHEAR WALLS OR MOMENT FRAMES, EXCEPT TIES AND HOOPS, SHALL CONFORM TO ASTM A-706.

7. ALL PREHEATING AND WELDING OF REINFORCING BARS SHALL BE DONE IN ACCORDANCE WITH AWS D1.4 LATEST EDITION AND SHALL BE CONTINUOUSLY INSPECTED BY A QUALIFIED LABORATORY. CONTRACTOR SHALL FURNISH WPS FOR ALL REBAR WELDING TO THE LABORATORY.

8. REINFORCING STEEL SHALL BE FABRICATED ACCORDING TO "MANUAL OF STANDARD PRACTICE FOR REINFORCED CONCRETE CONSTRUCTION".

9. WIRE FABRIC SHALL CONFORM TO ASTM A1064.

10. DIMENSIONS SHOWN FOR LOCATION OF REINFORCING ARE TO THE FACE OF BARS LISTED AND DENOTE CLEAR COVERAGE. NON-PRESTRESSED, CAST-IN-PLACE CONCRETE COVERAGE SHALL BE AS FOLLOWS, UNO:

CONCRETE DEPOSITED DIRECTLY AGAINST GROUND (EXCEPT SLABS)--------- 3" CONCRETE EXPOSED TO GROUND OR WEATHER BUT PLACED IN FORMS:
#5 AND SMALLER-------------------------------------------------------------------------- 1-1/2" #6 AND LARGER--------------------------------------------------------------------------- 2" BEAMS & COLUMNS (TIES)------------------------------------------------------------------------- 1-1/2" BEAMS & COLUMNS (MAIN REINFORCING)-------------------------------------------------- 2"

CAST-IN-PLACE WALLS (EXTERIOR FACE & SOIL SIDE)-------------------------------- SEE ABOVE CAST-IN-PLACE WALLS (INTERIOR FACE-#11 & SMALLER)--------------------------- 3/4"

TILT-UP WALLS--------------------------------------------------------------------------------------- SEE DETAILS SLABS (ON FORMS)--------------------------------------------------------------------------------- 3/4" SLABS (ON GROUND)------------------------------------------------------------------------------- 2" CLEAR FROM TOP

11. SPLICES IN CONTINUOUS REINFORCEMENT SHALL BE LAPPED UNO, SEE SCHEDULE THIS SHEET. SPLICES IN ADJACENT BARS SHALL BE GREATER THAN 5'-0" APART. SPLICE

CONTINUOUS BARS IN SOIL-BEARING GRADE BEAMS, STRUCTURAL SLABS ON GRADE AND MAT FOUNDATIONS AS FOLLOWS UNO: TOP BARS AT CENTERLINE OF SUPPORT; BOTTOM BARS AT MID-SPAN. SPLICE CONTINUOUS BARS IN ELEVATED SLABS AND BEAMS, ETC. AS FOLLOWS UNO: TOP BARS AT MID-SPAN; BOTTOM BARS AT CENTERLINE OF SUPPORT. ALL BARS SIZE #14

AND LARGER SHALL BE CONTINUOUS FOR FULL LENGTH SHOWN OR SPLICED WITH MECHANICAL COUPLERS AS NOTED IN DETAILS. SPLICES IN WWF SHALL BE 1-1/2 MESHES WIDE.

12. THE MINIMUM CLEAR SPACING BETWEEN PARALLEL BARS IN A LAYER SHALL NOT BE LESS THAN THE LARGER OF BAR DIAMETER, 1", OR 33% GREATER THAN THE MAXIMUM AGGREGATE SIZE (NOMINAL), WHICHEVER IS GREATEST. THIS REQUIREMENT ALSO APPLIES TO THE CLEAR

SPACING BETWEEN DIFFERENT LAYERS OF PARALLEL BARS AND TO THE CLEAR DISTANCE BETWEEN A CONTACT LAP SPLICE AND ADJACENT SPLICES OR BARS.

13. ALL HOOKS SHALL BE STANDARD HOOKS UNLESS OTHERWISE SHOWN OR NOTED. AT WALLS,

PROVIDE HOOKS AT ENDS OF ALL REINFORCING AT ENDS, CORNERS AND INTERSECTIONS, UNO.

14. CONSTRUCTION JOINTS SHALL BE MADE ROUGH AND ALL LAITANCE REMOVED FROM THE SURFACE. CONCRETE MAY BE ROUGHENED BY CHIPPING THE ENTIRE SURFACE, SAND BLASTING, OR RAKING THE SURFACE TO PROVIDE 1/4" DEEP DEFORMATIONS.

15. REMOVE ALL DEBRIS FROM FORMS BEFORE CASTING ANY CONCRETE.

16. REINFORCING, DOWELS, BOLTS, ANCHORS, SLEEVES, ETC. TO BE EMBEDDED IN CONCRETE SHALL BE SECURELY POSITIONED BEFORE PLACING CONCRETE.

17. ANCHOR BOLTS (AB'S) CAST IN CONCRETE FOR WALL SILL AND LEDGER APPLICATIONS SHALL BE HEADED BOLTS WITH CUT THREADS CONFORMING TO ASTM F1554, UNO. REFER TO "WOOD"

NOTES FOR ADDITIONAL REQUIREMENTS FOR BOLTS IN CONTACT WITH PRESSURE TREATED OR FIRE RETARDANT MATERIAL. REFER TO 'STRUCTURAL STEEL' NOTE FOR REQUIREMENTS

FOR ANCHOR RODS (AR'S) CAST IN CONCRETE FOR COLUMN BASE PLATE AND STEEL EMBED APPLICATIONS.

18. WALLS SHALL BE CAST IN HORIZONTAL LAYERS OF 2'-0" MAXIMUM DEPTH.

19. CONCRETE IN WALLS, PIERS OR COLUMNS SHALL SET AT LEAST 2 HOURS BEFORE PLACING CONCRETE IN BEAMS, SPANDRELS, OR SLABS SUPPORTED THEREON.

20. HORIZONTAL WALL BARS IN MULTI-CURTAIN CAST IN PLACE WALLS SHALL BE STAGGERED.

21. DOWEL ALL VERTICAL REINFORCING IN WALLS AND COLUMNS FROM FOUNDATION WITH SAME SIZE BAR.

22. CONSOLIDATE CONCRETE PLACED IN FORMS BY MECHANICAL VIBRATING EQUIPMENT SUPPLEMENTED BY HAND-SPADING, RODDING OR TAMPING. USE EQUIPMENT AND

PROCEDURES FOR CONSOLIDATION OF CONCRETE IN ACCORDANCE WITH THE RECOMMENDED PRACTICES OF ACI 309 TO SUIT THE TYPE OF CONCRETE AND PROJECT CONDITIONS. CONCRETE SHALL NOT BE DROPPED THROUGH REINFORCING STEEL (AS IN WALLS) SO AS TO CAUSE SEGREGATION OF AGGREGATES. IN SUCH CASES HOPPERS AND

CHUTES OR TRUNKS OF VARIABLE LENGTHS SHALL BE USED SO THAT THE FREE UNCONFINED FALL OF CONCRETE SHALL NOT EXCEED 6 FEET.

23. NO WOOD SPREADERS ALLOWED. NO WOOD STAKES ALLOWED IN AREAS TO BE CONCRETED.

24. ADDITIONAL REINFORCING IN PRECAST OR TILT-UP PANELS REQUIRED FOR LIFTING STRESSES SHALL BE SUPPLIED BY CONTRACTOR.

25. PROVIDE #4x4'-0" DIAGONAL REINFORCING AT EACH REINFORCING LAYER OF SLAB AT ALL REENTRANT CORNERS TYPICAL UNO. THIS APPLIES TO SLAB ON GRADE, CONCRETE OVER METAL DECK, AND ELEVATED STRUCTURAL SLAB CONDITIONS.

26. ALL SAW CUTTING SHALL BE DONE AFTER INITIAL SET HAS OCCURRED TO AVOID TEARING OR DAMAGE BY THE SAW BLADE, BUT BEFORE INITIAL SHRINKAGE HAS OCCURRED.

27. NOTIFY STRUCTURAL ENGINEER A MINIMUM OF 48 HOURS BEFORE PLACING ANY CONCRETE.

28. CONCRETE STRENGTHS & MIX PROPERTIES:

F'C @ MAX AGGR MAX W/CM*
ITEM 28 DAYS SIZE WEIGHT RATIO
A. FOUNDATIONS 3000 PSI 1-1/2" NW 0.58
B. SLAB ON GRADE 3500 PSI 1" NW 0.45

SITE & MISCELLANEOUS - SEE CIVIL OR ARCH DRAWINGS
* W/CM = WATER : CEMENTITIOUS MATERIAL RATIO

STRUCTURAL STEEL
500SN001

1. FABRICATION, ERECTION AND MATERIALS SHALL CONFORM WITH THE AISC SPECIFICATION FOR

STRUCTURAL STEEL BUILDINGS, THE AISC SEISMIC PROVISIONS FOR STRUCTURAL STEEL

BUILDINGS AND THE AISC CODE OF STANDARD PRACTICE, LATEST EDITIONS ADOPTED BY THE BUILDING CODE SPECIFIED IN THE DESIGN CRITERIA NOTES, UNO.

2. ALL HOT ROLLED STEEL SHAPES, PLATES AND BARS SHALL BE NEW STEEL CONFORMING TO ASTM A6, UNO IN THE STRUCTURAL DRAWINGS. STRUCTURAL STEEL SHALL BE AS FOLLOWS:

A. WIDE FLANGE AND WT SHAPES: ASTM A992
B. M- AND S- SHAPES: ASTM A36
C. C- AND MC- SHAPES: ASTM A992
D. L- SHAPES: ASTM A572 GRADE 50
E. ROUND HSS: ASTM A500 GRADE C (Fy = 46 KSI)
F. RECTANGULAR HSS: ASTM A500 GRADE C (Fy = 50 KSI)
G. PIPE: ASTM A53, GRADE B (Fy = 35 KSI)
H. BASE PLATES UP TO 4” THICK: ASTM A572 GRADE 50
I. ALL OTHER PLATE MATERIAL: ASTM A572 GRADE 50, UNO
J. BUILT UP COLUMNS: ASTM A572 GRADE 50
K. PLATE GIRDERS: ASTM A572 GRADE 50
L. CONNECTION MATERIAL
a. COLUMN CONTINUITY PLATES AND DOUBLER PLATES: ASTM A572 GRADE 50 b. BRACED FRAME GUSSET PLATES: ASTM A572 GRADE 50

3. ALL STRUCTURAL STEEL SHALL RECEIVE A MINIMUM OF ONE SHOP COAT OF RED PRIMER PAINT.

DO NOT PAINT AREAS TO BE FIELD WELDED, FIREPROOFED, GALVANIZED, TO RECEIVE SLIPCRITICAL HIGH STRENGTH BOLTS, OR TO BE EMBEDDED IN CONCRETE. PROVIDE ADDITIONAL PAINTING AS NOTED IN THE SPECIFICATIONS.

4. ALL STRUCTURAL STEEL SHALL BE ERECTED PLUMB AND TRUE TO LINE. TEMPORARY BRACING

SHALL BE INSTALLED AND SHALL BE LEFT IN PLACE UNTIL OTHER MEANS ARE PROVIDED TO ADEQUATELY BRACE THE STRUCTURE. THE CONTRACTOR IS RESPONSIBLE FOR REVIEWING ALL BASE PLATE AND SUPPORT CONDITIONS DURING ERECTION AND BRACING AS REQUIRED. SEE AISC AND OSHA REQUIREMENTS.

5. GROUT BELOW BASE PLATES SHALL BE NON-METALLIC, NON-SHRINK GROUT WITH A MINIMUM COMPRESSIVE STRENGTH OF 8,000 PSI UNO. COLUMN BASE PLATES SHALL BE PROMPTLY

GROUTED AFTER STEEL FRAME HAS BEEN PLUMBED AND PRIOR TO INSTALLATION OF METAL DECKING.

6. STRUCTURAL STEEL BELOW GRADE SHALL HAVE 3 INCHES MINIMUM OF CONCRETE COVER.

7. STRUCTURAL BOLTS AND THREADED FASTENERS
A. BOLTED CONNECTIONS SHALL CONSIST OF UNFINISHED BOLTS CONFORMING TO ASTM F3125 GRADE A325 UNO.

B. WHERE HIGH-STRENGTH BOLTS ARE SPECIFIED, BOLTS CONFORMING TO ASTM F3125 GRADE A325 OR GRADE A490 SHALL BE PROVIDED AS INDICATED. HIGH STRENGTH BOLTS IN SLIPCRITICAL AND PRETENSION JOINTS SHALL CONFORM TO THE REQUIREMENTS OF ASTM F1852

FOR TWIST-OFF TYPE TENSION CONTROL BOLT PRETENSIONING OR BE PROVIDED WITH DIRECT TENSION INDICATOR WASHERS CONFORMING TO THE REQUIREMENTS OF ASTM F959.

C. ANCHOR RODS CAST IN CONCRETE OR MASONRY SHALL BE HEADED BOLTS WITH CUT THREAD, FULL DIAMETER BODY STYLE CONFORMING TO ASTM F1554 GRADE 36, 55 (WELDABLE PER S1 SUPPLEMENTARY REQUIREMENTS), OR GRADE 105 AS INDICATED ON DRAWINGS. IN LIEU OF

HEADED ANCHOR RODS, THREADED ROD CONFORMING TO THE ABOVE SPECIFICATIONS MAY

BE USED WITH A SINGLE NUT WELDED TO THE ROD OR DOUBLE NUTS TIGHTENED TO PREVENT ROTATION. ANCHOR ROD PROJECTION ABOVE TOP OF FOUNDATION SHALL BE AS NOTED ON THE DRAWINGS.

D. BOLTED CONNECTIONS SHALL HAVE WASHERS CONFORMING TO ASTM F436 UNO. WASHERS

MAY BE OMITTED AT SNUG-TIGHTENED AND SLIP-CRITICAL CONNECTIONS, EXCEPT WHERE REQUIRED BY THE RCSC SPECIFICATION FOR STRUCTURAL JOINTS, LATEST EDITION.

E. BASE PLATES SHALL HAVE NUTS AND WASHERS AT TOP AND BOTTOM OF PLATE. WASHERS FOR BASE PLATES SHALL BE A36 SQUARE OR CIRCULAR PLATE UNLESS ASTM F844 WASHERS ARE PERMITTED. SEE BASE PLATE DETAILS FOR PLATE WASHER SIZE AND PERMISSIBLE WASHER TYPE.

F. THREADED RODS SHALL CONFORM TO ASTM A36 UNLESS NOTED OTHERWISE ON THE DRAWINGS.

G. PINS: ALL PINS IN PIN CONNECTED MEMBERS SHALL CONFORM TO ASTM A36 OR ASTM A108 AS INDICATED ON THE DRAWINGS.

8. ADDITIONAL REQUIREMENTS FOR "SLIP-CRITICAL" BOLTED CONNECTIONS:

A. "SLIP-CRITICAL" CONNECTIONS (A325-SC DESIGN VALUES WITH SPECIAL INSPECTION) ARE

REQUIRED AT ALL MOMENT FRAME CONNECTIONS, BRACED FRAME CONNECTIONS, AT ALL

CONNECTIONS ALONG CHORD LINES AND DRAG LINES (AS NOTED ON PLANS), AND UNO, AT ALL BOLTS IN OVERSIZED OR SLOTTED HOLES.

B. THE SPECIAL INSPECTOR MUST BE PRESENT DURING THE INSTALLATION AND TIGHTENING OPERATION OF "SLIP-CRITICAL" CONNECTIONS.

9. PROVIDE 3/4" DIAMETER STITCH BOLTS AND RING FILLS, SPACED AT NOT MORE THAN 2'-0" ON CENTER FOR ALL DOUBLE ANGLE MEMBERS UNO.

10. AT WOOD TO STEEL PARALLEL CONTACT, BOLT WITH 1/2" DIAMETER BOLTS AT MAXIMUM 24"CC UNLESS NOTED OTHERWISE IN THE DRAWINGS.

11. BOLT HOLES SHALL BE AISC STANDARD HOLES UNLESS SPECIFIED OTHERWISE. USE STANDARD AISC GAGE AND PITCH FOR BOLTS EXCEPT AS NOTED OTHERWISE.

12. WELDING SHALL BE DONE BY THE ELECTRIC ARC PROCESS IN ACCORDANCE WITH AMERICAN WELDING SOCIETY STANDARDS, USING ONLY CERTIFIED WELDERS. ALL GROOVE WELDS SHALL HAVE COMPLETE PENETRATION UNLESS NOTED OTHERWISE. ALL ELECTRODES FOR WELDING SHALL COMPLY WITH AWS D1.1 AND D1.8 AS APPLICABLE, E70 SERIES MINIMUM.

13. WELD LENGTHS SPECIFIED ON PLANS ARE THE NET EFFECTIVE LENGTHS REQUIRED.

14. MINIMUM FILLET WELDS: (T = THICKNESS OF THINNER PART JOINED) 3/16" @ T < 1/2"
1/4" @ T < 3/4"
5/16" @ T > 3/4"

15. WELDING PROCEDURE SPECIFICATIONS (WPS) FOR SHOP AND FIELD PREQUALIFIED WELD JOINTS

AND WELD JOINTS QUALIFIED BY TEST SHALL BE SUBMITTED FOR REVIEW BY THE STRUCTURAL ENGINEER AND THE OWNER’S TESTING LABORATORY PRIOR TO FABRICATION. ALL WELDING

PROCEDURE ITEMS SUCH AS BASE METALS, WELDING PROCESSES, FILLER METALS AND JOINT DETAILS THAT MEET THE REQUIREMENTS OF AWS D1.1 SECTION 3 SHALL BE CONSIDERED AS PREQUALIFIED. ANY CHANGE OR SUBSTITUTION THAT IS BEYOND THE RANGE OR TOLERANCE OR REQUIREMENTS FOR PREQUALIFICATION SHALL BE QUALIFIED BY TEST PER AWS D1.1 SECTION 4 PART B. SUBMIT TEST REPORTS SHOWING SUCCESSFUL PASSAGE OF QUALIFICATION TESTS FOR ALL NON-PREQUALIFIED WELDING PROCEDURE SPECIFICATIONS.

METAL DECK NOTES
530SN001

1. PROVIDE METAL DECKING OF TYPE AND GAUGE AS SHOWN ON PLANS AND AS INDICATED IN THE METAL DECK SCHEDULE.

2. METAL FLOOR DECK SHALL BE COMPOSITE TYPE, CONFORMING TO ASTM A653, STRUCTURAL QUALITY, AND SHALL BE ZINC COATED PER ASTM A653, G60 COATING DESIGNATION.

3. METAL ROOF DECK SHALL CONFORM TO ASTM A653, STRUCTURAL QUALITY, AND SHALL BE ZINC COATED PER ASTM A653, G60 COATING DESIGNATION.

4. PRIOR TO FABRICATION, THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR THE METAL

DECKING, SHOWING DECK GAUGE, SIZE AND LAYOUT AS WELL AS CLOSURE CONDITIONS, WELDS TO SUPPORTS AND SIDE LAP DETAILS.

5. CONNECTION AND WELDING OF DECKING TO STRUCTURAL SUPPORTS AND DECK SIDE SEAMS SHALL BE AS SPECIFIED IN THE STRUCTURAL DRAWINGS. ALL ELECTRODES FOR WELDING SHALL COMPLY WITH AWS CODE, E60 SERIES MINIMUM.

6. ALL REINFORCED OPENINGS IN METAL DECK SHALL BE INSTALLED BY METAL DECK SUBCONTRACTOR.

7. AT METAL DECKS TO RECEIVE CONCRETE, ABSOLUTELY NO CONDUIT OR PIPING OF ANY TYPE IS TO BE PLACED HORIZONTALLY WITHIN THE DEPTH OF THE CONCRETE ABOVE THE METAL DECK.

8. AT METAL DECK WITHOUT CONCRETE FILL THE FOLLOWING MAY BE ATTACHED WITHOUT SPECIFIC APPROVAL OF THE STRUCTURAL ENGINEER: ACOUSTICAL TILE AND GYPSUM BOARD CEILINGS ONLY; NO PIPING, DUCTING OR CONDUIT. MAXIMUM CEILING WEIGHT - 3.5 PSF.

MAXIMUM WIRE HANGER LOAD = 60#.

9. WHERE SUSPENSION OR HANGER WIRES ARE REQUIRED BY OTHERS, VERIFY AND COORDINATE LOCATIONS, PATTERNS, SPACINGS, ETC. WITH THE APPROPRIATE TRADE. DRILL OR PUNCH HOLES AT BOTTOM OF DECK FLUTES OF SUFFICIENT SIZE TO PASS SUPPORT WIRES. WIRE SUPPORTS SHALL BE LOOPED AND SECURED WITH A MINIMUM OF THREE (3) TIGHT TURNS AROUND A MINIMUM 1-1/2" x 12" LONG FURRING CHANNEL OR NO. 3 x 12" LONG REINFORCING BAR CENTERED ABOVE THE HOLE AND LAID IN THE DECK FLUTES.

SILL ANCHOR BOLT WASHER SCHEDULE
WALL TYPE 2x4 2x6
2x8 & LARGER
1 SIDE SHTG
2x8 & LARGER
2 SIDES SHTG
WASHER

DESIGNATION
BPS 5/8-3 BPS 5/8-6 BPS 5/8-6
3GA x 3" x STUD
WIDTH - 1/2" w/
11/16"Ø @ CL
WOOD
600SN001

1. ALL STRUCTURAL WOOD SHALL CONFORM WITH THE FOLLOWING SPECIFICATIONS:

SPECIES COMBINATION SHALL BE DOUG FIR - LARCH PER WCLIB GRADING RULES #17 OR WWPA STANDARD GRADING RULES FOR WESTERN LUMBER. DOUGLAS FIR – LARCH (NORTH) AND

DOUGLAS FIR (SOUTH) ARE NOT PERMITTED WITHOUT APPROVAL FROM THE STRUCTURAL ENGINEER.
2x, 3x AND 4x MEMBERS - #2 UNO.
6x AND LARGER MEMBERS - #1 UNO.
2x DECKING - SELECT DEX
MEMBERS 3x AND LARGER SHALL BE FREE OF HEART CENTER
REDWOOD - CALIFORNIA REDWOOD, RIS.

SHEATHING - US PRODUCT STANDARD PS 1-09 AND PS2-10. APA RATED STRUCT 1/SHEATHING w/ EXTERIOR GLUE @ WALLS, FLOORS, & ROOFS UNO

PRESSURE TREATED DOUGLAS FIR - TYPE AS APPROPRIATE FOR EXTERIOR ABOVE GROUND USE AS SPECIFIED, BY AWPA.

2. ALL WOOD IN DIRECT CONTACT WITH CONCRETE SHALL BE PRESSURE TREATED, EXCEPT LEDGERS, WHICH DO NOT NEED TO BE PRESSURE TREATED.

3. FIELD CUTS AND BOLT HOLES IN PRESSURE TREATED WOOD SHALL BE PROTECTED IN ACCORDANCE WITH AWPA STANDARD M4.

4. BEARING AND SHEAR WALLS SHALL HAVE DOUBLE TOP PLATES, LAPPED AT WALL AND PARTITION INTERSECTION WITH (3) 16d NAILS. SPLICE UPPER AND LOWER PLATES AS IN "TYPICAL STUD WALL & OPENING FRAMING DETAIL" ON TYPICAL DETAIL SHEET .

5. PROVIDE SOLID BLOCKING BETWEEN JOISTS AND RAFTERS AT ALL SUPPORTS.

6. PROVIDE BLOCKING AS REQUIRED AT CEILINGS, WALL FINISHES, FIRE BLOCKING, BACKING ETC.

7. JOISTS UNDER AND PARALLEL TO PARTITIONS SHALL BE DOUBLED AND NAILED TOGETHER.

8. THE MOISTURE CONTENT OF 2x MATERIAL AT TIME OF INITIAL USE SHALL BE LESS THAN 19%.

THE MOISTURE CONTENT OF LUMBER 3x AND LARGER AT TIME OF INITIAL USE SHALL BE LESS THAN 30% UNO.

9. HOLES FOR BOLTS IN WOOD SHALL BE BORED WITH A BIT OF THE SAME NOMINAL DIAMETER AS THE BOLT PLUS 1/16".

10. HOLES FOR LAG SCREWS SHALL BE FIRST BORED TO THE SAME DIAMETER AND DEPTH AS THE UNTHREADED SHANK. THE THREADED PORTION SHALL BE DRILLED TO 50% OF THE SHANK DIAMETER UNLESS NOTED OTHERWISE IN THE SPECIFICATIONS.

11. LAG SCREWS AND WOOD SCREWS SHALL BE SCREWED AND NOT DRIVEN INTO PLACE. SOAP MAY BE USED TO LUBRICATE SCREWS.

12. ALL BOLTS, LAG SCREWS AND POST-INSTALLED ANCHORS SHALL BE PROVIDED WITH METAL WASHERS UNDER HEADS AND NUTS WHICH BEAR ON WOOD. STEEL WASHERS SHALL BE SIMPSON BP OR BPS TYPE (3" SQ MIN w/ STD CUT WASHER WHERE REQD BY CODE). MALLEABLE IRON (MI) WASHERS SHALL BE ROUND AND CAST. STANDARD FLAT WASHERS SHALL BE PER ANSI B18.22.1 TYPE A - WIDE PATTERN. FOR WASHERS AT SILL ANCHORS, SEE SCHEDULE:

13. ALL BOLTS AND LAG SCREWS SHALL BE TIGHTENED ON INSTALLATION AND RETIGHTENED BEFORE CLOSING IN OR AT COMPLETION OF JOB.

14. ALL BOLTS SHALL BE FULL NOMINAL DIMENSION AT UNTHREADED PORTION. NO UPSET THREADED BOLTS ALLOWED.

15. ALL FASTENERS, INCLUDING NUTS AND WASHERS, IN CONTACT w/ PRESERVATIVE-TREATED OR FIRE-RETARDANT MATERIAL SHALL BE HOT-DIPPED GALVANIZED STEEL OR STAINLESS STEEL.

BOLTS MAY BE HOT-DIPPED OR MECHANICALLY DEPOSITED ZINC-COATED STEEL. PLAIN CARBON STEEL FASTENERS ARE PERMITTED IN CONTACT w/ SBX/DOT OR ZINC BORATE PRESERVATIVE-TREATED WOOD IN AN INTERIOR, DRY ENVIRONMENT.

16. USE OF MACHINE NAILING IS SUBJECT TO SATISFACTORY REVIEW FOR EACH PROJECT AND SUBJECT TO APPROVAL BY THE GOVERNING AGENCY. THE APPROVAL IS SUBJECT TO CONTINUED SATISFACTORY PERFORMANCE. MACHINE NAILING WILL NOT BE APPROVED IN 5/16" SHEATHING. IF NAIL HEADS PENETRATE THE OUTER PLY BY MORE THAN WOULD BE

NORMAL FOR A HAMMER OR IF MINIMUM ALLOWABLE EDGE DISTANCES ARE NOT MAINTAINED, THE PERFORMANCE WILL BE DEEMED UNSATISFACTORY.

17. BLOCK SHTG JOINTS WITH 2x4 FLAT BLOCKING WHERE NOTED ON ROOF OR FLOOR FRAMING PLANS AND WITH BLOCKING SAME SIZE AS STUDS AT WALLS. USE PLYCLIPS AT MIDSPAN OF UNSUPPORTED ROOF SHEATHING EDGES.

18. FRAMING HARDWARE SHOWN ON THE PLANS IS SIMPSON STRONG-TIE. USE FRAMING HARDWARE AS MANUFACTURED BY SIMPSON COMPANY OR EQUIVALENT. PRIOR TO

INSTALLATION OF ANY NON-SIMPSON HARDWARE, THE CONTRACTOR SHALL SUBMIT A LIST OF

ALL DETAIL REFERENCES WHERE A HARDWARE SUBSTITUTION IS PROPOSED, THE

DESIGNATION FOR THE SIMPSON ITEM AND NON-SIMPSON PROPOSED EQUIVALENT AND AN ICC REPORT FOR EACH SUBSTITUTION ITEM.

19. LAY ALL STRUCTURAL SHEATHING ON ROOF AND FLOORS WITH LONG DIMENSION PERPENDICULAR TO SUPPORTS UNLESS NOTED OTHERWISE.

20. NOTIFY STRUCTURAL ENGINEER AFTER WALL, FLOOR, AND ROOF SHTG NAILING HAS BEEN COMPLETED AND A MINIMUM OF 48 HOURS PRIOR TO CONCEALING NAILING.

SIMPSON HARDWARE
600SN004

1. UNLESS SPECIFICALLY NOTED OTHERWISE, HARDWARE SPECIFIED ON THE DRAWINGS SHALL BE SIMPSON HARDWARE.

2. SIMPSON HARDWARE FOR THIS PROJECT HAS BEEN SPECIFIED BASED ON THE ALLOWABLE

LOAD VALUES AND PRODUCT INFORMATION GIVEN IN THE SIMPSON CATALOG FOR THE YEAR THAT THESE DRAWINGS ARE DATED.

3. PLANS, SECTIONS AND DETAILS INDICATE GENERAL PRODUCT TYPE AND ANY REQUIRED MODIFICATIONS (I.E.: SLOPES AND SKEWS). SPECIFIC CATALOG CALL OUTS ARE DETERMINED BY INDIVIDUAL MEMBER SIZES.

EXAMPLES:

PLANS/SECTIONS INDICATE 2x10 MEMBERS SUPPORTED BY SIMPSON 'U' HANGERS.

SIMPSON CALL-OUT: U210.

PLANS/SECTIONS INDICATE 5-1/8"x18" GLB SUPPORTED BY 4X6 POST AND SIMPSON ECC CAP. SIMPSON CALL-OUT: ECC5&1/4-4 OR OPTION WITH STRAPS ROTATED 90° ECC5&1/4-6

4. WHERE THE SIMPSON CATALOG INDICATES TWO SIZES MAY BE USED FOR THE SAME SIZE MEMBER, USE THE LARGER SIZE.

EXAMPLE:

PLANS/SECTIONS INDICATE 4x8 MEMBER SUPPORTED BY SIMPSON LUS HANGERS.

SIMPSON CATALOG INDICATES LUS46 OR LUS48 MAY BE USED. THE LUS48 SHALL BE USED UNO.

5. USE SIMPSON 'MAX' NAILING CONFIGURATION ("FILL ALL HOLES WITH NAILS"), TYPICAL UNO.

6. WHERE MULTIPLE NAIL SIZES ARE INDICATED IN SIMPSON CATALOG, USE LARGEST NAIL SIZE LISTED, TYPICAL UNO.

7. HARDWARE SUPPLIER OTHER THAN SIMPSON SHALL SUBMIT A COMPARATIVE MATERIAL LIST

ITEMIZING PRODUCT DESIGNATION, LOAD RATING, AND SUPPORTED MEMBER SIZE FOR REVIEW BY THE ENFORCEMENT AGENCY AND THE STRUCTURAL ENGINEER.

FIRE-RETARDANT TREATED WOOD NOTES (FRT)
600SN005

1. ALL EXTERIOR STUD WALLS AND EXTERIOR PLYWOOD SHEATHING SHALL BE FIRE-RETARDANT TREATED WOOD (FRT). LUMBER AND PLYWOOD SHALL BE PRESSURE-IMPREGNATED WITH DBLAZE FIRE RETARDANT CHEMICALS BY VIANCE, INC. (ESR-2645), PYRO-GUARD FIRE RETARDANT CHEMICALS BY HOOVER TREATED WOOD PRODUCTS, INC. (ESR-1791), OR ENGINEER APPROVED EQUAL. HANDLE AND INSTALL ALL FRT WOOD PER MANUFACTURER'S RECOMMENDATIONS.

2. ALL LUMBER MUST BE KILN DRIED TO A MAXIMUM MOISTURE CONTENT OF 19 PERCENT AFTER TREATMENT. ALL PLYWOOD MUST BE KILN DRIED TO A MAXIMUM MOISTURE CONTENT OF 15 PERCENT AFTER TREATMENT. ALL FIRE-RETARDANT WOOD MUST COMPLY WITH THE REQUIREMENTS IN AWPA STANDARD C20 FOR LUMBER AND C27 PLYWOOD.

3. ALL FASTENERS USED IN FIRE-RETARDANT TREATED LUMBER AND PLYWOOD MUST BE HOTDIPPED ZINC-COATED GALVANIZED STEEL OR OTHER SUITABLE CORROSION RESISTANT MATERIAL. THE COATING WEIGHTS FOR ZINC COATED FASTENERS SHALL BE IN ACCORDANCE WITH CBC SECTION 2304.10.5.

4. ALL CARBON STEEL, GALVANIZED STEEL, ALUMINUM AND COPPER IN CONTACT WITH FRT

WOOD SHALL BE CORROSION RESISTANT AND SHALL EXHIBIT CORROSION RATES LESS THAN ONE MIL PER YEAR WHEN TESTED IN ACCORDANCE WITH FEDERAL SPECIFICATIONS MILL-19140, PER 4.6.5.2.

5. MINIMUM LUMBER DESIGN ADJUSTMENT FACTORS FOR DOUGLAS FIR FRT WOOD (ZONES 1B AND 2) SHALL BE AS FOLLOWS:

FLOOR/WALLS ROOF
COMPRESSION PARALLEL TO GRAIN, Fc 0.935 0.935
HORIZONTAL SHEAR, Fv 0.985 0.894
TENSION PARALLEL, Ft 0.874 0.775
BENDING MODULUS OF ELASTICITY, E 0.960 0.960
EXTREME FIBER STRESS, Fb 0.972 0.828
FASTENERS/CONNECTORS 0.900 0.900

6. ALL FRT WOOD SHALL BE SEPARATED FROM MASONRY OR CONCRETE THAT MAY GET WET WITH TWO LAYERS OF #15 ASPHALT-IMPREGNATED BUILDING PAPER, OR ENGINEER APPROVED EQUAL UNO.

7. ALL FRT LUMBER AND PLYWOOD SHALL BE LABELED IN ACCORDANCE WITH CBC 2303.2.5.

GENERAL NOTES
100SN001

1. INTERPRETATION OF DRAWINGS & SPECIFICATIONS
A. WHERE SPECIFICATIONS HAVE BEEN PREPARED FOR THIS PROJECT, THEY ARE ARRANGED

IN SEVERAL SECTIONS, BUT SUCH SEPARATION SHALL NOT BE CONSIDERED AS THE LIMITS OF THE WORK REQUIRED OF ANY SEPARATE TRADE. THE TERMS AND CONDITIONS OF

SUCH LIMITATIONS ARE WHOLLY BETWEEN THE CONTRACTOR AND THEIR SUBCONTRACTORS.

B. IN GENERAL, THE WORKING DETAILS WILL INDICATE DIMENSIONS, POSITION AND KIND OF CONSTRUCTION, AND THE SPECIFICATIONS, QUALITIES AND METHODS. ANY WORK

INDICATED ON THE WORKING DETAILS AND NOT MENTIONED IN THE SPECIFICATIONS, OR VICE VERSA, SHALL BE FURNISHED AS THOUGH FULLY SET FORTH IN BOTH. WORK NOT

PARTICULARLY DETAILED, MARKED OR SPECIFIED, SHALL BE IDENTICAL OR SIMILAR TO LIKE CASES OF CONSTRUCTION THAT ARE DETAILED, MARKED OR SPECIFIED. IF CONFLICTS

OCCUR ON DRAWINGS AND/OR SPECIFICATIONS, THE MOST EXPENSIVE MATERIALS OR METHODS WILL PREVAIL.

C. SHOULD AN ERROR APPEAR IN THE WORKING DETAILS OR SPECIFICATIONS OR IN WORK

DONE BY OTHERS AFFECTING THIS WORK, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT AT ONCE AND IN WRITING. IF THE CONTRACTOR PROCEEDS WITH THE WORK

SO AFFECTED WITHOUT HAVING GIVEN SUCH WRITTEN NOTICE AND WITHOUT RECEIVING

THE NECESSARY APPROVAL, DECISION OR INSTRUCTIONS IN WRITING FROM THE OWNER,

THEN THE CONTRACTOR SHALL HAVE NO VALID CLAIM AGAINST THE OWNER, FOR THE COST OF SO PROCEEDING AND SHALL MAKE GOOD ANY RESULTING DAMAGE OR DEFECT.

NO VERBAL APPROVAL, DECISION, OR INSTRUCTION SHALL BE VALID OR BE THE BASIS FOR ANY CLAIM AGAINST THE OWNER, ITS OFFICERS, EMPLOYEES OR AGENTS. THE

FOREGOING INCLUDES TYPICAL ERRORS IN THE SPECIFICATIONS OR NOTATIONAL ERRORS

IN THE WORKING DETAILS WHERE THE INTERPRETATION IS DOUBTFUL OR WHERE THE

ERROR IS SUFFICIENTLY APPARENT AS TO PLACE A REASONABLY PRUDENT CONTRACTOR

ON NOTICE THAT, SHOULD THE CONTRACTOR ELECT TO PROCEED, THEY ARE DOING SO AT THEIR OWN RISK.

2. CONSTRUCTION SHALL CONFORM TO ALL APPLICABLE CODES AND REGULATIONS.

3. SHOP DRAWING NOTE:

A. WHEN NOT ADDRESSED BY DIVISION 1 OF THE SPECIFICATIONS, SUBMITTALS SHALL BE ELECTRONIC PDF FORMAT.

B. THE PURPOSE OF SHOP DRAWING SUBMITTALS BY THE CONTRACTOR IS TO DEMONSTRATE

TO THE STRUCTURAL ENGINEER THAT THE CONTRACTOR UNDERSTANDS THE DESIGN

CONCEPT BY INDICATING WHICH MATERIAL THE CONTRACTOR INTENDS TO FURNISH AND

INSTALL, AND BY DETAILING THE FABRICATION AND INSTALLATION METHODS THE CONTRACTOR INTENDS TO USE ON A STAND ALONE SET OF DOCUMENTS. DUPLICATION OF DESIGN DOCUMENTS FOR THE PURPOSE OF SHOP DRAWINGS IS NOT ACCEPTABLE.

C. PRIOR TO FABRICATION, SHOP DRAWINGS SHALL BE SUBMITTED FOR REVIEW BY THE STRUCTURAL ENGINEER. SHOP DRAWING SUBMITTALS SHALL INCLUDE, BUT ARE NOT

NECESSARILY LIMITED TO, STRUCTURAL STEEL, REINFORCING STEEL, & GLUE-LAMINATED BEAMS.

D. PRIOR TO SUBMISSION THE CONTRACTOR SHALL REVIEW ALL SUBMITTALS FOR

CONFORMANCE WITH THE CONTRACT DOCUMENTS AND SHALL STAMP SUBMITTALS AS BEING "REVIEWED FOR CONFORMANCE".

E. SHOP DRAWING SUBMITTALS PROCESSED BY THE STRUCTURAL ENGINEER ARE NOT CHANGE ORDERS.

F. ANY DETAIL ON THE SHOP DRAWINGS THAT DEVIATES FROM THE CONTRACT DOCUMENTS SHALL CLEARLY BE MARKED WITH THE NOTE "THIS IS A CHANGE".

G. SHOP DRAWINGS OR CALCULATIONS SUBMITTED FOR REVIEW THAT REQUIRE

RESUBMITTAL FOR RE-REVIEW SHALL BE BILLED HOURLY FOR SUCH TIME TO THE GENERAL CONTRACTOR. RE-REVIEW WILL NOT PROCEED WITHOUT WRITTEN APPROVAL FROM THE GENERAL CONTRACTOR FOR ADDITIONAL ENGINEERING REVIEW SERVICES.

4. SAFETY NOTE:

A. IT IS THE CONTRACTORS RESPONSIBILITY TO COMPLY WITH THE PERTINENT SECTIONS, AS THEY APPLY TO THIS PROJECT, OF THE "CONSTRUCTION SAFETY ORDERS" ISSUED BY THE STATE OF CALIFORNIA LATEST EDITION, AND ALL OSHA REQUIREMENTS.

B. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ADEQUATE DESIGN AND CONSTRUCTION OF ALL FORMS AND SHORING REQUIRED. SHORING INDICATIONS (LOCATION, DIRECTION, DURATION, ETC.) ARE ONLY SHOWN ON THE STRUCTURAL DWGS WHEN REQUIRED TO IMPLEMENT THE DESIGN INTENT OF THE FINAL WORK PRODUCT. DETERMINATION

WHETHER SHORING IS REQUIRED FOR TEMPORARY OR INTERMEDIATE CONDITIONS DURING CONSTRUCTION IS WHOLLY THE RESPONSIBILITY OF THE CONTRACTOR.

C. THE OWNER AND THE STRUCTURAL ENGINEER DO NOT ACCEPT ANY RESPONSIBILITY FOR THE CONTRACTOR'S FAILURE TO COMPLY WITH THESE REQUIREMENTS.

5. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT AND STRUCTURAL ENGINEER WHERE A

CONFLICT OR DISCREPANCY OCCURS BETWEEN THE STRUCTURAL DRAWINGS AND ANY OTHER PORTION OF THE CONTRACT DOCUMENTS OR EXISTING FIELD CONDITIONS. SUCH

NOTIFICATION SHALL BE GIVEN IN DUE TIME SO AS NOT TO AFFECT THE CONSTRUCTION SCHEDULE. IN CASE OF A CONFLICT BETWEEN STRUCTURAL DRAWINGS AND SPECIFICATIONS

THE MORE RESTRICTIVE CONDITION SHALL TAKE PRECEDENCE UNLESS WRITTEN APPROVAL HAS BEEN GIVEN FOR THE LEAST RESTRICTIVE. CONTRACTOR SHALL VERIFY ALL DIMENSIONS WITH ARCHITECTURAL PRIOR TO COMMENCING ANY WORK.

6. WHEN CONSTRUCTION ATTACHES TO OR IS WITHIN AN EXISTING BUILDING, A COMPLETE SET OF DRAWINGS OF THE EXISTING BUILDING SHALL BE KEPT ON THE JOB SITE. CONTRACTOR TO OBTAIN THESE DRAWINGS FROM THE OWNER (IF THEY ARE AVAILABLE).

7. CONTRACTOR SHALL PROVIDE AN ALLOWANCE EQUAL TO 2% OF THE BID FOR STRUCTURAL STEEL, MISC. IRON AND REINFORCING STEEL TO BE USED AT THE DISCRETION OF THE STRUCTURAL ENGINEER. UNUSED AMOUNT TO REVERT TO THE OWNER UPON COMPLETION OF THE JOB.

8. ANY SUBSTITUTIONS FOR STRUCTURAL MEMBERS, HARDWARE OR DETAILS SHALL BE REVIEWED BY THE ARCHITECT AND STRUCTURAL ENGINEER. SUCH REVIEW WILL BE BILLED

ON A TIME AND MATERIALS BASIS TO THE GENERAL CONTRACTOR WITH NO GUARANTEE THAT THE SUBSTITUTION WILL BE ALLOWED.

9. DO NOT SCALE DRAWINGS. CONTACT THE ARCHITECT OR STRUCTURAL ENGINEER FOR ANY DIMENSIONS NOT SHOWN.

10. THESE DRAWINGS ARE NOT COMPLETE UNTIL REVIEWED AND ACCEPTED BY LOCAL BUILDING OFFICIALS AND THE OWNER AND SIGNED BY THE STRUCTURAL ENGINEER. (A) -
AB -
ABV -
ADDL -
AHU -
ALT -

APPROX -
ARCH -
(B) -
BLDG -
BLKG -
BLW -
BM -
B.O. -
BOF -
BOTT -
BRCG -
BRG -
BTWN -
BYND -
CC -
CG -
CJ -
CJP -
CL -
CLG -
CLR -
CMU -
COL -
CONC -
CONN -
CONT -

CONTR -

COORD -
CSK -
DBL -
DF -
DIAG -
DL -
DWG -
(E) -
EA -
EF -
EJ -
ELEV -
EN -
EOS -
EQ -
EW -
FB -
FC -
FDN -
FF -
FRMG -
FRT -
FS -
FTG -
GA -
GALV -
GLB -
GR -
GYP -
HD -
HDR -
HGR -
HK -

HORIZ -
HSB -
HSS -
HT -

OCCURS ABOVE

ANCHOR BOLT
ABOVE

ADDITIONAL

AIR HANDLING UNIT

ALTERNATE

APPROXIMATE

ARCHITECTURAL

OCCURS BELOW

BUILDING

BLOCKING
BELOW
BEAM

BOTTOM OF

BOTTOM OF FOOTING
BOTTOM

BRACING

BEARING

BETWEEN
BEYOND

CENTER TO CENTER

CENTER OF GRAVITY

CONSTRUCTION JOINT

COMPLETE JOINT PENETRATION

CENTERLINE

CEILING
CLEAR

CONCRETE MASONRY UNIT
COLUMN

CONCRETE

CONNECTION

CONTINUOUS

CONTRACTOR

COORDINATE

COUNTERSINK
DOUBLE

DOUGLAS FIR

DIAGONAL

DEAD LOAD

DRAWING

EXISTING
EACH

EACH FACE OR EDGE FASTENER

EXPANSION JOINT

ELEVATION

EDGE NAILING

EDGE OF SLAB
EQUAL

EACH WAY

FACE OF BLOCK/BRICK OR FLAT BAR

FACE OF CONCRETE

FOUNDATION

FINISH FLOOR

FRAMING

FIRE RETARDANT TREATED

FACE OF STUD OR FAR SIDE

FOOTING

GAUGE OR GAGE

GALVANIZED

GLUED LAMINATED BEAM
GRADE
GYPSUM

HOLDOWN
HEADER
HANGER
HOOK

HORIZONTAL

HIGH STRENGTH BOLT

HOLLOW STRUCTURAL SECTION
HEIGHT
JH -
LL -
LLH -
LLV -

LONGIT -
LS -
LW -
MECH -
MFR -
MI -
× -
MTL -
(N) -
NIC -
NS -
NTS -
NW -
O/ -
OH -
OPNG -
OSB -
PC -
PERP -
PJP -
PL -
PT -
PW -

REINF -
REQD -
RWD -
SC -
SCH -
SEOR -
SHTG -
SIM -
SJ -
SMS -
SOG -
SP -
SPCG -
SQ -
STD -

STFNR -

STGRD -
STL -

STRUCT -
SW -
T&B -
T&G -
THRD -
TN -
T.O. -
TOC -
TOF -
TOS -
TOW -

TRANS -
TYP -
UNO -
VERT -
VIF -
WF -
WHS -
WP -
WS -
WWF -
XS -
XXS -
Ø -

JOIST HANGER

LIVE LOAD

LONG LEG HORIZONTAL

LONG LEG VERTICAL

LONGITUDINAL

LAG SCREW

LIGHTWEIGHT

MECHANICAL

MANUFACTURER

MALLEABLE IRON
MARK
METAL
NEW

NOT IN CONTRACT

NEAR SIDE

NOT TO SCALE

NORMAL WEIGHT
OVER

OPPOSITE HAND

OPENING

ORIENTED STRAND BOARD
PIECE

PERPENDICULAR

PARTIAL JOINT PENETRATION
PLATE

PRESSURE TREATED

PUDDLE WELD

REINFORCING OR REINFORCEMENT

REQUIRED

REDWOOD

SLIP CRITICAL

SCHEDULE

STRUCTURAL ENGINEER OF RECORD

SHEATHING

SIMILAR

SLAB CONTROL JOINT

SHEET METAL SCREW

SLAB-ON-GRADE

STRUCTURAL PANEL

SPACING
SQUARE

STANDARD

STIFFENER

STAGGERED
STEEL

STRUCTURAL

SHEAR WALL

TOP & BOTTOM

TONGUE & GROOVE

THREADED

TOE NAIL
TOP OF

TOP OF CONCRETE (SLAB UNO)

TOP OF FOOTING OR TOP OF FRAMING

TOP OF STEEL

TOP OF WALL

TRANSVERSE

TYPICAL

UNLESS NOTED OTHERWISE

VERTICAL

VERIFY IN FIELD

WIDE FLANGE

WELDED HEADED STUD

WORK POINT

WOOD SCREW

WELDED WIRE FABRIC

EXTRA STRONG

DOUBLE EXTRA STRONG

ROUND OR DIAMETER

ABBREVIATIONS
100SN003

STRUCTURAL OBSERVATION
100SN017

1. IN ACCORDANCE WITH SECTION 1704.6 OF THE CBC, THIS PROJECT IS REQUIRED TO HAVE STRUCTURAL OBSERVATION. STRUCTURAL OBSERVATION MEANS THE VISUAL OBSERVATION

OF THE STRUCTURAL SYSTEM, FOR GENERAL CONFORMANCE TO THE APPROVED PLANS AND

SPECIFICATIONS, AT SIGNIFICANT CONSTRUCTION STAGES AND AT COMPLETION OF THE STRUCTURAL SYSTEM. STRUCTURAL OBSERVATION DOES NOT INCLUDE OR WAIVE THE RESPONSIBILITY FOR THE INSPECTIONS REQUIRED BY CBC SECTIONS 110 OR 1705. THE FOLLOWING PROJECT MILESTONES SHALL BE OBSERVED:

A. FOUNDATIONS (PRIOR TO CONCRETE PLACEMENT)
B. WOOD SHEATHED SHEAR WALLS, FLOORS, AND ROOFS (PRIOR TO COVERING)

2. THE OWNER SHALL EMPLOY THE ARCHITECT OR STRUCTURAL ENGINEER OF RECORD, OR

ANOTHER REGISTERED PROFESSIONAL ENGINEER OR ARCHITECT DESIGNATED TO PERFORM STRUCTURAL OBSERVATION. OBSERVED DEFICIENCIES SHALL BE REPORTED IN WRITING TO THE OWNER'S REPRESENTATIVE, SPECIAL INSPECTOR, CONTRACTOR AND BUILDING OFFICIAL.

THE STRUCTURAL OBSERVER SHALL SUBMIT TO THE BUILDING OFFICIAL A STATEMENT THAT

THE FIELD VISITS HAVE OCCURRED AND IDENTIFY ANY REPORTED DEFICIENCIES THAT, TO THE BEST OF THE STRUCTURAL OBSERVER'S KNOWLEDGE, HAVE NOT BEEN RESOLVED.

3. THE CONTRACTOR SHALL NOTIFY THE STRUCTURAL OBSERVER A MINIMUM OF 48 HOURS IN ADVANCE OF PROJECT MILESTONES SO THAT OBSERVATIONS MAY BE SCHEDULED.

WINDOW SYSTEM DESIGN CRITERIA
100SN010

1. THE FOLLOWING DESIGN CRITERIA APPLIES TO ALL GLAZED OPENINGS (WINDOW SYSTEMS, STOREFRONT, CURTAIN WALL, WINDOW WALL, ETC). WINDOW SYSTEMS ARE A DELEGATED DESIGN SYSTEM TO BE OVERSEEN BY THE GENERAL CONTRACTOR.

2. ELEMENTS OF THE WINDOW SYSTEM SHALL BE DESIGNED FOR ALL VERTICAL AND LATERAL

LOADING AS REQUIRED BY THE GOVERNING CODE AND AS SHOWN IN THE CONSTRUCTION

DOCUMENTS, BUT SHALL NOT BE LESS THAN THE LOADS REQUIRED IN THE SPECIFICATIONS (WHERE OCCURS). WIND LOADS SHALL BE DERIVED USING ASCE 7 CHAPTER 30, WITH THE WIND SPEED AND EXPOSURE CATEGORY AS NOTED IN THE DESIGN CRITERIA ON SHEET S1.01 .

3. ALL WINDOW SYSTEM ATTACHMENTS SHALL BE MADE DIRECTLY TO THE BUILDING AT THE LOCATIONS SHOWN AND IN THE MANNER DEPICTED IN THE CONSTRUCTION DOCUMENTS.

ATTACHMENT LOCATIONS PROVIDE EITHER VERTICAL SUPPORT OR OUT-OF-PLANE SUPPORT (OR BOTH) AS INDICATED IN THE CONSTRUCTION DOCUMENTS.

4. MULLIONS AND/OR OTHER WINDOW SYSTEM ELEMENTS SHALL BE DESIGNED TO SPAN BETWEEN THE SUPPORTS DESCRIBED IN NOTE 3. THE CONNECTIONS OF ANY INTERNAL ELEMENTS SHALL BE CAPABLE OF TRANSMITTING THE LOADS TO THE SUPPORTING MEMBER.

MULLIONS SHALL BE DESIGNED TO MEET DEFLECTION CRITERIA IN ACCORDANCE WITH THE CBC/IBC AND DSA IR 24-2.

5. WINDOW SYSTEM ELEMENTS SHALL BE FASTENED TO THE PRIMARY STRUCTURE BY MEANS OF MECHANICAL FASTENERS OR WELDS. ALL CONNECTIONS SHALL BE DESIGNED AND DETAILED TO MEET THE REQUIREMENTS OF ASCE 7 SECTION 13.5.3. ANY CONNECTOR TYPES AND/OR METHODS PROVIDED IN THE CONSTRUCTION DOCUMENTS ARE FOR REFERENCE ONLY.

6. WINDOW SYSTEM MANUFACTURER/INSTALLER SHALL DESIGN ALL CONNECTION MATERIALS (INCLUDING BUT NOT LIMITED TO EMBEDDED ITEMS, DIAGONAL BRACING ANGLES, BRACKETS, OUTRIGGERS, ETC.) AS REQUIRED FOR THE SUPPORT OF THE WINDOW SYSTEM.

INSTALLATION OF EMBEDDED ITEMS SHALL BE COORDINATED BY GENERAL CONTRACTOR.

7. CONNECTIONS OF WINDOW SYSTEM SHALL ACCOMMODATE VERTICAL DEFLECTIONS OF THE

STRUCTURE THROUGH THE USE OF RECEIVING CHANNELS, SLOTTED HOLES OR FLEXIBLE

CONNECTIONS THAT PERMIT THE STRUCTURE TO DEFLECT WITHOUT INDUCING LOADS OR DISTORTIONS INTO THE WINDOW SYSTEM. WHERE WINDOW SYSTEMS ATTACH DIRECTLY OR

INDIRECTLY TO THE FLOOR OR ROOF STRUCTURE, THE ATTACHMENT SHALL ACCOMMODATE DEFLECTIONS EQUAL TO A MINIMUM OF 1/2”.

8. THE SYSTEM SHALL MEET THE DISPLACEMENT REQUIREMENTS OF ASCE 7 SECTIONS 13.3.2 AND 13.5.9. ALL ELEMENTS OF THE WINDOW SYSTEM SHALL BE DESIGNED TO ACCOMMODATE THE FOLLOWING IN-PLANE RELATIVE DISPLACEMENTS:

SEISMIC (Dp) = 3/4"
WIND = 3/4"

9. FOR WINDOW SYSTEMS WITH A SPAN GREATER THAN 10 FEET, THE WINDOW SYSTEM

MANUFACTURER/INSTALLER SHALL SUBMIT COMPLETE DESIGN DRAWINGS AND CALCULATIONS FOR REVIEW BY THE ARCHITECT AND STRUCTURAL ENGINEER. SUBMITTAL

SHALL INCLUDE ALL GLAZING ELEMENTS, MULLIONS AND CONNECTIONS, INCLUDING MATERIAL

PROPERTIES, SECTION PROPERTIES AND ANY OTHER INFORMATION NECESSARY TO

COMPLETELY DOCUMENT THAT THE SYSTEM FULLY COMPLIES WITH ALL PROJECT REQUIREMENTS. DRAWINGS AND CALCULATIONS SHALL BE STAMPED AND SIGNED BY A CIVIL ENGINEER REGISTERED IN THE STATE IN WHICH THE PROJECT IS LOCATED.

10. FOR WINDOW SYSTEMS WITH A SPAN LESS THAN 10 FEET, THE WINDOW SYSTEM MANUFACTURER/INSTALLER SHALL SUBMIT SHOP DRAWINGS TO THE ARCHITECT FOR REVIEW.

POST-INSTALLED ANCHORS
305SN001

1. FOR CONCRETE CONSTRUCTION, POST-INSTALLED ANCHORS SHALL BE ONE OF THE FOLLOWING:

A. ADHESIVE ANCHORS FOR THRD ROD & REBAR:
a. HILTI HIT-HY 200 PER ESR-3187
b. HILTI HIT-RE500 V3 PER ESR-3814
c. SIMPSON SET-XP PER ESR-2508
d. SIMPSON SET-3G PER ESR-4057
e. DEWALT PURE 110+ ESR-3298
B. EXPANSION ANCHORS:
a. HILTI KB-TZ2 PER ESR-4266
b. SIMPSON STRONG BOLT 2 PER ESR-3037
c. DEWALT POWER-STUD+ SD2, SD4 OR SD6 AS NOTED PER ESR-2502 C. SCREW ANCHORS:
a. HILTI KWIK HUS-EZ (KH-EZ) PER ESR-3027
b. SIMPSON TITEN HD PER ESR-2713
c. DEWALT SCREWBOLT+ PER ESR-3889

2. FOR GROUT-FILLED MASONRY CONSTRUCTION, POST-INSTALLED ANCHORS SHALL BE ONE OF THE FOLLOWING:

A. ADHESIVE ANCHORS FOR THRD ROD & REBAR:
a. HILTI HIT-HY 270 PER ESR-4143
b. SIMPSON SET-XP PER IAPMO UES ER-265
c. DEWALT AC 100+ GOLD PER ESR-3200
B. EXPANSION ANCHORS:
a. HILTI KB-TZ2 PER ESR-4561
b. SIMPSON STRONG-BOLT 2 PER IAPMO ER-240
c. DEWALT POWER-STUD+ SD1 PER ESR-2966
C. SCREW ANCHORS:
a. HILTI KWIK HUS-EZ (KH-EZ) PER ESR-3056
b. SIMPSON TITEN HD PER ESR-1056
c. DEWALT SCREWBOLT+ PER ESR-4042

3. FOR UNREINFORCED MASONRY CONSTRUCTION, ADHESIVE ANCHORS SHALL BE ONE OF THE FOLLOWING:
a. HILTI HY-270 PER ESR-4144
b. SIMPSON ET-HD PER ESR-3630
c. DEWALT AC100+ GOLD PER ESR-4105

4. PLASTIC MESH SCREEN TUBES SHALL BE PROVIDED AND EXISTING WALL THICKNESS AND MORTAR SHEAR STRENGTH SHALL MEET THE REQUIREMENTS OF THE EVALUATION REPORT.

5. ANCHOR TYPE, SIZE & EMBEDMENT SHALL BE AS INDICATED IN DRAWINGS. POST-INSTALLED ANCHORS FOR REPAIR SHALL BE EVALUATED ON A CASE BY CASE BASIS. NOTIFY STRUCTURAL ENGINEER FOR REPAIRS.

6. ALL EMBEDMENT DEPTHS CALLED OUT IN DRAWINGS REFER TO EFFECTIVE EMBEDMENT UNLESS OTHERWISE NOTED. SEE DIAGRAM BELOW AND ICC REPORTS.

7. ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS GIVEN IN THE EVALUATION REPORT. PROVIDE MINIMUM EMBEDMENT PROVIDED IN ICC ESR REPORT UNLESS NOTED OTHERWISE.

8. PROVIDE SPECIAL INSPECTION AS INDICATED IN THE STATEMENT OF STRUCTURAL SPECIAL INSPECTIONS AND TESTING AND THE EVALUATION REPORT.

9. WHEN INSTALLING POST-INSTALLED ANCHORS IN EXISTING CONCRETE OR MASONRY, USE CARE AND CAUTION TO AVOID CUTTING OR DAMAGING EXISTING REINFORCING BARS. DO NOT INSTALL ANCHORS WITHIN 1 1/2" OF CMU HEAD JOINTS. DO NOT INSTALL ANCHORS IN PRESTRESSED CONCRETE ELEMENTS.

10. ANCHORS INSTALLED FROM THE BOTTOM INTO METAL DECK WITH CONCRETE SHALL BE

INSTALLED IN THE CENTER OF THE LOW FLUTE OF THE DECKING UNLESS NOTED OTHERWISE IN EVALUATION REPORT. THE DECKING SHALL HAVE A MINIMUM THICKNESS OF 20 GAUGE.

THE MINIMUM THICKNESS OF THE CONCRETE ABOVE THE HIGH FLUTE OF THE METAL DECK SHALL BE AS INDICATED IN THE EVALUATION REPORT. SEE EVALUATION REPORT FOR ADDITIONAL REQUIREMENTS, INCLUDING MINIMUM DIMENSIONS FOR FLUTE WIDTH AND DEPTH.

11. THE CONCRETE SHALL HAVE ATTAINED ITS MINIMUM DESIGN STRENGTH PRIOR TO INSTALLATION OF THE ANCHORS.

12. ADHESIVE ANCHORS SHALL BE INSTALLED IN CONCRETE HAVING A MINIMUM AGE OF 21 DAYS AT THE TIME OF ANCHOR INSTALLATION PER ACI 318, CHAPTER 17.

13. INSTALLER CERTIFICATION AND INSPECTION IS REQUIRED FOR HORIZONTAL AND UPWARDLY

INCLINED ADHESIVE ANCHORS SUBJECTED TO SUSTAINED TENSION LOADING IN ACCORDANCE WITH ACI 318, CHAPTER 17.

14. IF TEMPERATURE OF BASE MATERIAL AT TIME OF ADHESIVE ANCHOR INSTALLATION IS 45 DEGREES FARENHEIT OR LOWER, AN "ACRYLIC" OR COLD WEATHER ADHESIVE IS REQUIRED.

USE DEWALT AC200+, SIMPSON AT-XP, OR HILTI HIT-HY200 WHEN THIS OCCURS.

15. THE INSPECTION OF THE ANCHORS SHALL BE DONE BY A QUALIFIED INSPECTION AGENCY AND

A REPORT OF THE INSPECTION RESULTS SHALL BE SUBMITTED TO THE GOVERNING AGENCY AND ARCHITECT/STRUCTURAL ENGINEER.

INSTALLED ANCHOR DIAGRAMS
E
M
B
E
D

EFFECTIVE
EMBED

NOMINAL

PER REPORT

HOLE DEPTH
EMBED

EFFECTIVE
EMBED

NOMINAL

PER REPORT

HOLE DEPTH

EXPANSION ANCHOR SCREW ANCHOR
S

S TA TE O F CA L I FO R N I A

STRUCTURAL
R
ROFE P
ED

ER T IS
GE
SI N

ENGINEER
O AL
600 Q STREET, SUITE 200
SACRAMENTO, CA 95811
916 443 0303
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
WILLIAM B.

RADER
No. 3592
10/23/2024 5:26:07 PM c:\revit\2023-0123_DRY CREEK WWTP_rvt22_CENTRAL_Francisco_O_Rodriguez.rvt S101

GENERAL NOTES

DCWWTP OPERATIONS

AND LAB BLDG
- 2100 15.01
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP

APPLICABLE TO ALL DRAWINGS UNLESS NOTED OR SHOWN OTHERWISE

GENERAL NOTES
NO. DATE DESCRIPTION
1 8/28/2024 PC Revisions

BID SET (PRELIMINARY)

STATEMENT OF STRUCTURAL SPECIAL INSPECTIONS AND TESTING 110SN001

1. SPECIAL INSPECTIONS AND TESTING SHALL BE PROVIDED BY A TESTING AND INSPECTION

AGENCY, EMPLOYED BY THE OWNER (OR OWNER'S AUTHORIZED AGENT), AND APPROVED BY

THE BUILDING OFFICIAL TO PROVIDE SPECIAL INSPECTIONS AND TESTING FOR THE PARTICULAR TYPE OF CONSTRUCTION.

2. TABLES OF SPECIAL INSPECTIONS AND TESTING ARE DERIVED FROM THE STRUCTURAL PROVISIONS OF THE CBC AND REFERENCED STANDARDS AND ARE FOR REFERENCE ONLY.

THE INCLUDED TABLES ARE PROVIDED FOR THE CONVENIENCE OF THE OWNER, TESTING

AGENCY AND CONTRACTOR IN DEVELOPING THE SCOPE OF WORK FOR REQUIRED TESTING AND INSPECTION OF STRUCTURAL MATERIALS AND COMPONENTS. FINAL DEFINITION OF THIS

SCOPE OF WORK IS TO BE DETERMINED BY THE TESTING AGENCY AND THE OWNER (OR OWNER'S AUTHORIZED AGENT).

3. FREQUENCY OF SPECIAL INSPECTIONS AND TESTING SHALL BE, AT A MINIMUM, AS NOTED FOR THE INDIVIDUAL ELEMENTS WITHIN THE TABLES BELOW. THE CONTRACTOR SHALL

COORDINATE TIMING OF SPECIAL INSPECTIONS AND TESTING WITH THE SPECIAL INSPECTION AND TESTING AGENCY.

4. PRIOR TO THE START OF CONSTRUCTION, THE TESTING AND INSPECTION AGENCY SHALL

PROVIDE DOCUMENTATION TO THE BUILDING OFFICIAL DEMONSTRATING COMPETENCE AND

RELEVANT EXPERIENCE OR TRAINING OF THE SPECIAL INSPECTORS WHO WILL PERFORM THE

SPECIAL INSPECTIONS AND TESTS DURING CONSTRUCTION, IN ACCORDANCE WITH CBC SECTION 1704.2.1.

5. THE TESTING AND INSPECTION AGENCY SHALL SUBMIT REPORTS OF SPECIAL INSPECTIONS

AND TESTS TO THE BUILDING OFFICIAL, STRUCTURAL ENGINEER OF RECORD AND THE CONTRACTOR, PER CBC SECTION 1704.2.4. THE REPORTS SHALL INDICATE WHETHER WORK INSPECTED OR TESTED CONFORMED TO THE APPROVED CONSTRUCTION DOCUMENTS. ANY

DISCREPANCIES SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE CONTRACTOR FOR CORRECTION. IF DISCREPANCIES ARE NOT CORRECTED, THEY SHALL BE BROUGHT TO THE ATTENTION OF THE BUILDING OFFICIAL AND THE STRUCTURAL ENGINEER OF RECORD.

6. SPECIAL INSPECTION AND TESTING RECORDS SHALL BE RETAINED BY THE CONTRACTOR ON SITE UNTIL COMPLETION OF CONSTRUCTION.

7. THE CONTRACTOR SHALL SUBMIT A WRITTEN STATEMENT TO THE BUILDING OFFICIAL

ACKNOWLEDGING RESPONSIBILITY FOR CONSTRUCTION OF THE MAIN LATERAL-FORCE

RESISTING SYSTEM PRIOR TO COMMENCEMENT OF THAT WORK AS REQUIRED BY CBC SECTION 1704.4.

8. THE OWNER OR THE OWNER'S AUTHORIZED AGENT SHALL SUBMIT TO THE BUILDING OFFICIAL, A FINAL REPORT DOCUMENTING SPECIAL INSPECTIONS AND TESTS PER CBC SECTION 1704.2.4, AND REPORTS AND CERTIFICATES PER CBC SECTION 1704.5.

9. ALL SOILS AND FOUNDATION EXCAVATION INSPECTIONS SHALL BE BY THE GEOTECHNICAL

ENGINEER OF RECORD, OR A GEOTECHNICAL FIRM HIRED BY THE OWNER PER CBC SECTION 1705.6.

10. SPECIAL INSPECTION IS REQUIRED FOR ALL SHOP FABRICATED MEMBERS OR ASSEMBLIES UNLESS WAIVED PER THE EXCEPTIONS IN CBC SECTION 1704.2.5.

11. DEFINITIONS:
a. CONTINUOUS - SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS CONTINUOUSLY PRESENT WHEN AND WHERE THE WORK TO BE INSPECTED IS BEING PERFORMED. b. PERIODIC - SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS INTERMITTENTLY PRESENT WHERE THE WORK TO BE INSPECTED HAS BEEN OR IS BEING PERFORMED. c. QUALITY ASSURANCE (QA) - MONITORING AND INSPECTION TASKS PERFORMED BY AN

AGENCY OR FIRM OTHER THAN THE FABRICATOR OR ERECTOR TO ENSURE THAT THE

MATERIAL PROVIDED AND WORK PERFORMED BY THE FABRICATOR AND ERECTOR MEET

THE REQUIREMENTS OF THE APPROVED CONSTRUCTION DOCUMENTS AND REFERENCED STANDARDS. QUALITY ASSURANCE INCLUDES THOSE TASKS DESIGNATED 'SPECIAL INSPECTION' BY THE APPLICABLE CODE.
d. QUALITY CONTROL (QC) - CONTROLS AND INSPECTIONS IMPLEMENTED BY THE

FABRICATOR OR ERECTOR, AS APPLICABLE, TO ENSURE THAT THE MATERIAL PROVIDED

AND WORK PERFORMED MEET THE REQUIREMENTS OF THE APPROVED CONSTRUCTION DOCUMENTS AND REFERENCED STANDARDS.
e. OBSERVE (O) - OBSERVE THESE ITEMS ON A RANDOM BASIS (DAILY FOR LFRS).

OPERATIONS NEED NOT BE DELAYED PENDING THESE INSPECTIONS. f. PERFORM (P) - PERFORM THOSE TASKS PRIOR TO FINAL ACCEPTANCE FOR EACH ITEM OR ELEMENT.
g. DOCUMENT (D) - THE INSPECTOR SHALL PREPARE REPORTS INDICATING THAT THE WORK HAS BEEN PERFORMED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. THE REPORT

NEED NOT PROVIDE DETAILED MEASUREMENTS FOR JOINT FIT-UP, WPS SETTINGS, COMPLETED WELDS, OR OTHER INDIVIDUAL ITEMS LISTED IN THE TABLES. FOR SHOP FABRICATION, THE REPORT SHALL INDICATE THE PIECE MARK OF THE PIECE INSPECTED.

FOR FIELD WORK, THE REPORT SHALL INDICATE THE REFERENCE GRID LINES AND FLOOR OR ELEVATION INSPECTED. WORK NOT IN COMPLIANCE WITH THE CONTRACT DOCUMENTS

AND WHETHER THE NONCOMPLIANCE HAS BEEN SATISFACTORILY REPAIRED SHALL BE NOTED IN THE INSPECTION REPORT.

12. SPECIAL INSPECTIONS AND TESTING SHALL BE PERFORMED DURING CONSTRUCTION ON THE WORK SHOWN IN THE CONSTRUCTION DOCUMENTS AS REQUIRED BY CBC CHAPTER 17, THE TABLES LISTED BELOW, AND THE JURISDICTION'S SPECIAL INSPECTION AND TESTING FORM.

IF DISCREPANCIES ARE NOTED, CONTACT THE SEOR. ALL EXCEPTIONS INCLUDED IN CBC CHAPTER 17 ARE PERMITTED TO BE USED.
• SOILS
• CONCRETE CONSTRUCTION (POST-INSTALLED ANCHORS)
• MASONRY CONSTRUCTION - LEVEL 2 (POST-INSTALLED ANCHORS) TYPE

SOILS - REQUIRED SPECIAL INSPECTIONS AND TESTS
CBC TABLE 1705.6
110SN201

CONTINUOUS PERIODIC

1. VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE
ADEQUATE TO ACHIEVE THE DESIGN BEARING CAPACITY.
- X

2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND
HAVE REACHED PROPER MATERIAL.
- X

3. PERFORM CLASSIFICATION AND TESTING OF COMPACTED FILL MATERIALS.
- X

4. DURING FILL PLACEMENT, VERIFY USE OF PROPER MATERIALS

AND PROCEDURES IN ACCORDANCE WITH THE PROVISIONS OF
THE APPROVED GEOTECHNICAL REPORT. VERIFY DENSITIES

AND LIFT THICKNESSES DURING PLACEMENT AND COMPACTION
OF COMPACTED FILL.

X -

5. PRIOR TO PLACEMENT OF COMPACTED FILL, INSPECT

SUBGRADE AND VERIFY THAT SITE HAS BEEN PREPARED
PROPERLY.
- X
TYPE

CONCRETE CONSTRUCTION - REQUIRED SPECIAL INSPECTIONS AND TESTS CBC TABLE 1705.3
110SN301

CONTINUOUS PERIODIC REFERENCED STANDARD
a

1. INSPECT REINFORCEMENT,

INCLUDING PRESTRESSING
TENDONS, AND VERIFY PLACEMENT.

ACI 318 CH. 20, 25.2, 25.3,

26.6.1-26.6.3
- X

2. REINFORCING BAR WELDING: AWS D1.4
ACI 318: 26.6.4
A. VERIFY WELDABILITY OF

REINFORCING BARS OTHER
THAN ASTM A706
B. INSPECT SINGLE-PASS FILLET
WELDS, MAXIMUM 5/16"
C. INSPECT ALL OTHER WELDS
- X
- X
X -

3. INSPECT ANCHORS CAST IN
CONCRETE.

ACI 318: 17.8.2

4. INSPECT ANCHORS POST-INSTALLED

IN HARDENED CONCRETE
MEMBERS.
b
ACI 318: 17.8.2.4, 17.8.2
A. ADHESIVE ANCHORS INSTALLED

IN HORIZONTALLY OR UPWARDLY

INCLINED ORIENTATIONS TO

RESIST SUSTAINED TENSION
LOADS.
x -
B. MECHANICAL ANCHORS AND

ADHESIVE ANCHORS NOT
DEFINED IN 4.A.
- X

5. VERIFY USE OF REQUIRED DESIGN
MIX.

ACI 318: CH. 19, 26.4.3,

26.4.4 - X

6. PRIOR TO CONCRETE PLACEMENT,

FABRICATE SPECIMENS FOR

STRENGTH TESTS, PERFORM SLUMP

AND AIR CONTENT TESTS, AND

DETERMINE THE TEMPERATURE OF
THE CONCRETE.

ASTM C172
ASTM C31
ACI 318: 26.5, 26.12
X -

7. INSPECT CONCRETE AND

SHOTCRETE PLACEMENT FOR
PROPER APPLICATION TECHNIQUES.

ACI 318: 26.5

8. VERIFY MAINTENANCE OF SPECIFIED

CURING TEMPERATURE AND
TECHNIQUES.

ACI 318: 26.5.3-26.5.5- X

9. INSPECT PRESTRESSED CONCRETE
FOR:

ACI 318: 26.10
A. APPLICATION OF PRESTRESSING
FORCES
B. GROUTING OF BONDED
PRESTRESSING TENDONS.

10. INSPECT ERECTION OF PRECAST
CONCRETE MEMBERS.

ACI 318: CH. 26.9- X

13. VERIFY IN-SITU CONCRETE

STRENGTH, PRIOR TO STRESSING

OF TENDONS IN POST-TENSIONED

CONCRETE AND PRIOR TO REMOVAL

OF SHORES AND FORMS FROM
BEAMS AND STRUCTURAL SLABS.

ACI 318: 26.11.2- X

14. INSPECT FORMWORK FOR SHAPE,

LOCATION AND DIMENSIONS OF THE
CONCRETE MEMBER BEING FORMED.

ACI 318: 26.11.1.2(b)- X
A. WHERE APPLICABLE, SEE SECTION 1705.13.

B. SPECIFIC REQUIREMENTS FOR SPECIAL INSPECTION SHALL BE INCLUDED IN THE RESEARCH REPORT FOR THE ANCHOR ISSUED BY AN APPROVED SOURCE IN ACCORDANCE WITH 17.8.2 IN ACI 318, OR OTHER QUALIFICATION PROCEDURES. WHERE SPECIFIC REQUIREMENTS ARE

NOT PROVIDED, SPECIAL INSPECTION REQUIREMENTS SHALL BE SPECIFIED BY THE

REGISTERED DESIGN PROFESSIONAL AND SHALL BE APPROVED BY THE BUILDING OFFICIAL PRIOR TO COMMENCEMENT OF THE WORK.
- X
X -
X -
X -

11. FOR PRECAST CONCRETE

DIAPHRAGM CONNECTIONS OR

REINFORCEMENT AT JOINTS

CLASSIFIED AS MODERATE OR HIGH

DEFORMABILITY ELEMENTS (MDE OR

HDE) IN STRUCTURES ASSIGNED TO

SEISMIC DESIGN CATEGORY C, D, E

OR F, INSPECT SUCH CONNECTIONS

AND REINFORCEMENT IN THE FIELD
FOR:

ACI 318: 26.13.1.3
A. INSTALLATION OF THE
EMBEDDED PARTS.

B. COMPLETION OF THE CONTINUITY

OF REINFORCEMENT ACROSS
JOINTS.

X
-
X -
X -
ACI 550.5
C. COMPLETION OF CONNECTIONS
IN THE FIELD.

12. INSPECT INSTALLATION

TOLERANCES OF PRECAST

CONCRETE DIAPHRAGM

CONNECTIONS FOR COMPLIANCE
WITH ACI 550.5.

ACI 318: 26.13.1.3- X
TYPE

STRUCTURAL WOOD LFRS - REQUIRED SPECIAL INSPECTIONS
CBC SECTION 1705.12.1, 1705.13.2
110SN611

CONTINUOUS PERIODIC
-X
X1. FIELD GLUING OPERATIONS OF ELEMENTS OF THE LFRS.2. NAILING, BOLTING, ANCHORING AND OTHER FASTENING OF

ELEMENTS OF THE LFRS, INCLUDING WOOD SHEAR WALLS,

WOOD DIAPHRAGMS, DRAG STRUTS, BRACES, SHEAR PANELS
AND HOLD-DOWNS.

S

S TA TE
O F
CA
L
I

FO R N I A

STRUCTURAL
R
ROF
E
P

ED ER T IS GE
S
I
N

ENGINEER
O
AL
600 Q STREET, SUITE 200
SACRAMENTO, CA 95811
916 443 0303
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP
REVISIONS #

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
WILLIAM B.

RADER
No. 3592
10/23/2024 5:26:07 PM c:\revit\2023-0123_DRY CREEK WWTP_rvt22_CENTRAL_Francisco_O_Rodriguez.rvt S111

STRUCT SPECIAL

INSPECTIONS &

TESTING

DCWWTP OPERATIONS

AND LAB BLDG
2100 15.01Author
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP

APPLICABLE TO ALL DRAWINGS UNLESS NOTED OR SHOWN OTHERWISE

STRUCTURAL SPECIAL INSPECTIONS AND TESTING
NO. DATE DESCRIPTION
2 10/23/2024 PC Revisions 2
2 BID SET (PRELIMINARY)

FOUNDATION LEGEND

1. NOTES AND DETAILS ON SHEETS LABELED AS "GENERAL" OR "TYPICAL" ARE APPLICABLE TO ALL DRAWINGS, UNO.

2. VERIFY ALL BUILDING DIMENSIONS AND ELEVATIONS w/ ARCH DRAWINGS. NOTIFY THE ARCHITECT IMMEDIATELY IF THERE ARE ANY CONFLICTS w/ DIMENSIONS SHOWN.

3. DIMENSIONS SHOWN ARE TO THE CL OF COLUMN, FACE OF STUD.

4. SITE PREPARATION AND BUILDING PAD CONSTRUCTION SHALL BE DONE IN

ACCORDANCE WITH THE GEOTECHNICAL REPORT LISTED IN THE FOUNDATION GENERAL NOTES. BOTTOM OF FOOTING EXCAVATIONS SHALL BE REVIEWED BY GEOTECHNICAL ENGINEER PRIOR TO PLACEMENT OF REINFORCING STEEL. THE BOTTOM OF ALL FOOTINGS SHALL BE AT LEAST 18" BELOW ADJACENT MINIMUM

PREPARED BUILDING PAD ELEVATION ON ALL SIDES, TYP UNO OR AS SHOWN ON SECTIONS.

5. SLAB ON GRADE SHALL BE 6" THICK CONCRETE w/ #3 @ 18"CC EW AT MID-DEPTH.

CONCRETE SHALL BE INSTALLED OVER 15 MIL VAPOR RETARDER OVER 4" CLEAN CRUSHED ROCK. TOP OF CONCRETE SLAB IS 0'-0" UNO.

6. CONTRACTOR SHALL SUBMIT AN EDGE OF SLAB PLAN TO ARCHITECT & SEOR FOR REVIEW. SUBMITTAL SHALL BE DIMENSIONED AND LOCATED RELATIVE TO STRUCTURAL GRIDS.

7. PROVIDE SLAB ON GRADE CONTROL JOINTS (SJ) AS INDICATED PER TYP AT ALL INTERIOR SLABS. CONSTRUCTION JOINTS (CJ) MAY REPLACE CONTROL JOINTS AS REQUIRED.

8. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE SLAB CONTROL JOINTS

WITH ANY ARCHITECTURALLY EXPOSED SLAB AREAS OR THE LOCATION OF TILE CRACK CONTROL JOINTS. VERIFY SPECIAL CONDITION CONTROL JOINTS WITH ARCH DRAWINGS.

9. CONTRACTOR TO COORDINATE EXACT DIMENSIONS AND LOCATIONS OF THICKENED SLABS, HOUSEKEEPING PADS, ETC. WITH ALL OTHER DISCIPLINE'S DRAWINGS AS WELL AS WITH THE EQUIPMENT PROVIDED, PRIOR TO COMMENCING WORK.

10. ALL DEPRESSIONS, SLOPES, ETC. ARE SHOWN FOR REFERENCE ONLY. FOR EXACT DEPTHS, SLOPES, EXTENTS, ETC. SEE OTHER DISCIPLINES' DRAWINGS.

11. COORDINATE CURB LOCATIONS AND EXTENTS WITH ARCH DRAWINGS. FOR CURBS

BELOW NON-STRUCTURAL WALLS, SEE &
.

12. TEMPORARY LOADS APPLIED DURING CONSTRUCTION HAVE NOT BEEN CONSIDERED IN SLAB ON GRADE DESIGN.

13. SEE ARCH & CIVIL DRAWINGS FOR ALL EXTERIOR CURBS, FLATWORK, PLANTERS, RAMPS, ETC.

14. PROVIDE 3" MIN. CONCRETE COVER AT STRUCTURAL STEEL AND ANCHOR BOLTS BELOW GRADE, TYP.

15. CONTINUE ALL REINFORCING IN CONTINUOUS FOOTINGS THROUGH SPREAD FOOTINGS, TYP UNO.

16. FACE OF CONCRETE AT PERIMETER OF BLDG SHALL BE 1/2" OUTSIDE FACE OF STUD, TYP UNO. COORDINATE WITH ARCH DWGS.

17. ANCHOR BOLTS AT NON-SHEARWALLS SHALL BE AS INDICATED ON .

18. All WOOD STUD WALLS ARE TO BE 2x6 @ 16" CC UNO ON THE PLANS, SECTIONS, OR SCHEDULES. COORDINATE STUD SIZE WITH ARCH DWGS.

MK
X'-X" 2 (2)6

FOUNDATION PLAN NOTES
CONCRETE CURB. VERIFY EXTENT w/ ARCH DWGS.

CONCRETE HOUSEKEEPING PAD PER . SEE ARCH FOR EXTENT. SEE NOTE#11 FOR ADDL INFO.

SLOPED AND/OR DEPRESSED SLAB. DEPRESS BUILDING PAD AND PROVIDE FULL SLAB AND BASE THICKNESS. SEE & . WHERE
DEPRESSION IS GREATER THAN 2" AND ADJACENT TO BUILDING FOUNDATION

ELEMENT IT MAY BE NECESSARY TO STEP FOOTING IN ORDER TO MAINTAIN MINIMUM FOOTING EMBEDMENT PER SECTIONS. CONTRACTOR TO
COORDINATE IN FIELD.
8" CMU WALL. FOR REINFORCING, SEE AND CMU GENERAL NOTES.

CONDUITS IN CMU TO BE PER CMU GENERAL NOTES.

WOOD POST, 6x6 @ 6" NOMINAL WALLS

SHEAR WALL TYPE, EXTENT, AND ANCHOR BOLT LAYOUT, SEE FOR SCHEDULE, UNO. EXTENT INDICATES MINIMUM REQUIRED SHEAR WALL LENGTH.

SIMPSON HOLDOWN LOCATION. REFERENCE NUMBER INDICATES HDU HOLDOWN TYPE. SEE & .

Mk
Mk -X'-XX"
FOOTING MARK. SEE FOOTING SCHEDULE FOR TYPICAL TOF ELEVATION.

ELEVATION IS RELATIVE TO REFERENCE ELEVATION (0'-0").

FOOTING MARK WITH TOP OF FOOTING ELEVATION. ELEVATION IS RELATIVE TO REFERENCE ELEVATION (0'-0").

WOOD STRUCTURAL WALL.

MECHANICAL UNIT. THE CONTRACTOR SHALL COORDINATE ALL

MECHANICAL EQUIPMENT FOR SIZE & LOCATION WITH OTHER TRADES & THE STRUCTURAL DRAWINGS. UNIT SIZES & LOCATIONS SHOWN ARE
APPROXIMATE.
6/S501
10/S501 11/S501
2/S511
12/S501
A/S512
B/S512 4/S512
9/S501 8/S501
1/S516
1 FRAMING LEGEND
C=

1. NOTES AND DETAILS ON SHEETS LABELED AS "GENERAL" OR "TYPICAL" ARE APPLICABLE TO ALL DRAWINGS, UNO.

2. VERIFY ALL BUILDING DIMENSIONS AND ELEVATIONS w/ ARCH DRAWINGS. NOTIFY THE ARCHITECT IMMEDIATELY IF THERE ARE ANY CONFLICTS w/ DIMENSIONS SHOWN.

3. DIMENSIONS SHOWN ARE TO CL OF COLUMN, FACE OF STUD.

4. DESIGN, FABRICATION AND INSTALLATION OF MANUFACTURED STAIRS IS BY OTHERS.

5. FOR GUIDELINES AND LIMITATIONS FOR SUPPORTING FROM STRUCTURE, SEE SPECIFICATIONS.

6. SEPARATION JOINT DIMENSIONS SHOWN ON PLAN INDICATE MINIMUM CLEAR DISTANCE REQUIRED BETWEEN ADJACENT BLDG ELEMENTS. WHERE BLDG

FINISHES/FIRE PROTECTION OCCUR, CLEAR DIMENSION SHALL BE MAINTAINED BTWN THOSE ELEMENTS.

7. ALL WOOD STUD WALLS ARE TO BE 2x6 @ 16"CC UNO ON THE PLANS, SECTIONS, OR SCHEDULES. COORDINATE STUD SIZE WITH ARCH DWGS.

8. ROOF SHEATHING SHALL BE 15/32" (1/2" NOMINAL) APA RATED SHEATHING/ STRUCTURAL 1 GRADE CD w/ EXTERIOR GLUE. MIN SPAN RATING SHALL BE 24/0.

LAY LONG DIMENSION PERPENDICULAR TO SUPPORTS, ENDS STAGGERED AS SHOWN ON PLAN. NAIL w/ 10d NAILS @ 6"CC EDGES, 12"CC FIELD UNO ON PLANS.

WHERE BLOCKING IS NOTED, USE 2x4 FLAT AT ALL SHTG EDGES SUPPORTED IN Z2 CLIPS. USE PLYCLIPS AT MIDSPAN OF UNSUPPORTED ROOF SHEATHING EDGES.

9. ALIGN JOISTS OVER STUDS BELOW WHERE FRAMING IS PERPENDICULAR TO WALL.

10. PROVIDE AN ADDITIONAL JOIST UNDER INTERIOR PARTITION WALLS THAT ARE PARALLEL TO THE JOISTS.

11. PROVIDE JOIST HANGERS WHERE SPECIFIED ON PLANS, SECTIONS, OR WHERE JOIST IS NOT IN DIRECT BEARING. FOR JOIST HANGER SCHEDULE AND NOTES, SEE .

12. FOR WOOD BEAM TO HSS COLUMN CONNECTION, SEE TYP, UNO.

13. SPLICES AT CMST STRAPS SHALL BE LAPPED A MINIMUM OF 16" w/ NAILS DRIVEN THRU BOTH.

14. INSTALL STRAPS OVER SHTG UNO. STRAP NAILS MAY REPLACE TYP DIAPHRAGM NAILING.

15. WHERE HSS COLUMNS INTERRUPT PLATES, SPLICE PER .

16. SEE ARCH DRAWINGS FOR FLOOR TOPPING MATERIAL AND THICKNESS. MAX WEIGHT OF TOPPING SHALL NOT EXCEED 10 PSF.

17. SEE ARCH DWGS FOR INFORMATION REGARDING VENT OPENINGS AT BLOCKING AND SHEATHING.

18. WHERE EXTENT OF SHEAR WALL DOES NOT COINCIDE WITH EXTENT OF WALL FACE, PROVIDE GYPSUM BOARD FURRING TO PLANE OUT FINISHES. COORDINATE SIDE OF WALL TO BE SHEATHED WITH ARCH DRAWINGS, UNO.

19. WHERE FRAMING HARDWARE IS REQUIRED TO BE IN THE SAME PLANE AS THE WALL FINISHES, HARDWARE SHALL BE "LET-IN" TO FINISHES FOR A FLAT, SMOOTH APPEARANCE. TYPICAL ALL FLOORS.

20. VERIFY ALL FLOOR OR ROOF OPENING DIMENSIONS w/ ARCH & MECH DRAWINGS PRIOR TO STAIR FABRICATION. GENERAL CONTRACTOR IS RESPONSIBLE FOR

COORDINATION AND LOCATION OF PLACEMENT OF BEAMS ADJACENT TO STAIR OPENINGS.

21. WHERE WOOD STUD WALLS ABUT MASONRY WALLS, PROVIDE 5/8"Ø ANCHOR BOLTS w/ 5" EMBED @ 24"CC & 6" FROM T&B @ STUD END.

22. SEE ARCH FOR LOCATION OF CRICKETS REQUIRED FOR DRAINAGE. ROOF SHEATHING BELOW SHALL BE CONTINUOUS.

23. GENERAL CONTRACTOR TO COORDINATE SKYLIGHT LOCATIONS WITH ROOF TRUSS MANUFACTURER AND ARCH.

24. SEE PRE-MANUFACTURED WOOD TRUSS NOTES FOR LOADING AND CONFIGURATION INFORMATION.

PSL
LVL
LSL
HDR
DBL
MST48
(A) POST IS ABOVE ONLY
MK
X'-X" 2 (2)6

FRAMING PLAN NOTES
X'
-XX"
TOW
X'
-XX"
TOF
X'
-XX"
TOW
X'
-XX"
TOW
OPENING. LOCATE OPENING PER AMEP DRAWINGS. FOR SUPPORT
SEE .

CONCRETE CURB. SEE .

CONCRETE WALL. SEE FOUNDATION PLAN FOR ADDL INFO.

TOP OF WALL. TYPE INDICATED AT BASE OF WALL ONLY.

CONCRETE COLUMN. SIZE INDICATED AT BASE LEVEL OF COLUMN ONLY.

TOP OF WALL ELEVATION ABOVE REFERENCE TOP OF CONCRETE (0'-0").

SOLID GROUTED CMU WALL. SEE FOUNDATION PLAN FOR ADDL INFO.

WALL BELOW, SEE FOUNDATION OR FRAMING LEVEL BELOW FOR WALL TYPE.

CMU COLUMN. SIZE INDICATED AT BASE LEVEL OF COLUMN ONLY.

TOP OF WALL ELEVATION ABOVE REFERENCE TOP OF CONCRETE (0'-0").

WOOD STRUCTURAL WALL BELOW.

SHEAR WALL ABOVE; TYPE AND EXTENT, SEE FOR SCHEDULE, UNO.

EXTENT INDICATES MINIMUM REQUIRED SHEAR WALL LENGTH.

SHEAR WALL BELOW
3 1/2" WIDE x 11 7/8" DEEP LAMINATED STRAND LUMBER BEAM, TYP UNO. 1 3/4" WIDE x 11 7/8" DEEP LAMINATED VENEER LUMBER BEAM, TYP UNO. 5 1/4" WIDE x 11 7/8" DEEP PARALLEL STRAND LUMBER BEAM, TYP UNO.

HEIGHT OF CL OF BEAM CAMBER AS NOTED ON PLANS. WHERE C IS NOT NOTED, BEAMS ARE NOT CAMBERED. FABRICATE AND ERECT ALL BEAMS

WITH NATURAL BEAM CAMBER UP WHERE NO CAMBER IS INDICATED ON PLANS.

DOUBLE JOIST. TYPE AND SIZE TO MATCH ADJACENT JOISTS. CONNECT PER NAILING SCHEDULE OR .

HEADER BELOW. SEE UNO ON PLAN.

SIMPSON STRAP PER PLAN.

TOP PLATE SPLICE. TYPE PER . WHERE NO INDICATION OCCURS, SEE .

TOP OF FRAMING ELEVATION (i.e. UNDERSIDE OF FLOOR SHTG) ABOVE REFERENCE TOP OF CONCRETE (0'-0") TYP, UNO.

TOP OF WALL ELEVATION ABOVE REFERENCE TOP OF CONCRETE (0'-0") (i.e.

TOP OF DBL TOP PL, TYP UNO).

WOOD POST, 6x6 STUDS @ 6" NOMINAL WALLS, TYP UNO.

EXTENT OF BLOCKED DIAPHRAGM.

AREA OF OVERBUILD FRAMING. ROOF SHEATHING BELOW SHALL BE CONTINUOUS.

MECHANICAL UNIT. THE CONTRACTOR SHALL COORDINATE ALL

MECHANICAL EQUIPMENT FOR SIZE & LOCATION WITH OTHER TRADES & THE STRUCTURAL DRAWINGS. UNIT SIZES & LOCATIONS SHOWN ARE
APPROXIMATE.

SIMPSON HOLDOWN LOCATION. REFERENCE NUMBER INDICATES HDU HOLDOWN TYPE. SEE & .

RCT
RGT
RT1 ROOF TRUSS TYPE AND EXTENT. FOR PROFILES SEE SHEET
ROOF GIRDER TRUSS. COORDINATE GIRDER TRUSS PROFILE WITH ROOF CONFIGURATION.

ROOF COLLECTOR TRUSS. COORDINATE COLLECTOR TRUSS PROFILE WITH ROOF CONFIGURATION.

Mk STRAP
Mk
Mk

NAILING
TOP OF WALL. TYPE INDICATED AT BASE OF WALL ONLY.
10/S514
3/S512
2/S511
B/S512 8/S512
2/S511
4/S514
A/S512
S202
10/S501
4/S516
S515
S

S TA TE
O F
CA
L
I

FO R N I A

STRUCTURAL
R
ROF
E
P

ED ER T IS GE
S
I
N

ENGINEER
O
AL
600 Q STREET, SUITE 200
SACRAMENTO, CA 95811
916 443 0303
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP
REVISIONS #

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
WILLIAM B.

RADER
No. 3592
10/23/2024 5:26:07 PM c:\revit\2023-0123_DRY CREEK WWTP_rvt22_CENTRAL_Francisco_O_Rodriguez.rvt S121

PLAN NOTES

DCWWTP OPERATIONS

AND LAB BLDG
2100 15.01Author
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
NO. DATE DESCRIPTION
1 8/28/2024 PC Revisions

BID SET (PRELIMINARY)
1 1
22 44
55 10 10
11 11
AABBCC
D
EGG
6 77
88 99
F
33 1
1 0'-0"

CURB PLAN KEY

DEPRESSED SLAB

CONCRETE CURB
1 S

S TA TE
O F
CA
L
I

FO R N I A

STRUCTURAL
R
ROF
E
P

ED ER T IS GE
S
I
N

ENGINEER
O
AL
600 Q STREET, SUITE 200
SACRAMENTO, CA 95811
916 443 0303
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP
REVISIONS #

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
WILLIAM B.

RADER
No. 3592
10/23/2024 5:26:08 PM c:\revit\2023-0123_DRY CREEK WWTP_rvt22_CENTRAL_Francisco_O_Rodriguez.rvt S200

CURB PLAN

DCWWTP OPERATIONS

AND LAB BLDG
2100 15.01Author
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
- CURB PLAN 1/8" = 1'
-0"
SEE S121 FOR NOTES
NO. DATE DESCRIPTION
1 8/28/2024 PC Revisions

BID SET (PRELIMINARY)
1 1
22 44
55 10 10
11 11
AABBCC
D
EGG
68'-0" 18'-0" 12'-0" 56'-0"
154'-0"
7'-6"
127'-0"
68'-0"
C HSS4x4x1/2 HSS4x4x1/2 C HSS4x4x1/2 C HSS4x4x1/2 CC
34'-0 1/2"
1'-4" WIDE x 18" DEEP CONT

FOOTING TYP
2x6 STUDS
@ 16"CC TYP
13'-2"
A6x6 6x6
HSS5x5x1/4
6" CONCRETE SLAB ON
GRADE WITH #3 @ 18"CC
EA WAY OVER 15 MIL

VAPOR RETARDER OVER
4" CRUSHED ROCK PER
NOTE #5
6 77
88 99
F
15'-0"6'-7"15'-7"6'-10"5'-5"28'-5"11'-0"18'-9"6'-3" 13'-2" 26'-5 1/2"
A
S302
CC
6x86x8
33 6x66x6
4'-0" WIDE x 3'-6"

DEEP FOOTING
3 8'-0"
3 8'-0"
2 14'-0"
3 24'-0"
2 20'-0"
1 36'-0"
3 24'-0"
3 6'-0"
3 6'-0"
3 6'-0"
3 8'-0"
3 15'-0"
3 16'-0"
2 4'-6"
3 12'-0"
1 32'-0"
2 8'-0" 3
12'-0"
2 8'-0"8'-1 3/4"3'-11"3'-4"3'-9"8'-4"
C6x8
C
6x8
C 6x6 C 6x6
C
S302
E
S301F
S301
CHSS4x4x1/4
HSS4x4x1/2 HSS4x4x1/2
14 S501
C HSS4x4x1/4
22 2 2 2 2 A 2 A 2
2 A
2 A
2 2
A
2 A
2 A
2 2
2 A
2 A
2 A
A
2 A
2 2
22 TYP
1'-4"MIN
1'-4"
TYP
1'-4"MIN
TYP
12" MIN
TYP
2 2
2 88
11 1
1 11
1 1
1 1
1 1
11 1
1 1
1 1
1 1
HSS4x4x1/4HSS4x4x1/4
1 1
AA
22 1
S

S TA TE
O F
CA
L
I

FO R N I A

STRUCTURAL
R
ROF
E
P

ED ER T IS GE
S
I
N

ENGINEER
O
AL
600 Q STREET, SUITE 200
SACRAMENTO, CA 95811
916 443 0303
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP
REVISIONS #

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
WILLIAM B.

RADER
No. 3592
10/23/2024 5:26:08 PM c:\revit\2023-0123_DRY CREEK WWTP_rvt22_CENTRAL_Francisco_O_Rodriguez.rvt S201

FOUNDATION PLAN

DCWWTP OPERATIONS

AND LAB BLDG
2100 15.01Author
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
- FOUNDATION PLAN 1/8" = 1'
-0"
SEE S121 FOR NOTES
TOP OF FOOTING AT -1'-0" TYP UNO ON PLANS.

NOTE:

FOOTING SCHEDULE
Mk
SIZE
(WxLxD)
BOTT
REINF
TOP
REINF
A 3'-0" x 3'-0" x 1'-6" (4) #5 EW
C 5'-0" x 5'-0" x 1'-6" (7) #5 EW
S201 A
NO. DATE DESCRIPTION
1 8/28/2024 PC Revisions
2 10/23/2024 PC Revisions 2

BID SET (PRELIMINARY)
16" RED I-90 @ 24"CC 2x10 RAFTER TAILS AT EAVE
20"
RED
I-90H
@ 32"CC
RT-2

PRE-FAB

TRUSSES
@ 24"
CC
2x10

RAFTER TAILS AT
EAVE
16" RED I-90 @ 24"CC
2x10 RAFTER TAILS AT EAVE
2x8 @ 24"CC
16" RED I-90 @ 24"CC 2x10 RAFTER TAILS AT EAVE
2x10 @ 24"CC
2x10 @ 24"CC
2x10 @ 24"CC

HDR HDR HDR HDR HDR HDR DBL DBL DBL DBL

DBLDBLDBLDBL
DBL
DBL
DBL
DBL
DBL
DBL
DBL
DBL

HDR HDR HDR HDR HDR

HDR HDR
HDR
HDRHDR

HDR HDR

HDR HDR HDR HDR HDR HDR
HDR HDR HDR HDR HDR 5 1/8 x 12 GLB

HDR HDR

HDR HDR
5 1/8 x 12 GLB
1 3/4 x 11 7/8 LVL
1 3/4 x 11 7/8 LVL
11 22
44 55
10 10
11 11
AABBCC
D
EGG
RIDGE
RIDGE

VALLEY TRUSS
5 1/8 x 12 GLB
5 1/8 x 12 GLB
5 1/8 x 12 GLB
3/4" ROOF

SHEATHING
5 1/8 x 31.5 GLB

OPENING IN ROOF

PLANE BELOW
5 1/8 x 21 GLB
5 1/8 x 21 GLB
VALLEY
5 1/8 x 19 1/2 GLB (BELOW)
HSS12x6x1/2
6 77
88 99
F
C
S301
G
S301
H
S301
J
S301
B
S301
A
S302
A
S301
24'-0" TOW
24'-0" TOW
33 1 3/4x20 LVL LEDGER
15'-0" TOF 16'-0" TOF
15'-0" TOF 16'-0" TOF
6 x12 BM
14'-0" TOF
14'-0" TOF
14'-0" TOF
1 3/4x20 LVL LEDGER
5 1/8 x 31.5 GLB5 1/8 x 31.5 GLB5 1/8 x 31.5 GLB5 1/8 x 31.5 GLB 215#
215#
215#
215#
215#
215#
60#
70#
40#
60#
60#
60#
310#
60#
5 1/8 x 19 1/2 GLB
14'-0" TOF
6x6 TO HDR BLW TYP AT DORMER
6x8 HDR HIGH

ROOF SHTG PER
NOTE #11 TYP
HSS12x6x1/2
310#
310#
5 1/8 x 10.5 GLB

DBL TRUSSES AT

LOCATIONS WHERE

OPNG EXCEED

TRUSS SPCG, TYP
6x8 HEADOUT AT

LOCATIONS OF OPNG
w/ A35 CLIPS ON

BOTH SIDES AND

BOTH ENDS, TYP

FROM GRIDLINES E TO G ALONG THIS LINE
4x8 WALL STUDS @ 16"CC
FROM GRIDLINES 1-4 ALONG THIS LINE
4x8 WALL STUDS @ 16"CC
B
S302
C
S302

HEADOUT AT LOCATION
OF OPNG w/ 6x8 BM w/
HUTF HGR TYP AT IJOIST LOCATIONS
2x6 OUTRIGGERS
@ 24"CC
-
--- 2
S516

PROVIDE INVERTED

HU HANGER TO

FASCIA, TYP AT THIS

LOCATION
SIM
6x6 TO HDR BLW TYP AT DORMER
D
S302
B
S301
E
S302
F
S302 G
S302
H
S302
J
S302
RAKE
F
S302
MK
1500#
AHU
MK
1500#
AHU
MK
2300#
AHU
MK
1000#
AHU
L
S302
TYP

ROOF SHTG

LAYOUT PER
NOTE #11

SEE LOW CANOPY

FRAMING PLAN BELOW
6 S515
1 1
1 1
C
S301
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
1 1
HSS4x4x1/4HSS4x4x1/4
C10x25
HSS6x3x1/4
FLAT
1 COLLECTOR TRUSS =1000#COLLECTOR TRUSS =1000#
11 <varies>
PROVIDE MSTA24
ALONG GRID LINE 1

FROM WOOD TO

STEEL TRANSITION
PROVIDE 4X

BLOCKING AT

LOCATION
2 10 10
11 11 CC GG 9 9 FF A
S301

OPEN MESH

METAL ROOFING
L
S302
WTx17.5 @ 5'-8"CC,
TYP
CONT C10x15.3
1 1
S

S TA TE
O F
CA
L
I

FO R N I A

STRUCTURAL
R
ROF
E
P

ED ER T IS GE
S
I
N

ENGINEER
O
AL
600 Q STREET, SUITE 200
SACRAMENTO, CA 95811
916 443 0303
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP
REVISIONS #

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
WILLIAM B.

RADER
No. 3592
10/23/2024 5:26:09 PM c:\revit\2023-0123_DRY CREEK WWTP_rvt22_CENTRAL_Francisco_O_Rodriguez.rvt S202

ROOF FRAMING
PLAN

DCWWTP OPERATIONS

AND LAB BLDG
2100 15.01Author
1800 Booth Road
Roseville, CA 95747
ROOF FRAMING PLAN1/8" = 1'
-0" CITY OF ROSEVILLE - DCWWTP
SEE S121 FOR NOTES
- LOW CANOPY FRAMING PLAN 1/8" = 1'
-0"
NO. DATE DESCRIPTION
1 8/28/2024 PC Revisions
2 10/23/2024 PC Revisions 2

BID SET (PRELIMINARY)
C

SHTG PER PLAN

I-JOIST PER PLAN

SHTG PER
PLAN

WALL STUDS

PER PLAN

HDR PER
PLAN

BEVEL TOP PL

AND STRAP
PER
7 S514
HTS 16 @ EA

JOIST, WRAP END

OF STRAP TO

BOTT OF TOP PL
EN

LVL BLKG

SHEAR TRANSFER
CLIP @ 24"CC UNO
IN
A
S512

I-JOIST WEB

STFNR PER A
S512
16D TO EA SIDE

OF WEB AND EA

SIDE OF BLKG
2x10 OUTRIGGER
PER PLAN; ATTACH
TO ROOF JOIST w/
(6) 3/4"Ø LAG
SCREWS
2'-0" MAX 2'-0" MIN
1 3/4 LVL FASCIA w/
10D T&B EA JOIST

PROVIDE WEB STFNR

WHERE OUTRIGGER

ATTACHES TO I-JOIST
G
1 5

SHTG PER PLAN

SHTG PER PLAN

SHTG TO EXTEND

TO TRUSS BLKG

WALL STUDS

PER PLAN

TRUSS PER PLAN
2x4 TOP CHORD
2x4 BOTT CHORD

SOFFIT PER ARCH
SIMPSON LTS16
STRAP EA JOIST;
PROVIDE (6) 10d
NAILS INTO 2x4

BLKG AND TOP PL
1 1

WALL STUD PER
PLAN

SHTG PER PLAN

SHTG PER PLAN

LEDGER PER PLAN JOIST PER PLAN
PROVIDE 3x BLKG @ LEDGER
w/ A35 EA END TO STUD;

ALT T&B TO AVOID CONFLICT

OF NAILS EA SIDE OF STUD

I-JOIST WEB

STFNR AS IN
1 S514
1 3/4" LVL LEDGER, DEPTH TO
MATCH I-JOIST FRMG; PROVIDE (4)
SDS25600 @ EA STUD, 1 1/2" MIN
EDGE DISTANCE, 2" SPCG MIN
STUDS @ 16"CC PER PLAN
1 1
G

SHTG PER PLAN

WALL STUDS

PER PLAN

HDR PER PLAN
PROVIDE 3x BLKG @ LEDGER
w/ A35 EA END TO STUD; ALT

T&B TO AVOID CONFLICT OF

NAILS EA SIDE OF STUD
24" MAX
12" MIN
3'-0" MIN
1 3/4" LVL LEDGER, DEPTH TO
MATCH I-JOIST FRMG; PROVIDE
(4) SDS25600 @ EA STUD, 1 1/2"
MIN EDGE DISTANCE, 2" SPCG MIN

HU/HUC HGR

SHTG PER PLAN
CS 14 STRAP o/ 3x

BLKG IN WALL TO
LVL BLKG @ 48"CC

JOIST PER PLAN
EN
EN
2 1/2"

SADDLE HANGER
HSS10x5x1/4

SHTG PER PLAN

GLB PER PLAN

JOIST PER PLAN

JOIST PER PLAN
B
S301
SIM
4'-0" MIN

SOFFIT PER ARCH

C-CHANNEL

PER PLAN WT PER PLAN

MTL DECK PER
ARCH
A
A
1/4 6

SECTION A-A
NTS
MTL DECK PER PLAN 1/4 6-12
1/4 6
1 1
BIRDSMOUTH 2x

MAIN MEMBER
1 1

SHTG PER PLAN

TRUSS PER PLAN

SHTG PER PLAN

SHTG TO EXTEND

TO TRUSS BLKG

WALL STUDS

PER PLAN

HDR PER PLAN
2x4 TOP CHORD
2x4 BOTT CHORD

SOFFIT PER ARCH
SIMPSON LTS16
STRAP EA JOIST;
PROVIDE (6) 10d
NAILS INTO 2x4

BLKG AND TOP PL
1 SHTG

JOIST PER PLAN

GLB PER PLAN

HB SADDLE HGR

HDR PER PLAN

SHTG PER PLAN
2x PER PLAN

GLB PER PLAN
1 TOC

SEE PLAN
TOF

SEE PLAN

SEE PLAN

SLAB ON GRADE

PER PLAN
#4 DOWEL@
18"CC 12"
3" CLR
18"
MIN
(2) #5 T&B

BARS UNO

STOREFRONT
1 1
C

SHTG WHERE
OCCURS
EN

CURB REINF
PER 10
S501
.
6" @ CONC
SITEWORK, 8" @

LANDSCAPING
TOC

SEE PLAN
TOF

SEE PLAN
3" CLR
18"
MIN

SEE PLAN
(2) #5 T&B

BARS UNO

SLAB ON GRADE

PER PLAN
#4 DOWEL@
18"CC 12"
1 S

S TA TE O F CA L I FO R N I A

STRUCTURAL
R
ROFE P
ED

ER T IS
GE
SI N

ENGINEER
O AL
600 Q STREET, SUITE 200
SACRAMENTO, CA 95811
916 443 0303
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
WILLIAM B.

RADER
No. 3592
10/23/2024 5:26:09 PM c:\revit\2023-0123_DRY CREEK WWTP_rvt22_CENTRAL_Francisco_O_Rodriguez.rvt S301

BUILDING

SECTIONS

DCWWTP OPERATIONS

AND LAB BLDG
2100 15.01Author
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP

SECTION
S301
B 1/2" = 1'-0"
Section 7

SECTION
S301
C 1/2" = 1'-0"
Section 2

SECTION
S301
G 1/2" = 1'-0"
Section 3

SECTION
S301
H 1/2" = 1'-0"
Section 4

SECTION
S301
A 1/2" = 1'-0"
Section 9

SECTION
S301
D 1/2" = 1'-0"
Section 10

SECTION
S301
1/2" = 1'-0" J
Section 6

SECTION
S301
E 1/2" = 1'-0"
Section 11

SECTION
S301
F 1/2" = 1'-0"
Section 12
NO. DATE DESCRIPTION
1 8/28/2024 PC Revisions
2 10/23/2024 PC Revisions 2
2 2

BID SET (PRELIMINARY)
11 FULL SIZE CMU

WALL PER PLAN

JOIST PER
PLAN

SHTG PER
PLAN

WALL STUDS

PER PLAN
TOC

SEE PLAN
TOF

SEE PLAN

SLAB ON GRADE

PER PLAN
#4 DOWEL @
16"CC 12"

WOOD FRAMED
WALL

CANOPY ON

TOP OF CMU
HTS 16 @ EA JOIST,

WRAP END OF STRAP

TO BOTT OF TOP PL

SHEAR TRANSFER
CLIP @ 24"CC
UNO IN 8
S101
LB HGR

LVL BLKG
2x8 @ 24"CC AT

OUTRIGGER

LOCATION
EN
16D TO EA SIDE OF WEB

AND EA SIDE OF BLKG

SHTG PER
PLAN
1 3/4 LVL FASCIA
w/ 10D T&B EA
JOIST
EN

SITE WORK PER
ARCH
3" CLR TYP
(4) #6 EQ SPACED
T&B
#7 @ 12"CC
C

GLB PER PLAN

PROVIDE WEB STFNR

WHERE OUTRIGGER

ATTACHES TO I-JOIST

BOTH SIDES OF JOIST
4'-0" MAX
4'-0" MAX

WALL STUD PER PLAN

SHTG PER PLAN
2x10 OUTRIGGER;

ATTACH TO ROOF
JOIST w/ (12) 3/4"Ø

LAG SCREWS AT

LOCATION OF SISTER
2x6 @ 16"CC
HU HGR
(2) H8 TO TOP PL @ 32"CC
A34 EA SIDE OF JOIST

AT RAFTER TAIL

STUD PER PLAN

HDR PER PLAN
1 STUD PER PLAN

SHTG PER PLAN
EN

LEDGER PER PLAN JOIST PER PLAN

SHTG PER PLAN

I-JOIST WEB

STFNR AS IN
PROVIDE 3x BLKG @ LEDGER
w/ A35 EA END TO STUD;

ALT T&B TO AVOID CONFLICT

OF NAILS EA SIDE OF STUD
F
S301
AS IN
AS IN
G
S301

HSS PER PLAN

HSS PER PLAN
1/4 4
1/4 4
1 1
1/4 4
1 HSS PER PLAN
2x NAILER
SHTG
TRUSS

PER PLAN
F

JOIST PER PLAN

HGLS SADDLE
HANGER
SHTG

GLB PER PLAN

I JOIST PER PLAN
MIN
1'-0"

SHTG PER PLAN

SHTG PER PLAN

OUTRIGGER PER
PLAN
4 SHTG

SHTG PER PLAN
AS IN

I JOIST PER PLAN
SHTG

STUD PER PLAN
G
S301
SHTG
SHTG

TRUSS PER
PLAN
AS IN
H
S301
3 SHEAR PANEL BLOCKING SHTG
PER

SHTG PER PLAN
5 S515

STUD PER PLAN

DBL TOP PL
11 C-CHANNEL

PER PLAN

WT PER PLAN

MTL DECK PER
ARCH
A
A
1/4 6
1/4 6

MTL DECK

PER PLAN
1/4 6-12

SECTION A-A
NTS
S

S TA TE O F CA L I FO R N I A

STRUCTURAL
R
ROFE P
ED

ER T IS
GE
SI N

ENGINEER
O AL
600 Q STREET, SUITE 200
SACRAMENTO, CA 95811
916 443 0303
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
WILLIAM B.

RADER
No. 3592
10/23/2024 5:26:11 PM c:\revit\2023-0123_DRY CREEK WWTP_rvt22_CENTRAL_Francisco_O_Rodriguez.rvt S302

BUILDING

SECTIONS

DCWWTP OPERATIONS

AND LAB BLDG
2100 15.01Author
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP

SECTION
S302
A 1/2" = 1'-0"
Section 8

SECTION
S302
B 1/2" = 1'-0"
FOR - 1

SECTION
S302
C 1/2" = 1'-0"
FOR - 2
DETAIL
S302
D 1/2" = 1'-0"
Section 1
DETAIL
S302
E 1/2" = 1'-0"
FOR 5
DETAIL
S302
F 1/2" = 1'-0"
FOR 6
DETAIL
S302
G 1/2" = 1'-0"
FOR 7
DETAIL
S302
H 1/2" = 1'-0"
FOR 8
DETAIL
S302
1/2" = 1'-0"
J
FOR 9
DETAIL
S302
L 1/2" = 1'-0"
FOR 11
NO. DATE DESCRIPTION
1 8/28/2024 PC Revisions

BID SET (PRELIMINARY)
D
D
D
D

END HOOKS & BENDS

FOR DEVELOPMENT OF

DEFORMED BARS

TIES & STIRRUPS
90° 45°
180°
135°
90°

MINIMUM INSIDE BEND DIAMETER
D=6d FOR #3 THRU #8
D=8d FOR #9 THRU #11
D=10d FOR #14 THRU #18
NOTE:

ALL HOOKS SHALL BE 90° OR 180° STANDARD
HOOKS UNLESS OTHERWISE SHOWN OR NOTED.

MINIMUM INSIDE BEND DIAMETER
D=4d FOR #3 THRU #5
D=6d FOR #6 THRU #8
12d
d d
3" M
6 IN
d
2 1/2" MIN
4d

DO NOT EDIT
3" MIN
6d FOR #3 THRU #5
12d FOR #6 THRU #8
180°
2 1/2" MIN
4d
D
D
D
REBAR
REBAR
PL PER

DETAILS,
2/3d MIN, TYP
NOTES:

1. REINFORCING TO BE WELDED, EXCEPT ASTM A706, SHALL CONFORM TO THE MATERIAL PROPERTY REQUIREMENTS OF ANSI/AWS D1.4, NEWEST EDITION.

2. ALL PREHEATING AND WELDING SHALL BE DONE IN ACCORDANCE WITH ANSI/AWS D1.4, NEWEST EDITION. ALL ELECTRODES FOR WELDING SHALL COMPLY WITH AWS CODE, E80 SERIES MINIMUM FOR ASTM A706 GR60 AND E90 SERIES MINIMUM FOR ASTM A615 GR60.

FOR HIGHER GRADE REINFORCING, REFER TO AWS D1.4, NEWEST EDITION, FOR ELECTRODE REQUIREMENTS.

3. ALL WELDING SHALL BE CONTINUOUSLY INSPECTED BY A QUALIFIED LABORATORY.

4. GAPS BETWEEN REBAR AND PLATE SHALL NOTE EXCEED 1/4d OR 3/16", WHICHEVER IS LESS.

E = EFFECTIVE THROAT = .2d MIN
E
d
E
E
E
REBAR
MIN
2d
MIN
2d
A
A
d
1/8" MIN
d
6d
SEE AT

LEFT FOR
SIZE

SECTION A-A

TANGENT
POINT

WELD PARALLEL TO BAR LENGTH
REBAR

STEEL PL PER
DETAILS 2/3d

MIN, TYP

BUTT WELDED BAR
1/2d MIN D
SEE NOTE 4 1/2d MIN

DOUBLE LAYER BARS

SINGLE LAYER BARS

CORNER BARS MAY BE USED

IN LIEU OF SINGLE BEND
90° STD
HOOK
LAP
LAP

PROVIDE STD HOOK AT ENDS OF ALL

INTERIOR REBAR, TYPICAL
NOTE:

SEE CONCRETE NOTES FOR ADDL

REQUIREMENTS
90° STD
HOOK
LAP
HOOK
90° STD
HOOK
90° STD
HOOK
90° STD
HOOK
90° STD
HOOK
90° STD
LAP
HOOK
90° STD

AT SPLICE

LAP TYP

AS DIRECTED BY

GEOTECHNICAL ENGINEER
PIPE

CAULK WHERE

NECESSARY

LEAN-MIX

CONC FILL

ALL HORIZ PIPES TO CLEAR
SLEEVE BY 1" ALL AROUND;
WRAP RISERS w/ BLDG PAPER

AS REQD TO PREVENT BOND

UTILITY PIPES TO BE
LOCATED IN MIDDLE 1/3

OF TOTAL DEPTH OF
FTG; STEP FTG AS

REQD TO MAINTAIN

NO DIGGING FOR

TRENCH PARALLEL

TO FOOTING BELOW

THESE LINES

ROUGHEN TO
1/4" AMPLITUDE

MULTIPLE UTILITY PIPES

WHERE OCCUR, SHOWN
DASHED

UTILITY PIPE RISER

IN FTG, WHERE OCCURS
SLEEVE
NOTES:

1. THE PROVISIONS HEREIN ARE APPLICABLE TO
CONTINUOUS FOOTINGS AND GRADE BEAMS.

2. NO PIPES SHALL BE PLACED BELOW ISOLATED SPREAD
FOOTINGS OR WITHIN 2 TO 1 BEARING ZONE AROUND
SPREAD FOOTINGS.

3. REINFORCING SHALL NOT BE INTERRUPTED, CUT OR
DISPLACED BY PLACEMENT OF UTILITY PIPE.

4. LEAN MIX CONCRETE FILL TO BE PLACED BEFORE FOOTING
IS CAST (MONO-POUR FOOTING CONC OPTIONAL.) MAKE

SAME WIDTH AS FOOTING AND FULL WIDTH OF PIPE
TRENCH.

5. STEP FOOTING IF PIPE OCCURS OUTSIDE OF MIDDLE THIRD
OF ORIGINAL FOOTING DEPTH.

6. IF PIPE IS IN PLACE PRIOR TO CASTING CONCRETE, WRAP
PIPE w/ 1" STYROFOAM INSULATION IN LIEU OF SLEEVE.

7. UTILITY PIPES ARE NOT ALLOWED PARALLEL IN FOOTING.

8. MULTIPLE UTILITY PIPES (TWO OR MORE) MAY BE

INSTALLED AS SHOWN, PROVIDED THEY ARE SPACED A
MINIMUM OF (4) PIPE/CONDUIT DIAMETERS ON CENTER
WITH A MINIMUM OF 3" OF CONCRETE BETWEEN. PIPE

DIAMETER INDICATED IS THE ROUGH HOLE SIZE THRU
FOOTING.

9. UTILITY PIPE RISERS MAY OCCUR IN CONTINUOUS

FOOTINGS PROVIDED THEY ARE NO LARGER THAN
(FOOTING WIDTH/6) AND OCCUR WITHIN THE MIDDLE 1/2 OF
THE FOOTING WIDTH. MULTIPLE RISERS MAY OCCUR IF
SPACED AS NOTED ABOVE.

10. UTILITY PIPES PERPENDICULAR TO FOOTINGS AND MORE
THAN 2'-0" BELOW BOTTOM OF FOOTINGS DO NOT REQUIRE

LEAN-MIX CONCRETE ENCASEMENT, SUBJECT TO
ACCEPTANCE BY THE GEOTECHNICAL ENGINEER.

11. CONDITIONS NOT CONFORMING TO THE PARAMETERS

NOTED ABOVE SHALL BE REVIEWED ON A CASE-BY-CASE
BASIS.

D
D/3 D/3 D/3
9"
MIN
2'-0"
MIN
3"

SEE NOTES

SEE NOTES
MIN
6"
2'-6" MAX

MIN TRENCH
2'-0"
MIN
9"
1 2
2x6 BEVELED KEY

FULL WIDTH AT
12'' MAX VERTICAL
SPACING & 6"

EDGE DISTANCE TYP LONG
REINF

VERT REINF

WHERE OCCURS
OPTION:

USE METAL K-LATH IN LIEU

OF KEYS FOR FULL DEPTH OF

FOUNDATION AT UNEXPOSED
FOUNDATIONS ONLY.

ADD TIE OR

VERTICAL EA

SIDE OF JOINT
2" 2"

FOOTING

CURB/STEM WALL

WHERE OCCURS

TYP UNO
LAP
'D'/3 'D'/3 'D'/3
'D'
TYP
1"
1st POUR 2nd POUR

CONSTRUCTION JOINT (CJ) SLAB CONTROL JOINT (SJ) EXPANSION JOINT (EJ)

EXPANSION

JOINT MATERIAL

PER SPECS
#4 DOWELS x 3'-0" @
18"CC; CENTER ON
JOINT
1/8" SEMIRIGID

SEALANT
NOTES:

1. CONSTRUCTION JOINTS AND CONTROL JOINTS SHALL DIVIDE SLAB INTO AREAS NOT EXCEEDING 225 SQ FT WITHOUT REENTRANT CORNERS AND WITH LENGTH TO WIDTH RATIOS NOT EXCEEDING 1 1/2 TO 1. JOINT SPACING SHALL NOT EXCEED 15 FEET IN EITHER DIRECTION.

2. CONTRACTOR SHALL SUBMIT LAYOUT PLAN SHOWING PROPOSED CONTROL AND CONSTRUCTION JOINT LOCATIONS TO ARCHITECT & STRUCTURAL ENGINEER FOR REVIEW & APPROVAL.

3. SEMIRIGID SEALANT TO BE EUCLID EUCO #700 OR EQUAL.
3/8" RADIUS
TOOLED EDGES;
VERIFY w/ ARCH IF

SEALANT REQD
3/8" RADIUS

TOOLED EDGES
THICKEN SLAB 2" MIN

AT JOINT TYP
1/8" SAW
CUT
3/8" SEALANT OVER
5/8" PACKING MATERIAL

AT CONTRACTOR'S OPTION,

SLAB REINFORCING MAY
RUN THROUGH JOINT 24"

MIN IN LIEU OF DOWELS
PROVIDE 1/2"Øx18"
SMOOTH DOWELS @
18"CC AT ENTRIES &

ADA PATH

SEE PLAN FOR

SUBGRADE, TYP
T/4
1/2"JOINT
1"
'T'
6" MIN
1st POUR 2nd POUR

SJ, SEE OPTIONAL

SONOTUBE

BLOCKOUT
NOTES:

1. SLAB BLOCKOUT SHALL NOT EXTEND BEYOND FOOTING.

2. AT EXPOSED CONCRETE CONDITIONS, COORDINATE BLOCKOUT SHAPE AND SIZE w/ ARCH DWGS.

DOWEL TO

MATCH SLAB
REINF

EXTEND TYP SLAB

REINF AT EDGE OF

SLAB INTO BLOCKOUT

COLUMN PER

PLAN, TYP

SLAB BLOCKOUT (CJ), TYP SEE

OMIT DOWELS

EDGE CONDITION

DOWEL TO MATCH

SLAB REINF

EXTEND TYP SLAB REINF AT

EDGE INTO BLOCKOUT

CORNER CONDITION
MIN
6"
MIN
6"

INTERIOR CONDITION
6 S501
6 S501

SLAB ON GRADE

PER PLAN

SUBGRADE PER PLAN, MAINTAIN

THICKNESS AT SLAB DEPRESSION
NOTE:

DETAIL APPLIES TO DEPRESSION / STEPS ≤ 2". FOR LARGER
DEPRESSION / STEPS, SEE .

T
T
2" MAX
SEE ARCH;
PER
PLAN
PER
PLAN
1 6 MIN
2"
9/S501
.
#4 @ 18"CC
18"
18"

OPTIONAL CJ

ROUGHEN TO
1/4" AMPLITUDE
2" CLR

CONC SLAB ON

GRADE PER PLAN

SEE PLAN FOR

SUBGRADE
24" MAX
#4 CONT

THICKENED
EDGE
8"
4" MIN
ADDITIONAL #4 WHERE
STEP > 12"
#4 CONT T&B
#3 @ 18"CC

STD HK VARIES

OPTIONAL CJ,

ROUGHEN TO
1/4'' AMPLITUDE

SEE ARCH
8" MAX
6" UNO, 8" MAX

SEE ARCH

SEE PLAN FOR

SUBGRADE

SLAB ON GRADE

PER PLAN
VARIES
9 S501
8 S501

SILL PL OR TRACK
#3 @ 18"CC, TYP
#4 CONT
#4 CONT

SLAB DEPRESSIONWHERE OCCURS

WOOD OR METAL

STUDS PER
1/2"Øx6" EMBED AB @ 48''CC,
TYP AT NON-BEARING WALLS.

AT BRG AND SHEAR WALLS,
SEE #3 @ 18"CC

CAP TIE
WHERE 'W'≥10''
VARIES
STD HK

SEE PLAN FOR

SUBGRADE

OPTIONAL CJ,

ROUGHEN TO
1/4" AMPLITUDE
6" MAX

SLAB ON GRADE

PER PLAN

SEE ARCH
VARIES
'W' SEE ARCH
OR
TOC

SEE ARCH FOR
#4 CONT
A
S513
A
S513
1 1

HOUSEKEEPING PAD AS

REQD, SEE MECH/ELEC

DRAWINGS FOR

LOCATION AND EXTENT
#4 @ 18"CC TYP AT

PERIMETER

CONC SLAB ON GRADE

PER PLAN
#4 @ 12"CC EW
@ MID-DEPTH
OF PAD
#4 CONT
TYP
ROUGHEN TO 1/4''

AMPLITUDE,

MONOLITHIC POUR

OPTIONAL

TYPICAL SLAB

REINFORCING
18"
18"

SEE PLAN FOR

SUBGRADE
TYP
2" CLR

SEE MECH/ELEC

DRAWINGS FOR

EQUIP ATTACHMENT
ADDL DOWELS @ 18"CC NEAR

CL OF PAD WHEN LENGTH OR
WIDTH OF PAD EXCEEDS 10'
4" TYP, 6" MAX

PER MECH/ELEC
6" MIN
(14) BOLT DIA
COORD w/ EQUIP LAYOUT
DRILL & EPOXY #4 DOWEL w/ 2 1/2"
EMBED @ (E) SLAB CONDITION;
4" MIN SLAB THICKNESS

CL EQUIP

ATTACHMENT
4 S501

SLOPE IF REQD

BY SOIL CONDITION

INDICATED ON

FOUNDATION
PLAN BY:
90° STD HOOK,
TYP
NOTE:

VERTICAL BARS OR TIES NOT SHOWN FOR CLARITY.

PROVIDE AS NOTED ON DRAWINGS. VERTICAL BARS
TYPICALLY TO EXTEND BOTTOM BAR UNO.
* ALTERNATE AT
CMU WALL: USE
16" RISE & 32" RUN
S S
S S
D
CLR
3"
TYP
LAP

PER SCH
CLR
3"
MIN
2 x "S"
18" MAX
"S"*
CLR
3"
CLR
2"
MIN
D
TYP
LAP

PER SCH
CLR
2"

AT FIRST STEP
"D" + 2 x "S"
6"MIN PIPE THRU STEM

WALL AS OCCURS
SEE

ADD DIAGONAL BARS TO

MATCH LONGITUDINAL BARS

IN SIZE AND SPACING
CLR
2"
CLR
"S"
18"
MAX
3"
7 S501
PROVIDE 3" MIN

CONC COVER ALL

AROUND COLUMN

AND BASE PL

SLAB ON GRADE

HSS COLUMN
TYP
3" CLR

EQUAL EQUAL

SEE SCHEDULE
CLR
3"
SEE
SCH
CLR
2"
MIN
8"
CL COL
TOC
TOF
SLAB

BLOCKOUT

BASE PL

SEE FTG SCH

FOR REINF
16 S501

FOOTING

FINISHED GRADE

NATIVE UNDISTURBED

SOIL OR ROCK

ENGINEERED FILL

RELATIVE COMPACTION

GREATER THAN OR EQUAL
TO 95%, AT LEAST 3%

OVER OPTIMUM MOISTURE

MOISTURE CONDITIONED FILL

RELATIVE COMPACTION
BETWEEN 90% TO 93%,
AT LEAST 3% OVER

OPTIMUM MOISTURE

REQUIRED DEPTH OF

ENGINEERED FILL SHALL

BE VERIFIED IN FIELD BY

GEOTECHNICAL

ENGINEER

SLOPE AS REQD BY

GEOTECHNICAL REPORT
5'-0"
D≥0

SECTION
SEE

EDGE OF
FTG

LIMITS OF

ENGINEERED FILL

HSS COL
PL 5/8" OVER 1 1/2" FLOWABLE

NON-SHRINK GROUT
'BCOL' + 6"
'BCOL' + 6"
.

EQ EQ
1 1/2" 1 1/2"
.

EQ EQ
1 1/2" 1 1/2"
1/4
CL COL
(2) 1 1/16"Ø HOLES FOR
3/4"Ø x 1'-6" F1554 GR 36
ANCHOR RODS w/ DBL NUTS
AND 6" PROJECTION; PROVIDE
F844 WASHERS ABV & BLW

BASE PL
CL COL
S

S TA TE O F CA L I FO R N I A

STRUCTURAL
R
ROFE P
ED

ER T IS
GE
SI N

ENGINEER
O AL
600 Q STREET, SUITE 200
SACRAMENTO, CA 95811
916 443 0303
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
WILLIAM B.

RADER
No. 3592
10/23/2024 5:26:12 PM c:\revit\2023-0123_DRY CREEK WWTP_rvt22_CENTRAL_Francisco_O_Rodriguez.rvt S501

TYPICAL CONCRETE

DETAILS

DCWWTP OPERATIONS

AND LAB BLDG
2100 15.01Author
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP

DETAIL NO SCALE
S501
1 STANDARD REBAR

HOOKS & BENDS
300SD001

DETAIL NO SCALE
S501
2 REBAR WELDING
300SD002

DETAIL NO SCALE
S501
3 INTERSECTION & CORNER

REINF AT FTGS
200SD011

DETAIL NO SCALE
S501
4 FOOTINGS AT UTILITY
PIPES
200SD003

DETAIL NO SCALE
S501
5 FOUNDATION

CONSTRUCTION JOINT
200SD012

DETAIL NO SCALE
S501
6 SLAB ON GRADE JOINTS
310SD001

DETAIL NO SCALE
S501
7 SLAB ON GRADE

BLOCKOUT
310SD002

DETAIL NO SCALE
S501
8 SLAB DEPRESSION
310SD004

DETAIL NO SCALE
S501
9 STEP IN SLAB 310SD003

DETAIL NO SCALE
S501
10 CURB AT SOG
310SD006

DETAIL NO SCALE
S501
11 CURB AT SLAB

DEPRESSION
310SD007

DETAIL NO SCALE
S501
12 HOUSEKEEPING PAD AT

SLAB ON GRADE
310SD005

DETAIL NO SCALE
S501
13 FOOTING STEP 200SD016

DETAIL NO SCALE
S501
14 SPREAD FOOTING
210SD011

DETAIL NO SCALE
S501
15 ENGINEERED FILL
200SD001

DETAIL NO SCALE
S501
16 BASE PLATE AT HSS
COLUMN
510SD005
NO. DATE DESCRIPTION
1 8/28/2024 PC Revisions

BID SET (PRELIMINARY)

NAILING SCHEDULE
600SN002

ALL NAILS FOR STRUCTURAL WORK SHALL BE COMMON WIRE NAILS UNO, CONFORMING TO THE FOLLOWING MINIMUM SIZES:
8d - 0.131" SHANK DIA (0.281" HEAD DIA) x 2-1/2"
10d - 0.148" SHANK DIA (0.312" HEAD DIA) x 3"
10d SHORT - 0.148" SHANK DIA (0.312" HEAD DIA) x 1 1/2" 16d - 0.162" SHANK DIA (0.344" HEAD DIA) x 3 1/2"
20d - 0.192" SHANK DIA (0.406" HEAD DIA) x 4"
20d BOX - 0.148" SHANK DIA (0.375" HEAD DIA) x 4"
40d BOX - 0.162" SHANK DIA (0.406" HEAD DIA) x 5"
RSRS-03 - 0.131" SHANK DIA (0.281" HEAD DIA) x 2 1/2" (ROOF SHTG RING SHANK) HOLES SHALL BE PRE-DRILLED WHERE NECESSARY TO PREVENT SPLITTING. NAILING NOT NOTED BELOW OR ON PLANS SHALL BE A MINIMUM OF TWO NAILS AT EACH CONTACT. 8d FOR 1x MATERIAL AND 16d FOR 2x MATERIAL.

1. JOISTS OR RAFTERS------SAWN LUMBER BRG ON PLATES TN EACH SIDE--------------------(2)10d I-JOISTS BRG ON PLATES EACH SIDE OF WEB------------(2)10d LAPPED TO SIDES OF STUDS 2x4, 2x6 -----------------------------(3)16d 2x8 - 2x12 --------------------------(4)16d

2. STUDS TO BEARINGS----- 2x4 STUDS TN EACH SIDE--------------------(2)10d (3x, 4x SIM) EN IN LIEU OF TN----------------(2)16d
2x6 AND 2x8 STUDS TN EACH SIDE ------------------- (3)10d EN IN LIEU OF TN----------------(3)16d
2x10 AND 2x12 STUDS TN EACH SIDE--------------------(4)10d EN IN LIEU OF TN----------------(4)16d

3. BLOCKING--------------------- BETWEEN JOISTS, RAFTERS TN EACH SIDE EACH END----(2)10d OR STUDS EN IN PLACE OF TN-------------(2)16d
BETWEEN JOIST OR TN EA SIDE ----------------------- (3)10d

RAFTER BEARINGS (PLATES)

4. CONTINUOUS RIM-----------TO DBL TOP PLATES TN EA SIDE---------------16d @ 16"CC

OMIT WHERE SHEAR TRANSFER
FASTENERS PER .

OCCUR

5. LEDGERS ----------------------TO STUDS 1x LEDGER ------------------------(2)8d 2x LEDGER-------------------------(3)16d

6. DOUBLE TOP PLATES -----LOWER PLATE TO 2x4 STUD-----------------------------------------------------(2)16d LOWER PLATE TO 2x6 OR 2x8 STUD------------------------------------------(3)16d UPPER PLATE TO LOWER PLATE -------------SEE .

7. SILL PLATES ------------------TO PARALLEL FRAMING--------------------------------------------------16d @ 12"CC TO PERPENDICULAR FRAMING -------EACH CONTACT------------------(2)16d

8. MULTIPLE STUDS---------- STAGGER FOR WIDTHS MORE THAN 4" ----------------------------16d @ 12"CC

9. BUILT UP BEAMS -----------(2)2x MEMBERS, TOP AND BOTTOM ------------------16d @ 12"CC CLINCHED 3 OR MORE 2x MEMBERS -----------------------------------------1/2" DIA BOLTS @ 12"CC STAGGERED

10. CEILING STRIPPING ----- HOLES SHALL BE PRE-DRILLED FOR 1x ------------ (2)8d (1-SLANT) NAILS AT ENDS OF STRIPPING BOARDS.

WHERE CEILING IS PLASTER OR 5/8" 2x ------------(2)16A (1-SLANT)

GYPSUM USE ANNULAR RING NAILS
(NO SLANT).

11. SHEAR WALL NAILING-------------------------------------------------------- SEE .

12. FLOOR OR ROOF NAILING-----------------SEE PLAN NOTES AND .

13. NON-STRUCTURAL -------AT EDGES AND INTERIOR HDG CASING NAILS-------------6d @ 6"CC

SIDING SUPPORTS

14. NON-STRUCTURAL -------AT EDGES NAILS TO MATCH SHEAR WALLS @ 6"CC SHEATHING AT FIELD NAILS TO MATCH SHEAR WALLS @ 12"CC

15. USE DEFORMED SHANK NAILS FOR ALL FLOOR SHEATHING.

16. ALL EXPOSED FASTENERS SHALL HAVE A ZINC-COATING CORROSION RESISTIVE SURFACE.

17. NAILS USED INTO PRESSURE TREATED OR FIRE RETARDANT MATERIAL SHALL BE HOT-DIPPED GALVANIZED PER ASTM A123 OR STAINLESS STEEL.
2/S511
9/S511
2/S511
1/S512
1 1
1 16d @ 12"CC

MIN UNO

NO HORIZ JOINT
@ SHEAR WALLS

SILL NAILING
INDICATES CORRESPONDING NOTE FROM NAILING SCHEDULE. THIS

IS THE MINIMUM REQUIRED NAILING, SHEAR WALL SCHEDULE NAILING SUPERCEDES THIS DETAIL.

INDICATES CORRESPONDING NAILING FROM SHEAR WALL SCHEDULE .

NOTES:

SHEAR TRANSFER CLIP

AT SHEAR WALL
LVL
ABV
#
X
11 10
C
E 10
C
11 11
10 C
10 C
3 1
6 F
5 3
11 1
LVL
E ABV
610SD001
5/8"Ø x 12" AB
4'-0"CC, TYP

UNO ON PLAN
18" AB @ CURB
(20) 16d EQ

SPACED, TYP
2x TRIMMER, TYP;
(2) 2x TRIMMER
WHEN OPNG > 6'-0"

UNO ON PLANS
2x PTDF SILL PL
UNLESS NOTED 3x

ON SHEAR WALL

SCHEDULE
2x (LESS THAN 6'-0")
(2) 2x (6'-1" TO 10'-0")
TREAT END w/

PRESERVATIVE AT

CURB WHERE OCCURS
2x BLKG @

SHTG JOINTS

UNLESS NOTED
3x ON SHEAR

WALL SCHEDULE

CONDITION

WHERE BOLT

OCCURS AT
STUD
(20) 16d EQ SPACED BTWN SPLICES
OR 16d @ 16"CC STAGGERED,

WHICHEVER REQUIRES MORE NAILS
2x BLKG
2x KING STUD, TYP;
(2) 2x KING STUD &
SIMPSON A35 T&B
WHEN OPNG > 6'-0"

UNO ON PLANS
(8) 16d, TYP
HEADER

PER SCH
2x STUDS
@ 16"CC
(6) 16d
HDG,
TYP

PROVIDE WASHER AS NOTED

IN WOOD NOTES
(2) 2x CONT

TOP PL UNO
(2) 16d @ 2x4 STUDS
(3) 16d @ 2x6 & 2x8 STUDS
HDG @ SILL COND

PROVIDE HOLE

FOR BOLT & CSK

FOR NUT & WASHER

AS REQD
SIMPSON A35 T&B EA END OF HEADER AT

ALL EXTERIOR WALLS AT OPENINGS WIDER
THAN 8'-0" OR WHERE KING STUD IS 3x AND

GREATER
(2) 16d @ 2x4
(3) 16d @
2x6 & 2x8
HEADER
'D'

SPLICE, TYP
4'-0" MIN LAP
* * *

BOTT PL
BREAK

WIDTH OF

OPENING
0 TO 4'-0"
4'-1" TO 6'-0"
6'-1" TO 8'-0"

TYP UNO ON PLAN OR IN PLAN NOTES
8"
10"
12"

NOMINAL HEADER

DEPTH 'D'
> 8'-0" SEE PLAN

HEADER SCHEDULE
NOTES:

1. HEADER SHALL BE FULL WIDTH
OF STUD WALL.

2. PROVIDE POSTS & ANCHORS AT

HOLDOWNS WHERE OCCUR PER
PLAN, SEE .

3. AT OPENINGS FOR MECH DUCTS,
SEE .

4. FOR SHEAR WALL NAILING, SEE
SCH AND .

5. LOCATE TOP PLATE BREAKS
OVER STUDS.
1 1/2"

END OF SILL PL OR NOTCH OR
HOLE WIDER THAN 1/3 PL WIDTH
TOP PL
BREAK
* = 9" MAXIMUM
6" MINIMUM
4/S512
4/S512
4/S512
SHTG

TYP SHTG TYP

T-CORNER INTERSECTION CORNER T-CORNER
(2) SIDED
CORNER
(2) SIDED
1/4" CLR BTWN SHTG
16d @ 16"CC
TYP
16d @ 16"CC
TYP

INDICATES CORRESPONDING NOTE FROM NAILING SCHEDULE ON
GENERAL NOTES SHEET. THIS IS THE MINIMUM REQUIRED NAILING, SHEAR WALL SCHEDULE NAILING SUPERCEDES THIS DETAIL.

INDICATES CORRESPONDING NAILING FROM SHEAR WALL SCHEDULE .

NOTES:
2/S511
TYP
#
X
C 10 13
NOTE:

HOLES SHALL BE DRILLED SO AS
NOT TO SPLINTER THE STUD.
w/3 MAX FOR SINGLE STUDS,
3W/5 MAX IF THE STUD IS

DOUBLED AND NOT MORE THAN

TWO SUCH SUCCESSIVE

DOUBLED STUDS ARE SO
BORED
W
MAX
5/8"
MAX
5/8"
MAX
W/4
W
MIN
W
MIN
NOTE:

HOLES SHALL BE DRILLED SO AS
NOT TO SPLINTER THE STUD.

NO NOTCHES IN MIDDLE
1/2 OF SPAN; WHERE

NOTCHES OCCUR,

PREDRILL CORNERS PER
W
MAX
5/8"
MAX
5/8"
MAX
W/4
MAX
6"
W
MIN
W
MIN
5 S511
1/2" RADIUS
NOTES:

1. PREDRILL CORNERS OF NOTCHES SO AS NOT TO OVER CUT.

2. NOTCHES IN THE BOTTOM OF JOISTS ALLOWED ONLY WHERE
SPECIFICALLY SHOWN ON DRAWINGS.

3. APPLIES TO SAWN LUMBER MEMBERS ONLY. NO NOTCHES

ALLOWED IN OTHER TYPES OF MEMBER UNLESS SPECIFICALLY
DETAILED IN THE DRAWINGS.

NO NOTCHES IN
MIDDLE 1/3 OF
SPAN
'D'
D/10
MAX
D/4

MAX MIN
2"
D/4 OR 2"

MAX, TYP
D/3
MIN
2xD MIN
5 S511
SIMPSON CS16

STRAP EA SIDE

OF TOP PLATE

AS REQD
FOR 'D' GREATER THAN 1/3 W
OR 2", PROVIDE STRAP AT EA
SIDE AS SHOWN. 2W/3 MAX.

HOLE FOR PIPE

CENTERED ON
MEMBER

PLAN - HOLE IN DOUBLE TOP PLATES NOTCH IN PLATES

ANCHOR BOLTS

AS REQD
FOR 'D' GREATER THAN 1/3 W,
PROVIDE ANCHOR BOLTS AT 9"CC
MAX AND 6"CC MIN AT EA SIDE
OF HOLE. PROVIDE MIN OF
(2) AB PER SILL PIECE.

PLAN - HOLE IN SILL PLATE
(6) 6D EA

END OF STRAP

NOTCH IN

MEMBERS

PREDRILL

CORNERS
PER
NOTE:

FOR MULTIPLE HOLES AND NOTCHES, MAINTAIN 18" CLEAR MIN AND EXTEND STRAP 12" PAST LAST HOLE OR NOTCH.

PROVIDE STRAP AT ALL
NOTCHES. MAX NOTCH
D = W/3.

DO NOT

OVERCUT
12"
MIN
W
D D
W D MAX 6"
12"
MIN
12"
MIN

TIE SPLICE LAP SPLICE
TO OCCUR AT 4'-0"CC

ACROSS BLDG AT RAFTER

OR JOIST SPLICE

RAFTER OR
JOIST

SUPPORT

NAILS PER
SCH

NUMBER OF

SPLICE NAILS

NAILS PER SCHEDULE

EA SIDE OF SPLICE
@ 4'-0"CC
2x SCAB x 2'-0" LONG LAP JOISTS
1'-0"

SPLICE AT RAFTER

OR JOIST
MEMBER
SIZE
2x4 & 2x6
2x8 & 2x10
2x12 & 2x14
(3) 16d
(4) 16d
(5) 16d

SIMPSON TB X-BRIDGING, SOLID BLOCKING,
OR 2x3 X-BRIDGING w/ (2) 8d TN EA END;
NAIL BOTT AFTER SHTG IS IN PLACE.

NOTE:

SIMILAR AT SOLID SAWN FRAMING. DETAIL OCCURS AT
8'-0"CC AT FLOORS AND 10'-0"CC AT ROOFS. OMIT AT
SOLID SAWN ROOF RAFTERS 8" DEEP AND SMALLER,
UNO.

ROOF OR FLOOR

SHEATHING

ROOF OR FLOOR

JOIST TYP

EDGE NAILING
(EN)

FIELD NAILING
(FN)
NOTES:

1. SEE PLAN FOR SHEATHING TYPE AND NAIL SIZE AND SPACING.

2. PROVIDE EN AT ALL SHEET EDGES, BEAMS, SHEAR WALLS, BLOCKING, AND MECHANICAL UNITS.

3. EN SHALL BE PER PLAN.

FN SHALL BE @ 12"CC. NAIL SIZE TO MATCH EN.

4. PROVIDE FLAT BLOCKING AND EN AT ALL UNSUPPORTED EDGES WHERE BLOCKING AND NAILING ARE INDICATED ON PLAN.

5. STAGGER SP JOINTS AS SHOWN. MINIMUM PANEL DIMENSION IN EITHER DIRECTION IS 24".

6. EN SHALL BE 10d NAILS, UNO.

7. FRAMING AT PANEL EDGES, SHALL BE 3x WHERE NAILS ARE
SPACED < 3"CC.

8. ALL 3x AND GREATER MATERIAL IN DIAPHRAGMS SHALL BE LESS THAN 19% MOISTURE CONTENT UNLESS SPECIFICALLY ALLOWED BY SEOR IN WRITING.
2x4 FLAT BLOCKING

WHERE OCCURS
(2) ROWS EN ALL

BEAMS AND SHEAR
WALLS

LAY SHEETS

PERPENDICULAR

TO FRAMING

UNO ON PLAN

FRAMING

PLAN BM WHERE OCCURS
OPEN
NOTE:

OPENINGS TO BE 4'-0" SQUARE MAXIMUM
SPACING NO CLOSER THAN 6'-0"CC

FLOOR OR ROOF

FRAMING
2x6 BLKG MIN,
TYP

SIMPSON
ST22, TYP
(2) 2x BLKG,

MATCH DEPTH

OF FRAMING

SP SHEATHING
JH OR L50

CLIP, TYP

RAFTERS

DBL JOISTS OR
JOISTS
4x6 BLKG CENTERED

BELOW CL OF CURB

CONNECTOR TYPICAL
SIMPSON LUS46
HANGER, TYP @ BLKG

TO BLKG, & BLKG

TO JOIST

DASH INDICATES EXTENT

OF MECH UNIT ABOVE

ROOF SHEATHING

PLACE MECH UNIT SO

ENDS DO NOT ALIGN

WITH JOISTS
NOTE:

ALL UNITS SHALL BE PLACED TO ELIMINATE JOISTS

WHICH MUST BE HEADED OFF FOR PLENUMS
PROVIDE WEB STFNR @

I-JOIST BLKG
16d @ 12"CC
STGRD
POST
BEAM

PARALLEL PERPENDICULAR
BEAM
(3)16d
A35
CLIP (A34
AT 2x4

INT WALL)
POST
END
POST
POST

SIDE FRONT

FULL HT STUD

EA SIDE
(3) 16d

EA STUD
2x BLKG

EA SIDE
TOP PL

OVER BM
(2) 10d TN EA FACE
w/ (20) 16d MIN
4'-0" MIN LAP

TOP OFPOST

SIMPSON CCQ

CONN INVERTED

ELEVATION

SIMPSON ECCQ

CONN INVERTED

SIMPSON CCQ CONN

SIMPSON ECCQ
CONN

GLULAM BM

WOOD COL ABOVE

WHERE OCCURS

ELEVATION SECTION

DAP CAP INTO

BM WHEREVER

REQD FOR SMOOTH

FINISHES TYP TOP

OR BOTTOM

WHERE GLULAM BM

BEARS OVER STUD WALL,

THE TOP PL SHALL BE

CONTINUOUS AT CONNECTOR
w/ POST BLW

WOOD POST

USE VERT SLOTTED HOLES

AT UPPER BOLT TYP
NOTE:

1. GLULAM BM SHOWN.

ENGINEERED LUMBER BM
SIMILAR.

WOOD POST

SLAB ON GRADE

CONC PAD FTG

PER PLAN CONT

FTG, SIM

SIMPSON CBSQ

CL POST AND

FOOTING
S

S TA TE O F CA L I FO R N I A

STRUCTURAL
R
ROFE P
ED

ER T IS
GE
SI N

ENGINEER
O AL
600 Q STREET, SUITE 200
SACRAMENTO, CA 95811
916 443 0303
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
WILLIAM B.

RADER
No. 3592
10/23/2024 5:26:14 PM c:\revit\2023-0123_DRY CREEK WWTP_rvt22_CENTRAL_Francisco_O_Rodriguez.rvt S511

TYPICAL FRAMING

AND NAILING

DETAILS

DCWWTP OPERATIONS

AND LAB BLDG
2100 15.01Author
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP

DETAIL NO SCALE
S511
1 TYPICAL NAILING
600SD011

DETAIL NO SCALE
S511
2 STRUCTURAL WALL

FRAMING
600SD001

DETAIL NO SCALE
S511
3 STRUCTURAL STUD

FRAMING CONDITIONS
600SD014

DETAIL NO SCALE
S511
4 HOLE OR NOTCH AT STUD
600SD013

DETAIL NO SCALE
S511
5 NOTCHES IN JOISTS &

HEADERS
600SD101

DETAIL NO SCALE
S511
6 HOLE OR NOTCH THRU
PLATES
600SD012

DETAIL NO SCALE
S511
7 JOIST & RAFTER SPLICE 600SD102

DETAIL NO SCALE
S511
8 CROSS BRIDGING 600SD100 DETAIL NO SCALE
S511
9 FLOOR & ROOF NAILING
620SD100

DETAIL NO SCALE
S511
10 OPENING IN FLOOR OR
ROOF
600SD104

DETAIL NO SCALE
S511
11 MECHANICAL UNIT

SUPPORT AT JOISTS
600SD103

DETAIL NO SCALE
S511
12 POST & BEAM

CONNECTION
600SD200

DETAIL NO SCALE
S511
13 BEAM AT POST w/ CAP
660SD001

DETAIL NO SCALE
S511
14 POST BASE
663SD001
NO. DATE DESCRIPTION
1 8/28/2024 PC Revisions

BID SET (PRELIMINARY)
1/S512
NOTES:

A. APA RATED SHEATHING GRADE.

B. ALL TOP PLATES SHALL BE (2) 2x NOMINAL UNO ON SECTIONS OR DETAILS. NAILING SHALL BE STAGGERED BETWEEN PLATES.

C. FOR SHEAR WALL NAILING AND FRAMING REQUIREMENTS, SEE .

D. PROVIDE 12" LONG ANCHOR BOLTS EXCEPT AT CONCRETE OVER METAL DECK WHERE A MINIMUM OF 5" EMBEDMENT IS REQUIRED.

PROVIDE 18" LONG ANCHOR BOLTS AT CURBS, TYP. SEE WOOD NOTES ON GENERAL NOTES SHEET FOR WASHER REQUIREMENTS.

E. SHEAR/SILL FASTENERS ONLY REQUIRED WHERE INDICATED ON SECTIONS AND DETAILS. WHERE INDICATED, FASTENERS SHALL BE SIMPSON SDS 1/4" DIAMETER SCREWS x 4-1/2" LONG AT 2x SILLS AND 6" LONG @ 3x SILLS.

F. SHEAR TRANSFER CLIPS ARE ONLY REQD WHERE INDICATED ON SECTIONS AND DETAILS. WHERE INDICATED, CLIPS SHALL BE SIMPSON LTP4 WITH 0.131x2 1/2" NAILS (INSTALLED WITH LONG DIMENSION HORIZONTAL)OR A35 CLIPS.

SHEAR WALL SCHEDULE
15/32" APA RATED SHEATHING
15/32" SHTG
(1) SIDE

STUDS & BLKG
@ PANEL
JOINTS
2x

SILL & TOP
PLATES

SHEATHING

EDGE NAILING
10d @ 3"CC

STAGGERED
10d @ 6"CC

ANCHOR BOLT

SPACING
5/8"Ø @ 48"CC

SHEAR/SILL

TRANSFER

FASTENERS
SDS @ 12"CC

SHEATHING

MATERIAL
15/32" SHTG
(1) SIDE
15/32" SHTG
(1) SIDE
15/32" SHTG
(1) SIDE
15/32" SHTG
(2) SIDES
15/32" SHTG
(2) SIDES
15/32" SHTG
(2) SIDES
2x
3x
3x
3x

ALL STUDS
3x

ALL STUDS
3x

ALL STUDS
2x
2x TYP UNO
3x @ FND
2x TYP UNO
3x @ FND
2x TYP UNO
3x @ FND
2x TYP UNO
3x @ SILL PL
2x TYP UNO
3x @ SILL PL
10d @ 4"CC
10d @ 2"CC

STAGGERED
10d @ 3"CC

STAGGERED
10d @ 2"CC

STAGGERED
10d @ 4"CC
5/8"Ø @ 32"CC
5/8"Ø @ 32"CC
5/8"Ø @ 24"CC
5/8"Ø @ 24"CC
5/8"Ø @ 16"CC
5/8"Ø @ 12"CC
SDS @ 8"CC
SDS @ 8"CC
SDS @ 6"CC
SDS @ 8"CC INTO RIM
& 8"CC INTO 2x BLKG
@ 12"CC
SHEAR

TRANSFER
CLIPS
@ 8"CC
@ 8"CC
@ 6"CC
@ 8"CC
(2) SIDES
@ 8"CC
(2) SIDES
@ 6"CC
(2) SIDES
2x

A B C D E F
Mk
1 2
3 4
5 6
7 SDS @ 8"CC INTO RIM
& 8"CC INTO 2x BLKG
SDS @ 6"CC INTO RIM
& 6"CC INTO 2x BLKG
NOTES:

1. HD ANCHORS DO NOT REPLACE SILL BOLTS AT FOUNDATION.

2. DOUBLE HOLDOWN CONDITION, INDICATED WITH (2).

HD ANCHOR AND POST SCHEDULE
HDU2
ROD

DIAMETER
5/8"

ALTERNATE
ANCHOR @

FOUNDATION

ALTERNATE
STRAP @
FLOOR

FRAMING
NONE
MSTC66
POST @

SINGLE HD

MINIMUM
(2) 2x
POST @

DOUBLE HD

MINIMUM
4x

HOLDOWN
SSTB20
(16 5/8" MIN EMBED)
MSTC78
Mk
2 4
5 8
11 14
HDU4
HDU5
HDU8
HDU11
HDU14
5/8"
5/8"
7/8"
1"
1"
SSTB20
(16 5/8" MIN EMBED)
SSTB24
(20 5/8" MIN EMBED)
SSTB34
(28 7/8" MIN EMBED)
NONE
NONE
NONE
NONE
NONE
(2) 2x
(2) 2x
4x
6x
6x
4x
4x
6x
8x
8x
NOTES:

1. SEE SCHEDULE FOR SHEATHING TYPE AND NAIL SIZE AND SPACING.

2. PROVIDE EN AT ALL SHEET EDGES, SILL PL, TOP PL, BLOCKING, AND POSTS. AT ALL SHTG SHOWN ON THE STRUCTURAL DRAWINGS, EN SHALL BE 6"CC MIN.

3. EN SHALL BE 10d NAILS, UNO.

4. FN SHALL BE @ 12"CC. NAIL SIZE TO MATCH EN.

5. MINIMUM PANEL DIMENSION IN EITHER DIRECTION IS 12".

6. SEE SHEAR WALL SCHEDULE FOR INFORMATION NOT NOTED.

7. EDGE NAILING INTO ALL PRESSURE TREATED LUMBER SHALL BE HOT DIPPED GALVANIZED. STAINLESS STEEL MAY BE USED AS AN OPTION.

8. SHEAR WALL LENGTH ON PLAN INDICATES MINIMUM, CONTINUOUS REQUIRED LENGTH. ACTUAL SHEAR WALL LENGTH SHALL EXTEND TO WALL ENDS, CORNERS, OR OPENINGS PER ARCH DWGS UNO.

9. COORDINATE SIDE OF WALL TO RECEIVE SHEATHING WITH ARCH DWGS.

NOTIFY ARCHITECT OF CONFLICTS PRIOR TO COMMENCING ANY WORK.

STAGGERED

NAILING DETAIL

EDGE NAILING
(EN) PER SCH

FIELD NAILING
(FN)

EN SHALL BE EQUALLY

DISTRIBUTED TO EA
TOP PL

HOLDOWN

PER PLAN

SILL PL PER SCH
w/ HDG EN TYP

DBL TOP PL
EDGE BLOCKING w/

EN PER SCHEDULE

INTERIOR EDGE

ELEVATION

POST WHERE OCCURS
3x

ANCHOR BOLT

PLACEMENT
2x4 OR 2x6
2x8 & LARGER
2 3/4" @ 2x6
1 3/4" @ 2x4
CL @ (2) SIDED
2 3/4" @ ONE
SIDED STUD;

PL WASHER

PER SCH
3/8"
1/2"
3/8"

SEE PLAN NOTES

SHEAR WALL EXTENT
FS FS

PANEL JT MIN
1/2" 3/4"
MIN
1/2"

HOLDOWN POST

ANCHOR BOLTS

PER SCH

PL WASHER

PER WOOD
NOTES
1/2" MAX EDGE

OF WASHER TO

EDGE OF SILL
D
C
C
B
C

SHEATHING

PER SCH A
OPEN
NOTE:

1. OPENINGS TO BE 4'-0" SQUARE MAXIMUM
SPACING NO CLOSER THAN 6'-0"CC

2. OPENINGS IN DESIGNATED SHEAR WALLS

NOT PERMITTED UNLESS SPECIFICALLY

DETAILED ON PLAN

STUD WALL FRAMING
2x4 BLKG MIN,
TYP

SIMPSON
ST22 TYP
(2) 2x SILL,

MATCH DEPTH

OF FRAMING UNO

WALL SHEATHING

WHERE OCCURS

KING STUDS, TRIMMERS, AND

HEADERS PER UNO

SIMPSON DRIVE SCREW SPLICE

SIMPSON DRIVE SCREW SPLICE
NOTE:

FASTENERS WILL OCCUR AT EA SIDE OF SPLICE TO ESTABLISH CONTINUITY OF DBL TOP PL.

DBL 2x TOP PL
2 1
(10) 1/4"Øx3" SDS

EQUALLY SPACED
SPLICE
4'-0" MIN
MIN
6"
MIN
6"
SPLICE
4'-0" MIN
DBL 2x TOP PL
(20) 1/4"Øx3" SDS

EQUALLY SPACED

CL SPLICE

CL SPLICE
(2) ROWS, STAGGERED, OF
(10) 1/4"Øx3" SDS EQUALLY
SPACED (20) SDS TOTAL
(2) ROWS, STAGGERED, OF
(5) 1/4"Øx3" SDS EQUALLY
SPACED (10) SDS TOTAL

ANCHOR ROD

SEE SCHEDULE

NO CURB
PL5/16x3x0'-3"
w/ DBL NUTS (SIMPSON
BP 7/8 IS ACCEPTABLE)

WITH CURB

SIMPSON CNW TYP

AS REQD FOR CURB

CONDITION

SIMPSON HDU TYPE

HOLDOWN SEE PLAN

FOR SIZE AND LOCATION

OVERSIZE HOLE FOR HD

BOLT AS REQD FOR NO

CONTACT WITH BOLT

SIMPSON SDS SCREWS
1/4"Ø x 2 1/2", INSTALL PER

MFR RECOMMENDATIONS
ADDL #4 EA SIDE

OF ANCHOR
12"
(2) ROWS SP EN

FULL HEIGHT

SILL PL

HD POST
PER

TYP TYP
@ DBL
TYP
3"CLR

TYP ALL AROUND
4" CLR MIN
B
S512
B
S512
5 S512
6 S512

SSTB ALT
3 1/4" MIN @ SSTB

ALTERNATIVE

VERIFY SLAB EDGE
w/ ARCH
2x STUD

KING/HD POST

PER TYP
PLAN
2x TRIMMER

T-CORNER AT DOOR
EN
EN
2x STUD
MIN
EN

AT WINDOW

SILL BOLTS

PER SCH TYP

AT CORNER
EN TYP

SIMPSON HDU

PER TYP

EN AT HD

POST TYP

EN SHTG
16d@16"CC
2x TRIMMER
MIN
3"
MIN
3"
MIN
3"
MIN
3"
2" @ HDU11
1 1/2"TYP
B
S512
4 S512
NOTE: FOR DOUBLE SIDED

SHEAR SEE
SIM.
6/S512
1" CLR
1" CLR
1" CLR
1" CLR

SHEAR TRANSFER

SCHEDULE

AT T-CORNER

SIMPSON HDU
PER
PLAN

TRIMMER(S)
PER SCH 3x MIN
@ DBL SIDED
EN

AT DOOR AT WINDOW AT CORNER
EN @

HD POST

KING/HD POST

PER TYP

SIMPSON CNW

TYP AS REQD

FOR OFFSET

CONDITION

HD POST

AT CONTRACTORS
OPTION: MAY USE

THIS DETAIL AT
WINDOW COND.
1/4"Ø x 6" SDS
SCREWS @ 4"CC
(30 MIN)
2x @ SINGLE SIDED EN
3x @ DBL SIDED EN

HD POST
CLR
1"
CLR
1"
1" CLR
MIN
3"
MIN
3"
CLR
1"
Mk
TYP
3" MIN
EN TYP
EN
EN
TYP
EN
TYP

SILL BOLTS
TYP
EN
EN
TYP
2x. OMIT AT SINGLE SIDED

EN & FASTEN HD DIRECT

TO POST
EN TYP
SHEAR

TRANSFER PER
SCH @ 2xTYP
SHEAR

TRANSFER

PER SCH

SHEAR TRANSFER
PER SCH @ 2x, TYP
SHTG
(2) 11
(2) 14
2x. OMIT AT SINGLE

SIDED EN & FASTEN

HD DIRECT TO POST

EN, TYP
2x. OMIT AT SINGLE

SIDED EN & FASTEN

HD DIRECT TO POST
SHEAR

TRANSFER PER
SCHED. PROVIDE
(2) ROWS @ 3x
4x
SHTG

HD POST
(2) 2
(2) 4
(2) 5
(2) 8
NUMBER OF 1/4"Ø x 6"

SDS SCREWS
(EQ SPACED, TYP)
(5)
(7)
(9)
(14)
(19)
(29)
4 S512
B
S512
GLB; DRILL 1 1/4"Ø MAX HOLE

TO PASS HOLDOWN BOLT

DOUBLE TOP PL

PER SECTIONS

TO DBL PL EA SIDE OF BM

SIMPSON HDU HOLDOWNS
T&B (4x MIN STUD)

BLOCKING POST,

MATCH SIZE OF

POST BELOW, TYP
2x PL UNO

FLOOR SHTG

JOIST BLKG
OR RIM; I-JOIST

CONDITION SIM
(2) 2x PL,

TYP UNO
A36 THRD ROD PER
CONTRACTOR'S OPTION:

IN LIEU OF HDU USE

SIIMPSON STRAP

ALTERNATE PER
INSTALL ON 4x

MIN STUD
ABOVE & BLW; ALTERNATE
NOT PERMITTED @ DBL HDU
EQUAL
EQUAL

STRAP ALTERNATE
24" MAX FOR
B
S512

POST PER
4x MIN
B
S512

POST PER
4x MIN
NOTE:

DOUBLE HOLDOWN, INDICATED w/
(2), PER SIM.

B
S512
B
S512
6/S512
1/S512

POST WHERE OCCURS
PROVIDE 2x FLAT BLKG WHERE SHTG EDGE
ALIGNS w/ TOP OF HEADER WITHIN ±3/4".

CMSTC16 STRAP OVER SHTG

TOP & BOTTOM OF OPNGS
AS SHOWN; PROVIDE (2)
ROWS 10d NAILS @ SPCG TO

MATCH SHEAR WALL EN (OR
EQUIVALENT). WHERE WALL

SHTG OCCURS BOTH SIDES

OF WALL, STRAPS SHALL
OCCUR @ BOTH SIDES
OMIT EDGE NAILING @ SHTG

WHERE STRAPS OCCUR TYP
PROVIDE EN @ ALL

TRIMMERS AND KING
STUDS @ OPNG TYP

OPNGS IN WALL (FOR LIGHTING ETC) ARE
NOT ALLOWED @ BLKG / STRAP LOCATIONS;
COORD w/ SEOR IF ANY ARE ANTICIPATED
HOLDOWN/ POST @

ENDS OF SHEAR

WALL LINE PER PLAN
TYP

DBL TOP PLATE

BLKG FOR SHTG EDGE
4x FLAT BLKG FOR FORCE

TRANSFER

BOTTOM PLATE
NOTES:

1. FOR ADDL WALL FRAMING INFO, SEE .

2. FOR ADDL SHEAR WALL NAILING INFO, SEE .
4x FLAT BLKG FOR FORCE

TRANSFER

STRAPPED WALL COND ONLY
AS DESIGNATED BY Mk
s
TERMINATE STRAP @

PL HOLDOWN POST TYP
16d STGRD @ SPCG TO

MATCH SHEAR WALL EN

OPEN OPEN
OPEN
2/S511
S

S TA TE O F CA L I FO R N I A

STRUCTURAL
R
ROFE P
ED

ER T IS
GE
SI N

ENGINEER
O AL
600 Q STREET, SUITE 200
SACRAMENTO, CA 95811
916 443 0303
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
WILLIAM B.

RADER
No. 3592
10/23/2024 5:26:16 PM c:\revit\2023-0123_DRY CREEK WWTP_rvt22_CENTRAL_Francisco_O_Rodriguez.rvt S512

TYPICAL SHEAR

WALL AND

HOLDOWN DETAIL

DCWWTP OPERATIONS

AND LAB BLDG
2100 15.01Author
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
S512
A
610SD001
S512
B
610SD200

DETAIL NO SCALE
S512
1 SHEAR WALL NAILING
610SD025

DETAIL NO SCALE
S512
2 OPENING IN WALL

SHEATHING
610SD030

DETAIL NO SCALE
S512
3 TOP PLATE SDS SPLICE
620SD200

DETAIL NO SCALE
S512
4 HOLDOWN AT

FOUNDATION
610SD201

DETAIL NO SCALE
S512
5 HOLDOWN PLACEMENT

AT FOUNDATION
610SD205

DETAIL NO SCALE
S512
6 DOUBLE HOLDOWN

PLACEMENT AT FDN
610SD206

DETAIL NO SCALE
S512
7 TOP PLATE HOLDOWN AT
BEAM
620SD232

DETAIL NO SCALE
S512
8 HOLDOWN AT FLOOR
610SD301

DETAIL NO SCALE
S512
9 STRAPPED SHEAR WALL

FRAMING
610SD026
NO. DATE DESCRIPTION

BID SET (PRELIMINARY)
NOTE:

ALL STUDS SHALL BE DF #2 OR BETTER.

NON-BEARING INTERIOR STUD

MAX HEIGHT SCHEDULE
14'-0"
20'-0"
15'-6"
22'-0"
12'-4"
18'-6"
2x4
2x6
@ 12"CC @ 16"CC @ 24"CC

SPACING STUD SIZE

NON-BEARING INTERIOR HEADER

AND JAMB FRAMING SCHEDULE
1 2
3 4

OPENING
TYPE
1'-4" TO 4'-8"
4'-9" TO 9'-10"
9'-11" TO 14'-4"
14'-5" TO 18'-0"
STUD WIDTH x 6" D
STUD WIDTH x 8" D
STUD WIDTH x 10" D
STUD WIDTH x 12" D
2x FLAT
2x FLAT
2x FLAT
(3) 2x FLAT
2x
2x
(2) 2x
(3) 2x
2x
2x
(2) 2x
(2) 2x
'W'

WIDTH HEADER SIZE SILL SIZE JAMB STUDS

TRIMMER
STUDS
OPEN

TYP DUCT
OPNG

HEADER, TYP
OPEN
SILL

CONDITION WHERE OPENING

OCCURS AT DOOR/WINDOW

JAMB STUDS

JAMB STUDS AS FOR

WINDOW OPNG FULL HT
OPEN
OPEN

SILL AND HDR

FULL HT JAMB

STUDS TYP

WALL STUD TYP

INFILL STUD

FLOOR OR ROOF FRAMING
(3) 16d END

NAILS TYP

TRIMMER

STUDS TYP
2x TOP PL TYP
2x SILL PL TYP
A35 CLIP HDR TO JAMB

AT DUCT OPNGS TYP

STITCH NAIL MULTIPLE

JAMB/TRIMMER STUDS
TOGETHER w/ 16d @
24"CC TYP
'W'

MAX HEIGHT

TYP WINDOW
9" MAX 'W'

TYP DOOR
'W' 9" MAX
A/S513
B/S513
NOTES:

1. FOR FRAMING MEMBERS AT OPENINGS, SEE .

2. FOR WALL STUD SIZE & MAX HEIGHT, SEE .
'W'
@ MULTIPLE OPNGS; USE

COMBINED OPNG WIDTH

FOR SIZING OF JAMB STUDS

BTWN OPNGS
630SD011
630SD016
OPEN

HEADER TYP
OPEN
SILL

JAMB STUDS AS FOR

WINDOW OPNG FULL HT

FULL HT JAMB
STUDS

WALL STUD TYP

FLOOR OR ROOF FRAMING

DIAGONAL KICKERS
(3) 16d EN TYP

TRIMMER
STUDS
2x SILL PL TYP
2x TOP PL

STITCH NAIL MULTIPLE

JAMB/TRIMMER STUDS
TOGETHER w/ 16d @
24"CC TYP

PROVIDE
BOLTS @
CURB

CONDITION
A/S513
B/S513
9" MAX

TYP DOOR
'W' 9" MAX

TYP WINDOW
'W'

MAX HEIGHT
NOTES:

1. FOR FRAMING MEMBERS AT OPENINGS, SEE .

2. FOR WALL STUD SIZE & MAX HEIGHT, SEE .
630SD011
630SD016

TYP PLATE

TYP STUD

TYP STUD

TYP STUD TO PLATE

TYP CORNER

TOP OR BOTTOM

PLATE OR SILL

TYP STUD

TYP PLATE

TYP INTERSECTION

TYP STUD
TYP
STUD
TYP
STUD
TYP
HDR
(2) 10d TN

EA SIDE

TYP STUD TO HEADER
16d @ 24"CC
16d @ 24"CC
(2) 16d END NAIL
16d @ 24"CC
16d @ 24"CC

PARALLEL

TO JOISTS

PERPENDICULAR

TO JOISTS

SP, TYP
2x BLKG @ 48"CC w/
(2) 16d EA END
2x4 FLAT BLKG
@ 48"CC
2x4 FLAT @ 48"CC
2x4 CONT w/ 16d
EA BLK
2x PL
A35 CLIP @ 6'-0"CC
EA SIDE; DO NOT

NAIL TO TOP PL

BLKG EA
SIDE
2x BLKG @ 48"CC
MAX w/ (3) 16d EA

BLK TO TOP PL
2x PL
NOTES:

1. AT CONTRACTORS OPTION USE DTC CLIPS @ 48"CC IN LIEU OF SDPW SCREWS AT ROOF FRAMING ONLY.

2. FOR WALLS > 10' USE (2) SIMPSON SDPW SCREWS @ 48" CC. AT CONTRACTOR'S OPTION USE (2) DTC CLIPS AT 48"CC AT ROOF FRAMING ONLY.
2x4 SIDE BLKS @ 48"CC
w/ (2) 10d TN; DO NOT

NAIL TO CENTER BLK
TYP
1/4" CLR
1/4" CLR
1 / 4 "
CLR
1 / 4 "
CLR
1 / 4 "
CLR
16d @ EA JOIST
(16"CC MAX)
SIMPSON DTC ALTERNATE @

ROOF ONLY (SHOWN DASHED),
TYP. SEE NOTES FOR ADD'L
INFO

SIMPSON SDPW
@ 48"CC, TYP

TOP CONNECTION AT ROOF OR FLOOR TOP CONNECTION

AT BEAM
2x4 DIAGONAL BRACES
@ 4'-0"CC; ALTERNATE EA

SIDE WHERE POSSIBLE &
WITHIN 12" OF END OF
PLATE
A35 CLIP
@ 48"CC

INTERIOR WALL
1 1

CEILING LINE

PARALLEL

PERPENDICULAR

KICKER MAY BE
SKEWED ±5° AS

REQUIRED FOR

OBSTRUCTIONS

OR JOIST LAYOUT
TOP PL
(±5°)

INTERIOR WALL

TYPICAL
SLOPE
UNO
TOP PL

JOIST TYP
A35 CLIP AT EA
BRACE
2x6 MIN BLKG w/ EN @ EA

DIAGONAL BRACE

WHERE I-JOIST OCCURS

NOTCH BLKG SNUG

WHERE TOP PLATE SPLICES OCCUR, PROVIDE
KICKER WITHIN 12" OF SPLICE ON EA SIDE MAX 1"
3 1
3 WHERE BRACE
LENGTH IS BTWN 6'-1"
AND 14'-0" PROVIDE
DBL 2x4 w/ 16d @ 12"CC
STITCH NAILING IN "T"
SHAPE THUS:
3 3
SHEATHING w/

EN OR FN

MAX HEIGHT OF

PARTITION WALL
10'-0"
14'-0"
18'-6"

FASTENER SCHEDULE
1 2
3 4
2 3
4 6
3 3
4 5
16d END
NAILS
10d END
NAILS
#10 WOOD
SCREWS
2 AT CURB AT CURB TYPICAL
1/2"Ø BOLT w/
MIN 4" EMBED
@ 48"CC
SHOT PINS @ 24"CC

PER GENERAL NOTES

DEPRESSED

SLAB PER
* WHERE 'Y' IS GREATER THAN 1 1/2",
USE 1/2"Ø POST-INSTALLED ANCHOR
(3" EMBED) @ 48"CC IN LIEU OF SHOT
PINS.
#4 MIN
CONT
EMBED

DEPRESSION WHERE
OCCURS
CJ
AT FC
WHERE
OCCURS 1/2"Ø EPOXY ANCHOR
(3" EMBED) @ 48"CC

CURB POURED MONOLITHIC

SEPARATELY
'Y''Y'
* 'Y'
3" MIN
MAX
6"
2x PTDF SILL PL
2x PTDF SILL PL

CONC CURB
PER
2x PTDF SILL PL
CL PIN & SILL PL;

OFFSET PIN UP TO
1/2" TO MEET EDGE

DISTANCE

WHERE OCCURS
2 1/4" MIN @ FC
@ DEPRESSION

WHERE OCCURS

T-SHAPE WHERE REQD

PER SCHED TYP

PARALLEL TO

SUPPORT MEMBERS

PERPENDICULAR TO

SUPPORT MEMBERS
LEDGER w/ (2) 16d @ 16"CC @ STUD
WALL OR 5/8"⌀ AB @ 48"CC @

CMU/CONC WALL
H
H
H
H

VVVVVVV
B
B
B
B
B
B
B B
V
B
H
24" LONG
SPLICE BLKG w/
(4) 16d EA STUD

CLG FINISH PER

ARCH, TYP
BLKG
WALL
WALL
(4) 16d TYP @ ALL

CONTACT POINTS
1 1 MIN

WHERE I-JOIST OCCURS
PROVIDE WEB FILLER PER NOTCH BLKG AS REQD @

I-JOIST CONDITION
6" MAX
8 S513

CL SPLICE
BLOCKING 2x8 MIN FASTEN TO FRAMING

PER NAILING SCHEDULE ON SHEET
LEDGER
A35 CLIP OR U HGR @ LEDGER TYP
SOFFIT FRAMING SCHEDULE NOTES:

1. BRACE REQUIRED IN ALL VERTICAL OFFSETS. ALTERNATE
DIRECTION OF BRACE WHERE POSSIBLE.

2. SCHEDULE BASED ON: - 2x4 DF #2 MEMBERS UNO
- 13.0 PSF DL + 10 PSF LL
- MAX DL DEFLECTION = L/360
- * 2x6 DF #2
- ** REQUIRES DBL 2x4 w/ 16d @
12"CC STITCH NAILING IN 'T'
SHAPE THUS:

MAX MEMBER

SPACING

MAX ALLOW

AREA SUPP

MAX LENGTH

OF MEMBER
H
2'-0"
16 FT2
8'-0"
10'-0"*
V
2'-0"
18 FT2
8'-0"
B
8'-0"
64 FT2
6'-1" TO 14'-0" DBL
2x4 'T' SHAPE
BRACE**
<6'-0"
20 FT2 *
SHTG

FRAMING PER PLAN
2x4 HGR @ 48"CC

EA WAY STAGGER

TO LOAD ADJACENT
JOISTS
2x4 CEILING JOIST
@ 48"CC w/ (4) 16d

EA VERT
2x4 HGR @
48"CC EA WAY
w/ (3) 16d EA END
2x6 BLKG w/
JB26 HGR
EA END
2x4 FILLER
BLK w/ (6) 8d

CINCH NAILED
TO WEB
(4) 16d
TYP
2x6 LEDGER w/
(3) 16d EA STUD

SIMPSON LUS

SP WHERE

OCCURS, CONT

UNDER LEDGER

STUD WALL
2x4 LEDGER w/
(2) 16d EA STUD
2x4 STRIPPING @ 16"CC w/
(2) 16d (ONE SLANT) EA CONTACT
NOTE:

FOR LEDGER @ CMU OR CONCRETE WALL SEE 7/S513 . 630SD103

PARTIAL HEIGHT WOOD WALLS

CEILING JOIST SCHEDULE

MASONRY OR CONCRETE WALLS FULL HEIGHT WOOD WALLS
5/8"Ø @ 2'-8"CC
5/8"Ø @ 4'-0"CC
(3) 16d / CONTACT
(2) 16d / CONTACT

LEDGER BOLTING
5/8"Ø @ 4'-0"CC

LEDGER NAILING
(2) 16d / CONTACT
2x RIM JOIST TO MATCH JOIST
DEPTH; NAIL TO JOIST PER
'LEDGER NAILING' @ SCHEDULE
USE 2x BLKG WHERE JOISTS

CONTINUE

TOP PL PER

CLG JOIST PER

SCHEDULE OR BLKG
@ 4'-0"CC

JOISTS CONTINUE

WHERE OCCURS
2x STUDS
@ 16"CC

JOISTS CONTINUE

WHERE OCCURS
2x FULL DEPTH BLKG
@ 12'-0"CC AND EA
END; NAIL 1x4 TO
BLKG w/ (4) 8d TYP

CEILING JOIST

PER SCHEDULE
2x8 @ 16"CC
2x6 @ 16"CC
2x4 @ 16"CC
14'-1" TO 18'-0"
7'-7" TO 14'-0"
UP TO 7'-6"

SIZE & SPACINGMAXIMUM SPAN

CLG JOISTS PER SCHEDULE
OR BLKG @ 4'-0"CC w/

LUS HGR
2x LEDGER TO MATCH

JOIST DEPTH
2x STUDS
LUS HGR @ 16"CC
1x4 STRIPPING @ 6'-0"CC
w/ (2) 8d EA CONTACT TYP
2x LEDGER TO MATCH JOISTS w/

ANCHOR BOLTS PER SCHEDULE
2 S513
S

S TA TE O F CA L I FO R N I A

STRUCTURAL
R
ROFE P
ED

ER T IS
GE
SI N

ENGINEER
O AL
600 Q STREET, SUITE 200
SACRAMENTO, CA 95811
916 443 0303
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
WILLIAM B.

RADER
No. 3592
10/23/2024 5:26:17 PM c:\revit\2023-0123_DRY CREEK WWTP_rvt22_CENTRAL_Francisco_O_Rodriguez.rvt S513

INTERIOR TYPICAL

NON-STRUCTURAL

DETAILS

DCWWTP OPERATIONS

AND LAB BLDG
2100 15.01Author
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP
S513
A
630SD011
S513
B
630SD016

DETAIL NO SCALE
S513
1 FULL HT INTERIOR WOOD

STUD WALL ELEVATION
630SD001

DETAIL NO SCALE
S513
2 PARTIAL HEIGHT

INTERIOR WALL FRAMING
630SD006

DETAIL NO SCALE
S513
3 NON-STRUCTURAL

FRAMING CONDITIONS
630SD030

DETAIL NO SCALE
S513
4 INTERIOR NON-BEARING

PARTITION AT TOP PLATE
630SD022

DETAIL NO SCALE
S513
5 INTERIOR PARTIAL

HEIGHT WALL BRACING
630SD023

DETAIL NO SCALE
S513
6 INTERIOR NON-BEARING

PARTITION AT SILL PLATE
630SD021

DETAIL NO SCALE
S513
7 SOFFIT FRAMING 630SD103

DETAIL NO SCALE
S513
8 SUSPENDED FRAMING
630SD100

DETAIL NO SCALE
S513
9 CEILING FRAMING
630SD102
NO. DATE DESCRIPTION

BID SET (PRELIMINARY)

I-JOIST
640SN001
FLAT ROOF DESIGN LOAD 16 PSF DL 20 PSF LL
SLOPPED ROOF DESIGN LOAD 17 PSF DL 20 PSF LL
NET WIND UPLIFT LOAD (0.6D+0.6W) FOR ZONE 1' -2 PSF
NET WIND UPLIFT LOAD (0.6D+0.6W) FOR ZONE 1 -6 PSF
NET WIND UPLIFT LOAD (0.6D+0.6W) FOR ZONE 2 & 3 -10 PSF WIND LOAD ZONES DEFINED IN ASCE 7-16 FIG 30.3
DISCONTINUITY DISTANCE 'A' = 8.4 FT.

1. I-JOISTS AS INDICATED ON DRAWINGS ARE I-LEVEL (OR RED-BUILT) DESIGNATIONS AND ARE FOR REFERENCE TO INDICATE REQUIRED DEPTH, SPACING AND CAPACITY ONLY. SUBMIT

ALLOWABLE LOAD TABLES AND ICC-ESR FOR EQUIVALENT I-JOIST AND HARDWARE REVIEW BY DIRECT COMPARISON. FOR MINIMUM MATERIAL PROPERTIES AT NORMAL DURATION SEE TABLE BELOW.

2. CHORD MATERIAL SHALL BE LAMINATED VENEER LUMBER (LVL) OR MACHINE STRESS RATED LUMBER WITH A MINIMUM SPECIFIC GRAVITY OF 0.50.

3. WEB MATERIAL SHALL BE OSB.

4. DESIGN AND FABRICATION SHALL CONFORM TO THE MANUFACTURERS ICC-ESR.

5. ALLOWABLE STRESS INCREASE FOR LOAD DURATION SHALL BE:

WIND/SEISMIC - 60% ROOF - 25% SNOW - 15% FLOOR - 0%

6. I-JOIST SHOP DRAWINGS AND CALCULATIONS SHALL BE SUBMITTED TO THE ARCHITECT AND/OR STRUCTURAL ENGINEER FOR REVIEW PRIOR TO FABRICATION. DRAWINGS SHALL BE "STAND ALONE" WITH NO REFERENCES TO STRUCTURAL PLANS OR DETAILS. DETAILING FOR INSTALLATION SHALL BE COMPLETE. DUPLICATION (I.E. PHOTOCOPYING) OF DESIGN DRAWINGS IS NOT ACCEPTABLE.

7. I-JOIST SHOP DRAWINGS SHALL DETAIL THE REQUIRED BRIDGING AT ANY UNBRACED CHORD IN COMPRESSION UNDER ANY APPLICABLE LOAD COMBINATION. SPACING OF BRIDGING SHALL BE AS REQUIRED BY MANUFACTURER'S ICC REPORT OR ENGINEERING ANALYSIS.

8. MANUFACTURER TO PROVIDE LOCATIONS WHERE WEB STIFFENERS ARE REQUIRED (AT EACH

SIDE OF WEB) AS PART OF THE I-JOIST SHOP DRAWINGS

9. CALCULATIONS SHALL BE SIGNED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE IN WHICH THE PROJECT IS LOCATED.

10. I-JOIST DESIGNER SHALL INCORPORATE ONE 400# (150#DL, 250#LL NON-CONCURRENT) VERTICAL LOAD ON THE BOTTOM CHORD OF ALL JOISTS FROM ONE SPRINKLER LINE. JOIST MUST BE DESIGNED TO CARRY THE LOAD AT ANY POINT.

11. I-JOISTS SHALL BE DESIGNED FOR ALL CONCENTRATED LOADS SHOWN ON DRAWINGS IN ADDITION TO THE UNIFORM LOADINGS SHOWN ABOVE.

12. SEE FRAMING PLANS AND MECHANICAL PLANS FOR LOCATIONS AND WEIGHTS OF MECHANICAL UNITS. COORDINATE ADDITIONAL EQUIPMENT LOADS WITH THE MECHANICAL CONTRACTOR PRIOR TO FABRICATION.

13. FLOOR JOISTS SHALL BE DESIGNED FOR A MAXIMUM LIVE LOAD DEFLECTION OF L/360 AND TOTAL LOAD DEFLECTION OF L/240. ROOF JOISTS SHALL BE DESIGNED FOR A MAXIMUM LIVE LOAD DEFLECTION OF L/240 AND A MAXIMUM TOTAL LOAD DEFLECTION OF L/180. IF ROOF JOISTS SUPPORT PLASTER CEILINGS A MAXIMUM TOTAL LOAD DEFLECTION OF L/240 IS REQUIRED.

14. PROVIDE FULL HEIGHT BLOCKING AND/OR RIM JOIST AT ALL BOTTOM CHORD BEARING CONDITIONS AND WHERE NOTED ON DRAWINGS.

15. GENERAL CONTRACTOR TO PROVIDE TEMPORARY ERECTION BRACING AS REQUIRED BY MANUFACTURER'S ICC-ESR.

16. MANUFACTURER TO VERIFY AND GENERAL CONTRACTOR TO APPROVE ALL DIMENSIONS

REQUIRING COORDINATION BETWEEN STRUCTURAL DRAWINGS WITH ARCHITECTURAL DRAWINGS. ADDITIONALLY, GENERAL CONTRACTOR SHALL VERIFY SUPPORT DIMENSIONS AND WALL LAYOUT IN FIELD PRIOR TO FABRICATION.

17. MANUFACTURER TO COORDINATE I-JOIST LAYOUT WITH PLUMBING DRAWINGS. PROVIDE

ADDITIONAL I-JOIST AS REQUIRED TO MAINTAIN I-JOIST SPACING LIMITS EACH SIDE OF PIPE OR FIXTURE.

18. PROVIDE AN ADDITIONAL I-JOIST UNDER INTERIOR PARTITION WALLS THAT ARE PARALLEL TO THE I-JOISTS WHERE WALL LENGTH IS GREATER THAN 1/3 OF THE JOIST SPAN AND WHERE JOIST IS OFFSET UP TO WIDTH OF WALL.

19. WHERE DOUBLE I-JOISTS ARE REQUIRED OR INDICATED ON DESIGN DRAWINGS PROVIDE LOAD TRANSFER PER DOUBLE I-JOIST ATTACHMENT DETAIL .

20. FIRE SPRINKLER INSTALLER SHALL USE CONNECTORS WITH ICC APPROVAL.

21. CONTRACTOR TO PROVIDE BEVELED WOOD PLATES, BEAMS, NAILERS ETC. AT ALL SLOPED BEARING CONDITIONS 1/4:12 OR GREATER.

22. ALLOWABLE PENETRATIONS IN I-JOISTS SHALL BE COORDINATED WITH AND APPROVED BY IJOIST MANUFACTURER PRIOR TO CONSTRUCTION. ALLOWABLE PENETRATIONS IN I-JOISTS SHALL BE PER .

JOIST TYPE RESIST
MOMENT MIN EIx10^6
- 7/16"
DEPTH
"
FLANGE
"X"
FLANGE
GRADE

2.0DF
WEB
'#
-
-
-
-
"
"
"
"
"X"
"X"
"X"
"X"

2.0DF

2.0DF

2.0DF

2.0DF
7/16"
7/16"
7/16"
7/16"
'#
'#
'#
'#
RESIST
SHEAR
#
#
#
#
#
#IN2
#IN2
#IN2
#IN2
#IN2
4/S514
5/S514
4x6 BLKG
w/ LUS46

HGR TYP

BEARING

MECH UNIT OR OTHER

CONCENTRATED LOAD

NAILS TO

PENETRATE

OPPOSITE

STIFFENER

SNUG FIT

I-JOIST
NOTES:

1. WEB STIFFENERS TO BE FIELD INSTALLED AT ALL BEARING POINTS AND CONCENTRATED LOADS (MECH UNITS ETC) WHERE INDICATED ON THE SHOP DRAWINGS.

2. GAP MUST BE AT TOP AT ALL BEARING LOCATIONS AND AT BOTTOM AT CONCENTRATED LOADS.

BEARING

FLANGE SIZE STIFFENER/NAILS
5/8" SHTG w/ (2) ROWS 8d @ 4"CC

STGRD & CLINCHED

WEB STIFFENER SCHEDULE

FIELD INSTALLED

WEB STIFFENERS

PER SCH

NAILING

I-JOIST BLK
1 3/4

NAILING
3/4" SHTG w/ (2) ROWS 8d @ 4"CC

STGRD & CLINCHED
2 1/16
7/8" SHTG w/ (2) ROWS 8d @ 8"CC

STGRD EA SIDE
2 5/16
1" SHTG w/ (2) ROWS 8d @ 8"CC

STGRD EA SIDE
2 1/2
2x4 DF#2 w/ (2) ROWS 16d @ 8"CC

STGRD EA SIDE
3 1/2
2 5/16" MIN

AS REQD
GAP
GAP
1 1/2"
MAX
1 1/2"
MAX
GAP
1/8" MIN
2 3/4" MAX
A
A

SECTION A-A

PLAN AT NON-BRG COND PLAN AT BRG COND
2x4 BLKS
FIELD

INSTALLED

I-BLKG WEB

I-JOIST WEB

FIELD INSTALLED

WEB STIFFENERS
16d @ 6"CC
(3 MIN) TYP
2x4 BLK
FIELD

INSTALLED

SEE ARCH

FOR VENTING I-JOIST SP
2x4 BLKG TYP NAILING PER PLAN
DETAIL

I-JOIST WEB

I-BLKG WEB

LINE OF

SUPPORT BLW
8d @ 4"CC
TYP (4) LOCS
8d @ 4"CC

FLAT BLKG AT ALL

JOINTS WHERE

DESIGNATED

SP EDGE NAIL EA

SHEET TO BLKG

TYP WHERE OCCURS
SP

I-JOIST WEB
(2) 8d TOE NAILS

EA END TYP

JOIST EDGE
3/8" MIN

SP JOINT
3/8" MIN

SP EDGE

NAILING

SP NAILING

TO JOIST
SP
DF #2 FILLER PIECE;

THICKNESS AS REQD

FOR MIN OF SNUG FIT

BETWEEN FLANGES
16d @ 16"CC

STAGGERED

EA SIDE

DOUBLE I-JOIST

FILLER PIECE

WHERE JOISTS FRAME

INTO DOUBLE, PROVIDE
FILLER TOP AND BOTTOM;

SHOWN DASHED
16d @ 16"CC
16d @ 16"CC
MIN
5 1/2"
MAX
5/8" GAP

PARALLEL TO JOISTS

PERPENDICULAR
SP

I-JOIST BLKG
@ CLIP
2x4 FLAT BLKG
@ 48"CC TYP
(2) 8d TYP
SP
2x4 FLAT BLKG TYP

TO MATCH DTC

SPACING
NOTES:

1. AT CONTRACTOR'S OPTION USE SIMPSON DTC CLIPS @ 48"CC IN LIEU OF SDPW SCREWS AT ROOF FRAMING ONLY.

2. FOR WALLS > 10' USE (2) SIMPSON SDPW SCREWS @ 48" CC. AT CONTRACTOR'S OPTION USE (2) DTC CLIPS AT 48"CC AT ROOF FRAMING ONLY.

WALL ABOVE WHERE OCCURS,
PROVIDE I-JOIST BLKG @ 24"CC
TYP
1/4" CLR
1/4" CLR

SIMPSON SDPW
@ 48"CC, TYP
SIMPSON DTC ALTERNATE @

ROOF ONLY (SHOWN DASHED),
TYP. SEE NOTES FOR ADD'L
INFO
1 S514
(6) 16d END

NAILS TYP

I-JOIST

ISOLATOR WHERE
OCCURS, TYP; SEE MECH

PLANS FOR ROD AND

BOLT TYPES
4x6 BLKG AT MECH

SUPPORT, TYP

CENTER BOLT

IN BLOCK
4x6 BLKG

I-JOIST
ROD LOADS ≤ 60#
ROD LOADS ≤ 250#
4x6 BLKG
LUS46 HGR EA
END

FILLER PER
TYP
2 7/8" TOP OF

BOTT CHORD BOTT
OF BLK
1 S514

I-JOIST
2x4 BLKG,
TYP

STFNR BLK AS

SHOWN PER
(4) 10d TOE NAIL,
TYP
PLAN
NOTES:

1. THIS DETAIL APPLIES ONLY WHERE
SPECIFICALLY INDICATED.

2. FOR ADDITIONAL INFO NOT SHOWN
OR NOTED SEE .
1/8" SAW CUT

DO NOT CUT

BOTTOM FLANGE

DASH INDICATES I-JOIST

BLKG AND WEB STFNRS
@ NS & FS
C
1 L SLOT
3/4" FS
9/S514

NO FIELD CUT

ZONE PER MFR

PER MFR TYP

MIN DISTANCE

BTWN HOLES

PER MFR TYP

MIN DISTANCE

BTWN HOLES

MIN DISTANCE TO END

SUPPORT PER MFR

GROUPED HOLES ARE PERMITTED IF GROUP

PERIMETER MEETS THE REQUIREMENTS FOR
ROUND OR RECTANGULAR HOLES; VERIFY w/ MFR

MIN DISTANCE TO

INTERMEDIATE

SUPPORT PER MFR

NO FIELD CUT

ZONE PER MFR
NOTES:

1. DO NOT CUT, DRILL, OR NOTCH FLANGES.

2. DO NOT CUT HOLES LARGER THAN 1 1/2" IN CANTILEVER WITHOUT CONSULTING MFR.

3. SEE I-JOIST MANUFACTURER FOR ALLOWABLE HOLE SIZES AND MINIMUM DISTANCE BETWEEN HOLES AND BETWEEN HOLES AND NEAREST SUPPORT. ALLOWABLE HOLE SIZES AND MINIMUM DISTANCES MAY VARY BASED ON SUPPORT AND LOADING CONDITIONS.

4. MAINTAIN MINIMUM DISTANCE FROM BOTH SUPPORTS.

5. HOLES SHOULD BE LOCATED VERTICALLY IN THE WEB PER THE MFR TOLERANCES. LEAVE A MINIMUM OF 1/8" OF WEB AT TOP AND BOTTOM OF HOLE. DO NOT CUT FLANGES.

6. WHERE 1 1/2" KNOCKOUTS ARE PRESENT, CONFIRM WITH THE MFR THAT THEY DO NOT AFFECT HOLE PLACEMENT.

MAX ROUND HOLE

SIZE PER MFR TYP

MAX ROUND HOLE

SIZE PER MFR TYP

MAX RECTANGULAR

HOLE SIZE PER MFR TYP

MAX RECTANGULAR

HOLE SIZE PER MFR TYP
2x PL

STUD WALL
SP

BEVELED PL
2x4 x 1'-0" BLKG
w/ (6) 10d BACK

NAILS THRU WEB
SIMPSON LTS16
STRAP EA JOIST;
PROVIDE (6) 10d
NAILS INTO 2x4

BLKG AND TOP PL

I-JOIST BLKG AND STFNR

BLK NOT SHOWN FOR

CLARITY, SEE
EN
REQD
AS
1" MIN
2" MAX
(2) 16d EA SIDE

I-JOIST TO BEVELED PL
(3) 16d EA SIDE @ 2x10
STUDS

TOP PL NAILING
THRU 2x PL BLW

PER UNO
2 S514
2 S511

SLOT UPPER

BOLT HOLES
VERTICALLY 1 7/8''
BRG PL3/4

DAP BUCKET INTO BM

WHERE REQD FOR

SMOOTH FINISHES TYP

TOP OR BOTTOM
PL1/4x10x1'-4"

EA SIDE GLULAM
COLUMN

MATCH ROOF

SLOPE WHERE

REQUIRED

GLULAM BEAM
(2) 3/4"ØBOLTS

ELEVATION SECTION
PL1/4x10

EA SIDE

ELEVATION

END CONDITION CENTER CONDITION
3/8" 10"
4" 4" 2"
1 1/2"
1/2" 8" 1'-4"
1 1/2" 1 1/2"
3/8" 10"
4" 4" 2"
3/8"

BEAM WIDTH CLR
1/8" GREATER THAN
1/4
1/4
TYP
1/4

BOTT OF
BRG PL
3/4"Ø BOLTS

BOTT OFSIDE PL
S

S TA TE O F CA L I FO R N I A

STRUCTURAL
R
ROFE P
ED

ER T IS
GE
SI N

ENGINEER
O AL
600 Q STREET, SUITE 200
SACRAMENTO, CA 95811
916 443 0303
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
WILLIAM B.

RADER
No. 3592
10/23/2024 5:26:19 PM c:\revit\2023-0123_DRY CREEK WWTP_rvt22_CENTRAL_Francisco_O_Rodriguez.rvt S514

TYPICAL I-JOIST

DETAILS

DCWWTP OPERATIONS

AND LAB BLDG
2100 15.01Author
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP

DETAIL NO SCALE
S514
1 I-JOIST WEB STIFFENERS
640SD001

DETAIL NO SCALE
S514
2 I-JOIST BLOCKING
640SD002

DETAIL NO SCALE
S514
3 I-JOIST NAILING
640SD007

DETAIL NO SCALE
S514
4 DOUBLE I-JOIST

ATTACHMENT
640SD005

DETAIL NO SCALE
S514
5 INTERIOR NON-BEARING

PARTITION AT TOP PLATE
640SD003

DETAIL NO SCALE
S514
6 BLOCKING SUPPORT IN

I-JOIST
640SD020

DETAIL NO SCALE
S514
7 I-JOIST CONTINUITY
BREAK
640SD009

DETAIL NO SCALE
S514
8 I-JOIST ALLOWABLE
HOLES
640SD008

DETAIL NO SCALE
S514
9 I-JOIST TIE-DOWN
640SD006

DETAIL NO SCALE
S514
10 GLULAM BEAM OVER

STEEL COLUMN
665SD202
NO. DATE DESCRIPTION

BID SET (PRELIMINARY)

PRE-MANUFACTURED WOOD TRUSS NOTES
650SN001
TYP ROOF DESIGN LOADS UNO, SEE .

SLOPED TOP CHORD 11 PSF DL
20 PSF LL
NET WIND UPLIFT LOAD (0.6D+0.6W) FOR ZONE 1 -7 PSF WLNU NET WIND UPLIFT LOAD (0.6D+0.6W) FOR ZONE 2 -16 PSF WLNU NET WIND UPLIFT LOAD (0.6D+0.6W) FOR ZONE 3 -19 PSF WLNU WIND LOAD ZONES DEFINED IN ASCE 7-16 FIG 30.3
DISCONTINUITY DISTANCE 'A' = 5.6 FT
WIND WALL LOADS (0.6W) (BASED ON ZONE 5) -13 PSF WL
W

1. ALL MEMBERS SHALL BE 2x4 MIN UNO.

2. ALL TOP CHORD MEMBERS SHALL BE OF MATERIAL w/ A MINIMUM SPECIFIC GRAVITY OF 0.50.

3. PLATE MATERIAL SHALL BE ASTM A-446 GRADE A OR BETTER.

4. DESIGN AND FABRICATION SHALL CONFORM TO THE CODE AS DESIGNATED IN THE DESIGN CRITERIA NOTES AND ANSI/TPI 1-2014.

5. DESIGN AND CONSTRUCTION OF CONNECTIONS SHALL BE IN ACCORDANCE WITH PUBLISHED APPROVALS OF MANUFACTURER'S ICC-ESR. HEEL JOINT DESIGN SHALL CONSIDER THE EFFECTS OF ECCENTRIC LOADING IN ACCORDANCE WITH TRUSS PLATE INSTITUTE (TPI).

6. TRUSS DESIGNER SHALL OVERSIZE PLATES FOR CHORD MEMBERS TO ACCOUNT FOR WOOD DEFECTS LIKE KNOTS, KNOT HOLES AND GREATLY DISTORTED GRAINS. MAXIMUM ALLOWABLE DEFECT SIZE PER MEMBER SHALL BE 2 SQUARE INCHES. NO DEFECTS ALLOWED UNDER PLATES FOR WEB MEMBERS.

7. STRUCTURAL DESIGN OF BEAMS, POSTS & FOUNDATIONS SUPPORTING ROOF TRUSSES HAS BEEN BASED ON FRAMING CONFIGURATIONS SHOWN ON PLANS. DEVIATIONS TO THE FRAMING

CONFIGURATIONS SHOWN WILL REQUIRE ADDITIONAL DESIGN COORDINATION AND POTENTIAL REVISIONS TO FRAMING AND FOUNDATIONS. ANY REQUIRED REVISIONS TO THE STRUCTURAL

DRAWINGS WILL BE PREFORMED ON A TIME AND MATERIAL BASIS AND WILL BE CHARGED TO THE GENERAL CONTRACTOR.

8. ALL HARDWARE REQUIRED FOR CONNECTING TRUSSES (JACK TO HIP, HIP TO GIRDER OR GIRDER TO GIRDER, ETC.) SHALL BE DESIGNED, DETAILED AND PROVIDED BY TRUSS DESIGNER/MANUFACTURER.

9. TRUSS DESIGNER TO ACCOUNT FOR THE WEIGHT AND LATERAL RESTRAINT FORCES OF ALL EQUIPMENT IN THE DESIGN OF ALL TRUSSES WHICH SUPPORT SUCH EQUIPMENT. SEE OTHER DISCIPLINES DRAWINGS FOR WEIGHTS AND DETAILING. ADDITIONALLY, TRUSS DESIGNER

SHALL INCORPORATE WEIGHT AND SEISMIC RESTRAINT FORCES OF ALL PIPING AND CONDUIT IN TRUSS DESIGN. SEE OTHER DISCIPLINES DWGS FOR TYPE AND LOCATION.

10. TRUSS DESIGNER SHALL INCORPORATE ONE 400# (150#DL, 250#LL NON-CONCURRENT) VERTICAL LOAD ON THE BOTTOM CHORD OF ALL TRUSSES FROM ONE SPRINKLER LINE. TRUSS

MUST BE DESIGNED TO CARRY THE LOAD AT ANY POINT ALONG THE TOP AND BOTTOM CHORDS.

11. TRUSS DESIGNER SHALL INCORPORATE COLLECTOR LOADS FOR ALL COLLECTOR TRUSSES SHOWN ON PLANS. COLLECTOR LOADS ARE SHOWN @ 0.7E OR 0.6W (ASD FORCE LEVELS).

WHERE LOAD NOT INDICATED ON PLAN, COLLECTOR LOAD = 2500 LBS MIN. TRUSS MUST BE

DESIGNED TO RESIST FULL COLLECTOR LOAD APPLIED AXIALLY AT ANY POINT ALONG THE TOP

OR BOTTOM CHORD AND TO TRANSFER THE COLLECTOR LOAD THROUGH WEB MEMBERS AND

CONNECTIONS FROM TOP CHORD DOWN TO BOTTOM CHORD (APPLIED IN POUNDS PER FOOT) ALONG THE LENGTH OF THE TRUSS.

12. THE STRUCTURAL DRAWINGS GENERALLY INDICATE THE WIND UPLIFT CONNECTION DETAILING AT THE TRUSS SUPPORTS. TRUSS MANUFACTURER SHALL REVIEW THE STRUCTURAL

DRAWINGS FOR UPLIFT DESIGN AND SHALL MAKE A STATEMENT ON THE SHOP DRAWING SUBMITTAL STATING SUCH. ANY CONNECTIONS THAT ARE INCOMPATIBLE WITH THE TRUSS

SYSTEM SHALL BE BROUGHT TO THE ATTENTION OF THE STRUCTURAL ENGINEER FOR REVIEW AND INPUT DURING THE SHOP DRAWING SUBMITTAL PROCESS.

13. TRUSS MANUFACTURER SHALL PROVIDE DESIGNS THAT DO NOT EXCEED A BEARING STRESS OF 600 PSI AT THE REACTION POINTS. AT TRUSS MANUFACTURER'S OPTION, BEARING PLATES

OR OTHER CONNECTORS AS REQUIRED TO REDUCE BEARING STRESS AT SUPPORTING MEMBER TO 600 PSI MAX MAY BE DESIGNED, DETAILED, AND SUBMITTED FOR REVIEW TO THE ARCHITECT/STRUCTURAL ENGINEER.

14. ROOF JOISTS SHALL BE DESIGNED FOR A MAXIMUM TOTAL LOAD DEFLECTION OF L/180. IF ROOF JOISTS SUPPORT PLASTER CEILINGS A MAXIMUM TOTAL LOAD DEFLECTION OF L/240 IS REQUIRED.

15. TRUSS DESIGNER/MANUFACTURER SHALL CLEARLY DESIGNATE TRUSS MEMBER BRACING LOCATIONS IN THE SHOP DRAWINGS.

16. TRUSS MANUFACTURER TO VERIFY ALL DIMENSIONS SHOWN ON STRUCTURAL DRAWINGS WITH ARCHITECTURAL DRAWINGS AND IN FIELD WITH WALL LAYOUT PRIOR TO FABRICATION.

PROVIDE SHOP DRAWINGS WHICH SHALL INCLUDE PLAN DRAWING SHOWING TRUSS

LOCATIONS AND TRUSS PROFILES, WITH DIMENSIONS REVIEWED AND APPROVED BY GENERAL CONTRACTOR, PRIOR TO FABRICATION.

17. TRUSS LAYOUT AND PROFILE DRAWINGS, CALCULATIONS AND THE LATEST ICC APPROVED

TEST DATA FOR TRUSS METAL PLATE CONNECTORS SHALL BE SUBMITTED TO THE ARCHITECT

AND/OR ENGINEER FOR REVIEW AND SHALL ADDRESS ALL COMMENTS FROM THAT REVIEW PRIOR TO SUBMITTAL TO THE BUILDING DEPARTMENT.

18. TRUSS LAYOUT, PROFILE DRAWINGS AND CALCULATIONS FOR TRUSS DESIGNS AND ANY BEARING DETAILING PER NOTE 13 SHALL BE SIGNED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE IN WHICH THE PROJECT IS LOCATED. IT SHALL BE THE

RESPONSIBILITY OF THE MANUFACTURER TO OBTAIN BUILDING DEPARTMENT APPROVAL PRIOR TO FABRICATION.

19. BUILT UP GIRDER TRUSSES SHALL BE LAMINATED USING 1/2"Ø BOLTS AT 24"CC MAXIMUM THROUGH ALL MEMBERS (OR OTHER METHOD BY WRITTEN REQUEST).

20. GABLE END TRUSSES SHALL HAVE 2x VERTICALS AT 16"CC TYPICAL UNLESS NOTED OTHERWISE. WHERE GABLE END TRUSSES ARE REQUIRED TO SPAN OVER OPENINGS OR

TRANSFER COLLECTOR LOADS VERTICALS SHALL BE INFILLED AROUND TYPICAL WEB MEMBERS. TRUSS MANUFACTURER SHALL DESIGN, DETAIL AND PROVIDE INTERMEDIATE BRACING OF THE GABLE TRUSS WEBS AND VERTICALS AS REQUIRED TO RESIST OUT-OFPLANE WIND LOADS.

21. GENERAL CONTRACTOR TO DETERMINE AND PROVIDE TEMPORARY ERECTION BRACING AS REQUIRED.

22. FIRE SPRINKLER INSTALLER SHALL USE CONNECTORS WITH ICC APPROVAL. 3/S515
±WLNU
DL
LL
WLw
DLm
LEGEND:

DL = DEAD LOAD
LL = LIVE LOAD
WLNU = WIND NET UPLIFT LOAD
DLm = DEAD LOAD AT MECHANICAL UNIT, SEE PLAN FOR WEIGHT AND VERIFY LOCATIONS w/ MECH
WLw = WIND LOAD AT WALL (APPLY WALL LOAD TO GABLE TRUSS

VERTICAL AND WEB ELEMENTS)
WLw
NOTE:

SEE PLANS, SECTIONS AND DETAILS FOR ADDITIONAL LOADS.

RT-2
ARCH
SEE

INTERIOR SUPPORT

WHERE OCCURS

SEE PLAN
ARCH
SEE

SEE ARCH
NOTES:

1. SEE PRE-MANUFACTURED ROOF TRUSS NOTES FOR DESIGN REQUIREMENTS AND TYPICAL ROOF TRUSS LOADING.

2. SEE ARCH FOR TRUSS DIMENSIONS, SLOPES, OVERHANGS, ETC.

3. SEE PLANS FOR SUPPORT LOCATIONS.

T.O. DBL TOP PL

SEE PLAN

ROOF TRUSS
@ 24"CC, TYP

PRE-FAB BLKG PANEL BY TRUSS MFR TO BE

DESIGNED TO TRANSFER LATERAL LOAD FROM
ROOF TO WALL BELOW; PANEL DESIGN LOAD
SHALL BE 600 PLF MIN UNO; BEVEL TOP AS

REQD TO ACCOMODATE ROOF SLOPE
USE SIMPSON A35 CLIPS FROM BLKG TO
TRUSS VERT @ TOP & BOTTOM EA SIDE VARIES
(2) A35 FROM EA TRUSS BLKG

PANEL TO TOP PLATES TYP

UNO PER SHEARWALL
SCHEDULE DBL TOP PL; FOR SIZE

SPLICE REQD, SEE

SECTIONS AND DETAILS

COORD LOCATION OF
MECH DUCTWORK w/

LAYOUT OF TRUSS BLKG
WEBS
CONTRACTOR'S OPTION: USE
(2) LTP4 CLIPS IN LIEU OF (2)
A35 CLIPS FROM TRUSS BLKG
PANEL TO TOP PL. INSTALL

OVER SHTG

ELEVATION SECTION

ROOF SP
SP EN
CONTRACTOR'S OPTION:

PROVIDE LSL BLOCKING (UP TO 24"

DEEP) OR TRUSS BLOCKING PANEL

PER IN LIEU OF PRE-FAB
BLOCKING PANEL.
4/S515

EN ROOF SP

TRUSS BOTTOM
CHORD
TOP PL

ELEVATION SECTION
EN

WALL SP

PANEL SP
ROOF TRUSSES @
24"CC, TYP

TRUSS TOP
CHORD; SLOPE

WHERE OCCURS
2x4 MIN EA SIDE OF
TRUSS WEB w/ 16d
NOTES:

1. BLOCKING PANEL SP TO MATCH WALL SP THICKNESS & EDGE NAILING UNO. (1/2" SHEATHING w/ 10d @ 6"CC, MIN)

2. NAIL 2x4 BLKG TO TRUSS AND TOP PL w/ 16d, SPACING TO MATCH ROOF SP EN.

3. PROVIDE PREFABRICATED PANEL PER IN LIEU OF SHEATHED PANEL @ CONTRACTOR'S OPTION. PANEL BLOCKING OPTION IS NOT RECOMMENDED AT

POTENTIAL CONFLICTS WITH PANEL WEBS AND MECHANICAL OR PLUMBING ELEMENTS.

4. AT BLOCKING PANELS DIRECTLY BELOW A STRAP, PROVIDE 10d @ 3"CC BLOCKING PANEL EDGE NAILING AND 16d @ 3"CC BLOCKING TO TRUSS AND TOP PLATE NAILING MIN.
2x4 MIN T&B OF
TRUSS w/ 16d @ PL
5/S515
LSTA24 BENT 10d @ 4"CC (4) 16d
EN EN 3" @ 8'-0"CC C

SHTG TO

MATCH BLW

GABLE TRUSS PER
TRUSS NOTES;

COLLECTOR

TRUSS WHERE

REQD PER PLAN

SHEAR TRANSFER
CLIP
F

DBL TOP PL

SEE PLAN
ENC

SHTG PER PLAN
A34 CLIP
H2.5A CLIP
CONTRACTOR'S OPTION:

SUBSTITUTE PANEL BLOCKS PER

FOR BRACES
2x4 BRACE @ 48"CC & @ EA END
OF WALL; PROVIDE T SHAPE

WHERE REQD PER

ROOF TRUSS

PER PLAN
2x4 BLKG w/ A34

CLIP EA END
1 1
MAX

DBL TOP PL
NOTE:

SEE SHEAR WALL SCHEDULE ON SHEET FOR NAILI S512 NG AND MK 7 S513
4 S515
4'-0"
3'-0"
2x4 OUTRIGGERS
@ 24"CC
1 DBL TOP CHORDS
@ LOCATION OF

OUTRIGGERS
S

S TA TE
O F
CA
L
I

FO R N I A

STRUCTURAL
R
ROF
E
P

ED ER T IS GE
S
I
N

ENGINEER
O
AL
600 Q STREET, SUITE 200
SACRAMENTO, CA 95811
916 443 0303
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP
REVISIONS #

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
WILLIAM B.

RADER
No. 3592
10/23/2024 5:26:19 PM c:\revit\2023-0123_DRY CREEK WWTP_rvt22_CENTRAL_Francisco_O_Rodriguez.rvt S515

TYPICAL WOOD

TRUSS NOTES AND

DETAILS

DCWWTP OPERATIONS

AND LAB BLDG
2100 15.01Author
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP

DETAIL NO SCALE
S515 1

ROOF TRUSS LOADING

GABLE/MANSARD
650SD101

DETAIL NO SCALE
S515 3

TRUSS PROFILES
650SD100

DETAIL NO SCALE
S515 5

PREFABRICATED PANEL

BLOCKING
650SD020

DETAIL NO SCALE
S515 4

TRUSS BLOCKING PANEL
650SD010

DETAIL NO SCALE
S515 6

EXTERIOR WALL

TRUSS PARALLEL
650SD602
NO. DATE DESCRIPTION
1 8/28/2024 PC Revisions

BID SET (PRELIMINARY)
#4 AT 12"CC @ EA FACE
TYP HORIZ REINF;
REDUCE SPCG TO 16"CC WHERE NOMINAL
WALL LENGTH 'L' IS 4'-0" ≤ 'L' < 6'-0"

1. REFER TO CMU GENERAL NOTES ON SHEET FOR CONCRETE BLOCK UNITS, MORTAR AND GROUT REQUIREMENTS.

2. VERTICAL REINFORCING:

A. DOWELS WITH STANDARD 90° HOOKS INTO THE FOUNDATION SHALL MATCH AND LAP VERTICAL REINFORCING.

B. WHERE VERTICAL REINFORCING IS LOCATED AT EACH FACE, THE BARS DO NOT NEED TO BE

PLACED IN THE SAME CELL, BUT THE SPACING NOTED NEEDS TO BE MAINTAINED FOR EACH SIDE OF THE WALL.

3. HORIZONTAL REINFORCING:

A. INSTALL STD 180° HOOK AROUND VERTS AT WALL ENDS AND JOINTS IN ALL HORIZONTAL REINFORCING BARS.

B. WHERE THE VERTICAL BARS ARE CENTERED IN THE WALL, HORIZONTAL REINFORCING BARS

SHALL BE LOCATED ON ONE SIDE (OR BOTH SIDES) OF THE VERTICAL BARS, ALLOWING THE VERTICAL BARS TO BE CENTERED.

C. WHERE THE VERTICAL BARS ARE AT EACH FACE IN THE WALL, HORIZONTAL REINFORCING

BARS SHALL BE LOCATED TOWARD THE CENTER OF THE CELL, ALLOWING THE VERTICAL

BARS TO BE LOCATED BETWEEN THE HORIZONTAL REINFORCING AND THE NEAREST FACE OF THE WALL.

CMU WALL

REINFORCING - CENTERED
EQ EQ
EQ EQ
# AT "CC EACH FACE

TYPICAL VERTICAL REINFORCING

CMU WALL

REINFORCING - EACH FACE
EQ EQ ...

REINFORCING

COVER PER

CMU GENERAL
NOTES
#4 AT 16"CC

TYPICAL VERTICAL REINFORCING
#4 AT 16"CC @ EA FACE
TYP HORIZ REINF;
1 (2) 3/4"Ø BOLTS SLOT TOP HOLES
VERTICALLY 1 7/8"
PL1/4 EA SIDE OF

GLULAM BEAM
BRG PL

MATCH ROOF
SLOPE
NOTES:

1. SPLICE BEAMS AT CL OF COLUMN EXCEPT AT CANTILEVER CONDITION.

2. INCREASE WIDTH OF BEARING PLATE AS REQUIRED WHERE COLUMN IS WIDER THAN SUPPORTED BEAM.

HSS COL
+1/8"
BEAM
W IDTH
1'-2"
1 1/2" 1 1/2"
10"3/4"
4" 4" 2"
1/4
1/4
TYP

CL COL CL COL
CL BM
1 ELEVATION

HSS COL
PL1/4x4
(2) 2x6 PLATES

DETAIL IS

SYMMETRICAL

WHERE WALL

CONTINUES

END OF PL
1 1/2" 3" 3" 5 1/4"
3/16
3/4"Ø BOLTS

CARRIAGE BOLTS

ACCEPTABLE

PLAN VIEW A-A

DBL TOP
PLATES

WALL CONTINUOUS

OR PERPENDICULAR

WHERE OCCURS
AA
S

S TA TE
O F
CA
L
I

FO R N I A

STRUCTURAL
R
ROF
E
P

ED ER T IS GE
S
I
N

ENGINEER
O
AL
600 Q STREET, SUITE 200
SACRAMENTO, CA 95811
916 443 0303
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP
REVISIONS #

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
WILLIAM B.

RADER
No. 3592
10/23/2024 5:26:19 PM c:\revit\2023-0123_DRY CREEK WWTP_rvt22_CENTRAL_Francisco_O_Rodriguez.rvt S516

MISC DETAILS

DCWWTP OPERATIONS

AND LAB BLDG
2100 15.01Author
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP

DETAIL NO SCALE
S516 1
CMU WALL REINFORCING 411SD003

DETAIL NO SCALE
S516 2

BM OVER STL COL
665SD200
NO. DATE DESCRIPTION
1 8/28/2024 PC Revisions
2 10/23/2024 PC Revisions 2

DETAIL NO SCALE
S516 4

TOP PLATE AT COLUMN
665SD003
2 BID SET (PRELIMINARY)
THE CALIFORNIA ENERGY CODE SECTION 10-103 REQUIRES ACCEPTANCE TESTING ON ALL NEWLY INSTALLED LIGHTING CONTROLS, MECHANICAL SYSTEMS,ENVELOPES, AND PROCESS EQUIPMENT AFTER INSTALLATION AND BEFOREPROJECT COMPLETION. AN ACCEPTANCE TEST IS A FUNCTIONAL PERFORMANCETEST TO HELP ENSURE THAT NEWLY INSTALLED EQUIPMENT IS OPERATING AND INCOMPLIANCE WITH THE ENERGY CODE.LIGHTING CONTROLS ACCEPTANCE TESTS MUST BE PERFORMED BY A CERTIFIEDLIGHTING CONTROLS ACCEPTANCE TEST TECHNICIAN (ATT).MECHANICAL SYSTEM ACCEPTANCE TESTS MUST BE PERFORMED BY A CERTIFIEDMECHANICAL ATT FOR PROJECTS SUBMITTED ON OR AFTER OCTOBER 1, 2021.

A LISTING OF CERTIFIED ATT CAN BE FOUND AT
HTTPS://WWW.ENERGY.CA.GOV/PROGRAMS-AND-TOPICS/PROGRAMS/ ACCEPTANCE-TEST-TECHNICIAN-CERTIFICATION-PROVIDER-PROGRAM/ACCEPTANCETHE ACCEPTANCE TESTING PROCEDURES MUST BE REPEATED, AND DEFICIENCIESMUST BE CORRECTED BY THE BUILDER OR INSTALLING CONTRACTOR UNTIL THECONSTRUCTION/INSTALLATION OF THE SPECIFIED SYSTEMS CONFORM AND PASSTHE REQUIRED ACCEPTANCE CRITERIA.PROJECT INSPECTORS WILL COLLECT THE FORMS TO CONFIRM THAT THEREQUIRED ACCEPTANCE TESTS HAVE BEEN COMPLETED.

ACCEPTANCE TESTING REQUIREMENT
-
F F

WITH MVDSHOE FITTINGWITH MVD
AIR
FLOW
FLOW
AIR

CONICAL FITTING
AIR
FLOW
FLOW
AIRAIR
FLOW
FLOW
AIR

CONICAL FITTING
SUPPLY DUCT RISE 11
13 24

SUPPLY DUCT DROP
25 RETURN OR EXHAUST AIR DROP
12 RETURN OR EXHAUST AIR RISE
12"∅
12x12
MVD
10"∅ 12"∅
14/10
24x12
16x1214x12
14x10
14/10 16x1224x1230x5 16x12
24x12 7/524x12 16x1230x5 7/5
12x12
24x1224x12
12x12
24x1224x12 24x12

SECTION ATEXHAUSTDUCT RISER

EXHAUST DUCT DROP
R

LINED DUCT
R=36

RETURN DUCT DROP

RETURNSECTION ATDUCT RISER
24x12

TRANSITIONAL TURN
=1.5
WR
12x12
=1
WR
24x12

DUCT RISERSUPPLYSECTION AT

SUPPLY DUCT DROP

TURNINGVANES
W
14x1016x12
10/1424x12
16x1214x10 10/14
24x12
MVD
48x124/36/8
38x1210x8
12x12
38x12
4/36/8 10x1212x1248x1212x12
24x1224x12
12x12
24x12
12x6
24x12
24x12

FLEXDUCT

CONTRACTING FLOW

CONCENTRIC ECCENTRIC
24x12 24x12 1 IN 2
MAX.
12x12 12x12MAX.1 IN 2
MVD
12x1212"∅

SQUARE TOROUND TRANSITION
24x1214/10
14x10
16x12

TRANSITIONALRADIUS ELBOW
14" TRANSITION
10"10"
14" TRANSITION

W/ TURNINGSQUARE ELBOW
16x12
14x12
14/1024x1212"∅ 10"∅

ELONGATED
12"∅ 10"∅
TEE
30x5
16x12
24x12
24x5 BELOW24x7 ABOVE

W/ TURNING VANESSQUARE ELBOW
24x7 ABOVE24x5 BELOW
24x12 RADIUS ELBOW

TRANSITIONAL
7/5 SPLIT
30x5

TRANSITION
16x12

VANE ANGLE
20°-29°30°-50° AIRTURN
15° DEFLECTROL

TURNING VANES
12x12
24x12

CONVERGING OR DIVERGING

VANE ANGLE
FLEX. DUCTDIFFUSER

CEILINGDIFFUSER

BRANCH-SEEPLAN FOR SIZE
24x12

CEILINGDIFFUSERCAP ATEND OF RUN

DEFLECTROL

AND BRANCH

SAME SIZE

AS NECK SIZE
24x12

SAME SIZE

AND BRANCH

DEFLECTROL FIRE
DAMPER10'MAX.LENGTH -OVER 10'USE NO.6,7,8 OR 9

SIDEWALLREGISTER
6,7,8 OR 9USE NO.OVER 10'LENGTH -10'MAX.12x6

DEFLECTROL &BRANCH DUCTSAME SIZECEILINGDIFFUSER
24x12
14x10SQUARE ELBOWW/ DUCT TURNMVD16x12
48x1212x1210x8
24x1210/14
TRANSITIONALRADIUS ELBOW4/36/838x12TRANSITION
8"36"
4"
14"10"
14"
10"
RADIUS ELBOWTRANSITIONAL14x10
24x12
16x12
10/14 SPLIT

AIR FLOW

SQUARE ELBOWW/ DUCT TURN
4/36/838x12TRANSITION 12x12
48x1210x8

DIVERGING FLOW
24x12 1 IN 6 MAX.
12x121 IN 2MAX.
1 IN 6 MAX.12x12

CONCENTRIC ECCENTRIC
24x12
24x12 24x12
12x12 12x12
1 IN 2 MAX.

DUCT SYMBOLS

SYMBOL DESCRIPTION SYMBOL DESCRIPTION
1234
14161517
56 19
18 36"8"
4"
2120
87 10
9 2322

ACOUSTICALLY LINED
SHEET METAL DUCT 24 x 36 AL
45∅TEE

TURNING VANES
VANES

INDICATES ROUND DUCTSIN INCHES, TYPICAL

OR GRILLE

SIZE SHOWN IS NETINSIDE DIMENSION
26 24 x 36 AL
INCHES UNLESSOTHERWISE NOTED.

GENERAL NOTES MECHANICAL LEGEND

MARK OR EQUAL

GREENHECK
CFM
RH-1 FGR
MODEL NO.
2060 24"x24"
CURB
515
SIZE
30"x30"x12"

REMARKS
NOTES:1. PROVIDE 12" FACTORY STANDARD ROOF CURB.2. PROVIDE ALUMINUM BIRDSCREEN.3. PROVIDE BACKDRAFT DAMPER.

SEE NOTES34"x36" 19"
OPER.

APPROX.

WT.

LBS.
69 FPM THROAT SIZE HOOD SIZE HOOD HEIGHT MOUNTING DETAIL 6/M-401
RH-2 FGR 300 10"x10" 432 16"x16"x12" SEE NOTES20"x24" 14" 37RH-3 FGR 995 14"x20" 512 20"x26"x12" SEE NOTES24"x36" 16" 51RH-4 FGR 1470 18"x24" 490 24"x30"x16" SEE NOTES28"x36" 16" 57RH-5 FGR 1470 18"x24" 490 24"x30"x16" SEE NOTES28"x36" 16" 57 MFR

MODEL BORDER TYPE OBD FINISH DESCRIPTIONMARK
SG-1
SURFACE MOUNTED STEEL DOUBLE DEFLECTION SUPPLY GRILLE. 3/4"BLADE SPACING, FRONT BLADES PARALLEL TO SHORT DIMENSION. PROVIDE WITH STD. FINISH.

TITUS
300RS NO WHITESIDEWALL
GENERAL NOTES:

1. FURNISH ALL CEILING AIR TERMINALS WITH BORDER STYLES THAT COORDINATE WITH APPLICABLE CEILING TYPE. SEE

ARCHITECTURAL DRAWINGS FOR CEILING TYPES

2. PROVIDE RECTANGULAR TO ROUND DUCT ADAPTORS AND ROUND TO RECTANGULAR AS NEEDED TO MAKE DUCT CONNECTIONS PER PLANS.

3. TERMINAL NECK SIZE, TERMINAL FACE SIZE AND AIRFLOW DIRECTION DEFLECTIONS ARE PER PLANS.4. PAINT INSIDE OF DUCT PLENUMS ABOVE GRILLES, VISIBLE FROM OCCUPIED SPACE BELOW, FLAT BLACK. REFER TO SPECIFICATIONS. 350RL SIDEWALL WHITENORG-1
SIDEWALL STEEL SURFACE MOUNTED LOUVERED RETURN GRILLE. 3/4" BLADE SPACING, 35 DEGREE° DEFLECTION, BLADES PARALLEL TO LONG DIRECTION, PROVIDE WITH STD. FINISH.

SD-S

SURFACE MOUNTED STEEL MODULAR CORE, ADJUSTABLE, SURFACE MOUNTED CEILING DIFFUSER. PROVIDE WITH STD. FINISH. TITUS MCD NO WHITESURFACE 50F SURFACE WHITENOEG-S

LD PRICE RFD NO WHITET-BAR LAY-IN
SD-L
24"x24" STEEL MODULAR CORE, ADJUSTABLE, LAY-IN CEILING DIFFUSER.

PROVIDE WITH STD. FINISH. TITUS MCD NO WHITESURFACE
24"x24" STEEL, LAY-IN CEILING DIFFUSER. PROVIDE WITH STD. FINISH.

RG-L 50F T-BAR LAY-IN NO WHITE 24"x24" ALUMINUM LAY-IN CEILING RETURN GRILLE WITH 1/2"x1/2"x1/2 "
ALUMINUM EGG CRATE GRILLE. PROVIDE WITH STD. FINISH.

EG-L 50F T-BAR LAY-IN NO WHITE 24"x24" ALUMINUM LAY-IN CEILING EXHAUST GRILLE WITH 1/2"x1/2"x1/2 "
ALUMINUM EGG CRATE GRILLE. PROVIDE WITH STD. FINISH.
6/M-4016/M-4016/M-4016/M-401

ALUMINUM SURFACE MOUNTED CEILING EXHUAST GRILLE WIT
H 1
2"x
1 2"x
1 2"
ALUMINUM EGG CRATE GRILLE. PROVIDE WITH STD. FINISH.

TG-L 50F T-BAR LAY-IN NO WHITE 24"x24" ALUMINUM LAY-IN CEILING TRANSFER GRILLE WIT H 1/2"x1/2"x1/2
"
ALUMINUM EGG CRATE GRILLE. PROVIDE WITH STD. FINISH.
350RL SIDEWALL WHITENOTG-1
SIDEWALL STEEL SURFACE MOUNTED LOUVERED TRANSFER GRILLE. 3/4"BLADE SPACING, 35 DEGREE° DEFLECTION, BLADES PARALLEL TO LONGDIRECTION, PROVIDE WITH STD. FINISH.

RH-6 FGR 460 10"x14" 460 16"x20"x12" SEE NOTES24"x14" 16" 38 6/M-401 PLANS ARE NOT FOR CONSTRUCTION UNTIL APPROVED BY THE AUTHORITY HAVING JURISDICTION. THE CONTRACTORSHALL NOT ORDER ANY MATERIALS OR INSTALL ANY EQUIPMENT, PIPING, ETC. UNTIL PLANS ARE APPROVED BYTHE AUTHORITY HAVING JURISDICTION.

2. 9.8.7.6.6.5.

4.3.1. ALL WORK SHALL BE IN ACCORDANCE WITH ALL FEDERAL, STATE, CITY AND LOCAL CODES AND ORDINANCES.THE CONTRACTOR SHALL READ ALL OF THE GENERAL NOTES, SPECIFICATIONS AND PLANS AND SHALL BESATISFIED TO THEIR TRUE MEANING AND INTENT AND SHALL BE RESPONSIBLE FOR COMPLYING WITHEACH. WHEREVER TWO OR MORE SPECIFICATIONS MAY CONFLICT, THE MORE STRINGENT SPECIFICATIONSHALL TAKE PRECEDENCE.IT IS INTENDED THAT THESE PLANS AND SPECIFICATIONS REQUIRE ALL LABOR AND MATERIAL NECESSARY

AND PROPER FOR THE WORK CONTEMPLATED AND THAT THIS WORK BE COMPLETED IN ACCORDANCE WITH THEIR TRUE INTENT AND PURPOSE. THE CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVEIMMEDIATELY REGARDING ANY DISCREPANCIES OR AMBIGUITIES THAT MAY EXIST IN THE PLANS AND/OR SPECIFICATIONS PRIOR TO SUBMITTING BID. THE OWNER'S REPRESENTATIVE AND THE ENGINEER'S INTERPRETATIONTHEREOF SHALL BE CONCLUSIVE.THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR ANY FIELD CHANGES MADE WITHOUT PRIORWRITTEN AUTHORIZATION FROM THE OWNERS REPRESENTATIVE.CONTRACTOR SHALL INSTALL ALL PIPING AND DUCTWORK SYSTEMS TO BEST SUIT FIELD CONDITIONS, ANDCOORDINATE WITH THE INSTALLATION WORK OF OTHER TRADES. THE DRAWINGS ARE DIAGRAMMATIC ANDSHALL NOT BE SCALED TO DETERMINE EXACT LOCATION OF PIPING. NOTIFY CONSTRUCTION MANAGER OF ANY DEVIATIONS FROM THESE DRAWINGS PRIOR TO FABRICATION AND/OR INSTALLATION.

LOCATIONS AND DIMENSIONS OF EQUIPMENT, PIPING, AND THEIR SUPPORTS ARE SHOWNDIAGRAMMATICALLY AND SHALL NOT BE SCALED TO DETERMINE EXACT LOCATION OF PIPING ORDUCTWORK. ACTUAL DIMENSIONS AND LOCATIONS ARE DEPENDENT ON MATERIAL SUPPLIED BYCONTRACTORS. CONTRACTORS SHALL PROVIDE OR DETERMINE DIMENSIONS AND PROVIDE LAYOUTDRAWINGS FOR COORDINATION WITH OTHER TRADES IN ACCORDANCE WITH THE SPECIFICATIONS.CONTRACTOR SHALL REMOVE RUBBISH WASTE MATERIALS ON DAILY BASIS AND PROTECT AREAS FROMDAMAGE WHICH MAY OCCUR DURING CONSTRUCTION. CONTRACTOR SHALL BE RESPONSIBLE FOR ANYDAMAGE WHICH MAY OCCUR.

ALL WORK SHOWN ANYWHERE ON THE DRAWINGS IS INCLUDED; SHOULD AN ITEM (SUCH AS A VALVE) BE SHOWN ON A DETAIL OR SCHEMATIC BUT NOT ON A PLAN VIEW OR VICE VERSA, IT MUST BE PROVIDED ASTHOUGH IT WERE SHOWN IN ALL PLACES ON THE DRAWINGS.CONTRACTOR SHALL FURNISH ALL NECESSARY STRUCTURES, INSERTS, SLEEVES, HANGING DEVICES, MISCELLANEOUS ANGLES, CHANNELS, UNISTRUT ETC. FOR INSTALLATION OF MECHANICAL AND PLUMBING EQUIPMENT, DUCTWORK AND PIPING, ETC. CONTRACTOR SHALL COORDINATE WITH GENERAL CONTRACTOR AND ALL BUILDING TRADES TO AVOIDCONFLICTS AND TO MAINTAIN EQUIPMENT ACCESS AND SERVICEABILITY.

EACH MECHANICAL APPLIANCE SHALL BE APPROVED BY THE ADMINISTRATIVE AUTHORITY FOR SAFE USE ORCOMPLY WITH APPLICABLE NATIONALLY RECOGNIZED STANDARDS AS EVIDENCED BY THE LISTING AND LABELOF AN APPROVED AGENCY.

10.11. THERMOSTAT SETPOINTS SHALL BE PER CALIFORNIA T-24 REQUIREMENT. ANY DEVIATION FROM THESE SETPOINTS BECOMES THE RESPONSIBILITY OF THE USER OR CONTRACTOR.

12. SEISMIC BRACING FOR PIPING CARRYING HAZARDOUS OR COMBUSTIBLE MATERIALS (SUCH AS NATURAL LINES) SHALL BE PROVIDED FOR ALL PIPES > 1" DIAMETER IN SIZE. BRACING SHALL BE PER CBC SECTION 1616A.1.26.

ACCEPTABLE SEISMIC BRACING DETAILS INCLUDE THOSE SHOWN IN EATON/COOPER B-LINE OPM-0052-13.

13. SEISMIC BRACING FOR PIPING CARRYING HAZARDOUS OR COMBUSTIBLE MATERIALS (SUCH AS WATER LINES) SHALL BE PROVIDED FOR ALL PIPES > 3" DIAMETER IN SIZE. BRACING SHALL BE PER CBC SECTION 1616A.1.26.

ACCEPTABLE SEISMIC BRACING DETAILS INCLUDE THOSE SHOWN IN EATON/COOPER B-LINE OPM-0052-13.

MARK

SUPPLY FAN (UPFLOW)

COMPUTER ROOM AIR CONDITIONING UNITS SCHEDULE

COOLING ELECTRICAL SERVICE

VOLTAGE PHASE HZ

FILTERS

MCA MOCP
CRAC-1 PX018 66,500 54,800 SEE COMMENTS2800 1 0.90 460 3 60 18.8 25 MERV 8 670

AIR COOLED CONDENSER UNIT SCHEDULE

MARK REMARKS
MCA
ACCU-1 MCM040E1 1 1.8 CRAC-1 468 SEE NOTES 1-3,5
NOTES:1. PROVIDE WITH SINGLE CIRCUIT LINE SETS FROM CONDENSER TO INDOOR UNITS.2. PROVIDE CONTROLS WIRING BEWTEEN OUTDOOR ACCU UNITS AND INDOOR CRAC UNITS.3. REFRIGERANT 410A.4. CONTRACTOR SHALL COORDINATE AND PROVIDE THE MANUFACTURER'S REPRESENTATIVE THE FINAL REFRIGERANT ROUTE (PRIOR TO ORDERING OR INSTALLING ANY PIPING) TO VERIFY SIZES.

MAXIMUM LENGTH = 150 FT. AND 20 FEET MAX. VERTICAL DIFFERENCE BETWEEN INDOOR AND OUTDOOR UNIT. CONTRACTOR SHALL HAVE MANUFACTURER PROVIDE AN ENGINEEERED SHOP DRAWING IN THE SUBMITTAL.

NOTES:1. PROVIDE WITH STANDARD FEATURES.2. PROVIDE UNIT MOUNT CONDENSATE PUMP.3. COOLING CAPACITES ARE BASED ON 105°F AMBIENT, 75°F EDB, 61°F EWB, 45% RH. LAT = 54.3°F.4. COOLING CAPACITY OF UNITS IS BASED ON A MAXIMUM OF 3 KW COMPUTER RACK LOAD.5. PROVIDE UNIT WITH CONTACTS FOR AUTO-SHUT OFF.6. PROVIDE UNIT WITH PIPE ROUTING THRU TOP.7. COORDINATE WITH ELECTRICAL FOR POWER AND DISCONNECTS.8. R-410A REFRIGERANT.9. PROVIDE REMOTE UNIT START/STOP AND ALARM DRY CONTACT.

MOCP
15 0.20
LIEBERT MODEL NO. TOTAL
CFM

EXTERNAL
S.P. (IN) MOTOR QTY. HP TOTAL BTU/H SENSIBLE BTU/H SIZE (QTY)INCHES EFF WEIGHT
(LBS) COMMENTS

LIEBERT
MODEL NO.

ELECTRICAL SERVICE
UNIT
SERVED

OPERATING
WT. LBS.

QTY.

10.6 LBS. OF

REFRIGERANT
RL
5/8"
RS
7/8"
HP (EA.) FLA (EA.)

29.5"x28.5"x2"
RL
1/2
RS
5/8

PIPING SIZES

REFRIGERANT DRAIN
DIA.
3/4
FANS

1.25 VOLTAGE PHASE HZ

1.4 460 3 60

REFRIGERANT
SEE NOTE 5
F

NEWOPPOSED BLADE DAMPEROUTSIDE AIRPHASERETURN AIRRETURN DIFFUSERROOF EXHAUST FANREVOLUTION PER MINUTERETURN REGISTER (GRILLE)SHEET METALSUPPLY AIRSUPPLY DIFFUSER (REGISTER) (GRILLE)TRANSFER GRILLETURNING VANESUNDERCUT DOORSUP THRU ROOFUTR

UCDTVTGSD(R)(G)SASMRR(G)RPMREFRDRA
∅

OSAOBD(N)

ACADAEAL

CDCFMCEFEF(E)EGESPFCFDFTHZHPIFMBH
MVD

MCA MINIMUM CIRCUIT AMPACITY

MANUAL VOLUME DAMPER

THOUSAND BTU PER HOURHORSE POWERHERTZFOOT OR FEETFIRE DAMPERFLEXIBLE CONNECTIONEXTERNAL STATIC PRESSUREEXHAUST GRILLEEXISTINGEXHAUST FANCEILING EXHAUST FANCUBIC FEET PER MINUTECONDENSATE DRAIN

ACOUSTICAL LININGAIR EXTRACTORACCESS DOORAIR CONDITIONING

INDOOR FAN

RH RADIANT HEATER

FALFA FRESH AIR

FRESH AIR LOUVER

EAL EXHAUST AIR LOUVEREA EXHAUST AIR

TD TRANSFER DUCT

BACKDRAFT DAMPERBDDCENTERLINEDOOR LOUVER
CDL
L

FIRE/SMOKE DAMPERFSD FSD

GAUGEGALVANIZED IRON
GAGI

MAXIMUM OVER CURRENT PROTECTIONMOCPON CENTEROC

S SENSORT THERMOSTAT

TEMPERATURE CONTROL PANELTCP
LEAVING AIR TEMPERATURELATPOUNDSLBS.LOCK ROTOR AMPSLRAHEATING & VENTILATIONH&VGALVANIZED SHEET METALGSM

FLA FULL LOAD AMPS
FEET PER MINUTEFPMDEGREES FAHRENHEIT°FENTERING AIR TEMPERATUREEATDOWNDN.DRY BULBDBBRAKE HORSEPOWERBHP

ABOVE FINISHED FLOORAFF
MAXIMUMMAX.

VOLTSVVARIABLE AIR VOLUMEVAVVARIABLE FREQUENCY DRIVEVFDWITHW/WET BULBWBWEIGHTWT.TYPICALTYPTOTAL STATIC PRESSURETSP TEMPERATURETEMP.

SS STAINLESS STEEL
REFRIGERANT SUCTIONRSREFRIGERANT LIQUIDRLPOINT OF CONNECTIONPOCQUANTITYQTYOPENINGOPNG.MOTORIZED DAMPERM

MANUFACTURERMFR
MINIMUMMIN.

TO BE DETERMINEDTBD

BOTTOM OF DUCTBOD

SD SMOKE DETECTOR

OUTSIDE AIR HOODOSH
C CO2 SENSOR
(NECK SIZE) (TERMINAL TYPE)(TERMINAL CFM), (ENTERING DUCT)

AIR TERMINAL TAG DESCRIPTION
12x12 SD-L
300,12"Ø

CHILLED WATER SUPPLYCHWSCHILLED WATER RETURNCHWR

POINT OF DISCONNECTIONPOD

H SPACE HUMIDITY SENSOR

RELIEF HOOD SCHEDULE

DIFFUSER, REGISTER AND GRILLE SCHEDULE
7750 College Town Dr, Ste. 101Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A
F C O
TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:

PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:25:44 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt M-001

SYMBOLS ANDNOTESDCWWTP OPERATIONSAND LAB BLDG
4/24/18
Author 210015.01
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
NO. DATE DESCRIPTION

BID SET (PRELIMINARY)

SEE NOTES BELOW
NOTES:1. FIELD PROVIDED WALL MOUNTED THERMOSTAT WITH PROTECTIVE SCREEN AND SET TO MAINTAIN 40°F.2. FACTORY PROVIDED SURFACE MOUNTING FRAME - STAINLESS STEEL - MODEL SEDSMC.3. FACTORY PROVIDED STAINLESS STEEL FINISH.4. STANDARD DUAL PROTECTION: THERMAL CUTOUT WITH INDICATOR LIGHT AND ONE TIME THERMAL FUSE.

VARIABLE REFRIGERANT FLOW (VRF) OUTDOOR UNIT SCHEDULE
MARK
RXTQ36TAVJ9A 208/1/60 17220
NOTES:1. REFRIGERANT TYPE R410A2. CAPACITIES SHOWN HERE ARE AT AHRI NOMINAL CONDITIONS (AHRI 1230)3. THIS MARK HAS TWO ELECTRICAL SERVICES/POINTS OF CONNECTION.4. COORDINATE DISCONNECTS AND SERVICE WITH ELECTRICAL PLANS.5. SEE 8/M-403 FOR REFRIGERANT PIPE SIZES. THE CONTRACTOR SHALL COORDINATE WITH MANUFACTURER'S SUBMITTAL FOR FULL PIPING

LAYOUT AND PROVIDE SHOP DRAWINGS PRIOR TO SUBMITTAL
SEE NOTES10

ELECTRICAL

SERVICE
OPER.

WEIGHT
(LBS)
DAIKIN
MODEL NO.
(16)
ARI
IEER
(SEER)
ARI
EER

16.5 MCA MOCP DIMENSIONS (HxWxD)
(9)29
DESIGN

COOLING
(MBH)
36 DESIGN

HEATING
(MBH)

CONNECTION
RATIO

86.9 V/PH/HZ

REMARKS
39"x37"x14"
ARI
COP
(HSPF)
3/M-501

MOUNTING
DETAIL

CONTROL
DETAIL
2/M-401

REMARKS

DX COOLING COIL
CFM
MARK

SUPPLY FAN

VRF INDOOR FAN COIL UNIT SCHEDULE

ESP MBH SENS/TOT
WEIGHT
(LBS)

OUTSIDE AIR
(CFM)

HEAT PUMP HEATING
MBH EAT (°F)FLA
DAIKIN
MODEL NO. LAT (°F) TYPESERVED BY SPACE SERVED MCA MCOP

ELECTRICAL

SERVICE

DB/WB V/PH/HZ
EAT (°F) LAT (°F)
DB

DIMENSIONS
(L"xW"xH")
FC-1AFC-2AFC-3AFC-1BFC-2BFC-3B

VRF-AVRF-AVRF-AVRF-B
BUNK ROOM 129-131
OFFICE 114,115

CORRIDOR
OPEN OFFICE 108

STORAGE/LAUNDRY
CORRIDOR 118

NOMINAL
TONS

0.60.51.50.6 1.25

1.5 9/90.63FC-1D
WB °F
DB °F
EAT
FLA

REMARKS

DX COOLING
CFM
MARK

SUPPLY FAN
HP-1D 208/1/60 60 1 11.6 15 343
NOTES:1. REFRIGERANT TYPE R410A2. REFRIGERANT PIPE SIZES PER FAN COIL SCHEDULE.3. REFRIGERANT LINE LENGTH IS RATED FOR UP TO 165' TOTAL LENGTH, 100' HEIGHT DIFFERENCE AND UP TO 15 BENDS AT THE SCHEDULED LINE SIZES. CONTRACTOR TO NOTIFY OF DISCREPANCIES.

QTY
1 CONTROL ROOM 125
MBH

SENS/TOT
WEIGHT
(LBS) ROOM SERVED

17.80 ELECTRICAL

SERVICE

V/PH/HZ RLA
UNIT

SERVED WEIGHT (LBS)
15 LIQUID

REFRIGERANT

SUCTION

MANUFACTURER
AND
MODEL NO.

11.10.75 NOMINAL
TONS MARK NO.

COMPRESSOR

REMARKS
FC-1D

MOCPMCA

SEE NOTES
AHRI
EER
AHRI
SEER NO. FLA

CONDENSER
73 LRA
1 .13 4.0
COP

HEAT PUMP HEATING

TOTAL MBH
WB °F
DB °F
LAT
DB °F
EAT
DB °F
LAT

MANUFACTURER
AND
MODEL NO.

DAIKIN
FDMQ09RVJU
DAIKIN
RX09RMVJU9A
TYPE
2/M-401 DUCTED

MOUNTING
DETAIL
1/M-502

CONTROL
DETAIL

MOUNTING
DETAIL

CONTROL
DETAIL

ELECTRICAL

SERVICE

V/PH/HZ

MOCPMCA OSA (CFM)
HP-1E SEE NOTES FC-1E DUCTED CONTROL ROOM
FXSQ07TBVJU DUCTED 281 0.6" 0.6 5.3/5.9 76/61 59 8.4 70 98 208/1/60 0.8 15 22"x10"x32" 55 55 SEE NOTES DUCTED 530 0.6 1.2 10.6/12.0 75/61 57 208/1/60 2.88 15 28"x29"x32" 60DUCTED 281 0.6 0.6 4.8/4.8 76/61 61 208/1/60DUCTED 600 0.6 1.3 13.2/14.5 56 208/1/60 15 77 FXSQ05TBVJUFXSQ18TBVJU
281 0.6" 0.6 4.8/4.8 76/61 61 6.4 70 91 208/1/60 0.8 15 22"x10"x32" 55 55 74/61600 0.6" 1.3 13.2/14.5 56 19.8 70 100 208/1/60 1.6 15 39"x10"x32" 77 175 FC-1E

LOCATION
FAN
MARK MODEL NO.

MANUFACTURER/
CFM E.S.P.

MOTOR

ENCLOSURE
INPUT

RPM V/PH/HZ

SERVICE
MOTOR

ROOMS SERVED REMARKS
IEF-1
(INLET/
NOTES:1. COORDINATE WITH ELECTRICAL FOR POWER AND DISCONNECT2. PROVIDE WITH BACKDRAFT DAMPER3. INSTALL WITH LINE VOLTAGE THERMOSTAT. ON AT 90° F AND OFF AT 80° F.4. PROVIDE WITH MOTOR STARTER EQUIVALENT TO GREENHECK MSAC-1-9/J-G1.6-40 TYPE
DRIVE
2060 .35" 380 208/1/601640 66TENV 15.1/11.7 GREENHECK MENS LOCKER ROOM SQ-130-VG DIRECT DRIVE CEILING SONES

RADIATED)
DETAIL

MOUNTING
DETAIL

CONTROL
2/M-501
WEIGHT
OPER.
(LBS)
IEF-2 300 .35" 45 115/1/601566 56TENV 7.4/6.5 RESTROOM 119-120 GREENHECK SQ-80-VG DIRECT DRIVE 2/M-501 (W)
REYQ216AAYDA 460/3/60 97230 SEE NOTES11 20.529.9 3.25164 185 98.4 65"x69"x28" 3/M-501 DUCTED DUCTED
BUNK ROOM 126-128
FC-4BFC-5BFC-6BFC-7BFC-8BFC-9B
FC-10B
FXSQ05TBVJUFXSQ15TBVJUFXSQ18TBVJUFXSQ05TBVJUFXSQ30TBVJUFXSQ18TBVJUFXSQ12TBVJUFXSQ48TBVJUFXSQ12TBVJUFXSQ48TBVJU

VRF-BVRF-BVRF-BVRF-BVRF-BVRF-BVRF-BVRF-BVRF-B

0.62.51.51.04.01.04.0 DUCTEDDUCTEDDUCTEDDUCTEDDUCTEDDUCTEDDUCTED 281812600335
1307
335
1307

0.6"

0.60.60.6 0.6"0.6"

0.6 0.8 15 22"x10"x32" 55 35
35 185
8095704575
126289

6.4 70 91
76/6175/6175/6175/6175/6175/6175/6175/61

21.0/24.0 5112.7/14.5 56

9.3/9.6 51

31.6/38.7 53

4.7/4.8 619.3/9.6 51

31.6/38.7 53
208/1/60208/1/60208/1/60208/1/60208/1/60208/1/60208/1/60 707070707070707070

16.8 9919.8 100

6.4 91

33.6 10819.8 10013.3 10753.4 10813.3 10753.4 108
15151515151515

0.81.61.61.80.80.82.82.8 55827755
104
55 104
39"x29"x32"22"x29"x32"39"x29"x32"39"x29"x32"22"x29"x32"55"x29"x32"22"x29"x32"55"x29"x32"

REMARKS

VRF BRANCH CIRCUIT CONTROLLER BOX SCHEDULE
DAIKIN
MODEL NO.

ELECTRICAL

SERVICE

V/PH/HZ
WEIGHT
(LBS) MCA MOCPSERVICE
MAX

CAPACITY
(MBH)

DIMENSIONS
(LxWxH)
1 11.6 15 17.8015 11.10.75 731 4.0 60 343 1 9/90.63 DAIKIN RX09RMVJU9A DAIKIN FDMQ09RVJU HEF-1 765 .35" 201 460/3/602444 308TEFC - FH-1 GREENHECK VEKTOR-H-10 BELT DRIVE ROOF 5/M-401 1/M-503 HEF-2 765 .35" 201 460/3/602444 308TEFC - FH-2 GREENHECK VEKTOR-H-10 ROOF HEF-3 765 .35" 201 460/3/602444 308TEFC - FH-3 GREENHECK VEKTOR-H-10 ROOF

LOCATION
SIZE (IN.)
MARK MODEL NO. WIDTH DEPTH CFM V/∅/HZ ELECTRICAL

AIR VOLUME

REMARKS
FH-1 12.8" - 60 37.7" 765 0.22" 450 LABORATORY SEE NOTES WEIGHT
115/1/60
S.P. (IN.)

DUCT SIZE
(I.D.)
COLLAR
FH-2FH-3

LABCONCO

PROTECTOR XL
(IN.) (IN.) (LBS) (OR EQUAL) - 60 37.7" 765 0.22" 450 LABORATORY 115/1/60 SEE NOTES PROTECTOR XL - 60 37.7" 765 0.22" 450 LABORATORY 115/1/60 SEE NOTES PROTECTOR XL WEF-1
BROAN
512M 70 48 120/1/602660 -- 0.9 WALL -9/M-401 JANITOR SEE NOTES: 1-2 PORTS
HP-1F 214 1 8 31 18.825 10.83 FC-1F SEE NOTES132 EQUIPMENT ROOM 920 1 36/360.57DFC-1F 0.5 4.52 MITSUBISHI TPKA0A0361KA70A MITSUBISHI TRUZA0361KA70BA DUCTLESS HP-1G FC-1G DFC-1G
DFC-1HDFC-2H
HP-1HHP-2H
214214214
FC-1HFC-2H
MDF 36/36920 1 MITSUBISHI TPKA0A0361KA70A DUCTLESS
ELECTRICAL 36/36920 1 MITSUBISHI TPKA0A0361KA70A DUCTLESSELECTRICAL 36/36920 1 MITSUBISHI TPKA0A0361KA70A DUCTLESS 1 8 31 18.825 10.83 SEE NOTES13 4.52 MITSUBISHI TRUZA0361KA70BA 1 8 31 18.825 10.83 SEE NOTES13 4.52 MITSUBISHI TRUZA0361KA70BA1 8 31 18.825 10.83 SEE NOTES13 4.52 MITSUBISHI TRUZA0361KA70BA 1/M-502

0.50.50.50.50.50.50.5 222

0.570.570.57
20EH-1 SED1012C (WALL) 50 1000 8.33413 (10.5x1.125x17.25)

ELECTRICAL SERVICE
120/1PH/60HZ. WEIGHT
(LBS) BTU/hCFM
QMARK
MODEL NO.
(W"xD"xH")
MARK

WATTS AMPS

REMARKS
IEF-3IEF-4

GREENHECK
SQ-120 1470 .35" 323 460/3/601487 66ODP LABORATORY
DIRECT
DRIVE 1/M-503

GREENHECK
SQ-120 1470 .35" 323 460/3/601487 66ODP 10.3/7.8 LABORATORY DIRECT
DRIVE
OFFICE 110,111
OPEN OFFICE 108
OFFICE 104,105
OFFICE 103
RECEPTION 101
KITCHEN 109

10.3/7.8

0.61.51.30.72.20.72.2 .13
2/M-401
5/M-4015/M-4014/M-4014/M-4014/M-4014/M-401
2/M-4012/M-4012/M-4012/M-4012/M-401

CEILINGCEILINGCEILING

WOMENS LOCKER ROOM

12.8"12.8"

SEE NOTESSEE NOTESSEE NOTESSEE NOTESSEE NOTESSEE NOTESSEE NOTESSEE NOTESSEE NOTESSEE NOTESSEE NOTESSEE NOTES

CONFERENCE ROOM
107

CONFERENCE ROOM
102
CEF-1 GREENHECK SP-B150 150 .25" 128 115/1/601050 10ODP 3.0 CEILING -2/M-404 MECHANICAL 132 SEE NOTES: 1-3 DIRECT DRIVE

LOCATION

VARIABLE FREQUENCY DRIVE SCHEDULE
MARK VOLTS/PH/HZ REMARKSHP SERVES WEIGHT MOUNTING DETAIL MANUFACTURER / MODEL # VFD-1 ABB, INC / ACH580 IEF-31.0 18 8/M-404 SEE NOTES460/3/60 VFD-1 ABB, INC / ACH580 1.0 460/3/60 IEF-4 18 8/M-404 SEE NOTES SEE NOTES: 1,2,4SEE NOTES: 1,2,4SEE NOTES: 1,2,4SEE NOTES: 1-2SEE NOTES: 1-2SEE NOTES: 1-2SEE NOTES: 1-2

EQUIPMENT ROOM
136

EQUIPMENT ROOM
136
BELT
DRIVE
BELT
DRIVE
IEF-5

GREENHECK
SQ-90-VG 460 .35" 45 115/1/601525 56TENV 7.2/6.1 CEILING 4/M-404 SEE NOTES: 1-2 DIRECT DRIVE LABORATORY 1/M-5031/M-5031/M-5031/M-503
1/M-5021/M-5021/M-5021/M-502
208/1/60208/1/60208/1/60208/1/60208/1/60
NOTES:1. CFM IS AT 100 FPM WITH SASH AT (18"). PROVIDE STOP.2. STAINLESS STEEL EXHAUST COLLAR TRANSITION T0 12" DIAMETER.3. FOR CHEMICAL FUME HOOD DUCT MATERIALS, SEE SPECS.4. CONTRACTOR SHALL HIRE "TECHNICAL SAFETY SERVICES" (TSS) TO TEST HOOD FOR ASHRAE 110 CODE COMPLIANCE. COORDINATE TESTING WITH THE OWNER AND CONTRACTOR.

5. FH-1, FH-2, & FH-3 SHALL BE ACCESSIBLE. HEIGHT OF HOOD & UTILITIES SHALL MEET ALL ACCESSIBILITY REQUIREMENTS.

6. COORDINATE WITH LAB FURNITURE PROVIDER FOR ALL REQUIREMENTS.7. HOOD SHALL BE 316 STAINLESS STEEL INTERIOR ACID TYPE HOOD, WASHDOWN SYSTEM, INTEGRAL WORK SURFACE, DRAINAGE TROUGHS AND CONTROL PANEL.

8. REMOVABLE FRONT ACCESS PANELS, LIGHT WITH ON-OFF SWITCH.9. PROVIDE OVAL CUPSINK (BACK -LEFT) FOR FH-1 & (FRONT-LEFT) FOR FH-2 & FH-3.

ORIENTATION PER USER.

10. PROVIDE OUTLETS AND FAUCET FOR VACUUM, AIR, NITROGEN & DI WATER. SEE PLUMBING PLANS FOR LOCATIONS.

11. PROVIDE FUME HOOD ALARM.12. VERIFY ALL MODEL NUMBERS WITH MANUFACTURER.13. FUME HOODS SHALL BE PROVIDED BY CONTRACTOR.14. PROVIDE CABINET BASED UNDER HOOD.15. PROVIDE STAINLESS STEEL CLOSURE PANELS ABOVE HOOD TO CEILING. 460/3/60

DB WBWBDB
LAT °FEAT °FMBH
SENS. TOTAL

DX COOLINGSUPPLY FAN
CFM
MARK
RPM

REMARKS

V/PH/HZ
NOTES:1. SELECTION/DESIGN CRITERIA: 102°F DB/70°F WB. (SUMMER), 24°F DB (WINTER).2. PROVIDE DIRECT DRIVE ECM SUPPLY FAN.3. PROVIDE DUCT SMOKE DETECTOR. PROVIDED BY ELECTRICAL, INSTALLED BY MECHANICAL FOR AUTOMATIC SHUTDOWN PER 2022 CMC 609.1.

4. PROVIDE NEMA 3R DISCONNECT SWITCH.

MOCP

SEE NOTES
DAIKIN
MODEL NO. ESP
(IN.)

ELECTRICAL
UNIT
FLA

MINIMUM

OUTSIDE
AIR
(CFM)
WEIGHT
(LBS) EER TSP
(IN.) BHP FLA MCA

PRE FILTERS
QTY. SIZE MERV
(IN.)

HEAT PUMP HEATING
EAT
°F HP

NOMINAL
TONS
DOAS-A
MBH LAT °F IEER
6 DPSH06B 2060 1.0 2.0 2121 0.99 1.7 2.3 77.3 77.3 102 70 64 57 59.8 43 69 52.5 64.5 70 - - 1258 2060 LRA
(EA) QTY. RLA (EA)

COMPRESSORS CONDENSER FAN
HP
(EA) QTY. FLA (EA)
1 1/2 0.9
2 0.51 1.7 2.3 52.3 52.3 102 70 62 57 42.4 43 72 38.1 46.5 50 - - 119 460/3/60 SEE NOTES: 1,2,4DOAS-B 4 DPSH04B 1295 1.0 1.6 169 5 1295 4 16"x16"x2" 13 - - - 1 - 11.6 1 1/2 0.9
DOAS-C 64.3 164.3 102 70 62 57 126.4 43 70 99.6 105.8 125 - - 2104 4100 460/3/60 SEE NOTES12 DPSH12B 4100 1.0 2.4 1877 2.43 4.3 4.6 1 6 18"x24"x2" 13
2 1 3.4

SUPPLEMENTAL

ELECTRIC HEATING
LAT °FFLA EAT °FkW
30 36.1 28 7418 21.7 28 72
4 16"x16"x2" 13 - - - 54 65 28 69 - - - 1 - 11.6 1 - 25.0 VRF-A
NOTES:1. SELECTED WITH 102°F DB/70°F WB (SUMMER) AND 24°F DB (WINTER) TEMPERATURES.2. PROVIDE DIRECT-DRIVE PLENUM FAN WITH ECM MOTOR.3. REFRIGERANT PIPES SIZED PER 8/M-403.

4. SEE ELECTRICAL DRAWINGS FOR DISCONNECT LOCATION.5. MANUFACTURER PROVIDED INTEGRAL CONDENSATE LIFT PUMP. SEE PLUMBING DRAWINGS FOR CONDENSATE ROUTING.6. MFR PROVIDED FILTER BOX WITH MERV 13 FILTERS. COORDINATE FILTER SIZE WITH FILTER BOX CUTSHEETS.

SEE NOTES64 7595
NOTES:1. REFRIGERANT TYPE R410A2. WIRED REMOTE CONTROLLER3. DRAIN PIPE CONNECTION SIZE 5/8"4. REFRIGERANT PIPE SIZES MAY NEED TO BE MODIFIED PER MANUFACTURER INSTRUCTIONS BASED ON IN FIELD LENGTHS.

5. PROVIDE UNIT WITH MERV 13 FILTERS.
1/4 3/839 6780 43 86 40 3/M-401 1/M-502208/1/60 159
159 55 SEE NOTES64
VRF-B
SEE NOTES101208/1/60BCC-1
MARK
BS10Q54TAVJ 1.0 15VRF-2 290 32"x12"x19"
NOTES:1. COORDINATE DISCONNECT AND SERVICE WITH ELECTRICAL PLANS.2. SEE SHEET 8/M-403 FOR REFRIGERANT PIPE SIZES. THE CONTRACTOR SHALL COORDINATE WITH MANUFACTURER'S SUBMITTAL FOR FULL

PIPING LAYOUT AND PROVIDE SHOP DRAWINGS PRIOR TO SUBMITTAL

3. PROVIDE FULL PORT BALL VALVES ON EACH BRANCH SELECTOR BOX REFRIGERATION LIQUID AND SUCTION LINE BRANCH. 7595 39 6780 43 86
10 SEE NOTES46 7595 3/8 5/8 -- 7/M-401 -1 - SEE NOTES64 SEE NOTES64SEE NOTES64
7595 3/8 5/8 -- - - 7595 3/8 5/8 -- - - 7595 3/8 5/8 -- - - 3/M-401 8/M-401 7/M-401 8/M-401 7/M-401 8/M-401 7/M-401 8/M-401 1/4 3/8 111 HEATING LOCKED OUT HEATING LOCKED OUT HEATING LOCKED OUT HEATING LOCKED OUT NOTES:

1. COMPLETE WITH MANUAL BYPASS. SEE ELECTRICAL FOR FUSED DISCONNECT2. NEMA-3 RATED ENCLOSURE TYPE3. A PASS THROUGH I/O SHALL OPEN VALVES IN THE SYSTEM IF VFD GOES INTO BYPASS MODE TO ALLEVIATE OVER PRESSURIZATION 1/M-5021/M-5021/M-5021/M-5021/M-502
208/1/60208/1/60208/1/60208/1/60208/1/60

DENSING UNIT SCHEDULE INDOOR FAN COIL UNIT SCHEDULEOUTDOOR AIR COOLED CON

FUME HOOD SCHEDULE EXHAUST FAN SCHEDULE

ELECTRIC HEATER DEDICATED OUTSIDE AIR SYSTEM
7750 College Town Dr, Ste. 101Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A F C O TATS N I CA L CH E M
R. N
S
NOR
ROF P

ED RETS
I
GE
R

SS I ONAL
ENG I
N
E
E
R

AE E T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:25:45 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt M-002

MECHANICALSCHEDULESDCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
1 NO. DATE DESCRIPTION
1 08/28/2024 PC Comments

BID SET (PRELIMINARY)
C US
www.captiveaire.com
SHEET NO.

SCALE:

DWG.#:

DRAWN
DATE:

BY:

REVISIONS
DESCRIPTION DATE:

ACCORDANCE
No. 96
BUILT
NFPA
W I TH
I N
S
L
ID
T
E
R
12345678910111213141516171819202122
[3][3]
23 [2][1]
7007677

MASTER DRAWING
MRE
1 9/11/2024
Dry Creek Waste Water
3/4" =1'-0"
,
Northern California Office
1110 Burnett Ave, Suite G, Concord, CA, 94520 PHONE: (925) 962 - 1999 FAX: 9255668565 EMAIL: [email protected] 1 111 2 YEAR PARTS WARRANTY TAG QTY DESCRIPTION- VARIABLE SPEED CONTROL. - THERMAL OVERLOAD PROTECTION (SINGLE PHASE). - HIGH HEAT OPERATION 300°F (149°C). EXHAUST FAN MUST OPERATE CONTINUOUSLY WHILE EXHAUSTING AIR AT 300°F (149°C) UNTIL ALL FAN PARTS HAVE REACHED THERMAL EQUILIBRIUM, AND WITHOUT ANY DETERIORATING EFFECTS TO THE FAN WHICH WOULD CAUSE UNSAFE OPERATION. NORMAL TEMPERATURE TEST 19"21"
25 1/2"
12 1/8"
2"
18 1/2"
- INTERNAL WIRING.
- ROOF MOUNTED FANS.
- RESTAURANT MODEL.

FEATURES:
- DIRECT DRIVE CONSTRUCTION (NO BELTS/PULLEYS).

TOP VIEW
25 1/2"
21"
- NEMA 3R SAFETY DISCONNECT SWITCH.

DUCTWORK BETWEEN

EXHAUST RISER ON HOOD
AND FAN (BY OTHERS).
25 1/4"
- UL705
3" FLANGE.
19"
19"

ROOF OPENING
DIMENSIONS.
20 GAUGECONSTRUCTION.

STEEL
12"
19 1/2"
19 1/2"
CURB.

FAN #1 DU33HFA - EXHAUST FAN
OPTIONS- ECM WIRING PACKAGE - MANUAL OR0-10VDC REFERENCE SPEED CONTROL-RTC- (TELCO MOTOR), CCW ROTATION.- 2 YEAR PARTS WARRANTY. 1 # 1 18 LBS CURB 19.500"W X 19.500"L X 12.000"H.

NO ON FAN WEIGHT ITEM SIZE
1 1 DU33HFA CAPTIVEAIRE 900 0.500 1498 TEAO-ECM 0.333 0.2090 1 115 4.3 446 FPM 65 15.6 TAG QTY FAN UNIT MODEL # MANUFACTURER CFM ESP RPM MOTOR ENCL HP BHP PHASE VOLT FLA DISCHARGE VELOCITY WEIGHT (LBS) SONES 1 3624
VHB-G
CAPTIVEAIRE 6' 0" 700 DEG II N/A 150 900 4" 10" 900 1650 -0.154" 430 SS 100% ALONE ALONE

TAG MODEL MANUFACTURER LENGTH
MAX

COOKING
TEMP

TYPE APPLIANCE DUTY DESIGN CFM/FT TOTAL EXH CFM

EXHAUST PLENUM

RISER(S)

WIDTH LENG HEIGHT DIA CFM VEL SP
HOOD

CONSTRUCTION

HOOD CONFIG
END TO

END ROW
1 0 NO 157 LBS
TAG

FILTER(S)

TYPE QTY HEIGHT LENGTH

EFFICIENCY
@ 7

MICRONS

LIGHT(S)

QTY TYPE WIRE GUARD

UTILITY CABINET(S)

LOCATION SIZE

FIRE SYSTEM

TYPE SIZE

ELECTRICAL
MODEL #

SWITCHES

QUANTITY
FIRE
SYSTEM
PIPING
HOOD

HANGING
WEIGHT
DRAIN FULLPERIMETERGUTTER.

SEE HOOD TABLE.
§ EXHAUST RISER.

HANGING ANGLE.

EQUIPMENT
BY OTHERS.
80"
24" NOM.
36"

IT IS THE RESPONSIBILITY

OF THE ARCHITECT/OWNER TO

ENSURE THAT THE HOOD CLEARANCE

FROM LIMITED-COMBUSTIBLE

AND COMBUSTIBLE MATERIALS

IS IN COMPLIANCE WITH
LOCAL CODE REQUIREMENTS.
6' 0"NOM./6' 0.00"OD.
36"
§
36" 36"
18"
∅ 10"
1/2" - 13 TPIGRADE 5 (MINIMUM)STEEL HEX NUT.1/2" GRADE 5(MINIMUM) STEELFLAT WASHER.1/2" - 13 TPIGRADE 5 (MINIMUM)STEEL HEX NUTS.1/2" GRADE 5(MINIMUM) STEELFLAT WASHER.1/2" - 13 TPIGRADE 5 (MINIMUM)STEEL ALL-THREAD.

HOOD CORNERHANGING ANGLE(WEIGHT BEARING

ANCHOR POINT
FOR HOOD).

HOOD CORNER

HANGING ANGLE
1/2" - 13 TPIGRADE 5 (MINIMUM)STEEL HEX NUTS.1/2" GRADE 5(MINIMUM) STEELFLAT WASHER.

ASSEMBLY INSTRUCTIONS
HANGING ANGLE MUST BE SUPPORTED WITH 1/2" - 13 TPI GRADE 5(MINIMUM) ALL-THREAD. SANDWICH HANGING ANGLES AND CEILING ANCHOR POINTS WITH 1/2" GRADE 5 (MINIMUM) STEEL FLAT
WASHERS AND 1/2" - 13 TPI GRADE 5 (MINIMUM) HEX NUTS ASSHOWN. MUST USE DOUBLED HEX NUT CONFIGURATION BENEATHHOOD HANGING ANGLES AND ABOVE CEILING ANCHORS. MAINTAIN1/4" OF EXPOSED THREADS BENEATH BOTTOM HEX NUT. TORQUE ALL HEX NUTS TO 57 FT-LBS.
(HARDWARE BY INSTALLER)
REF-1REF-1
H-1
7750 College Town Dr, Ste. 101Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A F C O TATS N I CA L CH E M
R. N
S
NOR
ROF P

ED RETS
I
GE
R

SS I ONAL
ENG I
N
E
E
R

AE E T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:25:45 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt M-003

MECHANICALSCHEDULESDCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP CONSTRUCTION DOCUMENTS 1
NO. DATE DESCRIPTION
1 08/28/2024 PC Comments

BID SET (PRELIMINARY)
7750 College Town Dr, Ste. 101
Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A
F C O
TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:25:57 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt M-101
TITLE 24DCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
NO. DATE DESCRIPTION

BID SET (PRELIMINARY)
7750 College Town Dr, Ste. 101
Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A
F C O
TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:26:09 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt M-102
TITLE 24DCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
NO. DATE DESCRIPTION

BID SET (PRELIMINARY)
7750 College Town Dr, Ste. 101
Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A
F C O
TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:26:21 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt M-103
TITLE 24DCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
NO. DATE DESCRIPTION

BID SET (PRELIMINARY)
7750 College Town Dr, Ste. 101
Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A
F C O
TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:26:24 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt M-104
TITLE 24DCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
1 NO. DATE DESCRIPTION
1 08/28/2024 PC Comments

BID SET (PRELIMINARY)
7750 College Town Dr, Ste. 101
Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A
F C O
TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:26:24 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt M-105
TITLE 24DCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
1 NO. DATE DESCRIPTION
1 08/28/2024 PC Comments

BID SET (PRELIMINARY)
PH
PH
PH
CR
PH
CR
CR
CR
CR
CR
CR
CR
CR
A A.5
B
C
E
F
1 2
45 1011
131

BUNK ROOM
130
BUNK ROOM 129

BUNK ROOM
128

BUNK ROOM
127

BUNK ROOM
126

BUNK ROOM
125
CONTROL ROOM 2
118

CORRIDOR
135

FIRE RISER
134

ELECTRICAL
133
MDF
123

MEN'S LOCKER RM
124

LAUNDRY
122

WOMEN'S LOCKER RM
113

WORK ROOM
136

EQUIPMENT ROOM
112

LABORATORY
111
OFFICE
114
OFFICE
115
OFFICE
116

RECORDS
117

STORAGE
121

JANITOR
118

CORRIDOR
108

OPEN OFFICE
120

RESTROOM
119

RESTROOM
109

KITCHEN
107

CONFERENCE ROOM
106
CONTROL ROOM 1
105
OFFICE
104
OFFICE
103
OFFICE
101

RECEPTION
102

CONFERENCE ROOM
110
OFFICE
FC
1A
FC
2A FC
3A
FC
1D
FC
8B
FC
9B
FC
7B
FC
6B
FC
1B
FC
2B
FC
4B
FC
1E
UP
IEF
1 IEF
2 FC
3B
FC
5B
FC
10B
FH
1 FH
2 FH
3 460,18"x8"
18"x8",SG-1
TYP. OF 3
10"ø
280,10"
⌀
10"x10",SD-L
TYP. OF 2
160,8"
⌀
8"x8",SD-L
10"øAL
TYP. OF 2
265,10"
⌀
10"x10",RG-L
TYP. OF 2
140,8"
⌀
8"x8",RG-L
TYP. OF 2
415,14"
⌀
16"x16",RG-L
160,8"
⌀
8"x6",SG-1
14"øAL
12"ø
160,8"
⌀
8"x8",SD-L
TYP. OF 3
12"øAL
280,10"
⌀
10"x10",RG-L
360,10"
⌀
10"x10",SD-L
815,22"x10"
22"x10",RG-1
225,8"
⌀
10"x10",SD-L
TYP. OF 3
225,8"
⌀
12"x8",RG-1
10"ø
14"øAL
38"x10"AL
335,10"
⌀
10"x10",SD-L
300,10"
⌀
10"x10",RG-L
12"ø
12"øAL
170,8"
⌀
10"x10",RG-L
285,10"
⌀
10"x10",RG-L
280,10"
⌀
10"x10",SD-L
100,6"
⌀
6"x6",SD-L
335,10"
⌀
10"x10",RG-L
460,12"
⌀
12"x12",SD-L
335,10"
⌀
10"x10",RG-L
18"ø
1305,36"x12"
36"x12",RG-1
WEF
1 EH
1 DFC
2H
DFC
1H
DFC
1F
IEF
3 IEF
4 24"x24",LD
220,8"
⌀
TYP. OF 4
24"x48",LD
235,8"
⌀
TYP. OF 4
24"x48",LD
235,8"
⌀
TYP. OF 2
24"x48",LD
235,8"
⌀
24"x48",LD
235,8"
⌀
TYP. OF 2
TYP. OF 2
1470,18"
⌀
20"x20",EG-L
1470,18"
⌀
20"x20",EG-L
0,12"x12"
12"x12",TG-S
TYP. OF 3
UCD
75,6"
⌀
6"x6",SD-S
TYP. OF 2
10"ø
8"ø
75,6"
⌀
6"x6",SD-L
TYP. OF 2
150,8"
⌀
8"x8",EG-S
TYP. OF 2
195,8"x6"
8"x6",SG-1
110,6"
⌀
8"x8",SD-L
TYP. OF 3
110,6"
⌀
8"x8",SD-L
TYP. OF 3
345,22"x10"
24"x12",RG-1
170,10"x6"
10"x6",SG-1
TYP. OF 2
10"ø
6"ø
6"ø
8"ø
600,18"x10"
18"x10",RG-1
TYP. OF 4
10"ø
12"øAL
10"ø 20"ø
400,18"x8"
18"x8",SG-1
TYP. OF 3
8"ø 8"ø
90,6"
⌀
8"x8",RG-L
TYP. OF 3
6"ø
6"ø
8"ø
630,12"
⌀
14"x14",EG-S
TYP. OF 2
16"ø 14"ø 400,10"
⌀
12"x12",EG-S
TYP. OF 2
500,12"
⌀
12"x12",SD-S
TYP. OF 2
260,10"
⌀
10"x10",SD-S
TYP. OF 2
18"ø 20"ø
20"ø
16"ø
6"ø
10"ø
14"ø
6"ø
10"ø
6"ø 10"ø
14"øAL 14"ø
12"øAL
12"ø
12"ø
400,12"
⌀
12"x12",SD-S
18"øAL
10"øAL12"øAL 10"øAL
18"øAL
12"øAL 10"øAL
18"øAL
18"øAL
54"x10"AL
1300,56"x12"
56"x12",RG-1
10"øAL
10"ø
8"ø
10"øAL
10"øAL 10"øAL
10"ø
8"ø
10"øAL
22"x10"AL
38"x10"AL
10"ø
10"øAL
12"øAL
14"øAL
10"øAL
10"øAL
0,12"x12"
12"x12",TG-1
0,12"x12"
12"x12",TG-S
132

MECHANICAL
BCC
1 1
1 1
1 1
1 1
1 1
1 6"ø
1 1
1 1
1 2
2 2
2 3
4 4
4 4
5 6
7 8
8 9
9 11
12 10
10"ø
FSD
FSD

FSD FSD

FSD FSD
MVD, TYP.

FSD

FSD FSD
MVD, TYP.

MVD, TYP. MVD,
TYP.
3 6789
T
T
13 26"x12"AL
UCD
28"x10"AL
T FC-1A FC-2A
T
FC-1D
T
UP
FC-7B
T
T FC-6B
T FC-3A
FC-3B
T
FC-4B
T
T
T FC-5B
FC-1E
FC-1B
T
T FC-2B
T FC-8B
FC-9B
T
FC-10B
T

T DOAS-C
T
T
T
CEF
1 0,6"x6"
6"x6",TG-S
TYP. OF 2
0,6"x6"
6"x6",TG-1
DN
6"ø
0,12"x12"
12"x12",TG-L
TYP. OF 2
0,12"x12"
12"x12",TG-L
T CEF-1
CRAC
1 14
15 DFC-1H
DFC-2H
DFC-1G
CRAC-1
T
16 300,10"
⌀
10"x10",RG-L
335,10"
⌀
10"x10",SD-L
0,12"x12"
12"x12",TG-L
TYP. OF 2
0,12"x12"
12"x12",TG-L
TYP. OF 2
0,12"x12"
12"x12",TG-L
TYP. OF 2
0,12"x12"
12"x12",TG-L
TYP. OF 2
0,10"x10"
12"x12",TG-L
TYP. OF 2
UCD
HU
1 0,12"x12"
12"x12",TG-L
TYP. EACH BUNK ROOM
90,6"
⌀
8"x8",RG-L
TYP. OF 3
0,12"x12"
12"x12",TG-1
TYP. EACH BUNK ROOM
VFD
2 VFD
1 17
17 IEF
5 2
18 DN
DOAS-C
18"
⌀ UP TO RH-4
16"
⌀ UP TO RH-3
160,8"
⌀
8"x6",SG-1
DOAS-C

T DOAS-C
19 137

BREAK ROOM
H
1 20
12"ø
1 7750 College Town Dr, Ste. 101Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A
F C O
TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:26:42 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt M-201

FLOOR PLAN -MECHANICALDCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
N
1 1/8" = 1'-0" FLOOR PLAN - MECHANICAL
KEYED NOTES:INSTALL FAN COIL TIGHT TO STRUCTURE PER DETAIL 3/M-401. INSTALL INLINE EXHAUST FAN TIGHT TO STRUCTURE PER DETAIL 4/M-401. INSTALL WALL EXHAUST FAN PER DETAIL 9/M-401.INSTALL DUCTLESS FAN COIL ON WALL PER DETAIL 7/M-401 AND 8/M-401.INSTALL ELECTRIC WALL HEATER PER DETAIL 1/M-403.INSTALL BRANCH CIRCUIT CONTROLLER TIGHT TO STRUCTURE PER DETAIL 6/M-402.SUPPORT CONCEALED ROUND DUCT TIGHT TO STRUCTURE PER DETAIL 1/M-402.TYP.SUPPORT EXPOSED ROUND SPIRAL DUCT PER DETAIIL 1/M-402. SUPPORT DUCT CENTERED AT 13'-6" A.F.F.INSTALL AIR TERMINAL ON EXPOSED DUCT PER DETAIL 4/M-402. TYP.INSTALL AIR TERMINAL PER DETAIL 3/M-402. TYP.SUPPORT RECTANGULAR DUCT PER DETAIL 2/M-402. TYP.4" DRYER VENT TO EXTERIOR WALL CAP. SEE DETAIL 3/M-403.DASHED AREA INDICATES SERVICE CLEARANCE, TYP.INSTALL CRAC UNIT TO SLAB PER DETAIL 3/M-404.INSTALL CEILING EXHAUST FAN TIGHT TO STRUCTURE PER DETAIL 2/M-404.ARCHITECTURAL RANGE HOOD, SEE ARCH SHEETS. TRANSITION FROM HOOD INLET SIZE TO 8" ⌀ EXHAUST DUCT. ROUTE EXHAUST DUCT THRU ROOF PER
DETAIL 6/M-404.INSTALL VFD ON WALL PER DETAIL 8/M-404.8' STAINLESS STEEL WALL CANOPY HOOD, SIMILAR TO INTER DYNE SYSTEMS WCH-9630-18.WALL MOUNTED THERMOSTAT LOCATED AT 48" TO TOP OF DEVICE AT LOCATION SHOWN. COORDINATE LOCATION WITH ARCHITECT PRIOR TO ROUGH-IN. TYP.NEW TYPE II HOOD, INSTALL PER DETAIL 9/M-404. 123456789
1011121314151617181920
1 NO. DATE DESCRIPTION
1 08/28/2024 PC Comments

BID SET (PRELIMINARY)
A A.5
B
C
E
F
1 2
45 1011
RH
1 RH
2 VRF
A
VRF
B
HP
1D
HP
1E
HEF
1 HEF
2 HEF
3 RH
3 HP
1F
HP
1G
HP
1H
HP
2H
RH
4 RH
5 1
2 22
2 2
2 2
22 1
1 3
33 4
4 4
4 4
5 6
6 6
3 6789
ACCU
1 8
RH
6 4
REF
1 DOAS
B
DOAS
A
DOAS
C
7750 College Town Dr, Ste. 101Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A
F C O
TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:26:42 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt M-221

ROOF PLAN -MECHANICALDCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
1 1/8" = 1'-0" ROOF PLAN - MECHANICAL
N
KEYED NOTES:INSTALL DOAS ON ROOF PER DETAIL 1/M-401. MAINTAIN 10' CLEARANCE BETWEEN OUTSIDE AIR INTAKE AND ANY EXHAUST OR VENTS THRU ROOF.INSTALL OUTDOOR VRF/HP UNIT ON ROOF PER DETAIL 2/M-401. INSTALL HOOD EXHAUST FAN ON ROOF PER DETAIL 5/M-401. INSTALL RELIEF HOOD ON ROOF PER DETAIIL 6/M-401. SUPPORT REFRIIGERANT PIPES ON ROOF PER DETAIL 8/M-402, TYP. SEE 1/M-301 FOR CONTINUATION AND DETAIL 8/M-403 FOR SIZES.REFRIGERANT PIPES THRU ROOF PER DETAIL 7/M-402. INSTALL ACCU ON ROOF PER DETAIL 4/M-404. UNISTRUT SUPPORT FOR HOOD EXHAUST FANS, SEE DETAIL 7/M-404. NEW ROOF EXHAUST FAN, INSTALL PER DETAIL 10/M-401. 123456789
1 1
NO. DATE DESCRIPTION
1 08/28/2024 PC Comments

BID SET (PRELIMINARY)
PH
PH
PH
PH
A A.5
B
C
E
F
1 2
45 1011
FC
1A
FC
2A
FC
3A
DFC
1F
FC
1B
FC
4B
BCC
1 FC
8B FC
5B
FC
6B
FC
7B
FC
9B
FC
10B
FC
2B
FC
3B
FC
1E
FC
1D
DFC
2H
DFC
1H
3 6789
CRAC
1 UPS-1UPS-2

TRANSFORMERS

SWITCHGEAR
1 2
2 3
2 DFC
1G
7750 College Town Dr, Ste. 101Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A
F C O
TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:26:47 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt M-301

REFRIGERANTPIPING PLANDCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
1 1/8" = 1'-0" FLOOR PLAN - MECHANICAL REFRIGERANT PIPING KEYED NOTES:SEE SHEET 8/M-403 FOR REFRIGERANT PIPE SYSTEM DIAGRAM SHOWING SIZES AND TRACKING OF PIPES THROUGH BUILDING. SUPPORT PIPES TIGHT TO STRUCTURE PER DETAIL 9/M-402, TYP.REFRIGERANT PIPES FROM ROOF PER DETAIL 7/M-402. SEE 1/M-221 FOR CONTINUATION.AVOID ROUTING REFRIGERANT ABOVE ELECTRICAL EQUIPMENT, TYP. 123
NO. DATE DESCRIPTION

BID SET (PRELIMINARY)
1/2"
5-1/2"
1-1/2" TYP.

TYPICAL 14 GA STRAP DETAIL

CANT STRIP
24 GA. GALV. SM FLASHINGUNIT BASE RAIL
PREFAB CURB & WOODNAILER- FURNISHED BYHOLD DOWN FABRICATEDRIGID INSULATIONSTEEL.FROM 6" WIDE, 14 GAUNIT MFR.

GASKET - ALL

AROUND UNIT
#10x1" WOOD SCREW W/NEOPRENE WASHER @ 12" 0.C.

MECHANICAL UNIT
ATTACH TO UNIT TO 14
GA STRAP W/ (4) #10 x
1/2" TEK SCREWS
ATTACH TO CURB TO 14 GA STRAP
W/ (4) #10 x 1/2" TEK SCREWS
NOTES:

1. (6) 14 GA STRAPS PER TOTAL - (3) PER LONG SIDE

ROOFING

CURBUNIT
3/8"x5" LAG SCREWS AT24" O.C. INTO BLOCKINGBELOW.

W/ NUT & WASHER@ 12" O.C.

ROOFING
PREFAB CURB W/ FIREPROOF WOOD NAILER2x8 WOOD NAILER(2 PER LEG)1/2"øx3" LAG BOLT CURB SLOPE TO MATCHROOF SLOPE 1/2" THRU BOLT

SHEATHING

ROOFSTRUCTURE
ROOF JOISTS4x4 BLOCKING BETWEEN
@ EA. END, EA. SIDE.JOIST W/ SIMPSON U44ROOF JOIST HUNG FROM4xWOOD BLOCKING BETWEEN 26 GA. COUNTERFLASHING

NEOPRENE GASKET

HEAT PUMP FAN COIL
FCFC
1±0.1
1 3/32"ø PRESTRETCHED GALVANIZED AIRCRAFTCABLE 7x19 STRAND CORE. (1 PER CORNER) WITHMASON SCB AT FAN COIL HOUSING. NOT REQUIREDWHEN FAN COIL IS SECURED WITHIN 12" TO THESTRUCTURE ABOVE. SEE DETAIL 7/M-403. REFRIGERANT PIPE CONNECTIONS. REFER TO MANUFACTURER'S INSTALLATION MANUAL.PRIMARY CONDENSATE POINT OF CONNECTION.REFER TO PLUMBING DRAWINGSSECONDARY CONDENSATE POINT OF CONNECTION.REFER TO PLUMBING DRAWINGS

EQUIPMENT

PLAN VIEW
1±0.1
1 3/32"øPRESTRETCHEDGALVANIZED

AIRCRAFT CABLE
7x19 STRAND CORE.
(4)-3/8"ØHANGER ROD

LOCKING NUTS & WASHERS

AT CORNER MOUNTING
POINTS.

PROVIDE ROD STIFFENERS ONHANGER RODS PER TABLE ONDETAIL 2/M-403 SEE DETAIL 5/M-403 FORUPPER ATTACHMENTDETAILS
SEE DETAIL 5/M-403 FOR UPPER

ATTACHMENT CONDITIONS

LOCKING NUTS & WASHERS

AT CORNER MOUNTING
POINTS.

INLINE EXHAUST FAN
FCFC
PROVIDE ROD STIFFENERS ONHANGER RODS PER TABLE ONDETAIL 2/M-403 1±0.1
1 3/32"ø PRESTRETCHED GALVANIZED AIRCRAFTCABLE 7x19 STRAND CORE. (1 PER CORNER) WITHMASON SCB AT FAN COIL HOUSING. NOT REQUIREDWHEN EXHAUST FAN IS SECURED WITHIN 12" TOTHE STRUCTURE ABOVE. SEE DETAIL 7/M-403. EQUIPMENT

PLAN VIEW
1±0.1
1 3/32"øPRESTRETCHEDGALVANIZED

AIRCRAFT CABLE
7x19 STRAND CORE.
(4)-3/8"ØHANGER ROD

1.5 1
HEF
1,2,3

COUNTER FLASHING
ROOF STRUCT.

ALL WELDED DUCT, FOR CONN. TO
HOOD SEE HOOD MFG.DOCUMENTATION.

ROOF CANT STRIP
SECURE W/ 3/8"∅ LAG SCREW THRUCURB FLANGE TO BLOCKING W/ 3"EMBED. TYP. (4) SCREWS PER SIDE.

U44 (TYP. EA. END)4x4 BLOCKING W/ "SIMPSON"

1. FOR ALL FLASHING AND ROOFING SEE ARCHITECTURAL PLANS NOTE:

CURB WITH 3/4" S.M. SCREWS @ 6" O.C.SECURE FAN FRAME TO VENTED

UNDER COUNTER FLASHINGBUILT UP ROOF, RUN UP &
COMBINATION CURB & VENT. CURB ASREQUIRED TO PLACE THIS POINT MIN.7' ABOVE ROOF

SECURE VENTED CURB EXTENSION TO
ADAPTER WITH #10 SHEET METAL SCREWS
@6" O.C. (MIN. 2 PER SIDE)
SECURE ADAPTER TO PREFAB CURB WITH#10x1 1/2" S.M. SCREWS WITH NEOPRENEWASHER @12" O.C. (MIN. 2 PER SIDE)

WOOD SLEEPER ALL AROUND CURBSHAPED TO LEVEL FAN
GUY WIRE TO UNISTRUTSUPPORT, SEE DETAIL 7/M-404 . EQUIPMENT

PLAN VIEW
1 1±

PREFAB METAL CURB WITH WOODNAILER & INSULATION
SEE ARCHITECTURAL PLANSFOR ALL FLASHING AND ROOFINGNOTE:
(E) ROOF
CURB FLANGE TO BLOCKING W/ 3"EMBED. TYP. (4) SCREWS PER SIDE.

U44 (TYP. EA. END)4x4 BLOCKING W/ "SIMPSON"
SECURE W/ 3/8"∅ LAG SCREW THRU
(E) ROOF STRUCT.

CANT STRIPFLASHING(OVERLAP ROOFING MIN 4")20 GA. G.I. FLASHING DUCT
O.C. MIN. 2 PER SIDE1/4"∅ LAG BOLTS 12"SECURE FAN TORUBBER PAD1/4" NEOPRENEWOOD NAILER W/

PREFAB METAL CURB WITH WOODNAILER & INSULATION

WOOD SLEEPER ALL AROUNDCURB SHAPED TO LEVEL FAN
10" MINIMUMCEILING ORFLOOR ABOVEMOUNTING BRACKET(BY UNIT MFR.)1/4"ø ALAG SCREWS W/ 2"MIN. PENETRATION IN STUDOF BLK'G, 2 TOP, 2 BOT. +6'-8" AFF MIN
4" x 4" BLOCKING w/SIMPSON A34 TOP &BOTTOM EA. END.

WOOD STUD WALL
4D4D

HIGH WALL FAN COIL
NOTES:

1. SEE STRUCTURAL DRAWINGS FOR BACKING BEHIND MANUFACTURER'S MOUNTING BRACKET.

STEEL BACKING TRACK

INDOOR FAN COIL

METAL STUD WALL
MOUNTING BRACKET(BY UNIT MFR.)
10" MIN.CEILING

BACKING TRACK
MOUNTING BRACKET BY AC UNIT MFR.SECURE TO BACKING TRACK IN WALLWITH MIN (8) #14 x 1-1/2" SMS INPRE-DRILLED HOLES.

ELEVATION (TYPICAL)

PLAN (TYPICAL)

INDOOR FAN COIL
16" MAX
3" MIN
2X BLOCKING SUPPORTING FAN

EXTERIOR WOOD STUD WALL

EXTERIOR LOUVERED WALL CAP
WALL EXHAUST FAN WEF-1INCLUDED FLEXIBLE DUCT 8" ROUND EXHAUST

TERMINAL ON WALL
REF
1 COUNTER FLASHING
ROOF STRUCT.

ROOF CANT STRIP
SECURE W/ 3/8"Ø LAG SCREW THRUCURB FLANGE TO BLOCKING W/ 3"EMBED. TYP. (4) SCREWS PER SIDE.

LUS44 (TYP. EA. END)4x4 BLOCKING W/ "SIMPSON"
NOTE: FOR ALL FLASHING AND ROOFING SEE ARCHITECTURAL PLANS 1/4"Ø LAG BOLTS 12" O.C. MIN. 2 PER SIDESECURE FAN TO WOOD NAILER W/

UNDER COUNTER FLASHINGBUILT UP ROOF, RUN UP &
COMBINATION CURB & VENT. CURB ASREQUIRED TO PLACE THIS POINT MIN.40" ABOVE ROOF

WOOD SLEEPER ALL AROUND CURBSHAPED TO LEVEL FAN

PREFAB METAL CURB WITH WOODNAILER & INSULATION
7750 College Town Dr, Ste. 101Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A
F C O
TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:26:47 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt M-401

DETAILSDCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
1 SCALE: NONE DOAS UNIT ON ROOF DETAIL2 SCALE: NONE HP/VRF UNIT ON ROOF DETAIL 3 SCALE: NONE FAN COIL DETAIL
4 SCALE: NONE INLINE EXHAUST FAN DETAIL5 SCALE: NONE HOOD EXHAUST FAN MOUNTING DETAIL6 SCALE: NONE RELIEF HOOD MOUNTING DETAIL 7 SCALE: NONE DUCTLESS WALL MOUNTED UNIT DETAIL8 SCALE: NONE DUCTLESS WALL MOUNTED DETAIL (METAL STUD)9 SCALE: NONE WALL EXHAUST MOUNTING DETAIL 10 SCALE: NONE REF INSTALLATION DETAIL
1 NO. DATE DESCRIPTION
1 08/28/2024 PC Comments

BID SET (PRELIMINARY)

SECURE STRAP TO DUCT WITH
#10x3/4" SHEET METAL SCREWS, 12"O.C., (MIN 2)
DUCT
SECURE WITH 1/4" BOLT & NUT, TYP.

NOTES:1. DUCT SUPPORT SHALL BE SPACED MAX. 8'-0" AND EACH TURN OF DIRECTION. PROVIDE SUPPORT AT ALL FLEXIBLE CONNECTIONS & DUCT MOUNTED EQUIPMENT.

2. SWAY WIRE MAY BE OMITTED WHEN SECURING TOP OF DUCT WITHIN 12" OF STRUCTURE ABOVE. SWAY WIRE PROVISIONS TO BE USED FOR PROTECTING DUCT FROM SWINGING

TO HIT OTHER DUCTING OR MECHANICAL EQUIPMENT
SEE DETAIL 4/M-403 FOR UPPER

ATTACHMENT

BENT PLATE
12 GA SWAY WIRE
SEE DETAIL 6/M-403 FOR UPPER
1-1/2" WIDE SHEET METAL ATTACHMENTSTRAP @ 8'-0" O.C.
6/M-403
#10x3/4" SELF-DRILLING SMS,2 PER SIDE @ 3" FROM DUCTCORNERS, TYP.

SEE DETAIL 4/M-403
FOR UPPER ATTACHMENTCONDITIONS. (TYP)
12 GA SWAY WIRE

BENT PLATE
DUCT STRAP 1-1/2"x18ga @10'-0"OC
NOTES:

1. SWAY WIRE MAY BE OMITTED WHEN SECURING TOP OF DUCT WITHIN 12" OF STRUCTURE ABOVE. SWAY WIRE PROVISIONS TO BE USED FOR PROTECTING DUCT FROM SWINGING TO HIT OTHER DUCTING OR MECHANICAL EQUIPMENT.

2. SEISMICALLY BRACED DUCTS EXCEEDING 6 SQ FT IN CROSS SECTIONAL AREA SHALL BE SECURED PER DETAIL .

GSM DUCT ELBOW

GSM DUCT ELBOW
FLEXIBLE FIBROUSDUCT. SEE SPECS
12 GA SAFETY WIRE.SEE DETAIL 6/M-403
SHEET METALSCREWS, TYP.

T-BAR CEILING
NOTES:

1. PEEL BACK JACKET AND SECURE TO PLENUMCOLLAR. USE A MIN. OF (3) SHEET METAL SCREWS AND (2) FULL WRAPS OF DUCT TAPE. PULL BACK
JACKET AND APPLY (2) FULL WRAPS OF DUCT TAPE.

ALTERNATE METHOD: BANDING DEVICE OR PANDUIT
STRAP, IN LIEU OF SHEET METAL SCREWS.2. IF A MINIMUM 3 DUCT DIAMETERS OF STRAIGHTRUN IS NOT AVAILABLE ABOVE REGISTER USEPLENUM ABOVE REGISTER.3. FLEXIBLE AIR DUCTS AND CONNECTORS SHALLBE NOT MORE THAN 5 FEET IN LENGTH ANDSHALL NOT BE USED IN LIEU OF RIGID ELBOWS ORFITTINGS PER CMC 603.4.1.4. FOR CONFINED SPACES, USE PLENUM BOX ABOVE DIFFUSER. SEE DETAIL B BELOW.

UNCONFINED SPACEA
12" MINIMUMFLEX DUCT
SUPPLY AIR DIFFUSER.DIFFUSERSURFACE MOUNTED
45°

OUTLET DIMENSIONSSEE PLANS FOR AIRCOUNTER-SUNK SCREW (TYP)

AIR OUTLET

EXPOSED SUPPLYDUCT
1"
COLLAR SHAPE TO FITMAIN DUCT. PROVIDERUBBER GASKET ALL AROUNDTO SEAL MAIN DUCT AIRTIGHT. FASTEN WITH #8S.M. SCREWS AT 6" O.C.(MIN 2 PER SIDE) 22 GA. DUCT COLLAR
8"
AIR OUTLET FRAME + 1/4"

MANUAL VOLUME DAMPER

ROUND DUCT
3-8 4
X
15-26
LARGER
27 &
9-14
1013
7 45°

DIMENSION, INCHES
DIA X

AIR FLOW
DIA

AIR FLOWAIR FLOW

EXHAUST
SUPPLY

EXHAUST

AIR FLOW
SUPPLY
BALANCING DAMPER- MIN OF1 DUCT DIA DOWNSTREAM OFFITTING REFRIGERANT PIPE POINT OF CONNECTION.SEE INSTALLATION INSTRUCTIONS

TYPICAL REF GASLINE CONNECTION

TYPICAL REF LIQUIDLINE CONNECTION
CONDENSATE DRAIN PORT.COORDINATE WITHPLUMBING DRAWINGS

CLEARANCE ZONES
12" 12"
8"
4"
27"

ACCESS POINT

PLAN VIEW

FRONT VIEW

SIDE VIEW
THREADED HANGERRODS, SEE DETAIL 5/M-403. LOCKING WASHING AND NUTS AND CORNERMOUNTING POINTS.

NOTE: PROVIDE ROD STIFFENERS ON HANGER RODS PER TABLE ON DETAIL 2/M-403 Control box

ROOFING

SEE PLANS FOR PIPE SIZE
AND QUANTITY.
8" MAXIMUM WIDTH,LENGTH AS REQ'D
EXTEND ROOFINGTO TOP OF CURB.CANT STRIP
2"
ALL JOINTS WATER-TIGHT.

CROSS BREAK TOP, SOLDER24 GA CAP & PIPING CUT-OUTS.

COVER OF CURB TO FIT SNUGLY
AND TIGHT TO TOP OF CURB.

FILL CURB WITH BATT INSULATION.

ROOF ASSEMBLY
NOTES:

SIDE VIEW
MAINTAIN 2" CLEARANCESADDLE CUT-OUTS, (TYP)
RUBBER GROMMET,PORTION OF CURB.INSTALL ON INNERSIZE TO MATCH PIPE. 2"
BETWEEN EACH PIPE.

SEE ELECTRICAL PLANS FOR POWER
AND CONDUITS.

SEE STRUCTURAL DRAWINGS
THY CURB MODEL TC-218 GA ROOF CURB. NAILTHRU ROOF INTO BLOCKING.

END NAIL BLOCKING, TYP.
2x4 VERT. W/ 2- 16d'S TOJOIST TOP & BOTTOMCHORD, TYP.
2x4 BLOCKING W/LUS 24 TOVERT. EACH SIDE OFPENETRATION
B-LINE CHANNEL W/ WOODSCREWS & WASHER TO 2xBLOCKING & CLAMP TO PIPE 2x4 BLOCKING. BACKNAIL TO PERP BLK. TYP.
#10 SELF TAPPING -CADIMUM PLATED SHEETMETAL SCREWS 8" O.C. (3SIDES) PROVIDE RUBBERGROMMET REFRIGERANT PIPE. SIZE CLAMP FOR OUTSIDEOF INSULATION.

UNISTRUT PIPE CLAMP, LOOSE FIT

ROOF DECK AND SINGLE PLY
TRAFFIC PAD. EXTEND 8"

MINIMUM ALL AROUND
SLEEPER. SECURE TO

ROOF WITH ROOFING
CEMENT

HEX NUTS, WASHER AND
1/2" ALL-THREAD ROD, 2 TYP

HEX NUT

HEX HEAD MACHINE SCREW ANDSQUARE NUT, INCLUDED WITHPIPE CLAMP UNISTRUT P100

HEX NUT AND WASHER
"DURA-BLOK" SUPPORT
12" MAX
USE DB_DSSERIES"DURA-BLOK"CHANNELSUPPORTWITH RISERS
ABOVE 12"

PIPING WITH INSULATIONSPACER
UNISTRUT P1000

PIPE CLAMP
SEE DETAIL 5/M-403 FOR RODUPPER ATTACHMENTCONDITION.
2" MIN.
3/8"ø THREADED ROD
NOTES:1. PROVIDE PIPE SUPPORT AT ALL CHANGES IN DIRECTION.2. HORIZONTAL PIPE SUPPORTS SHALL BE SPACED MAX. 6'-0" O.C.3. FIRE PROTECTION WATER PIPING CANNOT BE SUPPORTED WITH THIS SYSTEM.4. PROJECT MAX LOAD: 8.8 LBS./FT.5. USE A CUSHIONED CLAMP TO PROTECT INTERFACE FROM DISSIMILAR METALS6. AIRCRAFT CABLE MAY BE OMITTED WHEN HANGER ROD LENGTH DOES NOT EXCEED 12" 7750 College Town Dr, Ste. 101Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A F C O TATS N I CA L CH E M
R. N
S
NOR
ROF P

ED RETS
I
GE
R

SS I ONAL
ENG I
N
E
E
R

AE E T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:26:48 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt M-402

DETAILSDCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
1 SCALE: NONE ROUND DUCT SUPPORT DETAIL
2 SCALE: NONE RECTANGULAR DUCT MOUNTING DETAIL
3 SCALE: NONE DIFFUSER INSTALLATION DETAILS
4 SCALE: NONE EXPOSED DUCT TERMINAL DETAIL5 SCALE: NONE ROUND DUCT TAP DETAIL 6 SCALE: NONE BRANCH CIRCUIT CONTROLLER DETAIL
7 SCALE: NONE REFRIGERANT PIPE THRU ROOF DETAIL
8 SCALE: NONE REFRIGERANT PIPES ON ROOF
9 SCALE: NONE PIPE HANGER TRAPEZE SUPPORT
NO. DATE DESCRIPTION

BID SET (PRELIMINARY)

WOOD FRAMED WALL
SECURE FRONT COVER, THRU SURFACEMOUNTING FRAME, TO BACKBOX WITHPROVIDED SCREWS BY MFR. (2 TOTAL, TOP

AND BOTTOM)
NOTE:

1. MAINTAIN CLEARANCES: 4.5" ON SIDES AND 12" ON TOP AND KEEP ALL COMBUSTIBLES AWAY FROM HEATER. SEE MFR INSTALLATION INSTRUCTIONS.

2. MOUNT UNIT AT AND FIELD PROVIDED THERMOSTAT +48" TO TOP OF UNIT IN FIRE RISER ROOM.

PROVIDE HORIZONTAL WOOD BLOCKING
BETWEEN WALL STUDS. SECUREBLOCKING SIMILAR TO 1/M6.01

SURFACE MOUNTING
ADAPTER PROVIDED BY MFR.

SECURE SURFACE MOUNTING

ADAPTER TO BLOCKING WITH
(2) 3/8"ø x 3" LAG SCREWS ONEACH SIDE - FIELD PROVIDED

SECTION VIEW
ELECT5RIC HEATER, EH-1, WITH BACK BOX,SURFACE MOUNTING FRAME AND FRONTCOVER UNISTRUT P2486
ROD
SIZE (IN.)
MAX

STIFFENER
LENGTH
(IN.)
MAX

SPACING
(IN.)
MAX

UNBRACED
LENGTH
(IN.)
1-3/16"
1-1/4"
1/2"x1-1/2" x 13 UNCLOCKING BOLT
THREADED RODUNISTRUT P1000
3/8"1/2"5/8"3/4"
156"156"156"156"
28"38"48"57"
18"25"31"37"
7/8"ø RL1-1/8"ø RS1-1/8"ø RHL
1/4"ø RL
1/2"ø RS
1/4"ø RL
1/2"ø RS
1/4"ø RL
1/2"ø RS
1/4"ø RL
1/2ø RS
3/8"ø RL
5/8"ø RS
1ST FLOOR
3/8"ø RL
5/8"ø RS
1/4"ø RL
1/2"ø RS
1/4"ø RL
1/2"ø RS
1/4"ø RL
1/2"ø RS
3/8"ø RL
5/8"ø RS
1/4"ø RL
1/2"ø RS
1/4"ø RL
1/2"ø RS
1/4"ø RL
1/2"ø RS
3/8"ø RL
5/8"ø RS
3/8"ø RL
5/8"ø RS
1/4"ø RL
3/8"ø RS
1/4"ø RL
3/8"ø RS
3/8"ø RL
5/8"ø RS
3/8"ø RL
5/8"ø RS
3/8"ø RL
5/8"ø RS
3/8"ø RL
5/8"ø RS
3/8"ø RL
5/8"ø RS
1/2"ø RL
5/8"ø RS
VRF
B
BCC
1 FC
1B
FC
2B
FC
3B
FC
4B
FC
5B
HP
1G
HP
2G
VRF
A
HP
1H
HP
2H
HP
1F
HP
1E
HP
1D
FC
1A
FC
2A
FC
3A
FC
6B
FC
7B
FC
8B
FC
9B
FC
10B
FC
1D
FC
1E
DFC
1F
DFC
1G
DFC
2G
DFC
1H
DFC
2H
ACCU
1 CRAC
1 INTERIOR FACE OF WALL

ESCUTCHEON PLATE

AT INTERIOR WALL

DUCT THRU WALL,

REFER TO PLANS

FOR SIZES
2x BLOCKING

AROUND OPENING

EXTERIOR FACE OF WALL
PANHEAD WOOD SCREWS @ 6" ONCENTER MINIMUM PER 2 SIDES

SM SCREWS OR POP RIVETS
MASTIC

SMALL SLEEVE TO BESOLDERED ALL SEAMS TO BEWATER TIGHT
3/8" THRU BOLT ANDNUT TO BLOCKING
2x4 BLOCKING. SECURE TOFRAMING WITH SIMPSON A34JOIST HANGER, EACH END.

ALTERNATEATTACHMENT

LOCATION FOR THRUBOLTWOODENSTRUCTURAL JOISTS
1-1/2" WIDE SHEET METAL STRAP.GAUGE PER SMACNA HVAC DUCTCONSTRUCTION STANDARDS.

ALTERNATEATTACHMENT

LOCATION

WOODENSTRUCTURAL JOISTS
1-1/2"1-1/2"
5"
1-1/8"
1-1/8"
4x4 BLOCKING. SECURE TOFRAMING WITH SIMPSON A35JOIST HANGER, EACH END.

DOUBLE NUT WITH LOCKWASHER
(2) 1/2" THRU BOLTS ANDLOCK WASHERS
3/8"ø HANGER ROD
1 1±
2x4 BLOCKING. SECURE TOFRAMING WITH SIMPSON A34JOIST HANGER, EACH END.

ALTERNATEATTACHMENT

LOCATIONWOODENSTRUCTURAL JOISTS
1/4"ø x1-1/2" LAG SCREWINTO BLOCKING
CABLE CLAMP &(4) TIGHT TURNSEACH END
UNISTRUT P1546
12 GA WIRE
2x4 BLOCKING. SECURE TOFRAMING WITH SIMPSON A34JOIST HANGER, EACH END.

ALTERNATE ATTACHMENT
LOCATION FOR 3/8"ø THRU BOLT,LOCKING NUT AND WASHERSWOODEN 30-45° STRUCTURAL JOISTS
3/32"ø PRESTRECHED AIRCRAFTCABLE 7x19 STRAND CORE @45°. 20 FT MAXMASON IND. N.Y. BRACKET FOR

AIRCRAFT CABLE BRACING
UNISTRUT P1843 W/3/8"ø x 3" LAG BOLT INTOBLOCKING 7750 College Town Dr, Ste. 101 Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A
F C O
TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:26:48 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt M-403

DETAILSDCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
1 SCALE: NONE ELECTRIC WALL HEATER DETAIL
2 SCALE: NONE ROD STIFFENER DETAIL
8 SCALE: NONE REFRIGERANT PIPING DIAGRAM
3 SCALE: NONE WALL CAP DETAIL
4 SCALE: NONE METAL STRAP UPPER ATTACHMENT5 SCALE: NONE HANGER ROD UPPER ATTACHMENT 6 SCALE: NONE 12 GA WIRE UPPER ATTACHMENT7 SCALE: NONE AIR CRAFT CABLE UPPER ATTACHMENT NO. DATE DESCRIPTION

BID SET (PRELIMINARY)
System No. W-L-7042

SECTION A-A

1. Wall Assembly — The 1 or 2 hr fire rated wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400, V400 or W400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features.

A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and spaced 24 in. (610 mm) OC.

B. Gypsum Board* — For 1 hr assembly, one layer of min 5/8 in. (16 mm) thick wallboard as required in the individual Wall and Partition Design.

For 2 hr assembly, two layers of min 5/8 in. (16 mm) thick wallboard as required in the individual Wall and Partition Design. Max diam of opening is 14-1/2 in. (368 mm) for wood stud walls and 21-3/4 in. (552 mm) for steel stud walls.

The hourly F and FH Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed.

2. Through Penetrant — Galv steel duct to be installed concentrically or eccentrically within the firestop system. The annular space between the duct and periphery of opening shall be 0 in. (0 mm, point contact) and max 1-1/2 in. (64 mm) Duct to be rigidly supported on both sides of wallassembly.

A. Spiral Wound HVAC Duct — Nom 20 in. (502 mm) diam (or smaller) No. 24 MSG (or heavier) galv steel spriral wound duct.

B. Sheet Metal Duct — Nom 12 in. (305 mm) diam (or smaller) No. 28 MSG (or heavier) galv sheet steel duct.

3. Fill, Void or Cavity Material*—Sealant — Min 5/8 in. (16 mm) and 1-1/4 in. (32 mm) thickness of fill material applied within annulus, flush with both surfaces of wall assembly for 1 or 2 hr rated walls, respectively. At the point contact location between duct and wallboard, a min 1/2 in. (13 mm) diam bead of sealant shall be applied at the wallboard/duct interface on both surfaces of wall assembly.

HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP601S Elastomeric Firestop Sealant, FS-ONE Sealant, FS-ONE MAX Intumescent Sealant or CP606 Flexible Firestop Sealant
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

A
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.

January 27, 2015
A
1A
3 2
3 1B
ANSI/UL1479 (ASTM E814) CAN/ULC S115
F Ratings - 1 and 2 Hr (See Items 1
and 3)
F Ratings - 1 and 2 Hr (See Items 1
and 3)
T Rating - 0 Hr FT Rating - 0 Hr
FH Ratings - 1 and 2 Hr (See Items 1
and 3)
FTH Rating - 0 Hr

CLASSIFIED
R
Classified by
Underwriters Laboratories, Inc.
to UL 1479

CLASSIFIED
R
Classified by
Underwriters Laboratories, Inc.
to UL 1479
Hilti Firestop Systems
3"
SKIRT8" MIN.
2x6 BLOCKING ALL AROUNDOPNG. BTWN. ROOF TRUSS W/ 34HANGERS EA. SIDE, EA. END.TAPED FLEXCONNECTIONBACKDRAFT DAMPER GRILLE
22 GA. GALV. S.M. ROOFHOOD - PAINT TO MATCHROOFING
1/4" MESHGALV. SCREEN
ROOFINGROOF CONST.

FINISHED CEILING#10 X 1 1/2" WOOD SCREWS,IF BLOCKING IS USED. (TYP.2 PER SIDE) 12 GA. X 1 1/4" LONG ROOFINGNAIL, MIN. (2) PER SIDE. SEALWATER TIGHT WITH SILICONESEALANT.

NOTE: MAINTAIN A MINIMUM 10'-0" CLEARANCE FROMOUTSIDE AIR INTAKES TO EXHAUST. 2x CEILING FRAMINGMEMBERS

CONCRETE SLAB

CRAC UNIT HOUSING
1/2"Øx2" EMBED. HILTIKB-TZ2, TYP OF (1) AT EA.GUSSET AT EA. CORNER 24 GAUGE SHEET METALDRIP PAN BELOW UNIT. SEAL

ALL PENETRATIONS
THROUGH PAN WATERTIGHT. PROVIDE LIQUI-TECTPOINT LEAK DETECTIONSENSOR.

ANCHOR TO SUPPORT CURB
PER SECTION BELOWTHYBAR EQUIPMENT MOUNTINGSUPPORT #TEMS2, 12" HIGH, 18GAUGE GALV. STEEL SHELL, BASEPLATE AND COUNTERFLASHING,WITH NAILER, ALL WELDEDCONSTRUCTION.

FLEX. COUPLING (TYP)

PIPE SUPPORT ON ROOF
REFER TO 5/M404 FOR

ANCHORAGE OF UNIT

TO CURB
18"TALL EQUIPMENTSTAND LEG, BY MFR.(TYPICAL OF 4 LEGS)
LIQUID & HOT GAS LINES. SIZEPER AIR COOLED CONDENSERSCHEDULE ON M001 INVERTED TRAPS ON RL&HGLINES TO EXTEND MINIMUM 7
- 1/2" ABOVE BASE OF COIL.
- 1. TYPICAL FOR EACH LEG.

2. COORDINATE WITH MANUFACTURER'S RECOMMENDED PIPING DIAGRAMS PRIOR TO ORDERING OR FABRICATION OF ANY PIPING. DIAGRAM ISINTENDED FOR REFERENCE ONLY.

3. CURB ANCHORAGE DETAIL, SEE 5/M404.

ELECTRICAL
UNIT WEIGHT: 468 LBS
3"MIN.

ACCU
1 W/ NUT & WASHER@ 12" O.C.

ROOFING
PREFAB CURB W/ FIREPROOF WOOD NAILER2x8 WOOD NAILER(2 PER LEG)1/2"øx3" LAG BOLT CURB SLOPE TO MATCHROOF SLOPE 1/2" THRU BOLT

SHEATHING

ROOFSTRUCTURE
ROOF JOISTS4x4 BLOCKING BETWEEN
@ EA. END, EA. SIDE.JOIST W/ SIMPSON U44ROOF JOIST HUNG FROM4xWOOD BLOCKING BETWEEN 26 GA. COUNTERFLASHING

NEOPRENE GASKET
3"
MIN. 3" ALL AROUND

EXHAUST ROOFCAP
1/8" MESH BIRD ANDSPARK SCREEN

ROOFING MATERIAL(BY GENERAL CONTRACTOR)

SEAL WEATHER-TIGHT ALL

AROUND WALL CAP PERARCH DRAWINGS

PLYWOOD SHEATHINGMTL SEAM ROOF

EXHAUST DUCT
SHEET METAL STRAP, ATTACHTO STRUCTURE WITH #10x1 1/2WOOD SCREWDUCT CLAMP

WOOD FRAMING PERSTRUCTURAL DRAWINGS
SECURE 1/2"øx2" EYEBOLTTO CHANNEL NUT W/SPRING
GUY WIRES, 3 REQUIRED.SECURE TO UNISTRUTSTRUCTURE. LOCATETURNBUCKLES AND SAFETYSPRINGS @ ANCHOR. SPRINGSEQUAL TO KELLEMS #203-02-001(GRAINGER #6D262). 5 1_
2 "
6x10 PT (FLAT)
DAP NAILER 1" @BOLT
20" I-JOIST@32"O.C.
4x4 BLOCKING LUS44, TYP

FILL COUNTER SUNKHOLE W/ MASTIC
CANT STRIP ALL (4)SIDES
24 GA G.I. FLASHING CAP SOLDER

ALL JOINTS WATER TIGHT

SET BASE PLATE IN MASTIC
SDS25400 TYP
UNISTRUT P2224
3/8" HEX HEAD SCREWWITH WASHER ANDCHANNEL NUT,TYPICAL.

UNISTRUT P1068
END CAP, TYP.

UNISTRUT P2072A SQ

TOP VIEW

SIDE VIEW
UNISTRUT P1065

HEF HEF HEF
UNISTRUT P2224

AVOID INSTALLING POST

IN FRONT OF EXHAUSTFAN MOTOR COVER

WEB STIFFENER ATLOCATION OF HANGER,SEE STRUCTURAL
5'
SECURE 3/4" PLYWOOD TO FRAMINGPER STRUCTURAL PLANS.METAL STUD WALLSECURE MOUNTING PLATE TOPLYWOOD BACKING WITH #12WOOD SCREWS (TYP.)WALL MOUNTED VFD

PROFILE VIEW
1/2"∅ M.B.(TYP OF 2)

ROOF SHTG

ROOF MEMBER
1 1/4"
5"
1 1/2" 1 1/2"
1 1/4"
2"
3" MIN.

ANGLE 3x3x3/8

DETAIL A

END VIEW FRONT VIEW
(E) STUD, TYP
#10 SMS TO MTL STUDSOR #10 WOODSCREWS TOWOOD STUDS. PREDRILLSTRUT, IF NECCESSARY.

ATTACH STRUT TO MIN. 2
(E) STUDS.

PIPE CLAMP

HANGER ROD
P100 STRUT
P111 PIPE CLAMP

AROUND HANGER
ROD

HANGER ROD
STUD

DETAIL B

END VIEW FRONT VIEW
6" MIN.

ALL AROUND
A
- TYP. 4 PLACES
B
- ROOF STRUCTURE
TYP. 2 PLACES ATCORNERS OF HOOD.
12"ø DUCTCOLLAR
(4)
1/2" HANGER
RODS FOR HOOD.
24"
80"

DRAIN FULLPERIMETERGUTTER

FINISHED FLOOR

EQUIPMENT BYOTHER
3"

COUPLER
H
1 7750 College Town Dr, Ste. 101Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A
F C O
TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:26:49 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt M-404

DETAILSDCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
1 SCALE: NONE DUCT THRU RATED WALL DETAIL2 SCALE: NONE CEF MOUNTING DETAIL 3 SCALE: NONE CRAC UNIT ANCHORAGE DETAIL
4 SCALE: NONE ACCU ANCHORAGE AND PIPING DETAIL5 SCALE: NONE ACCU ANCHORAGE DETAIL6 SCALE: NONE KITCHEN EXHAUST THRU ROOF 7 SCALE: NONE HEF UNISTRUT SUPPORT DETAIL8 SCALE: NONE VFD ON WALL DETAIL9 SCALE: NONE TYPE II INSTALLATION DETAIL 1 NO. DATE DESCRIPTION
1 08/28/2024 PC Comments

BID SET (PRELIMINARY)
SA DX
/
/
/
E
H
SF-1
OSA
FILTER
/
R C G Y1 O/B Y2 W2
Unit TB
SA-1 SD

PELICAN

ROOM TEMPERATURE
72°F
Touch to adjust
TC3

POWER BY
E.C.

FACTORY

CONTROLLER
DOAS

DOAS SHALL BE ORDER WITH

FACTORY INTEGRATED

CONTROLS AND STANDARD
24VAC CONTROL TERMINAL

BOARD FOR CONVENTIONAL

THERMOSTAT CONNECTION

SEQUENCE OF OPERATION
GENERAL:

THE NETWORK THERMOSTAT SHALL BE PROGRAMMED AS
DIRECTED BY THE OWNER FOR OCCUPIED PERIODS,UNOCCUPIED PERIODS AND HOLIDAYS. DURING PERIODS OF

OCCUPANCY, THE SUPPLY FAN SHALL BE ENABLED AND STAGED

HEATING OR COOLING SHALL BE PROVIDED TO MAINTAIN
TEMPERATURE SETPOINT. THE OUTSIDE AIR DAMPER SHALL
MODULATE FULLY CLOSED WHENEVER THE UNIT IS DISABLED.

COOLING:ON A CALL FOR COOLING, STAGES OF DX COOLING SHALL BE ENABLED TO MAINTAIN ROOM COOLING SETPOINT.

HEATING:

ON A CALL FOR HEATING, STAGES OF HEATING SHALL BE ENABLED TO MAINTAIN ROOM HEATING SETPOINT.

SAFETIES:

THE DUCT SMOKE DETECTOR(S) SHALL BE HARD WIRED TO STOPTHE EQUIPMENT WHEN PRODUCTS OF COMBUSTION ARE DETECTED IN THE AIR STREAM. PROVIDED BY ELECTRICAL CONTRACTOR (E.C.)INSTALLED BY MECHANICAL CONTRACTOR (M.C.)

TO CORRESPONDING UNIT

COMMUNICATION
CABLE
DAIKIN
CoolCast-24-DK
Conventional
24vac
Thermostat
Communication
Adapter
SA
FC
(INDOOR UNIT)
RA
D
X
FILTER SF-1
BCC
VRF
(OUTDOOR UNIT)
POWER
BY E.C.

POWER
BY E.C.

Daikin VRF Controller
(If Required)

TO NEXT UNIT
COMM
CABLE
RCD

PELICAN

ROOM TEMPERATURE
72°F
Touch to adjust
GWY Y2W2
POWER
BY E.C.

XF1
24VAC

POWER BY
ELEC.
24V
RH
G2
Y
W2
W
G1
CC
G3
P1 P2
SA-1
PELICAN TA1
RCD
TC3
SEQUENCE OF OPERATION:

VRF INDOOR UNITS:

GENERAL:

THE PELICAN NETWORK THERMOSTAT SHALL BE

PROGRAMMED AS DIRECTED BY THE DISTRICT FOR

OCCUPIED

PERIODS, UNOCCUPIED PERIODS AND
HOLIDAYS.COORDINATE WITH DISTRICT REPRESENTATIVEFOR NETWORK

SETTINGS, OCCUPANCY SCHEDULES, SETPOINTS, SETBACK,
ETC. DURING PERIODS OF OCCUPANCY, THE SUPPLY

FAN SHALL BE ENABLED AND STAGED HEATING OR COOLING

SHALL BE PROVIDED TO MAINTAIN ROOM
TEMPERATURE SETPOINT. PELICAN WIRELESS THERMOSTAT

SHALL COMMUNICATE WITH THE FAN COIL THROUGH
MANUFACTURER’S 24VAC THERMOSTAT ADAPTER.

COOLING:

UPON CALL FROM PELICAN ZONE THERMOSTAT, THE VRF

SYSTEM INTERNAL CONTROL LOGIC ACTIVATES DX

COOLING AS REQUIRED TO MAINTAIN THE ZONE

TEMPERATURE SETPOINT DURING OCCUPIED PERIODS ORTHE

SETBACK TEMPERATURE SETPOINT DURING UNOCCUPIED
PERIODS. AFTER SETPOINT TEMPERATURE IS SATISFIEDDX COOLING DEACTIVATES.HEATING:

UPON CALL FROM PELICAN ZONE THERMOSTAT, THE VRF

SYSTEM INTERNAL CONTROL LOGIC ACTIVATES DX

HEATING AS REQUIRED TO MAINTAIN THE ZONE

TEMPERATURE SETPOINT DURING OCCUPIED PERIODS ORTHE

SETBACK TEMPERATURE SETPOINT DURING UNOCCUPIED
PERIODS. AFTER SETPOINT TEMPERATURE IS SATISFIEDDX HEATING DEACTIVATES.

R
C
D
L
120
N
CD R Y W G W2 Y2
ENC
EAEA
POWER
BY E.C.

PM5
240VAC120VAC
N
1Y 2W 3G 4W2 5Y2

MODULE POWER IN
120VAC(120-N) or
240VAC(L-N)
RM
Low Voltage
Antenna

INCLUDED WITH
PM5 MODULE
MOTOR

STARTER

CONTROL

VOLTAGE
INLINE EXHAUST FAN:

IEF-1 & IEF-2 SHALL RUN WHENEVER DOAS-A UNIT IS RUNNING.

AN ALARM SHALL BE GENERATED AT THE BMS IF THE EXHAUST FAN IS COMMANDED TO RUN AND THE SYSTEM FAILS TO CONFIRM EXHAUST FAN RUNNING STATUS.

Pelican
TA1
R
C
D
T
T

DISTRICT'S INTERNET WAN
CUSTOMER PC w/ BROWSER

PELICAN
SERVER
Pelican
Wireless Systems
WR400
Wireless
Repeater
Power Cable
with AC Adaptor Ethernet Cable
Ethernet (RJ-45)Connector Port
RJ
Router/Hub
RJ
To InternetConnection

FACTORY IP ADDRESS

GATEWAY WILL CONNECT

AUTOMATICALLY TO

PELICAN SERVER AFTER
SERIAL NO. OF GATEWAY

IS REGISTERED ON PELICAN SITE
Go to: https://www.pelicanwireless.com/new-site-setup/
OR
Mobile Device Pelican
Wireless Systems
GW400
Wireless
Gateway
GW
1 ACTUAL QUANTITY AND LOCATIONS
TO BE DETERMINED BY INSTALLER.

PelicanWireless Systems
GW400 Wireless Gateway

PELICAN

ROOM TEMPERATURE
72 °F
Touch to adjust
GW
1 Pelican
Wireless Systems
PEARL

ECONOMIZER

CONTROLLER PELICAN

ROOM TEMPERATURE
72 °F
Touch to adjust

NETWORK
SWITCH
7750 College Town Dr, Ste. 101Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A F C O TATS N I CA L CH E M
R. N
S
NOR
ROF P

ED RETS
I
GE
R

SS I ONAL
ENG I
N
E
E
R

AE E T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:26:49 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt M-501

CONTROLSDCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
1 SCALE: NONE DOAS SYSTEM CONTROL DETAIL3 SCALE: NONE VRF SYSTEM CONTROL DETAIL 2 SCALE: NONE INLINE EXHAUST FAN CONTROL DETAIL
4 SCALE: NONE PELICAN WIRELESS LAN LAYOUT
NO. DATE DESCRIPTION

BID SET (PRELIMINARY)
R C Y1 Y2
TB

OUTDOOR UNIT

TO INDOOR UNIT

WIRE AS NECESSARY
POWER
BY E.C.

PELICAN

ROOM TEMPERATURE
72°F
Touch to adjust
TC3
R C G Y O Y2 W2
SA

SATPOWER
BY ELECT.

TA1
DX
RA
SF
NOTE: DFC-1G AND
CRAC-1 SERVE MDF-133.

DFC-1G SHALL HAVE A

HIGHER TEMPERATURE

SETPOINT TO WORK AS A
BACKUP FOR CRAC-1

SEQUENCE OF OPERATION
GENERAL:

THE NETWORK THERMOSTAT SHALL BE PROGRAMMED

AS DIRECTED BY THE DISTRICT FOR REQUIRE

SETPOINTS AND ALARMS DURING OCCUPIED AND
UNOCCUPIED PERIODS. THE UNIT SHALL ENABLE THE

SUPPLY FAN AND DX COOLING TO MAINTAIN ZONE
TEMPERATURE SETPOINT AS COMMANDED BY THEZONE THERMOSTAT.

COOLING:

ON A CALL FOR COOLING, STAGES OF DX COOLING
SHALL BE ENABLED TO MAINTAIN ROOM COOLINGSETPOINT.

ALARMS:

SAFE TEMPERATURE ALARM SHALL ACTIVATE

ANYTIME THE SPACE TEMPERATURE EXCEEDS THE
DEFINED LIMITS.

SUPPLY SAFE TEMPERATURE ALARM SHALL ACTIVATE

ANYTIME DURING HEATING OR COOLING IF THE
LEAVING AIR TEMPERATURE EXCEEDS THE DEFINEDLIMITS.
(OUTDOOR UNIT)
(INDOOR UNIT)

THIRD PARTY

THERMOSTAT

INTERFACE
XF1
24VAC
20VA
POWER
BY E.C.

PELICAN

ROOM TEMPERATURE
72°F
Touch to adjust
TC1

POWER BY
ELEC.

NOTE: DFC-1H & DFC-2H
SERVE ELECTRICAL-134.

DFC-1H & DFC-2H

THERMOSTATS SHALL

HAVE HEATING LOCKED
OUT. ONE UNTI SHALL

RUN A TIME WITH THE
OTHER AS BACK UP.

SEQUENCE OF OPERATION
GENERAL:

THE NETWORK THERMOSTAT SHALL BE PROGRAMMED AS

DIRECTED BY THE DISTRICT FOR REQUIRE SETPOINTS AND
ALARMS DURING OCCUPIED AND UNOCCUPIED PERIODS. THE

UNIT SHALL ENABLE THE SUPPLY FAN AND DX COOLING OR

HEATING TO MAINTAIN ZONE TEMPERATURE SETPOINT AS
COMMANDED BY THE ZONE THERMOSTAT.

COOLING:ON A CALL FOR COOLING, DX COOLING SHALL BE ENABLED TO MAINTAIN ROOM COOLING SETPOINT.HEATING:

ON A CALL FOR HEATING, DX HEATING SHALL BE ENABLED TO
MAINTAIN ROOM HEATING SETPOINT.

ALARMS:

TEMPERATURE ALARM SHALL ACTIVATE ANYTIME THE SPACETEMPERATURE EXCEEDS THE DEFINED LIMITS. 7750 College Town Dr, Ste. 101Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A F C O TATS N I CA L CH E M
R. N
S
NOR
ROF P

ED RETS
I
GE
R

SS I ONAL
ENG I
N
E
E
R

AE E T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:26:50 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt M-502

CONTROLSDCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP CONSTRUCTION DOCUMENTS 2 SCALE: NONE CRAC UNIT CONTROL DETAIL 1 SCALE: NONE INDOOR FAN COIL UNIT CONTROL DETAIL
NO. DATE DESCRIPTION

BID SET (PRELIMINARY)
SA
D
X
/
/
/
E
H
SF-1
OSA
FILTER
/
R C G Y1 O/B Y2 W2
Unit TB
SA-1 SD

PELICAN

ROOM TEMPERATURE
72°F
Touch to adjust
TC3

POWER BY
ELEC.

FACTORY

CONTROLLER
DOAS

DOAS SHALL BE ORDER WITH

FACTORY INTEGRATED

CONTROLS AND STANDARD
24VAC CONTROL TERMINAL

BOARD FOR CONVENTIONAL

THERMOSTAT CONNECTION
EAEA
POWER
BY ELEC.

FH-2 EA
EA
POWER
BY ELEC.

EA FH-3EA
POWER
BY ELEC.

HOOD
SWITCH
FH-1

PANELIZED
CUSTOM

PROGRAMMABLE

CONTROLLER EA
EA
POWER
BY ELEC.

VFD
IEF-3 EA
EA
POWER
BY ELEC.

VFD
IEF-4
0-10VDC SPEED SIGNAL
0-10VDC SPEED SIGNAL
HOOD
SWITCH
HOOD
SWITCH
EAEA
POWER
BY ELEC.

MOTOR

STARTER
IEF-5
RT1-AC
RC
Pelican Wireless
24VAC POWER

REMOTE TEMPERATURE

SENSOR FOR TEMPERATURE
AVERAGING.

PANEL PROVIDED BY TOTAL
CONTROL. CONTACT BILL
CARMODY @ (916) 780-5929

SEQUENCE OF OPERATION
GENERAL:

THE NETWORK THERMOSTAT SHALL BE PROGRAMMED AS DIRECTED BY THE OWNER FOR OCCUPIED PERIODS, UNOCCUPIED PERIODS AND HOLIDAYS. DURING PERIODS OF OCCUPANCY, THE SUPPLY FAN SHALL BE ENABLED AND STAGED HEATING OR COOLING SHALL BE PROVIDED TO MAINTAIN TEMPERATURE SETPOINT. THE OUTSIDE AIR DAMPER SHALL MODULATE FULLY CLOSED WHENEVER THE UNIT IS DISABLED.

COOLING:

ON A CALL FOR COOLING, STAGES OF DX COOLING SHALL BE ENABLED TO MAINTAIN ROOM COOLING SETPOINT.

HEATING:

ON A CALL FOR HEATING, STAGES OF HEATING SHALL BE ENABLED TO MAINTAIN ROOM HEATING SETPOINT.

SAFETIES:

THE DUCT SMOKE DETECTOR(S) SHALL BE HARD WIRED TO STOP THE EQUIPMENT WHEN PRODUCTS OF COMBUSTION ARE DETECTED IN THE AIR STREAM. PROVIDED BY ELECTRICAL CONTRACTOR (E.C.) INSTALLED BY MECHANICAL CONTRACTOR (M.C.)IEF-3 & IEF-4:

IEF-3 & IEF-4 SHALL RUN AT FULL SPEED WHENEVER THE DOAS-C IS RUNNING AND THE FUME HOODS (FH-1, FH-2 & FH-3) ARE OFF. IEF-3 SHALL SHUT DOWN AND IEF-4 SHALL SLOW DOWN (AS DETERMINED BY THE AIR BALANCER CONTRACTOR) TO MAINTAIN A SLIGHT NEGATIVE PRESSURE IN THE SPACE WHENEVER ALL 3 FUME HOODS ARE RUNNING. IEF-3 AND IEF-4 SHALL RAMP UP (AS DETERMINED BY THE AIR BALANCER CONTRACTOR) TO MAINTAIN A SLIGHT NEGATIVE PRESSURE IN THE SPACE WHENEVER ONLY ONE OR TWO FUME HOODS ARE RUNNING.

IEF-5:

IEF-5 OPERATION SHALL BE INTERLOCK WITH MUA-C UNIT. IEF-5 SHALL RUN WHENEVER THE MUA SUPPLY FAN IS RUNNING.
7750 College Town Dr, Ste. 101Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A
F C O
TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:26:50 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt M-503

CONTROLSDCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
1 SCALE: NONE LAB AREA CONTROL DETAIL
NO. DATE DESCRIPTION

BID SET (PRELIMINARY)
NOTE: IF YOU END UP WITH A (-) NEGATIVE VALUE, A BOOSTER PUMP WILL BE REQUIRED.

CALCULATION SHEET.IF SO, REFER TO BOOSTER PUMP

COLD WATER CALCULATIONS

DESIGN CRITERIA
Total estimated demand (GPM) from fixture calc sheet:

1. Pressure @ Street Main (Static Pressure -
information can be aquired from the local Water
Purveyor)

2. Pressure loss due to height (from buried
depth below grade to the highest most point
in the system - above ceiling, floor level of a
multi-story building, etc…)
17 3. Pressure loss thru meter (Note: losses may vary from 2 PSI up to 5 PSI - verify meter type and losses with the local Water Purveyor)

4. Pressure loss thru other devices (i.e., BFP) (Note:
losses may vary from 8 PSI up to 15 PSI - verify BFP type and losses with the local Water Purveyor)

5. Total pressure loss (add lines 2, 3 & 4)

6. Pressure required at highest fixture (Note: 20 PSI for a Flush Tank Water Closet and 25 PSI for a Flush Valve
Water Closet)

7. Pressure available for Friction Loss (line1-line 5-line 6)

8. Total developed length of run (Note: Add an addition 25% of total pipe length to account for equivalent
length of fittings and valves).

FRICTION LOSS CALCULATION
from line 7 27.622 PSI X 100 =
from line 8 350
Cold Water Service Required:
2 Water meter size required, based on above demand:-

7.89 PSI/100 ft.
ft. x .434
76 75

7.378 5
10 22.378
25 27.622
350
XXXX
XXXX

PLUMBING GENERAL NOTES
T
OF
HP
MG
SD

PLUMBING LEGEND

AMERICAN DISABILITIES ACT
G
CD
RWL AD
ADA
AFF
AFG
BFF/G
BV
CO
CWR
EWH
FA
FCO
FFE

ABOVE FINISH FLOOR

ABOVE FINISH GRADE

BELOW FINISH FLOOR/GRADE

BALL VALVE

CLEAN OUT

COLD WATER RISER

ELECTRIC WATER HEATER

FROM ABOVE

FLOOR CLEANOUT

FINISHED FLOOR ELEVATION
FM
FSR
GCO G
GR/D
GWH
HWR
IE
MV
OF
P&TRV
PSI
RD
RWL
SOC
SOV
TYP
UF
US
VB
VR
VTR
WCO
WHA
WM

FLOOR MOUNT

FIRE SPRINKLER RISER

GRADE CLEANOUT
GAS

GAS RISER/DROP

GAS WATER HEATER

HOT WATER RETURN

INVERT ELEVATION

MIXING VALVE

OVER FLOW

PRESSURE & TEMP RELIEF VALVE

POUNDS PER SQUARE INCH

ROOF DRAIN

RAIN WATER LEADER

SHUT OFF COCK

SHUT OFF VALVE

TYPICAL

UNDER FLOOR

UNDER SLAB

VALVE BOX

VENT RISER

VENT THRU ROOF

WALL CLEANOUT

WATER HAMMER ARRESTOR

WALL MOUNT

SANITARY SEWER (SS)/ WASTE (W)

SANITARY VENT (V)

COLD WATER (CW)
HOT WATER (140° F) (HW)
HOT WATER RETURN (140° F) (HWR)

COMPRESSED AIR

CONDENSATE DRAIN

DRAIN LINE

GAS (G)

GAS - MEDIUM PRESSURE

GAS - HIGH PRESSURE

RAIN WATER LEADER OVERFLOW (OF)

RAIN WATER LEADER (RWL)

STORM DRAIN (SD)
TEMPERED WATER (110° F) (TW)

SHUT OFF VALVE IN VALVE BOX

ABC ABOVE CEILING R GAS PRESSURE REGULATOR

CD CONDENSATE DRAIN

CW COLD WATER

FB FROM BELOW

HW HOT WATER

GAS PRESSURE REGULATORGPR
V VENT

SS SANITARY SEWER

CHECK VALVE

BALANCING VALVE
UNION

STRAINER & BLOW-OFF VALVE

THERMOMETER

PRESSURE GAUGE

CIRCUIT SETTER

BALL VALVE
PUMP

SAD SEE ARCHITECTURAL DRAWINGS

SMD SEE MECHANICAL DRAWINGS

SPD SEE PLUMBING DRAWING

DI DEIONIZED WATER

LA LABORATORY AIR

LV LABORATORY VACUUM

COTG CLEAN OUT TO GRADE

W WASTE

SD SECONDARY DRAIN

MEDICAL AIR OUTLET (DECK)

MEDICAL GAS OUTLET (DECK)

VACUUM OUTLET (DECK)

MEDICAL AIR OUTLET (WALL/BACK)

MEDICAL AIR OUTLET (WALL/BACK)

MEDICAL AIR OUTLET (WALL/BACK)
T-24 PIPING INSULATION REQUIREMENTS

1. PLANS ARE NOT FOR CONSTRUCTION UNTIL APPROVED BY THE AUTHORITY HAVING JURISDICTION. THE CONTRACTOR SHALL NOT ORDER ANY MATERIALS OR INSTALL ANY EQUIPMENT, PIPING, ETC. UNTIL PLANS ARE APPROVED BY THE AUTHORITY HAVING JURISDICTION.

2. ALL FIXTURES WHITE UNLESS OTHERWISE NOTED.

3. ALL FIXTURES SHALL BE PROVIDED WITH STOP VALVES. VALVES MAY BE IN SUPPLY PIPES OR INTEGRAL WITH SUPPLY FITTINGS.

4. WHERE FLUSHOMETER VALVE CONFLICTS WITH GRAB BARS, CONTRACTOR SHALL MODIFY VACUUM BREAKER TUBE TO ENSURE VALVE AND GRAB BAR ARE ADEQUATELY SEPARATED.

5. CONTRACTOR SHALL COORDINATE ALL PLUMBING LINE LOCATIONS WITH OTHER TRADES.

6. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF FIXTURES AND MOUNTING HEIGHTS.

7. CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS AND PAY ALL COSTS INVOLVED.

8. INSULATE HOT & COLD WATER SUPPLY PIPES, STOPS, P-TRAP AND DRAIN LINE AT EACH ADA LAVATORY AND SINK WITH ANTI-MICROBIAL, SEAMLESS, VANDAL RESISTANT PROTECTIVE PIPE COVER "PROWRAP" OR EQUAL.

9. ALL PIPE PENETRATIONS THROUGH ROOF SHALL BE FLASHED SIMILAR TO VTR'S.

10. ALL SANITARY SEWER VENT PIPE PENETRATIONS THROUGH ROOF SHALL TERMINATE AT A MINIMUM DISTANCE OF 25' FROM ANY FRESH AIR INTAKE.

11. MINIMUM LOCAL CONNECTION SIZES SHALL BE MADE IN ACCORDANCE WITH THE SCHEDULE OF CONNECTIONS.

12. ALL WATER PIPING SIZED IN ACCORDANCE WITH 2022 CPC, APPENDIX A.

13. GAS PIPING SIZED IN ACCORDANCE WITH TABLE 1216.2, 2022 CPC. FOR MBH AND A MAXIMUM LENGTH OF '.

14. ALL WASTE, WATER, FIRE AND STORM DRAIN PIPING SHALL BE STUBBED 5' OUTSIDE BUILDING TO CONNECTION POINT SHOWN. SEE CIVIL DRAWINGS FOR CONTINUATION. CONTRACTOR SHALL MAKE FINAL CONNECTIONS TO SITE PIPING.

15. COORDINATE ALL TRENCHING WITH CONTRACTOR.

16. ALL HOSE BIBBS SHALL BE 3/4" AND MOUNTED AT 12" ABOVE FINISHED FLOOR UNLESS OTHERWISE NOTED. ALL HOSE BIBBS SHALL HAVE A NON-REMOVABLE VACUUM BREAKER.

17. PROVIDE MATERIALS IN ACCORDANCE WITH 2022 CALIFORNIA PLUMBING CODE AND STATE CODE REGULATIONS.

18. SEISMIC SUPPORTS AND BRACING FOR ALL PIPING SHALL BE PROVIDED IN ACCORDANCE WITH 2022 CBC SECTION 1613, LATEST EDITION OF ASCE7; SECTION 13.6.1 AND NFPA 13 STANDARDS FOR SUPPORT AND ANCHORAGE. METHODS AND MATERIALS PUBLISHED BY SMACNA AND APPROVED BY STATE AGENCIES SHALL BE USED.

19. THE CONDENSATE DRAIN RECEPTACLE (CDR) AND ASSOCIATED WASTE AND VENT PIPING IS NOT REQUIRED AT SITES WHERE THE ROOF DRAINS CONNECT TO A STORM DRAIN SYSTEM. CD LINES FROM ROOFTOP MECHANICAL EQUIPMENT MAY SPILL OVER ROOF DRAINS WITH A TURNED-DOWN ELBOW.

20. THE WATER CLOSET CONTROLS (FLUSH HANDLE) MUST BE LOCATED ON THE CLEAR/ WIDE SIDE OF THE ACCESSIBLE WATER CLOSETS.

21. HAZARDOUS AND COMBUSTIBLE MATERIAL LINES (E.G. GAS LINES) GREATER THAN 1" IN DIAMETER AND NON-HAZARDOUS LINES (E.G. WATER LINES) GREATER THAN 3" IN DIAMETER REQUIRE SEISMIC BRACING PER 2022 CBC SECTION 1617A.1.26. ACCEPTABLE SEISMIC BRACING DETAILS INCLUDE THOSE SHOWN IN THE EATON/COOPER B-LINE OPM-0052-13 WITH 2022 REVISIONS OR MASON INDUSTRIES OPM-0043-13 WITH 2022 REVISIONS. CONTRACTOR TO CONFIRM BRACING DETAILS WITH DESIGN TEAM.

22. ANY HORIZONTAL DRAINAGE PIPE SERVING SINKS OR URINALS SHALL BE PROVIDED WITH A CLEANOUT AT ITS UPPER TERMINAL PER CPC 2022 707.4. A CLEANOUT SHALL BE FURNISHED ABOVE THE FIXTURE

CONNECTION FITTING SERVING EACH URINAL, REGARDLESS OF THE LOCATION OF THE URINAL IN THE BUILDING.

23. A CLEANOUT IS REQUIRED ON ALL RAINWATER AND OVERFLOW LEADERS AT THE BASE OF THE LEADER BEFORE IT DROPS BELOW GRADE TO CONNECT TO THE HORIZONTAL DRAIN. CLEANOUTS SHALL ALSO BE INSTALLED ON LEADERS AT INTERVALS NOT TO EXCEED 100 FET IN STRAIGHT HORIZONTAL RUNS, AND FOR EACH AGGREGATE HORIZONTAL CHANGE IN DIRECTION EXCEEDING 135 DEGREES.

DIO DI OUTLET

AO AIR OUTLET

VO VACUUM OUTLET

24. ALL PIPING SHALL BE LABELED AS PER SPECIFICATION 22 05 53.

25. ALL NEW WATER PIPING SHALL BE DISINFECTED PER SPECIFICATION SECTION 22 11 16.

WATER SIZING

ACID WASTE

ACID VENT
AW
AVR 1/2"3/4"1/2"3/4" 1/2"3/4"1/2"3/4"2"1-1/2"2"2"SHSHOWE (1) 2"1-1/2"2"2"TDTRENCH DRAIN
(3)
(1)
3/8"3/8"1/2"2"LAVATORY L
1"2"4"4"WATER CLOSET WC
2"3"3"FSFLOOR SINK S
UR
HB
FD
SS

FIXTURE
SINK
URINAL

FLOOR DRAIN

SERVICE SINK

HOSE BIBB

PLUMBING FIXTURE CONNECTION SCHEDULE
WASTE
SYMBOL

COLD WATER HOT WATER

BRANCH OUTLET VENT TRAP BRANCH OUTLET BRANCH OUTLET
2"
2"
2"
3"
2"
3"
2"
2"
1 1/2"
3"
2"
3/4"
1/2"
3/4"
1/2"
3/4"
3/8"
1/2"
1/2" 1/2
3/4" 1/2"
3"
1-1/2"
1-1/2"
1-1/2"
1-1/2"
1-1/2" 1-1/2"
1-1/2"
1-1/2"1-1/2"
2"
1-1/2"
1-1/2" 1-1/2" 3/4"
1/2"
1/2"
(2)
(2)
DF

ELECTRIC WATER

COOLER/DRINKIING
(FLUSH VALVE)

FOUNTAIN
4"
2"
2"
(1)
EEW 3/4" 3/4"
ESH 1-1/2" 1-1/2"2" 1-1/4" 1-1/2"

EMERGENCY

EYEWASH

EMERGENCY SHOWER

EYEWASH
NOTES:
(1) TRAP PRIMER CONNECTION ONLY WHERE NOTED ON PLANS.
(2) TEMPERED OR HOT WATER ONLY WHERE INDICATED ON PLANS. (3) FLOOR SINKS SERVING FIRE SPRINKLER RISER ROOMS REQUIRE A 6" WASTE AND 3" VENT CONNECTION.

ABOVE 350
251-350
201-250
141-200
105-140 -
40-60
BELOW 40
RANGE (°F)

TEMPERATURE
FLUID

0.32-0.34

0.29-0.32

0.27-0.30

0.25-0.29

0.22-0.28 -

0.21-0.27

0.20-0.26
(IN BTU-INCH

PER HOUR

PER SQUARE
FOOT PER °F

CONDUCTIVITY RANGE
SPACE HEATING AND SERVICE WATER HEATING SYSTEMS (STEAM, STEAM CONDENSATE AND HOT WATER); 250
200
150
125
100

SPACE COOLING SYSTEMS (CHILLED WATER, REFRIGERANT AND BRINE) - 75 50

INSULATION
MEAN
RATING

TEMPERATURE
(°F)

4.5 3.0

2.5 1.5

1.0 0.5

1.0 NOMINAL PIPE DIAMETER (IN INCHES)

0.75 NONRES RES

INSULATION THICKNESS REQUIRED (IN INCHES)
<1

5.0 4.0

2.5 1.5

1.5 0.5

1.5 0.75

NONRES RES
1 TO <1.5 1.5 TO <4

1.0 1.5

1.5 2.0

2.5 4.5

5.0 1.0

1.5 1.5

2.0 3.0

4.5 5.0

1.0 1.5

1.5 2.0

3.0 4.5

5.0 4 TO <8 ≥8

COLD WATER - FT FU'S
3/4"
1"
1-1/4"
1-1/2"
2"
HOT WATER 3/4" 8.0 7.0 4.5 6.0
1" 15.0 11.0 4.5 4.0
1-1/4" 30.0 20.0 4.5 3.0
1-1/2" 46.0 27.0 4.5 2.8
(SIZED PER CPC 2022 - APPENDIX A)
2" 107.0 45.0 4.5 2.0
SIZE FU'S GPM VELOCITY PSI LOSS/100'

8.0 7.0 4.5 6.0

15.0 11.0 4.5 4.0

30.0 20.0 4.5 3.0

46.0 27.0 4.5 2.8
264.0 78.0 7.2 4.0
COLD WATER - FV FU'S 1-1/2" 10.0 27.0 4.5 2.8
2" 53.0 54.0 6.0 3.0
7750 College Town Dr, Ste. 101
Sacramento, CA 95817
Tel (916) 447-2841
www.peterseng.com
Job no.
consulting mechanical and electrical engineers
PETERS
engineering
M31176
EXP. 12/31/25 A E EAL I FORN I A F C O TATS N I CA L CH E M R. N S NOR ROF P ED RETSI GER SS I ONAL ENG I NEER AE E T I CH

23.020
311 VERNON ST
ROSEVILLE, CA 95768
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP
REVISIONS #

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
2/11/2025 1:47:43 PM C:\Users\gsettles\Documents\23.020 Dry Creek WWTP MEP_r22_gsettles.rvt P-001

SYMBOLS AND
NOTES

DCWWTP OPERATIONS

AND LAB BLDG
4/24/18
Author 210015.01
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
Plumbing Sheet List
Sheet Number Sheet Name
FP-201 FLOOR PLAN - FIRE PROTECTION
P-001 SYMBOLS AND NOTES
P-002 PLUMBING SCHEDULES
P-101 SITE PLAN - PLUMBING PHASE 1
P-102 SITE PLAN - PLUMBING PHASE 2
P-200 FLOOR PLAN - PLUMBING FIXTURE

IDENTIFICATION
P-201 FLOOR PLAN - PLUMBING WASTE & VENT
P-202 FLOOR PLAN - PLUMBING WATER & GAS
P-221 ROOF PLAN - PLUMBING
P-301 ENLARGED LAB WATER & WASTE PLANS
P-302 ENLARGED LAB DI WATER, AIR AND VAC
PLANS
P-303 ENLARGED LOCKER ROOM PLANS
P-400 DETAILS
P-401 DETAILS
P-402 DETAILS
P-403 DETAILS
NO. DATE DESCRIPTION

BID SET (PRELIMINARY)

DISHWASHER

CEILING
WALL

FIRE RATED

KITCHEN
HOT AND COLD SUPPLY.

DI WATER.
930-317SAM
HOT AND COLD SUPPLY.

DI WATER.
930-317SAM
MLP200
HOT AND COLD SUPPLY.

DI WATER.
930-317SAM

EQUIPMENT SCHEDULE

DETAILLOCATIONDESCRIPTION/TRIMNUMBERMAKESYMBOL

MECHANICAL
ROOM
132
NBF-36B & G CIRCULATION PUMP, LEAD FREE BRONZE CONSTRUCTION, 10 GPM, 25' HEAD. PROVIDE TIMER KIT AND AQUASTAT.1-1/4" CONNECTION. 3-SPEED OPERATION.WEIGHT: 13.1 LBS ELECTRICAL: 115V. 60 HZ, 270W, 1PHTHERMAL EXPANSION TANK, 2 GALLONS TOTAL VOLUME,0.45 MAXIMUM ACCEPTANCE FACTOR. SECURE WITHHOLDRITE QUICK STRAP #QS-U BRACKET.ELECTRIC WATER HEATER, 70-1/4" HIGH X 28"∅. 100GALLON CAPACITY, 88 GPH RECOVERY AT 80° F. TEMP.RISE, DIRECT VENT. SET AT 140° F.OPERATING WEIGHT. = 1400 LBS.,ELECTRICAL: 15KW, 208V, 1PH, 72.1 AMPS.

DSE-100A MECHANICAL
ROOM
132

MECHANICAL
ROOM
132
THERM-X-TROL ST-5C
A.O. SMITH

PLUMBING FIXTURE SCHEDULE

NUMBERMAKESYMBOL DESCRIPTION/TRIM MATERIALSUPPORT
FLUSH VALVE WATER CLOSET WITH ELONGATED BOWL,TOP SPUD, 16-5/8" RIM HEIGHT.LOW CONSUMPTION SENSOR FLUSH VALVE (1.28 GPF),PROVIDED WITH MANUAL OVERRIDE BUTTON.KOHLER K-4731-C OPEN FRONT WHITE SEAT. PROVIDESUPPLY AND STOP, COMMERCIAL CLOSET CARRIER.MOUNTING HEIGHT PER ARCHITECTURAL PLANS, FLUSHVALVE LEVER ON WIDE SIDE OF STALL.

WC-1 KOHLER FLOOR VIT. CHINA
SLOAN
VALVE
(SENSOR)

BATTERY
OPTIMA
111-1.28

ACCESSIBLE
LOCATION --- WASHOUT URINAL, 3/4" TOP SPUD, 2" THREADED OUTLET.

LOW CONSUMPTION SENSOR FLUSH VALVE (0.125 GPF),PROVIDED WITH MANUAL OVERRIDE BUTTON.PROVIDE COMMERCIAL CARRIER AND WALL CLEANOUT.MOUNTING HEIGHT PER ARCHITECTURAL PLANS.

KOHLER K-4991-ET
BARDON
UR-1 WALL VIT. CHINA

SLOAN SFSM
186-0.125

ACCESSIBLE

VALVE --- (SENSOR)

BATTERY
L-1 K-2209 COUNTER VIT. CHINA
CAXTON
KOHLER
420-T41E2805
ABCP

CHICAGO
FAUCET
(MANUAL)

ACCESSIBLE
LOCKER
RM
L-2 KOHLER WALL VIT. CHINA

ACCESSIBLE
CHICAGO 116.221.AB.1
FAUCET
K-2031 RESTROOM

GREENWICH
(SENSOR)

BATTERY
SH-1 MOEN 3988EP WALL

SERIES --- LOCKER ACCESSIBLE RM
PISTON OPERATED WATER HAMMER ARRESTER. SIZE ASRECOMMENDED BY MANUFACTURER.

SIOUX

CHIEF --- --- LEAD FREE WHA
IMB ICE MAKER CONNECTION BOX, LEAD FREE 1/2" QUARTER WALL TURN BALL VALVE WITH HAMMER ARRESTOR.

AB9700HA ---- WMB GUY WASHING MACHINE BOX: CENTER DRAIN, 1/2" QUARTER TURN BALL VALVES WITH HAMMER ARRESTORS.

SSWB3
GRAY

WALL PVC
RESIN
GUY
GRAY
ZURN CD3P LEAD
FREE
AG SPEEDFLEX AIR GAP FITTING FOR KS-1 MOUNTED ON SINK LEDGE. --- --- --- --- HB ACORN WALL STAINLESS STEEL ROOF ROUGH BRONZE 8126-LF
HOSE BIBB (INTERIOR) W/ INTEGRAL VACUUM BREAKER,STAINLESS STEEL RECESSED BOX WITH KEY.HOSE BIBB (ROOF/EXTERIOR) W/ INTEGRAL VACUUMBREAKER. 8151 --- --- ELMDOR AP ACCESS PANEL. 24" X 24", 16 GAUGE GALVANNEALED STEEL WITH PRIME COAT FINISH. AUTOMATIC CLOSER, SELF-LATCHING, 2" THICK FIRE RATED INSULATION, WELDED PAN TYPE. 1-1/2 HOUR FIRE RATING. FRC 24X24 ELMDOR DW SERIES --- PRIMER COATED PRIMER COATED ACCESS PANEL, 14 GAUGE GALVANNEALED STEEL WITH PRIIME COAT FINISH.

MS-1 28" x 28" x 12" HIGH TERRAZZO CORNER MOP SINK WITH INTEGRAL STAINLESS STEEL CAP, INTEGRAL 3" FLOORDRAIN SUPPLIED WITH REMOVABLE STAINLESS STEELGRID STRAINER. PROVIDE 1453-BB STRAINER AND P-TRAP.PROVIDE ACORN KH36 HOSE WITH WALL HANGER, KMHMOP HANGER WITH 3 SPRING LOADED GRIPS ON BRACKET.WALL MOUNTED H & CW FAUCET WITH VACUUM BREAKERSPOUT WITH PAIL HOOK, WALL BRACE, LEVER HANDLES,PROVIDE SUPPLIES AND STOPS.

ACORN TCR-28 FLOOR PORTLAND CEMENT
(WHITE W/WHITE
CHIPS)
(CORNER)
CHICAGO 897-CP
(FAUCET)

JANITOR
RM 121
POWEREX IBVS0202 DIRECT DRIVEN SYSTEM, 2 HP SYSTEM, ROTARY VANE VACUUM PUMP. VERTICAL TANK MOUNT, 11 SCFM AT19"HgV, AIR COOLED, OIL DRAIN VALVE ASSEMBLY,MOUNTED ON VIBRATION ISOLATORS, 10 MICRON INLETFILTER, FLEXIBLE CONNECTOR. VACUUM RECEIVER RATEDFOR MINIMUM 200 PSIG DESIGN PRESSURE. CHECK VALVEBETWEEN INLET FILTER AND VACUUM PUMP. EPOXY LINED30 GALLON VERTICAL RECEIVER WITH VACUUM GAUGE AND MANUAL DRAIN. EXHAUST FLEX HOSE WITH DRIP LEGAND VALVE.

PURCHASE WITH SPEEDAIRE XDV SERIES TIMED
ELECTRIC AUTO DRAIN. 115VWEIGHT: 326 LBS
ELECTRICAL: 208V, 3PH, 8.0 FLA.

CULLIGAN

EQUIPMENT
ROOM
136
CULLIGAN DEIONIZER SYSTEM, PORTABLE EXCHANGEDEIONIZERS. PROVIDE: CATION RESIN TANK, ANION RESINTANK, MIXED BED POLISHER, 1 MICRON FILTER, RESINTRAP FILTER, WATER QUALITY MONITOR, RESISTIVITYSENSOR AND GAUGES.

KS-1 ELUHAD
281655
ELKAY

CHICAGO
FAUCET
(MANUAL)

STAINLESS
STEEL
1100-E35-
317ABCP

COUNTER
THERMOSTATIC MIXING VALVE, INTEGRAL CHECK VALVES,MOUNTING BRACKET, LEAD FREE, 0.25 GPM MIN. FLOW,LOCKING TEMPERATURE REGULATOR, 3/8" INLETS, 3/8"OUTLET, SET AT A MAX. TEMP. OF 110° F 170-ALF-BP
BRKT

LEONARD

KITCHEN
RM 109

BRACKET

FD FLOOR DRAIN (CONCRETE FLOOR) - SEE PLAN FOR SIZE,
CAST IRON P-TRAP.

ZURN Z415B --- FLOOR DRAIN (TILE FLOOR) - SEE PLANS FOR SIZE, CAS T
IRON P-TRAP.

Z415S
FLOOR DRAIN (COMPOSITION TYPE FLOOR) -SEE PLAN FORSIZE, CAST IRON P-TRAP.

Z415SL
FLOOR DRAIN (EPOXY TYPE FLOOR) -SEE PLAN FOR SIZE,CAST IRON P-TRAP.

Z415BL

CAST IRON

BODY W/

NICKEL-BRONZE
STRAINER --- TP 695-01SIOUX BRASS
CHIEF
TRAP PRIMER VALVE. PROVIDE WITH UNION AND BALL --- VALVE. PROVIDE MANIFOLD AS NECESSARY --- ACCESSIBLE DI
1 VAC
1 LAC
1 ET
1 CP
1 EWH
1 LAVATORY, 20-1/4" X 18-1/4" X 4-1/4, SINGLE HOLE. PROVIDE "CHICAGO" 327-XCP FLAT GRID STRAINER, P-TRAP,SUPPLIES AND STOPS, AND COMMERCIAL FLOOR MOUNTED WALL CARRIER WITH CONCEALED ARMS.

HOT AND COLD SUPPLY, SINGLE HOLE, SENSOR OPERATEDFAUCET, 0.5 GPM, SET TIMER TO 20 SECONDS. USER ADJUSTABLE TEMPERATURE CONTROL MIXER, 6 VOLT LITHIU
M
BATTERY INCLUDED.

SHOWER TRIM, SINGLE FUNCTION HAND SHOWER WITH 30"SLIDE BAR, DOUBLE CHECK VALVE IN HANDLE, 69" HOSE,

1.75 GPM. PROVIDE WITH "MOEN" A721 SERIES DROP ELL
FOR HANDSHOWER, PROVIDE "MOEN" S1001EP SERIES 10"
RAINSHOWER HEAD @ 1.75 GPM, PROVIDE "MOEN" S110
SERIES 14" SHOWER ARM AND FLANGE FOR THESHOWERHEAD. PROVIDE "MOEN" M-CORE 3 SERIES VALVE

TRIM WITH INTEGRATED DIVERTER, TEMPERATURE AND

PRESSURE BALANCE SYSTEM CERTIFIED TO (ASME
A112.18.1/CSA B-125-1, ASSE 1016)

PLUMBING FIXTURE SCHEDULE

NUMBERMAKESYMBOL DESCRIPTION/TRIM MATERIALSUPPORT
EPOXY
RESIN

LOCATION
LAB
RM 112
WB-1 STAINLESS STEEL

EEW/SH STAINLESS
STEEL
FS ------ DECK MOUNTED SINGLE HOLE HOT DECK-MOUNTED TIN-LINED LABORATORY PURE WATER FITTING. 5-1/4" SWING GOOSENECK SERRATED SPOUT. MOUNT TO THE RIGHT OF WITH HANDLE TO OPEN DECK/COUNTER SIDE.

COUNTER
FLOOR
LAB SINK, 27" X 22" X 10" 4 HOLE, 18 GAUGE 304 STAINLESS STEEL. CENTER DRAIN LOCATION, PROVIDE WITH LKAD174OFFSET GRID STRAINER, P-TRAP, SUPPLIES AND STOPS.

DECK MOUNTED SINGLE HOLE HOT

DECK-MOUNTED TIN-LINED LABORATORY PURE
WATER FITTING. 5-1/4" SWING GOOSENECK SERRATED
SPOUT. MOUNT TO THE RIGHT OF WITH HANDLE
TO OPEN DECK/COUNTER SIDE.

COUNTER
WALL
12" X 12" X 8" DEEP, HALF GRATE, DOME STRAINER, ACI
D
RESISTING EPOXY COATED INTERIOR WITH NICKEL BRONZERIM. 2" WASTE CONNECTION. --- LS-1 DURCON CHICAGO FAUCET (MANUAL) 930-317SAM ACCESSIBLE A25 T&S (MANUAL) SS-1 ELKAY CHICAGO FAUCET (MANUAL) 930-317SAM DLSR272210 969-317PLCTF 969-317PLCTF GUARDIAN GBF2150 G6040 ZURN Z-1901-2- KC-2 DF-1 ELKAY LZSTLG8W
SLK

WALL LIGHT GRAY
FINISH

CORRIDOR
RM 118 (SURFACE)
DUAL HEIGHT DRINKING FOUNTAIN AND BOTTLER FILLER.FILTERED, REFRIGERATED, 8.0 GPH OF 50°F, "FLEXI-GUARD" BUBBLERS, ELECTRONIC FRONT AND SIDE
PUSH BUTTONS. ELECTRONIC SENSOR BOTTLER FILLER.PROVIDE MOUNTING FRAME, P-TRAPS, SUPPLY AND ISOLATION BALL VALVE.

ELEC.: 115V, 60Hz, 360W, 6 FLA
HOT AND COLD SUPPLY, 8" CENTERS, L-TYPE SWING
SPOUT, 4" WRIST BLADES, 1.5 GPM AERATOR.

RC J.R. SMITH 3960 --- ROOF CEPTOR, INDIRECT WASTE DRAIN, 8-1/2" ROUND SOLID WATER DAM WITH VANDAL PROOF BOTTOM DOME STRAINER. 2" OUTLET.

ROOF CAST
IRON

TD FLOOR DRAIN (CONCRETE FLOOR) - SEE PLAN FOR SIZE,
CAST IRON P-TRAP. 9" SQUARE HINGED HEAVY-DUTYDRAIN WITH SEDIMENT BUCKET.

ZURN Z513 --- CAST IRON

BODY W/

NICKEL-BRONZE

STRAINER

EXTERIOR

COVERED
SPACE
RM 138
LAB SINK, 18" X 15" X 5" EPOXY-RESIN, CORNER DRAINLOCATION, PROVIDE WITH S03-R GRID STRAINER, P-TRAP,SUPPLIES AND STOPS.

AND COLD WATER MIXING FAUCET. 6" SWING GOOSENECK
SPOUT WITH ATMOSPHERIC VACUUM BREAKER. PROVIDE
WITH DECK PLATE.

AND COLD WATER MIXING FAUCET. 6" SWING GOOSENECK
SPOUT WITH ATMOSPHERIC VACUUM BREAKER. PROVIDE
WITH DECK PLATE.

RECESSED SAFETY STATION WITH DRAIN PAN, EXPOSEDSHOWER HEAD. SHOWER AND EYE/FACE WASH, 16 GAUGESTAINLESS STEEL COMBINATION COVER AND DRAIN PAN ATEYE/FACE WASH. 1"IPS BRASS STAY-OPEN BALL VALVEWITH STAINLESS STEEL "PANIC BAR" ACTUATOR.

THERMOSTATIC MIXING VALVE, SET TO 75 DEGREESFAHRENHEIT OUTPUT TEMPERATURE. (ANSI/ASSE 1071) 48"x29"x14" WASH BASIN, LEFT PORTS 2 HOLES, AND 8"CENTERS. 16 GAUGE 304 STAINLESS STEEL. REAR DRAINLOCATION, PROVIDE WITH 3-1/2" BASKET DRAIN, P-TRAP,SUPPLIES AND STOPS.HOT AND COLD SUPPLY . 8" CENTERS, DECK MOUNT PRE-RINSE UNIT WITH 1.15 GPM SPRAY VALVE, 6"
ADJUSTABLE WALL BRACKET, ADD-ON FAUCET WITH 2.2
GPM 14" L-TYPE SWING SPOUT AND 1/2" INLETS. PROVID
E
SUPPLIES AND STOPS.

STAINLESS
STEEL
LAB
RM 112
WORK
RM 113
LAB
RM 112

EQUIPMENT
ROOM
136

EQUIPMENT
ROOM
136
FOOD WASTE DISPOSER, MULTI GRIND. PROVIDE WITHINSINKERATOR "QUCK LOCK" MOUNTING CONFIGURATION.

EVOLUTION

COMPACT

INSINKERATOR
D-350-MB
K-96057-0

HIGHLINE
FLUSH VALVE WATER CLOSET WITH ELONGATED BOWL, TOPSPUD, 15-1/4" RIM HEIGHT.LOW CONSUMPTION SENSOR FLUSH VALVE (1.28 GPF),PROVIDED WITH MANUAL OVERRIDE BUTTON.KOHLER K-4731-C OPEN FRONT WHITE SEAT. PROVIDESUPPLY AND STOP, COMMERCIAL CLOSET CARRIER.MOUNTING HEIGHT PER ARCHITECTURAL PLANS, FLUSHVALVE LEVER ON WIDE SIDE OF STALL.

KOHLER FLOOR VIT. CHINA
SLOAN
VALVE
(SENSOR)

BATTERY
OPTIMA
111-1.28
WC-2 --- HOT AND COLD SUPPLY , 4" CENTERS, 4-1/4" LEVER HANDLE,

0.5 GPM, 4-5/8" CENTER TO CENTER SPOUT LOCATION,
ANTI-SCALD. (ASSE 1070 CERITIFIED)
K-96053-0

WELLCOMME
LAVATORY, 14" X 17" OVAL, UNDERMOUNT SINK,PROVIDE P-TRAP, FLAT GRID STRAINER AND STOPS.

SINGLE COMPARTMENT UNDERMOUNT SINK, 18-1/2" X30-1/2" X 5-3/8" DEPTH, 18 GAUGE TYPE 304 STAINLESSSTEEL, 8" CENTERS, REAR CENTER DRAIN LOCATION.PROVIDE BASKET STRAINER AND TAILPIECE, P-TRAP,SUPPLIES AND STOP.

THERMOSTATIC MIXING VALVE, INTEGRAL CHECK VALVES,MOUNTING BRACKET, LEAD FREE, 0.25 GPM MIN. FLOW,LOCKING TEMPERATURE REGULATOR, 3/8" INLETS, 3/8"OUTLET, SET AT A MAX. TEMP. OF 110° F 170-ALF-BP
BRKT

LEONARD BRACKET
6-41-48D
GOULDS DIONIZED WATER PUMP. MULTI STAGE, 15 GPM, 126.8FT HEAD.ELEC: 208V, 1HP, 4.1A
DIWP
1 EQUIPMENT
ROOM
136
3SV5GC4
F60N
PUMP INFORMATION CONTACT: KURT ECKROTH, CALHYDRONICS, E: [email protected], 916-315-2001CULLIGAN INFORMATION CONTACT: GREG IBSEN, 916-927-5005, E: [email protected]/ MARK FELTON 800-464-7373E: [email protected] MEDAES INFORMATION CONTACT: MARK PERKINS, 916-709-3505, E: [email protected]

GUARDIAN
ZURN REDUCED PRESSURE BACKFLOW PREVENTER. PROVIDE
WITH FULL PORT BALL VALVES, UNION AND "Y" STRAINER.1-1/4" SIZE.

RPBFP
1 EQUIPMENT
ROOM
136
975XL
GD
OIL-LESS SCROLL LABORATORY AIR, SINGLE POINTCONNECTION, BASE MOUNT, DUPLEX DESSICANT DRYINGSYSTEM WITH PURGE CONTROL, PIPED 3-VALVE BYPASS

ASSEMBLY, ELECTRONIC DRAIN VALVE, LIQUID LEVEL
GUAGE GLASS, SAFETY RELIEF VALVE AND MANUAL DRAINVALVE. V-BELT DRIVEN COMPRESSOR, 3600 RPM, ONEINLET AIR FILTER, INTEGRAL AIR-COOLED AFTERCOOLER,INTEGRATED DRAIN TRAP WITH AUTOMATIC SOLENOIDDRAIN VALVE, INCLUDES FLEX CONNECTOR, SAFETYRELIEF VALVE, ISOLATION VALVE AND CHECK VALVE.PROVIDE WITH HCAI (OSHPD) PRE-APPROVEDSEISMICALLY RESTRAINED ISOLATION. DRYING INCLUDESPREFILTER RATED FOR 0.01 MICRON WITH AUTOMATICDRAIN AND ELEMENT CHANGE INDICATOR. CONTROLSYSTEM INCLUDES TOUCH SCREEN CONTROLS, CIRCUITBREAKER DISCONNECTS FOR EACH MOTOR.WEIGHT: 1,134 LBSELECTRICAL: 460V. 3PH. 2 HP SYSTEM LAS02D-080V-D

BEACONMEDAES
DSN ZURN WALL Z199 DOWNSPOUT NOZZLE, NICKEL BRONZE BODY. DECORATIVE CERAMIC NORTH FACE OF WALL FLANGE AND OUTLET NOZZLE. EXTERIOR

RD/OFD COMBINATION ROOF AND OVERFLOW DRAINS WITH

UNDERDECK CLAMP, SUMP RECEIVER AND CAST IRONDOME

ZURN ROOF CAST
IRON
Z165 ROOF
LAB SINK, 25" X 15" X 10" EPOXY-RESIN, CORNER DRAI
N
LOCATION, PROVIDE WITH S03-R GRID STRAINER, P-TRAP,SUPPLIES AND STOPS.

DECK MOUNTED SINGLE HOLE HOT

DECK-MOUNTED TIN-LINED LABORATORY PURE
WATER FITTING. 5-1/4" SWING GOOSENECK SERRATED
SPOUT. MOUNT TO THE RIGHT OF WITH HANDLE
TO OPEN DECK/COUNTER SIDE.

LS-2 DURCON COUNTER

CHICAGO
FAUCET
(MANUAL)
930-317SAM
969-317PLCTF
AND COLD WATER MIXING FAUCET. 6" SWING GOOSENECK
SPOUT WITH ATMOSPHERIC VACUUM BREAKER. PROVIDE
WITH DECK PLATE.

LAB
RM 112
EPOXY
RESIN
D55

ADVANCE
TABCO
5PR-8D14
211233
2 P-402
4 P-401
4 P-401
4 P-401
2 P-402
2 P-402
1 P-402
1 P-403
7750 College Town Dr, Ste. 101Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A
F C O
TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:38:04 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt P-002

PLUMBINGSCHEDULESDCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
NO. DATE DESCRIPTION

BID SET (PRELIMINARY)
I
I
w
G
G
MH
I I
I
I
I
I
I
I
I
I
I
I I
MH
I
I
I
I
wM
MH
I I
I I I
I
MH
MH
E
I
MH
I
I
I
G
E
I
I
w
I
I
I
SLB
SLB
SLB
G
G.RISER
G
1"RSR
1"RSR
G 1'7" G 2'0"
G 1'8"
G 1'6"
1" G 1'6"
ICV(TYP.)
HB

SIGNAL BOX
E.PANEL
ICV I
C MH
RIM=136.12
MH
I
I I I
I
ICV
(2)E.RISERS

I I I I
E.PANEL
I
ICV(TYP.)
GV(TYP.)
HB
E.PANEL
G.RISER
E.PANEL
HB
ACU
XF
C.BOX
I
E.RISER
I
ICV
I
I
I
I
XF
32"
SAVE
DS
FFE=135.73
DS
COL(TYP.)
CP 6'0"
C
P
6'6"
C
P
9'0"
PP8"PP 6'8"
8"PP 4'0"
PP 4'4"
8"PP 3'6"
PP 3'8"
8"PP 3'8"
PP 2'7"
8"PP 4'0"
EOT
EOT

UN BOX FOD
EOT
EOT
EOT
EOT
EOT
EOT
U
N
M
E
T
AL U
N
M
E
T
AL
2" UN

PVC RSR
UN
METAL
UN
METAL

UN METAL

UN METAL

UN METAL

UN METAL
U
N
3'0"

VISIBLE
TRENCH
U
N
2'6"
U
N
2 6' "
RSRS
RSRS
RSRS
RSR NT
RSR

RSRRSRS
RSR
RSR
RSR
SL 2'8" SL 3'0"
SL 3'0"
E 1'0" E 3'0"
E
3'0"
E
3'0"
SL 1'8"
SL 4'0"
SL 3'0"
SL
2'0"
SL
2'0"
SL 2
0' "
SL 3'0"SL 1'0"
SL 2'6"
SL 3'0"
SL 2'0"
SL 2'0"
E 3'0"
E 4'0"
E 4'0"
E 3'0"
HVE 4'2"
E
3'0"
HVE 2'0"
E
3'0"
E 4'0"
HVE 2'0"
E
3'0"
E
2'0"
E 3'6"E 3'6"
E 1'0"
HVE
3'0"
E
2'9"
HVE
3'3"
E
4'0"
E 4'0"
HVE
3'4"
E
2'4"
E 3'0"
SL
2'0"
SL
2'0"
E 3'0"
HVE
3'6"
HVE 2'4"
HVE 3'6"
E
2'0"
E 4'0"
E 4'3" SL 2'8"
E 5'0"
SL 1'8"
E 3'6"
SL 3'0"
E
5'0"
E 1'7"
SL 3'0"
E
3'0"
E 4'6"
E 4'0"
E 4'0" E 3'0"
RSR
RSRS
T 4'0"
COM 4'0"
COM 4'0"
C
O
M
3 0' "
C
O
M
3 6' "
COM 2'4"
COM 3'0"
C
O
M
3'0"
COM 5'0"
C
O
M
5 0' "
COM 3'0"
C
O
M
4 0' "
AT&T 4'0"
AT&T 3'0"
T
2'4"
T
3'0" T
3'0"
C
O
M
2'3" C
O
M
2'0" C
O
M
2'0"
COM 3'4"
COM 2'0"
COM
1'8"
COM 2'3"
COM
3'8"
COM 3'6"
COM
4'5"
COM 3'0"
COM 2'4"
COM 3'0"
COM
2'0"
COM 4'0"
COM 5'0"
COM 4'0"
C
O
M
5'0" C
O
M
3'0"
T 2'4"
COM 2'6"
COM
3'6"

1.5"RSR
2"RSR

1.5"RSR
1"RSR NT
1"RSR
G
5'0"
3"G
3'0"
3"G 4'6"
E
O
T
G 1'9"

1.5" G 1'1"

1.5" G 2'0"
3'6"
3" G
G 1'3"
G 1'6"
3"G
2'6"
3"G
2'3"
3"G 4'0" 3"G 4'0"
3"G 4'0"
EOT
8"SD
3'7"
8"SD
3'10"
6'0"
3'8"
3'9"
2'5"
2'7"
7'0"
5'0"
3'1"
5'7"
12"S
D
7'4"
N
A
NT
TON
2'5"
FW
EOT
2"RSR
W
EOT
NT TON
NT
2"RSR
1"RSR
NT TON
1'10"
NT TON
1'8"
R
S
R
TW NT
TON 1'8"
NT TON
2'7"
NT
EOT
IRR
2'0"
FW 4'0"
W (P
W) 4'0"
W (U
W) 2'6"
W (P
W) 4'0"
W (U
W) 3'0"
W (P
W) 4'0"
W (U
W) 3'7"
IR
R
2'0"
W (P
W) 4'0"
W (U
W) 4'6"
IR
R 1'6"
IRR 2'0"
W (U
W) 4'0"
W (U
W) 5'0"
IR
R
2'6"
IRR 2'0"
IRR
3'0"
IRR
3'0"
IRR
2'0"
IRR 2'0"
IRR
2'0"
IRR 2'4"
IRR 2'0"
IR
R 1'5"
IRR 2'0"
IRR
1'0"
IR
R 1 0' "
IR
R 1 4' "
IRR 2'0"
W (U
W) 7'0"
W (U
W) 4'6"
IRR 1'7"
W 1'6"
W
1'6"
EOT
2"W 2'4"
W (U
W) 4'6"
2"W 2'2"
W (U
W) 7'0"
W (U
W) 4'0"
FW 3'4"
FW 5'0"
2"W 4'0"
2"W 1'7"
FW 5'0"
2"W 3'6"
2"W
2 0' "
2"W
2 0' "
4"SSCO
4"SSCO
6"SSCOEOT
EOT

SS TANKS
NVP
6"S
S
3'3"
6"S
S
4'6"
6"S
S
6'0" 6"S
S
6'8"
6'0"
9'3" 9'2"
9'3" 6"SS
4"S
S
7 0' "
6"SS 5'5"
5'6"
3'6"
5'6"
5 4' "
24"SS
15'0"
13'10"
13'7"
11'10"
12'8 NA"
U
N
DIA
S
S
T
W
9'0"
10'2" 10'1"
10'0"
12"S
S
9'10"
6'3"
4"S
S
3'6"
(2)4"
SSCO
6"SS
5'10"
8'0"
9'11"
ICV(TYP.)
WV(TYP.)
ICV(TYP.)
ICV(TYP.)
WV
WV
FH
PIV
W.BOX
FDC
WV W.RISER
HB
HB
HB
WV
WV
FH
ICV(TYP.)
WV(TYP.)
W.METER
ICV(TYP.)
ICV
WV
HB
ICV
ICV(TYP.)
ICV
ICV(TYP.)
FH
WV
HB
W.BOX
G.RISER
GV(TYP.)
G.RISER
G.RISER
G.RISER
XF
ACU
XF

GENERATOR
XF
acu
IC E+C BOX
E.PANEL
E.PANEL
E.RISER
E.RISER
E.RISER
EMH
RIM=136.65
EMH
RIM=136.46
E.PANEL
(2)E.RISERS
IC
IC
IC
IC
IC
EMH
RIM=131.84
EMH
RIM=132.71
E.BOX
IC
IC
EMH
RIM=131.98
IC
IC
EMH
RIM=132.70
E.BOX
E.RISER
LIGHT(TYP.)
XF
E+C VAULT
VALVE?
C MH
RIM=136.72
C MH
RIM=133.32
C MH
RIM=134.75
C MH
RIM=134.84
C MH
RIM=132.09
SIG MH
RIM=131.43
MS
16"
18"oak
14"oak
4"
8"
10"oak
6"
8"
22"
12"
12"
4"
24"
8"
22"
6"(6)
10"(4)
2"(3) 8"
MAIN
ST.

P
RIM
A
R
Y
CIR.

P
R
MI A
R
Y
CIR.

T.BOX
2 4
10 13
(E) 3"Ø GAS
U.G.
1 2
3 G
7750 College Town Dr, Ste. 101
Sacramento, CA 95817
Tel (916) 447-2841
www.peterseng.com
Job no.
consulting mechanical and electrical engineers
PETERS
engineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A

F C O TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON ST
ROSEVILLE, CA 95768
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
2/20/2025 9:45:43 AM C:\Users\gsettles\Documents\23.020 Dry Creek WWTP MEP_r22_gsettles.rvt P-101

SITE PLAN -
PLUMBING PHASE 1

DCWWTP OPERATIONS

AND LAB BLDG
4/24/18
Author 210015.01
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
1 1/16" = 1'-0"
SITE PLAN - PLUMBING PHASE 1
SHEET NOTES:

1. ALL EXISTING EQUIPMENT, PIPE ROUTING, VAVLES, ETC., SHOWN ON PLANS

ARE BASED ON AVAILABLE EXISTING DRAWINGS AND LIMITED SITE SURVEYS, AND SHOWN FOR CLARITY ONLY.

KEYED NOTES:

CONNECT NEW 3/4"Ø GAS POLYETHYLENE PIPE TO EXISTING. CONTRACTOR TO VERIFY EXACT POINT OF CONNECTION.

NEW UNDERGROUND NATURAL 3/4"Ø GAS POLYETHYLENE PIPE. LOCATE MINIMUM 24" BELOW SUBGRADE. COORDINATE WITH ALL NEW AND EXISTING UNDERGROUND UTLITIES. SEE SHEEET C3.1.

GAS RISER AT BUILDING. SEE SHEET P-202.
1 2
3 NO. DATE DESCRIPTION
I
I
w
G
G
MH
I I
I
I
I
I
I
I
I
I
I
I I
MH
I
I
I
I
wM
MH
I I
I I I
I
MH
MH
E
I
MH
I
I
I
G
E
I
I
w
I
I
I
SLB
SLB
SLB
G
G.RISER
G
1"RSR
1"RSR
G 1'7" G 2'0"
G 1'8"
G 1'6"
1" G 1'6"
ICV(TYP.)
HB

SIGNAL BOX
E.PANEL
ICV I
C MH
RIM=136.12
MH
I
I I I
I
ICV
(2)E.RISERS

I I I I
E.PANEL
I
ICV(TYP.)
GV(TYP.)
HB
E.PANEL
G.RISER
E.PANEL
HB
ACU
XF
C.BOX
I
E.RISER
I
ICV
I
I
I
I
XF
32"
SAVE
DS
FFE=135.73
DS
COL(TYP.)
CP 6'0"
C
P
6'6"
C
P
9'0"
PP
8"P
P
6'8"
8"P
P
4'0"
P
P
4'4"
8"P
P
3'6"
P
P
3'8"
8"P
P
3'8"
P
P
2'7"
8"P
P
4'0"
EOT
EOT

UN BOX FOD
EOT
EOT
EOT
EOT
EOT
EOT
U
N
M
E
T
AL U
N
M
E
T
AL
2" UN

PVC RSR
UN
METAL
UN
METAL

UN METAL

UN METAL

UN METAL

UN METAL
U
N
3'0"

VISIBLE
TRENCH
U
N
2'6"
U
N
2 6' "
RSRS
RSRS
RSRS
RSR NT
RSR

RSRRSRS
RSR
RSR
RSR
SL 2'8"
SL 3'0"
SL 3'0"
E 1'0" E 3'0"
E
3'0"
E
3'0"
SL 1'8"
SL 4'0"
SL 3'0"
SL
2'0"
SL
2'0"
SL 2
0' "
SL 3'0"SL 1'0"
SL 2'6"
SL 3'0"
SL 2'0"
SL 2'0"
E 3'0"
E 4'0"
E 4'0"
E 3'0"
HVE 4'2"
E
3'0"
HVE 2'0"
E
3'0"
E 4'0"
HVE 2'0"
E
3'0"
E
2'0"
E 3'6"E 3'6"
E 1'0"
HVE
3'0"
E
2'9"
HVE
3'3"
E
4'0"
E 4'0"
HVE
3'4"
E
2'4"
E 3'0"
SL
2'0"
SL
2'0"
E 3'0"
HVE
3'6"
HVE 2'4"
HVE 3'6"
E
2'0"
E 4'0"
E 4'3" SL 2'8"
E 5'0"
SL 1'8"
E 3'6"
SL 3'0"
E
5'0"
E 1'7"
SL 3'0"
E
3'0"
E 4'6"
E 4'0"
E 4'0" E 3'0"
RSR
RSRS
T 4'0"
COM 4'0"
COM 4'0"
C
O
M
3 0' "
C
O
M
3 6' "
COM 2'4"
COM 3'0"
C
O
M
3'0"
COM 5'0"
C
O
M
5 0' "
COM 3'0"
C
O
M
4 0' "
AT&T 4'0"
AT&T 3'0"
T
2'4"
T
3'0" T
3'0"
C
O
M
2'3" C
O
M
2'0" C
O
M
2'0"
COM 3'4"
COM 2'0"
COM
1'8"
COM 2'3"
COM
3'8"
COM 3'6"
COM
4'5"
COM 3'0"
COM 2'4"
COM 3'0"
COM
2'0"
COM 4'0"
COM 5'0"
COM 4'0"
C
O
M
5'0" C
O
M
3'0"
T 2'4"
COM 2'6"
COM
3'6"

1.5"RSR
2"RSR

1.5"RSR
1"RSR NT
1"RSR
G
5'0"
3"G
3'0"
3"G 4'6"
E
O
T
G 1'9"

1.5" G 1'1"

1.5" G 2'0"
3'6"
3" G
G 1'3"
G 1'6"
3"G
2'6"
3"G
2'3"
3"G 4'0" 3"G 4'0"
3"G 4'0"
EOT
8"SD
3'7"
8"SD
3'10"
6'0"
3'8"
3'9"
2'5"
2'7"
7'0"
5'0"
3'1"
5'7"
12"S
D
7'4"
N
A
NT
TON
2'5"
FW
EOT
2"RSR
W
EOT
NT TON
NT
2"RSR
1"RSR
NT TON
1'10"
NT TON
1'8"
R
S
R
TW NT
TON 1'8"
NT TON
2'7"
NT
EOT
IRR
2'0"
FW 4'0"
W (P
W) 4'0"
W (U
W) 2'6"
W (P
W) 4'0"
W (U
W) 3'0"
W (P
W) 4'0"
W (U
W) 3'7"
IR
R
2'0"
W (P
W) 4'0"
W (U
W) 4'6"
IR
R 1'6"
IRR 2'0"
W (U
W) 4'0"
W (U
W) 5'0"
IR
R
2'6"
IRR 2'0"
IRR
3'0"
IRR
3'0"
IRR
2'0"
IRR 2'0"
IRR
2'0"
IRR 2'4"
IRR 2'0"
IR
R 1'5"
IRR 2'0"
IRR
1'0"
IR
R 1 0' "
IR
R 1 4' "
IRR 2'0"
W (U
W) 7'0"
W (U
W) 4'6"
IRR 1'7"
W 1'6"
W
1'6"
EOT
2"W 2'4"
W (U
W) 4'6"
2"W 2'2"
W (U
W) 7'0"
W (U
W) 4'0"
FW 3'4"
FW 5'0"
2"W 4'0"
2"W 1'7"
FW 5'0"
2"W 3'6"
2"W
2 0' "
2"W
2 0' "
4"SSCO
4"SSCO
6"SSCOEOT
EOT

SS TANKS
NVP
6"S
S
3'3"
6"S
S
4'6"
6"S
S
6'0" 6"S
S
6'8"
6'0"
9'3" 9'2"
9'3" 6"SS
4"S
S
7 0' "
6"SS 5'5"
5'6"
3'6"
5'6"
5 4' "
24"SS
15'0"
13'10"
13'7"
11'10"
12'8 NA"
U
N
DIA
S
S
T
W
9'0"
10'2" 10'1"
10'0"
12"S
S
9'10"
6'3"
4"S
S
3'6"
(2)4"
SSCO
6"SS
5'10"
8'0"
9'11"
ICV(TYP.)
WV(TYP.)
ICV(TYP.)
ICV(TYP.)
WV
WV
FH
PIV
W.BOX
FDC
WV W.RISER
HB
HB
HB
WV
WV
FH
ICV(TYP.)
WV(TYP.)
W.METER
ICV(TYP.)
ICV
WV
HB
ICV
ICV(TYP.)
ICV
ICV(TYP.)
FH
WV
HB
W.BOX
G.RISER
GV(TYP.)
G.RISER
G.RISER
G.RISER
XF
ACU
XF

GENERATOR
XF
acu
IC E+C BOX
E.PANEL
E.PANEL
E.RISER
E.RISER
E.RISER
EMH
RIM=136.65
EMH
RIM=136.46
E.PANEL
(2)E.RISERS
IC
IC
IC
IC
IC
EMH
RIM=131.84
EMH
RIM=132.71
E.BOX
IC
IC
EMH
RIM=131.98
IC
IC
EMH
RIM=132.70
E.BOX
E.RISER
LIGHT(TYP.)
XF
E+C VAULT
VALVE?
C MH
RIM=136.72
C MH
RIM=133.32
C MH
RIM=134.75
C MH
RIM=134.84
C MH
RIM=132.09
SIG MH
RIM=131.43
MS
16"
18"oak
14"oak
4"
8"
10"oak
6"
8"
22"
12"
12"
4"
24"
8"
22"
6"(6)
10"(4)
2"(3) 8"
MAIN
ST.

P
RIM
A
R
Y
CIR.

P
R
MI A
R
Y
CIR.

T.BOX
2 4
10 13
BUILDING TO BE DEMOLISHED.

SEE ARCHITECTURAL PLANS.
1 4
1 2
1 1
2 5
7750 College Town Dr, Ste. 101
Sacramento, CA 95817
Tel (916) 447-2841
www.peterseng.com
Job no.
consulting mechanical and electrical engineers
PETERS
engineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A

F C O TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON ST
ROSEVILLE, CA 95768
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
2/11/2
0 2
5 1:4
7:4
7 P
M
C:\U
s
ers\g
s
ettle
s\D
o
c
u
m
e
nts\2

3.0 2
0 Dry
Cre
e
k
W
W
T
P
M
E
P
_r2
2 _
g
s
ettle
s.rvt
P-102

SITE PLAN -
PLUMBING PHASE 2

DCWWTP OPERATIONS

AND LAB BLDG
4/24/18
210015.01Author
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
NO. DATE DESCRIPTION
SHEET NOTES:

1. ALL EXISTING EQUIPMENT, PIPE ROUTING, VAVLES, ETC., SHOWN ON PLANS

ARE BASED ON AVAILABLE EXISTING DRAWINGS AND LIMITED SITE SURVEYS, AND SHOWN FOR CLARITY ONLY.

2. CONTRACTOR SHALL VEIFY EXISTING UNDERGROUND GAS PIPE MATERIAL AND CONTACT ENGINEER.

KEYED NOTES:

NEW 1"Ø GAS PIPE UNDERGROUND. LOCATE A MINIMUM 24" BELOW SUBGRADE. COORDINATE WITH ALL NEW AND EXISTING UNDERGROUND UTILITIES. SEE SHEET C3.1.

CONNECT NEW 1"Ø GAS PIPE TO EXISTING WITH SHUT-OFF VALVE AND VALVE BOX.

CONNECT NEW 1"Ø GAS PIPE TO EXISTING UNDERGOUND.

PROVIDE NEW 3"Ø UNDERGROUND GAS PIPE. LOCATE AT 24" BELOW SUBGRADE.

RECONNECT GAS PIPING FROM PHASE 1 TO NEW GAS PIPING IN PHASE 2. 1 1 1/16" = 1'-0"
SITE PLAN - PLUMBING PHASE 2
2 3
4 DEMOLITION KEYED NOTES:

REMOVE EXISTING UNDERGROUND GAS PIPE AND ALL APPURTENENCES.

INSTALL A NEW PIPE.
1 5

BID SET (PRELIMINARY)
PH
PH
PH
CR
PH
CR
CR
CR
CR
CR
CR
CR
CR
A A.5B C E F
1 2
4 5
10 11
131

BUNK ROOM
130

BUNK ROOM
129

BUNK ROOM
128

BUNK ROOM
127

BUNK ROOM
126

BUNK ROOM
125
CONTROL ROOM 2
118

CORRIDOR
135

FIRE RISER
134

ELECTRICAL
133
MDF
132

MECHANICAL
123

MEN'S LOCKER RM
124

LAUNDRY
122

WOMEN'S LOCKER RM
113

WORK ROOM
136

EQUIPMENT ROOM
112

LABORATORY
111
OFFICE
114
OFFICE
115
OFFICE
116

RECORDS
117

STORAGE
121

JANITOR
118

CORRIDOR
108

OPEN OFFICE
120

RESTROOM
119

RESTROOM
109

KITCHEN
107

CONFERENCE ROOM
106
CONTROL ROOM 1
105
OFFICE
104
OFFICE
103
OFFICE
101

RECEPTION
102

CONFERENCE ROOM
UR-1
WC-1
WC-2 WC-1
WC-1
L-2
WC-1
L-2
KS-1
GD
DF-1
MS-1
WMB
FD
FD
FD FD
FD
FD
FD
AG
IMB
SH-1
SH-1
SH-1
SH-1 SH-1
FD

IMB IMB
L-1 L-1
L-1 L-1
FD
FD
FD WC-2
FD
WB-1
SS-1 EEW/SH
FS
LS-2
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
LS-1
HB
HB
HB
HB
HB
HB
HB
TP
WHA
AP
FD
TP
AP
3 6
7 8
9 FS
TD
UR-1
TP
AP
TP
AP
AP
WHA
AP
FS
138

EXTERIOR COVERED SPACE
TP
FD
137

BREAK ROOM
FD FD
FD
7750 College Town Dr, Ste. 101
Sacramento, CA 95817
Tel (916) 447-2841
www.peterseng.com
Job no.
consulting mechanical and electrical engineers
PETERS
engineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A

F C O TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON ST
ROSEVILLE, CA 95768
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
2/13/2025 3:14:21 PM C:\Users\gsettles\Documents\23.020 Dry Creek WWTP MEP_r22_gsettles.rvt P-200

FLOOR PLAN -

PLUMBING FIXTURE

IDENTIFICATION

DCWWTP OPERATIONS

AND LAB BLDG
4/24/18
210015.01Author
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
1 1/8" = 1'-0"

FLOOR PLAN - PLUMBING FIXTURE IDENTIFICATION
N
SHEET NOTES:

1. SEE SHEET P-201 FOR WASTE AND VENT LAYOUT.

2. SEE SHEET P-202 FOR WATER AND NATURAL GAS LAYOUT.

3. SEE ENLARGED SHEET P-302 FOR AIR, VACUUM AND DI WATER LAYOUT.

4. FOR MODEL TYPES LISTED ON THIS SHEET REFER TO SHEET P-002 ON THE PLUMBING SCHEDULES.

NO. DATE DESCRIPTION

CONSTRUCTION DOCUMENTS

BID SET (PRELIMINARY)
PH
PH
PH
CR
PH
CR
CR
CR
CR
CR
CR
CR
CR
A A.5
B
C
E
F
1 2
45 1011
131

BUNK ROOM
130

BUNK ROOM
129

BUNK ROOM
128

BUNK ROOM
127

BUNK ROOM
126

BUNK ROOM
125
CONTROL ROOM 2
118

CORRIDOR
135

FIRE RISER
134

ELECTRICAL
133
MDF
123

MEN'S LOCKER RM
124

LAUNDRY
122

WOMEN'S LOCKER RM
113

WORK ROOM
136

EQUIPMENT ROOM
112

LABORATORY
111
OFFICE
114
OFFICE
115
OFFICE
116

RECORDS
117

STORAGE
121

JANITOR
118

CORRIDOR
108

OPEN OFFICE
120

RESTROOM
119

RESTROOM
109

KITCHEN
107

CONFERENCE ROOM
106
CONTROL ROOM 1
105
OFFICE
104
OFFICE
103
OFFICE
101

RECEPTION
102

CONFERENCE ROOM
4" SS CIVIL POCI.E. = -7'-0" B.F.G.

FC-2A
FC-1D
FC-1A
FC-1B
FC-4B
FC-9B
FC-10B
FC-1E
FC-8B
FC-5B
FC-6B
FC-7B
FC-2B
FC-3B
4"SS(2.0)
2-WAY COTG
4"SS(70.0)
4"SS
4"FCO
4"COTG
P-301
1 EWH
1 DFC-2H
DFC-1H
DFC-1F
3"VTR
CD

CD CD CD
2 2
2 CD CD
CD
CD
3 6789
P-303
1 4"FCO
4"FCO
3"FCO
CO
CO
1 2
2 2
2 2
2 8
4 4
CO
CD
3/4"CD,ABC
2 2
2 8
5 6
CO
2 2
2 3"VTR(26.0)
2"VTR
2"VR
2"WCO
3/4"CD
3/4"CD
3/4"CD
3/4"CD
3/4"CD
3/4"CD
2"SS
3"V(24.0)
2"V(20.0)
2"V
2"V(2.0)
4"SS(14.0)
4"SS(84.0) 4"SS(86.0)
3"SS
7 3
3/4"CD
137

BREAK ROOM
7750 College Town Dr, Ste. 101Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A
F C O
TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:38:15 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt P-201

FLOOR PLAN -PLUMBING WASTE& VENTDCWWTP OPERATIONSAND LAB BLDG 4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
1 FLOOR PLAN - PLUMBING WASTE & VENT 1/8" = 1'-0"
N
SHEET NOTES:KEYED NOTES:DROP 3/4"CD IN WALL TO SINK TAIL PIECE. SEE DETAIL 3/P-402.CONNECT 3/4"CD TO MECHANICAL EQUIPMENT WITH CLEANOUT. RISE CONDENSATE UP TIGHT TO STRUCTURE AND GRAVITY DRAIN TO DROP. RUN T&PRV TO FLOOR SINK AND SPILL WITH 6" AIRGAP. RUN DRAIN LINE TO FLOOR SINK WITH 1" AIRGAP. SEE DETAIL 5/P-402.PROVIDE CLEANOUT ACCESSIBLE ABOVE T-BAR CEILING.3/4" CD TO RUN DOWN IN WALL, SPILL OVER FLOOR SINK WITH 1" AIRGAP. 2"V TO RUN BELOW WINDOW AND ROUTE AS SHOWN. SEE DETAIL 7/P-400.3/4"CD TO RUN DOWN IN WALL. DAYLIGHT 6" ABOVE MOP SINK WITH TURNED DOWN ELL. TERMINATE 1" ABOVE FLOODRIM OF MOP SINK. DROP 3/4"CD IN WALL AND DAYLIGHT 6" ABOVE GRADE. SPILL OVER LANDSCAPE WITH 1" AIRGAP. 1 1. RUN ALL WASTE AND VENT AT 1/4" PER FOOT SLOPE.2. SEE SHEET P-200 FOR FIXTURE IDENTIFICATION.

3. SEE SHEET
P-202 FOR WATER AND NATURAL GAS LAYOUT.

4. SEE ENLARGED SHEET
P-302 FOR AIR, VACUUM AND DI WATER LAYOUT.

5. FOR DETAILED NOTES NOT LISTED ON THIS SHEET REFER TO ENLARGED PLANS. 2345678
NO. DATE DESCRIPTION

BID SET (PRELIMINARY)
PH
PH
PH
CR
PH
CR
CR
CR
CR
CR
CR
CR
CR
A A.5BCEF
1 245
10 11
131

BUNK ROOM
130

BUNK ROOM
129

BUNK ROOM
128

BUNK ROOM
127

BUNK ROOM
126

BUNK ROOM
125
CONTROL ROOM 2
118

CORRIDOR
135

FIRE RISER
134

ELECTRICAL
133
MDF
123

MEN'S LOCKER RM
124

LAUNDRY
122

WOMEN'S LOCKER RM
113

WORK ROOM
136

EQUIPMENT ROOM
112

LABORATORY
111
OFFICE
114
OFFICE
115
OFFICE
116

RECORDS
117

STORAGE
121

JANITOR
118

CORRIDOR
108

OPEN OFFICE
120

RESTROOM
119

RESTROOM
109

KITCHEN
107

CONFERENCE ROOM
106
CONTROL ROOM 1
105
OFFICE
104
OFFICE
103
OFFICE
101

RECEPTION
102

CONFERENCE ROOM
2"CWR 2"CW CIVIL POC

SOV IN VB
2"CW
132

MECHANICAL
P-301 2
G
G
1 EWH1
DFC-2H
DFC-1H
3/4"HWR
2 ET1
3 4
3 6789
P-303 2
110
OFFICE
2"CW
1-1/2"CW
(10.5)
1-1/2"CW
(19.0)
2 3/4"CW
3/4"HW
1-1/2"CW
3/4"HW
1"HW
(3.75)
(5.0)
1-1/2"HW (36.0)
2"CW (100.0)
2"HW
2"CW
3/4"HWR
(52.0)
(49.5)
F
6"FSR CP1
5 137
BREAK ROOM6 7
1/2"G(72.2 CFH)
8 9
3/4"Ø GAS POLYETHYLENE

PIPE, FOR CONTINUATION

SEE SHEET
P-101.

DEMAND = 178.2 CFH

TOTAL DEVELOPED
LENGTH =440 FT TO THE
METER.
1"G 1"G
1/2"G(72.2 CFH)
1"G
7750 College Town Dr, Ste. 101
Sacramento, CA 95817
Tel (916) 447-2841
www.peterseng.com
Job no.
consulting mechanical and electrical engineers
PETERS
engineering
M31176
EXP. 12/31/25 A E EAL I FORN I A F C O TATS N I CA L CH E M R. N S NOR ROF P ED RETSI GER SS I ONAL ENG I NEER AE E T I CH

23.020
311 VERNON ST
ROSEVILLE, CA 95768
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP
REVISIONS #

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
2/20/2025 9:45:45 AM C:\Users\gsettles\Documents\23.020 Dry Creek WWTP MEP_r22_gsettles.rvt P-202

FLOOR PLAN -

PLUMBING WATER
& GAS

DCWWTP OPERATIONS

AND LAB BLDG
4/24/18
210015.01Author
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
1 1/8" = 1'-0"

FLOOR PLAN - PLUMBING WATER & GAS
N
SHEET NOTES:

KEYED NOTES:

PROVIDE PRESSURE REDUCING VALVE IN VALVE BOX AND SET TO 75 PSI.

PROVIDE LINE SIZED ISOLATION BALL VALVE ACCESSIBLE ABOVE THE T-BAR CEILING.

PROVIDE WATER HAMMER ARRESTOR BEHIND 12" X 16" WALL ACCESS PANEL. MOUNT PANEL BELOW GRAB BAR. PROVIDE WITH ISOLATION BALL VALVE.

DROP 3/4"Ø COLD WATER DOWN WALL TO EXTERIOR HOSE BIB. TEE 1/2"

COLD WATER LINE TO TRAP PRIMER LOCATION AND RUN TRAP PRIMER LINE TO TRENCH DRAIN. MOUNT HOSE BIB AT 30" A.F.G.

REFER TO FIRE SPRINKLER PLANS FOR FIRE SPRINKLER RISER LOCATION.

DROP 1/2"Ø CW TO FEED LAVATORY AND ICE MAKER BOX FOR
REFRIGERATORS. LOCATE IMB AT 24" ABOVE FINISHED FLOOR.

DROP 1/2"Ø CW TO ICE MAKER BOX FOR REFRIGERATORS. LOCATE IMB AT 24" ABOVE FINISHED FLOOR.

DROP 1/2"Ø GAS DOWN IN WALL TO 12" ABOVE FINISHED FLOOR. PROVIDE 1/2" SHUT OFF VALVE AND FLEX PIPE FOR FUTURE CONNECTION TO GAS BURNER. TERMINATE WITH MALE PIPE THREAD FOR CONNECTION TO APPLIANCE PRESSURE REGULATOR.
1"Ø GAS RISER WITH GAS PRESSURE REGULATOR FROM 9.5 PSI TO 7" W.C.

INSIDE THE BUILDING.
12 1. SEE SHEET
P-200 FOR FIXTURE IDENTIFICATION.

2. SEE SHEET
P-201 FOR WASTE AND VENT LAYOUT.

3. SEE ENLARGED SHEET
P-302 FOR AIR, VACUUM AND DI WATER LAYOUT.

4. FOR DETAILED NOTES NOT LISTED ON THIS SHEET REFER TO ENLARGED PLANS.

5. NUMBERS LISTED ON THE PLANS IN PARENTHESIS ARE WATER FIXTURE UNIT VALUES. 3456789 GAS LOAD:

RANGE/STOVE = 72.2 MBH
BUNSEN BURNES = 4 MBH EACH (4 TOTAL)
FUME HOOD = 30 MBH EACH (3 TOTAL)
TOTAL MBH = 178.2 MBH
TOTAL DEVELOPED LENGTH FROM GAS REGULATOR= 220 FEET
2022 CPC TABLE 1215.2
LESS THAN 2 PSI, PRESSURE DROP 0.5 IN W.C.

NO. DATE DESCRIPTION
A A.5
B
C
E
F
1 2
45 1011
VRF-B
VRF-A RH-1
HEF-3HEF-2HEF-1
RH-3

ROOF HATCH
HB
2"VTR
2"AVTR
3"AVTR
3"VTR
3 6789
CO
3"VTR
3"VTR
CD CD
CD
RC
RH-4
RH-2
2 2
2 RH-5
3/4"CD
2"VTR
3"RD/OFD1,084 SQ. FT.
3"RD/OFD1,084 SQ. FT.
3 3
3 SEE ELECTRAL PLANS FOR SOLAR PANEL LAYOUT
7750 College Town Dr, Ste. 101Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A
F C O
TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:38:22 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt P-221

ROOF PLAN -PLUMBINGDCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
N
1 1/8" = 1'-0" ROOF PLAN - PLUMBING
SHEET NOTES:KEYED NOTES:DROP 3/4"CONDENSATE DOWN ROOF CEPTOR INTO CEILING SPACE. SEE SHEET P-301 FOR CONTINUTAION.

CONNECT 3/4" CONDENSATE TO MECHANICAL EQUIPMENT WITH P-TRAP AND CLEANOUT. SEE DETAIL 4/P-402. MAINTAIN 10' CLEARANCE FOR OUTSIDE AIR INTAKE OF ALL VTR LOCATIONS. 12 1

1. LOCATE VENT MINIMUM OF 10' FROM AIR INTAKE.
3 NO. DATE DESCRIPTION

BID SET (PRELIMINARY)
PH
PH
CR
CR
CR
PH
PH
CR
CR
CR E
F
124
113

WORK ROOM
136

EQUIPMENT ROOM
112

LABORATORY
4"SS(46.0)
3"AW(20.0)
4"SS(4.0)
4"GCO
3"AW
WCO
WCO
2"AVTR
2"VTR
2"AVR
2"AVR
2"AVR
2"VR
2"VR
L-EQ-10
3"GCO
DFC
1F
3/4"CD
2"V
3 L-EQ-49
1-1/2"AV(4.0)
12 13
14 2"AW(4.0)
2"AW(6.0)
2"AW
2"AW(8.0)
2"AV
1-1/2"AV(4.0)
1-1/2"AV(6.0)
3"AV, ABC(18.0)
21 21
22 3"AW(24.0) 3"AW(10.0) 3"AW(8.0)
4"SS(24.0)
3"AV (20.0)
4"SS(70.0)
3"SD CIVIL POC
I.E. =-2'-10" B.F.G.
3"SD CIVIL POC
I.E. =-2'-10" B.F.G.
3"RWL
3"OFL
3"RWL 3"OFL
23 24 23 23
25 25
25 1-1/2"AV, ABC 2"AV 2"AV, ABC
26 EF
124
113

WORK ROOM
112

LABORATORY
LAC1
2"CW
1"HW
VAC1
DI 1
1 4
33 887
55956
3/4"HW BG
3/4"CW BG
G
G
GG
2 2
RPBFP 12
2 2
1"CW
3 (8 CFH)
(30 CFH)
(30 CFH)
(30 CFH)
3/4"HW BG
3/4"CW BG
3/4"CW
3/4"CW 21"CW
(10.5)
1"CW
(9.0)
(15 .0)
(15.0)
(15.0)
1"HW
1-1/2"HW
(33.0)
3/4"HW
3/4"CW
1"HW (13.5)
1"HW
(10.5)
3/4"HW
1-1/4"HW
11L-EQ-31
8 8
GG
G
G
16 15
136

EQUIPMENT ROOM
1"ICW
17 18
19 20
DIWP 1
RESIN
TRAP
(72.2 CFH)
1/2"G
3/4"G
1"G
1/2"G
10 1/2"G
1/2"G
1"G
1/2"G
(4 CFH)
(2 CFH)
(2 CFH)
(2 CFH)
3/4"G
7750 College Town Dr, Ste. 101
Sacramento, CA 95817
Tel (916) 447-2841
www.peterseng.com
Job no.
consulting mechanical and electrical engineers
PETERS
engineering
M31176
EXP. 12/31/25 A E EAL I FORN I A F C O TATS N I CA L CH E M R. N S NOR ROF P ED RETSI GER SS I ONAL ENG I NEER AE E T I CH

23.020
311 VERNON ST
ROSEVILLE, CA 95768
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP
REVISIONS #

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
2/20/2025 9:45:50 AM C:\Users\gsettles\Documents\23.020 Dry Creek WWTP MEP_r22_gsettles.rvt P-301

ENLARGED LAB

WATER & WASTE
PLANS

DCWWTP OPERATIONS

AND LAB BLDG
4/24/18
210015.01Author
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
1 1/4" = 1'-0"

ENLARGED LAB PLAN - WASTE & VENT
2 1/4" = 1'-0"

ENLARGED LAB PLAN - WATER & GAS
SHEET NOTES:

KEYED NOTES:

DROP 1"Ø HOT AND COLD WATER DOWN WALL TO BELOW FLOOR AND RUN TO SERVE THE LAB SINKS SHOWN.

PROVIDE LINE SIZED ISOLATION BALL VALVE ACCESSIBLE ABOVE THE T-BAR CEILING.

DROP 3/4"Ø HOT AND COLD WATER DOWN WALL AND RUN HORIZONTALLY

BELOW THE WINDOW TIGHT TO THE BACK OF THE CABINET TO SERVE THE LAB SINK. PIPING TO THE SINK IS SHOWN OFFSET FOR CLARITY. 3/4"Ø COLD WATER RISER TO ROOF HOSE BIBB.
1/2"Ø COLD WATER DROP AND 1/2"Ø GAS DROP DOWN TO FUME HOOD.

PROVIDE END OF LINE WATER CONNECTION WITH SOV. CONNECT GAS TO

OUTLET AT THE FUME HOOD
DROP 1/2"Ø GAS LINE DOWN WALL AND PROVIDE EMERGENCY GAS SHUT

OFF VALVE BEHIND ACCESS PANEL AND RISE GAS BACK UP TO CEILING SPACE TO FEED EACH OUTLET SHOWN ON PLANS. FOR DETAIL SEE 3/P -400.

DROP 3/4"Ø HOT AND COLD WATER DOWN WALL AND TEE TO FEED EACH BACK TO BACK SINK.

DROP 1/2"Ø GAS DOWN WALL AND RUN TO GAS OUTLET TURRET AT THE DECK.

DROP 3/4"Ø HOT AND COLD WATER DOWN WALL AND RUN THROUGH THE

THERMOSTATIC MIXING VALVE AND RUN TO THE EMERGENCY EYE WASH AND EMERGENCY SHOWER. SEE DETAIL 6/P
-400.

FOR CONTINUATION SEE SHEET
P-202.

DROP 1/2"Ø COLD WATER DOWN WALL AND STUB EXPOSED BEHIND EQUIPMENT. PROVIDE 6' MINIMUM OF COILED COPPER TUBING, TO ALLOW FOR EQUIPMENT TO MOVE AWAY FROM WALL. PROVIDE WITH SHUT OFF VALVE AND 1/4"Ø COMPRESSION FITTING FOR CONNECTION TO ICE MAKER. 3/4"Ø CONDENSATE DROP FROM MECHANICAL EQUIPMENT ON ROOF. ROUTE TIGHT TO UNDERSIDE OF STRUCTURE AND GRAVITY DRAIN TO DROP.

SPILL 3/4"Ø CONDENSATE, LAC
-1 DRAINAGE, AND VAC-1 DRAINAGE OVER
FLOOR SINK WITH 1" AIRGAP.

CONNECT 3"Ø ACID WASTE TO 4"Ø SANITARY SEWER.

DROP 1"Ø CW DOWN WALL AND DAYLIGHT TO EQUIPMENT ROOM TO RUN THROUGH RPBFP/1. FOR PIPE SUPPORT ON WALL SEE DETAIL 5/P -401.

DROP AND RUN DRAIN FROM RPBFP/1 TO FLOOR SINK WITH 1" AIRGAP. FOR PIPING DIAGRAM WITH VALVES SEE DETAIL 4/P
-401.
1 MICRON DI WATER PRE-FILTER FOR DI WATER SYSTEM. FOR PIPING DIAGRAM REFER TO DETAIL 4/P
-401.

RISE 1"Ø ICW HIGH ON WALL AND RUN OVER DOORWAY AS SHOWN. FOR PIPE SUPPORT ON WALL SEE DETAIL 5/P
-401.

DROP 1"Ø ICW DOWN WALL AND RUN TO DIP/1. FOR PIPING DETAIL SEE 4/P-401. FOR PIPE SUPPORT ON WALL SEE DETAIL 5/P-401.

DI PIPING IS SHOWN ON ENLARGED PLAN SHEET
P-302. THIS SHEET SHOWS
DOMESTIC COLD WATER PIPING ONLY. FOR CONTINUATION OF WATER PIPING, DI WATER, REFER TO REFERENCED SHEET.

MOUNT DRAIN TIGHT TO WALL AND ROUTE TO SINK.

CONNECT DRAIN FROM
L-EQ-10 AND L-EQ-49 TO SINK TAILBIECE. SEE DETAIL
3/P402.

PROVIDE DSN AT OVERFLOW TERMINATION POINT. REFER TO
ARCHITECTURAL PLANS FOR OVERFLOW SPOUT LOCATION.
3"Ø RAIN WATER LEADER TO DROP IN WALL TO BELOW GRADE. RUN AT 1/4" PER FOOT SLOPE. REFER TO CIVIL PLANS FOR POINT OF CONNECTION. 2"Ø AV FROM ISLAND SINKS DROP TO BELOW GRADE AND ROUTE TO RISER LOCATION. SEE DETAIL 7/P
-400.

ROUTE DRAIN FROM AIR COMPRESSOR AT 1/4" PER FOOT TO FLOOR SINK WITH 1" AIRGAP.
1 N
23456789
10 1. RUN ALL WASTE AND VENT AT 1/4" PER FOOT SLOPE.

2. SEE SHEET
P-200 FOR FIXTURE IDENTIFICATION.

3. SEE OVERALL PLANS
P-201 AND P-202 FOR CONTINUATION OF PIPING LAYOUT.

4. SEE SHEET
P-302 FOR AIR, VACUUM AND DI WATER LAYOUT.

5. NUMBERS LISTED ON THE PLANS IN PARENTHESIS ARE WATER FIXTURE UNIT VALUES.

UNLESS NOTED OTHERWISE IN THE CASE OF NATURAL GAS.

6. ALL LAB EQUIPMNET IS PROVIDED BY OTHERS. FOR EQUIPMENT LAYOUT AND LIST REFER TO ARCHITECTURAL PLANS.
11 12
13 14
15 16
17 18
19 20
21 22
23 24
25 26
NO. DATE DESCRIPTION
PH
PH
CR
CR
CR
PH
PH
CR
CR
CR E
F
124
113

WORK ROOM
112

LABORATORY
LAC
1 LV LV LV
LV
LV
LV
LV
LV
LV
VOAO
LA LA
LA
LA LA
LA
LA
LA
VO
VO
LA
LV
2 AOVOVOAO
AOVO
AOVO
AOVOAO
AO
AOVO
VOAO
VOAO
VOAO
VOAO
VO
VO
AOAOLV
LA
DIWP
1 3
4 44
LV LA
AOVO
AOVO
5 5 TYP.

TYP.
66 7
8 8
2 6
(20% FACTOR - 6.36 CFM)
3/4"LA (5% FACTOR - 1.5 CFM)
1-1/4"LV
1-1/4"LV
1-1/4"LV
1"LV, ABC 1"LV 3/4"LV, BFF
1-1/2"LV
1"LV3/4"LV
6 6
6 13
12 3/4"LA
3/4"LA
3/4"LA, ABC3/4"LA, BFF
3/4"LA, ABC
1/2"LA, BFF
3/4"LA
1-1/4"LV
LA
1-1/4"LV 3/4"LA
1"LV, ABC
1"LV
3/4"LA
3/4"LV
7 7
7 7
7 477
7 6
6 66
1"LV, BFF
3/4"LV
1/2"LA
3/4"LV
1/2"LA
3/4"LV
1/2"LA
1/2"LA3/4"LV
1/2"LA1/2"LA
1/2"LA3/4"LV3/4"LA
14 VAC
1 E
F
124
113

WORK ROOM
112

LABORATORY
DI
DI
DI DI
DI
DI
DIDI
1"DI
1"DI
DI
1"DI
1 L-E
Q-10
(FLASKSCRUBBER)
DI
VAC
1 LAC
1 DIO
DIO
DIO
DIO
DIO
DIO
DIO
DIO
11 1
1 1
1 3
33 3
3 3 3
3 3
3 DIODIO
1 1
3 10
9 RPBFP/1

PRE-FILTER FOR DI

WATER SYSTEM
11 1"DI
7750 College Town Dr, Ste. 101Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A
F C O
TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:38:31 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt P-302

ENLARGED LAB DIWATER, AIR ANDVAC PLANSDCWWTP OPERATIONSAND LAB BLDG 4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
SHEET NOTES:KEYED NOTES:DROP A 1"DI WATER LOOP DOWN TO SINK AND RISE BACK UP WITH SHUT OFF VALVES AND BYPASS. CONNECT DI TO DI FAUCET AT COUNTER. TYPICAL.DROP LA AND LV TO BELOW GRADE. LINE-SIZE BYPASS VALVES ON DI WATER LOOP TO BE ACCESSIBLE ABOVE T- BAR CEILING. BYPASS VALVE TO REMAIN CLOSED. 1/2" LA AND 3/4" LV DOWN IN WALL TO FUME HOOD. PROVIDE LINE-SIZE ISOLATION VALVES ACCESSIBLE BEHIND ACCESS PLATE ON THE HOOD. CONNECT VACUUM AND AIR TO CONTROLLED SERVICE FIXTURE VALVE WITH QUICK RELEASE FOR CONNECTION TO HOOD. PROVIDE LINE-SIZE BYPASS VALVE ACCESSIBLE ABOVE T-BAR CEILING, TYP.LA AND LV TO RISE ABOVE GRADE AND CONNECT TO THE OUTLETS ON THE COUNTERS. SEE PLANS FOR SIZING.DROP LA AND LV IN WALL TO ROUTE BELOW THE COUNTERS. SEE PLANS FOR SIZING.LA AND LV TO RISE TO CONNECT TO OUTLETS ON THE COUNTER. FOR DOMESTIC COLD WATER SUPPLY FEEDING THE BACKFLOW PREVENTER AND THE DI WATER PRE-FILTER REFER TO ENLARGED DOMESTIC WATER PLAN 2/P-301. AND FOR PIPING RELATED TO THE DI WATER SYSTEM REFER TO DETAIL 4/P-401. DI WATER SUPPLY TO LAB AREA. DI WATER RETURN. REFER TO DETAIL 4/P-401 FOR VALVES AND CONNECTION POINT.LA TO DROP BELOW GRADE. SEE PLANS FOR SIZING.LV TO DROP BELOW GRADE. SEE PLANS FOR SIZING.DROP 3/4" LA TO 3'-2-3/4" ABOVE FINISHED FLOOR WITH LINE-SIZED SOV. TERMINATE WITH SOUTH FACING ELL 3/4"NPT MALE ADAPTER FOR CONNECTION TO AIR COMPRESSOR. 1 1 1/4" = 1'-0" ENLARGED LAB PLAN - VAC & AIR2 1/4" = 1'-0" ENLARGED LAB PLAN - DI WATER 234

1. SEE SHEET
P-200 FOR FIXTURE IDENTIFICATION.

2. SEE OVERALL PLAN
P-202 FOR CONTINUATION OF PIPING LAYOUT.

4. SEE SHEET
P-301 FOR WATER, WASTE AND VENT LAYOUT.

5. VACUUM LINE SIZING IS PER 2022 CPC TABLE 1323.1.4(6). 56789
1011121314
NO. DATE DESCRIPTION

BID SET (PRELIMINARY)
CR
A.5C
453
123

MEN'S LOCKER RM
124

LAUNDRY
122

WOMEN'S LOCKER RM
3/4"HWR
3/4"HWR
1 1
4 2
63 1
5 3/4"HW
3/4"CW
3/4"HW3/4"CW
3/4"HW3/4"CW
2" CW
3/4"HW
2"CW1-1/2"CW
(22.0)
1-1/2"CW
1-1/2"HW (36.0)
3/4"HW
1-1/2"HW (43.5)1-1/2"HW (40.5)
2"HW (49.5)
2"CW
2"CW (80.0)
7 7
3/4"CW
3/4"HW
1-1/2"CW
2"CW
2"CW
3/4"HW
2"CW
2"CW (100.0)
A.5C
453
123

MEN'S LOCKER RM
124

LAUNDRY
122

WOMEN'S LOCKER RM

SKYLIGHT

SKYLIGHT,
2 TYP
2"WCO
3"VTR(18.0)
2"V(6.0)
2"V
1-1/2"VR
1-1/2"VR
4"SS(24.0)
4"SS(4.0)
2"WCO
1-1/2"V(2.0)
3"VTR(26.0)
2"V(2.0)
2"SS
2"SS
2"V 2"V
1-1/2"VR
1-1/2"VR
1-1/2"VR
1-1/2"VR
2"V(10.0)
2"V 3/4"CD 8
CD
FC-3A
9 3"V(24.0)
2"SS(2.0)
4"SS(46.0)
3/4"CD
3/4"CD
CO
2"V8
1-1/2"VR
FCO
FCO
1-1/2"VR
FCO FCO FCO 1-1/2"VR 1-1/2"VR
1-1/2"VR
1-1/2"VR
7750 College Town Dr, Ste. 101
Sacramento, CA 95817
Tel (916) 447-2841
www.peterseng.com
Job no.
consulting mechanical and electrical engineers
PETERS
engineering
M31176
EXP. 12/31/25 A E EAL I FORN I A F C O TATS N I CA L CH E M R. N S NOR ROF P ED RETSI GER SS I ONAL ENG I NEER AE E T I CH

23.020
311 VERNON ST
ROSEVILLE, CA 95768
DATE:

JOB NUMBER:

SHEET TITLE
DRAWN BY:

PROJECT OWNER & TITLE
SHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT

THESE PLANS OR THE SPECIFICATIONS ARE

SUITABLE FOR ANY SITE OTHER THAN THE ONE

FOR WHICH THEY WERE SPECIFICALLY
PREPARED. THE ARCHITECT DISCLAIMS

RESPONSIBILITY FOR THESE PLANS AND

SPECIFICATIONS IF THEY ARE USED IN WHOLE OR
IN PART AT ANY OTHER SITE. WRITTEN

DIMENSIONS ON THESE DRAWINGS SHALL HAVE
PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP
REVISIONS #

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/20/2024 12:34:21 PM C:\Users\tcawelti\Documents\23.020 Dry Creek WWTP [email protected] P-303

ENLARGED LOCKER

ROOM PLANS

DCWWTP OPERATIONS

AND LAB BLDG
4/24/18
210015.01Author
1800 Booth Road
Roseville, CA 95747

CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
SHEET NOTES:

KEYED NOTES:

PROVIDE LINE SIZED ISOLATION BALL VALVE ACCESSIBLE ABOVE 24" X 24" CEILING ACCESS PANEL.

PROVIDE TRAP PRIMER AND WATER HAMMER ARRESTOR BEHIND 12" X 16" WALL ACCESS PANEL. MOUNT PANEL BELOW GRAB BAR. MAINTAIN 12" A.F.F.

FOR THE TRAP PRIMER LOCATION PER CODE. RUN TO FLOOR DRAINS SHOWN ON PLAN. SEE DETAIL 5/P
-400.

PROVIDE TRAP PRIMER BEHIND 12" X 16" WALL ACCESS PANEL. MOUNT PANEL ABOVE LAUNDRY FOLDING TABLE. RUN TO FLOOR DRAINS SHOWN ON PLANS. SEE DETAIL 2/P
-401.

PROVIDE TRAP PRIMER BEHIND 12" X 16" WALL ACCESS PANEL. MOUNT PANEL BELOW GRAB BAR. MAINTAIN 12" A.F.F. FOR THE TRAP PRIMER LOCATION PER CODE. RUN TO FLOOR DRAINS SHOWN ON PLAN. SEE DETAIL 2/P-401.

PROVIDE WATER HAMMER ARRESTOR ABOVE 14" X 14" CEILING ACCESS PANEL. PROVIDE WITH ISOLATION BALL VALVE.

DROP 3/4" HOT AND COLD WATER DOWN WALL AND RUN TO WASHING MACHINE BOX. MAKE FINAL CONNECTION TO CLOTHES WASHER.

DROP 3/4" COLD WATER DOWN WALL FOR LAVATORY CONNECTION AND TEE 3/4" IN WALL FOR HOSE BIBB BELOW LAV COUNTER.

DROP 3/4"CONDENSATE IN WALL TO SINK TAIL PIECE. SEE DETAIL 3/P -402.

CONNECT 3/4"CONDENSATE TO MECHANICAL EQUIPMENT WITH CLEANOUT.

RISE CONDENSATE UP TIGHT TO STRUCTURE AND GRAVITY DRAIN TO DROP. 123
2 1/4" = 1'-0"

ENLARGED FLOOR PLAN - PLUMBING WATER & GAS
1 1/4" = 1'-0"

ENLARGED FLOOR PLAN - PLUMBING WASTE & VENT

1. RUN ALL WASTE AND VENT AT 1/4" PER FOOT SLOPE.

2. SEE SHEET
P-200 FOR FIXTURE IDENTIFICATION.

3. SEE OVERALL PLANS
P-201 AND P-202 FOR CONTINUATION OF PIPING LAYOUT.

4. NUMBERS LISTED ON THE PLANS IN PARENTHESIS ARE WATER OR WASTE FIXTURE UNIT VALUES. 456789
NO. DATE DESCRIPTION

BID SET (PRELIMINARY)

GAS METER DETAIL ROOF CEPTOR

COMPRESSED AIR DROP

EMERGENCY GAS SOC DETAIL

SHOWER AND SWING-DOWN EYE/FACE WASHBARRIER-FREE COMBINATION EMERGENCYISLAND VENT TRAP PRIMER/WATER HAMMER ARRESTOR DETAIL G
G

SHUT-OFF
GAS
5 RISE FROMTOP OF MAIN

AIR MAIN OR
DROP1/2"B.V.
+48" A.F.F.

BRANCH
4"

A AIR OUTLET
QUICK COUPLER@+36" A.F.F.

A

CONDENSATE PIPE
2" P-TRAP
RC
1-1/2"VTR2" WASTE1-1/2" VENT
J.R. SMITH 3960 DOME BOTTOM ROOF
CEPTOR. DUCO CAST IRON WITH

VANDAL PROOF SCREWS
2" WASTE OUTLET

FINISHED FLOOR
SOC

STAINLESS STEEL ACCESS LINE SIZE EMERGENCY GAS
DOOR "ELMDOR" FR 10"x10"

CL-SS (RED SIGN READING
"GAS SHUT OFF VALVE")

MOUNT BOTTOM OF ACCESS

DOOR ABOVE THE

COUNTERTOP

BUILDING WALL
UNION

FINISHED GRADE
18" APPROX.

PIPE SLEEVE THRU WALL. SEAL

AND PROVIDE ESCUTCHEON PLATE BOTH
SIDES OF WALL.SHUT-OFF VALVELINE SIZE SEISMIC
SEE
SPECS.

CONTINUATION.('P' SHEETS) FOR SIZE ANDREFER TO PLUMBING PLANS CONSPICUOUSLY MARKED: "GAS SHUT-OFF"LINE SIZE GAS SHUT-OFF VALVE

UPC LISTEDDIELECTRIC FITTINGGAS SHUT-OFFLINE SIZE

GAS METER
BY UTILITY COMPANY (PG&E).GAS METER IS SIZED FOR A TOTALESTIMATED DEMAND OF ---- MBH.DELIVERY PRESSURE SET AT 7" W.C. 30" MIN HORIZONTAL
GAS MAIN.

AND PLASTIC PIPING.

FITTING BETWEEN METIALLIC

APPROVED TRANSITION
1"1" 1"
LETTERSENAMEL FILLEDENGRAVED, REDSCREWS, TYP.CSK OVAL HEADSTAINLESS STEEL

ALUMINUM PLATE
3/32" THICK
8"
4"

SIGN ON WALL

FRONT VIEW

SIDE VIEW
1 1/2" DRAIN

FINISHED FLOOR
NOTE: INSTALL COMBINATION
EMERGENCY SHOWER AND SWING-DOWNEYE/FACE WASH PER MANUFACTURESREQUIREMENTS.

SWING-DOWN SHOWER

ACTUATING ARM

EYE/FACEWASH
1" INLET

STAINLESS STEELSHOWER HEAD
1" TEMPERED SUPPLY
36" MAX
P-TRAP
S
LOCATIONS.

ABOVE LAY-IN CEILING SEE FLOOR PLANS FORALTERNATE TRAP PRIMER AND B.V. LOCATION NOTE:

FIN. FLOOR
TO TRAP AS REQ'D.CONNECT 1/2" CW
1/2" CWD, TYPICAL

CW PIPE IN WALL
WHA

SEAL WATERTIGHT, TYPICAL

STUD WALL
1/2" BALL VALVE
14" x 14" STAINLESS STEEL LOCKABLE,

ACCESS DOOR AND CABINET, ELMDOR
OR EQUAL. PROVIDE HINGED DOOR AND

CYLINDER LOCK
1/2" CW PIPING BELOW FLOOR.SLOPE TOWARD DRAIN

COUNTER TOP
2"ACID WASTE
2"ACID LONG RADIUSELBOWTAPPED SPIGOTFIXTURE OUTLETTAILPIECEP-TRAP W/ C.O.PLUG SINK
2"ACID VENT RISER
C.O.
2"ACID VENT DROP

2. NOTES:

1. 2"ACID WASTE
WCO
WALL
2"VR
COORDINATE LOCATION OF VENT W/ CABINET CASEWORK SO THAT TOP OFVENT WILL FIT BETWEEN SINK & SIDE OR REAR OF CABINET.

ALL PIPING SHALL BE ENCLOSED WITHIN CABINET.

USE VENT DETAIL FOR SINKS BELOW WINDOWS.
2" ACID HORIZONTAL FOOT VENT

EXTEND VENT AS HIGH AS

POSSIBLE UNDER

COUNTERTOP, BUT NO

LESS THAN COUNTERTOP

OR DRAINBOARD HEIGHT

3. SCALE: NONE SCALE: NONESCALE: NONE
SCALE: NONE 1
2 3 SCALE: NONE
46 7 SCALE: NONE SCALE: NONE
7750 College Town Dr, Ste. 101Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A F C O TATS N I CA L CH E M
R. N
S
NOR
ROF P

ED RETS
I
GE
R

SS I ONAL
ENG I
N
E
E
R

AE E T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:38:35 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt P-400

DETAILSDCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
NO. DATE DESCRIPTION

BID SET (PRELIMINARY)
6/S5.14

VENT THRU ROOF DETAIL

AM FLOOR DRAIN TRAP PRIMER DETAILDI WATER PIPING DIAGR

PIPE SUPPORTPIPE SUPPORT ON WOOD WALL
24 35

ROOF STRUCTURE

ROOFINGFLASHINGELMDOR/STONEMAN SEAMLESS

WATERPROOFING COMPOUND

PERMASEAL
OR CAULK TYPE FOR ALL STEELCAST IRON VENTS AND THREADEDCOUNTER FLASHING SLEEVE FOR"ELMDOR/STONEMAN" CAULK TYPE CLEAR FRESH AIR INTAKES,EXTEND WHERE REQ'D TOVENTS 3" & LARGER ONLYTURNED IN ON CAST IRONELMDOR/STONEMAN #1100- 9"MIN.EXTEND AS REQ'D.

ETC.

VENTS.
4-6LB-8SK FLASHING

PIPE CLAMP
P-TRAP
S
LOCATIONS.

ABOVE LAY-IN CEILING SEE FLOOR PLANS FORALTERNATE TRAP PRIMER AND B.V. LOCATION NOTE:

STUD WALL
DRAINSLOPE TOWARDBELOW FLOOR.1/2" C.W. PIPINGFIN. FLOOR TO TRAP AS REQ'D.CONNECT 1/2" CW

FLOOR DRAIN
SEAL WATERTIGHTCW PIPE IN WALLUNION1/2" CWD

BALL VALVE

TRAP PRIMER(TP)SECURE TO STUDS
14" x 14" STAINLESS STEEL LOCKABLE,

ACCESS DOOR AND CABINET, ELMDOR
OR EQUAL. PROVIDE HINGED DOOR AND

CYLINDER LOCK
6 7
7 3 4 5

BALL VALVE, TYP

UNION, TYP
1 SEE 2/P-301 FOR LOCATION. THIS
SECTION OF PIPING IS ON OPPOSITEWALL FROM THE DIWP/1 AND DI TANKS NOTE:

PIPING AND VALVES SHOWN DARK IS PROVIDED BY

CONTRACTOR, ALL PIPING AND EQUIPMENT SHOWN
LIGHT IN COLOR IS PER "CULLIGAN". FOR CONTACT
SEE EQUIPMENT PLANS SHEET P-002. 1" DI WATER SUPPLY TO LAB 1-1/4" ICW SUPPLY FROM OVER DOOR TO DI TANKS DI WATER TANKS AND PIPING BY "CULLIGAN" -A--A- 1-1/4"ICW SUPPLY OVER DOOR TO DI TANKS Y-STRAINER W/HOSE END BLOW OFF PETE'S PLUG, TYP 1-1/4"DCW SUPPLY RUN AND SPILL DRAIN LINE TO FLOOR SINK WITH 1" AIRGAP RPBFP 1 DIWP 1 1" DI WATER RETURN FROM LAB

PRESSURE GAUGEPRESSURE RELIEF VALVE

CHECK VALVE
TRAP PRIMER,SPILL TO FLOORSINK WITH 1"
AIRGAP
LABEL
1 DESCRIPTION
2345
PROVIDED BY:

PRE-FILTER ASSEMBLY, 1 MICRONPRESSURE GAUGES, STAINLESS STEELCATION RESIN TANK, 14" X 48" ANION RESIN TANK, 14" X 48"
MIXED BED POLISHER TANK, 14" X 48"
7 MONITOR, WATER QUALITY8 FLOW CONTROL, 15 GPM
2 6 FILTER ASSEMBLY, RESIN TRAP
8 2
3/8"ø ALL THREAD, SEE

FOR UPPER

ATTACHMENT
SHEET METAL STRAP, ATTACHTO STRUCTURE WITH #10x11/2 WOOD SCREW

PIPING WITHINSULATION SPACER
1 5/8" FRAMINGCHANNEL

PIPE CLAMP
NOTES:1. PROVIDE PIPE SUPPORT AT ALL CHANGES IN DIRECTION.2. HORIZONTAL PIPE SUPPORTS SHALL BE SPACED MAX. 6'-0" O.C.

3. FIRE PROTECTION WATER PIPING CANNOT BE SUPPORTED WITH THIS SYSTEM.4. PROJECT MAX LOAD: 250 LB.5. USE A CUSHIONED CLAMP TO PROTECT INTERFACE FROM DISSIMILAR METALS6. AIRCRAFT CABLE MAY BE OMITTED WHEN HANGER ROD LENGTH DOES NOT EXCEED 12" 3/32"ø PRESTRETCHEDGALVANIZED AIRCRAFTCABLE 7x19 STRANDCORE @ 45°. 20 FT. MAXLENGTH SEE DETAIL 6/S5.14 FOR ROD UPPER ATTACHMENT CONDITION.
2" MIN.

SEE DETAIL ABOVEFOR CABLE UPPER
ATTACHMENT CONDITION.

MASON IND. N.Y.BRACKET FOR

AIRCRAFT CABLE

BRACING
3/8"ø THREADED ROD
BLINE 3100 SERIESCLEVIS HANGER

BARE PIPE INSULATED PIPE
3/32"ø PRESTRETCHEDGALVANIZED AIRCRAFTCABLE 7x19 STRANDCORE @ 45°. 20 FT. MAXLENGTH MASON IND. N.Y.BRACKET FOR

AIRCRAFT CABLE

BRACINGSEE DETAIL ABOVEFOR CABLE UPPER
ATTACHMENT CONDITION.

BLINE 3100 SERIESCLEVIS HANGER
NOTES:

1. SUPPORT AT ALL CHANGES IN DIRECTION.2. VERTICAL PIPE SUPPORT SHALL BE SPACED MAX. 4'-0" O.C.

WALL
1 5/8" FRAMING CHANNEL, 24" LONG
'SUPERSTRUT' A716 CUSH-A-CLAMPPIPE CLAMPREFRIGERANT PIPING WITH INSULATION

AND GALVANIZED SHIELD

3. HORIZONTAL PIPE SUPPORT SHALL BE SPACED MAX. 8'-0" O.C. 1/4" LAG SCREW INTO FRAMING ORBLOCKING BETWEEN FRAMING W/ 3"MINIMUM EMBEDMENT, 2 REQ'D 3/32"ø PRESTRETCHEDGALVANIZED AIRCRAFTCABLE 7x19 STRANDCORE @ 45°. 20 FT. MAXLENGTH

SEE DETAIL ABOVEFOR CABLE UPPER
ATTACHMENT CONDITION.

MASON IND. N.Y.BRACKET FOR

AIRCRAFT CABLE

BRACING

CALCIUM SILICATESHIELD
3/32"ø PRESTRECHED
AIRCRAFT CABLE 7x19
STRAND CORE @ 45°. 20 FTMAXMASON IND. N.Y. BRACKET FOR

AIRCRAFT CABLE BRACING
UNISTRUT P1843 WITH3/8"øx3" LAG SCREWINTO BLOCKING
SECURE 2x4 BLOCKING TO FRAMING WITHSIMPSON LUS JOIST HANGER, EACH END.

ALTERNATE ATTACHMENT
LOCATION FOR 1/2"ø THRU BOLT,LOCKING NUT AND WASHERS

STRUCTURAL I-JOISTS
1 SCALE: NONE
SCALE: NONESCALE: NONE
SCALE: NONESCALE: NONE
30-45°
7750 College Town Dr, Ste. 101Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A F C O TATS N I CA L CH E M
R. N
S
NOR
ROF P

ED RETS
I
GE
R

SS I ONAL
ENG I
N
E
E
R

AE E T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:38:35 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt P-401

DETAILSDCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
NO. DATE DESCRIPTION

BID SET (PRELIMINARY)

MECHANICAL UNIT

CONDENSATE/WASTE CONNECTION TO TAILPIECE

WATER HEATER PIPING DIAGRAM ANDMOUNTING TO WOOD STUD WALL

VACUUM - POWEREX DETAIL

CONDENSATE P-TRAP TO MECHANICAL UNIT DETAIL

CONDENSATE TO DRYWELL
T

SINK OR LAVATORY
3/4" CD OR WASTE DRAIN.SLOPE DOWN TO SINK
TAILPIECE.

LAVATORY/SINK BRANCH
TAILPIECE.

WASTE P-TRAP
NOTES:

1. REFER TO PLANS FOR SIZES AND CONTINUATION.

ET
1 WH
1 CHECK VALVE, TYP

THERMOSTAT, TYP

BALL VALVE, TYP

HW SUPPLY
NOTE:

VACUUM RELIEF VALVE, "WATTS"MODEL N36 OR EQUAL
3/4" HARD TEMPERED COPPER DRAIN FROMP&TRV, SPILL TO FLOORSINK @ 6" ABOVEFLOOD RIM

CW SUPPLY
HOLDRITE 40-S-34-U PLATFORM.SEE EQUIPMENT SCHEDULE.

SECTION VIEW

TOP VIEW

STUD PER PLAN
1/4"x2-1/2" SDS SCREW, 4 TOTAL
GYP. BOARD

WOOD STUD WALL

STUD PER PLAN

WATER HEATERSHEET METAL STRAP
2"x16 GA. GALV. SHEET METALSTEEL PLUMBERS TAPE WRAPPED

ALL AROUND WATER HEATER,
TYPICAL.

SECURE SHEET METAL STRAP TO STUDWITH 1/4" Ø x 2-1/2" SDS, 4 TOTAL

STUD PER PLAN
AT 16" O.C.

1. PROVIDE AND SECURE WITH SHEET METAL STRAP, UPPER AND BOTTOM THIRD OF WATER HEATER. STRAPS TO BE A MINIMU
M
DISTANCE OF 4" FROM CONTROLS. ALSO PLACE ONE STRAP ATCENTER OF EXPANSION TANK. ATTACH TO WALL PER DETAIL. 2. REFER TO PLANS FOR COLD WATER, HOT WATER, AND HOT WATERRETURN SIZING.

3. MOUNT WATER HEATER TO BE IN CONTACT WITH THE WALL OR PROVIDE A SADDLE FOR TIGHT FIT.

HONEYWELL AQUASTAT #L4006A1967 OREQUAL. LOCATE AS FAR FROM CIRCULATOR AS POSSIBLE WITHIN THE ROOM. SET TEMP
TO 5 DEGREES F. BELOW WATER HEATERHOT WATER OUTLET TEMPERATURE.

CP
1 HOT WATER RETURN

DIELECTRIC UNION, TYP

PROVIDE AND SECURE WITH SHEET METALSTRAP, SEE DETAIL FOR WALL ANCHORAGE 3x MIN BLOCKING
REQUIRED FOR A35 ONEACH SIDE
PROVIDE FULL DEPTH BLOCKINGWITH A35 CLIP TOP AND BOTTOMEA END AT ALL POINT OF

ANCHORAGE
4" MIN PER
ICC ESR-2236

HOLDRITE PLATFORM LEG
(2)SAFETY CLIP, 14 GAUGE CRS,GALVANIZED IN LEG
FLOOR

CONCRETE ANCHOR
3/8"Øx2-1/2" EMBED HILTI
KB-TZ2. INTALL ANCHORS PER
ICC ESR-4266 AND PROVIDE

SPECIAL INSPECTION NOTED

IN THE REPORT (TORQUE
TEST 30 FT-LB)
HOLDRITE 40-S-24-A FLOOR MOUNTING
SET WATER HEATER TEMPERATURE TO 140°F

AT DRAIN PAN
AB
X = STATIC PRESSURE IN AHU
A = 2" PLUS X
B = X
VENT

CLEANOUT

DRAIN LINE SHALL BE AT LEASTTHE SAME SIZE AS THE NIPPLEON THE DRAIN PAN END OF LINE CLEANOUT.SEE PLANS FOR LOCATIONS
1/4" PER FOOT SLOPEDOWNWARDS FROM UNIT

FLEX CONNECTIONFOR EQUIPMENT ONSEISMIC ROOF CURBS

TERMINATE CONDENSATE

AS SHOWN ON PLANS
1"
18" DIA. BY 4'-0"DEEP CONC. PIPEDRYWELL
CONC. ACCESSCOVER

FROM FAN COIL UNITCONDENSATE DRAIN PIPE
FINISHED SIDEWALKCOARSE WASHEDROCK; 3/4" DIA. MIN. GROUT FLOOR

FINISHED FLOOR

FLOOR SINK
VERTICAL SYMPLEX TANKMOUNT MODEL #IVS0202
9 6
4 7
8 5
1 2
DESCRIPTION MODEL NO. QTY.
1 MOTOR STARTER 208V PVI10022AJ 12 VACUUM PUMP/ MOTOR ASSEMBLY VPB02000AV 1 VACUUM SWITCH (NOT SHOWN) VP001303AV 13
4* PVI10022AJ 1
5 --- 16 VP00406AV 17 HA001301AV 18 GA031600AV 1
INLET AIR FILTER ELEMENTRECIEVER TANK 30 GAL.CHECK VALVE

VACUUM HOSEVACUUM GAUGE
9 PE001004AV 1 HOUR METER
- VP000801AJ 1 OIL- 0531.002.00 1 OIL FILTER- V532.140.156 1 SEPERATOR FILTER *=2,500 HOUR REPLACEMENT
VACUUM
TANK

ISOLATION VALVE
CHECK
VALVE

TOATMOSPHERENPTF

MANUAL DRAIN VALVE

STARTER

PIPING DIAGRAM WITH SINGLE PUMP

THERMOMETER

AUTOMATIC DRAIN
VALVE

SOLENOID
NOTES:

1. DRIP LEG AND DRAIN VALVE MUST BE INSTALLED NEAR EXHAUST FITTING OF PUMP.

2. MINIMUM CLEARANCE OF 36" AROUND AND ABOVE THE SYSTEM.3. USE FLEXIBLE HOSE TO CONNECT THE INLET AND OUTLET OF THE UNIT TO PIPING.

VACUUM
SWITCH

PRESSURE
GAGE
FLEX
HOSE
AIR
FILTER
VAC.

PUMP

DRIP LEG ANDDRAIN VALVE
REF.

NO
(3)1/2"Ø HILTI KB-TZCONCRETE ANCHORWITH 2" EMBEDMENT.

SCALE: NONE
3 2 NTS
SCALE: NONE
1 4 SCALE: NONE
SCALE: NONE
5 7750 College Town Dr, Ste. 101Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A
F C O
TATS

N I CA L
CH E M
R. N
S
NOR
ROF P

ED RETSI GER

SS I ONAL

ENG I NEER
AE
E
T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:38:35 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt P-402

DETAILSDCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS
NO. DATE DESCRIPTION

BID SET (PRELIMINARY)

HOSE BIBB ON ROOF DETAIL

BEACON MEDAES AIR COMPRESSOR DETAIL

BELOW SINK/LAVTHERMOSTATIC MIXING VALVE

ROOF DRAIN AND OVERFLOW DRAIN

UTILITY PIPE TRENCH

ICE MAKER BOX DETAIL
CH

SINK/LAVATORY

COLD WATER SUPPLY AND STOP

HOT WATER SUPPLY AND STOP

MOUNTING BRACKET

THERMOSTATIC MIXING VALVE, MOUNT

UNDER LAVATORY AS HIGH AS POSSIBLE

WHEN NOT LOCATED BEHIND AN

ACCESS PANEL
NOTE:INSTALL PER MANUFACTURER'S INSTRUCTIONS.

WIDTH AS REQUIRED

FLOORFINISHED

COVER HOLD DOWN
SCREW
1/2" THICK STEEL

COVER PLATE
"WALKER" TYPE VA LINEAR

TRENCHDUCT OR EQUAL

COMBINATION CLIP

ATTACHING SCREW

SEE PLANS FOR

PIPE SIZE AND

SERVICE TYPE
"UNI-STRUT" CHANNEL

WITH PIPE CLAMP
16 GAUGE

GALVANIZED STEEL

DUCT BODY
THREADED1/2"CONNECTION WITH1/4"OUTLET WITHSHUT-OFF VALVE. ROUTETO ICE MACHINE.

MOUNT ICE MAKER BOXMAXIMUM OF 24" ABOVEFINISHED FLOOR

WATERSUPPLY

BALL VALVEFINISHEDFLOOR
3/4" COPPER OR RED BRASS PIPEHOSE BIBB WITH VACUUM BREAKER

MIXING FAUCET

WATER DAM COLLAR
2"

ROOFDECK &FLASHING

CAS IRON DRAINBODY

OVERFLOW PIPING,SEE FLOOR PLANFOR SIZE, TYPICAL

OVERFLOWDRAIN

ROOF DRAIN

RAINWATER PIPING,SEE FLOOR PLAN FORSIZE, TYPICAL
FLASHING CLAMP &UNDERDECK CLAMP,TYPICAL.CAST IRONDOMES,TYPICAL 4" MAX.

DEPTH2"
24"

ROOF DECK

VOLCOME WEATHER SEAL

STAINLESS STEEL HOSECLAMP AROUND ROOF JACK
1-1/4" SCH. 80, PVC SLEEVE. FILL

ANNULAR SPACE WITH FOAM

FINISHED ROOFROOF JACK

SECURE PIPE CLAMPTO PIPE AS REQUIRED

STRUCTURAL

FRAMING MEMBER

SECURE SHEET METAL STRAP
TO STRUCTURE WITH #10x1-1/2"

WOOD SCREW
2 SCALE: NONE
1 SCALE: NONE
3 SCALE: NONE
4 SCALE: NONE
5 SCALE: NONE6 SCALE: NONE
7750 College Town Dr, Ste. 101Sacramento, CA 95817Tel (916) 447-2841www.peterseng.comJob no. consulting mechanical and electrical engineers
PETERSengineering
M31176
EXP. 12/31/25
A E
E

AL I FORN I A F C O TATS N I CA L CH E M
R. N
S
NOR
ROF P

ED RETS
I
GE
R

SS I ONAL
ENG I
N
E
E
R

AE E T I CH

23.020
311 VERNON STROSEVILLE, CA 95768DATE:

JOB NUMBER:

SHEET TITLEDRAWN BY:PROJECT OWNER & TITLESHEET NO.

DATE PLOTTED: FILE LOCATION:

THE ARCHITECT DOES NOT REPRESENT THAT THESE PLANS OR THE SPECIFICATIONS ARE SUITABLE FOR ANY SITE OTHER THAN THE ONE FOR WHICH THEY WERE SPECIFICALLY PREPARED. THE ARCHITECT DISCLAIMS RESPONSIBILITY FOR THESE PLANS AND SPECIFICATIONS IF THEY ARE USED IN WHOLE OR IN PART AT ANY OTHER SITE. WRITTEN DIMENSIONS ON THESE DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS.

ARCHITECT STAMP

REVISIONS
#

CONSULTANT STAMP
City of Roseville Approval
2237 DOUGLAS BLVD, SUITE 160
ROSEVILLE, CA 95661
TEL (916) 786-8178
9/16/2024 3:38:36 PM S:\23.020 Dry Creek WWTP\drwgs\REVIT\23.020 Dry Creek WWTP MEP_r22.rvt P-403

DETAILSDCWWTP OPERATIONSAND LAB BLDG
4/24/18
210015.01Author
1800 Booth RoadRoseville, CA 95747CITY OF ROSEVILLE - DCWWTP

CONSTRUCTION DOCUMENTS

PROVIDE LINE-SIZE
SOV
6" HOUSEKEEPING PAD
FLOOR
3/4"Ø HILTI KB-TZ CONCRETE ANCHOR WITH 2"EMBEDMENT (4 PLACES) NO. DATE DESCRIPTION

BID SET (PRELIMINARY)
CR
CR

1. PLANS ARE NOT FOR CONSTRUCTION UNTIL APPROVED BY THE AUTHORITY HAVING JURISDICTION. THE CONTRACTOR SHALL NOT ORDER ANY MATERIALS OR INSTALL ANY EQUIPMENT, PIPING, ETC. UNTIL PLANS ARE APPROVED BY THE AUTHORITY HAVING JURISDICTION.

2. PROTECT EXISTING EQUIPMENT AND FURNISHINGS FROM ANY DAMAGE DUE TO DUST, MOISTURE OR CONTACT WITH WORK CREW OR MATERIALS.

3. ADEQUATELY STRAP AND SUPPORT ALL CONDUIT WORK PER CEC. IN GENERAL, SUPPORT ALL CONDUIT WITHIN THREE FEET (3') OF OUTLET BOX, CABINET OR PANEL AND MAXIMUM TEN FEET (10') ON CENTER THEREAFTER.

4. CORE BORE SHALL BE 1" DIAMETER LARGER THAN EACH CONDUIT. SPACE CONDUIT HOLES 3" APART. SEAL AROUND CONDUIT WITH NON-SHRINK, NON-METALLIC GROUT.

5. ALL CONDUCTORS INSTALLED IN PANELBOARDS SHALL BE TRAINED, LACED, AND INSTALLED WITH PHASE TAPE ON ALL CONDUCTORS.

6. LABEL DEVICES (I.E. RECEPTACLES, ETC.) ON EACH COVER PLATE IDENTIFYING CIRCUIT AND PANEL DEVICE IS CONNECTED TO.

7. CLEAN ALL EXTERIOR AND INTERIOR SURFACES OF PANELS AND ALL MATERIAL AND METAL SHAVINGS FROM PANEL AND CABINET INTERIORS. ALL OPENINGS SHALL BE SEALED AND APPLY TOUCH-UP SPRAY PAINT WHERE NEEDED.

8. FIELD COORDINATE DEVICE LOCATIONS PRIOR TO ROUGH-IN.

9. CONTRACTOR WILL PROVIDE WARNING LABELS NOTING THE POTENTIAL FOR ELECTRIC ARC FLASH HAZARDS PER CEC 110.16. PROVIDE LABELS ON EQUIPMENT SUCH AS

SWITCHBOARDS, SWITCHGEAR, PANELBOARDS, INDUSTRIAL CONTROL PANELS, METER SOCKET ENCLOSURES, MOTOR CONTROL CENTERS, MOTOR STARTER / CONTACTOR PANELS, DISCONNECTS, ETC..

9.1. CONTRACTOR TO PROVIDE BREAKER COORDINATION STUDY COMPLETE WITH BREAKER SETTINGS.

9.2. CONTRACTOR WILL PROVIDE ARC FLASH LABELS FOR ELECTRICAL POWER PANELS INCLUDED IN THE PROJECT SCOPE IN ACCORDANCE WITH NFPA 70E AND SPECIFICATION SECTION 26 05 73 'OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY'. THE ARC-FLASH LABELS MESSAGE OR CONTENT SHALL BE PROVIDED BY THE CONTRACTOR.

10. INSTALLATION SHALL COMPLY WITH CEC 210.4 - EACH MULTIWIRE BRANCH CIRCUIT SHALL BE PROVIDED WITH A MEANS THAT WILL SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED CONDUCTORS AT THE POINT WHERE THE BRANCH CIRCUIT ORIGINATES. THEREFORE ANY CIRCUIT SHARING A COMMON NEUTRAL SHALL BE CAPABLE OF SIMULTANEOUS DISCONNECT OR DEDICATED NEUTRALS SHALL BE INSTALLED.

11. ALL EQUIPMENT AND APPURTENANCES USE IN THIS PROJECT SHALL BE UL (NRTL) LISTED AND LABELED FOR THE PURPOSE AS PER CEC-2019ART.110.3 AND 690.4B.

12. SUPPORT ENCLOSURES, BOXES AND CONDUIT INSTALLATIONS PER CEC 314.23 (A) THROUGH (H).

13. SEAL CONDUIT OPENINGS THROUGH WALLS AND CEILINGS. INSTALL ESCUTCHEON PLATES AT BUILDING INTERIOR. WHERE EQUIPMENT IS INSTALLED ON THE EXTERIOR WALL, STUB CONDUITS THROUGH WALL AND SEAL CONDUIT OPENINGS, THEN INSTALL EXTERIOR EQUIPMENT. ALSO, SEAL AROUND THE PERIMETER EDGE OF THE EQUIPMENT ENCLOSURE BETWEEN THE ENCLOSURE AND BUILDING.

14. RACEWAY SEALS. ALL RACEWAYS ENTERING/EXITING A BUILDING SHALL BE SEALED AT BOTH ENDS TO PREVENT MOISTURE AND RODENTS FROM ENTERING THE BUILDING.

SEALANTS SHALL BE LISTED FOR USE WITH CABLE INSULATION, CONDUCTOR INSULATION, BARE CONDUCTOR, SHIELD, OR OTHER COMPONENTS.

15. CONDUITS INSTALLED ON ROOF AND BUILDING EXTERIOR SHALL BE RIGID GALV. STEEL (HEAVY WALL) WITH THREADED FITTINGS. CONDUIT AND WALL TO BE PAINTED OUT TO MATCH EXTERIOR FINISH.

16. EXPOSED CONDUITS TRANSITIONING FROM BELOW OR AT GRADE TO A HEIGHT OF 8 FEET AFG SHALL BE RMC OR IMC.

17. SPLICES AND TERMINALS SHALL BE COMPRESSION TYPE OF SEAMLESS PURE COPPER, TIN PLATED, LONG BARREL (TERMINALS WITH TWO-HOLE PAD AND INSPECTION WINDOW WITH NEMA DRILLING), AS MANUFACTURED BY BURNDY TYPE YS, YAZ-2N OR EQUAL. CLEAN ALL SURFACES AND INSTALL WITH OXIDE INHIBITING COMPOUND, BURNDY PENETROX-E OR EQUAL. APPLY COMPOUND BETWEEN BUS AND LUG PAD AND BETWEEN CONDUCTOR AND LUG BARREL. INSTALL COMPRESSION CONNECTORS WITH 360° CIRCUMFERENTIAL COMPRESSION DYE, BURNDY HYPRESS OR EQUAL. THE INDENTER OR OTHER TYPE TOOLS WILL NOT BE ACCEPTABLE.

18. INSTALL 'MECHANICALLY FASTENED PHENOLIC NAMEPLATE WITH WHITE LETTERING ON BLACK BACKGROUND ON ALL EQUIPMENT, INCLUDING PULL BOXES, WITH DESCRIPTION INDICATED ON DRAWINGS. NAMEPLATES SHALL READ EXACTLY AS DESCRIBED ON THE DRAWINGS. IN GENERAL NAMEPLATE LETTERING SIZE SHALL BE 3/16" HIGH FOR ALL NAMEPLATES SERVING FEEDER AND BRANCH CIRCUIT BREAKERS. ON MAIN SERVICE PANEL, DISTRIBUTION PANELS AND ALL OTHER NAMEPLATES LETTERING SHALL BE 1/4" HIGH.

18.1. ALL SWITCHBOARDS, SWITCHGEAR, PANELBOARDS, VFD'S, MOTORS, JUNCTION BOXES, PULL BOXES, DISCONNECT SWITCHES, ETC., SHALL BE MARKED TO INDICATE EACH DEVICE OR EQUIPMENT WHERE THE POWER ORIGINATES PER CEC 408.4, FIELD IDENTIFICATION REQUIRED, (B) SOURCE OF SUPPLY.

19. EVERY CIRCUIT SHALL BE IDENTIFIED IN A CIRCUIT DIRECTORY AND AT EACH SWITCH OR CIRCUIT BREAKER PER CEC 408.4, FIELD IDENTIFICATION REQUIRED, (A) CIRCUIT DIRECTORY OR IDENTIFICATION. CIRCUIT DIRECTORIES (NEW AND MODIFIED) SHALL BE TYPE WRITTEN, HAND MADE MODIFICATIONS TO PANEL DIRECTORIES WILL NOT BE ACCEPTABLE. CIRCUIT NUMBERS AT SWITCHES OR CIRCUIT BREAKERS SHALL BE ENGRAVED OR A PERMANENTLY AFFIXED PRE-PRINTED LABELS.

20. COORDINATE EQUIPMENT LOCATIONS, CONTROL AND POWER WIRING REQUIREMENTS AND CONNECT POINTS WITH ALL APPLICABLE DISCIPLINES.

21. PROVIDE AND INSTALL FUSES PER UNIT NAMEPLATE DATA ON THE EQUIPMENT PROVIDED.

22. VERIFY CEILING TYPES PRIOR TO ORDERING LUMINAIRES. CONFIRM THAT FEATURES DESCRIBED IN THE SPECIFICATION OF THE LUMINAIRE ARE INCLUDED AS WELL AS PART NUMBERS LISTED ON SCHEDULE IN THE SUBMITTAL PACKAGE. CLARIFY NOTED DISCREPANCIES WITH ENGINEER PRIOR TO BID.

23. A LAMINATED COPY OF THE FINAL RECORD ONE LINE DIAGRAM SHALL BE PLACED IN EACH ELEC ROOM.

24. PROVIDE WIRING DEVICES AND COVER PLATES IN COLOR(S) SELECTED BY ARCHITECT. THE COLOR OF THE WIRING DEVICE AND COVER PLATE SHALL BE THE SAME UNLESS SPECIFICALLY NOTED OTHERWISE.

25. RECEPTACLE WEATHERPROOF COVERS SHALL BE LISTED "EXTRA DUTY", LOCAKBLE, METAL, IN-USE TYPE.

25.1. GROUND FAULT CIRCUIT INTERRUPTER DUPLEX OUTLETS INSTALLED OUTDOORS SHALL BE "WEATHER RESISTANT", (WR) LISTED.

26. ALL CONDUITS PASSING THROUGH A BUILDING SHOULD BE METALLIC PER NEC ART.690.31E.

27. FOR ROOF PENETRATIONS, REFER TO ARCHITECTURAL PLANS FOR INSTALLATION REQUIREMENTS.

28. FOR WALL PENETRATION INSTALLATIONS, REFER TO ARCHITECTURAL PLANS FOR REQUIREMENTS.

29. PROVIDE "LOCK-ON" DEVICE FOR ALL CIRCUIT BREAKERS ON EMERGENCY DEDICATED CIRCUITS.

30. DRAWINGS ARE TO BE CONSIDERED DIAGRAMMATIC. CONTRACTOR SHALL ACCEPT RESPONSIBILITY IN FAMILIARIZING THEMSELVES WITH ARCHITECTURAL AND STRUCTURAL CONDITIONS ALONG WITH INHERENT SPACE LIMITATIONS. WITH THAT UNDERSTANDING SHALL PROVIDE ALL ITEMS OF LABOR, MATERIALS AND TOOLS REQUIRED TO PROVIDE A COMPLETE INSTALLATION.

31. PROVIDE SWITCHED/CONTROLLED RECEPTACLES WITH PERMANENT MARKINGS PER THE CALIFORNIA ENERGY CODE. MARKING SHALL BE AS PROVIDED BY THE MANUFACTURER OF THE RECEPTACLE, STAMPED INTO THE FACE (IE, LEVITON #5362-1PW OR EQUAL.) SYMBOL SHALL BE OF CONTRASTING COLOR TO THE DEVICE COLOR.

32. PROVIDE DATA SHEETS FOR ALL ELECTRICAL AND LOW VOLTAGE EQUIPMENT (INCLUDING BUT NOT LIMITED TO LIGHTING CONTROLS, FIRE ALARM, INTRUSION ALARM, CCTV, ACCESS

CONTROL, INTERCOM, DATA/TELECOMMUNICATIONS AND SOUND REINFORCEMENT SYSTEMS) INCLUDED IN THIS PROJECT FOR REVIEW AND APPROVAL PRIOR TO ORDERING ANY EQUIPMENT OR DEVICES. REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL SUBMITTAL REQUIREMENTS.

33. SUBMIT SHOP DRAWINGS FOR ALL ELECTRICAL AND LOW VOLTAGE SYSTEMS (INCLUDING BUT NOT LIMITED TO LIGHTING CONTROLS, FIRE ALARM, INTRUSION ALARM, CCTV, ACCESS

CONTROL, INTERCOM, DATA/TELECOMMUNICATIONS AND SOUND REINFORCEMENT SYSTEMS) FOR REVIEW AND APPROVAL PRIOR TO THE INSTALLATION OF ANY EQUIPMENT, DEVICES, RACEWAY OR WIRING. REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL SUBMITTAL REQUIREMENTS.

GENERAL NOTES

LENGTH OF CONDUCTOR

WIRE SIZE IN (GAUGE)
#12 #10 #8 #6 #4
1200VA 74 121 183 284 434
1560VA 57 93 141 218 334
1800VA 49 81 122 189 289
1920VA 46 76 115 178 271
2340VA 62 94 146 223
2880VA 51 76 118 181
3000VA 48 73 114 174
3900VA 56 87 134
4800VAX 46 71 108
NOTES

1. THIS CHART IS FOR COPPER CONDUCTORS ONLY.

2. THIS CHART ASSUMES AN 80% POWER FACTOR AND STEEL RACEWAYS.

3. 2019 CALIFORNIA ENERGY CODE, 130.5(c) ALLOWS A MAXIMUM COMBINED VOLTAGE DROP OF 5%. THIS CHART ASSUMES A MAXIMUM DROP OF 3% FOR FEEDERS. THIS CHART PROVIDES THE MAXIMUM LENGTH OF CONDUCTORS FOR LESS THAN 2% VOLTAGE DROP ON A BRANCH CIRCUIT AT GIVEN VA LOAD.

4. USE WIRE SIZE FROM THIS CHART UNLESS LARGER CONDUCTOR SIZES ARE NOTED ON THE DRAWINGS.

5. FOR VA VALUES NOT SHOWN USE NEXT HIGHEST VALUE FROM THE CHART 120V BRANCH CIRCUIT

VOLT DROP CONDUCTOR LENGTH CHART XXXX XX

LOAD IN
VOLT

AMPERES
ABBREVIATION LIST @A
AC
A/C
AER
AF
AFF
AIC
AT
AWG
BC
BD
BFC
BRKR
BLDG
BPS C
C/B
CIRC
CLG
CO
CONT
CU
CWP
(D)
DC
DISC
DP
(E)
E/W
EA
EL
ELEC
EM
EMT
EOL
EQUIP
(ER)
EWC
EWH
(F)
FACP
FAEP
FATC
FBO
FLUOR
FT
GA
GFCI
GLZ
GND
GP
GYP
HID
HP
HT
HZ
IMC
IN
ISC
(RMS SYMMETRICAL)
ISO
J-BOX
KCMIL
KVA
KW
LC
LV
MCM
MECH
MDP
MH
MISC
MLO
MPOE
MSB
(N)
NIC
NIES
PLANS & SPECS.

NL
NO, #
NTS
OC.

OFOI P
PB
PFB

MOUNTING HARDWARE
PDZ
PFCT

TRANSFORMER
PH, Ø
PLYWD
PNL
PR
PVC
(R)
REQ'D
RM
RMC
(RR)
SDZ
SKZ
SPEC
STC
SQ
SW
TEL
TGB
BUSBAR
TMGB

GROUNDING BUSBAR
TTB
TYP
UG
UON V
WP
WT W
W/
XFMR &
AT
AMPERE

ALTERNATING CURRENT

AIR CONDITIONING

ARC ENERGY REDUCTION

AMP FRAME RATING OR

ABOVE FINISHED FLOOR

AMPERES INTERRUPTING CAPACITY

AMP TRIP SETTING

AMERICAN WIRE GAUGE

BARE COPPER
BOARD

BELOW FINISHED CEILING

BREAKER

BUILDING

BOOSTER POWER SUPPLY

CONDUIT

CIRCUIT BREAKER

CIRCUIT

CEILING

CONDUIT ONLY, WITH PULL LINE

CONTINUOUS
COPPER

METALLIC COLD WATER PIPE

DEMOLISH

DIRECT CURRENT

DISCONNECT

DISTRIBUTION PANEL

EXISTING

EACH WITH
EACH

EVENING LIGHT

ELECTRIC

EMERGENCY

ELECTRICAL METALLIC TUBING

END OF LINE DEVICE

EQUIPMENT

EXISTING RELOCATED

ELECTRICAL WATER COOLER

ELECTRIC WATER HEATER
FUTURE

FIRE ALARM CONTROL PANEL

FIRE ALARM EXTENDER PANEL

FIRE ALARM TERMINAL CABINET

FURNISHED BY OTHERS

FLUORESCENT
FOOT
GAUGE

GROUND FAULT CIRCUIT INTERRUPT

GENERAL LIGHTING ZONE
GROUND

METALLIC GAS PIPE
GYPSUM

HIGH INTENSITY DISCHARGE

HORSE POWER
HEIGHT
HERTZ

INTERMEDIATE METALLIC CONDUIT
INCH

SHORT CIRCUIT CURRENT

ISOLATED

JUNCTION BOX

THOUSAND CIRCULAR MILLS

KILO VOLT AMP

KILOWATT

LIGHTING CONTROL PANEL

LOW VOLTAGE

THOUSAND CIRCULAR MILLS

MECHANICAL

MAIN DISTRIBUTION PANEL

METAL HALIDE

MISCELLANEOUS

MAIN LUGS ONLY

MAIN POINT OF ENTRY

MAIN SWITCHBOARD
NEW

NOT IN CONTRACT

NOT IN ELECTRICAL SECTION OF THESE

NIGHT LIGHT
NUMBER

NOT TO SCALE

ON CENTER

OWNER FURNISHED, OWNER INSTALLED
POLE

PULL BOX

PROVISION FOR FUTURE BREAKER W/

PRIMARY DAYLIT ZONE

PROVISION FOR FUTURE CURRENT
PHASE

PLYWOOD
PANEL
PAIR

POLYVINYL CHLORIDE CONDUIT